Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 09:03:29
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 29203.66 | 630.47 | 630.47 |
Net Site Energy | 29203.66 | 630.47 | 630.47 |
Total Source Energy | 88612.89 | 1913.04 | 1913.04 |
Net Source Energy | 88612.89 | 1913.04 | 1913.04 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1114.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2459.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3718.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 672.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1941.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2337.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 262.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 732.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.11 |
Humidification | 5.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 745.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27343.31 | 1860.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.17 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1114.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2459.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3718.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 672.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2337.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 262.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 732.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.11 |
Humidification | General | 5.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 745.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1114.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2459.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3718.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 672.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1941.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2337.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 262.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 732.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.11 |
Humidification | Unassigned | 5.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 745.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 125.15 | 40.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
Other | 370.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 590.31 | 40.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 125.15 | 40.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
Other | 370.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 590.31 | 40.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 27343.311 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 27343.311 | 100.00 |
Total On-Site and Utility Electric Sources | 27343.311 | 100.00 |
Total Electricity End Uses | 27343.311 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 3160.17 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 3160.17 | 100.00 |
Total Water End Uses | 3160.17 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 14.67 |
Time Setpoint Not Met During Occupied Cooling | 66.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5939.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.3279 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.3279 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.3279 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.3279 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 9.3279 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.3279 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 9.3279 | 18.58 | 484.4232 | |
Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.8860 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 14-AUG-15:39 | 10-JAN-07:00 | - | - | - | - | - | - | - | - | - | - | 21-JUL-12:00 |
Heating | 0.00 | 743188.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 321893.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84885.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 217916.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 47637.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 54987.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25539.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1838139.92 | 768728.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 743188.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 321893.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5451.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 217916.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 47637.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 54987.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 25539.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1208.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11775.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2130.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6150.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7403.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 830.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2319.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 16.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 808.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 86596.27 | 2016.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 26.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 168.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 254.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 50.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1869.51 | 43.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 26.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 168.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 254.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 50.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1869.51 | 43.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.72 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.507609 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.86 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.492315 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.58 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.94 | 0.320255 | 0.323000 | 1.92 | 0.854014 | 0.500000 | 0.001190 | 0.000167 | 1.92 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 55.67 | 0.341643 | 0.336000 | 18.71 | 0.911047 | 0.500000 | 0.001115 | 0.003329 | 18.71 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.30 | 0.358839 | 0.361000 | 1.91 | 0.956903 | 0.500000 | 0.001062 | 0.000632 | 2.17 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.817389 | 0.292175 | 0.300000 | 0.245217 | 0.779133 | 0.500000 | 0.001304 | 0.000065 | 0.245217 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.13 | 0.135974 | 0.300000 | 0.339562 | 0.362597 | 0.500000 | 0.002802 | 0.000062 | 0.339562 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.61 | 0.148327 | 0.300000 | 0.483038 | 0.395539 | 0.500000 | 0.002569 | 0.000102 | 0.483038 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.39 | 0.110762 | 0.300000 | 0.416854 | 0.300000 | 0.500000 | 0.003440 | 0.000054 | 0.416854 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.30 | 0.327147 | 0.322000 | 2.35 | 0.872392 | 0.500000 | 0.001165 | 0.001442 | 4.97 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.65 | 0.132157 | 0.300000 | 3.49 | 0.352418 | 0.500000 | 0.002883 | 0.000980 | 3.49 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 16.36 | 0.146023 | 0.300000 | 4.91 | 0.389394 | 0.500000 | 0.002609 | 0.001451 | 5.00 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.33 | 0.124829 | 0.300000 | 3.70 | 0.332877 | 0.500000 | 0.003052 | 0.000936 | 3.70 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.807751 | 0.295661 | 0.300000 | 0.242325 | 0.788430 | 0.500000 | 0.001289 | 0.000196 | 0.676153 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.14 | 0.134490 | 0.300000 | 0.343309 | 0.358639 | 0.500000 | 0.002833 | 0.000130 | 0.448586 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.72 | 0.139044 | 0.300000 | 0.515288 | 0.370784 | 0.500000 | 0.002740 | 0.000197 | 0.679907 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.29 | 0.119154 | 0.300000 | 0.387494 | 0.317744 | 0.500000 | 0.003198 | 0.000124 | 0.425945 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19110.21 | 0.000167 | 385.25 |
CORE_MID VAV BOX REHEAT COIL | 380472.93 | 0.003329 | 8555.06 |
CORE_TOP VAV BOX REHEAT COIL | 72211.89 | 0.000632 | 1907.33 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7475.33 | 0.000065 | 190.15 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7136.41 | 0.000062 | 161.70 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11694.26 | 0.000102 | 275.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6211.13 | 0.000054 | 131.64 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 164834.14 | 0.001442 | 4348.69 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 112025.01 | 0.000980 | 2910.44 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 165847.67 | 0.001451 | 4375.40 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 107029.17 | 0.000936 | 2668.28 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22430.03 | 0.000196 | 591.57 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14880.05 | 0.000130 | 392.43 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22554.31 | 0.000197 | 594.84 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14130.37 | 0.000124 | 372.68 |
VAV_BOT WITH REHEAT HEATING COIL | 53338.37 | 0.000467 | 879.23 |
VAV_MID WITH REHEAT HEATING COIL | 514337.61 | 0.004500 | 8442.28 |
VAV_TOP WITH REHEAT HEATING COIL | 49508.89 | 0.000433 | 820.79 |
CAV_BAS HEATING COIL | 280157.10 | 0.002451 | 6241.03 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.44 | 3.40 | 10.89 | 3.40 | 9.38 | 9.38 | 0.300000 | 0.362675 | 9.38 |
VAV_MID WITH REHEAT | 51.65 | 33.16 | 103.30 | 33.16 | 86.40 | 86.40 | 0.300000 | 0.383771 | 86.40 |
VAV_TOP WITH REHEAT | 5.13 | 3.40 | 10.26 | 4.40 | 9.29 | 9.29 | 0.300000 | 0.473509 | 9.29 |
CAV_BAS | 5.72 | 5.72 | 5.72 | 5.72 | 5.72 | 5.72 | 1.00 | 1.00 | 5.72 |
AIRLOOP DATACENTER BASEMENT | 21.58 | 21.58 | 21.58 | 21.58 | 21.58 | 21.58 | 1.00 | 0.999994 | 21.58 |
AIRLOOP DATACENTER BOT | 0.507609 | 0.507609 | 0.507609 | 0.507609 | 0.507609 | 0.507609 | 1.00 | 1.00 | 0.507609 |
AIRLOOP DATACENTER MID | 4.86 | 4.86 | 4.86 | 4.86 | 4.86 | 4.86 | 1.00 | 1.00 | 4.86 |
AIRLOOP DATACENTER TOP | 0.492315 | 0.492315 | 0.492315 | 0.492315 | 0.492315 | 0.492315 | 1.00 | 1.00 | 0.492315 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.38 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 86.40 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.29 | |
CAV_BAS_OA_CONTROLLER | 5.72 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.58 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.507609 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.86 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.492315 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 24.66 | 6.67 | 11.02 | 0.008721 | 0.008500 | 161891.93 | 0.006887 | 9.38 |
VAV_MID WITH REHEAT COOLING COIL | 24.73 | 6.67 | 10.92 | 0.008732 | 0.008500 | 1511405.00 | 0.064299 | 86.40 |
VAV_TOP WITH REHEAT COOLING COIL | 24.65 | 6.67 | 11.02 | 0.008719 | 0.008500 | 160198.72 | 0.006815 | 9.29 |
CAV_BAS COOLING COIL | 24.07 | 6.67 | 11.41 | 0.008842 | 0.008500 | 94026.05 | 0.004000 | 5.72 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.38 |
VAV_MID WITH REHEAT FAN | 86.40 |
VAV_TOP WITH REHEAT FAN | 9.29 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006887 | 0.000069 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000467 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.064299 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004500 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006815 | 0.000070 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000433 | |
CAV_BAS_COOLC_CONTROLLER | 0.004000 | 0.000119 |
CAV_BAS_HEATC_CONTROLLER | 0.002451 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.72 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.58 | 426539.63 | 307267.62 | 0.010446 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.507609 | 9778.39 | 7136.49 | 0.000239 |
AIRLOOP DATACENTER MID COOLING COIL | 4.86 | 93552.38 | 68268.81 | 0.002291 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.492315 | 9485.13 | 6921.88 | 0.000232 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.58 | 21.58 | 21.58 | 21.58 | 426539.63 | 426539.63 | 17946.39 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.507609 | 0.507609 | 0.507609 | 0.507609 | 9778.39 | 9778.39 | 829.05 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.86 | 4.86 | 4.86 | 4.86 | 93552.38 | 93552.38 | 8290.49 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.492315 | 0.492315 | 0.492315 | 0.492315 | 9485.13 | 9485.13 | 829.05 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.58 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.507609 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.86 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.492315 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.58 | 426539.63 | 0.010446 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.507609 | 9778.39 | 0.000239 |
AIRLOOP DATACENTER MID HEATING COIL | 4.86 | 93552.38 | 0.002291 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.492315 | 9485.13 | 0.000232 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 17946.39 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 829.05 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8290.49 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 829.05 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000145 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.082001 | 16897.41 | |
HEATSYS1 PUMP | 0.017719 | 5336.17 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.082001 | 9.84 |
HEATSYS1 | 0.017719 | 2.13 |
COOLSYS1_SUPPLY | 0.082001 | 9.84 |
SINGLE WATER PLANT LOOP | 0.013209 | 1.59 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.082001 | 0.082001 | 344200.30 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2025384.87 | 2025384.87 | 0.017719 |
CENTRAL BOILER | 544088.59 | 533268.90 | 0.013209 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.082001 | 11698.65 |
PLANT CIRC PUMP | 0.013209 | 3368.90 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.082001 | 0.041325 | 972468.51 | 978387.60 | 0.049602 |
COOLSYS1 CHILLER2 | 0.082001 | 0.041325 | 972468.51 | 978387.60 | 0.049602 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013209 | 139666.47 | 59619.35 | 69833.23 | 7879.72 | 21448.89 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.099204 | 11.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.099204 | 29878.19 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 38.07 | 1162291.80 | 7.61 | 145286.48 |
TOWERWATERSYS COOLTOWER 2 | 38.07 | 1162291.80 | 7.61 | 145286.48 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.050290 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.328 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 14.170 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 9.328 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.751 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 25926.330 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25926.330 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 7310.116 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7310.116 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.226 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.149 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.571 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6483 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7026 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4692 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.15847945E-14 | 0.40415870E-16 | -0.13570955E-09 | -0.55776231E-17 |
51 | 8 | 0.19900788E-07 | 0.16227319E-12 | 0.35673126E-03 | -0.22627880E-09 |
52 | 7 | -0.11611995E-01 | 0.86155623E-08 | -0.22179000E-01 | 0.13203260E-03 |
53 | 6 | 0.38824249 | 0.30290701E-05 | 0.45749374 | -0.45461023E-02 |
54 | 5 | -5.0235921 | 0.11413317E-03 | -4.3290265 | 0.61113495E-01 |
55 | 4 | 32.264180 | 0.94131685E-03 | 21.001374 | -0.41231550 |
56 | 3 | -109.65428 | 0.20665218E-02 | -54.756066 | 1.4924847 |
57 | 2 | 195.57288 | 0.11699747E-02 | 77.079281 | -2.8759721 |
58 | 1 | -170.58880 | 0.12564906E-03 | -55.024271 | 2.7354972 |
59 | 0 | 57.057407 | 0.71994484E-06 | 15.597457 | |
60 | 9 | 0.92194319E-15 | 0.45185080E-16 | -0.13934922E-09 | -0.37336789E-17 |
61 | 8 | 0.20414049E-07 | 0.15291409E-12 | 0.36227410E-03 | -0.23211478E-09 |
62 | 7 | -0.11777906E-01 | 0.80689916E-08 | -0.22418053E-01 | 0.13391908E-03 |
63 | 6 | 0.39275134 | 0.28300412E-05 | 0.46134659 | -0.45992504E-02 |
64 | 5 | -5.0676021 | 0.10641223E-03 | -4.3586752 | 0.61659190E-01 |
65 | 4 | 32.458904 | 0.87600040E-03 | 21.117392 | -0.41490080 |
66 | 3 | -110.06874 | 0.19199492E-02 | -54.985491 | 1.4984722 |
67 | 2 | 195.98384 | 0.10853975E-02 | 77.289466 | -2.8824978 |
68 | 1 | -170.74067 | 0.11640795E-03 | -55.084954 | 2.7381589 |
69 | 0 | 57.057407 | 0.66605595E-06 | 15.587079 | |
70 | 9 | 0.99499981E-15 | 0.49201796E-16 | -0.11918706E-09 | -0.33210447E-17 |
71 | 8 | 0.17565796E-07 | 0.20231051E-12 | 0.33086922E-03 | -0.19972915E-09 |
72 | 7 | -0.10835659E-01 | 0.11065463E-07 | -0.21059630E-01 | 0.12320537E-03 |
73 | 6 | 0.36714142 | 0.39371282E-05 | 0.43940598 | -0.42973741E-02 |
74 | 5 | -4.8175888 | 0.14987275E-03 | -4.1895891 | 0.58559222E-01 |
75 | 4 | 31.352470 | 0.12474171E-02 | 20.455190 | -0.40021127 |
76 | 3 | -107.71307 | 0.27606440E-02 | -53.675749 | 1.4644420 |
77 | 2 | 193.64724 | 0.15741070E-02 | 76.090603 | -2.8453956 |
78 | 1 | -169.87685 | 0.17016149E-03 | -54.740743 | 2.7230195 |
79 | 0 | 57.057407 | 0.98204117E-06 | 15.647518 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5263E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.5283E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1955E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.1972E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5346E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5359E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9650E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9658E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5724E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7083E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2348E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3541E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5678E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6655E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9845E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0341E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1336 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2275E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1533 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.5980E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.5471E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1363E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1298E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4495E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5798E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7475E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2429E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3976E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5739E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6891E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9850E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0355E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5261E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.5284E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1953E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.1973E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5346E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5361E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9650E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9657E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7866E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1849E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6684E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1337E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1487E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2791E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3625E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3966E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6175E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8907E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4547E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7200E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6320E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4036E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2472E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5878E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6509E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7522E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4887E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5631E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1078E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1374E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3626E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3972E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1664E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1684E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8331E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8348E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5995E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6007E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9651E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9658E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2119E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3289E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8711E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9657E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6309E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7013E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9850E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0356E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6051E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1002E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7930E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5973E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7840E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1012E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1298E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4491E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2100E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3285E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8683E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9613E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6261E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6862E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9846E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0341E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1663E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1683E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8330E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8346E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5993E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6004E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9650E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9657E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1511E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2566E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8448E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9214E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7601E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7872E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3627E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3972E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6698E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4840E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2438E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1988E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9184E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1019E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2472E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5878E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2512E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5282E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9781E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2847E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7979E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9138E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3624E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3966E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1279 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1025 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1427 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1180 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1013 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.6204E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.7714E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.3115E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.4271E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.9609E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2513E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7733E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.3611E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.3189E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8823E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3360E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2598E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0126E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3790E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3769E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3659E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8106E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7714E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3111E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.3983E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4253E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.9354E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0851E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5957E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9407E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8823E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3360E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1277 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1026 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1425 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1182 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1013 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.6308E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.7768E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.3160E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.4224E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.9643E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.2476E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7769E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3623E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.3245E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8875E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3404E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2540E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0137E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3749E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3779E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3675E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8134E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7768E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3156E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.3938E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4278E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.9320E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0876E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5970E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9455E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8875E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3404E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 78617.37001 | 78617.37001 | 5.72143 | 5.72143 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -4.30000 | 2.65759E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 81616.98158 | 81616.98158 | 5.93915 | 5.93915 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 765281.88619 | 765281.88619 | 55.67349 | 55.67349 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 194124.25142 | 194124.25142 | 8.22879 | 10.77825 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 72871.74450 | 72871.74450 | 5.30056 | 5.30056 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 50596.92094 | 50596.92094 | 2.16978 | 2.16978 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11130.73332 | 11130.73332 | 0.81739 | 0.81739 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 5035.64904 | 5035.64904 | 0.21553 | 0.21553 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15413.32479 | 15413.32479 | 1.13187 | 1.13187 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 21.10683 | 8.39884E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3757.45656 | 3757.45656 | 0.16100 | 0.16100 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 21925.96091 | 21925.96091 | 1.61013 | 1.61013 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 26.09667 | 8.40660E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6886.33422 | 6886.33422 | 0.29550 | 0.29550 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18921.79432 | 18921.79432 | 1.38951 | 1.38951 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2067.55038 | 2067.55038 | 8.79662E-002 | 8.79662E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 99408.70850 | 99408.70850 | 7.30010 | 7.30010 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 115400.05071 | 115400.05071 | 4.96546 | 4.96546 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 158585.54026 | 158585.54026 | 11.64566 | 11.64566 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 77242.13655 | 77242.13655 | 3.32410 | 3.32410 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 222720.08599 | 222720.08599 | 16.35537 | 16.35537 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 116108.42878 | 116108.42878 | 4.99607 | 4.99607 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 167894.92441 | 167894.92441 | 12.32928 | 12.32928 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 70209.32992 | 70209.32992 | 3.02027 | 3.02027 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 10999.51958 | 10999.51958 | 0.80775 | 0.80775 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 15697.32053 | 15697.32053 | 0.67615 | 0.67615 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15583.45429 | 15583.45429 | 1.14436 | 1.14436 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 21.91067 | 8.40008E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 10413.31118 | 10413.31118 | 0.44859 | 0.44859 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 23389.91321 | 23389.91321 | 1.71763 | 1.71763 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 15784.20195 | 15784.20195 | 0.67991 | 0.67991 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 17589.11747 | 17589.11747 | 1.29165 | 1.29165 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9889.20202 | 9889.20202 | 0.42595 | 0.42595 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8763.78224 | 8763.78224 | 0.50761 | 0.50761 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 23.30600 | 8.40224E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 83828.79024 | 83828.79024 | 4.85549 | 4.85549 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 23.30600 | 8.40224E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8499.71560 | 8499.71560 | 0.49232 | 0.49232 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 23.30600 | 8.40224E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372548.60595 | 372548.60595 | 21.57820 | 21.57820 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 18.11900 | 8.39428E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | -4.30000 | 2.65759E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 130808.97 | 9.38309 | 9.38309 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 37623.00 | 1.83783 | 1.83783 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1189734.56 | 86.39523 | 86.39523 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 519567.82 | 27.08414 | 27.08414 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 131833.17 | 9.29311 | 9.29311 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 51952.67 | 4.40037 | 4.40037 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 20:20:00 |
7 | CAV_BAS | Cooling | Sensible | 71169.42 | 5.72143 | 5.72143 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 63649.34 | 1.20016 | 1.20016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 366146.57 | 21.57833 | 21.57833 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 17946.39 | 0.33839 | 0.33839 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8559.16 | 0.50761 | 0.50761 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 829.05 | 1.56323E-002 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 81841.51 | 4.85549 | 4.85549 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8290.49 | 0.15632 | 0.15632 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8299.18 | 0.49232 | 0.49232 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 829.05 | 1.56323E-002 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.72143 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.93915 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32026 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32300 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.91835 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85401 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18968E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.67184E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.91835 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19110.20977 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.67184E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 385.24683 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 55.67349 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34164 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33600 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.70629 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91105 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11520E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.32854E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.70629 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 380472.93263 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.32854E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8555.06464 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.30056 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35884 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36100 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.91350 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95690 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06176E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.31741E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.16978 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 72211.89064 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.31741E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1907.33426 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81739 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29217 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24522 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77913 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30401E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.53975E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24522 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7475.33302 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.53975E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 190.15448 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13187 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13597 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33956 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36260 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.80201E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.24324E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33956 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7136.40784 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.24324E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 161.70206 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.61013 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14833 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.48304 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39554 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56865E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02306E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.48304 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11694.25545 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02306E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 274.99960 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38951 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11076 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41685 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.43981E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.43377E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41685 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6211.12901 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.43377E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 131.64093 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.30010 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32715 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32200 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.35063 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87239 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16461E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.44204E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.96546 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 164834.14436 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44204E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4348.69043 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.64566 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13216 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.49370 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35242 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88294E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.80044E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.49370 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 112025.00840 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.80044E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2910.43722 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.35537 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14602 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.90661 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38939 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60918E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45091E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.99607 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 165847.66808 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45091E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4375.39798 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.32928 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12483 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.69878 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33288 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05218E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.36338E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.69878 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 107029.16693 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.36338E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2668.27930 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80775 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29566 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24233 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78843 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28864E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.96228E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.67615 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22430.02973 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.96228E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 591.56510 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.14436 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13449 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34331 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35864 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.83293E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.30177E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.44859 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14880.04839 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30177E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 392.43269 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.71763 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13904 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.51529 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37078 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74014E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.97315E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.67991 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22554.30835 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97315E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 594.83982 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29165 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11915 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38749 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31774 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.19754E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.23619E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42595 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14130.36749 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23619E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 372.67715 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.50761 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.85549 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49232 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.57820 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.44403 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.40302 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.88805 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.40302 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.38309 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.38309 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.36268 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 51.65195 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 33.15602 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 103.30390 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 33.15602 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 86.39523 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 86.39523 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.38377 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.13097 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.40192 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.26194 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.40037 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.29311 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.29311 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.47351 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.72143 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.72143 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.72143 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.72143 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.72143 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.72143 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.57820 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.57820 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.57820 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.57820 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.57833 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.57833 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.50761 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.50761 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.50761 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.50761 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.50761 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.50761 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.85549 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.85549 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.85549 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.85549 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.85549 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.85549 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49232 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49232 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49232 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49232 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49232 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.49232 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.38309 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 86.39523 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.29311 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.72143 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.57833 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.50761 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.85549 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.49232 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.38309 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.66036 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02357 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72139E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 161891.93254 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.88726E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.38309 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 53338.37289 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.66627E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 879.22825 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.38309 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.88726E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.91408E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.66627E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 86.39523 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.73047 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92267 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73211E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1511404.99673 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.42987E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 86.39523 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 514337.60557 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.49965E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8442.27862 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 86.39523 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.42987E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.40592E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.49965E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.29311 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.65493 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02356 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71858E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 160198.72318 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.81522E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.29311 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 49508.88865 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.33125E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 820.78585 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.29311 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.81522E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.98716E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.33125E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.72143 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.06883 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.40637 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.84190E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 94026.05046 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.00009E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.72143 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 280157.10452 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.45094E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6241.03423 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.72143 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.00009E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.19045E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.45094E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.57833 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.57833 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 426539.62943 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 307267.61555 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04459E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.57833 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.57833 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.57833 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.57833 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 426539.62943 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 426539.62943 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 17946.39161 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.57833 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.57833 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 426539.62943 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04459E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 17946.39161 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.44715E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.50761 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50761 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9778.38787 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7136.49438 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.39472E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.50761 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.50761 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.50761 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.50761 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9778.38787 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9778.38787 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 829.04894 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.50761 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50761 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9778.38787 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.39472E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 829.04894 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.85549 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.85549 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 93552.37959 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 68268.80575 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29109E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.85549 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.85549 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.85549 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.85549 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 93552.37959 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 93552.37959 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8290.48945 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.85549 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.85549 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 93552.37959 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29109E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8290.48945 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49232 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49232 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9485.13227 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6921.88345 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32290E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49232 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49232 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49232 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49232 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9485.13227 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9485.13227 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 829.04894 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49232 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49232 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9485.13227 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32290E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 829.04894 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.20012E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 16897.41406 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.20012E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.84015 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.20012E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.20012E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 344200.30409 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.77190E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.12627 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.77190E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 5336.16974 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2025384.87173 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2025384.87000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.77190E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.20012E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.84015 |
451 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 8.20012E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 11698.64975 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.20012E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.13249E-002 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 972468.51067 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 978387.60000 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.96022E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.20012E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.13249E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 972468.51067 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 978387.60000 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.96022E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.32088E-002 |
464 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.58505 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.32088E-002 |
466 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3368.90000 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.32088E-002 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59619.35198 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21448.89151 |
473 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 544088.58691 |
474 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 533268.90000 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.32088E-002 |
476 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
477 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
479 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
480 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
481 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 9.92043E-002 |
482 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 11.90452 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 9.92043E-002 |
484 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 29878.18523 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 38.06889 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1162291.80114 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 7.61378 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 145286.47514 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 38.06889 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1162291.80114 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 7.61378 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 145286.47514 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.02900E-002 |
494 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.02900E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18120.34 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 360558.91 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 68436.43 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7079.43 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6762.67 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11079.26 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5887.65 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 156182.18 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 106083.34 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 157142.30 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 101369.33 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21251.44 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14098.10 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21369.16 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13387.92 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 41184.02 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 393679.43 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 38676.91 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 222184.73 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 211191.12 | 151136.64 | 60054.48 | 0.72 | 22037.08 | 223.51 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1964858.48 | 1401838.93 | 563019.55 | 0.71 | 206019.82 | 2089.57 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 209076.77 | 149646.08 | 59430.68 | 0.72 | 21817.93 | 221.29 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 124213.34 | 89846.76 | 34366.58 | 0.72 | 12771.96 | 129.54 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 7.08 | 24.14 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 7.08 | 24.14 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3799118508 | 0.2652598119 | Pass | Pass | 0.6263142306 | 0.5688319489 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.7033404323E-003 | 4.2902228522E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.1178847054E-003 | 3.9095096457E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.2906255501E-002 | 2.5552027932E-002 | Pass | Pass | 0.5488099137 | 0.5265672349 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.5052175145E-002 | 1.3701798135E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.3843379527E-002 | 7.0428267552E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.7989075277E-002 | 9.3128290431E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.3899899156E-002 | 4.3333778453E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.0466045268E-002 | 1.9180287159E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.7402682515E-002 | 6.7368136899E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.6795281980E-002 | 9.4643673267E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.9002436876E-002 | 4.4195419365E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2233788918 | 0.2130573020 | Pass | Pass | 16.5523141697 | 34.2465411271 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1524791419 | 0.1680961056 | Pass | Pass | 9.0635685889 | 19.8864430835 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1366476591 | 0.1319533281 | Pass | Pass | 6.1957980585 | 18.0724897970 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.6468304476E-002 | 8.9006916171E-002 | Pass | Pass | 9.8913429966 | 24.5126903769 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.6210317271E-003 | 5.8558733967E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.6940850333E-003 | 8.6080118422E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.7149382653E-002 | 5.8370127171E-002 | Pass | Pass | 0.5337859414 | 0.4787326774 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.8564264928E-006 | 5.5512877743E-006 | Pass | Pass | 3.4989272491E-003 | 4.1516215677E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.1364704137E-006 | 8.0963344703E-006 | Pass | Pass | 0.1056808537 | 0.3708901157 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.0553643368E-002 | 1.9654870758E-002 | Pass | Pass | 3.8631749938E-003 | 5.0223863008E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.3653380293E-006 | 6.7600268108E-006 | Pass | Pass | 4.9128987855E-005 | 1.0726635813E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6109.53 | 131.42 | 0.00 | 25203.28 | 14841.53 | 46285.78 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 1043.06 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.171 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.3279 | 2779.43 | 25926.33 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 240.45 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.3279 | 24961.20 | 232836.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 2159.39 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.62 | 0.0000 | Y | 19.00 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.43 | 0.0000 | Y | 12.18 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.33 | 0.0000 | Y | 18.84 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.52 | 0.0000 | Y | 12.21 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.3279 | 3134.13 | 29234.97 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.66 | 0.0000 | Y | 190.20 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.44 | 0.0000 | Y | 121.81 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.3279 | 3134.20 | 29235.61 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.35 | 0.0000 | Y | 188.52 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.54 | 0.0000 | Y | 122.14 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.66 | 0.0000 | Y | 19.02 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.44 | 0.0000 | Y | 12.18 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.35 | 0.0000 | Y | 18.85 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.54 | 0.0000 | Y | 12.21 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 9.3279 | 783.68 | 7310.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 67.80 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 16.0861 | 362.03 | 5823.61 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 59.65 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
Interior Lighting Total | 9.3913 | 46320.38 | 435009.77 | 1160.71 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.01 | AstronomicalClock | - | 42.50 | 42.50 | 79.55 | |
EXTERIOR_LIGHTS_B | 44362.79 | AstronomicalClock | - | 83.54 | 71.23 | 593.14 | |
Exterior Lighting Total | 54335.80 | 672.69 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1923088.97 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2025384.87 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 978387.60 | 5.33 | 967370.46 | 4.98 | 7.08 | 24.14 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 978387.60 | 5.33 | 967370.46 | 4.98 | 7.08 | 24.14 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 533268.90 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1162291.80 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1162291.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 161891.93 | 211191.12 | 151136.64 | 60054.48 | 0.72 | - | 22037.08 | 223.51 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1511405.00 | 1964858.48 | 1401838.93 | 563019.55 | 0.71 | - | 206019.82 | 2089.57 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 160198.72 | 209076.77 | 149646.08 | 59430.68 | 0.72 | - | 21817.93 | 221.29 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 94026.05 | 124213.34 | 89846.76 | 34366.58 | 0.72 | - | 12771.96 | 129.54 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 426539.63 | 307267.62 | 119272.01 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9778.39 | 7136.49 | 2641.89 | 0.73 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 93552.38 | 68268.81 | 25283.57 | 0.73 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9485.13 | 6921.88 | 2563.25 | 0.73 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19110.21 | 18120.34 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 380472.93 | 360558.91 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 72211.89 | 68436.43 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 7475.33 | 7079.43 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 7136.41 | 6762.67 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11694.26 | 11079.26 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 6211.13 | 5887.65 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 164834.14 | 156182.18 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 112025.01 | 106083.34 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 165847.67 | 157142.30 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 107029.17 | 101369.33 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 22430.03 | 21251.44 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14880.05 | 14098.10 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22554.31 | 21369.16 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 14130.37 | 13387.92 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 53338.37 | 41184.02 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 514337.61 | 393679.43 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 49508.89 | 38676.91 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 280157.10 | 222184.73 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 426539.63 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9778.39 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 93552.38 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9485.13 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 17946.39 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 829.05 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8290.49 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 829.05 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.38 | 20276.36 | 2160.95 | 1.00 | 1.12 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 86.40 | 197303.18 | 2283.73 | 1.00 | 1.07 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.29 | 20081.92 | 2160.95 | 1.00 | 1.12 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.72 | 9701.57 | 1695.65 | 1.00 | 1.16 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.58 | 35776.29 | 1657.97 | 1.00 | 1.13 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 568.58 | 1120.11 | 1.00 | 1.60 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.86 | 5438.67 | 1120.11 | 1.00 | 1.16 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 551.45 | 1120.11 | 1.00 | 1.61 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.082001 | 16897.41 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.017719 | 5336.17 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.082001 | 11698.65 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013209 | 3368.90 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.099204 | 29878.19 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 78617.37 | 78617.37 | 28.29 | 5.721 | 5.721 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 19.67 | 0.00840 | 1.200 | 0.00 |
CORE_BOTTOM | 81616.98 | 81616.98 | 32.70 | 5.939 | 5.939 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 19.67 | 0.00840 | 1.078 | 0.00 |
CORE_MID | 765281.89 | 765281.89 | 306.59 | 55.673 | 55.673 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 19.67 | 0.00840 | 10.778 | 0.00 |
CORE_TOP | 72871.74 | 72871.74 | 29.19 | 5.301 | 5.301 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 19.67 | 0.00840 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11130.73 | 11130.73 | 35.51 | 0.817 | 0.817 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00884 | 26.40 | 0.00841 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15413.32 | 15413.32 | 76.31 | 1.132 | 1.132 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00866 | 21.11 | 0.00840 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 21925.96 | 21925.96 | 69.96 | 1.610 | 1.610 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00867 | 26.10 | 0.00841 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18921.79 | 18921.79 | 93.68 | 1.390 | 1.390 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00863 | 25.13 | 0.00841 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 99408.71 | 99408.71 | 317.18 | 7.300 | 7.300 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00887 | 26.40 | 0.00841 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 158585.54 | 158585.54 | 785.17 | 11.646 | 11.646 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00865 | 21.39 | 0.00840 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 222720.09 | 222720.09 | 710.61 | 16.355 | 16.355 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00867 | 26.17 | 0.00841 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 167894.92 | 167894.92 | 831.27 | 12.329 | 12.329 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00864 | 24.97 | 0.00840 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 10999.52 | 10999.52 | 35.10 | 0.808 | 0.808 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00883 | 26.40 | 0.00841 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15583.45 | 15583.45 | 77.16 | 1.144 | 1.144 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.00 | 24.00 | 0.00865 | 21.91 | 0.00840 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 23389.91 | 23389.91 | 74.63 | 1.718 | 1.718 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00866 | 26.25 | 0.00841 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17589.12 | 17589.12 | 87.09 | 1.292 | 1.292 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00864 | 24.97 | 0.00840 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8763.78 | 8763.78 | 242.08 | 0.508 | 0.508 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00858 | 23.31 | 0.00840 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 83828.79 | 83828.79 | 2315.54 | 4.855 | 4.855 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 23.31 | 0.00840 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8499.72 | 8499.72 | 234.78 | 0.492 | 0.492 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 23.31 | 0.00840 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372548.61 | 372548.61 | 475.38 | 21.578 | 21.578 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 18.12 | 0.00839 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 24.38 | 0.00266 | -4.30 | 0.00266 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 19.60 | 22.13 | 0.00266 | -4.30 | 0.00266 | 1.078 | 0.00 |
CORE_MID | 194124.25 | 194124.25 | 77.77 | 8.229 | 10.778 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 10.778 | 0.00 |
CORE_TOP | 50596.92 | 50596.92 | 20.27 | 2.170 | 2.170 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 5035.65 | 5035.65 | 16.07 | 0.216 | 0.216 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00737 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3757.46 | 3757.46 | 18.60 | 0.161 | 0.161 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6886.33 | 6886.33 | 21.97 | 0.296 | 0.296 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00760 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2067.55 | 2067.55 | 10.24 | 0.088 | 0.088 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00688 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 115400.05 | 115400.05 | 368.20 | 4.965 | 4.965 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -4.30 | 0.00266 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 77242.14 | 77242.14 | 382.43 | 3.324 | 3.324 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -4.30 | 0.00266 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 116108.43 | 116108.43 | 370.46 | 4.996 | 4.996 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.30 | 0.00266 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 70209.33 | 70209.33 | 347.61 | 3.020 | 3.020 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -4.30 | 0.00266 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15697.32 | 15697.32 | 50.09 | 0.676 | 0.676 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 10413.31 | 10413.31 | 51.56 | 0.449 | 0.449 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15784.20 | 15784.20 | 50.36 | 0.680 | 0.680 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9889.20 | 9889.20 | 48.96 | 0.426 | 0.426 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -4.30 | 0.00266 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 18.00 | 26.75 | 0.00850 | -4.30 | 0.00266 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 23.61 | 0.00647 | -4.30 | 0.00266 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 21.72 | 0.00298 | -4.30 | 0.00266 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 18.00 | 27.00 | 0.00850 | -4.30 | 0.00266 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.38 | 9.38 | 1.84 | 1.84 | 9.3831 | 3.4030 | 9.3831 | 0.3627 | 0.3000 |
VAV_MID WITH REHEAT | 86.40 | 86.40 | 27.08 | 27.08 | 86.3952 | 33.1560 | 86.3952 | 0.3838 | 0.3000 |
VAV_TOP WITH REHEAT | 9.29 | 9.29 | 4.40 | 4.40 | 9.2931 | 4.4004 | 9.2931 | 0.4735 | 0.3000 |
