Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820

Simulation Timestamp: 2023-10-16 09:03:25


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 34930.34 754.10 754.10
Net Site Energy 34930.34 754.10 754.10
Total Source Energy 109412.95 2362.09 2362.09
Net Source Energy 109412.95 2362.09 2362.09


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 22.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 6662.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3705.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 670.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1941.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2768.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1329.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1974.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19163.14
Humidification 82.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.57
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 559.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 34348.76 581.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21473.87
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 22.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 6662.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 3705.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 670.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5871.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 87.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2768.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 1329.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1974.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19163.14
Humidification General 82.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.57
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 559.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 22.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 6662.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 3705.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 670.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1941.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2768.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 1329.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1974.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19163.14
Humidification Unassigned 82.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.57
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 559.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 94.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 276.71 12.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.46
Other 370.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 741.55 12.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.46


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 94.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 276.71 12.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.46
Other 370.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 741.55 12.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.46


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 34348.759 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 34348.759 100.00
     
Total On-Site and Utility Electric Sources 34348.759 100.00
Total Electricity End Uses 34348.759 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 21473.87 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 21473.87 100.00
Total Water End Uses 21473.87 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 1069.17
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03
RunPeriod RUNPERIOD 1
Weather File New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Latitude [deg] 28.58
Longitude [deg] 77.20
Elevation [m] 216.00
Time Zone 5.50
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 9.3279 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.3279 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 9.3279 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.3279 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 16.0861 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 16.0861 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 16.0861 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 9.3279 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.3913 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.3913 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.3279 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 9.3279 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 9.3279 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 9.3279 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 9.3279 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 9.3279 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 9.3279 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 9.3279 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 9.3279 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 9.3279 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 9.3279 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 9.3279 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 9.3279 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 9.3279 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 9.3279 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 9.3279 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 16.0861 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 16.0861 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 16.0861 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 9.3279 18.58 484.4232  
Total 46320.38             9.3913 9.29 17.8789  
Conditioned Total 46320.38             9.3913 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.8860 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 07-AUG-15:20 02-JAN-06:19 - - - - - - - - - - 19-APR-15:09
Heating 0.00 207455.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 573986.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 316816.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 794004.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 84885.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 226054.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 69995.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 93058.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 21664.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2158800.56 229119.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 207455.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 573986.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 316816.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 5451.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 226054.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 69995.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 93058.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 21664.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 23.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 21101.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 11734.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2124.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48180.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6150.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8767.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 4210.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 6252.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 260.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 606.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 108782.52 630.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 455.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 253.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 45.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 189.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 90.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 134.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 5.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 13.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2348.48 13.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 455.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 253.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 45.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 189.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 90.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 134.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 5.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 13.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2348.48 13.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 6.00
DATACENTER_BOT_ZN_6 DIRECT AIR 0.490269
DATACENTER_MID_ZN_6 DIRECT AIR 4.67
DATACENTER_TOP_ZN_6 DIRECT AIR 0.469775
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 21.97
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 6.30 0.301693 0.312000 1.97 0.804514 0.500000 0.001263 0.000169 1.97 12.80 0.008000
CORE_MID VAV BOX COMPONENT 59.79 0.318117 0.324000 19.37 0.848313 0.500000 0.001198 0.003101 19.37 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 6.13 0.310288 0.327000 2.00 0.827433 0.500000 0.001228 0.000549 2.00 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.22 0.196091 0.300000 0.365373 0.522908 0.500000 0.001943 0.000046 0.365373 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.949727 0.162052 0.300000 0.284918 0.432138 0.500000 0.002351 0.000037 0.284918 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.24 0.192743 0.300000 0.371726 0.513982 0.500000 0.001977 0.000063 0.371726 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.24 0.124468 0.300000 0.370950 0.331916 0.500000 0.003061 0.000033 0.370950 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 11.81 0.202280 0.300000 3.54 0.539413 0.500000 0.001884 0.001070 3.74 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 9.80 0.157011 0.300000 2.94 0.418696 0.500000 0.002427 0.000752 2.94 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 11.91 0.200493 0.300000 3.57 0.534649 0.500000 0.001900 0.001070 3.74 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 10.48 0.146873 0.300000 3.14 0.391663 0.500000 0.002594 0.000702 3.14 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.38 0.172948 0.300000 0.414263 0.461196 0.500000 0.002203 0.000155 0.540259 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.05 0.146938 0.300000 0.314225 0.391835 0.500000 0.002593 0.000102 0.355715 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.38 0.172587 0.300000 0.415140 0.460232 0.500000 0.002208 0.000155 0.540265 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.18 0.130420 0.300000 0.354021 0.347788 0.500000 0.002921 0.000096 0.354021 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 19305.91 0.000169 389.19
CORE_MID VAV BOX REHEAT COIL 354464.71 0.003101 7814.76
CORE_TOP VAV BOX REHEAT COIL 62750.60 0.000549 1623.88
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 5254.70 0.000046 111.03
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 4232.59 0.000037 89.87
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 7182.26 0.000063 160.18
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 3784.43 0.000033 76.59
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 122321.44 0.001070 3228.47
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 85910.31 0.000752 2161.68
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 122322.11 0.001070 3228.48
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 80227.15 0.000702 1925.62
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 17668.25 0.000155 466.11
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 11632.41 0.000102 306.87
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 17668.43 0.000155 466.11
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 11025.84 0.000096 284.71
VAV_BOT WITH REHEAT HEATING COIL 23748.16 0.000208 415.27
VAV_MID WITH REHEAT HEATING COIL 157846.57 0.001381 2799.19
VAV_TOP WITH REHEAT HEATING COIL 12003.85 0.000105 215.28
CAV_BAS HEATING COIL 274173.69 0.002399 6235.34
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.47 3.36 10.95 3.36 10.32 10.32 0.300000 0.325609 10.32
VAV_MID WITH REHEAT 51.89 32.57 103.79 32.57 97.66 97.66 0.300000 0.333517 97.66
VAV_TOP WITH REHEAT 5.56 3.50 11.12 3.64 11.03 11.03 0.300000 0.329863 11.03
CAV_BAS 6.00 6.00 6.00 6.00 6.00 6.00 1.00 1.00 6.00
AIRLOOP DATACENTER BASEMENT 21.97 21.97 21.97 21.97 21.97 21.97 1.00 0.999988 21.97
AIRLOOP DATACENTER BOT 0.490269 0.490269 0.490269 0.490269 0.490269 0.490269 1.00 1.00 0.490269
AIRLOOP DATACENTER MID 4.67 4.67 4.67 4.67 4.67 4.67 1.00 1.00 4.67
AIRLOOP DATACENTER TOP 0.469775 0.469775 0.469775 0.469775 0.469775 0.469775 1.00 1.00 0.469775
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 10.32  
VAV_MID WITH REHEAT_OA_CONTROLLER 97.66  
VAV_TOP WITH REHEAT_OA_CONTROLLER 11.03  
CAV_BAS_OA_CONTROLLER 6.00 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 21.97 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.490269 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.67 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.469775 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 28.58 6.67 11.00 0.007797 0.007000 241356.59 0.010268 10.32
VAV_MID WITH REHEAT COOLING COIL 29.01 6.67 10.99 0.007874 0.007000 2357913.58 0.100311 97.66
VAV_TOP WITH REHEAT COOLING COIL 28.15 6.67 11.00 0.007744 0.007000 250531.59 0.010658 11.03
CAV_BAS COOLING COIL 27.43 6.67 11.38 0.007827 0.007000 129929.42 0.005527 6.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 10.32
VAV_MID WITH REHEAT FAN 97.66
VAV_TOP WITH REHEAT FAN 11.03
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.010268 0.000046
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000208  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.100311 0.000005
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.001381  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.010658 0.000045
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000105  
CAV_BAS_COOLC_CONTROLLER 0.005527 0.000086
CAV_BAS_HEATC_CONTROLLER 0.002399  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 6.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 21.97 452498.18 281793.92 0.011082
AIRLOOP DATACENTER BOT COOLING COIL 0.490269 9816.00 6187.94 0.000240
AIRLOOP DATACENTER MID COOLING COIL 4.67 93579.44 58964.62 0.002292
AIRLOOP DATACENTER TOP COOLING COIL 0.469775 9667.57 6011.05 0.000237
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.97 21.97 21.97 21.97 452498.18 452498.18 13450.69 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.490269 0.490269 0.490269 0.490269 9816.00 9816.00 621.37 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.67 4.67 4.67 4.67 93579.44 93579.44 6213.66 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.469775 0.469775 0.469775 0.469775 9667.57 9667.57 621.37 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 21.97
AIRLOOP DATACENTER BOT SUPPLY FAN 0.490269
AIRLOOP DATACENTER MID SUPPLY FAN 4.67
AIRLOOP DATACENTER TOP SUPPLY FAN 0.469775
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 21.97 452498.18 0.011082
AIRLOOP DATACENTER BOT HEATING COIL 0.490269 9816.00 0.000240
AIRLOOP DATACENTER MID HEATING COIL 4.67 93579.44 0.002292
AIRLOOP DATACENTER TOP HEATING COIL 0.469775 9667.57 0.000237
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 13450.69
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 621.37
AIRLOOP DATACENTER MID_SUPPHEATCOIL 6213.66
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 621.37
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000048 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.126765 26121.50  
HEATSYS1 PUMP 0.012191 3671.44 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.126765 15.21
HEATSYS1 0.012191 1.46
COOLSYS1_SUPPLY 0.126765 15.21
SINGLE WATER PLANT LOOP 0.013851 1.66
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.126765 0.126765 532094.85 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 1393523.42 1393523.42 0.012191
CENTRAL BOILER 570524.21 559477.15 0.013851
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.126765 18084.79
PLANT CIRC PUMP 0.013851 3532.58
SWHSYS1 PUMP 0.000440 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.126765 0.064005 1508197.93 1515297.13 0.074986
COOLSYS1 CHILLER2 0.126765 0.064005 1508197.93 1515297.13 0.074986
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013851 139666.47 57235.65 69833.23 7879.72 21206.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.149973 18.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.149973 45168.57
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 59.14 1797868.51 11.83 224733.56
TOWERWATERSYS COOLTOWER 2 59.14 1797868.51 11.83 224733.56
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.077887
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 25.10 19.60 14.50 13.40 17.00 22.40 29.10 33.00 33.60 31.70 30.00 28.70


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 28.58 77.20 5.50 216.00 98757 1.1738


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 24.84 20.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 9.328 4.842 0.000 0.000 0.000 0.000 14.170 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 16.086 215.299 0.000 0.000 0.000 0.000 231.385 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 16.086 215.299 0.000 0.000 0.000 0.000 231.385 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 16.086 215.299 0.000 0.000 0.000 0.000 231.385 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 9.328 484.423 0.000 0.000 0.000 0.000 493.751 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 25926.330 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25926.330
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 23283.667 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 23283.667
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 23283.667 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 23283.667
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 23283.667 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 23283.667
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2923.497 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.497
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2923.561 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.561
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2923.497 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.497
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2923.561 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.561
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2923.497 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.497
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2923.561 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.561
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 7310.116 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 7310.116
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 582.361 16.086 298.861 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 582.361
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 582.361 16.086 298.861 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 582.361
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 582.361 16.086 298.861 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 582.361


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.743 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.656 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 2.135 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.4064
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.4365
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.3009
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
47 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
48 1 -21.915918 0.11588205 -6.3286394 0.20197014
49 0 21.365777 0.10835518 5.5011278  
50 9 0.76055735E-15 0.55973061E-16 -0.11090261E-09 -0.43371185E-17
51 8 0.16390423E-07 0.22068143E-12 0.31740643E-03 -0.18636477E-09
52 7 -0.10429999E-01 0.12271718E-07 -0.20474149E-01 0.11859286E-03
53 6 0.35611320 0.43955117E-05 0.42991281 -0.41673803E-02
54 5 -4.7098961 0.16827687E-03 -4.1162358 0.57223947E-01
55 4 30.875684 0.14076848E-02 20.167480 -0.39388153
56 3 -106.69740 0.31291265E-02 -53.106522 1.4497707
57 2 192.63914 0.17911574E-02 75.570394 -2.8293896
58 1 -169.50392 0.19431750E-03 -54.592911 2.7164834
59 0 57.057407 0.11257899E-05 15.674734  
60 9 0.11474244E-14 0.54197419E-16 -0.11508650E-09 -0.49945851E-17
61 8 0.16984416E-07 0.21156325E-12 0.32425024E-03 -0.19311866E-09
62 7 -0.10636353E-01 0.11664670E-07 -0.20772028E-01 0.12093918E-03
63 6 0.36172330 0.41637772E-05 0.43474562 -0.42335086E-02
64 5 -4.7646824 0.15893927E-03 -4.1535939 0.57903236E-01
65 4 31.118254 0.13261305E-02 20.314042 -0.39710182
66 3 -107.21418 0.29411649E-02 -53.396504 1.4572354
67 2 193.15212 0.16802168E-02 75.835339 -2.8375342
68 1 -169.69371 0.18194848E-03 -54.668081 2.7198097
69 0 57.057407 0.10520719E-05 15.660794  
70 9 0.66246833E-15 0.57738042E-16 -0.92036509E-10 -0.27018983E-17
71 8 0.13701644E-07 0.25726543E-12 0.28527343E-03 -0.15579243E-09
72 7 -0.94571194E-02 0.14940887E-07 -0.19068097E-01 0.10753086E-03
73 6 0.32965778 0.54453531E-05 0.40701455 -0.38555430E-02
74 5 -4.4514676 0.21157254E-03 -3.9387765 0.54019785E-01
75 4 29.731016 0.17930056E-02 19.470280 -0.37868589
76 3 -104.25747 0.40308508E-02 -51.726693 1.4145289
77 2 190.21562 0.23301583E-02 74.311741 -2.7909129
78 1 -168.60668 0.25508611E-03 -54.239505 2.7007581
79 0 57.057407 0.14924561E-05 15.743350  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.5047_SHGC_EAST_0.25 35 1 VerySmooth 2.869 2.869 1.000 0.251    
2 WINDOW_U_0.5047_SHGC_SOUTH_0.25 36 1 VerySmooth 2.869 2.869 1.000 0.251    
3 WINDOW_U_0.5047_SHGC_WEST_0.25 37 1 VerySmooth 2.869 2.869 1.000 0.251    
4 WINDOW_U_0.5047_SHGC_NORTH_0.25 38 1 VerySmooth 2.869 2.869 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   1.90891E-002 0.16139 0.61055 0.61055 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10708 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   1.90891E-002 0.16139 0.61055 0.61055 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10708 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   1.90891E-002 0.16139 0.61055 0.61055 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10708 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   1.90891E-002 0.16139 0.61055 0.61055 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10708 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.496 7.5104E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6556E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6567E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8034E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8043E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1458E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1465E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2452E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6818E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7553E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8248E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8865E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1628E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2127E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2574E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2891E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.3694E-002
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0906E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.1712E-002
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2798E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.0286E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2382E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6042E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.1095E-003
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6871E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7813E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8306E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9145E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1681E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2329E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2577E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2900E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6555E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6568E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8033E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8044E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1458E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1467E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2451E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.7734E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.9022E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6487E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7820E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.5073E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5748E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1302E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1521E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.2792E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.5967E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.1179E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.4553E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.3343E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.3602E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6787E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 9.9865E-003
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.7433E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7949E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6113E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.6492E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.4871E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5031E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1303E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1525E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2193E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2205E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0482E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0492E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.2927E-004
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.2997E-004
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2452E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2462E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3126E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0702E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1232E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.4683E-004
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.8505E-004
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2577E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2900E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8970E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0736E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4831E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 8.2182E-003
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4618E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 5.7927E-003
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6042E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.1067E-003
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2442E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3101E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0678E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1184E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.4273E-004
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.7257E-004
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2574E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2891E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2192E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2203E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0481E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0490E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.2918E-004
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.2973E-004
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2451E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3719E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4257E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1617E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.2007E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1392E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1537E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1303E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1525E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.5554E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.3237E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.2515E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.1301E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6176E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.0860E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6787E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 9.9865E-003
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3958E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4967E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1920E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.2913E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1581E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.2174E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1302E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1521E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 7.2526E-002
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.2005E-002
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 7.8513E-002
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.4500E-002
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 6.3253E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.1602E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.0133E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.4574E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.7645E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.2088E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.5896E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.0428E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.7878E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.9148E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.0820E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.4729E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.2887E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.5929E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8364E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.2718E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8071E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 9.9091E-003
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.0133E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.4571E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.9784E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.8510E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.6470E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.6146E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.0155E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.5644E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.0820E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.4729E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 7.2523E-002
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.2071E-002
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 7.8524E-002
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.4578E-002
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 6.3293E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.1668E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.0168E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.4602E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.7636E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.2110E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.5896E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.0450E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.7898E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.9182E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.0854E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.4757E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.2861E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.5936E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8346E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.2724E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8081E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 9.9234E-003
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.0168E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.4599E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.9768E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.8524E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.6462E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.6160E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.0169E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.5670E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.0854E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.4757E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 80997.47746 80997.47746 6.00031 6.00031 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 34.82200 9.14597E-003 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016   00:10:00 6.30000 6.07234E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 85109.98323 85109.98323 6.30457 6.30457 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 34.82200 9.14597E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782   00:10:00 6.30000 6.07234E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 807330.69511 807330.69511 59.79062 59.79062 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 34.82200 9.14597E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 164331.48709 164331.48709 7.04256 10.77825 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 82761.94199 82761.94199 6.12994 6.12994 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 34.82200 9.14597E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 43076.99797 43076.99797 1.87236 1.87236 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 16295.18124 16295.18124 1.21791 1.21791 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:20:00 41.80600 9.15758E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 1670.32548 1670.32548 7.25146E-002 0.13533 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 12707.01997 12707.01997 0.94973 0.94973 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:10:00 38.55650 9.15215E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 1437.36817 1437.36817 6.21895E-002 8.72129E-002 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 16578.53304 16578.53304 1.23909 1.23909 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 42.00000 9.15790E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 3534.94656 3534.94656 0.15294 0.15294 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 16544.01509 16544.01509 1.23650 1.23650 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:20:00 41.15933 9.15650E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 149.21061 149.21061 6.54944E-003 8.72129E-002 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 157963.51643 157963.51643 11.80645 11.80645 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00 41.70900 9.15741E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 85655.61543 85655.61543 3.73659 3.73659 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 131147.79722 131147.79722 9.80218 9.80218 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:20:00 38.79900 9.15255E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 57054.55283 57054.55283 2.48932 2.48932 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 159374.32940 159374.32940 11.91190 11.91190 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:10:00 42.00000 9.15790E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 85656.08753 85656.08753 3.73661 3.73661 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 140200.19665 140200.19665 10.47875 10.47875 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 41.03000 9.15628E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 49381.77448 49381.77448 2.15288 2.15288 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 18475.28620 18475.28620 1.38088 1.38088 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00 41.61200 9.15725E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 12366.35462 12366.35462 0.54026 0.54026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 14013.77129 14013.77129 1.04742 1.04742 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:40:00 39.28400 9.15337E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 8141.55349 8141.55349 0.35572 0.35572 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 18514.36401 18514.36401 1.38380 1.38380 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:40:00 42.00000 9.15790E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 12366.47583 12366.47583 0.54026 0.54026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 15788.63614 15788.63614 1.18007 1.18007 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:20:00 41.15933 9.15650E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 7551.69961 7551.69961 0.32985 0.32985 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8317.57586 8317.57586 0.49027 0.49027 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 32.36467 9.14193E-003 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 6.30000 6.07234E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 79223.02557 79223.02557 4.66970 4.66970 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 32.36467 9.14193E-003 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632   00:10:00 6.30000 6.07234E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7969.88615 7969.88615 0.46978 0.46978 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 32.36467 9.14193E-003 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 6.30000 6.07234E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 372677.23982 372677.23982 21.96910 21.96910 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:00:00 33.17300 9.14325E-003 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839   00:10:00 6.30000 6.07234E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 185614.19 10.31912 10.31912 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 11810.70 1.54052 1.54052 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1743599.86 97.66206 97.66206 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 175518.16 22.89365 22.89365 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00
5 VAV_TOP WITH REHEAT Cooling Sensible 199321.47 11.03019 11.03019 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 19399.83 3.63846 3.63846 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 12:00:00
7 CAV_BAS Cooling Sensible 95111.21 6.00031 6.00031 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
8 CAV_BAS Heating Sensible 47704.73 1.20016 1.20016 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 373427.12 21.96936 21.96936 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 13450.69 0.33839 0.33839 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8310.31 0.49027 0.49027 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 621.37 1.56323E-002 1.56323E-002 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 79200.80 4.66970 4.66970 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 6213.66 0.15632 0.15632 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 8121.28 0.46978 0.46978 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 621.37 1.56323E-002 1.56323E-002 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.00031
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.30457
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30169
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31200
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.96703
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.80451
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.26287E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.68897E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.96703
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19305.91256
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.68897E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 389.19204
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 59.79062
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31812
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32400
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 19.37216
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.84831
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.19767E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.10101E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 19.37216
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 354464.71433
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.10101E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7814.75718
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.12994
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31029
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32700
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.00449
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.82743
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.22789E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.48970E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.00449
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 62750.59959
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.48970E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1623.88468
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.21791
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19609
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.36537
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52291
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.94298E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.59704E-005
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.36537
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5254.69755
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.59704E-005
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 111.02922
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.94973
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16205
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.28492
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.43214
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.35110E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.70286E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.28492
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4232.59349
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.70286E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 89.87477
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.23909
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19274
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.37173
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51398
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.97672E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.28335E-005
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.37173
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7182.25802
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.28335E-005
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 160.17985
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.23650
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12447
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.37095
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33192
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.06102E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.31079E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.37095
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3784.43454
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.31079E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 76.58780
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.80645
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20228
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.54194
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53941
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.88353E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.07012E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.73659
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 122321.44301
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.07012E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3228.46535
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.80218
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15701
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.94065
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.41870
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.42658E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.51581E-004
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.94065
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 85910.30719
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.51581E-004
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2161.68315
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.91190
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20049
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.57357
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53465
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.90031E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.07013E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.73661
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 122322.11399
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.07013E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3228.48315
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.47875
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14687
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.14363
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39166
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.59407E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.01862E-004
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.14363
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 80227.14680
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.01862E-004
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1925.62373
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.38088
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17295
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.41426
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.46120
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.20297E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.54570E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.54026
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17668.25253
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.54570E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 466.10897
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.04742
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14694
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.31422
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39183
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.59293E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.01765E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.35572
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11632.41214
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.01765E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 306.86877
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.38380
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17259
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.41514
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.46023
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.20758E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.54571E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.54026
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17668.42545
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.54571E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 466.11354
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.18007
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13042
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.35402
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34779
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.92132E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.64588E-005
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.35402
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11025.83731
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.64588E-005
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 284.70665
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.49027
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.66970
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.46978
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.96910
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.47390
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.35999
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.94780
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.35999
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.31912
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.31912
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.32561
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 51.89495
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 32.57195
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 103.78990
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 32.57195
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 97.66206
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 97.66206
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.33352
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.56105
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.50214
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.12210
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.63846
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 11.03019
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 11.03019
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.32986
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.00031
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 6.00031
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 6.00031
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 6.00031
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 6.00031
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 6.00031
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.96910
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.96910
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.96910
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.96910
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.96936
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.96936
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.49027
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.49027
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.49027
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.49027
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.49027
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.49027
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.66970
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.66970
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.66970
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.66970
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.66970
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.66970
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.46978
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.46978
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.46978
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.46978
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.46978
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.46978
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.31912
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 97.66206
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 11.03019
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 6.00031
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.96936
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.49027
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.66970
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.46978
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.31912
289 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 28.58048
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.00351
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.79700E-003
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 241356.59277
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.02679E-002
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.31912
297 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 23748.15990
298 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.07759E-004
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 415.27267
300 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.31912
301 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.02679E-002
302 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.63768E-005
303 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.07759E-004
304 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 97.66206
305 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 29.00842
306 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.99417
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.87408E-003
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2357913.57540
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 0.10031
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 97.66206
313 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 157846.56772
314 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.38091E-003
315 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2799.18938
316 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 97.66206
317 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 0.10031
318 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.74714E-006
319 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.38091E-003
320 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 11.03019
321 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 28.14853
322 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
323 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.00334
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.74381E-003
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 250531.58737
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.06582E-002
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 11.03019
329 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 12003.85018
330 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.05015E-004
331 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 215.27776
332 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 11.03019
333 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.06582E-002
334 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.46784E-005
335 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.05015E-004
336 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 6.00031
337 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
338 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 27.43335
339 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
340 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.38288
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.82714E-003
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 129929.42170
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.52750E-003
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.00031
346 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 274173.69394
347 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.39859E-003
348 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 6235.33659
349 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 6.00031
350 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.52750E-003
351 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 8.61494E-005
352 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.39859E-003
353 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.96936
354 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
355 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 21.96936
356 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 452498.17935
357 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 281793.92302
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.10817E-002
359 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.96936
360 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.96936
361 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.96936
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.96936
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 452498.17935
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 452498.17935
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 13450.69260
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
367 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.96936
368 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 21.96936
369 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 452498.17935
370 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.10817E-002
371 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 13450.69260
372 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 4.79680E-005
373 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
374 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
375 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
376 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.49027
377 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
378 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.49027
379 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9815.99603
380 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6187.93703
381 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.40393E-004
382 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.49027
383 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.49027
384 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.49027
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.49027
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9815.99603
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9815.99603
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 621.36627
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
390 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.49027
391 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.49027
392 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9815.99603
393 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.40393E-004
394 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 621.36627
395 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.66970
396 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
397 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.66970
398 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 93579.43888
399 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 58964.61639
400 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.29175E-003
401 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.66970
402 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.66970
403 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.66970
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.66970
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 93579.43888
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 93579.43888
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 6213.66275
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
409 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.66970
410 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.66970
411 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 93579.43888
412 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.29175E-003
413 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 6213.66275
414 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.46978
415 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
416 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.46978
417 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9667.56989
418 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6011.05370
419 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.36758E-004
420 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.46978
421 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.46978
422 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.46978
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.46978
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9667.56989
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9667.56989
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 621.36627
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
428 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.46978
429 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.46978
430 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9667.56989
431 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.36758E-004
432 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 621.36627
433 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.12676
434 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 26121.49654
435 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.12676
436 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 15.21176
437 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.12676
438 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.12676
439 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 532094.85308
440 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
441 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.21912E-002
442 PlantLoop HEATSYS1 Plant Loop Volume [m3] 1.46294
443 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.21912E-002
444 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 3671.43924
445 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
446 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 1393523.42025
447 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1393523.42000
448 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.21912E-002
449 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.12676
450 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 15.21176
451 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 0.12676
452 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 18084.79320
453 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12676
454 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.40050E-002
455 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1508197.92627
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1515297.13000
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 7.49864E-002
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12676
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.40050E-002
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1508197.92627
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1515297.13000
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 7.49864E-002
463 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.38506E-002
464 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.66207
465 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.38506E-002
466 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3532.58467
467 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.38506E-002
468 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
469 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 57235.65209
470 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
471 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
472 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21206.81799
473 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 570524.20687
474 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 559477.15000
475 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.38506E-002
476 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
477 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
478 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
479 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 5.95776
480 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
481 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.14997
482 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 17.99675
483 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.14997
484 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 45168.56681
485 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 59.14368
486 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1797868.50833
487 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 11.82874
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 224733.56354
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 59.14368
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1797868.50833
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 11.82874
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 224733.56354
493 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.78875E-002
494 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.78875E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 18306.11
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 335948.34
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 59425.67
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 4981.54
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 4012.19
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 6806.74
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 3588.38
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 115913.30
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 81367.10
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 115913.94
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 76003.83
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 16741.22
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 11022.02
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 16741.38
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 10441.70
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 20587.86
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 140443.62
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 10901.62
19 Coil:Heating:Water CAV_BAS HEATING COIL 222940.25


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 299652.41 197029.86 102622.55 0.66 39620.38 401.85
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2863121.85 1876541.53 986580.32 0.66 376814.65 3821.86
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 317512.27 209402.59 108109.68 0.66 42208.83 428.11
4 Coil:Cooling:Water CAV_BAS COOLING COIL 167887.83 111708.42 56179.41 0.67 21775.96 220.86


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.4280320945 0.1530026816 Pass Pass 0.5976132940 0.5325469323 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 2.7337635684E-003 1.9562766559E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 2.7180802702E-003 1.9721523306E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 2.1261162874E-002 1.2432479400E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.1435016540E-002 1.4937118153E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 2.9226300171E-002 3.2584578127E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 5.0201021144E-002 3.8096652175E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 3.4675848196E-002 3.1130802620E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 2.2933855634E-002 1.4927967742E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 3.1497007180E-002 3.1020824174E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 5.6774554238E-002 4.1000894541E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 3.7253234422E-002 3.1671558669E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 3.5421802548E-002 2.1209316811E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 4.3184758995E-002 2.7979712960E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 6.8150328986E-002 4.4253274121E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 5.0528570428E-002 3.6492444470E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.7962427425E-003 3.0255200991E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.9177804348E-003 3.2881723605E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.3650241304E-002 4.8160798559E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 4.8671183059E-005 7.3405586830E-005 Pass Pass 2.2839333565E-003 1.2874448111E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 3.2465811243E-005 4.8724899005E-005 Pass Pass 7.6716630630E-003 4.0002602177E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 3.6162954691E-002 1.7994252821E-002 Pass Pass 1.0467739042E-002 8.7036845776E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 1.5556399860E-004 2.0494683110E-004 Pass Pass 5.8406980087E-005 1.0850276967E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 4680.80 -43.1 0.00 -5232.3 41819.39 41224.83



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 6.30 0.00 6.30 Wetbulb [C] 0.50 270.00
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 42.00 9.70 22.20 Wetbulb [C] 3.20 320.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.60 4      
Feb 21.40 43      
Mar 12.00 35      
Apr 29.10 12      
May 29.10 57      
Jun 197.10 59      
Jul 47.90 83      
Aug 0.00 0      
Sep 171.60 106      
Oct 4.80 31      
Nov 1.20 7      
Dec 33.00 13      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.327 1.656 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.327 1.656 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.327 1.656 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.327 1.656 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.273 0.283 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.5047_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.5047_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.5047_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.5047_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.5047_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.5047_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.5047_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 869.21 2.869 0.251 0.251             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.5047_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 579.48 2.869 0.251 0.251             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.5047_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 869.21 2.869 0.251 0.251             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.5047_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 579.48 2.869 0.251 0.251             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.5047_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 86.92 2.869 0.251 0.251             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.5047_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 57.95 2.869 0.251 0.251             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.5047_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 86.92 2.869 0.251 0.251             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.5047_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 57.95 2.869 0.251 0.251             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 2.869 0.251 0.251                      
North Total or Average             1043.06 2.869 0.251 0.251                      
Non-North Total or Average             2433.80 2.869 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.3279 2779.43 25926.33 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 240.45
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 9.3279 2496.12 23283.67 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 215.94
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 9.3279 24961.20 232836.67 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 2159.39
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 9.3279 2496.12 23283.67 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 215.94
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 9.3279 313.41 2923.50 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.96 0.0000 Y 18.64
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.93 0.0000 Y 12.00
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 9.3279 313.42 2923.56 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.76 0.0000 Y 18.53
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.90 0.0000 Y 11.99
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 9.3279 3134.13 29234.97 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.99 0.0000 Y 186.55
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 9.3279 2019.75 18840.12 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.94 0.0000 Y 120.04
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 9.3279 3134.20 29235.61 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.79 0.0000 Y 185.41
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 9.3279 2019.75 18840.12 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.91 0.0000 Y 119.94
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 9.3279 313.41 2923.50 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.99 0.0000 Y 18.66
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.94 0.0000 Y 12.00
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 9.3279 313.42 2923.56 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.79 0.0000 Y 18.54
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.91 0.0000 Y 11.99
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 9.3279 783.68 7310.12 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 67.80
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 16.0861 36.20 582.36 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 5.97
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 16.0861 362.03 5823.61 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 59.65
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 16.0861 36.20 582.36 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 5.97
Interior Lighting Total       9.3913 46320.38 435009.77               1157.50


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.56 1127.62
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.56 0.00
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.50 1127.59
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.50 0.00
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.56 1127.62
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.56 0.00
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.50 1127.59
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.50 0.00
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.56 1127.62
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.56 0.00
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.50 1127.59
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.50 0.00
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 9973.01 AstronomicalClock -   41.75 41.75 78.17
EXTERIOR_LIGHTS_B 44362.79 AstronomicalClock -   83.75 71.15 592.54
Exterior Lighting Total 54335.80           670.70



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2972878.68          
HEATSYS1 BOILER Boiler:HotWater 1393523.42 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1515297.13 6.28 1450347.10 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1515297.13 6.28 1450347.10 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 559477.15 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1797868.51          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1797868.51          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 241356.59 299652.41 197029.86 102622.55 0.66 - 39620.38 401.85
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2357913.58 2863121.85 1876541.53 986580.32 0.66 - 376814.65 3821.86
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 250531.59 317512.27 209402.59 108109.68 0.66 - 42208.83 428.11
CAV_BAS COOLING COIL Coil:Cooling:Water 129929.42 167887.83 111708.42 56179.41 0.67 - 21775.96 220.86
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   452498.18 281793.92 170704.26 0.62 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9816.00 6187.94 3628.06 0.63 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   93579.44 58964.62 34614.82 0.63 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9667.57 6011.05 3656.52 0.62 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 19305.91 18306.11 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 354464.71 335948.34 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 62750.60 59425.67 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 5254.70 4981.54 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 4232.59 4012.19 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 7182.26 6806.74 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 3784.43 3588.38 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 122321.44 115913.30 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 85910.31 81367.10 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 122322.11 115913.94 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 80227.15 76003.83 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 17668.25 16741.22 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 11632.41 11022.02 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 17668.43 16741.38 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 11025.84 10441.70 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 23748.16 20587.86 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 157846.57 140443.62 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 12003.85 10901.62 -
CAV_BAS HEATING COIL Coil:Heating:Water 274173.69 222940.25 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   452498.18 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9816.00 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   93579.44 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9667.57 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   13450.69 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   621.37 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   6213.66 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   621.37 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 10.32 22180.58 2149.46 1.00 1.12 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 97.66 211042.50 2160.95 1.00 1.08 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 11.03 23709.01 2149.46 1.00 1.12 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 6.00 10174.45 1695.65 1.00 1.15 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 21.97 36232.89 1649.25 1.00 1.14 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.49 549.15 1120.11 1.00 1.61 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.67 5230.57 1120.11 1.00 1.16 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.47 526.20 1120.11 1.00 1.63 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.126765 26121.50 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.012191 3671.44 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.126765 18084.79 142664.32 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013851 3532.58 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 3168.45 0.000440 5.96 13540.37 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.149973 45168.57 301178.23 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.50 0.08



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 80997.48 80997.48 29.14 6.000 6.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 24.00 24.00 0.00743 34.82 0.00915 1.200 0.00
CORE_BOTTOM 85109.98 85109.98 34.10 6.305 6.305 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 24.00 24.00 0.00737 34.82 0.00915 1.078 0.00
CORE_MID 807330.70 807330.70 323.43 59.791 59.791 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 24.00 24.00 0.00739 34.82 0.00915 10.778 0.00
CORE_TOP 82761.94 82761.94 33.16 6.130 6.130 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 24.00 24.00 0.00738 34.82 0.00915 1.078 0.00
PERIMETER_BOT_ZN_3 16295.18 16295.18 51.99 1.218 1.218 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:20:00 24.00 24.00 0.00726 41.81 0.00916 0.135 0.00
PERIMETER_BOT_ZN_2 12707.02 12707.02 62.91 0.950 0.950 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:10:00 24.00 24.00 0.00722 38.56 0.00915 0.087 0.00
PERIMETER_BOT_ZN_1 16578.53 16578.53 52.90 1.239 1.239 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 24.00 24.00 0.00726 42.00 0.00916 0.135 0.00
PERIMETER_BOT_ZN_4 16544.02 16544.02 81.91 1.236 1.236 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:20:00 24.00 24.00 0.00717 41.16 0.00916 0.087 0.00
PERIMETER_MID_ZN_3 157963.52 157963.52 504.01 11.806 11.806 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00 24.00 24.00 0.00731 41.71 0.00916 1.353 0.00
PERIMETER_MID_ZN_2 131147.80 131147.80 649.33 9.802 9.802 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:20:00 24.00 24.00 0.00724 38.80 0.00915 0.872 0.00
PERIMETER_MID_ZN_1 159374.33 159374.33 508.50 11.912 11.912 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:10:00 24.00 24.00 0.00730 42.00 0.00916 1.353 0.00
PERIMETER_MID_ZN_4 140200.20 140200.20 694.15 10.479 10.479 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 24.00 24.00 0.00723 41.03 0.00916 0.872 0.00
PERIMETER_TOP_ZN_3 18475.29 18475.29 58.95 1.381 1.381 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00 24.00 24.00 0.00728 41.61 0.00916 0.135 0.00
PERIMETER_TOP_ZN_2 14013.77 14013.77 69.38 1.047 1.047 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:40:00 24.00 24.00 0.00724 39.28 0.00915 0.087 0.00
PERIMETER_TOP_ZN_1 18514.36 18514.36 59.07 1.384 1.384 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:40:00 24.00 24.00 0.00728 42.00 0.00916 0.135 0.00
PERIMETER_TOP_ZN_4 15788.64 15788.64 78.17 1.180 1.180 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:20:00 24.00 24.00 0.00721 41.16 0.00916 0.087 0.00
DATACENTER_BOT_ZN_6 8317.58 8317.58 229.75 0.490 0.490 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 27.00 27.00 0.00700 32.36 0.00914 0.016 0.00
DATACENTER_MID_ZN_6 79223.03 79223.03 2188.32 4.670 4.670 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 27.00 27.00 0.00700 32.36 0.00914 0.156 0.00
DATACENTER_TOP_ZN_6 7969.89 7969.89 220.15 0.470 0.470 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 27.00 27.00 0.00700 32.36 0.00914 0.016 0.00
DATACENTER_BASEMENT_ZN_6 372677.24 372677.24 475.55 21.969 21.969 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:00:00 27.00 27.00 0.00704 33.17 0.00914 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200   00:10:00 15.60 25.81 0.00607 6.30 0.00607 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078   00:10:00 15.60 23.39 0.00607 6.30 0.00607 1.078 0.00
CORE_MID 164331.49 164331.49 65.83 7.043 10.778 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 6.30 0.00607 10.778 0.00
CORE_TOP 43077.00 43077.00 17.26 1.872 1.872 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 6.30 0.00607 1.078 0.00
PERIMETER_BOT_ZN_3 1670.33 1670.33 5.33 0.073 0.135 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00775 6.30 0.00607 0.135 0.00
PERIMETER_BOT_ZN_2 1437.37 1437.37 7.12 0.062 0.087 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00778 6.30 0.00607 0.087 0.00
PERIMETER_BOT_ZN_1 3534.95 3534.95 11.28 0.153 0.153 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00785 6.30 0.00607 0.135 0.00
PERIMETER_BOT_ZN_4 149.21 149.21 0.74 0.007 0.087 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00717 6.30 0.00607 0.087 0.00
PERIMETER_MID_ZN_3 85655.62 85655.62 273.30 3.737 3.737 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00790 6.30 0.00607 1.353 0.00
PERIMETER_MID_ZN_2 57054.55 57054.55 282.48 2.489 2.489 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00790 6.30 0.00607 0.872 0.00
PERIMETER_MID_ZN_1 85656.09 85656.09 273.30 3.737 3.737 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00790 6.30 0.00607 1.353 0.00
PERIMETER_MID_ZN_4 49381.77 49381.77 244.49 2.153 2.153 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00787 6.30 0.00607 0.872 0.00
PERIMETER_TOP_ZN_3 12366.35 12366.35 39.46 0.540 0.540 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 6.30 0.00607 0.135 0.00
PERIMETER_TOP_ZN_2 8141.55 8141.55 40.31 0.356 0.356 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 6.30 0.00607 0.087 0.00
PERIMETER_TOP_ZN_1 12366.48 12366.48 39.46 0.540 0.540 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 6.30 0.00607 0.135 0.00
PERIMETER_TOP_ZN_4 7551.70 7551.70 37.39 0.330 0.330 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00794 6.30 0.00607 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 27.00 0.00700 6.30 0.00607 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156   00:10:00 18.00 25.16 0.00698 6.30 0.00607 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 24.11 0.00620 6.30 0.00607 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338   00:10:00 18.00 27.00 0.00700 6.30 0.00607 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 10.32 10.32 1.54 1.54 10.3191 3.3600 10.3191 0.3256 0.3000
VAV_MID WITH REHEAT 97.66 97.66 22.89 22.89 97.6621 32.5719 97.6621 0.3335 0.3000
VAV_TOP WITH REHEAT 11.03 11.03 3.64 3.64 11.0302 3.6385 11.0302 0.3299 0.3000
CAV_BAS 6.00 6.00 1.20 1.20 6.0003 6.0003 6.0003 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.97 21.97 0.34 0.34 21.9694 21.9691 21.9694 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.49 0.49 0.02 0.02 0.4903 0.4903 0.4903 1.0000 1.0000
AIRLOOP DATACENTER MID 4.67 4.67 0.16 0.16 4.6697 4.6697 4.6697 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.47 0.47 0.02 0.02 0.4698 0.4698 0.4698 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 19305.913 19305.913 1.967027 0.00016890 389.192   1/21 00:10:00   1/21 00:10:00 19305.91 19305.91 1.967027 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00800000 50.4125 0.00 0.00 19377.10 19377.10
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 354464.714 354464.714 19.372161 0.00310101 7814.757 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 354464.71 354464.71 19.372161 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00800000 50.4125 164331.49 0.00 355688.04 355688.04
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 62750.600 62750.600 2.004490 0.00054897 1623.885 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 62750.60 62750.60 2.004490 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00800000 50.4125 43077.00 0.00 62943.01 62943.01
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 5254.698 5254.698 0.365373 0.00004597 111.029 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5254.70 5254.70 0.365373 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00775217 48.8704 1670.33 0.00 5273.65 5273.65
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 4232.593 4232.593 0.284918 0.00003703 89.875 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4232.59 4232.59 0.284918 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00777922 49.0390 1437.37 0.00 4247.52 4247.52
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 7182.258 7182.258 0.371726 0.00006283 160.180 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 7182.26 7182.26 0.371726 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00784759 49.4646 3534.95 0.00 7206.91 7206.91
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 3784.435 3784.435 0.370950 0.00003311 76.588 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3784.43 3784.43 0.370950 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00716599 45.2170 149.21 0.00 3798.36 3798.36
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 122321.443 122321.443 3.736591 0.00107012 3228.465 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 122321.44 122321.44 3.736591 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00790031 49.7931 85655.62 0.00 122740.94 122740.94
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 85910.307 85910.307 2.940653 0.00075158 2161.683 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 85910.31 85910.31 2.940653 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00790358 49.8134 57054.55 0.00 86177.19 86177.19
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 122322.114 122322.114 3.736611 0.00107013 3228.483 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 122322.11 122322.11 3.736611 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00790031 49.7931 85656.09 0.00 122741.61 122741.61
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 80227.147 80227.147 3.143626 0.00070186 1925.624 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 80227.15 80227.15 3.143626 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00786997 49.6044 49381.77 0.00 80487.34 80487.34
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 17668.253 17668.253 0.540259 0.00015457 466.109 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 17668.25 17668.25 0.540259 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00794874 50.0942 12366.35 0.00 17727.30 17727.30
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 11632.412 11632.412 0.355715 0.00010177 306.869 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11632.41 11632.41 0.355715 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00794965 50.0999 8141.55 0.00 11671.23 11671.23
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 17668.425 17668.425 0.540265 0.00015457 466.114 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 17668.43 17668.43 0.540265 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00794874 50.0942 12366.48 0.00 17727.48 17727.48
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 11025.837 11025.837 0.354021 0.00009646 284.707 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11025.84 11025.84 0.354021 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00793757 50.0248 7551.70 0.00 11059.67 11059.67
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 241356.593 -999.000 10.319117 0.01026787 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 241356.59 219638.36 10.319117 28.58 17.12 0.00779700 11.00 9.55 0.00700000 42.00 0.00915790 22.26 24.5970 24.00 0.00733236 38.5491 133425.99 0.00 245909.77 232462.97
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 23748.160 23748.160 3.095735 0.00020776 415.273 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 23748.16 23748.16 3.095735 6.30 6.30 0.00615922 12.80 11.37 0.00800000 6.30 0.00607234 6.30 81.9899 22.62 0.00659670 37.7261 6791.85 0.00 24925.48 24925.48
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2357913.575 -999.000 97.662056 0.10031109 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 2357913.58 2131484.75 97.662056 29.01 17.33 0.00787408 10.99 9.55 0.00700000 42.00 0.00915790 22.26 25.9896 24.00 0.00737901 38.7918 1220258.72 0.00 2400789.09 2250877.93
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 157846.568 157846.568 29.298617 0.00138091 2799.189 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 157846.57 157846.57 29.298617 8.23 7.53 0.00632265 12.80 11.37 0.00800000 6.30 0.00607234 6.30 86.6319 21.00 0.00793397 50.0022 442079.52 0.00 170034.66 170034.66
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 250531.587 -999.000 11.030192 0.01065819 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00 250531.59 228949.23 11.030192 28.15 16.93 0.00774381 11.00 9.55 0.00700000 42.00 0.00915790 22.26 23.0113 24.00 0.00732015 38.4859 147310.24 0.00 255351.06 242746.17
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 12003.850 12003.850 3.309057 0.00010501 215.278 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12003.85 12003.85 3.309057 9.72 8.44 0.00651626 12.80 11.37 0.00800000 6.30 0.00607234 6.30 76.7043 21.00 0.00797793 50.2754 57545.58 0.00 13198.58 13198.58
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 129929.422 -999.000 6.000309 0.00552750 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 129929.42 117190.69 6.000309 27.43 16.75 0.00782714 11.38 9.72 0.00700000 39.77 0.00915417 21.63 20.0016 24.00 0.00745765 39.2002 79880.86 0.00 132494.66 125499.34
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 274173.694 274173.694 6.000309 0.00239859 6235.337 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 274173.69 274173.69 6.000309 1.26 1.26 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 20.0016 25.81 0.00607234 28.7199 0.00 0.00 235929.42 235929.42
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 452498.179 281793.923 21.969355 0.01108165 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:10:00 406431.02 402713.71 -999.0 28.66 16.55 0.00707469 12.80 10.34 0.00700000 42.00 0.00915790 22.26 -999.0000 27.00 0.00704205 30.9975 372190.56 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9815.996 6187.937 0.490269 0.00024039 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 8770.51 8695.23 -999.0 28.14 16.36 0.00706830 12.80 10.34 0.00700000 32.36 0.00914193 19.41 -999.0000 27.00 0.00700000 30.8097 8269.80 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 93579.439 58964.616 4.669705 0.00229175 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 83626.46 82873.44 -999.0 28.15 16.37 0.00707170 12.80 10.34 0.00700000 32.36 0.00914193 19.41 -999.0000 27.00 0.00700000 30.8097 78812.63 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9667.570 6011.054 0.469775 0.00023676 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 8682.90 8513.18 -999.0 28.45 16.54 0.00715964 12.80 10.34 0.00700000 41.29 0.00915671 22.06 -999.0000 27.00 0.00709081 31.2079 7959.40 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 452498.179 452498.179 21.969355 0.01108165 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 452498.18 452498.18 21.969355 6.30 6.30 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 1.5403 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9815.996 9815.996 0.490269 0.00024039 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9816.00 9816.00 0.490269 6.30 6.30 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.1885 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 93579.439 93579.439 4.669705 0.00229175 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 93579.44 93579.44 4.669705 6.30 6.30 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.3476 25.16 0.00698209 34.2539 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9667.570 9667.570 0.469775 0.00023676 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9667.57 9667.57 0.469775 6.30 6.30 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.3276 24.11 0.00620124 32.4414 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 13450.693 13450.693 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 13450.69 13450.69 21.969355 0.10 0.10 0.00698571 40.00 20.89 0.00800000 6.30 0.00607234 6.30 1.5403 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 621.366 621.366 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 621.37 621.37 0.490269 0.20 0.20 0.00697042 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.1885 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 6213.663 6213.663 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 6213.66 6213.66 4.669705 0.21 0.21 0.00695164 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.3476 25.16 0.00698209 34.2539 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 621.366 621.366 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 621.37 621.37 0.469775 0.21 0.21 0.00619695 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.3276 24.11 0.00620124 32.4414 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 19305.913 19305.913 1.967027 0.00016890 389.192 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 1.3581 1.385403   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 19305.91 19305.91 1.0000 2.30886810 1.967027 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.16887932 60.00 32.22 27.78 0.000 19305.91 6.30 0.00607234 6.30 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 50.4125 0.00 0.00 19377.10 19377.10 2.30886810 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 354464.714 354464.714 19.372161 0.00310101 7814.757 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 24.9348 25.436581 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 354464.71 354464.71 1.0000 22.73876087 19.372161 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 3.10069562 60.00 32.22 27.78 0.000 354464.71 6.30 0.00607234 6.30 0.00000000 0.0000 20.58 0.00800000 21.00 0.00800000 50.4125 164331.49 0.00 355688.04 355688.04 22.73876087 12.80 11.60 0.00800000 33059.8 28.14 17.41 0.00800000 48702.2
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 62750.600 62750.600 2.004490 0.00054897 1623.885 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 4.4142 4.503017 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 62750.60 62750.60 1.0000 2.35284144 2.004490 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.54891362 60.00 32.22 27.78 0.000 62750.60 6.30 0.00607234 6.30 0.00000000 0.0000 20.86 0.00800000 21.00 0.00800000 50.4125 43077.00 0.00 62943.01 62943.01 2.35284144 12.80 11.60 0.00800000 33059.8 39.03 20.89 0.00800000 59811.7
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 5254.698 5254.698 0.365373 0.00004597 111.029 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 0.3696 0.377080 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 5254.70 5254.70 1.0000 0.42886945 0.365373 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.04596570 60.00 32.22 27.78 0.000 5254.70 6.30 0.00607234 6.30 0.00000000 0.0000 20.91 0.00775217 21.00 0.00775217 48.8704 1670.33 0.00 5273.65 5273.65 0.42886945 12.80 11.60 0.00800000 33059.8 24.86 16.26 0.00800000 45356.5
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 4232.593 4232.593 0.284918 0.00003703 89.875 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 0.2977 0.303733 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 4232.59 4232.59 1.0000 0.33443276 0.284918 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.03702480 60.00 32.22 27.78 0.000 4232.59 6.30 0.00607234 6.30 0.00000000 0.0000 20.87 0.00777922 21.00 0.00777922 49.0390 1437.37 0.00 4247.52 4247.52 0.33443276 12.80 11.60 0.00800000 33059.8 25.26 16.40 0.00800000 45760.5
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 7182.258 7182.258 0.371726 0.00006283 160.180 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 0.5052 0.515403 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 7182.26 7182.26 1.0000 0.43632692 0.371726 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.06282712 60.00 32.22 27.78 0.000 7182.26 6.30 0.00607234 6.30 0.00000000 0.0000 20.87 0.00784759 21.00 0.00784759 49.4646 3534.95 0.00 7206.91 7206.91 0.43632692 12.80 11.60 0.00800000 33059.8 29.00 17.70 0.00800000 49577.0
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 3784.435 3784.435 0.370950 0.00003311 76.588 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 0.2662 0.271573 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 3784.43 3784.43 1.0000 0.43541566 0.370950 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.03310451 60.00 32.22 27.78 0.000 3784.43 6.30 0.00607234 6.30 0.00000000 0.0000 20.99 0.00716599 21.00 0.00716599 45.2170 149.21 0.00 3798.36 3798.36 0.43541566 12.80 11.60 0.00800000 33059.8 21.35 14.98 0.00800000 41783.4
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 122321.443 122321.443 3.736591 0.00107012 3228.465 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 8.6047 8.777853 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 122321.44 122321.44 1.0000 4.38595607 3.736591 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 1.07001218 60.00 32.22 27.78 0.000 122321.44 6.30 0.00607234 6.30 0.00000000 0.0000 20.91 0.00790031 21.00 0.00790031 49.7931 85655.62 0.00 122740.94 122740.94 4.38595607 12.80 11.60 0.00800000 33059.8 40.24 21.25 0.00800000 61044.8
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 85910.307 85910.307 2.940653 0.00075158 2161.683 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 6.0433 6.164970 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 85910.31 85910.31 1.0000 3.45169573 2.940653 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.75150418 60.00 32.22 27.78 0.000 85910.31 6.30 0.00607234 6.30 0.00000000 0.0000 20.91 0.00790358 21.00 0.00790358 49.8134 57054.55 0.00 86177.19 86177.19 3.45169573 12.80 11.60 0.00800000 33059.8 37.28 20.36 0.00800000 58026.5
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 122322.114 122322.114 3.736611 0.00107013 3228.483 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 8.6047 8.777902 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 122322.11 122322.11 1.0000 4.38597986 3.736611 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 1.07001805 60.00 32.22 27.78 0.000 122322.11 6.30 0.00607234 6.30 0.00000000 0.0000 20.91 0.00790031 21.00 0.00790031 49.7931 85656.09 0.00 122741.61 122741.61 4.38597986 12.80 11.60 0.00800000 33059.8 40.24 21.25 0.00800000 61044.8
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 80227.147 80227.147 3.143626 0.00070186 1925.624 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 5.6436 5.757144 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 80227.15 80227.15 1.0000 3.68994256 3.143626 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.70179048 60.00 32.22 27.78 0.000 80227.15 6.30 0.00607234 6.30 0.00000000 0.0000 20.91 0.00786997 21.00 0.00786997 49.6044 49381.77 0.00 80487.34 80487.34 3.68994256 12.80 11.60 0.00800000 33059.8 34.19 19.40 0.00800000 54872.5
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 17668.253 17668.253 0.540259 0.00015457 466.109 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 1.2429 1.267883 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 17668.25 17668.25 1.0000 0.63414873 0.540259 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.15455381 60.00 32.22 27.78 0.000 17668.25 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00794874 21.00 0.00794874 50.0942 12366.35 0.00 17727.30 17727.30 0.63414873 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61014.3
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 11632.412 11632.412 0.355715 0.00010177 306.869 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 0.8183 0.834748 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 11632.41 11632.41 1.0000 0.41753340 0.355715 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.10175503 60.00 32.22 27.78 0.000 11632.41 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00794965 21.00 0.00794965 50.0999 8141.55 0.00 11671.23 11671.23 0.41753340 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61012.6
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 17668.425 17668.425 0.540265 0.00015457 466.114 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 1.2429 1.267896 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 17668.43 17668.43 1.0000 0.63415491 0.540265 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.15455533 60.00 32.22 27.78 0.000 17668.43 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00794874 21.00 0.00794874 50.0942 12366.48 0.00 17727.48 17727.48 0.63415491 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61014.3
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 11025.837 11025.837 0.354021 0.00009646 284.707 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 0.7756 0.791220 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 11025.84 11025.84 1.0000 0.41554447 0.354021 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.09644899 60.00 32.22 27.78 0.000 11025.84 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00793757 21.00 0.00793757 50.0248 7551.70 0.00 11059.67 11059.67 0.41554447 12.80 11.60 0.00800000 33059.8 38.90 20.85 0.00800000 59674.7
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 241356.593 -999.000 10.319117 0.01026787 -999.000 -999.0000 1.00000 1.00000 1019.3342 1004.8586 1.1738 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.319117 12.11242912   4197.9300 999.8980 126.75172122 12.27 6.67 5.60 2979731.18 8.0999 8.099945 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 Sensible 241356.59 219638.36 1.0000 12.11242912 10.319117 28.58 17.12 0.00779700 48632.9 11.00 9.55 0.00700000 28706.5 10.26681997 6.67 12.27 5.60 22180.576 219176.02 42.00 0.00915790 22.26 2.53819000 24.5970 24.00 0.00733236 24.00 0.00733236 38.5491 133425.99 0.00 245909.77 232462.97 12.11242912 28.58 17.39 0.00779700 48632.9 9.75 9.59 0.00735629 28330.6
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 23748.160 23748.160 3.095735 0.00020776 415.273 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.319117 12.11242912   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 1.6706 1.704181 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 23748.16 23748.16 1.0000 3.63372874 3.095735 6.30 6.30 0.00615922 21802.5 12.80 11.37 0.00800000 33059.8 0.20773807 60.00 32.22 27.78 0.000 23748.16 6.30 0.00607234 6.30 2.53819000 81.9899 6.28 0.00655470 22.62 0.00659670 37.7261 6791.85 0.00 24925.48 24925.48 3.63372874 2.80 2.80 0.00615922 18249.4 9.55 8.16 0.00615922 25108.9
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2357913.575 -999.000 97.662056 0.10031109 -999.000 -999.0000 1.00000 1.00000 1019.4775 1004.8586 1.1738 VAV_MID WITH REHEAT FAN Fan:VariableVolume 97.662056 114.63430087   4197.9300 999.8980 126.75172122 12.27 6.67 5.60 2979731.18 79.1318 79.131755 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 Sensible 2357913.58 2131484.75 1.0000 114.63430087 97.662056 29.01 17.33 0.00787408 49266.0 10.99 9.55 0.00700000 28697.0 100.30086152 6.67 12.27 5.60 211042.501 2146871.07 42.00 0.00915790 22.26 25.38195000 25.9896 24.00 0.00737901 24.00 0.00737901 38.7918 1220258.72 0.00 2400789.09 2250877.93 114.63430087 29.01 17.60 0.00787408 49266.0 9.75 9.59 0.00735494 28323.0
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 157846.568 157846.568 29.298617 0.00138091 2799.189 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 VAV_MID WITH REHEAT FAN Fan:VariableVolume 97.662056 114.63430087   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 11.1037 11.327156 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 157846.57 157846.57 1.0000 34.39029026 29.298617 8.23 7.53 0.00632265 24181.5 12.80 11.37 0.00800000 33059.8 1.38076977 60.00 32.22 27.78 0.000 157846.57 6.30 0.00607234 6.30 25.38195000 86.6319 20.75 0.00794474 21.00 0.00793397 50.0022 442079.52 0.00 170034.66 170034.66 34.39029026 2.80 2.80 0.00632265 18659.0 7.66 7.45 0.00632265 23603.3
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 250531.587 -999.000 11.030192 0.01065819 -999.000 -999.0000 1.00000 1.00000 1019.2354 1004.8586 1.1738 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 11.030192 12.94707848   4197.9300 999.8980 126.75172122 12.27 6.67 5.60 2979731.18 8.4079 8.407859 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00 Sensible 250531.59 228949.23 1.0000 12.94707848 11.030192 28.15 16.93 0.00774381 48056.8 11.00 9.55 0.00700000 28706.4 10.65710564 6.67 12.27 5.60 23709.006 226822.58 42.00 0.00915790 22.26 2.53819000 23.0113 24.00 0.00732015 24.00 0.00732015 38.4859 147310.24 0.00 255351.06 242746.17 12.94707848 28.15 17.20 0.00774381 48056.8 9.75 9.59 0.00735733 28334.1
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 12003.850 12003.850 3.309057 0.00010501 215.278 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 11.030192 12.94707848   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 0.8444 0.861403 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12003.85 12003.85 1.0000 3.88412354 3.309057 9.72 8.44 0.00651626 26186.1 12.80 11.37 0.00800000 33059.8 0.10500421 60.00 32.22 27.78 0.000 12003.85 6.30 0.00607234 6.30 2.53819000 76.7043 21.00 0.00797793 21.00 0.00797793 50.2754 57545.58 0.00 13198.58 13198.58 3.88412354 2.80 2.80 0.00651626 19144.2 6.14 6.14 0.00651626 22542.3
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 129929.422 -999.000 6.000309 0.00552750 -999.000 -999.0000 1.00000 1.00000 1019.3903 1004.8586 1.1738 CAV_BAS FAN Fan:ConstantVolume 6.000309 7.04307530   4197.9300 999.8980 126.75172122 12.27 6.67 5.60 2979731.18 4.3604 4.360441 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:20:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 Sensible 129929.42 117190.69 1.0000 7.04307530 6.000309 27.43 16.75 0.00782714 47540.5 11.38 9.72 0.00700000 29092.7 5.52693410 6.67 12.27 5.60 10174.450 119754.97 39.77 0.00915417 21.63 1.20015641 20.0016 24.00 0.00745765 24.00 0.00745765 39.2002 79880.86 0.00 132494.66 125499.34 7.04307530 27.43 17.02 0.00782714 47540.5 9.95 9.77 0.00743292 28728.4
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 274173.694 274173.694 6.000309 0.00239859 6235.337 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 CAV_BAS FAN Fan:ConstantVolume 6.000309 7.04307530   4197.9300 999.8980 12.18990717 54.44 82.22 27.78 1421568.63 19.2867 19.674854 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 274173.69 274173.69 1.0000 7.04307530 6.000309 1.26 1.26 0.00607234 16467.0 40.00 20.89 0.00800000 60796.0 2.39834640 60.00 32.22 27.78 0.000 274173.69 6.30 0.00607234 6.30 1.20015641 20.0016 0.00 0.00607234 25.81 0.00607234 28.7199 0.00 0.00 235929.42 235929.42 7.04307530 12.80 9.56 0.00607234 28193.0 45.77 21.49 0.00607234 61691.1
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 452498.179 281793.923 21.969355 0.01108165 -999.000 -999.0000 -999.00000 -999.00000 1017.9915 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:10:00 Sensible 406431.02 402713.71 0.8982 -999.0 -999.0 28.66 16.55 0.00707469 46868.1 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 406431.02 42.00 0.00915790 22.26 0.33839277 -999.0000 27.00 0.00704205 27.00 0.00704205 30.9975 372190.56 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9815.996 6187.937 0.490269 0.00024039 -999.000 -999.0000 -999.00000 -999.00000 1017.9796 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 06:30:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 Sensible 8770.51 8695.23 0.8935 -999.0 -999.0 28.14 16.36 0.00706830 46325.7 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8770.51 32.36 0.00914193 19.41 0.01563234 -999.0000 27.00 0.00700000 27.00 0.00700000 30.8097 8269.80 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 93579.439 58964.616 4.669705 0.00229175 -999.000 -999.0000 -999.00000 -999.00000 1017.9859 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 06:40:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 Sensible 83626.46 82873.44 0.8936 -999.0 -999.0 28.15 16.37 0.00707170 46343.1 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 83626.46 32.36 0.00914193 19.41 0.15632344 -999.0000 27.00 0.00700000 27.00 0.00700000 30.8097 78812.63 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9667.570 6011.054 0.469775 0.00023676 -999.000 -999.0000 -999.00000 -999.00000 1018.1494 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 Sensible 8682.90 8513.18 0.8981 -999.0 -999.0 28.45 16.54 0.00715964 46868.8 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8682.90 41.29 0.00915671 22.06 0.01563234 -999.0000 27.00 0.00709081 27.00 0.00709081 31.2079 7959.40 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 452498.179 452498.179 21.969355 0.01108165 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 452498.18 452498.18 1.0000 25.78730951 21.969355 6.30 6.30 0.00607234 21588.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 452498.18 6.30 0.00607234 6.30 0.33839277 1.5403 0.00 0.00700000 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9815.996 9815.996 0.490269 0.00024039 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9816.00 9816.00 1.0000 0.57547109 0.490269 6.30 6.30 0.00607234 21588.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9816.00 6.30 0.00607234 6.30 0.01563234 3.1885 0.00 0.00700000 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 93579.439 93579.439 4.669705 0.00229175 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 93579.44 93579.44 1.0000 5.48123179 4.669705 6.30 6.30 0.00607234 21588.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 93579.44 6.30 0.00607234 6.30 0.15632344 3.3476 0.00 0.00698209 25.16 0.00698209 34.2539 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9667.570 9667.570 0.469775 0.00023676 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9667.57 9667.57 1.0000 0.55141536 0.469775 6.30 6.30 0.00607234 21588.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9667.57 6.30 0.00607234 6.30 0.01563234 3.3276 0.00 0.00620124 24.11 0.00620124 32.4414 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 13450.693 13450.693 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.969355 25.78730951   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 13450.69 13450.69 1.0000 25.78730951 21.969355 0.10 0.10 0.00698571 17569.6 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 13450.69 6.30 0.00607234 6.30 0.33839277 1.5403 0.00 0.00700000 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 621.366 621.366 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.490269 0.57547109   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 621.37 621.37 1.0000 0.57547109 0.490269 0.20 0.20 0.00697042 17637.1 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 621.37 6.30 0.00607234 6.30 0.01563234 3.1885 0.00 0.00700000 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 6213.663 6213.663 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.669705 5.48123179   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 6213.66 6213.66 1.0000 5.48123179 4.669705 0.21 0.21 0.00695164 17600.3 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6213.66 6.30 0.00607234 6.30 0.15632344 3.3476 0.00 0.00698209 25.16 0.00698209 34.2539 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 621.366 621.366 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.469775 0.55141536   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 621.37 621.37 1.0000 0.55141536 0.469775 0.21 0.21 0.00619695 15711.3 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 621.37 6.30 0.00607234 6.30 0.01563234 3.3276 0.00 0.00620124 24.11 0.00620124 32.4414 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 5406.17 1646.50 1646.50
CORE_BOTTOM 5435.00 20.33 13.00
CORE_MID 4811.33 270.17 22.00
CORE_TOP 4334.50 1015.67 28.50
PERIMETER_BOT_ZN_3 4502.83 926.50 101.00
PERIMETER_BOT_ZN_2 4590.67 957.00 160.00
PERIMETER_BOT_ZN_1 5187.33 635.50 259.00
PERIMETER_BOT_ZN_4 5401.17 728.83 472.50
PERIMETER_MID_ZN_3 3841.50 1887.33 223.17
PERIMETER_MID_ZN_2 3450.50 1503.00 301.67
PERIMETER_MID_ZN_1 4955.17 956.50 375.50
PERIMETER_MID_ZN_4 4255.67 1589.33 304.83
PERIMETER_TOP_ZN_3 3776.83 2269.67 402.67
PERIMETER_TOP_ZN_2 4068.00 1974.00 406.83
PERIMETER_TOP_ZN_1 4661.33 1343.67 405.33
PERIMETER_TOP_ZN_4 4047.50 1954.17 393.50
DATACENTER_BOT_ZN_6 5943.00 1685.17 1685.17
DATACENTER_MID_ZN_6 5943.00 489.83 489.83
DATACENTER_TOP_ZN_6 5909.00 752.50 740.33
DATACENTER_BASEMENT_ZN_6 5943.00 5943.00 5943.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 100.50 0.00 8.00
CORE_BOTTOM 0.00 8.67 0.00 0.00
CORE_MID 0.00 0.17 0.00 0.00
CORE_TOP 0.17 0.67 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 30.50 0.00 12.50
PERIMETER_BOT_ZN_2 0.00 33.50 0.00 25.00
PERIMETER_BOT_ZN_1 0.00 78.17 0.00 55.17
PERIMETER_BOT_ZN_4 0.00 223.83 0.00 70.17
PERIMETER_MID_ZN_3 0.00 22.17 0.00 8.33
PERIMETER_MID_ZN_2 0.00 40.33 0.00 31.00
PERIMETER_MID_ZN_1 0.00 70.33 0.00 51.67
PERIMETER_MID_ZN_4 0.00 66.50 0.00 28.83
PERIMETER_TOP_ZN_3 0.33 46.50 0.00 21.17
PERIMETER_TOP_ZN_2 0.33 71.00 0.00 44.83
PERIMETER_TOP_ZN_1 0.33 84.17 0.00 52.00
PERIMETER_TOP_ZN_4 0.33 86.17 0.00 34.50
DATACENTER_BOT_ZN_6 0.00 545.00 0.00 449.50
DATACENTER_MID_ZN_6 0.00 451.00 0.00 399.67
DATACENTER_TOP_ZN_6 0.00 309.00 0.00 277.50
DATACENTER_BASEMENT_ZN_6 0.00 1282.17 0.00 919.50
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 0.33 1636.17 0.00 1069.17
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.75 149.60 6779.02 0.535 0.000 0.000 0.000
CORE_BOTTOM 56.35 134.35 6849.35 0.469 0.000 0.000 0.000
CORE_MID 56.35 134.35 6849.35 0.449 0.000 0.000 0.000
CORE_TOP 56.35 134.35 6849.35 0.436 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.08 16.87 860.00 0.614 0.017 0.000 0.000
PERIMETER_BOT_ZN_2 4.56 10.87 554.22 0.717 0.017 0.000 0.000
PERIMETER_BOT_ZN_1 7.08 16.87 860.02 0.762 0.017 0.000 0.000
PERIMETER_BOT_ZN_4 4.56 10.87 554.22 1.050 0.017 0.000 0.000
PERIMETER_MID_ZN_3 7.08 16.87 860.00 0.639 0.039 0.000 0.000
PERIMETER_MID_ZN_2 3.99 10.87 554.22 0.796 0.042 0.000 0.000
PERIMETER_MID_ZN_1 7.08 16.87 860.02 0.824 0.039 0.000 0.000
PERIMETER_MID_ZN_4 4.56 10.87 554.22 0.885 0.041 0.000 0.000
PERIMETER_TOP_ZN_3 7.08 16.87 860.00 0.673 0.049 0.000 0.000
PERIMETER_TOP_ZN_2 4.56 10.87 554.22 0.835 0.050 0.000 0.000
PERIMETER_TOP_ZN_1 7.08 16.87 860.02 0.824 0.049 0.000 0.000
PERIMETER_TOP_ZN_4 4.56 10.87 554.22 0.903 0.050 0.000 0.000
DATACENTER_BOT_ZN_6 0.82 1.95 99.34 0.590 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.82 1.95 99.34 0.590 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.82 1.95 99.34 0.590 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.69 42.18 1911.37 0.665 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.75 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 56.35 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 56.35 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 56.35 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.08 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.56 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.08 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.56 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.08 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.99 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.08 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.56 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.08 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.56 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.08 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.56 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.82 1.95 99.34 0.545 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.82 1.95 99.34 0.545 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.82 1.95 99.34 0.545 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.69 42.18 1911.37 0.613 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.75 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 56.35 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 56.35 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 56.35 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.08 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.56 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.08 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.56 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.08 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.99 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.08 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.56 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.08 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.56 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.08 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.56 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.82 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.82 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.82 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.69 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1040.03 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 24045975.87 0.00 24045975.87 0.00 24045975.87 37848132.68 3194.53 5565.47 0.00 748.77
CORE_BOTTOM 23002973.66 0.00 23002973.66 0.00 23002973.66 33990283.35 8091.59 92.89 575.52 1289.78
CORE_MID 0.20E+09 0.00 0.20E+09 0.00 0.20E+09 0.34E+09 8135.83 86.93 537.24 744.20
CORE_TOP 19713247.91 0.00 19713247.91 0.00 19713247.91 33990283.35 8700.82 34.40 24.78 735.67
PERIMETER_BOT_ZN_3 3866899.62 0.00 3866899.62 135485.55 4002385.18 4267819.30 3607.66 108.66 5043.68 1289.78
PERIMETER_BOT_ZN_2 2932653.22 0.00 2932653.22 90323.64 3022976.86 2750345.05 2743.97 80.78 5935.25 1289.78
PERIMETER_BOT_ZN_1 4618345.88 0.00 4618345.88 135485.55 4753831.44 4267912.63 2498.56 55.89 6205.55 1289.78
PERIMETER_BOT_ZN_4 4233477.40 0.00 4233477.40 90323.64 4323801.04 2750345.05 2218.38 0.00 6541.62 1289.78
PERIMETER_MID_ZN_3 36420877.03 0.00 36420877.03 317743.67 36738620.70 42678193.03 3954.68 38.75 4766.58 744.20
PERIMETER_MID_ZN_2 30054298.27 0.00 30054298.27 211828.97 30266127.24 27503450.52 3013.61 46.68 5699.71 1653.20
PERIMETER_MID_ZN_1 45625166.60 0.00 45625166.60 317743.67 45942910.27 42679126.28 3089.27 10.04 5660.69 744.20
PERIMETER_MID_ZN_4 32573291.61 0.00 32573291.61 211828.97 32785120.58 27503450.52 2977.93 14.05 5768.01 744.20
PERIMETER_TOP_ZN_3 3858725.50 0.00 3858725.50 394502.81 4253228.30 4267819.30 3547.26 54.73 5158.01 735.67
PERIMETER_TOP_ZN_2 3063161.55 0.00 3063161.55 263001.69 3326163.24 2750345.05 2999.45 16.32 5744.23 735.67
PERIMETER_TOP_ZN_1 4610989.49 0.00 4610989.49 394502.81 5005492.29 4267912.63 2993.99 5.91 5760.10 735.67
PERIMETER_TOP_ZN_4 3343814.53 0.00 3343814.53 263001.69 3606816.22 2750345.05 2972.44 2.38 5785.19 735.67
DATACENTER_BOT_ZN_6 492981.60 0.00 492981.60 0.00 492981.60 492981.60 0.00 8760.00 0.00 2817.00
DATACENTER_MID_ZN_6 4929815.99 0.00 4929815.99 0.00 4929815.99 4929815.99 0.00 8760.00 0.00 2817.00
DATACENTER_TOP_ZN_6 492981.60 0.00 492981.60 0.00 492981.60 492981.60 0.00 8760.00 0.00 2817.00
DATACENTER_BASEMENT_ZN_6 10671554.30 0.00 10671554.30 0.00 10671554.30 10671554.30 0.00 8760.00 0.00 2817.00
Total Facility 0.36E+10 0.00 0.36E+10 12358080.11 0.36E+10 0.50E+10 8760.00 8760.00 6949.17 3726.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 0.9727 0.0000 0.9727 0.0000 0.9727 1.2002 1126.30 4816.70 0.00
CORE_BOTTOM 0.8625 0.0000 0.8625 0.0000 0.8625 1.0778 5291.02 92.06 559.92
CORE_MID 8.2571 0.0000 8.2571 0.0000 8.2571 10.7782 5330.59 86.60 525.81
CORE_TOP 0.8025 0.0000 0.8025 0.0000 0.8025 1.0778 5887.62 34.04 21.34
PERIMETER_BOT_ZN_3 0.1415 0.0000 0.1415 0.0039 0.1454 0.1353 2063.22 107.86 3771.92
PERIMETER_BOT_ZN_2 0.1066 0.0000 0.1066 0.0026 0.1092 0.0872 1201.29 80.30 4661.41
PERIMETER_BOT_ZN_1 0.1758 0.0000 0.1758 0.0039 0.1797 0.1353 955.74 55.45 4931.80
PERIMETER_BOT_ZN_4 0.1561 0.0000 0.1561 0.0026 0.1587 0.0872 691.16 0.00 5251.84
PERIMETER_MID_ZN_3 1.4759 0.0000 1.4759 0.0091 1.4850 1.3533 1869.76 38.72 4034.53
PERIMETER_MID_ZN_2 1.1849 0.0000 1.1849 0.0062 1.1911 0.8721 907.22 27.67 4099.11
PERIMETER_MID_ZN_1 1.9020 0.0000 1.9020 0.0091 1.9111 1.3533 1007.70 10.00 4925.30
PERIMETER_MID_ZN_4 1.3166 0.0000 1.3166 0.0060 1.3227 0.8721 900.78 13.59 5028.63
PERIMETER_TOP_ZN_3 0.1555 0.0000 0.1555 0.0113 0.1668 0.1353 1461.55 54.47 4426.99
PERIMETER_TOP_ZN_2 0.1244 0.0000 0.1244 0.0075 0.1319 0.0872 915.31 16.11 5011.58
PERIMETER_TOP_ZN_1 0.1904 0.0000 0.1904 0.0113 0.2017 0.1353 910.78 5.87 5026.35
PERIMETER_TOP_ZN_4 0.1346 0.0000 0.1346 0.0075 0.1421 0.0872 890.53 2.25 5050.22
DATACENTER_BOT_ZN_6 0.0156 0.0000 0.0156 0.0000 0.0156 0.0156 0.00 5943.00 0.00
DATACENTER_MID_ZN_6 0.1563 0.0000 0.1563 0.0000 0.1563 0.1563 0.00 5943.00 0.00
DATACENTER_TOP_ZN_6 0.0156 0.0000 0.0156 0.0000 0.0156 0.0156 0.00 5943.00 0.00
DATACENTER_BASEMENT_ZN_6 0.3384 0.0000 0.3384 0.0000 0.3384 0.3384 0.00 5943.00 0.00
Total Facility 147.1199 0.0000 147.1199 0.3545 147.4745 158.4706 5943.00 5943.00 5397.14


