Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 09:03:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 33686.75 | 727.26 | 727.26 |
Net Site Energy | 33686.75 | 727.26 | 727.26 |
Total Source Energy | 98001.72 | 2115.74 | 2115.74 |
Net Source Energy | 98001.72 | 2115.74 | 2115.74 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3397.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3205.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3711.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 671.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1941.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2703.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 416.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3188.49 |
Humidification | 840.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.78 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 771.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 29517.66 | 4169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5781.45 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3397.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3205.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3711.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 671.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2703.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 416.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3188.49 |
Humidification | General | 840.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.78 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 771.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3397.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3205.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3711.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 671.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1941.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2703.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 416.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3188.49 |
Humidification | Unassigned | 840.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.78 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 771.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 172.28 | 90.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 370.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 637.25 | 90.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 172.28 | 90.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 370.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 637.25 | 90.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 29517.660 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 29517.660 | 100.00 |
Total On-Site and Utility Electric Sources | 29517.660 | 100.00 |
Total Electricity End Uses | 29517.660 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5781.45 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5781.45 | 100.00 |
Total Water End Uses | 5781.45 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 115.33 |
Time Setpoint Not Met During Occupied Cooling | 480.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5942.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.3279 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.3279 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.3279 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.3279 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 9.3279 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.3279 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 9.3279 | 18.58 | 484.4232 | |
Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.8860 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-15:39 | 09-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 25-JUL-11:50 |
Heating | 0.00 | 2285209.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 426109.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84885.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 301770.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 55015.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 81829.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 16223.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27391.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2076655.13 | 2312600.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2285209.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 426109.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5451.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 301770.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 55015.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 81829.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 16223.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 27391.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3682.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10152.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11753.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2125.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6150.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8562.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1320.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2574.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 2662.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 836.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 93482.43 | 4519.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 79.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 219.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 253.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 184.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 55.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 57.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2018.17 | 97.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 79.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 219.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 253.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 184.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 55.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 57.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2018.17 | 97.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.47 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.570008 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.46 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.555614 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.47 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.79 | 0.279943 | 0.300000 | 2.04 | 0.746515 | 0.500000 | 0.001361 | 0.000238 | 2.04 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 63.87 | 0.297787 | 0.307000 | 19.61 | 0.794099 | 0.500000 | 0.001279 | 0.004597 | 19.61 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.18 | 0.307671 | 0.326000 | 2.02 | 0.820455 | 0.500000 | 0.001238 | 0.001001 | 3.90 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.08 | 0.220653 | 0.300000 | 0.324701 | 0.588407 | 0.500000 | 0.001727 | 0.000175 | 0.682446 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.34 | 0.114754 | 0.300000 | 0.402354 | 0.306009 | 0.500000 | 0.003320 | 0.000120 | 0.468499 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.70 | 0.140701 | 0.300000 | 0.509219 | 0.375203 | 0.500000 | 0.002708 | 0.000192 | 0.750352 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.67 | 0.092014 | 0.300000 | 0.501787 | 0.300000 | 0.500000 | 0.004141 | 0.000109 | 0.501787 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.19 | 0.234469 | 0.300000 | 3.06 | 0.625250 | 0.500000 | 0.001625 | 0.002504 | 9.77 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 14.10 | 0.109118 | 0.300000 | 4.23 | 0.300000 | 0.500000 | 0.003492 | 0.001661 | 6.48 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 17.07 | 0.139909 | 0.300000 | 5.12 | 0.373090 | 0.500000 | 0.002723 | 0.002534 | 9.89 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 15.16 | 0.101491 | 0.300000 | 4.55 | 0.300000 | 0.500000 | 0.003754 | 0.001628 | 6.35 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.29 | 0.185614 | 0.300000 | 0.385995 | 0.494972 | 0.500000 | 0.002053 | 0.000330 | 1.29 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.41 | 0.108849 | 0.300000 | 0.424179 | 0.300000 | 0.500000 | 0.003500 | 0.000218 | 0.848943 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.84 | 0.129706 | 0.300000 | 0.552386 | 0.345882 | 0.500000 | 0.002937 | 0.000333 | 1.30 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.61 | 0.095365 | 0.300000 | 0.484156 | 0.300000 | 0.500000 | 0.003995 | 0.000217 | 0.846961 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 27176.71 | 0.000238 | 577.10 |
CORE_MID VAV BOX REHEAT COIL | 525448.40 | 0.004597 | 13336.12 |
CORE_TOP VAV BOX REHEAT COIL | 114474.95 | 0.001001 | 3020.42 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 20010.40 | 0.000175 | 527.73 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 13735.44 | 0.000120 | 362.22 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 21997.98 | 0.000192 | 580.11 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 12407.03 | 0.000109 | 305.53 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 286203.60 | 0.002504 | 7545.67 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 189849.57 | 0.001661 | 5005.23 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 289677.87 | 0.002534 | 7637.22 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 186046.86 | 0.001628 | 4905.02 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 37689.39 | 0.000330 | 993.53 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 24867.16 | 0.000218 | 655.51 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 38120.11 | 0.000333 | 1004.88 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 24809.04 | 0.000217 | 653.98 |
VAV_BOT WITH REHEAT HEATING COIL | 99832.45 | 0.000873 | 1534.40 |
VAV_MID WITH REHEAT HEATING COIL | 1054592.05 | 0.009226 | 15670.25 |
VAV_TOP WITH REHEAT HEATING COIL | 103926.02 | 0.000909 | 1594.65 |
CAV_BAS HEATING COIL | 309103.33 | 0.002704 | 6611.30 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.29 | 3.78 | 12.59 | 3.78 | 10.93 | 10.93 | 0.300000 | 0.345557 | 10.93 |
VAV_MID WITH REHEAT | 60.20 | 36.57 | 120.40 | 49.56 | 101.25 | 101.25 | 0.300000 | 0.489528 | 101.25 |