CAV_BAS | 5.72 | 5.72 | 1.20 | 1.20 | 5.7214 | 5.7214 | 5.7214 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.58 | 21.58 | 0.34 | 0.34 | 21.5783 | 21.5782 | 21.5783 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.51 | 0.51 | 0.02 | 0.02 | 0.5076 | 0.5076 | 0.5076 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.86 | 4.86 | 0.16 | 0.16 | 4.8555 | 4.8555 | 4.8555 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.49 | 0.49 | 0.02 | 0.02 | 0.4923 | 0.4923 | 0.4923 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19110.210 | 19110.210 | 1.918346 | 0.00016718 | 385.247 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 19110.21 | 19110.21 | 1.918346 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 0.00 | 0.00 | 19180.67 | 19180.67 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 380472.933 | 380472.933 | 18.706292 | 0.00332854 | 8555.065 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 380472.93 | 380472.93 | 18.706292 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 194124.25 | 0.00 | 381773.81 | 381773.81 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 72211.891 | 72211.891 | 2.169782 | 0.00063174 | 1907.334 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 72211.89 | 72211.89 | 2.169782 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 50596.92 | 0.00 | 72469.75 | 72469.75 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7475.333 | 7475.333 | 0.245217 | 0.00006540 | 190.154 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7475.33 | 7475.33 | 0.245217 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00737301 | 47.2078 | 5035.65 | 0.00 | 7498.43 | 7498.43 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7136.408 | 7136.408 | 0.339562 | 0.00006243 | 161.702 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7136.41 | 7136.41 | 0.339562 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00747122 | 47.8291 | 3757.46 | 0.00 | 7160.73 | 7160.73 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 11694.255 | 11694.255 | 0.483038 | 0.00010231 | 275.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11694.26 | 11694.26 | 0.483038 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00760295 | 48.6617 | 6886.33 | 0.00 | 11732.57 | 11732.57 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6211.129 | 6211.129 | 0.416854 | 0.00005434 | 131.641 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6211.13 | 6211.13 | 0.416854 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00688415 | 44.1122 | 2067.55 | 0.00 | 6233.06 | 6233.06 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 164834.144 | 164834.144 | 4.965457 | 0.00144204 | 4348.690 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 164834.14 | 164834.14 | 4.965457 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00772281 | 49.4197 | 115400.05 | 0.00 | 165386.32 | 165386.32 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 112025.008 | 112025.008 | 3.493697 | 0.00098004 | 2910.437 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 112025.01 | 112025.01 | 3.493697 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00773695 | 49.5090 | 77242.14 | 0.00 | 112367.98 | 112367.98 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 165847.668 | 165847.668 | 4.996066 | 0.00145091 | 4375.398 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 165847.67 | 165847.67 | 4.996066 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00772667 | 49.4440 | 116108.43 | 0.00 | 166403.01 | 166403.01 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 107029.167 | 107029.167 | 3.698784 | 0.00093634 | 2668.279 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 107029.17 | 107029.17 | 3.698784 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00767491 | 49.1172 | 70209.33 | 0.00 | 107363.33 | 107363.33 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22430.030 | 22430.030 | 0.676153 | 0.00019623 | 591.565 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22430.03 | 22430.03 | 0.676153 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00780974 | 49.9685 | 15697.32 | 0.00 | 22503.81 | 22503.81 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14880.048 | 14880.048 | 0.448586 | 0.00013018 | 392.433 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14880.05 | 14880.05 | 0.448586 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00781056 | 49.9737 | 10413.31 | 0.00 | 14928.92 | 14928.92 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22554.308 | 22554.308 | 0.679907 | 0.00019731 | 594.840 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22554.31 | 22554.31 | 0.679907 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00781111 | 49.9772 | 15784.20 | 0.00 | 22628.47 | 22628.47 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14130.367 | 14130.367 | 0.425945 | 0.00012362 | 372.677 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14130.37 | 14130.37 | 0.425945 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00779560 | 49.8793 | 9889.20 | 0.00 | 14176.89 | 14176.89 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 161891.933 | -999.000 | 9.383093 | 0.00688726 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 161891.93 | 155399.77 | 9.383093 | 24.66 | 16.70 | 0.00872139 | 11.02 | 11.02 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 27.0507 | 24.00 | 0.00884092 | 47.0636 | 125452.59 | 0.00 | 163373.31 | 145632.64 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 53338.373 | 53338.373 | 2.814928 | 0.00046663 | 879.228 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 53338.37 | 53338.37 | 2.814928 | -3.03 | -3.21 | 0.00285147 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 90.1689 | 21.55 | 0.00517354 | 32.1418 | 17746.99 | 0.00 | 49826.65 | 49826.65 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1511404.997 | -999.000 | 86.395228 | 0.06429866 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1511405.00 | 1448300.47 | 86.395228 | 24.73 | 16.73 | 0.00873211 | 10.92 | 10.92 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 29.3789 | 24.00 | 0.00887456 | 47.2402 | 1134311.56 | 0.00 | 1525264.18 | 1355027.58 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 514337.606 | 514337.606 | 25.918568 | 0.00449965 | 8442.279 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 514337.61 | 514337.61 | 25.918568 | -3.78 | -3.80 | 0.00276552 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 97.9296 | 21.00 | 0.00784987 | 50.2210 | 504871.90 | 0.00 | 476271.19 | 476271.19 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 160198.723 | -999.000 | 9.293111 | 0.00681522 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 160198.72 | 153850.43 | 9.293111 | 24.65 | 16.70 | 0.00871858 | 11.02 | 11.02 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 27.3126 | 24.00 | 0.00883569 | 47.0362 | 126492.90 | 0.00 | 161665.16 | 144167.85 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 49508.889 | 49508.889 | 2.787933 | 0.00043313 | 820.786 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 20:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 49508.89 | 49508.89 | 2.787933 | -2.03 | -2.19 | 0.00312269 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 91.0420 | 21.00 | 0.00784960 | 50.2193 | 58606.77 | 0.00 | 46797.91 | 46797.91 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 94026.050 | -999.000 | 5.721434 | 0.00400009 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 94026.05 | 88079.87 | 5.721434 | 24.07 | 16.60 | 0.00884190 | 11.41 | 11.41 | 0.00850000 | 24.31 | 0.00840380 | 16.31 | 20.9765 | 24.00 | 0.00897091 | 47.7462 | 77564.74 | 0.00 | 94883.63 | 83301.24 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 280157.105 | 280157.105 | 5.721434 | 0.00245094 | 6241.034 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 280157.10 | 280157.10 | 5.721434 | -0.90 | -2.29 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 20.9765 | 24.43 | 0.00265759 | 13.9239 | 0.00 | 0.00 | 234762.50 | 234762.50 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 426539.629 | 307267.616 | 21.578331 | 0.01044593 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 396992.51 | 394661.31 | -999.0 | 28.40 | 17.83 | 0.00854005 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | -999.0000 | 27.00 | 0.00854217 | 38.0732 | 372143.15 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9778.388 | 7136.494 | 0.507609 | 0.00023947 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9061.66 | 8956.60 | -999.0 | 27.84 | 17.67 | 0.00857693 | 12.80 | 12.00 | 0.00850000 | 23.31 | 0.00840224 | 15.95 | -999.0000 | 27.00 | 0.00858248 | 38.2479 | 8763.78 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93552.380 | 68268.806 | 4.855490 | 0.00229109 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 86697.58 | 85648.65 | -999.0 | 27.84 | 17.67 | 0.00858030 | 12.80 | 12.00 | 0.00850000 | 23.31 | 0.00840224 | 15.95 | -999.0000 | 27.00 | 0.00858622 | 38.2645 | 83828.79 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9485.132 | 6921.883 | 0.492315 | 0.00023229 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8790.08 | 8685.03 | -999.0 | 27.84 | 17.67 | 0.00857931 | 12.80 | 12.00 | 0.00850000 | 23.31 | 0.00840224 | 15.95 | -999.0000 | 27.00 | 0.00858512 | 38.2596 | 8499.72 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 426539.629 | 426539.629 | 21.578331 | 0.01044593 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 426539.63 | 426539.63 | 21.578331 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 1.5682 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9778.388 | 9778.388 | 0.507609 | 0.00023947 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9778.39 | 9778.39 | 0.507609 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.0796 | 26.98 | 0.00850000 | 37.9283 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93552.380 | 93552.380 | 4.855490 | 0.00229109 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 93552.38 | 93552.38 | 4.855490 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.2195 | 24.76 | 0.00646541 | 33.0078 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9485.132 | 9485.132 | 0.492315 | 0.00023229 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9485.13 | 9485.13 | 0.492315 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1753 | 23.56 | 0.00298326 | 16.4560 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 17946.392 | 17946.392 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 17946.39 | 17946.39 | 21.578331 | -0.07 | -0.07 | 0.00840838 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 1.5682 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 829.05 | 829.05 | 0.507609 | -0.13 | -0.13 | 0.00832008 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.0796 | 26.98 | 0.00850000 | 37.9283 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8290.489 | 8290.489 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8290.49 | 8290.49 | 4.855490 | -0.14 | -0.14 | 0.00634282 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.2195 | 24.76 | 0.00646541 | 33.0078 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 829.05 | 829.05 | 0.492315 | -0.14 | -1.36 | 0.00297292 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1753 | 23.56 | 0.00298326 | 16.4560 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19110.210 | 19110.210 | 1.918346 | 0.00016718 | 385.247 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 0.9249 | 0.943535 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | Sensible | 19110.21 | 19110.21 | 1.0000 | 2.28546325 | 1.918346 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.16716740 | 60.00 | 32.22 | 27.78 | 0.000 | 19110.21 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 0.00 | 0.00 | 19180.67 | 19180.67 | 2.28546325 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 380472.933 | 380472.933 | 18.706292 | 0.00332854 | 8555.065 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 18.4146 | 18.785216 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 380472.93 | 380472.93 | 1.0000 | 22.28615326 | 18.706292 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 3.32820365 | 60.00 | 32.22 | 27.78 | 0.000 | 380472.93 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.56 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 194124.25 | 0.00 | 381773.81 | 381773.81 | 22.28615326 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.60 | 17.90 | 0.00800000 | 50190.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 72211.891 | 72211.891 | 2.169782 | 0.00063174 | 1907.334 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 3.4950 | 3.565342 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 72211.89 | 72211.89 | 1.0000 | 2.58501709 | 2.169782 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.63167668 | 60.00 | 32.22 | 27.78 | 0.000 | 72211.89 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 50596.92 | 0.00 | 72469.75 | 72469.75 | 2.58501709 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.29 | 21.27 | 0.00800000 | 61094.4 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7475.333 | 7475.333 | 0.245217 | 0.00006540 | 190.154 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 0.3618 | 0.369082 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7475.33 | 7475.33 | 1.0000 | 0.29214444 | 0.245217 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.06539080 | 60.00 | 32.22 | 27.78 | 0.000 | 7475.33 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.86 | 0.00737301 | 21.00 | 0.00737301 | 47.2078 | 5035.65 | 0.00 | 7498.43 | 7498.43 | 0.29214444 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.97 | 20.57 | 0.00800000 | 58726.7 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7136.408 | 7136.408 | 0.339562 | 0.00006243 | 161.702 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 0.3454 | 0.352348 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7136.41 | 7136.41 | 1.0000 | 0.40454437 | 0.339562 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.06242604 | 60.00 | 32.22 | 27.78 | 0.000 | 7136.41 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.92 | 0.00747122 | 21.00 | 0.00747122 | 47.8291 | 3757.46 | 0.00 | 7160.73 | 7160.73 | 0.40454437 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.16 | 18.09 | 0.00800000 | 50760.6 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11694.255 | 11694.255 | 0.483038 | 0.00010231 | 275.000 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 0.5660 | 0.577384 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11694.26 | 11694.26 | 1.0000 | 0.57547841 | 0.483038 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.10229601 | 60.00 | 32.22 | 27.78 | 0.000 | 11694.26 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00760295 | 21.00 | 0.00760295 | 48.6617 | 6886.33 | 0.00 | 11732.57 | 11732.57 | 0.57547841 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.79 | 18.95 | 0.00800000 | 53447.3 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6211.129 | 6211.129 | 0.416854 | 0.00005434 | 131.641 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 0.3006 | 0.306664 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6211.13 | 6211.13 | 1.0000 | 0.49662780 | 0.416854 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.05433212 | 60.00 | 32.22 | 27.78 | 0.000 | 6211.13 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.87 | 0.00688415 | 21.00 | 0.00688415 | 44.1122 | 2067.55 | 0.00 | 6233.06 | 6233.06 | 0.49662780 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.11 | 16.35 | 0.00800000 | 45610.6 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 164834.144 | 164834.144 | 4.965457 | 0.00144204 | 4348.690 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 7.9779 | 8.138411 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 164834.14 | 164834.14 | 1.0000 | 5.91570601 | 4.965457 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 1.44189390 | 60.00 | 32.22 | 27.78 | 0.000 | 164834.14 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00772281 | 21.00 | 0.00772281 | 49.4197 | 115400.05 | 0.00 | 165386.32 | 165386.32 | 5.91570601 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61017.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 112025.008 | 112025.008 | 3.493697 | 0.00098004 | 2910.437 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 5.4219 | 5.531048 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 112025.01 | 112025.01 | 1.0000 | 4.16229272 | 3.493697 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.97994367 | 60.00 | 32.22 | 27.78 | 0.000 | 112025.01 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00773695 | 21.00 | 0.00773695 | 49.5090 | 77242.14 | 0.00 | 112367.98 | 112367.98 | 4.16229272 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.27 | 20.97 | 0.00800000 | 60056.5 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 165847.668 | 165847.668 | 4.996066 | 0.00145091 | 4375.398 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 8.0269 | 8.188452 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 165847.67 | 165847.67 | 1.0000 | 5.95217366 | 4.996066 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 1.45075974 | 60.00 | 32.22 | 27.78 | 0.000 | 165847.67 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00772667 | 21.00 | 0.00772667 | 49.4440 | 116108.43 | 0.00 | 166403.01 | 166403.01 | 5.95217366 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61016.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 107029.167 | 107029.167 | 3.698784 | 0.00093634 | 2668.279 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 5.1801 | 5.284387 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 107029.17 | 107029.17 | 1.0000 | 4.40662828 | 3.698784 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.93624233 | 60.00 | 32.22 | 27.78 | 0.000 | 107029.17 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00767491 | 21.00 | 0.00767491 | 49.1172 | 70209.33 | 0.00 | 107363.33 | 107363.33 | 4.40662828 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.69 | 20.18 | 0.00800000 | 57423.9 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22430.030 | 22430.030 | 0.676153 | 0.00019623 | 591.565 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 1.0856 | 1.107445 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22430.03 | 22430.03 | 1.0000 | 0.80554943 | 0.676153 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.19620767 | 60.00 | 32.22 | 27.78 | 0.000 | 22430.03 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00780974 | 21.00 | 0.00780974 | 49.9685 | 15697.32 | 0.00 | 22503.81 | 22503.81 | 0.80554943 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60995.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14880.048 | 14880.048 | 0.448586 | 0.00013018 | 392.433 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 0.7202 | 0.734678 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14880.05 | 14880.05 | 1.0000 | 0.53443224 | 0.448586 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.13016388 | 60.00 | 32.22 | 27.78 | 0.000 | 14880.05 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00781056 | 21.00 | 0.00781056 | 49.9737 | 10413.31 | 0.00 | 14928.92 | 14928.92 | 0.53443224 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60994.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22554.308 | 22554.308 | 0.679907 | 0.00019731 | 594.840 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 1.0916 | 1.113581 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22554.31 | 22554.31 | 1.0000 | 0.81002165 | 0.679907 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.19729480 | 60.00 | 32.22 | 27.78 | 0.000 | 22554.31 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00781111 | 21.00 | 0.00781111 | 49.9772 | 15784.20 | 0.00 | 22628.47 | 22628.47 | 0.81002165 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60995.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14130.367 | 14130.367 | 0.425945 | 0.00012362 | 372.677 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 0.6839 | 0.697663 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14130.37 | 14130.37 | 1.0000 | 0.50745945 | 0.425945 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.12360601 | 60.00 | 32.22 | 27.78 | 0.000 | 14130.37 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00779560 | 21.00 | 0.00779560 | 49.8793 | 9889.20 | 0.00 | 14176.89 | 14176.89 | 0.50745945 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.8 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 161891.933 | -999.000 | 9.383093 | 0.00688726 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0526 | 1004.8586 | 1.1914 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.383093 | 11.17875440 | 4197.9300 | 999.8980 | 81.99286412 | 12.27 | 6.67 | 5.60 | 1927521.70 | 8.3990 | 8.398968 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 161891.93 | 155399.77 | 1.0000 | 11.17875440 | 9.383093 | 24.66 | 16.70 | 0.00872139 | 46991.2 | 11.02 | 11.02 | 0.00850000 | 32509.1 | 6.88655448 | 6.67 | 12.27 | 5.60 | 20276.364 | 141615.57 | 26.40 | 0.00840708 | 17.04 | 2.53819000 | 27.0507 | 24.00 | 0.00884092 | 24.00 | 0.00884092 | 47.0636 | 125452.59 | 0.00 | 163373.31 | 145632.64 | 11.17875440 | 24.66 | 16.81 | 0.00872139 | 46991.2 | 11.90 | 11.31 | 0.00809239 | 32376.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 53338.373 | 53338.373 | 2.814928 | 0.00046663 | 879.228 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.383093 | 11.17875440 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 2.5815 | 2.633493 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 53338.37 | 53338.37 | 1.0000 | 3.35362632 | 2.814928 | -3.03 | -3.21 | 0.00285147 | 4072.9 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 0.46657975 | 60.00 | 32.22 | 27.78 | 0.000 | 53338.37 | -4.30 | 0.00265759 | -4.30 | 2.53819000 | 90.1689 | 8.64 | 0.00462975 | 21.55 | 0.00517354 | 32.1418 | 17746.99 | 0.00 | 49826.65 | 49826.65 | 3.35362632 | 2.80 | 0.31 | 0.00285147 | 9959.8 | 17.51 | 8.08 | 0.00285147 | 24817.3 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1511404.997 | -999.000 | 86.395228 | 0.06429866 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0726 | 1004.8586 | 1.1914 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 86.395228 | 102.92885657 | 4197.9300 | 999.8980 | 81.99286412 | 12.27 | 6.67 | 5.60 | 1927521.70 | 78.4118 | 78.411828 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1511405.00 | 1448300.47 | 1.0000 | 102.92885657 | 86.395228 | 24.73 | 16.73 | 0.00873211 | 47090.1 | 10.92 | 10.92 | 0.00850000 | 32406.1 | 64.29210335 | 6.67 | 12.27 | 5.60 | 197303.185 | 1314101.81 | 26.40 | 0.00840708 | 17.04 | 25.38195000 | 29.3789 | 24.00 | 0.00887456 | 24.00 | 0.00887456 | 47.2402 | 1134311.56 | 0.00 | 1525264.18 | 1355027.58 | 102.92885657 | 24.73 | 16.84 | 0.00873211 | 47090.1 | 11.84 | 11.27 | 0.00807656 | 32271.5 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 514337.606 | 514337.606 | 25.918568 | 0.00449965 | 8442.279 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 86.395228 | 102.92885657 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 24.8936 | 25.394561 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 514337.61 | 514337.61 | 1.0000 | 30.87865697 | 25.918568 | -3.78 | -3.80 | 0.00276552 | 3102.5 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 4.49919074 | 60.00 | 32.22 | 27.78 | 0.000 | 514337.61 | -4.30 | 0.00265759 | -4.30 | 25.38195000 | 97.9296 | 21.00 | 0.00787062 | 21.00 | 0.00784987 | 50.2210 | 504871.90 | 0.00 | 476271.19 | 476271.19 | 30.87865697 | 2.80 | 0.18 | 0.00276552 | 9744.3 | 18.07 | 8.24 | 0.00276552 | 25168.3 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 160198.723 | -999.000 | 9.293111 | 0.00681522 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0474 | 1004.8586 | 1.1914 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.293111 | 11.07155243 | 4197.9300 | 999.8980 | 81.99286412 | 12.27 | 6.67 | 5.60 | 1927521.70 | 8.3111 | 8.311124 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 160198.72 | 153850.43 | 1.0000 | 11.07155243 | 9.293111 | 24.65 | 16.70 | 0.00871858 | 46978.5 | 11.02 | 11.02 | 0.00850000 | 32509.1 | 6.81452879 | 6.67 | 12.27 | 5.60 | 20081.918 | 140116.81 | 26.40 | 0.00840708 | 17.04 | 2.53819000 | 27.3126 | 24.00 | 0.00883569 | 24.00 | 0.00883569 | 47.0362 | 126492.90 | 0.00 | 161665.16 | 144167.85 | 11.07155243 | 24.65 | 16.81 | 0.00871858 | 46978.5 | 11.90 | 11.31 | 0.00809220 | 32376.6 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 49508.889 | 49508.889 | 2.787933 | 0.00043313 | 820.786 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.293111 | 11.07155243 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 2.3962 | 2.444419 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 20:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 49508.89 | 49508.89 | 1.0000 | 3.32146573 | 2.787933 | -2.03 | -2.19 | 0.00312269 | 5754.3 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 0.43308117 | 60.00 | 32.22 | 27.78 | 0.000 | 49508.89 | -4.30 | 0.00265759 | -4.30 | 2.53819000 | 91.0420 | 21.00 | 0.00784960 | 21.00 | 0.00784960 | 50.2193 | 58606.77 | 0.00 | 46797.91 | 46797.91 | 3.32146573 | 2.80 | 0.70 | 0.00312269 | 10639.5 | 16.74 | 8.03 | 0.00312269 | 24729.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 94026.050 | -999.000 | 5.721434 | 0.00400009 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2766 | 1004.8586 | 1.1914 | CAV_BAS FAN | Fan:ConstantVolume | 5.721434 | 6.81635592 | 4197.9300 | 999.8980 | 81.99286412 | 12.27 | 6.67 | 5.60 | 1927521.70 | 4.8781 | 4.878080 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 94026.05 | 88079.87 | 1.0000 | 6.81635592 | 5.721434 | 24.07 | 16.60 | 0.00884190 | 46694.0 | 11.41 | 11.41 | 0.00850000 | 32899.8 | 3.99967750 | 6.67 | 12.27 | 5.60 | 9701.574 | 84324.48 | 24.31 | 0.00840380 | 16.31 | 1.20015641 | 20.9765 | 24.00 | 0.00897091 | 24.00 | 0.00897091 | 47.7462 | 77564.74 | 0.00 | 94883.63 | 83301.24 | 6.81635592 | 24.07 | 16.71 | 0.00884190 | 46694.0 | 12.10 | 11.47 | 0.00816853 | 32774.0 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 280157.105 | 280157.105 | 5.721434 | 0.00245094 | 6241.034 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | CAV_BAS FAN | Fan:ConstantVolume | 5.721434 | 6.81635592 | 4197.9300 | 999.8980 | 17.71714289 | 54.44 | 82.22 | 27.78 | 2066146.55 | 13.5594 | 13.832290 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 280157.10 | 280157.10 | 1.0000 | 6.81635592 | 5.721434 | -0.90 | -2.29 | 0.00265759 | 5735.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 2.45068654 | 60.00 | 32.22 | 27.78 | 0.000 | 280157.10 | -4.30 | 0.00265759 | -4.30 | 1.20015641 | 20.9765 | 0.00 | 0.00265759 | 24.43 | 0.00265759 | 13.9239 | 0.00 | 0.00 | 234762.50 | 234762.50 | 6.81635592 | 12.80 | 5.54 | 0.00265759 | 19571.7 | 46.91 | 19.27 | 0.00265759 | 54012.7 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 426539.629 | 307267.616 | 21.578331 | 0.01044593 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7155 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 396992.51 | 394661.31 | 0.9307 | -999.0 | -999.0 | 28.40 | 17.83 | 0.00854005 | 50349.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 396992.51 | 26.40 | 0.00840708 | 17.04 | 0.33839277 | -999.0000 | 27.00 | 0.00854217 | 27.00 | 0.00854217 | 38.0732 | 372143.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9778.388 | 7136.494 | 0.507609 | 0.00023947 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7841 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 9061.66 | 8956.60 | 0.9267 | -999.0 | -999.0 | 27.84 | 17.67 | 0.00857693 | 49869.5 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9061.66 | 23.31 | 0.00840224 | 15.95 | 0.01563234 | -999.0000 | 27.00 | 0.00858248 | 27.00 | 0.00858248 | 38.2479 | 8763.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 93552.380 | 68268.806 | 4.855490 | 0.00229109 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7903 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 86697.58 | 85648.65 | 0.9267 | -999.0 | -999.0 | 27.84 | 17.67 | 0.00858030 | 49872.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86697.58 | 23.31 | 0.00840224 | 15.95 | 0.15632344 | -999.0000 | 27.00 | 0.00858622 | 27.00 | 0.00858622 | 38.2645 | 83828.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9485.132 | 6921.883 | 0.492315 | 0.00023229 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7885 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8790.08 | 8685.03 | 0.9267 | -999.0 | -999.0 | 27.84 | 17.67 | 0.00857931 | 49871.9 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8790.08 | 23.31 | 0.00840224 | 15.95 | 0.01563234 | -999.0000 | 27.00 | 0.00858512 | 27.00 | 0.00858512 | 38.2596 | 8499.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 426539.629 | 426539.629 | 21.578331 | 0.01044593 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 426539.63 | 426539.63 | 1.0000 | 25.70782007 | 21.578331 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 426539.63 | -4.30 | 0.00265759 | -4.30 | 0.33839277 | 1.5682 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9778.388 | 9778.388 | 0.507609 | 0.00023947 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9778.39 | 9778.39 | 1.0000 | 0.60475109 | 0.507609 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9778.39 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.0796 | 0.00 | 0.00850000 | 26.98 | 0.00850000 | 37.9283 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 93552.380 | 93552.380 | 4.855490 | 0.00229109 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 93552.38 | 93552.38 | 1.0000 | 5.78469435 | 4.855490 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93552.38 | -4.30 | 0.00265759 | -4.30 | 0.15632344 | 3.2195 | 0.00 | 0.00646541 | 24.76 | 0.00646541 | 33.0078 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9485.132 | 9485.132 | 0.492315 | 0.00023229 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9485.13 | 9485.13 | 1.0000 | 0.58653062 | 0.492315 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9485.13 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.1753 | 0.00 | 0.00298326 | 23.56 | 0.00298326 | 16.4560 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17946.392 | 17946.392 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.578331 | 25.70782007 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 17946.39 | 17946.39 | 1.0000 | 25.70782007 | 21.578331 | -0.07 | -0.07 | 0.00840838 | 20960.0 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17946.39 | -4.30 | 0.00265759 | -4.30 | 0.33839277 | 1.5682 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.507609 | 0.60475109 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 829.05 | 829.05 | 1.0000 | 0.60475109 | 0.507609 | -0.13 | -0.13 | 0.00832008 | 20672.9 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 829.05 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.0796 | 0.00 | 0.00850000 | 26.98 | 0.00850000 | 37.9283 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8290.489 | 8290.489 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.855490 | 5.78469435 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8290.49 | 8290.49 | 1.0000 | 5.78469435 | 4.855490 | -0.14 | -0.14 | 0.00634282 | 15722.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8290.49 | -4.30 | 0.00265759 | -4.30 | 0.15632344 | 3.2195 | 0.00 | 0.00646541 | 24.76 | 0.00646541 | 33.0078 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.492315 | 0.58653062 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 829.05 | 829.05 | 1.0000 | 0.58653062 | 0.492315 | -0.14 | -1.36 | 0.00297292 | 7297.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 829.05 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.1753 | 0.00 | 0.00298326 | 23.56 | 0.00298326 | 16.4560 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.38 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 86.40 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.29 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.72 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2511.50 | 161.83 | 0.00 |
CORE_BOTTOM | 2468.67 | 408.50 | 12.33 |
CORE_MID | 1174.83 | 2445.83 | 12.33 |
CORE_TOP | 1203.17 | 3986.00 | 350.17 |
PERIMETER_BOT_ZN_3 | 1149.00 | 3321.33 | 15.00 |
PERIMETER_BOT_ZN_2 | 1360.83 | 3851.50 | 65.33 |
PERIMETER_BOT_ZN_1 | 1625.33 | 3504.00 | 72.50 |
PERIMETER_BOT_ZN_4 | 2417.17 | 2466.33 | 70.33 |
PERIMETER_MID_ZN_3 | 1239.33 | 4601.33 | 698.50 |
PERIMETER_MID_ZN_2 | 1411.00 | 3839.50 | 637.33 |
PERIMETER_MID_ZN_1 | 1611.00 | 4070.67 | 394.33 |
PERIMETER_MID_ZN_4 | 1424.50 | 4556.33 | 501.67 |
PERIMETER_TOP_ZN_3 | 2184.50 | 4940.50 | 1714.33 |
PERIMETER_TOP_ZN_2 | 2544.83 | 4529.33 | 1580.00 |
PERIMETER_TOP_ZN_1 | 2268.00 | 4451.33 | 1241.17 |
PERIMETER_TOP_ZN_4 | 2114.17 | 4800.00 | 1329.50 |
DATACENTER_BOT_ZN_6 | 5943.00 | 707.67 | 707.67 |
DATACENTER_MID_ZN_6 | 5924.33 | 71.67 | 71.67 |
DATACENTER_TOP_ZN_6 | 5529.67 | 231.50 | 141.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5823.17 | 5823.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5939.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 66.50 | 0.00 | 4.50 |
CORE_BOTTOM | 0.00 | 2.33 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 9.67 | 0.00 | 9.67 |
PERIMETER_BOT_ZN_1 | 0.00 | 11.50 | 0.00 | 11.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 31.33 | 0.00 | 15.67 |
PERIMETER_MID_ZN_3 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 1.50 | 6.67 | 0.00 | 6.67 |
PERIMETER_MID_ZN_1 | 0.33 | 9.67 | 0.00 | 9.67 |
PERIMETER_MID_ZN_4 | 0.17 | 12.50 | 0.00 | 6.83 |
PERIMETER_TOP_ZN_3 | 54.67 | 0.00 | 14.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 26.00 | 4.00 | 0.50 | 4.00 |
PERIMETER_TOP_ZN_1 | 18.83 | 7.50 | 0.00 | 7.50 |
PERIMETER_TOP_ZN_4 | 16.17 | 12.17 | 0.00 | 6.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 12.50 | 0.00 | 10.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 57.00 | 152.50 | 14.67 | 66.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.39 | 149.60 | 6779.02 | 1.368 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.14 | 134.35 | 6849.35 | 1.042 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.14 | 134.35 | 6849.35 | 0.787 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.14 | 134.35 | 6849.35 | 0.709 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.92 | 16.87 | 860.00 | 0.884 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.46 | 10.87 | 554.22 | 1.571 | 0.026 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.92 | 16.87 | 860.02 | 1.609 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.46 | 10.87 | 554.22 | 2.113 | 0.026 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.92 | 16.87 | 860.00 | 0.687 | 0.059 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.89 | 10.87 | 554.22 | 1.407 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.92 | 16.87 | 860.02 | 1.530 | 0.059 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.46 | 10.87 | 554.22 | 1.612 | 0.061 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.92 | 16.87 | 860.00 | 0.661 | 0.073 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.46 | 10.87 | 554.22 | 1.439 | 0.075 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.92 | 16.87 | 860.02 | 1.494 | 0.073 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.46 | 10.87 | 554.22 | 1.613 | 0.075 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.31 | 42.18 | 1911.37 | 0.480 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.39 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.14 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.14 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.14 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.92 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.46 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.92 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.46 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.92 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.89 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.92 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.46 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.92 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.46 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.92 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.46 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.31 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.39 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.14 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.14 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.14 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.92 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.46 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.92 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.46 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.92 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.89 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.92 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.46 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.92 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.46 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.92 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.46 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.31 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1017.45 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 56188394.06 | 0.00 | 56188394.06 | 0.00 | 56188394.06 | 37848132.68 | 3926.55 | 114.09 | 4719.35 | 402.00 |
CORE_BOTTOM | 43783270.58 | 0.00 | 43783270.58 | 0.00 | 43783270.58 | 33990283.35 | 4225.67 | 63.04 | 4471.29 | 418.70 |
CORE_MID | 0.32E+09 | 0.00 | 0.32E+09 | 0.00 | 0.32E+09 | 0.34E+09 | 5350.36 | 72.04 | 3337.61 | 123.38 |
CORE_TOP | 28802273.01 | 0.00 | 28802273.01 | 0.00 | 28802273.01 | 33990283.35 | 6125.69 | 51.68 | 2582.63 | 218.28 |
PERIMETER_BOT_ZN_3 | 4687982.84 | 0.00 | 4687982.84 | 255127.48 | 4943110.32 | 4267819.30 | 5060.69 | 102.08 | 3597.23 | 418.70 |
PERIMETER_BOT_ZN_2 | 5444137.98 | 0.00 | 5444137.98 | 170084.87 | 5614222.85 | 2750345.05 | 3482.95 | 0.00 | 5277.05 | 418.70 |
PERIMETER_BOT_ZN_1 | 8587659.70 | 0.00 | 8587659.70 | 255127.48 | 8842787.18 | 4267912.63 | 3482.95 | 0.00 | 5277.05 | 418.70 |
PERIMETER_BOT_ZN_4 | 7285352.95 | 0.00 | 7285352.95 | 170084.87 | 7455437.82 | 2750345.05 | 3482.95 | 0.00 | 5277.05 | 418.70 |
PERIMETER_MID_ZN_3 | 35236796.72 | 0.00 | 35236796.72 | 598343.38 | 35835140.09 | 42678193.03 | 5831.11 | 88.14 | 2840.74 | 123.38 |
PERIMETER_MID_ZN_2 | 50280898.45 | 0.00 | 50280898.45 | 398895.31 | 50679793.76 | 27503450.52 | 3852.42 | 0.00 | 4907.58 | 1032.37 |
PERIMETER_MID_ZN_1 | 78406758.45 | 0.00 | 78406758.45 | 598343.38 | 79005101.83 | 42679126.28 | 3855.15 | 3.73 | 4901.13 | 123.38 |
PERIMETER_MID_ZN_4 | 53458228.70 | 0.00 | 53458228.70 | 398895.31 | 53857124.02 | 27503450.52 | 3852.42 | 0.00 | 4907.58 | 123.38 |
PERIMETER_TOP_ZN_3 | 3389462.10 | 0.00 | 3389462.10 | 742904.54 | 4132366.64 | 4267819.30 | 6065.79 | 68.91 | 2625.30 | 218.28 |
PERIMETER_TOP_ZN_2 | 4753721.20 | 0.00 | 4753721.20 | 495269.35 | 5248990.55 | 2750345.05 | 3956.73 | 7.59 | 4795.68 | 218.28 |
PERIMETER_TOP_ZN_1 | 7643058.64 | 0.00 | 7643058.64 | 742904.54 | 8385963.18 | 4267912.63 | 3971.19 | 8.96 | 4779.85 | 218.28 |
PERIMETER_TOP_ZN_4 | 5335821.31 | 0.00 | 5335821.31 | 495269.35 | 5831090.66 | 2750345.05 | 3926.72 | 4.54 | 4828.73 | 218.28 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.56E+10 | 0.00 | 0.56E+10 | 23271546.24 | 0.56E+10 | 0.50E+10 | 6383.50 | 4414.14 | 5438.97 | 1594.22 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.5261 | 0.0000 | 2.5261 | 0.0000 | 2.5261 | 1.2002 | 1309.86 | 108.90 | 4524.23 |
CORE_BOTTOM | 1.9431 | 0.0000 | 1.9431 | 0.0000 | 1.9431 | 1.0778 | 1714.91 | 57.90 | 4170.19 |
CORE_MID | 14.6726 | 0.0000 | 14.6726 | 0.0000 | 14.6726 | 10.7782 | 2616.25 | 69.74 | 3257.02 |
CORE_TOP | 1.3242 | 0.0000 | 1.3242 | 0.0000 | 1.3242 | 1.0778 | 3344.06 | 51.14 | 2547.80 |
PERIMETER_BOT_ZN_3 | 0.2071 | 0.0000 | 0.2071 | 0.0059 | 0.2130 | 0.1353 | 2545.85 | 95.14 | 3302.01 |
PERIMETER_BOT_ZN_2 | 0.2378 | 0.0000 | 0.2378 | 0.0039 | 0.2417 | 0.0872 | 1084.65 | 0.00 | 4858.35 |
PERIMETER_BOT_ZN_1 | 0.3777 | 0.0000 | 0.3777 | 0.0059 | 0.3836 | 0.1353 | 1084.65 | 0.00 | 4858.35 |
PERIMETER_BOT_ZN_4 | 0.3193 | 0.0000 | 0.3193 | 0.0039 | 0.3232 | 0.0872 | 1084.65 | 0.00 | 4858.35 |
PERIMETER_MID_ZN_3 | 1.6135 | 0.0000 | 1.6135 | 0.0138 | 1.6274 | 1.3533 | 3096.15 | 85.61 | 2761.24 |
PERIMETER_MID_ZN_2 | 2.1332 | 0.0000 | 2.1332 | 0.0098 | 2.1430 | 0.8721 | 1158.79 | 0.00 | 3875.21 |
PERIMETER_MID_ZN_1 | 3.5954 | 0.0000 | 3.5954 | 0.0138 | 3.6092 | 1.3533 | 1159.90 | 2.75 | 4780.35 |
PERIMETER_MID_ZN_4 | 2.4437 | 0.0000 | 2.4437 | 0.0092 | 2.4529 | 0.8721 | 1158.79 | 0.00 | 4784.21 |
PERIMETER_TOP_ZN_3 | 0.1555 | 0.0000 | 0.1555 | 0.0172 | 0.1727 | 0.1353 | 3286.01 | 68.09 | 2588.90 |
PERIMETER_TOP_ZN_2 | 0.2182 | 0.0000 | 0.2182 | 0.0115 | 0.2297 | 0.0872 | 1236.33 | 5.17 | 4701.50 |
PERIMETER_TOP_ZN_1 | 0.3513 | 0.0000 | 0.3513 | 0.0172 | 0.3685 | 0.1353 | 1245.55 | 5.41 | 4692.04 |
PERIMETER_TOP_ZN_4 | 0.2447 | 0.0000 | 0.2447 | 0.0115 | 0.2561 | 0.0872 | 1220.65 | 2.03 | 4720.33 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 253.9012 | 0.0000 | 253.9012 | 0.5438 | 254.4449 | 158.4706 | 3566.50 | 4384.76 | 4903.36 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 99055379.65 | 0.00 | 99055379.65 | 48026705.38 | 3485.21 | 0.66 | 5274.13 | 418.70 |
VAV_MID WITH REHEAT | 0.76E+09 | 0.00 | 0.76E+09 | 0.48E+09 | 3881.43 | 2.22 | 4876.35 | 123.38 |
VAV_TOP WITH REHEAT | 70860969.76 | 0.00 | 70860969.76 | 48026705.38 | 4040.75 | 5.43 | 4713.82 | 218.28 |
CAV_BAS | 79751967.42 | 0.00 | 79751967.42 | 37848132.68 | 3825.85 | 4.41 | 4929.74 | 401.97 |
AIRLOOP DATACENTER BASEMENT | 7505992.82 | 0.00 | 7505992.82 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 346745.77 | 0.00 | 346745.77 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3467457.73 | 0.00 | 3467457.73 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 346745.77 | 0.00 | 346745.77 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.3786 | 0.0000 | 4.3786 | 1.5229 | 1086.91 | 0.66 | 4855.43 |
VAV_MID WITH REHEAT | 34.9532 | 0.0000 | 34.9532 | 15.2292 | 1174.81 | 1.04 | 4767.15 |
VAV_TOP WITH REHEAT | 3.2558 | 0.0000 | 3.2558 | 1.5229 | 1287.45 | 4.25 | 4651.30 |
CAV_BAS | 3.5855 | 0.0000 | 3.5855 | 1.2002 | 1295.57 | 0.70 | 4646.73 |
AIRLOOP DATACENTER BASEMENT | 0.3508 | 0.0000 | 0.3508 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0162 | 0.0000 | 0.0162 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1621 | 0.0000 | 0.1621 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0162 | 0.0000 | 0.0162 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 4776.69 | 0.00 | 0.00 | 0.00 | 500.36 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 4071.87 | 0.00 | 0.00 | 0.00 | 835.71 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 3339.21 | 0.00 | 0.00 | 0.00 | 1648.75 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 106.50 | 4962.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.6837 | 0.0000 | 0.0000 | 0.0000 | 2.5172 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 47.3627 | 0.0000 | 0.0000 | 0.0000 | 24.8366 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.9011 | 0.0000 | 0.0000 | 0.0000 | 2.4624 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7115 | 4.6332 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4804 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0222 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2219 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0222 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1380 |
Defaulted Fields | 1179 |
Fields with Defaults | 3862 |
Autosized Fields | 330 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27343.31 | 369055.61 | 01-JAN-10:10 | 1838139.92 | 14-AUG-15:40 |
Electricity:Building | 18931.68 | 251811.03 | 01-JAN-09:40 | 1146857.44 | 01-DEC-15:30 |
Electricity:Zone:BASEMENT | 664.85 | 14623.97 | 01-JAN-00:10 | 34452.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18931.68 | 251811.03 | 01-JAN-09:40 | 1146857.44 | 01-DEC-15:30 |
InteriorLights:Electricity | 3718.27 | 17601.77 | 01-JAN-09:40 | 352853.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3718.27 | 17601.77 | 01-JAN-09:40 | 352853.36 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3718.27 | 17601.77 | 01-JAN-09:40 | 352853.36 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3718.27 | 17601.77 | 01-JAN-09:40 | 352853.36 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 537.23 | 7090.40 | 01-JAN-00:10 | 36983.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5372.24 | 70903.72 | 01-JAN-00:10 | 369831.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 537.22 | 7090.37 | 01-JAN-00:10 | 36983.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 59.34 | 839.57 | 01-JAN-09:40 | 4643.71 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 19.00 | 80.80 | 01-JAN-09:40 | 2367.39 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 19.00 | 80.80 | 01-JAN-09:40 | 2367.39 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 38.17 | 541.05 | 01-JAN-08:50 | 2992.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.18 | 52.07 | 01-JAN-08:50 | 1525.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.18 | 52.07 | 01-JAN-08:50 | 1525.64 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 59.18 | 839.58 | 01-JAN-08:50 | 4643.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.84 | 80.80 | 01-JAN-08:50 | 2367.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.84 | 80.80 | 01-JAN-08:50 | 2367.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 38.21 | 541.05 | 01-JAN-09:40 | 2992.57 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 12.21 | 52.07 | 01-JAN-09:40 | 1525.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 12.21 | 52.07 | 01-JAN-09:40 | 1525.64 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 593.62 | 8395.70 | 01-JAN-09:40 | 46437.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 190.20 | 807.98 | 01-JAN-09:40 | 23673.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 190.20 | 807.98 | 01-JAN-09:40 | 23673.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 381.79 | 5410.51 | 01-JAN-08:50 | 29925.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 121.81 | 520.69 | 01-JAN-08:50 | 15256.36 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 121.81 | 520.69 | 01-JAN-08:50 | 15256.36 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 591.95 | 8395.84 | 01-JAN-08:50 | 46437.94 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 188.52 | 807.99 | 01-JAN-08:50 | 23674.41 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 188.52 | 807.99 | 01-JAN-08:50 | 23674.41 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 382.12 | 5410.48 | 01-JAN-09:40 | 29925.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 122.14 | 520.69 | 01-JAN-09:40 | 15256.36 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 122.14 | 520.69 | 01-JAN-09:40 | 15256.36 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 59.36 | 839.57 | 01-JAN-09:40 | 4643.71 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 19.02 | 80.80 | 01-JAN-09:40 | 2367.39 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 19.02 | 80.80 | 01-JAN-09:40 | 2367.39 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 38.18 | 541.05 | 01-JAN-08:50 | 2992.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.18 | 52.07 | 01-JAN-08:50 | 1525.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.18 | 52.07 | 01-JAN-08:50 | 1525.64 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 59.20 | 839.58 | 01-JAN-08:50 | 4643.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.85 | 80.80 | 01-JAN-08:50 | 2367.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.85 | 80.80 | 01-JAN-08:50 | 2367.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 38.21 | 541.05 | 01-JAN-09:40 | 2992.57 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 12.21 | 52.07 | 01-JAN-09:40 | 1525.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 12.21 | 52.07 | 01-JAN-09:40 | 1525.64 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7562.65 | 95237.01 | 01-JAN-00:10 | 385552.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1598.46 | 19775.43 | 01-JAN-00:10 | 83152.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1172.11 | 6171.55 | 11-JAN-24:00 | 328593.25 | 13-JUN-16:00 |
HeatRejection:Electricity | 732.44 | 2398.39 | 10-JAN-08:00 | 77869.83 | 22-MAY-14:10 |
General:HeatRejection:Electricity | 732.44 | 2398.39 | 10-JAN-08:00 | 77869.83 | 22-MAY-14:10 |
Electricity:HVAC | 4712.21 | 75502.73 | 01-JAN-08:50 | 377738.08 | 14-AUG-15:30 |
ExteriorEquipment:Electricity | 1941.94 | 28795.69 | 01-JAN-00:10 | 118959.22 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.33 | 1613.62 | 01-JAN-00:10 | 5481.25 | 01-DEC-15:40 |
ElectricityPurchased:Facility | 27343.31 | 369055.61 | 01-JAN-10:10 | 1838139.92 | 14-AUG-15:40 |
ElectricityPurchased:Plant | 27343.31 | 369055.61 | 01-JAN-10:10 | 1838139.92 | 14-AUG-15:40 |
Cogeneration:ElectricityPurchased | 27343.31 | 369055.61 | 01-JAN-10:10 | 1838139.92 | 14-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 27343.31 | 369055.61 | 01-JAN-10:10 | 1838139.92 | 14-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 27343.31 | 369055.61 | 01-JAN-10:10 | 1838139.92 | 14-AUG-15:40 |
ElectricityNet:Plant | 27343.31 | 369055.61 | 01-JAN-10:10 | 1838139.92 | 14-AUG-15:40 |
Cogeneration:ElectricityNet | 27343.31 | 369055.61 | 01-JAN-10:10 | 1838139.92 | 14-AUG-15:40 |
General:Cogeneration:ElectricityNet | 27343.31 | 369055.61 | 01-JAN-10:10 | 1838139.92 | 14-AUG-15:40 |
Fans:Electricity | 2337.62 | 42334.99 | 03-JAN-00:40 | 230352.26 | 13-JUN-15:30 |
General:Fans:Electricity | 2337.62 | 42334.99 | 03-JAN-00:40 | 230352.26 | 13-JUN-15:30 |
ExteriorLights:Electricity | 672.69 | 0.00 | 01-JAN-08:20 | 54335.80 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 672.69 | 0.00 | 01-JAN-08:20 | 54335.80 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 2459.64 | 28612.93 | 02-JAN-07:30 | 325650.88 | 14-AUG-15:00 |
General:Cooling:Electricity | 2459.64 | 28612.93 | 02-JAN-07:30 | 325650.88 | 14-AUG-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 5.10 | 0.00 | 01-JAN-00:10 | 5914.45 | 10-JAN-21:00 |
General:Humidifier:Electricity | 5.10 | 0.00 | 01-JAN-00:10 | 5914.45 | 10-JAN-21:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 262.21 | 3368.90 | 01-JAN-00:10 | 51782.73 | 28-APR-15:00 |
General:Pumps:Electricity | 262.21 | 3368.90 | 01-JAN-00:10 | 51782.73 | 28-APR-15:00 |
WIRED_LTG_ELECTRICITY | 104.48 | 0.00 | 01-JAN-00:10 | 9915.18 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1860.35 | 5695.87 | 30-APR-16:10 | 768728.48 | 10-JAN-08:00 |
NaturalGas:Plant | 1860.35 | 5695.87 | 30-APR-16:10 | 768728.48 | 10-JAN-08:00 |
Heating:NaturalGas | 1114.93 | 0.00 | 01-JAN-00:10 | 743188.72 | 10-JAN-08:00 |
Boiler:Heating:NaturalGas | 1114.93 | 0.00 | 01-JAN-00:10 | 743188.72 | 10-JAN-08:00 |
WaterSystems:NaturalGas | 745.42 | 5695.87 | 30-APR-16:10 | 82176.29 | 15-FEB-12:50 |
Water Heater:WaterSystems:NaturalGas | 745.42 | 5695.87 | 30-APR-16:10 | 82176.29 | 15-FEB-12:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 13293.84 | 140678.10 | 10-JAN-08:00 | 1919875.35 | 14-AUG-15:50 |
PlantLoopCoolingDemand:HVAC | 13293.84 | 140678.10 | 10-JAN-08:00 | 1919875.35 | 14-AUG-15:50 |
CoolingCoils:PlantLoopCoolingDemand | 13293.84 | 140678.10 | 10-JAN-08:00 | 1919875.35 | 14-AUG-15:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 3160.17 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-13:00 |
Water:HVAC | 1.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-JAN-21:00 |
Humidifier:Water | 1.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-JAN-21:00 |
General:Humidifier:Water | 1.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-JAN-21:00 |
MainsWater:Facility | 3160.17 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-13:00 |
MainsWater:HVAC | 1.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-JAN-21:00 |
Humidifier:MainsWater | 1.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-JAN-21:00 |
General:Humidifier:MainsWater | 1.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-JAN-21:00 |
Water:Plant | 3158.28 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-13:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 3158.28 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-13:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 878.11 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
General:HeatRejection:Water | 878.11 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
HeatRejection:MainsWater | 878.11 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
General:HeatRejection:MainsWater | 878.11 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 34886.87 | 218360.96 | 09-JAN-04:40 | 7627479.93 | 13-JUN-16:00 |
EnergyTransfer:Building | 17943.46 | 88582.92 | 08-JAN-10:50 | 1520200.51 | 14-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 684.53 | 0.00 | 01-JAN-00:10 | 69851.05 | 13-NOV-06:10 |
Heating:EnergyTransfer | 159.89 | 0.00 | 06-JAN-22:10 | 387145.83 | 26-DEC-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.47 | 0.00 | 01-JAN-00:10 | 13923.67 | 22-JUL-16:10 |
General:Heating:EnergyTransfer | 159.89 | 0.00 | 06-JAN-22:10 | 387145.83 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.47 | 0.00 | 01-JAN-00:10 | 13923.67 | 22-JUL-16:10 |
Cooling:EnergyTransfer | 17783.57 | 88013.10 | 08-JAN-10:10 | 1520200.51 | 14-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 681.06 | 0.00 | 01-JAN-00:10 | 69851.05 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer | 17783.57 | 88013.10 | 08-JAN-10:10 | 1520200.51 | 14-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 681.06 | 0.00 | 01-JAN-00:10 | 69851.05 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 617.40 | 0.00 | 01-JAN-00:10 | 52856.44 | 24-APR-09:40 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 617.40 | 0.00 | 01-JAN-00:10 | 52856.44 | 24-APR-09:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 617.40 | 0.00 | 01-JAN-00:10 | 52856.44 | 24-APR-09:40 |
EnergyTransfer:Zone:CORE_MID | 4333.08 | 0.00 | 01-JAN-00:10 | 425764.23 | 24-JUL-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4333.08 | 0.00 | 01-JAN-00:10 | 425764.23 | 24-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4333.08 | 0.00 | 01-JAN-00:10 | 425764.23 | 24-JUL-16:00 |
EnergyTransfer:Zone:CORE_TOP | 365.67 | 0.00 | 01-JAN-00:10 | 63324.86 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 4.29 | 0.00 | 01-JAN-00:10 | 63324.86 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 4.29 | 0.00 | 01-JAN-00:10 | 63324.86 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 361.38 | 0.00 | 01-JAN-00:10 | 49017.81 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 361.38 | 0.00 | 01-JAN-00:10 | 49017.81 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.93 | 0.00 | 01-JAN-00:10 | 8540.05 | 10-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 86.43 | 12-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 86.43 | 12-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.93 | 0.00 | 01-JAN-00:10 | 8540.05 | 10-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.93 | 0.00 | 01-JAN-00:10 | 8540.05 | 10-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.77 | 0.00 | 01-JAN-00:10 | 11675.52 | 13-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 655.91 | 11-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 655.91 | 11-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.77 | 0.00 | 01-JAN-00:10 | 11675.52 | 13-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.77 | 0.00 | 01-JAN-00:10 | 11675.52 | 13-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 104.43 | 0.00 | 01-JAN-00:10 | 18584.11 | 11-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 2369.06 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 2369.06 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 104.41 | 0.00 | 01-JAN-00:10 | 18584.11 | 11-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 104.41 | 0.00 | 01-JAN-00:10 | 18584.11 | 11-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 94.56 | 0.00 | 01-JAN-00:10 | 15509.48 | 28-APR-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 7.74 | 11-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 7.74 | 11-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 94.56 | 0.00 | 01-JAN-00:10 | 15509.48 | 28-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 94.56 | 0.00 | 01-JAN-00:10 | 15509.48 | 28-APR-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 397.13 | 0.00 | 01-JAN-00:10 | 82252.50 | 26-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 19.55 | 0.00 | 01-JAN-00:10 | 82252.50 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 19.55 | 0.00 | 01-JAN-00:10 | 82252.50 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 377.57 | 0.00 | 01-JAN-00:10 | 73344.31 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 377.57 | 0.00 | 01-JAN-00:10 | 73344.31 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 504.91 | 0.00 | 01-JAN-00:10 | 121130.57 | 13-JUN-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 13.08 | 0.00 | 01-JAN-00:10 | 61625.94 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 13.08 | 0.00 | 01-JAN-00:10 | 61625.94 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 491.83 | 0.00 | 01-JAN-00:10 | 121130.57 | 13-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 491.83 | 0.00 | 01-JAN-00:10 | 121130.57 | 13-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 867.56 | 0.00 | 01-JAN-00:10 | 197191.01 | 11-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 10.82 | 0.00 | 01-JAN-00:10 | 69394.23 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 10.82 | 0.00 | 01-JAN-00:10 | 69394.23 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 856.74 | 0.00 | 01-JAN-00:10 | 197191.01 | 11-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 856.74 | 0.00 | 01-JAN-00:10 | 197191.01 | 11-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 543.29 | 0.00 | 01-JAN-00:10 | 139522.21 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 6.90 | 0.00 | 01-JAN-00:10 | 46293.56 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 6.90 | 0.00 | 01-JAN-00:10 | 46293.56 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 536.39 | 0.00 | 01-JAN-00:10 | 139522.21 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 536.39 | 0.00 | 01-JAN-00:10 | 139522.21 | 13-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.97 | 0.00 | 01-JAN-00:10 | 11025.88 | 26-DEC-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.50 | 0.00 | 01-JAN-00:10 | 11025.88 | 26-DEC-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.50 | 0.00 | 01-JAN-00:10 | 11025.88 | 26-DEC-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.47 | 0.00 | 01-JAN-00:10 | 8173.51 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.47 | 0.00 | 01-JAN-00:10 | 8173.51 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 48.72 | 0.00 | 01-JAN-00:10 | 12045.89 | 13-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.88 | 0.00 | 01-JAN-00:10 | 11530.02 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.88 | 0.00 | 01-JAN-00:10 | 11530.02 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 40.84 | 0.00 | 01-JAN-00:10 | 12045.89 | 13-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 40.84 | 0.00 | 01-JAN-00:10 | 12045.89 | 13-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 81.10 | 0.00 | 01-JAN-00:10 | 19954.11 | 11-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.88 | 0.00 | 01-JAN-00:10 | 16309.83 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.88 | 0.00 | 01-JAN-00:10 | 16309.83 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 72.22 | 0.00 | 01-JAN-00:10 | 19954.11 | 11-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 72.22 | 0.00 | 01-JAN-00:10 | 19954.11 | 11-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.78 | 0.00 | 01-JAN-00:10 | 14590.33 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.15 | 0.00 | 01-JAN-00:10 | 9734.14 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.15 | 0.00 | 01-JAN-00:10 | 9734.14 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.62 | 0.00 | 01-JAN-00:10 | 14590.33 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.62 | 0.00 | 01-JAN-00:10 | 14590.33 | 13-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 57.60 | 0.00 | 01-JAN-00:10 | 7589.94 | 24-JUL-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.11 | 0.00 | 01-JAN-00:10 | 3933.36 | 15-JAN-12:00 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.11 | 0.00 | 01-JAN-00:10 | 3933.36 | 15-JAN-12:00 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 56.49 | 0.00 | 01-JAN-00:10 | 7589.94 | 24-JUL-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 56.49 | 0.00 | 01-JAN-00:10 | 7589.94 | 24-JUL-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 356.32 | 0.00 | 01-JAN-00:10 | 54825.94 | 24-JUL-15:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 32.71 | 0.00 | 01-JAN-00:10 | 40753.72 | 26-DEC-14:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 32.71 | 0.00 | 01-JAN-00:10 | 40753.72 | 26-DEC-14:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 323.60 | 0.00 | 01-JAN-00:10 | 54825.94 | 24-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 323.60 | 0.00 | 01-JAN-00:10 | 54825.94 | 24-JUL-15:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 68.07 | 0.00 | 01-JAN-00:10 | 17005.77 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.60 | 0.00 | 01-JAN-00:10 | 17005.77 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.60 | 0.00 | 01-JAN-00:10 | 17005.77 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.47 | 0.00 | 01-JAN-00:10 | 16784.90 | 13-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.47 | 0.00 | 01-JAN-00:10 | 16784.90 | 13-JUN-14:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.91 | 737.20 | 14-JAN-18:20 | 8263.55 | 30-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.91 | 737.20 | 14-JAN-18:20 | 8263.55 | 30-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.91 | 737.20 | 14-JAN-18:20 | 8263.55 | 30-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1184.87 | 5.55 | 09-JAN-01:40 | 77667.92 | 30-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.30 | 0.00 | 01-JAN-15:10 | 3578.86 | 01-JAN-08:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.30 | 0.00 | 01-JAN-15:10 | 3578.86 | 01-JAN-08:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1184.57 | 0.00 | 01-JAN-00:10 | 77667.92 | 30-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1184.57 | 0.00 | 01-JAN-00:10 | 77667.92 | 30-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.29 | 0.04 | 11-JAN-20:50 | 7893.10 | 30-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.62 | 0.00 | 02-JAN-13:30 | 583.51 | 08-JAN-18:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.62 | 0.00 | 02-JAN-13:30 | 583.51 | 08-JAN-18:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.67 | 0.00 | 01-JAN-00:10 | 7893.10 | 30-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.67 | 0.00 | 01-JAN-00:10 | 7893.10 | 30-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.58 | 86787.91 | 15-JAN-06:00 | 368795.75 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.58 | 86787.91 | 15-JAN-06:00 | 368795.75 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.58 | 86787.91 | 15-JAN-06:00 | 368795.75 | 15-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 1259.19 | 0.00 | 01-JAN-00:10 | 639776.32 | 10-JAN-08:00 |
PlantLoopHeatingDemand:Plant | 442.36 | 0.00 | 01-JAN-00:10 | 51544.64 | 14-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 442.36 | 0.00 | 01-JAN-00:10 | 51544.64 | 14-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 442.36 | 0.00 | 01-JAN-00:10 | 51544.64 | 14-FEB-12:20 |
EnergyTransfer:HVAC | 11828.51 | 123473.29 | 28-JAN-17:10 | 1765303.77 | 14-AUG-15:50 |
HeatingCoils:EnergyTransfer | 816.83 | 0.00 | 01-JAN-00:10 | 622852.30 | 10-JAN-08:00 |
PlantLoopHeatingDemand:HVAC | 816.83 | 0.00 | 01-JAN-00:10 | 622852.30 | 10-JAN-08:00 |
HeatingCoils:PlantLoopHeatingDemand | 816.83 | 0.00 | 01-JAN-00:10 | 622852.30 | 10-JAN-08:00 |
CoolingCoils:EnergyTransfer | 11011.68 | 111956.96 | 10-JAN-08:00 | 1765303.77 | 14-AUG-15:50 |
EnergyTransfer:Plant | 5114.91 | 0.00 | 01-JAN-00:10 | 4591004.81 | 13-JUN-16:00 |
LoopToLoop:EnergyTransfer | 1281.57 | -2995.40 | 20-APR-15:30 | 1444985.07 | 13-JUN-16:00 |
WaterSystems:EnergyTransfer | 442.36 | 0.00 | 01-JAN-00:10 | 51544.64 | 14-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 442.36 | 0.00 | 01-JAN-00:10 | 51544.64 | 14-FEB-12:20 |
Boilers:EnergyTransfer | 809.83 | 0.00 | 01-JAN-00:10 | 619609.68 | 10-JAN-08:00 |
Chillers:EnergyTransfer | 1201.83 | 0.00 | 01-JAN-00:10 | 1453474.04 | 13-JUN-16:00 |
HeatRejection:EnergyTransfer | 1379.31 | 0.00 | 01-JAN-00:10 | 1655827.53 | 13-JUN-16:00 |
General:HeatRejection:EnergyTransfer | 1379.31 | 0.00 | 01-JAN-00:10 | 1655827.53 | 13-JUN-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.473 | -681.056 | 0.000 | 0.000 | 92.722 | 240.449 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -79.985 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -617.403 | 0.000 | 0.000 | 83.411 | 215.940 | 321.286 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -3.234 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4333.077 | 0.000 | 0.000 | 841.514 | 2159.397 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1880.680 |
CORE_TOP | 0.000 | 0.000 | 4.288 | -361.375 | 0.000 | 0.000 | 87.549 | 215.940 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -267.686 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -59.935 | 0.000 | 0.000 | 10.735 | 18.998 | 40.342 | 18.607 | 0.000 | 0.002 | 28.841 | 0.000 | -53.268 | 0.000 | -4.321 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.003 | -64.771 | 0.000 | 0.000 | 7.170 | 12.177 | 25.998 | 42.493 | 0.000 | 0.001 | 12.469 | 0.000 | -32.748 | 0.000 | -2.793 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.020 | -104.408 | 0.000 | 0.000 | 11.024 | 18.839 | 40.343 | 85.249 | 0.000 | 0.002 | 3.080 | 0.000 | -49.908 | 0.000 | -4.242 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -94.557 | 0.000 | 0.000 | 6.957 | 12.209 | 25.998 | 40.475 | 0.000 | 0.001 | 49.838 | 0.000 | -37.822 | 0.000 | -3.100 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 19.554 | -377.573 | 0.000 | 0.000 | 113.283 | 190.200 | 403.423 | 195.823 | 0.000 | 0.037 | 23.462 | 0.000 | -477.479 | 0.000 | -90.730 | -0.004 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 13.078 | -491.833 | 0.000 | 0.000 | 54.622 | 121.809 | 259.981 | 428.287 | 0.000 | 0.028 | 0.017 | 0.000 | -304.950 | 0.000 | -60.955 | -20.068 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 10.815 | -856.744 | 0.000 | 0.000 | 113.118 | 188.522 | 403.429 | 854.760 | 0.000 | 0.040 | 0.007 | 0.000 | -478.577 | 0.000 | -94.577 | -140.785 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 6.903 | -536.389 | 0.000 | 0.000 | 74.941 | 122.144 | 259.979 | 418.038 | 0.000 | 0.022 | 43.329 | 0.000 | -326.158 | 0.000 | -62.810 | -0.005 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 13.495 | -29.471 | 0.000 | 0.000 | 11.666 | 19.020 | 40.342 | 20.491 | 0.000 | 0.004 | 0.001 | 0.000 | -43.773 | 0.000 | -10.398 | -21.377 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 7.879 | -40.839 | 0.000 | 0.000 | 7.499 | 12.181 | 25.998 | 43.346 | 0.000 | 0.003 | 0.000 | 0.000 | -28.358 | 0.000 | -7.091 | -20.618 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 8.880 | -72.220 | 0.000 | 0.000 | 11.573 | 18.852 | 40.343 | 86.416 | 0.000 | 0.005 | 0.001 | 0.000 | -44.432 | 0.000 | -10.950 | -38.467 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 5.153 | -45.624 | 0.000 | 0.000 | 7.628 | 12.214 | 25.998 | 42.203 | 0.000 | 0.003 | 0.000 | 0.000 | -30.565 | 0.000 | -7.341 | -9.669 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -137.912 | 0.000 | 0.000 | 0.950 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -22.884 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.305 | -1184.569 | 0.000 | 0.000 | 9.502 | 59.652 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -423.695 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.618 | -105.674 | 0.000 | 0.000 | 0.951 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -55.741 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7171.577 | 0.000 | 0.000 | 20.565 | 67.796 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -411.641 |
GROUNDFLOOR_PLENUM | 1.112 | -56.488 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 64.459 | 0.000 | 0.000 | 0.000 | -9.085 | 0.000 |
MIDFLOOR_PLENUM | 32.713 | -323.602 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.048 | 445.990 | 0.000 | 0.000 | 0.000 | -155.150 | -0.006 |
TOPFLOOR_PLENUM | 31.599 | -36.468 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 21.275 | 0.000 | 0.000 | 0.000 | -16.409 | -0.000 |
Total Facility | 65.424 | -416.558 | 94.465 | -17367.005 | 0.000 | 0.000 | 1567.380 | 3718.269 | 15213.411 | 2276.188 | 0.000 | 0.202 | 692.770 | 0.000 | -1908.039 | 0.000 | -539.952 | -3396.546 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 21-FEB-04:01 | 0.00 | 0.00 | 0.00 | -114397.85 | 0.00 | 0.00 | 0.00 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 99773.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 10-OCT-03:02 | 0.00 | 0.00 | 0.00 | -95620.73 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.15 | 0.00 | 0.00 | 0.00 | 86516.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 25-JUL-04:03 | 0.00 | 0.00 | 0.00 | -811969.28 | 0.00 | 0.00 | 0.00 | 20950.64 | 80571.20 | 0.00 | 0.00 | 0.00 | 710447.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25-JUL-05:02 | 0.00 | 0.00 | 0.00 | -76769.16 | 0.00 | 0.00 | 841.61 | 2095.06 | 8057.12 | 0.00 | 0.00 | 0.00 | 65775.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 26-JUN-05:02 | 0.00 | 0.00 | 0.00 | -11360.62 | 0.00 | 0.00 | 107.41 | 161.60 | 1011.70 | 2724.37 | 0.00 | 0.00 | 7428.47 | 0.00 | -0.00 | 0.00 | -72.92 | 0.00 |
PERIMETER_BOT_ZN_2 | 30-APR-08:52 | 0.00 | 0.00 | 0.00 | -20085.82 | 0.00 | 0.00 | 23.43 | 52.07 | 488.98 | 15000.64 | 0.00 | 0.00 | 4705.76 | 0.00 | -0.00 | 0.00 | -185.06 | 0.00 |
PERIMETER_BOT_ZN_1 | 30-APR-12:52 | 0.00 | 0.00 | 0.00 | -29949.56 | 0.00 | 0.00 | 34.15 | 80.80 | 758.78 | 21993.66 | 0.00 | 0.00 | 7197.54 | 0.00 | -0.00 | 0.00 | -115.37 | 0.00 |
PERIMETER_BOT_ZN_4 | 25-JUN-16:41 | 0.00 | 0.00 | 0.00 | -26520.89 | 0.00 | 0.00 | 20.04 | 52.07 | 488.98 | 15055.90 | 0.00 | 0.00 | 10969.84 | 0.00 | -0.00 | 0.00 | -65.93 | 0.00 |
PERIMETER_MID_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -73335.13 | 0.00 | 0.00 | 11143.94 | 14542.87 | 22763.18 | 39014.10 | 0.00 | 402.50 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14531.47 |
PERIMETER_MID_ZN_2 | 30-APR-09:22 | 0.00 | 0.00 | 0.00 | -207452.90 | 0.00 | 0.00 | 230.70 | 520.69 | 4889.82 | 135587.71 | 0.00 | 0.00 | 69941.10 | 0.00 | -0.00 | 0.00 | -3717.12 | 0.00 |
PERIMETER_MID_ZN_1 | 30-APR-12:42 | 0.00 | 0.00 | 0.00 | -307128.66 | 0.00 | 0.00 | 335.85 | 807.99 | 7587.84 | 222881.16 | 0.00 | 0.00 | 78312.93 | 0.00 | -0.00 | 0.00 | -2797.12 | 0.00 |
PERIMETER_MID_ZN_4 | 21-MAY-16:52 | 0.00 | 0.00 | 0.00 | -224242.16 | 0.00 | 0.00 | 224.49 | 520.69 | 4889.79 | 158314.40 | 0.00 | 0.00 | 63095.86 | 0.00 | -0.00 | 0.00 | -2803.06 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -8172.49 | 0.00 | 0.00 | 1114.39 | 1454.29 | 2276.32 | 3861.58 | 0.00 | 47.70 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -581.79 |
PERIMETER_TOP_ZN_2 | 16-JUL-09:12 | 0.00 | 0.00 | 0.00 | -19876.11 | 0.00 | 0.00 | 24.63 | 52.07 | 488.98 | 13585.58 | 0.00 | 0.00 | 6167.76 | 0.00 | -0.00 | 0.00 | -442.92 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-14:52 | 0.00 | 0.00 | 0.00 | -30332.13 | 0.00 | 0.00 | 36.84 | 80.80 | 758.78 | 13197.98 | 0.00 | 0.00 | 16735.92 | 0.00 | -0.00 | 0.00 | -478.19 | 0.00 |
PERIMETER_TOP_ZN_4 | 20-AUG-16:41 | 0.00 | 0.00 | 0.00 | -22633.12 | 0.00 | 0.00 | 22.00 | 52.07 | 488.98 | 14018.61 | 0.00 | 0.00 | 8232.13 | 0.00 | -0.00 | 0.00 | -180.66 | 0.00 |
DATACENTER_BOT_ZN_6 | 30-APR-17:44 | 0.00 | 0.00 | 0.00 | -8268.36 | 0.00 | 0.00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 445.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 30-APR-17:52 | 0.00 | 0.00 | 0.00 | -77667.92 | 0.00 | 0.00 | 0.00 | 289.38 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -565.68 |
DATACENTER_TOP_ZN_6 | 30-APR-17:52 | 0.00 | 0.00 | 0.00 | -7893.10 | 0.00 | 0.00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 69.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 30-APR-19:53 | 0.00 | 0.00 | 0.00 | -369923.18 | 0.00 | 0.00 | 0.00 | 328.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10038.23 |
GROUNDFLOOR_PLENUM | 24-JUL-05:13 | 0.00 | -10768.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10906.30 | 0.00 | -0.00 | 0.00 | -137.50 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-05:13 | 0.00 | -69666.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72114.64 | 0.00 | -0.00 | 0.00 | -2447.82 | 0.00 |
TOPFLOOR_PLENUM | 13-JUN-14:20 | 0.00 | -16784.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16799.68 | 0.00 | -0.00 | 0.00 | -14.72 | 0.00 |
Total Facility | 15-AUG-05:02 | 0.00 | 26253.73 | 0.00 | -1760501.41 | 0.00 | 0.00 | 16173.33 | 39207.80 | 623236.89 | 0.00 | 0.00 | 0.00 | 1128178.02 | 0.00 | -71710.73 | 0.00 | -837.62 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-JUL-16:02 | 0.00 | 0.00 | 15185.57 | 0.00 | 0.00 | 0.00 | 520.13 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30329.67 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-04:11 | 0.00 | 0.00 | 72022.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -81127.33 |
PERIMETER_BOT_ZN_3 | 12-JAN-06:03 | 0.00 | 0.00 | 605.02 | 0.00 | 0.00 | 0.00 | 138.85 | 263.06 | 1011.70 | 0.00 | 0.00 | 0.00 | 1740.93 | 0.00 | -3703.95 | 0.00 | -55.61 | 0.00 |
PERIMETER_BOT_ZN_2 | 10-JAN-06:01 | 0.00 | 0.00 | 3702.82 | 0.00 | 0.00 | 0.00 | 91.27 | 169.52 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2815.09 | 0.00 | -94.33 | -1706.18 |
PERIMETER_BOT_ZN_1 | 10-JAN-06:01 | 0.00 | 0.00 | 7550.58 | 0.00 | 0.00 | 0.00 | 144.01 | 263.06 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4073.30 | 0.00 | -139.84 | -4756.23 |
PERIMETER_BOT_ZN_4 | 11-JAN-06:06 | 0.00 | 0.00 | 54.15 | 0.00 | 0.00 | 0.00 | 85.53 | 169.52 | 651.97 | 0.00 | 0.00 | 0.00 | 1796.84 | 0.00 | -2685.94 | 0.00 | -72.07 | 0.00 |
PERIMETER_MID_ZN_3 | 26-DEC-04:03 | 0.00 | 0.00 | 98259.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.28 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33750.29 | 0.00 | -16509.93 | -59431.52 |
PERIMETER_MID_ZN_2 | 26-DEC-05:01 | 0.00 | 0.00 | 118111.76 | 0.00 | 0.00 | 0.00 | 0.00 | 1695.23 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17979.53 | 0.00 | -7936.37 | -100410.86 |
PERIMETER_MID_ZN_1 | 26-DEC-05:01 | 0.00 | 0.00 | 169610.44 | 0.00 | 0.00 | 0.00 | 0.00 | 2630.62 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28822.47 | 0.00 | -12311.50 | -141224.22 |
PERIMETER_MID_ZN_4 | 26-DEC-05:01 | 0.00 | 0.00 | 106756.93 | 0.00 | 0.00 | 0.00 | 0.00 | 1695.23 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19118.58 | 0.00 | -8165.35 | -87687.96 |
PERIMETER_TOP_ZN_3 | 26-DEC-04:11 | 0.00 | 0.00 | 12083.99 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2279.24 | 0.00 | -1635.38 | -9312.60 |
PERIMETER_TOP_ZN_2 | 26-DEC-04:11 | 0.00 | 0.00 | 15981.62 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1521.58 | 0.00 | -1123.05 | -14073.73 |
PERIMETER_TOP_ZN_1 | 26-DEC-04:11 | 0.00 | 0.00 | 23936.82 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2381.33 | 0.00 | -1704.49 | -20994.24 |
PERIMETER_TOP_ZN_4 | 26-DEC-04:11 | 0.00 | 0.00 | 16186.16 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1630.63 | 0.00 | -1154.24 | -14138.02 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-08:40 | 0.00 | 0.00 | 3578.87 | 0.00 | 0.00 | 0.00 | 53.08 | 289.38 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23407.38 |
DATACENTER_TOP_ZN_6 | 08-JAN-18:10 | 0.00 | 0.00 | 583.51 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2561.05 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:01 | 13232.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -891.97 | -12340.85 |
MIDFLOOR_PLENUM | 30-APR-15:21 | 88238.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -243.80 | -87994.92 |
TOPFLOOR_PLENUM | 09-JAN-06:13 | 21103.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21103.88 |
Total Facility | 26-DEC-05:01 | -800833.82 | 779370.00 | 620704.74 | -779370.00 | 0.00 | 0.00 | 0.00 | 39207.80 | 623236.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -112599.41 | 0.00 | -71430.31 | -298285.88 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.8881 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.3831 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 103.3039 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 86.3952 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.2619 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.2931 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.7214 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.7214 | 0.2098 | 1.0000 | Not calculated | 1.2002 | 0.2098 | ||
AIRLOOP DATACENTER BASEMENT | 21.5782 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.5783 | 0.0157 | 1.0000 | Not calculated | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.5076 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5076 | 0.0308 | 1.0000 | Not calculated | 0.0156 | 0.0308 | ||
AIRLOOP DATACENTER MID | 4.8555 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8555 | 0.0322 | 1.0000 | Not calculated | 0.1563 | 0.0322 | ||
AIRLOOP DATACENTER TOP | 0.4923 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4923 | 0.0318 | 1.0000 | Not calculated | 0.0156 | 0.0318 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.4440 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.4030 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 51.6520 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 33.1560 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.1310 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.4019 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.7214 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.7214 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2098 | ||
AIRLOOP DATACENTER BASEMENT | 21.5782 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.5782 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.5076 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5076 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0308 | ||
AIRLOOP DATACENTER MID | 4.8555 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8555 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0322 | ||
AIRLOOP DATACENTER TOP | 0.4923 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4923 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0318 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7214 | 5.7214 | 5.7214 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9392 | 5.9392 | 1.9183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 55.6735 | 55.6735 | 18.7063 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3006 | 5.3006 | 1.9135 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8174 | 0.8174 | 0.2452 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1319 | 1.1319 | 0.3396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6101 | 1.6101 | 0.4830 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3895 | 1.3895 | 0.4169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.3001 | 7.3001 | 2.3506 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.6457 | 11.6457 | 3.4937 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.3554 | 16.3554 | 4.9066 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.3293 | 12.3293 | 3.6988 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8078 | 0.8078 | 0.2423 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1444 | 1.1444 | 0.3433 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7176 | 1.7176 | 0.5153 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2916 | 1.2916 | 0.3875 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5076 | 0.5076 | 0.5076 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8555 | 4.8555 | 4.8555 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4923 | 0.4923 | 0.4923 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.5782 | 21.5782 | 21.5782 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.8881 | 9.3831 | 10.8881 | 3.4030 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 103.3039 | 86.3952 | 103.3039 | 33.1560 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.2619 | 9.2931 | 10.2619 | 3.4019 | 0.0000 | 1.0000 |