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 53256913.86 0.00 53256913.86 48026705.38 2218.20 0.00 6541.80 1289.78
VAV_MID WITH REHEAT 0.48E+09 0.00 0.48E+09 0.48E+09 2950.21 0.00 5809.79 744.20
VAV_TOP WITH REHEAT 47657061.12 0.00 47657061.12 48026705.38 2967.33 0.00 5792.67 735.67
CAV_BAS 33129879.64 0.00 33129879.64 37848132.68 3194.53 0.00 5565.47 748.77
AIRLOOP DATACENTER BASEMENT 14702971.99 0.00 14702971.99 10671554.30 0.00 0.00 8760.00 2817.00
AIRLOOP DATACENTER BOT 679216.39 0.00 679216.39 492981.60 0.00 0.00 8760.00 2817.00
AIRLOOP DATACENTER MID 6792163.95 0.00 6792163.95 4929815.99 0.00 0.00 8760.00 2817.00
AIRLOOP DATACENTER TOP 679216.39 0.00 679216.39 492981.60 0.00 0.00 8760.00 2817.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 1.9875 0.0000 1.9875 1.5229 690.98 0.00 5252.02
VAV_MID WITH REHEAT 19.5227 0.0000 19.5227 15.2292 877.41 0.00 5065.59
VAV_TOP WITH REHEAT 1.9391 0.0000 1.9391 1.5229 886.00 0.00 5057.00
CAV_BAS 1.3402 0.0000 1.3402 1.2002 1126.30 0.00 4816.70
AIRLOOP DATACENTER BASEMENT 0.4662 0.0000 0.4662 0.3384 0.00 0.00 5943.00
AIRLOOP DATACENTER BOT 0.0215 0.0000 0.0215 0.0156 0.00 0.00 5943.00
AIRLOOP DATACENTER MID 0.2154 0.0000 0.2154 0.1563 0.00 0.00 5943.00
AIRLOOP DATACENTER TOP 0.0215 0.0000 0.0215 0.0156 0.00 0.00 5943.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 0.00 0.00 0.00 0.00 0.00 6541.80 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 0.00 0.00 0.00 0.00 0.00 5809.79 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 0.00 0.00 0.00 0.00 0.00 5792.67 0.00 0.00 0.00
CAV_BAS 0.00 5565.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 2.2490 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 22.9068 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 2.2789 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.6538 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4662 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0215 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2154 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0215 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1380
Defaulted Fields 1179
Fields with Defaults 3862
Autosized Fields 330
Autosizable Fields 409
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 34348.76 380994.45 01-JAN-10:20 2158800.56 07-AUG-15:20
Electricity:Building 18918.81 251811.03 01-JAN-08:50 1136695.02 29-DEC-17:00
Electricity:Zone:BASEMENT 664.85 14623.97 01-JAN-00:10 34452.17 02-JAN-08:10
Electricity:SpaceType:GENERAL 18918.81 251811.03 01-JAN-08:50 1136695.02 29-DEC-17:00
InteriorLights:Electricity 3705.40 17601.77 01-JAN-08:50 344557.66 11-OCT-07:10
InteriorLights:Electricity:Zone:BASEMENT 240.45 1166.43 01-JAN-00:10 20994.62 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 3705.40 17601.77 01-JAN-08:50 344557.66 11-OCT-07:10
LightsWired:InteriorLights:Electricity 3705.40 17601.77 01-JAN-08:50 344557.66 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 240.45 1166.43 01-JAN-00:10 20994.62 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 3705.40 17601.77 01-JAN-08:50 344557.66 11-OCT-07:10
Electricity:Zone:CORE_BOTTOM 537.23 7090.40 01-JAN-00:10 36983.24 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
Electricity:Zone:CORE_MID 5372.24 70903.72 01-JAN-00:10 369831.68 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2159.40 10475.32 01-JAN-00:10 188546.48 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 2159.40 10475.32 01-JAN-00:10 188546.48 02-JAN-08:10
Electricity:Zone:CORE_TOP 537.22 7090.37 01-JAN-00:10 36983.17 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 58.98 839.57 01-JAN-08:40 4434.82 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 18.64 80.80 01-JAN-08:40 2158.51 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 18.64 80.80 01-JAN-08:40 2158.51 11-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_2 38.00 541.05 01-JAN-07:50 2859.76 27-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 12.00 52.07 01-JAN-07:50 1392.81 27-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 12.00 52.07 01-JAN-07:50 1392.81 27-NOV-17:00
Electricity:Zone:PERIMETER_BOT_ZN_1 58.87 839.58 01-JAN-07:50 4426.36 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 18.53 80.80 01-JAN-07:50 2150.01 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 18.53 80.80 01-JAN-07:50 2150.01 11-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_4 37.99 541.05 01-JAN-08:50 2864.08 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.99 52.07 01-JAN-08:50 1397.15 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.99 52.07 01-JAN-08:50 1397.15 11-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_3 589.98 8395.70 01-JAN-08:40 44409.33 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 186.55 807.98 01-JAN-08:40 21646.15 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 186.55 807.98 01-JAN-08:40 21646.15 11-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_2 380.02 5410.51 01-JAN-07:50 28609.47 27-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 120.04 520.69 01-JAN-07:50 13940.01 27-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 120.04 520.69 01-JAN-07:50 13940.01 27-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_1 588.84 8395.84 01-JAN-08:00 44328.26 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 185.42 807.99 01-JAN-08:00 21564.73 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 185.42 807.99 01-JAN-08:00 21564.73 11-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_4 379.92 5410.48 01-JAN-08:50 28650.36 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 119.94 520.69 01-JAN-08:50 13980.99 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 119.94 520.69 01-JAN-08:50 13980.99 11-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_3 59.00 839.57 01-JAN-08:40 4440.72 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 18.66 80.80 01-JAN-08:40 2164.41 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 18.66 80.80 01-JAN-08:40 2164.41 11-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_2 38.00 541.05 01-JAN-07:50 2860.88 27-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 12.00 52.07 01-JAN-07:50 1393.93 27-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 12.00 52.07 01-JAN-07:50 1393.93 27-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_1 58.88 839.58 01-JAN-08:00 4432.62 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 18.54 80.80 01-JAN-08:00 2156.27 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 18.54 80.80 01-JAN-08:00 2156.27 11-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_4 37.99 541.05 01-JAN-08:50 2864.91 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 11.99 52.07 01-JAN-08:50 1397.97 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 11.99 52.07 01-JAN-08:50 1397.97 11-OCT-07:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7562.65 95237.01 01-JAN-00:10 385552.11 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 67.80 328.88 01-JAN-00:10 5919.59 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 67.80 328.88 01-JAN-00:10 5919.59 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 159.85 1977.54 01-JAN-00:10 8315.27 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1598.46 19775.43 01-JAN-00:10 83152.69 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 59.65 289.38 01-JAN-00:10 5208.47 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 59.65 289.38 01-JAN-00:10 5208.47 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 159.85 1977.54 01-JAN-00:10 8315.27 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
InteriorEquipment:Electricity 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 6533.09 8215.67 05-JAN-06:00 562660.38 22-JUN-15:40
HeatRejection:Electricity 1974.33 4598.82 05-JAN-07:00 93058.23 06-MAR-14:40
General:HeatRejection:Electricity 1974.33 4598.82 05-JAN-07:00 93058.23 06-MAR-14:40
Electricity:HVAC 6371.55 82634.38 16-JAN-04:40 439378.88 07-JUL-14:50
ExteriorEquipment:Electricity 1941.93 28795.69 01-JAN-00:10 118952.28 11-OCT-07:20
Transformer:ExteriorEquipment:Electricity 87.32 1613.62 01-JAN-00:10 5474.32 11-OCT-07:20
ElectricityPurchased:Facility 34348.76 380994.45 01-JAN-10:20 2158800.56 07-AUG-15:20
ElectricityPurchased:Plant 34348.76 380994.45 01-JAN-10:20 2158800.56 07-AUG-15:20
Cogeneration:ElectricityPurchased 34348.76 380994.45 01-JAN-10:20 2158800.56 07-AUG-15:20
General:Cogeneration:ElectricityPurchased 34348.76 380994.45 01-JAN-10:20 2158800.56 07-AUG-15:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 34348.76 380994.45 01-JAN-10:20 2158800.56 07-AUG-15:20
ElectricityNet:Plant 34348.76 380994.45 01-JAN-10:20 2158800.56 07-AUG-15:20
Cogeneration:ElectricityNet 34348.76 380994.45 01-JAN-10:20 2158800.56 07-AUG-15:20
General:Cogeneration:ElectricityNet 34348.76 380994.45 01-JAN-10:20 2158800.56 07-AUG-15:20
Fans:Electricity 2768.50 42538.82 11-JUN-15:00 245998.42 06-JUN-14:00
General:Fans:Electricity 2768.50 42538.82 11-JUN-15:00 245998.42 06-JUN-14:00
ExteriorLights:Electricity 670.70 0.00 01-JAN-07:20 54335.80 01-JAN-06:10
General:ExteriorLights:Electricity 670.70 0.00 01-JAN-07:20 54335.80 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
Cooling:Electricity 6662.79 33742.87 08-JAN-07:00 583147.84 28-AUG-14:50
General:Cooling:Electricity 6662.79 33742.87 08-JAN-07:00 583147.84 28-AUG-14:50
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 82.17 0.00 12-JAN-13:10 28596.21 22-DEC-06:00
General:Humidifier:Electricity 82.17 0.00 12-JAN-13:10 28596.21 22-DEC-06:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 1329.53 3532.58 01-JAN-00:10 71743.86 28-AUG-05:10
General:Pumps:Electricity 1329.53 3532.58 01-JAN-00:10 71743.86 28-AUG-05:10
WIRED_LTG_ELECTRICITY 104.12 0.00 01-JAN-00:10 9682.07 11-OCT-07:20
WIRED_INT_EQUIP 5871.99 115917.86 04-MAR-00:10 320838.49 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 581.58 5695.87 16-APR-15:00 229119.80 02-JAN-06:20
NaturalGas:Plant 581.58 5695.87 16-APR-15:00 229119.80 02-JAN-06:20
Heating:NaturalGas 22.01 0.00 01-JAN-00:10 207455.14 02-JAN-06:20
Boiler:Heating:NaturalGas 22.01 0.00 01-JAN-00:10 207455.14 02-JAN-06:20
WaterSystems:NaturalGas 559.57 5695.87 16-APR-15:00 72853.16 23-JAN-12:50
Water Heater:WaterSystems:NaturalGas 559.57 5695.87 16-APR-15:00 72853.16 23-JAN-12:50


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 36544.29 166124.82 22-JAN-07:00 3175446.85 28-AUG-14:40
PlantLoopCoolingDemand:HVAC 36544.29 166124.82 22-JAN-07:00 3175446.85 28-AUG-14:40
CoolingCoils:PlantLoopCoolingDemand 36544.29 166124.82 22-JAN-07:00 3175446.85 28-AUG-14:40


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 21473.87 0.00 11-MAR-00:20 0.00 19-APR-15:10
Water:HVAC 30.57 0.00 12-JAN-13:10 0.00 22-DEC-06:00
Humidifier:Water 30.57 0.00 12-JAN-13:10 0.00 22-DEC-06:00
General:Humidifier:Water 30.57 0.00 12-JAN-13:10 0.00 22-DEC-06:00
MainsWater:Facility 21473.87 0.00 11-MAR-00:20 0.00 19-APR-15:10
MainsWater:HVAC 30.57 0.00 12-JAN-13:10 0.00 22-DEC-06:00
Humidifier:MainsWater 30.57 0.00 12-JAN-13:10 0.00 22-DEC-06:00
General:Humidifier:MainsWater 30.57 0.00 12-JAN-13:10 0.00 22-DEC-06:00
Water:Plant 21443.30 0.00 01-JAN-00:10 0.00 19-APR-15:10
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 21443.30 0.00 01-JAN-00:10 0.00 19-APR-15:10
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 19163.14 0.00 01-JAN-00:10 0.00 19-APR-15:00
General:HeatRejection:Water 19163.14 0.00 01-JAN-00:10 0.00 19-APR-15:00
HeatRejection:MainsWater 19163.14 0.00 01-JAN-00:10 0.00 19-APR-15:00
General:HeatRejection:MainsWater 19163.14 0.00 01-JAN-00:10 0.00 19-APR-15:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 126050.24 230221.84 22-JAN-06:00 12410525.63 28-AUG-14:40
EnergyTransfer:Building 23808.33 97452.71 08-JAN-08:00 1700887.49 27-APR-15:30
EnergyTransfer:Zone:BASEMENT 803.12 0.00 01-JAN-00:10 76533.69 07-AUG-05:20
Heating:EnergyTransfer 17.72 0.00 02-JAN-12:20 91697.74 02-JAN-06:10
Heating:EnergyTransfer:Zone:BASEMENT 4.77 0.00 01-JAN-00:10 33524.56 10-JUN-16:10
General:Heating:EnergyTransfer 17.72 0.00 02-JAN-12:20 91697.74 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 4.77 0.00 01-JAN-00:10 33524.56 10-JUN-16:10
Cooling:EnergyTransfer 23790.62 97291.08 01-JAN-07:40 1700887.49 27-APR-15:30
Cooling:EnergyTransfer:Zone:BASEMENT 798.35 0.00 01-JAN-00:10 76533.69 07-AUG-05:20
General:Cooling:EnergyTransfer 23790.62 97291.08 01-JAN-07:40 1700887.49 27-APR-15:30
General:Cooling:EnergyTransfer:Zone:BASEMENT 798.35 0.00 01-JAN-00:10 76533.69 07-AUG-05:20
EnergyTransfer:Zone:CORE_BOTTOM 802.22 0.00 01-JAN-00:10 60494.61 07-AUG-09:20
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 802.22 0.00 01-JAN-00:10 60494.61 07-AUG-09:20
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 802.22 0.00 01-JAN-00:10 60494.61 07-AUG-09:20
EnergyTransfer:Zone:CORE_MID 6152.48 0.00 01-JAN-00:10 476404.24 05-SEP-09:20
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 6152.48 0.00 01-JAN-00:10 476404.24 05-SEP-09:20
General:Cooling:EnergyTransfer:Zone:CORE_MID 6152.48 0.00 01-JAN-00:10 476404.24 05-SEP-09:20
EnergyTransfer:Zone:CORE_TOP 629.07 0.00 01-JAN-00:10 59337.72 12-JUN-15:30
Heating:EnergyTransfer:Zone:CORE_TOP 0.21 0.00 01-JAN-00:10 35320.08 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 0.21 0.00 01-JAN-00:10 35320.08 02-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_TOP 628.86 0.00 01-JAN-00:10 59337.72 12-JUN-15:30
General:Cooling:EnergyTransfer:Zone:CORE_TOP 628.86 0.00 01-JAN-00:10 59337.72 12-JUN-15:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 132.40 0.00 01-JAN-00:10 13056.35 12-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 132.40 0.00 01-JAN-00:10 13056.35 12-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 132.40 0.00 01-JAN-00:10 13056.35 12-JUN-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 99.04 0.00 01-JAN-00:10 12385.40 12-JUN-09:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 99.04 0.00 01-JAN-00:10 12385.40 12-JUN-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 99.04 0.00 01-JAN-00:10 12385.40 12-JUN-09:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 164.76 0.00 01-JAN-00:10 17047.26 02-OCT-13:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 164.76 0.00 01-JAN-00:10 17047.26 02-OCT-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 164.76 0.00 01-JAN-00:10 17047.26 02-OCT-13:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 147.66 0.00 01-JAN-00:10 16711.97 27-APR-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 147.66 0.00 01-JAN-00:10 16711.97 27-APR-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 147.66 0.00 01-JAN-00:10 16711.97 27-APR-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 1074.28 0.00 01-JAN-00:10 123083.58 12-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 0.01 0.00 01-JAN-00:10 6322.33 21-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 0.01 0.00 01-JAN-00:10 6322.33 21-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 1074.28 0.00 01-JAN-00:10 123083.58 12-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 1074.28 0.00 01-JAN-00:10 123083.58 12-JUN-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 892.66 0.00 01-JAN-00:10 123379.75 03-MAY-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 0.00 0.00 01-JAN-00:10 3371.48 21-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 0.00 0.00 01-JAN-00:10 3371.48 21-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 892.65 0.00 01-JAN-00:10 123379.75 03-MAY-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 892.65 0.00 01-JAN-00:10 123379.75 03-MAY-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1427.09 0.00 01-JAN-00:10 165566.51 02-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1427.09 0.00 01-JAN-00:10 165566.51 02-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1427.09 0.00 01-JAN-00:10 165566.51 02-OCT-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 964.21 0.00 01-JAN-00:10 137298.53 06-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.00 0.00 01-JAN-00:10 130.06 03-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.00 0.00 01-JAN-00:10 130.06 03-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 964.21 0.00 01-JAN-00:10 137298.53 06-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 964.21 0.00 01-JAN-00:10 137298.53 06-JUN-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 116.34 0.00 01-JAN-00:10 14404.07 12-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 0.76 0.00 01-JAN-00:10 11246.70 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 0.76 0.00 01-JAN-00:10 11246.70 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 115.58 0.00 01-JAN-00:10 14404.07 12-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 115.58 0.00 01-JAN-00:10 14404.07 12-JUN-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 95.40 0.00 01-JAN-00:10 13503.04 12-JUN-09:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 0.28 0.00 01-JAN-00:10 7016.81 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 0.28 0.00 01-JAN-00:10 7016.81 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 95.12 0.00 01-JAN-00:10 13503.04 12-JUN-09:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 95.12 0.00 01-JAN-00:10 13503.04 12-JUN-09:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 149.57 0.00 01-JAN-00:10 18704.39 02-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.17 0.00 01-JAN-00:10 8480.98 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.17 0.00 01-JAN-00:10 8480.98 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 149.40 0.00 01-JAN-00:10 18704.39 02-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 149.40 0.00 01-JAN-00:10 18704.39 02-OCT-13:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 102.27 0.00 01-JAN-00:10 15121.03 06-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.16 0.00 01-JAN-00:10 5322.09 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.16 0.00 01-JAN-00:10 5322.09 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 102.10 0.00 01-JAN-00:10 15121.03 06-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 102.10 0.00 01-JAN-00:10 15121.03 06-JUN-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 125.18 0.00 01-JAN-00:10 14842.18 07-AUG-05:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.77 0.00 01-JAN-00:10 3072.99 24-DEC-10:50
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.77 0.00 01-JAN-00:10 3072.99 24-DEC-10:50
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 124.40 0.00 01-JAN-00:10 14842.18 07-AUG-05:20
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 124.40 0.00 01-JAN-00:10 14842.18 07-AUG-05:20
EnergyTransfer:Zone:MIDFLOOR_PLENUM 966.55 0.00 01-JAN-00:10 102157.26 05-JUL-15:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 4.95 0.00 01-JAN-00:10 21829.92 12-FEB-13:00
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 4.95 0.00 01-JAN-00:10 21829.92 12-FEB-13:00
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 961.61 0.00 01-JAN-00:10 102157.26 05-JUL-15:20
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 961.61 0.00 01-JAN-00:10 102157.26 05-JUL-15:20
EnergyTransfer:Zone:TOPFLOOR_PLENUM 169.34 0.00 01-JAN-00:10 31890.04 12-JUN-13:50
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 5.56 0.00 01-JAN-00:10 15109.25 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 5.56 0.00 01-JAN-00:10 15109.25 02-JAN-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 163.78 0.00 01-JAN-00:10 31890.04 12-JUN-13:50
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 163.78 0.00 01-JAN-00:10 31890.04 12-JUN-13:50
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 143.58 1129.53 07-JAN-08:00 7751.97 16-APR-22:40
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 143.58 1129.53 07-JAN-08:00 7751.97 16-APR-22:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 143.58 1129.53 07-JAN-08:00 7751.97 16-APR-22:40
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1331.36 6147.12 01-JAN-07:50 73381.61 12-APR-16:00
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1331.36 6147.12 01-JAN-07:50 73381.61 12-APR-16:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1331.36 6147.12 01-JAN-07:50 73381.61 12-APR-16:00
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 130.21 4.65 29-JAN-01:50 7474.21 12-APR-16:00
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.06 0.00 02-JAN-11:00 329.09 01-JAN-14:00
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.06 0.00 02-JAN-11:00 329.09 01-JAN-14:00
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 130.15 0.00 01-JAN-00:10 7474.21 12-APR-16:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 130.15 0.00 01-JAN-00:10 7474.21 12-APR-16:00
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7189.54 88610.81 14-MAY-02:00 369990.54 15-AUG-23:50
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7189.54 88610.81 14-MAY-02:00 369990.54 15-AUG-23:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7189.54 88610.81 14-MAY-02:00 369990.54 15-AUG-23:50
PlantLoopHeatingDemand:Facility 307.79 0.00 01-JAN-00:10 168761.40 02-JAN-06:20
PlantLoopHeatingDemand:Plant 293.17 0.00 01-JAN-00:10 40154.25 17-JAN-12:10
WaterSystems:PlantLoopHeatingDemand 293.17 0.00 01-JAN-00:10 40154.25 17-JAN-12:10
General:WaterSystems:PlantLoopHeatingDemand 293.17 0.00 01-JAN-00:10 40154.25 17-JAN-12:10
EnergyTransfer:HVAC 33125.35 132363.64 22-JAN-07:00 2977459.74 28-AUG-14:40
HeatingCoils:EnergyTransfer 14.62 0.00 01-JAN-00:10 163820.71 02-JAN-06:20
PlantLoopHeatingDemand:HVAC 14.62 0.00 01-JAN-00:10 163820.71 02-JAN-06:20
HeatingCoils:PlantLoopHeatingDemand 14.62 0.00 01-JAN-00:10 163820.71 02-JAN-06:20
CoolingCoils:EnergyTransfer 33110.73 132363.64 22-JAN-07:00 2977459.74 28-AUG-14:40
EnergyTransfer:Plant 69116.55 0.00 01-JAN-00:10 8079045.27 22-JUN-15:40
LoopToLoop:EnergyTransfer 23379.69 0.00 01-JAN-00:10 2545254.36 22-JUN-15:40
WaterSystems:EnergyTransfer 293.17 0.00 01-JAN-00:10 40154.25 17-JAN-12:10
WaterUse:WaterSystems:EnergyTransfer 293.17 0.00 01-JAN-00:10 40154.25 17-JAN-12:10
Boilers:EnergyTransfer 14.31 0.00 01-JAN-00:10 155766.48 02-JAN-06:20
Chillers:EnergyTransfer 21100.08 0.00 01-JAN-00:10 2557582.00 22-JUN-15:40
HeatRejection:EnergyTransfer 24329.30 0.00 01-JAN-00:10 2956607.79 22-JUN-15:40
General:HeatRejection:EnergyTransfer 24329.30 0.00 01-JAN-00:10 2956607.79 22-JUN-15:40
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 4.770 -798.351 0.000 0.000 92.651 240.449 424.397 0.000 0.000 0.000 36.085 0.000 0.000 0.000 0.000 -0.014
CORE_BOTTOM 0.000 0.000 0.000 -802.218 0.000 0.000 83.411 215.940 321.286 0.000 0.000 0.000 181.583 0.000 0.000 0.000 0.000 -0.008
CORE_MID 0.000 0.000 0.000 -6152.465 0.000 0.000 835.283 2159.397 3212.845 0.000 0.000 0.000 0.032 0.000 0.000 0.000 0.000 -55.061
CORE_TOP 0.000 0.000 0.214 -628.853 0.000 0.000 84.143 215.940 321.285 0.000 0.000 0.000 7.271 0.000 0.000 0.000 0.000 -0.001
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -132.396 0.000 0.000 10.540 18.636 40.342 42.541 0.000 0.652 41.018 0.000 -20.977 0.000 -0.356 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.000 -99.037 0.000 0.000 6.788 12.000 25.998 50.547 0.000 0.444 16.197 0.000 -12.702 0.000 -0.234 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.000 -164.757 0.000 0.000 10.493 18.528 40.343 90.446 0.000 0.637 25.103 0.000 -20.408 0.000 -0.387 -0.000
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -147.657 0.000 0.000 6.760 11.990 25.998 49.064 0.000 0.407 69.750 0.000 -16.031 0.000 -0.281 0.000
PERIMETER_MID_ZN_3 0.000 0.000 0.009 -1074.265 0.000 0.000 107.061 186.553 403.423 435.888 0.000 14.732 127.101 0.000 -193.035 0.000 -7.466 0.000
PERIMETER_MID_ZN_2 0.000 0.000 0.005 -892.646 0.000 0.000 50.394 120.037 259.981 504.998 0.000 9.674 76.251 0.000 -123.408 0.000 -5.286 -0.007
PERIMETER_MID_ZN_1 0.000 0.000 0.000 -1427.078 0.000 0.000 105.134 185.416 403.429 904.975 0.000 14.222 25.811 0.000 -202.804 0.000 -9.104 -0.001
PERIMETER_MID_ZN_4 0.000 0.000 0.000 -964.198 0.000 0.000 68.805 119.941 259.979 506.840 0.000 9.480 142.076 0.000 -137.406 0.000 -5.517 -0.001
PERIMETER_TOP_ZN_3 0.000 0.000 0.760 -115.578 0.000 0.000 10.889 18.655 40.342 43.524 0.000 1.804 18.115 0.000 -17.696 0.000 -0.815 -0.001
PERIMETER_TOP_ZN_2 0.000 0.000 0.283 -95.119 0.000 0.000 6.926 12.004 25.998 50.396 0.000 1.172 10.508 0.000 -11.571 0.000 -0.597 -0.000
PERIMETER_TOP_ZN_1 0.000 0.000 0.169 -149.395 0.000 0.000 10.606 18.542 40.343 90.259 0.000 1.735 7.902 0.000 -19.113 0.000 -1.047 -0.002
PERIMETER_TOP_ZN_4 0.000 0.000 0.165 -102.102 0.000 0.000 6.973 11.994 25.998 50.555 0.000 1.166 18.780 0.000 -12.899 0.000 -0.630 -0.001
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -143.584 0.000 0.000 0.938 5.965 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -17.199
DATACENTER_MID_ZN_6 0.000 0.000 0.000 -1331.365 0.000 0.000 9.390 59.652 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -276.483
DATACENTER_TOP_ZN_6 0.000 0.000 0.062 -130.152 0.000 0.000 0.943 5.965 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -30.698
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7189.558 0.000 0.000 19.442 67.796 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -392.538
GROUNDFLOOR_PLENUM 0.772 -124.404 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.181 123.257 0.000 0.000 0.000 -0.807 -0.000
MIDFLOOR_PLENUM 4.946 -961.602 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 21.298 949.149 0.000 0.000 0.000 -13.792 -0.000
TOPFLOOR_PLENUM 5.563 -163.776 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.208 157.380 0.000 0.000 0.000 -1.375 -0.001
Total Facility 11.282 -1249.782 6.437 -22540.774 0.000 0.000 1527.567 3705.397 15213.411 2820.034 0.000 80.813 2033.371 0.000 -788.051 0.000 -47.692 -772.016


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 06-FEB-04:02 0.00 0.00 0.00 -109231.06 0.00 0.00 0.00 1166.43 13457.54 0.00 0.00 0.00 94607.09 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 02-JAN-04:02 0.00 0.00 0.00 -99789.01 0.00 0.00 0.00 1047.53 8057.15 0.00 0.00 0.00 90684.32 0.00 -0.00 0.00 0.00 0.00
CORE_MID 27-FEB-04:02 0.00 0.00 0.00 -890837.08 0.00 0.00 0.00 10475.32 80571.20 0.00 0.00 0.00 799790.56 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 11-SEP-03:02 0.00 0.00 0.00 -91301.90 0.00 0.00 0.00 1047.53 8057.12 0.00 0.00 0.00 82197.25 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 02-JUL-16:21 0.00 0.00 0.00 -21466.24 0.00 0.00 39.58 80.80 758.77 5390.93 0.00 171.23 15024.94 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 29-MAY-08:51 0.00 0.00 0.00 -17868.71 0.00 0.00 21.52 52.07 488.98 11250.29 0.00 222.01 5833.84 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 09-OCT-12:52 0.00 0.00 0.00 -23066.86 0.00 0.00 35.04 80.80 758.78 14069.67 0.00 13.28 8109.29 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 02-JUL-16:21 0.00 0.00 0.00 -24559.73 0.00 0.00 18.06 52.07 488.98 10410.88 0.00 97.32 13492.43 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 28-MAY-15:31 0.00 0.00 0.00 -207574.06 0.00 0.00 392.53 807.98 7587.73 50272.25 0.00 12620.26 135893.31 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 29-MAY-08:51 0.00 0.00 0.00 -185364.56 0.00 0.00 210.24 520.69 4889.82 111631.50 0.00 4952.86 63159.45 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 01-OCT-13:11 0.00 0.00 0.00 -228705.66 0.00 0.00 331.45 807.99 7587.84 146075.27 0.00 1502.42 72400.68 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 28-MAY-15:31 0.00 0.00 0.00 -206359.79 0.00 0.00 186.46 520.69 4889.79 126275.94 0.00 7377.21 67109.71 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 02-JUL-13:12 0.00 0.00 0.00 -23767.01 0.00 0.00 38.41 80.80 758.77 4759.96 0.00 634.05 17495.02 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 30-APR-10:02 0.00 0.00 0.00 -19303.98 0.00 0.00 21.97 52.07 488.98 9143.91 0.00 94.15 9502.89 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 01-OCT-15:21 0.00 0.00 0.00 -26295.84 0.00 0.00 32.42 80.80 758.78 8340.73 0.00 148.10 16935.01 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 28-MAY-16:31 0.00 0.00 0.00 -21894.95 0.00 0.00 15.63 52.07 488.98 11229.91 0.00 893.41 9214.94 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 16-APR-22:35 0.00 0.00 0.00 -7756.40 0.00 0.00 0.00 28.94 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -66.96
DATACENTER_MID_ZN_6 12-APR-16:00 0.00 0.00 0.00 -73376.97 0.00 0.00 993.76 5208.47 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -10769.47
DATACENTER_TOP_ZN_6 16-APR-20:52 0.00 0.00 0.00 -7487.81 0.00 0.00 0.00 28.94 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -335.55
DATACENTER_BASEMENT_ZN_6 15-AUG-23:42 0.00 0.00 0.00 -370173.97 0.00 0.00 0.00 328.88 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -9787.44
GROUNDFLOOR_PLENUM 03-JUL-05:13 0.00 -19317.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75.88 19241.31 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 05-JUL-05:02 0.00 -143773.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 929.83 142843.39 0.00 -0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 12-JUN-13:50 0.00 -31891.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 368.39 31523.14 0.00 -0.00 0.00 0.00 0.00
Total Facility 17-APR-05:02 0.00 -88134.89 0.00 -2165464.61 0.00 0.00 15599.09 39207.80 623236.89 0.00 0.00 0.00 1606915.55 0.00 -31355.54 0.00 -4.30 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 10-JUN-16:01 0.00 0.00 35445.80 0.00 0.00 0.00 520.12 1166.43 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -50589.89
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP 02-JAN-05:01 0.00 0.00 61811.42 0.00 0.00 0.00 0.00 2095.06 8057.12 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -71963.61
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 21-DEC-06:02 0.00 0.00 31611.91 0.00 0.00 0.00 1418.66 2630.56 10116.97 0.00 0.00 0.00 0.00 0.00 -35244.56 0.00 -103.66 -10429.89
PERIMETER_MID_ZN_2 21-DEC-06:02 0.00 0.00 16857.55 0.00 0.00 0.00 914.61 1695.23 6519.76 0.00 0.00 0.00 0.00 0.00 -23478.36 0.00 -69.09 -2439.69
PERIMETER_MID_ZN_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 02-JAN-06:06 0.00 0.00 636.34 0.00 0.00 0.00 871.44 1695.23 6519.72 0.00 0.00 0.00 12438.60 0.00 -22161.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 02-JAN-04:02 0.00 0.00 16886.51 0.00 0.00 0.00 0.00 131.53 1011.70 0.00 0.00 0.00 0.00 0.00 -2285.30 0.00 0.00 -15744.43
PERIMETER_TOP_ZN_2 02-JAN-04:02 0.00 0.00 11556.07 0.00 0.00 0.00 0.00 84.76 651.98 0.00 0.00 0.00 0.00 0.00 -1562.58 0.00 0.00 -10730.22
PERIMETER_TOP_ZN_1 02-JAN-05:01 0.00 0.00 16403.13 0.00 0.00 0.00 0.00 263.06 1011.71 0.00 0.00 0.00 0.00 0.00 -2556.55 0.00 0.00 -15121.36
PERIMETER_TOP_ZN_4 02-JAN-05:01 0.00 0.00 11135.95 0.00 0.00 0.00 0.00 169.52 651.97 0.00 0.00 0.00 0.00 0.00 -1712.87 0.00 0.00 -10244.57
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 01-JAN-14:00 0.00 0.00 334.99 0.00 0.00 0.00 6.16 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2318.70
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 29-DEC-04:02 10769.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -582.05 -10187.56
MIDFLOOR_PLENUM 11-SEP-03:02 97402.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -97402.57
TOPFLOOR_PLENUM 27-FEB-06:03 19838.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -22.62 -19815.44
Total Facility 02-JAN-06:01 -1124064.14 1208717.09 113117.65 -1208717.09 0.00 0.00 17496.38 39207.80 268362.69 0.00 0.00 0.00 816459.66 0.00 -130580.04 0.00 0.00 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 10.9478 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.3191 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 103.7899 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 97.6621 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 11.1221 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.0302 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.0003 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.0003 0.2000 1.0000 Not calculated 1.2002 0.2000    
AIRLOOP DATACENTER BASEMENT 21.9691 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.9694 0.0154 1.0000 Not calculated 0.3384 0.0154    
AIRLOOP DATACENTER BOT 0.4903 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4903 0.0319 1.0000 Not calculated 0.0156 0.0319    
AIRLOOP DATACENTER MID 4.6697 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.6697 0.0335 1.0000 Not calculated 0.1563 0.0335    
AIRLOOP DATACENTER TOP 0.4698 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4698 0.0333 1.0000 Not calculated 0.0156 0.0333    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.4739 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.3600 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 51.8950 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 32.5719 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.5611 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.5021 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.0003 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.0003 1.0000 1.0000 Not calculated 1.2002 0.2000    
AIRLOOP DATACENTER BASEMENT 21.9691 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.9691 1.0000 1.0000 Not calculated 0.3384 0.0154    
AIRLOOP DATACENTER BOT 0.4903 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4903 1.0000 1.0000 Not calculated 0.0156 0.0319    
AIRLOOP DATACENTER MID 4.6697 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.6697 1.0000 1.0000 Not calculated 0.1563 0.0335    
AIRLOOP DATACENTER TOP 0.4698 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4698 1.0000 1.0000 Not calculated 0.0156 0.0333    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.0003 6.0003 6.0003 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.3046 6.3046 1.9670 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 59.7906 59.7906 19.3722 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.1299 6.1299 2.0045 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2179 1.2179 0.3654 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9497 0.9497 0.2849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2391 1.2391 0.3717 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2365 1.2365 0.3709 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.8065 11.8065 3.5419 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.8022 9.8022 2.9407 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.9119 11.9119 3.5736 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.4788 10.4788 3.1436 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3809 1.3809 0.4143 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0474 1.0474 0.3142 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3838 1.3838 0.4151 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1801 1.1801 0.3540 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4903 0.4903 0.4903 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.6697 4.6697 4.6697 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4698 0.4698 0.4698 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.9691 21.9691 21.9691 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 10.9478 10.3191 10.9478 3.3600 0.0000 1.0000
VAV_MID WITH REHEAT 103.7899 97.6621 103.7899 32.5719 0.0000 1.0000
VAV_TOP WITH REHEAT 11.1221 11.0302 11.1221 3.5021 0.0000 1.0000
CAV_BAS 6.0003 6.0003 6.0003 6.0003 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.9691 21.9694 21.9691 21.9691 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4903 0.4903 0.4903 0.4903 0.0156 1.0000
AIRLOOP DATACENTER MID 4.6697 4.6697 4.6697 4.6697 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4698 0.4698 0.4698 0.4698 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.0003 6.0003 6.0003 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.1523 3.1523 1.9670 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 29.8953 29.8953 19.3722 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.0650 3.0650 2.0045 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6090 0.6090 0.3654 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4749 0.4749 0.2849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6195 0.6195 0.3717 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6182 0.6182 0.3709 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.9032 5.9032 3.5419 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.9011 4.9011 2.9407 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.9559 5.9559 3.5736 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.2394 5.2394 3.1436 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6904 0.6904 0.4143 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5237 0.5237 0.3142 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6919 0.6919 0.4151 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5900 0.5900 0.3540 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4903 0.4903 0.4903 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.6697 4.6697 4.6697 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4698 0.4698 0.4698 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.9691 21.9691 21.9691 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.4739 3.3600 3.3600 3.3600 0.0000 1.0000
VAV_MID WITH REHEAT 51.8950 32.5719 32.5719 32.5719 0.0000 1.0000
VAV_TOP WITH REHEAT 5.5611 3.5021 3.5021 3.5021 0.0000 1.0000
CAV_BAS 6.0003 6.0003 6.0003 6.0003 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.9691 21.9691 21.9691 21.9691 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4903 0.4903 0.4903 0.4903 0.0156 1.0000
AIRLOOP DATACENTER MID 4.6697 4.6697 4.6697 4.6697 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4698 0.4698 0.4698 0.4698 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 1069.17
Number of hours not met 1069.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 22.01 207455.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 6662.79 583147.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 3705.40 344557.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 670.70 54335.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5871.99 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 87.32 5474.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2768.50 245998.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 1329.53 71743.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1974.33 93058.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 82.17 28596.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 559.57 72853.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 15213.41 34348.76
Natural Gas 0.00 581.58
Additional 0.00 0.00
Total 15213.41 34930.34


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 79.99
Space Heating 0.00
Space Cooling 143.84
Fans (All) 59.77
Service Water Heating 0.00
Receptacle Equipment 328.44
Miscellaneous (All) 741.55
Subtotal 741.55


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.48
Service Water Heating 12.08
Miscellaneous (All) 12.56
Subtotal 12.56


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 10.61
Space Heating 0.06
Space Cooling 19.07
Fans (All) 7.93
Service Water Heating 1.60
Receptacle Equipment 43.55
Miscellaneous 17.17


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2645. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4487. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 2347. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 7320.33 1439.67 0.00 0.00 0.00
CORE_BOTTOM 8633.33 126.67 0.00 0.00 0.00
CORE_MID 8749.50 10.50 0.00 0.00 0.00
CORE_TOP 8740.33 19.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8698.00 62.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8679.67 80.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8584.67 175.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7827.67 932.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8521.33 238.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8421.00 339.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8207.67 552.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8014.00 746.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8489.50 270.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8374.67 385.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8212.50 547.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8091.33 668.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 6201.00 2559.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 6191.00 2569.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 6778.17 1981.83 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7285.17 1474.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8752.00 8.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8309.00 451.00 0.00 0.00 0.00
Min 6191.00 0.00 0.00 0.00 0.00
Max 8760.00 2569.00 0.00 0.00 0.00
Average 8080.08 679.92 0.00 0.00 0.00
Sum 185841.83 15638.17 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 365035.50 3580.50 0.00 0.00 0.00
CORE_BOTTOM 330570.00 243.00 0.00 0.00 0.00
CORE_MID 330790.00 23.00 0.00 0.00 0.00
CORE_TOP 330786.00 27.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1360.17 907.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1348.67 919.33 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1506.17 761.83 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 82005.17 21389.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 365035.50 21389.83 0.00 0.00 0.00
Average 79123.94 1210.97 0.00 0.00 0.00
Sum 1819850.67 27852.33 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 5379.33 3380.67 0.00 0.00 0.00
CORE_BOTTOM 7243.83 1516.17 0.00 0.00 0.00
CORE_MID 7392.33 1367.67 0.00 0.00 0.00
CORE_TOP 7270.17 1489.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 7173.33 1586.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 7548.83 1211.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 6879.17 1880.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 6441.17 2318.83 0.00 0.00 0.00
PERIMETER_MID_ZN_3 6985.83 1774.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 6946.33 1813.67 0.00 0.00 0.00
PERIMETER_MID_ZN_1 6658.67 2101.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 6785.83 1974.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 7023.33 1736.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 6935.17 1824.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 6713.00 2047.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 6835.67 1924.33 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7153.17 1606.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7143.17 1616.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7542.50 1217.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7549.50 1210.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 6158.33 2601.67 0.00 0.00 0.00
MIDFLOOR_PLENUM 5782.17 2977.83 0.00 0.00 0.00
TOPFLOOR_PLENUM 4774.50 3985.50 0.00 0.00 0.00
Min 4774.50 1210.50 0.00 0.00 0.00
Max 7549.50 3985.50 0.00 0.00 0.00
Average 6796.32 1963.68 0.00 0.00 0.00
Sum 156315.33 45164.67 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 335155.67 33460.33 0.00 0.00 0.00
CORE_BOTTOM 328051.67 2761.33 0.00 0.00 0.00
CORE_MID 328380.17 2432.83 0.00 0.00 0.00
CORE_TOP 327806.00 3007.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38923.50 1.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18353.83 0.17 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38923.50 1.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38923.83 1.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24908.83 0.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38923.83 1.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1655.83 612.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1646.33 621.67 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1792.50 475.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 87390.67 16004.33 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 335155.67 33460.33 0.00 0.00 0.00
Average 77753.14 2581.78 0.00 0.00 0.00
Sum 1788322.17 59380.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:25

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.618984E+11 103951.05 02-JAN-04:02 6.67 6.44 0.567015E+10 7499.04 04-JAN-10:39 14.27 11.27
February 0.551110E+11 109229.72 06-FEB-04:02 10.55 9.45 0.514293E+10 7499.07 02-FEB-10:09 10.55 9.45
March 0.633248E+11 99597.32 20-MAR-03:02 16.45 11.38 0.613622E+10 7499.00 16-MAR-09:00 16.45 11.38
April 0.593189E+11 103960.08 28-APR-03:02 28.85 17.10 0.545287E+10 7499.03 04-APR-09:09 28.85 17.10
May 0.633768E+11 101121.25 29-MAY-17:30 40.55 21.29 0.590449E+10 7498.86 05-MAY-09:00 40.55 21.29
June 0.661049E+11 97197.30 04-JUN-16:18 42.13 22.34 0.588556E+10 7498.86 07-JUN-09:20 37.90 20.70
July 0.701452E+11 90226.06 04-JUL-17:50 40.15 24.18 0.547769E+10 7498.75 27-JUL-13:20 30.70 26.49
August 0.800719E+11 89891.21 22-AUG-03:02 25.88 25.10 0.614087E+10 7498.73 24-AUG-09:20 29.43 26.79
September 0.701609E+11 91295.74 26-SEP-03:02 25.65 21.91 0.545596E+10 7498.75 15-SEP-13:20 25.65 21.91
October 0.723871E+11 101896.69 22-OCT-14:58 31.00 17.63 0.567501E+10 7498.92 17-OCT-09:30 31.00 17.63
November 0.695645E+11 100328.77 25-NOV-04:02 10.85 9.43 0.561917E+10 7498.96 09-NOV-10:09 10.85 9.43
December 0.668903E+11 104029.50 04-DEC-04:02 8.72 8.07 0.547563E+10 7498.95 13-DEC-10:20 18.53 13.02
                     
Annual Sum or Average 0.798355E+12         0.680365E+11        
Minimum of Months 0.551110E+11 89891.21   6.67 6.44 0.514293E+10 7498.73   10.55 9.43
Maximum of Months 0.800719E+11 109229.72   42.13 25.10 0.614087E+10 7499.07   40.55 26.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.487554E+11 99916.88 02-JAN-04:02 6.67 6.44 0.508167E+10 6734.74 09-JAN-10:09 12.05 10.60
February 0.504797E+11 99228.75 27-FEB-04:02 11.72 10.91 0.460714E+10 6734.76 02-FEB-10:09 11.72 10.91
March 0.686045E+11 96286.94 20-MAR-03:02 16.45 11.38 0.549929E+10 6734.76 27-MAR-09:09 23.33 16.01
April 0.751122E+11 91047.23 03-APR-05:03 22.60 18.05 0.487679E+10 6734.75 04-APR-09:09 26.87 18.01
May 0.709245E+11 90543.43 23-MAY-03:02 28.47 24.77 0.528197E+10 6734.55 08-MAY-13:09 28.47 24.77
June 0.723878E+11 89334.66 12-JUN-05:02 34.12 19.12 0.526629E+10 6734.60 12-JUN-13:09 43.40 22.40
July 0.755286E+11 88616.29 03-JUL-05:05 29.37 24.69 0.489326E+10 6734.54 17-JUL-13:00 33.90 27.72
August 0.852228E+11 89718.17 07-AUG-05:01 29.53 24.79 0.549526E+10 6734.54 21-AUG-13:00 28.90 27.65
September 0.645272E+11 92135.53 09-SEP-03:02 24.35 23.85 0.488218E+10 6734.55 05-SEP-09:09 24.35 23.85
October 0.679997E+11 96183.40 31-OCT-03:02 16.50 14.83 0.507809E+10 6734.66 24-OCT-09:09 16.50 14.83
November 0.634625E+11 98643.62 27-NOV-04:02 10.65 9.14 0.503182E+10 6734.70 16-NOV-10:09 10.65 9.14
December 0.592137E+11 97215.02 04-DEC-04:02 8.72 8.07 0.490419E+10 6734.72 18-DEC-10:00 21.70 14.67
                     
Annual Sum or Average 0.802218E+12         0.608980E+11        
Minimum of Months 0.487554E+11 88616.29   6.67 6.44 0.460714E+10 6734.54   10.65 9.14
Maximum of Months 0.852228E+11 99916.88   34.12 24.79 0.549929E+10 6734.76   43.40 27.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.373440E+11 84447.06 14-JAN-06:02 14.50 12.49 0.504779E+10 6734.71 04-JAN-10:00 14.50 12.49
February 0.386929E+11 89117.55 27-FEB-04:02 11.72 10.91 0.458968E+10 6734.74 02-FEB-10:09 11.72 10.91
March 0.525900E+11 88362.11 14-MAR-03:02 20.88 16.42 0.549435E+10 6734.76 27-MAR-09:09 23.33 16.01
April 0.550784E+11 88104.09 10-APR-03:02 18.93 13.53 0.487506E+10 6734.75 04-APR-09:09 18.93 13.53
May 0.611170E+11 85296.08 23-MAY-03:02 28.47 24.77 0.527746E+10 6734.64 01-MAY-09:20 28.47 24.77
June 0.596061E+11 85511.90 28-JUN-03:02 26.40 25.45 0.526387E+10 6734.62 12-JUN-13:09 26.40 25.45
July 0.579266E+11 86492.59 19-JUL-03:02 23.42 23.42 0.488985E+10 6734.56 18-JUL-13:09 23.42 23.42
August 0.598551E+11 85206.90 24-AUG-03:02 25.58 24.96 0.549398E+10 6734.56 21-AUG-13:09 25.58 24.96
September 0.532801E+11 86005.11 05-SEP-03:02 26.38 25.08 0.488087E+10 6734.57 08-SEP-13:30 28.50 25.88
October 0.535129E+11 88145.15 24-OCT-03:02 18.57 14.45 0.507382E+10 6734.66 16-OCT-09:09 18.57 14.45
November 0.468661E+11 85450.51 21-NOV-05:03 13.53 10.41 0.502049E+10 6734.70 06-NOV-10:09 13.53 10.41
December 0.393783E+11 84218.72 16-DEC-06:02 14.32 11.10 0.487296E+10 6734.67 13-DEC-10:09 14.32 11.10
                     
Annual Sum or Average 0.615248E+12         0.607802E+11        
Minimum of Months 0.373440E+11 84218.72   11.72 10.41 0.458968E+10 6734.56   11.72 10.41
Maximum of Months 0.611170E+11 89117.55   28.47 25.45 0.549435E+10 6734.76   28.50 25.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.273149E+11 38168.36 26-JAN-16:20 19.67 13.02 0.474876E+10 6734.60 13-JAN-10:00 19.67 13.02
February 0.321693E+11 83378.14 23-FEB-06:03 15.05 13.57 0.449975E+10 6734.64 24-FEB-10:09 20.63 14.93
March 0.510000E+11 90633.37 30-MAR-03:02 21.95 16.80 0.547620E+10 6734.75 27-MAR-09:09 21.95 16.80
April 0.609669E+11 88943.51 17-APR-05:03 24.22 18.83 0.487673E+10 6734.74 04-APR-09:09 24.22 18.83
May 0.715239E+11 88053.44 30-MAY-05:02 30.25 21.57 0.528342E+10 6734.59 01-MAY-09:09 30.25 21.57
June 0.701220E+11 89421.07 12-JUN-05:02 34.12 19.12 0.526811E+10 6734.62 12-JUN-13:09 43.40 22.40
July 0.669360E+11 88435.22 28-JUL-03:02 27.00 25.79 0.489626E+10 6734.53 17-JUL-13:00 27.00 25.79
August 0.671953E+11 90084.88 21-AUG-03:02 25.87 25.24 0.549750E+10 6734.54 21-AUG-13:00 28.90 27.65
September 0.578177E+11 91320.89 11-SEP-03:02 26.07 25.28 0.488246E+10 6734.54 08-SEP-13:00 26.07 25.28
October 0.535585E+11 89812.63 05-OCT-03:02 22.73 17.70 0.506646E+10 6734.65 30-OCT-09:09 21.27 16.75
November 0.405833E+11 85308.42 01-NOV-05:02 15.60 12.04 0.497118E+10 6734.68 06-NOV-10:09 23.13 17.24
December 0.296680E+11 64695.22 29-DEC-06:03 16.53 12.55 0.469849E+10 6734.61 29-DEC-14:00 19.50 14.92
                     
Annual Sum or Average 0.628856E+12         0.601653E+11        
Minimum of Months 0.273149E+11 38168.36   15.05 12.04 0.449975E+10 6734.53   19.50 13.02
Maximum of Months 0.715239E+11 91320.89   34.12 25.79 0.549750E+10 6734.75   43.40 27.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.502521E+10 5168.16 26-JAN-14:10 22.35 13.84 0.605802E+09 845.61 13-JAN-14:09 22.35 13.84
February 0.586892E+10 6947.13 23-FEB-14:30 26.10 14.00 0.564956E+09 845.61 27-FEB-10:09 16.10 13.56
March 0.976868E+10 14150.29 14-MAR-05:03 20.70 16.42 0.687091E+09 845.63 30-MAR-13:50 32.05 19.26
April 0.135760E+11 17247.52 17-APR-05:02 24.22 18.83 0.612643E+09 845.63 04-APR-09:09 24.22 18.83
May 0.149771E+11 20475.13 29-MAY-16:11 41.17 21.49 0.664734E+09 845.61 08-MAY-13:09 41.17 21.49
June 0.155686E+11 20164.92 11-JUN-17:02 42.88 23.08 0.662379E+09 845.64 12-JUN-13:00 43.90 22.36
July 0.154121E+11 21474.38 02-JUL-16:21 40.35 26.46 0.615987E+09 845.60 10-JUL-13:09 39.20 26.78
August 0.161640E+11 19657.47 06-AUG-15:01 36.30 26.24 0.690769E+09 845.60 21-AUG-13:20 29.43 27.58
September 0.115971E+11 17183.10 05-SEP-03:02 26.38 25.08 0.613523E+09 845.61 08-SEP-13:30 28.50 25.88
October 0.104546E+11 15461.45 11-OCT-05:03 23.85 20.24 0.636253E+09 845.62 10-OCT-13:00 23.85 20.24
November 0.780053E+10 9034.84 06-NOV-06:03 14.70 13.68 0.625963E+09 845.63 06-NOV-14:50 28.48 18.19
December 0.618403E+10 6111.32 26-DEC-14:10 22.68 14.39 0.599645E+09 845.62 18-DEC-10:00 22.68 14.39
                     
Annual Sum or Average 0.132397E+12         0.757975E+10        
Minimum of Months 0.502521E+10 5168.16   14.70 13.68 0.564956E+09 845.60   16.10 13.56
Maximum of Months 0.161640E+11 21474.38   42.88 26.46 0.690769E+09 845.64   43.90 27.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.403047E+10 4508.41 26-JAN-10:20 18.10 12.94 0.397721E+09 544.95 04-JAN-10:00 18.10 12.94
February 0.479077E+10 7097.53 21-FEB-09:50 18.65 13.10 0.364827E+09 544.95 02-FEB-10:09 18.65 13.10
March 0.785013E+10 11885.31 26-MAR-09:32 24.67 14.70 0.442377E+09 544.96 27-MAR-09:20 23.77 16.23
April 0.106403E+11 17253.71 16-APR-09:42 34.62 21.58 0.394585E+09 545.37 28-APR-09:50 33.47 18.33
May 0.120288E+11 17873.96 29-MAY-08:51 33.70 20.93 0.428584E+09 545.25 26-MAY-09:00 33.70 20.93
June 0.113207E+11 15997.03 11-JUN-10:22 37.75 25.19 0.426636E+09 545.14 12-JUN-09:00 40.00 22.14
July 0.105026E+11 16552.48 02-JUL-15:41 40.33 26.36 0.396534E+09 545.09 07-JUL-09:00 36.90 24.55
August 0.103761E+11 16125.85 06-AUG-10:22 32.90 25.51 0.444449E+09 545.01 07-AUG-09:00 33.20 25.77
September 0.861180E+10 11630.22 11-SEP-05:03 25.73 25.09 0.394924E+09 544.94 08-SEP-13:30 25.73 25.09
October 0.818900E+10 13649.40 09-OCT-10:13 28.37 20.42 0.409585E+09 544.95 23-OCT-09:00 25.70 17.02
November 0.609505E+10 6745.81 13-NOV-09:50 21.78 14.28 0.402908E+09 544.95 06-NOV-14:50 21.78 14.28
December 0.460184E+10 5008.55 01-DEC-10:00 18.30 11.37 0.385825E+09 544.95 18-DEC-10:00 21.70 14.67
                     
Annual Sum or Average 0.990376E+11         0.488895E+10        
Minimum of Months 0.403047E+10 4508.41   18.10 11.37 0.364827E+09 544.94   18.10 12.94
Maximum of Months 0.120288E+11 17873.96   40.33 26.36 0.444449E+09 545.37   40.00 25.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.839025E+10 12576.52 12-JAN-13:40 22.93 13.82 0.623645E+09 845.89 12-JAN-14:20 23.40 14.05
February 0.925672E+10 22076.29 20-FEB-14:02 26.38 13.56 0.571615E+09 846.13 07-FEB-14:50 26.38 13.56
March 0.138044E+11 21384.44 12-MAR-12:13 30.03 18.68 0.689519E+09 846.07 08-MAR-14:00 30.03 18.68
April 0.160840E+11 21642.96 16-APR-11:42 37.98 21.94 0.613511E+09 845.96 06-APR-13:00 37.98 21.94
May 0.156255E+11 20920.49 29-MAY-16:11 41.17 21.49 0.664917E+09 845.92 05-MAY-13:20 41.17 21.49
June 0.155457E+11 20152.06 11-JUN-16:22 43.25 23.12 0.662366E+09 846.12 12-JUN-13:20 43.50 22.39
July 0.155323E+11 21826.65 02-JUL-16:21 40.35 26.46 0.616014E+09 846.08 05-JUL-13:20 37.90 25.56
August 0.167710E+11 20805.29 06-AUG-15:01 36.30 26.24 0.690937E+09 846.16 09-AUG-13:20 34.53 26.23
September 0.137941E+11 21889.53 24-SEP-13:22 34.85 24.63 0.614076E+09 846.02 19-SEP-13:00 34.85 24.63
October 0.157945E+11 23070.20 09-OCT-12:52 32.30 19.97 0.639227E+09 867.46 02-OCT-13:30 32.30 19.97
November 0.139213E+11 21636.63 19-NOV-12:53 25.80 16.93 0.631367E+09 846.27 24-NOV-14:00 24.80 13.62
December 0.102379E+11 21285.83 03-DEC-12:02 22.92 14.22 0.609543E+09 846.21 04-DEC-14:00 23.20 14.27
                     
Annual Sum or Average 0.164758E+12         0.762674E+10        
Minimum of Months 0.839025E+10 12576.52   22.92 13.56 0.571615E+09 845.89   23.20 13.56
Maximum of Months 0.167710E+11 23070.20   43.25 26.46 0.690937E+09 867.46   43.50 26.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.567662E+10 7243.53 31-JAN-16:00 21.10 11.23 0.393570E+09 544.95 13-JAN-14:09 21.10 11.23
February 0.689408E+10 20874.59 20-FEB-16:02 25.43 14.23 0.369178E+09 544.95 15-FEB-14:50 25.43 14.23
March 0.121444E+11 19808.32 26-MAR-16:12 29.73 16.34 0.445786E+09 544.96 30-MAR-13:50 32.05 19.26
April 0.174553E+11 22754.91 30-APR-16:21 37.45 18.00 0.396404E+09 544.96 04-APR-09:09 37.45 18.00
May 0.146943E+11 22379.18 28-MAY-16:21 42.00 19.52 0.428841E+09 544.94 05-MAY-09:00 42.00 19.52
June 0.156288E+11 22436.19 18-JUN-15:52 33.10 23.21 0.427463E+09 544.95 12-JUN-13:09 33.10 23.21
July 0.155865E+11 24575.11 02-JUL-16:21 40.35 26.46 0.397692E+09 544.94 05-JUL-13:00 37.90 25.56
August 0.185566E+11 22365.96 06-AUG-15:41 36.30 26.24 0.446266E+09 544.94 21-AUG-13:20 29.43 27.58
September 0.112580E+11 22119.60 24-SEP-15:22 34.95 25.05 0.395821E+09 544.94 08-SEP-13:30 34.95 25.05
October 0.115501E+11 22262.12 15-OCT-15:22 32.35 19.26 0.411777E+09 544.95 10-OCT-13:00 32.35 19.26
November 0.980347E+10 16368.41 06-NOV-06:03 14.70 13.68 0.407572E+09 544.97 06-NOV-14:50 28.48 18.19
December 0.840906E+10 16473.23 29-DEC-06:03 16.53 12.55 0.396329E+09 544.95 18-DEC-10:00 16.53 12.55
                     
Annual Sum or Average 0.147657E+12         0.491670E+10        
Minimum of Months 0.567662E+10 7243.53   14.70 11.23 0.369178E+09 544.94   16.53 11.23
Maximum of Months 0.185566E+11 24575.11   42.00 26.46 0.446266E+09 544.97   42.00 27.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.381768E+10 4060.34 14-JAN-06:02 14.50 12.49 0.549984E+09 845.60 26-JAN-14:00 21.60 13.66
February 0.440536E+10 5793.28 24-FEB-15:00 26.40 17.38 0.536227E+09 845.61 24-FEB-14:20 26.40 17.38
March 0.734410E+10 14190.40 11-MAR-06:02 23.80 17.15 0.678988E+09 845.63 30-MAR-13:50 32.05 19.26
April 0.105327E+11 15096.75 16-APR-17:12 37.53 22.72 0.612480E+09 845.63 04-APR-09:09 37.53 22.72
May 0.139282E+11 20757.40 28-MAY-15:31 42.27 19.32 0.664932E+09 845.62 01-MAY-09:20 42.27 19.32
June 0.139811E+11 19544.74 11-JUN-17:02 42.88 23.08 0.662714E+09 845.76 12-JUN-13:00 43.90 22.36
July 0.129739E+11 19519.38 02-JUL-16:42 40.32 26.53 0.616541E+09 845.60 10-JUL-13:09 39.20 26.78
August 0.123814E+11 16589.55 07-AUG-05:03 29.53 24.79 0.691316E+09 845.60 21-AUG-13:20 29.43 27.58
September 0.995001E+10 16677.96 05-SEP-03:02 26.38 25.08 0.613654E+09 845.60 08-SEP-13:30 28.50 25.88
October 0.827476E+10 14472.00 03-OCT-05:03 22.92 17.52 0.633279E+09 845.61 16-OCT-09:09 26.53 17.36
November 0.566611E+10 6134.11 09-NOV-14:30 29.30 17.79 0.607934E+09 845.61 15-NOV-14:39 26.43 17.71
December 0.417224E+10 4268.30 03-DEC-14:13 24.20 14.19 0.545230E+09 833.63 29-DEC-14:00 19.50 14.92
                     
Annual Sum or Average 0.107428E+12         0.741328E+10        
Minimum of Months 0.381768E+10 4060.34   14.50 12.49 0.536227E+09 833.63   19.50 13.66
Maximum of Months 0.139811E+11 20757.40   42.88 26.53 0.691316E+09 845.76   43.90 27.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.336714E+10 3555.07 08-JAN-13:32 21.57 12.76 0.269474E+09 521.19 26-JAN-11:20 20.27 13.36
February 0.400092E+10 6183.97 22-FEB-10:00 20.60 13.92 0.260065E+09 521.21 15-FEB-11:20 20.60 13.92
March 0.683039E+10 12412.53 12-MAR-11:23 28.95 18.26 0.323022E+09 521.21 16-MAR-10:20 20.53 15.55
April 0.974388E+10 18167.11 16-APR-09:12 33.47 21.34 0.291157E+09 521.78 17-APR-10:50 34.22 22.89
May 0.119064E+11 18541.85 29-MAY-08:51 33.70 20.93 0.315638E+09 521.76 26-MAY-10:00 33.70 20.93
June 0.109092E+11 16682.48 11-JUN-10:22 37.75 25.19 0.313884E+09 521.72 12-JUN-10:00 41.40 22.35
July 0.962571E+10 16519.72 02-JUL-12:02 37.38 26.47 0.292971E+09 521.62 06-JUL-10:50 37.57 25.52
August 0.905638E+10 13720.98 06-AUG-15:31 36.30 26.24 0.327247E+09 521.20 21-AUG-12:09 30.20 27.51
September 0.788013E+10 15032.16 24-SEP-10:13 31.60 25.28 0.290869E+09 521.20 29-SEP-14:20 33.83 22.63
October 0.725084E+10 17084.87 01-OCT-09:52 29.70 19.34 0.300714E+09 521.22 10-OCT-14:20 31.63 20.81
November 0.508741E+10 6180.83 09-NOV-10:00 24.50 17.90 0.291967E+09 521.21 06-NOV-15:20 24.50 17.90
December 0.360696E+10 4094.76 01-DEC-10:00 18.30 11.37 0.265341E+09 521.20 01-DEC-11:20 20.70 12.30
                     
Annual Sum or Average 0.892654E+11         0.354235E+10        
Minimum of Months 0.336714E+10 3555.07   18.30 11.37 0.260065E+09 521.19   20.27 12.30
Maximum of Months 0.119064E+11 18541.85   37.75 26.47 0.327247E+09 521.78   41.40 27.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.766998E+10 19532.51 08-JAN-13:32 21.57 12.76 0.616705E+09 845.91 11-JAN-14:00 22.20 11.82
February 0.815938E+10 21358.36 20-FEB-13:52 26.40 13.47 0.565694E+09 846.03 07-FEB-14:00 26.40 13.47
March 0.117338E+11 21297.94 12-MAR-13:22 30.95 19.20 0.687742E+09 847.90 30-MAR-13:50 32.05 19.26
April 0.132010E+11 20807.26 16-APR-11:52 38.20 21.94 0.613952E+09 845.86 21-APR-13:00 35.00 19.79
May 0.145327E+11 21077.93 28-MAY-15:31 42.27 19.32 0.665105E+09 845.83 04-MAY-13:00 42.27 19.32
June 0.138828E+11 18514.64 11-JUN-16:22 43.25 23.12 0.662691E+09 845.68 12-JUN-13:00 43.90 22.36
July 0.130703E+11 19866.79 30-JUL-15:32 34.73 27.14 0.616565E+09 845.62 10-JUL-13:09 34.73 27.14
August 0.130662E+11 20003.02 06-AUG-14:51 36.30 26.24 0.691566E+09 845.78 07-AUG-13:00 37.20 26.26
September 0.123332E+11 20757.08 24-SEP-16:12 34.57 25.35 0.614391E+09 850.66 28-SEP-13:39 35.37 22.75
October 0.142197E+11 22870.36 01-OCT-13:11 35.43 19.93 0.639662E+09 877.09 02-OCT-13:50 36.37 21.07
November 0.124258E+11 21631.53 11-NOV-12:02 27.58 17.19 0.629846E+09 856.02 01-NOV-13:39 27.58 17.19
December 0.841440E+10 20688.27 03-DEC-12:53 24.00 14.17 0.602447E+09 845.93 04-DEC-14:00 23.20 14.27
                     
Annual Sum or Average 0.142709E+12         0.760637E+10        
Minimum of Months 0.766998E+10 18514.64   21.57 12.76 0.565694E+09 845.62   22.20 11.82
Maximum of Months 0.145327E+11 22870.36   43.25 27.14 0.691566E+09 877.09   43.90 27.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.371254E+10 5129.19 31-JAN-16:10 20.95 11.21 0.361895E+09 544.94 25-JAN-14:00 20.95 11.21
February 0.429337E+10 7454.26 21-FEB-16:00 26.10 15.66 0.346046E+09 544.95 24-FEB-14:30 26.15 17.19
March 0.730679E+10 16641.04 12-MAR-16:02 31.18 19.88 0.438106E+09 544.96 30-MAR-13:50 32.05 19.26
April 0.104776E+11 19104.66 30-APR-16:11 37.57 18.06 0.395632E+09 544.95 04-APR-09:09 37.57 18.06
May 0.123459E+11 20637.36 28-MAY-15:31 42.27 19.32 0.428818E+09 544.95 01-MAY-09:20 42.27 19.32
June 0.119966E+11 18671.21 11-JUN-16:22 43.25 23.12 0.427335E+09 544.95 07-JUN-09:20 43.25 23.12
July 0.103893E+11 18492.31 02-JUL-16:42 40.32 26.53 0.397430E+09 544.94 10-JUL-09:30 33.55 26.55
August 0.100215E+11 18437.69 06-AUG-16:11 36.20 26.31 0.445712E+09 544.94 28-AUG-09:09 30.88 27.50
September 0.844681E+10 18845.57 24-SEP-16:12 34.57 25.35 0.395371E+09 544.94 08-SEP-13:30 34.57 25.35
October 0.768865E+10 18836.35 01-OCT-16:32 34.77 20.19 0.408469E+09 544.95 16-OCT-09:09 26.53 17.36
November 0.567622E+10 8153.10 11-NOV-15:22 28.00 17.36 0.392440E+09 544.95 06-NOV-14:00 28.00 17.36
December 0.406548E+10 5567.63 01-DEC-15:30 22.85 13.56 0.359046E+09 544.94 18-DEC-14:00 22.10 15.00
                     
Annual Sum or Average 0.964207E+11         0.479630E+10        
Minimum of Months 0.371254E+10 5129.19   20.95 11.21 0.346046E+09 544.94   20.95 11.21
Maximum of Months 0.123459E+11 20637.36   43.25 26.53 0.445712E+09 544.96   43.25 27.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.294144E+10 3935.55 26-JAN-15:10 21.37 13.58 0.503140E+09 807.53 26-JAN-14:00 21.37 13.58
February 0.406488E+10 5857.82 23-FEB-14:50 25.90 14.07 0.502174E+09 845.61 24-FEB-14:20 26.07 17.12
March 0.757042E+10 13337.96 30-MAR-05:02 21.37 16.59 0.662846E+09 845.63 30-MAR-13:50 32.05 19.26
April 0.117869E+11 22585.54 30-APR-16:01 37.68 18.13 0.610509E+09 845.63 28-APR-13:20 37.68 18.13
May 0.160112E+11 23646.01 28-MAY-16:31 41.90 19.53 0.664845E+09 845.61 05-MAY-09:00 41.90 19.53
June 0.160306E+11 23411.41 11-JUN-16:22 43.25 23.12 0.662637E+09 845.62 12-JUN-13:09 43.40 22.40
July 0.148449E+11 23774.53 02-JUL-13:12 38.63 26.37 0.616567E+09 845.60 10-JUL-09:09 32.98 26.50
August 0.138302E+11 19555.61 21-AUG-03:02 25.87 25.24 0.691260E+09 845.60 28-AUG-09:09 30.88 27.50
September 0.109634E+11 22757.80 17-SEP-15:22 34.15 26.07 0.612504E+09 845.60 08-SEP-13:39 34.15 26.07
October 0.871994E+10 17338.00 01-OCT-15:21 35.75 20.04 0.625377E+09 845.61 16-OCT-09:20 26.87 17.49
November 0.543937E+10 6498.77 09-NOV-14:50 29.23 17.74 0.579664E+09 845.61 15-NOV-14:30 26.40 17.66
December 0.337656E+10 3904.05 28-DEC-16:30 23.30 15.06 0.499145E+09 798.71 28-DEC-14:00 23.30 15.06
                     
Annual Sum or Average 0.115580E+12         0.723067E+10        
Minimum of Months 0.294144E+10 3904.05   21.37 13.58 0.499145E+09 798.71   21.37 13.58
Maximum of Months 0.160306E+11 23774.53   43.25 26.37 0.691260E+09 845.63   43.40 27.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.275722E+10 3123.41 26-JAN-14:50 21.75 13.69 0.341464E+09 539.57 26-JAN-14:00 21.60 13.66
February 0.362577E+10 5712.13 23-FEB-10:40 22.80 14.32 0.343956E+09 544.95 15-FEB-10:39 22.80 14.32
March 0.694573E+10 10150.85 30-MAR-05:02 21.37 16.59 0.437969E+09 544.96 27-MAR-09:20 21.37 16.59
April 0.107530E+11 19303.45 30-APR-10:02 31.85 16.40 0.395132E+09 545.27 17-APR-09:20 31.85 16.40
May 0.134762E+11 18767.72 29-MAY-09:42 35.45 21.98 0.428849E+09 545.22 26-MAY-09:00 35.45 21.98
June 0.124140E+11 18001.42 11-JUN-10:22 37.75 25.19 0.427028E+09 545.21 13-JUN-09:20 35.17 26.05
July 0.109683E+11 18647.13 02-JUL-09:12 34.77 25.77 0.397300E+09 545.22 05-JUL-09:20 35.67 25.11
August 0.101604E+11 14173.33 06-AUG-15:12 36.30 26.24 0.445300E+09 544.94 28-AUG-09:09 30.88 27.50
September 0.868065E+10 17654.60 17-SEP-15:22 34.15 26.07 0.394655E+09 544.94 08-SEP-13:39 34.15 26.07
October 0.758432E+10 18087.22 01-OCT-10:42 31.62 19.69 0.406986E+09 544.95 16-OCT-09:30 27.20 17.62
November 0.476902E+10 5822.99 09-NOV-10:30 25.75 18.10 0.391960E+09 544.95 06-NOV-14:50 25.75 18.10
December 0.298584E+10 3136.89 01-DEC-15:10 23.22 13.42 0.340549E+09 542.19 01-DEC-14:00 23.22 13.42
                     
Annual Sum or Average 0.951204E+11         0.475115E+10        
Minimum of Months 0.275722E+10 3123.41   21.37 13.42 0.340549E+09 539.57   21.37 13.42
Maximum of Months 0.134762E+11 19303.45   37.75 26.24 0.445300E+09 545.27   35.67 27.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.625814E+10 12079.49 12-JAN-14:20 23.40 14.05 0.585102E+09 845.64 25-JAN-14:00 23.00 13.41
February 0.745148E+10 23757.35 20-FEB-13:32 26.23 13.43 0.547508E+09 845.97 21-FEB-14:00 26.30 15.42
March 0.118779E+11 23817.90 12-MAR-12:13 30.03 18.68 0.680499E+09 846.03 09-MAR-14:00 30.03 18.68
April 0.146171E+11 24374.25 30-APR-13:22 37.15 18.65 0.612793E+09 846.03 25-APR-13:20 37.15 18.65
May 0.166551E+11 23759.38 28-MAY-15:51 42.30 19.48 0.665006E+09 846.07 04-MAY-13:20 42.30 19.48
June 0.159184E+11 23354.92 11-JUN-16:22 43.25 23.12 0.662616E+09 845.95 12-JUN-13:39 43.70 22.38
July 0.149361E+11 24004.33 02-JUL-13:12 38.63 26.37 0.616586E+09 845.62 10-JUL-13:09 39.20 26.78
August 0.145606E+11 21165.32 06-AUG-15:12 36.30 26.24 0.691491E+09 845.62 28-AUG-09:09 30.88 27.50
September 0.134624E+11 24663.08 17-SEP-15:22 34.15 26.07 0.613672E+09 845.83 26-SEP-13:00 35.70 22.91
October 0.147642E+11 26297.07 01-OCT-15:21 35.75 20.04 0.636535E+09 851.95 02-OCT-13:50 36.37 21.07
November 0.118049E+11 25516.90 12-NOV-13:42 28.12 16.00 0.622038E+09 846.09 17-NOV-14:00 28.00 17.86
December 0.709011E+10 13620.39 01-DEC-13:50 23.35 13.02 0.580381E+09 845.64 04-DEC-14:00 23.20 14.27
                     
Annual Sum or Average 0.149396E+12         0.751423E+10        
Minimum of Months 0.625814E+10 12079.49   23.35 13.02 0.547508E+09 845.62   23.00 13.41
Maximum of Months 0.166551E+11 26297.07   43.25 26.37 0.691491E+09 851.95   43.70 27.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.308031E+10 4618.69 31-JAN-16:10 20.95 11.21 0.338653E+09 544.61 12-JAN-14:00 20.95 11.21
February 0.399393E+10 7456.53 21-FEB-16:00 26.10 15.66 0.329410E+09 544.95 24-FEB-14:20 26.07 17.12
March 0.744793E+10 15940.38 12-MAR-16:12 31.07 19.87 0.429216E+09 544.96 30-MAR-13:50 32.05 19.26
April 0.114254E+11 21431.11 30-APR-16:01 37.68 18.13 0.394606E+09 544.95 04-APR-09:09 37.68 18.13
May 0.138441E+11 21894.48 28-MAY-16:31 41.90 19.53 0.428597E+09 544.95 05-MAY-09:00 41.90 19.53
June 0.134583E+11 21419.54 11-JUN-16:22 43.25 23.12 0.427127E+09 544.95 12-JUN-13:09 43.40 22.40
July 0.116779E+11 21663.92 02-JUL-16:31 40.33 26.50 0.397246E+09 544.94 10-JUL-09:09 32.98 26.50
August 0.110084E+11 20156.40 06-AUG-16:32 36.10 26.38 0.445414E+09 544.94 28-AUG-09:09 30.88 27.50
September 0.921544E+10 21246.26 17-SEP-16:02 34.13 26.16 0.394350E+09 544.94 08-SEP-13:39 34.13 26.16
October 0.802642E+10 21833.44 01-OCT-15:21 35.75 20.04 0.403626E+09 544.95 16-OCT-09:30 27.20 17.62
November 0.545336E+10 8263.12 08-NOV-15:30 29.55 18.29 0.379179E+09 544.95 06-NOV-14:50 29.55 18.29
December 0.347157E+10 5237.79 28-DEC-15:40 24.03 15.27 0.336885E+09 544.94 28-DEC-14:00 24.03 15.27
                     
