Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 09:04:01
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 29620.02 | 639.46 | 639.46 |
Net Site Energy | 29620.02 | 639.46 | 639.46 |
Total Source Energy | 90115.53 | 1945.48 | 1945.48 |
Net Source Energy | 90115.53 | 1945.48 | 1945.48 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1050.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2710.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3715.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 673.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1941.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2335.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 346.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 906.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1882.48 |
Humidification | 4.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 721.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27848.02 | 1772.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4164.43 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1050.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2710.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3715.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 673.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2335.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 346.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 906.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1882.48 |
Humidification | General | 4.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 721.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1050.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2710.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3715.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 673.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1941.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2335.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 346.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 906.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1882.48 |
Humidification | Unassigned | 4.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 721.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.09 | 38.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Other | 370.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 601.20 | 38.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.09 | 38.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Other | 370.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 601.20 | 38.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 27848.021 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 27848.021 | 100.00 |
Total On-Site and Utility Electric Sources | 27848.021 | 100.00 |
Total Electricity End Uses | 27848.021 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 4164.43 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 4164.43 | 100.00 |
Total Water End Uses | 4164.43 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 15.50 |
Time Setpoint Not Met During Occupied Cooling | 161.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.3279 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.3279 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.3279 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.3279 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 9.3279 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.3279 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 9.3279 | 18.58 | 484.4232 | |
Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.8860 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:09 | 02-JAN-06:19 | - | - | - | - | - | - | - | - | - | - | 10-AUG-15:00 |
Heating | 0.00 | 1298390.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 399068.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84885.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 255194.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52321.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 80718.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1983009.31 | 1304086.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1298390.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 399068.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5451.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 255194.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 52321.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 80718.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1138.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8583.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11767.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2131.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6150.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7397.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1098.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2870.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 15.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 782.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 88194.68 | 1920.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 24.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 185.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 254.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 46.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 61.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1904.01 | 41.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 24.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 185.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 254.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 46.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 61.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1904.01 | 41.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.80 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.512494 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.90 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.497874 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.67 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.01 | 0.316327 | 0.321000 | 1.93 | 0.843538 | 0.500000 | 0.001204 | 0.000168 | 1.93 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 56.37 | 0.337428 | 0.335000 | 18.88 | 0.899808 | 0.500000 | 0.001129 | 0.003650 | 18.88 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.45 | 0.349105 | 0.355000 | 1.93 | 0.930947 | 0.500000 | 0.001091 | 0.000660 | 2.27 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.871700 | 0.273971 | 0.300000 | 0.261510 | 0.730590 | 0.500000 | 0.001391 | 0.000078 | 0.268428 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.19 | 0.129843 | 0.300000 | 0.355595 | 0.346248 | 0.500000 | 0.002934 | 0.000070 | 0.355595 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.67 | 0.142951 | 0.300000 | 0.501206 | 0.381202 | 0.500000 | 0.002665 | 0.000112 | 0.501206 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.43 | 0.107549 | 0.300000 | 0.429305 | 0.300000 | 0.500000 | 0.003543 | 0.000061 | 0.429305 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.98 | 0.299344 | 0.300000 | 2.39 | 0.798251 | 0.500000 | 0.001273 | 0.001706 | 5.90 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 12.21 | 0.126098 | 0.300000 | 3.66 | 0.336262 | 0.500000 | 0.003021 | 0.001132 | 3.92 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 17.09 | 0.139752 | 0.300000 | 5.13 | 0.372673 | 0.500000 | 0.002726 | 0.001695 | 5.86 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.80 | 0.120277 | 0.300000 | 3.84 | 0.320739 | 0.500000 | 0.003168 | 0.001072 | 3.84 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.892277 | 0.267653 | 0.300000 | 0.267683 | 0.713741 | 0.500000 | 0.001423 | 0.000224 | 0.774018 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.21 | 0.127309 | 0.300000 | 0.362672 | 0.339491 | 0.500000 | 0.002993 | 0.000148 | 0.510997 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.81 | 0.131998 | 0.300000 | 0.542792 | 0.351996 | 0.500000 | 0.002886 | 0.000222 | 0.768766 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.35 | 0.114318 | 0.300000 | 0.403885 | 0.304849 | 0.500000 | 0.003333 | 0.000141 | 0.488216 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19157.03 | 0.000168 | 386.19 |
CORE_MID VAV BOX REHEAT COIL | 417224.27 | 0.003650 | 9579.61 |
CORE_TOP VAV BOX REHEAT COIL | 75411.06 | 0.000660 | 1991.57 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8895.45 | 0.000078 | 234.89 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8024.97 | 0.000070 | 185.28 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12799.72 | 0.000112 | 306.21 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7007.68 | 0.000061 | 150.87 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 195061.42 | 0.001706 | 5144.67 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 129443.77 | 0.001132 | 3413.92 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 193692.76 | 0.001695 | 5108.61 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 122573.72 | 0.001072 | 3183.78 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 25570.31 | 0.000224 | 674.24 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16880.43 | 0.000148 | 445.10 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 25397.09 | 0.000222 | 669.68 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 16128.90 | 0.000141 | 425.29 |
VAV_BOT WITH REHEAT HEATING COIL | 52800.18 | 0.000462 | 872.91 |
VAV_MID WITH REHEAT HEATING COIL | 502194.78 | 0.004393 | 8279.57 |
VAV_TOP WITH REHEAT HEATING COIL | 47802.65 | 0.000418 | 797.56 |
CAV_BAS HEATING COIL | 282635.29 | 0.002473 | 6298.23 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.59 | 3.48 | 11.17 | 3.48 | 9.63 | 9.63 | 0.300000 | 0.361051 | 9.63 |
VAV_MID WITH REHEAT | 53.22 | 33.90 | 106.44 | 33.90 | 88.86 | 88.86 | 0.300000 | 0.381555 | 88.86 |
VAV_TOP WITH REHEAT | 5.35 | 3.51 | 10.71 | 4.82 | 9.71 | 9.71 | 0.300000 | 0.496102 | 9.71 |
CAV_BAS | 5.80 | 5.80 | 5.80 | 5.80 | 5.80 | 5.80 | 1.00 | 1.00 | 5.80 |
AIRLOOP DATACENTER BASEMENT | 21.67 | 21.67 | 21.67 | 21.67 | 21.67 | 21.67 | 1.00 | 0.999994 | 21.67 |
AIRLOOP DATACENTER BOT | 0.512494 | 0.512494 | 0.512494 | 0.512494 | 0.512494 | 0.512494 | 1.00 | 1.00 | 0.512494 |
AIRLOOP DATACENTER MID | 4.90 | 4.90 | 4.90 | 4.90 | 4.90 | 4.90 | 1.00 | 1.00 | 4.90 |
AIRLOOP DATACENTER TOP | 0.497874 | 0.497874 | 0.497874 | 0.497874 | 0.497874 | 0.497874 | 1.00 | 1.00 | 0.497874 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.63 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 88.86 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.71 | |
CAV_BAS_OA_CONTROLLER | 5.80 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.67 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.512494 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.90 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.497874 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.45 | 6.67 | 11.02 | 0.008831 | 0.008500 | 178023.96 | 0.007574 | 9.63 |
VAV_MID WITH REHEAT COOLING COIL | 25.59 | 6.67 | 11.02 | 0.008854 | 0.008500 | 1663742.00 | 0.070779 | 88.86 |
VAV_TOP WITH REHEAT COOLING COIL | 25.41 | 6.67 | 11.02 | 0.008827 | 0.008500 | 178908.15 | 0.007611 | 9.71 |
CAV_BAS COOLING COIL | 24.93 | 6.67 | 11.40 | 0.008940 | 0.008500 | 102703.41 | 0.004369 | 5.80 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.63 |
VAV_MID WITH REHEAT FAN | 88.86 |
VAV_TOP WITH REHEAT FAN | 9.71 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007574 | 0.000063 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000462 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.070779 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004393 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007611 | 0.000063 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000418 | |
CAV_BAS_COOLC_CONTROLLER | 0.004369 | 0.000109 |
CAV_BAS_HEATC_CONTROLLER | 0.002473 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.80 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.67 | 428635.78 | 307024.89 | 0.010497 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.512494 | 9907.08 | 7177.82 | 0.000243 |
AIRLOOP DATACENTER MID COOLING COIL | 4.90 | 94845.19 | 68699.03 | 0.002323 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.497874 | 9627.43 | 6974.00 | 0.000236 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.67 | 21.67 | 21.67 | 21.67 | 428635.78 | 428635.78 | 17840.03 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.512494 | 0.512494 | 0.512494 | 0.512494 | 9907.08 | 9907.08 | 824.14 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.90 | 4.90 | 4.90 | 4.90 | 94845.19 | 94845.19 | 8241.36 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.497874 | 0.497874 | 0.497874 | 0.497874 | 9627.43 | 9627.43 | 824.14 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.67 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.512494 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.90 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.497874 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.67 | 428635.78 | 0.010497 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.512494 | 9907.08 | 0.000243 |
AIRLOOP DATACENTER MID HEATING COIL | 4.90 | 94845.19 | 0.002323 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.497874 | 9627.43 | 0.000236 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 17840.03 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 824.14 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8241.36 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 824.14 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000144 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.090333 | 18614.36 | |
HEATSYS1 PUMP | 0.018885 | 5687.41 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.090333 | 10.84 |
HEATSYS1 | 0.018885 | 2.27 |
COOLSYS1_SUPPLY | 0.090333 | 10.84 |
SINGLE WATER PLANT LOOP | 0.013298 | 1.60 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.090333 | 0.090333 | 379174.56 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2158701.47 | 2158701.47 | 0.018885 |
CENTRAL BOILER | 547780.66 | 537089.69 | 0.013298 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.090333 | 12887.35 |
PLANT CIRC PUMP | 0.013298 | 3391.76 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.090333 | 0.045731 | 1077603.35 | 1082714.38 | 0.053580 |
COOLSYS1 CHILLER2 | 0.090333 | 0.045731 | 1077603.35 | 1082714.38 | 0.053580 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013298 | 139666.47 | 59253.35 | 69833.23 | 7879.72 | 21413.20 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.107159 | 12.86 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.107159 | 32273.97 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 42.01 | 1286228.76 | 8.40 | 160778.60 |
TOWERWATERSYS COOLTOWER 2 | 42.01 | 1286228.76 | 8.40 | 160778.60 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.055653 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.328 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 14.170 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 9.328 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.751 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 25926.330 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25926.330 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 7310.116 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7310.116 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.226 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.149 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.571 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6483 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7026 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4692 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.15847945E-14 | 0.40415870E-16 | -0.13570955E-09 | -0.55776231E-17 |
51 | 8 | 0.19900788E-07 | 0.16227319E-12 | 0.35673126E-03 | -0.22627880E-09 |
52 | 7 | -0.11611995E-01 | 0.86155623E-08 | -0.22179000E-01 | 0.13203260E-03 |
53 | 6 | 0.38824249 | 0.30290701E-05 | 0.45749374 | -0.45461023E-02 |
54 | 5 | -5.0235921 | 0.11413317E-03 | -4.3290265 | 0.61113495E-01 |
55 | 4 | 32.264180 | 0.94131685E-03 | 21.001374 | -0.41231550 |
56 | 3 | -109.65428 | 0.20665218E-02 | -54.756066 | 1.4924847 |
57 | 2 | 195.57288 | 0.11699747E-02 | 77.079281 | -2.8759721 |
58 | 1 | -170.58880 | 0.12564906E-03 | -55.024271 | 2.7354972 |
59 | 0 | 57.057407 | 0.71994484E-06 | 15.597457 | |
60 | 9 | 0.92194319E-15 | 0.45185080E-16 | -0.13934922E-09 | -0.37336789E-17 |
61 | 8 | 0.20414049E-07 | 0.15291409E-12 | 0.36227410E-03 | -0.23211478E-09 |
62 | 7 | -0.11777906E-01 | 0.80689916E-08 | -0.22418053E-01 | 0.13391908E-03 |
63 | 6 | 0.39275134 | 0.28300412E-05 | 0.46134659 | -0.45992504E-02 |
64 | 5 | -5.0676021 | 0.10641223E-03 | -4.3586752 | 0.61659190E-01 |
65 | 4 | 32.458904 | 0.87600040E-03 | 21.117392 | -0.41490080 |
66 | 3 | -110.06874 | 0.19199492E-02 | -54.985491 | 1.4984722 |
67 | 2 | 195.98384 | 0.10853975E-02 | 77.289466 | -2.8824978 |
68 | 1 | -170.74067 | 0.11640795E-03 | -55.084954 | 2.7381589 |
69 | 0 | 57.057407 | 0.66605595E-06 | 15.587079 | |
70 | 9 | 0.99499981E-15 | 0.49201796E-16 | -0.11918706E-09 | -0.33210447E-17 |
71 | 8 | 0.17565796E-07 | 0.20231051E-12 | 0.33086922E-03 | -0.19972915E-09 |
72 | 7 | -0.10835659E-01 | 0.11065463E-07 | -0.21059630E-01 | 0.12320537E-03 |
73 | 6 | 0.36714142 | 0.39371282E-05 | 0.43940598 | -0.42973741E-02 |
74 | 5 | -4.8175888 | 0.14987275E-03 | -4.1895891 | 0.58559222E-01 |
75 | 4 | 31.352470 | 0.12474171E-02 | 20.455190 | -0.40021127 |
76 | 3 | -107.71307 | 0.27606440E-02 | -53.675749 | 1.4644420 |
77 | 2 | 193.64724 | 0.15741070E-02 | 76.090603 | -2.8453956 |
78 | 1 | -169.87685 | 0.17016149E-03 | -54.740743 | 2.7230195 |
79 | 0 | 57.057407 | 0.98204117E-06 | 15.647518 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6638E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.6660E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3898E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3917E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5045E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5059E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9650E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9658E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7125E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.8593E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4319E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5637E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5399E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6440E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9845E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0341E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1319 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5411E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1515 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1004 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.3560E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1039E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1298E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4495E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7152E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.8728E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4347E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5780E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5421E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6523E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9850E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0355E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6636E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.6658E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3896E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3915E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5043E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5058E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9650E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9657E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6195E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9955E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4498E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8867E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0315E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1572E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3625E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3966E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2513E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7534E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9802E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5393E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3822E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3056E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2472E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5878E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4753E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5812E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2573E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3348E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9910E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0202E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3626E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3972E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2031E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2051E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8608E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8624E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6180E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6192E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9651E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9658E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2486E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3683E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8984E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9945E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6484E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7167E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9850E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0356E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.7022E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1593E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8655E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6418E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8477E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1236E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1298E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4491E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2474E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3660E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8971E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9916E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6467E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7114E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9846E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0341E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2030E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2050E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8607E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8623E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6179E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6191E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9650E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9657E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.3437E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4508E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0862E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1644E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9029E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9314E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3627E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3972E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0056E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6457E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6636E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4002E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2021E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2285E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2472E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5878E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4748E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8131E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2615E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.6489E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9423E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0641E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3624E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3966E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1247 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1028 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1386 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1187 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.9331E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.5491E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.7714E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.3115E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.0341E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7833E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.7415E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.5395E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.0932E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1950E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8823E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3360E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.3627E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0858E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4562E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4321E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4350E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8413E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7714E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3111E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7666E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6405E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.3965E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3543E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9001E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0985E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8823E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3360E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1245 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1029 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1384 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1188 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.9323E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.5591E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.7768E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.3160E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.0291E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7863E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.7375E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.5426E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.0943E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2003E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8875E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3404E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.3566E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0871E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4519E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4332E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4367E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8442E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7768E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3156E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7617E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6433E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.3927E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3571E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9012E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1036E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8875E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3404E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 79372.28585 | 79372.28585 | 5.79797 | 5.79797 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | -4.20000 | 2.69032E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 82323.38214 | 82323.38214 | 6.01291 | 6.01291 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 771957.61200 | 771957.61200 | 56.36890 | 56.36890 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 229801.15061 | 229801.15061 | 9.81730 | 10.77825 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 74620.32461 | 74620.32461 | 5.44834 | 5.44834 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 52831.90210 | 52831.90210 | 2.27494 | 2.27494 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11826.63825 | 11826.63825 | 0.87170 | 0.87170 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 6237.63755 | 6237.63755 | 0.26843 | 0.26843 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 16081.69739 | 16081.69739 | 1.18532 | 1.18532 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.81136E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 4503.12952 | 4503.12952 | 0.19397 | 0.19397 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 22666.91266 | 22666.91266 | 1.67069 | 1.67069 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 7833.50232 | 7833.50232 | 0.33768 | 0.33768 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19415.27610 | 19415.27610 | 1.43102 | 1.43102 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 28.08267 | 8.81938E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2762.26484 | 2762.26484 | 0.11848 | 0.11848 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 108241.88452 | 108241.88452 | 7.97813 | 7.97813 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 136565.54079 | 136565.54079 | 5.90143 | 5.90143 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 165592.92837 | 165592.92837 | 12.20518 | 12.20518 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 23.35067 | 8.81188E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 90622.82533 | 90622.82533 | 3.91648 | 3.91648 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 231856.46071 | 231856.46071 | 17.08922 | 17.08922 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 135608.77252 | 135608.77252 | 5.85993 | 5.85993 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 173607.28754 | 173607.28754 | 12.79588 | 12.79588 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.81889E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 84527.34443 | 84527.34443 | 3.65218 | 3.65218 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 12105.81988 | 12105.81988 | 0.89228 | 0.89228 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 17897.51927 | 17897.51927 | 0.77402 | 0.77402 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16401.74942 | 16401.74942 | 1.20891 | 1.20891 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 11815.01323 | 11815.01323 | 0.51100 | 0.51100 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 24547.63799 | 24547.63799 | 1.80931 | 1.80931 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 17776.41367 | 17776.41367 | 0.76877 | 0.76877 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18265.61937 | 18265.61937 | 1.34628 | 1.34628 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 11289.54426 | 11289.54426 | 0.48822 | 0.48822 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8815.59245 | 8815.59245 | 0.51249 | 0.51249 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.81585E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 84356.96175 | 84356.96175 | 4.90411 | 4.90411 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.81585E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8564.08645 | 8564.08645 | 0.49787 | 0.49787 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.81585E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372799.12034 | 372799.12034 | 21.67241 | 21.67241 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 19.93600 | 8.80655E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 02:10:00 | -4.20000 | 2.69032E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 142910.43 | 9.63233 | 9.63233 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 40480.51 | 1.99639 | 1.99639 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1316244.31 | 88.85774 | 88.85774 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 514437.00 | 30.10828 | 30.10828 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:40:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 146015.54 | 9.70956 | 9.70956 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 50965.57 | 4.81693 | 4.81693 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 |
7 | CAV_BAS | Cooling | Sensible | 75849.21 | 5.79797 | 5.79797 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 63272.12 | 1.20016 | 1.20016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 367609.03 | 21.67254 | 21.67254 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 17840.03 | 0.33839 | 0.33839 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8658.12 | 0.51249 | 0.51249 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 824.14 | 1.56323E-002 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 82841.00 | 4.90411 | 4.90411 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8241.36 | 0.15632 | 0.15632 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8410.50 | 0.49787 | 0.49787 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 824.14 | 1.56323E-002 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.79797 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.01291 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31633 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32100 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93014 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84354 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20445E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.67594E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.93014 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19157.02940 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.67594E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 386.19068 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 56.36890 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33743 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33500 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.88358 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89981 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12913E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.65006E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.88358 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 417224.27179 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.65006E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9579.61042 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.44834 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34910 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35500 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93416 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93095 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09136E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.59729E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.27494 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 75411.05862 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.59729E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1991.56679 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87170 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27397 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26151 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73059 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39066E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.78213E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26843 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8895.44704 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.78213E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 234.89299 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18532 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12984 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.35559 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34625 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.93431E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.02059E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35559 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8024.96526 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.02059E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 185.27540 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.67069 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14295 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.50121 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38120 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66525E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.11978E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50121 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12799.71718 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11978E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 306.20522 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43102 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10755 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42931 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.54256E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.13062E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42931 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7007.68073 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.13062E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 150.87269 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.97813 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29934 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.39344 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79825 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27278E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.70648E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.90143 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 195061.42264 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70648E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5144.66854 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.20518 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12610 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.66155 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33626 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.02146E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.13243E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.91648 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 129443.77067 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13243E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3413.92298 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.08922 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13975 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.12677 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37267 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.72625E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69451E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.85993 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 193692.75963 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69451E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5108.60561 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.79588 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12028 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.83876 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32074 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16769E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07233E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.83876 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 122573.71694 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07233E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3183.78319 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89228 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26765 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26768 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71374 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42349E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.23700E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.77402 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25570.30966 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.23700E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 674.24426 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.20891 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12731 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36267 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33949 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.99271E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.47677E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51100 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16880.42696 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47677E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 445.09799 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.80931 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13200 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.54279 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35200 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88640E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.22185E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76877 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25397.09359 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.22185E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 669.68026 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.34628 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11432 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40389 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30485 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33280E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.41103E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.48822 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16128.90388 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41103E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 425.29442 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51249 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.90411 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49787 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.67241 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.58581 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.47776 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.17163 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.47776 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.63233 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.63233 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.36105 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 53.21866 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 33.90411 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 106.43731 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 33.90411 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 88.85774 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 88.85774 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.38155 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.35256 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.51119 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.70512 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.81693 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.70956 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.70956 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.49610 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.79797 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.79797 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.79797 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.79797 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.79797 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.79797 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.67241 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.67241 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.67241 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.67241 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.67254 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.67254 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51249 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51249 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51249 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51249 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51249 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.51249 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.90411 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.90411 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.90411 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.90411 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.90411 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.90411 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49787 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49787 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49787 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49787 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49787 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.49787 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.63233 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 88.85774 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.70956 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.79797 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.67254 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.51249 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.90411 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.49787 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.63233 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.44573 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01737 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.83130E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 178023.96137 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.57355E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.63233 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 52800.17526 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.61919E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 872.91096 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.63233 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.57355E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.28755E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.61919E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 88.85774 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.58739 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01744 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.85447E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1663742.00313 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.07794E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 88.85774 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 502194.78253 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.39342E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8279.57453 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 88.85774 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.07794E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.72781E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.39342E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.70956 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.41108 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01735 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82668E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 178908.14695 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.61117E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.70956 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 47802.65150 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.18198E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 797.55573 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.70956 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.61117E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.25647E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.18198E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.79797 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.92533 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.40148 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.93976E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 102703.40854 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.36924E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.79797 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 282635.29126 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.47262E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6298.23434 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.79797 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.36924E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.08987E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.47262E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.67254 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.67254 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 428635.77654 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 307024.88642 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04973E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.67254 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.67254 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.67254 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.67254 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 428635.77654 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 428635.77654 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 17840.03233 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.67254 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.67254 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 428635.77654 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04973E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 17840.03233 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.43976E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51249 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51249 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9907.08490 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7177.82380 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42624E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.51249 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.51249 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.51249 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.51249 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9907.08490 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9907.08490 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.13559 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51249 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51249 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9907.08490 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42624E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 824.13559 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.90411 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.90411 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 94845.18627 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 68699.02881 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32275E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.90411 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.90411 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.90411 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.90411 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 94845.18627 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 94845.18627 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8241.35587 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.90411 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.90411 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 94845.18627 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32275E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8241.35587 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49787 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49787 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9627.43468 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6973.99806 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35775E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49787 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49787 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49787 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49787 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9627.43468 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9627.43468 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.13559 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49787 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49787 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9627.43468 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35775E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 824.13559 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.03334E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 18614.36326 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.03334E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.84001 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.03334E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.03334E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 379174.55714 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.88853E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.26623 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.88853E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 5687.41163 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2158701.47452 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2158701.47000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.88853E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.03334E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.84001 |
451 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 9.03334E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 12887.35159 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.03334E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.57314E-002 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1077603.35357 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1082714.37500 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.35795E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.03334E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.57314E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1077603.35357 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1082714.37500 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.35795E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.32984E-002 |
464 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.59581 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.32984E-002 |
466 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3391.76065 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.32984E-002 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59253.35237 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21413.19787 |
473 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 547780.65767 |
474 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 537089.69000 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.32984E-002 |
476 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
477 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
479 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
480 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
481 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10716 |
482 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.85909 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10716 |
484 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 32273.97163 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 42.01268 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1286228.76243 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.40254 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 160778.59530 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 42.01268 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1286228.76243 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.40254 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 160778.59530 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.56525E-002 |
494 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.56525E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18164.78 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 395328.47 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 71467.06 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8430.01 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7603.62 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12125.78 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6642.24 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 184814.20 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 122642.95 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 183517.68 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 116073.83 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 24225.93 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15992.86 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 24061.84 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15280.93 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 41013.22 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 387906.01 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 37826.47 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 224237.09 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 224113.70 | 158133.84 | 65979.86 | 0.71 | 23293.10 | 236.25 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2078473.46 | 1463718.27 | 614755.19 | 0.70 | 215631.23 | 2187.05 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 225609.25 | 159264.51 | 66344.74 | 0.71 | 23455.45 | 237.90 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 130636.47 | 93030.24 | 37606.23 | 0.71 | 13359.50 | 135.50 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.1825120324 | 0.2028678264 | Pass | Pass | 1.2462211735 | 7.3219142293 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 1.3358954202E-003 | 1.7352243275E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.3314377150E-003 | 2.4187284046E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.2473646882E-002 | 1.2852108495E-002 | Pass | Pass | 0.6043272106 | 1.3456894538 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.4750295691E-002 | 1.2847456334E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.5803601548E-002 | 1.4165987443E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.4084706584E-002 | 1.4509870869E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.5143746197E-002 | 1.3276059877E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.8865830615E-002 | 1.4960710402E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.9758795310E-002 | 1.6536103202E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.9692509043E-002 | 1.7609478661E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.0294238526E-002 | 1.6068580124E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2658051928 | 0.2562892451 | Pass | Pass | 7.8665650332 | 21.4329795397 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2710298099 | 0.2651228249 | Pass | Pass | 5.2251846708 | 13.8293624590 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2555177118 | 0.2525427567 | Pass | Pass | 5.2890043923 | 13.9266518585 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1606645959 | 0.1730482638 | Pass | Pass | 6.1110603093 | 17.4512969902 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.1165369594E-003 | 4.3166712647E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.1004502737E-003 | 5.1403533601E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.8802516385E-002 | 5.9952356731E-002 | Pass | Pass | 0.4679501366 | 0.4734198929 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.2750276446E-006 | 7.7857927154E-006 | Pass | Pass | 1.3050789970E-003 | 1.1545951161E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.5614330440E-003 | 3.6235949240E-003 | Pass | Pass | 1.4477129201E-003 | 1.2385322680E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.4019115696E-003 | 3.7207570048E-003 | Pass | Pass | 1.9262894761E-003 | 1.3708501802E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.4970201088E-006 | 1.2067288394E-005 | Pass | Pass | 2.7444606568E-005 | 1.1045331663E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5987.48 | 192.27 | 0.00 | 23694.78 | 16556.25 | 46430.79 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 1043.06 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.171 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.3279 | 2779.43 | 25926.33 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 240.45 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.3279 | 24961.20 | 232836.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 2159.39 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.50 | 0.0000 | Y | 18.93 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.38 | 0.0000 | Y | 12.16 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.20 | 0.0000 | Y | 18.77 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.34 | 0.0000 | Y | 12.14 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.3279 | 3134.13 | 29234.97 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.54 | 0.0000 | Y | 189.53 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.39 | 0.0000 | Y | 121.63 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.3279 | 3134.20 | 29235.61 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.23 | 0.0000 | Y | 187.84 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.35 | 0.0000 | Y | 121.49 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.54 | 0.0000 | Y | 18.95 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.39 | 0.0000 | Y | 12.16 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.23 | 0.0000 | Y | 18.78 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.35 | 0.0000 | Y | 12.15 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 9.3279 | 783.68 | 7310.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 67.80 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 16.0861 | 362.03 | 5823.61 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 59.65 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
Interior Lighting Total | 9.3913 | 46320.38 | 435009.77 | 1160.06 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.01 | AstronomicalClock | - | 42.59 | 42.59 | 79.73 | |
EXTERIOR_LIGHTS_B | 44362.79 | AstronomicalClock | - | 83.55 | 71.26 | 593.42 | |
Exterior Lighting Total | 54335.80 | 673.15 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2118494.38 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2158701.47 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1082714.38 | 6.28 | 1036299.56 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1082714.38 | 6.28 | 1036299.56 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 537089.69 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1286228.76 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1286228.76 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 178023.96 | 224113.70 | 158133.84 | 65979.86 | 0.71 | - | 23293.10 | 236.25 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1663742.00 | 2078473.46 | 1463718.27 | 614755.19 | 0.70 | - | 215631.23 | 2187.05 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 178908.15 | 225609.25 | 159264.51 | 66344.74 | 0.71 | - | 23455.45 | 237.90 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 102703.41 | 130636.47 | 93030.24 | 37606.23 | 0.71 | - | 13359.50 | 135.50 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 428635.78 | 307024.89 | 121610.89 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9907.08 | 7177.82 | 2729.26 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 94845.19 | 68699.03 | 26146.16 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9627.43 | 6974.00 | 2653.44 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19157.03 | 18164.78 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 417224.27 | 395328.47 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 75411.06 | 71467.06 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 8895.45 | 8430.01 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 8024.97 | 7603.62 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12799.72 | 12125.78 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7007.68 | 6642.24 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 195061.42 | 184814.20 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 129443.77 | 122642.95 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 193692.76 | 183517.68 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 122573.72 | 116073.83 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 25570.31 | 24225.93 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 16880.43 | 15992.86 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25397.09 | 24061.84 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 16128.90 | 15280.93 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 52800.18 | 41013.22 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 502194.78 | 387906.01 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 47802.65 | 37826.47 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 282635.29 | 224237.09 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 428635.78 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9907.08 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 94845.19 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9627.43 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 17840.03 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 824.14 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8241.36 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 824.14 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.63 | 20814.94 | 2160.95 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 88.86 | 192016.83 | 2160.95 | 1.00 | 1.08 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.71 | 20981.84 | 2160.95 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.80 | 9831.35 | 1695.65 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 21.67 | 35743.38 | 1649.25 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 574.05 | 1120.11 | 1.00 | 1.59 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.90 | 5493.14 | 1120.11 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 557.67 | 1120.11 | 1.00 | 1.61 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.090333 | 18614.36 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.018885 | 5687.41 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.090333 | 12887.35 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013298 | 3391.76 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.107159 | 32273.97 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 79372.29 | 79372.29 | 28.56 | 5.798 | 5.798 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 21.70 | 0.00881 | 1.200 | 0.00 |
CORE_BOTTOM | 82323.38 | 82323.38 | 32.98 | 6.013 | 6.013 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 21.70 | 0.00881 | 1.078 | 0.00 |
CORE_MID | 771957.61 | 771957.61 | 309.26 | 56.369 | 56.369 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 21.70 | 0.00881 | 10.778 | 0.00 |
CORE_TOP | 74620.32 | 74620.32 | 29.89 | 5.448 | 5.448 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 21.70 | 0.00881 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11826.64 | 11826.64 | 37.74 | 0.872 | 0.872 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00882 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 16081.70 | 16081.70 | 79.62 | 1.185 | 1.185 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00866 | 23.02 | 0.00881 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 22666.91 | 22666.91 | 72.32 | 1.671 | 1.671 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00867 | 29.05 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19415.28 | 19415.28 | 96.13 | 1.431 | 1.431 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 24.00 | 24.00 | 0.00863 | 28.08 | 0.00882 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 108241.88 | 108241.88 | 345.37 | 7.978 | 7.978 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00885 | 29.40 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 165592.93 | 165592.93 | 819.87 | 12.205 | 12.205 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00865 | 23.35 | 0.00881 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 231856.46 | 231856.46 | 739.76 | 17.089 | 17.089 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00867 | 29.14 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 173607.29 | 173607.29 | 859.55 | 12.796 | 12.796 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00865 | 27.77 | 0.00882 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12105.82 | 12105.82 | 38.63 | 0.892 | 0.892 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00882 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16401.75 | 16401.75 | 81.21 | 1.209 | 1.209 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00866 | 23.68 | 0.00881 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 24547.64 | 24547.64 | 78.32 | 1.809 | 1.809 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00866 | 29.23 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18265.62 | 18265.62 | 90.43 | 1.346 | 1.346 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00864 | 27.94 | 0.00882 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8815.59 | 8815.59 | 243.51 | 0.512 | 0.512 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00858 | 25.86 | 0.00882 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 84356.96 | 84356.96 | 2330.13 | 4.904 | 4.904 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 25.86 | 0.00882 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8564.09 | 8564.09 | 236.56 | 0.498 | 0.498 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00858 | 25.86 | 0.00882 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372799.12 | 372799.12 | 475.70 | 21.672 | 21.672 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 19.94 | 0.00881 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | 21.00 | 24.40 | 0.00269 | -4.20 | 0.00269 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 19.60 | 21.97 | 0.00269 | -4.20 | 0.00269 | 1.078 | 0.00 |
CORE_MID | 229801.15 | 229801.15 | 92.06 | 9.817 | 10.778 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 10.778 | 0.00 |
CORE_TOP | 52831.90 | 52831.90 | 21.17 | 2.275 | 2.275 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 6237.64 | 6237.64 | 19.90 | 0.268 | 0.268 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00685 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 4503.13 | 4503.13 | 22.30 | 0.194 | 0.194 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00700 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 7833.50 | 7833.50 | 24.99 | 0.338 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00722 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2762.26 | 2762.26 | 13.68 | 0.118 | 0.118 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00618 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 136565.54 | 136565.54 | 435.74 | 5.901 | 5.901 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00743 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 90622.83 | 90622.83 | 448.68 | 3.916 | 3.916 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00743 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 135608.77 | 135608.77 | 432.67 | 5.860 | 5.860 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00742 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 84527.34 | 84527.34 | 418.50 | 3.652 | 3.652 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00738 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17897.52 | 17897.52 | 57.11 | 0.774 | 0.774 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 11815.01 | 11815.01 | 58.50 | 0.511 | 0.511 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 17776.41 | 17776.41 | 56.72 | 0.769 | 0.769 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 11289.54 | 11289.54 | 55.90 | 0.488 | 0.488 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00746 | -4.20 | 0.00269 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 18.00 | 26.52 | 0.00850 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.29 | 0.00506 | -4.20 | 0.00269 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.61 | 0.00310 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 02:10:00 | 18.00 | 27.00 | 0.00850 | -4.20 | 0.00269 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.63 | 9.63 | 2.00 | 2.00 | 9.6323 | 3.4778 | 9.6323 | 0.3611 | 0.3000 |
VAV_MID WITH REHEAT | 88.86 | 88.86 | 30.11 | 30.11 | 88.8577 | 33.9041 | 88.8577 | 0.3816 | 0.3000 |
VAV_TOP WITH REHEAT | 9.71 | 9.71 | 4.82 | 4.82 | 9.7096 | 4.8169 | 9.7096 | 0.4961 | 0.3000 |