CAV_BAS | 5.7214 | 5.7214 | 5.7214 | 5.7214 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5782 | 21.5783 | 21.5782 | 21.5782 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5076 | 0.5076 | 0.5076 | 0.5076 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8555 | 4.8555 | 4.8555 | 4.8555 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4923 | 0.4923 | 0.4923 | 0.4923 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7214 | 5.7214 | 5.7214 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9696 | 2.9696 | 1.9183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.8367 | 27.8367 | 18.7063 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6503 | 2.6503 | 1.9135 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4087 | 0.4087 | 0.2452 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5659 | 0.5659 | 0.3396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8051 | 0.8051 | 0.4830 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6948 | 0.6948 | 0.4169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.6501 | 3.6501 | 2.3506 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8228 | 5.8228 | 3.4937 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.1777 | 8.1777 | 4.9066 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1646 | 6.1646 | 3.6988 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4039 | 0.4039 | 0.2423 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5722 | 0.5722 | 0.3433 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8588 | 0.8588 | 0.5153 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6458 | 0.6458 | 0.3875 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5076 | 0.5076 | 0.5076 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8555 | 4.8555 | 4.8555 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4923 | 0.4923 | 0.4923 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.5782 | 21.5782 | 21.5782 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.4440 | 3.4030 | 3.4030 | 3.4030 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 51.6520 | 33.1560 | 33.1560 | 33.1560 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.1310 | 3.4019 | 3.4019 | 3.4019 | 0.0000 | 1.0000 |
CAV_BAS | 5.7214 | 5.7214 | 5.7214 | 5.7214 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5782 | 21.5782 | 21.5782 | 21.5782 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5076 | 0.5076 | 0.5076 | 0.5076 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8555 | 4.8555 | 4.8555 | 4.8555 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4923 | 0.4923 | 0.4923 | 0.4923 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 14.67 |
Number of hours cooling loads not met | 66.17 |
Number of hours not met | 80.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1114.93 | 743188.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2459.64 | 325650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3718.27 | 352853.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 672.69 | 54335.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.33 | 5481.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2337.62 | 230352.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 262.21 | 51782.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 732.44 | 77869.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 5.10 | 5914.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 745.42 | 82176.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 27343.31 |
Natural Gas | 0.00 | 1860.35 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 29203.66 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 80.27 |
Space Heating | 0.00 |
Space Cooling | 53.10 |
Fans (All) | 50.47 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 590.31 |
Subtotal | 590.31 |
Natural Gas [MJ/m2] | |
Space Heating | 24.07 |
Service Water Heating | 16.09 |
Miscellaneous (All) | 40.16 |
Subtotal | 40.16 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.73 |
Space Heating | 3.82 |
Space Cooling | 8.42 |
Fans (All) | 8.00 |
Service Water Heating | 2.55 |
Receptacle Equipment | 52.09 |
Miscellaneous | 12.38 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2645. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8527.83 | 232.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8724.67 | 35.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8581.50 | 178.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8741.50 | 18.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7829.33 | 930.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7783.50 | 976.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7752.50 | 1007.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8106.50 | 653.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
Min | 7752.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1007.50 | 0.00 | 0.00 | 0.00 |
Average | 8580.17 | 179.83 | 0.00 | 0.00 | 0.00 |
Sum | 197343.83 | 4136.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368066.50 | 549.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330737.00 | 76.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1641.67 | 626.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1608.00 | 660.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1590.67 | 677.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 85536.00 | 17859.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368066.50 | 17859.00 | 0.00 | 0.00 | 0.00 |
Average | 79445.86 | 889.05 | 0.00 | 0.00 | 0.00 |
Sum | 1827254.83 | 20448.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8473.17 | 286.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8625.17 | 106.83 | 28.00 | 0.00 | 0.00 |
CORE_MID | 8688.50 | 71.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8748.33 | 11.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8609.00 | 151.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8738.50 | 21.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8731.67 | 28.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8740.67 | 19.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8584.83 | 175.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8566.83 | 193.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8561.33 | 198.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8698.00 | 62.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8739.67 | 20.33 | 0.00 | 0.00 | 0.00 |
Min | 8473.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 286.83 | 28.00 | 0.00 | 0.00 |
Average | 8695.82 | 62.96 | 1.22 | 0.00 | 0.00 |
Sum | 200003.83 | 1448.17 | 28.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367854.17 | 761.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330615.67 | 125.33 | 72.00 | 0.00 | 0.00 |
CORE_MID | 330712.00 | 101.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330798.00 | 15.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2128.33 | 139.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2114.17 | 153.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2110.83 | 157.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 101718.33 | 1676.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367854.17 | 1676.67 | 72.00 | 0.00 | 0.00 |
Average | 80195.67 | 136.11 | 3.13 | 0.00 | 0.00 |
Sum | 1844500.50 | 3130.50 | 72.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:29
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.507106E+11 | 113401.85 | 02-JAN-04:11 | 1.13 | 0.68 | 0.566122E+10 | 7499.20 | 20-JAN-10:20 | 4.67 | 4.23 |
February | 0.465824E+11 | 114403.93 | 21-FEB-04:01 | 5.93 | 5.00 | 0.513562E+10 | 7499.15 | 17-FEB-10:09 | 5.93 | 5.00 |
March | 0.568101E+11 | 111717.34 | 27-MAR-03:02 | 1.65 | 0.90 | 0.613036E+10 | 7499.13 | 28-MAR-13:20 | 10.33 | 6.95 |
April | 0.574004E+11 | 113102.86 | 10-APR-03:02 | 5.75 | 4.68 | 0.545053E+10 | 7499.30 | 25-APR-13:20 | 13.33 | 9.08 |
May | 0.576357E+11 | 111457.41 | 30-MAY-03:02 | 8.00 | 7.45 | 0.589971E+10 | 7499.07 | 16-MAY-13:20 | 8.00 | 7.45 |
June | 0.598801E+11 | 112666.31 | 12-JUN-03:02 | 8.83 | 8.83 | 0.588131E+10 | 7499.34 | 08-JUN-13:20 | 8.83 | 8.83 |
July | 0.605998E+11 | 112051.91 | 03-JUL-03:02 | 9.83 | 8.38 | 0.547287E+10 | 7499.11 | 18-JUL-13:20 | 19.00 | 15.69 |
August | 0.667016E+11 | 112438.50 | 28-AUG-03:02 | 9.83 | 9.25 | 0.613703E+10 | 7499.41 | 08-AUG-13:09 | 9.83 | 9.25 |
September | 0.578889E+11 | 113036.51 | 05-SEP-03:02 | 8.67 | 7.28 | 0.545054E+10 | 7499.32 | 06-SEP-09:20 | 13.67 | 11.59 |
October | 0.579333E+11 | 112341.60 | 16-OCT-03:02 | 8.17 | 8.08 | 0.566778E+10 | 7499.31 | 17-OCT-09:20 | 11.67 | 11.31 |
November | 0.555722E+11 | 113365.04 | 27-NOV-04:01 | 4.83 | 4.00 | 0.561168E+10 | 7499.12 | 10-NOV-10:20 | 4.83 | 4.00 |
December | 0.533400E+11 | 112071.36 | 04-DEC-04:01 | 1.33 | 0.37 | 0.546628E+10 | 7499.12 | 20-DEC-10:20 | 8.33 | 7.62 |
Annual Sum or Average | 0.681055E+12 | 0.679649E+11 | ||||||||
Minimum of Months | 0.465824E+11 | 111457.41 | 1.13 | 0.37 | 0.513562E+10 | 7499.07 | 4.67 | 4.00 | ||
Maximum of Months | 0.667016E+11 | 114403.93 | 9.83 | 9.25 | 0.613703E+10 | 7499.41 | 19.00 | 15.69 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.396042E+11 | 88689.19 | 02-JAN-05:01 | 1.00 | 0.59 | 0.506305E+10 | 6734.78 | 20-JAN-10:20 | 4.67 | 4.23 |
February | 0.388598E+11 | 88324.76 | 21-FEB-04:01 | 5.93 | 5.00 | 0.460033E+10 | 6734.78 | 17-FEB-10:09 | 5.93 | 5.00 |
March | 0.503016E+11 | 90705.28 | 27-MAR-04:01 | 1.33 | 0.49 | 0.550042E+10 | 6734.78 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.571486E+11 | 95138.46 | 24-APR-03:02 | 7.00 | 5.63 | 0.488608E+10 | 6735.06 | 14-APR-13:00 | 7.00 | 5.63 |
May | 0.520328E+11 | 91904.61 | 01-MAY-03:02 | 6.17 | 5.21 | 0.528645E+10 | 6734.74 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.576408E+11 | 92767.64 | 05-JUN-03:02 | 11.17 | 11.17 | 0.527159E+10 | 6734.99 | 08-JUN-13:09 | 13.50 | 10.04 |
July | 0.616411E+11 | 95206.23 | 05-JUL-03:02 | 8.00 | 6.98 | 0.489905E+10 | 6734.85 | 03-JUL-09:09 | 8.00 | 6.98 |
August | 0.695487E+11 | 91890.00 | 28-AUG-03:02 | 9.83 | 9.25 | 0.549913E+10 | 6734.93 | 08-AUG-09:00 | 9.83 | 9.25 |
September | 0.515433E+11 | 92573.41 | 05-SEP-03:02 | 8.67 | 7.28 | 0.487992E+10 | 6734.99 | 06-SEP-09:09 | 13.33 | 11.45 |
October | 0.482769E+11 | 95619.44 | 10-OCT-03:02 | 10.83 | 10.83 | 0.508053E+10 | 6734.96 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.462614E+11 | 93192.86 | 13-NOV-04:02 | 5.50 | 5.09 | 0.503103E+10 | 6734.75 | 10-NOV-10:20 | 5.50 | 5.09 |
December | 0.445426E+11 | 88558.18 | 18-DEC-05:01 | 0.83 | 0.83 | 0.490002E+10 | 6734.82 | 04-DEC-14:00 | 0.83 | 0.83 |
Annual Sum or Average | 0.617402E+12 | 0.608976E+11 | ||||||||
Minimum of Months | 0.388598E+11 | 88324.76 | 0.83 | 0.49 | 0.460033E+10 | 6734.74 | 0.83 | 0.83 | ||
Maximum of Months | 0.695487E+11 | 95619.44 | 11.17 | 11.17 | 0.550042E+10 | 6735.06 | 23.00 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278022E+11 | 72443.43 | 26-JAN-06:02 | 5.00 | 4.51 | 0.492694E+10 | 6734.77 | 20-JAN-10:20 | 5.00 | 4.51 |
February | 0.264102E+11 | 71446.14 | 10-FEB-06:02 | 5.00 | 4.51 | 0.451095E+10 | 6734.78 | 17-FEB-10:09 | 3.50 | 2.58 |
March | 0.329868E+11 | 74769.50 | 24-MAR-05:02 | 4.00 | 3.12 | 0.542372E+10 | 6734.72 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.379197E+11 | 79618.57 | 13-APR-05:02 | 6.00 | 4.60 | 0.485770E+10 | 6734.98 | 14-APR-13:00 | 13.00 | 8.45 |
May | 0.407395E+11 | 80511.85 | 31-MAY-05:02 | 7.67 | 7.59 | 0.526164E+10 | 6734.71 | 22-MAY-13:00 | 7.67 | 7.59 |
June | 0.444074E+11 | 80991.89 | 27-JUN-04:03 | 14.00 | 14.00 | 0.525836E+10 | 6734.94 | 08-JUN-13:09 | 14.00 | 14.00 |
July | 0.442744E+11 | 81207.43 | 25-JUL-04:03 | 13.00 | 12.54 | 0.488649E+10 | 6734.79 | 03-JUL-09:09 | 13.00 | 12.54 |
August | 0.484941E+11 | 80901.46 | 15-AUG-04:02 | 13.17 | 10.37 | 0.548845E+10 | 6734.88 | 08-AUG-09:00 | 13.17 | 10.37 |
September | 0.413212E+11 | 81104.15 | 14-SEP-04:02 | 11.00 | 9.85 | 0.486220E+10 | 6734.92 | 06-SEP-09:09 | 11.00 | 9.85 |
October | 0.339811E+11 | 80251.88 | 05-OCT-05:02 | 4.00 | 4.00 | 0.502815E+10 | 6734.88 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.289351E+11 | 73116.81 | 01-NOV-05:02 | 5.00 | 4.51 | 0.493718E+10 | 6734.73 | 10-NOV-10:20 | 11.00 | 9.41 |
December | 0.260367E+11 | 43866.58 | 22-DEC-06:03 | 3.00 | 2.55 | 0.471524E+10 | 6734.71 | 08-DEC-10:39 | 3.00 | 2.55 |
Annual Sum or Average | 0.433308E+12 | 0.601570E+11 | ||||||||
Minimum of Months | 0.260367E+11 | 43866.58 | 3.00 | 2.55 | 0.451095E+10 | 6734.71 | 3.00 | 2.55 | ||
Maximum of Months | 0.484941E+11 | 81207.43 | 14.00 | 14.00 | 0.548845E+10 | 6734.98 | 14.00 | 14.00 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200316E+11 | 23716.07 | 19-JAN-17:00 | 6.00 | 6.00 | 0.431544E+10 | 6734.51 | 20-JAN-14:00 | 8.00 | 6.49 |
February | 0.194788E+11 | 22882.94 | 09-FEB-17:00 | 6.00 | 4.60 | 0.400763E+10 | 6676.34 | 09-FEB-14:00 | 6.00 | 4.60 |
March | 0.249024E+11 | 27611.94 | 31-MAR-16:00 | 9.00 | 4.96 | 0.496881E+10 | 6734.52 | 31-MAR-13:00 | 9.00 | 4.96 |
April | 0.315683E+11 | 69540.28 | 21-APR-05:03 | 8.00 | 6.97 | 0.472901E+10 | 6734.95 | 14-APR-13:00 | 8.00 | 6.97 |
May | 0.351604E+11 | 71837.15 | 23-MAY-05:03 | 9.67 | 9.01 | 0.516353E+10 | 6734.71 | 22-MAY-13:00 | 9.67 | 9.01 |
June | 0.415632E+11 | 76020.21 | 26-JUN-05:02 | 14.33 | 11.96 | 0.522198E+10 | 6734.89 | 09-JUN-13:00 | 14.33 | 11.96 |
July | 0.424342E+11 | 76776.69 | 25-JUL-05:02 | 13.00 | 13.00 | 0.485675E+10 | 6734.75 | 18-JUL-13:09 | 13.00 | 13.00 |
August | 0.452316E+11 | 75718.62 | 17-AUG-05:02 | 13.17 | 13.07 | 0.545866E+10 | 6734.82 | 08-AUG-09:00 | 13.17 | 13.07 |
September | 0.354481E+11 | 72946.73 | 13-SEP-05:03 | 9.33 | 9.25 | 0.479548E+10 | 6734.86 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.252726E+11 | 35233.41 | 05-OCT-16:00 | 16.00 | 9.13 | 0.471056E+10 | 6734.57 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.212078E+11 | 27518.79 | 10-NOV-16:40 | 8.33 | 7.19 | 0.442338E+10 | 6734.45 | 09-NOV-14:00 | 8.33 | 7.19 |
December | 0.190782E+11 | 19207.07 | 21-DEC-17:00 | 6.00 | 5.49 | 0.410830E+10 | 6556.03 | 21-DEC-14:00 | 6.00 | 5.49 |
Annual Sum or Average | 0.361377E+12 | 0.567595E+11 | ||||||||
Minimum of Months | 0.190782E+11 | 19207.07 | 6.00 | 4.60 | 0.400763E+10 | 6556.03 | 6.00 | 4.60 | ||
Maximum of Months | 0.452316E+11 | 76776.69 | 16.00 | 13.07 | 0.545866E+10 | 6734.95 | 16.00 | 14.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285049E+10 | 2968.93 | 18-JAN-06:02 | 6.17 | 5.66 | 0.569842E+09 | 845.61 | 19-JAN-14:00 | 9.00 | 7.43 |
February | 0.282836E+10 | 3155.41 | 21-FEB-14:10 | 9.00 | 7.84 | 0.535320E+09 | 845.61 | 21-FEB-14:09 | 9.00 | 7.84 |
March | 0.390759E+10 | 4805.88 | 20-MAR-12:40 | 10.20 | 6.56 | 0.665696E+09 | 845.63 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.562539E+10 | 6848.68 | 28-APR-14:00 | 20.00 | 12.76 | 0.606544E+09 | 845.66 | 14-APR-13:00 | 20.00 | 12.76 |
May | 0.548856E+10 | 6892.98 | 22-MAY-15:00 | 24.00 | 16.08 | 0.656414E+09 | 845.63 | 22-MAY-13:00 | 24.00 | 16.08 |
June | 0.723380E+10 | 11361.11 | 26-JUN-05:02 | 14.33 | 11.96 | 0.660150E+09 | 845.66 | 08-JUN-13:09 | 14.33 | 11.96 |
July | 0.800917E+10 | 11052.39 | 24-JUL-05:03 | 13.00 | 13.00 | 0.614191E+09 | 845.64 | 18-JUL-13:09 | 13.00 | 13.00 |
August | 0.841086E+10 | 8994.84 | 07-AUG-05:03 | 10.17 | 9.06 | 0.688974E+09 | 845.64 | 08-AUG-09:00 | 18.00 | 14.98 |
September | 0.534464E+10 | 6397.39 | 13-SEP-15:10 | 23.00 | 16.22 | 0.605806E+09 | 845.64 | 06-SEP-09:09 | 23.00 | 16.22 |
October | 0.395010E+10 | 5431.71 | 10-OCT-13:10 | 13.00 | 11.87 | 0.619442E+09 | 845.62 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.329786E+10 | 3681.25 | 08-NOV-14:30 | 12.00 | 11.73 | 0.598948E+09 | 845.62 | 24-NOV-14:09 | 12.83 | 11.81 |
December | 0.298796E+10 | 2945.82 | 11-DEC-05:02 | 3.00 | 3.00 | 0.563018E+09 | 841.41 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.599348E+11 | 0.738435E+10 | ||||||||
Minimum of Months | 0.282836E+10 | 2945.82 | 3.00 | 3.00 | 0.535320E+09 | 841.41 | 8.00 | 6.98 | ||
Maximum of Months | 0.841086E+10 | 11361.11 | 24.00 | 16.22 | 0.688974E+09 | 845.66 | 24.00 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316970E+10 | 3862.07 | 18-JAN-06:02 | 6.17 | 5.66 | 0.336415E+09 | 544.52 | 20-JAN-10:30 | 5.00 | 4.55 |
February | 0.321124E+10 | 4330.11 | 17-FEB-09:45 | 2.67 | 1.90 | 0.314663E+09 | 544.95 | 17-FEB-10:09 | 3.50 | 2.58 |
March | 0.413422E+10 | 4015.50 | 20-MAR-03:02 | 5.92 | 5.48 | 0.385074E+09 | 544.72 | 31-MAR-09:00 | 9.00 | 5.32 |
April | 0.644735E+10 | 20081.15 | 30-APR-08:52 | 18.00 | 11.96 | 0.384972E+09 | 544.98 | 14-APR-13:00 | 18.00 | 11.96 |
May | 0.652509E+10 | 19538.56 | 21-MAY-08:22 | 13.00 | 9.56 | 0.414987E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.730557E+10 | 19329.64 | 25-JUN-09:52 | 18.00 | 12.90 | 0.419832E+09 | 545.01 | 13-JUN-09:09 | 18.00 | 12.90 |
July | 0.792309E+10 | 18136.05 | 23-JUL-08:12 | 19.33 | 15.41 | 0.392380E+09 | 544.97 | 03-JUL-09:09 | 19.33 | 15.41 |
August | 0.851038E+10 | 15268.71 | 20-AUG-10:13 | 16.33 | 13.20 | 0.438314E+09 | 544.97 | 23-AUG-09:09 | 16.17 | 12.09 |
September | 0.650637E+10 | 13817.55 | 24-SEP-09:23 | 18.00 | 14.39 | 0.386864E+09 | 544.99 | 06-SEP-09:09 | 18.00 | 14.39 |
October | 0.444088E+10 | 7279.91 | 01-OCT-08:55 | 12.00 | 8.41 | 0.370730E+09 | 544.96 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.358553E+10 | 4085.46 | 13-NOV-04:02 | 5.50 | 5.09 | 0.342367E+09 | 544.95 | 13-NOV-10:09 | 8.17 | 7.54 |
December | 0.301107E+10 | 3680.09 | 11-DEC-05:02 | 3.00 | 3.00 | 0.320518E+09 | 514.48 | 26-DEC-10:30 | 3.50 | 1.21 |
Annual Sum or Average | 0.647705E+11 | 0.450712E+10 | ||||||||
Minimum of Months | 0.301107E+10 | 3680.09 | 2.67 | 1.90 | 0.314663E+09 | 514.48 | 3.50 | 1.21 | ||
Maximum of Months | 0.851038E+10 | 20081.15 | 19.33 | 15.41 | 0.438314E+09 | 545.01 | 23.00 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.538493E+10 | 12726.29 | 20-JAN-12:00 | 8.00 | 6.08 | 0.547999E+09 | 845.64 | 20-JAN-10:00 | 8.00 | 6.08 |
February | 0.583344E+10 | 14332.79 | 17-FEB-13:30 | 6.00 | 3.38 | 0.512258E+09 | 845.64 | 17-FEB-10:00 | 6.00 | 3.38 |
March | 0.632455E+10 | 9916.16 | 28-MAR-12:10 | 11.67 | 7.18 | 0.613925E+09 | 845.66 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.106718E+11 | 29943.27 | 30-APR-12:52 | 22.00 | 13.06 | 0.592718E+09 | 846.74 | 28-APR-13:39 | 22.00 | 13.06 |
May | 0.914721E+10 | 14427.84 | 22-MAY-13:10 | 22.17 | 14.96 | 0.632000E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.101118E+11 | 14406.95 | 11-JUN-14:02 | 17.83 | 14.32 | 0.646343E+09 | 845.69 | 08-JUN-13:09 | 17.83 | 14.32 |
July | 0.117375E+11 | 18182.01 | 16-JUL-14:02 | 19.00 | 15.28 | 0.606328E+09 | 845.66 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.140374E+11 | 18331.84 | 06-AUG-13:13 | 17.33 | 13.63 | 0.682112E+09 | 846.30 | 29-AUG-13:50 | 17.83 | 13.84 |
September | 0.118404E+11 | 28364.31 | 24-SEP-14:02 | 21.17 | 15.44 | 0.598922E+09 | 846.50 | 27-SEP-13:00 | 22.00 | 13.55 |
October | 0.830649E+10 | 17352.12 | 03-OCT-13:10 | 13.17 | 9.32 | 0.585390E+09 | 846.12 | 03-OCT-13:00 | 14.00 | 9.41 |
November | 0.602563E+10 | 22483.75 | 11-NOV-13:13 | 9.00 | 7.29 | 0.555527E+09 | 845.64 | 13-NOV-10:09 | 8.17 | 7.54 |
December | 0.498694E+10 | 12686.85 | 18-DEC-13:30 | 8.00 | 5.46 | 0.521978E+09 | 845.64 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.104408E+12 | 0.709550E+10 | ||||||||
Minimum of Months | 0.498694E+10 | 9916.16 | 6.00 | 3.38 | 0.512258E+09 | 845.64 | 6.00 | 3.37 | ||
Maximum of Months | 0.140374E+11 | 29943.27 | 22.17 | 15.44 | 0.682112E+09 | 846.74 | 23.00 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.452728E+10 | 6637.49 | 30-JAN-16:30 | 7.55 | 6.78 | 0.349160E+09 | 544.94 | 19-JAN-14:00 | 7.55 | 6.78 |
February | 0.499593E+10 | 8936.44 | 27-FEB-16:30 | 8.00 | 6.72 | 0.339179E+09 | 544.94 | 13-FEB-14:00 | 8.00 | 6.72 |
March | 0.644022E+10 | 9662.37 | 23-MAR-16:00 | 10.00 | 6.65 | 0.427594E+09 | 544.96 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.993780E+10 | 25108.19 | 30-APR-16:11 | 24.00 | 12.95 | 0.394364E+09 | 544.99 | 14-APR-13:00 | 24.00 | 12.95 |
May | 0.815448E+10 | 21077.57 | 21-MAY-15:02 | 18.83 | 10.43 | 0.413014E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.102637E+11 | 26524.46 | 25-JUN-16:41 | 21.67 | 14.18 | 0.424906E+09 | 544.98 | 08-JUN-13:09 | 21.67 | 14.18 |
July | 0.120674E+11 | 25377.00 | 09-JUL-15:02 | 21.00 | 15.38 | 0.396765E+09 | 544.96 | 03-JUL-09:09 | 21.00 | 15.38 |
August | 0.132603E+11 | 24802.22 | 20-AUG-16:12 | 23.33 | 14.80 | 0.445687E+09 | 544.97 | 08-AUG-09:00 | 23.33 | 14.80 |
September | 0.775051E+10 | 23249.96 | 24-SEP-16:02 | 21.83 | 15.35 | 0.383514E+09 | 544.97 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.624037E+10 | 10451.94 | 03-OCT-15:30 | 14.00 | 8.96 | 0.389729E+09 | 544.96 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.556822E+10 | 7519.27 | 09-NOV-06:03 | 9.00 | 9.00 | 0.383845E+09 | 544.95 | 08-NOV-14:00 | 9.00 | 9.00 |
December | 0.535081E+10 | 6785.91 | 18-DEC-14:30 | 8.00 | 5.66 | 0.371765E+09 | 544.95 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.945570E+11 | 0.471952E+10 | ||||||||
Minimum of Months | 0.452728E+10 | 6637.49 | 7.55 | 5.66 | 0.339179E+09 | 544.94 | 6.00 | 3.37 | ||
Maximum of Months | 0.132603E+11 | 26524.46 | 24.00 | 15.38 | 0.445687E+09 | 544.99 | 24.00 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137100E+10 | 2193.18 | 26-JAN-06:02 | 5.00 | 4.51 | 0.495009E+09 | 759.79 | 19-JAN-14:00 | 5.00 | 4.51 |
February | 0.146356E+10 | 2010.93 | 08-FEB-16:30 | 8.00 | 7.73 | 0.456906E+09 | 740.73 | 22-FEB-14:00 | 9.00 | 6.99 |
March | 0.235585E+10 | 2297.94 | 24-MAR-05:02 | 4.00 | 3.12 | 0.578198E+09 | 816.24 | 30-MAR-13:00 | 13.00 | 7.37 |
April | 0.332550E+10 | 5271.30 | 28-APR-15:30 | 20.05 | 13.01 | 0.574437E+09 | 845.64 | 14-APR-13:00 | 20.05 | 13.01 |
May | 0.384775E+10 | 5602.45 | 23-MAY-14:00 | 19.00 | 14.77 | 0.632062E+09 | 845.62 | 22-MAY-13:00 | 19.00 | 14.77 |
June | 0.518357E+10 | 7334.43 | 13-JUN-16:00 | 26.50 | 17.70 | 0.652452E+09 | 845.65 | 08-JUN-13:09 | 26.50 | 17.70 |
July | 0.550041E+10 | 7074.92 | 10-JUL-15:00 | 23.00 | 16.69 | 0.607887E+09 | 845.63 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.545585E+10 | 6178.24 | 10-AUG-15:00 | 21.00 | 15.45 | 0.680661E+09 | 845.63 | 08-AUG-09:00 | 21.00 | 15.45 |
September | 0.390131E+10 | 5587.59 | 13-SEP-15:30 | 23.00 | 16.22 | 0.588432E+09 | 845.63 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.255829E+10 | 3042.69 | 11-OCT-15:00 | 17.00 | 11.04 | 0.556596E+09 | 845.60 | 11-OCT-13:30 | 17.00 | 11.04 |
November | 0.176558E+10 | 2432.26 | 09-NOV-06:03 | 9.00 | 9.00 | 0.506506E+09 | 781.91 | 10-NOV-14:00 | 12.00 | 8.42 |
December | 0.102860E+10 | 1859.71 | 21-DEC-16:10 | 6.83 | 6.31 | 0.461920E+09 | 700.83 | 21-DEC-14:50 | 6.83 | 6.31 |
Annual Sum or Average | 0.377573E+11 | 0.679107E+10 | ||||||||
Minimum of Months | 0.102860E+10 | 1859.71 | 4.00 | 3.12 | 0.456906E+09 | 700.83 | 5.00 | 4.51 | ||
Maximum of Months | 0.550041E+10 | 7334.43 | 26.50 | 17.70 | 0.680661E+09 | 845.65 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147739E+10 | 3062.91 | 20-JAN-10:00 | 4.00 | 3.60 | 0.225268E+09 | 462.02 | 20-JAN-09:00 | 4.00 | 3.60 |
February | 0.168621E+10 | 3272.23 | 17-FEB-10:00 | 3.00 | 2.16 | 0.208373E+09 | 486.91 | 17-FEB-09:00 | 3.00 | 2.16 |
March | 0.259100E+10 | 3259.28 | 24-MAR-05:02 | 4.00 | 3.12 | 0.252777E+09 | 476.10 | 30-MAR-10:39 | 9.67 | 6.89 |
April | 0.530049E+10 | 20743.60 | 30-APR-09:22 | 19.00 | 12.37 | 0.272935E+09 | 521.32 | 28-APR-07:00 | 19.00 | 12.37 |
May | 0.569833E+10 | 11560.43 | 23-MAY-09:00 | 19.00 | 14.78 | 0.292703E+09 | 521.21 | 22-MAY-14:09 | 19.00 | 14.78 |
June | 0.655147E+10 | 14967.44 | 11-JUN-09:43 | 16.00 | 13.04 | 0.301017E+09 | 521.46 | 13-JUN-08:00 | 21.60 | 15.95 |
July | 0.681997E+10 | 20105.65 | 23-JUL-08:52 | 20.00 | 15.65 | 0.285257E+09 | 521.23 | 10-JUL-10:39 | 20.00 | 15.65 |
August | 0.728241E+10 | 18226.34 | 20-AUG-10:13 | 16.33 | 13.20 | 0.316092E+09 | 521.23 | 14-AUG-07:10 | 16.33 | 13.20 |
September | 0.578398E+10 | 14487.34 | 04-SEP-09:32 | 14.33 | 10.99 | 0.277342E+09 | 521.22 | 07-SEP-10:09 | 13.17 | 10.79 |
October | 0.320666E+10 | 5730.59 | 04-OCT-10:10 | 13.02 | 9.83 | 0.248601E+09 | 521.20 | 02-OCT-10:30 | 13.02 | 9.83 |
November | 0.182294E+10 | 3424.04 | 09-NOV-06:03 | 9.00 | 9.00 | 0.225082E+09 | 456.03 | 03-NOV-10:30 | 9.00 | 9.00 |
December | 0.962018E+09 | 2641.55 | 06-DEC-10:00 | 4.00 | 3.12 | 0.214051E+09 | 419.39 | 06-DEC-09:00 | 4.00 | 3.12 |
Annual Sum or Average | 0.491829E+11 | 0.311950E+10 | ||||||||
Minimum of Months | 0.962018E+09 | 2641.55 | 3.00 | 2.16 | 0.208373E+09 | 419.39 | 3.00 | 2.16 | ||
Maximum of Months | 0.728241E+10 | 20743.60 | 20.00 | 15.65 | 0.316092E+09 | 521.46 | 21.60 | 15.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405599E+10 | 12135.21 | 20-JAN-12:00 | 8.00 | 6.08 | 0.523438E+09 | 845.64 | 20-JAN-10:39 | 8.00 | 6.08 |
February | 0.455595E+10 | 15186.24 | 17-FEB-13:40 | 6.00 | 3.25 | 0.488712E+09 | 845.64 | 17-FEB-10:00 | 6.00 | 3.25 |
March | 0.465191E+10 | 8262.84 | 28-MAR-12:10 | 11.67 | 7.18 | 0.570415E+09 | 845.65 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.884729E+10 | 30708.06 | 30-APR-12:42 | 22.00 | 13.22 | 0.573727E+09 | 846.40 | 28-APR-13:39 | 22.00 | 13.22 |
May | 0.804385E+10 | 14420.58 | 22-MAY-13:20 | 22.33 | 15.12 | 0.610235E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.870350E+10 | 13840.02 | 13-JUN-13:20 | 24.37 | 17.19 | 0.628570E+09 | 845.69 | 08-JUN-13:09 | 24.37 | 17.19 |
July | 0.967183E+10 | 14362.05 | 31-JUL-13:10 | 18.17 | 12.08 | 0.593975E+09 | 845.66 | 18-JUL-13:09 | 18.17 | 12.08 |
August | 0.117064E+11 | 26355.84 | 13-AUG-14:52 | 21.00 | 15.45 | 0.668677E+09 | 846.31 | 29-AUG-13:50 | 17.83 | 13.84 |
September | 0.113432E+11 | 29353.97 | 10-SEP-12:12 | 21.00 | 15.44 | 0.589553E+09 | 846.68 | 29-SEP-13:00 | 16.00 | 9.47 |
October | 0.719104E+10 | 25615.49 | 01-OCT-12:43 | 12.33 | 9.81 | 0.558454E+09 | 846.05 | 04-OCT-13:50 | 14.00 | 10.28 |
November | 0.425156E+10 | 12382.06 | 03-NOV-12:40 | 9.00 | 5.48 | 0.517979E+09 | 845.63 | 03-NOV-13:00 | 9.00 | 5.72 |
December | 0.265190E+10 | 10752.22 | 18-DEC-13:30 | 8.00 | 5.46 | 0.484269E+09 | 845.64 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.856745E+11 | 0.680800E+10 | ||||||||
Minimum of Months | 0.265190E+10 | 8262.84 | 6.00 | 3.25 | 0.484269E+09 | 845.63 | 6.00 | 3.25 | ||
Maximum of Months | 0.117064E+11 | 30708.06 | 24.37 | 17.19 | 0.668677E+09 | 846.68 | 24.37 | 17.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186287E+10 | 3613.92 | 19-JAN-15:50 | 8.17 | 7.46 | 0.310707E+09 | 504.62 | 19-JAN-15:00 | 8.00 | 7.45 |
February | 0.226228E+10 | 5585.74 | 27-FEB-16:30 | 8.00 | 6.72 | 0.290225E+09 | 521.18 | 27-FEB-16:00 | 8.00 | 6.97 |
March | 0.315094E+10 | 5559.01 | 23-MAR-17:00 | 10.00 | 6.65 | 0.348991E+09 | 521.17 | 31-MAR-15:00 | 9.00 | 4.96 |
April | 0.538756E+10 | 22021.53 | 30-APR-17:21 | 24.00 | 12.86 | 0.350042E+09 | 544.95 | 28-APR-13:00 | 24.00 | 12.86 |
May | 0.595045E+10 | 22432.17 | 21-MAY-16:52 | 20.00 | 12.79 | 0.381603E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.715387E+10 | 21191.67 | 11-JUN-16:42 | 14.33 | 12.47 | 0.401647E+09 | 544.97 | 09-JUN-13:00 | 14.33 | 12.47 |
July | 0.758316E+10 | 22216.14 | 09-JUL-16:51 | 21.00 | 15.03 | 0.380599E+09 | 544.96 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.743601E+10 | 22307.54 | 13-AUG-16:52 | 19.00 | 14.78 | 0.423525E+09 | 544.96 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.571822E+10 | 17951.83 | 10-SEP-16:12 | 20.33 | 16.35 | 0.357462E+09 | 544.96 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.357060E+10 | 7885.44 | 03-OCT-16:00 | 14.00 | 8.96 | 0.334272E+09 | 543.50 | 05-OCT-13:00 | 16.00 | 8.75 |
November | 0.230050E+10 | 3796.60 | 09-NOV-06:03 | 9.00 | 9.00 | 0.310700E+09 | 518.30 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.126254E+10 | 3042.51 | 21-DEC-14:40 | 8.00 | 6.98 | 0.292954E+09 | 465.91 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.536390E+11 | 0.418273E+10 | ||||||||
Minimum of Months | 0.126254E+10 | 3042.51 | 8.00 | 6.65 | 0.290225E+09 | 465.91 | 8.00 | 4.96 | ||
Maximum of Months | 0.758316E+10 | 22432.17 | 24.00 | 16.35 | 0.423525E+09 | 544.97 | 24.00 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.514417E+09 | 1916.21 | 19-JAN-16:10 | 7.67 | 7.22 | 0.469673E+09 | 697.80 | 19-JAN-14:00 | 7.67 | 7.22 |
February | 0.633700E+09 | 1799.03 | 09-FEB-16:00 | 8.00 | 5.66 | 0.427160E+09 | 671.14 | 22-FEB-14:00 | 9.00 | 6.99 |
March | 0.136993E+10 | 2145.36 | 30-MAR-15:30 | 12.00 | 6.19 | 0.529897E+09 | 752.92 | 30-MAR-13:00 | 12.00 | 6.19 |
April | 0.269080E+10 | 5462.43 | 28-APR-15:40 | 20.03 | 12.78 | 0.538581E+09 | 845.63 | 14-APR-13:00 | 20.03 | 12.78 |
May | 0.328064E+10 | 6156.21 | 22-MAY-15:40 | 23.33 | 15.55 | 0.596597E+09 | 845.62 | 22-MAY-13:00 | 23.33 | 15.55 |
June | 0.477064E+10 | 8173.51 | 13-JUN-16:00 | 26.50 | 17.70 | 0.637216E+09 | 845.64 | 09-JUN-13:00 | 26.50 | 17.70 |
July | 0.518225E+10 | 7778.77 | 10-JUL-15:00 | 23.00 | 16.69 | 0.598701E+09 | 845.63 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.501404E+10 | 6638.20 | 14-AUG-16:00 | 26.00 | 15.86 | 0.667467E+09 | 845.63 | 15-AUG-13:00 | 19.00 | 15.28 |
September | 0.328021E+10 | 5701.43 | 13-SEP-15:30 | 23.00 | 16.22 | 0.563476E+09 | 845.62 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.167797E+10 | 2378.10 | 06-OCT-16:00 | 17.00 | 9.21 | 0.505375E+09 | 797.16 | 11-OCT-13:00 | 16.00 | 10.23 |
November | 0.788890E+09 | 2029.07 | 10-NOV-15:30 | 11.50 | 8.42 | 0.470816E+09 | 728.94 | 10-NOV-14:00 | 11.50 | 8.42 |
December | 0.267116E+09 | 1674.42 | 21-DEC-16:20 | 6.67 | 6.15 | 0.448267E+09 | 639.86 | 21-DEC-14:00 | 6.67 | 6.15 |
Annual Sum or Average | 0.294706E+11 | 0.645323E+10 | ||||||||
Minimum of Months | 0.267116E+09 | 1674.42 | 6.67 | 5.66 | 0.427160E+09 | 639.86 | 6.67 | 6.15 | ||
Maximum of Months | 0.518225E+10 | 8173.51 | 26.50 | 17.70 | 0.667467E+09 | 845.64 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.626224E+09 | 2645.97 | 20-JAN-10:30 | 5.00 | 4.55 | 0.301026E+09 | 447.00 | 20-JAN-10:39 | 5.33 | 4.86 |
February | 0.870880E+09 | 2783.74 | 24-FEB-10:30 | 5.50 | 4.13 | 0.275339E+09 | 462.55 | 24-FEB-10:39 | 5.67 | 4.28 |
March | 0.157811E+10 | 2779.80 | 30-MAR-10:40 | 9.67 | 6.89 | 0.332988E+09 | 454.62 | 31-MAR-09:00 | 9.00 | 5.32 |
April | 0.455072E+10 | 18562.24 | 30-APR-10:23 | 19.50 | 11.92 | 0.365523E+09 | 544.98 | 14-APR-13:00 | 19.50 | 11.92 |
May | 0.501569E+10 | 11668.40 | 21-MAY-09:02 | 13.00 | 9.47 | 0.391405E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.623386E+10 | 19638.18 | 25-JUN-10:02 | 18.50 | 13.17 | 0.406769E+09 | 545.63 | 13-JUN-09:00 | 18.50 | 13.17 |
July | 0.654432E+10 | 19876.34 | 16-JUL-09:12 | 16.00 | 13.59 | 0.386392E+09 | 544.97 | 03-JUL-09:09 | 16.00 | 13.59 |
August | 0.694646E+10 | 18561.23 | 20-AUG-08:42 | 16.83 | 13.42 | 0.429450E+09 | 544.97 | 23-AUG-09:09 | 16.17 | 12.09 |
September | 0.508207E+10 | 9569.80 | 12-SEP-09:30 | 17.50 | 14.46 | 0.374695E+09 | 544.98 | 06-SEP-09:09 | 17.50 | 14.46 |
October | 0.221493E+10 | 4424.72 | 04-OCT-10:00 | 13.00 | 9.81 | 0.325849E+09 | 544.94 | 04-OCT-09:50 | 13.00 | 9.81 |
November | 0.843152E+09 | 2549.85 | 10-NOV-15:00 | 12.00 | 8.42 | 0.299218E+09 | 436.27 | 03-NOV-09:00 | 12.00 | 8.42 |
December | 0.332426E+09 | 2258.65 | 06-DEC-06:05 | 3.17 | 2.31 | 0.288925E+09 | 403.38 | 04-DEC-10:20 | 3.17 | 2.31 |
Annual Sum or Average | 0.408388E+11 | 0.417758E+10 | ||||||||
Minimum of Months | 0.332426E+09 | 2258.65 | 3.17 | 2.31 | 0.275339E+09 | 403.38 | 3.17 | 2.31 | ||
Maximum of Months | 0.694646E+10 | 19876.34 | 19.50 | 14.46 | 0.429450E+09 | 545.63 | 23.00 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245837E+10 | 9465.30 | 20-JAN-12:00 | 8.00 | 6.08 | 0.496931E+09 | 845.64 | 20-JAN-14:50 | 8.17 | 6.51 |
February | 0.298239E+10 | 13025.66 | 17-FEB-14:10 | 6.00 | 3.06 | 0.464152E+09 | 845.63 | 24-FEB-14:20 | 6.00 | 4.60 |
March | 0.309915E+10 | 6119.00 | 10-MAR-14:40 | 8.67 | 4.91 | 0.537875E+09 | 845.65 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.777132E+10 | 29665.34 | 30-APR-13:42 | 22.83 | 12.83 | 0.551796E+09 | 846.48 | 28-APR-13:39 | 22.83 | 12.83 |
May | 0.713241E+10 | 14999.09 | 22-MAY-13:30 | 22.50 | 15.28 | 0.585829E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.831099E+10 | 14645.82 | 13-JUN-13:30 | 24.55 | 17.26 | 0.611076E+09 | 845.68 | 08-JUN-13:09 | 24.55 | 17.26 |
July | 0.939440E+10 | 15604.81 | 23-JUL-13:32 | 21.33 | 16.14 | 0.581638E+09 | 845.67 | 21-JUL-13:09 | 21.33 | 16.14 |
August | 0.112948E+11 | 24910.92 | 06-AUG-13:42 | 17.83 | 13.83 | 0.655220E+09 | 845.66 | 15-AUG-13:39 | 19.67 | 15.37 |
September | 0.103541E+11 | 30339.12 | 10-SEP-14:52 | 22.00 | 16.43 | 0.575323E+09 | 846.36 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.545459E+10 | 17359.68 | 03-OCT-13:30 | 13.50 | 9.36 | 0.531325E+09 | 845.66 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.254789E+10 | 10008.23 | 03-NOV-12:50 | 9.00 | 5.42 | 0.490423E+09 | 845.63 | 03-NOV-13:00 | 9.00 | 5.72 |
December | 0.141932E+10 | 7288.14 | 18-DEC-13:40 | 8.00 | 5.53 | 0.465455E+09 | 845.63 | 18-DEC-14:09 | 8.00 | 5.67 |
Annual Sum or Average | 0.722197E+11 | 0.654704E+10 | ||||||||
Minimum of Months | 0.141932E+10 | 6119.00 | 6.00 | 3.06 | 0.464152E+09 | 845.63 | 6.00 | 4.60 | ||
Maximum of Months | 0.112948E+11 | 30339.12 | 24.55 | 17.26 | 0.655220E+09 | 846.48 | 24.55 | 17.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.942029E+09 | 3541.36 | 19-JAN-15:50 | 8.17 | 7.46 | 0.303692E+09 | 480.25 | 19-JAN-15:00 | 8.00 | 7.45 |
February | 0.134438E+10 | 4401.27 | 27-FEB-16:40 | 8.00 | 6.81 | 0.281966E+09 | 521.18 | 27-FEB-16:00 | 8.00 | 6.97 |
March | 0.209179E+10 | 4773.02 | 23-MAR-17:00 | 10.00 | 6.65 | 0.335527E+09 | 513.07 | 23-MAR-15:00 | 10.00 | 6.65 |
April | 0.478205E+10 | 22016.34 | 30-APR-17:02 | 24.00 | 12.67 | 0.334297E+09 | 544.95 | 28-APR-13:00 | 24.00 | 12.67 |
May | 0.538441E+10 | 18379.95 | 21-MAY-17:02 | 20.00 | 12.86 | 0.365701E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.692213E+10 | 21635.03 | 25-JUN-17:32 | 21.67 | 18.03 | 0.389236E+09 | 544.97 | 09-JUN-13:00 | 21.67 | 18.03 |
July | 0.741914E+10 | 22486.64 | 23-JUL-16:52 | 21.00 | 16.54 | 0.371451E+09 | 544.96 | 18-JUL-13:09 | 21.00 | 16.54 |
August | 0.720169E+10 | 22631.69 | 20-AUG-16:41 | 22.33 | 14.82 | 0.411721E+09 | 544.96 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.519518E+10 | 15998.42 | 10-SEP-16:12 | 20.33 | 16.35 | 0.344068E+09 | 544.96 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.256452E+10 | 7342.29 | 03-OCT-16:00 | 14.00 | 8.96 | 0.319178E+09 | 522.64 | 03-OCT-13:00 | 14.00 | 8.96 |
November | 0.124676E+10 | 3577.07 | 10-NOV-15:40 | 11.33 | 8.41 | 0.302417E+09 | 489.72 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.530039E+09 | 2898.68 | 21-DEC-14:40 | 8.00 | 6.98 | 0.289731E+09 | 437.72 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.456241E+11 | 0.404899E+10 | ||||||||
Minimum of Months | 0.530039E+09 | 2898.68 | 8.00 | 6.65 | 0.281966E+09 | 437.72 | 8.00 | 6.65 | ||
Maximum of Months | 0.741914E+10 | 22631.69 | 24.00 | 18.03 | 0.411721E+09 | 544.97 | 24.00 | 18.03 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238658E+10 | 5542.13 | 02-JAN-06:10 | 1.17 | 0.75 | 0.00 | 0.00 | 01-JAN-00:10 | 1.17 | 0.75 |
February | 0.225321E+10 | 5318.07 | 24-FEB-06:08 | -0.3 | -0.3 | 0.00 | 0.00 | 01-FEB-00:10 | -0.3 | -0.3 |
March | 0.342844E+10 | 5810.72 | 25-MAR-05:10 | 1.83 | 1.40 | 0.00 | 0.00 | 01-MAR-00:10 | 1.83 | 1.40 |
April | 0.565967E+10 | 8095.67 | 10-APR-05:13 | 6.33 | 5.37 | 0.00 | 0.00 | 01-APR-00:10 | 6.33 | 5.37 |
May | 0.501403E+10 | 8564.48 | 01-MAY-05:15 | 4.67 | 3.91 | 0.00 | 0.00 | 01-MAY-00:10 | 4.67 | 3.91 |
June | 0.658307E+10 | 8777.37 | 05-JUN-05:13 | 12.00 | 11.46 | 0.00 | 0.00 | 01-JUN-00:10 | 12.00 | 11.46 |
July | 0.747785E+10 | 10769.22 | 24-JUL-05:13 | 13.00 | 13.00 | 0.00 | 0.00 | 01-JUL-00:10 | 13.00 | 13.00 |
August | 0.832737E+10 | 10229.34 | 21-AUG-05:13 | 11.00 | 9.86 | 0.00 | 0.00 | 01-AUG-00:10 | 11.00 | 9.86 |
September | 0.583001E+10 | 7912.78 | 14-SEP-05:13 | 11.33 | 10.21 | 0.00 | 0.00 | 01-SEP-00:10 | 11.33 | 10.21 |
October | 0.414229E+10 | 8978.40 | 10-OCT-05:13 | 11.00 | 11.00 | 0.00 | 0.00 | 01-OCT-00:10 | 11.00 | 11.00 |
November | 0.308621E+10 | 6544.15 | 13-NOV-06:13 | 4.33 | 3.86 | 0.00 | 0.00 | 01-NOV-00:10 | 4.33 | 3.86 |
December | 0.229893E+10 | 4507.40 | 27-DEC-06:07 | -2.0 | -2.0 | 0.00 | 0.00 | 01-DEC-00:10 | -2.0 | -2.0 |
Annual Sum or Average | 0.564877E+11 | 0.00 | ||||||||
Minimum of Months | 0.225321E+10 | 4507.40 | -2.0 | -2.0 | 0.00 | 0.00 | -2.0 | -2.0 | ||
Maximum of Months | 0.832737E+10 | 10769.22 | 13.00 | 13.00 | 0.00 | 0.00 | 13.00 | 13.00 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.883022E+09 | 3980.94 | 10-JAN-05:01 | -4.0 | -4.8 | 0.00 | 0.00 | 01-JAN-00:10 | -4.0 | -4.8 |
February | 0.952283E+09 | 5251.94 | 18-FEB-06:02 | -1.2 | -1.5 | 0.00 | 0.00 | 01-FEB-00:10 | -1.2 | -1.5 |
March | 0.157636E+10 | 3720.26 | 11-MAR-18:00 | 3.00 | 2.55 | 0.00 | 0.00 | 01-MAR-00:10 | 3.00 | 2.55 |
April | 0.299401E+10 | 5562.45 | 22-APR-05:17 | 6.33 | 5.52 | 0.00 | 0.00 | 01-APR-00:10 | 6.33 | 5.52 |
May | 0.317332E+10 | 5597.15 | 25-MAY-05:10 | 7.17 | 7.17 | 0.00 | 0.00 | 01-MAY-00:10 | 7.17 | 7.17 |
June | 0.442692E+10 | 5931.01 | 27-JUN-05:10 | 14.17 | 14.17 | 0.00 | 0.00 | 01-JUN-00:10 | 14.17 | 14.17 |
July | 0.490330E+10 | 6966.82 | 24-JUL-05:13 | 13.00 | 13.00 | 0.00 | 0.00 | 01-JUL-00:10 | 13.00 | 13.00 |
August | 0.531617E+10 | 6463.39 | 17-AUG-05:13 | 13.33 | 13.15 | 0.00 | 0.00 | 01-AUG-00:10 | 13.33 | 13.15 |
September | 0.413071E+10 | 6206.39 | 14-SEP-05:13 | 11.33 | 10.21 | 0.00 | 0.00 | 01-SEP-00:10 | 11.33 | 10.21 |
October | 0.228102E+10 | 5937.31 | 06-OCT-05:10 | 3.00 | 3.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3.00 | 3.00 |
November | 0.116662E+10 | 4730.69 | 17-NOV-06:02 | 2.67 | 1.51 | 0.00 | 0.00 | 01-NOV-00:10 | 2.67 | 1.51 |
December | 0.556640E+09 | 5007.40 | 30-DEC-05:01 | -1.8 | -3.4 | 0.00 | 0.00 | 01-DEC-00:10 | -1.8 | -3.4 |
Annual Sum or Average | 0.323604E+11 | 0.00 | ||||||||
Minimum of Months | 0.556640E+09 | 3720.26 | -4.0 | -4.8 | 0.00 | 0.00 | -4.0 | -4.8 | ||
Maximum of Months | 0.531617E+10 | 6966.82 | 14.17 | 14.17 | 0.00 | 0.00 | 14.17 | 14.17 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5188904.73 | 809.53 | 19-JAN-17:20 | 5.67 | 5.50 | 0.00 | 0.00 | 01-JAN-00:10 | 5.67 | 5.50 |
February | 21870995.03 | 1090.65 | 22-FEB-12:40 | 9.33 | 7.76 | 0.00 | 0.00 | 01-FEB-00:10 | 9.33 | 7.76 |
March | 0.310973E+09 | 3293.38 | 25-MAR-12:40 | 13.33 | 10.44 | 0.00 | 0.00 | 01-MAR-00:10 | 13.33 | 10.44 |
April | 0.383593E+10 | 13665.58 | 28-APR-14:50 | 20.08 | 13.54 | 0.00 | 0.00 | 01-APR-00:10 | 20.08 | 13.54 |
May | 0.445767E+10 | 14471.32 | 22-MAY-14:40 | 23.67 | 15.97 | 0.00 | 0.00 | 01-MAY-00:10 | 23.67 | 15.97 |
June | 0.686826E+10 | 16784.90 | 13-JUN-14:20 | 25.40 | 17.58 | 0.00 | 0.00 | 01-JUN-00:10 | 25.40 | 17.58 |
July | 0.793127E+10 | 16368.62 | 21-JUL-14:40 | 27.00 | 15.95 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 15.95 |
August | 0.757816E+10 | 14379.29 | 14-AUG-15:00 | 25.00 | 16.02 | 0.00 | 0.00 | 01-AUG-00:10 | 25.00 | 16.02 |
September | 0.454419E+10 | 12259.74 | 12-SEP-15:10 | 21.83 | 15.52 | 0.00 | 0.00 | 01-SEP-00:10 | 21.83 | 15.52 |
October | 0.893392E+09 | 5105.34 | 03-OCT-14:40 | 14.00 | 9.11 | 0.00 | 0.00 | 01-OCT-00:10 | 14.00 | 9.11 |
November | 22092595.74 | 1024.14 | 10-NOV-14:20 | 12.00 | 8.75 | 0.00 | 0.00 | 01-NOV-00:10 | 12.00 | 8.75 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.364690E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.00 | 3.53 | 0.00 | 0.00 | 4.00 | 3.53 | ||
Maximum of Months | 0.793127E+10 | 16784.90 | 27.00 | 17.58 | 0.00 | 0.00 | 27.00 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323479E+10 | 2012.16 | 19-JAN-16:20 | 7.33 | 6.98 | 95230133.77 | 126.83 | 18-JAN-14:00 | 7.33 | 6.98 |
February | 0.782438E+10 | 4177.31 | 27-FEB-17:00 | 8.00 | 6.97 | 86396566.64 | 126.83 | 08-FEB-14:00 | 8.00 | 6.97 |
March | 0.140781E+11 | 7038.06 | 31-MAR-24:00 | 4.30 | 1.71 | 0.103236E+09 | 126.82 | 20-MAR-09:09 | 4.30 | 1.71 |
April | 0.189788E+11 | 8268.36 | 30-APR-17:44 | 24.00 | 13.04 | 91605071.05 | 126.82 | 19-APR-09:09 | 24.00 | 13.04 |
May | 0.427156E+10 | 3390.21 | 31-MAY-24:00 | 9.40 | 7.45 | 99235002.05 | 126.84 | 23-MAY-13:00 | 9.40 | 7.45 |
June | 0.931417E+10 | 5216.82 | 30-JUN-24:00 | 11.00 | 9.86 | 98963338.09 | 126.85 | 27-JUN-09:09 | 11.00 | 9.86 |
July | 0.147546E+11 | 7292.04 | 31-JUL-24:00 | 11.40 | 9.79 | 91885001.71 | 126.83 | 25-JUL-09:09 | 11.40 | 9.79 |
August | 0.197568E+11 | 8128.84 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103238E+09 | 126.83 | 08-AUG-13:50 | 17.83 | 13.92 |
September | 0.417490E+10 | 3272.16 | 30-SEP-24:00 | 7.60 | 5.71 | 91609954.57 | 126.84 | 11-SEP-13:50 | 7.60 | 5.71 |
October | 0.909574E+10 | 5093.00 | 31-OCT-24:00 | 6.60 | 4.32 | 95232113.19 | 126.83 | 10-OCT-13:00 | 6.60 | 4.32 |
November | 0.135600E+11 | 5813.58 | 03-NOV-16:00 | 8.00 | 4.84 | 94301238.96 | 126.83 | 08-NOV-14:00 | 12.00 | 12.00 |
December | 0.188683E+11 | 7549.23 | 18-DEC-15:15 | 7.20 | 5.18 | 91880854.38 | 126.82 | 29-DEC-14:09 | 3.00 | 0.26 |
Annual Sum or Average | 0.137912E+12 | 0.114281E+10 | ||||||||
Minimum of Months | 0.323479E+10 | 2012.16 | 4.30 | 1.71 | 86396566.64 | 126.82 | 3.00 | 0.26 | ||
Maximum of Months | 0.197568E+11 | 8268.36 | 24.00 | 13.92 | 0.103238E+09 | 126.85 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145978E+10 | 1756.19 | 19-JAN-16:40 | 6.67 | 6.49 | 95227823.01 | 126.82 | 18-JAN-14:00 | 6.67 | 6.49 |
February | 0.602726E+10 | 3774.48 | 27-FEB-17:00 | 8.00 | 6.97 | 86396570.56 | 126.83 | 08-FEB-14:00 | 8.00 | 6.97 |
March | 0.119282E+11 | 6253.80 | 31-MAR-24:00 | 4.30 | 1.71 | 0.103236E+09 | 126.82 | 20-MAR-09:09 | 4.30 | 1.71 |
April | 0.173544E+11 | 7766.79 | 30-APR-17:53 | 24.00 | 13.13 | 91605084.11 | 126.82 | 28-APR-13:09 | 24.00 | 13.13 |
May | 0.333824E+10 | 3069.62 | 31-MAY-24:00 | 9.40 | 7.45 | 99234885.78 | 126.84 | 23-MAY-13:00 | 9.40 | 7.45 |
June | 0.839588E+10 | 4680.54 | 30-JUN-24:00 | 11.00 | 9.86 | 98962935.67 | 126.84 | 27-JUN-09:09 | 11.00 | 9.86 |
July | 0.136597E+11 | 6822.59 | 31-JUL-24:00 | 11.40 | 9.79 | 91885292.24 | 126.83 | 24-JUL-13:00 | 11.40 | 9.79 |
August | 0.184947E+11 | 7522.44 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103238E+09 | 126.83 | 08-AUG-13:50 | 17.83 | 13.92 |
September | 0.332007E+10 | 2842.37 | 30-SEP-23:40 | 7.63 | 5.74 | 91609563.11 | 126.84 | 12-SEP-13:00 | 7.63 | 5.74 |
October | 0.742206E+10 | 4348.47 | 31-OCT-24:00 | 6.60 | 4.32 | 95231951.27 | 126.83 | 10-OCT-13:00 | 6.60 | 4.32 |
November | 0.112553E+11 | 5345.08 | 03-NOV-16:00 | 8.00 | 4.84 | 94301132.65 | 126.83 | 08-NOV-14:00 | 12.00 | 12.00 |
December | 0.158014E+11 | 6865.04 | 21-DEC-15:20 | 7.67 | 6.81 | 91880862.58 | 126.82 | 29-DEC-14:09 | 3.00 | 0.26 |
Annual Sum or Average | 0.118457E+12 | 0.114281E+10 | ||||||||
Minimum of Months | 0.145978E+10 | 1756.19 | 4.30 | 1.71 | 86396570.56 | 126.82 | 3.00 | 0.26 | ||
Maximum of Months | 0.184947E+11 | 7766.79 | 24.00 | 13.92 | 0.103238E+09 | 126.84 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.453396E+09 | 1640.13 | 19-JAN-16:30 | 7.00 | 6.74 | 93991671.00 | 128.38 | 17-JAN-10:30 | 7.00 | 6.74 |
February | 0.426459E+10 | 3582.49 | 17-FEB-17:00 | 5.00 | 2.86 | 86396569.45 | 126.82 | 08-FEB-14:00 | 5.00 | 2.86 |
March | 0.104055E+11 | 5780.76 | 31-MAR-23:20 | 4.57 | 1.75 | 0.103236E+09 | 126.82 | 20-MAR-09:09 | 4.57 | 1.75 |
April | 0.165274E+11 | 7893.10 | 30-APR-17:58 | 24.00 | 13.13 | 91605087.59 | 126.82 | 28-APR-13:09 | 24.00 | 13.13 |
May | 0.259285E+10 | 2898.17 | 31-MAY-23:30 | 9.85 | 8.62 | 99235144.51 | 126.84 | 23-MAY-13:00 | 9.85 | 8.62 |
June | 0.801536E+10 | 4407.90 | 30-JUN-23:30 | 11.00 | 10.17 | 98962950.76 | 126.84 | 27-JUN-09:09 | 11.00 | 10.17 |
July | 0.133320E+11 | 6667.25 | 31-JUL-23:30 | 11.35 | 9.97 | 91885336.22 | 126.83 | 24-JUL-13:09 | 11.35 | 9.97 |
August | 0.181755E+11 | 7582.76 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103239E+09 | 126.83 | 08-AUG-13:50 | 17.83 | 13.92 |
September | 0.267701E+10 | 2297.72 | 30-SEP-23:20 | 7.67 | 5.77 | 91609501.75 | 126.84 | 12-SEP-13:00 | 7.67 | 5.77 |
October | 0.598252E+10 | 3813.95 | 31-OCT-23:20 | 6.67 | 4.17 | 95231883.26 | 126.83 | 13-OCT-13:00 | 6.67 | 4.17 |
November | 0.951261E+10 | 5259.59 | 10-NOV-16:20 | 9.67 | 7.83 | 94301140.25 | 126.83 | 08-NOV-14:00 | 9.67 | 7.83 |
December | 0.137351E+11 | 6633.65 | 21-DEC-15:20 | 7.67 | 6.81 | 91880865.47 | 126.82 | 29-DEC-14:09 | 3.00 | 0.26 |
Annual Sum or Average | 0.105674E+12 | 0.114157E+10 | ||||||||
Minimum of Months | 0.453396E+09 | 1640.13 | 4.57 | 1.75 | 86396569.45 | 126.82 | 3.00 | 0.26 | ||
Maximum of Months | 0.181755E+11 | 7893.10 | 24.00 | 13.92 | 0.103239E+09 | 128.38 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237801E+12 | 91991.58 | 19-JAN-17:00 | 6.00 | 6.00 | 0.206159E+10 | 2747.29 | 09-JAN-10:09 | 6.00 | 6.00 |
February | 0.435707E+12 | 183522.89 | 09-FEB-17:00 | 6.00 | 4.60 | 0.187035E+10 | 2745.81 | 17-FEB-14:09 | 6.00 | 3.06 |
March | 0.729168E+12 | 358866.16 | 31-MAR-24:00 | 4.30 | 1.71 | 0.223495E+10 | 2746.36 | 08-MAR-10:09 | 4.30 | 1.71 |
April | 0.944305E+12 | 369923.18 | 30-APR-19:53 | 17.00 | 12.41 | 0.198337E+10 | 2746.67 | 14-APR-13:09 | 17.00 | 12.41 |
May | 0.241127E+12 | 176088.32 | 31-MAY-24:00 | 9.40 | 7.45 | 0.214816E+10 | 2745.88 | 23-MAY-13:00 | 9.40 | 7.45 |
June | 0.470711E+12 | 267478.16 | 30-JUN-24:00 | 11.00 | 9.86 | 0.214228E+10 | 2745.91 | 27-JUN-09:09 | 11.00 | 9.86 |
July | 0.732478E+12 | 360192.42 | 31-JUL-24:00 | 11.40 | 9.79 | 0.198903E+10 | 2745.56 | 25-JUL-09:00 | 11.40 | 9.79 |
August | 0.977945E+12 | 368795.75 | 15-AUG-16:00 | 17.00 | 13.95 | 0.223727E+10 | 2843.76 | 14-AUG-13:00 | 17.00 | 13.95 |
September | 0.234801E+12 | 175583.31 | 30-SEP-24:00 | 7.60 | 5.71 | 0.198313E+10 | 2746.00 | 19-SEP-13:00 | 7.60 | 5.71 |
October | 0.485692E+12 | 267595.17 | 31-OCT-24:00 | 6.60 | 4.32 | 0.206150E+10 | 2745.64 | 13-OCT-13:00 | 6.60 | 4.32 |
November | 0.706929E+12 | 276173.92 | 10-NOV-17:00 | 7.00 | 6.47 | 0.204142E+10 | 2746.38 | 29-NOV-10:09 | 2.17 | 0.48 |
December | 0.974914E+12 | 367657.51 | 21-DEC-17:00 | 6.00 | 5.49 | 0.198924E+10 | 2747.72 | 04-DEC-10:00 | 6.00 | 5.49 |
Annual Sum or Average | 0.717158E+13 | 0.247423E+11 | ||||||||
Minimum of Months | 0.234801E+12 | 91991.58 | 4.30 | 1.71 | 0.187035E+10 | 2745.56 | 2.17 | 0.48 | ||
Maximum of Months | 0.977945E+12 | 369923.18 | 17.00 | 13.95 | 0.223727E+10 | 2843.76 | 17.00 | 13.95 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372307E+09 | 11849.38 | 24-JAN-05:05 | 6.00 |
February | 0.138549E+09 | 11779.08 | 06-FEB-04:04 | 2.17 |
March | 0.168996E+09 | 11820.62 | 09-MAR-05:05 | 6.67 |
April | 0.291195E+09 | 13937.88 | 18-APR-03:53 | 8.00 |
May | 0.294347E+09 | 11849.28 | 20-MAY-04:05 | 4.83 |
June | 0.212161E+09 | 13924.15 | 27-JUN-03:53 | 14.00 |
July | 0.370274E+09 | 15185.65 | 22-JUL-16:02 | 29.00 |
August | 0.300181E+09 | 13673.45 | 30-AUG-03:53 | 10.00 |
September | 0.323001E+09 | 13653.20 | 04-SEP-14:52 | 16.00 |
October | 0.380578E+09 | 12009.80 | 30-OCT-03:05 | 7.00 |
November | 0.351525E+09 | 13279.16 | 07-NOV-04:53 | 8.00 |
December | 0.269567E+09 | 11992.62 | 26-DEC-04:05 | 2.00 |
Annual Sum or Average | 0.347268E+10 | |||
Minimum of Months | 0.138549E+09 | 11779.08 | 2.00 | |
Maximum of Months | 0.380578E+09 | 15185.65 | 29.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139126E+10 | 72022.72 | 02-JAN-04:11 | 1.13 |
February | 0.644283E+09 | 65806.78 | 21-FEB-05:01 | 5.48 |
March | 0.222869E+09 | 63945.51 | 06-MAR-05:01 | 3.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 53669194.23 | 59133.76 | 23-OCT-05:03 | 3.17 |
November | 0.585668E+09 | 66172.59 | 20-NOV-05:11 | 0.33 |
December | 0.139006E+10 | 70106.61 | 26-DEC-04:11 | 2.00 |
Annual Sum or Average | 0.428781E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.33 | |
Maximum of Months | 0.139126E+10 | 72022.72 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 102120.74 | 605.01 | 12-JAN-06:03 | -2.0 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 102120.74 | |||
Minimum of Months | 0.00 | 0.00 | -2.0 | |
Maximum of Months | 102120.74 | 605.01 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2351588.01 | 3702.80 | 10-JAN-06:01 | -4.0 |
February | 115039.81 | 615.03 | 24-FEB-06:06 | -0.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 1092.92 | 9.11 | 30-NOV-06:06 | 4.00 |
December | 987988.04 | 3617.78 | 30-DEC-06:01 | -1.0 |
Annual Sum or Average | 3455708.78 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 2351588.01 | 3702.80 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13607618.54 | 7550.55 | 10-JAN-06:01 | -4.0 |
February | 500632.11 | 1029.28 | 17-FEB-06:02 | -3.1 |
March | 363284.56 | 2489.72 | 06-MAR-06:01 | 4.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 1075455.38 | 7232.43 | 27-NOV-06:01 | 4.00 |
December | 4832729.17 | 7221.49 | 26-DEC-06:03 | 1.92 |
Annual Sum or Average | 20379719.76 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 13607618.54 | 7550.55 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4641.19 | 54.15 | 11-JAN-06:06 | -2.9 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 4641.19 | |||
Minimum of Months | 0.00 | 0.00 | -2.9 | |
Maximum of Months | 4641.19 | 54.15 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.545669E+09 | 9545.97 | 02-JAN-05:01 | 1.00 |
February | 0.258041E+09 | 9102.76 | 13-FEB-05:01 | -1.0 |
March | 63409229.63 | 8677.08 | 04-MAR-06:02 | 3.00 |
April | 51943.99 | 346.29 | 01-APR-05:05 | 2.17 |
May | 818972.66 | 4678.05 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 12107811.90 | 7059.83 | 21-OCT-05:03 | 7.00 |
November | 0.239517E+09 | 9325.30 | 20-NOV-05:02 | 0.67 |
December | 0.835774E+09 | 9825.77 | 26-DEC-04:03 | 2.00 |
Annual Sum or Average | 0.195539E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.835774E+09 | 9825.77 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.337600E+09 | 11465.61 | 11-JAN-05:01 | -3.0 |
February | 0.161695E+09 | 10832.63 | 17-FEB-05:01 | -2.1 |
March | 47608330.46 | 10408.71 | 04-MAR-06:02 | 3.00 |
April | 174511.98 | 597.37 | 08-APR-05:06 | 0.00 |
May | 808607.20 | 5070.24 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 11273114.45 | 7178.85 | 28-OCT-05:02 | 7.00 |
November | 0.162714E+09 | 10948.51 | 29-NOV-05:01 | -0.2 |
December | 0.585967E+09 | 11810.64 | 26-DEC-05:01 | 1.98 |
Annual Sum or Average | 0.130784E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.0 | |
Maximum of Months | 0.585967E+09 | 11810.64 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245396E+09 | 16184.29 | 10-JAN-05:01 | -4.0 |
February | 96909663.77 | 15255.10 | 17-FEB-06:02 | -3.1 |
March | 36424625.98 | 15262.01 | 04-MAR-06:02 | 3.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 2159103.29 | 9049.41 | 05-MAY-05:03 | 6.00 |
June | 189386.98 | 946.93 | 08-JUN-05:03 | 6.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 5405622.04 | 8658.69 | 28-OCT-05:02 | 7.00 |
November | 0.129285E+09 | 15833.56 | 27-NOV-05:01 | 4.00 |
December | 0.565766E+09 | 16960.33 | 26-DEC-05:01 | 1.98 |
Annual Sum or Average | 0.108153E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.565766E+09 | 16960.33 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189534E+09 | 10291.05 | 11-JAN-05:01 | -3.0 |
February | 69681414.69 | 9307.62 | 17-FEB-06:02 | -3.1 |
March | 12702048.30 | 8573.67 | 04-MAR-06:02 | 3.00 |
April | 20199.54 | 134.66 | 11-APR-05:08 | 5.83 |
May | 909580.24 | 4563.64 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 2320425.93 | 3811.52 | 28-OCT-05:02 | 7.00 |
November | 91975172.91 | 9967.78 | 29-NOV-05:01 | -0.2 |
December | 0.323137E+09 | 10675.19 | 26-DEC-05:01 | 1.98 |
Annual Sum or Average | 0.690280E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.1 | |
Maximum of Months | 0.323137E+09 | 10675.19 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.322178E+10 | 11908.81 | 02-JAN-04:11 | 1.13 |
February | 0.220670E+10 | 11777.23 | 13-FEB-04:01 | -1.8 |
March | 0.124415E+10 | 11167.31 | 06-MAR-04:02 | 3.80 |
April | 0.187342E+09 | 9787.94 | 01-APR-04:02 | 2.67 |
May | 97144179.96 | 10219.74 | 05-MAY-04:02 | 5.17 |
June | 820738.55 | 3417.34 | 07-JUN-05:03 | 6.33 |
July | 132832.42 | 885.55 | 31-JUL-05:03 | 7.50 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 14076170.35 | 9466.93 | 18-SEP-05:03 | 12.00 |
October | 0.661326E+09 | 10837.06 | 23-OCT-04:01 | 3.00 |
November | 0.191837E+10 | 11927.90 | 27-NOV-04:01 | 4.83 |
December | 0.394346E+10 | 12083.94 | 26-DEC-04:11 | 2.00 |
Annual Sum or Average | 0.134953E+11 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 0.394346E+10 | 12083.94 | 12.00 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181700E+10 | 15688.36 | 02-JAN-04:11 | 1.13 |
February | 0.123137E+10 | 15201.84 | 27-FEB-04:01 | 6.00 |
March | 0.764317E+09 | 14391.53 | 06-MAR-04:02 | 3.80 |
April | 63454839.38 | 12119.32 | 03-APR-05:02 | 3.83 |
May | 43877488.70 | 13236.87 | 05-MAY-04:02 | 5.17 |
June | 255832.04 | 1703.61 | 07-JUN-05:03 | 6.33 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 1355425.31 | 3314.28 | 18-SEP-05:03 | 12.00 |
October | 0.385099E+09 | 13743.96 | 23-OCT-04:01 | 3.00 |
November | 0.113224E+10 | 15492.28 | 27-NOV-04:01 | 4.83 |
December | 0.244037E+10 | 15981.52 | 26-DEC-04:11 | 2.00 |
Annual Sum or Average | 0.787934E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.13 | |
Maximum of Months | 0.244037E+10 | 15981.52 | 12.00 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186402E+10 | 23474.30 | 02-JAN-04:11 | 1.13 |
February | 0.127614E+10 | 22796.27 | 27-FEB-04:01 | 6.00 |
March | 0.967336E+09 | 21059.61 | 27-MAR-04:01 | 1.33 |
April | 92416335.39 | 15460.02 | 03-APR-05:02 | 3.83 |
May | 0.121706E+09 | 19884.78 | 05-MAY-04:02 | 5.17 |
June | 4365290.93 | 8827.06 | 08-JUN-05:03 | 6.17 |
July | 25521.00 | 170.14 | 01-JUL-05:03 | 10.17 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 472399.84 | 2558.60 | 07-SEP-05:03 | 8.83 |
October | 0.403829E+09 | 19809.65 | 16-OCT-04:01 | 8.67 |
November | 0.122607E+10 | 23216.26 | 27-NOV-04:01 | 4.83 |
December | 0.292384E+10 | 23936.67 | 26-DEC-04:11 | 2.00 |
Annual Sum or Average | 0.888021E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.13 | |
Maximum of Months | 0.292384E+10 | 23936.67 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129382E+10 | 15976.18 | 02-JAN-04:11 | 1.13 |
February | 0.754688E+09 | 14805.40 | 27-FEB-04:01 | 6.00 |
March | 0.441432E+09 | 14013.91 | 13-MAR-04:01 | 2.18 |
April | 26719450.58 | 8743.38 | 01-APR-05:03 | 2.17 |
May | 42492281.75 | 13068.41 | 05-MAY-04:02 | 5.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 1710985.90 | 4622.54 | 07-SEP-05:03 | 8.83 |
October | 0.210609E+09 | 13080.78 | 30-OCT-04:01 | 7.00 |
November | 0.735632E+09 | 15295.78 | 27-NOV-04:01 | 4.83 |
December | 0.164576E+10 | 16186.05 | 26-DEC-04:11 | 2.00 |
Annual Sum or Average | 0.515287E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.13 | |
Maximum of Months | 0.164576E+10 | 16186.05 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81796724.08 | 10567.49 | 17-JAN-05:01 | 6.00 |
February | 69582769.00 | 11819.31 | 21-FEB-04:01 | 5.93 |
March | 67390431.39 | 11331.97 | 06-MAR-05:01 | 3.83 |
April | 0.125364E+09 | 11504.01 | 03-APR-03:02 | 4.67 |
May | 0.105484E+09 | 9437.91 | 08-MAY-03:02 | 8.05 |
June | 94871380.97 | 10079.14 | 19-JUN-03:02 | 11.00 |
July | 0.132132E+09 | 10947.21 | 03-JUL-03:02 | 9.83 |
August | 0.119642E+09 | 10468.06 | 31-AUG-03:02 | 12.00 |
September | 85861289.19 | 10311.14 | 01-SEP-03:02 | 12.92 |
October | 70263656.74 | 10460.24 | 16-OCT-03:02 | 8.17 |
November | 89119223.64 | 12352.87 | 27-NOV-04:01 | 4.83 |
December | 70043591.44 | 13229.44 | 18-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.111155E+10 | |||
Minimum of Months | 67390431.39 | 9437.91 | 0.83 | |
Maximum of Months | 0.132132E+09 | 13229.44 | 12.92 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.800426E+09 | 7178.81 | 24-JAN-06:02 | 6.00 |
February | 0.506956E+09 | 7847.59 | 08-FEB-06:02 | 6.00 |
March | 0.229367E+09 | 7230.65 | 09-MAR-06:03 | 7.15 |
April | 41531493.23 | 8824.14 | 30-APR-15:21 | 24.00 |
May | 67687651.91 | 7069.84 | 30-MAY-04:03 | 8.00 |
June | 55390645.57 | 6920.71 | 19-JUN-04:03 | 11.00 |
July | 64381756.61 | 7834.10 | 05-JUL-03:02 | 8.00 |
August | 58863137.46 | 6476.52 | 01-AUG-04:03 | 12.17 |
September | 72699332.80 | 7951.21 | 10-SEP-16:12 | 20.33 |
October | 0.109406E+09 | 7276.90 | 31-OCT-05:03 | 7.00 |
November | 0.321830E+09 | 7278.83 | 15-NOV-06:03 | 10.50 |
December | 0.942708E+09 | 4930.10 | 22-DEC-06:03 | 3.00 |
Annual Sum or Average | 0.327125E+10 | |||
Minimum of Months | 41531493.23 | 4930.10 | 3.00 | |
Maximum of Months | 0.942708E+09 | 8824.14 | 24.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.632081E+10 | 21104.00 | 09-JAN-06:13 | -2.0 |
February | 0.444194E+10 | 15432.85 | 13-FEB-06:03 | -1.0 |
March | 0.339723E+10 | 12188.48 | 06-MAR-06:13 | 4.00 |
April | 0.106161E+10 | 17185.86 | 28-APR-05:03 | 6.17 |
May | 0.788937E+09 | 17575.91 | 25-MAY-05:03 | 7.17 |
June | 0.234415E+09 | 17606.69 | 02-JUN-05:03 | 8.17 |
July | 0.176305E+09 | 18535.94 | 05-JUL-05:02 | 7.33 |
August | 0.245786E+09 | 16595.32 | 23-AUG-05:03 | 9.33 |
September | 0.598076E+09 | 16116.30 | 29-SEP-05:03 | 9.33 |
October | 0.227259E+10 | 9759.26 | 23-OCT-05:08 | 3.17 |
November | 0.439167E+10 | 17659.86 | 20-NOV-05:23 | 0.00 |
December | 0.766943E+10 | 19601.53 | 26-DEC-05:13 | 1.97 |
Annual Sum or Average | 0.315988E+11 | |||
Minimum of Months | 0.176305E+09 | 9759.26 | -2.0 | |
Maximum of Months | 0.766943E+10 | 21104.00 | 9.33 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30493054.58 | 357.89 | 01-JAN-08:35 | 4.33 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 30493054.58 | |||
Minimum of Months | 0.00 | 0.00 | 3.80 | |
Maximum of Months | 30493054.58 | 357.89 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.612364E+09 | 583.51 | 08-JAN-18:10 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 3107391.62 | 438.49 | 16-MAY-05:08 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 2061151.13 | 373.08 | 17-SEP-03:15 | 8.33 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.617532E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.612364E+09 | 583.51 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200626E+11 | 20994.62 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.181982E+11 | 20994.62 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.216246E+11 | 20994.62 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.193152E+11 | 20994.62 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.208436E+11 | 20994.62 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.207428E+11 | 20994.62 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.194159E+11 | 20994.62 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.216246E+11 | 20994.62 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.193152E+11 | 20994.62 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.200626E+11 | 20994.62 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.198274E+11 | 20994.62 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.194159E+11 | 20994.62 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.240449E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.181982E+11 | 20994.62 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.216246E+11 | 20994.62 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.175012E+10 | 2367.39 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.147912E+10 | 2262.51 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.167117E+10 | 2085.34 | 15-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.144984E+10 | 1857.94 | 10-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.153025E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.151013E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.142091E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.160477E+10 | 1619.92 | 22-AUG-07:30 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.147265E+10 | 1739.02 | 08-SEP-07:30 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.161601E+10 | 2357.84 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.171814E+10 | 2367.39 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.177495E+10 | 2367.39 | 01-DEC-15:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.189981E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.142091E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.177495E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.111044E+10 | 1525.64 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.945980E+09 | 1453.24 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107550E+10 | 1313.52 | 15-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.934516E+09 | 1146.89 | 10-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.987900E+09 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.975286E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.917678E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.103516E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.946263E+09 | 1041.97 | 08-SEP-07:30 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.103453E+10 | 1519.16 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.109318E+10 | 1525.64 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.112019E+10 | 1525.64 | 01-DEC-15:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.121766E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.917678E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.112019E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.170746E+10 | 2367.44 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.145857E+10 | 2257.66 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166414E+10 | 2072.48 | 15-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145184E+10 | 1849.63 | 10-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.153462E+10 | 1454.32 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.151439E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.142538E+10 | 1454.32 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.160752E+10 | 1606.29 | 22-AUG-07:30 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147056E+10 | 1701.83 | 08-SEP-07:30 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.160114E+10 | 2357.50 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.168134E+10 | 2367.44 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.172203E+10 | 2367.44 | 01-DEC-15:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.188390E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.142538E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.172203E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.111640E+10 | 1525.64 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.947689E+09 | 1459.11 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107731E+10 | 1358.43 | 15-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.935476E+09 | 1222.92 | 10-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.987778E+09 | 937.20 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.974259E+09 | 937.20 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.916976E+09 | 937.20 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103583E+10 | 1100.32 | 22-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.950723E+09 | 1234.82 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.104033E+10 | 1519.53 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.109693E+10 | 1525.64 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.112975E+10 | 1525.64 | 01-DEC-15:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.122094E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.916976E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.112975E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.175371E+10 | 2367.39 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.148156E+10 | 2265.66 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.167267E+10 | 2093.85 | 15-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.145023E+10 | 1873.12 | 10-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.153085E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.151052E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.142113E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.160475E+10 | 1641.87 | 22-AUG-07:30 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.147340E+10 | 1757.63 | 08-SEP-07:30 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.161827E+10 | 2358.13 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.172285E+10 | 2367.39 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.178011E+10 | 2367.39 | 01-DEC-15:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.190200E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.142113E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.178011E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.111114E+10 | 1525.64 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.946483E+09 | 1453.93 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107582E+10 | 1316.25 | 15-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.934670E+09 | 1152.04 | 10-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.988013E+09 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.975414E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.917785E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.103531E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.946416E+09 | 1047.62 | 08-SEP-07:30 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.103492E+10 | 1519.22 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.109389E+10 | 1525.64 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.112102E+10 | 1525.64 | 01-DEC-15:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.121809E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.917785E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.112102E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.170924E+10 | 2367.44 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.145986E+10 | 2261.04 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166502E+10 | 2081.57 | 15-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145227E+10 | 1865.12 | 10-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.153512E+10 | 1454.32 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.151483E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.142573E+10 | 1454.32 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.160798E+10 | 1628.67 | 22-AUG-07:30 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147131E+10 | 1721.85 | 08-SEP-07:30 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.160249E+10 | 2357.81 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.168406E+10 | 2367.44 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.172432E+10 | 2367.44 | 01-DEC-15:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.188522E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.142573E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.172432E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.111701E+10 | 1525.64 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.948168E+09 | 1459.62 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107770E+10 | 1359.72 | 15-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.935656E+09 | 1225.23 | 10-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.987901E+09 | 937.20 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.974393E+09 | 937.20 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.917085E+09 | 937.20 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103599E+10 | 1103.36 | 22-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.951021E+09 | 1236.84 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.104070E+10 | 1519.57 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.109779E+10 | 1525.64 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.113103E+10 | 1525.64 | 01-DEC-15:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.122144E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.917085E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.113103E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.175369E+10 | 2367.39 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.148154E+10 | 2265.55 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.167265E+10 | 2093.60 | 15-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.145023E+10 | 1872.65 | 10-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.153085E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.151052E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.142113E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.160474E+10 | 1641.18 | 22-AUG-07:30 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.147340E+10 | 1757.04 | 08-SEP-07:30 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.161842E+10 | 2358.11 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.172278E+10 | 2367.39 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.178006E+10 | 2367.39 | 01-DEC-15:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.190200E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.142113E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.178006E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.111114E+10 | 1525.64 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.946480E+09 | 1453.86 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107581E+10 | 1316.13 | 15-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.934671E+09 | 1151.80 | 10-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.988013E+09 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.975397E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.917802E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.103531E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.946450E+09 | 1047.35 | 08-SEP-07:30 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.103491E+10 | 1519.21 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.109389E+10 | 1525.64 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.112090E+10 | 1525.64 | 01-DEC-15:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.121808E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.917802E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.112090E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.170926E+10 | 2367.44 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.145986E+10 | 2260.94 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166500E+10 | 2081.32 | 15-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145229E+10 | 1864.64 | 10-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.153511E+10 | 1454.32 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.151482E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.142571E+10 | 1454.32 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.160798E+10 | 1627.98 | 22-AUG-07:30 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147132E+10 | 1721.27 | 08-SEP-07:30 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.160248E+10 | 2357.80 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.168404E+10 | 2367.44 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.172431E+10 | 2367.44 | 01-DEC-15:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.188522E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.142571E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.172431E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.111701E+10 | 1525.64 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.948164E+09 | 1459.55 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107769E+10 | 1359.56 | 15-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.935660E+09 | 1224.93 | 10-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.987903E+09 | 937.20 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.974375E+09 | 937.20 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.917087E+09 | 937.20 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103599E+10 | 1103.01 | 22-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.951031E+09 | 1236.70 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.104069E+10 | 1519.57 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.109777E+10 | 1525.64 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.113101E+10 | 1525.64 | 01-DEC-15:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.122144E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.917087E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.113101E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.565679E+10 | 5919.59 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.513113E+10 | 5919.59 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.609720E+10 | 5919.59 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.544605E+10 | 5919.59 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.587700E+10 | 5919.59 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.584858E+10 | 5919.59 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.547447E+10 | 5919.59 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.609720E+10 | 5919.59 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.544605E+10 | 5919.59 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.565679E+10 | 5919.59 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.559049E+10 | 5919.59 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.547447E+10 | 5919.59 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.677962E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.513113E+10 | 5919.59 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.609720E+10 | 5919.59 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.208436E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.207428E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.198274E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.240449E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.175012E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224838E+09 |
February | 0.136985E+10 | 0.147912E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316520E+09 |
March | 0.163685E+10 | 0.167117E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188318E+09 |
April | 0.145243E+10 | 0.144984E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234653E+09 |
May | 0.157338E+10 | 0.153025E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 | 0.557692E+09 |
June | 0.156900E+10 | 0.151013E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249727.21 | 0.429974E+09 |
July | 0.145680E+10 | 0.142091E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1208601.59 | 0.414547E+09 |
August | 0.163685E+10 | 0.160477E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161945.65 | 0.298445E+09 |
September | 0.145243E+10 | 0.147265E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313786E+09 |
October | 0.150991E+10 | 0.161601E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341563E+09 |
November | 0.149516E+10 | 0.171814E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422353E+09 |
December | 0.145680E+10 | 0.177495E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578382E+09 |
Annual Sum or Average | 0.181194E+11 | 0.189981E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1620277.97 | 0.432107E+10 |
Minimum of Months | 0.136985E+10 | 0.142091E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188318E+09 |
Maximum of Months | 0.163685E+10 | 0.177495E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1208601.59 | 0.578382E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.111044E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147842E+09 |
February | 0.882782E+09 | 0.945980E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205666E+09 |
March | 0.105485E+10 | 0.107550E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120268E+09 |
April | 0.936002E+09 | 0.934516E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.20 | 0.152510E+09 |
May | 0.101394E+10 | 0.987900E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 0.367224E+09 |
June | 0.101113E+10 | 0.975286E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167060.26 | 0.278242E+09 |
July | 0.938820E+09 | 0.917678E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 944276.43 | 0.264822E+09 |
August | 0.105485E+10 | 0.103516E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109121.30 | 0.187687E+09 |
September | 0.936002E+09 | 0.946263E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208598E+09 |
October | 0.973041E+09 | 0.103453E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220585E+09 |
November | 0.963541E+09 | 0.109318E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270038E+09 |
December | 0.938820E+09 | 0.112019E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369047E+09 |
Annual Sum or Average | 0.116768E+11 | 0.121766E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1220865.51 | 0.279253E+10 |
Minimum of Months | 0.882782E+09 | 0.917678E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120268E+09 |
Maximum of Months | 0.105485E+10 | 0.112019E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 944276.43 | 0.369047E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.170746E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222751E+09 |
February | 0.136988E+10 | 0.145857E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312525E+09 |
March | 0.163688E+10 | 0.166414E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181040E+09 |
April | 0.145246E+10 | 0.145184E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233833E+09 |
May | 0.157341E+10 | 0.153462E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 0.548530E+09 |
June | 0.156904E+10 | 0.151439E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249721.68 | 0.419577E+09 |
July | 0.145684E+10 | 0.142538E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1337860.24 | 0.403824E+09 |
August | 0.163688E+10 | 0.160752E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161944.59 | 0.296021E+09 |
September | 0.145246E+10 | 0.147056E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320599E+09 |
October | 0.150994E+10 | 0.160114E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339008E+09 |
November | 0.149520E+10 | 0.168134E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410946E+09 |
