Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190

Simulation Timestamp: 2023-10-16 09:03:06


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 31788.48 686.27 686.27
Net Site Energy 31788.48 686.27 686.27
Total Source Energy 97969.60 2115.04 2115.04
Net Source Energy 97969.60 2115.04 2115.04


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 640.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4111.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3711.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 670.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1941.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2525.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 801.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1454.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7725.98
Humidification 8.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.33
Heat Recovery 50.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 657.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 30490.10 1298.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10009.48
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 640.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 4111.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 3711.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 670.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5871.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 87.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2525.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 801.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1454.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7725.98
Humidification General 8.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.33
Heat Recovery General 50.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 657.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 640.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 4111.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 3711.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 670.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1941.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2525.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 801.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1454.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7725.98
Humidification Unassigned 8.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.33
Heat Recovery Unassigned 50.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 657.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 94.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 192.19 28.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.22
Other 371.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 658.24 28.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.22


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 94.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 192.19 28.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.22
Other 371.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 658.24 28.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.22


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 30490.104 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 30490.104 100.00
     
Total On-Site and Utility Electric Sources 30490.104 100.00
Total Electricity End Uses 30490.104 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 1232.78 57.10
Air to Air Heat Recovery for Heating 926.28 42.90
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 2159.06 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 10009.48 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 10009.48 100.00
Total Water End Uses 10009.48 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 29.67
Time Setpoint Not Met During Occupied Cooling 501.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 5940.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03
RunPeriod RUNPERIOD 1
Weather File Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Latitude [deg] 33.63
Longitude [deg] -84.4
Elevation [m] 308.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 9.3279 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.3279 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 9.3279 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.3279 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 16.0861 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 16.0861 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 16.0861 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 9.3279 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.3913 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.3913 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.3279 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 9.3279 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 9.3279 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 9.3279 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 9.3279 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 9.3279 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 9.3279 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 9.3279 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 9.3279 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 9.3279 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 9.3279 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 9.3279 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 9.3279 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 9.3279 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 9.3279 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 9.3279 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 16.0861 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 16.0861 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 16.0861 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 9.3279 18.58 484.4232  
Total 46320.38             9.3913 9.29 17.8789  
Conditioned Total 46320.38             9.3913 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.8860 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 03-AUG-15:50 13-FEB-07:10 - - - - - - - - - - 14-APR-15:00
Heating 0.00 1589015.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 453790.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 316816.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 794004.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 84885.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 235348.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 68250.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 92421.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 10207.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2051130.69 1599222.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1589015.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 453790.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 316816.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 5451.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 235348.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 68250.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 92421.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 10207.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 694.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 13021.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 11753.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2124.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48180.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6150.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7999.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 2539.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 4605.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 28.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 159.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 712.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 96562.16 1407.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 14.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 281.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 253.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 45.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 172.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 54.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 99.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2084.66 30.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 14.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 281.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 253.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 45.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 172.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 54.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 99.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2084.66 30.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.85
DATACENTER_BOT_ZN_6 DIRECT AIR 0.488735
DATACENTER_MID_ZN_6 DIRECT AIR 4.65
DATACENTER_TOP_ZN_6 DIRECT AIR 0.469960
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 22.10
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 6.15 0.309238 0.315000 1.94 0.824634 0.500000 0.001232 0.000165 1.94 12.80 0.008000
CORE_MID VAV BOX COMPONENT 58.05 0.327633 0.327000 18.98 0.873689 0.500000 0.001163 0.004064 18.98 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.74 0.331613 0.337000 1.93 0.884301 0.500000 0.001149 0.000766 2.70 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.992262 0.240683 0.300000 0.297679 0.641821 0.500000 0.001583 0.000122 0.429468 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.955957 0.160996 0.300000 0.286787 0.429322 0.500000 0.002367 0.000084 0.295666 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.14 0.210042 0.300000 0.341112 0.560111 0.500000 0.001814 0.000137 0.484494 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.23 0.124964 0.300000 0.369477 0.333239 0.500000 0.003049 0.000076 0.369477 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 9.31 0.256515 0.300000 2.79 0.684040 0.500000 0.001485 0.002058 7.28 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 9.80 0.157001 0.300000 2.94 0.418669 0.500000 0.002427 0.001350 4.78 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 10.73 0.222482 0.300000 3.22 0.593285 0.500000 0.001712 0.002035 7.20 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 10.37 0.148442 0.300000 3.11 0.395847 0.500000 0.002567 0.001304 4.61 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.06 0.224395 0.300000 0.319286 0.598387 0.500000 0.001698 0.000266 0.940328 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.01 0.153067 0.300000 0.301643 0.408179 0.500000 0.002489 0.000174 0.614373 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.20 0.199092 0.300000 0.359873 0.530911 0.500000 0.001914 0.000263 0.930660 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.13 0.136626 0.300000 0.337940 0.364337 0.500000 0.002789 0.000171 0.604058 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 18808.47 0.000165 379.16
CORE_MID VAV BOX REHEAT COIL 464580.39 0.004064 11044.24
CORE_TOP VAV BOX REHEAT COIL 87569.98 0.000766 2311.76
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 13894.74 0.000122 366.60
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 9564.50 0.000084 252.33
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 15671.90 0.000137 413.45
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 8690.05 0.000076 204.17
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 235288.57 0.002058 6204.29
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 154368.28 0.001350 4070.45
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 232645.67 0.002035 6134.66
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 149044.56 0.001304 3930.16
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 30372.89 0.000266 800.75
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 19843.93 0.000174 523.16
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 30061.01 0.000263 792.53
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 19511.04 0.000171 514.39
VAV_BOT WITH REHEAT HEATING COIL 56929.09 0.000498 933.50
VAV_MID WITH REHEAT HEATING COIL 552647.74 0.004835 9026.33
VAV_TOP WITH REHEAT HEATING COIL 53128.59 0.000465 876.29
CAV_BAS HEATING COIL 281605.15 0.002464 6249.44
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.23 3.23 10.47 3.23 9.71 9.71 0.300000 0.333009 9.71
VAV_MID WITH REHEAT 49.13 31.05 98.27 36.13 90.43 90.43 0.300000 0.399584 90.43
VAV_TOP WITH REHEAT 5.07 3.25 10.13 5.79 9.66 9.66 0.300000 0.599935 9.66
CAV_BAS 5.85 5.85 5.85 5.85 5.85 5.85 1.00 1.00 5.85
AIRLOOP DATACENTER BASEMENT 22.10 22.10 22.10 22.10 22.10 22.10 1.00 0.999989 22.10
AIRLOOP DATACENTER BOT 0.488735 0.488735 0.488735 0.488735 0.488735 0.488735 1.00 1.00 0.488735
AIRLOOP DATACENTER MID 4.65 4.65 4.65 4.65 4.65 4.65 1.00 1.00 4.65
AIRLOOP DATACENTER TOP 0.469960 0.469960 0.469960 0.469960 0.469960 0.469960 1.00 1.00 0.469960
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 9.71 2.54
VAV_MID WITH REHEAT_OA_CONTROLLER 90.43 25.38
VAV_TOP WITH REHEAT_OA_CONTROLLER 9.66 2.54
CAV_BAS_OA_CONTROLLER 5.85 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 22.10 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.488735 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.65 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.469960 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.54
VAV_MID WITH REHEAT OA HEAT RECOVERY 25.38
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 26.86 6.67 10.98 0.010431 0.008500 238172.21 0.010132 9.71
VAV_MID WITH REHEAT COOLING COIL 27.18 6.67 10.88 0.010679 0.008500 2330680.07 0.099153 90.43
VAV_TOP WITH REHEAT COOLING COIL 26.75 6.67 10.98 0.010417 0.008500 235167.98 0.010005 9.66
CAV_BAS COOLING COIL 25.83 6.67 11.37 0.010203 0.008500 129625.70 0.005515 5.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 9.71
VAV_MID WITH REHEAT FAN 90.43
VAV_TOP WITH REHEAT FAN 9.66
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.010132 0.000047
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000498  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.099153 0.000005
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.004835  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.010005 0.000048
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000465  
CAV_BAS_COOLC_CONTROLLER 0.005515 0.000086
CAV_BAS_HEATC_CONTROLLER 0.002464  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 22.10 437646.58 303283.71 0.010718
AIRLOOP DATACENTER BOT COOLING COIL 0.488735 9630.22 6683.16 0.000236
AIRLOOP DATACENTER MID COOLING COIL 4.65 91737.04 63598.28 0.002247
AIRLOOP DATACENTER TOP COOLING COIL 0.469960 9272.38 6430.23 0.000227
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 22.10 22.10 22.10 22.10 437646.58 437646.58 18278.08 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.488735 0.488735 0.488735 0.488735 9630.22 9630.22 844.37 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.65 4.65 4.65 4.65 91737.04 91737.04 8443.71 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.469960 0.469960 0.469960 0.469960 9272.38 9272.38 844.37 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 22.10
AIRLOOP DATACENTER BOT SUPPLY FAN 0.488735
AIRLOOP DATACENTER MID SUPPLY FAN 4.65
AIRLOOP DATACENTER TOP SUPPLY FAN 0.469960
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 22.10 437646.58 0.010718
AIRLOOP DATACENTER BOT HEATING COIL 0.488735 9630.22 0.000236
AIRLOOP DATACENTER MID HEATING COIL 4.65 91737.04 0.002247
AIRLOOP DATACENTER TOP HEATING COIL 0.469960 9272.38 0.000227
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 18278.08
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 844.37
AIRLOOP DATACENTER MID_SUPPHEATCOIL 8443.71
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 844.37
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000153 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.124804 25717.50  
HEATSYS1 PUMP 0.021296 6413.32 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.124804 14.98
HEATSYS1 0.021296 2.56
COOLSYS1_SUPPLY 0.124804 14.98
SINGLE WATER PLANT LOOP 0.013427 1.61
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.124804 0.124804 523865.35 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 2434226.56 2434226.56 0.021296
CENTRAL BOILER 553097.65 542182.77 0.013427
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.124804 17805.09
PLANT CIRC PUMP 0.013427 3424.68
SWHSYS1 PUMP 0.000440 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.124804 0.062735 1478271.96 1485342.51 0.073504
COOLSYS1 CHILLER2 0.124804 0.062735 1478271.96 1485342.51 0.073504
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013427 139666.47 58751.96 69833.23 7879.72 21362.98
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.147008 17.64
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.147008 44275.67
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 58.93 1762320.86 11.79 220290.11
TOWERWATERSYS COOLTOWER 2 58.93 1762320.86 11.79 220290.11
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.076347
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 11.90 7.70 4.00 7.90 13.80 17.20 20.80 24.80 26.10 26.50 22.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 33.63 -84.43 -5.00 308.00 97679 1.1610


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.60 22.50 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 9.328 4.842 0.000 0.000 0.000 0.000 14.170 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 16.086 215.299 0.000 0.000 0.000 0.000 231.385 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 16.086 215.299 0.000 0.000 0.000 0.000 231.385 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 16.086 215.299 0.000 0.000 0.000 0.000 231.385 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 9.328 484.423 0.000 0.000 0.000 0.000 493.751 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 25926.330 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25926.330
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 23283.667 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 23283.667
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 23283.667 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 23283.667
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 23283.667 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 23283.667
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2923.497 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.497
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2923.561 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.561
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2923.497 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.497
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2923.561 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.561
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2923.497 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.497
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2923.561 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.561
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 7310.116 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 7310.116
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 582.361 16.086 298.861 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 582.361
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 582.361 16.086 298.861 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 582.361
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 582.361 16.086 298.861 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 582.361


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.498 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.416 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.867 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.5004
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5391
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.3683
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
47 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
48 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
49 0 21.361010 0.87247630E-01 5.4456762  
50 9 0.14091426E-14 0.48101397E-16 -0.12271849E-09 -0.49605034E-17
51 8 0.18065296E-07 0.19413100E-12 0.33649602E-03 -0.20540863E-09
52 7 -0.11004888E-01 0.10546945E-07 -0.21303752E-01 0.12512956E-03
53 6 0.37174157 0.37425545E-05 0.44335749 -0.43515980E-02
54 5 -4.8625044 0.14213861E-03 -4.2200868 0.59116134E-01
55 4 31.551289 0.11806248E-02 20.574731 -0.40285082
56 3 -108.13650 0.26081321E-02 -53.912227 1.4705586
57 2 194.06739 0.14847903E-02 76.306869 -2.8520668
58 1 -170.03224 0.16027253E-03 -54.802483 2.7257428
59 0 57.057407 0.92345258E-06 15.636386  
60 9 0.11726792E-14 0.46876770E-16 -0.12664795E-09 -0.40425794E-17
61 8 0.18621286E-07 0.18477046E-12 0.34269676E-03 -0.21173044E-09
62 7 -0.11191167E-01 0.99660246E-08 -0.21572393E-01 0.12724763E-03
63 6 0.37680492 0.35261678E-05 0.44770143 -0.44112820E-02
64 5 -4.9119389 0.13358806E-03 -4.2535898 0.59729078E-01
65 4 31.770087 0.11071467E-02 20.706000 -0.40575564
66 3 -108.60241 0.24410452E-02 -54.171883 1.4772891
67 2 194.52961 0.13872791E-02 76.544434 -2.8594062
68 1 -170.20315 0.14950961E-03 -54.870487 2.7287383
69 0 57.057407 0.85997654E-06 15.624277  
70 9 0.98458787E-15 0.55454857E-16 -0.10492535E-09 -0.15601002E-17
71 8 0.15540463E-07 0.23311053E-12 0.30746206E-03 -0.17670042E-09
72 7 -0.10129638E-01 0.13130386E-07 -0.20040359E-01 0.11517765E-03
73 6 0.34794661 0.47273228E-05 0.42286390 -0.40711180E-02
74 5 -4.6301347 0.18177508E-03 -4.0616887 0.56235001E-01
75 4 30.522476 0.15264987E-02 19.953355 -0.38919251
76 3 -105.94476 0.34047073E-02 -52.682811 1.4388992
77 2 191.89184 0.19546755E-02 75.183526 -2.8175246
78 1 -169.22736 0.21263380E-03 -54.483619 2.7116363
79 0 57.057407 0.12355163E-05 15.695393  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.4644_SHGC_EAST_0.25 35 1 VerySmooth 2.640 2.640 1.000 0.251    
2 WINDOW_U_0.4644_SHGC_SOUTH_0.25 36 1 VerySmooth 2.640 2.640 1.000 0.251    
3 WINDOW_U_0.4644_SHGC_WEST_0.25 37 1 VerySmooth 2.640 2.640 1.000 0.251    
4 WINDOW_U_0.4644_SHGC_NORTH_0.25 38 1 VerySmooth 2.640 2.640 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.496 7.5104E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8576E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8588E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0627E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0636E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1965E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1972E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2452E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8841E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9574E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0842E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.1455E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2138E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2647E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2574E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2891E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.9514E-002
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.5821E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.9420E-002
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.9097E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.1838E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.3924E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6042E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.1095E-003
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8923E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9988E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0932E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.1909E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2216E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2944E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2577E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2900E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8576E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8591E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0626E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0639E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1965E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1974E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2451E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9893E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.1535E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9090E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0865E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6660E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7416E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1302E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1521E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.6649E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.7784E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.5899E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.6705E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.6669E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.5111E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6787E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 9.9865E-003
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9489E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0027E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.8579E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.8975E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6437E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.6612E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1303E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1525E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2519E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2531E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0708E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0718E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.5534E-004
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.5613E-004
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2452E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2802E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3489E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0943E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1498E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.7508E-004
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0180E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2577E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2900E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9763E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1285E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5382E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 8.6054E-003
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5549E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 6.1673E-003
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6042E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.1067E-003
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2777E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3470E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0909E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1437E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.6906E-004
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.9954E-004
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2574E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2891E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2518E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2530E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0707E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0716E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.5522E-004
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.5579E-004
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2451E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3645E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4222E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1390E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1805E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1397E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1547E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1303E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1525E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.5180E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.3326E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1920E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.1281E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6222E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.1005E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6787E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 9.9865E-003
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3925E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4998E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1750E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.2820E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1598E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.2218E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1302E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1521E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.0715E-002
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.7955E-002
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.9227E-002
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.2135E-002
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 6.5812E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.3388E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.0133E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.4574E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.1810E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.4404E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.0992E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.3184E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.1418E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.1001E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.0820E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.4729E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.3737E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.6608E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8955E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.3196E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.9079E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.0403E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.0133E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.4571E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.9382E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.8591E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.5823E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.6090E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.0182E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.5792E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.0820E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.4729E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.0678E-002
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.8033E-002
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.9195E-002
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.2230E-002
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 6.5838E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.3458E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.0168E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.4602E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.1798E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.4428E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.0990E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.3211E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.1435E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.1038E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.0854E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.4757E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.3708E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.6614E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8936E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.3202E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.9089E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.0418E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.0168E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.4599E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.9362E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.8605E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.5810E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.6103E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.0194E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.5817E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.0854E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.4757E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 78267.83568 78267.83568 5.84563 5.84563 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -6.30000 2.29779E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 82357.66466 82357.66466 6.15075 6.15075 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 -6.30000 2.29779E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 777519.50276 777519.50276 58.05404 58.05404 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 280293.32590 280293.32590 12.26174 12.26174 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 76821.34944 76821.34944 5.73574 5.73574 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 61327.70771 61327.70771 2.70325 2.70325 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 13166.73446 13166.73446 0.99226 0.99226 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40000 1.44733E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 9731.54397 9731.54397 0.42947 0.42947 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 12685.03860 12685.03860 0.95596 0.95596 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 30.52083 1.44662E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 6698.01016 6698.01016 0.29567 0.29567 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 15087.87876 15087.87876 1.13704 1.13704 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 34.32083 1.44731E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 10973.99237 10973.99237 0.48449 0.48449 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 16342.64323 16342.64323 1.23159 1.23159 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.91167 1.44705E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 5110.99486 5110.99486 0.22530 0.22530 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 123533.85594 123533.85594 9.31020 9.31020 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40000 1.44733E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 164701.69641 164701.69641 7.28144 7.28144 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 130070.93264 130070.93264 9.80282 9.80282 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 30.79000 1.44667E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 108056.77091 108056.77091 4.77739 4.77739 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 142434.17322 142434.17322 10.73462 10.73462 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 34.40000 1.44733E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 162853.90780 162853.90780 7.19951 7.19951 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 137570.30299 137570.30299 10.36800 10.36800 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 32.75333 1.44703E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 104334.41755 104334.41755 4.61240 4.61240 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 14121.36146 14121.36146 1.06429 1.06429 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 34.11500 1.44727E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 21257.23883 21257.23883 0.94033 0.94033 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 13341.08105 13341.08105 1.00548 1.00548 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 31.26500 1.44675E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 13888.28767 13888.28767 0.61437 0.61437 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 15916.50222 15916.50222 1.19958 1.19958 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 34.40000 1.44733E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 21039.16912 21039.16912 0.93066 0.93066 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 14946.50153 14946.50153 1.12647 1.12647 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 32.75333 1.44703E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 13655.49406 13655.49406 0.60406 0.60406 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8223.53460 8223.53460 0.48874 0.48874 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 24.96333 1.44561E-002 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:20:00 -6.30000 2.29779E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 78191.32816 78191.32816 4.64701 4.64701 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 24.96333 1.44561E-002 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -6.30000 2.29779E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7906.68061 7906.68061 0.46996 0.46996 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 30.69500 1.44665E-002 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -6.30000 2.29779E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 371765.91078 371765.91078 22.09665 22.09665 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 25.75500 1.44575E-002 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 11:20:00 -6.30000 2.29779E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 151251.17 9.70708 9.70708 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 55990.24 2.51276 2.51276 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1390568.76 90.42532 90.42532 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 564677.14 36.13248 36.13248 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:30:00
5 VAV_TOP WITH REHEAT Cooling Sensible 156248.21 9.65551 9.65551 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 56437.02 5.79267 5.79267 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 22:20:00
7 CAV_BAS Cooling Sensible 81661.53 5.84563 5.84563 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 64825.70 1.20016 1.20016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 368437.54 22.09688 22.09688 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 18278.08 0.33839 0.33839 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8090.26 0.48874 0.48874 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 844.37 1.56323E-002 1.56323E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 77007.88 4.64701 4.64701 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 8443.71 0.15632 0.15632 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 7851.83 0.46996 0.46996 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 844.37 1.56323E-002 1.56323E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.84563
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.15075
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30924
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31500
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.93749
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.82463
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.23206E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.64545E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.93749
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18808.46857
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.64545E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 379.16396
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 58.05404
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32763
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32700
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 18.98367
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.87369
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.16289E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.06435E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 18.98367
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 464580.38504
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.06435E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 11044.24280
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.73574
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33161
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33700
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.93294
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.88430
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.14893E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.66100E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.70325
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 87569.97557
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.66100E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2311.76452
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.99226
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24068
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.29768
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.64182
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.58300E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.21557E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.42947
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13894.74067
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.21557E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 366.59553
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.95596
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16100
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.28679
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.42932
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.36652E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.36744E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.29567
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9564.50200
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.36744E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 252.33184
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.13704
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21004
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.34111
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.56011
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.81393E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.37105E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.48449
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15671.90154
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.37105E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 413.44606
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.23159
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12496
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.36948
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33324
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.04887E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.60244E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.36948
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8690.05454
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.60244E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 204.17281
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.31020
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25651
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.79306
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.68404
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.48529E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.05841E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.28144
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 235288.57361
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.05841E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6204.29450
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.80282
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15700
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.94085
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.41867
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.42674E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.35048E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.77739
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 154368.28094
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.35048E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4070.44775
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.73462
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22248
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.22038
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.59329
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.71250E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.03529E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.19951
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 232645.67414
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.03529E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6134.65769
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.36800
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14844
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.11040
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39585
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.56665E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.30391E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.61240
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 149044.55852
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.30391E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3930.15904
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.06429
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22440
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.31929
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.59839
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.69790E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.65715E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.94033
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 30372.89293
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.65715E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 800.74996
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.00548
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15307
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.30164
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40818
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.48911E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.73603E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.61437
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19843.92747
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.73603E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 523.15857
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.19958
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19909
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.35987
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53091
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.91369E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.62987E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.93066
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 30061.01215
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.62987E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 792.53230
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.12647
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13663
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.33794
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36434
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.78863E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.70691E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.60406
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19511.03770
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.70691E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 514.38551
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.48874
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.64701
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.46996
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 22.09665
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.23380
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.23254
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.46760
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.23254
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.70708
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.70708
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.33301
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 49.13484
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 31.04836
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 98.26968
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 36.13248
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 90.42532
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 90.42532
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.39958
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.06577
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.25169
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.13154
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 5.79267
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.65551
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.65551
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.59993
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.84563
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.84563
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.84563
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.84563
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.84563
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.84563
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 22.09665
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 22.09665
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 22.09665
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 22.09665
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 22.09688
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 22.09688
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.48874
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.48874
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.48874
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.48874
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.48874
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.48874
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.64701
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.64701
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.64701
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.64701
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.64701
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.64701
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.46996
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.46996
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.46996
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.46996
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.46996
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.46996
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.70708
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 90.42532
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.65551
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.84563
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 22.09688
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.48874
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.64701
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.46996
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.70708
289 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.53819
290 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.86207
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.98272
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.04314E-002
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 238172.21058
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.01324E-002
298 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.70708
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 56929.08838
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.98040E-004
301 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 933.49856
302 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.70708
303 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.01324E-002
304 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.69968E-005
305 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.98040E-004
306 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 90.42532
307 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 25.38195
308 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 25.38195
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.18436
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.88033
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.06792E-002
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2330680.07421
315 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.91525E-002
316 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 90.42532
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 552647.73889
318 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.83480E-003
319 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 9026.32914
320 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 90.42532
321 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.91525E-002
322 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.80261E-006
323 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.83480E-003
324 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.65551
325 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.53819
326 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.74767
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.98267
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.04165E-002
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
332 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 235167.98005
333 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.00046E-002
334 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.65551
335 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 53128.59326
336 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.64792E-004
337 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 876.28614
338 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.65551
339 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.00046E-002
340 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.75972E-005
341 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.64792E-004
342 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.84563
343 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 25.83494
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.37342
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.02027E-002
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
349 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 129625.69596
350 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.51458E-003
351 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.84563
352 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 281605.14914
353 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.46360E-003
354 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 6249.43800
355 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.84563
356 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.51458E-003
357 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 8.63512E-005
358 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.46360E-003
359 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 22.09688
360 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
361 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 22.09688
362 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 437646.58193
363 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 303283.70780
364 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.07179E-002
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 22.09688
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 22.09688
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 22.09688
368 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 22.09688
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 437646.58193
370 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 437646.58193
371 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 18278.07505
372 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
373 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 22.09688
374 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 22.09688
375 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 437646.58193
376 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.07179E-002
377 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 18278.07505
378 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.53127E-004
379 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
380 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
381 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
382 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.48874
383 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.48874
385 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9630.21888
386 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6683.15852
387 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.35843E-004
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.48874
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.48874
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.48874
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.48874
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9630.21888
393 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9630.21888
394 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 844.37135
395 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
396 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.48874
397 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.48874
398 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9630.21888
399 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.35843E-004
400 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 844.37135
401 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.64701
402 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
403 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.64701
404 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 91737.04096
405 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 63598.28180
406 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.24663E-003
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.64701
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.64701
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.64701
410 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.64701
411 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 91737.04096
412 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 91737.04096
413 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 8443.71345
414 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
415 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.64701
416 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.64701
417 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 91737.04096
418 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.24663E-003
419 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 8443.71345
420 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.46996
421 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
422 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.46996
423 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9272.38281
424 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6430.23126
425 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.27080E-004
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.46996
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.46996
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.46996
429 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.46996
430 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9272.38281
431 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9272.38281
432 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 844.37135
433 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
434 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.46996
435 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.46996
436 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9272.38281
437 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.27080E-004
438 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 844.37135
439 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.12480
440 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 25717.49539
441 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.12480
442 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 14.97649
443 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.12480
444 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.12480
445 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 523865.35014
446 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
447 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.12957E-002
448 PlantLoop HEATSYS1 Plant Loop Volume [m3] 2.55548
449 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.12957E-002
450 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 6413.32236
451 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
452 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 2434226.55506
453 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 2434226.56000
454 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.12957E-002
455 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.12480
456 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 14.97649
457 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 0.12480
458 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 17805.08957
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12480
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.27350E-002
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1478271.96164
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1485342.51500
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 7.35041E-002
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12480
465 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.27350E-002
466 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1478271.96164
467 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1485342.51500
468 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 7.35041E-002
469 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.34275E-002
470 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.61130
471 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.34275E-002
472 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3424.68253
473 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.34275E-002
474 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
475 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 58751.95628
476 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
477 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
478 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21362.97914
479 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 553097.65271
480 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 542182.77000
481 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.34275E-002
482 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
483 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
484 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
485 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 5.95776
486 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
487 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.14701
488 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 17.64098
489 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.14701
490 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 44275.66798
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 58.92701
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1762320.85944
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 11.78540
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 220290.10743
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 58.92701
496 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1762320.85944
497 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 11.78540
498 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 220290.10743
499 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.63475E-002
500 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.63475E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 17834.59
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 440151.45
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 82987.54
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 13166.22
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 9062.92
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 14849.95
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 8233.51
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 222928.56
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 146258.65
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 220424.85
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 141215.20
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 28776.36
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 18800.80
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 28480.91
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 18485.43
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 43485.11
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 418709.39
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 41073.87
19 Coil:Heating:Water CAV_BAS HEATING COIL 222338.86


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 258538.62 172079.06 86459.56 0.67 27464.34 278.56
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2461534.97 1627653.39 833881.58 0.66 263452.38 2672.08
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 256499.98 170866.23 85633.75 0.67 27254.69 276.43
4 Coil:Cooling:Water CAV_BAS COOLING COIL 148012.76 100023.06 47989.70 0.68 15428.15 156.48


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.2476158841 0.2246361978 Pass Pass 0.9996910148 2.3362964398 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 1.8907695253E-003 1.8975309608E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 2.4517077310E-003 2.5332331099E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 2.7421685817E-002 3.6212529428E-002 Pass Pass 0.1110396668 0.3121997257 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.2104420815E-002 2.3121226802E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 2.2337211346E-002 2.3532330931E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 2.2110814238E-002 2.2482894990E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 2.2450234346E-002 2.3191308731E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 2.7466980893E-002 2.7648782144E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 2.8181422856E-002 2.8292352948E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 2.8572353946E-002 2.9109777498E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 2.8774464231E-002 2.8905650819E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 7.4589934703E-002 0.1249518912 Pass Pass 3.0033600093 16.2335056278 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 7.3670046008E-002 0.1214861940 Pass Pass 2.5209282543 13.6582599400 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 6.5991386160E-002 0.1015442306 Pass Pass 2.3854081433 12.7332289348 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 3.6047352817E-002 3.9347962092E-002 Pass Pass 4.2808966907 26.9828103503 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.7248577132E-003 4.0701018397E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 5.1325833253E-003 6.3854251476E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 4.7348637098E-002 4.6035129239E-002 Pass Pass 0.1112134531 0.3072055742 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 5.2541744812E-006 7.2063473840E-006 Pass Pass 1.8977196386E-003 1.3434863801E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 8.3356434474E-004 2.2725670083E-003 Pass Pass 1.0451178780E-002 8.7707779352E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 1.4979224501E-002 1.0646683131E-002 Pass Pass 2.3873808932E-003 3.0560659530E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 7.2246526621E-006 9.9272645880E-006 Pass Pass 3.4408218018E-005 1.0830441649E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 5637.03 110.21 0.00 12119.85 25718.57 43585.63



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB -6.30 0.00 -6.30 Wetbulb [C] 5.30 320.00
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 34.40 9.50 23.50 Wetbulb [C] 4.00 300.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 90.00 25      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.168 1.416 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.168 1.416 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.168 1.416 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.168 1.416 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.221 0.228 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.4644_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.4644_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.4644_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.4644_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.4644_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.4644_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.4644_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 869.21 2.640 0.251 0.251             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.4644_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 579.48 2.640 0.251 0.251             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.4644_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 869.21 2.640 0.251 0.251             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.4644_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 579.48 2.640 0.251 0.251             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.4644_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 86.92 2.640 0.251 0.251             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.4644_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 57.95 2.640 0.251 0.251             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.4644_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 86.92 2.640 0.251 0.251             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.4644_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 57.95 2.640 0.251 0.251             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 2.640 0.251 0.251                      
North Total or Average             1043.06 2.640 0.251 0.251                      
Non-North Total or Average             2433.80 2.640 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.3279 2779.43 25926.33 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 240.45
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 9.3279 2496.12 23283.67 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 215.94
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 9.3279 24961.20 232836.67 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 2159.39
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 9.3279 2496.12 23283.67 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 215.94
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 9.3279 313.41 2923.50 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.36 0.0000 Y 18.86
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.09 0.0000 Y 12.06
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 9.3279 313.42 2923.56 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.88 0.0000 Y 18.59
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.25 0.0000 Y 12.11
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 9.3279 3134.13 29234.97 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.41 0.0000 Y 188.81
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 9.3279 2019.75 18840.12 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.11 0.0000 Y 120.63
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 9.3279 3134.20 29235.61 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.91 0.0000 Y 186.12
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 9.3279 2019.75 18840.12 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.26 0.0000 Y 121.17
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 9.3279 313.41 2923.50 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.41 0.0000 Y 18.88
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.11 0.0000 Y 12.06
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 9.3279 313.42 2923.56 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.92 0.0000 Y 18.61
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.26 0.0000 Y 12.12
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 9.3279 783.68 7310.12 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 67.80
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 16.0861 36.20 582.36 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 5.97
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 16.0861 362.03 5823.61 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 59.65
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 16.0861 36.20 582.36 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 5.97
Interior Lighting Total       9.3913 46320.38 435009.77               1158.93


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.56 1127.62
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.56 0.00
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.50 1127.59
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.50 0.00
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.56 1127.62
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.56 0.00
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.50 1127.59
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.50 0.00
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.56 1127.62
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.56 0.00
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.50 1127.59
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.50 0.00
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 9973.01 AstronomicalClock -   41.77 41.77 78.20
EXTERIOR_LIGHTS_B 44362.79 AstronomicalClock -   83.77 71.17 592.67
Exterior Lighting Total 54335.80           670.87



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2926899.44          
HEATSYS1 BOILER Boiler:HotWater 2434226.56 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1485342.51 6.28 1421657.46 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1485342.51 6.28 1421657.46 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 542182.77 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1762320.86          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1762320.86          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 238172.21 258538.62 172079.06 86459.56 0.67 - 27464.34 278.56
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2330680.07 2461534.97 1627653.39 833881.58 0.66 - 263452.38 2672.08
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 235167.98 256499.98 170866.23 85633.75 0.67 - 27254.69 276.43
CAV_BAS COOLING COIL Coil:Cooling:Water 129625.70 148012.76 100023.06 47989.70 0.68 - 15428.15 156.48
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   437646.58 303283.71 134362.87 0.69 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9630.22 6683.16 2947.06 0.69 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   91737.04 63598.28 28138.76 0.69 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9272.38 6430.23 2842.15 0.69 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 18808.47 17834.59 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 464580.39 440151.45 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 87569.98 82987.54 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 13894.74 13166.22 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 9564.50 9062.92 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 15671.90 14849.95 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 8690.05 8233.51 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 235288.57 222928.56 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 154368.28 146258.65 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 232645.67 220424.85 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 149044.56 141215.20 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 30372.89 28776.36 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 19843.93 18800.80 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 30061.01 28480.91 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 19511.04 18485.43 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 56929.09 43485.11 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 552647.74 418709.39 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 53128.59 41073.87 -
CAV_BAS HEATING COIL Coil:Heating:Water 281605.15 222338.86 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   437646.58 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9630.22 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   91737.04 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9272.38 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   18278.08 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   844.37 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   8443.71 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   844.37 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 9.71 20976.49 2160.95 1.00 1.12 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 90.43 206506.83 2283.73 1.00 1.07 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 9.66 20865.04 2160.95 1.00 1.12 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.85 9912.16 1695.65 1.00 1.16 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 22.10 36443.22 1649.25 1.00 1.14 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.49 547.44 1120.11 1.00 1.62 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.65 5205.15 1120.11 1.00 1.16 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.47 526.41 1120.11 1.00 1.63 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.124804 25717.50 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.021296 6413.32 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.124804 17805.09 142664.32 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013427 3424.68 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 3168.45 0.000440 5.96 13540.37 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.147008 44275.67 301178.23 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.50 0.08



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 78267.84 78267.84 28.16 5.846 5.846 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00895 27.37 0.01446 1.200 0.00
CORE_BOTTOM 82357.66 82357.66 32.99 6.151 6.151 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00888 27.37 0.01446 1.078 0.00
CORE_MID 777519.50 777519.50 311.49 58.054 58.054 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00890 27.37 0.01446 10.778 0.00
CORE_TOP 76821.35 76821.35 30.78 5.736 5.736 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00891 27.37 0.01446 1.078 0.00
PERIMETER_BOT_ZN_3 13166.73 13166.73 42.01 0.992 0.992 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00891 34.40 0.01447 0.135 0.00
PERIMETER_BOT_ZN_2 12685.04 12685.04 62.80 0.956 0.956 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 24.00 24.00 0.00878 30.52 0.01447 0.087 0.00
PERIMETER_BOT_ZN_1 15087.88 15087.88 48.14 1.137 1.137 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 24.00 0.00886 34.32 0.01447 0.135 0.00
PERIMETER_BOT_ZN_4 16342.64 16342.64 80.91 1.232 1.232 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00872 32.91 0.01447 0.087 0.00
PERIMETER_MID_ZN_3 123533.86 123533.86 394.16 9.310 9.310 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00911 34.40 0.01447 1.353 0.00
PERIMETER_MID_ZN_2 130070.93 130070.93 643.99 9.803 9.803 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 24.00 24.00 0.00889 30.79 0.01447 0.872 0.00
PERIMETER_MID_ZN_1 142434.17 142434.17 454.45 10.735 10.735 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00903 34.40 0.01447 1.353 0.00
PERIMETER_MID_ZN_4 137570.30 137570.30 681.12 10.368 10.368 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00887 32.75 0.01447 0.872 0.00
PERIMETER_TOP_ZN_3 14121.36 14121.36 45.06 1.064 1.064 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 24.00 24.00 0.00910 34.12 0.01447 0.135 0.00
PERIMETER_TOP_ZN_2 13341.08 13341.08 66.05 1.005 1.005 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 24.00 24.00 0.00892 31.26 0.01447 0.087 0.00
PERIMETER_TOP_ZN_1 15916.50 15916.50 50.78 1.200 1.200 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 24.00 0.00903 34.40 0.01447 0.135 0.00
PERIMETER_TOP_ZN_4 14946.50 14946.50 74.00 1.126 1.126 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00888 32.75 0.01447 0.087 0.00
DATACENTER_BOT_ZN_6 8223.53 8223.53 227.15 0.489 0.489 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 27.00 27.00 0.00850 24.96 0.01446 0.016 0.00
DATACENTER_MID_ZN_6 78191.33 78191.33 2159.82 4.647 4.647 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 27.00 27.00 0.00850 24.96 0.01446 0.156 0.00
DATACENTER_TOP_ZN_6 7906.68 7906.68 218.40 0.470 0.470 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.00 27.00 0.00859 30.70 0.01447 0.016 0.00
DATACENTER_BASEMENT_ZN_6 371765.91 371765.91 474.39 22.097 22.097 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00854 25.75 0.01446 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:30:00 21.00 23.45 0.00230 -6.30 0.00230 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 17.60 21.02 0.00230 -6.30 0.00230 1.078 0.00
CORE_MID 280293.33 280293.33 112.29 12.262 12.262 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -6.30 0.00230 10.778 0.00
CORE_TOP 61327.71 61327.71 24.57 2.703 2.703 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -6.30 0.00230 1.078 0.00
PERIMETER_BOT_ZN_3 9731.54 9731.54 31.05 0.429 0.429 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00736 -6.30 0.00230 0.135 0.00
PERIMETER_BOT_ZN_2 6698.01 6698.01 33.16 0.296 0.296 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00742 -6.30 0.00230 0.087 0.00
PERIMETER_BOT_ZN_1 10973.99 10973.99 35.01 0.484 0.484 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00749 -6.30 0.00230 0.135 0.00
PERIMETER_BOT_ZN_4 5110.99 5110.99 25.31 0.225 0.225 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00701 -6.30 0.00230 0.087 0.00
PERIMETER_MID_ZN_3 164701.70 164701.70 525.51 7.281 7.281 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00741 -6.30 0.00230 1.353 0.00
PERIMETER_MID_ZN_2 108056.77 108056.77 535.00 4.777 4.777 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00740 -6.30 0.00230 0.872 0.00
PERIMETER_MID_ZN_1 162853.91 162853.91 519.60 7.200 7.200 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00741 -6.30 0.00230 1.353 0.00
PERIMETER_MID_ZN_4 104334.42 104334.42 516.57 4.612 4.612 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00738 -6.30 0.00230 0.872 0.00
PERIMETER_TOP_ZN_3 21257.24 21257.24 67.83 0.940 0.940 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00744 -6.30 0.00230 0.135 0.00
PERIMETER_TOP_ZN_2 13888.29 13888.29 68.76 0.614 0.614 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00743 -6.30 0.00230 0.087 0.00
PERIMETER_TOP_ZN_1 21039.17 21039.17 67.13 0.931 0.931 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00744 -6.30 0.00230 0.135 0.00
PERIMETER_TOP_ZN_4 13655.49 13655.49 67.61 0.604 0.604 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00742 -6.30 0.00230 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:20:00 18.00 25.42 0.00797 -6.30 0.00230 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.89 0.00296 -6.30 0.00230 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 21.00 0.00276 -6.30 0.00230 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 11:20:00 18.00 27.00 0.00850 -6.30 0.00230 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 9.71 9.71 2.51 2.51 9.7071 3.2325 9.7071 0.3330 0.3000
VAV_MID WITH REHEAT 90.43 90.43 36.13 36.13 90.4253 36.1325 90.4253 0.3996 0.3000
VAV_TOP WITH REHEAT 9.66 9.66 5.79 5.79 9.6555 5.7927 9.6555 0.5999 0.3000
CAV_BAS 5.85 5.85 1.20 1.20 5.8456 5.8456 5.8456 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 22.10 22.10 0.34 0.34 22.0969 22.0966 22.0969 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.49 0.49 0.02 0.02 0.4887 0.4887 0.4887 1.0000 1.0000
AIRLOOP DATACENTER MID 4.65 4.65 0.16 0.16 4.6470 4.6470 4.6470 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.47 0.47 0.02 0.02 0.4700 0.4700 0.4700 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 18808.469 18808.469 1.937487 0.00016454 379.164 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 18808.47 18808.47 1.937487 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 0.00 0.00 18877.82 18877.82
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 464580.385 464580.385 18.983670 0.00406435 11044.243 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 464580.39 464580.39 18.983670 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 280293.33 0.00 466094.00 466094.00
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 87569.976 87569.976 2.703253 0.00076610 2311.765 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 87569.98 87569.98 2.703253 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 61327.71 0.00 87873.91 87873.91
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 13894.741 13894.741 0.429468 0.00012156 366.596 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13894.74 13894.74 0.429468 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00736137 45.9345 9731.54 0.00 13941.44 13941.44
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 9564.502 9564.502 0.295666 0.00008367 252.332 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 9564.50 9564.50 0.295666 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00741999 46.2957 6698.01 0.00 9596.53 9596.53
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 15671.902 15671.902 0.484494 0.00013710 413.446 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 15671.90 15671.90 0.484494 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00749196 46.7388 10973.99 0.00 15724.30 15724.30
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 8690.055 8690.055 0.369477 0.00007602 204.173 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8690.05 8690.05 0.369477 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00700546 43.7400 5110.99 0.00 8718.54 8718.54
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 235288.574 235288.574 7.281439 0.00205841 6204.295 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 235288.57 235288.57 7.281439 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00741190 46.2477 164701.70 0.00 236054.14 236054.14
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 154368.281 154368.281 4.777390 0.00135048 4070.448 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 154368.28 154368.28 4.777390 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00740474 46.2037 108056.77 0.00 154870.05 154870.05
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 232645.674 232645.674 7.199512 0.00203529 6134.658 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 232645.67 232645.67 7.199512 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00740515 46.2061 162853.91 0.00 233403.03 233403.03
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 149044.559 149044.559 4.612402 0.00130391 3930.159 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 149044.56 149044.56 4.612402 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00738309 46.0703 104334.42 0.00 149529.67 149529.67
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 30372.893 30372.893 0.940328 0.00026572 800.750 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 30372.89 30372.89 0.940328 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00744127 46.4300 21257.24 0.00 30470.64 30470.64
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 19843.927 19843.927 0.614373 0.00017360 523.159 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19843.93 19843.93 0.614373 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00743113 46.3676 13888.29 0.00 19907.75 19907.75
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 30061.012 30061.012 0.930660 0.00026299 792.532 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 30061.01 30061.01 0.930660 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00743593 46.3970 21039.17 0.00 30157.79 30157.79
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 19511.038 19511.038 0.604058 0.00017069 514.386 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19511.04 19511.04 0.604058 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00742233 46.3134 13655.49 0.00 19573.81 19573.81
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 238172.211 -999.000 9.707084 0.01013240 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 238172.21 182474.99 9.707084 26.86 18.54 0.01043139 10.98 10.98 0.00850000 34.40 0.01447326 23.54 26.1478 24.00 0.00889598 46.1452 122343.38 0.00 243868.37 177970.22
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 56929.088 56929.088 2.912125 0.00049804 933.499 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 56929.09 56929.09 2.912125 -3.96 -4.19 0.00266912 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 87.1594 21.02 0.00578879 36.1577 32514.54 0.00 52604.58 52604.58
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2330680.074 -999.000 90.425325 0.09915252 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 2330680.07 1742433.47 90.425325 27.18 18.83 0.01067923 10.88 10.88 0.00850000 34.40 0.01447326 23.54 28.0695 24.00 0.00900397 46.6982 1099566.21 0.00 2385079.72 1701728.33
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 552647.739 552647.739 27.127597 0.00483480 9026.329 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:30:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 552647.74 552647.74 27.127597 -4.66 -4.69 0.00262862 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 93.5650 19.62 0.00715767 48.6357 428469.23 0.00 506498.46 506498.46
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 235167.980 -999.000 9.655506 0.01000459 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 235167.98 180197.09 9.655506 26.75 18.49 0.01041650 10.98 10.98 0.00850000 34.40 0.01447326 23.54 26.2875 24.00 0.00895892 46.4680 127417.81 0.00 240817.44 175700.63
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 53128.593 53128.593 2.896652 0.00046479 876.286 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 53128.59 53128.59 2.896652 -2.92 -3.15 0.00292893 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 87.6250 18.28 0.00735331 54.3330 53426.68 0.00 49692.76 49692.76
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 129625.696 -999.000 5.845627 0.00551458 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 129625.70 100675.05 5.845627 25.83 18.03 0.01020270 11.37 11.18 0.00850000 32.21 0.01446927 22.96 20.5308 24.00 0.00897472 46.5476 77210.39 0.00 132916.33 98424.67
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 281605.149 281605.149 5.845627 0.00246360 6249.438 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 281605.15 281605.15 5.845627 -1.29 -3.23 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 20.5308 23.55 0.00229779 12.3755 0.00 0.00 234864.54 234864.54
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 437646.582 303283.708 22.096884 0.01071794 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 405671.70 398091.82 -999.0 28.56 17.68 0.00863322 12.80 11.77 0.00850000 34.40 0.01447326 23.54 -999.0000 27.00 0.00854228 37.1024 371256.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9630.219 6683.159 0.488735 0.00023584 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 8918.20 8568.11 -999.0 28.10 17.64 0.00877851 12.80 11.77 0.00850000 30.70 0.01446650 22.54 -999.0000 27.00 0.00858881 37.2995 8148.86 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 91737.041 63598.282 4.647012 0.00224663 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 84980.57 81483.57 -999.0 28.10 17.65 0.00879254 12.80 11.77 0.00850000 30.52 0.01446618 22.49 -999.0000 27.00 0.00859341 37.3194 77564.88 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9272.383 6430.231 0.469960 0.00022708 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 8588.71 8241.76 -999.0 28.10 17.65 0.00878701 12.80 11.77 0.00850000 30.70 0.01446650 22.54 -999.0000 27.00 0.00859159 37.3115 7906.68 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 437646.582 437646.582 22.096884 0.01071794 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 437646.58 437646.58 22.096884 -6.30 -6.30 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 1.5314 27.00 0.00850000 36.9155 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9630.219 9630.219 0.488735 0.00023584 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9630.22 9630.22 0.488735 -6.30 -6.30 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.1985 25.97 0.00796565 36.7905 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 91737.041 91737.041 4.647012 0.00224663 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 91737.04 91737.04 4.647012 -6.30 -6.30 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.3640 24.04 0.00295589 15.4409 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9272.383 9272.383 0.469960 0.00022708 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9272.38 9272.38 0.469960 -6.30 -6.30 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.3263 22.90 0.00276448 15.4755 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 18278.075 18278.075 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 18278.08 18278.08 22.096884 -0.10 -0.10 0.00840502 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 1.5314 27.00 0.00850000 36.9155 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 844.371 844.371 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 844.37 844.37 0.488735 -0.20 -0.20 0.00778436 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.1985 25.97 0.00796565 36.7905 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 8443.713 8443.713 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 8443.71 8443.71 4.647012 -0.21 -1.60 0.00293375 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.3640 24.04 0.00295589 15.4409 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 844.371 844.371 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 844.37 844.37 0.469960 -0.21 -1.88 0.00274895 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.3263 22.90 0.00276448 15.4755 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 18808.469 18808.469 1.937487 0.00016454 379.164 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 0.7574 0.772667 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 Sensible 18808.47 18808.47 1.0000 2.24937686 1.937487 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.16452790 60.00 32.22 27.78 0.000 18808.47 -6.30 0.00229779 -6.30 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 49.8624 0.00 0.00 18877.82 18877.82 2.24937686 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 464580.385 464580.385 18.983670 0.00406435 11044.243 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 18.7088 19.085339 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 464580.39 464580.39 1.0000 22.03959590 18.983670 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 4.06393727 60.00 32.22 27.78 0.000 464580.39 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 49.8624 280293.33 0.00 466094.00 466094.00 22.03959590 12.80 11.60 0.00800000 33059.8 33.54 19.19 0.00800000 54207.9
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 87569.976 87569.976 2.703253 0.00076610 2311.765 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 3.5265 3.597446 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 87569.98 87569.98 1.0000 3.13841342 2.703253 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.76602220 60.00 32.22 27.78 0.000 87569.98 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 49.8624 61327.71 0.00 87873.91 87873.91 3.13841342 12.80 11.60 0.00800000 33059.8 40.26 21.26 0.00800000 61059.3
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 13894.741 13894.741 0.429468 0.00012156 366.596 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 0.5595 0.570807 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13894.74 13894.74 1.0000 0.49860241 0.429468 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.12154485 60.00 32.22 27.78 0.000 13894.74 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.91 0.00736137 21.00 0.00736137 45.9345 9731.54 0.00 13941.44 13941.44 0.49860241 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61020.9
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 9564.502 9564.502 0.295666 0.00008367 252.332 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 0.3852 0.392917 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 9564.50 9564.50 1.0000 0.34326168 0.295666 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.08366590 60.00 32.22 27.78 0.000 9564.50 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.91 0.00741999 21.00 0.00741999 46.2957 6698.01 0.00 9596.53 9596.53 0.34326168 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61016.7
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 15671.902 15671.902 0.484494 0.00013710 413.446 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 0.6311 0.643814 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 15671.90 15671.90 1.0000 0.56248638 0.484494 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.13709065 60.00 32.22 27.78 0.000 15671.90 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00749196 21.00 0.00749196 46.7388 10973.99 0.00 15724.30 15724.30 0.56248638 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61014.8
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 8690.055 8690.055 0.369477 0.00007602 204.173 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 0.3500 0.356994 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8690.05 8690.05 1.0000 0.42895442 0.369477 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.07601663 60.00 32.22 27.78 0.000 8690.05 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.91 0.00700546 21.00 0.00700546 43.7400 5110.99 0.00 8718.54 8718.54 0.42895442 12.80 11.60 0.00800000 33059.8 32.73 18.93 0.00800000 53384.9
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 235288.574 235288.574 7.281439 0.00205841 6204.295 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 9.4752 9.665845 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 235288.57 235288.57 1.0000 8.45357959 7.281439 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 2.05819711 60.00 32.22 27.78 0.000 235288.57 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00741190 21.00 0.00741190 46.2477 164701.70 0.00 236054.14 236054.14 8.45357959 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60983.4
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 154368.281 154368.281 4.777390 0.00135048 4070.448 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 6.2165 6.341574 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 154368.28 154368.28 1.0000 5.54643824 4.777390 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 1.35034330 60.00 32.22 27.78 0.000 154368.28 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00740474 21.00 0.00740474 46.2037 108056.77 0.00 154870.05 154870.05 5.54643824 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60982.3
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 232645.674 232645.674 7.199512 0.00203529 6134.658 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 9.3687 9.557273 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 232645.67 232645.67 1.0000 8.35846461 7.199512 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 2.03507823 60.00 32.22 27.78 0.000 232645.67 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00740515 21.00 0.00740515 46.2061 162853.91 0.00 233403.03 233403.03 8.35846461 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60984.0
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 149044.559 149044.559 4.612402 0.00130391 3930.159 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 6.0021 6.122871 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 149044.56 149044.56 1.0000 5.35489070 4.612402 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 1.30377380 60.00 32.22 27.78 0.000 149044.56 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00738309 21.00 0.00738309 46.0703 104334.42 0.00 149529.67 149529.67 5.35489070 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60983.8
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 30372.893 30372.893 0.940328 0.00026572 800.750 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 1.2231 1.247743 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 30372.89 30372.89 1.0000 1.09169879 0.940328 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.26568821 60.00 32.22 27.78 0.000 30372.89 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00744127 21.00 0.00744127 46.4300 21257.24 0.00 30470.64 30470.64 1.09169879 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.0
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 19843.927 19843.927 0.614373 0.00017360 523.159 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 0.7991 0.815205 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19843.93 19843.93 1.0000 0.71327230 0.614373 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.17358562 60.00 32.22 27.78 0.000 19843.93 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00743113 21.00 0.00743113 46.3676 13888.29 0.00 19907.75 19907.75 0.71327230 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60970.3
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 30061.012 30061.012 0.930660 0.00026299 792.532 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 1.2106 1.234931 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 30061.01 30061.01 1.0000 1.08047461 0.930660 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.26296002 60.00 32.22 27.78 0.000 30061.01 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00743593 21.00 0.00743593 46.3970 21039.17 0.00 30157.79 30157.79 1.08047461 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.4
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 19511.038 19511.038 0.604058 0.00017069 514.386 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 0.7857 0.801529 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19511.04 19511.04 1.0000 0.70129752 0.604058 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.17067366 60.00 32.22 27.78 0.000 19511.04 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00742233 21.00 0.00742233 46.3134 13655.49 0.00 19573.81 19573.81 0.70129752 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60970.7
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 238172.211 -999.000 9.707084 0.01013240 -999.000 -999.0000 1.00000 1.00000 1024.2314 1004.8586 1.1610 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.707084 11.26969693   4197.9300 999.8980 124.79134958 12.27 6.67 5.60 2933645.96 8.1186 8.118642 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 238172.21 182474.99 1.0000 11.26969693 9.707084 26.86 18.54 0.01043139 53601.3 10.98 10.98 0.00850000 32467.4 10.13136281 6.67 12.27 5.60 20976.492 217195.72 34.40 0.01447326 23.54 2.53819000 26.1478 24.00 0.00889598 24.00 0.00889598 46.1452 122343.38 0.00 243868.37 177970.22 11.26969693 26.86 18.94 0.01043139 53601.3 11.44 11.14 0.00811304 31962.0
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 56929.088 56929.088 2.912125 0.00049804 933.499 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.707084 11.26969693   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 2.2926 2.338693 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 56929.09 56929.09 1.0000 3.38090908 2.912125 -3.96 -4.19 0.00266912 2679.5 12.80 11.27 0.00800000 33059.8 0.49798969 60.00 32.22 27.78 0.000 56929.09 -6.30 0.00229779 -6.30 2.53819000 87.1594 11.95 0.00518956 21.02 0.00578879 36.1577 32514.54 0.00 52604.58 52604.58 3.38090908 2.80 0.04 0.00266912 9502.7 18.21 8.20 0.00266912 25062.0
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2330680.074 -999.000 90.425325 0.09915252 -999.000 -999.0000 1.00000 1.00000 1024.6922 1004.8586 1.1610 VAV_MID WITH REHEAT FAN Fan:VariableVolume 90.425325 104.98168082   4197.9300 999.8980 124.79134958 12.27 6.67 5.60 2933645.96 79.4465 79.446535 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 2330680.07 1742433.47 1.0000 104.98168082 90.425325 27.18 18.83 0.01067923 54563.7 10.88 10.88 0.00850000 32362.9 99.14240361 6.67 12.27 5.60 206506.829 2124173.25 34.40 0.01447326 23.54 25.38195000 28.0695 24.00 0.00900397 24.00 0.00900397 46.6982 1099566.21 0.00 2385079.72 1701728.33 104.98168082 27.18 19.24 0.01067923 54563.7 11.37 11.09 0.00809832 31844.7
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 552647.739 552647.739 27.127597 0.00483480 9026.329 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 VAV_MID WITH REHEAT FAN Fan:VariableVolume 90.425325 104.98168082   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 22.2553 22.703217 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:30:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 552647.74 552647.74 1.0000 31.49450424 27.127597 -4.66 -4.69 0.00262862 1866.1 12.80 11.27 0.00800000 33059.8 4.83431031 60.00 32.22 27.78 0.000 552647.74 -6.30 0.00229779 -6.30 25.38195000 93.5650 19.15 0.00743893 19.62 0.00715767 48.6357 428469.23 0.00 506498.46 506498.46 31.49450424 2.80 -0.22 0.00262862 9401.3 18.73 8.39 0.00262862 25483.4
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 235167.980 -999.000 9.655506 0.01000459 -999.000 -999.0000 1.00000 1.00000 1024.2038 1004.8586 1.1610 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.655506 11.20981647   4197.9300 999.8980 124.79134958 12.27 6.67 5.60 2933645.96 8.0162 8.016236 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 Sensible 235167.98 180197.09 1.0000 11.20981647 9.655506 26.75 18.49 0.01041650 53446.1 10.98 10.98 0.00850000 32467.4 10.00356894 6.67 12.27 5.60 20865.035 214302.94 34.40 0.01447326 23.54 2.53819000 26.2875 24.00 0.00895892 24.00 0.00895892 46.4680 127417.81 0.00 240817.44 175700.63 11.20981647 26.75 18.89 0.01041650 53446.1 11.44 11.14 0.00811340 31963.4
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 53128.593 53128.593 2.896652 0.00046479 876.286 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.655506 11.20981647   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 2.1395 2.182566 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 53128.59 53128.59 1.0000 3.36294494 2.896652 -2.92 -3.15 0.00292893 4373.2 12.80 11.27 0.00800000 33059.8 0.46474470 60.00 32.22 27.78 0.000 53128.59 -6.30 0.00229779 -6.30 2.53819000 87.6250 21.00 0.00739787 18.28 0.00735331 54.3330 53426.68 0.00 49692.76 49692.76 3.36294494 2.80 0.42 0.00292893 10153.9 17.43 8.13 0.00292893 24930.4
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 129625.696 -999.000 5.845627 0.00551458 -999.000 -999.0000 1.00000 1.00000 1023.8063 1004.8586 1.1610 CAV_BAS FAN Fan:ConstantVolume 5.845627 6.78663585   4197.9300 999.8980 124.79134958 12.27 6.67 5.60 2933645.96 4.4186 4.418587 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 129625.70 100675.05 1.0000 6.78663585 5.845627 25.83 18.03 0.01020270 51966.3 11.37 11.18 0.00850000 32866.2 5.51401422 6.67 12.27 5.60 9912.163 119713.53 32.21 0.01446927 22.96 1.20015641 20.5308 24.00 0.00897472 24.00 0.00897472 46.5476 77210.39 0.00 132916.33 98424.67 6.78663585 25.83 18.42 0.01020270 51966.3 11.67 11.31 0.00818802 32381.3
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 281605.149 281605.149 5.845627 0.00246360 6249.438 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 CAV_BAS FAN Fan:ConstantVolume 5.845627 6.78663585   4197.9300 999.8980 21.29350343 54.44 82.22 27.78 2483216.33 11.3403 11.568568 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 281605.15 281605.15 1.0000 6.78663585 5.845627 -1.29 -3.23 0.00229779 4441.4 40.00 20.76 0.00800000 60796.0 2.46335338 60.00 32.22 27.78 0.000 281605.15 -6.30 0.00229779 -6.30 1.20015641 20.5308 0.00 0.00229779 23.55 0.00229779 12.3755 0.00 0.00 234864.54 234864.54 6.78663585 12.80 5.08 0.00229779 18663.3 47.09 19.05 0.00229779 53270.2
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 437646.582 303283.708 22.096884 0.01071794 -999.000 -999.0000 -999.00000 -999.00000 1020.8887 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 405671.70 398091.82 0.9269 -999.0 -999.0 28.56 17.68 0.00863322 50743.5 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 405671.70 34.40 0.01447326 23.54 0.33839277 -999.0000 27.00 0.00854228 27.00 0.00854228 37.1024 371256.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9630.219 6683.159 0.488735 0.00023584 -999.000 -999.0000 -999.00000 -999.00000 1021.1588 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 Sensible 8918.20 8568.11 0.9261 -999.0 -999.0 28.10 17.64 0.00877851 50648.1 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8918.20 30.70 0.01446650 22.54 0.01563234 -999.0000 27.00 0.00858881 27.00 0.00858881 37.2995 8148.86 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 91737.041 63598.282 4.647012 0.00224663 -999.000 -999.0000 -999.00000 -999.00000 1021.1849 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 Sensible 84980.57 81483.57 0.9263 -999.0 -999.0 28.10 17.65 0.00879254 50684.0 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 84980.57 30.52 0.01446618 22.49 0.15632344 -999.0000 27.00 0.00859341 27.00 0.00859341 37.3194 77564.88 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9272.383 6430.231 0.469960 0.00022708 -999.000 -999.0000 -999.00000 -999.00000 1021.1746 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 8588.71 8241.76 0.9263 -999.0 -999.0 28.10 17.65 0.00878701 50673.5 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8588.71 30.70 0.01446650 22.54 0.01563234 -999.0000 27.00 0.00859159 27.00 0.00859159 37.3115 7906.68 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 437646.582 437646.582 22.096884 0.01071794 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 437646.58 437646.58 1.0000 25.65396409 22.096884 -6.30 -6.30 0.00229779 -610.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 437646.58 -6.30 0.00229779 -6.30 0.33839277 1.5314 0.00 0.00850000 27.00 0.00850000 36.9155 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9630.219 9630.219 0.488735 0.00023584 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9630.22 9630.22 1.0000 0.56741020 0.488735 -6.30 -6.30 0.00229779 -610.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9630.22 -6.30 0.00229779 -6.30 0.01563234 3.1985 0.00 0.00796565 25.97 0.00796565 36.7905 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 91737.041 91737.041 4.647012 0.00224663 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 91737.04 91737.04 1.0000 5.39507149 4.647012 -6.30 -6.30 0.00229779 -610.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 91737.04 -6.30 0.00229779 -6.30 0.15632344 3.3640 0.00 0.00295589 24.04 0.00295589 15.4409 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9272.383 9272.383 0.469960 0.00022708 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9272.38 9272.38 1.0000 0.54561246 0.469960 -6.30 -6.30 0.00229779 -610.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9272.38 -6.30 0.00229779 -6.30 0.01563234 3.3263 0.00 0.00276448 22.90 0.00276448 15.4755 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 18278.075 18278.075 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 22.096884 25.65396409   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 18278.08 18278.08 1.0000 25.65396409 22.096884 -0.10 -0.10 0.00840502 20922.0 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 18278.08 -6.30 0.00229779 -6.30 0.33839277 1.5314 0.00 0.00850000 27.00 0.00850000 36.9155 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 844.371 844.371 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.488735 0.56741020   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 844.37 844.37 1.0000 0.56741020 0.488735 -0.20 -0.20 0.00778436 19262.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 844.37 -6.30 0.00229779 -6.30 0.01563234 3.1985 0.00 0.00796565 25.97 0.00796565 36.7905 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 8443.713 8443.713 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.647012 5.39507149   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 8443.71 8443.71 1.0000 5.39507149 4.647012 -0.21 -1.60 0.00293375 7123.0 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8443.71 -6.30 0.00229779 -6.30 0.15632344 3.3640 0.00 0.00295589 24.04 0.00295589 15.4409 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 844.371 844.371 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.469960 0.54561246   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 844.37 844.37 1.0000 0.54561246 0.469960 -0.21 -1.88 0.00274895 6663.3 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 844.37 -6.30 0.00229779 -6.30 0.01563234 3.3263 0.00 0.00276448 22.90 0.00276448 15.4755 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 2.54 9.71 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 25.38 90.43 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 2.54 9.66 -      
CAV_BAS_OA_CONTROLLER DifferentialEnthalpy 1.20 5.85 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 3686.17 1684.33 1162.33
CORE_BOTTOM 3685.17 656.67 38.50
CORE_MID 3120.67 1837.67 81.50
CORE_TOP 3215.33 2534.17 433.67
PERIMETER_BOT_ZN_3 3119.83 2438.83 271.50
PERIMETER_BOT_ZN_2 2998.33 2600.17 263.83
PERIMETER_BOT_ZN_1 3323.83 1950.00 241.67
PERIMETER_BOT_ZN_4 3776.33 1613.83 312.00
PERIMETER_MID_ZN_3 3371.00 3284.83 1058.00
PERIMETER_MID_ZN_2 2743.17 2794.83 862.33
PERIMETER_MID_ZN_1 3266.83 2531.17 581.17
PERIMETER_MID_ZN_4 3269.17 3064.17 798.50
PERIMETER_TOP_ZN_3 3644.00 3520.00 1538.17
PERIMETER_TOP_ZN_2 3569.17 3373.00 1362.33
PERIMETER_TOP_ZN_1 3437.00 2948.00 984.67
PERIMETER_TOP_ZN_4 3468.50 3343.00 1206.00
DATACENTER_BOT_ZN_6 5939.50 1226.33 1226.33
DATACENTER_MID_ZN_6 5736.67 177.83 162.33
DATACENTER_TOP_ZN_6 5445.17 567.50 397.50
DATACENTER_BASEMENT_ZN_6 5943.00 5723.67 5723.67
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5940.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 68.33 0.00 4.00
CORE_BOTTOM 0.00 2.33 0.00 0.00
CORE_MID 0.00 0.17 0.00 0.17
CORE_TOP 4.50 0.00 0.50 0.00
PERIMETER_BOT_ZN_3 0.00 1.00 0.00 0.33
PERIMETER_BOT_ZN_2 0.00 10.50 0.00 10.50
PERIMETER_BOT_ZN_1 0.33 16.67 0.00 16.17
PERIMETER_BOT_ZN_4 0.00 94.17 0.00 31.83
PERIMETER_MID_ZN_3 17.50 0.33 3.67 0.33
PERIMETER_MID_ZN_2 11.17 15.50 0.33 15.50
PERIMETER_MID_ZN_1 8.67 13.33 0.50 13.33
PERIMETER_MID_ZN_4 9.17 21.50 0.50 11.17
PERIMETER_TOP_ZN_3 96.83 4.17 29.67 2.50
PERIMETER_TOP_ZN_2 55.33 26.17 7.33 24.00
PERIMETER_TOP_ZN_1 41.50 14.50 7.33 12.83
PERIMETER_TOP_ZN_4 35.50 26.17 5.83 13.50
DATACENTER_BOT_ZN_6 0.00 40.67 0.00 40.67
DATACENTER_MID_ZN_6 0.00 45.33 0.00 45.33
DATACENTER_TOP_ZN_6 0.00 40.67 0.00 40.67
DATACENTER_BASEMENT_ZN_6 0.00 475.00 0.00 420.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 102.17 677.33 29.67 501.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.01 149.60 6779.02 1.272 0.000 0.000 0.000
CORE_BOTTOM 55.69 134.35 6849.35 0.995 0.000 0.000 0.000
CORE_MID 55.69 134.35 6849.35 0.829 0.000 0.000 0.000
CORE_TOP 55.69 134.35 6849.35 0.783 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.99 16.87 860.00 0.956 0.043 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 1.313 0.045 0.000 0.000
PERIMETER_BOT_ZN_1 6.99 16.87 860.02 1.274 0.043 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 1.880 0.045 0.000 0.000
PERIMETER_MID_ZN_3 6.99 16.87 860.00 0.872 0.101 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 1.267 0.111 0.000 0.000
PERIMETER_MID_ZN_1 6.99 16.87 860.02 1.193 0.102 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 1.436 0.105 0.000 0.000
PERIMETER_TOP_ZN_3 6.99 16.87 860.00 0.933 0.126 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 1.380 0.130 0.000 0.000
PERIMETER_TOP_ZN_1 6.99 16.87 860.02 1.197 0.126 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 1.491 0.130 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.48 42.18 1911.37 0.481 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.01 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.69 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.69 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.69 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.99 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.99 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.99 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.99 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.99 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.99 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.48 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.01 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.69 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.69 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.69 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.99 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.99 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.99 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.94 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.99 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.99 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.99 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.48 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1027.73 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 53344857.12 0.00 53344857.12 0.00 53344857.12 37848132.68 3941.69 1663.06 3155.26 361.19
CORE_BOTTOM 41759731.82 0.00 41759731.82 0.00 41759731.82 33990283.35 3866.50 4.43 4889.07 328.63
CORE_MID 0.34E+09 0.00 0.34E+09 0.00 0.34E+09 0.34E+09 4157.93 6.49 4595.59 162.56
CORE_TOP 31722538.28 0.00 31722538.28 0.00 31722538.28 33990283.35 4245.48 1.24 4513.28 219.64
PERIMETER_BOT_ZN_3 5078351.26 0.00 5078351.26 439326.30 5517677.56 4267819.30 3850.27 11.54 4898.19 328.63
PERIMETER_BOT_ZN_2 4522936.78 0.00 4522936.78 292884.00 4815820.78 2750345.05 3775.70 2.09 4982.21 328.63
PERIMETER_BOT_ZN_1 6717689.94 0.00 6717689.94 439326.30 7157016.24 4267912.63 3809.34 3.33 4947.33 328.63
PERIMETER_BOT_ZN_4 6439126.76 0.00 6439126.76 292884.00 6732010.76 2750345.05 3760.97 0.00 4999.03 328.63
PERIMETER_MID_ZN_3 44820147.04 0.00 44820147.04 1030333.47 45850480.51 42678193.03 4139.30 2.94 4617.76 162.56
PERIMETER_MID_ZN_2 45203740.75 0.00 45203740.75 686888.51 45890629.26 27503450.52 4053.96 2.17 4703.87 1071.56
PERIMETER_MID_ZN_1 61056002.61 0.00 61056002.61 1030333.47 62086336.08 42679126.28 4110.97 4.01 4645.02 162.56
PERIMETER_MID_ZN_4 47661323.34 0.00 47661323.34 686888.51 48348211.85 27503450.52 4048.40 2.30 4709.30 162.56
PERIMETER_TOP_ZN_3 4768659.37 0.00 4768659.37 1279256.65 6047916.03 4267819.30 4205.84 3.22 4550.94 219.64
PERIMETER_TOP_ZN_2 4542867.72 0.00 4542867.72 852837.19 5395704.91 2750345.05 4152.16 5.36 4602.48 219.64
PERIMETER_TOP_ZN_1 6093203.34 0.00 6093203.34 1279256.65 7372459.99 4267912.63 4195.19 2.24 4562.57 219.64
PERIMETER_TOP_ZN_4 4912340.83 0.00 4912340.83 852837.19 5765178.02 2750345.05 4132.23 1.91 4625.86 219.64
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5288266.81 0.00 5288266.81 0.00 5288266.81 10671554.30 4419.00 4341.00 0.00 0.00
Total Facility 0.56E+10 0.00 0.56E+10 40073047.80 0.56E+10 0.50E+10 4446.87 4385.28 5196.96 1574.51


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.3458 0.0000 2.3458 0.0000 2.3458 1.2002 1372.24 1660.58 2910.18
CORE_BOTTOM 1.8544 0.0000 1.8544 0.0000 1.8544 1.0778 1329.24 2.09 4611.67
CORE_MID 15.4546 0.0000 15.4546 0.0000 15.4546 10.7782 1431.84 5.64 4505.52
CORE_TOP 1.4592 0.0000 1.4592 0.0000 1.4592 1.0778 1471.78 1.18 4470.04
PERIMETER_BOT_ZN_3 0.2238 0.0000 0.2238 0.0102 0.2340 0.1353 1340.98 8.24 4593.78
PERIMETER_BOT_ZN_2 0.1983 0.0000 0.1983 0.0068 0.2051 0.0872 1285.08 1.75 4656.16
PERIMETER_BOT_ZN_1 0.2984 0.0000 0.2984 0.0102 0.3086 0.1353 1311.49 1.33 4630.18
PERIMETER_BOT_ZN_4 0.2837 0.0000 0.2837 0.0068 0.2905 0.0872 1272.60 0.00 4670.40
PERIMETER_MID_ZN_3 2.0449 0.0000 2.0449 0.0239 2.0688 1.3533 1417.72 2.38 4522.90
PERIMETER_MID_ZN_2 1.9169 0.0000 1.9169 0.0169 1.9338 0.8721 1354.93 1.34 3677.73
PERIMETER_MID_ZN_1 2.7966 0.0000 2.7966 0.0239 2.8204 1.3533 1390.34 3.38 4549.28
PERIMETER_MID_ZN_4 2.1723 0.0000 2.1723 0.0159 2.1882 0.8721 1352.67 1.10 4589.23
PERIMETER_TOP_ZN_3 0.2192 0.0000 0.2192 0.0297 0.2488 0.1353 1439.97 1.77 4501.25
PERIMETER_TOP_ZN_2 0.2089 0.0000 0.2089 0.0198 0.2287 0.0872 1404.85 3.93 4534.22
PERIMETER_TOP_ZN_1 0.2807 0.0000 0.2807 0.0297 0.3103 0.1353 1430.48 1.18 4511.35
PERIMETER_TOP_ZN_4 0.2258 0.0000 0.2258 0.0198 0.2455 0.0872 1394.09 1.05 4547.86
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 0.2472 0.0000 0.2472 0.0000 0.2472 0.3384 1602.00 4341.00 0.00
Total Facility 252.8628 0.0000 252.8628 0.9383 253.8011 158.4706 1629.87 4366.48 4712.35