CAV_BAS | 5.80 | 5.80 | 1.20 | 1.20 | 5.7980 | 5.7980 | 5.7980 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.67 | 21.67 | 0.34 | 0.34 | 21.6725 | 21.6724 | 21.6725 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.51 | 0.51 | 0.02 | 0.02 | 0.5125 | 0.5125 | 0.5125 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.90 | 4.90 | 0.16 | 0.16 | 4.9041 | 4.9041 | 4.9041 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.50 | 0.50 | 0.02 | 0.02 | 0.4979 | 0.4979 | 0.4979 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19157.029 | 19157.029 | 1.930144 | 0.00016759 | 386.191 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 19157.03 | 19157.03 | 1.930144 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 19227.67 | 19227.67 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 417224.272 | 417224.272 | 18.883582 | 0.00365006 | 9579.610 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 417224.27 | 417224.27 | 18.883582 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 229801.15 | 0.00 | 418610.20 | 418610.20 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 75411.059 | 75411.059 | 2.274936 | 0.00065973 | 1991.567 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 75411.06 | 75411.06 | 2.274936 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 52831.90 | 0.00 | 75678.43 | 75678.43 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8895.447 | 8895.447 | 0.268428 | 0.00007782 | 234.893 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8895.45 | 8895.45 | 0.268428 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00685379 | 43.7619 | 6237.64 | 0.00 | 8926.76 | 8926.76 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8024.965 | 8024.965 | 0.355595 | 0.00007021 | 185.275 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8024.97 | 8024.97 | 0.355595 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00699754 | 44.6693 | 4503.13 | 0.00 | 8051.53 | 8051.53 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 12799.717 | 12799.717 | 0.501206 | 0.00011198 | 306.205 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12799.72 | 12799.72 | 0.501206 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00721842 | 46.0621 | 7833.50 | 0.00 | 12841.29 | 12841.29 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7007.681 | 7007.681 | 0.429305 | 0.00006131 | 150.873 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7007.68 | 7007.68 | 0.429305 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00617799 | 39.4896 | 2762.26 | 0.00 | 7032.19 | 7032.19 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 195061.423 | 195061.423 | 5.901430 | 0.00170648 | 5144.669 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 195061.42 | 195061.42 | 5.901430 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00742903 | 47.3906 | 136565.54 | 0.00 | 195704.16 | 195704.16 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 129443.771 | 129443.771 | 3.916485 | 0.00113243 | 3413.923 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 129443.77 | 129443.77 | 3.916485 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00743250 | 47.4125 | 90622.83 | 0.00 | 129869.53 | 129869.53 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 193692.760 | 193692.760 | 5.859935 | 0.00169451 | 5108.606 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 193692.76 | 193692.76 | 5.859935 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00742402 | 47.3591 | 135608.77 | 0.00 | 194331.24 | 194331.24 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 122573.717 | 122573.717 | 3.838764 | 0.00107233 | 3183.783 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 122573.72 | 122573.72 | 3.838764 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00737948 | 47.0786 | 84527.34 | 0.00 | 122949.02 | 122949.02 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 25570.310 | 25570.310 | 0.774018 | 0.00022370 | 674.244 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25570.31 | 25570.31 | 0.774018 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00748578 | 47.7490 | 17897.52 | 0.00 | 25653.39 | 25653.39 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 16880.427 | 16880.427 | 0.510997 | 0.00014768 | 445.098 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16880.43 | 16880.43 | 0.510997 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00748211 | 47.7260 | 11815.01 | 0.00 | 16935.21 | 16935.21 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 25397.094 | 25397.094 | 0.768766 | 0.00022218 | 669.680 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25397.09 | 25397.09 | 0.768766 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00748236 | 47.7274 | 17776.41 | 0.00 | 25479.64 | 25479.64 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 16128.904 | 16128.904 | 0.488216 | 0.00014110 | 425.294 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16128.90 | 16128.90 | 0.488216 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00745825 | 47.5757 | 11289.54 | 0.00 | 16181.34 | 16181.34 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 178023.961 | -999.000 | 9.632326 | 0.00757355 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 178023.96 | 168135.52 | 9.632326 | 25.45 | 17.03 | 0.00883130 | 11.02 | 11.02 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 26.3507 | 24.00 | 0.00883488 | 46.8590 | 128546.37 | 0.00 | 180094.11 | 158678.12 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 52800.175 | 52800.175 | 2.889698 | 0.00046192 | 872.911 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 52800.18 | 52800.18 | 2.889698 | -2.52 | -2.80 | 0.00292767 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 87.8358 | 21.43 | 0.00510362 | 31.8136 | 21336.53 | 0.00 | 49621.60 | 49621.60 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1663742.003 | -999.000 | 88.857736 | 0.07077943 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1663742.00 | 1566161.80 | 88.857736 | 25.59 | 17.09 | 0.00885447 | 11.02 | 11.02 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 28.5647 | 24.00 | 0.00886821 | 47.0333 | 1170830.20 | 0.00 | 1682270.31 | 1478967.05 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 502194.783 | 502194.783 | 26.657321 | 0.00439342 | 8279.575 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 502194.78 | 502194.78 | 26.657321 | -2.99 | -3.08 | 0.00292548 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 95.2157 | 21.00 | 0.00752810 | 48.0127 | 487649.57 | 0.00 | 469315.72 | 469315.72 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 178908.147 | -999.000 | 9.709561 | 0.00761117 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 178908.15 | 169078.79 | 9.709561 | 25.41 | 17.01 | 0.00882668 | 11.02 | 11.02 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 26.1411 | 24.00 | 0.00882852 | 46.8257 | 131700.22 | 0.00 | 180991.63 | 159535.22 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 47802.652 | 47802.652 | 2.912868 | 0.00041820 | 797.556 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 47802.65 | 47802.65 | 2.912868 | -0.96 | -1.30 | 0.00331346 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 87.1371 | 19.80 | 0.00750260 | 51.5284 | 54061.61 | 0.00 | 45772.20 | 45772.20 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 102703.409 | -999.000 | 5.797971 | 0.00436924 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 102703.41 | 95004.68 | 5.797971 | 24.93 | 16.94 | 0.00893976 | 11.40 | 11.39 | 0.00850000 | 28.05 | 0.00881933 | 17.90 | 20.6996 | 24.00 | 0.00897549 | 47.5946 | 71152.89 | 0.00 | 103893.87 | 90423.38 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 282635.291 | 282635.291 | 5.797971 | 0.00247262 | 6298.234 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 282635.29 | 282635.29 | 5.797971 | -0.87 | -2.23 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.6996 | 24.46 | 0.00269032 | 14.0189 | 0.00 | 0.00 | 236932.53 | 236932.53 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 428635.777 | 307024.886 | 21.672544 | 0.01049726 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 398737.62 | 396037.01 | -999.0 | 28.45 | 17.81 | 0.00854651 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | -999.0000 | 27.00 | 0.00854214 | 37.9331 | 372397.79 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9907.085 | 7177.824 | 0.512494 | 0.00024262 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9180.64 | 9058.43 | -999.0 | 27.92 | 17.67 | 0.00858923 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00881585 | 17.16 | -999.0000 | 27.00 | 0.00858210 | 38.1056 | 8815.59 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94845.186 | 68699.029 | 4.904113 | 0.00232275 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 87896.89 | 86676.34 | -999.0 | 27.92 | 17.67 | 0.00859312 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00881585 | 17.16 | -999.0000 | 27.00 | 0.00858579 | 38.1219 | 84356.96 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9627.435 | 6973.998 | 0.497874 | 0.00023578 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8921.93 | 8799.71 | -999.0 | 27.92 | 17.67 | 0.00859184 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00881585 | 17.16 | -999.0000 | 27.00 | 0.00858458 | 38.1165 | 8564.09 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 428635.777 | 428635.777 | 21.672544 | 0.01049726 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 428635.78 | 428635.78 | 21.672544 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5614 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9907.085 | 9907.085 | 0.512494 | 0.00024262 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9907.08 | 9907.08 | 0.512494 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.0502 | 26.84 | 0.00850000 | 38.0914 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94845.186 | 94845.186 | 4.904113 | 0.00232275 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 94845.19 | 94845.19 | 4.904113 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1876 | 24.49 | 0.00505638 | 26.1957 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9627.435 | 9627.435 | 0.497874 | 0.00023578 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9627.43 | 9627.43 | 0.497874 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1398 | 23.39 | 0.00310467 | 17.2388 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 17840.032 | 17840.032 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17840.03 | 17840.03 | 21.672544 | -0.07 | -0.07 | 0.00840929 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5614 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.14 | 824.14 | 0.512494 | -0.13 | -0.13 | 0.00832279 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.0502 | 26.84 | 0.00850000 | 38.0914 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8241.356 | 8241.356 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8241.36 | 8241.36 | 4.904113 | -0.13 | -0.13 | 0.00498096 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1876 | 24.49 | 0.00505638 | 26.1957 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.14 | 824.14 | 0.497874 | -0.13 | -1.19 | 0.00309166 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1398 | 23.39 | 0.00310467 | 17.2388 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19157.029 | 19157.029 | 1.930144 | 0.00016759 | 386.191 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 0.8699 | 0.887433 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | Sensible | 19157.03 | 19157.03 | 1.0000 | 2.29106259 | 1.930144 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.16757695 | 60.00 | 32.22 | 27.78 | 0.000 | 19157.03 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 19227.67 | 19227.67 | 2.29106259 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 417224.272 | 417224.272 | 18.883582 | 0.00365006 | 9579.610 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 18.9463 | 19.327558 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 417224.27 | 417224.27 | 1.0000 | 22.41463817 | 18.883582 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 3.64968759 | 60.00 | 32.22 | 27.78 | 0.000 | 417224.27 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.88 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 229801.15 | 0.00 | 418610.20 | 418610.20 | 22.41463817 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.11 | 18.41 | 0.00800000 | 51735.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 75411.059 | 75411.059 | 2.274936 | 0.00065973 | 1991.567 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 3.4244 | 3.493353 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 75411.06 | 75411.06 | 1.0000 | 2.70032789 | 2.274936 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.65966154 | 60.00 | 32.22 | 27.78 | 0.000 | 75411.06 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 52831.90 | 0.00 | 75678.43 | 75678.43 | 2.70032789 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.28 | 21.27 | 0.00800000 | 61085.5 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8895.447 | 8895.447 | 0.268428 | 0.00007782 | 234.893 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 0.4039 | 0.412074 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8895.45 | 8895.45 | 1.0000 | 0.31862112 | 0.268428 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.07781331 | 60.00 | 32.22 | 27.78 | 0.000 | 8895.45 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00685379 | 21.00 | 0.00685379 | 43.7619 | 6237.64 | 0.00 | 8926.76 | 8926.76 | 0.31862112 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.28 | 21.26 | 0.00800000 | 61076.7 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8024.965 | 8024.965 | 0.355595 | 0.00007021 | 185.275 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 0.3644 | 0.371750 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8024.97 | 8024.97 | 1.0000 | 0.42208756 | 0.355595 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.07019874 | 60.00 | 32.22 | 27.78 | 0.000 | 8024.97 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00699754 | 21.00 | 0.00699754 | 44.6693 | 4503.13 | 0.00 | 8051.53 | 8051.53 | 0.42208756 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.51 | 18.54 | 0.00800000 | 52135.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12799.717 | 12799.717 | 0.501206 | 0.00011198 | 306.205 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 0.5812 | 0.592936 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12799.72 | 12799.72 | 1.0000 | 0.59492677 | 0.501206 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.11196609 | 60.00 | 32.22 | 27.78 | 0.000 | 12799.72 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00721842 | 21.00 | 0.00721842 | 46.0621 | 7833.50 | 0.00 | 12841.29 | 12841.29 | 0.59492677 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.97 | 19.33 | 0.00800000 | 54644.5 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7007.681 | 7007.681 | 0.429305 | 0.00006131 | 150.873 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 0.3182 | 0.324625 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7007.68 | 7007.68 | 1.0000 | 0.50958117 | 0.429305 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06129999 | 60.00 | 32.22 | 27.78 | 0.000 | 7007.68 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00617799 | 21.00 | 0.00617799 | 39.4896 | 2762.26 | 0.00 | 7032.19 | 7032.19 | 0.50958117 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.33 | 16.78 | 0.00800000 | 46859.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 195061.423 | 195061.423 | 5.901430 | 0.00170648 | 5144.669 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 8.8578 | 9.036054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 195061.42 | 195061.42 | 1.0000 | 7.00494325 | 5.901430 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.70630834 | 60.00 | 32.22 | 27.78 | 0.000 | 195061.42 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00742903 | 21.00 | 0.00742903 | 47.3906 | 136565.54 | 0.00 | 195704.16 | 195704.16 | 7.00494325 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60997.8 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 129443.771 | 129443.771 | 3.916485 | 0.00113243 | 3413.923 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 5.8781 | 5.996372 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 129443.77 | 129443.77 | 1.0000 | 4.64883141 | 3.916485 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.13231505 | 60.00 | 32.22 | 27.78 | 0.000 | 129443.77 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00743250 | 21.00 | 0.00743250 | 47.4125 | 90622.83 | 0.00 | 129869.53 | 129869.53 | 4.64883141 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60995.8 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 193692.760 | 193692.760 | 5.859935 | 0.00169451 | 5108.606 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 8.7956 | 8.972651 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 193692.76 | 193692.76 | 1.0000 | 6.95568829 | 5.859935 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.69433590 | 60.00 | 32.22 | 27.78 | 0.000 | 193692.76 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00742402 | 21.00 | 0.00742402 | 47.3591 | 135608.77 | 0.00 | 194331.24 | 194331.24 | 6.95568829 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60998.3 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 122573.717 | 122573.717 | 3.838764 | 0.00107233 | 3183.783 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 5.5661 | 5.678123 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 122573.72 | 122573.72 | 1.0000 | 4.55657762 | 3.838764 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.07221896 | 60.00 | 32.22 | 27.78 | 0.000 | 122573.72 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00737948 | 21.00 | 0.00737948 | 47.0786 | 84527.34 | 0.00 | 122949.02 | 122949.02 | 4.55657762 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.26 | 20.96 | 0.00800000 | 60042.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25570.310 | 25570.310 | 0.774018 | 0.00022370 | 674.244 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 1.1612 | 1.184523 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25570.31 | 25570.31 | 1.0000 | 0.91875207 | 0.774018 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.22367740 | 60.00 | 32.22 | 27.78 | 0.000 | 25570.31 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00748578 | 21.00 | 0.00748578 | 47.7490 | 17897.52 | 0.00 | 25653.39 | 25653.39 | 0.91875207 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16880.427 | 16880.427 | 0.510997 | 0.00014768 | 445.098 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 0.7665 | 0.781971 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16880.43 | 16880.43 | 1.0000 | 0.60654859 | 0.510997 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.14766227 | 60.00 | 32.22 | 27.78 | 0.000 | 16880.43 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00748211 | 21.00 | 0.00748211 | 47.7260 | 11815.01 | 0.00 | 16935.21 | 16935.21 | 0.60654859 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.4 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25397.094 | 25397.094 | 0.768766 | 0.00022218 | 669.680 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 1.1533 | 1.176499 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25397.09 | 25397.09 | 1.0000 | 0.91251820 | 0.768766 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.22216219 | 60.00 | 32.22 | 27.78 | 0.000 | 25397.09 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00748236 | 21.00 | 0.00748236 | 47.7274 | 17776.41 | 0.00 | 25479.64 | 25479.64 | 0.91251820 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.2 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16128.904 | 16128.904 | 0.488216 | 0.00014110 | 425.294 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 0.7324 | 0.747158 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16128.90 | 16128.90 | 1.0000 | 0.57950795 | 0.488216 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.14108829 | 60.00 | 32.22 | 27.78 | 0.000 | 16128.90 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00745825 | 21.00 | 0.00745825 | 47.5757 | 11289.54 | 0.00 | 16181.34 | 16181.34 | 0.57950795 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.4 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 178023.961 | -999.000 | 9.632326 | 0.00757355 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2569 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.632326 | 11.43348231 | 4197.9300 | 999.8980 | 90.32417338 | 12.27 | 6.67 | 5.60 | 2123377.52 | 8.3840 | 8.384000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 178023.96 | 168135.52 | 1.0000 | 11.43348231 | 9.632326 | 25.45 | 17.03 | 0.00883130 | 48073.2 | 11.02 | 11.02 | 0.00850000 | 32502.8 | 7.57277827 | 6.67 | 12.27 | 5.60 | 20814.944 | 157209.02 | 29.40 | 0.00882150 | 18.34 | 2.53819000 | 26.3507 | 24.00 | 0.00883488 | 24.00 | 0.00883488 | 46.8590 | 128546.37 | 0.00 | 180094.11 | 158678.12 | 11.43348231 | 25.45 | 17.18 | 0.00883130 | 48073.2 | 11.86 | 11.29 | 0.00808888 | 32321.7 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 52800.175 | 52800.175 | 2.889698 | 0.00046192 | 872.911 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.632326 | 11.43348231 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 2.3977 | 2.445923 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 52800.18 | 52800.18 | 1.0000 | 3.43004469 | 2.889698 | -2.52 | -2.80 | 0.00292767 | 4777.0 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.46187185 | 60.00 | 32.22 | 27.78 | 0.000 | 52800.18 | -4.20 | 0.00269032 | -4.20 | 2.53819000 | 87.8358 | 9.62 | 0.00464152 | 21.43 | 0.00510362 | 31.8136 | 21336.53 | 0.00 | 49621.60 | 49621.60 | 3.43004469 | 2.80 | 0.42 | 0.00292767 | 10150.7 | 17.12 | 7.99 | 0.00292767 | 24617.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1663742.003 | -999.000 | 88.857736 | 0.07077943 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3000 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 88.857736 | 105.47331317 | 4197.9300 | 999.8980 | 90.32417338 | 12.27 | 6.67 | 5.60 | 2123377.52 | 78.3536 | 78.353566 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1663742.00 | 1566161.80 | 1.0000 | 105.47331317 | 88.857736 | 25.59 | 17.09 | 0.00885447 | 48276.9 | 11.02 | 11.02 | 0.00850000 | 32502.8 | 70.77221065 | 6.67 | 12.27 | 5.60 | 192016.835 | 1471725.17 | 29.40 | 0.00882150 | 18.34 | 25.38195000 | 28.5647 | 24.00 | 0.00886821 | 24.00 | 0.00886821 | 47.0333 | 1170830.20 | 0.00 | 1682270.31 | 1478967.05 | 105.47331317 | 25.59 | 17.24 | 0.00885447 | 48276.9 | 11.86 | 11.29 | 0.00809048 | 32327.2 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 502194.783 | 502194.783 | 26.657321 | 0.00439342 | 8279.575 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 88.857736 | 105.47331317 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 22.8048 | 23.263744 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 502194.78 | 502194.78 | 1.0000 | 31.64199395 | 26.657321 | -2.99 | -3.08 | 0.00292548 | 4291.3 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 4.39297086 | 60.00 | 32.22 | 27.78 | 0.000 | 502194.78 | -4.20 | 0.00269032 | -4.20 | 25.38195000 | 95.2157 | 21.00 | 0.00760562 | 21.00 | 0.00752810 | 48.0127 | 487649.57 | 0.00 | 469315.72 | 469315.72 | 31.64199395 | 2.80 | 0.41 | 0.00292548 | 10145.2 | 17.48 | 8.15 | 0.00292548 | 24977.3 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 178908.147 | -999.000 | 9.709561 | 0.00761117 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2484 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.709561 | 11.52515962 | 4197.9300 | 999.8980 | 90.32417338 | 12.27 | 6.67 | 5.60 | 2123377.52 | 8.4256 | 8.425640 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 178908.15 | 169078.79 | 1.0000 | 11.52515962 | 9.709561 | 25.41 | 17.01 | 0.00882668 | 48026.0 | 11.02 | 11.02 | 0.00850000 | 32502.8 | 7.61038974 | 6.67 | 12.27 | 5.60 | 20981.845 | 157926.30 | 29.40 | 0.00882150 | 18.34 | 2.53819000 | 26.1411 | 24.00 | 0.00882852 | 24.00 | 0.00882852 | 46.8257 | 131700.22 | 0.00 | 180991.63 | 159535.22 | 11.52515962 | 25.41 | 17.16 | 0.00882668 | 48026.0 | 11.86 | 11.29 | 0.00808878 | 32322.0 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 47802.652 | 47802.652 | 2.912868 | 0.00041820 | 797.556 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.709561 | 11.52515962 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 2.1707 | 2.214417 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 47802.65 | 47802.65 | 1.0000 | 3.45754789 | 2.912868 | -0.96 | -1.30 | 0.00331346 | 7317.5 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.41815579 | 60.00 | 32.22 | 27.78 | 0.000 | 47802.65 | -4.20 | 0.00269032 | -4.20 | 2.53819000 | 87.1371 | 21.00 | 0.00753484 | 19.80 | 0.00750260 | 51.5284 | 54061.61 | 0.00 | 45772.20 | 45772.20 | 3.45754789 | 2.80 | 0.98 | 0.00331346 | 11117.6 | 15.89 | 7.86 | 0.00331346 | 24355.9 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 102703.409 | -999.000 | 5.797971 | 0.00436924 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4586 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 5.797971 | 6.88213772 | 4197.9300 | 999.8980 | 90.32417338 | 12.27 | 6.67 | 5.60 | 2123377.52 | 4.8368 | 4.836795 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 102703.41 | 95004.68 | 1.0000 | 6.88213772 | 5.797971 | 24.93 | 16.94 | 0.00893976 | 47818.0 | 11.40 | 11.39 | 0.00850000 | 32894.8 | 4.36879471 | 6.67 | 12.27 | 5.60 | 9831.354 | 92872.05 | 28.05 | 0.00881933 | 17.90 | 1.20015641 | 20.6996 | 24.00 | 0.00897549 | 24.00 | 0.00897549 | 47.5946 | 71152.89 | 0.00 | 103893.87 | 90423.38 | 6.88213772 | 24.93 | 17.09 | 0.00893976 | 47818.0 | 12.06 | 11.45 | 0.00816408 | 32721.8 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 282635.291 | 282635.291 | 5.797971 | 0.00247262 | 6298.234 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 5.797971 | 6.88213772 | 4197.9300 | 999.8980 | 18.88333572 | 54.44 | 82.22 | 27.78 | 2202146.20 | 12.8345 | 13.092838 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 282635.29 | 282635.29 | 1.0000 | 6.88213772 | 5.797971 | -0.87 | -2.23 | 0.00269032 | 5850.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 2.47236459 | 60.00 | 32.22 | 27.78 | 0.000 | 282635.29 | -4.20 | 0.00269032 | -4.20 | 1.20015641 | 20.6996 | 0.00 | 0.00269032 | 24.46 | 0.00269032 | 14.0189 | 0.00 | 0.00 | 236932.53 | 236932.53 | 6.88213772 | 12.80 | 5.58 | 0.00269032 | 19654.3 | 46.89 | 19.29 | 0.00269032 | 54081.5 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 428635.777 | 307024.886 | 21.672544 | 0.01049726 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7275 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 398737.62 | 396037.01 | 0.9302 | -999.0 | -999.0 | 28.45 | 17.81 | 0.00854651 | 50411.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 398737.62 | 29.40 | 0.00882150 | 18.34 | 0.33839277 | -999.0000 | 27.00 | 0.00854214 | 27.00 | 0.00854214 | 37.9331 | 372397.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9907.085 | 7177.824 | 0.512494 | 0.00024262 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8069 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 9180.64 | 9058.43 | 0.9267 | -999.0 | -999.0 | 27.92 | 17.67 | 0.00858923 | 49985.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9180.64 | 25.86 | 0.00881585 | 17.16 | 0.01563234 | -999.0000 | 27.00 | 0.00858210 | 27.00 | 0.00858210 | 38.1056 | 8815.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 94845.186 | 68699.029 | 4.904113 | 0.00232275 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8142 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 87896.89 | 86676.34 | 0.9267 | -999.0 | -999.0 | 27.92 | 17.67 | 0.00859312 | 49993.7 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87896.89 | 25.86 | 0.00881585 | 17.16 | 0.15632344 | -999.0000 | 27.00 | 0.00858579 | 27.00 | 0.00858579 | 38.1219 | 84356.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9627.435 | 6973.998 | 0.497874 | 0.00023578 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8118 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8921.93 | 8799.71 | 0.9267 | -999.0 | -999.0 | 27.92 | 17.67 | 0.00859184 | 49991.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8921.93 | 25.86 | 0.00881585 | 17.16 | 0.01563234 | -999.0000 | 27.00 | 0.00858458 | 27.00 | 0.00858458 | 38.1165 | 8564.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 428635.777 | 428635.777 | 21.672544 | 0.01049726 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 428635.78 | 428635.78 | 1.0000 | 25.72510942 | 21.672544 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 428635.78 | -4.20 | 0.00269032 | -4.20 | 0.33839277 | 1.5614 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9907.085 | 9907.085 | 0.512494 | 0.00024262 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9907.08 | 9907.08 | 1.0000 | 0.60832591 | 0.512494 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9907.08 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.0502 | 0.00 | 0.00850000 | 26.84 | 0.00850000 | 38.0914 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 94845.186 | 94845.186 | 4.904113 | 0.00232275 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 94845.19 | 94845.19 | 1.0000 | 5.82113638 | 4.904113 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94845.19 | -4.20 | 0.00269032 | -4.20 | 0.15632344 | 3.1876 | 0.00 | 0.00505638 | 24.49 | 0.00505638 | 26.1957 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9627.435 | 9627.435 | 0.497874 | 0.00023578 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9627.43 | 9627.43 | 1.0000 | 0.59097205 | 0.497874 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9627.43 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.1398 | 0.00 | 0.00310467 | 23.39 | 0.00310467 | 17.2388 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17840.032 | 17840.032 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.672544 | 25.72510942 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 17840.03 | 17840.03 | 1.0000 | 25.72510942 | 21.672544 | -0.07 | -0.07 | 0.00840929 | 20964.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17840.03 | -4.20 | 0.00269032 | -4.20 | 0.33839277 | 1.5614 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.512494 | 0.60832591 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 824.14 | 824.14 | 1.0000 | 0.60832591 | 0.512494 | -0.13 | -0.13 | 0.00832279 | 20684.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.14 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.0502 | 0.00 | 0.00850000 | 26.84 | 0.00850000 | 38.0914 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8241.356 | 8241.356 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.904113 | 5.82113638 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8241.36 | 8241.36 | 1.0000 | 5.82113638 | 4.904113 | -0.13 | -0.13 | 0.00498096 | 12321.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8241.36 | -4.20 | 0.00269032 | -4.20 | 0.15632344 | 3.1876 | 0.00 | 0.00505638 | 24.49 | 0.00505638 | 26.1957 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.497874 | 0.59097205 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 824.14 | 824.14 | 1.0000 | 0.59097205 | 0.497874 | -0.13 | -1.19 | 0.00309166 | 7598.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.14 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.1398 | 0.00 | 0.00310467 | 23.39 | 0.00310467 | 17.2388 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.63 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 88.86 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.71 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.80 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2676.17 | 187.33 | 0.33 |
CORE_BOTTOM | 2642.83 | 404.50 | 12.83 |
CORE_MID | 1428.00 | 2403.17 | 12.67 |
CORE_TOP | 1458.50 | 3560.50 | 348.00 |
PERIMETER_BOT_ZN_3 | 1438.67 | 3014.67 | 23.00 |
PERIMETER_BOT_ZN_2 | 1384.17 | 3792.33 | 61.33 |
PERIMETER_BOT_ZN_1 | 1858.17 | 3293.50 | 89.67 |
PERIMETER_BOT_ZN_4 | 2668.17 | 2256.67 | 90.33 |
PERIMETER_MID_ZN_3 | 1575.67 | 4183.50 | 763.17 |
PERIMETER_MID_ZN_2 | 1531.50 | 3807.33 | 732.50 |
PERIMETER_MID_ZN_1 | 1880.17 | 3876.33 | 509.00 |
PERIMETER_MID_ZN_4 | 1692.67 | 4305.83 | 576.00 |
PERIMETER_TOP_ZN_3 | 2226.83 | 4611.83 | 1536.50 |
PERIMETER_TOP_ZN_2 | 2422.83 | 4490.17 | 1425.17 |
PERIMETER_TOP_ZN_1 | 2305.83 | 4241.33 | 1124.83 |
PERIMETER_TOP_ZN_4 | 2179.00 | 4586.00 | 1210.50 |
DATACENTER_BOT_ZN_6 | 5943.00 | 829.17 | 829.17 |
DATACENTER_MID_ZN_6 | 5854.83 | 152.00 | 137.67 |
DATACENTER_TOP_ZN_6 | 5545.67 | 344.00 | 225.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5804.17 | 5804.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 70.33 | 0.00 | 4.00 |
CORE_BOTTOM | 0.00 | 2.67 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 3.17 | 0.00 | 0.17 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 7.67 | 0.00 | 7.67 |
PERIMETER_BOT_ZN_1 | 0.00 | 9.33 | 0.00 | 9.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 39.83 | 0.00 | 18.00 |
PERIMETER_MID_ZN_3 | 3.67 | 0.00 | 0.33 | 0.00 |
PERIMETER_MID_ZN_2 | 2.83 | 7.00 | 0.00 | 7.00 |
PERIMETER_MID_ZN_1 | 1.67 | 7.50 | 0.00 | 7.50 |
PERIMETER_MID_ZN_4 | 1.00 | 13.50 | 0.00 | 6.67 |
PERIMETER_TOP_ZN_3 | 66.33 | 0.00 | 15.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 46.17 | 6.17 | 4.00 | 6.17 |
PERIMETER_TOP_ZN_1 | 31.00 | 6.83 | 2.00 | 6.83 |
PERIMETER_TOP_ZN_4 | 22.17 | 12.33 | 1.67 | 5.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 112.50 | 0.00 | 108.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 70.50 | 259.67 | 15.50 | 161.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 1.489 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 1.093 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.818 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.758 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.978 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.672 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.707 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.225 | 0.042 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.746 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.501 | 0.105 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.606 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.695 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.767 | 0.118 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.569 | 0.122 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.608 | 0.118 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.731 | 0.122 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.481 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 61340684.04 | 0.00 | 61340684.04 | 0.00 | 61340684.04 | 37848132.68 | 3861.95 | 252.42 | 4645.62 | 433.54 |
CORE_BOTTOM | 46339880.46 | 0.00 | 46339880.46 | 0.00 | 46339880.46 | 33990283.35 | 4093.22 | 35.67 | 4631.10 | 471.98 |
CORE_MID | 0.33E+09 | 0.00 | 0.33E+09 | 0.00 | 0.33E+09 | 0.34E+09 | 5191.26 | 65.69 | 3503.05 | 157.63 |
CORE_TOP | 30866922.67 | 0.00 | 30866922.67 | 0.00 | 30866922.67 | 33990283.35 | 5718.12 | 49.95 | 2991.94 | 240.24 |
PERIMETER_BOT_ZN_3 | 5248217.29 | 0.00 | 5248217.29 | 420131.66 | 5668348.95 | 4267819.30 | 4408.21 | 96.32 | 4255.47 | 471.98 |
PERIMETER_BOT_ZN_2 | 5887565.75 | 0.00 | 5887565.75 | 280087.58 | 6167653.33 | 2750345.05 | 3420.14 | 1.83 | 5338.03 | 471.98 |
PERIMETER_BOT_ZN_1 | 9236239.00 | 0.00 | 9236239.00 | 420131.66 | 9656370.66 | 4267912.63 | 3419.64 | 0.00 | 5340.36 | 471.98 |
PERIMETER_BOT_ZN_4 | 7778551.84 | 0.00 | 7778551.84 | 280087.58 | 8058639.42 | 2750345.05 | 3419.64 | 0.00 | 5340.36 | 471.98 |
PERIMETER_MID_ZN_3 | 38396825.36 | 0.00 | 38396825.36 | 985321.86 | 39382147.21 | 42678193.03 | 5357.54 | 77.85 | 3324.61 | 157.63 |
PERIMETER_MID_ZN_2 | 53694166.95 | 0.00 | 53694166.95 | 656880.79 | 54351047.74 | 27503450.52 | 3851.56 | 0.08 | 4908.35 | 1066.63 |
PERIMETER_MID_ZN_1 | 82687005.81 | 0.00 | 82687005.81 | 985321.86 | 83672327.66 | 42679126.28 | 3853.82 | 1.05 | 4905.13 | 157.63 |
PERIMETER_MID_ZN_4 | 56533661.42 | 0.00 | 56533661.42 | 656880.79 | 57190542.21 | 27503450.52 | 3852.24 | 0.64 | 4907.12 | 157.63 |
PERIMETER_TOP_ZN_3 | 3940680.00 | 0.00 | 3940680.00 | 1223376.39 | 5164056.39 | 4267819.30 | 5156.31 | 279.32 | 3324.37 | 240.24 |
PERIMETER_TOP_ZN_2 | 5198604.13 | 0.00 | 5198604.13 | 815583.70 | 6014187.83 | 2750345.05 | 3925.20 | 5.85 | 4828.95 | 240.24 |
PERIMETER_TOP_ZN_1 | 8248509.55 | 0.00 | 8248509.55 | 1223376.39 | 9471885.94 | 4267912.63 | 3935.58 | 4.99 | 4819.43 | 240.24 |
PERIMETER_TOP_ZN_4 | 5745761.18 | 0.00 | 5745761.18 | 815583.70 | 6561344.88 | 2750345.05 | 3907.14 | 5.62 | 4847.25 | 240.24 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.59E+10 | 0.00 | 0.59E+10 | 38322411.53 | 0.59E+10 | 0.50E+10 | 6035.75 | 4401.14 | 5538.53 | 1685.14 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.7423 | 0.0000 | 2.7423 | 0.0000 | 2.7423 | 1.2002 | 1300.86 | 247.48 | 4394.67 |
CORE_BOTTOM | 2.0332 | 0.0000 | 2.0332 | 0.0000 | 2.0332 | 1.0778 | 1676.29 | 31.83 | 4234.88 |
CORE_MID | 15.2303 | 0.0000 | 15.2303 | 0.0000 | 15.2303 | 10.7782 | 2488.01 | 65.34 | 3389.65 |
CORE_TOP | 1.4128 | 0.0000 | 1.4128 | 0.0000 | 1.4128 | 1.0778 | 2956.38 | 49.69 | 2936.92 |
PERIMETER_BOT_ZN_3 | 0.2287 | 0.0000 | 0.2287 | 0.0095 | 0.2383 | 0.1353 | 2008.97 | 91.10 | 3842.93 |
PERIMETER_BOT_ZN_2 | 0.2526 | 0.0000 | 0.2526 | 0.0064 | 0.2590 | 0.0872 | 1075.12 | 1.83 | 4866.05 |
PERIMETER_BOT_ZN_1 | 0.3999 | 0.0000 | 0.3999 | 0.0095 | 0.4094 | 0.1353 | 1074.62 | 0.00 | 4868.38 |
PERIMETER_BOT_ZN_4 | 0.3355 | 0.0000 | 0.3355 | 0.0064 | 0.3419 | 0.0872 | 1074.62 | 0.00 | 4868.38 |
PERIMETER_MID_ZN_3 | 1.7478 | 0.0000 | 1.7478 | 0.0224 | 1.7702 | 1.3533 | 2656.30 | 76.49 | 3210.21 |
PERIMETER_MID_ZN_2 | 2.2715 | 0.0000 | 2.2715 | 0.0159 | 2.2874 | 0.8721 | 1190.90 | 0.00 | 3843.10 |
PERIMETER_MID_ZN_1 | 3.7650 | 0.0000 | 3.7650 | 0.0224 | 3.7874 | 1.3533 | 1191.44 | 0.21 | 4751.35 |
PERIMETER_MID_ZN_4 | 2.5648 | 0.0000 | 2.5648 | 0.0149 | 2.5797 | 0.8721 | 1191.73 | 0.50 | 4750.77 |
PERIMETER_TOP_ZN_3 | 0.1800 | 0.0000 | 0.1800 | 0.0278 | 0.2078 | 0.1353 | 2400.46 | 278.73 | 3263.81 |
PERIMETER_TOP_ZN_2 | 0.2375 | 0.0000 | 0.2375 | 0.0185 | 0.2560 | 0.0872 | 1237.51 | 3.00 | 4702.50 |
PERIMETER_TOP_ZN_1 | 0.3773 | 0.0000 | 0.3773 | 0.0278 | 0.4051 | 0.1353 | 1242.20 | 2.61 | 4698.19 |
PERIMETER_TOP_ZN_4 | 0.2620 | 0.0000 | 0.2620 | 0.0185 | 0.2805 | 0.0872 | 1229.00 | 3.43 | 4710.58 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 265.6677 | 0.0000 | 265.6677 | 0.8803 | 266.5480 | 158.4706 | 3218.75 | 4376.71 | 4913.98 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.10E+09 | 0.00 | 0.10E+09 | 48026705.38 | 3419.64 | 0.00 | 5340.36 | 471.98 |
VAV_MID WITH REHEAT | 0.80E+09 | 0.00 | 0.80E+09 | 0.48E+09 | 3873.53 | 1.43 | 4885.03 | 157.63 |
VAV_TOP WITH REHEAT | 76083818.38 | 0.00 | 76083818.38 | 48026705.38 | 3995.99 | 7.02 | 4756.99 | 240.24 |
CAV_BAS | 86425780.11 | 0.00 | 86425780.11 | 37848132.68 | 3781.30 | 3.66 | 4975.04 | 433.54 |
AIRLOOP DATACENTER BASEMENT | 7450888.29 | 0.00 | 7450888.29 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 344200.17 | 0.00 | 344200.17 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3442001.72 | 0.00 | 3442001.72 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 344200.17 | 0.00 | 344200.17 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.5790 | 0.0000 | 4.5790 | 1.5229 | 1074.62 | 0.00 | 4868.38 |
VAV_MID WITH REHEAT | 36.2751 | 0.0000 | 36.2751 | 15.2292 | 1201.72 | 0.62 | 4740.66 |
VAV_TOP WITH REHEAT | 3.4794 | 0.0000 | 3.4794 | 1.5229 | 1274.65 | 4.33 | 4664.02 |
CAV_BAS | 3.8638 | 0.0000 | 3.8638 | 1.2002 | 1291.64 | 0.46 | 4650.90 |
AIRLOOP DATACENTER BASEMENT | 0.3483 | 0.0000 | 0.3483 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0161 | 0.0000 | 0.0161 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1609 | 0.0000 | 0.1609 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0161 | 0.0000 | 0.0161 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 4943.90 | 0.00 | 0.00 | 0.00 | 396.46 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 4142.40 | 0.00 | 0.00 | 0.00 | 767.83 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 3690.40 | 0.00 | 0.00 | 0.00 | 1326.33 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 244.83 | 4854.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.8729 | 0.0000 | 0.0000 | 0.0000 | 2.4122 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 49.3863 | 0.0000 | 0.0000 | 0.0000 | 24.5479 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 5.0519 | 0.0000 | 0.0000 | 0.0000 | 2.4503 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6967 | 5.1015 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4769 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2203 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1380 |
Defaulted Fields | 1179 |
Fields with Defaults | 3862 |
Autosized Fields | 330 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27848.02 | 367534.46 | 16-JAN-10:20 | 1983009.31 | 10-AUG-15:10 |
Electricity:Building | 18929.06 | 251811.03 | 01-JAN-09:50 | 1146857.44 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 664.85 | 14623.97 | 01-JAN-00:10 | 34452.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18929.06 | 251811.03 | 01-JAN-09:50 | 1146857.44 | 01-DEC-16:20 |
InteriorLights:Electricity | 3715.64 | 17601.77 | 01-JAN-09:50 | 352853.36 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3715.64 | 17601.77 | 01-JAN-09:50 | 352853.36 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 3715.64 | 17601.77 | 01-JAN-09:50 | 352853.36 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3715.64 | 17601.77 | 01-JAN-09:50 | 352853.36 | 02-JAN-16:30 |
Electricity:Zone:CORE_BOTTOM | 537.23 | 7090.40 | 01-JAN-00:10 | 36983.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5372.24 | 70903.72 | 01-JAN-00:10 | 369831.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 537.22 | 7090.37 | 01-JAN-00:10 | 36983.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 59.27 | 839.57 | 01-JAN-09:40 | 4643.71 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.93 | 80.80 | 01-JAN-09:40 | 2367.39 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.93 | 80.80 | 01-JAN-09:40 | 2367.39 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 38.16 | 541.05 | 01-JAN-09:20 | 2992.58 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.16 | 52.07 | 01-JAN-09:20 | 1525.64 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.16 | 52.07 | 01-JAN-09:20 | 1525.64 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 59.11 | 839.58 | 01-JAN-09:20 | 4643.79 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.77 | 80.80 | 01-JAN-09:20 | 2367.44 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.77 | 80.80 | 01-JAN-09:20 | 2367.44 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 38.14 | 541.05 | 01-JAN-09:40 | 2992.57 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 12.14 | 52.07 | 01-JAN-09:40 | 1525.64 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 12.14 | 52.07 | 01-JAN-09:40 | 1525.64 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 592.95 | 8395.70 | 01-JAN-09:50 | 46437.07 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 189.53 | 807.98 | 01-JAN-09:50 | 23673.89 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 189.53 | 807.98 | 01-JAN-09:50 | 23673.89 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 381.61 | 5410.51 | 01-JAN-09:20 | 29925.82 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 121.63 | 520.69 | 01-JAN-09:20 | 15256.36 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 121.63 | 520.69 | 01-JAN-09:20 | 15256.36 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 591.27 | 8395.84 | 01-JAN-09:20 | 46437.94 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 187.84 | 807.99 | 01-JAN-09:20 | 23674.41 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 187.84 | 807.99 | 01-JAN-09:20 | 23674.41 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 381.47 | 5410.48 | 01-JAN-09:40 | 29925.72 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 121.49 | 520.69 | 01-JAN-09:40 | 15256.36 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 121.49 | 520.69 | 01-JAN-09:40 | 15256.36 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 59.30 | 839.57 | 01-JAN-09:50 | 4643.71 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.95 | 80.80 | 01-JAN-09:50 | 2367.39 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.95 | 80.80 | 01-JAN-09:50 | 2367.39 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 38.16 | 541.05 | 01-JAN-09:20 | 2992.58 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.16 | 52.07 | 01-JAN-09:20 | 1525.64 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.16 | 52.07 | 01-JAN-09:20 | 1525.64 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 59.13 | 839.58 | 01-JAN-09:20 | 4643.79 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.78 | 80.80 | 01-JAN-09:20 | 2367.44 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.78 | 80.80 | 01-JAN-09:20 | 2367.44 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 38.15 | 541.05 | 01-JAN-09:40 | 2992.57 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 12.15 | 52.07 | 01-JAN-09:40 | 1525.64 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 12.15 | 52.07 | 01-JAN-09:40 | 1525.64 | 02-JAN-16:30 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7562.65 | 95237.01 | 01-JAN-00:10 | 385552.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1598.46 | 19775.43 | 01-JAN-00:10 | 83152.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1613.45 | 6286.68 | 15-JAN-08:10 | 371943.41 | 29-AUG-14:30 |
HeatRejection:Electricity | 906.25 | 2618.54 | 07-JAN-08:00 | 80718.76 | 27-APR-12:30 |
General:HeatRejection:Electricity | 906.25 | 2618.54 | 07-JAN-08:00 | 80718.76 | 27-APR-12:30 |
Electricity:HVAC | 4777.75 | 74712.92 | 01-JAN-23:50 | 433213.87 | 10-AUG-14:50 |
ExteriorEquipment:Electricity | 1941.94 | 28795.69 | 01-JAN-00:10 | 118958.47 | 28-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.33 | 1613.62 | 01-JAN-00:10 | 5481.25 | 01-DEC-16:30 |
ElectricityPurchased:Facility | 27848.02 | 367534.46 | 16-JAN-10:20 | 1983009.31 | 10-AUG-15:10 |
ElectricityPurchased:Plant | 27848.02 | 367534.46 | 16-JAN-10:20 | 1983009.31 | 10-AUG-15:10 |
Cogeneration:ElectricityPurchased | 27848.02 | 367534.46 | 16-JAN-10:20 | 1983009.31 | 10-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 27848.02 | 367534.46 | 16-JAN-10:20 | 1983009.31 | 10-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 27848.02 | 367534.46 | 16-JAN-10:20 | 1983009.31 | 10-AUG-15:10 |
ElectricityNet:Plant | 27848.02 | 367534.46 | 16-JAN-10:20 | 1983009.31 | 10-AUG-15:10 |
Cogeneration:ElectricityNet | 27848.02 | 367534.46 | 16-JAN-10:20 | 1983009.31 | 10-AUG-15:10 |
General:Cogeneration:ElectricityNet | 27848.02 | 367534.46 | 16-JAN-10:20 | 1983009.31 | 10-AUG-15:10 |
Fans:Electricity | 2335.93 | 42368.23 | 01-JAN-10:50 | 257070.54 | 10-AUG-14:50 |
General:Fans:Electricity | 2335.93 | 42368.23 | 01-JAN-10:50 | 257070.54 | 10-AUG-14:50 |
ExteriorLights:Electricity | 673.15 | 0.00 | 01-JAN-08:10 | 54335.80 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 673.15 | 0.00 | 01-JAN-08:10 | 54335.80 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 2710.15 | 28608.80 | 17-JAN-07:10 | 409599.59 | 29-AUG-14:30 |
General:Cooling:Electricity | 2710.15 | 28608.80 | 17-JAN-07:10 | 409599.59 | 29-AUG-14:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 4.78 | 0.00 | 01-JAN-00:10 | 8453.97 | 01-APR-16:10 |
General:Humidifier:Electricity | 4.78 | 0.00 | 01-JAN-00:10 | 8453.97 | 01-APR-16:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 346.76 | 3391.76 | 01-JAN-00:40 | 56728.45 | 19-JUL-13:30 |
General:Pumps:Electricity | 346.76 | 3391.76 | 01-JAN-00:40 | 56728.45 | 19-JUL-13:30 |
WIRED_LTG_ELECTRICITY | 104.41 | 0.00 | 01-JAN-00:10 | 9915.18 | 02-JAN-16:40 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1772.00 | 5695.87 | 23-JUL-16:10 | 1304086.33 | 02-JAN-06:20 |
NaturalGas:Plant | 1772.00 | 5695.87 | 23-JUL-16:10 | 1304086.33 | 02-JAN-06:20 |
Heating:NaturalGas | 1050.18 | 0.00 | 01-JAN-00:40 | 1298390.46 | 02-JAN-06:20 |
Boiler:Heating:NaturalGas | 1050.18 | 0.00 | 01-JAN-00:40 | 1298390.46 | 02-JAN-06:20 |
WaterSystems:NaturalGas | 721.82 | 5695.87 | 23-JUL-16:10 | 81418.03 | 08-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 721.82 | 5695.87 | 23-JUL-16:10 | 81418.03 | 08-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 14580.67 | 141694.30 | 09-JAN-07:10 | 2361586.04 | 29-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 14580.67 | 141694.30 | 09-JAN-07:10 | 2361586.04 | 29-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 14580.67 | 141694.30 | 09-JAN-07:10 | 2361586.04 | 29-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 4164.43 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
Water:HVAC | 1.78 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-16:10 |
Humidifier:Water | 1.78 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-16:10 |
General:Humidifier:Water | 1.78 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-16:10 |
MainsWater:Facility | 4164.43 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
MainsWater:HVAC | 1.78 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-16:10 |
Humidifier:MainsWater | 1.78 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-16:10 |
General:Humidifier:MainsWater | 1.78 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-16:10 |
Water:Plant | 4162.65 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 4162.65 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 1882.48 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:Water | 1882.48 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
HeatRejection:MainsWater | 1882.48 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:MainsWater | 1882.48 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 40038.89 | 217049.66 | 16-JAN-05:40 | 9176912.99 | 29-AUG-14:30 |
EnergyTransfer:Building | 18276.83 | 88420.75 | 21-JAN-19:50 | 1650686.81 | 10-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 694.53 | 0.00 | 01-JAN-00:10 | 69810.83 | 05-SEP-05:10 |
Heating:EnergyTransfer | 195.31 | 0.00 | 05-JAN-22:10 | 883200.92 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.75 | 0.00 | 01-JAN-00:10 | 11346.76 | 01-APR-16:10 |
General:Heating:EnergyTransfer | 195.31 | 0.00 | 05-JAN-22:10 | 883200.92 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.75 | 0.00 | 01-JAN-00:10 | 11346.76 | 01-APR-16:10 |
Cooling:EnergyTransfer | 18081.52 | 87333.61 | 16-JAN-05:40 | 1650686.81 | 10-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 690.77 | 0.00 | 01-JAN-00:10 | 69810.83 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 18081.52 | 87333.61 | 16-JAN-05:40 | 1650686.81 | 10-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 690.77 | 0.00 | 01-JAN-00:10 | 69810.83 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 628.80 | 0.00 | 01-JAN-00:10 | 53613.45 | 14-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 628.80 | 0.00 | 01-JAN-00:10 | 53613.45 | 14-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 628.80 | 0.00 | 01-JAN-00:10 | 53613.45 | 14-AUG-13:10 |
EnergyTransfer:Zone:CORE_MID | 4387.94 | 0.00 | 01-JAN-00:10 | 441275.08 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.70 | 0.00 | 01-JAN-00:10 | 288642.51 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.70 | 0.00 | 01-JAN-00:10 | 288642.51 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4386.25 | 0.00 | 01-JAN-00:10 | 441275.08 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4386.25 | 0.00 | 01-JAN-00:10 | 441275.08 | 10-AUG-16:00 |
EnergyTransfer:Zone:CORE_TOP | 385.54 | 0.00 | 01-JAN-00:40 | 65440.81 | 17-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 4.70 | 0.00 | 01-JAN-00:10 | 65440.81 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 4.70 | 0.00 | 01-JAN-00:10 | 65440.81 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 380.84 | 0.00 | 01-JAN-00:40 | 50977.13 | 10-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 380.84 | 0.00 | 01-JAN-00:40 | 50977.13 | 10-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.79 | 0.00 | 01-JAN-00:10 | 9438.47 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 48.11 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 48.11 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.79 | 0.00 | 01-JAN-00:10 | 9438.47 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.79 | 0.00 | 01-JAN-00:10 | 9438.47 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.16 | 0.00 | 01-JAN-00:10 | 13025.48 | 31-JUL-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 653.49 | 14-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 653.49 | 14-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.16 | 0.00 | 01-JAN-00:10 | 13025.48 | 31-JUL-08:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.16 | 0.00 | 01-JAN-00:10 | 13025.48 | 31-JUL-08:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 110.47 | 0.00 | 01-JAN-00:10 | 20762.84 | 04-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 4323.05 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 4323.05 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 110.43 | 0.00 | 01-JAN-00:10 | 20762.84 | 04-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 110.43 | 0.00 | 01-JAN-00:10 | 20762.84 | 04-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 99.35 | 0.00 | 01-JAN-00:10 | 17437.92 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 99.35 | 0.00 | 01-JAN-00:10 | 17437.92 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 99.35 | 0.00 | 01-JAN-00:10 | 17437.92 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 436.50 | 0.00 | 01-JAN-00:10 | 100961.25 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.49 | 0.00 | 01-JAN-00:10 | 100961.25 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.49 | 0.00 | 01-JAN-00:10 | 100961.25 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 411.00 | 0.00 | 01-JAN-00:10 | 82642.33 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 411.00 | 0.00 | 01-JAN-00:10 | 82642.33 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 520.57 | 0.00 | 01-JAN-00:10 | 135041.94 | 10-AUG-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 17.89 | 0.00 | 01-JAN-00:10 | 82063.44 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 17.89 | 0.00 | 01-JAN-00:10 | 82063.44 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 502.68 | 0.00 | 01-JAN-00:10 | 135041.94 | 10-AUG-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 502.68 | 0.00 | 01-JAN-00:10 | 135041.94 | 10-AUG-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 906.55 | 0.00 | 01-JAN-00:10 | 222136.77 | 04-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 16.84 | 0.00 | 01-JAN-00:10 | 122277.75 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 16.84 | 0.00 | 01-JAN-00:10 | 122277.75 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 889.70 | 0.00 | 01-JAN-00:10 | 222136.77 | 04-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 889.70 | 0.00 | 01-JAN-00:10 | 222136.77 | 04-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 572.60 | 0.00 | 01-JAN-00:10 | 149100.70 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 9.31 | 0.00 | 01-JAN-00:10 | 68454.93 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 9.31 | 0.00 | 01-JAN-00:10 | 68454.93 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 563.28 | 0.00 | 01-JAN-00:10 | 149100.70 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 563.28 | 0.00 | 01-JAN-00:10 | 149100.70 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 48.83 | 0.00 | 01-JAN-00:40 | 11637.12 | 17-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.56 | 0.00 | 01-JAN-00:40 | 11637.12 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.56 | 0.00 | 01-JAN-00:40 | 11637.12 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 35.27 | 0.00 | 01-JAN-00:10 | 9210.58 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 35.27 | 0.00 | 01-JAN-00:10 | 9210.58 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 52.08 | 0.00 | 01-JAN-00:40 | 13551.39 | 10-AUG-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 8.31 | 0.00 | 01-JAN-00:40 | 11566.57 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 8.31 | 0.00 | 01-JAN-00:40 | 11566.57 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.77 | 0.00 | 01-JAN-00:10 | 13551.39 | 10-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.77 | 0.00 | 01-JAN-00:10 | 13551.39 | 10-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 87.73 | 0.00 | 01-JAN-00:40 | 22109.43 | 04-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 9.49 | 0.00 | 01-JAN-00:40 | 17080.88 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 9.49 | 0.00 | 01-JAN-00:40 | 17080.88 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 78.24 | 0.00 | 01-JAN-00:10 | 22109.43 | 04-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 78.24 | 0.00 | 01-JAN-00:10 | 22109.43 | 04-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 55.13 | 0.00 | 01-JAN-00:40 | 15541.05 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.32 | 0.00 | 01-JAN-00:40 | 10413.89 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.32 | 0.00 | 01-JAN-00:40 | 10413.89 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 49.81 | 0.00 | 01-JAN-00:10 | 15541.05 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 49.81 | 0.00 | 01-JAN-00:10 | 15541.05 | 10-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 62.10 | 0.00 | 01-JAN-00:10 | 8714.62 | 14-AUG-15:00 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.19 | 0.00 | 01-JAN-00:10 | 3467.64 | 29-OCT-10:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.19 | 0.00 | 01-JAN-00:10 | 3467.64 | 29-OCT-10:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 60.91 | 0.00 | 01-JAN-00:10 | 8714.62 | 14-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 60.91 | 0.00 | 01-JAN-00:10 | 8714.62 | 14-AUG-15:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 406.00 | 0.00 | 01-JAN-00:10 | 109310.61 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 45.41 | 0.00 | 01-JAN-00:10 | 109310.61 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 45.41 | 0.00 | 01-JAN-00:10 | 109310.61 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 360.59 | 0.00 | 01-JAN-00:10 | 69659.18 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 360.59 | 0.00 | 01-JAN-00:10 | 69659.18 | 10-AUG-15:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 72.95 | 0.00 | 01-JAN-00:40 | 19865.66 | 17-JAN-05:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 29.52 | 0.00 | 01-JAN-00:40 | 19865.66 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 29.52 | 0.00 | 01-JAN-00:40 | 19865.66 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 43.43 | 0.00 | 01-JAN-00:10 | 19089.03 | 10-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 43.43 | 0.00 | 01-JAN-00:10 | 19089.03 | 10-AUG-14:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.36 | 681.05 | 21-JAN-18:20 | 8556.89 | 06-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.36 | 681.05 | 21-JAN-18:20 | 8556.89 | 06-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.36 | 681.05 | 21-JAN-18:20 | 8556.89 | 06-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1192.37 | 5.16 | 14-JAN-20:40 | 79223.94 | 06-AUG-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 2.05 | 0.00 | 02-JAN-12:30 | 5542.68 | 01-JAN-22:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 2.05 | 0.00 | 02-JAN-12:30 | 5542.68 | 01-JAN-22:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1190.32 | 0.00 | 01-JAN-00:10 | 79223.94 | 06-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1190.32 | 0.00 | 01-JAN-00:10 | 79223.94 | 06-AUG-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 109.30 | 0.01 | 05-JAN-09:00 | 8047.02 | 06-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.73 | 0.00 | 02-JAN-13:30 | 601.13 | 08-JAN-18:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.73 | 0.00 | 02-JAN-13:30 | 601.13 | 08-JAN-18:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.57 | 0.00 | 01-JAN-00:10 | 8047.02 | 06-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.57 | 0.00 | 01-JAN-00:10 | 8047.02 | 06-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.18 | 86559.20 | 17-JAN-05:00 | 369474.10 | 11-AUG-15:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.18 | 86559.20 | 17-JAN-05:00 | 369474.10 | 11-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.18 | 86559.20 | 17-JAN-05:00 | 369474.10 | 11-AUG-15:20 |
PlantLoopHeatingDemand:Facility | 1185.26 | 0.00 | 01-JAN-00:40 | 1063618.53 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 423.42 | 0.00 | 01-JAN-00:10 | 50362.48 | 13-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 423.42 | 0.00 | 01-JAN-00:10 | 50362.48 | 13-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 423.42 | 0.00 | 01-JAN-00:10 | 50362.48 | 13-FEB-12:50 |
EnergyTransfer:HVAC | 12992.81 | 123651.04 | 16-JAN-05:40 | 2190200.39 | 29-AUG-14:30 |
HeatingCoils:EnergyTransfer | 761.84 | 0.00 | 01-JAN-00:40 | 1057503.96 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 761.84 | 0.00 | 01-JAN-00:40 | 1057503.96 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 761.84 | 0.00 | 01-JAN-00:40 | 1057503.96 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 12230.96 | 112870.21 | 07-JAN-08:00 | 2190200.39 | 29-AUG-14:30 |
EnergyTransfer:Plant | 8769.25 | -5553.16 | 24-FEB-05:10 | 5378294.89 | 29-AUG-14:30 |
LoopToLoop:EnergyTransfer | 2517.62 | -6085.65 | 24-FEB-05:10 | 1700150.43 | 29-AUG-14:30 |
WaterSystems:EnergyTransfer | 423.42 | 0.00 | 01-JAN-00:10 | 50362.48 | 13-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 423.42 | 0.00 | 01-JAN-00:10 | 50362.48 | 13-FEB-12:50 |
Boilers:EnergyTransfer | 755.33 | 0.00 | 01-JAN-00:40 | 1082136.86 | 02-JAN-06:20 |
Chillers:EnergyTransfer | 2356.22 | 0.00 | 01-JAN-00:10 | 1707498.07 | 29-AUG-14:30 |
HeatRejection:EnergyTransfer | 2716.67 | 0.00 | 01-JAN-00:10 | 1945712.02 | 29-AUG-14:30 |
General:HeatRejection:EnergyTransfer | 2716.67 | 0.00 | 01-JAN-00:10 | 1945712.02 | 29-AUG-14:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.754 | -690.774 | 0.000 | 0.000 | 92.713 | 240.449 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -70.538 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -628.804 | 0.000 | 0.000 | 83.417 | 215.940 | 321.286 | 0.000 | 0.000 | 0.000 | 8.161 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 1.696 | -4386.232 | 0.000 | 0.000 | 843.433 | 2159.397 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1831.139 |
CORE_TOP | 0.000 | 0.000 | 4.705 | -380.835 | 0.000 | 0.000 | 87.132 | 215.940 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -248.226 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -65.787 | 0.000 | 0.000 | 10.734 | 18.932 | 40.342 | 19.999 | 0.000 | 0.015 | 29.900 | 0.000 | -47.552 | 0.000 | -6.584 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.002 | -67.162 | 0.000 | 0.000 | 7.182 | 12.158 | 25.998 | 39.161 | 0.000 | 0.012 | 15.903 | 0.000 | -29.064 | 0.000 | -4.189 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.037 | -110.434 | 0.000 | 0.000 | 11.016 | 18.769 | 40.343 | 84.493 | 0.000 | 0.014 | 6.126 | 0.000 | -43.971 | 0.000 | -6.394 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -99.351 | 0.000 | 0.000 | 6.953 | 12.144 | 25.998 | 41.178 | 0.000 | 0.008 | 51.537 | 0.000 | -33.733 | 0.000 | -4.733 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 25.495 | -411.002 | 0.000 | 0.000 | 113.014 | 189.532 | 403.423 | 209.275 | 0.000 | 0.400 | 26.005 | 0.000 | -420.735 | 0.000 | -135.407 | -0.018 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 17.888 | -502.680 | 0.000 | 0.000 | 54.793 | 121.629 | 259.981 | 395.020 | 0.000 | 0.259 | 10.306 | 0.000 | -267.632 | 0.000 | -89.564 | -0.004 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 16.842 | -889.700 | 0.000 | 0.000 | 113.165 | 187.843 | 403.429 | 846.193 | 0.000 | 0.312 | 0.018 | 0.000 | -417.759 | 0.000 | -140.468 | -119.857 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 9.314 | -563.280 | 0.000 | 0.000 | 74.739 | 121.487 | 259.979 | 424.311 | 0.000 | 0.217 | 52.481 | 0.000 | -285.748 | 0.000 | -93.501 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 13.563 | -35.270 | 0.000 | 0.000 | 11.606 | 18.953 | 40.342 | 21.645 | 0.000 | 0.047 | 0.000 | 0.000 | -38.689 | 0.000 | -15.493 | -16.703 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 8.312 | -43.770 | 0.000 | 0.000 | 7.512 | 12.163 | 25.998 | 39.888 | 0.000 | 0.028 | 0.000 | 0.000 | -24.980 | 0.000 | -10.391 | -14.760 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 9.485 | -78.244 | 0.000 | 0.000 | 11.538 | 18.784 | 40.343 | 85.350 | 0.000 | 0.036 | 0.000 | 0.000 | -38.927 | 0.000 | -16.210 | -32.155 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 5.315 | -49.811 | 0.000 | 0.000 | 7.590 | 12.149 | 25.998 | 42.721 | 0.000 | 0.026 | 0.000 | 0.000 | -26.842 | 0.000 | -10.904 | -6.243 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -138.356 | 0.000 | 0.000 | 0.950 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -22.440 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 2.052 | -1190.316 | 0.000 | 0.000 | 9.503 | 59.652 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -419.696 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.731 | -108.574 | 0.000 | 0.000 | 0.952 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -52.955 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7176.181 | 0.000 | 0.000 | 20.495 | 67.796 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -406.967 |
GROUNDFLOOR_PLENUM | 1.192 | -60.909 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.024 | 73.557 | 0.000 | 0.000 | 0.000 | -13.863 | 0.000 |
MIDFLOOR_PLENUM | 45.408 | -360.587 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.483 | 547.824 | 0.000 | 0.000 | 0.000 | -233.128 | -0.007 |
TOPFLOOR_PLENUM | 29.520 | -43.431 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.028 | 38.339 | 0.000 | 0.000 | 0.000 | -24.456 | -0.001 |
Total Facility | 76.119 | -464.928 | 119.191 | -17616.562 | 0.000 | 0.000 | 1568.439 | 3715.644 | 15213.411 | 2249.235 | 0.000 | 1.908 | 860.157 | 0.000 | -1675.634 | 0.000 | -805.284 | -3241.712 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 17-APR-03:02 | 0.00 | 0.00 | 0.00 | -114210.89 | 0.00 | 0.00 | 0.00 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 99586.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 10-OCT-03:02 | 0.00 | 0.00 | 0.00 | -96431.91 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.15 | 0.00 | 0.00 | 0.00 | 87327.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 28-AUG-03:02 | 0.00 | 0.00 | 0.00 | -856254.18 | 0.00 | 0.00 | 0.00 | 10475.32 | 80571.20 | 0.00 | 0.00 | 0.00 | 765207.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 12-JUN-03:02 | 0.00 | 0.00 | 0.00 | -81176.95 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.12 | 0.00 | 0.00 | 0.00 | 72072.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 | -11947.30 | 0.00 | 0.00 | 107.26 | 161.60 | 1011.70 | 220.66 | 0.00 | 0.00 | 10505.93 | 0.00 | -0.00 | 0.00 | -59.84 | 0.00 |
PERIMETER_BOT_ZN_2 | 13-AUG-08:22 | 0.00 | 0.00 | 0.00 | -21721.41 | 0.00 | 0.00 | 22.42 | 52.07 | 488.98 | 16693.31 | 0.00 | 0.00 | 4636.41 | 0.00 | -0.00 | 0.00 | -171.78 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-12:41 | 0.00 | 0.00 | 0.00 | -31342.36 | 0.00 | 0.00 | 34.10 | 80.80 | 758.78 | 23064.59 | 0.00 | 0.00 | 7570.69 | 0.00 | -0.00 | 0.00 | -166.60 | 0.00 |
PERIMETER_BOT_ZN_4 | 23-JUL-17:31 | 0.00 | 0.00 | 0.00 | -28999.58 | 0.00 | 0.00 | 0.00 | 52.07 | 488.98 | 16375.80 | 0.00 | 0.00 | 12163.83 | 0.00 | -0.00 | 0.00 | -81.10 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -82640.62 | 0.00 | 0.00 | 11143.81 | 14542.87 | 22763.18 | 53024.94 | 0.00 | 810.55 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19644.73 |
PERIMETER_MID_ZN_2 | 23-JUL-08:42 | 0.00 | 0.00 | 0.00 | -226046.95 | 0.00 | 0.00 | 216.60 | 520.69 | 4889.82 | 153125.21 | 0.00 | 0.00 | 72145.49 | 0.00 | -0.00 | 0.00 | -4850.87 | 0.00 |
PERIMETER_MID_ZN_1 | 13-AUG-13:42 | 0.00 | 0.00 | 0.00 | -311743.69 | 0.00 | 0.00 | 352.28 | 807.99 | 7587.84 | 157382.09 | 0.00 | 0.00 | 146217.43 | 0.00 | -0.00 | 0.00 | -603.94 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-18:41 | 0.00 | 0.00 | 0.00 | -247623.36 | 0.00 | 0.00 | 0.00 | 520.69 | 4889.79 | 105912.14 | 0.00 | 0.00 | 138887.06 | 0.00 | -0.00 | 0.00 | -2586.31 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -9210.44 | 0.00 | 0.00 | 1114.38 | 1454.29 | 2276.32 | 5258.56 | 0.00 | 98.95 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -992.04 |
PERIMETER_TOP_ZN_2 | 06-AUG-09:42 | 0.00 | 0.00 | 0.00 | -21086.88 | 0.00 | 0.00 | 23.93 | 52.07 | 488.98 | 12256.16 | 0.00 | 0.00 | 8719.02 | 0.00 | -0.00 | 0.00 | -453.29 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-14:01 | 0.00 | 0.00 | 0.00 | -34538.03 | 0.00 | 0.00 | 32.15 | 80.80 | 758.78 | 19083.68 | 0.00 | 0.00 | 14957.09 | 0.00 | -0.00 | 0.00 | -374.48 | 0.00 |
PERIMETER_TOP_ZN_4 | 07-MAY-16:41 | 0.00 | 0.00 | 0.00 | -25583.76 | 0.00 | 0.00 | 20.51 | 52.07 | 488.98 | 16323.93 | 0.00 | 0.00 | 9091.48 | 0.00 | -0.00 | 0.00 | -393.21 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-18:40 | 0.00 | 0.00 | 0.00 | -8556.89 | 0.00 | 0.00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 733.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-18:11 | 0.00 | 0.00 | 0.00 | -79223.94 | 0.00 | 0.00 | 0.00 | 289.38 | 77944.22 | 0.00 | 0.00 | 0.00 | 990.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 06-AUG-18:38 | 0.00 | 0.00 | 0.00 | -8047.02 | 0.00 | 0.00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 223.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 29-AUG-21:14 | 0.00 | 0.00 | 0.00 | -370325.78 | 0.00 | 0.00 | 114.51 | 657.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10079.01 |
GROUNDFLOOR_PLENUM | 12-JUN-05:13 | 0.00 | -11238.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11371.51 | 0.00 | -0.00 | 0.00 | -133.38 | 0.00 |
MIDFLOOR_PLENUM | 26-AUG-05:13 | 0.00 | -74224.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75458.96 | 0.00 | -0.00 | 0.00 | -1234.78 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:30 | 0.00 | -19088.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.62 | 19021.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-AUG-05:03 | 0.00 | 5569.80 | 0.00 | -1827733.33 | 0.00 | 0.00 | 15717.48 | 38982.20 | 623236.89 | 18201.04 | 0.00 | 0.00 | 1168588.57 | 0.00 | -38862.01 | 0.00 | -3700.64 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 20-JUN-03:53 | 0.00 | 0.00 | 14104.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28728.47 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 365149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20950.64 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -466671.09 |
CORE_TOP | 17-JAN-04:01 | 0.00 | 0.00 | 75883.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -84988.25 |
PERIMETER_BOT_ZN_3 | 09-JAN-06:05 | 0.00 | 0.00 | 192.43 | 0.00 | 0.00 | 0.00 | 138.73 | 263.06 | 1011.70 | 0.00 | 0.00 | 0.00 | 2417.03 | 0.00 | -3890.89 | 0.00 | -132.05 | 0.00 |
PERIMETER_BOT_ZN_2 | 14-FEB-06:01 | 0.00 | 0.00 | 4574.45 | 0.00 | 0.00 | 0.00 | 90.54 | 169.52 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2443.86 | 0.00 | -76.75 | -2965.87 |
PERIMETER_BOT_ZN_1 | 17-JAN-06:03 | 0.00 | 0.00 | 9626.23 | 0.00 | 0.00 | 0.00 | 148.60 | 263.06 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3034.93 | 0.00 | -91.27 | -7923.40 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-04:01 | 0.00 | 0.00 | 116441.02 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.28 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15302.70 | 0.00 | -11137.12 | -101433.45 |
PERIMETER_MID_ZN_2 | 02-JAN-04:01 | 0.00 | 0.00 | 147738.54 | 0.00 | 0.00 | 0.00 | 0.00 | 847.62 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10075.62 | 0.00 | -7646.16 | -137384.13 |
PERIMETER_MID_ZN_1 | 02-JAN-04:01 | 0.00 | 0.00 | 213842.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.31 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15748.84 | 0.00 | -11566.36 | -197959.66 |
PERIMETER_MID_ZN_4 | 02-JAN-04:01 | 0.00 | 0.00 | 137267.77 | 0.00 | 0.00 | 0.00 | 0.00 | 847.62 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11332.81 | 0.00 | -8294.79 | -125007.51 |
PERIMETER_TOP_ZN_3 | 19-FEB-08:63 | 0.00 | 0.00 | 13355.31 | 0.00 | 0.00 | 0.00 | 88.77 | 96.70 | 758.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2559.02 | 0.00 | -2338.41 | -9402.12 |
PERIMETER_TOP_ZN_2 | 26-DEC-04:01 | 0.00 | 0.00 | 16916.29 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1756.01 | 0.00 | -692.22 | -15204.80 |
PERIMETER_TOP_ZN_1 | 26-DEC-04:01 | 0.00 | 0.00 | 25390.78 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2578.73 | 0.00 | -1038.01 | -22917.29 |
PERIMETER_TOP_ZN_4 | 26-DEC-04:01 | 0.00 | 0.00 | 17301.36 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1771.76 | 0.00 | -696.83 | -15569.51 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-22:20 | 0.00 | 0.00 | 5542.68 | 0.00 | 0.00 | 0.00 | 0.00 | 289.38 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25318.12 |
DATACENTER_TOP_ZN_6 | 08-JAN-17:15 | 0.00 | 0.00 | 607.93 | 0.00 | 0.00 | 0.00 | 5.88 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2591.36 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 28-DEC-05:01 | 13739.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1647.80 | -12092.08 |
MIDFLOOR_PLENUM | 02-JAN-06:13 | 129897.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5201.72 | -124696.09 |
TOPFLOOR_PLENUM | 17-JAN-05:12 | 22207.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1104.39 | -21103.06 |
Total Facility | 02-JAN-05:22 | -70734.64 | 151773.80 | 1011478.25 | -151773.80 | 0.00 | 0.00 | 0.00 | 39207.80 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77309.58 | 0.00 | -74811.38 | -1096193.13 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.1716 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.6323 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 106.4373 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 88.8577 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.7051 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.7096 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.7980 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.7980 | 0.2070 | 1.0000 | Not calculated | 1.2002 | 0.2070 | ||
AIRLOOP DATACENTER BASEMENT | 21.6724 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.6725 | 0.0156 | 1.0000 | Not calculated | 0.3384 | 0.0156 | ||
AIRLOOP DATACENTER BOT | 0.5125 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5125 | 0.0305 | 1.0000 | Not calculated | 0.0156 | 0.0305 | ||
AIRLOOP DATACENTER MID | 4.9041 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.9041 | 0.0319 | 1.0000 | Not calculated | 0.1563 | 0.0319 | ||
AIRLOOP DATACENTER TOP | 0.4979 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4979 | 0.0314 | 1.0000 | Not calculated | 0.0156 | 0.0314 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.5858 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.4778 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 53.2187 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 33.9041 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.3526 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.5112 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.7980 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.7980 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2070 | ||
AIRLOOP DATACENTER BASEMENT | 21.6724 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.6724 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0156 | ||
AIRLOOP DATACENTER BOT | 0.5125 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5125 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0305 | ||
AIRLOOP DATACENTER MID | 4.9041 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.9041 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0319 | ||
AIRLOOP DATACENTER TOP | 0.4979 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4979 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0314 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7980 | 5.7980 | 5.7980 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0129 | 6.0129 | 1.9301 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 56.3689 | 56.3689 | 18.8836 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4483 | 5.4483 | 1.9342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8717 | 0.8717 | 0.2615 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1853 | 1.1853 | 0.3556 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6707 | 1.6707 | 0.5012 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4310 | 1.4310 | 0.4293 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.9781 | 7.9781 | 2.3934 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.2052 | 12.2052 | 3.6616 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.0892 | 17.0892 | 5.1268 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.7959 | 12.7959 | 3.8388 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8923 | 0.8923 | 0.2677 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2089 | 1.2089 | 0.3627 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8093 | 1.8093 | 0.5428 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3463 | 1.3463 | 0.4039 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5125 | 0.5125 | 0.5125 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9041 | 4.9041 | 4.9041 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4979 | 0.4979 | 0.4979 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.6724 | 21.6724 | 21.6724 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.1716 | 9.6323 | 11.1716 | 3.4778 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 106.4373 | 88.8577 | 106.4373 | 33.9041 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.7051 | 9.7096 | 10.7051 | 3.5112 | 0.0000 | 1.0000 |
CAV_BAS | 5.7980 | 5.7980 | 5.7980 | 5.7980 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.6724 | 21.6725 | 21.6724 | 21.6724 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5125 | 0.5125 | 0.5125 | 0.5125 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.9041 | 4.9041 | 4.9041 | 4.9041 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4979 | 0.4979 | 0.4979 | 0.4979 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7980 | 5.7980 | 5.7980 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0065 | 3.0065 | 1.9301 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.1845 | 28.1845 | 18.8836 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7242 | 2.7242 | 1.9342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4358 | 0.4358 | 0.2615 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5927 | 0.5927 | 0.3556 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8353 | 0.8353 | 0.5012 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7155 | 0.7155 | 0.4293 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9891 | 3.9891 | 2.3934 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1026 | 6.1026 | 3.6616 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.5446 | 8.5446 | 5.1268 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3979 | 6.3979 | 3.8388 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4461 | 0.4461 | 0.2677 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6045 | 0.6045 | 0.3627 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9047 | 0.9047 | 0.5428 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6731 | 0.6731 | 0.4039 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5125 | 0.5125 | 0.5125 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9041 | 4.9041 | 4.9041 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4979 | 0.4979 | 0.4979 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.6724 | 21.6724 | 21.6724 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.5858 | 3.4778 | 3.4778 | 3.4778 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 53.2187 | 33.9041 | 33.9041 | 33.9041 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.3526 | 3.5112 | 3.5112 | 3.5112 | 0.0000 | 1.0000 |
CAV_BAS | 5.7980 | 5.7980 | 5.7980 | 5.7980 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.6724 | 21.6724 | 21.6724 | 21.6724 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5125 | 0.5125 | 0.5125 | 0.5125 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.9041 | 4.9041 | 4.9041 | 4.9041 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4979 | 0.4979 | 0.4979 | 0.4979 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 15.50 |
Number of hours cooling loads not met | 161.33 |
Number of hours not met | 176.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1050.18 | 1298390.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2710.15 | 409599.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3715.64 | 352853.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 673.15 | 54335.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.33 | 5481.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2335.93 | 257070.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 346.76 | 56728.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 906.25 | 80718.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 4.78 | 8453.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 721.82 | 81418.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 27848.02 |
Natural Gas | 0.00 | 1772.00 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 29620.02 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 80.22 |
Space Heating | 0.00 |
Space Cooling | 58.51 |
Fans (All) | 50.43 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 601.20 |
Subtotal | 601.20 |
Natural Gas [MJ/m2] | |
Space Heating | 22.67 |
Service Water Heating | 15.58 |
Miscellaneous (All) | 38.26 |
Subtotal | 38.26 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.54 |
Space Heating | 3.55 |
Space Cooling | 9.15 |
Fans (All) | 7.89 |
Service Water Heating | 2.44 |