VAV_TOP WITH REHEAT | 6.17 | 3.86 | 12.34 | 8.18 | 11.30 | 11.30 | 0.300000 | 0.724143 | 11.30 |
CAV_BAS | 6.47 | 6.47 | 6.47 | 6.47 | 6.47 | 6.47 | 1.00 | 1.00 | 6.47 |
AIRLOOP DATACENTER BASEMENT | 24.47 | 24.47 | 24.47 | 24.47 | 24.47 | 24.47 | 1.00 | 0.999991 | 24.47 |
AIRLOOP DATACENTER BOT | 0.570008 | 0.570008 | 0.570008 | 0.570008 | 0.570008 | 0.570008 | 1.00 | 1.00 | 0.570008 |
AIRLOOP DATACENTER MID | 5.46 | 5.46 | 5.46 | 5.46 | 5.46 | 5.46 | 1.00 | 1.00 | 5.46 |
AIRLOOP DATACENTER TOP | 0.555614 | 0.555614 | 0.555614 | 0.555614 | 0.555614 | 0.555614 | 1.00 | 1.00 | 0.555614 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.93 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 101.25 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.30 | |
CAV_BAS_OA_CONTROLLER | 6.47 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.47 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.570008 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.46 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.555614 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.19 | 6.67 | 10.68 | 0.007088 | 0.007000 | 184210.74 | 0.007837 | 10.93 |
VAV_MID WITH REHEAT COOLING COIL | 26.44 | 6.67 | 10.68 | 0.007076 | 0.007000 | 1730478.66 | 0.073619 | 101.25 |
VAV_TOP WITH REHEAT COOLING COIL | 26.12 | 6.67 | 10.68 | 0.007074 | 0.007000 | 189241.84 | 0.008051 | 11.30 |
CAV_BAS COOLING COIL | 25.80 | 6.67 | 11.22 | 0.007242 | 0.007000 | 105376.19 | 0.004483 | 6.47 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.93 |
VAV_MID WITH REHEAT FAN | 101.25 |
VAV_TOP WITH REHEAT FAN | 11.30 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007837 | 0.000061 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000873 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.073619 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.009226 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.008051 | 0.000059 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000909 | |
CAV_BAS_COOLC_CONTROLLER | 0.004483 | 0.000106 |
CAV_BAS_HEATC_CONTROLLER | 0.002704 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.47 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.47 | 465166.58 | 261784.15 | 0.011392 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.570008 | 10529.65 | 5988.34 | 0.000258 |
AIRLOOP DATACENTER MID COOLING COIL | 5.46 | 100857.57 | 57346.94 | 0.002470 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.555614 | 10265.81 | 5837.55 | 0.000251 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.47 | 24.47 | 24.47 | 24.47 | 465166.58 | 465166.58 | 24207.99 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.570008 | 0.570008 | 0.570008 | 0.570008 | 10529.65 | 10529.65 | 1118.31 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.46 | 5.46 | 5.46 | 5.46 | 100857.57 | 100857.57 | 11183.09 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.555614 | 0.555614 | 0.555614 | 0.555614 | 10265.81 | 10265.81 | 1118.31 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.47 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.570008 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.46 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.555614 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.47 | 465166.58 | 0.011392 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.570008 | 10529.65 | 0.000258 |
AIRLOOP DATACENTER MID HEATING COIL | 5.46 | 100857.57 | 0.002470 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.555614 | 10265.81 | 0.000251 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 24207.99 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1118.31 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 11183.09 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1118.31 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000191 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.093989 | 19367.66 | |
HEATSYS1 PUMP | 0.029569 | 8905.02 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.093989 | 11.28 |
HEATSYS1 | 0.029569 | 3.55 |
COOLSYS1_SUPPLY | 0.093989 | 11.28 |
SINGLE WATER PLANT LOOP | 0.014371 | 1.72 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.093989 | 0.093989 | 394519.18 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3379968.34 | 3379968.34 | 0.029569 |
CENTRAL BOILER | 591969.18 | 579237.53 | 0.014371 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.093989 | 13408.88 |
PLANT CIRC PUMP | 0.014371 | 3665.37 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.093989 | 0.047347 | 1115664.70 | 1120956.40 | 0.055472 |
COOLSYS1 CHILLER2 | 0.093989 | 0.047347 | 1115664.70 | 1120956.40 | 0.055472 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014371 | 139666.47 | 55634.27 | 69833.23 | 7879.72 | 21031.62 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.110944 | 13.31 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.110944 | 33413.90 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 49.02 | 1331643.43 | 9.80 | 166455.43 |
TOWERWATERSYS COOLTOWER 2 | 49.02 | 1331643.43 | 9.80 | 166455.43 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.057618 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.328 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 14.170 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 9.328 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.751 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 25926.330 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25926.330 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 7310.116 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7310.116 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.147 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.072 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.485 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7043 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7653 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5060 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.18777991E-14 | 0.39318316E-16 | -0.13945218E-09 | -0.53504997E-17 |
51 | 8 | 0.20428582E-07 | 0.15263370E-12 | 0.36243033E-03 | -0.23227999E-09 |
52 | 7 | -0.11782580E-01 | 0.80534805E-08 | -0.22424787E-01 | 0.13397222E-03 |
53 | 6 | 0.39287835 | 0.28244099E-05 | 0.46145507 | -0.46007477E-02 |
54 | 5 | -5.0688419 | 0.10619431E-03 | -4.3595097 | 0.61674563E-01 |
55 | 4 | 32.464389 | 0.87416084E-03 | 21.120657 | -0.41497362 |
56 | 3 | -110.08041 | 0.19158287E-02 | -54.991947 | 1.4986409 |
57 | 2 | 195.99541 | 0.10830235E-02 | 77.295382 | -2.8826816 |
58 | 1 | -170.74495 | 0.11614893E-03 | -55.086664 | 2.7382339 |
59 | 0 | 57.057407 | 0.66454694E-06 | 15.586789 | |
60 | 9 | -0.35772101E-15 | 0.35300796E-16 | -0.14299885E-09 | 0.43432634E-17 |
61 | 8 | 0.20929462E-07 | 0.14329262E-12 | 0.36779278E-03 | -0.23797519E-09 |
62 | 7 | -0.11942934E-01 | 0.75175974E-08 | -0.22655780E-01 | 0.13579551E-03 |
63 | 6 | 0.39723595 | 0.26304111E-05 | 0.46517473 | -0.46521131E-02 |
64 | 5 | -5.1113728 | 0.98704798E-04 | -4.3881162 | 0.62201922E-01 |
65 | 4 | 32.652551 | 0.81106559E-03 | 21.232557 | -0.41747184 |
66 | 3 | -110.48086 | 0.17747443E-02 | -55.213214 | 1.5044261 |
67 | 2 | 196.39242 | 0.10018625E-02 | 77.498162 | -2.8889858 |
68 | 1 | -170.89164 | 0.10730575E-03 | -55.145342 | 2.7408049 |
69 | 0 | 57.057407 | 0.61309336E-06 | 15.576862 | |
70 | 9 | 0.62620750E-15 | 0.53459335E-16 | -0.12331227E-09 | -0.46720721E-17 |
71 | 8 | 0.18149323E-07 | 0.19273772E-12 | 0.33743729E-03 | -0.20636407E-09 |
72 | 7 | -0.11033179E-01 | 0.10459398E-07 | -0.21344557E-01 | 0.12545125E-03 |
73 | 6 | 0.37251059 | 0.37098382E-05 | 0.44401761 | -0.43606628E-02 |
74 | 5 | -4.8700128 | 0.14084247E-03 | -4.2251796 | 0.59209231E-01 |
75 | 4 | 31.584523 | 0.11694623E-02 | 20.594689 | -0.40329204 |
76 | 3 | -108.20727 | 0.25827026E-02 | -53.951706 | 1.4715810 |
77 | 2 | 194.13760 | 0.14699268E-02 | 76.342983 | -2.8531817 |
78 | 1 | -170.05820 | 0.15862972E-03 | -54.812808 | 2.7261979 |
79 | 0 | 57.057407 | 0.91374417E-06 | 15.634538 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4803E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4823E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1356E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.1372E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5287E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5299E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9650E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9658E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5256E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.6567E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1737E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.2878E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5607E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6550E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9845E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0341E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1338 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1635E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1537 