Annual Sum or Average 0.102103E+12         0.470431E+10        
Minimum of Months 0.308031E+10 4618.69   20.95 11.21 0.329410E+09 544.61   20.95 11.21
Maximum of Months 0.138441E+11 21894.48   43.25 26.50 0.445414E+09 544.96   43.40 27.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.471145E+10 8730.68 02-JAN-06:13 6.50 6.28 0.00 0.00 01-JAN-00:10 6.50 6.28
February 0.580980E+10 11725.83 21-FEB-06:13 11.70 10.89 0.00 0.00 01-FEB-00:10 11.70 10.89
March 0.957692E+10 11356.57 06-MAR-06:13 15.77 13.93 0.00 0.00 01-MAR-00:10 15.77 13.93
April 0.127158E+11 17284.87 17-APR-05:15 24.33 18.88 0.00 0.00 01-APR-00:10 24.33 18.88
May 0.136869E+11 17187.45 01-MAY-05:15 32.50 19.11 0.00 0.00 01-MAY-00:10 32.50 19.11
June 0.136879E+11 17622.67 12-JUN-05:15 34.23 19.16 0.00 0.00 01-JUN-00:10 34.23 19.16
July 0.133998E+11 19320.30 03-JUL-05:13 29.33 24.63 0.00 0.00 01-JUL-00:10 29.33 24.63
August 0.145531E+11 18127.66 07-AUG-05:13 29.57 24.74 0.00 0.00 01-AUG-00:10 29.57 24.74
September 0.107566E+11 15021.85 05-SEP-05:15 26.20 25.15 0.00 0.00 01-SEP-00:10 26.20 25.15
October 0.106116E+11 14093.22 10-OCT-05:15 19.90 18.09 0.00 0.00 01-OCT-00:10 19.90 18.09
November 0.854179E+10 12959.81 13-NOV-06:13 15.27 12.05 0.00 0.00 01-NOV-00:10 15.27 12.05
December 0.635253E+10 10585.62 26-DEC-06:13 10.23 8.49 0.00 0.00 01-DEC-00:10 10.23 8.49
                     
Annual Sum or Average 0.124404E+12         0.00        
Minimum of Months 0.471145E+10 8730.68   6.50 6.28 0.00 0.00   6.50 6.28
Maximum of Months 0.145531E+11 19320.30   34.23 25.15 0.00 0.00   34.23 25.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.285880E+10 5083.61 21-JAN-06:08 5.50 5.15 0.00 0.00 01-JAN-00:10 5.50 5.15
February 0.393191E+10 6836.17 23-FEB-06:13 15.10 13.65 0.00 0.00 01-FEB-00:10 15.10 13.65
March 0.727288E+10 7962.68 15-MAR-05:03 18.17 15.10 0.00 0.00 01-MAR-00:10 18.17 15.10
April 0.987035E+10 9651.62 21-APR-05:03 26.98 17.68 0.00 0.00 01-APR-00:10 26.98 17.68
May 0.119263E+11 11915.05 31-MAY-05:03 31.72 21.12 0.00 0.00 01-MAY-00:10 31.72 21.12
June 0.115875E+11 11252.69 09-JUN-05:03 31.20 23.77 0.00 0.00 01-JUN-00:10 31.20 23.77
July 0.107167E+11 14378.42 05-JUL-05:02 32.57 24.73 0.00 0.00 01-JUL-00:10 32.57 24.73
August 0.106468E+11 11853.16 08-AUG-05:02 30.10 25.30 0.00 0.00 01-AUG-00:10 30.10 25.30
September 0.918615E+10 12616.52 05-SEP-05:15 26.20 25.15 0.00 0.00 01-SEP-00:10 26.20 25.15
October 0.852256E+10 9259.85 20-OCT-05:02 20.15 17.63 0.00 0.00 01-OCT-00:10 20.15 17.63
November 0.597566E+10 8965.11 13-NOV-06:13 15.27 12.05 0.00 0.00 01-NOV-00:10 15.27 12.05
December 0.366519E+10 5446.69 02-DEC-06:10 8.72 8.46 0.00 0.00 01-DEC-00:10 8.72 8.46
                     
Annual Sum or Average 0.961608E+11         0.00        
Minimum of Months 0.285880E+10 5083.61   5.50 5.15 0.00 0.00   5.50 5.15
Maximum of Months 0.119263E+11 14378.42   32.57 25.30 0.00 0.00   32.57 25.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.230813E+10 7274.40 12-JAN-14:50 23.55 14.16 0.00 0.00 01-JAN-00:10 23.55 14.16
February 0.457124E+10 13930.36 22-FEB-14:40 27.07 16.24 0.00 0.00 01-FEB-00:10 27.07 16.24
March 0.111903E+11 21896.13 28-MAR-15:20 35.57 18.58 0.00 0.00 01-MAR-00:10 35.57 18.58
April 0.191848E+11 26854.17 26-APR-14:50 39.22 22.03 0.00 0.00 01-APR-00:10 39.22 22.03
May 0.248545E+11 30383.45 01-MAY-14:20 43.93 22.01 0.00 0.00 01-MAY-00:10 43.93 22.01
June 0.247666E+11 31890.04 12-JUN-13:50 43.80 22.37 0.00 0.00 01-JUN-00:10 43.80 22.37
July 0.204144E+11 28449.61 07-JUL-14:00 40.30 24.54 0.00 0.00 01-JUL-00:10 40.30 24.54
August 0.188552E+11 25400.53 07-AUG-14:00 37.20 26.26 0.00 0.00 01-AUG-00:10 37.20 26.26
September 0.149114E+11 22285.97 26-SEP-14:40 35.97 22.76 0.00 0.00 01-SEP-00:10 35.97 22.76
October 0.128028E+11 21182.08 02-OCT-14:00 36.40 21.05 0.00 0.00 01-OCT-00:10 36.40 21.05
November 0.714902E+10 14879.60 09-NOV-14:10 29.37 17.83 0.00 0.00 01-NOV-00:10 29.37 17.83
December 0.276974E+10 8626.81 01-DEC-14:30 23.45 13.21 0.00 0.00 01-DEC-00:10 23.45 13.21
                     
Annual Sum or Average 0.163778E+12         0.00        
Minimum of Months 0.230813E+10 7274.40   23.45 13.21 0.00 0.00   23.45 13.21
Maximum of Months 0.248545E+11 31890.04   43.93 26.26 0.00 0.00   43.93 26.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.407200E+10 1950.12 30-JAN-17:00 19.20 10.80 95236931.08 126.85 17-JAN-14:00 19.20 10.80
February 0.852571E+10 3916.24 21-FEB-17:00 25.40 15.70 86404198.12 126.85 09-FEB-14:00 25.40 15.70
March 0.147028E+11 7207.09 31-MAR-23:55 23.70 16.75 0.103241E+09 126.84 23-MAR-09:09 23.70 16.75
April 0.191796E+11 7756.45 16-APR-22:35 27.57 19.98 95186930.25 145.20 27-APR-13:00 39.60 19.54
May 0.481678E+10 3509.96 31-MAY-24:00 28.10 22.60 99241500.94 126.86 30-MAY-09:20 28.10 22.60
June 0.953363E+10 5382.56 30-JUN-23:57 33.10 24.67 98979051.96 126.88 27-JUN-09:09 33.10 24.67
July 0.148770E+11 7269.26 31-JUL-23:57 29.40 26.34 91893405.44 126.85 18-JUL-09:00 29.40 26.34
August 0.196850E+11 7616.83 16-AUG-09:40 25.23 24.59 0.112180E+09 151.26 07-AUG-13:00 25.23 24.59
September 0.460734E+10 3506.22 30-SEP-23:47 26.60 21.97 91606879.69 126.86 26-SEP-13:00 26.60 21.97
October 0.976349E+10 5408.90 31-OCT-24:00 17.80 15.13 95244614.69 126.87 12-OCT-09:39 17.80 15.13
November 0.142445E+11 5828.83 13-NOV-16:30 27.00 16.63 94304826.12 126.83 10-NOV-10:09 27.00 16.63
December 0.195760E+11 7687.46 28-DEC-17:00 22.80 14.91 91882189.92 126.83 11-DEC-10:09 22.80 14.91
                     
Annual Sum or Average 0.143584E+12         0.115540E+10        
Minimum of Months 0.407200E+10 1950.12   17.80 10.80 86404198.12 126.83   17.80 10.80
Maximum of Months 0.196850E+11 7756.45   33.10 26.34 0.112180E+09 151.26   39.60 26.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.292708E+10 1787.32 12-JAN-17:00 22.30 14.53 95235296.59 126.84 13-JAN-14:00 21.50 15.25
February 0.754040E+10 3680.77 21-FEB-17:00 25.40 15.70 86403614.12 126.84 09-FEB-14:00 25.40 15.70
March 0.138642E+11 6965.49 31-MAR-23:55 23.70 16.75 0.103242E+09 126.84 29-MAR-09:09 23.70 16.75
April 0.181825E+11 7338.16 12-APR-16:00 28.10 17.52 95003097.88 144.07 26-APR-13:00 38.80 22.02
May 0.448503E+10 3382.31 31-MAY-24:00 28.10 22.60 99238933.94 126.85 30-MAY-13:09 28.10 22.60
June 0.903350E+10 5209.02 30-JUN-23:42 33.12 24.58 98980134.82 126.87 28-JUN-13:20 33.12 24.58
July 0.141311E+11 6987.17 31-JUL-24:00 29.40 26.34 91895044.64 126.85 18-JUL-13:00 29.40 26.34
August 0.185810E+11 7182.48 16-AUG-10:50 25.82 25.06 0.110916E+09 147.54 07-AUG-13:00 25.82 25.06
September 0.425242E+10 3402.17 30-SEP-23:47 26.60 21.97 91605872.17 126.85 27-SEP-13:00 26.60 21.97
October 0.914898E+10 5089.52 31-OCT-24:00 17.80 15.13 95244476.58 126.86 13-OCT-09:20 17.80 15.13
November 0.131751E+11 5502.47 08-NOV-16:40 28.33 18.82 94305004.47 126.83 10-NOV-10:09 23.57 17.22
December 0.178152E+11 7247.83 01-DEC-17:00 21.20 14.26 91882401.60 126.83 11-DEC-10:00 10.00 9.32
                     
Annual Sum or Average 0.133136E+12         0.115395E+10        
Minimum of Months 0.292708E+10 1787.32   17.80 14.26 86403614.12 126.83   10.00 9.32
Maximum of Months 0.185810E+11 7338.16   33.12 26.34 0.110916E+09 147.54   38.80 26.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.157049E+10 1790.41 12-JAN-17:00 22.30 14.53 95061612.91 126.84 13-JAN-14:00 21.50 15.25
February 0.684371E+10 3710.93 22-FEB-17:00 25.70 15.75 86404283.59 126.84 15-FEB-14:50 25.70 15.75
March 0.136683E+11 6911.88 31-MAR-23:55 23.70 16.75 0.103242E+09 126.84 29-MAR-09:09 23.70 16.75
April 0.183139E+11 7487.94 16-APR-20:52 28.40 20.06 93957075.30 142.43 26-APR-13:00 38.80 22.02
May 0.469774E+10 3354.11 31-MAY-24:00 28.10 22.60 99239481.17 126.85 10-MAY-13:00 28.10 22.60
June 0.923095E+10 5249.71 30-JUN-23:57 33.10 24.67 98980799.82 126.88 26-JUN-09:00 33.10 24.67
July 0.143274E+11 7042.96 31-JUL-23:57 29.40 26.34 91896142.19 126.86 18-JUL-09:00 29.40 26.34
August 0.188494E+11 7296.57 20-AUG-16:22 27.25 25.83 0.108433E+09 146.05 07-AUG-13:00 27.25 25.83
September 0.430917E+10 3382.09 30-SEP-23:34 26.60 22.02 91605938.98 126.86 27-SEP-13:00 26.60 22.02
October 0.905063E+10 4940.77 31-OCT-24:00 17.80 15.13 95245478.22 126.86 12-OCT-13:00 17.80 15.13
November 0.126557E+11 5557.69 08-NOV-16:30 28.55 18.76 94305645.39 126.83 10-NOV-10:09 23.57 17.22
December 0.166347E+11 7241.78 28-DEC-17:00 22.80 14.91 91882977.10 126.83 11-DEC-10:50 22.80 14.91
                     
Annual Sum or Average 0.130152E+12         0.115025E+10        
Minimum of Months 0.157049E+10 1790.41   17.80 14.53 86404283.59 126.83   17.80 14.91
Maximum of Months 0.188494E+11 7487.94   33.10 26.34 0.108433E+09 146.05   38.80 26.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.242031E+12 93285.70 26-JAN-17:00 18.60 12.70 0.206241E+10 2748.30 26-JAN-10:09 18.60 12.70
February 0.438528E+12 184671.54 21-FEB-17:00 25.40 15.70 0.187106E+10 2749.10 28-FEB-10:09 18.42 14.43
March 0.730503E+12 359056.19 31-MAR-23:55 23.70 16.75 0.223525E+10 2749.75 20-MAR-09:00 23.70 16.75
April 0.935252E+12 368482.41 30-APR-04:25 23.15 16.67 0.240535E+10 4044.43 28-APR-13:00 23.15 16.67
May 0.243004E+12 176395.08 31-MAY-24:00 28.10 22.60 0.214884E+10 2747.23 24-MAY-09:00 28.10 22.60
June 0.472699E+12 268595.66 30-JUN-24:00 33.10 24.67 0.214278E+10 2746.95 27-JUN-09:00 33.10 24.67
July 0.735783E+12 356264.77 31-JUL-23:23 29.40 26.34 0.198927E+10 2746.02 18-JUL-09:00 29.40 26.34
August 0.968189E+12 370180.76 15-AUG-23:42 23.53 22.96 0.293157E+10 4080.49 07-AUG-13:00 23.53 22.96
September 0.240169E+12 177656.23 30-SEP-23:53 26.60 21.92 0.198369E+10 2747.28 14-SEP-13:09 26.60 21.92
October 0.491305E+12 269769.60 31-OCT-24:00 17.80 15.13 0.206191E+10 2746.43 13-OCT-09:09 17.80 15.13
November 0.712049E+12 277921.28 13-NOV-17:00 26.40 16.65 0.204192E+10 2749.64 28-NOV-10:30 18.60 13.96
December 0.980030E+12 369279.31 04-DEC-17:00 20.10 14.52 0.199058E+10 2819.26 28-DEC-14:00 24.50 15.39
                     
Annual Sum or Average 0.718954E+13         0.258646E+11        
Minimum of Months 0.240169E+12 93285.70   17.80 12.70 0.187106E+10 2746.02   17.80 12.70
Maximum of Months 0.980030E+12 370180.76   33.10 26.34 0.293157E+10 4080.49   33.10 26.34



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5304976.04 2885.00 14-JAN-17:25 20.25
February 72178275.55 11359.91 20-FEB-13:54 26.40
March 0.144591E+09 15727.80 11-MAR-17:03 29.70
April 0.495071E+09 30323.79 15-APR-16:01 39.58
May 0.699186E+09 33641.50 27-MAY-16:01 42.00
June 0.610514E+09 35445.22 10-JUN-16:01 43.12
July 0.807686E+09 29797.30 02-JUL-17:13 40.07
August 0.515003E+09 24643.02 05-AUG-16:02 35.70
September 0.700923E+09 23310.25 17-SEP-20:10 37.37
October 0.536185E+09 23599.32 01-OCT-13:13 35.43
November 0.163791E+09 14744.62 04-NOV-16:03 29.18
December 19048372.55 6871.43 03-DEC-12:34 23.57
         
Annual Sum or Average 0.476948E+10      
Minimum of Months 5304976.04 2885.00   20.25
Maximum of Months 0.807686E+09 35445.22   43.12



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.213754E+09 61816.21 02-JAN-05:01 6.48
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.213754E+09      
Minimum of Months 0.00 0.00   6.48
Maximum of Months 0.213754E+09 61816.21   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 388878.10 866.17 04-JAN-06:06 5.65
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 525951.65 3161.17 21-DEC-06:02 5.27
         
Annual Sum or Average 914829.76      
Minimum of Months 0.00 0.00   5.27
Maximum of Months 525951.65 3161.17   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 275671.88 1295.46 02-JAN-06:03 6.45
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 211385.47 1685.74 21-DEC-06:02 5.27
         
Annual Sum or Average 487057.35      
Minimum of Months 0.00 0.00   5.27
Maximum of Months 275671.88 1685.74   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 13258.43 63.64 02-JAN-06:06 6.45
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 13258.43      
Minimum of Months 0.00 0.00   6.45
Maximum of Months 13258.43 63.64   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.524939E+09 16889.17 02-JAN-04:02 6.67
February 62815946.89 14548.63 11-FEB-06:02 9.30
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 150598.69 1003.99 27-NOV-06:05 9.55
December 0.172279E+09 14760.32 21-DEC-06:02 5.27
         
Annual Sum or Average 0.760184E+09      
Minimum of Months 0.00 0.00   5.27
Maximum of Months 0.524939E+09 16889.17   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.213649E+09 11558.26 02-JAN-04:02 6.67
February 17172610.77 10063.68 11-FEB-06:02 9.30
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 52280058.49 9962.70 21-DEC-06:02 5.27
         
Annual Sum or Average 0.283102E+09      
Minimum of Months 0.00 0.00   5.27
Maximum of Months 0.213649E+09 11558.26   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.135930E+09 16402.62 02-JAN-05:01 6.48
February 14099320.05 14539.04 11-FEB-06:02 9.30
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 19042766.27 13168.77 23-DEC-06:03 5.43
         
Annual Sum or Average 0.169073E+09      
Minimum of Months 0.00 0.00   5.43
Maximum of Months 0.135930E+09 16402.62   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.132198E+09 11135.38 02-JAN-05:01 6.48
February 8502235.34 9332.46 11-FEB-06:02 9.30
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 24288928.48 8770.27 23-DEC-06:03 5.43
         
Annual Sum or Average 0.164989E+09      
Minimum of Months 0.00 0.00   5.43
Maximum of Months 0.132198E+09 11135.38   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 62735782.19 9502.06 17-JAN-04:02 11.75
February 75948447.63 9578.85 13-FEB-04:02 11.62
March 78625899.78 8809.87 22-MAR-03:02 17.73
April 40611402.68 6485.51 16-APR-15:01 39.63
May 33609943.53 6638.71 23-MAY-03:02 28.47
June 38227238.37 6146.39 11-JUN-16:22 43.25
July 46798007.53 5930.67 02-JUL-17:01 40.18
August 43577048.35 6198.35 06-AUG-15:01 36.30
September 73927733.22 8970.93 11-SEP-03:02 26.07
October 82098626.36 8047.52 13-OCT-03:02 21.62
November 90538828.57 8955.83 29-NOV-04:02 14.55
December 0.105750E+09 10769.36 29-DEC-04:02 16.07
         
Annual Sum or Average 0.772449E+09      
Minimum of Months 33609943.53 5930.67   11.62
Maximum of Months 0.105750E+09 10769.36   43.25



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 33096618.26 6994.09 18-JAN-06:02 13.58
February 46997298.52 6612.17 27-FEB-04:02 11.72
March 40788910.58 6665.58 29-MAR-03:02 21.75
April 35733557.33 7060.86 13-APR-03:02 24.18
May 36497816.99 7447.12 24-MAY-03:02 26.12
June 32326965.84 7701.80 21-JUN-03:02 28.25
July 43873878.77 7760.43 28-JUL-03:02 27.00
August 40315339.05 7758.66 17-AUG-03:02 27.35
September 52031879.58 9740.65 11-SEP-03:02 26.07
October 44629353.85 6335.78 11-OCT-03:02 24.45
November 43218713.45 5990.06 28-NOV-05:03 15.20
December 45118047.90 6799.23 22-DEC-06:03 12.42
         
Annual Sum or Average 0.494628E+09      
Minimum of Months 32326965.84 5990.06   11.72
Maximum of Months 52031879.58 9740.65   28.25



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.207829E+10 19204.98 02-JAN-06:13 6.50
February 0.848482E+09 19839.23 27-FEB-06:03 10.82
March 0.281191E+09 18415.24 02-MAR-06:02 14.48
April 83496241.93 14581.13 10-APR-03:02 18.93
May 28171619.45 7264.75 16-MAY-03:02 27.05
June 13273741.18 9267.15 28-JUN-03:02 26.40
July 14467513.80 7476.25 19-JUL-03:02 23.42
August 22204597.61 9429.48 21-AUG-03:02 25.87
September 53615935.55 11495.34 11-SEP-03:02 26.07
October 0.171835E+09 17420.98 31-OCT-05:02 15.53
November 0.512813E+09 18295.82 13-NOV-06:02 15.13
December 0.145542E+10 15278.79 29-DEC-06:03 16.53
         
Annual Sum or Average 0.556326E+10      
Minimum of Months 13273741.18 7264.75   6.50
Maximum of Months 0.207829E+10 19839.23   27.05



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 61856676.18 334.98 01-JAN-14:00 16.20
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 61856676.18      
Minimum of Months 0.00 0.00   9.73
Maximum of Months 61856676.18 334.98   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:03 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.200626E+11 20994.62 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.181982E+11 20994.62 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.216246E+11 20994.62 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.193152E+11 20994.62 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.208436E+11 20994.62 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.207428E+11 20994.62 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.194159E+11 20994.62 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.216246E+11 20994.62 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.193152E+11 20994.62 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.200626E+11 20994.62 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.198274E+11 20994.62 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.194159E+11 20994.62 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.240449E+12     0.424397E+12    
Minimum of Months 0.181982E+11 20994.62   0.325565E+11 13457.54  
Maximum of Months 0.216246E+11 20994.62   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.180176E+11 18854.65 02-JAN-08:09 0.270551E+11 18128.59 02-JAN-08:09
February 0.163433E+11 18854.65 01-FEB-08:09 0.244881E+11 18128.59 01-FEB-08:09
March 0.194204E+11 18854.65 01-MAR-08:09 0.280558E+11 18128.59 01-MAR-08:09
April 0.173464E+11 18854.65 03-APR-07:10 0.261305E+11 18128.59 03-APR-07:10
May 0.187190E+11 18854.65 01-MAY-07:10 0.275555E+11 18128.59 01-MAY-07:10
June 0.186285E+11 18854.65 01-JUN-07:10 0.270261E+11 18128.59 01-JUN-07:10
July 0.174369E+11 18854.65 03-JUL-07:10 0.266527E+11 18128.59 03-JUL-07:10
August 0.194204E+11 18854.65 01-AUG-07:10 0.280558E+11 18128.59 01-AUG-07:10
September 0.173464E+11 18854.65 01-SEP-07:10 0.261160E+11 18128.59 01-SEP-07:10
October 0.180176E+11 18854.65 02-OCT-07:10 0.270624E+11 18128.59 02-OCT-07:10
November 0.178064E+11 18854.65 01-NOV-07:10 0.264424E+11 18128.59 01-NOV-07:10
December 0.174369E+11 18854.65 01-DEC-08:09 0.266454E+11 18128.59 01-DEC-08:09
             
Annual Sum or Average 0.215940E+12     0.321286E+12    
Minimum of Months 0.163433E+11 18854.65   0.244881E+11 18128.59  
Maximum of Months 0.194204E+11 18854.65   0.280558E+11 18128.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.180176E+11 18854.65 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.163433E+11 18854.65 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.194204E+11 18854.65 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.173464E+11 18854.65 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.187190E+11 18854.65 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.186285E+11 18854.65 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.174369E+11 18854.65 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.194204E+11 18854.65 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.173464E+11 18854.65 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.180176E+11 18854.65 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.178064E+11 18854.65 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.174369E+11 18854.65 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.215940E+12     0.321285E+12    
Minimum of Months 0.163433E+11 18854.65   0.244880E+11 18128.52  
Maximum of Months 0.194204E+11 18854.65   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.180176E+11 18854.65 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.163433E+11 18854.65 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.194204E+11 18854.65 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.173464E+11 18854.65 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.187190E+11 18854.65 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.186285E+11 18854.65 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.174369E+11 18854.65 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.194204E+11 18854.65 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.173464E+11 18854.65 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.180176E+11 18854.65 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.178064E+11 18854.65 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.174369E+11 18854.65 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.215940E+12     0.321285E+12    
Minimum of Months 0.163433E+11 18854.65   0.244880E+11 18128.52  
Maximum of Months 0.194204E+11 18854.65   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.161367E+10 2053.69 18-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.143559E+10 2020.68 10-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.165968E+10 2037.36 14-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.146632E+10 1454.29 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.156139E+10 1690.49 24-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.155299E+10 1678.00 23-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.147268E+10 1974.74 26-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.164706E+10 2023.33 16-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.148954E+10 2071.97 08-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.157160E+10 2158.51 11-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.158822E+10 2124.33 27-NOV-16:00 0.332024E+10 2276.32 01-NOV-07:10
December 0.157724E+10 2135.26 29-DEC-16:00 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.186360E+11     0.403423E+11    
Minimum of Months 0.143559E+10 1454.29   0.307485E+10 2276.32  
Maximum of Months 0.165968E+10 2158.51   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.103404E+10 1316.68 17-JAN-16:00 0.218927E+10 1466.95 02-JAN-08:09
February 0.923933E+09 1309.00 09-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.106837E+10 1230.05 14-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.946046E+09 937.20 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.100982E+10 937.20 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.100417E+10 937.20 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.950100E+09 1241.75 26-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.106129E+10 1276.47 16-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.959766E+09 1310.06 07-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.100873E+10 1375.35 11-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.102196E+10 1392.81 27-NOV-16:00 0.213969E+10 1466.95 01-NOV-07:10
December 0.101139E+10 1385.08 29-DEC-16:00 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.119996E+11     0.259981E+11    
Minimum of Months 0.923933E+09 937.20   0.198155E+10 1466.95  
Maximum of Months 0.106837E+10 1392.81   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.157987E+10 1993.21 18-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.141978E+10 1970.72 10-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.165425E+10 2019.13 14-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.146821E+10 1454.32 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.156895E+10 1742.03 24-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.155965E+10 1754.19 23-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.147808E+10 1997.05 26-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.164987E+10 2033.20 16-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.148816E+10 2069.09 08-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.155981E+10 2150.01 11-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.156167E+10 1997.86 27-NOV-16:00 0.332029E+10 2276.35 01-NOV-07:10
December 0.153979E+10 2079.48 29-DEC-16:00 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.185281E+11     0.403429E+11    
Minimum of Months 0.141978E+10 1454.32   0.307490E+10 2276.35  
Maximum of Months 0.165425E+10 2150.01   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.102971E+10 1332.60 18-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.919572E+09 1315.32 10-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.107117E+10 1346.92 14-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.946746E+09 1161.65 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.101081E+10 1172.53 24-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.100409E+10 1174.34 23-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.952733E+09 1301.32 26-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.106572E+10 1325.08 16-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.962276E+09 1349.18 08-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.101505E+10 1397.15 11-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.101120E+10 1298.06 03-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.100043E+10 1322.25 29-DEC-16:00 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.119895E+11     0.259979E+11    
Minimum of Months 0.919572E+09 1161.65   0.198154E+10 1466.94  
Maximum of Months 0.107117E+10 1397.15   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.161666E+10 2062.64 18-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.143698E+10 2030.61 10-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.166082E+10 2047.04 14-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.146672E+10 1454.29 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.156301E+10 1710.01 24-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.155414E+10 1697.89 23-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.147360E+10 1986.21 26-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.164848E+10 2033.40 16-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.149098E+10 2080.61 08-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.157336E+10 2164.62 11-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.159039E+10 2131.35 27-NOV-16:00 0.332024E+10 2276.32 01-NOV-07:10
December 0.158013E+10 2141.99 29-DEC-16:00 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.186553E+11     0.403423E+11    
Minimum of Months 0.143698E+10 1454.29   0.307485E+10 2276.32  
Maximum of Months 0.166082E+10 2164.62   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.103461E+10 1318.37 17-JAN-16:00 0.218927E+10 1466.95 02-JAN-08:09
February 0.924273E+09 1310.64 09-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.106879E+10 1233.40 14-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.946252E+09 937.20 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.101004E+10 937.20 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.100432E+10 937.20 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.950449E+09 1246.24 26-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.106159E+10 1279.69 16-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.960005E+09 1312.79 08-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.100892E+10 1376.92 11-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.102246E+10 1394.00 27-NOV-16:00 0.213969E+10 1466.95 01-NOV-07:10
December 0.101200E+10 1386.20 29-DEC-16:00 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.120037E+11     0.259981E+11    
Minimum of Months 0.924273E+09 937.20   0.198155E+10 1466.95  
Maximum of Months 0.106879E+10 1394.00   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.158408E+10 2006.26 18-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.142041E+10 1982.43 10-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.165504E+10 2029.53 14-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.146869E+10 1454.32 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.156974E+10 1759.65 24-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.156068E+10 1771.33 23-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.147944E+10 2007.69 26-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.165097E+10 2042.89 16-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.148901E+10 2077.84 08-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.155906E+10 2156.47 11-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.156263E+10 2009.34 27-NOV-16:00 0.332029E+10 2276.35 01-NOV-07:10
December 0.154181E+10 2088.27 29-DEC-16:00 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.185416E+11     0.403429E+11    
Minimum of Months 0.142041E+10 1454.32   0.307490E+10 2276.35  
Maximum of Months 0.165504E+10 2156.47   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.103033E+10 1334.11 18-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.920065E+09 1316.91 10-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.107162E+10 1348.23 14-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.946999E+09 1165.32 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.101099E+10 1175.10 24-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.100423E+10 1176.91 23-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.953207E+09 1302.96 26-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.106602E+10 1326.56 16-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.962585E+09 1350.48 08-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.101548E+10 1398.10 11-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.101159E+10 1300.59 03-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.100094E+10 1324.39 29-DEC-16:00 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.119941E+11     0.259979E+11    
Minimum of Months 0.920065E+09 1165.32   0.198154E+10 1466.94  
Maximum of Months 0.107162E+10 1398.10   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.161667E+10 2062.35 18-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.143697E+10 2030.29 10-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.166082E+10 2046.81 14-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.146673E+10 1454.29 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.156300E+10 1709.49 24-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.155410E+10 1697.36 23-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.147358E+10 1985.85 26-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.164837E+10 2033.08 16-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.149096E+10 2080.33 08-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.157335E+10 2164.41 11-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.159039E+10 2131.24 27-NOV-16:00 0.332024E+10 2276.32 01-NOV-07:10
December 0.158015E+10 2141.79 29-DEC-16:00 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.186551E+11     0.403423E+11    
Minimum of Months 0.143697E+10 1454.29   0.307485E+10 2276.32  
Maximum of Months 0.166082E+10 2164.41   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.103462E+10 1318.22 17-JAN-16:00 0.218927E+10 1466.95 02-JAN-08:09
February 0.924276E+09 1310.43 09-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.106879E+10 1233.32 14-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.946256E+09 937.20 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.101004E+10 937.20 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.100432E+10 937.20 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.950438E+09 1246.05 26-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.106158E+10 1279.53 16-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.960000E+09 1312.64 08-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.100892E+10 1376.81 11-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.102247E+10 1393.93 27-NOV-16:00 0.213969E+10 1466.95 01-NOV-07:10
December 0.101202E+10 1386.08 29-DEC-16:00 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.120037E+11     0.259981E+11    
Minimum of Months 0.924276E+09 937.20   0.198155E+10 1466.95  
Maximum of Months 0.106879E+10 1393.93   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.158409E+10 2006.00 18-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.142041E+10 1982.11 10-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.165505E+10 2029.30 14-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.146869E+10 1454.32 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.156973E+10 1759.12 24-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.156066E+10 1770.81 23-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.147941E+10 2007.33 26-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.165095E+10 2042.57 16-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.148899E+10 2077.55 08-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.155905E+10 2156.27 11-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.156264E+10 2009.29 27-NOV-16:00 0.332029E+10 2276.35 01-NOV-07:10
December 0.154185E+10 2088.10 29-DEC-16:00 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.185415E+11     0.403429E+11    
Minimum of Months 0.142041E+10 1454.32   0.307490E+10 2276.35  
Maximum of Months 0.165505E+10 2156.27   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.103035E+10 1333.93 18-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.920071E+09 1316.71 10-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.107166E+10 1348.07 14-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.947004E+09 1165.33 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.101099E+10 1174.77 24-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.100422E+10 1176.59 23-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.953190E+09 1302.74 26-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.106600E+10 1326.36 16-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.962577E+09 1350.30 08-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.101547E+10 1397.97 11-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.101166E+10 1300.54 03-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.100095E+10 1324.31 29-DEC-16:00 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.119941E+11     0.259979E+11    
Minimum of Months 0.920071E+09 1165.33   0.198154E+10 1466.94  
Maximum of Months 0.107166E+10 1397.97   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.497722E+09 520.85 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.451470E+09 520.85 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.536472E+09 520.85 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.479179E+09 520.85 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.517097E+09 520.85 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.514597E+09 520.85 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.481680E+09 520.85 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.536472E+09 520.85 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.479179E+09 520.85 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.497722E+09 520.85 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.491888E+09 520.85 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.481680E+09 520.85 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.596516E+10     0.153881E+12    
Minimum of Months 0.451470E+09 520.85   0.505780E+10 1948.61  
Maximum of Months 0.536472E+09 520.85   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.497722E+09 520.85 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.451470E+09 520.85 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.536472E+09 520.85 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.479179E+09 520.85 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.517097E+09 520.85 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.514597E+09 520.85 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.481680E+09 520.85 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.536472E+09 520.85 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.479179E+09 520.85 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.497722E+09 520.85 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.491888E+09 520.85 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.481680E+09 520.85 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.596516E+10     0.153881E+12    
Minimum of Months 0.451470E+09 520.85   0.505780E+10 1948.61  
Maximum of Months 0.536472E+09 520.85   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.497722E+09 520.85 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.451470E+09 520.85 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.536472E+09 520.85 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.479179E+09 520.85 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.517097E+09 520.85 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.514597E+09 520.85 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.481680E+09 520.85 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.536472E+09 520.85 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.479179E+09 520.85 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.497722E+09 520.85 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.491888E+09 520.85 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.481680E+09 520.85 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.596516E+10     0.153881E+12    
Minimum of Months 0.451470E+09 520.85   0.505780E+10 1948.61  
Maximum of Months 0.536472E+09 520.85   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.565679E+10 5919.59 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.513113E+10 5919.59 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.609720E+10 5919.59 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.544605E+10 5919.59 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.587700E+10 5919.59 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.584858E+10 5919.59 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.547447E+10 5919.59 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.609720E+10 5919.59 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.544605E+10 5919.59 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.565679E+10 5919.59 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.559049E+10 5919.59 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.547447E+10 5919.59 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.677962E+11     0.749486E+13    
Minimum of Months 0.513113E+10 5919.59   0.246344E+12 94908.13  
Maximum of Months 0.609720E+10 5919.59   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.200626E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.181982E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.216246E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.193152E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.208436E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.207428E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.194159E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.216246E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.193152E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.200626E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.198274E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.194159E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.240449E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.181982E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.216246E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.180176E+11 0.270551E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.163433E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.194204E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.173464E+11 0.261305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.187190E+11 0.275555E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.186285E+11 0.270261E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.174369E+11 0.266527E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.194204E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.173464E+11 0.261160E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.180176E+11 0.270624E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.178064E+11 0.264424E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.174369E+11 0.266454E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.215940E+12 0.321286E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.163433E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.194204E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.180176E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.173464E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.187190E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.186285E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.174369E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.173464E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.180176E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.178064E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.174369E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.215940E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.180176E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.173464E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.187190E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.186285E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.174369E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.173464E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.180176E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.178064E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.174369E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.215940E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.161367E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 91304863.12
February 0.136985E+10 0.143559E+10 0.307485E+10 0.00 0.00 0.00 0.00 1566589.00 95171720.83
March 0.163685E+10 0.165968E+10 0.352283E+10 0.00 0.00 0.00 0.00 19133966.66 55886759.81
April 0.145243E+10 0.146632E+10 0.328108E+10 0.00 0.00 0.00 0.00 74536167.75 3040210.32
May 0.157338E+10 0.156139E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.158472E+09 1049217.18
June 0.156900E+10 0.155299E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.107614E+09 597771.53
July 0.145680E+10 0.147268E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.137585E+09 223536.32
August 0.163685E+10 0.164706E+10 0.352283E+10 0.00 0.00 0.00 0.00 79139384.06 249796.28
September 0.145243E+10 0.148954E+10 0.327926E+10 0.00 0.00 0.00 0.00 45186489.00 1288808.60
October 0.150991E+10 0.157160E+10 0.339809E+10 0.00 0.00 0.00 0.00 23926045.53 4489850.26
November 0.149516E+10 0.158822E+10 0.332024E+10 0.00 0.00 0.00 0.00 5199730.54 19840662.95
December 0.145680E+10 0.157724E+10 0.334573E+10 0.00 0.00 0.00 0.00 99038.81 82692100.26
                   
Annual Sum or Average 0.181194E+11 0.186360E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.652458E+09 0.355835E+09
Minimum of Months 0.136985E+10 0.143559E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 223536.32
Maximum of Months 0.163685E+10 0.165968E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.158472E+09 95171720.83



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.103404E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 61284264.03
February 0.882782E+09 0.923933E+09 0.198155E+10 0.00 0.00 0.00 0.00 913833.91 63552372.87
March 0.105485E+10 0.106837E+10 0.227025E+10 0.00 0.00 0.00 0.00 12394280.01 35840404.66
April 0.936002E+09 0.946046E+09 0.211446E+10 0.00 0.00 0.00 0.00 49682528.08 1657206.07
May 0.101394E+10 0.100982E+10 0.222976E+10 0.00 0.00 0.00 0.00 0.105203E+09 621262.09
June 0.101113E+10 0.100417E+10 0.218692E+10 0.00 0.00 0.00 0.00 73459023.26 297084.82
July 0.938820E+09 0.950100E+09 0.215670E+10 0.00 0.00 0.00 0.00 95802374.57 83032.77
August 0.105485E+10 0.106129E+10 0.227025E+10 0.00 0.00 0.00 0.00 56369294.33 62017.67
September 0.936002E+09 0.959766E+09 0.211328E+10 0.00 0.00 0.00 0.00 30850525.99 634952.56
October 0.973041E+09 0.100873E+10 0.218986E+10 0.00 0.00 0.00 0.00 15446076.28 2887726.32
November 0.963541E+09 0.102196E+10 0.213969E+10 0.00 0.00 0.00 0.00 3402157.89 13244572.56
December 0.938820E+09 0.101139E+10 0.215612E+10 0.00 0.00 0.00 0.00 67097.31 54026713.85
                   
Annual Sum or Average 0.116768E+11 0.119996E+11 0.259981E+11 0.00 0.00 0.00 0.00 0.443591E+09 0.234192E+09
Minimum of Months 0.882782E+09 0.923933E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 62017.67
Maximum of Months 0.105485E+10 0.106837E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.105203E+09 63552372.87



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.157987E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 96481646.89
February 0.136988E+10 0.141978E+10 0.307490E+10 0.00 0.00 0.00 0.00 871612.67 0.103999E+09
March 0.163688E+10 0.165425E+10 0.352288E+10 0.00 0.00 0.00 0.00 15994705.66 61376942.30
April 0.145246E+10 0.146821E+10 0.328113E+10 0.00 0.00 0.00 0.00 71008675.37 3401374.73
May 0.157341E+10 0.156895E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.157344E+09 1065684.72
June 0.156904E+10 0.155965E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.107693E+09 599989.17
July 0.145684E+10 0.147808E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.137539E+09 214376.71
August 0.163688E+10 0.164987E+10 0.352288E+10 0.00 0.00 0.00 0.00 78597771.04 269311.55
September 0.145246E+10 0.148816E+10 0.327931E+10 0.00 0.00 0.00 0.00 43557913.71 1242886.74
October 0.150994E+10 0.155981E+10 0.339814E+10 0.00 0.00 0.00 0.00 20859138.78 5074467.89
November 0.149520E+10 0.156167E+10 0.332029E+10 0.00 0.00 0.00 0.00 3778500.89 22765186.51
December 0.145684E+10 0.153979E+10 0.334578E+10 0.00 0.00 0.00 0.00 17145.13 90054340.11
                   
Annual Sum or Average 0.181198E+11 0.185281E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.637261E+09 0.386545E+09
Minimum of Months 0.136988E+10 0.141978E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 214376.71
Maximum of Months 0.163688E+10 0.165425E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.157344E+09 0.103999E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.102971E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 66398456.27
February 0.882782E+09 0.919572E+09 0.198154E+10 0.00 0.00 0.00 0.00 617677.06 73682212.14
March 0.105485E+10 0.107117E+10 0.227023E+10 0.00 0.00 0.00 0.00 10668908.02 47958503.18
April 0.936002E+09 0.946746E+09 0.211444E+10 0.00 0.00 0.00 0.00 44443698.15 4032401.43
May 0.101394E+10 0.101081E+10 0.222974E+10 0.00 0.00 0.00 0.00 0.102912E+09 1032166.42
June 0.101113E+10 0.100409E+10 0.218691E+10 0.00 0.00 0.00 0.00 68828749.92 720692.65
July 0.938820E+09 0.952733E+09 0.215669E+10 0.00 0.00 0.00 0.00 86319395.62 294048.56
August 0.105485E+10 0.106572E+10 0.227023E+10 0.00 0.00 0.00 0.00 46760439.83 534462.71
September 0.936002E+09 0.962276E+09 0.211327E+10 0.00 0.00 0.00 0.00 28918910.86 1550481.97
October 0.973041E+09 0.101505E+10 0.218984E+10 0.00 0.00 0.00 0.00 14666875.48 3754091.36
November 0.963541E+09 0.101120E+10 0.213967E+10 0.00 0.00 0.00 0.00 2741323.19 15762475.66
December 0.938820E+09 0.100043E+10 0.215610E+10 0.00 0.00 0.00 0.00 11545.02 65024649.24
                   
Annual Sum or Average 0.116768E+11 0.119895E+11 0.259979E+11 0.00 0.00 0.00 0.00 0.406889E+09 0.280745E+09
Minimum of Months 0.882782E+09 0.919572E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 294048.56
Maximum of Months 0.105485E+10 0.107117E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.102912E+09 73682212.14



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.161666E+10 0.339718E+10 0.00 0.00 0.00 0.00 141065.03 0.182132E+09
February 0.136985E+10 0.143698E+10 0.307485E+10 0.00 0.00 0.00 0.00 6258745.23 0.195400E+09
March 0.163685E+10 0.166082E+10 0.352283E+10 0.00 0.00 0.00 0.00 45844568.21 0.129575E+09
April 0.145243E+10 0.146672E+10 0.328108E+10 0.00 0.00 0.00 0.00 0.171170E+09 11707174.23
May 0.157338E+10 0.156301E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.360290E+09 2924016.12
June 0.156900E+10 0.155414E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.242925E+09 2356919.46
July 0.145680E+10 0.147360E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.300212E+09 942081.89
August 0.163685E+10 0.164848E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.172813E+09 1893888.13
September 0.145243E+10 0.149098E+10 0.327926E+10 0.00 0.00 0.00 0.00 0.100703E+09 3555333.98
October 0.150991E+10 0.157336E+10 0.339809E+10 0.00 0.00 0.00 0.00 56438318.81 11013829.80
November 0.149516E+10 0.159039E+10 0.332024E+10 0.00 0.00 0.00 0.00 14718343.46 41176133.91
December 0.145680E+10 0.158013E+10 0.334573E+10 0.00 0.00 0.00 0.00 1675484.44 0.163904E+09
                   
Annual Sum or Average 0.181194E+11 0.186553E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.147319E+10 0.746581E+09
Minimum of Months 0.136985E+10 0.143698E+10 0.307485E+10 0.00 0.00 0.00 0.00 141065.03 942081.89
Maximum of Months 0.163685E+10 0.166082E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.360290E+09 0.195400E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.103461E+10 0.218927E+10 0.00 0.00 0.00 0.00 13325.40 0.127237E+09
February 0.649041E+09 0.924273E+09 0.198155E+10 0.00 0.00 0.00 0.00 2551445.51 0.139059E+09
March 0.773965E+09 0.106879E+10 0.227025E+10 0.00 0.00 0.00 0.00 27058181.48 92435310.90
April 0.688021E+09 0.946252E+09 0.211446E+10 0.00 0.00 0.00 0.00 0.108661E+09 8992819.97
May 0.744847E+09 0.101004E+10 0.222976E+10 0.00 0.00 0.00 0.00 0.237533E+09 2035115.90
June 0.742030E+09 0.100432E+10 0.218692E+10 0.00 0.00 0.00 0.00 0.162825E+09 1602713.19
July 0.690839E+09 0.950449E+09 0.215670E+10 0.00 0.00 0.00 0.00 0.202080E+09 600874.99
August 0.773965E+09 0.106159E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.115603E+09 1277114.74
September 0.688021E+09 0.960005E+09 0.211328E+10 0.00 0.00 0.00 0.00 67116457.49 2197837.49
October 0.715730E+09 0.100892E+10 0.218986E+10 0.00 0.00 0.00 0.00 35034467.86 7895208.01
November 0.708685E+09 0.102246E+10 0.213969E+10 0.00 0.00 0.00 0.00 8331634.98 29723660.25
December 0.690839E+09 0.101200E+10 0.215612E+10 0.00 0.00 0.00 0.00 601373.24 0.115511E+09
                   
Annual Sum or Average 0.858171E+10 0.120037E+11 0.259981E+11 0.00 0.00 0.00 0.00 0.967409E+09 0.528567E+09
Minimum of Months 0.649041E+09 0.924273E+09 0.198155E+10 0.00 0.00 0.00 0.00 13325.40 600874.99
Maximum of Months 0.773965E+09 0.106879E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.237533E+09 0.139059E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.158408E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.219980E+09
February 0.136988E+10 0.142041E+10 0.307490E+10 0.00 0.00 0.00 0.00 1854000.10 0.238970E+09
March 0.163688E+10 0.165504E+10 0.352288E+10 0.00 0.00 0.00 0.00 35439110.64 0.152453E+09
April 0.145246E+10 0.146869E+10 0.328113E+10 0.00 0.00 0.00 0.00 0.161189E+09 13798674.78
May 0.157341E+10 0.156974E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.358090E+09 3050543.97
June 0.156904E+10 0.156068E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.243340E+09 2300992.48
July 0.145684E+10 0.147944E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.300233E+09 943169.63
August 0.163688E+10 0.165097E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.170260E+09 1981065.23
September 0.145246E+10 0.148901E+10 0.327931E+10 0.00 0.00 0.00 0.00 96183661.46 3891443.38
October 0.150994E+10 0.155906E+10 0.339814E+10 0.00 0.00 0.00 0.00 47208642.59 13347837.12
November 0.149520E+10 0.156263E+10 0.332029E+10 0.00 0.00 0.00 0.00 8392227.18 53439035.31
December 0.145684E+10 0.154181E+10 0.334578E+10 0.00 0.00 0.00 0.00 29237.36 0.206209E+09
                   
Annual Sum or Average 0.181198E+11 0.185416E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.142222E+10 0.910365E+09
Minimum of Months 0.136988E+10 0.142041E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 943169.63
Maximum of Months 0.163688E+10 0.165504E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.358090E+09 0.238970E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.103033E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.131170E+09
February 0.882782E+09 0.920065E+09 0.198154E+10 0.00 0.00 0.00 0.00 2091928.69 0.142461E+09
March 0.105485E+10 0.107162E+10 0.227023E+10 0.00 0.00 0.00 0.00 26251045.14 0.100582E+09
April 0.936002E+09 0.946999E+09 0.211444E+10 0.00 0.00 0.00 0.00 0.107209E+09 10552830.86
May 0.101394E+10 0.101099E+10 0.222974E+10 0.00 0.00 0.00 0.00 0.235112E+09 2695314.55
June 0.101113E+10 0.100423E+10 0.218691E+10 0.00 0.00 0.00 0.00 0.158827E+09 2121673.65
July 0.938820E+09 0.953207E+09 0.215669E+10 0.00 0.00 0.00 0.00 0.197143E+09 784003.02
August 0.105485E+10 0.106602E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.112337E+09 1635716.68
September 0.936002E+09 0.962585E+09 0.211327E+10 0.00 0.00 0.00 0.00 65389353.78 2905783.35
October 0.973041E+09 0.101548E+10 0.218984E+10 0.00 0.00 0.00 0.00 35039359.78 8042921.97
November 0.963541E+09 0.101159E+10 0.213967E+10 0.00 0.00 0.00 0.00 8179788.57 29731396.30
December 0.938820E+09 0.100094E+10 0.215610E+10 0.00 0.00 0.00 0.00 404557.99 0.118975E+09
                   
Annual Sum or Average 0.116768E+11 0.119941E+11 0.259979E+11 0.00 0.00 0.00 0.00 0.947985E+09 0.551659E+09
Minimum of Months 0.882782E+09 0.920065E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 784003.02
Maximum of Months 0.105485E+10 0.107162E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.235112E+09 0.142461E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.161667E+10 0.339718E+10 0.00 0.00 0.00 0.00 392441.64 0.188412E+09
February 0.136985E+10 0.143697E+10 0.307485E+10 0.00 0.00 0.00 0.00 10215370.88 0.213175E+09
March 0.163685E+10 0.166082E+10 0.352283E+10 0.00 0.00 0.00 0.00 56647777.02 0.152624E+09
April 0.145243E+10 0.146673E+10 0.328108E+10 0.00 0.00 0.00 0.00 0.207446E+09 14138246.33
May 0.157338E+10 0.156300E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.439974E+09 3678819.84
June 0.156900E+10 0.155410E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.297038E+09 3123361.73
July 0.145680E+10 0.147358E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.366610E+09 1187027.41
August 0.163685E+10 0.164837E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.209827E+09 2599283.24
September 0.145243E+10 0.149096E+10 0.327926E+10 0.00 0.00 0.00 0.00 0.123180E+09 4396860.02
October 0.150991E+10 0.157335E+10 0.339809E+10 0.00 0.00 0.00 0.00 69480443.45 12934859.21
November 0.149516E+10 0.159039E+10 0.332024E+10 0.00 0.00 0.00 0.00 20257287.69 45222591.56
December 0.145680E+10 0.158015E+10 0.334573E+10 0.00 0.00 0.00 0.00 3324962.99 0.173229E+09
                   
Annual Sum or Average 0.181194E+11 0.186551E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.180439E+10 0.814721E+09
Minimum of Months 0.136985E+10 0.143697E+10 0.307485E+10 0.00 0.00 0.00 0.00 392441.64 1187027.41
Maximum of Months 0.163685E+10 0.166082E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.439974E+09 0.213175E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.103462E+10 0.218927E+10 0.00 0.00 0.00 0.00 65011.45 0.135266E+09
February 0.882782E+09 0.924276E+09 0.198155E+10 0.00 0.00 0.00 0.00 3781845.48 0.157629E+09
March 0.105485E+10 0.106879E+10 0.227025E+10 0.00 0.00 0.00 0.00 32201356.84 0.112750E+09
April 0.936002E+09 0.946256E+09 0.211446E+10 0.00 0.00 0.00 0.00 0.130823E+09 11340395.52
May 0.101394E+10 0.101004E+10 0.222976E+10 0.00 0.00 0.00 0.00 0.288024E+09 2666413.11
June 0.101113E+10 0.100432E+10 0.218692E+10 0.00 0.00 0.00 0.00 0.197875E+09 2138722.30
July 0.938820E+09 0.950438E+09 0.215670E+10 0.00 0.00 0.00 0.00 0.245144E+09 774820.56
August 0.105485E+10 0.106158E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.139331E+09 1757266.62
September 0.936002E+09 0.960000E+09 0.211328E+10 0.00 0.00 0.00 0.00 81415394.92 2825649.85
October 0.973041E+09 0.100892E+10 0.218986E+10 0.00 0.00 0.00 0.00 42190021.37 9676490.44
November 0.963541E+09 0.102247E+10 0.213969E+10 0.00 0.00 0.00 0.00 10507531.78 34321856.79
December 0.938820E+09 0.101202E+10 0.215612E+10 0.00 0.00 0.00 0.00 1086303.66 0.126078E+09
                   
Annual Sum or Average 0.116768E+11 0.120037E+11 0.259981E+11 0.00 0.00 0.00 0.00 0.117244E+10 0.597223E+09
Minimum of Months 0.882782E+09 0.924276E+09 0.198155E+10 0.00 0.00 0.00 0.00 65011.45 774820.56
Maximum of Months 0.105485E+10 0.106879E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.288024E+09 0.157629E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.158409E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.243475E+09
February 0.136988E+10 0.142041E+10 0.307490E+10 0.00 0.00 0.00 0.00 2076604.50 0.274561E+09
March 0.163688E+10 0.165505E+10 0.352288E+10 0.00 0.00 0.00 0.00 42835129.17 0.185194E+09
April 0.145246E+10 0.146869E+10 0.328113E+10 0.00 0.00 0.00 0.00 0.196374E+09 17145867.70
May 0.157341E+10 0.156973E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.437146E+09 3857179.41
June 0.156904E+10 0.156066E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.297320E+09 3067846.98
July 0.145684E+10 0.147941E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.366426E+09 1188676.94
August 0.163688E+10 0.165095E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.206868E+09 2722521.55
September 0.145246E+10 0.148899E+10 0.327931E+10 0.00 0.00 0.00 0.00 0.117920E+09 4913728.41
October 0.150994E+10 0.155905E+10 0.339814E+10 0.00 0.00 0.00 0.00 57575980.20 16266024.03
November 0.149520E+10 0.156264E+10 0.332029E+10 0.00 0.00 0.00 0.00 9980671.68 62882782.85
December 0.145684E+10 0.154185E+10 0.334578E+10 0.00 0.00 0.00 0.00 24857.13 0.232157E+09
                   
Annual Sum or Average 0.181198E+11 0.185415E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.173455E+10 0.104743E+10
Minimum of Months 0.136988E+10 0.142041E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 1188676.94
Maximum of Months 0.163688E+10 0.165505E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.437146E+09 0.274561E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.103035E+10 0.218926E+10 0.00 0.00 0.00 0.00 12891.05 0.144105E+09
February 0.882782E+09 0.920071E+09 0.198154E+10 0.00 0.00 0.00 0.00 3289615.06 0.162435E+09
March 0.105485E+10 0.107166E+10 0.227023E+10 0.00 0.00 0.00 0.00 32186575.14 0.121527E+09
April 0.936002E+09 0.947004E+09 0.211444E+10 0.00 0.00 0.00 0.00 0.131230E+09 13076826.83
May 0.101394E+10 0.101099E+10 0.222974E+10 0.00 0.00 0.00 0.00 0.288672E+09 3320563.28
June 0.101113E+10 0.100422E+10 0.218691E+10 0.00 0.00 0.00 0.00 0.195331E+09 2596998.40
July 0.938820E+09 0.953190E+09 0.215669E+10 0.00 0.00 0.00 0.00 0.242818E+09 988145.35
August 0.105485E+10 0.106600E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.137596E+09 2172285.51
September 0.936002E+09 0.962577E+09 0.211327E+10 0.00 0.00 0.00 0.00 80638832.02 3577089.34
October 0.973041E+09 0.101547E+10 0.218984E+10 0.00 0.00 0.00 0.00 43290897.59 9669843.24
November 0.963541E+09 0.101166E+10 0.213967E+10 0.00 0.00 0.00 0.00 10652120.50 34170683.54
December 0.938820E+09 0.100095E+10 0.215610E+10 0.00 0.00 0.00 0.00 667347.26 0.132629E+09
                   
Annual Sum or Average 0.116768E+11 0.119941E+11 0.259979E+11 0.00 0.00 0.00 0.00 0.116638E+10 0.630269E+09
Minimum of Months 0.882782E+09 0.920071E+09 0.198154E+10 0.00 0.00 0.00 0.00 12891.05 988145.35
Maximum of Months 0.105485E+10 0.107166E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.288672E+09 0.162435E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.497722E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.451470E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.536472E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.479179E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.517097E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.514597E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.481680E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.536472E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.479179E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.497722E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.491888E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.481680E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.596516E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.451470E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.536472E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.497722E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.451470E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.536472E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.479179E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.517097E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.514597E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.481680E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.536472E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.479179E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.497722E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.491888E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.481680E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.596516E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.451470E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.536472E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.497722E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.451470E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.536472E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.479179E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.517097E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.514597E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.481680E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.536472E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.479179E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.497722E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.491888E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.481680E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.596516E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.451470E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.536472E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.565679E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.513113E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.609720E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.544605E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.587700E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.584858E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.547447E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.609720E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.544605E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.565679E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.559049E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.547447E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.677962E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.513113E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.609720E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.201323E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1018758.60 0.213512E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29708988.62 0.130886E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.133306E+09 9858134.55
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.296153E+09 2771589.55
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.200598E+09 1460523.74
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.253396E+09 694790.28
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.139513E+09 1046417.69
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 79944417.28 2056090.87
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40800243.27 11184538.56
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6807208.04 46252444.46
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.185859E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.118125E+10 0.806905E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 694790.28
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.296153E+09 0.213512E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.341267E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2742506.10 0.363278E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54990182.84 0.230750E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.241294E+09 19811319.99
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.535096E+09 4976983.96
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.359830E+09 2831530.77
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.454209E+09 1321640.19
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.250811E+09 2195303.04
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.142919E+09 3669925.75
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74032155.07 20159522.92
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13681760.37 78591918.76
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 234224.81 0.310330E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.212984E+10 0.137918E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1321640.19
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.535096E+09 0.363278E+09



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.329755E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 716501.58 0.368207E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 46160419.26 0.243634E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.239612E+09 19079598.74
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.570072E+09 5684846.45
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.388214E+09 3564368.87
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.475315E+09 1379858.09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.260946E+09 3633068.16
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.145497E+09 4717351.83
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70416828.26 19795243.97
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10375023.62 76961890.39
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330795.55 0.298426E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.220766E+10 0.137484E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1379858.09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.570072E+09 0.368207E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 20994.62 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 20994.62 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 20994.62 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 20994.62 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 20994.62 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 20994.62 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 20994.62 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 20994.62 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 20994.62 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 20994.62 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 20994.62 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 20994.62 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   20994.62   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   20994.62   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18854.65 02-JAN-08:09 18128.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18854.65 01-FEB-08:09 18128.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18854.65 01-MAR-08:09 18128.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18854.65 03-APR-07:10 18128.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18854.65 01-MAY-07:10 18128.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18854.65 01-JUN-07:10 18128.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18854.65 03-JUL-07:10 18128.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18854.65 01-AUG-07:10 18128.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18854.65 01-SEP-07:10 18128.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18854.65 02-OCT-07:10 18128.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18854.65 01-NOV-07:10 18128.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18854.65 01-DEC-08:09 18128.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18854.65   18128.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18854.65   18128.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18854.65 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18854.65 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18854.65 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18854.65 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18854.65 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18854.65 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18854.65 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18854.65 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18854.65 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18854.65 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18854.65 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18854.65 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18854.65 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18854.65 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18854.65 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18854.65 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18854.65 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18854.65 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18854.65 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18854.65 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18854.65 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18854.65 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18854.65 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18854.65 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2053.69 18-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 237.61 15-JAN-17:00
February 2010.79 01-FEB-10:09 2020.68 10-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 57.68 19-FEB-15:10 311.69 09-FEB-22:20
March 2010.79 01-MAR-10:09 2037.36 14-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 221.92 26-MAR-15:00 688.33 24-MAR-24:00
April 2010.79 03-APR-09:09 1454.29 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 360.35 15-APR-17:02 99.18 22-APR-17:50
May 2010.79 01-MAY-09:09 1690.49 24-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 612.38 28-MAY-14:25 47.38 13-MAY-03:00
June 2010.79 01-JUN-09:09 1678.00 23-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 307.61 17-JUN-20:50 48.67 18-JUN-05:00
July 2010.79 03-JUL-09:09 1974.74 26-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 303.30 02-JUL-11:50 41.56 19-JUL-02:30
August 2010.79 01-AUG-09:09 2023.33 16-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 197.88 06-AUG-13:47 40.43 15-AUG-23:50
September 2010.79 01-SEP-09:09 2071.97 08-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 176.85 24-SEP-14:50 28.22 08-SEP-22:20
October 2010.79 02-OCT-09:09 2158.51 11-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 215.60 15-OCT-12:10 95.91 12-OCT-03:00
November 2010.79 01-NOV-09:09 2124.33 27-NOV-16:00 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 76.44 12-NOV-14:00 156.22 28-NOV-04:43
December 2010.79 01-DEC-10:09 2135.26 29-DEC-16:00 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 20.55 24-DEC-14:10 367.18 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1454.29   2276.32   0.00 0.00 0.00 0.00 0.00   28.22  
Maximum of Months 2010.79   2158.51   2276.32   0.00 0.00 0.00 0.00 612.38   688.33  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1316.68 17-JAN-16:00 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 155.11 15-JAN-17:00
February 1295.83 01-FEB-10:09 1309.00 09-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 35.77 19-FEB-15:10 197.95 09-FEB-22:20
March 1295.83 01-MAR-10:09 1230.05 14-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 141.67 26-MAR-15:00 451.85 24-MAR-24:00
April 1295.83 03-APR-09:09 937.20 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 242.87 15-APR-17:02 59.75 22-APR-17:50
May 1295.83 01-MAY-09:09 937.20 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 406.33 28-MAY-14:24 30.95 15-MAY-02:40
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 215.59 17-JUN-21:10 28.22 18-JUN-05:10
July 1295.83 03-JUL-09:09 1241.75 26-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 203.85 02-JUL-11:45 22.43 19-JUL-02:30
August 1295.83 01-AUG-09:09 1276.47 16-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 136.73 06-AUG-13:50 20.64 15-AUG-23:50
September 1295.83 01-SEP-09:09 1310.06 07-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 121.23 24-SEP-14:10 15.83 08-SEP-22:20
October 1295.83 02-OCT-09:09 1375.35 11-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 138.55 15-OCT-12:10 59.05 12-OCT-03:00
November 1295.83 01-NOV-09:09 1392.81 27-NOV-16:00 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 51.89 12-NOV-14:00 100.71 28-NOV-04:43
December 1295.83 01-DEC-10:09 1385.08 29-DEC-16:00 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 13.80 24-DEC-14:10 230.16 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.95   0.00 0.00 0.00 0.00 0.00   15.83  
Maximum of Months 1295.83   1392.81   1466.95   0.00 0.00 0.00 0.00 406.33   451.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1993.21 18-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 241.52 22-JAN-14:13
February 2010.83 01-FEB-10:09 1970.72 10-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 12.62 21-FEB-15:00 307.14 09-FEB-22:20
March 2010.83 01-MAR-10:09 2019.13 14-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 161.17 26-MAR-14:58 746.89 24-MAR-24:00
April 2010.83 03-APR-09:09 1454.32 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 346.70 15-APR-17:02 104.79 22-APR-17:50
May 2010.83 01-MAY-09:09 1742.03 24-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 604.46 28-MAY-14:24 49.27 15-MAY-02:40
June 2010.83 01-JUN-09:09 1754.19 23-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 308.43 17-JUN-20:35 49.22 18-JUN-05:00
July 2010.83 03-JUL-09:09 1997.05 26-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 301.28 02-JUL-11:47 40.99 19-JUL-02:30
August 2010.83 01-AUG-09:09 2033.20 16-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 195.66 06-AUG-13:45 41.73 15-AUG-23:50
September 2010.83 01-SEP-09:09 2069.09 08-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 161.52 24-SEP-14:06 27.09 08-SEP-22:20
October 2010.83 02-OCT-09:09 2150.01 11-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 176.63 15-OCT-12:45 96.17 12-OCT-03:00
November 2010.83 01-NOV-09:09 1997.86 27-NOV-16:00 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 36.90 12-NOV-14:35 170.47 29-NOV-24:00
December 2010.83 01-DEC-10:09 2079.48 29-DEC-16:00 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 2.90 28-DEC-14:00 405.43 31-DEC-15:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1454.32   2276.35   0.00 0.00 0.00 0.00 0.00   27.09  
Maximum of Months 2010.83   2150.01   2276.35   0.00 0.00 0.00 0.00 604.46   746.89  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1332.60 18-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 170.84 15-JAN-17:00
February 1295.83 01-FEB-10:09 1315.32 10-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 8.43 21-FEB-15:00 229.10 09-FEB-22:20
March 1295.83 01-MAR-10:09 1346.92 14-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 109.74 26-MAR-13:00 616.82 24-MAR-24:00
April 1295.83 03-APR-09:09 1161.65 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 223.74 15-APR-17:07 115.48 22-APR-17:50
May 1295.83 01-MAY-09:09 1172.53 24-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 405.70 28-MAY-13:44 45.28 15-MAY-02:40
June 1295.83 01-JUN-09:09 1174.34 23-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 194.90 17-JUN-21:10 47.14 18-JUN-05:00
July 1295.83 03-JUL-09:09 1301.32 26-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 206.44 02-JUL-11:47 41.55 19-JUL-02:30
August 1295.83 01-AUG-09:09 1325.08 16-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 128.13 06-AUG-09:46 47.85 15-AUG-23:50
September 1295.83 01-SEP-09:09 1349.18 08-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 118.89 24-SEP-14:06 26.93 08-SEP-22:20
October 1295.83 02-OCT-09:09 1397.15 11-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 143.15 15-OCT-12:10 78.78 12-OCT-03:00
November 1295.83 01-NOV-09:09 1298.06 03-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 31.70 12-NOV-12:40 128.35 29-NOV-24:00
December 1295.83 01-DEC-10:09 1322.25 29-DEC-16:00 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 1.95 28-DEC-14:00 293.23 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1161.65   1466.94   0.00 0.00 0.00 0.00 0.00   26.93  
Maximum of Months 1295.83   1397.15   1466.94   0.00 0.00 0.00 0.00 405.70   616.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2062.64 18-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 29.81 08-JAN-15:00 476.68 15-JAN-17:00
February 2010.79 01-FEB-10:09 2030.61 10-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 208.65 19-FEB-15:00 652.28 09-FEB-22:10
March 2010.79 01-MAR-10:09 2047.04 14-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 553.85 26-MAR-15:00 1327.01 24-MAR-24:00
April 2010.79 03-APR-09:09 1454.29 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 856.86 15-APR-17:02 207.48 22-APR-18:30
May 2010.79 01-MAY-09:09 1710.01 24-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 1426.61 28-MAY-14:56 119.57 15-MAY-03:00
June 2010.79 01-JUN-09:09 1697.89 23-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 703.88 17-JUN-20:50 119.22 18-JUN-05:00
July 2010.79 03-JUL-09:09 1986.21 26-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 710.95 02-JUL-12:08 107.25 19-JUL-02:55
August 2010.79 01-AUG-09:09 2033.40 16-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 486.16 06-AUG-09:00 125.16 15-AUG-24:00
September 2010.79 01-SEP-09:09 2080.61 08-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 408.55 24-SEP-14:20 53.43 08-SEP-22:20
October 2010.79 02-OCT-09:09 2164.62 11-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 511.96 15-OCT-12:10 211.35 12-OCT-03:00
November 2010.79 01-NOV-09:09 2131.35 27-NOV-16:00 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 222.34 12-NOV-14:00 337.17 28-NOV-04:53
December 2010.79 01-DEC-10:09 2141.99 29-DEC-16:00 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 141.18 24-DEC-14:10 720.80 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1454.29   2276.32   0.00 0.00 0.00 0.00 29.81   53.43  
Maximum of Months 2010.79   2164.62   2276.32   0.00 0.00 0.00 0.00 1426.61   1327.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1318.37 17-JAN-16:00 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 9.10 08-JAN-15:00 316.88 15-JAN-17:00
February 1239.33 01-FEB-08:09 1310.64 09-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 107.20 19-FEB-15:00 425.96 18-FEB-06:00
March 1239.33 01-MAR-08:09 1233.40 14-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 321.87 26-MAR-15:00 941.06 24-MAR-24:00
April 1239.33 03-APR-07:10 937.20 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 561.90 15-APR-17:02 157.03 22-APR-18:10
May 1239.33 01-MAY-07:10 937.20 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 956.08 28-MAY-14:54 89.34 15-MAY-03:00
June 1239.33 01-JUN-07:10 937.20 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 485.83 17-JUN-20:50 79.17 18-JUN-05:00
July 1239.33 03-JUL-07:10 1246.24 26-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 480.41 02-JUL-12:08 69.74 19-JUL-02:55
August 1239.33 01-AUG-07:10 1279.69 16-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 316.39 06-AUG-14:20 86.02 15-AUG-24:00
September 1239.33 01-SEP-07:10 1312.79 08-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 273.39 24-SEP-15:00 32.24 08-SEP-22:20
October 1239.33 02-OCT-07:10 1376.92 11-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 313.55 15-OCT-12:50 140.43 12-OCT-03:00
November 1239.33 01-NOV-07:10 1394.00 27-NOV-16:00 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 130.61 12-NOV-14:00 232.34 28-NOV-04:53
December 1239.33 01-DEC-08:09 1386.20 29-DEC-16:00 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 67.91 24-DEC-14:10 470.90 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   937.20   1466.95   0.00 0.00 0.00 0.00 9.10   32.24  
Maximum of Months 1239.33   1394.00   1466.95   0.00 0.00 0.00 0.00 956.08   941.06  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2006.26 18-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 574.19 22-JAN-14:50
February 2010.83 01-FEB-10:09 1982.43 10-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 28.20 21-FEB-15:00 677.82 18-FEB-05:53
March 2010.83 01-MAR-10:09 2029.53 14-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 355.75 26-MAR-14:58 1528.21 24-MAR-24:00
April 2010.83 03-APR-09:09 1454.32 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 817.93 15-APR-17:02 234.31 22-APR-18:10
May 2010.83 01-MAY-09:09 1759.65 24-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 1429.77 28-MAY-14:54 129.34 15-MAY-03:00
June 2010.83 01-JUN-09:09 1771.33 23-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 709.81 17-JUN-20:50 118.05 18-JUN-05:00
July 2010.83 03-JUL-09:09 2007.69 26-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 710.81 02-JUL-12:08 106.87 19-JUL-02:55
August 2010.83 01-AUG-09:09 2042.89 16-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 481.15 06-AUG-09:00 128.43 15-AUG-24:00
September 2010.83 01-SEP-09:09 2077.84 08-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 371.86 24-SEP-14:55 54.18 08-SEP-22:20
October 2010.83 02-OCT-09:09 2156.47 11-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 384.08 15-OCT-13:24 218.73 12-OCT-03:00
November 2010.83 01-NOV-09:09 2009.34 27-NOV-16:00 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 72.22 13-NOV-14:00 388.12 28-NOV-04:53
December 2010.83 01-DEC-10:09 2088.27 29-DEC-16:00 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 5.58 28-DEC-14:00 933.47 31-DEC-14:27
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1454.32   2276.35   0.00 0.00 0.00 0.00 0.00   54.18  
Maximum of Months 2010.83   2156.47   2276.35   0.00 0.00 0.00 0.00 1429.77   1528.21  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1334.11 18-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 330.84 15-JAN-17:00
February 1295.83 01-FEB-10:09 1316.91 10-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 73.08 19-FEB-14:20 437.83 18-FEB-06:00
March 1295.83 01-MAR-10:09 1348.23 14-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 328.18 26-MAR-13:00 1037.32 24-MAR-24:00
April 1295.83 03-APR-09:09 1165.32 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 530.89 15-APR-17:08 162.98 22-APR-18:10
May 1295.83 01-MAY-09:09 1175.10 24-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 940.55 28-MAY-14:15 114.16 15-MAY-03:00
June 1295.83 01-JUN-09:09 1176.91 23-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 453.78 17-JUN-20:35 95.41 18-JUN-04:03
July 1295.83 03-JUL-09:09 1302.96 26-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 488.10 02-JUL-12:10 75.50 19-JUL-02:55
August 1295.83 01-AUG-09:09 1326.56 16-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 338.67 06-AUG-09:40 93.62 15-AUG-24:00
September 1295.83 01-SEP-09:09 1350.48 08-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 260.21 24-SEP-14:15 36.68 08-SEP-22:20
October 1295.83 02-OCT-09:09 1398.10 11-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 359.71 15-OCT-12:10 146.53 12-OCT-03:00
November 1295.83 01-NOV-09:09 1300.59 03-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 124.07 12-NOV-13:20 242.16 28-NOV-04:53
December 1295.83 01-DEC-10:09 1324.39 29-DEC-16:00 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 50.10 24-DEC-13:43 493.06 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1165.32   1466.94   0.00 0.00 0.00 0.00 0.00   36.68  
Maximum of Months 1295.83   1398.10   1466.94   0.00 0.00 0.00 0.00 940.55   1037.32  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2062.35 18-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 63.35 08-JAN-15:00 502.41 15-JAN-17:00
February 2010.79 01-FEB-10:09 2030.29 10-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 279.84 19-FEB-15:10 735.41 09-FEB-22:10
March 2010.79 01-MAR-10:09 2046.81 14-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 675.22 26-MAR-15:00 1525.99 24-MAR-24:00
April 2010.79 03-APR-09:09 1454.29 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 1027.08 15-APR-17:02 235.01 22-APR-18:30
May 2010.79 01-MAY-09:09 1709.49 24-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 1738.15 28-MAY-13:56 154.86 15-MAY-02:28
June 2010.79 01-JUN-09:09 1697.36 23-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 833.43 17-JUN-20:50 158.38 18-JUN-04:03
July 2010.79 03-JUL-09:09 1985.85 26-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 869.57 02-JUL-11:58 130.63 19-JUL-02:55
August 2010.79 01-AUG-09:09 2033.08 16-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 598.84 06-AUG-09:20 171.20 15-AUG-24:00
September 2010.79 01-SEP-09:09 2080.33 08-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 487.17 24-SEP-14:30 59.39 08-SEP-22:20
October 2010.79 02-OCT-09:09 2164.41 11-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 639.38 15-OCT-12:20 246.90 12-OCT-03:00
November 2010.79 01-NOV-09:09 2131.24 27-NOV-16:00 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 274.50 12-NOV-13:50 367.41 28-NOV-04:53
December 2010.79 01-DEC-10:09 2141.79 29-DEC-16:00 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 231.72 24-DEC-14:10 790.05 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1454.29   2276.32   0.00 0.00 0.00 0.00 63.35   59.39  
Maximum of Months 2010.79   2164.41   2276.32   0.00 0.00 0.00 0.00 1738.15   1525.99  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1318.22 17-JAN-16:00 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 23.37 08-JAN-15:00 334.40 15-JAN-17:00
February 1295.83 01-FEB-10:09 1310.43 09-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 140.59 19-FEB-15:10 486.04 09-FEB-22:10
March 1295.83 01-MAR-10:09 1233.32 14-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 392.78 26-MAR-15:00 1104.25 24-MAR-24:00
April 1295.83 03-APR-09:09 937.20 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 663.71 15-APR-17:02 184.80 22-APR-18:10
May 1295.83 01-MAY-09:09 937.20 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 1147.07 28-MAY-14:54 116.68 15-MAY-02:28
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 567.43 17-JUN-21:10 106.21 18-JUN-04:03
July 1295.83 03-JUL-09:09 1246.05 26-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 583.79 02-JUL-11:58 85.40 19-JUL-02:55
August 1295.83 01-AUG-09:09 1279.53 16-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 389.56 06-AUG-14:00 117.77 15-AUG-24:00
September 1295.83 01-SEP-09:09 1312.64 08-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 331.20 24-SEP-14:30 36.55 08-SEP-22:20
October 1295.83 02-OCT-09:09 1376.81 11-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 377.50 15-OCT-13:00 165.06 12-OCT-03:00
November 1295.83 01-NOV-09:09 1393.93 27-NOV-16:00 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 156.90 12-NOV-13:50 258.70 28-NOV-04:53
December 1295.83 01-DEC-10:09 1386.08 29-DEC-16:00 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 116.29 24-DEC-14:40 523.70 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.95   0.00 0.00 0.00 0.00 23.37   36.55  
Maximum of Months 1295.83   1393.93   1466.95   0.00 0.00 0.00 0.00 1147.07   1104.25  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2006.00 18-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 664.79 22-JAN-15:00
February 2010.83 01-FEB-10:09 1982.11 10-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 33.31 21-FEB-15:00 777.64 18-FEB-05:53
March 2010.83 01-MAR-10:09 2029.30 14-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 442.80 26-MAR-14:58 1804.80 24-MAR-24:00
April 2010.83 03-APR-09:09 1454.32 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 975.31 15-APR-17:02 271.56 22-APR-18:10
May 2010.83 01-MAY-09:09 1759.12 24-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 1720.61 28-MAY-14:53 166.88 15-MAY-02:28
June 2010.83 01-JUN-09:09 1770.81 23-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 838.79 17-JUN-20:50 156.91 18-JUN-04:03
July 2010.83 03-JUL-09:09 2007.33 26-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 867.64 02-JUL-11:58 130.15 19-JUL-02:55
August 2010.83 01-AUG-09:09 2042.57 16-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 587.68 06-AUG-09:20 175.58 15-AUG-24:00
September 2010.83 01-SEP-09:09 2077.55 08-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 472.23 24-SEP-14:28 60.42 08-SEP-22:20
October 2010.83 02-OCT-09:09 2156.27 11-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 475.92 15-OCT-12:15 256.95 12-OCT-03:00
November 2010.83 01-NOV-09:09 2009.29 27-NOV-16:00 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 96.43 12-NOV-14:25 440.75 28-NOV-04:53
December 2010.83 01-DEC-10:09 2088.10 29-DEC-16:00 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 5.41 28-DEC-14:00 1074.19 31-DEC-14:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1454.32   2276.35   0.00 0.00 0.00 0.00 0.00   60.42  
Maximum of Months 2010.83   2156.27   2276.35   0.00 0.00 0.00 0.00 1720.61   1804.80  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1333.93 18-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 13.45 08-JAN-13:57 362.78 15-JAN-17:00
February 1295.83 01-FEB-10:09 1316.71 10-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 111.13 19-FEB-13:50 503.76 18-FEB-05:53
March 1295.83 01-MAR-10:09 1348.07 14-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 400.61 26-MAR-13:00 1219.68 24-MAR-24:00
April 1295.83 03-APR-09:09 1165.33 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 652.30 15-APR-17:08 187.56 22-APR-18:10
May 1295.83 01-MAY-09:09 1174.77 24-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 1147.07 28-MAY-14:54 139.10 15-MAY-02:28
June 1295.83 01-JUN-09:09 1176.59 23-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 546.47 17-JUN-21:10 123.17 18-JUN-03:55
July 1295.83 03-JUL-09:09 1302.74 26-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 597.34 02-JUL-12:00 91.89 19-JUL-02:55
August 1295.83 01-AUG-09:09 1326.36 16-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 426.10 06-AUG-09:20 126.41 15-AUG-24:00
September 1295.83 01-SEP-09:09 1350.30 08-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 324.03 24-SEP-14:28 40.67 08-SEP-22:20
October 1295.83 02-OCT-09:09 1397.97 11-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 445.74 15-OCT-12:20 172.53 12-OCT-03:00
November 1295.83 01-NOV-09:09 1300.54 03-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 152.53 12-NOV-13:10 273.49 28-NOV-04:53
December 1295.83 01-DEC-10:09 1324.31 29-DEC-16:00 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 81.56 24-DEC-13:40 549.94 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1165.33   1466.94   0.00 0.00 0.00 0.00 13.45   40.67  
Maximum of Months 1295.83   1397.97   1466.94   0.00 0.00 0.00 0.00 1147.07   1219.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 520.85 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 520.85 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 520.85 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 520.85 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 520.85 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 520.85 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 520.85 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 520.85 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 520.85 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 520.85 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 520.85 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 520.85 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   520.85   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   520.85   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 520.85 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 520.85 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 520.85 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 520.85 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 520.85 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 520.85 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 520.85 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 520.85 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 520.85 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 520.85 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 520.85 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 520.85 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   520.85   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   520.85   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 520.85 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 520.85 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 520.85 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 520.85 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 520.85 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 520.85 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 520.85 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 520.85 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 520.85 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 520.85 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 520.85 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 520.85 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   520.85   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   520.85   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 5919.59 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 5919.59 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 5919.59 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 5919.59 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 5919.59 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 5919.59 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 5919.59 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 5919.59 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 5919.59 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 5919.59 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 5919.59 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 5919.59 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   5919.59   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   5919.59   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 491.45 15-JAN-17:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.26 19-FEB-14:52 696.13 09-FEB-22:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 357.37 26-MAR-14:42 1458.00 24-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 715.93 15-APR-17:02 208.45 22-APR-17:56
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1227.71 28-MAY-14:51 86.97 13-MAY-03:04
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 574.17 03-JUN-17:02 92.41 18-JUN-05:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 600.38 02-JUL-12:00 78.68 19-JUL-02:38
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 387.58 06-AUG-14:00 77.81 15-AUG-23:50
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 334.42 24-SEP-14:30 38.85 08-SEP-22:20
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 372.71 15-OCT-12:30 185.27 12-OCT-03:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 86.63 12-NOV-14:20 352.21 28-NOV-04:53
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 776.90 29-DEC-24:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   38.85  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1227.71   1458.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 827.14 15-JAN-17:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 125.84 19-FEB-15:00 1213.61 09-FEB-22:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 694.90 26-MAR-14:42 2473.87 24-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1310.19 15-APR-17:02 354.96 22-APR-18:20
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2204.89 28-MAY-14:40 155.78 13-MAY-03:04
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1043.19 03-JUN-17:02 166.49 18-JUN-05:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1107.28 02-JUL-11:50 144.71 19-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 739.89 06-AUG-14:00 153.28 15-AUG-24:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 614.19 24-SEP-14:00 67.09 19-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 682.55 15-OCT-12:30 327.30 12-OCT-03:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 197.35 12-NOV-14:00 607.37 28-NOV-05:05
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43.21 24-DEC-13:52 1318.72 29-DEC-24:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   67.09  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2204.89   2473.87  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 809.17 15-JAN-17:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.54 19-FEB-14:52 1230.15 09-FEB-22:03
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 532.26 26-MAR-14:40 2445.47 24-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1344.94 15-APR-17:02 302.69 22-APR-18:40
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2164.30 28-MAY-15:00 179.96 13-MAY-03:04
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1127.02 17-JUN-20:50 201.13 18-JUN-05:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1032.49 02-JUL-10:52 156.97 19-JUL-02:55
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 698.32 06-AUG-08:52 225.39 15-AUG-24:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 535.44 24-SEP-14:10 64.37 19-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 628.77 15-OCT-11:52 350.27 12-OCT-03:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 145.09 12-NOV-14:10 569.61 28-NOV-04:53
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 72.42 24-DEC-15:00 1261.40 29-DEC-24:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   64.37  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2164.30   2445.47  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 103951.05 02-JAN-04:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
February 109229.72 06-FEB-04:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
March 99597.32 20-MAR-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
April 103960.08 28-APR-03:02 0.00 6998.55 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
May 101121.25 29-MAY-17:30 0.00 8164.98 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
June 97197.30 04-JUN-16:18 8078.51 10497.83 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
July 90226.06 04-JUL-17:50 0.00 8164.98 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
August 89891.21 22-AUG-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
September 91295.74 26-SEP-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
October 101896.69 22-OCT-14:58 5385.68 6998.55 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
November 100328.77 25-NOV-04:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
December 104029.50 04-DEC-04:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 89891.21   0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 109229.72   8078.51 10497.83 121117.90 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 99916.88 02-JAN-04:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
February 99228.75 27-FEB-04:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
March 96286.94 20-MAR-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
April 91047.23 03-APR-05:03 9673.43 12570.39 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
May 90543.43 23-MAY-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
June 89334.66 12-JUN-05:02 9673.43 12570.39 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
July 88616.29 03-JUL-05:05 9673.43 12570.39 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
August 89718.17 07-AUG-05:01 11285.67 14665.45 56400.06 0.00 0.00 0.00 0.00 0.00 0.00
September 92135.53 09-SEP-03:02 0.00 5237.66 30214.32 0.00 0.00 0.00 0.00 0.00 0.00
October 96183.40 31-OCT-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
November 98643.62 27-NOV-04:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
December 97215.02 04-DEC-04:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 88616.29   0.00 5237.66 30214.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 99916.88   11285.67 14665.45 56400.06 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 84447.06 14-JAN-06:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
February 89117.55 27-FEB-04:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
March 88362.11 14-MAR-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
April 88104.09 10-APR-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
May 85296.08 23-MAY-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
June 85511.90 28-JUN-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 86492.59 19-JUL-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 85206.90 24-AUG-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 86005.11 05-SEP-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
October 88145.15 24-OCT-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
November 85450.51 21-NOV-05:03 0.00 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
December 84218.72 16-DEC-06:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 84218.72   0.00 5237.66 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 89117.55   8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 38168.36 26-JAN-16:20 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 83378.14 23-FEB-06:03 6448.95 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
March 90633.37 30-MAR-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
April 88943.51 17-APR-05:03 9673.43 12570.39 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
May 88053.44 30-MAY-05:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
June 89421.07 12-JUN-05:02 9673.43 12570.39 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
July 88435.22 28-JUL-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 90084.88 21-AUG-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 91320.89 11-SEP-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
October 89812.63 05-OCT-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
November 85308.42 01-NOV-05:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
December 64695.22 29-DEC-06:03 6448.95 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 38168.36   0.00 5237.66 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 91320.89   15316.26 18854.65 48342.72 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5168.16 26-JAN-14:10 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 9.00
February 6947.13 23-FEB-14:30 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 5.79 0.00
March 14150.29 14-MAR-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 3.63
April 17247.52 17-APR-05:02 1214.60 1578.34 6070.18 0.00 0.00 0.00 0.00 0.00 0.04
May 20475.13 29-MAY-16:11 1012.16 807.98 7587.73 0.00 0.00 0.00 0.00 196.83 0.00
June 20164.92 11-JUN-17:02 0.00 484.79 4552.64 0.00 0.00 0.00 0.00 99.48 0.00
July 21474.38 02-JUL-16:21 910.95 727.18 6828.95 0.00 0.00 0.00 0.00 171.23 0.00
August 19657.47 06-AUG-15:01 708.51 565.58 5311.41 0.00 0.00 0.00 0.00 179.84 0.00
September 17183.10 05-SEP-03:02 0.00 657.64 5058.48 0.00 0.00 0.00 0.00 2.35 0.00
October 15461.45 11-OCT-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 0.91
November 9034.84 06-NOV-06:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 0.00
December 6111.32 26-DEC-14:10 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 1.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5168.16   0.00 484.79 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21474.38   2010.79 1578.34 7587.73 0.00 0.00 0.00 0.00 196.83 9.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4508.41 26-JAN-10:20 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 15.32
February 7097.53 21-FEB-09:50 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 10.39
March 11885.31 26-MAR-09:32 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 0.00 23.24
April 17253.71 16-APR-09:42 391.37 312.41 2933.89 0.00 0.00 0.00 0.00 13.04 0.00
May 17873.96 29-MAY-08:51 456.59 364.48 3422.87 0.00 0.00 0.00 0.00 222.01 0.00
June 15997.03 11-JUN-10:22 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 64.26 0.00
July 16552.48 02-JUL-15:41 587.05 468.62 4400.84 0.00 0.00 0.00 0.00 115.57 0.00
August 16125.85 06-AUG-10:22 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 101.42 0.00
September 11630.22 11-SEP-05:03 521.82 678.09 2607.90 0.00 0.00 0.00 0.00 0.06 0.00
October 13649.40 09-OCT-10:13 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 0.00 0.00
November 6745.81 13-NOV-09:50 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 6.04
December 5008.55 01-DEC-10:00 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 6.72
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4508.41   260.91 208.28 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17873.96   1295.83 937.20 4400.84 0.00 0.00 0.00 0.00 222.01 23.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12576.52 12-JAN-13:40 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 7.07
February 22076.29 20-FEB-14:02 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 0.00 6.79
March 21384.44 12-MAR-12:13 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 16.61 0.00
April 21642.96 16-APR-11:42 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 66.24 0.00
May 20920.49 29-MAY-16:11 1012.19 807.99 7587.84 0.00 0.00 0.00 0.00 195.98 0.00
June 20152.06 11-JUN-16:22 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 110.76 0.00
July 21826.65 02-JUL-16:21 910.97 727.20 6829.06 0.00 0.00 0.00 0.00 171.42 0.00
August 20805.29 06-AUG-15:01 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 175.64 0.00
September 21889.53 24-SEP-13:22 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 123.13 0.00
October 23070.20 09-OCT-12:52 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 13.28 0.00
November 21636.63 19-NOV-12:53 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 0.00 10.94
December 21285.83 03-DEC-12:02 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 0.00 4.02
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12576.52   404.87 323.20 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23070.20   1923.15 1454.32 7587.84 0.00 0.00 0.00 0.00 195.98 10.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7243.53 31-JAN-16:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 8.17
February 20874.59 20-FEB-16:02 326.14 260.35 2444.89 0.00 0.00 0.00 0.00 0.00 7.95
March 19808.32 26-MAR-16:12 326.14 260.35 2444.89 0.00 0.00 0.00 0.00 72.61 0.00
April 22754.91 30-APR-16:21 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 155.31 0.00
May 22379.18 28-MAY-16:21 652.28 520.69 4889.79 0.00 0.00 0.00 0.00 324.90 0.00
June 22436.19 18-JUN-15:52 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 18.29 0.00
July 24575.11 02-JUL-16:21 587.05 468.62 4400.81 0.00 0.00 0.00 0.00 97.32 0.00
August 22365.96 06-AUG-15:41 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 96.25 0.00
September 22119.60 24-SEP-15:22 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 80.21 0.00
October 22262.12 15-OCT-15:22 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 64.48 0.00
November 16368.41 06-NOV-06:03 521.82 678.09 2607.89 0.00 0.00 0.00 0.00 0.00 0.00
December 16473.23 29-DEC-06:03 521.82 678.09 2607.89 0.00 0.00 0.00 0.00 0.00 52.06
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7243.53   326.14 260.35 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24575.11   1239.33 937.20 4889.79 0.00 0.00 0.00 0.00 324.90 52.06