Receptacle Equipment | 51.36 |
Miscellaneous | 13.08 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2645. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8505.00 | 255.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8689.00 | 71.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8748.33 | 11.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8553.50 | 206.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8743.33 | 16.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8721.17 | 38.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8725.67 | 34.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7645.17 | 1114.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7605.67 | 1154.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7574.00 | 1186.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7850.50 | 909.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
Min | 7574.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1186.00 | 0.00 | 0.00 | 0.00 |
Average | 8540.09 | 219.91 | 0.00 | 0.00 | 0.00 |
Sum | 196422.00 | 5058.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367921.83 | 694.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330730.00 | 83.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1655.50 | 612.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1624.17 | 643.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1606.67 | 661.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 83497.50 | 19897.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367921.83 | 19897.50 | 0.00 | 0.00 | 0.00 |
Average | 79352.64 | 982.28 | 0.00 | 0.00 | 0.00 |
Sum | 1825110.67 | 22592.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8337.50 | 422.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8516.17 | 243.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8587.33 | 172.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8651.83 | 108.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8745.83 | 14.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8731.17 | 28.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8508.67 | 251.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8720.00 | 40.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8667.50 | 92.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8724.00 | 36.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8682.33 | 77.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8416.67 | 343.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8393.33 | 366.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8382.83 | 377.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8504.67 | 255.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8737.67 | 22.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8700.33 | 59.67 | 0.00 | 0.00 | 0.00 |
Min | 8337.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 422.50 | 0.00 | 0.00 | 0.00 |
Average | 8631.20 | 128.80 | 0.00 | 0.00 | 0.00 |
Sum | 198517.67 | 2962.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367613.83 | 1002.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330396.17 | 416.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330496.00 | 317.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330607.00 | 206.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2034.00 | 234.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2015.17 | 252.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2008.17 | 259.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 97513.00 | 5882.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367613.83 | 5882.00 | 0.00 | 0.00 | 0.00 |
Average | 79962.28 | 372.64 | 0.00 | 0.00 | 0.00 |
Sum | 1839132.33 | 8570.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:01
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487638E+11 | 113023.85 | 02-JAN-04:01 | 6.60 | 5.58 | 0.566023E+10 | 7499.16 | 05-JAN-10:20 | 2.60 | 2.43 |
February | 0.466693E+11 | 112122.65 | 21-FEB-04:01 | 1.70 | 0.99 | 0.513540E+10 | 7499.06 | 08-FEB-10:09 | 1.70 | 0.99 |
March | 0.590710E+11 | 113442.51 | 20-MAR-03:02 | 6.10 | 4.50 | 0.613229E+10 | 7499.09 | 09-MAR-14:20 | 6.10 | 4.50 |
April | 0.566389E+11 | 114235.41 | 17-APR-03:02 | 6.10 | 5.06 | 0.545031E+10 | 7499.05 | 27-APR-13:09 | 26.10 | 16.37 |
May | 0.589671E+11 | 113299.51 | 08-MAY-03:02 | 9.82 | 9.48 | 0.590127E+10 | 7499.14 | 05-MAY-09:20 | 9.82 | 9.48 |
June | 0.611507E+11 | 108292.34 | 05-JUN-03:02 | 11.02 | 10.00 | 0.588261E+10 | 7499.17 | 09-JUN-13:20 | 21.87 | 13.52 |
July | 0.615452E+11 | 111219.80 | 03-JUL-03:02 | 11.60 | 8.31 | 0.547355E+10 | 7499.12 | 11-JUL-09:20 | 16.13 | 15.49 |
August | 0.679060E+11 | 107646.74 | 21-AUG-00:52 | 13.60 | 11.96 | 0.613752E+10 | 7499.56 | 09-AUG-09:00 | 13.60 | 11.96 |
September | 0.590933E+11 | 109041.10 | 28-SEP-04:02 | 8.80 | 7.96 | 0.545189E+10 | 7499.13 | 14-SEP-09:20 | 8.80 | 7.96 |
October | 0.598310E+11 | 114027.39 | 16-OCT-03:02 | 7.20 | 6.13 | 0.566899E+10 | 7499.06 | 12-OCT-09:20 | 7.20 | 6.13 |
November | 0.567656E+11 | 113837.06 | 24-NOV-04:02 | 3.72 | 2.60 | 0.561299E+10 | 7499.04 | 10-NOV-10:30 | 3.72 | 2.60 |
December | 0.543728E+11 | 113911.12 | 11-DEC-04:01 | 2.88 | 2.18 | 0.546767E+10 | 7499.27 | 13-DEC-14:20 | 6.90 | 5.05 |
Annual Sum or Average | 0.690775E+12 | 0.679747E+11 | ||||||||
Minimum of Months | 0.466693E+11 | 107646.74 | 1.70 | 0.99 | 0.513540E+10 | 7499.04 | 1.70 | 0.99 | ||
Maximum of Months | 0.679060E+11 | 114235.41 | 13.60 | 11.96 | 0.613752E+10 | 7499.56 | 26.10 | 16.37 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372374E+11 | 88637.64 | 02-JAN-05:01 | 6.10 | 5.29 | 0.505318E+10 | 6734.78 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.386494E+11 | 87433.21 | 06-FEB-05:01 | 4.32 | 3.61 | 0.459796E+10 | 6734.72 | 08-FEB-10:09 | 2.48 | 1.47 |
March | 0.532083E+11 | 91900.10 | 20-MAR-03:02 | 6.10 | 4.50 | 0.550117E+10 | 6734.75 | 09-MAR-14:09 | 6.10 | 4.50 |
April | 0.562069E+11 | 93638.82 | 17-APR-03:02 | 6.10 | 5.06 | 0.488519E+10 | 6734.73 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.537578E+11 | 95150.20 | 01-MAY-03:02 | 11.78 | 9.72 | 0.528806E+10 | 6734.84 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.585357E+11 | 95870.83 | 12-JUN-03:02 | 15.00 | 13.35 | 0.527206E+10 | 6734.87 | 05-JUN-09:00 | 15.00 | 13.35 |
July | 0.638728E+11 | 95136.44 | 17-JUL-03:02 | 14.90 | 13.04 | 0.489869E+10 | 6734.80 | 28-JUL-13:00 | 20.00 | 15.26 |
August | 0.722167E+11 | 91507.86 | 28-AUG-03:02 | 16.12 | 14.27 | 0.549798E+10 | 6735.36 | 09-AUG-09:00 | 16.12 | 14.27 |
September | 0.515486E+11 | 94221.07 | 25-SEP-03:02 | 13.30 | 13.30 | 0.488542E+10 | 6734.83 | 14-SEP-09:09 | 13.30 | 13.30 |
October | 0.505117E+11 | 96434.73 | 10-OCT-03:02 | 12.20 | 10.91 | 0.508007E+10 | 6734.76 | 05-OCT-09:00 | 12.20 | 10.91 |
November | 0.471655E+11 | 95687.93 | 06-NOV-04:02 | 10.10 | 7.78 | 0.503072E+10 | 6734.73 | 13-NOV-10:39 | 2.43 | 2.35 |
December | 0.458938E+11 | 90085.18 | 26-DEC-04:01 | -1.0 | -1.0 | 0.490067E+10 | 6734.87 | 13-DEC-14:09 | -1.0 | -1.0 |
Annual Sum or Average | 0.628805E+12 | 0.608912E+11 | ||||||||
Minimum of Months | 0.372374E+11 | 87433.21 | -1.0 | -1.0 | 0.459796E+10 | 6734.72 | -1.0 | -1.0 | ||
Maximum of Months | 0.722167E+11 | 96434.73 | 16.12 | 14.27 | 0.550117E+10 | 6735.36 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248541E+11 | 28319.81 | 12-JAN-06:03 | 6.70 | 6.36 | 0.474710E+10 | 6734.61 | 27-JAN-14:09 | 9.72 | 8.09 |
February | 0.256914E+11 | 74079.75 | 28-FEB-06:03 | 10.60 | 9.74 | 0.446009E+10 | 6734.69 | 08-FEB-10:09 | 10.60 | 9.74 |
March | 0.350513E+11 | 76639.57 | 03-MAR-06:03 | 6.60 | 6.18 | 0.543594E+10 | 6734.73 | 09-MAR-14:09 | 14.90 | 12.35 |
April | 0.355584E+11 | 80880.02 | 28-APR-04:03 | 11.60 | 10.11 | 0.484741E+10 | 6734.72 | 27-APR-13:00 | 11.60 | 10.11 |
May | 0.427726E+11 | 81581.46 | 05-MAY-04:02 | 13.22 | 10.58 | 0.526835E+10 | 6734.82 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.452753E+11 | 83649.71 | 12-JUN-03:02 | 15.00 | 13.35 | 0.526113E+10 | 6734.83 | 09-JUN-13:09 | 15.00 | 13.35 |
July | 0.459124E+11 | 84098.88 | 10-JUL-03:02 | 13.80 | 12.22 | 0.489262E+10 | 6734.78 | 28-JUL-13:00 | 20.00 | 15.26 |
August | 0.503111E+11 | 85648.32 | 28-AUG-03:02 | 16.12 | 14.27 | 0.549240E+10 | 6735.25 | 09-AUG-09:00 | 16.12 | 14.27 |
September | 0.416428E+11 | 82894.29 | 12-SEP-04:02 | 12.20 | 11.52 | 0.487131E+10 | 6734.82 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.355983E+11 | 80783.04 | 10-OCT-04:03 | 12.20 | 10.98 | 0.503417E+10 | 6734.76 | 12-OCT-09:20 | 9.47 | 7.95 |
November | 0.291437E+11 | 76612.32 | 06-NOV-06:03 | 11.28 | 8.36 | 0.493601E+10 | 6734.72 | 10-NOV-10:30 | 7.25 | 5.94 |
December | 0.268136E+11 | 52504.58 | 07-DEC-06:03 | 4.27 | 2.78 | 0.471860E+10 | 6734.76 | 12-DEC-10:30 | 4.15 | 3.92 |
Annual Sum or Average | 0.438625E+12 | 0.599651E+11 | ||||||||
Minimum of Months | 0.248541E+11 | 28319.81 | 4.27 | 2.78 | 0.446009E+10 | 6734.61 | 4.15 | 3.92 | ||
Maximum of Months | 0.503111E+11 | 85648.32 | 16.12 | 14.27 | 0.549240E+10 | 6735.25 | 20.00 | 15.51 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196643E+11 | 19370.46 | 11-JAN-17:00 | 12.20 | 9.27 | 0.425519E+10 | 6548.90 | 12-JAN-14:00 | 7.20 | 5.88 |
February | 0.203293E+11 | 30556.48 | 28-FEB-17:00 | 14.40 | 10.82 | 0.402850E+10 | 6734.43 | 24-FEB-14:09 | 14.40 | 10.82 |
March | 0.275685E+11 | 33454.67 | 15-MAR-16:00 | 11.10 | 7.72 | 0.511035E+10 | 6734.65 | 09-MAR-14:09 | 11.10 | 7.72 |
April | 0.304246E+11 | 78330.75 | 28-APR-05:02 | 11.10 | 9.92 | 0.469315E+10 | 6734.73 | 27-APR-13:00 | 11.10 | 9.92 |
May | 0.386337E+11 | 78371.44 | 05-MAY-05:02 | 12.98 | 10.75 | 0.520678E+10 | 6734.80 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.433441E+11 | 81173.08 | 12-JUN-03:02 | 15.00 | 13.35 | 0.523766E+10 | 6734.83 | 09-JUN-13:09 | 15.00 | 13.35 |
July | 0.455926E+11 | 80159.12 | 25-JUL-04:02 | 13.90 | 12.99 | 0.487923E+10 | 6734.79 | 28-JUL-13:00 | 20.00 | 15.26 |
August | 0.491827E+11 | 80947.29 | 10-AUG-04:02 | 17.90 | 14.46 | 0.547618E+10 | 6735.25 | 09-AUG-09:00 | 17.90 | 14.46 |
September | 0.365619E+11 | 78494.74 | 15-SEP-05:02 | 11.60 | 11.30 | 0.481621E+10 | 6734.79 | 14-SEP-09:09 | 11.60 | 11.30 |
October | 0.277464E+11 | 62894.64 | 05-OCT-05:03 | 8.30 | 5.23 | 0.482030E+10 | 6734.63 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.218755E+11 | 27704.34 | 02-NOV-16:00 | 13.30 | 10.88 | 0.448921E+10 | 6734.57 | 06-NOV-14:00 | 11.10 | 10.22 |
December | 0.199142E+11 | 19397.77 | 06-DEC-17:00 | 1.10 | 0.98 | 0.416384E+10 | 6591.80 | 06-DEC-14:00 | 1.10 | 0.98 |
Annual Sum or Average | 0.380838E+12 | 0.571766E+11 | ||||||||
Minimum of Months | 0.196643E+11 | 19370.46 | 1.10 | 0.98 | 0.402850E+10 | 6548.90 | 1.10 | 0.98 | ||
Maximum of Months | 0.491827E+11 | 81173.08 | 17.90 | 14.46 | 0.547618E+10 | 6735.25 | 20.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.289665E+10 | 3028.59 | 11-JAN-06:02 | 9.90 | 7.47 | 0.558748E+09 | 828.64 | 11-JAN-14:39 | 14.40 | 10.49 |
February | 0.307723E+10 | 4719.23 | 27-FEB-15:30 | 19.70 | 12.30 | 0.530006E+09 | 845.61 | 24-FEB-10:09 | 19.70 | 12.30 |
March | 0.446480E+10 | 5160.42 | 10-MAR-14:30 | 16.40 | 11.76 | 0.669294E+09 | 845.63 | 09-MAR-14:09 | 16.40 | 11.76 |
April | 0.564705E+10 | 7489.76 | 27-APR-15:20 | 27.20 | 17.16 | 0.605173E+09 | 845.63 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.639281E+10 | 7543.39 | 05-MAY-05:02 | 12.98 | 10.75 | 0.658410E+09 | 845.63 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.762752E+10 | 11949.87 | 12-JUN-05:03 | 14.40 | 13.42 | 0.660373E+09 | 845.64 | 09-JUN-13:09 | 14.40 | 13.42 |
July | 0.891812E+10 | 11749.34 | 10-JUL-05:03 | 13.22 | 11.65 | 0.614380E+09 | 845.64 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.969979E+10 | 11860.79 | 28-AUG-05:03 | 14.83 | 13.93 | 0.689474E+09 | 845.71 | 09-AUG-09:00 | 14.83 | 13.93 |
September | 0.568730E+10 | 9369.15 | 05-SEP-05:03 | 10.68 | 9.20 | 0.607816E+09 | 845.63 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.447419E+10 | 9143.71 | 10-OCT-05:03 | 12.20 | 11.22 | 0.622571E+09 | 845.62 | 12-OCT-09:39 | 10.03 | 8.14 |
November | 0.362172E+10 | 4716.76 | 06-NOV-11:40 | 13.70 | 9.94 | 0.601892E+09 | 845.62 | 20-NOV-14:09 | 10.92 | 9.28 |
December | 0.327983E+10 | 3195.75 | 30-DEC-06:04 | 5.00 | 4.51 | 0.566889E+09 | 845.61 | 04-DEC-14:09 | 5.00 | 4.51 |
Annual Sum or Average | 0.657870E+11 | 0.738502E+10 | ||||||||
Minimum of Months | 0.289665E+10 | 3028.59 | 5.00 | 4.51 | 0.530006E+09 | 828.64 | 5.00 | 4.51 | ||
Maximum of Months | 0.969979E+10 | 11949.87 | 27.20 | 17.16 | 0.689474E+09 | 845.71 | 27.20 | 17.16 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294537E+10 | 3891.56 | 11-JAN-06:02 | 9.90 | 7.47 | 0.325872E+09 | 495.37 | 05-JAN-10:09 | 9.90 | 7.47 |
February | 0.329567E+10 | 4121.54 | 28-FEB-06:03 | 10.60 | 9.74 | 0.313181E+09 | 544.95 | 08-FEB-10:09 | 10.60 | 9.74 |
March | 0.485312E+10 | 7715.25 | 14-MAR-09:00 | 7.80 | 5.89 | 0.399869E+09 | 544.96 | 02-MAR-10:09 | 7.80 | 5.89 |
April | 0.597266E+10 | 10720.57 | 27-APR-08:30 | 16.95 | 12.18 | 0.377058E+09 | 544.96 | 20-APR-09:00 | 16.95 | 12.18 |
May | 0.653589E+10 | 20491.29 | 14-MAY-08:52 | 16.70 | 11.54 | 0.413454E+09 | 544.97 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.763253E+10 | 13450.73 | 25-JUN-08:43 | 16.52 | 11.95 | 0.419624E+09 | 544.97 | 09-JUN-13:09 | 16.52 | 11.95 |
July | 0.845384E+10 | 21693.96 | 23-JUL-08:12 | 18.17 | 13.67 | 0.390465E+09 | 546.00 | 31-JUL-09:20 | 22.57 | 17.16 |
August | 0.925329E+10 | 21725.42 | 13-AUG-08:22 | 20.20 | 15.50 | 0.438152E+09 | 545.76 | 10-AUG-09:20 | 20.20 | 15.50 |
September | 0.618270E+10 | 20946.81 | 10-SEP-08:42 | 15.82 | 13.36 | 0.379253E+09 | 544.97 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.488076E+10 | 8819.81 | 04-OCT-09:00 | 15.60 | 10.49 | 0.374947E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.382289E+10 | 4479.67 | 06-NOV-04:02 | 10.10 | 7.78 | 0.343064E+09 | 534.37 | 15-NOV-10:09 | 7.30 | 5.72 |
December | 0.333354E+10 | 3890.09 | 04-DEC-04:02 | 5.73 | 2.01 | 0.319841E+09 | 526.25 | 04-DEC-10:20 | 8.30 | 4.51 |
Annual Sum or Average | 0.671623E+11 | 0.449478E+10 | ||||||||
Minimum of Months | 0.294537E+10 | 3890.09 | 5.73 | 2.01 | 0.313181E+09 | 495.37 | 7.30 | 4.51 | ||
Maximum of Months | 0.925329E+10 | 21725.42 | 20.20 | 15.50 | 0.438152E+09 | 546.00 | 22.57 | 17.16 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460413E+10 | 13795.43 | 20-JAN-13:10 | 6.70 | 4.72 | 0.524635E+09 | 845.64 | 11-JAN-14:09 | 6.70 | 4.72 |
February | 0.597224E+10 | 16446.86 | 27-FEB-13:50 | 18.22 | 11.40 | 0.508359E+09 | 845.64 | 08-FEB-10:09 | 18.22 | 11.40 |
March | 0.887155E+10 | 17396.19 | 01-MAR-13:30 | 11.15 | 5.98 | 0.636255E+09 | 846.41 | 14-MAR-13:00 | 15.60 | 10.50 |
April | 0.996380E+10 | 28273.79 | 02-APR-13:22 | 18.90 | 11.09 | 0.586450E+09 | 846.47 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.985486E+10 | 28022.14 | 14-MAY-13:32 | 22.60 | 12.25 | 0.639849E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.104618E+11 | 13617.60 | 28-JUN-13:10 | 24.50 | 15.71 | 0.648000E+09 | 845.68 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.129138E+11 | 20899.67 | 30-JUL-12:53 | 26.10 | 17.75 | 0.607000E+09 | 846.53 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.150646E+11 | 30273.29 | 13-AUG-13:02 | 26.62 | 18.46 | 0.682433E+09 | 847.51 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.113162E+11 | 31340.75 | 10-SEP-12:41 | 20.40 | 13.99 | 0.593735E+09 | 847.07 | 15-SEP-13:50 | 21.70 | 16.50 |
October | 0.929596E+10 | 21075.06 | 08-OCT-13:13 | 18.53 | 13.81 | 0.595591E+09 | 846.48 | 02-OCT-13:20 | 18.53 | 13.81 |
November | 0.626781E+10 | 20976.12 | 11-NOV-12:43 | 6.42 | 5.03 | 0.555311E+09 | 845.63 | 08-NOV-14:00 | 6.42 | 5.03 |
December | 0.584769E+10 | 15216.33 | 05-DEC-12:30 | 10.30 | 6.13 | 0.525732E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.110434E+12 | 0.710335E+10 | ||||||||
Minimum of Months | 0.460413E+10 | 13617.60 | 6.42 | 4.72 | 0.508359E+09 | 845.63 | 6.42 | 4.72 | ||
Maximum of Months | 0.150646E+11 | 31340.75 | 26.62 | 18.46 | 0.682433E+09 | 847.51 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.436594E+10 | 5201.75 | 11-JAN-06:02 | 9.90 | 7.47 | 0.340256E+09 | 535.97 | 05-JAN-14:00 | 9.90 | 7.47 |
February | 0.497460E+10 | 10124.37 | 27-FEB-15:30 | 19.70 | 12.30 | 0.336518E+09 | 544.94 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.735732E+10 | 12382.55 | 14-MAR-16:00 | 17.20 | 10.94 | 0.430864E+09 | 544.96 | 09-MAR-14:09 | 17.20 | 10.94 |
April | 0.949980E+10 | 19937.35 | 02-APR-15:22 | 20.60 | 11.92 | 0.393131E+09 | 544.96 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.859891E+10 | 27217.80 | 07-MAY-16:41 | 21.78 | 16.19 | 0.417309E+09 | 544.96 | 05-MAY-09:09 | 21.78 | 16.19 |
June | 0.100235E+11 | 22629.42 | 18-JUN-17:12 | 17.03 | 12.24 | 0.424567E+09 | 544.97 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.132804E+11 | 29000.16 | 23-JUL-17:31 | 26.30 | 15.81 | 0.397058E+09 | 544.97 | 28-JUL-13:39 | 21.10 | 15.48 |
August | 0.147454E+11 | 26281.72 | 06-AUG-16:21 | 23.60 | 15.35 | 0.445579E+09 | 545.03 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.811539E+10 | 25454.03 | 10-SEP-15:22 | 22.50 | 14.40 | 0.384796E+09 | 544.96 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.679836E+10 | 12352.17 | 04-OCT-16:00 | 21.10 | 11.40 | 0.393147E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.580035E+10 | 11062.10 | 06-NOV-06:03 | 11.28 | 8.36 | 0.385211E+09 | 544.95 | 03-NOV-13:00 | 11.28 | 8.36 |
December | 0.579186E+10 | 12146.95 | 30-DEC-06:02 | 5.00 | 4.51 | 0.375132E+09 | 544.96 | 05-DEC-14:00 | 5.00 | 4.51 |
Annual Sum or Average | 0.993518E+11 | 0.472357E+10 | ||||||||
Minimum of Months | 0.436594E+10 | 5201.75 | 5.00 | 4.51 | 0.336518E+09 | 535.97 | 5.00 | 4.51 | ||
Maximum of Months | 0.147454E+11 | 29000.16 | 26.30 | 16.19 | 0.445579E+09 | 545.03 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.984476E+09 | 2000.13 | 11-JAN-16:30 | 13.30 | 9.90 | 0.477269E+09 | 724.73 | 11-JAN-14:00 | 13.30 | 9.90 |
February | 0.145188E+10 | 2486.29 | 28-FEB-06:03 | 10.60 | 9.74 | 0.454083E+09 | 835.78 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.259094E+10 | 2794.96 | 10-MAR-14:40 | 16.30 | 11.68 | 0.591460E+09 | 845.59 | 10-MAR-14:09 | 16.30 | 11.68 |
April | 0.312429E+10 | 6085.62 | 27-APR-15:40 | 27.20 | 17.03 | 0.563435E+09 | 845.62 | 27-APR-13:30 | 27.20 | 17.03 |
May | 0.464136E+10 | 6661.56 | 05-MAY-13:30 | 23.85 | 16.52 | 0.643425E+09 | 845.63 | 05-MAY-09:09 | 23.85 | 16.52 |
June | 0.551902E+10 | 7251.93 | 21-JUN-15:30 | 24.70 | 15.68 | 0.653751E+09 | 845.64 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.620994E+10 | 8264.23 | 24-JUL-15:00 | 30.60 | 18.78 | 0.611049E+09 | 845.63 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.648603E+10 | 7931.49 | 25-AUG-14:00 | 27.40 | 18.74 | 0.684934E+09 | 845.69 | 09-AUG-09:00 | 27.40 | 18.74 |
September | 0.421374E+10 | 6032.83 | 12-SEP-14:40 | 24.40 | 16.65 | 0.594627E+09 | 845.63 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.281973E+10 | 3795.12 | 04-OCT-15:30 | 21.40 | 11.45 | 0.568576E+09 | 845.61 | 02-OCT-13:09 | 21.40 | 11.45 |
November | 0.189594E+10 | 2420.25 | 03-NOV-05:03 | 10.60 | 9.38 | 0.509329E+09 | 800.39 | 02-NOV-13:00 | 10.60 | 9.38 |
December | 0.116295E+10 | 1924.66 | 29-DEC-16:10 | 10.40 | 8.63 | 0.466071E+09 | 707.89 | 29-DEC-14:00 | 10.40 | 8.63 |
Annual Sum or Average | 0.411003E+11 | 0.681801E+10 | ||||||||
Minimum of Months | 0.984476E+09 | 1924.66 | 10.40 | 8.63 | 0.454083E+09 | 707.89 | 10.40 | 8.63 | ||
Maximum of Months | 0.648603E+10 | 8264.23 | 30.60 | 18.78 | 0.684934E+09 | 845.69 | 27.40 | 18.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.844995E+09 | 2599.31 | 05-JAN-09:40 | 1.67 | 1.50 | 0.220846E+09 | 406.87 | 05-JAN-09:50 | 2.23 | 2.03 |
February | 0.162878E+10 | 3662.78 | 28-FEB-06:03 | 10.60 | 9.74 | 0.207437E+09 | 466.77 | 08-FEB-09:00 | 10.60 | 9.74 |
March | 0.334169E+10 | 5976.28 | 14-MAR-10:05 | 10.28 | 7.92 | 0.264708E+09 | 521.21 | 14-MAR-10:09 | 10.28 | 7.92 |
April | 0.451644E+10 | 10812.88 | 27-APR-09:00 | 17.80 | 12.21 | 0.260788E+09 | 521.21 | 20-APR-10:09 | 17.80 | 12.21 |
May | 0.575074E+10 | 12424.23 | 14-MAY-09:02 | 17.07 | 11.66 | 0.289997E+09 | 521.23 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.690179E+10 | 21484.25 | 25-JUN-09:12 | 17.07 | 12.34 | 0.300211E+09 | 521.21 | 07-JUN-10:20 | 17.07 | 12.34 |
July | 0.723966E+10 | 22603.64 | 23-JUL-08:42 | 18.72 | 13.76 | 0.283301E+09 | 521.49 | 31-JUL-08:00 | 22.20 | 16.89 |
August | 0.784779E+10 | 22466.18 | 13-AUG-08:22 | 20.20 | 15.50 | 0.316731E+09 | 521.48 | 08-AUG-08:30 | 20.20 | 15.50 |
September | 0.554677E+10 | 13354.49 | 10-SEP-09:32 | 16.83 | 13.52 | 0.266780E+09 | 521.21 | 11-SEP-10:09 | 19.08 | 14.37 |
October | 0.360678E+10 | 7694.89 | 04-OCT-09:00 | 15.60 | 10.49 | 0.252367E+09 | 521.22 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.192425E+10 | 3567.80 | 06-NOV-06:03 | 11.28 | 8.36 | 0.224927E+09 | 465.49 | 02-NOV-10:39 | 11.28 | 8.36 |
December | 0.111811E+10 | 2842.39 | 05-DEC-10:00 | 6.70 | 5.10 | 0.214326E+09 | 427.46 | 05-DEC-09:00 | 6.70 | 5.10 |
Annual Sum or Average | 0.502678E+11 | 0.310242E+10 | ||||||||
Minimum of Months | 0.844995E+09 | 2599.31 | 1.67 | 1.50 | 0.207437E+09 | 406.87 | 2.23 | 2.03 | ||
Maximum of Months | 0.784779E+10 | 22603.64 | 20.20 | 15.50 | 0.316731E+09 | 521.49 | 22.20 | 16.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270095E+10 | 13380.93 | 20-JAN-13:30 | 6.70 | 4.72 | 0.494003E+09 | 845.63 | 20-JAN-14:09 | 6.78 | 4.76 |
February | 0.446622E+10 | 16617.23 | 27-FEB-14:20 | 18.87 | 11.68 | 0.480611E+09 | 845.63 | 08-FEB-10:00 | 18.87 | 11.68 |
March | 0.715208E+10 | 18287.45 | 01-MAR-13:40 | 11.33 | 6.09 | 0.600932E+09 | 846.00 | 01-MAR-14:50 | 13.03 | 7.20 |
April | 0.769861E+10 | 18527.91 | 27-APR-13:10 | 26.10 | 16.37 | 0.559924E+09 | 846.28 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.876846E+10 | 15430.70 | 15-MAY-13:10 | 22.88 | 13.76 | 0.619829E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.900292E+10 | 13471.50 | 28-JUN-13:10 | 24.50 | 15.71 | 0.630117E+09 | 845.68 | 28-JUN-13:30 | 24.70 | 15.69 |
July | 0.105409E+11 | 22995.04 | 30-JUL-14:52 | 27.20 | 18.07 | 0.595640E+09 | 846.28 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.122213E+11 | 31178.51 | 13-AUG-13:42 | 27.08 | 18.72 | 0.670978E+09 | 847.34 | 29-AUG-13:39 | 29.43 | 20.04 |
September | 0.107916E+11 | 29734.04 | 10-SEP-13:32 | 21.67 | 14.47 | 0.579328E+09 | 846.95 | 15-SEP-13:00 | 21.70 | 16.45 |
October | 0.803300E+10 | 30280.49 | 08-OCT-13:02 | 18.17 | 13.70 | 0.569261E+09 | 846.08 | 04-OCT-13:00 | 18.17 | 13.70 |
November | 0.422550E+10 | 14606.49 | 04-NOV-13:30 | 20.85 | 16.00 | 0.512799E+09 | 845.63 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.336901E+10 | 13434.33 | 05-DEC-12:30 | 10.30 | 6.13 | 0.489804E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.889705E+11 | 0.680323E+10 | ||||||||
Minimum of Months | 0.270095E+10 | 13380.93 | 6.70 | 4.72 | 0.480611E+09 | 845.63 | 6.78 | 4.76 | ||
Maximum of Months | 0.122213E+11 | 31178.51 | 27.20 | 18.72 | 0.670978E+09 | 847.34 | 29.43 | 20.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127422E+10 | 3263.74 | 05-JAN-15:50 | 6.20 | 4.71 | 0.303460E+09 | 458.62 | 05-JAN-14:00 | 6.20 | 4.71 |
February | 0.207737E+10 | 6563.16 | 27-FEB-15:30 | 19.70 | 12.30 | 0.287322E+09 | 544.91 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.377135E+10 | 8820.84 | 14-MAR-16:00 | 17.20 | 10.94 | 0.358996E+09 | 544.92 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.481065E+10 | 12726.65 | 26-APR-16:00 | 24.40 | 14.49 | 0.342563E+09 | 544.96 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.638761E+10 | 21962.73 | 07-MAY-16:52 | 21.70 | 16.17 | 0.390107E+09 | 544.96 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.692373E+10 | 21922.44 | 18-JUN-17:01 | 17.12 | 12.23 | 0.400808E+09 | 544.96 | 28-JUN-13:30 | 24.70 | 15.69 |
July | 0.847300E+10 | 24759.37 | 23-JUL-18:41 | 24.68 | 15.75 | 0.384000E+09 | 544.96 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.844223E+10 | 22071.66 | 06-AUG-16:32 | 23.53 | 15.27 | 0.429099E+09 | 545.01 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.613955E+10 | 19493.89 | 10-SEP-16:52 | 22.20 | 14.17 | 0.360577E+09 | 544.95 | 15-SEP-13:00 | 21.70 | 16.45 |
October | 0.401095E+10 | 10212.31 | 04-OCT-16:00 | 21.10 | 11.40 | 0.340189E+09 | 544.91 | 02-OCT-13:00 | 21.10 | 11.40 |
November | 0.239087E+10 | 4064.66 | 04-NOV-15:40 | 20.37 | 15.93 | 0.309867E+09 | 505.66 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.162681E+10 | 3476.43 | 05-DEC-15:40 | 7.40 | 5.40 | 0.295943E+09 | 485.37 | 05-DEC-14:00 | 7.40 | 5.40 |
Annual Sum or Average | 0.563283E+11 | 0.420293E+10 | ||||||||
Minimum of Months | 0.127422E+10 | 3263.74 | 6.20 | 4.71 | 0.287322E+09 | 458.62 | 6.20 | 4.71 | ||
Maximum of Months | 0.847300E+10 | 24759.37 | 24.68 | 16.17 | 0.429099E+09 | 545.01 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364445E+09 | 1977.51 | 11-JAN-16:30 | 13.30 | 9.90 | 0.465206E+09 | 664.52 | 11-JAN-14:00 | 13.30 | 9.90 |
February | 0.788925E+09 | 2483.25 | 28-FEB-15:10 | 13.90 | 10.77 | 0.432400E+09 | 785.91 | 28-FEB-14:00 | 13.90 | 10.77 |
March | 0.185268E+10 | 2605.93 | 10-MAR-15:00 | 16.10 | 11.51 | 0.542263E+09 | 817.87 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.270769E+10 | 6567.25 | 27-APR-15:30 | 27.20 | 17.10 | 0.525795E+09 | 845.63 | 27-APR-13:30 | 27.20 | 17.10 |
May | 0.427365E+10 | 6890.50 | 05-MAY-13:30 | 23.85 | 16.52 | 0.616838E+09 | 845.63 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.531118E+10 | 7795.99 | 21-JUN-15:30 | 24.70 | 15.68 | 0.640422E+09 | 845.64 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.617252E+10 | 9210.58 | 24-JUL-15:00 | 30.60 | 18.78 | 0.604632E+09 | 845.64 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.638772E+10 | 8611.66 | 09-AUG-15:30 | 28.70 | 18.83 | 0.676351E+09 | 845.69 | 09-AUG-09:00 | 28.70 | 18.83 |
September | 0.387548E+10 | 6243.35 | 12-SEP-15:00 | 24.40 | 16.71 | 0.567368E+09 | 845.62 | 07-SEP-13:09 | 24.40 | 16.71 |
October | 0.214670E+10 | 3390.27 | 04-OCT-15:30 | 21.40 | 11.45 | 0.519912E+09 | 840.81 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.102361E+10 | 2315.15 | 02-NOV-14:40 | 13.67 | 11.26 | 0.473540E+09 | 742.94 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.365705E+09 | 1901.43 | 29-DEC-16:20 | 10.20 | 8.50 | 0.448876E+09 | 652.04 | 29-DEC-14:00 | 10.20 | 8.50 |
Annual Sum or Average | 0.352703E+11 | 0.651360E+10 | ||||||||
Minimum of Months | 0.364445E+09 | 1901.43 | 10.20 | 8.50 | 0.432400E+09 | 652.04 | 10.20 | 8.50 | ||
Maximum of Months | 0.638772E+10 | 9210.58 | 30.60 | 18.83 | 0.676351E+09 | 845.69 | 28.70 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357179E+09 | 2462.40 | 18-JAN-06:04 | 2.30 | 1.61 | 0.299420E+09 | 403.39 | 02-JAN-10:00 | 2.30 | 1.61 |
February | 0.100194E+10 | 2900.63 | 27-FEB-15:50 | 19.50 | 12.39 | 0.276005E+09 | 453.35 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.243779E+10 | 4346.46 | 14-MAR-10:00 | 10.00 | 7.75 | 0.349404E+09 | 544.95 | 14-MAR-09:00 | 10.00 | 7.75 |
April | 0.388685E+10 | 10404.70 | 27-APR-09:30 | 18.35 | 12.60 | 0.348372E+09 | 544.96 | 27-APR-13:30 | 26.10 | 16.55 |
May | 0.527333E+10 | 16656.40 | 14-MAY-08:52 | 16.70 | 11.54 | 0.390432E+09 | 544.97 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.666097E+10 | 20709.02 | 25-JUN-09:02 | 16.88 | 12.18 | 0.407507E+09 | 544.97 | 09-JUN-13:09 | 16.88 | 12.18 |
July | 0.717883E+10 | 19847.83 | 30-JUL-09:12 | 21.13 | 15.97 | 0.384116E+09 | 545.73 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.776849E+10 | 21086.87 | 06-AUG-09:42 | 16.80 | 13.46 | 0.430003E+09 | 545.69 | 08-AUG-09:00 | 23.60 | 17.64 |
September | 0.504080E+10 | 20466.21 | 10-SEP-09:22 | 16.65 | 13.51 | 0.357235E+09 | 544.97 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.270181E+10 | 6630.81 | 04-OCT-09:30 | 16.40 | 10.73 | 0.333125E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.104060E+10 | 2878.03 | 02-NOV-10:40 | 12.43 | 10.47 | 0.299666E+09 | 450.74 | 02-NOV-13:00 | 14.40 | 11.37 |
December | 0.420915E+09 | 2491.24 | 27-DEC-06:04 | 4.90 | 4.18 | 0.289158E+09 | 404.02 | 05-DEC-10:30 | 4.90 | 4.18 |
Annual Sum or Average | 0.437695E+11 | 0.416444E+10 | ||||||||
Minimum of Months | 0.357179E+09 | 2462.40 | 2.30 | 1.61 | 0.276005E+09 | 403.39 | 2.30 | 1.61 | ||
Maximum of Months | 0.776849E+10 | 21086.87 | 21.13 | 15.97 | 0.430003E+09 | 545.73 | 26.10 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167106E+10 | 11330.79 | 20-JAN-13:30 | 6.70 | 4.72 | 0.478392E+09 | 845.63 | 20-JAN-14:20 | 6.87 | 4.79 |
February | 0.319142E+10 | 15055.18 | 27-FEB-14:30 | 19.15 | 11.80 | 0.464483E+09 | 845.63 | 07-FEB-14:09 | 19.15 | 11.80 |
March | 0.560469E+10 | 17232.11 | 14-MAR-13:40 | 15.20 | 10.17 | 0.575241E+09 | 845.65 | 14-MAR-13:00 | 15.60 | 10.50 |
April | 0.674987E+10 | 23627.19 | 02-APR-13:22 | 18.90 | 11.09 | 0.539143E+09 | 846.38 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.813509E+10 | 24827.73 | 14-MAY-14:52 | 23.30 | 12.44 | 0.599453E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.876918E+10 | 14184.43 | 28-JUN-13:20 | 24.60 | 15.70 | 0.614503E+09 | 845.67 | 09-JUN-13:09 | 24.60 | 15.70 |
July | 0.105291E+11 | 23138.40 | 30-JUL-13:53 | 26.70 | 17.68 | 0.586272E+09 | 846.36 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.121787E+11 | 30622.98 | 06-AUG-13:02 | 21.85 | 15.38 | 0.660376E+09 | 847.11 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.101720E+11 | 34535.52 | 10-SEP-14:01 | 22.30 | 14.59 | 0.560725E+09 | 847.07 | 15-SEP-13:00 | 21.70 | 16.45 |
October | 0.658984E+10 | 30450.24 | 08-OCT-13:42 | 19.63 | 14.09 | 0.543499E+09 | 846.06 | 04-OCT-13:00 | 19.63 | 14.09 |
November | 0.266488E+10 | 13611.82 | 04-NOV-13:30 | 20.85 | 16.00 | 0.486814E+09 | 845.64 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.198904E+10 | 10605.01 | 05-DEC-12:30 | 10.30 | 6.13 | 0.472389E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.782449E+11 | 0.658129E+10 | ||||||||
Minimum of Months | 0.167106E+10 | 10605.01 | 6.70 | 4.72 | 0.464483E+09 | 845.63 | 6.87 | 4.79 | ||
Maximum of Months | 0.121787E+11 | 34535.52 | 26.70 | 17.68 | 0.660376E+09 | 847.11 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.637293E+09 | 3189.19 | 05-JAN-15:50 | 6.20 | 4.71 | 0.300506E+09 | 435.75 | 05-JAN-14:00 | 6.20 | 4.71 |
February | 0.133688E+10 | 5825.55 | 27-FEB-15:30 | 19.70 | 12.30 | 0.281094E+09 | 543.46 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.284661E+10 | 8536.70 | 14-MAR-16:00 | 17.20 | 10.94 | 0.345573E+09 | 543.66 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.423128E+10 | 12845.89 | 26-APR-16:00 | 24.40 | 14.49 | 0.328749E+09 | 544.96 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.603910E+10 | 25586.73 | 07-MAY-16:41 | 21.78 | 16.19 | 0.376089E+09 | 544.96 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.677624E+10 | 22963.83 | 18-JUN-17:01 | 17.12 | 12.23 | 0.390382E+09 | 544.94 | 20-JUN-13:09 | 23.30 | 15.62 |
July | 0.847759E+10 | 24348.22 | 23-JUL-17:02 | 26.60 | 15.64 | 0.377206E+09 | 544.96 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.840748E+10 | 23882.96 | 06-AUG-17:01 | 23.47 | 15.14 | 0.420808E+09 | 545.01 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.577802E+10 | 22901.87 | 10-SEP-15:22 | 22.50 | 14.40 | 0.347194E+09 | 544.94 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.313604E+10 | 10110.24 | 04-OCT-16:00 | 21.10 | 11.40 | 0.325319E+09 | 544.44 | 04-OCT-13:00 | 21.10 | 11.40 |
November | 0.137464E+10 | 3975.21 | 04-NOV-15:40 | 20.37 | 15.93 | 0.302074E+09 | 479.36 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.769837E+09 | 3344.65 | 05-DEC-15:30 | 8.05 | 5.82 | 0.291404E+09 | 455.60 | 05-DEC-14:00 | 8.05 | 5.82 |
Annual Sum or Average | 0.498110E+11 | 0.408640E+10 | ||||||||
Minimum of Months | 0.637293E+09 | 3189.19 | 6.20 | 4.71 | 0.281094E+09 | 435.75 | 6.20 | 4.71 | ||
Maximum of Months | 0.847759E+10 | 25586.73 | 26.60 | 16.19 | 0.420808E+09 | 545.01 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176846E+10 | 4613.25 | 04-JAN-06:08 | 5.18 | 4.57 | 0.00 | 0.00 | 01-JAN-00:10 | 5.18 | 4.57 |
February | 0.227484E+10 | 5414.01 | 07-FEB-06:10 | 2.88 | 2.44 | 0.00 | 0.00 | 01-FEB-00:10 | 2.88 | 2.44 |
March | 0.413930E+10 | 5665.23 | 20-MAR-05:15 | 5.97 | 4.27 | 0.00 | 0.00 | 01-MAR-00:10 | 5.97 | 4.27 |
April | 0.524982E+10 | 8200.34 | 03-APR-05:13 | 10.60 | 9.99 | 0.00 | 0.00 | 01-APR-00:10 | 10.60 | 9.99 |
May | 0.580444E+10 | 8694.24 | 08-MAY-05:13 | 9.60 | 9.49 | 0.00 | 0.00 | 01-MAY-00:10 | 9.60 | 9.49 |
June | 0.701532E+10 | 11238.33 | 12-JUN-05:13 | 14.40 | 13.42 | 0.00 | 0.00 | 01-JUN-00:10 | 14.40 | 13.42 |
July | 0.827168E+10 | 10382.83 | 10-JUL-05:13 | 13.13 | 11.62 | 0.00 | 0.00 | 01-JUL-00:10 | 13.13 | 11.62 |
August | 0.934057E+10 | 10389.48 | 28-AUG-05:13 | 14.87 | 13.94 | 0.00 | 0.00 | 01-AUG-00:10 | 14.87 | 13.94 |
September | 0.628781E+10 | 10465.02 | 05-SEP-05:13 | 10.77 | 9.27 | 0.00 | 0.00 | 01-SEP-00:10 | 10.77 | 9.27 |
October | 0.475418E+10 | 9343.48 | 10-OCT-05:15 | 12.20 | 11.16 | 0.00 | 0.00 | 01-OCT-00:10 | 12.20 | 11.16 |
November | 0.339393E+10 | 8000.50 | 06-NOV-06:13 | 11.47 | 8.44 | 0.00 | 0.00 | 01-NOV-00:10 | 11.47 | 8.44 |
December | 0.260920E+10 | 5474.91 | 30-DEC-06:08 | 5.00 | 4.51 | 0.00 | 0.00 | 01-DEC-00:10 | 5.00 | 4.51 |
Annual Sum or Average | 0.609095E+11 | 0.00 | ||||||||
Minimum of Months | 0.176846E+10 | 4613.25 | 2.88 | 2.44 | 0.00 | 0.00 | 2.88 | 2.44 | ||
Maximum of Months | 0.934057E+10 | 11238.33 | 14.87 | 13.94 | 0.00 | 0.00 | 14.87 | 13.94 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351244E+09 | 5293.39 | 14-JAN-05:01 | 2.20 | 1.44 | 0.00 | 0.00 | 01-JAN-00:10 | 2.20 | 1.44 |
February | 0.823332E+09 | 4219.12 | 17-FEB-05:01 | 1.10 | -0.4 | 0.00 | 0.00 | 01-FEB-00:10 | 1.10 | -0.4 |
March | 0.185434E+10 | 4351.01 | 22-MAR-05:10 | 6.10 | 5.58 | 0.00 | 0.00 | 01-MAR-00:10 | 6.10 | 5.58 |
April | 0.251384E+10 | 5916.88 | 28-APR-05:10 | 11.10 | 9.92 | 0.00 | 0.00 | 01-APR-00:10 | 11.10 | 9.92 |
May | 0.393896E+10 | 5964.21 | 08-MAY-05:13 | 9.60 | 9.49 | 0.00 | 0.00 | 01-MAY-00:10 | 9.60 | 9.49 |
June | 0.482317E+10 | 6787.55 | 12-JUN-05:13 | 14.40 | 13.42 | 0.00 | 0.00 | 01-JUN-00:10 | 14.40 | 13.42 |
July | 0.575449E+10 | 6459.31 | 10-JUL-05:13 | 13.13 | 11.62 | 0.00 | 0.00 | 01-JUL-00:10 | 13.13 | 11.62 |
August | 0.654594E+10 | 7422.50 | 26-AUG-05:13 | 14.77 | 14.11 | 0.00 | 0.00 | 01-AUG-00:10 | 14.77 | 14.11 |
September | 0.472818E+10 | 7145.36 | 12-SEP-05:13 | 12.03 | 11.22 | 0.00 | 0.00 | 01-SEP-00:10 | 12.03 | 11.22 |
October | 0.272528E+10 | 5797.09 | 12-OCT-05:10 | 6.78 | 5.58 | 0.00 | 0.00 | 01-OCT-00:10 | 6.78 | 5.58 |
November | 0.129079E+10 | 4329.65 | 13-NOV-06:01 | 1.70 | 1.50 | 0.00 | 0.00 | 01-NOV-00:10 | 1.70 | 1.50 |
December | 0.709285E+09 | 4727.68 | 09-DEC-06:02 | 0.87 | 0.59 | 0.00 | 0.00 | 01-DEC-00:10 | 0.87 | 0.59 |
Annual Sum or Average | 0.360589E+11 | 0.00 | ||||||||
Minimum of Months | 0.351244E+09 | 4219.12 | 0.87 | -0.4 | 0.00 | 0.00 | 0.87 | -0.4 | ||
Maximum of Months | 0.654594E+10 | 7422.50 | 14.77 | 14.11 | 0.00 | 0.00 | 14.77 | 14.11 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 423970.27 | 337.52 | 11-JAN-17:30 | 12.50 | 9.44 | 0.00 | 0.00 | 01-JAN-00:10 | 12.50 | 9.44 |
February | 0.185732E+09 | 2941.89 | 27-FEB-15:40 | 19.60 | 12.34 | 0.00 | 0.00 | 01-FEB-00:10 | 19.60 | 12.34 |
March | 0.104574E+10 | 5676.19 | 14-MAR-15:10 | 16.28 | 10.42 | 0.00 | 0.00 | 01-MAR-00:10 | 16.28 | 10.42 |
April | 0.319145E+10 | 15565.95 | 27-APR-14:20 | 26.47 | 16.98 | 0.00 | 0.00 | 01-APR-00:10 | 26.47 | 16.98 |
May | 0.575695E+10 | 15954.99 | 15-MAY-14:20 | 23.30 | 13.21 | 0.00 | 0.00 | 01-MAY-00:10 | 23.30 | 13.21 |
June | 0.750422E+10 | 16556.08 | 28-JUN-14:30 | 25.55 | 15.61 | 0.00 | 0.00 | 01-JUN-00:10 | 25.55 | 15.61 |
July | 0.961198E+10 | 18202.73 | 24-JUL-14:00 | 29.40 | 18.12 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 18.12 |
August | 0.952323E+10 | 19089.03 | 10-AUG-14:30 | 29.80 | 19.03 | 0.00 | 0.00 | 01-AUG-00:10 | 29.80 | 19.03 |
September | 0.503096E+10 | 14273.53 | 14-SEP-15:00 | 23.90 | 16.96 | 0.00 | 0.00 | 01-SEP-00:10 | 23.90 | 16.96 |
October | 0.143228E+10 | 8895.90 | 04-OCT-15:00 | 21.70 | 11.49 | 0.00 | 0.00 | 01-OCT-00:10 | 21.70 | 11.49 |
November | 0.148667E+09 | 3731.62 | 04-NOV-13:50 | 21.02 | 15.96 | 0.00 | 0.00 | 01-NOV-00:10 | 21.02 | 15.96 |
December | 48896.05 | 112.33 | 16-DEC-17:25 | 7.20 | 6.51 | 0.00 | 0.00 | 01-DEC-00:10 | 7.20 | 6.51 |
Annual Sum or Average | 0.434317E+11 | 0.00 | ||||||||
Minimum of Months | 48896.05 | 112.33 | 7.20 | 6.51 | 0.00 | 0.00 | 7.20 | 6.51 | ||
Maximum of Months | 0.961198E+10 | 19089.03 | 29.80 | 19.03 | 0.00 | 0.00 | 29.80 | 19.03 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296784E+10 | 1980.63 | 05-JAN-16:10 | 5.73 | 4.38 | 95230013.86 | 126.82 | 17-JAN-14:39 | 4.40 | 2.31 |
February | 0.776534E+10 | 4090.08 | 07-FEB-16:50 | 7.30 | 3.84 | 86397257.69 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.142238E+11 | 6986.26 | 31-MAR-24:00 | 8.00 | 7.45 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.00 | 7.45 |
April | 0.189050E+11 | 8188.89 | 26-APR-17:50 | 23.07 | 13.57 | 91605320.37 | 126.83 | 28-APR-09:00 | 11.70 | 11.07 |
May | 0.439244E+10 | 3482.01 | 31-MAY-24:00 | 13.00 | 10.11 | 99236185.53 | 126.84 | 31-MAY-13:00 | 13.00 | 10.11 |
June | 0.931958E+10 | 5349.26 | 30-JUN-24:00 | 15.50 | 12.58 | 98960913.46 | 126.84 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.148227E+11 | 7263.80 | 31-JUL-23:50 | 17.63 | 14.21 | 91884250.58 | 126.84 | 11-JUL-09:20 | 17.63 | 14.21 |
August | 0.198333E+11 | 8556.89 | 06-AUG-18:40 | 22.47 | 15.07 | 0.103239E+09 | 126.83 | 02-AUG-09:09 | 22.47 | 15.07 |
September | 0.431577E+10 | 3323.84 | 30-SEP-24:00 | 14.30 | 12.32 | 91612126.61 | 126.84 | 14-SEP-13:30 | 14.30 | 12.32 |
October | 0.921647E+10 | 4992.56 | 31-OCT-24:00 | 9.10 | 7.85 | 95231797.42 | 126.83 | 26-OCT-13:00 | 9.10 | 7.85 |
November | 0.136130E+11 | 5794.56 | 10-NOV-16:00 | 8.90 | 6.48 | 94301498.06 | 126.83 | 03-NOV-13:00 | 8.90 | 6.48 |
December | 0.189810E+11 | 7813.66 | 05-DEC-15:50 | 6.75 | 4.97 | 91880928.14 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.138356E+12 | 0.114282E+10 | ||||||||
Minimum of Months | 0.296784E+10 | 1980.63 | 5.73 | 3.84 | 86397257.69 | 126.82 | 4.40 | 2.31 | ||
Maximum of Months | 0.198333E+11 | 8556.89 | 23.07 | 15.07 | 0.103239E+09 | 126.84 | 22.47 | 15.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.933393E+09 | 1566.02 | 05-JAN-16:20 | 5.37 | 4.14 | 95078910.00 | 126.82 | 03-JAN-14:50 | 5.37 | 4.14 |
February | 0.577121E+10 | 3724.44 | 08-FEB-16:50 | 6.78 | 3.36 | 86397188.74 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.121993E+11 | 6128.85 | 31-MAR-24:00 | 8.00 | 7.45 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.00 | 7.45 |
April | 0.171244E+11 | 7759.40 | 26-APR-17:50 | 23.07 | 13.57 | 91605381.57 | 126.83 | 28-APR-09:00 | 11.70 | 11.07 |
May | 0.354080E+10 | 3225.97 | 31-MAY-24:00 | 13.00 | 10.11 | 99235920.47 | 126.84 | 31-MAY-13:00 | 13.00 | 10.11 |
June | 0.841426E+10 | 4993.39 | 30-JUN-24:00 | 15.50 | 12.58 | 98960655.94 | 126.84 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.138908E+11 | 7001.23 | 31-JUL-24:00 | 17.40 | 14.08 | 91884521.97 | 126.84 | 11-JUL-09:50 | 17.40 | 14.08 |
August | 0.186783E+11 | 7922.39 | 06-AUG-18:17 | 23.13 | 15.18 | 0.103240E+09 | 126.83 | 02-AUG-09:00 | 23.13 | 15.18 |
September | 0.355762E+10 | 2921.77 | 30-SEP-24:00 | 14.30 | 12.32 | 91611585.35 | 126.84 | 13-SEP-13:00 | 14.30 | 12.32 |
October | 0.762567E+10 | 4152.54 | 31-OCT-24:00 | 9.10 | 7.85 | 95231654.28 | 126.83 | 26-OCT-13:00 | 9.10 | 7.85 |
November | 0.113096E+11 | 5322.17 | 10-NOV-16:10 | 8.53 | 6.27 | 94301353.10 | 126.83 | 01-NOV-13:00 | 8.53 | 6.27 |
December | 0.159863E+11 | 7133.60 | 05-DEC-16:00 | 6.10 | 4.53 | 91880940.74 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.119032E+12 | 0.114266E+10 | ||||||||
Minimum of Months | 0.933393E+09 | 1566.02 | 5.37 | 3.36 | 86397188.74 | 126.82 | 5.37 | 4.14 | ||
Maximum of Months | 0.186783E+11 | 7922.39 | 23.13 | 15.18 | 0.103240E+09 | 126.84 | 23.13 | 15.18 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377398E+09 | 1398.26 | 05-JAN-16:20 | 5.37 | 4.14 | 93658219.14 | 127.65 | 18-JAN-10:30 | 4.15 | 3.68 |
February | 0.422820E+10 | 3604.74 | 27-FEB-16:20 | 19.23 | 12.34 | 86397237.04 | 126.83 | 24-FEB-10:00 | 19.23 | 12.34 |
March | 0.109083E+11 | 5688.93 | 02-MAR-17:00 | 12.80 | 8.57 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 14.40 | 11.89 |
April | 0.163019E+11 | 7828.54 | 26-APR-17:50 | 23.07 | 13.57 | 91605399.43 | 126.83 | 28-APR-09:00 | 11.70 | 11.07 |
May | 0.299258E+10 | 3137.07 | 31-MAY-23:40 | 13.33 | 10.48 | 99236081.78 | 126.84 | 31-MAY-13:00 | 13.33 | 10.48 |
June | 0.816117E+10 | 4883.63 | 30-JUN-24:00 | 15.50 | 12.58 | 98960649.36 | 126.84 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.137439E+11 | 6983.01 | 31-JUL-24:00 | 17.40 | 14.08 | 91884531.98 | 126.84 | 11-JUL-13:00 | 17.40 | 14.08 |
August | 0.185026E+11 | 8047.02 | 06-AUG-18:38 | 22.47 | 15.07 | 0.103240E+09 | 126.83 | 30-AUG-09:09 | 19.33 | 17.24 |
September | 0.303537E+10 | 2489.48 | 30-SEP-23:30 | 14.15 | 12.18 | 91611245.69 | 126.84 | 14-SEP-13:00 | 14.15 | 12.18 |
October | 0.648482E+10 | 4128.66 | 04-OCT-16:50 | 20.68 | 11.37 | 95231605.90 | 126.83 | 26-OCT-13:00 | 13.30 | 12.35 |
November | 0.975749E+10 | 5171.12 | 10-NOV-16:00 | 8.90 | 6.48 | 94301359.79 | 126.83 | 01-NOV-13:00 | 8.90 | 6.48 |
December | 0.140801E+11 | 6953.46 | 05-DEC-16:00 | 6.10 | 4.53 | 91880950.71 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.108574E+12 | 0.114124E+10 | ||||||||
Minimum of Months | 0.377398E+09 | 1398.26 | 5.37 | 4.14 | 86397237.04 | 126.82 | 4.15 | 3.68 | ||
Maximum of Months | 0.185026E+11 | 8047.02 | 23.07 | 15.07 | 0.103240E+09 | 127.65 | 19.33 | 17.24 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237297E+12 | 91721.74 | 12-JAN-17:00 | 7.20 | 5.41 | 0.206156E+10 | 2746.41 | 09-JAN-14:00 | 7.20 | 5.41 |
February | 0.435756E+12 | 184019.63 | 28-FEB-17:00 | 14.40 | 10.82 | 0.187052E+10 | 2746.64 | 13-FEB-10:09 | 14.40 | 10.82 |
March | 0.730114E+12 | 358670.22 | 31-MAR-24:00 | 8.00 | 7.45 | 0.223504E+10 | 2747.98 | 24-MAR-09:09 | 8.00 | 7.45 |
April | 0.943994E+12 | 368449.01 | 28-APR-16:00 | 16.70 | 12.02 | 0.199253E+10 | 3117.43 | 27-APR-13:00 | 16.70 | 12.02 |
May | 0.241712E+12 | 176445.04 | 31-MAY-24:00 | 13.00 | 10.11 | 0.214819E+10 | 2745.74 | 31-MAY-13:00 | 13.00 | 10.11 |
June | 0.471183E+12 | 268051.58 | 30-JUN-24:00 | 15.50 | 12.58 | 0.214221E+10 | 2745.81 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.733046E+12 | 360487.83 | 31-JUL-24:00 | 17.40 | 14.08 | 0.198901E+10 | 2745.59 | 11-JUL-09:30 | 17.40 | 14.08 |
August | 0.977722E+12 | 370336.62 | 29-AUG-21:14 | 21.10 | 16.07 | 0.229771E+10 | 3223.39 | 29-AUG-13:00 | 21.10 | 16.07 |
September | 0.235523E+12 | 175632.48 | 30-SEP-24:00 | 14.30 | 12.32 | 0.198320E+10 | 2746.03 | 25-SEP-09:00 | 14.30 | 12.32 |
October | 0.486584E+12 | 267382.27 | 31-OCT-24:00 | 9.10 | 7.85 | 0.206149E+10 | 2745.68 | 26-OCT-13:00 | 9.10 | 7.85 |
November | 0.707629E+12 | 276655.69 | 06-NOV-17:00 | 11.70 | 10.80 | 0.204140E+10 | 2746.99 | 16-NOV-10:09 | 6.88 | 2.51 |
December | 0.975621E+12 | 367998.47 | 04-DEC-17:00 | 6.70 | 4.39 | 0.198916E+10 | 2746.67 | 22-DEC-10:09 | 1.97 | 0.01 |
Annual Sum or Average | 0.717618E+13 | 0.248120E+11 | ||||||||
Minimum of Months | 0.235523E+12 | 91721.74 | 6.70 | 4.39 | 0.187052E+10 | 2745.59 | 1.97 | 0.01 | ||
Maximum of Months | 0.977722E+12 | 370336.62 | 21.10 | 16.07 | 0.229771E+10 | 3223.39 | 21.10 | 16.07 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211766E+09 | 11842.99 | 12-JAN-05:04 | 6.70 |
February | 0.110534E+09 | 12091.41 | 21-FEB-05:25 | 1.70 |
March | 0.258022E+09 | 11876.77 | 04-MAR-05:04 | 5.60 |
April | 0.245358E+09 | 13550.19 | 13-APR-04:33 | 7.97 |
May | 0.339911E+09 | 12016.41 | 18-MAY-04:05 | 6.52 |
June | 0.355815E+09 | 14104.79 | 20-JUN-03:53 | 13.30 |
July | 0.373315E+09 | 13492.02 | 23-JUL-22:53 | 20.00 |
August | 0.310797E+09 | 13545.10 | 07-AUG-02:53 | 14.70 |
September | 0.489340E+09 | 12033.07 | 25-SEP-03:25 | 13.30 |
October | 0.388833E+09 | 11933.51 | 11-OCT-03:04 | 7.80 |
November | 0.401797E+09 | 12136.63 | 14-NOV-04:15 | 5.00 |
December | 0.268547E+09 | 11778.73 | 07-DEC-04:14 | 3.30 |
Annual Sum or Average | 0.375404E+10 | |||
Minimum of Months | 0.110534E+09 | 11778.73 | 1.70 | |
Maximum of Months | 0.489340E+09 | 14104.79 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169602E+09 | 36517.85 | 02-JAN-05:01 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.169602E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.169602E+09 | 36517.85 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210402E+10 | 75883.59 | 17-JAN-04:01 | 1.70 |
February | 0.863663E+09 | 73403.70 | 21-FEB-04:01 | 1.70 |
March | 0.184819E+09 | 66602.86 | 06-MAR-05:01 | 6.70 |
April | 109007.95 | 726.72 | 17-APR-05:03 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 29617585.83 | 59803.09 | 16-OCT-05:03 | 7.12 |
November | 0.461236E+09 | 67655.83 | 13-NOV-05:01 | 1.20 |
December | 0.106152E+10 | 74098.12 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.470498E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.210402E+10 | 75883.59 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28863.25 | 192.42 | 09-JAN-06:05 | -1.5 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 28863.25 | |||
Minimum of Months | 0.00 | 0.00 | -1.5 | |
Maximum of Months | 28863.25 | 192.42 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 315854.09 | 1184.87 | 06-JAN-06:03 | -1.8 |
February | 497439.95 | 4574.46 | 14-FEB-06:01 | -0.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 915160.71 | 1820.96 | 12-DEC-06:03 | 0.87 |
Annual Sum or Average | 1728454.74 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 915160.71 | 4574.46 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24590613.20 | 9626.24 | 17-JAN-06:03 | 1.20 |
February | 5469999.36 | 8544.61 | 14-FEB-06:01 | -0.4 |
March | 643235.21 | 7504.41 | 06-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 1291770.05 | 8116.87 | 24-NOV-06:01 | 2.02 |
December | 4995550.21 | 8459.03 | 26-DEC-06:03 | -0.8 |
Annual Sum or Average | 36991168.03 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 24590613.20 | 9626.24 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116763E+10 | 11643.68 | 02-JAN-04:01 | 6.60 |
February | 0.480683E+09 | 10847.12 | 21-FEB-04:01 | 1.70 |
March | 74917210.07 | 9920.42 | 06-MAR-05:01 | 6.70 |
April | 8569611.42 | 8850.49 | 11-APR-05:03 | 5.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 13435795.97 | 9276.60 | 30-OCT-05:03 | 7.20 |
November | 0.180457E+09 | 9793.25 | 27-NOV-05:01 | 12.12 |
December | 0.623799E+09 | 10762.77 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.254949E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.116763E+10 | 11643.68 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.785851E+09 | 14772.66 | 02-JAN-04:01 | 6.60 |
February | 0.302044E+09 | 13521.59 | 21-FEB-05:01 | 1.70 |
March | 53197261.87 | 12108.83 | 06-MAR-05:01 | 6.70 |
April | 10957388.62 | 8513.43 | 11-APR-05:03 | 5.60 |
May | 424854.38 | 2594.28 | 18-MAY-05:03 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 91493.42 | 609.96 | 27-SEP-05:08 | 7.38 |
October | 12678135.26 | 9349.29 | 28-OCT-05:02 | 8.22 |
November | 0.143607E+09 | 12131.45 | 30-NOV-05:01 | 5.60 |
December | 0.479955E+09 | 13401.43 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.178881E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.785851E+09 | 14772.66 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.785111E+09 | 21382.67 | 02-JAN-04:01 | 6.60 |
February | 0.251492E+09 | 19117.45 | 21-FEB-05:01 | 1.70 |
March | 38427384.36 | 17538.21 | 06-MAR-05:01 | 6.70 |
April | 7449892.49 | 9504.04 | 11-APR-05:03 | 5.60 |
May | 510007.40 | 3365.91 | 18-MAY-05:03 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 5038858.77 | 12632.96 | 28-OCT-05:02 | 8.22 |
November | 0.131205E+09 | 17657.11 | 30-NOV-05:01 | 5.60 |
December | 0.464961E+09 | 19286.68 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.168419E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.785111E+09 | 21382.67 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.464352E+09 | 13725.61 | 02-JAN-04:01 | 6.60 |
February | 0.166126E+09 | 12493.61 | 21-FEB-05:01 | 1.70 |
March | 20647274.60 | 10754.44 | 06-MAR-06:01 | 6.70 |
April | 2289079.94 | 3801.62 | 18-APR-05:03 | 3.30 |
May | 193211.03 | 1288.07 | 18-MAY-05:03 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 2090654.10 | 6528.15 | 28-OCT-05:02 | 8.22 |
November | 62119663.23 | 11009.91 | 13-NOV-06:01 | 1.70 |
December | 0.213619E+09 | 12465.38 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.931437E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.464352E+09 | 13725.61 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.427175E+10 | 13328.18 | 16-JAN-08:23 | -0.9 |
February | 0.266529E+10 | 13355.43 | 19-FEB-08:63 | -4.7 |
March | 0.976340E+09 | 12988.82 | 06-MAR-04:01 | 6.70 |
April | 0.331590E+09 | 11554.72 | 11-APR-04:01 | 5.10 |
May | 31318663.32 | 10355.82 | 18-MAY-05:03 | 5.60 |
June | 939823.88 | 5021.90 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 5961192.33 | 5916.21 | 27-SEP-05:03 | 7.38 |
October | 0.403014E+09 | 11913.68 | 30-OCT-04:01 | 7.20 |
November | 0.157143E+10 | 12901.48 | 13-NOV-04:01 | 1.60 |
December | 0.330541E+10 | 13205.68 | 26-DEC-03:53 | -1.1 |
Annual Sum or Average | 0.135630E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.7 | |
Maximum of Months | 0.427175E+10 | 13355.43 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267309E+10 | 16856.24 | 17-JAN-04:01 | 1.70 |
February | 0.150221E+10 | 16843.11 | 21-FEB-04:01 | 1.70 |
March | 0.562161E+09 | 16800.04 | 06-MAR-04:01 | 6.70 |
April | 0.184161E+09 | 14940.22 | 11-APR-04:01 | 5.10 |
May | 27786712.93 | 11527.75 | 19-MAY-05:02 | 7.88 |
June | 2360092.13 | 6382.33 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 5738000.71 | 6259.56 | 27-SEP-05:03 | 7.38 |
October | 0.259267E+09 | 14936.63 | 30-OCT-04:01 | 7.20 |
November | 0.100651E+10 | 16743.52 | 13-NOV-04:01 | 1.60 |
December | 0.208825E+10 | 16916.19 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.831153E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.267309E+10 | 16916.19 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303424E+10 | 25309.43 | 17-JAN-04:01 | 1.70 |
February | 0.155791E+10 | 25257.50 | 21-FEB-04:01 | 1.70 |
March | 0.664917E+09 | 24966.30 | 06-MAR-04:01 | 6.70 |
April | 0.271624E+09 | 22213.38 | 11-APR-04:01 | 5.10 |
May | 40602543.77 | 13821.62 | 18-MAY-05:03 | 5.60 |
June | 2156852.93 | 7519.76 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 5339528.06 | 6315.14 | 27-SEP-05:03 | 7.38 |
October | 0.273613E+09 | 21819.27 | 16-OCT-04:01 | 7.20 |
November | 0.117889E+10 | 23904.76 | 13-NOV-04:01 | 1.60 |
December | 0.245597E+10 | 25390.64 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.948527E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.303424E+10 | 25390.64 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189847E+10 | 17273.72 | 17-JAN-04:01 | 1.70 |
February | 0.934970E+09 | 17221.05 | 21-FEB-04:01 | 1.70 |
March | 0.356069E+09 | 16246.33 | 06-MAR-04:01 | 6.70 |
April | 0.117657E+09 | 14582.67 | 11-APR-04:01 | 5.10 |
May | 16740215.15 | 8774.78 | 18-MAY-05:03 | 5.60 |
June | 118452.62 | 789.68 | 14-JUN-05:03 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 162462.63 | 360.58 | 26-SEP-05:08 | 13.30 |
October | 0.135602E+09 | 14311.50 | 30-OCT-04:01 | 7.20 |
November | 0.597027E+09 | 15465.68 | 30-NOV-05:01 | 5.60 |
December | 0.125853E+10 | 17301.26 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.531534E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.189847E+10 | 17301.26 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102861E+09 | 12061.50 | 30-JAN-06:01 | 6.02 |
February | 71808375.52 | 12970.96 | 21-FEB-05:01 | 1.70 |
March | 92171909.02 | 12538.67 | 06-MAR-05:01 | 6.70 |
April | 0.140454E+09 | 12946.61 | 10-APR-03:02 | 10.50 |
May | 91987925.21 | 11317.46 | 01-MAY-03:02 | 11.78 |
June | 90019912.91 | 10128.36 | 12-JUN-03:02 | 15.00 |
July | 0.126906E+09 | 11807.26 | 17-JUL-03:02 | 14.90 |
August | 0.121872E+09 | 11616.39 | 04-AUG-03:02 | 13.92 |
September | 64635811.04 | 9028.99 | 18-SEP-03:02 | 12.88 |
October | 98528983.82 | 11251.43 | 23-OCT-03:02 | 10.60 |
November | 91899387.82 | 13269.18 | 27-NOV-04:02 | 13.12 |
December | 98483658.09 | 13739.50 | 28-DEC-05:01 | 8.98 |
Annual Sum or Average | 0.119163E+10 | |||
Minimum of Months | 64635811.04 | 9028.99 | 1.70 | |
Maximum of Months | 0.140454E+09 | 13739.50 | 15.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194028E+10 | 12989.97 | 02-JAN-06:13 | 6.10 |
February | 0.777670E+09 | 7651.13 | 28-FEB-06:03 | 10.60 |
March | 0.195871E+09 | 8087.34 | 15-MAR-05:03 | 8.03 |
April | 68213746.93 | 7783.89 | 10-APR-05:03 | 8.80 |
May | 64630695.94 | 7075.33 | 01-MAY-04:03 | 12.20 |
June | 63356306.66 | 7000.92 | 12-JUN-03:02 | 15.00 |
July | 67566980.43 | 7977.48 | 17-JUL-03:02 | 14.90 |
August | 54105577.25 | 7284.59 | 28-AUG-03:02 | 16.12 |
September | 53153355.65 | 7785.81 | 10-SEP-16:12 | 22.20 |
October | 93135600.36 | 7482.10 | 26-OCT-05:03 | 12.20 |
November | 0.310681E+09 | 7736.24 | 02-NOV-05:03 | 10.50 |
December | 0.852002E+09 | 6404.39 | 07-DEC-06:03 | 4.27 |
Annual Sum or Average | 0.454067E+10 | |||
Minimum of Months | 53153355.65 | 6404.39 | 4.27 | |
Maximum of Months | 0.194028E+10 | 12989.97 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.800755E+10 | 22207.45 | 17-JAN-05:12 | 1.50 |
February | 0.493301E+10 | 20762.55 | 21-FEB-05:12 | 1.70 |
March | 0.254813E+10 | 13621.77 | 06-MAR-06:13 | 6.70 |
April | 0.115380E+10 | 15100.62 | 14-APR-05:02 | 9.40 |
May | 0.422733E+09 | 15673.63 | 04-MAY-05:03 | 10.78 |
June | 0.157549E+09 | 16289.47 | 19-JUN-05:03 | 11.20 |
July | 93297967.54 | 14659.25 | 07-JUL-05:03 | 11.47 |
August | 0.113689E+09 | 14804.56 | 21-AUG-05:03 | 11.20 |
September | 0.310855E+09 | 15096.17 | 08-SEP-05:03 | 10.18 |
October | 0.149428E+10 | 16190.90 | 05-OCT-05:03 | 8.30 |
November | 0.368195E+10 | 15130.00 | 13-NOV-06:13 | 1.70 |
December | 0.660261E+10 | 21290.39 | 26-DEC-05:23 | -0.6 |
Annual Sum or Average | 0.295195E+11 | |||
Minimum of Months | 93297967.54 | 13621.77 | -0.6 | |
Maximum of Months | 0.800755E+10 | 22207.45 | 11.47 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205166E+09 | 554.27 | 01-JAN-22:20 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.205166E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.205166E+09 | 554.27 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.706104E+09 | 607.93 | 08-JAN-17:15 | 2.57 |
February | 24634020.72 | 434.67 | 19-FEB-10:37 | -1.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 251839.73 | 406.02 | 18-MAY-04:43 | 5.78 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.730990E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.9 | |
Maximum of Months | 0.706104E+09 | 607.93 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200626E+11 | 20994.62 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.181982E+11 | 20994.62 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.216246E+11 | 20994.62 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.193152E+11 | 20994.62 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.208436E+11 | 20994.62 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.207428E+11 | 20994.62 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.194159E+11 | 20994.62 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.216246E+11 | 20994.62 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.193152E+11 | 20994.62 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.200626E+11 | 20994.62 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.198274E+11 | 20994.62 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.194159E+11 | 20994.62 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.240449E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.181982E+11 | 20994.62 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.216246E+11 | 20994.62 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.173975E+10 | 2367.39 | 02-JAN-16:30 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.148101E+10 | 2194.09 | 02-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.167254E+10 | 1982.51 | 22-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.145330E+10 | 1684.66 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.154275E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.151712E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.142650E+10 | 1625.32 | 12-JUL-08:30 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.160226E+10 | 1454.29 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.147946E+10 | 1993.67 | 25-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.160284E+10 | 2343.46 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.169018E+10 | 2367.39 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.172391E+10 | 2367.39 | 01-DEC-16:19 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.189316E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.142650E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.173975E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110614E+10 | 1525.64 | 02-JAN-16:30 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.950159E+09 | 1426.44 | 02-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107679E+10 | 1239.91 | 22-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.937481E+09 | 937.20 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.996654E+09 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.980776E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.923398E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.103614E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.951255E+09 | 1249.33 | 25-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.102722E+10 | 1506.62 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.108037E+10 | 1525.64 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.109129E+10 | 1525.64 | 01-DEC-16:19 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.121577E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.923398E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.110614E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.169432E+10 | 2367.44 | 02-JAN-16:30 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.145709E+10 | 2154.87 | 02-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166436E+10 | 1965.56 | 22-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145450E+10 | 1660.41 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.154681E+10 | 1454.32 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.152263E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.143457E+10 | 1454.32 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.160759E+10 | 1454.32 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147698E+10 | 1980.83 | 25-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.158426E+10 | 2339.11 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.165929E+10 | 2367.44 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.166631E+10 | 2367.44 | 01-DEC-16:19 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.187687E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.143457E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.169432E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110582E+10 | 1525.64 | 02-JAN-16:30 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.944793E+09 | 1384.97 | 02-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107558E+10 | 1294.89 | 22-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.936824E+09 | 1148.06 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.994986E+09 | 937.20 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.978900E+09 | 937.20 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.922736E+09 | 1179.65 | 12-JUL-07:30 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103363E+10 | 1180.38 | 28-AUG-07:30 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.953731E+09 | 1300.35 | 25-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.102831E+10 | 1510.69 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.107780E+10 | 1525.64 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.109047E+10 | 1525.64 | 01-DEC-16:19 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.121436E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.922736E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.110582E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.174330E+10 | 2367.39 | 02-JAN-16:30 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.148385E+10 | 2199.35 | 02-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.167436E+10 | 1994.11 | 22-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.145385E+10 | 1704.70 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.154322E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.151751E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.142689E+10 | 1643.83 | 12-JUL-08:30 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.160231E+10 | 1454.29 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.148034E+10 | 2004.83 | 25-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.160541E+10 | 2344.16 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.169359E+10 | 2367.39 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.172858E+10 | 2367.39 | 01-DEC-16:19 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.189532E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.142689E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.174330E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110684E+10 | 1525.64 | 02-JAN-16:30 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.950625E+09 | 1427.27 | 02-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107730E+10 | 1243.43 | 22-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.937684E+09 | 937.20 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.996821E+09 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.980934E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.923599E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.103638E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.951516E+09 | 1252.67 | 25-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.102775E+10 | 1506.86 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.108103E+10 | 1525.64 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.109237E+10 | 1525.64 | 01-DEC-16:19 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.121629E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.923599E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.110684E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.169686E+10 | 2367.44 | 02-JAN-16:30 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.145827E+10 | 2162.02 | 02-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166562E+10 | 1977.89 | 22-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145511E+10 | 1681.33 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.154739E+10 | 1454.32 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.152323E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.143524E+10 | 1594.54 | 12-JUL-07:30 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.160841E+10 | 1454.32 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147780E+10 | 1992.49 | 25-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.158625E+10 | 2340.02 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.166139E+10 | 2367.44 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.166870E+10 | 2367.44 | 01-DEC-16:19 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.187843E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.143524E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.169686E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110659E+10 | 1525.64 | 02-JAN-16:30 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.945361E+09 | 1386.11 | 02-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107602E+10 | 1296.67 | 22-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.936983E+09 | 1150.91 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.995093E+09 | 937.20 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.979066E+09 | 937.20 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.922904E+09 | 1181.77 | 12-JUL-07:30 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103384E+10 | 1182.77 | 28-AUG-07:30 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.953993E+09 | 1302.07 | 25-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.102888E+10 | 1510.81 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.107855E+10 | 1525.64 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.109143E+10 | 1525.64 | 01-DEC-16:19 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.121487E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.922904E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.110659E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.174326E+10 | 2367.39 | 02-JAN-16:30 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.148384E+10 | 2199.23 | 02-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.167434E+10 | 1993.75 | 22-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.145385E+10 | 1704.16 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.154321E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.151751E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.142689E+10 | 1643.28 | 12-JUL-08:30 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.160231E+10 | 1454.29 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.148034E+10 | 2004.47 | 25-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.160540E+10 | 2344.14 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.169355E+10 | 2367.39 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.172854E+10 | 2367.39 | 01-DEC-16:19 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.189530E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.142689E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.174326E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110678E+10 | 1525.64 | 02-JAN-16:30 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.950621E+09 | 1427.19 | 02-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107729E+10 | 1243.26 | 22-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.937682E+09 | 937.20 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.996821E+09 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.980957E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.923604E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.103641E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.951516E+09 | 1252.49 | 25-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.102774E+10 | 1506.85 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.108101E+10 | 1525.64 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.109237E+10 | 1525.64 | 01-DEC-16:19 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.121628E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.923604E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.110678E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.169685E+10 | 2367.44 | 02-JAN-16:30 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.145826E+10 | 2161.92 | 02-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166561E+10 | 1977.54 | 22-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145511E+10 | 1680.79 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.154739E+10 | 1454.32 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.152323E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.143525E+10 | 1594.11 | 12-JUL-07:30 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.160841E+10 | 1454.32 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147780E+10 | 1992.14 | 25-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.158624E+10 | 2340.00 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.166141E+10 | 2367.44 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.166869E+10 | 2367.44 | 01-DEC-16:19 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.187842E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.143525E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.169685E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110653E+10 | 1525.64 | 02-JAN-16:30 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.945359E+09 | 1385.98 | 02-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107601E+10 | 1296.45 | 22-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.936998E+09 | 1150.58 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.995090E+09 | 937.20 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.979065E+09 | 937.20 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.922905E+09 | 1181.53 | 12-JUL-07:30 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103385E+10 | 1182.71 | 28-AUG-07:30 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.953992E+09 | 1301.85 | 25-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.102888E+10 | 1510.79 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.107854E+10 | 1525.64 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.109143E+10 | 1525.64 | 01-DEC-16:19 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.121486E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.922905E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.110653E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.565679E+10 | 5919.59 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.513113E+10 | 5919.59 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.609720E+10 | 5919.59 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.544605E+10 | 5919.59 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.587700E+10 | 5919.59 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.584858E+10 | 5919.59 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.547447E+10 | 5919.59 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.609720E+10 | 5919.59 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.544605E+10 | 5919.59 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.565679E+10 | 5919.59 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.559049E+10 | 5919.59 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.547447E+10 | 5919.59 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.677962E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.513113E+10 | 5919.59 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.609720E+10 | 5919.59 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.208436E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.207428E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.198274E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.240449E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.173975E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812206E+09 |
February | 0.136985E+10 | 0.148101E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723252E+09 |
March | 0.163685E+10 | 0.167254E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696116E+09 |
April | 0.145243E+10 | 0.145330E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1006828.40 | 0.657821E+09 |
May | 0.157338E+10 | 0.154275E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38450.35 | 0.503485E+09 |
June | 0.156900E+10 | 0.151712E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 386372.46 | 0.417041E+09 |
July | 0.145680E+10 | 0.142650E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5477420.39 | 0.344798E+09 |
August | 0.163685E+10 | 0.160226E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8451945.34 | 0.278983E+09 |
September | 0.145243E+10 | 0.147946E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38316.06 | 0.235510E+09 |
October | 0.150991E+10 | 0.160284E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558028E+09 |
November | 0.149516E+10 | 0.169018E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648930E+09 |
December | 0.145680E+10 | 0.172391E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708295E+09 |
Annual Sum or Average | 0.181194E+11 | 0.189316E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15399333.01 | 0.658447E+10 |
Minimum of Months | 0.136985E+10 | 0.142650E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235510E+09 |
Maximum of Months | 0.163685E+10 | 0.173975E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8451945.34 | 0.812206E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.110614E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526443E+09 |
February | 0.882782E+09 | 0.950159E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469391E+09 |
March | 0.105485E+10 | 0.107679E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444491E+09 |
April | 0.936002E+09 | 0.937481E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 972042.73 | 0.417057E+09 |
May | 0.101394E+10 | 0.996654E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26644.58 | 0.325514E+09 |
June | 0.101113E+10 | 0.980776E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 269306.65 | 0.267612E+09 |
July | 0.938820E+09 | 0.923398E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4279139.33 | 0.211319E+09 |
August | 0.105485E+10 | 0.103614E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6008693.51 | 0.166699E+09 |
September | 0.936002E+09 | 0.951255E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26456.54 | 0.151118E+09 |
October | 0.973041E+09 | 0.102722E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354495E+09 |
November | 0.963541E+09 | 0.108037E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407454E+09 |
December | 0.938820E+09 | 0.109129E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447144E+09 |
Annual Sum or Average | 0.116768E+11 | 0.121577E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11582283.35 | 0.418874E+10 |
Minimum of Months | 0.882782E+09 | 0.923398E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151118E+09 |
Maximum of Months | 0.105485E+10 | 0.110614E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6008693.51 | 0.526443E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.169432E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777884E+09 |
February | 0.136988E+10 | 0.145709E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716383E+09 |
March | 0.163688E+10 | 0.166436E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680876E+09 |
April | 0.145246E+10 | 0.145450E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1025767.53 | 0.639898E+09 |
May | 0.157341E+10 | 0.154681E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38445.76 | 0.493087E+09 |
June | 0.156904E+10 | 0.152263E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 386355.97 | 0.405664E+09 |
July | 0.145684E+10 | 0.143457E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4442492.64 | 0.331362E+09 |
August | 0.163688E+10 | 0.160759E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8061994.41 | 0.267102E+09 |
September | 0.145246E+10 | 0.147698E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38208.01 | 0.236892E+09 |
October | 0.150994E+10 | 0.158426E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549329E+09 |
November | 0.149520E+10 | 0.165929E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618041E+09 |
December | 0.145684E+10 | 0.166631E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677423E+09 |
Annual Sum or Average | 0.181198E+11 | 0.187687E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13993264.32 | 0.639394E+10 |
Minimum of Months | 0.136988E+10 | 0.143457E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236892E+09 |
Maximum of Months | 0.163688E+10 | 0.169432E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8061994.41 | 0.777884E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.110582E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554982E+09 |
February | 0.882782E+09 | 0.944793E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512726E+09 |
March | 0.105485E+10 | 0.107558E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503155E+09 |
April | 0.936002E+09 | 0.936824E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 357317.84 | 0.484769E+09 |
May | 0.101394E+10 | 0.994986E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25631.99 | 0.356098E+09 |
June | 0.101113E+10 | 0.978900E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 257566.78 | 0.300774E+09 |
July | 0.938820E+09 | 0.922736E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2431135.11 | 0.257493E+09 |
August | 0.105485E+10 | 0.103363E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5317460.60 | 0.210796E+09 |
September | 0.936002E+09 | 0.953731E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25540.47 | 0.169284E+09 |
October | 0.973041E+09 | 0.102831E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397970E+09 |
November | 0.963541E+09 | 0.107780E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465870E+09 |
December | 0.938820E+09 | 0.109047E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519019E+09 |
Annual Sum or Average | 0.116768E+11 | 0.121436E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8414652.79 | 0.473294E+10 |
Minimum of Months | 0.882782E+09 | 0.922736E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169284E+09 |
Maximum of Months | 0.105485E+10 | 0.110582E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5317460.60 | 0.554982E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.174330E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160290E+10 |
February | 0.136985E+10 | 0.148385E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144536E+10 |
March | 0.163685E+10 | 0.167436E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141769E+10 |
April | 0.145243E+10 | 0.145385E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3313098.32 | 0.136272E+10 |
May | 0.157338E+10 | 0.154322E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64019.64 | 0.109374E+10 |
June | 0.156900E+10 | 0.151751E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795793.37 | 0.912014E+09 |
July | 0.145680E+10 | 0.142689E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15330911.88 | 0.768825E+09 |
August | 0.163685E+10 | 0.160231E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20422988.45 | 0.625565E+09 |
September | 0.145243E+10 | 0.148034E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67132.54 | 0.509601E+09 |
October | 0.150991E+10 | 0.160541E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113805E+10 |