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.5149E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.5460E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1244E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1298E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4495E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5360E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7125E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1852E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3502E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5692E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6882E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9850E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0355E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4802E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4826E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1354E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.1375E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5286E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5302E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9650E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9657E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9356E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3574E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8593E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3554E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2341E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3671E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3625E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3966E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9134E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0176E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8337E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8818E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8114E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4776E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2472E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5878E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8013E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9010E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6817E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7553E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1933E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2235E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3626E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3972E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1610E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1631E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8300E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8318E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6002E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6015E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9651E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9658E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2071E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3238E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8688E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9639E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6326E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7051E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9850E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0356E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5928E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0905E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7862E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5915E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7858E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1027E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1298E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4491E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2047E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3243E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8651E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9584E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6259E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6839E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9846E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0341E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1609E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1629E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8299E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8315E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6000E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6011E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9650E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9657E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0671E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1729E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7366E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8133E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6833E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7100E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3627E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3972E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.5138E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4180E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0462E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1137E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7632E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0352E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2472E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5878E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1557E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4083E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8546E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1297E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7200E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8324E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3624E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3966E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1307 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1040 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1464 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1201 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1017 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.6289E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.7714E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.3115E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.7452E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1233E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6590E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.9809E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.5532E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4116E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8823E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3360E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2473E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0013E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3722E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3702E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3677E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8123E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7714E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3111E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2277E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3362E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.7188E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9703E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.4291E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.8571E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8823E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3360E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1305 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1041 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1462 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1202 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1017 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.6394E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.7768E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.3160E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.7405E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1270E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6553E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.9849E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.5544E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4174E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8875E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3404E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2416E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0024E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3682E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3712E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3694E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8151E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7768E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3156E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2232E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3386E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.7155E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9726E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.4304E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.8618E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8875E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3404E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 78387.80853 | 78387.80853 | 6.47407 | 6.47407 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 82273.91105 | 82273.91105 | 6.79439 | 6.79439 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 9227.34779 | 9227.34779 | 0.44638 | 1.07782 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 773613.85370 | 773613.85370 | 63.87256 | 63.87256 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 352773.19363 | 352773.19363 | 17.08187 | 17.08187 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 74880.97514 | 74880.97514 | 6.18208 | 6.18208 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 80130.06328 | 80130.06328 | 3.90018 | 3.90018 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12992.98707 | 12992.98707 | 1.08234 | 1.08234 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 14004.02258 | 14004.02258 | 0.68245 | 0.68245 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 16100.42153 | 16100.42153 | 1.34118 | 1.34118 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.09333 | 6.29258E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 9611.96117 | 9611.96117 | 0.46850 | 0.46850 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 20376.61395 | 20376.61395 | 1.69740 | 1.69740 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.30642E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 15393.54707 | 15393.54707 | 0.75035 | 0.75035 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20079.35392 | 20079.35392 | 1.67262 | 1.67262 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7991.39497 | 7991.39497 | 0.38927 | 0.38927 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 122275.10923 | 122275.10923 | 10.18560 | 10.18560 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 200265.88498 | 200265.88498 | 9.76741 | 9.76741 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 169321.00044 | 169321.00044 | 14.10443 | 14.10443 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.96000 | 6.29539E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 132841.97254 | 132841.97254 | 6.47935 | 6.47935 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 204922.66876 | 204922.66876 | 17.07013 | 17.07013 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 202694.95481 | 202694.95481 | 9.88613 | 9.88613 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 182046.26311 | 182046.26311 | 15.16446 | 15.16446 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 130183.00372 | 130183.00372 | 6.34945 | 6.34945 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13915.48179 | 13915.48179 | 1.15916 | 1.15916 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.30633E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 26368.98672 | 26368.98672 | 1.28665 | 1.28665 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16974.00908 | 16974.00908 | 1.41393 | 1.41393 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.41333 | 6.29608E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 17397.95006 | 17397.95006 | 0.84894 | 0.84894 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 22104.30035 | 22104.30035 | 1.84129 | 1.84129 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.30683E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 26670.13923 | 26670.13923 | 1.30137 | 1.30137 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 19374.05535 | 19374.05535 | 1.61385 | 1.61385 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 17357.27514 | 17357.27514 | 0.84696 | 0.84696 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8675.43569 | 8675.43569 | 0.57001 | 0.57001 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 83069.49152 | 83069.49152 | 5.45800 | 5.45800 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8456.34415 | 8456.34415 | 0.55561 | 0.55561 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 26.57333 | 6.29632E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372452.66094 | 372452.66094 | 24.47120 | 24.47120 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.84000 | 6.28481E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | -27.60000 | 3.41898E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 151923.12 | 10.92837 | 10.92837 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 106253.88 | 3.36839 | 3.36839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1413040.05 | 101.24908 | 101.24908 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1083253.27 | 49.56421 | 49.56421 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 158720.29 | 11.30177 | 11.30177 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 108507.10 | 8.18410 | 8.18410 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:30:00 |
7 | CAV_BAS | Cooling | Sensible | 78972.58 | 6.47407 | 6.47407 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 85856.97 | 1.20016 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 369515.79 | 24.47142 | 24.47142 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 24207.99 | 0.33839 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8553.12 | 0.57001 | 0.57001 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 81892.91 | 5.45800 | 5.45800 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 11183.09 | 0.15632 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8341.36 | 0.55561 | 0.55561 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.47407 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.79439 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27994 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03832 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74652 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36099E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.37754E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.03832 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27176.70936 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.37754E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 577.09924 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 63.87256 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29779 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30700 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.60888 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79410 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27944E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.59685E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.60888 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 525448.40488 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.59685E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 13336.11814 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.18208 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30767 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32600 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.01536 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82045 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.23834E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00148E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.90018 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 114474.94732 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00148E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3020.41839 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.08234 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22065 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32470 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58841 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72670E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.75060E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68245 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20010.39903 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.75060E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 527.73014 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.34118 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11475 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40235 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30601 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.32016E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.20164E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46850 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13735.43802 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20164E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 362.22142 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.69740 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14070 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.50922 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37520 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.70786E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92448E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75035 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21997.97573 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92448E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 580.10556 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.67262 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.20141E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.50179 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.14067E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08542E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50179 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12407.02618 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08542E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 305.53127 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.18560 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23447 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.05568 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62525 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.62495E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.50383E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.76741 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 286203.60007 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.50383E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7545.67122 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.10443 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10912 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.23133 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.49163E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.66089E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.47935 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 189849.56718 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66089E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5005.23300 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.07013 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13991 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.12104 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37309 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.72321E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.53423E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.88613 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 289677.86801 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53423E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7637.21666 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.16446 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10149 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.54934 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.75404E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.62762E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.34945 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 186046.86375 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62762E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4905.01990 