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 86956974.59 0.00 86956974.59 48026705.38 3785.79 2.10 4972.10 328.63
VAV_MID WITH REHEAT 0.72E+09 0.00 0.72E+09 0.48E+09 4087.32 2.58 4670.10 162.56
VAV_TOP WITH REHEAT 70130401.45 0.00 70130401.45 48026705.38 4185.21 3.35 4571.44 219.47
CAV_BAS 71901747.33 0.00 71901747.33 37848132.68 3886.48 2.84 4870.68 361.19
AIRLOOP DATACENTER BASEMENT 7127877.82 0.00 7127877.82 10671554.30 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER BOT 329278.43 0.00 329278.43 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3292784.26 0.00 3292784.26 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 329278.43 0.00 329278.43 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.8528 0.0000 3.8528 1.5229 1291.15 1.74 4650.10
VAV_MID WITH REHEAT 33.0618 0.0000 33.0618 15.2292 1372.71 0.44 4569.85
VAV_TOP WITH REHEAT 3.2258 0.0000 3.2258 1.5229 1425.32 2.21 4515.47
CAV_BAS 3.1618 0.0000 3.1618 1.2002 1356.76 0.84 4585.40
AIRLOOP DATACENTER BASEMENT 0.3332 0.0000 0.3332 0.3384 1602.00 0.00 4341.00
AIRLOOP DATACENTER BOT 0.0154 0.0000 0.0154 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1539 0.0000 0.1539 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0154 0.0000 0.0154 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 2236.10 2762.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 2525.87 2251.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 2719.31 2137.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAV_BAS 0.00 1657.78 3304.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 3.4252 6.2606 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 34.2290 52.7097 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 3.4250 5.1428 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.6184 5.4737 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4562 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0211 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2108 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0211 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1386
Defaulted Fields 1179
Fields with Defaults 3922
Autosized Fields 336
Autosizable Fields 412
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 30490.10 367451.46 08-JAN-10:30 2051130.69 03-AUG-15:50
Electricity:Building 18924.55 251811.03 01-JAN-09:20 1140760.82 06-DEC-08:10
Electricity:Zone:BASEMENT 664.85 14623.97 01-JAN-00:10 34452.17 02-JAN-08:10
Electricity:SpaceType:GENERAL 18924.55 251811.03 01-JAN-09:20 1140760.82 06-DEC-08:10
InteriorLights:Electricity 3711.13 17601.77 01-JAN-09:20 352689.08 30-OCT-07:10
InteriorLights:Electricity:Zone:BASEMENT 240.45 1166.43 01-JAN-00:10 20994.62 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 3711.13 17601.77 01-JAN-09:20 352689.08 30-OCT-07:10
LightsWired:InteriorLights:Electricity 3711.13 17601.77 01-JAN-09:20 352689.08 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 240.45 1166.43 01-JAN-00:10 20994.62 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 3711.13 17601.77 01-JAN-09:20 352689.08 30-OCT-07:10
Electricity:Zone:CORE_BOTTOM 537.23 7090.40 01-JAN-00:10 36983.24 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
Electricity:Zone:CORE_MID 5372.24 70903.72 01-JAN-00:10 369831.68 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2159.40 10475.32 01-JAN-00:10 188546.48 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 2159.40 10475.32 01-JAN-00:10 188546.48 02-JAN-08:10
Electricity:Zone:CORE_TOP 537.22 7090.37 01-JAN-00:10 36983.17 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 59.20 839.57 01-JAN-09:10 4639.46 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 18.86 80.80 01-JAN-09:10 2363.15 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 18.86 80.80 01-JAN-09:10 2363.15 30-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_2 38.06 541.05 01-JAN-08:50 2989.85 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 12.06 52.07 01-JAN-08:50 1522.90 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 12.06 52.07 01-JAN-08:50 1522.90 30-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_1 58.94 839.58 01-JAN-08:50 4639.55 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 18.59 80.80 01-JAN-08:50 2363.20 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 18.59 80.80 01-JAN-08:50 2363.20 30-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_4 38.11 541.05 01-JAN-09:20 2989.84 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 12.11 52.07 01-JAN-09:20 1522.90 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 12.11 52.07 01-JAN-09:20 1522.90 30-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_3 592.24 8395.70 01-JAN-09:10 46395.89 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 188.81 807.98 01-JAN-09:10 23632.71 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 188.81 807.98 01-JAN-09:10 23632.71 30-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_2 380.61 5410.51 01-JAN-08:50 29898.67 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 120.63 520.69 01-JAN-08:50 15229.21 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 120.63 520.69 01-JAN-08:50 15229.21 30-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_1 589.55 8395.84 01-JAN-08:50 46396.76 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 186.12 807.99 01-JAN-08:50 23633.23 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 186.12 807.99 01-JAN-08:50 23633.23 30-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_4 381.15 5410.48 01-JAN-09:20 29898.58 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 121.17 520.69 01-JAN-09:20 15229.21 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 121.17 520.69 01-JAN-09:20 15229.21 30-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_3 59.22 839.57 01-JAN-09:10 4639.58 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 18.88 80.80 01-JAN-09:10 2363.27 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 18.88 80.80 01-JAN-09:10 2363.27 30-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_2 38.06 541.05 01-JAN-08:50 2989.86 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 12.06 52.07 01-JAN-08:50 1522.92 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 12.06 52.07 01-JAN-08:50 1522.92 30-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_1 58.96 839.58 01-JAN-08:50 4639.67 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 18.61 80.80 01-JAN-08:50 2363.32 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 18.61 80.80 01-JAN-08:50 2363.32 30-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_4 38.12 541.05 01-JAN-09:20 2989.85 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 12.12 52.07 01-JAN-09:20 1522.92 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 12.12 52.07 01-JAN-09:20 1522.92 30-OCT-07:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7562.65 95237.01 01-JAN-00:10 385552.11 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 67.80 328.88 01-JAN-00:10 5919.59 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 67.80 328.88 01-JAN-00:10 5919.59 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 159.85 1977.54 01-JAN-00:10 8315.27 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1598.46 19775.43 01-JAN-00:10 83152.69 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 59.65 289.38 01-JAN-00:10 5208.47 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 59.65 289.38 01-JAN-00:10 5208.47 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 159.85 1977.54 01-JAN-00:10 8315.27 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
InteriorEquipment:Electricity 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 3640.67 5992.31 07-JAN-17:10 448738.32 21-AUG-10:50
HeatRejection:Electricity 1454.27 2326.74 14-JAN-08:00 92421.41 29-MAR-15:50
General:HeatRejection:Electricity 1454.27 2326.74 14-JAN-08:00 92421.41 29-MAR-15:50
Electricity:HVAC 5399.41 75169.68 08-JAN-23:10 450902.24 13-APR-14:50
ExteriorEquipment:Electricity 1941.94 28795.69 01-JAN-00:10 118959.08 30-OCT-07:20
Transformer:ExteriorEquipment:Electricity 87.33 1613.62 01-JAN-00:10 5481.12 30-OCT-07:20
ElectricityPurchased:Facility 30490.10 367451.46 08-JAN-10:30 2051130.69 03-AUG-15:50
ElectricityPurchased:Plant 30490.10 367451.46 08-JAN-10:30 2051130.69 03-AUG-15:50
Cogeneration:ElectricityPurchased 30490.10 367451.46 08-JAN-10:30 2051130.69 03-AUG-15:50
General:Cogeneration:ElectricityPurchased 30490.10 367451.46 08-JAN-10:30 2051130.69 03-AUG-15:50
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 30490.10 367451.46 08-JAN-10:30 2051130.69 03-AUG-15:50
ElectricityNet:Plant 30490.10 367451.46 08-JAN-10:30 2051130.69 03-AUG-15:50
Cogeneration:ElectricityNet 30490.10 367451.46 08-JAN-10:30 2051130.69 03-AUG-15:50
General:Cogeneration:ElectricityNet 30490.10 367451.46 08-JAN-10:30 2051130.69 03-AUG-15:50
Fans:Electricity 2525.85 42722.22 12-JAN-02:00 287700.46 02-JUN-13:40
General:Fans:Electricity 2525.85 42722.22 12-JAN-02:00 287700.46 02-JUN-13:40
ExteriorLights:Electricity 670.87 0.00 01-JAN-07:50 54335.80 01-JAN-06:10
General:ExteriorLights:Electricity 670.87 0.00 01-JAN-07:50 54335.80 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
HeatRecovery:Electricity 50.38 0.00 01-JAN-00:10 5613.48 02-JAN-07:10
General:HeatRecovery:Electricity 50.38 0.00 01-JAN-00:10 5613.48 02-JAN-07:10
Cooling:Electricity 4111.57 28117.05 09-JAN-07:10 456189.80 17-AUG-13:10
General:Cooling:Electricity 4111.57 28117.05 09-JAN-07:10 456189.80 17-AUG-13:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 8.95 0.00 01-JAN-00:10 5867.99 05-JAN-18:10
General:Humidifier:Electricity 8.95 0.00 01-JAN-00:10 5867.99 05-JAN-18:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 801.73 3424.68 01-JAN-01:40 73998.79 17-APR-14:20
General:Pumps:Electricity 801.73 3424.68 01-JAN-01:40 73998.79 17-APR-14:20
WIRED_LTG_ELECTRICITY 104.28 0.00 01-JAN-00:10 9910.56 30-OCT-07:20
WIRED_INT_EQUIP 5871.99 115917.86 04-MAR-00:10 320838.49 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 1298.37 5695.87 13-AUG-16:20 1599222.50 13-FEB-07:10
NaturalGas:Plant 1298.37 5695.87 13-AUG-16:20 1599222.50 13-FEB-07:10
Heating:NaturalGas 640.67 0.00 01-JAN-00:10 1589015.49 13-FEB-07:10
Boiler:Heating:NaturalGas 640.67 0.00 01-JAN-00:10 1589015.49 13-FEB-07:10
WaterSystems:NaturalGas 657.71 5695.87 06-JAN-05:20 79691.14 26-JAN-12:50
Water Heater:WaterSystems:NaturalGas 657.71 5695.87 06-JAN-05:20 79691.14 26-JAN-12:50


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 22373.89 138568.20 09-JAN-07:10 2625822.64 21-AUG-10:50
PlantLoopCoolingDemand:HVAC 22373.89 138568.20 09-JAN-07:10 2625822.64 21-AUG-10:50
CoolingCoils:PlantLoopCoolingDemand 22373.89 138568.20 09-JAN-07:10 2625822.64 21-AUG-10:50


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 10009.48 0.00 01-JAN-00:10 0.00 14-APR-16:00
Water:HVAC 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
Humidifier:Water 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
General:Humidifier:Water 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
MainsWater:Facility 10009.48 0.00 01-JAN-00:10 0.00 14-APR-16:00
MainsWater:HVAC 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
Humidifier:MainsWater 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
General:Humidifier:MainsWater 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
Water:Plant 10006.15 0.00 01-JAN-00:10 0.00 14-APR-16:00
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 10006.15 0.00 01-JAN-00:10 0.00 14-APR-16:00
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 7725.98 0.00 01-JAN-00:10 0.00 13-APR-14:50
General:HeatRejection:Water 7725.98 0.00 01-JAN-00:10 0.00 13-APR-14:50
HeatRejection:MainsWater 7725.98 0.00 01-JAN-00:10 0.00 13-APR-14:50
General:HeatRejection:MainsWater 7725.98 0.00 01-JAN-00:10 0.00 13-APR-14:50


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 72320.71 213874.70 09-JAN-01:50 10169515.45 10-AUG-16:00
EnergyTransfer:Building 19756.12 88034.12 14-JAN-20:20 1610772.61 02-AUG-15:40
EnergyTransfer:Zone:BASEMENT 695.85 0.00 01-JAN-00:10 71799.17 13-NOV-06:10
Heating:EnergyTransfer 249.34 0.00 13-JAN-22:10 753054.04 13-FEB-06:10
Heating:EnergyTransfer:Zone:BASEMENT 4.14 0.00 01-JAN-00:10 23770.39 08-JUL-16:10
General:Heating:EnergyTransfer 249.34 0.00 13-JAN-22:10 753054.04 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 4.14 0.00 01-JAN-00:10 23770.39 08-JUL-16:10
Cooling:EnergyTransfer 19506.78 85563.31 09-JAN-01:50 1610772.61 02-AUG-15:40
Cooling:EnergyTransfer:Zone:BASEMENT 691.71 0.00 01-JAN-00:10 71799.17 13-NOV-06:10
General:Cooling:EnergyTransfer 19506.78 85563.31 09-JAN-01:50 1610772.61 02-AUG-15:40
General:Cooling:EnergyTransfer:Zone:BASEMENT 691.71 0.00 01-JAN-00:10 71799.17 13-NOV-06:10
EnergyTransfer:Zone:CORE_BOTTOM 681.25 0.00 01-JAN-00:10 55140.84 07-AUG-13:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 681.25 0.00 01-JAN-00:10 55140.84 07-AUG-13:10
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 681.25 0.00 01-JAN-00:10 55140.84 07-AUG-13:10
EnergyTransfer:Zone:CORE_MID 5011.82 0.00 01-JAN-00:10 501549.49 15-MAY-14:10
Heating:EnergyTransfer:Zone:CORE_MID 0.76 0.00 01-JAN-00:10 158750.90 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.76 0.00 01-JAN-00:10 158750.90 09-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_MID 5011.06 0.00 01-JAN-00:10 501549.49 15-MAY-14:10
General:Cooling:EnergyTransfer:Zone:CORE_MID 5011.06 0.00 01-JAN-00:10 501549.49 15-MAY-14:10
EnergyTransfer:Zone:CORE_TOP 474.43 0.00 01-JAN-00:10 66159.74 13-FEB-05:10
Heating:EnergyTransfer:Zone:CORE_TOP 5.18 0.00 01-JAN-00:10 66159.74 13-FEB-05:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 5.18 0.00 01-JAN-00:10 66159.74 13-FEB-05:10
Cooling:EnergyTransfer:Zone:CORE_TOP 469.25 0.00 01-JAN-00:10 52770.66 25-AUG-13:50
General:Cooling:EnergyTransfer:Zone:CORE_TOP 469.25 0.00 01-JAN-00:10 52770.66 25-AUG-13:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 85.36 0.00 01-JAN-00:10 10293.76 09-AUG-14:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.21 0.00 01-JAN-00:10 4654.19 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.21 0.00 01-JAN-00:10 4654.19 13-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 85.15 0.00 01-JAN-00:10 10293.76 09-AUG-14:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 85.15 0.00 01-JAN-00:10 10293.76 09-AUG-14:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 72.02 0.00 01-JAN-00:10 10619.81 07-JUL-09:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.16 0.00 01-JAN-00:10 3125.84 14-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.16 0.00 01-JAN-00:10 3125.84 14-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 71.86 0.00 01-JAN-00:10 10619.81 07-JUL-09:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 71.86 0.00 01-JAN-00:10 10619.81 07-JUL-09:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 108.97 0.00 01-JAN-00:10 15429.01 10-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.29 0.00 01-JAN-00:10 7536.52 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.29 0.00 01-JAN-00:10 7536.52 09-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 108.68 0.00 01-JAN-00:10 15429.01 10-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 108.68 0.00 01-JAN-00:10 15429.01 10-OCT-13:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 108.08 0.00 01-JAN-00:10 14670.17 18-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.01 0.00 01-JAN-00:10 2030.06 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.01 0.00 01-JAN-00:10 2030.06 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 108.07 0.00 01-JAN-00:10 14670.17 18-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 108.07 0.00 01-JAN-00:10 14670.17 18-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 655.28 0.00 01-JAN-00:10 120626.12 13-FEB-05:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 49.65 0.00 01-JAN-00:10 120626.12 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 49.65 0.00 01-JAN-00:10 120626.12 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 605.63 0.00 01-JAN-00:10 95255.07 14-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 605.63 0.00 01-JAN-00:10 95255.07 14-JUL-15:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 612.13 0.00 01-JAN-00:10 109723.99 07-JUL-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 25.51 0.00 01-JAN-00:10 108526.76 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 25.51 0.00 01-JAN-00:10 108526.76 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 586.62 0.00 01-JAN-00:10 109723.99 07-JUL-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 586.62 0.00 01-JAN-00:10 109723.99 07-JUL-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 886.22 0.00 01-JAN-00:10 146940.49 10-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 21.78 0.00 01-JAN-00:10 133214.37 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 21.78 0.00 01-JAN-00:10 133214.37 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 864.43 0.00 01-JAN-00:10 146940.49 10-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 864.43 0.00 01-JAN-00:10 146940.49 10-OCT-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 645.33 0.00 01-JAN-00:10 113365.17 02-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 18.96 0.00 01-JAN-00:10 98078.36 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 18.96 0.00 01-JAN-00:10 98078.36 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 626.38 0.00 01-JAN-00:10 113365.17 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 626.38 0.00 01-JAN-00:10 113365.17 02-AUG-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 76.18 0.00 01-JAN-00:10 15157.73 13-FEB-04:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 15.96 0.00 01-JAN-00:10 15157.73 13-FEB-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 15.96 0.00 01-JAN-00:10 15157.73 13-FEB-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 60.22 0.00 01-JAN-00:10 10668.62 14-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 60.22 0.00 01-JAN-00:10 10668.62 14-JUL-15:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 65.72 0.00 01-JAN-00:10 12770.31 13-FEB-04:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 8.06 0.00 01-JAN-00:10 12770.31 13-FEB-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 8.06 0.00 01-JAN-00:10 12770.31 13-FEB-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 57.66 0.00 01-JAN-00:10 11461.14 07-JUL-09:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 57.66 0.00 01-JAN-00:10 11461.14 07-JUL-09:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 92.10 0.00 01-JAN-00:10 16446.00 13-FEB-04:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 8.32 0.00 01-JAN-00:10 16446.00 13-FEB-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 8.32 0.00 01-JAN-00:10 16446.00 13-FEB-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 83.78 0.00 01-JAN-00:10 16012.04 10-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 83.78 0.00 01-JAN-00:10 16012.04 10-OCT-13:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 68.18 0.00 01-JAN-00:10 12968.45 09-JAN-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 6.45 0.00 01-JAN-00:10 12968.45 09-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 6.45 0.00 01-JAN-00:10 12968.45 09-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 61.73 0.00 01-JAN-00:10 12163.29 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 61.73 0.00 01-JAN-00:10 12163.29 02-AUG-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 77.48 0.00 01-JAN-00:10 9892.70 07-AUG-14:40
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.60 0.00 01-JAN-00:10 4590.56 13-FEB-08:20
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.60 0.00 01-JAN-00:10 4590.56 13-FEB-08:20
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 75.87 0.00 01-JAN-00:10 9892.70 07-AUG-14:40
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 75.87 0.00 01-JAN-00:10 9892.70 07-AUG-14:40
EnergyTransfer:Zone:MIDFLOOR_PLENUM 578.14 0.00 01-JAN-00:10 81326.82 05-JAN-12:00
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 52.15 0.00 01-JAN-00:10 81326.82 05-JAN-12:00
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 52.15 0.00 01-JAN-00:10 81326.82 05-JAN-12:00
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 525.99 0.00 01-JAN-00:10 79357.92 05-JUL-16:00
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 525.99 0.00 01-JAN-00:10 79357.92 05-JUL-16:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 104.02 0.00 01-JAN-00:10 24537.75 13-FEB-06:20
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 27.04 0.00 01-JAN-00:10 24537.75 13-FEB-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 27.04 0.00 01-JAN-00:10 24537.75 13-FEB-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 76.98 0.00 01-JAN-00:10 21473.12 07-JUL-15:10
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 76.98 0.00 01-JAN-00:10 21473.12 07-JUL-15:10
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 139.59 335.30 08-JAN-08:00 7885.44 09-APR-18:20
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 139.59 335.30 08-JAN-08:00 7885.44 09-APR-18:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 139.59 335.30 08-JAN-08:00 7885.44 09-APR-18:20
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1243.49 0.28 23-JAN-07:40 74169.61 13-AUG-18:40
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 2.41 0.00 02-JAN-09:00 5356.86 08-JAN-01:40
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 2.41 0.00 02-JAN-09:00 5356.86 08-JAN-01:40
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1241.08 0.00 01-JAN-00:10 74169.61 13-AUG-18:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1241.08 0.00 01-JAN-00:10 74169.61 13-AUG-18:40
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 118.11 0.13 14-JAN-10:40 7563.85 13-AUG-19:10
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.69 0.00 02-JAN-13:10 579.25 15-JAN-19:00
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.69 0.00 02-JAN-13:10 579.25 15-JAN-19:00
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 117.42 0.00 01-JAN-00:10 7563.85 13-AUG-19:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 117.42 0.00 01-JAN-00:10 7563.85 13-AUG-19:10
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7156.38 85087.16 09-JAN-05:00 369986.88 07-AUG-21:20
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7156.38 85087.16 09-JAN-05:00 369986.88 07-AUG-21:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7156.38 85087.16 09-JAN-05:00 369986.88 07-AUG-21:20
PlantLoopHeatingDemand:Facility 829.05 0.00 01-JAN-00:10 1311075.39 13-FEB-07:10
PlantLoopHeatingDemand:Plant 371.93 0.00 01-JAN-00:10 47931.16 01-FEB-12:30
WaterSystems:PlantLoopHeatingDemand 371.93 0.00 01-JAN-00:10 47931.16 01-FEB-12:30
General:WaterSystems:PlantLoopHeatingDemand 371.93 0.00 01-JAN-00:10 47931.16 01-FEB-12:30
EnergyTransfer:HVAC 22263.17 122553.96 09-JAN-01:50 2887962.26 10-AUG-16:00
HeatingCoils:EnergyTransfer 457.12 0.00 01-JAN-00:10 1295248.29 13-FEB-07:10
PlantLoopHeatingDemand:HVAC 457.12 0.00 01-JAN-00:10 1295248.29 13-FEB-07:10
HeatingCoils:PlantLoopHeatingDemand 457.12 0.00 01-JAN-00:10 1295248.29 13-FEB-07:10
CoolingCoils:EnergyTransfer 19646.98 110451.15 09-JAN-07:10 2469512.45 21-AUG-10:50
HeatRecoveryForHeating:EnergyTransfer 926.28 0.00 01-JAN-00:10 805188.63 03-FEB-07:20
HeatRecoveryForCooling:EnergyTransfer 1232.78 0.00 01-JAN-00:10 589224.25 07-JUL-12:00
EnergyTransfer:Plant 30301.43 0.00 01-JAN-00:10 6364503.37 17-APR-14:20
LoopToLoop:EnergyTransfer 10056.84 -714.93 05-JAN-13:10 2017060.51 17-APR-14:20
WaterSystems:EnergyTransfer 371.93 0.00 01-JAN-00:10 47931.16 01-FEB-12:30
WaterUse:WaterSystems:EnergyTransfer 371.93 0.00 01-JAN-00:10 47931.16 01-FEB-12:30
Boilers:EnergyTransfer 452.92 0.00 01-JAN-00:10 1323433.68 13-FEB-07:10
Chillers:EnergyTransfer 9017.54 0.00 01-JAN-00:10 1999982.69 17-APR-14:20
HeatRejection:EnergyTransfer 10402.20 0.00 01-JAN-00:10 2268211.89 17-APR-14:20
General:HeatRejection:EnergyTransfer 10402.20 0.00 01-JAN-00:10 2268211.89 17-APR-14:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 4.138 -691.714 0.000 0.000 92.715 240.449 424.397 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -69.986
CORE_BOTTOM 0.000 0.000 0.000 -681.243 0.000 0.000 83.434 215.940 321.286 0.000 0.000 0.000 60.583 0.000 0.000 0.000 0.000 -0.002
CORE_MID 0.000 0.000 0.762 -5011.039 0.000 0.000 841.743 2159.397 3212.845 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1203.707
CORE_TOP 0.000 0.000 5.179 -469.249 0.000 0.000 86.039 215.940 321.285 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -159.194
PERIMETER_BOT_ZN_3 0.000 0.000 0.214 -85.146 0.000 0.000 10.770 18.857 40.342 22.962 0.000 0.235 39.834 0.000 -43.084 0.000 -4.984 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.164 -71.857 0.000 0.000 6.987 12.058 25.998 38.319 0.000 0.166 16.822 0.000 -25.405 0.000 -3.252 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.289 -108.679 0.000 0.000 10.687 18.593 40.343 67.301 0.000 0.229 14.806 0.000 -38.517 0.000 -5.052 -0.000
PERIMETER_BOT_ZN_4 0.000 0.000 0.008 -108.067 0.000 0.000 6.872 12.112 25.998 37.661 0.000 0.141 59.795 0.000 -30.836 0.000 -3.684 0.000
PERIMETER_MID_ZN_3 0.000 0.000 49.648 -605.623 0.000 0.000 111.463 188.815 403.423 237.408 0.000 5.444 98.578 0.000 -386.723 0.000 -102.433 -0.021
PERIMETER_MID_ZN_2 0.000 0.000 25.508 -586.614 0.000 0.000 52.835 120.629 259.981 384.653 0.000 3.553 46.155 0.000 -237.081 0.000 -69.619 -0.001
PERIMETER_MID_ZN_1 0.000 0.000 21.782 -864.421 0.000 0.000 108.430 186.121 403.429 673.216 0.000 5.130 0.012 0.000 -369.684 0.000 -111.632 -52.371
PERIMETER_MID_ZN_4 0.000 0.000 18.957 -626.369 0.000 0.000 71.966 121.171 259.979 388.146 0.000 3.391 97.787 0.000 -262.682 0.000 -72.345 0.000
PERIMETER_TOP_ZN_3 0.000 0.000 15.958 -60.217 0.000 0.000 11.337 18.882 40.342 23.989 0.000 0.657 0.001 0.000 -36.126 0.000 -11.807 -3.015
PERIMETER_TOP_ZN_2 0.000 0.000 8.057 -57.660 0.000 0.000 7.251 12.063 25.998 38.663 0.000 0.419 0.000 0.000 -22.390 0.000 -8.084 -4.318
PERIMETER_TOP_ZN_1 0.000 0.000 8.323 -83.778 0.000 0.000 11.029 18.614 40.343 67.792 0.000 0.609 0.000 0.000 -34.746 0.000 -12.853 -15.334
PERIMETER_TOP_ZN_4 0.000 0.000 6.449 -61.733 0.000 0.000 7.301 12.117 25.998 38.907 0.000 0.410 3.858 0.000 -24.875 0.000 -8.433 -0.000
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -139.586 0.000 0.000 0.949 5.965 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -21.209
DATACENTER_MID_ZN_6 0.000 0.000 2.413 -1241.083 0.000 0.000 9.488 59.652 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -369.276
DATACENTER_TOP_ZN_6 0.000 0.000 0.694 -117.420 0.000 0.000 0.951 5.965 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -44.071
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7156.386 0.000 0.000 20.226 67.796 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -426.493
GROUNDFLOOR_PLENUM 1.603 -75.873 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.407 84.715 0.000 0.000 0.000 -10.851 0.000
MIDFLOOR_PLENUM 52.150 -525.984 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 7.443 648.249 0.000 0.000 0.000 -181.859 -0.004
TOPFLOOR_PLENUM 27.042 -76.979 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.650 67.976 0.000 0.000 0.000 -18.689 -0.002
Total Facility 80.795 -678.836 168.545 -18827.884 0.000 0.000 1552.474 3711.135 15213.411 2019.017 0.000 28.884 1239.172 0.000 -1512.148 0.000 -625.578 -2369.004


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 11-DEC-04:02 0.00 0.00 0.00 -114923.87 0.00 0.00 0.00 1166.43 13457.54 0.00 0.00 0.00 100299.90 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 13-NOV-04:02 0.00 0.00 0.00 -96104.66 0.00 0.00 0.00 1047.53 8057.15 0.00 0.00 0.00 86999.97 0.00 -0.00 0.00 0.00 0.00
CORE_MID 20-JUN-03:02 0.00 0.00 0.00 -847754.36 0.00 0.00 0.00 10475.32 80571.20 0.00 0.00 0.00 756707.84 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 19-JUN-03:02 0.00 0.00 0.00 -86780.79 0.00 0.00 0.00 1047.53 8057.12 0.00 0.00 0.00 77676.13 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 09-JUL-18:01 0.00 0.00 0.00 -16292.46 0.00 0.00 0.00 80.80 758.77 3444.14 0.00 124.89 11883.86 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 04-JUL-09:32 0.00 0.00 0.00 -16410.13 0.00 0.00 24.96 52.07 488.98 9431.24 0.00 0.00 6421.71 0.00 -0.00 0.00 -8.83 0.00
PERIMETER_BOT_ZN_1 08-OCT-14:02 0.00 0.00 0.00 -19829.47 0.00 0.00 38.70 80.80 758.78 12962.54 0.00 0.00 6017.78 0.00 -0.00 0.00 -29.12 0.00
PERIMETER_BOT_ZN_4 04-JUL-17:31 0.00 0.00 0.00 -22957.82 0.00 0.00 0.00 52.07 488.98 8744.21 0.00 37.36 13635.20 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 25-JUN-16:41 0.00 0.00 0.00 -151459.06 0.00 0.00 440.99 807.98 7587.73 39157.41 0.00 5387.03 98077.93 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 04-JUL-09:32 0.00 0.00 0.00 -171132.03 0.00 0.00 241.33 520.69 4889.82 93032.38 0.00 0.00 72745.99 0.00 -0.00 0.00 -298.18 0.00
PERIMETER_MID_ZN_1 09-OCT-14:42 0.00 0.00 0.00 -190768.24 0.00 0.00 379.31 807.99 7587.84 108087.80 0.00 0.00 74036.53 0.00 -0.00 0.00 -131.24 0.00
PERIMETER_MID_ZN_4 04-JUL-17:31 0.00 0.00 0.00 -189853.81 0.00 0.00 0.00 520.69 4889.79 87696.98 0.00 977.70 95768.65 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 06-AUG-17:01 0.00 0.00 0.00 -17794.06 0.00 0.00 0.00 80.80 758.77 2572.78 0.00 551.07 13830.65 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 06-AUG-11:02 0.00 0.00 0.00 -17596.90 0.00 0.00 23.73 52.07 488.98 6181.08 0.00 109.06 10741.98 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 09-OCT-14:32 0.00 0.00 0.00 -21119.71 0.00 0.00 38.06 80.80 758.78 11272.71 0.00 0.00 8990.95 0.00 -0.00 0.00 -21.59 0.00
PERIMETER_TOP_ZN_4 06-AUG-17:01 0.00 0.00 0.00 -20636.84 0.00 0.00 0.00 52.07 488.98 7219.92 0.00 263.79 12612.08 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 09-APR-18:13 0.00 0.00 0.00 -7885.44 0.00 0.00 0.00 28.94 7794.42 0.00 0.00 0.00 62.08 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 13-AUG-18:40 0.00 0.00 0.00 -74169.61 0.00 0.00 0.00 289.38 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -4063.99
DATACENTER_TOP_ZN_6 13-AUG-19:32 0.00 0.00 0.00 -7566.92 0.00 0.00 0.00 28.94 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -256.44
DATACENTER_BASEMENT_ZN_6 07-AUG-21:12 0.00 0.00 0.00 -370323.42 0.00 0.00 113.48 657.76 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -10080.34
GROUNDFLOOR_PLENUM 14-AUG-05:15 0.00 -13406.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13433.71 0.00 -0.00 0.00 -27.03 0.00
MIDFLOOR_PLENUM 30-AUG-05:15 0.00 -85973.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 86725.77 0.00 -0.00 0.00 -752.62 0.00
TOPFLOOR_PLENUM 07-JUL-15:10 0.00 -21472.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 114.90 21357.66 0.00 -0.00 0.00 0.00 0.00
Total Facility 07-AUG-05:03 0.00 -57853.81 0.00 -1885231.36 0.00 0.00 15730.14 39207.80 623236.89 0.00 0.00 0.00 1299294.97 0.00 -33352.10 0.00 -1032.53 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 08-JUL-16:02 0.00 0.00 25322.13 0.00 0.00 0.00 520.13 1166.43 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -40466.23
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID 09-JAN-05:01 0.00 0.00 401375.39 0.00 0.00 0.00 0.00 20950.64 80571.20 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -502897.23
CORE_TOP 09-JAN-04:01 0.00 0.00 79161.55 0.00 0.00 0.00 0.00 1047.53 8057.12 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -88266.20
PERIMETER_BOT_ZN_3 13-FEB-05:02 0.00 0.00 11825.97 0.00 0.00 0.00 0.00 263.06 1011.70 0.00 0.00 0.00 0.00 0.00 -5087.74 0.00 -1389.83 -6623.15
PERIMETER_BOT_ZN_2 13-FEB-05:02 0.00 0.00 9386.04 0.00 0.00 0.00 0.00 169.52 651.98 0.00 0.00 0.00 0.00 0.00 -3384.22 0.00 -928.63 -5894.70
PERIMETER_BOT_ZN_1 09-JAN-05:01 0.00 0.00 14343.18 0.00 0.00 0.00 0.00 263.06 1011.71 0.00 0.00 0.00 0.00 0.00 -3957.11 0.00 -881.67 -10779.18
PERIMETER_BOT_ZN_4 13-FEB-06:01 0.00 0.00 7001.29 0.00 0.00 0.00 94.15 169.52 651.97 0.00 0.00 0.00 0.00 0.00 -3538.67 0.00 -248.55 -4129.70
PERIMETER_MID_ZN_3 12-FEB-05:22 0.00 0.00 136834.73 0.00 0.00 0.00 0.00 1315.28 7587.73 0.00 0.00 0.00 0.00 0.00 -56729.76 0.00 -37479.29 -51528.69
PERIMETER_MID_ZN_2 12-FEB-05:22 0.00 0.00 142153.87 0.00 0.00 0.00 0.00 847.62 4889.82 0.00 0.00 0.00 0.00 0.00 -36433.59 0.00 -25332.61 -86125.11
PERIMETER_MID_ZN_1 12-FEB-05:22 0.00 0.00 154821.25 0.00 0.00 0.00 0.00 1315.31 7587.84 0.00 0.00 0.00 0.00 0.00 -55331.51 0.00 -38156.70 -70236.20
PERIMETER_MID_ZN_4 09-JAN-04:01 0.00 0.00 144950.71 0.00 0.00 0.00 0.00 847.62 6519.72 0.00 0.00 0.00 0.00 0.00 -24003.43 0.00 -11303.50 -117011.12
PERIMETER_TOP_ZN_3 12-FEB-05:22 0.00 0.00 16682.70 0.00 0.00 0.00 0.00 131.53 758.77 0.00 0.00 0.00 0.00 0.00 -5324.59 0.00 -4384.04 -7864.37
PERIMETER_TOP_ZN_2 12-FEB-05:22 0.00 0.00 15585.08 0.00 0.00 0.00 0.00 84.76 488.98 0.00 0.00 0.00 0.00 0.00 -3419.22 0.00 -2962.95 -9776.66
PERIMETER_TOP_ZN_1 12-FEB-05:22 0.00 0.00 18635.37 0.00 0.00 0.00 0.00 131.53 758.78 0.00 0.00 0.00 0.00 0.00 -5170.38 0.00 -4432.83 -9922.48
PERIMETER_TOP_ZN_4 12-FEB-05:22 0.00 0.00 17046.62 0.00 0.00 0.00 0.00 84.76 488.98 0.00 0.00 0.00 0.00 0.00 -3634.25 0.00 -3031.56 -10954.55
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 08-JAN-01:40 0.00 0.00 5356.86 0.00 0.00 0.00 0.00 289.38 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -25132.29
DATACENTER_TOP_ZN_6 15-JAN-19:00 0.00 0.00 579.25 0.00 0.00 0.00 0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2556.80
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 26-DEC-04:03 13738.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -1809.59 -11928.77
MIDFLOOR_PLENUM 05-JAN-11:33 140286.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -10510.22 -129776.39
TOPFLOOR_PLENUM 13-FEB-05:32 25574.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -5009.54 -20564.72
Total Facility 09-JAN-06:01 -154712.91 203413.70 1054210.93 -203413.70 0.00 0.00 21352.49 39207.80 268362.69 0.00 0.00 0.00 0.00 0.00 -157169.26 0.00 -27941.05 -1043310.69



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 10.4676 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.7071 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 98.2697 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 90.4253 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 10.1315 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.6555 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.8456 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.8456 0.2053 1.0000 Not calculated 1.2002 0.2053    
AIRLOOP DATACENTER BASEMENT 22.0966 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 22.0969 0.0153 1.0000 Not calculated 0.3384 0.0153    
AIRLOOP DATACENTER BOT 0.4887 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4887 0.0320 1.0000 Not calculated 0.0156 0.0320    
AIRLOOP DATACENTER MID 4.6470 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.6470 0.0336 1.0000 Not calculated 0.1563 0.0336    
AIRLOOP DATACENTER TOP 0.4700 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4700 0.0333 1.0000 Not calculated 0.0156 0.0333    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.2338 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.2325 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 49.1348 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 31.0484 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.0658 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.2517 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.8456 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.8456 1.0000 1.0000 Not calculated 1.2002 0.2053    
AIRLOOP DATACENTER BASEMENT 22.0966 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 22.0966 1.0000 1.0000 Not calculated 0.3384 0.0153    
AIRLOOP DATACENTER BOT 0.4887 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4887 1.0000 1.0000 Not calculated 0.0156 0.0320    
AIRLOOP DATACENTER MID 4.6470 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.6470 1.0000 1.0000 Not calculated 0.1563 0.0336    
AIRLOOP DATACENTER TOP 0.4700 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4700 1.0000 1.0000 Not calculated 0.0156 0.0333    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.8456 5.8456 5.8456 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.1508 6.1508 1.9375 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 58.0540 58.0540 18.9837 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.7357 5.7357 1.9329 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9923 0.9923 0.2977 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9560 0.9560 0.2868 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1370 1.1370 0.3411 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2316 1.2316 0.3695 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.3102 9.3102 2.7931 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.8028 9.8028 2.9408 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.7346 10.7346 3.2204 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.3680 10.3680 3.1104 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0643 1.0643 0.3193 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0055 1.0055 0.3016 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1996 1.1996 0.3599 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1265 1.1265 0.3379 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4887 0.4887 0.4887 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.6470 4.6470 4.6470 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4700 0.4700 0.4700 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 22.0966 22.0966 22.0966 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 10.4676 9.7071 10.4676 3.2325 0.0000 1.0000
VAV_MID WITH REHEAT 98.2697 90.4253 98.2697 31.0484 0.0000 1.0000
VAV_TOP WITH REHEAT 10.1315 9.6555 10.1315 3.2517 0.0000 1.0000
CAV_BAS 5.8456 5.8456 5.8456 5.8456 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 22.0966 22.0969 22.0966 22.0966 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4887 0.4887 0.4887 0.4887 0.0156 1.0000
AIRLOOP DATACENTER MID 4.6470 4.6470 4.6470 4.6470 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4700 0.4700 0.4700 0.4700 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.8456 5.8456 5.8456 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.0754 3.0754 1.9375 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 29.0270 29.0270 18.9837 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8679 2.8679 1.9329 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4961 0.4961 0.2977 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4780 0.4780 0.2868 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5685 0.5685 0.3411 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6158 0.6158 0.3695 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.6551 4.6551 2.7931 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.9014 4.9014 2.9408 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.3673 5.3673 3.2204 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.1840 5.1840 3.1104 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5321 0.5321 0.3193 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5027 0.5027 0.3016 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5998 0.5998 0.3599 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5632 0.5632 0.3379 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4887 0.4887 0.4887 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.6470 4.6470 4.6470 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4700 0.4700 0.4700 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 22.0966 22.0966 22.0966 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.2338 3.2325 3.2325 3.2325 0.0000 1.0000
VAV_MID WITH REHEAT 49.1348 31.0484 31.0484 31.0484 0.0000 1.0000
VAV_TOP WITH REHEAT 5.0658 3.2517 3.2517 3.2517 0.0000 1.0000
CAV_BAS 5.8456 5.8456 5.8456 5.8456 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 22.0966 22.0966 22.0966 22.0966 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4887 0.4887 0.4887 0.4887 0.0156 1.0000
AIRLOOP DATACENTER MID 4.6470 4.6470 4.6470 4.6470 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4700 0.4700 0.4700 0.4700 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 29.67
Number of hours cooling loads not met 501.00
Number of hours not met 530.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 640.67 1589015.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 4111.57 456189.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 3711.13 352689.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 670.87 54335.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5871.99 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 87.33 5481.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2525.85 287700.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 801.73 73998.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1454.27 92421.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 8.95 5867.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 50.38 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 657.71 79691.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 15213.41 30490.10
Natural Gas 0.00 1298.37
Additional 0.00 0.00
Total 15213.41 31788.48


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 80.12
Space Heating 0.00
Space Cooling 88.76
Fans (All) 54.53
Service Water Heating 0.00
Receptacle Equipment 328.44
Miscellaneous (All) 658.24
Subtotal 658.24


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 13.83
Service Water Heating 14.20
Miscellaneous (All) 28.03
Subtotal 28.03


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 11.67
Space Heating 2.02
Space Cooling 12.93
Fans (All) 7.95
Service Water Heating 2.07
Receptacle Equipment 47.86
Miscellaneous 15.50


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2645. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4487. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 2347. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8027.83 732.17 0.00 0.00 0.00
CORE_BOTTOM 8678.50 81.50 0.00 0.00 0.00
CORE_MID 8759.17 0.83 0.00 0.00 0.00
CORE_TOP 8748.33 11.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8746.50 13.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8714.67 45.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8716.83 43.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8109.67 650.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8731.33 28.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8610.67 149.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8643.50 116.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8301.67 458.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8699.83 60.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8572.50 187.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8606.83 153.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8323.50 436.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 6781.83 1978.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 6771.50 1988.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 6742.83 2017.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 6628.83 2131.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8590.00 170.00 0.00 0.00 0.00
Min 6628.83 0.00 0.00 0.00 0.00
Max 8760.00 2131.17 0.00 0.00 0.00
Average 8262.01 497.99 0.00 0.00 0.00
Sum 190026.33 11453.67 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 366573.17 2042.83 0.00 0.00 0.00
CORE_BOTTOM 330687.00 126.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330807.00 6.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1240.83 1027.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1229.83 1038.17 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1220.67 1047.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 61354.00 42041.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 366573.17 42041.00 0.00 0.00 0.00
Average 78277.15 2057.76 0.00 0.00 0.00
Sum 1800374.50 47328.50 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 6295.00 2465.00 0.00 0.00 0.00
CORE_BOTTOM 7466.00 1294.00 0.00 0.00 0.00
CORE_MID 7463.00 1297.00 0.00 0.00 0.00
CORE_TOP 7496.17 1263.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 7551.17 1208.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 7975.33 784.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 7582.50 1177.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7124.83 1635.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 7425.50 1334.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 7472.00 1288.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 7350.83 1409.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7337.67 1422.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 7475.67 1284.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 7484.00 1276.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 7396.67 1363.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7380.00 1380.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7396.33 1363.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7358.17 1401.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7334.33 1425.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7482.33 1277.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 7166.67 1593.33 0.00 0.00 0.00
MIDFLOOR_PLENUM 7238.67 1521.33 0.00 0.00 0.00
TOPFLOOR_PLENUM 6423.33 2336.67 0.00 0.00 0.00
Min 6295.00 784.67 0.00 0.00 0.00
Max 7975.33 2465.00 0.00 0.00 0.00
Average 7333.75 1426.25 0.00 0.00 0.00
Sum 168676.17 32803.83 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 345199.83 23416.17 0.00 0.00 0.00
CORE_BOTTOM 328414.33 2398.67 0.00 0.00 0.00
CORE_MID 328514.50 2298.50 0.00 0.00 0.00
CORE_TOP 328164.33 2648.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38920.33 4.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38922.33 2.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38919.00 6.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24908.67 0.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38921.83 3.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24908.83 0.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1473.33 794.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1457.00 811.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1443.67 824.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 75864.83 27530.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 345199.83 27530.17 0.00 0.00 0.00
Average 77694.08 2640.83 0.00 0.00 0.00
Sum 1786963.83 60739.17 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:06

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.472557E+11 109093.15 02-JAN-04:03 3.30 2.57 0.565359E+10 7499.16 10-JAN-14:09 3.98 1.51
February 0.441967E+11 109664.00 27-FEB-04:02 11.20 6.60 0.513240E+10 7499.15 28-FEB-14:20 25.00 13.71
March 0.559121E+11 111022.50 13-MAR-03:02 7.70 3.23 0.613087E+10 7499.46 08-MAR-10:20 7.70 3.23
April 0.506788E+11 109035.55 10-APR-03:02 10.32 6.33 0.544633E+10 7499.26 03-APR-09:20 10.32 6.33
May 0.553991E+11 107862.13 15-MAY-03:02 12.80 11.19 0.589995E+10 7499.39 11-MAY-09:00 12.80 11.19
June 0.595708E+11 100968.31 10-JUN-05:02 11.28 8.79 0.588213E+10 7499.07 09-JUN-09:00 11.28 8.79
July 0.610352E+11 92535.35 03-JUL-03:02 17.80 16.72 0.547419E+10 7498.78 28-JUL-09:20 19.40 19.40
August 0.693769E+11 87250.99 26-AUG-03:02 21.70 17.57 0.613922E+10 7499.01 25-AUG-09:39 21.70 17.57
September 0.632257E+11 100330.03 14-SEP-03:02 13.72 12.10 0.545431E+10 7499.17 22-SEP-13:09 26.20 16.90
October 0.646852E+11 110967.27 30-OCT-03:02 8.90 8.90 0.567249E+10 7498.97 31-OCT-09:00 10.60 9.10
November 0.627481E+11 112151.79 20-NOV-04:02 10.63 8.44 0.561649E+10 7499.35 16-NOV-10:20 10.63 8.44
December 0.576283E+11 114909.02 11-DEC-04:02 7.12 6.27 0.547007E+10 7499.26 11-DEC-10:39 13.90 11.28
                     
Annual Sum or Average 0.691713E+12         0.679720E+11        
Minimum of Months 0.441967E+11 87250.99   3.30 2.57 0.513240E+10 7498.78   3.98 1.51
Maximum of Months 0.693769E+11 114909.02   21.70 17.57 0.613922E+10 7499.46   26.20 19.40



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.367208E+11 87864.18 02-JAN-06:02 3.30 2.54 0.504922E+10 6750.38 03-JAN-14:00 2.80 2.54
February 0.391809E+11 90363.19 21-FEB-04:03 6.70 4.44 0.459431E+10 6747.64 07-FEB-14:00 6.70 4.44
March 0.573910E+11 92577.88 13-MAR-03:02 7.70 3.23 0.550026E+10 6735.22 08-MAR-10:09 7.70 3.23
April 0.606136E+11 91042.64 05-APR-03:02 12.12 11.47 0.488278E+10 6839.87 14-APR-13:50 27.12 15.42
May 0.572607E+11 93899.66 08-MAY-03:02 16.78 16.47 0.528829E+10 6818.86 18-MAY-13:20 28.70 18.38
June 0.654536E+11 90526.79 01-JUN-03:02 19.73 17.88 0.526952E+10 6734.84 09-JUN-09:00 24.40 15.46
July 0.703536E+11 89480.77 29-JUL-03:02 17.70 17.43 0.489452E+10 6734.56 05-JUL-09:00 17.70 17.43
August 0.796125E+11 82140.59 08-AUG-04:23 20.60 20.43 0.549421E+10 6734.63 25-AUG-13:50 30.92 18.65
September 0.573538E+11 95243.17 18-SEP-03:02 15.00 14.25 0.488482E+10 6734.83 22-SEP-13:30 26.40 17.18
October 0.557873E+11 94071.26 16-OCT-03:02 13.90 13.26 0.508068E+10 6734.71 30-OCT-09:00 11.10 11.10
November 0.529991E+11 96114.60 13-NOV-04:02 5.40 2.09 0.503221E+10 6735.03 16-NOV-10:09 10.68 10.03
December 0.485181E+11 92234.92 11-DEC-04:02 7.12 6.27 0.490315E+10 6734.97 11-DEC-10:00 15.00 12.11
                     
Annual Sum or Average 0.681245E+12         0.608740E+11        
Minimum of Months 0.367208E+11 82140.59   3.30 2.09 0.459431E+10 6734.56   2.80 2.54
Maximum of Months 0.796125E+11 96114.60   20.60 20.43 0.550026E+10 6839.87   30.92 18.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.254895E+11 65721.43 05-JAN-11:33 0.03 -4.6 0.473986E+10 6832.63 05-JAN-11:00 0.60 -4.3
February 0.273172E+11 77635.86 23-FEB-06:03 5.50 3.99 0.442844E+10 7298.42 02-FEB-10:30 5.50 3.99
March 0.409097E+11 81356.74 30-MAR-04:03 17.30 15.29 0.547163E+10 6737.49 22-MAR-13:09 17.30 15.29
April 0.420835E+11 82417.86 21-APR-04:03 15.60 14.27 0.487310E+10 6782.37 14-APR-13:50 15.60 14.27
May 0.494103E+11 84764.16 31-MAY-03:02 20.92 19.80 0.528347E+10 6864.74 15-MAY-13:39 20.92 19.80
June 0.531776E+11 84794.05 20-JUN-03:02 20.40 19.67 0.526759E+10 6738.49 02-JUN-13:50 20.40 19.67
July 0.530497E+11 84563.52 26-JUL-03:02 21.70 21.41 0.489411E+10 6734.55 05-JUL-09:20 21.70 21.41
August 0.573491E+11 84261.34 25-AUG-03:02 20.50 18.92 0.549536E+10 6734.71 25-AUG-13:09 30.18 18.86
September 0.478129E+11 84617.26 11-SEP-03:02 20.00 18.85 0.487839E+10 6734.81 22-SEP-13:50 26.60 17.45
October 0.410871E+11 82354.80 18-OCT-04:03 20.00 20.00 0.505581E+10 6760.86 25-OCT-09:50 8.22 6.77
November 0.346327E+11 81820.84 04-NOV-05:02 16.60 15.28 0.498607E+10 6768.89 20-NOV-10:09 4.90 2.39
December 0.287870E+11 79238.75 14-DEC-06:03 6.60 5.31 0.476036E+10 6805.48 01-DEC-10:09 6.60 5.31
                     
Annual Sum or Average 0.501106E+12         0.601342E+11        
Minimum of Months 0.254895E+11 65721.43   0.03 -4.6 0.442844E+10 6734.55   0.60 -4.3
Maximum of Months 0.573491E+11 84794.05   21.70 21.41 0.549536E+10 7298.42   30.18 21.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.190323E+11 30488.72 20-JAN-17:00 16.70 11.48 0.423394E+10 6734.26 20-JAN-14:00 16.70 11.48
February 0.215242E+11 38955.49 28-FEB-17:00 23.90 12.94 0.410107E+10 6734.75 22-FEB-14:00 23.90 12.94
March 0.341955E+11 80162.48 31-MAR-04:03 17.12 14.83 0.533425E+10 6734.85 08-MAR-10:00 17.12 14.83
April 0.383594E+11 81971.81 24-APR-04:03 13.90 13.90 0.481835E+10 6891.67 17-APR-13:00 13.90 13.90
May 0.495072E+11 85140.36 30-MAY-03:02 20.00 17.77 0.527482E+10 6767.47 19-MAY-13:39 20.00 17.77
June 0.565566E+11 86798.98 19-JUN-03:02 20.60 19.79 0.526817E+10 6734.80 09-JUN-09:00 20.60 19.79
July 0.576697E+11 84643.21 03-JUL-03:02 17.80 16.72 0.489517E+10 6734.52 28-JUL-09:09 19.40 19.40
August 0.621185E+11 84199.07 08-AUG-03:02 21.02 20.73 0.549771E+10 6742.39 25-AUG-13:50 30.92 18.65
September 0.467118E+11 85801.98 05-SEP-03:02 22.02 20.50 0.486799E+10 6734.79 22-SEP-13:00 26.70 17.59
October 0.350214E+11 81051.42 18-OCT-04:03 20.00 20.00 0.494371E+10 6750.04 04-OCT-09:20 20.00 20.00
November 0.263046E+11 75235.52 04-NOV-05:02 16.60 15.28 0.473603E+10 6734.68 02-NOV-09:00 16.60 15.28
December 0.222512E+11 61707.63 13-DEC-06:03 16.70 15.65 0.429783E+10 6734.52 14-DEC-14:00 15.00 10.54
                     
Annual Sum or Average 0.469252E+12         0.582690E+11        
Minimum of Months 0.190323E+11 30488.72   13.90 11.48 0.410107E+10 6734.26   13.90 10.54
Maximum of Months 0.621185E+11 86798.98   23.90 20.73 0.549771E+10 6891.67   30.92 20.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.258109E+10 3738.25 31-JAN-15:00 21.10 12.97 0.529799E+09 845.60 19-JAN-14:00 21.10 12.97
February 0.327032E+10 5987.05 28-FEB-15:00 25.00 13.71 0.512283E+09 845.64 22-FEB-14:09 25.00 13.71
March 0.566302E+10 9132.41 30-MAR-05:03 17.80 16.10 0.670998E+09 845.64 08-MAR-10:00 17.80 16.10
April 0.716516E+10 10617.15 19-APR-05:03 16.02 14.35 0.605383E+09 854.66 18-APR-13:39 16.02 14.35
May 0.806542E+10 12398.95 30-MAY-05:03 18.68 17.36 0.662060E+09 857.03 18-MAY-13:20 18.68 17.36
June 0.110192E+11 16106.91 25-JUN-16:41 32.88 22.29 0.661899E+09 845.64 09-JUN-09:00 32.88 22.29
July 0.120973E+11 16295.45 09-JUL-18:01 32.70 22.56 0.615347E+09 845.63 05-JUL-13:39 32.70 22.56
August 0.133133E+11 12345.25 14-AUG-05:03 23.30 20.62 0.690423E+09 846.05 10-AUG-13:39 23.30 20.62
September 0.783026E+10 12045.38 05-SEP-03:02 22.02 20.50 0.611580E+09 845.65 22-SEP-13:30 26.40 17.18
October 0.578443E+10 11399.33 18-OCT-05:03 20.00 20.00 0.622985E+09 845.62 12-OCT-09:09 20.00 20.00
November 0.457799E+10 5685.05 02-NOV-14:00 23.30 17.05 0.604710E+09 845.63 06-NOV-10:09 14.87 12.62
December 0.377912E+10 7211.23 13-DEC-06:03 16.70 15.65 0.562233E+09 845.62 12-DEC-10:00 16.70 15.65
                     
Annual Sum or Average 0.851467E+11         0.734970E+10        
Minimum of Months 0.258109E+10 3738.25   16.02 12.97 0.512283E+09 845.60   14.87 12.62
Maximum of Months 0.133133E+11 16295.45   32.88 22.56 0.690423E+09 857.03   32.88 22.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.236632E+10 3099.59 31-JAN-06:02 10.00 8.54 0.338942E+09 534.14 31-JAN-10:00 14.40 11.88
February 0.300477E+10 6232.97 27-FEB-09:40 12.23 5.46 0.326240E+09 544.96 28-FEB-10:00 20.60 11.95
March 0.496324E+10 7103.79 14-MAR-09:30 16.95 13.93 0.425908E+09 545.00 08-MAR-10:09 16.95 13.93
April 0.628561E+10 8650.84 17-APR-08:40 19.27 13.92 0.388277E+09 550.72 18-APR-13:39 27.40 16.07
May 0.717531E+10 16058.82 07-MAY-09:23 24.15 19.65 0.425492E+09 553.76 18-MAY-13:20 28.70 18.38
June 0.899868E+10 16295.78 25-JUN-10:02 29.50 22.85 0.426010E+09 545.25 05-JUN-09:00 29.50 22.85
July 0.975426E+10 16417.45 04-JUL-09:32 26.47 23.26 0.395571E+09 545.42 05-JUL-09:30 29.15 23.71
August 0.101731E+11 11289.96 27-AUG-09:43 26.83 21.78 0.443843E+09 545.37 07-AUG-09:00 26.83 21.78
September 0.685713E+10 14803.05 24-SEP-09:43 25.63 18.45 0.391710E+09 545.44 08-SEP-09:00 25.63 18.45
October 0.516258E+10 7662.42 10-OCT-09:30 21.95 18.16 0.396061E+09 544.95 05-OCT-09:00 21.95 18.16
November 0.391683E+10 5862.82 06-NOV-09:30 13.30 11.71 0.380498E+09 544.96 06-NOV-10:09 14.87 12.62
December 0.319955E+10 3611.55 13-DEC-04:02 17.20 15.19 0.351224E+09 544.97 11-DEC-10:00 17.20 15.19
                     
Annual Sum or Average 0.718574E+11         0.468978E+10        
Minimum of Months 0.236632E+10 3099.59   10.00 5.46 0.326240E+09 534.14   14.40 11.88
Maximum of Months 0.101731E+11 16417.45   29.50 23.26 0.443843E+09 553.76   29.50 23.71



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.415955E+10 11186.28 26-JAN-13:40 0.00 -3.9 0.567142E+09 845.64 10-JAN-14:09 0.00 -3.9
February 0.519165E+10 16062.58 26-FEB-12:43 23.72 12.50 0.529851E+09 847.14 02-FEB-14:30 23.72 12.50
March 0.830328E+10 13802.25 30-MAR-13:30 27.25 18.02 0.672253E+09 847.00 30-MAR-13:50 27.62 17.92
April 0.909990E+10 13594.02 17-APR-14:00 28.90 16.63 0.604293E+09 875.51 17-APR-13:20 28.90 16.63
May 0.900199E+10 14006.53 30-MAY-03:02 20.00 17.77 0.660333E+09 863.81 16-MAY-13:39 20.00 17.77
June 0.113926E+11 17343.17 25-JUN-16:41 32.88 22.29 0.661224E+09 845.65 09-JUN-09:00 32.88 22.29
July 0.127532E+11 18627.18 09-JUL-16:01 33.80 23.13 0.615088E+09 846.00 31-JUL-13:00 30.60 24.81
August 0.152465E+11 15137.59 27-AUG-15:02 31.70 21.48 0.690760E+09 846.52 14-AUG-13:20 31.70 21.48
September 0.103977E+11 19428.00 24-SEP-13:02 28.80 19.88 0.611569E+09 846.72 22-SEP-13:39 28.80 19.88
October 0.938522E+10 19828.97 08-OCT-14:02 26.78 18.72 0.624396E+09 865.23 10-OCT-13:50 29.22 21.00
November 0.753488E+10 19614.22 11-NOV-13:13 21.10 11.68 0.614650E+09 846.07 14-NOV-14:50 19.72 9.25
December 0.621354E+10 13771.07 10-DEC-12:53 15.60 7.72 0.581291E+09 846.16 12-DEC-14:20 22.80 16.78
                     
Annual Sum or Average 0.108680E+12         0.743285E+10        
Minimum of Months 0.415955E+10 11186.28   0.00 -3.9 0.529851E+09 845.64   0.00 -3.9
Maximum of Months 0.152465E+11 19828.97   33.80 23.13 0.690760E+09 875.51   32.88 24.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.361917E+10 4773.26 20-JAN-16:30 16.95 12.13 0.347202E+09 544.93 20-JAN-14:00 16.95 12.13
February 0.462683E+10 9235.97 27-FEB-16:40 22.40 11.40 0.340664E+09 544.96 22-FEB-14:09 22.40 11.40
March 0.831917E+10 15878.61 30-MAR-05:03 17.80 16.10 0.440936E+09 544.99 08-MAR-10:09 17.80 16.10
April 0.107993E+11 20634.32 09-APR-16:32 21.70 10.73 0.395561E+09 552.98 18-APR-13:39 27.40 16.07
May 0.898760E+10 16209.18 29-MAY-17:53 29.40 20.07 0.426534E+09 554.72 18-MAY-13:20 29.40 20.07
June 0.121407E+11 22469.47 25-JUN-16:01 33.22 22.10 0.427256E+09 544.97 09-JUN-09:00 33.22 22.10
July 0.141034E+11 22967.04 04-JUL-17:31 30.40 22.45 0.397397E+09 544.94 31-JUL-13:00 30.60 24.81
August 0.168533E+11 21925.47 13-AUG-16:22 30.55 22.29 0.445974E+09 544.95 10-AUG-13:39 30.55 22.29
September 0.871890E+10 20567.27 24-SEP-16:22 28.35 19.92 0.394031E+09 544.98 22-SEP-13:30 28.35 19.92
October 0.752920E+10 20561.19 08-OCT-15:22 27.20 18.90 0.404662E+09 544.95 04-OCT-13:00 27.20 18.90
November 0.653904E+10 12136.88 04-NOV-03:02 17.20 15.81 0.399807E+09 544.98 16-NOV-10:09 10.68 10.03
December 0.583082E+10 16398.99 13-DEC-06:03 16.70 15.65 0.385104E+09 544.97 11-DEC-10:00 16.70 15.65
                     
Annual Sum or Average 0.108067E+12         0.480513E+10        
Minimum of Months 0.361917E+10 4773.26   16.70 10.73 0.340664E+09 544.93   10.68 10.03
Maximum of Months 0.168533E+11 22967.04   33.22 22.45 0.445974E+09 554.72   33.22 24.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.787259E+09 2536.78 20-JAN-15:50 17.30 12.80 0.477453E+09 783.58 20-JAN-14:00 17.30 12.80
February 0.158744E+10 4205.37 28-FEB-15:00 25.00 13.71 0.458326E+09 845.61 28-FEB-14:09 25.00 13.71
March 0.367825E+10 6423.60 30-MAR-16:00 27.80 17.47 0.619872E+09 845.60 29-MAR-13:09 27.80 17.47
April 0.454666E+10 7562.71 12-APR-14:40 28.50 16.95 0.584158E+09 850.32 14-APR-13:50 27.12 15.42
May 0.669695E+10 8534.72 30-MAY-15:00 30.60 21.44 0.657633E+09 862.43 15-MAY-13:39 30.60 21.44
June 0.912169E+10 15148.92 25-JUN-16:41 32.88 22.29 0.661394E+09 850.16 02-JUN-13:50 32.88 22.29
July 0.952975E+10 12120.27 15-JUL-03:02 23.90 20.50 0.615239E+09 845.60 03-JUL-13:30 23.90 20.50
August 0.997690E+10 13329.16 06-AUG-17:01 32.20 23.07 0.690766E+09 845.62 25-AUG-13:09 30.18 18.86
September 0.635452E+10 11099.43 27-SEP-05:03 22.80 20.09 0.607472E+09 845.64 22-SEP-13:50 22.80 20.09
October 0.403993E+10 6254.82 02-OCT-14:40 26.70 20.10 0.584428E+09 845.61 05-OCT-13:09 20.00 14.95
November 0.266585E+10 3748.10 03-NOV-14:00 21.70 17.40 0.536482E+09 845.61 03-NOV-13:39 21.70 17.40
December 0.157788E+10 3251.69 13-DEC-06:03 16.70 15.65 0.479827E+09 845.60 13-DEC-14:09 18.30 16.86
                     
Annual Sum or Average 0.605631E+11         0.697305E+10        
Minimum of Months 0.787259E+09 2536.78   16.70 12.80 0.458326E+09 783.58   17.30 12.80
Maximum of Months 0.997690E+10 15148.92   32.88 23.07 0.690766E+09 862.43   32.88 22.29



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.982459E+09 2742.90 26-JAN-13:38 0.00 -3.9 0.224683E+09 456.90 31-JAN-16:00 19.40 13.37
February 0.172928E+10 4633.63 02-FEB-11:45 0.92 -1.6 0.219298E+09 521.21 28-FEB-11:09 20.87 12.02
March 0.379110E+10 5573.89 14-MAR-11:00 20.60 15.46 0.295188E+09 522.63 07-MAR-09:39 20.60 15.46
April 0.494101E+10 8472.37 17-APR-10:10 23.27 15.57 0.279654E+09 532.14 12-APR-14:00 23.27 15.57
May 0.662489E+10 16566.35 07-MAY-09:32 24.43 19.78 0.309881E+09 532.50 15-MAY-14:09 28.30 17.25
June 0.824629E+10 17090.83 25-JUN-10:02 29.50 22.85 0.312954E+09 524.26 02-JUN-12:39 29.50 22.85
July 0.866361E+10 17120.02 04-JUL-09:32 26.47 23.26 0.291769E+09 521.75 07-JUL-10:50 32.02 24.15
August 0.881585E+10 17004.03 06-AUG-11:02 30.68 23.75 0.326616E+09 521.84 01-AUG-10:50 30.68 23.75
September 0.620773E+10 14463.72 24-SEP-10:13 26.67 18.72 0.285219E+09 521.22 15-SEP-12:20 26.67 18.72
October 0.413295E+10 6658.27 11-OCT-10:20 23.73 19.29 0.276500E+09 521.21 05-OCT-12:09 23.73 19.29
November 0.279671E+10 3842.96 06-NOV-09:50 14.03 12.24 0.251225E+09 521.19 06-NOV-09:00 14.40 12.50
December 0.173012E+10 3836.87 01-DEC-10:45 3.95 0.75 0.225269E+09 482.51 13-DEC-11:00 20.00 17.41
                     
Annual Sum or Average 0.586620E+11         0.329826E+10        
Minimum of Months 0.982459E+09 2742.90   0.00 -3.9 0.219298E+09 456.90   14.40 12.02
Maximum of Months 0.881585E+10 17120.02   30.68 23.75 0.326616E+09 532.50   32.02 24.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.299807E+10 13959.58 26-JAN-13:38 0.00 -3.9 0.539137E+09 879.01 05-JAN-11:00 0.00 -3.9
February 0.384332E+10 17422.17 26-FEB-13:03 23.98 12.59 0.504068E+09 858.05 03-FEB-14:39 23.98 12.59
March 0.641754E+10 13246.66 30-MAR-13:30 27.25 18.02 0.652091E+09 846.84 30-MAR-13:00 27.80 17.87
April 0.656460E+10 14036.06 17-APR-15:00 28.90 16.41 0.593936E+09 876.12 14-APR-13:50 28.90 16.41
May 0.779806E+10 11273.90 15-MAY-14:10 28.30 17.25 0.656589E+09 867.68 15-MAY-13:39 28.30 17.25
June 0.948210E+10 17362.02 25-JUN-16:41 32.88 22.29 0.660313E+09 851.11 02-JUN-13:50 32.88 22.29
July 0.101214E+11 13970.14 15-JUL-03:02 23.90 20.50 0.614990E+09 845.76 14-JUL-13:39 23.90 20.50
August 0.118917E+11 18216.02 06-AUG-13:42 32.70 23.92 0.691271E+09 864.52 25-AUG-13:00 31.10 18.60
September 0.920950E+10 18435.74 24-SEP-12:53 28.90 19.89 0.609237E+09 863.14 22-SEP-13:39 28.90 19.89
October 0.787937E+10 19076.74 09-OCT-14:42 27.70 19.55 0.611522E+09 873.05 10-OCT-13:50 29.22 21.00
November 0.584994E+10 18440.17 11-NOV-13:43 21.10 11.67 0.593648E+09 845.94 06-NOV-14:20 21.10 11.67
December 0.438784E+10 11380.90 08-DEC-14:10 12.80 5.52 0.549948E+09 848.89 07-DEC-10:00 12.80 5.52
                     
Annual Sum or Average 0.864434E+11         0.727675E+10        
Minimum of Months 0.299807E+10 11273.90   0.00 -3.9 0.504068E+09 845.76   0.00 -3.9
Maximum of Months 0.118917E+11 19076.74   32.88 23.92 0.691271E+09 879.01   32.88 22.29



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.124280E+10 3545.37 05-JAN-16:33 1.47 -3.7 0.310690E+09 494.44 20-JAN-16:49 16.78 11.69
February 0.202275E+10 6558.40 27-FEB-17:00 22.20 11.44 0.296799E+09 544.94 28-FEB-14:39 25.00 13.71
March 0.440252E+10 9128.98 30-MAR-16:00 27.80 17.47 0.396248E+09 544.94 29-MAR-13:09 27.80 17.47
April 0.537510E+10 17015.57 09-APR-17:01 21.60 10.86 0.373824E+09 549.12 14-APR-13:50 27.12 15.42
May 0.678685E+10 17705.99 21-MAY-17:42 25.78 19.40 0.419508E+09 558.34 15-MAY-13:39 25.78 19.40
June 0.838579E+10 18723.39 25-JUN-16:41 32.88 22.29 0.425044E+09 545.38 02-JUN-13:50 32.88 22.29
July 0.886677E+10 18992.51 04-JUL-17:31 30.40 22.45 0.395995E+09 544.94 07-JUL-09:20 29.97 24.13
August 0.947011E+10 18642.02 06-AUG-17:01 32.20 23.07 0.445302E+09 544.95 25-AUG-13:09 30.18 18.86
September 0.638115E+10 12086.02 27-SEP-05:03 22.80 20.09 0.387641E+09 544.96 22-SEP-13:50 22.80 20.09
October 0.449813E+10 9329.71 11-OCT-16:00 26.10 17.12 0.371308E+09 544.94 16-OCT-13:50 24.90 19.07
November 0.314409E+10 6016.06 06-NOV-16:00 20.60 10.48 0.344765E+09 544.88 06-NOV-14:00 20.60 10.48
December 0.206152E+10 3710.80 13-DEC-06:03 16.70 15.65 0.313102E+09 542.28 12-DEC-14:00 16.70 15.65
                     
Annual Sum or Average 0.626376E+11         0.448023E+10        
Minimum of Months 0.124280E+10 3545.37   1.47 -3.7 0.296799E+09 494.44   16.70 10.48
Maximum of Months 0.947011E+10 18992.51   32.88 23.07 0.445302E+09 558.34   32.88 24.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.464405E+09 2784.04 20-JAN-17:00 16.70 11.48 0.469747E+09 755.82 20-JAN-14:00 16.70 11.48
February 0.114700E+10 3669.65 28-FEB-15:40 23.87 12.92 0.442768E+09 845.60 28-FEB-14:00 23.87 12.92
March 0.325773E+10 7047.72 30-MAR-16:00 27.80 17.47 0.582821E+09 845.60 28-MAR-13:09 27.80 17.47
April 0.441773E+10 7312.59 18-APR-14:20 26.67 16.26 0.561372E+09 845.64 12-APR-13:30 26.67 16.26
May 0.690883E+10 9408.12 30-MAY-15:00 30.60 21.44 0.648727E+09 845.66 19-MAY-13:50 30.60 21.44
June 0.976551E+10 13531.80 26-JUN-05:02 23.30 21.67 0.659802E+09 845.64 02-JUN-13:00 23.30 21.67
July 0.104047E+11 17321.87 23-JUL-17:01 29.82 23.13 0.614638E+09 845.60 03-JUL-13:20 29.82 23.13
August 0.108323E+11 17796.77 06-AUG-17:01 32.20 23.07 0.690454E+09 846.54 25-AUG-13:50 30.92 18.65
September 0.646571E+10 12892.92 27-SEP-05:03 22.80 20.09 0.599106E+09 845.64 22-SEP-13:00 22.80 20.09
October 0.355866E+10 6564.27 02-OCT-14:50 26.70 20.16 0.553587E+09 845.60 19-OCT-13:09 22.48 19.30
November 0.206672E+10 3619.81 04-NOV-05:02 16.60 15.28 0.499091E+09 839.58 03-NOV-13:00 16.60 15.28
December 0.928658E+09 3042.60 13-DEC-15:10 18.12 16.87 0.460319E+09 812.91 13-DEC-14:00 18.12 16.87
                     
Annual Sum or Average 0.602179E+11         0.678243E+10        
Minimum of Months 0.464405E+09 2784.04   16.60 11.48 0.442768E+09 755.82   16.60 11.48
Maximum of Months 0.108323E+11 17796.77   32.20 23.13 0.690454E+09 846.54   30.92 23.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.546216E+09 2421.86 31-JAN-17:00 19.40 13.37 0.302121E+09 462.34 31-JAN-14:00 19.40 13.37
February 0.131196E+10 3421.08 28-FEB-15:00 25.00 13.71 0.292285E+09 544.94 28-FEB-14:30 25.00 13.71
March 0.330507E+10 5339.66 30-MAR-11:00 22.20 17.83 0.391159E+09 544.97 08-MAR-10:00 22.20 17.83
April 0.472023E+10 9781.82 16-APR-09:53 22.20 14.59 0.375758E+09 544.97 12-APR-13:30 22.20 14.59
May 0.680887E+10 15897.72 07-MAY-09:53 25.00 20.03 0.420163E+09 545.00 11-MAY-09:00 17.20 13.27
June 0.883041E+10 16865.62 04-JUN-11:23 29.40 19.71 0.425847E+09 545.20 05-JUN-09:00 28.90 20.65
July 0.940981E+10 17123.55 23-JUL-08:22 25.30 22.43 0.395462E+09 545.28 05-JUL-09:39 25.30 22.43
August 0.958510E+10 17604.16 06-AUG-11:02 30.68 23.75 0.444556E+09 545.26 07-AUG-09:00 29.40 23.41
September 0.631132E+10 10041.68 08-SEP-09:40 26.83 22.22 0.386054E+09 545.24 08-SEP-09:50 27.02 22.34
October 0.360953E+10 6420.15 11-OCT-10:30 24.20 19.54 0.369491E+09 544.95 20-OCT-13:09 18.22 11.22
November 0.214872E+10 3377.36 04-NOV-05:02 16.60 15.28 0.325888E+09 531.64 06-NOV-10:00 17.20 13.02
December 0.107384E+10 2657.70 13-DEC-15:10 18.12 16.87 0.296877E+09 494.97 13-DEC-14:00 18.12 16.87
                     
Annual Sum or Average 0.576611E+11         0.442566E+10        
Minimum of Months 0.546216E+09 2421.86   16.60 13.37 0.292285E+09 462.34   17.20 11.22
Maximum of Months 0.958510E+10 17604.16   30.68 23.75 0.444556E+09 545.28   29.40 23.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.219310E+10 7336.26 11-JAN-14:50 6.70 2.05 0.517245E+09 845.64 27-JAN-14:39 3.53 -2.0
February 0.303194E+10 13498.14 21-FEB-14:30 22.25 10.82 0.484946E+09 845.79 21-FEB-14:00 22.80 11.27
March 0.564130E+10 13794.26 30-MAR-13:50 27.62 17.92 0.624355E+09 845.74 30-MAR-13:00 27.80 17.87
April 0.631444E+10 15200.04 17-APR-14:05 28.90 16.59 0.576373E+09 885.59 17-APR-13:00 28.90 16.59
May 0.803122E+10 11023.85 30-MAY-14:30 30.60 21.24 0.647771E+09 850.47 19-MAY-13:39 30.60 21.24
June 0.101650E+11 14042.79 29-JUN-05:03 22.20 20.68 0.657808E+09 845.66 02-JUN-13:00 22.20 20.68
July 0.110396E+11 19390.10 23-JUL-17:01 29.82 23.13 0.613911E+09 845.62 18-JUL-13:20 29.82 23.13
August 0.128680E+11 20533.56 06-AUG-13:42 32.70 23.92 0.690827E+09 852.95 25-AUG-13:00 31.10 18.60
September 0.935621E+10 20628.08 24-SEP-14:32 28.70 20.36 0.603140E+09 849.16 22-SEP-13:50 28.70 20.36
October 0.710447E+10 21119.79 09-OCT-14:32 27.60 19.53 0.591961E+09 850.55 10-OCT-13:50 29.22 21.00
November 0.477254E+10 17611.28 11-NOV-13:43 21.10 11.67 0.560496E+09 845.80 06-NOV-14:00 21.10 11.67
December 0.326162E+10 9880.06 12-DEC-13:50 22.52 17.00 0.521502E+09 846.60 04-DEC-14:20 22.52 17.00
                     
Annual Sum or Average 0.837795E+11         0.709033E+10        
Minimum of Months 0.219310E+10 7336.26   6.70 2.05 0.484946E+09 845.62   3.53 -2.0
Maximum of Months 0.128680E+11 21119.79   32.70 23.92 0.690827E+09 885.59   31.10 23.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.877709E+09 3048.51 20-JAN-16:40 16.87 11.91 0.304959E+09 484.10 20-JAN-16:49 16.78 11.69
February 0.159166E+10 6289.79 27-FEB-17:00 22.20 11.44 0.288680E+09 544.48 28-FEB-14:00 25.00 13.71
March 0.393018E+10 9560.51 30-MAR-16:00 27.80 17.47 0.378296E+09 544.93 09-MAR-14:50 27.80 17.47
April 0.520853E+10 17582.73 09-APR-17:33 21.30 11.08 0.361176E+09 544.97 12-APR-13:30 28.35 16.82
May 0.698372E+10 19310.26 21-MAY-17:42 25.78 19.40 0.412545E+09 552.32 16-MAY-15:00 25.78 19.40
June 0.887383E+10 20179.44 11-JUN-17:12 32.20 20.99 0.422986E+09 544.97 02-JUN-13:00 32.20 20.99
July 0.955421E+10 20520.56 23-JUL-17:01 29.82 23.13 0.394899E+09 544.94 03-JUL-13:09 29.82 23.13
August 0.101722E+11 20643.38 06-AUG-17:01 32.20 23.07 0.444624E+09 547.14 25-AUG-13:50 30.92 18.65
September 0.649339E+10 15117.86 03-SEP-15:32 29.80 23.28 0.381436E+09 544.96 22-SEP-13:00 26.70 17.59
October 0.405670E+10 10863.14 09-OCT-16:33 27.07 19.44 0.356762E+09 544.93 19-OCT-13:09 22.48 19.30
November 0.255680E+10 5661.05 06-NOV-16:10 20.32 10.34 0.327183E+09 544.82 06-NOV-14:00 20.32 10.34
December 0.143453E+10 3192.92 12-DEC-14:50 22.80 16.32 0.301938E+09 522.11 12-DEC-14:00 22.80 16.17
                     
Annual Sum or Average 0.617335E+11         0.437548E+10        
Minimum of Months 0.877709E+09 3048.51   16.87 10.34 0.288680E+09 484.10   16.78 10.34
Maximum of Months 0.101722E+11 20643.38   32.20 23.28 0.444624E+09 552.32   32.20 23.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.108382E+10 4952.59 02-JAN-06:08 3.30 2.54 0.00 0.00 01-JAN-00:10 3.30 2.54
February 0.209277E+10 5638.68 21-FEB-06:15 5.60 3.82 0.00 0.00 01-FEB-00:10 5.60 3.82
March 0.515601E+10 7023.93 13-MAR-05:15 6.70 2.88 0.00 0.00 01-MAR-00:10 6.70 2.88
April 0.649359E+10 8310.96 17-APR-13:10 27.98 16.86 0.00 0.00 01-APR-00:10 27.98 16.86
May 0.751225E+10 10962.25 30-MAY-05:15 19.07 17.52 0.00 0.00 01-MAY-00:10 19.07 17.52
June 0.971613E+10 11125.54 26-JUN-05:15 23.30 21.67 0.00 0.00 01-JUN-00:10 23.30 21.67
July 0.106680E+11 10602.35 03-JUL-05:15 17.97 16.43 0.00 0.00 01-JUL-00:10 17.97 16.43
August 0.121473E+11 13408.52 14-AUG-05:15 23.30 20.62 0.00 0.00 01-AUG-00:10 23.30 20.62
September 0.800264E+10 12465.49 05-SEP-05:13 21.70 20.50 0.00 0.00 01-SEP-00:10 21.70 20.50
October 0.593327E+10 10779.22 10-OCT-05:13 15.73 14.81 0.00 0.00 01-OCT-00:10 15.73 14.81
November 0.435774E+10 8321.76 06-NOV-06:15 9.23 8.65 0.00 0.00 01-NOV-00:10 9.23 8.65
December 0.271026E+10 6830.15 13-DEC-06:13 16.70 15.65 0.00 0.00 01-DEC-00:10 16.70 15.65
                     
Annual Sum or Average 0.758738E+11         0.00        
Minimum of Months 0.108382E+10 4952.59   3.30 2.54 0.00 0.00   3.30 2.54
Maximum of Months 0.121473E+11 13408.52   27.98 21.67 0.00 0.00   27.98 21.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.306373E+09 5428.65 27-JAN-05:01 -5.7 -7.2 0.00 0.00 01-JAN-00:10 -5.7 -7.2
February 0.896636E+09 7959.34 12-FEB-05:22 -11.9 -13.2 0.00 0.00 01-FEB-00:10 -11.9 -13.2
March 0.278789E+10 5057.09 15-MAR-05:10 8.22 4.19 0.00 0.00 01-MAR-00:10 8.22 4.19
April 0.414831E+10 6190.98 17-APR-14:55 28.90 16.41 0.00 0.00 01-APR-00:10 28.90 16.41
May 0.593409E+10 8380.49 30-MAY-05:03 18.68 17.36 0.00 0.00 01-MAY-00:10 18.68 17.36
June 0.795831E+10 8555.02 26-JUN-05:02 23.30 21.67 0.00 0.00 01-JUN-00:10 23.30 21.67
July 0.845242E+10 8253.65 24-JUL-05:03 20.60 19.50 0.00 0.00 01-JUL-00:10 20.60 19.50
August 0.924996E+10 8598.77 30-AUG-05:15 20.60 19.07 0.00 0.00 01-AUG-00:10 20.60 19.07
September 0.645393E+10 7897.84 05-SEP-05:13 21.70 20.50 0.00 0.00 01-SEP-00:10 21.70 20.50
October 0.367909E+10 5509.33 11-OCT-05:15 18.53 16.62 0.00 0.00 01-OCT-00:10 18.53 16.62
November 0.188080E+10 4766.87 21-NOV-05:01 -2.3 -3.6 0.00 0.00 01-NOV-00:10 -2.3 -3.6
December 0.850935E+09 5236.77 18-DEC-05:01 -5.0 -6.8 0.00 0.00 01-DEC-00:10 -5.0 -6.8
                     