November | 0.149516E+10 | 0.169359E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128215E+10 |
December | 0.145680E+10 | 0.172858E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138213E+10 |
Annual Sum or Average | 0.181194E+11 | 0.189532E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39993944.19 | 0.135407E+11 |
Minimum of Months | 0.136985E+10 | 0.142689E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509601E+09 |
Maximum of Months | 0.163685E+10 | 0.174330E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20422988.45 | 0.160290E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.110684E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106402E+10 |
February | 0.649041E+09 | 0.950625E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972420E+09 |
March | 0.773965E+09 | 0.107730E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939010E+09 |
April | 0.688021E+09 | 0.937684E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2361408.12 | 0.908213E+09 |
May | 0.744847E+09 | 0.996821E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45556.04 | 0.716667E+09 |
June | 0.742030E+09 | 0.980934E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 577431.45 | 0.603468E+09 |
July | 0.690839E+09 | 0.923599E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9394476.54 | 0.503045E+09 |
August | 0.773965E+09 | 0.103638E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13460570.41 | 0.411123E+09 |
September | 0.688021E+09 | 0.951516E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48876.69 | 0.332505E+09 |
October | 0.715730E+09 | 0.102775E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747385E+09 |
November | 0.708685E+09 | 0.108103E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841168E+09 |
December | 0.690839E+09 | 0.109237E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917333E+09 |
Annual Sum or Average | 0.858171E+10 | 0.121629E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25888319.26 | 0.895636E+10 |
Minimum of Months | 0.649041E+09 | 0.923599E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332505E+09 |
Maximum of Months | 0.773965E+09 | 0.110684E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13460570.41 | 0.106402E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.169686E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165925E+10 |
February | 0.136988E+10 | 0.145827E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156257E+10 |
March | 0.163688E+10 | 0.166562E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148750E+10 |
April | 0.145246E+10 | 0.145511E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2165218.84 | 0.140958E+10 |
May | 0.157341E+10 | 0.154739E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64007.98 | 0.110282E+10 |
June | 0.156904E+10 | 0.152323E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 800337.09 | 0.905916E+09 |
July | 0.145684E+10 | 0.143524E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9907058.06 | 0.772451E+09 |
August | 0.163688E+10 | 0.160841E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18152207.19 | 0.638031E+09 |
September | 0.145246E+10 | 0.147780E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66572.57 | 0.537169E+09 |
October | 0.150994E+10 | 0.158625E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121247E+10 |
November | 0.149520E+10 | 0.166139E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131996E+10 |
December | 0.145684E+10 | 0.166870E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143907E+10 |
Annual Sum or Average | 0.181198E+11 | 0.187843E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31155401.72 | 0.140468E+11 |
Minimum of Months | 0.136988E+10 | 0.143524E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537169E+09 |
Maximum of Months | 0.163688E+10 | 0.169686E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18152207.19 | 0.165925E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.110659E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109511E+10 |
February | 0.882782E+09 | 0.945361E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100118E+10 |
March | 0.105485E+10 | 0.107602E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972375E+09 |
April | 0.936002E+09 | 0.936983E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1036792.75 | 0.941126E+09 |
May | 0.101394E+10 | 0.995093E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54370.05 | 0.759345E+09 |
June | 0.101113E+10 | 0.979066E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530951.67 | 0.624631E+09 |
July | 0.938820E+09 | 0.922904E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7054625.14 | 0.556884E+09 |
August | 0.105485E+10 | 0.103384E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12992338.85 | 0.448155E+09 |
September | 0.936002E+09 | 0.953993E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44747.65 | 0.358224E+09 |
October | 0.973041E+09 | 0.102888E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777381E+09 |
November | 0.963541E+09 | 0.107855E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867644E+09 |
December | 0.938820E+09 | 0.109143E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948018E+09 |
Annual Sum or Average | 0.116768E+11 | 0.121487E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21713826.10 | 0.935007E+10 |
Minimum of Months | 0.882782E+09 | 0.922904E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358224E+09 |
Maximum of Months | 0.105485E+10 | 0.110659E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12992338.85 | 0.109511E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.174326E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184835E+10 |
February | 0.136985E+10 | 0.148384E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164144E+10 |
March | 0.163685E+10 | 0.167434E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159181E+10 |
April | 0.145243E+10 | 0.145385E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4322095.53 | 0.155034E+10 |
May | 0.157338E+10 | 0.154321E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51956.96 | 0.127771E+10 |
June | 0.156900E+10 | 0.151751E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 861563.20 | 0.109099E+10 |
July | 0.145680E+10 | 0.142689E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17048633.04 | 0.927862E+09 |
August | 0.163685E+10 | 0.160231E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24425409.59 | 0.750530E+09 |
September | 0.145243E+10 | 0.148034E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57894.71 | 0.589287E+09 |
October | 0.150991E+10 | 0.160540E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125850E+10 |
November | 0.149516E+10 | 0.169355E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142393E+10 |
December | 0.145680E+10 | 0.172854E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154268E+10 |
Annual Sum or Average | 0.181194E+11 | 0.189530E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46767553.03 | 0.154934E+11 |
Minimum of Months | 0.136985E+10 | 0.142689E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589287E+09 |
Maximum of Months | 0.163685E+10 | 0.174326E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24425409.59 | 0.184835E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.110678E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123132E+10 |
February | 0.882782E+09 | 0.950621E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110374E+10 |
March | 0.105485E+10 | 0.107729E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107064E+10 |
April | 0.936002E+09 | 0.937682E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2804531.68 | 0.105273E+10 |
May | 0.101394E+10 | 0.996821E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35527.19 | 0.853744E+09 |
June | 0.101113E+10 | 0.980957E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 579809.65 | 0.736062E+09 |
July | 0.938820E+09 | 0.923604E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9157496.60 | 0.617547E+09 |
August | 0.105485E+10 | 0.103641E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15303252.63 | 0.504326E+09 |
September | 0.936002E+09 | 0.951516E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40127.28 | 0.395175E+09 |
October | 0.973041E+09 | 0.102774E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847480E+09 |
November | 0.963541E+09 | 0.108101E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947711E+09 |
December | 0.938820E+09 | 0.109237E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103017E+10 |
Annual Sum or Average | 0.116768E+11 | 0.121628E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27920745.03 | 0.103907E+11 |
Minimum of Months | 0.882782E+09 | 0.923604E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395175E+09 |
Maximum of Months | 0.105485E+10 | 0.110678E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15303252.63 | 0.123132E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.169685E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189376E+10 |
February | 0.136988E+10 | 0.145826E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175835E+10 |
March | 0.163688E+10 | 0.166561E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169777E+10 |
April | 0.145246E+10 | 0.145511E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2438740.75 | 0.163094E+10 |
May | 0.157341E+10 | 0.154739E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51945.23 | 0.130459E+10 |
June | 0.156904E+10 | 0.152323E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 862349.51 | 0.109099E+10 |
July | 0.145684E+10 | 0.143525E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10663044.30 | 0.940469E+09 |
August | 0.163688E+10 | 0.160841E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21568804.30 | 0.774378E+09 |
September | 0.145246E+10 | 0.147780E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57432.27 | 0.637011E+09 |
October | 0.150994E+10 | 0.158624E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138017E+10 |
November | 0.149520E+10 | 0.166141E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148801E+10 |
December | 0.145684E+10 | 0.166869E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161361E+10 |
Annual Sum or Average | 0.181198E+11 | 0.187842E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35642316.37 | 0.162100E+11 |
Minimum of Months | 0.136988E+10 | 0.143525E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637011E+09 |
Maximum of Months | 0.163688E+10 | 0.169685E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21568804.30 | 0.189376E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.110653E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126159E+10 |
February | 0.882782E+09 | 0.945359E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114632E+10 |
March | 0.105485E+10 | 0.107601E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112211E+10 |
April | 0.936002E+09 | 0.936998E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1221780.16 | 0.109787E+10 |
May | 0.101394E+10 | 0.995090E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49330.86 | 0.903551E+09 |
June | 0.101113E+10 | 0.979065E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 574329.39 | 0.754792E+09 |
July | 0.938820E+09 | 0.922905E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8196542.62 | 0.679823E+09 |
August | 0.105485E+10 | 0.103385E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15666321.53 | 0.544979E+09 |
September | 0.936002E+09 | 0.953992E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38591.84 | 0.425822E+09 |
October | 0.973041E+09 | 0.102888E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893844E+09 |
November | 0.963541E+09 | 0.107854E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994149E+09 |
December | 0.938820E+09 | 0.109143E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107878E+10 |
Annual Sum or Average | 0.116768E+11 | 0.121486E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25746896.40 | 0.109036E+11 |
Minimum of Months | 0.882782E+09 | 0.922905E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425822E+09 |
Maximum of Months | 0.105485E+10 | 0.110653E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15666321.53 | 0.126159E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.565679E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.513113E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.609720E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.544605E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.587700E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.584858E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.547447E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.609720E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.544605E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.565679E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.559049E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.547447E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.677962E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.513113E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.609720E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172950E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153482E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146420E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1511725.62 | 0.137144E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5234.57 | 0.104915E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307442.91 | 0.864958E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8643689.96 | 0.720379E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13374371.37 | 0.595394E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2853.54 | 0.495743E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117592E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136375E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149765E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23845317.96 | 0.138629E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495743E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13374371.37 | 0.172950E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279689E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255000E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247058E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3920643.08 | 0.232019E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8545.08 | 0.182287E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560214.14 | 0.150030E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18661337.28 | 0.125766E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25183633.21 | 0.104170E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4061.17 | 0.863273E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198696E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225478E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244761E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48338433.98 | 0.233128E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863273E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25183633.21 | 0.279689E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281298E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256951E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254689E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3108087.68 | 0.248359E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203150E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157012.66 | 0.172083E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6368828.64 | 0.146289E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17992016.24 | 0.118310E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.942629E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203735E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225369E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241064E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27625945.23 | 0.244556E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.942629E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17992016.24 | 0.281298E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 20994.62 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 20994.62 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 20994.62 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 20994.62 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 20994.62 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 20994.62 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 20994.62 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 20994.62 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 20994.62 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 20994.62 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 20994.62 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 20994.62 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2367.39 | 02-JAN-16:30 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1318.82 | 28-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 2194.09 | 02-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1240.53 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1982.51 | 22-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1163.52 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1684.66 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.85 | 01-APR-17:02 | 1197.48 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 05-MAY-16:00 | 865.77 | 18-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 28-JUN-16:00 | 1178.27 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1625.32 | 12-JUL-08:30 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.15 | 23-JUL-16:00 | 606.65 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1454.29 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.56 | 13-AUG-15:10 | 758.43 | 04-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1993.67 | 25-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 14-SEP-17:00 | 567.93 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2343.46 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1039.30 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1260.35 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-16:19 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1043.13 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.93 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 140.15 | 1318.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-16:30 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 851.98 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1426.44 | 02-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 799.29 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1239.91 | 22-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 758.82 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 937.20 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.32 | 01-APR-17:02 | 780.68 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 05-MAY-16:00 | 558.04 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 28-JUN-16:00 | 763.43 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.35 | 23-JUL-15:40 | 386.21 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.44 | 13-AUG-15:10 | 477.23 | 04-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1249.33 | 25-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.63 | 14-SEP-17:00 | 363.32 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1506.62 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 646.85 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 799.61 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:19 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 667.27 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.32 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 119.35 | 851.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2367.44 | 02-JAN-16:30 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1254.03 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2154.87 | 02-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1212.62 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 1965.56 | 22-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1169.04 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1660.41 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.42 | 01-APR-17:20 | 1186.76 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1454.32 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 05-MAY-16:00 | 840.59 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 28-JUN-16:00 | 1140.37 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1454.32 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.44 | 23-JUL-16:00 | 593.00 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1454.32 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.73 | 13-AUG-15:08 | 756.40 | 04-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1980.83 | 25-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 14-SEP-17:00 | 544.08 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2339.11 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 970.52 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1201.02 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-16:19 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 956.45 | 02-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.08 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 136.44 | 1254.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-16:30 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 912.34 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1384.97 | 02-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 876.52 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1294.89 | 22-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 858.29 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1148.06 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.63 | 01-APR-16:00 | 892.82 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 05-MAY-16:00 | 602.08 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 28-JUN-16:00 | 851.56 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1179.65 | 12-JUL-07:30 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.14 | 23-JUL-13:52 | 468.28 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 1180.38 | 28-AUG-07:30 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 08-AUG-17:00 | 607.68 | 04-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1300.35 | 25-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.63 | 14-SEP-17:00 | 397.96 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1510.69 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 709.65 | 31-OCT-21:20 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 900.13 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:19 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 777.15 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.96 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 56.14 | 912.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2367.39 | 02-JAN-16:30 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2645.06 | 12-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 2199.35 | 02-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2431.92 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1994.11 | 22-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2321.42 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1704.70 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.17 | 01-APR-17:02 | 2452.72 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 05-MAY-16:00 | 1828.38 | 18-MAY-04:55 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.60 | 28-JUN-16:00 | 2402.49 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1643.83 | 12-JUL-08:30 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.89 | 23-JUL-14:10 | 1237.02 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1454.29 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.89 | 13-AUG-15:10 | 1722.73 | 11-AUG-03:55 |
September | 2010.79 | 01-SEP-09:09 | 2004.83 | 25-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 | 14-SEP-17:00 | 1195.43 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2344.16 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2172.30 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2510.38 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-16:19 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2031.83 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1195.43 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 424.17 | 2645.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1525.64 | 02-JAN-16:30 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1738.08 | 12-JAN-24:00 |
February | 1239.33 | 01-FEB-08:09 | 1427.27 | 02-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1603.65 | 16-FEB-04:00 |
March | 1239.33 | 01-MAR-08:09 | 1243.43 | 22-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1558.55 | 28-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 937.20 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.90 | 01-APR-17:20 | 1650.19 | 07-APR-24:00 |
May | 1239.33 | 01-MAY-07:10 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 05-MAY-16:00 | 1190.71 | 22-MAY-24:00 |
June | 1239.33 | 01-JUN-07:10 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 28-JUN-16:00 | 1577.95 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.84 | 23-JUL-16:10 | 806.09 | 02-JUL-04:00 |
August | 1239.33 | 01-AUG-07:10 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.57 | 13-AUG-15:10 | 1158.52 | 11-AUG-04:00 |
September | 1239.33 | 01-SEP-07:10 | 1252.67 | 25-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 14-SEP-17:00 | 752.33 | 18-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 1506.86 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1442.73 | 31-OCT-21:03 |
November | 1239.33 | 01-NOV-07:10 | 1525.64 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1657.47 | 29-NOV-23:00 |
December | 1239.33 | 01-DEC-08:09 | 1525.64 | 01-DEC-16:19 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1346.73 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 752.33 | |||||
Maximum of Months | 1239.33 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 327.90 | 1738.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2367.44 | 02-JAN-16:30 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2636.58 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2162.02 | 02-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2667.19 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 1977.89 | 22-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2453.43 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1681.33 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.16 | 01-APR-17:20 | 2492.59 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1454.32 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 05-MAY-16:00 | 1809.91 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.60 | 28-JUN-16:00 | 2358.00 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1594.54 | 12-JUL-07:30 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.76 | 23-JUL-16:10 | 1250.78 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1454.32 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.65 | 13-AUG-15:08 | 1777.58 | 11-AUG-04:00 |
September | 2010.83 | 01-SEP-09:09 | 1992.49 | 25-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 | 14-SEP-17:00 | 1176.48 | 30-SEP-04:55 |
October | 2010.83 | 02-OCT-09:09 | 2340.02 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2168.21 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2506.10 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-16:19 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2052.75 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.48 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 317.76 | 2667.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-16:30 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1764.38 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1386.11 | 02-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1634.06 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1296.67 | 22-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1580.93 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1150.91 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.89 | 01-APR-17:20 | 1634.12 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 05-MAY-16:00 | 1227.78 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 | 28-JUN-16:00 | 1581.88 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1181.77 | 12-JUL-07:30 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.19 | 23-JUL-13:30 | 871.94 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 1182.77 | 28-AUG-07:30 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.36 | 13-AUG-12:30 | 1241.89 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 1302.07 | 25-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 14-SEP-17:00 | 786.37 | 30-SEP-04:55 |
October | 1295.83 | 02-OCT-09:09 | 1510.81 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1447.46 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1687.63 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:19 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1375.26 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 786.37 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 240.19 | 1764.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2367.39 | 02-JAN-16:30 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3094.32 | 12-JAN-22:03 |
February | 2010.79 | 01-FEB-10:09 | 2199.23 | 02-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2908.58 | 16-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 1993.75 | 22-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2822.23 | 29-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 1704.16 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 570.31 | 01-APR-17:02 | 2909.81 | 10-APR-21:03 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.40 | 05-MAY-16:00 | 2142.26 | 22-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.13 | 28-JUN-16:00 | 2722.69 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1643.28 | 12-JUL-08:30 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.36 | 23-JUL-13:54 | 1400.92 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1454.29 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.83 | 13-AUG-14:51 | 2110.79 | 11-AUG-03:55 |
September | 2010.79 | 01-SEP-09:09 | 2004.47 | 25-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 14-SEP-17:00 | 1329.43 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2344.14 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2678.50 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2907.64 | 29-NOV-22:03 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-16:19 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2403.79 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1329.43 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 570.31 | 3094.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-16:30 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2060.37 | 12-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 1427.19 | 02-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1937.81 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1243.26 | 22-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1881.51 | 29-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 937.20 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 392.29 | 01-APR-17:02 | 1935.24 | 10-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 05-MAY-16:00 | 1421.94 | 18-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 | 28-JUN-16:00 | 1793.49 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 280.58 | 23-JUL-15:50 | 916.10 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.45 | 13-AUG-15:20 | 1446.03 | 11-AUG-03:55 |
September | 1295.83 | 01-SEP-09:09 | 1252.49 | 25-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 14-SEP-17:00 | 848.37 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1506.85 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1783.11 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1936.29 | 29-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:19 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1601.29 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.37 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 392.29 | 2060.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2367.44 | 02-JAN-16:30 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3095.71 | 12-JAN-22:03 |
February | 2010.83 | 01-FEB-10:09 | 2161.92 | 02-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2909.80 | 16-FEB-22:03 |
March | 2010.83 | 01-MAR-10:09 | 1977.54 | 22-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2822.13 | 29-MAR-05:00 |
April | 2010.83 | 03-APR-09:09 | 1680.79 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.20 | 01-APR-17:02 | 2913.99 | 10-APR-21:03 |
May | 2010.83 | 01-MAY-09:09 | 1454.32 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 05-MAY-16:00 | 2133.03 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 | 28-JUN-16:00 | 2666.50 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1594.11 | 12-JUL-07:30 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.31 | 23-JUL-15:50 | 1425.31 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1454.32 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.37 | 13-AUG-15:20 | 2215.52 | 11-AUG-03:55 |
September | 2010.83 | 01-SEP-09:09 | 1992.14 | 25-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 14-SEP-17:00 | 1341.18 | 30-SEP-04:55 |
October | 2010.83 | 02-OCT-09:09 | 2340.00 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2677.43 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2908.08 | 29-NOV-22:03 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-16:19 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2407.46 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1341.18 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 358.31 | 3095.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-16:30 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2066.45 | 12-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 1385.98 | 02-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1942.02 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1296.45 | 22-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1881.62 | 29-MAR-05:00 |
April | 1295.83 | 03-APR-09:09 | 1150.58 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.28 | 01-APR-17:30 | 1956.27 | 10-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 | 06-MAY-13:00 | 1450.97 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 | 28-JUN-16:00 | 1793.95 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1181.53 | 12-JUL-07:30 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.09 | 23-JUL-13:50 | 1035.18 | 22-JUL-22:55 |
August | 1295.83 | 01-AUG-09:09 | 1182.71 | 28-AUG-07:30 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.72 | 13-AUG-12:40 | 1552.09 | 11-AUG-03:55 |
September | 1295.83 | 01-SEP-09:09 | 1301.85 | 25-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 14-SEP-17:00 | 902.58 | 30-SEP-04:55 |
October | 1295.83 | 02-OCT-09:09 | 1510.79 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1788.62 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1957.41 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:19 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1615.54 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.58 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 272.09 | 2066.45 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5919.59 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5919.59 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5919.59 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5919.59 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5919.59 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5919.59 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5919.59 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5919.59 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5919.59 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5919.59 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5919.59 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5919.59 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2830.38 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2636.09 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2467.40 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.78 | 01-APR-17:02 | 2509.30 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 05-MAY-16:00 | 1847.74 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.89 | 28-JUN-15:00 | 2481.44 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.77 | 23-JUL-16:00 | 1254.16 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.67 | 13-AUG-14:51 | 1605.66 | 11-AUG-03:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | 14-SEP-17:00 | 1169.61 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2200.14 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2679.48 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2209.34 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1169.61 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.77 | 2830.38 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4765.83 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4408.77 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4158.56 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.28 | 01-APR-17:02 | 4291.03 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 05-MAY-16:00 | 3242.63 | 18-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.14 | 28-JUN-15:00 | 4253.34 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.14 | 23-JUL-15:51 | 2142.38 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.50 | 13-AUG-14:51 | 2910.84 | 11-AUG-03:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 14-SEP-17:00 | 2009.13 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3741.10 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4460.51 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3573.08 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2009.13 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.28 | 4765.83 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4819.01 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4372.56 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4252.43 | 29-MAR-04:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.47 | 01-APR-17:02 | 4553.58 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 3301.62 | 22-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 28-JUN-17:00 | 4310.03 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.97 | 23-JUL-14:00 | 2194.75 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.67 | 08-AUG-17:00 | 3309.41 | 11-AUG-03:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 2064.09 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4081.46 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4586.23 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3775.03 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2064.09 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.47 | 4819.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 113023.85 | 02-JAN-04:01 | 0.00 | 9331.40 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 112122.65 | 21-FEB-04:01 | 0.00 | 8164.98 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 113442.51 | 20-MAR-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 114235.41 | 17-APR-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 113299.51 | 08-MAY-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 108292.34 | 05-JUN-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 111219.80 | 03-JUL-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 107646.74 | 21-AUG-00:52 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 109041.10 | 28-SEP-04:02 | 0.00 | 11664.26 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 114027.39 | 16-OCT-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 113837.06 | 24-NOV-04:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 113911.12 | 11-DEC-04:01 | 0.00 | 8164.98 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 107646.74 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 114235.41 | 0.00 | 11664.26 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 88637.64 | 02-JAN-05:01 | 0.00 | 14665.45 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87433.21 | 06-FEB-05:01 | 0.00 | 14665.45 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 91900.10 | 20-MAR-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 93638.82 | 17-APR-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95150.20 | 01-MAY-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 95870.83 | 12-JUN-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 95136.44 | 17-JUL-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 91507.86 | 28-AUG-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94221.07 | 25-SEP-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96434.73 | 10-OCT-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95687.93 | 06-NOV-04:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 90085.18 | 26-DEC-04:01 | 0.00 | 7332.73 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 87433.21 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96434.73 | 0.00 | 14665.45 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 28319.81 | 12-JAN-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74079.75 | 28-FEB-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 76639.57 | 03-MAR-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80880.02 | 28-APR-04:03 | 0.00 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81581.46 | 05-MAY-04:02 | 0.00 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83649.71 | 12-JUN-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84098.88 | 10-JUL-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85648.32 | 28-AUG-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82894.29 | 12-SEP-04:02 | 0.00 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80783.04 | 10-OCT-04:03 | 0.00 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 76612.32 | 06-NOV-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52504.58 | 07-DEC-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 28319.81 | 0.00 | 5237.66 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85648.32 | 6448.95 | 10475.32 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19370.46 | 11-JAN-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30556.48 | 28-FEB-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33454.67 | 15-MAR-16:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78330.75 | 28-APR-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78371.44 | 05-MAY-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81173.08 | 12-JUN-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80159.12 | 25-JUL-04:02 | 0.00 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80947.29 | 10-AUG-04:02 | 0.00 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78494.74 | 15-SEP-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 62894.64 | 05-OCT-05:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27704.34 | 02-NOV-16:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19397.77 | 06-DEC-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19370.46 | 0.00 | 6285.19 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81173.08 | 15316.26 | 18854.65 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3028.59 | 11-JAN-06:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.54 |
February | 4719.23 | 27-FEB-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 |
March | 5160.42 | 10-MAR-14:30 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.62 |
April | 7489.76 | 27-APR-15:20 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 | 0.00 |
May | 7543.39 | 05-MAY-05:02 | 1012.16 | 934.22 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11949.87 | 12-JUN-05:03 | 809.73 | 646.38 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.84 |
July | 11749.34 | 10-JUL-05:03 | 809.73 | 900.58 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.39 |
August | 11860.79 | 28-AUG-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 |
September | 9369.15 | 05-SEP-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.96 |
October | 9143.71 | 10-OCT-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.94 |
November | 4716.76 | 06-NOV-11:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.04 |
December | 3195.75 | 30-DEC-06:04 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3028.59 | 809.73 | 646.38 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11949.87 | 2010.79 | 1454.29 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 | 90.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3891.56 | 11-JAN-06:02 | 652.28 | 847.62 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.72 |
February | 4121.54 | 28-FEB-06:03 | 521.82 | 678.09 | 2607.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 |
March | 7715.25 | 14-MAR-09:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 |
April | 10720.57 | 27-APR-08:30 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 |
May | 20491.29 | 14-MAY-08:52 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.53 |
June | 13450.73 | 25-JUN-08:43 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.87 |
July | 21693.96 | 23-JUL-08:12 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.93 |
August | 21725.42 | 13-AUG-08:22 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.78 |
September | 20946.81 | 10-SEP-08:42 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.14 |
October | 8819.81 | 04-OCT-09:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 |
November | 4479.67 | 06-NOV-04:02 | 0.00 | 423.81 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.21 |
December | 3890.09 | 04-DEC-04:02 | 0.00 | 423.81 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3890.09 | 0.00 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 | |
Maximum of Months | 21725.42 | 1239.33 | 937.20 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13795.43 | 20-JAN-13:10 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 |
February | 16446.86 | 27-FEB-13:50 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.84 |
March | 17396.19 | 01-MAR-13:30 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.12 |
April | 28273.79 | 02-APR-13:22 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.92 |
May | 28022.14 | 14-MAY-13:32 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.21 |
June | 13617.60 | 28-JUN-13:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 0.00 |
July | 20899.67 | 30-JUL-12:53 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 |
August | 30273.29 | 13-AUG-13:02 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.79 |
September | 31340.75 | 10-SEP-12:41 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.60 |
October | 21075.06 | 08-OCT-13:13 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.50 |
November | 20976.12 | 11-NOV-12:43 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.19 |
December | 15216.33 | 05-DEC-12:30 | 1058.33 | 1454.32 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13617.60 | 404.87 | 323.20 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31340.75 | 2010.83 | 1454.32 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 384.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5201.75 | 11-JAN-06:02 | 652.28 | 847.62 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.35 |
February | 10124.37 | 27-FEB-15:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 |
March | 12382.55 | 14-MAR-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 |
April | 19937.35 | 02-APR-15:22 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.07 |
May | 27217.80 | 07-MAY-16:41 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.21 |
June | 22629.42 | 18-JUN-17:12 | 0.00 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.38 |
July | 29000.16 | 23-JUL-17:31 | 0.00 | 468.62 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.10 |
August | 26281.72 | 06-AUG-16:21 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.98 |
September | 25454.03 | 10-SEP-15:22 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.31 |
October | 12352.17 | 04-OCT-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.73 |
November | 11062.10 | 06-NOV-06:03 | 521.82 | 678.09 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.81 |
December | 12146.95 | 30-DEC-06:02 | 652.28 | 847.62 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5201.75 | 0.00 | 260.35 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 | |
Maximum of Months | 29000.16 | 1239.33 | 937.20 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2000.13 | 11-JAN-16:30 | 1923.11 | 2310.40 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.79 |
February | 2486.29 | 28-FEB-06:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.35 |
March | 2794.96 | 10-MAR-14:40 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.32 |
April | 6085.62 | 27-APR-15:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 51.57 | 0.00 |
May | 6661.56 | 05-MAY-13:30 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 |
June | 7251.93 | 21-JUN-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 0.00 |
July | 8264.23 | 24-JUL-15:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 81.05 | 0.00 |
August | 7931.49 | 25-AUG-14:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 | 0.00 |
September | 6032.83 | 12-SEP-14:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 0.00 |
October | 3795.12 | 04-OCT-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.21 |
November | 2420.25 | 03-NOV-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.54 |
December | 1924.66 | 29-DEC-16:10 | 1923.11 | 2252.18 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1924.66 | 809.73 | 1052.22 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8264.23 | 2010.79 | 2310.40 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 81.05 | 226.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2599.31 | 05-JAN-09:40 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.94 |
February | 3662.78 | 28-FEB-06:03 | 521.82 | 678.09 | 2607.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.43 |
March | 5976.28 | 14-MAR-10:05 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.19 |
April | 10812.88 | 27-APR-09:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.08 |
May | 12424.23 | 14-MAY-09:02 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.24 |
June | 21484.25 | 25-JUN-09:12 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.26 |
July | 22603.64 | 23-JUL-08:42 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.09 |
August | 22466.18 | 13-AUG-08:22 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.38 |
September | 13354.49 | 10-SEP-09:32 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.23 |
October | 7694.89 | 04-OCT-09:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.62 |
November | 3567.80 | 06-NOV-06:03 | 521.82 | 678.09 | 2607.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.42 |
December | 2842.39 | 05-DEC-10:00 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2599.31 | 260.91 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.08 | |
Maximum of Months | 22603.64 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13380.93 | 20-JAN-13:30 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.78 |
February | 16617.23 | 27-FEB-14:20 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.21 |
March | 18287.45 | 01-MAR-13:40 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.11 |
April | 18527.91 | 27-APR-13:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 27.94 | 0.00 |
May | 15430.70 | 15-MAY-13:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.76 |
June | 13471.50 | 28-JUN-13:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 0.00 |
July | 22995.04 | 30-JUL-14:52 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 | 0.00 |
August | 31178.51 | 13-AUG-13:42 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.39 |
September | 29734.04 | 10-SEP-13:32 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.93 |
October | 30280.49 | 08-OCT-13:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.43 |
November | 14606.49 | 04-NOV-13:30 | 211.67 | 242.38 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13434.33 | 05-DEC-12:30 | 1058.33 | 1454.32 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13380.93 | 211.67 | 242.38 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31178.51 | 2010.83 | 1454.32 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 27.94 | 508.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3263.74 | 05-JAN-15:50 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.85 |
February | 6563.16 | 27-FEB-15:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.99 |
March | 8820.84 | 14-MAR-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 |
April | 12726.65 | 26-APR-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 0.00 |
May | 21962.73 | 07-MAY-16:52 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.64 |
June | 21922.44 | 18-JUN-17:01 | 0.00 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.21 |
July | 24759.37 | 23-JUL-18:41 | 0.00 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.63 |
August | 22071.66 | 06-AUG-16:32 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.24 |
September | 19493.89 | 10-SEP-16:52 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.60 |
October | 10212.31 | 04-OCT-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.13 |
November | 4064.66 | 04-NOV-15:40 | 130.46 | 156.20 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 |
December | 3476.43 | 05-DEC-15:40 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3263.74 | 0.00 | 156.20 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24759.37 | 1239.33 | 937.20 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 570.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1977.51 | 11-JAN-16:30 | 1923.11 | 2310.37 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.67 |
February | 2483.25 | 28-FEB-15:10 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 |
March | 2605.93 | 10-MAR-15:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.09 |
April | 6567.25 | 27-APR-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 61.78 | 0.00 |
May | 6890.50 | 05-MAY-13:30 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 |
June | 7795.99 | 21-JUN-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 0.00 |
July | 9210.58 | 24-JUL-15:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 98.95 | 0.00 |
August | 8611.66 | 09-AUG-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 116.49 | 0.00 |
September | 6243.35 | 12-SEP-15:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 | 0.00 |
October | 3390.27 | 04-OCT-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.18 |
November | 2315.15 | 02-NOV-14:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.29 |
December | 1901.43 | 29-DEC-16:20 | 1923.11 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1901.43 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9210.58 | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 116.49 | 260.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2462.40 | 18-JAN-06:04 | 913.19 | 1186.66 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.13 |
February | 2900.63 | 27-FEB-15:50 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.48 |
March | 4346.46 | 14-MAR-10:00 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.65 |
April | 10404.70 | 27-APR-09:30 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.09 |
May | 16656.40 | 14-MAY-08:52 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.68 |
June | 20709.02 | 25-JUN-09:02 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.10 |
July | 19847.83 | 30-JUL-09:12 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.37 |
August | 21086.87 | 06-AUG-09:42 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.29 |
September | 20466.21 | 10-SEP-09:22 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.12 |
October | 6630.81 | 04-OCT-09:30 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.53 |
November | 2878.03 | 02-NOV-10:40 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.07 |
December | 2491.24 | 27-DEC-06:04 | 913.19 | 1186.66 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2462.40 | 326.14 | 260.35 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.48 | |
Maximum of Months | 21086.87 | 1295.83 | 1186.66 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11330.79 | 20-JAN-13:30 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.20 |
February | 15055.18 | 27-FEB-14:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.61 |
March | 17232.11 | 14-MAR-13:40 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.81 |
April | 23627.19 | 02-APR-13:22 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 778.88 |
May | 24827.73 | 14-MAY-14:52 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.26 |
June | 14184.43 | 28-JUN-13:20 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8.39 | 0.00 |
July | 23138.40 | 30-JUL-13:53 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.03 |
August | 30622.98 | 06-AUG-13:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.88 |
September | 34535.52 | 10-SEP-14:01 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.48 |
October | 30450.24 | 08-OCT-13:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.88 |
November | 13611.82 | 04-NOV-13:30 | 211.67 | 242.38 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10605.01 | 05-DEC-12:30 | 1058.33 | 1454.32 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10605.01 | 211.67 | 242.38 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34535.52 | 2010.83 | 1454.32 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 8.39 | 778.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3189.19 | 05-JAN-15:50 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.78 |
February | 5825.55 | 27-FEB-15:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.70 |
March | 8536.70 | 14-MAR-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
April | 12845.89 | 26-APR-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 0.00 |
May | 25586.73 | 07-MAY-16:41 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.21 |
June | 22963.83 | 18-JUN-17:01 | 0.00 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 710.85 |
July | 24348.22 | 23-JUL-17:02 | 0.00 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.09 |
August | 23882.96 | 06-AUG-17:01 | 0.00 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.20 |
September | 22901.87 | 10-SEP-15:22 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.40 |
October | 10110.24 | 04-OCT-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.49 |
November | 3975.21 | 04-NOV-15:40 | 130.46 | 156.20 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 |
December | 3344.65 | 05-DEC-15:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3189.19 | 0.00 | 156.20 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25586.73 | 1239.33 | 937.20 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 710.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4613.25 | 04-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.25 |
February | 5414.01 | 07-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.36 |
March | 5665.23 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.77 |
April | 8200.34 | 03-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.47 |
May | 8694.24 | 08-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.36 |
June | 11238.33 | 12-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.38 |
July | 10382.83 | 10-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.23 |
August | 10389.48 | 28-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.47 |
September | 10465.02 | 05-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.31 |
October | 9343.48 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.70 |
November | 8000.50 | 06-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.97 |
December | 5474.91 | 30-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4613.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.47 | |
Maximum of Months | 11238.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5293.39 | 14-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2947.66 |
February | 4219.12 | 17-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1557.82 |
March | 4351.01 | 22-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5916.88 | 28-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.65 |
May | 5964.21 | 08-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.37 |
June | 6787.55 | 12-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.59 |
July | 6459.31 | 10-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.43 |
August | 7422.50 | 26-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.48 |
September | 7145.36 | 12-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.36 |
October | 5797.09 | 12-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.83 |
November | 4329.65 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.97 |
December | 4727.68 | 09-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4219.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7422.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2947.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 337.52 | 11-JAN-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.96 |
February | 2941.89 | 27-FEB-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.93 |
March | 5676.19 | 14-MAR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.68 |
April | 15565.95 | 27-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 0.00 |
May | 15954.99 | 15-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.08 |
June | 16556.08 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.08 |
July | 18202.73 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.59 | 0.00 |
August | 19089.03 | 10-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.62 | 0.00 |
September | 14273.53 | 14-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.07 |
October | 8895.90 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.31 |
November | 3731.62 | 04-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 112.33 | 16-DEC-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 112.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19089.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.59 | 542.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1980.63 | 05-JAN-16:10 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4090.08 | 07-FEB-16:50 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6986.26 | 31-MAR-24:00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8188.89 | 26-APR-17:50 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3482.01 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5349.26 | 30-JUN-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7263.80 | 31-JUL-23:50 | 0.00 | 86.81 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8556.89 | 06-AUG-18:40 | 0.00 | 144.69 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3323.84 | 30-SEP-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4992.56 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5794.56 | 10-NOV-16:00 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7813.66 | 05-DEC-15:50 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1980.63 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8556.89 | 222.14 | 520.85 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1566.02 | 05-JAN-16:20 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3724.44 | 08-FEB-16:50 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6128.85 | 31-MAR-24:00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7759.40 | 26-APR-17:50 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3225.97 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4993.39 | 30-JUN-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7001.23 | 31-JUL-24:00 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7922.39 | 06-AUG-18:17 | 0.00 | 260.44 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2921.77 | 30-SEP-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4152.54 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5322.17 | 10-NOV-16:10 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7133.60 | 05-DEC-16:00 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1566.02 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7922.39 | 222.14 | 520.85 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1398.26 | 05-JAN-16:20 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3604.74 | 27-FEB-16:20 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5688.93 | 02-MAR-17:00 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7828.54 | 26-APR-17:50 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3137.07 | 31-MAY-23:40 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4883.63 | 30-JUN-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6983.01 | 31-JUL-24:00 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8047.02 | 06-AUG-18:38 | 0.00 | 144.69 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2489.48 | 30-SEP-23:30 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4128.66 | 04-OCT-16:50 | 70.15 | 289.36 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5171.12 | 10-NOV-16:00 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6953.46 | 05-DEC-16:00 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1398.26 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8047.02 | 222.14 | 520.85 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91721.74 | 12-JAN-17:00 | 4808.68 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184019.63 | 28-FEB-17:00 | 4808.68 | 5919.59 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358670.22 | 31-MAR-24:00 | 0.00 | 328.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368449.01 | 28-APR-16:00 | 4808.68 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176445.04 | 31-MAY-24:00 | 0.00 | 328.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268051.58 | 30-JUN-24:00 | 0.00 | 328.88 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360487.83 | 31-JUL-24:00 | 0.00 | 1315.53 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370336.62 | 29-AUG-21:14 | 1265.44 | 3288.82 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175632.48 | 30-SEP-24:00 | 0.00 | 328.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267382.27 | 31-OCT-24:00 | 0.00 | 328.88 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276655.69 | 06-NOV-17:00 | 4808.68 | 5919.59 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367998.47 | 04-DEC-17:00 | 4808.68 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91721.74 | 0.00 | 328.88 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370336.62 | 4808.68 | 5919.59 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.165278E+13 | 1097296.64 | 12-JAN-16:00 | 0.411518E+12 | 1304086.33 | 02-JAN-06:19 |
February | 0.185713E+13 | 1283513.26 | 27-FEB-16:10 | 0.253251E+12 | 652908.43 | 21-FEB-07:19 |
March | 0.251334E+13 | 1437178.87 | 14-MAR-15:39 | 0.130765E+12 | 453248.72 | 06-MAR-06:10 |
April | 0.281140E+13 | 1884113.54 | 27-APR-15:09 | 0.817022E+11 | 322161.58 | 11-APR-05:10 |
May | 0.176395E+13 | 1355486.84 | 04-MAY-15:09 | 0.659555E+11 | 202861.18 | 18-MAY-05:10 |
June | 0.219794E+13 | 1565896.89 | 28-JUN-15:30 | 0.598045E+11 | 77517.57 | 09-JUN-11:50 |
July | 0.270385E+13 | 1794311.80 | 31-JUL-15:20 | 0.565522E+11 | 76525.32 | 03-JUL-11:39 |
August | 0.323315E+13 | 1983009.31 | 10-AUG-15:09 | 0.600093E+11 | 75879.02 | 28-AUG-11:39 |
September | 0.175576E+13 | 1421836.74 | 12-SEP-15:20 | 0.573976E+11 | 84448.42 | 27-SEP-05:49 |
October | 0.211312E+13 | 1376066.56 | 04-OCT-15:30 | 0.874563E+11 | 355608.05 | 28-OCT-05:10 |
November | 0.240885E+13 | 1414440.00 | 08-NOV-16:00 | 0.189273E+12 | 526775.85 | 24-NOV-07:10 |
December | 0.283675E+13 | 1548999.70 | 01-DEC-16:19 | 0.318318E+12 | 780981.35 | 26-DEC-07:19 |
Annual Sum or Average | 0.278480E+14 | 0.177200E+13 | ||||
Minimum of Months | 0.165278E+13 | 1097296.64 | 0.565522E+11 | 75879.02 | ||
Maximum of Months | 0.323315E+13 | 1983009.31 | 0.411518E+12 | 1304086.33 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.315739E+12 | 0.770639E+11 | 0.811612E+12 | 0.164873E+12 | 0.170403E+12 | 0.129516E+11 | 0.00 | 0.868662E+11 | 0.122508E+11 | 0.102174E+10 | 0.00 | 0.00 | 0.00 |
February | 0.282919E+12 | 0.623044E+11 | 0.102011E+13 | 0.148926E+12 | 0.157922E+12 | 0.124265E+11 | 0.00 | 0.143168E+12 | 0.282954E+11 | 0.105965E+10 | 0.00 | 0.00 | 0.00 |
March | 0.333120E+12 | 0.589701E+11 | 0.146267E+13 | 0.165150E+12 | 0.186721E+12 | 0.146623E+11 | 0.00 | 0.225893E+12 | 0.652170E+11 | 0.942840E+09 | 0.00 | 0.00 | 0.00 |
April | 0.296070E+12 | 0.470192E+11 | 0.170311E+13 | 0.159524E+12 | 0.188253E+12 | 0.214929E+11 | 0.00 | 0.297649E+12 | 0.978603E+11 | 0.423197E+09 | 0.00 | 0.00 | 0.00 |
May | 0.318543E+12 | 0.407176E+11 | 0.820521E+12 | 0.165009E+12 | 0.206071E+12 | 0.306855E+11 | 0.00 | 0.127666E+12 | 0.546784E+11 | 62018380.21 | 0.00 | 0.00 | 0.00 |
June | 0.316316E+12 | 0.354545E+11 | 0.110677E+13 | 0.159786E+12 | 0.213376E+12 | 0.426631E+11 | 0.00 | 0.219822E+12 | 0.103744E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.296415E+12 | 0.381281E+11 | 0.143888E+13 | 0.164745E+12 | 0.229484E+12 | 0.591872E+11 | 0.00 | 0.343146E+12 | 0.133870E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.330574E+12 | 0.446580E+11 | 0.177780E+13 | 0.165149E+12 | 0.245407E+12 | 0.677661E+11 | 0.00 | 0.459532E+12 | 0.142263E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.297030E+12 | 0.526918E+11 | 0.784732E+12 | 0.159522E+12 | 0.206644E+12 | 0.381156E+11 | 0.00 | 0.141422E+12 | 0.755987E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.310877E+12 | 0.648383E+11 | 0.112899E+13 | 0.164871E+12 | 0.189088E+12 | 0.184850E+11 | 0.00 | 0.169141E+12 | 0.667953E+11 | 35308214.77 | 0.00 | 0.00 | 0.00 |
November | 0.311166E+12 | 0.718615E+11 | 0.140306E+13 | 0.159635E+12 | 0.170322E+12 | 0.149496E+11 | 0.00 | 0.215755E+12 | 0.617914E+11 | 0.307834E+09 | 0.00 | 0.00 | 0.00 |
December | 0.306877E+12 | 0.794438E+11 | 0.175516E+13 | 0.164750E+12 | 0.172241E+12 | 0.133714E+11 | 0.00 | 0.280088E+12 | 0.638876E+11 | 0.932330E+09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371564E+13 | 0.673151E+12 | 0.152134E+14 | 0.194194E+13 | 0.233593E+13 | 0.346757E+12 | 0.00 | 0.271015E+13 | 0.906252E+12 | 0.478492E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.282919E+12 | 0.354545E+11 | 0.784732E+12 | 0.148926E+12 | 0.157922E+12 | 0.124265E+11 | 0.00 | 0.868662E+11 | 0.122508E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.333120E+12 | 0.794438E+11 | 0.177780E+13 | 0.165150E+12 | 0.245407E+12 | 0.677661E+11 | 0.00 | 0.459532E+12 | 0.142263E+12 | 0.105965E+10 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.347935E+12 | 0.00 | 0.635830E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.195254E+12 | 0.00 | 0.579968E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.641522E+11 | 0.00 | 0.666127E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.215614E+11 | 0.00 | 0.601409E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.402017E+10 | 0.00 | 0.619353E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.504613E+09 | 0.00 | 0.592999E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.565522E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 29914363.14 | 0.00 | 0.599794E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.145483E+10 | 0.00 | 0.559428E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.283938E+11 | 0.00 | 0.590626E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.129887E+12 | 0.00 | 0.593858E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.256987E+12 | 0.00 | 0.613305E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.105018E+13 | 0.00 | 0.721822E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.559428E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.347935E+12 | 0.00 | 0.666127E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 352853.36 | 02-JAN-16:30 | 54335.80 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 118955.15 | 04-JAN-08:20 | 100453.36 | 20-JAN-13:20 | 36424.75 | 02-JAN-06:19 | 0.00 | 01-JAN-00:10 |
February | 345329.27 | 02-FEB-16:00 | 54335.80 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 118951.23 | 02-FEB-08:20 | 127484.00 | 27-FEB-14:00 | 34134.42 | 21-FEB-06:40 | 0.00 | 01-FEB-00:10 |
March | 337535.03 | 22-MAR-07:10 | 54335.80 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 118946.42 | 22-MAR-07:19 | 142913.51 | 14-MAR-15:30 | 33407.99 | 24-MAR-05:10 | 0.00 | 01-MAR-00:10 |
April | 325064.63 | 03-APR-07:10 | 54335.80 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 118936.02 | 03-APR-07:19 | 220467.41 | 27-APR-14:30 | 54523.82 | 27-APR-11:50 | 0.00 | 01-APR-00:10 |
May | 316816.17 | 01-MAY-07:10 | 54335.80 | 01-MAY-19:19 | 439129.89 | 01-MAY-07:10 | 118929.14 | 01-MAY-07:19 | 204846.95 | 15-MAY-15:20 | 54128.27 | 04-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 316816.17 | 01-JUN-07:10 | 54335.80 | 01-JUN-19:00 | 557421.28 | 01-JUN-07:10 | 118929.14 | 01-JUN-07:19 | 211065.33 | 28-JUN-15:20 | 56203.41 | 27-JUN-13:30 | 0.00 | 01-JUN-00:10 |
July | 321703.69 | 12-JUL-08:30 | 54335.80 | 01-JUL-20:10 | 675712.68 | 03-JUL-07:10 | 118932.87 | 12-JUL-07:40 | 236483.86 | 31-JUL-14:00 | 56728.45 | 19-JUL-13:30 | 0.00 | 01-JUL-00:10 |
August | 319760.63 | 28-AUG-07:30 | 54335.80 | 01-AUG-19:40 | 794004.08 | 01-AUG-07:10 | 118931.60 | 28-AUG-07:40 | 257070.54 | 10-AUG-14:50 | 54161.81 | 09-AUG-09:39 | 0.00 | 01-AUG-00:10 |
September | 338015.86 | 25-SEP-07:10 | 54335.80 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 118946.82 | 25-SEP-07:19 | 228589.10 | 14-SEP-15:09 | 56579.67 | 08-SEP-14:39 | 0.00 | 01-SEP-00:10 |
October | 351840.41 | 31-OCT-07:10 | 54335.80 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 118958.37 | 31-OCT-07:19 | 191759.39 | 04-OCT-15:30 | 34000.70 | 04-OCT-13:30 | 0.00 | 01-OCT-00:10 |
November | 352853.36 | 06-NOV-16:49 | 54335.80 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 118958.41 | 03-NOV-07:19 | 112594.94 | 15-NOV-13:09 | 33746.00 | 13-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 352853.36 | 01-DEC-16:19 | 54335.80 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 118958.47 | 28-DEC-08:20 | 109372.42 | 06-DEC-14:09 | 34795.90 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 316816.17 | 54335.80 | 439129.89 | 118929.14 | 100453.36 | 33407.99 | 0.00 | |||||||
Maximum of Months | 352853.36 | 54335.80 | 794004.08 | 118958.47 | 257070.54 | 56728.45 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 37493.72 | 20-JAN-15:50 | 23085.92 | 11-JAN-14:00 | 4833.89 | 14-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 137228.91 | 27-FEB-14:00 | 49831.31 | 27-FEB-15:09 | 4628.55 | 11-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 156083.31 | 18-MAR-15:00 | 49546.82 | 18-MAR-14:20 | 5278.55 | 25-MAR-16:30 | 0.00 | 0.00 | 0.00 |
April | 343506.72 | 27-APR-15:09 | 80718.76 | 27-APR-12:30 | 8453.97 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 |
May | 220957.81 | 04-MAY-13:50 | 80718.76 | 05-MAY-12:39 | 2095.65 | 20-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 266844.20 | 28-JUN-15:39 | 80718.76 | 21-JUN-15:30 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 360922.16 | 31-JUL-15:00 | 80718.76 | 07-JUL-11:50 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 409599.59 | 29-AUG-14:30 | 80718.76 | 07-AUG-10:20 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 227131.98 | 14-SEP-13:09 | 80718.76 | 11-SEP-15:50 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 149694.03 | 04-OCT-14:00 | 50483.19 | 04-OCT-15:20 | 1713.99 | 03-OCT-20:00 | 0.00 | 0.00 | 0.00 |
November | 162716.66 | 04-NOV-13:00 | 50709.29 | 04-NOV-13:00 | 3640.78 | 15-NOV-21:00 | 0.00 | 0.00 | 0.00 |
December | 109001.29 | 04-DEC-15:09 | 49248.27 | 14-DEC-11:50 | 4257.59 | 02-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 37493.72 | 23085.92 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 409599.59 | 80718.76 | 8453.97 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1097296.64 | 12-JAN-16:00 | 352853.36 | 439129.89 | 54335.80 | 84915.83 | 92087.20 | 32328.83 | 0.00 | 36293.11 | 5352.63 |
February | 1283513.26 | 27-FEB-16:10 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 113803.57 | 32518.16 | 0.00 | 128345.14 | 49723.19 |
March | 1437178.87 | 14-MAR-15:39 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 142837.84 | 32394.82 | 0.00 | 135137.57 | 49394.04 |
April | 1884113.54 | 27-APR-15:09 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 213159.34 | 51022.72 | 0.00 | 343506.72 | 80718.76 |
May | 1355486.84 | 04-MAY-15:09 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 198038.18 | 54013.75 | 0.00 | 209504.25 | 53098.86 |
June | 1565896.89 | 28-JUN-15:30 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 210961.66 | 51451.50 | 0.00 | 263641.76 | 80718.76 |
July | 1794311.80 | 31-JUL-15:20 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 235039.30 | 51716.79 | 0.00 | 349422.36 | 80718.76 |
August | 1983009.31 | 10-AUG-15:09 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 255194.21 | 52321.66 | 0.00 | 399068.69 | 80718.76 |
September | 1421836.74 | 12-SEP-15:20 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 224313.97 | 51010.89 | 0.00 | 224961.31 | 80718.76 |
October | 1376066.56 | 04-OCT-15:30 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 191759.39 | 33101.38 | 0.00 | 141685.97 | 50396.62 |
November | 1414440.00 | 08-NOV-16:00 | 352853.36 | 675712.68 | 54335.80 | 84915.83 | 102020.94 | 32303.11 | 0.00 | 85460.95 | 26837.34 |
December | 1548999.70 | 01-DEC-16:19 | 352853.36 | 794004.08 | 54335.80 | 84907.53 | 94020.21 | 32322.85 | 0.00 | 107889.35 | 28666.54 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1097296.64 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 92087.20 | 32303.11 | 0.00 | 36293.11 | 5352.63 | |