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4060.34 14-JAN-06:02 1012.16 1315.28 5058.48 0.00 0.00 0.00 0.00 0.00 90.04
February 5793.28 24-FEB-15:00 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 24.00 0.00
March 14190.40 11-MAR-06:02 1012.16 1315.28 5058.48 0.00 0.00 0.00 0.00 0.00 3.15
April 15096.75 16-APR-17:12 0.00 484.79 4552.64 0.00 0.00 0.00 0.00 71.66 0.00
May 20757.40 28-MAY-15:31 809.73 646.38 6070.18 0.00 0.00 0.00 0.00 1262.03 0.00
June 19544.74 11-JUN-17:02 0.00 484.79 4552.64 0.00 0.00 0.00 0.00 231.83 0.00
July 19519.38 02-JUL-16:42 607.30 484.79 4552.64 0.00 0.00 0.00 0.00 427.01 0.00
August 16589.55 07-AUG-05:03 1417.03 1841.39 7081.88 0.00 0.00 0.00 0.00 27.56 0.00
September 16677.96 05-SEP-03:02 0.00 657.64 5058.48 0.00 0.00 0.00 0.00 5.59 0.00
October 14472.00 03-OCT-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 0.27
November 6134.11 09-NOV-14:30 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 17.61 0.00
December 4268.30 03-DEC-14:13 404.87 323.19 3035.09 0.00 0.00 0.00 0.00 7.64 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4060.34   0.00 323.19 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20757.40   2010.79 1841.39 7081.88 0.00 0.00 0.00 0.00 1262.03 90.04



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3555.07 08-JAN-13:32 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 0.00 24.30
February 6183.97 22-FEB-10:00 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 12.52
March 12412.53 12-MAR-11:23 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 21.05 0.00
April 18167.11 16-APR-09:12 391.37 312.41 2933.89 0.00 0.00 0.00 0.00 16.09 0.00
May 18541.85 29-MAY-08:51 456.59 364.48 3422.87 0.00 0.00 0.00 0.00 495.29 0.00
June 16682.48 11-JUN-10:22 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 147.67 0.00
July 16519.72 02-JUL-12:02 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 423.74 0.00
August 13720.98 06-AUG-15:31 587.05 468.62 4400.84 0.00 0.00 0.00 0.00 263.55 0.00
September 15032.16 24-SEP-10:13 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 74.13 0.00
October 17084.87 01-OCT-09:52 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 23.42 0.00
November 6180.83 09-NOV-10:00 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.53 0.00
December 4094.76 01-DEC-10:00 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 16.06
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3555.07   260.91 208.28 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18541.85   1239.33 937.20 4400.84 0.00 0.00 0.00 0.00 495.29 24.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19532.51 08-JAN-13:32 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 0.00 113.92
February 21358.36 20-FEB-13:52 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 0.00 17.79
March 21297.94 12-MAR-13:22 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 34.57 0.00
April 20807.26 16-APR-11:52 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 164.33 0.00
May 21077.93 28-MAY-15:31 809.75 646.40 6070.27 0.00 0.00 0.00 0.00 1253.64 0.00
June 18514.64 11-JUN-16:22 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 258.23 0.00
July 19866.79 30-JUL-15:32 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 320.64 0.00
August 20003.02 06-AUG-14:51 809.75 646.40 6070.27 0.00 0.00 0.00 0.00 416.38 0.00
September 20757.08 24-SEP-16:12 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 233.53 0.00
October 22870.36 01-OCT-13:11 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 150.24 0.00
November 21631.53 11-NOV-12:02 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 0.00 2.93
December 20688.27 03-DEC-12:53 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 0.00 17.12
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 18514.64   404.87 323.20 3035.14 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22870.36   809.75 646.40 6070.27 0.00 0.00 0.00 0.00 1253.64 113.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5129.19 31-JAN-16:10 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 20.60
February 7454.26 21-FEB-16:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 18.19 0.00
March 16641.04 12-MAR-16:02 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 87.79 0.00
April 19104.66 30-APR-16:11 652.28 520.69 4889.79 0.00 0.00 0.00 0.00 365.88 0.00
May 20637.36 28-MAY-15:31 521.82 416.55 3911.83 0.00 0.00 0.00 0.00 737.72 0.00
June 18671.21 11-JUN-16:22 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 160.60 0.00
July 18492.31 02-JUL-16:42 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 264.95 0.00
August 18437.69 06-AUG-16:11 587.05 468.62 4400.81 0.00 0.00 0.00 0.00 218.49 0.00
September 18845.57 24-SEP-16:12 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 145.32 0.00
October 18836.35 01-OCT-16:32 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 56.22 0.00
November 8153.10 11-NOV-15:22 326.14 260.35 2444.89 0.00 0.00 0.00 0.00 13.42 0.00
December 5567.63 01-DEC-15:30 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 3.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5129.19   326.14 260.35 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20637.36   1239.33 937.20 4889.79 0.00 0.00 0.00 0.00 737.72 20.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3935.55 26-JAN-15:10 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 32.76
February 5857.82 23-FEB-14:50 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 14.07 0.00
March 13337.96 30-MAR-05:02 1012.16 1315.28 5058.48 0.00 0.00 0.00 0.00 0.00 10.07
April 22585.54 30-APR-16:01 809.73 646.38 6070.18 0.00 0.00 0.00 0.00 785.45 0.00
May 23646.01 28-MAY-16:31 708.51 565.58 5311.41 0.00 0.00 0.00 0.00 1462.40 0.00
June 23411.41 11-JUN-16:22 607.30 484.79 4552.64 0.00 0.00 0.00 0.00 311.27 0.00
July 23774.53 02-JUL-13:12 506.08 403.99 3793.86 0.00 0.00 0.00 0.00 634.05 0.00
August 19555.61 21-AUG-03:02 0.00 657.64 5058.48 0.00 0.00 0.00 0.00 0.00 0.00
September 22757.80 17-SEP-15:22 607.30 484.79 4552.64 0.00 0.00 0.00 0.00 331.47 0.00
October 17338.00 01-OCT-15:21 708.51 565.58 5311.41 0.00 0.00 0.00 0.00 196.62 0.00
November 6498.77 09-NOV-14:50 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 20.29 0.00
December 3904.05 28-DEC-16:30 1923.11 1740.80 2276.32 0.00 0.00 0.00 0.00 0.00 3.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3904.05   0.00 403.99 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23774.53   2010.79 1740.80 6070.18 0.00 0.00 0.00 0.00 1462.40 32.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3123.41 26-JAN-14:50 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 22.92
February 5712.13 23-FEB-10:40 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 6.55
March 10150.85 30-MAR-05:02 652.28 847.62 3259.88 0.00 0.00 0.00 0.00 0.00 6.76
April 19303.45 30-APR-10:02 391.37 312.41 2933.89 0.00 0.00 0.00 0.00 94.15 0.00
May 18767.72 29-MAY-09:42 391.37 312.41 2933.89 0.00 0.00 0.00 0.00 795.92 0.00
June 18001.42 11-JUN-10:22 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 179.11 0.00
July 18647.13 02-JUL-09:12 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 369.26 0.00
August 14173.33 06-AUG-15:12 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 332.47 0.00
September 17654.60 17-SEP-15:22 391.37 312.41 2933.89 0.00 0.00 0.00 0.00 211.22 0.00
October 18087.22 01-OCT-10:42 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 68.19 0.00
November 5822.99 09-NOV-10:30 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 2.57 0.00
December 3136.89 01-DEC-15:10 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 3.19
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3123.41   326.14 260.35 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19303.45   1295.83 937.20 3259.88 0.00 0.00 0.00 0.00 795.92 22.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12079.49 12-JAN-14:20 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 16.02
February 23757.35 20-FEB-13:32 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 0.00 19.54
March 23817.90 12-MAR-12:13 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 45.02 0.00
April 24374.25 30-APR-13:22 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 604.08 0.00
May 23759.38 28-MAY-15:51 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 1571.95 0.00
June 23354.92 11-JUN-16:22 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 312.52 0.00
July 24004.33 02-JUL-13:12 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 627.82 0.00
August 21165.32 06-AUG-15:12 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 499.23 0.00
September 24663.08 17-SEP-15:22 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 279.51 0.00
October 26297.07 01-OCT-15:21 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 148.10 0.00
November 25516.90 12-NOV-13:42 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 0.00 19.25
December 13620.39 01-DEC-13:50 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 4.39
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12079.49   404.87 323.20 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26297.07   2010.83 1454.32 5311.49 0.00 0.00 0.00 0.00 1571.95 19.54



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4618.69 31-JAN-16:10 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 26.46
February 7456.53 21-FEB-16:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 21.35 0.00
March 15940.38 12-MAR-16:12 326.14 260.35 2444.89 0.00 0.00 0.00 0.00 109.60 0.00
April 21431.11 30-APR-16:01 521.82 416.55 3911.83 0.00 0.00 0.00 0.00 449.43 0.00
May 21894.48 28-MAY-16:31 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 893.41 0.00
June 21419.54 11-JUN-16:22 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 194.54 0.00
July 21663.92 02-JUL-16:31 521.82 416.55 3911.83 0.00 0.00 0.00 0.00 311.27 0.00
August 20156.40 06-AUG-16:32 326.14 260.35 2444.89 0.00 0.00 0.00 0.00 268.27 0.00
September 21246.26 17-SEP-16:02 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 141.91 0.00
October 21833.44 01-OCT-15:21 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 104.95 0.00
November 8263.12 08-NOV-15:30 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 11.46 0.00
December 5237.79 28-DEC-15:40 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 1.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4618.69   326.14 260.35 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21894.48   1239.33 937.20 3911.83 0.00 0.00 0.00 0.00 893.41 26.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8730.68 02-JAN-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 11725.83 21-FEB-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.15
March 11356.57 06-MAR-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.66
April 17284.87 17-APR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.16
May 17187.45 01-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 55.89 0.00
June 17622.67 12-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.72 0.00
July 19320.30 03-JUL-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75.88 0.00
August 18127.66 07-AUG-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.59 0.00
September 15021.85 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.42 0.00
October 14093.22 10-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 12959.81 13-NOV-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.06
December 10585.62 26-DEC-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 8730.68   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19320.30   0.00 0.00 0.00 0.00 0.00 0.00 0.00 75.88 24.06



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5083.61 21-JAN-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 6836.17 23-FEB-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.03
March 7962.68 15-MAR-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85.37
April 9651.62 21-APR-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45.49 0.00
May 11915.05 31-MAY-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 149.96 0.00
June 11252.69 09-JUN-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65.02 0.00
July 14378.42 05-JUL-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 92.98 0.00
August 11853.16 08-AUG-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67.71 0.00
September 12616.52 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.03 0.00
October 9259.85 20-OCT-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.11
November 8965.11 13-NOV-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42.51
December 5446.69 02-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.96
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5083.61   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14378.42   0.00 0.00 0.00 0.00 0.00 0.00 0.00 149.96 85.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7274.40 12-JAN-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47.76
February 13930.36 22-FEB-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.17 0.00
March 21896.13 28-MAR-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 26854.17 26-APR-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 113.78 0.00
May 30383.45 01-MAY-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 336.26 0.00
June 31890.04 12-JUN-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 368.39 0.00
July 28449.61 07-JUL-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 254.56 0.00
August 25400.53 07-AUG-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 243.08 0.00
September 22285.97 26-SEP-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 107.82 0.00
October 21182.08 02-OCT-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 128.72 0.00
November 14879.60 09-NOV-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.14 0.00
December 8626.81 01-DEC-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.35
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 7274.40   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31890.04   0.00 0.00 0.00 0.00 0.00 0.00 0.00 368.39 47.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1950.12 30-JAN-17:00 222.14 520.85 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3916.24 21-FEB-17:00 222.14 520.85 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 7207.09 31-MAR-23:55 0.00 57.88 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
April 7756.45 16-APR-22:35 0.00 115.75 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
May 3509.96 31-MAY-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5382.56 30-JUN-23:57 0.00 86.81 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 7269.26 31-JUL-23:57 0.00 115.75 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7616.83 16-AUG-09:40 232.27 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3506.22 30-SEP-23:47 0.00 86.81 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
October 5408.90 31-OCT-24:00 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5828.83 13-NOV-16:30 222.14 520.85 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7687.46 28-DEC-17:00 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1950.12   0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7756.45   232.27 520.85 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1787.32 12-JAN-17:00 222.14 520.85 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3680.77 21-FEB-17:00 222.14 520.85 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6965.49 31-MAR-23:55 0.00 57.88 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
April 7338.16 12-APR-16:00 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3382.31 31-MAY-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5209.02 30-JUN-23:42 0.00 144.69 29229.08 0.00 0.00 0.00 0.00 0.00 0.00
July 6987.17 31-JUL-24:00 0.00 115.75 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7182.48 16-AUG-10:50 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3402.17 30-SEP-23:47 0.00 86.81 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
October 5089.52 31-OCT-24:00 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5502.47 08-NOV-16:40 222.14 520.85 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7247.83 01-DEC-17:00 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1787.32   0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7338.16   222.14 520.85 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1790.41 12-JAN-17:00 222.14 520.85 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3710.93 22-FEB-17:00 222.14 520.85 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6911.88 31-MAR-23:55 0.00 57.88 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
April 7487.94 16-APR-20:52 0.00 144.69 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
May 3354.11 31-MAY-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5249.71 30-JUN-23:57 0.00 86.81 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 7042.96 31-JUL-23:57 0.00 115.75 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7296.57 20-AUG-16:22 58.46 144.69 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
September 3382.09 30-SEP-23:34 0.00 144.69 19486.06 0.00 0.00 0.00 0.00 0.00 0.00
October 4940.77 31-OCT-24:00 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5557.69 08-NOV-16:30 222.14 520.85 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7241.78 28-DEC-17:00 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1790.41   0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7487.94   222.14 520.85 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 93285.70 26-JAN-17:00 4808.68 5919.59 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 184671.54 21-FEB-17:00 4808.68 5919.59 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 359056.19 31-MAR-23:55 0.00 657.76 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
April 368482.41 30-APR-04:25 0.00 657.76 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
May 176395.08 31-MAY-24:00 0.00 328.88 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 268595.66 30-JUN-24:00 0.00 986.65 854173.17 0.00 0.00 0.00 0.00 0.00 0.00
July 356264.77 31-JUL-23:23 0.00 986.65 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
August 370180.76 15-AUG-23:42 0.00 1644.41 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
September 177656.23 30-SEP-23:53 0.00 1315.53 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
October 269769.60 31-OCT-24:00 0.00 328.88 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 277921.28 13-NOV-17:00 4808.68 5919.59 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 369279.31 04-DEC-17:00 4808.68 5919.59 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 93285.70   0.00 328.88 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 370180.76   4808.68 5919.59 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.188259E+13 1239063.77 12-JAN-16:40 0.684854E+11 229119.80 02-JAN-06:19
February 0.214632E+13 1417125.51 28-FEB-16:49 0.505675E+11 120959.28 11-FEB-06:10
March 0.297401E+13 1821714.73 13-MAR-15:00 0.533281E+11 70167.58 06-MAR-12:00
April 0.345631E+13 2056558.06 18-APR-15:09 0.459330E+11 65830.89 04-APR-11:20
May 0.250998E+13 1623426.74 09-MAY-15:00 0.447756E+11 60223.49 01-MAY-11:39
June 0.297248E+13 1866585.05 22-JUN-15:09 0.410898E+11 53095.15 01-JUN-11:20
July 0.350314E+13 2028655.29 05-JUL-15:00 0.392825E+11 47728.87 03-JUL-11:30
August 0.395827E+13 2158800.56 07-AUG-15:20 0.423317E+11 52099.36 31-AUG-11:00
September 0.237849E+13 1645849.57 14-SEP-15:20 0.418917E+11 58215.59 27-SEP-11:39
October 0.263762E+13 1664821.09 03-OCT-15:00 0.467954E+11 65535.49 31-OCT-11:00
November 0.278181E+13 1694780.59 01-NOV-15:20 0.493766E+11 69832.76 29-NOV-12:39
December 0.314776E+13 1713651.65 28-DEC-16:00 0.577241E+11 166303.50 21-DEC-06:10
             
Annual Sum or Average 0.343488E+14     0.581581E+12    
Minimum of Months 0.188259E+13 1239063.77   0.392825E+11 47728.87  
Maximum of Months 0.395827E+13 2158800.56   0.684854E+11 229119.80  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.311083E+12 0.665010E+11 0.811612E+12 0.164870E+12 0.185224E+12 0.736513E+11 0.00 0.190855E+12 0.667904E+11 0.120010E+11 0.00 0.00 0.00
February 0.281284E+12 0.569578E+11 0.102011E+13 0.148925E+12 0.178861E+12 0.723554E+11 0.00 0.272619E+12 0.102125E+12 0.130839E+11 0.00 0.00 0.00
March 0.332677E+12 0.580246E+11 0.146267E+13 0.165150E+12 0.228734E+12 0.979183E+11 0.00 0.480948E+12 0.141142E+12 0.674613E+10 0.00 0.00 0.00
April 0.296610E+12 0.512248E+11 0.170311E+13 0.159525E+12 0.248770E+12 0.122444E+12 0.00 0.714617E+12 0.159080E+12 0.935151E+09 0.00 0.00 0.00
May 0.319396E+12 0.486028E+11 0.820521E+12 0.165009E+12 0.271283E+12 0.134250E+12 0.00 0.547620E+12 0.203280E+12 16492772.22 0.00 0.00 0.00
June 0.317786E+12 0.447045E+11 0.110677E+13 0.159787E+12 0.267376E+12 0.135422E+12 0.00 0.725974E+12 0.214653E+12 0.00 0.00 0.00 0.00
July 0.298190E+12 0.474617E+11 0.143888E+13 0.164746E+12 0.259328E+12 0.147651E+12 0.00 0.913289E+12 0.233593E+12 0.00 0.00 0.00 0.00
August 0.332326E+12 0.509501E+11 0.177780E+13 0.165150E+12 0.267601E+12 0.149010E+12 0.00 0.983870E+12 0.231562E+12 0.00 0.00 0.00 0.00
September 0.297496E+12 0.540285E+11 0.784732E+12 0.159523E+12 0.237564E+12 0.120858E+12 0.00 0.517138E+12 0.207147E+12 0.00 0.00 0.00 0.00
October 0.309783E+12 0.609588E+11 0.112899E+13 0.164870E+12 0.228723E+12 0.108924E+12 0.00 0.470735E+12 0.163316E+12 0.131635E+10 0.00 0.00 0.00
November 0.307239E+12 0.632547E+11 0.140306E+13 0.159632E+12 0.203384E+12 0.871684E+11 0.00 0.415502E+12 0.128936E+12 0.136297E+11 0.00 0.00 0.00
December 0.301526E+12 0.680333E+11 0.175516E+13 0.164746E+12 0.191649E+12 0.798765E+11 0.00 0.429621E+12 0.122706E+12 0.344439E+11 0.00 0.00 0.00
                           
Annual Sum or Average 0.370540E+13 0.670702E+12 0.152134E+14 0.194193E+13 0.276850E+13 0.132953E+13 0.00 0.666279E+13 0.197433E+13 0.821727E+11 0.00 0.00 0.00
Minimum of Months 0.281284E+12 0.447045E+11 0.784732E+12 0.148925E+12 0.178861E+12 0.723554E+11 0.00 0.190855E+12 0.667904E+11 0.00 0.00 0.00 0.00
Maximum of Months 0.332677E+12 0.680333E+11 0.177780E+13 0.165150E+12 0.271283E+12 0.149010E+12 0.00 0.983870E+12 0.233593E+12 0.344439E+11 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.142735E+11 0.00 0.542120E+11 0.00 0.00
February 0.00 0.00 0.211367E+10 0.00 0.484538E+11 0.00 0.00
March 0.00 0.00 3045324.56 0.00 0.533250E+11 0.00 0.00
April 0.00 0.00 0.00 0.00 0.459330E+11 0.00 0.00
May 0.00 0.00 0.00 0.00 0.447756E+11 0.00 0.00
June 0.00 0.00 0.00 0.00 0.410898E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.392825E+11 0.00 0.00
August 0.00 0.00 0.00 0.00 0.423317E+11 0.00 0.00
September 0.00 0.00 0.00 0.00 0.418917E+11 0.00 0.00
October 0.00 0.00 0.00 0.00 0.467954E+11 0.00 0.00
November 0.00 0.00 0.152325E+09 0.00 0.492243E+11 0.00 0.00
December 0.00 0.00 0.547094E+10 0.00 0.522531E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.220134E+11 0.00 0.559568E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.392825E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.142735E+11 0.00 0.542120E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 339503.01 18-JAN-08:09 54335.80 01-JAN-06:10 439129.89 02-JAN-08:09 118948.06 18-JAN-08:20 126883.81 12-JAN-14:00 67731.31 12-JAN-14:50 0.00 01-JAN-00:10
February 338358.91 10-FEB-08:09 54335.80 01-FEB-06:10 557421.28 01-FEB-08:09 118947.11 10-FEB-08:20 161821.43 22-FEB-15:50 68195.95 17-FEB-11:00 0.00 01-FEB-00:10
March 339293.08 14-MAR-07:10 54335.80 01-MAR-06:10 675712.68 01-MAR-08:09 118947.89 14-MAR-07:19 199432.64 13-MAR-15:00 68785.43 28-MAR-13:00 0.00 01-MAR-00:10
April 319549.97 03-APR-07:10 54335.80 01-APR-05:10 794004.08 03-APR-07:10 118931.42 03-APR-07:19 218529.07 17-APR-15:09 70907.26 10-APR-14:09 0.00 01-APR-00:10
May 326362.57 24-MAY-07:10 54335.80 01-MAY-05:10 439129.89 01-MAY-07:10 118937.10 24-MAY-07:19 237009.98 03-MAY-14:09 70317.99 03-MAY-15:50 0.00 01-MAY-00:10
June 326379.08 23-JUN-07:10 54335.80 01-JUN-05:10 557421.28 01-JUN-07:10 118937.11 23-JUN-07:19 245998.42 06-JUN-13:00 70634.16 09-JUN-15:00 0.00 01-JUN-00:10
July 337908.04 26-JUL-07:10 54335.80 01-JUL-05:10 675712.68 03-JUL-07:10 118946.73 26-JUL-07:19 239344.97 05-JUL-15:20 71599.91 31-JUL-05:10 0.00 01-JUL-00:10
August 339585.16 16-AUG-07:10 54335.80 01-AUG-05:10 794004.08 01-AUG-07:10 118948.13 16-AUG-07:19 226054.35 07-AUG-15:20 71743.86 28-AUG-05:10 0.00 01-AUG-00:10
September 341258.41 08-SEP-07:10 54335.80 01-SEP-05:10 439129.89 01-SEP-07:10 118949.53 08-SEP-07:19 213932.08 25-SEP-15:50 69814.91 28-SEP-14:09 0.00 01-SEP-00:10
October 344557.66 11-OCT-07:10 54335.80 01-OCT-05:10 557421.28 02-OCT-07:10 118952.28 11-OCT-07:19 194325.92 04-OCT-15:00 69834.51 04-OCT-12:20 0.00 01-OCT-00:10
November 340730.57 27-NOV-16:00 54335.80 01-NOV-05:10 675712.68 01-NOV-07:10 118939.87 03-NOV-07:19 167227.66 09-NOV-15:00 69321.28 13-NOV-14:09 0.00 01-NOV-00:10
December 342690.94 29-DEC-16:00 54335.80 01-DEC-06:10 794004.08 01-DEC-08:09 118936.85 29-DEC-08:20 139614.13 01-DEC-15:30 68447.74 04-DEC-13:39 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 319549.97   54335.80   439129.89   118931.42   126883.81   67731.31   0.00  
Maximum of Months 344557.66   54335.80   794004.08   118952.28   245998.42   71743.86   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 156247.97 25-JAN-15:09 50613.09 25-JAN-14:00 7523.25 21-JAN-17:40 0.00 0.00 0.00
February 203132.86 07-FEB-15:20 53243.76 24-FEB-16:19 11145.70 04-FEB-05:00 0.00 0.00 0.00
March 395490.04 28-MAR-13:00 93058.23 06-MAR-14:39 13979.04 01-MAR-05:00 0.00 0.00 0.00
April 496677.85 18-APR-15:39 93058.23 03-APR-09:09 7548.28 11-APR-04:00 0.00 0.00 0.00
May 429935.06 17-MAY-15:30 93058.23 01-MAY-07:10 2126.21 28-MAY-14:00 0.00 0.00 0.00
June 540360.71 22-JUN-15:50 93058.23 01-JUN-05:40 0.00 01-JUN-00:10 0.00 0.00 0.00
July 551148.18 10-JUL-13:00 93058.23 01-JUL-06:30 0.00 01-JUL-00:10 0.00 0.00 0.00
August 583147.84 28-AUG-14:50 93058.23 01-AUG-00:40 0.00 01-AUG-00:10 0.00 0.00 0.00
September 440548.62 14-SEP-15:30 93058.23 01-SEP-00:40 0.00 01-SEP-00:10 0.00 0.00 0.00
October 398667.54 04-OCT-12:20 93058.23 02-OCT-08:20 7216.98 31-OCT-04:00 0.00 0.00 0.00
November 372232.55 06-NOV-13:09 93058.23 06-NOV-11:20 15187.16 30-NOV-22:00 0.00 0.00 0.00
December 262980.62 01-DEC-15:20 50859.45 27-DEC-13:50 28596.21 22-DEC-05:00 0.00 0.00 0.00
                   
Annual Sum or Average             0.00 0.00 0.00
Minimum of Months 156247.97   50613.09   0.00   0.00 0.00 0.00
Maximum of Months 583147.84   93058.23   28596.21   0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1239063.77 12-JAN-16:40 322304.13 439129.89 0.00 84888.71 120387.65 67505.23 0.00 154560.89 50287.27
February 1417125.51 28-FEB-16:49 316816.17 557421.28 0.00 84885.75 138493.24 67478.06 0.00 200954.17 51076.84
March 1821714.73 13-MAR-15:00 316816.17 675712.68 0.00 84885.75 199432.64 68200.58 0.00 383608.68 93058.23
April 2056558.06 18-APR-15:09 316816.17 794004.08 0.00 84885.75 205424.27 68983.83 0.00 493385.74 93058.23
May 1623426.74 09-MAY-15:00 316816.17 439129.89 0.00 84885.75 216886.69 69201.83 0.00 403448.18 93058.23
June 1866585.05 22-JUN-15:09 316816.17 557421.28 0.00 84885.75 210780.62 70265.64 0.00 533357.37 93058.23
July 2028655.29 05-JUL-15:00 316816.17 675712.68 0.00 84885.75 237193.79 69934.88 0.00 551053.79 93058.23
August 2158800.56 07-AUG-15:20 316816.17 794004.08 0.00 84885.75 226054.35 69995.90 0.00 573986.09 93058.23
September 1645849.57 14-SEP-15:20 316816.17 439129.89 0.00 84885.75 202167.15 69681.05 0.00 440111.34 93058.23
October 1664821.09 03-OCT-15:00 316816.17 557421.28 0.00 84885.75 177434.00 68443.63 0.00 366762.03 93058.23
November 1694780.59 01-NOV-15:20 316816.17 675712.68 0.00 84885.75 142547.15 68781.27 0.00 353065.05 52972.53
December 1713651.65 28-DEC-16:00 327070.15 794004.08 0.00 84892.76 126707.76 67434.74 0.00 262916.00 50626.16
                       
Annual Sum or Average                      
Minimum of Months 1239063.77   316816.17 439129.89 0.00 84885.75 120387.65 67434.74 0.00 154560.89 50287.27
Maximum of Months 2158800.56   327070.15 794004.08 0.00 84892.76 237193.79 70265.64 0.00 573986.09 93058.23



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 207455.14 02-JAN-06:19 0.00 72853.16 23-JAN-12:50 0.00
February 0.00 0.00 94402.55 11-FEB-06:10 0.00 72391.72 07-FEB-12:39 0.00
March 0.00 0.00 1016.70 01-MAR-06:49 0.00 70167.58 06-MAR-12:00 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 65830.89 04-APR-11:20 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 60223.49 01-MAY-11:39 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 53095.15 01-JUN-11:20 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 47728.87 03-JUL-11:30 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 52099.36 31-AUG-11:00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 58215.59 27-SEP-11:39 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 65535.49 31-OCT-11:00 0.00
November 0.00 0.00 7514.73 27-NOV-06:00 0.00 69832.76 29-NOV-12:39 0.00
December 0.00 0.00 142653.91 21-DEC-06:10 0.00 72354.25 27-DEC-12:39 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 47728.87   0.00
Maximum of Months 0.00 0.00 207455.14   0.00 72853.16   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 10.17 26.87 2.83 26.97
February 0.00 0.00 0.00 0.00 5.67 26.56 0.33 26.52
March 0.00 0.00 0.00 0.00 3.17 26.00 0.00 26.00
April 0.00 0.00 0.00 0.00 4.33 25.95 0.17 25.90
May 0.00 0.00 0.00 0.00 5.17 26.09 0.00 26.09
June 0.00 0.00 0.00 0.00 5.67 25.92 0.00 25.92
July 0.00 0.00 0.00 0.00 9.83 25.85 0.83 25.89
August 0.00 0.00 0.00 0.00 11.00 25.94 1.33 26.02
September 0.00 0.00 0.00 0.00 11.00 26.04 0.33 26.04
October 0.00 0.00 0.00 0.00 10.67 26.06 0.33 26.11
November 0.00 0.00 0.00 0.00 13.17 26.25 1.17 26.28
December 0.00 0.00 0.00 0.00 10.67 26.30 0.67 26.32
                 
Annual Sum or Average 0.00   0.00   100.50 26.17 8.00 26.22
Minimum of Months 0.00 0.00 0.00 0.00 3.17 25.85 0.00 25.89
Maximum of Months 0.00 0.00 0.00 0.00 13.17 26.87 2.83 26.97



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.50 25.58 0.00 25.58
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 25.69 0.00 25.69
May 0.00 0.00 0.00 0.00 0.67 25.62 0.00 25.62
June 0.00 0.00 0.00 0.00 0.17 25.58 0.00 25.58
July 0.00 0.00 0.00 0.00 1.17 25.63 0.00 25.63
August 0.00 0.00 0.00 0.00 1.83 25.69 0.00 25.69
September 0.00 0.00 0.00 0.00 0.50 25.65 0.00 25.65
October 0.00 0.00 0.00 0.00 0.67 25.62 0.00 25.62
November 0.00 0.00 0.00 0.00 1.67 25.61 0.00 25.61
December 0.00 0.00 0.00 0.00 1.17 25.63 0.00 25.63
                 
Annual Sum or Average 0.00   0.00   8.67 25.64 0.00 25.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.83 25.69 0.00 25.69



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 25.57 0.00 25.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.21 0.00 19.21 0.00 19.21 0.00 19.21
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
July 0.00 0.00 0.00 0.00 0.33 25.58 0.00 25.58
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.17 25.59 0.00 25.59
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 19.21 0.00 19.21 0.67 24.30 0.00 24.30
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.21 0.00 19.21 0.33 25.59 0.00 25.59



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.50 26.65 0.83 26.92
May 0.00 0.00 0.00 0.00 6.33 26.95 3.17 27.13
June 0.00 0.00 0.00 0.00 5.00 26.79 1.67 26.97
July 0.00 0.00 0.00 0.00 9.50 26.94 3.83 27.10
August 0.00 0.00 0.00 0.00 7.67 26.57 3.00 26.81
September 0.00 0.00 0.00 0.00 0.50 25.67 0.00 25.67
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   30.50 26.79 12.50 26.99
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.50 26.95 3.83 27.13



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 27.34 0.17 27.34
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 4.83 27.70 4.83 27.70
May 0.00 0.00 0.00 0.00 10.83 27.69 8.17 27.82
June 0.00 0.00 0.00 0.00 4.83 27.13 2.83 27.36
July 0.00 0.00 0.00 0.00 8.17 27.31 5.17 27.47
August 0.00 0.00 0.00 0.00 2.67 26.95 1.83 27.17
September 0.00 0.00 0.00 0.00 0.67 27.34 0.67 27.34
October 0.00 0.00 0.00 0.00 1.33 27.55 1.33 27.55
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   33.50 27.44 25.00 27.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 10.83 27.70 8.17 27.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.33 27.30 0.33 27.30
February 0.00 0.00 0.00 0.00 3.33 27.74 3.33 27.74
March 0.00 0.00 0.00 0.00 4.17 27.70 4.17 27.70
April 0.00 0.00 0.00 0.00 7.50 27.32 4.83 27.52
May 0.00 0.00 0.00 0.00 8.50 27.06 4.33 27.27
June 0.00 0.00 0.00 0.00 5.17 26.85 2.17 27.05
July 0.00 0.00 0.00 0.00 11.33 27.00 5.50 27.17
August 0.00 0.00 0.00 0.00 9.67 26.89 4.67 27.14
September 0.00 0.00 0.00 0.00 4.33 27.25 3.00 27.48
October 0.00 0.00 0.00 0.00 11.67 27.95 10.67 28.00
November 0.00 0.00 0.00 0.00 8.83 27.92 8.83 27.92
December 0.00 0.00 0.00 0.00 3.33 27.60 3.33 27.60
                 
Annual Sum or Average 0.00   0.00   78.17 27.37 55.17 27.54
Minimum of Months 0.00 0.00 0.00 0.00 0.33 26.85 0.33 27.05
Maximum of Months 0.00 0.00 0.00 0.00 11.67 27.95 10.67 28.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.17 27.62 1.17 27.62
March 0.00 0.00 0.00 0.00 10.50 27.30 4.33 27.49
April 0.00 0.00 0.00 0.00 47.17 27.58 12.50 27.70
May 0.00 0.00 0.00 0.00 18.67 27.39 5.67 27.64
June 0.00 0.00 0.00 0.00 24.33 27.22 5.33 27.41
July 0.00 0.00 0.00 0.00 35.83 27.46 11.83 27.61
August 0.00 0.00 0.00 0.00 55.17 27.61 14.17 27.68
September 0.00 0.00 0.00 0.00 10.67 27.18 3.50 27.32
October 0.00 0.00 0.00 0.00 13.83 27.43 6.50 27.61
November 0.00 0.00 0.00 0.00 4.83 27.64 3.83 27.69
December 0.00 0.00 0.00 0.00 1.67 27.37 1.33 27.37
                 
Annual Sum or Average 0.00   0.00   223.83 27.47 70.17 27.61
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 55.17 27.64 14.17 27.70



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 7.33 27.12 4.00 27.29
June 0.00 0.00 0.00 0.00 5.83 26.60 1.67 26.80
July 0.00 0.00 0.00 0.00 7.67 26.70 2.67 26.90
August 0.00 0.00 0.00 0.00 1.33 25.62 0.00 25.62
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   22.17 26.75 8.33 26.96
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.67 27.12 4.00 27.29



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.67 27.44 0.67 27.44
April 0.00 0.00 0.00 0.00 6.33 27.86 5.83 27.88
May 0.00 0.00 0.00 0.00 11.83 27.77 8.50 27.94
June 0.00 0.00 0.00 0.00 7.00 27.19 4.17 27.41
July 0.00 0.00 0.00 0.00 8.33 27.51 5.67 27.66
August 0.00 0.00 0.00 0.00 2.17 27.58 2.17 27.58
September 0.00 0.00 0.00 0.00 1.33 27.45 1.33 27.45
October 0.00 0.00 0.00 0.00 2.67 27.55 2.67 27.55
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   40.33 27.59 31.00 27.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 11.83 27.86 8.50 27.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.50 27.41 0.50 27.41
February 0.00 0.00 0.00 0.00 3.33 27.76 3.33 27.76
March 0.00 0.00 0.00 0.00 4.00 27.73 3.83 27.74
April 0.00 0.00 0.00 0.00 5.50 27.61 4.33 27.68
May 0.00 0.00 0.00 0.00 8.33 27.18 4.67 27.38
June 0.00 0.00 0.00 0.00 5.83 26.57 2.00 26.80
July 0.00 0.00 0.00 0.00 9.17 26.81 4.33 27.01
August 0.00 0.00 0.00 0.00 5.67 26.77 3.33 27.03
September 0.00 0.00 0.00 0.00 4.50 27.31 3.17 27.52
October 0.00 0.00 0.00 0.00 12.00 28.04 10.67 28.09
November 0.00 0.00 0.00 0.00 9.17 27.92 9.17 27.92
December 0.00 0.00 0.00 0.00 2.33 27.60 2.33 27.60
                 
Annual Sum or Average 0.00   0.00   70.33 27.41 51.67 27.57
Minimum of Months 0.00 0.00 0.00 0.00 0.50 26.57 0.50 26.80
Maximum of Months 0.00 0.00 0.00 0.00 12.00 28.04 10.67 28.09



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 1.67 27.75 1.00 27.79
April 0.00 0.00 0.00 0.00 8.67 27.65 4.50 27.81
May 0.00 0.00 0.00 0.00 14.83 27.65 5.83 27.88
June 0.00 0.00 0.00 0.00 13.17 27.28 4.17 27.49
July 0.00 0.00 0.00 0.00 14.00 27.43 5.00 27.61
August 0.00 0.00 0.00 0.00 7.33 27.04 2.83 27.30
September 0.00 0.00 0.00 0.00 2.67 27.84 1.67 27.95
October 0.00 0.00 0.00 0.00 4.17 27.85 3.83 27.86
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   66.50 27.49 28.83 27.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 14.83 27.85 5.83 27.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 18.47 0.00 18.47 0.00 18.47 0.00 18.47
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.67 27.57 1.83 27.59
May 0.00 0.00 0.00 0.00 12.17 27.45 6.33 27.59
June 0.00 0.00 0.00 0.00 9.67 27.01 3.00 27.23
July 0.00 0.00 0.00 0.00 15.67 27.32 6.50 27.45
August 0.00 0.00 0.00 0.00 5.83 26.99 3.00 27.18
September 0.00 0.00 0.00 0.00 0.50 27.30 0.50 27.30
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 18.47 0.00 18.47 46.50 27.20 21.17 27.37
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 18.47 0.00 18.47 15.67 27.57 6.50 27.59



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 18.56 0.00 18.56 0.00 18.56 0.00 18.56
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 27.44 0.50 27.44
April 0.00 0.00 0.00 0.00 8.67 28.00 7.00 28.02
May 0.00 0.00 0.00 0.00 18.33 27.86 10.83 28.03
June 0.00 0.00 0.00 0.00 11.17 27.28 4.67 27.54
July 0.00 0.00 0.00 0.00 17.50 27.62 9.50 27.76
August 0.00 0.00 0.00 0.00 7.67 27.50 5.50 27.60
September 0.00 0.00 0.00 0.00 4.17 27.65 3.83 27.66
October 0.00 0.00 0.00 0.00 3.00 27.57 3.00 27.57
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 18.56 0.00 18.56 71.00 27.62 44.83 27.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 18.56 0.00 18.56 18.33 28.00 10.83 28.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 18.91 0.00 18.91 0.00 18.91 0.00 18.91
February 0.00 0.00 0.00 0.00 1.83 27.71 1.83 27.71
March 0.00 0.00 0.00 0.00 3.83 27.84 3.50 27.85
April 0.00 0.00 0.00 0.00 6.83 27.91 4.67 27.97
May 0.00 0.00 0.00 0.00 14.17 27.48 7.50 27.63
June 0.00 0.00 0.00 0.00 9.50 26.99 3.00 27.22
July 0.00 0.00 0.00 0.00 16.00 27.33 7.00 27.47
August 0.00 0.00 0.00 0.00 7.83 27.17 4.00 27.39
September 0.00 0.00 0.00 0.00 5.17 27.68 3.17 27.84
October 0.00 0.00 0.00 0.00 12.00 28.19 10.33 28.23
November 0.00 0.00 0.00 0.00 6.83 27.92 6.83 27.92
December 0.00 0.00 0.00 0.00 0.17 27.28 0.17 27.28
                 
Annual Sum or Average 0.33 18.91 0.00 18.91 84.17 27.54 52.00 27.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.91 0.00 18.91
Maximum of Months 0.33 18.91 0.00 18.91 16.00 28.19 10.33 28.23



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 18.94 0.00 18.94 0.00 18.94 0.00 18.94
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 1.83 27.86 1.17 27.91
April 0.00 0.00 0.00 0.00 10.17 27.89 4.83 28.04
May 0.00 0.00 0.00 0.00 20.50 27.79 7.33 28.00
June 0.00 0.00 0.00 0.00 18.17 27.42 5.17 27.64
July 0.00 0.00 0.00 0.00 18.17 27.69 6.67 27.84
August 0.00 0.00 0.00 0.00 9.00 27.38 3.17 27.61
September 0.00 0.00 0.00 0.00 3.67 27.96 2.17 28.05
October 0.00 0.00 0.00 0.00 4.67 28.01 4.00 28.03
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 18.94 0.00 18.94 86.17 27.65 34.50 27.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 18.94 0.00 18.94 20.50 28.01 7.33 28.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 154.00 28.23 137.50 28.23
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 391.00 28.24 312.00 28.25
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   545.00 28.24 449.50 28.25
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 391.00 28.24 312.00 28.25



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 140.00 28.17 129.00 28.17
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 311.00 28.14 270.67 28.15
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   451.00 28.15 399.67 28.16
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 311.00 28.17 270.67 28.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 104.33 28.18 94.00 28.17
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 204.67 28.13 183.50 28.12
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   309.00 28.14 277.50 28.14
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 204.67 28.18 183.50 28.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 538.00 29.49 405.50 29.60
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.00 28.31 0.00 28.31
August 0.00 0.00 0.00 0.00 743.17 30.22 514.00 30.30
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1282.17 29.91 919.50 30.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 743.17 30.22 514.00 30.30



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.83 27.26 323.33 24.90 1.83 24.92
February 12.00 26.81 365.50 24.75 12.00 24.81
March 34.33 25.14 446.33 24.56 34.33 24.60
April 31.00 24.23 422.83 24.60 31.00 24.57
May 284.33 24.49 494.33 24.52 284.33 24.51
June 335.00 24.59 496.00 24.54 335.00 24.55
July 297.67 25.09 497.00 24.81 297.67 24.89
August 264.50 24.99 514.00 24.67 264.50 24.75
September 279.50 25.02 485.00 24.74 279.50 24.82
October 105.83 25.13 502.00 24.72 105.83 24.78
November 0.50 27.41 470.00 24.67 0.50 24.67
December 0.00 0.00 389.83 24.79 0.00 24.79
             
Annual Sum or Average 1646.50 24.86 5406.17 24.68 1646.50 24.71
Minimum of Months 0.00 0.00 323.33 24.52 0.00 24.51
Maximum of Months 335.00 27.41 514.00 24.90 335.00 24.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 18.83 25.74 298.33 24.77 12.33 24.84
February 1.17 25.41 372.33 24.44 0.67 24.44
March 0.00 0.00 467.50 24.30 0.00 24.30
April 0.00 0.00 450.33 24.22 0.00 24.22
May 0.00 0.00 494.33 24.21 0.00 24.21
June 0.00 0.00 496.00 24.19 0.00 24.19
July 0.00 0.00 497.00 24.23 0.00 24.23
August 0.00 0.00 514.00 24.20 0.00 24.20
September 0.00 0.00 485.00 24.30 0.00 24.30
October 0.00 0.00 502.00 24.35 0.00 24.35
November 0.00 0.00 470.17 24.42 0.00 24.42
December 0.33 23.96 388.00 24.53 0.00 24.53
             
Annual Sum or Average 20.33 25.69 5435.00 24.33 13.00 24.33
Minimum of Months 0.00 0.00 298.33 24.19 0.00 24.19
Maximum of Months 18.83 25.74 514.00 24.77 12.33 24.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 118.17 23.65 160.00 24.11 13.17 24.13
February 55.33 23.85 274.33 24.24 7.83 24.28
March 6.17 23.68 415.67 24.25 0.17 24.25
April 2.50 23.84 400.83 24.22 0.00 24.22
May 0.00 0.00 483.67 24.14 0.00 24.14
June 0.00 0.00 496.00 24.15 0.00 24.15
July 0.00 0.00 497.00 24.18 0.00 24.18
August 0.00 0.00 514.00 24.19 0.00 24.19
September 0.83 26.22 484.67 24.29 0.83 24.29
October 0.00 0.00 492.00 24.30 0.00 24.30
November 8.83 23.57 403.50 24.28 0.00 24.28
December 78.33 23.50 189.67 24.10 0.00 24.10
             
Annual Sum or Average 270.17 23.66 4811.33 24.21 22.00 24.21
Minimum of Months 0.00 0.00 160.00 24.10 0.00 24.10
Maximum of Months 118.17 26.22 514.00 24.30 13.17 24.30



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 375.17 22.58 50.67 22.61 15.50 22.52
February 190.33 23.10 167.50 23.59 7.83 23.62
March 33.17 23.54 373.33 24.15 1.67 24.15
April 0.00 0.00 425.83 24.26 0.00 24.26
May 0.00 0.00 502.67 24.23 0.00 24.23
June 0.00 0.00 496.00 24.22 0.00 24.22
July 0.00 0.00 497.00 24.29 0.00 24.29
August 0.00 0.00 514.00 24.25 0.00 24.25
September 3.67 26.78 481.50 24.34 3.50 24.36
October 0.00 0.00 478.00 24.28 0.00 24.28
November 94.83 23.18 285.33 23.91 0.00 23.91
December 318.50 22.78 62.67 22.98 0.00 22.98
             
Annual Sum or Average 1015.67 22.84 4334.50 23.96 28.50 23.96
Minimum of Months 0.00 0.00 50.67 22.61 0.00 22.52
Maximum of Months 375.17 26.78 514.00 24.34 15.50 24.36



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 335.83 22.89 64.00 23.13 0.00 23.13
February 161.17 23.05 176.17 23.63 0.00 23.63
March 31.00 23.27 391.83 24.15 0.00 24.15
April 5.17 26.64 450.67 24.32 5.17 24.34
May 14.00 26.78 508.00 24.46 14.00 24.52
June 14.67 26.43 496.00 24.40 14.67 24.45
July 34.00 26.60 497.00 24.58 34.00 24.70
August 19.33 26.60 514.00 24.38 19.33 24.46
September 13.83 26.16 485.00 24.43 13.83 24.48
October 0.00 0.00 487.83 24.29 0.00 24.29
November 62.50 23.24 333.50 24.05 0.00 24.05
December 235.00 23.10 98.83 23.40 0.00 23.40
             
Annual Sum or Average 926.50 23.41 4502.83 24.16 101.00 24.20
Minimum of Months 0.00 0.00 64.00 23.13 0.00 23.13
Maximum of Months 335.83 26.78 514.00 24.58 34.00 24.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 260.00 22.75 91.67 23.18 0.00 23.18
February 146.33 22.86 218.17 23.70 0.00 23.70
March 50.33 23.25 398.17 24.13 2.83 24.15
April 29.00 25.76 445.67 24.39 20.33 24.49
May 39.33 26.89 508.00 24.61 39.33 24.77
June 17.33 26.64 496.00 24.38 17.33 24.45
July 32.00 26.66 497.00 24.51 32.00 24.63
August 15.83 26.55 514.00 24.26 15.83 24.33
September 18.17 26.24 484.83 24.41 18.17 24.47
October 21.50 25.38 468.33 24.39 14.00 24.45
November 80.50 23.00 334.67 24.01 0.17 24.01
December 246.67 22.83 134.17 23.33 0.00 23.33
             
Annual Sum or Average 957.00 23.49 4590.67 24.17 160.00 24.24
Minimum of Months 15.83 22.75 91.67 23.18 0.00 23.18
Maximum of Months 260.00 26.89 514.00 24.61 39.33 24.77



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 168.83 22.95 221.00 23.73 0.17 23.74
February 87.67 23.31 310.67 24.20 8.33 24.26
March 35.83 25.04 446.83 24.42 17.17 24.51
April 21.50 26.89 468.83 24.48 21.50 24.59
May 24.83 26.76 508.00 24.53 24.83 24.63
June 15.67 26.46 496.00 24.40 15.67 24.46
July 34.83 26.66 497.00 24.58 34.83 24.71
August 21.67 26.77 514.00 24.41 21.67 24.50
September 28.33 26.50 485.00 24.56 28.33 24.66
October 46.17 26.96 498.67 24.75 46.17 24.92
November 48.33 25.92 433.83 24.69 34.67 24.85
December 101.83 23.28 307.50 24.18 5.67 24.23
             
Annual Sum or Average 635.50 24.55 5187.33 24.44 259.00 24.54
Minimum of Months 15.67 22.95 221.00 23.73 0.17 23.74
Maximum of Months 168.83 26.96 514.00 24.75 46.17 24.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 197.33 22.84 180.67 23.62 0.00 23.62
February 52.17 23.38 349.50 24.34 5.17 24.37
March 24.00 26.97 503.83 24.57 24.00 24.67
April 65.33 26.83 485.00 24.82 65.33 25.04
May 47.83 26.89 508.00 24.69 47.83 24.86
June 55.33 26.72 496.00 24.68 55.33 24.86
July 82.33 26.67 497.00 24.87 82.33 25.09
August 83.67 26.68 514.00 24.80 83.67 25.03
September 40.67 26.80 485.00 24.65 40.67 24.81
October 43.17 26.94 502.00 24.72 43.17 24.88
November 22.33 26.86 475.67 24.65 22.33 24.75
December 14.67 24.00 404.50 24.58 2.67 24.60
             
Annual Sum or Average 728.83 25.41 5401.17 24.62 472.50 24.77
Minimum of Months 14.67 22.84 180.67 23.62 0.00 23.62
Maximum of Months 197.33 26.97 514.00 24.87 83.67 25.09



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 490.17 22.13 0.00 22.13 0.00 22.13
February 328.00 22.59 59.50 22.83 0.00 22.83
March 117.33 23.11 281.83 23.84 0.00 23.84
April 5.83 24.35 426.17 24.36 1.67 24.37
May 16.67 26.74 508.00 24.50 16.67 24.57
June 29.00 26.19 496.00 24.48 29.00 24.57
July 79.33 26.23 497.00 24.75 79.33 24.93
August 55.17 26.10 514.00 24.55 55.17 24.69
September 41.33 26.16 485.00 24.55 41.33 24.67
October 20.00 23.00 435.83 24.21 0.00 24.21
November 230.67 22.90 138.17 23.32 0.00 23.32
December 473.83 22.31 0.00 22.31 0.00 22.31
             
Annual Sum or Average 1887.33 22.91 3841.50 23.88 223.17 23.97
Minimum of Months 5.83 22.13 0.00 22.13 0.00 22.13
Maximum of Months 490.17 26.74 514.00 24.75 79.33 24.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.17 22.36 2.50 22.37 0.00 22.37
February 210.67 22.55 100.67 23.12 0.00 23.12
March 73.50 23.10 289.67 24.11 4.33 24.15
April 30.00 26.47 373.83 24.73 26.83 24.86
May 44.33 26.92 430.00 24.79 44.33 24.97
June 35.67 26.54 418.00 24.63 35.67 24.77
July 73.17 26.42 422.00 24.88 73.17 25.07
August 47.50 26.32 433.00 24.64 47.50 24.79
September 53.50 26.19 403.33 24.70 53.50 24.86
October 35.17 24.64 375.67 24.51 16.17 24.59
November 142.67 22.80 197.17 23.67 0.17 23.67
December 353.67 22.40 4.67 22.44 0.00 22.44
             
Annual Sum or Average 1503.00 23.30 3450.50 24.13 301.67 24.27
Minimum of Months 30.00 22.36 2.50 22.37 0.00 22.37
Maximum of Months 403.17 26.92 433.00 24.88 73.17 25.07



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 230.17 22.84 192.50 23.52 0.67 23.53
February 122.33 23.04 264.50 24.02 8.67 24.09
March 50.83 24.33 415.00 24.39 16.33 24.47
April 18.67 26.86 451.33 24.57 18.50 24.66
May 24.83 26.76 508.00 24.55 24.83 24.65
June 29.00 26.19 496.00 24.48 29.00 24.57
July 80.00 26.25 497.00 24.76 80.00 24.94
August 55.67 26.29 514.00 24.59 55.67 24.74
September 54.17 26.40 485.00 24.69 54.17 24.84
October 46.33 27.03 491.17 24.81 46.33 24.98
November 73.33 25.04 407.33 24.63 36.17 24.80
December 171.17 22.97 233.33 23.89 5.17 23.93
             
Annual Sum or Average 956.50 24.31 4955.17 24.45 375.50 24.57
Minimum of Months 18.67 22.84 192.50 23.52 0.67 23.53
Maximum of Months 230.17 27.03 514.00 24.81 80.00 24.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 424.17 22.28 25.17 22.38 0.00 22.38
February 252.00 22.55 125.17 23.14 0.00 23.14
March 72.67 23.17 368.00 24.12 4.67 24.15
April 22.83 26.96 465.33 24.61 22.83 24.71
May 39.67 26.98 508.00 24.67 39.67 24.82
June 49.17 26.65 496.00 24.64 49.17 24.80
July 71.67 26.58 497.00 24.80 71.67 25.00
August 49.17 26.55 514.00 24.61 49.17 24.77
September 52.33 26.44 481.33 24.65 52.33 24.81
October 30.17 24.92 462.67 24.43 15.33 24.51
November 139.33 22.80 254.83 23.72 0.00 23.72
December 386.17 22.47 58.17 22.69 0.00 22.69
             
Annual Sum or Average 1589.33 23.29 4255.67 24.12 304.83 24.24
Minimum of Months 22.83 22.28 25.17 22.38 0.00 22.38
Maximum of Months 424.17 26.98 514.00 24.80 71.67 25.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 501.67 21.22 76.50 21.03 76.50 20.89
February 387.67 21.99 41.00 22.11 8.50 22.06
March 188.67 22.76 238.00 23.53 0.00 23.53
April 28.83 24.08 419.67 24.34 7.50 24.38
May 34.00 26.72 506.67 24.57 34.00 24.70
June 37.17 26.30 496.00 24.51 37.17 24.63
July 84.50 26.28 497.00 24.78 84.50 24.97
August 55.00 26.18 514.00 24.56 55.00 24.70
September 49.00 26.08 475.17 24.55 48.50 24.68
October 67.33 22.81 382.17 24.02 0.50 24.02
November 338.83 22.43 82.50 22.71 2.33 22.69
December 497.00 21.48 48.17 21.34 48.17 21.22
             
Annual Sum or Average 2269.67 22.38 3776.83 23.52 402.67 23.55
Minimum of Months 28.83 21.22 41.00 21.03 0.00 20.89
Maximum of Months 501.67 26.72 514.00 24.78 84.50 24.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 488.83 21.58 38.17 21.45 38.17 21.33
February 301.50 22.26 102.17 22.70 3.00 22.68
March 105.00 22.89 343.17 23.96 4.50 23.99
April 44.33 25.78 451.17 24.61 31.50 24.74
May 52.00 26.91 506.33 24.72 52.00 24.91
June 45.00 26.51 496.00 24.57 45.00 24.72
July 85.33 26.42 497.00 24.81 85.33 25.02
August 50.17 26.42 514.00 24.57 50.17 24.72
September 60.17 25.97 469.33 24.60 56.00 24.75
October 59.67 24.02 430.50 24.36 20.17 24.46
November 200.17 22.49 199.17 23.31 0.00 23.31
December 481.83 21.93 21.00 21.86 21.00 21.79
             
Annual Sum or Average 1974.00 22.82 4068.00 23.84 406.83 23.95
Minimum of Months 44.33 21.58 21.00 21.45 0.00 21.33
Maximum of Months 488.83 26.91 514.00 24.81 85.33 25.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 323.17 22.01 141.50 22.53 18.50 22.42
February 192.00 22.42 207.67 23.46 4.50 23.50
March 94.00 23.50 376.33 24.19 15.00 24.27
April 28.67 25.87 444.67 24.55 20.33 24.65
May 37.00 26.78 506.67 24.60 37.00 24.74
June 36.83 26.29 496.00 24.51 36.83 24.62
July 84.50 26.30 497.00 24.78 84.50 24.98
August 55.67 26.32 514.00 24.60 55.67 24.75
September 55.17 26.33 477.33 24.67 54.83 24.83
October 59.50 26.00 467.50 24.74 44.33 24.92
November 112.83 23.71 355.50 24.31 27.17 24.45
December 264.33 22.27 177.17 23.09 6.67 23.05
             
Annual Sum or Average 1343.67 23.50 4661.33 24.22 405.33 24.34
Minimum of Months 28.67 22.01 141.50 22.53 4.50 22.42
Maximum of Months 323.17 26.78 514.00 24.78 84.50 24.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 456.17 21.56 41.00 21.49 31.17 21.38
February 317.00 22.11 95.00 22.60 0.00 22.60
March 130.83 22.86 316.33 23.86 5.50 23.90
April 32.33 26.25 453.00 24.60 26.67 24.72
May 49.50 26.92 507.17 24.69 49.50 24.88
June 52.50 26.64 496.00 24.63 52.50 24.80
July 82.17 26.50 497.00 24.81 82.17 25.02
August 56.17 26.49 514.00 24.61 56.17 24.78
September 59.33 26.16 469.33 24.63 55.67 24.80
October 60.00 23.87 418.50 24.32 17.33 24.41
November 228.33 22.46 189.33 23.22 0.00 23.22
December 429.83 21.81 50.83 21.92 16.83 21.86
             
Annual Sum or Average 1954.17 22.81 4047.50 23.85 393.50 23.97
Minimum of Months 32.33 21.56 41.00 21.49 0.00 21.38
Maximum of Months 456.17 26.92 514.00 24.81 82.17 25.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 79.50 27.00 514.00 27.00 79.50 27.00
April 361.17 27.54 485.00 27.46 361.17 27.49
May 49.67 27.00 508.00 27.00 49.67 27.00
June 189.50 27.00 496.00 27.00 189.50 27.00
July 285.00 27.00 497.00 27.00 285.00 27.00
August 499.67 27.86 514.00 27.85 499.67 27.86
September 49.83 27.00 485.00 27.00 49.83 27.00
October 45.17 27.00 502.00 27.00 45.17 27.00
November 70.17 27.00 489.00 27.00 70.17 27.00
December 55.50 27.00 497.00 27.00 55.50 27.00
             
Annual Sum or Average 1685.17 27.37 5943.00 27.17 1685.17 27.20
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 499.67 27.86 514.00 27.85 499.67 27.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 0.00 0.00 514.00 27.00 0.00 27.00
April 162.67 28.00 485.00 27.52 162.67 27.62
May 0.83 27.00 508.00 27.00 0.83 27.00
June 12.50 27.00 496.00 27.00 12.50 27.00
July 17.00 27.00 497.00 27.00 17.00 27.00
August 296.50 28.11 514.00 27.84 296.50 27.91
September 0.00 0.00 485.00 27.00 0.00 27.00
October 0.33 27.00 502.00 27.00 0.33 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 497.00 27.00 0.00 27.00
             
Annual Sum or Average 489.83 28.00 5943.00 27.16 489.83 27.22
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 296.50 28.11 514.00 27.84 296.50 27.91



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 12.17 24.59 468.00 26.94 0.00 26.94
February 0.00 0.00 454.00 27.00 0.00 27.00
March 6.33 27.00 514.00 27.00 6.33 27.00
April 154.83 27.80 485.00 27.39 154.83 27.47
May 79.17 27.00 508.00 27.00 79.17 27.00
June 117.83 27.00 496.00 27.00 117.83 27.00
July 101.17 27.00 497.00 27.00 101.17 27.00
August 242.67 27.94 514.00 27.62 242.67 27.70
September 27.83 27.00 485.00 27.00 27.83 27.00
October 10.50 27.00 502.00 27.00 10.50 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 497.00 27.00 0.00 27.00
             
Annual Sum or Average 752.50 27.43 5909.00 27.10 740.33 27.14
Minimum of Months 0.00 0.00 454.00 26.94 0.00 26.94
Maximum of Months 242.67 27.94 514.00 27.62 242.67 27.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 27.01 502.00 27.01 502.00 27.01
February 454.00 27.01 454.00 27.01 454.00 27.01
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 29.31 485.00 29.31 485.00 29.31
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 30.43 514.00 30.43 514.00 30.43
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.01 497.00 27.01 497.00 27.01
             
Annual Sum or Average 5943.00 27.49 5943.00 27.49 5943.00 27.49
Minimum of Months 454.00 27.00 454.00 27.00 454.00 27.00
Maximum of Months 514.00 30.43 514.00 30.43 514.00 30.43



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00072 29.14011 0.86088 20.68628
February 454.00000 27.00091 29.62669 0.91711 22.80368
March 514.00000 27.00054 31.23450 0.98372 25.47058
April 485.00000 27.40295 32.55602 1.12323 31.84709
May 508.00000 27.00079 37.38577 0.33778 7.42628
June 496.00000 27.00234 37.17537 0.38305 8.10142
July 497.00000 27.00154 36.38610 0.41573 8.64529
August 514.00000 27.84063 34.76086 0.67860 15.51010
September 485.00000 27.00015 40.15412 0.34995 7.58807
October 502.00000 27.00160 33.22966 0.97941 25.28925
November 489.00000 27.00059 30.48441 0.97781 25.22834
December 497.00000 27.00017 28.25814 0.96936 24.88606
           
Annual Sum or Average 5943.00000 27.10637 33.38587 0.74663 18.57905
Minimum of Months 454.00000 27.00015 28.25814 0.33778 7.42628
Maximum of Months 514.00000 27.84063 40.15412 1.12323 31.84709



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00052 29.42895 0.78710 18.12306
February 454.00000 27.00085 29.71436 0.83503 19.77600
March 514.00000 27.00054 31.25270 0.90813 22.46411
April 485.00000 27.36346 32.60403 1.02845 27.60834
May 508.00000 27.00054 37.59655 0.29134 6.81897
June 496.00000 27.00238 37.32999 0.31321 7.09042
July 497.00000 27.00162 36.51790 0.32007 7.17362
August 514.00000 27.68536 34.97247 0.49486 10.84069
September 485.00000 27.00007 40.64669 0.30033 6.91637
October 502.00000 27.00156 33.33641 0.92115 22.95682
November 489.00000 27.00058 30.51208 0.88328 21.52526
December 497.00000 27.00018 28.25535 0.83192 19.67436
           