Annual Sum or Average 0.525987E+11         0.00        
Minimum of Months 0.306373E+09 4766.87   -11.9 -13.2 0.00 0.00   -11.9 -13.2
Maximum of Months 0.924996E+10 8598.77   28.90 21.67 0.00 0.00   28.90 21.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.123850E+09 2134.95 31-JAN-17:30 19.15 13.30 0.00 0.00 01-JAN-00:10 19.15 13.30
February 0.763667E+09 7167.35 28-FEB-16:00 23.30 12.53 0.00 0.00 01-FEB-00:10 23.30 12.53
March 0.309008E+10 13968.58 30-MAR-15:30 27.80 17.27 0.00 0.00 01-MAR-00:10 27.80 17.27
April 0.593093E+10 18712.52 17-APR-14:55 28.90 16.41 0.00 0.00 01-APR-00:10 28.90 16.41
May 0.973675E+10 19033.05 16-MAY-15:23 29.40 17.75 0.00 0.00 01-MAY-00:10 29.40 17.75
June 0.137442E+11 19401.19 12-JUN-15:00 33.30 22.72 0.00 0.00 01-JUN-00:10 33.30 22.72
July 0.145465E+11 21473.12 07-JUL-15:10 35.10 23.86 0.00 0.00 01-JUL-00:10 35.10 23.86
August 0.153230E+11 20461.65 01-AUG-14:20 34.27 23.72 0.00 0.00 01-AUG-00:10 34.27 23.72
September 0.838100E+10 16953.81 06-SEP-14:40 29.97 23.06 0.00 0.00 01-SEP-00:10 29.97 23.06
October 0.385387E+10 12443.83 10-OCT-14:50 28.98 20.71 0.00 0.00 01-OCT-00:10 28.98 20.71
November 0.122420E+10 5739.47 06-NOV-15:10 20.60 10.48 0.00 0.00 01-NOV-00:10 20.60 10.48
December 0.261990E+09 4145.75 12-DEC-14:40 22.80 16.47 0.00 0.00 01-DEC-00:10 22.80 16.47
                     
Annual Sum or Average 0.769800E+11         0.00        
Minimum of Months 0.123850E+09 2134.95   19.15 10.48 0.00 0.00   19.15 10.48
Maximum of Months 0.153230E+11 21473.12   35.10 23.86 0.00 0.00   35.10 23.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.291193E+10 1859.89 23-JAN-17:00 10.00 3.54 95230847.30 126.84 19-JAN-10:30 10.00 3.54
February 0.776375E+10 3895.39 24-FEB-17:50 15.18 6.70 86397290.95 126.84 17-FEB-14:00 15.18 6.70
March 0.144246E+11 7173.25 31-MAR-24:00 12.10 7.93 0.103239E+09 126.84 28-MAR-09:09 12.10 7.93
April 0.189561E+11 7885.44 09-APR-18:13 19.80 10.92 91606058.19 126.83 03-APR-09:39 19.80 10.92
May 0.455249E+10 3499.96 31-MAY-24:00 21.00 18.72 99242597.79 126.86 01-MAY-13:09 21.00 18.72
June 0.939732E+10 5356.39 30-JUN-24:00 22.30 21.46 98974624.41 126.86 23-JUN-09:50 22.30 21.46
July 0.147720E+11 7236.04 31-JUL-23:53 25.20 21.98 91891602.75 126.85 26-JUL-09:09 25.20 21.98
August 0.198827E+11 7861.64 13-AUG-19:32 29.60 21.73 0.104648E+09 134.91 02-AUG-13:00 29.60 21.73
September 0.446834E+10 3247.60 30-SEP-24:00 16.80 15.75 91612159.65 126.86 01-SEP-13:00 16.80 15.75
October 0.945419E+10 5166.67 31-OCT-24:00 9.70 6.26 95238525.68 126.86 18-OCT-09:00 9.70 6.26
November 0.138916E+11 5914.96 06-NOV-17:00 18.90 9.61 94302033.48 126.84 02-NOV-09:20 18.90 9.61
December 0.191106E+11 7699.27 19-DEC-17:00 13.90 5.19 91881319.07 126.83 06-DEC-14:00 13.90 5.19
                     
Annual Sum or Average 0.139585E+12         0.114426E+10        
Minimum of Months 0.291193E+10 1859.89   9.70 3.54 86397290.95 126.83   9.70 3.54
Maximum of Months 0.198827E+11 7885.44   29.60 21.98 0.104648E+09 134.91   29.60 21.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.979315E+09 1527.92 27-JAN-17:00 4.40 -1.6 95039361.33 126.83 20-JAN-14:09 4.40 -1.6
February 0.588230E+10 3616.38 24-FEB-17:50 15.18 6.70 86397236.72 126.84 17-FEB-14:00 15.18 6.70
March 0.129876E+11 6725.37 31-MAR-24:00 12.10 7.93 0.103239E+09 126.84 31-MAR-13:09 12.10 7.93
April 0.177621E+11 7351.78 14-APR-18:20 23.90 15.14 91606169.94 126.83 03-APR-13:00 23.90 15.14
May 0.408230E+10 3309.83 31-MAY-24:00 21.00 18.72 99238714.04 126.85 30-MAY-13:00 21.00 18.72
June 0.888930E+10 5146.10 30-JUN-24:00 22.30 21.46 98974487.92 126.86 26-JUN-13:00 22.30 21.46
July 0.140648E+11 7016.36 31-JUL-23:53 25.20 21.98 91892752.90 126.85 26-JUL-09:09 25.20 21.98
August 0.188977E+11 7416.96 13-AUG-18:35 30.37 21.91 0.104752E+09 135.65 02-AUG-13:00 30.37 21.91
September 0.395458E+10 2744.13 30-SEP-24:00 16.80 15.75 91609436.37 126.85 25-SEP-09:00 16.80 15.75
October 0.823541E+10 4483.19 31-OCT-24:00 9.70 6.26 95237747.13 126.86 18-OCT-13:30 9.70 6.26
November 0.120761E+11 5514.27 06-NOV-17:00 18.90 9.61 94301926.04 126.83 03-NOV-13:50 18.90 9.61
December 0.162967E+11 7111.63 08-DEC-17:00 11.10 4.72 91881379.77 126.83 13-DEC-14:30 18.30 16.86
                     
Annual Sum or Average 0.124108E+12         0.114417E+10        
Minimum of Months 0.979315E+09 1527.92   4.40 -1.6 86397236.72 126.83   4.40 -1.6
Maximum of Months 0.188977E+11 7416.96   30.37 21.98 0.104752E+09 135.65   30.37 21.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.438461E+09 1531.88 20-JAN-17:00 16.70 11.48 92542061.07 127.72 24-JAN-10:30 6.10 2.41
February 0.465852E+10 3626.26 28-FEB-17:00 23.90 12.94 86396601.44 126.84 17-FEB-14:00 23.90 12.94
March 0.121965E+11 6464.41 31-MAR-23:20 12.23 7.91 0.103239E+09 126.84 31-MAR-13:09 12.23 7.91
April 0.173732E+11 7415.28 14-APR-18:20 23.90 15.14 91606262.87 126.83 03-APR-09:50 23.90 15.14
May 0.398559E+10 3262.56 31-MAY-24:00 21.00 18.72 99239842.07 126.86 30-MAY-13:50 21.00 18.72
June 0.893478E+10 5120.83 30-JUN-24:00 22.30 21.46 98974858.25 126.86 26-JUN-13:39 22.30 21.46
July 0.141390E+11 7047.42 31-JUL-23:53 25.20 21.98 91892406.74 126.85 26-JUL-09:09 25.20 21.98
August 0.189796E+11 7566.92 13-AUG-19:32 29.60 21.73 0.104613E+09 135.84 02-AUG-13:00 29.60 21.73
September 0.381719E+10 2278.30 30-SEP-24:00 16.80 15.75 91609511.41 126.85 25-SEP-09:00 16.80 15.75
October 0.752545E+10 4048.28 31-OCT-23:20 9.63 5.89 95237747.43 126.86 18-OCT-13:00 9.63 5.89
November 0.108707E+11 5502.06 06-NOV-17:00 18.90 9.61 94301944.14 126.83 03-NOV-13:50 18.90 9.61
December 0.145013E+11 7028.82 07-DEC-17:00 14.40 6.55 91881432.71 126.83 13-DEC-14:20 18.30 16.86
                     
Annual Sum or Average 0.117420E+12         0.114153E+10        
Minimum of Months 0.438461E+09 1531.88   9.63 5.89 86396601.44 126.83   6.10 2.41
Maximum of Months 0.189796E+11 7566.92   29.60 21.98 0.104613E+09 135.84   29.60 21.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.235935E+12 91570.43 20-JAN-17:00 16.70 11.48 0.206172E+10 2747.27 12-JAN-10:00 16.70 11.48
February 0.433456E+12 183221.00 28-FEB-17:00 23.90 12.94 0.187076E+10 2748.93 09-FEB-14:50 23.90 12.94
March 0.726828E+12 357933.25 31-MAR-24:00 12.10 7.93 0.223509E+10 2747.32 20-MAR-13:09 12.10 7.93
April 0.938478E+12 365785.66 20-APR-15:30 24.15 16.80 0.200694E+10 3014.81 12-APR-13:00 24.15 16.80
May 0.239222E+12 175217.85 31-MAY-24:00 21.00 18.72 0.214857E+10 2746.59 31-MAY-13:00 21.00 18.72
June 0.469340E+12 267283.91 30-JUN-24:00 22.30 21.46 0.214258E+10 2746.33 26-JUN-09:00 22.30 21.46
July 0.731188E+12 359513.21 31-JUL-23:53 25.20 21.98 0.198919E+10 2745.89 26-JUL-09:09 25.20 21.98
August 0.972528E+12 370334.94 07-AUG-21:12 22.60 21.54 0.254970E+10 3595.50 18-AUG-13:50 33.48 22.91
September 0.236656E+12 175586.24 30-SEP-24:00 16.80 15.75 0.198355E+10 2746.99 28-SEP-13:00 16.80 15.75
October 0.488015E+12 268167.23 31-OCT-24:00 9.70 6.26 0.206165E+10 2746.39 18-OCT-13:30 9.70 6.26
November 0.709162E+12 277199.09 06-NOV-17:00 18.90 9.61 0.204177E+10 2747.81 22-NOV-14:09 11.28 3.90
December 0.975567E+12 368140.31 12-DEC-17:00 21.70 16.13 0.198971E+10 2748.50 04-DEC-14:09 21.70 16.13
                     
Annual Sum or Average 0.715638E+13         0.250812E+11        
Minimum of Months 0.235935E+12 91570.43   9.70 6.26 0.187076E+10 2745.89   9.70 3.90
Maximum of Months 0.975567E+12 370334.94   25.20 21.98 0.254970E+10 3595.50   33.48 22.91



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.259752E+09 12022.25 02-JAN-04:05 3.30
February 0.142423E+09 12037.83 23-FEB-05:05 6.02
March 0.202331E+09 13835.93 23-MAR-04:53 6.10
April 0.233635E+09 14124.37 07-APR-04:53 3.30
May 0.309426E+09 15595.64 06-MAY-16:03 29.63
June 0.355816E+09 20776.37 24-JUN-16:02 33.22
July 0.472346E+09 25322.00 08-JUL-16:02 36.32
August 0.449670E+09 19424.60 19-AUG-16:02 32.33
September 0.452001E+09 14159.81 27-SEP-03:53 22.80
October 0.481698E+09 12200.68 31-OCT-03:15 8.90
November 0.437340E+09 12100.77 07-NOV-04:05 7.12
December 0.342092E+09 11761.63 27-DEC-04:03 2.20
         
Annual Sum or Average 0.413853E+10      
Minimum of Months 0.142423E+09 11761.63   2.20
Maximum of Months 0.481698E+09 25322.00   36.32



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.70
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.80
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 39148603.42 40137.59 09-JAN-05:01 -2.2
February 36398800.54 38964.27 13-FEB-06:01 -5.6
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 620938.20 1938.51 18-DEC-09:53 0.60
         
Annual Sum or Average 76168342.16      
Minimum of Months 0.00 0.00   -5.6
Maximum of Months 39148603.42 40137.59   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.265402E+10 79161.57 09-JAN-04:01 -1.8
February 0.124417E+10 78451.83 13-FEB-04:01 -5.0
March 4576127.46 30507.52 20-MAR-05:03 5.00
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 31899044.78 64663.39 22-NOV-06:01 -3.3
December 0.124402E+10 75214.29 04-DEC-04:01 -2.3
         
Annual Sum or Average 0.517869E+10      
Minimum of Months 0.00 0.00   -5.0
Maximum of Months 0.265402E+10 79161.57   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.153234E+09 11789.98 09-JAN-05:01 -2.2
February 60197706.91 11825.81 13-FEB-05:02 -5.1
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 89916.36 1198.88 22-NOV-06:01 -3.3
December 879907.34 9347.09 18-DEC-06:01 -5.0
         
Annual Sum or Average 0.214402E+09      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.153234E+09 11825.81   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.116911E+09 9331.22 09-JAN-05:01 -2.2
February 39565983.55 9385.86 13-FEB-05:02 -5.1
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 1244650.72 6622.91 21-NOV-06:01 -2.8
December 6269672.68 7882.03 18-DEC-06:01 -5.0
         
Annual Sum or Average 0.163991E+09      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.116911E+09 9385.86   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.201197E+09 14343.34 09-JAN-05:01 -2.2
February 74243827.10 13757.89 13-FEB-05:02 -5.1
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 1388188.29 10853.67 21-NOV-06:01 -2.8
December 12560218.13 12014.75 01-DEC-06:01 -3.9
         
Annual Sum or Average 0.289389E+09      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.201197E+09 14343.34   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6921788.83 6995.12 09-JAN-06:01 -2.4
February 894132.59 7001.06 13-FEB-06:01 -5.6
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 7815921.42      
Minimum of Months 0.00 0.00   -5.6
Maximum of Months 6921788.83 7001.06   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.249295E+10 13320.48 09-JAN-04:01 -1.8
February 0.136041E+10 13683.59 12-FEB-05:22 -11.9
March 33931091.05 10555.51 18-MAR-05:03 3.22
April 5383188.05 9603.85 06-APR-05:02 0.18
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 9233141.78 10518.14 26-OCT-05:03 2.20
November 0.165725E+09 11730.83 22-NOV-05:01 -2.9
December 0.897145E+09 12580.21 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.496477E+10      
Minimum of Months 0.00 0.00   -11.9
Maximum of Months 0.249295E+10 13683.59   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.135309E+10 13874.58 09-JAN-04:01 -1.8
February 0.665864E+09 14215.54 12-FEB-05:22 -11.9
March 18927289.47 10386.53 18-MAR-05:03 3.22
April 2226767.41 5680.40 06-APR-05:02 0.18
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 6199057.34 7961.04 26-OCT-05:03 2.20
November 71508729.78 12004.18 22-NOV-05:01 -2.9
December 0.433004E+09 12830.24 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.255082E+10      
Minimum of Months 0.00 0.00   -11.9
Maximum of Months 0.135309E+10 14215.54   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.118891E+10 15206.81 09-JAN-04:01 -1.8
February 0.576922E+09 15482.26 12-FEB-05:22 -11.9
March 10012172.27 12046.12 22-MAR-05:03 6.02
April 305938.63 2484.58 06-APR-05:02 0.18
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 209636.86 1397.58 31-OCT-05:03 8.30
November 58765446.94 12973.89 21-NOV-05:01 -2.3
December 0.343074E+09 13718.37 26-DEC-05:01 3.80
         
Annual Sum or Average 0.217820E+10      
Minimum of Months 0.00 0.00   -11.9
Maximum of Months 0.118891E+10 15482.26   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100948E+10 14495.08 09-JAN-04:01 -1.8
February 0.501076E+09 14420.75 13-FEB-04:01 -5.0
March 3683368.85 7788.14 22-MAR-05:03 6.02
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 350903.91 1701.22 26-OCT-05:03 2.20
November 62331813.91 12593.31 22-NOV-05:01 -2.9
December 0.318706E+09 13080.78 26-DEC-05:01 3.80
         
Annual Sum or Average 0.189563E+10      
Minimum of Months 0.00 0.00   -5.0
Maximum of Months 0.100948E+10 14495.08   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.669141E+10 15901.79 09-JAN-03:53 -1.7
February 0.381432E+10 16683.35 12-FEB-05:22 -11.9
March 0.446771E+09 13485.55 20-MAR-04:01 6.42
April 0.117368E+09 12995.58 06-APR-04:02 0.92
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.173238E+09 13263.62 26-OCT-04:02 2.70
November 0.109833E+10 14818.34 22-NOV-04:01 -2.8
December 0.361623E+10 15464.87 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.159577E+11      
Minimum of Months 0.00 0.00   -11.9
Maximum of Months 0.669141E+10 16683.35   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.351592E+10 14778.53 08-JAN-02:32 -5.6
February 0.195464E+10 15585.64 12-FEB-05:22 -11.9
March 0.202260E+09 12574.66 22-MAR-04:01 6.60
April 47939152.43 11962.19 06-APR-04:02 0.92
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.100063E+09 12334.92 26-OCT-04:02 2.70
November 0.480119E+09 13652.49 22-NOV-04:01 -2.8
December 0.175596E+10 14456.48 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.805690E+10      
Minimum of Months 0.00 0.00   -11.9
Maximum of Months 0.351592E+10 15585.64   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.369101E+10 17704.76 09-JAN-03:53 -1.7
February 0.208486E+10 18636.17 12-FEB-05:22 -11.9
March 0.217285E+09 14929.40 22-MAR-04:01 6.60
April 73313395.81 14190.91 06-APR-04:02 0.92
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.109167E+09 14234.58 30-OCT-04:03 8.90
November 0.443106E+09 16004.14 21-NOV-04:02 -1.8
December 0.170426E+10 17192.22 26-DEC-04:11 3.90
         
Annual Sum or Average 0.832300E+10      
Minimum of Months 0.00 0.00   -11.9
Maximum of Months 0.369101E+10 18636.17   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.299503E+10 16200.33 09-JAN-03:53 -1.7
February 0.154336E+10 17046.92 12-FEB-05:22 -11.9
March 0.115600E+09 13683.49 22-MAR-04:01 6.60
April 29051402.95 11190.46 06-APR-05:02 0.18
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 56119825.19 11694.09 25-OCT-05:02 9.90
November 0.399030E+09 14939.92 22-NOV-04:01 -2.8
December 0.131044E+10 15855.58 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.644863E+10      
Minimum of Months 0.00 0.00   -11.9
Maximum of Months 0.299503E+10 17046.92   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.457612E+09 12899.86 17-JAN-06:01 4.72
February 0.302674E+09 12483.68 10-FEB-05:07 5.10
March 0.100803E+09 10082.76 27-MAR-03:02 10.50
April 0.121384E+09 10405.28 04-APR-03:02 15.10
May 65864587.94 8905.58 01-MAY-03:02 16.27
June 70841928.32 7724.01 16-JUN-03:02 21.02
July 74864136.24 8400.06 29-JUL-03:02 17.70
August 47057287.54 4680.53 27-AUG-15:02 31.70
September 67335868.57 7686.52 18-SEP-03:02 15.00
October 92123722.98 11728.60 02-OCT-03:02 19.82
November 0.111363E+09 12197.76 24-NOV-04:03 8.90
December 90797319.24 13723.34 26-DEC-04:03 3.90
         
Annual Sum or Average 0.160272E+10      
Minimum of Months 47057287.54 4680.53   3.90
Maximum of Months 0.457612E+09 13723.34   31.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.244381E+10 14027.70 05-JAN-11:33 0.03
February 0.122297E+10 10192.73 03-FEB-13:20 -0.7
March 81619019.66 8022.62 21-MAR-05:03 11.52
April 47483679.50 8195.46 03-APR-04:03 20.22
May 54828742.51 7543.25 01-MAY-03:02 16.27
June 40900173.80 6771.24 14-JUN-03:02 22.62
July 43611559.04 7255.78 31-JUL-03:02 21.60
August 39082799.03 7180.88 01-AUG-03:02 24.15
September 44667872.81 6534.38 25-SEP-03:02 20.10
October 63780917.42 7881.91 25-OCT-05:02 9.90
November 0.155972E+09 8544.03 28-NOV-06:03 11.52
December 0.976193E+09 8048.98 12-DEC-06:03 12.70
         
Annual Sum or Average 0.521493E+10      
Minimum of Months 39082799.03 6534.38   -0.7
Maximum of Months 0.244381E+10 14027.70   24.15



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.931608E+10 24348.92 09-JAN-05:18 -2.2
February 0.563225E+10 25574.28 13-FEB-05:32 -5.4
March 0.151926E+10 16194.31 01-MAR-06:03 8.40
April 0.732236E+09 17868.07 25-APR-05:03 9.40
May 0.214955E+09 18902.18 11-MAY-05:02 8.22
June 0.109154E+09 16231.79 08-JUN-05:03 11.70
July 64504434.44 10578.48 03-JUL-03:02 17.80
August 51098492.63 9960.65 28-AUG-03:02 21.60
September 0.167868E+09 15706.63 29-SEP-05:03 12.30
October 0.113691E+10 17158.11 20-OCT-05:03 9.90
November 0.245286E+10 14470.87 22-NOV-06:13 -3.3
December 0.564384E+10 23801.61 18-DEC-05:33 -5.0
         
Annual Sum or Average 0.270410E+11      
Minimum of Months 51098492.63 9960.65   -5.4
Maximum of Months 0.931608E+10 25574.28   21.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.70
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.80
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.241339E+09 535.69 08-JAN-01:40 -5.8
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.241339E+09      
Minimum of Months 0.00 0.00   -5.8
Maximum of Months 0.241339E+09 535.69   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.651424E+09 579.25 15-JAN-19:00 3.90
February 42996212.39 535.43 12-FEB-07:45 -12.3
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.694420E+09      
Minimum of Months 0.00 0.00   -12.3
Maximum of Months 0.651424E+09 579.25   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.70
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:02 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:02 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.80
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.200626E+11 20994.62 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.181982E+11 20994.62 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.216246E+11 20994.62 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.193152E+11 20994.62 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.208436E+11 20994.62 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.207428E+11 20994.62 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.194159E+11 20994.62 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.216246E+11 20994.62 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.193152E+11 20994.62 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.200626E+11 20994.62 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.198274E+11 20994.62 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.194159E+11 20994.62 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.240449E+12     0.424397E+12    
Minimum of Months 0.181982E+11 20994.62   0.325565E+11 13457.54  
Maximum of Months 0.216246E+11 20994.62   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.180176E+11 18854.65 02-JAN-08:09 0.270551E+11 18128.59 02-JAN-08:09
February 0.163433E+11 18854.65 01-FEB-08:09 0.244881E+11 18128.59 01-FEB-08:09
March 0.194204E+11 18854.65 01-MAR-08:09 0.280558E+11 18128.59 01-MAR-08:09
April 0.173464E+11 18854.65 03-APR-07:10 0.261305E+11 18128.59 03-APR-07:10
May 0.187190E+11 18854.65 01-MAY-07:10 0.275555E+11 18128.59 01-MAY-07:10
June 0.186285E+11 18854.65 01-JUN-07:10 0.270261E+11 18128.59 01-JUN-07:10
July 0.174369E+11 18854.65 03-JUL-07:10 0.266527E+11 18128.59 03-JUL-07:10
August 0.194204E+11 18854.65 01-AUG-07:10 0.280558E+11 18128.59 01-AUG-07:10
September 0.173464E+11 18854.65 01-SEP-07:10 0.261160E+11 18128.59 01-SEP-07:10
October 0.180176E+11 18854.65 02-OCT-07:10 0.270624E+11 18128.59 02-OCT-07:10
November 0.178064E+11 18854.65 01-NOV-07:10 0.264424E+11 18128.59 01-NOV-07:10
December 0.174369E+11 18854.65 01-DEC-08:09 0.266454E+11 18128.59 01-DEC-08:09
             
Annual Sum or Average 0.215940E+12     0.321286E+12    
Minimum of Months 0.163433E+11 18854.65   0.244881E+11 18128.59  
Maximum of Months 0.194204E+11 18854.65   0.280558E+11 18128.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.180176E+11 18854.65 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.163433E+11 18854.65 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.194204E+11 18854.65 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.173464E+11 18854.65 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.187190E+11 18854.65 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.186285E+11 18854.65 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.174369E+11 18854.65 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.194204E+11 18854.65 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.173464E+11 18854.65 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.180176E+11 18854.65 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.178064E+11 18854.65 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.174369E+11 18854.65 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.215940E+12     0.321285E+12    
Minimum of Months 0.163433E+11 18854.65   0.244880E+11 18128.52  
Maximum of Months 0.194204E+11 18854.65   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.180176E+11 18854.65 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.163433E+11 18854.65 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.194204E+11 18854.65 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.173464E+11 18854.65 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.187190E+11 18854.65 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.186285E+11 18854.65 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.174369E+11 18854.65 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.194204E+11 18854.65 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.173464E+11 18854.65 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.180176E+11 18854.65 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.178064E+11 18854.65 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.174369E+11 18854.65 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.215940E+12     0.321285E+12    
Minimum of Months 0.163433E+11 18854.65   0.244880E+11 18128.52  
Maximum of Months 0.194204E+11 18854.65   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.166997E+10 2217.83 03-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.151325E+10 2318.86 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.167794E+10 2230.65 21-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.146459E+10 2078.82 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.155027E+10 1626.14 24-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.153128E+10 1454.29 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.144454E+10 1766.67 27-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.162533E+10 2008.73 24-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.149135E+10 2143.20 29-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.163458E+10 2363.15 30-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.162553E+10 2341.95 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.162874E+10 2221.92 06-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.188574E+11     0.403423E+11    
Minimum of Months 0.144454E+10 1454.29   0.307485E+10 2276.32  
Maximum of Months 0.167794E+10 2363.15   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105497E+10 1409.07 03-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.954609E+09 1494.36 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.107397E+10 1427.69 21-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.944524E+09 1302.63 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.100328E+10 937.20 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.992018E+09 937.20 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.934583E+09 1055.50 27-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.104940E+10 1254.33 24-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.957652E+09 1356.03 29-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.102890E+10 1522.90 30-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.103648E+10 1500.56 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.102713E+10 1411.95 06-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.120575E+11     0.259981E+11    
Minimum of Months 0.934583E+09 937.20   0.198155E+10 1466.95  
Maximum of Months 0.107397E+10 1522.90   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.160508E+10 2196.45 03-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.145987E+10 2318.91 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.166544E+10 2228.45 21-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.146823E+10 2084.50 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.155963E+10 1746.80 24-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.154193E+10 1629.84 23-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.145496E+10 1835.92 27-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.163024E+10 2024.82 24-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.148738E+10 2130.41 29-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.158236E+10 2363.20 30-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.157840E+10 2333.33 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.155932E+10 2198.55 06-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.185929E+11     0.403429E+11    
Minimum of Months 0.145496E+10 1629.84   0.307490E+10 2276.35  
Maximum of Months 0.166544E+10 2363.20   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105686E+10 1433.50 03-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.963790E+09 1494.36 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.108405E+10 1443.43 21-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.948947E+09 1366.10 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.100522E+10 1266.53 24-MAY-07:30 0.222974E+10 1466.94 01-MAY-07:10
June 0.992378E+09 1119.04 23-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.937768E+09 1225.96 27-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.105257E+10 1327.51 24-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.966316E+09 1392.40 29-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.104697E+10 1522.90 30-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.103093E+10 1511.05 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.102666E+10 1435.03 06-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.121125E+11     0.259979E+11    
Minimum of Months 0.937768E+09 1119.04   0.198154E+10 1466.94  
Maximum of Months 0.108405E+10 1522.90   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.167367E+10 2222.17 03-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.151672E+10 2320.29 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.167969E+10 2234.71 21-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.146568E+10 2087.33 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.155091E+10 1646.65 24-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.153171E+10 1454.29 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.144532E+10 1784.22 27-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.162653E+10 2019.30 24-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.149291E+10 2149.80 29-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.163661E+10 2363.27 30-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.162888E+10 2342.66 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.163284E+10 2226.11 06-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.188815E+11     0.403423E+11    
Minimum of Months 0.144532E+10 1454.29   0.307485E+10 2276.32  
Maximum of Months 0.167969E+10 2363.27   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105625E+10 1410.52 03-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.955139E+09 1494.59 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.107444E+10 1428.82 21-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.944900E+09 1306.19 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.100349E+10 937.20 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.992188E+09 937.20 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.934786E+09 1062.47 27-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.104965E+10 1258.36 24-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.958106E+09 1358.15 29-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.102926E+10 1522.92 30-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.103703E+10 1500.98 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.102769E+10 1413.34 06-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.120629E+11     0.259981E+11    
Minimum of Months 0.934786E+09 937.20   0.198155E+10 1466.95  
Maximum of Months 0.107444E+10 1522.92   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.160919E+10 2201.81 03-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.146171E+10 2320.34 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.166663E+10 2232.60 21-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.146915E+10 2092.76 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.156076E+10 1763.21 24-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.154279E+10 1650.07 23-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.145609E+10 1850.90 27-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.163126E+10 2034.74 24-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.148841E+10 2137.58 29-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.158565E+10 2363.32 30-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.157959E+10 2334.43 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.156084E+10 2203.86 06-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.186121E+11     0.403429E+11    
Minimum of Months 0.145609E+10 1650.07   0.307490E+10 2276.35  
Maximum of Months 0.166663E+10 2363.32   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105727E+10 1434.22 03-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.963950E+09 1494.59 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.108455E+10 1444.03 21-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.949366E+09 1367.28 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.100561E+10 1268.01 24-MAY-07:30 0.222974E+10 1466.94 01-MAY-07:10
June 0.992613E+09 1121.93 23-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.937996E+09 1228.19 27-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.105291E+10 1328.97 24-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.966902E+09 1393.40 29-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.104722E+10 1522.92 30-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.103140E+10 1511.17 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.102729E+10 1435.74 06-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.121171E+11     0.259979E+11    
Minimum of Months 0.937996E+09 1121.93   0.198154E+10 1466.94  
Maximum of Months 0.108455E+10 1522.92   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.167369E+10 2222.03 03-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.151670E+10 2320.24 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.167970E+10 2234.58 21-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.146569E+10 2087.09 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.155090E+10 1646.39 24-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.153171E+10 1454.29 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.144531E+10 1783.80 27-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.162652E+10 2019.00 24-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.149291E+10 2149.60 29-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.163661E+10 2363.27 30-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.162890E+10 2342.64 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.163296E+10 2225.98 06-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.188816E+11     0.403423E+11    
Minimum of Months 0.144531E+10 1454.29   0.307485E+10 2276.32  
Maximum of Months 0.167970E+10 2363.27   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105627E+10 1410.45 03-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.955124E+09 1494.56 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.107445E+10 1428.75 21-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.944909E+09 1306.08 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.100349E+10 937.20 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.992189E+09 937.20 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.934785E+09 1062.32 27-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.104965E+10 1258.23 24-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.958138E+09 1358.05 29-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.102927E+10 1522.92 30-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.103704E+10 1500.98 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.102770E+10 1413.27 06-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.120630E+11     0.259981E+11    
Minimum of Months 0.934785E+09 937.20   0.198155E+10 1466.95  
Maximum of Months 0.107445E+10 1522.92   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.160911E+10 2201.69 03-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.146341E+10 2320.29 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.166662E+10 2232.47 21-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.146916E+10 2092.53 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.156075E+10 1762.93 24-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.154278E+10 1649.51 23-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.145609E+10 1850.47 27-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.163125E+10 2034.43 24-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.148841E+10 2137.38 29-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.158563E+10 2363.32 30-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.157967E+10 2334.42 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.156084E+10 2203.74 06-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.186137E+11     0.403429E+11    
Minimum of Months 0.145609E+10 1649.51   0.307490E+10 2276.35  
Maximum of Months 0.166662E+10 2363.32   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105730E+10 1434.13 03-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.963948E+09 1494.56 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.108456E+10 1443.95 21-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.949452E+09 1367.13 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.100561E+10 1267.89 24-MAY-07:30 0.222974E+10 1466.94 01-MAY-07:10
June 0.992633E+09 1121.58 23-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.937999E+09 1227.92 27-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.105291E+10 1328.79 24-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.966913E+09 1393.27 29-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.104723E+10 1522.92 30-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.103146E+10 1511.16 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.102731E+10 1435.65 06-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.121173E+11     0.259979E+11    
Minimum of Months 0.937999E+09 1121.58   0.198154E+10 1466.94  
Maximum of Months 0.108456E+10 1522.92   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.497722E+09 520.85 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.451470E+09 520.85 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.536472E+09 520.85 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.479179E+09 520.85 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.517097E+09 520.85 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.514597E+09 520.85 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.481680E+09 520.85 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.536472E+09 520.85 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.479179E+09 520.85 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.497722E+09 520.85 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.491888E+09 520.85 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.481680E+09 520.85 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.596516E+10     0.153881E+12    
Minimum of Months 0.451470E+09 520.85   0.505780E+10 1948.61  
Maximum of Months 0.536472E+09 520.85   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.497722E+09 520.85 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.451470E+09 520.85 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.536472E+09 520.85 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.479179E+09 520.85 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.517097E+09 520.85 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.514597E+09 520.85 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.481680E+09 520.85 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.536472E+09 520.85 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.479179E+09 520.85 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.497722E+09 520.85 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.491888E+09 520.85 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.481680E+09 520.85 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.596516E+10     0.153881E+12    
Minimum of Months 0.451470E+09 520.85   0.505780E+10 1948.61  
Maximum of Months 0.536472E+09 520.85   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.497722E+09 520.85 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.451470E+09 520.85 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.536472E+09 520.85 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.479179E+09 520.85 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.517097E+09 520.85 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.514597E+09 520.85 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.481680E+09 520.85 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.536472E+09 520.85 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.479179E+09 520.85 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.497722E+09 520.85 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.491888E+09 520.85 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.481680E+09 520.85 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.596516E+10     0.153881E+12    
Minimum of Months 0.451470E+09 520.85   0.505780E+10 1948.61  
Maximum of Months 0.536472E+09 520.85   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.565679E+10 5919.59 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.513113E+10 5919.59 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.609720E+10 5919.59 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.544605E+10 5919.59 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.587700E+10 5919.59 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.584858E+10 5919.59 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.547447E+10 5919.59 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.609720E+10 5919.59 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.544605E+10 5919.59 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.565679E+10 5919.59 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.559049E+10 5919.59 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.547447E+10 5919.59 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.677962E+11     0.749486E+13    
Minimum of Months 0.513113E+10 5919.59   0.246344E+12 94908.13  
Maximum of Months 0.609720E+10 5919.59   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.200626E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.181982E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.216246E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.193152E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.208436E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.207428E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.194159E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.216246E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.193152E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.200626E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.198274E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.194159E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.240449E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.181982E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.216246E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.180176E+11 0.270551E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.163433E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.194204E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.173464E+11 0.261305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.187190E+11 0.275555E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.186285E+11 0.270261E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.174369E+11 0.266527E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.194204E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.173464E+11 0.261160E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.180176E+11 0.270624E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.178064E+11 0.264424E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.174369E+11 0.266454E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.215940E+12 0.321286E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.163433E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.194204E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.180176E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.173464E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.187190E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.186285E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.174369E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.173464E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.180176E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.178064E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.174369E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.215940E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.180176E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.173464E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.187190E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.186285E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.174369E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.173464E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.180176E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.178064E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.174369E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.215940E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.166997E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.970326E+09
February 0.136985E+10 0.151325E+10 0.307485E+10 0.00 0.00 0.00 0.00 512908.03 0.826551E+09
March 0.163685E+10 0.167794E+10 0.352283E+10 0.00 0.00 0.00 0.00 1629968.41 0.539230E+09
April 0.145243E+10 0.146459E+10 0.328108E+10 0.00 0.00 0.00 0.00 4842532.95 0.319943E+09
May 0.157338E+10 0.155027E+10 0.346000E+10 0.00 0.00 0.00 0.00 14352137.39 0.204644E+09
June 0.156900E+10 0.153128E+10 0.339353E+10 0.00 0.00 0.00 0.00 59835975.96 91368449.31
July 0.145680E+10 0.144454E+10 0.334664E+10 0.00 0.00 0.00 0.00 66839429.22 55913901.05
August 0.163685E+10 0.162533E+10 0.352283E+10 0.00 0.00 0.00 0.00 64750481.22 25741084.00
September 0.145243E+10 0.149135E+10 0.327926E+10 0.00 0.00 0.00 0.00 17881379.50 0.106607E+09
October 0.150991E+10 0.163458E+10 0.339809E+10 0.00 0.00 0.00 0.00 4101739.44 0.366704E+09
November 0.149516E+10 0.162553E+10 0.332024E+10 0.00 0.00 0.00 0.00 26094.34 0.539859E+09
December 0.145680E+10 0.162874E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.937566E+09
                   
Annual Sum or Average 0.181194E+11 0.188574E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.234773E+09 0.498445E+10
Minimum of Months 0.136985E+10 0.144454E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 25741084.00
Maximum of Months 0.163685E+10 0.167794E+10 0.352283E+10 0.00 0.00 0.00 0.00 66839429.22 0.970326E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.105497E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.648024E+09
February 0.882782E+09 0.954609E+09 0.198155E+10 0.00 0.00 0.00 0.00 249353.04 0.548392E+09
March 0.105485E+10 0.107397E+10 0.227025E+10 0.00 0.00 0.00 0.00 1376927.44 0.351346E+09
April 0.936002E+09 0.944524E+09 0.211446E+10 0.00 0.00 0.00 0.00 3568506.82 0.202840E+09
May 0.101394E+10 0.100328E+10 0.222976E+10 0.00 0.00 0.00 0.00 9552159.08 0.136710E+09
June 0.101113E+10 0.992018E+09 0.218692E+10 0.00 0.00 0.00 0.00 40881665.52 56343618.54
July 0.938820E+09 0.934583E+09 0.215670E+10 0.00 0.00 0.00 0.00 47227248.20 31734004.47
August 0.105485E+10 0.104940E+10 0.227025E+10 0.00 0.00 0.00 0.00 48039751.86 10626897.98
September 0.936002E+09 0.957652E+09 0.211328E+10 0.00 0.00 0.00 0.00 12322422.31 67530212.12
October 0.973041E+09 0.102890E+10 0.218986E+10 0.00 0.00 0.00 0.00 2725825.59 0.238607E+09
November 0.963541E+09 0.103648E+10 0.213969E+10 0.00 0.00 0.00 0.00 168481.55 0.351433E+09
December 0.938820E+09 0.102713E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.608255E+09
                   
Annual Sum or Average 0.116768E+11 0.120575E+11 0.259981E+11 0.00 0.00 0.00 0.00 0.166112E+09 0.325184E+10
Minimum of Months 0.882782E+09 0.934583E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 10626897.98
Maximum of Months 0.105485E+10 0.107397E+10 0.227025E+10 0.00 0.00 0.00 0.00 48039751.86 0.648024E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.160508E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.983584E+09
February 0.136988E+10 0.145987E+10 0.307490E+10 0.00 0.00 0.00 0.00 95570.58 0.843213E+09
March 0.163688E+10 0.166544E+10 0.352288E+10 0.00 0.00 0.00 0.00 1574516.27 0.556711E+09
April 0.145246E+10 0.146823E+10 0.328113E+10 0.00 0.00 0.00 0.00 4112108.66 0.319675E+09
May 0.157341E+10 0.155963E+10 0.346006E+10 0.00 0.00 0.00 0.00 13985607.02 0.204022E+09
June 0.156904E+10 0.154193E+10 0.339359E+10 0.00 0.00 0.00 0.00 60499370.44 88950457.08
July 0.145684E+10 0.145496E+10 0.334669E+10 0.00 0.00 0.00 0.00 67495517.49 53764617.04
August 0.163688E+10 0.163024E+10 0.352288E+10 0.00 0.00 0.00 0.00 63028413.34 25759964.47
September 0.145246E+10 0.148738E+10 0.327931E+10 0.00 0.00 0.00 0.00 15528025.15 0.108156E+09
October 0.150994E+10 0.158236E+10 0.339814E+10 0.00 0.00 0.00 0.00 2487238.26 0.378426E+09
November 0.149520E+10 0.157840E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.555930E+09
December 0.145684E+10 0.155932E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.934113E+09
                   
Annual Sum or Average 0.181198E+11 0.185929E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.228806E+09 0.505231E+10
Minimum of Months 0.136988E+10 0.145496E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 25759964.47
Maximum of Months 0.163688E+10 0.166544E+10 0.352288E+10 0.00 0.00 0.00 0.00 67495517.49 0.983584E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.105686E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.678414E+09
February 0.882782E+09 0.963790E+09 0.198154E+10 0.00 0.00 0.00 0.00 94817.93 0.596052E+09
March 0.105485E+10 0.108405E+10 0.227023E+10 0.00 0.00 0.00 0.00 1039176.42 0.411813E+09
April 0.936002E+09 0.948947E+09 0.211444E+10 0.00 0.00 0.00 0.00 2609429.44 0.248512E+09
May 0.101394E+10 0.100522E+10 0.222974E+10 0.00 0.00 0.00 0.00 8706313.14 0.151759E+09
June 0.101113E+10 0.992378E+09 0.218691E+10 0.00 0.00 0.00 0.00 37638206.60 71087878.46
July 0.938820E+09 0.937768E+09 0.215669E+10 0.00 0.00 0.00 0.00 40594297.60 45629186.93
August 0.105485E+10 0.105257E+10 0.227023E+10 0.00 0.00 0.00 0.00 37680145.06 27310904.60
September 0.936002E+09 0.966316E+09 0.211327E+10 0.00 0.00 0.00 0.00 11123174.22 80175045.99
October 0.973041E+09 0.104697E+10 0.218984E+10 0.00 0.00 0.00 0.00 1873056.38 0.272752E+09
November 0.963541E+09 0.103093E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.401760E+09
December 0.938820E+09 0.102666E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.699097E+09
                   
Annual Sum or Average 0.116768E+11 0.121125E+11 0.259979E+11 0.00 0.00 0.00 0.00 0.141359E+09 0.368436E+10
Minimum of Months 0.882782E+09 0.937768E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 27310904.60
Maximum of Months 0.105485E+10 0.108405E+10 0.227023E+10 0.00 0.00 0.00 0.00 40594297.60 0.699097E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.167367E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.196992E+10
February 0.136985E+10 0.151672E+10 0.307485E+10 0.00 0.00 0.00 0.00 3672111.50 0.168131E+10
March 0.163685E+10 0.167969E+10 0.352283E+10 0.00 0.00 0.00 0.00 4624322.65 0.110675E+10
April 0.145243E+10 0.146568E+10 0.328108E+10 0.00 0.00 0.00 0.00 12801238.69 0.695853E+09
May 0.157338E+10 0.155091E+10 0.346000E+10 0.00 0.00 0.00 0.00 33501791.78 0.454760E+09
June 0.156900E+10 0.153171E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.136717E+09 0.226972E+09
July 0.145680E+10 0.144532E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.150281E+09 0.147113E+09
August 0.163685E+10 0.162653E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.146246E+09 91718736.89
September 0.145243E+10 0.149291E+10 0.327926E+10 0.00 0.00 0.00 0.00 42473640.82 0.232808E+09
October 0.150991E+10 0.163661E+10 0.339809E+10 0.00 0.00 0.00 0.00 13437729.08 0.750094E+09
November 0.149516E+10 0.162888E+10 0.332024E+10 0.00 0.00 0.00 0.00 600964.18 0.107379E+10
December 0.145680E+10 0.163284E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.181222E+10
                   
Annual Sum or Average 0.181194E+11 0.188815E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.544356E+09 0.102433E+11
Minimum of Months 0.136985E+10 0.144532E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 91718736.89
Maximum of Months 0.163685E+10 0.167969E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.150281E+09 0.196992E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.105625E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.133585E+10
February 0.649041E+09 0.955139E+09 0.198155E+10 0.00 0.00 0.00 0.00 1138899.45 0.114573E+10
March 0.773965E+09 0.107444E+10 0.227025E+10 0.00 0.00 0.00 0.00 3632032.56 0.761211E+09
April 0.688021E+09 0.944900E+09 0.211446E+10 0.00 0.00 0.00 0.00 7429464.81 0.475582E+09
May 0.744847E+09 0.100349E+10 0.222976E+10 0.00 0.00 0.00 0.00 20712391.21 0.314674E+09
June 0.742030E+09 0.992188E+09 0.218692E+10 0.00 0.00 0.00 0.00 90210495.11 0.154674E+09
July 0.690839E+09 0.934786E+09 0.215670E+10 0.00 0.00 0.00 0.00 99479340.53 98909108.31
August 0.773965E+09 0.104965E+10 0.227025E+10 0.00 0.00 0.00 0.00 97232764.09 61395920.70
September 0.688021E+09 0.958106E+09 0.211328E+10 0.00 0.00 0.00 0.00 27979618.68 0.153118E+09
October 0.715730E+09 0.102926E+10 0.218986E+10 0.00 0.00 0.00 0.00 7151976.38 0.509840E+09
November 0.708685E+09 0.103703E+10 0.213969E+10 0.00 0.00 0.00 0.00 306698.39 0.729962E+09
December 0.690839E+09 0.102769E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.122097E+10
                   
Annual Sum or Average 0.858171E+10 0.120629E+11 0.259981E+11 0.00 0.00 0.00 0.00 0.355274E+09 0.696192E+10
Minimum of Months 0.649041E+09 0.934786E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 61395920.70
Maximum of Months 0.773965E+09 0.107444E+10 0.227025E+10 0.00 0.00 0.00 0.00 99479340.53 0.133585E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.160919E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.214367E+10
February 0.136988E+10 0.146171E+10 0.307490E+10 0.00 0.00 0.00 0.00 191690.37 0.183269E+10
March 0.163688E+10 0.166663E+10 0.352288E+10 0.00 0.00 0.00 0.00 3488204.80 0.123813E+10
April 0.145246E+10 0.146915E+10 0.328113E+10 0.00 0.00 0.00 0.00 9183066.50 0.732254E+09
May 0.157341E+10 0.156076E+10 0.346006E+10 0.00 0.00 0.00 0.00 31585588.16 0.462695E+09
June 0.156904E+10 0.154279E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.137857E+09 0.224553E+09
July 0.145684E+10 0.145609E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.151133E+09 0.145835E+09
August 0.163688E+10 0.163126E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.139566E+09 98074347.52
September 0.145246E+10 0.148841E+10 0.327931E+10 0.00 0.00 0.00 0.00 34707140.62 0.247928E+09
October 0.150994E+10 0.158565E+10 0.339814E+10 0.00 0.00 0.00 0.00 5285255.36 0.842494E+09
November 0.149520E+10 0.157959E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.122438E+10
December 0.145684E+10 0.156084E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.197052E+10
                   
Annual Sum or Average 0.181198E+11 0.186121E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.512998E+09 0.111632E+11
Minimum of Months 0.136988E+10 0.145609E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 98074347.52
Maximum of Months 0.163688E+10 0.166663E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.151133E+09 0.214367E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.105727E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.136728E+10
February 0.882782E+09 0.963950E+09 0.198154E+10 0.00 0.00 0.00 0.00 1361781.36 0.116900E+10
March 0.105485E+10 0.108455E+10 0.227023E+10 0.00 0.00 0.00 0.00 2560902.87 0.807155E+09
April 0.936002E+09 0.949366E+09 0.211444E+10 0.00 0.00 0.00 0.00 6992052.03 0.503247E+09
May 0.101394E+10 0.100561E+10 0.222974E+10 0.00 0.00 0.00 0.00 20371243.74 0.325841E+09
June 0.101113E+10 0.992613E+09 0.218691E+10 0.00 0.00 0.00 0.00 87913416.25 0.165114E+09
July 0.938820E+09 0.937996E+09 0.215669E+10 0.00 0.00 0.00 0.00 96633101.17 0.106216E+09
August 0.105485E+10 0.105291E+10 0.227023E+10 0.00 0.00 0.00 0.00 90737826.04 75260917.43
September 0.936002E+09 0.966902E+09 0.211327E+10 0.00 0.00 0.00 0.00 26600204.33 0.164887E+09
October 0.973041E+09 0.104722E+10 0.218984E+10 0.00 0.00 0.00 0.00 5908723.95 0.532879E+09
November 0.963541E+09 0.103140E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.758287E+09
December 0.938820E+09 0.102729E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.125933E+10
                   
Annual Sum or Average 0.116768E+11 0.121171E+11 0.259979E+11 0.00 0.00 0.00 0.00 0.339079E+09 0.723450E+10
Minimum of Months 0.882782E+09 0.937996E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 75260917.43
Maximum of Months 0.105485E+10 0.108455E+10 0.227023E+10 0.00 0.00 0.00 0.00 96633101.17 0.136728E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.167369E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.229355E+10
February 0.136985E+10 0.151670E+10 0.307485E+10 0.00 0.00 0.00 0.00 6738870.32 0.196905E+10
March 0.163685E+10 0.167970E+10 0.352283E+10 0.00 0.00 0.00 0.00 6491985.29 0.125818E+10
April 0.145243E+10 0.146569E+10 0.328108E+10 0.00 0.00 0.00 0.00 15823281.63 0.808506E+09
May 0.157338E+10 0.155090E+10 0.346000E+10 0.00 0.00 0.00 0.00 39772086.06 0.550845E+09
June 0.156900E+10 0.153171E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.163243E+09 0.285117E+09
July 0.145680E+10 0.144531E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.178138E+09 0.183705E+09
August 0.163685E+10 0.162652E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.173073E+09 0.117546E+09
September 0.145243E+10 0.149291E+10 0.327926E+10 0.00 0.00 0.00 0.00 50888483.07 0.274440E+09
October 0.150991E+10 0.163661E+10 0.339809E+10 0.00 0.00 0.00 0.00 19039761.27 0.845699E+09
November 0.149516E+10 0.162890E+10 0.332024E+10 0.00 0.00 0.00 0.00 3832291.06 0.118900E+10
December 0.145680E+10 0.163296E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.203131E+10
                   
Annual Sum or Average 0.181194E+11 0.188816E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.657040E+09 0.118070E+11
Minimum of Months 0.136985E+10 0.144531E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.117546E+09
Maximum of Months 0.163685E+10 0.167970E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.178138E+09 0.229355E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.105627E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.154635E+10
February 0.882782E+09 0.955124E+09 0.198155E+10 0.00 0.00 0.00 0.00 1895940.51 0.134120E+10
March 0.105485E+10 0.107445E+10 0.227025E+10 0.00 0.00 0.00 0.00 4543930.92 0.882151E+09
April 0.936002E+09 0.944909E+09 0.211446E+10 0.00 0.00 0.00 0.00 8318045.69 0.564490E+09
May 0.101394E+10 0.100349E+10 0.222976E+10 0.00 0.00 0.00 0.00 23775664.76 0.387735E+09
June 0.101113E+10 0.992189E+09 0.218692E+10 0.00 0.00 0.00 0.00 0.106943E+09 0.197153E+09
July 0.938820E+09 0.934785E+09 0.215670E+10 0.00 0.00 0.00 0.00 0.116711E+09 0.125127E+09
August 0.105485E+10 0.104965E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.114061E+09 79840883.24
September 0.936002E+09 0.958138E+09 0.211328E+10 0.00 0.00 0.00 0.00 32128060.39 0.184968E+09
October 0.973041E+09 0.102927E+10 0.218986E+10 0.00 0.00 0.00 0.00 8995661.99 0.589627E+09
November 0.963541E+09 0.103704E+10 0.213969E+10 0.00 0.00 0.00 0.00 1976550.12 0.819938E+09
December 0.938820E+09 0.102770E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.136504E+10
                   
Annual Sum or Average 0.116768E+11 0.120630E+11 0.259981E+11 0.00 0.00 0.00 0.00 0.419348E+09 0.808362E+10
Minimum of Months 0.882782E+09 0.934785E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 79840883.24
Maximum of Months 0.105485E+10 0.107445E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.116711E+09 0.154635E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.160911E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.244547E+10
February 0.136988E+10 0.146341E+10 0.307490E+10 0.00 0.00 0.00 0.00 201226.37 0.212265E+10
March 0.163688E+10 0.166662E+10 0.352288E+10 0.00 0.00 0.00 0.00 4196722.91 0.143528E+10
April 0.145246E+10 0.146916E+10 0.328113E+10 0.00 0.00 0.00 0.00 10719530.96 0.861072E+09
May 0.157341E+10 0.156075E+10 0.346006E+10 0.00 0.00 0.00 0.00 37170890.36 0.563131E+09
June 0.156904E+10 0.154278E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.164489E+09 0.282156E+09
July 0.145684E+10 0.145609E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.178826E+09 0.181827E+09
August 0.163688E+10 0.163125E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.166531E+09 0.126106E+09
September 0.145246E+10 0.148841E+10 0.327931E+10 0.00 0.00 0.00 0.00 41188346.50 0.296816E+09
October 0.150994E+10 0.158563E+10 0.339814E+10 0.00 0.00 0.00 0.00 6151946.80 0.976522E+09
November 0.149520E+10 0.157967E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.138014E+10
December 0.145684E+10 0.156084E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.218192E+10
                   
Annual Sum or Average 0.181198E+11 0.186137E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.609475E+09 0.128531E+11
Minimum of Months 0.136988E+10 0.145609E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.126106E+09
Maximum of Months 0.163688E+10 0.166662E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.178826E+09 0.244547E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.105730E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.158167E+10
February 0.882782E+09 0.963948E+09 0.198154E+10 0.00 0.00 0.00 0.00 2140976.07 0.137417E+10
March 0.105485E+10 0.108456E+10 0.227023E+10 0.00 0.00 0.00 0.00 3251396.66 0.942736E+09
April 0.936002E+09 0.949452E+09 0.211444E+10 0.00 0.00 0.00 0.00 8343382.73 0.597543E+09
May 0.101394E+10 0.100561E+10 0.222974E+10 0.00 0.00 0.00 0.00 24667674.06 0.398352E+09
June 0.101113E+10 0.992633E+09 0.218691E+10 0.00 0.00 0.00 0.00 0.106327E+09 0.207365E+09
July 0.938820E+09 0.937999E+09 0.215669E+10 0.00 0.00 0.00 0.00 0.116336E+09 0.131553E+09
August 0.105485E+10 0.105291E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.109550E+09 95121122.42
September 0.936002E+09 0.966913E+09 0.211327E+10 0.00 0.00 0.00 0.00 31907401.46 0.197799E+09
October 0.973041E+09 0.104723E+10 0.218984E+10 0.00 0.00 0.00 0.00 7779576.65 0.619790E+09
November 0.963541E+09 0.103146E+10 0.213967E+10 0.00 0.00 0.00 0.00 14771.46 0.862557E+09
December 0.938820E+09 0.102731E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.142484E+10
                   
Annual Sum or Average 0.116768E+11 0.121173E+11 0.259979E+11 0.00 0.00 0.00 0.00 0.410319E+09 0.843349E+10
Minimum of Months 0.882782E+09 0.937999E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 95121122.42
Maximum of Months 0.105485E+10 0.108456E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.116336E+09 0.158167E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.497722E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.451470E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.536472E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.479179E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.517097E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.514597E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.481680E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.536472E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.479179E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.497722E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.491888E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.481680E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.596516E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.451470E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.536472E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.497722E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.451470E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.536472E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.479179E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.517097E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.514597E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.481680E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.536472E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.479179E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.497722E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.491888E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.481680E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.596516E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.451470E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.536472E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.497722E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.451470E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.536472E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.479179E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.517097E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.514597E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.481680E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.536472E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.479179E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.497722E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.491888E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.481680E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.596516E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.451470E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.536472E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.565679E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.513113E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.609720E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.544605E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.587700E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.584858E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.547447E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.609720E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.544605E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.565679E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.559049E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.547447E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.677962E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.513113E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.609720E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.212422E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 87413.85 0.180796E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2080349.92 0.116980E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6392438.39 0.692464E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22618052.22 0.431367E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.106781E+09 0.199414E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.122489E+09 0.127915E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.113361E+09 73841163.30
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28092026.09 0.228880E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4815119.03 0.792329E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.117248E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.203004E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.406716E+09 0.108507E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73841163.30
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.122489E+09 0.212422E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.349607E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1188412.33 0.299942E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4268535.72 0.198715E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13017044.65 0.119837E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42417053.24 0.758836E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.192750E+09 0.359746E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.221360E+09 0.232649E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.204603E+09 0.144503E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53076042.67 0.398436E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11316652.97 0.134437E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 331529.65 0.195449E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.331188E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.744328E+09 0.181859E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.144503E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.221360E+09 0.349607E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.349049E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1329808.61 0.306061E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2952799.74 0.209629E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6297537.47 0.130913E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27450139.27 0.870472E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.174286E+09 0.419257E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.198152E+09 0.277999E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.188062E+09 0.177904E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41979088.59 0.431862E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7856579.43 0.139833E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1790605.79 0.195026E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.320627E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.650156E+09 0.186889E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.177904E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.198152E+09 0.349049E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 20994.62 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 20994.62 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 20994.62 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 20994.62 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 20994.62 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 20994.62 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 20994.62 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 20994.62 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 20994.62 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 20994.62 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 20994.62 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 20994.62 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   20994.62   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   20994.62   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18854.65 02-JAN-08:09 18128.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18854.65 01-FEB-08:09 18128.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18854.65 01-MAR-08:09 18128.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18854.65 03-APR-07:10 18128.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18854.65 01-MAY-07:10 18128.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18854.65 01-JUN-07:10 18128.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18854.65 03-JUL-07:10 18128.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18854.65 01-AUG-07:10 18128.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18854.65 01-SEP-07:10 18128.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18854.65 02-OCT-07:10 18128.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18854.65 01-NOV-07:10 18128.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18854.65 01-DEC-08:09 18128.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18854.65   18128.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18854.65   18128.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18854.65 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18854.65 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18854.65 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18854.65 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18854.65 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18854.65 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18854.65 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18854.65 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18854.65 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18854.65 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18854.65 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18854.65 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18854.65 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18854.65 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18854.65 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18854.65 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18854.65 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18854.65 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18854.65 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18854.65 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18854.65 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18854.65 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18854.65 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18854.65 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2217.83 03-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1727.90 07-JAN-18:03
February 2010.79 01-FEB-10:09 2318.86 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 45.76 26-FEB-14:50 2129.33 12-FEB-00:55
March 2010.79 01-MAR-10:09 2230.65 21-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 46.43 30-MAR-16:00 1402.74 22-MAR-03:00
April 2010.79 03-APR-09:09 2078.82 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 83.63 16-APR-12:10 714.38 05-APR-05:00
May 2010.79 01-MAY-09:09 1626.14 24-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 114.05 07-MAY-12:10 551.93 10-MAY-04:00
June 2010.79 01-JUN-09:09 1454.29 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 323.08 11-JUN-15:00 406.35 07-JUN-03:00
July 2010.79 03-JUL-09:09 1766.67 27-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 308.28 08-JUL-18:53 300.36 28-JUL-22:00
August 2010.79 01-AUG-09:09 2008.73 24-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 324.58 06-AUG-14:00 164.89 31-AUG-05:00
September 2010.79 01-SEP-09:09 2143.20 29-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 128.76 17-SEP-15:00 380.90 30-SEP-19:00
October 2010.79 02-OCT-09:09 2363.15 30-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 97.27 09-OCT-15:43 833.25 28-OCT-03:53
November 2010.79 01-NOV-09:09 2341.95 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 21.65 19-NOV-15:10 1187.95 07-NOV-02:00
December 2010.79 01-DEC-10:09 2221.92 06-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2076.09 17-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1454.29   2276.32   0.00 0.00 0.00 0.00 0.00   164.89  
Maximum of Months 2010.79   2363.15   2276.32   0.00 0.00 0.00 0.00 324.58   2129.33  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1409.07 03-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1134.74 07-JAN-18:10
February 1295.83 01-FEB-10:09 1494.36 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 28.03 26-FEB-15:30 1402.78 12-FEB-00:55
March 1295.83 01-MAR-10:09 1427.69 21-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 35.97 11-MAR-16:00 901.04 22-MAR-03:00
April 1295.83 03-APR-09:09 1302.63 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 44.47 16-APR-14:10 450.74 05-APR-05:00
May 1295.83 01-MAY-09:09 937.20 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 70.48 29-MAY-18:00 364.41 10-MAY-04:00
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 214.86 25-JUN-16:10 267.98 07-JUN-03:00
July 1295.83 03-JUL-09:09 1055.50 27-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 221.60 08-JUL-18:53 185.20 28-JUL-24:00
August 1295.83 01-AUG-09:09 1254.33 24-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 234.39 06-AUG-14:00 87.94 31-AUG-05:00
September 1295.83 01-SEP-09:09 1356.03 29-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 106.30 17-SEP-15:00 239.53 30-SEP-19:00
October 1295.83 02-OCT-09:09 1522.90 30-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 69.85 09-OCT-15:43 540.30 28-OCT-03:53
November 1295.83 01-NOV-09:09 1500.56 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 43.17 19-NOV-15:10 779.18 07-NOV-02:00
December 1295.83 01-DEC-10:09 1411.95 06-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1345.25 17-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.95   0.00 0.00 0.00 0.00 0.00   87.94  
Maximum of Months 1295.83   1522.90   1466.95   0.00 0.00 0.00 0.00 234.39   1402.78  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2196.45 03-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1710.14 07-JAN-18:03
February 2010.83 01-FEB-10:09 2318.91 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 18.54 28-FEB-15:00 2092.81 12-FEB-00:55
March 2010.83 01-MAR-10:09 2228.45 21-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 46.40 30-MAR-16:00 1359.84 22-MAR-03:00
April 2010.83 03-APR-09:09 2084.50 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 40.30 16-APR-14:10 701.36 05-APR-05:00
May 2010.83 01-MAY-09:09 1746.80 24-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 99.97 07-MAY-12:10 548.31 10-MAY-04:00
June 2010.83 01-JUN-09:09 1629.84 23-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 323.89 11-JUN-15:00 407.60 07-JUN-03:00
July 2010.83 03-JUL-09:09 1835.92 27-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 310.13 08-JUL-18:53 296.83 28-JUL-22:00
August 2010.83 01-AUG-09:09 2024.82 24-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 314.61 06-AUG-13:58 165.80 31-AUG-05:00
September 2010.83 01-SEP-09:09 2130.41 29-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 84.05 17-SEP-15:00 362.77 30-SEP-19:00
October 2010.83 02-OCT-09:09 2363.20 30-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 46.49 09-OCT-15:38 839.88 28-OCT-03:53
November 2010.83 01-NOV-09:09 2333.33 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1225.63 07-NOV-02:00
December 2010.83 01-DEC-10:09 2198.55 06-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2011.72 17-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1629.84   2276.35   0.00 0.00 0.00 0.00 0.00   165.80  
Maximum of Months 2010.83   2363.20   2276.35   0.00 0.00 0.00 0.00 323.89   2092.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1433.50 03-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1182.97 07-JAN-18:10
February 1295.83 01-FEB-10:09 1494.36 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 15.80 26-FEB-13:30 1499.58 12-FEB-00:55
March 1295.83 01-MAR-10:09 1443.43 21-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 30.95 30-MAR-16:00 1035.43 22-MAR-03:00
April 1295.83 03-APR-09:09 1366.10 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 41.86 16-APR-12:10 532.73 05-APR-05:00
May 1295.83 01-MAY-09:09 1266.53 24-MAY-07:30 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 89.09 07-MAY-12:10 393.17 10-MAY-04:00
June 1295.83 01-JUN-09:09 1119.04 23-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 189.99 25-JUN-16:04 312.37 07-JUN-03:00
July 1295.83 03-JUL-09:09 1225.96 27-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 181.86 08-JUL-18:50 238.12 28-JUL-22:00
August 1295.83 01-AUG-09:09 1327.51 24-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 213.10 06-AUG-13:58 155.90 31-AUG-05:00
September 1295.83 01-SEP-09:09 1392.40 29-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 80.51 17-SEP-12:20 279.81 30-SEP-19:00
October 1295.83 02-OCT-09:09 1522.90 30-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 33.06 09-OCT-13:43 619.97 28-OCT-03:53
November 1295.83 01-NOV-09:09 1511.05 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 888.22 07-NOV-02:00
December 1295.83 01-DEC-10:09 1435.03 06-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1525.68 17-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1119.04   1466.94   0.00 0.00 0.00 0.00 0.00   155.90  
Maximum of Months 1295.83   1522.90   1466.94   0.00 0.00 0.00 0.00 213.10   1525.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2222.17 03-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3769.70 07-JAN-18:03
February 2010.79 01-FEB-10:09 2320.29 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 220.76 26-FEB-13:10 4432.83 12-FEB-00:55
March 2010.79 01-MAR-10:09 2234.71 21-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 134.81 11-MAR-16:00 2733.97 22-MAR-03:00
April 2010.79 03-APR-09:09 2087.33 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 227.51 16-APR-12:10 1524.13 05-APR-05:00
May 2010.79 01-MAY-09:09 1646.65 24-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 276.52 07-MAY-12:00 1223.14 10-MAY-04:00
June 2010.79 01-JUN-09:09 1454.29 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 737.23 11-JUN-14:52 906.67 07-JUN-03:00
July 2010.79 03-JUL-09:09 1784.22 27-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 712.44 08-JUL-18:53 631.12 28-JUL-22:00
August 2010.79 01-AUG-09:09 2019.30 24-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 750.00 06-AUG-14:00 391.12 25-AUG-04:47
September 2010.79 01-SEP-09:09 2149.80 29-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 315.47 17-SEP-15:00 828.49 29-SEP-04:57
October 2010.79 02-OCT-09:09 2363.27 30-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 320.48 08-OCT-13:52 1652.06 28-OCT-03:53
November 2010.79 01-NOV-09:09 2342.66 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 137.60 19-NOV-14:52 2560.04 30-NOV-22:03
December 2010.79 01-DEC-10:09 2226.11 06-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3943.51 17-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1454.29   2276.32   0.00 0.00 0.00 0.00 0.00   391.12  
Maximum of Months 2010.79   2363.27   2276.32   0.00 0.00 0.00 0.00 750.00   4432.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1410.52 03-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2491.17 07-JAN-18:03
February 1239.33 01-FEB-08:09 1494.59 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 104.66 26-FEB-15:50 2955.19 12-FEB-01:00
March 1239.33 01-MAR-08:09 1428.82 21-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 99.27 11-MAR-18:03 1797.30 22-MAR-05:00
April 1239.33 03-APR-07:10 1306.19 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 108.43 08-APR-17:02 1002.22 05-APR-05:00
May 1239.33 01-MAY-07:10 937.20 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 160.09 29-MAY-17:50 823.06 10-MAY-04:00
June 1239.33 01-JUN-07:10 937.20 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 496.98 11-JUN-15:10 622.83 07-JUN-03:00
July 1239.33 03-JUL-07:10 1062.47 27-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 497.67 08-JUL-18:53 420.01 02-JUL-03:00
August 1239.33 01-AUG-07:10 1258.36 24-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 496.93 06-AUG-13:53 260.48 29-AUG-01:53
September 1239.33 01-SEP-07:10 1358.15 29-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 249.29 17-SEP-14:50 541.77 29-SEP-04:57
October 1239.33 02-OCT-07:10 1522.92 30-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 181.19 09-OCT-15:30 1095.97 28-OCT-03:53
November 1239.33 01-NOV-07:10 1500.98 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 68.15 19-NOV-14:52 1703.52 30-NOV-22:03
December 1239.33 01-DEC-08:09 1413.34 06-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2625.13 17-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   937.20   1466.95   0.00 0.00 0.00 0.00 0.00   260.48  
Maximum of Months 1239.33   1522.92   1466.95   0.00 0.00 0.00 0.00 497.67   2955.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2201.81 03-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3814.85 07-JAN-18:03
February 2010.83 01-FEB-10:09 2320.34 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 38.76 28-FEB-15:00 4640.03 11-FEB-18:03
March 2010.83 01-MAR-10:09 2232.60 21-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 105.44 30-MAR-16:00 2764.72 22-MAR-03:00
April 2010.83 03-APR-09:09 2092.76 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 94.90 08-APR-17:02 1528.51 05-APR-05:00
May 2010.83 01-MAY-09:09 1763.21 24-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 246.47 07-MAY-12:00 1243.93 10-MAY-04:00
June 2010.83 01-JUN-09:09 1650.07 23-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 736.82 11-JUN-15:20 914.14 07-JUN-03:00
July 2010.83 03-JUL-09:09 1850.90 27-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 718.00 08-JUL-18:53 629.25 28-JUL-22:00
August 2010.83 01-AUG-09:09 2034.74 24-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 679.10 06-AUG-13:53 399.92 25-AUG-04:47
September 2010.83 01-SEP-09:09 2137.58 29-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 187.93 17-SEP-15:00 830.83 29-SEP-04:57
October 2010.83 02-OCT-09:09 2363.32 30-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 89.11 09-OCT-16:06 1765.60 28-OCT-03:53
November 2010.83 01-NOV-09:09 2334.43 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2601.77 07-NOV-02:00
December 2010.83 01-DEC-10:09 2203.86 06-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4086.63 17-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1650.07   2276.35   0.00 0.00 0.00 0.00 0.00   399.92  
Maximum of Months 2010.83   2363.32   2276.35   0.00 0.00 0.00 0.00 736.82   4640.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1434.22 03-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2546.31 07-JAN-18:03
February 1295.83 01-FEB-10:09 1494.59 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 159.36 26-FEB-13:10 3165.40 11-FEB-18:03
March 1295.83 01-MAR-10:09 1444.03 21-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 70.52 30-MAR-16:00 1852.09 22-MAR-03:00
April 1295.83 03-APR-09:09 1367.28 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 161.22 16-APR-12:10 1024.22 05-APR-05:00
May 1295.83 01-MAY-09:09 1268.01 24-MAY-07:30 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 214.37 07-MAY-12:00 854.81 10-MAY-04:00
June 1295.83 01-JUN-09:09 1121.93 23-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 463.50 11-JUN-15:06 643.70 07-JUN-03:00
July 1295.83 03-JUL-09:09 1228.19 27-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 444.39 08-JUL-18:50 428.99 28-JUL-22:00
August 1295.83 01-AUG-09:09 1328.97 24-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 507.89 06-AUG-14:00 300.82 29-AUG-01:53
September 1295.83 01-SEP-09:09 1393.40 29-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 210.74 17-SEP-12:10 548.64 29-SEP-04:57
October 1295.83 02-OCT-09:09 1522.92 30-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 159.57 08-OCT-13:52 1141.45 28-OCT-03:53
November 1295.83 01-NOV-09:09 1511.17 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1709.11 30-NOV-22:03
December 1295.83 01-DEC-10:09 1435.74 06-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2692.89 17-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1121.93   1466.94   0.00 0.00 0.00 0.00 0.00   300.82  
Maximum of Months 1295.83   1522.92   1466.94   0.00 0.00 0.00 0.00 507.89   3165.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2222.03 03-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4463.71 07-JAN-18:03
February 2010.79 01-FEB-10:09 2320.24 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 385.71 26-FEB-13:20 5527.45 12-FEB-01:00
March 2010.79 01-MAR-10:09 2234.58 21-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 199.58 11-MAR-18:03 3374.22 22-MAR-05:00
April 2010.79 03-APR-09:09 2087.09 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 271.80 16-APR-12:10 1828.92 05-APR-04:53
May 2010.79 01-MAY-09:09 1646.39 24-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 326.19 07-MAY-12:00 1402.79 10-MAY-04:00
June 2010.79 01-JUN-09:09 1454.29 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 906.14 11-JUN-15:00 1112.81 07-JUN-03:00
July 2010.79 03-JUL-09:09 1783.80 27-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 802.05 08-JUL-18:53 765.13 01-JUL-20:00
August 2010.79 01-AUG-09:09 2019.00 24-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 886.43 06-AUG-13:53 513.03 25-AUG-04:53
September 2010.79 01-SEP-09:09 2149.60 29-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 374.87 17-SEP-14:50 930.09 29-SEP-04:53
October 2010.79 02-OCT-09:09 2363.27 30-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 486.70 08-OCT-13:52 1849.45 28-OCT-03:53
November 2010.79 01-NOV-09:09 2342.64 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 420.27 19-NOV-14:52 3166.02 30-NOV-22:03
December 2010.79 01-DEC-10:09 2225.98 06-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4462.04 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1454.29   2276.32   0.00 0.00 0.00 0.00 0.00   513.03  
Maximum of Months 2010.79   2363.27   2276.32   0.00 0.00 0.00 0.00 906.14   5527.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1410.45 03-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3092.21 07-JAN-05:10
February 1295.83 01-FEB-10:09 1494.56 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 173.27 26-FEB-15:50 3684.98 12-FEB-01:00
March 1295.83 01-MAR-10:09 1428.75 21-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 134.92 11-MAR-18:03 2249.37 22-MAR-05:00
April 1295.83 03-APR-09:09 1306.08 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 122.00 16-APR-14:00 1214.79 05-APR-04:53
May 1295.83 01-MAY-09:09 937.20 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 181.91 29-MAY-17:42 949.50 10-MAY-04:00
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 592.49 11-JUN-15:20 768.51 07-JUN-03:00
July 1295.83 03-JUL-09:09 1062.32 27-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 549.55 08-JUL-18:50 551.59 01-JUL-20:00
August 1295.83 01-AUG-09:09 1258.23 24-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 578.48 06-AUG-13:53 336.08 25-AUG-04:53
September 1295.83 01-SEP-09:09 1358.05 29-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 285.14 17-SEP-14:50 613.35 29-SEP-04:53
October 1295.83 02-OCT-09:09 1522.92 30-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 235.62 08-OCT-13:52 1236.61 28-OCT-03:53
November 1295.83 01-NOV-09:09 1500.98 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 249.09 19-NOV-14:52 2108.62 30-NOV-22:03
December 1295.83 01-DEC-10:09 1413.27 06-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2973.19 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.95   0.00 0.00 0.00 0.00 0.00   336.08  
Maximum of Months 1295.83   1522.92   1466.95   0.00 0.00 0.00 0.00 592.49   3684.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2201.69 03-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4523.47 07-JAN-18:03
February 2010.83 01-FEB-10:09 2320.29 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 42.24 28-FEB-15:00 5527.24 12-FEB-01:00
March 2010.83 01-MAR-10:09 2232.47 21-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 127.29 30-MAR-16:00 3374.10 22-MAR-05:00
April 2010.83 03-APR-09:09 2092.53 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 131.06 16-APR-14:00 1837.65 05-APR-04:53
May 2010.83 01-MAY-09:09 1762.93 24-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 283.68 07-MAY-12:00 1432.72 10-MAY-04:00
June 2010.83 01-JUN-09:09 1649.51 23-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 896.59 11-JUN-15:00 1123.60 07-JUN-03:00
July 2010.83 03-JUL-09:09 1850.47 27-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 803.91 08-JUL-18:53 766.99 01-JUL-20:00
August 2010.83 01-AUG-09:09 2034.43 24-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 827.29 06-AUG-13:58 528.12 25-AUG-04:53
September 2010.83 01-SEP-09:09 2137.38 29-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 228.55 17-SEP-14:50 936.10 29-SEP-04:53
October 2010.83 02-OCT-09:09 2363.32 30-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 124.27 09-OCT-15:58 2009.40 28-OCT-03:53
November 2010.83 01-NOV-09:09 2334.42 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3168.34 30-NOV-22:03
December 2010.83 01-DEC-10:09 2203.74 06-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4459.99 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1649.51   2276.35   0.00 0.00 0.00 0.00 0.00   528.12  
Maximum of Months 2010.83   2363.32   2276.35   0.00 0.00 0.00 0.00 896.59   5527.24  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1434.13 03-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3092.18 07-JAN-05:08
February 1295.83 01-FEB-10:09 1494.56 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 220.37 26-FEB-13:20 3787.95 11-FEB-18:03
March 1295.83 01-MAR-10:09 1443.95 21-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 84.96 30-MAR-16:00 2249.34 22-MAR-05:00
April 1295.83 03-APR-09:09 1367.13 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 181.78 16-APR-12:10 1241.96 05-APR-04:53
May 1295.83 01-MAY-09:09 1267.89 24-MAY-07:30 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 267.19 07-MAY-12:00 992.56 10-MAY-04:00
June 1295.83 01-JUN-09:09 1121.58 23-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 550.08 11-JUN-15:16 792.21 07-JUN-03:00
July 1295.83 03-JUL-09:09 1227.92 27-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 510.75 08-JUL-18:50 528.13 01-JUL-20:00
August 1295.83 01-AUG-09:09 1328.79 24-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 611.77 06-AUG-13:53 379.82 29-AUG-01:53
September 1295.83 01-SEP-09:09 1393.27 29-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 246.51 24-SEP-12:40 625.58 29-SEP-04:53
October 1295.83 02-OCT-09:09 1522.92 30-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 257.05 08-OCT-13:52 1301.13 28-OCT-03:53
November 1295.83 01-NOV-09:09 1511.16 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 19.79 19-NOV-14:52 2115.94 30-NOV-22:03
December 1295.83 01-DEC-10:09 1435.65 06-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2973.16 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1121.58   1466.94   0.00 0.00 0.00 0.00 0.00   379.82  
Maximum of Months 1295.83   1522.92   1466.94   0.00 0.00 0.00 0.00 611.77   3787.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 520.85 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 520.85 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 520.85 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 520.85 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 520.85 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 520.85 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 520.85 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 520.85 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 520.85 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 520.85 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 520.85 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 520.85 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   520.85   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   520.85   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 520.85 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 520.85 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 520.85 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 520.85 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 520.85 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 520.85 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 520.85 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 520.85 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 520.85 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 520.85 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 520.85 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 520.85 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   520.85   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   520.85   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 520.85 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 520.85 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 520.85 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 520.85 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 520.85 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 520.85 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 520.85 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 520.85 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 520.85 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 520.85 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 520.85 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 520.85 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   520.85   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   520.85   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 5919.59 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 5919.59 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 5919.59 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 5919.59 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 5919.59 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 5919.59 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 5919.59 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 5919.59 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 5919.59 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 5919.59 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 5919.59 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 5919.59 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   5919.59   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   5919.59   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3798.06 07-JAN-18:03
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16.98 28-FEB-15:00 4739.89 12-FEB-00:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.03 30-MAR-16:00 3037.11 22-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 121.02 16-APR-13:52 1522.92 05-APR-05:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 191.30 07-MAY-12:30 1206.22 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 632.18 11-JUN-15:00 826.96 07-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 622.67 08-JUL-18:53 597.96 28-JUL-24:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 653.04 06-AUG-14:00 366.42 25-AUG-04:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 219.18 17-SEP-14:55 833.96 29-SEP-04:53
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 124.77 09-OCT-16:00 1780.06 28-OCT-03:53
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2594.39 21-NOV-04:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4573.64 17-DEC-03:55
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   366.42  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 653.04   4739.89  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 6521.85 07-JAN-18:03
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 118.35 26-FEB-14:53 8061.38 12-FEB-00:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 139.68 11-MAR-16:00 5119.65 22-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 247.94 16-APR-11:52 2646.68 05-APR-05:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 379.91 07-MAY-12:00 2149.14 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1167.15 11-JUN-14:52 1468.96 07-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1140.90 08-JUL-18:53 1043.44 28-JUL-22:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1190.85 06-AUG-14:00 698.23 25-AUG-04:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 442.62 17-SEP-15:00 1480.51 29-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 314.99 09-OCT-15:53 3018.66 28-OCT-03:53
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 132.55 19-NOV-14:52 4436.36 21-NOV-04:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 7606.79 17-DEC-03:55
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   698.23  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1190.85   8061.38  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 7112.05 07-JAN-18:03
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 135.60 26-FEB-14:50 8444.89 11-FEB-18:03
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 121.00 11-MAR-16:00 5024.26 22-MAR-05:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 151.21 16-APR-14:00 2868.63 05-APR-04:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 231.28 29-MAY-18:00 2152.78 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 969.78 11-JUN-15:00 1683.83 07-JUN-03:04
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1041.91 08-JUL-18:53 1189.95 01-JUL-20:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 947.26 06-AUG-14:00 755.37 25-AUG-05:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 262.58 17-SEP-15:00 1406.18 29-SEP-04:53
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 258.93 08-OCT-13:54 3082.85 28-OCT-03:53
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 389.11 19-NOV-14:52 4729.77 30-NOV-22:03
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 7098.90 17-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   755.37  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1041.91   8444.89  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 109093.15 02-JAN-04:03 0.00 4665.70 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
February 109664.00 27-FEB-04:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
March 111022.50 13-MAR-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
April 109035.55 10-APR-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
May 107862.13 15-MAY-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
June 100968.31 10-JUN-05:02 8976.13 11664.26 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 92535.35 03-JUL-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
August 87250.99 26-AUG-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
September 100330.03 14-SEP-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
October 110967.27 30-OCT-03:02 0.00 4665.70 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
November 112151.79 20-NOV-04:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
December 114909.02 11-DEC-04:02 0.00 6998.55 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 87250.99   0.00 4665.70 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 114909.02   8976.13 11664.26 80745.26 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 87864.18 02-JAN-06:02 8061.19 10475.32 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
February 90363.19 21-FEB-04:03 0.00 4190.13 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
March 92577.88 13-MAR-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
April 91042.64 05-APR-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
May 93899.66 08-MAY-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
June 90526.79 01-JUN-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
July 89480.77 29-JUL-03:02 0.00 5237.66 30214.32 0.00 0.00 0.00 0.00 0.00 0.00
August 82140.59 08-AUG-04:23 0.00 8380.26 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
September 95243.17 18-SEP-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
October 94071.26 16-OCT-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
November 96114.60 13-NOV-04:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
December 92234.92 11-DEC-04:02 0.00 6285.19 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 82140.59   0.00 4190.13 30214.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 96114.60   8061.19 10475.32 48342.90 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 65721.43 05-JAN-11:33 45948.79 56563.94 54385.56 0.00 0.00 0.00 0.00 0.00 0.00
February 77635.86 23-FEB-06:03 6448.95 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
March 81356.74 30-MAR-04:03 0.00 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
April 82417.86 21-APR-04:03 0.00 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
May 84764.16 31-MAY-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
June 84794.05 20-JUN-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 84563.52 26-JUL-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 84261.34 25-AUG-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 84617.26 11-SEP-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
October 82354.80 18-OCT-04:03 0.00 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
November 81820.84 04-NOV-05:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
December 79238.75 14-DEC-06:03 6448.95 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 65721.43   0.00 5237.66 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 84794.05   45948.79 56563.94 54385.56 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 30488.72 20-JAN-17:00 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 38955.49 28-FEB-17:00 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
March 80162.48 31-MAR-04:03 0.00 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
April 81971.81 24-APR-04:03 0.00 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
May 85140.36 30-MAY-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
June 86798.98 19-JUN-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 84643.21 03-JUL-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 84199.07 08-AUG-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 85801.98 05-SEP-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
October 81051.42 18-OCT-04:03 0.00 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
November 75235.52 04-NOV-05:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
December 61707.63 13-DEC-06:03 6448.95 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 30488.72   0.00 5237.66 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 86798.98   15316.26 18854.65 40285.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3738.25 31-JAN-15:00 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 28.97
February 5987.05 28-FEB-15:00 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 18.54 0.00
March 9132.41 30-MAR-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 44.84
April 10617.15 19-APR-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 35.82
May 12398.95 30-MAY-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 16.18
June 16106.91 25-JUN-16:41 708.51 565.58 5311.41 0.00 0.00 0.00 0.00 238.56 0.00
July 16295.45 09-JUL-18:01 0.00 565.58 5311.41 0.00 0.00 0.00 0.00 124.89 0.00
August 12345.25 14-AUG-05:03 1214.60 1578.34 6070.18 0.00 0.00 0.00 0.00 0.00 5.87
September 12045.38 05-SEP-03:02 0.00 657.64 5058.48 0.00 0.00 0.00 0.00 0.00 104.94
October 11399.33 18-OCT-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 30.15
November 5685.05 02-NOV-14:00 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 7.53
December 7211.23 13-DEC-06:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 53.06
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3738.25   0.00 565.58 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16295.45   2010.79 1578.34 6070.18 0.00 0.00 0.00 0.00 238.56 104.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3099.59 31-JAN-06:02 652.28 847.62 3259.88 0.00 0.00 0.00 0.00 0.00 49.13
February 6232.97 27-FEB-09:40 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 63.24
March 7103.79 14-MAR-09:30 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 36.09
April 8650.84 17-APR-08:40 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 21.79
May 16058.82 07-MAY-09:23 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 0.00 59.77
June 16295.78 25-JUN-10:02 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 42.05 0.00
July 16417.45 04-JUL-09:32 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 8.83
August 11289.96 27-AUG-09:43 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 0.02 0.00
September 14803.05 24-SEP-09:43 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 0.00 16.12
October 7662.42 10-OCT-09:30 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 8.54
November 5862.82 06-NOV-09:30 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 62.39
December 3611.55 13-DEC-04:02 0.00 423.81 3259.88 0.00 0.00 0.00 0.00 0.00 162.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3099.59   0.00 208.28 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16417.45   1295.83 937.20 3259.88 0.00 0.00 0.00 0.00 42.05 162.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11186.28 26-JAN-13:40 9615.76 7271.59 11381.76 0.00 0.00 0.00 0.00 0.00 233.43
February 16062.58 26-FEB-12:43 303.66 242.40 2276.35 0.00 0.00 0.00 0.00 0.00 140.11
March 13802.25 30-MAR-13:30 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 31.40 0.00
April 13594.02 17-APR-14:00 4021.67 2908.64 4552.71 0.00 0.00 0.00 0.00 12.43 0.00
May 14006.53 30-MAY-03:02 0.00 657.65 5058.56 0.00 0.00 0.00 0.00 0.00 63.09
June 17343.17 25-JUN-16:41 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 238.53 0.00
July 18627.18 09-JUL-16:01 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 189.65 0.00
August 15137.59 27-AUG-15:02 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 138.92 0.00
September 19428.00 24-SEP-13:02 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 44.71 0.00
October 19828.97 08-OCT-14:02 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 0.00 29.12
November 19614.22 11-NOV-13:13 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 0.00 230.66
December 13771.07 10-DEC-12:53 303.66 242.40 2276.35 0.00 0.00 0.00 0.00 0.00 167.46
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11186.28   0.00 242.40 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19828.97   9615.76 7271.59 11381.76 0.00 0.00 0.00 0.00 238.53 233.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4773.26 20-JAN-16:30 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 44.51
February 9235.97 27-FEB-16:40 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 2.59
March 15878.61 30-MAR-05:03 521.82 678.09 2607.89 0.00 0.00 0.00 0.00 0.00 31.28
April 20634.32 09-APR-16:32 326.14 260.35 2444.89 0.00 0.00 0.00 0.00 0.00 37.76
May 16209.18 29-MAY-17:53 0.00 208.28 1955.92 0.00 0.00 0.00 0.00 41.05 0.00
June 22469.47 25-JUN-16:01 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 131.49 0.00
July 22967.04 04-JUL-17:31 0.00 364.48 3422.85 0.00 0.00 0.00 0.00 37.36 0.00
August 21925.47 13-AUG-16:22 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 50.77 0.00
September 20567.27 24-SEP-16:22 326.14 260.35 2444.89 0.00 0.00 0.00 0.00 13.31 0.00
October 20561.19 08-OCT-15:22 326.14 260.35 2444.89 0.00 0.00 0.00 0.00 2.60 0.00
November 12136.88 04-NOV-03:02 0.00 423.81 2444.89 0.00 0.00 0.00 0.00 0.00 84.33
December 16398.99 13-DEC-06:03 521.82 678.09 2607.89 0.00 0.00 0.00 0.00 0.00 37.14
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4773.26   0.00 208.28 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22967.04   1239.33 937.20 3422.85 0.00 0.00 0.00 0.00 131.49 84.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2536.78 20-JAN-15:50 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 150.53
February 4205.37 28-FEB-15:00 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 38.76 0.00
March 6423.60 30-MAR-16:00 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 105.78 0.00
April 7562.71 12-APR-14:40 3846.22 2908.57 4552.64 0.00 0.00 0.00 0.00 57.43 0.00
May 8534.72 30-MAY-15:00 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 92.33 0.00
June 15148.92 25-JUN-16:41 708.51 565.58 5311.41 0.00 0.00 0.00 0.00 538.70 0.00
July 12120.27 15-JUL-03:02 0.00 657.64 3793.86 0.00 0.00 0.00 0.00 0.00 67.78
August 13329.16 06-AUG-17:01 0.00 565.58 5311.41 0.00 0.00 0.00 0.00 496.17 0.00
September 11099.43 27-SEP-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 25.61
October 6254.82 02-OCT-14:40 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 56.82 0.00
November 3748.10 03-NOV-14:00 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 30.58
December 3251.69 13-DEC-06:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 108.14
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2536.78   0.00 565.58 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15148.92   3846.22 2908.57 5311.41 0.00 0.00 0.00 0.00 538.70 150.53