Maximum of Months | 1983009.31 | 352853.36 | 794004.08 | 54335.80 | 84915.83 | 255194.21 | 54013.75 | 0.00 | 399068.69 | 80718.76 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1298390.46 | 02-JAN-06:19 | 0.00 | 81360.36 | 31-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 623325.18 | 21-FEB-07:10 | 0.00 | 81418.03 | 08-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 447552.85 | 06-MAR-06:10 | 0.00 | 81295.48 | 01-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 316465.71 | 11-APR-05:10 | 0.00 | 80493.27 | 03-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 181673.32 | 18-MAY-05:10 | 0.00 | 79354.80 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 51132.55 | 14-JUN-05:10 | 0.00 | 77517.57 | 09-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 76525.32 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 3420.69 | 03-AUG-05:00 | 0.00 | 75879.02 | 28-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 61425.72 | 27-SEP-05:10 | 0.00 | 76773.06 | 28-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 328864.23 | 28-OCT-05:10 | 0.00 | 78224.06 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 497639.60 | 24-NOV-07:10 | 0.00 | 79657.88 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 751626.24 | 26-DEC-07:10 | 0.00 | 80731.25 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 75879.02 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1298390.46 | 0.00 | 81418.03 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 26.71 | 1.17 | 26.87 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.88 | 0.00 | 25.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 26.10 | 0.00 | 26.10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.94 | 0.00 | 25.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.33 | 0.00 | 26.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.60 | 0.00 | 26.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 26.39 | 0.00 | 26.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.17 | 0.00 | 26.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.86 | 0.17 | 26.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.58 | 1.17 | 26.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 26.56 | 1.50 | 26.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 26.25 | 0.00 | 26.25 |
Annual Sum or Average | 0.00 | 0.00 | 70.33 | 26.45 | 4.00 | 26.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.88 | 0.00 | 25.88 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.86 | 1.50 | 26.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.59 | 0.00 | 25.59 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.62 | 0.00 | 25.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.69 | 0.00 | 25.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.73 | 0.00 | 25.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.63 | 0.00 | 25.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.65 | 0.00 | 25.65 |
Annual Sum or Average | 0.00 | 0.00 | 2.67 | 25.66 | 0.00 | 25.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.73 | 0.00 | 25.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 18.75 | 0.17 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
February | 0.33 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
December | 0.67 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
Annual Sum or Average | 3.17 | 18.81 | 0.17 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.68 | 1.17 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.90 | 1.00 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.16 | 2.17 | 28.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.05 | 2.17 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.87 | 1.00 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.67 | 27.96 | 7.67 | 27.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.16 | 2.17 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.60 | 0.83 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.54 | 0.50 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.33 | 27.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.79 | 1.83 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.90 | 2.67 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.15 | 1.67 | 28.15 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.77 | 0.83 | 27.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.33 | 27.80 | 9.33 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.15 | 2.67 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.65 | 2.67 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.24 | 2.67 | 28.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.02 | 1.67 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.87 | 5.50 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.44 | 3.50 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.08 | 1.50 | 28.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.37 | 0.17 | 27.37 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.38 | 0.17 | 27.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 39.83 | 27.77 | 18.00 | 27.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 28.24 | 5.50 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.84 | 0.33 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
February | 0.67 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Annual Sum or Average | 3.67 | 18.98 | 0.33 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.35 | 0.33 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
February | 0.67 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.77 | 0.83 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.04 | 0.83 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.26 | 2.33 | 28.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.18 | 2.17 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.90 | 0.83 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Annual Sum or Average | 2.83 | 18.95 | 0.00 | 18.95 | 7.00 | 25.47 | 7.00 | 26.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.30 | 0.00 | 19.30 | 2.33 | 28.26 | 2.33 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
February | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.48 | 0.67 | 27.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.49 | 0.50 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.78 | 1.83 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.98 | 2.17 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.37 | 1.67 | 28.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.88 | 0.67 | 27.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Annual Sum or Average | 1.67 | 18.81 | 0.00 | 18.81 | 7.50 | 26.27 | 7.50 | 27.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.41 | 0.00 | 19.41 | 2.17 | 28.37 | 2.17 | 28.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.17 | 1.83 | 28.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.02 | 0.67 | 28.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.47 | 1.67 | 28.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.22 | 1.50 | 28.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.85 | 1.00 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 18.57 | 0.00 | 18.57 | 13.50 | 27.56 | 6.67 | 27.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 18.57 | 0.00 | 18.57 | 4.17 | 28.47 | 1.83 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.50 | 16.97 | 7.33 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
February | 17.00 | 17.10 | 4.67 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
March | 2.50 | 18.94 | 0.17 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
April | 0.50 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.83 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
November | 4.83 | 18.87 | 0.67 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
December | 12.17 | 18.22 | 2.17 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
Annual Sum or Average | 66.33 | 17.49 | 15.00 | 17.58 | 0.00 | 17.58 | 0.00 | 17.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.50 | 19.34 | 7.33 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.00 | 16.09 | 3.17 | 15.94 | 0.00 | 15.94 | 0.00 | 15.94 |
February | 9.50 | 16.61 | 0.83 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
March | 2.33 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
April | 0.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.43 | 0.50 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.71 | 0.67 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.14 | 2.33 | 28.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.06 | 2.00 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.54 | 0.67 | 27.54 |
October | 0.83 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
November | 3.50 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
December | 8.33 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 |
Annual Sum or Average | 46.17 | 16.90 | 4.00 | 16.74 | 6.17 | 17.96 | 6.17 | 18.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 0.00 | 15.94 |
Maximum of Months | 21.00 | 19.32 | 3.17 | 19.32 | 2.33 | 28.14 | 2.33 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.83 | 16.57 | 1.33 | 16.43 | 0.00 | 16.43 | 0.00 | 16.43 |
February | 4.67 | 17.41 | 0.67 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
March | 1.50 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
April | 0.33 | 19.30 | 0.00 | 19.30 | 0.33 | 23.31 | 0.33 | 24.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.35 | 0.50 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.85 | 2.00 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.01 | 2.17 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.43 | 1.50 | 28.43 |
October | 0.33 | 19.38 | 0.00 | 19.38 | 0.33 | 23.45 | 0.33 | 24.81 |
November | 3.17 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
December | 6.17 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
Annual Sum or Average | 31.00 | 17.42 | 2.00 | 17.27 | 6.83 | 19.10 | 6.83 | 20.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.83 | 19.38 | 1.33 | 19.38 | 2.17 | 28.43 | 2.17 | 28.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.17 | 17.21 | 1.00 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
February | 3.83 | 17.84 | 0.67 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
March | 1.17 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
April | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.12 | 1.83 | 28.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.92 | 0.67 | 27.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.71 | 1.50 | 28.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.32 | 1.33 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.20 | 0.50 | 28.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.33 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
December | 5.50 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
Annual Sum or Average | 22.17 | 18.01 | 1.67 | 17.80 | 12.33 | 21.39 | 5.83 | 22.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.17 | 19.42 | 1.00 | 19.42 | 3.83 | 28.71 | 1.83 | 28.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 28.43 | 17.17 | 28.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 94.00 | 28.44 | 91.33 | 28.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 112.50 | 28.44 | 108.50 | 28.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 94.00 | 28.44 | 91.33 | 28.44 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 73.33 | 23.99 | 86.50 | 25.09 | 0.00 | 25.09 |
February | 52.17 | 24.00 | 105.17 | 25.07 | 0.00 | 25.07 |
March | 34.33 | 24.00 | 102.67 | 25.38 | 0.00 | 25.38 |
April | 3.17 | 24.00 | 156.33 | 25.51 | 0.00 | 25.51 |
May | 0.00 | 0.00 | 229.83 | 25.06 | 0.00 | 25.06 |
June | 0.00 | 0.00 | 275.17 | 24.82 | 0.00 | 24.82 |
July | 0.00 | 0.00 | 403.17 | 24.74 | 0.00 | 24.74 |
August | 0.33 | 27.13 | 472.00 | 24.51 | 0.33 | 24.52 |
September | 0.00 | 0.00 | 366.33 | 24.70 | 0.00 | 24.70 |
October | 0.00 | 0.00 | 181.50 | 25.51 | 0.00 | 25.51 |
November | 1.67 | 24.00 | 190.00 | 25.40 | 0.00 | 25.40 |
December | 22.33 | 24.00 | 107.50 | 25.88 | 0.00 | 25.88 |
Annual Sum or Average | 187.33 | 24.00 | 2676.17 | 24.99 | 0.33 | 24.99 |
Minimum of Months | 0.00 | 0.00 | 86.50 | 24.51 | 0.00 | 24.52 |
Maximum of Months | 73.33 | 27.13 | 472.00 | 25.88 | 0.33 | 25.88 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 187.00 | 23.86 | 23.33 | 24.03 | 12.83 | 24.12 |
February | 96.50 | 23.84 | 73.67 | 24.34 | 0.00 | 24.34 |
March | 36.33 | 23.97 | 108.67 | 25.00 | 0.00 | 25.00 |
April | 2.50 | 23.98 | 169.17 | 24.97 | 0.00 | 24.97 |
May | 7.83 | 23.79 | 226.67 | 24.64 | 0.00 | 24.64 |
June | 0.00 | 0.00 | 299.00 | 24.47 | 0.00 | 24.47 |
July | 0.00 | 0.00 | 422.67 | 24.38 | 0.00 | 24.38 |
August | 0.00 | 0.00 | 480.00 | 24.27 | 0.00 | 24.27 |
September | 0.00 | 0.00 | 361.00 | 24.49 | 0.00 | 24.49 |
October | 9.00 | 23.72 | 192.50 | 24.96 | 0.00 | 24.96 |
November | 15.67 | 23.86 | 186.67 | 24.93 | 0.00 | 24.93 |
December | 49.67 | 23.90 | 99.50 | 25.12 | 0.00 | 25.12 |
Annual Sum or Average | 404.50 | 23.87 | 2642.83 | 24.55 | 12.83 | 24.56 |
Minimum of Months | 0.00 | 0.00 | 23.33 | 24.03 | 0.00 | 24.12 |
Maximum of Months | 187.00 | 23.98 | 480.00 | 25.12 | 12.83 | 25.12 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 468.67 | 22.81 | 12.67 | 22.71 | 12.67 | 22.62 |
February | 372.50 | 23.24 | 0.00 | 23.24 | 0.00 | 23.24 |
March | 308.17 | 23.61 | 4.00 | 23.62 | 0.00 | 23.62 |
April | 173.33 | 23.57 | 44.33 | 23.81 | 0.00 | 23.81 |
May | 86.17 | 23.61 | 134.50 | 24.15 | 0.00 | 24.15 |
June | 28.17 | 23.60 | 174.00 | 24.39 | 0.00 | 24.39 |
July | 6.50 | 23.52 | 311.17 | 24.39 | 0.00 | 24.39 |
August | 13.83 | 23.47 | 405.33 | 24.25 | 0.00 | 24.25 |
September | 22.83 | 23.47 | 263.50 | 24.38 | 0.00 | 24.38 |
October | 168.00 | 23.48 | 53.67 | 23.85 | 0.00 | 23.85 |
November | 316.00 | 23.45 | 24.83 | 23.53 | 0.00 | 23.53 |
December | 439.00 | 23.19 | 0.00 | 23.19 | 0.00 | 23.19 |
Annual Sum or Average | 2403.17 | 23.28 | 1428.00 | 23.70 | 12.67 | 23.68 |
Minimum of Months | 6.50 | 22.81 | 0.00 | 22.71 | 0.00 | 22.62 |
Maximum of Months | 468.67 | 23.61 | 405.33 | 24.39 | 12.67 | 24.39 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.36 | 123.67 | 20.94 | 123.67 | 20.66 |
February | 439.33 | 21.87 | 74.83 | 21.54 | 74.83 | 21.29 |
March | 459.33 | 22.68 | 16.83 | 22.61 | 16.50 | 22.53 |
April | 324.67 | 23.00 | 33.67 | 23.13 | 0.00 | 23.13 |
May | 204.17 | 23.29 | 77.83 | 23.56 | 0.00 | 23.56 |
June | 93.33 | 23.46 | 154.50 | 24.03 | 0.00 | 24.03 |
July | 29.50 | 23.50 | 302.83 | 24.25 | 0.00 | 24.25 |
August | 45.17 | 23.35 | 361.17 | 24.12 | 0.00 | 24.12 |
September | 137.83 | 23.23 | 175.67 | 23.81 | 0.00 | 23.81 |
October | 370.67 | 22.81 | 2.50 | 22.81 | 0.00 | 22.81 |
November | 457.50 | 22.22 | 34.67 | 22.09 | 32.67 | 21.98 |
December | 497.00 | 21.65 | 100.33 | 21.37 | 100.33 | 21.17 |
Annual Sum or Average | 3560.50 | 22.33 | 1458.50 | 22.58 | 348.00 | 22.39 |
Minimum of Months | 29.50 | 21.36 | 2.50 | 20.94 | 0.00 | 20.66 |
Maximum of Months | 502.00 | 23.50 | 361.17 | 24.25 | 123.67 | 24.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.18 | 16.83 | 22.14 | 16.83 | 22.10 |
February | 420.00 | 22.59 | 6.17 | 22.56 | 6.17 | 22.53 |
March | 410.67 | 23.27 | 0.17 | 23.27 | 0.00 | 23.27 |
April | 221.50 | 23.51 | 55.67 | 23.70 | 0.00 | 23.70 |
May | 146.17 | 23.50 | 118.67 | 23.91 | 0.00 | 23.91 |
June | 25.67 | 23.53 | 204.17 | 24.29 | 0.00 | 24.29 |
July | 0.00 | 0.00 | 376.33 | 24.33 | 0.00 | 24.33 |
August | 5.17 | 23.54 | 422.33 | 24.22 | 0.00 | 24.22 |
September | 101.50 | 23.37 | 203.50 | 24.02 | 0.00 | 24.02 |
October | 294.00 | 23.25 | 20.33 | 23.38 | 0.00 | 23.38 |
November | 395.67 | 23.04 | 14.50 | 23.10 | 0.00 | 23.10 |
December | 492.33 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
Annual Sum or Average | 3014.67 | 22.92 | 1438.67 | 23.36 | 23.00 | 23.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.14 | 0.00 | 22.10 |
Maximum of Months | 502.00 | 23.54 | 422.33 | 24.33 | 16.83 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.47 | 22.33 | 21.43 | 22.33 | 21.40 |
February | 437.00 | 21.86 | 9.50 | 21.84 | 8.83 | 21.81 |
March | 469.33 | 22.41 | 2.83 | 22.42 | 0.00 | 22.42 |
April | 289.50 | 22.69 | 78.50 | 23.03 | 0.00 | 23.03 |
May | 223.83 | 22.83 | 157.50 | 23.46 | 3.33 | 23.49 |
June | 122.00 | 23.01 | 239.83 | 23.88 | 4.17 | 23.92 |
July | 102.83 | 23.27 | 301.83 | 24.00 | 9.17 | 24.06 |
August | 101.17 | 23.15 | 329.00 | 23.90 | 8.67 | 23.96 |
September | 200.50 | 22.71 | 190.67 | 23.53 | 4.50 | 23.57 |
October | 379.67 | 22.45 | 46.17 | 22.68 | 0.00 | 22.68 |
November | 467.50 | 22.01 | 5.67 | 22.04 | 0.00 | 22.04 |
December | 497.00 | 21.67 | 0.33 | 21.67 | 0.33 | 21.67 |
Annual Sum or Average | 3792.33 | 22.20 | 1384.17 | 22.74 | 61.33 | 22.75 |
Minimum of Months | 101.17 | 21.47 | 0.33 | 21.43 | 0.00 | 21.40 |
Maximum of Months | 502.00 | 23.27 | 329.00 | 24.00 | 22.33 | 24.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 471.50 | 21.49 | 46.67 | 21.46 | 38.83 | 21.38 |
February | 363.33 | 21.90 | 66.50 | 22.17 | 16.17 | 22.11 |
March | 372.83 | 22.46 | 58.00 | 22.70 | 0.00 | 22.70 |
April | 251.33 | 22.80 | 123.50 | 23.30 | 1.00 | 23.31 |
May | 224.83 | 22.87 | 168.17 | 23.51 | 2.17 | 23.53 |
June | 137.17 | 22.96 | 232.00 | 23.82 | 1.33 | 23.83 |
July | 82.83 | 23.34 | 331.67 | 24.11 | 7.50 | 24.16 |
August | 78.17 | 23.50 | 375.33 | 24.09 | 10.67 | 24.15 |
September | 161.17 | 22.92 | 260.00 | 23.83 | 6.33 | 23.88 |
October | 296.50 | 22.56 | 126.17 | 23.15 | 2.50 | 23.18 |
November | 412.67 | 22.14 | 41.50 | 22.38 | 0.50 | 22.38 |
December | 441.17 | 21.82 | 28.67 | 21.96 | 2.67 | 21.95 |
Annual Sum or Average | 3293.50 | 22.29 | 1858.17 | 22.99 | 89.67 | 22.98 |
Minimum of Months | 78.17 | 21.49 | 28.67 | 21.46 | 0.00 | 21.38 |
Maximum of Months | 471.50 | 23.50 | 375.33 | 24.11 | 38.83 | 24.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.50 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
February | 360.33 | 22.52 | 38.83 | 22.76 | 0.00 | 22.76 |
March | 219.67 | 23.02 | 108.17 | 23.62 | 0.00 | 23.62 |
April | 59.67 | 23.83 | 280.50 | 24.62 | 10.17 | 24.68 |
May | 137.83 | 23.22 | 262.67 | 24.11 | 12.50 | 24.20 |
June | 25.67 | 24.12 | 395.00 | 24.42 | 7.33 | 24.46 |
July | 27.17 | 26.99 | 480.33 | 24.67 | 27.17 | 24.78 |
August | 21.83 | 26.98 | 514.00 | 24.51 | 21.83 | 24.61 |
September | 104.67 | 23.15 | 300.50 | 24.19 | 9.00 | 24.25 |
October | 215.83 | 22.88 | 148.33 | 23.72 | 1.50 | 23.73 |
November | 272.17 | 22.94 | 92.67 | 23.45 | 0.83 | 23.46 |
December | 315.33 | 22.96 | 47.17 | 23.26 | 0.00 | 23.26 |
Annual Sum or Average | 2256.67 | 22.81 | 2668.17 | 23.78 | 90.33 | 23.84 |
Minimum of Months | 21.83 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
Maximum of Months | 496.50 | 26.99 | 514.00 | 24.67 | 27.17 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.52 | 261.50 | 20.31 | 261.50 | 20.20 |
February | 454.00 | 21.00 | 150.33 | 20.73 | 150.33 | 20.57 |
March | 510.83 | 21.91 | 38.00 | 21.80 | 38.00 | 21.70 |
April | 420.50 | 22.56 | 17.17 | 22.61 | 1.67 | 22.61 |
May | 288.83 | 23.02 | 54.50 | 23.20 | 0.00 | 23.20 |
June | 142.00 | 23.31 | 94.50 | 23.66 | 0.00 | 23.66 |
July | 67.00 | 23.44 | 251.00 | 24.03 | 0.00 | 24.03 |
August | 91.33 | 23.33 | 301.67 | 23.97 | 0.00 | 23.97 |
September | 243.00 | 23.06 | 95.33 | 23.37 | 0.00 | 23.37 |
October | 478.00 | 22.31 | 4.00 | 22.29 | 4.00 | 22.27 |
November | 489.00 | 21.40 | 92.67 | 21.21 | 92.67 | 21.07 |
December | 497.00 | 20.78 | 215.00 | 20.60 | 215.00 | 20.50 |
Annual Sum or Average | 4183.50 | 21.81 | 1575.67 | 21.91 | 763.17 | 21.69 |
Minimum of Months | 67.00 | 20.52 | 4.00 | 20.31 | 0.00 | 20.20 |
Maximum of Months | 510.83 | 23.44 | 301.67 | 24.03 | 261.50 | 24.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.34 | 243.67 | 20.16 | 243.67 | 20.08 |
February | 385.00 | 20.86 | 134.83 | 20.67 | 134.83 | 20.56 |
March | 424.50 | 21.45 | 28.50 | 21.37 | 27.83 | 21.30 |
April | 320.83 | 22.04 | 39.67 | 22.30 | 0.67 | 22.30 |
May | 283.83 | 22.37 | 81.33 | 22.85 | 3.00 | 22.88 |
June | 187.33 | 22.71 | 147.17 | 23.49 | 3.33 | 23.52 |
July | 152.67 | 23.07 | 207.33 | 23.86 | 10.33 | 23.95 |
August | 143.67 | 22.95 | 230.33 | 23.80 | 9.67 | 23.88 |
September | 252.67 | 22.33 | 108.00 | 22.97 | 3.83 | 23.01 |
October | 390.83 | 21.70 | 21.00 | 21.80 | 5.67 | 21.78 |
November | 417.00 | 21.01 | 90.50 | 20.87 | 90.50 | 20.77 |
December | 422.00 | 20.60 | 199.17 | 20.46 | 199.17 | 20.38 |
Annual Sum or Average | 3807.33 | 21.51 | 1531.50 | 21.77 | 732.50 | 21.60 |
Minimum of Months | 143.67 | 20.34 | 21.00 | 20.16 | 0.67 | 20.08 |
Maximum of Months | 427.00 | 23.07 | 243.67 | 23.86 | 243.67 | 23.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 485.83 | 20.83 | 192.33 | 20.64 | 186.50 | 20.51 |
February | 382.00 | 21.26 | 110.00 | 21.35 | 72.83 | 21.20 |
March | 400.83 | 21.69 | 61.50 | 21.88 | 17.67 | 21.82 |
April | 315.83 | 22.11 | 94.67 | 22.66 | 1.17 | 22.68 |
May | 290.67 | 22.45 | 127.00 | 23.04 | 2.33 | 23.06 |
June | 228.33 | 22.66 | 152.00 | 23.34 | 1.17 | 23.36 |
July | 153.50 | 22.96 | 269.83 | 23.84 | 6.50 | 23.88 |
August | 151.17 | 23.01 | 299.50 | 23.87 | 9.83 | 23.93 |
September | 222.33 | 22.66 | 222.00 | 23.52 | 7.33 | 23.58 |
October | 348.83 | 22.03 | 105.67 | 22.63 | 2.83 | 22.66 |
November | 441.17 | 21.38 | 78.67 | 21.49 | 47.83 | 21.40 |
December | 455.83 | 21.01 | 167.00 | 20.92 | 153.00 | 20.79 |
Annual Sum or Average | 3876.33 | 21.76 | 1880.17 | 22.27 | 509.00 | 22.13 |
Minimum of Months | 151.17 | 20.83 | 61.50 | 20.64 | 1.17 | 20.51 |
Maximum of Months | 485.83 | 23.01 | 299.50 | 23.87 | 186.50 | 23.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.60 | 212.83 | 20.42 | 212.83 | 20.32 |
February | 444.33 | 21.02 | 105.00 | 20.85 | 102.67 | 20.73 |
March | 484.50 | 21.56 | 29.83 | 21.56 | 20.33 | 21.51 |
April | 372.00 | 22.02 | 62.50 | 22.39 | 0.17 | 22.39 |
May | 313.67 | 22.56 | 122.17 | 23.09 | 8.67 | 23.17 |
June | 233.17 | 22.70 | 163.50 | 23.38 | 2.17 | 23.40 |
July | 127.67 | 23.18 | 303.00 | 24.09 | 10.83 | 24.16 |
August | 134.50 | 22.89 | 298.50 | 23.88 | 8.17 | 23.94 |
September | 270.00 | 22.49 | 159.17 | 23.21 | 5.17 | 23.25 |
October | 446.33 | 21.80 | 27.83 | 21.96 | 0.67 | 21.97 |
November | 480.67 | 21.17 | 56.17 | 21.12 | 52.17 | 21.06 |
December | 497.00 | 20.87 | 152.17 | 20.73 | 152.17 | 20.64 |
Annual Sum or Average | 4305.83 | 21.62 | 1692.67 | 22.02 | 576.00 | 21.89 |
Minimum of Months | 127.67 | 20.60 | 27.83 | 20.42 | 0.17 | 20.32 |
Maximum of Months | 502.00 | 23.18 | 303.00 | 24.09 | 212.83 | 24.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 373.50 | 19.89 | 373.50 | 19.83 |
February | 454.00 | 20.38 | 267.83 | 20.15 | 267.83 | 20.05 |
March | 514.00 | 21.06 | 171.67 | 20.82 | 171.67 | 20.68 |
April | 452.00 | 21.87 | 66.83 | 21.73 | 56.67 | 21.59 |
May | 347.83 | 22.41 | 54.33 | 22.56 | 8.00 | 22.52 |
June | 220.17 | 22.95 | 82.50 | 23.28 | 0.00 | 23.28 |
July | 138.17 | 23.15 | 228.67 | 23.77 | 0.00 | 23.77 |
August | 161.00 | 22.98 | 262.83 | 23.69 | 0.00 | 23.69 |
September | 337.50 | 22.52 | 59.83 | 22.75 | 0.00 | 22.75 |
October | 499.17 | 21.45 | 73.67 | 21.24 | 73.67 | 21.08 |
November | 489.00 | 20.57 | 219.50 | 20.31 | 219.50 | 20.18 |
December | 497.00 | 20.14 | 365.67 | 20.00 | 365.67 | 19.95 |
Annual Sum or Average | 4611.83 | 21.28 | 2226.83 | 21.24 | 1536.50 | 20.98 |
Minimum of Months | 138.17 | 20.04 | 54.33 | 19.89 | 0.00 | 19.83 |
Maximum of Months | 514.00 | 23.15 | 373.50 | 23.77 | 373.50 | 23.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.05 | 363.50 | 19.89 | 363.50 | 19.83 |
February | 454.00 | 20.41 | 241.83 | 20.20 | 241.83 | 20.10 |
March | 511.67 | 21.07 | 126.83 | 20.85 | 126.83 | 20.70 |
April | 385.33 | 21.72 | 70.83 | 21.78 | 36.33 | 21.66 |
May | 327.33 | 22.06 | 109.17 | 22.54 | 9.50 | 22.51 |
June | 211.00 | 22.53 | 202.33 | 23.41 | 2.50 | 23.43 |
July | 167.00 | 22.91 | 267.83 | 23.78 | 10.50 | 23.85 |
August | 170.00 | 22.77 | 285.50 | 23.69 | 10.50 | 23.76 |
September | 299.67 | 21.99 | 131.17 | 22.69 | 2.33 | 22.71 |
October | 476.17 | 21.35 | 60.83 | 21.21 | 58.33 | 21.08 |
November | 489.00 | 20.53 | 212.00 | 20.30 | 212.00 | 20.19 |
December | 497.00 | 20.16 | 351.00 | 20.01 | 351.00 | 19.95 |
Annual Sum or Average | 4490.17 | 21.15 | 2422.83 | 21.34 | 1425.17 | 21.10 |
Minimum of Months | 167.00 | 20.05 | 60.83 | 19.89 | 2.33 | 19.83 |
Maximum of Months | 511.67 | 22.91 | 363.50 | 23.78 | 363.50 | 23.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.50 | 20.30 | 296.17 | 20.06 | 295.00 | 19.95 |
February | 411.33 | 20.79 | 197.50 | 20.65 | 180.50 | 20.49 |
March | 434.00 | 21.22 | 137.00 | 21.14 | 108.83 | 20.96 |
April | 347.83 | 21.66 | 115.17 | 21.97 | 41.17 | 21.83 |
May | 327.17 | 22.03 | 115.00 | 22.58 | 7.83 | 22.57 |
June | 265.17 | 22.39 | 142.67 | 23.07 | 2.00 | 23.09 |
July | 191.17 | 22.75 | 256.33 | 23.65 | 8.33 | 23.71 |
August | 192.83 | 22.69 | 273.83 | 23.63 | 9.67 | 23.70 |
September | 256.17 | 22.17 | 196.83 | 23.12 | 6.33 | 23.17 |
October | 383.17 | 21.47 | 125.83 | 21.88 | 39.00 | 21.76 |
November | 457.33 | 20.80 | 176.67 | 20.71 | 154.50 | 20.55 |
December | 477.67 | 20.47 | 272.83 | 20.23 | 271.67 | 20.11 |
Annual Sum or Average | 4241.33 | 21.33 | 2305.83 | 21.64 | 1124.83 | 21.40 |
Minimum of Months | 191.17 | 20.30 | 115.00 | 20.06 | 2.00 | 19.95 |
Maximum of Months | 497.50 | 22.75 | 296.17 | 23.65 | 295.00 | 23.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.16 | 322.17 | 19.97 | 322.17 | 19.88 |
February | 451.50 | 20.61 | 215.00 | 20.38 | 214.17 | 20.27 |
March | 494.83 | 21.12 | 117.17 | 21.00 | 110.17 | 20.88 |
April | 394.17 | 21.60 | 88.00 | 21.82 | 35.17 | 21.72 |
May | 354.17 | 22.16 | 104.00 | 22.67 | 9.33 | 22.73 |
June | 275.33 | 22.43 | 149.17 | 23.10 | 2.33 | 23.13 |
July | 162.67 | 22.89 | 279.00 | 23.87 | 12.33 | 23.95 |
August | 194.67 | 22.68 | 261.17 | 23.62 | 8.33 | 23.68 |
September | 308.83 | 22.11 | 132.33 | 22.79 | 3.67 | 22.83 |
October | 465.83 | 21.36 | 56.33 | 21.36 | 39.33 | 21.27 |
November | 485.00 | 20.74 | 161.83 | 20.55 | 160.67 | 20.43 |
December | 497.00 | 20.39 | 292.83 | 20.22 | 292.83 | 20.14 |
Annual Sum or Average | 4586.00 | 21.27 | 2179.00 | 21.49 | 1210.50 | 21.28 |
Minimum of Months | 162.67 | 20.16 | 56.33 | 19.97 | 2.33 | 19.88 |
Maximum of Months | 502.00 | 22.89 | 322.17 | 23.87 | 322.17 | 23.95 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 2.50 | 27.00 | 454.00 | 27.00 | 2.50 | 27.00 |
March | 10.50 | 27.00 | 514.00 | 27.00 | 10.50 | 27.00 |
April | 127.50 | 27.00 | 485.00 | 27.00 | 127.50 | 27.00 |
May | 6.50 | 27.00 | 508.00 | 27.00 | 6.50 | 27.00 |
June | 41.67 | 27.00 | 496.00 | 27.00 | 41.67 | 27.00 |
July | 226.33 | 27.00 | 497.00 | 27.00 | 226.33 | 27.00 |
August | 357.00 | 27.00 | 514.00 | 27.00 | 357.00 | 27.00 |
September | 29.83 | 27.00 | 485.00 | 27.00 | 29.83 | 27.00 |
October | 13.83 | 27.00 | 502.00 | 27.00 | 13.83 | 27.00 |
November | 5.33 | 27.00 | 489.00 | 27.00 | 5.33 | 27.00 |
December | 8.17 | 27.00 | 497.00 | 27.00 | 8.17 | 27.00 |
Annual Sum or Average | 829.17 | 27.00 | 5943.00 | 27.00 | 829.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 357.00 | 27.00 | 514.00 | 27.00 | 357.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.33 | 24.99 | 441.33 | 26.94 | 0.00 | 26.94 |
February | 0.00 | 0.00 | 426.50 | 27.00 | 0.00 | 27.00 |
March | 0.67 | 27.00 | 514.00 | 27.00 | 0.67 | 27.00 |
April | 8.17 | 27.00 | 485.00 | 27.00 | 8.17 | 27.00 |
May | 0.17 | 27.00 | 508.00 | 27.00 | 0.17 | 27.00 |
June | 7.67 | 27.00 | 496.00 | 27.00 | 7.67 | 27.00 |
July | 35.50 | 27.00 | 497.00 | 27.00 | 35.50 | 27.00 |
August | 70.50 | 27.00 | 514.00 | 27.00 | 70.50 | 27.00 |
September | 11.17 | 27.00 | 485.00 | 27.00 | 11.17 | 27.00 |
October | 3.83 | 27.00 | 502.00 | 27.00 | 3.83 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 152.00 | 26.81 | 5854.83 | 27.00 | 137.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 426.50 | 26.94 | 0.00 | 26.94 |
Maximum of Months | 70.50 | 27.00 | 514.00 | 27.00 | 70.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.33 | 24.37 | 335.17 | 26.28 | 12.00 | 26.18 |
February | 26.00 | 27.00 | 358.67 | 27.00 | 0.00 | 27.00 |
March | 0.67 | 27.00 | 482.50 | 27.00 | 0.67 | 27.00 |
April | 10.33 | 27.00 | 485.00 | 27.00 | 10.33 | 27.00 |
May | 2.17 | 27.00 | 508.00 | 27.00 | 2.17 | 27.00 |
June | 20.17 | 27.00 | 496.00 | 27.00 | 20.17 | 27.00 |
July | 69.67 | 27.00 | 497.00 | 27.00 | 69.67 | 27.00 |
August | 92.17 | 27.00 | 514.00 | 27.00 | 92.17 | 27.00 |
September | 15.17 | 27.00 | 485.00 | 27.00 | 15.17 | 27.00 |
October | 3.50 | 27.00 | 502.00 | 27.00 | 3.50 | 27.00 |
November | 0.00 | 0.00 | 466.33 | 27.00 | 0.00 | 27.00 |
December | 5.83 | 27.00 | 416.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 344.00 | 26.25 | 5545.67 | 26.95 | 225.83 | 26.94 |
Minimum of Months | 0.00 | 0.00 | 335.17 | 26.28 | 0.00 | 26.18 |
Maximum of Months | 98.33 | 27.00 | 514.00 | 27.00 | 92.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 363.17 | 27.00 | 502.00 | 27.00 | 363.17 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.05 | 485.00 | 27.05 | 485.00 | 27.05 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.29 | 514.00 | 27.29 | 514.00 | 27.29 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5804.17 | 27.03 | 5943.00 | 27.03 | 5804.17 | 27.03 |
Minimum of Months | 363.17 | 27.00 | 454.00 | 27.00 | 363.17 | 27.00 |
Maximum of Months | 514.00 | 27.29 | 514.00 | 27.29 | 514.00 | 27.29 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 26.86510 | 0.77209 | 17.65563 |
February | 454.00000 | 27.00006 | 27.12278 | 0.83730 | 19.92910 |
March | 514.00000 | 27.00003 | 28.05840 | 0.91024 | 22.58057 |
April | 485.00000 | 27.00002 | 30.83287 | 0.99056 | 25.78673 |
May | 508.00000 | 27.00024 | 33.84386 | 0.25150 | 6.42949 |
June | 496.00000 | 27.00026 | 35.23087 | 0.32995 | 7.34594 |
July | 497.00000 | 27.00027 | 36.54364 | 0.40765 | 8.54544 |
August | 514.00000 | 27.00078 | 37.19334 | 0.45212 | 9.35775 |
September | 485.00000 | 27.00060 | 36.75422 | 0.28441 | 6.79632 |
October | 502.00000 | 27.00012 | 33.35043 | 0.92991 | 23.31873 |
November | 489.00000 | 27.00010 | 31.36219 | 0.92232 | 23.03319 |
December | 497.00000 | 27.00000 | 27.25927 | 0.90566 | 22.37550 |
Annual Sum or Average | 5943.00000 | 27.00021 | 32.06704 | 0.66436 | 16.04858 |
Minimum of Months | 454.00000 | 27.00000 | 26.86510 | 0.25150 | 6.42949 |
Maximum of Months | 514.00000 | 27.00078 | 37.19334 | 0.99056 | 25.78673 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.93727 | 27.10226 | 0.64032 | 13.89161 |
February | 454.00000 | 27.00006 | 27.12129 | 0.70707 | 15.72466 |
March | 514.00000 | 27.00003 | 28.03508 | 0.77406 | 17.75144 |
April | 485.00000 | 27.00002 | 30.81016 | 0.85052 | 20.39068 |
May | 508.00000 | 27.00022 | 33.86680 | 0.16030 | 5.70656 |
June | 496.00000 | 27.00024 | 35.22683 | 0.21984 | 6.14137 |
July | 497.00000 | 27.00029 | 36.54174 | 0.28933 | 6.88000 |
August | 514.00000 | 27.00069 | 37.19460 | 0.31145 | 7.18809 |
September | 485.00000 | 27.00056 | 36.86980 | 0.19828 | 5.98010 |
October | 502.00000 | 27.00011 | 33.34469 | 0.82188 | 19.33720 |
November | 489.00000 | 27.00009 | 31.34693 | 0.76951 | 17.57053 |
December | 497.00000 | 27.00000 | 27.24490 | 0.71911 | 15.97564 |
Annual Sum or Average | 5943.00000 | 26.99490 | 32.09115 | 0.53670 | 12.67456 |
Minimum of Months | 454.00000 | 26.93727 | 27.10226 | 0.16030 | 5.70656 |
Maximum of Months | 514.00000 | 27.00069 | 37.19460 | 0.85052 | 20.39068 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.42718 | 27.56751 | 0.47341 | 11.76001 |
February | 454.00000 | 27.00022 | 27.13460 | 0.63553 | 13.85006 |
March | 514.00000 | 27.00003 | 28.04705 | 0.71401 | 15.95833 |
April | 485.00000 | 27.00002 | 30.82060 | 0.80854 | 19.02146 |
May | 508.00000 | 27.00022 | 33.89655 | 0.12501 | 5.65890 |
June | 496.00000 | 27.00024 | 35.24253 | 0.20516 | 6.11574 |
July | 497.00000 | 27.00029 | 36.55194 | 0.28290 | 6.90828 |
August | 514.00000 | 27.00061 | 37.20538 | 0.29963 | 7.15289 |
September | 485.00000 | 27.00053 | 36.95907 | 0.16058 | 5.83430 |
October | 502.00000 | 27.00011 | 33.37394 | 0.76709 | 17.56451 |
November | 489.00000 | 27.00009 | 31.36634 | 0.69691 | 15.39670 |
December | 497.00000 | 27.00000 | 27.25106 | 0.63661 | 13.69836 |
Annual Sum or Average | 5943.00000 | 26.95181 | 32.15086 | 0.48214 | 11.54664 |
Minimum of Months | 454.00000 | 26.42718 | 27.13460 | 0.12501 | 5.65890 |
Maximum of Months | 514.00000 | 27.00061 | 37.20538 | 0.80854 | 19.02146 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00056 | 30.99902 | 1.04565 | 28.09864 |
February | 454.00000 | 27.00256 | 31.59576 | 1.22189 | 36.34021 |
March | 514.00000 | 27.00228 | 31.47255 | 1.38024 | 44.46678 |
April | 485.00000 | 27.05446 | 32.43553 | 1.53930 | 53.03060 |
May | 508.00000 | 27.00045 | 34.24456 | 0.53431 | 11.04307 |
June | 496.00000 | 27.00029 | 35.36655 | 0.77034 | 17.53135 |
July | 497.00000 | 27.00026 | 36.50863 | 0.98884 | 25.67427 |
August | 514.00000 | 27.28961 | 36.86388 | 1.26796 | 38.85394 |
September | 485.00000 | 27.00092 | 36.26062 | 0.57760 | 12.04064 |
October | 502.00000 | 27.00021 | 33.76470 | 1.27443 | 38.97183 |
November | 489.00000 | 27.00088 | 32.63017 | 1.39960 | 45.49725 |
December | 497.00000 | 27.00246 | 30.81867 | 1.50603 | 51.22921 |
Annual Sum or Average | 5943.00000 | 27.03039 | 33.59487 | 1.12488 | 33.54011 |
Minimum of Months | 454.00000 | 27.00021 | 30.81867 | 0.53431 | 11.04307 |
Maximum of Months | 514.00000 | 27.28961 | 36.86388 | 1.53930 | 53.03060 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.43714 | 26.81095 | 0.36752 | 8.15952 |
February | 454.00000 | 24.43720 | 28.10251 | 0.38386 | 8.44925 |
March | 514.00000 | 24.39766 | 27.96882 | 0.38693 | 8.45942 |
April | 485.00000 | 24.50606 | 31.57716 | 0.43983 | 9.57677 |
May | 508.00000 | 24.48479 | 36.28105 | -0.3849 | 9.03304 |
June | 496.00000 | 24.45868 | 38.40884 | -0.3671 | 8.65706 |
July | 497.00000 | 24.60049 | 43.75842 | -0.2839 | 7.86513 |
August | 514.00000 | 24.47037 | 47.69522 | -0.2859 | 7.60005 |
September | 485.00000 | 24.53202 | 43.88230 | -0.3064 | 8.07495 |
October | 502.00000 | 24.55321 | 34.82754 | 0.47637 | 10.34558 |
November | 489.00000 | 24.55775 | 32.94456 | 0.45974 | 10.03825 |
December | 497.00000 | 24.51763 | 27.52138 | 0.40507 | 8.92689 |
Annual Sum or Average | 5943.00000 | 24.49596 | 35.03411 | 0.10465 | 8.76295 |
Minimum of Months | 454.00000 | 24.39766 | 26.81095 | -0.3849 | 7.60005 |
Maximum of Months | 514.00000 | 24.60049 | 47.69522 | 0.47637 | 10.34558 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.11457 | 31.35876 | 0.31545 | 7.58186 |
February | 454.00000 | 24.23687 | 30.02640 | 0.34815 | 7.79384 |
March | 514.00000 | 24.31667 | 29.33362 | 0.38436 | 8.34921 |
April | 485.00000 | 24.35880 | 32.47379 | 0.43079 | 9.20459 |
May | 508.00000 | 24.30881 | 37.58705 | -0.4181 | 9.17199 |
June | 496.00000 | 24.28778 | 39.66661 | -0.3884 | 8.57893 |
July | 497.00000 | 24.32803 | 44.52430 | -0.3320 | 7.71768 |
August | 514.00000 | 24.25517 | 48.10901 | -0.3167 | 7.40359 |
September | 485.00000 | 24.36482 | 45.20811 | -0.3425 | 8.12026 |
October | 502.00000 | 24.39332 | 36.32129 | 0.45041 | 9.62716 |
November | 489.00000 | 24.40426 | 34.67016 | 0.43373 | 9.31004 |
December | 497.00000 | 24.37151 | 29.61778 | 0.38512 | 8.41098 |
Annual Sum or Average | 5943.00000 | 24.31169 | 36.62456 | 0.07633 | 8.44017 |
Minimum of Months | 454.00000 | 24.11457 | 29.33362 | -0.4181 | 7.40359 |
Maximum of Months | 514.00000 | 24.40426 | 48.10901 | 0.45041 | 9.62716 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.88424 | 34.08078 | -0.0125 | 6.06827 |
February | 454.00000 | 23.37861 | 32.64086 | 0.11608 | 6.00764 |
March | 514.00000 | 23.81228 | 31.43221 | 0.23272 | 6.40138 |
April | 485.00000 | 23.99723 | 34.36845 | 0.30863 | 7.28695 |
May | 508.00000 | 24.09944 | 38.47393 | -0.5189 | 11.02342 |
June | 496.00000 | 24.15336 | 40.38415 | -0.4726 | 9.96616 |
July | 497.00000 | 24.23895 | 45.55566 | -0.4053 | 8.84468 |
August | 514.00000 | 24.18903 | 48.97163 | -0.3893 | 8.54284 |
September | 485.00000 | 24.19238 | 46.06004 | -0.4295 | 9.31607 |
October | 502.00000 | 23.96712 | 38.11718 | 0.32208 | 7.47712 |
November | 489.00000 | 23.67583 | 37.75302 | 0.22805 | 6.50601 |
December | 497.00000 | 23.28677 | 33.10469 | 0.09150 | 5.70226 |
Annual Sum or Average | 5943.00000 | 23.82606 | 38.45338 | -0.0797 | 7.77645 |
Minimum of Months | 454.00000 | 22.88424 | 31.43221 | -0.5189 | 5.70226 |
Maximum of Months | 514.00000 | 24.23895 | 48.97163 | 0.32208 | 11.02342 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.36244 | 34.46465 | -0.4013 | 11.92726 |
February | 454.00000 | 21.93818 | 34.78832 | -0.2449 | 9.40712 |
March | 514.00000 | 22.82322 | 33.89056 | -0.0192 | 6.40225 |
April | 485.00000 | 23.37104 | 36.11396 | 0.14982 | 6.49094 |
May | 508.00000 | 23.77586 | 39.51951 | -0.6367 | 14.48657 |
June | 496.00000 | 24.03541 | 40.74699 | -0.5139 | 10.97354 |
July | 497.00000 | 24.15808 | 45.80083 | -0.4277 | 9.22242 |
August | 514.00000 | 24.08461 | 49.32818 | -0.4231 | 9.19504 |
September | 485.00000 | 23.86913 | 47.38798 | -0.5508 | 12.12800 |
October | 502.00000 | 23.12727 | 40.86726 | 0.10686 | 6.31908 |
November | 489.00000 | 22.33393 | 41.46776 | -0.1079 | 6.94922 |
December | 497.00000 | 21.65361 | 36.03162 | -0.3186 | 9.03659 |
Annual Sum or Average | 5943.00000 | 23.05322 | 40.06702 | -0.2832 | 9.38123 |
Minimum of Months | 454.00000 | 21.36244 | 33.89056 | -0.6367 | 6.31908 |
Maximum of Months | 514.00000 | 24.15808 | 49.32818 | 0.14982 | 14.48657 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.18347 | 31.15063 | -0.1815 | 6.57006 |
February | 454.00000 | 22.69376 | 31.13698 | -0.0503 | 6.23338 |
March | 514.00000 | 23.42398 | 30.43603 | 0.13122 | 5.89367 |
April | 485.00000 | 23.85915 | 32.79138 | 0.27633 | 7.01503 |
May | 508.00000 | 23.97726 | 37.42215 | -0.5542 | 12.15251 |
June | 496.00000 | 24.15355 | 39.24683 | -0.4499 | 9.57946 |
July | 497.00000 | 24.25326 | 43.89212 | -0.3633 | 8.07479 |
August | 514.00000 | 24.17780 | 47.64798 | -0.3599 | 8.00168 |
September | 485.00000 | 24.00837 | 45.41884 | -0.5024 | 10.95354 |
October | 502.00000 | 23.62456 | 37.44793 | 0.22885 | 6.57649 |
November | 489.00000 | 23.23974 | 36.22435 | 0.11446 | 5.99239 |
December | 497.00000 | 22.79858 | 31.33378 | -0.0300 | 5.48862 |
Annual Sum or Average | 5943.00000 | 23.53883 | 37.05497 | -0.1465 | 7.72046 |
Minimum of Months | 454.00000 | 22.18347 | 30.43603 | -0.5542 | 5.48862 |
Maximum of Months | 514.00000 | 24.25326 | 47.64798 | 0.27633 | 12.15251 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.46839 | 31.41394 | -0.3221 | 7.61360 |
February | 454.00000 | 21.94975 | 31.62530 | -0.1877 | 6.82654 |
March | 514.00000 | 22.56009 | 31.17243 | -0.0214 | 5.92450 |
April | 485.00000 | 23.24384 | 33.54532 | 0.19127 | 6.90558 |
May | 508.00000 | 23.56597 | 37.91618 | -0.6110 | 15.16883 |
June | 496.00000 | 23.84717 | 39.67230 | -0.4645 | 11.24974 |
July | 497.00000 | 23.88760 | 44.61811 | -0.4067 | 10.14190 |
August | 514.00000 | 23.79246 | 48.54486 | -0.4044 | 10.17760 |
September | 485.00000 | 23.53106 | 46.21612 | -0.5722 | 14.37162 |
October | 502.00000 | 22.86419 | 38.38834 | 0.10119 | 6.42675 |
November | 489.00000 | 22.10260 | 37.56598 | -0.1116 | 6.15489 |
December | 497.00000 | 21.66712 | 32.27373 | -0.2615 | 6.85055 |
Annual Sum or Average | 5943.00000 | 22.88066 | 37.78925 | -0.2570 | 8.99950 |
Minimum of Months | 454.00000 | 21.46839 | 31.17243 | -0.6110 | 5.92450 |
Maximum of Months | 514.00000 | 23.88760 | 48.54486 | 0.19127 | 15.16883 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.66331 | 31.22140 | -0.2788 | 8.12102 |
February | 454.00000 | 22.40832 | 30.87418 | -0.0716 | 7.55315 |
March | 514.00000 | 22.91798 | 30.47014 | 0.07639 | 6.68470 |
April | 485.00000 | 23.44444 | 33.06368 | 0.24379 | 7.66421 |
May | 508.00000 | 23.59792 | 37.81214 | -0.6072 | 15.19072 |
June | 496.00000 | 23.83416 | 39.76307 | -0.4973 | 11.71354 |
July | 497.00000 | 24.02280 | 44.23080 | -0.3682 | 9.29567 |
August | 514.00000 | 23.96707 | 47.97618 | -0.3379 | 8.93714 |
September | 485.00000 | 23.79616 | 45.38800 | -0.4534 | 12.10877 |
October | 502.00000 | 23.28406 | 37.39284 | 0.21932 | 7.87856 |
November | 489.00000 | 22.49741 | 36.81468 | -0.0181 | 6.86669 |
December | 497.00000 | 22.09507 | 31.60389 | -0.1559 | 7.13453 |
Annual Sum or Average | 5943.00000 | 23.13291 | 37.26316 | -0.1890 | 9.10834 |
Minimum of Months | 454.00000 | 21.66331 | 30.47014 | -0.6072 | 6.68470 |
Maximum of Months | 514.00000 | 24.02280 | 47.97618 | 0.24379 | 15.19072 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.97726 | 30.37501 | -0.1747 | 6.22685 |
February | 454.00000 | 22.92250 | 29.70273 | 0.07156 | 6.44853 |
March | 514.00000 | 23.78624 | 28.74500 | 0.30355 | 7.71394 |
April | 485.00000 | 24.33048 | 31.20651 | 0.50269 | 11.22876 |
May | 508.00000 | 23.97121 | 36.87912 | -0.4263 | 11.19546 |
June | 496.00000 | 24.24886 | 38.60554 | -0.2731 | 7.88493 |
July | 497.00000 | 24.50908 | 42.82855 | -0.0872 | 6.81149 |
August | 514.00000 | 24.41027 | 46.57458 | -0.0775 | 6.45660 |
September | 485.00000 | 24.02293 | 44.72877 | -0.3589 | 9.96880 |
October | 502.00000 | 23.75299 | 36.23784 | 0.33985 | 8.47461 |
November | 489.00000 | 23.58294 | 34.35052 | 0.26389 | 7.52755 |
December | 497.00000 | 23.53508 | 28.84965 | 0.21115 | 6.66145 |
Annual Sum or Average | 5943.00000 | 23.75949 | 35.80212 | 0.02355 | 8.05107 |
Minimum of Months | 454.00000 | 21.97726 | 28.74500 | -0.4263 | 6.22685 |
Maximum of Months | 514.00000 | 24.50908 | 46.57458 | 0.50269 | 11.22876 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.52197 | 34.05111 | -0.6176 | 14.95011 |
February | 454.00000 | 21.00173 | 34.17853 | -0.4734 | 11.90597 |
March | 514.00000 | 21.91889 | 33.77282 | -0.2339 | 7.31273 |
April | 485.00000 | 22.76138 | 35.69594 | -0.0011 | 6.30674 |
May | 508.00000 | 23.45983 | 38.93625 | -0.7491 | 18.29536 |
June | 496.00000 | 23.85287 | 40.35510 | -0.5837 | 12.79436 |
July | 497.00000 | 24.03236 | 44.71869 | -0.4767 | 10.19662 |
August | 514.00000 | 23.95918 | 48.71843 | -0.4775 | 10.37770 |
September | 485.00000 | 23.54423 | 47.03234 | -0.6801 | 15.84144 |
October | 502.00000 | 22.38884 | 40.79548 | -0.0717 | 6.20542 |
November | 489.00000 | 21.39781 | 40.37925 | -0.3336 | 8.61627 |
December | 497.00000 | 20.77926 | 35.21482 | -0.5370 | 11.91343 |
Annual Sum or Average | 5943.00000 | 22.48007 | 39.52245 | -0.4365 | 11.22366 |
Minimum of Months | 454.00000 | 20.52197 | 33.77282 | -0.7491 | 6.20542 |
Maximum of Months | 514.00000 | 24.03236 | 48.71843 | -0.0011 | 18.29536 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.34405 | 32.75998 | -0.6598 | 15.88486 |
February | 385.00000 | 20.85655 | 32.90579 | -0.4955 | 11.46524 |
March | 433.00000 | 21.49555 | 33.05267 | -0.2986 | 7.85981 |
April | 410.00000 | 22.50354 | 34.80148 | -0.0066 | 6.94617 |
May | 430.00000 | 22.97598 | 38.94264 | -0.8255 | 22.92091 |
June | 418.00000 | 23.53008 | 40.37004 | -0.5909 | 15.32237 |
July | 422.00000 | 23.76759 | 44.67005 | -0.4758 | 12.48621 |
August | 433.00000 | 23.69190 | 48.64287 | -0.4675 | 12.38847 |
September | 410.00000 | 23.02562 | 47.32768 | -0.7609 | 20.89172 |
October | 427.00000 | 21.91602 | 40.49054 | -0.1438 | 6.85910 |
November | 417.00000 | 21.00844 | 39.68956 | -0.4139 | 9.40849 |
December | 422.00000 | 20.60430 | 33.99980 | -0.5768 | 12.67990 |
Annual Sum or Average | 5034.00000 | 22.15110 | 39.00736 | -0.4766 | 12.93425 |
Minimum of Months | 385.00000 | 20.34405 | 32.75998 | -0.8255 | 6.85910 |
Maximum of Months | 433.00000 | 23.76759 | 48.64287 | -0.0066 | 22.92091 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.95203 | 32.44998 | -0.4837 | 12.37392 |
February | 454.00000 | 21.74407 | 32.10612 | -0.2462 | 9.47895 |
March | 514.00000 | 22.23409 | 32.12904 | -0.0926 | 7.65415 |
April | 485.00000 | 22.85988 | 34.47468 | 0.09383 | 7.66770 |
May | 508.00000 | 23.17495 | 38.85518 | -0.7526 | 20.46764 |
June | 496.00000 | 23.45632 | 40.79521 | -0.6362 | 16.00434 |
July | 497.00000 | 23.79515 | 44.93017 | -0.4649 | 11.88017 |
August | 514.00000 | 23.76857 | 48.77043 | -0.4268 | 11.43988 |
September | 485.00000 | 23.49660 | 46.22576 | -0.5532 | 15.50292 |
October | 502.00000 | 22.73913 | 38.83594 | 0.08675 | 8.01793 |
November | 489.00000 | 21.68941 | 38.82313 | -0.2279 | 8.42577 |
December | 497.00000 | 21.28136 | 33.32843 | -0.3831 | 10.39483 |
Annual Sum or Average | 5943.00000 | 22.60632 | 38.52190 | -0.3418 | 11.63029 |
Minimum of Months | 454.00000 | 20.95203 | 32.10612 | -0.7526 | 7.65415 |
Maximum of Months | 514.00000 | 23.79515 | 48.77043 | 0.09383 | 20.46764 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.60126 | 32.81107 | -0.5772 | 13.30266 |
February | 454.00000 | 21.08195 | 33.06308 | -0.4199 | 10.37422 |
March | 514.00000 | 21.70368 | 32.96753 | -0.2330 | 7.42266 |
April | 485.00000 | 22.54871 | 35.08560 | 0.01849 | 7.14072 |
May | 508.00000 | 23.13126 | 38.93042 | -0.7476 | 20.61796 |
June | 496.00000 | 23.44126 | 40.77013 | -0.6092 | 15.34982 |
July | 497.00000 | 23.95717 | 44.45914 | -0.3682 | 10.49673 |
August | 514.00000 | 23.77222 | 48.80511 | -0.4126 | 11.18867 |
September | 485.00000 | 23.23875 | 46.97864 | -0.6620 | 17.71143 |
October | 502.00000 | 22.06849 | 40.32696 | -0.0924 | 6.63790 |
November | 489.00000 | 21.22229 | 39.67877 | -0.3441 | 8.36196 |
December | 497.00000 | 20.86532 | 33.90805 | -0.4913 | 10.67210 |
Annual Sum or Average | 5943.00000 | 22.31280 | 39.02209 | -0.4119 | 11.61651 |
Minimum of Months | 454.00000 | 20.60126 | 32.81107 | -0.7476 | 6.63790 |
Maximum of Months | 514.00000 | 23.95717 | 48.80511 | 0.01849 | 20.61796 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.03598 | 34.83307 | -0.7899 | 21.16907 |
February | 454.00000 | 20.37814 | 35.28549 | -0.6706 | 17.58474 |
March | 514.00000 | 21.05574 | 35.32119 | -0.4636 | 11.27351 |
April | 485.00000 | 22.00831 | 37.20624 | -0.1883 | 7.86644 |
May | 508.00000 | 22.91519 | 40.22137 | -0.9330 | 26.15137 |
June | 496.00000 | 23.56172 | 41.07717 | -0.6791 | 16.21782 |
July | 497.00000 | 23.83203 | 45.19276 | -0.5387 | 12.14171 |
August | 514.00000 | 23.73500 | 49.36917 | -0.5493 | 12.65640 |
September | 485.00000 | 22.96171 | 48.69877 | -0.8768 | 23.48821 |
October | 502.00000 | 21.46068 | 42.98808 | -0.3073 | 8.52965 |
November | 489.00000 | 20.56702 | 42.20147 | -0.5715 | 14.16585 |
December | 497.00000 | 20.13549 | 36.55295 | -0.7487 | 19.12293 |
Annual Sum or Average | 5943.00000 | 21.90014 | 40.77932 | -0.6096 | 15.84953 |
Minimum of Months | 454.00000 | 20.03598 | 34.83307 | -0.9330 | 7.86644 |
Maximum of Months | 514.00000 | 23.83203 | 49.36917 | -0.1883 | 26.15137 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.04517 | 33.99353 | -0.7833 | 20.86670 |
February | 454.00000 | 20.41063 | 34.45932 | -0.6429 | 16.19968 |
March | 514.00000 | 21.08123 | 34.43680 | -0.4243 | 10.50993 |
April | 485.00000 | 22.18448 | 36.04794 | -0.0909 | 7.81030 |
May | 508.00000 | 22.77694 | 39.85730 | -0.8927 | 26.04563 |
June | 496.00000 | 23.46433 | 40.64524 | -0.6023 | 16.01571 |
July | 497.00000 | 23.69588 | 45.14045 | -0.4800 | 12.88080 |
August | 514.00000 | 23.61146 | 49.19678 | -0.4753 | 12.93843 |
September | 485.00000 | 22.78682 | 48.38888 | -0.8417 | 24.45395 |
October | 502.00000 | 21.48034 | 42.02363 | -0.2695 | 8.34289 |
November | 489.00000 | 20.52637 | 41.44811 | -0.5722 | 13.84190 |
December | 497.00000 | 20.15779 | 35.66316 | -0.7379 | 18.70832 |
Annual Sum or Average | 5943.00000 | 21.86388 | 40.14466 | -0.5675 | 15.70956 |
Minimum of Months | 454.00000 | 20.04517 | 33.99353 | -0.8927 | 7.81030 |
Maximum of Months | 514.00000 | 23.69588 | 49.19678 | -0.0909 | 26.04563 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.33764 | 33.50514 | -0.6780 | 18.08439 |
February | 454.00000 | 21.10493 | 33.25500 | -0.4428 | 13.25576 |
March | 514.00000 | 21.65465 | 33.38980 | -0.2629 | 9.95402 |
April | 485.00000 | 22.36671 | 35.62080 | -0.0400 | 8.46142 |
May | 508.00000 | 22.77423 | 39.83597 | -0.8946 | 26.54258 |
June | 496.00000 | 23.18843 | 41.41083 | -0.7227 | 19.51631 |
July | 497.00000 | 23.60450 | 45.37804 | -0.5212 | 14.04432 |
August | 514.00000 | 23.55915 | 49.36758 | -0.4905 | 13.74184 |
September | 485.00000 | 23.11077 | 47.37137 | -0.6898 | 20.79340 |
October | 502.00000 | 22.14356 | 40.42567 | -0.0799 | 8.74057 |
November | 489.00000 | 21.04025 | 40.31872 | -0.4281 | 11.95828 |
December | 497.00000 | 20.60761 | 34.84531 | -0.5965 | 15.97448 |
Annual Sum or Average | 5943.00000 | 22.13302 | 39.60337 | -0.4881 | 15.10738 |
Minimum of Months | 454.00000 | 20.33764 | 33.25500 | -0.8946 | 8.46142 |
Maximum of Months | 514.00000 | 23.60450 | 49.36758 | -0.0400 | 26.54258 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.15573 | 33.67683 | -0.7320 | 19.08024 |
February | 454.00000 | 20.62651 | 33.94529 | -0.5715 | 14.57909 |
March | 514.00000 | 21.23018 | 34.00060 | -0.3770 | 9.77947 |
April | 485.00000 | 22.09138 | 36.14563 | -0.1050 | 8.03191 |
May | 508.00000 | 22.74056 | 39.86219 | -0.8839 | 26.36079 |
June | 496.00000 | 23.17595 | 41.37488 | -0.6941 | 18.66529 |
July | 497.00000 | 23.76253 | 44.90720 | -0.4251 | 12.35762 |
August | 514.00000 | 23.55049 | 49.42832 | -0.4802 | 13.46904 |
September | 485.00000 | 22.84059 | 48.14714 | -0.8003 | 23.10991 |
October | 502.00000 | 21.56072 | 41.70933 | -0.2376 | 7.90468 |
November | 489.00000 | 20.76771 | 40.77564 | -0.4970 | 11.75040 |
December | 497.00000 | 20.38785 | 35.03613 | -0.6566 | 15.82157 |
Annual Sum or Average | 5943.00000 | 21.91839 | 39.95668 | -0.5384 | 15.07978 |
Minimum of Months | 454.00000 | 20.15573 | 33.67683 | -0.8839 | 7.90468 |
Maximum of Months | 514.00000 | 23.76253 | 49.42832 | -0.1050 | 26.36079 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.245634E+09 | 2549.80 | 09-JAN-05:17 | 26.81 | 0.111852E+10 | 0.00 | 0.136415E+10 | 0.16 | 4.56 | 07-JAN-06:50 | 0.00 | 0.00 |
February | 0.142522E+10 | 66264.48 | 27-FEB-15:00 | 34.76 | 0.819586E+10 | 0.00 | 0.962108E+10 | 0.25 | 7.11 | 27-FEB-15:00 | 0.00 | 0.00 |
March | 0.230324E+10 | 51890.90 | 18-MAR-16:00 | 51.61 | 0.114467E+11 | 0.00 | 0.137500E+11 | 0.32 | 6.31 | 18-MAR-16:00 | 0.00 | 0.00 |
April | 0.128548E+11 | 91853.14 | 27-APR-14:40 | 114.58 | 0.785191E+11 | 0.00 | 0.913739E+11 | 0.84 | 7.44 | 27-APR-11:50 | 0.00 | 0.00 |
May | 0.263593E+11 | 86680.13 | 04-MAY-13:50 | 198.18 | 0.159999E+12 | 0.00 | 0.186358E+12 | 1.45 | 7.43 | 04-MAY-13:30 | 0.00 | 0.00 |
June | 0.469340E+11 | 89513.11 | 28-JUN-15:00 | 305.63 | 0.291730E+12 | 0.00 | 0.338664E+12 | 2.40 | 7.47 | 21-JUN-13:50 | 0.00 | 0.00 |
July | 0.728888E+11 | 112779.03 | 31-JUL-16:00 | 442.40 | 0.477515E+12 | 0.00 | 0.550404E+12 | 3.50 | 7.47 | 19-JUL-13:30 | 0.00 | 0.00 |
August | 0.863285E+11 | 119106.98 | 29-AUG-14:30 | 493.82 | 0.576089E+12 | 0.00 | 0.662417E+12 | 3.95 | 7.49 | 30-AUG-09:00 | 0.00 | 0.00 |
September | 0.381937E+11 | 89791.38 | 14-SEP-13:10 | 263.39 | 0.238232E+12 | 0.00 | 0.276426E+12 | 2.04 | 7.49 | 08-SEP-14:40 | 0.00 | 0.00 |
October | 0.787845E+10 | 74223.16 | 04-OCT-11:40 | 89.09 | 0.441571E+11 | 0.00 | 0.520355E+11 | 0.60 | 7.37 | 04-OCT-11:40 | 0.00 | 0.00 |
November | 0.172607E+10 | 60512.27 | 04-NOV-14:00 | 55.53 | 0.963863E+10 | 0.00 | 0.113647E+11 | 0.36 | 6.80 | 04-NOV-14:00 | 0.00 | 0.00 |
December | 0.315582E+09 | 7861.20 | 28-DEC-06:03 | 33.80 | 0.143710E+10 | 0.00 | 0.175268E+10 | 0.21 | 4.56 | 13-DEC-10:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.297453E+12 | 2109.59 | 0.189808E+13 | 0.00 | 0.219553E+13 | 1.35 | 0.00 | 0.00 | ||||
Minimum of Months | 0.245634E+09 | 2549.80 | 26.81 | 0.111852E+10 | 0.00 | 0.136415E+10 | 0.16 | 4.56 | 0.00 | 0.00 | ||
Maximum of Months | 0.863285E+11 | 119106.98 | 493.82 | 0.576089E+12 | 0.00 | 0.662417E+12 | 3.95 | 7.49 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.238581E+10 | 91853.14 | 27-APR-14:40 | 8.00 | 0.172972E+11 | 0.00 | 0.196830E+11 | 0.08 | 7.44 | 27-APR-11:50 | 0.00 | 0.00 |
May | 0.303467E+10 | 86680.13 | 04-MAY-13:50 | 10.67 | 0.220535E+11 | 0.00 | 0.250882E+11 | 0.10 | 7.43 | 04-MAY-13:30 | 0.00 | 0.00 |
June | 0.589222E+10 | 89513.11 | 28-JUN-15:00 | 20.17 | 0.429744E+11 | 0.00 | 0.488666E+11 | 0.20 | 7.47 | 21-JUN-13:50 | 0.00 | 0.00 |
July | 0.143357E+11 | 112779.03 | 31-JUL-16:00 | 46.89 | 0.104253E+12 | 0.00 | 0.118589E+12 | 0.46 | 7.47 | 19-JUL-13:30 | 0.00 | 0.00 |
August | 0.308109E+11 | 119106.98 | 29-AUG-14:30 | 95.50 | 0.223872E+12 | 0.00 | 0.254683E+12 | 0.93 | 7.44 | 09-AUG-09:50 | 0.00 | 0.00 |
September | 0.653218E+10 | 89791.38 | 14-SEP-13:10 | 22.33 | 0.476947E+11 | 0.00 | 0.542268E+11 | 0.23 | 7.49 | 08-SEP-14:40 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.629915E+11 | 203.56 | 0.458145E+12 | 0.00 | 0.521136E+12 | 0.17 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.308109E+11 | 119106.98 | 95.50 | 0.223872E+12 | 0.00 | 0.254683E+12 | 0.93 | 7.49 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.122508E+11 | 744.00 | 23085.92 | 11-JAN-15:00 | 178798.48 | 11-JAN-15:00 | 21.66 | 18.33 | 14.17 |
February | 0.282890E+11 | 672.00 | 49248.27 | 27-FEB-11:40 | 343612.79 | 27-FEB-16:20 | 24.62 | 18.36 | 14.17 |
March | 0.652114E+11 | 744.00 | 49248.27 | 08-MAR-10:30 | 588880.69 | 31-MAR-24:00 | 27.62 | 18.42 | 14.17 |
April | 0.973468E+11 | 720.00 | 49248.27 | 01-APR-08:50 | 669063.19 | 27-APR-18:10 | 31.37 | 19.28 | 14.17 |
May | 0.541104E+11 | 744.00 | 49248.27 | 02-MAY-12:50 | 323551.80 | 31-MAY-23:30 | 22.69 | 18.92 | 14.17 |
June | 0.102729E+12 | 720.00 | 49248.27 | 01-JUN-11:00 | 467609.90 | 30-JUN-24:00 | 26.66 | 19.96 | 14.17 |
July | 0.128198E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 627732.06 | 31-JUL-23:32 | 31.84 | 22.14 | 14.17 |
August | 0.131173E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 690140.60 | 10-AUG-19:10 | 37.01 | 24.40 | 14.17 |
September | 0.733347E+11 | 720.00 | 49248.27 | 01-SEP-08:50 | 317414.15 | 30-SEP-24:00 | 23.00 | 19.15 | 14.17 |
October | 0.667573E+11 | 744.00 | 49248.27 | 01-OCT-03:50 | 448445.25 | 31-OCT-24:00 | 25.00 | 18.52 | 14.17 |
November | 0.617670E+11 | 720.00 | 49248.27 | 02-NOV-13:00 | 494145.64 | 04-NOV-17:03 | 27.55 | 18.41 | 14.17 |
December | 0.638876E+11 | 744.00 | 49248.27 | 14-DEC-11:50 | 600405.77 | 10-DEC-15:48 | 30.15 | 18.33 | 14.17 |
Annual Sum or Average | 0.885054E+12 | 8760.00 | 27.46 | 19.53 | 14.17 | ||||
Minimum of Months | 0.122508E+11 | 672.00 | 23085.92 | 178798.48 | 21.66 | 18.33 | 14.17 | ||
Maximum of Months | 0.131173E+12 | 744.00 | 49248.27 | 690140.60 | 37.01 | 24.40 | 14.17 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 211677.19 | 07-JAN-05:52 | 20.89 | 20.89 | 0.25 |
February | 6408154.83 | 6.00 | 583.04 | 27-FEB-15:10 | 548674.42 | 27-FEB-15:10 | 21.06 | 21.04 | 0.98 |
March | 5623322.85 | 12.40 | 298.54 | 18-MAR-14:20 | 392496.20 | 18-MAR-16:00 | 21.04 | 21.02 | 1.76 |
April | 0.336427E+09 | 60.13 | 15735.24 | 27-APR-12:30 | 1044464.10 | 26-APR-14:30 | 21.23 | 21.05 | 6.07 |
May | 0.476175E+09 | 137.30 | 15735.24 | 05-MAY-12:20 | 1022542.72 | 04-MAY-13:20 | 21.49 | 21.14 | 12.43 |
June | 0.816387E+09 | 239.66 | 15735.24 | 21-JUN-15:30 | 1038838.30 | 28-JUN-14:30 | 21.89 | 21.21 | 21.13 |
July | 0.398870E+10 | 334.51 | 15735.24 | 07-JUL-11:40 | 1045660.09 | 06-JUL-15:40 | 22.24 | 21.18 | 28.87 |
August | 0.704227E+10 | 376.01 | 15735.24 | 07-AUG-10:00 | 1029466.33 | 21-AUG-15:30 | 22.48 | 21.24 | 32.35 |
September | 0.165172E+10 | 199.29 | 15735.24 | 11-SEP-15:50 | 1018799.67 | 08-SEP-14:30 | 21.75 | 21.20 | 18.13 |
October | 37988270.03 | 42.98 | 1234.92 | 04-OCT-15:20 | 944028.31 | 04-OCT-15:00 | 21.16 | 21.06 | 4.63 |
November | 24373156.40 | 7.11 | 1461.01 | 04-NOV-14:00 | 485706.24 | 04-NOV-14:00 | 21.04 | 21.02 | 1.12 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 207914.05 | 26-DEC-05:43 | 21.03 | 21.02 | 0.31 |
Annual Sum or Average | 0.143861E+11 | 1415.39 | 21.44 | 21.09 | 10.74 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 207914.05 | 20.89 | 20.89 | 0.25 | ||
Maximum of Months | 0.704227E+10 | 376.01 | 15735.24 | 1045660.09 | 22.48 | 21.24 | 32.35 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 20.89 | 20.89 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.06 | 21.06 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.04 | 21.04 | 0.00 |
April | 0.177092E+09 | 5.67 | 15735.24 | 27-APR-12:30 | 1044464.10 | 26-APR-14:30 | 21.23 | 21.20 | 0.42 |
May | 91807998.07 | 5.00 | 15735.24 | 05-MAY-12:40 | 1022542.72 | 04-MAY-13:20 | 21.49 | 21.46 | 0.36 |
June | 0.198428E+09 | 11.17 | 15735.24 | 21-JUN-15:30 | 1038838.30 | 28-JUN-14:30 | 21.89 | 21.82 | 0.83 |
July | 0.168398E+10 | 37.17 | 15735.24 | 07-JUL-11:50 | 1045660.09 | 06-JUL-15:40 | 22.24 | 22.05 | 2.67 |
August | 0.404771E+10 | 75.50 | 15735.24 | 07-AUG-10:20 | 1029466.33 | 21-AUG-15:30 | 22.48 | 22.10 | 5.42 |
September | 0.612228E+09 | 13.00 | 15735.24 | 11-SEP-15:50 | 1018799.67 | 08-SEP-14:30 | 21.75 | 21.68 | 0.96 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.16 | 21.16 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.04 | 21.04 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.03 | 21.03 | 0.00 |
Annual Sum or Average | 0.681125E+10 | 147.50 | 21.44 | 21.38 | 0.90 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 20.89 | 0.00 | ||
Maximum of Months | 0.404771E+10 | 75.50 | 15735.24 | 1045660.09 | 22.48 | 22.10 | 5.42 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.258587E+12 | 0.00 | 494.94 | 1604107.31 | 03-JAN-06:03 | 0.00 | 26.99 | 62.41 | 0.45 | 0.00 | 0.04 | 0.74 | 03-JAN-06:03 |
February | 0.141795E+12 | 0.00 | 384.78 | 1195098.67 | 16-FEB-05:01 | 0.00 | 24.87 | 56.05 | 0.27 | 0.00 | 0.03 | 0.55 | 16-FEB-05:01 |
March | 0.434163E+11 | 0.00 | 311.58 | 1191927.50 | 06-MAR-05:01 | 0.00 | 22.30 | 46.13 | 0.07 | 0.00 | 0.01 | 0.55 | 06-MAR-05:01 |
April | 0.142512E+11 | 0.00 | 154.03 | 780046.82 | 11-APR-05:03 | 0.00 | 22.19 | 34.45 | 0.02 | 0.00 | 0.00 | 0.36 | 11-APR-05:03 |
May | 0.258549E+10 | 0.00 | 67.74 | 319814.17 | 18-MAY-05:03 | 0.00 | 20.86 | 26.19 | 0.00 | 0.00 | 0.00 | 0.15 | 18-MAY-05:03 |
June | 0.323307E+09 | 0.00 | 17.29 | 43355.03 | 14-JUN-05:03 | 0.00 | 19.57 | 21.01 | 0.00 | 0.00 | 0.00 | 0.02 | 14-JUN-05:03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 19.55 | 19.55 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 19166201.74 | 0.00 | 8.07 | 2771.72 | 03-AUG-05:08 | 0.00 | 19.45 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 | 03-AUG-05:08 |
September | 0.932112E+09 | 0.00 | 54.46 | 61452.56 | 27-SEP-05:10 | 0.00 | 19.37 | 23.91 | 0.00 | 0.00 | 0.00 | 0.03 | 27-SEP-05:10 |
October | 0.184335E+11 | 0.00 | 233.83 | 992694.08 | 28-OCT-05:02 | 0.00 | 20.22 | 38.58 | 0.03 | 0.00 | 0.00 | 0.46 | 28-OCT-05:02 |
November | 0.896078E+11 | 0.00 | 356.31 | 1178915.54 | 24-NOV-06:01 | 0.00 | 22.40 | 50.57 | 0.15 | 0.00 | 0.02 | 0.55 | 24-NOV-06:01 |
December | 0.185375E+12 | 0.00 | 437.88 | 1220091.76 | 27-DEC-05:01 | 0.00 | 24.94 | 57.37 | 0.31 | 0.00 | 0.03 | 0.57 | 27-DEC-05:01 |
Annual Sum or Average | 0.755325E+12 | 0.00 | 2520.91 | 0.00 | 21.88 | 37.94 | 0.11 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 19.55 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.258587E+12 | 0.00 | 494.94 | 1604107.31 | 0.00 | 26.99 | 62.41 | 0.45 | 0.00 | 0.04 | 0.74 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 21.66 | 21.66 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 24.62 | 24.62 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.62 | 27.62 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 31.37 | 31.37 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 22.69 | 22.69 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 26.66 | 26.66 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 31.84 | 31.84 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 37.01 | 37.01 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 23.00 | 23.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 25.00 | 25.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.55 | 27.55 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 30.15 | 30.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 27.46 | 27.46 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.66 | 21.66 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.01 | 37.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1564.80 | 0.00 | 1.02 | 1564.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 02-JAN-06:01 | 0.86 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 0.792885E+09 | 0.00 | 8.46 | 0.792885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53102.46 | 27-FEB-15:00 | 53102.46 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.104864E+10 | 0.00 | 29.12 | 0.104864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27826.20 | 18-MAR-16:00 | 27826.20 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.100492E+11 | 0.00 | 94.59 | 0.100492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120461.23 | 27-APR-14:30 | 120461.23 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 |
May | 0.165309E+11 | 0.00 | 178.72 | 0.165268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98394.03 | 04-MAY-15:00 | 98394.03 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.323628E+11 | 0.00 | 290.91 | 0.323536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110382.39 | 28-JUN-15:20 | 110382.39 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.589222E+11 | 0.00 | 417.78 | 0.579823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142416.23 | 31-JUL-16:00 | 129254.18 | 31-JUL-14:40 | 0.00 | 0.00 | 0.00 |
August | 0.818136E+11 | 0.00 | 477.73 | 0.789533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151565.34 | 29-AUG-14:30 | 137460.97 | 29-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.256484E+11 | 0.00 | 249.07 | 0.252054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110855.85 | 14-SEP-13:00 | 106030.84 | 12-SEP-14:40 | 0.00 | 0.00 | 0.00 |
October | 0.454281E+10 | 0.00 | 72.27 | 0.454281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75993.94 | 04-OCT-15:00 | 75993.94 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.656917E+09 | 0.00 | 10.17 | 0.656917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35166.83 | 04-NOV-14:00 | 35166.83 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 2025.31 | 0.00 | 1.38 | 2025.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 26-DEC-05:52 | 0.81 | 26-DEC-05:52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232368E+12 | 0.00 | 1831.24 | 0.228112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1564.80 | 0.00 | 1.02 | 1564.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.81 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.818136E+11 | 0.00 | 477.73 | 0.789533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151565.34 | 137460.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 66618.44 | 0.00 | 25.28 | 66618.44 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 02-JAN-06:13 | 3.24 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 |
February | 0.523285E+10 | 0.00 | 33.92 | 0.523285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 360598.40 | 27-FEB-15:00 | 360598.40 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.750277E+10 | 0.00 | 49.00 | 0.750277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 252564.06 | 18-MAR-14:00 | 252564.06 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.744492E+11 | 0.00 | 96.41 | 0.744492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1016421.83 | 27-APR-14:50 | 1016421.83 | 27-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.143109E+12 | 0.00 | 182.97 | 0.143086E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 914705.40 | 04-MAY-15:00 | 914705.40 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.265622E+12 | 0.00 | 279.47 | 0.265619E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 992812.98 | 28-JUN-15:30 | 992812.98 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.469568E+12 | 0.00 | 373.54 | 0.463357E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1254461.21 | 31-JUL-16:00 | 1110168.85 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.629965E+12 | 0.00 | 397.20 | 0.609744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1322050.96 | 29-AUG-14:30 | 1212067.27 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.228374E+12 | 0.00 | 244.45 | 0.223385E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1063603.05 | 14-SEP-13:00 | 993569.67 | 12-SEP-15:20 | 0.00 | 0.00 | 0.00 |
October | 0.359190E+11 | 0.00 | 78.31 | 0.359190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 659281.03 | 04-OCT-15:00 | 659281.03 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.577554E+10 | 0.00 | 52.40 | 0.577554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 316901.29 | 04-NOV-14:00 | 316901.29 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 84346.93 | 0.00 | 33.58 | 84346.93 | 0.00 | 0.00 | 0.00 | 0.00 | 3.55 | 20-DEC-06:40 | 3.55 | 20-DEC-06:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186552E+13 | 0.00 | 1846.53 | 0.183407E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 66618.44 | 0.00 | 25.28 | 66618.44 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 3.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.629965E+12 | 0.00 | 397.20 | 0.609744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1322050.96 | 1212067.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 66560.84 | 0.00 | 0.79 | 66560.84 | 0.00 | 0.00 | 0.00 | 0.00 | 193.42 | 02-JAN-04:20 | 193.42 | 02-JAN-04:20 | 0.00 | 0.00 | 0.00 |
February | 0.427343E+09 | 0.00 | 8.61 | 0.427343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27207.16 | 27-FEB-15:00 | 27207.16 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.675303E+09 | 0.00 | 26.00 | 0.675303E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24756.03 | 18-MAR-14:00 | 24756.03 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.770370E+10 | 0.00 | 75.89 | 0.770370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120072.31 | 27-APR-14:50 | 120072.31 | 27-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.147982E+11 | 0.00 | 168.06 | 0.147942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101935.11 | 04-MAY-15:00 | 101935.11 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.281241E+11 | 0.00 | 270.54 | 0.281221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120043.88 | 28-JUN-15:20 | 120043.88 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.504478E+11 | 0.00 | 358.54 | 0.497805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 146594.48 | 31-JUL-16:00 | 134026.00 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.671747E+11 | 0.00 | 385.18 | 0.651020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152469.12 | 10-AUG-15:40 | 144287.12 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.226088E+11 | 0.00 | 233.36 | 0.222423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107776.85 | 14-SEP-13:10 | 104923.73 | 12-SEP-15:20 | 0.00 | 0.00 | 0.00 |
October | 0.313174E+10 | 0.00 | 60.09 | 0.313174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65198.51 | 04-OCT-15:00 | 65198.51 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.562307E+09 | 0.00 | 8.59 | 0.562307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31532.84 | 04-NOV-14:00 | 31532.84 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 79833.72 | 0.00 | 0.12 | 79833.72 | 0.00 | 0.00 | 0.00 | 0.00 | 314.68 | 26-DEC-04:20 | 314.68 | 26-DEC-04:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195654E+12 | 0.00 | 1595.77 | 0.192542E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 66560.84 | 0.00 | 0.12 | 66560.84 | 0.00 | 0.00 | 0.00 | 0.00 | 193.42 | 193.42 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.671747E+11 | 0.00 | 385.18 | 0.651020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152469.12 | 144287.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1261208.54 | 0.00 | 0.07 | 1261208.54 | 0.00 | 0.00 | 0.00 | 0.00 | 9142.44 | 11-JAN-06:02 | 9142.44 | 11-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.447807E+09 | 0.00 | 6.79 | 0.439967E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47457.93 | 24-FEB-05:02 | 32243.74 | 24-FEB-05:02 | 0.00 | 0.00 | 0.00 |
March | 0.116881E+09 | 0.00 | 5.53 | 0.109503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23875.08 | 10-MAR-06:03 | 15771.10 | 09-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.403601E+10 | 0.00 | 44.76 | 0.403202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60794.34 | 27-APR-16:00 | 60794.34 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.764494E+10 | 0.00 | 97.79 | 0.763956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59367.42 | 15-MAY-16:00 | 59367.42 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.159405E+11 | 0.00 | 191.76 | 0.159106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59078.56 | 28-JUN-15:40 | 59078.56 | 28-JUN-15:40 | 0.00 | 0.00 | 0.00 |
July | 0.298102E+11 | 0.00 | 272.00 | 0.295269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78614.37 | 31-JUL-12:10 | 73441.49 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.419790E+11 | 0.00 | 310.13 | 0.414142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91451.33 | 13-AUG-16:40 | 91451.33 | 13-AUG-16:40 | 0.00 | 0.00 | 0.00 |
September | 0.123264E+11 | 0.00 | 154.58 | 0.122432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59374.75 | 11-SEP-15:00 | 59374.75 | 11-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.160932E+10 | 0.00 | 36.20 | 0.159996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44296.57 | 09-OCT-10:22 | 44296.57 | 09-OCT-10:22 | 0.00 | 0.00 | 0.00 |
November | 0.248574E+09 | 0.00 | 5.30 | 0.242013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32093.81 | 04-NOV-04:02 | 22579.79 | 27-NOV-04:02 | 0.00 | 0.00 | 0.00 |
December | 5242049.13 | 0.00 | 0.21 | 5242049.13 | 0.00 | 0.00 | 0.00 | 0.00 | 11199.72 | 16-DEC-06:02 | 11199.72 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114166E+12 | 0.00 | 1125.12 | 0.113165E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1261208.54 | 0.00 | 0.07 | 1261208.54 | 0.00 | 0.00 | 0.00 | 0.00 | 9142.44 | 9142.44 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.419790E+11 | 0.00 | 310.13 | 0.414142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91451.33 | 91451.33 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.321684E+12 | 0.807293E+11 | 744.00 | 0.321676E+12 | 7870583.44 | 0.00 | 0.34 | 31-JAN-22:03 | 0.31 | 07-JAN-08:00 | 124452.07 | 11-JAN-22:07 | 124452.07 | 11-JAN-22:07 | 729.76 | 02-JAN-07:10 | 31222.17 | 31-JAN-22:03 | 0.00 |
February | 0.512873E+12 | 0.121910E+12 | 672.00 | 0.512631E+12 | 0.242706E+09 | 0.00 | 0.56 | 27-FEB-15:00 | 0.53 | 21-FEB-07:10 | 216585.62 | 27-FEB-15:00 | 216585.62 | 27-FEB-15:00 | 3284.07 | 24-FEB-10:50 | 58711.23 | 27-FEB-15:00 | 0.00 |
March | 0.816116E+12 | 0.186434E+12 | 744.00 | 0.815931E+12 | 0.185004E+09 | 0.00 | 0.94 | 31-MAR-24:00 | 0.72 | 01-MAR-07:10 | 394413.60 | 31-MAR-24:00 | 394413.60 | 31-MAR-24:00 | 3954.23 | 09-MAR-15:10 | 86451.09 | 31-MAR-24:00 | 0.00 |
April | 0.102912E+13 | 0.232497E+12 | 720.00 | 0.102882E+13 | 0.302094E+09 | 0.00 | 1.00 | 01-APR-12:10 | 0.36 | 30-APR-24:00 | 405882.19 | 27-APR-19:20 | 404968.78 | 27-APR-18:50 | 3942.48 | 14-APR-16:10 | 129513.18 | 27-APR-16:00 | 0.00 |
May | 0.331671E+12 | 0.837365E+11 | 744.00 | 0.330569E+12 | 0.110255E+10 | 0.00 | 0.54 | 31-MAY-23:20 | 0.31 | 27-MAY-06:50 | 212776.02 | 31-MAY-23:20 | 212191.54 | 31-MAY-24:00 | 4018.36 | 05-MAY-17:00 | 49572.67 | 31-MAY-23:20 | 0.00 |
June | 0.560002E+12 | 0.138399E+12 | 720.00 | 0.558385E+12 | 0.161719E+10 | 0.00 | 0.74 | 30-JUN-23:30 | 0.53 | 01-JUN-06:30 | 304609.62 | 30-JUN-24:00 | 303795.15 | 30-JUN-24:00 | 5385.10 | 12-JUN-15:00 | 72154.14 | 28-JUN-17:00 | 0.00 |
July | 0.827921E+12 | 0.209701E+12 | 744.00 | 0.824936E+12 | 0.298426E+10 | 0.00 | 0.96 | 31-JUL-23:15 | 0.73 | 01-JUL-07:00 | 396933.76 | 31-JUL-23:55 | 396231.53 | 31-JUL-23:55 | 5874.43 | 28-JUL-14:00 | 114077.44 | 24-JUL-15:00 | 0.00 |
August | 0.107275E+13 | 0.279531E+12 | 744.00 | 0.106969E+13 | 0.306278E+10 | 0.00 | 1.00 | 06-AUG-14:13 | 0.37 | 31-AUG-24:00 | 410766.80 | 29-AUG-21:00 | 406969.46 | 29-AUG-21:14 | 6733.99 | 29-AUG-20:00 | 141517.38 | 10-AUG-17:00 | 0.00 |
September | 0.325455E+12 | 0.820251E+11 | 720.00 | 0.322645E+12 | 0.280963E+10 | 0.00 | 0.53 | 30-SEP-24:00 | 0.32 | 27-SEP-06:30 | 211624.01 | 30-SEP-24:00 | 211375.87 | 30-SEP-24:00 | 4796.19 | 01-SEP-11:00 | 49362.02 | 30-SEP-24:00 | 0.00 |
October | 0.575085E+12 | 0.136138E+12 | 744.00 | 0.574558E+12 | 0.527434E+09 | 0.00 | 0.74 | 31-OCT-24:00 | 0.53 | 21-OCT-06:40 | 303125.64 | 31-OCT-24:00 | 303125.64 | 31-OCT-24:00 | 3528.31 | 26-OCT-14:00 | 68613.04 | 31-OCT-24:00 | 0.00 |
November | 0.791457E+12 | 0.179838E+12 | 720.00 | 0.790883E+12 | 0.574068E+09 | 0.00 | 0.78 | 04-NOV-15:00 | 0.73 | 02-NOV-07:00 | 310601.76 | 04-NOV-18:00 | 308851.22 | 06-NOV-22:03 | 4030.31 | 03-NOV-16:00 | 85393.63 | 04-NOV-15:00 | 0.00 |
December | 0.106052E+13 | 0.233527E+12 | 744.00 | 0.106048E+13 | 38105445.72 | 0.00 | 0.96 | 06-DEC-22:03 | 0.92 | 29-DEC-07:10 | 400537.50 | 05-DEC-22:03 | 400537.50 | 05-DEC-22:03 | 1914.30 | 28-DEC-17:00 | 88296.18 | 06-DEC-22:03 | 0.00 |
Annual Sum or Average | 0.822465E+13 | 0.196446E+13 | 8760.00 | 0.821120E+13 | 0.134537E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.321684E+12 | 0.807293E+11 | 672.00 | 0.321676E+12 | 7870583.44 | 0.00 | 0.34 | 0.31 | 124452.07 | 124452.07 | 729.76 | 31222.17 | 0.00 | ||||||
Maximum of Months | 0.107275E+13 | 0.279531E+12 | 744.00 | 0.106969E+13 | 0.306278E+10 | 0.00 | 1.00 | 0.92 | 410766.80 | 406969.46 | 6733.99 | 141517.38 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.397904E+10 | 0.103683E+10 | 744.00 | 0.397869E+10 | 350077.61 | 0.00 | 0.27 | 08-JAN-16:03 | 0.11 | 07-JAN-08:00 | 2154.48 | 05-JAN-16:10 | 2154.48 | 05-JAN-16:10 | 15.65 | 02-JAN-07:10 | 554.89 | 08-JAN-16:03 | 0.00 |
February | 0.871943E+10 | 0.211082E+10 | 672.00 | 0.870877E+10 | 10660227.58 | 0.00 | 0.53 | 12-FEB-16:45 | 0.36 | 18-FEB-18:00 | 4451.15 | 27-FEB-16:20 | 4451.15 | 27-FEB-16:20 | 132.30 | 24-FEB-11:00 | 1155.78 | 27-FEB-16:10 | 0.00 |
March | 0.153099E+11 | 0.352650E+10 | 744.00 | 0.153014E+11 | 8461506.32 | 0.00 | 0.80 | 31-MAR-24:00 | 0.56 | 01-MAR-07:10 | 7560.31 | 31-MAR-24:00 | 7560.31 | 31-MAR-24:00 | 140.39 | 09-MAR-15:10 | 1716.47 | 18-MAR-17:02 | 0.00 |
April | 0.200461E+11 | 0.452374E+10 | 720.00 | 0.200332E+11 | 12828780.14 | 0.00 | 0.98 | 01-APR-17:32 | 0.30 | 30-APR-24:00 | 8688.04 | 26-APR-17:50 | 8688.04 | 26-APR-17:50 | 164.90 | 28-APR-11:10 | 2748.01 | 01-APR-17:12 | 0.00 |
May | 0.565176E+10 | 0.141989E+10 | 744.00 | 0.561217E+10 | 39587719.55 | 0.00 | 0.45 | 31-MAY-24:00 | 0.17 | 18-MAY-06:50 | 4072.44 | 31-MAY-24:00 | 4056.19 | 31-MAY-24:00 | 134.57 | 05-MAY-16:10 | 933.17 | 31-MAY-24:00 | 0.00 |
June | 0.106127E+11 | 0.259048E+10 | 720.00 | 0.105560E+11 | 56713216.63 | 0.00 | 0.64 | 30-JUN-24:00 | 0.40 | 14-JUN-06:30 | 5943.65 | 30-JUN-24:00 | 5923.32 | 30-JUN-24:00 | 209.32 | 12-JUN-15:00 | 1448.77 | 28-JUN-16:00 | 0.00 |
July | 0.162937E+11 | 0.407162E+10 | 744.00 | 0.161827E+11 | 0.110975E+09 | 0.00 | 0.84 | 31-JUL-23:32 | 0.61 | 01-JUL-07:00 | 7857.17 | 31-JUL-23:55 | 7837.88 | 31-JUL-23:50 | 226.99 | 11-JUL-09:30 | 2313.62 | 24-JUL-15:00 | 0.00 |
August | 0.213466E+11 | 0.551647E+10 | 744.00 | 0.212072E+11 | 0.139440E+09 | 0.00 | 1.00 | 10-AUG-17:40 | 0.29 | 31-AUG-24:00 | 9130.94 | 06-AUG-18:36 | 9130.94 | 06-AUG-18:36 | 256.81 | 30-AUG-08:00 | 3100.93 | 10-AUG-17:40 | 0.00 |
September | 0.564823E+10 | 0.140908E+10 | 720.00 | 0.554845E+10 | 99785698.96 | 0.00 | 0.44 | 30-SEP-24:00 | 0.18 | 27-SEP-07:00 | 3904.94 | 30-SEP-24:00 | 3897.89 | 30-SEP-24:00 | 179.17 | 14-SEP-11:00 | 898.83 | 30-SEP-24:00 | 0.00 |
October | 0.104193E+11 | 0.244758E+10 | 744.00 | 0.103955E+11 | 23743900.00 | 0.00 | 0.61 | 31-OCT-24:00 | 0.37 | 28-OCT-07:00 | 5566.61 | 31-OCT-24:00 | 5566.61 | 31-OCT-24:00 | 139.29 | 26-OCT-14:00 | 1333.42 | 04-OCT-16:40 | 0.00 |
November | 0.146914E+11 | 0.333013E+10 | 720.00 | 0.146666E+11 | 24850960.40 | 0.00 | 0.69 | 04-NOV-16:00 | 0.57 | 18-NOV-18:00 | 6285.69 | 12-NOV-16:10 | 6285.69 | 12-NOV-16:10 | 170.78 | 03-NOV-16:00 | 1654.53 | 04-NOV-15:40 | 0.00 |
December | 0.200170E+11 | 0.445376E+10 | 744.00 | 0.200145E+11 | 2432922.12 | 0.00 | 0.89 | 03-DEC-15:23 | 0.75 | 16-DEC-18:00 | 8056.06 | 10-DEC-15:25 | 8056.06 | 10-DEC-15:25 | 85.68 | 28-DEC-15:00 | 1805.86 | 03-DEC-15:23 | 0.00 |
Annual Sum or Average | 0.152735E+12 | 0.364369E+11 | 8760.00 | 0.152205E+12 | 0.529830E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.397904E+10 | 0.103683E+10 | 672.00 | 0.397869E+10 | 350077.61 | 0.00 | 0.27 | 0.11 | 2154.48 | 2154.48 | 15.65 | 554.89 | 0.00 | ||||||
Maximum of Months | 0.213466E+11 | 0.551647E+10 | 744.00 | 0.212072E+11 | 0.139440E+09 | 0.00 | 1.00 | 0.75 | 9130.94 | 9130.94 | 256.81 | 3100.93 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.167273E+11 | 0.466698E+10 | 685.42 | 0.167273E+11 | 86127.75 | 0.00 | 0.22 | 05-JAN-16:10 | 0.00 | 01-JAN-00:05 | 17136.08 | 05-JAN-16:10 | 17136.08 | 05-JAN-16:10 | 21.70 | 02-JAN-11:40 | 4339.16 | 05-JAN-16:10 | 0.00 |
February | 0.666526E+11 | 0.164403E+11 | 672.00 | 0.665485E+11 | 0.104090E+09 | 0.00 | 0.49 | 27-FEB-16:20 | 0.23 | 21-FEB-07:10 | 40647.78 | 27-FEB-16:20 | 40647.78 | 27-FEB-16:20 | 1272.77 | 24-FEB-11:10 | 10587.03 | 27-FEB-16:20 | 0.00 |
March | 0.132193E+12 | 0.308118E+11 | 744.00 | 0.132108E+12 | 84496431.15 | 0.00 | 0.75 | 31-MAR-24:00 | 0.49 | 06-MAR-07:10 | 66781.65 | 31-MAR-24:00 | 66781.65 | 31-MAR-24:00 | 1376.81 | 09-MAR-17:00 | 15686.42 | 18-MAR-17:02 | 0.00 |
April | 0.182016E+12 | 0.413967E+11 | 720.00 | 0.181886E+12 | 0.129913E+09 | 0.00 | 0.96 | 26-APR-17:50 | 0.23 | 30-APR-24:00 | 82338.18 | 26-APR-17:50 | 82338.18 | 26-APR-17:50 | 1642.53 | 28-APR-11:10 | 25801.80 | 27-APR-16:00 | 0.00 |
May | 0.473262E+11 | 0.120334E+11 | 744.00 | 0.469429E+11 | 0.383285E+09 | 0.00 | 0.44 | 31-MAY-24:00 | 0.12 | 18-MAY-06:10 | 37923.17 | 31-MAY-23:50 | 37754.17 | 31-MAY-24:00 | 1324.92 | 05-MAY-16:10 | 8712.36 | 31-MAY-24:00 | 0.00 |
June | 0.964232E+11 | 0.236828E+11 | 720.00 | 0.958661E+11 | 0.557101E+09 | 0.00 | 0.63 | 30-JUN-24:00 | 0.36 | 14-JUN-06:10 | 55621.63 | 30-JUN-24:00 | 55427.14 | 30-JUN-24:00 | 2073.72 | 12-JUN-15:00 | 13746.24 | 28-JUN-16:00 | 0.00 |
July | 0.152944E+12 | 0.383310E+11 | 744.00 | 0.151846E+12 | 0.109814E+10 | 0.00 | 0.84 | 31-JUL-23:15 | 0.58 | 18-JUL-06:10 | 75708.24 | 31-JUL-23:55 | 75505.79 | 31-JUL-23:55 | 2259.38 | 11-JUL-09:30 | 21971.53 | 24-JUL-15:00 | 0.00 |
August | 0.201250E+12 | 0.521476E+11 | 744.00 | 0.199860E+12 | 0.139056E+10 | 0.00 | 1.00 | 10-AUG-17:40 | 0.25 | 31-AUG-24:00 | 84717.07 | 06-AUG-18:17 | 84717.07 | 06-AUG-18:17 | 2560.80 | 30-AUG-08:00 | 29686.84 | 10-AUG-17:40 | 0.00 |
September | 0.482249E+11 | 0.121589E+11 | 720.00 | 0.472619E+11 | 0.963014E+09 | 0.00 | 0.41 | 30-SEP-24:00 | 0.14 | 28-SEP-07:00 | 34784.09 | 30-SEP-24:00 | 34710.88 | 30-SEP-24:00 | 1763.83 | 14-SEP-13:30 | 8148.91 | 14-SEP-17:00 | 0.00 |