Annual Sum or Average 5943.00000 27.08967 33.53396 0.65793 15.86972
Minimum of Months 454.00000 27.00007 28.25535 0.29134 6.81897
Maximum of Months 514.00000 27.68536 40.64669 1.02845 27.60834



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.91961 29.82819 0.70289 15.82164
February 454.00000 27.00093 29.20742 0.79212 18.37296
March 514.00000 27.00061 30.62016 0.89585 22.04891
April 485.00000 27.26354 32.11160 1.02092 27.30957
May 508.00000 27.00060 36.94132 0.32152 7.26539
June 496.00000 27.00249 36.65314 0.34334 7.56221
July 497.00000 27.00178 35.83286 0.34520 7.57130
August 514.00000 27.46495 34.40980 0.45871 10.14665
September 485.00000 27.00007 39.99818 0.30907 7.06868
October 502.00000 27.00167 32.72368 0.91510 22.76297
November 489.00000 27.00066 29.89260 0.85036 20.38499
December 497.00000 27.00024 27.70765 0.76595 17.53049
           
Annual Sum or Average 5943.00000 27.05568 33.01415 0.64190 15.28156
Minimum of Months 454.00000 26.91961 27.70765 0.30907 7.06868
Maximum of Months 514.00000 27.46495 39.99818 1.02092 27.30957



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00513 30.03527 1.09590 30.33343
February 454.00000 27.00589 30.19842 1.24092 37.27707
March 514.00000 27.00304 31.02997 1.38238 44.57894
April 485.00000 29.30881 31.14036 1.98357 74.29898
May 508.00000 27.00345 34.95621 0.56285 11.70843
June 496.00000 27.00317 35.09126 0.78994 18.17770
July 497.00000 27.00170 34.50539 1.00238 26.23808
August 514.00000 30.42832 31.93572 2.19963 83.26724
September 485.00000 27.00419 35.50384 0.63856 13.62670
October 502.00000 27.00273 32.00682 1.30197 40.37678
November 489.00000 27.00422 30.64767 1.42214 46.69788
December 497.00000 27.00668 30.05369 1.53457 52.78114
           
Annual Sum or Average 5943.00000 27.48826 32.26949 1.26435 40.02171
Minimum of Months 454.00000 27.00170 30.03527 0.56285 11.70843
Maximum of Months 514.00000 30.42832 35.50384 2.19963 83.26724



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.57583 39.66639 0.51892 11.27526
February 454.00000 24.54944 44.29399 0.54447 11.76741
March 514.00000 24.45027 48.12555 0.55120 11.85104
April 485.00000 24.54390 47.50027 0.56683 12.28872
May 508.00000 24.52874 58.25629 -0.2019 6.88209
June 496.00000 24.49860 61.96334 -0.1715 6.84703
July 497.00000 24.65087 62.90484 -0.1040 7.14001
August 514.00000 24.50823 61.73300 -0.1372 6.98172
September 485.00000 24.58650 62.82090 -0.1197 7.09070
October 502.00000 24.63548 55.64772 0.66810 15.09308
November 489.00000 24.64004 46.84334 0.60366 13.32727
December 497.00000 24.62476 39.75811 0.54160 11.79960
           
Annual Sum or Average 5943.00000 24.56559 52.53039 0.26884 10.17678
Minimum of Months 454.00000 24.45027 39.66639 -0.2019 6.84703
Maximum of Months 514.00000 24.65087 62.90484 0.66810 15.09308



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.41929 42.42926 0.49793 10.89102
February 454.00000 24.36019 45.45331 0.52182 11.02094
March 514.00000 24.27266 48.86171 0.54388 11.42074
April 485.00000 24.20387 48.66174 0.54261 11.30311
May 508.00000 24.20222 54.32670 -0.2925 6.97465
June 496.00000 24.18641 56.11245 -0.2757 6.75028
July 497.00000 24.23233 56.37679 -0.2530 6.52425
August 514.00000 24.20159 56.08780 -0.2438 6.41962
September 485.00000 24.30469 56.58026 -0.2480 6.70851
October 502.00000 24.34989 53.98583 0.60108 12.83387
November 489.00000 24.40718 47.96903 0.57002 12.14570
December 497.00000 24.41995 41.05898 0.51335 10.88475
           
Annual Sum or Average 5943.00000 24.29590 50.70415 0.20336 9.47363
Minimum of Months 454.00000 24.18641 41.05898 -0.2925 6.41962
Maximum of Months 514.00000 24.41995 56.58026 0.60108 12.83387



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.06438 43.49560 0.39005 8.51063
February 454.00000 24.14180 45.92017 0.44126 9.38417
March 514.00000 24.20778 48.95639 0.50021 10.45188
April 485.00000 24.18401 48.79398 0.50223 10.43940
May 508.00000 24.13290 54.67013 -0.3421 7.61246
June 496.00000 24.15428 56.62953 -0.3204 7.33527
July 497.00000 24.18406 57.28152 -0.3116 7.23574
August 514.00000 24.19437 57.37620 -0.3033 7.15754
September 485.00000 24.28632 56.94065 -0.2828 7.12010
October 502.00000 24.28711 54.34092 0.56140 11.82625
November 489.00000 24.23305 48.38138 0.49523 10.36280
December 497.00000 24.06198 42.05651 0.38723 8.37666
           
Annual Sum or Average 5943.00000 24.17768 51.28523 0.14011 8.81193
Minimum of Months 454.00000 24.06198 42.05651 -0.3421 7.12010
Maximum of Months 514.00000 24.28711 57.37620 0.56140 11.82625



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.93168 46.58799 0.09425 6.66226
February 454.00000 23.63005 47.76919 0.30809 7.83026
March 514.00000 24.10100 49.66703 0.47778 10.04687
April 485.00000 24.22786 48.99780 0.53129 11.10347
May 508.00000 24.23120 54.25609 -0.2727 6.83771
June 496.00000 24.22260 56.17026 -0.2589 6.70744
July 497.00000 24.29033 56.79764 -0.2459 6.62384
August 514.00000 24.24954 57.15733 -0.2592 6.71975
September 485.00000 24.31950 57.04440 -0.2539 6.87891
October 502.00000 24.24763 55.14796 0.55908 11.74372
November 489.00000 23.89666 50.09410 0.40925 8.91314
December 497.00000 23.21100 44.80654 0.16601 6.71578
           
Annual Sum or Average 5943.00000 23.96554 52.08021 0.10234 8.06377
Minimum of Months 454.00000 22.93168 44.80654 -0.2727 6.62384
Maximum of Months 514.00000 24.31950 57.15733 0.55908 11.74372



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.28900 43.50460 0.19529 6.57904
February 454.00000 23.70319 46.36509 0.34070 8.01749
March 514.00000 24.08996 48.60011 0.49019 10.30271
April 485.00000 24.26435 47.64394 0.58157 12.40544
May 508.00000 24.39942 52.88873 -0.1524 6.22539
June 496.00000 24.33710 54.90135 -0.1400 6.01441
July 497.00000 24.43885 55.41611 -0.1122 6.23792
August 514.00000 24.29834 55.37595 -0.1532 6.12229
September 485.00000 24.38038 56.00557 -0.1846 6.43308
October 502.00000 24.26413 53.50691 0.58011 12.29755
November 489.00000 24.00510 48.42199 0.44816 9.48141
December 497.00000 23.58988 42.41999 0.27892 7.12904
           
Annual Sum or Average 5943.00000 24.09088 50.45679 0.17918 8.09701
Minimum of Months 454.00000 23.28900 42.41999 -0.1846 6.01441
Maximum of Months 514.00000 24.43885 56.00557 0.58157 12.40544



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.40767 43.00136 0.24267 7.09759
February 454.00000 23.72349 46.14724 0.37257 8.70338
March 514.00000 24.06298 48.48698 0.51641 11.13271
April 485.00000 24.25535 47.51033 0.61602 13.56918
May 508.00000 24.43593 52.62967 -0.0812 6.34985
June 496.00000 24.30063 54.91498 -0.1225 6.03167
July 497.00000 24.36651 55.61840 -0.1264 6.38755
August 514.00000 24.19225 55.76925 -0.1938 6.38727
September 485.00000 24.33675 56.00562 -0.1699 6.42077
October 502.00000 24.27174 53.29960 0.61010 13.34004
November 489.00000 23.95400 48.36114 0.46204 10.01402
December 497.00000 23.46276 42.60172 0.26767 7.28786
           
Annual Sum or Average 5943.00000 24.06648 50.39956 0.19747 8.55164
Minimum of Months 454.00000 23.40767 42.60172 -0.1938 6.03167
Maximum of Months 514.00000 24.43593 56.00562 0.61602 13.56918



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.79108 41.89171 0.35992 8.78599
February 454.00000 24.11069 45.03053 0.48783 11.00844
March 514.00000 24.28312 47.77491 0.58826 12.87152
April 485.00000 24.35996 47.23995 0.63665 14.04003
May 508.00000 24.41803 52.80480 -0.1353 6.25307
June 496.00000 24.33294 54.91447 -0.1423 6.04419
July 497.00000 24.43918 55.40822 -0.1105 6.27979
August 514.00000 24.31347 55.28478 -0.1382 6.15922
September 485.00000 24.44498 55.65630 -0.1214 6.36047
October 502.00000 24.53534 52.34175 0.71317 16.53606
November 489.00000 24.45034 46.70254 0.63624 14.42515
December 497.00000 24.10741 40.80752 0.45731 10.39647
           
Annual Sum or Average 5943.00000 24.29960 49.69638 0.26681 9.91116
Minimum of Months 454.00000 23.79108 40.80752 -0.1423 6.04419
Maximum of Months 514.00000 24.53534 55.65630 0.71317 16.53606



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.68776 41.94532 0.33905 8.33823
February 454.00000 24.21552 44.56468 0.52928 11.64760
March 514.00000 24.43996 47.21988 0.67771 15.28207
April 485.00000 24.55498 46.51747 0.79736 19.19822
May 508.00000 24.48305 52.42333 -0.0079 6.33060
June 496.00000 24.45040 54.27365 0.02891 6.26182
July 497.00000 24.57109 54.63447 0.05846 6.72483
August 514.00000 24.49557 54.35312 0.09069 6.67788
September 485.00000 24.47297 55.36249 -0.0582 6.21100
October 502.00000 24.53082 52.33862 0.72867 16.84605
November 489.00000 24.52522 46.47368 0.66225 14.88360
December 497.00000 24.44889 39.81798 0.56547 12.35983
           
Annual Sum or Average 5943.00000 24.40713 49.20116 0.36581 10.87437
Minimum of Months 454.00000 23.68776 39.81798 -0.0582 6.21100
Maximum of Months 514.00000 24.57109 55.36249 0.79736 19.19822



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.17086 45.94754 -0.0796 5.99965
February 454.00000 22.96336 47.97609 0.14700 6.54477
March 514.00000 23.85124 49.01750 0.40917 9.00679
April 485.00000 24.30071 47.48387 0.55607 11.82774
May 508.00000 24.42404 53.01776 -0.1628 6.39263
June 496.00000 24.38254 55.53137 -0.1476 6.21274
July 497.00000 24.51703 56.78774 -0.1148 6.51643
August 514.00000 24.38271 56.92529 -0.1711 6.43607
September 485.00000 24.41321 57.12092 -0.1915 6.77282
October 502.00000 24.14322 53.98306 0.52954 11.17351
November 489.00000 23.43774 49.82565 0.29075 7.36298
December 497.00000 22.37212 45.02651 -0.0286 5.95482
           
Annual Sum or Average 5943.00000 23.78591 51.58627 0.08527 7.51789
Minimum of Months 454.00000 22.17086 45.02651 -0.1915 5.95482
Maximum of Months 514.00000 24.51703 57.12092 0.55607 11.82774



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 22.44179 44.57469 0.00037 5.85039
February 385.00000 23.26180 46.44778 0.23913 7.43303
March 433.00000 24.03580 47.68338 0.48329 10.75114
April 410.00000 24.51193 46.16202 0.64609 14.62939
May 430.00000 24.56636 52.33464 -0.0619 6.73520
June 418.00000 24.46318 55.16831 -0.0922 6.35366
July 422.00000 24.60832 56.45570 -0.0703 6.84157
August 433.00000 24.45277 56.64605 -0.1373 6.58316
September 410.00000 24.48059 56.90399 -0.1442 6.89652
October 427.00000 24.33463 53.12284 0.60148 13.40768
November 417.00000 23.66835 48.56868 0.37030 8.71600
December 422.00000 22.64981 43.79562 0.05394 6.09779
           
Annual Sum or Average 5034.00000 23.95979 50.68621 0.15633 8.35583
Minimum of Months 385.00000 22.44179 43.79562 -0.1442 5.85039
Maximum of Months 433.00000 24.60832 56.90399 0.64609 14.62939



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.58843 42.06051 0.30519 8.32907
February 454.00000 23.94714 45.02302 0.43399 10.36394
March 514.00000 24.24525 47.53600 0.55974 12.32942
April 485.00000 24.44047 46.92503 0.62534 13.81119
May 508.00000 24.44166 52.92959 -0.1463 6.39157
June 496.00000 24.37772 55.54863 -0.1513 6.23294
July 497.00000 24.51762 56.76844 -0.1129 6.53575
August 514.00000 24.40909 56.76304 -0.1500 6.46412
September 485.00000 24.49402 56.63175 -0.1184 6.69373
October 502.00000 24.57250 52.21291 0.70808 16.51763
November 489.00000 24.38060 46.47355 0.60351 13.76894
December 497.00000 23.86956 40.97338 0.37984 9.57172
           
Annual Sum or Average 5943.00000 24.27538 50.03265 0.24240 9.73581
Minimum of Months 454.00000 23.58843 40.97338 -0.1513 6.23294
Maximum of Months 514.00000 24.57250 56.76844 0.70808 16.51763



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.54103 44.60593 0.03617 6.15340
February 454.00000 23.23515 46.88848 0.24685 7.60982
March 514.00000 24.03819 48.16540 0.50565 11.12450
April 485.00000 24.46191 46.85218 0.66519 15.02597
May 508.00000 24.48822 52.64908 -0.0612 6.53211
June 496.00000 24.43878 55.13759 -0.0560 6.35052
July 497.00000 24.54543 56.35193 -0.0593 6.68115
August 514.00000 24.42853 56.46513 -0.1064 6.40466
September 485.00000 24.45021 56.66215 -0.1242 6.75453
October 502.00000 24.30403 53.23781 0.61390 13.59194
November 489.00000 23.70117 48.59981 0.39714 9.07271
December 497.00000 22.80381 43.51165 0.10395 6.38835
           
Annual Sum or Average 5943.00000 23.95816 50.79605 0.17896 8.47061
Minimum of Months 454.00000 22.54103 43.51165 -0.1242 6.15340
Maximum of Months 514.00000 24.54543 56.66215 0.66519 15.02597



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.21710 48.03899 -0.3337 8.89581
February 454.00000 22.26723 49.86649 -0.0215 6.69480
March 514.00000 23.55555 50.09448 0.34916 8.54773
April 485.00000 24.25024 48.04199 0.56580 12.25700
May 508.00000 24.42704 53.00939 -0.1238 6.42084
June 496.00000 24.37819 55.46715 -0.1098 6.18655
July 497.00000 24.52461 56.75447 -0.0795 6.63310
August 514.00000 24.38635 56.98932 -0.1433 6.41564
September 485.00000 24.36572 57.50065 -0.1864 6.90269
October 502.00000 23.95799 55.19894 0.49899 10.78527
November 489.00000 22.85365 51.92086 0.15780 6.75599
December 497.00000 21.47687 47.11609 -0.2576 7.80184
           
Annual Sum or Average 5943.00000 23.48086 52.52356 0.02614 7.85986
Minimum of Months 454.00000 21.21710 47.11609 -0.3337 6.18655
Maximum of Months 514.00000 24.52461 57.50065 0.56580 12.25700



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.63776 46.77365 -0.2082 7.44620
February 454.00000 22.84101 48.13740 0.13988 7.17470
March 514.00000 23.90425 48.84393 0.47367 10.77832
April 485.00000 24.42098 47.32208 0.66867 15.26954
May 508.00000 24.49441 52.60632 -0.0215 6.72123
June 496.00000 24.39375 55.23639 -0.0534 6.30359
July 497.00000 24.53365 56.52188 -0.0441 6.88134
August 514.00000 24.38888 56.79223 -0.1133 6.50082
September 485.00000 24.37942 57.18507 -0.1375 6.88833
October 502.00000 24.20690 54.12590 0.59666 13.35640
November 489.00000 23.37649 50.11778 0.30879 8.25314
December 497.00000 21.98638 45.64129 -0.1157 6.70970
           
Annual Sum or Average 5943.00000 23.72013 51.63939 0.12376 8.52427
Minimum of Months 454.00000 21.63776 45.64129 -0.2082 6.30359
Maximum of Months 514.00000 24.53365 57.18507 0.66867 15.26954



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.78254 43.89004 0.08763 8.08646
February 454.00000 23.47868 46.39355 0.31458 9.47695
March 514.00000 24.07810 48.31668 0.52805 12.01701
April 485.00000 24.40030 47.47665 0.63898 14.33298
May 508.00000 24.44310 52.93076 -0.1072 6.45623
June 496.00000 24.37442 55.48374 -0.1132 6.20743
July 497.00000 24.52547 56.74188 -0.0776 6.66381
August 514.00000 24.41034 56.84022 -0.1224 6.46538
September 485.00000 24.45869 56.98461 -0.1081 6.82704
October 502.00000 24.48583 53.15880 0.70064 16.47985
November 489.00000 24.11661 47.77529 0.53939 12.79827
December 497.00000 23.23359 42.50425 0.20898 8.59970
           
Annual Sum or Average 5943.00000 24.06929 50.74739 0.20579 9.52387
Minimum of Months 454.00000 22.78254 42.50425 -0.1224 6.20743
Maximum of Months 514.00000 24.52547 56.98461 0.70064 16.47985



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.77023 46.27938 -0.1695 7.47100
February 454.00000 22.70059 48.40947 0.11655 7.28478
March 514.00000 23.80631 49.09615 0.46072 10.70602
April 485.00000 24.41232 47.43103 0.67584 15.50955
May 508.00000 24.47407 52.72439 -0.0273 6.76541
June 496.00000 24.41580 55.16085 -0.0233 6.48546
July 497.00000 24.53347 56.42899 -0.0306 6.86759
August 514.00000 24.40946 56.63391 -0.0866 6.47532
September 485.00000 24.38831 57.11785 -0.1223 6.97547
October 502.00000 24.14663 54.37335 0.59081 13.28434
November 489.00000 23.27280 50.30611 0.30003 8.28400
December 497.00000 22.10203 45.18875 -0.0769 6.92874
           
Annual Sum or Average 5943.00000 23.71005 51.62452 0.13343 8.58559
Minimum of Months 454.00000 21.77023 45.18875 -0.1695 6.47532
Maximum of Months 514.00000 24.53347 57.11785 0.67584 15.50955



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.910608E+11 107943.83 25-JAN-15:10 434.64 0.556646E+12 0.00 0.647707E+12 3.30 7.36 18-JAN-06:04 0.00 0.00
February 0.102960E+12 112659.78 07-FEB-15:20 425.05 0.651563E+12 0.00 0.754523E+12 3.77 7.56 25-FEB-06:02 0.00 0.00
March 0.154579E+12 137315.90 11-MAR-06:02 565.69 0.102575E+13 0.00 0.118033E+13 4.76 7.54 30-MAR-05:02 0.00 0.00
April 0.197485E+12 199993.45 17-APR-05:03 671.95 0.131774E+13 0.00 0.151523E+13 5.82 7.63 19-APR-05:03 0.00 0.00
May 0.250512E+12 217356.56 25-MAY-05:03 687.27 0.166412E+13 0.00 0.191463E+13 5.93 7.55 11-MAY-05:03 0.00 0.00
June 0.267291E+12 229085.48 27-JUN-05:03 663.17 0.173728E+13 0.00 0.200457E+13 5.79 7.52 02-JUN-05:03 0.00 0.00
July 0.292315E+12 235708.26 31-JUL-05:03 702.31 0.184818E+13 0.00 0.214050E+13 5.71 7.26 19-JUL-03:02 0.00 0.00
August 0.290000E+12 236330.70 28-AUG-05:03 710.13 0.183266E+13 0.00 0.212266E+13 5.70 7.30 07-AUG-05:03 0.00 0.00
September 0.226910E+12 226435.65 11-SEP-05:05 597.04 0.146487E+13 0.00 0.169178E+13 5.10 7.60 27-SEP-05:03 0.00 0.00
October 0.177474E+12 205326.84 04-OCT-05:02 589.91 0.119353E+13 0.00 0.137101E+13 5.04 7.77 18-OCT-05:02 0.00 0.00
November 0.132918E+12 115526.25 06-NOV-13:10 515.46 0.862757E+12 0.00 0.995675E+12 4.37 7.63 13-NOV-06:04 0.00 0.00
December 0.103093E+12 108815.30 01-DEC-15:20 474.46 0.638369E+12 0.00 0.741462E+12 3.64 7.36 01-DEC-11:30 0.00 0.00
                         
Annual Sum or Average 0.228660E+13     7037.06 0.147935E+14 0.00 0.170801E+14 4.92     0.00 0.00
Minimum of Months 0.910608E+11 107943.83   425.05 0.556646E+12 0.00 0.647707E+12 3.30 7.26   0.00 0.00
Maximum of Months 0.292315E+12 236330.70   710.13 0.184818E+13 0.00 0.214050E+13 5.93 7.77   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 13382786.40 111523.22 25-FEB-06:02 0.03 0.101166E+09 0.00 0.114549E+09 0.00 7.56 25-FEB-06:02 0.00 0.00
March 0.159118E+11 137315.90 11-MAR-06:02 40.14 0.113052E+12 0.00 0.128964E+12 0.38 7.54 30-MAR-05:02 0.00 0.00
April 0.604766E+11 199993.45 17-APR-05:03 144.74 0.427766E+12 0.00 0.488242E+12 1.42 7.63 19-APR-05:03 0.00 0.00
May 0.115238E+12 217356.56 25-MAY-05:03 250.53 0.792423E+12 0.00 0.907662E+12 2.32 7.55 11-MAY-05:03 0.00 0.00
June 0.156401E+12 229085.48 27-JUN-05:03 314.62 0.104326E+13 0.00 0.119966E+13 2.92 7.52 02-JUN-05:03 0.00 0.00
July 0.202612E+12 235708.26 31-JUL-05:03 400.38 0.132301E+13 0.00 0.152563E+13 3.51 7.26 19-JUL-03:02 0.00 0.00
August 0.207602E+12 236330.70 28-AUG-05:03 402.46 0.135459E+13 0.00 0.156219E+13 3.53 7.30 07-AUG-05:03 0.00 0.00
September 0.128654E+12 226435.65 11-SEP-05:05 266.59 0.858805E+12 0.00 0.987458E+12 2.47 7.60 27-SEP-05:03 0.00 0.00
October 0.521608E+11 205326.84 04-OCT-05:02 125.88 0.368173E+12 0.00 0.420334E+12 1.19 7.77 18-OCT-05:02 0.00 0.00
November 0.356331E+10 115526.25 06-NOV-13:10 9.11 0.254228E+11 0.00 0.289861E+11 0.09 7.63 13-NOV-06:04 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.942632E+12     1954.49 0.630660E+13 0.00 0.724924E+13 1.50     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.207602E+12 236330.70   402.46 0.135459E+13 0.00 0.156219E+13 3.53 7.77   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.663863E+11 744.00 49248.27 02-JAN-13:30 216017.63 12-JAN-17:00 22.67 19.07 14.75
February 0.101253E+12 672.00 49248.27 01-FEB-10:20 380277.07 24-FEB-16:10 28.03 21.43 14.75
March 0.131872E+12 744.00 49248.27 01-MAR-00:10 650723.08 31-MAR-24:00 36.96 27.23 14.75
April 0.127652E+12 720.00 49248.27 01-APR-00:03 721001.50 16-APR-17:12 48.63 35.70 14.75
May 0.131907E+12 744.00 49248.27 01-MAY-00:03 380038.19 31-MAY-23:50 39.88 35.28 14.75
June 0.127652E+12 720.00 49248.27 01-JUN-00:10 558519.48 30-JUN-23:53 45.37 37.55 14.75
July 0.131907E+12 744.00 49248.27 01-JUL-00:03 691314.85 31-JUL-24:00 48.04 37.18 14.75
August 0.131907E+12 744.00 49248.27 01-AUG-00:03 724442.51 25-AUG-14:30 50.17 36.83 14.75
September 0.127652E+12 720.00 49248.27 01-SEP-00:05 378738.22 30-SEP-23:20 35.72 31.07 14.75
October 0.131907E+12 744.00 49248.27 01-OCT-00:03 488108.12 31-OCT-23:40 35.81 28.65 14.75
November 0.125556E+12 720.00 49248.27 01-NOV-00:10 551748.18 08-NOV-16:20 34.20 24.57 14.75
December 0.122191E+12 744.00 49248.27 01-DEC-07:00 671951.82 28-DEC-16:30 33.56 21.45 14.75
                   
Annual Sum or Average 0.145784E+13 8760.00         38.31 29.71 14.75
Minimum of Months 0.663863E+11 672.00 49248.27   216017.63   22.67 19.07 14.75
Maximum of Months 0.131907E+12 744.00 49248.27   724442.51   50.17 37.55 14.75



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.404185E+09 323.58 1364.81 25-JAN-15:00 1138789.27 25-JAN-15:50 22.10 21.29 38.69
February 0.872536E+09 366.48 3995.49 24-FEB-16:20 1298716.05 22-FEB-15:30 22.53 21.42 44.94
March 0.748649E+10 506.42 21904.98 06-MAR-12:50 1390471.32 08-MAR-13:50 22.97 21.31 55.50
April 0.232772E+11 623.53 21904.98 01-APR-09:10 1433744.14 10-APR-15:40 23.68 21.60 68.76
May 0.485966E+11 687.27 21904.98 01-MAY-04:07 1477696.28 24-MAY-05:05 26.13 23.75 67.67
June 0.519638E+11 663.17 21904.98 01-JUN-00:12 1498338.52 22-JUN-15:50 28.36 25.78 62.77
July 0.553829E+11 702.31 21904.98 01-JUL-00:03 1507072.39 31-JUL-05:03 30.06 27.38 61.29
August 0.559991E+11 710.13 21904.98 01-AUG-00:03 1525685.01 28-AUG-05:03 29.89 27.23 63.81
September 0.470020E+11 597.04 21904.98 01-SEP-00:05 1573238.90 05-SEP-05:06 28.31 26.10 54.73
October 0.235512E+11 564.99 21904.98 01-OCT-00:33 1388525.85 04-OCT-05:04 23.56 21.77 59.09
November 0.324328E+10 450.55 21904.98 06-NOV-10:40 1388331.25 01-NOV-15:50 22.80 21.29 51.34
December 0.514988E+09 364.85 1611.18 27-DEC-13:50 1182753.60 01-DEC-15:40 22.24 21.29 43.65
                   
Annual Sum or Average 0.318294E+12 6560.33         25.23 23.36 56.08
Minimum of Months 0.404185E+09 323.58 1364.81   1138789.27   22.10 21.29 38.69
Maximum of Months 0.559991E+11 710.13 21904.98   1573238.90   30.06 27.38 68.76



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 22.10 22.10 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 22.53 22.53 0.00
March 0.178307E+10 23.57 21904.98 06-MAR-14:40 1348890.29 14-MAR-14:20 22.97 22.86 2.37
April 0.815090E+10 105.94 21904.98 03-APR-05:03 1433744.14 10-APR-15:40 23.68 23.20 10.99
May 0.227764E+11 288.87 21904.98 01-MAY-05:02 1477696.28 24-MAY-05:05 26.13 24.88 27.63
June 0.350378E+11 444.32 21904.98 01-JUN-03:02 1498338.52 22-JUN-15:50 28.36 26.35 40.05
July 0.463036E+11 587.18 21904.98 01-JUL-00:23 1507072.39 31-JUL-05:03 30.06 27.54 49.73
August 0.436567E+11 553.61 21904.98 01-AUG-00:30 1525685.01 28-AUG-05:03 29.89 27.43 48.10
September 0.324932E+11 412.05 21904.98 01-SEP-00:28 1573238.90 05-SEP-05:06 28.31 26.50 35.53
October 0.785800E+10 99.79 21904.98 01-OCT-14:02 1388525.85 04-OCT-05:04 23.56 23.14 10.02
November 0.136569E+09 4.00 21904.98 06-NOV-11:20 1382133.35 13-NOV-14:30 22.80 22.77 0.41
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 22.24 22.24 0.00
                   
Annual Sum or Average 0.198196E+12 2519.32         25.23 24.31 18.86
Minimum of Months 0.00 0.00 0.00   0.00   22.10 22.10 0.00
Maximum of Months 0.463036E+11 587.18 21904.98   1573238.90   30.06 27.54 49.73



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.937313E+10 0.00 188.15 214389.78 03-JAN-06:03 0.00 26.42 39.99 0.02 0.00 0.00 0.15 03-JAN-06:03
February 0.133847E+10 0.00 66.45 121606.28 11-FEB-06:02 0.00 21.91 27.53 0.00 0.00 0.00 0.09 11-FEB-06:02
March 1925490.69 0.00 1.50 642.83 01-MAR-06:50 0.00 20.68 20.80 0.00 0.00 0.00 0.00 01-MAR-06:50
April 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 20.68 20.68 0.00 0.00 0.00 0.00 01-APR-00:03
May 0.00 0.00 0.00 0.00 01-MAY-00:03 0.00 20.68 20.68 0.00 0.00 0.00 0.00 01-MAY-00:03
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 20.68 20.68 0.00 0.00 0.00 0.00 01-JUN-00:10
July 0.00 0.00 0.00 0.00 01-JUL-00:03 0.00 20.68 20.68 0.00 0.00 0.00 0.00 01-JUL-00:03
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 20.68 20.68 0.00 0.00 0.00 0.00 01-AUG-00:03
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 20.68 20.68 0.00 0.00 0.00 0.00 01-SEP-00:05
October 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 20.68 20.68 0.00 0.00 0.00 0.00 01-OCT-00:03
November 96311779.32 0.00 17.20 5007.30 27-NOV-06:20 0.00 20.58 21.99 0.00 0.00 0.00 0.00 27-NOV-06:20
December 0.350425E+10 0.00 141.17 195903.17 21-DEC-06:02 0.00 22.43 33.11 0.01 0.00 0.00 0.14 21-DEC-06:02
                           
Annual Sum or Average 0.143141E+11 0.00 414.47     0.00 21.40 24.02 0.00 0.00 0.00    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 20.58 20.68 0.00 0.00 0.00 0.00  
Maximum of Months 0.937313E+10 0.00 188.15 214389.78   0.00 26.42 39.99 0.02 0.00 0.00 0.15  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 22.67 22.67 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 28.03 28.03 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 36.96 36.96 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 48.63 48.63 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:03 0.00 39.88 39.88 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 45.37 45.37 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:03 0.00 48.04 48.04 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 50.17 50.17 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 35.72 35.72 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 35.81 35.81 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 34.20 34.20 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 33.56 33.56 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 38.31 38.31 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 22.67 22.67 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 50.17 50.17 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.551477E+11 0.00 413.05 0.550594E+11 0.00 0.00 0.00 0.00 124272.76 02-JAN-06:03 94445.01 14-JAN-05:02 0.00 0.00 0.00
February 0.727524E+11 0.00 410.76 0.725854E+11 0.00 0.00 0.00 0.00 152978.55 25-FEB-04:02 112523.37 21-FEB-06:03 0.00 0.00 0.00
March 0.129389E+12 0.00 549.99 0.127435E+12 0.00 0.00 0.00 0.00 218056.73 29-MAR-05:02 161086.79 14-MAR-05:03 0.00 0.00 0.00
April 0.185927E+12 0.00 625.32 0.179024E+12 0.00 0.00 0.00 0.00 266193.40 17-APR-05:03 185838.51 17-APR-05:03 0.00 0.00 0.00
May 0.225479E+12 0.00 612.64 0.192353E+12 0.00 0.00 0.00 0.00 281586.37 22-MAY-05:02 200216.03 01-MAY-05:03 0.00 0.00 0.00
June 0.264382E+12 0.00 608.12 0.197548E+12 0.00 0.00 0.00 0.00 301171.54 29-JUN-05:02 204726.69 12-JUN-05:03 0.00 0.00 0.00
July 0.305430E+12 0.00 636.65 0.191305E+12 0.00 0.00 0.00 0.00 305776.95 17-JUL-05:03 193798.14 05-JUL-05:02 0.00 0.00 0.00
August 0.330330E+12 0.00 660.08 0.203546E+12 0.00 0.00 0.00 0.00 311690.62 28-AUG-05:03 191625.16 07-AUG-05:03 0.00 0.00 0.00
September 0.227887E+12 0.00 537.52 0.148271E+12 0.00 0.00 0.00 0.00 290773.28 05-SEP-03:02 178538.81 05-SEP-03:02 0.00 0.00 0.00
October 0.156275E+12 0.00 545.78 0.139563E+12 0.00 0.00 0.00 0.00 262460.46 04-OCT-05:02 172680.96 04-OCT-05:02 0.00 0.00 0.00
November 0.107927E+12 0.00 481.22 0.106676E+12 0.00 0.00 0.00 0.00 171389.39 06-NOV-06:03 139989.89 06-NOV-06:03 0.00 0.00 0.00
December 0.763068E+11 0.00 454.39 0.763068E+11 0.00 0.00 0.00 0.00 117445.95 29-DEC-06:03 117445.95 29-DEC-06:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.213723E+13 0.00 6535.53 0.168967E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.551477E+11 0.00 410.76 0.550594E+11 0.00 0.00 0.00 0.00 117445.95   94445.01   0.00 0.00 0.00
Maximum of Months 0.330330E+12 0.00 660.08 0.203546E+12 0.00 0.00 0.00 0.00 311690.62   204726.69   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.399574E+12 0.00 378.68 0.399137E+12 0.00 0.00 0.00 0.00 1039018.35 18-JAN-06:02 866772.41 14-JAN-06:02 0.00 0.00 0.00
February 0.539654E+12 0.00 380.28 0.538463E+12 0.00 0.00 0.00 0.00 1442929.56 25-FEB-06:02 999008.09 25-FEB-06:02 0.00 0.00 0.00
March 0.998560E+12 0.00 472.85 0.984494E+12 0.00 0.00 0.00 0.00 2153112.37 11-MAR-06:02 1551814.83 11-MAR-06:02 0.00 0.00 0.00
April 0.144127E+13 0.00 515.89 0.139021E+13 0.00 0.00 0.00 0.00 2321106.57 27-APR-05:03 1705165.89 27-APR-05:03 0.00 0.00 0.00
May 0.206128E+13 0.00 585.51 0.174580E+13 0.00 0.00 0.00 0.00 2827145.56 24-MAY-03:02 1690995.84 19-MAY-05:02 0.00 0.00 0.00
June 0.233610E+13 0.00 561.27 0.171968E+13 0.00 0.00 0.00 0.00 2944871.51 27-JUN-05:03 1801751.82 07-JUN-05:02 0.00 0.00 0.00
July 0.255859E+13 0.00 555.97 0.154365E+13 0.00 0.00 0.00 0.00 3275022.81 20-JUL-03:02 1768407.75 05-JUL-05:02 0.00 0.00 0.00
August 0.254024E+13 0.00 543.86 0.148349E+13 0.00 0.00 0.00 0.00 2990989.56 11-AUG-03:02 1689898.36 07-AUG-05:01 0.00 0.00 0.00
September 0.198051E+13 0.00 479.09 0.126414E+13 0.00 0.00 0.00 0.00 2943218.74 11-SEP-03:02 1672094.99 05-SEP-03:02 0.00 0.00 0.00
October 0.128008E+13 0.00 479.40 0.113594E+13 0.00 0.00 0.00 0.00 2474623.86 04-OCT-05:02 1624675.56 04-OCT-05:02 0.00 0.00 0.00
November 0.801234E+12 0.00 432.08 0.792170E+12 0.00 0.00 0.00 0.00 1599715.86 09-NOV-06:03 1082554.35 09-NOV-06:03 0.00 0.00 0.00
December 0.466031E+12 0.00 402.46 0.466031E+12 0.00 0.00 0.00 0.00 898420.44 29-DEC-06:03 898420.44 29-DEC-06:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.174031E+14 0.00 5787.34 0.134632E+14 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.399574E+12 0.00 378.68 0.399137E+12 0.00 0.00 0.00 0.00 898420.44   866772.41   0.00 0.00 0.00
Maximum of Months 0.255859E+13 0.00 585.51 0.174580E+13 0.00 0.00 0.00 0.00 3275022.81   1801751.82   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.292588E+11 0.00 338.64 0.292482E+11 0.00 0.00 0.00 0.00 67572.36 12-JAN-15:30 67572.36 12-JAN-15:30 0.00 0.00 0.00
February 0.477579E+11 0.00 355.16 0.476534E+11 0.00 0.00 0.00 0.00 130621.65 25-FEB-06:02 101035.28 22-FEB-15:00 0.00 0.00 0.00
March 0.102628E+12 0.00 456.88 0.101264E+12 0.00 0.00 0.00 0.00 215562.06 11-MAR-06:02 156297.93 11-MAR-06:02 0.00 0.00 0.00
April 0.162918E+12 0.00 521.62 0.157648E+12 0.00 0.00 0.00 0.00 253548.83 27-APR-05:03 186687.28 27-APR-05:03 0.00 0.00 0.00
May 0.236869E+12 0.00 598.46 0.203960E+12 0.00 0.00 0.00 0.00 306118.38 24-MAY-03:02 202711.36 30-MAY-05:02 0.00 0.00 0.00
June 0.265561E+12 0.00 573.64 0.201746E+12 0.00 0.00 0.00 0.00 322630.92 23-JUN-05:02 218204.54 12-JUN-05:03 0.00 0.00 0.00
July 0.283916E+12 0.00 573.20 0.178471E+12 0.00 0.00 0.00 0.00 331090.40 22-JUL-05:03 205648.28 05-JUL-05:02 0.00 0.00 0.00
August 0.276710E+12 0.00 556.15 0.167952E+12 0.00 0.00 0.00 0.00 323165.85 12-AUG-03:02 192103.78 14-AUG-05:02 0.00 0.00 0.00
September 0.213524E+12 0.00 491.11 0.139667E+12 0.00 0.00 0.00 0.00 335060.70 11-SEP-03:02 185105.53 11-SEP-03:02 0.00 0.00 0.00
October 0.132816E+12 0.00 471.62 0.119173E+12 0.00 0.00 0.00 0.00 243803.48 04-OCT-03:02 161741.40 04-OCT-03:02 0.00 0.00 0.00
November 0.744814E+11 0.00 406.11 0.740300E+11 0.00 0.00 0.00 0.00 145290.04 10-NOV-06:02 112778.99 09-NOV-15:00 0.00 0.00 0.00
December 0.357410E+11 0.00 372.33 0.357410E+11 0.00 0.00 0.00 0.00 74196.35 01-DEC-15:00 74196.35 01-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.186218E+13 0.00 5714.91 0.145655E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.292588E+11 0.00 338.64 0.292482E+11 0.00 0.00 0.00 0.00 67572.36   67572.36   0.00 0.00 0.00
Maximum of Months 0.283916E+12 0.00 598.46 0.203960E+12 0.00 0.00 0.00 0.00 335060.70   218204.54   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.560333E+11 0.00 402.35 0.559598E+11 0.00 0.00 0.00 0.00 110961.60 18-JAN-04:03 91184.16 23-JAN-04:03 0.00 0.00 0.00
February 0.573217E+11 0.00 375.75 0.572663E+11 0.00 0.00 0.00 0.00 129214.42 25-FEB-04:02 108071.47 20-FEB-15:12 0.00 0.00 0.00
March 0.787844E+11 0.00 444.40 0.785347E+11 0.00 0.00 0.00 0.00 162720.99 11-MAR-04:02 102553.30 13-MAR-03:02 0.00 0.00 0.00
April 0.900437E+11 0.00 418.88 0.881115E+11 0.00 0.00 0.00 0.00 168329.96 27-APR-03:02 126911.21 16-APR-17:40 0.00 0.00 0.00
May 0.115380E+12 0.00 451.26 0.103035E+12 0.00 0.00 0.00 0.00 201736.51 22-MAY-03:02 133437.85 29-MAY-17:30 0.00 0.00 0.00
June 0.134888E+12 0.00 454.42 0.107085E+12 0.00 0.00 0.00 0.00 225203.45 26-JUN-03:02 131226.91 04-JUN-16:18 0.00 0.00 0.00
July 0.155844E+12 0.00 470.02 0.106407E+12 0.00 0.00 0.00 0.00 245465.76 30-JUL-20:57 121758.86 04-JUL-17:50 0.00 0.00 0.00
August 0.174314E+12 0.00 503.86 0.115266E+12 0.00 0.00 0.00 0.00 257505.02 27-AUG-14:59 107512.11 08-AUG-03:02 0.00 0.00 0.00
September 0.139122E+12 0.00 467.81 0.996875E+11 0.00 0.00 0.00 0.00 239604.66 11-SEP-00:22 111237.54 24-SEP-14:08 0.00 0.00 0.00
October 0.101533E+12 0.00 478.10 0.947397E+11 0.00 0.00 0.00 0.00 179649.53 04-OCT-03:02 125757.84 01-OCT-14:36 0.00 0.00 0.00
November 0.787329E+11 0.00 442.12 0.784526E+11 0.00 0.00 0.00 0.00 140973.37 09-NOV-04:03 109218.57 11-NOV-13:18 0.00 0.00 0.00
December 0.635985E+11 0.00 417.86 0.635899E+11 0.00 0.00 0.00 0.00 106326.79 30-DEC-04:02 96268.31 29-DEC-04:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.124560E+13 0.00 5326.83 0.104814E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.560333E+11 0.00 375.75 0.559598E+11 0.00 0.00 0.00 0.00 106326.79   91184.16   0.00 0.00 0.00
Maximum of Months 0.174314E+12 0.00 503.86 0.115266E+12 0.00 0.00 0.00 0.00 257505.02   133437.85   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.338687E+12 0.877633E+11 744.00 0.325039E+12 0.136477E+11 0.00 0.36 12-JAN-16:00 0.32 22-JAN-06:00 132584.48 17-JAN-17:00 127940.65 12-JAN-15:00 6872.97 17-JAN-17:00 41428.62 12-JAN-15:00 0.00
February 0.534019E+12 0.142106E+12 672.00 0.517130E+12 0.168886E+11 0.00 0.60 22-FEB-15:00 0.53 01-FEB-00:10 226157.43 24-FEB-17:00 220704.51 22-FEB-15:00 10353.56 27-FEB-09:40 77934.92 22-FEB-15:00 0.00
March 0.836897E+12 0.254946E+12 744.00 0.822943E+12 0.139534E+11 0.00 0.98 31-MAR-24:00 0.74 01-MAR-02:70 396209.03 31-MAR-24:00 393971.56 31-MAR-23:55 13898.93 05-MAR-06:00 136907.14 28-MAR-15:30 0.00
April 0.103528E+13 0.370554E+12 720.00 0.102909E+13 0.619589E+10 0.00 1.00 01-APR-08:20 0.42 30-APR-24:00 410074.23 25-APR-04:55 403756.52 30-APR-04:25 8780.38 26-APR-21:00 174123.26 15-APR-15:00 0.00
May 0.363541E+12 0.149095E+12 744.00 0.346709E+12 0.168320E+11 0.00 0.60 31-MAY-23:13 0.35 28-MAY-05:00 226648.48 31-MAY-23:03 213153.01 31-MAY-24:00 15211.74 22-MAY-23:10 79266.62 31-MAY-23:13 0.00
June 0.599562E+12 0.246185E+12 720.00 0.573831E+12 0.257310E+11 0.00 0.85 30-JUN-24:00 0.58 18-JUN-05:00 318783.06 30-JUN-23:02 307423.31 30-JUN-24:00 18595.09 28-JUN-13:30 127808.70 30-JUN-24:00 0.00
July 0.874908E+12 0.340176E+12 744.00 0.838308E+12 0.365997E+11 0.00 1.00 31-JUL-23:02 0.80 19-JUL-02:55 402165.42 31-JUL-24:00 390442.05 31-JUL-24:00 19572.30 18-JUL-08:30 158006.70 07-JUL-15:00 0.00
August 0.110066E+13 0.392627E+12 744.00 0.106513E+13 0.355226E+11 0.00 1.00 01-AUG-00:03 0.45 31-AUG-24:00 422167.53 10-AUG-14:00 405159.56 15-AUG-23:55 20781.92 25-AUG-16:00 166798.64 07-AUG-15:00 0.00
September 0.367475E+12 0.132707E+12 720.00 0.336224E+12 0.312510E+11 0.00 0.59 30-SEP-23:05 0.36 27-SEP-05:00 227309.79 30-SEP-23:05 213808.29 30-SEP-23:53 18116.48 12-SEP-16:00 76428.56 30-SEP-23:20 0.00
October 0.602836E+12 0.198279E+12 744.00 0.586451E+12 0.163847E+11 0.00 0.76 31-OCT-23:30 0.55 31-OCT-05:00 311062.02 31-OCT-24:00 302638.89 31-OCT-24:00 11516.79 13-OCT-08:30 102133.97 02-OCT-15:00 0.00
November 0.818523E+12 0.230316E+12 720.00 0.799030E+12 0.194939E+11 0.00 0.84 08-NOV-15:00 0.75 26-NOV-06:00 321970.29 24-NOV-08:15 314991.31 08-NOV-15:00 14619.93 23-NOV-08:00 119035.72 08-NOV-15:00 0.00
December 0.110010E+13 0.270608E+12 744.00 0.106551E+13 0.345844E+11 0.00 1.00 25-DEC-13:57 0.93 01-DEC-00:10 422262.40 22-DEC-06:03 404478.53 28-DEC-17:00 25569.76 22-DEC-06:03 130708.24 28-DEC-14:10 0.00
                                       
Annual Sum or Average 0.857248E+13 0.281536E+13 8760.00 0.830540E+13 0.267085E+12 0.00                         0.00
Minimum of Months 0.338687E+12 0.877633E+11 672.00 0.325039E+12 0.619589E+10 0.00 0.36   0.32   132584.48   127940.65   6872.97   41428.62   0.00
Maximum of Months 0.110066E+13 0.392627E+12 744.00 0.106551E+13 0.365997E+11 0.00 1.00   0.93   422262.40   405159.56   25569.76   174123.26   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.500855E+10 0.130589E+10 744.00 0.486377E+10 0.144779E+09 0.00 0.32 12-JAN-17:00 0.17 07-JAN-08:00 2535.93 12-JAN-17:00 2405.11 12-JAN-17:00 253.59 17-JAN-17:00 756.13 12-JAN-16:00 0.00
February 0.962832E+10 0.254379E+10 672.00 0.940246E+10 0.225860E+09 0.00 0.56 21-FEB-17:00 0.40 01-FEB-07:00 4586.17 21-FEB-17:00 4436.12 21-FEB-17:00 262.69 15-FEB-17:10 1515.15 22-FEB-15:00 0.00
March 0.162732E+11 0.486739E+10 744.00 0.159437E+11 0.329528E+09 0.00 0.90 31-MAR-24:00 0.63 01-MAR-07:00 7794.97 31-MAR-24:00 7695.35 31-MAR-23:55 336.17 30-MAR-16:10 2757.94 28-MAR-16:00 0.00
April 0.210003E+11 0.750660E+10 720.00 0.206930E+11 0.307348E+09 0.00 1.00 01-APR-15:00 0.39 30-APR-24:00 8548.31 16-APR-20:54 8320.25 16-APR-22:35 382.71 26-APR-08:00 3616.15 15-APR-15:00 0.00
May 0.725726E+10 0.287000E+10 744.00 0.659478E+10 0.662475E+09 0.00 0.56 31-MAY-23:03 0.28 13-MAY-07:00 4650.35 31-MAY-23:03 4083.37 31-MAY-24:00 643.08 22-MAY-23:10 1628.11 01-MAY-15:50 0.00
June 0.123709E+11 0.487687E+10 720.00 0.112895E+11 0.108139E+10 0.00 0.80 30-JUN-23:12 0.53 18-JUN-04:25 6545.17 30-JUN-23:02 6051.33 30-JUN-23:57 812.81 28-JUN-13:40 2579.17 08-JUN-16:00 0.00
July 0.182093E+11 0.679429E+10 744.00 0.166004E+11 0.160887E+10 0.00 1.00 31-JUL-23:02 0.75 19-JUL-03:02 8653.05 31-JUL-23:02 7870.11 31-JUL-24:00 846.46 18-JUL-08:20 3281.30 02-JUL-16:50 0.00
August 0.229816E+11 0.815018E+10 744.00 0.212870E+11 0.169453E+10 0.00 1.00 01-AUG-07:30 0.38 31-AUG-23:05 8877.56 10-AUG-14:10 8138.05 29-AUG-03:32 863.21 21-AUG-14:00 3470.31 07-AUG-15:00 0.00
September 0.739861E+10 0.254184E+10 720.00 0.612792E+10 0.127068E+10 0.00 0.55 30-SEP-23:05 0.30 27-SEP-06:00 4621.76 30-SEP-23:05 4051.24 30-SEP-23:47 734.98 12-SEP-16:00 1480.54 30-SEP-23:20 0.00
October 0.117609E+11 0.376527E+10 744.00 0.111429E+11 0.617990E+09 0.00 0.68 31-OCT-23:20 0.46 31-OCT-06:00 5988.36 31-OCT-23:10 5787.03 31-OCT-24:00 494.68 06-OCT-09:40 2067.73 02-OCT-15:10 0.00
November 0.156218E+11 0.433842E+10 720.00 0.153125E+11 0.309341E+09 0.00 0.80 08-NOV-16:20 0.63 25-NOV-08:00 6643.26 08-NOV-16:40 6394.67 08-NOV-16:30 283.16 08-NOV-20:00 2354.99 08-NOV-15:00 0.00
December 0.205933E+11 0.505868E+10 744.00 0.204236E+11 0.169681E+09 0.00 0.95 28-DEC-16:40 0.80 23-DEC-08:00 8318.76 28-DEC-17:00 8158.39 28-DEC-17:00 252.66 29-DEC-17:10 2585.35 28-DEC-15:00 0.00
                                       
Annual Sum or Average 0.168104E+12 0.546192E+11 8760.00 0.159682E+12 0.842248E+10 0.00                         0.00
Minimum of Months 0.500855E+10 0.130589E+10 672.00 0.486377E+10 0.144779E+09 0.00 0.32   0.17   2535.93   2405.11   252.66   756.13   0.00
Maximum of Months 0.229816E+11 0.815018E+10 744.00 0.212870E+11 0.169453E+10 0.00 1.00   0.80   8877.56   8320.25   863.21   3616.15   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.378506E+11 0.100677E+11 744.00 0.364888E+11 0.136175E+10 0.00 0.31 12-JAN-17:00 0.11 01-JAN-06:55 23519.28 13-JAN-17:00 22233.48 12-JAN-17:00 2444.23 17-JAN-17:00 6987.39 12-JAN-16:50 0.00
February 0.857714E+11 0.228533E+11 672.00 0.835400E+11 0.223139E+10 0.00 0.56 22-FEB-17:00 0.35 11-FEB-08:00 43267.32 22-FEB-17:00 41745.54 21-FEB-17:00 2601.68 15-FEB-17:00 14348.64 22-FEB-15:00 0.00
March 0.153635E+12 0.460445E+11 744.00 0.150352E+12 0.328374E+10 0.00 0.91 31-MAR-24:00 0.61 01-MAR-07:00 75278.30 31-MAR-24:00 74276.65 31-MAR-23:55 3339.79 10-MAR-17:10 26283.44 28-MAR-16:00 0.00
April 0.199385E+12 0.713424E+11 720.00 0.196304E+12 0.308105E+10 0.00 1.00 01-APR-14:50 0.33 30-APR-24:00 81280.53 12-APR-16:00 79024.97 12-APR-16:00 3826.54 26-APR-08:00 34468.43 15-APR-15:00 0.00
May 0.684750E+11 0.270851E+11 744.00 0.619288E+11 0.654623E+10 0.00 0.56 31-MAY-23:13 0.27 13-MAY-07:00 44872.84 31-MAY-23:03 39296.57 31-MAY-24:00 6293.99 22-MAY-23:20 15030.94 01-MAY-16:00 0.00
June 0.117971E+12 0.464575E+11 720.00 0.107217E+12 0.107537E+11 0.00 0.81 30-JUN-23:23 0.53 02-JUN-06:00 63359.21 30-JUN-23:02 58520.51 30-JUN-23:42 8092.84 28-JUN-13:30 24590.64 08-JUN-16:00 0.00
July 0.173886E+12 0.647873E+11 744.00 0.157845E+12 0.160410E+11 0.00 1.00 31-JUL-23:02 0.75 19-JUL-02:50 82778.59 31-JUL-23:02 75591.78 31-JUL-24:00 8439.38 18-JUL-08:20 30886.56 02-JUL-17:00 0.00
August 0.218200E+12 0.775549E+11 744.00 0.201224E+12 0.169754E+11 0.00 1.00 01-AUG-00:03 0.34 31-AUG-23:05 84519.27 10-AUG-14:10 76964.94 10-AUG-16:10 8605.14 21-AUG-14:00 33073.80 07-AUG-15:00 0.00
September 0.696018E+11 0.238924E+11 720.00 0.570511E+11 0.125507E+11 0.00 0.56 30-SEP-23:05 0.28 09-SEP-17:20 45100.20 30-SEP-23:05 39211.09 30-SEP-23:47 7275.45 12-SEP-16:00 14378.35 30-SEP-23:20 0.00
October 0.110715E+12 0.354976E+11 744.00 0.104585E+12 0.613008E+10 0.00 0.68 31-OCT-23:20 0.44 31-OCT-06:00 56464.50 31-OCT-23:10 54415.42 31-OCT-24:00 4936.58 06-OCT-09:40 19618.00 02-OCT-15:10 0.00
November 0.144834E+12 0.404091E+11 720.00 0.141754E+12 0.307967E+10 0.00 0.80 08-NOV-16:30 0.59 25-NOV-08:00 63051.60 08-NOV-16:50 60549.53 08-NOV-16:30 2791.21 08-NOV-20:00 22327.51 08-NOV-15:00 0.00
December 0.187626E+12 0.464298E+11 744.00 0.185929E+12 0.169760E+10 0.00 0.94 28-DEC-16:40 0.75 23-DEC-08:00 78455.51 28-DEC-17:00 76860.60 28-DEC-17:00 2516.77 29-DEC-17:10 24429.99 28-DEC-15:00 0.00
                                       
Annual Sum or Average 0.156795E+13 0.512422E+12 8760.00 0.148422E+13 0.837323E+11 0.00                         0.00
Minimum of Months 0.378506E+11 0.100677E+11 672.00 0.364888E+11 0.136175E+10 0.00 0.31   0.11   23519.28   22233.48   2444.23   6987.39   0.00
Maximum of Months 0.218200E+12 0.775549E+11 744.00 0.201224E+12 0.169754E+11 0.00 1.00   0.75   84519.27   79024.97   8605.14   34468.43   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.236917E+10 0.657129E+09 669.78 0.224348E+10 0.125685E+09 0.00 0.30 12-JAN-17:00 0.00 01-JAN-00:05 2366.30 12-JAN-17:00 2229.68 12-JAN-17:00 252.88 17-JAN-16:20 706.63 12-JAN-16:40 0.00
February 0.790104E+10 0.214177E+10 672.00 0.766512E+10 0.235918E+09 0.00 0.55 22-FEB-17:00 0.26 11-FEB-05:55 4374.65 22-FEB-17:00 4213.59 22-FEB-17:00 267.68 15-FEB-17:00 1458.53 22-FEB-15:00 0.00
March 0.151950E+11 0.460039E+10 744.00 0.148479E+11 0.347089E+09 0.00 0.89 31-MAR-24:00 0.55 01-MAR-08:00 7484.67 31-MAR-24:00 7377.29 31-MAR-23:55 341.73 10-MAR-17:10 2700.81 28-MAR-16:00 0.00
April 0.200991E+11 0.725302E+10 720.00 0.197737E+11 0.325387E+09 0.00 1.00 01-APR-16:50 0.33 30-APR-24:00 8328.97 16-APR-20:45 8058.99 16-APR-20:45 389.85 26-APR-08:00 3560.48 15-APR-15:00 0.00
May 0.708995E+10 0.281889E+10 744.00 0.641440E+10 0.675549E+09 0.00 0.55 31-MAY-23:13 0.26 13-MAY-07:00 4470.53 31-MAY-23:03 3904.77 31-MAY-24:00 640.61 31-MAY-23:03 1630.48 28-MAY-16:41 0.00
June 0.120234E+11 0.476283E+10 720.00 0.109277E+11 0.109569E+10 0.00 0.80 30-JUN-23:12 0.50 24-JUN-14:00 6403.03 30-JUN-23:02 5895.66 30-JUN-24:00 820.51 28-JUN-13:30 2573.10 11-JUN-16:50 0.00
July 0.176142E+11 0.660460E+10 744.00 0.159897E+11 0.162452E+10 0.00 0.99 31-JUL-23:02 0.73 19-JUL-02:55 8401.04 31-JUL-23:02 7621.05 31-JUL-24:00 850.97 18-JUL-08:20 3303.24 02-JUL-17:00 0.00
August 0.221336E+11 0.793704E+10 744.00 0.204100E+11 0.172357E+10 0.00 1.00 01-AUG-09:00 0.34 31-AUG-23:12 8626.26 10-AUG-14:10 7841.64 20-AUG-16:15 872.38 21-AUG-14:00 3415.70 07-AUG-15:00 0.00
September 0.704468E+10 0.243260E+10 720.00 0.577045E+10 0.127424E+10 0.00 0.55 30-SEP-23:05 0.26 09-SEP-17:12 4502.76 30-SEP-23:05 3904.67 30-SEP-23:34 734.59 12-SEP-16:00 1444.66 30-SEP-23:20 0.00
October 0.109998E+11 0.355879E+10 744.00 0.103688E+11 0.630952E+09 0.00 0.65 31-OCT-23:20 0.40 28-OCT-07:00 5526.58 31-OCT-23:10 5296.07 31-OCT-24:00 502.87 06-OCT-09:50 2024.74 02-OCT-15:10 0.00
November 0.139896E+11 0.395676E+10 720.00 0.136645E+11 0.325164E+09 0.00 0.78 08-NOV-16:20 0.50 26-NOV-07:30 6368.32 08-NOV-16:40 6114.37 08-NOV-16:30 285.92 08-NOV-20:00 2268.12 08-NOV-15:00 0.00
December 0.176063E+11 0.443145E+10 744.00 0.174211E+11 0.185240E+09 0.00 0.92 28-DEC-16:40 0.61 31-DEC-08:00 7856.84 28-DEC-17:00 7689.88 28-DEC-17:00 258.22 29-DEC-17:10 2462.46 28-DEC-15:00 0.00
                                       
Annual Sum or Average 0.154066E+12 0.511553E+11 8685.78 0.145497E+12 0.856900E+10 0.00                         0.00
Minimum of Months 0.236917E+10 0.657129E+09 669.78 0.224348E+10 0.125685E+09 0.00 0.30   0.00   2366.30   2229.68   252.88   706.63   0.00
Maximum of Months 0.221336E+11 0.793704E+10 744.00 0.204100E+11 0.172357E+10 0.00 1.00   0.73   8626.26   8058.99   872.38   3560.48   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.15 0.00 91.15 48.60 364.15 0.00 0.00 0.00
February 108.09 0.00 108.09 101.14 276.67 0.00 0.00 0.00
March 130.25 0.00 130.25 198.15 157.20 0.00 0.00 0.00
April 141.33 0.48 140.85 341.82 49.29 0.00 0.00 0.00
May 156.58 4.39 152.19 477.69 7.31 0.00 0.00 0.00
June 162.09 6.00 156.08 517.82 5.57 0.00 0.00 0.00
July 159.85 2.53 157.32 462.03 1.15 0.00 0.00 0.00
August 146.75 0.46 146.29 386.34 4.17 0.00 0.00 0.00
September 130.76 0.01 130.75 303.33 20.03 0.00 0.00 0.00
October 113.28 0.00 113.28 219.98 119.12 0.00 0.00 0.00
November 95.95 0.00 95.95 117.38 243.55 0.00 0.00 0.00
December 88.92 0.00 88.92 53.44 355.26 0.00 0.00 0.00
                 
Annual Sum or Average 127.18 1.16 126.02 269.80 133.04 0.00 0.00 0.00
Minimum of Months 88.92 0.00 88.92 48.60 1.15 0.00 0.00 0.00
Maximum of Months 162.09 6.00 157.32 517.82 364.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.15 0.00 91.15 48.60 364.15 0.00 0.00 0.00
February 108.09 0.00 108.09 101.14 276.67 0.00 0.00 0.00
March 130.24 0.00 130.24 198.15 157.20 0.00 0.00 0.00
April 141.33 0.48 140.85 341.82 49.29 0.00 0.00 0.00
May 156.58 4.39 152.18 477.69 7.31 0.00 0.00 0.00
June 162.08 6.00 156.08 517.82 5.57 0.00 0.00 0.00
July 159.85 2.53 157.32 462.02 1.15 0.00 0.00 0.00
August 146.75 0.46 146.29 386.34 4.17 0.00 0.00 0.00
September 130.76 0.01 130.75 303.33 20.02 0.00 0.00 0.00
October 113.28 0.00 113.28 219.98 119.11 0.00 0.00 0.00
November 95.95 0.00 95.95 117.38 243.55 0.00 0.00 0.00
December 88.92 0.00 88.92 53.44 355.26 0.00 0.00 0.00
                 
Annual Sum or Average 127.18 1.16 126.02 269.79 133.04 0.00 0.00 0.00
Minimum of Months 88.92 0.00 88.92 48.60 1.15 0.00 0.00 0.00
Maximum of Months 162.08 6.00 157.32 517.82 364.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.15 0.00 91.15 48.60 364.15 0.00 0.00 0.00
February 108.09 0.00 108.09 101.14 276.67 0.00 0.00 0.00
March 130.24 0.00 130.24 198.15 157.20 0.00 0.00 0.00
April 141.33 0.48 140.85 341.82 49.29 0.00 0.00 0.00
May 156.58 4.39 152.19 477.69 7.31 0.00 0.00 0.00
June 162.08 6.00 156.08 517.82 5.57 0.00 0.00 0.00
July 159.85 2.53 157.32 462.02 1.15 0.00 0.00 0.00
August 146.75 0.46 146.29 386.34 4.17 0.00 0.00 0.00
September 130.76 0.01 130.75 303.33 20.03 0.00 0.00 0.00
October 113.28 0.00 113.28 219.98 119.11 0.00 0.00 0.00
November 95.95 0.00 95.95 117.38 243.55 0.00 0.00 0.00
December 88.92 0.00 88.92 53.44 355.26 0.00 0.00 0.00
                 
Annual Sum or Average 127.18 1.16 126.02 269.80 133.04 0.00 0.00 0.00
Minimum of Months 88.92 0.00 88.92 48.60 1.15 0.00 0.00 0.00
Maximum of Months 162.08 6.00 157.32 517.82 364.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.15 0.00 91.15 48.60 364.15 0.00 0.00 0.00
February 108.09 0.00 108.09 101.14 276.67 0.00 0.00 0.00
March 130.24 0.00 130.24 198.15 157.20 0.00 0.00 0.00
April 141.33 0.48 140.85 341.82 49.29 0.00 0.00 0.00
May 156.58 4.39 152.18 477.69 7.31 0.00 0.00 0.00
June 162.08 6.00 156.08 517.82 5.57 0.00 0.00 0.00
July 159.85 2.53 157.32 462.02 1.15 0.00 0.00 0.00
August 146.75 0.46 146.29 386.34 4.17 0.00 0.00 0.00
September 130.76 0.01 130.75 303.33 20.02 0.00 0.00 0.00
October 113.28 0.00 113.28 219.98 119.11 0.00 0.00 0.00
November 95.95 0.00 95.95 117.38 243.55 0.00 0.00 0.00
December 88.92 0.00 88.92 53.44 355.26 0.00 0.00 0.00
                 
Annual Sum or Average 127.18 1.16 126.02 269.79 133.04 0.00 0.00 0.00
Minimum of Months 88.92 0.00 88.92 48.60 1.15 0.00 0.00 0.00
Maximum of Months 162.08 6.00 157.32 517.82 364.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.14 0.00 91.14 48.60 364.13 0.00 0.00 0.00
February 108.08 0.00 108.08 101.13 276.66 0.00 0.00 0.00
March 130.24 0.00 130.24 198.14 157.19 0.00 0.00 0.00
April 141.32 0.48 140.84 341.81 49.29 0.00 0.00 0.00
May 156.57 4.39 152.18 477.67 7.31 0.00 0.00 0.00
June 162.08 6.00 156.07 517.80 5.57 0.00 0.00 0.00
July 159.84 2.53 157.31 462.00 1.15 0.00 0.00 0.00
August 146.74 0.46 146.28 386.33 4.17 0.00 0.00 0.00
September 130.75 0.01 130.74 303.32 20.02 0.00 0.00 0.00
October 113.27 0.00 113.27 219.97 119.11 0.00 0.00 0.00
November 95.94 0.00 95.94 117.38 243.54 0.00 0.00 0.00
December 88.91 0.00 88.91 53.43 355.25 0.00 0.00 0.00
                 
Annual Sum or Average 127.17 1.16 126.01 269.78 133.03 0.00 0.00 0.00
Minimum of Months 88.91 0.00 88.91 48.60 1.15 0.00 0.00 0.00
Maximum of Months 162.08 6.00 157.31 517.80 364.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 216.96 87.08 129.87 219.21 365.79 0.00 0.00 0.00
February 263.57 108.82 154.76 341.29 280.55 0.00 0.00 0.00
March 321.53 132.72 188.81 524.69 160.38 0.00 0.00 0.00
April 382.54 178.36 204.18 782.09 49.31 0.00 0.00 0.00
May 376.52 166.93 209.59 887.54 7.39 0.00 0.00 0.00
June 306.44 101.68 204.76 805.15 5.23 0.00 0.00 0.00
July 257.56 54.39 203.17 666.55 0.76 0.00 0.00 0.00
August 232.07 40.39 191.68 565.49 2.44 0.00 0.00 0.00
September 247.94 69.14 178.79 521.24 19.75 0.00 0.00 0.00
October 271.22 109.55 161.66 502.66 124.82 0.00 0.00 0.00
November 240.47 103.22 137.25 356.57 247.42 0.00 0.00 0.00
December 209.68 83.08 126.60 230.83 354.54 0.00 0.00 0.00
                 
Annual Sum or Average 277.13 102.79 174.35 534.28 134.26 0.00 0.00 0.00
Minimum of Months 209.68 40.39 126.60 219.21 0.76 0.00 0.00 0.00
Maximum of Months 382.54 178.36 209.59 887.54 365.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 216.96 87.08 129.87 219.21 365.79 0.00 0.00 0.00
February 263.57 108.82 154.76 341.29 280.55 0.00 0.00 0.00
March 321.53 132.72 188.81 524.69 160.38 0.00 0.00 0.00
April 382.54 178.36 204.18 782.09 49.31 0.00 0.00 0.00
May 376.52 166.93 209.59 887.54 7.39 0.00 0.00 0.00
June 306.44 101.68 204.76 805.15 5.23 0.00 0.00 0.00
July 257.56 54.39 203.17 666.55 0.76 0.00 0.00 0.00
August 232.07 40.39 191.68 565.49 2.44 0.00 0.00 0.00
September 247.94 69.14 178.79 521.24 19.75 0.00 0.00 0.00
October 271.22 109.55 161.66 502.66 124.82 0.00 0.00 0.00
November 240.47 103.22 137.25 356.57 247.42 0.00 0.00 0.00
December 209.68 83.08 126.60 230.83 354.54 0.00 0.00 0.00
                 
Annual Sum or Average 277.13 102.79 174.35 534.28 134.26 0.00 0.00 0.00
Minimum of Months 209.68 40.39 126.60 219.21 0.76 0.00 0.00 0.00
Maximum of Months 382.54 178.36 209.59 887.54 365.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 216.95 87.08 129.87 219.21 365.78 0.00 0.00 0.00
February 263.57 108.81 154.75 341.28 280.54 0.00 0.00 0.00
March 321.53 132.71 188.81 524.68 160.37 0.00 0.00 0.00
April 382.53 178.36 204.18 782.08 49.31 0.00 0.00 0.00
May 376.52 166.93 209.59 887.52 7.39 0.00 0.00 0.00
June 306.43 101.67 204.76 805.13 5.23 0.00 0.00 0.00
July 257.55 54.39 203.16 666.54 0.76 0.00 0.00 0.00
August 232.06 40.38 191.68 565.48 2.44 0.00 0.00 0.00
September 247.93 69.14 178.79 521.23 19.75 0.00 0.00 0.00
October 271.21 109.55 161.66 502.65 124.82 0.00 0.00 0.00
November 240.47 103.22 137.25 356.56 247.42 0.00 0.00 0.00
December 209.68 83.08 126.60 230.83 354.54 0.00 0.00 0.00
                 
Annual Sum or Average 277.13 102.78 174.34 534.27 134.26 0.00 0.00 0.00
Minimum of Months 209.68 40.38 126.60 219.21 0.76 0.00 0.00 0.00
Maximum of Months 382.53 178.36 209.59 887.52 365.78 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 414.54 251.88 162.65 568.27 332.84 0.00 0.00 0.00
February 394.17 218.93 175.24 588.59 267.96 0.00 0.00 0.00
March 337.02 148.86 188.16 589.09 161.73 0.00 0.00 0.00
April 236.73 66.81 169.92 549.36 53.97 0.00 0.00 0.00
May 170.24 12.60 157.64 511.34 7.39 0.00 0.00 0.00
June 155.72 2.66 153.07 505.61 5.55 0.00 0.00 0.00
July 162.43 2.23 160.20 469.00 1.07 0.00 0.00 0.00
August 172.31 9.20 163.11 438.83 4.40 0.00 0.00 0.00
September 230.99 59.95 171.04 496.69 22.56 0.00 0.00 0.00
October 397.40 221.90 175.49 736.26 127.20 0.00 0.00 0.00
November 496.37 328.09 168.28 804.33 244.21 0.00 0.00 0.00
December 443.00 277.59 165.40 629.42 331.48 0.00 0.00 0.00
                 
Annual Sum or Average 300.37 132.90 167.47 573.61 129.43 0.00 0.00 0.00
Minimum of Months 155.72 2.23 153.07 438.83 1.07 0.00 0.00 0.00
Maximum of Months 496.37 328.09 188.16 804.33 332.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 414.53 251.88 162.65 568.26 332.84 0.00 0.00 0.00
February 394.16 218.93 175.23 588.58 267.96 0.00 0.00 0.00
March 337.02 148.86 188.16 589.08 161.73 0.00 0.00 0.00
April 236.72 66.81 169.91 549.36 53.97 0.00 0.00 0.00
May 170.24 12.60 157.64 511.34 7.39 0.00 0.00 0.00
June 155.72 2.66 153.07 505.61 5.55 0.00 0.00 0.00
July 162.43 2.23 160.20 469.00 1.07 0.00 0.00 0.00
August 172.31 9.20 163.10 438.83 4.40 0.00 0.00 0.00
September 230.99 59.95 171.04 496.69 22.56 0.00 0.00 0.00
October 397.39 221.90 175.49 736.26 127.20 0.00 0.00 0.00
November 496.37 328.09 168.28 804.32 244.21 0.00 0.00 0.00
December 442.99 277.59 165.40 629.42 331.48 0.00 0.00 0.00
                 
Annual Sum or Average 300.37 132.90 167.47 573.61 129.43 0.00 0.00 0.00
Minimum of Months 155.72 2.23 153.07 438.83 1.07 0.00 0.00 0.00
Maximum of Months 496.37 328.09 188.16 804.32 332.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 414.54 251.88 162.65 568.27 332.84 0.00 0.00 0.00
February 394.17 218.93 175.24 588.59 267.96 0.00 0.00 0.00
March 337.02 148.86 188.16 589.09 161.73 0.00 0.00 0.00
April 236.73 66.81 169.92 549.36 53.97 0.00 0.00 0.00
May 170.24 12.60 157.64 511.34 7.39 0.00 0.00 0.00
June 155.72 2.66 153.07 505.61 5.55 0.00 0.00 0.00
July 162.43 2.23 160.20 469.00 1.07 0.00 0.00 0.00
August 172.31 9.20 163.11 438.83 4.40 0.00 0.00 0.00
September 230.99 59.95 171.04 496.69 22.56 0.00 0.00 0.00
October 397.40 221.90 175.49 736.26 127.20 0.00 0.00 0.00
November 496.37 328.09 168.28 804.33 244.21 0.00 0.00 0.00
December 443.00 277.59 165.40 629.42 331.48 0.00 0.00 0.00
                 
Annual Sum or Average 300.37 132.90 167.47 573.61 129.43 0.00 0.00 0.00
Minimum of Months 155.72 2.23 153.07 438.83 1.07 0.00 0.00 0.00
Maximum of Months 496.37 328.09 188.16 804.33 332.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 414.53 251.88 162.65 568.26 332.84 0.00 0.00 0.00
February 394.16 218.93 175.23 588.58 267.96 0.00 0.00 0.00
March 337.02 148.86 188.16 589.08 161.73 0.00 0.00 0.00
April 236.72 66.81 169.91 549.36 53.97 0.00 0.00 0.00
May 170.24 12.60 157.64 511.34 7.39 0.00 0.00 0.00
June 155.72 2.66 153.07 505.61 5.55 0.00 0.00 0.00
July 162.43 2.23 160.20 469.00 1.07 0.00 0.00 0.00
August 172.31 9.20 163.10 438.83 4.40 0.00 0.00 0.00
September 230.99 59.95 171.04 496.69 22.56 0.00 0.00 0.00
October 397.39 221.90 175.49 736.26 127.20 0.00 0.00 0.00
November 496.37 328.09 168.28 804.32 244.21 0.00 0.00 0.00
December 442.99 277.59 165.40 629.42 331.48 0.00 0.00 0.00
                 
Annual Sum or Average 300.37 132.90 167.47 573.61 129.43 0.00 0.00 0.00
Minimum of Months 155.72 2.23 153.07 438.83 1.07 0.00 0.00 0.00
Maximum of Months 496.37 328.09 188.16 804.32 332.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 414.52 251.87 162.65 568.24 332.82 0.00 0.00 0.00
February 394.15 218.92 175.23 588.56 267.95 0.00 0.00 0.00
March 337.01 148.85 188.15 589.06 161.72 0.00 0.00 0.00
April 236.72 66.81 169.91 549.34 53.97 0.00 0.00 0.00
May 170.23 12.60 157.63 511.32 7.39 0.00 0.00 0.00
June 155.72 2.66 153.06 505.59 5.55 0.00 0.00 0.00
July 162.43 2.23 160.19 468.98 1.07 0.00 0.00 0.00
August 172.30 9.20 163.10 438.81 4.40 0.00 0.00 0.00
September 230.98 59.95 171.03 496.67 22.55 0.00 0.00 0.00
October 397.38 221.89 175.49 736.23 127.19 0.00 0.00 0.00
November 496.35 328.07 168.27 804.29 244.20 0.00 0.00 0.00
December 442.98 277.58 165.40 629.39 331.46 0.00 0.00 0.00
                 