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2742.90 26-JAN-13:38 6196.63 4685.99 7334.73 0.00 0.00 0.00 0.00 0.00 323.82
February 4633.63 02-FEB-11:45 2478.65 1874.40 2933.89 0.00 0.00 0.00 0.00 0.00 459.75
March 5573.89 14-MAR-11:00 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 39.21
April 8472.37 17-APR-10:10 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 8.78
May 16566.35 07-MAY-09:32 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 0.00 140.98
June 17090.83 25-JUN-10:02 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 80.65 0.00
July 17120.02 04-JUL-09:32 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 29.82
August 17004.03 06-AUG-11:02 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 95.35 0.00
September 14463.72 24-SEP-10:13 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 0.00 7.96
October 6658.27 11-OCT-10:20 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 5.71
November 3842.96 06-NOV-09:50 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 152.34
December 3836.87 01-DEC-10:45 0.00 1874.40 2933.89 0.00 0.00 0.00 0.00 0.00 201.73
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2742.90   0.00 208.28 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17120.02   6196.63 4685.99 7334.73 0.00 0.00 0.00 0.00 95.35 459.75



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13959.58 26-JAN-13:38 9615.76 7271.59 11381.76 0.00 0.00 0.00 0.00 0.00 557.24
February 17422.17 26-FEB-13:03 303.66 242.40 2276.35 0.00 0.00 0.00 0.00 0.00 303.68
March 13246.66 30-MAR-13:30 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 71.45 0.00
April 14036.06 17-APR-15:00 3846.30 2908.64 4552.71 0.00 0.00 0.00 0.00 58.48 0.00
May 11273.90 15-MAY-14:10 3846.30 2908.64 4552.71 0.00 0.00 0.00 0.00 36.33 0.00
June 17362.02 25-JUN-16:41 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 545.87 0.00
July 13970.14 15-JUL-03:02 0.00 657.65 3793.92 0.00 0.00 0.00 0.00 0.00 67.96
August 18216.02 06-AUG-13:42 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 546.27 0.00
September 18435.74 24-SEP-12:53 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 99.43 0.00
October 19076.74 09-OCT-14:42 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 0.00 13.12
November 18440.17 11-NOV-13:43 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 0.00 545.06
December 11380.90 08-DEC-14:10 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 397.34
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11273.90   0.00 242.40 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19076.74   9615.76 7271.59 11381.76 0.00 0.00 0.00 0.00 546.27 557.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3545.37 05-JAN-16:33 3717.98 2811.59 4400.81 0.00 0.00 0.00 0.00 0.00 378.66
February 6558.40 27-FEB-17:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 10.89
March 9128.98 30-MAR-16:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 70.52 0.00
April 17015.57 09-APR-17:01 0.00 364.48 3422.85 0.00 0.00 0.00 0.00 0.00 93.28
May 17705.99 21-MAY-17:42 0.00 260.35 2444.89 0.00 0.00 0.00 0.00 0.00 105.31
June 18723.39 25-JUN-16:41 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 267.89 0.00
July 18992.51 04-JUL-17:31 0.00 364.48 3422.85 0.00 0.00 0.00 0.00 97.77 0.00
August 18642.02 06-AUG-17:01 0.00 364.48 3422.85 0.00 0.00 0.00 0.00 236.86 0.00
September 12086.02 27-SEP-05:03 521.82 678.09 2607.89 0.00 0.00 0.00 0.00 0.00 14.87
October 9329.71 11-OCT-16:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 27.59 0.00
November 6016.06 06-NOV-16:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 77.92
December 3710.80 13-DEC-06:03 521.82 678.09 2607.89 0.00 0.00 0.00 0.00 0.00 74.83
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3545.37   0.00 260.35 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18992.51   3717.98 2811.59 4400.81 0.00 0.00 0.00 0.00 267.89 378.66



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2784.04 20-JAN-17:00 1923.11 1788.54 2276.32 0.00 0.00 0.00 0.00 0.00 152.44
February 3669.65 28-FEB-15:40 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 14.72
March 7047.72 30-MAR-16:00 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 127.45 0.00
April 7312.59 18-APR-14:20 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 28.78 0.00
May 9408.12 30-MAY-15:00 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 112.71 0.00
June 13531.80 26-JUN-05:02 1012.16 1315.28 5058.48 0.00 0.00 0.00 0.00 0.00 18.27
July 17321.87 23-JUL-17:01 0.00 565.58 5311.41 0.00 0.00 0.00 0.00 327.06 0.00
August 17796.77 06-AUG-17:01 0.00 565.58 5311.41 0.00 0.00 0.00 0.00 551.07 0.00
September 12892.92 27-SEP-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 29.21
October 6564.27 02-OCT-14:50 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 71.88 0.00
November 3619.81 04-NOV-05:02 1012.16 1315.28 5058.48 0.00 0.00 0.00 0.00 0.00 72.50
December 3042.60 13-DEC-15:10 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 88.19
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2784.04   0.00 565.58 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17796.77   1923.11 1788.54 5311.41 0.00 0.00 0.00 0.00 551.07 152.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2421.86 31-JAN-17:00 1239.33 1173.56 1466.95 0.00 0.00 0.00 0.00 0.00 39.52
February 3421.08 28-FEB-15:00 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 28.16 0.00
March 5339.66 30-MAR-11:00 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 38.68
April 9781.82 16-APR-09:53 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 0.00 166.37
May 15897.72 07-MAY-09:53 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 0.00 141.98
June 16865.62 04-JUN-11:23 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 76.59 0.00
July 17123.55 23-JUL-08:22 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 160.96
August 17604.16 06-AUG-11:02 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 109.06 0.00
September 10041.68 08-SEP-09:40 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 26.80 0.00
October 6420.15 11-OCT-10:30 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 0.30
November 3377.36 04-NOV-05:02 652.28 847.62 3259.88 0.00 0.00 0.00 0.00 0.00 47.45
December 2657.70 13-DEC-15:10 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 52.61
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2421.86   260.91 208.28 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17604.16   1295.83 1173.56 3259.88 0.00 0.00 0.00 0.00 109.06 166.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7336.26 11-JAN-14:50 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 197.56
February 13498.14 21-FEB-14:30 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 51.40
March 13794.26 30-MAR-13:50 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 95.79 0.00
April 15200.04 17-APR-14:05 3846.30 2908.64 4552.71 0.00 0.00 0.00 0.00 40.57 0.00
May 11023.85 30-MAY-14:30 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 120.53 0.00
June 14042.79 29-JUN-05:03 809.75 1052.25 4046.85 0.00 0.00 0.00 0.00 0.00 39.06
July 19390.10 23-JUL-17:01 0.00 565.60 5311.49 0.00 0.00 0.00 0.00 337.62 0.00
August 20533.56 06-AUG-13:42 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 633.40 0.00
September 20628.08 24-SEP-14:32 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 88.91 0.00
October 21119.79 09-OCT-14:32 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 0.00 21.59
November 17611.28 11-NOV-13:43 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 0.00 618.76
December 9880.06 12-DEC-13:50 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 47.04
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7336.26   0.00 323.20 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21119.79   3846.30 2908.64 5311.49 0.00 0.00 0.00 0.00 633.40 618.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3048.51 20-JAN-16:40 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 114.90
February 6289.79 27-FEB-17:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 14.29
March 9560.51 30-MAR-16:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 84.96 0.00
April 17582.73 09-APR-17:33 0.00 208.28 1955.92 0.00 0.00 0.00 0.00 0.00 149.25
May 19310.26 21-MAY-17:42 0.00 260.35 2444.89 0.00 0.00 0.00 0.00 0.00 144.48
June 20179.44 11-JUN-17:12 0.00 312.41 2933.87 0.00 0.00 0.00 0.00 201.58 0.00
July 20520.56 23-JUL-17:01 0.00 364.48 3422.85 0.00 0.00 0.00 0.00 89.15 0.00
August 20643.38 06-AUG-17:01 0.00 364.48 3422.85 0.00 0.00 0.00 0.00 263.79 0.00
September 15117.86 03-SEP-15:32 326.14 260.35 2444.89 0.00 0.00 0.00 0.00 69.78 0.00
October 10863.14 09-OCT-16:33 260.91 208.28 1955.92 0.00 0.00 0.00 0.00 5.81 0.00
November 5661.05 06-NOV-16:10 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 106.58
December 3192.92 12-DEC-14:50 1295.83 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 16.90
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3048.51   0.00 208.28 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20643.38   1295.83 937.20 3422.85 0.00 0.00 0.00 0.00 263.79 149.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4952.59 02-JAN-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 245.67
February 5638.68 21-FEB-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 282.72
March 7023.93 13-MAR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 98.79
April 8310.96 17-APR-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.60 0.00
May 10962.25 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.69
June 11125.54 26-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.78
July 10602.35 03-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.94
August 13408.52 14-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.03
September 12465.49 05-SEP-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54.20
October 10779.22 10-OCT-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 98.47
November 8321.76 06-NOV-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 232.12
December 6830.15 13-DEC-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 116.88
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4952.59   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13408.52   0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.60 282.72



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5428.65 27-JAN-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2801.92
February 7959.34 12-FEB-05:22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6806.23
March 5057.09 15-MAR-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 641.56
April 6190.98 17-APR-14:55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78.74 0.00
May 8380.49 30-MAY-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70.74
June 8555.02 26-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47.52
July 8253.65 24-JUL-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 77.61
August 8598.77 30-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75.26
September 7897.84 05-SEP-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90.75
October 5509.33 11-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 165.38
November 4766.87 21-NOV-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3739.19
December 5236.77 18-DEC-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2116.12
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4766.87   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8598.77   0.00 0.00 0.00 0.00 0.00 0.00 0.00 78.74 6806.23



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2134.95 31-JAN-17:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 143.68
February 7167.35 28-FEB-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 104.41
March 13968.58 30-MAR-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 107.66 0.00
April 18712.52 17-APR-14:55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70.05 0.00
May 19033.05 16-MAY-15:23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 87.80 0.00
June 19401.19 12-JUN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 243.98 0.00
July 21473.12 07-JUL-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 114.90 0.00
August 20461.65 01-AUG-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 192.39 0.00
September 16953.81 06-SEP-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 114.05 0.00
October 12443.83 10-OCT-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.16 0.00
November 5739.47 06-NOV-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 275.91
December 4145.75 12-DEC-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78.73
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2134.95   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21473.12   0.00 0.00 0.00 0.00 0.00 0.00 0.00 243.98 275.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1859.89 23-JAN-17:00 222.14 520.85 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3895.39 24-FEB-17:50 70.15 289.36 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 7173.25 31-MAR-24:00 0.00 28.94 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7885.44 09-APR-18:13 0.00 86.81 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
May 3499.96 31-MAY-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5356.39 30-JUN-24:00 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7236.04 31-JUL-23:53 0.00 115.75 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7861.64 13-AUG-19:32 0.00 144.69 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
September 3247.60 30-SEP-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5166.67 31-OCT-24:00 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5914.96 06-NOV-17:00 222.14 520.85 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7699.27 19-DEC-17:00 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1859.89   0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7885.44   222.14 520.85 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1527.92 27-JAN-17:00 222.14 520.85 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3616.38 24-FEB-17:50 70.15 289.36 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6725.37 31-MAR-24:00 0.00 28.94 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7351.78 14-APR-18:20 23.38 173.61 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3309.83 31-MAY-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5146.10 30-JUN-24:00 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7016.36 31-JUL-23:53 0.00 115.75 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7416.96 13-AUG-18:35 0.00 57.88 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
September 2744.13 30-SEP-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4483.19 31-OCT-24:00 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5514.27 06-NOV-17:00 222.14 520.85 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7111.63 08-DEC-17:00 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1527.92   0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7416.96   222.14 520.85 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1531.88 20-JAN-17:00 222.14 520.85 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3626.26 28-FEB-17:00 222.14 520.85 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6464.41 31-MAR-23:20 0.00 28.94 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7415.28 14-APR-18:20 23.38 173.61 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3262.56 31-MAY-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5120.83 30-JUN-24:00 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7047.42 31-JUL-23:53 0.00 115.75 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7566.92 13-AUG-19:32 0.00 144.69 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
September 2278.30 30-SEP-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4048.28 31-OCT-23:20 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5502.06 06-NOV-17:00 222.14 520.85 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7028.82 07-DEC-17:00 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1531.88   0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7566.92   222.14 520.85 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 91570.43 20-JAN-17:00 4808.68 5919.59 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 183221.00 28-FEB-17:00 4808.68 5919.59 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 357933.25 31-MAR-24:00 0.00 328.88 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 365785.66 20-APR-15:30 4808.68 5919.59 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 175217.85 31-MAY-24:00 0.00 328.88 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 267283.91 30-JUN-24:00 0.00 328.88 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 359513.21 31-JUL-23:53 0.00 1315.53 1518530.09 0.00 0.00 0.00 0.00 0.00 0.00
August 370334.94 07-AUG-21:12 1265.44 3288.82 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
September 175586.24 30-SEP-24:00 0.00 328.88 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 268167.23 31-OCT-24:00 0.00 328.88 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 277199.09 06-NOV-17:00 4808.68 5919.59 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 368140.31 12-DEC-17:00 4808.68 5919.59 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 91570.43   0.00 328.88 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 370334.94   4808.68 5919.59 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.167172E+13 1134900.15 31-JAN-16:00 0.325995E+12 1559351.01 09-JAN-07:10
February 0.191697E+13 1376166.00 27-FEB-16:30 0.212654E+12 1599222.50 13-FEB-07:10
March 0.265730E+13 1762364.59 29-MAR-15:50 0.865959E+11 656971.21 18-MAR-06:10
April 0.301480E+13 2018713.57 12-APR-15:09 0.625374E+11 745834.77 06-APR-06:10
May 0.207622E+13 1586520.64 16-MAY-15:39 0.584747E+11 268979.39 11-MAY-06:10
June 0.261561E+13 1712724.82 19-JUN-15:00 0.521492E+11 128934.32 03-JUN-11:00
July 0.312169E+13 1910194.72 07-JUL-15:20 0.483364E+11 66680.97 07-JUL-11:30
August 0.366896E+13 2051130.69 03-AUG-15:50 0.512757E+11 70462.62 25-AUG-13:50
September 0.206387E+13 1522680.10 05-SEP-15:20 0.495716E+11 189594.16 14-SEP-14:00
October 0.229729E+13 1619975.52 02-OCT-15:00 0.654302E+11 707441.57 26-OCT-06:10
November 0.251032E+13 1521432.58 27-NOV-16:00 0.100687E+12 1128143.48 22-NOV-07:10
December 0.287534E+13 1645685.23 12-DEC-16:00 0.184666E+12 1311098.38 18-DEC-07:10
             
Annual Sum or Average 0.304901E+14     0.129837E+13    
Minimum of Months 0.167172E+13 1134900.15   0.483364E+11 66680.97  
Maximum of Months 0.366896E+13 2051130.69   0.325995E+12 1599222.50  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.312650E+12 0.689787E+11 0.811612E+12 0.164871E+12 0.170947E+12 0.225934E+11 0.00 0.924887E+11 0.192115E+11 0.261356E+10 0.575761E+10 0.00 0.00
February 0.283633E+12 0.580988E+11 0.102011E+13 0.148927E+12 0.160822E+12 0.279201E+11 0.00 0.161428E+12 0.505042E+11 0.183575E+10 0.369348E+10 0.00 0.00
March 0.333264E+12 0.582202E+11 0.146267E+13 0.165151E+12 0.196678E+12 0.471699E+11 0.00 0.287151E+12 0.104195E+12 0.934868E+09 0.187303E+10 0.00 0.00
April 0.296614E+12 0.502467E+11 0.170311E+13 0.159525E+12 0.203786E+12 0.664587E+11 0.00 0.408205E+12 0.125026E+12 0.295935E+09 0.153716E+10 0.00 0.00
May 0.319000E+12 0.466141E+11 0.820521E+12 0.165009E+12 0.229264E+12 0.828557E+11 0.00 0.265424E+12 0.144240E+12 52100105.45 0.324272E+10 0.00 0.00
June 0.317018E+12 0.427810E+11 0.110677E+13 0.159787E+12 0.252068E+12 0.104173E+12 0.00 0.454243E+12 0.172485E+12 14620867.52 0.626239E+10 0.00 0.00
July 0.297201E+12 0.450818E+11 0.143888E+13 0.164745E+12 0.258660E+12 0.118010E+12 0.00 0.597831E+12 0.194324E+12 0.00 0.696296E+10 0.00 0.00
August 0.331525E+12 0.495156E+11 0.177780E+13 0.165150E+12 0.274450E+12 0.128724E+12 0.00 0.729556E+12 0.204519E+12 373973.73 0.772583E+10 0.00 0.00
September 0.297540E+12 0.537025E+11 0.784732E+12 0.159523E+12 0.223429E+12 0.875610E+11 0.00 0.296503E+12 0.156541E+12 0.00 0.433473E+10 0.00 0.00
October 0.311482E+12 0.618064E+11 0.112899E+13 0.164872E+12 0.199912E+12 0.560752E+11 0.00 0.260440E+12 0.111031E+12 40908317.60 0.264049E+10 0.00 0.00
November 0.308315E+12 0.653412E+11 0.140306E+13 0.159633E+12 0.180385E+12 0.381132E+11 0.00 0.261490E+12 0.904909E+11 0.121863E+10 0.226869E+10 0.00 0.00
December 0.302890E+12 0.704784E+11 0.175516E+13 0.164747E+12 0.175452E+12 0.220750E+11 0.00 0.296815E+12 0.817060E+11 0.193880E+10 0.408231E+10 0.00 0.00
                           
Annual Sum or Average 0.371113E+13 0.670866E+12 0.152134E+14 0.194194E+13 0.252585E+13 0.801729E+12 0.00 0.411157E+13 0.145427E+13 0.894555E+10 0.503814E+11 0.00 0.00
Minimum of Months 0.283633E+12 0.427810E+11 0.784732E+12 0.148927E+12 0.160822E+12 0.220750E+11 0.00 0.924887E+11 0.192115E+11 0.00 0.153716E+10 0.00 0.00
Maximum of Months 0.333264E+12 0.704784E+11 0.177780E+13 0.165151E+12 0.274450E+12 0.128724E+12 0.00 0.729556E+12 0.204519E+12 0.261356E+10 0.772583E+10 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.264655E+12 0.00 0.613396E+11 0.00 0.00
February 0.00 0.00 0.156916E+12 0.00 0.557376E+11 0.00 0.00
March 0.00 0.00 0.236842E+11 0.00 0.629117E+11 0.00 0.00
April 0.00 0.00 0.717924E+10 0.00 0.553581E+11 0.00 0.00
May 0.00 0.00 0.327461E+10 0.00 0.552001E+11 0.00 0.00
June 0.00 0.00 0.885605E+09 0.00 0.512636E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.483364E+11 0.00 0.00
August 0.00 0.00 44854437.23 0.00 0.512309E+11 0.00 0.00
September 0.00 0.00 0.558145E+09 0.00 0.490135E+11 0.00 0.00
October 0.00 0.00 0.120352E+11 0.00 0.533949E+11 0.00 0.00
November 0.00 0.00 0.453086E+11 0.00 0.553787E+11 0.00 0.00
December 0.00 0.00 0.126126E+12 0.00 0.585404E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.640668E+12 0.00 0.657705E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.483364E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.264655E+12 0.00 0.629117E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 346632.45 03-JAN-08:09 54335.80 01-JAN-06:10 439129.89 02-JAN-08:09 118954.02 03-JAN-08:20 195800.45 26-JAN-13:09 45955.96 07-JAN-05:10 0.00 01-JAN-00:10
February 350974.44 01-FEB-08:09 54335.80 01-FEB-06:10 557421.28 01-FEB-08:09 118957.65 01-FEB-08:20 147177.39 28-FEB-15:39 65820.21 28-FEB-15:39 0.00 01-FEB-00:10
March 347491.78 21-MAR-07:10 54335.80 01-MAR-06:10 675712.68 01-MAR-08:09 118954.74 21-MAR-07:19 181979.29 29-MAR-15:50 69360.56 30-MAR-14:39 0.00 01-MAR-00:10
April 341640.55 03-APR-07:10 54335.80 01-APR-05:10 794004.08 03-APR-07:10 118949.85 03-APR-07:19 280932.24 13-APR-14:50 73998.79 17-APR-14:20 0.00 01-APR-00:10
May 326430.59 24-MAY-07:10 54335.80 01-MAY-05:10 439129.89 01-MAY-07:10 118937.15 24-MAY-07:19 276227.21 16-MAY-15:39 69808.60 16-MAY-15:39 0.00 01-MAY-00:10
June 321357.89 23-JUN-07:10 54335.80 01-JUN-05:10 557421.28 01-JUN-07:10 118932.93 23-JUN-07:19 287700.46 02-JUN-13:39 68262.45 02-JUN-14:09 0.00 01-JUN-00:10
July 330486.50 27-JUL-07:10 54335.80 01-JUL-05:10 675712.68 03-JUL-07:10 118940.54 27-JUL-07:19 238506.86 07-JUL-15:20 68424.05 07-JUL-15:00 0.00 01-JUL-00:10
August 339089.73 24-AUG-07:10 54335.80 01-AUG-05:10 794004.08 01-AUG-07:10 118947.72 24-AUG-07:19 241762.26 25-AUG-10:39 69327.91 25-AUG-13:50 0.00 01-AUG-00:10
September 343869.80 29-SEP-07:10 54335.80 01-SEP-05:10 439129.89 01-SEP-07:10 118951.71 29-SEP-07:19 255461.63 22-SEP-14:00 69667.27 13-SEP-14:50 0.00 01-SEP-00:10
October 352689.08 30-OCT-07:10 54335.80 01-OCT-05:10 557421.28 02-OCT-07:10 118959.08 30-OCT-07:19 182132.67 02-OCT-15:00 70083.33 10-OCT-13:30 0.00 01-OCT-00:10
November 351688.64 01-NOV-07:10 54335.80 01-NOV-05:10 675712.68 01-NOV-07:10 118958.25 01-NOV-07:19 147483.43 06-NOV-16:19 44750.85 21-NOV-05:10 0.00 01-NOV-00:10
December 346756.74 06-DEC-08:09 54335.80 01-DEC-06:10 794004.08 01-DEC-08:09 118954.12 06-DEC-08:20 126125.02 14-DEC-08:30 45706.12 26-DEC-07:19 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 321357.89   54335.80   439129.89   118932.93   126125.02   44750.85   0.00  
Maximum of Months 352689.08   54335.80   794004.08   118959.08   287700.46   73998.79   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 119418.28 31-JAN-15:50 50484.77 19-JAN-15:00 5867.99 05-JAN-18:10 5613.48 02-JAN-07:10 0.00 0.00
February 195409.24 28-FEB-14:50 51473.78 28-FEB-14:00 5743.42 03-FEB-18:00 5613.48 01-FEB-07:10 0.00 0.00
March 373662.49 30-MAR-14:39 92421.41 29-MAR-15:50 5583.23 18-MAR-16:10 5613.48 01-MAR-07:10 0.00 0.00
April 437284.10 17-APR-14:20 92421.41 04-APR-13:30 4004.77 05-APR-18:00 5613.48 04-APR-08:00 0.00 0.00
May 323288.67 19-MAY-13:09 92421.41 03-MAY-14:20 2994.85 10-MAY-18:00 5613.48 02-MAY-11:00 0.00 0.00
June 362631.97 19-JUN-15:00 92421.41 01-JUN-08:20 2980.52 10-JUN-16:00 5613.48 01-JUN-06:40 0.00 0.00
July 436071.58 07-JUL-15:00 92421.41 01-JUL-06:10 0.00 01-JUL-00:10 5613.48 01-JUL-06:10 0.00 0.00
August 456189.80 17-AUG-13:09 92421.41 01-AUG-05:30 264.19 06-AUG-16:10 5613.48 01-AUG-06:10 0.00 0.00
September 329306.85 06-SEP-12:20 92421.41 01-SEP-10:09 0.00 01-SEP-00:10 5613.48 01-SEP-08:00 0.00 0.00
October 346337.74 10-OCT-13:30 92421.41 02-OCT-09:50 2663.41 31-OCT-20:00 5613.48 02-OCT-08:39 0.00 0.00
November 218208.27 02-NOV-13:50 70834.84 27-NOV-16:10 4329.13 22-NOV-18:10 5613.48 01-NOV-06:10 0.00 0.00
December 243200.64 12-DEC-14:30 52705.17 13-DEC-11:09 5337.55 02-DEC-17:00 5613.48 01-DEC-07:10 0.00 0.00
                     
Annual Sum or Average                 0.00 0.00
Minimum of Months 119418.28   50484.77   0.00   5613.48   0.00 0.00
Maximum of Months 456189.80   92421.41   5867.99   5613.48   0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1134900.15 31-JAN-16:00 323165.75 439129.89 0.00 84889.13 94703.41 43528.69 0.00 99815.13 49668.15
February 1376166.00 27-FEB-16:30 316816.17 557421.28 0.00 84885.75 140915.42 43691.79 0.00 182128.98 50109.82
March 1762364.59 29-MAR-15:50 316816.17 675712.68 0.00 84885.75 181979.29 67053.01 0.00 341625.13 92421.41
April 2018713.57 12-APR-15:09 316816.17 794004.08 0.00 84885.75 260940.64 69507.41 0.00 398266.95 92421.41
May 1586520.64 16-MAY-15:39 316816.17 439129.89 0.00 84885.75 276227.21 69808.60 0.00 305360.46 92421.41
June 1712724.82 19-JUN-15:00 316816.17 557421.28 0.00 84885.75 225146.74 67788.01 0.00 362631.97 92421.41
July 1910194.72 07-JUL-15:20 316816.17 675712.68 0.00 84885.75 238506.86 68038.93 0.00 428199.44 92421.41
August 2051130.69 03-AUG-15:50 316816.17 794004.08 0.00 84885.75 235348.48 68250.44 0.00 453790.90 92421.41
September 1522680.10 05-SEP-15:20 316816.17 439129.89 0.00 84885.75 214086.03 67530.04 0.00 302197.33 92421.41
October 1619975.52 02-OCT-15:00 316816.17 557421.28 0.00 84885.75 182132.67 67126.53 0.00 313558.23 92421.41
November 1521432.58 27-NOV-16:00 339848.75 675712.68 0.00 84902.80 98495.07 43713.22 0.00 207925.22 70834.84
December 1645685.23 12-DEC-16:00 336240.19 794004.08 0.00 84898.77 110235.50 43659.09 0.00 225127.10 51520.50
                       
Annual Sum or Average                      
Minimum of Months 1134900.15   316816.17 439129.89 0.00 84885.75 94703.41 43528.69 0.00 99815.13 49668.15
Maximum of Months 2051130.69   339848.75 794004.08 0.00 84902.80 276227.21 69808.60 0.00 453790.90 92421.41



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 1530223.80 09-JAN-07:10 0.00 79691.14 26-JAN-12:50 0.00
February 0.00 0.00 1589015.49 13-FEB-07:10 0.00 79681.57 03-FEB-12:20 0.00
March 0.00 0.00 646849.14 18-MAR-06:10 0.00 79100.29 01-MAR-12:30 0.00
April 0.00 0.00 717004.95 06-APR-06:10 0.00 76977.49 03-APR-11:30 0.00
May 0.00 0.00 240536.32 11-MAY-06:10 0.00 73997.68 02-MAY-11:30 0.00
June 0.00 0.00 100251.03 03-JUN-11:00 0.00 70363.16 01-JUN-11:39 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 66680.97 07-JUL-11:30 0.00
August 0.00 0.00 36074.67 25-AUG-13:50 0.00 65927.67 15-AUG-11:20 0.00
September 0.00 0.00 158357.94 14-SEP-14:00 0.00 69715.16 29-SEP-11:39 0.00
October 0.00 0.00 682233.93 26-OCT-06:10 0.00 73489.30 30-OCT-11:39 0.00
November 0.00 0.00 1099396.46 22-NOV-07:10 0.00 76493.81 27-NOV-12:00 0.00
December 0.00 0.00 1282117.36 18-DEC-07:10 0.00 78817.47 29-DEC-12:50 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 65927.67   0.00
Maximum of Months 0.00 0.00 1589015.49   0.00 79691.14   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 5.17 27.12 2.00 27.21
February 0.00 0.00 0.00 0.00 2.00 26.38 0.00 26.38
March 0.00 0.00 0.00 0.00 1.33 25.72 0.00 25.72
April 0.00 0.00 0.00 0.00 1.83 25.67 0.00 25.67
May 0.00 0.00 0.00 0.00 2.50 25.89 0.00 25.89
June 0.00 0.00 0.00 0.00 3.50 26.09 0.00 26.09
July 0.00 0.00 0.00 0.00 5.00 26.05 0.00 26.05
August 0.00 0.00 0.00 0.00 8.50 26.23 0.00 26.23
September 0.00 0.00 0.00 0.00 8.00 26.32 0.50 26.33
October 0.00 0.00 0.00 0.00 11.00 26.54 0.33 26.56
November 0.00 0.00 0.00 0.00 11.33 26.69 0.17 26.70
December 0.00 0.00 0.00 0.00 8.17 26.64 1.00 26.73
                 
Annual Sum or Average 0.00   0.00   68.33 26.43 4.00 26.48
Minimum of Months 0.00 0.00 0.00 0.00 1.33 25.67 0.00 25.67
Maximum of Months 0.00 0.00 0.00 0.00 11.33 27.12 2.00 27.21



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 25.62 0.00 25.62
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.83 25.61 0.00 25.61
September 0.00 0.00 0.00 0.00 0.50 25.59 0.00 25.59
October 0.00 0.00 0.00 0.00 0.17 25.62 0.00 25.62
November 0.00 0.00 0.00 0.00 0.50 25.60 0.00 25.60
December 0.00 0.00 0.00 0.00 0.17 25.60 0.00 25.60
                 
Annual Sum or Average 0.00   0.00   2.33 25.60 0.00 25.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 25.62 0.00 25.62



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 24.60 0.17 24.60
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 24.60 0.17 24.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 24.60 0.17 24.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 18.86 0.17 18.97 0.00 18.97 0.00 18.97
February 1.17 18.93 0.17 19.10 0.00 19.10 0.00 19.10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.17 19.12 0.17 19.28 0.00 19.28 0.00 19.28
                 
Annual Sum or Average 4.50 18.95 0.50 19.09 0.00 19.09 0.00 19.09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.17 19.12 0.17 19.28 0.00 19.28 0.00 19.28



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 26.73 0.33 26.95
August 0.00 0.00 0.00 0.00 0.50 25.69 0.00 25.69
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.00 26.21 0.33 26.48
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.50 26.73 0.33 26.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 27.28 0.17 27.28
May 0.00 0.00 0.00 0.00 1.33 27.49 1.33 27.49
June 0.00 0.00 0.00 0.00 2.50 27.74 2.50 27.74
July 0.00 0.00 0.00 0.00 3.00 27.72 3.00 27.72
August 0.00 0.00 0.00 0.00 2.17 27.64 2.17 27.64
September 0.00 0.00 0.00 0.00 1.17 27.50 1.17 27.50
October 0.00 0.00 0.00 0.00 0.17 27.33 0.17 27.33
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   10.50 27.64 10.50 27.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.00 27.74 3.00 27.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.21 0.00 19.21 0.00 19.21 0.00 19.21
February 0.17 19.39 0.00 19.39 1.83 26.82 1.83 27.14
March 0.00 0.00 0.00 0.00 0.17 27.32 0.17 27.32
April 0.00 0.00 0.00 0.00 0.33 27.38 0.33 27.38
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 27.37 0.50 27.37
August 0.00 0.00 0.00 0.00 4.50 27.29 4.00 27.39
September 0.00 0.00 0.00 0.00 1.00 27.68 1.00 27.68
October 0.00 0.00 0.00 0.00 4.50 27.72 4.50 27.72
November 0.00 0.00 0.00 0.00 3.00 27.67 3.00 27.67
December 0.00 0.00 0.00 0.00 0.83 27.39 0.83 27.39
                 
Annual Sum or Average 0.33 19.30 0.00 19.30 16.67 27.37 16.17 27.47
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.39 0.00 19.39 4.50 27.72 4.50 27.72



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.33 27.36 0.33 27.36
March 0.00 0.00 0.00 0.00 3.67 27.62 2.00 27.63
April 0.00 0.00 0.00 0.00 10.17 27.36 4.33 27.46
May 0.00 0.00 0.00 0.00 3.00 27.68 1.33 27.69
June 0.00 0.00 0.00 0.00 15.17 27.36 4.50 27.47
July 0.00 0.00 0.00 0.00 23.50 27.31 6.67 27.49
August 0.00 0.00 0.00 0.00 30.17 27.30 6.67 27.46
September 0.00 0.00 0.00 0.00 3.50 27.53 2.33 27.55
October 0.00 0.00 0.00 0.00 2.83 27.76 2.00 27.80
November 0.00 0.00 0.00 0.00 1.83 27.45 1.67 27.46
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   94.17 27.37 31.83 27.50
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 30.17 27.76 6.67 27.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.50 18.81 1.17 19.00 0.00 19.00 0.00 19.00
February 7.00 17.57 2.17 17.68 0.00 17.68 0.00 17.68
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 27.27 0.33 27.27
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 19.20 0.00 19.20 0.00 19.20 0.00 19.20
December 2.67 18.98 0.33 19.11 0.00 19.11 0.00 19.11
                 
Annual Sum or Average 17.50 18.35 3.67 18.44 0.33 18.58 0.33 18.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7.50 19.20 2.17 19.20 0.33 27.27 0.33 27.27



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.00 18.52 0.00 18.52 0.00 18.52 0.00 18.52
February 4.00 17.27 0.33 17.07 0.00 17.07 0.00 17.07
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 27.43 0.33 27.43
May 0.00 0.00 0.00 0.00 1.17 27.54 1.17 27.54
June 0.00 0.00 0.00 0.00 3.33 27.76 3.33 27.76
July 0.00 0.00 0.00 0.00 5.50 27.71 5.50 27.71
August 0.00 0.00 0.00 0.00 4.33 27.67 4.33 27.67
September 0.00 0.00 0.00 0.00 0.83 27.43 0.83 27.43
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 19.24 0.00 19.24 0.00 19.24 0.00 19.24
December 1.83 18.94 0.00 18.94 0.00 18.94 0.00 18.94
                 
Annual Sum or Average 11.17 18.16 0.33 18.06 15.50 23.58 15.50 25.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.00 19.24 0.33 19.24 5.50 27.76 5.50 27.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.50 18.88 0.17 18.93 0.17 19.12 0.17 19.30
February 2.83 17.70 0.33 17.40 1.00 19.86 1.00 21.38
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 27.33 0.50 27.33
August 0.00 0.00 0.00 0.00 3.33 27.43 3.33 27.43
September 0.00 0.00 0.00 0.00 1.33 27.56 1.33 27.56
October 0.00 0.00 0.00 0.00 4.33 27.69 4.33 27.69
November 0.17 19.44 0.00 19.44 2.17 27.06 2.17 27.35
December 1.17 19.11 0.00 19.11 0.50 21.58 0.50 22.91
                 
Annual Sum or Average 8.67 18.53 0.50 18.43 13.33 23.83 13.33 25.21
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.50 19.44 0.33 19.44 4.33 27.69 4.33 27.69



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.33 18.75 0.00 18.75 0.00 18.75 0.00 18.75
February 3.00 17.77 0.50 17.36 0.00 17.36 0.00 17.36
March 0.00 0.00 0.00 0.00 0.17 27.26 0.17 27.26
April 0.00 0.00 0.00 0.00 1.00 27.56 0.67 27.54
May 0.00 0.00 0.00 0.00 2.17 27.64 1.17 27.63
June 0.00 0.00 0.00 0.00 4.17 27.88 2.17 27.89
July 0.00 0.00 0.00 0.00 7.33 28.01 3.50 28.01
August 0.00 0.00 0.00 0.00 5.67 27.82 2.83 27.90
September 0.00 0.00 0.00 0.00 1.00 27.49 0.67 27.50
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 19.28 0.00 19.28 0.00 19.28 0.00 19.28
December 1.50 19.08 0.00 19.08 0.00 19.08 0.00 19.08
                 
Annual Sum or Average 9.17 18.50 0.50 18.32 21.50 24.89 11.17 25.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.33 19.28 0.50 19.28 7.33 28.01 3.50 28.01



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 42.83 16.92 13.50 17.04 0.00 17.04 0.00 17.04
February 26.83 16.49 8.83 16.61 0.00 16.61 0.00 16.61
March 0.83 19.22 0.00 19.22 0.00 19.22 0.00 19.22
April 0.17 19.33 0.00 19.33 0.00 19.33 0.00 19.33
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.67 27.44 0.33 27.45
July 0.00 0.00 0.00 0.00 2.83 27.51 1.67 27.51
August 0.00 0.00 0.00 0.00 0.67 27.35 0.50 27.35
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.17 19.26 0.00 19.26 0.00 19.26 0.00 19.26
November 2.67 18.70 0.33 18.87 0.00 18.87 0.00 18.87
December 23.33 17.15 7.00 17.32 0.00 17.32 0.00 17.32
                 
Annual Sum or Average 96.83 16.93 29.67 17.05 4.17 17.39 2.50 17.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 42.83 19.33 13.50 19.33 2.83 27.51 1.67 27.51



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 25.00 16.09 4.50 15.99 0.00 15.99 0.00 15.99
February 14.67 16.10 1.67 16.08 0.00 16.08 0.00 16.08
March 0.67 19.22 0.00 19.22 0.00 19.22 0.00 19.22
April 0.17 19.37 0.00 19.37 0.00 19.37 0.00 19.37
May 0.00 0.00 0.00 0.00 0.83 27.49 0.83 27.49
June 0.00 0.00 0.00 0.00 5.83 27.71 5.33 27.73
July 0.00 0.00 0.00 0.00 11.83 27.67 10.67 27.69
August 0.00 0.00 0.00 0.00 7.00 27.74 6.50 27.75
September 0.00 0.00 0.00 0.00 0.67 27.37 0.67 27.37
October 0.17 19.28 0.00 19.28 0.00 19.28 0.00 19.28
November 2.00 18.42 0.00 18.42 0.00 18.42 0.00 18.42
December 12.67 16.86 1.17 16.82 0.00 16.82 0.00 16.82
                 
Annual Sum or Average 55.33 16.41 7.33 16.32 26.17 19.67 24.00 21.38
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.99 0.00 15.99
Maximum of Months 25.00 19.37 4.50 19.37 11.83 27.74 10.67 27.75



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 20.17 16.93 4.00 16.95 0.00 16.95 0.00 16.95
February 12.50 16.60 2.50 16.60 0.00 16.60 0.00 16.60
March 0.33 19.24 0.00 19.24 0.00 19.24 0.00 19.24
April 0.00 0.00 0.00 0.00 0.17 27.29 0.17 27.29
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.17 27.38 1.00 27.39
July 0.00 0.00 0.00 0.00 3.00 27.54 2.17 27.55
August 0.00 0.00 0.00 0.00 5.50 27.62 4.83 27.63
September 0.00 0.00 0.00 0.00 1.33 27.67 1.33 27.67
October 0.00 0.00 0.00 0.00 2.83 27.65 2.83 27.65
November 1.17 18.34 0.00 18.34 0.50 21.05 0.50 22.50
December 7.33 18.26 0.83 18.24 0.00 18.24 0.00 18.24
                 
Annual Sum or Average 41.50 17.12 7.33 17.10 14.50 19.50 12.83 20.87
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20.17 19.24 4.00 19.24 5.50 27.67 4.83 27.67



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 17.83 16.24 3.33 16.02 0.00 16.02 0.00 16.02
February 10.50 16.19 2.17 15.98 0.00 15.98 0.00 15.98
March 0.17 19.20 0.00 19.20 0.00 19.20 0.00 19.20
April 0.00 0.00 0.00 0.00 1.00 27.52 0.67 27.49
May 0.00 0.00 0.00 0.00 2.67 27.41 1.50 27.31
June 0.00 0.00 0.00 0.00 5.00 28.03 2.50 28.04
July 0.00 0.00 0.00 0.00 9.50 28.07 4.33 28.09
August 0.00 0.00 0.00 0.00 6.83 28.04 3.67 28.08
September 0.00 0.00 0.00 0.00 1.17 27.53 0.83 27.54
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.33 18.13 0.00 18.13 0.00 18.13 0.00 18.13
December 5.67 18.13 0.33 18.10 0.00 18.10 0.00 18.10
                 
Annual Sum or Average 35.50 16.61 5.83 16.39 26.17 20.87 13.50 22.05
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17.83 19.20 3.33 19.20 9.50 28.07 4.33 28.09



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 40.67 27.76 40.67 27.76
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   40.67 27.76 40.67 27.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 40.67 27.76 40.67 27.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 45.33 27.78 45.33 27.78
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   45.33 27.78 45.33 27.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 45.33 27.78 45.33 27.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 40.67 27.81 40.67 27.81
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   40.67 27.81 40.67 27.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 40.67 27.81 40.67 27.81



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 56.67 28.00 53.00 28.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 418.33 29.00 367.00 29.03
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   475.00 28.88 420.00 28.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 418.33 29.00 367.00 29.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 213.50 23.96 80.50 24.34 0.00 24.34
February 147.00 24.22 90.00 24.66 12.67 24.77
March 56.33 24.01 179.50 24.71 1.00 24.70
April 55.67 24.55 261.50 24.76 34.83 24.77
May 146.67 24.62 435.83 24.56 139.83 24.58
June 222.83 24.59 455.67 24.52 222.83 24.54
July 282.83 25.07 497.00 24.78 282.83 24.85
August 243.33 25.01 514.00 24.66 243.33 24.74
September 158.83 25.24 475.33 24.74 158.83 24.84
October 41.83 25.43 314.00 25.02 41.83 25.06
November 39.33 25.09 217.83 25.29 23.17 25.33
December 76.17 24.00 165.00 25.04 1.17 25.04
             
Annual Sum or Average 1684.33 24.67 3686.17 24.72 1162.33 24.77
Minimum of Months 39.33 23.96 80.50 24.34 0.00 24.34
Maximum of Months 282.83 25.43 514.00 25.29 282.83 25.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 300.17 23.95 55.00 24.06 12.67 24.13
February 168.50 24.07 80.00 24.34 9.67 24.40
March 41.17 23.99 196.17 24.54 0.00 24.54
April 6.33 24.00 296.17 24.47 0.00 24.47
May 1.17 24.00 448.33 24.35 0.00 24.35
June 0.00 0.00 457.00 24.26 0.00 24.26
July 0.00 0.00 497.00 24.26 0.00 24.26
August 0.00 0.00 514.00 24.19 0.00 24.19
September 3.83 26.72 477.83 24.38 3.83 24.39
October 13.33 25.85 312.17 24.68 11.33 24.73
November 35.33 24.06 209.50 24.79 1.00 24.80
December 86.83 23.99 142.00 24.72 0.00 24.72
             
Annual Sum or Average 656.67 24.05 3685.17 24.38 38.50 24.39
Minimum of Months 0.00 0.00 55.00 24.06 0.00 24.13
Maximum of Months 300.17 26.72 514.00 24.79 12.67 24.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 474.17 22.83 36.83 22.77 32.50 22.71
February 365.83 23.20 39.50 23.22 22.50 23.20
March 176.50 23.75 128.00 24.02 0.00 24.02
April 61.50 23.79 225.00 24.31 1.33 24.31
May 14.50 23.84 432.50 24.27 0.00 24.27
June 5.50 23.76 444.67 24.24 0.00 24.24
July 0.00 0.00 496.00 24.26 0.00 24.26
August 0.00 0.00 514.00 24.22 0.00 24.22
September 8.67 25.63 457.67 24.31 7.50 24.34
October 84.67 23.75 220.50 24.23 14.00 24.26
November 237.67 23.77 86.83 23.90 3.67 23.91
December 408.67 23.34 39.17 23.41 0.00 23.41
             
Annual Sum or Average 1837.67 23.33 3120.67 23.91 81.50 23.89
Minimum of Months 0.00 0.00 36.83 22.77 0.00 22.71
Maximum of Months 474.17 25.63 514.00 24.31 32.50 24.34



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 490.67 21.31 179.33 20.94 177.50 20.72
February 418.17 22.11 97.00 21.85 87.67 21.64
March 314.33 23.13 105.50 23.32 9.00 23.27
April 144.00 23.39 193.83 23.91 3.33 23.92
May 28.67 23.61 424.83 24.21 0.00 24.21
June 6.67 23.67 444.67 24.26 0.00 24.26
July 0.83 23.14 488.83 24.30 0.00 24.30
August 0.00 0.00 514.00 24.26 0.00 24.26
September 25.50 23.81 430.33 24.26 7.17 24.28
October 237.83 23.10 147.17 23.46 13.67 23.46
November 406.50 22.83 61.50 22.87 26.00 22.82
December 461.00 21.80 128.33 21.57 109.33 21.35
             
Annual Sum or Average 2534.17 22.34 3215.33 23.13 433.67 22.94
Minimum of Months 0.00 0.00 61.50 20.94 0.00 20.72
Maximum of Months 490.67 23.81 514.00 24.30 177.50 24.30



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 476.50 21.63 139.67 21.45 134.00 21.32
February 403.67 22.24 77.00 22.06 66.83 21.88
March 313.50 23.24 95.33 23.46 0.00 23.46
April 127.50 23.39 214.67 23.94 0.00 23.94
May 35.33 24.00 411.83 24.28 6.67 24.30
June 10.00 24.71 453.50 24.33 4.67 24.35
July 12.83 26.05 497.00 24.41 12.83 24.45
August 3.33 26.68 514.00 24.28 3.33 24.29
September 39.83 24.83 425.17 24.39 24.00 24.46
October 222.33 23.29 175.83 23.72 9.00 23.76
November 358.67 23.13 73.83 23.32 0.00 23.32
December 435.33 22.55 42.00 22.61 10.17 22.58
             
Annual Sum or Average 2438.83 22.70 3119.83 23.46 271.50 23.38
Minimum of Months 3.33 21.63 42.00 21.45 0.00 21.32
Maximum of Months 476.50 26.68 514.00 24.41 134.00 24.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 496.83 21.72 99.00 21.54 99.00 21.42
February 392.50 22.04 51.50 22.00 40.50 21.89
March 308.50 22.83 97.83 23.19 0.00 23.19
April 138.67 22.94 222.33 23.69 0.67 23.70
May 61.83 24.16 406.00 24.34 19.33 24.43
June 20.83 25.31 457.50 24.34 12.33 24.40
July 29.67 25.94 483.17 24.41 25.17 24.51
August 16.50 26.57 504.00 24.25 16.00 24.32
September 68.00 24.15 403.00 24.29 28.67 24.39
October 226.67 22.88 188.83 23.54 8.67 23.58
November 376.67 22.76 54.50 22.96 1.33 22.95
December 463.50 22.20 30.67 22.23 12.17 22.19
             
Annual Sum or Average 2600.17 22.53 2998.33 23.37 263.83 23.36
Minimum of Months 16.50 21.72 30.67 21.54 0.00 21.42
Maximum of Months 496.83 26.57 504.00 24.41 99.00 24.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 411.50 21.94 92.33 21.82 76.50 21.64
February 327.33 22.32 59.83 22.45 26.33 22.33
March 212.50 23.07 155.00 23.66 0.17 23.66
April 109.50 23.20 257.00 23.98 0.67 23.99
May 43.50 23.90 404.17 24.28 8.83 24.31
June 12.33 24.23 443.67 24.30 3.67 24.31
July 20.17 26.15 494.50 24.43 20.17 24.49
August 22.00 26.71 514.00 24.39 22.00 24.48
September 63.33 24.87 438.33 24.48 35.83 24.60
October 155.33 23.47 271.00 24.11 25.50 24.24
November 232.67 23.17 133.00 23.71 10.17 23.76
December 339.83 22.55 61.00 22.75 11.83 22.70
             
Annual Sum or Average 1950.00 22.82 3323.83 23.72 241.67 23.72
Minimum of Months 12.33 21.94 59.83 21.82 0.17 21.64
Maximum of Months 411.50 26.71 514.00 24.48 76.50 24.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 454.17 21.94 43.00 21.91 32.67 21.84
February 307.00 22.48 73.83 22.81 13.00 22.74
March 100.17 23.45 257.50 24.30 4.33 24.34
April 39.17 25.74 397.00 24.71 26.67 24.84
May 33.17 25.10 461.67 24.46 18.33 24.54
June 36.83 26.87 484.33 24.61 36.83 24.76
July 53.67 26.81 497.00 24.75 53.67 24.93
August 61.17 26.68 514.00 24.69 61.17 24.88
September 47.33 26.16 450.83 24.62 41.33 24.77
October 107.33 23.68 301.83 24.40 19.00 24.50
November 142.83 23.30 191.00 24.16 5.00 24.20
December 231.00 23.19 104.33 23.69 0.00 23.69
             
Annual Sum or Average 1613.83 23.29 3776.33 24.13 312.00 24.23
Minimum of Months 33.17 21.94 43.00 21.91 0.00 21.84
Maximum of Months 454.17 26.87 514.00 24.75 61.17 24.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.46 357.50 20.29 357.50 20.22
February 450.33 21.14 167.83 20.85 167.83 20.68
March 434.67 22.30 93.83 22.39 33.33 22.29
April 257.67 22.87 140.83 23.32 10.00 23.33
May 84.00 23.48 369.67 24.10 11.83 24.12
June 35.50 25.19 434.33 24.39 25.00 24.47
July 60.00 25.53 490.83 24.53 56.33 24.64
August 53.33 25.69 514.00 24.45 53.33 24.56
September 87.17 24.00 381.67 24.21 36.50 24.31
October 371.00 22.48 116.00 22.83 19.67 22.87
November 463.50 21.89 73.50 21.78 62.00 21.65
December 485.67 20.84 231.00 20.64 224.67 20.52
             
Annual Sum or Average 3284.83 21.87 3371.00 22.57 1058.00 22.38
Minimum of Months 35.50 20.46 73.50 20.29 10.00 20.22
Maximum of Months 502.00 25.69 514.00 24.53 357.50 24.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.50 282.33 20.34 282.33 20.27
February 368.00 21.18 133.00 20.92 131.50 20.76
March 343.17 22.30 56.00 22.49 8.50 22.46
April 179.33 22.70 144.33 23.47 8.00 23.50
May 94.33 23.75 301.33 24.30 25.50 24.42
June 44.17 25.55 378.17 24.56 32.33 24.69
July 78.00 25.75 405.17 24.76 65.50 24.95
August 61.17 26.25 427.67 24.65 61.17 24.83
September 105.50 23.74 298.50 24.24 37.17 24.38
October 276.50 22.29 113.00 22.84 17.83 22.88
November 396.00 21.86 40.00 21.83 28.83 21.75
December 421.67 20.87 163.67 20.64 163.67 20.51
             
Annual Sum or Average 2794.83 21.96 2743.17 22.71 862.33 22.59
Minimum of Months 44.17 20.50 40.00 20.34 8.00 20.27
Maximum of Months 427.00 26.25 427.67 24.76 282.33 24.95



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 444.17 21.33 178.00 21.04 171.83 20.84
February 373.00 21.76 99.00 21.71 77.33 21.52
March 284.17 22.63 125.83 23.17 5.83 23.15
April 176.33 22.92 204.83 23.70 6.50 23.73
May 76.33 23.41 376.00 24.12 11.33 24.15
June 43.83 24.70 431.67 24.34 23.17 24.42
July 60.50 25.52 485.83 24.53 55.83 24.64
August 60.00 26.08 514.00 24.56 60.00 24.70
September 84.33 24.54 419.17 24.43 44.00 24.56
October 216.33 22.98 233.33 23.74 33.67 23.87
November 313.33 22.64 96.17 23.04 18.67 23.02
December 398.83 21.71 103.00 21.63 73.00 21.41
             
Annual Sum or Average 2531.17 22.45 3266.83 23.30 581.17 23.24
Minimum of Months 43.83 21.33 96.17 21.04 5.83 20.84
Maximum of Months 444.17 26.08 514.00 24.56 171.83 24.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.75 275.50 20.55 275.50 20.46
February 432.83 21.27 127.17 21.06 122.67 20.89
March 357.67 22.24 101.17 22.64 8.83 22.61
April 192.00 22.80 218.33 23.64 8.50 23.69
May 84.17 23.45 381.83 24.16 16.50 24.22
June 46.33 25.10 448.50 24.44 28.00 24.55
July 64.17 25.81 481.50 24.61 57.33 24.76
August 52.67 26.52 514.00 24.60 52.67 24.76
September 98.50 23.82 378.50 24.24 37.67 24.36
October 315.17 22.40 143.33 22.97 16.17 23.02
November 434.50 21.95 51.00 21.98 29.50 21.90
December 484.17 21.12 148.33 20.92 145.17 20.79
             
Annual Sum or Average 3064.17 21.97 3269.17 22.83 798.50 22.71
Minimum of Months 46.33 20.75 51.00 20.55 8.50 20.46
Maximum of Months 502.00 26.52 514.00 24.61 275.50 24.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.04 415.67 19.91 415.67 19.87
February 451.50 20.72 252.17 20.48 252.17 20.36
March 449.50 21.63 128.50 21.64 80.17 21.47
April 298.50 22.34 130.33 22.71 29.00 22.65
May 122.83 23.07 342.33 23.91 15.83 23.94
June 57.00 24.69 429.67 24.37 31.50 24.46
July 77.00 25.32 482.17 24.54 67.50 24.66
August 63.50 25.67 511.17 24.47 63.50 24.59
September 126.83 23.42 326.83 24.03 38.33 24.13
October 399.83 21.84 106.67 22.17 31.83 22.17
November 479.00 21.15 180.83 20.92 175.00 20.77
December 492.50 20.28 337.67 20.07 337.67 19.99
             
Annual Sum or Average 3520.00 21.43 3644.00 22.10 1538.17 21.87
Minimum of Months 57.00 20.04 106.67 19.91 15.83 19.87
Maximum of Months 502.00 25.67 511.17 24.54 415.67 24.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.13 396.00 20.00 396.00 19.96
February 447.17 20.94 208.00 20.64 208.00 20.49
March 420.33 21.95 95.67 22.05 40.83 21.94
April 233.67 22.44 174.33 23.16 16.33 23.14
May 114.33 23.51 364.17 24.16 30.00 24.27
June 54.50 25.52 450.50 24.51 40.00 24.66
July 93.33 25.62 473.67 24.68 77.17 24.87
August 72.00 26.19 504.67 24.60 70.67 24.78
September 133.67 23.35 348.50 24.07 40.83 24.20
October 332.83 21.91 133.83 22.43 27.50 22.42
November 472.17 21.33 117.83 21.15 113.00 21.02
December 497.00 20.37 302.00 20.14 302.00 20.04
             
Annual Sum or Average 3373.00 21.61 3569.17 22.34 1362.33 22.15
Minimum of Months 54.50 20.13 95.67 20.00 16.33 19.96
Maximum of Months 502.00 26.19 504.67 24.68 396.00 24.87



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 480.67 20.80 268.33 20.44 268.33 20.27
February 393.17 21.23 172.83 21.04 155.83 20.83
March 333.67 22.10 135.50 22.47 35.83 22.32
April 229.50 22.49 187.17 23.23 17.50 23.22
May 119.17 23.10 344.50 23.96 18.17 24.00
June 63.17 24.42 421.50 24.33 29.17 24.43
July 80.17 25.29 481.17 24.53 68.33 24.66
August 66.83 26.03 512.17 24.57 66.83 24.72
September 109.17 23.95 390.67 24.29 46.83 24.44
October 261.50 22.32 206.00 23.18 33.17 23.24
November 368.00 21.92 112.83 22.05 62.50 21.88
December 443.00 21.03 204.33 20.74 182.17 20.49
             
Annual Sum or Average 2948.00 21.97 3437.00 22.76 984.67 22.59
Minimum of Months 63.17 20.80 112.83 20.44 17.50 20.27
Maximum of Months 480.67 26.03 512.17 24.57 268.33 24.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.28 350.67 20.10 350.67 20.03
February 438.33 20.91 191.50 20.68 187.83 20.54
March 391.50 21.79 117.33 22.05 42.17 21.92
April 240.50 22.40 192.50 23.21 18.00 23.23
May 126.00 23.12 354.33 23.98 20.67 24.06
June 63.83 24.76 436.17 24.42 34.50 24.55
July 83.67 25.50 475.50 24.59 69.00 24.76
August 61.17 26.44 509.83 24.61 61.17 24.78
September 137.33 23.34 343.17 24.07 41.33 24.20
October 350.67 21.95 126.50 22.49 20.50 22.53
November 454.00 21.40 114.00 21.27 103.17 21.13
December 494.00 20.61 257.00 20.35 257.00 20.22
             
Annual Sum or Average 3343.00 21.63 3468.50 22.41 1206.00 22.23
Minimum of Months 61.17 20.28 114.00 20.10 18.00 20.03
Maximum of Months 502.00 26.44 509.83 24.61 350.67 24.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 498.50 27.00 0.00 27.00
February 0.83 27.00 454.00 27.00 0.83 27.00
March 38.50 27.00 514.00 27.00 38.50 27.00
April 188.50 27.00 485.00 27.00 188.50 27.00
May 2.50 27.00 508.00 27.00 2.50 27.00
June 149.17 27.00 496.00 27.00 149.17 27.00
July 259.33 27.00 497.00 27.00 259.33 27.00
August 485.17 27.12 514.00 27.11 485.17 27.11
September 32.00 27.00 485.00 27.00 32.00 27.00
October 27.50 27.00 502.00 27.00 27.50 27.00
November 18.17 27.00 489.00 27.00 18.17 27.00
December 24.67 27.00 497.00 27.00 24.67 27.00
             
Annual Sum or Average 1226.33 27.05 5939.50 27.02 1226.33 27.02
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 485.17 27.12 514.00 27.11 485.17 27.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 15.50 25.78 364.50 26.95 0.00 26.95
February 0.00 0.00 397.17 27.00 0.00 27.00
March 0.33 27.00 514.00 27.00 0.33 27.00
April 3.83 27.00 485.00 27.00 3.83 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 0.00 0.00 496.00 27.00 0.00 27.00
July 22.50 27.00 497.00 27.00 22.50 27.00
August 134.33 27.44 514.00 27.18 134.33 27.23
September 1.33 27.00 485.00 27.00 1.33 27.00
October 0.00 0.00 502.00 27.00 0.00 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 485.00 27.00 0.00 27.00
             
Annual Sum or Average 177.83 27.22 5736.67 27.02 162.33 27.03
Minimum of Months 0.00 0.00 364.50 26.95 0.00 26.95
Maximum of Months 134.33 27.44 514.00 27.18 134.33 27.23



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 153.50 24.81 255.83 25.97 19.67 25.83
February 26.17 26.99 347.50 27.00 0.00 27.00
March 2.83 27.00 499.17 27.00 2.83 27.00
April 17.83 27.00 485.00 27.00 17.83 27.00
May 1.83 27.00 508.00 27.00 1.83 27.00
June 48.00 27.00 496.00 27.00 48.00 27.00
July 114.67 27.00 497.00 27.00 114.67 27.00
August 176.50 27.31 514.00 27.16 176.50 27.19
September 15.33 27.00 485.00 27.00 15.33 27.00
October 0.83 27.00 502.00 27.00 0.83 27.00
November 0.00 0.00 458.83 27.00 0.00 27.00
December 10.00 27.00 396.83 27.00 0.00 27.00
             
Annual Sum or Average 567.50 26.50 5445.17 26.95 397.50 26.95
Minimum of Months 0.00 0.00 255.83 25.97 0.00 25.83
Maximum of Months 176.50 27.31 514.00 27.16 176.50 27.19



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 285.50 27.00 502.00 27.00 285.50 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.14 485.00 27.14 485.00 27.14
May 505.17 27.00 508.00 27.00 505.17 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 28.52 514.00 28.52 514.00 28.52
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.01 497.00 27.01 497.00 27.01
             
Annual Sum or Average 5723.67 27.15 5943.00 27.15 5723.67 27.15
Minimum of Months 285.50 27.00 454.00 27.00 285.50 27.00
Maximum of Months 514.00 28.52 514.00 28.52 514.00 28.52



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00007 21.64979 0.72791 16.36507
February 454.00000 27.00011 24.16533 0.81340 19.14950
March 514.00000 27.00018 29.03942 0.93500 23.57720
April 485.00000 27.00010 32.61407 1.01220 26.69237
May 508.00000 27.00087 36.67141 0.29009 6.82504
June 496.00000 27.00153 37.48103 0.36209 7.79643
July 497.00000 27.00104 37.95938 0.41487 8.63857
August 514.00000 27.11037 37.91760 0.49821 10.36098
September 485.00000 27.00076 38.49002 0.31448 7.13116
October 502.00000 27.00070 33.71341 0.95081 24.15222
November 489.00000 27.00017 27.48488 0.91618 22.83932
December 497.00000 27.00005 24.82671 0.89921 22.20321
           
Annual Sum or Average 5943.00000 27.01001 31.89117 0.67646 16.27345
Minimum of Months 454.00000 27.00005 21.64979 0.29009 6.82504
Maximum of Months 514.00000 27.11037 38.49002 1.01220 26.69237



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.94953 21.78731 0.60206 12.98417
February 454.00000 27.00010 24.15649 0.68909 15.26956
March 514.00000 27.00018 29.00430 0.82594 19.56557
April 485.00000 27.00010 32.57681 0.90711 22.47736
May 508.00000 27.00058 36.78108 0.23221 6.22056
June 496.00000 27.00152 37.51431 0.28851 6.81736
July 497.00000 27.00110 37.97872 0.32033 7.20103
August 514.00000 27.11552 37.92066 0.37903 8.18947
September 485.00000 27.00046 38.69303 0.24950 6.39819
October 502.00000 27.00064 33.73700 0.85960 20.69386
November 489.00000 27.00016 27.45143 0.78277 18.07432
December 497.00000 27.00005 24.79688 0.71796 16.03812
           
Annual Sum or Average 5943.00000 27.00614 31.92338 0.56988 13.29954
Minimum of Months 454.00000 26.94953 21.78731 0.23221 6.22056
Maximum of Months 514.00000 27.11552 38.69303 0.90711 22.47736



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.29191 22.50476 0.40753 10.83142
February 454.00000 26.99945 24.18069 0.63051 13.79193
March 514.00000 27.00018 29.02348 0.78582 18.32922
April 485.00000 27.00011 32.59502 0.88549 21.75241
May 508.00000 27.00067 36.80130 0.23006 6.28662
June 496.00000 27.00155 37.51634 0.30166 7.03953
July 497.00000 27.00109 37.99035 0.33606 7.47544
August 514.00000 27.10715 37.94016 0.39267 8.47071
September 485.00000 27.00049 38.75782 0.24214 6.40348
October 502.00000 27.00064 33.79415 0.82333 19.49198
November 489.00000 27.00016 27.47730 0.72093 16.22605
December 497.00000 27.00005 24.81244 0.64021 13.94520
           
Annual Sum or Average 5943.00000 26.94983 32.00708 0.53189 12.48199
Minimum of Months 454.00000 26.29191 22.50476 0.23006 6.28662
Maximum of Months 514.00000 27.10715 38.75782 0.88549 21.75241



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00093 30.99149 1.02719 27.30666
February 454.00000 27.00242 31.23583 1.19513 35.02691
March 514.00000 27.00234 32.56622 1.36358 43.58966
April 485.00000 27.13562 33.84518 1.52763 52.40133
May 508.00000 27.00201 36.12551 0.50662 10.42246
June 496.00000 27.00191 37.12860 0.76220 17.27145
July 497.00000 27.00108 37.67098 0.97850 25.24709
August 514.00000 28.51798 36.69802 1.60437 56.31656
September 485.00000 27.00272 37.29103 0.60523 12.72996
October 502.00000 27.00091 34.05330 1.28987 39.76327
November 489.00000 27.00345 32.02293 1.40843 45.96698
December 497.00000 27.00525 31.28108 1.51085 51.49157
           
Annual Sum or Average 5943.00000 27.14426 34.26424 1.14876 34.82921
Minimum of Months 454.00000 27.00091 30.99149 0.50662 10.42246
Maximum of Months 514.00000 28.51798 37.67098 1.60437 56.31656



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.39225 22.40999 0.32225 7.68947
February 454.00000 24.41228 25.93810 0.35704 8.39617
March 514.00000 24.38034 32.42063 0.40736 8.92246
April 485.00000 24.45370 39.81206 0.47326 10.25812
May 508.00000 24.46779 52.89798 -0.2828 7.73040
June 496.00000 24.45184 56.73001 -0.2435 7.17832
July 497.00000 24.60936 62.27014 -0.1482 6.93476
August 514.00000 24.48914 60.93934 -0.1792 6.88981
September 485.00000 24.56429 56.95709 -0.1894 7.34050
October 502.00000 24.60405 41.90038 0.54773 12.16900
November 489.00000 24.60592 29.96105 0.46123 10.30789
December 497.00000 24.54864 26.15408 0.41000 9.28425
           
Annual Sum or Average 5943.00000 24.49832 42.50174 0.15900 8.58700
Minimum of Months 454.00000 24.38034 22.40999 -0.2828 6.88981
Maximum of Months 514.00000 24.60936 62.27014 0.54773 12.16900



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.08971 26.54735 0.27412 7.40712
February 454.00000 24.20616 27.50235 0.32606 7.75517
March 514.00000 24.29658 32.91113 0.41525 9.00204
April 485.00000 24.30726 39.89893 0.47807 10.14532
May 508.00000 24.31133 50.89618 -0.3100 7.56068
June 496.00000 24.24112 52.11868 -0.3025 7.23727
July 497.00000 24.25777 55.65767 -0.2631 6.68569
August 514.00000 24.18619 55.28996 -0.2714 6.68375
September 485.00000 24.35150 53.79292 -0.2674 7.11531
October 502.00000 24.39746 42.30477 0.50729 10.88465
November 489.00000 24.42357 31.03426 0.42856 9.36153
December 497.00000 24.41100 27.83381 0.38959 8.78436
           
Annual Sum or Average 5943.00000 24.28993 41.42737 0.11464 8.21708
Minimum of Months 454.00000 24.08971 26.54735 -0.3100 6.68375
Maximum of Months 514.00000 24.42357 55.65767 0.50729 10.88465



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.89840 28.82358 -0.0405 6.18454
February 454.00000 23.37175 29.49772 0.09822 6.49270
March 514.00000 24.04667 34.27399 0.32715 7.65821
April 485.00000 24.20315 40.80000 0.42197 9.11394
May 508.00000 24.23958 51.29896 -0.3562 8.09001
June 496.00000 24.21813 52.56862 -0.3388 7.79857
July 497.00000 24.25520 56.31812 -0.3018 7.23597
August 514.00000 24.21654 56.14453 -0.3078 7.25854
September 485.00000 24.26060 54.36121 -0.3243 7.67686
October 502.00000 24.12264 43.58663 0.41456 8.91946
November 489.00000 23.96716 32.65346 0.28420 7.13473
December 497.00000 23.46589 30.78183 0.12771 6.04028
           
Annual Sum or Average 5943.00000 23.94258 42.69903 -0.0012 7.47192
Minimum of Months 454.00000 22.89840 28.82358 -0.3562 6.04028
Maximum of Months 514.00000 24.26060 56.31812 0.42197 9.11394