October | 0.876194E+11 | 0.208362E+11 | 744.00 | 0.873852E+11 | 0.234237E+09 | 0.00 | 0.56 | 04-OCT-16:50 | 0.31 | 28-OCT-07:00 | 47018.57 | 31-OCT-24:00 | 47018.57 | 31-OCT-24:00 | 1348.93 | 26-OCT-14:10 | 12544.15 | 04-OCT-16:40 | 0.00 |
November | 0.123237E+12 | 0.283437E+11 | 720.00 | 0.122991E+12 | 0.245916E+09 | 0.00 | 0.66 | 04-NOV-16:00 | 0.48 | 24-NOV-07:10 | 56637.56 | 04-NOV-16:00 | 55627.33 | 04-NOV-16:00 | 1686.59 | 03-NOV-16:00 | 15073.98 | 04-NOV-15:50 | 0.00 |
December | 0.169561E+12 | 0.383324E+11 | 744.00 | 0.169536E+12 | 24712228.86 | 0.00 | 0.82 | 05-DEC-15:50 | 0.63 | 26-DEC-07:10 | 72932.27 | 05-DEC-15:50 | 72932.27 | 05-DEC-15:50 | 847.75 | 28-DEC-15:00 | 16098.08 | 05-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.132417E+13 | 0.319182E+12 | 8701.42 | 0.131896E+13 | 0.521555E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.167273E+11 | 0.466698E+10 | 672.00 | 0.167273E+11 | 86127.75 | 0.00 | 0.22 | 0.00 | 17136.08 | 17136.08 | 21.70 | 4339.16 | 0.00 | ||||||
Maximum of Months | 0.201250E+12 | 0.521476E+11 | 744.00 | 0.199860E+12 | 0.139056E+10 | 0.00 | 1.00 | 0.63 | 84717.07 | 84717.07 | 2560.80 | 29686.84 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.642259E+09 | 0.187432E+09 | 387.42 | 0.642259E+09 | -0.0 | 0.00 | 0.20 | 05-JAN-16:10 | 0.00 | 01-JAN-00:05 | 1555.70 | 05-JAN-16:10 | 1555.70 | 05-JAN-16:10 | 0.00 | 26-JAN-16:30 | 397.62 | 05-JAN-16:10 | 0.00 |
February | 0.511774E+10 | 0.128250E+10 | 671.75 | 0.510750E+10 | 10238140.82 | 0.00 | 0.47 | 27-FEB-16:20 | 0.00 | 19-FEB-06:03 | 4015.55 | 27-FEB-16:20 | 4015.55 | 27-FEB-16:20 | 125.69 | 24-FEB-11:10 | 1048.63 | 27-FEB-16:20 | 0.00 |
March | 0.119505E+11 | 0.281743E+10 | 744.00 | 0.119422E+11 | 8343088.38 | 0.00 | 0.69 | 31-MAR-23:20 | 0.35 | 06-MAR-04:01 | 6216.83 | 31-MAR-23:20 | 6216.83 | 31-MAR-23:20 | 137.15 | 09-MAR-17:00 | 1535.48 | 18-MAR-17:02 | 0.00 |
April | 0.174006E+11 | 0.399106E+10 | 720.00 | 0.173877E+11 | 12875400.70 | 0.00 | 0.95 | 26-APR-17:50 | 0.17 | 30-APR-24:00 | 8311.32 | 26-APR-17:50 | 8311.32 | 26-APR-17:50 | 163.69 | 28-APR-11:10 | 2613.51 | 27-APR-16:00 | 0.00 |
May | 0.420608E+10 | 0.108250E+10 | 743.86 | 0.416820E+10 | 37883743.64 | 0.00 | 0.43 | 31-MAY-23:30 | 0.00 | 18-MAY-04:43 | 3721.13 | 31-MAY-23:20 | 3694.91 | 31-MAY-23:40 | 133.57 | 05-MAY-16:10 | 856.97 | 31-MAY-23:30 | 0.00 |
June | 0.941064E+10 | 0.232348E+10 | 720.00 | 0.935520E+10 | 55444240.55 | 0.00 | 0.61 | 30-JUN-23:50 | 0.31 | 14-JUN-06:10 | 5460.54 | 30-JUN-24:00 | 5441.31 | 30-JUN-24:00 | 207.17 | 12-JUN-15:00 | 1406.32 | 28-JUN-16:00 | 0.00 |
July | 0.151696E+11 | 0.381747E+10 | 744.00 | 0.150600E+11 | 0.109544E+09 | 0.00 | 0.83 | 31-JUL-23:15 | 0.55 | 18-JUL-06:10 | 7561.04 | 31-JUL-23:55 | 7540.72 | 31-JUL-23:55 | 225.34 | 11-JUL-09:40 | 2237.68 | 24-JUL-15:00 | 0.00 |
August | 0.199714E+11 | 0.519746E+10 | 744.00 | 0.198326E+11 | 0.138802E+09 | 0.00 | 1.00 | 10-AUG-17:50 | 0.23 | 31-AUG-24:00 | 8604.70 | 06-AUG-18:38 | 8604.70 | 06-AUG-18:38 | 255.07 | 30-AUG-08:00 | 3013.27 | 10-AUG-17:40 | 0.00 |
September | 0.432016E+10 | 0.110282E+10 | 720.00 | 0.422561E+10 | 94550062.77 | 0.00 | 0.36 | 30-SEP-23:30 | 0.07 | 27-SEP-06:10 | 3055.32 | 30-SEP-23:30 | 3047.18 | 30-SEP-23:30 | 179.32 | 14-SEP-13:20 | 832.70 | 14-SEP-17:00 | 0.00 |
October | 0.764303E+10 | 0.184090E+10 | 744.00 | 0.762010E+10 | 22930993.05 | 0.00 | 0.55 | 04-OCT-16:50 | 0.21 | 16-OCT-06:10 | 4566.99 | 04-OCT-16:50 | 4566.99 | 04-OCT-16:50 | 132.32 | 26-OCT-14:10 | 1264.54 | 04-OCT-16:40 | 0.00 |
November | 0.107930E+11 | 0.251747E+10 | 720.00 | 0.107687E+11 | 24281708.86 | 0.00 | 0.64 | 04-NOV-16:00 | 0.35 | 13-NOV-04:01 | 5561.40 | 04-NOV-16:00 | 5461.24 | 04-NOV-16:00 | 167.87 | 03-NOV-16:00 | 1486.92 | 04-NOV-15:40 | 0.00 |
December | 0.150723E+11 | 0.345924E+10 | 744.00 | 0.150699E+11 | 2436201.42 | 0.00 | 0.79 | 05-DEC-15:50 | 0.46 | 26-DEC-04:03 | 7121.27 | 05-DEC-15:50 | 7121.27 | 05-DEC-15:50 | 84.20 | 28-DEC-15:00 | 1580.01 | 05-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.121697E+12 | 0.296198E+11 | 8403.03 | 0.121180E+12 | 0.517330E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.642259E+09 | 0.187432E+09 | 387.42 | 0.642259E+09 | -0.0 | 0.00 | 0.20 | 0.00 | 1555.70 | 1555.70 | 0.00 | 397.62 | 0.00 | ||||||
Maximum of Months | 0.199714E+11 | 0.519746E+10 | 744.00 | 0.198326E+11 | 0.138802E+09 | 0.00 | 1.00 | 0.55 | 8604.70 | 8604.70 | 255.07 | 3013.27 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.91 | 0.00 | 73.91 | 1.23 | 486.12 | 0.00 | 0.00 | 0.00 |
February | 115.01 | 0.00 | 115.01 | 16.40 | 427.88 | 0.00 | 0.00 | 0.00 |
March | 169.44 | 0.00 | 169.44 | 61.75 | 349.32 | 0.00 | 0.00 | 0.00 |
April | 239.78 | 0.85 | 238.93 | 145.42 | 273.52 | 0.00 | 0.00 | 0.00 |
May | 308.53 | 9.17 | 299.37 | 244.45 | 211.00 | 0.00 | 0.00 | 0.00 |
June | 324.42 | 21.42 | 302.99 | 284.99 | 162.40 | 0.00 | 0.00 | 0.00 |
July | 308.34 | 24.18 | 284.16 | 304.89 | 144.77 | 0.00 | 0.00 | 0.00 |
August | 249.60 | 6.75 | 242.86 | 249.31 | 142.60 | 0.00 | 0.00 | 0.00 |
September | 193.88 | 0.06 | 193.83 | 144.36 | 216.14 | 0.00 | 0.00 | 0.00 |
October | 132.84 | 0.00 | 132.84 | 53.00 | 306.57 | 0.00 | 0.00 | 0.00 |
November | 83.68 | 0.00 | 83.68 | 7.72 | 403.94 | 0.00 | 0.00 | 0.00 |
December | 62.80 | 0.00 | 62.80 | 0.29 | 502.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.88 | 5.24 | 183.64 | 126.84 | 301.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.80 | 0.00 | 62.80 | 0.29 | 142.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.42 | 24.18 | 302.99 | 304.89 | 502.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.91 | 0.00 | 73.91 | 1.23 | 486.12 | 0.00 | 0.00 | 0.00 |
February | 115.00 | 0.00 | 115.00 | 16.39 | 427.88 | 0.00 | 0.00 | 0.00 |
March | 169.44 | 0.00 | 169.44 | 61.75 | 349.32 | 0.00 | 0.00 | 0.00 |
April | 239.77 | 0.85 | 238.92 | 145.42 | 273.52 | 0.00 | 0.00 | 0.00 |
May | 308.53 | 9.17 | 299.36 | 244.44 | 211.00 | 0.00 | 0.00 | 0.00 |
June | 324.41 | 21.42 | 302.99 | 284.98 | 162.40 | 0.00 | 0.00 | 0.00 |
July | 308.34 | 24.17 | 284.16 | 304.88 | 144.77 | 0.00 | 0.00 | 0.00 |
August | 249.60 | 6.75 | 242.85 | 249.31 | 142.60 | 0.00 | 0.00 | 0.00 |
September | 193.88 | 0.06 | 193.82 | 144.36 | 216.14 | 0.00 | 0.00 | 0.00 |
October | 132.84 | 0.00 | 132.84 | 53.00 | 306.57 | 0.00 | 0.00 | 0.00 |
November | 83.68 | 0.00 | 83.68 | 7.72 | 403.94 | 0.00 | 0.00 | 0.00 |
December | 62.80 | 0.00 | 62.80 | 0.29 | 502.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.88 | 5.24 | 183.64 | 126.84 | 301.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.80 | 0.00 | 62.80 | 0.29 | 142.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.41 | 24.17 | 302.99 | 304.88 | 502.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.91 | 0.00 | 73.91 | 1.23 | 486.12 | 0.00 | 0.00 | 0.00 |
February | 115.00 | 0.00 | 115.00 | 16.39 | 427.88 | 0.00 | 0.00 | 0.00 |
March | 169.44 | 0.00 | 169.44 | 61.75 | 349.32 | 0.00 | 0.00 | 0.00 |
April | 239.78 | 0.85 | 238.92 | 145.42 | 273.52 | 0.00 | 0.00 | 0.00 |
May | 308.53 | 9.17 | 299.36 | 244.44 | 211.00 | 0.00 | 0.00 | 0.00 |
June | 324.41 | 21.42 | 302.99 | 284.98 | 162.40 | 0.00 | 0.00 | 0.00 |
July | 308.34 | 24.17 | 284.16 | 304.89 | 144.77 | 0.00 | 0.00 | 0.00 |
August | 249.60 | 6.75 | 242.85 | 249.31 | 142.60 | 0.00 | 0.00 | 0.00 |
September | 193.88 | 0.06 | 193.82 | 144.36 | 216.14 | 0.00 | 0.00 | 0.00 |
October | 132.84 | 0.00 | 132.84 | 53.00 | 306.57 | 0.00 | 0.00 | 0.00 |
November | 83.68 | 0.00 | 83.68 | 7.72 | 403.94 | 0.00 | 0.00 | 0.00 |
December | 62.80 | 0.00 | 62.80 | 0.29 | 502.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.88 | 5.24 | 183.64 | 126.84 | 301.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.80 | 0.00 | 62.80 | 0.29 | 142.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.41 | 24.17 | 302.99 | 304.89 | 502.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.91 | 0.00 | 73.91 | 1.23 | 486.12 | 0.00 | 0.00 | 0.00 |
February | 115.00 | 0.00 | 115.00 | 16.39 | 427.88 | 0.00 | 0.00 | 0.00 |
March | 169.44 | 0.00 | 169.44 | 61.75 | 349.32 | 0.00 | 0.00 | 0.00 |
April | 239.77 | 0.85 | 238.92 | 145.42 | 273.52 | 0.00 | 0.00 | 0.00 |
May | 308.53 | 9.17 | 299.36 | 244.44 | 211.00 | 0.00 | 0.00 | 0.00 |
June | 324.41 | 21.42 | 302.99 | 284.98 | 162.40 | 0.00 | 0.00 | 0.00 |
July | 308.34 | 24.17 | 284.16 | 304.88 | 144.77 | 0.00 | 0.00 | 0.00 |
August | 249.60 | 6.75 | 242.85 | 249.31 | 142.60 | 0.00 | 0.00 | 0.00 |
September | 193.88 | 0.06 | 193.82 | 144.36 | 216.14 | 0.00 | 0.00 | 0.00 |
October | 132.84 | 0.00 | 132.84 | 53.00 | 306.57 | 0.00 | 0.00 | 0.00 |
November | 83.68 | 0.00 | 83.68 | 7.72 | 403.94 | 0.00 | 0.00 | 0.00 |
December | 62.80 | 0.00 | 62.80 | 0.29 | 502.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.88 | 5.24 | 183.64 | 126.84 | 301.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.80 | 0.00 | 62.80 | 0.29 | 142.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.41 | 24.17 | 302.99 | 304.88 | 502.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.91 | 0.00 | 73.91 | 1.23 | 486.10 | 0.00 | 0.00 | 0.00 |
February | 115.00 | 0.00 | 115.00 | 16.39 | 427.86 | 0.00 | 0.00 | 0.00 |
March | 169.43 | 0.00 | 169.43 | 61.75 | 349.31 | 0.00 | 0.00 | 0.00 |
April | 239.77 | 0.85 | 238.91 | 145.41 | 273.50 | 0.00 | 0.00 | 0.00 |
May | 308.52 | 9.17 | 299.35 | 244.43 | 211.00 | 0.00 | 0.00 | 0.00 |
June | 324.40 | 21.42 | 302.98 | 284.97 | 162.39 | 0.00 | 0.00 | 0.00 |
July | 308.32 | 24.17 | 284.15 | 304.87 | 144.77 | 0.00 | 0.00 | 0.00 |
August | 249.59 | 6.75 | 242.84 | 249.30 | 142.60 | 0.00 | 0.00 | 0.00 |
September | 193.87 | 0.06 | 193.82 | 144.35 | 216.13 | 0.00 | 0.00 | 0.00 |
October | 132.83 | 0.00 | 132.83 | 53.00 | 306.55 | 0.00 | 0.00 | 0.00 |
November | 83.67 | 0.00 | 83.67 | 7.72 | 403.93 | 0.00 | 0.00 | 0.00 |
December | 62.80 | 0.00 | 62.80 | 0.29 | 502.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.87 | 5.24 | 183.63 | 126.83 | 301.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.80 | 0.00 | 62.80 | 0.29 | 142.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.40 | 24.17 | 302.98 | 304.87 | 502.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.96 | 33.46 | 98.50 | 43.00 | 496.85 | 0.00 | 0.00 | 0.00 |
February | 242.13 | 85.94 | 156.19 | 147.69 | 428.18 | 0.00 | 0.00 | 0.00 |
March | 361.52 | 130.87 | 230.65 | 290.83 | 351.04 | 0.00 | 0.00 | 0.00 |
April | 560.42 | 232.86 | 327.56 | 553.14 | 275.58 | 0.00 | 0.00 | 0.00 |
May | 596.34 | 207.33 | 389.00 | 621.11 | 228.11 | 0.00 | 0.00 | 0.00 |
June | 714.18 | 310.74 | 403.43 | 799.61 | 176.89 | 0.00 | 0.00 | 0.00 |
July | 665.07 | 298.52 | 366.55 | 778.29 | 150.84 | 0.00 | 0.00 | 0.00 |
August | 653.67 | 327.00 | 326.67 | 789.24 | 145.35 | 0.00 | 0.00 | 0.00 |
September | 483.29 | 222.90 | 260.39 | 519.66 | 222.61 | 0.00 | 0.00 | 0.00 |
October | 315.01 | 133.85 | 181.16 | 277.55 | 310.83 | 0.00 | 0.00 | 0.00 |
November | 154.40 | 43.59 | 110.81 | 76.40 | 404.46 | 0.00 | 0.00 | 0.00 |
December | 126.64 | 40.77 | 85.87 | 54.31 | 502.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 417.82 | 172.70 | 245.12 | 413.93 | 307.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 126.64 | 33.46 | 85.87 | 43.00 | 145.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 714.18 | 327.00 | 403.43 | 799.61 | 502.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.96 | 33.46 | 98.50 | 43.00 | 496.85 | 0.00 | 0.00 | 0.00 |
February | 242.13 | 85.94 | 156.19 | 147.69 | 428.18 | 0.00 | 0.00 | 0.00 |
March | 361.52 | 130.87 | 230.65 | 290.83 | 351.04 | 0.00 | 0.00 | 0.00 |
April | 560.42 | 232.86 | 327.56 | 553.14 | 275.58 | 0.00 | 0.00 | 0.00 |
May | 596.34 | 207.33 | 389.00 | 621.11 | 228.11 | 0.00 | 0.00 | 0.00 |
June | 714.18 | 310.74 | 403.43 | 799.61 | 176.89 | 0.00 | 0.00 | 0.00 |
July | 665.07 | 298.52 | 366.55 | 778.29 | 150.84 | 0.00 | 0.00 | 0.00 |
August | 653.67 | 327.00 | 326.67 | 789.24 | 145.35 | 0.00 | 0.00 | 0.00 |
September | 483.29 | 222.90 | 260.39 | 519.66 | 222.61 | 0.00 | 0.00 | 0.00 |
October | 315.01 | 133.85 | 181.16 | 277.55 | 310.83 | 0.00 | 0.00 | 0.00 |
November | 154.40 | 43.59 | 110.81 | 76.40 | 404.46 | 0.00 | 0.00 | 0.00 |
December | 126.64 | 40.77 | 85.87 | 54.31 | 502.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 417.82 | 172.70 | 245.12 | 413.93 | 307.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 126.64 | 33.46 | 85.87 | 43.00 | 145.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 714.18 | 327.00 | 403.43 | 799.61 | 502.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.96 | 33.46 | 98.50 | 43.00 | 496.84 | 0.00 | 0.00 | 0.00 |
February | 242.13 | 85.94 | 156.19 | 147.68 | 428.17 | 0.00 | 0.00 | 0.00 |
March | 361.51 | 130.87 | 230.64 | 290.83 | 351.03 | 0.00 | 0.00 | 0.00 |
April | 560.41 | 232.86 | 327.55 | 553.13 | 275.57 | 0.00 | 0.00 | 0.00 |
May | 596.32 | 207.33 | 389.00 | 621.10 | 228.10 | 0.00 | 0.00 | 0.00 |
June | 714.17 | 310.74 | 403.43 | 799.59 | 176.89 | 0.00 | 0.00 | 0.00 |
July | 665.05 | 298.51 | 366.54 | 778.28 | 150.84 | 0.00 | 0.00 | 0.00 |
August | 653.66 | 327.00 | 326.66 | 789.23 | 145.35 | 0.00 | 0.00 | 0.00 |
September | 483.28 | 222.89 | 260.39 | 519.65 | 222.60 | 0.00 | 0.00 | 0.00 |
October | 315.00 | 133.85 | 181.16 | 277.55 | 310.82 | 0.00 | 0.00 | 0.00 |
November | 154.40 | 43.59 | 110.81 | 76.39 | 404.45 | 0.00 | 0.00 | 0.00 |
December | 126.64 | 40.77 | 85.87 | 54.31 | 502.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 417.81 | 172.70 | 245.12 | 413.92 | 307.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 126.64 | 33.46 | 85.87 | 43.00 | 145.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 714.17 | 327.00 | 403.43 | 799.59 | 502.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 326.55 | 193.91 | 132.64 | 279.08 | 411.22 | 0.00 | 0.00 | 0.00 |
February | 502.18 | 310.86 | 191.33 | 491.41 | 370.78 | 0.00 | 0.00 | 0.00 |
March | 540.20 | 288.08 | 252.12 | 555.63 | 323.64 | 0.00 | 0.00 | 0.00 |
April | 570.35 | 247.64 | 322.71 | 622.54 | 270.70 | 0.00 | 0.00 | 0.00 |
May | 521.52 | 155.36 | 366.15 | 578.72 | 219.27 | 0.00 | 0.00 | 0.00 |
June | 477.14 | 128.10 | 349.03 | 541.05 | 173.63 | 0.00 | 0.00 | 0.00 |
July | 520.34 | 190.57 | 329.76 | 648.37 | 154.93 | 0.00 | 0.00 | 0.00 |
August | 559.04 | 260.69 | 298.35 | 717.54 | 149.60 | 0.00 | 0.00 | 0.00 |
September | 619.39 | 342.05 | 277.34 | 747.18 | 213.24 | 0.00 | 0.00 | 0.00 |
October | 561.06 | 346.41 | 214.65 | 617.46 | 284.72 | 0.00 | 0.00 | 0.00 |
November | 331.72 | 190.10 | 141.62 | 303.59 | 350.36 | 0.00 | 0.00 | 0.00 |
December | 347.07 | 224.60 | 122.47 | 325.73 | 429.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 489.50 | 239.42 | 250.08 | 535.86 | 278.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 326.55 | 128.10 | 122.47 | 279.08 | 149.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 619.39 | 346.41 | 366.15 | 747.18 | 429.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 326.55 | 193.90 | 132.64 | 279.07 | 411.22 | 0.00 | 0.00 | 0.00 |
February | 502.18 | 310.85 | 191.32 | 491.41 | 370.78 | 0.00 | 0.00 | 0.00 |
March | 540.20 | 288.08 | 252.12 | 555.62 | 323.64 | 0.00 | 0.00 | 0.00 |
April | 570.35 | 247.64 | 322.71 | 622.54 | 270.70 | 0.00 | 0.00 | 0.00 |
May | 521.51 | 155.36 | 366.15 | 578.71 | 219.27 | 0.00 | 0.00 | 0.00 |
June | 477.13 | 128.10 | 349.03 | 541.05 | 173.63 | 0.00 | 0.00 | 0.00 |
July | 520.34 | 190.57 | 329.76 | 648.37 | 154.93 | 0.00 | 0.00 | 0.00 |
August | 559.03 | 260.68 | 298.35 | 717.54 | 149.60 | 0.00 | 0.00 | 0.00 |
September | 619.38 | 342.04 | 277.34 | 747.18 | 213.24 | 0.00 | 0.00 | 0.00 |
October | 561.06 | 346.41 | 214.65 | 617.46 | 284.72 | 0.00 | 0.00 | 0.00 |
November | 331.72 | 190.10 | 141.62 | 303.59 | 350.36 | 0.00 | 0.00 | 0.00 |
December | 347.07 | 224.60 | 122.47 | 325.72 | 429.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 489.50 | 239.42 | 250.08 | 535.86 | 278.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 326.55 | 128.10 | 122.47 | 279.07 | 149.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 619.38 | 346.41 | 366.15 | 747.18 | 429.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 326.55 | 193.91 | 132.64 | 279.08 | 411.22 | 0.00 | 0.00 | 0.00 |
February | 502.18 | 310.86 | 191.33 | 491.41 | 370.78 | 0.00 | 0.00 | 0.00 |
March | 540.20 | 288.08 | 252.12 | 555.63 | 323.64 | 0.00 | 0.00 | 0.00 |
April | 570.35 | 247.64 | 322.71 | 622.54 | 270.70 | 0.00 | 0.00 | 0.00 |
May | 521.52 | 155.36 | 366.15 | 578.72 | 219.27 | 0.00 | 0.00 | 0.00 |
June | 477.14 | 128.10 | 349.03 | 541.05 | 173.63 | 0.00 | 0.00 | 0.00 |
July | 520.34 | 190.57 | 329.76 | 648.37 | 154.93 | 0.00 | 0.00 | 0.00 |
August | 559.04 | 260.69 | 298.35 | 717.54 | 149.60 | 0.00 | 0.00 | 0.00 |
September | 619.39 | 342.05 | 277.34 | 747.18 | 213.24 | 0.00 | 0.00 | 0.00 |
October | 561.06 | 346.41 | 214.65 | 617.46 | 284.72 | 0.00 | 0.00 | 0.00 |
November | 331.72 | 190.10 | 141.62 | 303.59 | 350.36 | 0.00 | 0.00 | 0.00 |
December | 347.07 | 224.60 | 122.47 | 325.73 | 429.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 489.50 | 239.42 | 250.08 | 535.86 | 278.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 326.55 | 128.10 | 122.47 | 279.08 | 149.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 619.39 | 346.41 | 366.15 | 747.18 | 429.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 326.55 | 193.90 | 132.64 | 279.07 | 411.22 | 0.00 | 0.00 | 0.00 |
February | 502.18 | 310.85 | 191.32 | 491.41 | 370.78 | 0.00 | 0.00 | 0.00 |
March | 540.20 | 288.08 | 252.12 | 555.62 | 323.64 | 0.00 | 0.00 | 0.00 |
April | 570.35 | 247.64 | 322.71 | 622.54 | 270.70 | 0.00 | 0.00 | 0.00 |
May | 521.51 | 155.36 | 366.15 | 578.71 | 219.27 | 0.00 | 0.00 | 0.00 |
June | 477.13 | 128.10 | 349.03 | 541.05 | 173.63 | 0.00 | 0.00 | 0.00 |
July | 520.34 | 190.57 | 329.76 | 648.37 | 154.93 | 0.00 | 0.00 | 0.00 |
August | 559.03 | 260.68 | 298.35 | 717.54 | 149.60 | 0.00 | 0.00 | 0.00 |
September | 619.38 | 342.04 | 277.34 | 747.18 | 213.24 | 0.00 | 0.00 | 0.00 |
October | 561.06 | 346.41 | 214.65 | 617.46 | 284.72 | 0.00 | 0.00 | 0.00 |
November | 331.72 | 190.10 | 141.62 | 303.59 | 350.36 | 0.00 | 0.00 | 0.00 |
December | 347.07 | 224.60 | 122.47 | 325.72 | 429.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 489.50 | 239.42 | 250.08 | 535.86 | 278.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 326.55 | 128.10 | 122.47 | 279.07 | 149.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 619.38 | 346.41 | 366.15 | 747.18 | 429.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 326.53 | 193.90 | 132.64 | 279.06 | 411.21 | 0.00 | 0.00 | 0.00 |
February | 502.16 | 310.84 | 191.32 | 491.39 | 370.77 | 0.00 | 0.00 | 0.00 |
March | 540.18 | 288.07 | 252.11 | 555.60 | 323.62 | 0.00 | 0.00 | 0.00 |
April | 570.33 | 247.63 | 322.70 | 622.51 | 270.69 | 0.00 | 0.00 | 0.00 |
May | 521.49 | 155.36 | 366.14 | 578.69 | 219.26 | 0.00 | 0.00 | 0.00 |
June | 477.12 | 128.10 | 349.02 | 541.03 | 173.63 | 0.00 | 0.00 | 0.00 |
July | 520.32 | 190.57 | 329.75 | 648.34 | 154.92 | 0.00 | 0.00 | 0.00 |
August | 559.01 | 260.68 | 298.34 | 717.51 | 149.59 | 0.00 | 0.00 | 0.00 |
September | 619.36 | 342.03 | 277.33 | 747.15 | 213.23 | 0.00 | 0.00 | 0.00 |
October | 561.04 | 346.40 | 214.64 | 617.43 | 284.71 | 0.00 | 0.00 | 0.00 |
November | 331.70 | 190.09 | 141.61 | 303.58 | 350.35 | 0.00 | 0.00 | 0.00 |
December | 347.06 | 224.59 | 122.46 | 325.71 | 429.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 489.48 | 239.41 | 250.07 | 535.84 | 278.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 326.53 | 128.10 | 122.46 | 279.06 | 149.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 619.36 | 346.40 | 366.14 | 747.15 | 429.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.18 | 41.04 | 98.14 | 53.35 | 528.81 | 0.00 | 0.00 | 0.00 |
February | 249.55 | 93.79 | 155.76 | 157.33 | 477.22 | 0.00 | 0.00 | 0.00 |
March | 349.68 | 118.03 | 231.65 | 268.47 | 409.72 | 0.00 | 0.00 | 0.00 |
April | 532.00 | 203.40 | 328.60 | 500.56 | 339.48 | 0.00 | 0.00 | 0.00 |
May | 684.56 | 278.10 | 406.46 | 729.15 | 258.50 | 0.00 | 0.00 | 0.00 |
June | 658.36 | 255.62 | 402.74 | 713.54 | 210.76 | 0.00 | 0.00 | 0.00 |
July | 813.31 | 427.52 | 385.79 | 964.04 | 195.05 | 0.00 | 0.00 | 0.00 |
August | 672.80 | 343.55 | 329.25 | 803.59 | 194.86 | 0.00 | 0.00 | 0.00 |
September | 547.90 | 262.89 | 285.00 | 608.87 | 255.57 | 0.00 | 0.00 | 0.00 |
October | 311.92 | 127.09 | 184.83 | 268.58 | 358.11 | 0.00 | 0.00 | 0.00 |
November | 155.33 | 43.81 | 111.52 | 72.81 | 467.61 | 0.00 | 0.00 | 0.00 |
December | 130.59 | 44.75 | 85.84 | 60.81 | 589.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 438.24 | 187.34 | 250.90 | 435.25 | 356.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.59 | 41.04 | 85.84 | 53.35 | 194.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 813.31 | 427.52 | 406.46 | 964.04 | 589.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.18 | 41.04 | 98.14 | 53.35 | 528.81 | 0.00 | 0.00 | 0.00 |
February | 249.55 | 93.79 | 155.76 | 157.33 | 477.22 | 0.00 | 0.00 | 0.00 |
March | 349.68 | 118.03 | 231.65 | 268.47 | 409.72 | 0.00 | 0.00 | 0.00 |
April | 532.00 | 203.40 | 328.60 | 500.56 | 339.48 | 0.00 | 0.00 | 0.00 |
May | 684.56 | 278.10 | 406.46 | 729.15 | 258.50 | 0.00 | 0.00 | 0.00 |
June | 658.36 | 255.62 | 402.74 | 713.54 | 210.76 | 0.00 | 0.00 | 0.00 |
July | 813.31 | 427.52 | 385.79 | 964.04 | 195.05 | 0.00 | 0.00 | 0.00 |
August | 672.80 | 343.55 | 329.25 | 803.59 | 194.86 | 0.00 | 0.00 | 0.00 |
September | 547.90 | 262.89 | 285.00 | 608.87 | 255.57 | 0.00 | 0.00 | 0.00 |
October | 311.92 | 127.09 | 184.83 | 268.58 | 358.11 | 0.00 | 0.00 | 0.00 |
November | 155.33 | 43.81 | 111.52 | 72.81 | 467.61 | 0.00 | 0.00 | 0.00 |
December | 130.59 | 44.75 | 85.84 | 60.81 | 589.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 438.24 | 187.34 | 250.90 | 435.25 | 356.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.59 | 41.04 | 85.84 | 53.35 | 194.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 813.31 | 427.52 | 406.46 | 964.04 | 589.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.18 | 41.04 | 98.14 | 53.34 | 528.80 | 0.00 | 0.00 | 0.00 |
February | 249.54 | 93.79 | 155.76 | 157.33 | 477.21 | 0.00 | 0.00 | 0.00 |
March | 349.67 | 118.02 | 231.65 | 268.47 | 409.72 | 0.00 | 0.00 | 0.00 |
April | 531.99 | 203.40 | 328.59 | 500.55 | 339.47 | 0.00 | 0.00 | 0.00 |
May | 684.55 | 278.09 | 406.45 | 729.14 | 258.50 | 0.00 | 0.00 | 0.00 |
June | 658.35 | 255.61 | 402.73 | 713.53 | 210.76 | 0.00 | 0.00 | 0.00 |
July | 813.30 | 427.51 | 385.79 | 964.03 | 195.04 | 0.00 | 0.00 | 0.00 |
August | 672.79 | 343.55 | 329.25 | 803.57 | 194.85 | 0.00 | 0.00 | 0.00 |
September | 547.89 | 262.89 | 285.00 | 608.86 | 255.56 | 0.00 | 0.00 | 0.00 |
October | 311.91 | 127.09 | 184.82 | 268.58 | 358.10 | 0.00 | 0.00 | 0.00 |
November | 155.33 | 43.81 | 111.52 | 72.81 | 467.61 | 0.00 | 0.00 | 0.00 |
December | 130.59 | 44.75 | 85.84 | 60.81 | 589.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 438.23 | 187.34 | 250.89 | 435.24 | 356.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.59 | 41.04 | 85.84 | 53.34 | 194.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 813.30 | 427.51 | 406.45 | 964.03 | 589.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.55 | 0.00 | 369.55 | 14.89 | 2092.79 | 0.00 | 0.00 | 0.00 |
February | 575.03 | 0.00 | 575.03 | 119.45 | 1860.32 | 0.00 | 0.00 | 0.00 |
March | 847.21 | 0.00 | 847.21 | 363.91 | 1536.68 | 0.00 | 0.00 | 0.00 |
April | 1198.89 | 4.25 | 1194.64 | 785.21 | 1221.84 | 0.00 | 0.00 | 0.00 |
May | 1542.67 | 45.83 | 1496.84 | 1252.25 | 991.64 | 0.00 | 0.00 | 0.00 |
June | 1622.08 | 107.12 | 1514.96 | 1446.62 | 764.86 | 0.00 | 0.00 | 0.00 |
July | 1541.70 | 120.88 | 1420.82 | 1546.02 | 688.78 | 0.00 | 0.00 | 0.00 |
August | 1248.01 | 33.74 | 1214.28 | 1272.46 | 675.02 | 0.00 | 0.00 | 0.00 |
September | 969.41 | 0.29 | 969.13 | 743.71 | 1011.93 | 0.00 | 0.00 | 0.00 |
October | 664.21 | 0.00 | 664.21 | 309.01 | 1355.89 | 0.00 | 0.00 | 0.00 |
November | 418.39 | 0.00 | 418.39 | 62.04 | 1717.30 | 0.00 | 0.00 | 0.00 |
December | 314.02 | 0.00 | 314.02 | 7.41 | 2123.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 944.42 | 26.20 | 918.22 | 663.61 | 1334.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 314.02 | 0.00 | 314.02 | 7.41 | 675.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1622.08 | 120.88 | 1514.96 | 1546.02 | 2123.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 395.87 | 100.37 | 295.51 | 142.55 | 1322.51 | 0.00 | 0.00 | 0.00 |
February | 726.39 | 257.81 | 468.58 | 471.90 | 1166.24 | 0.00 | 0.00 | 0.00 |
March | 1084.55 | 392.62 | 691.93 | 898.23 | 964.90 | 0.00 | 0.00 | 0.00 |
April | 1681.24 | 698.58 | 982.66 | 1674.20 | 774.63 | 0.00 | 0.00 | 0.00 |
May | 1788.99 | 621.99 | 1167.00 | 1871.87 | 648.44 | 0.00 | 0.00 | 0.00 |
June | 2142.51 | 932.22 | 1210.29 | 2393.48 | 510.77 | 0.00 | 0.00 | 0.00 |
July | 1995.18 | 895.55 | 1099.63 | 2326.26 | 449.26 | 0.00 | 0.00 | 0.00 |
August | 1960.98 | 981.00 | 979.99 | 2358.58 | 440.09 | 0.00 | 0.00 | 0.00 |
September | 1449.86 | 668.69 | 781.17 | 1566.48 | 633.13 | 0.00 | 0.00 | 0.00 |
October | 945.02 | 401.54 | 543.47 | 854.53 | 852.26 | 0.00 | 0.00 | 0.00 |
November | 463.19 | 130.76 | 332.43 | 248.73 | 1086.95 | 0.00 | 0.00 | 0.00 |
December | 379.92 | 122.31 | 257.61 | 176.98 | 1352.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1253.45 | 518.09 | 735.36 | 1252.60 | 848.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.92 | 100.37 | 257.61 | 142.55 | 440.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2142.51 | 981.00 | 1210.29 | 2393.48 | 1352.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1632.78 | 969.55 | 663.23 | 1411.36 | 1926.27 | 0.00 | 0.00 | 0.00 |
February | 2510.96 | 1554.32 | 956.64 | 2469.94 | 1762.04 | 0.00 | 0.00 | 0.00 |
March | 2701.07 | 1440.45 | 1260.62 | 2783.82 | 1530.49 | 0.00 | 0.00 | 0.00 |
April | 2851.81 | 1238.24 | 1613.57 | 3115.91 | 1286.28 | 0.00 | 0.00 | 0.00 |
May | 2607.62 | 776.84 | 1830.78 | 2888.48 | 1058.16 | 0.00 | 0.00 | 0.00 |
June | 2385.72 | 640.53 | 1745.18 | 2705.33 | 831.49 | 0.00 | 0.00 | 0.00 |
July | 2601.73 | 952.89 | 1648.84 | 3235.80 | 757.68 | 0.00 | 0.00 | 0.00 |
August | 2795.23 | 1303.46 | 1491.77 | 3582.71 | 737.02 | 0.00 | 0.00 | 0.00 |
September | 3097.00 | 1710.26 | 1386.73 | 3728.16 | 1039.55 | 0.00 | 0.00 | 0.00 |
October | 2805.36 | 1732.10 | 1073.26 | 3084.23 | 1358.06 | 0.00 | 0.00 | 0.00 |
November | 1658.62 | 950.53 | 708.09 | 1536.79 | 1635.76 | 0.00 | 0.00 | 0.00 |
December | 1735.39 | 1123.04 | 612.35 | 1647.32 | 1999.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2447.55 | 1197.14 | 1250.41 | 2683.26 | 1324.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1632.78 | 640.53 | 612.35 | 1411.36 | 737.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3097.00 | 1732.10 | 1830.78 | 3728.16 | 1999.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 417.55 | 123.13 | 294.42 | 176.36 | 1368.24 | 0.00 | 0.00 | 0.00 |
February | 748.63 | 281.36 | 467.28 | 517.87 | 1214.83 | 0.00 | 0.00 | 0.00 |
March | 1049.03 | 354.08 | 694.95 | 868.91 | 1016.59 | 0.00 | 0.00 | 0.00 |
April | 1595.98 | 610.21 | 985.78 | 1576.87 | 847.15 | 0.00 | 0.00 | 0.00 |
May | 2053.66 | 834.29 | 1219.37 | 2213.81 | 711.56 | 0.00 | 0.00 | 0.00 |
June | 1975.06 | 766.85 | 1208.21 | 2178.56 | 559.96 | 0.00 | 0.00 | 0.00 |
July | 2439.91 | 1282.54 | 1157.37 | 2922.83 | 528.21 | 0.00 | 0.00 | 0.00 |
August | 2018.39 | 1030.65 | 987.74 | 2454.47 | 510.28 | 0.00 | 0.00 | 0.00 |
September | 1643.67 | 788.67 | 855.00 | 1852.46 | 698.07 | 0.00 | 0.00 | 0.00 |
October | 935.75 | 381.27 | 554.48 | 853.88 | 905.51 | 0.00 | 0.00 | 0.00 |
November | 466.00 | 131.43 | 334.57 | 257.28 | 1124.19 | 0.00 | 0.00 | 0.00 |
December | 391.76 | 134.25 | 257.51 | 207.96 | 1405.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1314.71 | 562.02 | 752.69 | 1345.48 | 906.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 391.76 | 123.13 | 257.51 | 176.36 | 510.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2439.91 | 1282.54 | 1219.37 | 2922.83 | 1405.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.55 | 0.00 | 369.55 | 23.31 | 1928.63 | 0.00 | 0.00 | 0.00 |
February | 575.03 | 0.00 | 575.03 | 145.52 | 1698.60 | 0.00 | 0.00 | 0.00 |
March | 847.21 | 0.00 | 847.21 | 407.90 | 1391.69 | 0.00 | 0.00 | 0.00 |
April | 1198.89 | 4.25 | 1194.64 | 829.51 | 1126.28 | 0.00 | 0.00 | 0.00 |
May | 1542.67 | 45.83 | 1496.84 | 1284.36 | 933.94 | 0.00 | 0.00 | 0.00 |
June | 1622.08 | 107.12 | 1514.96 | 1457.72 | 736.96 | 0.00 | 0.00 | 0.00 |
July | 1541.70 | 120.88 | 1420.82 | 1548.08 | 670.62 | 0.00 | 0.00 | 0.00 |
August | 1248.01 | 33.74 | 1214.28 | 1278.82 | 653.28 | 0.00 | 0.00 | 0.00 |
September | 969.41 | 0.29 | 969.13 | 770.18 | 943.41 | 0.00 | 0.00 | 0.00 |
October | 664.21 | 0.00 | 664.21 | 352.09 | 1214.62 | 0.00 | 0.00 | 0.00 |
November | 418.39 | 0.00 | 418.39 | 83.56 | 1529.30 | 0.00 | 0.00 | 0.00 |
December | 314.02 | 0.00 | 314.02 | 15.70 | 1921.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 944.42 | 26.20 | 918.22 | 686.36 | 1226.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 314.02 | 0.00 | 314.02 | 15.70 | 653.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1622.08 | 120.88 | 1514.96 | 1548.08 | 1928.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 395.87 | 100.37 | 295.51 | 154.35 | 1224.54 | 0.00 | 0.00 | 0.00 |
February | 726.39 | 257.81 | 468.58 | 497.11 | 1073.16 | 0.00 | 0.00 | 0.00 |
March | 1084.55 | 392.62 | 691.93 | 924.71 | 890.63 | 0.00 | 0.00 | 0.00 |
April | 1681.24 | 698.58 | 982.66 | 1694.84 | 728.28 | 0.00 | 0.00 | 0.00 |
May | 1788.99 | 621.99 | 1167.00 | 1882.07 | 620.68 | 0.00 | 0.00 | 0.00 |
June | 2142.51 | 932.22 | 1210.29 | 2390.29 | 499.45 | 0.00 | 0.00 | 0.00 |
July | 1995.18 | 895.55 | 1099.63 | 2321.29 | 444.11 | 0.00 | 0.00 | 0.00 |
August | 1960.98 | 981.00 | 979.99 | 2355.64 | 433.48 | 0.00 | 0.00 | 0.00 |
September | 1449.86 | 668.69 | 781.17 | 1575.70 | 603.93 | 0.00 | 0.00 | 0.00 |
October | 945.02 | 401.54 | 543.47 | 878.51 | 782.93 | 0.00 | 0.00 | 0.00 |
November | 463.19 | 130.76 | 332.43 | 266.41 | 984.82 | 0.00 | 0.00 | 0.00 |
December | 379.92 | 122.31 | 257.61 | 190.84 | 1235.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1253.45 | 518.09 | 735.36 | 1264.84 | 792.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.92 | 100.37 | 257.61 | 154.35 | 433.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2142.51 | 981.00 | 1210.29 | 2390.29 | 1235.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1632.78 | 969.55 | 663.23 | 1448.51 | 1773.61 | 0.00 | 0.00 | 0.00 |
February | 2510.96 | 1554.32 | 956.64 | 2517.64 | 1618.30 | 0.00 | 0.00 | 0.00 |
March | 2701.07 | 1440.45 | 1260.62 | 2817.30 | 1410.57 | 0.00 | 0.00 | 0.00 |
April | 2851.81 | 1238.24 | 1613.57 | 3142.89 | 1206.47 | 0.00 | 0.00 | 0.00 |
May | 2607.62 | 776.84 | 1830.78 | 2904.89 | 1006.80 | 0.00 | 0.00 | 0.00 |
June | 2385.72 | 640.53 | 1745.18 | 2708.15 | 805.57 | 0.00 | 0.00 | 0.00 |
July | 2601.73 | 952.89 | 1648.84 | 3231.42 | 743.25 | 0.00 | 0.00 | 0.00 |
August | 2795.23 | 1303.46 | 1491.77 | 3581.41 | 720.14 | 0.00 | 0.00 | 0.00 |
September | 3097.00 | 1710.26 | 1386.73 | 3742.65 | 990.47 | 0.00 | 0.00 | 0.00 |
October | 2805.36 | 1732.10 | 1073.26 | 3117.78 | 1248.94 | 0.00 | 0.00 | 0.00 |
November | 1658.62 | 950.53 | 708.09 | 1574.87 | 1485.84 | 0.00 | 0.00 | 0.00 |
December | 1735.39 | 1123.04 | 612.35 | 1682.61 | 1825.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2447.55 | 1197.14 | 1250.41 | 2706.44 | 1234.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1632.78 | 640.53 | 612.35 | 1448.51 | 720.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3097.00 | 1732.10 | 1830.78 | 3742.65 | 1825.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 417.55 | 123.13 | 294.42 | 185.25 | 1269.83 | 0.00 | 0.00 | 0.00 |
February | 748.63 | 281.36 | 467.28 | 534.81 | 1129.17 | 0.00 | 0.00 | 0.00 |
March | 1049.03 | 354.08 | 694.95 | 886.56 | 946.57 | 0.00 | 0.00 | 0.00 |
April | 1595.98 | 610.21 | 985.78 | 1592.75 | 799.36 | 0.00 | 0.00 | 0.00 |
May | 2053.66 | 834.29 | 1219.37 | 2223.05 | 680.67 | 0.00 | 0.00 | 0.00 |
June | 1975.06 | 766.85 | 1208.21 | 2179.27 | 543.81 | 0.00 | 0.00 | 0.00 |
July | 2439.91 | 1282.54 | 1157.37 | 2918.24 | 518.84 | 0.00 | 0.00 | 0.00 |
August | 2018.39 | 1030.65 | 987.74 | 2453.77 | 499.41 | 0.00 | 0.00 | 0.00 |
September | 1643.67 | 788.67 | 855.00 | 1862.09 | 667.00 | 0.00 | 0.00 | 0.00 |
October | 935.75 | 381.27 | 554.48 | 871.50 | 840.12 | 0.00 | 0.00 | 0.00 |
November | 466.00 | 131.43 | 334.57 | 269.23 | 1035.63 | 0.00 | 0.00 | 0.00 |
December | 391.76 | 134.25 | 257.51 | 215.81 | 1298.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1314.71 | 562.02 | 752.69 | 1354.67 | 851.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 391.76 | 123.13 | 257.51 | 185.25 | 499.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2439.91 | 1282.54 | 1219.37 | 2918.24 | 1298.79 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197959E+09 | 0.00 | 0.197959E+09 | 3286265.20 | 0.130203E+10 |
February | 0.278220E+09 | 0.00 | 0.278220E+09 | 39663397.16 | 0.103513E+10 |
March | 0.453833E+09 | 0.00 | 0.453833E+09 | 0.165396E+09 | 0.935629E+09 |
April | 0.621504E+09 | 2204649.25 | 0.619299E+09 | 0.376933E+09 | 0.708951E+09 |
May | 0.826376E+09 | 24550284.83 | 0.801826E+09 | 0.654724E+09 | 0.565152E+09 |
June | 0.840885E+09 | 55528167.89 | 0.785357E+09 | 0.738684E+09 | 0.420943E+09 |
July | 0.825856E+09 | 64750568.16 | 0.761105E+09 | 0.816614E+09 | 0.387763E+09 |
August | 0.668536E+09 | 18072419.02 | 0.650464E+09 | 0.667755E+09 | 0.381950E+09 |
September | 0.502543E+09 | 148191.49 | 0.502395E+09 | 0.374189E+09 | 0.560242E+09 |
October | 0.355803E+09 | 0.00 | 0.355803E+09 | 0.141965E+09 | 0.821108E+09 |
November | 0.216891E+09 | 0.00 | 0.216891E+09 | 20001317.60 | 0.104702E+10 |
December | 0.168214E+09 | 0.00 | 0.168214E+09 | 763989.66 | 0.134460E+10 |
Annual Sum or Average | 0.595662E+10 | 0.165254E+09 | 0.579137E+10 | 0.399997E+10 | 0.951052E+10 |
Minimum of Months | 0.168214E+09 | 0.00 | 0.168214E+09 | 763989.66 | 0.381950E+09 |
Maximum of Months | 0.840885E+09 | 64750568.16 | 0.801826E+09 | 0.816614E+09 | 0.134460E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197956E+09 | 0.00 | 0.197956E+09 | 3285829.39 | 0.130203E+10 |
February | 0.278216E+09 | 0.00 | 0.278216E+09 | 39661063.67 | 0.103513E+10 |
March | 0.453826E+09 | 0.00 | 0.453826E+09 | 0.165390E+09 | 0.935629E+09 |
April | 0.621495E+09 | 2204600.78 | 0.619290E+09 | 0.376923E+09 | 0.708952E+09 |
May | 0.826364E+09 | 24549745.12 | 0.801814E+09 | 0.654709E+09 | 0.565152E+09 |
June | 0.840873E+09 | 55526947.17 | 0.785346E+09 | 0.738669E+09 | 0.420943E+09 |
July | 0.825845E+09 | 64749144.70 | 0.761095E+09 | 0.816600E+09 | 0.387762E+09 |
August | 0.668527E+09 | 18072021.72 | 0.650455E+09 | 0.667745E+09 | 0.381949E+09 |
September | 0.502536E+09 | 148188.23 | 0.502388E+09 | 0.374181E+09 | 0.560241E+09 |
October | 0.355798E+09 | 0.00 | 0.355798E+09 | 0.141961E+09 | 0.821108E+09 |
November | 0.216888E+09 | 0.00 | 0.216888E+09 | 20000004.77 | 0.104703E+10 |
December | 0.168211E+09 | 0.00 | 0.168211E+09 | 763870.14 | 0.134460E+10 |
Annual Sum or Average | 0.595653E+10 | 0.165251E+09 | 0.579128E+10 | 0.399989E+10 | 0.951053E+10 |
Minimum of Months | 0.168211E+09 | 0.00 | 0.168211E+09 | 763870.14 | 0.381949E+09 |
Maximum of Months | 0.840873E+09 | 64749144.70 | 0.801814E+09 | 0.816600E+09 | 0.134460E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197957E+09 | 0.00 | 0.197957E+09 | 3285974.66 | 0.130203E+10 |
February | 0.278217E+09 | 0.00 | 0.278217E+09 | 39661841.50 | 0.103513E+10 |
March | 0.453829E+09 | 0.00 | 0.453829E+09 | 0.165392E+09 | 0.935629E+09 |
April | 0.621498E+09 | 2204616.94 | 0.619293E+09 | 0.376926E+09 | 0.708952E+09 |
May | 0.826368E+09 | 24549925.03 | 0.801818E+09 | 0.654714E+09 | 0.565152E+09 |
June | 0.840877E+09 | 55527354.08 | 0.785349E+09 | 0.738674E+09 | 0.420943E+09 |
July | 0.825848E+09 | 64749619.19 | 0.761099E+09 | 0.816605E+09 | 0.387763E+09 |
August | 0.668530E+09 | 18072154.15 | 0.650458E+09 | 0.667748E+09 | 0.381949E+09 |
September | 0.502539E+09 | 148189.32 | 0.502391E+09 | 0.374184E+09 | 0.560241E+09 |
October | 0.355800E+09 | 0.00 | 0.355800E+09 | 0.141962E+09 | 0.821108E+09 |
November | 0.216889E+09 | 0.00 | 0.216889E+09 | 20000442.38 | 0.104702E+10 |
December | 0.168212E+09 | 0.00 | 0.168212E+09 | 763909.98 | 0.134460E+10 |
Annual Sum or Average | 0.595656E+10 | 0.165252E+09 | 0.579131E+10 | 0.399992E+10 | 0.951053E+10 |
Minimum of Months | 0.168212E+09 | 0.00 | 0.168212E+09 | 763909.98 | 0.381949E+09 |
Maximum of Months | 0.840877E+09 | 64749619.19 | 0.801818E+09 | 0.816605E+09 | 0.134460E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197956E+09 | 0.00 | 0.197956E+09 | 3285829.39 | 0.130203E+10 |
February | 0.278216E+09 | 0.00 | 0.278216E+09 | 39661063.67 | 0.103513E+10 |
March | 0.453826E+09 | 0.00 | 0.453826E+09 | 0.165390E+09 | 0.935629E+09 |
April | 0.621495E+09 | 2204600.78 | 0.619290E+09 | 0.376923E+09 | 0.708952E+09 |
May | 0.826364E+09 | 24549745.12 | 0.801814E+09 | 0.654709E+09 | 0.565152E+09 |
June | 0.840873E+09 | 55526947.17 | 0.785346E+09 | 0.738669E+09 | 0.420943E+09 |
July | 0.825845E+09 | 64749144.70 | 0.761095E+09 | 0.816600E+09 | 0.387762E+09 |
August | 0.668527E+09 | 18072021.72 | 0.650455E+09 | 0.667745E+09 | 0.381949E+09 |
September | 0.502536E+09 | 148188.23 | 0.502388E+09 | 0.374181E+09 | 0.560241E+09 |
October | 0.355798E+09 | 0.00 | 0.355798E+09 | 0.141961E+09 | 0.821108E+09 |
November | 0.216888E+09 | 0.00 | 0.216888E+09 | 20000004.77 | 0.104703E+10 |
December | 0.168211E+09 | 0.00 | 0.168211E+09 | 763870.14 | 0.134460E+10 |
Annual Sum or Average | 0.595653E+10 | 0.165251E+09 | 0.579128E+10 | 0.399989E+10 | 0.951053E+10 |
Minimum of Months | 0.168211E+09 | 0.00 | 0.168211E+09 | 763870.14 | 0.381949E+09 |
Maximum of Months | 0.840873E+09 | 64749144.70 | 0.801814E+09 | 0.816600E+09 | 0.134460E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197948E+09 | 0.00 | 0.197948E+09 | 3285769.59 | 0.130198E+10 |
February | 0.278205E+09 | 0.00 | 0.278205E+09 | 39659854.05 | 0.103509E+10 |
March | 0.453809E+09 | 0.00 | 0.453809E+09 | 0.165384E+09 | 0.935592E+09 |
April | 0.621471E+09 | 2204520.00 | 0.619267E+09 | 0.376909E+09 | 0.708923E+09 |
May | 0.826333E+09 | 24548845.61 | 0.801784E+09 | 0.654686E+09 | 0.565130E+09 |
June | 0.840841E+09 | 55524912.63 | 0.785316E+09 | 0.738641E+09 | 0.420926E+09 |
July | 0.825813E+09 | 64746772.26 | 0.761066E+09 | 0.816569E+09 | 0.387747E+09 |
August | 0.668502E+09 | 18071359.55 | 0.650430E+09 | 0.667720E+09 | 0.381934E+09 |
September | 0.502517E+09 | 148182.80 | 0.502369E+09 | 0.374167E+09 | 0.560218E+09 |
October | 0.355784E+09 | 0.00 | 0.355784E+09 | 0.141956E+09 | 0.821075E+09 |
November | 0.216879E+09 | 0.00 | 0.216879E+09 | 19999417.48 | 0.104698E+10 |
December | 0.168205E+09 | 0.00 | 0.168205E+09 | 763859.27 | 0.134454E+10 |
Annual Sum or Average | 0.595631E+10 | 0.165245E+09 | 0.579106E+10 | 0.399974E+10 | 0.951014E+10 |
Minimum of Months | 0.168205E+09 | 0.00 | 0.168205E+09 | 763859.27 | 0.381934E+09 |
Maximum of Months | 0.840841E+09 | 64746772.26 | 0.801784E+09 | 0.816569E+09 | 0.134454E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353439E+09 | 89608626.54 | 0.263831E+09 | 0.115179E+09 | 0.133076E+10 |
February | 0.585766E+09 | 0.207901E+09 | 0.377865E+09 | 0.357283E+09 | 0.103586E+10 |
March | 0.968296E+09 | 0.350531E+09 | 0.617764E+09 | 0.778969E+09 | 0.940217E+09 |
April | 0.145260E+10 | 0.603578E+09 | 0.849026E+09 | 0.143373E+10 | 0.714298E+09 |
May | 0.159722E+10 | 0.555318E+09 | 0.104191E+10 | 0.166358E+10 | 0.610966E+09 |
June | 0.185115E+10 | 0.805449E+09 | 0.104570E+10 | 0.207259E+10 | 0.458497E+09 |
July | 0.178131E+10 | 0.799556E+09 | 0.981757E+09 | 0.208458E+10 | 0.404022E+09 |
August | 0.175078E+10 | 0.875841E+09 | 0.874940E+09 | 0.211391E+10 | 0.389307E+09 |
September | 0.125269E+10 | 0.577752E+09 | 0.674939E+09 | 0.134697E+10 | 0.576993E+09 |
October | 0.843718E+09 | 0.358501E+09 | 0.485217E+09 | 0.743396E+09 | 0.832521E+09 |
November | 0.400204E+09 | 0.112982E+09 | 0.287222E+09 | 0.198018E+09 | 0.104835E+10 |
December | 0.339199E+09 | 0.109198E+09 | 0.230001E+09 | 0.145462E+09 | 0.134630E+10 |
Annual Sum or Average | 0.131764E+11 | 0.544622E+10 | 0.773017E+10 | 0.130537E+11 | 0.968808E+10 |
Minimum of Months | 0.339199E+09 | 89608626.54 | 0.230001E+09 | 0.115179E+09 | 0.389307E+09 |
Maximum of Months | 0.185115E+10 | 0.875841E+09 | 0.104570E+10 | 0.211391E+10 | 0.134630E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353439E+09 | 89608626.54 | 0.263831E+09 | 0.115179E+09 | 0.133076E+10 |
February | 0.585766E+09 | 0.207901E+09 | 0.377865E+09 | 0.357283E+09 | 0.103586E+10 |
March | 0.968296E+09 | 0.350531E+09 | 0.617764E+09 | 0.778969E+09 | 0.940217E+09 |
April | 0.145260E+10 | 0.603578E+09 | 0.849026E+09 | 0.143373E+10 | 0.714298E+09 |
May | 0.159722E+10 | 0.555318E+09 | 0.104191E+10 | 0.166358E+10 | 0.610966E+09 |
June | 0.185115E+10 | 0.805449E+09 | 0.104570E+10 | 0.207259E+10 | 0.458497E+09 |
July | 0.178131E+10 | 0.799556E+09 | 0.981757E+09 | 0.208458E+10 | 0.404022E+09 |
August | 0.175078E+10 | 0.875841E+09 | 0.874940E+09 | 0.211391E+10 | 0.389307E+09 |
September | 0.125269E+10 | 0.577752E+09 | 0.674939E+09 | 0.134697E+10 | 0.576993E+09 |
October | 0.843718E+09 | 0.358501E+09 | 0.485217E+09 | 0.743396E+09 | 0.832521E+09 |
November | 0.400204E+09 | 0.112982E+09 | 0.287222E+09 | 0.198018E+09 | 0.104835E+10 |
December | 0.339199E+09 | 0.109198E+09 | 0.230001E+09 | 0.145462E+09 | 0.134630E+10 |
Annual Sum or Average | 0.131764E+11 | 0.544622E+10 | 0.773017E+10 | 0.130537E+11 | 0.968808E+10 |
Minimum of Months | 0.339199E+09 | 89608626.54 | 0.230001E+09 | 0.115179E+09 | 0.389307E+09 |
Maximum of Months | 0.185115E+10 | 0.875841E+09 | 0.104570E+10 | 0.211391E+10 | 0.134630E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353433E+09 | 89606989.19 | 0.263826E+09 | 0.115177E+09 | 0.133073E+10 |
February | 0.585755E+09 | 0.207897E+09 | 0.377858E+09 | 0.357276E+09 | 0.103584E+10 |
March | 0.968278E+09 | 0.350525E+09 | 0.617753E+09 | 0.778954E+09 | 0.940200E+09 |
April | 0.145258E+10 | 0.603567E+09 | 0.849011E+09 | 0.143370E+10 | 0.714285E+09 |
May | 0.159719E+10 | 0.555308E+09 | 0.104189E+10 | 0.166355E+10 | 0.610955E+09 |
June | 0.185112E+10 | 0.805434E+09 | 0.104568E+10 | 0.207255E+10 | 0.458489E+09 |
July | 0.178128E+10 | 0.799541E+09 | 0.981739E+09 | 0.208454E+10 | 0.404014E+09 |
August | 0.175075E+10 | 0.875825E+09 | 0.874924E+09 | 0.211387E+10 | 0.389300E+09 |
September | 0.125267E+10 | 0.577741E+09 | 0.674926E+09 | 0.134695E+10 | 0.576982E+09 |
October | 0.843703E+09 | 0.358495E+09 | 0.485209E+09 | 0.743383E+09 | 0.832505E+09 |
November | 0.400197E+09 | 0.112980E+09 | 0.287217E+09 | 0.198014E+09 | 0.104833E+10 |
December | 0.339193E+09 | 0.109196E+09 | 0.229997E+09 | 0.145460E+09 | 0.134627E+10 |
Annual Sum or Average | 0.131761E+11 | 0.544612E+10 | 0.773003E+10 | 0.130534E+11 | 0.968790E+10 |
Minimum of Months | 0.339193E+09 | 89606989.19 | 0.229997E+09 | 0.115177E+09 | 0.389300E+09 |
Maximum of Months | 0.185112E+10 | 0.875825E+09 | 0.104568E+10 | 0.211387E+10 | 0.134627E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.874629E+09 | 0.519358E+09 | 0.355271E+09 | 0.747477E+09 | 0.110142E+10 |
February | 0.121488E+10 | 0.752025E+09 | 0.462854E+09 | 0.118883E+10 | 0.896998E+09 |
March | 0.144688E+10 | 0.771604E+09 | 0.675278E+09 | 0.148819E+10 | 0.866830E+09 |
April | 0.147836E+10 | 0.641891E+09 | 0.836465E+09 | 0.161363E+10 | 0.701664E+09 |
May | 0.139683E+10 | 0.416127E+09 | 0.980702E+09 | 0.155004E+10 | 0.587289E+09 |
June | 0.123674E+10 | 0.332046E+09 | 0.904693E+09 | 0.140241E+10 | 0.450058E+09 |
July | 0.139367E+10 | 0.510434E+09 | 0.883240E+09 | 0.173659E+10 | 0.414963E+09 |
August | 0.149732E+10 | 0.698224E+09 | 0.799101E+09 | 0.192187E+10 | 0.400680E+09 |
September | 0.160546E+10 | 0.886583E+09 | 0.718873E+09 | 0.193670E+10 | 0.552723E+09 |
October | 0.150275E+10 | 0.927832E+09 | 0.574913E+09 | 0.165381E+10 | 0.762589E+09 |
November | 0.859812E+09 | 0.492744E+09 | 0.367069E+09 | 0.786915E+09 | 0.908135E+09 |
December | 0.929596E+09 | 0.601578E+09 | 0.328019E+09 | 0.872426E+09 | 0.115096E+10 |
Annual Sum or Average | 0.154369E+11 | 0.755044E+10 | 0.788648E+10 | 0.168989E+11 | 0.879431E+10 |
Minimum of Months | 0.859812E+09 | 0.332046E+09 | 0.328019E+09 | 0.747477E+09 | 0.400680E+09 |
Maximum of Months | 0.160546E+10 | 0.927832E+09 | 0.980702E+09 | 0.193670E+10 | 0.115096E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.874623E+09 | 0.519354E+09 | 0.355269E+09 | 0.747469E+09 | 0.110142E+10 |
February | 0.121487E+10 | 0.752020E+09 | 0.462852E+09 | 0.118881E+10 | 0.896998E+09 |
March | 0.144687E+10 | 0.771598E+09 | 0.675274E+09 | 0.148817E+10 | 0.866830E+09 |
April | 0.147835E+10 | 0.641886E+09 | 0.836461E+09 | 0.161362E+10 | 0.701664E+09 |
May | 0.139682E+10 | 0.416124E+09 | 0.980697E+09 | 0.155003E+10 | 0.587289E+09 |
June | 0.123673E+10 | 0.332044E+09 | 0.904688E+09 | 0.140240E+10 | 0.450058E+09 |
July | 0.139367E+10 | 0.510430E+09 | 0.883236E+09 | 0.173658E+10 | 0.414962E+09 |
August | 0.149732E+10 | 0.698218E+09 | 0.799097E+09 | 0.192186E+10 | 0.400680E+09 |
September | 0.160545E+10 | 0.886576E+09 | 0.718869E+09 | 0.193668E+10 | 0.552723E+09 |
October | 0.150274E+10 | 0.927825E+09 | 0.574910E+09 | 0.165380E+10 | 0.762588E+09 |
November | 0.859806E+09 | 0.492740E+09 | 0.367066E+09 | 0.786908E+09 | 0.908135E+09 |
December | 0.929590E+09 | 0.601573E+09 | 0.328017E+09 | 0.872418E+09 | 0.115096E+10 |
Annual Sum or Average | 0.154368E+11 | 0.755039E+10 | 0.788644E+10 | 0.168988E+11 | 0.879431E+10 |
Minimum of Months | 0.859806E+09 | 0.332044E+09 | 0.328017E+09 | 0.747469E+09 | 0.400680E+09 |
Maximum of Months | 0.160545E+10 | 0.927825E+09 | 0.980697E+09 | 0.193668E+10 | 0.115096E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.874629E+09 | 0.519358E+09 | 0.355271E+09 | 0.747477E+09 | 0.110142E+10 |
February | 0.121488E+10 | 0.752025E+09 | 0.462854E+09 | 0.118883E+10 | 0.896998E+09 |
March | 0.144688E+10 | 0.771604E+09 | 0.675278E+09 | 0.148819E+10 | 0.866830E+09 |
April | 0.147836E+10 | 0.641891E+09 | 0.836465E+09 | 0.161363E+10 | 0.701664E+09 |
May | 0.139683E+10 | 0.416127E+09 | 0.980702E+09 | 0.155004E+10 | 0.587289E+09 |
June | 0.123674E+10 | 0.332046E+09 | 0.904693E+09 | 0.140241E+10 | 0.450058E+09 |
July | 0.139367E+10 | 0.510434E+09 | 0.883240E+09 | 0.173659E+10 | 0.414963E+09 |
August | 0.149732E+10 | 0.698224E+09 | 0.799101E+09 | 0.192187E+10 | 0.400680E+09 |
September | 0.160546E+10 | 0.886583E+09 | 0.718873E+09 | 0.193670E+10 | 0.552723E+09 |
October | 0.150275E+10 | 0.927832E+09 | 0.574913E+09 | 0.165381E+10 | 0.762589E+09 |
November | 0.859812E+09 | 0.492744E+09 | 0.367069E+09 | 0.786915E+09 | 0.908135E+09 |
December | 0.929596E+09 | 0.601578E+09 | 0.328019E+09 | 0.872426E+09 | 0.115096E+10 |
Annual Sum or Average | 0.154369E+11 | 0.755044E+10 | 0.788648E+10 | 0.168989E+11 | 0.879431E+10 |
Minimum of Months | 0.859812E+09 | 0.332046E+09 | 0.328019E+09 | 0.747477E+09 | 0.400680E+09 |
Maximum of Months | 0.160546E+10 | 0.927832E+09 | 0.980702E+09 | 0.193670E+10 | 0.115096E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.874623E+09 | 0.519354E+09 | 0.355269E+09 | 0.747469E+09 | 0.110142E+10 |
February | 0.121487E+10 | 0.752020E+09 | 0.462852E+09 | 0.118881E+10 | 0.896998E+09 |
March | 0.144687E+10 | 0.771598E+09 | 0.675274E+09 | 0.148817E+10 | 0.866830E+09 |
April | 0.147835E+10 | 0.641886E+09 | 0.836461E+09 | 0.161362E+10 | 0.701664E+09 |
May | 0.139682E+10 | 0.416124E+09 | 0.980697E+09 | 0.155003E+10 | 0.587289E+09 |
June | 0.123673E+10 | 0.332044E+09 | 0.904688E+09 | 0.140240E+10 | 0.450058E+09 |
July | 0.139367E+10 | 0.510430E+09 | 0.883236E+09 | 0.173658E+10 | 0.414962E+09 |
August | 0.149732E+10 | 0.698218E+09 | 0.799097E+09 | 0.192186E+10 | 0.400680E+09 |
September | 0.160545E+10 | 0.886576E+09 | 0.718869E+09 | 0.193668E+10 | 0.552723E+09 |
October | 0.150274E+10 | 0.927825E+09 | 0.574910E+09 | 0.165380E+10 | 0.762588E+09 |
November | 0.859806E+09 | 0.492740E+09 | 0.367066E+09 | 0.786908E+09 | 0.908135E+09 |
December | 0.929590E+09 | 0.601573E+09 | 0.328017E+09 | 0.872418E+09 | 0.115096E+10 |
Annual Sum or Average | 0.154368E+11 | 0.755039E+10 | 0.788644E+10 | 0.168988E+11 | 0.879431E+10 |
Minimum of Months | 0.859806E+09 | 0.332044E+09 | 0.328017E+09 | 0.747469E+09 | 0.400680E+09 |
Maximum of Months | 0.160545E+10 | 0.927825E+09 | 0.980697E+09 | 0.193668E+10 | 0.115096E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.874591E+09 | 0.519335E+09 | 0.355256E+09 | 0.747443E+09 | 0.110138E+10 |
February | 0.121483E+10 | 0.751992E+09 | 0.462834E+09 | 0.118877E+10 | 0.896961E+09 |
March | 0.144682E+10 | 0.771570E+09 | 0.675249E+09 | 0.148812E+10 | 0.866795E+09 |
April | 0.147829E+10 | 0.641863E+09 | 0.836429E+09 | 0.161356E+10 | 0.701635E+09 |
May | 0.139677E+10 | 0.416108E+09 | 0.980660E+09 | 0.154997E+10 | 0.587265E+09 |
June | 0.123669E+10 | 0.332032E+09 | 0.904654E+09 | 0.140235E+10 | 0.450040E+09 |
July | 0.139361E+10 | 0.510412E+09 | 0.883203E+09 | 0.173652E+10 | 0.414946E+09 |
August | 0.149726E+10 | 0.698193E+09 | 0.799067E+09 | 0.192179E+10 | 0.400664E+09 |
September | 0.160539E+10 | 0.886544E+09 | 0.718842E+09 | 0.193661E+10 | 0.552701E+09 |
October | 0.150268E+10 | 0.927791E+09 | 0.574888E+09 | 0.165374E+10 | 0.762558E+09 |
November | 0.859775E+09 | 0.492722E+09 | 0.367053E+09 | 0.786880E+09 | 0.908098E+09 |
December | 0.929556E+09 | 0.601551E+09 | 0.328004E+09 | 0.872387E+09 | 0.115092E+10 |
Annual Sum or Average | 0.154363E+11 | 0.755011E+10 | 0.788614E+10 | 0.168981E+11 | 0.879395E+10 |
Minimum of Months | 0.859775E+09 | 0.332032E+09 | 0.328004E+09 | 0.747443E+09 | 0.400664E+09 |
Maximum of Months | 0.160539E+10 | 0.927791E+09 | 0.980660E+09 | 0.193661E+10 | 0.115092E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.372792E+09 | 0.109930E+09 | 0.262863E+09 | 0.142881E+09 | 0.141636E+10 |
February | 0.603705E+09 | 0.226889E+09 | 0.376816E+09 | 0.380615E+09 | 0.115449E+10 |
March | 0.936582E+09 | 0.316121E+09 | 0.620460E+09 | 0.719078E+09 | 0.109741E+10 |
April | 0.137894E+10 | 0.527223E+09 | 0.851720E+09 | 0.129744E+10 | 0.879927E+09 |
May | 0.183353E+10 | 0.744862E+09 | 0.108866E+10 | 0.195296E+10 | 0.692375E+09 |
June | 0.170647E+10 | 0.662564E+09 | 0.104390E+10 | 0.184949E+10 | 0.546293E+09 |
July | 0.217838E+10 | 0.114507E+10 | 0.103331E+10 | 0.258210E+10 | 0.522417E+09 |
August | 0.180204E+10 | 0.920173E+09 | 0.881866E+09 | 0.215233E+10 | 0.521904E+09 |
September | 0.142015E+10 | 0.681418E+09 | 0.738730E+09 | 0.157819E+10 | 0.662436E+09 |
October | 0.835444E+09 | 0.340404E+09 | 0.495041E+09 | 0.719365E+09 | 0.959156E+09 |
November | 0.402625E+09 | 0.113557E+09 | 0.289068E+09 | 0.188725E+09 | 0.121206E+10 |
December | 0.349767E+09 | 0.119856E+09 | 0.229911E+09 | 0.162883E+09 | 0.157973E+10 |
Annual Sum or Average | 0.138204E+11 | 0.590806E+10 | 0.791235E+10 | 0.137261E+11 | 0.112446E+11 |
Minimum of Months | 0.349767E+09 | 0.109930E+09 | 0.229911E+09 | 0.142881E+09 | 0.521904E+09 |
Maximum of Months | 0.217838E+10 | 0.114507E+10 | 0.108866E+10 | 0.258210E+10 | 0.157973E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.372792E+09 | 0.109930E+09 | 0.262863E+09 | 0.142881E+09 | 0.141636E+10 |
February | 0.603705E+09 | 0.226889E+09 | 0.376816E+09 | 0.380615E+09 | 0.115449E+10 |
March | 0.936582E+09 | 0.316121E+09 | 0.620460E+09 | 0.719078E+09 | 0.109741E+10 |
April | 0.137894E+10 | 0.527223E+09 | 0.851720E+09 | 0.129744E+10 | 0.879927E+09 |
May | 0.183353E+10 | 0.744862E+09 | 0.108866E+10 | 0.195296E+10 | 0.692375E+09 |
June | 0.170647E+10 | 0.662564E+09 | 0.104390E+10 | 0.184949E+10 | 0.546293E+09 |
July | 0.217838E+10 | 0.114507E+10 | 0.103331E+10 | 0.258210E+10 | 0.522417E+09 |
August | 0.180204E+10 | 0.920173E+09 | 0.881866E+09 | 0.215233E+10 | 0.521904E+09 |
September | 0.142015E+10 | 0.681418E+09 | 0.738730E+09 | 0.157819E+10 | 0.662436E+09 |
October | 0.835444E+09 | 0.340404E+09 | 0.495041E+09 | 0.719365E+09 | 0.959156E+09 |
November | 0.402625E+09 | 0.113557E+09 | 0.289068E+09 | 0.188725E+09 | 0.121206E+10 |
December | 0.349767E+09 | 0.119856E+09 | 0.229911E+09 | 0.162883E+09 | 0.157973E+10 |
Annual Sum or Average | 0.138204E+11 | 0.590806E+10 | 0.791235E+10 | 0.137261E+11 | 0.112446E+11 |
Minimum of Months | 0.349767E+09 | 0.109930E+09 | 0.229911E+09 | 0.142881E+09 | 0.521904E+09 |
Maximum of Months | 0.217838E+10 | 0.114507E+10 | 0.108866E+10 | 0.258210E+10 | 0.157973E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.372786E+09 | 0.109928E+09 | 0.262858E+09 | 0.142878E+09 | 0.141634E+10 |
February | 0.603694E+09 | 0.226885E+09 | 0.376809E+09 | 0.380608E+09 | 0.115447E+10 |
March | 0.936565E+09 | 0.316116E+09 | 0.620449E+09 | 0.719065E+09 | 0.109739E+10 |
April | 0.137892E+10 | 0.527213E+09 | 0.851705E+09 | 0.129742E+10 | 0.879911E+09 |
May | 0.183349E+10 | 0.744849E+09 | 0.108864E+10 | 0.195293E+10 | 0.692363E+09 |
June | 0.170644E+10 | 0.662552E+09 | 0.104388E+10 | 0.184946E+10 | 0.546283E+09 |
July | 0.217834E+10 | 0.114505E+10 | 0.103329E+10 | 0.258205E+10 | 0.522408E+09 |
August | 0.180201E+10 | 0.920156E+09 | 0.881850E+09 | 0.215229E+10 | 0.521895E+09 |
September | 0.142012E+10 | 0.681405E+09 | 0.738717E+09 | 0.157816E+10 | 0.662424E+09 |
October | 0.835429E+09 | 0.340398E+09 | 0.495032E+09 | 0.719351E+09 | 0.959139E+09 |
November | 0.402618E+09 | 0.113555E+09 | 0.289063E+09 | 0.188721E+09 | 0.121204E+10 |
December | 0.349761E+09 | 0.119854E+09 | 0.229907E+09 | 0.162880E+09 | 0.157970E+10 |
Annual Sum or Average | 0.138202E+11 | 0.590796E+10 | 0.791221E+10 | 0.137258E+11 | 0.112443E+11 |
Minimum of Months | 0.349761E+09 | 0.109928E+09 | 0.229907E+09 | 0.142878E+09 | 0.521895E+09 |
Maximum of Months | 0.217834E+10 | 0.114505E+10 | 0.108864E+10 | 0.258205E+10 | 0.157970E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.989797E+09 | 0.00 | 0.989797E+09 | 39873043.04 | 0.560534E+10 |
February | 0.139110E+10 | 0.00 | 0.139110E+10 | 0.288966E+09 | 0.450048E+10 |
March | 0.226917E+10 | 0.00 | 0.226917E+10 | 0.974699E+09 | 0.411586E+10 |
April | 0.310752E+10 | 11023316.49 | 0.309650E+10 | 0.203526E+10 | 0.316701E+10 |
May | 0.413188E+10 | 0.122752E+09 | 0.400913E+10 | 0.335402E+10 | 0.265601E+10 |
June | 0.420442E+10 | 0.277643E+09 | 0.392678E+10 | 0.374963E+10 | 0.198251E+10 |
July | 0.412928E+10 | 0.323755E+09 | 0.380552E+10 | 0.414086E+10 | 0.184483E+10 |
August | 0.334268E+10 | 90362670.95 | 0.325232E+10 | 0.340817E+10 | 0.180798E+10 |
September | 0.251272E+10 | 740962.17 | 0.251198E+10 | 0.192769E+10 | 0.262292E+10 |
October | 0.177902E+10 | 0.00 | 0.177902E+10 | 0.827655E+09 | 0.363161E+10 |
November | 0.108446E+10 | 0.00 | 0.108446E+10 | 0.160818E+09 | 0.445125E+10 |
December | 0.841072E+09 | 0.00 | 0.841072E+09 | 19852536.83 | 0.568767E+10 |
Annual Sum or Average | 0.297831E+11 | 0.826277E+09 | 0.289568E+11 | 0.209275E+11 | 0.420735E+11 |
Minimum of Months | 0.841072E+09 | 0.00 | 0.841072E+09 | 19852536.83 | 0.180798E+10 |
Maximum of Months | 0.420442E+10 | 0.323755E+09 | 0.400913E+10 | 0.414086E+10 | 0.568767E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106031E+10 | 0.268823E+09 | 0.791484E+09 | 0.381803E+09 | 0.354222E+10 |
February | 0.175728E+10 | 0.623696E+09 | 0.113358E+10 | 0.114162E+10 | 0.282138E+10 |
March | 0.290486E+10 | 0.105158E+10 | 0.185327E+10 | 0.240583E+10 | 0.258440E+10 |
April | 0.435777E+10 | 0.181072E+10 | 0.254705E+10 | 0.433952E+10 | 0.200785E+10 |
May | 0.479162E+10 | 0.166594E+10 | 0.312568E+10 | 0.501362E+10 | 0.173679E+10 |
June | 0.555340E+10 | 0.241632E+10 | 0.313707E+10 | 0.620391E+10 | 0.132392E+10 |
July | 0.534388E+10 | 0.239864E+10 | 0.294524E+10 | 0.623066E+10 | 0.120330E+10 |
August | 0.525229E+10 | 0.262750E+10 | 0.262479E+10 | 0.631722E+10 | 0.117873E+10 |
September | 0.375803E+10 | 0.173324E+10 | 0.202480E+10 | 0.406032E+10 | 0.164108E+10 |
October | 0.253113E+10 | 0.107549E+10 | 0.145564E+10 | 0.228877E+10 | 0.228269E+10 |
November | 0.120060E+10 | 0.338941E+09 | 0.861658E+09 | 0.644706E+09 | 0.281738E+10 |
December | 0.101759E+10 | 0.327591E+09 | 0.689996E+09 | 0.474022E+09 | 0.362345E+10 |
Annual Sum or Average | 0.395288E+11 | 0.163385E+11 | 0.231903E+11 | 0.395020E+11 | 0.267632E+11 |
Minimum of Months | 0.101759E+10 | 0.268823E+09 | 0.689996E+09 | 0.381803E+09 | 0.117873E+10 |
Maximum of Months | 0.555340E+10 | 0.262750E+10 | 0.313707E+10 | 0.631722E+10 | 0.362345E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.437323E+10 | 0.259684E+10 | 0.177639E+10 | 0.378019E+10 | 0.515932E+10 |
February | 0.607451E+10 | 0.376021E+10 | 0.231431E+10 | 0.597529E+10 | 0.426274E+10 |
March | 0.723454E+10 | 0.385810E+10 | 0.337644E+10 | 0.745618E+10 | 0.409926E+10 |
April | 0.739190E+10 | 0.320952E+10 | 0.418238E+10 | 0.807645E+10 | 0.333403E+10 |
May | 0.698424E+10 | 0.208068E+10 | 0.490357E+10 | 0.773651E+10 | 0.283417E+10 |
June | 0.618378E+10 | 0.166027E+10 | 0.452351E+10 | 0.701223E+10 | 0.215523E+10 |
July | 0.696847E+10 | 0.255222E+10 | 0.441624E+10 | 0.866676E+10 | 0.202936E+10 |
August | 0.748674E+10 | 0.349119E+10 | 0.399555E+10 | 0.959593E+10 | 0.197403E+10 |
September | 0.802742E+10 | 0.443301E+10 | 0.359441E+10 | 0.966340E+10 | 0.269453E+10 |
October | 0.751387E+10 | 0.463926E+10 | 0.287461E+10 | 0.826081E+10 | 0.363742E+10 |
November | 0.429914E+10 | 0.246377E+10 | 0.183537E+10 | 0.398335E+10 | 0.423990E+10 |
December | 0.464807E+10 | 0.300795E+10 | 0.164012E+10 | 0.441219E+10 | 0.535591E+10 |
Annual Sum or Average | 0.771859E+11 | 0.377530E+11 | 0.394329E+11 | 0.846193E+11 | 0.417759E+11 |
Minimum of Months | 0.429914E+10 | 0.166027E+10 | 0.164012E+10 | 0.378019E+10 | 0.197403E+10 |
Maximum of Months | 0.802742E+10 | 0.463926E+10 | 0.490357E+10 | 0.966340E+10 | 0.535591E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111837E+10 | 0.329786E+09 | 0.788580E+09 | 0.472355E+09 | 0.366470E+10 |
February | 0.181110E+10 | 0.680661E+09 | 0.113044E+10 | 0.125283E+10 | 0.293891E+10 |
March | 0.280972E+10 | 0.948354E+09 | 0.186136E+10 | 0.232730E+10 | 0.272282E+10 |
April | 0.413679E+10 | 0.158165E+10 | 0.255513E+10 | 0.408725E+10 | 0.219582E+10 |
May | 0.550052E+10 | 0.223456E+10 | 0.326596E+10 | 0.592948E+10 | 0.190584E+10 |
June | 0.511935E+10 | 0.198767E+10 | 0.313167E+10 | 0.564684E+10 | 0.145142E+10 |
July | 0.653506E+10 | 0.343516E+10 | 0.309990E+10 | 0.782852E+10 | 0.141477E+10 |
August | 0.540606E+10 | 0.276049E+10 | 0.264557E+10 | 0.657405E+10 | 0.136673E+10 |
September | 0.426040E+10 | 0.204423E+10 | 0.221617E+10 | 0.480159E+10 | 0.180940E+10 |
October | 0.250631E+10 | 0.102120E+10 | 0.148511E+10 | 0.228703E+10 | 0.242531E+10 |
November | 0.120786E+10 | 0.340668E+09 | 0.867196E+09 | 0.666872E+09 | 0.291390E+10 |
December | 0.104929E+10 | 0.359565E+09 | 0.689726E+09 | 0.557008E+09 | 0.376520E+10 |
Annual Sum or Average | 0.414608E+11 | 0.177240E+11 | 0.237368E+11 | 0.424311E+11 | 0.285748E+11 |
Minimum of Months | 0.104929E+10 | 0.329786E+09 | 0.689726E+09 | 0.472355E+09 | 0.136673E+10 |
Maximum of Months | 0.653506E+10 | 0.343516E+10 | 0.326596E+10 | 0.782852E+10 | 0.376520E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.989797E+09 | 0.00 | 0.989797E+09 | 62443136.44 | 0.516565E+10 |
February | 0.139110E+10 | 0.00 | 0.139110E+10 | 0.352050E+09 | 0.410925E+10 |
March | 0.226917E+10 | 0.00 | 0.226917E+10 | 0.109252E+10 | 0.372749E+10 |
April | 0.310752E+10 | 11023316.49 | 0.309650E+10 | 0.215008E+10 | 0.291932E+10 |
May | 0.413188E+10 | 0.122752E+09 | 0.400913E+10 | 0.344003E+10 | 0.250148E+10 |
June | 0.420442E+10 | 0.277643E+09 | 0.392678E+10 | 0.377840E+10 | 0.191020E+10 |
July | 0.412928E+10 | 0.323755E+09 | 0.380552E+10 | 0.414638E+10 | 0.179618E+10 |
August | 0.334268E+10 | 90362670.95 | 0.325232E+10 | 0.342519E+10 | 0.174975E+10 |
September | 0.251272E+10 | 740962.17 | 0.251198E+10 | 0.199631E+10 | 0.244531E+10 |
October | 0.177902E+10 | 0.00 | 0.177902E+10 | 0.943043E+09 | 0.325325E+10 |
November | 0.108446E+10 | 0.00 | 0.108446E+10 | 0.216590E+09 | 0.396394E+10 |
December | 0.841072E+09 | 0.00 | 0.841072E+09 | 42048691.61 | 0.514749E+10 |
Annual Sum or Average | 0.297831E+11 | 0.826277E+09 | 0.289568E+11 | 0.216451E+11 | 0.386893E+11 |
Minimum of Months | 0.841072E+09 | 0.00 | 0.841072E+09 | 42048691.61 | 0.174975E+10 |
Maximum of Months | 0.420442E+10 | 0.323755E+09 | 0.400913E+10 | 0.414638E+10 | 0.516565E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106031E+10 | 0.268823E+09 | 0.791484E+09 | 0.413414E+09 | 0.327981E+10 |
February | 0.175728E+10 | 0.623696E+09 | 0.113358E+10 | 0.120260E+10 | 0.259618E+10 |
March | 0.290486E+10 | 0.105158E+10 | 0.185327E+10 | 0.247674E+10 | 0.238546E+10 |
April | 0.435777E+10 | 0.181072E+10 | 0.254705E+10 | 0.439302E+10 | 0.188769E+10 |
May | 0.479162E+10 | 0.166594E+10 | 0.312568E+10 | 0.504095E+10 | 0.166242E+10 |
June | 0.555340E+10 | 0.241632E+10 | 0.313707E+10 | 0.619562E+10 | 0.129457E+10 |
July | 0.534388E+10 | 0.239864E+10 | 0.294524E+10 | 0.621733E+10 | 0.118950E+10 |
August | 0.525229E+10 | 0.262750E+10 | 0.262479E+10 | 0.630935E+10 | 0.116103E+10 |
September | 0.375803E+10 | 0.173324E+10 | 0.202480E+10 | 0.408422E+10 | 0.156539E+10 |
October | 0.253113E+10 | 0.107549E+10 | 0.145564E+10 | 0.235301E+10 | 0.209700E+10 |
November | 0.120060E+10 | 0.338941E+09 | 0.861658E+09 | 0.690532E+09 | 0.255266E+10 |
December | 0.101759E+10 | 0.327591E+09 | 0.689996E+09 | 0.511152E+09 | 0.330865E+10 |
Annual Sum or Average | 0.395288E+11 | 0.163385E+11 | 0.231903E+11 | 0.398880E+11 | 0.249804E+11 |
Minimum of Months | 0.101759E+10 | 0.268823E+09 | 0.689996E+09 | 0.413414E+09 | 0.116103E+10 |
Maximum of Months | 0.555340E+10 | 0.262750E+10 | 0.313707E+10 | 0.630935E+10 | 0.330865E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.437323E+10 | 0.259684E+10 | 0.177639E+10 | 0.387970E+10 | 0.475044E+10 |
February | 0.607451E+10 | 0.376021E+10 | 0.231431E+10 | 0.609067E+10 | 0.391500E+10 |
March | 0.723454E+10 | 0.385810E+10 | 0.337644E+10 | 0.754585E+10 | 0.377807E+10 |
April | 0.739190E+10 | 0.320952E+10 | 0.418238E+10 | 0.814636E+10 | 0.312717E+10 |
May | 0.698424E+10 | 0.208068E+10 | 0.490357E+10 | 0.778046E+10 | 0.269663E+10 |
June | 0.618378E+10 | 0.166027E+10 | 0.452351E+10 | 0.701952E+10 | 0.208803E+10 |
July | 0.696847E+10 | 0.255222E+10 | 0.441624E+10 | 0.865504E+10 | 0.199072E+10 |
August | 0.748674E+10 | 0.349119E+10 | 0.399555E+10 | 0.959244E+10 | 0.192883E+10 |
September | 0.802742E+10 | 0.443301E+10 | 0.359441E+10 | 0.970096E+10 | 0.256730E+10 |
October | 0.751387E+10 | 0.463926E+10 | 0.287461E+10 | 0.835065E+10 | 0.334517E+10 |
November | 0.429914E+10 | 0.246377E+10 | 0.183537E+10 | 0.408207E+10 | 0.385129E+10 |
December | 0.464807E+10 | 0.300795E+10 | 0.164012E+10 | 0.450669E+10 | 0.488879E+10 |
Annual Sum or Average | 0.771859E+11 | 0.377530E+11 | 0.394329E+11 | 0.853504E+11 | 0.389274E+11 |
Minimum of Months | 0.429914E+10 | 0.166027E+10 | 0.164012E+10 | 0.387970E+10 | 0.192883E+10 |
Maximum of Months | 0.802742E+10 | 0.463926E+10 | 0.490357E+10 | 0.970096E+10 | 0.488879E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111837E+10 | 0.329786E+09 | 0.788580E+09 | 0.496177E+09 | 0.340111E+10 |
February | 0.181110E+10 | 0.680661E+09 | 0.113044E+10 | 0.129382E+10 | 0.273170E+10 |
March | 0.280972E+10 | 0.948354E+09 | 0.186136E+10 | 0.237456E+10 | 0.253530E+10 |
April | 0.413679E+10 | 0.158165E+10 | 0.255513E+10 | 0.412841E+10 | 0.207194E+10 |
May | 0.550052E+10 | 0.223456E+10 | 0.326596E+10 | 0.595420E+10 | 0.182312E+10 |
June | 0.511935E+10 | 0.198767E+10 | 0.313167E+10 | 0.564866E+10 | 0.140956E+10 |
July | 0.653506E+10 | 0.343516E+10 | 0.309990E+10 | 0.781621E+10 | 0.138966E+10 |
August | 0.540606E+10 | 0.276049E+10 | 0.264557E+10 | 0.657217E+10 | 0.133762E+10 |
September | 0.426040E+10 | 0.204423E+10 | 0.221617E+10 | 0.482653E+10 | 0.172885E+10 |
October | 0.250631E+10 | 0.102120E+10 | 0.148511E+10 | 0.233422E+10 | 0.225017E+10 |
November | 0.120786E+10 | 0.340668E+09 | 0.867196E+09 | 0.697854E+09 | 0.268436E+10 |
December | 0.104929E+10 | 0.359565E+09 | 0.689726E+09 | 0.578027E+09 | 0.347869E+10 |
Annual Sum or Average | 0.414608E+11 | 0.177240E+11 | 0.237368E+11 | 0.427208E+11 | 0.268421E+11 |
Minimum of Months | 0.104929E+10 | 0.329786E+09 | 0.689726E+09 | 0.496177E+09 | 0.133762E+10 |
Maximum of Months | 0.653506E+10 | 0.343516E+10 | 0.326596E+10 | 0.781621E+10 | 0.347869E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.13 | 2430.60 | 369.54 | 0.00 | 369.54 | 0.00 | 0.00 |
February | 81.97 | 2139.39 | 575.01 | 0.00 | 575.01 | 0.00 | 0.00 |
March | 308.75 | 1746.61 | 847.19 | 0.00 | 847.19 | 0.00 | 0.00 |
April | 727.09 | 1367.57 | 1198.87 | 4.25 | 1194.61 | 0.00 | 0.00 |
May | 1222.20 | 1055.01 | 1542.64 | 45.83 | 1496.81 | 0.00 | 0.00 |
June | 1424.90 | 812.00 | 1622.05 | 107.11 | 1514.94 | 0.00 | 0.00 |
July | 1524.41 | 723.86 | 1541.67 | 120.87 | 1420.80 | 0.00 | 0.00 |
August | 1246.53 | 713.01 | 1247.99 | 33.74 | 1214.26 | 0.00 | 0.00 |
September | 721.80 | 1080.70 | 969.40 | 0.29 | 969.11 | 0.00 | 0.00 |
October | 265.01 | 1532.82 | 664.20 | 0.00 | 664.20 | 0.00 | 0.00 |
November | 38.58 | 2019.71 | 418.38 | 0.00 | 418.38 | 0.00 | 0.00 |
December | 1.43 | 2510.06 | 314.01 | 0.00 | 314.01 | 0.00 | 0.00 |
Annual Sum or Average | 634.18 | 1507.87 | 944.40 | 26.20 | 918.20 | 0.00 | 0.00 |
Minimum of Months | 1.43 | 713.01 | 314.01 | 0.00 | 314.01 | 0.00 | 0.00 |
Maximum of Months | 1524.41 | 2510.06 | 1622.05 | 120.87 | 1514.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 129.01 | 1490.53 | 395.88 | 100.37 | 295.51 | 0.00 | 0.00 |
February | 443.06 | 1284.54 | 726.39 | 257.81 | 468.58 | 0.00 | 0.00 |
March | 872.50 | 1053.10 | 1084.55 | 392.62 | 691.94 | 0.00 | 0.00 |
April | 1659.40 | 826.73 | 1681.24 | 698.58 | 982.66 | 0.00 | 0.00 |
May | 1863.32 | 684.32 | 1788.99 | 621.99 | 1167.00 | 0.00 | 0.00 |
June | 2398.81 | 530.67 | 2142.52 | 932.23 | 1210.30 | 0.00 | 0.00 |
July | 2334.87 | 452.53 | 1995.19 | 895.55 | 1099.63 | 0.00 | 0.00 |
August | 2367.72 | 436.05 | 1960.99 | 981.00 | 979.99 | 0.00 | 0.00 |
September | 1558.98 | 667.81 | 1449.86 | 668.69 | 781.17 | 0.00 | 0.00 |
October | 832.65 | 932.48 | 945.02 | 401.54 | 543.47 | 0.00 | 0.00 |
November | 229.19 | 1213.36 | 463.20 | 130.76 | 332.43 | 0.00 | 0.00 |
December | 162.93 | 1507.94 | 379.92 | 122.31 | 257.62 | 0.00 | 0.00 |
Annual Sum or Average | 1241.78 | 921.62 | 1253.45 | 518.09 | 735.36 | 0.00 | 0.00 |
Minimum of Months | 129.01 | 436.05 | 379.92 | 100.37 | 257.62 | 0.00 | 0.00 |
Maximum of Months | 2398.81 | 1507.94 | 2142.52 | 981.00 | 1210.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1395.36 | 2056.10 | 1632.73 | 969.52 | 663.21 | 0.00 | 0.00 |
February | 2457.03 | 1853.90 | 2510.88 | 1554.27 | 956.62 | 0.00 | 0.00 |
March | 2778.09 | 1618.17 | 2700.99 | 1440.40 | 1260.59 | 0.00 | 0.00 |
April | 3112.67 | 1353.51 | 2851.74 | 1238.20 | 1613.53 | 0.00 | 0.00 |
May | 2893.56 | 1096.33 | 2607.55 | 776.81 | 1830.74 | 0.00 | 0.00 |
June | 2705.24 | 868.16 | 2385.66 | 640.51 | 1745.14 | 0.00 | 0.00 |
July | 3241.81 | 774.64 | 2601.66 | 952.86 | 1648.80 | 0.00 | 0.00 |
August | 3587.68 | 747.98 | 2795.15 | 1303.42 | 1491.74 | 0.00 | 0.00 |
September | 3735.87 | 1066.20 | 3096.91 | 1710.21 | 1386.70 | 0.00 | 0.00 |
October | 3087.27 | 1423.58 | 2805.27 | 1732.04 | 1073.23 | 0.00 | 0.00 |
November | 1517.95 | 1751.79 | 1658.57 | 950.50 | 708.07 | 0.00 | 0.00 |
December | 1628.61 | 2148.58 | 1735.34 | 1123.00 | 612.33 | 0.00 | 0.00 |
Annual Sum or Average | 2679.27 | 1394.32 | 2447.48 | 1197.10 | 1250.38 | 0.00 | 0.00 |
Minimum of Months | 1395.36 | 747.98 | 1632.73 | 640.51 | 612.33 | 0.00 | 0.00 |
Maximum of Months | 3735.87 | 2148.58 | 3096.91 | 1732.04 | 1830.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 160.04 | 1586.42 | 417.55 | 123.13 | 294.42 | 0.00 | 0.00 |
February | 471.99 | 1431.65 | 748.64 | 281.36 | 467.28 | 0.00 | 0.00 |
March | 805.41 | 1229.17 | 1049.03 | 354.08 | 694.96 | 0.00 | 0.00 |
April | 1501.66 | 1018.43 | 1595.99 | 610.21 | 985.78 | 0.00 | 0.00 |
May | 2187.45 | 775.51 | 2053.67 | 834.29 | 1219.37 | 0.00 | 0.00 |
June | 2140.60 | 632.28 | 1975.06 | 766.85 | 1208.21 | 0.00 | 0.00 |
July | 2892.11 | 585.14 | 2439.92 | 1282.55 | 1157.37 | 0.00 | 0.00 |
August | 2410.75 | 584.57 | 2018.40 | 1030.65 | 987.75 | 0.00 | 0.00 |
September | 1826.60 | 766.70 | 1643.68 | 788.67 | 855.01 | 0.00 | 0.00 |
October | 805.73 | 1074.32 | 935.75 | 381.27 | 554.48 | 0.00 | 0.00 |
November | 218.43 | 1402.84 | 466.00 | 131.43 | 334.57 | 0.00 | 0.00 |
December | 182.44 | 1769.40 | 391.76 | 134.25 | 257.52 | 0.00 | 0.00 |
Annual Sum or Average | 1305.74 | 1069.68 | 1314.72 | 562.03 | 752.69 | 0.00 | 0.00 |
Minimum of Months | 160.04 | 584.57 | 391.76 | 123.13 | 257.52 | 0.00 | 0.00 |
Maximum of Months | 2892.11 | 1769.40 | 2439.92 | 1282.55 | 1219.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.89 | 2092.79 | 369.55 | 0.00 | 369.55 | 0.00 | 0.00 |
February | 119.45 | 1860.32 | 575.03 | 0.00 | 575.03 | 0.00 | 0.00 |
March | 363.91 | 1536.68 | 847.21 | 0.00 | 847.21 | 0.00 | 0.00 |
April | 785.21 | 1221.84 | 1198.89 | 4.25 | 1194.64 | 0.00 | 0.00 |
May | 1252.25 | 991.64 | 1542.67 | 45.83 | 1496.84 | 0.00 | 0.00 |
June | 1446.62 | 764.86 | 1622.08 | 107.12 | 1514.96 | 0.00 | 0.00 |
July | 1546.02 | 688.78 | 1541.70 | 120.88 | 1420.82 | 0.00 | 0.00 |
August | 1272.46 | 675.02 | 1248.01 | 33.74 | 1214.28 | 0.00 | 0.00 |
September | 743.71 | 1011.93 | 969.41 | 0.29 | 969.13 | 0.00 | 0.00 |
October | 309.01 | 1355.89 | 664.21 | 0.00 | 664.21 | 0.00 | 0.00 |
November | 62.04 | 1717.30 | 418.39 | 0.00 | 418.39 | 0.00 | 0.00 |
December | 7.41 | 2123.53 | 314.02 | 0.00 | 314.02 | 0.00 | 0.00 |
Annual Sum or Average | 663.61 | 1334.14 | 944.42 | 26.20 | 918.22 | 0.00 | 0.00 |
Minimum of Months | 7.41 | 675.02 | 314.02 | 0.00 | 314.02 | 0.00 | 0.00 |
Maximum of Months | 1546.02 | 2123.53 | 1622.08 | 120.88 | 1514.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 142.55 | 1322.51 | 395.87 | 100.37 | 295.51 | 0.00 | 0.00 |
February | 471.90 | 1166.24 | 726.39 | 257.81 | 468.58 | 0.00 | 0.00 |
March | 898.23 | 964.90 | 1084.55 | 392.62 | 691.93 | 0.00 | 0.00 |
April | 1674.20 | 774.63 | 1681.24 | 698.58 | 982.66 | 0.00 | 0.00 |
May | 1871.87 | 648.44 | 1788.99 | 621.99 | 1167.00 | 0.00 | 0.00 |
June | 2393.48 | 510.77 | 2142.51 | 932.22 | 1210.29 | 0.00 | 0.00 |
July | 2326.26 | 449.26 | 1995.18 | 895.55 | 1099.63 | 0.00 | 0.00 |
August | 2358.58 | 440.09 | 1960.98 | 981.00 | 979.99 | 0.00 | 0.00 |
September | 1566.48 | 633.13 | 1449.86 | 668.69 | 781.17 | 0.00 | 0.00 |
October | 854.53 | 852.26 | 945.02 | 401.54 | 543.47 | 0.00 | 0.00 |
November | 248.73 | 1086.95 | 463.19 | 130.76 | 332.43 | 0.00 | 0.00 |
December | 176.98 | 1352.84 | 379.92 | 122.31 | 257.61 | 0.00 | 0.00 |
Annual Sum or Average | 1252.60 | 848.66 | 1253.45 | 518.09 | 735.36 | 0.00 | 0.00 |
Minimum of Months | 142.55 | 440.09 | 379.92 | 100.37 | 257.61 | 0.00 | 0.00 |
Maximum of Months | 2393.48 | 1352.84 | 2142.51 | 981.00 | 1210.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1411.36 | 1926.27 | 1632.78 | 969.55 | 663.23 | 0.00 | 0.00 |
February | 2469.94 | 1762.04 | 2510.96 | 1554.32 | 956.64 | 0.00 | 0.00 |
March | 2783.82 | 1530.49 | 2701.07 | 1440.45 | 1260.62 | 0.00 | 0.00 |
April | 3115.91 | 1286.28 | 2851.81 | 1238.24 | 1613.57 | 0.00 | 0.00 |
May | 2888.48 | 1058.16 | 2607.62 | 776.84 | 1830.78 | 0.00 | 0.00 |
June | 2705.33 | 831.49 | 2385.72 | 640.53 | 1745.18 | 0.00 | 0.00 |
July | 3235.80 | 757.68 | 2601.73 | 952.89 | 1648.84 | 0.00 | 0.00 |
August | 3582.71 | 737.02 | 2795.23 | 1303.46 | 1491.77 | 0.00 | 0.00 |
September | 3728.16 | 1039.55 | 3097.00 | 1710.26 | 1386.73 | 0.00 | 0.00 |
October | 3084.23 | 1358.06 | 2805.36 | 1732.10 | 1073.26 | 0.00 | 0.00 |
November | 1536.79 | 1635.76 | 1658.62 | 950.53 | 708.09 | 0.00 | 0.00 |
December | 1647.32 | 1999.67 | 1735.39 | 1123.04 | 612.35 | 0.00 | 0.00 |
Annual Sum or Average | 2683.26 | 1324.70 | 2447.55 | 1197.14 | 1250.41 | 0.00 | 0.00 |
Minimum of Months | 1411.36 | 737.02 | 1632.78 | 640.53 | 612.35 | 0.00 | 0.00 |
Maximum of Months | 3728.16 | 1999.67 | 3097.00 | 1732.10 | 1830.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 176.36 | 1368.24 | 417.55 | 123.13 | 294.42 | 0.00 | 0.00 |
February | 517.87 | 1214.83 | 748.63 | 281.36 | 467.28 | 0.00 | 0.00 |
March | 868.91 | 1016.59 | 1049.03 | 354.08 | 694.95 | 0.00 | 0.00 |
April | 1576.87 | 847.15 | 1595.98 | 610.21 | 985.78 | 0.00 | 0.00 |
May | 2213.81 | 711.56 | 2053.66 | 834.29 | 1219.37 | 0.00 | 0.00 |
June | 2178.56 | 559.96 | 1975.06 | 766.85 | 1208.21 | 0.00 | 0.00 |
July | 2922.83 | 528.21 | 2439.91 | 1282.54 | 1157.37 | 0.00 | 0.00 |
August | 2454.47 | 510.28 | 2018.39 | 1030.65 | 987.74 | 0.00 | 0.00 |
September | 1852.46 | 698.07 | 1643.67 | 788.67 | 855.00 | 0.00 | 0.00 |
October | 853.88 | 905.51 | 935.75 | 381.27 | 554.48 | 0.00 | 0.00 |
November | 257.28 | 1124.19 | 466.00 | 131.43 | 334.57 | 0.00 | 0.00 |
December | 207.96 | 1405.76 | 391.76 | 134.25 | 257.51 | 0.00 | 0.00 |
Annual Sum or Average | 1345.48 | 906.10 | 1314.71 | 562.02 | 752.69 | 0.00 | 0.00 |
Minimum of Months | 176.36 | 510.28 | 391.76 | 123.13 | 257.51 | 0.00 | 0.00 |
Maximum of Months | 2922.83 | 1405.76 | 2439.91 | 1282.54 | 1219.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 23.31 | 1928.63 | 369.55 | 0.00 | 369.55 | 0.00 | 0.00 |
February | 145.52 | 1698.60 | 575.03 | 0.00 | 575.03 | 0.00 | 0.00 |
March | 407.90 | 1391.69 | 847.21 | 0.00 | 847.21 | 0.00 | 0.00 |
April | 829.51 | 1126.28 | 1198.89 | 4.25 | 1194.64 | 0.00 | 0.00 |
May | 1284.36 | 933.94 | 1542.67 | 45.83 | 1496.84 | 0.00 | 0.00 |
June | 1457.72 | 736.96 | 1622.08 | 107.12 | 1514.96 | 0.00 | 0.00 |
July | 1548.08 | 670.62 | 1541.70 | 120.88 | 1420.82 | 0.00 | 0.00 |
August | 1278.82 | 653.28 | 1248.01 | 33.74 | 1214.28 | 0.00 | 0.00 |
September | 770.18 | 943.41 | 969.41 | 0.29 | 969.13 | 0.00 | 0.00 |
October | 352.09 | 1214.62 | 664.21 | 0.00 | 664.21 | 0.00 | 0.00 |
November | 83.56 | 1529.30 | 418.39 | 0.00 | 418.39 | 0.00 | 0.00 |
December | 15.70 | 1921.85 | 314.02 | 0.00 | 314.02 | 0.00 | 0.00 |
Annual Sum or Average | 686.36 | 1226.83 | 944.42 | 26.20 | 918.22 | 0.00 | 0.00 |
Minimum of Months | 15.70 | 653.28 | 314.02 | 0.00 | 314.02 | 0.00 | 0.00 |
Maximum of Months | 1548.08 | 1928.63 | 1622.08 | 120.88 | 1514.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 154.35 | 1224.54 | 395.87 | 100.37 | 295.51 | 0.00 | 0.00 |
February | 497.11 | 1073.16 | 726.39 | 257.81 | 468.58 | 0.00 | 0.00 |
March | 924.71 | 890.63 | 1084.55 | 392.62 | 691.93 | 0.00 | 0.00 |
April | 1694.84 | 728.28 | 1681.24 | 698.58 | 982.66 | 0.00 | 0.00 |
May | 1882.07 | 620.68 | 1788.99 | 621.99 | 1167.00 | 0.00 | 0.00 |
June | 2390.29 | 499.45 | 2142.51 | 932.22 | 1210.29 | 0.00 | 0.00 |
July | 2321.29 | 444.11 | 1995.18 | 895.55 | 1099.63 | 0.00 | 0.00 |
August | 2355.64 | 433.48 | 1960.98 | 981.00 | 979.99 | 0.00 | 0.00 |
September | 1575.70 | 603.93 | 1449.86 | 668.69 | 781.17 | 0.00 | 0.00 |
October | 878.51 | 782.93 | 945.02 | 401.54 | 543.47 | 0.00 | 0.00 |
November | 266.41 | 984.82 | 463.19 | 130.76 | 332.43 | 0.00 | 0.00 |
December | 190.84 | 1235.31 | 379.92 | 122.31 | 257.61 | 0.00 | 0.00 |
Annual Sum or Average | 1264.84 | 792.12 | 1253.45 | 518.09 | 735.36 | 0.00 | 0.00 |
Minimum of Months | 154.35 | 433.48 | 379.92 | 100.37 | 257.61 | 0.00 | 0.00 |
Maximum of Months | 2390.29 | 1235.31 | 2142.51 | 981.00 | 1210.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1448.51 | 1773.61 | 1632.78 | 969.55 | 663.23 | 0.00 | 0.00 |
February | 2517.64 | 1618.30 | 2510.96 | 1554.32 | 956.64 | 0.00 | 0.00 |
March | 2817.30 | 1410.57 | 2701.07 | 1440.45 | 1260.62 | 0.00 | 0.00 |
April | 3142.89 | 1206.47 | 2851.81 | 1238.24 | 1613.57 | 0.00 | 0.00 |
May | 2904.89 | 1006.80 | 2607.62 | 776.84 | 1830.78 | 0.00 | 0.00 |
June | 2708.15 | 805.57 | 2385.72 | 640.53 | 1745.18 | 0.00 | 0.00 |
July | 3231.42 | 743.25 | 2601.73 | 952.89 | 1648.84 | 0.00 | 0.00 |
August | 3581.41 | 720.14 | 2795.23 | 1303.46 | 1491.77 | 0.00 | 0.00 |
September | 3742.65 | 990.47 | 3097.00 | 1710.26 | 1386.73 | 0.00 | 0.00 |
October | 3117.78 | 1248.94 | 2805.36 | 1732.10 | 1073.26 | 0.00 | 0.00 |
November | 1574.87 | 1485.84 | 1658.62 | 950.53 | 708.09 | 0.00 | 0.00 |
December | 1682.61 | 1825.26 | 1735.39 | 1123.04 | 612.35 | 0.00 | 0.00 |
Annual Sum or Average | 2706.44 | 1234.38 | 2447.55 | 1197.14 | 1250.41 | 0.00 | 0.00 |
Minimum of Months | 1448.51 | 720.14 | 1632.78 | 640.53 | 612.35 | 0.00 | 0.00 |
Maximum of Months | 3742.65 | 1825.26 | 3097.00 | 1732.10 | 1830.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 185.25 | 1269.83 | 417.55 | 123.13 | 294.42 | 0.00 | 0.00 |
February | 534.81 | 1129.17 | 748.63 | 281.36 | 467.28 | 0.00 | 0.00 |
March | 886.56 | 946.57 | 1049.03 | 354.08 | 694.95 | 0.00 | 0.00 |
April | 1592.75 | 799.36 | 1595.98 | 610.21 | 985.78 | 0.00 | 0.00 |
May | 2223.05 | 680.67 | 2053.66 | 834.29 | 1219.37 | 0.00 | 0.00 |
June | 2179.27 | 543.81 | 1975.06 | 766.85 | 1208.21 | 0.00 | 0.00 |
July | 2918.24 | 518.84 | 2439.91 | 1282.54 | 1157.37 | 0.00 | 0.00 |
August | 2453.77 | 499.41 | 2018.39 | 1030.65 | 987.74 | 0.00 | 0.00 |
September | 1862.09 | 667.00 | 1643.67 | 788.67 | 855.00 | 0.00 | 0.00 |
October | 871.50 | 840.12 | 935.75 | 381.27 | 554.48 | 0.00 | 0.00 |
November | 269.23 | 1035.63 | 466.00 | 131.43 | 334.57 | 0.00 | 0.00 |
December | 215.81 | 1298.79 | 391.76 | 134.25 | 257.51 | 0.00 | 0.00 |
Annual Sum or Average | 1354.67 | 851.16 | 1314.71 | 562.02 | 752.69 | 0.00 | 0.00 |
Minimum of Months | 185.25 | 499.41 | 391.76 | 123.13 | 257.51 | 0.00 | 0.00 |
Maximum of Months | 2918.24 | 1298.79 | 2439.91 | 1282.54 | 1219.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 16429668.22 | 0.651012E+10 | 0.989776E+09 | 0.00 | 0.989776E+09 | 0.00 | 0.00 |
February | 0.198307E+09 | 0.517561E+10 | 0.139107E+10 | 0.00 | 0.139107E+10 | 0.00 | 0.00 |
March | 0.826953E+09 | 0.467811E+10 | 0.226912E+10 | 0.00 | 0.226912E+10 | 0.00 | 0.00 |
April | 0.188461E+10 | 0.354473E+10 | 0.310746E+10 | 11022987.75 | 0.309644E+10 | 0.00 | 0.00 |
May | 0.327354E+10 | 0.282574E+10 | 0.413181E+10 | 0.122749E+09 | 0.400906E+10 | 0.00 | 0.00 |
June | 0.369334E+10 | 0.210470E+10 | 0.420435E+10 | 0.277634E+09 | 0.392671E+10 | 0.00 | 0.00 |
July | 0.408299E+10 | 0.193880E+10 | 0.412921E+10 | 0.323745E+09 | 0.380546E+10 | 0.00 | 0.00 |
August | 0.333871E+10 | 0.190973E+10 | 0.334262E+10 | 90359976.16 | 0.325226E+10 | 0.00 | 0.00 |
September | 0.187090E+10 | 0.280118E+10 | 0.251267E+10 | 740940.07 | 0.251193E+10 | 0.00 | 0.00 |
October | 0.709805E+09 | 0.410551E+10 | 0.177898E+10 | 0.00 | 0.177898E+10 | 0.00 | 0.00 |
November | 0.100001E+09 | 0.523508E+10 | 0.108443E+10 | 0.00 | 0.108443E+10 | 0.00 | 0.00 |