December | 0.145684E+10 | 0.172203E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553106E+09 |
Annual Sum or Average | 0.181198E+11 | 0.188390E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1749529.94 | 0.424176E+10 |
Minimum of Months | 0.136988E+10 | 0.142538E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181040E+09 |
Maximum of Months | 0.163688E+10 | 0.172203E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1337860.24 | 0.553106E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.111640E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154461E+09 |
February | 0.882782E+09 | 0.947689E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223334E+09 |
March | 0.105485E+10 | 0.107731E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133023E+09 |
April | 0.936002E+09 | 0.935476E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171570E+09 |
May | 0.101394E+10 | 0.987778E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 0.391357E+09 |
June | 0.101113E+10 | 0.974259E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166466.78 | 0.309759E+09 |
July | 0.938820E+09 | 0.916976E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 679870.43 | 0.305471E+09 |
August | 0.105485E+10 | 0.103583E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107936.41 | 0.222941E+09 |
September | 0.936002E+09 | 0.950723E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221248E+09 |
October | 0.973041E+09 | 0.104033E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242894E+09 |
November | 0.963541E+09 | 0.109693E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303289E+09 |
December | 0.938820E+09 | 0.112975E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420490E+09 |
Annual Sum or Average | 0.116768E+11 | 0.122094E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 954275.96 | 0.309984E+10 |
Minimum of Months | 0.882782E+09 | 0.916976E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133023E+09 |
Maximum of Months | 0.105485E+10 | 0.112975E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 679870.43 | 0.420490E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.175371E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459451E+09 |
February | 0.136985E+10 | 0.148156E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653407E+09 |
March | 0.163685E+10 | 0.167267E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391576E+09 |
April | 0.145243E+10 | 0.145023E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499509E+09 |
May | 0.157338E+10 | 0.153085E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121166E+10 |
June | 0.156900E+10 | 0.151052E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 546230.67 | 0.945462E+09 |
July | 0.145680E+10 | 0.142113E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2820708.33 | 0.898946E+09 |
August | 0.163685E+10 | 0.160475E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356975.01 | 0.649746E+09 |
September | 0.145243E+10 | 0.147340E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672751E+09 |
October | 0.150991E+10 | 0.161827E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703851E+09 |
November | 0.149516E+10 | 0.172285E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845654E+09 |
December | 0.145680E+10 | 0.178011E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114104E+10 |
Annual Sum or Average | 0.181194E+11 | 0.190200E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3723914.01 | 0.907305E+10 |
Minimum of Months | 0.136985E+10 | 0.142113E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391576E+09 |
Maximum of Months | 0.163685E+10 | 0.178011E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2820708.33 | 0.121166E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.111114E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308984E+09 |
February | 0.649041E+09 | 0.946483E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438666E+09 |
March | 0.773965E+09 | 0.107582E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258176E+09 |
April | 0.688021E+09 | 0.934670E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2564.30 | 0.342756E+09 |
May | 0.744847E+09 | 0.988013E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816228E+09 |
June | 0.742030E+09 | 0.975414E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 371729.92 | 0.627777E+09 |
July | 0.690839E+09 | 0.917785E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2146468.98 | 0.607581E+09 |
August | 0.773965E+09 | 0.103531E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 246683.00 | 0.438053E+09 |
September | 0.688021E+09 | 0.946416E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463424E+09 |
October | 0.715730E+09 | 0.103492E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470497E+09 |
November | 0.708685E+09 | 0.109389E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562992E+09 |
December | 0.690839E+09 | 0.112102E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760318E+09 |
Annual Sum or Average | 0.858171E+10 | 0.121809E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2767446.21 | 0.609545E+10 |
Minimum of Months | 0.649041E+09 | 0.917785E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258176E+09 |
Maximum of Months | 0.773965E+09 | 0.112102E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2146468.98 | 0.816228E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.170924E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494996E+09 |
February | 0.136988E+10 | 0.145986E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698873E+09 |
March | 0.163688E+10 | 0.166502E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399192E+09 |
April | 0.145246E+10 | 0.145227E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530727E+09 |
May | 0.157341E+10 | 0.153512E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123588E+10 |
June | 0.156904E+10 | 0.151483E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 547354.17 | 0.943147E+09 |
July | 0.145684E+10 | 0.142573E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3138736.94 | 0.913769E+09 |
August | 0.163688E+10 | 0.160798E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356973.23 | 0.681463E+09 |
September | 0.145246E+10 | 0.147131E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731353E+09 |
October | 0.150994E+10 | 0.160249E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755471E+09 |
November | 0.149520E+10 | 0.168406E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891199E+09 |
December | 0.145684E+10 | 0.172432E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118167E+10 |
Annual Sum or Average | 0.181198E+11 | 0.188522E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4043064.34 | 0.945774E+10 |
Minimum of Months | 0.136988E+10 | 0.142573E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399192E+09 |
Maximum of Months | 0.163688E+10 | 0.172432E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3138736.94 | 0.123588E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.111701E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315050E+09 |
February | 0.882782E+09 | 0.948168E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450930E+09 |
March | 0.105485E+10 | 0.107770E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261710E+09 |
April | 0.936002E+09 | 0.935656E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347315E+09 |
May | 0.101394E+10 | 0.987901E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842815E+09 |
June | 0.101113E+10 | 0.974393E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 364136.88 | 0.658824E+09 |
July | 0.938820E+09 | 0.917085E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1631172.17 | 0.639703E+09 |
August | 0.105485E+10 | 0.103599E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 237998.37 | 0.462344E+09 |
September | 0.936002E+09 | 0.951021E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465151E+09 |
October | 0.973041E+09 | 0.104070E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482484E+09 |
November | 0.963541E+09 | 0.109779E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575821E+09 |
December | 0.938820E+09 | 0.113103E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778803E+09 |
Annual Sum or Average | 0.116768E+11 | 0.122144E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2233307.42 | 0.628095E+10 |
Minimum of Months | 0.882782E+09 | 0.917085E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261710E+09 |
Maximum of Months | 0.105485E+10 | 0.113103E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1631172.17 | 0.842815E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.175369E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512057E+09 |
February | 0.136985E+10 | 0.148154E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727538E+09 |
March | 0.163685E+10 | 0.167265E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444008E+09 |
April | 0.145243E+10 | 0.145023E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573536E+09 |
May | 0.157338E+10 | 0.153085E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140716E+10 |
June | 0.156900E+10 | 0.151052E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 630074.45 | 0.112545E+10 |
July | 0.145680E+10 | 0.142113E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3182699.41 | 0.107022E+10 |
August | 0.163685E+10 | 0.160474E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 415511.94 | 0.774575E+09 |
September | 0.145243E+10 | 0.147340E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769988E+09 |
October | 0.150991E+10 | 0.161842E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777265E+09 |
November | 0.149516E+10 | 0.172278E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935592E+09 |
December | 0.145680E+10 | 0.178006E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128081E+10 |
Annual Sum or Average | 0.181194E+11 | 0.190200E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4228285.81 | 0.103982E+11 |
Minimum of Months | 0.136985E+10 | 0.142113E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444008E+09 |
Maximum of Months | 0.163685E+10 | 0.178006E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3182699.41 | 0.140716E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.111114E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344482E+09 |
February | 0.882782E+09 | 0.946480E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492184E+09 |
March | 0.105485E+10 | 0.107581E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297432E+09 |
April | 0.936002E+09 | 0.934671E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401903E+09 |
May | 0.101394E+10 | 0.988013E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966064E+09 |
June | 0.101113E+10 | 0.975397E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 420768.04 | 0.757503E+09 |
July | 0.938820E+09 | 0.917802E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2413518.59 | 0.737242E+09 |
August | 0.105485E+10 | 0.103531E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 279484.87 | 0.533090E+09 |
September | 0.936002E+09 | 0.946450E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546654E+09 |
October | 0.973041E+09 | 0.103491E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530158E+09 |
November | 0.963541E+09 | 0.109389E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629027E+09 |
December | 0.938820E+09 | 0.112090E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855544E+09 |
Annual Sum or Average | 0.116768E+11 | 0.121808E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3113771.51 | 0.709128E+10 |
Minimum of Months | 0.882782E+09 | 0.917802E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297432E+09 |
Maximum of Months | 0.105485E+10 | 0.112090E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2413518.59 | 0.966064E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.170926E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546869E+09 |
February | 0.136988E+10 | 0.145986E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785300E+09 |
March | 0.163688E+10 | 0.166500E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457433E+09 |
April | 0.145246E+10 | 0.145229E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621476E+09 |
May | 0.157341E+10 | 0.153511E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145624E+10 |
June | 0.156904E+10 | 0.151482E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 630132.28 | 0.112883E+10 |
July | 0.145684E+10 | 0.142571E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3627210.48 | 0.109691E+10 |
August | 0.163688E+10 | 0.160798E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 415514.90 | 0.823318E+09 |
September | 0.145246E+10 | 0.147132E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861873E+09 |
October | 0.150994E+10 | 0.160248E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858247E+09 |
November | 0.149520E+10 | 0.168404E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995115E+09 |
December | 0.145684E+10 | 0.172431E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131843E+10 |
Annual Sum or Average | 0.181198E+11 | 0.188522E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4672857.66 | 0.109500E+11 |
Minimum of Months | 0.136988E+10 | 0.142571E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457433E+09 |
Maximum of Months | 0.163688E+10 | 0.172431E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3627210.48 | 0.145624E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.111701E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355042E+09 |
February | 0.882782E+09 | 0.948164E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515045E+09 |
March | 0.105485E+10 | 0.107769E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304564E+09 |
April | 0.936002E+09 | 0.935660E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407699E+09 |
May | 0.101394E+10 | 0.987903E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999707E+09 |
June | 0.101113E+10 | 0.974375E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 420028.52 | 0.792705E+09 |
July | 0.938820E+09 | 0.917087E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1932424.82 | 0.771511E+09 |
August | 0.105485E+10 | 0.103599E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277024.72 | 0.557763E+09 |
September | 0.936002E+09 | 0.951031E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547386E+09 |
October | 0.973041E+09 | 0.104069E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552066E+09 |
November | 0.963541E+09 | 0.109777E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654360E+09 |
December | 0.938820E+09 | 0.113101E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883401E+09 |
Annual Sum or Average | 0.116768E+11 | 0.122144E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2629478.06 | 0.734125E+10 |
Minimum of Months | 0.882782E+09 | 0.917087E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304564E+09 |
Maximum of Months | 0.105485E+10 | 0.113101E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1932424.82 | 0.999707E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.565679E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.513113E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.609720E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.544605E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.587700E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.584858E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.547447E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.609720E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.544605E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.565679E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.559049E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.547447E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.677962E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.513113E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.609720E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477802E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670221E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389962E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489193E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116518E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294710.83 | 0.890707E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2067467.38 | 0.860515E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200903.59 | 0.631651E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667622E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721089E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.896952E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122420E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2563081.80 | 0.908510E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389962E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2067467.38 | 0.122420E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.798507E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114014E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661936E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841957E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203120E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552426.43 | 0.155352E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3870797.16 | 0.148800E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395025.03 | 0.109696E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116106E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123047E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149966E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201157E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4818248.61 | 0.155150E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661936E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3870797.16 | 0.203120E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788776E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114008E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695597E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929330E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223321E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175491.49 | 0.176193E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2610714.62 | 0.169249E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209518.96 | 0.123515E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124625E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124575E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147041E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197014E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2995725.07 | 0.164091E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695597E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2610714.62 | 0.223321E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 20994.62 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 20994.62 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 20994.62 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 20994.62 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 20994.62 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 20994.62 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 20994.62 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 20994.62 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 20994.62 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 20994.62 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 20994.62 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 20994.62 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2367.39 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 744.74 | 08-JAN-08:00 |
February | 2010.79 | 01-FEB-10:09 | 2262.51 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 674.01 | 08-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 2085.34 | 15-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 697.16 | 27-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1857.94 | 10-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 763.54 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 22-MAY-15:00 | 1096.85 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 13-JUN-15:30 | 761.04 | 05-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.51 | 22-JUL-17:10 | 731.06 | 30-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 1619.92 | 22-AUG-07:30 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 | 14-AUG-16:50 | 520.84 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1739.02 | 08-SEP-07:30 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 680.76 | 06-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 2357.84 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 857.86 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 912.83 | 25-NOV-04:53 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-15:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1328.05 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.84 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 58.51 | 1328.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 491.59 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.24 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 425.58 | 08-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 1313.52 | 15-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 443.25 | 27-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1146.89 | 10-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 | 30-APR-19:00 | 491.13 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 707.13 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.09 | 13-JUN-15:30 | 541.68 | 18-JUN-11:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.19 | 22-JUL-19:10 | 458.92 | 30-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.16 | 14-AUG-16:50 | 316.03 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 1041.97 | 08-SEP-07:30 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 448.01 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1519.16 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 538.68 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 579.02 | 25-NOV-04:53 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-15:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 831.29 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.03 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 61.19 | 831.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2367.44 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 724.88 | 08-JAN-08:00 |
February | 2010.83 | 01-FEB-10:09 | 2257.66 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 688.13 | 05-FEB-14:00 |
March | 2010.83 | 01-MAR-10:09 | 2072.48 | 15-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 660.24 | 27-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1849.63 | 10-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 731.28 | 23-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1454.32 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 22-MAY-15:00 | 1059.54 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 13-JUN-15:30 | 771.51 | 18-JUN-12:20 |
July | 2010.83 | 03-JUL-09:09 | 1454.32 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.47 | 22-JUL-19:10 | 726.83 | 30-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 1606.29 | 22-AUG-07:30 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 | 14-AUG-16:50 | 513.79 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1701.83 | 08-SEP-07:30 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 665.56 | 06-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 2357.50 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 831.34 | 20-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 851.62 | 25-NOV-04:53 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-15:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1265.50 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.79 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 80.47 | 1265.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 518.91 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1459.11 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 469.20 | 14-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1358.43 | 15-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 497.53 | 27-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1222.92 | 10-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 571.36 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 761.29 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.09 | 13-JUN-15:30 | 599.79 | 18-JUN-16:20 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.90 | 22-JUL-19:08 | 623.19 | 30-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 1100.32 | 22-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 | 14-AUG-16:50 | 395.77 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 1234.82 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 473.41 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1519.53 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 616.16 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 670.23 | 25-NOV-04:53 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-15:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 951.81 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.77 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 35.90 | 951.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2367.39 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1492.43 | 08-JAN-08:00 |
February | 2010.79 | 01-FEB-10:09 | 2265.66 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1450.20 | 08-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 2093.85 | 15-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1445.12 | 27-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1873.12 | 10-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1511.76 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 2321.77 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 13-JUN-15:40 | 1657.83 | 05-JUN-21:13 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.06 | 22-JUL-18:52 | 1463.90 | 11-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 1641.87 | 22-AUG-07:30 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.98 | 14-AUG-16:50 | 1112.92 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1757.63 | 08-SEP-07:30 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1423.85 | 06-SEP-03:55 |
October | 2010.79 | 02-OCT-09:09 | 2358.13 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1732.67 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1718.44 | 25-NOV-04:53 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-15:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2708.61 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.92 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 143.06 | 2708.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1525.64 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1000.63 | 08-JAN-08:00 |
February | 1239.33 | 01-FEB-08:09 | 1453.93 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 964.05 | 08-FEB-22:03 |
March | 1239.33 | 01-MAR-08:09 | 1316.25 | 15-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 960.79 | 27-MAR-21:03 |
April | 1239.33 | 03-APR-07:10 | 1152.04 | 10-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 | 30-APR-18:50 | 1013.44 | 23-APR-22:00 |
May | 1239.33 | 01-MAY-07:10 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1492.89 | 04-MAY-23:00 |
June | 1239.33 | 01-JUN-07:10 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 | 13-JUN-15:40 | 1248.00 | 18-JUN-10:00 |
July | 1239.33 | 03-JUL-07:10 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.84 | 22-JUL-19:10 | 988.82 | 11-JUL-02:00 |
August | 1239.33 | 01-AUG-07:10 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.68 | 14-AUG-18:00 | 702.53 | 18-AUG-03:00 |
September | 1239.33 | 01-SEP-07:10 | 1047.62 | 08-SEP-07:30 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 964.65 | 06-SEP-03:55 |
October | 1239.33 | 02-OCT-07:10 | 1519.22 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1120.47 | 20-OCT-22:00 |
November | 1239.33 | 01-NOV-07:10 | 1525.64 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1123.55 | 25-NOV-04:53 |
December | 1239.33 | 01-DEC-08:09 | 1525.64 | 01-DEC-15:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1751.12 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702.53 | |||||
Maximum of Months | 1239.33 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 141.84 | 1751.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2367.44 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1576.06 | 08-JAN-08:00 |
February | 2010.83 | 01-FEB-10:09 | 2261.04 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1536.80 | 05-FEB-14:00 |
March | 2010.83 | 01-MAR-10:09 | 2081.57 | 15-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1443.06 | 27-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1865.12 | 10-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1634.70 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 1454.32 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 2267.01 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 13-JUN-15:40 | 1832.27 | 18-JUN-15:55 |
July | 2010.83 | 03-JUL-09:09 | 1454.32 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.89 | 22-JUL-19:10 | 1556.42 | 30-JUL-18:40 |
August | 2010.83 | 01-AUG-09:09 | 1628.67 | 22-AUG-07:30 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.98 | 14-AUG-16:50 | 1117.70 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1721.85 | 08-SEP-07:30 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1460.65 | 06-SEP-03:55 |
October | 2010.83 | 02-OCT-09:09 | 2357.81 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1841.07 | 01-OCT-24:00 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1724.42 | 26-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-15:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2692.92 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1117.70 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 191.89 | 2692.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1023.20 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1459.62 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 970.29 | 08-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1359.72 | 15-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 963.87 | 27-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1225.23 | 10-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1031.71 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1532.02 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 | 13-JUN-15:40 | 1339.28 | 18-JUN-16:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.05 | 22-JUL-19:08 | 1310.09 | 30-JUL-18:40 |
August | 1295.83 | 01-AUG-09:09 | 1103.36 | 22-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.66 | 14-AUG-16:50 | 790.35 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 1236.84 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 963.46 | 06-SEP-03:55 |
October | 1295.83 | 02-OCT-09:09 | 1519.57 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1170.05 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1158.23 | 25-NOV-04:53 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-15:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1790.98 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 790.35 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 79.05 | 1790.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2367.39 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1650.75 | 10-JAN-05:52 |
February | 2010.79 | 01-FEB-10:09 | 2265.55 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1790.97 | 08-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 2093.60 | 15-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1780.15 | 27-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1872.65 | 10-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1625.29 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 2624.96 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 13-JUN-15:50 | 1979.76 | 05-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.41 | 22-JUL-17:01 | 1754.41 | 30-JUL-18:47 |
August | 2010.79 | 01-AUG-09:09 | 1641.18 | 22-AUG-07:30 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.92 | 14-AUG-16:50 | 1327.39 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1757.04 | 08-SEP-07:30 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1578.56 | 06-SEP-03:55 |
October | 2010.79 | 02-OCT-09:09 | 2358.11 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1962.19 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2133.20 | 25-NOV-05:09 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-15:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3141.15 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1327.39 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 158.41 | 3141.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1107.04 | 10-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 1453.86 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1192.88 | 08-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1316.13 | 15-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1186.26 | 27-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1151.80 | 10-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1093.72 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1714.57 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 | 13-JUN-15:50 | 1527.47 | 18-JUN-10:32 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.40 | 22-JUL-19:10 | 1217.83 | 30-JUL-18:47 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 | 14-AUG-16:50 | 830.57 | 22-AUG-02:00 |
September | 1295.83 | 01-SEP-09:09 | 1047.35 | 08-SEP-07:30 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1083.11 | 06-SEP-03:55 |
October | 1295.83 | 02-OCT-09:09 | 1519.21 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1290.50 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1437.73 | 25-NOV-05:04 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-15:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2046.45 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 830.57 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 154.40 | 2046.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2367.44 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1665.14 | 10-JAN-05:52 |
February | 2010.83 | 01-FEB-10:09 | 2260.94 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1796.60 | 08-FEB-22:03 |
March | 2010.83 | 01-MAR-10:09 | 2081.32 | 15-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1780.75 | 27-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1864.64 | 10-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1829.07 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 1454.32 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 2595.45 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 13-JUN-15:50 | 2223.77 | 18-JUN-15:55 |
July | 2010.83 | 03-JUL-09:09 | 1454.32 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.68 | 22-JUL-19:10 | 1974.29 | 30-JUL-18:47 |
August | 2010.83 | 01-AUG-09:09 | 1627.98 | 22-AUG-07:30 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.92 | 14-AUG-16:50 | 1342.58 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1721.27 | 08-SEP-07:30 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1635.48 | 06-SEP-03:55 |
October | 2010.83 | 02-OCT-09:09 | 2357.80 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2042.53 | 01-OCT-24:00 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2162.28 | 25-NOV-05:04 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-15:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3144.70 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.58 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 219.68 | 3144.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1110.66 | 10-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 1459.55 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1200.14 | 08-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1359.56 | 15-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1191.13 | 27-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1224.93 | 10-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1134.57 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1764.25 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 | 13-JUN-15:50 | 1636.67 | 18-JUN-16:10 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.45 | 22-JUL-19:08 | 1660.49 | 30-JUL-18:47 |
August | 1295.83 | 01-AUG-09:09 | 1103.01 | 22-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 | 14-AUG-16:50 | 950.88 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 1236.70 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1082.43 | 06-SEP-03:55 |
October | 1295.83 | 02-OCT-09:09 | 1519.57 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1359.52 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1422.20 | 25-NOV-05:07 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-15:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2109.54 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.88 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 94.45 | 2109.54 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5919.59 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5919.59 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5919.59 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5919.59 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5919.59 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5919.59 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5919.59 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5919.59 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5919.59 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5919.59 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5919.59 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5919.59 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1619.86 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1442.58 | 08-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1457.35 | 27-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1594.32 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 2347.22 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.58 | 13-JUN-16:00 | 1578.40 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.31 | 22-JUL-18:52 | 1456.44 | 30-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.38 | 14-AUG-17:00 | 1079.76 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1463.93 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1801.44 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1948.34 | 25-NOV-04:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2868.82 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1079.76 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.31 | 2868.82 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2742.74 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2481.49 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2451.97 | 27-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2684.57 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 4090.47 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.64 | 13-JUN-16:00 | 2741.93 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.38 | 22-JUL-18:52 | 2426.24 | 11-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.62 | 14-AUG-17:00 | 1889.38 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2529.45 | 06-SEP-03:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3060.59 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3176.07 | 25-NOV-04:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4777.71 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1889.38 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.38 | 4777.71 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2435.08 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2690.59 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2639.82 | 27-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2625.13 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 4216.90 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.31 | 13-JUN-17:00 | 3335.85 | 18-JUN-15:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.86 | 22-JUL-18:52 | 2956.74 | 30-JUL-18:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.94 | 14-AUG-18:00 | 2054.81 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2493.10 | 06-SEP-03:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3118.10 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3049.34 | 25-NOV-05:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5092.16 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2054.81 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.86 | 5092.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 113401.85 | 02-JAN-04:11 | 0.00 | 9331.40 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 114403.93 | 21-FEB-04:01 | 0.00 | 9331.40 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 111717.34 | 27-MAR-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 113102.86 | 10-APR-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 111457.41 | 30-MAY-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 112666.31 | 12-JUN-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 112051.91 | 03-JUL-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 112438.50 | 28-AUG-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 113036.51 | 05-SEP-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 112341.60 | 16-OCT-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 113365.04 | 27-NOV-04:01 | 0.00 | 9331.40 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 112071.36 | 04-DEC-04:01 | 0.00 | 8164.98 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 111457.41 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 114403.93 | 0.00 | 9331.40 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 88689.19 | 02-JAN-05:01 | 0.00 | 14665.45 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 88324.76 | 21-FEB-04:01 | 0.00 | 8380.26 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90705.28 | 27-MAR-04:01 | 0.00 | 16760.51 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95138.46 | 24-APR-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 91904.61 | 01-MAY-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92767.64 | 05-JUN-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 95206.23 | 05-JUL-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 91890.00 | 28-AUG-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92573.41 | 05-SEP-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95619.44 | 10-OCT-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 93192.86 | 13-NOV-04:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 88558.18 | 18-DEC-05:01 | 0.00 | 14665.45 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 88324.76 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95619.44 | 0.00 | 16760.51 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 72443.43 | 26-JAN-06:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 71446.14 | 10-FEB-06:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 74769.50 | 24-MAR-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79618.57 | 13-APR-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80511.85 | 31-MAY-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80991.89 | 27-JUN-04:03 | 0.00 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81207.43 | 25-JUL-04:03 | 0.00 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80901.46 | 15-AUG-04:02 | 0.00 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81104.15 | 14-SEP-04:02 | 0.00 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80251.88 | 05-OCT-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 73116.81 | 01-NOV-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 43866.58 | 22-DEC-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 43866.58 | 0.00 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81207.43 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 23716.07 | 19-JAN-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22882.94 | 09-FEB-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27611.94 | 31-MAR-16:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 69540.28 | 21-APR-05:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71837.15 | 23-MAY-05:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76020.21 | 26-JUN-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76776.69 | 25-JUL-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75718.62 | 17-AUG-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72946.73 | 13-SEP-05:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35233.41 | 05-OCT-16:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27518.79 | 10-NOV-16:40 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19207.07 | 21-DEC-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19207.07 | 6448.95 | 8380.26 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76776.69 | 15316.26 | 18854.65 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2968.93 | 18-JAN-06:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3155.41 | 21-FEB-14:10 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.44 |
March | 4805.88 | 20-MAR-12:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.93 |
April | 6848.68 | 28-APR-14:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 |
May | 6892.98 | 22-MAY-15:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 0.00 |
June | 11361.11 | 26-JUN-05:02 | 1012.16 | 807.98 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.92 |
July | 11052.39 | 24-JUL-05:03 | 809.73 | 941.26 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.04 |
August | 8994.84 | 07-AUG-05:03 | 809.73 | 1028.35 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.14 |
September | 6397.39 | 13-SEP-15:10 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 |
October | 5431.71 | 10-OCT-13:10 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 |
November | 3681.25 | 08-NOV-14:30 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 |
December | 2945.82 | 11-DEC-05:02 | 0.00 | 2367.51 | 9105.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2945.82 | 0.00 | 807.98 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11361.11 | 2010.79 | 2367.51 | 9105.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 79.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3862.07 | 18-JAN-06:02 | 652.28 | 847.62 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4330.11 | 17-FEB-09:45 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4015.50 | 20-MAR-03:02 | 0.00 | 423.81 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.99 |
April | 20081.15 | 30-APR-08:52 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.06 |
May | 19538.56 | 21-MAY-08:22 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.62 |
June | 19329.64 | 25-JUN-09:52 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18136.05 | 23-JUL-08:12 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.93 |
August | 15268.71 | 20-AUG-10:13 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.75 |
September | 13817.55 | 24-SEP-09:23 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.71 |
October | 7279.91 | 01-OCT-08:55 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4085.46 | 13-NOV-04:02 | 0.00 | 423.81 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3680.09 | 11-DEC-05:02 | 0.00 | 1525.71 | 5867.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3680.09 | 0.00 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20081.15 | 2478.65 | 1874.40 | 5867.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12726.29 | 20-JAN-12:00 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14332.79 | 17-FEB-13:30 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.17 |
March | 9916.16 | 28-MAR-12:10 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.35 |
April | 29943.27 | 30-APR-12:52 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.37 |
May | 14427.84 | 22-MAY-13:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 |
June | 14406.95 | 11-JUN-14:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.23 |
July | 18182.01 | 16-JUL-14:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.19 |
August | 18331.84 | 06-AUG-13:13 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.30 |
September | 28364.31 | 24-SEP-14:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.67 |
October | 17352.12 | 03-OCT-13:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.78 |
November | 22483.75 | 11-NOV-13:13 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.51 |
December | 12686.85 | 18-DEC-13:30 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9916.16 | 404.87 | 323.20 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29943.27 | 2010.83 | 1454.32 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6637.49 | 30-JAN-16:30 | 3717.98 | 2811.59 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8936.44 | 27-FEB-16:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9662.37 | 23-MAR-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.98 |
April | 25108.19 | 30-APR-16:11 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.18 |
May | 21077.57 | 21-MAY-15:02 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.19 |
June | 26524.46 | 25-JUN-16:41 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.93 |
July | 25377.00 | 09-JUL-15:02 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.16 |
August | 24802.22 | 20-AUG-16:12 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.43 |
September | 23249.96 | 24-SEP-16:02 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.35 |
October | 10451.94 | 03-OCT-15:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.09 |
November | 7519.27 | 09-NOV-06:03 | 521.82 | 678.09 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6785.91 | 18-DEC-14:30 | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6637.49 | 326.14 | 260.35 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26524.46 | 3717.98 | 2811.59 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2193.18 | 26-JAN-06:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2010.93 | 08-FEB-16:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.19 |
March | 2297.94 | 24-MAR-05:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5271.30 | 28-APR-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 |
May | 5602.45 | 23-MAY-14:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.94 |
June | 7334.43 | 13-JUN-16:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 40.25 | 0.00 |
July | 7074.92 | 10-JUL-15:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 |
August | 6178.24 | 10-AUG-15:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.63 |
September | 5587.59 | 13-SEP-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 |
October | 3042.69 | 11-OCT-15:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.14 |
November | 2432.26 | 09-NOV-06:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1859.71 | 21-DEC-16:10 | 1923.11 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1859.71 | 809.73 | 1052.22 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7334.43 | 2010.79 | 2367.39 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 40.25 | 183.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3062.91 | 20-JAN-10:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3272.23 | 17-FEB-10:00 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3259.28 | 24-MAR-05:02 | 652.28 | 847.62 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20743.60 | 30-APR-09:22 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.71 |
May | 11560.43 | 23-MAY-09:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.69 |
June | 14967.44 | 11-JUN-09:43 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.93 |
July | 20105.65 | 23-JUL-08:52 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.68 |
August | 18226.34 | 20-AUG-10:13 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.55 |
September | 14487.34 | 04-SEP-09:32 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.36 |
October | 5730.59 | 04-OCT-10:10 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 |
November | 3424.04 | 09-NOV-06:03 | 521.82 | 678.09 | 2607.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2641.55 | 06-DEC-10:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2641.55 | 260.91 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20743.60 | 2478.65 | 1874.40 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12135.21 | 20-JAN-12:00 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15186.24 | 17-FEB-13:40 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.98 |
March | 8262.84 | 28-MAR-12:10 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.32 |
April | 30708.06 | 30-APR-12:42 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.71 |
May | 14420.58 | 22-MAY-13:20 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 |
June | 13840.02 | 13-JUN-13:20 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 0.00 |
July | 14362.05 | 31-JUL-13:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.85 |
August | 26355.84 | 13-AUG-14:52 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.47 |
September | 29353.97 | 10-SEP-12:12 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.81 |
October | 25615.49 | 01-OCT-12:43 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 761.97 |
November | 12382.06 | 03-NOV-12:40 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.92 |
December | 10752.22 | 18-DEC-13:30 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8262.84 | 404.87 | 323.20 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30708.06 | 2010.83 | 1454.32 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 761.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3613.92 | 19-JAN-15:50 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5585.74 | 27-FEB-16:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5559.01 | 23-MAR-17:00 | 391.37 | 520.67 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.29 |
April | 22021.53 | 30-APR-17:21 | 0.00 | 468.62 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 |
May | 22432.17 | 21-MAY-16:52 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.31 |
June | 21191.67 | 11-JUN-16:42 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.00 |
July | 22216.14 | 09-JUL-16:51 | 587.05 | 468.62 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.29 |
August | 22307.54 | 13-AUG-16:52 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.08 |
September | 17951.83 | 10-SEP-16:12 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.46 |
October | 7885.44 | 03-OCT-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.69 |
November | 3796.60 | 09-NOV-06:03 | 521.82 | 678.09 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3042.51 | 21-DEC-14:40 | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3042.51 | 0.00 | 260.35 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22432.17 | 1295.83 | 937.20 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1916.21 | 19-JAN-16:10 | 1923.11 | 1942.84 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1799.03 | 09-FEB-16:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.45 |
March | 2145.36 | 30-MAR-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.62 |
April | 5462.43 | 28-APR-15:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.66 |
May | 6156.21 | 22-MAY-15:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 |
June | 8173.51 | 13-JUN-16:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 47.70 | 0.00 |
July | 7778.77 | 10-JUL-15:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 |
August | 6638.20 | 14-AUG-16:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 32.87 | 0.00 |
September | 5701.43 | 13-SEP-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 |
October | 2378.10 | 06-OCT-16:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.99 |
November | 2029.07 | 10-NOV-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.47 |
December | 1674.42 | 21-DEC-16:20 | 1923.11 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1674.42 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8173.51 | 1923.11 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 47.70 | 276.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2645.97 | 20-JAN-10:30 | 2591.66 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2783.74 | 24-FEB-10:30 | 2591.66 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.64 |
March | 2779.80 | 30-MAR-10:40 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.01 |
April | 18562.24 | 30-APR-10:23 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.33 |
May | 11668.40 | 21-MAY-09:02 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.82 |
June | 19638.18 | 25-JUN-10:02 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.56 |
July | 19876.34 | 16-JUL-09:12 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.92 |
August | 18561.23 | 20-AUG-08:42 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.22 |
September | 9569.80 | 12-SEP-09:30 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.54 |
October | 4424.72 | 04-OCT-10:00 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2549.85 | 10-NOV-15:00 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.10 |
December | 2258.65 | 06-DEC-06:05 | 782.73 | 1017.14 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2258.65 | 260.91 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19876.34 | 2591.66 | 1874.40 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9465.30 | 20-JAN-12:00 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13025.66 | 17-FEB-14:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.87 |
March | 6119.00 | 10-MAR-14:40 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.31 |
April | 29665.34 | 30-APR-13:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.80 |
May | 14999.09 | 22-MAY-13:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 |
June | 14645.82 | 13-JUN-13:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 0.00 |
July | 15604.81 | 23-JUL-13:32 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.89 |
August | 24910.92 | 06-AUG-13:42 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.74 |
September | 30339.12 | 10-SEP-14:52 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.19 |
October | 17359.68 | 03-OCT-13:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.30 |
November | 10008.23 | 03-NOV-12:50 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.56 |
December | 7288.14 | 18-DEC-13:40 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6119.00 | 404.87 | 323.20 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30339.12 | 2010.83 | 1454.32 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 584.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3541.36 | 19-JAN-15:50 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4401.27 | 27-FEB-16:40 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4773.02 | 23-MAR-17:00 | 391.37 | 520.67 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.99 |
April | 22016.34 | 30-APR-17:02 | 0.00 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.98 |
May | 18379.95 | 21-MAY-17:02 | 0.00 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.67 |
June | 21635.03 | 25-JUN-17:32 | 0.00 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 |
July | 22486.64 | 23-JUL-16:52 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.88 |
August | 22631.69 | 20-AUG-16:41 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.66 |
September | 15998.42 | 10-SEP-16:12 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.79 |
October | 7342.29 | 03-OCT-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.99 |
November | 3577.07 | 10-NOV-15:40 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.12 |
December | 2898.68 | 21-DEC-14:40 | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2898.68 | 0.00 | 260.35 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22631.69 | 1295.83 | 937.20 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5542.13 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5318.07 | 24-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.62 |
March | 5810.72 | 25-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8095.67 | 10-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8564.48 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.70 |
June | 8777.37 | 05-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10769.22 | 24-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.50 |
August | 10229.34 | 21-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.72 |
September | 7912.78 | 14-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8978.40 | 10-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6544.15 | 13-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.31 |
December | 4507.40 | 27-DEC-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4507.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10769.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3980.94 | 10-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1265.28 |
February | 5251.94 | 18-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.40 |
March | 3720.26 | 11-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.89 |
April | 5562.45 | 22-APR-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5597.15 | 25-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.27 |
June | 5931.01 | 27-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.17 |
July | 6966.82 | 24-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.78 |
August | 6463.39 | 17-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.05 |
September | 6206.39 | 14-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5937.31 | 06-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.14 |
November | 4730.69 | 17-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.44 |
December | 5007.40 | 30-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1978.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3720.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6966.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1978.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 809.53 | 19-JAN-17:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1090.65 | 22-FEB-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.95 |
March | 3293.38 | 25-MAR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.12 |
April | 13665.58 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.85 |
May | 14471.32 | 22-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.44 |
June | 16784.90 | 13-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 |
July | 16368.62 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 0.00 |
August | 14379.29 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.28 |
September | 12259.74 | 12-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.92 |
October | 5105.34 | 03-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.02 |
November | 1024.14 | 10-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.22 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 607.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16784.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 607.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2012.16 | 19-JAN-16:20 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4177.31 | 27-FEB-17:00 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7038.06 | 31-MAR-24:00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8268.36 | 30-APR-17:44 | 0.00 | 144.69 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3390.21 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5216.82 | 30-JUN-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7292.04 | 31-JUL-24:00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8128.84 | 13-AUG-18:10 | 0.00 | 144.69 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3272.16 | 30-SEP-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5093.00 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5813.58 | 03-NOV-16:00 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7549.23 | 18-DEC-15:15 | 444.28 | 1041.69 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2012.16 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8268.36 | 444.28 | 1041.69 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1756.19 | 19-JAN-16:40 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3774.48 | 27-FEB-17:00 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6253.80 | 31-MAR-24:00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7766.79 | 30-APR-17:53 | 0.00 | 173.63 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3069.62 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4680.54 | 30-JUN-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6822.59 | 31-JUL-24:00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7522.44 | 13-AUG-18:10 | 0.00 | 144.69 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2842.37 | 30-SEP-23:40 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4348.47 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5345.08 | 03-NOV-16:00 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6865.04 | 21-DEC-15:20 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1756.19 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7766.79 | 222.14 | 520.85 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1640.13 | 19-JAN-16:30 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3582.49 | 17-FEB-17:00 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5780.76 | 31-MAR-23:20 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7893.10 | 30-APR-17:58 | 0.00 | 173.63 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2898.17 | 31-MAY-23:30 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4407.90 | 30-JUN-23:30 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6667.25 | 31-JUL-23:30 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7582.76 | 13-AUG-18:10 | 0.00 | 144.69 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2297.72 | 30-SEP-23:20 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3813.95 | 31-OCT-23:20 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5259.59 | 10-NOV-16:20 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6633.65 | 21-DEC-15:20 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1640.13 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7893.10 | 222.14 | 520.85 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91991.58 | 19-JAN-17:00 | 4808.68 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183522.89 | 09-FEB-17:00 | 4808.68 | 5919.59 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358866.16 | 31-MAR-24:00 | 0.00 | 328.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369923.18 | 30-APR-19:53 | 0.00 | 1315.53 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176088.32 | 31-MAY-24:00 | 0.00 | 328.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267478.16 | 30-JUN-24:00 | 0.00 | 328.88 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360192.42 | 31-JUL-24:00 | 0.00 | 328.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 368795.75 | 15-AUG-16:00 | 4808.68 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175583.31 | 30-SEP-24:00 | 0.00 | 328.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267595.17 | 31-OCT-24:00 | 0.00 | 328.88 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276173.92 | 10-NOV-17:00 | 4808.68 | 5919.59 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367657.51 | 21-DEC-17:00 | 4808.68 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91991.58 | 0.00 | 328.88 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369923.18 | 4808.68 | 5919.59 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.165775E+13 | 1113825.10 | 02-JAN-08:09 | 0.343516E+12 | 768728.48 | 10-JAN-07:00 |
February | 0.184764E+13 | 1174987.93 | 02-FEB-16:00 | 0.241838E+12 | 661248.78 | 17-FEB-07:10 |
March | 0.248412E+13 | 1332154.61 | 20-MAR-07:00 | 0.196235E+12 | 462627.20 | 27-MAR-06:10 |
April | 0.279360E+13 | 1755216.61 | 28-APR-14:00 | 0.771373E+11 | 320210.62 | 08-APR-06:10 |
May | 0.169919E+13 | 1341869.34 | 22-MAY-15:09 | 0.720612E+11 | 282204.05 | 05-MAY-05:10 |
June | 0.213383E+13 | 1599597.02 | 13-JUN-15:30 | 0.622482E+11 | 79848.85 | 01-JUN-11:50 |
July | 0.260693E+13 | 1712532.73 | 21-JUL-15:39 | 0.593930E+11 | 78843.03 | 05-JUL-11:30 |
August | 0.310164E+13 | 1838139.92 | 14-AUG-15:39 | 0.630139E+11 | 78376.56 | 31-AUG-11:00 |
September | 0.171810E+13 | 1366050.96 | 13-SEP-15:20 | 0.600885E+11 | 128636.24 | 21-SEP-06:10 |
October | 0.207901E+13 | 1300254.57 | 06-OCT-15:20 | 0.104194E+12 | 330558.14 | 23-OCT-06:40 |
November | 0.239235E+13 | 1403481.83 | 16-NOV-16:40 | 0.205595E+12 | 590475.17 | 29-NOV-07:10 |
December | 0.282915E+13 | 1544836.54 | 21-DEC-16:19 | 0.375030E+12 | 644942.88 | 26-DEC-05:10 |
Annual Sum or Average | 0.273433E+14 | 0.186035E+13 | ||||
Minimum of Months | 0.165775E+13 | 1113825.10 | 0.593930E+11 | 78376.56 | ||
Maximum of Months | 0.310164E+13 | 1838139.92 | 0.375030E+12 | 768728.48 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.316190E+12 | 0.775529E+11 | 0.811612E+12 | 0.164873E+12 | 0.173488E+12 | 0.122975E+11 | 0.00 | 0.883997E+11 | 0.122302E+11 | 0.110358E+10 | 0.00 | 0.00 | 0.00 |
February | 0.282895E+12 | 0.625652E+11 | 0.102011E+13 | 0.148926E+12 | 0.158712E+12 | 0.135305E+11 | 0.00 | 0.142219E+12 | 0.179720E+11 | 0.716431E+09 | 0.00 | 0.00 | 0.00 |
March | 0.333095E+12 | 0.590027E+11 | 0.146267E+13 | 0.165150E+12 | 0.181106E+12 | 0.141820E+11 | 0.00 | 0.221860E+12 | 0.461330E+11 | 0.923566E+09 | 0.00 | 0.00 | 0.00 |
April | 0.295941E+12 | 0.467258E+11 | 0.170311E+13 | 0.159524E+12 | 0.199001E+12 | 0.167415E+11 | 0.00 | 0.286338E+12 | 0.856048E+11 | 0.615723E+09 | 0.00 | 0.00 | 0.00 |
May | 0.318055E+12 | 0.402007E+11 | 0.820521E+12 | 0.165009E+12 | 0.204757E+12 | 0.170227E+11 | 0.00 | 0.104232E+12 | 0.292965E+11 | 93452653.78 | 0.00 | 0.00 | 0.00 |
June | 0.316009E+12 | 0.349097E+11 | 0.110677E+13 | 0.159786E+12 | 0.215961E+12 | 0.281553E+11 | 0.00 | 0.188269E+12 | 0.839692E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.296093E+12 | 0.375553E+11 | 0.143888E+13 | 0.164745E+12 | 0.225599E+12 | 0.422406E+11 | 0.00 | 0.283113E+12 | 0.118706E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.330612E+12 | 0.443040E+11 | 0.177780E+13 | 0.165149E+12 | 0.238545E+12 | 0.489253E+11 | 0.00 | 0.367094E+12 | 0.129211E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.296772E+12 | 0.525940E+11 | 0.784732E+12 | 0.159522E+12 | 0.209941E+12 | 0.327054E+11 | 0.00 | 0.124360E+12 | 0.574461E+11 | 27902124.52 | 0.00 | 0.00 | 0.00 |
October | 0.311456E+12 | 0.650013E+11 | 0.112899E+13 | 0.164871E+12 | 0.187357E+12 | 0.125918E+11 | 0.00 | 0.161448E+12 | 0.471802E+11 | 0.110805E+09 | 0.00 | 0.00 | 0.00 |
November | 0.312172E+12 | 0.722201E+11 | 0.140306E+13 | 0.159636E+12 | 0.171096E+12 | 0.108906E+11 | 0.00 | 0.213015E+12 | 0.498417E+11 | 0.420839E+09 | 0.00 | 0.00 | 0.00 |
December | 0.308981E+12 | 0.800632E+11 | 0.175516E+13 | 0.164751E+12 | 0.172054E+12 | 0.129237E+11 | 0.00 | 0.279289E+12 | 0.548449E+11 | 0.108321E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371827E+13 | 0.672695E+12 | 0.152134E+14 | 0.194194E+13 | 0.233762E+13 | 0.262207E+12 | 0.00 | 0.245964E+13 | 0.732436E+12 | 0.509551E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.282895E+12 | 0.349097E+11 | 0.784732E+12 | 0.148926E+12 | 0.158712E+12 | 0.108906E+11 | 0.00 | 0.883997E+11 | 0.122302E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.333095E+12 | 0.800632E+11 | 0.177780E+13 | 0.165150E+12 | 0.238545E+12 | 0.489253E+11 | 0.00 | 0.367094E+12 | 0.129211E+12 | 0.110358E+10 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.278799E+12 | 0.00 | 0.647167E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.182815E+12 | 0.00 | 0.590229E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.128187E+12 | 0.00 | 0.680476E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.153303E+11 | 0.00 | 0.618070E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.789860E+10 | 0.00 | 0.641626E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.320641E+09 | 0.00 | 0.619275E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.115833E+09 | 0.00 | 0.592771E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 38137560.56 | 0.00 | 0.629757E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.164760E+10 | 0.00 | 0.584409E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.429355E+11 | 0.00 | 0.612587E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.144475E+12 | 0.00 | 0.611197E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.312363E+12 | 0.00 | 0.626666E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.111493E+13 | 0.00 | 0.745423E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 38137560.56 | 0.00 | 0.584409E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.312363E+12 | 0.00 | 0.680476E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 352853.36 | 02-JAN-08:09 | 54335.80 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 118959.22 | 02-JAN-08:20 | 114634.34 | 20-JAN-11:00 | 31738.20 | 09-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 348695.04 | 01-FEB-08:09 | 54335.80 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 118955.74 | 01-FEB-08:20 | 118074.24 | 17-FEB-14:09 | 31337.88 | 13-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 341614.39 | 15-MAR-07:10 | 54335.80 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 118949.83 | 15-MAR-07:19 | 112763.87 | 23-MAR-15:00 | 30923.38 | 07-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 332766.70 | 10-APR-07:10 | 54335.80 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 118942.44 | 10-APR-07:19 | 223029.95 | 28-APR-14:00 | 51782.73 | 28-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 316816.17 | 01-MAY-07:10 | 54335.80 | 01-MAY-19:19 | 439129.89 | 01-MAY-07:10 | 118929.14 | 01-MAY-07:19 | 196553.55 | 23-MAY-15:20 | 49338.54 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 316816.17 | 01-JUN-07:10 | 54335.80 | 01-JUN-19:00 | 557421.28 | 01-JUN-07:10 | 118929.14 | 01-JUN-07:19 | 230352.26 | 13-JUN-15:30 | 51449.29 | 20-JUN-14:00 | 0.00 | 01-JUN-00:10 |
July | 316816.17 | 03-JUL-07:10 | 54335.80 | 01-JUL-20:19 | 675712.68 | 03-JUL-07:10 | 118929.14 | 03-JUL-07:19 | 227381.47 | 21-JUL-15:20 | 50079.63 | 06-JUL-13:00 | 0.00 | 01-JUL-00:10 |
August | 322989.06 | 22-AUG-07:30 | 54335.80 | 01-AUG-19:49 | 794004.08 | 01-AUG-07:10 | 118934.29 | 22-AUG-07:40 | 219428.89 | 14-AUG-15:09 | 51397.05 | 21-AUG-12:09 | 0.00 | 01-AUG-00:10 |
September | 327530.87 | 08-SEP-07:30 | 54335.80 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 118938.07 | 08-SEP-07:40 | 224401.90 | 12-SEP-15:20 | 48512.31 | 12-SEP-15:09 | 0.00 | 01-SEP-00:10 |
October | 352476.11 | 31-OCT-07:10 | 54335.80 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 118958.90 | 31-OCT-07:19 | 166762.76 | 03-OCT-14:50 | 30502.60 | 23-OCT-05:30 | 0.00 | 01-OCT-00:10 |
November | 352853.36 | 06-NOV-16:49 | 54335.80 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 118958.96 | 02-NOV-07:19 | 117904.35 | 10-NOV-13:30 | 31706.60 | 20-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 352853.36 | 01-DEC-15:30 | 54335.80 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 118959.22 | 27-DEC-08:20 | 102063.86 | 21-DEC-14:09 | 32198.02 | 26-DEC-05:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 316816.17 | 54335.80 | 439129.89 | 118929.14 | 102063.86 | 30502.60 | 0.00 | |||||||
Maximum of Months | 352853.36 | 54335.80 | 794004.08 | 118959.22 | 230352.26 | 51782.73 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 36966.88 | 20-JAN-16:49 | 18673.36 | 29-JAN-05:00 | 5914.45 | 10-JAN-20:00 | 0.00 | 0.00 | 0.00 |
February | 63188.16 | 24-FEB-16:00 | 21374.70 | 07-FEB-14:00 | 3659.73 | 17-FEB-20:00 | 0.00 | 0.00 | 0.00 |
March | 105470.49 | 31-MAR-23:00 | 46274.23 | 25-MAR-12:00 | 3493.75 | 03-MAR-21:49 | 0.00 | 0.00 | 0.00 |
April | 279622.69 | 28-APR-14:00 | 50845.82 | 28-APR-15:09 | 3251.94 | 14-APR-11:00 | 0.00 | 0.00 | 0.00 |
May | 197994.68 | 22-MAY-15:00 | 77869.83 | 22-MAY-14:09 | 2575.86 | 06-MAY-16:10 | 0.00 | 0.00 | 0.00 |
June | 291836.83 | 13-JUN-15:00 | 77869.83 | 12-JUN-13:30 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 306724.63 | 21-JUL-15:39 | 77869.83 | 10-JUL-08:50 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 325650.88 | 14-AUG-14:00 | 77869.83 | 14-AUG-10:20 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 203333.95 | 12-SEP-14:50 | 77869.83 | 11-SEP-13:00 | 1372.78 | 30-SEP-11:09 | 0.00 | 0.00 | 0.00 |
October | 106218.98 | 07-OCT-14:00 | 49440.68 | 11-OCT-14:00 | 2542.25 | 07-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 98649.08 | 24-NOV-11:00 | 49248.27 | 24-NOV-11:20 | 3625.76 | 28-NOV-20:00 | 0.00 | 0.00 | 0.00 |
December | 107264.22 | 04-DEC-11:00 | 47806.88 | 23-DEC-10:00 | 4696.06 | 29-DEC-20:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 36966.88 | 18673.36 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 325650.88 | 77869.83 | 5914.45 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1113825.10 | 02-JAN-08:09 | 352853.36 | 439129.89 | 54335.80 | 118765.30 | 82627.13 | 31493.80 | 0.00 | 31289.49 | 3330.34 |
February | 1174987.93 | 02-FEB-16:00 | 339484.94 | 557421.28 | 0.00 | 84900.90 | 94939.02 | 29935.67 | 0.00 | 60723.35 | 7582.77 |
March | 1332154.61 | 20-MAR-07:00 | 316816.17 | 675712.68 | 0.00 | 118929.98 | 83241.95 | 29952.91 | 0.00 | 83033.05 | 24467.88 |
April | 1755216.61 | 28-APR-14:00 | 316816.17 | 794004.08 | 0.00 | 39494.57 | 223029.95 | 51782.73 | 0.00 | 279622.69 | 50466.42 |
May | 1341869.34 | 22-MAY-15:09 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 188035.34 | 47332.41 | 0.00 | 187799.94 | 77869.83 |
June | 1599597.02 | 13-JUN-15:30 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 230352.26 | 47736.45 | 0.00 | 284515.27 | 77869.83 |
July | 1712532.73 | 21-JUL-15:39 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 226176.46 | 48243.61 | 0.00 | 306724.63 | 53973.43 |