Annual Sum or Average 300.36 132.89 167.47 573.59 129.42 0.00 0.00 0.00
Minimum of Months 155.72 2.23 153.06 438.81 1.07 0.00 0.00 0.00
Maximum of Months 496.35 328.07 188.15 804.29 332.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 212.26 82.60 129.65 235.54 421.97 0.00 0.00 0.00
February 242.72 89.45 153.27 316.69 339.87 0.00 0.00 0.00
March 314.75 125.82 188.93 507.04 208.81 0.00 0.00 0.00
April 382.57 179.41 203.16 753.74 85.05 0.00 0.00 0.00
May 362.26 153.66 208.60 847.23 13.37 0.00 0.00 0.00
June 340.26 132.17 208.09 834.80 10.77 0.00 0.00 0.00
July 252.49 49.11 203.38 613.79 4.29 0.00 0.00 0.00
August 231.88 41.21 190.67 513.19 16.98 0.00 0.00 0.00
September 254.90 74.83 180.07 520.96 33.50 0.00 0.00 0.00
October 265.31 105.65 159.67 487.26 157.26 0.00 0.00 0.00
November 240.02 102.29 137.72 360.71 309.08 0.00 0.00 0.00
December 205.39 78.32 127.07 225.55 441.14 0.00 0.00 0.00
                 
Annual Sum or Average 275.35 101.08 174.27 518.60 169.44 0.00 0.00 0.00
Minimum of Months 205.39 41.21 127.07 225.55 4.29 0.00 0.00 0.00
Maximum of Months 382.57 179.41 208.60 847.23 441.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 212.26 82.60 129.65 235.54 421.97 0.00 0.00 0.00
February 242.72 89.45 153.27 316.69 339.87 0.00 0.00 0.00
March 314.75 125.82 188.93 507.04 208.81 0.00 0.00 0.00
April 382.57 179.41 203.16 753.74 85.05 0.00 0.00 0.00
May 362.26 153.66 208.60 847.23 13.37 0.00 0.00 0.00
June 340.26 132.17 208.09 834.80 10.77 0.00 0.00 0.00
July 252.49 49.11 203.38 613.79 4.29 0.00 0.00 0.00
August 231.88 41.21 190.67 513.19 16.98 0.00 0.00 0.00
September 254.90 74.83 180.07 520.96 33.50 0.00 0.00 0.00
October 265.31 105.65 159.67 487.26 157.26 0.00 0.00 0.00
November 240.02 102.29 137.72 360.71 309.08 0.00 0.00 0.00
December 205.39 78.32 127.07 225.55 441.14 0.00 0.00 0.00
                 
Annual Sum or Average 275.35 101.08 174.27 518.60 169.44 0.00 0.00 0.00
Minimum of Months 205.39 41.21 127.07 225.55 4.29 0.00 0.00 0.00
Maximum of Months 382.57 179.41 208.60 847.23 441.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 212.25 82.60 129.65 235.53 421.97 0.00 0.00 0.00
February 242.72 89.45 153.27 316.68 339.86 0.00 0.00 0.00
March 314.74 125.81 188.93 507.03 208.81 0.00 0.00 0.00
April 382.56 179.41 203.16 753.72 85.05 0.00 0.00 0.00
May 362.25 153.66 208.59 847.21 13.37 0.00 0.00 0.00
June 340.25 132.16 208.09 834.78 10.77 0.00 0.00 0.00
July 252.48 49.11 203.38 613.77 4.29 0.00 0.00 0.00
August 231.88 41.21 190.67 513.18 16.98 0.00 0.00 0.00
September 254.90 74.83 180.07 520.95 33.50 0.00 0.00 0.00
October 265.31 105.65 159.66 487.25 157.25 0.00 0.00 0.00
November 240.02 102.29 137.72 360.70 309.08 0.00 0.00 0.00
December 205.38 78.32 127.07 225.54 441.13 0.00 0.00 0.00
                 
Annual Sum or Average 275.35 101.08 174.27 518.59 169.44 0.00 0.00 0.00
Minimum of Months 205.38 41.21 127.07 225.54 4.29 0.00 0.00 0.00
Maximum of Months 382.56 179.41 208.59 847.21 441.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 455.75 0.00 455.75 294.09 1637.52 0.00 0.00 0.00
February 540.44 0.00 540.44 551.59 1259.55 0.00 0.00 0.00
March 651.23 0.00 651.23 1017.26 748.95 0.00 0.00 0.00
April 706.64 2.40 704.24 1746.58 251.70 0.00 0.00 0.00
May 782.90 21.97 760.93 2412.64 38.28 0.00 0.00 0.00
June 810.43 30.02 780.41 2610.30 31.32 0.00 0.00 0.00
July 799.27 12.66 786.61 2325.30 8.43 0.00 0.00 0.00
August 733.75 2.29 731.46 1962.47 27.74 0.00 0.00 0.00
September 653.79 0.05 653.75 1528.59 106.50 0.00 0.00 0.00
October 566.40 0.00 566.40 1124.93 578.01 0.00 0.00 0.00
November 479.74 0.00 479.74 630.87 1120.57 0.00 0.00 0.00
December 444.59 0.00 444.59 333.15 1569.12 0.00 0.00 0.00
                 
Annual Sum or Average 635.89 5.80 630.09 1382.19 612.11 0.00 0.00 0.00
Minimum of Months 444.59 0.00 444.59 294.09 8.43 0.00 0.00 0.00
Maximum of Months 810.43 30.02 786.61 2610.30 1637.52 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 650.86 261.25 389.61 690.14 1014.34 0.00 0.00 0.00
February 790.71 326.44 464.27 1036.29 798.87 0.00 0.00 0.00
March 964.58 398.15 566.44 1567.94 488.92 0.00 0.00 0.00
April 1147.61 535.07 612.53 2330.49 175.70 0.00 0.00 0.00
May 1129.56 500.78 628.77 2654.06 25.82 0.00 0.00 0.00
June 919.31 305.03 614.29 2401.88 20.78 0.00 0.00 0.00
July 772.66 163.16 609.49 1976.00 4.83 0.00 0.00 0.00
August 696.20 121.15 575.04 1671.30 18.40 0.00 0.00 0.00
September 743.81 207.43 536.38 1555.82 72.45 0.00 0.00 0.00
October 813.64 328.66 484.98 1504.40 385.33 0.00 0.00 0.00
November 721.41 309.66 411.75 1079.14 719.30 0.00 0.00 0.00
December 629.04 249.23 379.81 724.92 991.98 0.00 0.00 0.00
                 
Annual Sum or Average 831.39 308.36 523.03 1601.34 391.32 0.00 0.00 0.00
Minimum of Months 629.04 121.15 379.81 690.14 4.83 0.00 0.00 0.00
Maximum of Months 1147.61 535.07 628.77 2654.06 1014.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2072.73 1259.44 813.28 2825.23 1639.43 0.00 0.00 0.00
February 1970.86 1094.67 876.19 2927.25 1314.03 0.00 0.00 0.00
March 1685.13 744.31 940.82 2935.71 810.24 0.00 0.00 0.00
April 1183.64 334.06 849.58 2757.84 284.37 0.00 0.00 0.00
May 851.20 63.01 788.18 2578.84 38.38 0.00 0.00 0.00
June 778.63 13.29 765.34 2550.64 30.88 0.00 0.00 0.00
July 812.18 11.17 801.01 2362.08 7.47 0.00 0.00 0.00
August 861.55 46.01 815.54 2216.64 29.02 0.00 0.00 0.00
September 1154.98 299.78 855.20 2478.89 124.70 0.00 0.00 0.00
October 1987.02 1109.54 877.48 3667.91 650.56 0.00 0.00 0.00
November 2481.90 1640.48 841.42 4005.99 1212.62 0.00 0.00 0.00
December 2215.03 1388.00 827.03 3144.57 1610.62 0.00 0.00 0.00
                 
Annual Sum or Average 1501.89 664.51 837.38 2869.66 643.09 0.00 0.00 0.00
Minimum of Months 778.63 11.17 765.34 2216.64 7.47 0.00 0.00 0.00
Maximum of Months 2481.90 1640.48 940.82 4005.99 1639.43 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 636.76 247.80 388.96 746.80 1123.44 0.00 0.00 0.00
February 728.15 268.34 459.81 994.36 884.19 0.00 0.00 0.00
March 944.23 377.44 566.79 1557.88 549.28 0.00 0.00 0.00
April 1147.70 538.23 609.47 2322.74 206.38 0.00 0.00 0.00
May 1086.77 460.98 625.78 2570.25 35.31 0.00 0.00 0.00
June 1020.76 396.49 624.27 2555.83 27.12 0.00 0.00 0.00
July 757.46 147.33 610.13 1913.74 7.80 0.00 0.00 0.00
August 695.65 123.64 572.01 1646.20 24.10 0.00 0.00 0.00
September 764.70 224.49 540.20 1584.15 87.72 0.00 0.00 0.00
October 795.93 316.94 478.99 1490.17 424.86 0.00 0.00 0.00
November 720.05 306.88 413.17 1131.30 797.39 0.00 0.00 0.00
December 616.15 234.95 381.20 751.00 1084.23 0.00 0.00 0.00
                 
Annual Sum or Average 826.04 303.23 522.82 1607.18 435.71 0.00 0.00 0.00
Minimum of Months 616.15 123.64 381.20 746.80 7.80 0.00 0.00 0.00
Maximum of Months 1147.70 538.23 625.78 2570.25 1123.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 455.75 0.00 455.75 350.80 1434.86 0.00 0.00 0.00
February 540.44 0.00 540.44 592.24 1147.75 0.00 0.00 0.00
March 651.23 0.00 651.23 1024.00 714.46 0.00 0.00 0.00
April 706.64 2.40 704.24 1722.45 248.57 0.00 0.00 0.00
May 782.90 21.97 760.93 2370.19 40.79 0.00 0.00 0.00
June 810.43 30.02 780.41 2566.82 33.79 0.00 0.00 0.00
July 799.27 12.66 786.61 2280.58 8.74 0.00 0.00 0.00
August 733.75 2.29 731.46 1926.58 30.35 0.00 0.00 0.00
September 653.79 0.05 653.75 1510.04 107.23 0.00 0.00 0.00
October 566.40 0.00 566.40 1122.00 558.62 0.00 0.00 0.00
November 479.74 0.00 479.74 662.03 1037.83 0.00 0.00 0.00
December 444.59 0.00 444.59 387.84 1401.08 0.00 0.00 0.00
                 
Annual Sum or Average 635.89 5.80 630.09 1380.12 561.14 0.00 0.00 0.00
Minimum of Months 444.59 0.00 444.59 350.80 8.74 0.00 0.00 0.00
Maximum of Months 810.43 30.02 786.61 2566.82 1434.86 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 650.86 261.25 389.61 742.42 902.50 0.00 0.00 0.00
February 790.71 326.44 464.27 1062.29 745.35 0.00 0.00 0.00
March 964.58 398.15 566.44 1565.65 477.85 0.00 0.00 0.00
April 1147.61 535.07 612.53 2309.11 177.69 0.00 0.00 0.00
May 1129.56 500.78 628.77 2619.68 28.56 0.00 0.00 0.00
June 919.31 305.03 614.29 2367.68 22.89 0.00 0.00 0.00
July 772.66 163.16 609.49 1941.60 4.98 0.00 0.00 0.00
August 696.20 121.15 575.04 1644.30 20.47 0.00 0.00 0.00
September 743.81 207.43 536.38 1539.92 74.79 0.00 0.00 0.00
October 813.64 328.66 484.98 1497.75 380.59 0.00 0.00 0.00
November 721.41 309.66 411.75 1094.99 683.46 0.00 0.00 0.00
December 629.04 249.23 379.81 769.15 904.03 0.00 0.00 0.00
                 
Annual Sum or Average 831.39 308.36 523.03 1598.06 366.91 0.00 0.00 0.00
Minimum of Months 629.04 121.15 379.81 742.42 4.98 0.00 0.00 0.00
Maximum of Months 1147.61 535.07 628.77 2619.68 904.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2072.73 1259.44 813.28 2887.24 1472.64 0.00 0.00 0.00
February 1970.86 1094.67 876.19 2953.51 1229.30 0.00 0.00 0.00
March 1685.13 744.31 940.82 2929.66 788.87 0.00 0.00 0.00
April 1183.64 334.06 849.58 2729.93 284.80 0.00 0.00 0.00
May 851.20 63.01 788.18 2535.53 41.03 0.00 0.00 0.00
June 778.63 13.29 765.34 2506.51 33.42 0.00 0.00 0.00
July 812.18 11.17 801.01 2316.77 7.63 0.00 0.00 0.00
August 861.55 46.01 815.54 2180.37 31.87 0.00 0.00 0.00
September 1154.98 299.78 855.20 2456.72 127.69 0.00 0.00 0.00
October 1987.02 1109.54 877.48 3655.02 643.56 0.00 0.00 0.00
November 2481.90 1640.48 841.42 4015.35 1161.92 0.00 0.00 0.00
December 2215.03 1388.00 827.03 3195.93 1484.13 0.00 0.00 0.00
                 
Annual Sum or Average 1501.89 664.51 837.38 2862.11 606.07 0.00 0.00 0.00
Minimum of Months 778.63 11.17 765.34 2180.37 7.63 0.00 0.00 0.00
Maximum of Months 2481.90 1640.48 940.82 4015.35 1484.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 636.76 247.80 388.96 776.40 1014.22 0.00 0.00 0.00
February 728.15 268.34 459.81 1011.72 825.63 0.00 0.00 0.00
March 944.23 377.44 566.79 1556.72 532.74 0.00 0.00 0.00
April 1147.70 538.23 609.47 2305.30 205.49 0.00 0.00 0.00
May 1086.77 460.98 625.78 2544.10 36.85 0.00 0.00 0.00
June 1020.76 396.49 624.27 2528.42 28.35 0.00 0.00 0.00
July 757.46 147.33 610.13 1887.98 7.82 0.00 0.00 0.00
August 695.65 123.64 572.01 1626.04 25.49 0.00 0.00 0.00
September 764.70 224.49 540.20 1572.11 87.88 0.00 0.00 0.00
October 795.93 316.94 478.99 1485.74 415.53 0.00 0.00 0.00
November 720.05 306.88 413.17 1143.14 755.85 0.00 0.00 0.00
December 616.15 234.95 381.20 778.94 994.79 0.00 0.00 0.00
                 
Annual Sum or Average 826.04 303.23 522.82 1603.10 409.03 0.00 0.00 0.00
Minimum of Months 616.15 123.64 381.20 776.40 7.82 0.00 0.00 0.00
Maximum of Months 1147.70 538.23 625.78 2544.10 1014.22 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244134E+09 0.00 0.244134E+09 0.130182E+09 0.975338E+09
February 0.261485E+09 0.00 0.261485E+09 0.244673E+09 0.669321E+09
March 0.348851E+09 0.00 0.348851E+09 0.530726E+09 0.421036E+09
April 0.366321E+09 1242306.39 0.365078E+09 0.886010E+09 0.127767E+09
May 0.419386E+09 11768647.88 0.407617E+09 0.127944E+10 19589653.05
June 0.420126E+09 15561451.75 0.404565E+09 0.134220E+10 14444425.28
July 0.428151E+09 6779998.49 0.421371E+09 0.123749E+10 3067051.66
August 0.393055E+09 1224970.50 0.391830E+09 0.103478E+10 11160836.65
September 0.338926E+09 23798.53 0.338902E+09 0.786234E+09 51906013.73
October 0.303407E+09 0.00 0.303407E+09 0.589186E+09 0.319039E+09
November 0.248699E+09 0.00 0.248699E+09 0.304258E+09 0.631275E+09
December 0.238157E+09 0.00 0.238157E+09 0.143126E+09 0.951538E+09
           
Annual Sum or Average 0.401070E+10 36601173.55 0.397410E+10 0.850831E+10 0.419548E+10
Minimum of Months 0.238157E+09 0.00 0.238157E+09 0.130182E+09 3067051.66
Maximum of Months 0.428151E+09 15561451.75 0.421371E+09 0.134220E+10 0.975338E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244130E+09 0.00 0.244130E+09 0.130179E+09 0.975336E+09
February 0.261481E+09 0.00 0.261481E+09 0.244669E+09 0.669319E+09
March 0.348846E+09 0.00 0.348846E+09 0.530720E+09 0.421033E+09
April 0.366316E+09 1242279.08 0.365074E+09 0.886006E+09 0.127765E+09
May 0.419380E+09 11768389.16 0.407612E+09 0.127944E+10 19588960.19
June 0.420121E+09 15561109.65 0.404560E+09 0.134219E+10 14444184.46
July 0.428145E+09 6779849.44 0.421365E+09 0.123748E+10 3066927.04
August 0.393049E+09 1224943.57 0.391824E+09 0.103478E+10 11160486.79
September 0.338921E+09 23798.01 0.338897E+09 0.786228E+09 51904656.19
October 0.303403E+09 0.00 0.303403E+09 0.589182E+09 0.319036E+09
November 0.248696E+09 0.00 0.248696E+09 0.304255E+09 0.631271E+09
December 0.238154E+09 0.00 0.238154E+09 0.143123E+09 0.951535E+09
           
Annual Sum or Average 0.401064E+10 36600368.92 0.397404E+10 0.850825E+10 0.419546E+10
Minimum of Months 0.238154E+09 0.00 0.238154E+09 0.130179E+09 3066927.04
Maximum of Months 0.428145E+09 15561109.65 0.421365E+09 0.134219E+10 0.975336E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244132E+09 0.00 0.244132E+09 0.130180E+09 0.975337E+09
February 0.261483E+09 0.00 0.261483E+09 0.244671E+09 0.669320E+09
March 0.348848E+09 0.00 0.348848E+09 0.530722E+09 0.421034E+09
April 0.366318E+09 1242288.19 0.365075E+09 0.886008E+09 0.127765E+09
May 0.419382E+09 11768475.40 0.407614E+09 0.127944E+10 19589191.15
June 0.420122E+09 15561223.69 0.404561E+09 0.134220E+10 14444264.73
July 0.428147E+09 6779899.12 0.421367E+09 0.123748E+10 3066968.58
August 0.393051E+09 1224952.55 0.391826E+09 0.103478E+10 11160603.41
September 0.338923E+09 23798.18 0.338899E+09 0.786230E+09 51905108.69
October 0.303405E+09 0.00 0.303405E+09 0.589183E+09 0.319037E+09
November 0.248697E+09 0.00 0.248697E+09 0.304256E+09 0.631272E+09
December 0.238155E+09 0.00 0.238155E+09 0.143124E+09 0.951536E+09
           
Annual Sum or Average 0.401066E+10 36600637.13 0.397406E+10 0.850827E+10 0.419547E+10
Minimum of Months 0.238155E+09 0.00 0.238155E+09 0.130180E+09 3066968.58
Maximum of Months 0.428147E+09 15561223.69 0.421367E+09 0.134220E+10 0.975337E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244130E+09 0.00 0.244130E+09 0.130179E+09 0.975336E+09
February 0.261481E+09 0.00 0.261481E+09 0.244669E+09 0.669319E+09
March 0.348846E+09 0.00 0.348846E+09 0.530720E+09 0.421033E+09
April 0.366316E+09 1242279.08 0.365074E+09 0.886006E+09 0.127765E+09
May 0.419380E+09 11768389.16 0.407612E+09 0.127944E+10 19588960.19
June 0.420121E+09 15561109.65 0.404560E+09 0.134219E+10 14444184.46
July 0.428145E+09 6779849.44 0.421365E+09 0.123748E+10 3066927.04
August 0.393049E+09 1224943.57 0.391824E+09 0.103478E+10 11160486.79
September 0.338921E+09 23798.01 0.338897E+09 0.786228E+09 51904656.19
October 0.303403E+09 0.00 0.303403E+09 0.589182E+09 0.319036E+09
November 0.248696E+09 0.00 0.248696E+09 0.304255E+09 0.631271E+09
December 0.238154E+09 0.00 0.238154E+09 0.143123E+09 0.951535E+09
           
Annual Sum or Average 0.401064E+10 36600368.92 0.397404E+10 0.850825E+10 0.419546E+10
Minimum of Months 0.238154E+09 0.00 0.238154E+09 0.130179E+09 3066927.04
Maximum of Months 0.428145E+09 15561109.65 0.421365E+09 0.134219E+10 0.975336E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244121E+09 0.00 0.244121E+09 0.130174E+09 0.975297E+09
February 0.261472E+09 0.00 0.261472E+09 0.244660E+09 0.669292E+09
March 0.348833E+09 0.00 0.348833E+09 0.530700E+09 0.421016E+09
April 0.366302E+09 1242233.56 0.365060E+09 0.885971E+09 0.127760E+09
May 0.419364E+09 11767957.96 0.407596E+09 0.127939E+10 19588286.14
June 0.420105E+09 15560539.49 0.404544E+09 0.134214E+10 14443642.43
July 0.428128E+09 6779601.02 0.421349E+09 0.123743E+10 3066824.20
August 0.393034E+09 1224898.69 0.391809E+09 0.103474E+10 11160095.28
September 0.338908E+09 23797.13 0.338884E+09 0.786197E+09 51902790.44
October 0.303392E+09 0.00 0.303392E+09 0.589159E+09 0.319023E+09
November 0.248686E+09 0.00 0.248686E+09 0.304244E+09 0.631246E+09
December 0.238145E+09 0.00 0.238145E+09 0.143118E+09 0.951497E+09
           
Annual Sum or Average 0.401049E+10 36599027.86 0.397389E+10 0.850792E+10 0.419529E+10
Minimum of Months 0.238145E+09 0.00 0.238145E+09 0.130174E+09 3066824.20
Maximum of Months 0.428128E+09 15560539.49 0.421349E+09 0.134214E+10 0.975297E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.581093E+09 0.233243E+09 0.347850E+09 0.587138E+09 0.979722E+09
February 0.637636E+09 0.263246E+09 0.374390E+09 0.825649E+09 0.678698E+09
March 0.861189E+09 0.355469E+09 0.505720E+09 0.140533E+10 0.429551E+09
April 0.991541E+09 0.462307E+09 0.529234E+09 0.202718E+10 0.127813E+09
May 0.100848E+10 0.447105E+09 0.561375E+09 0.237718E+10 19805665.93
June 0.794294E+09 0.263546E+09 0.530748E+09 0.208694E+10 13560202.90
July 0.689836E+09 0.145675E+09 0.544161E+09 0.178528E+10 2046330.05
August 0.621571E+09 0.108168E+09 0.513403E+09 0.151462E+10 6530810.10
September 0.642656E+09 0.179221E+09 0.463435E+09 0.135105E+10 51188234.25
October 0.726423E+09 0.293427E+09 0.432996E+09 0.134633E+10 0.334320E+09
November 0.623303E+09 0.267550E+09 0.355753E+09 0.924229E+09 0.641322E+09
December 0.561610E+09 0.222513E+09 0.339097E+09 0.618259E+09 0.949605E+09
           
Annual Sum or Average 0.873963E+10 0.324147E+10 0.549816E+10 0.168492E+11 0.423416E+10
Minimum of Months 0.561610E+09 0.108168E+09 0.339097E+09 0.587138E+09 2046330.05
Maximum of Months 0.100848E+10 0.462307E+09 0.561375E+09 0.237718E+10 0.979722E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.581093E+09 0.233243E+09 0.347850E+09 0.587138E+09 0.979722E+09
February 0.637636E+09 0.263246E+09 0.374390E+09 0.825649E+09 0.678698E+09
March 0.861189E+09 0.355469E+09 0.505720E+09 0.140533E+10 0.429551E+09
April 0.991541E+09 0.462307E+09 0.529234E+09 0.202718E+10 0.127813E+09
May 0.100848E+10 0.447105E+09 0.561375E+09 0.237718E+10 19805665.93
June 0.794294E+09 0.263546E+09 0.530748E+09 0.208694E+10 13560202.90
July 0.689836E+09 0.145675E+09 0.544161E+09 0.178528E+10 2046330.05
August 0.621571E+09 0.108168E+09 0.513403E+09 0.151462E+10 6530810.10
September 0.642656E+09 0.179221E+09 0.463435E+09 0.135105E+10 51188234.25
October 0.726423E+09 0.293427E+09 0.432996E+09 0.134633E+10 0.334320E+09
November 0.623303E+09 0.267550E+09 0.355753E+09 0.924229E+09 0.641322E+09
December 0.561610E+09 0.222513E+09 0.339097E+09 0.618259E+09 0.949605E+09
           
Annual Sum or Average 0.873963E+10 0.324147E+10 0.549816E+10 0.168492E+11 0.423416E+10
Minimum of Months 0.561610E+09 0.108168E+09 0.339097E+09 0.587138E+09 2046330.05
Maximum of Months 0.100848E+10 0.462307E+09 0.561375E+09 0.237718E+10 0.979722E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.581082E+09 0.233238E+09 0.347844E+09 0.587127E+09 0.979704E+09
February 0.637624E+09 0.263241E+09 0.374383E+09 0.825634E+09 0.678685E+09
March 0.861174E+09 0.355463E+09 0.505711E+09 0.140530E+10 0.429543E+09
April 0.991523E+09 0.462299E+09 0.529224E+09 0.202714E+10 0.127810E+09
May 0.100846E+10 0.447097E+09 0.561365E+09 0.237714E+10 19805304.04
June 0.794279E+09 0.263541E+09 0.530738E+09 0.208690E+10 13559955.12
July 0.689824E+09 0.145672E+09 0.544151E+09 0.178525E+10 2046292.66
August 0.621560E+09 0.108166E+09 0.513394E+09 0.151459E+10 6530690.77
September 0.642644E+09 0.179218E+09 0.463427E+09 0.135102E+10 51187298.93
October 0.726410E+09 0.293422E+09 0.432988E+09 0.134631E+10 0.334314E+09
November 0.623291E+09 0.267545E+09 0.355746E+09 0.924212E+09 0.641311E+09
December 0.561600E+09 0.222509E+09 0.339091E+09 0.618248E+09 0.949588E+09
           
Annual Sum or Average 0.873947E+10 0.324141E+10 0.549806E+10 0.168489E+11 0.423408E+10
Minimum of Months 0.561600E+09 0.108166E+09 0.339091E+09 0.587127E+09 2046292.66
Maximum of Months 0.100846E+10 0.462299E+09 0.561365E+09 0.237714E+10 0.979704E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111030E+10 0.674644E+09 0.435654E+09 0.152205E+10 0.891470E+09
February 0.953565E+09 0.529635E+09 0.423930E+09 0.142391E+10 0.648247E+09
March 0.902678E+09 0.398704E+09 0.503975E+09 0.157781E+10 0.433181E+09
April 0.613594E+09 0.173173E+09 0.440420E+09 0.142394E+10 0.139887E+09
May 0.455965E+09 33753370.59 0.422212E+09 0.136958E+10 19805066.96
June 0.403636E+09 6887849.73 0.396748E+09 0.131054E+10 14387328.12
July 0.435064E+09 5983889.20 0.429080E+09 0.125618E+10 2853905.27
August 0.461510E+09 24647909.05 0.436862E+09 0.117537E+10 11776735.47
September 0.598732E+09 0.155401E+09 0.443331E+09 0.128741E+10 58464256.17
October 0.106439E+10 0.594348E+09 0.470041E+09 0.197201E+10 0.340683E+09
November 0.128659E+10 0.850407E+09 0.436184E+09 0.208482E+10 0.632988E+09
December 0.118652E+10 0.743507E+09 0.443017E+09 0.168584E+10 0.887826E+09
           
Annual Sum or Average 0.947255E+10 0.419109E+10 0.528145E+10 0.180895E+11 0.408157E+10
Minimum of Months 0.403636E+09 5983889.20 0.396748E+09 0.117537E+10 2853905.27
Maximum of Months 0.128659E+10 0.850407E+09 0.503975E+09 0.208482E+10 0.891470E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111029E+10 0.674639E+09 0.435651E+09 0.152204E+10 0.891469E+09
February 0.953558E+09 0.529631E+09 0.423927E+09 0.142390E+10 0.648246E+09
March 0.902673E+09 0.398701E+09 0.503972E+09 0.157780E+10 0.433180E+09
April 0.613590E+09 0.173172E+09 0.440418E+09 0.142393E+10 0.139886E+09
May 0.455963E+09 33753123.25 0.422210E+09 0.136958E+10 19804837.89
June 0.403635E+09 6887799.25 0.396747E+09 0.131054E+10 14387253.31
July 0.435061E+09 5983845.35 0.429078E+09 0.125618E+10 2853870.87
August 0.461507E+09 24647728.43 0.436859E+09 0.117537E+10 11776613.91
September 0.598729E+09 0.155400E+09 0.443328E+09 0.128741E+10 58463778.42
October 0.106438E+10 0.594344E+09 0.470039E+09 0.197199E+10 0.340682E+09
November 0.128658E+10 0.850401E+09 0.436181E+09 0.208481E+10 0.632987E+09
December 0.118652E+10 0.743502E+09 0.443014E+09 0.168583E+10 0.887825E+09
           
Annual Sum or Average 0.947249E+10 0.419106E+10 0.528143E+10 0.180894E+11 0.408156E+10
Minimum of Months 0.403635E+09 5983845.35 0.396747E+09 0.117537E+10 2853870.87
Maximum of Months 0.128658E+10 0.850401E+09 0.503972E+09 0.208481E+10 0.891469E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111030E+10 0.674644E+09 0.435654E+09 0.152205E+10 0.891470E+09
February 0.953565E+09 0.529635E+09 0.423930E+09 0.142391E+10 0.648247E+09
March 0.902678E+09 0.398704E+09 0.503975E+09 0.157781E+10 0.433181E+09
April 0.613594E+09 0.173173E+09 0.440420E+09 0.142394E+10 0.139887E+09
May 0.455965E+09 33753370.59 0.422212E+09 0.136958E+10 19805066.96
June 0.403636E+09 6887849.73 0.396748E+09 0.131054E+10 14387328.12
July 0.435064E+09 5983889.20 0.429080E+09 0.125618E+10 2853905.27
August 0.461510E+09 24647909.05 0.436862E+09 0.117537E+10 11776735.47
September 0.598732E+09 0.155401E+09 0.443331E+09 0.128741E+10 58464256.17
October 0.106439E+10 0.594348E+09 0.470041E+09 0.197201E+10 0.340683E+09
November 0.128659E+10 0.850407E+09 0.436184E+09 0.208482E+10 0.632988E+09
December 0.118652E+10 0.743507E+09 0.443017E+09 0.168584E+10 0.887826E+09
           
Annual Sum or Average 0.947255E+10 0.419109E+10 0.528145E+10 0.180895E+11 0.408157E+10
Minimum of Months 0.403636E+09 5983889.20 0.396748E+09 0.117537E+10 2853905.27
Maximum of Months 0.128659E+10 0.850407E+09 0.503975E+09 0.208482E+10 0.891470E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111029E+10 0.674639E+09 0.435651E+09 0.152204E+10 0.891469E+09
February 0.953558E+09 0.529631E+09 0.423927E+09 0.142390E+10 0.648246E+09
March 0.902673E+09 0.398701E+09 0.503972E+09 0.157780E+10 0.433180E+09
April 0.613590E+09 0.173172E+09 0.440418E+09 0.142393E+10 0.139886E+09
May 0.455963E+09 33753123.25 0.422210E+09 0.136958E+10 19804837.89
June 0.403635E+09 6887799.25 0.396747E+09 0.131054E+10 14387253.31
July 0.435061E+09 5983845.35 0.429078E+09 0.125618E+10 2853870.87
August 0.461507E+09 24647728.43 0.436859E+09 0.117537E+10 11776613.91
September 0.598729E+09 0.155400E+09 0.443328E+09 0.128741E+10 58463778.42
October 0.106438E+10 0.594344E+09 0.470039E+09 0.197199E+10 0.340682E+09
November 0.128658E+10 0.850401E+09 0.436181E+09 0.208481E+10 0.632987E+09
December 0.118652E+10 0.743502E+09 0.443014E+09 0.168583E+10 0.887825E+09
           
Annual Sum or Average 0.947249E+10 0.419106E+10 0.528143E+10 0.180894E+11 0.408156E+10
Minimum of Months 0.403635E+09 5983845.35 0.396747E+09 0.117537E+10 2853870.87
Maximum of Months 0.128658E+10 0.850401E+09 0.503972E+09 0.208481E+10 0.891469E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111025E+10 0.674614E+09 0.435635E+09 0.152198E+10 0.891433E+09
February 0.953523E+09 0.529612E+09 0.423911E+09 0.142385E+10 0.648220E+09
March 0.902639E+09 0.398686E+09 0.503953E+09 0.157774E+10 0.433163E+09
April 0.613567E+09 0.173166E+09 0.440401E+09 0.142388E+10 0.139881E+09
May 0.455946E+09 33751886.52 0.422194E+09 0.136952E+10 19804154.20
June 0.403619E+09 6887546.88 0.396732E+09 0.131049E+10 14386710.84
July 0.435045E+09 5983626.10 0.429061E+09 0.125613E+10 2853773.05
August 0.461490E+09 24646825.33 0.436843E+09 0.117532E+10 11776200.04
September 0.598706E+09 0.155394E+09 0.443312E+09 0.128736E+10 58461660.94
October 0.106434E+10 0.594322E+09 0.470021E+09 0.197192E+10 0.340669E+09
November 0.128653E+10 0.850370E+09 0.436165E+09 0.208473E+10 0.632962E+09
December 0.118647E+10 0.743475E+09 0.442998E+09 0.168577E+10 0.887789E+09
           
Annual Sum or Average 0.947214E+10 0.419091E+10 0.528123E+10 0.180887E+11 0.408140E+10
Minimum of Months 0.403619E+09 5983626.10 0.396732E+09 0.117532E+10 2853773.05
Maximum of Months 0.128653E+10 0.850370E+09 0.503953E+09 0.208473E+10 0.891433E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.568506E+09 0.221241E+09 0.347265E+09 0.630866E+09 0.113022E+10
February 0.587189E+09 0.216395E+09 0.370794E+09 0.766132E+09 0.822206E+09
March 0.843016E+09 0.336983E+09 0.506033E+09 0.135805E+10 0.559282E+09
April 0.991624E+09 0.465034E+09 0.526590E+09 0.195369E+10 0.220459E+09
May 0.970274E+09 0.411570E+09 0.558703E+09 0.226921E+10 35807931.47
June 0.881948E+09 0.342572E+09 0.539376E+09 0.216380E+10 27919116.69
July 0.676266E+09 0.131534E+09 0.544732E+09 0.164396E+10 11494086.85
August 0.621079E+09 0.110385E+09 0.510694E+09 0.137454E+10 45479557.40
September 0.660705E+09 0.193964E+09 0.466741E+09 0.135033E+10 86826852.37
October 0.710616E+09 0.282966E+09 0.427650E+09 0.130507E+10 0.421197E+09
November 0.622131E+09 0.265149E+09 0.356983E+09 0.934957E+09 0.801144E+09
December 0.550107E+09 0.209768E+09 0.340339E+09 0.604100E+09 0.118155E+10
           
Annual Sum or Average 0.868346E+10 0.318756E+10 0.549590E+10 0.163547E+11 0.534359E+10
Minimum of Months 0.550107E+09 0.110385E+09 0.340339E+09 0.604100E+09 11494086.85
Maximum of Months 0.991624E+09 0.465034E+09 0.558703E+09 0.226921E+10 0.118155E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.568506E+09 0.221241E+09 0.347265E+09 0.630866E+09 0.113022E+10
February 0.587189E+09 0.216395E+09 0.370794E+09 0.766132E+09 0.822206E+09
March 0.843016E+09 0.336983E+09 0.506033E+09 0.135805E+10 0.559282E+09
April 0.991624E+09 0.465034E+09 0.526590E+09 0.195369E+10 0.220459E+09
May 0.970274E+09 0.411570E+09 0.558703E+09 0.226921E+10 35807931.47
June 0.881948E+09 0.342572E+09 0.539376E+09 0.216380E+10 27919116.69
July 0.676266E+09 0.131534E+09 0.544732E+09 0.164396E+10 11494086.85
August 0.621079E+09 0.110385E+09 0.510694E+09 0.137454E+10 45479557.40
September 0.660705E+09 0.193964E+09 0.466741E+09 0.135033E+10 86826852.37
October 0.710616E+09 0.282966E+09 0.427650E+09 0.130507E+10 0.421197E+09
November 0.622131E+09 0.265149E+09 0.356983E+09 0.934957E+09 0.801144E+09
December 0.550107E+09 0.209768E+09 0.340339E+09 0.604100E+09 0.118155E+10
           
Annual Sum or Average 0.868346E+10 0.318756E+10 0.549590E+10 0.163547E+11 0.534359E+10
Minimum of Months 0.550107E+09 0.110385E+09 0.340339E+09 0.604100E+09 11494086.85
Maximum of Months 0.991624E+09 0.465034E+09 0.558703E+09 0.226921E+10 0.118155E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.568496E+09 0.221237E+09 0.347259E+09 0.630855E+09 0.113020E+10
February 0.587178E+09 0.216391E+09 0.370787E+09 0.766118E+09 0.822191E+09
March 0.843001E+09 0.336977E+09 0.506024E+09 0.135803E+10 0.559272E+09
April 0.991605E+09 0.465025E+09 0.526580E+09 0.195365E+10 0.220455E+09
May 0.970256E+09 0.411563E+09 0.558693E+09 0.226917E+10 35807277.18
June 0.881932E+09 0.342566E+09 0.539366E+09 0.216376E+10 27918606.54
July 0.676253E+09 0.131532E+09 0.544722E+09 0.164393E+10 11493876.82
August 0.621068E+09 0.110383E+09 0.510685E+09 0.137451E+10 45478726.39
September 0.660693E+09 0.193961E+09 0.466732E+09 0.135031E+10 86825265.85
October 0.710603E+09 0.282961E+09 0.427642E+09 0.130504E+10 0.421190E+09
November 0.622120E+09 0.265144E+09 0.356976E+09 0.934940E+09 0.801129E+09
December 0.550097E+09 0.209764E+09 0.340333E+09 0.604089E+09 0.118153E+10
           
Annual Sum or Average 0.868330E+10 0.318750E+10 0.549580E+10 0.163544E+11 0.534349E+10
Minimum of Months 0.550097E+09 0.110383E+09 0.340333E+09 0.604089E+09 11493876.82
Maximum of Months 0.991605E+09 0.465025E+09 0.558693E+09 0.226917E+10 0.118153E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.122067E+10 0.00 0.122067E+10 0.787704E+09 0.438594E+10
February 0.130743E+10 0.00 0.130743E+10 0.133441E+10 0.304711E+10
March 0.174425E+10 0.00 0.174425E+10 0.272462E+10 0.200599E+10
April 0.183160E+10 6211571.55 0.182539E+10 0.452714E+10 0.652407E+09
May 0.209692E+10 58843614.39 0.203808E+10 0.646201E+10 0.102538E+09
June 0.210063E+10 77807754.61 0.202282E+10 0.676589E+10 81186150.52
July 0.214076E+10 33900208.49 0.210686E+10 0.622808E+10 22587717.29
August 0.196528E+10 6124891.54 0.195915E+10 0.525628E+10 74296566.66
September 0.169463E+10 118993.41 0.169451E+10 0.396211E+10 0.276058E+09
October 0.151703E+10 0.00 0.151703E+10 0.301302E+10 0.154814E+10
November 0.124349E+10 0.00 0.124349E+10 0.163522E+10 0.290451E+10
December 0.119078E+10 0.00 0.119078E+10 0.892305E+09 0.420274E+10
           
Annual Sum or Average 0.200535E+11 0.183007E+09 0.198705E+11 0.435888E+11 0.193035E+11
Minimum of Months 0.119078E+10 0.00 0.119078E+10 0.787704E+09 22587717.29
Maximum of Months 0.214076E+10 77807754.61 0.210686E+10 0.676589E+10 0.438594E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.174326E+10 0.699721E+09 0.104354E+10 0.184848E+10 0.271680E+10
February 0.191289E+10 0.789730E+09 0.112316E+10 0.250699E+10 0.193262E+10
March 0.258354E+10 0.106640E+10 0.151715E+10 0.419958E+10 0.130952E+10
April 0.297459E+10 0.138691E+10 0.158769E+10 0.604063E+10 0.455427E+09
May 0.302541E+10 0.134130E+10 0.168411E+10 0.710865E+10 69153025.91
June 0.238286E+10 0.790630E+09 0.159223E+10 0.622568E+10 53855834.36
July 0.206949E+10 0.437021E+09 0.163247E+10 0.529251E+10 12924606.31
August 0.186469E+10 0.324501E+09 0.154019E+10 0.447640E+10 49289897.03
September 0.192795E+10 0.537657E+09 0.139029E+10 0.403269E+10 0.187788E+09
October 0.217925E+10 0.880272E+09 0.129897E+10 0.402938E+10 0.103206E+10
November 0.186989E+10 0.802641E+09 0.106725E+10 0.279714E+10 0.186442E+10
December 0.168481E+10 0.667533E+09 0.101728E+10 0.194163E+10 0.265692E+10
           
Annual Sum or Average 0.262186E+11 0.972431E+10 0.164943E+11 0.504998E+11 0.123408E+11
Minimum of Months 0.168481E+10 0.324501E+09 0.101728E+10 0.184848E+10 12924606.31
Maximum of Months 0.302541E+10 0.138691E+10 0.168411E+10 0.710865E+10 0.271680E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.555159E+10 0.337329E+10 0.217830E+10 0.756709E+10 0.439105E+10
February 0.476791E+10 0.264823E+10 0.211968E+10 0.708161E+10 0.317891E+10
March 0.451346E+10 0.199356E+10 0.251990E+10 0.786302E+10 0.217015E+10
April 0.306800E+10 0.865885E+09 0.220212E+10 0.714833E+10 0.737085E+09
May 0.227984E+10 0.168770E+09 0.211107E+10 0.690717E+10 0.102794E+09
June 0.201820E+10 34439972.86 0.198376E+10 0.661126E+10 80049606.88
July 0.217534E+10 29920075.17 0.214542E+10 0.632658E+10 20011221.71
August 0.230758E+10 0.123242E+09 0.218434E+10 0.593705E+10 77714619.05
September 0.299371E+10 0.777023E+09 0.221668E+10 0.642529E+10 0.323219E+09
October 0.532204E+10 0.297180E+10 0.235023E+10 0.982414E+10 0.174246E+10
November 0.643307E+10 0.425213E+10 0.218095E+10 0.103835E+11 0.314311E+10
December 0.593273E+10 0.371762E+10 0.221512E+10 0.842242E+10 0.431390E+10
           
Annual Sum or Average 0.473635E+11 0.209559E+11 0.264076E+11 0.904975E+11 0.202804E+11
Minimum of Months 0.201820E+10 29920075.17 0.198376E+10 0.593705E+10 20011221.71
Maximum of Months 0.643307E+10 0.425213E+10 0.251990E+10 0.103835E+11 0.439105E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170550E+10 0.663716E+09 0.104178E+10 0.200024E+10 0.300901E+10
February 0.176155E+10 0.649178E+09 0.111237E+10 0.240556E+10 0.213904E+10
March 0.252902E+10 0.101094E+10 0.151808E+10 0.417263E+10 0.147118E+10
April 0.297484E+10 0.139509E+10 0.157975E+10 0.602055E+10 0.534943E+09
May 0.291079E+10 0.123470E+10 0.167609E+10 0.688415E+10 94580319.99
June 0.264582E+10 0.102771E+10 0.161811E+10 0.662471E+10 70298217.95
July 0.202878E+10 0.394598E+09 0.163418E+10 0.512577E+10 20898399.94
August 0.186322E+10 0.331151E+09 0.153207E+10 0.440919E+10 64540666.80
September 0.198210E+10 0.581887E+09 0.140021E+10 0.410613E+10 0.227363E+09
October 0.213182E+10 0.848889E+09 0.128294E+10 0.399128E+10 0.113794E+10
November 0.186638E+10 0.795438E+09 0.107094E+10 0.293233E+10 0.206683E+10
December 0.165030E+10 0.629299E+09 0.102101E+10 0.201149E+10 0.290401E+10
           
Annual Sum or Average 0.260501E+11 0.956259E+10 0.164875E+11 0.506840E+11 0.137406E+11
Minimum of Months 0.165030E+10 0.331151E+09 0.102101E+10 0.200024E+10 20898399.94
Maximum of Months 0.297484E+10 0.139509E+10 0.167609E+10 0.688415E+10 0.300901E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.122067E+10 0.00 0.122067E+10 0.939590E+09 0.384313E+10
February 0.130743E+10 0.00 0.130743E+10 0.143274E+10 0.277664E+10
March 0.174425E+10 0.00 0.174425E+10 0.274269E+10 0.191360E+10
April 0.183160E+10 6211571.55 0.182539E+10 0.446458E+10 0.644289E+09
May 0.209692E+10 58843614.39 0.203808E+10 0.634831E+10 0.109265E+09
June 0.210063E+10 77807754.61 0.202282E+10 0.665320E+10 87572832.08
July 0.214076E+10 33900208.49 0.210686E+10 0.610829E+10 23400604.58
August 0.196528E+10 6124891.54 0.195915E+10 0.516014E+10 81300455.28
September 0.169463E+10 118993.41 0.169451E+10 0.391401E+10 0.277935E+09
October 0.151703E+10 0.00 0.151703E+10 0.300516E+10 0.149621E+10
November 0.124349E+10 0.00 0.124349E+10 0.171599E+10 0.269005E+10
December 0.119078E+10 0.00 0.119078E+10 0.103879E+10 0.375264E+10
           
Annual Sum or Average 0.200535E+11 0.183007E+09 0.198705E+11 0.435235E+11 0.176960E+11
Minimum of Months 0.119078E+10 0.00 0.119078E+10 0.939590E+09 23400604.58
Maximum of Months 0.214076E+10 77807754.61 0.210686E+10 0.665320E+10 0.384313E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.174326E+10 0.699721E+09 0.104354E+10 0.198851E+10 0.241726E+10
February 0.191289E+10 0.789730E+09 0.112316E+10 0.256989E+10 0.180315E+10
March 0.258354E+10 0.106640E+10 0.151715E+10 0.419343E+10 0.127986E+10
April 0.297459E+10 0.138691E+10 0.158769E+10 0.598521E+10 0.460568E+09
May 0.302541E+10 0.134130E+10 0.168411E+10 0.701654E+10 76503274.79
June 0.238286E+10 0.790630E+09 0.159223E+10 0.613702E+10 59323828.07
July 0.206949E+10 0.437021E+09 0.163247E+10 0.520037E+10 13351592.25
August 0.186469E+10 0.324501E+09 0.154019E+10 0.440409E+10 54822785.64
September 0.192795E+10 0.537657E+09 0.139029E+10 0.399146E+10 0.193869E+09
October 0.217925E+10 0.880272E+09 0.129897E+10 0.401157E+10 0.101937E+10
November 0.186989E+10 0.802641E+09 0.106725E+10 0.283821E+10 0.177154E+10
December 0.168481E+10 0.667533E+09 0.101728E+10 0.206010E+10 0.242134E+10
           
Annual Sum or Average 0.262186E+11 0.972431E+10 0.164943E+11 0.503964E+11 0.115710E+11
Minimum of Months 0.168481E+10 0.324501E+09 0.101728E+10 0.198851E+10 13351592.25
Maximum of Months 0.302541E+10 0.138691E+10 0.168411E+10 0.701654E+10 0.242134E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.555159E+10 0.337329E+10 0.217830E+10 0.773319E+10 0.394431E+10
February 0.476791E+10 0.264823E+10 0.211968E+10 0.714514E+10 0.297393E+10
March 0.451346E+10 0.199356E+10 0.251990E+10 0.784680E+10 0.211291E+10
April 0.306800E+10 0.865885E+09 0.220212E+10 0.707598E+10 0.738200E+09
May 0.227984E+10 0.168770E+09 0.211107E+10 0.679117E+10 0.109889E+09
June 0.201820E+10 34439972.86 0.198376E+10 0.649688E+10 86626236.95
July 0.217534E+10 29920075.17 0.214542E+10 0.620523E+10 20431277.23
August 0.230758E+10 0.123242E+09 0.218434E+10 0.583991E+10 85365602.64
September 0.299371E+10 0.777023E+09 0.221668E+10 0.636781E+10 0.330972E+09
October 0.532204E+10 0.297180E+10 0.235023E+10 0.978961E+10 0.172370E+10
November 0.643307E+10 0.425213E+10 0.218095E+10 0.104078E+11 0.301170E+10
December 0.593273E+10 0.371762E+10 0.221512E+10 0.855999E+10 0.397510E+10
           
Annual Sum or Average 0.473635E+11 0.209559E+11 0.264076E+11 0.902595E+11 0.191131E+11
Minimum of Months 0.201820E+10 29920075.17 0.198376E+10 0.583991E+10 20431277.23
Maximum of Months 0.643307E+10 0.425213E+10 0.251990E+10 0.104078E+11 0.397510E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170550E+10 0.663716E+09 0.104178E+10 0.207950E+10 0.271648E+10
February 0.176155E+10 0.649178E+09 0.111237E+10 0.244756E+10 0.199735E+10
March 0.252902E+10 0.101094E+10 0.151808E+10 0.416951E+10 0.142688E+10
April 0.297484E+10 0.139509E+10 0.157975E+10 0.597533E+10 0.532618E+09
May 0.291079E+10 0.123470E+10 0.167609E+10 0.681412E+10 98710896.68
June 0.264582E+10 0.102771E+10 0.161811E+10 0.655366E+10 73479914.97
July 0.202878E+10 0.394598E+09 0.163418E+10 0.505677E+10 20955766.78
August 0.186322E+10 0.331151E+09 0.153207E+10 0.435517E+10 68284712.84
September 0.198210E+10 0.581887E+09 0.140021E+10 0.407490E+10 0.227787E+09
October 0.213182E+10 0.848889E+09 0.128294E+10 0.397941E+10 0.111295E+10
November 0.186638E+10 0.795438E+09 0.107094E+10 0.296303E+10 0.195916E+10
December 0.165030E+10 0.629299E+09 0.102101E+10 0.208632E+10 0.266446E+10
           
Annual Sum or Average 0.260501E+11 0.956259E+10 0.164875E+11 0.505553E+11 0.128991E+11
Minimum of Months 0.165030E+10 0.331151E+09 0.102101E+10 0.207950E+10 20955766.78
Maximum of Months 0.297484E+10 0.139509E+10 0.167609E+10 0.681412E+10 0.271648E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 243.02 1820.73 455.74 0.00 455.74 0.00 0.00
February 505.68 1383.34 540.43 0.00 540.43 0.00 0.00
March 990.74 785.97 651.22 0.00 651.22 0.00 0.00
April 1709.11 246.46 706.63 2.40 704.23 0.00 0.00
May 2388.42 36.57 782.89 21.97 760.92 0.00 0.00
June 2589.09 27.86 810.41 30.02 780.40 0.00 0.00
July 2310.10 5.73 799.25 12.66 786.60 0.00 0.00
August 1931.69 20.83 733.74 2.29 731.45 0.00 0.00
September 1516.63 100.12 653.78 0.05 653.73 0.00 0.00
October 1099.87 595.57 566.39 0.00 566.39 0.00 0.00
November 586.91 1217.72 479.74 0.00 479.74 0.00 0.00
December 267.18 1776.30 444.58 0.00 444.58 0.00 0.00
               
Annual Sum or Average 1348.97 665.18 635.88 5.80 630.08 0.00 0.00
Minimum of Months 243.02 5.73 444.58 0.00 444.58 0.00 0.00
Maximum of Months 2589.09 1820.73 810.41 30.02 786.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 657.63 1097.35 650.86 261.25 389.61 0.00 0.00
February 1023.86 841.63 790.71 326.44 464.27 0.00 0.00
March 1574.06 481.13 964.59 398.15 566.44 0.00 0.00
April 2346.26 147.93 1147.61 535.07 612.54 0.00 0.00
May 2662.60 22.18 1129.56 500.79 628.78 0.00 0.00
June 2415.43 15.69 919.32 305.03 614.29 0.00 0.00
July 1999.63 2.29 772.66 163.17 609.50 0.00 0.00
August 1696.47 7.31 696.20 121.16 575.04 0.00 0.00
September 1563.70 59.25 743.81 207.43 536.38 0.00 0.00
October 1507.98 374.46 813.64 328.66 484.98 0.00 0.00
November 1069.70 742.27 721.41 309.66 411.75 0.00 0.00
December 692.49 1063.62 629.04 249.23 379.81 0.00 0.00
               
Annual Sum or Average 1602.84 402.79 831.39 308.36 523.03 0.00 0.00
Minimum of Months 657.63 2.29 629.04 121.16 379.81 0.00 0.00
Maximum of Months 2662.60 1097.35 1147.61 535.07 628.78 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2841.31 1664.17 2072.66 1259.40 813.26 0.00 0.00
February 2942.91 1339.78 1970.80 1094.64 876.17 0.00 0.00
March 2945.41 808.65 1685.09 744.29 940.80 0.00 0.00
April 2746.77 269.84 1183.62 334.05 849.57 0.00 0.00
May 2556.69 36.97 851.18 63.01 788.17 0.00 0.00
June 2528.03 27.75 778.61 13.29 765.32 0.00 0.00
July 2345.00 5.33 812.16 11.17 800.99 0.00 0.00
August 2194.14 21.98 861.53 46.01 815.52 0.00 0.00
September 2483.41 112.78 1154.95 299.77 855.18 0.00 0.00
October 3681.27 635.98 1986.97 1109.51 877.46 0.00 0.00
November 4021.60 1221.03 2481.82 1640.43 841.39 0.00 0.00
December 3147.07 1657.37 2214.96 1387.95 827.01 0.00 0.00
               
Annual Sum or Average 2868.04 647.12 1501.85 664.49 837.36 0.00 0.00
Minimum of Months 2194.14 5.33 778.61 11.17 765.32 0.00 0.00
Maximum of Months 4021.60 1664.17 2481.82 1640.43 940.80 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 706.61 1265.92 636.76 247.80 388.96 0.00 0.00
February 950.06 1019.59 728.16 268.35 459.81 0.00 0.00
March 1521.10 626.43 944.23 377.44 566.79 0.00 0.00
April 2261.20 255.16 1147.71 538.23 609.48 0.00 0.00
May 2541.67 40.11 1086.77 460.99 625.78 0.00 0.00
June 2504.38 32.31 1020.77 396.49 624.27 0.00 0.00
July 1841.35 12.87 757.46 147.33 610.13 0.00 0.00
August 1539.57 50.94 695.65 123.64 572.01 0.00 0.00
September 1562.88 100.49 764.70 224.49 540.21 0.00 0.00
October 1461.76 471.77 795.94 316.94 479.00 0.00 0.00
November 1082.12 927.24 720.06 306.88 413.17 0.00 0.00
December 676.63 1323.41 616.16 234.95 381.20 0.00 0.00
               
Annual Sum or Average 1555.80 508.33 826.05 303.23 522.82 0.00 0.00
Minimum of Months 676.63 12.87 616.16 123.64 381.20 0.00 0.00
Maximum of Months 2541.67 1323.41 1147.71 538.23 625.78 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 294.09 1637.52 455.75 0.00 455.75 0.00 0.00
February 551.59 1259.55 540.44 0.00 540.44 0.00 0.00
March 1017.26 748.95 651.23 0.00 651.23 0.00 0.00
April 1746.58 251.70 706.64 2.40 704.24 0.00 0.00
May 2412.64 38.28 782.90 21.97 760.93 0.00 0.00
June 2610.30 31.32 810.43 30.02 780.41 0.00 0.00
July 2325.30 8.43 799.27 12.66 786.61 0.00 0.00
August 1962.47 27.74 733.75 2.29 731.46 0.00 0.00
September 1528.59 106.50 653.79 0.05 653.75 0.00 0.00
October 1124.93 578.01 566.40 0.00 566.40 0.00 0.00
November 630.87 1120.57 479.74 0.00 479.74 0.00 0.00
December 333.15 1569.12 444.59 0.00 444.59 0.00 0.00
               
Annual Sum or Average 1382.19 612.11 635.89 5.80 630.09 0.00 0.00
Minimum of Months 294.09 8.43 444.59 0.00 444.59 0.00 0.00
Maximum of Months 2610.30 1637.52 810.43 30.02 786.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 690.14 1014.34 650.86 261.25 389.61 0.00 0.00
February 1036.29 798.87 790.71 326.44 464.27 0.00 0.00
March 1567.94 488.92 964.58 398.15 566.44 0.00 0.00
April 2330.49 175.70 1147.61 535.07 612.53 0.00 0.00
May 2654.06 25.82 1129.56 500.78 628.77 0.00 0.00
June 2401.88 20.78 919.31 305.03 614.29 0.00 0.00
July 1976.00 4.83 772.66 163.16 609.49 0.00 0.00
August 1671.30 18.40 696.20 121.15 575.04 0.00 0.00
September 1555.82 72.45 743.81 207.43 536.38 0.00 0.00
October 1504.40 385.33 813.64 328.66 484.98 0.00 0.00
November 1079.14 719.30 721.41 309.66 411.75 0.00 0.00
December 724.92 991.98 629.04 249.23 379.81 0.00 0.00
               
Annual Sum or Average 1601.34 391.32 831.39 308.36 523.03 0.00 0.00
Minimum of Months 690.14 4.83 629.04 121.15 379.81 0.00 0.00
Maximum of Months 2654.06 1014.34 1147.61 535.07 628.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2825.23 1639.43 2072.73 1259.44 813.28 0.00 0.00
February 2927.25 1314.03 1970.86 1094.67 876.19 0.00 0.00
March 2935.71 810.24 1685.13 744.31 940.82 0.00 0.00
April 2757.84 284.37 1183.64 334.06 849.58 0.00 0.00
May 2578.84 38.38 851.20 63.01 788.18 0.00 0.00
June 2550.64 30.88 778.63 13.29 765.34 0.00 0.00
July 2362.08 7.47 812.18 11.17 801.01 0.00 0.00
August 2216.64 29.02 861.55 46.01 815.54 0.00 0.00
September 2478.89 124.70 1154.98 299.78 855.20 0.00 0.00
October 3667.91 650.56 1987.02 1109.54 877.48 0.00 0.00
November 4005.99 1212.62 2481.90 1640.48 841.42 0.00 0.00
December 3144.57 1610.62 2215.03 1388.00 827.03 0.00 0.00
               
Annual Sum or Average 2869.66 643.09 1501.89 664.51 837.38 0.00 0.00
Minimum of Months 2216.64 7.47 778.63 11.17 765.34 0.00 0.00
Maximum of Months 4005.99 1639.43 2481.90 1640.48 940.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 746.80 1123.44 636.76 247.80 388.96 0.00 0.00
February 994.36 884.19 728.15 268.34 459.81 0.00 0.00
March 1557.88 549.28 944.23 377.44 566.79 0.00 0.00
April 2322.74 206.38 1147.70 538.23 609.47 0.00 0.00
May 2570.25 35.31 1086.77 460.98 625.78 0.00 0.00
June 2555.83 27.12 1020.76 396.49 624.27 0.00 0.00
July 1913.74 7.80 757.46 147.33 610.13 0.00 0.00
August 1646.20 24.10 695.65 123.64 572.01 0.00 0.00
September 1584.15 87.72 764.70 224.49 540.20 0.00 0.00
October 1490.17 424.86 795.93 316.94 478.99 0.00 0.00
November 1131.30 797.39 720.05 306.88 413.17 0.00 0.00
December 751.00 1084.23 616.15 234.95 381.20 0.00 0.00
               
Annual Sum or Average 1607.18 435.71 826.04 303.23 522.82 0.00 0.00
Minimum of Months 746.80 7.80 616.15 123.64 381.20 0.00 0.00
Maximum of Months 2570.25 1123.44 1147.70 538.23 625.78 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 350.80 1434.86 455.75 0.00 455.75 0.00 0.00
February 592.24 1147.75 540.44 0.00 540.44 0.00 0.00
March 1024.00 714.46 651.23 0.00 651.23 0.00 0.00
April 1722.45 248.57 706.64 2.40 704.24 0.00 0.00
May 2370.19 40.79 782.90 21.97 760.93 0.00 0.00
June 2566.82 33.79 810.43 30.02 780.41 0.00 0.00
July 2280.58 8.74 799.27 12.66 786.61 0.00 0.00
August 1926.58 30.35 733.75 2.29 731.46 0.00 0.00
September 1510.04 107.23 653.79 0.05 653.75 0.00 0.00
October 1122.00 558.62 566.40 0.00 566.40 0.00 0.00
November 662.03 1037.83 479.74 0.00 479.74 0.00 0.00
December 387.84 1401.08 444.59 0.00 444.59 0.00 0.00
               
Annual Sum or Average 1380.12 561.14 635.89 5.80 630.09 0.00 0.00
Minimum of Months 350.80 8.74 444.59 0.00 444.59 0.00 0.00
Maximum of Months 2566.82 1434.86 810.43 30.02 786.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 742.42 902.50 650.86 261.25 389.61 0.00 0.00
February 1062.29 745.35 790.71 326.44 464.27 0.00 0.00
March 1565.65 477.85 964.58 398.15 566.44 0.00 0.00
April 2309.11 177.69 1147.61 535.07 612.53 0.00 0.00
May 2619.68 28.56 1129.56 500.78 628.77 0.00 0.00
June 2367.68 22.89 919.31 305.03 614.29 0.00 0.00
July 1941.60 4.98 772.66 163.16 609.49 0.00 0.00
August 1644.30 20.47 696.20 121.15 575.04 0.00 0.00
September 1539.92 74.79 743.81 207.43 536.38 0.00 0.00
October 1497.75 380.59 813.64 328.66 484.98 0.00 0.00
November 1094.99 683.46 721.41 309.66 411.75 0.00 0.00
December 769.15 904.03 629.04 249.23 379.81 0.00 0.00
               
Annual Sum or Average 1598.06 366.91 831.39 308.36 523.03 0.00 0.00
Minimum of Months 742.42 4.98 629.04 121.15 379.81 0.00 0.00
Maximum of Months 2619.68 904.03 1147.61 535.07 628.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2887.24 1472.64 2072.73 1259.44 813.28 0.00 0.00
February 2953.51 1229.30 1970.86 1094.67 876.19 0.00 0.00
March 2929.66 788.87 1685.13 744.31 940.82 0.00 0.00
April 2729.93 284.80 1183.64 334.06 849.58 0.00 0.00
May 2535.53 41.03 851.20 63.01 788.18 0.00 0.00
June 2506.51 33.42 778.63 13.29 765.34 0.00 0.00
July 2316.77 7.63 812.18 11.17 801.01 0.00 0.00
August 2180.37 31.87 861.55 46.01 815.54 0.00 0.00
September 2456.72 127.69 1154.98 299.78 855.20 0.00 0.00
October 3655.02 643.56 1987.02 1109.54 877.48 0.00 0.00
November 4015.35 1161.92 2481.90 1640.48 841.42 0.00 0.00
December 3195.93 1484.13 2215.03 1388.00 827.03 0.00 0.00
               
Annual Sum or Average 2862.11 606.07 1501.89 664.51 837.38 0.00 0.00
Minimum of Months 2180.37 7.63 778.63 11.17 765.34 0.00 0.00
Maximum of Months 4015.35 1484.13 2481.90 1640.48 940.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 776.40 1014.22 636.76 247.80 388.96 0.00 0.00
February 1011.72 825.63 728.15 268.34 459.81 0.00 0.00
March 1556.72 532.74 944.23 377.44 566.79 0.00 0.00
April 2305.30 205.49 1147.70 538.23 609.47 0.00 0.00
May 2544.10 36.85 1086.77 460.98 625.78 0.00 0.00
June 2528.42 28.35 1020.76 396.49 624.27 0.00 0.00
July 1887.98 7.82 757.46 147.33 610.13 0.00 0.00
August 1626.04 25.49 695.65 123.64 572.01 0.00 0.00
September 1572.11 87.88 764.70 224.49 540.20 0.00 0.00
October 1485.74 415.53 795.93 316.94 478.99 0.00 0.00
November 1143.14 755.85 720.05 306.88 413.17 0.00 0.00
December 778.94 994.79 616.15 234.95 381.20 0.00 0.00
               
Annual Sum or Average 1603.10 409.03 826.04 303.23 522.82 0.00 0.00
Minimum of Months 776.40 7.82 616.15 123.64 381.20 0.00 0.00
Maximum of Months 2544.10 1014.22 1147.70 538.23 625.78 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.650892E+09 0.487664E+10 0.122065E+10 0.00 0.122065E+10 0.00 0.00
February 0.122334E+10 0.334657E+10 0.130740E+10 0.00 0.130740E+10 0.00 0.00
March 0.265359E+10 0.210515E+10 0.174422E+10 0.00 0.174422E+10 0.00 0.00
April 0.443000E+10 0.638822E+09 0.183157E+10 6211386.31 0.182536E+10 0.00 0.00
May 0.639715E+10 97945050.72 0.209689E+10 58841859.56 0.203805E+10 0.00 0.00
June 0.671092E+10 72220701.36 0.210059E+10 77805434.24 0.202279E+10 0.00 0.00
July 0.618736E+10 15334698.52 0.214072E+10 33899197.52 0.210682E+10 0.00 0.00
August 0.517385E+10 55802508.90 0.196524E+10 6124708.88 0.195911E+10 0.00 0.00
September 0.393112E+10 0.259523E+09 0.169460E+10 118989.86 0.169448E+10 0.00 0.00
October 0.294589E+10 0.159517E+10 0.151701E+10 0.00 0.151701E+10 0.00 0.00
November 0.152127E+10 0.315633E+10 0.124347E+10 0.00 0.124347E+10 0.00 0.00
December 0.715615E+09 0.475764E+10 0.119076E+10 0.00 0.119076E+10 0.00 0.00
               
Annual Sum or Average 0.425410E+11 0.209772E+11 0.200531E+11 0.183002E+09 0.198701E+11 0.00 0.00
Minimum of Months 0.650892E+09 15334698.52 0.119076E+10 0.00 0.119076E+10 0.00 0.00
Maximum of Months 0.671092E+10 0.487664E+10 0.214072E+10 77805434.24 0.210682E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.176140E+10 0.293915E+10 0.174327E+10 0.699724E+09 0.104354E+10 0.00 0.00
February 0.247693E+10 0.203608E+10 0.191290E+10 0.789733E+09 0.112316E+10 0.00 0.00
March 0.421595E+10 0.128865E+10 0.258355E+10 0.106640E+10 0.151715E+10 0.00 0.00
April 0.608150E+10 0.383436E+09 0.297461E+10 0.138691E+10 0.158769E+10 0.00 0.00
May 0.713151E+10 59416635.90 0.302542E+10 0.134131E+10 0.168411E+10 0.00 0.00
June 0.626078E+10 40680360.91 0.238287E+10 0.790633E+09 0.159223E+10 0.00 0.00
July 0.535581E+10 6138952.76 0.206950E+10 0.437022E+09 0.163247E+10 0.00 0.00
August 0.454382E+10 19592310.97 0.186470E+10 0.324502E+09 0.154020E+10 0.00 0.00
September 0.405312E+10 0.153564E+09 0.192796E+10 0.537659E+09 0.139030E+10 0.00 0.00
October 0.403896E+10 0.100295E+10 0.217926E+10 0.880276E+09 0.129898E+10 0.00 0.00
November 0.277267E+10 0.192396E+10 0.186990E+10 0.802644E+09 0.106725E+10 0.00 0.00
December 0.185477E+10 0.284880E+10 0.168482E+10 0.667536E+09 0.101729E+10 0.00 0.00
               
Annual Sum or Average 0.505472E+11 0.127024E+11 0.262187E+11 0.972435E+10 0.164944E+11 0.00 0.00
Minimum of Months 0.176140E+10 6138952.76 0.168482E+10 0.324502E+09 0.101729E+10 0.00 0.00
Maximum of Months 0.713151E+10 0.293915E+10 0.302542E+10 0.138691E+10 0.168411E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.761016E+10 0.445731E+10 0.555142E+10 0.337318E+10 0.217825E+10 0.00 0.00
February 0.711948E+10 0.324120E+10 0.476777E+10 0.264814E+10 0.211962E+10 0.00 0.00
March 0.788897E+10 0.216588E+10 0.451334E+10 0.199349E+10 0.251985E+10 0.00 0.00
April 0.711963E+10 0.699425E+09 0.306794E+10 0.865857E+09 0.220208E+10 0.00 0.00
May 0.684783E+10 99023963.90 0.227980E+10 0.168765E+09 0.211104E+10 0.00 0.00
June 0.655266E+10 71935873.70 0.201816E+10 34438844.85 0.198372E+10 0.00 0.00
July 0.628084E+10 14269325.33 0.217530E+10 29919095.19 0.214538E+10 0.00 0.00
August 0.587679E+10 58882898.80 0.230752E+10 0.123238E+09 0.218429E+10 0.00 0.00
September 0.643700E+10 0.292318E+09 0.299363E+10 0.776997E+09 0.221663E+10 0.00 0.00
October 0.985992E+10 0.170340E+10 0.532189E+10 0.297171E+10 0.235018E+10 0.00 0.00
November 0.104240E+11 0.316491E+10 0.643288E+10 0.425199E+10 0.218090E+10 0.00 0.00
December 0.842912E+10 0.443909E+10 0.593256E+10 0.371749E+10 0.221506E+10 0.00 0.00
               
Annual Sum or Average 0.904464E+11 0.204077E+11 0.473622E+11 0.209552E+11 0.264070E+11 0.00 0.00
Minimum of Months 0.587679E+10 14269325.33 0.201816E+10 29919095.19 0.198372E+10 0.00 0.00
Maximum of Months 0.104240E+11 0.445731E+10 0.643288E+10 0.425199E+10 0.251985E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.189259E+10 0.339063E+10 0.170551E+10 0.663719E+09 0.104179E+10 0.00 0.00
February 0.229838E+10 0.246660E+10 0.176155E+10 0.649181E+09 0.111237E+10 0.00 0.00
March 0.407413E+10 0.167784E+10 0.252903E+10 0.101094E+10 0.151809E+10 0.00 0.00
April 0.586102E+10 0.661373E+09 0.297485E+10 0.139509E+10 0.157976E+10 0.00 0.00
May 0.680760E+10 0.107423E+09 0.291080E+10 0.123470E+10 0.167610E+10 0.00 0.00
June 0.649135E+10 83756839.92 0.264583E+10 0.102771E+10 0.161812E+10 0.00 0.00
July 0.493186E+10 34482050.52 0.202878E+10 0.394599E+09 0.163419E+10 0.00 0.00
August 0.412359E+10 0.136438E+09 0.186323E+10 0.331152E+09 0.153207E+10 0.00 0.00
September 0.405097E+10 0.260479E+09 0.198210E+10 0.581889E+09 0.140021E+10 0.00 0.00
October 0.391518E+10 0.126358E+10 0.213183E+10 0.848893E+09 0.128294E+10 0.00 0.00
November 0.280485E+10 0.240342E+10 0.186638E+10 0.795441E+09 0.107094E+10 0.00 0.00
December 0.181229E+10 0.354463E+10 0.165031E+10 0.629301E+09 0.102101E+10 0.00 0.00
               
Annual Sum or Average 0.490638E+11 0.160307E+11 0.260502E+11 0.956263E+10 0.164876E+11 0.00 0.00
Minimum of Months 0.181229E+10 34482050.52 0.165031E+10 0.331152E+09 0.102101E+10 0.00 0.00
Maximum of Months 0.680760E+10 0.354463E+10 0.297485E+10 0.139509E+10 0.167610E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.787704E+09 0.438594E+10 0.122067E+10 0.00 0.122067E+10 0.00 0.00
February 0.133441E+10 0.304711E+10 0.130743E+10 0.00 0.130743E+10 0.00 0.00
March 0.272462E+10 0.200599E+10 0.174425E+10 0.00 0.174425E+10 0.00 0.00
April 0.452714E+10 0.652407E+09 0.183160E+10 6211571.55 0.182539E+10 0.00 0.00
May 0.646201E+10 0.102538E+09 0.209692E+10 58843614.39 0.203808E+10 0.00 0.00
June 0.676589E+10 81186150.52 0.210063E+10 77807754.61 0.202282E+10 0.00 0.00
July 0.622808E+10 22587717.29 0.214076E+10 33900208.49 0.210686E+10 0.00 0.00
August 0.525628E+10 74296566.66 0.196528E+10 6124891.54 0.195915E+10 0.00 0.00
September 0.396211E+10 0.276058E+09 0.169463E+10 118993.41 0.169451E+10 0.00 0.00
October 0.301302E+10 0.154814E+10 0.151703E+10 0.00 0.151703E+10 0.00 0.00
November 0.163522E+10 0.290451E+10 0.124349E+10 0.00 0.124349E+10 0.00 0.00
December 0.892305E+09 0.420274E+10 0.119078E+10 0.00 0.119078E+10 0.00 0.00
               
Annual Sum or Average 0.435888E+11 0.193035E+11 0.200535E+11 0.183007E+09 0.198705E+11 0.00 0.00
Minimum of Months 0.787704E+09 22587717.29 0.119078E+10 0.00 0.119078E+10 0.00 0.00
Maximum of Months 0.676589E+10 0.438594E+10 0.214076E+10 77807754.61 0.210686E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.184848E+10 0.271680E+10 0.174326E+10 0.699721E+09 0.104354E+10 0.00 0.00
February 0.250699E+10 0.193262E+10 0.191289E+10 0.789730E+09 0.112316E+10 0.00 0.00
March 0.419958E+10 0.130952E+10 0.258354E+10 0.106640E+10 0.151715E+10 0.00 0.00
April 0.604063E+10 0.455427E+09 0.297459E+10 0.138691E+10 0.158769E+10 0.00 0.00
May 0.710865E+10 69153025.91 0.302541E+10 0.134130E+10 0.168411E+10 0.00 0.00
June 0.622568E+10 53855834.36 0.238286E+10 0.790630E+09 0.159223E+10 0.00 0.00
July 0.529251E+10 12924606.31 0.206949E+10 0.437021E+09 0.163247E+10 0.00 0.00
August 0.447640E+10 49289897.03 0.186469E+10 0.324501E+09 0.154019E+10 0.00 0.00
September 0.403269E+10 0.187788E+09 0.192795E+10 0.537657E+09 0.139029E+10 0.00 0.00
October 0.402938E+10 0.103206E+10 0.217925E+10 0.880272E+09 0.129897E+10 0.00 0.00
November 0.279714E+10 0.186442E+10 0.186989E+10 0.802641E+09 0.106725E+10 0.00 0.00
December 0.194163E+10 0.265692E+10 0.168481E+10 0.667533E+09 0.101728E+10 0.00 0.00
               
Annual Sum or Average 0.504998E+11 0.123408E+11 0.262186E+11 0.972431E+10 0.164943E+11 0.00 0.00
Minimum of Months 0.184848E+10 12924606.31 0.168481E+10 0.324501E+09 0.101728E+10 0.00 0.00
Maximum of Months 0.710865E+10 0.271680E+10 0.302541E+10 0.138691E+10 0.168411E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.756709E+10 0.439105E+10 0.555159E+10 0.337329E+10 0.217830E+10 0.00 0.00
February 0.708161E+10 0.317891E+10 0.476791E+10 0.264823E+10 0.211968E+10 0.00 0.00
March 0.786302E+10 0.217015E+10 0.451346E+10 0.199356E+10 0.251990E+10 0.00 0.00
April 0.714833E+10 0.737085E+09 0.306800E+10 0.865885E+09 0.220212E+10 0.00 0.00
May 0.690717E+10 0.102794E+09 0.227984E+10 0.168770E+09 0.211107E+10 0.00 0.00
June 0.661126E+10 80049606.88 0.201820E+10 34439972.86 0.198376E+10 0.00 0.00
July 0.632658E+10 20011221.71 0.217534E+10 29920075.17 0.214542E+10 0.00 0.00
August 0.593705E+10 77714619.05 0.230758E+10 0.123242E+09 0.218434E+10 0.00 0.00
September 0.642529E+10 0.323219E+09 0.299371E+10 0.777023E+09 0.221668E+10 0.00 0.00
October 0.982414E+10 0.174246E+10 0.532204E+10 0.297180E+10 0.235023E+10 0.00 0.00
November 0.103835E+11 0.314311E+10 0.643307E+10 0.425213E+10 0.218095E+10 0.00 0.00
December 0.842242E+10 0.431390E+10 0.593273E+10 0.371762E+10 0.221512E+10 0.00 0.00
               