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.37002 29.37571 -0.4333 12.78828
February 454.00000 22.26229 32.07409 -0.1786 9.21382
March 514.00000 23.51106 35.89461 0.18791 7.16848
April 485.00000 23.93656 41.58279 0.35306 8.33294
May 508.00000 24.20301 51.40264 -0.3641 8.34009
June 496.00000 24.24812 52.37595 -0.3141 7.54318
July 497.00000 24.29125 56.11137 -0.2723 6.96687
August 514.00000 24.25567 55.99929 -0.2780 6.94120
September 485.00000 24.19744 54.84441 -0.3446 8.10225
October 502.00000 23.61562 45.48748 0.28406 7.54835
November 489.00000 23.02235 35.22122 0.04208 6.77792
December 497.00000 21.96028 32.89803 -0.2515 9.34102
           
Annual Sum or Average 5943.00000 23.41479 43.69771 -0.1310 8.24720
Minimum of Months 454.00000 21.37002 29.37571 -0.4333 6.77792
Maximum of Months 514.00000 24.29125 56.11137 0.35306 12.78828



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.74551 26.18038 -0.3185 9.08479
February 454.00000 22.44610 28.12269 -0.1229 7.82788
March 514.00000 23.56491 33.59862 0.20595 6.93978
April 485.00000 23.95925 40.16893 0.37065 8.61264
May 508.00000 24.21656 50.63667 -0.3464 8.32596
June 496.00000 24.29184 51.51423 -0.2575 6.99154
July 497.00000 24.37103 55.15713 -0.1910 6.42855
August 514.00000 24.26304 54.83803 -0.2170 6.42658
September 485.00000 24.25679 54.17645 -0.3090 7.91903
October 502.00000 23.76443 43.57249 0.32588 8.07995
November 489.00000 23.38987 32.42203 0.14284 6.67352
December 497.00000 22.72724 28.59728 -0.0508 6.49440
           
Annual Sum or Average 5943.00000 23.59097 41.68810 -0.0643 7.47807
Minimum of Months 454.00000 21.74551 26.18038 -0.3464 6.42658
Maximum of Months 514.00000 24.37103 55.15713 0.37065 9.08479



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.74284 25.89344 -0.3042 8.55858
February 454.00000 22.34576 28.05144 -0.1225 7.65780
March 514.00000 23.34767 33.71801 0.18734 7.07858
April 485.00000 23.73575 40.50401 0.35765 8.62664
May 508.00000 24.18337 50.45276 -0.2980 8.44691
June 496.00000 24.25200 51.40523 -0.2212 6.98860
July 497.00000 24.28089 55.19197 -0.1740 6.80603
August 514.00000 24.15343 55.03749 -0.2183 6.82495
September 485.00000 24.11318 54.28699 -0.3007 8.47506
October 502.00000 23.57550 43.65243 0.31578 8.44915
November 489.00000 23.08539 32.64890 0.09730 6.59571
December 497.00000 22.31888 28.93809 -0.1249 6.65237
           
Annual Sum or Average 5943.00000 23.43598 41.75438 -0.0673 7.59326
Minimum of Months 454.00000 21.74284 25.89344 -0.3042 6.59571
Maximum of Months 514.00000 24.28089 55.19197 0.35765 8.62664



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.36734 25.35630 -0.1570 8.44501
February 454.00000 22.88743 27.43394 0.00639 7.93142
March 514.00000 23.77136 32.89848 0.29083 8.18546
April 485.00000 23.97733 39.89574 0.40227 9.34672
May 508.00000 24.18234 50.61710 -0.3396 8.49049
June 496.00000 24.25411 51.57217 -0.2658 7.20329
July 497.00000 24.35046 55.15804 -0.1897 6.51252
August 514.00000 24.29232 54.60046 -0.1758 6.36157
September 485.00000 24.31706 53.70731 -0.2375 7.63585
October 502.00000 23.98909 42.56346 0.42821 10.32741
November 489.00000 23.76382 31.28753 0.27159 8.33262
December 497.00000 23.08127 27.86487 0.06389 7.10078
           
Annual Sum or Average 5943.00000 23.77555 41.18761 0.00741 7.98667
Minimum of Months 454.00000 22.36734 25.35630 -0.3396 6.36157
Maximum of Months 514.00000 24.35046 55.15804 0.42821 10.32741



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.15269 25.02017 -0.1798 7.48011
February 454.00000 23.08473 26.47037 0.08389 7.45347
March 514.00000 24.19730 31.75492 0.44381 10.19347
April 485.00000 24.48116 38.46459 0.61083 13.81010
May 508.00000 24.33948 49.86477 -0.1995 7.23180
June 496.00000 24.42800 50.71221 -0.0859 6.38994
July 497.00000 24.52712 54.12495 0.00681 6.43226
August 514.00000 24.45237 53.67462 0.03279 6.32623
September 485.00000 24.36559 53.30489 -0.1682 7.23225
October 502.00000 24.18869 41.83404 0.50004 11.40334
November 489.00000 24.10832 30.34113 0.38223 9.40872
December 497.00000 23.85968 26.15468 0.27700 7.75729
           
Annual Sum or Average 5943.00000 24.02127 40.25201 0.14177 8.42273
Minimum of Months 454.00000 22.15269 25.02017 -0.1995 6.32623
Maximum of Months 514.00000 24.52712 54.12495 0.61083 13.81010



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.46003 28.31116 -0.6830 17.54031
February 454.00000 21.16521 30.06462 -0.4678 12.88111
March 514.00000 22.55802 35.73580 -0.0466 7.17068
April 485.00000 23.42958 41.93374 0.22386 7.61011
May 508.00000 24.04326 51.59386 -0.4243 9.80196
June 496.00000 24.27403 52.51136 -0.2864 7.51843
July 497.00000 24.39240 56.87187 -0.2097 6.80640
August 514.00000 24.32237 56.81581 -0.2315 6.77650
September 485.00000 24.07799 55.69842 -0.3884 9.31559
October 502.00000 22.86480 46.53118 0.10240 6.92258
November 489.00000 21.98657 35.50561 -0.2040 7.82345
December 497.00000 20.91213 31.69877 -0.5128 13.03675
           
Annual Sum or Average 5943.00000 22.88700 43.71201 -0.2596 9.40644
Minimum of Months 454.00000 20.46003 28.31116 -0.6830 6.77650
Maximum of Months 514.00000 24.39240 56.87187 0.22386 17.54031



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.49960 27.18193 -0.6570 16.12478
February 385.00000 21.31971 29.18766 -0.4082 11.71719
March 433.00000 22.66557 34.56490 0.00607 6.95665
April 410.00000 23.52200 41.15295 0.28485 8.37057
May 430.00000 24.08899 50.86739 -0.3527 10.01959
June 418.00000 24.36774 51.90296 -0.2058 7.43572
July 422.00000 24.49746 56.19789 -0.1245 7.40252
August 433.00000 24.40415 56.29468 -0.1587 7.03977
September 410.00000 24.00111 55.57507 -0.3586 10.14058
October 427.00000 22.91722 45.57105 0.14458 7.62114
November 417.00000 21.97069 34.57631 -0.1835 7.31253
December 422.00000 20.87420 30.91557 -0.5014 12.13213
           
Annual Sum or Average 5034.00000 22.93709 42.91857 -0.2087 9.33853
Minimum of Months 385.00000 20.49960 27.18193 -0.6570 6.95665
Maximum of Months 433.00000 24.49746 56.29468 0.28485 16.12478



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.67810 26.62935 -0.3422 11.55490
February 454.00000 22.23577 28.45223 -0.1676 9.53255
March 514.00000 23.36830 33.91423 0.18204 7.87990
April 485.00000 23.73452 40.94109 0.32570 8.74516
May 508.00000 24.05607 51.36760 -0.3974 9.57530
June 496.00000 24.23985 52.53520 -0.2919 7.73585
July 497.00000 24.38290 56.76292 -0.2036 6.87194
August 514.00000 24.37734 56.32739 -0.1789 6.65019
September 485.00000 24.23231 54.73715 -0.2782 8.41910
October 502.00000 23.66135 43.92682 0.34218 9.69402
November 489.00000 23.24780 32.72240 0.13923 8.01360
December 497.00000 22.20175 29.59638 -0.1584 9.03100
           
Annual Sum or Average 5943.00000 23.46034 42.43626 -0.0858 8.63394
Minimum of Months 454.00000 21.67810 26.62935 -0.3974 6.65019
Maximum of Months 514.00000 24.38290 56.76292 0.34218 11.55490



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.74961 27.37580 -0.5811 14.25359
February 454.00000 21.41383 29.18390 -0.3720 10.96395
March 514.00000 22.82331 34.66208 0.06262 7.40778
April 485.00000 23.62567 41.05358 0.32669 8.98513
May 508.00000 24.03720 51.19407 -0.3517 9.33855
June 496.00000 24.28954 52.08730 -0.2123 7.36974
July 497.00000 24.39797 56.29586 -0.1386 6.94538
August 514.00000 24.39854 55.92522 -0.1283 6.62774
September 485.00000 24.03427 55.31362 -0.3308 9.43588
October 502.00000 23.00812 45.48215 0.17907 7.77045
November 489.00000 22.18761 34.46114 -0.1200 7.28187
December 497.00000 21.17783 30.75744 -0.4165 10.68748
           
Annual Sum or Average 5943.00000 23.02453 42.92159 -0.1725 8.90222
Minimum of Months 454.00000 20.74961 27.37580 -0.5811 6.62774
Maximum of Months 514.00000 24.39854 56.29586 0.32669 14.25359



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.03915 29.43544 -0.8377 23.41923
February 454.00000 20.73668 31.21982 -0.6105 16.27068
March 514.00000 21.91813 36.93268 -0.2092 9.09744
April 485.00000 22.97698 42.92760 0.11670 7.69682
May 508.00000 23.86685 52.12075 -0.4736 11.49145
June 496.00000 24.23868 52.59646 -0.2820 7.83717
July 497.00000 24.36924 57.02261 -0.1981 7.01084
August 514.00000 24.32166 56.98183 -0.2140 6.78566
September 485.00000 23.87759 56.63922 -0.4473 11.14809
October 502.00000 22.25517 48.33536 -0.0493 7.61241
November 489.00000 21.20215 37.19946 -0.4151 11.28444
December 497.00000 20.30515 33.18201 -0.7053 19.07388
           
Annual Sum or Average 5943.00000 22.52325 44.65154 -0.3589 11.52205
Minimum of Months 454.00000 20.03915 29.43544 -0.8377 6.78566
Maximum of Months 514.00000 24.36924 57.02261 0.11670 23.41923



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.13029 28.97512 -0.7881 21.32044
February 454.00000 20.98379 30.55880 -0.5203 14.40416
March 514.00000 22.30963 35.95433 -0.0851 7.78675
April 485.00000 23.30987 41.95558 0.24088 8.37148
May 508.00000 23.99397 51.32743 -0.3588 10.30576
June 496.00000 24.31060 51.95430 -0.1858 7.32742
July 497.00000 24.40623 56.29586 -0.1134 7.53065
August 514.00000 24.35239 56.28104 -0.1366 6.91468
September 485.00000 23.87624 56.05453 -0.3788 10.99421
October 502.00000 22.61314 46.93956 0.06601 7.89477
November 489.00000 21.40312 36.42675 -0.3388 9.49406
December 497.00000 20.37243 32.77726 -0.6596 17.42045
           
Annual Sum or Average 5943.00000 22.68576 43.89238 -0.2699 10.78032
Minimum of Months 454.00000 20.13029 28.97512 -0.7881 6.91468
Maximum of Months 514.00000 24.40623 56.29586 0.24088 21.32044



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.94321 28.13144 -0.5544 16.46107
February 454.00000 21.66614 29.77336 -0.3331 12.38583
March 514.00000 22.84378 35.03043 0.04578 8.39916
April 485.00000 23.35992 41.86304 0.23586 8.56850
May 508.00000 23.89467 51.86860 -0.4412 11.12925
June 496.00000 24.19421 52.64855 -0.2900 8.16609
July 497.00000 24.34918 56.96429 -0.1946 7.17665
August 514.00000 24.37044 56.51603 -0.1617 6.71761
September 485.00000 24.07788 55.54480 -0.3213 9.82195
October 502.00000 23.21927 45.44875 0.22733 9.49088
November 489.00000 22.51501 34.41224 -0.0559 8.71795
December 497.00000 21.36578 31.41720 -0.3899 13.43987
           
Annual Sum or Average 5943.00000 23.07764 43.40706 -0.1855 10.02086
Minimum of Months 454.00000 20.94321 28.13144 -0.5544 6.71761
Maximum of Months 514.00000 24.37044 56.96429 0.23586 16.46107



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.28273 28.61370 -0.7365 19.72984
February 454.00000 21.02948 30.32852 -0.4951 13.78581
March 514.00000 22.34465 35.71623 -0.0616 8.33260
April 485.00000 23.26726 41.90589 0.24158 8.78048
May 508.00000 23.86752 51.72065 -0.3964 10.85064
June 496.00000 24.23327 52.24817 -0.2133 7.84427
July 497.00000 24.35056 56.55134 -0.1335 7.31305
August 514.00000 24.37653 56.16524 -0.1161 6.78992
September 485.00000 23.85153 56.17804 -0.3820 11.11768
October 502.00000 22.56844 46.93238 0.06660 7.88307
November 489.00000 21.58602 35.91463 -0.2854 9.25664
December 497.00000 20.62373 32.19384 -0.5853 15.30996
           
Annual Sum or Average 5943.00000 22.71212 43.80765 -0.2565 10.55310
Minimum of Months 454.00000 20.28273 28.61370 -0.7365 6.78992
Maximum of Months 514.00000 24.37653 56.55134 0.24158 19.72984



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.493930E+10 78000.59 31-JAN-15:50 87.32 0.233681E+11 0.00 0.283074E+11 0.54 6.66 31-JAN-15:50 0.00 0.00
February 0.153096E+11 109101.67 28-FEB-14:50 132.09 0.852461E+11 0.00 0.100556E+12 0.97 7.27 28-FEB-13:40 0.00 0.00
March 0.430645E+11 121393.62 30-MAR-14:40 260.23 0.255336E+12 0.00 0.298401E+12 1.85 7.34 30-MAR-11:00 0.00 0.00
April 0.754984E+11 134114.60 17-APR-14:20 384.12 0.471968E+12 0.00 0.547467E+12 2.98 7.46 17-APR-14:20 0.00 0.00
May 0.127096E+12 148888.83 31-MAY-03:02 470.75 0.828373E+12 0.00 0.955469E+12 3.89 7.62 31-MAY-05:03 0.00 0.00
June 0.168685E+12 180268.40 26-JUN-05:02 554.15 0.111229E+13 0.00 0.128098E+13 4.80 7.78 21-JUN-05:02 0.00 0.00
July 0.189447E+12 190916.72 27-JUL-05:02 636.52 0.123141E+13 0.00 0.142086E+13 5.21 7.69 28-JUL-05:03 0.00 0.00
August 0.206126E+12 208101.97 24-AUG-05:04 686.22 0.133779E+13 0.00 0.154392E+13 5.55 7.66 30-AUG-05:02 0.00 0.00
September 0.138400E+12 170085.19 05-SEP-05:03 478.33 0.909793E+12 0.00 0.104819E+13 4.12 7.69 11-SEP-04:33 0.00 0.00
October 0.680332E+11 132591.02 19-OCT-05:03 305.49 0.426336E+12 0.00 0.494370E+12 2.34 7.56 18-OCT-04:03 0.00 0.00
November 0.312021E+11 102700.24 02-NOV-13:50 202.34 0.177396E+12 0.00 0.208598E+12 1.45 7.23 02-NOV-13:50 0.00 0.00
December 0.913421E+10 96347.58 12-DEC-14:30 86.99 0.518563E+11 0.00 0.609905E+11 0.58 7.11 12-DEC-14:30 0.00 0.00
                         
Annual Sum or Average 0.107694E+13     4284.56 0.691117E+13 0.00 0.798811E+13 2.87     0.00 0.00
Minimum of Months 0.493930E+10 78000.59   86.99 0.233681E+11 0.00 0.283074E+11 0.54 6.66   0.00 0.00
Maximum of Months 0.206126E+12 208101.97   686.22 0.133779E+13 0.00 0.154392E+13 5.55 7.78   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.995695E+09 121393.62 30-MAR-14:40 2.50 0.710569E+10 0.00 0.810138E+10 0.02 7.22 30-MAR-14:50 0.00 0.00
April 0.609060E+10 134114.60 17-APR-14:20 15.25 0.436231E+11 0.00 0.497137E+11 0.15 7.46 17-APR-14:20 0.00 0.00
May 0.208509E+11 148888.83 31-MAY-03:02 52.26 0.146358E+12 0.00 0.167209E+12 0.49 7.62 31-MAY-05:03 0.00 0.00
June 0.643046E+11 180268.40 26-JUN-05:02 154.02 0.439378E+12 0.00 0.503682E+12 1.46 7.78 21-JUN-05:02 0.00 0.00
July 0.736632E+11 190916.72 27-JUL-05:02 172.93 0.501553E+12 0.00 0.575216E+12 1.58 7.69 28-JUL-05:03 0.00 0.00
August 0.931019E+11 208101.97 24-AUG-05:04 213.41 0.630709E+12 0.00 0.723811E+12 1.94 7.66 30-AUG-05:02 0.00 0.00
September 0.370927E+11 170085.19 05-SEP-05:03 89.68 0.256337E+12 0.00 0.293429E+12 0.86 7.69 11-SEP-04:33 0.00 0.00
October 0.116310E+11 132591.02 19-OCT-05:03 28.79 0.813052E+11 0.00 0.929362E+11 0.27 7.56 18-OCT-04:03 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.307731E+12     728.84 0.210637E+13 0.00 0.241410E+13 0.57     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.931019E+11 208101.97   213.41 0.630709E+12 0.00 0.723811E+12 1.94 7.78   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.191628E+11 744.00 49248.27 19-JAN-12:00 382529.50 26-JAN-13:32 21.83 18.38 14.12
February 0.504229E+11 672.00 49248.27 01-FEB-19:00 437074.54 03-FEB-15:43 25.23 18.91 14.22
March 0.102560E+12 744.00 49248.27 01-MAR-00:10 597204.45 31-MAR-24:00 29.87 20.50 14.28
April 0.120217E+12 720.00 49248.27 01-APR-09:40 674037.10 17-APR-16:10 35.99 23.62 14.30
May 0.122402E+12 744.00 49248.27 01-MAY-00:02 340525.86 31-MAY-23:40 27.07 23.05 14.30
June 0.126531E+12 720.00 49248.27 01-JUN-00:10 489911.58 30-JUN-24:00 35.31 28.12 14.30
July 0.131907E+12 744.00 49248.27 01-JUL-00:10 653613.91 31-JUL-23:53 41.01 30.75 14.30
August 0.131907E+12 744.00 49248.27 01-AUG-00:03 709339.73 11-AUG-16:30 45.77 32.60 14.30
September 0.123492E+12 720.00 49248.27 01-SEP-00:02 320106.67 30-SEP-24:00 28.69 24.54 14.30
October 0.101212E+12 744.00 49248.27 01-OCT-00:10 455936.68 31-OCT-24:00 27.76 21.04 14.27
November 0.898852E+11 720.00 49248.27 01-NOV-10:35 512537.02 02-NOV-14:10 29.16 19.83 14.28
December 0.815131E+11 744.00 49248.27 04-DEC-15:30 656978.98 12-DEC-15:10 30.70 18.86 14.29
                   
Annual Sum or Average 0.120121E+13 8760.00         31.58 23.38 14.27
Minimum of Months 0.191628E+11 672.00 49248.27   320106.67   21.83 18.38 14.12
Maximum of Months 0.131907E+12 744.00 49248.27   709339.73   45.77 32.60 14.30



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 48723034.05 22.43 1236.50 19-JAN-16:00 585716.84 31-JAN-15:50 21.06 21.02 3.81
February 81353946.58 58.24 2225.51 28-FEB-15:00 1056961.35 28-FEB-13:20 21.21 21.07 9.51
March 0.146710E+10 163.23 21586.57 28-MAR-15:50 1166555.86 30-MAR-15:20 21.52 21.13 21.36
April 0.426203E+10 287.57 21586.57 03-APR-04:05 1609281.52 14-APR-15:50 21.93 21.15 35.32
May 0.178047E+11 447.18 21586.57 01-MAY-13:10 1177166.32 12-MAY-15:40 22.99 21.73 45.92
June 0.324991E+11 537.27 21586.57 01-JUN-03:02 1334590.23 08-JUN-15:50 24.56 22.86 55.62
July 0.448789E+11 635.58 21586.57 01-JUL-00:32 1190891.35 27-JUL-05:04 25.55 23.72 60.98
August 0.513593E+11 686.18 21586.57 01-AUG-00:08 1243929.21 24-AUG-05:04 26.29 24.31 65.47
September 0.251966E+11 462.43 21586.57 01-SEP-04:08 1325377.29 13-SEP-15:40 24.11 22.69 48.14
October 0.751021E+10 252.65 21586.57 02-OCT-04:03 1148444.57 11-OCT-16:10 22.18 21.53 27.96
November 0.605715E+09 135.66 21586.57 27-NOV-16:10 863281.99 02-NOV-13:50 21.42 21.14 17.23
December 0.192820E+09 37.63 3456.90 13-DEC-11:10 801044.11 12-DEC-14:30 21.08 21.00 5.11
                   
Annual Sum or Average 0.185906E+12 3726.05         22.84 21.95 33.16
Minimum of Months 48723034.05 22.43 1236.50   585716.84   21.06 21.00 3.81
Maximum of Months 0.513593E+11 686.18 21586.57   1609281.52   26.29 24.31 65.47



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 21.06 21.06 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 21.21 21.21 0.00
March 0.168375E+09 2.17 21586.57 29-MAR-15:50 1166555.86 30-MAR-15:20 21.52 21.51 0.21
April 0.546405E+09 7.86 21586.57 04-APR-13:30 1412166.88 13-APR-14:50 21.93 21.89 0.80
May 0.403259E+10 51.89 21586.57 03-MAY-14:20 1175503.57 15-MAY-15:50 22.99 22.77 5.11
June 0.134554E+11 173.14 21586.57 01-JUN-05:04 1175483.04 02-JUN-10:40 24.56 23.85 17.32
July 0.175384E+11 225.69 21586.57 01-JUL-05:03 1190891.35 27-JUL-05:04 25.55 24.63 20.54
August 0.212529E+11 273.48 21586.57 01-AUG-03:02 1243929.21 24-AUG-05:04 26.29 25.17 24.85
September 0.785298E+10 101.05 21586.57 01-SEP-05:05 1325377.29 13-SEP-15:40 24.11 23.69 10.09
October 0.230868E+10 29.71 21586.57 02-OCT-09:50 1012484.10 11-OCT-15:20 22.18 22.05 2.91
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 21.42 21.42 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 21.08 21.08 0.00
                   
Annual Sum or Average 0.671557E+11 865.00         22.84 22.54 6.87
Minimum of Months 0.00 0.00 0.00   0.00   21.06 21.06 0.00
Maximum of Months 0.212529E+11 273.48 21586.57   1412166.88   26.29 25.17 24.85



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.189541E+12 0.00 478.83 1538862.95 02-JAN-06:02 0.00 29.09 61.07 0.38 0.00 0.03 0.63 02-JAN-06:02
February 0.112108E+12 0.00 338.77 1377556.71 13-FEB-06:01 0.00 26.85 52.40 0.25 0.00 0.02 0.57 13-FEB-06:01
March 0.161308E+11 0.00 159.21 845252.55 22-MAR-05:03 0.00 27.39 38.59 0.03 0.00 0.00 0.35 22-MAR-05:03
April 0.490352E+10 0.00 72.91 594456.89 06-APR-06:10 0.00 38.65 42.95 0.01 0.00 0.00 0.24 06-APR-06:10
May 0.217959E+10 0.00 31.63 167072.52 11-MAY-06:10 0.00 44.63 46.14 0.01 0.00 0.00 0.07 11-MAY-06:10
June 0.578803E+09 0.00 11.17 64231.07 03-JUN-12:00 0.00 53.71 54.18 0.00 0.00 0.00 0.03 03-JUN-12:00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 54.52 54.52 0.00 0.00 0.00 0.00 01-JUL-00:10
August 29286204.54 0.00 1.75 23113.13 25-AUG-13:50 0.00 54.05 54.11 0.00 0.00 0.00 0.01 25-AUG-13:50
September 0.362495E+09 0.00 15.92 101460.30 14-SEP-15:00 0.00 52.00 52.65 0.00 0.00 0.00 0.04 14-SEP-15:00
October 0.803075E+10 0.00 118.66 578351.45 26-OCT-05:03 0.00 30.04 38.37 0.01 0.00 0.00 0.24 26-OCT-05:03
November 0.310109E+11 0.00 221.04 1127967.28 25-NOV-06:01 0.00 25.80 41.97 0.06 0.00 0.00 0.46 25-NOV-06:01
December 0.880430E+11 0.00 393.00 1176088.85 26-DEC-05:01 0.00 25.29 53.27 0.17 0.00 0.01 0.48 26-DEC-05:01
                           
Annual Sum or Average 0.452918E+12 0.00 1842.88     0.00 38.55 49.17 0.08 0.00 0.01    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 25.29 38.37 0.00 0.00 0.00 0.00  
Maximum of Months 0.189541E+12 0.00 478.83 1538862.95   0.00 54.52 61.07 0.38 0.00 0.03 0.63  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 21.83 21.83 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 25.23 25.23 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 29.87 29.87 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 35.99 35.99 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:02 0.00 27.07 27.07 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 35.31 35.31 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 41.01 41.01 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 45.77 45.77 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:02 0.00 28.69 28.69 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 27.76 27.76 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 29.16 29.16 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 30.70 30.70 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 31.58 31.58 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 21.83 21.83 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 45.77 45.77 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.198280E+10 0.00 60.89 0.187542E+10 0.00 0.00 0.00 0.00 41599.57 31-JAN-15:00 41599.57 31-JAN-15:00 0.00 0.00 0.00
February 0.848749E+10 0.00 111.98 0.848331E+10 0.00 0.00 0.00 0.00 92211.38 28-FEB-15:00 92211.38 28-FEB-15:00 0.00 0.00 0.00
March 0.270838E+11 0.00 246.69 0.261654E+11 0.00 0.00 0.00 0.00 126352.88 30-MAR-05:03 125419.18 30-MAR-14:30 0.00 0.00 0.00
April 0.593506E+11 0.00 375.29 0.565493E+11 0.00 0.00 0.00 0.00 166868.64 17-APR-15:00 166868.64 17-APR-15:00 0.00 0.00 0.00
May 0.948286E+11 0.00 453.60 0.804717E+11 0.00 0.00 0.00 0.00 212907.75 31-MAY-03:02 164182.70 16-MAY-15:40 0.00 0.00 0.00
June 0.149290E+12 0.00 535.03 0.125402E+12 0.00 0.00 0.00 0.00 220342.84 26-JUN-05:02 156456.50 26-JUN-05:02 0.00 0.00 0.00
July 0.177982E+12 0.00 602.72 0.142759E+12 0.00 0.00 0.00 0.00 215751.27 17-JUL-05:03 154744.50 10-JUL-04:03 0.00 0.00 0.00
August 0.207460E+12 0.00 653.37 0.165899E+12 0.00 0.00 0.00 0.00 221848.30 07-AUG-05:03 182638.23 25-AUG-14:00 0.00 0.00 0.00
September 0.113116E+12 0.00 455.15 0.919298E+11 0.00 0.00 0.00 0.00 227672.48 05-SEP-03:02 157742.07 05-SEP-03:02 0.00 0.00 0.00
October 0.517056E+11 0.00 279.35 0.420874E+11 0.00 0.00 0.00 0.00 217641.84 19-OCT-05:03 146174.62 18-OCT-05:03 0.00 0.00 0.00
November 0.183662E+11 0.00 172.79 0.169287E+11 0.00 0.00 0.00 0.00 118267.43 27-NOV-06:03 118267.43 27-NOV-06:03 0.00 0.00 0.00
December 0.569561E+10 0.00 62.28 0.478798E+10 0.00 0.00 0.00 0.00 110224.97 13-DEC-06:03 75593.27 12-DEC-14:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.915349E+12 0.00 4009.14 0.763340E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.198280E+10 0.00 60.89 0.187542E+10 0.00 0.00 0.00 0.00 41599.57   41599.57   0.00 0.00 0.00
Maximum of Months 0.207460E+12 0.00 653.37 0.165899E+12 0.00 0.00 0.00 0.00 227672.48   182638.23   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.144249E+11 0.00 66.38 0.137684E+11 0.00 0.00 0.00 0.00 309146.43 31-JAN-15:00 309146.43 31-JAN-15:00 0.00 0.00 0.00
February 0.633944E+11 0.00 102.66 0.633944E+11 0.00 0.00 0.00 0.00 727541.52 28-FEB-15:00 727541.52 28-FEB-15:00 0.00 0.00 0.00
March 0.201860E+12 0.00 225.49 0.195986E+12 0.00 0.00 0.00 0.00 1156652.07 30-MAR-15:20 1156652.07 30-MAR-15:20 0.00 0.00 0.00
April 0.429048E+12 0.00 306.52 0.411037E+12 0.00 0.00 0.00 0.00 1553135.93 12-APR-14:40 1553135.93 12-APR-14:40 0.00 0.00 0.00
May 0.830103E+12 0.00 433.13 0.702445E+12 0.00 0.00 0.00 0.00 1765834.77 31-MAY-03:02 1567064.58 19-MAY-13:10 0.00 0.00 0.00
June 0.126985E+13 0.00 467.70 0.103091E+13 0.00 0.00 0.00 0.00 2161595.29 24-JUN-05:03 1459354.34 14-JUN-03:02 0.00 0.00 0.00
July 0.144371E+13 0.00 493.17 0.109503E+13 0.00 0.00 0.00 0.00 2242378.74 14-JUL-03:02 1473104.19 15-JUL-05:03 0.00 0.00 0.00
August 0.162546E+13 0.00 513.92 0.120836E+13 0.00 0.00 0.00 0.00 2517226.01 23-AUG-03:02 1575389.64 25-AUG-13:50 0.00 0.00 0.00
September 0.974399E+12 0.00 423.39 0.769309E+12 0.00 0.00 0.00 0.00 2155005.74 27-SEP-05:03 1435590.22 27-SEP-05:03 0.00 0.00 0.00
October 0.403308E+12 0.00 263.05 0.319247E+12 0.00 0.00 0.00 0.00 1837833.88 18-OCT-04:03 1078298.03 18-OCT-04:03 0.00 0.00 0.00
November 0.125975E+12 0.00 165.30 0.118555E+12 0.00 0.00 0.00 0.00 771822.99 04-NOV-05:02 556029.91 02-NOV-14:00 0.00 0.00 0.00
December 0.349632E+11 0.00 59.31 0.297104E+11 0.00 0.00 0.00 0.00 836741.85 13-DEC-06:03 502054.09 12-DEC-14:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.741648E+13 0.00 3520.02 0.595776E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.144249E+11 0.00 59.31 0.137684E+11 0.00 0.00 0.00 0.00 309146.43   309146.43   0.00 0.00 0.00
Maximum of Months 0.162546E+13 0.00 513.92 0.120836E+13 0.00 0.00 0.00 0.00 2517226.01   1575389.64   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.133325E+10 0.00 72.41 0.126813E+10 0.00 0.00 0.00 0.00 24819.03 31-JAN-15:00 24819.03 31-JAN-15:00 0.00 0.00 0.00
February 0.549883E+10 0.00 106.10 0.549883E+10 0.00 0.00 0.00 0.00 69599.68 28-FEB-15:00 69599.68 28-FEB-15:00 0.00 0.00 0.00
March 0.194692E+11 0.00 220.04 0.190508E+11 0.00 0.00 0.00 0.00 127836.40 30-MAR-15:30 127836.40 30-MAR-15:30 0.00 0.00 0.00
April 0.440849E+11 0.00 299.29 0.423593E+11 0.00 0.00 0.00 0.00 167531.78 17-APR-15:00 167531.78 17-APR-15:00 0.00 0.00 0.00
May 0.897048E+11 0.00 427.89 0.768287E+11 0.00 0.00 0.00 0.00 169693.82 16-MAY-15:40 169693.82 16-MAY-15:40 0.00 0.00 0.00
June 0.140246E+12 0.00 469.67 0.115584E+12 0.00 0.00 0.00 0.00 222371.00 29-JUN-05:03 149489.60 14-JUN-03:02 0.00 0.00 0.00
July 0.159566E+12 0.00 501.61 0.123878E+12 0.00 0.00 0.00 0.00 239690.96 14-JUL-03:02 157723.39 15-JUL-03:02 0.00 0.00 0.00
August 0.178030E+12 0.00 523.67 0.135335E+12 0.00 0.00 0.00 0.00 269757.61 23-AUG-03:02 178789.56 25-AUG-13:40 0.00 0.00 0.00
September 0.100559E+12 0.00 418.48 0.803705E+11 0.00 0.00 0.00 0.00 224550.45 27-SEP-05:03 148261.22 27-SEP-05:03 0.00 0.00 0.00
October 0.394586E+11 0.00 252.92 0.310869E+11 0.00 0.00 0.00 0.00 209629.00 19-OCT-04:03 109815.32 18-OCT-05:03 0.00 0.00 0.00
November 0.107436E+11 0.00 168.74 0.101097E+11 0.00 0.00 0.00 0.00 69268.52 04-NOV-05:02 54267.11 02-NOV-14:00 0.00 0.00 0.00
December 0.298258E+10 0.00 68.86 0.252223E+10 0.00 0.00 0.00 0.00 44724.07 12-DEC-14:40 44724.07 12-DEC-14:40 0.00 0.00 0.00
                               
Annual Sum or Average 0.791677E+12 0.00 3529.68 0.643892E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.133325E+10 0.00 68.86 0.126813E+10 0.00 0.00 0.00 0.00 24819.03   24819.03   0.00 0.00 0.00
Maximum of Months 0.178030E+12 0.00 523.67 0.135335E+12 0.00 0.00 0.00 0.00 269757.61   178789.56   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.654960E+09 0.00 19.08 0.638719E+09 0.00 0.00 0.00 0.00 51712.16 19-JAN-05:02 31134.54 31-JAN-15:00 0.00 0.00 0.00
February 0.429000E+10 0.00 48.50 0.427141E+10 0.00 0.00 0.00 0.00 60831.06 28-FEB-14:20 60831.06 28-FEB-14:20 0.00 0.00 0.00
March 0.133790E+11 0.00 145.46 0.133359E+11 0.00 0.00 0.00 0.00 84394.81 29-MAR-04:03 78391.21 30-MAR-14:30 0.00 0.00 0.00
April 0.281709E+11 0.00 224.61 0.277378E+11 0.00 0.00 0.00 0.00 91436.89 17-APR-14:20 91436.89 17-APR-14:20 0.00 0.00 0.00
May 0.509565E+11 0.00 344.08 0.466949E+11 0.00 0.00 0.00 0.00 134085.00 31-MAY-03:02 93423.50 29-MAY-15:42 0.00 0.00 0.00
June 0.871638E+11 0.00 398.78 0.736925E+11 0.00 0.00 0.00 0.00 160487.35 26-JUN-03:02 109811.09 12-JUN-03:02 0.00 0.00 0.00
July 0.997131E+11 0.00 411.40 0.793583E+11 0.00 0.00 0.00 0.00 160904.56 09-JUL-19:58 94047.93 06-JUL-03:02 0.00 0.00 0.00
August 0.119852E+12 0.00 467.80 0.938395E+11 0.00 0.00 0.00 0.00 170939.38 06-AUG-17:00 99308.08 14-AUG-03:02 0.00 0.00 0.00
September 0.740994E+11 0.00 378.53 0.627840E+11 0.00 0.00 0.00 0.00 170246.34 17-SEP-15:30 95108.68 04-SEP-15:50 0.00 0.00 0.00
October 0.326725E+11 0.00 220.63 0.276098E+11 0.00 0.00 0.00 0.00 147025.23 19-OCT-03:02 93299.44 09-OCT-14:42 0.00 0.00 0.00
November 0.105825E+11 0.00 119.07 0.989265E+10 0.00 0.00 0.00 0.00 82619.10 27-NOV-06:03 82530.39 20-NOV-00:52 0.00 0.00 0.00
December 0.304282E+10 0.00 37.27 0.281530E+10 0.00 0.00 0.00 0.00 78224.66 13-DEC-06:03 50315.27 12-DEC-14:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.524577E+12 0.00 2815.19 0.442671E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.654960E+09 0.00 19.08 0.638719E+09 0.00 0.00 0.00 0.00 51712.16   31134.54   0.00 0.00 0.00
Maximum of Months 0.119852E+12 0.00 467.80 0.938395E+11 0.00 0.00 0.00 0.00 170939.38   109811.09   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.322966E+12 0.816798E+11 744.00 0.322464E+12 0.502097E+09 0.00 0.35 24-JAN-16:00 0.30 09-JAN-07:10 130083.10 19-JAN-17:00 125397.23 31-JAN-15:00 6021.32 19-JAN-17:10 37668.51 24-JAN-16:00 0.00
February 0.513952E+12 0.125231E+12 672.00 0.513402E+12 0.549722E+09 0.00 0.59 28-FEB-14:10 0.51 01-FEB-07:10 220175.47 17-FEB-17:00 218635.45 28-FEB-15:00 5771.76 17-FEB-17:10 71004.96 28-FEB-14:20 0.00
March 0.819449E+12 0.200918E+12 744.00 0.817911E+12 0.153868E+10 0.00 0.92 31-MAR-24:00 0.72 06-MAR-07:20 394376.47 31-MAR-24:00 394376.47 31-MAR-24:00 8561.71 31-MAR-11:50 106824.49 30-MAR-16:00 0.00
April 0.103082E+13 0.267539E+12 720.00 0.102886E+13 0.196602E+10 0.00 1.00 02-APR-13:05 0.36 30-APR-24:00 406828.74 21-APR-15:00 403055.58 16-APR-18:45 7159.23 04-APR-10:00 137038.88 17-APR-16:00 0.00
May 0.340757E+12 0.981646E+11 744.00 0.334600E+12 0.615763E+10 0.00 0.55 31-MAY-23:20 0.31 12-MAY-07:00 213073.78 31-MAY-23:10 211664.28 31-MAY-24:00 8679.58 23-MAY-14:00 60373.34 31-MAY-23:20 0.00
June 0.572826E+12 0.181490E+12 720.00 0.563876E+12 0.894952E+10 0.00 0.77 30-JUN-24:00 0.53 10-JUN-06:30 303977.93 30-JUN-23:03 303727.15 30-JUN-24:00 13129.37 26-JUN-17:00 92499.63 06-JUN-15:00 0.00
July 0.840267E+12 0.273456E+12 744.00 0.829354E+12 0.109132E+11 0.00 0.99 31-JUL-23:43 0.75 29-JUL-04:00 396710.96 31-JUL-23:53 395957.48 31-JUL-23:53 13964.44 25-JUL-16:50 134920.06 08-JUL-15:40 0.00
August 0.108066E+13 0.349535E+12 744.00 0.106955E+13 0.111073E+11 0.00 1.00 01-AUG-07:10 0.38 31-AUG-24:00 422669.57 08-AUG-17:00 407577.21 07-AUG-21:03 19211.25 11-AUG-17:00 153696.90 01-AUG-16:10 0.00
September 0.337763E+12 0.101184E+12 720.00 0.329527E+12 0.823614E+10 0.00 0.53 30-SEP-24:00 0.32 29-SEP-06:10 212264.84 30-SEP-23:20 212029.51 30-SEP-24:00 10501.09 28-SEP-13:20 53670.95 07-SEP-16:00 0.00
October 0.584208E+12 0.151093E+12 744.00 0.580533E+12 0.367482E+10 0.00 0.74 31-OCT-24:00 0.53 31-OCT-07:00 304610.49 31-OCT-24:00 304610.49 31-OCT-24:00 11882.95 18-OCT-16:10 82720.49 10-OCT-16:00 0.00
November 0.798227E+12 0.191548E+12 720.00 0.796774E+12 0.145284E+10 0.00 0.81 19-NOV-15:00 0.72 13-NOV-07:20 317828.33 27-NOV-17:00 311352.73 02-NOV-14:00 6768.71 27-NOV-17:10 98090.86 19-NOV-15:00 0.00
December 0.106526E+13 0.239279E+12 744.00 0.106452E+13 0.744764E+09 0.00 1.00 12-DEC-14:40 0.90 01-DEC-07:10 408607.11 13-DEC-14:00 402753.98 12-DEC-15:00 7806.47 13-DEC-14:00 120257.93 12-DEC-14:40 0.00
                                       
Annual Sum or Average 0.830716E+13 0.226112E+13 8760.00 0.825137E+13 0.557927E+11 0.00                         0.00
Minimum of Months 0.322966E+12 0.816798E+11 672.00 0.322464E+12 0.502097E+09 0.00 0.35   0.30   130083.10   125397.23   5771.76   37668.51   0.00
Maximum of Months 0.108066E+13 0.349535E+12 744.00 0.106955E+13 0.111073E+11 0.00 1.00   0.90   422669.57   407577.21   19211.25   153696.90   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.388000E+10 0.103832E+10 744.00 0.386082E+10 19172887.66 0.00 0.29 15-JAN-17:35 0.06 09-JAN-07:10 2286.82 20-JAN-17:00 2184.50 20-JAN-17:00 224.95 19-JAN-17:00 623.04 31-JAN-15:00 0.00
February 0.872691E+10 0.218294E+10 672.00 0.870482E+10 22097426.29 0.00 0.58 26-FEB-17:33 0.33 13-FEB-07:10 4453.16 20-FEB-17:57 4421.18 20-FEB-17:57 230.32 17-FEB-17:00 1394.61 26-FEB-17:12 0.00
March 0.156533E+11 0.384236E+10 744.00 0.155876E+11 65707574.37 0.00 0.84 31-MAR-24:00 0.59 22-MAR-06:30 7720.69 31-MAR-24:00 7720.69 31-MAR-24:00 305.38 31-MAR-11:40 2127.89 30-MAR-16:00 0.00
April 0.202801E+11 0.521182E+10 720.00 0.201905E+11 89602271.97 0.00 0.98 08-APR-18:12 0.30 30-APR-24:00 8432.87 09-APR-18:13 8432.87 09-APR-18:13 332.43 04-APR-10:00 2833.99 17-APR-16:00 0.00
May 0.614787E+10 0.174437E+10 744.00 0.591563E+10 0.232242E+09 0.00 0.49 31-MAY-24:00 0.20 11-MAY-06:10 4101.81 31-MAY-24:00 4047.65 31-MAY-24:00 339.64 31-MAY-11:00 1135.83 31-MAY-23:20 0.00
June 0.111893E+11 0.347399E+10 720.00 0.108197E+11 0.369590E+09 0.00 0.69 30-JUN-24:00 0.43 10-JUN-06:50 5924.57 30-JUN-23:03 5903.83 30-JUN-24:00 481.36 26-JUN-16:50 1869.53 06-JUN-15:10 0.00
July 0.167372E+11 0.533069E+10 744.00 0.162639E+11 0.473312E+09 0.00 0.91 31-JUL-23:53 0.66 29-JUL-06:10 7802.82 31-JUL-23:53 7783.51 31-JUL-23:53 548.65 26-JUL-09:00 2743.91 07-JUL-16:00 0.00
August 0.219282E+11 0.704147E+10 744.00 0.213794E+11 0.548867E+09 0.00 1.00 01-AUG-10:10 0.31 31-AUG-23:50 8910.23 04-AUG-15:00 8424.63 13-AUG-19:34 643.76 11-AUG-16:50 3243.57 01-AUG-16:10 0.00
September 0.612801E+10 0.180415E+10 720.00 0.581391E+10 0.314102E+09 0.00 0.45 30-SEP-24:00 0.21 29-SEP-06:10 3809.52 30-SEP-24:00 3795.04 30-SEP-24:00 419.16 05-SEP-11:00 1099.21 07-SEP-16:00 0.00
October 0.108360E+11 0.276590E+10 744.00 0.106852E+11 0.150796E+09 0.00 0.66 31-OCT-24:00 0.39 26-OCT-07:00 5714.11 31-OCT-24:00 5714.11 31-OCT-24:00 505.42 18-OCT-16:00 1661.56 10-OCT-16:00 0.00
November 0.150491E+11 0.363472E+10 720.00 0.149919E+11 57154858.80 0.00 0.78 19-NOV-16:50 0.59 30-NOV-22:00 6351.58 11-NOV-17:00 6351.58 11-NOV-17:00 281.70 27-NOV-17:10 1978.00 19-NOV-15:00 0.00
December 0.202053E+11 0.461241E+10 744.00 0.201732E+11 32074955.37 0.00 0.97 10-DEC-16:35 0.75 01-DEC-07:10 8238.83 11-DEC-16:50 8089.39 17-DEC-17:10 330.84 13-DEC-16:00 2360.68 12-DEC-14:50 0.00
                                       
Annual Sum or Average 0.156761E+12 0.426831E+11 8760.00 0.154387E+12 0.237472E+10 0.00                         0.00
Minimum of Months 0.388000E+10 0.103832E+10 672.00 0.386082E+10 19172887.66 0.00 0.29   0.06   2286.82   2184.50   224.95   623.04   0.00
Maximum of Months 0.219282E+11 0.704147E+10 744.00 0.213794E+11 0.548867E+09 0.00 1.00   0.75   8910.23   8432.87   643.76   3243.57   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.163281E+11 0.463079E+10 654.11 0.161539E+11 0.174256E+09 0.00 0.25 20-JAN-17:00 0.00 01-JAN-00:05 19530.52 20-JAN-17:00 18500.76 20-JAN-17:00 2118.61 19-JAN-17:00 5080.24 31-JAN-15:00 0.00
February 0.677968E+11 0.172764E+11 672.00 0.675829E+11 0.213917E+09 0.00 0.54 27-FEB-17:00 0.16 13-FEB-07:10 40685.97 28-FEB-17:00 40685.97 28-FEB-17:00 2243.60 17-FEB-17:00 12715.09 28-FEB-15:00 0.00
March 0.141442E+12 0.349919E+11 744.00 0.140785E+12 0.656478E+09 0.00 0.83 31-MAR-24:00 0.53 22-MAR-06:30 72458.81 31-MAR-24:00 72458.81 31-MAR-24:00 3024.72 31-MAR-11:40 20254.32 30-MAR-16:00 0.00
April 0.190165E+12 0.490304E+11 720.00 0.189267E+12 0.897917E+09 0.00 0.98 17-APR-16:00 0.27 30-APR-24:00 79426.71 04-APR-15:30 78436.75 17-APR-16:00 3327.66 04-APR-10:00 26907.43 17-APR-16:00 0.00
May 0.560115E+11 0.159838E+11 744.00 0.537319E+11 0.227964E+10 0.00 0.49 31-MAY-24:00 0.18 11-MAY-06:10 38870.98 31-MAY-24:00 38306.23 31-MAY-24:00 3377.93 31-MAY-11:00 10767.99 31-MAY-23:30 0.00
June 0.106096E+12 0.329672E+11 720.00 0.102419E+12 0.367678E+10 0.00 0.70 30-JUN-24:00 0.41 10-JUN-07:00 56867.18 30-JUN-24:00 56666.29 30-JUN-24:00 4793.58 23-JUN-10:10 17842.99 06-JUN-15:10 0.00
July 0.159566E+12 0.508156E+11 744.00 0.154846E+12 0.472044E+10 0.00 0.92 31-JUL-23:53 0.64 29-JUL-06:10 75557.80 31-JUL-23:53 75369.05 31-JUL-23:53 5481.10 26-JUL-09:00 26178.28 07-JUL-16:00 0.00
August 0.208708E+12 0.670100E+11 744.00 0.203221E+12 0.548640E+10 0.00 1.00 01-AUG-09:50 0.27 31-AUG-24:00 84473.89 04-AUG-14:50 79374.76 13-AUG-18:35 6392.27 11-AUG-16:50 30903.59 01-AUG-16:10 0.00
September 0.553801E+11 0.164078E+11 720.00 0.523021E+11 0.307803E+10 0.00 0.41 30-SEP-24:00 0.17 30-SEP-17:00 32864.18 30-SEP-24:00 32646.88 30-SEP-24:00 4148.34 05-SEP-11:00 10459.35 07-SEP-16:00 0.00
October 0.954332E+11 0.246084E+11 744.00 0.939438E+11 0.148948E+10 0.00 0.61 31-OCT-24:00 0.33 31-OCT-07:00 50037.09 31-OCT-24:00 50037.09 31-OCT-24:00 5030.77 18-OCT-16:00 15678.14 10-OCT-16:00 0.00
November 0.131632E+12 0.321450E+11 720.00 0.131067E+12 0.565633E+09 0.00 0.76 08-NOV-17:00 0.52 25-NOV-07:10 59251.80 02-NOV-16:00 58871.43 08-NOV-17:00 2791.11 27-NOV-17:00 17683.00 19-NOV-16:53 0.00
December 0.173194E+12 0.401347E+11 744.00 0.172872E+12 0.321952E+09 0.00 0.91 12-DEC-15:10 0.65 26-DEC-07:30 76764.68 11-DEC-17:00 74873.81 11-DEC-17:00 3293.92 13-DEC-16:00 22121.17 12-DEC-15:00 0.00
                                       
Annual Sum or Average 0.140175E+13 0.386002E+12 8670.11 0.137819E+13 0.235609E+11 0.00                         0.00
Minimum of Months 0.163281E+11 0.463079E+10 654.11 0.161539E+11 0.174256E+09 0.00 0.25   0.00   19530.52   18500.76   2118.61   5080.24   0.00
Maximum of Months 0.208708E+12 0.670100E+11 744.00 0.203221E+12 0.548640E+10 0.00 1.00   0.65   84473.89   79374.76   6392.27   30903.59   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.703677E+09 0.200533E+09 331.40 0.687387E+09 16290418.65 0.00 0.25 20-JAN-17:00 0.00 01-JAN-00:05 1973.82 20-JAN-17:00 1868.80 20-JAN-17:00 216.91 19-JAN-17:00 485.47 31-JAN-17:00 0.00
February 0.552683E+10 0.142777E+10 663.89 0.550586E+10 20968092.39 0.00 0.54 27-FEB-17:00 0.00 05-FEB-05:23 4095.19 28-FEB-17:00 4095.19 28-FEB-17:00 222.89 17-FEB-17:00 1271.39 28-FEB-15:00 0.00
March 0.133685E+11 0.333794E+10 744.00 0.133033E+11 65201313.23 0.00 0.80 31-MAR-23:20 0.45 23-MAR-06:10 6990.82 31-MAR-23:20 6990.82 31-MAR-23:20 302.61 31-MAR-11:40 2051.25 30-MAR-16:00 0.00
April 0.186427E+11 0.483479E+10 720.00 0.185532E+11 89463170.26 0.00 0.98 17-APR-16:00 0.26 30-APR-24:00 7986.02 17-APR-16:00 7949.96 17-APR-16:00 332.84 04-APR-10:00 2725.79 17-APR-16:00 0.00
May 0.551972E+10 0.158454E+10 744.00 0.529231E+10 0.227404E+09 0.00 0.48 31-MAY-23:50 0.12 11-MAY-07:00 3847.58 31-MAY-23:20 3789.24 31-MAY-24:00 342.31 31-MAY-11:00 1068.85 31-MAY-23:20 0.00
June 0.106704E+11 0.332227E+10 720.00 0.103026E+11 0.367771E+09 0.00 0.69 30-JUN-24:00 0.38 08-JUN-06:50 5667.46 30-JUN-24:00 5647.25 30-JUN-24:00 480.95 23-JUN-10:10 1818.39 06-JUN-15:10 0.00
July 0.160464E+11 0.511794E+10 744.00 0.155745E+11 0.471868E+09 0.00 0.91 31-JUL-23:53 0.62 29-JUL-07:00 7592.84 31-JUL-23:53 7573.86 31-JUL-23:53 548.49 26-JUL-09:00 2667.68 07-JUL-16:00 0.00
August 0.209686E+11 0.674115E+10 744.00 0.204201E+11 0.548496E+09 0.00 1.00 01-AUG-10:10 0.26 31-AUG-24:00 8556.78 04-AUG-15:00 8109.63 13-AUG-19:32 637.73 11-AUG-16:50 3123.81 01-AUG-16:10 0.00
September 0.541425E+10 0.161460E+10 720.00 0.510815E+10 0.306100E+09 0.00 0.39 07-SEP-16:00 0.12 29-SEP-07:00 2972.15 07-SEP-16:00 2804.90 30-SEP-24:00 417.20 05-SEP-11:00 1075.08 07-SEP-16:00 0.00
October 0.884832E+10 0.230827E+10 744.00 0.870021E+10 0.148115E+09 0.00 0.58 10-OCT-16:00 0.23 30-OCT-06:10 4596.63 18-OCT-16:00 4574.69 31-OCT-23:20 503.65 18-OCT-16:00 1588.04 10-OCT-16:00 0.00
November 0.119724E+11 0.296019E+10 720.00 0.119165E+11 55930218.19 0.00 0.74 08-NOV-17:00 0.40 22-NOV-07:10 5955.09 02-NOV-16:00 5878.44 06-NOV-17:00 278.54 27-NOV-17:00 1726.69 02-NOV-14:00 0.00
December 0.155396E+11 0.365460E+10 744.00 0.155076E+11 31966906.42 0.00 0.90 12-DEC-15:20 0.48 18-DEC-04:13 7637.30 13-DEC-16:00 7422.15 12-DEC-15:40 328.92 13-DEC-16:00 2205.41 12-DEC-15:00 0.00
                                       
Annual Sum or Average 0.133221E+12 0.371046E+11 8339.29 0.130872E+12 0.234957E+10 0.00                         0.00
Minimum of Months 0.703677E+09 0.200533E+09 331.40 0.687387E+09 16290418.65 0.00 0.25   0.00   1973.82   1868.80   216.91   485.47   0.00
Maximum of Months 0.209686E+11 0.674115E+10 744.00 0.204201E+11 0.548496E+09 0.00 1.00   0.62   8556.78   8109.63   637.73   3123.81   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.22 0.00 74.22 6.60 594.35 0.00 0.00 0.00
February 82.27 0.00 82.27 27.05 489.95 0.00 0.00 0.00
March 115.50 0.00 115.50 67.31 309.58 0.00 0.00 0.00
April 139.70 0.62 139.08 145.20 234.52 0.00 0.00 0.00
May 167.08 5.33 161.75 232.04 146.16 0.00 0.00 0.00
June 183.88 12.14 171.74 337.13 88.28 0.00 0.00 0.00
July 173.49 8.43 165.06 338.00 62.11 0.00 0.00 0.00
August 154.29 1.68 152.61 307.92 50.76 0.00 0.00 0.00
September 116.63 0.02 116.62 173.13 126.75 0.00 0.00 0.00
October 88.68 0.00 88.68 70.44 282.05 0.00 0.00 0.00
November 79.36 0.00 79.36 29.10 393.90 0.00 0.00 0.00
December 68.61 0.00 68.61 5.40 513.35 0.00 0.00 0.00
                 
Annual Sum or Average 120.52 2.36 118.16 145.63 273.24 0.00 0.00 0.00
Minimum of Months 68.61 0.00 68.61 5.40 50.76 0.00 0.00 0.00
Maximum of Months 183.88 12.14 171.74 338.00 594.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.22 0.00 74.22 6.60 594.35 0.00 0.00 0.00
February 82.26 0.00 82.26 27.05 489.95 0.00 0.00 0.00
March 115.49 0.00 115.49 67.31 309.58 0.00 0.00 0.00
April 139.70 0.62 139.08 145.20 234.52 0.00 0.00 0.00
May 167.08 5.33 161.75 232.04 146.16 0.00 0.00 0.00
June 183.88 12.14 171.74 337.13 88.28 0.00 0.00 0.00
July 173.49 8.43 165.06 338.00 62.11 0.00 0.00 0.00
August 154.29 1.68 152.61 307.92 50.76 0.00 0.00 0.00
September 116.63 0.02 116.61 173.13 126.75 0.00 0.00 0.00
October 88.68 0.00 88.68 70.44 282.05 0.00 0.00 0.00
November 79.36 0.00 79.36 29.10 393.90 0.00 0.00 0.00
December 68.61 0.00 68.61 5.40 513.35 0.00 0.00 0.00
                 
Annual Sum or Average 120.52 2.36 118.15 145.62 273.24 0.00 0.00 0.00
Minimum of Months 68.61 0.00 68.61 5.40 50.76 0.00 0.00 0.00
Maximum of Months 183.88 12.14 171.74 338.00 594.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.22 0.00 74.22 6.60 594.35 0.00 0.00 0.00
February 82.26 0.00 82.26 27.05 489.95 0.00 0.00 0.00
March 115.50 0.00 115.50 67.31 309.58 0.00 0.00 0.00
April 139.70 0.62 139.08 145.20 234.52 0.00 0.00 0.00
May 167.08 5.33 161.75 232.04 146.16 0.00 0.00 0.00
June 183.88 12.14 171.74 337.13 88.28 0.00 0.00 0.00
July 173.49 8.43 165.06 338.00 62.11 0.00 0.00 0.00
August 154.29 1.68 152.61 307.92 50.76 0.00 0.00 0.00
September 116.63 0.02 116.61 173.13 126.75 0.00 0.00 0.00
October 88.68 0.00 88.68 70.44 282.05 0.00 0.00 0.00
November 79.36 0.00 79.36 29.10 393.90 0.00 0.00 0.00
December 68.61 0.00 68.61 5.40 513.35 0.00 0.00 0.00
                 
Annual Sum or Average 120.52 2.36 118.15 145.62 273.24 0.00 0.00 0.00
Minimum of Months 68.61 0.00 68.61 5.40 50.76 0.00 0.00 0.00
Maximum of Months 183.88 12.14 171.74 338.00 594.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.22 0.00 74.22 6.60 594.35 0.00 0.00 0.00
February 82.26 0.00 82.26 27.05 489.95 0.00 0.00 0.00
March 115.49 0.00 115.49 67.31 309.58 0.00 0.00 0.00
April 139.70 0.62 139.08 145.20 234.52 0.00 0.00 0.00
May 167.08 5.33 161.75 232.04 146.16 0.00 0.00 0.00
June 183.88 12.14 171.74 337.13 88.28 0.00 0.00 0.00
July 173.49 8.43 165.06 338.00 62.11 0.00 0.00 0.00
August 154.29 1.68 152.61 307.92 50.76 0.00 0.00 0.00
September 116.63 0.02 116.61 173.13 126.75 0.00 0.00 0.00
October 88.68 0.00 88.68 70.44 282.05 0.00 0.00 0.00
November 79.36 0.00 79.36 29.10 393.90 0.00 0.00 0.00
December 68.61 0.00 68.61 5.40 513.35 0.00 0.00 0.00
                 
Annual Sum or Average 120.52 2.36 118.15 145.62 273.24 0.00 0.00 0.00
Minimum of Months 68.61 0.00 68.61 5.40 50.76 0.00 0.00 0.00
Maximum of Months 183.88 12.14 171.74 338.00 594.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.22 0.00 74.22 6.60 594.33 0.00 0.00 0.00
February 82.26 0.00 82.26 27.05 489.93 0.00 0.00 0.00
March 115.49 0.00 115.49 67.31 309.57 0.00 0.00 0.00
April 139.70 0.62 139.08 145.19 234.51 0.00 0.00 0.00
May 167.07 5.33 161.74 232.03 146.16 0.00 0.00 0.00
June 183.87 12.14 171.73 337.12 88.28 0.00 0.00 0.00
July 173.48 8.43 165.05 337.98 62.10 0.00 0.00 0.00
August 154.29 1.68 152.61 307.91 50.76 0.00 0.00 0.00
September 116.63 0.02 116.61 173.12 126.75 0.00 0.00 0.00
October 88.67 0.00 88.67 70.44 282.03 0.00 0.00 0.00
November 79.36 0.00 79.36 29.10 393.88 0.00 0.00 0.00
December 68.61 0.00 68.61 5.40 513.33 0.00 0.00 0.00
                 
Annual Sum or Average 120.51 2.36 118.15 145.62 273.23 0.00 0.00 0.00
Minimum of Months 68.61 0.00 68.61 5.40 50.76 0.00 0.00 0.00
Maximum of Months 183.87 12.14 171.73 337.98 594.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 181.11 81.69 99.42 114.23 585.41 0.00 0.00 0.00
February 228.32 122.67 105.65 209.02 479.03 0.00 0.00 0.00
March 287.25 130.77 156.49 316.16 302.09 0.00 0.00 0.00
April 347.36 158.39 188.97 478.30 232.10 0.00 0.00 0.00
May 381.43 161.30 220.13 588.34 156.87 0.00 0.00 0.00
June 394.91 165.52 229.39 700.36 93.42 0.00 0.00 0.00
July 385.05 161.88 223.17 708.73 62.49 0.00 0.00 0.00
August 352.20 139.73 212.47 660.57 47.01 0.00 0.00 0.00
September 289.46 128.25 161.21 465.47 131.20 0.00 0.00 0.00
October 246.93 128.48 118.45 311.13 279.08 0.00 0.00 0.00
November 197.42 89.39 108.03 180.83 377.69 0.00 0.00 0.00
December 171.01 77.95 93.06 114.87 488.60 0.00 0.00 0.00
                 
Annual Sum or Average 288.83 128.81 160.01 405.03 268.53 0.00 0.00 0.00
Minimum of Months 171.01 77.95 93.06 114.23 47.01 0.00 0.00 0.00
Maximum of Months 394.91 165.52 229.39 708.73 585.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 181.11 81.69 99.42 114.23 585.41 0.00 0.00 0.00
February 228.32 122.67 105.65 209.02 479.03 0.00 0.00 0.00
March 287.25 130.77 156.49 316.16 302.09 0.00 0.00 0.00
April 347.36 158.39 188.97 478.30 232.10 0.00 0.00 0.00
May 381.43 161.30 220.13 588.34 156.87 0.00 0.00 0.00
June 394.91 165.52 229.39 700.36 93.42 0.00 0.00 0.00
July 385.05 161.88 223.17 708.73 62.49 0.00 0.00 0.00
August 352.20 139.73 212.47 660.57 47.01 0.00 0.00 0.00
September 289.46 128.25 161.21 465.47 131.20 0.00 0.00 0.00
October 246.93 128.48 118.45 311.13 279.08 0.00 0.00 0.00
November 197.42 89.39 108.03 180.83 377.69 0.00 0.00 0.00
December 171.01 77.95 93.06 114.87 488.60 0.00 0.00 0.00
                 
Annual Sum or Average 288.83 128.81 160.01 405.03 268.53 0.00 0.00 0.00
Minimum of Months 171.01 77.95 93.06 114.23 47.01 0.00 0.00 0.00
Maximum of Months 394.91 165.52 229.39 708.73 585.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 181.10 81.69 99.42 114.23 585.40 0.00 0.00 0.00
February 228.32 122.67 105.64 209.02 479.02 0.00 0.00 0.00
March 287.25 130.76 156.48 316.16 302.08 0.00 0.00 0.00
April 347.36 158.39 188.97 478.29 232.09 0.00 0.00 0.00
May 381.42 161.30 220.12 588.33 156.87 0.00 0.00 0.00
June 394.90 165.51 229.39 700.34 93.42 0.00 0.00 0.00
July 385.04 161.88 223.17 708.72 62.49 0.00 0.00 0.00
August 352.19 139.73 212.46 660.56 47.01 0.00 0.00 0.00
September 289.45 128.25 161.20 465.46 131.20 0.00 0.00 0.00
October 246.93 128.48 118.44 311.13 279.07 0.00 0.00 0.00
November 197.42 89.39 108.03 180.83 377.68 0.00 0.00 0.00
December 171.00 77.95 93.05 114.87 488.59 0.00 0.00 0.00
                 
Annual Sum or Average 288.82 128.81 160.01 405.02 268.52 0.00 0.00 0.00
Minimum of Months 171.00 77.95 93.05 114.23 47.01 0.00 0.00 0.00
Maximum of Months 394.90 165.51 229.39 708.72 585.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 396.93 276.74 120.19 438.41 478.56 0.00 0.00 0.00
February 370.47 248.33 122.13 448.70 415.66 0.00 0.00 0.00
March 333.18 173.63 159.55 440.51 289.51 0.00 0.00 0.00
April 249.53 81.23 168.30 369.21 235.90 0.00 0.00 0.00
May 201.61 23.43 178.18 318.67 153.94 0.00 0.00 0.00
June 186.41 10.37 176.04 354.31 94.04 0.00 0.00 0.00
July 188.46 14.05 174.40 377.29 64.26 0.00 0.00 0.00
August 225.00 42.03 182.97 457.93 53.33 0.00 0.00 0.00
September 247.45 92.04 155.41 425.95 128.44 0.00 0.00 0.00
October 358.73 232.38 126.34 527.64 263.16 0.00 0.00 0.00
November 385.92 256.09 129.83 503.03 345.10 0.00 0.00 0.00
December 391.26 275.26 116.01 460.62 420.36 0.00 0.00 0.00
                 
Annual Sum or Average 294.25 143.31 150.94 426.83 244.27 0.00 0.00 0.00
Minimum of Months 186.41 10.37 116.01 318.67 53.33 0.00 0.00 0.00
Maximum of Months 396.93 276.74 182.97 527.64 478.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 396.93 276.74 120.19 438.41 478.56 0.00 0.00 0.00
February 370.47 248.33 122.13 448.70 415.66 0.00 0.00 0.00
March 333.18 173.63 159.55 440.50 289.51 0.00 0.00 0.00
April 249.53 81.23 168.30 369.21 235.90 0.00 0.00 0.00
May 201.61 23.43 178.18 318.67 153.94 0.00 0.00 0.00
June 186.41 10.37 176.04 354.31 94.04 0.00 0.00 0.00
July 188.46 14.05 174.40 377.29 64.26 0.00 0.00 0.00
August 225.00 42.03 182.97 457.92 53.33 0.00 0.00 0.00
September 247.45 92.04 155.41 425.94 128.44 0.00 0.00 0.00
October 358.72 232.38 126.34 527.63 263.16 0.00 0.00 0.00
November 385.92 256.09 129.83 503.03 345.10 0.00 0.00 0.00
December 391.26 275.25 116.01 460.61 420.36 0.00 0.00 0.00
                 
Annual Sum or Average 294.25 143.31 150.94 426.82 244.27 0.00 0.00 0.00
Minimum of Months 186.41 10.37 116.01 318.67 53.33 0.00 0.00 0.00
Maximum of Months 396.93 276.74 182.97 527.63 478.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 396.93 276.74 120.19 438.41 478.56 0.00 0.00 0.00
February 370.47 248.33 122.13 448.70 415.66 0.00 0.00 0.00
March 333.18 173.63 159.55 440.51 289.51 0.00 0.00 0.00
April 249.53 81.23 168.30 369.21 235.90 0.00 0.00 0.00
May 201.61 23.43 178.18 318.67 153.94 0.00 0.00 0.00
June 186.41 10.37 176.04 354.31 94.04 0.00 0.00 0.00
July 188.46 14.05 174.40 377.29 64.26 0.00 0.00 0.00
August 225.00 42.03 182.97 457.93 53.33 0.00 0.00 0.00
September 247.45 92.04 155.41 425.95 128.44 0.00 0.00 0.00
October 358.73 232.38 126.34 527.64 263.16 0.00 0.00 0.00
November 385.92 256.09 129.83 503.03 345.10 0.00 0.00 0.00
December 391.26 275.26 116.01 460.62 420.36 0.00 0.00 0.00
                 
Annual Sum or Average 294.25 143.31 150.94 426.83 244.27 0.00 0.00 0.00
Minimum of Months 186.41 10.37 116.01 318.67 53.33 0.00 0.00 0.00
Maximum of Months 396.93 276.74 182.97 527.64 478.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 396.93 276.74 120.19 438.41 478.56 0.00 0.00 0.00
February 370.47 248.33 122.13 448.70 415.66 0.00 0.00 0.00
March 333.18 173.63 159.55 440.50 289.51 0.00 0.00 0.00
April 249.53 81.23 168.30 369.21 235.90 0.00 0.00 0.00
May 201.61 23.43 178.18 318.67 153.94 0.00 0.00 0.00
June 186.41 10.37 176.04 354.31 94.04 0.00 0.00 0.00
July 188.46 14.05 174.40 377.29 64.26 0.00 0.00 0.00
August 225.00 42.03 182.97 457.92 53.33 0.00 0.00 0.00
September 247.45 92.04 155.41 425.94 128.44 0.00 0.00 0.00
October 358.72 232.38 126.34 527.63 263.16 0.00 0.00 0.00
November 385.92 256.09 129.83 503.03 345.10 0.00 0.00 0.00
December 391.26 275.25 116.01 460.61 420.36 0.00 0.00 0.00
                 
Annual Sum or Average 294.25 143.31 150.94 426.82 244.27 0.00 0.00 0.00
Minimum of Months 186.41 10.37 116.01 318.67 53.33 0.00 0.00 0.00
Maximum of Months 396.93 276.74 182.97 527.63 478.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 396.91 276.73 120.19 438.39 478.54 0.00 0.00 0.00
February 370.45 248.32 122.13 448.68 415.64 0.00 0.00 0.00
March 333.16 173.62 159.54 440.49 289.50 0.00 0.00 0.00
April 249.52 81.22 168.29 369.19 235.89 0.00 0.00 0.00
May 201.60 23.43 178.17 318.65 153.93 0.00 0.00 0.00
June 186.40 10.37 176.03 354.29 94.03 0.00 0.00 0.00
July 188.45 14.05 174.40 377.27 64.26 0.00 0.00 0.00
August 224.99 42.03 182.96 457.91 53.33 0.00 0.00 0.00
September 247.44 92.03 155.40 425.93 128.44 0.00 0.00 0.00
October 358.71 232.37 126.34 527.61 263.15 0.00 0.00 0.00
November 385.91 256.08 129.83 503.01 345.09 0.00 0.00 0.00
December 391.25 275.24 116.00 460.60 420.34 0.00 0.00 0.00
                 
Annual Sum or Average 294.24 143.30 150.94 426.81 244.26 0.00 0.00 0.00
Minimum of Months 186.40 10.37 116.00 318.65 53.33 0.00 0.00 0.00
Maximum of Months 396.91 276.73 182.96 527.61 478.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 186.02 86.29 99.73 131.88 635.38 0.00 0.00 0.00
February 213.55 99.85 113.70 200.89 552.40 0.00 0.00 0.00
March 314.76 152.10 162.66 368.25 376.44 0.00 0.00 0.00
April 354.10 162.04 192.07 482.67 301.53 0.00 0.00 0.00
May 355.89 134.83 221.05 551.71 188.14 0.00 0.00 0.00
June 374.26 143.98 230.28 658.34 123.89 0.00 0.00 0.00
July 353.01 130.89 222.13 639.86 92.18 0.00 0.00 0.00
August 345.90 129.35 216.55 630.12 85.07 0.00 0.00 0.00
September 281.82 117.39 164.43 449.00 157.68 0.00 0.00 0.00
October 251.06 130.33 120.73 328.87 340.65 0.00 0.00 0.00
November 200.37 89.94 110.43 202.39 467.76 0.00 0.00 0.00
December 165.30 72.30 93.00 120.29 603.86 0.00 0.00 0.00
                 
Annual Sum or Average 283.36 120.86 162.50 398.08 325.93 0.00 0.00 0.00
Minimum of Months 165.30 72.30 93.00 120.29 85.07 0.00 0.00 0.00
Maximum of Months 374.26 162.04 230.28 658.34 635.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 186.02 86.29 99.73 131.88 635.38 0.00 0.00 0.00
February 213.55 99.85 113.70 200.89 552.40 0.00 0.00 0.00
March 314.76 152.10 162.66 368.25 376.44 0.00 0.00 0.00
April 354.10 162.04 192.07 482.67 301.53 0.00 0.00 0.00
May 355.89 134.83 221.05 551.71 188.14 0.00 0.00 0.00
June 374.26 143.98 230.28 658.34 123.89 0.00 0.00 0.00
July 353.01 130.89 222.13 639.86 92.18 0.00 0.00 0.00
August 345.90 129.35 216.55 630.12 85.07 0.00 0.00 0.00
September 281.82 117.39 164.43 449.00 157.68 0.00 0.00 0.00
October 251.06 130.33 120.73 328.87 340.65 0.00 0.00 0.00
November 200.37 89.94 110.43 202.39 467.76 0.00 0.00 0.00
December 165.30 72.30 93.00 120.29 603.86 0.00 0.00 0.00
                 
Annual Sum or Average 283.36 120.86 162.50 398.08 325.93 0.00 0.00 0.00
Minimum of Months 165.30 72.30 93.00 120.29 85.07 0.00 0.00 0.00
Maximum of Months 374.26 162.04 230.28 658.34 635.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 186.02 86.29 99.73 131.88 635.36 0.00 0.00 0.00
February 213.55 99.85 113.70 200.89 552.39 0.00 0.00 0.00
March 314.76 152.10 162.66 368.24 376.44 0.00 0.00 0.00
April 354.10 162.03 192.06 482.66 301.52 0.00 0.00 0.00
May 355.88 134.83 221.05 551.70 188.13 0.00 0.00 0.00
June 374.25 143.97 230.28 658.33 123.89 0.00 0.00 0.00
July 353.01 130.88 222.12 639.85 92.18 0.00 0.00 0.00
August 345.90 129.35 216.54 630.11 85.07 0.00 0.00 0.00
September 281.81 117.39 164.42 448.99 157.68 0.00 0.00 0.00
October 251.06 130.33 120.73 328.86 340.64 0.00 0.00 0.00
November 200.36 89.93 110.43 202.39 467.76 0.00 0.00 0.00
December 165.30 72.30 93.00 120.29 603.85 0.00 0.00 0.00
                 
Annual Sum or Average 283.35 120.86 162.49 398.07 325.93 0.00 0.00 0.00
Minimum of Months 165.30 72.30 93.00 120.29 85.07 0.00 0.00 0.00
Maximum of Months 374.25 162.03 230.28 658.33 635.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 371.10 0.00 371.10 49.29 2641.84 0.00 0.00 0.00
February 411.33 0.00 411.33 168.33 2173.89 0.00 0.00 0.00
March 577.48 0.00 577.48 379.58 1385.65 0.00 0.00 0.00
April 698.52 3.10 695.42 760.05 1093.88 0.00 0.00 0.00
May 835.42 26.66 808.75 1169.89 704.82 0.00 0.00 0.00
June 919.41 60.70 858.71 1694.48 440.58 0.00 0.00 0.00
July 867.47 42.17 825.30 1701.53 314.46 0.00 0.00 0.00
August 771.47 8.40 763.07 1556.70 259.43 0.00 0.00 0.00
September 583.16 0.08 583.08 880.14 599.61 0.00 0.00 0.00
October 443.39 0.00 443.39 388.95 1261.01 0.00 0.00 0.00
November 396.82 0.00 396.82 195.66 1726.38 0.00 0.00 0.00
December 343.05 0.00 343.05 49.38 2171.93 0.00 0.00 0.00
                 
Annual Sum or Average 602.59 11.81 590.78 752.82 1226.29 0.00 0.00 0.00
Minimum of Months 343.05 0.00 343.05 49.29 259.43 0.00 0.00 0.00
Maximum of Months 919.41 60.70 858.71 1701.53 2641.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 543.32 245.06 298.25 367.95 1580.23 0.00 0.00 0.00
February 684.95 368.02 316.93 650.00 1309.56 0.00 0.00 0.00
March 861.75 392.29 469.46 959.64 850.08 0.00 0.00 0.00
April 1042.08 475.16 566.92 1428.64 687.60 0.00 0.00 0.00
May 1144.28 483.90 660.38 1752.18 464.63 0.00 0.00 0.00
June 1184.71 496.54 688.17 2084.79 296.20 0.00 0.00 0.00
July 1155.14 485.64 669.50 2107.83 210.87 0.00 0.00 0.00
August 1056.57 419.18 637.39 1963.86 173.30 0.00 0.00 0.00
September 868.36 384.75 483.61 1392.54 383.85 0.00 0.00 0.00
October 740.78 385.45 355.34 944.18 777.31 0.00 0.00 0.00
November 592.26 268.17 324.09 575.69 1030.10 0.00 0.00 0.00
December 513.01 233.85 279.16 373.75 1291.94 0.00 0.00 0.00
                 
Annual Sum or Average 866.47 386.44 480.03 1219.73 751.78 0.00 0.00 0.00
Minimum of Months 513.01 233.85 279.16 367.95 173.30 0.00 0.00 0.00
Maximum of Months 1184.71 496.54 688.17 2107.83 1580.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1984.69 1383.72 600.97 2198.90 2277.06 0.00 0.00 0.00
February 1852.38 1241.70 610.68 2246.19 1971.66 0.00 0.00 0.00
March 1665.92 868.18 797.74 2192.73 1389.56 0.00 0.00 0.00
April 1247.66 406.14 841.52 1843.54 1146.60 0.00 0.00 0.00
May 1008.06 117.16 890.89 1590.88 752.83 0.00 0.00 0.00
June 932.06 51.87 880.19 1777.78 470.98 0.00 0.00 0.00
July 942.29 70.26 872.03 1894.82 328.68 0.00 0.00 0.00
August 1125.03 210.16 914.87 2294.65 279.75 0.00 0.00 0.00
September 1237.25 460.19 777.06 2122.27 630.02 0.00 0.00 0.00
October 1793.66 1161.94 631.73 2624.88 1266.92 0.00 0.00 0.00
November 1929.66 1280.49 649.17 2515.16 1647.76 0.00 0.00 0.00
December 1956.35 1376.31 580.04 2317.00 1957.06 0.00 0.00 0.00
                 