August | 1838139.92 | 14-AUG-15:39 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 217916.00 | 47637.25 | 0.00 | 321893.53 | 54987.14 |
September | 1366050.96 | 13-SEP-15:20 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 214673.95 | 46949.30 | 0.00 | 185726.07 | 77869.83 |
October | 1300254.57 | 06-OCT-15:20 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 157904.17 | 30034.47 | 0.00 | 103806.80 | 49385.93 |
November | 1403481.83 | 16-NOV-16:40 | 352853.36 | 675712.68 | 54335.80 | 84915.24 | 100830.66 | 29910.92 | 0.00 | 84641.18 | 20282.00 |
December | 1544836.54 | 21-DEC-16:19 | 352853.36 | 794004.08 | 54335.80 | 84915.83 | 96230.06 | 29914.40 | 0.00 | 106341.04 | 26241.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1113825.10 | 316816.17 | 439129.89 | 0.00 | 39494.57 | 82627.13 | 29910.92 | 0.00 | 31289.49 | 3330.34 | |
Maximum of Months | 1838139.92 | 352853.36 | 794004.08 | 54335.80 | 118929.98 | 230352.26 | 51782.73 | 0.00 | 321893.53 | 77869.83 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 743188.72 | 10-JAN-07:00 | 0.00 | 82108.47 | 30-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 631683.21 | 17-FEB-07:10 | 0.00 | 82176.29 | 15-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 433158.92 | 27-MAR-06:10 | 0.00 | 82132.10 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 298686.03 | 08-APR-06:10 | 0.00 | 81617.66 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 255373.89 | 05-MAY-05:10 | 0.00 | 80871.16 | 01-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 42463.09 | 08-JUN-05:10 | 0.00 | 79848.85 | 01-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 6804.44 | 01-JUL-05:10 | 0.00 | 78843.03 | 05-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 3372.77 | 12-AUG-05:40 | 0.00 | 78376.56 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 99556.69 | 21-SEP-06:10 | 0.00 | 78867.86 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 301072.11 | 23-OCT-06:40 | 0.00 | 79811.44 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 561141.30 | 29-NOV-07:10 | 0.00 | 80842.15 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 639247.01 | 26-DEC-05:10 | 0.00 | 81576.23 | 27-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 3372.77 | 0.00 | 78376.56 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 743188.72 | 0.00 | 82176.29 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.18 | 3.00 | 27.25 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.99 | 0.00 | 25.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.02 | 0.00 | 26.02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 26.37 | 0.00 | 26.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 26.46 | 0.17 | 26.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.97 | 0.00 | 25.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.47 | 0.00 | 26.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 26.25 | 0.00 | 26.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.27 | 0.17 | 26.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.42 | 0.00 | 26.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.36 | 0.83 | 26.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 26.43 | 0.33 | 26.48 |
Annual Sum or Average | 0.00 | 0.00 | 66.50 | 26.44 | 4.50 | 26.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.97 | 0.00 | 25.97 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.18 | 3.00 | 27.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.59 | 0.00 | 25.59 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.85 | 0.00 | 25.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 25.64 | 0.00 | 25.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.85 | 0.00 | 25.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
February | 0.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
December | 0.83 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
Annual Sum or Average | 2.50 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.93 | 1.00 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.63 | 1.00 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.55 | 1.83 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.89 | 2.67 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.61 | 1.83 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.59 | 1.33 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.67 | 27.71 | 9.67 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.93 | 2.67 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.20 | 1.50 | 28.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.57 | 1.50 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.72 | 3.67 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.81 | 3.00 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.83 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.38 | 0.67 | 27.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.50 | 27.74 | 11.50 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.20 | 3.67 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.16 | 2.17 | 28.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.93 | 1.83 | 27.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.12 | 2.00 | 28.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.20 | 3.83 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.97 | 4.00 | 28.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.59 | 1.67 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 31.33 | 28.05 | 15.67 | 28.11 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.20 | 4.00 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Annual Sum or Average | 1.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.02 | 1.00 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.63 | 0.50 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.61 | 1.17 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.17 | 2.17 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.68 | 1.33 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.33 | 0.50 | 27.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Annual Sum or Average | 1.50 | 19.30 | 0.00 | 19.30 | 6.67 | 26.28 | 6.67 | 26.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.34 | 0.00 | 19.34 | 2.17 | 28.17 | 2.17 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.30 | 1.50 | 28.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.48 | 0.83 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.73 | 2.67 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.90 | 3.67 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.76 | 0.83 | 27.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.37 | 0.17 | 27.37 |
December | 0.33 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Annual Sum or Average | 0.33 | 19.36 | 0.00 | 19.36 | 9.67 | 27.57 | 9.67 | 27.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.36 | 0.00 | 19.36 | 3.67 | 28.30 | 3.67 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.42 | 0.67 | 28.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.89 | 0.83 | 27.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.15 | 1.00 | 28.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.09 | 2.00 | 28.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.90 | 2.00 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.39 | 0.33 | 27.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Annual Sum or Average | 0.17 | 19.29 | 0.00 | 19.29 | 12.50 | 27.93 | 6.83 | 27.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.29 | 0.00 | 19.29 | 4.67 | 28.42 | 2.00 | 28.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.67 | 18.91 | 4.67 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
February | 8.50 | 18.96 | 1.67 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
March | 2.50 | 19.24 | 0.33 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.83 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
November | 8.67 | 18.61 | 2.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
December | 20.33 | 18.30 | 5.50 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
Annual Sum or Average | 54.67 | 18.67 | 14.17 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.33 | 19.38 | 5.50 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
February | 4.50 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
March | 1.50 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.86 | 0.83 | 27.86 |
May | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.60 | 0.50 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.05 | 2.17 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.59 | 0.50 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.67 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
November | 4.00 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
December | 10.00 | 17.31 | 0.50 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
Annual Sum or Average | 26.00 | 18.03 | 0.50 | 17.98 | 4.00 | 19.28 | 4.00 | 20.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.00 | 19.30 | 0.50 | 19.30 | 2.17 | 28.05 | 2.17 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
February | 3.17 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
March | 1.33 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.31 | 1.50 | 28.31 |
May | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.65 | 1.00 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.63 | 2.67 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.92 | 2.33 | 27.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.17 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
December | 7.00 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
Annual Sum or Average | 18.83 | 18.53 | 0.00 | 18.53 | 7.50 | 21.19 | 7.50 | 22.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.00 | 19.35 | 0.00 | 19.35 | 2.67 | 28.31 | 2.67 | 28.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
February | 2.33 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
March | 1.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.34 | 0.83 | 28.33 |
May | 0.17 | 19.43 | 0.00 | 19.43 | 1.17 | 26.85 | 0.67 | 27.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.22 | 1.00 | 28.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.09 | 2.17 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.92 | 1.83 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.83 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
December | 6.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
Annual Sum or Average | 16.17 | 18.59 | 0.00 | 18.59 | 12.17 | 22.66 | 6.67 | 23.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 19.43 | 0.00 | 19.43 | 4.83 | 28.34 | 2.17 | 28.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.31 | 5.00 | 28.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.10 | 5.00 | 28.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.50 | 28.22 | 10.00 | 28.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.31 | 5.00 | 28.26 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 69.33 | 23.97 | 103.17 | 25.19 | 0.00 | 25.19 |
February | 32.50 | 24.00 | 88.00 | 25.51 | 0.00 | 25.51 |
March | 26.50 | 24.01 | 86.33 | 25.56 | 0.00 | 25.56 |
April | 0.33 | 24.00 | 104.33 | 26.30 | 0.00 | 26.30 |
May | 1.33 | 24.00 | 177.67 | 25.29 | 0.00 | 25.29 |
June | 0.00 | 0.00 | 319.83 | 24.68 | 0.00 | 24.68 |
July | 0.00 | 0.00 | 421.50 | 24.69 | 0.00 | 24.69 |
August | 0.00 | 0.00 | 428.83 | 24.55 | 0.00 | 24.55 |
September | 0.00 | 0.00 | 313.50 | 24.79 | 0.00 | 24.79 |
October | 0.83 | 24.00 | 197.00 | 25.35 | 0.00 | 25.35 |
November | 5.50 | 24.00 | 166.17 | 25.50 | 0.00 | 25.50 |
December | 25.50 | 24.00 | 105.17 | 25.77 | 0.00 | 25.77 |
Annual Sum or Average | 161.83 | 23.99 | 2511.50 | 25.04 | 0.00 | 25.04 |
Minimum of Months | 0.00 | 0.00 | 86.33 | 24.55 | 0.00 | 24.55 |
Maximum of Months | 69.33 | 24.01 | 428.83 | 26.30 | 0.00 | 26.30 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 164.33 | 23.97 | 62.17 | 24.39 | 12.33 | 24.49 |
February | 88.50 | 23.84 | 65.17 | 24.55 | 0.00 | 24.55 |
March | 34.17 | 23.90 | 78.67 | 25.25 | 0.00 | 25.25 |
April | 3.17 | 23.93 | 105.67 | 25.62 | 0.00 | 25.62 |
May | 12.50 | 23.79 | 167.17 | 24.76 | 0.00 | 24.76 |
June | 0.00 | 0.00 | 345.50 | 24.40 | 0.00 | 24.40 |
July | 0.00 | 0.00 | 429.33 | 24.38 | 0.00 | 24.38 |
August | 0.00 | 0.00 | 451.00 | 24.31 | 0.00 | 24.31 |
September | 0.67 | 23.77 | 306.33 | 24.43 | 0.00 | 24.43 |
October | 14.50 | 23.76 | 205.67 | 24.90 | 0.00 | 24.90 |
November | 29.83 | 23.90 | 160.50 | 24.99 | 0.00 | 24.99 |
December | 60.83 | 23.87 | 91.50 | 25.02 | 0.00 | 25.02 |
Annual Sum or Average | 408.50 | 23.90 | 2468.67 | 24.60 | 12.33 | 24.61 |
Minimum of Months | 0.00 | 0.00 | 62.17 | 24.31 | 0.00 | 24.31 |
Maximum of Months | 164.33 | 23.97 | 451.00 | 25.62 | 12.33 | 25.62 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 404.83 | 23.28 | 12.33 | 23.25 | 12.33 | 23.22 |
February | 340.17 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
March | 345.83 | 23.55 | 0.00 | 23.55 | 0.00 | 23.55 |
April | 154.83 | 23.68 | 26.00 | 23.92 | 0.00 | 23.92 |
May | 132.00 | 23.57 | 82.33 | 23.98 | 0.00 | 23.98 |
June | 32.17 | 23.53 | 232.17 | 24.27 | 0.00 | 24.27 |
July | 24.33 | 23.46 | 297.17 | 24.28 | 0.00 | 24.28 |
August | 5.67 | 23.44 | 299.67 | 24.26 | 0.00 | 24.26 |
September | 57.83 | 23.55 | 175.00 | 24.19 | 0.00 | 24.19 |
October | 195.00 | 23.49 | 46.17 | 23.71 | 0.00 | 23.71 |
November | 304.67 | 23.42 | 4.00 | 23.43 | 0.00 | 23.43 |
December | 448.50 | 23.16 | 0.00 | 23.16 | 0.00 | 23.16 |
Annual Sum or Average | 2445.83 | 23.40 | 1174.83 | 23.72 | 12.33 | 23.71 |
Minimum of Months | 5.67 | 23.16 | 0.00 | 23.16 | 0.00 | 23.16 |
Maximum of Months | 448.50 | 23.68 | 299.67 | 24.28 | 12.33 | 24.28 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.33 | 21.66 | 93.83 | 21.38 | 93.83 | 21.18 |
February | 452.83 | 21.91 | 71.33 | 21.66 | 71.33 | 21.46 |
March | 505.50 | 22.45 | 23.17 | 22.36 | 23.17 | 22.28 |
April | 324.83 | 23.19 | 3.17 | 23.20 | 0.00 | 23.20 |
May | 276.00 | 23.19 | 52.33 | 23.34 | 0.00 | 23.34 |
June | 125.83 | 23.33 | 195.33 | 23.85 | 0.00 | 23.85 |
July | 108.67 | 23.33 | 254.67 | 23.96 | 0.00 | 23.96 |
August | 85.00 | 23.36 | 245.33 | 23.96 | 0.00 | 23.96 |
September | 213.00 | 23.15 | 102.00 | 23.46 | 0.00 | 23.46 |
October | 425.33 | 22.59 | 0.17 | 22.59 | 0.00 | 22.59 |
November | 474.67 | 22.10 | 45.50 | 21.95 | 45.50 | 21.82 |
December | 497.00 | 21.48 | 116.33 | 21.16 | 116.33 | 20.94 |
Annual Sum or Average | 3986.00 | 22.36 | 1203.17 | 22.50 | 350.17 | 22.34 |
Minimum of Months | 85.00 | 21.48 | 0.17 | 21.16 | 0.00 | 20.94 |
Maximum of Months | 505.50 | 23.36 | 254.67 | 23.96 | 116.33 | 23.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.00 | 22.47 | 15.00 | 22.43 | 15.00 | 22.39 |
February | 438.67 | 22.71 | 0.00 | 22.71 | 0.00 | 22.71 |
March | 458.33 | 23.24 | 4.33 | 23.26 | 0.00 | 23.26 |
April | 228.17 | 23.59 | 14.00 | 23.67 | 0.00 | 23.67 |
May | 211.83 | 23.47 | 57.00 | 23.65 | 0.00 | 23.65 |
June | 40.33 | 23.66 | 243.83 | 24.18 | 0.00 | 24.18 |
July | 4.83 | 23.72 | 345.83 | 24.31 | 0.00 | 24.31 |
August | 18.83 | 23.64 | 342.50 | 24.19 | 0.00 | 24.19 |
September | 159.00 | 23.40 | 109.83 | 23.73 | 0.00 | 23.73 |
October | 342.83 | 23.21 | 16.67 | 23.27 | 0.00 | 23.27 |
November | 424.50 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
December | 497.00 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
Annual Sum or Average | 3321.33 | 23.00 | 1149.00 | 23.32 | 15.00 | 23.31 |
Minimum of Months | 4.83 | 22.47 | 0.00 | 22.43 | 0.00 | 22.39 |
Maximum of Months | 497.00 | 23.72 | 345.83 | 24.31 | 15.00 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 495.17 | 21.79 | 18.83 | 21.78 | 17.17 | 21.75 |
February | 440.33 | 21.92 | 1.33 | 21.93 | 0.33 | 21.93 |
March | 495.33 | 22.20 | 1.67 | 22.21 | 0.00 | 22.21 |
April | 239.83 | 22.89 | 80.67 | 23.29 | 3.00 | 23.32 |
May | 235.67 | 22.86 | 149.17 | 23.51 | 2.50 | 23.53 |
June | 147.00 | 23.12 | 247.83 | 23.85 | 7.00 | 23.90 |
July | 108.83 | 23.33 | 310.67 | 24.09 | 11.83 | 24.17 |
August | 125.17 | 23.09 | 293.17 | 23.86 | 7.33 | 23.92 |
September | 193.67 | 22.86 | 207.67 | 23.64 | 5.67 | 23.69 |
October | 390.33 | 22.34 | 37.83 | 22.53 | 0.00 | 22.53 |
November | 483.17 | 22.06 | 1.50 | 22.07 | 0.00 | 22.07 |
December | 497.00 | 21.64 | 10.50 | 21.62 | 10.50 | 21.61 |
Annual Sum or Average | 3851.50 | 22.25 | 1360.83 | 22.78 | 65.33 | 22.80 |
Minimum of Months | 108.83 | 21.64 | 1.33 | 21.62 | 0.00 | 21.61 |
Maximum of Months | 497.00 | 23.33 | 310.67 | 24.09 | 17.17 | 24.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 431.50 | 21.83 | 43.00 | 22.01 | 11.50 | 21.99 |
February | 364.67 | 22.00 | 42.17 | 22.26 | 2.00 | 22.25 |
March | 463.17 | 22.32 | 0.00 | 22.32 | 0.00 | 22.32 |
April | 221.17 | 23.01 | 119.17 | 23.49 | 5.33 | 23.55 |
May | 283.50 | 22.77 | 127.00 | 23.27 | 0.00 | 23.27 |
June | 153.33 | 22.94 | 228.00 | 23.70 | 0.50 | 23.71 |
July | 112.00 | 23.25 | 302.33 | 24.03 | 8.17 | 24.08 |
August | 99.33 | 23.58 | 339.17 | 24.14 | 16.50 | 24.23 |
September | 167.50 | 23.07 | 258.00 | 23.88 | 11.67 | 23.96 |
October | 337.67 | 22.48 | 100.17 | 22.92 | 1.50 | 22.94 |
November | 414.33 | 22.18 | 35.17 | 22.39 | 0.50 | 22.40 |
December | 455.83 | 21.73 | 31.17 | 21.80 | 14.83 | 21.76 |
Annual Sum or Average | 3504.00 | 22.35 | 1625.33 | 22.97 | 72.50 | 22.99 |
Minimum of Months | 99.33 | 21.73 | 0.00 | 21.80 | 0.00 | 21.76 |
Maximum of Months | 463.17 | 23.58 | 339.17 | 24.14 | 16.50 | 24.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 469.67 | 22.18 | 8.33 | 22.23 | 0.00 | 22.23 |
February | 361.33 | 22.69 | 36.50 | 22.88 | 0.00 | 22.88 |
March | 274.17 | 23.00 | 57.33 | 23.43 | 0.00 | 23.43 |
April | 51.67 | 23.85 | 272.50 | 24.70 | 7.00 | 24.75 |
May | 180.50 | 23.02 | 197.00 | 23.83 | 6.00 | 23.88 |
June | 35.33 | 24.42 | 403.17 | 24.43 | 12.17 | 24.50 |
July | 23.33 | 26.45 | 472.33 | 24.61 | 20.00 | 24.70 |
August | 19.17 | 26.99 | 500.83 | 24.53 | 19.17 | 24.62 |
September | 145.00 | 22.99 | 244.17 | 23.88 | 6.00 | 23.92 |
October | 256.00 | 22.84 | 121.17 | 23.51 | 0.00 | 23.51 |
November | 289.83 | 22.89 | 76.17 | 23.36 | 0.00 | 23.36 |
December | 360.33 | 22.94 | 27.67 | 23.13 | 0.00 | 23.13 |
Annual Sum or Average | 2466.33 | 22.86 | 2417.17 | 23.72 | 70.33 | 23.77 |
Minimum of Months | 19.17 | 22.18 | 8.33 | 22.23 | 0.00 | 22.23 |
Maximum of Months | 469.67 | 26.99 | 500.83 | 24.70 | 20.00 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.01 | 195.17 | 20.83 | 195.17 | 20.72 |
February | 454.00 | 21.12 | 126.83 | 20.94 | 126.83 | 20.81 |
March | 514.00 | 21.76 | 39.33 | 21.68 | 39.33 | 21.61 |
April | 429.00 | 22.81 | 2.17 | 22.80 | 2.17 | 22.78 |
May | 388.67 | 22.88 | 21.00 | 22.94 | 0.00 | 22.94 |
June | 185.67 | 23.26 | 122.00 | 23.60 | 0.00 | 23.60 |
July | 150.17 | 23.30 | 197.67 | 23.77 | 0.00 | 23.77 |
August | 170.00 | 23.26 | 150.00 | 23.61 | 0.00 | 23.61 |
September | 327.83 | 22.88 | 50.17 | 23.03 | 0.00 | 23.03 |
October | 494.00 | 22.10 | 10.33 | 22.06 | 10.33 | 22.03 |
November | 489.00 | 21.32 | 88.00 | 21.16 | 88.00 | 21.05 |
December | 497.00 | 20.69 | 236.67 | 20.52 | 236.67 | 20.43 |
Annual Sum or Average | 4601.33 | 21.93 | 1239.33 | 21.93 | 698.50 | 21.75 |
Minimum of Months | 150.17 | 20.69 | 2.17 | 20.52 | 0.00 | 20.43 |
Maximum of Months | 514.00 | 23.30 | 236.67 | 23.77 | 236.67 | 23.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.87 | 157.50 | 20.75 | 157.50 | 20.69 |
February | 385.00 | 21.02 | 94.67 | 20.91 | 94.67 | 20.83 |
March | 433.00 | 21.29 | 41.17 | 21.24 | 41.17 | 21.19 |
April | 289.00 | 22.47 | 47.17 | 22.76 | 4.33 | 22.80 |
May | 283.17 | 22.34 | 89.50 | 22.88 | 1.33 | 22.89 |
June | 207.50 | 22.70 | 155.33 | 23.44 | 5.17 | 23.49 |
July | 160.67 | 23.03 | 203.83 | 23.91 | 11.33 | 24.00 |
August | 180.67 | 22.88 | 184.83 | 23.60 | 7.33 | 23.66 |
September | 226.33 | 22.38 | 118.83 | 23.11 | 1.67 | 23.13 |
October | 408.17 | 21.67 | 11.50 | 21.69 | 6.17 | 21.67 |
November | 417.00 | 21.02 | 81.50 | 20.92 | 81.50 | 20.85 |
December | 422.00 | 20.57 | 225.17 | 20.43 | 225.17 | 20.37 |
Annual Sum or Average | 3839.50 | 21.60 | 1411.00 | 21.90 | 637.33 | 21.77 |
Minimum of Months | 160.67 | 20.57 | 11.50 | 20.43 | 1.33 | 20.37 |
Maximum of Months | 433.00 | 23.03 | 225.17 | 23.91 | 225.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 447.00 | 21.39 | 101.67 | 21.39 | 83.83 | 21.29 |
February | 381.83 | 21.50 | 73.67 | 21.66 | 37.67 | 21.57 |
March | 494.17 | 21.66 | 23.83 | 21.62 | 23.83 | 21.58 |
April | 285.00 | 22.53 | 101.33 | 23.06 | 5.33 | 23.11 |
May | 335.67 | 22.32 | 103.00 | 22.81 | 0.00 | 22.81 |
June | 249.00 | 22.61 | 175.17 | 23.28 | 0.17 | 23.28 |
July | 191.33 | 22.80 | 227.83 | 23.63 | 6.00 | 23.68 |
August | 181.00 | 23.04 | 260.83 | 23.76 | 12.17 | 23.84 |
September | 212.33 | 22.81 | 228.50 | 23.64 | 14.83 | 23.75 |
October | 373.67 | 21.95 | 85.00 | 22.36 | 5.67 | 22.38 |
November | 441.17 | 21.47 | 61.17 | 21.57 | 38.67 | 21.50 |
December | 478.50 | 21.03 | 169.00 | 20.86 | 166.17 | 20.75 |
Annual Sum or Average | 4070.67 | 21.90 | 1611.00 | 22.36 | 394.33 | 22.28 |
Minimum of Months | 181.00 | 21.03 | 23.83 | 20.86 | 0.00 | 20.75 |
Maximum of Months | 494.17 | 23.04 | 260.83 | 23.76 | 166.17 | 23.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.33 | 21.04 | 134.50 | 20.93 | 134.50 | 20.86 |
February | 440.50 | 21.20 | 65.00 | 21.11 | 63.67 | 21.03 |
March | 507.00 | 21.43 | 19.67 | 21.40 | 19.33 | 21.38 |
April | 369.50 | 22.43 | 59.33 | 22.70 | 2.50 | 22.72 |
May | 360.67 | 22.35 | 95.50 | 22.78 | 2.33 | 22.80 |
June | 230.50 | 22.75 | 196.00 | 23.46 | 4.50 | 23.49 |
July | 171.83 | 22.89 | 263.67 | 23.77 | 10.67 | 23.84 |
August | 196.00 | 22.88 | 217.67 | 23.59 | 8.83 | 23.66 |
September | 326.00 | 22.39 | 103.83 | 22.86 | 2.33 | 22.88 |
October | 467.67 | 21.71 | 17.83 | 21.79 | 1.50 | 21.79 |
November | 488.33 | 21.18 | 55.67 | 21.10 | 55.67 | 21.03 |
December | 497.00 | 20.75 | 195.83 | 20.63 | 195.83 | 20.56 |
Annual Sum or Average | 4556.33 | 21.70 | 1424.50 | 22.02 | 501.67 | 21.92 |
Minimum of Months | 171.83 | 20.75 | 17.83 | 20.63 | 1.50 | 20.56 |
Maximum of Months | 507.00 | 22.89 | 263.67 | 23.77 | 195.83 | 23.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.26 | 354.00 | 20.10 | 354.00 | 20.04 |
February | 454.00 | 20.31 | 278.50 | 20.12 | 278.50 | 20.03 |
March | 514.00 | 20.93 | 214.33 | 20.75 | 214.33 | 20.65 |
April | 453.50 | 22.10 | 52.00 | 21.93 | 52.00 | 21.78 |
May | 430.50 | 22.19 | 41.50 | 22.21 | 17.83 | 22.14 |
June | 251.83 | 22.79 | 106.83 | 23.17 | 0.00 | 23.17 |
July | 212.00 | 22.84 | 174.67 | 23.41 | 0.00 | 23.41 |
August | 254.00 | 22.91 | 129.00 | 23.28 | 0.00 | 23.28 |
September | 380.67 | 22.30 | 44.33 | 22.40 | 8.33 | 22.35 |
October | 502.00 | 21.14 | 123.83 | 20.90 | 123.83 | 20.75 |
November | 489.00 | 20.47 | 264.50 | 20.26 | 264.50 | 20.16 |
December | 497.00 | 20.04 | 401.00 | 19.93 | 401.00 | 19.89 |
Annual Sum or Average | 4940.50 | 21.29 | 2184.50 | 21.15 | 1714.33 | 20.91 |
Minimum of Months | 212.00 | 20.04 | 41.50 | 19.93 | 0.00 | 19.89 |
Maximum of Months | 514.00 | 22.91 | 401.00 | 23.41 | 401.00 | 23.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.32 | 337.67 | 20.18 | 337.67 | 20.12 |
February | 454.00 | 20.44 | 257.67 | 20.26 | 257.67 | 20.18 |
March | 514.00 | 20.84 | 206.33 | 20.72 | 206.33 | 20.65 |
April | 349.67 | 22.14 | 66.67 | 22.32 | 23.67 | 22.26 |
May | 350.83 | 22.08 | 97.17 | 22.51 | 5.67 | 22.48 |
June | 238.50 | 22.37 | 194.50 | 23.22 | 2.17 | 23.24 |
July | 181.33 | 22.77 | 262.00 | 23.74 | 11.67 | 23.82 |
August | 205.33 | 22.64 | 247.33 | 23.49 | 3.67 | 23.52 |
September | 259.50 | 22.06 | 146.67 | 22.84 | 2.67 | 22.82 |
October | 488.17 | 21.16 | 104.83 | 20.97 | 104.83 | 20.84 |
November | 489.00 | 20.50 | 237.17 | 20.31 | 237.17 | 20.22 |
December | 497.00 | 20.08 | 386.83 | 19.97 | 386.83 | 19.92 |
Annual Sum or Average | 4529.33 | 21.16 | 2544.83 | 21.34 | 1580.00 | 21.11 |
Minimum of Months | 181.33 | 20.08 | 66.67 | 19.97 | 2.17 | 19.92 |
Maximum of Months | 514.00 | 22.77 | 386.83 | 23.74 | 386.83 | 23.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.17 | 20.76 | 255.50 | 20.56 | 252.00 | 20.45 |
February | 416.67 | 20.93 | 185.00 | 20.76 | 172.33 | 20.61 |
March | 505.50 | 21.06 | 176.00 | 20.90 | 176.00 | 20.80 |
April | 333.67 | 22.11 | 108.50 | 22.44 | 32.17 | 22.38 |
May | 366.50 | 21.83 | 110.00 | 22.27 | 17.17 | 22.21 |
June | 282.67 | 22.21 | 157.33 | 22.92 | 0.67 | 22.92 |
July | 230.00 | 22.44 | 207.67 | 23.33 | 6.67 | 23.38 |
August | 224.17 | 22.69 | 232.83 | 23.48 | 11.67 | 23.56 |
September | 243.67 | 22.25 | 212.17 | 23.19 | 15.17 | 23.23 |
October | 412.17 | 21.35 | 112.33 | 21.54 | 57.33 | 21.41 |
November | 466.50 | 20.87 | 184.50 | 20.72 | 173.83 | 20.58 |
December | 490.67 | 20.40 | 326.17 | 20.21 | 326.17 | 20.13 |
Annual Sum or Average | 4451.33 | 21.38 | 2268.00 | 21.62 | 1241.17 | 21.41 |
Minimum of Months | 224.17 | 20.40 | 108.50 | 20.21 | 0.67 | 20.13 |
Maximum of Months | 505.50 | 22.69 | 326.17 | 23.48 | 326.17 | 23.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.49 | 298.33 | 20.34 | 298.33 | 20.27 |
February | 451.00 | 20.72 | 203.00 | 20.51 | 203.00 | 20.40 |
March | 510.33 | 20.98 | 155.33 | 20.87 | 155.33 | 20.80 |
April | 390.17 | 21.91 | 73.33 | 22.11 | 24.50 | 22.06 |
May | 378.67 | 21.83 | 92.00 | 22.29 | 7.67 | 22.29 |
June | 270.50 | 22.37 | 163.83 | 23.08 | 4.17 | 23.12 |
July | 212.17 | 22.52 | 228.00 | 23.45 | 10.67 | 23.53 |
August | 262.17 | 22.62 | 184.33 | 23.28 | 8.50 | 23.34 |
September | 359.83 | 21.98 | 93.50 | 22.42 | 5.50 | 22.42 |
October | 477.17 | 21.16 | 71.00 | 21.11 | 60.33 | 21.01 |
November | 489.00 | 20.70 | 197.17 | 20.52 | 197.17 | 20.43 |
December | 497.00 | 20.26 | 354.33 | 20.13 | 354.33 | 20.08 |
Annual Sum or Average | 4800.00 | 21.27 | 2114.17 | 21.41 | 1329.50 | 21.22 |
Minimum of Months | 212.17 | 20.26 | 71.00 | 20.13 | 4.17 | 20.08 |
Maximum of Months | 510.33 | 22.62 | 354.33 | 23.45 | 354.33 | 23.53 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 4.17 | 27.00 | 454.00 | 27.00 | 4.17 | 27.00 |
March | 3.33 | 27.00 | 514.00 | 27.00 | 3.33 | 27.00 |
April | 81.17 | 27.00 | 485.00 | 27.00 | 81.17 | 27.00 |
May | 8.67 | 27.00 | 508.00 | 27.00 | 8.67 | 27.00 |
June | 63.33 | 27.00 | 496.00 | 27.00 | 63.33 | 27.00 |
July | 194.50 | 27.00 | 497.00 | 27.00 | 194.50 | 27.00 |
August | 319.17 | 27.00 | 514.00 | 27.00 | 319.17 | 27.00 |
September | 17.17 | 27.00 | 485.00 | 27.00 | 17.17 | 27.00 |
October | 11.00 | 27.00 | 502.00 | 27.00 | 11.00 | 27.00 |
November | 4.33 | 27.00 | 489.00 | 27.00 | 4.33 | 27.00 |
December | 0.83 | 27.00 | 497.00 | 27.00 | 0.83 | 27.00 |
Annual Sum or Average | 707.67 | 27.00 | 5943.00 | 27.00 | 707.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 319.17 | 27.00 | 514.00 | 27.00 | 319.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 492.50 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 8.17 | 27.00 | 485.00 | 27.00 | 8.17 | 27.00 |
May | 2.00 | 27.00 | 508.00 | 27.00 | 2.00 | 27.00 |
June | 7.50 | 27.00 | 496.00 | 27.00 | 7.50 | 27.00 |
July | 15.83 | 27.00 | 497.00 | 27.00 | 15.83 | 27.00 |
August | 34.00 | 27.00 | 514.00 | 27.00 | 34.00 | 27.00 |
September | 4.17 | 27.00 | 485.00 | 27.00 | 4.17 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 487.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 71.67 | 27.00 | 5924.33 | 27.00 | 71.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 34.00 | 27.00 | 514.00 | 27.00 | 34.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 80.50 | 25.24 | 340.67 | 26.66 | 0.00 | 26.66 |
February | 3.17 | 27.00 | 380.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 485.83 | 27.00 | 0.00 | 27.00 |
April | 10.83 | 27.00 | 485.00 | 27.00 | 10.83 | 27.00 |
May | 5.33 | 27.00 | 508.00 | 27.00 | 5.33 | 27.00 |
June | 22.50 | 27.00 | 496.00 | 27.00 | 22.50 | 27.00 |
July | 43.17 | 27.00 | 497.00 | 27.00 | 43.17 | 27.00 |
August | 53.67 | 27.00 | 514.00 | 27.00 | 53.67 | 27.00 |
September | 5.83 | 27.00 | 485.00 | 27.00 | 5.83 | 27.00 |
October | 0.00 | 0.00 | 499.67 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 448.33 | 27.00 | 0.00 | 27.00 |
December | 6.50 | 27.00 | 390.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 231.50 | 26.39 | 5529.67 | 26.98 | 141.33 | 26.98 |
Minimum of Months | 0.00 | 0.00 | 340.67 | 26.66 | 0.00 | 26.66 |
Maximum of Months | 80.50 | 27.00 | 514.00 | 27.00 | 53.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 382.17 | 27.00 | 502.00 | 27.00 | 382.17 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.02 | 514.00 | 27.02 | 514.00 | 27.02 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5823.17 | 27.00 | 5943.00 | 27.00 | 5823.17 | 27.00 |
Minimum of Months | 382.17 | 27.00 | 454.00 | 27.00 | 382.17 | 27.00 |
Maximum of Months | 514.00 | 27.02 | 514.00 | 27.02 | 514.00 | 27.02 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 27.62661 | 0.79326 | 18.37972 |
February | 454.00000 | 27.00001 | 27.89914 | 0.84854 | 20.28250 |
March | 514.00000 | 27.00000 | 27.83709 | 0.89537 | 21.99224 |
April | 485.00000 | 27.00000 | 28.45591 | 0.97808 | 25.27046 |
May | 508.00000 | 27.00014 | 32.84716 | 0.23327 | 6.26623 |
June | 496.00000 | 27.00045 | 35.97789 | 0.33761 | 7.45690 |
July | 497.00000 | 27.00033 | 36.28466 | 0.39497 | 8.32481 |
August | 514.00000 | 27.00015 | 36.50680 | 0.43597 | 9.03051 |
September | 485.00000 | 27.00043 | 36.23331 | 0.26432 | 6.56867 |
October | 502.00000 | 27.00015 | 32.68793 | 0.91494 | 22.73452 |
November | 489.00000 | 27.00007 | 30.57370 | 0.91191 | 22.63488 |
December | 497.00000 | 27.00000 | 26.74723 | 0.89173 | 21.85796 |
Annual Sum or Average | 5943.00000 | 27.00014 | 31.66749 | 0.65640 | 15.84830 |
Minimum of Months | 454.00000 | 27.00000 | 26.74723 | 0.23327 | 6.26623 |
Maximum of Months | 514.00000 | 27.00045 | 36.50680 | 0.97808 | 25.27046 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99966 | 27.63119 | 0.69272 | 15.22233 |
February | 454.00000 | 27.00001 | 27.88336 | 0.72727 | 16.26778 |
March | 514.00000 | 27.00000 | 27.82468 | 0.75474 | 17.08516 |
April | 485.00000 | 27.00000 | 28.44617 | 0.84678 | 20.26100 |
May | 508.00000 | 27.00013 | 32.84921 | 0.13701 | 5.59710 |
June | 496.00000 | 27.00043 | 35.99724 | 0.22805 | 6.22827 |
July | 497.00000 | 27.00035 | 36.28928 | 0.26337 | 6.59359 |
August | 514.00000 | 27.00017 | 36.50557 | 0.28401 | 6.80303 |
September | 485.00000 | 27.00040 | 36.32098 | 0.17231 | 5.78596 |
October | 502.00000 | 27.00014 | 32.68878 | 0.80439 | 18.73342 |
November | 489.00000 | 27.00006 | 30.55070 | 0.76059 | 17.29200 |
December | 497.00000 | 27.00000 | 26.72867 | 0.70447 | 15.54748 |
Annual Sum or Average | 5943.00000 | 27.00011 | 31.67066 | 0.52929 | 12.57532 |
Minimum of Months | 454.00000 | 26.99966 | 26.72867 | 0.13701 | 5.59710 |
Maximum of Months | 514.00000 | 27.00043 | 36.50557 | 0.84678 | 20.26100 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.67445 | 28.24630 | 0.54572 | 12.20031 |
February | 454.00000 | 27.00001 | 27.89147 | 0.64271 | 13.93315 |
March | 514.00000 | 27.00000 | 27.82949 | 0.68350 | 14.98283 |
April | 485.00000 | 27.00000 | 28.44924 | 0.80445 | 18.90415 |
May | 508.00000 | 27.00034 | 32.86486 | 0.08846 | 5.56125 |
June | 496.00000 | 27.00043 | 36.01382 | 0.20365 | 6.14744 |
July | 497.00000 | 27.00035 | 36.30145 | 0.24388 | 6.53570 |
August | 514.00000 | 27.00018 | 36.51652 | 0.26148 | 6.65866 |
September | 485.00000 | 27.00046 | 36.38839 | 0.12808 | 5.65905 |
October | 502.00000 | 27.00013 | 32.72519 | 0.73632 | 16.59444 |
November | 489.00000 | 27.00006 | 30.57188 | 0.67943 | 14.89861 |
December | 497.00000 | 27.00000 | 26.73459 | 0.61706 | 13.20342 |
Annual Sum or Average | 5943.00000 | 26.97267 | 31.73940 | 0.46768 | 11.23801 |
Minimum of Months | 454.00000 | 26.67445 | 26.73459 | 0.08846 | 5.56125 |
Maximum of Months | 514.00000 | 27.00046 | 36.51652 | 0.80445 | 18.90415 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00071 | 31.41413 | 1.05563 | 28.53987 |
February | 454.00000 | 27.00196 | 31.21876 | 1.21813 | 36.15009 |
March | 514.00000 | 27.00232 | 30.82056 | 1.36684 | 43.75674 |
April | 485.00000 | 27.01423 | 30.96803 | 1.52105 | 52.04560 |
May | 508.00000 | 27.00036 | 33.44893 | 0.51763 | 10.67899 |
June | 496.00000 | 27.00055 | 35.83390 | 0.76827 | 17.45887 |
July | 497.00000 | 27.00033 | 36.17492 | 0.97977 | 25.30039 |
August | 514.00000 | 27.01598 | 36.44523 | 1.18025 | 34.31075 |
September | 485.00000 | 27.00076 | 35.95384 | 0.56399 | 11.72109 |
October | 502.00000 | 27.00043 | 33.58355 | 1.26477 | 38.48488 |
November | 489.00000 | 27.00115 | 32.45992 | 1.39262 | 45.12662 |
December | 497.00000 | 27.00285 | 30.58460 | 1.49887 | 50.84043 |
Annual Sum or Average | 5943.00000 | 27.00349 | 33.25794 | 1.10974 | 32.82947 |
Minimum of Months | 454.00000 | 27.00033 | 30.58460 | 0.51763 | 10.67899 |
Maximum of Months | 514.00000 | 27.01598 | 36.44523 | 1.52105 | 52.04560 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.45481 | 27.70428 | 0.38259 | 8.51659 |
February | 454.00000 | 24.44170 | 28.54544 | 0.38781 | 8.48390 |
March | 514.00000 | 24.37327 | 27.83740 | 0.37625 | 8.30069 |
April | 485.00000 | 24.50970 | 27.95872 | 0.41650 | 9.12855 |
May | 508.00000 | 24.46488 | 34.17699 | -0.4103 | 9.35979 |
June | 496.00000 | 24.43650 | 42.03334 | -0.3515 | 8.39591 |
July | 497.00000 | 24.58762 | 43.59015 | -0.2917 | 7.83847 |
August | 514.00000 | 24.46337 | 44.47153 | -0.3136 | 8.01145 |
September | 485.00000 | 24.51044 | 41.17683 | -0.3351 | 8.44068 |
October | 502.00000 | 24.53963 | 34.86477 | 0.46918 | 10.13987 |
November | 489.00000 | 24.53828 | 31.50067 | 0.44234 | 9.60989 |
December | 497.00000 | 24.49684 | 26.87543 | 0.39352 | 8.71030 |
Annual Sum or Average | 5943.00000 | 24.48450 | 34.27604 | 0.09414 | 8.74405 |
Minimum of Months | 454.00000 | 24.37327 | 26.87543 | -0.4103 | 7.83847 |
Maximum of Months | 514.00000 | 24.58762 | 44.47153 | 0.46918 | 10.13987 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.21545 | 32.07247 | 0.35131 | 8.30107 |
February | 454.00000 | 24.26444 | 30.57228 | 0.35883 | 7.88570 |
March | 514.00000 | 24.30776 | 29.51474 | 0.37657 | 8.25538 |
April | 485.00000 | 24.37413 | 28.97449 | 0.41277 | 8.87632 |
May | 508.00000 | 24.28742 | 35.40754 | -0.4468 | 9.62049 |
June | 496.00000 | 24.27878 | 42.95598 | -0.3722 | 8.30375 |
July | 497.00000 | 24.32909 | 44.89880 | -0.3326 | 7.73235 |
August | 514.00000 | 24.27215 | 45.25910 | -0.3357 | 7.71766 |
September | 485.00000 | 24.27043 | 42.37237 | -0.3917 | 8.61588 |
October | 502.00000 | 24.40429 | 36.34371 | 0.44669 | 9.54202 |
November | 489.00000 | 24.40788 | 33.33772 | 0.42255 | 9.09195 |
December | 497.00000 | 24.36408 | 28.99520 | 0.37526 | 8.27716 |
Annual Sum or Average | 5943.00000 | 24.31467 | 35.93848 | 0.06915 | 8.52091 |
Minimum of Months | 454.00000 | 24.21545 | 28.97449 | -0.4468 | 7.71766 |
Maximum of Months | 514.00000 | 24.40788 | 45.25910 | 0.44669 | 9.62049 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.43034 | 34.24811 | 0.13604 | 5.89021 |
February | 454.00000 | 23.56709 | 32.98504 | 0.16776 | 5.97682 |
March | 514.00000 | 23.72189 | 32.05659 | 0.20841 | 6.18045 |
April | 485.00000 | 24.07206 | 30.59820 | 0.30692 | 7.15769 |
May | 508.00000 | 24.04809 | 36.55657 | -0.5573 | 11.92542 |
June | 496.00000 | 24.12568 | 43.89060 | -0.4614 | 9.76153 |
July | 497.00000 | 24.16162 | 45.93687 | -0.4341 | 9.27447 |
August | 514.00000 | 24.12576 | 46.29640 | -0.4338 | 9.18181 |
September | 485.00000 | 24.06765 | 43.41500 | -0.4896 | 10.34646 |
October | 502.00000 | 23.92550 | 38.28153 | 0.30805 | 7.25406 |
November | 489.00000 | 23.67881 | 36.18043 | 0.21758 | 6.40495 |
December | 497.00000 | 23.24114 | 32.46524 | 0.07347 | 5.70178 |
Annual Sum or Average | 5943.00000 | 23.84897 | 37.78453 | -0.0825 | 7.93752 |
Minimum of Months | 454.00000 | 23.24114 | 30.59820 | -0.5573 | 5.70178 |
Maximum of Months | 514.00000 | 24.16162 | 46.29640 | 0.30805 | 11.92542 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.67947 | 35.99237 | -0.3131 | 9.31065 |
February | 454.00000 | 21.91788 | 36.42669 | -0.2445 | 8.22309 |
March | 514.00000 | 22.47670 | 35.17367 | -0.1068 | 6.50683 |
April | 485.00000 | 23.48024 | 32.32422 | 0.15585 | 6.32272 |
May | 508.00000 | 23.58939 | 38.12123 | -0.7256 | 17.34229 |
June | 496.00000 | 23.91730 | 44.72241 | -0.5349 | 11.59252 |
July | 497.00000 | 23.96568 | 46.68368 | -0.4995 | 10.86574 |
August | 514.00000 | 23.95648 | 46.97853 | -0.4955 | 10.52686 |
September | 485.00000 | 23.66342 | 45.35233 | -0.6378 | 14.46610 |
October | 502.00000 | 22.80443 | 41.72290 | 0.02354 | 6.19638 |
November | 489.00000 | 22.15621 | 40.06950 | -0.1637 | 7.19821 |
December | 497.00000 | 21.47857 | 35.14897 | -0.3708 | 9.99482 |
Annual Sum or Average | 5943.00000 | 22.93110 | 39.92308 | -0.3275 | 9.89452 |
Minimum of Months | 454.00000 | 21.47857 | 32.32422 | -0.7256 | 6.19638 |
Maximum of Months | 514.00000 | 23.96568 | 46.97853 | 0.15585 | 17.34229 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.48867 | 32.30463 | -0.1065 | 6.15947 |
February | 454.00000 | 22.75594 | 32.47558 | -0.0369 | 5.75363 |
March | 514.00000 | 23.34343 | 30.87223 | 0.10166 | 5.78112 |
April | 485.00000 | 23.89268 | 29.27933 | 0.25744 | 6.71740 |
May | 508.00000 | 23.84039 | 35.58476 | -0.6346 | 14.11480 |
June | 496.00000 | 24.11606 | 42.59127 | -0.4485 | 9.58862 |
July | 497.00000 | 24.22793 | 44.38902 | -0.3850 | 8.43646 |
August | 514.00000 | 24.13435 | 44.98373 | -0.4175 | 8.91017 |
September | 485.00000 | 23.84148 | 42.62817 | -0.5840 | 12.78327 |
October | 502.00000 | 23.49766 | 37.78235 | 0.18946 | 6.26611 |
November | 489.00000 | 23.14988 | 35.08238 | 0.07731 | 5.80990 |
December | 497.00000 | 22.68760 | 30.79212 | -0.0663 | 5.65964 |
Annual Sum or Average | 5943.00000 | 23.50341 | 36.60026 | -0.1728 | 8.01481 |
Minimum of Months | 454.00000 | 22.48867 | 29.27933 | -0.6346 | 5.65964 |
Maximum of Months | 514.00000 | 24.22793 | 44.98373 | 0.25744 | 14.11480 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.83552 | 32.26007 | -0.2283 | 6.98797 |
February | 454.00000 | 21.99538 | 32.66717 | -0.1775 | 6.56867 |
March | 514.00000 | 22.27454 | 31.63451 | -0.1073 | 6.11618 |
April | 485.00000 | 23.51886 | 29.34009 | 0.23890 | 7.40537 |
May | 508.00000 | 23.59153 | 35.46323 | -0.6188 | 15.58205 |
June | 496.00000 | 23.78753 | 43.07261 | -0.4715 | 11.51420 |
July | 497.00000 | 23.96863 | 44.86526 | -0.3859 | 10.02772 |
August | 514.00000 | 23.80669 | 45.55210 | -0.4337 | 10.70359 |
September | 485.00000 | 23.64266 | 42.51955 | -0.5426 | 13.74550 |
October | 502.00000 | 22.75840 | 38.57125 | 0.06397 | 6.28387 |
November | 489.00000 | 22.08657 | 36.10042 | -0.1333 | 6.10958 |
December | 497.00000 | 21.64066 | 31.40201 | -0.2824 | 7.18797 |
Annual Sum or Average | 5943.00000 | 22.91476 | 36.99333 | -0.2581 | 9.03898 |
Minimum of Months | 454.00000 | 21.64066 | 29.34009 | -0.6188 | 6.10958 |
Maximum of Months | 514.00000 | 23.96863 | 45.55210 | 0.23890 | 15.58205 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.19735 | 31.70685 | -0.1391 | 7.46016 |
February | 454.00000 | 22.46182 | 31.82312 | -0.0586 | 7.15643 |
March | 514.00000 | 22.48695 | 31.34115 | -0.0621 | 6.22463 |
April | 485.00000 | 23.64145 | 29.05381 | 0.27312 | 7.97698 |
May | 508.00000 | 23.40470 | 35.87130 | -0.7001 | 17.95203 |
June | 496.00000 | 23.73566 | 43.21846 | -0.5142 | 12.16650 |
July | 497.00000 | 23.94029 | 44.87880 | -0.4088 | 10.18190 |
August | 514.00000 | 23.99365 | 44.97050 | -0.3613 | 9.58299 |
September | 485.00000 | 23.81128 | 41.96111 | -0.4549 | 12.42248 |
October | 502.00000 | 23.06156 | 37.84966 | 0.15107 | 7.24138 |
November | 489.00000 | 22.52037 | 35.32233 | -0.0286 | 6.65324 |
December | 497.00000 | 21.95201 | 30.93474 | -0.2097 | 7.50333 |
Annual Sum or Average | 5943.00000 | 23.10393 | 36.62164 | -0.2118 | 9.39681 |
Minimum of Months | 454.00000 | 21.95201 | 29.05381 | -0.7001 | 6.22463 |
Maximum of Months | 514.00000 | 23.99365 | 44.97050 | 0.27312 | 17.95203 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.32544 | 31.13136 | -0.0876 | 6.22490 |
February | 454.00000 | 23.03234 | 30.55448 | 0.09873 | 6.22822 |
March | 514.00000 | 23.66647 | 28.93888 | 0.25262 | 7.19314 |
April | 485.00000 | 24.40453 | 27.61391 | 0.50236 | 11.15441 |
May | 508.00000 | 23.80931 | 34.85824 | -0.5073 | 12.68724 |
June | 496.00000 | 24.26085 | 41.69652 | -0.2410 | 7.74018 |
July | 497.00000 | 24.47034 | 43.34105 | -0.1215 | 6.95391 |
August | 514.00000 | 24.42423 | 43.68755 | -0.1222 | 6.76526 |
September | 485.00000 | 23.80068 | 41.96326 | -0.4596 | 11.48265 |
October | 502.00000 | 23.62594 | 36.46197 | 0.29539 | 7.82337 |
November | 489.00000 | 23.52998 | 33.02152 | 0.23412 | 7.08261 |
December | 497.00000 | 23.39965 | 28.24688 | 0.16280 | 6.32291 |
Annual Sum or Average | 5943.00000 | 23.73355 | 35.16653 | -0.0009 | 8.14061 |
Minimum of Months | 454.00000 | 22.32544 | 27.61391 | -0.5073 | 6.22490 |
Maximum of Months | 514.00000 | 24.47034 | 43.68755 | 0.50236 | 12.68724 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.01213 | 34.94683 | -0.4846 | 11.11413 |
February | 454.00000 | 21.12484 | 35.57375 | -0.4408 | 10.03297 |
March | 514.00000 | 21.76091 | 34.35604 | -0.2817 | 7.48054 |
April | 485.00000 | 22.94834 | 31.81062 | 0.01582 | 6.07535 |
May | 508.00000 | 23.14194 | 37.48974 | -0.8847 | 23.12355 |
June | 496.00000 | 23.74616 | 43.90721 | -0.6035 | 13.48113 |
July | 497.00000 | 23.83686 | 45.65863 | -0.5527 | 12.14973 |
August | 514.00000 | 23.73749 | 46.50361 | -0.5912 | 12.99138 |
September | 485.00000 | 23.24007 | 44.36949 | -0.8062 | 20.11581 |
October | 502.00000 | 22.12919 | 41.44786 | -0.1395 | 6.46100 |
November | 489.00000 | 21.31891 | 39.03020 | -0.3695 | 8.92711 |
December | 497.00000 | 20.69370 | 34.42323 | -0.5727 | 12.85202 |
Annual Sum or Average | 5943.00000 | 22.40047 | 39.15851 | -0.4769 | 12.08608 |
Minimum of Months | 454.00000 | 20.69370 | 31.81062 | -0.8847 | 6.07535 |
Maximum of Months | 514.00000 | 23.83686 | 46.50361 | 0.01582 | 23.12355 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.87145 | 33.43669 | -0.5115 | 11.13522 |
February | 385.00000 | 21.02353 | 33.91928 | -0.4542 | 9.89032 |
March | 433.00000 | 21.29335 | 33.43724 | -0.3733 | 8.38313 |
April | 410.00000 | 22.97342 | 30.42123 | 0.08922 | 7.13048 |
May | 430.00000 | 23.01268 | 36.43970 | -0.8303 | 23.26719 |
June | 418.00000 | 23.43339 | 43.72971 | -0.6100 | 15.94691 |
July | 422.00000 | 23.79196 | 45.10400 | -0.4748 | 12.94156 |
August | 433.00000 | 23.56500 | 45.93796 | -0.5408 | 13.79040 |
September | 410.00000 | 23.20508 | 43.27487 | -0.7133 | 19.36485 |
October | 427.00000 | 21.78686 | 40.61335 | -0.1888 | 6.96647 |
November | 417.00000 | 21.02223 | 38.00510 | -0.4293 | 9.38045 |
December | 422.00000 | 20.56857 | 33.06710 | -0.6016 | 13.34208 |
Annual Sum or Average | 5034.00000 | 22.21753 | 38.15009 | -0.4710 | 12.64908 |
Minimum of Months | 385.00000 | 20.56857 | 30.42123 | -0.8303 | 6.96647 |
Maximum of Months | 433.00000 | 23.79196 | 45.93796 | 0.08922 | 23.26719 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.71763 | 32.49412 | -0.2742 | 8.90248 |
February | 454.00000 | 21.96040 | 32.89639 | -0.1924 | 8.45068 |
March | 514.00000 | 21.75258 | 33.10155 | -0.2479 | 7.46522 |
April | 485.00000 | 23.22149 | 30.12150 | 0.16351 | 7.84211 |
May | 508.00000 | 22.96285 | 36.92563 | -0.8510 | 23.96905 |
June | 496.00000 | 23.34139 | 44.33027 | -0.6569 | 16.69193 |
July | 497.00000 | 23.61856 | 45.82011 | -0.5345 | 13.74810 |
August | 514.00000 | 23.69112 | 45.90152 | -0.4773 | 12.49439 |
September | 485.00000 | 23.56899 | 42.51051 | -0.5360 | 15.48853 |
October | 502.00000 | 22.52122 | 39.42609 | 0.02044 | 7.50823 |
November | 489.00000 | 21.77311 | 37.14484 | -0.2223 | 8.10422 |
December | 497.00000 | 21.14934 | 32.56462 | -0.4375 | 10.74468 |
Annual Sum or Average | 5943.00000 | 22.60954 | 37.81593 | -0.3564 | 11.81907 |
Minimum of Months | 454.00000 | 21.14934 | 30.12150 | -0.8510 | 7.46522 |
Maximum of Months | 514.00000 | 23.69112 | 45.90152 | 0.16351 | 23.96905 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.04140 | 33.55664 | -0.4515 | 9.99470 |
February | 454.00000 | 21.28807 | 34.01614 | -0.3657 | 8.88885 |
March | 514.00000 | 21.46258 | 33.44075 | -0.3124 | 7.69051 |
April | 485.00000 | 22.83545 | 30.78639 | 0.06644 | 6.94358 |
May | 508.00000 | 22.87619 | 37.03335 | -0.8580 | 24.37029 |
June | 496.00000 | 23.46597 | 43.93662 | -0.5723 | 14.87374 |
July | 497.00000 | 23.68459 | 45.59532 | -0.4760 | 12.78928 |
August | 514.00000 | 23.56189 | 46.32060 | -0.5244 | 13.14920 |
September | 485.00000 | 22.93153 | 44.21804 | -0.7932 | 21.55583 |
October | 502.00000 | 21.86894 | 40.82992 | -0.1533 | 6.64161 |
November | 489.00000 | 21.18840 | 38.10581 | -0.3699 | 8.53614 |
December | 497.00000 | 20.75385 | 33.11434 | -0.5401 | 11.64555 |
Annual Sum or Average | 5943.00000 | 22.25351 | 38.45159 | -0.4472 | 12.28278 |
Minimum of Months | 454.00000 | 20.75385 | 30.78639 | -0.8580 | 6.64161 |
Maximum of Months | 514.00000 | 23.68459 | 46.32060 | 0.06644 | 24.37029 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.25578 | 36.51247 | -0.7237 | 18.44110 |
February | 454.00000 | 20.31063 | 37.37079 | -0.6867 | 17.28067 |
March | 514.00000 | 20.92524 | 36.13267 | -0.5182 | 11.80495 |
April | 485.00000 | 22.22698 | 33.32219 | -0.1658 | 7.61651 |
May | 508.00000 | 22.46062 | 39.07589 | -1.1204 | 33.85965 |
June | 496.00000 | 23.38979 | 44.94094 | -0.7254 | 18.01779 |
July | 497.00000 | 23.53655 | 46.49796 | -0.6543 | 15.89282 |
August | 514.00000 | 23.44448 | 47.39374 | -0.6939 | 16.66306 |
September | 485.00000 | 22.65871 | 46.00701 | -1.0104 | 28.98380 |
October | 502.00000 | 21.13543 | 44.05570 | -0.4012 | 9.87962 |
November | 489.00000 | 20.47400 | 41.04631 | -0.6181 | 15.09080 |
December | 497.00000 | 20.03815 | 35.82467 | -0.7910 | 20.84021 |
Annual Sum or Average | 5943.00000 | 21.74908 | 40.71110 | -0.6763 | 17.87302 |
Minimum of Months | 454.00000 | 20.03815 | 33.32219 | -1.1204 | 7.61651 |
Maximum of Months | 514.00000 | 23.53655 | 47.39374 | -0.1658 | 33.85965 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.32002 | 35.15105 | -0.6978 | 17.22966 |
February | 454.00000 | 20.44276 | 35.97391 | -0.6397 | 15.37930 |
March | 514.00000 | 20.84027 | 35.04384 | -0.5219 | 11.51237 |
April | 485.00000 | 22.67806 | 31.32893 | 0.01102 | 7.63045 |
May | 508.00000 | 22.72087 | 37.59160 | -0.9350 | 27.64079 |
June | 496.00000 | 23.26805 | 44.52890 | -0.6567 | 17.80611 |
July | 497.00000 | 23.65739 | 45.73660 | -0.5076 | 13.93296 |
August | 514.00000 | 23.48961 | 46.48610 | -0.5556 | 14.44457 |
September | 485.00000 | 23.01116 | 44.18631 | -0.7852 | 22.06963 |
October | 502.00000 | 21.24047 | 42.77303 | -0.3476 | 9.22743 |
November | 489.00000 | 20.49574 | 39.90009 | -0.6042 | 14.22571 |
December | 497.00000 | 20.08283 | 34.71366 | -0.7760 | 20.18976 |
Annual Sum or Average | 5943.00000 | 21.86331 | 39.48496 | -0.5853 | 15.95133 |
Minimum of Months | 454.00000 | 20.08283 | 31.32893 | -0.9350 | 7.63045 |
Maximum of Months | 514.00000 | 23.65739 | 46.48610 | 0.01102 | 27.64079 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.91700 | 34.02479 | -0.5194 | 13.67338 |
February | 454.00000 | 21.19160 | 34.54134 | -0.4260 | 12.24312 |
March | 514.00000 | 21.10418 | 34.58833 | -0.4458 | 10.61990 |
April | 485.00000 | 22.72910 | 31.18987 | 0.03128 | 8.28168 |
May | 508.00000 | 22.49040 | 38.09895 | -1.0261 | 31.80931 |
June | 496.00000 | 23.00420 | 45.25343 | -0.7700 | 21.26796 |
July | 497.00000 | 23.33466 | 46.57359 | -0.6276 | 17.41367 |
August | 514.00000 | 23.44261 | 46.59854 | -0.5618 | 15.51734 |
September | 485.00000 | 23.20784 | 43.53289 | -0.6727 | 20.57555 |
October | 502.00000 | 21.85300 | 41.31255 | -0.1736 | 8.84753 |
November | 489.00000 | 21.04052 | 38.83333 | -0.4463 | 11.79025 |
December | 497.00000 | 20.44694 | 34.01620 | -0.6636 | 17.03928 |
Annual Sum or Average | 5943.00000 | 22.06823 | 39.09041 | -0.5272 | 15.79855 |
Minimum of Months | 454.00000 | 20.44694 | 31.18987 | -1.0261 | 8.28168 |
Maximum of Months | 514.00000 | 23.44261 | 46.59854 | 0.03128 | 31.80931 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.49253 | 34.64707 | -0.6383 | 15.41607 |
February | 454.00000 | 20.74032 | 35.25860 | -0.5450 | 13.24481 |
March | 514.00000 | 20.99736 | 34.58426 | -0.4651 | 10.40806 |
April | 485.00000 | 22.33605 | 31.85832 | -0.0641 | 7.74573 |
May | 508.00000 | 22.42824 | 38.16321 | -1.0219 | 31.90317 |
June | 496.00000 | 23.12645 | 44.84403 | -0.6845 | 19.11103 |
July | 497.00000 | 23.40264 | 46.32246 | -0.5679 | 16.11528 |
August | 514.00000 | 23.26679 | 47.12491 | -0.6224 | 16.55922 |
September | 485.00000 | 22.51929 | 45.35846 | -0.9428 | 27.96756 |
October | 502.00000 | 21.30351 | 42.46375 | -0.3205 | 8.57103 |
November | 489.00000 | 20.69733 | 39.32180 | -0.5367 | 12.40528 |
December | 497.00000 | 20.26050 | 34.19984 | -0.7136 | 17.65766 |
Annual Sum or Average | 5943.00000 | 21.80551 | 39.54958 | -0.5947 | 16.45196 |
Minimum of Months | 454.00000 | 20.26050 | 31.85832 | -1.0219 | 7.74573 |
Maximum of Months | 514.00000 | 23.40264 | 47.12491 | -0.0641 | 31.90317 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.184809E+09 | 2064.05 | 24-JAN-06:08 | 25.08 | 0.950377E+09 | 0.00 | 0.113519E+10 | 0.17 | 5.26 | 31-JAN-06:30 | 0.00 | 0.00 |
February | 0.372237E+09 | 2063.91 | 17-FEB-07:00 | 50.55 | 0.191583E+10 | 0.00 | 0.228806E+10 | 0.39 | 5.26 | 13-FEB-14:50 | 0.00 | 0.00 |
March | 0.368510E+09 | 2063.81 | 21-MAR-05:20 | 50.11 | 0.189794E+10 | 0.00 | 0.226645E+10 | 0.35 | 5.26 | 03-MAR-16:30 | 0.00 | 0.00 |
April | 0.698851E+10 | 73240.44 | 28-APR-15:00 | 82.75 | 0.450190E+11 | 0.00 | 0.520075E+11 | 0.66 | 7.84 | 28-APR-15:00 | 0.00 | 0.00 |
May | 0.814891E+10 | 75377.78 | 22-MAY-16:00 | 79.89 | 0.542604E+11 | 0.00 | 0.624093E+11 | 0.64 | 7.77 | 23-MAY-12:20 | 0.00 | 0.00 |
June | 0.224303E+11 | 101176.75 | 13-JUN-16:00 | 188.39 | 0.152535E+12 | 0.00 | 0.174965E+12 | 1.59 | 7.87 | 27-JUN-05:02 | 0.00 | 0.00 |
July | 0.394561E+11 | 89163.33 | 21-JUL-15:40 | 329.60 | 0.265265E+12 | 0.00 | 0.304721E+12 | 2.70 | 7.79 | 24-JUL-15:00 | 0.00 | 0.00 |
August | 0.523121E+11 | 87045.37 | 14-AUG-15:00 | 398.94 | 0.353480E+12 | 0.00 | 0.405792E+12 | 3.35 | 7.80 | 08-AUG-13:00 | 0.00 | 0.00 |
September | 0.268854E+11 | 78867.36 | 12-SEP-14:50 | 239.17 | 0.178769E+12 | 0.00 | 0.205654E+12 | 2.00 | 7.79 | 11-SEP-12:40 | 0.00 | 0.00 |
October | 0.212247E+10 | 38037.38 | 07-OCT-15:00 | 36.00 | 0.113692E+11 | 0.00 | 0.134916E+11 | 0.25 | 6.67 | 06-OCT-15:30 | 0.00 | 0.00 |
November | 0.153178E+09 | 11625.84 | 24-NOV-12:00 | 18.08 | 0.786832E+09 | 0.00 | 0.940009E+09 | 0.13 | 5.26 | 20-NOV-06:40 | 0.00 | 0.00 |
December | 0.226177E+09 | 2064.85 | 26-DEC-04:20 | 30.69 | 0.116329E+10 | 0.00 | 0.138947E+10 | 0.21 | 5.26 | 04-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.159649E+12 | 1529.27 | 0.106741E+13 | 0.00 | 0.122706E+13 | 1.04 | 0.00 | 0.00 | ||||
Minimum of Months | 0.153178E+09 | 2063.81 | 18.08 | 0.786832E+09 | 0.00 | 0.940009E+09 | 0.13 | 5.26 | 0.00 | 0.00 | ||
Maximum of Months | 0.523121E+11 | 101176.75 | 398.94 | 0.353480E+12 | 0.00 | 0.405792E+12 | 3.35 | 7.87 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 43944262.03 | 73240.44 | 28-APR-15:00 | 0.17 | 0.344436E+09 | 0.00 | 0.388380E+09 | 0.00 | 7.84 | 28-APR-15:00 | 0.00 | 0.00 |
May | 0.787435E+09 | 75377.78 | 22-MAY-16:00 | 3.17 | 0.595536E+10 | 0.00 | 0.674279E+10 | 0.03 | 7.70 | 22-MAY-13:40 | 0.00 | 0.00 |
June | 0.497730E+10 | 101176.75 | 13-JUN-16:00 | 18.90 | 0.373598E+11 | 0.00 | 0.423371E+11 | 0.20 | 7.75 | 20-JUN-14:10 | 0.00 | 0.00 |
July | 0.474101E+10 | 89163.33 | 21-JUL-15:40 | 18.20 | 0.357458E+11 | 0.00 | 0.404868E+11 | 0.18 | 7.74 | 19-JUL-16:00 | 0.00 | 0.00 |
August | 0.401791E+10 | 87045.37 | 14-AUG-15:00 | 15.67 | 0.302774E+11 | 0.00 | 0.342953E+11 | 0.16 | 7.75 | 21-AUG-15:30 | 0.00 | 0.00 |
September | 0.325571E+10 | 78867.36 | 12-SEP-14:50 | 13.17 | 0.247404E+11 | 0.00 | 0.279961E+11 | 0.14 | 7.77 | 12-SEP-14:00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.178233E+11 | 69.27 | 0.134423E+12 | 0.00 | 0.152247E+12 | 0.06 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.497730E+10 | 101176.75 | 18.90 | 0.373598E+11 | 0.00 | 0.423371E+11 | 0.20 | 7.84 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.122302E+11 | 744.00 | 18673.36 | 29-JAN-06:00 | 181940.80 | 19-JAN-16:10 | 21.75 | 18.33 | 14.07 |
February | 0.179720E+11 | 672.00 | 21374.70 | 07-FEB-15:00 | 326261.47 | 19-FEB-17:07 | 24.64 | 18.33 | 14.07 |
March | 0.461330E+11 | 744.00 | 46274.23 | 25-MAR-13:00 | 591877.38 | 31-MAR-24:00 | 27.51 | 18.33 | 14.07 |
April | 0.855541E+11 | 720.00 | 49248.27 | 15-APR-13:10 | 677929.95 | 30-APR-19:23 | 30.95 | 18.78 | 14.07 |
May | 0.290809E+11 | 744.00 | 49248.27 | 11-MAY-14:50 | 319845.82 | 31-MAY-24:00 | 22.18 | 18.46 | 14.07 |
June | 0.822273E+11 | 720.00 | 49248.27 | 01-JUN-11:50 | 455128.39 | 30-JUN-24:00 | 25.74 | 19.06 | 14.07 |
July | 0.117009E+12 | 744.00 | 49248.27 | 01-JUL-12:30 | 599240.05 | 31-JUL-24:00 | 29.81 | 20.21 | 14.07 |
August | 0.127632E+12 | 744.00 | 49248.27 | 01-AUG-06:10 | 667529.72 | 20-AUG-17:12 | 33.80 | 21.35 | 14.07 |
September | 0.566628E+11 | 720.00 | 49248.27 | 01-SEP-09:40 | 316906.34 | 30-SEP-24:00 | 22.62 | 18.82 | 14.07 |
October | 0.471754E+11 | 744.00 | 49248.27 | 05-OCT-13:50 | 452173.82 | 31-OCT-24:00 | 24.82 | 18.36 | 14.07 |
November | 0.498417E+11 | 720.00 | 49248.27 | 24-NOV-11:20 | 469229.70 | 24-NOV-12:10 | 27.50 | 18.33 | 14.07 |
December | 0.548449E+11 | 744.00 | 47806.88 | 23-DEC-11:00 | 594983.94 | 21-DEC-22:10 | 30.19 | 18.33 | 14.07 |
Annual Sum or Average | 0.726363E+12 | 8760.00 | 26.81 | 18.90 | 14.07 | ||||
Minimum of Months | 0.122302E+11 | 672.00 | 18673.36 | 181940.80 | 21.75 | 18.33 | 14.07 | ||
Maximum of Months | 0.127632E+12 | 744.00 | 49248.27 | 677929.95 | 33.80 | 21.35 | 14.07 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 192495.64 | 10-JAN-05:43 | 20.92 | 20.91 | 0.16 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 192952.97 | 17-FEB-05:53 | 21.03 | 21.02 | 0.48 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 192319.47 | 08-MAR-06:50 | 20.93 | 20.93 | 0.59 |
April | 50731207.00 | 38.30 | 1597.55 | 28-APR-15:10 | 817704.42 | 28-APR-14:50 | 21.07 | 20.96 | 3.94 |
May | 0.157710E+09 | 48.57 | 14310.78 | 22-MAY-14:10 | 920272.72 | 22-MAY-13:30 | 21.16 | 21.03 | 4.23 |
June | 0.119117E+10 | 131.08 | 14310.78 | 12-JUN-12:20 | 924886.06 | 20-JUN-14:50 | 21.46 | 21.08 | 11.55 |
July | 0.129664E+10 | 252.50 | 14310.78 | 10-JUL-08:30 | 904978.31 | 12-JUL-15:40 | 21.73 | 21.10 | 19.82 |
August | 0.131226E+10 | 339.06 | 14310.78 | 14-AUG-09:50 | 938593.89 | 28-AUG-15:20 | 21.96 | 21.13 | 25.11 |
September | 0.612400E+09 | 172.38 | 14310.78 | 11-SEP-13:40 | 895065.46 | 13-SEP-12:40 | 21.55 | 21.10 | 14.48 |
October | 4730569.00 | 16.12 | 192.41 | 11-OCT-15:00 | 304634.24 | 06-OCT-15:30 | 21.06 | 21.03 | 1.65 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 192203.48 | 20-NOV-05:56 | 20.96 | 20.95 | 0.14 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 189284.62 | 29-DEC-06:00 | 21.03 | 21.03 | 0.26 |
Annual Sum or Average | 0.462564E+10 | 998.01 | 21.24 | 21.02 | 6.91 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 189284.62 | 20.92 | 20.91 | 0.14 | ||
Maximum of Months | 0.131226E+10 | 339.06 | 14310.78 | 938593.89 | 21.96 | 21.13 | 25.11 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 20.92 | 20.92 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.03 | 21.03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.93 | 20.93 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.07 | 21.07 | 0.00 |
May | 57887665.92 | 2.00 | 14310.78 | 22-MAY-14:10 | 920272.72 | 22-MAY-13:30 | 21.16 | 21.15 | 0.13 |
June | 0.550707E+09 | 11.88 | 14310.78 | 12-JUN-13:30 | 924886.06 | 20-JUN-14:50 | 21.46 | 21.40 | 0.82 |
July | 0.400877E+09 | 11.33 | 14310.78 | 10-JUL-08:50 | 904978.31 | 12-JUL-15:40 | 21.73 | 21.67 | 0.75 |
August | 0.266973E+09 | 10.17 | 14310.78 | 14-AUG-10:20 | 938593.89 | 28-AUG-15:20 | 21.96 | 21.90 | 0.68 |
September | 0.170949E+09 | 4.83 | 14310.78 | 11-SEP-14:00 | 895065.46 | 13-SEP-12:40 | 21.55 | 21.53 | 0.33 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.06 | 21.06 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.96 | 20.96 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.03 | 21.03 | 0.00 |
Annual Sum or Average | 0.144739E+10 | 40.21 | 21.24 | 21.22 | 0.23 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 | 20.92 | 0.00 | ||
Maximum of Months | 0.550707E+09 | 11.88 | 14310.78 | 938593.89 | 21.96 | 21.90 | 0.82 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.209031E+12 | 0.00 | 429.18 | 1033021.05 | 10-JAN-05:01 | 0.00 | 26.67 | 57.55 | 0.37 | 0.00 | 0.04 | 0.51 | 10-JAN-05:01 |
February | 0.131797E+12 | 0.00 | 373.00 | 1028956.95 | 17-FEB-06:02 | 0.00 | 25.74 | 56.13 | 0.25 | 0.00 | 0.03 | 0.51 | 17-FEB-06:02 |
March | 0.890114E+11 | 0.00 | 379.02 | 959094.33 | 04-MAR-06:02 | 0.00 | 23.93 | 52.40 | 0.15 | 0.00 | 0.02 | 0.47 | 04-MAR-06:02 |
April | 0.100824E+11 | 0.00 | 116.79 | 229861.80 | 08-APR-06:05 | 0.00 | 23.43 | 32.57 | 0.02 | 0.00 | 0.00 | 0.11 | 08-APR-06:05 |
May | 0.510487E+10 | 0.00 | 105.06 | 624850.06 | 05-MAY-05:03 | 0.00 | 21.51 | 29.66 | 0.01 | 0.00 | 0.00 | 0.31 | 05-MAY-05:03 |
June | 0.205435E+09 | 0.00 | 30.28 | 69964.13 | 08-JUN-05:03 | 0.00 | 20.55 | 23.03 | 0.00 | 0.00 | 0.00 | 0.03 | 08-JUN-05:03 |
July | 74214766.25 | 0.00 | 15.27 | 5104.71 | 01-JUL-05:03 | 0.00 | 19.99 | 21.21 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-05:03 |
August | 24434823.37 | 0.00 | 6.72 | 3253.48 | 12-AUG-05:10 | 0.00 | 19.81 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 12-AUG-05:10 |
September | 0.105562E+10 | 0.00 | 60.96 | 63786.20 | 21-SEP-06:10 | 0.00 | 20.19 | 25.21 | 0.00 | 0.00 | 0.00 | 0.03 | 21-SEP-06:10 |
October | 0.282847E+11 | 0.00 | 270.61 | 673984.97 | 28-OCT-05:02 | 0.00 | 22.50 | 43.23 | 0.04 | 0.00 | 0.01 | 0.33 | 28-OCT-05:02 |
November | 0.102459E+12 | 0.00 | 381.63 | 1093834.03 | 27-NOV-05:01 | 0.00 | 23.51 | 53.25 | 0.18 | 0.00 | 0.02 | 0.54 | 27-NOV-05:01 |
December | 0.232701E+12 | 0.00 | 449.36 | 1053002.48 | 27-DEC-06:02 | 0.00 | 26.69 | 59.20 | 0.40 | 0.00 | 0.04 | 0.52 | 27-DEC-06:02 |
Annual Sum or Average | 0.809831E+12 | 0.00 | 2617.88 | 0.00 | 22.86 | 39.41 | 0.12 | 0.00 | 0.01 | ||||
Minimum of Months | 24434823.37 | 0.00 | 6.72 | 3253.48 | 0.00 | 19.81 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.232701E+12 | 0.00 | 449.36 | 1093834.03 | 0.00 | 26.69 | 59.20 | 0.40 | 0.00 | 0.04 | 0.54 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 21.75 | 21.75 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 24.64 | 24.64 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.51 | 27.51 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 30.95 | 30.95 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 22.18 | 22.18 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 25.74 | 25.74 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 29.81 | 29.81 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 33.80 | 33.80 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 22.62 | 22.62 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 24.82 | 24.82 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.50 | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 30.19 | 30.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 26.81 | 26.81 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 | 21.75 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 | 33.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2220.89 | 0.00 | 1.21 | 2220.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 02-JAN-08:65 | 0.97 | 02-JAN-08:65 | 0.00 | 0.00 | 0.00 |
February | 223.15 | 0.00 | 0.17 | 223.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 04-FEB-14:40 | 0.37 | 04-FEB-14:40 | 0.00 | 0.00 | 0.00 |
March | 3185.11 | 0.00 | 2.21 | 3185.11 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 | 20-MAR-04:47 | 1.07 | 20-MAR-04:47 | 0.00 | 0.00 | 0.00 |
April | 0.439389E+10 | 0.00 | 54.49 | 0.438864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78510.00 | 30-APR-14:52 | 78510.00 | 30-APR-14:52 | 0.00 | 0.00 | 0.00 |
May | 0.545442E+10 | 0.00 | 66.52 | 0.545442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95691.42 | 22-MAY-15:00 | 95691.42 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.180485E+11 | 0.00 | 174.12 | 0.176245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122967.03 | 13-JUN-16:00 | 113631.44 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.304760E+11 | 0.00 | 308.50 | 0.303459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116532.32 | 21-JUL-15:20 | 116532.32 | 21-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.403580E+11 | 0.00 | 379.80 | 0.399995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121201.36 | 14-AUG-15:10 | 121201.36 | 14-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.187667E+11 | 0.00 | 211.44 | 0.187064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86544.84 | 13-SEP-14:20 | 86544.84 | 13-SEP-14:20 | 0.00 | 0.00 | 0.00 |
October | 0.982622E+09 | 0.00 | 23.75 | 0.982622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24007.20 | 11-OCT-15:00 | 24007.20 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 15664202.89 | 0.00 | 0.83 | 15664202.89 | 0.00 | 0.00 | 0.00 | 0.00 | 9168.98 | 24-NOV-12:00 | 9168.98 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 957.97 | 0.00 | 0.85 | 957.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 19-DEC-05:25 | 0.39 | 19-DEC-05:25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118496E+12 | 0.00 | 1223.88 | 0.117518E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 223.15 | 0.00 | 0.17 | 223.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 0.37 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.403580E+11 | 0.00 | 379.80 | 0.399995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122967.03 | 121201.36 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 69830.70 | 0.00 | 24.49 | 69830.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 | 15-JAN-13:58 | 3.96 | 15-JAN-13:58 | 0.00 | 0.00 | 0.00 |
February | 121828.74 | 0.00 | 50.38 | 121828.74 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 04-FEB-14:40 | 2.72 | 04-FEB-14:40 | 0.00 | 0.00 | 0.00 |
March | 144988.29 | 0.00 | 48.75 | 144988.29 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 | 27-MAR-05:03 | 4.32 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.361742E+11 | 0.00 | 76.78 | 0.361463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 763059.02 | 30-APR-15:21 | 763059.02 | 30-APR-15:21 | 0.00 | 0.00 | 0.00 |
May | 0.465161E+11 | 0.00 | 75.70 | 0.465161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 818001.83 | 22-MAY-15:00 | 818001.83 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.149868E+12 | 0.00 | 171.30 | 0.146395E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1121838.73 | 13-JUN-16:00 | 1022645.21 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.243175E+12 | 0.00 | 294.77 | 0.242560E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1043395.28 | 21-JUL-15:40 | 1043395.28 | 21-JUL-15:40 | 0.00 | 0.00 | 0.00 |
August | 0.310482E+12 | 0.00 | 372.42 | 0.308623E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 973616.35 | 14-AUG-15:50 | 973616.35 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 |
September | 0.165378E+12 | 0.00 | 224.77 | 0.164262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 815248.94 | 13-SEP-14:40 | 815248.94 | 13-SEP-14:40 | 0.00 | 0.00 | 0.00 |
October | 0.818616E+10 | 0.00 | 35.09 | 0.818616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201945.47 | 07-OCT-15:00 | 201945.47 | 07-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 67609836.05 | 0.00 | 17.82 | 67609836.05 | 0.00 | 0.00 | 0.00 | 0.00 | 47971.86 | 24-NOV-12:00 | 47971.86 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 75855.96 | 0.00 | 29.39 | 75855.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26-DEC-06:03 | 2.33 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.959847E+12 | 0.00 | 1421.67 | 0.952756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 69830.70 | 0.00 | 17.82 | 69830.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 2.33 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.310482E+12 | 0.00 | 372.42 | 0.308623E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1121838.73 | 1043395.28 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 230.66 | 0.00 | 0.17 | 230.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 | 01-JAN-20:00 | 0.38 | 01-JAN-20:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 53.57 | 0.00 | 0.03 | 53.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 06-MAR-05:22 | 0.45 | 06-MAR-05:22 | 0.00 | 0.00 | 0.00 |
April | 0.352872E+10 | 0.00 | 51.44 | 0.352872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71566.81 | 30-APR-16:22 | 71566.81 | 30-APR-16:22 | 0.00 | 0.00 | 0.00 |
May | 0.480583E+10 | 0.00 | 64.89 | 0.480583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92073.07 | 22-MAY-15:00 | 92073.07 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.157777E+11 | 0.00 | 158.79 | 0.154129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133732.80 | 13-JUN-16:00 | 123908.59 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.249995E+11 | 0.00 | 278.90 | 0.249498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123014.56 | 21-JUL-15:40 | 123014.56 | 21-JUL-15:40 | 0.00 | 0.00 | 0.00 |
August | 0.300505E+11 | 0.00 | 360.47 | 0.299521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113610.59 | 14-AUG-16:00 | 113610.59 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.151489E+11 | 0.00 | 196.79 | 0.150879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84365.75 | 13-SEP-15:20 | 84365.75 | 13-SEP-15:20 | 0.00 | 0.00 | 0.00 |
October | 0.610181E+09 | 0.00 | 22.50 | 0.610181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19343.97 | 07-OCT-15:00 | 19343.97 | 07-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 5113630.04 | 0.00 | 0.67 | 5113630.04 | 0.00 | 0.00 | 0.00 | 0.00 | 3850.03 | 24-NOV-12:00 | 3850.03 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 29134.00 | 0.00 | 1.15 | 29134.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.11 | 26-DEC-04:16 | 304.11 | 26-DEC-04:16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.949265E+11 | 0.00 | 1135.82 | 0.943526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.300505E+11 | 0.00 | 360.47 | 0.299521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133732.80 | 123908.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 6327.39 | 0.00 | 0.17 | 6327.39 | 0.00 | 0.00 | 0.00 | 0.00 | 10.55 | 16-FEB-20:30 | 10.55 | 16-FEB-20:30 | 0.00 | 0.00 | 0.00 |
March | 1228608.27 | 0.00 | 0.07 | 608804.95 | 0.00 | 0.00 | 0.00 | 0.00 | 6085.90 | 18-MAR-05:03 | 2765.04 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.731211E+09 | 0.00 | 17.87 | 0.731211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28596.35 | 28-APR-15:00 | 28596.35 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.228274E+10 | 0.00 | 32.38 | 0.228274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58418.02 | 22-MAY-15:00 | 58418.02 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.822478E+10 | 0.00 | 86.68 | 0.817648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61308.29 | 12-JUN-15:00 | 61308.29 | 12-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.133619E+11 | 0.00 | 175.66 | 0.132611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66630.16 | 10-JUL-11:00 | 66630.16 | 10-JUL-11:00 | 0.00 | 0.00 | 0.00 |
August | 0.174902E+11 | 0.00 | 255.28 | 0.174500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66280.67 | 14-AUG-16:00 | 66280.67 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.849575E+10 | 0.00 | 117.92 | 0.847371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49803.60 | 25-SEP-13:00 | 49803.60 | 25-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.139882E+09 | 0.00 | 8.88 | 0.128104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21688.27 | 20-OCT-05:03 | 9849.73 | 13-OCT-05:03 | 0.00 | 0.00 | 0.00 |
November | 13067293.49 | 0.00 | 0.76 | 12084935.21 | 0.00 | 0.00 | 0.00 | 0.00 | 9577.19 | 24-NOV-06:03 | 8385.94 | 15-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.507407E+11 | 0.00 | 695.69 | 0.505160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.174902E+11 | 0.00 | 255.28 | 0.174500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66630.16 | 66630.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.321916E+12 | 0.805814E+11 | 744.00 | 0.321897E+12 | 18454684.97 | 0.00 | 0.34 | 20-JAN-22:03 | 0.31 | 10-JAN-08:00 | 124755.64 | 19-JAN-22:03 | 124755.64 | 19-JAN-22:03 | 1062.96 | 18-JAN-17:00 | 31234.61 | 20-JAN-22:03 | 0.00 |
February | 0.511826E+12 | 0.121671E+12 | 672.00 | 0.511815E+12 | 11302972.31 | 0.00 | 0.56 | 13-FEB-22:03 | 0.53 | 01-FEB-18:10 | 216247.23 | 23-FEB-22:03 | 216247.23 | 23-FEB-22:03 | 1198.52 | 08-FEB-16:40 | 51421.59 | 10-FEB-22:03 | 0.00 |
March | 0.813504E+12 | 0.185507E+12 | 744.00 | 0.813502E+12 | 1739878.43 | 0.00 | 0.95 | 31-MAR-24:00 | 0.73 | 20-MAR-06:30 | 394642.49 | 31-MAR-24:00 | 394642.49 | 31-MAR-24:00 | 1818.55 | 20-MAR-06:10 | 86943.77 | 31-MAR-24:00 | 0.00 |
April | 0.102851E+13 | 0.229564E+12 | 720.00 | 0.102851E+13 | 0.00 | 0.00 | 1.00 | 29-APR-17:02 | 0.37 | 30-APR-23:57 | 408730.14 | 30-APR-19:43 | 408730.14 | 30-APR-19:43 | 0.00 | 11-APR-21:10 | 120270.03 | 30-APR-18:10 | 0.00 |
May | 0.328870E+12 | 0.818970E+11 | 744.00 | 0.328362E+12 | 0.508329E+09 | 0.00 | 0.54 | 31-MAY-24:00 | 0.31 | 05-MAY-06:05 | 211864.62 | 31-MAY-24:00 | 211864.62 | 31-MAY-24:00 | 3892.64 | 23-MAY-13:00 | 49373.29 | 31-MAY-24:00 | 0.00 |
June | 0.558980E+12 | 0.133497E+12 | 720.00 | 0.556669E+12 | 0.231128E+10 | 0.00 | 0.74 | 30-JUN-24:00 | 0.53 | 01-JUN-06:20 | 303254.46 | 30-JUN-24:00 | 303254.46 | 30-JUN-24:00 | 5660.80 | 26-JUN-17:50 | 72787.15 | 13-JUN-17:00 | 0.00 |
July | 0.825806E+12 | 0.196410E+12 | 744.00 | 0.822952E+12 | 0.285402E+10 | 0.00 | 0.93 | 31-JUL-24:00 | 0.73 | 01-JUL-06:30 | 395968.72 | 31-JUL-24:00 | 395968.72 | 31-JUL-24:00 | 5874.83 | 18-JUL-16:00 | 111026.16 | 22-JUL-18:00 | 0.00 |
August | 0.107103E+13 | 0.254554E+12 | 744.00 | 0.106831E+13 | 0.271514E+10 | 0.00 | 1.00 | 14-AUG-12:20 | 0.37 | 31-AUG-24:00 | 406602.48 | 17-AUG-15:30 | 403970.86 | 14-AUG-19:40 | 6021.19 | 11-AUG-14:00 | 127950.92 | 14-AUG-17:40 | 0.00 |
September | 0.323323E+12 | 0.805974E+11 | 720.00 | 0.321393E+12 | 0.193056E+10 | 0.00 | 0.55 | 30-SEP-24:00 | 0.31 | 20-SEP-06:10 | 211359.61 | 30-SEP-24:00 | 211359.61 | 30-SEP-24:00 | 4372.41 | 19-SEP-14:10 | 50311.97 | 30-SEP-24:00 | 0.00 |
October | 0.573413E+12 | 0.135016E+12 | 744.00 | 0.572846E+12 | 0.566457E+09 | 0.00 | 0.75 | 31-OCT-24:00 | 0.53 | 19-OCT-06:10 | 303371.48 | 31-OCT-24:00 | 303371.48 | 31-OCT-24:00 | 4210.98 | 17-OCT-15:20 | 69207.09 | 31-OCT-24:00 | 0.00 |
November | 0.789964E+12 | 0.178989E+12 | 720.00 | 0.789647E+12 | 0.317299E+09 | 0.00 | 0.77 | 17-NOV-22:03 | 0.73 | 25-NOV-07:30 | 308647.57 | 08-NOV-15:00 | 308539.80 | 03-NOV-21:03 | 3267.44 | 24-NOV-12:30 | 72544.82 | 24-NOV-12:00 | 0.00 |
December | 0.105922E+13 | 0.233356E+12 | 744.00 | 0.105922E+13 | -0.0 | 0.00 | 0.96 | 13-DEC-22:03 | 0.93 | 20-DEC-18:10 | 400199.83 | 26-DEC-22:03 | 400199.83 | 26-DEC-22:03 | 0.00 | 08-DEC-17:00 | 88066.59 | 06-DEC-22:03 | 0.00 |
Annual Sum or Average | 0.820636E+13 | 0.191164E+13 | 8760.00 | 0.819513E+13 | 0.112346E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.321916E+12 | 0.805814E+11 | 672.00 | 0.321393E+12 | -0.0 | 0.00 | 0.34 | 0.31 | 124755.64 | 124755.64 | 0.00 | 31234.61 | 0.00 | ||||||
Maximum of Months | 0.107103E+13 | 0.254554E+12 | 744.00 | 0.106831E+13 | 0.285402E+10 | 0.00 | 1.00 | 0.93 | 408730.14 | 408730.14 | 6021.19 | 127950.92 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.421519E+10 | 0.108528E+10 | 744.00 | 0.421371E+10 | 1481130.46 | 0.00 | 0.27 | 16-JAN-16:30 | 0.11 | 10-JAN-08:00 | 2294.96 | 01-JAN-16:10 | 2289.34 | 01-JAN-16:05 | 52.87 | 18-JAN-16:30 | 552.99 | 16-JAN-16:30 | 0.00 |
February | 0.871742E+10 | 0.209789E+10 | 672.00 | 0.871620E+10 | 1224350.57 | 0.00 | 0.52 | 19-FEB-16:55 | 0.36 | 02-FEB-07:40 | 4388.25 | 19-FEB-17:00 | 4388.25 | 19-FEB-17:00 | 54.39 | 07-FEB-17:00 | 1057.31 | 19-FEB-16:55 | 0.00 |
March | 0.150688E+11 | 0.345546E+10 | 744.00 | 0.150685E+11 | 319148.16 | 0.00 | 0.84 | 31-MAR-24:00 | 0.57 | 18-MAR-17:00 | 7606.64 | 31-MAR-24:00 | 7606.64 | 31-MAR-24:00 | 65.37 | 20-MAR-06:10 | 1704.54 | 31-MAR-24:00 | 0.00 |
April | 0.200577E+11 | 0.448011E+10 | 720.00 | 0.200574E+11 | 297670.84 | 0.00 | 1.00 | 30-APR-17:31 | 0.30 | 30-APR-23:53 | 8826.48 | 30-APR-18:00 | 8826.48 | 30-APR-18:00 | 54.77 | 28-APR-11:00 | 2646.89 | 30-APR-18:00 | 0.00 |
May | 0.541844E+10 | 0.134527E+10 | 744.00 | 0.539756E+10 | 20884434.72 | 0.00 | 0.45 | 31-MAY-24:00 | 0.17 | 05-MAY-06:05 | 3958.79 | 31-MAY-24:00 | 3958.79 | 31-MAY-24:00 | 138.16 | 23-MAY-15:50 | 908.43 | 31-MAY-24:00 | 0.00 |
June | 0.105650E+11 | 0.248688E+10 | 720.00 | 0.104750E+11 | 89997113.08 | 0.00 | 0.63 | 30-JUN-24:00 | 0.41 | 01-JUN-06:30 | 5785.40 | 30-JUN-24:00 | 5785.40 | 30-JUN-24:00 | 212.54 | 27-JUN-08:20 | 1476.98 | 13-JUN-16:00 | 0.00 |
July | 0.161411E+11 | 0.378281E+10 | 744.00 | 0.160304E+11 | 0.110660E+09 | 0.00 | 0.83 | 31-JUL-24:00 | 0.59 | 01-JUL-06:40 | 7860.62 | 31-JUL-24:00 | 7860.62 | 31-JUL-24:00 | 226.26 | 18-JUL-16:00 | 2298.88 | 22-JUL-18:35 | 0.00 |
August | 0.211444E+11 | 0.496065E+10 | 744.00 | 0.210283E+11 | 0.116023E+09 | 0.00 | 0.96 | 14-AUG-18:00 | 0.29 | 31-AUG-24:00 | 8711.61 | 13-AUG-18:04 | 8697.43 | 13-AUG-18:04 | 251.28 | 08-AUG-13:30 | 2691.49 | 14-AUG-18:00 | 0.00 |
September | 0.543435E+10 | 0.134342E+10 | 720.00 | 0.536492E+10 | 69430001.60 | 0.00 | 0.45 | 30-SEP-24:00 | 0.18 | 21-SEP-06:10 | 3840.74 | 30-SEP-24:00 | 3840.74 | 30-SEP-24:00 | 158.81 | 19-SEP-16:00 | 914.11 | 30-SEP-24:00 | 0.00 |
October | 0.102447E+11 | 0.240156E+10 | 744.00 | 0.102180E+11 | 26664406.61 | 0.00 | 0.64 | 31-OCT-24:00 | 0.37 | 28-OCT-07:00 | 5661.58 | 31-OCT-24:00 | 5661.58 | 31-OCT-24:00 | 148.02 | 17-OCT-15:30 | 1292.47 | 31-OCT-24:00 | 0.00 |
November | 0.145863E+11 | 0.330758E+10 | 720.00 | 0.145705E+11 | 15828697.68 | 0.00 | 0.69 | 19-NOV-16:05 | 0.57 | 25-NOV-08:00 | 6131.88 | 19-NOV-16:10 | 6131.88 | 19-NOV-16:10 | 143.36 | 08-NOV-15:10 | 1394.24 | 19-NOV-16:05 | 0.00 |
December | 0.198574E+11 | 0.442624E+10 | 744.00 | 0.198573E+11 | 66694.98 | 0.00 | 0.89 | 31-DEC-15:15 | 0.76 | 02-DEC-18:00 | 8001.21 | 25-DEC-15:15 | 8001.21 | 25-DEC-15:15 | 33.85 | 20-DEC-17:10 | 1794.27 | 31-DEC-15:15 | 0.00 |
Annual Sum or Average | 0.151451E+12 | 0.351732E+11 | 8760.00 | 0.150998E+12 | 0.452877E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.421519E+10 | 0.108528E+10 | 672.00 | 0.421371E+10 | 66694.98 | 0.00 | 0.27 | 0.11 | 2294.96 | 2289.34 | 33.85 | 552.99 | 0.00 | ||||||
Maximum of Months | 0.211444E+11 | 0.496065E+10 | 744.00 | 0.210283E+11 | 0.116023E+09 | 0.00 | 1.00 | 0.76 | 8826.48 | 8826.48 | 251.28 | 2691.49 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.234357E+11 | 0.632518E+10 | 742.92 | 0.234212E+11 | 14533883.24 | 0.00 | 0.24 | 19-JAN-16:20 | 0.00 | 02-JAN-07:10 | 19216.42 | 19-JAN-16:20 | 19216.42 | 19-JAN-16:20 | 496.85 | 18-JAN-16:30 | 4717.33 | 19-JAN-16:20 | 0.00 |
February | 0.686061E+11 | 0.167978E+11 | 672.00 | 0.685935E+11 | 12617474.35 | 0.00 | 0.48 | 17-FEB-17:00 | 0.27 | 13-FEB-07:10 | 39585.19 | 27-FEB-17:00 | 39585.19 | 27-FEB-17:00 | 532.98 | 07-FEB-17:00 | 9218.69 | 17-FEB-17:00 | 0.00 |
March | 0.128529E+12 | 0.298561E+11 | 744.00 | 0.128526E+12 | 3248839.96 | 0.00 | 0.80 | 31-MAR-24:00 | 0.51 | 18-MAR-17:00 | 67976.64 | 31-MAR-24:00 | 67976.64 | 31-MAR-24:00 | 563.65 | 20-MAR-06:10 | 15379.55 | 31-MAR-24:00 | 0.00 |
April | 0.183693E+12 | 0.412833E+11 | 720.00 | 0.183690E+12 | 3284332.85 | 0.00 | 0.99 | 30-APR-18:00 | 0.27 | 30-APR-23:57 | 83106.59 | 30-APR-17:53 | 83106.59 | 30-APR-17:53 | 576.90 | 28-APR-11:00 | 25022.56 | 30-APR-18:00 | 0.00 |
May | 0.441855E+11 | 0.111122E+11 | 744.00 | 0.439808E+11 | 0.204730E+09 | 0.00 | 0.43 | 31-MAY-24:00 | 0.11 | 05-MAY-06:05 | 36134.84 | 31-MAY-24:00 | 36134.84 | 31-MAY-24:00 | 1370.31 | 23-MAY-16:00 | 8328.47 | 31-MAY-24:00 | 0.00 |
June | 0.958154E+11 | 0.226825E+11 | 720.00 | 0.949272E+11 | 0.888181E+09 | 0.00 | 0.60 | 30-JUN-24:00 | 0.36 | 08-JUN-06:10 | 52244.09 | 30-JUN-24:00 | 52244.09 | 30-JUN-24:00 | 2087.08 | 27-JUN-08:20 | 14018.21 | 13-JUN-16:00 | 0.00 |
July | 0.149789E+12 | 0.352528E+11 | 744.00 | 0.148693E+12 | 0.109595E+10 | 0.00 | 0.81 | 31-JUL-24:00 | 0.56 | 01-JUL-06:40 | 73664.60 | 31-JUL-24:00 | 73664.60 | 31-JUL-24:00 | 2241.66 | 18-JUL-16:00 | 21805.26 | 22-JUL-18:35 | 0.00 |
August | 0.198157E+12 | 0.466350E+11 | 744.00 | 0.197001E+12 | 0.115591E+10 | 0.00 | 0.95 | 14-AUG-18:00 | 0.24 | 31-AUG-24:00 | 80802.21 | 13-AUG-18:04 | 80663.22 | 13-AUG-18:04 | 2500.13 | 08-AUG-13:30 | 25617.10 | 14-AUG-18:00 | 0.00 |
September | 0.451288E+11 | 0.112916E+11 | 720.00 | 0.444604E+11 | 0.668413E+09 | 0.00 | 0.42 | 30-SEP-23:40 | 0.13 | 07-SEP-06:05 | 33862.33 | 30-SEP-23:40 | 33862.33 | 30-SEP-23:40 | 1593.89 | 19-SEP-16:00 | 8123.78 | 30-SEP-23:40 | 0.00 |
October | 0.850459E+11 | 0.201984E+11 | 744.00 | 0.847820E+11 | 0.263836E+09 | 0.00 | 0.58 | 31-OCT-24:00 | 0.30 | 28-OCT-07:00 | 48923.34 | 31-OCT-24:00 | 48923.34 | 31-OCT-24:00 | 1429.24 | 17-OCT-15:30 | 11304.76 | 31-OCT-24:00 | 0.00 |
November | 0.122176E+12 | 0.281125E+11 | 720.00 | 0.122018E+12 | 0.158278E+09 | 0.00 | 0.65 | 03-NOV-16:00 | 0.48 | 20-NOV-07:10 | 55885.63 | 10-NOV-16:00 | 55697.69 | 10-NOV-16:00 | 1423.32 | 08-NOV-15:10 | 12537.45 | 03-NOV-16:00 | 0.00 |
December | 0.167244E+12 | 0.378999E+11 | 744.00 | 0.167243E+12 | 992383.88 | 0.00 | 0.81 | 29-DEC-15:40 | 0.65 | 26-DEC-07:10 | 70425.90 | 21-DEC-15:20 | 70425.90 | 21-DEC-15:20 | 365.29 | 20-DEC-17:10 | 15658.82 | 29-DEC-15:40 | 0.00 |
Annual Sum or Average | 0.131180E+13 | 0.307447E+12 | 8758.92 | 0.130734E+13 | 0.446998E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.234357E+11 | 0.632518E+10 | 672.00 | 0.234212E+11 | 992383.88 | 0.00 | 0.24 | 0.00 | 19216.42 | 19216.42 | 365.29 | 4717.33 | 0.00 | ||||||