Annual Sum or Average 0.904975E+11 0.202804E+11 0.473635E+11 0.209559E+11 0.264076E+11 0.00 0.00
Minimum of Months 0.593705E+10 20011221.71 0.201820E+10 29920075.17 0.198376E+10 0.00 0.00
Maximum of Months 0.103835E+11 0.439105E+10 0.643307E+10 0.425213E+10 0.251990E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.200024E+10 0.300901E+10 0.170550E+10 0.663716E+09 0.104178E+10 0.00 0.00
February 0.240556E+10 0.213904E+10 0.176155E+10 0.649178E+09 0.111237E+10 0.00 0.00
March 0.417263E+10 0.147118E+10 0.252902E+10 0.101094E+10 0.151808E+10 0.00 0.00
April 0.602055E+10 0.534943E+09 0.297484E+10 0.139509E+10 0.157975E+10 0.00 0.00
May 0.688415E+10 94580319.99 0.291079E+10 0.123470E+10 0.167609E+10 0.00 0.00
June 0.662471E+10 70298217.95 0.264582E+10 0.102771E+10 0.161811E+10 0.00 0.00
July 0.512577E+10 20898399.94 0.202878E+10 0.394598E+09 0.163418E+10 0.00 0.00
August 0.440919E+10 64540666.80 0.186322E+10 0.331151E+09 0.153207E+10 0.00 0.00
September 0.410613E+10 0.227363E+09 0.198210E+10 0.581887E+09 0.140021E+10 0.00 0.00
October 0.399128E+10 0.113794E+10 0.213182E+10 0.848889E+09 0.128294E+10 0.00 0.00
November 0.293233E+10 0.206683E+10 0.186638E+10 0.795438E+09 0.107094E+10 0.00 0.00
December 0.201149E+10 0.290401E+10 0.165030E+10 0.629299E+09 0.102101E+10 0.00 0.00
               
Annual Sum or Average 0.506840E+11 0.137406E+11 0.260501E+11 0.956259E+10 0.164875E+11 0.00 0.00
Minimum of Months 0.200024E+10 20898399.94 0.165030E+10 0.331151E+09 0.102101E+10 0.00 0.00
Maximum of Months 0.688415E+10 0.300901E+10 0.297484E+10 0.139509E+10 0.167609E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.939590E+09 0.384313E+10 0.122067E+10 0.00 0.122067E+10 0.00 0.00
February 0.143274E+10 0.277664E+10 0.130743E+10 0.00 0.130743E+10 0.00 0.00
March 0.274269E+10 0.191360E+10 0.174425E+10 0.00 0.174425E+10 0.00 0.00
April 0.446458E+10 0.644289E+09 0.183160E+10 6211571.55 0.182539E+10 0.00 0.00
May 0.634831E+10 0.109265E+09 0.209692E+10 58843614.39 0.203808E+10 0.00 0.00
June 0.665320E+10 87572832.08 0.210063E+10 77807754.61 0.202282E+10 0.00 0.00
July 0.610829E+10 23400604.58 0.214076E+10 33900208.49 0.210686E+10 0.00 0.00
August 0.516014E+10 81300455.28 0.196528E+10 6124891.54 0.195915E+10 0.00 0.00
September 0.391401E+10 0.277935E+09 0.169463E+10 118993.41 0.169451E+10 0.00 0.00
October 0.300516E+10 0.149621E+10 0.151703E+10 0.00 0.151703E+10 0.00 0.00
November 0.171599E+10 0.269005E+10 0.124349E+10 0.00 0.124349E+10 0.00 0.00
December 0.103879E+10 0.375264E+10 0.119078E+10 0.00 0.119078E+10 0.00 0.00
               
Annual Sum or Average 0.435235E+11 0.176960E+11 0.200535E+11 0.183007E+09 0.198705E+11 0.00 0.00
Minimum of Months 0.939590E+09 23400604.58 0.119078E+10 0.00 0.119078E+10 0.00 0.00
Maximum of Months 0.665320E+10 0.384313E+10 0.214076E+10 77807754.61 0.210686E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.198851E+10 0.241726E+10 0.174326E+10 0.699721E+09 0.104354E+10 0.00 0.00
February 0.256989E+10 0.180315E+10 0.191289E+10 0.789730E+09 0.112316E+10 0.00 0.00
March 0.419343E+10 0.127986E+10 0.258354E+10 0.106640E+10 0.151715E+10 0.00 0.00
April 0.598521E+10 0.460568E+09 0.297459E+10 0.138691E+10 0.158769E+10 0.00 0.00
May 0.701654E+10 76503274.79 0.302541E+10 0.134130E+10 0.168411E+10 0.00 0.00
June 0.613702E+10 59323828.07 0.238286E+10 0.790630E+09 0.159223E+10 0.00 0.00
July 0.520037E+10 13351592.25 0.206949E+10 0.437021E+09 0.163247E+10 0.00 0.00
August 0.440409E+10 54822785.64 0.186469E+10 0.324501E+09 0.154019E+10 0.00 0.00
September 0.399146E+10 0.193869E+09 0.192795E+10 0.537657E+09 0.139029E+10 0.00 0.00
October 0.401157E+10 0.101937E+10 0.217925E+10 0.880272E+09 0.129897E+10 0.00 0.00
November 0.283821E+10 0.177154E+10 0.186989E+10 0.802641E+09 0.106725E+10 0.00 0.00
December 0.206010E+10 0.242134E+10 0.168481E+10 0.667533E+09 0.101728E+10 0.00 0.00
               
Annual Sum or Average 0.503964E+11 0.115710E+11 0.262186E+11 0.972431E+10 0.164943E+11 0.00 0.00
Minimum of Months 0.198851E+10 13351592.25 0.168481E+10 0.324501E+09 0.101728E+10 0.00 0.00
Maximum of Months 0.701654E+10 0.242134E+10 0.302541E+10 0.138691E+10 0.168411E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.773319E+10 0.394431E+10 0.555159E+10 0.337329E+10 0.217830E+10 0.00 0.00
February 0.714514E+10 0.297393E+10 0.476791E+10 0.264823E+10 0.211968E+10 0.00 0.00
March 0.784680E+10 0.211291E+10 0.451346E+10 0.199356E+10 0.251990E+10 0.00 0.00
April 0.707598E+10 0.738200E+09 0.306800E+10 0.865885E+09 0.220212E+10 0.00 0.00
May 0.679117E+10 0.109889E+09 0.227984E+10 0.168770E+09 0.211107E+10 0.00 0.00
June 0.649688E+10 86626236.95 0.201820E+10 34439972.86 0.198376E+10 0.00 0.00
July 0.620523E+10 20431277.23 0.217534E+10 29920075.17 0.214542E+10 0.00 0.00
August 0.583991E+10 85365602.64 0.230758E+10 0.123242E+09 0.218434E+10 0.00 0.00
September 0.636781E+10 0.330972E+09 0.299371E+10 0.777023E+09 0.221668E+10 0.00 0.00
October 0.978961E+10 0.172370E+10 0.532204E+10 0.297180E+10 0.235023E+10 0.00 0.00
November 0.104078E+11 0.301170E+10 0.643307E+10 0.425213E+10 0.218095E+10 0.00 0.00
December 0.855999E+10 0.397510E+10 0.593273E+10 0.371762E+10 0.221512E+10 0.00 0.00
               
Annual Sum or Average 0.902595E+11 0.191131E+11 0.473635E+11 0.209559E+11 0.264076E+11 0.00 0.00
Minimum of Months 0.583991E+10 20431277.23 0.201820E+10 29920075.17 0.198376E+10 0.00 0.00
Maximum of Months 0.104078E+11 0.397510E+10 0.643307E+10 0.425213E+10 0.251990E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.207950E+10 0.271648E+10 0.170550E+10 0.663716E+09 0.104178E+10 0.00 0.00
February 0.244756E+10 0.199735E+10 0.176155E+10 0.649178E+09 0.111237E+10 0.00 0.00
March 0.416951E+10 0.142688E+10 0.252902E+10 0.101094E+10 0.151808E+10 0.00 0.00
April 0.597533E+10 0.532618E+09 0.297484E+10 0.139509E+10 0.157975E+10 0.00 0.00
May 0.681412E+10 98710896.68 0.291079E+10 0.123470E+10 0.167609E+10 0.00 0.00
June 0.655366E+10 73479914.97 0.264582E+10 0.102771E+10 0.161811E+10 0.00 0.00
July 0.505677E+10 20955766.78 0.202878E+10 0.394598E+09 0.163418E+10 0.00 0.00
August 0.435517E+10 68284712.84 0.186322E+10 0.331151E+09 0.153207E+10 0.00 0.00
September 0.407490E+10 0.227787E+09 0.198210E+10 0.581887E+09 0.140021E+10 0.00 0.00
October 0.397941E+10 0.111295E+10 0.213182E+10 0.848889E+09 0.128294E+10 0.00 0.00
November 0.296303E+10 0.195916E+10 0.186638E+10 0.795438E+09 0.107094E+10 0.00 0.00
December 0.208632E+10 0.266446E+10 0.165030E+10 0.629299E+09 0.102101E+10 0.00 0.00
               
Annual Sum or Average 0.505553E+11 0.128991E+11 0.260501E+11 0.956259E+10 0.164875E+11 0.00 0.00
Minimum of Months 0.207950E+10 20955766.78 0.165030E+10 0.331151E+09 0.102101E+10 0.00 0.00
Maximum of Months 0.681412E+10 0.271648E+10 0.297484E+10 0.139509E+10 0.167609E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.39 10.38 7.87 1.20 0.38 63.33 149.51 0.00
February 16.97 12.78 9.69 1.81 4.63 75.94 163.32 0.01
March 22.37 15.60 11.23 1.86 10.07 92.70 193.23 0.00
April 29.13 18.33 11.93 1.64 16.17 89.20 259.84 0.01
May 32.98 21.97 16.72 2.17 21.14 97.31 248.85 0.02
June 33.59 24.39 20.62 1.55 23.45 107.22 203.36 0.06
July 31.67 26.29 24.51 2.27 24.88 132.35 83.14 0.02
August 30.03 26.31 25.11 1.75 23.81 127.44 60.46 0.00
September 28.75 24.70 23.21 1.33 20.22 105.62 105.60 0.08
October 25.09 18.74 15.36 0.77 12.83 75.09 190.08 0.00
November 19.63 14.46 10.99 0.66 5.78 58.54 201.10 0.00
December 14.52 10.88 7.89 0.97 0.94 60.91 153.60 0.01
                 
Annual Sum or Average 24.88 18.77 15.46 1.50 13.74 90.59 167.44 0.02
Minimum of Months 13.39 10.38 7.87 0.66 0.38 58.54 60.46 0.00
Maximum of Months 33.59 26.31 25.11 2.27 24.88 132.35 259.84 0.08



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 23.60 12-JAN-14:00 14.20 7.40 3.80 8.15 163.00 476.00
February 27.10 22-FEB-14:00 16.20 9.10 1.50 15.39 225.00 451.00
March 35.60 28-MAR-14:00 18.50 7.70 0.00 19.52 182.00 699.00
April 40.30 15-APR-14:00 20.67 10.00 6.70 28.43 201.00 649.50
May 44.50 03-MAY-14:00 20.64 5.30 2.80 28.91 150.00 809.00
June 44.60 07-JUN-15:00 21.53 9.10 3.10 28.43 167.00 640.50
July 40.40 02-JUL-15:00 26.36 21.60 2.10 29.87 200.00 545.50
August 37.30 07-AUG-14:00 26.58 22.90 3.00 29.87 311.00 370.00
September 37.50 17-SEP-19:00 27.68 24.60 0.20 28.59 0.00 0.00
October 36.40 02-OCT-14:20 21.05 13.00 1.80 21.61 187.33 678.83
November 30.30 04-NOV-13:00 17.17 8.90 1.10 14.84 155.00 710.00
December 24.60 28-DEC-13:00 15.30 8.90 2.80 10.88 181.50 535.00
                 
Annual Sum or Average                
Minimum of Months 23.60   14.20 5.30 0.00 8.15 0.00 0.00
Maximum of Months 44.60   27.68 24.60 6.70 29.87 311.00 809.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 4.80 05-JAN-06:00 4.73 4.60 0.00 -10.2 0.00 0.00
February 6.90 02-FEB-05:00 6.67 6.50 0.00 -7.8 0.00 0.00
March 13.30 01-MAR-03:00 10.56 8.30 0.80 -1.4 0.00 0.00
April 17.40 11-APR-04:00 13.58 10.90 0.00 3.06 0.00 0.00
May 22.70 13-MAY-04:00 20.32 19.30 2.10 20.40 0.00 0.00
June 23.30 18-JUN-04:00 21.80 21.20 2.70 17.75 0.00 0.00
July 23.20 19-JUL-02:00 23.20 23.20 2.30 15.39 0.00 0.00
August 23.40 15-AUG-23:00 22.91 22.80 2.40 21.78 0.00 0.00
September 23.00 27-SEP-04:00 20.74 19.70 0.00 10.30 0.00 0.00
October 15.50 31-OCT-04:00 14.07 13.20 0.00 1.80 0.00 0.00
November 9.50 27-NOV-05:00 8.75 8.10 0.00 -5.0 0.00 0.00
December 5.00 21-DEC-04:00 4.08 3.00 0.00 -10.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 4.80   4.08 3.00 0.00 -10.5 0.00 0.00
Maximum of Months 23.40   23.20 23.20 2.70 21.78 0.00 0.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 15.62 17-JAN-14:00 18.20 14.10 1.00 11.07 198.00 56.50
February 18.14 25-FEB-16:00 21.20 16.60 5.90 10.88 107.50 156.50
March 21.38 10-MAR-18:49 29.25 17.73 2.10 21.44 0.00 0.00
April 23.42 18-APR-13:00 37.10 17.80 5.70 23.49 233.50 671.50
May 27.40 22-MAY-22:00 29.40 26.80 0.00 20.40 0.00 0.00
June 28.92 28-JUN-12:00 34.40 27.50 1.00 25.49 332.50 501.50
July 29.18 01-JUL-16:00 37.20 26.80 2.30 25.66 196.00 196.00
August 29.17 27-AUG-15:00 35.10 27.40 1.30 29.55 256.00 129.00
September 28.10 14-SEP-16:00 33.70 26.40 1.40 26.48 122.50 108.50
October 23.06 06-OCT-10:00 28.60 20.80 1.30 20.22 327.00 348.50
November 18.93 08-NOV-17:10 27.55 14.47 0.17 16.67 28.00 65.33
December 15.64 29-DEC-19:00 16.80 14.90 4.80 13.54 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 15.62   16.80 14.10 0.00 10.88 0.00 0.00
Maximum of Months 29.18   37.20 27.50 5.90 29.55 332.50 671.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.10 17-JAN-13:00 17.80 15.48 0.90 9.72 260.50 81.50
February 16.60 25-FEB-16:00 21.20 18.14 5.90 10.88 107.50 156.50
March 18.30 10-MAR-19:00 27.70 21.26 2.10 21.44 0.00 0.00
April 19.30 26-APR-23:10 28.53 22.04 0.00 15.61 0.00 0.00
May 26.80 22-MAY-22:00 29.40 27.40 0.00 20.40 0.00 0.00
June 27.50 28-JUN-12:00 34.40 28.92 1.00 25.49 332.50 501.50
July 27.30 18-JUL-06:19 29.10 27.70 1.17 26.48 20.00 0.00
August 28.80 12-AUG-07:00 29.10 28.83 2.90 26.81 113.00 6.50
September 26.50 12-SEP-14:00 30.50 27.38 0.90 25.99 260.00 20.00
October 21.10 06-OCT-08:00 25.50 22.41 0.30 17.21 239.00 159.00
November 16.30 08-NOV-21:19 20.10 17.59 0.00 10.95 0.00 0.00
December 14.90 29-DEC-20:10 16.72 15.59 4.73 13.13 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 14.10   16.72 15.48 0.00 9.72 0.00 0.00
Maximum of Months 28.80   34.40 28.92 5.90 26.81 332.50 501.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 20.92 27.26 0.00
February 18.00 13.00 16.00 21.74 33.91 0.00
March 18.00 13.00 16.00 24.21 44.04 0.00
April 18.00 13.00 16.00 27.79 55.91 0.00
May 18.00 13.00 16.00 31.48 58.43 0.00
June 18.00 13.00 16.00 34.27 54.82 0.00
July 18.00 13.00 16.00 35.42 39.75 0.00
August 18.00 13.00 16.00 34.60 34.68 0.00
September 18.00 13.00 16.00 32.04 35.55 0.00
October 18.00 13.00 16.00 28.44 39.44 0.00
November 18.00 13.00 16.00 24.77 33.85 0.00
December 18.00 13.00 16.00 22.02 26.79 0.00
             
Annual Sum or Average 18.00 13.00 16.00 28.18 40.37 0.00
Minimum of Months 18.00 13.00 16.00 20.92 26.79 0.00
Maximum of Months 18.00 13.00 16.00 35.42 58.43 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.313245E+11 -0.303042E+11 0.00 0.00 744.00 0.00 -0.102032E+10 58.97 0.00 0.00
February 0.278778E+11 -0.269554E+11 0.00 0.00 672.00 0.00 -922328717.7 58.97 0.00 0.00
March 0.305995E+11 -0.295748E+11 0.00 0.00 744.00 0.00 -0.102473E+10 58.98 0.00 0.00
April 0.250564E+11 -0.240684E+11 0.00 0.00 720.00 0.00 -987953811.3 58.97 0.00 0.00
May 0.237327E+11 -0.227111E+11 0.00 0.00 744.00 0.00 -0.102161E+10 58.97 0.00 0.00
June 0.211658E+11 -0.201766E+11 0.00 0.00 720.00 0.00 -989229059.1 58.96 0.00 0.00
July 0.193127E+11 -0.182960E+11 0.00 0.00 744.00 0.00 -0.101665E+10 58.96 0.00 0.00
August 0.217655E+11 -0.207448E+11 0.00 0.00 744.00 0.00 -0.102071E+10 58.97 0.00 0.00
September 0.218144E+11 -0.208288E+11 0.00 0.00 720.00 0.00 -985584850.1 58.97 0.00 0.00
October 0.253561E+11 -0.243388E+11 0.00 0.00 744.00 0.00 -0.101738E+10 58.97 0.00 0.00
November 0.277040E+11 -0.267188E+11 0.00 0.00 720.00 0.00 -985113992.5 58.98 0.00 0.00
December 0.297406E+11 -0.287224E+11 0.00 0.00 744.00 0.00 -0.101817E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.305450E+12 -0.293440E+12 0.00 0.00 8760.00 0.00 -0.120098E+11 58.97 0.00 0.00
Minimum of Months 0.193127E+11 -0.303042E+11 0.00 0.00 672.00 0.00 -0.102473E+10 58.96 0.00 0.00
Maximum of Months 0.313245E+11 -0.182960E+11 0.00 0.00 744.00 0.00 -922328717.7 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.64 0.61 01-JAN-07:49 5229.40 34.80 297.00 284.33 1049.42 24.95 250.50 263.50
February 303.83 0.64 0.61 01-FEB-07:49 3042.78 28.08 195.67 268.33 918.85 20.43 147.00 236.00
March 364.50 0.64 0.61 01-MAR-07:40 1477.59 17.65 7.50 315.00 789.00 20.23 129.17 279.83
April 379.83 0.65 0.61 01-APR-07:10 982.72 16.01 0.00 322.67 578.92 18.84 10.17 280.50
May 406.00 0.65 0.61 01-MAY-06:49 833.18 15.69 0.00 340.50 488.09 18.64 0.67 292.67
June 386.67 0.65 0.61 01-JUN-06:00 829.12 15.40 0.00 326.00 473.29 18.30 0.00 274.67
July 379.83 0.64 0.61 01-JUL-06:40 948.58 15.96 0.00 324.17 486.34 18.75 3.33 260.67
August 372.50 0.65 0.61 01-AUG-06:49 1073.85 16.05 0.00 313.50 530.54 18.80 51.17 252.33
September 344.33 0.64 0.61 01-SEP-06:00 1299.80 16.77 0.00 294.33 664.41 19.62 123.67 248.67
October 347.33 0.65 0.61 01-OCT-06:00 2269.30 18.78 39.33 300.17 883.15 19.96 131.00 269.67
November 317.83 0.64 0.61 01-NOV-07:19 7147.17 34.42 292.17 279.00 1080.60 22.63 172.83 259.17
December 315.50 0.64 0.61 01-DEC-07:30 5499.61 34.82 293.00 280.17 1253.63 27.25 275.83 276.00
                         
Annual Sum or Average 4237.50 0.64     2399.52 21.42 1124.67 3648.17 745.67 20.52 1295.33 3193.67
Minimum of Months 303.83 0.64 0.61   829.12 15.40 0.00 268.33 473.29 18.30 0.00 236.00
Maximum of Months 406.00 0.65 0.61   7147.17 34.82 297.00 340.50 1253.63 27.25 275.83 292.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.66 0.61 01-JAN-07:49 1408.41 17.63 83.67 252.17 757.96 18.92 74.33 200.50
February 303.83 0.65 0.61 01-FEB-07:49 1747.84 17.40 75.00 246.17 948.69 18.63 69.50 199.00
March 364.50 0.64 0.61 01-MAR-07:40 1690.85 15.45 57.83 305.67 849.32 14.19 2.67 264.67
April 379.83 0.65 0.61 01-APR-06:49 2045.00 11.68 0.00 316.00 1092.67 13.06 0.00 279.50
May 406.00 0.64 0.61 01-MAY-06:10 2207.47 11.81 0.00 344.83 801.02 13.00 0.00 301.00
June 386.67 0.65 0.61 01-JUN-06:40 1740.72 11.88 0.00 329.00 689.86 12.82 0.00 278.83
July 379.83 0.64 0.61 01-JUL-06:10 1427.28 12.51 0.00 328.33 612.22 13.14 0.00 260.00
August 372.50 0.65 0.61 01-AUG-06:19 1286.70 12.44 0.00 311.50 583.45 13.09 0.00 246.83
September 344.33 0.65 0.61 01-SEP-06:49 1436.76 13.06 8.50 289.17 722.50 13.86 5.50 230.67
October 347.33 0.65 0.61 01-OCT-06:49 1588.53 17.03 85.83 283.83 776.70 16.43 55.00 240.67
November 317.83 0.65 0.61 01-NOV-07:10 1431.06 17.88 82.50 254.67 711.90 17.54 56.17 210.67
December 315.50 0.65 0.61 01-DEC-07:40 1471.06 18.19 87.83 247.67 805.64 19.64 79.67 206.17
                         
Annual Sum or Average 4237.50 0.65     1635.41 14.54 481.17 3509.00 777.75 15.15 342.83 2918.50
Minimum of Months 303.83 0.64 0.61   1286.70 11.68 0.00 246.17 583.45 12.82 0.00 199.00
Maximum of Months 406.00 0.66 0.61   2207.47 18.19 87.83 344.83 1092.67 19.64 79.67 301.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.67 0.61 01-JAN-08:39 450.37 0.00 0.00 225.50 281.20 0.00 0.00 101.67
February 303.83 0.66 0.61 01-FEB-08:20 520.95 0.00 0.00 237.00 323.35 0.00 0.00 146.67
March 364.50 0.64 0.61 01-MAR-07:00 616.84 0.00 0.00 302.83 381.62 0.00 0.00 236.67
April 379.83 0.65 0.61 01-APR-07:10 664.67 0.00 0.00 325.67 417.80 0.00 0.00 278.67
May 406.00 0.64 0.61 01-MAY-06:19 802.65 0.00 0.00 360.00 471.90 0.00 0.00 322.83
June 386.67 0.64 0.61 01-JUN-06:49 896.14 0.00 0.00 342.50 498.79 0.00 0.00 300.17
July 379.83 0.63 0.61 01-JUL-06:19 922.74 0.00 0.00 336.83 477.54 0.00 0.00 278.83
August 372.50 0.64 0.61 01-AUG-06:40 827.49 0.00 0.00 317.17 427.45 0.00 0.00 249.33
September 344.33 0.64 0.61 01-SEP-06:00 710.28 0.00 0.00 290.67 393.92 0.00 0.00 216.67
October 347.33 0.66 0.61 01-OCT-07:10 543.29 0.00 0.00 279.17 345.60 0.00 0.00 198.00
November 317.83 0.66 0.61 01-NOV-07:40 456.83 0.00 0.00 235.17 304.39 0.00 0.00 132.33
December 315.50 0.67 0.61 01-DEC-08:20 442.31 0.00 0.00 223.17 279.49 0.00 0.00 89.33
                         
Annual Sum or Average 4237.50 0.65     667.50 0.00 0.00 3475.67 389.74 0.00 0.00 2551.17
Minimum of Months 303.83 0.63 0.61   442.31 0.00 0.00 223.17 279.49 0.00 0.00 89.33
Maximum of Months 406.00 0.67 0.61   922.74 0.00 0.00 360.00 498.79 0.00 0.00 322.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.66 0.61 01-JAN-08:50 1413.08 17.63 82.50 250.33 745.72 18.67 71.50 201.67
February 303.83 0.65 0.61 01-FEB-08:39 1662.73 17.31 77.00 247.67 663.34 16.83 44.00 201.83
March 364.50 0.64 0.61 01-MAR-08:09 1645.38 15.39 57.33 306.00 822.80 14.13 1.83 264.50
April 379.83 0.65 0.61 01-APR-07:30 1881.74 11.68 0.00 319.50 978.65 13.07 0.00 282.83
May 406.00 0.64 0.61 01-MAY-07:10 1807.33 11.79 0.00 342.00 934.99 12.97 0.00 301.67
June 386.67 0.65 0.61 01-JUN-07:10 1804.63 11.96 0.00 329.83 716.76 12.90 0.00 284.17
July 379.83 0.64 0.61 01-JUL-06:00 1378.71 12.53 0.00 325.67 605.46 13.16 0.00 263.17
August 372.50 0.65 0.61 01-AUG-07:10 1272.69 12.41 0.00 311.33 626.22 13.05 0.00 248.17
September 344.33 0.64 0.61 01-SEP-07:30 1410.50 13.13 8.50 290.00 698.44 13.92 5.50 236.00
October 347.33 0.65 0.61 01-OCT-07:30 1689.01 16.96 84.83 281.00 848.39 16.34 54.00 242.00
November 317.83 0.65 0.61 01-NOV-07:00 1480.96 17.90 84.83 257.67 720.42 17.28 55.00 211.83
December 315.50 0.65 0.61 01-DEC-08:20 1293.14 18.30 87.33 252.17 650.84 17.73 56.33 204.50
                         
Annual Sum or Average 4237.50 0.65     1569.62 14.54 482.33 3513.17 755.35 14.83 288.17 2942.33
Minimum of Months 303.83 0.64 0.61   1272.69 11.68 0.00 247.67 605.46 12.90 0.00 201.67
Maximum of Months 406.00 0.66 0.61   1881.74 18.30 87.33 342.00 978.65 18.67 71.50 301.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.64 0.61 01-JAN-07:00 5130.05 30.67 258.67 276.50 1080.85 20.87 85.17 263.83
February 303.83 0.64 0.61 01-FEB-07:49 3016.51 25.57 194.00 267.83 950.11 15.67 0.00 237.17
March 364.50 0.64 0.61 01-MAR-07:40 1455.73 11.86 7.50 313.67 815.73 16.26 0.00 281.83
April 379.83 0.65 0.61 01-APR-07:10 970.59 10.73 0.00 320.17 598.55 15.38 0.00 283.17
May 406.00 0.65 0.61 01-MAY-06:49 820.23 10.24 0.00 338.33 503.19 14.95 0.00 296.17
June 386.67 0.65 0.61 01-JUN-06:00 814.68 9.84 0.00 325.33 487.37 14.45 0.00 277.50
July 379.83 0.64 0.61 01-JUL-06:40 926.96 9.83 0.00 322.50 499.91 14.41 0.00 264.33
August 372.50 0.65 0.61 01-AUG-06:49 1046.53 9.89 0.00 312.00 544.67 14.35 0.00 254.50
September 344.33 0.64 0.61 01-SEP-06:00 1270.45 10.66 0.00 294.00 683.06 15.30 0.00 250.67
October 347.33 0.65 0.61 01-OCT-06:00 2255.69 13.22 39.33 301.83 915.79 15.53 5.33 271.67
November 317.83 0.64 0.61 01-NOV-07:19 7119.93 33.41 288.33 277.83 1123.69 18.15 45.17 263.67
December 315.50 0.64 0.61 01-DEC-07:40 5415.75 32.21 273.33 276.17 1276.95 22.72 113.50 272.50
                         
Annual Sum or Average 4237.50 0.64     2368.49 16.61 1061.17 3626.17 768.69 16.35 249.17 3217.00
Minimum of Months 303.83 0.64 0.61   814.68 9.83 0.00 267.83 487.37 14.35 0.00 237.17
Maximum of Months 406.00 0.65 0.61   7119.93 33.41 288.33 338.33 1276.95 22.72 113.50 296.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.66 0.61 01-JAN-07:49 1401.92 15.60 84.33 251.83 733.15 15.14 55.17 201.00
February 303.83 0.65 0.61 01-FEB-07:49 1742.61 15.21 75.33 245.67 968.45 16.85 70.00 201.83
March 364.50 0.64 0.61 01-MAR-07:40 1697.60 12.81 57.83 304.83 872.79 11.71 2.83 267.33
April 379.83 0.65 0.61 01-APR-06:49 2033.91 8.42 0.00 314.83 1117.79 10.77 0.00 282.50
May 406.00 0.64 0.61 01-MAY-06:10 2100.19 8.45 0.00 344.33 827.26 10.77 0.00 305.17
June 386.67 0.65 0.61 01-JUN-06:40 1728.87 8.66 0.00 328.33 712.17 10.73 0.00 283.50
July 379.83 0.64 0.61 01-JUL-06:10 1389.78 9.10 0.00 327.17 635.10 10.93 0.00 264.00
August 372.50 0.65 0.61 01-AUG-06:19 1272.50 9.07 0.00 311.00 658.83 10.81 0.00 251.17
September 344.33 0.65 0.61 01-SEP-06:49 1432.36 9.82 8.50 288.17 740.98 11.49 5.50 237.00
October 347.33 0.65 0.61 01-OCT-06:49 1572.48 14.64 81.83 283.50 797.34 14.52 55.50 244.17
November 317.83 0.65 0.61 01-NOV-07:10 1329.36 13.75 59.00 253.67 731.65 15.56 56.50 214.67
December 315.50 0.66 0.61 01-DEC-07:40 1464.61 16.15 87.83 247.33 822.19 17.81 79.83 210.17
                         
Annual Sum or Average 4237.50 0.65     1608.38 11.57 454.67 3500.67 800.71 12.88 325.33 2962.50
Minimum of Months 303.83 0.64 0.61   1272.50 8.42 0.00 245.67 635.10 10.73 0.00 201.00
Maximum of Months 406.00 0.66 0.61   2100.19 16.15 87.83 344.33 1117.79 17.81 79.83 305.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.67 0.61 01-JAN-08:39 441.09 0.00 0.00 221.50 288.57 0.00 0.00 116.67
February 303.83 0.66 0.61 01-FEB-08:20 511.05 0.00 0.00 234.33 332.25 0.00 0.00 152.83
March 364.50 0.64 0.61 01-MAR-07:00 606.20 0.00 0.00 300.33 392.55 0.00 0.00 241.00
April 379.83 0.65 0.61 01-APR-07:10 655.23 0.00 0.00 324.83 430.59 0.00 0.00 282.33
May 406.00 0.64 0.61 01-MAY-06:30 787.27 0.00 0.00 356.17 486.43 0.00 0.00 325.00
June 386.67 0.64 0.61 01-JUN-06:49 879.81 0.00 0.00 340.50 515.22 0.00 0.00 304.33
July 379.83 0.64 0.61 01-JUL-06:19 903.51 0.00 0.00 334.17 490.83 0.00 0.00 281.33
August 372.50 0.64 0.61 01-AUG-06:40 809.72 0.00 0.00 315.33 439.36 0.00 0.00 253.50
September 344.33 0.65 0.61 01-SEP-06:00 695.82 0.00 0.00 289.00 404.84 0.00 0.00 220.83
October 347.33 0.66 0.61 01-OCT-07:19 533.66 0.00 0.00 276.50 355.31 0.00 0.00 205.67
November 317.83 0.66 0.61 01-NOV-07:49 448.06 0.00 0.00 233.00 312.52 0.00 0.00 144.17
December 315.50 0.67 0.61 01-DEC-08:20 432.98 0.00 0.00 219.33 286.65 0.00 0.00 103.33
                         
Annual Sum or Average 4237.50 0.65     654.76 0.00 0.00 3445.00 400.97 0.00 0.00 2631.00
Minimum of Months 303.83 0.64 0.61   432.98 0.00 0.00 219.33 286.65 0.00 0.00 103.33
Maximum of Months 406.00 0.67 0.61   903.51 0.00 0.00 356.17 515.22 0.00 0.00 325.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.66 0.61 01-JAN-08:50 1406.70 15.58 82.83 249.50 761.98 16.83 72.00 204.17
February 303.83 0.65 0.61 01-FEB-08:39 1656.77 15.12 77.00 246.67 681.65 14.81 44.33 205.50
March 364.50 0.64 0.61 01-MAR-08:09 1651.00 12.76 57.33 305.50 845.71 11.66 1.83 268.50
April 379.83 0.65 0.61 01-APR-07:30 1870.60 8.42 0.00 318.83 964.50 10.78 0.00 283.17
May 406.00 0.65 0.61 01-MAY-07:10 1792.11 8.45 0.00 341.17 960.72 10.75 0.00 304.50
June 386.67 0.65 0.61 01-JUN-07:10 1794.68 8.64 0.00 329.67 741.16 10.74 0.00 288.33
July 379.83 0.64 0.61 01-JUL-06:00 1347.38 9.13 0.00 324.50 623.83 10.95 0.00 268.17
August 372.50 0.65 0.61 01-AUG-07:10 1258.54 9.05 0.00 310.17 643.06 10.78 0.00 252.83
September 344.33 0.64 0.61 01-SEP-07:30 1405.39 9.87 8.50 290.00 717.02 11.55 5.50 240.33
October 347.33 0.65 0.61 01-OCT-07:30 1689.90 14.87 85.00 280.33 868.71 14.44 54.17 246.00
November 317.83 0.65 0.61 01-NOV-07:00 1476.23 15.84 85.00 256.83 739.90 15.26 55.00 216.67
December 315.50 0.65 0.61 01-DEC-08:20 1287.98 16.29 87.33 251.67 667.01 15.64 56.33 208.50
                         
Annual Sum or Average 4237.50 0.65     1560.70 11.74 483.00 3504.83 772.25 12.67 289.17 2986.67
Minimum of Months 303.83 0.64 0.61   1258.54 8.42 0.00 246.67 623.83 10.74 0.00 204.17
Maximum of Months 406.00 0.66 0.61   1870.60 16.29 87.33 341.17 964.50 16.83 72.00 304.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.64 0.61 01-JAN-07:00 5129.79 30.66 258.67 276.50 1082.07 20.86 85.17 263.83
February 303.83 0.64 0.61 01-FEB-07:49 3017.09 25.55 194.00 267.83 951.25 15.65 0.00 237.33
March 364.50 0.64 0.61 01-MAR-07:40 1456.41 11.82 7.50 313.67 816.67 16.24 0.00 281.83
April 379.83 0.65 0.61 01-APR-07:10 970.87 10.69 0.00 320.17 599.12 15.37 0.00 283.33
May 406.00 0.65 0.61 01-MAY-06:49 820.44 10.20 0.00 338.33 503.68 14.93 0.00 296.17
June 386.67 0.65 0.61 01-JUN-06:00 814.96 9.80 0.00 325.33 487.88 14.43 0.00 277.67
July 379.83 0.64 0.61 01-JUL-06:40 927.68 9.80 0.00 322.50 500.61 14.39 0.00 265.00
August 372.50 0.65 0.61 01-AUG-06:49 1047.44 9.85 0.00 312.00 545.51 14.34 0.00 254.67
September 344.33 0.64 0.61 01-SEP-06:00 1271.35 10.62 0.00 294.00 684.03 15.28 0.00 250.67
October 347.33 0.65 0.61 01-OCT-06:00 2256.24 13.18 39.33 301.83 916.80 15.52 5.33 271.67
November 317.83 0.64 0.61 01-NOV-07:19 7119.82 33.40 288.33 277.83 1124.81 18.13 45.17 263.67
December 315.50 0.64 0.61 01-DEC-07:40 5415.31 32.19 273.33 276.17 1278.23 22.71 113.50 272.50
                         
Annual Sum or Average 4237.50 0.64     2368.86 16.58 1061.17 3626.17 769.57 16.33 249.17 3218.33
Minimum of Months 303.83 0.64 0.61   814.96 9.80 0.00 267.83 487.88 14.34 0.00 237.33
Maximum of Months 406.00 0.65 0.61   7119.82 33.40 288.33 338.33 1278.23 22.71 113.50 296.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.66 0.61 01-JAN-07:49 1401.67 15.59 84.33 251.83 733.67 15.13 55.17 201.33
February 303.83 0.65 0.61 01-FEB-07:49 1742.37 15.20 75.33 245.50 969.07 16.85 70.00 201.83
March 364.50 0.64 0.61 01-MAR-07:40 1697.34 12.79 57.83 304.83 873.48 11.70 2.83 267.33
April 379.83 0.65 0.61 01-APR-06:49 2033.75 8.41 0.00 314.83 1118.43 10.76 0.00 282.67
May 406.00 0.64 0.61 01-MAY-06:10 2100.13 8.44 0.00 344.33 827.95 10.76 0.00 305.17
June 386.67 0.65 0.61 01-JUN-06:40 1729.09 8.64 0.00 328.33 712.90 10.72 0.00 283.67
July 379.83 0.64 0.61 01-JUL-06:10 1390.42 9.09 0.00 327.17 635.96 10.92 0.00 264.33
August 372.50 0.65 0.61 01-AUG-06:19 1273.19 9.06 0.00 311.00 659.70 10.81 0.00 251.17
September 344.33 0.65 0.61 01-SEP-06:49 1432.68 9.81 8.50 288.17 741.81 11.48 5.50 237.17
October 347.33 0.65 0.61 01-OCT-06:49 1572.17 14.63 81.83 283.50 797.95 14.51 55.50 244.17
November 317.83 0.65 0.61 01-NOV-07:10 1329.00 13.74 59.00 253.67 732.15 15.55 56.50 214.67
December 315.50 0.66 0.61 01-DEC-07:40 1464.34 16.14 87.83 247.33 822.71 17.80 79.83 210.17
                         
Annual Sum or Average 4237.50 0.65     1608.39 11.55 454.67 3500.50 801.39 12.87 325.33 2963.67
Minimum of Months 303.83 0.64 0.61   1273.19 8.41 0.00 245.50 635.96 10.72 0.00 201.33
Maximum of Months 406.00 0.66 0.61   2100.13 16.14 87.83 344.33 1118.43 17.80 79.83 305.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.67 0.61 01-JAN-08:39 440.97 0.00 0.00 221.50 288.80 0.00 0.00 117.17
February 303.83 0.66 0.61 01-FEB-08:20 510.95 0.00 0.00 234.33 332.51 0.00 0.00 153.33
March 364.50 0.64 0.61 01-MAR-07:00 606.11 0.00 0.00 300.33 392.86 0.00 0.00 241.00
April 379.83 0.65 0.61 01-APR-07:10 655.12 0.00 0.00 324.83 430.92 0.00 0.00 282.33
May 406.00 0.64 0.61 01-MAY-06:30 787.31 0.00 0.00 356.17 486.87 0.00 0.00 325.00
June 386.67 0.64 0.61 01-JUN-06:49 880.04 0.00 0.00 340.50 515.77 0.00 0.00 304.50
July 379.83 0.64 0.61 01-JUL-06:19 904.08 0.00 0.00 334.17 491.50 0.00 0.00 281.67
August 372.50 0.64 0.61 01-AUG-06:40 810.24 0.00 0.00 315.33 439.99 0.00 0.00 253.50
September 344.33 0.65 0.61 01-SEP-06:00 696.04 0.00 0.00 289.00 405.31 0.00 0.00 221.00
October 347.33 0.66 0.61 01-OCT-07:19 533.51 0.00 0.00 276.50 355.57 0.00 0.00 206.00
November 317.83 0.66 0.61 01-NOV-07:49 447.82 0.00 0.00 233.00 312.70 0.00 0.00 144.33
December 315.50 0.67 0.61 01-DEC-08:20 432.83 0.00 0.00 219.33 286.86 0.00 0.00 103.50
                         
Annual Sum or Average 4237.50 0.65     654.83 0.00 0.00 3445.00 401.36 0.00 0.00 2633.33
Minimum of Months 303.83 0.64 0.61   432.83 0.00 0.00 219.33 286.86 0.00 0.00 103.50
Maximum of Months 406.00 0.67 0.61   904.08 0.00 0.00 356.17 515.77 0.00 0.00 325.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.66 0.61 01-JAN-08:50 1406.46 15.57 82.83 249.33 762.50 16.83 72.00 204.17
February 303.83 0.65 0.61 01-FEB-08:39 1656.59 15.11 77.00 246.67 682.26 14.81 44.33 205.67
March 364.50 0.64 0.61 01-MAR-08:09 1650.77 12.75 57.33 305.33 846.40 11.65 1.83 268.50
April 379.83 0.65 0.61 01-APR-07:30 1870.45 8.41 0.00 318.83 965.12 10.77 0.00 283.17
May 406.00 0.65 0.61 01-MAY-07:10 1792.07 8.44 0.00 341.17 961.41 10.74 0.00 304.83
June 386.67 0.65 0.61 01-JUN-07:10 1794.84 8.62 0.00 329.67 741.91 10.73 0.00 288.33
July 379.83 0.64 0.61 01-JUL-06:00 1348.05 9.11 0.00 324.50 624.69 10.94 0.00 268.33
August 372.50 0.65 0.61 01-AUG-07:10 1259.24 9.04 0.00 310.17 643.93 10.77 0.00 253.00
September 344.33 0.64 0.61 01-SEP-07:30 1405.74 9.86 8.50 290.00 717.85 11.54 5.50 240.50
October 347.33 0.65 0.61 01-OCT-07:30 1689.70 14.86 85.00 280.33 869.31 14.44 54.17 246.00
November 317.83 0.65 0.61 01-NOV-07:00 1475.88 15.83 85.00 256.83 740.39 15.25 55.00 216.83
December 315.50 0.65 0.61 01-DEC-08:20 1287.74 16.28 87.33 251.33 667.52 15.64 56.33 208.50
                         
Annual Sum or Average 4237.50 0.65     1560.73 11.73 483.00 3504.17 772.92 12.66 289.17 2987.83
Minimum of Months 303.83 0.64 0.61   1259.24 8.41 0.00 246.67 624.69 10.73 0.00 204.17
Maximum of Months 406.00 0.66 0.61   1870.45 16.28 87.33 341.17 965.12 16.83 72.00 304.83



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 9289584.61 2187.61 05-JAN-06:20 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 5407126.38 1406.81 23-DEC-05:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 14696711.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 9289584.61 2187.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.148577E+10 48618.94 05-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 705417.59 793.05 02-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.403160E+09 32724.15 21-DEC-06:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.188964E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148577E+10 48618.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.144119E+10 36830.44 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.127732E+09 18595.42 11-FEB-06:08 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.417489E+09 54282.01 21-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.198641E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144119E+10 54282.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.698593E+09 33413.02 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.114089E+09 16456.67 11-FEB-06:06 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.228041E+09 35672.38 21-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.104072E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.698593E+09 35672.38   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 21434756.99 5489.90 03-JAN-06:50 0.00 0.00 0.00 0.00 0.00
February 43345650.50 14802.39 11-FEB-06:08 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 64780407.49     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 43345650.50 14802.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.650368E+09 20942.91 02-JAN-06:06 0.00 0.00 0.00 0.00 0.00
February 99794552.68 15495.28 11-FEB-06:20 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.188810E+09 19186.18 23-DEC-06:08 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.938972E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.650368E+09 20942.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.110795E+10 12395.21 02-JAN-04:02 0.00 0.00 0.00 0.00 0.00
February 79686612.90 6165.88 02-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.263313E+09 11673.30 23-DEC-05:47 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.145095E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.110795E+10 12395.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.499266E+09 72331.39 02-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.499266E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.499266E+09 72331.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.166130E+10 18850.48 02-JAN-04:02 0.00 0.00 0.00 0.00 0.00
February 0.395577E+09 18567.81 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 1854131.43 503.80 01-MAR-06:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 64166451.96 3676.09 27-NOV-06:05 0.00 0.00 0.00 0.00 0.00
December 0.962798E+09 18667.45 23-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.308569E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.166130E+10 18850.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.727174E+09 13276.34 02-JAN-04:02 0.00 0.00 0.00 0.00 0.00
February 0.171514E+09 13075.36 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 212782.67 183.82 01-MAR-06:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 19177636.26 1965.31 27-NOV-06:20 0.00 0.00 0.00 0.00 0.00
December 0.430842E+09 13139.61 21-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.134892E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.727174E+09 13276.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.547569E+09 18767.79 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.133029E+09 18587.29 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.218993E+09 16839.66 23-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.899590E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.547569E+09 18767.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.775182E+09 13171.09 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.198498E+09 13043.70 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 14826396.31 997.49 25-NOV-07:30 0.00 0.00 0.00 0.00 0.00
December 0.412591E+09 11643.62 23-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.140110E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.775182E+09 13171.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.551477E+11 0.550594E+11 124272.76 02-JAN-06:03 81435.71 0.31
February 0.00 0.00 0.727524E+11 0.725854E+11 152978.55 25-FEB-04:02 109610.20 0.49
March 0.00 0.00 0.129389E+12 0.127435E+12 218056.73 29-MAR-05:02 153225.56 0.67
April 0.00 0.00 0.185927E+12 0.179024E+12 266193.40 17-APR-05:03 185838.51 0.81
May 0.00 0.00 0.225479E+12 0.192353E+12 281586.37 22-MAY-05:02 180519.56 0.82
June 0.00 0.00 0.264382E+12 0.197548E+12 301171.54 29-JUN-05:02 177714.34 0.84
July 0.00 0.00 0.305430E+12 0.191305E+12 305776.95 17-JUL-05:03 186611.97 0.86
August 0.00 0.00 0.330330E+12 0.203546E+12 311690.62 28-AUG-05:03 183803.46 0.89
September 0.00 0.00 0.227887E+12 0.148271E+12 290773.28 05-SEP-03:02 178538.81 0.75
October 0.00 0.00 0.156275E+12 0.139563E+12 262460.46 04-OCT-05:02 172680.96 0.73
November 0.00 0.00 0.107927E+12 0.106676E+12 171389.39 06-NOV-06:03 139989.89 0.63
December 0.00 0.00 0.763068E+11 0.763068E+11 117445.95 29-DEC-06:03 117445.95 0.41
                 
Annual Sum or Average 0.00 0.00 0.213723E+13 0.168967E+13       0.68
Minimum of Months 0.00 0.00 0.551477E+11 0.550594E+11 117445.95   81435.71 0.31
Maximum of Months 0.00 0.00 0.330330E+12 0.203546E+12 311690.62   186611.97 0.89



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.399574E+12 0.399137E+12 1039018.35 18-JAN-06:02 826873.97 0.30
February 0.00 0.00 0.539654E+12 0.538463E+12 1442929.56 25-FEB-06:02 999008.09 0.44
March 0.00 0.00 0.998560E+12 0.984494E+12 2153112.37 11-MAR-06:02 1551814.83 0.57
April 0.00 0.00 0.144127E+13 0.139021E+13 2321106.57 27-APR-05:03 1705165.89 0.65
May 0.00 0.00 0.206128E+13 0.174580E+13 2827145.56 24-MAY-03:02 1616577.22 0.78
June 0.00 0.00 0.233610E+13 0.171968E+13 2944871.51 27-JUN-05:03 1679413.12 0.78
July 0.00 0.00 0.255859E+13 0.154365E+13 3275022.81 20-JUL-03:02 1663227.92 0.75
August 0.00 0.00 0.254024E+13 0.148349E+13 2990989.56 11-AUG-03:02 1616253.80 0.73
September 0.00 0.00 0.198051E+13 0.126414E+13 2943218.74 11-SEP-03:02 1620852.87 0.67
October 0.00 0.00 0.128008E+13 0.113594E+13 2474623.86 04-OCT-05:02 1624675.56 0.64
November 0.00 0.00 0.801234E+12 0.792170E+12 1599715.86 09-NOV-06:03 1082554.35 0.56
December 0.00 0.00 0.466031E+12 0.466031E+12 898420.44 29-DEC-06:03 898420.44 0.35
                 
Annual Sum or Average 0.00 0.00 0.174031E+14 0.134632E+14       0.60
Minimum of Months 0.00 0.00 0.399574E+12 0.399137E+12 898420.44   826873.97 0.30
Maximum of Months 0.00 0.00 0.255859E+13 0.174580E+13 3275022.81   1705165.89 0.78



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.292588E+11 0.292482E+11 67572.36 12-JAN-15:30 67572.36 0.27
February 0.00 0.00 0.477579E+11 0.476534E+11 130621.65 25-FEB-06:02 88612.94 0.42
March 0.00 0.00 0.102628E+12 0.101264E+12 215562.06 11-MAR-06:02 156297.93 0.55
April 0.00 0.00 0.162918E+12 0.157648E+12 253548.83 27-APR-05:03 186687.28 0.67
May 0.00 0.00 0.236869E+12 0.203960E+12 306118.38 24-MAY-03:02 178899.05 0.80
June 0.00 0.00 0.265561E+12 0.201746E+12 322630.92 23-JUN-05:02 196905.72 0.80
July 0.00 0.00 0.283916E+12 0.178471E+12 331090.40 22-JUL-05:03 190874.73 0.77
August 0.00 0.00 0.276710E+12 0.167952E+12 323165.85 12-AUG-03:02 186409.65 0.75
September 0.00 0.00 0.213524E+12 0.139667E+12 335060.70 11-SEP-03:02 185105.53 0.68
October 0.00 0.00 0.132816E+12 0.119173E+12 243803.48 04-OCT-03:02 161741.40 0.63
November 0.00 0.00 0.744814E+11 0.740300E+11 145290.04 10-NOV-06:02 101398.25 0.53
December 0.00 0.00 0.357410E+11 0.357410E+11 74196.35 01-DEC-15:00 74196.35 0.33
                 
Annual Sum or Average 0.00 0.00 0.186218E+13 0.145655E+13       0.60
Minimum of Months 0.00 0.00 0.292588E+11 0.292482E+11 67572.36   67572.36 0.27
Maximum of Months 0.00 0.00 0.283916E+12 0.203960E+12 335060.70   196905.72 0.80



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.560333E+11 0.559598E+11 110961.60 18-JAN-04:03 88544.27 0.31
February 0.00 0.00 0.573217E+11 0.572663E+11 129214.42 25-FEB-04:02 91034.56 0.46
March 0.00 0.00 0.787844E+11 0.785347E+11 162720.99 11-MAR-04:02 96672.73 0.54
April 0.00 0.00 0.900437E+11 0.881115E+11 168329.96 27-APR-03:02 103432.25 0.53
May 0.00 0.00 0.115380E+12 0.103035E+12 201736.51 22-MAY-03:02 98357.54 0.61
June 0.00 0.00 0.134888E+12 0.107085E+12 225203.45 26-JUN-03:02 90967.26 0.63
July 0.00 0.00 0.155844E+12 0.106407E+12 245465.76 30-JUL-20:57 96221.69 0.63
August 0.00 0.00 0.174314E+12 0.115266E+12 257505.02 27-AUG-14:59 103362.04 0.68
September 0.00 0.00 0.139122E+12 0.996875E+11 239604.66 11-SEP-00:22 94365.29 0.65
October 0.00 0.00 0.101533E+12 0.947397E+11 179649.53 04-OCT-03:02 102088.10 0.64
November 0.00 0.00 0.787329E+11 0.784526E+11 140973.37 09-NOV-04:03 91288.51 0.58
December 0.00 0.00 0.635985E+11 0.635899E+11 106326.79 30-DEC-04:02 85325.49 0.39
                 
Annual Sum or Average 0.00 0.00 0.124560E+13 0.104814E+13       0.55
Minimum of Months 0.00 0.00 0.560333E+11 0.559598E+11 106326.79   85325.49 0.31
Maximum of Months 0.00 0.00 0.174314E+12 0.115266E+12 257505.02   103432.25 0.68



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.338687E+12 0.325039E+12 132584.48 17-JAN-17:00 125711.52 0.00
February 0.00 0.00 0.534019E+12 0.517130E+12 226157.43 24-FEB-17:00 220120.41 0.00
March 0.00 0.00 0.836897E+12 0.822943E+12 396209.03 31-MAR-24:00 393969.12 0.00
April 0.00 0.00 0.103528E+13 0.102909E+13 410074.23 25-APR-04:55 402292.70 0.00
May 0.00 0.00 0.363541E+12 0.346709E+12 226648.48 31-MAY-23:03 212595.43 0.00
June 0.00 0.00 0.599562E+12 0.573831E+12 318783.06 30-JUN-23:02 306809.50 0.00
July 0.00 0.00 0.874908E+12 0.838308E+12 402165.42 31-JUL-24:00 390442.05 0.00
August 0.00 0.00 0.110066E+13 0.106513E+13 422167.53 10-AUG-14:00 402368.36 0.00
September 0.00 0.00 0.367475E+12 0.336224E+12 227309.79 30-SEP-23:05 213126.49 0.00
October 0.00 0.00 0.602836E+12 0.586451E+12 311062.02 31-OCT-24:00 302638.89 0.00
November 0.00 0.00 0.818523E+12 0.799030E+12 321970.29 24-NOV-08:15 307788.00 0.00
December 0.00 0.00 0.110010E+13 0.106551E+13 422262.40 22-DEC-06:03 396692.63 0.00
                 
Annual Sum or Average 0.00 0.00 0.857248E+13 0.830540E+13       0.00
Minimum of Months 0.00 0.00 0.338687E+12 0.325039E+12 132584.48   125711.52 0.00
Maximum of Months 0.00 0.00 0.110066E+13 0.106551E+13 422262.40   402368.36 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.500855E+10 0.486377E+10 2535.93 12-JAN-17:00 2405.11 0.00
February 0.00 0.00 0.962832E+10 0.940246E+10 4586.17 21-FEB-17:00 4436.12 0.00
March 0.00 0.00 0.162732E+11 0.159437E+11 7794.97 31-MAR-24:00 7695.27 0.00
April 0.00 0.00 0.210003E+11 0.206930E+11 8548.31 16-APR-20:54 8292.25 0.00
May 0.00 0.00 0.725726E+10 0.659478E+10 4650.35 31-MAY-23:03 4042.97 0.00
June 0.00 0.00 0.123709E+11 0.112895E+11 6545.17 30-JUN-23:02 6030.46 0.00
July 0.00 0.00 0.182093E+11 0.166004E+11 8653.05 31-JUL-23:02 7844.40 0.00
August 0.00 0.00 0.229816E+11 0.212870E+11 8877.56 10-AUG-14:10 8058.43 0.00
September 0.00 0.00 0.739861E+10 0.612792E+10 4621.76 30-SEP-23:05 4003.81 0.00
October 0.00 0.00 0.117609E+11 0.111429E+11 5988.36 31-OCT-23:10 5739.75 0.00
November 0.00 0.00 0.156218E+11 0.153125E+11 6643.26 08-NOV-16:40 6389.67 0.00
December 0.00 0.00 0.205933E+11 0.204236E+11 8318.76 28-DEC-17:00 8158.39 0.00
                 
Annual Sum or Average 0.00 0.00 0.168104E+12 0.159682E+12       0.00
Minimum of Months 0.00 0.00 0.500855E+10 0.486377E+10 2535.93   2405.11 0.00
Maximum of Months 0.00 0.00 0.229816E+11 0.212870E+11 8877.56   8292.25 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.378506E+11 0.364888E+11 23519.28 13-JAN-17:00 21624.62 0.00
February 0.00 0.00 0.857714E+11 0.835400E+11 43267.32 22-FEB-17:00 41734.44 0.00
March 0.00 0.00 0.153635E+12 0.150352E+12 75278.30 31-MAR-24:00 74275.81 0.00
April 0.00 0.00 0.199385E+12 0.196304E+12 81280.53 12-APR-16:00 79024.97 0.00
May 0.00 0.00 0.684750E+11 0.619288E+11 44872.84 31-MAY-23:03 38613.76 0.00
June 0.00 0.00 0.117971E+12 0.107217E+12 63359.21 30-JUN-23:02 58169.03 0.00
July 0.00 0.00 0.173886E+12 0.157845E+12 82778.59 31-JUL-23:02 74714.26 0.00
August 0.00 0.00 0.218200E+12 0.201224E+12 84519.27 10-AUG-14:10 76367.98 0.00
September 0.00 0.00 0.696018E+11 0.570511E+11 45100.20 30-SEP-23:05 38758.11 0.00
October 0.00 0.00 0.110715E+12 0.104585E+12 56464.50 31-OCT-23:10 53907.70 0.00
November 0.00 0.00 0.144834E+12 0.141754E+12 63051.60 08-NOV-16:50 60450.04 0.00
December 0.00 0.00 0.187626E+12 0.185929E+12 78455.51 28-DEC-17:00 76860.60 0.00
                 
Annual Sum or Average 0.00 0.00 0.156795E+13 0.148422E+13       0.00
Minimum of Months 0.00 0.00 0.378506E+11 0.364888E+11 23519.28   21624.62 0.00
Maximum of Months 0.00 0.00 0.218200E+12 0.201224E+12 84519.27   79024.97 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.236917E+10 0.224348E+10 2366.30 12-JAN-17:00 2229.68 0.00
February 0.00 0.00 0.790104E+10 0.766512E+10 4374.65 22-FEB-17:00 4213.59 0.00
March 0.00 0.00 0.151950E+11 0.148479E+11 7484.67 31-MAR-24:00 7377.20 0.00
April 0.00 0.00 0.200991E+11 0.197737E+11 8328.97 16-APR-20:45 8058.99 0.00
May 0.00 0.00 0.708995E+10 0.641440E+10 4470.53 31-MAY-23:03 3829.93 0.00
June 0.00 0.00 0.120234E+11 0.109277E+11 6403.03 30-JUN-23:02 5874.74 0.00
July 0.00 0.00 0.176142E+11 0.159897E+11 8401.04 31-JUL-23:02 7577.21 0.00
August 0.00 0.00 0.221336E+11 0.204100E+11 8626.26 10-AUG-14:10 7796.95 0.00
September 0.00 0.00 0.704468E+10 0.577045E+10 4502.76 30-SEP-23:05 3859.66 0.00
October 0.00 0.00 0.109998E+11 0.103688E+11 5526.58 31-OCT-23:10 5258.66 0.00
November 0.00 0.00 0.139896E+11 0.136645E+11 6368.32 08-NOV-16:40 6109.16 0.00
December 0.00 0.00 0.176063E+11 0.174211E+11 7856.84 28-DEC-17:00 7689.88 0.00
                 
Annual Sum or Average 0.00 0.00 0.154066E+12 0.145497E+12       0.00
Minimum of Months 0.00 0.00 0.236917E+10 0.224348E+10 2366.30   2229.68 0.00
Maximum of Months 0.00 0.00 0.221336E+11 0.204100E+11 8626.26   8058.99 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 3499.52 214389.78 03-JAN-06:03
February 0.00 0.00 01-FEB-00:10 553.27 121606.28 11-FEB-06:02
March 0.00 0.00 01-MAR-00:10 0.72 642.83 01-MAR-06:50
April 0.00 0.00 01-APR-00:03 0.00 0.00 01-APR-00:03
May 0.00 0.00 01-MAY-00:03 0.00 0.00 01-MAY-00:03
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:03 0.00 0.00 01-JUL-00:03
August 0.00 0.00 01-AUG-00:03 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:05 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:03 0.00 0.00 01-OCT-00:03
November 0.00 0.00 01-NOV-00:10 37.16 5007.30 27-NOV-06:20
December 0.00 0.00 01-DEC-00:10 1308.34 195903.17 21-DEC-06:02
             
Annual Sum or Average 0.00     453.90    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   3499.52 214389.78  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 411691.87 1576675.02 25-JAN-15:10 15.24 79654.43 30-JAN-03:25
February 533734.27 1686102.13 25-FEB-06:02 226.75 403043.43 06-FEB-02:55
March 759702.12 2062647.19 11-MAR-06:02 6.17 75056.23 05-MAR-08:62
April 1010586.50 3172067.73 17-APR-05:03 0.00 0.00 01-APR-00:03
May 1236806.15 3470543.18 24-MAY-05:03 0.00 0.00 01-MAY-00:03
June 1335682.18 3479936.18 14-JUN-05:03 0.00 0.00 01-JUN-00:10
July 1376548.86 3577045.24 25-JUL-05:03 0.00 0.00 01-JUL-00:03
August 1365252.90 4050799.93 07-AUG-05:03 0.00 0.00 01-AUG-00:03
September 1126118.84 4340337.56 05-SEP-05:04 0.00 0.00 01-SEP-00:05
October 885693.57 3280572.65 04-OCT-05:02 11.08 104806.99 28-OCT-20:42
November 659670.46 1674325.97 06-NOV-13:10 19.41 80784.30 26-NOV-20:45
December 472196.23 1591082.45 01-DEC-15:20 0.58 10298.37 03-DEC-17:42
             
Annual Sum or Average 933290.25     21.80    
Minimum of Months 411691.87 1576675.02   0.00 0.00  
Maximum of Months 1376548.86 4340337.56   226.75 403043.43  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 266398.89 2053215.46 18-JAN-06:02 0.00 0.00 01-JAN-00:05
February 373616.31 2821064.45 25-FEB-06:02 0.00 0.00 01-FEB-00:10
March 575436.73 3728296.69 11-MAR-06:02 0.00 0.00 01-MAR-00:10
April 796015.36 4177766.42 17-APR-05:02 0.00 0.00 01-APR-00:03
May 1040063.26 4956669.74 24-MAY-05:03 0.00 0.00 01-MAY-00:03
June 1206173.90 5004998.43 23-JUN-05:02 0.00 0.00 01-JUN-00:10
July 1272885.70 5127806.82 31-JUL-05:02 0.00 0.00 01-JUL-00:03
August 1275799.08 5149122.84 28-AUG-05:02 0.00 0.00 01-AUG-00:03
September 1037190.49 5175404.37 05-SEP-05:02 0.00 0.00 01-SEP-00:05
October 695245.46 4747675.18 04-OCT-05:02 0.00 0.00 01-OCT-00:03
November 500564.00 3037722.87 09-NOV-06:03 0.00 0.00 01-NOV-00:10
December 316610.20 1899994.18 29-DEC-06:03 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 781849.83     0.00    
Minimum of Months 266398.89 1899994.18   0.00 0.00  
Maximum of Months 1275799.08 5175404.37   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 222968.87 587948.98 12-JAN-15:00 0.00 0.00 01-JAN-00:05
February 500647.69 1023886.66 22-FEB-15:00 0.00 0.00 01-FEB-00:10
March 970475.90 1771608.43 28-MAR-15:20 0.00 0.00 01-MAR-00:10
April 1594566.23 2235167.67 15-APR-15:00 0.00 0.00 01-APR-00:03
May 1125053.44 1788767.04 01-MAY-15:00 0.00 0.00 01-MAY-00:03
June 1418913.01 2077062.60 08-JUN-16:00 0.00 0.00 01-JUN-00:10
July 1562214.74 2099724.66 07-JUL-15:00 0.00 0.00 01-JUL-00:03
August 1677298.29 2097242.06 07-AUG-15:00 0.00 0.00 01-AUG-00:03
September 903977.83 1401087.29 17-SEP-20:00 0.00 0.00 01-SEP-00:05
October 909464.99 1585426.29 02-OCT-15:00 0.00 0.00 01-OCT-00:03
November 824512.51 1432582.66 08-NOV-15:00 0.00 0.00 01-NOV-00:10
December 790137.70 1330929.74 28-DEC-14:20 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 1044556.86     0.00    
Minimum of Months 222968.87 587948.98   0.00 0.00  
Maximum of Months 1677298.29 2235167.67   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 12736.38 41939.78 18-JAN-12:50
February 0.00 0.00 01-FEB-00:10 12565.30 41685.69 01-FEB-12:20
March 0.00 0.00 01-MAR-00:10 12460.90 39954.81 01-MAR-12:40
April 0.00 0.00 01-APR-00:03 10707.24 36293.94 03-APR-11:20
May 0.00 0.00 01-MAY-00:03 9907.69 32609.11 01-MAY-11:30
June 0.00 0.00 01-JUN-00:10 9215.80 29022.62 01-JUN-12:00
July 0.00 0.00 01-JUL-00:03 8271.59 26830.22 03-JUL-11:20
August 0.00 0.00 01-AUG-00:03 9179.75 28572.30 31-AUG-11:50
September 0.00 0.00 01-SEP-00:05 9468.39 31771.68 29-SEP-11:20
October 0.00 0.00 01-OCT-00:03 10512.63 35911.19 31-OCT-11:50
November 0.00 0.00 01-NOV-00:10 11729.89 39429.38 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 12146.27 41510.39 29-DEC-13:00
             
Annual Sum or Average 0.00     10731.89    
Minimum of Months 0.00 0.00   8271.59 26830.22  
Maximum of Months 0.00 0.00   12736.38 41939.78  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 244589.05 1138789.27 25-JAN-15:50 2780.89 142006.95 21-JAN-06:30
February 351751.30 1572203.41 25-FEB-06:02 952.10 132838.06 02-FEB-07:00
March 605254.13 3340521.99 10-MAR-17:00 210.17 78791.98 01-MAR-04:30
April 1095135.57 5094516.93 18-APR-14:00 116.49 31528.10 09-APR-23:27
May 2269400.51 6858010.74 17-MAY-15:30 0.00 0.00 01-MAY-00:03
June 3402094.33 7900866.08 22-JUN-15:50 0.00 0.00 01-JUN-00:10
July 4395535.27 7926461.46 31-JUL-05:03 0.00 0.00 01-JUL-00:03
August 4401664.96 7980936.25 28-AUG-05:03 0.00 0.00 01-AUG-00:03
September 3000791.17 7547560.56 14-SEP-15:30 0.00 0.00 01-SEP-00:05
October 982297.67 4800260.76 04-OCT-05:04 29.97 30147.33 30-OCT-01:50
November 487846.39 2764266.70 13-NOV-14:30 493.63 84869.05 27-NOV-03:30
December 287802.45 1182753.60 01-DEC-15:40 1490.54 144666.78 23-DEC-07:00
             
Annual Sum or Average 1803309.38     506.36    
Minimum of Months 244589.05 1138789.27   0.00 0.00  
Maximum of Months 4401664.96 7980936.25   2780.89 144666.78  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.167064E+11 0.87 10174.45 01-JAN-00:20 1.42
February 0.148366E+11 0.85 10174.45 01-FEB-04:03 1.42
March 0.167797E+11 0.87 10174.45 01-MAR-04:02 1.42
April 0.156489E+11 0.84 10174.45 01-APR-03:02 1.42
May 0.167857E+11 0.87 10174.45 01-MAY-00:03 1.42
June 0.168586E+11 0.90 10174.45 01-JUN-03:02 1.41
July 0.174745E+11 0.90 10174.45 01-JUL-03:02 1.41
August 0.186617E+11 0.96 10174.45 01-AUG-03:02 1.41
September 0.175204E+11 0.93 10174.45 01-SEP-03:02 1.41
October 0.180738E+11 0.93 10174.45 01-OCT-09:25 1.40
November 0.173156E+11 0.93 10174.45 01-NOV-03:02 1.41
December 0.171902E+11 0.89 10174.45 01-DEC-04:02 1.42
           
Annual Sum or Average 0.203852E+12 0.90      
Minimum of Months 0.148366E+11 0.84 10174.45   1.40
Maximum of Months 0.186617E+11 0.96 10174.45   1.42



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.613777E+10 0.37 10149.55 02-JAN-04:02 1.10
February 0.711973E+10 0.44 13970.45 21-FEB-06:03 1.34
March 0.111338E+11 0.57 22171.70 14-MAR-05:03 1.79
April 0.138470E+11 0.70 22171.70 17-APR-04:22 1.79
May 0.132897E+11 0.65 22171.70 01-MAY-04:22 1.79
June 0.140456E+11 0.69 22171.70 05-JUN-05:02 1.79
July 0.141774E+11 0.69 22171.70 01-JUL-05:03 1.79
August 0.173631E+11 0.78 22171.70 07-AUG-05:01 1.79
September 0.109296E+11 0.57 22171.70 06-SEP-05:03 1.79
October 0.105351E+11 0.55 22171.70 03-OCT-05:03 1.79
November 0.930219E+10 0.50 19023.46 06-NOV-06:03 1.63
December 0.842569E+10 0.45 13874.36 29-DEC-06:03 1.33
           
Annual Sum or Average 0.136307E+12 0.58      
Minimum of Months 0.613777E+10 0.37 10149.55   1.10
Maximum of Months 0.173631E+11 0.78 22171.70   1.79



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.449800E+11 0.32 97039.59 02-JAN-06:01 1.11
February 0.499375E+11 0.37 114060.78 21-FEB-06:03 1.23
March 0.793905E+11 0.46 210958.08 11-MAR-06:02 1.80
April 0.981349E+11 0.55 210958.08 15-APR-05:03 1.80
May 0.113842E+12 0.61 210958.08 03-MAY-05:03 1.80
June 0.112808E+12 0.61 210958.08 01-JUN-05:03 1.80
July 0.102204E+12 0.56 210958.08 05-JUL-05:02 1.80
August 0.106187E+12 0.57 210958.08 01-AUG-05:03 1.80
September 0.894786E+11 0.51 210958.08 02-SEP-05:03 1.80
October 0.782988E+11 0.46 210958.08 03-OCT-05:03 1.80
November 0.611042E+11 0.40 128423.05 13-NOV-06:02 1.32
December 0.484460E+11 0.34 97039.59 01-DEC-05:03 1.11
           
Annual Sum or Average 0.984812E+12 0.48      
Minimum of Months 0.449800E+11 0.32 97039.59   1.11
Maximum of Months 0.113842E+12 0.61 210958.08   1.80



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.346403E+10 0.28 4945.93 12-JAN-15:30 0.70
February 0.405743E+10 0.31 8982.37 09-FEB-06:02 0.98
March 0.749354E+10 0.41 20639.43 30-MAR-05:02 1.64
April 0.108785E+11 0.55 23699.52 17-APR-05:02 1.79
May 0.134300E+11 0.63 23699.52 01-MAY-05:02 1.79
June 0.134036E+11 0.64 23699.52 03-JUN-05:02 1.79
July 0.115360E+11 0.57 23699.52 01-JUL-05:03 1.79
August 0.114524E+11 0.56 23699.52 01-AUG-05:03 1.79
September 0.937494E+10 0.49 23699.52 11-SEP-03:02 1.79
October 0.787926E+10 0.43 18614.79 04-OCT-03:02 1.54
November 0.540165E+10 0.35 11669.82 10-NOV-06:02 1.15
December 0.365090E+10 0.28 8982.37 29-DEC-06:03 0.98
           
Annual Sum or Average 0.102022E+12 0.46      
Minimum of Months 0.346403E+10 0.28 4945.93   0.70
Maximum of Months 0.134300E+11 0.64 23699.52   1.79



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.970462E+11 1.38 36232.89 01-JAN-00:05 1.38
February 0.876546E+11 1.38 36232.89 01-FEB-00:10 1.38
March 0.970462E+11 1.38 36232.89 01-MAR-00:10 1.38
April 0.939157E+11 1.38 36232.89 01-APR-00:03 1.38
May 0.970462E+11 1.38 36232.89 01-MAY-00:03 1.38
June 0.939157E+11 1.38 36232.89 01-JUN-00:10 1.38
July 0.970462E+11 1.38 36232.89 01-JUL-00:03 1.38
August 0.970462E+11 1.38 36232.89 01-AUG-00:03 1.38
September 0.939157E+11 1.38 36232.89 01-SEP-00:05 1.38
October 0.970462E+11 1.38 36232.89 01-OCT-00:03 1.38
November 0.939157E+11 1.38 36232.89 01-NOV-00:10 1.38
December 0.970462E+11 1.38 36232.89 01-DEC-00:10 1.38
           
Annual Sum or Average 0.114264E+13 1.38      
Minimum of Months 0.876546E+11 1.38 36232.89   1.38
Maximum of Months 0.970462E+11 1.38 36232.89   1.38



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.147086E+10 0.94 549.15 01-JAN-00:05 0.94
February 0.132851E+10 0.94 549.15 01-FEB-00:10 0.94
March 0.147086E+10 0.94 549.15 01-MAR-00:10 0.94
April 0.142341E+10 0.94 549.15 01-APR-00:03 0.94
May 0.147086E+10 0.93 549.15 01-MAY-00:03 0.94
June 0.142341E+10 0.93 549.15 01-JUN-00:10 0.94
July 0.147086E+10 0.93 549.15 01-JUL-00:03 0.93
August 0.147086E+10 0.93 549.15 01-AUG-00:03 0.94
September 0.142341E+10 0.93 549.15 01-SEP-00:05 0.93
October 0.147086E+10 0.94 549.15 01-OCT-00:07 0.94
November 0.142341E+10 0.94 549.15 01-NOV-00:10 0.94
December 0.147086E+10 0.94 549.15 01-DEC-00:10 0.94
           
Annual Sum or Average 0.173181E+11 0.94      
Minimum of Months 0.132851E+10 0.93 549.15   0.93
Maximum of Months 0.147086E+10 0.94 549.15   0.94



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.140096E+11 0.94 5230.57 01-JAN-00:05 0.94
February 0.126538E+11 0.94 5230.57 01-FEB-00:10 0.94
March 0.140096E+11 0.94 5230.57 01-MAR-00:10 0.94
April 0.135576E+11 0.94 5230.57 01-APR-00:03 0.94
May 0.140096E+11 0.93 5230.57 01-MAY-00:03 0.94
June 0.135576E+11 0.93 5230.57 01-JUN-00:10 0.94
July 0.140096E+11 0.93 5230.57 01-JUL-00:03 0.93
August 0.140096E+11 0.93 5230.57 01-AUG-00:03 0.93
September 0.135576E+11 0.93 5230.57 01-SEP-00:05 0.93
October 0.140096E+11 0.94 5230.57 01-OCT-00:03 0.94
November 0.135576E+11 0.94 5230.57 01-NOV-00:10 0.94
December 0.140096E+11 0.94 5230.57 01-DEC-00:10 0.94
           
Annual Sum or Average 0.164951E+12 0.94      
Minimum of Months 0.126538E+11 0.93 5230.57   0.93
Maximum of Months 0.140096E+11 0.94 5230.57   0.94



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.140937E+10 0.94 526.20 01-JAN-00:05 0.94
February 0.127298E+10 0.94 526.20 01-FEB-00:10 0.94
March 0.140937E+10 0.94 526.20 01-MAR-00:10 0.94
April 0.136391E+10 0.94 526.20 01-APR-00:03 0.94
May 0.140937E+10 0.93 526.20 01-MAY-00:03 0.94
June 0.136391E+10 0.93 526.20 01-JUN-00:10 0.94
July 0.140937E+10 0.93 526.20 01-JUL-00:03 0.94
August 0.140937E+10 0.93 526.20 01-AUG-00:03 0.94
September 0.136391E+10 0.93 526.20 01-SEP-00:05 0.93
October 0.140937E+10 0.94 526.20 01-OCT-00:03 0.94
November 0.136391E+10 0.94 526.20 01-NOV-00:10 0.94
December 0.140937E+10 0.94 526.20 01-DEC-00:10 0.94
           
Annual Sum or Average 0.165942E+11 0.94      
Minimum of Months 0.127298E+10 0.93 526.20   0.93
Maximum of Months 0.140937E+10 0.94 526.20   0.94