Annual Sum or Average 1471.29 716.57 754.72 2134.75 1172.26 0.00 0.00 0.00
Minimum of Months 932.06 51.87 580.04 1590.88 279.75 0.00 0.00 0.00
Maximum of Months 1984.69 1383.72 914.87 2624.88 2277.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 558.06 258.87 299.19 426.49 1680.91 0.00 0.00 0.00
February 640.65 299.54 341.11 644.49 1418.42 0.00 0.00 0.00
March 944.28 456.30 487.98 1150.78 951.91 0.00 0.00 0.00
April 1062.30 486.10 576.20 1497.76 781.17 0.00 0.00 0.00
May 1067.64 404.49 663.16 1668.04 523.20 0.00 0.00 0.00
June 1122.77 431.92 690.84 1995.04 341.95 0.00 0.00 0.00
July 1059.03 392.65 666.38 1954.17 242.80 0.00 0.00 0.00
August 1037.70 388.06 649.64 1933.07 211.06 0.00 0.00 0.00
September 845.44 352.16 493.28 1364.83 424.98 0.00 0.00 0.00
October 753.19 390.99 362.20 1020.89 871.08 0.00 0.00 0.00
November 601.10 269.80 331.29 664.92 1158.68 0.00 0.00 0.00
December 495.90 216.91 278.99 411.75 1425.84 0.00 0.00 0.00
                 
Annual Sum or Average 850.07 362.58 487.49 1230.80 832.96 0.00 0.00 0.00
Minimum of Months 495.90 216.91 278.99 411.75 211.06 0.00 0.00 0.00
Maximum of Months 1122.77 486.10 690.84 1995.04 1680.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 371.10 0.00 371.10 62.59 2468.48 0.00 0.00 0.00
February 411.33 0.00 411.33 185.94 2034.24 0.00 0.00 0.00
March 577.48 0.00 577.48 410.43 1274.52 0.00 0.00 0.00
April 698.52 3.10 695.42 779.65 1036.32 0.00 0.00 0.00
May 835.42 26.66 808.75 1166.37 690.85 0.00 0.00 0.00
June 919.41 60.70 858.71 1676.14 445.72 0.00 0.00 0.00
July 867.47 42.17 825.30 1679.37 319.90 0.00 0.00 0.00
August 771.47 8.40 763.07 1534.99 266.23 0.00 0.00 0.00
September 583.16 0.08 583.08 879.79 578.50 0.00 0.00 0.00
October 443.39 0.00 443.39 414.33 1156.35 0.00 0.00 0.00
November 396.82 0.00 396.82 234.58 1563.22 0.00 0.00 0.00
December 343.05 0.00 343.05 65.33 1967.37 0.00 0.00 0.00
                 
Annual Sum or Average 602.59 11.81 590.78 760.68 1145.55 0.00 0.00 0.00
Minimum of Months 343.05 0.00 343.05 62.59 266.23 0.00 0.00 0.00
Maximum of Months 919.41 60.70 858.71 1679.37 2468.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 543.32 245.06 298.25 389.48 1473.12 0.00 0.00 0.00
February 684.95 368.02 316.93 670.32 1228.81 0.00 0.00 0.00
March 861.75 392.29 469.46 981.01 797.69 0.00 0.00 0.00
April 1042.08 475.16 566.92 1435.62 664.33 0.00 0.00 0.00
May 1144.28 483.90 660.38 1743.66 462.71 0.00 0.00 0.00
June 1184.71 496.54 688.17 2068.43 302.74 0.00 0.00 0.00
July 1155.14 485.64 669.50 2088.91 216.22 0.00 0.00 0.00
August 1056.57 419.18 637.39 1945.71 179.42 0.00 0.00 0.00
September 868.36 384.75 483.61 1387.06 377.86 0.00 0.00 0.00
October 740.78 385.45 355.34 958.92 730.00 0.00 0.00 0.00
November 592.26 268.17 324.09 610.04 946.61 0.00 0.00 0.00
December 513.01 233.85 279.16 398.45 1172.93 0.00 0.00 0.00
                 
Annual Sum or Average 866.47 386.44 480.03 1226.01 709.99 0.00 0.00 0.00
Minimum of Months 513.01 233.85 279.16 389.48 179.42 0.00 0.00 0.00
Maximum of Months 1184.71 496.54 688.17 2088.91 1473.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1984.69 1383.72 600.97 2257.56 2105.55 0.00 0.00 0.00
February 1852.38 1241.70 610.68 2285.10 1839.68 0.00 0.00 0.00
March 1665.92 868.18 797.74 2219.49 1300.06 0.00 0.00 0.00
April 1247.66 406.14 841.52 1855.01 1096.94 0.00 0.00 0.00
May 1008.06 117.16 890.89 1583.35 740.05 0.00 0.00 0.00
June 932.06 51.87 880.19 1758.89 475.31 0.00 0.00 0.00
July 942.29 70.26 872.03 1872.01 333.66 0.00 0.00 0.00
August 1125.03 210.16 914.87 2271.06 287.51 0.00 0.00 0.00
September 1237.25 460.19 777.06 2115.91 615.89 0.00 0.00 0.00
October 1793.66 1161.94 631.73 2640.84 1187.73 0.00 0.00 0.00
November 1929.66 1280.49 649.17 2564.29 1514.90 0.00 0.00 0.00
December 1956.35 1376.31 580.04 2375.94 1772.93 0.00 0.00 0.00
                 
Annual Sum or Average 1471.29 716.57 754.72 2149.68 1101.79 0.00 0.00 0.00
Minimum of Months 932.06 51.87 580.04 1583.35 287.51 0.00 0.00 0.00
Maximum of Months 1984.69 1383.72 914.87 2640.84 2105.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 558.06 258.87 299.19 442.29 1571.98 0.00 0.00 0.00
February 640.65 299.54 341.11 655.15 1339.36 0.00 0.00 0.00
March 944.28 456.30 487.98 1162.71 894.90 0.00 0.00 0.00
April 1062.30 486.10 576.20 1503.30 751.85 0.00 0.00 0.00
May 1067.64 404.49 663.16 1662.43 516.27 0.00 0.00 0.00
June 1122.77 431.92 690.84 1980.60 344.82 0.00 0.00 0.00
July 1059.03 392.65 666.38 1939.30 245.25 0.00 0.00 0.00
August 1037.70 388.06 649.64 1918.25 214.78 0.00 0.00 0.00
September 845.44 352.16 493.28 1362.00 415.25 0.00 0.00 0.00
October 753.19 390.99 362.20 1029.83 819.15 0.00 0.00 0.00
November 601.10 269.80 331.29 685.43 1074.20 0.00 0.00 0.00
December 495.90 216.91 278.99 426.66 1312.34 0.00 0.00 0.00
                 
Annual Sum or Average 850.07 362.58 487.49 1233.73 788.77 0.00 0.00 0.00
Minimum of Months 495.90 216.91 278.99 426.66 214.78 0.00 0.00 0.00
Maximum of Months 1122.77 486.10 690.84 1980.60 1571.98 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198791E+09 0.00 0.198791E+09 17678423.19 0.159192E+10
February 0.199017E+09 0.00 0.199017E+09 65431587.98 0.118528E+10
March 0.309346E+09 0.00 0.309346E+09 0.180281E+09 0.829177E+09
April 0.362112E+09 1606061.20 0.360506E+09 0.376360E+09 0.607880E+09
May 0.447516E+09 14282166.31 0.433234E+09 0.621497E+09 0.391484E+09
June 0.476624E+09 31468210.52 0.445155E+09 0.873846E+09 0.228828E+09
July 0.464685E+09 22588531.99 0.442097E+09 0.905303E+09 0.166348E+09
August 0.413261E+09 4501801.68 0.408759E+09 0.824740E+09 0.135968E+09
September 0.302309E+09 42556.45 0.302267E+09 0.448748E+09 0.328538E+09
October 0.237518E+09 0.00 0.237518E+09 0.188668E+09 0.755433E+09
November 0.205713E+09 0.00 0.205713E+09 75437397.74 0.102098E+10
December 0.183767E+09 0.00 0.183767E+09 14453234.12 0.137496E+10
           
Annual Sum or Average 0.380066E+10 74489328.14 0.372617E+10 0.459244E+10 0.861680E+10
Minimum of Months 0.183767E+09 0.00 0.183767E+09 14453234.12 0.135968E+09
Maximum of Months 0.476624E+09 31468210.52 0.445155E+09 0.905303E+09 0.159192E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198788E+09 0.00 0.198788E+09 17677743.18 0.159192E+10
February 0.199014E+09 0.00 0.199014E+09 65430064.09 0.118528E+10
March 0.309342E+09 0.00 0.309342E+09 0.180277E+09 0.829176E+09
April 0.362107E+09 1606025.89 0.360501E+09 0.376354E+09 0.607879E+09
May 0.447510E+09 14281852.33 0.433228E+09 0.621488E+09 0.391483E+09
June 0.476617E+09 31467518.73 0.445149E+09 0.873836E+09 0.228826E+09
July 0.464678E+09 22588035.41 0.442090E+09 0.905293E+09 0.166347E+09
August 0.413255E+09 4501702.71 0.408754E+09 0.824732E+09 0.135967E+09
September 0.302305E+09 42555.51 0.302263E+09 0.448743E+09 0.328536E+09
October 0.237515E+09 0.00 0.237515E+09 0.188666E+09 0.755432E+09
November 0.205710E+09 0.00 0.205710E+09 75435236.01 0.102098E+10
December 0.183765E+09 0.00 0.183765E+09 14452551.87 0.137496E+10
           
Annual Sum or Average 0.380061E+10 74487690.58 0.372612E+10 0.459238E+10 0.861678E+10
Minimum of Months 0.183765E+09 0.00 0.183765E+09 14452551.87 0.135967E+09
Maximum of Months 0.476617E+09 31467518.73 0.445149E+09 0.905293E+09 0.159192E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198789E+09 0.00 0.198789E+09 17677969.85 0.159192E+10
February 0.199015E+09 0.00 0.199015E+09 65430572.06 0.118528E+10
March 0.309343E+09 0.00 0.309343E+09 0.180279E+09 0.829176E+09
April 0.362109E+09 1606037.66 0.360502E+09 0.376356E+09 0.607879E+09
May 0.447512E+09 14281956.99 0.433230E+09 0.621491E+09 0.391484E+09
June 0.476619E+09 31467749.32 0.445151E+09 0.873839E+09 0.228827E+09
July 0.464681E+09 22588200.93 0.442092E+09 0.905296E+09 0.166347E+09
August 0.413257E+09 4501735.70 0.408755E+09 0.824734E+09 0.135967E+09
September 0.302307E+09 42555.83 0.302264E+09 0.448745E+09 0.328537E+09
October 0.237516E+09 0.00 0.237516E+09 0.188667E+09 0.755432E+09
November 0.205711E+09 0.00 0.205711E+09 75435956.58 0.102098E+10
December 0.183766E+09 0.00 0.183766E+09 14452779.29 0.137496E+10
           
Annual Sum or Average 0.380062E+10 74488236.43 0.372613E+10 0.459240E+10 0.861679E+10
Minimum of Months 0.183766E+09 0.00 0.183766E+09 14452779.29 0.135967E+09
Maximum of Months 0.476619E+09 31467749.32 0.445151E+09 0.905296E+09 0.159192E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198788E+09 0.00 0.198788E+09 17677743.18 0.159192E+10
February 0.199014E+09 0.00 0.199014E+09 65430064.09 0.118528E+10
March 0.309342E+09 0.00 0.309342E+09 0.180277E+09 0.829176E+09
April 0.362107E+09 1606025.89 0.360501E+09 0.376354E+09 0.607879E+09
May 0.447510E+09 14281852.33 0.433228E+09 0.621488E+09 0.391483E+09
June 0.476617E+09 31467518.73 0.445149E+09 0.873836E+09 0.228826E+09
July 0.464678E+09 22588035.41 0.442090E+09 0.905293E+09 0.166347E+09
August 0.413255E+09 4501702.71 0.408754E+09 0.824732E+09 0.135967E+09
September 0.302305E+09 42555.51 0.302263E+09 0.448743E+09 0.328536E+09
October 0.237515E+09 0.00 0.237515E+09 0.188666E+09 0.755432E+09
November 0.205710E+09 0.00 0.205710E+09 75435236.01 0.102098E+10
December 0.183765E+09 0.00 0.183765E+09 14452551.87 0.137496E+10
           
Annual Sum or Average 0.380061E+10 74487690.58 0.372612E+10 0.459238E+10 0.861678E+10
Minimum of Months 0.183765E+09 0.00 0.183765E+09 14452551.87 0.135967E+09
Maximum of Months 0.476617E+09 31467518.73 0.445149E+09 0.905293E+09 0.159192E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198780E+09 0.00 0.198780E+09 17677144.02 0.159185E+10
February 0.199007E+09 0.00 0.199007E+09 65427680.94 0.118523E+10
March 0.309330E+09 0.00 0.309330E+09 0.180271E+09 0.829142E+09
April 0.362093E+09 1605967.04 0.360487E+09 0.376340E+09 0.607854E+09
May 0.447493E+09 14281329.04 0.433212E+09 0.621465E+09 0.391468E+09
June 0.476599E+09 31466365.74 0.445132E+09 0.873803E+09 0.228817E+09
July 0.464661E+09 22587207.77 0.442074E+09 0.905258E+09 0.166340E+09
August 0.413240E+09 4501537.77 0.408738E+09 0.824700E+09 0.135961E+09
September 0.302294E+09 42553.96 0.302251E+09 0.448726E+09 0.328523E+09
October 0.237506E+09 0.00 0.237506E+09 0.188658E+09 0.755401E+09
November 0.205702E+09 0.00 0.205702E+09 75432555.91 0.102094E+10
December 0.183758E+09 0.00 0.183758E+09 14452083.07 0.137491E+10
           
Annual Sum or Average 0.380046E+10 74484961.31 0.372598E+10 0.459221E+10 0.861644E+10
Minimum of Months 0.183758E+09 0.00 0.183758E+09 14452083.07 0.135961E+09
Maximum of Months 0.476599E+09 31466365.74 0.445132E+09 0.905258E+09 0.159185E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.485078E+09 0.218795E+09 0.266283E+09 0.305954E+09 0.156797E+10
February 0.552351E+09 0.296774E+09 0.255577E+09 0.505664E+09 0.115886E+10
March 0.769377E+09 0.350243E+09 0.419134E+09 0.846811E+09 0.809113E+09
April 0.900364E+09 0.410543E+09 0.489821E+09 0.123975E+10 0.601593E+09
May 0.102162E+10 0.432029E+09 0.589593E+09 0.157581E+10 0.420168E+09
June 0.102360E+10 0.429017E+09 0.594585E+09 0.181532E+10 0.242157E+09
July 0.103132E+10 0.433583E+09 0.597740E+09 0.189826E+10 0.167384E+09
August 0.943319E+09 0.374248E+09 0.569071E+09 0.176927E+10 0.125920E+09
September 0.750271E+09 0.332425E+09 0.417845E+09 0.120649E+10 0.340069E+09
October 0.661379E+09 0.344132E+09 0.317248E+09 0.833336E+09 0.747486E+09
November 0.511721E+09 0.231705E+09 0.280016E+09 0.468724E+09 0.978974E+09
December 0.458024E+09 0.208785E+09 0.249239E+09 0.307680E+09 0.130866E+10
           
Annual Sum or Average 0.910843E+10 0.406228E+10 0.504615E+10 0.127731E+11 0.846835E+10
Minimum of Months 0.458024E+09 0.208785E+09 0.249239E+09 0.305954E+09 0.125920E+09
Maximum of Months 0.103132E+10 0.433583E+09 0.597740E+09 0.189826E+10 0.156797E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.485078E+09 0.218795E+09 0.266283E+09 0.305954E+09 0.156797E+10
February 0.552351E+09 0.296774E+09 0.255577E+09 0.505664E+09 0.115886E+10
March 0.769377E+09 0.350243E+09 0.419134E+09 0.846811E+09 0.809113E+09
April 0.900364E+09 0.410543E+09 0.489821E+09 0.123975E+10 0.601593E+09
May 0.102162E+10 0.432029E+09 0.589593E+09 0.157581E+10 0.420168E+09
June 0.102360E+10 0.429017E+09 0.594585E+09 0.181532E+10 0.242157E+09
July 0.103132E+10 0.433583E+09 0.597740E+09 0.189826E+10 0.167384E+09
August 0.943319E+09 0.374248E+09 0.569071E+09 0.176927E+10 0.125920E+09
September 0.750271E+09 0.332425E+09 0.417845E+09 0.120649E+10 0.340069E+09
October 0.661379E+09 0.344132E+09 0.317248E+09 0.833336E+09 0.747486E+09
November 0.511721E+09 0.231705E+09 0.280016E+09 0.468724E+09 0.978974E+09
December 0.458024E+09 0.208785E+09 0.249239E+09 0.307680E+09 0.130866E+10
           
Annual Sum or Average 0.910843E+10 0.406228E+10 0.504615E+10 0.127731E+11 0.846835E+10
Minimum of Months 0.458024E+09 0.208785E+09 0.249239E+09 0.305954E+09 0.125920E+09
Maximum of Months 0.103132E+10 0.433583E+09 0.597740E+09 0.189826E+10 0.156797E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.485069E+09 0.218791E+09 0.266279E+09 0.305949E+09 0.156794E+10
February 0.552341E+09 0.296769E+09 0.255572E+09 0.505655E+09 0.115884E+10
March 0.769363E+09 0.350237E+09 0.419127E+09 0.846796E+09 0.809098E+09
April 0.900347E+09 0.410535E+09 0.489812E+09 0.123973E+10 0.601582E+09
May 0.102160E+10 0.432021E+09 0.589582E+09 0.157578E+10 0.420161E+09
June 0.102358E+10 0.429009E+09 0.594575E+09 0.181529E+10 0.242152E+09
July 0.103130E+10 0.433575E+09 0.597729E+09 0.189822E+10 0.167381E+09
August 0.943302E+09 0.374241E+09 0.569060E+09 0.176923E+10 0.125917E+09
September 0.750257E+09 0.332419E+09 0.417838E+09 0.120646E+10 0.340062E+09
October 0.661367E+09 0.344126E+09 0.317242E+09 0.833321E+09 0.747473E+09
November 0.511712E+09 0.231701E+09 0.280011E+09 0.468716E+09 0.978956E+09
December 0.458016E+09 0.208781E+09 0.249234E+09 0.307674E+09 0.130864E+10
           
Annual Sum or Average 0.910827E+10 0.406221E+10 0.504606E+10 0.127728E+11 0.846820E+10
Minimum of Months 0.458016E+09 0.208781E+09 0.249234E+09 0.305949E+09 0.125917E+09
Maximum of Months 0.103130E+10 0.433575E+09 0.597729E+09 0.189822E+10 0.156794E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106314E+10 0.741215E+09 0.321924E+09 0.117424E+10 0.128177E+10
February 0.896239E+09 0.600772E+09 0.295467E+09 0.108550E+10 0.100556E+10
March 0.892383E+09 0.465055E+09 0.427328E+09 0.117986E+10 0.775423E+09
April 0.646778E+09 0.210538E+09 0.436239E+09 0.956995E+09 0.611443E+09
May 0.539991E+09 62760903.20 0.477230E+09 0.853517E+09 0.412308E+09
June 0.483173E+09 26886366.83 0.456287E+09 0.918363E+09 0.243749E+09
July 0.504761E+09 37637437.05 0.467123E+09 0.101053E+10 0.172127E+09
August 0.602647E+09 0.112576E+09 0.490071E+09 0.122651E+10 0.142841E+09
September 0.641382E+09 0.238559E+09 0.402823E+09 0.110405E+10 0.332920E+09
October 0.960813E+09 0.622414E+09 0.338400E+09 0.141322E+10 0.704841E+09
November 0.100032E+10 0.663792E+09 0.336525E+09 0.130387E+10 0.894506E+09
December 0.104796E+10 0.737246E+09 0.310714E+09 0.123372E+10 0.112589E+10
           
Annual Sum or Average 0.927958E+10 0.451945E+10 0.476013E+10 0.134604E+11 0.770338E+10
Minimum of Months 0.483173E+09 26886366.83 0.295467E+09 0.853517E+09 0.142841E+09
Maximum of Months 0.106314E+10 0.741215E+09 0.490071E+09 0.141322E+10 0.128177E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106313E+10 0.741209E+09 0.321922E+09 0.117423E+10 0.128177E+10
February 0.896233E+09 0.600768E+09 0.295465E+09 0.108549E+10 0.100556E+10
March 0.892377E+09 0.465052E+09 0.427325E+09 0.117985E+10 0.775423E+09
April 0.646774E+09 0.210537E+09 0.436237E+09 0.956988E+09 0.611443E+09
May 0.539988E+09 62760443.29 0.477227E+09 0.853513E+09 0.412307E+09
June 0.483171E+09 26886169.80 0.456284E+09 0.918360E+09 0.243748E+09
July 0.504758E+09 37637161.24 0.467121E+09 0.101052E+10 0.172126E+09
August 0.602644E+09 0.112575E+09 0.490069E+09 0.122650E+10 0.142840E+09
September 0.641378E+09 0.238558E+09 0.402821E+09 0.110405E+10 0.332919E+09
October 0.960807E+09 0.622409E+09 0.338398E+09 0.141321E+10 0.704840E+09
November 0.100031E+10 0.663787E+09 0.336523E+09 0.130385E+10 0.894506E+09
December 0.104795E+10 0.737241E+09 0.310712E+09 0.123371E+10 0.112589E+10
           
Annual Sum or Average 0.927952E+10 0.451942E+10 0.476010E+10 0.134603E+11 0.770338E+10
Minimum of Months 0.483171E+09 26886169.80 0.295465E+09 0.853513E+09 0.142840E+09
Maximum of Months 0.106313E+10 0.741209E+09 0.490069E+09 0.141321E+10 0.128177E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106314E+10 0.741215E+09 0.321924E+09 0.117424E+10 0.128177E+10
February 0.896239E+09 0.600772E+09 0.295467E+09 0.108550E+10 0.100556E+10
March 0.892383E+09 0.465055E+09 0.427328E+09 0.117986E+10 0.775423E+09
April 0.646778E+09 0.210538E+09 0.436239E+09 0.956995E+09 0.611443E+09
May 0.539991E+09 62760903.20 0.477230E+09 0.853517E+09 0.412308E+09
June 0.483173E+09 26886366.83 0.456287E+09 0.918363E+09 0.243749E+09
July 0.504761E+09 37637437.05 0.467123E+09 0.101053E+10 0.172127E+09
August 0.602647E+09 0.112576E+09 0.490071E+09 0.122651E+10 0.142841E+09
September 0.641382E+09 0.238559E+09 0.402823E+09 0.110405E+10 0.332920E+09
October 0.960813E+09 0.622414E+09 0.338400E+09 0.141322E+10 0.704841E+09
November 0.100032E+10 0.663792E+09 0.336525E+09 0.130387E+10 0.894506E+09
December 0.104796E+10 0.737246E+09 0.310714E+09 0.123372E+10 0.112589E+10
           
Annual Sum or Average 0.927958E+10 0.451945E+10 0.476013E+10 0.134604E+11 0.770338E+10
Minimum of Months 0.483173E+09 26886366.83 0.295467E+09 0.853517E+09 0.142841E+09
Maximum of Months 0.106314E+10 0.741215E+09 0.490071E+09 0.141322E+10 0.128177E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106313E+10 0.741209E+09 0.321922E+09 0.117423E+10 0.128177E+10
February 0.896233E+09 0.600768E+09 0.295465E+09 0.108549E+10 0.100556E+10
March 0.892377E+09 0.465052E+09 0.427325E+09 0.117985E+10 0.775423E+09
April 0.646774E+09 0.210537E+09 0.436237E+09 0.956988E+09 0.611443E+09
May 0.539988E+09 62760443.29 0.477227E+09 0.853513E+09 0.412307E+09
June 0.483171E+09 26886169.80 0.456284E+09 0.918360E+09 0.243748E+09
July 0.504758E+09 37637161.24 0.467121E+09 0.101052E+10 0.172126E+09
August 0.602644E+09 0.112575E+09 0.490069E+09 0.122650E+10 0.142840E+09
September 0.641378E+09 0.238558E+09 0.402821E+09 0.110405E+10 0.332919E+09
October 0.960807E+09 0.622409E+09 0.338398E+09 0.141321E+10 0.704840E+09
November 0.100031E+10 0.663787E+09 0.336523E+09 0.130385E+10 0.894506E+09
December 0.104795E+10 0.737241E+09 0.310712E+09 0.123371E+10 0.112589E+10
           
Annual Sum or Average 0.927952E+10 0.451942E+10 0.476010E+10 0.134603E+11 0.770338E+10
Minimum of Months 0.483171E+09 26886169.80 0.295465E+09 0.853513E+09 0.142840E+09
Maximum of Months 0.106313E+10 0.741209E+09 0.490069E+09 0.141321E+10 0.128177E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106309E+10 0.741182E+09 0.321910E+09 0.117419E+10 0.128172E+10
February 0.896200E+09 0.600746E+09 0.295454E+09 0.108545E+10 0.100552E+10
March 0.892344E+09 0.465035E+09 0.427309E+09 0.117980E+10 0.775392E+09
April 0.646750E+09 0.210529E+09 0.436221E+09 0.956953E+09 0.611419E+09
May 0.539967E+09 62758143.71 0.477209E+09 0.853480E+09 0.412291E+09
June 0.483152E+09 26885184.68 0.456267E+09 0.918324E+09 0.243738E+09
July 0.504739E+09 37635782.20 0.467103E+09 0.101049E+10 0.172120E+09
August 0.602621E+09 0.112571E+09 0.490050E+09 0.122646E+10 0.142835E+09
September 0.641354E+09 0.238549E+09 0.402805E+09 0.110400E+10 0.332906E+09
October 0.960772E+09 0.622387E+09 0.338385E+09 0.141316E+10 0.704812E+09
November 0.100027E+10 0.663763E+09 0.336510E+09 0.130381E+10 0.894470E+09
December 0.104791E+10 0.737214E+09 0.310700E+09 0.123366E+10 0.112584E+10
           
Annual Sum or Average 0.927918E+10 0.451925E+10 0.475992E+10 0.134598E+11 0.770307E+10
Minimum of Months 0.483152E+09 26885184.68 0.295454E+09 0.853480E+09 0.142835E+09
Maximum of Months 0.106309E+10 0.741182E+09 0.490050E+09 0.141316E+10 0.128172E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.498243E+09 0.231120E+09 0.267123E+09 0.353235E+09 0.170179E+10
February 0.516627E+09 0.241554E+09 0.275072E+09 0.485994E+09 0.133636E+10
March 0.843065E+09 0.407388E+09 0.435677E+09 0.986309E+09 0.100826E+10
April 0.917838E+09 0.419999E+09 0.497839E+09 0.125109E+10 0.781560E+09
May 0.953203E+09 0.361131E+09 0.592072E+09 0.147770E+10 0.503903E+09
June 0.970082E+09 0.373186E+09 0.596896E+09 0.170641E+10 0.321118E+09
July 0.945509E+09 0.350563E+09 0.594946E+09 0.171381E+10 0.246892E+09
August 0.926464E+09 0.346461E+09 0.580003E+09 0.168772E+10 0.227843E+09
September 0.730466E+09 0.304271E+09 0.426195E+09 0.116381E+10 0.408710E+09
October 0.672451E+09 0.349076E+09 0.323375E+09 0.880835E+09 0.912398E+09
November 0.519353E+09 0.233112E+09 0.286240E+09 0.524603E+09 0.121244E+10
December 0.442744E+09 0.193657E+09 0.249087E+09 0.322191E+09 0.161738E+10
           
Annual Sum or Average 0.893604E+10 0.381152E+10 0.512453E+10 0.125537E+11 0.102787E+11
Minimum of Months 0.442744E+09 0.193657E+09 0.249087E+09 0.322191E+09 0.227843E+09
Maximum of Months 0.970082E+09 0.419999E+09 0.596896E+09 0.171381E+10 0.170179E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.498243E+09 0.231120E+09 0.267123E+09 0.353235E+09 0.170179E+10
February 0.516627E+09 0.241554E+09 0.275072E+09 0.485994E+09 0.133636E+10
March 0.843065E+09 0.407388E+09 0.435677E+09 0.986309E+09 0.100826E+10
April 0.917838E+09 0.419999E+09 0.497839E+09 0.125109E+10 0.781560E+09
May 0.953203E+09 0.361131E+09 0.592072E+09 0.147770E+10 0.503903E+09
June 0.970082E+09 0.373186E+09 0.596896E+09 0.170641E+10 0.321118E+09
July 0.945509E+09 0.350563E+09 0.594946E+09 0.171381E+10 0.246892E+09
August 0.926464E+09 0.346461E+09 0.580003E+09 0.168772E+10 0.227843E+09
September 0.730466E+09 0.304271E+09 0.426195E+09 0.116381E+10 0.408710E+09
October 0.672451E+09 0.349076E+09 0.323375E+09 0.880835E+09 0.912398E+09
November 0.519353E+09 0.233112E+09 0.286240E+09 0.524603E+09 0.121244E+10
December 0.442744E+09 0.193657E+09 0.249087E+09 0.322191E+09 0.161738E+10
           
Annual Sum or Average 0.893604E+10 0.381152E+10 0.512453E+10 0.125537E+11 0.102787E+11
Minimum of Months 0.442744E+09 0.193657E+09 0.249087E+09 0.322191E+09 0.227843E+09
Maximum of Months 0.970082E+09 0.419999E+09 0.596896E+09 0.171381E+10 0.170179E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.498234E+09 0.231116E+09 0.267118E+09 0.353228E+09 0.170176E+10
February 0.516617E+09 0.241550E+09 0.275067E+09 0.485985E+09 0.133634E+10
March 0.843049E+09 0.407380E+09 0.435669E+09 0.986291E+09 0.100824E+10
April 0.917821E+09 0.419991E+09 0.497830E+09 0.125107E+10 0.781546E+09
May 0.953186E+09 0.361124E+09 0.592061E+09 0.147767E+10 0.503894E+09
June 0.970064E+09 0.373179E+09 0.596885E+09 0.170638E+10 0.321112E+09
July 0.945492E+09 0.350556E+09 0.594936E+09 0.171378E+10 0.246888E+09
August 0.926447E+09 0.346455E+09 0.579993E+09 0.168769E+10 0.227839E+09
September 0.730453E+09 0.304266E+09 0.426187E+09 0.116379E+10 0.408702E+09
October 0.672438E+09 0.349069E+09 0.323369E+09 0.880818E+09 0.912381E+09
November 0.519343E+09 0.233108E+09 0.286235E+09 0.524594E+09 0.121242E+10
December 0.442736E+09 0.193653E+09 0.249083E+09 0.322185E+09 0.161735E+10
           
Annual Sum or Average 0.893588E+10 0.381145E+10 0.512443E+10 0.125535E+11 0.102785E+11
Minimum of Months 0.442736E+09 0.193653E+09 0.249083E+09 0.322185E+09 0.227839E+09
Maximum of Months 0.970064E+09 0.419991E+09 0.596885E+09 0.171378E+10 0.170176E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.993954E+09 0.00 0.993954E+09 0.132010E+09 0.707592E+10
February 0.995084E+09 0.00 0.995084E+09 0.407213E+09 0.525908E+10
March 0.154673E+10 0.00 0.154673E+10 0.101667E+10 0.371131E+10
April 0.181056E+10 8030357.15 0.180253E+10 0.197004E+10 0.283534E+10
May 0.223758E+10 71411286.64 0.216617E+10 0.313343E+10 0.188778E+10
June 0.238312E+10 0.157342E+09 0.222578E+10 0.439209E+10 0.114199E+10
July 0.232342E+10 0.112943E+09 0.221048E+10 0.455737E+10 0.842242E+09
August 0.206630E+10 22509151.83 0.204380E+10 0.416946E+10 0.694860E+09
September 0.151155E+10 212783.61 0.151133E+10 0.228133E+10 0.155418E+10
October 0.118759E+10 0.00 0.118759E+10 0.104177E+10 0.337748E+10
November 0.102856E+10 0.00 0.102856E+10 0.507155E+09 0.447478E+10
December 0.918837E+09 0.00 0.918837E+09 0.132250E+09 0.581729E+10
           
Annual Sum or Average 0.190033E+11 0.372449E+09 0.186308E+11 0.237408E+11 0.386723E+11
Minimum of Months 0.918837E+09 0.00 0.918837E+09 0.132010E+09 0.694860E+09
Maximum of Months 0.238312E+10 0.157342E+09 0.222578E+10 0.455737E+10 0.707592E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.145522E+10 0.656378E+09 0.798842E+09 0.985514E+09 0.423248E+10
February 0.165704E+10 0.890313E+09 0.766723E+09 0.157248E+10 0.316810E+10
March 0.230811E+10 0.105072E+10 0.125739E+10 0.257030E+10 0.227684E+10
April 0.270106E+10 0.123161E+10 0.146945E+10 0.370303E+10 0.178226E+10
May 0.306484E+10 0.129607E+10 0.176876E+10 0.469303E+10 0.124447E+10
June 0.307078E+10 0.128704E+10 0.178374E+10 0.540377E+10 0.767744E+09
July 0.309394E+10 0.130073E+10 0.179320E+10 0.564561E+10 0.564806E+09
August 0.282993E+10 0.112273E+10 0.170720E+10 0.526000E+10 0.464158E+09
September 0.225079E+10 0.997266E+09 0.125352E+10 0.360948E+10 0.994950E+09
October 0.198412E+10 0.103239E+10 0.951733E+09 0.252890E+10 0.208195E+10
November 0.153515E+10 0.695109E+09 0.840039E+09 0.149218E+10 0.267003E+10
December 0.137406E+10 0.626349E+09 0.747709E+09 0.100105E+10 0.346033E+10
           
Annual Sum or Average 0.273250E+11 0.121867E+11 0.151383E+11 0.384653E+11 0.237081E+11
Minimum of Months 0.137406E+10 0.626349E+09 0.747709E+09 0.985514E+09 0.464158E+09
Maximum of Months 0.309394E+10 0.130073E+10 0.179320E+10 0.564561E+10 0.423248E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.531579E+10 0.370615E+10 0.160964E+10 0.588953E+10 0.609888E+10
February 0.448128E+10 0.300392E+10 0.147735E+10 0.543398E+10 0.476984E+10
March 0.446199E+10 0.232533E+10 0.213666E+10 0.587301E+10 0.372179E+10
April 0.323393E+10 0.105271E+10 0.218122E+10 0.477846E+10 0.297198E+10
May 0.269998E+10 0.313811E+09 0.238617E+10 0.426100E+10 0.201637E+10
June 0.241589E+10 0.134435E+09 0.228145E+10 0.460800E+10 0.122079E+10
July 0.252383E+10 0.188191E+09 0.233564E+10 0.507507E+10 0.880345E+09
August 0.301327E+10 0.562890E+09 0.245038E+10 0.614598E+10 0.749294E+09
September 0.320696E+10 0.119282E+10 0.201414E+10 0.550093E+10 0.163301E+10
October 0.480415E+10 0.311213E+10 0.169202E+10 0.703049E+10 0.339332E+10
November 0.500168E+10 0.331903E+10 0.168265E+10 0.651930E+10 0.427100E+10
December 0.523990E+10 0.368631E+10 0.155359E+10 0.620586E+10 0.524180E+10
           
Annual Sum or Average 0.463986E+11 0.225977E+11 0.238009E+11 0.673216E+11 0.369684E+11
Minimum of Months 0.241589E+10 0.134435E+09 0.147735E+10 0.426100E+10 0.749294E+09
Maximum of Months 0.531579E+10 0.370615E+10 0.245038E+10 0.703049E+10 0.609888E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.149471E+10 0.693353E+09 0.801361E+09 0.114232E+10 0.450216E+10
February 0.154986E+10 0.724655E+09 0.825209E+09 0.155914E+10 0.343143E+10
March 0.252917E+10 0.122215E+10 0.130702E+10 0.308226E+10 0.254959E+10
April 0.275349E+10 0.125998E+10 0.149350E+10 0.388218E+10 0.202480E+10
May 0.285958E+10 0.108338E+10 0.177620E+10 0.446767E+10 0.140135E+10
June 0.291021E+10 0.111955E+10 0.179067E+10 0.517115E+10 0.886336E+09
July 0.283650E+10 0.105168E+10 0.178482E+10 0.523404E+10 0.650321E+09
August 0.277936E+10 0.103937E+10 0.173999E+10 0.517755E+10 0.565316E+09
September 0.219138E+10 0.912804E+09 0.127857E+10 0.353764E+10 0.110154E+10
October 0.201733E+10 0.104722E+10 0.970115E+09 0.273435E+10 0.233311E+10
November 0.155804E+10 0.699329E+09 0.858712E+09 0.172348E+10 0.300331E+10
December 0.132822E+10 0.580965E+09 0.747255E+09 0.110283E+10 0.381896E+10
           
Annual Sum or Average 0.268079E+11 0.114344E+11 0.153734E+11 0.388146E+11 0.262682E+11
Minimum of Months 0.132822E+10 0.580965E+09 0.747255E+09 0.110283E+10 0.565316E+09
Maximum of Months 0.291021E+10 0.125998E+10 0.179067E+10 0.523404E+10 0.450216E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.993954E+09 0.00 0.993954E+09 0.167648E+09 0.661158E+10
February 0.995084E+09 0.00 0.995084E+09 0.449825E+09 0.492124E+10
March 0.154673E+10 0.00 0.154673E+10 0.109930E+10 0.341367E+10
April 0.181056E+10 8030357.15 0.180253E+10 0.202084E+10 0.268615E+10
May 0.223758E+10 71411286.64 0.216617E+10 0.312401E+10 0.185036E+10
June 0.238312E+10 0.157342E+09 0.222578E+10 0.434456E+10 0.115531E+10
July 0.232342E+10 0.112943E+09 0.221048E+10 0.449804E+10 0.856812E+09
August 0.206630E+10 22509151.83 0.204380E+10 0.411133E+10 0.713067E+09
September 0.151155E+10 212783.61 0.151133E+10 0.228041E+10 0.149946E+10
October 0.118759E+10 0.00 0.118759E+10 0.110974E+10 0.309717E+10
November 0.102856E+10 0.00 0.102856E+10 0.608030E+09 0.405187E+10
December 0.918837E+09 0.00 0.918837E+09 0.174979E+09 0.526941E+10
           
Annual Sum or Average 0.190033E+11 0.372449E+09 0.186308E+11 0.239887E+11 0.361261E+11
Minimum of Months 0.918837E+09 0.00 0.918837E+09 0.167648E+09 0.713067E+09
Maximum of Months 0.238312E+10 0.157342E+09 0.222578E+10 0.449804E+10 0.661158E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.145522E+10 0.656378E+09 0.798842E+09 0.104319E+10 0.394561E+10
February 0.165704E+10 0.890313E+09 0.766723E+09 0.162164E+10 0.297274E+10
March 0.230811E+10 0.105072E+10 0.125739E+10 0.262754E+10 0.213653E+10
April 0.270106E+10 0.123161E+10 0.146945E+10 0.372112E+10 0.172193E+10
May 0.306484E+10 0.129607E+10 0.176876E+10 0.467022E+10 0.123932E+10
June 0.307078E+10 0.128704E+10 0.178374E+10 0.536137E+10 0.784697E+09
July 0.309394E+10 0.130073E+10 0.179320E+10 0.559493E+10 0.579127E+09
August 0.282993E+10 0.112273E+10 0.170720E+10 0.521140E+10 0.480559E+09
September 0.225079E+10 0.997266E+09 0.125352E+10 0.359527E+10 0.979416E+09
October 0.198412E+10 0.103239E+10 0.951733E+09 0.256837E+10 0.195523E+10
November 0.153515E+10 0.695109E+09 0.840039E+09 0.158121E+10 0.245362E+10
December 0.137406E+10 0.626349E+09 0.747709E+09 0.106722E+10 0.314157E+10
           
Annual Sum or Average 0.273250E+11 0.121867E+11 0.151383E+11 0.386635E+11 0.223903E+11
Minimum of Months 0.137406E+10 0.626349E+09 0.747709E+09 0.104319E+10 0.480559E+09
Maximum of Months 0.309394E+10 0.130073E+10 0.179320E+10 0.559493E+10 0.394561E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.531579E+10 0.370615E+10 0.160964E+10 0.604666E+10 0.563950E+10
February 0.448128E+10 0.300392E+10 0.147735E+10 0.552812E+10 0.445056E+10
March 0.446199E+10 0.232533E+10 0.213666E+10 0.594468E+10 0.348209E+10
April 0.323393E+10 0.105271E+10 0.218122E+10 0.480819E+10 0.284326E+10
May 0.269998E+10 0.313811E+09 0.238617E+10 0.424084E+10 0.198215E+10
June 0.241589E+10 0.134435E+09 0.228145E+10 0.455903E+10 0.123201E+10
July 0.252383E+10 0.188191E+09 0.233564E+10 0.501399E+10 0.893670E+09
August 0.301327E+10 0.562890E+09 0.245038E+10 0.608280E+10 0.770059E+09
September 0.320696E+10 0.119282E+10 0.201414E+10 0.548443E+10 0.159639E+10
October 0.480415E+10 0.311213E+10 0.169202E+10 0.707322E+10 0.318122E+10
November 0.500168E+10 0.331903E+10 0.168265E+10 0.664663E+10 0.392663E+10
December 0.523990E+10 0.368631E+10 0.155359E+10 0.636373E+10 0.474862E+10
           
Annual Sum or Average 0.463986E+11 0.225977E+11 0.238009E+11 0.677923E+11 0.347462E+11
Minimum of Months 0.241589E+10 0.134435E+09 0.147735E+10 0.424084E+10 0.770059E+09
Maximum of Months 0.531579E+10 0.370615E+10 0.245038E+10 0.707322E+10 0.563950E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.149471E+10 0.693353E+09 0.801361E+09 0.118463E+10 0.421038E+10
February 0.154986E+10 0.724655E+09 0.825209E+09 0.158494E+10 0.324018E+10
March 0.252917E+10 0.122215E+10 0.130702E+10 0.311421E+10 0.239690E+10
April 0.275349E+10 0.125998E+10 0.149350E+10 0.389657E+10 0.194879E+10
May 0.285958E+10 0.108338E+10 0.177620E+10 0.445265E+10 0.138278E+10
June 0.291021E+10 0.111955E+10 0.179067E+10 0.513372E+10 0.893773E+09
July 0.283650E+10 0.105168E+10 0.178482E+10 0.519421E+10 0.656873E+09
August 0.277936E+10 0.103937E+10 0.173999E+10 0.513784E+10 0.575260E+09
September 0.219138E+10 0.912804E+09 0.127857E+10 0.353031E+10 0.107632E+10
October 0.201733E+10 0.104722E+10 0.970115E+09 0.275829E+10 0.219400E+10
November 0.155804E+10 0.699329E+09 0.858712E+09 0.177663E+10 0.278433E+10
December 0.132822E+10 0.580965E+09 0.747255E+09 0.114277E+10 0.351497E+10
           
Annual Sum or Average 0.268079E+11 0.114344E+11 0.153734E+11 0.389068E+11 0.248746E+11
Minimum of Months 0.132822E+10 0.580965E+09 0.747255E+09 0.114277E+10 0.575260E+09
Maximum of Months 0.291021E+10 0.125998E+10 0.179067E+10 0.519421E+10 0.421038E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 33.00 2971.75 371.09 0.00 371.09 0.00 0.00
February 135.23 2449.72 411.32 0.00 411.32 0.00 0.00
March 336.54 1547.88 577.47 0.00 577.47 0.00 0.00
April 725.99 1172.60 698.51 3.10 695.41 0.00 0.00
May 1160.18 730.81 835.40 26.66 808.74 0.00 0.00
June 1685.63 441.41 919.40 60.70 858.70 0.00 0.00
July 1689.98 310.53 867.45 42.17 825.28 0.00 0.00
August 1539.59 253.82 771.46 8.40 763.05 0.00 0.00
September 865.63 633.75 583.15 0.08 583.07 0.00 0.00
October 352.20 1410.22 443.39 0.00 443.39 0.00 0.00
November 145.52 1969.46 396.82 0.00 396.82 0.00 0.00
December 26.98 2566.74 343.05 0.00 343.05 0.00 0.00
               
Annual Sum or Average 728.11 1366.17 602.58 11.81 590.77 0.00 0.00
Minimum of Months 26.98 253.82 343.05 0.00 343.05 0.00 0.00
Maximum of Months 1689.98 2971.75 919.40 60.70 858.70 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 342.69 1756.22 543.32 245.06 298.25 0.00 0.00
February 627.06 1437.07 684.95 368.02 316.93 0.00 0.00
March 948.48 906.26 861.75 392.29 469.46 0.00 0.00
April 1434.88 696.28 1042.08 475.16 566.92 0.00 0.00
May 1765.01 470.62 1144.28 483.90 660.38 0.00 0.00
June 2101.05 280.27 1184.72 496.54 688.17 0.00 0.00
July 2126.17 187.48 1155.15 485.64 669.51 0.00 0.00
August 1981.69 141.04 1056.58 419.18 637.40 0.00 0.00
September 1396.39 393.60 868.36 384.75 483.61 0.00 0.00
October 933.39 837.23 740.79 385.45 355.34 0.00 0.00
November 542.50 1133.06 592.27 268.18 324.09 0.00 0.00
December 344.62 1465.79 513.02 233.85 279.16 0.00 0.00
               
Annual Sum or Average 1215.09 805.58 866.47 386.44 480.03 0.00 0.00
Minimum of Months 342.69 141.04 513.02 233.85 279.16 0.00 0.00
Maximum of Months 2126.17 1756.22 1184.72 496.54 688.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2192.03 2392.77 1984.63 1383.67 600.96 0.00 0.00
February 2243.48 2078.28 1852.32 1241.66 610.66 0.00 0.00
March 2202.51 1447.54 1665.87 868.15 797.72 0.00 0.00
April 1846.03 1179.47 1247.63 406.13 841.50 0.00 0.00
May 1593.32 769.68 1008.04 117.16 890.88 0.00 0.00
June 1771.52 470.19 932.04 51.86 880.17 0.00 0.00
July 1886.42 321.32 942.27 70.26 872.01 0.00 0.00
August 2289.61 266.65 1125.00 210.15 914.85 0.00 0.00
September 2129.71 642.20 1237.22 460.18 777.04 0.00 0.00
October 2638.15 1315.78 1793.61 1161.90 631.71 0.00 0.00
November 2515.14 1725.50 1929.60 1280.45 649.15 0.00 0.00
December 2303.06 2101.78 1956.29 1376.26 580.03 0.00 0.00
               
Annual Sum or Average 2134.10 1221.35 1471.25 716.55 754.71 0.00 0.00
Minimum of Months 1593.32 266.65 932.04 51.86 580.03 0.00 0.00
Maximum of Months 2638.15 2392.77 1984.63 1383.67 914.85 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 395.65 1906.11 558.06 258.87 299.19 0.00 0.00
February 602.67 1657.18 640.65 299.54 341.11 0.00 0.00
March 1104.73 1129.32 944.29 456.30 487.99 0.00 0.00
April 1448.01 904.58 1062.31 486.11 576.20 0.00 0.00
May 1655.12 564.40 1067.65 404.49 663.16 0.00 0.00
June 1975.00 371.66 1122.77 431.93 690.85 0.00 0.00
July 1919.58 276.54 1059.03 392.65 666.38 0.00 0.00
August 1890.36 255.20 1037.70 388.06 649.64 0.00 0.00
September 1346.99 473.04 845.44 352.16 493.28 0.00 0.00
October 986.59 1021.94 753.19 390.99 362.20 0.00 0.00
November 607.18 1403.28 601.10 269.80 331.29 0.00 0.00
December 360.87 1811.58 495.90 216.91 278.99 0.00 0.00
               
Annual Sum or Average 1194.22 977.80 850.08 362.59 487.49 0.00 0.00
Minimum of Months 360.87 255.20 495.90 216.91 278.99 0.00 0.00
Maximum of Months 1975.00 1906.11 1122.77 486.11 690.85 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 49.29 2641.84 371.10 0.00 371.10 0.00 0.00
February 168.33 2173.89 411.33 0.00 411.33 0.00 0.00
March 379.58 1385.65 577.48 0.00 577.48 0.00 0.00
April 760.05 1093.88 698.52 3.10 695.42 0.00 0.00
May 1169.89 704.82 835.42 26.66 808.75 0.00 0.00
June 1694.48 440.58 919.41 60.70 858.71 0.00 0.00
July 1701.53 314.46 867.47 42.17 825.30 0.00 0.00
August 1556.70 259.43 771.47 8.40 763.07 0.00 0.00
September 880.14 599.61 583.16 0.08 583.08 0.00 0.00
October 388.95 1261.01 443.39 0.00 443.39 0.00 0.00
November 195.66 1726.38 396.82 0.00 396.82 0.00 0.00
December 49.38 2171.93 343.05 0.00 343.05 0.00 0.00
               
Annual Sum or Average 752.82 1226.29 602.59 11.81 590.78 0.00 0.00
Minimum of Months 49.29 259.43 343.05 0.00 343.05 0.00 0.00
Maximum of Months 1701.53 2641.84 919.41 60.70 858.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 367.95 1580.23 543.32 245.06 298.25 0.00 0.00
February 650.00 1309.56 684.95 368.02 316.93 0.00 0.00
March 959.64 850.08 861.75 392.29 469.46 0.00 0.00
April 1428.64 687.60 1042.08 475.16 566.92 0.00 0.00
May 1752.18 464.63 1144.28 483.90 660.38 0.00 0.00
June 2084.79 296.20 1184.71 496.54 688.17 0.00 0.00
July 2107.83 210.87 1155.14 485.64 669.50 0.00 0.00
August 1963.86 173.30 1056.57 419.18 637.39 0.00 0.00
September 1392.54 383.85 868.36 384.75 483.61 0.00 0.00
October 944.18 777.31 740.78 385.45 355.34 0.00 0.00
November 575.69 1030.10 592.26 268.17 324.09 0.00 0.00
December 373.75 1291.94 513.01 233.85 279.16 0.00 0.00
               
Annual Sum or Average 1219.73 751.78 866.47 386.44 480.03 0.00 0.00
Minimum of Months 367.95 173.30 513.01 233.85 279.16 0.00 0.00
Maximum of Months 2107.83 1580.23 1184.71 496.54 688.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2198.90 2277.06 1984.69 1383.72 600.97 0.00 0.00
February 2246.19 1971.66 1852.38 1241.70 610.68 0.00 0.00
March 2192.73 1389.56 1665.92 868.18 797.74 0.00 0.00
April 1843.54 1146.60 1247.66 406.14 841.52 0.00 0.00
May 1590.88 752.83 1008.06 117.16 890.89 0.00 0.00
June 1777.78 470.98 932.06 51.87 880.19 0.00 0.00
July 1894.82 328.68 942.29 70.26 872.03 0.00 0.00
August 2294.65 279.75 1125.03 210.16 914.87 0.00 0.00
September 2122.27 630.02 1237.25 460.19 777.06 0.00 0.00
October 2624.88 1266.92 1793.66 1161.94 631.73 0.00 0.00
November 2515.16 1647.76 1929.66 1280.49 649.17 0.00 0.00
December 2317.00 1957.06 1956.35 1376.31 580.04 0.00 0.00
               
Annual Sum or Average 2134.75 1172.26 1471.29 716.57 754.72 0.00 0.00
Minimum of Months 1590.88 279.75 932.06 51.87 580.04 0.00 0.00
Maximum of Months 2624.88 2277.06 1984.69 1383.72 914.87 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 426.49 1680.91 558.06 258.87 299.19 0.00 0.00
February 644.49 1418.42 640.65 299.54 341.11 0.00 0.00
March 1150.78 951.91 944.28 456.30 487.98 0.00 0.00
April 1497.76 781.17 1062.30 486.10 576.20 0.00 0.00
May 1668.04 523.20 1067.64 404.49 663.16 0.00 0.00
June 1995.04 341.95 1122.77 431.92 690.84 0.00 0.00
July 1954.17 242.80 1059.03 392.65 666.38 0.00 0.00
August 1933.07 211.06 1037.70 388.06 649.64 0.00 0.00
September 1364.83 424.98 845.44 352.16 493.28 0.00 0.00
October 1020.89 871.08 753.19 390.99 362.20 0.00 0.00
November 664.92 1158.68 601.10 269.80 331.29 0.00 0.00
December 411.75 1425.84 495.90 216.91 278.99 0.00 0.00
               
Annual Sum or Average 1230.80 832.96 850.07 362.58 487.49 0.00 0.00
Minimum of Months 411.75 211.06 495.90 216.91 278.99 0.00 0.00
Maximum of Months 1995.04 1680.91 1122.77 486.10 690.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 62.59 2468.48 371.10 0.00 371.10 0.00 0.00
February 185.94 2034.24 411.33 0.00 411.33 0.00 0.00
March 410.43 1274.52 577.48 0.00 577.48 0.00 0.00
April 779.65 1036.32 698.52 3.10 695.42 0.00 0.00
May 1166.37 690.85 835.42 26.66 808.75 0.00 0.00
June 1676.14 445.72 919.41 60.70 858.71 0.00 0.00
July 1679.37 319.90 867.47 42.17 825.30 0.00 0.00
August 1534.99 266.23 771.47 8.40 763.07 0.00 0.00
September 879.79 578.50 583.16 0.08 583.08 0.00 0.00
October 414.33 1156.35 443.39 0.00 443.39 0.00 0.00
November 234.58 1563.22 396.82 0.00 396.82 0.00 0.00
December 65.33 1967.37 343.05 0.00 343.05 0.00 0.00
               
Annual Sum or Average 760.68 1145.55 602.59 11.81 590.78 0.00 0.00
Minimum of Months 62.59 266.23 343.05 0.00 343.05 0.00 0.00
Maximum of Months 1679.37 2468.48 919.41 60.70 858.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 389.48 1473.12 543.32 245.06 298.25 0.00 0.00
February 670.32 1228.81 684.95 368.02 316.93 0.00 0.00
March 981.01 797.69 861.75 392.29 469.46 0.00 0.00
April 1435.62 664.33 1042.08 475.16 566.92 0.00 0.00
May 1743.66 462.71 1144.28 483.90 660.38 0.00 0.00
June 2068.43 302.74 1184.71 496.54 688.17 0.00 0.00
July 2088.91 216.22 1155.14 485.64 669.50 0.00 0.00
August 1945.71 179.42 1056.57 419.18 637.39 0.00 0.00
September 1387.06 377.86 868.36 384.75 483.61 0.00 0.00
October 958.92 730.00 740.78 385.45 355.34 0.00 0.00
November 610.04 946.61 592.26 268.17 324.09 0.00 0.00
December 398.45 1172.93 513.01 233.85 279.16 0.00 0.00
               
Annual Sum or Average 1226.01 709.99 866.47 386.44 480.03 0.00 0.00
Minimum of Months 389.48 179.42 513.01 233.85 279.16 0.00 0.00
Maximum of Months 2088.91 1473.12 1184.71 496.54 688.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2257.56 2105.55 1984.69 1383.72 600.97 0.00 0.00
February 2285.10 1839.68 1852.38 1241.70 610.68 0.00 0.00
March 2219.49 1300.06 1665.92 868.18 797.74 0.00 0.00
April 1855.01 1096.94 1247.66 406.14 841.52 0.00 0.00
May 1583.35 740.05 1008.06 117.16 890.89 0.00 0.00
June 1758.89 475.31 932.06 51.87 880.19 0.00 0.00
July 1872.01 333.66 942.29 70.26 872.03 0.00 0.00
August 2271.06 287.51 1125.03 210.16 914.87 0.00 0.00
September 2115.91 615.89 1237.25 460.19 777.06 0.00 0.00
October 2640.84 1187.73 1793.66 1161.94 631.73 0.00 0.00
November 2564.29 1514.90 1929.66 1280.49 649.17 0.00 0.00
December 2375.94 1772.93 1956.35 1376.31 580.04 0.00 0.00
               
Annual Sum or Average 2149.68 1101.79 1471.29 716.57 754.72 0.00 0.00
Minimum of Months 1583.35 287.51 932.06 51.87 580.04 0.00 0.00
Maximum of Months 2640.84 2105.55 1984.69 1383.72 914.87 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 442.29 1571.98 558.06 258.87 299.19 0.00 0.00
February 655.15 1339.36 640.65 299.54 341.11 0.00 0.00
March 1162.71 894.90 944.28 456.30 487.98 0.00 0.00
April 1503.30 751.85 1062.30 486.10 576.20 0.00 0.00
May 1662.43 516.27 1067.64 404.49 663.16 0.00 0.00
June 1980.60 344.82 1122.77 431.92 690.84 0.00 0.00
July 1939.30 245.25 1059.03 392.65 666.38 0.00 0.00
August 1918.25 214.78 1037.70 388.06 649.64 0.00 0.00
September 1362.00 415.25 845.44 352.16 493.28 0.00 0.00
October 1029.83 819.15 753.19 390.99 362.20 0.00 0.00
November 685.43 1074.20 601.10 269.80 331.29 0.00 0.00
December 426.66 1312.34 495.90 216.91 278.99 0.00 0.00
               
Annual Sum or Average 1233.73 788.77 850.07 362.58 487.49 0.00 0.00
Minimum of Months 426.66 214.78 495.90 216.91 278.99 0.00 0.00
Maximum of Months 1980.60 1571.98 1122.77 486.10 690.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 88389023.41 0.795953E+10 0.993936E+09 0.00 0.993936E+09 0.00 0.00
February 0.327150E+09 0.592636E+10 0.995068E+09 0.00 0.995068E+09 0.00 0.00
March 0.901385E+09 0.414585E+10 0.154670E+10 0.00 0.154670E+10 0.00 0.00
April 0.188176E+10 0.303937E+10 0.181053E+10 8030117.67 0.180250E+10 0.00 0.00
May 0.310743E+10 0.195740E+10 0.223754E+10 71409157.01 0.216613E+10 0.00 0.00
June 0.436916E+10 0.114412E+10 0.238307E+10 0.157337E+09 0.222574E+10 0.00 0.00
July 0.452644E+10 0.831730E+09 0.232338E+10 0.112940E+09 0.221044E+10 0.00 0.00
August 0.412364E+10 0.679830E+09 0.206627E+10 22508480.56 0.204376E+10 0.00 0.00
September 0.224370E+10 0.164267E+10 0.151152E+10 212777.26 0.151131E+10 0.00 0.00
October 0.943325E+09 0.377713E+10 0.118757E+10 0.00 0.118757E+10 0.00 0.00
November 0.377176E+09 0.510485E+10 0.102854E+10 0.00 0.102854E+10 0.00 0.00
December 72263200.22 0.687475E+10 0.918820E+09 0.00 0.918820E+09 0.00 0.00
               
Annual Sum or Average 0.229618E+11 0.430836E+11 0.190030E+11 0.372438E+09 0.186305E+11 0.00 0.00
Minimum of Months 72263200.22 0.679830E+09 0.918820E+09 0.00 0.918820E+09 0.00 0.00
Maximum of Months 0.452644E+10 0.795953E+10 0.238307E+10 0.157337E+09 0.222574E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.917857E+09 0.470387E+10 0.145523E+10 0.656381E+09 0.798846E+09 0.00 0.00
February 0.151698E+10 0.347656E+10 0.165704E+10 0.890317E+09 0.766726E+09 0.00 0.00
March 0.254042E+10 0.242732E+10 0.230812E+10 0.105072E+10 0.125740E+10 0.00 0.00
April 0.371922E+10 0.180477E+10 0.270108E+10 0.123162E+10 0.146946E+10 0.00 0.00
May 0.472739E+10 0.126050E+10 0.306485E+10 0.129608E+10 0.176877E+10 0.00 0.00
June 0.544593E+10 0.726465E+09 0.307079E+10 0.128704E+10 0.178375E+10 0.00 0.00
July 0.569474E+10 0.502149E+09 0.309395E+10 0.130074E+10 0.179321E+10 0.00 0.00
August 0.530777E+10 0.377757E+09 0.282994E+10 0.112274E+10 0.170720E+10 0.00 0.00
September 0.361943E+10 0.102020E+10 0.225080E+10 0.997270E+09 0.125353E+10 0.00 0.00
October 0.249999E+10 0.224244E+10 0.198413E+10 0.103239E+10 0.951737E+09 0.00 0.00
November 0.140616E+10 0.293690E+10 0.153515E+10 0.695112E+09 0.840042E+09 0.00 0.00
December 0.923034E+09 0.392597E+10 0.137406E+10 0.626351E+09 0.747712E+09 0.00 0.00
               
Annual Sum or Average 0.383189E+11 0.254049E+11 0.273251E+11 0.121868E+11 0.151384E+11 0.00 0.00
Minimum of Months 0.917857E+09 0.377757E+09 0.137406E+10 0.626351E+09 0.747712E+09 0.00 0.00
Maximum of Months 0.569474E+10 0.470387E+10 0.309395E+10 0.130074E+10 0.179321E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.587112E+10 0.640880E+10 0.531563E+10 0.370603E+10 0.160960E+10 0.00 0.00
February 0.542743E+10 0.502778E+10 0.448114E+10 0.300382E+10 0.147732E+10 0.00 0.00
March 0.589921E+10 0.387708E+10 0.446186E+10 0.232525E+10 0.213662E+10 0.00 0.00
April 0.478492E+10 0.305719E+10 0.323385E+10 0.105268E+10 0.218117E+10 0.00 0.00
May 0.426754E+10 0.206152E+10 0.269992E+10 0.313801E+09 0.238612E+10 0.00 0.00
June 0.459177E+10 0.121873E+10 0.241584E+10 0.134430E+09 0.228141E+10 0.00 0.00
July 0.505259E+10 0.860626E+09 0.252378E+10 0.188185E+09 0.233559E+10 0.00 0.00
August 0.613249E+10 0.714197E+09 0.301320E+10 0.562872E+09 0.245033E+10 0.00 0.00
September 0.552020E+10 0.166458E+10 0.320688E+10 0.119278E+10 0.201409E+10 0.00 0.00
October 0.706602E+10 0.352417E+10 0.480401E+10 0.311203E+10 0.169198E+10 0.00 0.00
November 0.651925E+10 0.447249E+10 0.500153E+10 0.331892E+10 0.168261E+10 0.00 0.00
December 0.616851E+10 0.562940E+10 0.523974E+10 0.368619E+10 0.155355E+10 0.00 0.00
               
Annual Sum or Average 0.673011E+11 0.385166E+11 0.463974E+11 0.225970E+11 0.238004E+11 0.00 0.00
Minimum of Months 0.426754E+10 0.714197E+09 0.241584E+10 0.134430E+09 0.147732E+10 0.00 0.00
Maximum of Months 0.706602E+10 0.640880E+10 0.531563E+10 0.370603E+10 0.245033E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.105970E+10 0.510533E+10 0.149472E+10 0.693356E+09 0.801364E+09 0.00 0.00
February 0.145797E+10 0.400906E+10 0.154987E+10 0.724658E+09 0.825212E+09 0.00 0.00
March 0.295891E+10 0.302477E+10 0.252918E+10 0.122216E+10 0.130702E+10 0.00 0.00
April 0.375324E+10 0.234467E+10 0.275350E+10 0.125999E+10 0.149351E+10 0.00 0.00
May 0.443307E+10 0.151170E+10 0.285959E+10 0.108339E+10 0.177621E+10 0.00 0.00
June 0.511920E+10 0.963348E+09 0.291023E+10 0.111955E+10 0.179068E+10 0.00 0.00
July 0.514141E+10 0.740672E+09 0.283651E+10 0.105168E+10 0.178483E+10 0.00 0.00
August 0.506313E+10 0.683526E+09 0.277938E+10 0.103938E+10 0.174000E+10 0.00 0.00
September 0.349141E+10 0.122612E+10 0.219139E+10 0.912808E+09 0.127858E+10 0.00 0.00
October 0.264249E+10 0.273718E+10 0.201734E+10 0.104722E+10 0.970119E+09 0.00 0.00
November 0.157380E+10 0.363731E+10 0.155805E+10 0.699332E+09 0.858716E+09 0.00 0.00
December 0.966566E+09 0.485212E+10 0.132823E+10 0.580967E+09 0.747258E+09 0.00 0.00
               
Annual Sum or Average 0.376609E+11 0.308358E+11 0.268080E+11 0.114345E+11 0.153735E+11 0.00 0.00
Minimum of Months 0.966566E+09 0.683526E+09 0.132823E+10 0.580967E+09 0.747258E+09 0.00 0.00
Maximum of Months 0.514141E+10 0.510533E+10 0.291023E+10 0.125999E+10 0.179068E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.132010E+09 0.707592E+10 0.993954E+09 0.00 0.993954E+09 0.00 0.00
February 0.407213E+09 0.525908E+10 0.995084E+09 0.00 0.995084E+09 0.00 0.00
March 0.101667E+10 0.371131E+10 0.154673E+10 0.00 0.154673E+10 0.00 0.00
April 0.197004E+10 0.283534E+10 0.181056E+10 8030357.15 0.180253E+10 0.00 0.00
May 0.313343E+10 0.188778E+10 0.223758E+10 71411286.64 0.216617E+10 0.00 0.00
June 0.439209E+10 0.114199E+10 0.238312E+10 0.157342E+09 0.222578E+10 0.00 0.00
July 0.455737E+10 0.842242E+09 0.232342E+10 0.112943E+09 0.221048E+10 0.00 0.00
August 0.416946E+10 0.694860E+09 0.206630E+10 22509151.83 0.204380E+10 0.00 0.00
September 0.228133E+10 0.155418E+10 0.151155E+10 212783.61 0.151133E+10 0.00 0.00
October 0.104177E+10 0.337748E+10 0.118759E+10 0.00 0.118759E+10 0.00 0.00
November 0.507155E+09 0.447478E+10 0.102856E+10 0.00 0.102856E+10 0.00 0.00
December 0.132250E+09 0.581729E+10 0.918837E+09 0.00 0.918837E+09 0.00 0.00
               
Annual Sum or Average 0.237408E+11 0.386723E+11 0.190033E+11 0.372449E+09 0.186308E+11 0.00 0.00
Minimum of Months 0.132010E+09 0.694860E+09 0.918837E+09 0.00 0.918837E+09 0.00 0.00
Maximum of Months 0.455737E+10 0.707592E+10 0.238312E+10 0.157342E+09 0.222578E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.985514E+09 0.423248E+10 0.145522E+10 0.656378E+09 0.798842E+09 0.00 0.00
February 0.157248E+10 0.316810E+10 0.165704E+10 0.890313E+09 0.766723E+09 0.00 0.00
March 0.257030E+10 0.227684E+10 0.230811E+10 0.105072E+10 0.125739E+10 0.00 0.00
April 0.370303E+10 0.178226E+10 0.270106E+10 0.123161E+10 0.146945E+10 0.00 0.00
May 0.469303E+10 0.124447E+10 0.306484E+10 0.129607E+10 0.176876E+10 0.00 0.00
June 0.540377E+10 0.767744E+09 0.307078E+10 0.128704E+10 0.178374E+10 0.00 0.00
July 0.564561E+10 0.564806E+09 0.309394E+10 0.130073E+10 0.179320E+10 0.00 0.00
August 0.526000E+10 0.464158E+09 0.282993E+10 0.112273E+10 0.170720E+10 0.00 0.00
September 0.360948E+10 0.994950E+09 0.225079E+10 0.997266E+09 0.125352E+10 0.00 0.00
October 0.252890E+10 0.208195E+10 0.198412E+10 0.103239E+10 0.951733E+09 0.00 0.00
November 0.149218E+10 0.267003E+10 0.153515E+10 0.695109E+09 0.840039E+09 0.00 0.00
December 0.100105E+10 0.346033E+10 0.137406E+10 0.626349E+09 0.747709E+09 0.00 0.00
               
Annual Sum or Average 0.384653E+11 0.237081E+11 0.273250E+11 0.121867E+11 0.151383E+11 0.00 0.00
Minimum of Months 0.985514E+09 0.464158E+09 0.137406E+10 0.626349E+09 0.747709E+09 0.00 0.00
Maximum of Months 0.564561E+10 0.423248E+10 0.309394E+10 0.130073E+10 0.179320E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.588953E+10 0.609888E+10 0.531579E+10 0.370615E+10 0.160964E+10 0.00 0.00
February 0.543398E+10 0.476984E+10 0.448128E+10 0.300392E+10 0.147735E+10 0.00 0.00
March 0.587301E+10 0.372179E+10 0.446199E+10 0.232533E+10 0.213666E+10 0.00 0.00
April 0.477846E+10 0.297198E+10 0.323393E+10 0.105271E+10 0.218122E+10 0.00 0.00
May 0.426100E+10 0.201637E+10 0.269998E+10 0.313811E+09 0.238617E+10 0.00 0.00
June 0.460800E+10 0.122079E+10 0.241589E+10 0.134435E+09 0.228145E+10 0.00 0.00
July 0.507507E+10 0.880345E+09 0.252383E+10 0.188191E+09 0.233564E+10 0.00 0.00
August 0.614598E+10 0.749294E+09 0.301327E+10 0.562890E+09 0.245038E+10 0.00 0.00
September 0.550093E+10 0.163301E+10 0.320696E+10 0.119282E+10 0.201414E+10 0.00 0.00
October 0.703049E+10 0.339332E+10 0.480415E+10 0.311213E+10 0.169202E+10 0.00 0.00
November 0.651930E+10 0.427100E+10 0.500168E+10 0.331903E+10 0.168265E+10 0.00 0.00
December 0.620586E+10 0.524180E+10 0.523990E+10 0.368631E+10 0.155359E+10 0.00 0.00
               
Annual Sum or Average 0.673216E+11 0.369684E+11 0.463986E+11 0.225977E+11 0.238009E+11 0.00 0.00
Minimum of Months 0.426100E+10 0.749294E+09 0.241589E+10 0.134435E+09 0.147735E+10 0.00 0.00
Maximum of Months 0.703049E+10 0.609888E+10 0.531579E+10 0.370615E+10 0.245038E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.114232E+10 0.450216E+10 0.149471E+10 0.693353E+09 0.801361E+09 0.00 0.00
February 0.155914E+10 0.343143E+10 0.154986E+10 0.724655E+09 0.825209E+09 0.00 0.00
March 0.308226E+10 0.254959E+10 0.252917E+10 0.122215E+10 0.130702E+10 0.00 0.00
April 0.388218E+10 0.202480E+10 0.275349E+10 0.125998E+10 0.149350E+10 0.00 0.00
May 0.446767E+10 0.140135E+10 0.285958E+10 0.108338E+10 0.177620E+10 0.00 0.00
June 0.517115E+10 0.886336E+09 0.291021E+10 0.111955E+10 0.179067E+10 0.00 0.00
July 0.523404E+10 0.650321E+09 0.283650E+10 0.105168E+10 0.178482E+10 0.00 0.00
August 0.517755E+10 0.565316E+09 0.277936E+10 0.103937E+10 0.173999E+10 0.00 0.00
September 0.353764E+10 0.110154E+10 0.219138E+10 0.912804E+09 0.127857E+10 0.00 0.00
October 0.273435E+10 0.233311E+10 0.201733E+10 0.104722E+10 0.970115E+09 0.00 0.00
November 0.172348E+10 0.300331E+10 0.155804E+10 0.699329E+09 0.858712E+09 0.00 0.00
December 0.110283E+10 0.381896E+10 0.132822E+10 0.580965E+09 0.747255E+09 0.00 0.00
               
Annual Sum or Average 0.388146E+11 0.262682E+11 0.268079E+11 0.114344E+11 0.153734E+11 0.00 0.00
Minimum of Months 0.110283E+10 0.565316E+09 0.132822E+10 0.580965E+09 0.747255E+09 0.00 0.00
Maximum of Months 0.523404E+10 0.450216E+10 0.291021E+10 0.125998E+10 0.179067E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.167648E+09 0.661158E+10 0.993954E+09 0.00 0.993954E+09 0.00 0.00
February 0.449825E+09 0.492124E+10 0.995084E+09 0.00 0.995084E+09 0.00 0.00
March 0.109930E+10 0.341367E+10 0.154673E+10 0.00 0.154673E+10 0.00 0.00
April 0.202084E+10 0.268615E+10 0.181056E+10 8030357.15 0.180253E+10 0.00 0.00
May 0.312401E+10 0.185036E+10 0.223758E+10 71411286.64 0.216617E+10 0.00 0.00
June 0.434456E+10 0.115531E+10 0.238312E+10 0.157342E+09 0.222578E+10 0.00 0.00
July 0.449804E+10 0.856812E+09 0.232342E+10 0.112943E+09 0.221048E+10 0.00 0.00
August 0.411133E+10 0.713067E+09 0.206630E+10 22509151.83 0.204380E+10 0.00 0.00
September 0.228041E+10 0.149946E+10 0.151155E+10 212783.61 0.151133E+10 0.00 0.00
October 0.110974E+10 0.309717E+10 0.118759E+10 0.00 0.118759E+10 0.00 0.00
November 0.608030E+09 0.405187E+10 0.102856E+10 0.00 0.102856E+10 0.00 0.00
December 0.174979E+09 0.526941E+10 0.918837E+09 0.00 0.918837E+09 0.00 0.00
               
Annual Sum or Average 0.239887E+11 0.361261E+11 0.190033E+11 0.372449E+09 0.186308E+11 0.00 0.00
Minimum of Months 0.167648E+09 0.713067E+09 0.918837E+09 0.00 0.918837E+09 0.00 0.00
Maximum of Months 0.449804E+10 0.661158E+10 0.238312E+10 0.157342E+09 0.222578E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.104319E+10 0.394561E+10 0.145522E+10 0.656378E+09 0.798842E+09 0.00 0.00
February 0.162164E+10 0.297274E+10 0.165704E+10 0.890313E+09 0.766723E+09 0.00 0.00
March 0.262754E+10 0.213653E+10 0.230811E+10 0.105072E+10 0.125739E+10 0.00 0.00
April 0.372112E+10 0.172193E+10 0.270106E+10 0.123161E+10 0.146945E+10 0.00 0.00
May 0.467022E+10 0.123932E+10 0.306484E+10 0.129607E+10 0.176876E+10 0.00 0.00
June 0.536137E+10 0.784697E+09 0.307078E+10 0.128704E+10 0.178374E+10 0.00 0.00
July 0.559493E+10 0.579127E+09 0.309394E+10 0.130073E+10 0.179320E+10 0.00 0.00
August 0.521140E+10 0.480559E+09 0.282993E+10 0.112273E+10 0.170720E+10 0.00 0.00
September 0.359527E+10 0.979416E+09 0.225079E+10 0.997266E+09 0.125352E+10 0.00 0.00
October 0.256837E+10 0.195523E+10 0.198412E+10 0.103239E+10 0.951733E+09 0.00 0.00
November 0.158121E+10 0.245362E+10 0.153515E+10 0.695109E+09 0.840039E+09 0.00 0.00
December 0.106722E+10 0.314157E+10 0.137406E+10 0.626349E+09 0.747709E+09 0.00 0.00
               
Annual Sum or Average 0.386635E+11 0.223903E+11 0.273250E+11 0.121867E+11 0.151383E+11 0.00 0.00
Minimum of Months 0.104319E+10 0.480559E+09 0.137406E+10 0.626349E+09 0.747709E+09 0.00 0.00
Maximum of Months 0.559493E+10 0.394561E+10 0.309394E+10 0.130073E+10 0.179320E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.604666E+10 0.563950E+10 0.531579E+10 0.370615E+10 0.160964E+10 0.00 0.00
February 0.552812E+10 0.445056E+10 0.448128E+10 0.300392E+10 0.147735E+10 0.00 0.00
March 0.594468E+10 0.348209E+10 0.446199E+10 0.232533E+10 0.213666E+10 0.00 0.00
April 0.480819E+10 0.284326E+10 0.323393E+10 0.105271E+10 0.218122E+10 0.00 0.00
May 0.424084E+10 0.198215E+10 0.269998E+10 0.313811E+09 0.238617E+10 0.00 0.00
June 0.455903E+10 0.123201E+10 0.241589E+10 0.134435E+09 0.228145E+10 0.00 0.00
July 0.501399E+10 0.893670E+09 0.252383E+10 0.188191E+09 0.233564E+10 0.00 0.00
August 0.608280E+10 0.770059E+09 0.301327E+10 0.562890E+09 0.245038E+10 0.00 0.00
September 0.548443E+10 0.159639E+10 0.320696E+10 0.119282E+10 0.201414E+10 0.00 0.00
October 0.707322E+10 0.318122E+10 0.480415E+10 0.311213E+10 0.169202E+10 0.00 0.00
November 0.664663E+10 0.392663E+10 0.500168E+10 0.331903E+10 0.168265E+10 0.00 0.00
December 0.636373E+10 0.474862E+10 0.523990E+10 0.368631E+10 0.155359E+10 0.00 0.00
               
Annual Sum or Average 0.677923E+11 0.347462E+11 0.463986E+11 0.225977E+11 0.238009E+11 0.00 0.00
Minimum of Months 0.424084E+10 0.770059E+09 0.241589E+10 0.134435E+09 0.147735E+10 0.00 0.00
Maximum of Months 0.707322E+10 0.563950E+10 0.531579E+10 0.370615E+10 0.245038E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.118463E+10 0.421038E+10 0.149471E+10 0.693353E+09 0.801361E+09 0.00 0.00
February 0.158494E+10 0.324018E+10 0.154986E+10 0.724655E+09 0.825209E+09 0.00 0.00
March 0.311421E+10 0.239690E+10 0.252917E+10 0.122215E+10 0.130702E+10 0.00 0.00
April 0.389657E+10 0.194879E+10 0.275349E+10 0.125998E+10 0.149350E+10 0.00 0.00
May 0.445265E+10 0.138278E+10 0.285958E+10 0.108338E+10 0.177620E+10 0.00 0.00
June 0.513372E+10 0.893773E+09 0.291021E+10 0.111955E+10 0.179067E+10 0.00 0.00
July 0.519421E+10 0.656873E+09 0.283650E+10 0.105168E+10 0.178482E+10 0.00 0.00
August 0.513784E+10 0.575260E+09 0.277936E+10 0.103937E+10 0.173999E+10 0.00 0.00
September 0.353031E+10 0.107632E+10 0.219138E+10 0.912804E+09 0.127857E+10 0.00 0.00
October 0.275829E+10 0.219400E+10 0.201733E+10 0.104722E+10 0.970115E+09 0.00 0.00
November 0.177663E+10 0.278433E+10 0.155804E+10 0.699329E+09 0.858712E+09 0.00 0.00
December 0.114277E+10 0.351497E+10 0.132822E+10 0.580965E+09 0.747255E+09 0.00 0.00
               