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.28665 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18561 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38599 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49497 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.05264E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.29723E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28665 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37689.39131 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.29723E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 993.52682 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.41393 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10885 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42418 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.50025E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.17549E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84894 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24867.16385 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17549E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 655.51333 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.84129 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12971 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55239 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34588 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.93741E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.33491E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.30137 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38120.10621 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.33491E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1004.87616 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.61385 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.53650E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.48416 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.99517E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.17040E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84696 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24809.03901 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17040E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 653.98018 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.57001 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.45800 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.55561 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.47120 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.29396 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.77638 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.58793 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.77638 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.92837 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.92837 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34556 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 60.19859 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 36.56626 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 120.39719 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 49.56421 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 101.24908 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 101.24908 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.48953 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.16890 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.86207 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.33780 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 8.18410 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.30177 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.30177 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.72414 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.47407 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.47407 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.47407 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.47407 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.47407 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.47407 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.47120 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.47120 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.47120 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.47120 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.47142 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.47142 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.57001 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.57001 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.57001 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.57001 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.57001 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.57001 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.45800 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.45800 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.45800 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.45800 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.45800 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.45800 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.55561 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.55561 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.55561 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.55561 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.55561 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.55561 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.92837 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 101.24908 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.30177 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.47407 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.47142 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.57001 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.45800 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.55561 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.92837 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.18508 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68120 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.08825E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 184210.73752 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.83675E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.92837 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 99832.44627 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.73378E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1534.40011 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.92837 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.83675E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.07638E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.73378E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 101.24908 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.43561 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68115 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.07576E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1730478.65595 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.36186E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 101.24908 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1054592.04677 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.22603E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 15670.25308 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 101.24908 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.36186E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.46835E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.22603E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.30177 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.11766 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68114 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.07352E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 189241.84000 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.05079E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.30177 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 103926.01877 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.09190E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1594.65176 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.30177 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.05079E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.91483E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.09190E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.47407 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.79641 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.21885 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.24228E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 105376.18502 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.48295E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.47407 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 309103.32943 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.70417E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6611.29697 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.47407 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.48295E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.06223E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.70417E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.47142 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.47142 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 465166.58148 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 261784.14821 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.13919E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.47142 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.47142 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.47142 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.47142 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 465166.58148 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 465166.58148 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 24207.99248 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.47142 