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 42491359.24 38242223.31 1119.14 02-JAN-06:03 1007.23 1007.23 46.58 1.33
February 5533847.06 4980462.35 467.83 11-FEB-06:02 421.05 421.05 22.17 0.51
March 7689.25 6920.33 2.57 01-MAR-06:50 2.31 2.31 20.71 0.00
April 0.00 0.00 0.00 01-APR-00:03 0.00 0.00 20.68 0.00
May 0.00 0.00 0.00 01-MAY-00:03 0.00 0.00 20.68 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 20.68 0.00
July 0.00 0.00 0.00 01-JUL-00:03 0.00 0.00 20.68 0.00
August 0.00 0.00 0.00 01-AUG-00:03 0.00 0.00 20.68 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00 0.00 20.68 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00 0.00 20.68 0.00
November 382181.65 343963.49 19.80 27-NOV-06:20 17.82 17.82 20.33 0.02
December 14871169.30 13384052.37 746.87 21-DEC-06:02 672.19 672.19 24.62 0.84
                 
Annual Sum or Average 63286246.50 56957621.85            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 20.33 0.00
Maximum of Months 42491359.24 38242223.31 1119.14   1007.23 1007.23 46.58 1.33



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.393436E+09 0.354092E+09 5296.92 28-JAN-06:03 4767.23 4767.23 8.74 65.95
February 0.592101E+09 0.532890E+09 7389.47 17-FEB-06:02 6650.52 6650.52 8.90 75.89
March 0.109859E+10 0.988732E+09 19798.77 27-MAR-05:02 17818.90 17818.90 8.05 113.35
April 0.164206E+10 0.147785E+10 16744.89 17-APR-05:02 15070.40 15070.40 7.64 106.03
May 0.209080E+10 0.188172E+10 26275.61 24-MAY-05:03 23648.05 23648.05 7.93 126.75
June 0.243552E+10 0.219197E+10 23087.78 23-JUN-05:02 20779.00 20779.00 7.30 120.46
July 0.267156E+10 0.240440E+10 25363.25 28-JUL-05:03 22826.92 22826.92 7.40 125.00
August 0.280364E+10 0.252327E+10 25256.09 01-AUG-05:03 22730.48 22730.48 7.38 124.79
September 0.205988E+10 0.185389E+10 26275.61 05-SEP-05:02 23648.05 23648.05 7.97 126.75
October 0.136227E+10 0.122604E+10 23161.63 04-OCT-05:02 20845.47 20845.47 8.04 120.61
November 0.107705E+10 0.969346E+09 10951.82 13-NOV-06:02 9856.63 9856.63 9.06 89.29
December 0.547058E+09 0.492352E+09 4956.26 14-DEC-06:03 4460.64 4460.64 8.74 64.10
                 
Annual Sum or Average 0.187740E+11 0.168966E+11            
Minimum of Months 0.393436E+09 0.354092E+09 4956.26   4460.64 4460.64 7.30 64.10
Maximum of Months 0.280364E+10 0.252327E+10 26275.61   23648.05 23648.05 9.06 126.75



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.283083E+11 0.254775E+11 18084.79 01-JAN-00:25 16276.31 16276.31 8.46 126.75
February 0.277348E+11 0.249614E+11 18084.79 01-FEB-04:03 16276.31 16276.31 8.85 126.75
March 0.368358E+11 0.331522E+11 18084.79 01-MAR-04:02 16276.31 16276.31 9.34 126.75
April 0.437472E+11 0.393725E+11 18084.79 01-APR-00:03 16276.31 16276.31 7.35 126.75
May 0.447446E+11 0.402702E+11 18084.79 01-MAY-00:03 16276.31 16276.31 8.12 126.75
June 0.431759E+11 0.388583E+11 18084.79 01-JUN-00:12 16276.31 16276.31 7.05 126.75
July 0.457242E+11 0.411518E+11 18084.79 01-JUL-00:03 16276.31 16276.31 7.22 126.75
August 0.462330E+11 0.416097E+11 18084.79 01-AUG-00:03 16276.31 16276.31 7.27 126.75
September 0.388706E+11 0.349835E+11 18084.79 01-SEP-00:05 16276.31 16276.31 7.15 126.75
October 0.384193E+11 0.345774E+11 18084.79 01-OCT-00:33 16276.31 16276.31 8.54 126.75
November 0.335817E+11 0.302235E+11 18084.79 01-NOV-03:02 16276.31 16276.31 10.73 126.75
December 0.308923E+11 0.278030E+11 18084.79 01-DEC-04:02 16276.31 16276.31 9.43 126.75
                 
Annual Sum or Average 0.458268E+12 0.412441E+12            
Minimum of Months 0.277348E+11 0.249614E+11 18084.79   16276.31 16276.31 7.05 126.75
Maximum of Months 0.462330E+11 0.416097E+11 18084.79   16276.31 16276.31 10.73 126.75



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.946167E+10 0.851551E+10 3532.58 01-JAN-00:05 3179.33 3179.33 21.72 14.75
February 0.854603E+10 0.769143E+10 3532.58 01-FEB-00:10 3179.33 3179.33 24.23 14.75
March 0.946167E+10 0.851551E+10 3532.58 01-MAR-00:10 3179.33 3179.33 28.60 14.75
April 0.915646E+10 0.824081E+10 3532.58 01-APR-00:03 3179.33 3179.33 42.42 14.75
May 0.946167E+10 0.851551E+10 3532.58 01-MAY-00:03 3179.33 3179.33 37.75 14.75
June 0.915646E+10 0.824081E+10 3532.58 01-JUN-00:10 3179.33 3179.33 38.99 14.75
July 0.946167E+10 0.851551E+10 3532.58 01-JUL-00:03 3179.33 3179.33 49.06 14.75
August 0.946167E+10 0.851551E+10 3532.58 01-AUG-00:03 3179.33 3179.33 49.19 14.75
September 0.915646E+10 0.824081E+10 3532.58 01-SEP-00:05 3179.33 3179.33 36.31 14.75
October 0.946167E+10 0.851551E+10 3532.58 01-OCT-00:03 3179.33 3179.33 37.34 14.75
November 0.915646E+10 0.824081E+10 3532.58 01-NOV-00:10 3179.33 3179.33 31.82 14.75
December 0.946167E+10 0.851551E+10 3532.58 01-DEC-00:10 3179.33 3179.33 29.89 14.75
                 
Annual Sum or Average 0.111404E+12 0.100263E+12            
Minimum of Months 0.854603E+10 0.769143E+10 3532.58   3179.33 3179.33 21.72 14.75
Maximum of Months 0.946167E+10 0.851551E+10 3532.58   3179.33 3179.33 49.19 14.75



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 11967951.72 3590385.52 5.96 01-JAN-06:05 1.79 1.79 55.78 0.44
February 10809762.85 3242928.85 5.96 01-FEB-06:02 1.79 1.79 56.50 0.44
March 11967951.72 3590385.52 5.96 01-MAR-06:03 1.79 1.79 56.08 0.44
April 11581888.76 3474566.63 5.96 01-APR-05:03 1.79 1.79 57.55 0.44
May 11967951.72 3590385.52 5.96 01-MAY-05:02 1.79 1.79 57.71 0.44
June 11581888.76 3474566.63 5.96 01-JUN-05:03 1.79 1.79 58.08 0.44
July 11967951.72 3590385.52 5.96 01-JUL-05:03 1.79 1.79 57.81 0.44
August 11967951.72 3590385.52 5.96 01-AUG-05:03 1.79 1.79 57.60 0.44
September 11581888.76 3474566.63 5.96 01-SEP-05:03 1.79 1.79 56.62 0.44
October 11967951.72 3590385.52 5.96 01-OCT-05:10 1.79 1.79 56.89 0.44
November 11581888.76 3474566.63 5.96 01-NOV-05:02 1.79 1.79 56.84 0.44
December 11967951.72 3590385.52 5.96 01-DEC-06:03 1.79 1.79 56.28 0.44
                 
Annual Sum or Average 0.140913E+09 42273893.99            
Minimum of Months 10809762.85 3242928.85 5.96   1.79 1.79 55.78 0.44
Maximum of Months 11967951.72 3590385.52 5.96   1.79 1.79 58.08 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.354335E+11 0.318901E+11 44888.81 12-JAN-15:10 40399.93 40399.93 22.75 149.36
February 0.354661E+11 0.319195E+11 44916.91 25-FEB-06:02 40425.22 40425.22 23.62 149.36
March 0.505102E+11 0.454592E+11 45016.20 10-MAR-17:00 40514.58 40514.58 26.45 149.36
April 0.678862E+11 0.610976E+11 45105.33 18-APR-12:30 40594.80 40594.80 28.84 149.36
May 0.779412E+11 0.701471E+11 45105.33 09-MAY-13:10 40594.80 40594.80 28.87 149.36
June 0.806425E+11 0.725783E+11 45105.33 05-JUN-15:00 40594.80 40594.80 28.87 149.36
July 0.897819E+11 0.808037E+11 45105.33 01-JUL-07:10 40594.80 40594.80 29.33 149.36
August 0.904997E+11 0.814498E+11 45105.33 01-AUG-00:40 40594.80 40594.80 30.13 149.36
September 0.707598E+11 0.636838E+11 45105.33 01-SEP-00:40 40594.80 40594.80 29.93 149.36
October 0.596691E+11 0.537022E+11 45104.63 04-OCT-05:04 40594.17 40594.17 28.79 149.36
November 0.433413E+11 0.390072E+11 44981.38 13-NOV-14:30 40483.24 40483.24 25.53 149.36
December 0.389487E+11 0.350538E+11 44889.91 01-DEC-15:20 40400.92 40400.92 22.78 149.36
                 
Annual Sum or Average 0.740880E+12 0.666792E+12            
Minimum of Months 0.354335E+11 0.318901E+11 44888.81   40399.93 40399.93 22.75 149.36
Maximum of Months 0.904997E+11 0.814498E+11 45105.33   40594.80 40594.80 30.13 149.36



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 79.76 79.76 3499.52 214389.78 03-JAN-06:03
February 0.00 0.00 01-FEB-00:10 24.88 24.88 553.27 121606.28 11-FEB-06:02
March 0.00 0.00 01-MAR-00:10 20.72 20.72 0.72 642.83 01-MAR-06:50
April 0.00 0.00 01-APR-00:03 20.68 20.68 0.00 0.00 01-APR-00:03
May 0.00 0.00 01-MAY-00:03 20.68 20.68 0.00 0.00 01-MAY-00:03
June 0.00 0.00 01-JUN-00:10 20.68 20.68 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:03 20.68 20.68 0.00 0.00 01-JUL-00:03
August 0.00 0.00 01-AUG-00:03 20.68 20.68 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:05 20.68 20.68 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:03 20.68 20.68 0.00 0.00 01-OCT-00:03
November 0.00 0.00 01-NOV-00:10 20.68 20.68 37.16 5007.30 27-NOV-06:20
December 0.00 0.00 01-DEC-00:10 20.32 20.32 1308.34 195903.17 21-DEC-06:02
                 
Annual Sum or Average 0.00         453.90    
Minimum of Months 0.00 0.00   20.32 20.32 0.00 0.00  
Maximum of Months 0.00 0.00   79.76 79.76 3499.52 214389.78  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 411691.87 1576675.02 25-JAN-15:10 10.24 8.68 15.24 79654.43 30-JAN-03:25
February 533734.27 1686102.13 25-FEB-06:02 11.24 8.07 226.75 403043.43 06-FEB-02:55
March 759702.12 2062647.19 11-MAR-06:02 11.02 7.14 6.17 75056.23 05-MAR-08:62
April 1010586.50 3172067.73 17-APR-05:03 13.05 7.34 0.00 0.00 01-APR-00:03
May 1236806.15 3470543.18 24-MAY-05:03 13.47 7.76 0.00 0.00 01-MAY-00:03
June 1335682.18 3479936.18 14-JUN-05:03 13.26 7.55 0.00 0.00 01-JUN-00:10
July 1376548.86 3577045.24 25-JUL-05:03 13.44 7.73 0.00 0.00 01-JUL-00:03
August 1365252.90 4050799.93 07-AUG-05:03 14.33 8.62 0.00 0.00 01-AUG-00:03
September 1126118.84 4340337.56 05-SEP-05:04 14.96 9.24 0.00 0.00 01-SEP-00:05
October 885693.57 3280572.65 04-OCT-05:02 13.13 7.42 11.08 104806.99 28-OCT-20:42
November 659670.46 1674325.97 06-NOV-13:10 9.85 6.70 19.41 80784.30 26-NOV-20:45
December 472196.23 1591082.45 01-DEC-15:20 10.25 8.66 0.58 10298.37 03-DEC-17:42
                 
Annual Sum or Average 933290.25         21.80    
Minimum of Months 411691.87 1576675.02   9.85 6.70 0.00 0.00  
Maximum of Months 1376548.86 4340337.56   14.96 9.24 226.75 403043.43  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 266398.89 2053215.46 18-JAN-06:02 15.10 8.97 0.00 0.00 01-JAN-00:05
February 373616.31 2821064.45 25-FEB-06:02 15.88 8.28 0.00 0.00 01-FEB-00:10
March 575436.73 3728296.69 11-MAR-06:02 16.04 7.17 0.00 0.00 01-MAR-00:10
April 796015.36 4177766.42 17-APR-05:02 16.12 7.16 0.00 0.00 01-APR-00:03
May 1040063.26 4956669.74 24-MAY-05:03 16.05 7.85 0.00 0.00 01-MAY-00:03
June 1206173.90 5004998.43 23-JUN-05:02 16.63 6.83 0.00 0.00 01-JUN-00:10
July 1272885.70 5127806.82 31-JUL-05:02 17.04 7.73 0.00 0.00 01-JUL-00:03
August 1275799.08 5149122.84 28-AUG-05:02 16.98 7.20 0.00 0.00 01-AUG-00:03
September 1037190.49 5175404.37 05-SEP-05:02 16.46 7.88 0.00 0.00 01-SEP-00:05
October 695245.46 4747675.18 04-OCT-05:02 16.11 7.81 0.00 0.00 01-OCT-00:03
November 500564.00 3037722.87 09-NOV-06:03 15.66 8.12 0.00 0.00 01-NOV-00:10
December 316610.20 1899994.18 29-DEC-06:03 13.91 8.94 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 781849.83         0.00    
Minimum of Months 266398.89 1899994.18   13.91 6.83 0.00 0.00  
Maximum of Months 1275799.08 5175404.37   17.04 8.97 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 222968.87 587948.98 12-JAN-15:00 29.71 25.62 0.00 0.00 01-JAN-00:05
February 500647.69 1023886.66 22-FEB-15:00 38.00 30.73 0.00 0.00 01-FEB-00:10
March 970475.90 1771608.43 28-MAR-15:20 51.92 41.09 0.00 0.00 01-MAR-00:10
April 1594566.23 2235167.67 15-APR-15:00 60.38 47.14 0.00 0.00 01-APR-00:03
May 1125053.44 1788767.04 01-MAY-15:00 52.23 46.92 0.00 0.00 01-MAY-00:03
June 1418913.01 2077062.60 08-JUN-16:00 57.51 48.99 0.00 0.00 01-JUN-00:10
July 1562214.74 2099724.66 07-JUL-15:00 57.92 46.36 0.00 0.00 01-JUL-00:03
August 1677298.29 2097242.06 07-AUG-15:00 57.87 44.29 0.00 0.00 01-AUG-00:03
September 903977.83 1401087.29 17-SEP-20:00 45.06 40.04 0.00 0.00 01-SEP-00:05
October 909464.99 1585426.29 02-OCT-15:00 48.48 40.47 0.00 0.00 01-OCT-00:03
November 824512.51 1432582.66 08-NOV-15:00 45.65 35.19 0.00 0.00 01-NOV-00:10
December 790137.70 1330929.74 28-DEC-14:20 43.76 31.00 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 1044556.86         0.00    
Minimum of Months 222968.87 587948.98   29.71 25.62 0.00 0.00  
Maximum of Months 1677298.29 2235167.67   60.38 48.99 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 56.67 56.67 12736.38 41939.78 18-JAN-12:50
February 0.00 0.00 01-FEB-00:10 56.95 56.95 12565.30 41685.69 01-FEB-12:20
March 0.00 0.00 01-MAR-00:10 56.56 56.56 12460.90 39954.81 01-MAR-12:40
April 0.00 0.00 01-APR-00:03 57.93 57.93 10707.24 36293.94 03-APR-11:20
May 0.00 0.00 01-MAY-00:03 58.57 58.57 9907.69 32609.11 01-MAY-11:30
June 0.00 0.00 01-JUN-00:10 58.38 58.38 9215.80 29022.62 01-JUN-12:00
July 0.00 0.00 01-JUL-00:03 58.06 58.06 8271.59 26830.22 03-JUL-11:20
August 0.00 0.00 01-AUG-00:03 58.57 58.57 9179.75 28572.30 31-AUG-11:50
September 0.00 0.00 01-SEP-00:05 56.89 56.89 9468.39 31771.68 29-SEP-11:20
October 0.00 0.00 01-OCT-00:03 57.43 57.43 10512.63 35911.19 31-OCT-11:50
November 0.00 0.00 01-NOV-00:10 57.21 57.21 11729.89 39429.38 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 56.75 56.75 12146.27 41510.39 29-DEC-13:00
                 
Annual Sum or Average 0.00         10731.89    
Minimum of Months 0.00 0.00   56.56 56.56 8271.59 26830.22  
Maximum of Months 0.00 0.00   58.57 58.57 12736.38 41939.78  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 244589.05 1138789.27 25-JAN-15:50 24.75 21.10 2780.89 142006.95 21-JAN-06:30
February 351751.30 1572203.41 25-FEB-06:02 23.62 22.31 952.10 132838.06 02-FEB-07:00
March 605254.13 3340521.99 10-MAR-17:00 26.45 23.33 210.17 78791.98 01-MAR-04:30
April 1095135.57 5094516.93 18-APR-14:00 29.26 25.58 116.49 31528.10 09-APR-23:27
May 2269400.51 6858010.74 17-MAY-15:30 32.08 27.83 0.00 0.00 01-MAY-00:03
June 3402094.33 7900866.08 22-JUN-15:50 33.75 28.96 0.00 0.00 01-JUN-00:10
July 4395535.27 7926461.46 31-JUL-05:03 33.80 28.97 0.00 0.00 01-JUL-00:03
August 4401664.96 7980936.25 28-AUG-05:03 33.88 29.00 0.00 0.00 01-AUG-00:03
September 3000791.17 7547560.56 14-SEP-15:30 33.19 28.77 0.00 0.00 01-SEP-00:05
October 982297.67 4800260.76 04-OCT-05:04 28.79 24.34 29.97 30147.33 30-OCT-01:50
November 487846.39 2764266.70 13-NOV-14:30 25.53 21.10 493.63 84869.05 27-NOV-03:30
December 287802.45 1182753.60 01-DEC-15:40 24.89 21.10 1490.54 144666.78 23-DEC-07:00
                 
Annual Sum or Average 1803309.38         506.36    
Minimum of Months 244589.05 1138789.27   23.62 21.10 0.00 0.00  
Maximum of Months 4401664.96 7980936.25   33.88 29.00 2780.89 144666.78  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 9289584.61 0.00 0.551477E+11 0.613777E+10 0.00 0.00
February 0.00 0.00 0.727524E+11 0.711973E+10 0.00 0.00
March 0.00 0.00 0.129389E+12 0.111338E+11 0.00 0.00
April 0.00 0.00 0.185927E+12 0.138470E+11 0.00 0.00
May 0.00 0.00 0.225479E+12 0.132897E+11 0.00 0.00
June 0.00 0.00 0.264382E+12 0.140456E+11 0.00 0.00
July 0.00 0.00 0.305430E+12 0.141774E+11 0.00 0.00
August 0.00 0.00 0.330330E+12 0.173631E+11 0.00 0.00
September 0.00 0.00 0.227887E+12 0.109296E+11 0.00 0.00
October 0.00 0.00 0.156275E+12 0.105351E+11 0.00 0.00
November 0.00 0.00 0.107927E+12 0.930219E+10 0.00 0.00
December 5407126.38 0.00 0.763068E+11 0.842569E+10 0.00 0.00
             
Annual Sum or Average 14696711.00 0.00 0.213723E+13 0.136307E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.551477E+11 0.613777E+10 0.00 0.00
Maximum of Months 9289584.61 0.00 0.330330E+12 0.173631E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.429736E+10 0.00 0.399574E+12 0.449800E+11 0.00 0.00
February 0.385667E+09 0.00 0.539654E+12 0.499375E+11 0.00 0.00
March 0.00 0.00 0.998560E+12 0.793905E+11 0.00 0.00
April 0.00 0.00 0.144127E+13 0.981349E+11 0.00 0.00
May 0.00 0.00 0.206128E+13 0.113842E+12 0.00 0.00
June 0.00 0.00 0.233610E+13 0.112808E+12 0.00 0.00
July 0.00 0.00 0.255859E+13 0.102204E+12 0.00 0.00
August 0.00 0.00 0.254024E+13 0.106187E+12 0.00 0.00
September 0.00 0.00 0.198051E+13 0.894786E+11 0.00 0.00
October 0.00 0.00 0.128008E+13 0.782988E+11 0.00 0.00
November 0.00 0.00 0.801234E+12 0.611042E+11 0.00 0.00
December 0.123750E+10 0.00 0.466031E+12 0.484460E+11 0.00 0.00
             
Annual Sum or Average 0.592053E+10 0.00 0.174031E+14 0.984812E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.399574E+12 0.449800E+11 0.00 0.00
Maximum of Months 0.429736E+10 0.00 0.255859E+13 0.113842E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.531844E+10 0.00 0.292588E+11 0.346403E+10 0.00 0.00
February 0.978304E+09 0.00 0.477579E+11 0.405743E+10 0.00 0.00
March 2066914.10 0.00 0.102628E+12 0.749354E+10 0.00 0.00
April 0.00 0.00 0.162918E+12 0.108785E+11 0.00 0.00
May 0.00 0.00 0.236869E+12 0.134300E+11 0.00 0.00
June 0.00 0.00 0.265561E+12 0.134036E+11 0.00 0.00
July 0.00 0.00 0.283916E+12 0.115360E+11 0.00 0.00
August 0.00 0.00 0.276710E+12 0.114524E+11 0.00 0.00
September 0.00 0.00 0.213524E+12 0.937494E+10 0.00 0.00
October 0.00 0.00 0.132816E+12 0.787926E+10 0.00 0.00
November 98170484.54 0.00 0.744814E+11 0.540165E+10 0.00 0.00
December 0.228854E+10 0.00 0.357410E+11 0.365090E+10 0.00 0.00
             
Annual Sum or Average 0.868552E+10 0.00 0.186218E+13 0.102022E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.292588E+11 0.346403E+10 0.00 0.00
Maximum of Months 0.531844E+10 0.00 0.283916E+12 0.134300E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.560333E+11 0.167064E+11 0.00 0.00
February 0.00 0.00 0.573217E+11 0.148366E+11 0.00 0.00
March 0.00 0.00 0.787844E+11 0.167797E+11 0.00 0.00
April 0.00 0.00 0.900437E+11 0.156489E+11 0.00 0.00
May 0.00 0.00 0.115380E+12 0.167857E+11 0.00 0.00
June 0.00 0.00 0.134888E+12 0.168586E+11 0.00 0.00
July 0.00 0.00 0.155844E+12 0.174745E+11 0.00 0.00
August 0.00 0.00 0.174314E+12 0.186617E+11 0.00 0.00
September 0.00 0.00 0.139122E+12 0.175204E+11 0.00 0.00
October 0.00 0.00 0.101533E+12 0.180738E+11 0.00 0.00
November 0.00 0.00 0.787329E+11 0.173156E+11 0.00 0.00
December 0.00 0.00 0.635985E+11 0.171902E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.124560E+13 0.203852E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.560333E+11 0.148366E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.174314E+12 0.186617E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.426450E+12 0.196810E+12 0.00 4.46
February 0.00 0.00 0.676125E+12 0.242845E+12 0.00 4.87
March 0.00 0.00 0.109184E+13 0.358738E+12 0.00 2.51
April 0.00 0.00 0.140584E+13 0.465405E+12 0.00 0.35
May 0.00 0.00 0.512636E+12 0.246158E+12 0.00 0.01
June 0.00 0.00 0.845747E+12 0.340101E+12 0.00 0.00
July 0.00 0.00 0.121508E+13 0.437222E+12 0.00 0.00
August 0.00 0.00 0.149328E+13 0.489673E+12 0.00 0.00
September 0.00 0.00 0.500182E+12 0.226623E+12 0.00 0.00
October 0.00 0.00 0.801115E+12 0.296642E+12 0.00 0.49
November 0.00 0.00 0.104884E+13 0.337862E+12 0.00 5.07
December 0.00 0.00 0.137071E+13 0.402098E+12 0.00 12.81
             
Annual Sum or Average 0.00 0.00 0.113878E+14 0.404018E+13 0.00 30.57
Minimum of Months 0.00 0.00 0.426450E+12 0.196810E+12 0.00 0.00
Maximum of Months 0.00 0.00 0.149328E+13 0.489673E+12 0.00 12.81



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.631444E+10 0.277674E+10 0.00 0.00
February 0.00 0.00 0.121721E+11 0.387231E+10 0.00 0.00
March 0.00 0.00 0.211406E+11 0.633824E+10 0.00 0.00
April 0.00 0.00 0.285069E+11 0.893001E+10 0.00 0.00
May 0.00 0.00 0.101273E+11 0.434086E+10 0.00 0.00
June 0.00 0.00 0.172478E+11 0.630028E+10 0.00 0.00
July 0.00 0.00 0.250036E+11 0.826515E+10 0.00 0.00
August 0.00 0.00 0.311317E+11 0.962103E+10 0.00 0.00
September 0.00 0.00 0.994044E+10 0.396524E+10 0.00 0.00
October 0.00 0.00 0.155262E+11 0.523613E+10 0.00 0.00
November 0.00 0.00 0.199603E+11 0.576183E+10 0.00 0.00
December 0.00 0.00 0.256520E+11 0.652953E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.222723E+12 0.719374E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.631444E+10 0.277674E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.311317E+11 0.962103E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.479183E+11 0.240772E+11 0.00 0.00
February 0.00 0.00 0.108625E+12 0.355071E+11 0.00 0.00
March 0.00 0.00 0.199680E+12 0.600541E+11 0.00 0.00
April 0.00 0.00 0.270727E+12 0.849000E+11 0.00 0.00
May 0.00 0.00 0.955601E+11 0.410947E+11 0.00 0.00
June 0.00 0.00 0.164428E+12 0.600152E+11 0.00 0.00
July 0.00 0.00 0.238673E+12 0.787969E+11 0.00 0.00
August 0.00 0.00 0.295755E+12 0.915644E+11 0.00 0.00
September 0.00 0.00 0.934942E+11 0.374501E+11 0.00 0.00
October 0.00 0.00 0.146212E+12 0.495072E+11 0.00 0.00
November 0.00 0.00 0.185243E+12 0.539667E+11 0.00 0.00
December 0.00 0.00 0.234056E+12 0.604393E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.208037E+13 0.677373E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.479183E+11 0.240772E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.295755E+12 0.915644E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.302630E+10 0.206650E+10 0.00 0.00
February 0.00 0.00 0.100428E+11 0.341475E+10 0.00 0.00
March 0.00 0.00 0.197954E+11 0.600976E+10 0.00 0.00
April 0.00 0.00 0.273521E+11 0.861692E+10 0.00 0.00
May 0.00 0.00 0.990884E+10 0.422826E+10 0.00 0.00
June 0.00 0.00 0.167862E+11 0.612674E+10 0.00 0.00
July 0.00 0.00 0.242188E+11 0.801397E+10 0.00 0.00
August 0.00 0.00 0.300706E+11 0.934641E+10 0.00 0.00
September 0.00 0.00 0.947728E+10 0.379651E+10 0.00 0.00
October 0.00 0.00 0.145586E+11 0.496816E+10 0.00 0.00
November 0.00 0.00 0.179464E+11 0.532066E+10 0.00 0.00
December 0.00 0.00 0.220378E+11 0.584083E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.205221E+12 0.677495E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.302630E+10 0.206650E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.300706E+11 0.934641E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.613777E+10 0.551477E+11 9289584.61 0.00 0.00 0.00 0.00 0.00
February 0.711973E+10 0.727524E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.111338E+11 0.129389E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.138470E+11 0.185927E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132897E+11 0.225479E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.140456E+11 0.264382E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.141774E+11 0.305430E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.173631E+11 0.330330E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.109296E+11 0.227887E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.105351E+11 0.156275E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.930219E+10 0.107927E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.842569E+10 0.763068E+11 5407126.38 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.136307E+12 0.213723E+13 14696711.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.613777E+10 0.551477E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.173631E+11 0.330330E+12 9289584.61 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.449800E+11 0.399574E+12 0.429736E+10 0.00 0.00 0.00 0.00 0.00
February 0.499375E+11 0.539654E+12 0.385667E+09 0.00 0.00 0.00 0.00 0.00
March 0.793905E+11 0.998560E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.981349E+11 0.144127E+13 0.00 0.00 0.00 0.00 0.00 0.00
May 0.113842E+12 0.206128E+13 0.00 0.00 0.00 0.00 0.00 0.00
June 0.112808E+12 0.233610E+13 0.00 0.00 0.00 0.00 0.00 0.00
July 0.102204E+12 0.255859E+13 0.00 0.00 0.00 0.00 0.00 0.00
August 0.106187E+12 0.254024E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.894786E+11 0.198051E+13 0.00 0.00 0.00 0.00 0.00 0.00
October 0.782988E+11 0.128008E+13 0.00 0.00 0.00 0.00 0.00 0.00
November 0.611042E+11 0.801234E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.484460E+11 0.466031E+12 0.123750E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.984812E+12 0.174031E+14 0.592053E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.449800E+11 0.399574E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.113842E+12 0.255859E+13 0.429736E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.346403E+10 0.292588E+11 0.531844E+10 0.00 0.00 0.00 0.00 0.00
February 0.405743E+10 0.477579E+11 0.978304E+09 0.00 0.00 0.00 0.00 0.00
March 0.749354E+10 0.102628E+12 2066914.10 0.00 0.00 0.00 0.00 0.00
April 0.108785E+11 0.162918E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.134300E+11 0.236869E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134036E+11 0.265561E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.115360E+11 0.283916E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.114524E+11 0.276710E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.937494E+10 0.213524E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.787926E+10 0.132816E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.540165E+10 0.744814E+11 98170484.54 0.00 0.00 0.00 0.00 0.00
December 0.365090E+10 0.357410E+11 0.228854E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.102022E+12 0.186218E+13 0.868552E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.346403E+10 0.292588E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.134300E+11 0.283916E+12 0.531844E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.167064E+11 0.560333E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.148366E+11 0.573217E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.167797E+11 0.787844E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.156489E+11 0.900437E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.167857E+11 0.115380E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.168586E+11 0.134888E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.174745E+11 0.155844E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.186617E+11 0.174314E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.175204E+11 0.139122E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.180738E+11 0.101533E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.173156E+11 0.787329E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.171902E+11 0.635985E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.203852E+12 0.124560E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.148366E+11 0.560333E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.186617E+11 0.174314E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.970462E+11 0.338687E+12 0.00 0.00 0.00 0.119472E+11 0.00 0.00
February 0.876546E+11 0.534019E+12 0.00 0.00 0.00 0.130253E+11 0.00 0.00
March 0.970462E+11 0.836897E+12 0.00 0.00 0.00 0.671590E+10 0.00 0.00
April 0.939157E+11 0.103528E+13 0.00 0.00 0.00 0.930960E+09 0.00 0.00
May 0.970462E+11 0.363541E+12 0.00 0.00 0.00 16418864.26 0.00 0.00
June 0.939157E+11 0.599562E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.970462E+11 0.874908E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.970462E+11 0.110066E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.939157E+11 0.367475E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.970462E+11 0.602836E+12 0.00 0.00 0.00 0.131045E+10 0.00 0.00
November 0.939157E+11 0.818523E+12 0.00 0.00 0.00 0.135687E+11 0.00 0.00
December 0.970462E+11 0.110010E+13 0.00 0.00 0.00 0.342896E+11 0.00 0.00
                 
Annual Sum or Average 0.114264E+13 0.857248E+13 0.00 0.00 0.00 0.818045E+11 0.00 0.00
Minimum of Months 0.876546E+11 0.338687E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.970462E+11 0.110066E+13 0.00 0.00 0.00 0.342896E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.147086E+10 0.500855E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.132851E+10 0.962832E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.147086E+10 0.162732E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.142341E+10 0.210003E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.147086E+10 0.725726E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142341E+10 0.123709E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147086E+10 0.182093E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.147086E+10 0.229816E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.142341E+10 0.739861E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.147086E+10 0.117609E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.142341E+10 0.156218E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.147086E+10 0.205933E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.173181E+11 0.168104E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.132851E+10 0.500855E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147086E+10 0.229816E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.140096E+11 0.378506E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.126538E+11 0.857714E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.140096E+11 0.153635E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.135576E+11 0.199385E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140096E+11 0.684750E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.135576E+11 0.117971E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.140096E+11 0.173886E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.140096E+11 0.218200E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.135576E+11 0.696018E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.140096E+11 0.110715E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.135576E+11 0.144834E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140096E+11 0.187626E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.164951E+12 0.156795E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.126538E+11 0.378506E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140096E+11 0.218200E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.140937E+10 0.236917E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.127298E+10 0.790104E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.140937E+10 0.151950E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.136391E+10 0.200991E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140937E+10 0.708995E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.136391E+10 0.120234E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.140937E+10 0.176142E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.140937E+10 0.221336E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.136391E+10 0.704468E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.140937E+10 0.109998E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.136391E+10 0.139896E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140937E+10 0.176063E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.165942E+11 0.154066E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.127298E+10 0.236917E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140937E+10 0.221336E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.613777E+10 9289584.61 0.551477E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.711973E+10 0.00 0.727524E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.111338E+11 0.00 0.129389E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.138470E+11 0.00 0.185927E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132897E+11 0.00 0.225479E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.140456E+11 0.00 0.264382E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.141774E+11 0.00 0.305430E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.173631E+11 0.00 0.330330E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.109296E+11 0.00 0.227887E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.105351E+11 0.00 0.156275E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.930219E+10 0.00 0.107927E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.842569E+10 5407126.38 0.763068E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.136307E+12 14696711.00 0.213723E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.613777E+10 0.00 0.551477E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.173631E+11 9289584.61 0.330330E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.449800E+11 0.429736E+10 0.399574E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.499375E+11 0.385667E+09 0.539654E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.793905E+11 0.00 0.998560E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.981349E+11 0.00 0.144127E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.113842E+12 0.00 0.206128E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.112808E+12 0.00 0.233610E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.102204E+12 0.00 0.255859E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.106187E+12 0.00 0.254024E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.894786E+11 0.00 0.198051E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.782988E+11 0.00 0.128008E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.611042E+11 0.00 0.801234E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.484460E+11 0.123750E+10 0.466031E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.984812E+12 0.592053E+10 0.174031E+14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.449800E+11 0.00 0.399574E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.113842E+12 0.429736E+10 0.255859E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.346403E+10 0.531844E+10 0.292588E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.405743E+10 0.978304E+09 0.477579E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.749354E+10 2066914.10 0.102628E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.108785E+11 0.00 0.162918E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.134300E+11 0.00 0.236869E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134036E+11 0.00 0.265561E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.115360E+11 0.00 0.283916E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.114524E+11 0.00 0.276710E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.937494E+10 0.00 0.213524E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.787926E+10 0.00 0.132816E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.540165E+10 98170484.54 0.744814E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.365090E+10 0.228854E+10 0.357410E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.102022E+12 0.868552E+10 0.186218E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.346403E+10 0.00 0.292588E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.134300E+11 0.531844E+10 0.283916E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.167064E+11 0.00 0.560333E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.148366E+11 0.00 0.573217E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.167797E+11 0.00 0.787844E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.156489E+11 0.00 0.900437E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.167857E+11 0.00 0.115380E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.168586E+11 0.00 0.134888E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.174745E+11 0.00 0.155844E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.186617E+11 0.00 0.174314E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.175204E+11 0.00 0.139122E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.180738E+11 0.00 0.101533E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.173156E+11 0.00 0.787329E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.171902E+11 0.00 0.635985E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.203852E+12 0.00 0.124560E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.148366E+11 0.00 0.560333E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.186617E+11 0.00 0.174314E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.970462E+11 0.00 0.426450E+12 0.00 0.877633E+11 0.00 0.00 0.00 0.120010E+11 0.00 0.00 0.00
February 0.876546E+11 0.00 0.676125E+12 0.00 0.142106E+12 0.00 0.00 0.00 0.130839E+11 0.00 0.00 0.00
March 0.970462E+11 0.00 0.109184E+13 0.00 0.254946E+12 0.00 0.00 0.00 0.674613E+10 0.00 0.00 0.00
April 0.939157E+11 0.00 0.140584E+13 0.00 0.370554E+12 0.00 0.00 0.00 0.935151E+09 0.00 0.00 0.00
May 0.970462E+11 0.00 0.512636E+12 0.00 0.149095E+12 0.00 0.00 0.00 16492772.22 0.00 0.00 0.00
June 0.939157E+11 0.00 0.845747E+12 0.00 0.246185E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.970462E+11 0.00 0.121508E+13 0.00 0.340176E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.970462E+11 0.00 0.149328E+13 0.00 0.392627E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.939157E+11 0.00 0.500182E+12 0.00 0.132707E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.970462E+11 0.00 0.801115E+12 0.00 0.198279E+12 0.00 0.00 0.00 0.131635E+10 0.00 0.00 0.00
November 0.939157E+11 0.00 0.104884E+13 0.00 0.230316E+12 0.00 0.00 0.00 0.136297E+11 0.00 0.00 0.00
December 0.970462E+11 0.00 0.137071E+13 0.00 0.270608E+12 0.00 0.00 0.00 0.344439E+11 0.00 0.00 0.00
                         
Annual Sum or Average 0.114264E+13 0.00 0.113878E+14 0.00 0.281536E+13 0.00 0.00 0.00 0.821727E+11 0.00 0.00 0.00
Minimum of Months 0.876546E+11 0.00 0.426450E+12 0.00 0.877633E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.970462E+11 0.00 0.149328E+13 0.00 0.392627E+12 0.00 0.00 0.00 0.344439E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.147086E+10 0.00 0.631444E+10 0.00 0.130589E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.132851E+10 0.00 0.121721E+11 0.00 0.254379E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.147086E+10 0.00 0.211406E+11 0.00 0.486739E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.142341E+10 0.00 0.285069E+11 0.00 0.750660E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.147086E+10 0.00 0.101273E+11 0.00 0.287000E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142341E+10 0.00 0.172478E+11 0.00 0.487687E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147086E+10 0.00 0.250036E+11 0.00 0.679429E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.147086E+10 0.00 0.311317E+11 0.00 0.815018E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.142341E+10 0.00 0.994044E+10 0.00 0.254184E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.147086E+10 0.00 0.155262E+11 0.00 0.376527E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.142341E+10 0.00 0.199603E+11 0.00 0.433842E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.147086E+10 0.00 0.256520E+11 0.00 0.505868E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.173181E+11 0.00 0.222723E+12 0.00 0.546192E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.132851E+10 0.00 0.631444E+10 0.00 0.130589E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147086E+10 0.00 0.311317E+11 0.00 0.815018E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.140096E+11 0.00 0.479183E+11 0.00 0.100677E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.126538E+11 0.00 0.108625E+12 0.00 0.228533E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.140096E+11 0.00 0.199680E+12 0.00 0.460445E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.135576E+11 0.00 0.270727E+12 0.00 0.713424E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140096E+11 0.00 0.955601E+11 0.00 0.270851E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.135576E+11 0.00 0.164428E+12 0.00 0.464575E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.140096E+11 0.00 0.238673E+12 0.00 0.647873E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.140096E+11 0.00 0.295755E+12 0.00 0.775549E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.135576E+11 0.00 0.934942E+11 0.00 0.238924E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.140096E+11 0.00 0.146212E+12 0.00 0.354976E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.135576E+11 0.00 0.185243E+12 0.00 0.404091E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140096E+11 0.00 0.234056E+12 0.00 0.464298E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.164951E+12 0.00 0.208037E+13 0.00 0.512422E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.126538E+11 0.00 0.479183E+11 0.00 0.100677E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140096E+11 0.00 0.295755E+12 0.00 0.775549E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.140937E+10 0.00 0.302630E+10 0.00 0.657129E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.127298E+10 0.00 0.100428E+11 0.00 0.214177E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.140937E+10 0.00 0.197954E+11 0.00 0.460039E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.136391E+10 0.00 0.273521E+11 0.00 0.725302E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140937E+10 0.00 0.990884E+10 0.00 0.281889E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.136391E+10 0.00 0.167862E+11 0.00 0.476283E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.140937E+10 0.00 0.242188E+11 0.00 0.660460E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.140937E+10 0.00 0.300706E+11 0.00 0.793704E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.136391E+10 0.00 0.947728E+10 0.00 0.243260E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.140937E+10 0.00 0.145586E+11 0.00 0.355879E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.136391E+10 0.00 0.179464E+11 0.00 0.395676E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140937E+10 0.00 0.220378E+11 0.00 0.443145E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.165942E+11 0.00 0.205221E+12 0.00 0.511553E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.127298E+10 0.00 0.302630E+10 0.00 0.657129E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140937E+10 0.00 0.300706E+11 0.00 0.793704E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.253534E+10 0.00 0.00 0.123213E+09 0.00 0.00 0.260623E+11 0.00 0.40
February 0.951979E+09 0.00 0.00 0.112811E+09 0.00 0.00 0.168316E+11 0.00 0.39
March 0.371806E+09 0.152888E+10 0.00 0.101890E+09 27128244.13 0.00 0.854217E+10 0.00 0.40
April 20277093.79 0.106481E+11 0.00 23278920.19 0.275363E+09 0.00 0.550787E+09 0.00 0.39
May 7980773.40 0.299847E+11 0.00 3655843.92 0.512674E+09 0.00 55938996.63 0.00 0.41
June 0.00 0.464983E+11 0.00 761958.80 0.823218E+09 0.00 1204386.27 0.00 0.43
July 0.00 0.635183E+11 0.00 0.00 0.151967E+10 0.00 0.00 0.00 0.43
August 0.00 0.707933E+11 0.00 0.00 0.118707E+10 0.00 0.00 0.00 0.46
September 0.00 0.467536E+11 0.00 0.00 0.105432E+10 0.00 0.00 0.00 0.44
October 0.199071E+09 0.882792E+10 0.00 64773967.69 0.147078E+09 0.00 0.291520E+10 0.00 0.44
November 0.939481E+09 0.242066E+09 0.00 0.144728E+09 20523950.90 0.00 0.133170E+11 0.00 0.43
December 0.195219E+10 0.00 0.00 0.136110E+09 0.00 0.00 0.244035E+11 0.00 0.41
                   
Annual Sum or Average 0.697812E+10 0.278795E+12 0.00 0.711222E+09 0.556705E+10 0.00 0.926796E+11 0.00 0.42
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.39
Maximum of Months 0.253534E+10 0.707933E+11 0.00 0.144728E+09 0.151967E+10 0.00 0.260623E+11 0.00 0.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.197533E+10 0.00 0.00 85993123.41 0.00 0.00 0.221948E+11 0.00 0.33
February 0.189135E+10 0.00 0.00 87065429.11 2793699.20 0.00 0.146707E+11 0.00 0.35
March 0.225627E+10 0.114489E+10 0.00 87252076.75 0.370551E+09 0.00 0.793563E+10 0.00 0.40
April 0.586023E+09 0.702941E+10 0.00 24046421.98 0.381400E+10 0.00 0.769844E+09 0.00 0.44
May 11775318.21 0.236038E+11 0.00 734918.95 0.978374E+10 0.00 11818269.12 0.00 0.42
June 0.00 0.357910E+11 0.00 0.00 0.176203E+11 0.00 0.00 0.00 0.43
July 0.00 0.457924E+11 0.00 0.00 0.304622E+11 0.00 0.00 0.00 0.44
August 0.00 0.527069E+11 0.00 0.00 0.278592E+11 0.00 0.00 0.00 0.46
September 0.00 0.359314E+11 0.00 0.00 0.144480E+11 0.00 0.00 0.00 0.39
October 0.786213E+09 0.759374E+10 0.00 32844093.99 0.177336E+10 0.00 0.209787E+10 0.00 0.39
November 0.233219E+10 0.168018E+09 0.00 99890310.25 77225309.60 0.00 0.110264E+11 0.00 0.37
December 0.297583E+10 0.00 0.00 0.101984E+09 0.00 0.00 0.207251E+11 0.00 0.36
                   
Annual Sum or Average 0.128150E+11 0.209761E+12 0.00 0.519811E+09 0.106211E+12 0.00 0.794321E+11 0.00 0.40
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.33
Maximum of Months 0.297583E+10 0.527069E+11 0.00 0.101984E+09 0.304622E+11 0.00 0.221948E+11 0.00 0.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.243682E+11 0.00 0.00 0.544189E+09 0.00 0.00 0.179442E+12 0.00 0.30
February 0.129813E+11 0.00 0.00 0.622423E+09 0.104852E+09 0.00 0.126757E+12 0.00 0.32
March 0.985024E+10 0.116764E+11 0.00 0.721428E+09 0.322335E+10 0.00 0.736467E+11 0.00 0.34
April 0.212018E+10 0.679617E+11 0.00 0.188959E+09 0.304634E+11 0.00 0.609001E+10 0.00 0.36
May 85829221.13 0.232176E+12 0.00 4143289.54 0.867108E+11 0.00 0.107212E+09 0.00 0.40
June 0.00 0.349762E+12 0.00 0.00 0.137766E+12 0.00 0.00 0.00 0.39
July 0.00 0.440936E+12 0.00 0.00 0.214576E+12 0.00 0.00 0.00 0.38
August 0.00 0.500496E+12 0.00 0.00 0.158129E+12 0.00 0.00 0.00 0.38
September 0.00 0.352204E+12 0.00 0.00 0.936240E+11 0.00 0.00 0.00 0.35
October 0.489358E+10 0.751065E+11 0.00 0.259417E+09 0.128150E+11 0.00 0.183813E+11 0.00 0.34
November 0.146162E+11 0.178693E+10 0.00 0.720146E+09 0.954637E+09 0.00 0.923153E+11 0.00 0.33
December 0.192555E+11 0.00 0.00 0.579215E+09 12399877.70 0.00 0.168171E+12 0.00 0.31
                   
Annual Sum or Average 0.881710E+11 0.203211E+13 0.00 0.363992E+10 0.738379E+12 0.00 0.664911E+12 0.00 0.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Maximum of Months 0.243682E+11 0.500496E+12 0.00 0.721428E+09 0.214576E+12 0.00 0.179442E+12 0.00 0.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.104298E+11 0.00 0.00 19355079.83 0.00 0.233782E+09 0.616089E+10 0.00 0.27
February 0.431127E+10 0.00 0.00 37247640.85 4642977.54 0.00 0.729740E+10 0.00 0.29
March 0.104493E+10 0.841021E+09 0.00 62558856.14 0.231846E+09 0.00 0.634234E+10 0.00 0.32
April 0.180806E+09 0.595976E+10 0.00 23882923.88 0.269314E+10 0.00 0.707526E+09 0.00 0.37
May 6788607.89 0.223713E+11 0.00 299995.44 0.836285E+10 0.00 9253967.79 0.00 0.40
June 0.00 0.343220E+11 0.00 0.00 0.138710E+11 0.00 0.00 0.00 0.40
July 0.00 0.438972E+11 0.00 0.00 0.216475E+11 0.00 0.00 0.00 0.39
August 0.00 0.495737E+11 0.00 0.00 0.161728E+11 0.00 0.00 0.00 0.39
September 0.00 0.341007E+11 0.00 0.00 0.102331E+11 0.00 0.00 0.00 0.35
October 0.397465E+09 0.659159E+10 0.00 23741757.23 0.106768E+10 0.00 0.148508E+10 0.00 0.33
November 0.259380E+10 50009841.54 0.00 52509383.08 77500709.36 0.00 0.617079E+10 0.00 0.30
December 0.800829E+10 0.00 0.00 26020864.35 40838.80 0.00 0.695354E+10 0.00 0.27
                   
Annual Sum or Average 0.269731E+11 0.197707E+12 0.00 0.245617E+09 0.743621E+11 0.233782E+09 0.351268E+11 0.00 0.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.27
Maximum of Months 0.104298E+11 0.495737E+11 0.00 62558856.14 0.216475E+11 0.233782E+09 0.729740E+10 0.00 0.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.231095E+10 0.00 0.00 2757354.67 0.00 0.00 0.767901E+09 0.00 0.33
February 0.128259E+10 0.00 0.00 5281737.33 518926.24 0.00 0.850520E+09 0.00 0.36
March 0.660845E+09 0.196850E+09 0.00 8652596.97 68829429.03 0.00 0.770233E+09 0.00 0.47
April 0.119898E+09 0.140366E+10 0.00 3350977.36 0.698894E+09 0.00 98912131.87 0.00 0.64
May 1465443.78 0.531235E+10 0.00 149236.96 0.166977E+10 0.00 3214692.43 0.00 0.68
June 0.00 0.824392E+10 0.00 0.00 0.296490E+10 0.00 0.00 0.00 0.71
July 0.00 0.102078E+11 0.00 0.00 0.510513E+10 0.00 0.00 0.00 0.70
August 0.00 0.103319E+11 0.00 0.00 0.495472E+10 0.00 0.00 0.00 0.69
September 0.00 0.649231E+10 0.00 0.00 0.269341E+10 0.00 0.00 0.00 0.56
October 0.208445E+09 0.122728E+10 0.00 2778564.75 0.336612E+09 0.00 0.197357E+09 0.00 0.49
November 0.994323E+09 24333294.65 0.00 7541347.25 14344507.77 0.00 0.760002E+09 0.00 0.39
December 0.196301E+10 0.00 0.00 4766538.95 0.00 0.00 0.916537E+09 0.00 0.34
                   
Annual Sum or Average 0.754152E+10 0.434404E+11 0.00 35278354.24 0.185071E+11 0.00 0.436468E+10 0.00 0.53
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.33
Maximum of Months 0.231095E+10 0.103319E+11 0.00 8652596.97 0.510513E+10 0.00 0.916537E+09 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.161366E+10 0.00 0.00 3086918.09 0.00 0.00 0.823326E+09 0.00 0.40
February 0.952392E+09 0.00 0.00 4717963.25 404659.12 0.00 0.791621E+09 0.00 0.45
March 0.533269E+09 0.142668E+09 0.00 7061536.47 53265042.97 0.00 0.639289E+09 0.00 0.59
April 98418988.37 0.109186E+10 0.00 2710703.04 0.525594E+09 0.00 80896817.59 0.00 0.78
May 1285150.13 0.423510E+10 0.00 92335.62 0.123381E+10 0.00 2156235.73 0.00 0.84
June 0.00 0.571388E+10 0.00 0.00 0.242525E+10 0.00 0.00 0.00 0.81
July 0.00 0.650516E+10 0.00 0.00 0.423036E+10 0.00 0.00 0.00 0.76
August 0.00 0.600667E+10 0.00 0.00 0.422392E+10 0.00 0.00 0.00 0.72
September 0.00 0.466171E+10 0.00 0.00 0.212463E+10 0.00 0.00 0.00 0.65
October 0.197541E+09 0.913172E+09 0.00 2355478.13 0.260791E+09 0.00 0.139987E+09 0.00 0.60
November 0.844612E+09 17112082.90 0.00 5858458.65 11185859.23 0.00 0.568937E+09 0.00 0.48
December 0.156783E+10 0.00 0.00 3521339.94 0.00 0.00 0.668003E+09 0.00 0.41
                   
Annual Sum or Average 0.580900E+10 0.292873E+11 0.00 29404733.20 0.150892E+11 0.00 0.371422E+10 0.00 0.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.40
Maximum of Months 0.161366E+10 0.650516E+10 0.00 7061536.47 0.423036E+10 0.00 0.823326E+09 0.00 0.84



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.160248E+10 0.00 0.00 10672673.74 0.00 0.00 0.250283E+10 0.00 0.47
February 0.985412E+09 380532.15 0.00 13421918.21 188379.28 0.00 0.180561E+10 0.00 0.51
March 0.599987E+09 0.332331E+09 0.00 13970252.42 39060233.10 0.00 0.116444E+10 0.00 0.62
April 0.119607E+09 0.185601E+10 0.00 4243889.51 0.600852E+09 0.00 0.115606E+09 0.00 0.73
May 1467343.88 0.565292E+10 0.00 159690.72 0.160666E+10 0.00 3265661.44 0.00 0.71
June 0.00 0.817889E+10 0.00 0.00 0.304859E+10 0.00 0.00 0.00 0.71
July 0.00 0.103379E+11 0.00 0.00 0.511993E+10 0.00 0.00 0.00 0.71
August 0.00 0.109049E+11 0.00 0.00 0.488716E+10 0.00 0.00 0.00 0.71
September 0.00 0.807424E+10 0.00 0.00 0.243380E+10 0.00 0.00 0.00 0.65
October 0.178065E+09 0.204208E+10 0.00 5932322.31 0.233019E+09 0.00 0.299057E+09 0.00 0.69
November 0.708566E+09 61316501.30 0.00 21138051.05 9446436.12 0.00 0.170211E+10 0.00 0.61
December 0.136832E+10 0.00 0.00 14160524.39 0.00 0.00 0.248643E+10 0.00 0.49
                   
Annual Sum or Average 0.556390E+10 0.474410E+11 0.00 83699322.35 0.179787E+11 0.00 0.100794E+11 0.00 0.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
Maximum of Months 0.160248E+10 0.109049E+11 0.00 21138051.05 0.511993E+10 0.00 0.250283E+10 0.00 0.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.185380E+10 0.00 0.00 4619056.41 0.00 0.00 0.139590E+10 0.00 0.54
February 0.778598E+09 484732.86 0.00 8957023.29 75495.09 0.00 0.151536E+10 0.00 0.62
March 0.412867E+09 0.297705E+09 0.00 14419421.12 33595532.31 0.00 0.124071E+10 0.00 0.88
April 74596548.11 0.240504E+10 0.00 6115965.33 0.256153E+09 0.00 0.179241E+09 0.00 1.23
May 1157262.32 0.564736E+10 0.00 212680.08 0.127983E+10 0.00 3387559.23 0.00 1.06
June 0.00 0.912121E+10 0.00 0.00 0.219439E+10 0.00 0.00 0.00 1.12
July 0.00 0.120283E+11 0.00 0.00 0.359645E+10 0.00 0.00 0.00 1.11
August 0.00 0.151664E+11 0.00 0.00 0.224736E+10 0.00 0.00 0.00 1.22
September 0.00 0.670685E+10 0.00 0.00 0.230932E+10 0.00 0.00 0.00 0.86
October 0.164873E+09 0.145083E+10 0.00 4354255.67 0.250547E+09 0.00 0.258978E+09 0.00 0.83
November 0.565082E+09 41799301.37 0.00 13863125.01 9145046.07 0.00 0.139971E+10 0.00 0.72
December 0.746402E+09 0.00 0.00 12517636.71 0.00 0.00 0.262448E+10 0.00 0.65
                   
Annual Sum or Average 0.459738E+10 0.528660E+11 0.00 65059163.63 0.121769E+11 0.00 0.861777E+10 0.00 0.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.54
Maximum of Months 0.185380E+10 0.151664E+11 0.00 14419421.12 0.359645E+10 0.00 0.262448E+10 0.00 1.23



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.284279E+11 0.00 0.00 2123190.67 0.00 0.196742E+09 0.117039E+10 0.00 0.34
February 0.158227E+11 0.00 0.00 20991540.24 19170682.94 0.00 0.374341E+10 0.00 0.35
March 0.588590E+10 0.208005E+10 0.00 55308261.62 0.589652E+09 0.00 0.565885E+10 0.00 0.41
April 0.473584E+09 0.148873E+11 0.00 24595304.68 0.555279E+10 0.00 0.807901E+09 0.00 0.55
May 7914912.33 0.578275E+11 0.00 1308600.68 0.134949E+11 0.00 34185029.46 0.00 0.69
June 0.00 0.894130E+11 0.00 0.00 0.215078E+11 0.00 0.00 0.00 0.71
July 0.00 0.110797E+12 0.00 0.00 0.328464E+11 0.00 0.00 0.00 0.66
August 0.00 0.109325E+12 0.00 0.00 0.265219E+11 0.00 0.00 0.00 0.62
September 0.00 0.674123E+11 0.00 0.00 0.168230E+11 0.00 0.00 0.00 0.52
October 0.220197E+10 0.124418E+11 0.00 16073032.87 0.246591E+10 0.00 0.110708E+10 0.00 0.43
November 0.115571E+11 0.202279E+09 0.00 35777821.65 0.233257E+09 0.00 0.354159E+10 0.00 0.37
December 0.251515E+11 0.00 0.00 4751549.07 2267148.67 11957299.20 0.203394E+10 0.00 0.35
                   
Annual Sum or Average 0.895286E+11 0.464386E+12 0.00 0.160929E+09 0.120057E+12 0.208699E+09 0.180973E+11 0.00 0.50
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.34
Maximum of Months 0.284279E+11 0.110797E+12 0.00 55308261.62 0.328464E+11 0.196742E+09 0.565885E+10 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.212819E+11 0.00 0.00 6403059.24 0.00 18706693.77 0.344187E+10 0.00 0.43
February 0.109747E+11 0.00 0.00 31730435.11 15916247.97 0.00 0.590740E+10 0.00 0.47
March 0.408941E+10 0.175587E+10 0.00 63382270.59 0.476766E+09 0.00 0.649825E+10 0.00 0.58
April 0.320222E+09 0.141648E+11 0.00 27409266.30 0.392591E+10 0.00 0.906775E+09 0.00 0.78
May 7696151.61 0.489514E+11 0.00 878173.10 0.103389E+11 0.00 24343719.87 0.00 0.91
June 0.00 0.676055E+11 0.00 0.00 0.182164E+11 0.00 0.00 0.00 0.86
July 0.00 0.808939E+11 0.00 0.00 0.270296E+11 0.00 0.00 0.00 0.78
August 0.00 0.779928E+11 0.00 0.00 0.219776E+11 0.00 0.00 0.00 0.71
September 0.00 0.523811E+11 0.00 0.00 0.137832E+11 0.00 0.00 0.00 0.64
October 0.168796E+10 0.102642E+11 0.00 20377071.50 0.204804E+10 0.00 0.134390E+10 0.00 0.58
November 0.835533E+10 0.206108E+09 0.00 43840927.53 0.150045E+09 0.00 0.481233E+10 0.00 0.49
December 0.183777E+11 0.00 0.00 10073176.42 1882275.16 8827734.39 0.421154E+10 0.00 0.45
                   
Annual Sum or Average 0.650949E+11 0.354216E+12 0.00 0.204094E+09 0.979642E+11 27534428.16 0.271464E+11 0.00 0.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
Maximum of Months 0.212819E+11 0.808939E+11 0.00 63382270.59 0.270296E+11 18706693.77 0.649825E+10 0.00 0.91



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.161570E+11 0.00 0.00 97244609.72 0.00 0.00 0.239477E+11 0.00 0.49
February 0.950332E+10 14846985.51 0.00 0.117769E+09 7504382.35 0.00 0.172018E+11 0.00 0.53
March 0.400164E+10 0.389251E+10 0.00 0.123877E+09 0.202269E+09 0.00 0.114385E+11 0.00 0.59
April 0.401232E+09 0.206136E+11 0.00 35232376.65 0.444278E+10 0.00 0.104191E+10 0.00 0.67
May 7887307.41 0.610687E+11 0.00 1425213.32 0.130773E+11 0.00 34796267.87 0.00 0.72
June 0.00 0.881837E+11 0.00 0.00 0.221975E+11 0.00 0.00 0.00 0.70
July 0.00 0.111993E+12 0.00 0.00 0.327308E+11 0.00 0.00 0.00 0.67
August 0.00 0.118295E+12 0.00 0.00 0.242621E+11 0.00 0.00 0.00 0.65
September 0.00 0.868138E+11 0.00 0.00 0.136327E+11 0.00 0.00 0.00 0.62
October 0.973045E+09 0.229434E+11 0.00 48613603.58 0.117706E+10 0.00 0.319814E+10 0.00 0.69
November 0.545391E+10 0.840785E+09 0.00 0.193361E+09 84856967.12 0.00 0.172365E+11 0.00 0.66
December 0.138828E+11 770864.63 0.00 0.114795E+09 1516532.78 0.00 0.233144E+11 0.00 0.52
                   
Annual Sum or Average 0.503808E+11 0.514660E+12 0.00 0.732317E+09 0.111816E+12 0.00 0.974136E+11 0.00 0.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.49
Maximum of Months 0.161570E+11 0.118295E+12 0.00 0.193361E+09 0.327308E+11 0.00 0.239477E+11 0.00 0.72



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.229629E+11 0.00 0.00 14023598.52 0.00 11390569.37 0.380750E+10 0.00 0.47
February 0.129564E+11 387049.71 0.00 29408298.79 16627787.47 0.00 0.493368E+10 0.00 0.51
March 0.433800E+10 0.240654E+10 0.00 64232871.51 0.359297E+09 0.00 0.646300E+10 0.00 0.62
April 0.337330E+09 0.172464E+11 0.00 26180070.24 0.334337E+10 0.00 0.788577E+09 0.00 0.85
May 6247731.91 0.549170E+11 0.00 1277310.62 0.908152E+10 0.00 28489331.33 0.00 0.96
June 0.00 0.799669E+11 0.00 0.00 0.155721E+11 0.00 0.00 0.00 0.95
July 0.00 0.917101E+11 0.00 0.00 0.252106E+11 0.00 0.00 0.00 0.84
August 0.00 0.916036E+11 0.00 0.00 0.202799E+11 0.00 0.00 0.00 0.79
September 0.00 0.592349E+11 0.00 0.00 0.130485E+11 0.00 0.00 0.00 0.69
October 0.165515E+10 0.120177E+11 0.00 17295173.67 0.182891E+10 0.00 0.125802E+10 0.00 0.62
November 0.887343E+10 0.310467E+09 0.00 44160280.42 0.157111E+09 0.00 0.487985E+10 0.00 0.54
December 0.205431E+11 0.00 0.00 17727332.66 2012195.68 0.00 0.400296E+10 0.00 0.49
                   
Annual Sum or Average 0.716725E+11 0.409414E+12 0.00 0.214305E+09 0.888999E+11 11390569.37 0.261621E+11 0.00 0.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
Maximum of Months 0.229629E+11 0.917101E+11 0.00 64232871.51 0.252106E+11 11390569.37 0.646300E+10 0.00 0.96



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.248933E+10 0.00 0.00 24223.78 0.00 0.788502E+09 17673453.18 0.00 0.42
February 0.166850E+10 0.00 0.00 1186458.97 959553.66 0.172611E+09 0.209397E+09 0.00 0.40
March 0.657018E+09 0.147157E+09 0.00 4890352.74 50366783.18 0.00 0.503267E+09 0.00 0.43
April 61280533.95 0.126292E+10 0.00 3205689.08 0.539324E+09 0.00 94630041.19 0.00 0.57
May 652758.86 0.539722E+10 0.00 107076.86 0.137945E+10 0.00 3023061.09 0.00 0.71
June 0.00 0.848286E+10 0.00 0.00 0.231253E+10 0.00 0.00 0.00 0.72
July 0.00 0.109335E+11 0.00 0.00 0.347036E+10 0.00 0.00 0.00 0.69
August 0.00 0.107267E+11 0.00 0.00 0.288500E+10 0.00 0.00 0.00 0.63
September 0.00 0.650516E+10 0.00 0.00 0.209685E+10 0.00 0.00 0.00 0.54
October 0.246374E+09 0.104600E+10 0.00 1757652.80 0.302394E+09 0.00 78577764.14 0.00 0.46
November 0.124054E+10 2447789.74 0.00 2715416.05 22569410.78 387641.49 0.255971E+09 0.00 0.39
December 0.234047E+10 0.00 0.00 26546.30 8440.06 0.482550E+09 15173461.70 0.00 0.40
                   
Annual Sum or Average 0.870417E+10 0.445040E+11 0.00 13913416.59 0.130598E+11 0.144405E+10 0.117771E+10 0.00 0.53
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.39
Maximum of Months 0.248933E+10 0.109335E+11 0.00 4890352.74 0.347036E+10 0.788502E+09 0.503267E+09 0.00 0.72



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.200494E+10 0.00 0.00 150334.34 0.00 0.415200E+09 77471343.17 0.00 0.50
February 0.105702E+10 0.00 0.00 2479878.63 727834.66 66765337.12 0.475802E+09 0.00 0.49
March 0.345482E+09 0.124715E+09 0.00 6557308.70 35637137.77 0.00 0.656006E+09 0.00 0.57
April 35542943.26 0.123019E+10 0.00 3685320.66 0.336438E+09 0.00 0.107926E+09 0.00 0.79
May 519024.54 0.460013E+10 0.00 79030.69 0.936856E+09 0.00 2206329.01 0.00 0.91
June 0.00 0.648844E+10 0.00 0.00 0.174912E+10 0.00 0.00 0.00 0.85
July 0.00 0.806989E+10 0.00 0.00 0.258246E+10 0.00 0.00 0.00 0.79
August 0.00 0.784138E+10 0.00 0.00 0.213251E+10 0.00 0.00 0.00 0.72
September 0.00 0.509977E+10 0.00 0.00 0.157482E+10 0.00 0.00 0.00 0.66
October 0.151541E+09 0.896415E+09 0.00 2434564.55 0.209009E+09 0.00 0.124655E+09 0.00 0.59
November 0.723682E+09 7299360.38 0.00 4230202.50 11783916.41 0.00 0.458334E+09 0.00 0.48
December 0.185210E+10 0.00 0.00 238095.76 6401.90 0.175561E+09 0.124408E+09 0.00 0.48
                   
Annual Sum or Average 0.617083E+10 0.343582E+11 0.00 19854735.82 0.956937E+10 0.657526E+09 0.202681E+10 0.00 0.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.48
Maximum of Months 0.200494E+10 0.806989E+10 0.00 6557308.70 0.258246E+10 0.415200E+09 0.656006E+09 0.00 0.91



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.176195E+10 0.00 0.00 6590715.49 0.00 0.350470E+09 0.181608E+10 0.00 0.52
February 0.110467E+10 540443.06 0.00 9564071.48 436263.32 41283274.49 0.148483E+10 0.00 0.53
March 0.411289E+09 0.260823E+09 0.00 12317850.31 21584150.09 0.00 0.114609E+10 0.00 0.59
April 48220438.72 0.172114E+10 0.00 4692423.22 0.427331E+09 0.00 0.136152E+09 0.00 0.68
May 654139.65 0.569630E+10 0.00 118441.37 0.130398E+10 0.00 3076655.56 0.00 0.73
June 0.00 0.838707E+10 0.00 0.00 0.234776E+10 0.00 0.00 0.00 0.71
July 0.00 0.110298E+11 0.00 0.00 0.344948E+10 0.00 0.00 0.00 0.69
August 0.00 0.115172E+11 0.00 0.00 0.270306E+10 0.00 0.00 0.00 0.66
September 0.00 0.830667E+10 0.00 0.00 0.172174E+10 0.00 0.00 0.00 0.64
October 0.139734E+09 0.189349E+10 0.00 7648784.24 0.153030E+09 0.00 0.278440E+09 0.00 0.69
November 0.567053E+09 33873314.76 0.00 18308304.88 8791890.04 0.00 0.166940E+10 0.00 0.64
December 0.156566E+10 5275.34 0.00 8090655.93 4157.25 97347157.29 0.183625E+10 0.00 0.52
                   
Annual Sum or Average 0.559924E+10 0.488469E+11 0.00 67331246.92 0.121372E+11 0.489101E+09 0.837031E+10 0.00 0.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.52
Maximum of Months 0.176195E+10 0.115172E+11 0.00 18308304.88 0.344948E+10 0.350470E+09 0.183625E+10 0.00 0.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.209001E+10 0.00 0.00 800277.95 0.00 0.439425E+09 0.286569E+09 0.00 0.56
February 0.137272E+10 0.00 0.00 2285772.37 820014.30 46198656.98 0.382998E+09 0.00 0.55
March 0.457539E+09 0.167355E+09 0.00 6121923.94 28145930.75 0.00 0.614746E+09 0.00 0.62
April 37747010.55 0.140037E+10 0.00 3543786.63 0.325709E+09 0.00 0.100799E+09 0.00 0.84
May 514119.27 0.492269E+10 0.00 105168.06 0.955483E+09 0.00 2466227.60 0.00 0.95
June 0.00 0.734402E+10 0.00 0.00 0.171224E+10 0.00 0.00 0.00 0.94
July 0.00 0.873110E+10 0.00 0.00 0.278031E+10 0.00 0.00 0.00 0.85
August 0.00 0.876424E+10 0.00 0.00 0.224213E+10 0.00 0.00 0.00 0.79
September 0.00 0.554039E+10 0.00 0.00 0.171939E+10 0.00 0.00 0.00 0.71
October 0.186108E+09 0.996257E+09 0.00 2150864.84 0.218085E+09 0.00 94856892.29 0.00 0.64
November 0.934490E+09 11189420.17 0.00 4163006.93 13181578.52 0.00 0.394738E+09 0.00 0.55
December 0.205312E+10 0.00 0.00 1072862.03 7212.70 0.100380E+09 0.280255E+09 0.00 0.54
                   
Annual Sum or Average 0.713224E+10 0.378776E+11 0.00 20243662.76 0.999550E+10 0.586004E+09 0.215743E+10 0.00 0.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.54
Maximum of Months 0.209001E+10 0.876424E+10 0.00 6121923.94 0.278031E+10 0.439425E+09 0.614746E+09 0.00 0.95



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 8654138.35 0.00 0.00 0.623222E+09 0.00 0.58
February 0.00 5571301.20 0.00 18067452.19 0.00 0.00 0.307573E+09 0.00 0.59
March 0.00 0.106276E+09 0.00 19626366.74 0.00 0.00 0.106832E+09 0.00 0.59
April 0.00 0.323166E+09 0.00 9086480.20 0.00 0.00 8942789.34 0.00 0.59
May 0.00 0.840680E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.59
June 0.00 0.127956E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
July 0.00 0.174888E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.60
August 0.00 0.171928E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.60
September 0.00 0.124890E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
October 0.00 0.404048E+09 0.00 2219262.78 0.00 0.00 5839348.59 0.00 0.59
November 0.00 37191948.77 0.00 26484438.20 0.00 0.00 0.163138E+09 0.00 0.59
December 0.00 4599.62 0.00 46138839.67 0.00 0.00 0.502317E+09 0.00 0.58
                   
Annual Sum or Average 0.00 0.771357E+10 0.00 0.130277E+09 0.00 0.00 0.171786E+10 0.00 0.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.58
Maximum of Months 0.00 0.174888E+10 0.00 46138839.67 0.00 0.00 0.623222E+09 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 60765976.05 0.00 0.00 0.634309E+10 0.00 0.58
February 0.00 53132929.88 0.00 0.159618E+09 0.00 0.00 0.311668E+10 0.00 0.59
March 0.00 0.105924E+10 0.00 0.185134E+09 0.00 0.00 0.108017E+10 0.00 0.59
April 0.00 0.325654E+10 0.00 87817332.28 0.00 0.00 91257827.14 0.00 0.59
May 0.00 0.834591E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
June 0.00 0.127519E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.59
July 0.00 0.174510E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.60
August 0.00 0.173244E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.59
September 0.00 0.123487E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.59
October 0.00 0.401234E+10 0.00 20968437.19 0.00 0.00 62012636.72 0.00 0.59
November 0.00 0.369014E+09 0.00 0.244604E+09 0.00 0.00 0.165634E+10 0.00 0.59
December 0.00 36387.21 0.00 0.418980E+09 0.00 0.00 0.506321E+10 0.00 0.58
                   
Annual Sum or Average 0.00 0.769723E+11 0.00 0.117789E+10 0.00 0.00 0.174128E+11 0.00 0.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.58
Maximum of Months 0.00 0.174510E+11 0.00 0.418980E+09 0.00 0.00 0.634309E+10 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.125770E+09 0.00 0.00 2956206.50 0.00 0.00 0.517453E+09 0.00 0.58
February 0.00 6411699.49 0.00 14112916.01 0.00 0.00 0.301920E+09 0.00 0.59
March 0.00 0.114766E+09 0.00 17204437.23 0.00 0.00 99943182.08 0.00 0.59
April 0.00 0.345201E+09 0.00 7790812.56 0.00 0.00 7675519.72 0.00 0.59
May 0.00 0.853782E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.59
June 0.00 0.129449E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
July 0.00 0.176536E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.60
August 0.00 0.177071E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
September 0.00 0.125325E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
October 0.00 0.417533E+09 0.00 1803225.79 0.00 0.00 5185530.55 0.00 0.59
November 0.00 41936525.12 0.00 22458367.38 0.00 0.00 0.155443E+09 0.00 0.59
December 0.00 33346.54 0.00 38810433.98 0.00 0.00 0.493602E+09 0.00 0.58
                   
Annual Sum or Average 0.125770E+09 0.786348E+10 0.00 0.105136E+09 0.00 0.00 0.158122E+10 0.00 0.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.58
Maximum of Months 0.125770E+09 0.177071E+10 0.00 38810433.98 0.00 0.00 0.517453E+09 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.518074E+09 0.00 0.00 0.139754E+11 0.00 0.66
February 0.00 0.161721E+09 0.00 0.909772E+09 0.00 0.00 0.671620E+10 0.00 0.66
March 0.00 0.246917E+10 0.00 0.879791E+09 0.00 0.00 0.202313E+10 0.00 0.66
April 0.00 0.467584E+10 0.00 0.630141E+09 0.00 0.00 0.361787E+09 0.00 0.67
May 0.00 0.197030E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.67
June 0.00 0.289782E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.67
July 0.00 0.390304E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.67
August 0.00 0.330377E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.68
September 0.00 0.299069E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.67
October 0.00 0.949115E+10 0.00 90104904.49 0.00 0.00 87005648.59 0.00 0.66
November 0.00 0.891780E+09 0.00 0.123634E+10 0.00 0.00 0.325384E+10 0.00 0.66
December 0.00 0.00 0.00 0.224999E+10 0.00 0.00 0.110048E+11 0.00 0.66
                   
Annual Sum or Average 0.00 0.168346E+12 0.00 0.651421E+10 0.00 0.00 0.374221E+11 0.00 0.66
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.66
Maximum of Months 0.00 0.390304E+11 0.00 0.224999E+10 0.00 0.00 0.139754E+11 0.00 0.68



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:03:25

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.290801E+12 0.297082E+10 0.00 0.841500E+12 0.124387E+13
February 0.336479E+12 0.346056E+10 0.00 0.545281E+12 0.176774E+13
March 0.456868E+12 0.203902E+10 0.00 0.251530E+12 0.298370E+13
April 0.496319E+12 -0.161950E+10 0.00 -0.267228E+12 0.400853E+13
May 0.540680E+12 -0.736528E+10 0.00 -0.912278E+12 0.379056E+13
June 0.504740E+12 -0.833458E+10 0.00 -0.142033E+13 0.461809E+13
July 0.410556E+12 -0.177739E+11 0.00 -0.195028E+13 0.555892E+13
August 0.343882E+12 -0.124289E+11 0.00 -0.195881E+13 0.592804E+13
September 0.371757E+12 -0.716932E+10 0.00 -0.142695E+13 0.364143E+13
October 0.354566E+12 -653284901.4 0.00 -0.154198E+12 0.301859E+13
November 0.307619E+12 0.856992E+09 0.00 0.436688E+12 0.266316E+13
December 0.266531E+12 0.295404E+10 0.00 0.782655E+12 0.259671E+13
           
Annual Sum or Average 0.468080E+13 -0.430633E+11 0.00 -0.523243E+13 0.418193E+14
Minimum of Months 0.266531E+12 -0.177739E+11 0.00 -0.195881E+13 0.124387E+13