Maximum of Months | 0.198157E+12 | 0.466350E+11 | 744.00 | 0.197001E+12 | 0.115591E+10 | 0.00 | 0.99 | 0.65 | 83106.59 | 83106.59 | 2500.13 | 25617.10 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.778681E+09 | 0.223054E+09 | 434.39 | 0.777747E+09 | 933799.03 | 0.00 | 0.23 | 19-JAN-16:20 | 0.00 | 01-JAN-00:05 | 1814.66 | 19-JAN-16:20 | 1814.66 | 19-JAN-16:20 | 45.44 | 18-JAN-16:40 | 448.02 | 19-JAN-16:20 | 0.00 |
February | 0.511627E+10 | 0.128031E+10 | 672.00 | 0.511507E+10 | 1196549.03 | 0.00 | 0.46 | 17-FEB-17:00 | 0.10 | 20-FEB-08:30 | 3729.17 | 09-FEB-16:50 | 3729.17 | 09-FEB-16:50 | 51.57 | 08-FEB-16:40 | 892.40 | 17-FEB-17:00 | 0.00 |
March | 0.113504E+11 | 0.267268E+10 | 744.00 | 0.113501E+11 | 309685.33 | 0.00 | 0.74 | 31-MAR-23:20 | 0.38 | 06-MAR-04:57 | 6332.21 | 31-MAR-23:20 | 6332.21 | 31-MAR-23:20 | 45.21 | 20-MAR-06:10 | 1448.14 | 31-MAR-23:20 | 0.00 |
April | 0.175621E+11 | 0.397779E+10 | 720.00 | 0.175618E+11 | 316411.01 | 0.00 | 0.99 | 30-APR-18:00 | 0.26 | 30-APR-23:57 | 8444.54 | 30-APR-17:58 | 8444.54 | 30-APR-17:58 | 56.04 | 28-APR-11:00 | 2541.58 | 30-APR-18:00 | 0.00 |
May | 0.369028E+10 | 0.941647E+09 | 743.41 | 0.366998E+10 | 20301854.34 | 0.00 | 0.41 | 31-MAY-23:30 | 0.00 | 05-MAY-02:15 | 3449.61 | 31-MAY-23:30 | 3449.61 | 31-MAY-23:30 | 138.01 | 23-MAY-16:00 | 799.53 | 31-MAY-23:30 | 0.00 |
June | 0.922037E+10 | 0.219510E+10 | 720.00 | 0.913185E+10 | 88522622.18 | 0.00 | 0.56 | 30-JUN-23:30 | 0.30 | 08-JUN-06:10 | 4959.34 | 30-JUN-23:30 | 4959.34 | 30-JUN-23:30 | 208.43 | 26-JUN-16:10 | 1435.22 | 13-JUN-16:00 | 0.00 |
July | 0.146712E+11 | 0.347048E+10 | 744.00 | 0.145619E+11 | 0.109341E+09 | 0.00 | 0.80 | 22-JUL-18:50 | 0.51 | 01-JUL-06:40 | 7218.69 | 31-JUL-23:30 | 7218.69 | 31-JUL-23:30 | 224.31 | 18-JUL-16:00 | 2237.06 | 22-JUL-18:35 | 0.00 |
August | 0.195166E+11 | 0.461453E+10 | 744.00 | 0.194013E+11 | 0.115377E+09 | 0.00 | 0.95 | 14-AUG-18:00 | 0.21 | 31-AUG-24:00 | 8148.16 | 13-AUG-18:04 | 8134.22 | 13-AUG-18:04 | 249.60 | 08-AUG-13:30 | 2589.32 | 14-AUG-18:00 | 0.00 |
September | 0.388620E+10 | 0.986173E+09 | 719.83 | 0.382060E+10 | 65603377.48 | 0.00 | 0.35 | 30-SEP-23:20 | 0.00 | 17-SEP-03:15 | 2849.16 | 30-SEP-23:20 | 2849.16 | 30-SEP-23:20 | 160.04 | 19-SEP-16:00 | 755.91 | 13-SEP-17:00 | 0.00 |
October | 0.708477E+10 | 0.170919E+10 | 744.00 | 0.705899E+10 | 25780016.60 | 0.00 | 0.52 | 31-OCT-23:20 | 0.19 | 23-OCT-06:10 | 4365.39 | 31-OCT-23:20 | 4365.39 | 31-OCT-23:20 | 141.10 | 17-OCT-15:30 | 1022.43 | 31-OCT-23:20 | 0.00 |
November | 0.104944E+11 | 0.245265E+10 | 720.00 | 0.104788E+11 | 15584742.55 | 0.00 | 0.63 | 03-NOV-16:00 | 0.32 | 27-NOV-04:01 | 5518.16 | 10-NOV-16:00 | 5499.48 | 10-NOV-16:00 | 141.55 | 08-NOV-15:10 | 1234.36 | 03-NOV-16:00 | 0.00 |
December | 0.146784E+11 | 0.338087E+10 | 744.00 | 0.146783E+11 | 85923.21 | 0.00 | 0.77 | 29-DEC-15:40 | 0.48 | 26-DEC-04:11 | 6818.81 | 21-DEC-15:20 | 6818.81 | 21-DEC-15:20 | 34.59 | 20-DEC-17:10 | 1502.14 | 29-DEC-15:40 | 0.00 |
Annual Sum or Average | 0.118050E+12 | 0.279045E+11 | 8449.63 | 0.117606E+12 | 0.443353E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.778681E+09 | 0.223054E+09 | 434.39 | 0.777747E+09 | 85923.21 | 0.00 | 0.23 | 0.00 | 1814.66 | 1814.66 | 34.59 | 448.02 | 0.00 | ||||||
Maximum of Months | 0.195166E+11 | 0.461453E+10 | 744.00 | 0.194013E+11 | 0.115377E+09 | 0.00 | 0.99 | 0.51 | 8444.54 | 8444.54 | 249.60 | 2589.32 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.81 | 0.00 | 73.81 | 2.52 | 495.34 | 0.00 | 0.00 | 0.00 |
February | 115.25 | 0.00 | 115.25 | 9.76 | 462.97 | 0.00 | 0.00 | 0.00 |
March | 159.49 | 0.00 | 159.49 | 40.72 | 388.30 | 0.00 | 0.00 | 0.00 |
April | 259.67 | 1.16 | 258.51 | 153.21 | 305.81 | 0.00 | 0.00 | 0.00 |
May | 324.66 | 15.66 | 309.00 | 200.30 | 237.26 | 0.00 | 0.00 | 0.00 |
June | 358.89 | 22.50 | 336.39 | 291.10 | 186.50 | 0.00 | 0.00 | 0.00 |
July | 340.43 | 19.41 | 321.02 | 293.22 | 172.89 | 0.00 | 0.00 | 0.00 |
August | 267.59 | 4.19 | 263.40 | 224.27 | 194.56 | 0.00 | 0.00 | 0.00 |
September | 203.68 | 0.05 | 203.63 | 145.15 | 258.84 | 0.00 | 0.00 | 0.00 |
October | 130.51 | 0.00 | 130.51 | 45.00 | 359.81 | 0.00 | 0.00 | 0.00 |
November | 78.42 | 0.00 | 78.42 | 4.25 | 452.04 | 0.00 | 0.00 | 0.00 |
December | 53.40 | 0.00 | 53.40 | 0.01 | 546.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.52 | 5.28 | 192.23 | 118.01 | 337.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.40 | 0.00 | 53.40 | 0.01 | 172.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.89 | 22.50 | 336.39 | 293.22 | 546.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.81 | 0.00 | 73.81 | 2.52 | 495.34 | 0.00 | 0.00 | 0.00 |
February | 115.25 | 0.00 | 115.25 | 9.76 | 462.97 | 0.00 | 0.00 | 0.00 |
March | 159.49 | 0.00 | 159.49 | 40.72 | 388.30 | 0.00 | 0.00 | 0.00 |
April | 259.67 | 1.16 | 258.51 | 153.20 | 305.81 | 0.00 | 0.00 | 0.00 |
May | 324.65 | 15.66 | 308.99 | 200.29 | 237.26 | 0.00 | 0.00 | 0.00 |
June | 358.89 | 22.50 | 336.38 | 291.09 | 186.50 | 0.00 | 0.00 | 0.00 |
July | 340.42 | 19.41 | 321.01 | 293.21 | 172.89 | 0.00 | 0.00 | 0.00 |
August | 267.59 | 4.19 | 263.40 | 224.26 | 194.56 | 0.00 | 0.00 | 0.00 |
September | 203.67 | 0.05 | 203.63 | 145.15 | 258.84 | 0.00 | 0.00 | 0.00 |
October | 130.51 | 0.00 | 130.51 | 45.00 | 359.81 | 0.00 | 0.00 | 0.00 |
November | 78.42 | 0.00 | 78.42 | 4.25 | 452.04 | 0.00 | 0.00 | 0.00 |
December | 53.40 | 0.00 | 53.40 | 0.01 | 546.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.51 | 5.28 | 192.23 | 118.00 | 337.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.40 | 0.00 | 53.40 | 0.01 | 172.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.89 | 22.50 | 336.38 | 293.21 | 546.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.81 | 0.00 | 73.81 | 2.52 | 495.34 | 0.00 | 0.00 | 0.00 |
February | 115.25 | 0.00 | 115.25 | 9.76 | 462.97 | 0.00 | 0.00 | 0.00 |
March | 159.49 | 0.00 | 159.49 | 40.72 | 388.30 | 0.00 | 0.00 | 0.00 |
April | 259.67 | 1.16 | 258.51 | 153.20 | 305.81 | 0.00 | 0.00 | 0.00 |
May | 324.66 | 15.66 | 308.99 | 200.29 | 237.26 | 0.00 | 0.00 | 0.00 |
June | 358.89 | 22.50 | 336.38 | 291.09 | 186.50 | 0.00 | 0.00 | 0.00 |
July | 340.42 | 19.41 | 321.01 | 293.22 | 172.89 | 0.00 | 0.00 | 0.00 |
August | 267.59 | 4.19 | 263.40 | 224.26 | 194.56 | 0.00 | 0.00 | 0.00 |
September | 203.67 | 0.05 | 203.63 | 145.15 | 258.84 | 0.00 | 0.00 | 0.00 |
October | 130.51 | 0.00 | 130.51 | 45.00 | 359.81 | 0.00 | 0.00 | 0.00 |
November | 78.42 | 0.00 | 78.42 | 4.25 | 452.04 | 0.00 | 0.00 | 0.00 |
December | 53.40 | 0.00 | 53.40 | 0.01 | 546.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.51 | 5.28 | 192.23 | 118.00 | 337.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.40 | 0.00 | 53.40 | 0.01 | 172.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.89 | 22.50 | 336.38 | 293.22 | 546.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.81 | 0.00 | 73.81 | 2.52 | 495.34 | 0.00 | 0.00 | 0.00 |
February | 115.25 | 0.00 | 115.25 | 9.76 | 462.97 | 0.00 | 0.00 | 0.00 |
March | 159.49 | 0.00 | 159.49 | 40.72 | 388.30 | 0.00 | 0.00 | 0.00 |
April | 259.67 | 1.16 | 258.51 | 153.20 | 305.81 | 0.00 | 0.00 | 0.00 |
May | 324.65 | 15.66 | 308.99 | 200.29 | 237.26 | 0.00 | 0.00 | 0.00 |
June | 358.89 | 22.50 | 336.38 | 291.09 | 186.50 | 0.00 | 0.00 | 0.00 |
July | 340.42 | 19.41 | 321.01 | 293.21 | 172.89 | 0.00 | 0.00 | 0.00 |
August | 267.59 | 4.19 | 263.40 | 224.26 | 194.56 | 0.00 | 0.00 | 0.00 |
September | 203.67 | 0.05 | 203.63 | 145.15 | 258.84 | 0.00 | 0.00 | 0.00 |
October | 130.51 | 0.00 | 130.51 | 45.00 | 359.81 | 0.00 | 0.00 | 0.00 |
November | 78.42 | 0.00 | 78.42 | 4.25 | 452.04 | 0.00 | 0.00 | 0.00 |
December | 53.40 | 0.00 | 53.40 | 0.01 | 546.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.51 | 5.28 | 192.23 | 118.00 | 337.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.40 | 0.00 | 53.40 | 0.01 | 172.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.89 | 22.50 | 336.38 | 293.21 | 546.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.80 | 0.00 | 73.80 | 2.52 | 495.32 | 0.00 | 0.00 | 0.00 |
February | 115.25 | 0.00 | 115.25 | 9.76 | 462.95 | 0.00 | 0.00 | 0.00 |
March | 159.48 | 0.00 | 159.48 | 40.72 | 388.29 | 0.00 | 0.00 | 0.00 |
April | 259.66 | 1.16 | 258.50 | 153.20 | 305.80 | 0.00 | 0.00 | 0.00 |
May | 324.64 | 15.66 | 308.98 | 200.29 | 237.25 | 0.00 | 0.00 | 0.00 |
June | 358.87 | 22.50 | 336.37 | 291.08 | 186.49 | 0.00 | 0.00 | 0.00 |
July | 340.41 | 19.41 | 321.00 | 293.20 | 172.88 | 0.00 | 0.00 | 0.00 |
August | 267.58 | 4.19 | 263.39 | 224.26 | 194.55 | 0.00 | 0.00 | 0.00 |
September | 203.66 | 0.05 | 203.62 | 145.15 | 258.83 | 0.00 | 0.00 | 0.00 |
October | 130.51 | 0.00 | 130.51 | 45.00 | 359.80 | 0.00 | 0.00 | 0.00 |
November | 78.42 | 0.00 | 78.42 | 4.25 | 452.03 | 0.00 | 0.00 | 0.00 |
December | 53.40 | 0.00 | 53.40 | 0.01 | 546.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.51 | 5.28 | 192.22 | 118.00 | 337.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.40 | 0.00 | 53.40 | 0.01 | 172.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.87 | 22.50 | 336.37 | 293.20 | 546.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 167.62 | 67.33 | 100.29 | 90.93 | 500.91 | 0.00 | 0.00 | 0.00 |
February | 249.95 | 92.34 | 157.62 | 152.87 | 468.09 | 0.00 | 0.00 | 0.00 |
March | 261.21 | 51.47 | 209.73 | 148.54 | 388.63 | 0.00 | 0.00 | 0.00 |
April | 701.36 | 329.58 | 371.79 | 717.76 | 309.39 | 0.00 | 0.00 | 0.00 |
May | 737.46 | 321.59 | 415.87 | 737.71 | 263.67 | 0.00 | 0.00 | 0.00 |
June | 729.95 | 291.54 | 438.42 | 780.39 | 204.84 | 0.00 | 0.00 | 0.00 |
July | 745.14 | 316.68 | 428.45 | 831.53 | 188.19 | 0.00 | 0.00 | 0.00 |
August | 705.86 | 337.25 | 368.60 | 810.58 | 202.70 | 0.00 | 0.00 | 0.00 |
September | 635.65 | 338.01 | 297.64 | 703.90 | 266.06 | 0.00 | 0.00 | 0.00 |
October | 306.84 | 127.16 | 179.67 | 261.75 | 368.31 | 0.00 | 0.00 | 0.00 |
November | 159.96 | 54.52 | 105.44 | 86.15 | 452.32 | 0.00 | 0.00 | 0.00 |
December | 118.55 | 44.08 | 74.48 | 54.87 | 547.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 460.63 | 197.88 | 262.75 | 449.15 | 346.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 118.55 | 44.08 | 74.48 | 54.87 | 188.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 745.14 | 338.01 | 438.42 | 831.53 | 547.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 167.62 | 67.33 | 100.29 | 90.93 | 500.91 | 0.00 | 0.00 | 0.00 |
February | 249.95 | 92.34 | 157.62 | 152.87 | 468.09 | 0.00 | 0.00 | 0.00 |
March | 261.21 | 51.47 | 209.73 | 148.54 | 388.63 | 0.00 | 0.00 | 0.00 |
April | 701.36 | 329.58 | 371.79 | 717.76 | 309.39 | 0.00 | 0.00 | 0.00 |
May | 737.46 | 321.59 | 415.87 | 737.71 | 263.67 | 0.00 | 0.00 | 0.00 |
June | 729.95 | 291.54 | 438.42 | 780.39 | 204.84 | 0.00 | 0.00 | 0.00 |
July | 745.14 | 316.68 | 428.45 | 831.53 | 188.19 | 0.00 | 0.00 | 0.00 |
August | 705.86 | 337.25 | 368.60 | 810.58 | 202.70 | 0.00 | 0.00 | 0.00 |
September | 635.65 | 338.01 | 297.64 | 703.90 | 266.06 | 0.00 | 0.00 | 0.00 |
October | 306.84 | 127.16 | 179.67 | 261.75 | 368.31 | 0.00 | 0.00 | 0.00 |
November | 159.96 | 54.52 | 105.44 | 86.15 | 452.32 | 0.00 | 0.00 | 0.00 |
December | 118.55 | 44.08 | 74.48 | 54.87 | 547.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 460.63 | 197.88 | 262.75 | 449.15 | 346.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 118.55 | 44.08 | 74.48 | 54.87 | 188.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 745.14 | 338.01 | 438.42 | 831.53 | 547.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 167.62 | 67.33 | 100.29 | 90.93 | 500.90 | 0.00 | 0.00 | 0.00 |
February | 249.95 | 92.33 | 157.62 | 152.87 | 468.08 | 0.00 | 0.00 | 0.00 |
March | 261.20 | 51.47 | 209.73 | 148.54 | 388.63 | 0.00 | 0.00 | 0.00 |
April | 701.35 | 329.57 | 371.78 | 717.75 | 309.39 | 0.00 | 0.00 | 0.00 |
May | 737.45 | 321.59 | 415.86 | 737.70 | 263.67 | 0.00 | 0.00 | 0.00 |
June | 729.94 | 291.53 | 438.41 | 780.38 | 204.84 | 0.00 | 0.00 | 0.00 |
July | 745.12 | 316.68 | 428.45 | 831.51 | 188.18 | 0.00 | 0.00 | 0.00 |
August | 705.84 | 337.25 | 368.60 | 810.56 | 202.70 | 0.00 | 0.00 | 0.00 |
September | 635.64 | 338.00 | 297.63 | 703.89 | 266.06 | 0.00 | 0.00 | 0.00 |
October | 306.83 | 127.16 | 179.67 | 261.75 | 368.30 | 0.00 | 0.00 | 0.00 |
November | 159.96 | 54.52 | 105.44 | 86.15 | 452.31 | 0.00 | 0.00 | 0.00 |
December | 118.55 | 44.07 | 74.47 | 54.87 | 547.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 460.62 | 197.88 | 262.74 | 449.14 | 346.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 118.55 | 44.07 | 74.47 | 54.87 | 188.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 745.12 | 338.00 | 438.41 | 831.51 | 547.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 419.02 | 271.25 | 147.77 | 403.85 | 420.93 | 0.00 | 0.00 | 0.00 |
February | 511.76 | 312.28 | 199.48 | 507.30 | 412.34 | 0.00 | 0.00 | 0.00 |
March | 316.40 | 92.12 | 224.28 | 246.49 | 351.68 | 0.00 | 0.00 | 0.00 |
April | 657.04 | 296.97 | 360.06 | 732.29 | 304.69 | 0.00 | 0.00 | 0.00 |
May | 543.43 | 176.92 | 366.51 | 563.31 | 257.46 | 0.00 | 0.00 | 0.00 |
June | 500.62 | 121.18 | 379.44 | 540.11 | 199.77 | 0.00 | 0.00 | 0.00 |
July | 542.41 | 169.86 | 372.55 | 629.30 | 186.08 | 0.00 | 0.00 | 0.00 |
August | 635.58 | 285.91 | 349.67 | 779.39 | 202.89 | 0.00 | 0.00 | 0.00 |
September | 751.09 | 440.00 | 311.09 | 913.71 | 257.34 | 0.00 | 0.00 | 0.00 |
October | 516.03 | 301.60 | 214.43 | 557.18 | 333.99 | 0.00 | 0.00 | 0.00 |
November | 365.86 | 222.56 | 143.30 | 354.28 | 398.54 | 0.00 | 0.00 | 0.00 |
December | 289.98 | 185.79 | 104.19 | 269.59 | 478.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 503.33 | 238.77 | 264.56 | 540.65 | 316.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 289.98 | 92.12 | 104.19 | 246.49 | 186.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 751.09 | 440.00 | 379.44 | 913.71 | 478.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 419.02 | 271.25 | 147.77 | 403.84 | 420.93 | 0.00 | 0.00 | 0.00 |
February | 511.75 | 312.28 | 199.48 | 507.29 | 412.34 | 0.00 | 0.00 | 0.00 |
March | 316.40 | 92.12 | 224.28 | 246.49 | 351.68 | 0.00 | 0.00 | 0.00 |
April | 657.03 | 296.97 | 360.06 | 732.28 | 304.69 | 0.00 | 0.00 | 0.00 |
May | 543.43 | 176.92 | 366.51 | 563.31 | 257.46 | 0.00 | 0.00 | 0.00 |
June | 500.61 | 121.18 | 379.44 | 540.11 | 199.77 | 0.00 | 0.00 | 0.00 |
July | 542.40 | 169.86 | 372.55 | 629.30 | 186.08 | 0.00 | 0.00 | 0.00 |
August | 635.58 | 285.90 | 349.67 | 779.39 | 202.89 | 0.00 | 0.00 | 0.00 |
September | 751.09 | 440.00 | 311.09 | 913.70 | 257.34 | 0.00 | 0.00 | 0.00 |
October | 516.03 | 301.59 | 214.43 | 557.18 | 333.99 | 0.00 | 0.00 | 0.00 |
November | 365.86 | 222.56 | 143.30 | 354.28 | 398.54 | 0.00 | 0.00 | 0.00 |
December | 289.98 | 185.79 | 104.19 | 269.59 | 478.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 503.33 | 238.77 | 264.56 | 540.65 | 316.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 289.98 | 92.12 | 104.19 | 246.49 | 186.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 751.09 | 440.00 | 379.44 | 913.70 | 478.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 419.02 | 271.25 | 147.77 | 403.85 | 420.93 | 0.00 | 0.00 | 0.00 |
February | 511.76 | 312.28 | 199.48 | 507.30 | 412.34 | 0.00 | 0.00 | 0.00 |
March | 316.40 | 92.12 | 224.28 | 246.49 | 351.68 | 0.00 | 0.00 | 0.00 |
April | 657.04 | 296.97 | 360.06 | 732.29 | 304.69 | 0.00 | 0.00 | 0.00 |
May | 543.43 | 176.92 | 366.51 | 563.31 | 257.46 | 0.00 | 0.00 | 0.00 |
June | 500.62 | 121.18 | 379.44 | 540.11 | 199.77 | 0.00 | 0.00 | 0.00 |
July | 542.41 | 169.86 | 372.55 | 629.30 | 186.08 | 0.00 | 0.00 | 0.00 |
August | 635.58 | 285.91 | 349.67 | 779.39 | 202.89 | 0.00 | 0.00 | 0.00 |
September | 751.09 | 440.00 | 311.09 | 913.71 | 257.34 | 0.00 | 0.00 | 0.00 |
October | 516.03 | 301.60 | 214.43 | 557.18 | 333.99 | 0.00 | 0.00 | 0.00 |
November | 365.86 | 222.56 | 143.30 | 354.28 | 398.54 | 0.00 | 0.00 | 0.00 |
December | 289.98 | 185.79 | 104.19 | 269.59 | 478.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 503.33 | 238.77 | 264.56 | 540.65 | 316.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 289.98 | 92.12 | 104.19 | 246.49 | 186.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 751.09 | 440.00 | 379.44 | 913.71 | 478.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 419.02 | 271.25 | 147.77 | 403.84 | 420.93 | 0.00 | 0.00 | 0.00 |
February | 511.75 | 312.28 | 199.48 | 507.29 | 412.34 | 0.00 | 0.00 | 0.00 |
March | 316.40 | 92.12 | 224.28 | 246.49 | 351.68 | 0.00 | 0.00 | 0.00 |
April | 657.03 | 296.97 | 360.06 | 732.28 | 304.69 | 0.00 | 0.00 | 0.00 |
May | 543.43 | 176.92 | 366.51 | 563.31 | 257.46 | 0.00 | 0.00 | 0.00 |
June | 500.61 | 121.18 | 379.44 | 540.11 | 199.77 | 0.00 | 0.00 | 0.00 |
July | 542.40 | 169.86 | 372.55 | 629.30 | 186.08 | 0.00 | 0.00 | 0.00 |
August | 635.58 | 285.90 | 349.67 | 779.39 | 202.89 | 0.00 | 0.00 | 0.00 |
September | 751.09 | 440.00 | 311.09 | 913.70 | 257.34 | 0.00 | 0.00 | 0.00 |
October | 516.03 | 301.59 | 214.43 | 557.18 | 333.99 | 0.00 | 0.00 | 0.00 |
November | 365.86 | 222.56 | 143.30 | 354.28 | 398.54 | 0.00 | 0.00 | 0.00 |
December | 289.98 | 185.79 | 104.19 | 269.59 | 478.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 503.33 | 238.77 | 264.56 | 540.65 | 316.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 289.98 | 92.12 | 104.19 | 246.49 | 186.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 751.09 | 440.00 | 379.44 | 913.70 | 478.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 419.00 | 271.24 | 147.77 | 403.83 | 420.91 | 0.00 | 0.00 | 0.00 |
February | 511.73 | 312.27 | 199.47 | 507.27 | 412.33 | 0.00 | 0.00 | 0.00 |
March | 316.39 | 92.12 | 224.27 | 246.48 | 351.66 | 0.00 | 0.00 | 0.00 |
April | 657.01 | 296.96 | 360.05 | 732.25 | 304.68 | 0.00 | 0.00 | 0.00 |
May | 543.41 | 176.91 | 366.49 | 563.29 | 257.45 | 0.00 | 0.00 | 0.00 |
June | 500.59 | 121.17 | 379.42 | 540.09 | 199.76 | 0.00 | 0.00 | 0.00 |
July | 542.38 | 169.85 | 372.53 | 629.28 | 186.07 | 0.00 | 0.00 | 0.00 |
August | 635.55 | 285.89 | 349.66 | 779.36 | 202.88 | 0.00 | 0.00 | 0.00 |
September | 751.06 | 439.98 | 311.08 | 913.67 | 257.33 | 0.00 | 0.00 | 0.00 |
October | 516.01 | 301.58 | 214.43 | 557.16 | 333.97 | 0.00 | 0.00 | 0.00 |
November | 365.85 | 222.55 | 143.29 | 354.27 | 398.52 | 0.00 | 0.00 | 0.00 |
December | 289.97 | 185.78 | 104.18 | 269.58 | 478.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 503.31 | 238.76 | 264.55 | 540.63 | 316.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 289.97 | 92.12 | 104.18 | 246.48 | 186.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 751.06 | 439.98 | 379.42 | 913.67 | 478.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 163.00 | 53.86 | 109.15 | 88.39 | 535.94 | 0.00 | 0.00 | 0.00 |
February | 288.61 | 121.86 | 166.75 | 210.42 | 524.93 | 0.00 | 0.00 | 0.00 |
March | 260.96 | 49.92 | 211.04 | 134.25 | 447.68 | 0.00 | 0.00 | 0.00 |
April | 615.75 | 244.58 | 371.17 | 597.14 | 374.13 | 0.00 | 0.00 | 0.00 |
May | 722.42 | 293.76 | 428.66 | 715.44 | 296.81 | 0.00 | 0.00 | 0.00 |
June | 780.14 | 321.15 | 458.98 | 833.61 | 241.35 | 0.00 | 0.00 | 0.00 |
July | 794.53 | 350.31 | 444.22 | 882.64 | 230.06 | 0.00 | 0.00 | 0.00 |
August | 667.36 | 288.95 | 378.41 | 745.16 | 254.24 | 0.00 | 0.00 | 0.00 |
September | 535.40 | 240.08 | 295.31 | 579.60 | 302.65 | 0.00 | 0.00 | 0.00 |
October | 285.61 | 102.71 | 182.91 | 231.86 | 418.43 | 0.00 | 0.00 | 0.00 |
November | 154.56 | 45.12 | 109.44 | 81.70 | 527.57 | 0.00 | 0.00 | 0.00 |
December | 87.49 | 18.46 | 69.03 | 24.91 | 650.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 446.79 | 177.64 | 269.16 | 427.82 | 399.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.49 | 18.46 | 69.03 | 24.91 | 230.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 794.53 | 350.31 | 458.98 | 882.64 | 650.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 163.00 | 53.86 | 109.15 | 88.39 | 535.94 | 0.00 | 0.00 | 0.00 |
February | 288.61 | 121.86 | 166.75 | 210.42 | 524.93 | 0.00 | 0.00 | 0.00 |
March | 260.96 | 49.92 | 211.04 | 134.25 | 447.68 | 0.00 | 0.00 | 0.00 |
April | 615.75 | 244.58 | 371.17 | 597.14 | 374.13 | 0.00 | 0.00 | 0.00 |
May | 722.42 | 293.76 | 428.66 | 715.44 | 296.81 | 0.00 | 0.00 | 0.00 |
June | 780.14 | 321.15 | 458.98 | 833.61 | 241.35 | 0.00 | 0.00 | 0.00 |
July | 794.53 | 350.31 | 444.22 | 882.64 | 230.06 | 0.00 | 0.00 | 0.00 |
August | 667.36 | 288.95 | 378.41 | 745.16 | 254.24 | 0.00 | 0.00 | 0.00 |
September | 535.40 | 240.08 | 295.31 | 579.60 | 302.65 | 0.00 | 0.00 | 0.00 |
October | 285.61 | 102.71 | 182.91 | 231.86 | 418.43 | 0.00 | 0.00 | 0.00 |
November | 154.56 | 45.12 | 109.44 | 81.70 | 527.57 | 0.00 | 0.00 | 0.00 |
December | 87.49 | 18.46 | 69.03 | 24.91 | 650.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 446.79 | 177.64 | 269.16 | 427.82 | 399.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.49 | 18.46 | 69.03 | 24.91 | 230.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 794.53 | 350.31 | 458.98 | 882.64 | 650.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 163.00 | 53.86 | 109.15 | 88.39 | 535.93 | 0.00 | 0.00 | 0.00 |
February | 288.60 | 121.86 | 166.75 | 210.42 | 524.93 | 0.00 | 0.00 | 0.00 |
March | 260.96 | 49.92 | 211.04 | 134.25 | 447.67 | 0.00 | 0.00 | 0.00 |
April | 615.74 | 244.58 | 371.16 | 597.12 | 374.12 | 0.00 | 0.00 | 0.00 |
May | 722.41 | 293.76 | 428.65 | 715.43 | 296.81 | 0.00 | 0.00 | 0.00 |
June | 780.12 | 321.15 | 458.98 | 833.60 | 241.34 | 0.00 | 0.00 | 0.00 |
July | 794.52 | 350.31 | 444.21 | 882.63 | 230.06 | 0.00 | 0.00 | 0.00 |
August | 667.34 | 288.94 | 378.40 | 745.15 | 254.24 | 0.00 | 0.00 | 0.00 |
September | 535.39 | 240.08 | 295.31 | 579.59 | 302.64 | 0.00 | 0.00 | 0.00 |
October | 285.61 | 102.70 | 182.90 | 231.86 | 418.43 | 0.00 | 0.00 | 0.00 |
November | 154.56 | 45.12 | 109.44 | 81.70 | 527.56 | 0.00 | 0.00 | 0.00 |
December | 87.49 | 18.46 | 69.02 | 24.91 | 650.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 446.78 | 177.63 | 269.15 | 427.82 | 399.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.49 | 18.46 | 69.02 | 24.91 | 230.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 794.52 | 350.31 | 458.98 | 882.63 | 650.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.04 | 0.00 | 369.04 | 24.43 | 2202.89 | 0.00 | 0.00 | 0.00 |
February | 576.27 | 0.00 | 576.27 | 83.63 | 2054.94 | 0.00 | 0.00 | 0.00 |
March | 797.45 | 0.00 | 797.45 | 257.01 | 1719.63 | 0.00 | 0.00 | 0.00 |
April | 1298.37 | 5.81 | 1292.56 | 812.93 | 1400.04 | 0.00 | 0.00 | 0.00 |
May | 1623.30 | 78.32 | 1544.98 | 1042.73 | 1112.64 | 0.00 | 0.00 | 0.00 |
June | 1794.45 | 112.52 | 1681.93 | 1477.87 | 883.17 | 0.00 | 0.00 | 0.00 |
July | 1702.14 | 97.05 | 1605.09 | 1499.90 | 814.40 | 0.00 | 0.00 | 0.00 |
August | 1337.97 | 20.96 | 1317.00 | 1152.60 | 912.05 | 0.00 | 0.00 | 0.00 |
September | 1018.38 | 0.23 | 1018.15 | 756.57 | 1210.96 | 0.00 | 0.00 | 0.00 |
October | 652.57 | 0.00 | 652.57 | 267.91 | 1602.95 | 0.00 | 0.00 | 0.00 |
November | 392.10 | 0.00 | 392.10 | 41.49 | 1947.12 | 0.00 | 0.00 | 0.00 |
December | 267.02 | 0.00 | 267.02 | 1.87 | 2340.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 987.58 | 26.42 | 961.17 | 620.95 | 1514.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 267.02 | 0.00 | 267.02 | 1.87 | 814.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1794.45 | 112.52 | 1681.93 | 1499.90 | 2340.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.86 | 202.00 | 300.86 | 291.08 | 1376.60 | 0.00 | 0.00 | 0.00 |
February | 749.86 | 277.00 | 472.85 | 483.21 | 1296.37 | 0.00 | 0.00 | 0.00 |
March | 783.62 | 154.42 | 629.19 | 478.15 | 1075.09 | 0.00 | 0.00 | 0.00 |
April | 2104.07 | 988.72 | 1115.35 | 2158.45 | 889.13 | 0.00 | 0.00 | 0.00 |
May | 2212.37 | 964.77 | 1247.59 | 2217.54 | 753.33 | 0.00 | 0.00 | 0.00 |
June | 2189.84 | 874.60 | 1315.24 | 2339.95 | 592.02 | 0.00 | 0.00 | 0.00 |
July | 2235.39 | 950.04 | 1285.35 | 2487.79 | 550.64 | 0.00 | 0.00 | 0.00 |
August | 2117.55 | 1011.74 | 1105.80 | 2426.58 | 599.78 | 0.00 | 0.00 | 0.00 |
September | 1906.92 | 1014.01 | 892.91 | 2113.34 | 764.57 | 0.00 | 0.00 | 0.00 |
October | 920.50 | 381.48 | 539.02 | 806.62 | 1017.40 | 0.00 | 0.00 | 0.00 |
November | 479.88 | 163.55 | 316.33 | 276.72 | 1225.07 | 0.00 | 0.00 | 0.00 |
December | 355.65 | 132.23 | 223.42 | 179.95 | 1482.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1381.87 | 593.64 | 788.23 | 1358.09 | 966.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.65 | 132.23 | 223.42 | 179.95 | 550.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2235.39 | 1014.01 | 1315.24 | 2487.79 | 1482.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2095.14 | 1356.27 | 738.87 | 2030.04 | 2030.53 | 0.00 | 0.00 | 0.00 |
February | 2558.83 | 1561.43 | 997.40 | 2544.04 | 1992.58 | 0.00 | 0.00 | 0.00 |
March | 1582.04 | 460.62 | 1121.42 | 1259.39 | 1662.69 | 0.00 | 0.00 | 0.00 |
April | 3285.23 | 1484.89 | 1800.35 | 3662.44 | 1472.34 | 0.00 | 0.00 | 0.00 |
May | 2717.19 | 884.63 | 1832.56 | 2817.73 | 1247.77 | 0.00 | 0.00 | 0.00 |
June | 2503.11 | 605.90 | 1897.21 | 2707.85 | 962.73 | 0.00 | 0.00 | 0.00 |
July | 2712.08 | 849.32 | 1862.76 | 3152.24 | 900.31 | 0.00 | 0.00 | 0.00 |
August | 3177.96 | 1429.56 | 1748.39 | 3897.28 | 990.85 | 0.00 | 0.00 | 0.00 |
September | 3755.52 | 2200.05 | 1555.47 | 4553.01 | 1263.57 | 0.00 | 0.00 | 0.00 |
October | 2580.20 | 1508.01 | 1072.19 | 2789.80 | 1602.33 | 0.00 | 0.00 | 0.00 |
November | 1829.36 | 1112.85 | 716.51 | 1785.84 | 1876.07 | 0.00 | 0.00 | 0.00 |
December | 1449.93 | 928.98 | 520.95 | 1369.58 | 2238.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2516.70 | 1193.89 | 1322.81 | 2710.43 | 1517.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1449.93 | 460.62 | 520.95 | 1259.39 | 900.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3755.52 | 2200.05 | 1897.21 | 4553.01 | 2238.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 489.01 | 161.57 | 327.44 | 288.53 | 1429.71 | 0.00 | 0.00 | 0.00 |
February | 865.82 | 365.58 | 500.24 | 672.87 | 1369.27 | 0.00 | 0.00 | 0.00 |
March | 782.88 | 149.77 | 633.12 | 470.71 | 1118.92 | 0.00 | 0.00 | 0.00 |
April | 1847.24 | 733.74 | 1113.50 | 1862.90 | 968.82 | 0.00 | 0.00 | 0.00 |
May | 2167.24 | 881.27 | 1285.96 | 2180.63 | 823.21 | 0.00 | 0.00 | 0.00 |
June | 2340.38 | 963.45 | 1376.94 | 2536.53 | 656.24 | 0.00 | 0.00 | 0.00 |
July | 2383.58 | 1050.93 | 1332.65 | 2694.30 | 616.84 | 0.00 | 0.00 | 0.00 |
August | 2002.05 | 866.83 | 1135.22 | 2286.82 | 671.26 | 0.00 | 0.00 | 0.00 |
September | 1606.17 | 720.24 | 885.93 | 1771.64 | 832.39 | 0.00 | 0.00 | 0.00 |
October | 856.83 | 308.11 | 548.72 | 743.05 | 1074.18 | 0.00 | 0.00 | 0.00 |
November | 463.69 | 135.36 | 328.33 | 279.23 | 1293.47 | 0.00 | 0.00 | 0.00 |
December | 262.46 | 55.38 | 207.08 | 93.73 | 1576.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1340.36 | 532.90 | 807.46 | 1325.59 | 1034.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 262.46 | 55.38 | 207.08 | 93.73 | 616.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2383.58 | 1050.93 | 1376.94 | 2694.30 | 1576.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.04 | 0.00 | 369.04 | 40.37 | 1989.34 | 0.00 | 0.00 | 0.00 |
February | 576.27 | 0.00 | 576.27 | 120.33 | 1856.60 | 0.00 | 0.00 | 0.00 |
March | 797.45 | 0.00 | 797.45 | 302.76 | 1561.99 | 0.00 | 0.00 | 0.00 |
April | 1298.37 | 5.81 | 1292.56 | 854.79 | 1301.71 | 0.00 | 0.00 | 0.00 |
May | 1623.30 | 78.32 | 1544.98 | 1093.35 | 1039.70 | 0.00 | 0.00 | 0.00 |
June | 1794.45 | 112.52 | 1681.93 | 1497.87 | 845.63 | 0.00 | 0.00 | 0.00 |
July | 1702.14 | 97.05 | 1605.09 | 1516.16 | 782.89 | 0.00 | 0.00 | 0.00 |
August | 1337.97 | 20.96 | 1317.00 | 1166.35 | 875.80 | 0.00 | 0.00 | 0.00 |
September | 1018.38 | 0.23 | 1018.15 | 788.18 | 1133.55 | 0.00 | 0.00 | 0.00 |
October | 652.57 | 0.00 | 652.57 | 313.61 | 1431.68 | 0.00 | 0.00 | 0.00 |
November | 392.10 | 0.00 | 392.10 | 62.40 | 1738.38 | 0.00 | 0.00 | 0.00 |
December | 267.02 | 0.00 | 267.02 | 9.19 | 2127.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 987.58 | 26.42 | 961.17 | 649.76 | 1388.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 267.02 | 0.00 | 267.02 | 9.19 | 782.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1794.45 | 112.52 | 1681.93 | 1516.16 | 2127.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.86 | 202.00 | 300.86 | 310.52 | 1252.91 | 0.00 | 0.00 | 0.00 |
February | 749.86 | 277.00 | 472.85 | 513.97 | 1183.54 | 0.00 | 0.00 | 0.00 |
March | 783.62 | 154.42 | 629.19 | 506.68 | 991.32 | 0.00 | 0.00 | 0.00 |
April | 2104.07 | 988.72 | 1115.35 | 2178.24 | 842.67 | 0.00 | 0.00 | 0.00 |
May | 2212.37 | 964.77 | 1247.59 | 2236.51 | 716.43 | 0.00 | 0.00 | 0.00 |
June | 2189.84 | 874.60 | 1315.24 | 2344.76 | 573.73 | 0.00 | 0.00 | 0.00 |
July | 2235.39 | 950.04 | 1285.35 | 2489.22 | 536.08 | 0.00 | 0.00 | 0.00 |
August | 2117.55 | 1011.74 | 1105.80 | 2427.31 | 585.15 | 0.00 | 0.00 | 0.00 |
September | 1906.92 | 1014.01 | 892.91 | 2125.04 | 731.22 | 0.00 | 0.00 | 0.00 |
October | 920.50 | 381.48 | 539.02 | 834.60 | 927.42 | 0.00 | 0.00 | 0.00 |
November | 479.88 | 163.55 | 316.33 | 296.12 | 1110.28 | 0.00 | 0.00 | 0.00 |
December | 355.65 | 132.23 | 223.42 | 194.18 | 1356.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1381.87 | 593.64 | 788.23 | 1374.48 | 899.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.65 | 132.23 | 223.42 | 194.18 | 536.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2235.39 | 1014.01 | 1315.24 | 2489.22 | 1356.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2095.14 | 1356.27 | 738.87 | 2080.13 | 1844.99 | 0.00 | 0.00 | 0.00 |
February | 2558.83 | 1561.43 | 997.40 | 2598.03 | 1821.37 | 0.00 | 0.00 | 0.00 |
March | 1582.04 | 460.62 | 1121.42 | 1307.26 | 1528.45 | 0.00 | 0.00 | 0.00 |
April | 3285.23 | 1484.89 | 1800.35 | 3690.08 | 1392.30 | 0.00 | 0.00 | 0.00 |
May | 2717.19 | 884.63 | 1832.56 | 2845.33 | 1178.78 | 0.00 | 0.00 | 0.00 |
June | 2503.11 | 605.90 | 1897.21 | 2720.82 | 925.87 | 0.00 | 0.00 | 0.00 |
July | 2712.08 | 849.32 | 1862.76 | 3160.52 | 869.14 | 0.00 | 0.00 | 0.00 |
August | 3177.96 | 1429.56 | 1748.39 | 3901.36 | 960.39 | 0.00 | 0.00 | 0.00 |
September | 3755.52 | 2200.05 | 1555.47 | 4568.20 | 1205.62 | 0.00 | 0.00 | 0.00 |
October | 2580.20 | 1508.01 | 1072.19 | 2828.24 | 1463.62 | 0.00 | 0.00 | 0.00 |
November | 1829.36 | 1112.85 | 716.51 | 1825.01 | 1699.22 | 0.00 | 0.00 | 0.00 |
December | 1449.93 | 928.98 | 520.95 | 1403.59 | 2043.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2516.70 | 1193.89 | 1322.81 | 2740.24 | 1408.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1449.93 | 460.62 | 520.95 | 1307.26 | 869.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3755.52 | 2200.05 | 1897.21 | 4568.20 | 2043.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 489.01 | 161.57 | 327.44 | 302.88 | 1316.05 | 0.00 | 0.00 | 0.00 |
February | 865.82 | 365.58 | 500.24 | 693.15 | 1268.53 | 0.00 | 0.00 | 0.00 |
March | 782.88 | 149.77 | 633.12 | 491.79 | 1042.44 | 0.00 | 0.00 | 0.00 |
April | 1847.24 | 733.74 | 1113.50 | 1880.59 | 919.88 | 0.00 | 0.00 | 0.00 |
May | 2167.24 | 881.27 | 1285.96 | 2196.35 | 783.11 | 0.00 | 0.00 | 0.00 |
June | 2340.38 | 963.45 | 1376.94 | 2542.03 | 633.77 | 0.00 | 0.00 | 0.00 |
July | 2383.58 | 1050.93 | 1332.65 | 2697.25 | 597.43 | 0.00 | 0.00 | 0.00 |
August | 2002.05 | 866.83 | 1135.22 | 2290.53 | 650.61 | 0.00 | 0.00 | 0.00 |
September | 1606.17 | 720.24 | 885.93 | 1783.72 | 793.97 | 0.00 | 0.00 | 0.00 |
October | 856.83 | 308.11 | 548.72 | 763.35 | 992.17 | 0.00 | 0.00 | 0.00 |
November | 463.69 | 135.36 | 328.33 | 291.02 | 1190.58 | 0.00 | 0.00 | 0.00 |
December | 262.46 | 55.38 | 207.08 | 100.91 | 1460.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1340.36 | 532.90 | 807.46 | 1338.26 | 969.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 262.46 | 55.38 | 207.08 | 100.91 | 597.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2383.58 | 1050.93 | 1376.94 | 2697.25 | 1460.05 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197686E+09 | 0.00 | 0.197686E+09 | 6762320.18 | 0.132672E+10 |
February | 0.278821E+09 | 0.00 | 0.278821E+09 | 23619612.92 | 0.112001E+10 |
March | 0.427178E+09 | 0.00 | 0.427178E+09 | 0.109076E+09 | 0.104003E+10 |
April | 0.673077E+09 | 3012392.23 | 0.670065E+09 | 0.397109E+09 | 0.792665E+09 |
May | 0.869568E+09 | 41952227.78 | 0.827616E+09 | 0.536477E+09 | 0.635468E+09 |
June | 0.930245E+09 | 58332032.45 | 0.871913E+09 | 0.754527E+09 | 0.483397E+09 |
July | 0.911801E+09 | 51986276.96 | 0.859815E+09 | 0.785363E+09 | 0.463060E+09 |
August | 0.716723E+09 | 11229192.55 | 0.705494E+09 | 0.600678E+09 | 0.521105E+09 |
September | 0.527927E+09 | 116818.82 | 0.527810E+09 | 0.376239E+09 | 0.670925E+09 |
October | 0.349568E+09 | 0.00 | 0.349568E+09 | 0.120533E+09 | 0.963718E+09 |
November | 0.203263E+09 | 0.00 | 0.203263E+09 | 11023969.17 | 0.117170E+10 |
December | 0.143035E+09 | 0.00 | 0.143035E+09 | 14742.10 | 0.146497E+10 |
Annual Sum or Average | 0.622889E+10 | 0.166629E+09 | 0.606226E+10 | 0.372142E+10 | 0.106538E+11 |
Minimum of Months | 0.143035E+09 | 0.00 | 0.143035E+09 | 14742.10 | 0.463060E+09 |
Maximum of Months | 0.930245E+09 | 58332032.45 | 0.871913E+09 | 0.785363E+09 | 0.146497E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197682E+09 | 0.00 | 0.197682E+09 | 6761611.64 | 0.132672E+10 |
February | 0.278816E+09 | 0.00 | 0.278816E+09 | 23617469.13 | 0.112001E+10 |
March | 0.427171E+09 | 0.00 | 0.427171E+09 | 0.109070E+09 | 0.104003E+10 |
April | 0.673068E+09 | 3012326.01 | 0.670055E+09 | 0.397098E+09 | 0.792665E+09 |
May | 0.869556E+09 | 41951305.51 | 0.827604E+09 | 0.536463E+09 | 0.635468E+09 |
June | 0.930231E+09 | 58330750.09 | 0.871900E+09 | 0.754510E+09 | 0.483396E+09 |
July | 0.911788E+09 | 51985134.10 | 0.859803E+09 | 0.785346E+09 | 0.463060E+09 |
August | 0.716713E+09 | 11228945.69 | 0.705484E+09 | 0.600667E+09 | 0.521104E+09 |
September | 0.527920E+09 | 116816.25 | 0.527803E+09 | 0.376231E+09 | 0.670924E+09 |
October | 0.349562E+09 | 0.00 | 0.349562E+09 | 0.120529E+09 | 0.963717E+09 |
November | 0.203260E+09 | 0.00 | 0.203260E+09 | 11022926.61 | 0.117170E+10 |
December | 0.143033E+09 | 0.00 | 0.143033E+09 | 14733.21 | 0.146497E+10 |
Annual Sum or Average | 0.622880E+10 | 0.166625E+09 | 0.606217E+10 | 0.372133E+10 | 0.106538E+11 |
Minimum of Months | 0.143033E+09 | 0.00 | 0.143033E+09 | 14733.21 | 0.463060E+09 |
Maximum of Months | 0.930231E+09 | 58330750.09 | 0.871900E+09 | 0.785346E+09 | 0.146497E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197683E+09 | 0.00 | 0.197683E+09 | 6761847.82 | 0.132672E+10 |
February | 0.278818E+09 | 0.00 | 0.278818E+09 | 23618183.72 | 0.112001E+10 |
March | 0.427173E+09 | 0.00 | 0.427173E+09 | 0.109072E+09 | 0.104003E+10 |
April | 0.673071E+09 | 3012348.08 | 0.670058E+09 | 0.397102E+09 | 0.792665E+09 |
May | 0.869560E+09 | 41951612.94 | 0.827608E+09 | 0.536468E+09 | 0.635468E+09 |
June | 0.930236E+09 | 58331177.54 | 0.871904E+09 | 0.754515E+09 | 0.483397E+09 |
July | 0.911792E+09 | 51985515.06 | 0.859807E+09 | 0.785352E+09 | 0.463060E+09 |
August | 0.716716E+09 | 11229027.98 | 0.705487E+09 | 0.600671E+09 | 0.521104E+09 |
September | 0.527922E+09 | 116817.10 | 0.527805E+09 | 0.376234E+09 | 0.670924E+09 |
October | 0.349564E+09 | 0.00 | 0.349564E+09 | 0.120530E+09 | 0.963717E+09 |
November | 0.203261E+09 | 0.00 | 0.203261E+09 | 11023274.13 | 0.117170E+10 |
December | 0.143034E+09 | 0.00 | 0.143034E+09 | 14736.17 | 0.146497E+10 |
Annual Sum or Average | 0.622883E+10 | 0.166626E+09 | 0.606220E+10 | 0.372136E+10 | 0.106538E+11 |
Minimum of Months | 0.143034E+09 | 0.00 | 0.143034E+09 | 14736.17 | 0.463060E+09 |
Maximum of Months | 0.930236E+09 | 58331177.54 | 0.871904E+09 | 0.785352E+09 | 0.146497E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197682E+09 | 0.00 | 0.197682E+09 | 6761611.64 | 0.132672E+10 |
February | 0.278816E+09 | 0.00 | 0.278816E+09 | 23617469.13 | 0.112001E+10 |
March | 0.427171E+09 | 0.00 | 0.427171E+09 | 0.109070E+09 | 0.104003E+10 |
April | 0.673068E+09 | 3012326.01 | 0.670055E+09 | 0.397098E+09 | 0.792665E+09 |
May | 0.869556E+09 | 41951305.51 | 0.827604E+09 | 0.536463E+09 | 0.635468E+09 |
June | 0.930231E+09 | 58330750.09 | 0.871900E+09 | 0.754510E+09 | 0.483396E+09 |
July | 0.911788E+09 | 51985134.10 | 0.859803E+09 | 0.785346E+09 | 0.463060E+09 |
August | 0.716713E+09 | 11228945.69 | 0.705484E+09 | 0.600667E+09 | 0.521104E+09 |
September | 0.527920E+09 | 116816.25 | 0.527803E+09 | 0.376231E+09 | 0.670924E+09 |
October | 0.349562E+09 | 0.00 | 0.349562E+09 | 0.120529E+09 | 0.963717E+09 |
November | 0.203260E+09 | 0.00 | 0.203260E+09 | 11022926.61 | 0.117170E+10 |
December | 0.143033E+09 | 0.00 | 0.143033E+09 | 14733.21 | 0.146497E+10 |
Annual Sum or Average | 0.622880E+10 | 0.166625E+09 | 0.606217E+10 | 0.372133E+10 | 0.106538E+11 |
Minimum of Months | 0.143033E+09 | 0.00 | 0.143033E+09 | 14733.21 | 0.463060E+09 |
Maximum of Months | 0.930231E+09 | 58330750.09 | 0.871900E+09 | 0.785346E+09 | 0.146497E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197675E+09 | 0.00 | 0.197675E+09 | 6761457.20 | 0.132667E+10 |
February | 0.278806E+09 | 0.00 | 0.278806E+09 | 23616874.52 | 0.111997E+10 |
March | 0.427155E+09 | 0.00 | 0.427155E+09 | 0.109067E+09 | 0.103998E+10 |
April | 0.673042E+09 | 3012215.64 | 0.670030E+09 | 0.397084E+09 | 0.792633E+09 |
May | 0.869523E+09 | 41949768.39 | 0.827573E+09 | 0.536443E+09 | 0.635443E+09 |
June | 0.930196E+09 | 58328612.82 | 0.871867E+09 | 0.754482E+09 | 0.483377E+09 |
July | 0.911753E+09 | 51983229.34 | 0.859770E+09 | 0.785318E+09 | 0.463041E+09 |
August | 0.716686E+09 | 11228534.26 | 0.705457E+09 | 0.600645E+09 | 0.521083E+09 |
September | 0.527900E+09 | 116811.97 | 0.527783E+09 | 0.376217E+09 | 0.670897E+09 |
October | 0.349549E+09 | 0.00 | 0.349549E+09 | 0.120525E+09 | 0.963678E+09 |
November | 0.203252E+09 | 0.00 | 0.203252E+09 | 11022656.09 | 0.117165E+10 |
December | 0.143028E+09 | 0.00 | 0.143028E+09 | 14734.09 | 0.146491E+10 |
Annual Sum or Average | 0.622856E+10 | 0.166619E+09 | 0.606194E+10 | 0.372120E+10 | 0.106533E+11 |
Minimum of Months | 0.143028E+09 | 0.00 | 0.143028E+09 | 14734.09 | 0.463041E+09 |
Maximum of Months | 0.930196E+09 | 58328612.82 | 0.871867E+09 | 0.785318E+09 | 0.146491E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.448960E+09 | 0.180348E+09 | 0.268612E+09 | 0.243539E+09 | 0.134165E+10 |
February | 0.604690E+09 | 0.223377E+09 | 0.381313E+09 | 0.369826E+09 | 0.113239E+10 |
March | 0.699619E+09 | 0.137869E+09 | 0.561750E+09 | 0.397861E+09 | 0.104092E+10 |
April | 0.181794E+10 | 0.854261E+09 | 0.963676E+09 | 0.186045E+10 | 0.801946E+09 |
May | 0.197522E+10 | 0.861360E+09 | 0.111386E+10 | 0.197588E+10 | 0.706220E+09 |
June | 0.189204E+10 | 0.755662E+09 | 0.113638E+10 | 0.202277E+10 | 0.530957E+09 |
July | 0.199578E+10 | 0.848205E+09 | 0.114757E+10 | 0.222716E+10 | 0.504036E+09 |
August | 0.189056E+10 | 0.903294E+09 | 0.987270E+09 | 0.217105E+10 | 0.542922E+09 |
September | 0.164760E+10 | 0.876117E+09 | 0.771480E+09 | 0.182451E+10 | 0.689627E+09 |
October | 0.821827E+09 | 0.340586E+09 | 0.481241E+09 | 0.701079E+09 | 0.986476E+09 |
November | 0.414622E+09 | 0.141309E+09 | 0.273313E+09 | 0.223302E+09 | 0.117241E+10 |
December | 0.317528E+09 | 0.118053E+09 | 0.199476E+09 | 0.146955E+09 | 0.146641E+10 |
Annual Sum or Average | 0.145264E+11 | 0.624044E+10 | 0.828594E+10 | 0.141644E+11 | 0.109160E+11 |
Minimum of Months | 0.317528E+09 | 0.118053E+09 | 0.199476E+09 | 0.146955E+09 | 0.504036E+09 |
Maximum of Months | 0.199578E+10 | 0.903294E+09 | 0.114757E+10 | 0.222716E+10 | 0.146641E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.448960E+09 | 0.180348E+09 | 0.268612E+09 | 0.243539E+09 | 0.134165E+10 |
February | 0.604690E+09 | 0.223377E+09 | 0.381313E+09 | 0.369826E+09 | 0.113239E+10 |
March | 0.699619E+09 | 0.137869E+09 | 0.561750E+09 | 0.397861E+09 | 0.104092E+10 |
April | 0.181794E+10 | 0.854261E+09 | 0.963676E+09 | 0.186045E+10 | 0.801946E+09 |
May | 0.197522E+10 | 0.861360E+09 | 0.111386E+10 | 0.197588E+10 | 0.706220E+09 |
June | 0.189204E+10 | 0.755662E+09 | 0.113638E+10 | 0.202277E+10 | 0.530957E+09 |
July | 0.199578E+10 | 0.848205E+09 | 0.114757E+10 | 0.222716E+10 | 0.504036E+09 |
August | 0.189056E+10 | 0.903294E+09 | 0.987270E+09 | 0.217105E+10 | 0.542922E+09 |
September | 0.164760E+10 | 0.876117E+09 | 0.771480E+09 | 0.182451E+10 | 0.689627E+09 |
October | 0.821827E+09 | 0.340586E+09 | 0.481241E+09 | 0.701079E+09 | 0.986476E+09 |
November | 0.414622E+09 | 0.141309E+09 | 0.273313E+09 | 0.223302E+09 | 0.117241E+10 |
December | 0.317528E+09 | 0.118053E+09 | 0.199476E+09 | 0.146955E+09 | 0.146641E+10 |
Annual Sum or Average | 0.145264E+11 | 0.624044E+10 | 0.828594E+10 | 0.141644E+11 | 0.109160E+11 |
Minimum of Months | 0.317528E+09 | 0.118053E+09 | 0.199476E+09 | 0.146955E+09 | 0.504036E+09 |
Maximum of Months | 0.199578E+10 | 0.903294E+09 | 0.114757E+10 | 0.222716E+10 | 0.146641E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.448952E+09 | 0.180345E+09 | 0.268607E+09 | 0.243535E+09 | 0.134162E+10 |
February | 0.604679E+09 | 0.223373E+09 | 0.381306E+09 | 0.369820E+09 | 0.113237E+10 |
March | 0.699607E+09 | 0.137867E+09 | 0.561740E+09 | 0.397853E+09 | 0.104090E+10 |
April | 0.181790E+10 | 0.854245E+09 | 0.963659E+09 | 0.186041E+10 | 0.801931E+09 |
May | 0.197518E+10 | 0.861344E+09 | 0.111384E+10 | 0.197585E+10 | 0.706207E+09 |
June | 0.189200E+10 | 0.755648E+09 | 0.113636E+10 | 0.202273E+10 | 0.530947E+09 |
July | 0.199574E+10 | 0.848190E+09 | 0.114755E+10 | 0.222712E+10 | 0.504027E+09 |
August | 0.189053E+10 | 0.903277E+09 | 0.987252E+09 | 0.217102E+10 | 0.542912E+09 |
September | 0.164757E+10 | 0.876101E+09 | 0.771466E+09 | 0.182448E+10 | 0.689615E+09 |
October | 0.821812E+09 | 0.340580E+09 | 0.481232E+09 | 0.701066E+09 | 0.986458E+09 |
November | 0.414615E+09 | 0.141307E+09 | 0.273308E+09 | 0.223298E+09 | 0.117239E+10 |
December | 0.317523E+09 | 0.118050E+09 | 0.199472E+09 | 0.146953E+09 | 0.146638E+10 |
Annual Sum or Average | 0.145261E+11 | 0.624033E+10 | 0.828579E+10 | 0.141641E+11 | 0.109158E+11 |
Minimum of Months | 0.317523E+09 | 0.118050E+09 | 0.199472E+09 | 0.146953E+09 | 0.504027E+09 |
Maximum of Months | 0.199574E+10 | 0.903277E+09 | 0.114755E+10 | 0.222712E+10 | 0.146638E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112230E+10 | 0.726512E+09 | 0.395792E+09 | 0.108167E+10 | 0.112742E+10 |
February | 0.123804E+10 | 0.755468E+09 | 0.482573E+09 | 0.122725E+10 | 0.997539E+09 |
March | 0.847452E+09 | 0.246739E+09 | 0.600713E+09 | 0.660194E+09 | 0.941931E+09 |
April | 0.170304E+10 | 0.769749E+09 | 0.933287E+09 | 0.189808E+10 | 0.789755E+09 |
May | 0.145552E+10 | 0.473868E+09 | 0.981656E+09 | 0.150877E+10 | 0.689583E+09 |
June | 0.129760E+10 | 0.314092E+09 | 0.983505E+09 | 0.139998E+10 | 0.517808E+09 |
July | 0.145278E+10 | 0.454953E+09 | 0.997832E+09 | 0.168553E+10 | 0.498388E+09 |
August | 0.170234E+10 | 0.765773E+09 | 0.936569E+09 | 0.208752E+10 | 0.543413E+09 |
September | 0.194683E+10 | 0.114048E+10 | 0.806347E+09 | 0.236834E+10 | 0.667018E+09 |
October | 0.138213E+10 | 0.807793E+09 | 0.574341E+09 | 0.149236E+10 | 0.894549E+09 |
November | 0.948321E+09 | 0.576887E+09 | 0.371434E+09 | 0.918305E+09 | 0.103301E+10 |
December | 0.776686E+09 | 0.497625E+09 | 0.279060E+09 | 0.722080E+09 | 0.128126E+10 |
Annual Sum or Average | 0.158730E+11 | 0.752994E+10 | 0.834311E+10 | 0.170501E+11 | 0.998168E+10 |
Minimum of Months | 0.776686E+09 | 0.246739E+09 | 0.279060E+09 | 0.660194E+09 | 0.498388E+09 |
Maximum of Months | 0.194683E+10 | 0.114048E+10 | 0.997832E+09 | 0.236834E+10 | 0.128126E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112230E+10 | 0.726507E+09 | 0.395789E+09 | 0.108166E+10 | 0.112742E+10 |
February | 0.123803E+10 | 0.755463E+09 | 0.482570E+09 | 0.122724E+10 | 0.997539E+09 |
March | 0.847446E+09 | 0.246737E+09 | 0.600709E+09 | 0.660188E+09 | 0.941931E+09 |
April | 0.170303E+10 | 0.769743E+09 | 0.933282E+09 | 0.189807E+10 | 0.789755E+09 |
May | 0.145552E+10 | 0.473865E+09 | 0.981651E+09 | 0.150876E+10 | 0.689583E+09 |
June | 0.129759E+10 | 0.314089E+09 | 0.983500E+09 | 0.139997E+10 | 0.517808E+09 |
July | 0.145278E+10 | 0.454949E+09 | 0.997827E+09 | 0.168552E+10 | 0.498388E+09 |
August | 0.170233E+10 | 0.765767E+09 | 0.936565E+09 | 0.208751E+10 | 0.543412E+09 |
September | 0.194681E+10 | 0.114047E+10 | 0.806342E+09 | 0.236832E+10 | 0.667017E+09 |
October | 0.138212E+10 | 0.807787E+09 | 0.574337E+09 | 0.149234E+10 | 0.894549E+09 |
November | 0.948314E+09 | 0.576883E+09 | 0.371432E+09 | 0.918297E+09 | 0.103301E+10 |
December | 0.776680E+09 | 0.497622E+09 | 0.279058E+09 | 0.722074E+09 | 0.128126E+10 |
Annual Sum or Average | 0.158729E+11 | 0.752988E+10 | 0.834306E+10 | 0.170499E+11 | 0.998168E+10 |
Minimum of Months | 0.776680E+09 | 0.246737E+09 | 0.279058E+09 | 0.660188E+09 | 0.498388E+09 |
Maximum of Months | 0.194681E+10 | 0.114047E+10 | 0.997827E+09 | 0.236832E+10 | 0.128126E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112230E+10 | 0.726512E+09 | 0.395792E+09 | 0.108167E+10 | 0.112742E+10 |
February | 0.123804E+10 | 0.755468E+09 | 0.482573E+09 | 0.122725E+10 | 0.997539E+09 |
March | 0.847452E+09 | 0.246739E+09 | 0.600713E+09 | 0.660194E+09 | 0.941931E+09 |
April | 0.170304E+10 | 0.769749E+09 | 0.933287E+09 | 0.189808E+10 | 0.789755E+09 |
May | 0.145552E+10 | 0.473868E+09 | 0.981656E+09 | 0.150877E+10 | 0.689583E+09 |
June | 0.129760E+10 | 0.314092E+09 | 0.983505E+09 | 0.139998E+10 | 0.517808E+09 |
July | 0.145278E+10 | 0.454953E+09 | 0.997832E+09 | 0.168553E+10 | 0.498388E+09 |
August | 0.170234E+10 | 0.765773E+09 | 0.936569E+09 | 0.208752E+10 | 0.543413E+09 |
September | 0.194683E+10 | 0.114048E+10 | 0.806347E+09 | 0.236834E+10 | 0.667018E+09 |
October | 0.138213E+10 | 0.807793E+09 | 0.574341E+09 | 0.149236E+10 | 0.894549E+09 |
November | 0.948321E+09 | 0.576887E+09 | 0.371434E+09 | 0.918305E+09 | 0.103301E+10 |
December | 0.776686E+09 | 0.497625E+09 | 0.279060E+09 | 0.722080E+09 | 0.128126E+10 |
Annual Sum or Average | 0.158730E+11 | 0.752994E+10 | 0.834311E+10 | 0.170501E+11 | 0.998168E+10 |
Minimum of Months | 0.776686E+09 | 0.246739E+09 | 0.279060E+09 | 0.660194E+09 | 0.498388E+09 |
Maximum of Months | 0.194683E+10 | 0.114048E+10 | 0.997832E+09 | 0.236834E+10 | 0.128126E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112230E+10 | 0.726507E+09 | 0.395789E+09 | 0.108166E+10 | 0.112742E+10 |
February | 0.123803E+10 | 0.755463E+09 | 0.482570E+09 | 0.122724E+10 | 0.997539E+09 |
March | 0.847446E+09 | 0.246737E+09 | 0.600709E+09 | 0.660188E+09 | 0.941931E+09 |
April | 0.170303E+10 | 0.769743E+09 | 0.933282E+09 | 0.189807E+10 | 0.789755E+09 |
May | 0.145552E+10 | 0.473865E+09 | 0.981651E+09 | 0.150876E+10 | 0.689583E+09 |
June | 0.129759E+10 | 0.314089E+09 | 0.983500E+09 | 0.139997E+10 | 0.517808E+09 |
July | 0.145278E+10 | 0.454949E+09 | 0.997827E+09 | 0.168552E+10 | 0.498388E+09 |
August | 0.170233E+10 | 0.765767E+09 | 0.936565E+09 | 0.208751E+10 | 0.543412E+09 |
September | 0.194681E+10 | 0.114047E+10 | 0.806342E+09 | 0.236832E+10 | 0.667017E+09 |
October | 0.138212E+10 | 0.807787E+09 | 0.574337E+09 | 0.149234E+10 | 0.894549E+09 |
November | 0.948314E+09 | 0.576883E+09 | 0.371432E+09 | 0.918297E+09 | 0.103301E+10 |
December | 0.776680E+09 | 0.497622E+09 | 0.279058E+09 | 0.722074E+09 | 0.128126E+10 |
Annual Sum or Average | 0.158729E+11 | 0.752988E+10 | 0.834306E+10 | 0.170499E+11 | 0.998168E+10 |
Minimum of Months | 0.776680E+09 | 0.246737E+09 | 0.279058E+09 | 0.660188E+09 | 0.498388E+09 |
Maximum of Months | 0.194681E+10 | 0.114047E+10 | 0.997827E+09 | 0.236832E+10 | 0.128126E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112226E+10 | 0.726481E+09 | 0.395775E+09 | 0.108162E+10 | 0.112738E+10 |
February | 0.123799E+10 | 0.755435E+09 | 0.482552E+09 | 0.122720E+10 | 0.997499E+09 |
March | 0.847415E+09 | 0.246728E+09 | 0.600687E+09 | 0.660164E+09 | 0.941893E+09 |
April | 0.170296E+10 | 0.769715E+09 | 0.933247E+09 | 0.189800E+10 | 0.789723E+09 |
May | 0.145546E+10 | 0.473847E+09 | 0.981614E+09 | 0.150870E+10 | 0.689556E+09 |
June | 0.129754E+10 | 0.314078E+09 | 0.983463E+09 | 0.139992E+10 | 0.517787E+09 |
July | 0.145272E+10 | 0.454933E+09 | 0.997790E+09 | 0.168545E+10 | 0.498368E+09 |
August | 0.170227E+10 | 0.765739E+09 | 0.936529E+09 | 0.208743E+10 | 0.543391E+09 |
September | 0.194674E+10 | 0.114043E+10 | 0.806312E+09 | 0.236823E+10 | 0.666991E+09 |
October | 0.138207E+10 | 0.807757E+09 | 0.574316E+09 | 0.149229E+10 | 0.894513E+09 |
November | 0.948279E+09 | 0.576861E+09 | 0.371418E+09 | 0.918264E+09 | 0.103297E+10 |
December | 0.776652E+09 | 0.497603E+09 | 0.279048E+09 | 0.722048E+09 | 0.128121E+10 |
Annual Sum or Average | 0.158724E+11 | 0.752961E+10 | 0.834275E+10 | 0.170493E+11 | 0.998128E+10 |
Minimum of Months | 0.776652E+09 | 0.246728E+09 | 0.279048E+09 | 0.660164E+09 | 0.498368E+09 |
Maximum of Months | 0.194674E+10 | 0.114043E+10 | 0.997790E+09 | 0.236823E+10 | 0.128121E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.436592E+09 | 0.144252E+09 | 0.292340E+09 | 0.236747E+09 | 0.143546E+10 |
February | 0.698201E+09 | 0.294803E+09 | 0.403398E+09 | 0.509056E+09 | 0.126992E+10 |
March | 0.698965E+09 | 0.133712E+09 | 0.565253E+09 | 0.359580E+09 | 0.119907E+10 |
April | 0.159603E+10 | 0.633957E+09 | 0.962074E+09 | 0.154777E+10 | 0.969737E+09 |
May | 0.193493E+10 | 0.786810E+09 | 0.114812E+10 | 0.191624E+10 | 0.794978E+09 |
June | 0.202211E+10 | 0.832427E+09 | 0.118969E+10 | 0.216073E+10 | 0.625567E+09 |
July | 0.212808E+10 | 0.938277E+09 | 0.118980E+10 | 0.236407E+10 | 0.616191E+09 |
August | 0.178745E+10 | 0.773914E+09 | 0.101353E+10 | 0.199583E+10 | 0.680968E+09 |
September | 0.138775E+10 | 0.622298E+09 | 0.765451E+09 | 0.150232E+10 | 0.784458E+09 |
October | 0.764987E+09 | 0.275086E+09 | 0.489901E+09 | 0.621019E+09 | 0.112073E+10 |
November | 0.400630E+09 | 0.116949E+09 | 0.283681E+09 | 0.211759E+09 | 0.136747E+10 |
December | 0.234328E+09 | 49448223.76 | 0.184879E+09 | 66712946.24 | 0.174288E+10 |
Annual Sum or Average | 0.140901E+11 | 0.560193E+10 | 0.848812E+10 | 0.134918E+11 | 0.126074E+11 |
Minimum of Months | 0.234328E+09 | 49448223.76 | 0.184879E+09 | 66712946.24 | 0.616191E+09 |
Maximum of Months | 0.212808E+10 | 0.938277E+09 | 0.118980E+10 | 0.236407E+10 | 0.174288E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.436592E+09 | 0.144252E+09 | 0.292340E+09 | 0.236747E+09 | 0.143546E+10 |
February | 0.698201E+09 | 0.294803E+09 | 0.403398E+09 | 0.509056E+09 | 0.126992E+10 |
March | 0.698965E+09 | 0.133712E+09 | 0.565253E+09 | 0.359580E+09 | 0.119907E+10 |
April | 0.159603E+10 | 0.633957E+09 | 0.962074E+09 | 0.154777E+10 | 0.969737E+09 |
May | 0.193493E+10 | 0.786810E+09 | 0.114812E+10 | 0.191624E+10 | 0.794978E+09 |
June | 0.202211E+10 | 0.832427E+09 | 0.118969E+10 | 0.216073E+10 | 0.625567E+09 |
July | 0.212808E+10 | 0.938277E+09 | 0.118980E+10 | 0.236407E+10 | 0.616191E+09 |
August | 0.178745E+10 | 0.773914E+09 | 0.101353E+10 | 0.199583E+10 | 0.680968E+09 |
September | 0.138775E+10 | 0.622298E+09 | 0.765451E+09 | 0.150232E+10 | 0.784458E+09 |
October | 0.764987E+09 | 0.275086E+09 | 0.489901E+09 | 0.621019E+09 | 0.112073E+10 |
November | 0.400630E+09 | 0.116949E+09 | 0.283681E+09 | 0.211759E+09 | 0.136747E+10 |
December | 0.234328E+09 | 49448223.76 | 0.184879E+09 | 66712946.24 | 0.174288E+10 |
Annual Sum or Average | 0.140901E+11 | 0.560193E+10 | 0.848812E+10 | 0.134918E+11 | 0.126074E+11 |
Minimum of Months | 0.234328E+09 | 49448223.76 | 0.184879E+09 | 66712946.24 | 0.616191E+09 |
Maximum of Months | 0.212808E+10 | 0.938277E+09 | 0.118980E+10 | 0.236407E+10 | 0.174288E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.436584E+09 | 0.144249E+09 | 0.292335E+09 | 0.236743E+09 | 0.143543E+10 |
February | 0.698188E+09 | 0.294797E+09 | 0.403391E+09 | 0.509047E+09 | 0.126990E+10 |
March | 0.698952E+09 | 0.133710E+09 | 0.565243E+09 | 0.359574E+09 | 0.119905E+10 |
April | 0.159600E+10 | 0.633946E+09 | 0.962056E+09 | 0.154775E+10 | 0.969719E+09 |
May | 0.193490E+10 | 0.786795E+09 | 0.114810E+10 | 0.191620E+10 | 0.794964E+09 |
June | 0.202208E+10 | 0.832412E+09 | 0.118966E+10 | 0.216069E+10 | 0.625556E+09 |
July | 0.212804E+10 | 0.938260E+09 | 0.118978E+10 | 0.236403E+10 | 0.616180E+09 |
August | 0.178741E+10 | 0.773900E+09 | 0.101351E+10 | 0.199580E+10 | 0.680956E+09 |
September | 0.138772E+10 | 0.622286E+09 | 0.765437E+09 | 0.150230E+10 | 0.784444E+09 |
October | 0.764973E+09 | 0.275081E+09 | 0.489892E+09 | 0.621007E+09 | 0.112071E+10 |
November | 0.400623E+09 | 0.116947E+09 | 0.283676E+09 | 0.211756E+09 | 0.136745E+10 |
December | 0.234323E+09 | 49447320.23 | 0.184876E+09 | 66711727.25 | 0.174285E+10 |
Annual Sum or Average | 0.140898E+11 | 0.560183E+10 | 0.848797E+10 | 0.134916E+11 | 0.126072E+11 |
Minimum of Months | 0.234323E+09 | 49447320.23 | 0.184876E+09 | 66711727.25 | 0.616180E+09 |
Maximum of Months | 0.212804E+10 | 0.938260E+09 | 0.118978E+10 | 0.236403E+10 | 0.174285E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.988429E+09 | 0.00 | 0.988429E+09 | 65422253.00 | 0.590023E+10 |
February | 0.139410E+10 | 0.00 | 0.139410E+10 | 0.202328E+09 | 0.497131E+10 |
March | 0.213590E+10 | 0.00 | 0.213590E+10 | 0.688376E+09 | 0.460586E+10 |
April | 0.336538E+10 | 15062057.15 | 0.335032E+10 | 0.210710E+10 | 0.362891E+10 |
May | 0.434784E+10 | 0.209762E+09 | 0.413808E+10 | 0.279285E+10 | 0.298010E+10 |
June | 0.465123E+10 | 0.291662E+09 | 0.435956E+10 | 0.383064E+10 | 0.228918E+10 |
July | 0.455900E+10 | 0.259933E+09 | 0.429907E+10 | 0.401732E+10 | 0.218128E+10 |
August | 0.358361E+10 | 56146320.57 | 0.352747E+10 | 0.308713E+10 | 0.244284E+10 |
September | 0.263963E+10 | 584097.80 | 0.263905E+10 | 0.196102E+10 | 0.313881E+10 |
October | 0.174784E+10 | 0.00 | 0.174784E+10 | 0.717576E+09 | 0.429335E+10 |
November | 0.101632E+10 | 0.00 | 0.101632E+10 | 0.107548E+09 | 0.504694E+10 |
December | 0.715179E+09 | 0.00 | 0.715179E+09 | 5019202.77 | 0.626913E+10 |
Annual Sum or Average | 0.311445E+11 | 0.833150E+09 | 0.303113E+11 | 0.195823E+11 | 0.477479E+11 |
Minimum of Months | 0.715179E+09 | 0.00 | 0.715179E+09 | 5019202.77 | 0.218128E+10 |
Maximum of Months | 0.465123E+10 | 0.291662E+09 | 0.435956E+10 | 0.401732E+10 | 0.626913E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134687E+10 | 0.541039E+09 | 0.805829E+09 | 0.779638E+09 | 0.368710E+10 |
February | 0.181405E+10 | 0.670124E+09 | 0.114393E+10 | 0.116898E+10 | 0.313618E+10 |
March | 0.209884E+10 | 0.413604E+09 | 0.168523E+10 | 0.128069E+10 | 0.287952E+10 |
April | 0.545376E+10 | 0.256276E+10 | 0.289100E+10 | 0.559469E+10 | 0.230463E+10 |
May | 0.592560E+10 | 0.258405E+10 | 0.334155E+10 | 0.593947E+10 | 0.201773E+10 |
June | 0.567606E+10 | 0.226696E+10 | 0.340910E+10 | 0.606515E+10 | 0.153451E+10 |
July | 0.598727E+10 | 0.254459E+10 | 0.344268E+10 | 0.666330E+10 | 0.147484E+10 |
August | 0.567163E+10 | 0.270985E+10 | 0.296178E+10 | 0.649935E+10 | 0.160645E+10 |
September | 0.494274E+10 | 0.262832E+10 | 0.231442E+10 | 0.547778E+10 | 0.198177E+10 |
October | 0.246546E+10 | 0.102175E+10 | 0.144371E+10 | 0.216044E+10 | 0.272501E+10 |
November | 0.124385E+10 | 0.423923E+09 | 0.819931E+09 | 0.717268E+09 | 0.317539E+10 |
December | 0.952576E+09 | 0.354154E+09 | 0.598421E+09 | 0.481984E+09 | 0.397183E+10 |
Annual Sum or Average | 0.435787E+11 | 0.187211E+11 | 0.248576E+11 | 0.428287E+11 | 0.304950E+11 |
Minimum of Months | 0.952576E+09 | 0.354154E+09 | 0.598421E+09 | 0.481984E+09 | 0.147484E+10 |
Maximum of Months | 0.598727E+10 | 0.270985E+10 | 0.344268E+10 | 0.666330E+10 | 0.397183E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.561163E+10 | 0.363264E+10 | 0.197899E+10 | 0.543727E+10 | 0.543857E+10 |
February | 0.619033E+10 | 0.377742E+10 | 0.241290E+10 | 0.615454E+10 | 0.482044E+10 |
March | 0.423733E+10 | 0.123372E+10 | 0.300361E+10 | 0.337314E+10 | 0.445336E+10 |
April | 0.851532E+10 | 0.384883E+10 | 0.466650E+10 | 0.949304E+10 | 0.381631E+10 |
May | 0.727773E+10 | 0.236939E+10 | 0.490834E+10 | 0.754702E+10 | 0.334203E+10 |
June | 0.648807E+10 | 0.157049E+10 | 0.491758E+10 | 0.701874E+10 | 0.249539E+10 |
July | 0.726403E+10 | 0.227481E+10 | 0.498922E+10 | 0.844295E+10 | 0.241139E+10 |
August | 0.851185E+10 | 0.382894E+10 | 0.468290E+10 | 0.104385E+11 | 0.265388E+10 |
September | 0.973430E+10 | 0.570252E+10 | 0.403179E+10 | 0.118014E+11 | 0.327518E+10 |
October | 0.691080E+10 | 0.403905E+10 | 0.287175E+10 | 0.747220E+10 | 0.429167E+10 |
November | 0.474170E+10 | 0.288449E+10 | 0.185720E+10 | 0.462891E+10 | 0.486276E+10 |
December | 0.388350E+10 | 0.248818E+10 | 0.139532E+10 | 0.366829E+10 | 0.599674E+10 |
Annual Sum or Average | 0.793666E+11 | 0.376505E+11 | 0.417161E+11 | 0.854760E+11 | 0.478577E+11 |
Minimum of Months | 0.388350E+10 | 0.123372E+10 | 0.139532E+10 | 0.337314E+10 | 0.241139E+10 |
Maximum of Months | 0.973430E+10 | 0.570252E+10 | 0.498922E+10 | 0.118014E+11 | 0.599674E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130976E+10 | 0.432751E+09 | 0.877012E+09 | 0.772811E+09 | 0.382932E+10 |
February | 0.209458E+10 | 0.884399E+09 | 0.121018E+10 | 0.162782E+10 | 0.331253E+10 |
March | 0.209687E+10 | 0.401132E+09 | 0.169574E+10 | 0.126076E+10 | 0.299691E+10 |
April | 0.478804E+10 | 0.190185E+10 | 0.288619E+10 | 0.482863E+10 | 0.251119E+10 |
May | 0.580473E+10 | 0.236040E+10 | 0.344433E+10 | 0.584059E+10 | 0.220488E+10 |
June | 0.606628E+10 | 0.249726E+10 | 0.356902E+10 | 0.657468E+10 | 0.170097E+10 |
July | 0.638418E+10 | 0.281480E+10 | 0.356938E+10 | 0.721642E+10 | 0.165216E+10 |
August | 0.536228E+10 | 0.232172E+10 | 0.304057E+10 | 0.612501E+10 | 0.179790E+10 |
September | 0.416320E+10 | 0.186687E+10 | 0.229633E+10 | 0.459209E+10 | 0.215756E+10 |
October | 0.229494E+10 | 0.825250E+09 | 0.146969E+10 | 0.199017E+10 | 0.287707E+10 |
November | 0.120188E+10 | 0.350843E+09 | 0.851035E+09 | 0.723751E+09 | 0.335269E+10 |
December | 0.702975E+09 | 0.148343E+09 | 0.554632E+09 | 0.251049E+09 | 0.422266E+10 |
Annual Sum or Average | 0.422697E+11 | 0.168056E+11 | 0.254641E+11 | 0.418038E+11 | 0.326158E+11 |
Minimum of Months | 0.702975E+09 | 0.148343E+09 | 0.554632E+09 | 0.251049E+09 | 0.165216E+10 |
Maximum of Months | 0.638418E+10 | 0.281480E+10 | 0.356938E+10 | 0.721642E+10 | 0.422266E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.988429E+09 | 0.00 | 0.988429E+09 | 0.108126E+09 | 0.532824E+10 |
February | 0.139410E+10 | 0.00 | 0.139410E+10 | 0.291103E+09 | 0.449149E+10 |
March | 0.213590E+10 | 0.00 | 0.213590E+10 | 0.810909E+09 | 0.418364E+10 |
April | 0.336538E+10 | 15062057.15 | 0.335032E+10 | 0.221563E+10 | 0.337403E+10 |
May | 0.434784E+10 | 0.209762E+09 | 0.413808E+10 | 0.292842E+10 | 0.278473E+10 |
June | 0.465123E+10 | 0.291662E+09 | 0.435956E+10 | 0.388247E+10 | 0.219187E+10 |
July | 0.455900E+10 | 0.259933E+09 | 0.429907E+10 | 0.406089E+10 | 0.209690E+10 |
August | 0.358361E+10 | 56146320.57 | 0.352747E+10 | 0.312395E+10 | 0.234575E+10 |
September | 0.263963E+10 | 584097.80 | 0.263905E+10 | 0.204296E+10 | 0.293816E+10 |
October | 0.174784E+10 | 0.00 | 0.174784E+10 | 0.839973E+09 | 0.383462E+10 |
November | 0.101632E+10 | 0.00 | 0.101632E+10 | 0.161735E+09 | 0.450589E+10 |
December | 0.715179E+09 | 0.00 | 0.715179E+09 | 24609848.44 | 0.569774E+10 |
Annual Sum or Average | 0.311445E+11 | 0.833150E+09 | 0.303113E+11 | 0.204908E+11 | 0.437731E+11 |
Minimum of Months | 0.715179E+09 | 0.00 | 0.715179E+09 | 24609848.44 | 0.209690E+10 |
Maximum of Months | 0.465123E+10 | 0.291662E+09 | 0.435956E+10 | 0.406089E+10 | 0.569774E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134687E+10 | 0.541039E+09 | 0.805829E+09 | 0.831684E+09 | 0.335579E+10 |
February | 0.181405E+10 | 0.670124E+09 | 0.114393E+10 | 0.124340E+10 | 0.286321E+10 |
March | 0.209884E+10 | 0.413604E+09 | 0.168523E+10 | 0.135708E+10 | 0.265514E+10 |
April | 0.545376E+10 | 0.256276E+10 | 0.289100E+10 | 0.564600E+10 | 0.218421E+10 |
May | 0.592560E+10 | 0.258405E+10 | 0.334155E+10 | 0.599027E+10 | 0.191888E+10 |
June | 0.567606E+10 | 0.226696E+10 | 0.340910E+10 | 0.607762E+10 | 0.148711E+10 |
July | 0.598727E+10 | 0.254459E+10 | 0.344268E+10 | 0.666714E+10 | 0.143583E+10 |
August | 0.567163E+10 | 0.270985E+10 | 0.296178E+10 | 0.650132E+10 | 0.156727E+10 |
September | 0.494274E+10 | 0.262832E+10 | 0.231442E+10 | 0.550810E+10 | 0.189533E+10 |
October | 0.246546E+10 | 0.102175E+10 | 0.144371E+10 | 0.223539E+10 | 0.248399E+10 |
November | 0.124385E+10 | 0.423923E+09 | 0.819931E+09 | 0.767541E+09 | 0.287784E+10 |
December | 0.952576E+09 | 0.354154E+09 | 0.598421E+09 | 0.520087E+09 | 0.363331E+10 |
Annual Sum or Average | 0.435787E+11 | 0.187211E+11 | 0.248576E+11 | 0.433456E+11 | 0.283579E+11 |
Minimum of Months | 0.952576E+09 | 0.354154E+09 | 0.598421E+09 | 0.520087E+09 | 0.143583E+10 |
Maximum of Months | 0.598727E+10 | 0.270985E+10 | 0.344268E+10 | 0.666714E+10 | 0.363331E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.561163E+10 | 0.363264E+10 | 0.197899E+10 | 0.557143E+10 | 0.494161E+10 |
February | 0.619033E+10 | 0.377742E+10 | 0.241290E+10 | 0.628515E+10 | 0.440626E+10 |
March | 0.423733E+10 | 0.123372E+10 | 0.300361E+10 | 0.350136E+10 | 0.409379E+10 |
April | 0.851532E+10 | 0.384883E+10 | 0.466650E+10 | 0.956468E+10 | 0.360885E+10 |
May | 0.727773E+10 | 0.236939E+10 | 0.490834E+10 | 0.762092E+10 | 0.315726E+10 |
June | 0.648807E+10 | 0.157049E+10 | 0.491758E+10 | 0.705237E+10 | 0.239985E+10 |
July | 0.726403E+10 | 0.227481E+10 | 0.498922E+10 | 0.846514E+10 | 0.232791E+10 |
August | 0.851185E+10 | 0.382894E+10 | 0.468290E+10 | 0.104494E+11 | 0.257230E+10 |
September | 0.973430E+10 | 0.570252E+10 | 0.403179E+10 | 0.118408E+11 | 0.312498E+10 |
October | 0.691080E+10 | 0.403905E+10 | 0.287175E+10 | 0.757516E+10 | 0.392016E+10 |
November | 0.474170E+10 | 0.288449E+10 | 0.185720E+10 | 0.473043E+10 | 0.440439E+10 |
December | 0.388350E+10 | 0.248818E+10 | 0.139532E+10 | 0.375938E+10 | 0.547442E+10 |
Annual Sum or Average | 0.793666E+11 | 0.376505E+11 | 0.417161E+11 | 0.864162E+11 | 0.444318E+11 |
Minimum of Months | 0.388350E+10 | 0.123372E+10 | 0.139532E+10 | 0.350136E+10 | 0.232791E+10 |
Maximum of Months | 0.973430E+10 | 0.570252E+10 | 0.498922E+10 | 0.118408E+11 | 0.547442E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130976E+10 | 0.432751E+09 | 0.877012E+09 | 0.811238E+09 | 0.352492E+10 |
February | 0.209458E+10 | 0.884399E+09 | 0.121018E+10 | 0.167687E+10 | 0.306882E+10 |
March | 0.209687E+10 | 0.401132E+09 | 0.169574E+10 | 0.131720E+10 | 0.279207E+10 |
April | 0.478804E+10 | 0.190185E+10 | 0.288619E+10 | 0.487450E+10 | 0.238432E+10 |
May | 0.580473E+10 | 0.236040E+10 | 0.344433E+10 | 0.588270E+10 | 0.209749E+10 |
June | 0.606628E+10 | 0.249726E+10 | 0.356902E+10 | 0.658895E+10 | 0.164273E+10 |
July | 0.638418E+10 | 0.281480E+10 | 0.356938E+10 | 0.722431E+10 | 0.160016E+10 |
August | 0.536228E+10 | 0.232172E+10 | 0.304057E+10 | 0.613497E+10 | 0.174258E+10 |
September | 0.416320E+10 | 0.186687E+10 | 0.229633E+10 | 0.462340E+10 | 0.205797E+10 |
October | 0.229494E+10 | 0.825250E+09 | 0.146969E+10 | 0.204456E+10 | 0.265743E+10 |
November | 0.120188E+10 | 0.350843E+09 | 0.851035E+09 | 0.754323E+09 | 0.308598E+10 |
December | 0.702975E+09 | 0.148343E+09 | 0.554632E+09 | 0.270266E+09 | 0.391059E+10 |
Annual Sum or Average | 0.422697E+11 | 0.168056E+11 | 0.254641E+11 | 0.422033E+11 | 0.305651E+11 |
Minimum of Months | 0.702975E+09 | 0.148343E+09 | 0.554632E+09 | 0.270266E+09 | 0.160016E+10 |
Maximum of Months | 0.638418E+10 | 0.281480E+10 | 0.356938E+10 | 0.722431E+10 | 0.391059E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.62 | 2476.68 | 369.03 | 0.00 | 369.03 | 0.00 | 0.00 |
February | 48.81 | 2314.82 | 576.26 | 0.00 | 576.26 | 0.00 | 0.00 |
March | 203.61 | 1941.49 | 797.43 | 0.00 | 797.43 | 0.00 | 0.00 |
April | 766.01 | 1529.05 | 1298.35 | 5.81 | 1292.54 | 0.00 | 0.00 |
May | 1001.46 | 1186.27 | 1623.27 | 78.31 | 1544.95 | 0.00 | 0.00 |
June | 1455.46 | 932.47 | 1794.42 | 112.52 | 1681.90 | 0.00 | 0.00 |
July | 1466.07 | 864.43 | 1702.11 | 97.04 | 1605.06 | 0.00 | 0.00 |
August | 1121.31 | 972.78 | 1337.94 | 20.96 | 1316.98 | 0.00 | 0.00 |
September | 725.75 | 1294.21 | 1018.36 | 0.23 | 1018.13 | 0.00 | 0.00 |
October | 225.00 | 1799.04 | 652.56 | 0.00 | 652.56 | 0.00 | 0.00 |
November | 21.26 | 2260.20 | 392.09 | 0.00 | 392.09 | 0.00 | 0.00 |
December | 0.03 | 2734.76 | 267.01 | 0.00 | 267.01 | 0.00 | 0.00 |
Annual Sum or Average | 590.01 | 1689.13 | 987.57 | 26.42 | 961.15 | 0.00 | 0.00 |
Minimum of Months | 0.03 | 864.43 | 267.01 | 0.00 | 267.01 | 0.00 | 0.00 |
Maximum of Months | 1466.07 | 2734.76 | 1794.42 | 112.52 | 1681.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 272.78 | 1502.73 | 502.86 | 202.00 | 300.86 | 0.00 | 0.00 |
February | 458.61 | 1404.25 | 749.86 | 277.00 | 472.86 | 0.00 | 0.00 |
March | 445.63 | 1165.90 | 783.62 | 154.42 | 629.20 | 0.00 | 0.00 |
April | 2153.28 | 928.17 | 2104.08 | 988.72 | 1115.36 | 0.00 | 0.00 |
May | 2213.12 | 791.01 | 2212.38 | 964.78 | 1247.60 | 0.00 | 0.00 |
June | 2341.15 | 614.53 | 2189.85 | 874.60 | 1315.24 | 0.00 | 0.00 |
July | 2494.56 | 564.55 | 2235.40 | 950.04 | 1285.36 | 0.00 | 0.00 |
August | 2431.72 | 608.11 | 2117.55 | 1011.75 | 1105.81 | 0.00 | 0.00 |
September | 2111.69 | 798.17 | 1906.93 | 1014.02 | 892.91 | 0.00 | 0.00 |
October | 785.25 | 1104.92 | 920.50 | 381.48 | 539.02 | 0.00 | 0.00 |
November | 258.45 | 1356.95 | 479.88 | 163.55 | 316.33 | 0.00 | 0.00 |
December | 164.60 | 1642.47 | 355.65 | 132.23 | 223.43 | 0.00 | 0.00 |
Annual Sum or Average | 1347.44 | 1038.42 | 1381.88 | 593.65 | 788.23 | 0.00 | 0.00 |
Minimum of Months | 164.60 | 564.55 | 355.65 | 132.23 | 223.43 | 0.00 | 0.00 |
Maximum of Months | 2494.56 | 1642.47 | 2235.40 | 1014.02 | 1315.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2019.21 | 2104.64 | 2095.08 | 1356.23 | 738.85 | 0.00 | 0.00 |
February | 2536.45 | 2061.70 | 2558.75 | 1561.38 | 997.37 | 0.00 | 0.00 |
March | 1232.43 | 1758.37 | 1581.99 | 460.60 | 1121.39 | 0.00 | 0.00 |
April | 3661.38 | 1523.44 | 3285.14 | 1484.84 | 1800.30 | 0.00 | 0.00 |
May | 2816.52 | 1287.29 | 2717.12 | 884.60 | 1832.52 | 0.00 | 0.00 |
June | 2700.54 | 998.85 | 2503.05 | 605.88 | 1897.17 | 0.00 | 0.00 |
July | 3146.48 | 930.38 | 2712.01 | 849.29 | 1862.72 | 0.00 | 0.00 |
August | 3896.92 | 1014.43 | 3177.87 | 1429.52 | 1748.36 | 0.00 | 0.00 |
September | 4568.50 | 1286.67 | 3755.41 | 2199.97 | 1555.44 | 0.00 | 0.00 |
October | 2785.88 | 1669.92 | 2580.12 | 1507.96 | 1072.16 | 0.00 | 0.00 |
November | 1771.40 | 1992.68 | 1829.30 | 1112.81 | 716.49 | 0.00 | 0.00 |
December | 1347.95 | 2391.82 | 1449.89 | 928.95 | 520.94 | 0.00 | 0.00 |
Annual Sum or Average | 2703.24 | 1582.57 | 2516.63 | 1193.85 | 1322.78 | 0.00 | 0.00 |
Minimum of Months | 1232.43 | 930.38 | 1449.89 | 460.60 | 520.94 | 0.00 | 0.00 |
Maximum of Months | 4568.50 | 2391.82 | 3755.41 | 2199.97 | 1897.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 265.17 | 1607.81 | 489.01 | 161.57 | 327.44 | 0.00 | 0.00 |
February | 631.27 | 1574.79 | 865.82 | 365.58 | 500.24 | 0.00 | 0.00 |
March | 402.75 | 1343.03 | 782.89 | 149.77 | 633.12 | 0.00 | 0.00 |
April | 1791.40 | 1122.37 | 1847.25 | 733.74 | 1113.50 | 0.00 | 0.00 |
May | 2146.31 | 890.43 | 2167.25 | 881.28 | 1285.97 | 0.00 | 0.00 |
June | 2500.83 | 724.03 | 2340.39 | 963.45 | 1376.94 | 0.00 | 0.00 |
July | 2647.92 | 690.17 | 2383.59 | 1050.93 | 1332.66 | 0.00 | 0.00 |
August | 2235.46 | 762.73 | 2002.06 | 866.83 | 1135.22 | 0.00 | 0.00 |
September | 1738.79 | 907.93 | 1606.18 | 720.25 | 885.93 | 0.00 | 0.00 |
October | 695.58 | 1255.29 | 856.84 | 308.11 | 548.72 | 0.00 | 0.00 |
November | 245.09 | 1582.71 | 463.69 | 135.36 | 328.33 | 0.00 | 0.00 |
December | 74.72 | 1952.14 | 262.46 | 55.39 | 207.08 | 0.00 | 0.00 |
Annual Sum or Average | 1283.46 | 1199.33 | 1340.37 | 532.91 | 807.46 | 0.00 | 0.00 |
Minimum of Months | 74.72 | 690.17 | 262.46 | 55.39 | 207.08 | 0.00 | 0.00 |
Maximum of Months | 2647.92 | 1952.14 | 2383.59 | 1050.93 | 1376.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 24.43 | 2202.89 | 369.04 | 0.00 | 369.04 | 0.00 | 0.00 |
February | 83.63 | 2054.94 | 576.27 | 0.00 | 576.27 | 0.00 | 0.00 |
March | 257.01 | 1719.63 | 797.45 | 0.00 | 797.45 | 0.00 | 0.00 |
April | 812.93 | 1400.04 | 1298.37 | 5.81 | 1292.56 | 0.00 | 0.00 |
May | 1042.73 | 1112.64 | 1623.30 | 78.32 | 1544.98 | 0.00 | 0.00 |
June | 1477.87 | 883.17 | 1794.45 | 112.52 | 1681.93 | 0.00 | 0.00 |
July | 1499.90 | 814.40 | 1702.14 | 97.05 | 1605.09 | 0.00 | 0.00 |
August | 1152.60 | 912.05 | 1337.97 | 20.96 | 1317.00 | 0.00 | 0.00 |
September | 756.57 | 1210.96 | 1018.38 | 0.23 | 1018.15 | 0.00 | 0.00 |
October | 267.91 | 1602.95 | 652.57 | 0.00 | 652.57 | 0.00 | 0.00 |
November | 41.49 | 1947.12 | 392.10 | 0.00 | 392.10 | 0.00 | 0.00 |
December | 1.87 | 2340.62 | 267.02 | 0.00 | 267.02 | 0.00 | 0.00 |
Annual Sum or Average | 620.95 | 1514.08 | 987.58 | 26.42 | 961.17 | 0.00 | 0.00 |
Minimum of Months | 1.87 | 814.40 | 267.02 | 0.00 | 267.02 | 0.00 | 0.00 |
Maximum of Months | 1499.90 | 2340.62 | 1794.45 | 112.52 | 1681.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 291.08 | 1376.60 | 502.86 | 202.00 | 300.86 | 0.00 | 0.00 |
February | 483.21 | 1296.37 | 749.86 | 277.00 | 472.85 | 0.00 | 0.00 |
March | 478.15 | 1075.09 | 783.62 | 154.42 | 629.19 | 0.00 | 0.00 |
April | 2158.45 | 889.13 | 2104.07 | 988.72 | 1115.35 | 0.00 | 0.00 |
May | 2217.54 | 753.33 | 2212.37 | 964.77 | 1247.59 | 0.00 | 0.00 |
June | 2339.95 | 592.02 | 2189.84 | 874.60 | 1315.24 | 0.00 | 0.00 |
July | 2487.79 | 550.64 | 2235.39 | 950.04 | 1285.35 | 0.00 | 0.00 |
August | 2426.58 | 599.78 | 2117.55 | 1011.74 | 1105.80 | 0.00 | 0.00 |
September | 2113.34 | 764.57 | 1906.92 | 1014.01 | 892.91 | 0.00 | 0.00 |
October | 806.62 | 1017.40 | 920.50 | 381.48 | 539.02 | 0.00 | 0.00 |
November | 276.72 | 1225.07 | 479.88 | 163.55 | 316.33 | 0.00 | 0.00 |
December | 179.95 | 1482.91 | 355.65 | 132.23 | 223.42 | 0.00 | 0.00 |
Annual Sum or Average | 1358.09 | 966.99 | 1381.87 | 593.64 | 788.23 | 0.00 | 0.00 |
Minimum of Months | 179.95 | 550.64 | 355.65 | 132.23 | 223.42 | 0.00 | 0.00 |
Maximum of Months | 2487.79 | 1482.91 | 2235.39 | 1014.01 | 1315.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2030.04 | 2030.53 | 2095.14 | 1356.27 | 738.87 | 0.00 | 0.00 |
February | 2544.04 | 1992.58 | 2558.83 | 1561.43 | 997.40 | 0.00 | 0.00 |
March | 1259.39 | 1662.69 | 1582.04 | 460.62 | 1121.42 | 0.00 | 0.00 |
April | 3662.44 | 1472.34 | 3285.23 | 1484.89 | 1800.35 | 0.00 | 0.00 |
May | 2817.73 | 1247.77 | 2717.19 | 884.63 | 1832.56 | 0.00 | 0.00 |
June | 2707.85 | 962.73 | 2503.11 | 605.90 | 1897.21 | 0.00 | 0.00 |
July | 3152.24 | 900.31 | 2712.08 | 849.32 | 1862.76 | 0.00 | 0.00 |
August | 3897.28 | 990.85 | 3177.96 | 1429.56 | 1748.39 | 0.00 | 0.00 |
September | 4553.01 | 1263.57 | 3755.52 | 2200.05 | 1555.47 | 0.00 | 0.00 |
October | 2789.80 | 1602.33 | 2580.20 | 1508.01 | 1072.19 | 0.00 | 0.00 |
November | 1785.84 | 1876.07 | 1829.36 | 1112.85 | 716.51 | 0.00 | 0.00 |
December | 1369.58 | 2238.92 | 1449.93 | 928.98 | 520.95 | 0.00 | 0.00 |
Annual Sum or Average | 2710.43 | 1517.56 | 2516.70 | 1193.89 | 1322.81 | 0.00 | 0.00 |
Minimum of Months | 1259.39 | 900.31 | 1449.93 | 460.62 | 520.95 | 0.00 | 0.00 |
Maximum of Months | 4553.01 | 2238.92 | 3755.52 | 2200.05 | 1897.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 288.53 | 1429.71 | 489.01 | 161.57 | 327.44 | 0.00 | 0.00 |
February | 672.87 | 1369.27 | 865.82 | 365.58 | 500.24 | 0.00 | 0.00 |
March | 470.71 | 1118.92 | 782.88 | 149.77 | 633.12 | 0.00 | 0.00 |
April | 1862.90 | 968.82 | 1847.24 | 733.74 | 1113.50 | 0.00 | 0.00 |
May | 2180.63 | 823.21 | 2167.24 | 881.27 | 1285.96 | 0.00 | 0.00 |
June | 2536.53 | 656.24 | 2340.38 | 963.45 | 1376.94 | 0.00 | 0.00 |
July | 2694.30 | 616.84 | 2383.58 | 1050.93 | 1332.65 | 0.00 | 0.00 |
August | 2286.82 | 671.26 | 2002.05 | 866.83 | 1135.22 | 0.00 | 0.00 |
September | 1771.64 | 832.39 | 1606.17 | 720.24 | 885.93 | 0.00 | 0.00 |
October | 743.05 | 1074.18 | 856.83 | 308.11 | 548.72 | 0.00 | 0.00 |
November | 279.23 | 1293.47 | 463.69 | 135.36 | 328.33 | 0.00 | 0.00 |
December | 93.73 | 1576.56 | 262.46 | 55.38 | 207.08 | 0.00 | 0.00 |
Annual Sum or Average | 1325.59 | 1034.24 | 1340.36 | 532.90 | 807.46 | 0.00 | 0.00 |
Minimum of Months | 93.73 | 616.84 | 262.46 | 55.38 | 207.08 | 0.00 | 0.00 |
Maximum of Months | 2694.30 | 1576.56 | 2383.58 | 1050.93 | 1376.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 40.37 | 1989.34 | 369.04 | 0.00 | 369.04 | 0.00 | 0.00 |
February | 120.33 | 1856.60 | 576.27 | 0.00 | 576.27 | 0.00 | 0.00 |
March | 302.76 | 1561.99 | 797.45 | 0.00 | 797.45 | 0.00 | 0.00 |
April | 854.79 | 1301.71 | 1298.37 | 5.81 | 1292.56 | 0.00 | 0.00 |
May | 1093.35 | 1039.70 | 1623.30 | 78.32 | 1544.98 | 0.00 | 0.00 |
June | 1497.87 | 845.63 | 1794.45 | 112.52 | 1681.93 | 0.00 | 0.00 |
July | 1516.16 | 782.89 | 1702.14 | 97.05 | 1605.09 | 0.00 | 0.00 |
August | 1166.35 | 875.80 | 1337.97 | 20.96 | 1317.00 | 0.00 | 0.00 |
September | 788.18 | 1133.55 | 1018.38 | 0.23 | 1018.15 | 0.00 | 0.00 |
October | 313.61 | 1431.68 | 652.57 | 0.00 | 652.57 | 0.00 | 0.00 |
November | 62.40 | 1738.38 | 392.10 | 0.00 | 392.10 | 0.00 | 0.00 |
December | 9.19 | 2127.29 | 267.02 | 0.00 | 267.02 | 0.00 | 0.00 |
Annual Sum or Average | 649.76 | 1388.03 | 987.58 | 26.42 | 961.17 | 0.00 | 0.00 |
Minimum of Months | 9.19 | 782.89 | 267.02 | 0.00 | 267.02 | 0.00 | 0.00 |
Maximum of Months | 1516.16 | 2127.29 | 1794.45 | 112.52 | 1681.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 310.52 | 1252.91 | 502.86 | 202.00 | 300.86 | 0.00 | 0.00 |
February | 513.97 | 1183.54 | 749.86 | 277.00 | 472.85 | 0.00 | 0.00 |
March | 506.68 | 991.32 | 783.62 | 154.42 | 629.19 | 0.00 | 0.00 |
April | 2178.24 | 842.67 | 2104.07 | 988.72 | 1115.35 | 0.00 | 0.00 |
May | 2236.51 | 716.43 | 2212.37 | 964.77 | 1247.59 | 0.00 | 0.00 |
June | 2344.76 | 573.73 | 2189.84 | 874.60 | 1315.24 | 0.00 | 0.00 |
July | 2489.22 | 536.08 | 2235.39 | 950.04 | 1285.35 | 0.00 | 0.00 |
August | 2427.31 | 585.15 | 2117.55 | 1011.74 | 1105.80 | 0.00 | 0.00 |
September | 2125.04 | 731.22 | 1906.92 | 1014.01 | 892.91 | 0.00 | 0.00 |
October | 834.60 | 927.42 | 920.50 | 381.48 | 539.02 | 0.00 | 0.00 |
November | 296.12 | 1110.28 | 479.88 | 163.55 | 316.33 | 0.00 | 0.00 |
December | 194.18 | 1356.52 | 355.65 | 132.23 | 223.42 | 0.00 | 0.00 |
Annual Sum or Average | 1374.48 | 899.22 | 1381.87 | 593.64 | 788.23 | 0.00 | 0.00 |
Minimum of Months | 194.18 | 536.08 | 355.65 | 132.23 | 223.42 | 0.00 | 0.00 |
Maximum of Months | 2489.22 | 1356.52 | 2235.39 | 1014.01 | 1315.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2080.13 | 1844.99 | 2095.14 | 1356.27 | 738.87 | 0.00 | 0.00 |
February | 2598.03 | 1821.37 | 2558.83 | 1561.43 | 997.40 | 0.00 | 0.00 |
March | 1307.26 | 1528.45 | 1582.04 | 460.62 | 1121.42 | 0.00 | 0.00 |
April | 3690.08 | 1392.30 | 3285.23 | 1484.89 | 1800.35 | 0.00 | 0.00 |
May | 2845.33 | 1178.78 | 2717.19 | 884.63 | 1832.56 | 0.00 | 0.00 |
June | 2720.82 | 925.87 | 2503.11 | 605.90 | 1897.21 | 0.00 | 0.00 |
July | 3160.52 | 869.14 | 2712.08 | 849.32 | 1862.76 | 0.00 | 0.00 |
August | 3901.36 | 960.39 | 3177.96 | 1429.56 | 1748.39 | 0.00 | 0.00 |
September | 4568.20 | 1205.62 | 3755.52 | 2200.05 | 1555.47 | 0.00 | 0.00 |
October | 2828.24 | 1463.62 | 2580.20 | 1508.01 | 1072.19 | 0.00 | 0.00 |
November | 1825.01 | 1699.22 | 1829.36 | 1112.85 | 716.51 | 0.00 | 0.00 |
December | 1403.59 | 2043.92 | 1449.93 | 928.98 | 520.95 | 0.00 | 0.00 |
Annual Sum or Average | 2740.24 | 1408.92 | 2516.70 | 1193.89 | 1322.81 | 0.00 | 0.00 |
Minimum of Months | 1307.26 | 869.14 | 1449.93 | 460.62 | 520.95 | 0.00 | 0.00 |
Maximum of Months | 4568.20 | 2043.92 | 3755.52 | 2200.05 | 1897.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.88 | 1316.05 | 489.01 | 161.57 | 327.44 | 0.00 | 0.00 |
February | 693.15 | 1268.53 | 865.82 | 365.58 | 500.24 | 0.00 | 0.00 |
March | 491.79 | 1042.44 | 782.88 | 149.77 | 633.12 | 0.00 | 0.00 |
April | 1880.59 | 919.88 | 1847.24 | 733.74 | 1113.50 | 0.00 | 0.00 |
May | 2196.35 | 783.11 | 2167.24 | 881.27 | 1285.96 | 0.00 | 0.00 |
June | 2542.03 | 633.77 | 2340.38 | 963.45 | 1376.94 | 0.00 | 0.00 |
July | 2697.25 | 597.43 | 2383.58 | 1050.93 | 1332.65 | 0.00 | 0.00 |
August | 2290.53 | 650.61 | 2002.05 | 866.83 | 1135.22 | 0.00 | 0.00 |
September | 1783.72 | 793.97 | 1606.17 | 720.24 | 885.93 | 0.00 | 0.00 |
October | 763.35 | 992.17 | 856.83 | 308.11 | 548.72 | 0.00 | 0.00 |
November | 291.02 | 1190.58 | 463.69 | 135.36 | 328.33 | 0.00 | 0.00 |
December | 100.91 | 1460.05 | 262.46 | 55.38 | 207.08 | 0.00 | 0.00 |
Annual Sum or Average | 1338.26 | 969.21 | 1340.36 | 532.90 | 807.46 | 0.00 | 0.00 |
Minimum of Months | 100.91 | 597.43 | 262.46 | 55.38 | 207.08 | 0.00 | 0.00 |
Maximum of Months | 2697.25 | 1460.05 | 2383.58 | 1050.93 | 1376.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 33808848.47 | 0.663354E+10 | 0.988409E+09 | 0.00 | 0.988409E+09 | 0.00 | 0.00 |
February | 0.118090E+09 | 0.560002E+10 | 0.139408E+10 | 0.00 | 0.139408E+10 | 0.00 | 0.00 |
March | 0.545355E+09 | 0.520009E+10 | 0.213585E+10 | 0.00 | 0.213585E+10 | 0.00 | 0.00 |
April | 0.198549E+10 | 0.396329E+10 | 0.336532E+10 | 15061607.97 | 0.335026E+10 | 0.00 | 0.00 |
May | 0.268231E+10 | 0.317732E+10 | 0.434776E+10 | 0.209756E+09 | 0.413801E+10 | 0.00 | 0.00 |
June | 0.377254E+10 | 0.241696E+10 | 0.465114E+10 | 0.291653E+09 | 0.435948E+10 | 0.00 | 0.00 |
July | 0.392673E+10 | 0.231528E+10 | 0.455892E+10 | 0.259925E+09 | 0.429900E+10 | 0.00 | 0.00 |
August | 0.300333E+10 | 0.260550E+10 | 0.358355E+10 | 56144646.18 | 0.352741E+10 | 0.00 | 0.00 |
September | 0.188115E+10 | 0.335459E+10 | 0.263959E+10 | 584080.38 | 0.263900E+10 | 0.00 | 0.00 |
October | 0.602645E+09 | 0.481855E+10 | 0.174781E+10 | 0.00 | 0.174781E+10 | 0.00 | 0.00 |
November | 55115752.60 | 0.585845E+10 | 0.101629E+10 | 0.00 | 0.101629E+10 | 0.00 | 0.00 |
December | 73678.77 | 0.732479E+10 | 0.715163E+09 | 0.00 | 0.715163E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186066E+11 | 0.532684E+11 | 0.311439E+11 | 0.833125E+09 | 0.303108E+11 | 0.00 | 0.00 |
Minimum of Months | 73678.77 | 0.231528E+10 | 0.715163E+09 | 0.00 | 0.715163E+09 | 0.00 | 0.00 |
Maximum of Months | 0.392673E+10 | 0.732479E+10 | 0.465114E+10 | 0.291653E+09 | 0.435948E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.730613E+09 | 0.402492E+10 | 0.134687E+10 | 0.541041E+09 | 0.805832E+09 | 0.00 | 0.00 |
February | 0.110947E+10 | 0.339715E+10 | 0.181406E+10 | 0.670127E+09 | 0.114393E+10 | 0.00 | 0.00 |