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.47142 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 465166.58148 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.13919E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 24207.99248 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.90553E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.57001 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.57001 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10529.64782 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5988.33615 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.57870E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.57001 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.57001 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.57001 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.57001 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10529.64782 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10529.64782 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.57001 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.57001 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10529.64782 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.57870E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.45800 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.45800 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 100857.56788 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 57346.93932 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47000E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.45800 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.45800 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.45800 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.45800 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 100857.56788 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 100857.56788 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11183.08965 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.45800 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.45800 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 100857.56788 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47000E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11183.08965 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.55561 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55561 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10265.81115 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5837.54806 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.51409E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.55561 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.55561 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.55561 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.55561 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10265.81115 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10265.81115 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.55561 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55561 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10265.81115 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.51409E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.39890E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 19367.65858 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.39890E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 11.27869 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.39890E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.39890E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 394519.18187 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.95694E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.54833 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.95694E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 8905.01604 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3379968.34114 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3379968.34000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.95694E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.39890E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 11.27869 |
451 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 9.39890E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 13408.88335 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.39890E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.73467E-002 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1115664.70348 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1120956.40000 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.54720E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.39890E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.73467E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1115664.70348 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1120956.40000 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.54720E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.43712E-002 |
464 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.72454 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.43712E-002 |
466 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3665.36815 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.43712E-002 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 55634.27402 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21031.61623 |
473 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 591969.18212 |
474 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 579237.53000 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.43712E-002 |
476 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
477 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
479 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
480 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
481 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11094 |
482 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 13.31327 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11094 |
484 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 33413.90480 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 49.02430 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1331643.42517 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.80486 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 166455.42815 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 49.02430 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1331643.42517 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.80486 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 166455.42815 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.76175E-002 |
494 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.76175E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 25765.14 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 497792.72 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 108495.51 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18963.54 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 13016.72 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20846.85 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11755.19 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 271215.01 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 179906.44 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 274506.98 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 176303.19 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 35714.62 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 23564.17 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 36122.74 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23509.09 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 66984.17 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 679761.59 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 69595.74 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 233665.18 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 308458.20 | 189374.49 | 119083.72 | 0.61 | 61181.39 | 620.54 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2868045.49 | 1758557.19 | 1109488.30 | 0.61 | 561573.82 | 5695.79 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 318350.79 | 195588.76 | 122762.03 | 0.61 | 63457.87 | 643.62 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 176197.98 | 109542.43 | 66655.54 | 0.62 | 32123.51 | 325.81 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2735157663 | 0.2049469965 | Pass | Pass | 15.6346840116 | 71.1059399734 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.8838971254E-002 | 0.1315599782 | Pass | Pass | 5.0075414263E-002 | 0.2171181934 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.1576407246E-003 | 4.4733498081E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.9125455290E-002 | 2.2500655220E-002 | Pass | Pass | 0.5117472514 | 0.4950104399 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.6535007458E-002 | 9.5462690874E-002 | Pass | Pass | 4.9485986230E-002 | 0.2154014305 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1005643163 | 0.1925875195 | Pass | Pass | 5.0947688795E-002 | 0.2194513436 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1492119725 | 0.2319705725 | Pass | Pass | 5.0774361966E-002 | 0.2184788125 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.6956029983E-002 | 0.2326829007 | Pass | Pass | 4.9795610908E-002 | 0.2149279415 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.4725048441E-002 | 2.4965462429E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.7735291897E-002 | 7.0257213492E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1259374367 | 0.1206953959 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.9874998841E-002 | 5.3998252048E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3420562075 | 0.3550422560 | Pass | Pass | 5.9485957611 | 16.9753277118 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2345889194 | 0.3306408682 | Pass | Pass | 8.5729839216 | 34.4670213226 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2196254729 | 0.2417741011 | Pass | Pass | 0.7840771080 | 1.1091685840 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1977896593 | 0.2599585075 | Pass | Pass | 5.4754361298 | 27.3850567234 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.3678268075E-002 | 2.1381896761E-002 | Pass | Pass | 7.2489767127 | 76.5823880480 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.0701941294E-002 | 1.2456517783E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1091216160 | 8.4485632501E-002 | Pass | Pass | 0.5125480752 | 0.4805148290 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.5751914354E-006 | 4.4876915815E-006 | Pass | Pass | 4.1383857214E-003 | 4.0260454370E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.3248388476E-003 | 5.0817095637E-003 | Pass | Pass | 0.1266417630 | 0.5911756408 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.5303422289E-002 | 1.9830125643E-002 | Pass | Pass | 4.4604567185E-003 | 4.3632711518E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.2374463879E-005 | 7.9493992305E-005 | Pass | Pass | 4.5157799499E-005 | 1.0582862621E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7021.03 | 305.28 | 0.00 | 21315.02 | 19633.47 | 48274.79 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3622_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3622_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3622_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3622_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.058 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 1043.06 | 2.058 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.058 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.3279 | 2779.43 | 25926.33 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 240.45 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.3279 | 24961.20 | 232836.