December | 3819499.19 | 0.672294E+10 | 0.841054E+09 | 0.00 | 0.841054E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.199994E+11 | 0.475522E+11 | 0.297826E+11 | 0.826252E+09 | 0.289563E+11 | 0.00 | 0.00 |
Minimum of Months | 3819499.19 | 0.190973E+10 | 0.841054E+09 | 0.00 | 0.841054E+09 | 0.00 | 0.00 |
Maximum of Months | 0.408299E+10 | 0.672294E+10 | 0.420435E+10 | 0.323745E+09 | 0.400906E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.345536E+09 | 0.399224E+10 | 0.106031E+10 | 0.268824E+09 | 0.791487E+09 | 0.00 | 0.00 |
February | 0.107184E+10 | 0.310755E+10 | 0.175729E+10 | 0.623699E+09 | 0.113359E+10 | 0.00 | 0.00 |
March | 0.233689E+10 | 0.282063E+10 | 0.290487E+10 | 0.105159E+10 | 0.185328E+10 | 0.00 | 0.00 |
April | 0.430116E+10 | 0.214288E+10 | 0.435779E+10 | 0.181072E+10 | 0.254706E+10 | 0.00 | 0.00 |
May | 0.499071E+10 | 0.183289E+10 | 0.479164E+10 | 0.166594E+10 | 0.312570E+10 | 0.00 | 0.00 |
June | 0.621772E+10 | 0.137548E+10 | 0.555342E+10 | 0.241633E+10 | 0.313709E+10 | 0.00 | 0.00 |
July | 0.625370E+10 | 0.121206E+10 | 0.534391E+10 | 0.239865E+10 | 0.294525E+10 | 0.00 | 0.00 |
August | 0.634170E+10 | 0.116791E+10 | 0.525231E+10 | 0.262751E+10 | 0.262481E+10 | 0.00 | 0.00 |
September | 0.404089E+10 | 0.173097E+10 | 0.375805E+10 | 0.173324E+10 | 0.202480E+10 | 0.00 | 0.00 |
October | 0.223018E+10 | 0.249755E+10 | 0.253114E+10 | 0.107550E+10 | 0.145564E+10 | 0.00 | 0.00 |
November | 0.594050E+09 | 0.314503E+10 | 0.120060E+10 | 0.338943E+09 | 0.861662E+09 | 0.00 | 0.00 |
December | 0.436384E+09 | 0.403887E+10 | 0.101759E+10 | 0.327593E+09 | 0.689998E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.391608E+11 | 0.290641E+11 | 0.395289E+11 | 0.163385E+11 | 0.231904E+11 | 0.00 | 0.00 |
Minimum of Months | 0.345536E+09 | 0.116791E+10 | 0.101759E+10 | 0.268824E+09 | 0.689998E+09 | 0.00 | 0.00 |
Maximum of Months | 0.634170E+10 | 0.403887E+10 | 0.555342E+10 | 0.262751E+10 | 0.313709E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.373734E+10 | 0.550706E+10 | 0.437309E+10 | 0.259676E+10 | 0.177634E+10 | 0.00 | 0.00 |
February | 0.594405E+10 | 0.448495E+10 | 0.607433E+10 | 0.376008E+10 | 0.231425E+10 | 0.00 | 0.00 |
March | 0.744084E+10 | 0.433411E+10 | 0.723433E+10 | 0.385797E+10 | 0.337635E+10 | 0.00 | 0.00 |
April | 0.806804E+10 | 0.350829E+10 | 0.739170E+10 | 0.320942E+10 | 0.418228E+10 | 0.00 | 0.00 |
May | 0.775010E+10 | 0.293642E+10 | 0.698407E+10 | 0.208061E+10 | 0.490346E+10 | 0.00 | 0.00 |
June | 0.701199E+10 | 0.225027E+10 | 0.618363E+10 | 0.166021E+10 | 0.452341E+10 | 0.00 | 0.00 |
July | 0.868287E+10 | 0.207480E+10 | 0.696830E+10 | 0.255214E+10 | 0.441616E+10 | 0.00 | 0.00 |
August | 0.960925E+10 | 0.200338E+10 | 0.748654E+10 | 0.349108E+10 | 0.399546E+10 | 0.00 | 0.00 |
September | 0.968338E+10 | 0.276359E+10 | 0.802719E+10 | 0.443286E+10 | 0.359433E+10 | 0.00 | 0.00 |
October | 0.826895E+10 | 0.381291E+10 | 0.751364E+10 | 0.463911E+10 | 0.287453E+10 | 0.00 | 0.00 |
November | 0.393453E+10 | 0.454064E+10 | 0.429901E+10 | 0.246369E+10 | 0.183532E+10 | 0.00 | 0.00 |
December | 0.436208E+10 | 0.575477E+10 | 0.464793E+10 | 0.300785E+10 | 0.164008E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.844934E+11 | 0.439712E+11 | 0.771837E+11 | 0.377518E+11 | 0.394320E+11 | 0.00 | 0.00 |
Minimum of Months | 0.373734E+10 | 0.200338E+10 | 0.429901E+10 | 0.166021E+10 | 0.164008E+10 | 0.00 | 0.00 |
Maximum of Months | 0.968338E+10 | 0.575477E+10 | 0.802719E+10 | 0.463911E+10 | 0.490346E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.428639E+09 | 0.424906E+10 | 0.111837E+10 | 0.329787E+09 | 0.788583E+09 | 0.00 | 0.00 |
February | 0.114184E+10 | 0.346344E+10 | 0.181110E+10 | 0.680664E+09 | 0.113044E+10 | 0.00 | 0.00 |
March | 0.215722E+10 | 0.329220E+10 | 0.280973E+10 | 0.948358E+09 | 0.186137E+10 | 0.00 | 0.00 |
April | 0.389229E+10 | 0.263977E+10 | 0.413681E+10 | 0.158166E+10 | 0.255515E+10 | 0.00 | 0.00 |
May | 0.585886E+10 | 0.207711E+10 | 0.550054E+10 | 0.223457E+10 | 0.326597E+10 | 0.00 | 0.00 |
June | 0.554845E+10 | 0.163887E+10 | 0.511937E+10 | 0.198768E+10 | 0.313169E+10 | 0.00 | 0.00 |
July | 0.774624E+10 | 0.156724E+10 | 0.653509E+10 | 0.343518E+10 | 0.309991E+10 | 0.00 | 0.00 |
August | 0.645696E+10 | 0.156570E+10 | 0.540608E+10 | 0.276050E+10 | 0.264558E+10 | 0.00 | 0.00 |
September | 0.473455E+10 | 0.198730E+10 | 0.426042E+10 | 0.204424E+10 | 0.221618E+10 | 0.00 | 0.00 |
October | 0.215808E+10 | 0.287745E+10 | 0.250632E+10 | 0.102121E+10 | 0.148511E+10 | 0.00 | 0.00 |
November | 0.566171E+09 | 0.363615E+10 | 0.120787E+10 | 0.340669E+09 | 0.867199E+09 | 0.00 | 0.00 |
December | 0.488647E+09 | 0.473917E+10 | 0.104930E+10 | 0.359567E+09 | 0.689729E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.411779E+11 | 0.337335E+11 | 0.414610E+11 | 0.177241E+11 | 0.237369E+11 | 0.00 | 0.00 |
Minimum of Months | 0.428639E+09 | 0.156570E+10 | 0.104930E+10 | 0.329787E+09 | 0.689729E+09 | 0.00 | 0.00 |
Maximum of Months | 0.774624E+10 | 0.473917E+10 | 0.653509E+10 | 0.343518E+10 | 0.326597E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 39873043.04 | 0.560534E+10 | 0.989797E+09 | 0.00 | 0.989797E+09 | 0.00 | 0.00 |
February | 0.288966E+09 | 0.450048E+10 | 0.139110E+10 | 0.00 | 0.139110E+10 | 0.00 | 0.00 |
March | 0.974699E+09 | 0.411586E+10 | 0.226917E+10 | 0.00 | 0.226917E+10 | 0.00 | 0.00 |
April | 0.203526E+10 | 0.316701E+10 | 0.310752E+10 | 11023316.49 | 0.309650E+10 | 0.00 | 0.00 |
May | 0.335402E+10 | 0.265601E+10 | 0.413188E+10 | 0.122752E+09 | 0.400913E+10 | 0.00 | 0.00 |
June | 0.374963E+10 | 0.198251E+10 | 0.420442E+10 | 0.277643E+09 | 0.392678E+10 | 0.00 | 0.00 |
July | 0.414086E+10 | 0.184483E+10 | 0.412928E+10 | 0.323755E+09 | 0.380552E+10 | 0.00 | 0.00 |
August | 0.340817E+10 | 0.180798E+10 | 0.334268E+10 | 90362670.95 | 0.325232E+10 | 0.00 | 0.00 |
September | 0.192769E+10 | 0.262292E+10 | 0.251272E+10 | 740962.17 | 0.251198E+10 | 0.00 | 0.00 |
October | 0.827655E+09 | 0.363161E+10 | 0.177902E+10 | 0.00 | 0.177902E+10 | 0.00 | 0.00 |
November | 0.160818E+09 | 0.445125E+10 | 0.108446E+10 | 0.00 | 0.108446E+10 | 0.00 | 0.00 |
December | 19852536.83 | 0.568767E+10 | 0.841072E+09 | 0.00 | 0.841072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.209275E+11 | 0.420735E+11 | 0.297831E+11 | 0.826277E+09 | 0.289568E+11 | 0.00 | 0.00 |
Minimum of Months | 19852536.83 | 0.180798E+10 | 0.841072E+09 | 0.00 | 0.841072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.414086E+10 | 0.568767E+10 | 0.420442E+10 | 0.323755E+09 | 0.400913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.381803E+09 | 0.354222E+10 | 0.106031E+10 | 0.268823E+09 | 0.791484E+09 | 0.00 | 0.00 |
February | 0.114162E+10 | 0.282138E+10 | 0.175728E+10 | 0.623696E+09 | 0.113358E+10 | 0.00 | 0.00 |
March | 0.240583E+10 | 0.258440E+10 | 0.290486E+10 | 0.105158E+10 | 0.185327E+10 | 0.00 | 0.00 |
April | 0.433952E+10 | 0.200785E+10 | 0.435777E+10 | 0.181072E+10 | 0.254705E+10 | 0.00 | 0.00 |
May | 0.501362E+10 | 0.173679E+10 | 0.479162E+10 | 0.166594E+10 | 0.312568E+10 | 0.00 | 0.00 |
June | 0.620391E+10 | 0.132392E+10 | 0.555340E+10 | 0.241632E+10 | 0.313707E+10 | 0.00 | 0.00 |
July | 0.623066E+10 | 0.120330E+10 | 0.534388E+10 | 0.239864E+10 | 0.294524E+10 | 0.00 | 0.00 |
August | 0.631722E+10 | 0.117873E+10 | 0.525229E+10 | 0.262750E+10 | 0.262479E+10 | 0.00 | 0.00 |
September | 0.406032E+10 | 0.164108E+10 | 0.375803E+10 | 0.173324E+10 | 0.202480E+10 | 0.00 | 0.00 |
October | 0.228877E+10 | 0.228269E+10 | 0.253113E+10 | 0.107549E+10 | 0.145564E+10 | 0.00 | 0.00 |
November | 0.644706E+09 | 0.281738E+10 | 0.120060E+10 | 0.338941E+09 | 0.861658E+09 | 0.00 | 0.00 |
December | 0.474022E+09 | 0.362345E+10 | 0.101759E+10 | 0.327591E+09 | 0.689996E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.395020E+11 | 0.267632E+11 | 0.395288E+11 | 0.163385E+11 | 0.231903E+11 | 0.00 | 0.00 |
Minimum of Months | 0.381803E+09 | 0.117873E+10 | 0.101759E+10 | 0.268823E+09 | 0.689996E+09 | 0.00 | 0.00 |
Maximum of Months | 0.631722E+10 | 0.362345E+10 | 0.555340E+10 | 0.262750E+10 | 0.313707E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.378019E+10 | 0.515932E+10 | 0.437323E+10 | 0.259684E+10 | 0.177639E+10 | 0.00 | 0.00 |
February | 0.597529E+10 | 0.426274E+10 | 0.607451E+10 | 0.376021E+10 | 0.231431E+10 | 0.00 | 0.00 |
March | 0.745618E+10 | 0.409926E+10 | 0.723454E+10 | 0.385810E+10 | 0.337644E+10 | 0.00 | 0.00 |
April | 0.807645E+10 | 0.333403E+10 | 0.739190E+10 | 0.320952E+10 | 0.418238E+10 | 0.00 | 0.00 |
May | 0.773651E+10 | 0.283417E+10 | 0.698424E+10 | 0.208068E+10 | 0.490357E+10 | 0.00 | 0.00 |
June | 0.701223E+10 | 0.215523E+10 | 0.618378E+10 | 0.166027E+10 | 0.452351E+10 | 0.00 | 0.00 |
July | 0.866676E+10 | 0.202936E+10 | 0.696847E+10 | 0.255222E+10 | 0.441624E+10 | 0.00 | 0.00 |
August | 0.959593E+10 | 0.197403E+10 | 0.748674E+10 | 0.349119E+10 | 0.399555E+10 | 0.00 | 0.00 |
September | 0.966340E+10 | 0.269453E+10 | 0.802742E+10 | 0.443301E+10 | 0.359441E+10 | 0.00 | 0.00 |
October | 0.826081E+10 | 0.363742E+10 | 0.751387E+10 | 0.463926E+10 | 0.287461E+10 | 0.00 | 0.00 |
November | 0.398335E+10 | 0.423990E+10 | 0.429914E+10 | 0.246377E+10 | 0.183537E+10 | 0.00 | 0.00 |
December | 0.441219E+10 | 0.535591E+10 | 0.464807E+10 | 0.300795E+10 | 0.164012E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.846193E+11 | 0.417759E+11 | 0.771859E+11 | 0.377530E+11 | 0.394329E+11 | 0.00 | 0.00 |
Minimum of Months | 0.378019E+10 | 0.197403E+10 | 0.429914E+10 | 0.166027E+10 | 0.164012E+10 | 0.00 | 0.00 |
Maximum of Months | 0.966340E+10 | 0.535591E+10 | 0.802742E+10 | 0.463926E+10 | 0.490357E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.472355E+09 | 0.366470E+10 | 0.111837E+10 | 0.329786E+09 | 0.788580E+09 | 0.00 | 0.00 |
February | 0.125283E+10 | 0.293891E+10 | 0.181110E+10 | 0.680661E+09 | 0.113044E+10 | 0.00 | 0.00 |
March | 0.232730E+10 | 0.272282E+10 | 0.280972E+10 | 0.948354E+09 | 0.186136E+10 | 0.00 | 0.00 |
April | 0.408725E+10 | 0.219582E+10 | 0.413679E+10 | 0.158165E+10 | 0.255513E+10 | 0.00 | 0.00 |
May | 0.592948E+10 | 0.190584E+10 | 0.550052E+10 | 0.223456E+10 | 0.326596E+10 | 0.00 | 0.00 |
June | 0.564684E+10 | 0.145142E+10 | 0.511935E+10 | 0.198767E+10 | 0.313167E+10 | 0.00 | 0.00 |
July | 0.782852E+10 | 0.141477E+10 | 0.653506E+10 | 0.343516E+10 | 0.309990E+10 | 0.00 | 0.00 |
August | 0.657405E+10 | 0.136673E+10 | 0.540606E+10 | 0.276049E+10 | 0.264557E+10 | 0.00 | 0.00 |
September | 0.480159E+10 | 0.180940E+10 | 0.426040E+10 | 0.204423E+10 | 0.221617E+10 | 0.00 | 0.00 |
October | 0.228703E+10 | 0.242531E+10 | 0.250631E+10 | 0.102120E+10 | 0.148511E+10 | 0.00 | 0.00 |
November | 0.666872E+09 | 0.291390E+10 | 0.120786E+10 | 0.340668E+09 | 0.867196E+09 | 0.00 | 0.00 |
December | 0.557008E+09 | 0.376520E+10 | 0.104929E+10 | 0.359565E+09 | 0.689726E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.424311E+11 | 0.285748E+11 | 0.414608E+11 | 0.177240E+11 | 0.237368E+11 | 0.00 | 0.00 |
Minimum of Months | 0.472355E+09 | 0.136673E+10 | 0.104929E+10 | 0.329786E+09 | 0.689726E+09 | 0.00 | 0.00 |
Maximum of Months | 0.782852E+10 | 0.376520E+10 | 0.653506E+10 | 0.343516E+10 | 0.326596E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 62443136.44 | 0.516565E+10 | 0.989797E+09 | 0.00 | 0.989797E+09 | 0.00 | 0.00 |
February | 0.352050E+09 | 0.410925E+10 | 0.139110E+10 | 0.00 | 0.139110E+10 | 0.00 | 0.00 |
March | 0.109252E+10 | 0.372749E+10 | 0.226917E+10 | 0.00 | 0.226917E+10 | 0.00 | 0.00 |
April | 0.215008E+10 | 0.291932E+10 | 0.310752E+10 | 11023316.49 | 0.309650E+10 | 0.00 | 0.00 |
May | 0.344003E+10 | 0.250148E+10 | 0.413188E+10 | 0.122752E+09 | 0.400913E+10 | 0.00 | 0.00 |
June | 0.377840E+10 | 0.191020E+10 | 0.420442E+10 | 0.277643E+09 | 0.392678E+10 | 0.00 | 0.00 |
July | 0.414638E+10 | 0.179618E+10 | 0.412928E+10 | 0.323755E+09 | 0.380552E+10 | 0.00 | 0.00 |
August | 0.342519E+10 | 0.174975E+10 | 0.334268E+10 | 90362670.95 | 0.325232E+10 | 0.00 | 0.00 |
September | 0.199631E+10 | 0.244531E+10 | 0.251272E+10 | 740962.17 | 0.251198E+10 | 0.00 | 0.00 |
October | 0.943043E+09 | 0.325325E+10 | 0.177902E+10 | 0.00 | 0.177902E+10 | 0.00 | 0.00 |
November | 0.216590E+09 | 0.396394E+10 | 0.108446E+10 | 0.00 | 0.108446E+10 | 0.00 | 0.00 |
December | 42048691.61 | 0.514749E+10 | 0.841072E+09 | 0.00 | 0.841072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.216451E+11 | 0.386893E+11 | 0.297831E+11 | 0.826277E+09 | 0.289568E+11 | 0.00 | 0.00 |
Minimum of Months | 42048691.61 | 0.174975E+10 | 0.841072E+09 | 0.00 | 0.841072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.414638E+10 | 0.516565E+10 | 0.420442E+10 | 0.323755E+09 | 0.400913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.413414E+09 | 0.327981E+10 | 0.106031E+10 | 0.268823E+09 | 0.791484E+09 | 0.00 | 0.00 |
February | 0.120260E+10 | 0.259618E+10 | 0.175728E+10 | 0.623696E+09 | 0.113358E+10 | 0.00 | 0.00 |
March | 0.247674E+10 | 0.238546E+10 | 0.290486E+10 | 0.105158E+10 | 0.185327E+10 | 0.00 | 0.00 |
April | 0.439302E+10 | 0.188769E+10 | 0.435777E+10 | 0.181072E+10 | 0.254705E+10 | 0.00 | 0.00 |
May | 0.504095E+10 | 0.166242E+10 | 0.479162E+10 | 0.166594E+10 | 0.312568E+10 | 0.00 | 0.00 |
June | 0.619562E+10 | 0.129457E+10 | 0.555340E+10 | 0.241632E+10 | 0.313707E+10 | 0.00 | 0.00 |
July | 0.621733E+10 | 0.118950E+10 | 0.534388E+10 | 0.239864E+10 | 0.294524E+10 | 0.00 | 0.00 |
August | 0.630935E+10 | 0.116103E+10 | 0.525229E+10 | 0.262750E+10 | 0.262479E+10 | 0.00 | 0.00 |
September | 0.408422E+10 | 0.156539E+10 | 0.375803E+10 | 0.173324E+10 | 0.202480E+10 | 0.00 | 0.00 |
October | 0.235301E+10 | 0.209700E+10 | 0.253113E+10 | 0.107549E+10 | 0.145564E+10 | 0.00 | 0.00 |
November | 0.690532E+09 | 0.255266E+10 | 0.120060E+10 | 0.338941E+09 | 0.861658E+09 | 0.00 | 0.00 |
December | 0.511152E+09 | 0.330865E+10 | 0.101759E+10 | 0.327591E+09 | 0.689996E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.398880E+11 | 0.249804E+11 | 0.395288E+11 | 0.163385E+11 | 0.231903E+11 | 0.00 | 0.00 |
Minimum of Months | 0.413414E+09 | 0.116103E+10 | 0.101759E+10 | 0.268823E+09 | 0.689996E+09 | 0.00 | 0.00 |
Maximum of Months | 0.630935E+10 | 0.330865E+10 | 0.555340E+10 | 0.262750E+10 | 0.313707E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.387970E+10 | 0.475044E+10 | 0.437323E+10 | 0.259684E+10 | 0.177639E+10 | 0.00 | 0.00 |
February | 0.609067E+10 | 0.391500E+10 | 0.607451E+10 | 0.376021E+10 | 0.231431E+10 | 0.00 | 0.00 |
March | 0.754585E+10 | 0.377807E+10 | 0.723454E+10 | 0.385810E+10 | 0.337644E+10 | 0.00 | 0.00 |
April | 0.814636E+10 | 0.312717E+10 | 0.739190E+10 | 0.320952E+10 | 0.418238E+10 | 0.00 | 0.00 |
May | 0.778046E+10 | 0.269663E+10 | 0.698424E+10 | 0.208068E+10 | 0.490357E+10 | 0.00 | 0.00 |
June | 0.701952E+10 | 0.208803E+10 | 0.618378E+10 | 0.166027E+10 | 0.452351E+10 | 0.00 | 0.00 |
July | 0.865504E+10 | 0.199072E+10 | 0.696847E+10 | 0.255222E+10 | 0.441624E+10 | 0.00 | 0.00 |
August | 0.959244E+10 | 0.192883E+10 | 0.748674E+10 | 0.349119E+10 | 0.399555E+10 | 0.00 | 0.00 |
September | 0.970096E+10 | 0.256730E+10 | 0.802742E+10 | 0.443301E+10 | 0.359441E+10 | 0.00 | 0.00 |
October | 0.835065E+10 | 0.334517E+10 | 0.751387E+10 | 0.463926E+10 | 0.287461E+10 | 0.00 | 0.00 |
November | 0.408207E+10 | 0.385129E+10 | 0.429914E+10 | 0.246377E+10 | 0.183537E+10 | 0.00 | 0.00 |
December | 0.450669E+10 | 0.488879E+10 | 0.464807E+10 | 0.300795E+10 | 0.164012E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.853504E+11 | 0.389274E+11 | 0.771859E+11 | 0.377530E+11 | 0.394329E+11 | 0.00 | 0.00 |
Minimum of Months | 0.387970E+10 | 0.192883E+10 | 0.429914E+10 | 0.166027E+10 | 0.164012E+10 | 0.00 | 0.00 |
Maximum of Months | 0.970096E+10 | 0.488879E+10 | 0.802742E+10 | 0.463926E+10 | 0.490357E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.496177E+09 | 0.340111E+10 | 0.111837E+10 | 0.329786E+09 | 0.788580E+09 | 0.00 | 0.00 |
February | 0.129382E+10 | 0.273170E+10 | 0.181110E+10 | 0.680661E+09 | 0.113044E+10 | 0.00 | 0.00 |
March | 0.237456E+10 | 0.253530E+10 | 0.280972E+10 | 0.948354E+09 | 0.186136E+10 | 0.00 | 0.00 |
April | 0.412841E+10 | 0.207194E+10 | 0.413679E+10 | 0.158165E+10 | 0.255513E+10 | 0.00 | 0.00 |
May | 0.595420E+10 | 0.182312E+10 | 0.550052E+10 | 0.223456E+10 | 0.326596E+10 | 0.00 | 0.00 |
June | 0.564866E+10 | 0.140956E+10 | 0.511935E+10 | 0.198767E+10 | 0.313167E+10 | 0.00 | 0.00 |
July | 0.781621E+10 | 0.138966E+10 | 0.653506E+10 | 0.343516E+10 | 0.309990E+10 | 0.00 | 0.00 |
August | 0.657217E+10 | 0.133762E+10 | 0.540606E+10 | 0.276049E+10 | 0.264557E+10 | 0.00 | 0.00 |
September | 0.482653E+10 | 0.172885E+10 | 0.426040E+10 | 0.204423E+10 | 0.221617E+10 | 0.00 | 0.00 |
October | 0.233422E+10 | 0.225017E+10 | 0.250631E+10 | 0.102120E+10 | 0.148511E+10 | 0.00 | 0.00 |
November | 0.697854E+09 | 0.268436E+10 | 0.120786E+10 | 0.340668E+09 | 0.867196E+09 | 0.00 | 0.00 |
December | 0.578027E+09 | 0.347869E+10 | 0.104929E+10 | 0.359565E+09 | 0.689726E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.427208E+11 | 0.268421E+11 | 0.414608E+11 | 0.177240E+11 | 0.237368E+11 | 0.00 | 0.00 |
Minimum of Months | 0.496177E+09 | 0.133762E+10 | 0.104929E+10 | 0.329786E+09 | 0.689726E+09 | 0.00 | 0.00 |
Maximum of Months | 0.781621E+10 | 0.347869E+10 | 0.653506E+10 | 0.343516E+10 | 0.326596E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.388579E+11 | -0.378306E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102728E+10 | 58.97 | 0.00 | 0.00 |
February | 0.355430E+11 | -0.346158E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -927178946.4 | 58.97 | 0.00 | 0.00 |
March | 0.412862E+11 | -0.402592E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102695E+10 | 58.97 | 0.00 | 0.00 |
April | 0.364890E+11 | -0.354992E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989763975.9 | 58.98 | 0.00 | 0.00 |
May | 0.375194E+11 | -0.364953E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102405E+10 | 58.98 | 0.00 | 0.00 |
June | 0.358041E+11 | -0.348131E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990984015.2 | 58.97 | 0.00 | 0.00 |
July | 0.332005E+11 | -0.321811E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101941E+10 | 58.98 | 0.00 | 0.00 |
August | 0.359568E+11 | -0.349330E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102376E+10 | 58.98 | 0.00 | 0.00 |
September | 0.331061E+11 | -0.321175E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988568330.4 | 58.97 | 0.00 | 0.00 |
October | 0.352119E+11 | -0.341906E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102122E+10 | 58.97 | 0.00 | 0.00 |
November | 0.358806E+11 | -0.348919E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988750380.8 | 58.98 | 0.00 | 0.00 |
December | 0.370377E+11 | -0.360147E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102303E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.435893E+12 | -0.423842E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120509E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.331061E+11 | -0.402592E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102728E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.412862E+11 | -0.321175E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -927178946.4 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.63 | 0.61 | 01-JAN-09:20 | 2473.22 | 29.23 | 191.67 | 210.33 | 2060.06 | 33.61 | 226.00 | 177.83 |
February | 259.50 | 0.63 | 0.61 | 01-FEB-08:20 | 4391.87 | 31.25 | 222.33 | 236.83 | 1872.25 | 28.82 | 216.67 | 211.17 |
March | 247.00 | 0.63 | 0.61 | 01-MAR-07:40 | 7444.05 | 32.43 | 207.00 | 306.67 | 1439.87 | 21.62 | 146.17 | 256.83 |
April | 379.50 | 0.63 | 0.61 | 01-APR-06:40 | 1918.88 | 17.64 | 0.00 | 339.50 | 1036.89 | 20.62 | 199.33 | 295.00 |
May | 427.83 | 0.63 | 0.61 | 01-MAY-06:49 | 1765.46 | 17.48 | 0.00 | 378.00 | 941.04 | 20.41 | 188.50 | 331.17 |
June | 375.17 | 0.64 | 0.61 | 01-JUN-05:30 | 1530.80 | 16.98 | 0.00 | 386.33 | 862.83 | 19.94 | 163.67 | 330.33 |
July | 471.00 | 0.65 | 0.61 | 01-JUL-04:00 | 1360.66 | 15.76 | 0.00 | 381.00 | 780.69 | 18.72 | 139.00 | 319.00 |
August | 366.67 | 0.64 | 0.61 | 01-AUG-05:49 | 1603.62 | 16.81 | 0.00 | 361.83 | 938.45 | 19.80 | 144.17 | 313.00 |
September | 301.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2650.32 | 19.81 | 27.00 | 312.83 | 1244.38 | 21.39 | 176.17 | 275.50 |
October | 245.33 | 0.64 | 0.61 | 01-OCT-07:19 | 6863.19 | 33.71 | 216.50 | 278.67 | 1719.38 | 22.87 | 151.33 | 249.83 |
November | 242.67 | 0.63 | 0.61 | 01-NOV-07:49 | 2815.55 | 29.36 | 201.50 | 217.67 | 2328.31 | 33.24 | 229.83 | 185.50 |
December | 160.33 | 0.63 | 0.61 | 01-DEC-09:39 | 3178.44 | 30.11 | 111.33 | 199.50 | 2955.04 | 36.92 | 149.67 | 154.00 |
Annual Sum or Average | 3714.00 | 0.64 | 2834.70 | 22.45 | 1177.33 | 3609.17 | 1345.84 | 23.42 | 2130.50 | 3099.17 | ||
Minimum of Months | 160.33 | 0.63 | 0.61 | 1360.66 | 15.76 | 0.00 | 199.50 | 780.69 | 18.72 | 139.00 | 154.00 | |
Maximum of Months | 471.00 | 0.65 | 0.61 | 7444.05 | 33.71 | 222.33 | 386.33 | 2955.04 | 36.92 | 229.83 | 331.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.65 | 0.61 | 01-JAN-09:20 | 775.09 | 15.67 | 44.00 | 189.00 | 509.12 | 18.24 | 61.17 | 110.17 |
February | 259.50 | 0.64 | 0.61 | 01-FEB-08:20 | 1330.73 | 17.82 | 63.67 | 218.83 | 672.55 | 17.16 | 37.33 | 162.17 |
March | 247.00 | 0.64 | 0.61 | 01-MAR-07:30 | 2452.37 | 19.80 | 77.83 | 293.83 | 1004.18 | 17.78 | 36.67 | 232.83 |
April | 379.50 | 0.63 | 0.61 | 01-APR-06:10 | 2420.41 | 15.76 | 47.83 | 338.17 | 1408.03 | 14.77 | 0.00 | 292.67 |
May | 427.83 | 0.63 | 0.61 | 01-MAY-06:49 | 2623.93 | 15.32 | 43.33 | 381.67 | 1112.66 | 14.73 | 0.00 | 335.00 |
June | 375.17 | 0.64 | 0.61 | 01-JUN-04:00 | 2653.38 | 13.15 | 0.00 | 393.33 | 1485.43 | 14.45 | 0.00 | 341.17 |
July | 471.00 | 0.65 | 0.61 | 01-JUL-04:49 | 2578.54 | 12.21 | 3.67 | 393.33 | 1149.65 | 13.28 | 0.00 | 353.17 |
August | 366.67 | 0.64 | 0.61 | 01-AUG-05:30 | 3034.82 | 15.07 | 48.33 | 365.50 | 1291.47 | 14.22 | 3.17 | 322.67 |
September | 301.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2373.36 | 17.98 | 65.17 | 315.50 | 1373.94 | 17.72 | 39.67 | 269.50 |
October | 245.33 | 0.65 | 0.61 | 01-OCT-07:19 | 2255.04 | 19.75 | 80.50 | 261.00 | 929.32 | 17.78 | 39.17 | 205.83 |
November | 242.67 | 0.64 | 0.61 | 01-NOV-07:49 | 1007.38 | 17.32 | 63.33 | 197.50 | 530.23 | 17.81 | 52.67 | 122.00 |
December | 160.33 | 0.65 | 0.61 | 01-DEC-09:39 | 875.73 | 17.29 | 38.17 | 170.50 | 511.34 | 19.12 | 39.50 | 88.17 |
Annual Sum or Average | 3714.00 | 0.64 | 2194.98 | 15.94 | 575.83 | 3518.17 | 1071.29 | 15.90 | 309.33 | 2835.33 | ||
Minimum of Months | 160.33 | 0.63 | 0.61 | 775.09 | 12.21 | 0.00 | 170.50 | 509.12 | 13.28 | 0.00 | 88.17 | |
Maximum of Months | 471.00 | 0.65 | 0.61 | 3034.82 | 19.80 | 80.50 | 393.33 | 1485.43 | 19.12 | 61.17 | 353.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.66 | 0.61 | 01-JAN-09:39 | 434.78 | 0.00 | 0.00 | 160.17 | 236.13 | 0.00 | 0.00 | 14.00 |
February | 259.50 | 0.65 | 0.61 | 01-FEB-08:50 | 548.35 | 0.00 | 0.00 | 200.83 | 310.01 | 0.00 | 0.00 | 97.67 |
March | 247.00 | 0.64 | 0.61 | 01-MAR-07:00 | 732.61 | 0.00 | 0.00 | 286.67 | 436.10 | 0.00 | 0.00 | 180.00 |
April | 379.50 | 0.63 | 0.61 | 01-APR-06:40 | 864.45 | 0.00 | 0.00 | 342.83 | 500.63 | 0.00 | 0.00 | 279.67 |
May | 427.83 | 0.63 | 0.61 | 01-MAY-06:49 | 1056.13 | 0.00 | 0.00 | 394.00 | 610.90 | 0.00 | 0.00 | 353.50 |
June | 375.17 | 0.63 | 0.61 | 01-JUN-05:10 | 1121.53 | 0.00 | 0.00 | 407.33 | 640.59 | 0.00 | 0.00 | 369.67 |
July | 471.00 | 0.64 | 0.61 | 01-JUL-04:00 | 948.69 | 0.00 | 0.00 | 415.67 | 545.64 | 0.00 | 0.00 | 358.50 |
August | 366.67 | 0.63 | 0.61 | 01-AUG-05:40 | 805.02 | 0.00 | 0.00 | 378.67 | 512.66 | 0.00 | 0.00 | 324.67 |
September | 301.17 | 0.63 | 0.61 | 01-SEP-07:40 | 791.84 | 0.00 | 0.00 | 306.83 | 484.64 | 0.00 | 0.00 | 235.33 |
October | 245.33 | 0.65 | 0.61 | 01-OCT-07:40 | 589.76 | 0.00 | 0.00 | 245.83 | 360.79 | 0.00 | 0.00 | 137.17 |
November | 242.67 | 0.65 | 0.61 | 01-NOV-07:00 | 469.03 | 0.00 | 0.00 | 173.33 | 254.39 | 0.00 | 0.00 | 34.17 |
December | 160.33 | 0.68 | 0.61 | 01-DEC-09:50 | 398.06 | 0.00 | 0.00 | 131.50 | 235.15 | 0.00 | 0.00 | 14.17 |
Annual Sum or Average | 3714.00 | 0.64 | 788.94 | 0.00 | 0.00 | 3443.67 | 461.74 | 0.00 | 0.00 | 2398.50 | ||
Minimum of Months | 160.33 | 0.63 | 0.61 | 398.06 | 0.00 | 0.00 | 131.50 | 235.15 | 0.00 | 0.00 | 14.00 | |
Maximum of Months | 471.00 | 0.68 | 0.61 | 1121.53 | 0.00 | 0.00 | 415.67 | 640.59 | 0.00 | 0.00 | 369.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.65 | 0.61 | 01-JAN-09:39 | 921.54 | 17.68 | 68.00 | 191.33 | 478.03 | 16.75 | 40.33 | 110.50 |
February | 259.50 | 0.64 | 0.61 | 01-FEB-08:50 | 1208.46 | 16.18 | 42.17 | 219.67 | 663.27 | 17.27 | 38.00 | 164.50 |
March | 247.00 | 0.64 | 0.61 | 01-MAR-07:00 | 2046.50 | 18.17 | 58.83 | 295.50 | 1131.43 | 17.86 | 38.50 | 232.33 |
April | 379.50 | 0.63 | 0.61 | 01-APR-07:10 | 2563.30 | 15.73 | 48.50 | 336.50 | 1091.05 | 14.81 | 0.00 | 293.50 |
May | 427.83 | 0.63 | 0.61 | 01-MAY-06:00 | 2561.25 | 13.65 | 0.00 | 384.17 | 1397.95 | 14.88 | 1.50 | 337.17 |
June | 375.17 | 0.64 | 0.61 | 01-JUN-05:49 | 2698.26 | 13.23 | 0.00 | 391.17 | 1181.21 | 16.60 | 36.50 | 350.00 |
July | 471.00 | 0.65 | 0.61 | 01-JUL-05:10 | 2973.02 | 11.88 | 0.00 | 392.67 | 1269.55 | 15.27 | 45.50 | 347.00 |
August | 366.67 | 0.64 | 0.61 | 01-AUG-05:00 | 2682.34 | 12.99 | 8.50 | 370.33 | 1612.68 | 14.37 | 5.50 | 327.00 |
September | 301.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2936.05 | 18.80 | 78.00 | 307.33 | 1728.41 | 18.38 | 49.83 | 254.83 |
October | 245.33 | 0.64 | 0.61 | 01-OCT-07:40 | 2000.02 | 18.46 | 66.50 | 261.67 | 901.67 | 18.11 | 42.83 | 204.67 |
November | 242.67 | 0.64 | 0.61 | 01-NOV-07:00 | 983.21 | 17.19 | 59.17 | 198.67 | 501.69 | 16.41 | 37.67 | 117.50 |
December | 160.33 | 0.65 | 0.61 | 01-DEC-09:39 | 873.68 | 16.48 | 31.83 | 171.67 | 515.19 | 18.07 | 31.83 | 81.33 |
Annual Sum or Average | 3714.00 | 0.64 | 2223.08 | 15.36 | 461.50 | 3520.67 | 1118.99 | 16.27 | 368.00 | 2820.33 | ||
Minimum of Months | 160.33 | 0.63 | 0.61 | 873.68 | 11.88 | 0.00 | 171.67 | 478.03 | 14.37 | 0.00 | 81.33 | |
Maximum of Months | 471.00 | 0.65 | 0.61 | 2973.02 | 18.80 | 78.00 | 392.67 | 1728.41 | 18.38 | 49.83 | 350.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.64 | 0.61 | 01-JAN-09:20 | 2208.83 | 22.51 | 139.83 | 210.00 | 2060.14 | 31.66 | 208.83 | 176.67 |
February | 259.50 | 0.63 | 0.61 | 01-FEB-08:20 | 4342.82 | 30.39 | 218.17 | 236.17 | 1913.08 | 27.17 | 156.67 | 214.33 |
March | 247.00 | 0.63 | 0.61 | 01-MAR-07:40 | 7393.97 | 31.37 | 206.50 | 304.50 | 1487.36 | 17.00 | 7.50 | 258.83 |
April | 379.50 | 0.64 | 0.61 | 01-APR-06:49 | 1877.51 | 11.48 | 0.00 | 337.83 | 1070.79 | 16.23 | 0.00 | 296.83 |
May | 427.83 | 0.64 | 0.61 | 01-MAY-06:49 | 1726.20 | 11.46 | 0.00 | 376.33 | 970.40 | 16.15 | 0.00 | 333.17 |
June | 375.17 | 0.64 | 0.61 | 01-JUN-05:40 | 1504.43 | 11.35 | 0.00 | 384.17 | 891.22 | 16.03 | 0.00 | 332.50 |
July | 471.00 | 0.65 | 0.61 | 01-JUL-05:10 | 1341.42 | 9.95 | 0.00 | 380.00 | 809.04 | 14.64 | 0.00 | 322.17 |
August | 366.67 | 0.64 | 0.61 | 01-AUG-05:49 | 1583.72 | 11.02 | 0.00 | 361.00 | 974.59 | 15.85 | 0.00 | 315.50 |
September | 301.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2609.35 | 14.26 | 27.00 | 311.67 | 1288.86 | 17.13 | 0.00 | 277.67 |
October | 245.33 | 0.64 | 0.61 | 01-OCT-07:40 | 6798.45 | 32.88 | 216.33 | 276.00 | 1764.64 | 18.44 | 26.17 | 251.33 |
November | 242.67 | 0.63 | 0.61 | 01-NOV-07:49 | 2759.80 | 27.67 | 190.83 | 216.50 | 2350.84 | 32.77 | 226.33 | 186.50 |
December | 160.33 | 0.63 | 0.61 | 01-DEC-09:39 | 2589.28 | 20.94 | 72.00 | 197.00 | 2983.47 | 36.32 | 149.67 | 155.33 |
Annual Sum or Average | 3714.00 | 0.64 | 2758.52 | 17.68 | 1070.67 | 3591.17 | 1378.03 | 19.93 | 775.17 | 3120.83 | ||
Minimum of Months | 160.33 | 0.63 | 0.61 | 1341.42 | 9.95 | 0.00 | 197.00 | 809.04 | 14.64 | 0.00 | 155.33 | |
Maximum of Months | 471.00 | 0.65 | 0.61 | 7393.97 | 32.88 | 218.17 | 384.17 | 2983.47 | 36.32 | 226.33 | 333.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.65 | 0.61 | 01-JAN-09:20 | 767.39 | 13.13 | 44.17 | 187.83 | 519.47 | 16.48 | 62.00 | 114.50 |
February | 259.50 | 0.64 | 0.61 | 01-FEB-08:20 | 1323.36 | 15.60 | 64.00 | 218.50 | 689.00 | 15.00 | 38.17 | 165.33 |
March | 247.00 | 0.64 | 0.61 | 01-MAR-07:30 | 2284.53 | 15.77 | 58.00 | 293.50 | 1031.54 | 15.56 | 36.83 | 237.33 |
April | 379.50 | 0.63 | 0.61 | 01-APR-06:19 | 2418.80 | 12.93 | 48.00 | 337.67 | 1438.15 | 12.18 | 0.00 | 295.00 |
May | 427.83 | 0.63 | 0.61 | 01-MAY-06:49 | 2617.78 | 12.42 | 43.33 | 381.17 | 1143.12 | 12.28 | 0.00 | 338.83 |
June | 375.17 | 0.64 | 0.61 | 01-JUN-04:00 | 2643.27 | 9.77 | 0.00 | 392.50 | 1523.54 | 12.06 | 0.00 | 344.17 |
July | 471.00 | 0.65 | 0.61 | 01-JUL-04:49 | 2577.69 | 8.88 | 3.67 | 392.33 | 1167.96 | 10.91 | 0.00 | 356.33 |
August | 366.67 | 0.64 | 0.61 | 01-AUG-05:30 | 3038.87 | 12.22 | 48.33 | 364.67 | 1261.62 | 11.71 | 3.17 | 324.33 |
September | 301.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2363.45 | 15.45 | 63.17 | 314.50 | 1404.34 | 15.56 | 39.67 | 272.83 |
October | 245.33 | 0.65 | 0.61 | 01-OCT-07:19 | 2059.18 | 15.88 | 62.83 | 260.17 | 946.08 | 15.38 | 37.67 | 210.33 |
November | 242.67 | 0.64 | 0.61 | 01-NOV-07:49 | 1000.42 | 15.12 | 64.00 | 196.83 | 520.92 | 14.53 | 41.50 | 125.83 |
December | 160.33 | 0.65 | 0.61 | 01-DEC-09:39 | 868.50 | 14.93 | 38.17 | 169.00 | 523.08 | 17.08 | 38.83 | 91.33 |
Annual Sum or Average | 3714.00 | 0.64 | 2166.70 | 12.98 | 537.67 | 3508.67 | 1088.20 | 13.52 | 297.83 | 2876.17 | ||
Minimum of Months | 160.33 | 0.63 | 0.61 | 767.39 | 8.88 | 0.00 | 169.00 | 519.47 | 10.91 | 0.00 | 91.33 | |
Maximum of Months | 471.00 | 0.65 | 0.61 | 3038.87 | 15.88 | 64.00 | 392.50 | 1523.54 | 17.08 | 62.00 | 356.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.66 | 0.61 | 01-JAN-09:50 | 423.75 | 0.00 | 0.00 | 156.00 | 242.01 | 0.00 | 0.00 | 17.83 |
February | 259.50 | 0.65 | 0.61 | 01-FEB-08:50 | 535.62 | 0.00 | 0.00 | 197.33 | 318.09 | 0.00 | 0.00 | 104.00 |
March | 247.00 | 0.64 | 0.61 | 01-MAR-07:00 | 718.04 | 0.00 | 0.00 | 283.67 | 448.08 | 0.00 | 0.00 | 187.67 |
April | 379.50 | 0.63 | 0.61 | 01-APR-06:40 | 847.93 | 0.00 | 0.00 | 341.33 | 514.95 | 0.00 | 0.00 | 284.00 |
May | 427.83 | 0.63 | 0.61 | 01-MAY-06:49 | 1052.41 | 0.00 | 0.00 | 393.17 | 629.62 | 0.00 | 0.00 | 356.17 |
June | 375.17 | 0.63 | 0.61 | 01-JUN-05:10 | 1104.94 | 0.00 | 0.00 | 406.17 | 684.72 | 0.00 | 0.00 | 376.17 |
July | 471.00 | 0.64 | 0.61 | 01-JUL-04:00 | 940.55 | 0.00 | 0.00 | 415.67 | 587.34 | 0.00 | 0.00 | 366.83 |
August | 366.67 | 0.63 | 0.61 | 01-AUG-05:40 | 814.76 | 0.00 | 0.00 | 380.17 | 528.63 | 0.00 | 0.00 | 329.67 |
September | 301.17 | 0.63 | 0.61 | 01-SEP-07:40 | 776.70 | 0.00 | 0.00 | 305.00 | 498.22 | 0.00 | 0.00 | 239.50 |
October | 245.33 | 0.65 | 0.61 | 01-OCT-07:40 | 577.41 | 0.00 | 0.00 | 242.00 | 370.33 | 0.00 | 0.00 | 142.33 |
November | 242.67 | 0.66 | 0.61 | 01-NOV-07:00 | 457.46 | 0.00 | 0.00 | 170.67 | 260.91 | 0.00 | 0.00 | 39.50 |
December | 160.33 | 0.68 | 0.61 | 01-DEC-09:50 | 387.39 | 0.00 | 0.00 | 125.83 | 240.36 | 0.00 | 0.00 | 16.83 |
Annual Sum or Average | 3714.00 | 0.64 | 779.26 | 0.00 | 0.00 | 3417.00 | 480.80 | 0.00 | 0.00 | 2460.50 | ||
Minimum of Months | 160.33 | 0.63 | 0.61 | 387.39 | 0.00 | 0.00 | 125.83 | 240.36 | 0.00 | 0.00 | 16.83 | |
Maximum of Months | 471.00 | 0.68 | 0.61 | 1104.94 | 0.00 | 0.00 | 415.67 | 684.72 | 0.00 | 0.00 | 376.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.65 | 0.61 | 01-JAN-09:39 | 914.78 | 15.57 | 68.67 | 190.50 | 489.14 | 14.66 | 40.67 | 115.17 |
February | 259.50 | 0.64 | 0.61 | 01-FEB-08:50 | 1202.40 | 13.57 | 42.17 | 218.83 | 680.21 | 15.12 | 38.00 | 168.33 |
March | 247.00 | 0.64 | 0.61 | 01-MAR-07:00 | 2038.86 | 15.81 | 58.83 | 294.83 | 1157.24 | 15.68 | 38.50 | 235.83 |
April | 379.50 | 0.63 | 0.61 | 01-APR-07:10 | 2560.31 | 12.90 | 48.50 | 335.67 | 1078.45 | 12.25 | 0.00 | 293.50 |
May | 427.83 | 0.63 | 0.61 | 01-MAY-06:00 | 2550.60 | 10.17 | 0.00 | 383.67 | 1431.46 | 12.39 | 1.50 | 340.33 |
June | 375.17 | 0.64 | 0.61 | 01-JUN-05:49 | 2687.41 | 9.89 | 0.00 | 390.00 | 1215.47 | 14.45 | 35.17 | 352.67 |
July | 471.00 | 0.65 | 0.61 | 01-JUL-05:10 | 2972.59 | 8.41 | 0.00 | 392.17 | 1260.28 | 10.72 | 0.00 | 347.00 |
August | 366.67 | 0.64 | 0.61 | 01-AUG-05:00 | 2686.38 | 9.62 | 8.50 | 369.17 | 1651.00 | 11.86 | 5.50 | 330.00 |
September | 301.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2941.04 | 16.49 | 78.00 | 306.67 | 1764.43 | 16.29 | 49.83 | 257.50 |
October | 245.33 | 0.64 | 0.61 | 01-OCT-07:40 | 1968.39 | 15.92 | 63.50 | 260.83 | 925.85 | 15.98 | 43.00 | 209.33 |
November | 242.67 | 0.64 | 0.61 | 01-NOV-07:00 | 890.04 | 12.97 | 41.33 | 197.50 | 513.81 | 14.30 | 38.67 | 120.67 |
December | 160.33 | 0.66 | 0.61 | 01-DEC-09:39 | 866.75 | 13.96 | 31.83 | 171.00 | 526.88 | 15.88 | 31.67 | 83.83 |
Annual Sum or Average | 3714.00 | 0.64 | 2211.36 | 12.34 | 441.33 | 3510.83 | 1137.06 | 13.70 | 322.50 | 2854.17 | ||
Minimum of Months | 160.33 | 0.63 | 0.61 | 866.75 | 8.41 | 0.00 | 171.00 | 489.14 | 10.72 | 0.00 | 83.83 | |
Maximum of Months | 471.00 | 0.66 | 0.61 | 2972.59 | 16.49 | 78.00 | 392.17 | 1764.43 | 16.29 | 49.83 | 352.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.64 | 0.61 | 01-JAN-09:20 | 2208.00 | 22.49 | 139.83 | 210.00 | 2060.98 | 31.66 | 208.83 | 176.83 |
February | 259.50 | 0.63 | 0.61 | 01-FEB-08:20 | 4342.15 | 30.37 | 218.17 | 236.17 | 1914.38 | 27.16 | 156.67 | 214.50 |
March | 247.00 | 0.63 | 0.61 | 01-MAR-07:40 | 7394.07 | 31.35 | 206.50 | 304.67 | 1489.03 | 16.98 | 7.50 | 258.83 |
April | 379.50 | 0.64 | 0.61 | 01-APR-06:49 | 1878.52 | 11.45 | 0.00 | 337.83 | 1072.17 | 16.22 | 0.00 | 297.00 |
May | 427.83 | 0.64 | 0.61 | 01-MAY-06:49 | 1727.31 | 11.42 | 0.00 | 376.50 | 971.66 | 16.13 | 0.00 | 333.67 |
June | 375.17 | 0.64 | 0.61 | 01-JUN-05:40 | 1505.14 | 11.31 | 0.00 | 384.17 | 892.19 | 16.02 | 0.00 | 332.67 |
July | 471.00 | 0.65 | 0.61 | 01-JUL-05:10 | 1342.07 | 9.91 | 0.00 | 380.00 | 809.90 | 14.62 | 0.00 | 322.67 |
August | 366.67 | 0.64 | 0.61 | 01-AUG-05:49 | 1584.35 | 10.98 | 0.00 | 361.00 | 975.59 | 15.84 | 0.00 | 315.67 |
September | 301.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2609.81 | 14.22 | 27.00 | 311.67 | 1290.31 | 17.11 | 0.00 | 277.67 |
October | 245.33 | 0.64 | 0.61 | 01-OCT-07:40 | 6771.32 | 32.55 | 213.33 | 276.00 | 1766.10 | 18.43 | 26.17 | 251.33 |
November | 242.67 | 0.63 | 0.61 | 01-NOV-07:49 | 2673.24 | 25.66 | 172.17 | 215.33 | 2351.85 | 32.76 | 226.33 | 186.50 |
December | 160.33 | 0.63 | 0.61 | 01-DEC-09:39 | 2587.58 | 20.91 | 72.00 | 197.00 | 2984.15 | 36.32 | 149.67 | 155.50 |
Annual Sum or Average | 3714.00 | 0.64 | 2751.39 | 17.50 | 1049.00 | 3590.33 | 1379.19 | 19.92 | 775.17 | 3122.83 | ||
Minimum of Months | 160.33 | 0.63 | 0.61 | 1342.07 | 9.91 | 0.00 | 197.00 | 809.90 | 14.62 | 0.00 | 155.50 | |
Maximum of Months | 471.00 | 0.65 | 0.61 | 7394.07 | 32.55 | 218.17 | 384.17 | 2984.15 | 36.32 | 226.33 | 333.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.65 | 0.61 | 01-JAN-09:20 | 767.36 | 13.12 | 44.17 | 188.00 | 519.96 | 16.47 | 62.00 | 114.67 |
February | 259.50 | 0.64 | 0.61 | 01-FEB-08:20 | 1323.25 | 15.59 | 64.00 | 218.50 | 689.64 | 14.99 | 38.17 | 165.50 |
March | 247.00 | 0.64 | 0.61 | 01-MAR-07:30 | 2284.29 | 15.76 | 58.00 | 293.17 | 1032.41 | 15.55 | 36.83 | 238.17 |
April | 379.50 | 0.63 | 0.61 | 01-APR-06:19 | 2418.76 | 12.92 | 48.00 | 337.67 | 1439.12 | 12.18 | 0.00 | 295.17 |
May | 427.83 | 0.63 | 0.61 | 01-MAY-06:49 | 2618.15 | 12.41 | 43.33 | 381.17 | 1144.19 | 12.27 | 0.00 | 339.00 |
June | 375.17 | 0.64 | 0.61 | 01-JUN-04:00 | 2643.21 | 9.76 | 0.00 | 392.50 | 1524.54 | 12.05 | 0.00 | 344.33 |
July | 471.00 | 0.65 | 0.61 | 01-JUL-04:49 | 2577.74 | 8.87 | 3.67 | 392.33 | 1168.75 | 10.90 | 0.00 | 356.33 |
August | 366.67 | 0.64 | 0.61 | 01-AUG-05:30 | 3038.57 | 12.21 | 48.33 | 364.83 | 1262.41 | 11.71 | 3.17 | 324.33 |
September | 301.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2362.98 | 15.43 | 63.17 | 314.33 | 1405.12 | 15.55 | 39.67 | 273.00 |
October | 245.33 | 0.65 | 0.61 | 01-OCT-07:19 | 2058.78 | 15.87 | 62.83 | 260.17 | 946.74 | 15.38 | 37.67 | 210.67 |
November | 242.67 | 0.64 | 0.61 | 01-NOV-07:49 | 1000.40 | 15.11 | 64.00 | 196.83 | 521.47 | 14.53 | 41.50 | 126.00 |
December | 160.33 | 0.65 | 0.61 | 01-DEC-09:39 | 868.20 | 14.91 | 38.17 | 168.83 | 523.50 | 17.07 | 38.83 | 91.33 |
Annual Sum or Average | 3714.00 | 0.64 | 2166.60 | 12.97 | 537.67 | 3508.33 | 1089.00 | 13.51 | 297.83 | 2878.50 | ||
Minimum of Months | 160.33 | 0.63 | 0.61 | 767.36 | 8.87 | 0.00 | 168.83 | 519.96 | 10.90 | 0.00 | 91.33 | |
Maximum of Months | 471.00 | 0.65 | 0.61 | 3038.57 | 15.87 | 64.00 | 392.50 | 1524.54 | 17.07 | 62.00 | 356.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.66 | 0.61 | 01-JAN-09:50 | 423.87 | 0.00 | 0.00 | 156.17 | 242.32 | 0.00 | 0.00 | 18.17 |
February | 259.50 | 0.65 | 0.61 | 01-FEB-08:50 | 535.69 | 0.00 | 0.00 | 197.33 | 318.45 | 0.00 | 0.00 | 104.17 |
March | 247.00 | 0.64 | 0.61 | 01-MAR-07:00 | 718.00 | 0.00 | 0.00 | 283.50 | 448.51 | 0.00 | 0.00 | 187.67 |
April | 379.50 | 0.63 | 0.61 | 01-APR-06:40 | 848.00 | 0.00 | 0.00 | 341.33 | 515.48 | 0.00 | 0.00 | 284.33 |
May | 427.83 | 0.63 | 0.61 | 01-MAY-06:49 | 1052.61 | 0.00 | 0.00 | 393.17 | 630.30 | 0.00 | 0.00 | 356.33 |
June | 375.17 | 0.63 | 0.61 | 01-JUN-05:10 | 1104.90 | 0.00 | 0.00 | 406.17 | 685.31 | 0.00 | 0.00 | 376.33 |
July | 471.00 | 0.64 | 0.61 | 01-JUL-04:00 | 940.57 | 0.00 | 0.00 | 415.67 | 587.84 | 0.00 | 0.00 | 366.83 |
August | 366.67 | 0.63 | 0.61 | 01-AUG-05:40 | 814.65 | 0.00 | 0.00 | 380.17 | 529.05 | 0.00 | 0.00 | 329.83 |
September | 301.17 | 0.63 | 0.61 | 01-SEP-07:40 | 776.58 | 0.00 | 0.00 | 305.00 | 498.65 | 0.00 | 0.00 | 239.67 |
October | 245.33 | 0.65 | 0.61 | 01-OCT-07:40 | 577.30 | 0.00 | 0.00 | 241.83 | 370.65 | 0.00 | 0.00 | 142.50 |
November | 242.67 | 0.66 | 0.61 | 01-NOV-07:00 | 457.60 | 0.00 | 0.00 | 170.67 | 261.24 | 0.00 | 0.00 | 39.83 |
December | 160.33 | 0.68 | 0.61 | 01-DEC-09:50 | 387.32 | 0.00 | 0.00 | 125.67 | 240.59 | 0.00 | 0.00 | 16.83 |
Annual Sum or Average | 3714.00 | 0.64 | 779.27 | 0.00 | 0.00 | 3416.67 | 481.26 | 0.00 | 0.00 | 2462.50 | ||
Minimum of Months | 160.33 | 0.63 | 0.61 | 387.32 | 0.00 | 0.00 | 125.67 | 240.59 | 0.00 | 0.00 | 16.83 | |
Maximum of Months | 471.00 | 0.68 | 0.61 | 1104.90 | 0.00 | 0.00 | 415.67 | 685.31 | 0.00 | 0.00 | 376.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.65 | 0.61 | 01-JAN-09:39 | 914.75 | 15.57 | 68.67 | 190.50 | 489.64 | 14.65 | 40.67 | 115.83 |
February | 259.50 | 0.64 | 0.61 | 01-FEB-08:50 | 1202.29 | 13.56 | 42.17 | 218.83 | 680.84 | 15.11 | 38.00 | 168.33 |
March | 247.00 | 0.64 | 0.61 | 01-MAR-07:00 | 2038.60 | 15.80 | 58.83 | 294.83 | 1158.12 | 15.68 | 38.50 | 235.83 |
April | 379.50 | 0.63 | 0.61 | 01-APR-07:10 | 2560.26 | 12.89 | 48.50 | 335.67 | 1079.44 | 12.24 | 0.00 | 293.50 |
May | 427.83 | 0.63 | 0.61 | 01-MAY-06:00 | 2550.82 | 10.15 | 0.00 | 383.50 | 1432.61 | 12.39 | 1.50 | 340.50 |
June | 375.17 | 0.64 | 0.61 | 01-JUN-05:49 | 2687.40 | 9.88 | 0.00 | 390.00 | 1216.48 | 14.44 | 35.17 | 352.67 |
July | 471.00 | 0.65 | 0.61 | 01-JUL-05:10 | 2972.60 | 8.39 | 0.00 | 392.17 | 1261.15 | 10.71 | 0.00 | 347.00 |
August | 366.67 | 0.64 | 0.61 | 01-AUG-05:00 | 2686.06 | 9.60 | 8.50 | 369.17 | 1651.79 | 11.85 | 5.50 | 330.00 |
September | 301.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2940.50 | 16.48 | 78.00 | 306.50 | 1765.39 | 16.29 | 49.83 | 257.67 |
October | 245.33 | 0.64 | 0.61 | 01-OCT-07:40 | 1967.94 | 15.91 | 63.50 | 260.83 | 926.53 | 15.97 | 43.00 | 209.33 |
November | 242.67 | 0.64 | 0.61 | 01-NOV-07:00 | 890.03 | 12.96 | 41.33 | 197.67 | 514.35 | 14.30 | 38.67 | 120.67 |
December | 160.33 | 0.66 | 0.61 | 01-DEC-09:39 | 866.44 | 13.95 | 31.83 | 170.83 | 527.28 | 15.87 | 31.67 | 84.33 |
Annual Sum or Average | 3714.00 | 0.64 | 2211.23 | 12.33 | 441.33 | 3510.50 | 1137.89 | 13.70 | 322.50 | 2855.67 | ||
Minimum of Months | 160.33 | 0.63 | 0.61 | 866.44 | 8.39 | 0.00 | 170.83 | 489.64 | 10.71 | 0.00 | 84.33 | |
Maximum of Months | 471.00 | 0.66 | 0.61 | 2972.60 | 16.48 | 78.00 | 392.17 | 1765.39 | 16.29 | 49.83 | 352.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.383829E+10 | 23628.26 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191177E+10 | 18824.19 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137781E+09 | 10032.53 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5733050.72 | 3250.25 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.224927E+09 | 6685.64 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.910734E+09 | 13790.90 | 21-DEC-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.702923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.383829E+10 | 23628.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 26292264.42 | 2093.63 | 09-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 757798.77 | 196.35 | 18-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27050063.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26292264.42 | 2093.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.515351E+09 | 4688.27 | 06-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223453E+09 | 9859.23 | 14-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16522693.32 | 1491.71 | 25-MAR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 686235.64 | 1255.71 | 12-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4189254.93 | 487.41 | 28-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87220622.16 | 1857.42 | 22-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337403E+09 | 3982.32 | 12-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.515351E+09 | 9859.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.739189E+09 | 15765.99 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288209E+09 | 15820.65 | 14-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26935199.34 | 12098.62 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1023369.78 | 933.32 | 18-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44104.05 | 58.74 | 18-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6114976.10 | 1552.44 | 28-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117433E+09 | 15733.04 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.368840E+09 | 15852.02 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.739189E+09 | 15852.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 67113888.59 | 1694.22 | 17-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67113888.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 67113888.59 | 1694.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.915894E+11 | 267821.03 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.538159E+11 | 219340.73 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.934095E+10 | 164510.38 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.318499E+10 | 113213.77 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152985E+09 | 33071.13 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.557518E+09 | 37527.51 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231869E+11 | 165516.87 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.609204E+11 | 240296.57 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.915894E+11 | 267821.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.447082E+10 | 468762.48 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 71564522.87 | 31035.75 | 21-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6650224.46 | 7206.20 | 26-DEC-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.447082E+10 | 468762.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.247661E+11 | 118218.20 | 02-JAN-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121084E+11 | 126659.60 | 10-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301423E+10 | 127420.19 | 29-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.652288E+09 | 123628.99 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4235028.32 | 6070.30 | 18-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.869728E+09 | 122166.74 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.654177E+10 | 118918.70 | 14-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171878E+11 | 117714.15 | 27-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.651445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.247661E+11 | 127420.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.334818E+11 | 153975.41 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.186352E+11 | 156097.20 | 10-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.757638E+10 | 155714.26 | 25-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204137E+10 | 118758.69 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.480337E+09 | 60415.81 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 70300441.44 | 17142.46 | 14-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.246075E+09 | 30371.76 | 27-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.472314E+10 | 125433.18 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154613E+11 | 152365.61 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270807E+11 | 153556.23 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.334818E+11 | 156097.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.324987E+11 | 223582.17 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158103E+11 | 223108.10 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.620432E+10 | 218203.60 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.231985E+10 | 141609.92 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.447597E+09 | 81955.01 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45048250.35 | 11932.37 | 14-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88578643.13 | 29492.95 | 27-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330082E+10 | 168761.63 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137122E+11 | 221254.26 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253756E+11 | 222978.03 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.998030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.324987E+11 | 223582.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.278629E+11 | 149780.06 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150478E+11 | 149466.74 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.589790E+10 | 146143.11 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.175131E+10 | 72777.75 | 18-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.346546E+09 | 49044.58 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13599467.05 | 7290.31 | 14-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 58105017.74 | 9093.58 | 28-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347571E+10 | 94834.06 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120748E+11 | 148204.28 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213713E+11 | 149366.93 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.878999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.278629E+11 | 149780.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118359E+11 | 31230.97 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.764939E+10 | 27425.49 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.260697E+10 | 21825.27 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.937621E+09 | 16452.41 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113447E+09 | 7929.12 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5853799.49 | 1438.45 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.367577E+09 | 8881.56 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.441495E+10 | 21455.91 | 13-NOV-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.951512E+10 | 27665.24 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.374468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118359E+11 | 31230.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.507215E+10 | 79125.51 | 09-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227594E+10 | 78827.53 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.471303E+09 | 77350.73 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19868600.31 | 13272.10 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199933E+09 | 76812.35 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133789E+10 | 78533.15 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.319369E+10 | 79008.32 | 26-DEC-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.507215E+10 | 79125.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.649740E+10 | 13230.26 | 02-JAN-04:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427151E+10 | 13191.26 | 06-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204271E+10 | 13232.56 | 13-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.757872E+09 | 13168.52 | 15-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124506E+09 | 13102.80 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12135083.43 | 6765.60 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49643670.61 | 7657.08 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105442E+10 | 13173.36 | 23-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.306297E+10 | 13270.07 | 27-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.548126E+10 | 13231.06 | 18-DEC-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.649740E+10 | 13270.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.574509E+10 | 17651.55 | 07-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.366110E+10 | 17549.37 | 14-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204471E+10 | 17233.95 | 25-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.724009E+09 | 17225.29 | 18-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.255910E+09 | 14741.59 | 19-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47954782.90 | 8733.37 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9364514.69 | 2098.99 | 03-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.186181E+09 | 8609.18 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133582E+10 | 17137.70 | 17-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.327221E+10 | 17438.88 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.505121E+10 | 17545.72 | 26-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.574509E+10 | 17651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.674960E+10 | 26318.25 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406848E+10 | 26288.18 | 18-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.244753E+10 | 25814.96 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115508E+10 | 25846.49 | 18-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.430009E+09 | 17698.85 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 90666179.42 | 11042.66 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9494592.07 | 1925.39 | 03-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184893E+09 | 9840.13 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144159E+10 | 25587.10 | 16-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.392353E+10 | 26166.94 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.589610E+10 | 26327.18 | 26-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.674960E+10 | 26327.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.509194E+10 | 18115.64 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.320537E+10 | 18077.13 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195647E+10 | 17768.85 | 25-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.806790E+09 | 17757.12 | 18-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.267943E+09 | 11372.73 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47529929.20 | 3420.04 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1112182.29 | 264.27 | 03-AUG-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121826E+09 | 3005.30 | 26-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123445E+10 | 17576.83 | 16-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293110E+10 | 17978.14 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.427937E+10 | 18089.65 | 26-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.509194E+10 | 18115.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1564.80 | 1564.80 | 0.86 | 02-JAN-06:01 | 0.86 | 0.00 |
February | 0.00 | 0.00 | 0.792885E+09 | 0.792885E+09 | 53102.46 | 27-FEB-15:00 | 53102.46 | 0.00 |
March | 0.00 | 0.00 | 0.104864E+10 | 0.104864E+10 | 27826.20 | 18-MAR-16:00 | 27826.20 | 0.01 |
April | 0.00 | 0.00 | 0.100492E+11 | 0.100492E+11 | 120461.23 | 27-APR-14:30 | 120461.23 | 0.04 |
May | 0.00 | 0.00 | 0.165309E+11 | 0.165268E+11 | 98394.03 | 04-MAY-15:00 | 98394.03 | 0.12 |
June | 0.00 | 0.00 | 0.323628E+11 | 0.323536E+11 | 110382.39 | 28-JUN-15:20 | 110382.39 | 0.23 |
July | 0.00 | 0.00 | 0.589222E+11 | 0.579823E+11 | 142416.23 | 31-JUL-16:00 | 123535.21 | 0.47 |
August | 0.00 | 0.00 | 0.818136E+11 | 0.789533E+11 | 151565.34 | 29-AUG-14:30 | 132295.83 | 0.63 |
September | 0.00 | 0.00 | 0.256484E+11 | 0.252054E+11 | 110855.85 | 14-SEP-13:00 | 83678.75 | 0.31 |
October | 0.00 | 0.00 | 0.454281E+10 | 0.454281E+10 | 75993.94 | 04-OCT-15:00 | 75993.94 | 0.01 |
November | 0.00 | 0.00 | 0.656917E+09 | 0.656917E+09 | 35166.83 | 04-NOV-14:00 | 35166.83 | 0.01 |
December | 0.00 | 0.00 | 2025.31 | 2025.31 | 0.81 | 26-DEC-05:52 | 0.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.232368E+12 | 0.228112E+12 | 0.15 | |||
Minimum of Months | 0.00 | 0.00 | 1564.80 | 1564.80 | 0.81 | 0.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.818136E+11 | 0.789533E+11 | 151565.34 | 132295.83 | 0.63 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 66618.44 | 66618.44 | 3.24 | 02-JAN-06:13 | 3.24 | 0.01 |
February | 0.00 | 0.00 | 0.523285E+10 | 0.523285E+10 | 360598.40 | 27-FEB-15:00 | 360598.40 | 0.01 |
March | 0.00 | 0.00 | 0.750277E+10 | 0.750277E+10 | 252564.06 | 18-MAR-14:00 | 252564.06 | 0.01 |
April | 0.00 | 0.00 | 0.744492E+11 | 0.744492E+11 | 1016421.83 | 27-APR-14:50 | 1016421.83 | 0.04 |
May | 0.00 | 0.00 | 0.143109E+12 | 0.143086E+12 | 914705.40 | 04-MAY-15:00 | 914705.40 | 0.12 |
June | 0.00 | 0.00 | 0.265622E+12 | 0.265619E+12 | 992812.98 | 28-JUN-15:30 | 992812.98 | 0.22 |
July | 0.00 | 0.00 | 0.469568E+12 | 0.463357E+12 | 1254461.21 | 31-JUL-16:00 | 1072881.77 | 0.42 |
August | 0.00 | 0.00 | 0.629965E+12 | 0.609744E+12 | 1322050.96 | 29-AUG-14:30 | 1145683.56 | 0.52 |
September | 0.00 | 0.00 | 0.228374E+12 | 0.223385E+12 | 1063603.05 | 14-SEP-13:00 | 778202.30 | 0.30 |
October | 0.00 | 0.00 | 0.359190E+11 | 0.359190E+11 | 659281.03 | 04-OCT-15:00 | 659281.03 | 0.01 |
November | 0.00 | 0.00 | 0.577554E+10 | 0.577554E+10 | 316901.29 | 04-NOV-14:00 | 316901.29 | 0.02 |
December | 0.00 | 0.00 | 84346.93 | 84346.93 | 3.55 | 20-DEC-06:40 | 3.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186552E+13 | 0.183407E+13 | 0.14 | |||
Minimum of Months | 0.00 | 0.00 | 66618.44 | 66618.44 | 3.24 | 3.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.629965E+12 | 0.609744E+12 | 1322050.96 | 1145683.56 | 0.52 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 66560.84 | 66560.84 | 193.42 | 02-JAN-04:20 | 193.42 | 0.00 |
February | 0.00 | 0.00 | 0.427343E+09 | 0.427343E+09 | 27207.16 | 27-FEB-15:00 | 27207.16 | 0.00 |
March | 0.00 | 0.00 | 0.675303E+09 | 0.675303E+09 | 24756.03 | 18-MAR-14:00 | 24756.03 | 0.01 |
April | 0.00 | 0.00 | 0.770370E+10 | 0.770370E+10 | 120072.31 | 27-APR-14:50 | 120072.31 | 0.03 |
May | 0.00 | 0.00 | 0.147982E+11 | 0.147942E+11 | 101935.11 | 04-MAY-15:00 | 101935.11 | 0.12 |
June | 0.00 | 0.00 | 0.281241E+11 | 0.281221E+11 | 120043.88 | 28-JUN-15:20 | 120043.88 | 0.21 |
July | 0.00 | 0.00 | 0.504478E+11 | 0.497805E+11 | 146594.48 | 31-JUL-16:00 | 127662.40 | 0.41 |
August | 0.00 | 0.00 | 0.671747E+11 | 0.651020E+11 | 152469.12 | 10-AUG-15:40 | 140004.55 | 0.51 |
September | 0.00 | 0.00 | 0.226088E+11 | 0.222423E+11 | 107776.85 | 14-SEP-13:10 | 83931.79 | 0.29 |
October | 0.00 | 0.00 | 0.313174E+10 | 0.313174E+10 | 65198.51 | 04-OCT-15:00 | 65198.51 | 0.00 |
November | 0.00 | 0.00 | 0.562307E+09 | 0.562307E+09 | 31532.84 | 04-NOV-14:00 | 31532.84 | 0.01 |
December | 0.00 | 0.00 | 79833.72 | 79833.72 | 314.68 | 26-DEC-04:20 | 314.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.195654E+12 | 0.192542E+12 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 66560.84 | 66560.84 | 193.42 | 193.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.671747E+11 | 0.651020E+11 | 152469.12 | 140004.55 | 0.51 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1261208.54 | 1261208.54 | 9142.44 | 11-JAN-06:02 | 9142.44 | 0.00 |
February | 0.00 | 0.00 | 0.447807E+09 | 0.439967E+09 | 47457.93 | 24-FEB-05:02 | 32243.74 | 0.00 |
March | 0.00 | 0.00 | 0.116881E+09 | 0.109503E+09 | 23875.08 | 10-MAR-06:03 | 10943.44 | 0.00 |
April | 0.00 | 0.00 | 0.403601E+10 | 0.403202E+10 | 60794.34 | 27-APR-16:00 | 60794.34 | 0.02 |
May | 0.00 | 0.00 | 0.764494E+10 | 0.763956E+10 | 59367.42 | 15-MAY-16:00 | 59367.42 | 0.09 |
June | 0.00 | 0.00 | 0.159405E+11 | 0.159106E+11 | 59078.56 | 28-JUN-15:40 | 59078.56 | 0.16 |
July | 0.00 | 0.00 | 0.298102E+11 | 0.295269E+11 | 78614.37 | 31-JUL-12:10 | 69043.74 | 0.31 |
August | 0.00 | 0.00 | 0.419790E+11 | 0.414142E+11 | 91451.33 | 13-AUG-16:40 | 91451.33 | 0.41 |
September | 0.00 | 0.00 | 0.123264E+11 | 0.122432E+11 | 59374.75 | 11-SEP-15:00 | 59374.75 | 0.19 |
October | 0.00 | 0.00 | 0.160932E+10 | 0.159996E+10 | 44296.57 | 09-OCT-10:22 | 44296.57 | 0.00 |
November | 0.00 | 0.00 | 0.248574E+09 | 0.242013E+09 | 32093.81 | 04-NOV-04:02 | 21135.85 | 0.01 |
December | 0.00 | 0.00 | 5242049.13 | 5242049.13 | 11199.72 | 16-DEC-06:02 | 11199.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114166E+12 | 0.113165E+12 | 0.10 | |||
Minimum of Months | 0.00 | 0.00 | 1261208.54 | 1261208.54 | 9142.44 | 9142.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.419790E+11 | 0.414142E+11 | 91451.33 | 91451.33 | 0.41 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.321684E+12 | 0.321676E+12 | 124452.07 | 11-JAN-22:07 | 124452.07 | 0.00 |
February | 0.00 | 0.00 | 0.512873E+12 | 0.512631E+12 | 216585.62 | 27-FEB-15:00 | 216585.62 | 0.00 |
March | 0.00 | 0.00 | 0.816116E+12 | 0.815931E+12 | 394413.60 | 31-MAR-24:00 | 394413.60 | 0.00 |
April | 0.00 | 0.00 | 0.102912E+13 | 0.102882E+13 | 405882.19 | 27-APR-19:20 | 402166.84 | 0.00 |
May | 0.00 | 0.00 | 0.331671E+12 | 0.330569E+12 | 212776.02 | 31-MAY-23:20 | 211955.66 | 0.00 |
June | 0.00 | 0.00 | 0.560002E+12 | 0.558385E+12 | 304609.62 | 30-JUN-24:00 | 303795.15 | 0.00 |
July | 0.00 | 0.00 | 0.827921E+12 | 0.824936E+12 | 396933.76 | 31-JUL-23:55 | 396231.53 | 0.00 |
August | 0.00 | 0.00 | 0.107275E+13 | 0.106969E+13 | 410766.80 | 29-AUG-21:00 | 404531.36 | 0.00 |
September | 0.00 | 0.00 | 0.325455E+12 | 0.322645E+12 | 211624.01 | 30-SEP-24:00 | 211375.87 | 0.00 |
October | 0.00 | 0.00 | 0.575085E+12 | 0.574558E+12 | 303125.64 | 31-OCT-24:00 | 303125.64 | 0.00 |
November | 0.00 | 0.00 | 0.791457E+12 | 0.790883E+12 | 310601.76 | 04-NOV-18:00 | 307776.97 | 0.00 |
December | 0.00 | 0.00 | 0.106052E+13 | 0.106048E+13 | 400537.50 | 05-DEC-22:03 | 400537.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.822465E+13 | 0.821120E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.321684E+12 | 0.321676E+12 | 124452.07 | 124452.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107275E+13 | 0.106969E+13 | 410766.80 | 404531.36 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.397904E+10 | 0.397869E+10 | 2154.48 | 05-JAN-16:10 | 2154.48 | 0.00 |
February | 0.00 | 0.00 | 0.871943E+10 | 0.870877E+10 | 4451.15 | 27-FEB-16:20 | 4451.15 | 0.00 |
March | 0.00 | 0.00 | 0.153099E+11 | 0.153014E+11 | 7560.31 | 31-MAR-24:00 | 7560.31 | 0.00 |
April | 0.00 | 0.00 | 0.200461E+11 | 0.200332E+11 | 8688.04 | 26-APR-17:50 | 8688.04 | 0.00 |
May | 0.00 | 0.00 | 0.565176E+10 | 0.561217E+10 | 4072.44 | 31-MAY-24:00 | 4056.19 | 0.00 |
June | 0.00 | 0.00 | 0.106127E+11 | 0.105560E+11 | 5943.65 | 30-JUN-24:00 | 5923.32 | 0.00 |
July | 0.00 | 0.00 | 0.162937E+11 | 0.161827E+11 | 7857.17 | 31-JUL-23:55 | 7836.55 | 0.00 |
August | 0.00 | 0.00 | 0.213466E+11 | 0.212072E+11 | 9130.94 | 06-AUG-18:36 | 9130.94 | 0.00 |
September | 0.00 | 0.00 | 0.564823E+10 | 0.554845E+10 | 3904.94 | 30-SEP-24:00 | 3897.89 | 0.00 |
October | 0.00 | 0.00 | 0.104193E+11 | 0.103955E+11 | 5566.61 | 31-OCT-24:00 | 5566.61 | 0.00 |
November | 0.00 | 0.00 | 0.146914E+11 | 0.146666E+11 | 6285.69 | 12-NOV-16:10 | 6285.69 | 0.00 |
December | 0.00 | 0.00 | 0.200170E+11 | 0.200145E+11 | 8056.06 | 10-DEC-15:25 | 8056.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152735E+12 | 0.152205E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.397904E+10 | 0.397869E+10 | 2154.48 | 2154.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.213466E+11 | 0.212072E+11 | 9130.94 | 9130.94 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.167273E+11 | 0.167273E+11 | 17136.08 | 05-JAN-16:10 | 17136.08 | 0.00 |
February | 0.00 | 0.00 | 0.666526E+11 | 0.665485E+11 | 40647.78 | 27-FEB-16:20 | 40647.78 | 0.00 |
March | 0.00 | 0.00 | 0.132193E+12 | 0.132108E+12 | 66781.65 | 31-MAR-24:00 | 66781.65 | 0.00 |
April | 0.00 | 0.00 | 0.182016E+12 | 0.181886E+12 | 82338.18 | 26-APR-17:50 | 82338.18 | 0.00 |
May | 0.00 | 0.00 | 0.473262E+11 | 0.469429E+11 | 37923.17 | 31-MAY-23:50 | 37725.15 | 0.00 |
June | 0.00 | 0.00 | 0.964232E+11 | 0.958661E+11 | 55621.63 | 30-JUN-24:00 | 55427.14 | 0.00 |
July | 0.00 | 0.00 | 0.152944E+12 | 0.151846E+12 | 75708.24 | 31-JUL-23:55 | 75505.79 | 0.00 |
August | 0.00 | 0.00 | 0.201250E+12 | 0.199860E+12 | 84717.07 | 06-AUG-18:17 | 84717.07 | 0.00 |
September | 0.00 | 0.00 | 0.482249E+11 | 0.472619E+11 | 34784.09 | 30-SEP-24:00 | 34710.88 | 0.00 |
October | 0.00 | 0.00 | 0.876194E+11 | 0.873852E+11 | 47018.57 | 31-OCT-24:00 | 47018.57 | 0.00 |
November | 0.00 | 0.00 | 0.123237E+12 | 0.122991E+12 | 56637.56 | 04-NOV-16:00 | 55627.33 | 0.00 |
December | 0.00 | 0.00 | 0.169561E+12 | 0.169536E+12 | 72932.27 | 05-DEC-15:50 | 72932.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.132417E+13 | 0.131896E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.167273E+11 | 0.167273E+11 | 17136.08 | 17136.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201250E+12 | 0.199860E+12 | 84717.07 | 84717.07 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.642259E+09 | 0.642259E+09 | 1555.70 | 05-JAN-16:10 | 1555.70 | 0.00 |
February | 0.00 | 0.00 | 0.511774E+10 | 0.510750E+10 | 4015.55 | 27-FEB-16:20 | 4015.55 | 0.00 |
March | 0.00 | 0.00 | 0.119505E+11 | 0.119422E+11 | 6216.83 | 31-MAR-23:20 | 6216.83 | 0.00 |
April | 0.00 | 0.00 | 0.174006E+11 | 0.173877E+11 | 8311.32 | 26-APR-17:50 | 8311.32 | 0.00 |
May | 0.00 | 0.00 | 0.420608E+10 | 0.416820E+10 | 3721.13 | 31-MAY-23:20 | 3690.36 | 0.00 |
June | 0.00 | 0.00 | 0.941064E+10 | 0.935520E+10 | 5460.54 | 30-JUN-24:00 | 5441.31 | 0.00 |
July | 0.00 | 0.00 | 0.151696E+11 | 0.150600E+11 | 7561.04 | 31-JUL-23:55 | 7540.72 | 0.00 |
August | 0.00 | 0.00 | 0.199714E+11 | 0.198326E+11 | 8604.70 | 06-AUG-18:38 | 8604.70 | 0.00 |
September | 0.00 | 0.00 | 0.432016E+10 | 0.422561E+10 | 3055.32 | 30-SEP-23:30 | 3047.18 | 0.00 |
October | 0.00 | 0.00 | 0.764303E+10 | 0.762010E+10 | 4566.99 | 04-OCT-16:50 | 4566.99 | 0.00 |
November | 0.00 | 0.00 | 0.107930E+11 | 0.107687E+11 | 5561.40 | 04-NOV-16:00 | 5461.24 | 0.00 |
December | 0.00 | 0.00 | 0.150723E+11 | 0.150699E+11 | 7121.27 | 05-DEC-15:50 | 7121.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121697E+12 | 0.121180E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.642259E+09 | 0.642259E+09 | 1555.70 | 1555.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199714E+11 | 0.198326E+11 | 8604.70 | 8604.70 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 96545.22 | 1604107.31 | 03-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58612.49 | 1195098.67 | 16-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16209.79 | 1191927.50 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5498.16 | 780046.82 | 11-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 965.31 | 319814.17 | 18-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 124.73 | 43355.03 | 14-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 7.16 | 2771.72 | 03-AUG-05:08 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 359.61 | 61452.56 | 27-SEP-05:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6882.28 | 992694.08 | 28-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 34570.89 | 1178915.54 | 24-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 69210.94 | 1220091.76 | 27-DEC-05:01 |
Annual Sum or Average | 0.00 | 23951.21 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 96545.22 | 1604107.31 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 824.90 | 22910.62 | 09-JAN-04:50 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 6692.01 | 931281.17 | 27-FEB-15:00 | 3.13 | 19370.47 | 25-FEB-05:02 |
March | 8441.89 | 646735.60 | 18-MAR-16:00 | 18.02 | 62725.28 | 22-MAR-10:20 |
April | 60034.12 | 1323634.84 | 27-APR-14:50 | 8.16 | 75057.86 | 01-APR-23:02 |
May | 118228.79 | 1287534.21 | 04-MAY-13:50 | 0.07 | 1652.00 | 14-MAY-07:32 |
June | 222801.68 | 1324877.68 | 22-JUN-14:50 | 63.78 | 169577.23 | 11-JUN-09:05 |
July | 353217.47 | 1635018.64 | 31-JUL-16:00 | 16.94 | 48882.18 | 27-JUL-23:22 |
August | 427036.92 | 1707498.07 | 29-AUG-14:30 | 21.28 | 65285.79 | 23-AUG-01:02 |
September | 182037.08 | 1342315.93 | 14-SEP-13:00 | 117.76 | 245342.61 | 24-SEP-14:02 |
October | 32565.58 | 1080903.71 | 04-OCT-11:40 | 1.57 | 35015.20 | 10-OCT-01:12 |
November | 7345.38 | 813324.35 | 04-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1059.85 | 70670.01 | 28-DEC-06:03 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 119278.25 | 20.75 | ||||
Minimum of Months | 824.90 | 22910.62 | 0.00 | 0.00 | ||
Maximum of Months | 427036.92 | 1707498.07 | 117.76 | 245342.61 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.01 | 145.47 | 11-JAN-06:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3550.16 | 601816.67 | 27-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4396.85 | 376039.45 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43947.82 | 1388816.21 | 27-APR-11:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 86929.27 | 1404463.34 | 04-MAY-13:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 171015.51 | 1450543.28 | 27-JUN-13:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 283743.68 | 1696192.77 | 15-JUL-17:42 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 361305.22 | 1806055.93 | 30-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 144108.44 | 1449116.89 | 08-SEP-14:40 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 22105.53 | 1075062.29 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3649.97 | 521962.61 | 04-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 18.65 | 74413.38 | 16-DEC-05:01 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 94505.57 | 0.00 | ||||
Minimum of Months | 0.01 | 145.47 | 0.00 | 0.00 | ||
Maximum of Months | 361305.22 | 1806055.93 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 163992.05 | 178798.48 | 11-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 310304.52 | 566716.53 | 27-FEB-15:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 459560.14 | 802835.26 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 648279.75 | 1409510.83 | 27-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 214889.72 | 640785.66 | 05-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 412351.95 | 944393.39 | 28-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 671998.27 | 1397005.09 | 24-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 934156.86 | 1664786.14 | 10-AUG-17:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 230120.03 | 642008.68 | 14-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 329086.28 | 671394.94 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 456371.89 | 833693.02 | 04-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 586559.53 | 603630.23 | 14-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 452793.87 | 0.00 | ||||
Minimum of Months | 163992.05 | 178798.48 | 0.00 | 0.00 | ||
Maximum of Months | 934156.86 | 1664786.14 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15535.55 | 52072.20 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 15718.86 | 52133.96 | 10-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16437.76 | 51957.88 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15106.62 | 50821.54 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15038.35 | 49260.82 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14838.96 | 47362.86 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13427.64 | 45746.70 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 14450.77 | 45085.04 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 13809.24 | 46044.22 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14181.71 | 47795.08 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14876.11 | 49645.82 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14861.26 | 51152.26 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 14852.00 | ||||
Minimum of Months | 0.00 | 0.00 | 13427.64 | 45085.04 | ||
Maximum of Months | 0.00 | 0.00 | 16437.76 | 52133.96 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 21.81 | 21662.63 | 05-JAN-06:40 | 1142.94 | 116042.67 | 07-JAN-06:30 |
February | 3548.45 | 548674.42 | 27-FEB-15:10 | 1166.78 | 111062.13 | 09-FEB-16:30 |
March | 4276.02 | 392496.20 | 18-MAR-16:00 | 1163.50 | 113802.45 | 24-MAR-05:30 |
April | 48442.44 | 2167337.56 | 27-APR-15:50 | 1302.63 | 91105.43 | 17-APR-09:30 |
May | 87939.13 | 2136614.21 | 05-MAY-15:50 | 700.68 | 75122.15 | 17-MAY-19:50 |
June | 172836.96 | 2151806.27 | 28-JUN-14:30 | 504.19 | 71525.83 | 14-JUN-14:30 |
July | 302593.38 | 2982305.68 | 31-JUL-16:00 | 766.81 | 56096.17 | 01-JUL-10:40 |
August | 431856.14 | 3376428.39 | 29-AUG-14:30 | 588.32 | 54852.12 | 15-AUG-06:20 |
September | 146221.74 | 2131050.43 | 13-SEP-13:50 | 405.53 | 66358.23 | 27-SEP-05:30 |
October | 20409.41 | 944028.31 | 04-OCT-15:00 | 828.89 | 93431.77 | 13-OCT-05:30 |
November | 3533.65 | 485706.24 | 04-NOV-14:00 | 2020.94 | 106277.56 | 14-NOV-06:40 |
December | 29.14 | 22626.19 | 02-DEC-07:00 | 1265.87 | 115264.18 | 11-DEC-06:50 |
Annual Sum or Average | 102715.82 | 985.85 | ||||
Minimum of Months | 21.81 | 21662.63 | 405.53 | 54852.12 | ||
Maximum of Months | 431856.14 | 3376428.39 | 2020.94 | 116042.67 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148208E+11 | 0.79 | 9831.35 | 01-JAN-00:33 | 1.41 |
February | 0.132733E+11 | 0.79 | 9831.35 | 01-FEB-05:02 | 1.40 |
March | 0.160113E+11 | 0.86 | 9831.35 | 01-MAR-04:10 | 1.41 |
April | 0.146871E+11 | 0.81 | 9831.35 | 01-APR-04:02 | 1.41 |
May | 0.157140E+11 | 0.84 | 9831.35 | 01-MAY-01:30 | 1.40 |
June | 0.157071E+11 | 0.86 | 9831.35 | 01-JUN-03:02 | 1.40 |
July | 0.154074E+11 | 0.82 | 9831.35 | 01-JUL-03:02 | 1.41 |
August | 0.167067E+11 | 0.89 | 9831.35 | 01-AUG-03:02 | 1.40 |
September | 0.155811E+11 | 0.86 | 9831.35 | 01-SEP-03:02 | 1.40 |
October | 0.155847E+11 | 0.83 | 9831.35 | 02-OCT-02:20 | 1.40 |
November | 0.150022E+11 | 0.83 | 9831.35 | 01-NOV-03:10 | 1.41 |
December | 0.147942E+11 | 0.79 | 9831.35 | 01-DEC-05:00 | 1.41 |
Annual Sum or Average | 0.183290E+12 | 0.83 | |||
Minimum of Months | 0.132733E+11 | 0.79 | 9831.35 | 1.40 | |
Maximum of Months | 0.167067E+11 | 0.89 | 9831.35 | 1.41 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.443129E+10 | 0.32 | 12145.95 | 02-JAN-06:01 | 1.27 |
February | 0.495542E+10 | 0.36 | 13132.69 | 14-FEB-06:01 | 1.35 |
March | 0.745228E+10 | 0.44 | 12013.06 | 14-MAR-15:20 | 1.27 |
April | 0.899689E+10 | 0.50 | 17672.25 | 27-APR-14:20 | 1.61 |
May | 0.826864E+10 | 0.46 | 14818.32 | 15-MAY-14:30 | 1.45 |
June | 0.988550E+10 | 0.53 | 20426.72 | 12-JUN-05:03 | 1.76 |
July | 0.118151E+11 | 0.59 | 18988.28 | 31-JUL-14:40 | 1.68 |
August | 0.138787E+11 | 0.67 | 20806.62 | 09-AUG-05:02 | 1.79 |
September | 0.839354E+10 | 0.47 | 16602.76 | 11-SEP-15:00 | 1.55 |
October | 0.726086E+10 | 0.42 | 14390.78 | 04-OCT-15:10 | 1.42 |
November | 0.601403E+10 | 0.38 | 12382.52 | 06-NOV-06:03 | 1.29 |
December | 0.584438E+10 | 0.37 | 12712.67 | 30-DEC-06:02 | 1.31 |
Annual Sum or Average | 0.971967E+11 | 0.46 | |||
Minimum of Months | 0.443129E+10 | 0.32 | 12013.06 | 1.27 | |
Maximum of Months | 0.138787E+11 | 0.67 | 20806.62 | 1.79 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.335988E+11 | 0.30 | 51862.90 | 02-JAN-06:01 | 0.81 |
February | 0.337020E+11 | 0.31 | 122920.26 | 08-FEB-06:02 | 1.36 |
March | 0.459540E+11 | 0.35 | 122920.26 | 24-MAR-05:03 | 1.36 |
April | 0.504860E+11 | 0.36 | 135809.21 | 27-APR-14:30 | 1.43 |
May | 0.631700E+11 | 0.41 | 123833.83 | 15-MAY-15:20 | 1.36 |
June | 0.714262E+11 | 0.45 | 129055.92 | 28-JUN-15:20 | 1.39 |
July | 0.810194E+11 | 0.46 | 148218.86 | 31-JUL-15:20 | 1.51 |
August | 0.925787E+11 | 0.51 | 167447.58 | 10-AUG-15:10 | 1.63 |
September | 0.672082E+11 | 0.42 | 146887.76 | 14-SEP-15:10 | 1.50 |
October | 0.489250E+11 | 0.35 | 116316.45 | 28-OCT-05:02 | 1.31 |
November | 0.362392E+11 | 0.31 | 113209.99 | 16-NOV-06:03 | 1.29 |
December | 0.345353E+11 | 0.30 | 112682.48 | 07-DEC-06:03 | 1.28 |
Annual Sum or Average | 0.658843E+12 | 0.38 | |||
Minimum of Months | 0.335988E+11 | 0.30 | 51862.90 | 0.81 | |
Maximum of Months | 0.925787E+11 | 0.51 | 167447.58 | 1.63 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.407350E+10 | 0.36 | 4726.23 | 02-JAN-04:01 | 0.73 |
February | 0.349418E+10 | 0.34 | 4726.23 | 06-FEB-05:01 | 0.73 |
March | 0.382405E+10 | 0.32 | 5536.69 | 14-MAR-15:40 | 0.80 |
April | 0.426441E+10 | 0.32 | 14833.63 | 27-APR-14:30 | 1.43 |
May | 0.543925E+10 | 0.36 | 14224.99 | 15-MAY-15:20 | 1.40 |
June | 0.653854E+10 | 0.41 | 15146.01 | 28-JUN-15:20 | 1.45 |
July | 0.776308E+10 | 0.43 | 17610.28 | 31-JUL-15:20 | 1.59 |
August | 0.876425E+10 | 0.46 | 19592.76 | 10-AUG-15:10 | 1.70 |
September | 0.564253E+10 | 0.36 | 15273.31 | 14-SEP-15:00 | 1.46 |
October | 0.383797E+10 | 0.30 | 10460.05 | 04-OCT-15:20 | 1.16 |
November | 0.324817E+10 | 0.29 | 4726.23 | 13-NOV-05:01 | 0.73 |
December | 0.358827E+10 | 0.31 | 4726.23 | 04-DEC-05:01 | 0.74 |
Annual Sum or Average | 0.604782E+11 | 0.36 | |||
Minimum of Months | 0.324817E+10 | 0.29 | 4726.23 | 0.73 | |
Maximum of Months | 0.876425E+10 | 0.46 | 19592.76 | 1.70 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.957351E+11 | 1.37 | 35743.38 | 01-JAN-00:05 | 1.36 |
February | 0.864704E+11 | 1.36 | 35743.38 | 01-FEB-00:10 | 1.37 |
March | 0.957351E+11 | 1.37 | 35743.38 | 01-MAR-00:10 | 1.36 |
April | 0.926468E+11 | 1.36 | 35743.38 | 01-APR-00:10 | 1.36 |
May | 0.957351E+11 | 1.36 | 35743.38 | 01-MAY-00:10 | 1.36 |
June | 0.926468E+11 | 1.36 | 35743.38 | 01-JUN-00:10 | 1.36 |
July | 0.957351E+11 | 1.36 | 35743.38 | 01-JUL-00:10 | 1.36 |
August | 0.957351E+11 | 1.36 | 35743.38 | 01-AUG-00:03 | 1.36 |
September | 0.926468E+11 | 1.36 | 35743.38 | 01-SEP-00:03 | 1.36 |
October | 0.957351E+11 | 1.36 | 35743.38 | 01-OCT-00:10 | 1.36 |
November | 0.926468E+11 | 1.36 | 35743.38 | 01-NOV-00:10 | 1.36 |
December | 0.957351E+11 | 1.37 | 35743.38 | 01-DEC-00:10 | 1.37 |
Annual Sum or Average | 0.112720E+13 | 1.36 | |||
Minimum of Months | 0.864704E+11 | 1.36 | 35743.38 | 1.36 | |
Maximum of Months | 0.957351E+11 | 1.37 | 35743.38 | 1.37 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153753E+10 | 0.93 | 574.05 | 01-JAN-00:10 | 0.93 |
February | 0.138874E+10 | 0.93 | 574.05 | 01-FEB-00:10 | 0.93 |
March | 0.153753E+10 | 0.93 | 574.05 | 01-MAR-00:10 | 0.93 |
April | 0.148793E+10 | 0.93 | 574.05 | 01-APR-00:10 | 0.93 |
May | 0.153753E+10 | 0.93 | 574.05 | 01-MAY-00:10 | 0.93 |
June | 0.148793E+10 | 0.93 | 574.05 | 01-JUN-00:10 | 0.93 |
July | 0.153753E+10 | 0.93 | 574.05 | 01-JUL-00:10 | 0.93 |
August | 0.153753E+10 | 0.92 | 574.05 | 01-AUG-00:03 | 0.93 |
September | 0.148793E+10 | 0.93 | 574.05 | 01-SEP-00:03 | 0.93 |
October | 0.153753E+10 | 0.93 | 574.05 | 01-OCT-00:10 | 0.93 |
November | 0.148793E+10 | 0.93 | 574.05 | 01-NOV-00:10 | 0.93 |
December | 0.153753E+10 | 0.93 | 574.05 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.181032E+11 | 0.93 | |||
Minimum of Months | 0.138874E+10 | 0.92 | 574.05 | 0.93 | |
Maximum of Months | 0.153753E+10 | 0.93 | 574.05 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147128E+11 | 0.93 | 5493.14 | 01-JAN-00:05 | 0.92 |
February | 0.132890E+11 | 0.93 | 5493.14 | 01-FEB-00:10 | 0.93 |
March | 0.147128E+11 | 0.93 | 5493.14 | 01-MAR-00:10 | 0.93 |
April | 0.142382E+11 | 0.93 | 5493.14 | 01-APR-00:10 | 0.93 |
May | 0.147128E+11 | 0.93 | 5493.14 | 01-MAY-00:10 | 0.93 |
June | 0.142382E+11 | 0.93 | 5493.14 | 01-JUN-00:10 | 0.93 |
July | 0.147128E+11 | 0.93 | 5493.14 | 01-JUL-00:10 | 0.93 |
August | 0.147128E+11 | 0.92 | 5493.14 | 01-AUG-00:03 | 0.93 |
September | 0.142382E+11 | 0.93 | 5493.14 | 01-SEP-00:03 | 0.93 |
October | 0.147128E+11 | 0.93 | 5493.14 | 01-OCT-00:10 | 0.93 |
November | 0.142382E+11 | 0.93 | 5493.14 | 01-NOV-00:10 | 0.93 |
December | 0.147128E+11 | 0.93 | 5493.14 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.173232E+12 | 0.93 | |||
Minimum of Months | 0.132890E+11 | 0.92 | 5493.14 | 0.92 | |
Maximum of Months | 0.147128E+11 | 0.93 | 5493.14 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149367E+10 | 0.93 | 557.67 | 01-JAN-00:05 | 0.93 |
February | 0.134912E+10 | 0.93 | 557.67 | 01-FEB-00:10 | 0.93 |
March | 0.149367E+10 | 0.93 | 557.67 | 01-MAR-00:10 | 0.93 |
April | 0.144549E+10 | 0.93 | 557.67 | 01-APR-00:10 | 0.93 |
May | 0.149367E+10 | 0.93 | 557.67 | 01-MAY-00:10 | 0.93 |
June | 0.144549E+10 | 0.93 | 557.67 | 01-JUN-00:10 | 0.93 |
July | 0.149367E+10 | 0.93 | 557.67 | 01-JUL-00:10 | 0.93 |
August | 0.149367E+10 | 0.92 | 557.67 | 01-AUG-00:03 | 0.93 |
September | 0.144549E+10 | 0.93 | 557.67 | 01-SEP-00:03 | 0.93 |
October | 0.149367E+10 | 0.93 | 557.67 | 01-OCT-00:10 | 0.93 |
November | 0.144549E+10 | 0.93 | 557.67 | 01-NOV-00:10 | 0.93 |
December | 0.149367E+10 | 0.93 | 557.67 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.175868E+11 | 0.93 | |||
Minimum of Months | 0.134912E+10 | 0.92 | 557.67 | 0.93 | |
Maximum of Months | 0.149367E+10 | 0.93 | 557.67 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.106528E+10 | 0.958752E+09 | 4347.19 | 02-JAN-06:01 | 3912.47 | 3912.47 | 45.51 | 9.84 |
February | 0.584750E+09 | 0.526275E+09 | 3681.41 | 14-FEB-06:01 | 3313.27 | 3313.27 | 36.90 | 6.21 |
March | 0.176612E+09 | 0.158951E+09 | 3674.06 | 06-MAR-06:01 | 3306.65 | 3306.65 | 35.73 | 6.19 |
April | 57695806.83 | 51926226.15 | 2790.48 | 11-APR-05:03 | 2511.43 | 2511.43 | 32.02 | 3.88 |
May | 10276851.69 | 9249166.52 | 1197.62 | 18-MAY-05:03 | 1077.86 | 1077.86 | 23.81 | 1.36 |
June | 1262600.28 | 1136340.25 | 167.84 | 14-JUN-05:03 | 151.06 | 151.06 | 19.67 | 0.17 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 19.55 | 0.00 |