March | 0.119357E+10 | 0.312274E+10 | 0.209885E+10 | 0.413606E+09 | 0.168524E+10 | 0.00 | 0.00 |
April | 0.558131E+10 | 0.240582E+10 | 0.545378E+10 | 0.256277E+10 | 0.289101E+10 | 0.00 | 0.00 |
May | 0.592761E+10 | 0.211865E+10 | 0.592563E+10 | 0.258406E+10 | 0.334156E+10 | 0.00 | 0.00 |
June | 0.606827E+10 | 0.159286E+10 | 0.567608E+10 | 0.226697E+10 | 0.340911E+10 | 0.00 | 0.00 |
July | 0.668144E+10 | 0.151210E+10 | 0.598730E+10 | 0.254460E+10 | 0.344270E+10 | 0.00 | 0.00 |
August | 0.651313E+10 | 0.162876E+10 | 0.567166E+10 | 0.270986E+10 | 0.296179E+10 | 0.00 | 0.00 |
September | 0.547351E+10 | 0.206887E+10 | 0.494276E+10 | 0.262834E+10 | 0.231443E+10 | 0.00 | 0.00 |
October | 0.210322E+10 | 0.295941E+10 | 0.246547E+10 | 0.102175E+10 | 0.144371E+10 | 0.00 | 0.00 |
November | 0.669901E+09 | 0.351722E+10 | 0.124386E+10 | 0.423925E+09 | 0.819934E+09 | 0.00 | 0.00 |
December | 0.440864E+09 | 0.439920E+10 | 0.952580E+09 | 0.354156E+09 | 0.598424E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.424929E+11 | 0.327477E+11 | 0.435789E+11 | 0.187212E+11 | 0.248577E+11 | 0.00 | 0.00 |
Minimum of Months | 0.440864E+09 | 0.151210E+10 | 0.952580E+09 | 0.354156E+09 | 0.598424E+09 | 0.00 | 0.00 |
Maximum of Months | 0.668144E+10 | 0.439920E+10 | 0.598730E+10 | 0.270986E+10 | 0.344270E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.540826E+10 | 0.563707E+10 | 0.561146E+10 | 0.363252E+10 | 0.197894E+10 | 0.00 | 0.00 |
February | 0.613619E+10 | 0.498766E+10 | 0.619014E+10 | 0.377730E+10 | 0.241284E+10 | 0.00 | 0.00 |
March | 0.330093E+10 | 0.470962E+10 | 0.423721E+10 | 0.123368E+10 | 0.300353E+10 | 0.00 | 0.00 |
April | 0.949031E+10 | 0.394874E+10 | 0.851509E+10 | 0.384870E+10 | 0.466639E+10 | 0.00 | 0.00 |
May | 0.754377E+10 | 0.344789E+10 | 0.727754E+10 | 0.236931E+10 | 0.490823E+10 | 0.00 | 0.00 |
June | 0.699980E+10 | 0.258902E+10 | 0.648791E+10 | 0.157044E+10 | 0.491747E+10 | 0.00 | 0.00 |
July | 0.842754E+10 | 0.249192E+10 | 0.726385E+10 | 0.227474E+10 | 0.498911E+10 | 0.00 | 0.00 |
August | 0.104375E+11 | 0.271704E+10 | 0.851162E+10 | 0.382882E+10 | 0.468280E+10 | 0.00 | 0.00 |
September | 0.118415E+11 | 0.333506E+10 | 0.973402E+10 | 0.570233E+10 | 0.403169E+10 | 0.00 | 0.00 |
October | 0.746169E+10 | 0.447271E+10 | 0.691059E+10 | 0.403892E+10 | 0.287167E+10 | 0.00 | 0.00 |
November | 0.459147E+10 | 0.516502E+10 | 0.474155E+10 | 0.288440E+10 | 0.185715E+10 | 0.00 | 0.00 |
December | 0.361036E+10 | 0.640624E+10 | 0.388338E+10 | 0.248810E+10 | 0.139529E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.852493E+11 | 0.499080E+11 | 0.793644E+11 | 0.376493E+11 | 0.417151E+11 | 0.00 | 0.00 |
Minimum of Months | 0.330093E+10 | 0.249192E+10 | 0.388338E+10 | 0.123368E+10 | 0.139529E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118415E+11 | 0.640624E+10 | 0.973402E+10 | 0.570233E+10 | 0.498911E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.710237E+09 | 0.430635E+10 | 0.130977E+10 | 0.432753E+09 | 0.877016E+09 | 0.00 | 0.00 |
February | 0.152716E+10 | 0.380974E+10 | 0.209459E+10 | 0.884403E+09 | 0.121019E+10 | 0.00 | 0.00 |
March | 0.107873E+10 | 0.359718E+10 | 0.209688E+10 | 0.401134E+09 | 0.169575E+10 | 0.00 | 0.00 |
April | 0.464330E+10 | 0.290919E+10 | 0.478806E+10 | 0.190186E+10 | 0.288620E+10 | 0.00 | 0.00 |
May | 0.574868E+10 | 0.238492E+10 | 0.580476E+10 | 0.236041E+10 | 0.344434E+10 | 0.00 | 0.00 |
June | 0.648215E+10 | 0.187669E+10 | 0.606630E+10 | 0.249727E+10 | 0.356904E+10 | 0.00 | 0.00 |
July | 0.709218E+10 | 0.184856E+10 | 0.638420E+10 | 0.281481E+10 | 0.356939E+10 | 0.00 | 0.00 |
August | 0.598747E+10 | 0.204289E+10 | 0.536231E+10 | 0.232173E+10 | 0.304058E+10 | 0.00 | 0.00 |
September | 0.450694E+10 | 0.235336E+10 | 0.416322E+10 | 0.186688E+10 | 0.229634E+10 | 0.00 | 0.00 |
October | 0.186305E+10 | 0.336218E+10 | 0.229495E+10 | 0.825253E+09 | 0.146969E+10 | 0.00 | 0.00 |
November | 0.635275E+09 | 0.410239E+10 | 0.120188E+10 | 0.350845E+09 | 0.851039E+09 | 0.00 | 0.00 |
December | 0.200138E+09 | 0.522862E+10 | 0.702978E+09 | 0.148344E+09 | 0.554635E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.404753E+11 | 0.378221E+11 | 0.422699E+11 | 0.168057E+11 | 0.254642E+11 | 0.00 | 0.00 |
Minimum of Months | 0.200138E+09 | 0.184856E+10 | 0.702978E+09 | 0.148344E+09 | 0.554635E+09 | 0.00 | 0.00 |
Maximum of Months | 0.709218E+10 | 0.522862E+10 | 0.638420E+10 | 0.281481E+10 | 0.356939E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 65422253.00 | 0.590023E+10 | 0.988429E+09 | 0.00 | 0.988429E+09 | 0.00 | 0.00 |
February | 0.202328E+09 | 0.497131E+10 | 0.139410E+10 | 0.00 | 0.139410E+10 | 0.00 | 0.00 |
March | 0.688376E+09 | 0.460586E+10 | 0.213590E+10 | 0.00 | 0.213590E+10 | 0.00 | 0.00 |
April | 0.210710E+10 | 0.362891E+10 | 0.336538E+10 | 15062057.15 | 0.335032E+10 | 0.00 | 0.00 |
May | 0.279285E+10 | 0.298010E+10 | 0.434784E+10 | 0.209762E+09 | 0.413808E+10 | 0.00 | 0.00 |
June | 0.383064E+10 | 0.228918E+10 | 0.465123E+10 | 0.291662E+09 | 0.435956E+10 | 0.00 | 0.00 |
July | 0.401732E+10 | 0.218128E+10 | 0.455900E+10 | 0.259933E+09 | 0.429907E+10 | 0.00 | 0.00 |
August | 0.308713E+10 | 0.244284E+10 | 0.358361E+10 | 56146320.57 | 0.352747E+10 | 0.00 | 0.00 |
September | 0.196102E+10 | 0.313881E+10 | 0.263963E+10 | 584097.80 | 0.263905E+10 | 0.00 | 0.00 |
October | 0.717576E+09 | 0.429335E+10 | 0.174784E+10 | 0.00 | 0.174784E+10 | 0.00 | 0.00 |
November | 0.107548E+09 | 0.504694E+10 | 0.101632E+10 | 0.00 | 0.101632E+10 | 0.00 | 0.00 |
December | 5019202.77 | 0.626913E+10 | 0.715179E+09 | 0.00 | 0.715179E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.195823E+11 | 0.477479E+11 | 0.311445E+11 | 0.833150E+09 | 0.303113E+11 | 0.00 | 0.00 |
Minimum of Months | 5019202.77 | 0.218128E+10 | 0.715179E+09 | 0.00 | 0.715179E+09 | 0.00 | 0.00 |
Maximum of Months | 0.401732E+10 | 0.626913E+10 | 0.465123E+10 | 0.291662E+09 | 0.435956E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.779638E+09 | 0.368710E+10 | 0.134687E+10 | 0.541039E+09 | 0.805829E+09 | 0.00 | 0.00 |
February | 0.116898E+10 | 0.313618E+10 | 0.181405E+10 | 0.670124E+09 | 0.114393E+10 | 0.00 | 0.00 |
March | 0.128069E+10 | 0.287952E+10 | 0.209884E+10 | 0.413604E+09 | 0.168523E+10 | 0.00 | 0.00 |
April | 0.559469E+10 | 0.230463E+10 | 0.545376E+10 | 0.256276E+10 | 0.289100E+10 | 0.00 | 0.00 |
May | 0.593947E+10 | 0.201773E+10 | 0.592560E+10 | 0.258405E+10 | 0.334155E+10 | 0.00 | 0.00 |
June | 0.606515E+10 | 0.153451E+10 | 0.567606E+10 | 0.226696E+10 | 0.340910E+10 | 0.00 | 0.00 |
July | 0.666330E+10 | 0.147484E+10 | 0.598727E+10 | 0.254459E+10 | 0.344268E+10 | 0.00 | 0.00 |
August | 0.649935E+10 | 0.160645E+10 | 0.567163E+10 | 0.270985E+10 | 0.296178E+10 | 0.00 | 0.00 |
September | 0.547778E+10 | 0.198177E+10 | 0.494274E+10 | 0.262832E+10 | 0.231442E+10 | 0.00 | 0.00 |
October | 0.216044E+10 | 0.272501E+10 | 0.246546E+10 | 0.102175E+10 | 0.144371E+10 | 0.00 | 0.00 |
November | 0.717268E+09 | 0.317539E+10 | 0.124385E+10 | 0.423923E+09 | 0.819931E+09 | 0.00 | 0.00 |
December | 0.481984E+09 | 0.397183E+10 | 0.952576E+09 | 0.354154E+09 | 0.598421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.428287E+11 | 0.304950E+11 | 0.435787E+11 | 0.187211E+11 | 0.248576E+11 | 0.00 | 0.00 |
Minimum of Months | 0.481984E+09 | 0.147484E+10 | 0.952576E+09 | 0.354154E+09 | 0.598421E+09 | 0.00 | 0.00 |
Maximum of Months | 0.666330E+10 | 0.397183E+10 | 0.598727E+10 | 0.270985E+10 | 0.344268E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.543727E+10 | 0.543857E+10 | 0.561163E+10 | 0.363264E+10 | 0.197899E+10 | 0.00 | 0.00 |
February | 0.615454E+10 | 0.482044E+10 | 0.619033E+10 | 0.377742E+10 | 0.241290E+10 | 0.00 | 0.00 |
March | 0.337314E+10 | 0.445336E+10 | 0.423733E+10 | 0.123372E+10 | 0.300361E+10 | 0.00 | 0.00 |
April | 0.949304E+10 | 0.381631E+10 | 0.851532E+10 | 0.384883E+10 | 0.466650E+10 | 0.00 | 0.00 |
May | 0.754702E+10 | 0.334203E+10 | 0.727773E+10 | 0.236939E+10 | 0.490834E+10 | 0.00 | 0.00 |
June | 0.701874E+10 | 0.249539E+10 | 0.648807E+10 | 0.157049E+10 | 0.491758E+10 | 0.00 | 0.00 |
July | 0.844295E+10 | 0.241139E+10 | 0.726403E+10 | 0.227481E+10 | 0.498922E+10 | 0.00 | 0.00 |
August | 0.104385E+11 | 0.265388E+10 | 0.851185E+10 | 0.382894E+10 | 0.468290E+10 | 0.00 | 0.00 |
September | 0.118014E+11 | 0.327518E+10 | 0.973430E+10 | 0.570252E+10 | 0.403179E+10 | 0.00 | 0.00 |
October | 0.747220E+10 | 0.429167E+10 | 0.691080E+10 | 0.403905E+10 | 0.287175E+10 | 0.00 | 0.00 |
November | 0.462891E+10 | 0.486276E+10 | 0.474170E+10 | 0.288449E+10 | 0.185720E+10 | 0.00 | 0.00 |
December | 0.366829E+10 | 0.599674E+10 | 0.388350E+10 | 0.248818E+10 | 0.139532E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.854760E+11 | 0.478577E+11 | 0.793666E+11 | 0.376505E+11 | 0.417161E+11 | 0.00 | 0.00 |
Minimum of Months | 0.337314E+10 | 0.241139E+10 | 0.388350E+10 | 0.123372E+10 | 0.139532E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118014E+11 | 0.599674E+10 | 0.973430E+10 | 0.570252E+10 | 0.498922E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.772811E+09 | 0.382932E+10 | 0.130976E+10 | 0.432751E+09 | 0.877012E+09 | 0.00 | 0.00 |
February | 0.162782E+10 | 0.331253E+10 | 0.209458E+10 | 0.884399E+09 | 0.121018E+10 | 0.00 | 0.00 |
March | 0.126076E+10 | 0.299691E+10 | 0.209687E+10 | 0.401132E+09 | 0.169574E+10 | 0.00 | 0.00 |
April | 0.482863E+10 | 0.251119E+10 | 0.478804E+10 | 0.190185E+10 | 0.288619E+10 | 0.00 | 0.00 |
May | 0.584059E+10 | 0.220488E+10 | 0.580473E+10 | 0.236040E+10 | 0.344433E+10 | 0.00 | 0.00 |
June | 0.657468E+10 | 0.170097E+10 | 0.606628E+10 | 0.249726E+10 | 0.356902E+10 | 0.00 | 0.00 |
July | 0.721642E+10 | 0.165216E+10 | 0.638418E+10 | 0.281480E+10 | 0.356938E+10 | 0.00 | 0.00 |
August | 0.612501E+10 | 0.179790E+10 | 0.536228E+10 | 0.232172E+10 | 0.304057E+10 | 0.00 | 0.00 |
September | 0.459209E+10 | 0.215756E+10 | 0.416320E+10 | 0.186687E+10 | 0.229633E+10 | 0.00 | 0.00 |
October | 0.199017E+10 | 0.287707E+10 | 0.229494E+10 | 0.825250E+09 | 0.146969E+10 | 0.00 | 0.00 |
November | 0.723751E+09 | 0.335269E+10 | 0.120188E+10 | 0.350843E+09 | 0.851035E+09 | 0.00 | 0.00 |
December | 0.251049E+09 | 0.422266E+10 | 0.702975E+09 | 0.148343E+09 | 0.554632E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.418038E+11 | 0.326158E+11 | 0.422697E+11 | 0.168056E+11 | 0.254641E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251049E+09 | 0.165216E+10 | 0.702975E+09 | 0.148343E+09 | 0.554632E+09 | 0.00 | 0.00 |
Maximum of Months | 0.721642E+10 | 0.422266E+10 | 0.638418E+10 | 0.281480E+10 | 0.356938E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108126E+09 | 0.532824E+10 | 0.988429E+09 | 0.00 | 0.988429E+09 | 0.00 | 0.00 |
February | 0.291103E+09 | 0.449149E+10 | 0.139410E+10 | 0.00 | 0.139410E+10 | 0.00 | 0.00 |
March | 0.810909E+09 | 0.418364E+10 | 0.213590E+10 | 0.00 | 0.213590E+10 | 0.00 | 0.00 |
April | 0.221563E+10 | 0.337403E+10 | 0.336538E+10 | 15062057.15 | 0.335032E+10 | 0.00 | 0.00 |
May | 0.292842E+10 | 0.278473E+10 | 0.434784E+10 | 0.209762E+09 | 0.413808E+10 | 0.00 | 0.00 |
June | 0.388247E+10 | 0.219187E+10 | 0.465123E+10 | 0.291662E+09 | 0.435956E+10 | 0.00 | 0.00 |
July | 0.406089E+10 | 0.209690E+10 | 0.455900E+10 | 0.259933E+09 | 0.429907E+10 | 0.00 | 0.00 |
August | 0.312395E+10 | 0.234575E+10 | 0.358361E+10 | 56146320.57 | 0.352747E+10 | 0.00 | 0.00 |
September | 0.204296E+10 | 0.293816E+10 | 0.263963E+10 | 584097.80 | 0.263905E+10 | 0.00 | 0.00 |
October | 0.839973E+09 | 0.383462E+10 | 0.174784E+10 | 0.00 | 0.174784E+10 | 0.00 | 0.00 |
November | 0.161735E+09 | 0.450589E+10 | 0.101632E+10 | 0.00 | 0.101632E+10 | 0.00 | 0.00 |
December | 24609848.44 | 0.569774E+10 | 0.715179E+09 | 0.00 | 0.715179E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.204908E+11 | 0.437731E+11 | 0.311445E+11 | 0.833150E+09 | 0.303113E+11 | 0.00 | 0.00 |
Minimum of Months | 24609848.44 | 0.209690E+10 | 0.715179E+09 | 0.00 | 0.715179E+09 | 0.00 | 0.00 |
Maximum of Months | 0.406089E+10 | 0.569774E+10 | 0.465123E+10 | 0.291662E+09 | 0.435956E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.831684E+09 | 0.335579E+10 | 0.134687E+10 | 0.541039E+09 | 0.805829E+09 | 0.00 | 0.00 |
February | 0.124340E+10 | 0.286321E+10 | 0.181405E+10 | 0.670124E+09 | 0.114393E+10 | 0.00 | 0.00 |
March | 0.135708E+10 | 0.265514E+10 | 0.209884E+10 | 0.413604E+09 | 0.168523E+10 | 0.00 | 0.00 |
April | 0.564600E+10 | 0.218421E+10 | 0.545376E+10 | 0.256276E+10 | 0.289100E+10 | 0.00 | 0.00 |
May | 0.599027E+10 | 0.191888E+10 | 0.592560E+10 | 0.258405E+10 | 0.334155E+10 | 0.00 | 0.00 |
June | 0.607762E+10 | 0.148711E+10 | 0.567606E+10 | 0.226696E+10 | 0.340910E+10 | 0.00 | 0.00 |
July | 0.666714E+10 | 0.143583E+10 | 0.598727E+10 | 0.254459E+10 | 0.344268E+10 | 0.00 | 0.00 |
August | 0.650132E+10 | 0.156727E+10 | 0.567163E+10 | 0.270985E+10 | 0.296178E+10 | 0.00 | 0.00 |
September | 0.550810E+10 | 0.189533E+10 | 0.494274E+10 | 0.262832E+10 | 0.231442E+10 | 0.00 | 0.00 |
October | 0.223539E+10 | 0.248399E+10 | 0.246546E+10 | 0.102175E+10 | 0.144371E+10 | 0.00 | 0.00 |
November | 0.767541E+09 | 0.287784E+10 | 0.124385E+10 | 0.423923E+09 | 0.819931E+09 | 0.00 | 0.00 |
December | 0.520087E+09 | 0.363331E+10 | 0.952576E+09 | 0.354154E+09 | 0.598421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.433456E+11 | 0.283579E+11 | 0.435787E+11 | 0.187211E+11 | 0.248576E+11 | 0.00 | 0.00 |
Minimum of Months | 0.520087E+09 | 0.143583E+10 | 0.952576E+09 | 0.354154E+09 | 0.598421E+09 | 0.00 | 0.00 |
Maximum of Months | 0.666714E+10 | 0.363331E+10 | 0.598727E+10 | 0.270985E+10 | 0.344268E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.557143E+10 | 0.494161E+10 | 0.561163E+10 | 0.363264E+10 | 0.197899E+10 | 0.00 | 0.00 |
February | 0.628515E+10 | 0.440626E+10 | 0.619033E+10 | 0.377742E+10 | 0.241290E+10 | 0.00 | 0.00 |
March | 0.350136E+10 | 0.409379E+10 | 0.423733E+10 | 0.123372E+10 | 0.300361E+10 | 0.00 | 0.00 |
April | 0.956468E+10 | 0.360885E+10 | 0.851532E+10 | 0.384883E+10 | 0.466650E+10 | 0.00 | 0.00 |
May | 0.762092E+10 | 0.315726E+10 | 0.727773E+10 | 0.236939E+10 | 0.490834E+10 | 0.00 | 0.00 |
June | 0.705237E+10 | 0.239985E+10 | 0.648807E+10 | 0.157049E+10 | 0.491758E+10 | 0.00 | 0.00 |
July | 0.846514E+10 | 0.232791E+10 | 0.726403E+10 | 0.227481E+10 | 0.498922E+10 | 0.00 | 0.00 |
August | 0.104494E+11 | 0.257230E+10 | 0.851185E+10 | 0.382894E+10 | 0.468290E+10 | 0.00 | 0.00 |
September | 0.118408E+11 | 0.312498E+10 | 0.973430E+10 | 0.570252E+10 | 0.403179E+10 | 0.00 | 0.00 |
October | 0.757516E+10 | 0.392016E+10 | 0.691080E+10 | 0.403905E+10 | 0.287175E+10 | 0.00 | 0.00 |
November | 0.473043E+10 | 0.440439E+10 | 0.474170E+10 | 0.288449E+10 | 0.185720E+10 | 0.00 | 0.00 |
December | 0.375938E+10 | 0.547442E+10 | 0.388350E+10 | 0.248818E+10 | 0.139532E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.864162E+11 | 0.444318E+11 | 0.793666E+11 | 0.376505E+11 | 0.417161E+11 | 0.00 | 0.00 |
Minimum of Months | 0.350136E+10 | 0.232791E+10 | 0.388350E+10 | 0.123372E+10 | 0.139532E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118408E+11 | 0.547442E+10 | 0.973430E+10 | 0.570252E+10 | 0.498922E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.811238E+09 | 0.352492E+10 | 0.130976E+10 | 0.432751E+09 | 0.877012E+09 | 0.00 | 0.00 |
February | 0.167687E+10 | 0.306882E+10 | 0.209458E+10 | 0.884399E+09 | 0.121018E+10 | 0.00 | 0.00 |
March | 0.131720E+10 | 0.279207E+10 | 0.209687E+10 | 0.401132E+09 | 0.169574E+10 | 0.00 | 0.00 |
April | 0.487450E+10 | 0.238432E+10 | 0.478804E+10 | 0.190185E+10 | 0.288619E+10 | 0.00 | 0.00 |
May | 0.588270E+10 | 0.209749E+10 | 0.580473E+10 | 0.236040E+10 | 0.344433E+10 | 0.00 | 0.00 |
June | 0.658895E+10 | 0.164273E+10 | 0.606628E+10 | 0.249726E+10 | 0.356902E+10 | 0.00 | 0.00 |
July | 0.722431E+10 | 0.160016E+10 | 0.638418E+10 | 0.281480E+10 | 0.356938E+10 | 0.00 | 0.00 |
August | 0.613497E+10 | 0.174258E+10 | 0.536228E+10 | 0.232172E+10 | 0.304057E+10 | 0.00 | 0.00 |
September | 0.462340E+10 | 0.205797E+10 | 0.416320E+10 | 0.186687E+10 | 0.229633E+10 | 0.00 | 0.00 |
October | 0.204456E+10 | 0.265743E+10 | 0.229494E+10 | 0.825250E+09 | 0.146969E+10 | 0.00 | 0.00 |
November | 0.754323E+09 | 0.308598E+10 | 0.120188E+10 | 0.350843E+09 | 0.851035E+09 | 0.00 | 0.00 |
December | 0.270266E+09 | 0.391059E+10 | 0.702975E+09 | 0.148343E+09 | 0.554632E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.422033E+11 | 0.305651E+11 | 0.422697E+11 | 0.168056E+11 | 0.254641E+11 | 0.00 | 0.00 |
Minimum of Months | 0.270266E+09 | 0.160016E+10 | 0.702975E+09 | 0.148343E+09 | 0.554632E+09 | 0.00 | 0.00 |
Maximum of Months | 0.722431E+10 | 0.391059E+10 | 0.638418E+10 | 0.281480E+10 | 0.356938E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.397701E+11 | -0.387437E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102637E+10 | 58.98 | 0.00 | 0.00 |
February | 0.363679E+11 | -0.354407E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -927254035.8 | 58.98 | 0.00 | 0.00 |
March | 0.424402E+11 | -0.414118E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102837E+10 | 58.98 | 0.00 | 0.00 |
April | 0.378269E+11 | -0.368376E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989316093.3 | 58.97 | 0.00 | 0.00 |
May | 0.393117E+11 | -0.382864E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102530E+10 | 58.99 | 0.00 | 0.00 |
June | 0.379184E+11 | -0.369263E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992079769.6 | 58.98 | 0.00 | 0.00 |
July | 0.353927E+11 | -0.343729E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101988E+10 | 58.98 | 0.00 | 0.00 |
August | 0.383627E+11 | -0.373386E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102406E+10 | 58.98 | 0.00 | 0.00 |
September | 0.351152E+11 | -0.341258E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989430923.4 | 58.98 | 0.00 | 0.00 |
October | 0.369785E+11 | -0.359565E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102200E+10 | 58.98 | 0.00 | 0.00 |
November | 0.372668E+11 | -0.362774E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989429379.1 | 58.98 | 0.00 | 0.00 |
December | 0.381145E+11 | -0.370905E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102403E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.454866E+12 | -0.442808E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120575E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.351152E+11 | -0.414118E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102837E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.424402E+11 | -0.341258E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -927254035.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.64 | 0.61 | 01-JAN-08:50 | 3366.92 | 31.55 | 158.33 | 213.50 | 2988.48 | 37.39 | 190.17 | 181.50 |
February | 217.00 | 0.63 | 0.61 | 01-FEB-11:39 | 5046.50 | 33.21 | 193.50 | 237.17 | 2313.10 | 29.69 | 178.00 | 206.17 |
March | 215.50 | 0.63 | 0.61 | 01-MAR-11:39 | 3765.21 | 30.26 | 180.50 | 301.17 | 987.19 | 21.06 | 146.17 | 251.17 |
April | 359.67 | 0.64 | 0.61 | 01-APR-06:40 | 2193.16 | 18.32 | 0.00 | 348.33 | 1210.02 | 21.31 | 227.17 | 316.33 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 1750.35 | 17.87 | 0.00 | 401.00 | 962.16 | 20.85 | 219.50 | 353.67 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-05:30 | 1707.08 | 18.19 | 0.00 | 402.67 | 929.62 | 21.15 | 225.50 | 355.83 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-05:30 | 1693.73 | 17.92 | 0.00 | 412.33 | 945.96 | 20.90 | 217.50 | 366.67 |
August | 396.33 | 0.64 | 0.61 | 01-AUG-05:00 | 1953.34 | 17.95 | 0.00 | 374.33 | 1102.05 | 20.94 | 230.83 | 333.83 |
September | 337.67 | 0.63 | 0.61 | 01-SEP-07:40 | 2964.90 | 20.07 | 29.50 | 323.00 | 1327.84 | 21.53 | 212.50 | 291.00 |
October | 234.00 | 0.63 | 0.61 | 01-OCT-06:00 | 6491.31 | 33.98 | 212.17 | 273.17 | 1786.69 | 24.21 | 175.33 | 228.67 |
November | 171.33 | 0.64 | 0.61 | 01-NOV-11:39 | 3971.95 | 32.82 | 148.33 | 204.67 | 3442.55 | 37.29 | 167.83 | 161.17 |
December | 131.67 | 0.63 | 0.61 | 02-DEC-08:39 | 3170.03 | 31.91 | 101.33 | 169.17 | 2888.08 | 38.35 | 128.67 | 121.17 |
Annual Sum or Average | 3515.67 | 0.63 | 2817.14 | 22.97 | 1023.67 | 3660.50 | 1478.22 | 24.17 | 2319.17 | 3167.17 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 1693.73 | 17.87 | 0.00 | 169.17 | 929.62 | 20.85 | 128.67 | 121.17 | |
Maximum of Months | 429.00 | 0.64 | 0.61 | 6491.31 | 33.98 | 212.17 | 412.33 | 3442.55 | 38.35 | 230.83 | 366.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.65 | 0.61 | 01-JAN-08:50 | 1177.27 | 18.99 | 63.33 | 195.83 | 743.50 | 20.69 | 59.83 | 118.00 |
February | 217.00 | 0.64 | 0.61 | 01-FEB-11:39 | 1463.45 | 19.08 | 61.33 | 226.67 | 786.42 | 18.55 | 39.50 | 166.67 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 1649.17 | 17.67 | 52.33 | 293.50 | 891.82 | 18.77 | 51.83 | 223.67 |
April | 359.67 | 0.63 | 0.61 | 01-APR-06:10 | 2967.69 | 16.57 | 51.33 | 356.67 | 1814.55 | 15.57 | 0.00 | 317.00 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 3253.45 | 16.07 | 53.50 | 413.33 | 1446.59 | 15.30 | 0.00 | 360.00 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-04:49 | 3262.63 | 14.38 | 0.00 | 410.33 | 1471.55 | 15.66 | 0.00 | 371.50 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-04:49 | 3199.93 | 14.20 | 3.67 | 422.33 | 1421.45 | 15.43 | 0.00 | 382.50 |
August | 396.33 | 0.63 | 0.61 | 01-AUG-05:30 | 3105.90 | 16.26 | 53.00 | 380.67 | 1286.87 | 15.30 | 0.00 | 340.00 |
September | 337.67 | 0.63 | 0.61 | 01-SEP-07:40 | 2793.07 | 17.11 | 55.00 | 327.33 | 1606.99 | 16.00 | 5.50 | 291.83 |
October | 234.00 | 0.63 | 0.61 | 01-OCT-06:49 | 2144.87 | 19.34 | 66.00 | 261.83 | 987.53 | 18.72 | 36.83 | 191.17 |
November | 171.33 | 0.64 | 0.61 | 01-NOV-11:39 | 1222.69 | 19.33 | 53.17 | 187.83 | 690.38 | 19.00 | 38.17 | 106.17 |
December | 131.67 | 0.64 | 0.61 | 02-DEC-08:39 | 970.95 | 19.33 | 39.00 | 145.17 | 751.64 | 23.25 | 53.50 | 85.67 |
Annual Sum or Average | 3515.67 | 0.63 | 2575.29 | 16.76 | 551.67 | 3621.50 | 1274.16 | 16.87 | 285.17 | 2954.17 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 970.95 | 14.20 | 0.00 | 145.17 | 690.38 | 15.30 | 0.00 | 85.67 | |
Maximum of Months | 429.00 | 0.65 | 0.61 | 3262.63 | 19.34 | 66.00 | 422.33 | 1814.55 | 23.25 | 59.83 | 382.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.67 | 0.61 | 01-JAN-09:39 | 434.91 | 0.00 | 0.00 | 163.17 | 253.66 | 0.00 | 0.00 | 21.67 |
February | 217.00 | 0.65 | 0.61 | 01-FEB-11:39 | 577.57 | 0.00 | 0.00 | 209.00 | 338.72 | 0.00 | 0.00 | 97.17 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 726.31 | 0.00 | 0.00 | 287.33 | 390.38 | 0.00 | 0.00 | 164.33 |
April | 359.67 | 0.63 | 0.61 | 01-APR-06:30 | 945.18 | 0.00 | 0.00 | 354.67 | 564.09 | 0.00 | 0.00 | 307.83 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 1129.69 | 0.00 | 0.00 | 419.33 | 646.30 | 0.00 | 0.00 | 384.67 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-04:00 | 1281.71 | 0.00 | 0.00 | 421.00 | 708.90 | 0.00 | 0.00 | 390.67 |
July | 429.00 | 0.62 | 0.61 | 01-JUL-04:00 | 1185.09 | 0.00 | 0.00 | 431.83 | 694.10 | 0.00 | 0.00 | 401.67 |
August | 396.33 | 0.63 | 0.61 | 01-AUG-05:49 | 940.04 | 0.00 | 0.00 | 383.17 | 581.33 | 0.00 | 0.00 | 343.50 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 764.98 | 0.00 | 0.00 | 315.83 | 483.77 | 0.00 | 0.00 | 257.50 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-07:19 | 652.28 | 0.00 | 0.00 | 244.17 | 392.41 | 0.00 | 0.00 | 138.33 |
November | 171.33 | 0.66 | 0.61 | 01-NOV-11:39 | 482.08 | 0.00 | 0.00 | 156.00 | 283.01 | 0.00 | 0.00 | 46.50 |
December | 131.67 | 0.67 | 0.61 | 02-DEC-09:09 | 406.30 | 0.00 | 0.00 | 99.83 | 240.90 | 0.00 | 0.00 | 9.17 |
Annual Sum or Average | 3515.67 | 0.64 | 891.02 | 0.00 | 0.00 | 3485.33 | 521.79 | 0.00 | 0.00 | 2563.00 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 406.30 | 0.00 | 0.00 | 99.83 | 240.90 | 0.00 | 0.00 | 9.17 | |
Maximum of Months | 429.00 | 0.67 | 0.61 | 1281.71 | 0.00 | 0.00 | 431.83 | 708.90 | 0.00 | 0.00 | 401.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.66 | 0.61 | 01-JAN-09:39 | 1074.98 | 18.78 | 64.50 | 187.50 | 598.77 | 18.00 | 41.67 | 114.83 |
February | 217.00 | 0.64 | 0.61 | 01-FEB-11:39 | 1506.50 | 16.99 | 40.17 | 221.83 | 892.75 | 18.01 | 35.00 | 157.83 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 1555.12 | 17.64 | 53.67 | 291.83 | 865.20 | 17.21 | 34.50 | 226.33 |
April | 359.67 | 0.64 | 0.61 | 01-APR-07:10 | 3039.58 | 17.50 | 73.33 | 344.00 | 1354.69 | 15.47 | 0.00 | 311.33 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 2634.28 | 13.89 | 0.00 | 401.17 | 1499.51 | 15.30 | 1.33 | 365.33 |
June | 410.67 | 0.63 | 0.61 | 01-JUN-05:40 | 3207.22 | 14.28 | 0.00 | 405.17 | 1391.56 | 16.95 | 32.83 | 364.67 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-05:40 | 3163.81 | 13.93 | 0.00 | 414.83 | 1414.37 | 16.72 | 34.50 | 377.50 |
August | 396.33 | 0.64 | 0.61 | 01-AUG-06:10 | 2715.80 | 14.20 | 8.50 | 370.17 | 1555.22 | 15.49 | 5.50 | 333.33 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 2603.78 | 18.02 | 75.33 | 313.00 | 1482.84 | 17.93 | 49.00 | 274.67 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-07:30 | 2038.21 | 18.98 | 65.33 | 255.17 | 927.12 | 18.29 | 36.50 | 188.00 |
November | 171.33 | 0.65 | 0.61 | 01-NOV-11:39 | 1195.02 | 18.72 | 50.50 | 179.17 | 629.21 | 18.13 | 32.83 | 109.83 |
December | 131.67 | 0.66 | 0.61 | 02-DEC-09:09 | 812.69 | 16.98 | 30.17 | 133.17 | 449.05 | 17.44 | 20.67 | 64.17 |
Annual Sum or Average | 3515.67 | 0.64 | 2412.97 | 16.12 | 461.50 | 3517.00 | 1220.06 | 16.81 | 324.33 | 2887.83 | ||
Minimum of Months | 131.67 | 0.63 | 0.61 | 812.69 | 13.89 | 0.00 | 133.17 | 449.05 | 15.30 | 0.00 | 64.17 | |
Maximum of Months | 429.00 | 0.66 | 0.61 | 3207.22 | 18.98 | 75.33 | 414.83 | 1555.22 | 18.29 | 49.00 | 377.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.64 | 0.61 | 01-JAN-08:50 | 2902.66 | 23.97 | 113.17 | 211.83 | 2979.71 | 35.12 | 176.17 | 180.67 |
February | 217.00 | 0.63 | 0.61 | 01-FEB-11:39 | 4993.06 | 32.34 | 193.50 | 236.17 | 2404.79 | 29.54 | 141.83 | 209.83 |
March | 215.50 | 0.63 | 0.61 | 01-MAR-11:39 | 3707.91 | 29.14 | 180.00 | 300.50 | 1012.16 | 16.36 | 3.33 | 253.00 |
April | 359.67 | 0.64 | 0.61 | 01-APR-06:40 | 2152.57 | 12.51 | 0.00 | 347.67 | 1250.70 | 17.29 | 0.00 | 318.17 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 1717.33 | 12.17 | 0.00 | 399.83 | 993.32 | 16.91 | 0.00 | 356.50 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-05:30 | 1672.70 | 12.50 | 0.00 | 401.00 | 958.32 | 17.23 | 0.00 | 357.83 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-05:30 | 1663.32 | 12.27 | 0.00 | 410.67 | 976.75 | 17.04 | 0.00 | 368.00 |
August | 396.33 | 0.64 | 0.61 | 01-AUG-05:00 | 2051.53 | 12.54 | 5.50 | 371.50 | 1139.97 | 16.96 | 0.00 | 336.17 |
September | 337.67 | 0.63 | 0.61 | 01-SEP-07:40 | 3903.11 | 17.84 | 75.83 | 320.17 | 1375.29 | 17.33 | 0.00 | 292.00 |
October | 234.00 | 0.63 | 0.61 | 01-OCT-06:00 | 6395.32 | 33.02 | 209.17 | 270.83 | 1829.32 | 20.00 | 32.83 | 229.67 |
November | 171.33 | 0.64 | 0.61 | 01-NOV-11:39 | 3656.50 | 28.31 | 125.33 | 202.33 | 3474.17 | 36.97 | 167.17 | 162.50 |
December | 131.67 | 0.63 | 0.61 | 02-DEC-08:39 | 2174.90 | 18.23 | 46.50 | 164.17 | 2906.44 | 37.49 | 126.17 | 122.17 |
Annual Sum or Average | 3515.67 | 0.63 | 2810.85 | 18.18 | 949.00 | 3636.67 | 1513.78 | 20.76 | 647.50 | 3186.50 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 1663.32 | 12.17 | 0.00 | 164.17 | 958.32 | 16.36 | 0.00 | 122.17 | |
Maximum of Months | 429.00 | 0.64 | 0.61 | 6395.32 | 33.02 | 209.17 | 410.67 | 3474.17 | 37.49 | 176.17 | 368.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.65 | 0.61 | 01-JAN-08:50 | 1170.60 | 17.04 | 63.00 | 195.17 | 757.19 | 18.95 | 59.50 | 120.33 |
February | 217.00 | 0.64 | 0.61 | 01-FEB-11:39 | 1289.57 | 14.38 | 40.00 | 225.33 | 804.81 | 16.38 | 39.67 | 170.67 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 1638.87 | 15.23 | 52.33 | 292.17 | 910.92 | 16.89 | 52.50 | 227.67 |
April | 359.67 | 0.63 | 0.61 | 01-APR-06:10 | 2966.42 | 13.75 | 51.33 | 356.17 | 1851.83 | 12.90 | 0.00 | 320.50 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 3245.75 | 13.21 | 53.50 | 412.83 | 1481.79 | 12.83 | 0.00 | 362.83 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-04:49 | 3246.32 | 10.97 | 0.00 | 409.33 | 1508.46 | 13.23 | 0.00 | 373.33 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-04:49 | 3159.36 | 10.83 | 3.67 | 422.17 | 1458.75 | 12.98 | 0.00 | 384.83 |
August | 396.33 | 0.63 | 0.61 | 01-AUG-05:30 | 2913.91 | 13.47 | 53.00 | 380.00 | 1323.16 | 12.73 | 0.00 | 344.17 |
September | 337.67 | 0.63 | 0.61 | 01-SEP-07:40 | 2795.80 | 14.39 | 55.17 | 326.33 | 1641.40 | 13.33 | 5.50 | 293.67 |
October | 234.00 | 0.63 | 0.61 | 01-OCT-06:49 | 2137.08 | 17.16 | 66.00 | 261.00 | 1013.00 | 16.47 | 37.00 | 193.83 |
November | 171.33 | 0.64 | 0.61 | 01-NOV-11:39 | 1214.66 | 17.33 | 53.50 | 187.00 | 705.20 | 16.91 | 37.83 | 110.33 |
December | 131.67 | 0.64 | 0.61 | 02-DEC-08:39 | 963.07 | 17.09 | 39.00 | 143.83 | 757.01 | 21.15 | 50.33 | 87.17 |
Annual Sum or Average | 3515.67 | 0.63 | 2533.07 | 13.87 | 530.50 | 3611.33 | 1304.10 | 14.50 | 282.33 | 2989.33 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 963.07 | 10.83 | 0.00 | 143.83 | 705.20 | 12.73 | 0.00 | 87.17 | |
Maximum of Months | 429.00 | 0.65 | 0.61 | 3246.32 | 17.33 | 66.00 | 422.17 | 1851.83 | 21.15 | 59.50 | 384.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.67 | 0.61 | 01-JAN-09:39 | 423.38 | 0.00 | 0.00 | 159.33 | 259.38 | 0.00 | 0.00 | 26.50 |
February | 217.00 | 0.65 | 0.61 | 01-FEB-11:39 | 563.70 | 0.00 | 0.00 | 207.00 | 347.06 | 0.00 | 0.00 | 105.33 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 710.50 | 0.00 | 0.00 | 285.17 | 401.01 | 0.00 | 0.00 | 172.17 |
April | 359.67 | 0.63 | 0.61 | 01-APR-06:40 | 928.08 | 0.00 | 0.00 | 353.83 | 580.21 | 0.00 | 0.00 | 311.17 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 1096.66 | 0.00 | 0.00 | 418.00 | 665.50 | 0.00 | 0.00 | 387.33 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-04:00 | 1259.91 | 0.00 | 0.00 | 420.17 | 758.49 | 0.00 | 0.00 | 394.83 |
July | 429.00 | 0.62 | 0.61 | 01-JUL-04:00 | 1168.04 | 0.00 | 0.00 | 431.17 | 713.82 | 0.00 | 0.00 | 403.50 |
August | 396.33 | 0.63 | 0.61 | 01-AUG-05:40 | 938.16 | 0.00 | 0.00 | 384.00 | 597.89 | 0.00 | 0.00 | 345.83 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 750.14 | 0.00 | 0.00 | 313.50 | 496.97 | 0.00 | 0.00 | 261.33 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-07:19 | 637.47 | 0.00 | 0.00 | 241.50 | 402.35 | 0.00 | 0.00 | 144.50 |
November | 171.33 | 0.66 | 0.61 | 01-NOV-11:39 | 469.64 | 0.00 | 0.00 | 152.83 | 289.54 | 0.00 | 0.00 | 50.33 |
December | 131.67 | 0.67 | 0.61 | 02-DEC-09:09 | 395.15 | 0.00 | 0.00 | 95.83 | 246.07 | 0.00 | 0.00 | 11.67 |
Annual Sum or Average | 3515.67 | 0.64 | 874.61 | 0.00 | 0.00 | 3462.33 | 539.71 | 0.00 | 0.00 | 2614.50 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 395.15 | 0.00 | 0.00 | 95.83 | 246.07 | 0.00 | 0.00 | 11.67 | |
Maximum of Months | 429.00 | 0.67 | 0.61 | 1259.91 | 0.00 | 0.00 | 431.17 | 758.49 | 0.00 | 0.00 | 403.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.66 | 0.61 | 01-JAN-09:39 | 1066.34 | 16.94 | 64.50 | 186.83 | 611.55 | 15.98 | 41.50 | 118.33 |
February | 217.00 | 0.65 | 0.61 | 01-FEB-11:39 | 1499.03 | 14.46 | 40.17 | 221.67 | 913.56 | 15.81 | 35.17 | 162.83 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 1542.77 | 15.25 | 53.83 | 291.17 | 883.80 | 15.06 | 34.50 | 230.00 |
April | 359.67 | 0.64 | 0.61 | 01-APR-07:10 | 3036.08 | 15.05 | 73.33 | 343.00 | 1388.52 | 12.90 | 0.00 | 312.67 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 2621.30 | 10.51 | 0.00 | 400.33 | 1534.13 | 12.85 | 1.33 | 367.83 |
June | 410.67 | 0.63 | 0.61 | 01-JUN-05:40 | 3188.36 | 10.87 | 0.00 | 405.00 | 1429.06 | 14.79 | 32.83 | 366.83 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-05:40 | 3147.54 | 10.52 | 0.00 | 414.00 | 1452.26 | 14.56 | 34.50 | 379.67 |
August | 396.33 | 0.64 | 0.61 | 01-AUG-06:10 | 2710.19 | 10.96 | 8.50 | 369.17 | 1590.60 | 13.04 | 5.50 | 335.17 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 2604.51 | 15.67 | 75.33 | 312.67 | 1514.51 | 15.81 | 49.00 | 277.67 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-07:30 | 2028.00 | 16.86 | 65.33 | 254.17 | 950.78 | 16.06 | 36.50 | 190.50 |
November | 171.33 | 0.65 | 0.61 | 01-NOV-11:39 | 1186.08 | 16.65 | 50.50 | 177.50 | 643.52 | 15.94 | 32.83 | 113.00 |
December | 131.67 | 0.66 | 0.61 | 02-DEC-09:09 | 804.89 | 14.68 | 30.17 | 131.17 | 459.81 | 15.10 | 20.50 | 66.50 |
Annual Sum or Average | 3515.67 | 0.64 | 2403.21 | 13.33 | 461.67 | 3506.67 | 1249.47 | 14.54 | 324.17 | 2921.00 | ||
Minimum of Months | 131.67 | 0.63 | 0.61 | 804.89 | 10.51 | 0.00 | 131.17 | 459.81 | 12.85 | 0.00 | 66.50 | |
Maximum of Months | 429.00 | 0.66 | 0.61 | 3188.36 | 16.94 | 75.33 | 414.00 | 1590.60 | 16.06 | 49.00 | 379.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.64 | 0.61 | 01-JAN-08:50 | 2901.00 | 23.94 | 113.00 | 211.83 | 2980.54 | 35.11 | 176.17 | 180.83 |
February | 217.00 | 0.63 | 0.61 | 01-FEB-11:39 | 4991.80 | 32.32 | 193.50 | 236.17 | 2406.24 | 29.53 | 141.83 | 210.33 |
March | 215.50 | 0.63 | 0.61 | 01-MAR-11:39 | 3708.36 | 29.12 | 180.00 | 300.50 | 1013.79 | 16.34 | 3.33 | 253.00 |
April | 359.67 | 0.64 | 0.61 | 01-APR-06:40 | 2153.57 | 12.47 | 0.00 | 347.83 | 1252.22 | 17.28 | 0.00 | 318.17 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 1718.22 | 12.13 | 0.00 | 399.67 | 994.51 | 16.89 | 0.00 | 356.67 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-05:30 | 1673.62 | 12.46 | 0.00 | 401.00 | 959.48 | 17.21 | 0.00 | 357.83 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-05:30 | 1664.11 | 12.23 | 0.00 | 410.67 | 977.85 | 17.02 | 0.00 | 368.17 |
August | 396.33 | 0.64 | 0.61 | 01-AUG-05:00 | 2052.36 | 12.50 | 5.50 | 371.50 | 1141.24 | 16.94 | 0.00 | 336.17 |
September | 337.67 | 0.63 | 0.61 | 01-SEP-07:40 | 3903.46 | 17.81 | 75.83 | 320.17 | 1376.78 | 17.32 | 0.00 | 292.00 |
October | 234.00 | 0.63 | 0.61 | 01-OCT-06:00 | 6394.26 | 33.01 | 209.17 | 270.83 | 1831.01 | 19.99 | 32.83 | 229.83 |
November | 171.33 | 0.64 | 0.61 | 01-NOV-11:39 | 3654.57 | 28.29 | 125.33 | 202.33 | 3475.38 | 36.96 | 167.17 | 162.83 |
December | 131.67 | 0.63 | 0.61 | 02-DEC-08:39 | 2173.01 | 18.19 | 46.50 | 164.17 | 2907.16 | 37.48 | 126.17 | 122.33 |
Annual Sum or Average | 3515.67 | 0.63 | 2811.01 | 18.15 | 948.83 | 3636.67 | 1515.07 | 20.75 | 647.50 | 3188.17 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 1664.11 | 12.13 | 0.00 | 164.17 | 959.48 | 16.34 | 0.00 | 122.33 | |
Maximum of Months | 429.00 | 0.64 | 0.61 | 6394.26 | 33.01 | 209.17 | 410.67 | 3475.38 | 37.48 | 176.17 | 368.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.65 | 0.61 | 01-JAN-08:50 | 1170.32 | 17.03 | 63.00 | 195.33 | 757.65 | 18.94 | 59.50 | 120.67 |
February | 217.00 | 0.64 | 0.61 | 01-FEB-11:39 | 1289.21 | 14.37 | 40.00 | 225.33 | 805.44 | 16.38 | 39.67 | 171.00 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 1638.97 | 15.22 | 52.33 | 292.17 | 911.88 | 16.89 | 52.50 | 228.00 |
April | 359.67 | 0.63 | 0.61 | 01-APR-06:10 | 2966.01 | 13.74 | 51.33 | 356.00 | 1852.89 | 12.89 | 0.00 | 320.50 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 3245.76 | 13.20 | 53.50 | 412.83 | 1482.89 | 12.83 | 0.00 | 362.83 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-04:49 | 3246.38 | 10.96 | 0.00 | 409.50 | 1509.64 | 13.23 | 0.00 | 373.33 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-04:49 | 3159.24 | 10.82 | 3.67 | 422.17 | 1459.84 | 12.97 | 0.00 | 385.00 |
August | 396.33 | 0.63 | 0.61 | 01-AUG-05:30 | 2913.52 | 13.45 | 53.00 | 380.00 | 1324.13 | 12.72 | 0.00 | 344.00 |
September | 337.67 | 0.63 | 0.61 | 01-SEP-07:40 | 2794.92 | 14.38 | 55.17 | 326.17 | 1642.20 | 13.32 | 5.50 | 293.83 |
October | 234.00 | 0.63 | 0.61 | 01-OCT-06:49 | 2136.55 | 17.15 | 66.00 | 261.17 | 1013.75 | 16.46 | 37.00 | 194.00 |
November | 171.33 | 0.64 | 0.61 | 01-NOV-11:39 | 1214.31 | 17.32 | 53.50 | 187.00 | 705.73 | 16.90 | 37.83 | 110.67 |
December | 131.67 | 0.64 | 0.61 | 02-DEC-08:39 | 962.69 | 17.08 | 39.00 | 143.83 | 757.45 | 21.14 | 50.33 | 87.17 |
Annual Sum or Average | 3515.67 | 0.63 | 2532.80 | 13.86 | 530.50 | 3611.50 | 1305.01 | 14.49 | 282.33 | 2991.00 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 962.69 | 10.82 | 0.00 | 143.83 | 705.73 | 12.72 | 0.00 | 87.17 | |
Maximum of Months | 429.00 | 0.65 | 0.61 | 3246.38 | 17.32 | 66.00 | 422.17 | 1852.89 | 21.14 | 59.50 | 385.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.67 | 0.61 | 01-JAN-09:39 | 423.33 | 0.00 | 0.00 | 159.17 | 259.64 | 0.00 | 0.00 | 26.67 |
February | 217.00 | 0.65 | 0.61 | 01-FEB-11:39 | 563.66 | 0.00 | 0.00 | 207.00 | 347.41 | 0.00 | 0.00 | 105.67 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 710.75 | 0.00 | 0.00 | 285.33 | 401.55 | 0.00 | 0.00 | 172.83 |
April | 359.67 | 0.63 | 0.61 | 01-APR-06:40 | 927.99 | 0.00 | 0.00 | 353.83 | 580.73 | 0.00 | 0.00 | 311.17 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 1096.68 | 0.00 | 0.00 | 418.00 | 666.15 | 0.00 | 0.00 | 387.50 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-04:00 | 1260.01 | 0.00 | 0.00 | 420.17 | 759.23 | 0.00 | 0.00 | 395.00 |
July | 429.00 | 0.62 | 0.61 | 01-JUL-04:00 | 1168.00 | 0.00 | 0.00 | 431.17 | 714.47 | 0.00 | 0.00 | 403.67 |
August | 396.33 | 0.63 | 0.61 | 01-AUG-05:40 | 938.00 | 0.00 | 0.00 | 384.00 | 598.39 | 0.00 | 0.00 | 346.00 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 749.89 | 0.00 | 0.00 | 313.50 | 497.34 | 0.00 | 0.00 | 261.67 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-07:19 | 637.37 | 0.00 | 0.00 | 241.67 | 402.72 | 0.00 | 0.00 | 145.00 |
November | 171.33 | 0.66 | 0.61 | 01-NOV-11:39 | 469.58 | 0.00 | 0.00 | 153.17 | 289.83 | 0.00 | 0.00 | 50.67 |
December | 131.67 | 0.67 | 0.61 | 02-DEC-09:09 | 395.06 | 0.00 | 0.00 | 96.00 | 246.30 | 0.00 | 0.00 | 11.67 |
Annual Sum or Average | 3515.67 | 0.64 | 874.57 | 0.00 | 0.00 | 3463.00 | 540.21 | 0.00 | 0.00 | 2617.50 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 395.06 | 0.00 | 0.00 | 96.00 | 246.30 | 0.00 | 0.00 | 11.67 | |
Maximum of Months | 429.00 | 0.67 | 0.61 | 1260.01 | 0.00 | 0.00 | 431.17 | 759.23 | 0.00 | 0.00 | 403.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.66 | 0.61 | 01-JAN-09:39 | 1066.02 | 16.93 | 64.50 | 186.83 | 612.03 | 15.97 | 41.50 | 118.33 |
February | 217.00 | 0.65 | 0.61 | 01-FEB-11:39 | 1498.58 | 14.44 | 40.17 | 221.67 | 914.22 | 15.80 | 35.17 | 162.83 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 1542.87 | 15.24 | 53.83 | 291.17 | 884.77 | 15.06 | 34.50 | 230.17 |
April | 359.67 | 0.64 | 0.61 | 01-APR-07:10 | 3035.72 | 15.04 | 73.33 | 343.00 | 1389.57 | 12.89 | 0.00 | 312.83 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 2621.23 | 10.50 | 0.00 | 400.33 | 1535.25 | 12.84 | 1.33 | 367.83 |
June | 410.67 | 0.63 | 0.61 | 01-JUN-05:40 | 3188.33 | 10.86 | 0.00 | 405.00 | 1430.29 | 14.78 | 32.83 | 366.83 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-05:40 | 3147.31 | 10.51 | 0.00 | 414.17 | 1453.37 | 14.55 | 34.50 | 380.00 |
August | 396.33 | 0.64 | 0.61 | 01-AUG-06:10 | 2709.86 | 10.95 | 8.50 | 369.17 | 1591.65 | 13.03 | 5.50 | 335.17 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 2603.90 | 15.66 | 75.33 | 312.67 | 1515.39 | 15.80 | 49.00 | 277.83 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-07:30 | 2027.52 | 16.85 | 65.33 | 254.17 | 951.56 | 16.05 | 36.50 | 190.50 |
November | 171.33 | 0.65 | 0.61 | 01-NOV-11:39 | 1185.77 | 16.64 | 50.50 | 177.67 | 644.07 | 15.93 | 32.83 | 113.00 |
December | 131.67 | 0.66 | 0.61 | 02-DEC-09:09 | 804.65 | 14.67 | 30.17 | 131.17 | 460.24 | 15.09 | 20.50 | 66.50 |
Annual Sum or Average | 3515.67 | 0.64 | 2402.94 | 13.32 | 461.67 | 3507.00 | 1250.42 | 14.53 | 324.17 | 2921.83 | ||
Minimum of Months | 131.67 | 0.63 | 0.61 | 804.65 | 10.50 | 0.00 | 131.17 | 460.24 | 12.84 | 0.00 | 66.50 | |
Maximum of Months | 429.00 | 0.66 | 0.61 | 3188.33 | 16.93 | 75.33 | 414.17 | 1591.65 | 16.05 | 49.00 | 380.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.523563E+10 | 27969.24 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294822E+10 | 23229.70 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115419E+10 | 13948.29 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72261010.16 | 9950.89 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21062068.93 | 6814.16 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 260423.97 | 434.04 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 94765622.37 | 6045.04 | 07-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108470E+10 | 17203.20 | 29-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311344E+10 | 20513.68 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.523563E+10 | 27969.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 39463739.96 | 3022.85 | 12-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39463739.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39463739.96 | 3022.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.341788E+09 | 8838.45 | 10-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174131E+09 | 3451.17 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43222062.96 | 2208.07 | 16-MAR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 115576.27 | 192.63 | 01-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5234912.81 | 711.48 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102141E+09 | 2499.86 | 30-NOV-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.428815E+09 | 8771.06 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.428815E+09 | 8838.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.482995E+09 | 14574.36 | 10-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203707E+09 | 5567.97 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 76546010.04 | 6894.26 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1780519.83 | 1076.53 | 05-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12858815.35 | 1598.27 | 28-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126986E+09 | 14241.54 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.508458E+09 | 14463.47 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.508458E+09 | 14574.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 52509722.32 | 2758.09 | 11-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52509722.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52509722.32 | 2758.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.986239E+11 | 310744.95 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.585030E+11 | 258303.21 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.382046E+11 | 183063.97 | 08-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.481321E+10 | 147691.20 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.986913E+09 | 88343.82 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 827022.07 | 1378.37 | 07-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144130E+09 | 41524.26 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.493019E+10 | 91881.48 | 07-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.340197E+11 | 206910.50 | 29-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.891438E+11 | 241513.14 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.329370E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.986239E+11 | 310744.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 11952658.44 | 8626.86 | 02-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11952658.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11952658.44 | 8626.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.146699E+11 | 107919.60 | 30-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.919267E+10 | 116714.16 | 10-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.380705E+10 | 109684.99 | 16-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123194E+09 | 20898.21 | 01-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22012100.21 | 68564.29 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126591E+10 | 87998.72 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.780523E+10 | 112619.96 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201666E+11 | 109046.37 | 21-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.570525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201666E+11 | 116714.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.211343E+11 | 137735.91 | 11-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150294E+11 | 139715.17 | 24-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106010E+11 | 134404.60 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.588748E+09 | 33039.21 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.398648E+09 | 82985.83 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2620504.25 | 9955.93 | 07-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79916197.85 | 14714.68 | 21-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.555241E+10 | 93779.27 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151827E+11 | 136325.39 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282943E+11 | 136987.18 | 30-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.968639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.282943E+11 | 139715.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168542E+11 | 202595.27 | 10-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109242E+11 | 201887.29 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.945109E+10 | 197926.67 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.766644E+09 | 35710.77 | 11-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101269E+10 | 135852.71 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33090648.17 | 41444.35 | 08-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15121193.34 | 3739.23 | 07-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.382961E+10 | 117519.19 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115324E+11 | 200746.81 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.284922E+11 | 201350.31 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.829113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.284922E+11 | 202595.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181370E+11 | 130731.88 | 11-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112507E+11 | 132581.87 | 24-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.769550E+10 | 112832.06 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.536861E+09 | 25506.53 | 11-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.612656E+09 | 79832.92 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150382E+09 | 18949.94 | 07-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.445765E+10 | 61463.47 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120648E+11 | 129381.28 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246541E+11 | 129770.73 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.795596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246541E+11 | 132581.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136030E+11 | 36253.53 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.936112E+10 | 31895.80 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691456E+10 | 23908.29 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124937E+10 | 20043.67 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.385715E+09 | 13707.77 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6563074.26 | 3531.90 | 08-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66808480.69 | 8229.42 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144958E+10 | 14713.66 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.613668E+10 | 25960.20 | 29-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130468E+11 | 28448.84 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.522202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136030E+11 | 36253.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.335810E+10 | 76985.09 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176919E+10 | 76536.71 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.810185E+09 | 75365.07 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 497040.12 | 828.40 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288538E+09 | 74702.47 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153883E+10 | 76410.62 | 20-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.420423E+10 | 76365.77 | 30-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.420423E+10 | 76985.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.507794E+10 | 12019.60 | 31-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.373498E+10 | 12006.69 | 27-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246573E+10 | 12004.91 | 27-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.484426E+09 | 11919.64 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.289464E+09 | 11952.88 | 05-MAY-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5165312.80 | 4996.85 | 07-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1894915.34 | 2467.99 | 31-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121152E+09 | 11938.97 | 18-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145045E+10 | 11989.13 | 30-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.341504E+10 | 11997.12 | 27-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.601483E+10 | 12007.48 | 18-DEC-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.601483E+10 | 12019.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.444743E+10 | 16237.08 | 11-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336141E+10 | 16149.90 | 18-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.272999E+10 | 15945.92 | 16-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.376000E+09 | 15759.67 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.284239E+09 | 15727.43 | 05-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17730196.15 | 3937.82 | 07-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4285796.91 | 1701.33 | 31-JUL-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4469127.99 | 2211.94 | 23-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121706E+09 | 5547.16 | 18-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165299E+10 | 15834.97 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.342979E+10 | 16025.95 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.532559E+10 | 16101.90 | 30-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4285796.91 | 1701.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.532559E+10 | 16237.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.476442E+10 | 24453.68 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358247E+10 | 24330.98 | 17-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.343547E+10 | 24052.79 | 16-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.694890E+09 | 19782.40 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.719981E+09 | 23723.39 | 05-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106587E+09 | 12163.02 | 08-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 45238264.54 | 3541.40 | 01-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16155589.39 | 1492.82 | 12-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165734E+09 | 5919.97 | 07-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191934E+10 | 23885.75 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.380830E+10 | 24173.39 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.652628E+10 | 24287.83 | 30-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 16155589.39 | 1492.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.652628E+10 | 24453.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.405285E+10 | 16738.84 | 11-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289335E+10 | 16612.31 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239956E+10 | 16415.01 | 16-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.466463E+09 | 11235.68 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.423267E+09 | 16206.99 | 05-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35938446.23 | 2204.27 | 08-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25410511.16 | 1919.71 | 01-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4859728.97 | 628.43 | 24-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195839E+09 | 7142.13 | 07-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160928E+10 | 16109.18 | 23-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.306810E+10 | 16518.05 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.476661E+10 | 16597.73 | 30-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4859728.97 | 628.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.476661E+10 | 16738.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 93.38 | 0.78 | 06-JUL-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 93.38 | 0.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2220.89 | 2220.89 | 0.97 | 02-JAN-08:65 | 0.97 | 0.00 |
February | 0.00 | 0.00 | 223.15 | 223.15 | 0.37 | 04-FEB-14:40 | 0.37 | 0.00 |
March | 0.00 | 0.00 | 3185.11 | 3185.11 | 1.07 | 20-MAR-04:47 | 1.07 | 0.00 |
April | 0.00 | 0.00 | 0.439389E+10 | 0.438864E+10 | 78510.00 | 30-APR-14:52 | 78510.00 | 0.00 |
May | 0.00 | 0.00 | 0.545442E+10 | 0.545442E+10 | 95691.42 | 22-MAY-15:00 | 95691.42 | 0.06 |
June | 0.00 | 0.00 | 0.180485E+11 | 0.176245E+11 | 122967.03 | 13-JUN-16:00 | 111449.02 | 0.21 |
July | 0.00 | 0.00 | 0.304760E+11 | 0.303459E+11 | 116532.32 | 21-JUL-15:20 | 116532.32 | 0.37 |
August | 0.00 | 0.00 | 0.403580E+11 | 0.399995E+11 | 121201.36 | 14-AUG-15:10 | 121201.36 | 0.45 |
September | 0.00 | 0.00 | 0.187667E+11 | 0.187064E+11 | 86544.84 | 13-SEP-14:20 | 86544.84 | 0.21 |
October | 0.00 | 0.00 | 0.982622E+09 | 0.982622E+09 | 24007.20 | 11-OCT-15:00 | 24007.20 | 0.00 |
November | 0.00 | 0.00 | 15664202.89 | 15664202.89 | 9168.98 | 24-NOV-12:00 | 9168.98 | 0.00 |
December | 0.00 | 0.00 | 957.97 | 957.97 | 0.39 | 19-DEC-05:25 | 0.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118496E+12 | 0.117518E+12 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 223.15 | 223.15 | 0.37 | 0.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.403580E+11 | 0.399995E+11 | 122967.03 | 121201.36 | 0.45 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 69830.70 | 69830.70 | 3.96 | 15-JAN-13:58 | 3.96 | 0.01 |
February | 0.00 | 0.00 | 121828.74 | 121828.74 | 2.72 | 04-FEB-14:40 | 2.72 | 0.02 |
March | 0.00 | 0.00 | 144988.29 | 144988.29 | 4.32 | 27-MAR-05:03 | 4.32 | 0.00 |
April | 0.00 | 0.00 | 0.361742E+11 | 0.361463E+11 | 763059.02 | 30-APR-15:21 | 763059.02 | 0.00 |
May | 0.00 | 0.00 | 0.465161E+11 | 0.465161E+11 | 818001.83 | 22-MAY-15:00 | 818001.83 | 0.06 |
June | 0.00 | 0.00 | 0.149868E+12 | 0.146395E+12 | 1121838.73 | 13-JUN-16:00 | 999449.97 | 0.20 |
July | 0.00 | 0.00 | 0.243175E+12 | 0.242560E+12 | 1043395.28 | 21-JUL-15:40 | 1043395.28 | 0.35 |
August | 0.00 | 0.00 | 0.310482E+12 | 0.308623E+12 | 973616.35 | 14-AUG-15:50 | 973616.35 | 0.44 |
September | 0.00 | 0.00 | 0.165378E+12 | 0.164262E+12 | 815248.94 | 13-SEP-14:40 | 815248.94 | 0.22 |
October | 0.00 | 0.00 | 0.818616E+10 | 0.818616E+10 | 201945.47 | 07-OCT-15:00 | 201945.47 | 0.00 |
November | 0.00 | 0.00 | 67609836.05 | 67609836.05 | 47971.86 | 24-NOV-12:00 | 47971.86 | 0.00 |
December | 0.00 | 0.00 | 75855.96 | 75855.96 | 2.33 | 26-DEC-06:03 | 2.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.959847E+12 | 0.952756E+12 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 69830.70 | 69830.70 | 2.33 | 2.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.310482E+12 | 0.308623E+12 | 1121838.73 | 1043395.28 | 0.44 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 230.66 | 230.66 | 0.38 | 01-JAN-20:00 | 0.38 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 53.57 | 53.57 | 0.45 | 06-MAR-05:22 | 0.45 | 0.00 |
April | 0.00 | 0.00 | 0.352872E+10 | 0.352872E+10 | 71566.81 | 30-APR-16:22 | 71566.81 | 0.00 |
May | 0.00 | 0.00 | 0.480583E+10 | 0.480583E+10 | 92073.07 | 22-MAY-15:00 | 92073.07 | 0.06 |
June | 0.00 | 0.00 | 0.157777E+11 | 0.154129E+11 | 133732.80 | 13-JUN-16:00 | 120135.68 | 0.19 |
July | 0.00 | 0.00 | 0.249995E+11 | 0.249498E+11 | 123014.56 | 21-JUL-15:40 | 123014.56 | 0.34 |
August | 0.00 | 0.00 | 0.300505E+11 | 0.299521E+11 | 113610.59 | 14-AUG-16:00 | 113610.59 | 0.43 |
September | 0.00 | 0.00 | 0.151489E+11 | 0.150879E+11 | 84365.75 | 13-SEP-15:20 | 84365.75 | 0.20 |
October | 0.00 | 0.00 | 0.610181E+09 | 0.610181E+09 | 19343.97 | 07-OCT-15:00 | 19343.97 | 0.00 |
November | 0.00 | 0.00 | 5113630.04 | 5113630.04 | 3850.03 | 24-NOV-12:00 | 3850.03 | 0.00 |
December | 0.00 | 0.00 | 29134.00 | 29134.00 | 304.11 | 26-DEC-04:16 | 304.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.949265E+11 | 0.943526E+11 | 0.10 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.300505E+11 | 0.299521E+11 | 133732.80 | 123014.56 | 0.43 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 6327.39 | 6327.39 | 10.55 | 16-FEB-20:30 | 10.55 | 0.00 |
March | 0.00 | 0.00 | 1228608.27 | 608804.95 | 6085.90 | 18-MAR-05:03 | 2765.04 | 0.00 |
April | 0.00 | 0.00 | 0.731211E+09 | 0.731211E+09 | 28596.35 | 28-APR-15:00 | 28596.35 | 0.00 |
May | 0.00 | 0.00 | 0.228274E+10 | 0.228274E+10 | 58418.02 | 22-MAY-15:00 | 58418.02 | 0.04 |
June | 0.00 | 0.00 | 0.822478E+10 | 0.817648E+10 | 61308.29 | 12-JUN-15:00 | 61308.29 | 0.11 |
July | 0.00 | 0.00 | 0.133619E+11 | 0.132611E+11 | 66630.16 | 10-JUL-11:00 | 66630.16 | 0.20 |
August | 0.00 | 0.00 | 0.174902E+11 | 0.174500E+11 | 66280.67 | 14-AUG-16:00 | 66280.67 | 0.29 |
September | 0.00 | 0.00 | 0.849575E+10 | 0.847371E+10 | 49803.60 | 25-SEP-13:00 | 49803.60 | 0.12 |
October | 0.00 | 0.00 | 0.139882E+09 | 0.128104E+09 | 21688.27 | 20-OCT-05:03 | 9307.17 | 0.00 |
November | 0.00 | 0.00 | 13067293.49 | 12084935.21 | 9577.19 | 24-NOV-06:03 | 7906.01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.507407E+11 | 0.505160E+11 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.174902E+11 | 0.174500E+11 | 66630.16 | 66630.16 | 0.29 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.321916E+12 | 0.321897E+12 | 124755.64 | 19-JAN-22:03 | 124755.64 | 0.00 |
February | 0.00 | 0.00 | 0.511826E+12 | 0.511815E+12 | 216247.23 | 23-FEB-22:03 | 216247.23 | 0.00 |
March | 0.00 | 0.00 | 0.813504E+12 | 0.813502E+12 | 394642.49 | 31-MAR-24:00 | 394642.49 | 0.00 |
April | 0.00 | 0.00 | 0.102851E+13 | 0.102851E+13 | 408730.14 | 30-APR-19:43 | 408730.14 | 0.00 |
May | 0.00 | 0.00 | 0.328870E+12 | 0.328362E+12 | 211864.62 | 31-MAY-24:00 | 211864.62 | 0.00 |
June | 0.00 | 0.00 | 0.558980E+12 | 0.556669E+12 | 303254.46 | 30-JUN-24:00 | 303254.46 | 0.00 |
July | 0.00 | 0.00 | 0.825806E+12 | 0.822952E+12 | 395968.72 | 31-JUL-24:00 | 395968.72 | 0.00 |
August | 0.00 | 0.00 | 0.107103E+13 | 0.106831E+13 | 406602.48 | 17-AUG-15:30 | 402133.94 | 0.00 |
September | 0.00 | 0.00 | 0.323323E+12 | 0.321393E+12 | 211359.61 | 30-SEP-24:00 | 211359.61 | 0.00 |
October | 0.00 | 0.00 | 0.573413E+12 | 0.572846E+12 | 303371.48 | 31-OCT-24:00 | 303371.48 | 0.00 |
November | 0.00 | 0.00 | 0.789964E+12 | 0.789647E+12 | 308647.57 | 08-NOV-15:00 | 305390.58 | 0.00 |
December | 0.00 | 0.00 | 0.105922E+13 | 0.105922E+13 | 400199.83 | 26-DEC-22:03 | 400199.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.820636E+13 | 0.819513E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.321916E+12 | 0.321393E+12 | 124755.64 | 124755.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107103E+13 | 0.106831E+13 | 408730.14 | 408730.14 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.421519E+10 | 0.421371E+10 | 2294.96 | 01-JAN-16:10 | 2289.33 | 0.00 |
February | 0.00 | 0.00 | 0.871742E+10 | 0.871620E+10 | 4388.25 | 19-FEB-17:00 | 4388.25 | 0.00 |
March | 0.00 | 0.00 | 0.150688E+11 | 0.150685E+11 | 7606.64 | 31-MAR-24:00 | 7606.64 | 0.00 |
April | 0.00 | 0.00 | 0.200577E+11 | 0.200574E+11 | 8826.48 | 30-APR-18:00 | 8826.48 | 0.00 |
May | 0.00 | 0.00 | 0.541844E+10 | 0.539756E+10 | 3958.79 | 31-MAY-24:00 | 3958.79 | 0.00 |
June | 0.00 | 0.00 | 0.105650E+11 | 0.104750E+11 | 5785.40 | 30-JUN-24:00 | 5785.40 | 0.00 |
July | 0.00 | 0.00 | 0.161411E+11 | 0.160304E+11 | 7860.62 | 31-JUL-24:00 | 7860.62 | 0.00 |
August | 0.00 | 0.00 | 0.211444E+11 | 0.210283E+11 | 8711.61 | 13-AUG-18:04 | 8697.43 | 0.00 |
September | 0.00 | 0.00 | 0.543435E+10 | 0.536492E+10 | 3840.74 | 30-SEP-24:00 | 3840.74 | 0.00 |
October | 0.00 | 0.00 | 0.102447E+11 | 0.102180E+11 | 5661.58 | 31-OCT-24:00 | 5661.58 | 0.00 |
November | 0.00 | 0.00 | 0.145863E+11 | 0.145705E+11 | 6131.88 | 19-NOV-16:10 | 6131.88 | 0.00 |
December | 0.00 | 0.00 | 0.198574E+11 | 0.198573E+11 | 8001.21 | 25-DEC-15:15 | 8001.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151451E+12 | 0.150998E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.421519E+10 | 0.421371E+10 | 2294.96 | 2289.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.211444E+11 | 0.210283E+11 | 8826.48 | 8826.48 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.234357E+11 | 0.234212E+11 | 19216.42 | 19-JAN-16:20 | 19216.42 | 0.00 |
February | 0.00 | 0.00 | 0.686061E+11 | 0.685935E+11 | 39585.19 | 27-FEB-17:00 | 39585.19 | 0.00 |
March | 0.00 | 0.00 | 0.128529E+12 | 0.128526E+12 | 67976.64 | 31-MAR-24:00 | 67976.64 | 0.00 |
April | 0.00 | 0.00 | 0.183693E+12 | 0.183690E+12 | 83106.59 | 30-APR-17:53 | 83106.59 | 0.00 |
May | 0.00 | 0.00 | 0.441855E+11 | 0.439808E+11 | 36134.84 | 31-MAY-24:00 | 36134.84 | 0.00 |
June | 0.00 | 0.00 | 0.958154E+11 | 0.949272E+11 | 52244.09 | 30-JUN-24:00 | 52244.09 | 0.00 |
July | 0.00 | 0.00 | 0.149789E+12 | 0.148693E+12 | 73664.60 | 31-JUL-24:00 | 73664.60 | 0.00 |
August | 0.00 | 0.00 | 0.198157E+12 | 0.197001E+12 | 80802.21 | 13-AUG-18:04 | 80663.22 | 0.00 |
September | 0.00 | 0.00 | 0.451288E+11 | 0.444604E+11 | 33862.33 | 30-SEP-23:40 | 33862.33 | 0.00 |
October | 0.00 | 0.00 | 0.850459E+11 | 0.847820E+11 | 48923.34 | 31-OCT-24:00 | 48923.34 | 0.00 |
November | 0.00 | 0.00 | 0.122176E+12 | 0.122018E+12 | 55885.63 | 10-NOV-16:00 | 55697.69 | 0.00 |
December | 0.00 | 0.00 | 0.167244E+12 | 0.167243E+12 | 70425.90 | 21-DEC-15:20 | 70425.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.131180E+13 | 0.130734E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.234357E+11 | 0.234212E+11 | 19216.42 | 19216.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.198157E+12 | 0.197001E+12 | 83106.59 | 83106.59 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.778681E+09 | 0.777747E+09 | 1814.66 | 19-JAN-16:20 | 1814.66 | 0.00 |
February | 0.00 | 0.00 | 0.511627E+10 | 0.511507E+10 | 3729.17 | 09-FEB-16:50 | 3729.17 | 0.00 |
March | 0.00 | 0.00 | 0.113504E+11 | 0.113501E+11 | 6332.21 | 31-MAR-23:20 | 6332.21 | 0.00 |
April | 0.00 | 0.00 | 0.175621E+11 | 0.175618E+11 | 8444.54 | 30-APR-17:58 | 8444.54 | 0.00 |
May | 0.00 | 0.00 | 0.369028E+10 | 0.366998E+10 | 3449.61 | 31-MAY-23:30 | 3449.61 | 0.00 |
June | 0.00 | 0.00 | 0.922037E+10 | 0.913185E+10 | 4959.34 | 30-JUN-23:30 | 4959.34 | 0.00 |
July | 0.00 | 0.00 | 0.146712E+11 | 0.145619E+11 | 7218.69 | 31-JUL-23:30 | 7218.69 | 0.00 |
August | 0.00 | 0.00 | 0.195166E+11 | 0.194013E+11 | 8148.16 | 13-AUG-18:04 | 8134.22 | 0.00 |
September | 0.00 | 0.00 | 0.388620E+10 | 0.382060E+10 | 2849.16 | 30-SEP-23:20 | 2849.16 | 0.00 |
October | 0.00 | 0.00 | 0.708477E+10 | 0.705899E+10 | 4365.39 | 31-OCT-23:20 | 4365.39 | 0.00 |
November | 0.00 | 0.00 | 0.104944E+11 | 0.104788E+11 | 5518.16 | 10-NOV-16:00 | 5499.48 | 0.00 |
December | 0.00 | 0.00 | 0.146784E+11 | 0.146783E+11 | 6818.81 | 21-DEC-15:20 | 6818.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118050E+12 | 0.117606E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.778681E+09 | 0.777747E+09 | 1814.66 | 1814.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.195166E+11 | 0.194013E+11 | 8444.54 | 8444.54 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 78043.09 | 1033021.05 | 10-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 54479.71 | 1028956.95 | 17-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 33233.05 | 959094.33 | 04-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3889.80 | 229861.80 | 08-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 1905.94 | 624850.06 | 05-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 79.26 | 69964.13 | 08-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.71 | 5104.71 | 01-JUL-05:03 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 9.12 | 3253.48 | 12-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 407.26 | 63786.20 | 21-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10560.29 | 673984.97 | 28-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 39528.93 | 1093834.03 | 27-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 86880.53 | 1053002.48 | 27-DEC-06:02 |
Annual Sum or Average | 0.00 | 25679.57 | ||||
Minimum of Months | 0.00 | 0.00 | 9.12 | 3253.48 | ||
Maximum of Months | 0.00 | 0.00 | 86880.53 | 1093834.03 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 704.09 | 20892.23 | 10-JAN-06:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 1571.42 | 20892.23 | 28-FEB-07:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 1406.10 | 20892.22 | 01-MAR-06:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 34468.24 | 1148120.44 | 28-APR-15:00 | 0.32 | 5464.88 | 29-APR-19:47 |
May | 40244.41 | 1150632.37 | 22-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 117011.95 | 1453474.04 | 13-JUN-16:00 | 2.90 | 29898.79 | 25-JUN-22:22 |
July | 196784.74 | 1351666.91 | 21-JUL-15:40 | 0.46 | 10248.51 | 23-JUL-02:12 |
August | 262115.20 | 1283148.66 | 14-AUG-15:50 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 137024.68 | 1156495.31 | 12-SEP-14:50 | 3.16 | 35130.06 | 25-SEP-03:13 |
October | 8422.90 | 503027.20 | 06-OCT-15:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 602.36 | 117464.61 | 24-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 861.83 | 20981.62 | 26-DEC-04:17 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 67243.66 | 0.56 | ||||
Minimum of Months | 602.36 | 20892.22 | 0.00 | 0.00 | ||
Maximum of Months | 262115.20 | 1453474.04 | 3.16 | 35130.06 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.01 | 149.69 | 18-MAR-05:03 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 21692.70 | 1428013.98 | 30-APR-16:01 | 0.00 | 0.00 | 01-APR-00:10 |
May | 31008.06 | 1272898.11 | 22-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 96605.06 | 1450645.24 | 13-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 153279.25 | 1343351.39 | 21-JUL-15:40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 203272.97 | 1418943.75 | 20-AUG-16:12 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 108153.97 | 1364113.60 | 10-SEP-15:32 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 4794.66 | 319180.12 | 06-OCT-15:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 67.44 | 85606.47 | 24-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.03 | 220.42 | 26-DEC-04:16 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 51941.31 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 203272.97 | 1450645.24 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 167322.76 | 181940.80 | 19-JAN-16:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 309193.43 | 326261.47 | 19-FEB-17:07 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 451306.71 | 591877.38 | 31-MAR-24:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 622450.36 | 1224492.40 | 30-APR-18:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 188193.71 | 576278.74 | 22-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 363755.11 | 957356.82 | 13-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 565811.50 | 1339639.10 | 22-JUL-18:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 765338.78 | 1380289.92 | 14-AUG-17:40 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 209898.20 | 533646.04 | 13-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 318084.05 | 495950.86 | 07-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 450806.46 | 542858.71 | 24-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 584716.42 | 594983.94 | 21-DEC-22:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 417338.94 | 0.00 | ||||
Minimum of Months | 167322.76 | 181940.80 | 0.00 | 0.00 | ||
Maximum of Months | 765338.78 | 1380289.92 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15876.92 | 53232.79 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16061.89 | 53329.35 | 10-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16868.28 | 53226.72 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15620.14 | 52450.37 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15705.44 | 51325.51 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15652.49 | 49895.65 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14244.88 | 48625.78 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 15346.27 | 47980.49 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14578.20 | 48624.64 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14840.35 | 49885.93 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15410.52 | 51285.88 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15262.84 | 52482.71 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 15452.24 | ||||
Minimum of Months | 0.00 | 0.00 | 14244.88 | 47980.49 | ||
Maximum of Months | 0.00 | 0.00 | 16868.28 | 53329.35 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 22.58 | 22580.45 | 31-JAN-06:50 | 916.52 | 102043.89 | 25-JAN-06:50 |
February | 57.46 | 21570.23 | 23-FEB-06:40 | 2098.05 | 110647.46 | 24-FEB-06:30 |
March | 76.74 | 21385.20 | 21-MAR-05:40 | 1898.13 | 100995.89 | 07-MAR-07:00 |
April | 20955.01 | 1353399.83 | 28-APR-15:00 | 1078.53 | 89767.86 | 17-APR-05:30 |
May | 28376.57 | 1858406.90 | 22-MAY-15:00 | 465.64 | 79162.73 | 10-MAY-05:50 |
June | 98802.38 | 2221463.44 | 13-JUN-16:00 | 507.90 | 75600.65 | 08-JUN-05:40 |
July | 148893.46 | 2002952.40 | 21-JUL-13:20 | 620.27 | 74515.25 | 03-JUL-05:30 |
August | 187358.36 | 1957904.17 | 28-AUG-15:20 | 438.31 | 66376.49 | 30-AUG-05:50 |
September | 103201.77 | 1835749.69 | 13-SEP-12:50 | 610.15 | 77505.09 | 29-SEP-05:30 |
October | 4699.56 | 304634.24 | 06-OCT-15:30 | 405.99 | 86981.36 | 03-OCT-05:30 |
November | 21.57 | 30322.92 | 24-NOV-11:50 | 746.87 | 115512.68 | 17-NOV-06:50 |
December | 30.37 | 22332.30 | 18-DEC-06:40 | 1153.21 | 117393.49 | 31-DEC-07:00 |
Annual Sum or Average | 49710.18 | 903.80 | ||||
Minimum of Months | 21.57 | 21385.20 | 405.99 | 66376.49 | ||
Maximum of Months | 187358.36 | 2221463.44 | 2098.05 | 117393.49 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148609E+11 | 0.80 | 9701.57 | 01-JAN-00:20 | 1.41 |
February | 0.131214E+11 | 0.78 | 9701.57 | 01-FEB-05:03 | 1.40 |
March | 0.155410E+11 | 0.84 | 9701.57 | 01-MAR-05:03 | 1.40 |
April | 0.146431E+11 | 0.82 | 9701.57 | 01-APR-03:30 | 1.41 |
May | 0.154701E+11 | 0.83 | 9701.57 | 01-MAY-00:03 | 1.40 |
June | 0.152606E+11 | 0.85 | 9701.57 | 01-JUN-03:02 | 1.40 |
July | 0.149608E+11 | 0.80 | 9701.57 | 01-JUL-03:10 | 1.40 |
August | 0.163774E+11 | 0.88 | 9701.57 | 01-AUG-03:02 | 1.40 |
September | 0.150113E+11 | 0.83 | 9701.57 | 01-SEP-03:02 | 1.40 |
October | 0.152276E+11 | 0.82 | 9701.57 | 02-OCT-03:02 | 1.40 |
November | 0.146571E+11 | 0.82 | 9701.57 | 01-NOV-03:10 | 1.40 |
December | 0.146106E+11 | 0.79 | 9701.57 | 01-DEC-05:01 | 1.40 |
Annual Sum or Average | 0.179742E+12 | 0.82 | |||
Minimum of Months | 0.131214E+11 | 0.78 | 9701.57 | 1.40 | |
Maximum of Months | 0.163774E+11 | 0.88 | 9701.57 | 1.41 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.479782E+10 | 0.33 | 13012.36 | 10-JAN-06:01 | 1.36 |
February | 0.489540E+10 | 0.36 | 10790.67 | 01-FEB-06:02 | 1.20 |
March | 0.638495E+10 | 0.40 | 11465.78 | 25-MAR-05:02 | 1.25 |
April | 0.983017E+10 | 0.53 | 17362.42 | 28-APR-14:30 | 1.61 |
May | 0.790648E+10 | 0.45 | 13435.96 | 22-MAY-15:20 | 1.37 |
June | 0.985444E+10 | 0.53 | 17272.16 | 13-JUN-05:03 | 1.61 |
July | 0.113224E+11 | 0.57 | 18500.47 | 24-JUL-05:03 | 1.68 |
August | 0.132557E+11 | 0.64 | 19122.08 | 14-AUG-14:50 | 1.71 |
September | 0.856843E+10 | 0.48 | 14816.37 | 11-SEP-14:40 | 1.45 |
October | 0.678013E+10 | 0.40 | 12216.58 | 03-OCT-14:30 | 1.30 |
November | 0.588208E+10 | 0.38 | 12057.41 | 27-NOV-06:01 | 1.29 |
December | 0.556296E+10 | 0.36 | 13012.36 | 30-DEC-06:01 | 1.36 |
Annual Sum or Average | 0.950409E+11 | 0.45 | |||
Minimum of Months | 0.479782E+10 | 0.33 | 10790.67 | 1.20 | |
Maximum of Months | 0.132557E+11 | 0.64 | 19122.08 | 1.71 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.369395E+11 | 0.32 | 113960.16 | 21-JAN-06:03 | 1.34 |
February | 0.352018E+11 | 0.33 | 143066.01 | 24-FEB-06:02 | 1.54 |
March | 0.422958E+11 | 0.35 | 117771.36 | 16-MAR-05:02 | 1.37 |
April | 0.602700E+11 | 0.41 | 140688.50 | 28-APR-15:20 | 1.52 |
May | 0.629850E+11 | 0.42 | 118621.68 | 23-MAY-15:20 | 1.36 |
June | 0.747340E+11 | 0.48 | 145697.56 | 13-JUN-15:30 | 1.55 |
July | 0.790210E+11 | 0.47 | 144115.59 | 21-JUL-15:40 | 1.54 |
August | 0.881860E+11 | 0.52 | 135890.20 | 14-AUG-15:30 | 1.48 |
September | 0.711998E+11 | 0.46 | 144123.34 | 12-SEP-15:20 | 1.54 |
October | 0.484420E+11 | 0.35 | 115281.74 | 21-OCT-05:03 | 1.35 |
November | 0.376143E+11 | 0.32 | 129249.14 | 03-NOV-05:03 | 1.45 |
December | 0.348742E+11 | 0.31 | 84632.45 | 22-DEC-06:03 | 1.12 |
Annual Sum or Average | 0.671763E+12 | 0.40 | |||
Minimum of Months | 0.348742E+11 | 0.31 | 84632.45 | 1.12 | |
Maximum of Months | 0.881860E+11 | 0.52 | 145697.56 | 1.55 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.349976E+10 | 0.32 | 4538.52 | 02-JAN-04:11 | 0.73 |
February | 0.307684E+10 | 0.31 | 4538.52 | 06-FEB-05:01 | 0.73 |
March | 0.349471E+10 | 0.31 | 4538.52 | 06-MAR-05:01 | 0.73 |
April | 0.452567E+10 | 0.34 | 14046.80 | 28-APR-15:20 | 1.42 |
May | 0.500499E+10 | 0.35 | 13289.46 | 23-MAY-15:20 | 1.37 |
June | 0.637950E+10 | 0.41 | 16825.11 | 13-JUN-15:30 | 1.58 |
July | 0.690454E+10 | 0.41 | 15824.60 | 21-JUL-15:40 | 1.53 |
August | 0.733630E+10 | 0.43 | 14519.19 | 14-AUG-15:40 | 1.45 |
September | 0.542882E+10 | 0.37 | 14014.06 | 12-SEP-15:10 | 1.41 |
October | 0.351733E+10 | 0.30 | 6622.78 | 03-OCT-15:20 | 0.90 |
November | 0.321027E+10 | 0.30 | 4538.52 | 13-NOV-05:01 | 0.73 |
December | 0.361591E+10 | 0.33 | 4538.52 | 04-DEC-05:11 | 0.73 |
Annual Sum or Average | 0.559946E+11 | 0.35 | |||
Minimum of Months | 0.307684E+10 | 0.30 | 4538.52 | 0.73 | |
Maximum of Months | 0.733630E+10 | 0.43 | 16825.11 | 1.58 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.958232E+11 | 1.37 | 35776.29 | 01-JAN-00:10 | 1.36 |
February | 0.865500E+11 | 1.37 | 35776.29 | 01-FEB-00:10 | 1.37 |
March | 0.958232E+11 | 1.37 | 35776.29 | 01-MAR-00:10 | 1.37 |
April | 0.927322E+11 | 1.37 | 35776.29 | 01-APR-00:10 | 1.37 |
May | 0.958232E+11 | 1.37 | 35776.29 | 01-MAY-00:03 | 1.37 |
June | 0.927322E+11 | 1.36 | 35776.29 | 01-JUN-00:10 | 1.36 |
July | 0.958232E+11 | 1.36 | 35776.29 | 01-JUL-00:10 | 1.37 |
August | 0.958232E+11 | 1.36 | 35776.29 | 01-AUG-00:02 | 1.37 |
September | 0.927322E+11 | 1.36 | 35776.29 | 01-SEP-00:10 | 1.37 |
October | 0.958232E+11 | 1.37 | 35776.29 | 01-OCT-00:10 | 1.37 |
November | 0.927322E+11 | 1.37 | 35776.29 | 01-NOV-00:10 | 1.37 |
December | 0.958232E+11 | 1.37 | 35776.29 | 01-DEC-00:10 | 1.37 |
Annual Sum or Average | 0.112824E+13 | 1.37 | |||
Minimum of Months | 0.865500E+11 | 1.36 | 35776.29 | 1.36 | |
Maximum of Months | 0.958232E+11 | 1.37 | 35776.29 | 1.37 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152288E+10 | 0.93 | 568.58 | 01-JAN-00:05 | 0.92 |
February | 0.137550E+10 | 0.93 | 568.58 | 01-FEB-00:10 | 0.93 |
March | 0.152288E+10 | 0.93 | 568.58 | 01-MAR-00:10 | 0.92 |
April | 0.147375E+10 | 0.93 | 568.58 | 01-APR-00:10 | 0.93 |
May | 0.152288E+10 | 0.92 | 568.58 | 01-MAY-00:03 | 0.92 |
June | 0.147375E+10 | 0.92 | 568.58 | 01-JUN-00:10 | 0.92 |
July | 0.152288E+10 | 0.92 | 568.58 | 01-JUL-00:10 | 0.92 |
August | 0.152288E+10 | 0.92 | 568.58 | 01-AUG-00:02 | 0.92 |
September | 0.147375E+10 | 0.92 | 568.58 | 01-SEP-00:10 | 0.92 |
October | 0.152288E+10 | 0.92 | 568.58 | 01-OCT-00:10 | 0.93 |
November | 0.147375E+10 | 0.92 | 568.58 | 01-NOV-00:10 | 0.93 |
December | 0.152288E+10 | 0.93 | 568.58 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.179306E+11 | 0.92 | |||
Minimum of Months | 0.137550E+10 | 0.92 | 568.58 | 0.92 | |
Maximum of Months | 0.152288E+10 | 0.93 | 568.58 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145669E+11 | 0.93 | 5438.67 | 01-JAN-00:05 | 0.92 |
February | 0.131572E+11 | 0.93 | 5438.67 | 01-FEB-00:10 | 0.93 |
March | 0.145669E+11 | 0.93 | 5438.67 | 01-MAR-00:10 | 0.92 |
April | 0.140970E+11 | 0.93 | 5438.67 | 01-APR-00:10 | 0.93 |
May | 0.145669E+11 | 0.92 | 5438.67 | 01-MAY-00:03 | 0.92 |
June | 0.140970E+11 | 0.92 | 5438.67 | 01-JUN-00:10 | 0.92 |
July | 0.145669E+11 | 0.92 | 5438.67 | 01-JUL-00:10 | 0.92 |
August | 0.145669E+11 | 0.92 | 5438.67 | 01-AUG-00:02 | 0.92 |
September | 0.140970E+11 | 0.92 | 5438.67 | 01-SEP-00:10 | 0.92 |
October | 0.145669E+11 | 0.92 | 5438.67 | 01-OCT-00:10 | 0.93 |
November | 0.140970E+11 | 0.92 | 5438.67 | 01-NOV-00:10 | 0.93 |
December | 0.145669E+11 | 0.93 | 5438.67 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.171514E+12 | 0.92 | |||
Minimum of Months | 0.131572E+11 | 0.92 | 5438.67 | 0.92 | |
Maximum of Months | 0.145669E+11 | 0.93 | 5438.67 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147699E+10 | 0.93 | 551.45 | 01-JAN-00:05 | 0.92 |
February | 0.133406E+10 | 0.93 | 551.45 | 01-FEB-00:10 | 0.93 |
March | 0.147699E+10 | 0.93 | 551.45 | 01-MAR-00:10 | 0.92 |
April | 0.142935E+10 | 0.93 | 551.45 | 01-APR-00:10 | 0.93 |
May | 0.147699E+10 | 0.92 | 551.45 | 01-MAY-00:03 | 0.92 |
June | 0.142935E+10 | 0.92 | 551.45 | 01-JUN-00:10 | 0.92 |
July | 0.147699E+10 | 0.92 | 551.45 | 01-JUL-00:10 | 0.92 |
August | 0.147699E+10 | 0.92 | 551.45 | 01-AUG-00:02 | 0.92 |
September | 0.142935E+10 | 0.92 | 551.45 | 01-SEP-00:10 | 0.92 |
October | 0.147699E+10 | 0.92 | 551.45 | 01-OCT-00:10 | 0.93 |
November | 0.142935E+10 | 0.92 | 551.45 | 01-NOV-00:10 | 0.93 |
December | 0.147699E+10 | 0.93 | 551.45 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.173904E+11 | 0.92 | |||
Minimum of Months | 0.133406E+10 | 0.92 | 551.45 | 0.92 | |
Maximum of Months | 0.147699E+10 | 0.93 | 551.45 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.867631E+09 | 0.780868E+09 | 3355.15 | 10-JAN-06:01 | 3019.63 | 3019.63 | 39.61 | 5.49 |