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 2159.39 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.32 | 0.0000 | Y | 18.83 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.13 | 0.0000 | Y | 12.07 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.98 | 0.0000 | Y | 18.65 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.18 | 0.0000 | Y | 12.09 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.3279 | 3134.13 | 29234.97 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.35 | 0.0000 | Y | 188.52 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.14 | 0.0000 | Y | 120.74 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.3279 | 3134.20 | 29235.61 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.00 | 0.0000 | Y | 186.58 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.20 | 0.0000 | Y | 120.94 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.35 | 0.0000 | Y | 18.85 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.14 | 0.0000 | Y | 12.07 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.00 | 0.0000 | Y | 18.66 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.20 | 0.0000 | Y | 12.09 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 9.3279 | 783.68 | 7310.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 67.80 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 16.0861 | 362.03 | 5823.61 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 59.65 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
Interior Lighting Total | 9.3913 | 46320.38 | 435009.77 | 1158.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.01 | AstronomicalClock | - | 42.11 | 42.11 | 78.82 | |
EXTERIOR_LIGHTS_B | 44362.79 | AstronomicalClock | - | 83.57 | 71.13 | 592.33 | |
Exterior Lighting Total | 54335.80 | 671.16 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2204226.66 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3379968.34 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1120956.40 | 6.28 | 1072902.17 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1120956.40 | 6.28 | 1072902.17 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 579237.53 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1331643.43 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1331643.43 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 184210.74 | 308458.20 | 189374.49 | 119083.72 | 0.61 | - | 61181.39 | 620.54 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1730478.66 | 2868045.49 | 1758557.19 | 1109488.30 | 0.61 | - | 561573.82 | 5695.79 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 189241.84 | 318350.79 | 195588.76 | 122762.03 | 0.61 | - | 63457.87 | 643.62 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 105376.19 | 176197.98 | 109542.43 | 66655.54 | 0.62 | - | 32123.51 | 325.81 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 465166.58 | 261784.15 | 203382.43 | 0.56 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10529.65 | 5988.34 | 4541.31 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 100857.57 | 57346.94 | 43510.63 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10265.81 | 5837.55 | 4428.26 | 0.57 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 27176.71 | 25765.14 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 525448.40 | 497792.72 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 114474.95 | 108495.51 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 20010.40 | 18963.54 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13735.44 | 13016.72 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21997.98 | 20846.85 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12407.03 | 11755.19 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 286203.60 | 271215.01 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 189849.57 | 179906.44 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 289677.87 | 274506.98 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 186046.86 | 176303.19 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 37689.39 | 35714.62 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 24867.16 | 23564.17 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 38120.11 | 36122.74 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 24809.04 | 23509.09 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 99832.45 | 66984.17 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1054592.05 | 679761.59 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 103926.02 | 69595.74 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 309103.33 | 233665.18 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 465166.58 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10529.65 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 100857.57 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10265.81 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 24207.99 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 11183.09 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.93 | 24824.81 | 2271.59 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 101.25 | 229996.72 | 2271.59 | 1.00 | 1.08 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 11.30 | 25673.03 | 2271.59 | 1.00 | 1.11 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.47 | 10977.79 | 1695.65 | 1.00 | 1.15 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.47 | 40359.42 | 1649.25 | 1.00 | 1.14 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.57 | 638.47 | 1120.11 | 1.00 | 1.55 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.46 | 6113.55 | 1120.11 | 1.00 | 1.15 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.56 | 622.35 | 1120.11 | 1.00 | 1.56 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.093989 | 19367.66 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.029569 | 8905.02 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.093989 | 13408.88 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014371 | 3665.37 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.110944 | 33413.90 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 78387.81 | 78387.81 | 28.20 | 6.474 | 6.474 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00744 | 21.56 | 0.00629 | 1.200 | 0.00 |
CORE_BOTTOM | 82273.91 | 82273.91 | 32.96 | 6.794 | 6.794 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00738 | 21.56 | 0.00629 | 1.078 | 0.00 |
CORE_MID | 773613.85 | 773613.85 | 309.93 | 63.873 | 63.873 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 21.56 | 0.00629 | 10.778 | 0.00 |
CORE_TOP | 74880.98 | 74880.98 | 30.00 | 6.182 | 6.182 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00742 | 21.56 | 0.00629 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12992.99 | 12992.99 | 41.46 | 1.082 | 1.082 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00727 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 16100.42 | 16100.42 | 79.71 | 1.341 | 1.341 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00714 | 24.09 | 0.00629 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 20376.61 | 20376.61 | 65.01 | 1.697 | 1.697 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00717 | 33.13 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20079.35 | 20079.35 | 99.41 | 1.673 | 1.673 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00711 | 30.36 | 0.00630 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 122275.11 | 122275.11 | 390.14 | 10.186 | 10.186 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00725 | 33.40 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 169321.00 | 169321.00 | 838.33 | 14.104 | 14.104 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00712 | 25.96 | 0.00630 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 204922.67 | 204922.67 | 653.83 | 17.070 | 17.070 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00715 | 33.27 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 182046.26 | 182046.26 | 901.33 | 15.164 | 15.164 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00711 | 30.36 | 0.00630 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13915.48 | 13915.48 | 44.40 | 1.159 | 1.159 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00721 | 33.08 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16974.01 | 16974.01 | 84.04 | 1.414 | 1.414 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00711 | 26.41 | 0.00630 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 22104.30 | 22104.30 | 70.53 | 1.841 | 1.841 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00714 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 19374.06 | 19374.06 | 95.92 | 1.614 | 1.614 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00710 | 30.36 | 0.00630 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8675.44 | 8675.44 | 239.63 | 0.570 | 0.570 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00708 | 26.28 | 0.00630 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 83069.49 | 83069.49 | 2294.56 | 5.458 | 5.458 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00709 | 26.28 | 0.00630 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8456.34 | 8456.34 | 233.58 | 0.556 | 0.556 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00709 | 26.57 | 0.00630 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372452.66 | 372452.66 | 475.26 | 24.471 | 24.471 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 18.84 | 0.00628 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.70 | 0.00034 | -27.60 | 0.00034 | 1.200 | 0.00 |