August | 74944.67 | 67450.20 | 10.84 | 03-AUG-05:08 | 9.76 | 9.76 | 19.55 | 0.01 |
September | 3621122.82 | 3259010.54 | 234.39 | 27-SEP-05:10 | 210.95 | 210.95 | 19.54 | 0.24 |
October | 73870683.65 | 66483615.28 | 3224.51 | 28-OCT-05:02 | 2902.06 | 2902.06 | 30.90 | 4.87 |
November | 0.362899E+09 | 0.326609E+09 | 3666.53 | 24-NOV-06:01 | 3299.88 | 3299.88 | 34.98 | 6.16 |
December | 0.758297E+09 | 0.682468E+09 | 3667.66 | 26-DEC-06:03 | 3300.90 | 3300.90 | 42.45 | 6.15 |
Annual Sum or Average | 0.309464E+10 | 0.278518E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 | 0.00 | |
Maximum of Months | 0.106528E+10 | 0.958752E+09 | 4347.19 | 3912.47 | 3912.47 | 45.51 | 9.84 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 656.47 | 590.82 | 4.89 | 11-JAN-06:02 | 4.40 | 4.40 | 6.72 | 0.95 |
February | 3181482.25 | 2863334.02 | 297.98 | 27-FEB-15:00 | 268.18 | 268.18 | 8.88 | 14.39 |
March | 3299519.44 | 2969567.50 | 143.52 | 10-MAR-13:30 | 129.17 | 129.17 | 8.59 | 9.75 |
April | 0.136938E+09 | 0.123244E+09 | 6122.16 | 27-APR-11:50 | 5509.95 | 5509.95 | 7.28 | 57.58 |
May | 0.241305E+09 | 0.217175E+09 | 5701.42 | 04-MAY-15:00 | 5131.28 | 5131.28 | 7.07 | 55.91 |
June | 0.623895E+09 | 0.561505E+09 | 7799.82 | 27-JUN-13:30 | 7019.84 | 7019.84 | 7.41 | 63.62 |
July | 0.991493E+09 | 0.892344E+09 | 8324.98 | 19-JUL-13:30 | 7492.48 | 7492.48 | 7.45 | 65.33 |
August | 0.133215E+10 | 0.119894E+10 | 6890.12 | 30-AUG-05:03 | 6201.11 | 6201.11 | 8.74 | 60.46 |
September | 0.460149E+09 | 0.414134E+09 | 8179.64 | 08-SEP-14:40 | 7361.68 | 7361.68 | 7.57 | 64.87 |
October | 39300992.50 | 35370893.25 | 1653.20 | 04-OCT-13:20 | 1487.88 | 1487.88 | 7.99 | 32.75 |
November | 4535929.59 | 4082336.63 | 317.61 | 04-NOV-14:00 | 285.85 | 285.85 | 8.58 | 14.87 |
December | 27930.17 | 25137.16 | 37.54 | 16-DEC-05:01 | 33.78 | 33.78 | 8.45 | 4.37 |
Annual Sum or Average | 0.383628E+10 | 0.345265E+10 | ||||||
Minimum of Months | 656.47 | 590.82 | 4.89 | 4.40 | 4.40 | 6.72 | 0.95 | |
Maximum of Months | 0.133215E+10 | 0.119894E+10 | 8324.98 | 7492.48 | 7492.48 | 8.88 | 65.33 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.124392E+10 | 0.111953E+10 | 12887.35 | 01-JAN-14:35 | 11598.62 | 11598.62 | 8.43 | 90.32 |
February | 0.161791E+10 | 0.145612E+10 | 12887.35 | 01-FEB-06:02 | 11598.62 | 11598.62 | 8.41 | 90.32 |
March | 0.240968E+10 | 0.216871E+10 | 12887.35 | 01-MAR-05:02 | 11598.62 | 11598.62 | 8.45 | 90.32 |
April | 0.532441E+10 | 0.479197E+10 | 12887.35 | 01-APR-05:03 | 11598.62 | 11598.62 | 8.43 | 90.32 |
May | 0.919590E+10 | 0.827631E+10 | 12887.35 | 01-MAY-03:02 | 11598.62 | 11598.62 | 8.59 | 90.32 |
June | 0.142083E+11 | 0.127875E+11 | 12887.35 | 01-JUN-04:04 | 11598.62 | 11598.62 | 8.56 | 90.32 |
July | 0.205558E+11 | 0.185003E+11 | 12887.35 | 01-JUL-03:02 | 11598.62 | 11598.62 | 8.77 | 90.32 |
August | 0.229477E+11 | 0.206529E+11 | 12887.35 | 01-AUG-00:10 | 11598.62 | 11598.62 | 8.20 | 90.32 |
September | 0.122572E+11 | 0.110314E+11 | 12887.35 | 01-SEP-00:52 | 11598.62 | 11598.62 | 8.34 | 90.32 |
October | 0.413504E+10 | 0.372153E+10 | 12887.35 | 01-OCT-12:52 | 11598.62 | 11598.62 | 8.42 | 90.32 |
November | 0.257651E+10 | 0.231886E+10 | 12887.35 | 01-NOV-04:02 | 11598.62 | 11598.62 | 8.59 | 90.32 |
December | 0.156794E+10 | 0.141115E+10 | 12887.35 | 01-DEC-11:40 | 11598.62 | 11598.62 | 8.43 | 90.32 |
Annual Sum or Average | 0.980403E+11 | 0.882362E+11 | ||||||
Minimum of Months | 0.124392E+10 | 0.111953E+10 | 12887.35 | 11598.62 | 11598.62 | 8.20 | 90.32 | |
Maximum of Months | 0.229477E+11 | 0.206529E+11 | 12887.35 | 11598.62 | 11598.62 | 8.77 | 90.32 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.908449E+10 | 0.817604E+10 | 3391.76 | 01-JAN-00:05 | 3052.58 | 3052.58 | 21.57 | 14.17 |
February | 0.820535E+10 | 0.738481E+10 | 3391.76 | 01-FEB-00:10 | 3052.58 | 3052.58 | 24.25 | 14.17 |
March | 0.908449E+10 | 0.817604E+10 | 3391.76 | 01-MAR-00:10 | 3052.58 | 3052.58 | 27.17 | 14.17 |
April | 0.879144E+10 | 0.791230E+10 | 3391.76 | 01-APR-00:10 | 3052.58 | 3052.58 | 30.20 | 14.17 |
May | 0.908449E+10 | 0.817604E+10 | 3391.76 | 01-MAY-00:10 | 3052.58 | 3052.58 | 22.44 | 14.17 |
June | 0.879144E+10 | 0.791230E+10 | 3391.76 | 01-JUN-00:10 | 3052.58 | 3052.58 | 24.88 | 14.17 |
July | 0.908449E+10 | 0.817604E+10 | 3391.76 | 01-JUL-00:10 | 3052.58 | 3052.58 | 28.96 | 14.17 |
August | 0.908449E+10 | 0.817604E+10 | 3391.76 | 01-AUG-00:03 | 3052.58 | 3052.58 | 35.19 | 14.17 |
September | 0.879144E+10 | 0.791230E+10 | 3391.76 | 01-SEP-00:03 | 3052.58 | 3052.58 | 22.55 | 14.17 |
October | 0.908449E+10 | 0.817604E+10 | 3391.76 | 01-OCT-00:10 | 3052.58 | 3052.58 | 24.76 | 14.17 |
November | 0.879144E+10 | 0.791230E+10 | 3391.76 | 01-NOV-00:10 | 3052.58 | 3052.58 | 27.39 | 14.17 |
December | 0.908449E+10 | 0.817604E+10 | 3391.76 | 01-DEC-00:10 | 3052.58 | 3052.58 | 29.85 | 14.17 |
Annual Sum or Average | 0.106963E+12 | 0.962663E+11 | ||||||
Minimum of Months | 0.820535E+10 | 0.738481E+10 | 3391.76 | 3052.58 | 3052.58 | 21.57 | 14.17 | |
Maximum of Months | 0.908449E+10 | 0.817604E+10 | 3391.76 | 3052.58 | 3052.58 | 35.19 | 14.17 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 55.30 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:02 | 1.79 | 1.79 | 56.03 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 56.26 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 55.62 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 55.95 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 55.58 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 55.69 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 56.71 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.89 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.15 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:02 | 1.79 | 1.79 | 55.80 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:02 | 1.79 | 1.79 | 55.78 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.30 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 56.89 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.154594E+10 | 0.139135E+10 | 16019.07 | 05-JAN-06:40 | 14417.16 | 14417.16 | 21.20 | 53.36 |
February | 0.200451E+10 | 0.180406E+10 | 16046.31 | 27-FEB-15:10 | 14441.68 | 14441.68 | 23.56 | 53.36 |
March | 0.297625E+10 | 0.267862E+10 | 16038.23 | 18-MAR-16:00 | 14434.41 | 14434.41 | 22.86 | 53.36 |
April | 0.717086E+10 | 0.645377E+10 | 32151.83 | 27-APR-15:50 | 28936.65 | 28936.65 | 25.96 | 106.72 |
May | 0.121416E+11 | 0.109274E+11 | 32149.97 | 05-MAY-15:50 | 28934.98 | 28934.98 | 25.89 | 106.72 |
June | 0.190266E+11 | 0.171239E+11 | 32150.89 | 28-JUN-14:30 | 28935.80 | 28935.80 | 25.92 | 106.72 |
July | 0.285434E+11 | 0.256891E+11 | 32201.14 | 31-JUL-16:00 | 28981.03 | 28981.03 | 27.79 | 106.72 |
August | 0.343897E+11 | 0.309508E+11 | 32225.04 | 29-AUG-14:30 | 29002.54 | 29002.54 | 28.67 | 106.72 |
September | 0.165916E+11 | 0.149325E+11 | 32149.64 | 13-SEP-13:50 | 28934.67 | 28934.67 | 25.88 | 106.72 |
October | 0.514031E+10 | 0.462628E+10 | 16067.44 | 04-OCT-15:00 | 14460.69 | 14460.69 | 25.33 | 53.36 |
November | 0.320260E+10 | 0.288234E+10 | 16043.05 | 04-NOV-14:00 | 14438.75 | 14438.75 | 23.28 | 53.36 |
December | 0.194865E+10 | 0.175379E+10 | 16019.12 | 02-DEC-07:00 | 14417.20 | 14417.20 | 21.20 | 53.36 |
Annual Sum or Average | 0.134682E+12 | 0.121214E+12 | ||||||
Minimum of Months | 0.154594E+10 | 0.139135E+10 | 16019.07 | 14417.16 | 14417.16 | 21.20 | 53.36 | |
Maximum of Months | 0.343897E+11 | 0.309508E+11 | 32225.04 | 29002.54 | 29002.54 | 28.67 | 106.72 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 29.98 | 80.09 | 96545.22 | 1604107.31 | 03-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 24.17 | 24.17 | 58612.49 | 1195098.67 | 16-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 19.99 | 19.99 | 16209.79 | 1191927.50 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.33 | 20.33 | 5498.16 | 780046.82 | 11-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.81 | 22.81 | 965.31 | 319814.17 | 18-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 19.65 | 19.65 | 124.73 | 43355.03 | 14-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.55 | 19.55 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 19.55 | 19.55 | 7.16 | 2771.72 | 03-AUG-05:08 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.42 | 19.42 | 359.61 | 61452.56 | 27-SEP-05:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 19.05 | 19.05 | 6882.28 | 992694.08 | 28-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.81 | 21.81 | 34570.89 | 1178915.54 | 24-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25.41 | 25.41 | 69210.94 | 1220091.76 | 27-DEC-05:01 |
Annual Sum or Average | 0.00 | 23951.21 | ||||||
Minimum of Months | 0.00 | 0.00 | 19.05 | 19.05 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 29.98 | 80.09 | 96545.22 | 1604107.31 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 824.90 | 22910.62 | 09-JAN-04:50 | 8.43 | 8.40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 6692.01 | 931281.17 | 27-FEB-15:00 | 10.17 | 8.92 | 3.13 | 19370.47 | 25-FEB-05:02 |
March | 8441.89 | 646735.60 | 18-MAR-16:00 | 9.33 | 8.46 | 18.02 | 62725.28 | 22-MAR-10:20 |
April | 60034.12 | 1323634.84 | 27-APR-14:50 | 10.20 | 6.70 | 8.16 | 75057.86 | 01-APR-23:02 |
May | 118228.79 | 1287534.21 | 04-MAY-13:50 | 10.57 | 7.16 | 0.07 | 1652.00 | 14-MAY-07:32 |
June | 222801.68 | 1324877.68 | 22-JUN-14:50 | 10.72 | 7.22 | 63.78 | 169577.23 | 11-JUN-09:05 |
July | 353217.47 | 1635018.64 | 31-JUL-16:00 | 11.02 | 6.70 | 16.94 | 48882.18 | 27-JUL-23:22 |
August | 427036.92 | 1707498.07 | 29-AUG-14:30 | 11.21 | 6.70 | 21.28 | 65285.79 | 23-AUG-01:02 |
September | 182037.08 | 1342315.93 | 14-SEP-13:00 | 10.83 | 7.29 | 117.76 | 245342.61 | 24-SEP-14:02 |
October | 32565.58 | 1080903.71 | 04-OCT-11:40 | 10.56 | 9.11 | 1.57 | 35015.20 | 10-OCT-01:12 |
November | 7345.38 | 813324.35 | 04-NOV-14:00 | 9.69 | 8.60 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1059.85 | 70670.01 | 28-DEC-06:03 | 8.56 | 8.46 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 119278.25 | 20.75 | ||||||
Minimum of Months | 824.90 | 22910.62 | 8.43 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 427036.92 | 1707498.07 | 11.21 | 9.11 | 117.76 | 245342.61 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.01 | 145.47 | 11-JAN-06:02 | 6.74 | 8.40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3550.16 | 601816.67 | 27-FEB-15:00 | 16.70 | 8.88 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4396.85 | 376039.45 | 18-MAR-16:00 | 17.59 | 8.47 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43947.82 | 1388816.21 | 27-APR-11:50 | 12.46 | 8.31 | 0.00 | 0.00 | 01-APR-00:10 |
May | 86929.27 | 1404463.34 | 04-MAY-13:50 | 12.89 | 8.43 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 171015.51 | 1450543.28 | 27-JUN-13:30 | 12.14 | 8.45 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 283743.68 | 1696192.77 | 15-JUL-17:42 | 15.52 | 7.79 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 361305.22 | 1806055.93 | 30-AUG-05:03 | 13.84 | 9.06 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 144108.44 | 1449116.89 | 08-SEP-14:40 | 12.03 | 8.56 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 22105.53 | 1075062.29 | 04-OCT-15:00 | 15.49 | 8.69 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3649.97 | 521962.61 | 04-NOV-14:00 | 15.09 | 8.57 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 18.65 | 74413.38 | 16-DEC-05:01 | 10.77 | 8.41 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 94505.57 | 0.00 | ||||||
Minimum of Months | 0.01 | 145.47 | 6.74 | 7.79 | 0.00 | 0.00 | ||
Maximum of Months | 361305.22 | 1806055.93 | 17.59 | 9.06 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 163992.05 | 178798.48 | 11-JAN-15:00 | 21.96 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 310304.52 | 566716.53 | 27-FEB-15:10 | 29.76 | 22.89 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 459560.14 | 802835.26 | 18-MAR-16:00 | 34.45 | 24.82 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 648279.75 | 1409510.83 | 27-APR-16:00 | 46.31 | 33.10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 214889.72 | 640785.66 | 05-MAY-16:00 | 31.23 | 26.89 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 412351.95 | 944393.39 | 28-JUN-17:00 | 37.24 | 29.92 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 671998.27 | 1397005.09 | 24-JUL-15:00 | 46.07 | 35.37 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 934156.86 | 1664786.14 | 10-AUG-17:00 | 51.22 | 37.83 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 230120.03 | 642008.68 | 14-SEP-17:00 | 31.26 | 26.90 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 329086.28 | 671394.94 | 04-OCT-15:00 | 31.84 | 24.78 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 456371.89 | 833693.02 | 04-NOV-15:00 | 35.06 | 25.35 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 586559.53 | 603630.23 | 14-DEC-12:00 | 30.49 | 18.51 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 452793.87 | 0.00 | ||||||
Minimum of Months | 163992.05 | 178798.48 | 21.96 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 934156.86 | 1664786.14 | 51.22 | 37.83 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.62 | 56.62 | 15535.55 | 52072.20 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.63 | 56.63 | 15718.86 | 52133.96 | 10-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.47 | 56.47 | 16437.76 | 51957.88 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.27 | 56.27 | 15106.62 | 50821.54 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.81 | 56.81 | 15038.35 | 49260.82 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.16 | 56.16 | 14838.96 | 47362.86 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.26 | 56.26 | 13427.64 | 45746.70 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.64 | 57.64 | 14450.77 | 45085.04 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.42 | 57.42 | 13809.24 | 46044.22 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.16 | 57.16 | 14181.71 | 47795.08 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.34 | 56.34 | 14876.11 | 49645.82 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.34 | 56.34 | 14861.26 | 51152.26 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 14852.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.16 | 56.16 | 13427.64 | 45085.04 | ||
Maximum of Months | 0.00 | 0.00 | 57.64 | 57.64 | 16437.76 | 52133.96 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 21.81 | 21662.63 | 05-JAN-06:40 | 21.20 | 20.28 | 1142.94 | 116042.67 | 07-JAN-06:30 |
February | 3548.45 | 548674.42 | 27-FEB-15:10 | 23.56 | 21.10 | 1166.78 | 111062.13 | 09-FEB-16:30 |
March | 4276.02 | 392496.20 | 18-MAR-16:00 | 22.86 | 21.10 | 1163.50 | 113802.45 | 24-MAR-05:30 |
April | 48442.44 | 2167337.56 | 27-APR-15:50 | 25.96 | 21.80 | 1302.63 | 91105.43 | 17-APR-09:30 |
May | 87939.13 | 2136614.21 | 05-MAY-15:50 | 25.89 | 21.89 | 700.68 | 75122.15 | 17-MAY-19:50 |
June | 172836.96 | 2151806.27 | 28-JUN-14:30 | 25.92 | 21.27 | 504.19 | 71525.83 | 14-JUN-14:30 |
July | 302593.38 | 2982305.68 | 31-JUL-16:00 | 27.79 | 23.56 | 766.81 | 56096.17 | 01-JUL-10:40 |
August | 431856.14 | 3376428.39 | 29-AUG-14:30 | 28.67 | 24.25 | 588.32 | 54852.12 | 15-AUG-06:20 |
September | 146221.74 | 2131050.43 | 13-SEP-13:50 | 25.88 | 21.89 | 405.53 | 66358.23 | 27-SEP-05:30 |
October | 20409.41 | 944028.31 | 04-OCT-15:00 | 25.33 | 21.10 | 828.89 | 93431.77 | 13-OCT-05:30 |
November | 3533.65 | 485706.24 | 04-NOV-14:00 | 23.28 | 21.10 | 2020.94 | 106277.56 | 14-NOV-06:40 |
December | 29.14 | 22626.19 | 02-DEC-07:00 | 21.20 | 20.37 | 1265.87 | 115264.18 | 11-DEC-06:50 |
Annual Sum or Average | 102715.82 | 985.85 | ||||||
Minimum of Months | 21.81 | 21662.63 | 21.20 | 20.28 | 405.53 | 54852.12 | ||
Maximum of Months | 431856.14 | 3376428.39 | 28.67 | 24.25 | 2020.94 | 116042.67 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.518623E+10 | 0.00 | 1564.80 | 0.443129E+10 | 0.00 | 0.00 |
February | 0.242419E+10 | 0.00 | 0.792885E+09 | 0.495542E+10 | 0.00 | 0.00 |
March | 0.181239E+09 | 0.00 | 0.104864E+10 | 0.745228E+10 | 0.00 | 0.00 |
April | 7442656.14 | 0.00 | 0.100492E+11 | 0.899689E+10 | 0.00 | 0.00 |
May | 44104.05 | 0.00 | 0.165309E+11 | 0.826864E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.323628E+11 | 0.988550E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.589222E+11 | 0.118151E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.818136E+11 | 0.138787E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.256484E+11 | 0.839354E+10 | 0.00 | 0.00 |
October | 10304231.04 | 0.00 | 0.454281E+10 | 0.726086E+10 | 0.00 | 0.00 |
November | 0.429580E+09 | 0.00 | 0.656917E+09 | 0.601403E+10 | 0.00 | 0.00 |
December | 0.161698E+10 | 0.00 | 2025.31 | 0.584438E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.985601E+10 | 0.00 | 0.232368E+12 | 0.971967E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 1564.80 | 0.443129E+10 | 0.00 | 0.00 |
Maximum of Months | 0.518623E+10 | 0.00 | 0.818136E+11 | 0.138787E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.214670E+12 | 0.00 | 66618.44 | 0.335988E+11 | 0.00 | 0.00 |
February | 0.115489E+12 | 0.00 | 0.523285E+10 | 0.337020E+11 | 0.00 | 0.00 |
March | 0.320338E+11 | 0.00 | 0.750277E+10 | 0.459540E+11 | 0.00 | 0.00 |
April | 0.994981E+10 | 0.00 | 0.744492E+11 | 0.504860E+11 | 0.00 | 0.00 |
May | 0.143170E+10 | 0.00 | 0.143109E+12 | 0.631700E+11 | 0.00 | 0.00 |
June | 0.128948E+09 | 0.00 | 0.265622E+12 | 0.714262E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.469568E+12 | 0.810194E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.629965E+12 | 0.925787E+11 | 0.00 | 0.00 |
September | 0.392759E+09 | 0.00 | 0.228374E+12 | 0.672082E+11 | 0.00 | 0.00 |
October | 0.129269E+11 | 0.00 | 0.359190E+11 | 0.489250E+11 | 0.00 | 0.00 |
November | 0.709769E+11 | 0.00 | 0.577554E+10 | 0.362392E+11 | 0.00 | 0.00 |
December | 0.151942E+12 | 0.00 | 84346.93 | 0.345353E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.609942E+12 | 0.00 | 0.186552E+13 | 0.658843E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 66618.44 | 0.335988E+11 | 0.00 | 0.00 |
Maximum of Months | 0.214670E+12 | 0.00 | 0.629965E+12 | 0.925787E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.409920E+11 | 0.00 | 66560.84 | 0.407350E+10 | 0.00 | 0.00 |
February | 0.251318E+11 | 0.00 | 0.427343E+09 | 0.349418E+10 | 0.00 | 0.00 |
March | 0.115697E+11 | 0.00 | 0.675303E+09 | 0.382405E+10 | 0.00 | 0.00 |
April | 0.440124E+10 | 0.00 | 0.770370E+10 | 0.426441E+10 | 0.00 | 0.00 |
May | 0.119181E+10 | 0.00 | 0.147982E+11 | 0.543925E+10 | 0.00 | 0.00 |
June | 0.198286E+09 | 0.00 | 0.281241E+11 | 0.653854E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.504478E+11 | 0.776308E+10 | 0.00 | 0.00 |
August | 19971289.05 | 0.00 | 0.671747E+11 | 0.876425E+10 | 0.00 | 0.00 |
September | 0.548398E+09 | 0.00 | 0.226088E+11 | 0.564253E+10 | 0.00 | 0.00 |
October | 0.563379E+10 | 0.00 | 0.313174E+10 | 0.383797E+10 | 0.00 | 0.00 |
November | 0.189426E+11 | 0.00 | 0.562307E+09 | 0.324817E+10 | 0.00 | 0.00 |
December | 0.334167E+11 | 0.00 | 79833.72 | 0.358827E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.142046E+12 | 0.00 | 0.195654E+12 | 0.604782E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 66560.84 | 0.324817E+10 | 0.00 | 0.00 |
Maximum of Months | 0.409920E+11 | 0.00 | 0.671747E+11 | 0.876425E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 1261208.54 | 0.148208E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.447807E+09 | 0.132733E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.116881E+09 | 0.160113E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.403601E+10 | 0.146871E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.764494E+10 | 0.157140E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.159405E+11 | 0.157071E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.298102E+11 | 0.154074E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.419790E+11 | 0.167067E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.123264E+11 | 0.155811E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.160932E+10 | 0.155847E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.248574E+09 | 0.150022E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 5242049.13 | 0.147942E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114166E+12 | 0.183290E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 1261208.54 | 0.132733E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.419790E+11 | 0.167067E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.402413E+12 | 0.177486E+12 | 0.00 | 0.38 |
February | 0.00 | 0.00 | 0.634783E+12 | 0.209440E+12 | 0.00 | 0.39 |
March | 0.00 | 0.00 | 0.100255E+13 | 0.283112E+12 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.126161E+13 | 0.325567E+12 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.415408E+12 | 0.179534E+12 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.698401E+12 | 0.231046E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.103762E+13 | 0.305436E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.135228E+13 | 0.375266E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.407480E+12 | 0.174672E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.711223E+12 | 0.231908E+12 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.971294E+12 | 0.272792E+12 | 0.00 | 0.11 |
December | 0.00 | 0.00 | 0.129405E+13 | 0.330194E+12 | 0.00 | 0.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.101891E+14 | 0.309645E+13 | 0.00 | 1.78 |
Minimum of Months | 0.00 | 0.00 | 0.402413E+12 | 0.174672E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.135228E+13 | 0.375266E+12 | 0.00 | 0.39 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.501587E+10 | 0.257436E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108302E+11 | 0.349955E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.188364E+11 | 0.506403E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245698E+11 | 0.601168E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.707165E+10 | 0.295742E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132032E+11 | 0.407842E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203653E+11 | 0.560915E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.268631E+11 | 0.705400E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.705732E+10 | 0.289702E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.128669E+11 | 0.398511E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.180216E+11 | 0.481806E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.244707E+11 | 0.599129E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.189172E+12 | 0.545401E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.501587E+10 | 0.257436E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.268631E+11 | 0.705400E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.213943E+11 | 0.193798E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.830928E+11 | 0.297293E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.163004E+12 | 0.455246E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.223412E+12 | 0.556349E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.593596E+11 | 0.267462E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.120106E+12 | 0.379210E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.191275E+12 | 0.530438E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.253398E+12 | 0.668604E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.603838E+11 | 0.263971E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.108456E+12 | 0.355490E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.151581E+12 | 0.425819E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.207894E+12 | 0.530452E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.164336E+13 | 0.492413E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.213943E+11 | 0.193798E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.253398E+12 | 0.668604E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.829691E+09 | 0.168110E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.640023E+10 | 0.263162E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.147679E+11 | 0.431110E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.213917E+11 | 0.543655E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.528859E+10 | 0.257617E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.117341E+11 | 0.376897E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.189871E+11 | 0.531114E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.251689E+11 | 0.669113E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.542299E+10 | 0.254831E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.948393E+10 | 0.333457E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.133105E+11 | 0.396296E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.185316E+11 | 0.495291E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151317E+12 | 0.472065E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.829691E+09 | 0.168110E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.251689E+11 | 0.669113E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.443129E+10 | 1564.80 | 0.518623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.495542E+10 | 0.792885E+09 | 0.242419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.745228E+10 | 0.104864E+10 | 0.181239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.899689E+10 | 0.100492E+11 | 7442656.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.826864E+10 | 0.165309E+11 | 44104.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.988550E+10 | 0.323628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118151E+11 | 0.589222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138787E+11 | 0.818136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.839354E+10 | 0.256484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.726086E+10 | 0.454281E+10 | 10304231.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.601403E+10 | 0.656917E+09 | 0.429580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.584438E+10 | 2025.31 | 0.161698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.971967E+11 | 0.232368E+12 | 0.985601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.443129E+10 | 1564.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138787E+11 | 0.818136E+11 | 0.518623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.335988E+11 | 66618.44 | 0.214670E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.337020E+11 | 0.523285E+10 | 0.115489E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.459540E+11 | 0.750277E+10 | 0.320338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.504860E+11 | 0.744492E+11 | 0.994981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.631700E+11 | 0.143109E+12 | 0.143170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.714262E+11 | 0.265622E+12 | 0.128948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.810194E+11 | 0.469568E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.925787E+11 | 0.629965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.672082E+11 | 0.228374E+12 | 0.392759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.489250E+11 | 0.359190E+11 | 0.129269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.362392E+11 | 0.577554E+10 | 0.709769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345353E+11 | 84346.93 | 0.151942E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.658843E+12 | 0.186552E+13 | 0.609942E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.335988E+11 | 66618.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.925787E+11 | 0.629965E+12 | 0.214670E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.407350E+10 | 66560.84 | 0.409920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.349418E+10 | 0.427343E+09 | 0.251318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.382405E+10 | 0.675303E+09 | 0.115697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.426441E+10 | 0.770370E+10 | 0.440124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.543925E+10 | 0.147982E+11 | 0.119181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.653854E+10 | 0.281241E+11 | 0.198286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.776308E+10 | 0.504478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.876425E+10 | 0.671747E+11 | 19971289.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.564253E+10 | 0.226088E+11 | 0.548398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.383797E+10 | 0.313174E+10 | 0.563379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324817E+10 | 0.562307E+09 | 0.189426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358827E+10 | 79833.72 | 0.334167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.604782E+11 | 0.195654E+12 | 0.142046E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.324817E+10 | 66560.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.876425E+10 | 0.671747E+11 | 0.409920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148208E+11 | 1261208.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132733E+11 | 0.447807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160113E+11 | 0.116881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146871E+11 | 0.403601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157140E+11 | 0.764494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157071E+11 | 0.159405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154074E+11 | 0.298102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167067E+11 | 0.419790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155811E+11 | 0.123264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155847E+11 | 0.160932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150022E+11 | 0.248574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147942E+11 | 5242049.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183290E+12 | 0.114166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132733E+11 | 1261208.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167067E+11 | 0.419790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.957351E+11 | 0.321684E+12 | 0.00 | 0.00 | 0.00 | 0.101716E+10 | 0.00 | 0.00 |
February | 0.864704E+11 | 0.512873E+12 | 0.00 | 0.00 | 0.00 | 0.105490E+10 | 0.00 | 0.00 |
March | 0.957351E+11 | 0.816116E+12 | 0.00 | 0.00 | 0.00 | 0.938615E+09 | 0.00 | 0.00 |
April | 0.926468E+11 | 0.102912E+13 | 0.00 | 0.00 | 0.00 | 0.421301E+09 | 0.00 | 0.00 |
May | 0.957351E+11 | 0.331671E+12 | 0.00 | 0.00 | 0.00 | 61740461.37 | 0.00 | 0.00 |
June | 0.926468E+11 | 0.560002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.957351E+11 | 0.827921E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.957351E+11 | 0.107275E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.926468E+11 | 0.325455E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.957351E+11 | 0.575085E+12 | 0.00 | 0.00 | 0.00 | 35149990.41 | 0.00 | 0.00 |
November | 0.926468E+11 | 0.791457E+12 | 0.00 | 0.00 | 0.00 | 0.306454E+09 | 0.00 | 0.00 |
December | 0.957351E+11 | 0.106052E+13 | 0.00 | 0.00 | 0.00 | 0.928152E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112720E+13 | 0.822465E+13 | 0.00 | 0.00 | 0.00 | 0.476348E+10 | 0.00 | 0.00 |
Minimum of Months | 0.864704E+11 | 0.321684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.957351E+11 | 0.107275E+13 | 0.00 | 0.00 | 0.00 | 0.105490E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153753E+10 | 0.397904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138874E+10 | 0.871943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153753E+10 | 0.153099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148793E+10 | 0.200461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153753E+10 | 0.565176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148793E+10 | 0.106127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153753E+10 | 0.162937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153753E+10 | 0.213466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148793E+10 | 0.564823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153753E+10 | 0.104193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148793E+10 | 0.146914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153753E+10 | 0.200170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181032E+11 | 0.152735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138874E+10 | 0.397904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153753E+10 | 0.213466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147128E+11 | 0.167273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132890E+11 | 0.666526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147128E+11 | 0.132193E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142382E+11 | 0.182016E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147128E+11 | 0.473262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142382E+11 | 0.964232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147128E+11 | 0.152944E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147128E+11 | 0.201250E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142382E+11 | 0.482249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147128E+11 | 0.876194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142382E+11 | 0.123237E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147128E+11 | 0.169561E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173232E+12 | 0.132417E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132890E+11 | 0.167273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147128E+11 | 0.201250E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149367E+10 | 0.642259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134912E+10 | 0.511774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149367E+10 | 0.119505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144549E+10 | 0.174006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149367E+10 | 0.420608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144549E+10 | 0.941064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149367E+10 | 0.151696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149367E+10 | 0.199714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144549E+10 | 0.432016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149367E+10 | 0.764303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144549E+10 | 0.107930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149367E+10 | 0.150723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175868E+11 | 0.121697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134912E+10 | 0.642259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149367E+10 | 0.199714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.443129E+10 | 0.518623E+10 | 1564.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.495542E+10 | 0.242419E+10 | 0.792885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.745228E+10 | 0.181239E+09 | 0.104864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.899689E+10 | 7442656.14 | 0.100492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.826864E+10 | 44104.05 | 0.165309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.988550E+10 | 0.00 | 0.323628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118151E+11 | 0.00 | 0.589222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138787E+11 | 0.00 | 0.818136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.839354E+10 | 0.00 | 0.256484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.726086E+10 | 10304231.04 | 0.454281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.601403E+10 | 0.429580E+09 | 0.656917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.584438E+10 | 0.161698E+10 | 2025.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.971967E+11 | 0.985601E+10 | 0.232368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.443129E+10 | 0.00 | 1564.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138787E+11 | 0.518623E+10 | 0.818136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.335988E+11 | 0.214670E+12 | 66618.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.337020E+11 | 0.115489E+12 | 0.523285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.459540E+11 | 0.320338E+11 | 0.750277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.504860E+11 | 0.994981E+10 | 0.744492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.631700E+11 | 0.143170E+10 | 0.143109E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.714262E+11 | 0.128948E+09 | 0.265622E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.810194E+11 | 0.00 | 0.469568E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.925787E+11 | 0.00 | 0.629965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.672082E+11 | 0.392759E+09 | 0.228374E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.489250E+11 | 0.129269E+11 | 0.359190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.362392E+11 | 0.709769E+11 | 0.577554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345353E+11 | 0.151942E+12 | 84346.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.658843E+12 | 0.609942E+12 | 0.186552E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.335988E+11 | 0.00 | 66618.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.925787E+11 | 0.214670E+12 | 0.629965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.407350E+10 | 0.409920E+11 | 66560.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.349418E+10 | 0.251318E+11 | 0.427343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.382405E+10 | 0.115697E+11 | 0.675303E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.426441E+10 | 0.440124E+10 | 0.770370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.543925E+10 | 0.119181E+10 | 0.147982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.653854E+10 | 0.198286E+09 | 0.281241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.776308E+10 | 0.00 | 0.504478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.876425E+10 | 19971289.05 | 0.671747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.564253E+10 | 0.548398E+09 | 0.226088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.383797E+10 | 0.563379E+10 | 0.313174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324817E+10 | 0.189426E+11 | 0.562307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358827E+10 | 0.334167E+11 | 79833.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.604782E+11 | 0.142046E+12 | 0.195654E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.324817E+10 | 0.00 | 66560.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.876425E+10 | 0.409920E+11 | 0.671747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148208E+11 | 0.00 | 1261208.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132733E+11 | 0.00 | 0.447807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160113E+11 | 0.00 | 0.116881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146871E+11 | 0.00 | 0.403601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157140E+11 | 0.00 | 0.764494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157071E+11 | 0.00 | 0.159405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154074E+11 | 0.00 | 0.298102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167067E+11 | 0.00 | 0.419790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155811E+11 | 0.00 | 0.123264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155847E+11 | 0.00 | 0.160932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150022E+11 | 0.00 | 0.248574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147942E+11 | 0.00 | 5242049.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183290E+12 | 0.00 | 0.114166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132733E+11 | 0.00 | 1261208.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167067E+11 | 0.00 | 0.419790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.957351E+11 | 0.00 | 0.402413E+12 | 0.00 | 0.807293E+11 | 0.00 | 0.00 | 0.00 | 0.102174E+10 | 0.00 | 0.00 | 0.00 |
February | 0.864704E+11 | 0.00 | 0.634783E+12 | 0.00 | 0.121910E+12 | 0.00 | 0.00 | 0.00 | 0.105965E+10 | 0.00 | 0.00 | 0.00 |
March | 0.957351E+11 | 0.00 | 0.100255E+13 | 0.00 | 0.186434E+12 | 0.00 | 0.00 | 0.00 | 0.942840E+09 | 0.00 | 0.00 | 0.00 |
April | 0.926468E+11 | 0.00 | 0.126161E+13 | 0.00 | 0.232497E+12 | 0.00 | 0.00 | 0.00 | 0.423197E+09 | 0.00 | 0.00 | 0.00 |
May | 0.957351E+11 | 0.00 | 0.415408E+12 | 0.00 | 0.837365E+11 | 0.00 | 0.00 | 0.00 | 62018380.21 | 0.00 | 0.00 | 0.00 |
June | 0.926468E+11 | 0.00 | 0.698401E+12 | 0.00 | 0.138399E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.957351E+11 | 0.00 | 0.103762E+13 | 0.00 | 0.209701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.957351E+11 | 0.00 | 0.135228E+13 | 0.00 | 0.279531E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.926468E+11 | 0.00 | 0.407480E+12 | 0.00 | 0.820251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.957351E+11 | 0.00 | 0.711223E+12 | 0.00 | 0.136138E+12 | 0.00 | 0.00 | 0.00 | 35308214.77 | 0.00 | 0.00 | 0.00 |
November | 0.926468E+11 | 0.00 | 0.971294E+12 | 0.00 | 0.179838E+12 | 0.00 | 0.00 | 0.00 | 0.307834E+09 | 0.00 | 0.00 | 0.00 |
December | 0.957351E+11 | 0.00 | 0.129405E+13 | 0.00 | 0.233527E+12 | 0.00 | 0.00 | 0.00 | 0.932330E+09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112720E+13 | 0.00 | 0.101891E+14 | 0.00 | 0.196446E+13 | 0.00 | 0.00 | 0.00 | 0.478492E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.864704E+11 | 0.00 | 0.402413E+12 | 0.00 | 0.807293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.957351E+11 | 0.00 | 0.135228E+13 | 0.00 | 0.279531E+12 | 0.00 | 0.00 | 0.00 | 0.105965E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153753E+10 | 0.00 | 0.501587E+10 | 0.00 | 0.103683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138874E+10 | 0.00 | 0.108302E+11 | 0.00 | 0.211082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153753E+10 | 0.00 | 0.188364E+11 | 0.00 | 0.352650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148793E+10 | 0.00 | 0.245698E+11 | 0.00 | 0.452374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153753E+10 | 0.00 | 0.707165E+10 | 0.00 | 0.141989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148793E+10 | 0.00 | 0.132032E+11 | 0.00 | 0.259048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153753E+10 | 0.00 | 0.203653E+11 | 0.00 | 0.407162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153753E+10 | 0.00 | 0.268631E+11 | 0.00 | 0.551647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148793E+10 | 0.00 | 0.705732E+10 | 0.00 | 0.140908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153753E+10 | 0.00 | 0.128669E+11 | 0.00 | 0.244758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148793E+10 | 0.00 | 0.180216E+11 | 0.00 | 0.333013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153753E+10 | 0.00 | 0.244707E+11 | 0.00 | 0.445376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181032E+11 | 0.00 | 0.189172E+12 | 0.00 | 0.364369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138874E+10 | 0.00 | 0.501587E+10 | 0.00 | 0.103683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153753E+10 | 0.00 | 0.268631E+11 | 0.00 | 0.551647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147128E+11 | 0.00 | 0.213943E+11 | 0.00 | 0.466698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132890E+11 | 0.00 | 0.830928E+11 | 0.00 | 0.164403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147128E+11 | 0.00 | 0.163004E+12 | 0.00 | 0.308118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142382E+11 | 0.00 | 0.223412E+12 | 0.00 | 0.413967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147128E+11 | 0.00 | 0.593596E+11 | 0.00 | 0.120334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142382E+11 | 0.00 | 0.120106E+12 | 0.00 | 0.236828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147128E+11 | 0.00 | 0.191275E+12 | 0.00 | 0.383310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147128E+11 | 0.00 | 0.253398E+12 | 0.00 | 0.521476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142382E+11 | 0.00 | 0.603838E+11 | 0.00 | 0.121589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147128E+11 | 0.00 | 0.108456E+12 | 0.00 | 0.208362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142382E+11 | 0.00 | 0.151581E+12 | 0.00 | 0.283437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147128E+11 | 0.00 | 0.207894E+12 | 0.00 | 0.383324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173232E+12 | 0.00 | 0.164336E+13 | 0.00 | 0.319182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132890E+11 | 0.00 | 0.213943E+11 | 0.00 | 0.466698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147128E+11 | 0.00 | 0.253398E+12 | 0.00 | 0.521476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149367E+10 | 0.00 | 0.829691E+09 | 0.00 | 0.187432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134912E+10 | 0.00 | 0.640023E+10 | 0.00 | 0.128250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149367E+10 | 0.00 | 0.147679E+11 | 0.00 | 0.281743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144549E+10 | 0.00 | 0.213917E+11 | 0.00 | 0.399106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149367E+10 | 0.00 | 0.528859E+10 | 0.00 | 0.108250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144549E+10 | 0.00 | 0.117341E+11 | 0.00 | 0.232348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149367E+10 | 0.00 | 0.189871E+11 | 0.00 | 0.381747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149367E+10 | 0.00 | 0.251689E+11 | 0.00 | 0.519746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144549E+10 | 0.00 | 0.542299E+10 | 0.00 | 0.110282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149367E+10 | 0.00 | 0.948393E+10 | 0.00 | 0.184090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144549E+10 | 0.00 | 0.133105E+11 | 0.00 | 0.251747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149367E+10 | 0.00 | 0.185316E+11 | 0.00 | 0.345924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175868E+11 | 0.00 | 0.151317E+12 | 0.00 | 0.296198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134912E+10 | 0.00 | 0.829691E+09 | 0.00 | 0.187432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149367E+10 | 0.00 | 0.251689E+11 | 0.00 | 0.519746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.528948E+09 | 0.00 | 0.00 | 0.103897E+09 | 0.00 | 0.00 | 0.685918E+11 | 0.00 | 0.58 |
February | 0.400287E+09 | 0.00 | 0.00 | 97033676.32 | 0.00 | 0.00 | 0.641734E+11 | 0.00 | 0.70 |
March | 0.339427E+09 | 0.00 | 0.00 | 0.120942E+09 | 0.00 | 0.00 | 0.805269E+11 | 0.00 | 0.89 |
April | 0.300056E+09 | 22500510.31 | 0.00 | 0.115934E+09 | 0.00 | 0.00 | 0.722173E+11 | 0.00 | 0.99 |
May | 0.260724E+09 | 14090422.54 | 0.00 | 0.120982E+09 | 0.00 | 0.00 | 0.724222E+11 | 0.00 | 1.23 |
June | 0.168766E+09 | 16547906.29 | 0.00 | 0.124506E+09 | 1345755.55 | 0.00 | 0.663170E+11 | 0.00 | 1.47 |
July | 0.219661E+09 | 0.210503E+09 | 0.00 | 0.122837E+09 | 3282380.24 | 0.00 | 0.522006E+11 | 0.00 | 1.42 |
August | 0.162678E+09 | 0.505334E+09 | 0.00 | 0.126815E+09 | 183728.56 | 0.00 | 0.488267E+11 | 0.00 | 1.40 |
September | 0.367334E+09 | 0.00 | 0.00 | 0.125441E+09 | 0.00 | 0.00 | 0.670106E+11 | 0.00 | 1.41 |
October | 0.390124E+09 | 0.00 | 0.00 | 0.125816E+09 | 0.00 | 0.00 | 0.788825E+11 | 0.00 | 1.08 |
November | 0.388510E+09 | 0.00 | 0.00 | 0.118464E+09 | 0.00 | 0.00 | 0.764726E+11 | 0.00 | 0.83 |
December | 0.570845E+09 | 0.00 | 0.00 | 0.116350E+09 | 0.00 | 0.00 | 0.738345E+11 | 0.00 | 0.65 |
Annual Sum or Average | 0.409736E+10 | 0.768976E+09 | 0.00 | 0.141902E+10 | 4811864.35 | 0.00 | 0.821476E+12 | 0.00 | 1.06 |
Minimum of Months | 0.162678E+09 | 0.00 | 0.00 | 97033676.32 | 0.00 | 0.00 | 0.488267E+11 | 0.00 | 0.58 |
Maximum of Months | 0.570845E+09 | 0.505334E+09 | 0.00 | 0.126815E+09 | 3282380.24 | 0.00 | 0.805269E+11 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.294683E+10 | 0.00 | 0.00 | 59322773.70 | 0.00 | 0.00 | 0.424925E+11 | 0.00 | 0.38 |
February | 0.210118E+10 | 0.00 | 0.00 | 68383103.20 | 0.00 | 0.00 | 0.442424E+11 | 0.00 | 0.49 |
March | 0.248430E+10 | 0.00 | 0.00 | 97975191.65 | 0.00 | 0.00 | 0.619754E+11 | 0.00 | 0.68 |
April | 0.543099E+10 | 17048695.67 | 0.00 | 97476344.93 | 0.00 | 0.00 | 0.584622E+11 | 0.00 | 0.84 |
May | 0.419507E+10 | 599035.73 | 0.00 | 93761266.41 | 0.00 | 0.00 | 0.537689E+11 | 0.00 | 0.91 |
June | 0.459156E+10 | 19997349.22 | 0.00 | 0.101833E+09 | 5735862.25 | 0.00 | 0.508494E+11 | 0.00 | 1.09 |
July | 0.911701E+10 | 0.194652E+09 | 0.00 | 93225208.07 | 3577247.91 | 0.00 | 0.381553E+11 | 0.00 | 1.12 |
August | 0.921982E+10 | 0.714130E+09 | 0.00 | 94250990.37 | 7206416.48 | 0.00 | 0.361119E+11 | 0.00 | 1.16 |
September | 0.400806E+10 | 0.00 | 0.00 | 91538382.49 | 0.00 | 0.00 | 0.465732E+11 | 0.00 | 0.96 |
October | 0.330230E+10 | 0.00 | 0.00 | 91864435.77 | 0.00 | 0.00 | 0.565217E+11 | 0.00 | 0.78 |
November | 0.241039E+10 | 0.00 | 0.00 | 86944920.68 | 0.00 | 0.00 | 0.542645E+11 | 0.00 | 0.59 |
December | 0.197337E+10 | 0.00 | 0.00 | 86791894.89 | 0.00 | 0.00 | 0.526358E+11 | 0.00 | 0.47 |
Annual Sum or Average | 0.517809E+11 | 0.946427E+09 | 0.00 | 0.106337E+10 | 16519526.65 | 0.00 | 0.596053E+12 | 0.00 | 0.79 |
Minimum of Months | 0.197337E+10 | 0.00 | 0.00 | 59322773.70 | 0.00 | 0.00 | 0.361119E+11 | 0.00 | 0.38 |
Maximum of Months | 0.921982E+10 | 0.714130E+09 | 0.00 | 0.101833E+09 | 7206416.48 | 0.00 | 0.619754E+11 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205667E+12 | 0.00 | 0.00 | 0.133956E+09 | 0.00 | 0.165755E+10 | 0.121478E+12 | 0.00 | 0.29 |
February | 0.140290E+12 | 0.00 | 0.00 | 0.226200E+09 | 0.00 | 0.00 | 0.178477E+12 | 0.00 | 0.35 |
March | 0.976602E+11 | 0.00 | 0.00 | 0.438407E+09 | 0.00 | 0.00 | 0.316498E+12 | 0.00 | 0.45 |
April | 0.485225E+11 | 0.165367E+09 | 0.00 | 0.497272E+09 | 81704722.32 | 0.00 | 0.344592E+12 | 0.00 | 0.53 |
May | 0.341001E+11 | 10420373.41 | 0.00 | 0.672504E+09 | 0.00 | 0.00 | 0.416305E+12 | 0.00 | 0.73 |
June | 0.265547E+11 | 0.175820E+09 | 0.00 | 0.741731E+09 | 53763122.31 | 0.00 | 0.392150E+12 | 0.00 | 0.85 |
July | 0.294974E+11 | 0.157450E+10 | 0.00 | 0.711188E+09 | 47090096.06 | 0.00 | 0.293299E+12 | 0.00 | 0.81 |
August | 0.259152E+11 | 0.604449E+10 | 0.00 | 0.717399E+09 | 36285547.86 | 0.00 | 0.271975E+12 | 0.00 | 0.80 |
September | 0.307361E+11 | 0.00 | 0.00 | 0.682340E+09 | 0.00 | 0.00 | 0.365210E+12 | 0.00 | 0.78 |
October | 0.695916E+11 | 0.00 | 0.00 | 0.500859E+09 | 0.00 | 0.00 | 0.339878E+12 | 0.00 | 0.55 |
November | 0.112377E+12 | 0.00 | 0.00 | 0.312355E+09 | 0.00 | 0.00 | 0.232038E+12 | 0.00 | 0.38 |
December | 0.166930E+12 | 0.00 | 0.00 | 0.211757E+09 | 0.00 | 0.00 | 0.167207E+12 | 0.00 | 0.30 |
Annual Sum or Average | 0.987842E+12 | 0.797059E+10 | 0.00 | 0.584597E+10 | 0.218843E+09 | 0.165755E+10 | 0.343911E+13 | 0.00 | 0.57 |
Minimum of Months | 0.259152E+11 | 0.00 | 0.00 | 0.133956E+09 | 0.00 | 0.00 | 0.121478E+12 | 0.00 | 0.29 |
Maximum of Months | 0.205667E+12 | 0.604449E+10 | 0.00 | 0.741731E+09 | 81704722.32 | 0.165755E+10 | 0.416305E+12 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266296E+11 | 0.00 | 0.00 | 646384.08 | 0.00 | 0.100514E+10 | 0.128142E+10 | 0.00 | 0.27 |
February | 0.216999E+11 | 0.00 | 0.00 | 4485442.31 | 0.00 | 0.524645E+09 | 0.465667E+10 | 0.00 | 0.31 |
March | 0.183808E+11 | 0.00 | 0.00 | 14893024.32 | 0.00 | 0.133140E+09 | 0.142174E+11 | 0.00 | 0.38 |
April | 0.112896E+11 | 4341156.75 | 0.00 | 28881214.02 | 3066100.92 | 1933115.22 | 0.219635E+11 | 0.00 | 0.47 |
May | 0.820890E+10 | 0.00 | 0.00 | 48315439.92 | 0.00 | 0.00 | 0.323620E+11 | 0.00 | 0.67 |
June | 0.481908E+10 | 7261373.81 | 0.00 | 62717588.93 | 3341798.89 | 0.00 | 0.349650E+11 | 0.00 | 0.83 |
July | 0.303835E+10 | 0.102899E+09 | 0.00 | 64912922.44 | 4204483.26 | 0.00 | 0.284671E+11 | 0.00 | 0.81 |
August | 0.344869E+10 | 0.438328E+09 | 0.00 | 64714104.90 | 10125011.11 | 0.00 | 0.236799E+11 | 0.00 | 0.79 |
September | 0.752675E+10 | 0.00 | 0.00 | 46683756.80 | 0.00 | 0.00 | 0.259732E+11 | 0.00 | 0.70 |
October | 0.131487E+11 | 0.00 | 0.00 | 22103580.79 | 0.00 | 30640913.80 | 0.179215E+11 | 0.00 | 0.45 |
November | 0.202567E+11 | 0.00 | 0.00 | 5980631.40 | 0.00 | 0.382553E+09 | 0.620687E+10 | 0.00 | 0.32 |
December | 0.250694E+11 | 0.00 | 0.00 | 856872.70 | 0.00 | 0.771883E+09 | 0.190823E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.163517E+12 | 0.552829E+09 | 0.00 | 0.365191E+09 | 20737394.17 | 0.284994E+10 | 0.213603E+12 | 0.00 | 0.53 |
Minimum of Months | 0.303835E+10 | 0.00 | 0.00 | 646384.08 | 0.00 | 0.00 | 0.128142E+10 | 0.00 | 0.27 |
Maximum of Months | 0.266296E+11 | 0.438328E+09 | 0.00 | 64912922.44 | 10125011.11 | 0.100514E+10 | 0.349650E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.439195E+10 | 0.00 | 0.00 | 32309.60 | 0.00 | 465910.22 | 65941766.49 | 0.00 | 0.29 |
February | 0.345690E+10 | 0.00 | 0.00 | 824636.36 | 0.00 | 0.00 | 0.842845E+09 | 0.00 | 0.36 |
March | 0.267048E+10 | 0.00 | 0.00 | 3647802.52 | 0.00 | 0.00 | 0.311610E+10 | 0.00 | 0.50 |
April | 0.191805E+10 | 2517034.80 | 0.00 | 6160348.05 | 0.00 | 0.00 | 0.458383E+10 | 0.00 | 0.71 |
May | 0.138292E+10 | 139127.14 | 0.00 | 8260002.60 | 0.00 | 0.00 | 0.542619E+10 | 0.00 | 0.89 |
June | 0.890180E+09 | 3341441.27 | 0.00 | 11314118.18 | 777136.67 | 0.00 | 0.601570E+10 | 0.00 | 1.15 |
July | 0.138667E+10 | 33398219.24 | 0.00 | 11566830.29 | 484671.77 | 0.00 | 0.482484E+10 | 0.00 | 1.24 |
August | 0.143226E+10 | 0.118454E+09 | 0.00 | 10933075.20 | 976378.14 | 0.00 | 0.419495E+10 | 0.00 | 1.21 |
September | 0.144750E+10 | 0.00 | 0.00 | 6972111.83 | 0.00 | 0.00 | 0.404056E+10 | 0.00 | 0.87 |
October | 0.233978E+10 | 0.00 | 0.00 | 3996120.60 | 0.00 | 0.00 | 0.322384E+10 | 0.00 | 0.58 |
November | 0.279891E+10 | 0.00 | 0.00 | 1883602.69 | 0.00 | 0.00 | 0.196535E+10 | 0.00 | 0.40 |
December | 0.371669E+10 | 0.00 | 0.00 | 436542.70 | 0.00 | 0.00 | 0.827802E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.278323E+11 | 0.157849E+09 | 0.00 | 66027500.63 | 2238186.58 | 465910.22 | 0.391279E+11 | 0.00 | 0.71 |
Minimum of Months | 0.890180E+09 | 0.00 | 0.00 | 32309.60 | 0.00 | 0.00 | 65941766.49 | 0.00 | 0.29 |
Maximum of Months | 0.439195E+10 | 0.118454E+09 | 0.00 | 11566830.29 | 976378.14 | 465910.22 | 0.601570E+10 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.605410E+10 | 0.00 | 0.00 | 500.85 | 0.00 | 3410984.32 | 4891162.79 | 0.00 | 0.61 |
February | 0.524473E+10 | 0.00 | 0.00 | 351964.83 | 0.00 | 4057158.25 | 0.444479E+09 | 0.00 | 0.73 |
March | 0.494333E+10 | 0.00 | 0.00 | 1735783.64 | 0.00 | 0.00 | 0.222653E+10 | 0.00 | 0.93 |
April | 0.371377E+10 | 1753929.15 | 0.00 | 4752777.69 | 284409.09 | 0.00 | 0.378257E+10 | 0.00 | 1.23 |
May | 0.295647E+10 | 109935.85 | 0.00 | 6512634.40 | 0.00 | 0.00 | 0.449274E+10 | 0.00 | 1.46 |
June | 0.210279E+10 | 2354221.97 | 0.00 | 9235280.81 | 1056730.66 | 0.00 | 0.539563E+10 | 0.00 | 1.84 |
July | 0.277015E+10 | 25925649.96 | 0.00 | 8996538.70 | 659044.34 | 0.00 | 0.381936E+10 | 0.00 | 1.92 |
August | 0.278428E+10 | 90003945.36 | 0.00 | 8517034.33 | 778282.78 | 0.00 | 0.338169E+10 | 0.00 | 1.97 |
September | 0.300026E+10 | 0.00 | 0.00 | 5889625.40 | 0.00 | 0.00 | 0.353704E+10 | 0.00 | 1.55 |
October | 0.461939E+10 | 0.00 | 0.00 | 2502024.74 | 0.00 | 0.00 | 0.222711E+10 | 0.00 | 1.09 |
November | 0.590495E+10 | 0.00 | 0.00 | 148919.77 | 0.00 | 0.00 | 0.305570E+09 | 0.00 | 0.80 |
December | 0.608913E+10 | 0.00 | 0.00 | 34228.75 | 0.00 | 4972170.95 | 79234881.69 | 0.00 | 0.65 |
Annual Sum or Average | 0.501834E+11 | 0.120148E+09 | 0.00 | 48677313.91 | 2778466.87 | 12440313.53 | 0.296968E+11 | 0.00 | 1.24 |
Minimum of Months | 0.210279E+10 | 0.00 | 0.00 | 500.85 | 0.00 | 0.00 | 4891162.79 | 0.00 | 0.61 |
Maximum of Months | 0.608913E+10 | 90003945.36 | 0.00 | 9235280.81 | 1056730.66 | 4972170.95 | 0.539563E+10 | 0.00 | 1.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.751641E+10 | 0.00 | 0.00 | 1261906.18 | 0.00 | 0.155147E+09 | 0.109468E+10 | 0.00 | 0.57 |
February | 0.618278E+10 | 0.00 | 0.00 | 3778826.72 | 0.00 | 54726625.16 | 0.292826E+10 | 0.00 | 0.78 |
March | 0.601259E+10 | 0.00 | 0.00 | 7575067.31 | 0.00 | 600404.28 | 0.620667E+10 | 0.00 | 1.06 |
April | 0.477895E+10 | 6045772.27 | 0.00 | 9357765.34 | 0.00 | 0.00 | 0.697031E+10 | 0.00 | 1.31 |
May | 0.417012E+10 | 245401.32 | 0.00 | 10016714.71 | 0.00 | 0.00 | 0.670031E+10 | 0.00 | 1.43 |
June | 0.340259E+10 | 3974825.63 | 0.00 | 11417664.64 | 1489447.75 | 0.00 | 0.633740E+10 | 0.00 | 1.63 |
July | 0.387529E+10 | 54022962.20 | 0.00 | 12781326.08 | 928914.19 | 0.00 | 0.526081E+10 | 0.00 | 1.82 |
August | 0.377369E+10 | 0.207725E+09 | 0.00 | 12960044.58 | 432084.98 | 0.00 | 0.475742E+10 | 0.00 | 1.86 |
September | 0.371942E+10 | 0.00 | 0.00 | 14149938.24 | 0.00 | 0.00 | 0.675108E+10 | 0.00 | 1.78 |
October | 0.531316E+10 | 0.00 | 0.00 | 8985811.98 | 0.00 | 0.00 | 0.655590E+10 | 0.00 | 1.29 |
November | 0.700541E+10 | 0.00 | 0.00 | 2640715.04 | 0.00 | 5735087.90 | 0.229879E+10 | 0.00 | 0.79 |
December | 0.725977E+10 | 0.00 | 0.00 | 2740883.00 | 0.00 | 37894517.42 | 0.215828E+10 | 0.00 | 0.65 |
Annual Sum or Average | 0.630102E+11 | 0.272014E+09 | 0.00 | 97666663.82 | 2850446.92 | 0.254104E+09 | 0.580199E+11 | 0.00 | 1.25 |
Minimum of Months | 0.340259E+10 | 0.00 | 0.00 | 1261906.18 | 0.00 | 0.00 | 0.109468E+10 | 0.00 | 0.57 |
Maximum of Months | 0.751641E+10 | 0.207725E+09 | 0.00 | 14149938.24 | 1489447.75 | 0.155147E+09 | 0.697031E+10 | 0.00 | 1.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.705945E+10 | 0.00 | 0.00 | 137191.63 | 0.00 | 0.00 | 0.260006E+09 | 0.00 | 0.74 |
February | 0.504439E+10 | 0.00 | 0.00 | 1811283.53 | 0.00 | 0.00 | 0.202118E+10 | 0.00 | 0.92 |
March | 0.250615E+10 | 0.00 | 0.00 | 7179041.07 | 0.00 | 0.00 | 0.689675E+10 | 0.00 | 1.26 |
April | 0.141730E+10 | 4432937.33 | 0.00 | 13499920.32 | 0.00 | 0.00 | 0.899081E+10 | 0.00 | 1.80 |
May | 0.229581E+10 | 143778.85 | 0.00 | 11424466.43 | 0.00 | 0.00 | 0.673329E+10 | 0.00 | 1.88 |
June | 0.124656E+10 | 8599645.49 | 0.00 | 14762870.31 | 1059282.66 | 0.00 | 0.744382E+10 | 0.00 | 2.32 |
July | 0.190321E+10 | 62273471.85 | 0.00 | 19261584.64 | 233257.82 | 0.00 | 0.674981E+10 | 0.00 | 2.77 |
August | 0.183925E+10 | 0.197047E+09 | 0.00 | 19502092.36 | 1509410.96 | 0.00 | 0.631000E+10 | 0.00 | 2.72 |
September | 0.231175E+10 | 0.00 | 0.00 | 9527279.55 | 0.00 | 0.00 | 0.538819E+10 | 0.00 | 1.95 |
October | 0.307898E+10 | 0.00 | 0.00 | 5594367.50 | 0.00 | 0.00 | 0.546175E+10 | 0.00 | 1.41 |
November | 0.337083E+10 | 0.00 | 0.00 | 3453011.86 | 0.00 | 0.00 | 0.425884E+10 | 0.00 | 1.00 |
December | 0.352479E+10 | 0.00 | 0.00 | 3305821.37 | 0.00 | 0.00 | 0.410462E+10 | 0.00 | 0.81 |
Annual Sum or Average | 0.355985E+11 | 0.272497E+09 | 0.00 | 0.109459E+09 | 2801951.44 | 0.00 | 0.646191E+11 | 0.00 | 1.64 |
Minimum of Months | 0.124656E+10 | 0.00 | 0.00 | 137191.63 | 0.00 | 0.00 | 0.260006E+09 | 0.00 | 0.74 |
Maximum of Months | 0.705945E+10 | 0.197047E+09 | 0.00 | 19502092.36 | 1509410.96 | 0.00 | 0.899081E+10 | 0.00 | 2.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.222212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182719E+11 | 0.00 | 0.00 | 0.28 |
February | 0.273062E+11 | 0.00 | 0.00 | 388780.38 | 0.00 | 0.861531E+10 | 0.573576E+09 | 0.00 | 0.31 |
March | 0.367693E+11 | 0.00 | 0.00 | 1252372.50 | 0.00 | 0.202586E+10 | 0.247694E+10 | 0.00 | 0.36 |
April | 0.257665E+11 | 23497430.99 | 0.00 | 15853848.49 | 10355839.21 | 0.206153E+09 | 0.124676E+11 | 0.00 | 0.42 |
May | 0.181603E+11 | 2074483.42 | 0.00 | 48160626.23 | 0.00 | 0.00 | 0.307056E+11 | 0.00 | 0.67 |
June | 0.107936E+11 | 29925392.85 | 0.00 | 71608241.40 | 6814321.55 | 0.00 | 0.375917E+11 | 0.00 | 0.84 |
July | 0.852213E+10 | 0.279049E+09 | 0.00 | 78111366.41 | 5968534.61 | 0.00 | 0.313940E+11 | 0.00 | 0.86 |
August | 0.903748E+10 | 0.102693E+10 | 0.00 | 67383903.95 | 4599089.12 | 0.00 | 0.250814E+11 | 0.00 | 0.80 |
September | 0.183188E+11 | 0.00 | 0.00 | 40278951.48 | 0.00 | 0.00 | 0.218820E+11 | 0.00 | 0.66 |
October | 0.319334E+11 | 0.00 | 0.00 | 7452891.38 | 0.00 | 0.468674E+09 | 0.672822E+10 | 0.00 | 0.42 |
November | 0.328546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426312E+10 | 0.00 | 0.00 | 0.32 |
December | 0.258566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133571E+11 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.267540E+12 | 0.136147E+10 | 0.00 | 0.330491E+09 | 27737784.50 | 0.472081E+11 | 0.168901E+12 | 0.00 | 0.52 |
Minimum of Months | 0.852213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.367693E+11 | 0.102693E+10 | 0.00 | 78111366.41 | 10355839.21 | 0.182719E+11 | 0.375917E+11 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.337776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278520E+11 | 0.00 | 0.00 | 0.66 |
February | 0.439128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118262E+11 | 0.00 | 0.00 | 0.74 |
March | 0.548829E+11 | 0.00 | 0.00 | 5585495.58 | 0.00 | 0.280097E+10 | 0.581374E+10 | 0.00 | 0.85 |
April | 0.353301E+11 | 22444992.63 | 0.00 | 29272335.17 | 15842665.11 | 0.706569E+09 | 0.240330E+11 | 0.00 | 1.01 |
May | 0.349417E+11 | 2054559.80 | 0.00 | 46263473.03 | 0.00 | 21795048.76 | 0.319657E+11 | 0.00 | 1.36 |
June | 0.242818E+11 | 25855087.12 | 0.00 | 76495254.71 | 10424748.02 | 0.00 | 0.428525E+11 | 0.00 | 1.71 |
July | 0.198395E+11 | 0.258467E+09 | 0.00 | 83064134.08 | 9130838.47 | 0.00 | 0.321909E+11 | 0.00 | 1.65 |
August | 0.185139E+11 | 0.944278E+09 | 0.00 | 75095716.58 | 2851256.41 | 0.00 | 0.286267E+11 | 0.00 | 1.64 |
September | 0.358244E+11 | 0.00 | 0.00 | 44729169.46 | 0.00 | 7386307.70 | 0.237714E+11 | 0.00 | 1.46 |
October | 0.491556E+11 | 0.00 | 0.00 | 10665186.08 | 0.00 | 0.960389E+09 | 0.100388E+11 | 0.00 | 0.99 |
November | 0.496607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709384E+10 | 0.00 | 0.00 | 0.76 |
December | 0.388563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210281E+11 | 0.00 | 0.00 | 0.65 |
Annual Sum or Average | 0.438977E+12 | 0.125310E+10 | 0.00 | 0.371171E+09 | 38249508.02 | 0.722972E+11 | 0.199293E+12 | 0.00 | 1.13 |
Minimum of Months | 0.185139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 0.548829E+11 | 0.944278E+09 | 0.00 | 83064134.08 | 15842665.11 | 0.278520E+11 | 0.428525E+11 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.585203E+11 | 0.00 | 0.00 | 6846325.42 | 0.00 | 0.223404E+11 | 0.645595E+10 | 0.00 | 0.60 |
February | 0.537990E+11 | 0.00 | 0.00 | 32408622.69 | 0.00 | 0.100583E+11 | 0.234791E+11 | 0.00 | 0.76 |
March | 0.592405E+11 | 0.00 | 0.00 | 60094635.97 | 0.00 | 0.211072E+10 | 0.455570E+11 | 0.00 | 0.95 |
April | 0.455204E+11 | 0.110492E+09 | 0.00 | 65754818.25 | 0.00 | 0.578572E+09 | 0.471320E+11 | 0.00 | 1.06 |
May | 0.466424E+11 | 4195622.42 | 0.00 | 77735449.09 | 0.00 | 22166775.58 | 0.504505E+11 | 0.00 | 1.32 |
June | 0.390181E+11 | 39669205.58 | 0.00 | 84715576.01 | 14596325.15 | 0.00 | 0.451050E+11 | 0.00 | 1.45 |
July | 0.303864E+11 | 0.535950E+09 | 0.00 | 0.100436E+09 | 12784643.52 | 0.00 | 0.391318E+11 | 0.00 | 1.50 |
August | 0.283136E+11 | 0.213463E+10 | 0.00 | 0.100115E+09 | 9674670.39 | 0.00 | 0.338099E+11 | 0.00 | 1.48 |
September | 0.406511E+11 | 0.00 | 0.00 | 0.131462E+09 | 0.00 | 0.00 | 0.561111E+11 | 0.00 | 1.73 |
October | 0.518866E+11 | 0.00 | 0.00 | 78799083.17 | 0.00 | 0.427637E+09 | 0.533186E+11 | 0.00 | 1.20 |
November | 0.644957E+11 | 0.00 | 0.00 | 16658081.15 | 0.00 | 0.680878E+10 | 0.113679E+11 | 0.00 | 0.73 |
December | 0.553905E+11 | 0.00 | 0.00 | 17147248.51 | 0.00 | 0.192181E+11 | 0.129558E+11 | 0.00 | 0.62 |
Annual Sum or Average | 0.573865E+12 | 0.282494E+10 | 0.00 | 0.772172E+09 | 37055639.06 | 0.615646E+11 | 0.424875E+12 | 0.00 | 1.12 |
Minimum of Months | 0.283136E+11 | 0.00 | 0.00 | 6846325.42 | 0.00 | 0.00 | 0.645595E+10 | 0.00 | 0.60 |
Maximum of Months | 0.644957E+11 | 0.213463E+10 | 0.00 | 0.131462E+09 | 14596325.15 | 0.223404E+11 | 0.561111E+11 | 0.00 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.449850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195980E+11 | 0.00 | 0.00 | 0.69 |
February | 0.468723E+11 | 0.00 | 0.00 | 2263822.48 | 0.00 | 0.925027E+10 | 0.236894E+10 | 0.00 | 0.78 |
March | 0.572267E+11 | 0.00 | 0.00 | 8531733.43 | 0.00 | 0.155328E+10 | 0.871537E+10 | 0.00 | 0.91 |
April | 0.436485E+11 | 49943582.48 | 0.00 | 26071133.76 | 2819909.39 | 0.151682E+09 | 0.187440E+11 | 0.00 | 1.07 |
May | 0.367917E+11 | 2118313.93 | 0.00 | 62018061.12 | 0.00 | 8269673.91 | 0.330220E+11 | 0.00 | 1.50 |
June | 0.286897E+11 | 82260397.53 | 0.00 | 65967735.95 | 10929279.25 | 0.00 | 0.331922E+11 | 0.00 | 1.70 |
July | 0.186961E+11 | 0.551248E+09 | 0.00 | 92435759.56 | 3284348.72 | 0.00 | 0.335530E+11 | 0.00 | 1.82 |
August | 0.200323E+11 | 0.156493E+10 | 0.00 | 73589192.94 | 7376336.57 | 0.00 | 0.243711E+11 | 0.00 | 1.59 |
September | 0.376865E+11 | 0.00 | 0.00 | 49419831.38 | 0.00 | 0.00 | 0.228959E+11 | 0.00 | 1.58 |
October | 0.535903E+11 | 0.00 | 0.00 | 11932740.47 | 0.00 | 0.161442E+09 | 0.978598E+10 | 0.00 | 1.07 |
November | 0.542621E+11 | 0.00 | 0.00 | 441800.48 | 0.00 | 0.454874E+10 | 0.669613E+09 | 0.00 | 0.79 |
December | 0.501030E+11 | 0.00 | 0.00 | 10216.94 | 0.00 | 0.125431E+11 | 0.106218E+09 | 0.00 | 0.68 |
Annual Sum or Average | 0.492584E+12 | 0.225050E+10 | 0.00 | 0.392682E+09 | 24409873.92 | 0.478148E+11 | 0.187424E+12 | 0.00 | 1.19 |
Minimum of Months | 0.186961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
Maximum of Months | 0.572267E+11 | 0.156493E+10 | 0.00 | 92435759.56 | 10929279.25 | 0.195980E+11 | 0.335530E+11 | 0.00 | 1.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294745E+10 | 0.00 | 0.00 | 0.30 |
February | 0.168174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204175E+10 | 0.00 | 0.00 | 0.34 |
March | 0.335752E+10 | 0.00 | 0.00 | 7624.04 | 0.00 | 0.904732E+09 | 28795339.88 | 0.00 | 0.39 |
April | 0.288782E+10 | 587603.79 | 0.00 | 871491.65 | 424340.56 | 0.372002E+09 | 0.664948E+09 | 0.00 | 0.44 |
May | 0.241869E+10 | 0.00 | 0.00 | 3543646.56 | 0.00 | 48963498.73 | 0.230266E+10 | 0.00 | 0.65 |
June | 0.156677E+10 | 1131867.11 | 0.00 | 5996227.53 | 462496.46 | 2484152.05 | 0.319195E+10 | 0.00 | 0.84 |
July | 0.105202E+10 | 17416755.23 | 0.00 | 7223204.98 | 581889.78 | 0.00 | 0.298128E+10 | 0.00 | 0.87 |
August | 0.116618E+10 | 71944357.67 | 0.00 | 6173638.72 | 1401275.75 | 0.00 | 0.209671E+10 | 0.00 | 0.80 |
September | 0.240288E+10 | 0.00 | 0.00 | 2708725.75 | 0.00 | 30821248.58 | 0.141468E+10 | 0.00 | 0.65 |
October | 0.318082E+10 | 0.00 | 0.00 | 193145.81 | 0.00 | 0.475017E+09 | 0.180877E+09 | 0.00 | 0.43 |
November | 0.202544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166681E+10 | 0.00 | 0.00 | 0.35 |
December | 0.119669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269757E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.240596E+11 | 91080583.80 | 0.00 | 26717705.04 | 2870002.55 | 0.111876E+11 | 0.128619E+11 | 0.00 | 0.53 |
Minimum of Months | 0.105202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.335752E+10 | 71944357.67 | 0.00 | 7223204.98 | 1401275.75 | 0.294745E+10 | 0.319195E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357771E+10 | 0.00 | 0.00 | 0.63 |
February | 0.263387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235365E+10 | 0.00 | 0.00 | 0.71 |
March | 0.462356E+10 | 0.00 | 0.00 | 143181.80 | 0.00 | 0.918891E+09 | 0.256039E+09 | 0.00 | 0.82 |
April | 0.322040E+10 | 591639.71 | 0.00 | 2363396.95 | 574920.30 | 0.328869E+09 | 0.193758E+10 | 0.00 | 0.96 |
May | 0.322155E+10 | 0.00 | 0.00 | 4254401.31 | 0.00 | 83677999.62 | 0.300324E+10 | 0.00 | 1.30 |
June | 0.220098E+10 | 906650.63 | 0.00 | 7464999.94 | 626616.04 | 12420908.13 | 0.427296E+10 | 0.00 | 1.68 |
July | 0.173599E+10 | 15596375.54 | 0.00 | 8463923.65 | 751767.19 | 0.00 | 0.336515E+10 | 0.00 | 1.65 |
August | 0.164735E+10 | 66733030.87 | 0.00 | 7821177.12 | 1202892.12 | 0.00 | 0.277088E+10 | 0.00 | 1.64 |
September | 0.309857E+10 | 0.00 | 0.00 | 4198993.11 | 0.00 | 26711673.33 | 0.228870E+10 | 0.00 | 1.39 |
October | 0.408019E+10 | 0.00 | 0.00 | 687324.57 | 0.00 | 0.541474E+09 | 0.629376E+09 | 0.00 | 0.92 |
November | 0.291417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205284E+10 | 0.00 | 0.00 | 0.72 |
December | 0.194144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326865E+10 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.331675E+11 | 83827696.74 | 0.00 | 35397398.45 | 3156195.65 | 0.131649E+11 | 0.185239E+11 | 0.00 | 1.09 |
Minimum of Months | 0.164735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.462356E+10 | 66733030.87 | 0.00 | 8463923.65 | 1202892.12 | 0.357771E+10 | 0.427296E+10 | 0.00 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.392569E+10 | 0.00 | 0.00 | 275266.09 | 0.00 | 0.401352E+10 | 0.229583E+09 | 0.00 | 0.61 |
February | 0.397699E+10 | 0.00 | 0.00 | 2137570.94 | 0.00 | 0.237203E+10 | 0.163957E+10 | 0.00 | 0.74 |
March | 0.514582E+10 | 0.00 | 0.00 | 4411184.82 | 0.00 | 0.116766E+10 | 0.361760E+10 | 0.00 | 0.92 |
April | 0.432467E+10 | 3064289.04 | 0.00 | 5658990.68 | 0.00 | 0.589168E+09 | 0.411616E+10 | 0.00 | 1.05 |
May | 0.483509E+10 | 0.00 | 0.00 | 6866498.24 | 0.00 | 0.125757E+09 | 0.470760E+10 | 0.00 | 1.31 |
June | 0.413869E+10 | 1525914.47 | 0.00 | 7733233.03 | 937823.87 | 15052163.56 | 0.441367E+10 | 0.00 | 1.48 |
July | 0.307718E+10 | 32833156.95 | 0.00 | 10164932.55 | 119202.32 | 0.00 | 0.410421E+10 | 0.00 | 1.54 |
August | 0.288012E+10 | 0.147994E+09 | 0.00 | 10320956.02 | 272297.68 | 0.00 | 0.327495E+10 | 0.00 | 1.53 |
September | 0.409960E+10 | 0.00 | 0.00 | 12499507.04 | 0.00 | 53540980.21 | 0.532029E+10 | 0.00 | 1.71 |
October | 0.464837E+10 | 0.00 | 0.00 | 6007250.06 | 0.00 | 0.609708E+09 | 0.436043E+10 | 0.00 | 1.13 |
November | 0.474145E+10 | 0.00 | 0.00 | 976168.25 | 0.00 | 0.223607E+10 | 0.608599E+09 | 0.00 | 0.72 |
December | 0.368259E+10 | 0.00 | 0.00 | 818105.65 | 0.00 | 0.353114E+10 | 0.681428E+09 | 0.00 | 0.61 |
Annual Sum or Average | 0.494763E+11 | 0.185418E+09 | 0.00 | 67869663.37 | 1329323.88 | 0.147137E+11 | 0.370741E+11 | 0.00 | 1.11 |
Minimum of Months | 0.288012E+10 | 0.00 | 0.00 | 275266.09 | 0.00 | 0.00 | 0.229583E+09 | 0.00 | 0.61 |
Maximum of Months | 0.514582E+10 | 0.147994E+09 | 0.00 | 12499507.04 | 937823.87 | 0.401352E+10 | 0.532029E+10 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337429E+10 | 0.00 | 0.00 | 0.70 |
February | 0.348670E+10 | 0.00 | 0.00 | 106803.59 | 0.00 | 0.193853E+10 | 0.129580E+09 | 0.00 | 0.80 |
March | 0.514088E+10 | 0.00 | 0.00 | 581579.91 | 0.00 | 0.779888E+09 | 0.626518E+09 | 0.00 | 0.93 |
April | 0.418218E+10 | 1491791.50 | 0.00 | 2326549.36 | 53351.04 | 0.322998E+09 | 0.165885E+10 | 0.00 | 1.09 |
May | 0.398087E+10 | 0.00 | 0.00 | 5674345.45 | 0.00 | 49961231.61 | 0.301074E+10 | 0.00 | 1.51 |
June | 0.317471E+10 | 2971067.56 | 0.00 | 6057974.61 | 697823.39 | 436981.65 | 0.312307E+10 | 0.00 | 1.75 |
July | 0.201104E+10 | 33471969.01 | 0.00 | 10116326.01 | 805088.93 | 0.00 | 0.339701E+10 | 0.00 | 1.88 |
August | 0.217947E+10 | 0.106879E+09 | 0.00 | 7290512.27 | 2114271.34 | 0.00 | 0.218797E+10 | 0.00 | 1.63 |
September | 0.382839E+10 | 0.00 | 0.00 | 4509856.15 | 0.00 | 2277021.43 | 0.205270E+10 | 0.00 | 1.58 |
October | 0.476938E+10 | 0.00 | 0.00 | 902658.71 | 0.00 | 0.416758E+09 | 0.719781E+09 | 0.00 | 1.04 |
November | 0.393003E+10 | 0.00 | 0.00 | 19360.78 | 0.00 | 0.158983E+10 | 8085067.18 | 0.00 | 0.80 |
December | 0.291027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288704E+10 | 0.00 | 0.00 | 0.70 |
Annual Sum or Average | 0.422593E+11 | 0.144814E+09 | 0.00 | 37585966.86 | 3670534.70 | 0.113620E+11 | 0.169143E+11 | 0.00 | 1.20 |
Minimum of Months | 0.201104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
Maximum of Months | 0.514088E+10 | 0.106879E+09 | 0.00 | 10116326.01 | 2114271.34 | 0.337429E+10 | 0.339701E+10 | 0.00 | 1.88 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2830825.69 | 0.00 | 0.00 | 0.621512E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6917622.84 | 0.00 | 0.00 | 0.514527E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 13310054.25 | 0.00 | 0.00 | 0.542509E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 16643043.37 | 0.00 | 0.00 | 0.422155E+09 | 0.00 | 0.29 |
May | 0.00 | 10035.64 | 0.00 | 3957659.03 | 0.00 | 0.00 | 0.380880E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 8496929.53 | 0.00 | 0.00 | 0.298480E+09 | 0.00 | 0.30 |
July | 0.00 | 3883692.79 | 0.00 | 11102044.85 | 0.00 | 0.00 | 0.172317E+09 | 0.00 | 0.28 |
August | 0.00 | 12689949.48 | 0.00 | 14561320.52 | 0.00 | 0.00 | 0.130657E+09 | 0.00 | 0.31 |
September | 0.00 | 69650.83 | 0.00 | 3820896.25 | 0.00 | 0.00 | 0.258103E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 7946670.86 | 0.00 | 0.00 | 0.426353E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11554207.95 | 0.00 | 0.00 | 0.496192E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16169176.48 | 0.00 | 0.00 | 0.577126E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 16653328.74 | 0.00 | 0.117310E+09 | 0.00 | 0.00 | 0.484081E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2830825.69 | 0.00 | 0.00 | 0.130657E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 12689949.48 | 0.00 | 16643043.37 | 0.00 | 0.00 | 0.621512E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.286244E+09 | 0.00 | 0.00 | 13799303.29 | 0.00 | 0.00 | 0.594835E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 55649548.28 | 0.00 | 0.00 | 0.516085E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.117368E+09 | 0.00 | 0.00 | 0.543973E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.152640E+09 | 0.00 | 0.00 | 0.423373E+10 | 0.00 | 0.29 |
May | 0.00 | 68635.37 | 0.00 | 33265177.28 | 0.00 | 0.00 | 0.382155E+10 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 77787374.20 | 0.00 | 0.00 | 0.299294E+10 | 0.00 | 0.30 |
July | 0.00 | 38481628.62 | 0.00 | 0.104470E+09 | 0.00 | 0.00 | 0.173016E+10 | 0.00 | 0.28 |
August | 0.00 | 0.126317E+09 | 0.00 | 0.137473E+09 | 0.00 | 0.00 | 0.131510E+10 | 0.00 | 0.31 |
September | 0.00 | 550237.95 | 0.00 | 32444597.37 | 0.00 | 0.00 | 0.260689E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 67999344.95 | 0.00 | 0.00 | 0.427609E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 99271959.88 | 0.00 | 0.00 | 0.497781E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.141100E+09 | 0.00 | 0.00 | 0.579145E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.286244E+09 | 0.165417E+09 | 0.00 | 0.103327E+10 | 0.00 | 0.00 | 0.482947E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 13799303.29 | 0.00 | 0.00 | 0.131510E+10 | 0.00 | 0.28 |
Maximum of Months | 0.286244E+09 | 0.126317E+09 | 0.00 | 0.152640E+09 | 0.00 | 0.00 | 0.594835E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208163E+09 | 0.00 | 0.00 | 649400.19 | 0.00 | 0.00 | 0.409812E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4740965.63 | 0.00 | 0.00 | 0.517039E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 10931877.50 | 0.00 | 0.00 | 0.544883E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 14783409.10 | 0.00 | 0.00 | 0.423951E+09 | 0.00 | 0.29 |
May | 0.00 | 6460.19 | 0.00 | 3038577.29 | 0.00 | 0.00 | 0.382874E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 7646851.82 | 0.00 | 0.00 | 0.299649E+09 | 0.00 | 0.30 |
July | 0.00 | 3855375.36 | 0.00 | 10388818.14 | 0.00 | 0.00 | 0.173222E+09 | 0.00 | 0.28 |
August | 0.00 | 12638187.35 | 0.00 | 13642872.78 | 0.00 | 0.00 | 0.131790E+09 | 0.00 | 0.31 |
September | 0.00 | 52065.17 | 0.00 | 2931506.19 | 0.00 | 0.00 | 0.262426E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6133604.27 | 0.00 | 0.00 | 0.428714E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9043719.86 | 0.00 | 0.00 | 0.498924E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13075519.37 | 0.00 | 0.00 | 0.580214E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.208163E+09 | 16552088.07 | 0.00 | 97007122.14 | 0.00 | 0.00 | 0.465350E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 649400.19 | 0.00 | 0.00 | 0.131790E+09 | 0.00 | 0.28 |
Maximum of Months | 0.208163E+09 | 12638187.35 | 0.00 | 14783409.10 | 0.00 | 0.00 | 0.580214E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.205976E+09 | 0.00 | 0.00 | 0.142830E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.379748E+09 | 0.00 | 0.00 | 0.119055E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.678468E+09 | 0.00 | 0.00 | 0.122675E+11 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.00 | 0.830387E+09 | 0.00 | 0.00 | 0.910128E+10 | 0.00 | 0.32 |
May | 0.00 | 534039.08 | 0.00 | 0.213091E+09 | 0.00 | 0.00 | 0.814563E+10 | 0.00 | 0.33 |
June | 0.00 | 0.00 | 0.00 | 0.426328E+09 | 0.00 | 0.00 | 0.622183E+10 | 0.00 | 0.34 |
July | 0.00 | 94314737.45 | 0.00 | 0.533728E+09 | 0.00 | 0.00 | 0.341614E+10 | 0.00 | 0.31 |
August | 0.00 | 83280906.29 | 0.00 | 0.761896E+09 | 0.00 | 0.00 | 0.252492E+10 | 0.00 | 0.35 |
September | 0.00 | 4152995.11 | 0.00 | 0.203480E+09 | 0.00 | 0.00 | 0.527758E+10 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.00 | 0.416305E+09 | 0.00 | 0.00 | 0.906791E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.597973E+09 | 0.00 | 0.00 | 0.107046E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.827835E+09 | 0.00 | 0.00 | 0.129082E+11 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.182283E+09 | 0.00 | 0.607521E+10 | 0.00 | 0.00 | 0.105824E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.203480E+09 | 0.00 | 0.00 | 0.252492E+10 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 94314737.45 | 0.00 | 0.830387E+09 | 0.00 | 0.00 | 0.142830E+11 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:04:01
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.127144E+12 | 0.231519E+11 | 0.00 | 0.170297E+13 | 0.542887E+12 |
February | 0.241112E+12 | 0.208928E+11 | 0.00 | 0.171643E+13 | 0.840346E+12 |
March | 0.436079E+12 | 0.199284E+11 | 0.00 | 0.207248E+13 | 0.131999E+13 |
April | 0.667102E+12 | 0.191141E+11 | 0.00 | 0.210683E+13 | 0.178563E+13 |
May | 0.873867E+12 | 0.152172E+11 | 0.00 | 0.219385E+13 | 0.782958E+12 |
June | 0.887998E+12 | 0.125818E+11 | 0.00 | 0.200935E+13 | 0.139318E+13 |
July | 0.932717E+12 | 0.109515E+11 | 0.00 | 0.199256E+13 | 0.217516E+13 |
August | 0.735531E+12 | 0.862220E+10 | 0.00 | 0.165002E+13 | 0.280207E+13 |
September | 0.513353E+12 | 0.731588E+10 | 0.00 | 0.218234E+13 | 0.923077E+12 |
October | 0.331284E+12 | 0.160972E+11 | 0.00 | 0.221416E+13 | 0.994117E+12 |
November | 0.144132E+12 | 0.185209E+11 | 0.00 | 0.199332E+13 | 0.128758E+13 |
December | 0.971648E+11 | 0.198784E+11 | 0.00 | 0.186038E+13 | 0.170920E+13 |
Annual Sum or Average | 0.598748E+13 | 0.192272E+12 | 0.00 | 0.236947E+14 | 0.165562E+14 |
Minimum of Months | 0.971648E+11 | 0.731588E+10 | 0.00 | 0.165002E+13 | 0.542887E+12 |