February | 0.542439E+09 | 0.488195E+09 | 3323.89 | 27-FEB-06:01 | 2991.50 | 2991.50 | 36.84 | 5.40 |
March | 0.361945E+09 | 0.325751E+09 | 3241.19 | 06-MAR-06:01 | 2917.07 | 2917.07 | 37.06 | 5.14 |
April | 41151942.14 | 37036747.93 | 890.82 | 08-APR-06:05 | 801.74 | 801.74 | 25.22 | 0.99 |
May | 20674197.57 | 18606777.81 | 2255.46 | 05-MAY-05:03 | 2029.91 | 2029.91 | 29.45 | 2.95 |
June | 812374.58 | 731137.12 | 269.77 | 08-JUN-05:03 | 242.79 | 242.79 | 20.64 | 0.28 |
July | 293137.93 | 263824.13 | 20.21 | 01-JUL-05:03 | 18.19 | 18.19 | 20.28 | 0.02 |
August | 95971.57 | 86374.41 | 12.80 | 12-AUG-05:10 | 11.52 | 11.52 | 19.88 | 0.01 |
September | 4148532.52 | 3733679.27 | 246.80 | 21-SEP-06:10 | 222.12 | 222.12 | 20.86 | 0.26 |
October | 0.114426E+09 | 0.102984E+09 | 2342.14 | 28-OCT-05:02 | 2107.92 | 2107.92 | 28.05 | 3.11 |
November | 0.419869E+09 | 0.377882E+09 | 3348.77 | 27-NOV-06:01 | 3013.89 | 3013.89 | 37.46 | 5.47 |
December | 0.957539E+09 | 0.861785E+09 | 3358.01 | 30-DEC-06:01 | 3022.21 | 3022.21 | 39.90 | 5.50 |
Annual Sum or Average | 0.333103E+10 | 0.299792E+10 | ||||||
Minimum of Months | 95971.57 | 86374.41 | 12.80 | 11.52 | 11.52 | 19.88 | 0.01 | |
Maximum of Months | 0.957539E+09 | 0.861785E+09 | 3358.01 | 3022.21 | 3022.21 | 39.90 | 5.50 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 10.94 | 9.85 | 0.00 | 28-JAN-13:20 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 18.82 | 16.94 | 0.00 | 16-FEB-20:30 | 0.00 | 0.00 | 6.70 | 0.00 |
March | 711.56 | 640.40 | 3.47 | 18-MAR-05:03 | 3.12 | 3.12 | 6.73 | 0.70 |
April | 31587790.93 | 28429011.84 | 6981.32 | 28-APR-15:00 | 6283.19 | 6283.19 | 8.01 | 57.42 |
May | 0.110887E+09 | 99797864.43 | 4536.27 | 22-MAY-16:00 | 4082.64 | 4082.64 | 7.27 | 48.03 |
June | 0.329065E+09 | 0.296159E+09 | 6648.02 | 20-JUN-15:00 | 5983.21 | 5983.21 | 7.61 | 56.28 |
July | 0.472453E+09 | 0.425207E+09 | 5258.45 | 06-JUL-14:00 | 4732.61 | 4732.61 | 7.88 | 51.09 |
August | 0.626402E+09 | 0.563762E+09 | 6591.16 | 21-AUG-12:10 | 5932.04 | 5932.04 | 7.50 | 56.08 |
September | 0.300362E+09 | 0.270326E+09 | 3708.97 | 12-SEP-15:10 | 3338.08 | 3338.08 | 7.68 | 44.12 |
October | 3398588.23 | 3058729.41 | 116.90 | 06-OCT-15:30 | 105.21 | 105.21 | 8.89 | 8.33 |
November | 79922.36 | 71930.12 | 41.75 | 24-NOV-12:00 | 37.58 | 37.58 | 8.47 | 4.52 |
December | 16.29 | 14.67 | 0.05 | 26-DEC-04:16 | 0.04 | 0.04 | 8.47 | 0.01 |
Annual Sum or Average | 0.187424E+10 | 0.168681E+10 | ||||||
Minimum of Months | 10.94 | 9.85 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.626402E+09 | 0.563762E+09 | 6981.32 | 6283.19 | 6283.19 | 8.89 | 57.42 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.105610E+10 | 0.950494E+09 | 11698.65 | 01-JAN-20:00 | 10528.78 | 10528.78 | 8.43 | 81.99 |
February | 0.212892E+10 | 0.191603E+10 | 11698.65 | 01-FEB-15:00 | 10528.78 | 10528.78 | 8.43 | 81.99 |
March | 0.211020E+10 | 0.189918E+10 | 11698.65 | 01-MAR-06:03 | 10528.78 | 10528.78 | 8.43 | 81.99 |
April | 0.348690E+10 | 0.313821E+10 | 11698.65 | 01-APR-12:10 | 10528.78 | 10528.78 | 8.43 | 81.99 |
May | 0.336465E+10 | 0.302818E+10 | 11698.65 | 01-MAY-04:12 | 10528.78 | 10528.78 | 8.47 | 81.99 |
June | 0.793964E+10 | 0.714568E+10 | 11698.65 | 01-JUN-04:03 | 10528.78 | 10528.78 | 8.45 | 81.99 |
July | 0.138826E+11 | 0.124943E+11 | 11698.65 | 01-JUL-03:12 | 10528.78 | 10528.78 | 8.49 | 81.99 |
August | 0.168016E+11 | 0.151214E+11 | 11698.65 | 01-AUG-03:02 | 10528.78 | 10528.78 | 8.71 | 81.99 |
September | 0.100835E+11 | 0.907518E+10 | 11698.65 | 01-SEP-03:02 | 10528.78 | 10528.78 | 8.57 | 81.99 |
October | 0.151621E+10 | 0.136459E+10 | 11698.65 | 01-OCT-15:28 | 10528.78 | 10528.78 | 8.43 | 81.99 |
November | 0.761582E+09 | 0.685424E+09 | 11698.65 | 03-NOV-05:40 | 10528.78 | 10528.78 | 8.43 | 81.99 |
December | 0.129262E+10 | 0.116336E+10 | 11698.65 | 01-DEC-16:40 | 10528.78 | 10528.78 | 8.43 | 81.99 |
Annual Sum or Average | 0.644245E+11 | 0.579821E+11 | ||||||
Minimum of Months | 0.761582E+09 | 0.685424E+09 | 11698.65 | 10528.78 | 10528.78 | 8.43 | 81.99 | |
Maximum of Months | 0.168016E+11 | 0.151214E+11 | 11698.65 | 10528.78 | 10528.78 | 8.71 | 81.99 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.902326E+10 | 0.812094E+10 | 3368.90 | 01-JAN-00:05 | 3032.01 | 3032.01 | 21.67 | 14.07 |
February | 0.815004E+10 | 0.733504E+10 | 3368.90 | 01-FEB-00:10 | 3032.01 | 3032.01 | 24.31 | 14.07 |
March | 0.902326E+10 | 0.812094E+10 | 3368.90 | 01-MAR-00:10 | 3032.01 | 3032.01 | 27.18 | 14.07 |
April | 0.873219E+10 | 0.785897E+10 | 3368.90 | 01-APR-00:10 | 3032.01 | 3032.01 | 30.34 | 14.07 |
May | 0.902326E+10 | 0.812094E+10 | 3368.90 | 01-MAY-00:03 | 3032.01 | 3032.01 | 22.61 | 14.07 |
June | 0.873219E+10 | 0.785897E+10 | 3368.90 | 01-JUN-00:10 | 3032.01 | 3032.01 | 24.86 | 14.07 |
July | 0.902326E+10 | 0.812094E+10 | 3368.90 | 01-JUL-00:10 | 3032.01 | 3032.01 | 27.59 | 14.07 |
August | 0.902326E+10 | 0.812094E+10 | 3368.90 | 01-AUG-00:02 | 3032.01 | 3032.01 | 30.49 | 14.07 |
September | 0.873219E+10 | 0.785897E+10 | 3368.90 | 01-SEP-00:10 | 3032.01 | 3032.01 | 22.52 | 14.07 |
October | 0.902326E+10 | 0.812094E+10 | 3368.90 | 01-OCT-00:10 | 3032.01 | 3032.01 | 24.80 | 14.07 |
November | 0.873219E+10 | 0.785897E+10 | 3368.90 | 01-NOV-00:10 | 3032.01 | 3032.01 | 27.53 | 14.07 |
December | 0.902326E+10 | 0.812094E+10 | 3368.90 | 01-DEC-00:10 | 3032.01 | 3032.01 | 29.93 | 14.07 |
Annual Sum or Average | 0.106242E+12 | 0.956175E+11 | ||||||
Minimum of Months | 0.815004E+10 | 0.733504E+10 | 3368.90 | 3032.01 | 3032.01 | 21.67 | 14.07 | |
Maximum of Months | 0.902326E+10 | 0.812094E+10 | 3368.90 | 3032.01 | 3032.01 | 30.49 | 14.07 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 55.42 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:02 | 1.79 | 1.79 | 55.82 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 56.34 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 55.28 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 55.78 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 56.41 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 56.67 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 56.19 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.27 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 55.44 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:02 | 1.79 | 1.79 | 56.73 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:02 | 1.79 | 1.79 | 56.51 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.28 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 56.73 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.133857E+10 | 0.120471E+10 | 14830.06 | 31-JAN-06:50 | 13347.05 | 13347.05 | 21.21 | 49.40 |
February | 0.269831E+10 | 0.242848E+10 | 14830.00 | 23-FEB-06:40 | 13347.00 | 13347.00 | 21.20 | 49.40 |
March | 0.267458E+10 | 0.240713E+10 | 14830.00 | 21-MAR-05:40 | 13347.00 | 13347.00 | 21.20 | 49.40 |
April | 0.443813E+10 | 0.399432E+10 | 29727.91 | 28-APR-15:00 | 26755.12 | 26755.12 | 24.38 | 98.80 |
May | 0.449125E+10 | 0.404212E+10 | 29756.17 | 22-MAY-15:00 | 26780.55 | 26780.55 | 25.60 | 98.80 |
June | 0.111420E+11 | 0.100278E+11 | 29778.11 | 13-JUN-16:00 | 26800.30 | 26800.30 | 26.48 | 98.80 |
July | 0.188501E+11 | 0.169651E+11 | 29764.90 | 21-JUL-13:20 | 26788.41 | 26788.41 | 25.95 | 98.80 |
August | 0.224620E+11 | 0.202158E+11 | 29762.18 | 28-AUG-15:20 | 26785.96 | 26785.96 | 25.84 | 98.80 |
September | 0.135736E+11 | 0.122163E+11 | 29754.80 | 13-SEP-12:50 | 26779.32 | 26779.32 | 25.55 | 98.80 |
October | 0.192250E+10 | 0.173025E+10 | 14844.63 | 06-OCT-15:30 | 13360.17 | 13360.17 | 22.58 | 49.40 |
November | 0.965264E+09 | 0.868737E+09 | 14830.46 | 24-NOV-11:50 | 13347.41 | 13347.41 | 21.25 | 49.40 |
December | 0.163833E+10 | 0.147450E+10 | 14830.04 | 18-DEC-06:40 | 13347.04 | 13347.04 | 21.21 | 49.40 |
Annual Sum or Average | 0.861947E+11 | 0.775752E+11 | ||||||
Minimum of Months | 0.965264E+09 | 0.868737E+09 | 14830.00 | 13347.00 | 13347.00 | 21.20 | 49.40 | |
Maximum of Months | 0.224620E+11 | 0.202158E+11 | 29778.11 | 26800.30 | 26800.30 | 26.48 | 98.80 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 30.51 | 30.51 | 78043.09 | 1033021.05 | 10-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 23.11 | 23.11 | 54479.71 | 1028956.95 | 17-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.13 | 25.13 | 33233.05 | 959094.33 | 04-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.13 | 23.13 | 3889.80 | 229861.80 | 08-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.53 | 22.53 | 1905.94 | 624850.06 | 05-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.60 | 20.60 | 79.26 | 69964.13 | 08-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.28 | 20.28 | 27.71 | 5104.71 | 01-JUL-05:03 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 19.88 | 19.88 | 9.12 | 3253.48 | 12-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.70 | 19.70 | 407.26 | 63786.20 | 21-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20.24 | 20.24 | 10560.29 | 673984.97 | 28-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.19 | 21.19 | 39528.93 | 1093834.03 | 27-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25.99 | 25.99 | 86880.53 | 1053002.48 | 27-DEC-06:02 |
Annual Sum or Average | 0.00 | 25679.57 | ||||||
Minimum of Months | 0.00 | 0.00 | 19.70 | 19.70 | 9.12 | 3253.48 | ||
Maximum of Months | 0.00 | 0.00 | 30.51 | 30.51 | 86880.53 | 1093834.03 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 704.09 | 20892.23 | 10-JAN-06:00 | 8.43 | 8.40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 1571.42 | 20892.23 | 28-FEB-07:00 | 8.43 | 8.40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 1406.10 | 20892.22 | 01-MAR-06:40 | 8.43 | 8.40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 34468.24 | 1148120.44 | 28-APR-15:00 | 11.04 | 7.69 | 0.32 | 5464.88 | 29-APR-19:47 |
May | 40244.41 | 1150632.37 | 22-MAY-16:00 | 10.61 | 7.26 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 117011.95 | 1453474.04 | 13-JUN-16:00 | 10.96 | 6.73 | 2.90 | 29898.79 | 25-JUN-22:22 |
July | 196784.74 | 1351666.91 | 21-JUL-15:40 | 10.63 | 6.70 | 0.46 | 10248.51 | 23-JUL-02:12 |
August | 262115.20 | 1283148.66 | 14-AUG-15:50 | 10.57 | 6.83 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 137024.68 | 1156495.31 | 12-SEP-14:50 | 10.80 | 7.43 | 3.16 | 35130.06 | 25-SEP-03:13 |
October | 8422.90 | 503027.20 | 06-OCT-15:30 | 9.62 | 8.89 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 602.36 | 117464.61 | 24-NOV-12:00 | 8.65 | 8.48 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 861.83 | 20981.62 | 26-DEC-04:17 | 8.43 | 8.40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 67243.66 | 0.56 | ||||||
Minimum of Months | 602.36 | 20892.22 | 8.43 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 262115.20 | 1453474.04 | 11.04 | 8.89 | 3.16 | 35130.06 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.70 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.01 | 149.69 | 18-MAR-05:03 | 6.75 | 8.39 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 21692.70 | 1428013.98 | 30-APR-16:01 | 17.31 | 7.73 | 0.00 | 0.00 | 01-APR-00:10 |
May | 31008.06 | 1272898.11 | 22-MAY-16:00 | 13.03 | 8.51 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 96605.06 | 1450645.24 | 13-JUN-16:00 | 14.73 | 6.73 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 153279.25 | 1343351.39 | 21-JUL-15:40 | 14.22 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 203272.97 | 1418943.75 | 20-AUG-16:12 | 14.16 | 7.88 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 108153.97 | 1364113.60 | 10-SEP-15:32 | 14.64 | 8.21 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 4794.66 | 319180.12 | 06-OCT-15:30 | 15.86 | 8.89 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 67.44 | 85606.47 | 24-NOV-12:00 | 11.22 | 8.48 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.03 | 220.42 | 26-DEC-04:16 | 11.52 | 8.40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 51941.31 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 6.70 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 203272.97 | 1450645.24 | 17.31 | 8.89 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 167322.76 | 181940.80 | 19-JAN-16:10 | 22.05 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 309193.43 | 326261.47 | 19-FEB-17:07 | 24.98 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 451306.71 | 591877.38 | 31-MAR-24:00 | 30.34 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 622450.36 | 1224492.40 | 30-APR-18:00 | 42.88 | 29.71 | 0.00 | 0.00 | 01-APR-00:10 |
May | 188193.71 | 576278.74 | 22-MAY-15:00 | 30.03 | 25.80 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 363755.11 | 957356.82 | 13-JUN-17:00 | 37.62 | 30.20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 565811.50 | 1339639.10 | 22-JUL-18:00 | 45.13 | 34.59 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 765338.78 | 1380289.92 | 14-AUG-17:40 | 45.92 | 32.75 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 209898.20 | 533646.04 | 13-SEP-16:00 | 29.17 | 24.84 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 318084.05 | 495950.86 | 07-OCT-15:00 | 28.41 | 21.80 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 450806.46 | 542858.71 | 24-NOV-12:00 | 29.35 | 19.98 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 584716.42 | 594983.94 | 21-DEC-22:10 | 30.40 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 417338.94 | 0.00 | ||||||
Minimum of Months | 167322.76 | 181940.80 | 22.05 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 765338.78 | 1380289.92 | 45.92 | 34.59 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.12 | 57.12 | 15876.92 | 53232.79 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.43 | 56.43 | 16061.89 | 53329.35 | 10-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.76 | 56.76 | 16868.28 | 53226.72 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.94 | 55.94 | 15620.14 | 52450.37 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 56.64 | 56.64 | 15705.44 | 51325.51 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.61 | 56.61 | 15652.49 | 49895.65 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.21 | 57.21 | 14244.88 | 48625.78 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 56.79 | 56.79 | 15346.27 | 47980.49 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.82 | 56.82 | 14578.20 | 48624.64 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.55 | 56.55 | 14840.35 | 49885.93 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.19 | 57.19 | 15410.52 | 51285.88 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.04 | 57.04 | 15262.84 | 52482.71 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 15452.24 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.94 | 55.94 | 14244.88 | 47980.49 | ||
Maximum of Months | 0.00 | 0.00 | 57.21 | 57.21 | 16868.28 | 53329.35 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 22.58 | 22580.45 | 31-JAN-06:50 | 21.21 | 20.31 | 916.52 | 102043.89 | 25-JAN-06:50 |
February | 57.46 | 21570.23 | 23-FEB-06:40 | 21.20 | 20.35 | 2098.05 | 110647.46 | 24-FEB-06:30 |
March | 76.74 | 21385.20 | 21-MAR-05:40 | 21.20 | 20.31 | 1898.13 | 100995.89 | 07-MAR-07:00 |
April | 20955.01 | 1353399.83 | 28-APR-15:00 | 24.38 | 22.71 | 1078.53 | 89767.86 | 17-APR-05:30 |
May | 28376.57 | 1858406.90 | 22-MAY-15:00 | 25.60 | 21.35 | 465.64 | 79162.73 | 10-MAY-05:50 |
June | 98802.38 | 2221463.44 | 13-JUN-16:00 | 26.48 | 22.41 | 507.90 | 75600.65 | 08-JUN-05:40 |
July | 148893.46 | 2002952.40 | 21-JUL-13:20 | 25.95 | 21.64 | 620.27 | 74515.25 | 03-JUL-05:30 |
August | 187358.36 | 1957904.17 | 28-AUG-15:20 | 25.84 | 21.30 | 438.31 | 66376.49 | 30-AUG-05:50 |
September | 103201.77 | 1835749.69 | 13-SEP-12:50 | 25.55 | 21.21 | 610.15 | 77505.09 | 29-SEP-05:30 |
October | 4699.56 | 304634.24 | 06-OCT-15:30 | 22.58 | 21.10 | 405.99 | 86981.36 | 03-OCT-05:30 |
November | 21.57 | 30322.92 | 24-NOV-11:50 | 21.25 | 20.79 | 746.87 | 115512.68 | 17-NOV-06:50 |
December | 30.37 | 22332.30 | 18-DEC-06:40 | 21.21 | 20.32 | 1153.21 | 117393.49 | 31-DEC-07:00 |
Annual Sum or Average | 49710.18 | 903.80 | ||||||
Minimum of Months | 21.57 | 21385.20 | 21.20 | 20.31 | 405.99 | 66376.49 | ||
Maximum of Months | 187358.36 | 2221463.44 | 26.48 | 22.71 | 2098.05 | 117393.49 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.615239E+10 | 0.00 | 2220.89 | 0.479782E+10 | 0.00 | 0.00 |
February | 0.332606E+10 | 0.00 | 223.15 | 0.489540E+10 | 0.00 | 0.00 |
March | 0.127396E+10 | 0.00 | 3185.11 | 0.638495E+10 | 0.00 | 0.00 |
April | 72376586.43 | 0.00 | 0.439389E+10 | 0.983017E+10 | 0.00 | 0.00 |
May | 22842588.76 | 0.00 | 0.545442E+10 | 0.790648E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.180485E+11 | 0.985444E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.304760E+11 | 0.113224E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.403580E+11 | 0.132557E+11 | 0.00 | 0.00 |
September | 260423.97 | 0.00 | 0.187667E+11 | 0.856843E+10 | 0.00 | 0.00 |
October | 0.112859E+09 | 0.00 | 0.982622E+09 | 0.678013E+10 | 0.00 | 0.00 |
November | 0.131383E+10 | 0.00 | 15664202.89 | 0.588208E+10 | 0.00 | 0.00 |
December | 0.405071E+10 | 0.00 | 957.97 | 0.556296E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.163253E+11 | 0.00 | 0.118496E+12 | 0.950409E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 223.15 | 0.479782E+10 | 0.00 | 0.00 |
Maximum of Months | 0.615239E+10 | 0.00 | 0.403580E+11 | 0.132557E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.169431E+12 | 0.00 | 69830.70 | 0.369395E+11 | 0.00 | 0.00 |
February | 0.104900E+12 | 0.00 | 121828.74 | 0.352018E+11 | 0.00 | 0.00 |
March | 0.697592E+11 | 0.00 | 144988.29 | 0.422958E+11 | 0.00 | 0.00 |
April | 0.682866E+10 | 0.00 | 0.361742E+11 | 0.602700E+11 | 0.00 | 0.00 |
May | 0.303292E+10 | 0.00 | 0.465161E+11 | 0.629850E+11 | 0.00 | 0.00 |
June | 36538174.50 | 0.00 | 0.149868E+12 | 0.747340E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.243175E+12 | 0.790210E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.310482E+12 | 0.881860E+11 | 0.00 | 0.00 |
September | 0.389549E+09 | 0.00 | 0.165378E+12 | 0.711998E+11 | 0.00 | 0.00 |
October | 0.200358E+11 | 0.00 | 0.818616E+10 | 0.484420E+11 | 0.00 | 0.00 |
November | 0.806048E+11 | 0.00 | 67609836.05 | 0.376143E+11 | 0.00 | 0.00 |
December | 0.190751E+12 | 0.00 | 75855.96 | 0.348742E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.645770E+12 | 0.00 | 0.959847E+12 | 0.671763E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 69830.70 | 0.348742E+11 | 0.00 | 0.00 |
Maximum of Months | 0.190751E+12 | 0.00 | 0.310482E+12 | 0.881860E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.353037E+11 | 0.00 | 230.66 | 0.349976E+10 | 0.00 | 0.00 |
February | 0.247025E+11 | 0.00 | 0.00 | 0.307684E+10 | 0.00 | 0.00 |
March | 0.187555E+11 | 0.00 | 53.57 | 0.349471E+10 | 0.00 | 0.00 |
April | 0.327165E+10 | 0.00 | 0.352872E+10 | 0.452567E+10 | 0.00 | 0.00 |
May | 0.210267E+10 | 0.00 | 0.480583E+10 | 0.500499E+10 | 0.00 | 0.00 |
June | 0.171984E+09 | 0.00 | 0.157777E+11 | 0.637950E+10 | 0.00 | 0.00 |
July | 76829487.94 | 0.00 | 0.249995E+11 | 0.690454E+10 | 0.00 | 0.00 |
August | 25484446.35 | 0.00 | 0.300505E+11 | 0.733630E+10 | 0.00 | 0.00 |
September | 0.671239E+09 | 0.00 | 0.151489E+11 | 0.542882E+10 | 0.00 | 0.00 |
October | 0.837018E+10 | 0.00 | 0.610181E+09 | 0.351733E+10 | 0.00 | 0.00 |
November | 0.213967E+11 | 0.00 | 5113630.04 | 0.321027E+10 | 0.00 | 0.00 |
December | 0.398843E+11 | 0.00 | 29134.00 | 0.361591E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.154733E+12 | 0.00 | 0.949265E+11 | 0.559946E+11 | 0.00 | 0.00 |
Minimum of Months | 25484446.35 | 0.00 | 0.00 | 0.307684E+10 | 0.00 | 0.00 |
Maximum of Months | 0.398843E+11 | 0.00 | 0.300505E+11 | 0.733630E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.148609E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 6327.39 | 0.131214E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1228608.27 | 0.155410E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.731211E+09 | 0.146431E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.228274E+10 | 0.154701E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.822478E+10 | 0.152606E+11 | 0.00 | 0.00 |
July | 93.38 | 0.00 | 0.133619E+11 | 0.149608E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.174902E+11 | 0.163774E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.849575E+10 | 0.150113E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.139882E+09 | 0.152276E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 13067293.49 | 0.146571E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.146106E+11 | 0.00 | 0.00 |
Annual Sum or Average | 93.38 | 0.00 | 0.507407E+11 | 0.179742E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.131214E+11 | 0.00 | 0.00 |
Maximum of Months | 93.38 | 0.00 | 0.174902E+11 | 0.163774E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.402497E+12 | 0.177508E+12 | 0.00 | 0.41 |
February | 0.00 | 0.00 | 0.633497E+12 | 0.208937E+12 | 0.00 | 0.27 |
March | 0.00 | 0.00 | 0.999011E+12 | 0.282254E+12 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.125808E+13 | 0.322912E+12 | 0.00 | 0.23 |
May | 0.00 | 0.00 | 0.410767E+12 | 0.177814E+12 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.692478E+12 | 0.226230E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.102222E+13 | 0.292233E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.132558E+13 | 0.350377E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.403921E+12 | 0.173357E+12 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.708429E+12 | 0.230950E+12 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.968953E+12 | 0.272142E+12 | 0.00 | 0.16 |
December | 0.00 | 0.00 | 0.129258E+13 | 0.330262E+12 | 0.00 | 0.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.101180E+14 | 0.304498E+13 | 0.00 | 1.90 |
Minimum of Months | 0.00 | 0.00 | 0.402497E+12 | 0.173357E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.132558E+13 | 0.350377E+12 | 0.00 | 0.41 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.530047E+10 | 0.260816E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108153E+11 | 0.347339E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.185243E+11 | 0.497833E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245378E+11 | 0.595386E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.676371E+10 | 0.286814E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.130519E+11 | 0.396063E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.199239E+11 | 0.530568E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.261050E+11 | 0.648352E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.677777E+10 | 0.281717E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126462E+11 | 0.392444E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.178939E+11 | 0.478134E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.242836E+11 | 0.594912E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186624E+12 | 0.531038E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.530047E+10 | 0.260816E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.261050E+11 | 0.648352E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.297609E+11 | 0.208921E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.854039E+11 | 0.299550E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.158385E+12 | 0.444230E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.224977E+12 | 0.553804E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.552977E+11 | 0.256792E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.118498E+12 | 0.367795E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.185042E+12 | 0.498198E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.244792E+12 | 0.612020E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.564204E+11 | 0.253887E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.105244E+12 | 0.347653E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.150288E+12 | 0.422095E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.205143E+12 | 0.524668E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161925E+13 | 0.478961E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.297609E+11 | 0.208921E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.244792E+12 | 0.612020E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.100173E+10 | 0.170005E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.639658E+10 | 0.261437E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.140231E+11 | 0.414967E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.215399E+11 | 0.540714E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.463193E+10 | 0.241864E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.114155E+11 | 0.362444E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.181417E+11 | 0.494747E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.241312E+11 | 0.609152E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.487237E+10 | 0.241552E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.879396E+10 | 0.318618E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.129470E+11 | 0.388200E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.180592E+11 | 0.485786E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145954E+12 | 0.452949E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.100173E+10 | 0.170005E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.241312E+11 | 0.609152E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.479782E+10 | 2220.89 | 0.615239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489540E+10 | 223.15 | 0.332606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.638495E+10 | 3185.11 | 0.127396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.983017E+10 | 0.439389E+10 | 72376586.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.790648E+10 | 0.545442E+10 | 22842588.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.985444E+10 | 0.180485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113224E+11 | 0.304760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132557E+11 | 0.403580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.856843E+10 | 0.187667E+11 | 260423.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.678013E+10 | 0.982622E+09 | 0.112859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.588208E+10 | 15664202.89 | 0.131383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.556296E+10 | 957.97 | 0.405071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.950409E+11 | 0.118496E+12 | 0.163253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.479782E+10 | 223.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132557E+11 | 0.403580E+11 | 0.615239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.369395E+11 | 69830.70 | 0.169431E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.352018E+11 | 121828.74 | 0.104900E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.422958E+11 | 144988.29 | 0.697592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.602700E+11 | 0.361742E+11 | 0.682866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.629850E+11 | 0.465161E+11 | 0.303292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.747340E+11 | 0.149868E+12 | 36538174.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.790210E+11 | 0.243175E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.881860E+11 | 0.310482E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.711998E+11 | 0.165378E+12 | 0.389549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.484420E+11 | 0.818616E+10 | 0.200358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.376143E+11 | 67609836.05 | 0.806048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348742E+11 | 75855.96 | 0.190751E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.671763E+12 | 0.959847E+12 | 0.645770E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.348742E+11 | 69830.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.881860E+11 | 0.310482E+12 | 0.190751E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.349976E+10 | 230.66 | 0.353037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307684E+10 | 0.00 | 0.247025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.349471E+10 | 53.57 | 0.187555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.452567E+10 | 0.352872E+10 | 0.327165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.500499E+10 | 0.480583E+10 | 0.210267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.637950E+10 | 0.157777E+11 | 0.171984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.690454E+10 | 0.249995E+11 | 76829487.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.733630E+10 | 0.300505E+11 | 25484446.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.542882E+10 | 0.151489E+11 | 0.671239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.351733E+10 | 0.610181E+09 | 0.837018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321027E+10 | 5113630.04 | 0.213967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.361591E+10 | 29134.00 | 0.398843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559946E+11 | 0.949265E+11 | 0.154733E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.307684E+10 | 0.00 | 25484446.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.733630E+10 | 0.300505E+11 | 0.398843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131214E+11 | 6327.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155410E+11 | 1228608.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146431E+11 | 0.731211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154701E+11 | 0.228274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152606E+11 | 0.822478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149608E+11 | 0.133619E+11 | 93.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163774E+11 | 0.174902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150113E+11 | 0.849575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152276E+11 | 0.139908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146571E+11 | 13067293.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179742E+12 | 0.507408E+11 | 93.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163774E+11 | 0.174902E+11 | 93.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.958232E+11 | 0.321916E+12 | 0.00 | 0.00 | 0.00 | 0.109864E+10 | 0.00 | 0.00 |
February | 0.865500E+11 | 0.511826E+12 | 0.00 | 0.00 | 0.00 | 0.713220E+09 | 0.00 | 0.00 |
March | 0.958232E+11 | 0.813504E+12 | 0.00 | 0.00 | 0.00 | 0.919427E+09 | 0.00 | 0.00 |
April | 0.927322E+11 | 0.102851E+13 | 0.00 | 0.00 | 0.00 | 0.612964E+09 | 0.00 | 0.00 |
May | 0.958232E+11 | 0.328870E+12 | 0.00 | 0.00 | 0.00 | 93033870.61 | 0.00 | 0.00 |
June | 0.927322E+11 | 0.558980E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.958232E+11 | 0.825806E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.958232E+11 | 0.107103E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.927322E+11 | 0.323323E+12 | 0.00 | 0.00 | 0.00 | 27777088.58 | 0.00 | 0.00 |
October | 0.958232E+11 | 0.573413E+12 | 0.00 | 0.00 | 0.00 | 0.110309E+09 | 0.00 | 0.00 |
November | 0.927322E+11 | 0.789964E+12 | 0.00 | 0.00 | 0.00 | 0.418953E+09 | 0.00 | 0.00 |
December | 0.958232E+11 | 0.105922E+13 | 0.00 | 0.00 | 0.00 | 0.107835E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.112824E+13 | 0.820636E+13 | 0.00 | 0.00 | 0.00 | 0.507267E+10 | 0.00 | 0.00 |
Minimum of Months | 0.865500E+11 | 0.321916E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.958232E+11 | 0.107103E+13 | 0.00 | 0.00 | 0.00 | 0.109864E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.152288E+10 | 0.421519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137550E+10 | 0.871742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152288E+10 | 0.150688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147375E+10 | 0.200577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152288E+10 | 0.541844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147375E+10 | 0.105650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152288E+10 | 0.161411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152288E+10 | 0.211444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147375E+10 | 0.543435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152288E+10 | 0.102447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147375E+10 | 0.145863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152288E+10 | 0.198574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179306E+11 | 0.151451E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137550E+10 | 0.421519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152288E+10 | 0.211444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.145669E+11 | 0.234357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131572E+11 | 0.686061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145669E+11 | 0.128529E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140970E+11 | 0.183693E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145669E+11 | 0.441855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140970E+11 | 0.958154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145669E+11 | 0.149789E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145669E+11 | 0.198157E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140970E+11 | 0.451288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145669E+11 | 0.850459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140970E+11 | 0.122176E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145669E+11 | 0.167244E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171514E+12 | 0.131180E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131572E+11 | 0.234357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145669E+11 | 0.198157E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147699E+10 | 0.778681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133406E+10 | 0.511627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147699E+10 | 0.113504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142935E+10 | 0.175621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147699E+10 | 0.369028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142935E+10 | 0.922037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147699E+10 | 0.146712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147699E+10 | 0.195166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142935E+10 | 0.388620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147699E+10 | 0.708477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142935E+10 | 0.104944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147699E+10 | 0.146784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173904E+11 | 0.118050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133406E+10 | 0.778681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147699E+10 | 0.195166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.479782E+10 | 0.615239E+10 | 2220.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489540E+10 | 0.332606E+10 | 223.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.638495E+10 | 0.127396E+10 | 3185.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.983017E+10 | 72376586.43 | 0.439389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.790648E+10 | 22842588.76 | 0.545442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.985444E+10 | 0.00 | 0.180485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113224E+11 | 0.00 | 0.304760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132557E+11 | 0.00 | 0.403580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.856843E+10 | 260423.97 | 0.187667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.678013E+10 | 0.112859E+09 | 0.982622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.588208E+10 | 0.131383E+10 | 15664202.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.556296E+10 | 0.405071E+10 | 957.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.950409E+11 | 0.163253E+11 | 0.118496E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.479782E+10 | 0.00 | 223.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132557E+11 | 0.615239E+10 | 0.403580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.369395E+11 | 0.169431E+12 | 69830.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.352018E+11 | 0.104900E+12 | 121828.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.422958E+11 | 0.697592E+11 | 144988.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.602700E+11 | 0.682866E+10 | 0.361742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.629850E+11 | 0.303292E+10 | 0.465161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.747340E+11 | 36538174.50 | 0.149868E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.790210E+11 | 0.00 | 0.243175E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.881860E+11 | 0.00 | 0.310482E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.711998E+11 | 0.389549E+09 | 0.165378E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.484420E+11 | 0.200358E+11 | 0.818616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.376143E+11 | 0.806048E+11 | 67609836.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348742E+11 | 0.190751E+12 | 75855.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.671763E+12 | 0.645770E+12 | 0.959847E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.348742E+11 | 0.00 | 69830.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.881860E+11 | 0.190751E+12 | 0.310482E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.349976E+10 | 0.353037E+11 | 230.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307684E+10 | 0.247025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.349471E+10 | 0.187555E+11 | 53.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.452567E+10 | 0.327165E+10 | 0.352872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.500499E+10 | 0.210267E+10 | 0.480583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.637950E+10 | 0.171984E+09 | 0.157777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.690454E+10 | 76829487.94 | 0.249995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.733630E+10 | 25484446.35 | 0.300505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.542882E+10 | 0.671239E+09 | 0.151489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.351733E+10 | 0.837018E+10 | 0.610181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321027E+10 | 0.213967E+11 | 5113630.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.361591E+10 | 0.398843E+11 | 29134.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559946E+11 | 0.154733E+12 | 0.949265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.307684E+10 | 25484446.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.733630E+10 | 0.398843E+11 | 0.300505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131214E+11 | 0.00 | 6327.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155410E+11 | 0.00 | 1228608.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146431E+11 | 0.00 | 0.731211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154701E+11 | 0.00 | 0.228274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152606E+11 | 0.00 | 0.822478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149608E+11 | 93.38 | 0.133619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163774E+11 | 0.00 | 0.174902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150113E+11 | 0.00 | 0.849575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152276E+11 | 0.00 | 0.139882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146571E+11 | 0.00 | 13067293.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179742E+12 | 93.38 | 0.507407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163774E+11 | 93.38 | 0.174902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.958232E+11 | 0.00 | 0.402497E+12 | 0.00 | 0.805814E+11 | 0.00 | 0.00 | 0.00 | 0.110358E+10 | 0.00 | 0.00 | 0.00 |
February | 0.865500E+11 | 0.00 | 0.633497E+12 | 0.00 | 0.121671E+12 | 0.00 | 0.00 | 0.00 | 0.716431E+09 | 0.00 | 0.00 | 0.00 |
March | 0.958232E+11 | 0.00 | 0.999011E+12 | 0.00 | 0.185507E+12 | 0.00 | 0.00 | 0.00 | 0.923566E+09 | 0.00 | 0.00 | 0.00 |
April | 0.927322E+11 | 0.00 | 0.125808E+13 | 0.00 | 0.229564E+12 | 0.00 | 0.00 | 0.00 | 0.615723E+09 | 0.00 | 0.00 | 0.00 |
May | 0.958232E+11 | 0.00 | 0.410767E+12 | 0.00 | 0.818970E+11 | 0.00 | 0.00 | 0.00 | 93452653.78 | 0.00 | 0.00 | 0.00 |
June | 0.927322E+11 | 0.00 | 0.692478E+12 | 0.00 | 0.133497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.958232E+11 | 0.00 | 0.102222E+13 | 0.00 | 0.196410E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.958232E+11 | 0.00 | 0.132558E+13 | 0.00 | 0.254554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.927322E+11 | 0.00 | 0.403921E+12 | 0.00 | 0.805974E+11 | 0.00 | 0.00 | 0.00 | 27902124.52 | 0.00 | 0.00 | 0.00 |
October | 0.958232E+11 | 0.00 | 0.708429E+12 | 0.00 | 0.135016E+12 | 0.00 | 0.00 | 0.00 | 0.110805E+09 | 0.00 | 0.00 | 0.00 |
November | 0.927322E+11 | 0.00 | 0.968953E+12 | 0.00 | 0.178989E+12 | 0.00 | 0.00 | 0.00 | 0.420839E+09 | 0.00 | 0.00 | 0.00 |
December | 0.958232E+11 | 0.00 | 0.129258E+13 | 0.00 | 0.233356E+12 | 0.00 | 0.00 | 0.00 | 0.108321E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112824E+13 | 0.00 | 0.101180E+14 | 0.00 | 0.191164E+13 | 0.00 | 0.00 | 0.00 | 0.509551E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.865500E+11 | 0.00 | 0.402497E+12 | 0.00 | 0.805814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.958232E+11 | 0.00 | 0.132558E+13 | 0.00 | 0.254554E+12 | 0.00 | 0.00 | 0.00 | 0.110358E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.152288E+10 | 0.00 | 0.530047E+10 | 0.00 | 0.108528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137550E+10 | 0.00 | 0.108153E+11 | 0.00 | 0.209789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152288E+10 | 0.00 | 0.185243E+11 | 0.00 | 0.345546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147375E+10 | 0.00 | 0.245378E+11 | 0.00 | 0.448011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152288E+10 | 0.00 | 0.676371E+10 | 0.00 | 0.134527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147375E+10 | 0.00 | 0.130519E+11 | 0.00 | 0.248688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152288E+10 | 0.00 | 0.199239E+11 | 0.00 | 0.378281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152288E+10 | 0.00 | 0.261050E+11 | 0.00 | 0.496065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147375E+10 | 0.00 | 0.677777E+10 | 0.00 | 0.134342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152288E+10 | 0.00 | 0.126462E+11 | 0.00 | 0.240156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147375E+10 | 0.00 | 0.178939E+11 | 0.00 | 0.330758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152288E+10 | 0.00 | 0.242836E+11 | 0.00 | 0.442624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179306E+11 | 0.00 | 0.186624E+12 | 0.00 | 0.351732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137550E+10 | 0.00 | 0.530047E+10 | 0.00 | 0.108528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152288E+10 | 0.00 | 0.261050E+11 | 0.00 | 0.496065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.145669E+11 | 0.00 | 0.297609E+11 | 0.00 | 0.632518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131572E+11 | 0.00 | 0.854039E+11 | 0.00 | 0.167978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145669E+11 | 0.00 | 0.158385E+12 | 0.00 | 0.298561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140970E+11 | 0.00 | 0.224977E+12 | 0.00 | 0.412833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145669E+11 | 0.00 | 0.552977E+11 | 0.00 | 0.111122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140970E+11 | 0.00 | 0.118498E+12 | 0.00 | 0.226825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145669E+11 | 0.00 | 0.185042E+12 | 0.00 | 0.352528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145669E+11 | 0.00 | 0.244792E+12 | 0.00 | 0.466350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140970E+11 | 0.00 | 0.564204E+11 | 0.00 | 0.112916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145669E+11 | 0.00 | 0.105244E+12 | 0.00 | 0.201984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140970E+11 | 0.00 | 0.150288E+12 | 0.00 | 0.281125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145669E+11 | 0.00 | 0.205143E+12 | 0.00 | 0.378999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171514E+12 | 0.00 | 0.161925E+13 | 0.00 | 0.307447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131572E+11 | 0.00 | 0.297609E+11 | 0.00 | 0.632518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145669E+11 | 0.00 | 0.244792E+12 | 0.00 | 0.466350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147699E+10 | 0.00 | 0.100173E+10 | 0.00 | 0.223054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133406E+10 | 0.00 | 0.639658E+10 | 0.00 | 0.128031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147699E+10 | 0.00 | 0.140231E+11 | 0.00 | 0.267268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142935E+10 | 0.00 | 0.215399E+11 | 0.00 | 0.397779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147699E+10 | 0.00 | 0.463193E+10 | 0.00 | 0.941647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142935E+10 | 0.00 | 0.114155E+11 | 0.00 | 0.219510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147699E+10 | 0.00 | 0.181417E+11 | 0.00 | 0.347048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147699E+10 | 0.00 | 0.241312E+11 | 0.00 | 0.461453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142935E+10 | 0.00 | 0.487237E+10 | 0.00 | 0.986173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147699E+10 | 0.00 | 0.879396E+10 | 0.00 | 0.170919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142935E+10 | 0.00 | 0.129470E+11 | 0.00 | 0.245265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147699E+10 | 0.00 | 0.180592E+11 | 0.00 | 0.338087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173904E+11 | 0.00 | 0.145954E+12 | 0.00 | 0.279045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133406E+10 | 0.00 | 0.100173E+10 | 0.00 | 0.223054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147699E+10 | 0.00 | 0.241312E+11 | 0.00 | 0.461453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.584989E+09 | 0.00 | 0.00 | 0.106604E+09 | 0.00 | 0.00 | 0.703460E+11 | 0.00 | 0.58 |
February | 0.430985E+09 | 0.00 | 0.00 | 99429976.97 | 0.00 | 0.00 | 0.643080E+11 | 0.00 | 0.60 |
March | 0.382636E+09 | 0.00 | 0.00 | 0.113642E+09 | 0.00 | 0.00 | 0.780717E+11 | 0.00 | 0.71 |
April | 0.346379E+09 | 0.00 | 0.00 | 0.120384E+09 | 0.00 | 0.00 | 0.761482E+11 | 0.00 | 0.94 |
May | 0.373436E+09 | 0.00 | 0.00 | 0.116481E+09 | 0.00 | 0.00 | 0.760985E+11 | 0.00 | 0.97 |
June | 0.244319E+09 | 1785579.87 | 0.00 | 0.121539E+09 | 0.00 | 0.00 | 0.724410E+11 | 0.00 | 1.26 |
July | 0.306822E+09 | 53999362.72 | 0.00 | 0.125160E+09 | 6648750.17 | 0.00 | 0.671452E+11 | 0.00 | 1.34 |
August | 0.277086E+09 | 0.00 | 0.00 | 0.138983E+09 | 0.00 | 0.00 | 0.711998E+11 | 0.00 | 1.60 |
September | 0.349669E+09 | 0.00 | 0.00 | 0.122121E+09 | 0.00 | 0.00 | 0.693689E+11 | 0.00 | 1.30 |
October | 0.410784E+09 | 0.00 | 0.00 | 0.119775E+09 | 0.00 | 0.00 | 0.780843E+11 | 0.00 | 0.93 |
November | 0.404341E+09 | 0.00 | 0.00 | 0.116420E+09 | 0.00 | 0.00 | 0.751496E+11 | 0.00 | 0.74 |
December | 0.615029E+09 | 0.00 | 0.00 | 0.113649E+09 | 0.00 | 0.00 | 0.726751E+11 | 0.00 | 0.60 |
Annual Sum or Average | 0.472648E+10 | 55784942.58 | 0.00 | 0.141419E+10 | 6648750.17 | 0.00 | 0.871036E+12 | 0.00 | 0.97 |
Minimum of Months | 0.244319E+09 | 0.00 | 0.00 | 99429976.97 | 0.00 | 0.00 | 0.643080E+11 | 0.00 | 0.58 |
Maximum of Months | 0.615029E+09 | 53999362.72 | 0.00 | 0.138983E+09 | 6648750.17 | 0.00 | 0.780843E+11 | 0.00 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.233852E+10 | 0.00 | 0.00 | 67028653.22 | 0.00 | 0.00 | 0.478727E+11 | 0.00 | 0.40 |
February | 0.178047E+10 | 0.00 | 0.00 | 72990140.89 | 0.00 | 0.00 | 0.461521E+11 | 0.00 | 0.44 |
March | 0.161834E+10 | 0.00 | 0.00 | 92712335.65 | 0.00 | 0.00 | 0.602260E+11 | 0.00 | 0.54 |
April | 0.531845E+10 | 0.00 | 0.00 | 0.102936E+09 | 0.00 | 0.00 | 0.637841E+11 | 0.00 | 0.82 |
May | 0.454144E+10 | 0.00 | 0.00 | 89879471.44 | 0.00 | 0.00 | 0.571324E+11 | 0.00 | 0.75 |
June | 0.544861E+10 | 5243620.53 | 0.00 | 99321576.25 | 71510872.81 | 0.00 | 0.572596E+11 | 0.00 | 1.01 |
July | 0.867092E+10 | 24503223.38 | 0.00 | 99784824.76 | 9508658.84 | 0.00 | 0.517884E+11 | 0.00 | 1.10 |
August | 0.100631E+11 | 0.00 | 0.00 | 0.113120E+09 | 0.00 | 0.00 | 0.540468E+11 | 0.00 | 1.28 |
September | 0.512458E+10 | 0.00 | 0.00 | 90268501.67 | 0.00 | 0.00 | 0.487848E+11 | 0.00 | 0.94 |
October | 0.259972E+10 | 0.00 | 0.00 | 88012547.22 | 0.00 | 0.00 | 0.563614E+11 | 0.00 | 0.67 |
November | 0.204516E+10 | 0.00 | 0.00 | 86319508.67 | 0.00 | 0.00 | 0.542474E+11 | 0.00 | 0.54 |
December | 0.148558E+10 | 0.00 | 0.00 | 84504733.90 | 0.00 | 0.00 | 0.529043E+11 | 0.00 | 0.44 |
Annual Sum or Average | 0.510349E+11 | 29746843.90 | 0.00 | 0.108688E+10 | 81019531.65 | 0.00 | 0.650560E+12 | 0.00 | 0.74 |
Minimum of Months | 0.148558E+10 | 0.00 | 0.00 | 67028653.22 | 0.00 | 0.00 | 0.461521E+11 | 0.00 | 0.40 |
Maximum of Months | 0.100631E+11 | 24503223.38 | 0.00 | 0.113120E+09 | 71510872.81 | 0.00 | 0.637841E+11 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.165988E+12 | 0.00 | 0.00 | 0.254243E+09 | 0.00 | 0.00 | 0.210077E+12 | 0.00 | 0.31 |
February | 0.136400E+12 | 0.00 | 0.00 | 0.282683E+09 | 0.00 | 0.00 | 0.201448E+12 | 0.00 | 0.31 |
March | 0.127156E+12 | 0.00 | 0.00 | 0.381575E+09 | 0.00 | 0.00 | 0.281905E+12 | 0.00 | 0.36 |
April | 0.424694E+11 | 0.00 | 0.00 | 0.571170E+09 | 0.00 | 0.00 | 0.410445E+12 | 0.00 | 0.55 |
May | 0.526911E+11 | 0.00 | 0.00 | 0.608020E+09 | 0.00 | 0.00 | 0.423990E+12 | 0.00 | 0.59 |
June | 0.359955E+11 | 47711910.41 | 0.00 | 0.716757E+09 | 0.773367E+09 | 0.00 | 0.440308E+12 | 0.00 | 0.79 |
July | 0.428199E+11 | 0.276671E+09 | 0.00 | 0.714507E+09 | 94622222.76 | 0.00 | 0.381941E+12 | 0.00 | 0.81 |
August | 0.371942E+11 | 0.00 | 0.00 | 0.813957E+09 | 0.00 | 0.00 | 0.397731E+12 | 0.00 | 0.92 |
September | 0.457788E+11 | 0.00 | 0.00 | 0.650298E+09 | 0.00 | 0.00 | 0.377282E+12 | 0.00 | 0.77 |
October | 0.766641E+11 | 0.00 | 0.00 | 0.463954E+09 | 0.00 | 0.00 | 0.330443E+12 | 0.00 | 0.48 |
November | 0.122611E+12 | 0.00 | 0.00 | 0.312465E+09 | 0.00 | 0.00 | 0.230852E+12 | 0.00 | 0.34 |
December | 0.178986E+12 | 0.00 | 0.00 | 0.191954E+09 | 0.00 | 0.00 | 0.164121E+12 | 0.00 | 0.28 |
Annual Sum or Average | 0.106475E+13 | 0.324383E+09 | 0.00 | 0.596158E+10 | 0.867989E+09 | 0.00 | 0.385054E+13 | 0.00 | 0.54 |
Minimum of Months | 0.359955E+11 | 0.00 | 0.00 | 0.191954E+09 | 0.00 | 0.00 | 0.164121E+12 | 0.00 | 0.28 |
Maximum of Months | 0.178986E+12 | 0.276671E+09 | 0.00 | 0.813957E+09 | 0.773367E+09 | 0.00 | 0.440308E+12 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.272921E+11 | 0.00 | 0.00 | 2000173.44 | 0.00 | 0.112569E+10 | 0.240184E+10 | 0.00 | 0.27 |
February | 0.234940E+11 | 0.00 | 0.00 | 2746147.42 | 0.00 | 0.464673E+09 | 0.358656E+10 | 0.00 | 0.27 |
March | 0.238434E+11 | 0.00 | 0.00 | 7280018.77 | 0.00 | 0.270251E+09 | 0.818276E+10 | 0.00 | 0.31 |
April | 0.107964E+11 | 3087095.70 | 0.00 | 32762547.37 | 0.00 | 0.00 | 0.272527E+11 | 0.00 | 0.48 |
May | 0.102758E+11 | 0.00 | 0.00 | 40021537.14 | 0.00 | 0.00 | 0.309990E+11 | 0.00 | 0.52 |
June | 0.717020E+10 | 979627.69 | 0.00 | 57211364.85 | 64059468.81 | 0.00 | 0.375130E+11 | 0.00 | 0.75 |
July | 0.656419E+10 | 17075290.79 | 0.00 | 59865884.18 | 7259650.27 | 0.00 | 0.346172E+11 | 0.00 | 0.79 |
August | 0.622539E+10 | 0.00 | 0.00 | 64167631.36 | 0.00 | 0.00 | 0.348074E+11 | 0.00 | 0.87 |
September | 0.908043E+10 | 0.00 | 0.00 | 42847833.82 | 0.00 | 0.00 | 0.269228E+11 | 0.00 | 0.67 |
October | 0.168718E+11 | 0.00 | 0.00 | 13883422.83 | 0.00 | 87976032.37 | 0.129471E+11 | 0.00 | 0.37 |
November | 0.223955E+11 | 0.00 | 0.00 | 4160250.71 | 0.00 | 0.442554E+09 | 0.451527E+10 | 0.00 | 0.29 |
December | 0.272077E+11 | 0.00 | 0.00 | 456418.23 | 0.00 | 0.908084E+09 | 0.108610E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.191217E+12 | 21142014.19 | 0.00 | 0.327403E+09 | 71319119.07 | 0.329922E+10 | 0.224832E+12 | 0.00 | 0.49 |
Minimum of Months | 0.622539E+10 | 0.00 | 0.00 | 456418.23 | 0.00 | 0.00 | 0.108610E+10 | 0.00 | 0.27 |
Maximum of Months | 0.272921E+11 | 17075290.79 | 0.00 | 64167631.36 | 64059468.81 | 0.112569E+10 | 0.375130E+11 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.389948E+10 | 0.00 | 0.00 | 388202.40 | 0.00 | 573775.25 | 0.567815E+09 | 0.00 | 0.28 |
February | 0.322269E+10 | 0.00 | 0.00 | 722177.61 | 0.00 | 0.00 | 0.873764E+09 | 0.00 | 0.29 |
March | 0.268237E+10 | 0.00 | 0.00 | 2878098.92 | 0.00 | 0.00 | 0.253216E+10 | 0.00 | 0.36 |
April | 0.180069E+10 | 0.00 | 0.00 | 6656203.77 | 0.00 | 0.00 | 0.516765E+10 | 0.00 | 0.68 |
May | 0.164543E+10 | 0.00 | 0.00 | 6622683.05 | 0.00 | 0.00 | 0.496344E+10 | 0.00 | 0.66 |
June | 0.938030E+09 | 1020696.09 | 0.00 | 10601813.59 | 9141036.93 | 0.00 | 0.675197E+10 | 0.00 | 1.03 |
July | 0.127987E+10 | 4893504.68 | 0.00 | 11393787.48 | 1215465.54 | 0.00 | 0.635628E+10 | 0.00 | 1.15 |
August | 0.157411E+10 | 0.00 | 0.00 | 11865973.91 | 0.00 | 0.00 | 0.607577E+10 | 0.00 | 1.25 |
September | 0.180959E+10 | 0.00 | 0.00 | 6117067.74 | 0.00 | 0.00 | 0.384141E+10 | 0.00 | 0.80 |
October | 0.233938E+10 | 0.00 | 0.00 | 3321040.71 | 0.00 | 0.00 | 0.280999E+10 | 0.00 | 0.47 |
November | 0.284039E+10 | 0.00 | 0.00 | 1630066.02 | 0.00 | 0.00 | 0.163380E+10 | 0.00 | 0.34 |
December | 0.371025E+10 | 0.00 | 0.00 | 275838.57 | 0.00 | 0.00 | 0.628834E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.277423E+11 | 5914200.77 | 0.00 | 62472953.75 | 10356502.47 | 573775.25 | 0.422029E+11 | 0.00 | 0.63 |
Minimum of Months | 0.938030E+09 | 0.00 | 0.00 | 275838.57 | 0.00 | 0.00 | 0.567815E+09 | 0.00 | 0.27 |
Maximum of Months | 0.389948E+10 | 4893504.68 | 0.00 | 11865973.91 | 9141036.93 | 573775.25 | 0.675197E+10 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.603028E+10 | 0.00 | 0.00 | 59992.29 | 0.00 | 53527156.15 | 0.102830E+09 | 0.00 | 0.60 |
February | 0.532724E+10 | 0.00 | 0.00 | 343257.61 | 0.00 | 1600180.90 | 0.332586E+09 | 0.00 | 0.62 |
March | 0.593925E+10 | 0.00 | 0.00 | 321989.47 | 0.00 | 0.00 | 0.683700E+09 | 0.00 | 0.71 |
April | 0.312757E+10 | 0.00 | 0.00 | 7186330.49 | 0.00 | 0.00 | 0.521713E+10 | 0.00 | 1.24 |
May | 0.281972E+10 | 0.00 | 0.00 | 7042424.75 | 0.00 | 0.00 | 0.535554E+10 | 0.00 | 1.24 |
June | 0.239922E+10 | 658447.69 | 0.00 | 8539534.91 | 12657968.26 | 0.00 | 0.573517E+10 | 0.00 | 1.66 |
July | 0.275673E+10 | 6048634.57 | 0.00 | 9082097.89 | 1683104.92 | 0.00 | 0.522679E+10 | 0.00 | 1.80 |
August | 0.321228E+10 | 0.00 | 0.00 | 9631853.06 | 0.00 | 0.00 | 0.525419E+10 | 0.00 | 2.04 |
September | 0.296765E+10 | 0.00 | 0.00 | 7129309.00 | 0.00 | 0.00 | 0.429564E+10 | 0.00 | 1.55 |
October | 0.470699E+10 | 0.00 | 0.00 | 2001818.17 | 0.00 | 0.00 | 0.180405E+10 | 0.00 | 0.90 |
November | 0.583252E+10 | 0.00 | 0.00 | 117799.12 | 0.00 | 0.00 | 0.175529E+09 | 0.00 | 0.70 |
December | 0.594158E+10 | 0.00 | 0.00 | 14564.66 | 0.00 | 5644700.88 | 61914971.93 | 0.00 | 0.59 |
Annual Sum or Average | 0.510610E+11 | 6707082.25 | 0.00 | 51470971.42 | 14341073.18 | 60772037.93 | 0.342451E+11 | 0.00 | 1.14 |
Minimum of Months | 0.239922E+10 | 0.00 | 0.00 | 14564.66 | 0.00 | 0.00 | 61914971.93 | 0.00 | 0.59 |
Maximum of Months | 0.603028E+10 | 6048634.57 | 0.00 | 9631853.06 | 12657968.26 | 53527156.15 | 0.573517E+10 | 0.00 | 2.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.697087E+10 | 0.00 | 0.00 | 2713012.65 | 0.00 | 0.133216E+09 | 0.235172E+10 | 0.00 | 0.59 |
February | 0.601261E+10 | 0.00 | 0.00 | 4026775.02 | 0.00 | 4371046.52 | 0.310099E+10 | 0.00 | 0.65 |
March | 0.710831E+10 | 0.00 | 0.00 | 2364990.27 | 0.00 | 1329989.00 | 0.258445E+10 | 0.00 | 0.67 |
April | 0.421916E+10 | 0.00 | 0.00 | 13051644.98 | 0.00 | 0.00 | 0.924782E+10 | 0.00 | 1.34 |
May | 0.471382E+10 | 0.00 | 0.00 | 8317011.93 | 0.00 | 0.00 | 0.689395E+10 | 0.00 | 1.16 |
June | 0.368160E+10 | 1134597.25 | 0.00 | 10674324.46 | 18006398.98 | 0.00 | 0.748281E+10 | 0.00 | 1.49 |
July | 0.398587E+10 | 7312326.20 | 0.00 | 12881660.28 | 2394275.14 | 0.00 | 0.748385E+10 | 0.00 | 1.71 |
August | 0.407476E+10 | 0.00 | 0.00 | 17536211.65 | 0.00 | 0.00 | 0.887970E+10 | 0.00 | 2.12 |
September | 0.368292E+10 | 0.00 | 0.00 | 15205101.76 | 0.00 | 0.00 | 0.860185E+10 | 0.00 | 1.81 |
October | 0.544365E+10 | 0.00 | 0.00 | 7316037.62 | 0.00 | 0.00 | 0.601462E+10 | 0.00 | 1.08 |
November | 0.676832E+10 | 0.00 | 0.00 | 2821851.12 | 0.00 | 5860170.60 | 0.245719E+10 | 0.00 | 0.70 |
December | 0.748151E+10 | 0.00 | 0.00 | 1634150.37 | 0.00 | 22358457.76 | 0.146115E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.641434E+11 | 8446923.45 | 0.00 | 98542772.10 | 20400674.11 | 0.167136E+09 | 0.665601E+11 | 0.00 | 1.16 |
Minimum of Months | 0.368160E+10 | 0.00 | 0.00 | 1634150.37 | 0.00 | 0.00 | 0.146115E+10 | 0.00 | 0.57 |
Maximum of Months | 0.748151E+10 | 7312326.20 | 0.00 | 17536211.65 | 18006398.98 | 0.133216E+09 | 0.924782E+10 | 0.00 | 2.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.689032E+10 | 0.00 | 0.00 | 523601.86 | 0.00 | 349851.44 | 0.720007E+09 | 0.00 | 0.74 |
February | 0.476824E+10 | 0.00 | 0.00 | 2223729.46 | 0.00 | 0.00 | 0.249509E+10 | 0.00 | 0.80 |
March | 0.305053E+10 | 0.00 | 0.00 | 5312469.40 | 0.00 | 0.00 | 0.551243E+10 | 0.00 | 0.92 |
April | 0.130537E+10 | 0.00 | 0.00 | 16308373.28 | 0.00 | 0.00 | 0.105024E+11 | 0.00 | 1.82 |
May | 0.268900E+10 | 0.00 | 0.00 | 9095627.08 | 0.00 | 0.00 | 0.725869E+10 | 0.00 | 1.54 |
June | 0.126797E+10 | 20212600.90 | 0.00 | 15541651.84 | 3407767.43 | 0.00 | 0.945665E+10 | 0.00 | 2.24 |
July | 0.172837E+10 | 9405547.51 | 0.00 | 20202981.79 | 802543.60 | 0.00 | 0.952188E+10 | 0.00 | 2.63 |
August | 0.199399E+10 | 0.00 | 0.00 | 22754186.70 | 0.00 | 0.00 | 0.990788E+10 | 0.00 | 2.98 |
September | 0.292916E+10 | 0.00 | 0.00 | 8070170.72 | 0.00 | 0.00 | 0.542968E+10 | 0.00 | 1.83 |
October | 0.332503E+10 | 0.00 | 0.00 | 4511091.33 | 0.00 | 0.00 | 0.498456E+10 | 0.00 | 1.17 |
November | 0.371283E+10 | 0.00 | 0.00 | 3119475.57 | 0.00 | 0.00 | 0.383770E+10 | 0.00 | 0.88 |
December | 0.404392E+10 | 0.00 | 0.00 | 2433610.42 | 0.00 | 0.00 | 0.339791E+10 | 0.00 | 0.73 |
Annual Sum or Average | 0.377047E+11 | 29618148.41 | 0.00 | 0.110097E+09 | 4210311.03 | 349851.44 | 0.730249E+11 | 0.00 | 1.53 |
Minimum of Months | 0.126797E+10 | 0.00 | 0.00 | 523601.86 | 0.00 | 0.00 | 0.720007E+09 | 0.00 | 0.73 |
Maximum of Months | 0.689032E+10 | 20212600.90 | 0.00 | 22754186.70 | 3407767.43 | 349851.44 | 0.105024E+11 | 0.00 | 2.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.307585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120748E+11 | 0.00 | 0.00 | 0.27 |
February | 0.308551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657043E+10 | 0.00 | 0.00 | 0.27 |
March | 0.397895E+11 | 0.00 | 0.00 | 67233.81 | 0.00 | 0.245581E+10 | 0.327664E+09 | 0.00 | 0.30 |
April | 0.247003E+11 | 0.00 | 0.00 | 21105874.98 | 0.00 | 3906829.90 | 0.186924E+11 | 0.00 | 0.43 |
May | 0.239375E+11 | 0.00 | 0.00 | 30133301.40 | 0.00 | 11061675.55 | 0.236709E+11 | 0.00 | 0.49 |
June | 0.131485E+11 | 10264307.44 | 0.00 | 64144599.57 | 97181286.34 | 0.00 | 0.411003E+11 | 0.00 | 0.75 |
July | 0.127253E+11 | 57666348.79 | 0.00 | 67904265.12 | 11890231.09 | 0.00 | 0.385255E+11 | 0.00 | 0.81 |
August | 0.142851E+11 | 0.00 | 0.00 | 66422067.28 | 0.00 | 0.00 | 0.347458E+11 | 0.00 | 0.84 |
September | 0.226649E+11 | 0.00 | 0.00 | 32439883.50 | 0.00 | 0.00 | 0.197303E+11 | 0.00 | 0.62 |
October | 0.339583E+11 | 0.00 | 0.00 | 3638219.27 | 0.00 | 0.707800E+09 | 0.423230E+10 | 0.00 | 0.36 |
November | 0.323493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561743E+10 | 0.00 | 0.00 | 0.29 |
December | 0.242526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165650E+11 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.303425E+12 | 67930656.23 | 0.00 | 0.285855E+09 | 0.109072E+09 | 0.440062E+11 | 0.181025E+12 | 0.00 | 0.48 |
Minimum of Months | 0.127253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.397895E+11 | 57666348.79 | 0.00 | 67904265.12 | 97181286.34 | 0.165650E+11 | 0.411003E+11 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.474452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161306E+11 | 0.00 | 0.00 | 0.63 |
February | 0.467246E+11 | 0.00 | 0.00 | 16665.69 | 0.00 | 0.872193E+10 | 0.146120E+09 | 0.00 | 0.62 |
March | 0.590589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419977E+10 | 0.00 | 0.00 | 0.69 |
April | 0.280130E+11 | 0.00 | 0.00 | 53661456.42 | 0.00 | 19059023.45 | 0.414860E+11 | 0.00 | 1.07 |
May | 0.345491E+11 | 0.00 | 0.00 | 50365119.87 | 0.00 | 14819831.94 | 0.385052E+11 | 0.00 | 1.14 |
June | 0.276010E+11 | 8030128.00 | 0.00 | 69460696.14 | 0.144439E+09 | 0.00 | 0.449688E+11 | 0.00 | 1.53 |
July | 0.213820E+11 | 85276817.28 | 0.00 | 78220132.93 | 17672201.40 | 0.00 | 0.446122E+11 | 0.00 | 1.58 |
August | 0.244889E+11 | 0.00 | 0.00 | 82898725.22 | 0.00 | 0.00 | 0.447125E+11 | 0.00 | 1.79 |
September | 0.306579E+11 | 0.00 | 0.00 | 55964316.00 | 0.00 | 0.00 | 0.341288E+11 | 0.00 | 1.43 |
October | 0.471915E+11 | 0.00 | 0.00 | 8921695.92 | 0.00 | 0.123558E+10 | 0.100335E+11 | 0.00 | 0.84 |
November | 0.487834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761062E+10 | 0.00 | 0.00 | 0.67 |
December | 0.349926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255761E+11 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.450888E+12 | 93306945.28 | 0.00 | 0.399509E+09 | 0.162111E+09 | 0.635085E+11 | 0.258593E+12 | 0.00 | 1.05 |
Minimum of Months | 0.213820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.590589E+11 | 85276817.28 | 0.00 | 82898725.22 | 0.144439E+09 | 0.255761E+11 | 0.449688E+11 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.658504E+11 | 0.00 | 0.00 | 20919139.48 | 0.00 | 0.111989E+11 | 0.173215E+11 | 0.00 | 0.60 |
February | 0.577111E+11 | 0.00 | 0.00 | 31687886.99 | 0.00 | 0.595998E+10 | 0.229791E+11 | 0.00 | 0.63 |
March | 0.768249E+11 | 0.00 | 0.00 | 9099087.10 | 0.00 | 0.275271E+10 | 0.103177E+11 | 0.00 | 0.63 |
April | 0.392098E+11 | 0.00 | 0.00 | 0.109356E+09 | 0.00 | 0.00 | 0.731722E+11 | 0.00 | 1.15 |
May | 0.532010E+11 | 0.00 | 0.00 | 66405598.07 | 0.00 | 82227152.67 | 0.510816E+11 | 0.00 | 1.07 |
June | 0.432959E+11 | 12729458.05 | 0.00 | 79649980.37 | 0.202852E+09 | 12485799.70 | 0.532507E+11 | 0.00 | 1.33 |
July | 0.339261E+11 | 88619634.27 | 0.00 | 0.100366E+09 | 46444370.32 | 0.00 | 0.584486E+11 | 0.00 | 1.45 |
August | 0.325611E+11 | 0.00 | 0.00 | 0.143421E+09 | 0.00 | 0.00 | 0.716909E+11 | 0.00 | 1.83 |
September | 0.360203E+11 | 0.00 | 0.00 | 0.149676E+09 | 0.00 | 0.00 | 0.783452E+11 | 0.00 | 1.76 |
October | 0.542982E+11 | 0.00 | 0.00 | 66377101.19 | 0.00 | 0.551232E+09 | 0.492218E+11 | 0.00 | 1.01 |
November | 0.627206E+11 | 0.00 | 0.00 | 16877291.48 | 0.00 | 0.603067E+10 | 0.142284E+11 | 0.00 | 0.64 |
December | 0.561034E+11 | 0.00 | 0.00 | 8245034.35 | 0.00 | 0.238570E+11 | 0.666386E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.611723E+12 | 0.101349E+09 | 0.00 | 0.802080E+09 | 0.249296E+09 | 0.504452E+11 | 0.506722E+12 | 0.00 | 1.06 |
Minimum of Months | 0.325611E+11 | 0.00 | 0.00 | 8245034.35 | 0.00 | 0.00 | 0.666386E+10 | 0.00 | 0.57 |
Maximum of Months | 0.768249E+11 | 88619634.27 | 0.00 | 0.149676E+09 | 0.202852E+09 | 0.238570E+11 | 0.783452E+11 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.545792E+11 | 0.00 | 0.00 | 220139.49 | 0.00 | 0.122062E+11 | 0.505614E+09 | 0.00 | 0.66 |
February | 0.499462E+11 | 0.00 | 0.00 | 3405449.10 | 0.00 | 0.541004E+10 | 0.364250E+10 | 0.00 | 0.66 |
March | 0.629006E+11 | 0.00 | 0.00 | 2251713.59 | 0.00 | 0.172514E+10 | 0.249770E+10 | 0.00 | 0.73 |
April | 0.420310E+11 | 0.00 | 0.00 | 45282942.87 | 0.00 | 6560323.41 | 0.302564E+11 | 0.00 | 1.13 |
May | 0.427231E+11 | 0.00 | 0.00 | 48533366.20 | 0.00 | 68763763.94 | 0.346061E+11 | 0.00 | 1.23 |
June | 0.291541E+11 | 0.196298E+09 | 0.00 | 73961065.28 | 30301985.91 | 0.00 | 0.476977E+11 | 0.00 | 1.65 |
July | 0.215487E+11 | 0.100206E+09 | 0.00 | 95325943.04 | 10085094.34 | 0.00 | 0.502476E+11 | 0.00 | 1.76 |
August | 0.245797E+11 | 0.00 | 0.00 | 82126700.29 | 0.00 | 0.00 | 0.445133E+11 | 0.00 | 1.82 |
September | 0.401638E+11 | 0.00 | 0.00 | 38208704.53 | 0.00 | 0.00 | 0.251236E+11 | 0.00 | 1.48 |
October | 0.544743E+11 | 0.00 | 0.00 | 9257255.03 | 0.00 | 0.206415E+09 | 0.809179E+10 | 0.00 | 0.90 |
November | 0.528597E+11 | 0.00 | 0.00 | 510044.20 | 0.00 | 0.570687E+10 | 0.112597E+10 | 0.00 | 0.71 |
December | 0.453975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186896E+11 | 0.00 | 0.00 | 0.65 |
Annual Sum or Average | 0.520358E+12 | 0.296504E+09 | 0.00 | 0.399083E+09 | 40387080.26 | 0.440196E+11 | 0.248308E+12 | 0.00 | 1.12 |
Minimum of Months | 0.215487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 0.629006E+11 | 0.196298E+09 | 0.00 | 95325943.04 | 30301985.91 | 0.186896E+11 | 0.502476E+11 | 0.00 | 1.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277772E+10 | 0.00 | 0.00 | 0.28 |
February | 0.147412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205733E+10 | 0.00 | 0.00 | 0.28 |
March | 0.276647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129239E+10 | 0.00 | 0.00 | 0.30 |
April | 0.262088E+10 | 0.00 | 0.00 | 1091957.62 | 312235.76 | 0.320789E+09 | 0.108134E+10 | 0.00 | 0.40 |
May | 0.276520E+10 | 0.00 | 0.00 | 1953660.82 | 0.00 | 0.151782E+09 | 0.153983E+10 | 0.00 | 0.46 |
June | 0.164274E+10 | 201103.17 | 0.00 | 5242568.68 | 8112474.75 | 995476.38 | 0.343032E+10 | 0.00 | 0.71 |
July | 0.134644E+10 | 2714737.61 | 0.00 | 6143654.20 | 919360.25 | 360334.69 | 0.360095E+10 | 0.00 | 0.77 |
August | 0.159169E+10 | 0.00 | 0.00 | 5478802.10 | 0.00 | 0.00 | 0.306506E+10 | 0.00 | 0.79 |
September | 0.229247E+10 | 0.00 | 0.00 | 2160485.03 | 0.00 | 59626785.03 | 0.140687E+10 | 0.00 | 0.56 |
October | 0.279835E+10 | 0.00 | 0.00 | 9709.64 | 0.00 | 0.722436E+09 | 35233787.49 | 0.00 | 0.35 |
November | 0.175084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173011E+10 | 0.00 | 0.00 | 0.29 |
December | 0.857222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293374E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.231064E+11 | 2915840.79 | 0.00 | 22080838.09 | 9344070.77 | 0.120473E+11 | 0.141596E+11 | 0.00 | 0.46 |
Minimum of Months | 0.857222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.279835E+10 | 2714737.61 | 0.00 | 6143654.20 | 8112474.75 | 0.293374E+10 | 0.360095E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.218783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333660E+10 | 0.00 | 0.00 | 0.60 |
February | 0.248571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245359E+10 | 0.00 | 0.00 | 0.60 |
March | 0.411317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161154E+10 | 0.00 | 0.00 | 0.67 |
April | 0.265884E+10 | 945025.52 | 0.00 | 4119780.96 | 0.00 | 0.164466E+09 | 0.339000E+10 | 0.00 | 0.97 |
May | 0.320345E+10 | 0.00 | 0.00 | 4296638.68 | 0.00 | 0.121322E+09 | 0.332926E+10 | 0.00 | 1.06 |
June | 0.257267E+10 | 145767.05 | 0.00 | 6658095.06 | 11493163.72 | 871114.52 | 0.434069E+10 | 0.00 | 1.48 |
July | 0.183179E+10 | 6228070.76 | 0.00 | 7769414.60 | 1302482.69 | 0.00 | 0.450117E+10 | 0.00 | 1.53 |
August | 0.216796E+10 | 0.00 | 0.00 | 7914326.74 | 0.00 | 0.00 | 0.442860E+10 | 0.00 | 1.72 |
September | 0.255766E+10 | 0.00 | 0.00 | 4845634.06 | 0.00 | 17549816.72 | 0.309482E+10 | 0.00 | 1.30 |
October | 0.352866E+10 | 0.00 | 0.00 | 392405.24 | 0.00 | 0.859588E+09 | 0.647032E+09 | 0.00 | 0.76 |
November | 0.269070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218243E+10 | 0.00 | 0.00 | 0.63 |
December | 0.166777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358024E+10 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.316662E+11 | 7318863.33 | 0.00 | 35996295.34 | 12795646.40 | 0.143282E+11 | 0.237316E+11 | 0.00 | 0.99 |
Minimum of Months | 0.166777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.411317E+10 | 6228070.76 | 0.00 | 7914326.74 | 11493163.72 | 0.358024E+10 | 0.450117E+10 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.434645E+10 | 0.00 | 0.00 | 931494.51 | 0.00 | 0.317900E+10 | 0.907885E+09 | 0.00 | 0.59 |
February | 0.411677E+10 | 0.00 | 0.00 | 1802069.23 | 0.00 | 0.225152E+10 | 0.143993E+10 | 0.00 | 0.62 |
March | 0.621904E+10 | 0.00 | 0.00 | 355546.09 | 0.00 | 0.197905E+10 | 0.398672E+09 | 0.00 | 0.64 |
April | 0.379744E+10 | 0.00 | 0.00 | 9148242.84 | 663948.30 | 0.376244E+09 | 0.656013E+10 | 0.00 | 1.10 |
May | 0.510530E+10 | 0.00 | 0.00 | 5763542.67 | 0.00 | 0.354787E+09 | 0.468322E+10 | 0.00 | 1.04 |
June | 0.452862E+10 | 235736.88 | 0.00 | 7313960.47 | 17250630.86 | 17603896.86 | 0.506544E+10 | 0.00 | 1.32 |
July | 0.340619E+10 | 2010944.96 | 0.00 | 9663372.06 | 5386640.28 | 780865.05 | 0.592991E+10 | 0.00 | 1.45 |
August | 0.334599E+10 | 0.00 | 0.00 | 13268914.69 | 0.00 | 0.00 | 0.715517E+10 | 0.00 | 1.80 |
September | 0.338480E+10 | 0.00 | 0.00 | 13174482.45 | 0.00 | 3372820.54 | 0.739606E+10 | 0.00 | 1.66 |
October | 0.454912E+10 | 0.00 | 0.00 | 4742708.64 | 0.00 | 0.870862E+09 | 0.379139E+10 | 0.00 | 0.93 |
November | 0.458944E+10 | 0.00 | 0.00 | 812396.95 | 0.00 | 0.216623E+10 | 0.709099E+09 | 0.00 | 0.62 |
December | 0.318421E+10 | 0.00 | 0.00 | 315350.02 | 0.00 | 0.441595E+10 | 0.286736E+09 | 0.00 | 0.57 |
Annual Sum or Average | 0.505734E+11 | 2246681.84 | 0.00 | 67292080.61 | 23301219.44 | 0.156154E+11 | 0.443236E+11 | 0.00 | 1.03 |
Minimum of Months | 0.318421E+10 | 0.00 | 0.00 | 315350.02 | 0.00 | 0.00 | 0.286736E+09 | 0.00 | 0.57 |
Maximum of Months | 0.621904E+10 | 2010944.96 | 0.00 | 13268914.69 | 17250630.86 | 0.441595E+10 | 0.739606E+10 | 0.00 | 1.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.316373E+10 | 0.00 | 0.00 | 1828.17 | 0.00 | 0.305373E+10 | 13992147.02 | 0.00 | 0.68 |
February | 0.353754E+10 | 0.00 | 0.00 | 119319.47 | 0.00 | 0.184111E+10 | 0.193599E+09 | 0.00 | 0.68 |
March | 0.509770E+10 | 0.00 | 0.00 | 100481.83 | 0.00 | 0.122083E+10 | 0.141932E+09 | 0.00 | 0.75 |
April | 0.416055E+10 | 0.00 | 0.00 | 4046265.80 | 499285.37 | 0.171396E+09 | 0.271282E+10 | 0.00 | 1.11 |
May | 0.423940E+10 | 0.00 | 0.00 | 4287956.41 | 0.00 | 0.147691E+09 | 0.319525E+10 | 0.00 | 1.21 |
June | 0.325822E+10 | 15358991.25 | 0.00 | 6888309.21 | 2468127.15 | 0.00 | 0.445437E+10 | 0.00 | 1.66 |
July | 0.237790E+10 | 2210203.89 | 0.00 | 8786532.84 | 3727197.67 | 0.00 | 0.491827E+10 | 0.00 | 1.76 |
August | 0.275462E+10 | 0.00 | 0.00 | 7423168.57 | 0.00 | 0.00 | 0.417048E+10 | 0.00 | 1.82 |
September | 0.399148E+10 | 0.00 | 0.00 | 3330753.34 | 0.00 | 13157581.10 | 0.217836E+10 | 0.00 | 1.43 |
October | 0.440003E+10 | 0.00 | 0.00 | 683082.89 | 0.00 | 0.751616E+09 | 0.629666E+09 | 0.00 | 0.88 |
November | 0.368823E+10 | 0.00 | 0.00 | 3101.75 | 0.00 | 0.178912E+10 | 18499524.53 | 0.00 | 0.71 |
December | 0.230282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361635E+10 | 0.00 | 0.00 | 0.67 |
Annual Sum or Average | 0.429722E+11 | 17569195.15 | 0.00 | 35670800.27 | 6694610.18 | 0.126050E+11 | 0.226272E+11 | 0.00 | 1.12 |
Minimum of Months | 0.230282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
Maximum of Months | 0.509770E+10 | 15358991.25 | 0.00 | 8786532.84 | 3727197.67 | 0.361635E+10 | 0.491827E+10 | 0.00 | 1.82 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2980201.11 | 0.00 | 0.00 | 0.637618E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7272853.98 | 0.00 | 0.00 | 0.561962E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 12990704.77 | 0.00 | 0.00 | 0.623975E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 16991950.69 | 0.00 | 0.00 | 0.466920E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 3929864.55 | 0.00 | 0.00 | 0.473309E+09 | 0.00 | 0.29 |
June | 0.00 | 107050.50 | 0.00 | 8407061.65 | 0.00 | 0.00 | 0.324917E+09 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 12317308.96 | 0.00 | 0.00 | 0.231472E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 18245558.85 | 0.00 | 0.00 | 0.226895E+09 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 3799943.84 | 0.00 | 0.00 | 0.313529E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 7843803.38 | 0.00 | 0.00 | 0.462589E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11622605.35 | 0.00 | 0.00 | 0.530756E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16040070.92 | 0.00 | 0.00 | 0.612711E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 107050.50 | 0.00 | 0.122442E+09 | 0.00 | 0.00 | 0.546665E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2980201.11 | 0.00 | 0.00 | 0.226895E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 107050.50 | 0.00 | 18245558.85 | 0.00 | 0.00 | 0.637618E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28001991.98 | 0.00 | 0.00 | 18045104.35 | 0.00 | 0.00 | 0.636034E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 59824797.11 | 0.00 | 0.00 | 0.563207E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.113297E+09 | 0.00 | 0.00 | 0.625589E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.157035E+09 | 0.00 | 0.00 | 0.468228E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 32325007.03 | 0.00 | 0.00 | 0.474288E+10 | 0.00 | 0.29 |
June | 0.00 | 981704.67 | 0.00 | 76978039.70 | 0.00 | 0.00 | 0.326054E+10 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 0.115111E+09 | 0.00 | 0.00 | 0.232461E+10 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 0.171717E+09 | 0.00 | 0.00 | 0.228015E+10 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 31649600.80 | 0.00 | 0.00 | 0.315670E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 66540639.14 | 0.00 | 0.00 | 0.464028E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 99971179.86 | 0.00 | 0.00 | 0.532321E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.139429E+09 | 0.00 | 0.00 | 0.614674E+10 | 0.00 | 0.28 |
Annual Sum or Average | 28001991.98 | 981704.67 | 0.00 | 0.108192E+10 | 0.00 | 0.00 | 0.548057E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 18045104.35 | 0.00 | 0.00 | 0.228015E+10 | 0.00 | 0.28 |
Maximum of Months | 28001991.98 | 981704.67 | 0.00 | 0.171717E+09 | 0.00 | 0.00 | 0.636034E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194839E+09 | 0.00 | 0.00 | 778540.56 | 0.00 | 0.00 | 0.441587E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4957267.23 | 0.00 | 0.00 | 0.564294E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 10342756.04 | 0.00 | 0.00 | 0.626604E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15221537.69 | 0.00 | 0.00 | 0.468705E+09 | 0.00 | 0.29 |
May | 1414750.92 | 0.00 | 0.00 | 2815513.37 | 0.00 | 0.00 | 0.473495E+09 | 0.00 | 0.29 |
June | 0.00 | 101817.22 | 0.00 | 7489034.48 | 0.00 | 0.00 | 0.326533E+09 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 11372276.65 | 0.00 | 0.00 | 0.232783E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 16994261.71 | 0.00 | 0.00 | 0.228375E+09 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 2794619.05 | 0.00 | 0.00 | 0.316997E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 5817632.75 | 0.00 | 0.00 | 0.465441E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 8985562.99 | 0.00 | 0.00 | 0.533581E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 12835458.32 | 0.00 | 0.00 | 0.615826E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.196254E+09 | 101817.22 | 0.00 | 0.100404E+09 | 0.00 | 0.00 | 0.529422E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 778540.56 | 0.00 | 0.00 | 0.228375E+09 | 0.00 | 0.28 |
Maximum of Months | 0.194839E+09 | 101817.22 | 0.00 | 16994261.71 | 0.00 | 0.00 | 0.626604E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.206281E+09 | 0.00 | 0.00 | 0.147257E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.395066E+09 | 0.00 | 0.00 | 0.126177E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.667846E+09 | 0.00 | 0.00 | 0.139641E+11 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.00 | 0.843175E+09 | 0.00 | 0.00 | 0.102528E+11 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.00 | 0.214833E+09 | 0.00 | 0.00 | 0.102049E+11 | 0.00 | 0.33 |
June | 0.00 | 5348095.41 | 0.00 | 0.417849E+09 | 0.00 | 0.00 | 0.672915E+10 | 0.00 | 0.34 |
July | 0.00 | 34251.88 | 0.00 | 0.604494E+09 | 0.00 | 0.00 | 0.461740E+10 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.00 | 0.898476E+09 | 0.00 | 0.00 | 0.440085E+10 | 0.00 | 0.34 |
September | 0.00 | 0.00 | 0.00 | 0.208648E+09 | 0.00 | 0.00 | 0.654737E+10 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.00 | 0.414808E+09 | 0.00 | 0.00 | 0.989927E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.602618E+09 | 0.00 | 0.00 | 0.115688E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.825504E+09 | 0.00 | 0.00 | 0.137323E+11 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 5382347.29 | 0.00 | 0.629960E+10 | 0.00 | 0.00 | 0.119260E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.206281E+09 | 0.00 | 0.00 | 0.440085E+10 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 5348095.41 | 0.00 | 0.898476E+09 | 0.00 | 0.00 | 0.147257E+11 | 0.00 | 0.34 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:03:29
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.160338E+12 | 0.658956E+10 | 0.00 | 0.196923E+13 | 0.531481E+12 |
February | 0.253807E+12 | 0.938263E+10 | 0.00 | 0.178504E+13 | 0.820587E+12 |
March | 0.299094E+12 | 0.581864E+10 | 0.00 | 0.207382E+13 | 0.129896E+13 |
April | 0.758201E+12 | 0.724857E+10 | 0.00 | 0.227248E+13 | 0.170408E+13 |
May | 0.935070E+12 | 0.172283E+11 | 0.00 | 0.226553E+13 | 0.595785E+12 |
June | 0.935894E+12 | 0.135287E+11 | 0.00 | 0.223380E+13 | 0.117093E+13 |
July | 0.943753E+12 | 0.129058E+11 | 0.00 | 0.223789E+13 | 0.176792E+13 |
August | 0.774416E+12 | 0.957061E+10 | 0.00 | 0.217447E+13 | 0.226644E+13 |
September | 0.578255E+12 | 0.102267E+11 | 0.00 | 0.227743E+13 | 0.795341E+12 |
October | 0.273188E+12 | 0.100648E+11 | 0.00 | 0.213568E+13 | 0.925825E+12 |
November | 0.128495E+12 | 0.122506E+11 | 0.00 | 0.194508E+13 | 0.126119E+13 |
December | 0.690231E+11 | 0.166080E+11 | 0.00 | 0.183264E+13 | 0.170295E+13 |
Annual Sum or Average | 0.610953E+13 | 0.131423E+12 | 0.00 | 0.252031E+14 | 0.148415E+14 |
Minimum of Months | 0.690231E+11 | 0.581864E+10 | 0.00 | 0.178504E+13 | 0.531481E+12 |
Maximum of Months | 0.943753E+12 | 0.172283E+11 | 0.00 | 0.227743E+13 | 0.226644E+13 |