Annual Sum or Average 0.389068E+11 0.248746E+11 0.268079E+11 0.114344E+11 0.153734E+11 0.00 0.00
Minimum of Months 0.114277E+10 0.575260E+09 0.132822E+10 0.580965E+09 0.747255E+09 0.00 0.00
Maximum of Months 0.519421E+10 0.421038E+10 0.291021E+10 0.125998E+10 0.179067E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 3.96 1.39 -3.0 4.56 -7.8 48.74 150.20 0.00
February 7.94 4.18 -1.3 5.19 -4.0 51.84 169.20 0.00
March 13.76 8.97 3.80 4.89 2.25 76.95 193.22 0.00
April 17.21 12.54 8.82 3.95 6.45 95.37 211.82 0.00
May 20.84 16.44 13.69 3.50 11.46 117.34 200.00 0.00
June 24.80 19.35 16.45 3.85 15.08 121.81 213.08 0.00
July 26.06 21.68 19.85 3.24 17.64 119.92 194.46 0.00
August 26.55 22.42 20.72 3.39 18.21 115.12 179.15 0.00
September 22.53 18.74 16.82 3.06 13.44 83.74 156.58 0.02
October 16.03 13.02 10.77 4.05 5.85 53.01 190.38 0.00
November 11.94 8.22 4.17 4.16 0.30 52.20 150.38 0.00
December 7.70 4.64 0.26 4.69 -4.1 44.81 142.03 0.00
                 
Annual Sum or Average 16.65 12.68 9.31 4.04 6.29 81.91 179.25 0.00
Minimum of Months 3.96 1.39 -3.0 3.06 -7.8 44.81 142.03 0.00
Maximum of Months 26.55 22.42 20.72 5.19 18.21 121.81 213.08 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.10 31-JAN-14:00 12.97 6.70 5.70 12.22 200.50 90.50
February 25.00 26-FEB-14:00 12.75 1.70 4.10 8.15 91.50 816.00
March 27.80 30-MAR-13:00 17.87 12.20 5.70 16.30 231.50 710.50
April 28.90 17-APR-14:20 16.56 8.13 2.03 13.35 125.83 887.67
May 30.60 19-MAY-13:00 18.49 11.70 4.60 15.76 140.00 875.50
June 34.40 06-JUN-14:00 22.39 17.20 8.20 22.13 251.00 561.00
July 36.70 08-JUL-14:00 23.91 18.90 2.10 24.66 274.00 567.00
August 35.00 01-AUG-14:00 23.84 19.40 2.60 26.15 306.00 508.00
September 31.70 07-SEP-15:09 23.05 19.60 4.02 22.55 218.67 591.33
October 30.00 10-OCT-15:00 20.56 16.10 3.60 17.57 97.00 561.00
November 24.40 05-NOV-15:00 17.95 14.40 2.10 14.10 117.50 361.50
December 22.80 12-DEC-14:20 16.78 13.33 5.20 13.35 144.17 433.83
                 
Annual Sum or Average                
Minimum of Months 21.10   12.75 1.70 2.03 8.15 91.50 90.50
Maximum of Months 36.70   23.91 19.60 8.20 26.15 306.00 887.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.7 14-JAN-06:10 -7.8 -10.6 4.95 -24.7 0.00 0.00
February -12.8 12-FEB-06:00 -13.8 -18.3 7.20 -30.1 0.00 0.00
March 1.10 19-MAR-06:00 -1.5 -6.1 0.00 -16.2 17.00 290.50
April 0.00 06-APR-04:00 -1.1 -2.8 3.10 -16.5 0.00 0.00
May 7.80 11-MAY-05:00 5.45 2.80 4.10 -7.8 21.50 204.50
June 11.10 10-JUN-04:00 8.73 6.70 0.00 -2.5 0.00 0.00
July 17.20 28-JUL-22:00 16.88 16.70 4.10 14.28 0.00 0.00
August 18.30 25-AUG-05:00 17.20 16.70 3.60 5.13 0.00 0.00
September 11.70 29-SEP-03:00 11.07 10.60 2.60 -2.3 0.00 0.00
October 2.20 26-OCT-04:00 1.95 1.70 3.10 -13.4 0.00 0.00
November -3.3 22-NOV-05:00 -4.0 -5.6 5.20 -20.2 0.00 0.00
December -5.6 18-DEC-07:00 -7.3 -11.7 2.60 -22.7 17.00 320.50
                 
Annual Sum or Average                
Minimum of Months -12.8   -13.8 -18.3 0.00 -30.1 0.00 0.00
Maximum of Months 18.30   17.20 16.70 7.20 14.28 21.50 320.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.51 19-JAN-21:00 18.30 15.60 8.80 15.21 0.00 0.00
February 15.81 18-FEB-15:00 17.20 15.00 5.20 13.91 73.00 1.00
March 18.16 30-MAR-12:30 25.85 13.85 5.45 15.39 323.00 600.00
April 20.01 04-APR-13:00 25.00 17.80 9.30 18.64 307.00 197.50
May 22.34 30-MAY-17:00 27.80 20.00 4.10 21.96 97.50 79.50
June 24.32 23-JUN-11:39 31.13 21.87 4.83 22.98 338.17 565.17
July 25.06 07-JUL-11:00 33.30 22.20 3.60 20.75 116.50 900.00
August 25.13 19-AUG-16:00 30.00 23.30 3.10 23.66 197.00 136.50
September 24.10 09-SEP-10:00 30.60 21.70 2.60 21.27 236.00 482.00
October 23.20 18-OCT-15:00 25.60 22.20 5.70 23.82 159.00 2.00
November 18.88 19-NOV-14:00 24.40 16.10 8.20 13.91 143.00 384.50
December 17.57 13-DEC-10:00 19.40 16.70 4.60 14.47 227.50 77.00
                 
Annual Sum or Average                
Minimum of Months 15.81   17.20 13.85 2.60 13.91 0.00 0.00
Maximum of Months 25.13   33.30 23.30 9.30 23.82 338.17 900.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 15.60 19-JAN-17:00 17.20 16.13 6.70 14.10 0.00 0.00
February 15.00 18-FEB-16:19 17.20 15.81 5.53 13.91 50.33 1.00
March 16.10 31-MAR-10:00 21.70 18.06 13.90 18.64 268.00 8.00
April 17.80 04-APR-09:20 20.77 18.74 7.53 16.79 242.00 111.50
May 20.60 30-MAY-19:00 25.00 21.79 2.60 12.41 0.00 0.00
June 22.80 18-JUN-16:00 28.30 24.23 0.00 24.66 140.50 115.50
July 23.30 26-JUL-09:00 26.10 24.10 3.60 24.66 338.00 251.50
August 23.90 08-AUG-19:00 26.10 24.51 1.50 24.83 0.00 0.00
September 23.30 16-SEP-16:00 25.60 23.89 2.10 22.13 108.00 57.50
October 22.20 18-OCT-14:00 25.00 23.04 4.60 23.32 234.50 2.00
November 17.20 04-NOV-13:00 17.80 17.48 3.60 15.02 276.50 2.50
December 16.70 13-DEC-16:19 17.03 16.82 2.93 14.10 54.00 4.50
                 
Annual Sum or Average                
Minimum of Months 15.00   17.03 15.81 0.00 12.41 0.00 0.00
Maximum of Months 23.90   28.30 24.51 13.90 24.83 338.00 251.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 13.74 22.89 0.00
February 18.00 13.00 16.00 13.65 27.55 0.00
March 18.00 13.00 16.00 15.17 38.46 0.00
April 18.00 13.00 16.00 17.98 47.59 0.00
May 18.00 13.00 16.00 21.32 52.44 0.00
June 18.00 13.00 16.00 24.28 55.84 0.00
July 18.00 13.00 16.00 26.07 52.33 0.00
August 18.00 13.00 16.00 26.20 48.31 0.00
September 18.00 13.00 16.00 24.63 36.35 0.00
October 18.00 13.00 16.00 21.78 31.91 0.00
November 18.00 13.00 16.00 18.45 24.33 0.00
December 18.00 13.00 16.00 15.51 20.76 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.94 38.29 0.00
Minimum of Months 18.00 13.00 16.00 13.65 20.76 0.00
Maximum of Months 18.00 13.00 16.00 26.20 55.84 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.370517E+11 -0.360225E+11 0.00 0.00 744.00 0.00 -0.102917E+10 58.97 0.00 0.00
February 0.337318E+11 -0.328031E+11 0.00 0.00 672.00 0.00 -928689857.1 58.98 0.00 0.00
March 0.383089E+11 -0.372807E+11 0.00 0.00 744.00 0.00 -0.102824E+10 58.97 0.00 0.00
April 0.326406E+11 -0.316483E+11 0.00 0.00 720.00 0.00 -992289264.1 58.97 0.00 0.00
May 0.321098E+11 -0.310845E+11 0.00 0.00 744.00 0.00 -0.102524E+10 58.98 0.00 0.00
June 0.293463E+11 -0.283547E+11 0.00 0.00 720.00 0.00 -991558263.1 58.97 0.00 0.00
July 0.265865E+11 -0.255676E+11 0.00 0.00 744.00 0.00 -0.101883E+10 58.97 0.00 0.00
August 0.289272E+11 -0.279041E+11 0.00 0.00 744.00 0.00 -0.102310E+10 58.98 0.00 0.00
September 0.275328E+11 -0.265456E+11 0.00 0.00 720.00 0.00 -987188961.4 58.97 0.00 0.00
October 0.306577E+11 -0.296385E+11 0.00 0.00 744.00 0.00 -0.101925E+10 58.97 0.00 0.00
November 0.326505E+11 -0.316641E+11 0.00 0.00 720.00 0.00 -986405512.1 58.97 0.00 0.00
December 0.348015E+11 -0.337800E+11 0.00 0.00 744.00 0.00 -0.102147E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.384345E+12 -0.372294E+12 0.00 0.00 8760.00 0.00 -0.120514E+11 58.97 0.00 0.00
Minimum of Months 0.265865E+11 -0.372807E+11 0.00 0.00 672.00 0.00 -0.102917E+10 58.97 0.00 0.00
Maximum of Months 0.383089E+11 -0.255676E+11 0.00 0.00 744.00 0.00 -928689857.1 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.63 0.61 01-JAN-08:50 5135.26 32.94 258.50 264.50 1312.65 25.39 169.67 238.83
February 263.00 0.64 0.61 01-FEB-10:09 6070.35 32.98 229.00 235.83 860.67 20.49 86.33 208.17
March 351.67 0.64 0.61 01-MAR-08:20 1281.08 16.72 6.67 303.17 727.60 19.52 81.67 261.67
April 369.33 0.64 0.61 01-APR-07:00 1065.79 16.18 0.00 307.83 595.38 19.06 43.33 256.83
May 407.00 0.64 0.61 01-MAY-07:10 969.25 16.28 0.00 340.33 533.72 19.18 14.33 284.17
June 411.67 0.64 0.61 01-JUN-06:40 900.25 15.97 0.00 342.33 502.31 18.89 5.67 280.67
July 411.00 0.64 0.61 01-JUL-06:00 949.53 16.18 0.00 343.83 522.58 19.06 19.17 282.67
August 390.50 0.64 0.61 01-AUG-06:00 1160.38 16.90 0.00 337.17 623.04 19.77 73.67 287.50
September 298.50 0.64 0.61 01-SEP-07:10 1232.52 17.09 6.50 294.50 674.77 19.66 68.83 239.33
October 293.50 0.63 0.61 01-OCT-07:40 2333.42 22.85 116.50 283.83 793.20 18.88 57.83 232.67
November 299.00 0.64 0.61 01-NOV-07:00 5037.34 32.73 268.00 263.67 888.30 22.15 116.17 233.83
December 285.17 0.63 0.61 01-DEC-07:00 4771.83 32.10 248.33 255.67 1256.60 26.37 168.67 233.00
                         
Annual Sum or Average 4071.00 0.64     2324.11 21.44 1133.50 3572.67 742.80 20.48 905.33 3039.33
Minimum of Months 263.00 0.63 0.61   900.25 15.97 0.00 235.83 502.31 18.88 5.67 208.17
Maximum of Months 411.67 0.64 0.61   6070.35 32.98 268.00 343.83 1312.65 26.37 169.67 287.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.65 0.61 01-JAN-08:50 1150.59 16.61 66.00 215.50 567.26 15.83 39.33 138.17
February 263.00 0.66 0.61 01-FEB-10:09 1547.56 16.26 58.33 198.17 769.54 15.38 36.50 144.50
March 351.67 0.64 0.61 01-MAR-08:09 1758.97 15.99 74.00 286.00 688.23 13.18 1.17 231.50
April 369.33 0.64 0.61 01-APR-07:49 1720.30 11.66 0.00 305.83 929.61 13.00 0.00 255.33
May 407.00 0.64 0.61 01-MAY-06:49 1945.92 12.24 0.00 348.00 789.72 13.41 0.00 292.17
June 411.67 0.64 0.61 01-JUN-06:19 2057.22 12.20 0.00 350.83 800.40 13.33 0.00 298.33
July 411.00 0.64 0.61 01-JUL-05:00 1946.81 12.35 0.00 354.50 809.76 13.50 0.00 303.33
August 390.50 0.64 0.61 01-AUG-06:40 1800.03 12.67 0.00 335.17 945.55 13.89 0.00 285.33
September 298.50 0.65 0.61 01-SEP-06:00 1702.25 12.18 3.83 286.33 854.92 13.53 2.83 223.50
October 293.50 0.65 0.61 01-OCT-07:30 2100.80 17.88 88.00 240.50 728.49 15.33 39.83 172.50
November 299.00 0.66 0.61 01-NOV-07:00 1350.97 16.88 75.67 224.67 746.19 17.70 64.67 160.83
December 285.17 0.65 0.61 01-DEC-07:00 1182.96 17.30 70.33 212.67 589.97 16.47 44.00 140.83
                         
Annual Sum or Average 4071.00 0.64     1720.29 14.23 436.17 3358.17 777.69 14.38 228.33 2646.33
Minimum of Months 263.00 0.64 0.61   1150.59 11.66 0.00 198.17 567.26 13.00 0.00 138.17
Maximum of Months 411.67 0.66 0.61   2100.80 17.88 88.00 354.50 945.55 17.70 64.67 303.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.67 0.61 01-JAN-09:09 394.64 0.00 0.00 154.67 238.41 0.00 0.00 22.67
February 263.00 0.68 0.61 01-FEB-10:20 418.16 0.00 0.00 144.50 260.32 0.00 0.00 56.83
March 351.67 0.65 0.61 01-MAR-08:39 534.33 0.00 0.00 272.50 325.77 0.00 0.00 147.33
April 369.33 0.64 0.61 01-APR-07:00 640.11 0.00 0.00 308.33 382.25 0.00 0.00 222.33
May 407.00 0.63 0.61 01-MAY-06:00 792.30 0.00 0.00 365.33 467.79 0.00 0.00 317.83
June 411.67 0.63 0.61 01-JUN-06:30 865.26 0.00 0.00 376.00 502.46 0.00 0.00 339.83
July 411.00 0.63 0.61 01-JUL-06:10 878.77 0.00 0.00 373.83 488.83 0.00 0.00 328.17
August 390.50 0.63 0.61 01-AUG-06:49 781.93 0.00 0.00 349.67 454.17 0.00 0.00 290.50
September 298.50 0.65 0.61 01-SEP-07:10 591.65 0.00 0.00 282.17 358.67 0.00 0.00 161.83
October 293.50 0.67 0.61 01-OCT-07:00 435.87 0.00 0.00 181.67 280.35 0.00 0.00 74.83
November 299.00 0.67 0.61 01-NOV-08:20 407.13 0.00 0.00 185.33 247.91 0.00 0.00 23.50
December 285.17 0.67 0.61 01-DEC-09:20 380.11 0.00 0.00 147.33 230.80 0.00 0.00 2.50
                         
Annual Sum or Average 4071.00 0.65     621.19 0.00 0.00 3141.33 368.04 0.00 0.00 1988.17
Minimum of Months 263.00 0.63 0.61   380.11 0.00 0.00 144.50 230.80 0.00 0.00 2.50
Maximum of Months 411.67 0.68 0.61   878.77 0.00 0.00 376.00 502.46 0.00 0.00 339.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.65 0.61 01-JAN-09:20 1355.63 16.91 68.50 217.17 781.20 17.81 60.00 147.50
February 263.00 0.66 0.61 01-FEB-10:20 1344.91 16.16 59.50 185.00 674.52 15.38 37.00 137.33
March 351.67 0.64 0.61 01-MAR-08:39 1775.01 14.62 47.33 288.67 948.45 13.25 0.00 230.83
April 369.33 0.64 0.61 01-APR-08:20 1860.99 11.76 0.00 307.83 1056.72 13.10 0.00 259.67
May 407.00 0.64 0.61 01-MAY-07:30 1954.43 12.31 0.00 345.83 778.65 13.55 1.33 294.33
June 411.67 0.64 0.61 01-JUN-06:00 2044.68 12.27 0.00 350.17 838.62 15.32 37.83 300.33
July 411.00 0.64 0.61 01-JUL-07:30 2030.64 12.34 0.00 349.17 818.61 15.02 27.83 297.00
August 390.50 0.64 0.61 01-AUG-07:30 1988.68 12.97 4.83 338.33 819.73 14.00 0.00 289.67
September 298.50 0.64 0.61 01-SEP-07:30 1741.64 15.11 49.67 285.50 917.00 13.58 0.00 218.00
October 293.50 0.65 0.61 01-OCT-08:20 1840.40 16.22 70.50 231.67 701.56 12.66 2.17 172.83
November 299.00 0.65 0.61 01-NOV-08:20 1313.70 17.02 79.50 226.00 652.50 16.30 51.67 162.00
December 285.17 0.65 0.61 01-DEC-09:20 1143.04 17.04 70.83 209.67 577.15 16.33 44.00 139.00
                         
Annual Sum or Average 4071.00 0.65     1740.71 14.26 450.67 3335.00 807.25 14.61 261.83 2648.50
Minimum of Months 263.00 0.64 0.61   1143.04 11.76 0.00 185.00 577.15 12.66 0.00 137.33
Maximum of Months 411.67 0.66 0.61   2044.68 17.04 79.50 350.17 1056.72 17.81 60.00 300.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.64 0.61 01-JAN-08:50 5045.08 30.47 233.00 259.83 1347.48 21.60 100.50 240.17
February 263.00 0.64 0.61 01-FEB-10:09 6053.42 32.50 227.50 234.00 895.79 15.72 25.83 208.67
March 351.67 0.64 0.61 01-MAR-08:20 1263.71 10.58 6.50 302.33 755.03 15.21 0.00 264.33
April 369.33 0.64 0.61 01-APR-07:00 1048.79 10.33 0.00 306.67 615.77 15.14 0.00 259.33
May 407.00 0.64 0.61 01-MAY-07:10 950.46 10.60 0.00 338.17 549.68 15.36 0.00 287.67
June 411.67 0.64 0.61 01-JUN-06:40 882.89 10.44 0.00 340.50 517.04 15.16 0.00 283.67
July 411.00 0.64 0.61 01-JUL-06:00 930.38 10.63 0.00 342.00 537.66 15.32 0.00 286.67
August 390.50 0.64 0.61 01-AUG-06:00 1135.99 11.29 0.00 335.17 641.03 15.98 0.00 290.33
September 298.50 0.64 0.61 01-SEP-07:10 1210.33 11.47 6.50 293.33 696.93 15.79 0.00 242.83
October 293.50 0.64 0.61 01-OCT-07:49 2321.95 18.72 115.00 281.33 832.05 14.36 2.00 236.00
November 299.00 0.64 0.61 01-NOV-07:00 5016.18 32.05 266.33 262.83 943.91 19.77 79.33 241.00
December 285.17 0.63 0.61 01-DEC-07:00 4747.47 31.25 241.33 254.67 1246.24 21.07 97.50 228.17
                         
Annual Sum or Average 4071.00 0.64     2299.92 17.13 1096.17 3550.83 765.89 16.51 305.17 3068.83
Minimum of Months 263.00 0.63 0.61   882.89 10.33 0.00 234.00 517.04 14.36 0.00 208.67
Maximum of Months 411.67 0.64 0.61   6053.42 32.50 266.33 342.00 1347.48 21.60 100.50 290.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.65 0.61 01-JAN-08:50 1009.75 12.28 45.00 213.33 582.50 13.79 40.00 144.33
February 263.00 0.66 0.61 01-FEB-10:09 1552.29 14.00 58.50 198.00 790.91 13.33 37.00 149.67
March 351.67 0.64 0.61 01-MAR-08:09 1763.32 13.61 74.33 284.83 709.62 10.68 1.17 236.83
April 369.33 0.64 0.61 01-APR-07:49 1718.65 8.18 0.00 305.50 953.59 10.53 0.00 259.67
May 407.00 0.64 0.61 01-MAY-06:49 1930.85 8.76 0.00 347.17 815.20 11.06 0.00 298.67
June 411.67 0.64 0.61 01-JUN-06:19 1949.25 8.80 0.00 349.50 825.67 11.08 0.00 301.83
July 411.00 0.64 0.61 01-JUL-05:00 1931.72 8.92 0.00 353.50 834.79 11.20 0.00 307.50
August 390.50 0.64 0.61 01-AUG-06:40 1784.64 9.29 0.00 334.33 968.44 11.51 0.00 288.83
September 298.50 0.65 0.61 01-SEP-06:00 1705.07 8.76 2.67 285.00 878.49 11.09 2.83 227.83
October 293.50 0.65 0.61 01-OCT-07:30 1933.03 13.74 67.33 241.00 751.26 13.31 40.00 177.67
November 299.00 0.66 0.61 01-NOV-07:00 1348.79 14.75 75.83 224.33 762.09 15.92 66.50 167.50
December 285.17 0.65 0.61 01-DEC-07:00 1169.58 14.79 67.33 211.50 605.57 14.40 44.33 145.50
                         
Annual Sum or Average 4071.00 0.65     1682.35 11.01 391.00 3348.00 799.63 12.13 231.83 2705.83
Minimum of Months 263.00 0.64 0.61   1009.75 8.18 0.00 198.00 582.50 10.53 0.00 144.33
Maximum of Months 411.67 0.66 0.61   1949.25 14.79 75.83 353.50 968.44 15.92 66.50 307.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.68 0.61 01-JAN-09:09 387.32 0.00 0.00 151.83 245.31 0.00 0.00 27.50
February 263.00 0.68 0.61 01-FEB-10:30 411.46 0.00 0.00 142.33 268.29 0.00 0.00 65.50
March 351.67 0.65 0.61 01-MAR-08:39 525.69 0.00 0.00 269.33 335.69 0.00 0.00 165.00
April 369.33 0.64 0.61 01-APR-07:00 630.18 0.00 0.00 307.00 394.14 0.00 0.00 229.67
May 407.00 0.63 0.61 01-MAY-06:00 778.83 0.00 0.00 364.17 481.55 0.00 0.00 323.33
June 411.67 0.63 0.61 01-JUN-06:30 850.86 0.00 0.00 375.33 524.92 0.00 0.00 349.83
July 411.00 0.63 0.61 01-JUL-06:10 863.87 0.00 0.00 372.67 502.95 0.00 0.00 331.50
August 390.50 0.63 0.61 01-AUG-06:49 764.99 0.00 0.00 346.17 467.03 0.00 0.00 296.17
September 298.50 0.65 0.61 01-SEP-07:10 581.54 0.00 0.00 280.17 369.13 0.00 0.00 170.17
October 293.50 0.67 0.61 01-OCT-08:09 429.84 0.00 0.00 181.33 289.21 0.00 0.00 81.67
November 299.00 0.67 0.61 01-NOV-08:20 399.32 0.00 0.00 181.50 254.89 0.00 0.00 33.17
December 285.17 0.68 0.61 01-DEC-09:20 372.42 0.00 0.00 144.00 237.17 0.00 0.00 8.33
                         
Annual Sum or Average 4071.00 0.65     610.36 0.00 0.00 3115.83 379.65 0.00 0.00 2081.83
Minimum of Months 263.00 0.63 0.61   372.42 0.00 0.00 142.33 237.17 0.00 0.00 8.33
Maximum of Months 411.67 0.68 0.61   863.87 0.00 0.00 375.33 524.92 0.00 0.00 349.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.65 0.61 01-JAN-09:20 1354.76 14.66 68.00 216.67 797.92 15.99 60.17 152.83
February 263.00 0.66 0.61 01-FEB-10:20 1186.53 11.63 41.17 185.00 694.20 13.39 37.00 140.00
March 351.67 0.64 0.61 01-MAR-08:39 1780.49 11.79 47.33 288.00 910.80 10.67 0.00 233.67
April 369.33 0.64 0.61 01-APR-08:20 1859.15 8.28 0.00 307.50 1080.68 10.65 0.00 264.17
May 407.00 0.64 0.61 01-MAY-07:30 1848.58 8.88 0.00 344.83 802.13 11.16 0.00 299.00
June 411.67 0.64 0.61 01-JUN-06:00 2031.51 8.90 0.00 349.67 842.29 11.17 0.00 301.17
July 411.00 0.64 0.61 01-JUL-07:30 2006.01 8.96 0.00 348.67 825.82 11.20 0.00 299.17
August 390.50 0.64 0.61 01-AUG-07:30 1896.20 9.65 4.83 337.33 842.74 11.63 0.00 294.50
September 298.50 0.65 0.61 01-SEP-07:30 1745.67 12.49 49.67 284.83 940.03 11.09 0.00 223.67
October 293.50 0.65 0.61 01-OCT-08:20 1844.44 13.93 70.50 232.17 723.30 10.12 2.17 179.33
November 299.00 0.66 0.61 01-NOV-08:20 1311.61 14.88 79.67 225.67 668.62 14.31 51.83 167.33
December 285.17 0.65 0.61 01-DEC-09:20 1141.42 14.88 70.83 209.50 592.21 14.27 44.50 142.67
                         
Annual Sum or Average 4071.00 0.65     1707.77 11.24 432.00 3329.83 819.78 11.98 195.67 2697.50
Minimum of Months 263.00 0.64 0.61   1141.42 8.28 0.00 185.00 592.21 10.12 0.00 140.00
Maximum of Months 411.67 0.66 0.61   2031.51 14.88 79.67 349.67 1080.68 15.99 60.17 301.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.64 0.61 01-JAN-08:50 5044.69 30.46 233.00 259.83 1348.41 21.59 100.50 240.17
February 263.00 0.64 0.61 01-FEB-10:09 6018.43 31.23 217.00 230.17 896.64 15.70 25.83 208.67
March 351.67 0.64 0.61 01-MAR-08:20 1264.30 10.53 6.33 302.33 755.88 15.19 0.00 264.33
April 369.33 0.64 0.61 01-APR-07:00 1049.35 10.29 0.00 306.67 616.47 15.12 0.00 259.67
May 407.00 0.64 0.61 01-MAY-07:10 950.94 10.56 0.00 338.17 550.31 15.34 0.00 287.83
June 411.67 0.64 0.61 01-JUN-06:40 883.29 10.40 0.00 340.50 517.61 15.14 0.00 284.00
July 411.00 0.64 0.61 01-JUL-06:00 930.84 10.59 0.00 342.00 538.26 15.30 0.00 287.00
August 390.50 0.64 0.61 01-AUG-06:00 1136.63 11.25 0.00 335.17 641.82 15.96 0.00 290.33
September 298.50 0.64 0.61 01-SEP-07:10 1210.97 11.43 6.50 293.33 697.76 15.78 0.00 242.83
October 293.50 0.64 0.61 01-OCT-07:49 2322.34 18.69 115.00 281.33 832.83 14.34 2.00 236.33
November 299.00 0.64 0.61 01-NOV-07:00 5016.03 32.04 266.33 262.83 944.86 19.76 79.33 241.00
December 285.17 0.63 0.61 01-DEC-07:00 4746.91 31.24 241.17 254.67 1247.16 21.06 97.50 228.17
                         
Annual Sum or Average 4071.00 0.64     2297.95 17.02 1085.33 3547.00 766.65 16.50 305.17 3070.33
Minimum of Months 263.00 0.63 0.61   883.29 10.29 0.00 230.17 517.61 14.34 0.00 208.67
Maximum of Months 411.67 0.64 0.61   6018.43 32.04 266.33 342.00 1348.41 21.59 100.50 290.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.65 0.61 01-JAN-08:50 1009.65 12.26 45.00 213.33 582.94 13.78 40.00 144.83
February 263.00 0.66 0.61 01-FEB-10:09 1552.17 13.99 58.50 197.83 791.31 13.32 37.00 150.00
March 351.67 0.64 0.61 01-MAR-08:09 1763.27 13.60 74.33 284.83 710.18 10.67 1.17 236.83
April 369.33 0.64 0.61 01-APR-07:49 1718.74 8.17 0.00 305.50 954.22 10.52 0.00 259.83
May 407.00 0.64 0.61 01-MAY-06:49 1930.98 8.75 0.00 347.33 815.93 11.05 0.00 298.67
June 411.67 0.64 0.61 01-JUN-06:19 1949.34 8.79 0.00 349.33 826.41 11.07 0.00 301.83
July 411.00 0.64 0.61 01-JUL-05:00 1931.79 8.90 0.00 353.50 835.55 11.19 0.00 307.50
August 390.50 0.64 0.61 01-AUG-06:40 1784.78 9.27 0.00 334.33 969.22 11.50 0.00 289.17
September 298.50 0.65 0.61 01-SEP-06:00 1704.94 8.75 2.67 285.00 879.10 11.08 2.83 228.00
October 293.50 0.65 0.61 01-OCT-07:30 1932.81 13.73 67.33 241.00 751.69 13.30 40.00 177.83
November 299.00 0.66 0.61 01-NOV-07:00 1348.65 14.74 75.83 224.33 762.53 15.92 66.50 167.67
December 285.17 0.65 0.61 01-DEC-07:00 1169.44 14.78 67.33 211.50 605.97 14.39 44.33 145.67
                         
Annual Sum or Average 4071.00 0.65     1682.34 11.00 391.00 3347.83 800.23 12.13 231.83 2707.83
Minimum of Months 263.00 0.64 0.61   1009.65 8.17 0.00 197.83 582.94 10.52 0.00 144.83
Maximum of Months 411.67 0.66 0.61   1949.34 14.78 75.83 353.50 969.22 15.92 66.50 307.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.68 0.61 01-JAN-09:09 387.32 0.00 0.00 151.50 245.53 0.00 0.00 27.67
February 263.00 0.68 0.61 01-FEB-10:30 411.42 0.00 0.00 142.33 268.51 0.00 0.00 65.67
March 351.67 0.65 0.61 01-MAR-08:39 525.68 0.00 0.00 269.50 335.98 0.00 0.00 165.50
April 369.33 0.64 0.61 01-APR-07:00 630.24 0.00 0.00 307.00 394.51 0.00 0.00 229.67
May 407.00 0.63 0.61 01-MAY-06:00 778.97 0.00 0.00 364.17 482.03 0.00 0.00 323.67
June 411.67 0.63 0.61 01-JUN-06:30 851.03 0.00 0.00 375.33 525.44 0.00 0.00 349.83
July 411.00 0.63 0.61 01-JUL-06:10 864.03 0.00 0.00 372.67 503.46 0.00 0.00 331.50
August 390.50 0.63 0.61 01-AUG-06:49 765.08 0.00 0.00 346.33 467.50 0.00 0.00 296.33
September 298.50 0.65 0.61 01-SEP-07:10 581.51 0.00 0.00 280.00 369.45 0.00 0.00 170.33
October 293.50 0.67 0.61 01-OCT-08:09 429.76 0.00 0.00 181.50 289.42 0.00 0.00 81.67
November 299.00 0.67 0.61 01-NOV-08:20 399.29 0.00 0.00 181.50 255.12 0.00 0.00 33.17
December 285.17 0.68 0.61 01-DEC-09:20 372.39 0.00 0.00 143.67 237.38 0.00 0.00 8.33
                         
Annual Sum or Average 4071.00 0.65     610.41 0.00 0.00 3115.50 380.01 0.00 0.00 2083.33
Minimum of Months 263.00 0.63 0.61   372.39 0.00 0.00 142.33 237.38 0.00 0.00 8.33
Maximum of Months 411.67 0.68 0.61   864.03 0.00 0.00 375.33 525.44 0.00 0.00 349.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.65 0.61 01-JAN-09:20 1354.66 14.65 68.00 216.67 798.35 15.98 60.17 153.00
February 263.00 0.66 0.61 01-FEB-10:20 1186.37 11.62 41.17 185.00 694.68 13.38 37.00 140.00
March 351.67 0.64 0.61 01-MAR-08:39 1780.28 11.78 47.33 288.00 911.38 10.67 0.00 234.00
April 369.33 0.64 0.61 01-APR-08:20 1859.22 8.26 0.00 307.67 1081.34 10.64 0.00 264.33
May 407.00 0.64 0.61 01-MAY-07:30 1848.72 8.86 0.00 344.83 802.88 11.16 0.00 299.00
June 411.67 0.64 0.61 01-JUN-06:00 2031.61 8.88 0.00 349.67 843.04 11.16 0.00 301.33
July 411.00 0.64 0.61 01-JUL-07:30 2006.15 8.95 0.00 348.67 826.58 11.19 0.00 299.33
August 390.50 0.64 0.61 01-AUG-07:30 1896.36 9.64 4.83 337.33 839.50 11.62 0.00 294.50
September 298.50 0.65 0.61 01-SEP-07:30 1745.68 12.48 49.67 284.83 898.59 11.08 0.00 221.17
October 293.50 0.65 0.61 01-OCT-08:20 1844.23 13.92 70.50 232.17 723.76 10.11 2.17 179.33
November 299.00 0.66 0.61 01-NOV-08:20 1311.47 14.87 79.67 225.67 669.08 14.31 51.83 167.33
December 285.17 0.65 0.61 01-DEC-09:20 1141.29 14.87 70.83 209.17 592.62 14.27 44.50 143.17
                         
Annual Sum or Average 4071.00 0.65     1707.76 11.23 432.00 3329.67 816.93 11.97 195.67 2696.50
Minimum of Months 263.00 0.64 0.61   1141.29 8.26 0.00 185.00 592.62 10.11 0.00 140.00
Maximum of Months 411.67 0.66 0.61   2031.61 14.87 79.67 349.67 1081.34 15.98 60.17 301.33



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.125490E+10 51378.81 06-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.831263E+09 58109.47 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.190869E+09 27257.73 18-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.295089E+09 27164.08 06-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.171670E+09 9833.09 15-MAY-15:30 0.00 0.00 0.00 0.00 0.00
June 46717691.54 7396.97 02-JUN-15:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 1509395.83 4560.58 25-AUG-11:10 0.00 0.00 0.00 0.00 0.00
September 29117668.01 8279.74 14-SEP-14:50 0.00 0.00 0.00 0.00 0.00
October 95833582.56 27727.19 26-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.344881E+09 45052.04 22-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.706857E+09 46657.59 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.396871E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.125490E+10 58109.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.642481E+09 14892.62 14-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.237656E+09 14935.22 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 8377109.88 3945.55 22-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 31025966.41 13200.50 18-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.919540E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.642481E+09 14935.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.629239E+09 12050.94 14-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.261730E+09 12086.46 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 3597460.54 527.23 18-MAR-06:50 0.00 0.00 0.00 0.00 0.00
April 831391.80 611.29 06-APR-05:04 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 1905554.99 432.19 26-OCT-06:00 0.00 0.00 0.00 0.00 0.00
November 20136751.80 9253.84 21-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.106311E+09 12049.33 18-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.102375E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.629239E+09 12086.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.669461E+09 16935.56 14-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.241742E+09 16984.07 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 19508713.17 15165.54 21-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 90763389.60 16935.19 18-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.102147E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.669461E+09 16984.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.288141E+09 10457.20 09-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 39087211.13 10553.28 13-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.327228E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.288141E+09 10553.28   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.262322E+11 538473.62 06-JAN-17:40 0.00 0.00 0.00 0.00 0.00
February 0.238430E+11 590996.28 03-FEB-17:50 0.00 0.00 0.00 0.00 0.00
March 0.713028E+10 315280.92 22-MAR-07:30 0.00 0.00 0.00 0.00 0.00
April 0.266692E+10 355492.35 06-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.174408E+10 145017.40 11-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.514811E+09 50133.53 02-JUN-15:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 30192064.67 30086.69 25-AUG-13:50 0.00 0.00 0.00 0.00 0.00
September 0.334371E+09 118816.18 14-SEP-16:20 0.00 0.00 0.00 0.00 0.00
October 0.328712E+10 328828.48 26-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.929287E+10 493859.92 22-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.129090E+11 546024.12 18-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.879848E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.262322E+11 590996.28   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.205186E+10 541261.90 09-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.829214E+09 546043.98 13-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.288108E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.205186E+10 546043.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.438496E+11 135246.79 02-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.237310E+11 145024.27 25-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.183851E+10 144687.45 18-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.368941E+09 135784.18 06-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.514835E+09 145876.85 26-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.544976E+10 136782.48 18-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.201323E+11 145707.70 15-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.958849E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.438496E+11 145876.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.314144E+11 141111.02 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.170551E+11 140739.27 13-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.175395E+10 144478.37 18-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.271350E+09 83981.35 06-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.112762E+10 111251.23 26-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.394660E+10 140211.59 25-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.149570E+11 149347.48 16-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.705260E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.314144E+11 149347.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.224798E+11 154777.70 09-JAN-06:05 0.00 0.00 0.00 0.00 0.00
February 0.119634E+11 155160.41 11-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.753011E+09 149440.17 22-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.209647E+09 54652.75 06-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.407053E+09 39119.96 31-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.173748E+10 153487.62 25-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.830069E+10 164315.22 16-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.458511E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.224798E+11 164315.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.275133E+11 149460.23 09-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.146006E+11 148660.63 07-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.126485E+10 96704.89 22-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.184114E+09 23232.09 06-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.621124E+09 44821.88 26-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.385294E+10 148440.51 25-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.129015E+11 151521.54 16-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.609385E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.275133E+11 151521.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.187434E+10 54372.63 06-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.113896E+10 57542.67 13-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.250014E+09 32545.74 18-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.229605E+09 37404.54 06-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.125096E+09 15119.13 11-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 33053327.54 6757.36 02-JUN-13:50 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 9937221.65 6527.22 25-AUG-11:20 0.00 0.00 0.00 0.00 0.00
September 13734484.32 2723.99 22-SEP-14:40 0.00 0.00 0.00 0.00 0.00
October 0.170400E+09 34544.05 26-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.371732E+09 51279.73 22-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.735600E+09 56174.29 18-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.495248E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.187434E+10 57542.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.639639E+10 82584.56 02-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.292135E+10 82117.51 08-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 48586089.58 42625.71 20-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 19014382.94 4166.44 30-OCT-05:20 0.00 0.00 0.00 0.00 0.00
November 0.349020E+09 81918.38 25-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.282878E+10 82627.88 26-DEC-05:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.125632E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.639639E+10 82627.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.934813E+10 15410.68 02-JAN-05:35 0.00 0.00 0.00 0.00 0.00
February 0.556354E+10 16750.36 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.107426E+10 15336.07 02-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.280075E+09 15266.42 26-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 7127625.29 1410.29 11-MAY-05:20 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 926522.87 258.16 29-SEP-05:50 0.00 0.00 0.00 0.00 0.00
October 0.643591E+09 15347.68 31-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.217790E+10 15361.81 25-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.572328E+10 15379.86 26-DEC-05:17 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.248188E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.934813E+10 16750.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.581572E+10 14543.54 19-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.341172E+10 14498.12 11-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.665420E+09 14484.35 22-MAR-04:03 0.00 0.00 0.00 0.00 0.00
April 0.145459E+09 14363.16 06-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 4819230.85 1431.74 11-MAY-05:20 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 7602815.45 1304.48 29-SEP-05:20 0.00 0.00 0.00 0.00 0.00
October 0.499377E+09 14489.71 25-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.131063E+10 14514.06 25-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.351001E+10 14504.12 26-DEC-05:06 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.153708E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.581572E+10 14543.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.553113E+10 17370.41 02-JAN-05:17 0.00 0.00 0.00 0.00 0.00
February 0.337392E+10 17303.91 11-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.634226E+09 17306.56 22-MAR-04:03 0.00 0.00 0.00 0.00 0.00
April 0.197703E+09 17181.84 07-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 7195466.33 1058.94 11-MAY-06:00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 1698458.35 373.37 29-SEP-06:00 0.00 0.00 0.00 0.00 0.00
October 0.392964E+09 17310.31 31-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.100217E+10 17282.58 25-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.292954E+10 17337.15 26-DEC-05:17 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.140706E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.553113E+10 17370.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.533783E+10 16290.81 02-JAN-04:12 0.00 0.00 0.00 0.00 0.00
February 0.308317E+10 16246.13 11-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.618415E+09 16189.03 22-MAR-04:01 0.00 0.00 0.00 0.00 0.00
April 0.140306E+09 14298.56 06-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 2530784.78 342.09 11-MAY-05:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 5121561.78 1466.08 29-SEP-05:10 0.00 0.00 0.00 0.00 0.00
October 0.437969E+09 14936.60 25-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.128565E+10 16202.78 24-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.310999E+10 16211.68 27-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.140210E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.533783E+10 16290.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.198280E+10 0.187542E+10 41599.57 31-JAN-15:00 41599.57 0.03
February 0.00 0.00 0.848749E+10 0.848331E+10 92211.38 28-FEB-15:00 92211.38 0.04
March 0.00 0.00 0.270838E+11 0.261654E+11 126352.88 30-MAR-05:03 65283.66 0.17
April 0.00 0.00 0.593506E+11 0.565493E+11 166868.64 17-APR-15:00 166868.64 0.37
May 0.00 0.00 0.948286E+11 0.804717E+11 212907.75 31-MAY-03:02 144239.18 0.56
June 0.00 0.00 0.149290E+12 0.125402E+12 220342.84 26-JUN-05:02 156456.50 0.68
July 0.00 0.00 0.177982E+12 0.142759E+12 215751.27 17-JUL-05:03 154510.50 0.81
August 0.00 0.00 0.207460E+12 0.165899E+12 221848.30 07-AUG-05:03 157766.82 0.88
September 0.00 0.00 0.113116E+12 0.919298E+11 227672.48 05-SEP-03:02 157742.07 0.63
October 0.00 0.00 0.517056E+11 0.420874E+11 217641.84 19-OCT-05:03 143870.29 0.24
November 0.00 0.00 0.183662E+11 0.169287E+11 118267.43 27-NOV-06:03 118267.43 0.12
December 0.00 0.00 0.569561E+10 0.478798E+10 110224.97 13-DEC-06:03 52442.93 0.05
                 
Annual Sum or Average 0.00 0.00 0.915349E+12 0.763340E+12       0.38
Minimum of Months 0.00 0.00 0.198280E+10 0.187542E+10 41599.57   41599.57 0.03
Maximum of Months 0.00 0.00 0.207460E+12 0.165899E+12 227672.48   166868.64 0.88



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.144249E+11 0.137684E+11 309146.43 31-JAN-15:00 309146.43 0.03
February 0.00 0.00 0.633944E+11 0.633944E+11 727541.52 28-FEB-15:00 727541.52 0.03
March 0.00 0.00 0.201860E+12 0.195986E+12 1156652.07 30-MAR-15:20 1156652.07 0.16
April 0.00 0.00 0.429048E+12 0.411037E+12 1553135.93 12-APR-14:40 1553135.93 0.29
May 0.00 0.00 0.830103E+12 0.702445E+12 1765834.77 31-MAY-03:02 1132766.70 0.54
June 0.00 0.00 0.126985E+13 0.103091E+13 2161595.29 24-JUN-05:03 1415551.21 0.59
July 0.00 0.00 0.144371E+13 0.109503E+13 2242378.74 14-JUL-03:02 1465605.21 0.66
August 0.00 0.00 0.162546E+13 0.120836E+13 2517226.01 23-AUG-03:02 1449689.63 0.69
September 0.00 0.00 0.974399E+12 0.769309E+12 2155005.74 27-SEP-05:03 1435590.22 0.58
October 0.00 0.00 0.403308E+12 0.319247E+12 1837833.88 18-OCT-04:03 1078298.03 0.21
November 0.00 0.00 0.125975E+12 0.118555E+12 771822.99 04-NOV-05:02 401232.80 0.11
December 0.00 0.00 0.349632E+11 0.297104E+11 836741.85 13-DEC-06:03 401710.15 0.05
                 
Annual Sum or Average 0.00 0.00 0.741648E+13 0.595776E+13       0.33
Minimum of Months 0.00 0.00 0.144249E+11 0.137684E+11 309146.43   309146.43 0.03
Maximum of Months 0.00 0.00 0.162546E+13 0.120836E+13 2517226.01   1553135.93 0.69



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.133325E+10 0.126813E+10 24819.03 31-JAN-15:00 24819.03 0.03
February 0.00 0.00 0.549883E+10 0.549883E+10 69599.68 28-FEB-15:00 69599.68 0.03
March 0.00 0.00 0.194692E+11 0.190508E+11 127836.40 30-MAR-15:30 127836.40 0.15
April 0.00 0.00 0.440849E+11 0.423593E+11 167531.78 17-APR-15:00 167531.78 0.28
May 0.00 0.00 0.897048E+11 0.768287E+11 169693.82 16-MAY-15:40 169693.82 0.53
June 0.00 0.00 0.140246E+12 0.115584E+12 222371.00 29-JUN-05:03 145057.48 0.60
July 0.00 0.00 0.159566E+12 0.123878E+12 239690.96 14-JUL-03:02 154666.68 0.67
August 0.00 0.00 0.178030E+12 0.135335E+12 269757.61 23-AUG-03:02 153231.68 0.70
September 0.00 0.00 0.100559E+12 0.803705E+11 224550.45 27-SEP-05:03 148261.22 0.58
October 0.00 0.00 0.394586E+11 0.310869E+11 209629.00 19-OCT-04:03 103993.49 0.21
November 0.00 0.00 0.107436E+11 0.101097E+11 69268.52 04-NOV-05:02 36937.49 0.10
December 0.00 0.00 0.298258E+10 0.252223E+10 44724.07 12-DEC-14:40 44724.07 0.05
                 
Annual Sum or Average 0.00 0.00 0.791677E+12 0.643892E+12       0.33
Minimum of Months 0.00 0.00 0.133325E+10 0.126813E+10 24819.03   24819.03 0.03
Maximum of Months 0.00 0.00 0.178030E+12 0.135335E+12 269757.61   169693.82 0.70



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.654960E+09 0.638719E+09 51712.16 19-JAN-05:02 21872.50 0.02
February 0.00 0.00 0.429000E+10 0.427141E+10 60831.06 28-FEB-14:20 60831.06 0.01
March 0.00 0.00 0.133790E+11 0.133359E+11 84394.81 29-MAR-04:03 48177.77 0.12
April 0.00 0.00 0.281709E+11 0.277378E+11 91436.89 17-APR-14:20 91436.89 0.23
May 0.00 0.00 0.509565E+11 0.466949E+11 134085.00 31-MAY-03:02 53339.07 0.43
June 0.00 0.00 0.871638E+11 0.736925E+11 160487.35 26-JUN-03:02 93879.61 0.51
July 0.00 0.00 0.997131E+11 0.793583E+11 160904.56 09-JUL-19:58 90415.30 0.55
August 0.00 0.00 0.119852E+12 0.938395E+11 170939.38 06-AUG-17:00 90563.37 0.63
September 0.00 0.00 0.740994E+11 0.627840E+11 170246.34 17-SEP-15:30 91581.25 0.52
October 0.00 0.00 0.326725E+11 0.276098E+11 147025.23 19-OCT-03:02 89449.06 0.19
November 0.00 0.00 0.105825E+11 0.989265E+10 82619.10 27-NOV-06:03 41080.11 0.08
December 0.00 0.00 0.304282E+10 0.281530E+10 78224.66 13-DEC-06:03 36877.32 0.04
                 
Annual Sum or Average 0.00 0.00 0.524577E+12 0.442671E+12       0.28
Minimum of Months 0.00 0.00 0.654960E+09 0.638719E+09 51712.16   21872.50 0.01
Maximum of Months 0.00 0.00 0.119852E+12 0.938395E+11 170939.38   93879.61 0.63



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.322966E+12 0.322464E+12 130083.10 19-JAN-17:00 124069.89 0.00
February 0.00 0.00 0.513952E+12 0.513402E+12 220175.47 17-FEB-17:00 214473.75 0.00
March 0.00 0.00 0.819449E+12 0.817911E+12 394376.47 31-MAR-24:00 394376.47 0.00
April 0.00 0.00 0.103082E+13 0.102886E+13 406828.74 21-APR-15:00 400382.54 0.00
May 0.00 0.00 0.340757E+12 0.334600E+12 213073.78 31-MAY-23:10 211091.89 0.00
June 0.00 0.00 0.572826E+12 0.563876E+12 303977.93 30-JUN-23:03 303070.61 0.00
July 0.00 0.00 0.840267E+12 0.829354E+12 396710.96 31-JUL-23:53 395957.48 0.00
August 0.00 0.00 0.108066E+13 0.106955E+13 422669.57 08-AUG-17:00 404110.58 0.00
September 0.00 0.00 0.337763E+12 0.329527E+12 212264.84 30-SEP-23:20 211758.45 0.00
October 0.00 0.00 0.584208E+12 0.580533E+12 304610.49 31-OCT-24:00 304610.49 0.00
November 0.00 0.00 0.798227E+12 0.796774E+12 317828.33 27-NOV-17:00 311185.01 0.00
December 0.00 0.00 0.106526E+13 0.106452E+13 408607.11 13-DEC-14:00 400800.63 0.00
                 
Annual Sum or Average 0.00 0.00 0.830716E+13 0.825137E+13       0.00
Minimum of Months 0.00 0.00 0.322966E+12 0.322464E+12 130083.10   124069.89 0.00
Maximum of Months 0.00 0.00 0.108066E+13 0.106955E+13 422669.57   404110.58 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.388000E+10 0.386082E+10 2286.82 20-JAN-17:00 2184.50 0.00
February 0.00 0.00 0.872691E+10 0.870482E+10 4453.16 20-FEB-17:57 4421.18 0.00
March 0.00 0.00 0.156533E+11 0.155876E+11 7720.69 31-MAR-24:00 7720.69 0.00
April 0.00 0.00 0.202801E+11 0.201905E+11 8432.87 09-APR-18:13 8432.87 0.00
May 0.00 0.00 0.614787E+10 0.591563E+10 4101.81 31-MAY-24:00 4047.65 0.00
June 0.00 0.00 0.111893E+11 0.108197E+11 5924.57 30-JUN-23:03 5872.78 0.00
July 0.00 0.00 0.167372E+11 0.162639E+11 7802.82 31-JUL-23:53 7783.51 0.00
August 0.00 0.00 0.219282E+11 0.213794E+11 8910.23 04-AUG-15:00 8286.90 0.00
September 0.00 0.00 0.612801E+10 0.581391E+10 3809.52 30-SEP-24:00 3795.04 0.00
October 0.00 0.00 0.108360E+11 0.106852E+11 5714.11 31-OCT-24:00 5714.11 0.00
November 0.00 0.00 0.150491E+11 0.149919E+11 6351.58 11-NOV-17:00 6351.58 0.00
December 0.00 0.00 0.202053E+11 0.201732E+11 8238.83 11-DEC-16:50 8050.45 0.00
                 
Annual Sum or Average 0.00 0.00 0.156761E+12 0.154387E+12       0.00
Minimum of Months 0.00 0.00 0.388000E+10 0.386082E+10 2286.82   2184.50 0.00
Maximum of Months 0.00 0.00 0.219282E+11 0.213794E+11 8910.23   8432.87 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.163281E+11 0.161539E+11 19530.52 20-JAN-17:00 18500.76 0.00
February 0.00 0.00 0.677968E+11 0.675829E+11 40685.97 28-FEB-17:00 40685.97 0.00
March 0.00 0.00 0.141442E+12 0.140785E+12 72458.81 31-MAR-24:00 72458.81 0.00
April 0.00 0.00 0.190165E+12 0.189267E+12 79426.71 04-APR-15:30 76484.20 0.00
May 0.00 0.00 0.560115E+11 0.537319E+11 38870.98 31-MAY-24:00 38306.23 0.00
June 0.00 0.00 0.106096E+12 0.102419E+12 56867.18 30-JUN-24:00 56666.29 0.00
July 0.00 0.00 0.159566E+12 0.154846E+12 75557.80 31-JUL-23:53 75369.05 0.00
August 0.00 0.00 0.208708E+12 0.203221E+12 84473.89 04-AUG-14:50 78354.88 0.00
September 0.00 0.00 0.553801E+11 0.523021E+11 32864.18 30-SEP-24:00 32646.88 0.00
October 0.00 0.00 0.954332E+11 0.939438E+11 50037.09 31-OCT-24:00 50037.09 0.00
November 0.00 0.00 0.131632E+12 0.131067E+12 59251.80 02-NOV-16:00 57406.38 0.00
December 0.00 0.00 0.173194E+12 0.172872E+12 76764.68 11-DEC-17:00 74873.81 0.00
                 
Annual Sum or Average 0.00 0.00 0.140175E+13 0.137819E+13       0.00
Minimum of Months 0.00 0.00 0.163281E+11 0.161539E+11 19530.52   18500.76 0.00
Maximum of Months 0.00 0.00 0.208708E+12 0.203221E+12 84473.89   78354.88 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.703677E+09 0.687387E+09 1973.82 20-JAN-17:00 1868.80 0.00
February 0.00 0.00 0.552683E+10 0.550586E+10 4095.19 28-FEB-17:00 4095.19 0.00
March 0.00 0.00 0.133685E+11 0.133033E+11 6990.82 31-MAR-23:20 6990.82 0.00
April 0.00 0.00 0.186427E+11 0.185532E+11 7986.02 17-APR-16:00 7949.96 0.00
May 0.00 0.00 0.551972E+10 0.529231E+10 3847.58 31-MAY-23:20 3755.70 0.00
June 0.00 0.00 0.106704E+11 0.103026E+11 5667.46 30-JUN-24:00 5647.25 0.00
July 0.00 0.00 0.160464E+11 0.155745E+11 7592.84 31-JUL-23:53 7573.86 0.00
August 0.00 0.00 0.209686E+11 0.204201E+11 8556.78 04-AUG-15:00 7936.87 0.00
September 0.00 0.00 0.541425E+10 0.510815E+10 2972.15 07-SEP-16:00 2591.45 0.00
October 0.00 0.00 0.884832E+10 0.870021E+10 4596.63 18-OCT-16:00 4092.98 0.00
November 0.00 0.00 0.119724E+11 0.119165E+11 5955.09 02-NOV-16:00 5770.32 0.00
December 0.00 0.00 0.155396E+11 0.155076E+11 7637.30 13-DEC-16:00 7308.38 0.00
                 
Annual Sum or Average 0.00 0.00 0.133221E+12 0.130872E+12       0.00
Minimum of Months 0.00 0.00 0.703677E+09 0.687387E+09 1973.82   1868.80 0.00
Maximum of Months 0.00 0.00 0.209686E+11 0.204201E+11 8556.78   7949.96 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 70766.49 1538862.95 02-JAN-06:02
February 0.00 0.00 01-FEB-00:10 46340.84 1377556.71 13-FEB-06:01
March 0.00 0.00 01-MAR-00:10 6022.53 845252.55 22-MAR-05:03
April 0.00 0.00 01-APR-00:10 1891.79 594456.89 06-APR-06:10
May 0.00 0.00 01-MAY-00:02 813.76 167072.52 11-MAY-06:10
June 0.00 0.00 01-JUN-00:10 223.30 64231.07 03-JUN-12:00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:03 10.93 23113.13 25-AUG-13:50
September 0.00 0.00 01-SEP-00:02 139.85 101460.30 14-SEP-15:00
October 0.00 0.00 01-OCT-00:10 2998.34 578351.45 26-OCT-05:03
November 0.00 0.00 01-NOV-00:10 11964.10 1127967.28 25-NOV-06:01
December 0.00 0.00 01-DEC-00:10 32871.49 1176088.85 26-DEC-05:01
             
Annual Sum or Average 0.00     14361.93    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   70766.49 1538862.95  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 17348.96 1032955.60 31-JAN-15:50 0.00 0.00 01-JAN-00:05
February 70101.72 1584029.14 28-FEB-14:50 46.17 231201.10 27-FEB-04:02
March 189690.67 1736171.16 30-MAR-14:40 112.39 250873.72 12-MAR-09:02
April 362501.79 1999982.69 17-APR-14:20 38.53 82802.49 13-APR-23:53
May 615987.90 2228548.90 31-MAY-03:02 286.63 564710.83 21-MAY-07:00
June 855749.64 2713352.57 15-JUN-05:03 130.58 293653.70 10-JUN-04:05
July 916874.13 2764532.01 27-JUL-05:02 5.42 89687.98 01-JUL-20:22
August 996407.91 3243385.68 24-AUG-05:04 0.00 0.00 01-AUG-00:03
September 699543.03 2550798.41 05-SEP-05:03 23.28 143386.02 24-SEP-07:50
October 317005.45 1958930.45 18-OCT-04:03 152.84 265117.07 08-OCT-08:32
November 136135.83 1476152.59 02-NOV-13:50 27.86 222313.15 27-NOV-04:02
December 38496.39 1363127.86 12-DEC-14:30 4.21 37582.59 11-DEC-10:05
             
Annual Sum or Average 436786.06     69.33    
Minimum of Months 17348.96 1032955.60   0.00 0.00  
Maximum of Months 996407.91 3243385.68   286.63 564710.83  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 8749.86 718859.87 31-JAN-15:50 0.00 0.00 01-JAN-00:05
February 40605.16 1084421.26 28-FEB-15:00 0.00 0.00 01-FEB-00:10
March 120492.09 2248578.75 30-MAR-05:03 0.00 0.00 01-MAR-00:10
April 257869.10 2711416.62 03-APR-05:03 0.00 0.00 01-APR-00:10
May 468687.18 3638253.25 31-MAY-03:02 0.00 0.00 01-MAY-00:02
June 704072.13 4190160.83 26-JUN-05:02 0.00 0.00 01-JUN-00:10
July 768636.82 4332760.77 27-JUL-05:02 0.00 0.00 01-JUL-00:10
August 858189.61 4327220.44 14-AUG-05:02 0.00 0.00 01-AUG-00:03
September 560482.09 4033142.99 27-SEP-05:03 0.00 0.00 01-SEP-00:02
October 238736.19 3395039.35 18-OCT-04:03 0.00 0.00 01-OCT-00:10
November 80145.71 1896543.43 04-NOV-05:02 0.00 0.00 01-NOV-00:10
December 22338.05 1784218.57 13-DEC-06:03 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 345958.19     0.00    
Minimum of Months 8749.86 718859.87   0.00 0.00  
Maximum of Months 858189.61 4332760.77   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 167227.08 420261.63 31-JAN-15:00 0.00 0.00 01-JAN-00:05
February 340960.61 858129.45 28-FEB-15:00 0.00 0.00 01-FEB-00:10
March 577447.12 1250528.13 30-MAR-16:00 0.00 0.00 01-MAR-00:10
April 890525.47 1523681.86 17-APR-16:00 0.00 0.00 01-APR-00:10
May 437428.51 961360.02 30-MAY-15:00 0.00 0.00 01-MAY-00:02
June 856147.77 1408051.73 06-JUN-15:00 0.00 0.00 01-JUN-00:10
July 1148829.01 1769834.07 08-JUL-16:00 0.00 0.00 01-JUL-00:10
August 1395774.08 1878069.76 01-AUG-16:10 0.00 0.00 01-AUG-00:03
September 518847.75 1036202.57 07-SEP-16:00 0.00 0.00 01-SEP-00:02
October 470672.21 1159829.27 10-OCT-16:00 0.00 0.00 01-OCT-00:10
November 541085.16 1034793.13 05-NOV-16:00 0.00 0.00 01-NOV-00:10
December 619572.40 1182296.85 12-DEC-14:50 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 665946.70     0.00    
Minimum of Months 167227.08 420261.63   0.00 0.00  
Maximum of Months 1395774.08 1878069.76   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 14860.45 49748.26 26-JAN-12:35
February 0.00 0.00 01-FEB-00:10 14973.08 49704.19 02-FEB-12:30
March 0.00 0.00 01-MAR-00:10 15328.52 48924.72 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 13621.54 46281.64 03-APR-11:50
May 0.00 0.00 01-MAY-00:02 13024.40 43153.19 01-MAY-11:30
June 0.00 0.00 01-JUN-00:10 12357.15 39663.05 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 10969.10 36973.10 03-JUL-11:50
August 0.00 0.00 01-AUG-00:03 11839.37 36862.36 31-AUG-12:00
September 0.00 0.00 01-SEP-00:02 11664.40 39124.33 29-SEP-12:00
October 0.00 0.00 01-OCT-00:10 12488.54 42651.66 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 13633.80 46038.58 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 14030.32 48554.06 29-DEC-12:20
             
Annual Sum or Average 0.00     13222.78    
Minimum of Months 0.00 0.00   10969.10 36862.36  
Maximum of Months 0.00 0.00   15328.52 49748.26  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 8740.11 585716.84 31-JAN-15:50 3090.07 178679.33 14-JAN-04:42
February 40713.47 1056961.35 28-FEB-13:20 2500.33 181730.19 01-FEB-07:20
March 119904.10 2726888.03 30-MAR-15:20 1956.64 131491.02 22-MAR-12:20
April 270379.82 2990626.19 04-APR-13:30 1148.08 120470.25 06-APR-18:00
May 600764.79 4261116.14 31-MAY-12:40 141.95 111734.00 09-MAY-20:10
June 1480711.40 5527364.99 23-JUN-12:10 86.67 39239.11 10-JUN-22:30
July 1850441.03 5924986.93 07-JUL-12:20 0.10 1347.87 03-JUL-02:33
August 2264496.55 6176701.56 10-AUG-16:00 0.00 0.00 01-AUG-00:03
September 1001871.01 5467199.45 06-SEP-12:30 40.36 41371.92 18-SEP-06:50
October 335493.07 4840762.12 18-OCT-16:00 966.78 121429.91 06-OCT-05:40
November 80723.28 863281.99 02-NOV-13:50 1907.10 154707.89 22-NOV-11:10
December 21694.83 801044.11 12-DEC-14:30 2328.51 155031.44 18-DEC-16:50
             
Annual Sum or Average 677803.04     1173.92    
Minimum of Months 8740.11 585716.84   0.00 0.00  
Maximum of Months 2264496.55 6176701.56   3090.07 181730.19  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.149601E+11 0.81 9912.16 01-JAN-00:25 1.44
February 0.133392E+11 0.80 9912.16 01-FEB-05:01 1.44
March 0.158923E+11 0.86 9912.16 01-MAR-04:02 1.44
April 0.144668E+11 0.81 9912.16 01-APR-04:03 1.44
May 0.155128E+11 0.83 9912.16 01-MAY-03:02 1.43
June 0.155993E+11 0.86 9912.16 01-JUN-03:02 1.43
July 0.155070E+11 0.83 9912.16 01-JUL-03:02 1.43
August 0.170704E+11 0.91 9912.16 01-AUG-03:02 1.43
September 0.163282E+11 0.91 9912.16 01-SEP-03:02 1.43
October 0.164144E+11 0.89 9912.16 01-OCT-21:50 1.42
November 0.158782E+11 0.89 9912.16 01-NOV-03:02 1.44
December 0.153103E+11 0.83 9912.16 01-DEC-04:02 1.44
           
Annual Sum or Average 0.186279E+12 0.85      
Minimum of Months 0.133392E+11 0.80 9912.16   1.42
Maximum of Months 0.170704E+11 0.91 9912.16   1.44



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.427838E+10 0.32 13436.69 05-JAN-12:00 1.39
February 0.490341E+10 0.37 14934.93 02-FEB-16:40 1.48
March 0.812801E+10 0.48 17903.48 30-MAR-05:03 1.65
April 0.965127E+10 0.55 20968.10 11-APR-15:33 1.83
May 0.935758E+10 0.51 20968.10 15-MAY-13:40 1.82
June 0.121280E+11 0.64 20968.10 02-JUN-15:10 1.82
July 0.134205E+11 0.68 20968.10 03-JUL-05:02 1.82
August 0.159098E+11 0.77 20968.10 08-AUG-05:02 1.82
September 0.947181E+10 0.52 20968.10 05-SEP-05:03 1.82
October 0.808396E+10 0.46 20968.10 18-OCT-05:03 1.82
November 0.712264E+10 0.44 13194.57 06-NOV-16:20 1.37
December 0.633009E+10 0.39 15737.14 13-DEC-06:03 1.52
           
Annual Sum or Average 0.108786E+12 0.51      
Minimum of Months 0.427838E+10 0.32 13194.57   1.37
Maximum of Months 0.159098E+11 0.77 20968.10   1.83



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.334349E+11 0.33 136251.90 05-JAN-11:55 1.50
February 0.358138E+11 0.35 136251.90 03-FEB-13:20 1.50
March 0.539419E+11 0.40 118673.14 18-MAR-05:03 1.37
April 0.635527E+11 0.43 206424.23 12-APR-14:40 1.93
May 0.821157E+11 0.50 206424.23 15-MAY-14:05 1.93
June 0.103021E+12 0.59 206424.23 02-JUN-13:40 1.93
July 0.104345E+12 0.58 206424.23 06-JUL-03:02 1.92
August 0.115055E+12 0.62 206424.23 03-AUG-03:02 1.92
September 0.795036E+11 0.49 206424.23 16-SEP-05:03 1.93
October 0.563773E+11 0.40 118790.91 10-OCT-05:03 1.36
November 0.433129E+11 0.35 110561.55 18-NOV-06:03 1.31
December 0.358618E+11 0.32 138744.17 16-DEC-06:02 1.51
           
Annual Sum or Average 0.806336E+12 0.45      
Minimum of Months 0.334349E+11 0.32 110561.55   1.31
Maximum of Months 0.115055E+12 0.62 206424.23   1.93



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.384657E+10 0.37 4239.51 02-JAN-04:11 0.71
February 0.341155E+10 0.35 6587.75 28-FEB-16:20 0.90
March 0.428847E+10 0.34 12260.70 30-MAR-15:50 1.30
April 0.537923E+10 0.37 20856.69 12-APR-14:30 1.83
May 0.785033E+10 0.45 20856.69 15-MAY-15:10 1.82
June 0.105839E+11 0.56 20856.69 02-JUN-14:20 1.82
July 0.109597E+11 0.56 20856.69 05-JUL-05:03 1.82
August 0.119873E+11 0.60 20856.69 10-AUG-03:02 1.82
September 0.738967E+10 0.44 20856.69 27-SEP-05:03 1.82
October 0.460939E+10 0.34 10902.86 02-OCT-15:20 1.21
November 0.333572E+10 0.30 9060.18 03-NOV-05:03 1.08
December 0.352213E+10 0.33 9060.18 13-DEC-06:03 1.08
           
Annual Sum or Average 0.771640E+11 0.42      
Minimum of Months 0.333572E+10 0.30 4239.51   0.71
Maximum of Months 0.119873E+11 0.60 20856.69   1.83



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.976095E+11 1.40 36443.22 01-JAN-00:05 1.39
February 0.881634E+11 1.40 36443.22 01-FEB-00:10 1.39
March 0.976095E+11 1.39 36443.22 01-MAR-00:10 1.40
April 0.944608E+11 1.39 36443.22 01-APR-00:10 1.39
May 0.976095E+11 1.39 36443.22 01-MAY-00:02 1.39
June 0.944608E+11 1.39 36443.22 01-JUN-00:10 1.39
July 0.976095E+11 1.39 36443.22 01-JUL-00:10 1.39
August 0.976095E+11 1.39 36443.22 01-AUG-00:03 1.39
September 0.944608E+11 1.39 36443.22 01-SEP-00:02 1.39
October 0.976095E+11 1.39 36443.22 01-OCT-00:10 1.39
November 0.944608E+11 1.39 36443.22 01-NOV-00:10 1.40
December 0.976095E+11 1.40 36443.22 01-DEC-00:10 1.39
           
Annual Sum or Average 0.114927E+13 1.39      
Minimum of Months 0.881634E+11 1.39 36443.22   1.39
Maximum of Months 0.976095E+11 1.40 36443.22   1.40



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.146625E+10 0.95 547.44 01-JAN-00:05 0.95
February 0.132436E+10 0.95 547.44 01-FEB-00:10 0.95
March 0.146625E+10 0.95 547.44 01-MAR-00:10 0.95
April 0.141895E+10 0.95 547.44 01-APR-00:10 0.95
May 0.146625E+10 0.95 547.44 01-MAY-00:02 0.95
June 0.141895E+10 0.95 547.44 01-JUN-00:10 0.95
July 0.146625E+10 0.95 547.44 01-JUL-00:10 0.95
August 0.146625E+10 0.94 547.44 01-AUG-00:03 0.95
September 0.141895E+10 0.95 547.44 01-SEP-00:02 0.95
October 0.146625E+10 0.95 547.44 01-OCT-00:10 0.95
November 0.141895E+10 0.95 547.44 01-NOV-00:10 0.95
December 0.146625E+10 0.95 547.44 01-DEC-00:10 0.95
           
Annual Sum or Average 0.172640E+11 0.95      
Minimum of Months 0.132436E+10 0.94 547.44   0.95
Maximum of Months 0.146625E+10 0.95 547.44   0.95



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.139415E+11 0.95 5205.15 01-JAN-00:05 0.95
February 0.125923E+11 0.95 5205.15 01-FEB-00:20 0.95
March 0.139415E+11 0.95 5205.15 01-MAR-00:10 0.95
April 0.134918E+11 0.95 5205.15 01-APR-00:10 0.95
May 0.139415E+11 0.95 5205.15 01-MAY-00:02 0.95
June 0.134918E+11 0.95 5205.15 01-JUN-00:10 0.95
July 0.139415E+11 0.95 5205.15 01-JUL-00:10 0.95
August 0.139415E+11 0.94 5205.15 01-AUG-00:03 0.95
September 0.134918E+11 0.94 5205.15 01-SEP-00:02 0.95
October 0.139415E+11 0.95 5205.15 01-OCT-00:10 0.95
November 0.134918E+11 0.95 5205.15 01-NOV-00:10 0.95
December 0.139415E+11 0.95 5205.15 01-DEC-00:10 0.95
           
Annual Sum or Average 0.164150E+12 0.95      
Minimum of Months 0.125923E+11 0.94 5205.15   0.95
Maximum of Months 0.139415E+11 0.95 5205.15   0.95



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.140993E+10 0.95 526.41 01-JAN-00:05 0.95
February 0.127348E+10 0.95 526.41 01-FEB-00:10 0.95
March 0.140993E+10 0.95 526.41 01-MAR-00:10 0.95
April 0.136444E+10 0.95 526.41 01-APR-00:10 0.95
May 0.140993E+10 0.95 526.41 01-MAY-00:02 0.95
June 0.136444E+10 0.95 526.41 01-JUN-00:20 0.95
July 0.140993E+10 0.95 526.41 01-JUL-00:10 0.95
August 0.140993E+10 0.94 526.41 01-AUG-00:03 0.95
September 0.136444E+10 0.94 526.41 01-SEP-00:02 0.95
October 0.140993E+10 0.95 526.41 01-OCT-00:10 0.95
November 0.136444E+10 0.95 526.41 01-NOV-00:10 0.95
December 0.140993E+10 0.95 526.41 01-DEC-00:10 0.95
           
Annual Sum or Average 0.166007E+11 0.95      
Minimum of Months 0.127348E+10 0.94 526.41   0.95
Maximum of Months 0.140993E+10 0.95 526.41   0.95



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.894547E+09 0.805092E+09 4779.05 09-JAN-06:01 4301.14 4301.14 47.83 10.07
February 0.528670E+09 0.475803E+09 4757.53 13-FEB-06:01 4281.78 4281.78 48.78 9.91
March 70803031.25 63722728.12 3094.32 22-MAR-05:03 2784.88 2784.88 32.67 4.27
April 26664680.90 23998212.81 2397.34 06-APR-06:10 2157.61 2157.61 33.74 3.02
May 15126795.22 13614115.70 764.88 11-MAY-06:10 688.39 688.39 31.20 0.82
June 4444405.82 3999965.24 413.93 03-JUN-12:00 372.53 372.53 43.82 0.43
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 54.52 0.00
August 262381.09 236142.99 203.80 25-AUG-13:50 183.42 183.42 52.90 0.21
September 3208355.79 2887520.21 887.89 14-SEP-15:00 799.10 799.10 54.06 0.96
October 34530718.89 31077647.00 2289.37 26-OCT-05:03 2060.44 2060.44 32.11 2.85
November 0.134971E+09 0.121474E+09 3752.86 25-NOV-06:01 3377.58 3377.58 34.34 5.79
December 0.396765E+09 0.357088E+09 4283.85 18-DEC-07:10 3855.46 3855.46 47.60 7.46
                 
Annual Sum or Average 0.210999E+10 0.189899E+10            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 31.20 0.00
Maximum of Months 0.894547E+09 0.805092E+09 4779.05   4301.14 4301.14 54.52 10.07



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 8051891.26 7246702.13 445.44 31-JAN-15:50 400.89 400.89 8.51 20.70
February 34802627.34 31322364.61 657.91 21-FEB-14:30 592.12 592.12 8.59 25.19
March 0.197703E+09 0.177933E+09 7371.45 30-MAR-05:03 6634.30 6634.30 8.60 75.13
April 0.671035E+09 0.603932E+09 10458.87 03-APR-05:03 9412.98 9412.98 8.69 86.82
May 0.102979E+10 0.926807E+09 15433.93 31-MAY-03:02 13890.54 13890.54 8.16 101.66
June 0.170076E+10 0.153069E+10 25869.23 15-JUN-05:03 23282.31 23282.31 7.82 124.79
July 0.191115E+10 0.172003E+10 25869.23 10-JUL-05:03 23282.31 23282.31 8.00 124.79
August 0.229711E+10 0.206740E+10 25869.23 07-AUG-05:03 23282.31 23282.31 7.65 124.79
September 0.139564E+10 0.125608E+10 25869.23 27-SEP-05:03 23282.31 23282.31 7.65 124.79
October 0.541396E+09 0.487256E+09 13974.54 18-OCT-04:03 12577.08 12577.08 7.97 97.68
November 87243064.44 78518758.00 4132.98 04-NOV-05:02 3719.69 3719.69 8.45 58.76
December 27358267.16 24622440.44 4673.64 13-DEC-06:03 4206.27 4206.27 8.52 61.96
                 
Annual Sum or Average 0.990204E+10 0.891184E+10            
Minimum of Months 8051891.26 7246702.13 445.44   400.89 400.89 7.65 20.70
Maximum of Months 0.229711E+10 0.206740E+10 25869.23   23282.31 23282.31 8.69 124.79



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.559733E+10 0.503759E+10 17805.09 02-JAN-07:20 16024.58 16024.58 8.42 124.79
February 0.850104E+10 0.765094E+10 17805.09 01-FEB-06:03 16024.58 16024.58 8.45 124.79
March 0.167316E+11 0.150585E+11 17805.09 01-MAR-05:10 16024.58 16024.58 8.47 124.79
April 0.246894E+11 0.222205E+11 17805.09 01-APR-04:03 16024.58 16024.58 8.71 124.79
May 0.302243E+11 0.272019E+11 17805.09 01-MAY-00:02 16024.58 16024.58 8.32 124.79
June 0.355676E+11 0.320109E+11 17805.09 01-JUN-03:02 16024.58 16024.58 11.04 124.79
July 0.408045E+11 0.367240E+11 17805.09 01-JUL-00:32 16024.58 16024.58 7.59 124.79
August 0.439856E+11 0.395870E+11 17805.09 01-AUG-00:08 16024.58 16024.58 7.15 124.79
September 0.306741E+11 0.276067E+11 17805.09 01-SEP-00:02 16024.58 16024.58 7.72 124.79
October 0.196379E+11 0.176742E+11 17805.09 01-OCT-12:42 16024.58 16024.58 8.35 124.79
November 0.129854E+11 0.116869E+11 17805.09 01-NOV-05:03 16024.58 16024.58 8.76 124.79
December 0.558157E+10 0.502342E+10 17805.09 01-DEC-04:10 16024.58 16024.58 8.49 124.79
                 
Annual Sum or Average 0.274980E+12 0.247482E+12            
Minimum of Months 0.558157E+10 0.502342E+10 17805.09   16024.58 16024.58 7.15 124.79
Maximum of Months 0.439856E+11 0.395870E+11 17805.09   16024.58 16024.58 11.04 124.79



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.917267E+10 0.825540E+10 3424.68 01-JAN-00:05 3082.21 3082.21 21.57 14.30
February 0.828499E+10 0.745649E+10 3424.68 01-FEB-00:10 3082.21 3082.21 24.31 14.30
March 0.917267E+10 0.825540E+10 3424.68 01-MAR-00:10 3082.21 3082.21 28.10 14.30
April 0.887678E+10 0.798910E+10 3424.68 01-APR-00:10 3082.21 3082.21 30.25 14.30
May 0.917267E+10 0.825540E+10 3424.68 01-MAY-00:02 3082.21 3082.21 22.72 14.30
June 0.887678E+10 0.798910E+10 3424.68 01-JUN-00:10 3082.21 3082.21 30.77 14.30
July 0.917267E+10 0.825540E+10 3424.68 01-JUL-00:10 3082.21 3082.21 36.41 14.30
August 0.917267E+10 0.825540E+10 3424.68 01-AUG-00:03 3082.21 3082.21 43.91 14.30
September 0.887678E+10 0.798910E+10 3424.68 01-SEP-00:02 3082.21 3082.21 27.71 14.30
October 0.917267E+10 0.825540E+10 3424.68 01-OCT-00:10 3082.21 3082.21 26.12 14.30
November 0.887678E+10 0.798910E+10 3424.68 01-NOV-00:10 3082.21 3082.21 27.46 14.30
December 0.917267E+10 0.825540E+10 3424.68 01-DEC-00:10 3082.21 3082.21 29.78 14.30
                 
Annual Sum or Average 0.108001E+12 0.972007E+11            
Minimum of Months 0.828499E+10 0.745649E+10 3424.68   3082.21 3082.21 21.57 14.30
Maximum of Months 0.917267E+10 0.825540E+10 3424.68   3082.21 3082.21 43.91 14.30



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 11967951.72 3590385.52 5.96 01-JAN-06:10 1.79 1.79 55.78 0.44
February 10809762.85 3242928.85 5.96 01-FEB-06:03 1.79 1.79 56.53 0.44
March 11967951.72 3590385.52 5.96 01-MAR-06:03 1.79 1.79 56.46 0.44
April 11581888.76 3474566.63 5.96 01-APR-05:03 1.79 1.79 55.65 0.44
May 11967951.72 3590385.52 5.96 01-MAY-05:03 1.79 1.79 56.57 0.44
June 11581888.76 3474566.63 5.96 01-JUN-05:02 1.79 1.79 57.23 0.44
July 11967951.72 3590385.52 5.96 01-JUL-05:03 1.79 1.79 56.68 0.44
August 11967951.72 3590385.52 5.96 01-AUG-05:03 1.79 1.79 56.34 0.44
September 11581888.76 3474566.63 5.96 01-SEP-05:03 1.79 1.79 57.07 0.44
October 11967951.72 3590385.52 5.96 01-OCT-05:10 1.79 1.79 56.90 0.44
November 11581888.76 3474566.63 5.96 01-NOV-05:03 1.79 1.79 55.84 0.44
December 11967951.72 3590385.52 5.96 01-DEC-06:01 1.79 1.79 55.95 0.44
                 
Annual Sum or Average 0.140913E+09 42273893.99            
Minimum of Months 10809762.85 3242928.85 5.96   1.79 1.79 55.65 0.44
Maximum of Months 11967951.72 3590385.52 5.96   1.79 1.79 57.23 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.690884E+10 0.621796E+10 22004.80 31-JAN-15:50 19804.32 19804.32 23.01 73.21
February 0.105598E+11 0.950382E+10 44002.88 28-FEB-15:40 39602.59 39602.59 22.79 146.41
March 0.209851E+11 0.188866E+11 44093.22 30-MAR-15:20 39683.90 39683.90 25.56 146.41
April 0.321832E+11 0.289649E+11 44109.15 04-APR-13:30 39698.24 39698.24 25.99 146.41
May 0.424019E+11 0.381617E+11 44186.05 31-MAY-12:40 39767.44 39767.44 28.06 146.41
June 0.580121E+11 0.522109E+11 44213.68 12-JUN-11:10 39792.31 39792.31 28.82 146.41
July 0.661093E+11 0.594984E+11 44213.68 05-JUL-08:20 39792.31 39792.31 28.85 146.41
August 0.732560E+11 0.659304E+11 44213.68 01-AUG-09:20 39792.31 39792.31 28.96 146.41
September 0.465997E+11 0.419397E+11 44213.68 05-SEP-15:00 39792.31 39792.31 28.83 146.41
October 0.266767E+11 0.240090E+11 44213.68 18-OCT-15:00 39792.31 39792.31 28.84 146.41
November 0.160172E+11 0.144155E+11 22019.16 02-NOV-13:50 19817.25 19817.25 23.92 73.21
December 0.688471E+10 0.619623E+10 22015.94 12-DEC-14:30 19814.35 19814.35 23.72 73.21
                 
Annual Sum or Average 0.406594E+12 0.365935E+12            
Minimum of Months 0.688471E+10 0.619623E+10 22004.80   19804.32 19804.32 22.79 73.21
Maximum of Months 0.732560E+11 0.659304E+11 44213.68   39792.31 39792.31 28.96 146.41



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 30.99 30.99 70766.49 1538862.95 02-JAN-06:02
February 0.00 0.00 01-FEB-00:10 23.40 23.40 46340.84 1377556.71 13-FEB-06:01
March 0.00 0.00 01-MAR-00:10 25.23 25.23 6022.53 845252.55 22-MAR-05:03
April 0.00 0.00 01-APR-00:10 37.28 37.28 1891.79 594456.89 06-APR-06:10
May 0.00 0.00 01-MAY-00:02 29.55 29.55 813.76 167072.52 11-MAY-06:10
June 0.00 0.00 01-JUN-00:10 56.24 56.24 223.30 64231.07 03-JUN-12:00
July 0.00 0.00 01-JUL-00:10 54.52 54.52 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:03 54.52 54.52 10.93 23113.13 25-AUG-13:50
September 0.00 0.00 01-SEP-00:02 52.28 52.28 139.85 101460.30 14-SEP-15:00
October 0.00 0.00 01-OCT-00:10 47.50 47.50 2998.34 578351.45 26-OCT-05:03
November 0.00 0.00 01-NOV-00:10 25.21 25.21 11964.10 1127967.28 25-NOV-06:01
December 0.00 0.00 01-DEC-00:10 46.09 46.09 32871.49 1176088.85 26-DEC-05:01
                 
Annual Sum or Average 0.00         14361.93    
Minimum of Months 0.00 0.00   23.40 23.40 0.00 0.00  
Maximum of Months 0.00 0.00   56.24 56.24 70766.49 1538862.95  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 17348.96 1032955.60 31-JAN-15:50 9.66 8.66 0.00 0.00 01-JAN-00:05
February 70101.72 1584029.14 28-FEB-14:50 9.98 8.35 46.17 231201.10 27-FEB-04:02
March 189690.67 1736171.16 30-MAR-14:40 10.02 6.70 112.39 250873.72 12-MAR-09:02
April 362501.79 1999982.69 17-APR-14:20 10.52 6.70 38.53 82802.49 13-APR-23:53
May 615987.90 2228548.90 31-MAY-03:02 11.83 7.57 286.63 564710.83 21-MAY-07:00
June 855749.64 2713352.57 15-JUN-05:03 12.57 7.38 130.58 293653.70 10-JUN-04:05
July 916874.13 2764532.01 27-JUL-05:02 12.68 7.39 5.42 89687.98 01-JUL-20:22
August 996407.91 3243385.68 24-AUG-05:04 13.48 7.80 0.00 0.00 01-AUG-00:03
September 699543.03 2550798.41 05-SEP-05:03 12.33 7.45 23.28 143386.02 24-SEP-07:50
October 317005.45 1958930.45 18-OCT-04:03 11.46 7.71 152.84 265117.07 08-OCT-08:32
November 136135.83 1476152.59 02-NOV-13:50 10.03 8.62 27.86 222313.15 27-NOV-04:02
December 38496.39 1363127.86 12-DEC-14:30 9.89 8.58 4.21 37582.59 11-DEC-10:05
                 
Annual Sum or Average 436786.06         69.33    
Minimum of Months 17348.96 1032955.60   9.66 6.70 0.00 0.00  
Maximum of Months 996407.91 3243385.68   13.48 8.66 286.63 564710.83  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 8749.86 718859.87 31-JAN-15:50 15.00 8.64 0.00 0.00 01-JAN-00:05
February 40605.16 1084421.26 28-FEB-15:00 17.79 8.06 0.00 0.00 01-FEB-00:10
March 120492.09 2248578.75 30-MAR-05:03 13.85 8.84 0.00 0.00 01-MAR-00:10
April 257869.10 2711416.62 03-APR-05:03 14.16 8.92 0.00 0.00 01-APR-00:10
May 468687.18 3638253.25 31-MAY-03:02 15.25 7.81 0.00 0.00 01-MAY-00:02
June 704072.13 4190160.83 26-JUN-05:02 14.85 7.60 0.00 0.00 01-JUN-00:10
July 768636.82 4332760.77 27-JUL-05:02 15.00 7.87 0.00 0.00 01-JUL-00:10
August 858189.61 4327220.44 14-AUG-05:02 14.99 7.69 0.00 0.00 01-AUG-00:03
September 560482.09 4033142.99 27-SEP-05:03 14.42 7.35 0.00 0.00 01-SEP-00:02
October 238736.19 3395039.35 18-OCT-04:03 15.01 7.76 0.00 0.00 01-OCT-00:10
November 80145.71 1896543.43 04-NOV-05:02 14.41 8.75 0.00 0.00 01-NOV-00:10
December 22338.05 1784218.57 13-DEC-06:03 13.58 8.82 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 345958.19         0.00    
Minimum of Months 8749.86 718859.87   13.58 7.35 0.00 0.00  
Maximum of Months 858189.61 4332760.77   17.79 8.92 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 167227.08 420261.63 31-JAN-15:00 26.75 22.84 0.00 0.00 01-JAN-00:05
February 340960.61 858129.45 28-FEB-15:00 35.38 28.23 0.00 0.00 01-FEB-00:10
March 577447.12 1250528.13 30-MAR-16:00 42.99 32.57 0.00 0.00 01-MAR-00:10
April 890525.47 1523681.86 17-APR-16:00 48.23 35.00 0.00 0.00 01-APR-00:10
May 437428.51 961360.02 30-MAY-15:00 37.39 32.72 0.00 0.00 01-MAY-00:02
June 856147.77 1408051.73 06-JUN-15:00 46.02 38.06 0.00 0.00 01-JUN-00:10
July 1148829.01 1769834.07 08-JUL-16:00 52.91 41.84 0.00 0.00 01-JUL-00:10
August 1395774.08 1878069.76 01-AUG-16:10 54.96 41.35 0.00 0.00 01-AUG-00:03
September 518847.75 1036202.57 07-SEP-16:00 38.85 33.93 0.00 0.00 01-SEP-00:02
October 470672.21 1159829.27 10-OCT-16:00 41.24 33.52 0.00 0.00 01-OCT-00:10
November 541085.16 1034793.13 05-NOV-16:00 38.82 28.91 0.00 0.00 01-NOV-00:10
December 619572.40 1182296.85 12-DEC-14:50 41.68 28.72 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 665946.70         0.00    
Minimum of Months 167227.08 420261.63   26.75 22.84 0.00 0.00  
Maximum of Months 1395774.08 1878069.76   54.96 41.84 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 56.88 56.88 14860.45 49748.26 26-JAN-12:35
February 0.00 0.00 01-FEB-00:10 57.11 57.11 14973.08 49704.19 02-FEB-12:30
March 0.00 0.00 01-MAR-00:10 57.04 57.04 15328.52 48924.72 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 56.24 56.24 13621.54 46281.64 03-APR-11:50
May 0.00 0.00 01-MAY-00:02 57.28 57.28 13024.40 43153.19 01-MAY-11:30
June 0.00 0.00 01-JUN-00:10 57.61 57.61 12357.15 39663.05 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 57.08 57.08 10969.10 36973.10 03-JUL-11:50
August 0.00 0.00 01-AUG-00:03 56.76 56.76 11839.37 36862.36 31-AUG-12:00
September 0.00 0.00 01-SEP-00:02 57.46 57.46 11664.40 39124.33 29-SEP-12:00
October 0.00 0.00 01-OCT-00:10 57.67 57.67 12488.54 42651.66 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 56.36 56.36 13633.80 46038.58 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 56.41 56.41 14030.32 48554.06 29-DEC-12:20
                 
Annual Sum or Average 0.00         13222.78    
Minimum of Months 0.00 0.00   56.24 56.24 10969.10 36862.36  
Maximum of Months 0.00 0.00   57.67 57.67 15328.52 49748.26  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 8740.11 585716.84 31-JAN-15:50 23.01 21.10 3090.07 178679.33 14-JAN-04:42
February 40713.47 1056961.35 28-FEB-13:20 24.55 21.10 2500.33 181730.19 01-FEB-07:20
March 119904.10 2726888.03 30-MAR-15:20 25.56 21.74 1956.64 131491.02 22-MAR-12:20
April 270379.82 2990626.19 04-APR-13:30 25.99 22.98 1148.08 120470.25 06-APR-18:00
May 600764.79 4261116.14 31-MAY-12:40 28.06 24.90 141.95 111734.00 09-MAY-20:10
June 1480711.40 5527364.99 23-JUN-12:10 30.13 26.92 86.67 39239.11 10-JUN-22:30
July 1850441.03 5924986.93 07-JUL-12:20 30.78 27.46 0.10 1347.87 03-JUL-02:33
August 2264496.55 6176701.56 10-AUG-16:00 31.19 27.75 0.00 0.00 01-AUG-00:03
September 1001871.01 5467199.45 06-SEP-12:30 30.03 26.63 40.36 41371.92 18-SEP-06:50
October 335493.07 4840762.12 18-OCT-16:00 29.01 25.91 966.78 121429.91 06-OCT-05:40
November 80723.28 863281.99 02-NOV-13:50 23.92 21.10 1907.10 154707.89 22-NOV-11:10
December 21694.83 801044.11 12-DEC-14:30 23.72 21.10 2328.51 155031.44 18-DEC-16:50
                 
Annual Sum or Average 677803.04         1173.92    
Minimum of Months 8740.11 585716.84   23.01 21.10 0.00 0.00  
Maximum of Months 2264496.55 6176701.56   31.19 27.75 3090.07 181730.19  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.348422E+10 0.00 0.198280E+10 0.427838E+10 0.00 0.00
February 0.161148E+10 0.00 0.848749E+10 0.490341E+10 0.00 0.00
March 0.194467E+09 0.00 0.270838E+11 0.812801E+10 0.00 0.00
April 0.295920E+09 0.00 0.593506E+11 0.965127E+10 0.00 0.00
May 0.171670E+09 0.00 0.948286E+11 0.935758E+10 0.00 0.00
June 46717691.54 0.00 0.149290E+12 0.121280E+11 0.00 0.00
July 0.00 0.00 0.177982E+12 0.134205E+11 0.00 0.00
August 1509395.83 0.00 0.207460E+12 0.159098E+11 0.00 0.00
September 29117668.01 0.00 0.113116E+12 0.947181E+10 0.00 0.00
October 97739137.55 0.00 0.517056E+11 0.808396E+10 0.00 0.00
November 0.392904E+09 0.00 0.183662E+11 0.712264E+10 0.00 0.00
December 0.934958E+09 0.00 0.569561E+10 0.633009E+10 0.00 0.00
             
Annual Sum or Average 0.726070E+10 0.00 0.915349E+12 0.108786E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.198280E+10 0.427838E+10 0.00 0.00
Maximum of Months 0.348422E+10 0.00 0.207460E+12 0.159098E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.153541E+12 0.00 0.144249E+11 0.334349E+11 0.00 0.00
February 0.920222E+11 0.00 0.633944E+11 0.358138E+11 0.00 0.00
March 0.127406E+11 0.00 0.201860E+12 0.539419E+11 0.00 0.00
April 0.370097E+10 0.00 0.429048E+12 0.635527E+11 0.00 0.00
May 0.174408E+10 0.00 0.830103E+12 0.821157E+11 0.00 0.00
June 0.514811E+09 0.00 0.126985E+13 0.103021E+12 0.00 0.00
July 0.00 0.00 0.144371E+13 0.104345E+12 0.00 0.00
August 30192064.67 0.00 0.162546E+13 0.115055E+12 0.00 0.00
September 0.334371E+09 0.00 0.974399E+12 0.795036E+11 0.00 0.00
October 0.595775E+10 0.00 0.403308E+12 0.563773E+11 0.00 0.00
November 0.242797E+11 0.00 0.125975E+12 0.433129E+11 0.00 0.00
December 0.692005E+11 0.00 0.349632E+11 0.358618E+11 0.00 0.00
             
Annual Sum or Average 0.364066E+12 0.00 0.741648E+13 0.806336E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.144249E+11 0.334349E+11 0.00 0.00
Maximum of Months 0.153541E+12 0.00 0.162546E+13 0.115055E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.343036E+11 0.00 0.133325E+10 0.384657E+10 0.00 0.00
February 0.194927E+11 0.00 0.549883E+10 0.341155E+10 0.00 0.00
March 0.329092E+10 0.00 0.194692E+11 0.428847E+10 0.00 0.00
April 0.993147E+09 0.00 0.440849E+11 0.537923E+10 0.00 0.00
May 0.146769E+09 0.00 0.897048E+11 0.785033E+10 0.00 0.00
June 33053327.54 0.00 0.140246E+12 0.105839E+11 0.00 0.00
July 0.00 0.00 0.159566E+12 0.109597E+11 0.00 0.00
August 9937221.65 0.00 0.178030E+12 0.119873E+11 0.00 0.00
September 29083842.77 0.00 0.100559E+12 0.738967E+10 0.00 0.00
October 0.216332E+10 0.00 0.394586E+11 0.460939E+10 0.00 0.00
November 0.649711E+10 0.00 0.107436E+11 0.333572E+10 0.00 0.00
December 0.188372E+11 0.00 0.298258E+10 0.352213E+10 0.00 0.00
             
Annual Sum or Average 0.857968E+11 0.00 0.791677E+12 0.771640E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.133325E+10 0.333572E+10 0.00 0.00
Maximum of Months 0.343036E+11 0.00 0.178030E+12 0.119873E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.654960E+09 0.149601E+11 0.00 0.00
February 0.00 0.00 0.429000E+10 0.133392E+11 0.00 0.00
March 0.00 0.00 0.133790E+11 0.158923E+11 0.00 0.00
April 0.00 0.00 0.281709E+11 0.144668E+11 0.00 0.00
May 0.00 0.00 0.509565E+11 0.155128E+11 0.00 0.00
June 0.00 0.00 0.871638E+11 0.155993E+11 0.00 0.00
July 0.00 0.00 0.997131E+11 0.155070E+11 0.00 0.00
August 0.00 0.00 0.119852E+12 0.170704E+11 0.00 0.00
September 0.00 0.00 0.740994E+11 0.163282E+11 0.00 0.00
October 0.00 0.00 0.326725E+11 0.164144E+11 0.00 0.00
November 0.00 0.00 0.105825E+11 0.158782E+11 0.00 0.00
December 0.00 0.00 0.304282E+10 0.153103E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.524577E+12 0.186279E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.654960E+09 0.133392E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.119852E+12 0.170704E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.404646E+12 0.181903E+12 0.00 0.97
February 0.00 0.00 0.639183E+12 0.215231E+12 0.00 0.68
March 0.00 0.00 0.102037E+13 0.299463E+12 0.00 0.35
April 0.00 0.00 0.129836E+13 0.362296E+12 0.00 0.11
May 0.00 0.00 0.438922E+12 0.195826E+12 0.00 0.02
June 0.00 0.00 0.754315E+12 0.275965E+12 0.00 0.01
July 0.00 0.00 0.111372E+13 0.371066E+12 0.00 0.00
August 0.00 0.00 0.143019E+13 0.447145E+12 0.00 0.00
September 0.00 0.00 0.438947E+12 0.195645E+12 0.00 0.00
October 0.00 0.00 0.735301E+12 0.248744E+12 0.00 0.02
November 0.00 0.00 0.989775E+12 0.287228E+12 0.00 0.45
December 0.00 0.00 0.130454E+13 0.338827E+12 0.00 0.72
             
Annual Sum or Average 0.00 0.00 0.105683E+14 0.341934E+13 0.00 3.33
Minimum of Months 0.00 0.00 0.404646E+12 0.181903E+12 0.00 0.00
Maximum of Months 0.00 0.00 0.143019E+13 0.447145E+12 0.00 0.97



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.491832E+10 0.250458E+10 0.00 0.00
February 0.00 0.00 0.109099E+11 0.350729E+10 0.00 0.00
March 0.00 0.00 0.194957E+11 0.530862E+10 0.00 0.00
April 0.00 0.00 0.254919E+11 0.663078E+10 0.00 0.00
May 0.00 0.00 0.789224E+10 0.321063E+10 0.00 0.00
June 0.00 0.00 0.146633E+11 0.489294E+10 0.00 0.00
July 0.00 0.00 0.220679E+11 0.679694E+10 0.00 0.00
August 0.00 0.00 0.289697E+11 0.850773E+10 0.00 0.00
September 0.00 0.00 0.793216E+10 0.322310E+10 0.00 0.00
October 0.00 0.00 0.136019E+11 0.423215E+10 0.00 0.00
November 0.00 0.00 0.186838E+11 0.505368E+10 0.00 0.00
December 0.00 0.00 0.248177E+11 0.607866E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.199444E+12 0.599471E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.491832E+10 0.250458E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.289697E+11 0.850773E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.209589E+11 0.185723E+11 0.00 0.00
February 0.00 0.00 0.850732E+11 0.298687E+11 0.00 0.00
March 0.00 0.00 0.176434E+12 0.489334E+11 0.00 0.00
April 0.00 0.00 0.239196E+12 0.625222E+11 0.00 0.00
May 0.00 0.00 0.719954E+11 0.299253E+11 0.00 0.00
June 0.00 0.00 0.139063E+12 0.464590E+11 0.00 0.00
July 0.00 0.00 0.210382E+12 0.647571E+11 0.00 0.00
August 0.00 0.00 0.275718E+12 0.809515E+11 0.00 0.00
September 0.00 0.00 0.717880E+11 0.298996E+11 0.00 0.00
October 0.00 0.00 0.120042E+12 0.385499E+11 0.00 0.00
November 0.00 0.00 0.163777E+12 0.456368E+11 0.00 0.00
December 0.00 0.00 0.213329E+12 0.540762E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.178776E+13 0.550152E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.209589E+11 0.185723E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.275718E+12 0.809515E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.904210E+09 0.161046E+10 0.00 0.00
February 0.00 0.00 0.695460E+10 0.270125E+10 0.00 0.00
March 0.00 0.00 0.167064E+11 0.474787E+10 0.00 0.00
April 0.00 0.00 0.234774E+11 0.619923E+10 0.00 0.00
May 0.00 0.00 0.710425E+10 0.299446E+10 0.00 0.00
June 0.00 0.00 0.139927E+11 0.468671E+10 0.00 0.00
July 0.00 0.00 0.211644E+11 0.652786E+10 0.00 0.00
August 0.00 0.00 0.277098E+11 0.815108E+10 0.00 0.00
September 0.00 0.00 0.702885E+10 0.297904E+10 0.00 0.00
October 0.00 0.00 0.111566E+11 0.371820E+10 0.00 0.00
November 0.00 0.00 0.149326E+11 0.432464E+10 0.00 0.00
December 0.00 0.00 0.191942E+11 0.506452E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.170326E+12 0.537053E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.904210E+09 0.161046E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.277098E+11 0.815108E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.427838E+10 0.198280E+10 0.348422E+10 0.245134E+11 0.00 0.00 0.00 0.00
February 0.490341E+10 0.848749E+10 0.161148E+10 0.124114E+11 0.00 0.00 0.00 0.00
March 0.812801E+10 0.270838E+11 0.194467E+09 0.144332E+10 0.102544E+09 0.00 0.00 0.00
April 0.965127E+10 0.593506E+11 0.295920E+09 0.367470E+09 0.508830E+09 0.00 0.00 0.00
May 0.935758E+10 0.948286E+11 0.171670E+09 24039215.86 0.356452E+10 0.00 0.00 0.00
June 0.121280E+11 0.149290E+12 46717691.54 0.00 0.216615E+11 0.00 0.00 0.00
July 0.134205E+11 0.177982E+12 0.00 0.00 0.296588E+11 0.00 0.00 0.00
August 0.159098E+11 0.207460E+12 1509395.83 0.00 0.370630E+11 0.00 0.00 0.00
September 0.947181E+10 0.113116E+12 29117668.01 0.00 0.101394E+11 0.00 0.00 0.00
October 0.808396E+10 0.517056E+11 97739137.55 0.577703E+09 0.196621E+10 0.00 0.00 0.00
November 0.712264E+10 0.183662E+11 0.392904E+09 0.255648E+10 0.00 0.00 0.00 0.00
December 0.633009E+10 0.569561E+10 0.934958E+09 0.618246E+10 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.108786E+12 0.915349E+12 0.726070E+10 0.480762E+11 0.104665E+12 0.00 0.00 0.00
Minimum of Months 0.427838E+10 0.198280E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.159098E+11 0.207460E+12 0.348422E+10 0.245134E+11 0.370630E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.334349E+11 0.144251E+11 0.153541E+12 0.335979E+12 0.00 0.00 0.00 0.00
February 0.358138E+11 0.633944E+11 0.920222E+11 0.176997E+12 0.00 0.00 0.00 0.00
March 0.539419E+11 0.201860E+12 0.127406E+11 0.336610E+11 0.131049E+10 0.00 0.00 0.00
April 0.635527E+11 0.429048E+12 0.370097E+10 0.104265E+11 0.504137E+10 0.00 0.00 0.00
May 0.821157E+11 0.830103E+12 0.174408E+10 0.657557E+09 0.360079E+11 0.00 0.00 0.00
June 0.103021E+12 0.126985E+13 0.514811E+09 0.00 0.214824E+12 0.00 0.00 0.00
July 0.104345E+12 0.144371E+13 0.00 0.00 0.291620E+12 0.00 0.00 0.00
August 0.115055E+12 0.162546E+13 30192064.67 0.00 0.359739E+12 0.00 0.00 0.00
September 0.795036E+11 0.974399E+12 0.334371E+09 0.00 0.102623E+12 0.00 0.00 0.00
October 0.563773E+11 0.403308E+12 0.595775E+10 0.181913E+11 0.198782E+11 0.00 0.00 0.00
November 0.433129E+11 0.125975E+12 0.242797E+11 0.616430E+11 0.00 0.00 0.00 0.00
December 0.358618E+11 0.349632E+11 0.692005E+11 0.144933E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.806336E+12 0.741648E+13 0.364066E+12 0.782488E+12 0.103104E+13 0.00 0.00 0.00
Minimum of Months 0.334349E+11 0.144251E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.115055E+12 0.162546E+13 0.153541E+12 0.335979E+12 0.359739E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.384657E+10 0.133325E+10 0.343036E+11 0.367266E+11 0.00 0.00 0.00 0.00
February 0.341155E+10 0.549883E+10 0.194927E+11 0.209871E+11 0.00 0.00 0.00 0.00
March 0.428847E+10 0.194692E+11 0.329092E+10 0.605439E+10 85578573.62 0.00 0.00 0.00
April 0.537923E+10 0.440849E+11 0.993147E+09 0.163417E+10 0.259226E+09 0.00 0.00 0.00
May 0.785033E+10 0.897048E+11 0.146769E+09 0.127897E+09 0.274562E+10 0.00 0.00 0.00
June 0.105839E+11 0.140246E+12 33053327.54 1479476.81 0.201217E+11 0.00 0.00 0.00
July 0.109597E+11 0.159566E+12 0.00 0.00 0.280225E+11 0.00 0.00 0.00
August 0.119873E+11 0.178030E+12 9937221.65 0.00 0.347742E+11 0.00 0.00 0.00
September 0.738967E+10 0.100559E+12 29083842.77 4118484.68 0.960337E+10 0.00 0.00 0.00
October 0.460939E+10 0.394586E+11 0.216332E+10 0.326652E+10 0.145475E+10 0.00 0.00 0.00
November 0.333572E+10 0.107436E+11 0.649711E+10 0.958046E+10 0.00 0.00 0.00 0.00
December 0.352213E+10 0.298258E+10 0.188372E+11 0.173364E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.771640E+11 0.791677E+12 0.857968E+11 0.957192E+11 0.970670E+11 0.00 0.00 0.00
Minimum of Months 0.333572E+10 0.133325E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.119873E+11 0.178030E+12 0.343036E+11 0.367266E+11 0.347742E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.149601E+11 0.654960E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133392E+11 0.429000E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.158923E+11 0.133790E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.144668E+11 0.281709E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.155128E+11 0.509565E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.155993E+11 0.871638E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.155070E+11 0.997131E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.170704E+11 0.119852E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.163282E+11 0.740994E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.164144E+11 0.326725E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.158782E+11 0.105825E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153103E+11 0.304282E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.186279E+12 0.524577E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133392E+11 0.654960E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.170704E+11 0.119852E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.976095E+11 0.322966E+12 0.00 0.00 0.00 0.260185E+10 0.00 0.00
February 0.881634E+11 0.513952E+12 0.00 0.00 0.00 0.182752E+10 0.00 0.00
March 0.976095E+11 0.819449E+12 0.00 0.00 0.00 0.930679E+09 0.00 0.00
April 0.944608E+11 0.103082E+13 0.00 0.00 0.00 0.294609E+09 0.00 0.00
May 0.976095E+11 0.340757E+12 0.00 0.00 0.00 51866632.71 0.00 0.00
June 0.944608E+11 0.572826E+12 0.00 0.00 0.00 14555348.00 0.00 0.00
July 0.976095E+11 0.840267E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.976095E+11 0.108066E+13 0.00 0.00 0.00 372297.87 0.00 0.00
September 0.944608E+11 0.337763E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.976095E+11 0.584208E+12 0.00 0.00 0.00 40724997.87 0.00 0.00
November 0.944608E+11 0.798227E+12 0.00 0.00 0.00 0.121317E+10 0.00 0.00
December 0.976095E+11 0.106526E+13 0.00 0.00 0.00 0.193011E+10 0.00 0.00
                 
Annual Sum or Average 0.114927E+13 0.830716E+13 0.00 0.00 0.00 0.890546E+10 0.00 0.00
Minimum of Months 0.881634E+11 0.322966E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.976095E+11 0.108066E+13 0.00 0.00 0.00 0.260185E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.146625E+10 0.388000E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.132436E+10 0.872691E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.146625E+10 0.156533E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.141895E+10 0.202801E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.146625E+10 0.614787E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.141895E+10 0.111893E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.146625E+10 0.167372E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.146625E+10 0.219282E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.141895E+10 0.612801E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.146625E+10 0.108360E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.141895E+10 0.150491E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.146625E+10 0.202053E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.172640E+11 0.156761E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.132436E+10 0.388000E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.146625E+10 0.219282E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.139415E+11 0.163281E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.125923E+11 0.677968E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.139415E+11 0.141442E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134918E+11 0.190165E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139415E+11 0.560115E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134918E+11 0.106096E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.139415E+11 0.159566E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.139415E+11 0.208708E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.134918E+11 0.553801E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.139415E+11 0.954332E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.134918E+11 0.131632E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.139415E+11 0.173194E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.164150E+12 0.140175E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.125923E+11 0.163281E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.139415E+11 0.208708E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.140993E+10 0.703677E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.127348E+10 0.552683E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.140993E+10 0.133685E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.136444E+10 0.186427E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140993E+10 0.551972E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.136444E+10 0.106704E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.140993E+10 0.160464E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.140993E+10 0.209686E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.136444E+10 0.541425E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.140993E+10 0.884832E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.136444E+10 0.119724E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140993E+10 0.155396E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.166007E+11 0.133221E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.127348E+10 0.703677E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140993E+10 0.209686E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.427838E+10 0.348422E+10 0.198280E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.490341E+10 0.161148E+10 0.848749E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.812801E+10 0.194467E+09 0.270838E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.965127E+10 0.295920E+09 0.593506E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.935758E+10 0.171670E+09 0.948286E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.121280E+11 46717691.54 0.149290E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.134205E+11 0.00 0.177982E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.159098E+11 1509395.83 0.207460E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.947181E+10 29117668.01 0.113116E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.808396E+10 97739137.55 0.517056E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.712264E+10 0.392904E+09 0.183662E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.633009E+10 0.934958E+09 0.569561E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.108786E+12 0.726070E+10 0.915349E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427838E+10 0.00 0.198280E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.159098E+11 0.348422E+10 0.207460E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.334349E+11 0.153541E+12 0.144249E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.358138E+11 0.920222E+11 0.633944E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.539419E+11 0.127406E+11 0.201860E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.635527E+11 0.370097E+10 0.429048E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.821157E+11 0.174408E+10 0.830103E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.103021E+12 0.514811E+09 0.126985E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.104345E+12 0.00 0.144371E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.115055E+12 30192064.67 0.162546E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.795036E+11 0.334371E+09 0.974399E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.563773E+11 0.595775E+10 0.403308E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.433129E+11 0.242797E+11 0.125975E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.358618E+11 0.692005E+11 0.349632E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.806336E+12 0.364066E+12 0.741648E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.334349E+11 0.00 0.144249E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.115055E+12 0.153541E+12 0.162546E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.384657E+10 0.343036E+11 0.133325E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.341155E+10 0.194927E+11 0.549883E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.428847E+10 0.329092E+10 0.194692E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.537923E+10 0.993147E+09 0.440849E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.785033E+10 0.146769E+09 0.897048E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.105839E+11 33053327.54 0.140246E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.109597E+11 0.00 0.159566E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.119873E+11 9937221.65 0.178030E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.738967E+10 29083842.77 0.100559E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.460939E+10 0.216332E+10 0.394586E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.333572E+10 0.649711E+10 0.107436E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.352213E+10 0.188372E+11 0.298258E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.771640E+11 0.857968E+11 0.791677E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.333572E+10 0.00 0.133325E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.119873E+11 0.343036E+11 0.178030E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.149601E+11 0.00 0.654960E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133392E+11 0.00 0.429000E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.158923E+11 0.00 0.133790E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.144668E+11 0.00 0.281709E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.155128E+11 0.00 0.509565E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.155993E+11 0.00 0.871638E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.155070E+11 0.00 0.997131E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.170704E+11 0.00 0.119852E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.163282E+11 0.00 0.740994E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.164144E+11 0.00 0.326725E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.158782E+11 0.00 0.105825E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153103E+11 0.00 0.304282E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.186279E+12 0.00 0.524577E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133392E+11 0.00 0.654960E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.170704E+11 0.00 0.119852E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.976095E+11 0.00 0.404646E+12 0.00 0.816798E+11 0.00 0.00 0.00 0.261356E+10 0.00 0.00 0.00
February 0.881634E+11 0.00 0.639183E+12 0.00 0.125231E+12 0.00 0.00 0.00 0.183575E+10 0.00 0.00 0.00
March 0.976095E+11 0.00 0.102037E+13 0.00 0.200918E+12 0.00 0.00 0.00 0.934868E+09 0.00 0.00 0.00
April 0.944608E+11 0.00 0.129836E+13 0.00 0.267539E+12 0.00 0.00 0.00 0.295935E+09 0.00 0.00 0.00
May 0.976095E+11 0.00 0.438922E+12 0.00 0.981646E+11 0.00 0.00 0.00 52100105.45 0.00 0.00 0.00
June 0.944608E+11 0.00 0.754315E+12 0.00 0.181490E+12 0.00 0.00 0.00 14620867.52 0.00 0.00 0.00
July 0.976095E+11 0.00 0.111372E+13 0.00 0.273456E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.976095E+11 0.00 0.143019E+13 0.00 0.349535E+12 0.00 0.00 0.00 373973.73 0.00 0.00 0.00
September 0.944608E+11 0.00 0.438947E+12 0.00 0.101184E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.976095E+11 0.00 0.735301E+12 0.00 0.151093E+12 0.00 0.00 0.00 40908317.60 0.00 0.00 0.00
November 0.944608E+11 0.00 0.989775E+12 0.00 0.191548E+12 0.00 0.00 0.00 0.121863E+10 0.00 0.00 0.00
December 0.976095E+11 0.00 0.130454E+13 0.00 0.239279E+12 0.00 0.00 0.00 0.193880E+10 0.00 0.00 0.00
                         
Annual Sum or Average 0.114927E+13 0.00 0.105683E+14 0.00 0.226112E+13 0.00 0.00 0.00 0.894555E+10 0.00 0.00 0.00
Minimum of Months 0.881634E+11 0.00 0.404646E+12 0.00 0.816798E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.976095E+11 0.00 0.143019E+13 0.00 0.349535E+12 0.00 0.00 0.00 0.261356E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.146625E+10 0.00 0.491832E+10 0.00 0.103832E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.132436E+10 0.00 0.109099E+11 0.00 0.218294E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.146625E+10 0.00 0.194957E+11 0.00 0.384236E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.141895E+10 0.00 0.254919E+11 0.00 0.521182E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.146625E+10 0.00 0.789224E+10 0.00 0.174437E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.141895E+10 0.00 0.146633E+11 0.00 0.347399E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.146625E+10 0.00 0.220679E+11 0.00 0.533069E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.146625E+10 0.00 0.289697E+11 0.00 0.704147E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.141895E+10 0.00 0.793216E+10 0.00 0.180415E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.146625E+10 0.00 0.136019E+11 0.00 0.276590E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.141895E+10 0.00 0.186838E+11 0.00 0.363472E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.146625E+10 0.00 0.248177E+11 0.00 0.461241E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.172640E+11 0.00 0.199444E+12 0.00 0.426831E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.132436E+10 0.00 0.491832E+10 0.00 0.103832E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.146625E+10 0.00 0.289697E+11 0.00 0.704147E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.139415E+11 0.00 0.209589E+11 0.00 0.463079E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.125923E+11 0.00 0.850732E+11 0.00 0.172764E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.139415E+11 0.00 0.176434E+12 0.00 0.349919E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134918E+11 0.00 0.239196E+12 0.00 0.490304E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139415E+11 0.00 0.719954E+11 0.00 0.159838E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134918E+11 0.00 0.139063E+12 0.00 0.329672E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.139415E+11 0.00 0.210382E+12 0.00 0.508156E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.139415E+11 0.00 0.275718E+12 0.00 0.670100E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.134918E+11 0.00 0.717880E+11 0.00 0.164078E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.139415E+11 0.00 0.120042E+12 0.00 0.246084E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.134918E+11 0.00 0.163777E+12 0.00 0.321450E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.139415E+11 0.00 0.213329E+12 0.00 0.401347E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.164150E+12 0.00 0.178776E+13 0.00 0.386002E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.125923E+11 0.00 0.209589E+11 0.00 0.463079E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.139415E+11 0.00 0.275718E+12 0.00 0.670100E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.140993E+10 0.00 0.904210E+09 0.00 0.200533E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.127348E+10 0.00 0.695460E+10 0.00 0.142777E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.140993E+10 0.00 0.167064E+11 0.00 0.333794E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.136444E+10 0.00 0.234774E+11 0.00 0.483479E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140993E+10 0.00 0.710425E+10 0.00 0.158454E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.136444E+10 0.00 0.139927E+11 0.00 0.332227E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.140993E+10 0.00 0.211644E+11 0.00 0.511794E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.140993E+10 0.00 0.277098E+11 0.00 0.674115E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.136444E+10 0.00 0.702885E+10 0.00 0.161460E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.140993E+10 0.00 0.111566E+11 0.00 0.230827E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.136444E+10 0.00 0.149326E+11 0.00 0.296019E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140993E+10 0.00 0.191942E+11 0.00 0.365460E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.166007E+11 0.00 0.170326E+12 0.00 0.371046E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.127348E+10 0.00 0.904210E+09 0.00 0.200533E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140993E+10 0.00 0.277098E+11 0.00 0.674115E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.964459E+09 0.00 0.00 0.103496E+09 0.00 0.00 0.660024E+11 0.00 0.65
February 0.348535E+09 376705.72 0.00 92720109.15 0.00 0.00 0.579710E+11 0.00 0.86
March 0.167421E+09 99922217.53 0.00 0.107283E+09 759274.81 0.00 0.643287E+11 0.00 1.24
April 77028629.23 0.300567E+09 0.00 85570379.06 10637641.09 0.00 0.422279E+11 0.00 1.21
May 73195358.28 0.223218E+10 0.00 75782051.43 20519042.49 0.00 0.277049E+11 0.00 1.21
June 33286171.28 0.144792E+11 0.00 33619924.80 71178069.68 0.00 0.789676E+10 0.00 0.67
July 29880214.49 0.213171E+11 0.00 18717267.37 0.231179E+09 0.00 0.319297E+10 0.00 0.47
August 495235.85 0.284617E+11 0.00 4663354.71 0.188375E+09 0.00 0.819166E+09 0.00 0.39
September 0.149373E+09 0.876050E+10 0.00 65134403.83 72729544.41 0.00 0.191518E+11 0.00 0.99
October 0.240347E+09 0.247936E+10 0.00 0.109740E+09 3501.08 0.00 0.561803E+11 0.00 1.18
November 0.300381E+09 3185699.29 0.00 0.132772E+09 0.00 0.00 0.728872E+11 0.00 1.24
December 0.573106E+09 0.00 0.00 0.128843E+09 0.00 0.00 0.744206E+11 0.00 0.92
                   
Annual Sum or Average 0.295751E+10 0.781341E+11 0.00 0.958340E+09 0.595381E+09 0.00 0.492784E+12 0.00 0.92
Minimum of Months 495235.85 0.00 0.00 4663354.71 0.00 0.00 0.819166E+09 0.00 0.39
Maximum of Months 0.964459E+09 0.284617E+11 0.00 0.132772E+09 0.231179E+09 0.00 0.744206E+11 0.00 1.24



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.385410E+10 0.00 0.00 62026825.19 0.00 0.00 0.389130E+11 0.00 0.51
February 0.275207E+10 0.00 0.00 69355541.29 0.00 0.00 0.394672E+11 0.00 0.66
March 0.432565E+10 55368609.74 0.00 97820548.38 210084.50 0.00 0.507104E+11 0.00 0.97
April 0.610130E+10 0.355640E+09 0.00 83302952.38 9770740.39 0.00 0.341051E+11 0.00 1.04
May 0.190543E+10 0.206444E+10 0.00 56431279.35 39259059.33 0.00 0.156341E+11 0.00 0.82
June 0.131891E+10 0.983425E+10 0.00 18324464.71 0.103187E+09 0.00 0.475622E+10 0.00 0.58
July 0.236921E+09 0.140686E+11 0.00 3761197.88 0.287820E+09 0.00 0.367103E+09 0.00 0.42
August 0.109554E+09 0.188833E+11 0.00 1940362.66 0.153612E+09 0.00 0.245332E+09 0.00 0.44
September 0.100272E+10 0.719022E+10 0.00 38752379.29 0.188308E+09 0.00 0.107610E+11 0.00 0.70
October 0.199370E+10 0.257766E+10 0.00 76407755.60 0.00 0.00 0.389424E+11 0.00 0.81
November 0.281822E+10 224326.95 0.00 96422027.85 0.00 0.00 0.513704E+11 0.00 0.88
December 0.214614E+10 0.00 0.00 95367329.56 0.00 0.00 0.531753E+11 0.00 0.70
                   
Annual Sum or Average 0.285647E+11 0.550297E+11 0.00 0.699913E+09 0.782167E+09 0.00 0.338447E+12 0.00 0.71
Minimum of Months 0.109554E+09 0.00 0.00 1940362.66 0.00 0.00 0.245332E+09 0.00 0.42
Maximum of Months 0.610130E+10 0.188833E+11 0.00 97820548.38 0.287820E+09 0.00 0.531753E+11 0.00 1.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.182388E+12 0.00 0.00 0.137707E+09 0.00 0.769090E+09 0.112186E+12 0.00 0.44
February 0.121748E+12 0.00 0.00 0.266019E+09 0.00 0.115423E+09 0.170849E+12 0.00 0.53
March 0.377408E+11 0.461185E+09 0.00 0.613103E+09 0.142183E+09 0.00 0.346645E+12 0.00 0.73
April 0.176513E+11 0.338665E+10 0.00 0.603523E+09 0.193120E+09 0.00 0.254004E+12 0.00 0.77
May 0.135718E+11 0.202226E+11 0.00 0.485634E+09 0.387138E+09 0.00 0.133705E+12 0.00 0.73
June 0.690969E+10 0.954659E+11 0.00 0.166868E+09 0.916839E+09 0.00 0.408485E+11 0.00 0.53
July 0.987562E+09 0.135020E+12 0.00 30251527.75 0.283942E+10 0.00 0.277770E+10 0.00 0.40
August 0.499873E+09 0.180907E+12 0.00 21870007.13 0.154458E+10 0.00 0.247218E+10 0.00 0.44
September 0.105876E+11 0.696077E+11 0.00 0.327518E+09 0.184872E+10 0.00 0.869009E+11 0.00 0.62
October 0.241551E+11 0.233677E+11 0.00 0.484077E+09 0.00 0.00 0.268231E+12 0.00 0.63
November 0.496184E+11 36673767.56 0.00 0.485210E+09 0.474146E+09 0.00 0.298729E+12 0.00 0.62
December 0.124401E+12 0.00 0.00 0.281714E+09 0.00 0.00 0.194507E+12 0.00 0.49
                   
Annual Sum or Average 0.590260E+12 0.528475E+12 0.00 0.390349E+10 0.834614E+10 0.884512E+09 0.191186E+13 0.00 0.58
Minimum of Months 0.499873E+09 0.00 0.00 21870007.13 0.00 0.00 0.247218E+10 0.00 0.40
Maximum of Months 0.182388E+12 0.180907E+12 0.00 0.613103E+09 0.283942E+10 0.769090E+09 0.346645E+12 0.00 0.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.184492E+11 0.00 0.00 2157355.32 0.00 0.172042E+10 0.212034E+10 0.00 0.42
February 0.144187E+11 0.00 0.00 10030765.33 0.00 0.631934E+09 0.680061E+10 0.00 0.48
March 0.888695E+10 14557590.96 0.00 37557199.33 13292569.95 1347374.31 0.210065E+11 0.00 0.64
April 0.420996E+10 0.227621E+09 0.00 46056579.21 13239387.42 0.00 0.181195E+11 0.00 0.72
May 0.128916E+10 0.184136E+10 0.00 44938778.38 37147421.61 0.00 0.113506E+11 0.00 0.74
June 0.422061E+09 0.947998E+10 0.00 14904555.68 0.102404E+09 0.00 0.360135E+10 0.00 0.53
July 90523533.13 0.130568E+11 0.00 2309499.57 0.576243E+09 0.00 0.203287E+09 0.00 0.40
August 38620339.40 0.178205E+11 0.00 2418172.75 0.144608E+09 0.00 0.192216E+09 0.00 0.44
September 0.109729E+10 0.665130E+10 0.00 27117430.08 0.262045E+09 0.00 0.675968E+10 0.00 0.59
October 0.690474E+10 0.227717E+10 0.00 26680801.52 0.00 0.00 0.152669E+11 0.00 0.56
November 0.119428E+11 0.00 0.00 19278519.32 83197716.43 16242841.89 0.129013E+11 0.00 0.52
December 0.171513E+11 0.00 0.00 7127824.97 0.00 0.527662E+09 0.589436E+10 0.00 0.44
                   
Annual Sum or Average 0.849013E+11 0.513692E+11 0.00 0.240577E+09 0.123218E+10 0.289761E+10 0.104217E+12 0.00 0.54
Minimum of Months 38620339.40 0.00 0.00 2157355.32 0.00 0.00 0.192216E+09 0.00 0.40
Maximum of Months 0.184492E+11 0.178205E+11 0.00 46056579.21 0.576243E+09 0.172042E+10 0.210065E+11 0.00 0.74



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.393669E+10 0.00 0.00 363328.48 0.00 0.445659E+09 0.301103E+09 0.00 0.45
February 0.341535E+10 0.00 0.00 1377496.39 0.00 0.125712E+09 0.844081E+09 0.00 0.56
March 0.260999E+10 7431387.89 0.00 4982752.60 32277.74 0.00 0.289421E+10 0.00 0.82
April 0.184153E+10 51074240.21 0.00 6358525.94 1501192.97 0.00 0.255597E+10 0.00 1.00
May 0.570187E+09 0.334978E+09 0.00 5079613.98 6031827.83 0.00 0.148509E+10 0.00 0.89
June 0.264859E+09 0.175465E+10 0.00 1987433.81 15853836.94 0.00 0.517465E+09 0.00 0.76
July 43676525.92 0.253428E+10 0.00 347311.02 44221224.76 0.00 37292308.05 0.00 0.59
August 17559475.88 0.320639E+10 0.00 223640.50 23601131.03 0.00 27993832.00 0.00 0.60
September 0.508094E+09 0.106973E+10 0.00 3127639.14 28931928.33 0.00 0.818734E+09 0.00 0.73
October 0.193752E+10 0.347547E+09 0.00 3176773.95 0.00 0.00 0.197803E+10 0.00 0.67
November 0.277213E+10 22285.79 0.00 3377629.72 0.00 323816.88 0.217006E+10 0.00 0.67
December 0.390473E+10 0.00 0.00 1359954.49 0.00 1213569.59 0.112694E+10 0.00 0.52
                   
Annual Sum or Average 0.218223E+11 0.930610E+10 0.00 31762100.00 0.120173E+09 0.572909E+09 0.147570E+11 0.00 0.69
Minimum of Months 17559475.88 0.00 0.00 223640.50 0.00 0.00 27993832.00 0.00 0.45
Maximum of Months 0.393669E+10 0.320639E+10 0.00 6358525.94 44221224.76 0.445659E+09 0.289421E+10 0.00 1.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.382669E+10 0.00 0.00 127476.98 0.00 0.424692E+09 0.245200E+09 0.00 0.67
February 0.334125E+10 0.00 0.00 1329748.58 0.00 0.113383E+09 0.853996E+09 0.00 0.84
March 0.278716E+10 5713551.29 0.00 3858738.99 31096.74 0.00 0.245824E+10 0.00 1.15
April 0.206956E+10 33810561.28 0.00 5330463.44 1446266.50 0.00 0.222833E+10 0.00 1.42
May 0.737911E+09 0.271070E+09 0.00 4389920.49 7311142.97 0.00 0.134442E+10 0.00 1.27
June 0.299070E+09 0.133901E+10 0.00 1870085.44 15273768.12 0.00 0.523955E+09 0.00 0.99
July 56710504.91 0.195342E+10 0.00 107108.61 50001512.10 0.00 15277547.74 0.00 0.71
August 27117058.38 0.227851E+10 0.00 119954.35 24247074.26 0.00 14434196.03 0.00 0.69
September 0.586689E+09 0.889782E+09 0.00 2651840.57 33327421.34 0.00 0.751506E+09 0.00 1.02
October 0.202712E+10 0.245006E+09 0.00 2903606.56 6243129.28 0.00 0.190572E+10 0.00 0.98
November 0.299317E+10 19517.77 0.00 1918044.65 0.00 3996716.68 0.160372E+10 0.00 0.93
December 0.408870E+10 0.00 0.00 608882.09 0.00 54934291.65 0.628894E+09 0.00 0.74
                   
Annual Sum or Average 0.228412E+11 0.701634E+10 0.00 25215870.74 0.137881E+09 0.597006E+09 0.125737E+11 0.00 0.95
Minimum of Months 27117058.38 0.00 0.00 107108.61 0.00 0.00 14434196.03 0.00 0.67
Maximum of Months 0.408870E+10 0.227851E+10 0.00 5330463.44 50001512.10 0.424692E+09 0.245824E+10 0.00 1.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.322408E+10 0.00 0.00 3870279.21 0.00 0.498539E+09 0.262783E+10 0.00 0.60
February 0.294560E+10 0.00 0.00 5387106.31 0.00 0.173220E+09 0.306554E+10 0.00 0.83
March 0.251284E+10 14905975.53 0.00 9351645.10 36987.29 0.00 0.513094E+10 0.00 1.20
April 0.218338E+10 61312845.38 0.00 8413824.01 1720227.61 0.00 0.315492E+10 0.00 1.27
May 0.822409E+09 0.375720E+09 0.00 5019160.88 6911914.04 0.00 0.143268E+10 0.00 0.99
June 0.373088E+09 0.177037E+10 0.00 1762078.23 18167023.53 0.00 0.438580E+09 0.00 0.78
July 54831528.00 0.259466E+10 0.00 268315.65 50673413.24 0.00 32710217.06 0.00 0.60
August 20121527.22 0.358632E+10 0.00 224712.30 27044702.45 0.00 28945761.46 0.00 0.68
September 0.589479E+09 0.135083E+10 0.00 4446114.17 33153300.66 0.00 0.104994E+10 0.00 0.97
October 0.174849E+10 0.454630E+09 0.00 8404736.29 0.00 0.00 0.446689E+10 0.00 1.11
November 0.226157E+10 23214.95 0.00 9774224.95 0.00 4667212.47 0.541912E+10 0.00 1.08
December 0.304952E+10 0.00 0.00 6836096.56 0.00 83024693.21 0.469348E+10 0.00 0.82
                   
Annual Sum or Average 0.197854E+11 0.102088E+11 0.00 63758293.67 0.137708E+09 0.759451E+09 0.315416E+11 0.00 0.91
Minimum of Months 20121527.22 0.00 0.00 224712.30 0.00 0.00 28945761.46 0.00 0.60
Maximum of Months 0.322408E+10 0.358632E+10 0.00 9774224.95 50673413.24 0.498539E+09 0.541912E+10 0.00 1.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.495548E+10 0.00 0.00 738482.51 0.00 37580550.19 0.822531E+09 0.00 0.87
February 0.340878E+10 0.00 0.00 3118586.91 0.00 3299843.55 0.218044E+10 0.00 1.12
March 0.129620E+10 14580271.72 0.00 10988512.69 40062.95 0.00 0.622252E+10 0.00 1.79
April 0.112734E+10 71290298.37 0.00 14032955.40 1143962.35 0.00 0.514907E+10 0.00 2.26
May 0.590008E+09 0.334281E+09 0.00 6108034.53 6839604.33 0.00 0.180015E+10 0.00 1.56
June 0.255634E+09 0.180248E+10 0.00 2743211.73 14762870.92 0.00 0.661696E+09 0.00 1.30
July 37269278.09 0.278645E+10 0.00 681799.59 42891648.65 0.00 65108719.59 0.00 1.02
August 11011430.96 0.394175E+10 0.00 469402.21 8361096.02 0.00 51459623.32 0.00 1.15
September 0.428554E+09 0.111423E+10 0.00 3749316.44 34004771.78 0.00 0.108045E+10 0.00 1.27
October 0.133278E+10 0.371620E+09 0.00 6232199.45 0.00 0.00 0.379711E+10 0.00 1.36
November 0.160632E+10 29023.91 0.00 7942967.92 0.00 0.00 0.501563E+10 0.00 1.41
December 0.184474E+10 0.00 0.00 6248353.16 0.00 0.00 0.507892E+10 0.00 1.12
                   
Annual Sum or Average 0.168941E+11 0.104367E+11 0.00 63053822.55 0.108044E+09 40880393.75 0.319251E+11 0.00 1.35
Minimum of Months 11011430.96 0.00 0.00 469402.21 0.00 0.00 51459623.32 0.00 0.87
Maximum of Months 0.495548E+10 0.394175E+10 0.00 14032955.40 42891648.65 37580550.19 0.622252E+10 0.00 2.26



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.186118E+11 0.00 0.00 0.00 0.00 0.234000E+11 0.00 0.00 0.50
February 0.227739E+11 0.00 0.00 2129929.29 0.00 0.144751E+11 0.642770E+09 0.00 0.53
March 0.326735E+11 44646531.23 0.00 14730410.96 40248106.76 0.128229E+10 0.697958E+10 0.00 0.63
April 0.182556E+11 0.455244E+09 0.00 28642228.20 24401651.73 0.353041E+09 0.101952E+11 0.00 0.70
May 0.744533E+10 0.322112E+10 0.00 33941637.97 69153754.18 0.00 0.905060E+10 0.00 0.77
June 0.215372E+10 0.175643E+11 0.00 15069120.69 0.134894E+09 0.00 0.359694E+10 0.00 0.71
July 0.280549E+09 0.253191E+11 0.00 2005315.03 0.417763E+09 0.00 0.214409E+09 0.00 0.58
August 75581894.92 0.319210E+11 0.00 1854373.69 0.227253E+09 0.00 0.274200E+09 0.00 0.61
September 0.571218E+10 0.102889E+11 0.00 20917284.15 0.284251E+09 0.00 0.516280E+10 0.00 0.64
October 0.259539E+11 0.303192E+10 0.00 7956954.73 38245593.60 0.238331E+09 0.468296E+10 0.00 0.55
November 0.328887E+11 0.00 0.00 3130712.22 75156728.52 0.343186E+10 0.214825E+10 0.00 0.54
December 0.286235E+11 0.00 0.00 1239070.70 0.00 0.118285E+11 0.567303E+09 0.00 0.49
                   
Annual Sum or Average 0.195448E+12 0.918462E+11 0.00 0.131617E+09 0.131137E+10 0.550091E+11 0.435150E+11 0.00 0.61
Minimum of Months 75581894.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.49
Maximum of Months 0.328887E+11 0.319210E+11 0.00 33941637.97 0.417763E+09 0.234000E+11 0.101952E+11 0.00 0.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.247684E+11 0.00 0.00 0.00 0.00 0.190443E+11 0.00 0.00 0.81
February 0.251160E+11 0.00 0.00 4968262.13 0.00 0.111402E+11 0.357277E+10 0.00 0.87
March 0.284234E+11 49808274.28 0.00 20105828.61 27760347.88 0.874704E+09 0.138831E+11 0.00 1.01
April 0.155809E+11 0.373145E+09 0.00 40000735.80 36292235.15 0.159719E+09 0.168968E+11 0.00 1.20
May 0.799968E+10 0.284064E+10 0.00 35193119.50 85435215.45 0.00 0.107830E+11 0.00 1.22
June 0.222192E+10 0.147853E+11 0.00 17706398.11 0.179146E+09 0.00 0.486605E+10 0.00 1.02
July 0.335071E+09 0.219383E+11 0.00 1127300.68 0.978483E+09 0.00 0.167034E+09 0.00 0.81
August 0.175475E+09 0.268706E+11 0.00 1617508.48 0.299129E+09 0.00 0.200680E+09 0.00 0.83
September 0.674953E+10 0.820269E+10 0.00 21665005.33 0.174466E+10 0.00 0.559987E+10 0.00 1.01
October 0.234187E+11 0.209622E+10 0.00 17038679.62 0.535178E+09 0.313858E+09 0.103891E+11 0.00 0.91
November 0.351864E+11 0.00 0.00 2862538.08 79133419.92 0.202140E+10 0.322874E+10 0.00 0.88
December 0.346458E+11 0.00 0.00 329.41 0.00 0.835952E+10 7603416.65 0.00 0.80
                   
Annual Sum or Average 0.204621E+12 0.771567E+11 0.00 0.162286E+09 0.396522E+10 0.419137E+11 0.695947E+11 0.00 0.95
Minimum of Months 0.175475E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.80
Maximum of Months 0.351864E+11 0.268706E+11 0.00 40000735.80 0.174466E+10 0.190443E+11 0.168968E+11 0.00 1.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.239063E+11 0.00 0.00 27172423.30 0.00 0.119230E+11 0.191564E+11 0.00 0.63
February 0.246587E+11 0.00 0.00 37362652.69 0.00 0.686202E+10 0.206756E+11 0.00 0.78
March 0.242627E+11 0.178504E+09 0.00 65128628.35 874199.39 0.684326E+09 0.340300E+11 0.00 0.99
April 0.171390E+11 0.658434E+09 0.00 57159067.33 21023633.49 9920039.39 0.198142E+11 0.00 0.98
May 0.898476E+10 0.373840E+10 0.00 37991125.70 79733923.27 0.00 0.998413E+10 0.00 0.89
June 0.309747E+10 0.178645E+11 0.00 13625535.57 0.155532E+09 0.00 0.309333E+10 0.00 0.74
July 0.338554E+09 0.262752E+11 0.00 1696020.54 0.603619E+09 0.00 0.208436E+09 0.00 0.61
August 84886393.30 0.371320E+11 0.00 2238076.65 0.262021E+09 0.00 0.310255E+09 0.00 0.73
September 0.616503E+10 0.139058E+11 0.00 38903214.46 0.313616E+09 0.00 0.812573E+10 0.00 0.93
October 0.173980E+11 0.443129E+10 0.00 68128777.90 49134954.17 6785800.31 0.341233E+11 0.00 0.99
November 0.231095E+11 0.00 0.00 70315904.75 86655321.84 0.104755E+10 0.362679E+11 0.00 0.91
December 0.263991E+11 0.00 0.00 43363268.93 0.00 0.518126E+10 0.281936E+11 0.00 0.73
                   
Annual Sum or Average 0.175544E+12 0.104184E+12 0.00 0.463085E+09 0.157221E+10 0.257149E+11 0.213983E+12 0.00 0.83
Minimum of Months 84886393.30 0.00 0.00 1696020.54 0.00 0.00 0.208436E+09 0.00 0.61
Maximum of Months 0.263991E+11 0.371320E+11 0.00 70315904.75 0.603619E+09 0.119230E+11 0.362679E+11 0.00 0.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.285685E+11 0.00 0.00 69572.74 0.00 0.175126E+11 0.210485E+09 0.00 0.85
February 0.308143E+11 0.00 0.00 5042587.25 0.00 0.894753E+10 0.246334E+10 0.00 0.93
March 0.343632E+11 0.135813E+09 0.00 23979746.89 6534436.11 0.273950E+09 0.120988E+11 0.00 1.14
April 0.179464E+11 0.546227E+09 0.00 39388952.92 16267943.76 0.00 0.146023E+11 0.00 1.27
May 0.844350E+10 0.293790E+10 0.00 31927424.06 74158078.71 0.00 0.939241E+10 0.00 1.24
June 0.291831E+10 0.151595E+11 0.00 13401855.67 0.127754E+09 0.00 0.295725E+10 0.00 1.04
July 0.315129E+09 0.219091E+11 0.00 1900686.55 0.787062E+09 0.00 0.222209E+09 0.00 0.82
August 81902243.05 0.294346E+11 0.00 1723887.78 0.175015E+09 0.00 0.271761E+09 0.00 0.89
September 0.687730E+10 0.927953E+10 0.00 19957694.91 0.909738E+09 0.00 0.459915E+10 0.00 1.03
October 0.270314E+11 0.258488E+10 0.00 15585637.78 0.284007E+09 68920878.21 0.857803E+10 0.00 0.98
November 0.365270E+11 0.00 0.00 8446728.22 83695773.64 0.135516E+10 0.542946E+10 0.00 0.96
December 0.364975E+11 0.00 0.00 1646010.04 0.00 0.733854E+10 0.161549E+10 0.00 0.85
                   
Annual Sum or Average 0.230384E+12 0.819875E+11 0.00 0.163071E+09 0.246423E+10 0.354967E+11 0.624407E+11 0.00 1.00
Minimum of Months 81902243.05 0.00 0.00 69572.74 0.00 0.00 0.210485E+09 0.00 0.82
Maximum of Months 0.365270E+11 0.294346E+11 0.00 39388952.92 0.909738E+09 0.175126E+11 0.146023E+11 0.00 1.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.953063E+09 0.00 0.00 0.00 0.00 0.283307E+10 0.00 0.00 0.56
February 0.172722E+10 0.00 0.00 85087.52 0.00 0.176915E+10 25741455.71 0.00 0.59
March 0.310061E+10 1118713.17 0.00 1121107.12 3211503.23 0.539620E+09 0.477710E+09 0.00 0.69
April 0.205765E+10 29508340.80 0.00 2511491.87 2562593.33 96772054.40 0.716050E+09 0.00 0.75
May 0.850102E+09 0.285135E+09 0.00 3239373.53 9208933.89 0.00 0.750408E+09 0.00 0.81
June 0.247497E+09 0.170309E+10 0.00 1361689.29 17840366.01 0.00 0.292815E+09 0.00 0.71
July 25968329.06 0.239530E+10 0.00 122130.11 0.101996E+09 0.00 16227573.31 0.00 0.58
August 14533161.00 0.309220E+10 0.00 178015.25 23886458.05 0.00 16529264.19 0.00 0.61
September 0.628710E+09 0.903292E+09 0.00 1772872.82 0.144671E+09 0.00 0.384888E+09 0.00 0.65
October 0.250403E+10 0.287363E+09 0.00 360852.47 16361069.44 0.308478E+09 0.230788E+09 0.00 0.60
November 0.285589E+10 0.00 8831901.77 116697.60 4900492.47 0.849058E+09 62400493.36 10288.05 0.61
December 0.178462E+10 0.00 0.00 21260.79 0.00 0.203414E+10 29963918.13 0.00 0.56
                   
Annual Sum or Average 0.167499E+11 0.869701E+10 8831901.77 10890578.36 0.324639E+09 0.843028E+10 0.300352E+10 10288.05 0.64
Minimum of Months 14533161.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.56
Maximum of Months 0.310061E+10 0.309220E+10 8831901.77 3239373.53 0.144671E+09 0.283307E+10 0.750408E+09 10288.05 0.81



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.145332E+10 0.00 0.00 0.00 0.00 0.201920E+10 0.00 0.00 0.80
February 0.179479E+10 0.00 0.00 269824.68 0.00 0.129790E+10 0.182918E+09 0.00 0.86
March 0.266899E+10 1772505.29 0.00 1551850.58 2107149.57 0.289664E+09 0.931539E+09 0.00 1.01
April 0.141337E+10 25770914.10 0.00 3976658.88 2626814.97 59281457.22 0.145386E+10 0.00 1.20
May 0.671671E+09 0.255793E+09 0.00 3909906.44 13192763.96 0.00 0.103036E+10 0.00 1.27
June 0.178565E+09 0.144625E+10 0.00 1752252.83 34185012.73 0.00 0.462200E+09 0.00 1.03
July 26023031.04 0.215132E+10 0.00 72721.61 0.100330E+09 0.00 13643352.10 0.00 0.81
August 16839902.98 0.262489E+10 0.00 208626.08 54125551.20 0.00 15128421.88 0.00 0.84
September 0.536384E+09 0.787325E+09 0.00 2256100.86 0.201609E+09 0.00 0.548385E+09 0.00 1.01
October 0.192592E+10 0.210028E+09 0.00 1368866.76 52142462.91 0.204159E+09 0.834279E+09 0.00 0.90
November 0.287343E+10 0.00 8349856.93 126615.72 4629701.58 0.514643E+09 0.159178E+09 3732.11 0.90
December 0.219008E+10 0.00 0.00 0.00 0.00 0.140288E+10 0.00 0.00 0.81
                   
Annual Sum or Average 0.157494E+11 0.750315E+10 8349856.93 15493424.44 0.464948E+09 0.578772E+10 0.563149E+10 3732.11 0.95
Minimum of Months 16839902.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.80
Maximum of Months 0.287343E+10 0.262489E+10 8349856.93 3976658.88 0.201609E+09 0.201920E+10 0.145386E+10 3732.11 1.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.196744E+10 0.00 0.00 1208310.19 0.00 0.149748E+10 0.857566E+09 0.00 0.63
February 0.192101E+10 0.00 0.00 2548489.11 0.00 0.109943E+10 0.141125E+10 0.00 0.78
March 0.248973E+10 8037082.35 0.00 5232020.93 60518.07 0.315914E+09 0.265638E+10 0.00 0.97
April 0.177387E+10 43464540.91 0.00 5502490.63 2028030.74 91791046.94 0.168686E+10 0.00 1.01
May 0.951235E+09 0.327764E+09 0.00 3848547.60 11582197.73 0.00 0.890506E+09 0.00 0.94
June 0.313464E+09 0.173038E+10 0.00 1281998.58 26337449.58 0.00 0.278678E+09 0.00 0.74
July 29765785.78 0.249958E+10 0.00 93058.39 0.114962E+09 0.00 17544316.69 0.00 0.61
August 15764780.44 0.359052E+10 0.00 242423.92 26922920.53 0.00 19220481.77 0.00 0.72
September 0.582972E+09 0.128808E+10 0.00 3833401.24 99657518.25 0.00 0.771801E+09 0.00 0.93
October 0.173798E+10 0.424193E+09 0.00 5397159.62 9513454.18 0.162886E+09 0.278328E+10 0.00 0.97
November 0.237770E+10 0.00 0.00 4463709.26 15489661.23 0.418956E+09 0.245899E+10 0.00 0.89
December 0.226824E+10 0.00 0.00 2471280.41 0.00 0.892647E+09 0.167030E+10 0.00 0.70
                   
Annual Sum or Average 0.164292E+11 0.991202E+10 0.00 36122889.86 0.306554E+09 0.447910E+10 0.155024E+11 0.00 0.82
Minimum of Months 15764780.44 0.00 0.00 93058.39 0.00 0.00 17544316.69 0.00 0.61
Maximum of Months 0.248973E+10 0.359052E+10 0.00 5502490.63 0.114962E+09 0.149748E+10 0.278328E+10 0.00 1.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.180062E+10 0.00 0.00 1721.11 0.00 0.205768E+10 15578807.25 0.00 0.89
February 0.224407E+10 0.00 0.00 388792.37 0.00 0.123951E+10 0.201598E+09 0.00 0.97
March 0.306953E+10 5211530.83 0.00 2120312.99 921000.21 0.292144E+09 0.108915E+10 0.00 1.18
April 0.185311E+10 35465946.36 0.00 3855679.65 2616467.05 62839036.51 0.121895E+10 0.00 1.32
May 0.897731E+09 0.251602E+09 0.00 3266394.05 15000547.05 0.00 0.833681E+09 0.00 1.30
June 0.285683E+09 0.143676E+10 0.00 1296834.08 36040375.50 0.00 0.273618E+09 0.00 1.03
July 26785095.67 0.207315E+10 0.00 144297.49 0.113993E+09 0.00 18174123.67 0.00 0.80
August 14015884.00 0.283663E+10 0.00 170360.95 17814667.46 0.00 16866063.78 0.00 0.87
September 0.650445E+09 0.834137E+09 0.00 1886252.76 0.173408E+09 0.00 0.411262E+09 0.00 1.04
October 0.252719E+10 0.238667E+09 0.00 1223611.18 49551726.60 0.130955E+09 0.683867E+09 0.00 1.01
November 0.302892E+10 0.00 0.00 539445.88 14545602.24 0.570109E+09 0.406512E+09 0.00 1.02
December 0.274677E+10 0.00 0.00 33704.59 0.00 0.120188E+10 65547404.00 0.00 0.91
                   
Annual Sum or Average 0.191449E+11 0.771163E+10 0.00 14927407.11 0.423892E+09 0.555512E+10 0.523481E+10 0.00 1.03
Minimum of Months 14015884.00 0.00 0.00 1721.11 0.00 0.00 15578807.25 0.00 0.80
Maximum of Months 0.306953E+10 0.283663E+10 0.00 3855679.65 0.173408E+09 0.205768E+10 0.121895E+10 0.00 1.32



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 2986913.38 0.00 0.00 0.592752E+09 0.00 0.28
February 0.00 0.00 0.00 7237022.17 0.00 0.00 0.444832E+09 0.00 0.28
March 0.00 4296492.00 0.00 12079555.68 0.00 0.00 0.341301E+09 0.00 0.31
April 0.00 11302990.37 0.00 14441425.65 0.00 0.00 0.186619E+09 0.00 0.29
May 0.00 66560490.23 0.00 1444277.91 0.00 0.00 59774772.58 0.00 0.29
June 0.00 0.278944E+09 0.00 1319537.84 0.00 0.00 27365874.69 0.00 0.30
July 0.00 0.392022E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.479363E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.156540E+09 0.00 1273454.01 0.00 0.00 34031301.67 0.00 0.29
October 0.00 50450521.09 0.00 6005871.20 0.00 0.00 0.241300E+09 0.00 0.28
November 0.00 3590752.49 0.00 11056224.13 0.00 0.00 0.355661E+09 0.00 0.28
December 0.00 442616.74 0.00 16463960.50 0.00 0.00 0.448645E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.144351E+10 0.00 74308242.48 0.00 0.00 0.273228E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.479363E+09 0.00 16463960.50 0.00 0.00 0.592752E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.551031E+09 0.00 0.00 14899125.43 0.00 0.00 0.539992E+10 0.00 0.28
February 0.00 0.00 0.00 58766809.99 0.00 0.00 0.446328E+10 0.00 0.28
March 0.00 42643861.66 0.00 0.109862E+09 0.00 0.00 0.341968E+10 0.00 0.31
April 0.00 0.113227E+09 0.00 0.135776E+09 0.00 0.00 0.187095E+10 0.00 0.29
May 0.00 0.647930E+09 0.00 13271965.25 0.00 0.00 0.602108E+09 0.00 0.29
June 0.00 0.278031E+10 0.00 12343170.97 0.00 0.00 0.273571E+09 0.00 0.30
July 0.00 0.391455E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.478665E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.153930E+10 0.00 11341628.07 0.00 0.00 0.350069E+09 0.00 0.29
October 0.00 0.499039E+09 0.00 52716722.75 0.00 0.00 0.242067E+10 0.00 0.28
November 0.00 34884040.00 0.00 98598077.26 0.00 0.00 0.356536E+10 0.00 0.28
December 0.00 4334768.86 0.00 0.145205E+09 0.00 0.00 0.450258E+10 0.00 0.28
                   
Annual Sum or Average 0.551031E+09 0.143629E+11 0.00 0.652780E+09 0.00 0.00 0.268682E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.551031E+09 0.478665E+10 0.00 0.145205E+09 0.00 0.00 0.539992E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.251656E+09 0.00 0.00 751640.36 0.00 0.00 0.335898E+09 0.00 0.28
February 0.00 0.00 0.00 5122689.64 0.00 0.00 0.447356E+09 0.00 0.28
March 0.00 4244044.74 0.00 10456385.49 0.00 0.00 0.342769E+09 0.00 0.31
April 0.00 11264458.16 0.00 13334245.67 0.00 0.00 0.187536E+09 0.00 0.29
May 0.00 64778423.35 0.00 1263741.09 0.00 0.00 60544190.10 0.00 0.29
June 0.00 0.278105E+09 0.00 1220575.42 0.00 0.00 27413570.42 0.00 0.30
July 0.00 0.391315E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.479053E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.153718E+09 0.00 1061605.79 0.00 0.00 35820093.97 0.00 0.29
October 0.00 49723750.31 0.00 4848265.70 0.00 0.00 0.243135E+09 0.00 0.28
November 0.00 3410828.33 0.00 9169669.55 0.00 0.00 0.357505E+09 0.00 0.28
December 0.00 420484.63 0.00 13533887.68 0.00 0.00 0.451441E+09 0.00 0.28
                   
Annual Sum or Average 0.251656E+09 0.143603E+10 0.00 60762706.40 0.00 0.00 0.248942E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.251656E+09 0.479053E+09 0.00 13533887.68 0.00 0.00 0.451441E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.215857E+09 0.00 0.00 0.151409E+11 0.00 0.32
February 0.00 0.00 0.00 0.395105E+09 0.00 0.00 0.111571E+11 0.00 0.32
March 0.00 84336128.46 0.00 0.603080E+09 0.00 0.00 0.799192E+10 0.00 0.34
April 0.00 0.231659E+09 0.00 0.721661E+09 0.00 0.00 0.408951E+10 0.00 0.32
May 0.00 0.174547E+10 0.00 71049066.76 0.00 0.00 0.128923E+10 0.00 0.33
June 0.00 0.628302E+10 0.00 65278277.36 0.00 0.00 0.583801E+09 0.00 0.34
July 0.00 0.864861E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
August 0.00 0.874883E+10 0.00 35051.25 0.00 0.00 0.00 0.00 0.35
September 0.00 0.380397E+10 0.00 62729723.98 0.00 0.00 0.641238E+09 0.00 0.33
October 0.00 0.116854E+10 0.00 0.310848E+09 0.00 0.00 0.516441E+10 0.00 0.32
November 0.00 69138415.71 0.00 0.560300E+09 0.00 0.00 0.855038E+10 0.00 0.32
December 0.00 9766119.94 0.00 0.834081E+09 0.00 0.00 0.110667E+11 0.00 0.31
                   
Annual Sum or Average 0.00 0.307934E+11 0.00 0.384002E+10 0.00 0.00 0.656751E+11 0.00 0.33
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.00 0.874883E+10 0.00 0.834081E+09 0.00 0.00 0.151409E+11 0.00 0.35



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:03:06

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.352921E+12 0.288310E+11 0.00 0.191974E+13 0.568375E+12
February 0.353626E+12 0.254947E+11 0.00 0.179699E+13 0.959473E+12
March 0.515988E+12 0.167877E+11 0.00 0.197915E+13 0.169750E+13
April 0.578332E+12 0.915696E+10 0.00 0.152643E+13 0.239826E+13
May 0.637104E+12 0.437477E+10 0.00 0.878618E+12 0.189135E+13
June 0.619142E+12 -0.440618E+10 0.00 -0.142412E+12 0.301034E+13
July 0.596713E+12 -0.900969E+10 0.00 -0.617512E+12 0.370701E+13
August 0.554827E+12 -0.116921E+11 0.00 -0.832913E+12 0.439933E+13
September 0.429168E+12 -525685573.1 0.00 0.269871E+12 0.213998E+13
October 0.408891E+12 0.908929E+10 0.00 0.149587E+13 0.163837E+13
November 0.302150E+12 0.151711E+11 0.00 0.187838E+13 0.153411E+13
December 0.288168E+12 0.269343E+11 0.00 0.196743E+13 0.177441E+13
           
Annual Sum or Average 0.563703E+13 0.110206E+12 0.00 0.121196E+14 0.257185E+14
Minimum of Months 0.288168E+12 -0.116921E+11 0.00 -0.832913E+12 0.568375E+12
Maximum of Months 0.637104E+12 0.288310E+11 0.00 0.197915E+13 0.439933E+13