CORE_BOTTOM | 9227.35 | 9227.35 | 3.70 | 0.446 | 1.078 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
CORE_MID | 352773.19 | 352773.19 | 141.33 | 17.082 | 17.082 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 10.778 | 0.00 |
CORE_TOP | 80130.06 | 80130.06 | 32.10 | 3.900 | 3.900 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14004.02 | 14004.02 | 44.68 | 0.682 | 0.682 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 9611.96 | 9611.96 | 47.59 | 0.468 | 0.468 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15393.55 | 15393.55 | 49.11 | 0.750 | 0.750 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7991.39 | 7991.39 | 39.57 | 0.389 | 0.389 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 200265.88 | 200265.88 | 638.98 | 9.767 | 9.767 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 132841.97 | 132841.97 | 657.71 | 6.479 | 6.479 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 202694.95 | 202694.95 | 646.72 | 9.886 | 9.886 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 130183.00 | 130183.00 | 644.55 | 6.349 | 6.349 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 26368.99 | 26368.99 | 84.13 | 1.287 | 1.287 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 17397.95 | 17397.95 | 86.14 | 0.849 | 0.849 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 26670.14 | 26670.14 | 85.09 | 1.301 | 1.301 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17357.28 | 17357.28 | 85.94 | 0.847 | 0.847 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -27.60 | 0.00034 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.21 | 0.00098 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.23 | 0.00098 | -27.60 | 0.00034 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 19.68 | 0.00098 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | 18.00 | 27.00 | 0.00700 | -27.60 | 0.00034 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.93 | 10.93 | 3.37 | 3.37 | 10.9284 | 3.7764 | 10.9284 | 0.3456 | 0.3000 |
VAV_MID WITH REHEAT | 101.25 | 101.25 | 49.56 | 49.56 | 101.2491 | 49.5642 | 101.2491 | 0.4895 | 0.3000 |
VAV_TOP WITH REHEAT | 11.30 | 11.30 | 8.18 | 8.18 | 11.3018 | 8.1841 | 11.3018 | 0.7241 | 0.3000 |
CAV_BAS | 6.47 | 6.47 | 1.20 | 1.20 | 6.4741 | 6.4741 | 6.4741 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.47 | 24.47 | 0.34 | 0.34 | 24.4714 | 24.4712 | 24.4714 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.57 | 0.57 | 0.02 | 0.02 | 0.5700 | 0.5700 | 0.5700 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.46 | 5.46 | 0.16 | 0.16 | 5.4580 | 5.4580 | 5.4580 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.56 | 0.56 | 0.02 | 0.02 | 0.5556 | 0.5556 | 0.5556 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 27176.709 | 27176.709 | 2.038317 | 0.00023775 | 577.099 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27176.71 | 27176.71 | 2.038317 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00799999 | 45.2309 | 9227.35 | 0.00 | 27272.54 | 27272.54 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 525448.405 | 525448.405 | 19.608877 | 0.00459685 | 13336.118 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 525448.40 | 525448.40 | 19.608877 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 352773.19 | 0.00 | 527073.53 | 527073.53 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 114474.947 | 114474.947 | 3.900181 | 0.00100148 | 3020.418 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 114474.95 | 114474.95 | 3.900181 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 80130.06 | 0.00 | 114860.69 | 114860.69 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 20010.399 | 20010.399 | 0.682446 | 0.00017506 | 527.730 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20010.40 | 20010.40 | 0.682446 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00777257 | 43.9637 | 14004.02 | 0.00 | 20076.07 | 20076.07 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 13735.438 | 13735.438 | 0.468499 | 0.00012016 | 362.221 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13735.44 | 13735.44 | 0.468499 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00778445 | 44.0300 | 9611.96 | 0.00 | 13780.37 | 13780.37 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 21997.976 | 21997.976 | 0.750352 | 0.00019245 | 580.106 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21997.98 | 21997.98 | 0.750352 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00780023 | 44.1180 | 15393.55 | 0.00 | 22069.87 | 22069.87 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 12407.026 | 12407.026 | 0.501787 | 0.00010854 | 305.531 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12407.03 | 12407.03 | 0.501787 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00770102 | 43.5646 | 7991.39 | 0.00 | 12446.04 | 12446.04 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 286203.600 | 286203.600 | 9.767409 | 0.00250383 | 7545.671 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 286203.60 | 286203.60 | 9.767409 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00765732 | 43.3222 | 200265.88 | 0.00 | 287126.21 | 287126.21 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 189849.567 | 189849.567 | 6.479353 | 0.00166089 | 5005.233 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 189849.57 | 189849.57 | 6.479353 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00765595 | 43.3146 | 132841.97 | 0.00 | 190460.89 | 190460.89 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 289677.868 | 289677.868 | 9.886126 | 0.00253423 | 7637.217 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 289677.87 | 289677.87 | 9.886126 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00766138 | 43.3448 | 202694.95 | 0.00 | 290611.30 | 290611.30 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 186046.864 | 186046.864 | 6.349451 | 0.00162762 | 4905.020 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 186046.86 | 186046.86 | 6.349451 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00764910 | 43.2764 | 130183.00 | 0.00 | 186646.25 | 186646.25 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 37689.391 | 37689.391 | 1.286648 | 0.00032972 | 993.527 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37689.39 | 37583.07 | 1.286648 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767644 | 43.4299 | 26368.99 | 0.00 | 37809.86 | 37809.86 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 24867.164 | 24867.164 | 0.848943 | 0.00021755 | 655.513 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24867.16 | 24867.16 | 0.848943 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767313 | 43.4115 | 17397.95 | 0.00 | 24946.59 | 24946.59 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 38120.106 | 38120.106 | 1.301366 | 0.00033349 | 1004.876 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38120.11 | 38120.11 | 1.301366 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767993 | 43.4494 | 26670.14 | 0.00 | 38241.92 | 38241.92 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 24809.039 | 24809.039 | 0.846961 | 0.00021704 | 653.980 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24809.04 | 24809.04 | 0.846961 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767261 | 43.4087 | 17357.28 | 0.00 | 24888.27 | 24888.27 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 184210.738 | -999.000 | 10.928369 | 0.00783675 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 184210.74 | 182137.24 | 10.928369 | 26.19 | 14.59 | 0.00708825 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 22.8235 | 24.00 | 0.00732504 | 34.5527 | 128751.81 | 0.00 | 207680.83 | 204565.70 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 99832.446 | 99832.446 | 3.278511 | 0.00087338 | 1534.400 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 99832.45 | 99832.45 | 3.278511 | -15.97 | -15.97 | 0.00213112 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 76.0784 | 19.41 | 0.00772660 | 48.2177 | 33826.76 | 0.00 | 81014.05 | 81014.05 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1730478.656 | -999.000 | 101.249077 | 0.07361856 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1730478.66 | 1713938.70 | 101.249077 | 26.44 | 14.66 | 0.00707576 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 25.0688 | 24.00 | 0.00734480 | 34.6448 | 1175525.39 | 0.00 | 1948421.16 | 1922548.22 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1054592.047 | 1054592.047 | 30.374723 | 0.00922603 | 15670.253 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1054592.05 | 1054592.05 | 30.374723 | -20.01 | -20.01 | 0.00153009 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 83.5627 | 17.82 | 0.00755555 | 52.0890 | 368953.52 | 0.00 | 821867.45 | 821867.45 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 189241.840 | -999.000 | 11.301772 | 0.00805079 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 189241.84 | 187457.73 | 11.301772 | 26.12 | 14.55 | 0.00707352 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 22.4583 | 24.00 | 0.00729659 | 34.4200 | 135194.17 | 0.00 | 213483.34 | 210721.82 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 103926.019 | 103926.019 | 3.390532 | 0.00090919 | 1594.652 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:30:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 103926.02 | 103926.02 | 3.390532 | -16.16 | -16.16 | 0.00213940 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 74.8611 | 15.76 | 0.00758378 | 59.5988 | 38318.26 | 0.00 | 84172.05 | 84172.05 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 105376.185 | -999.000 | 6.474075 | 0.00448295 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 105376.19 | 102120.20 | 6.474075 | 25.80 | 14.58 | 0.00724228 | 11.22 | 8.74 | 0.00700000 | 32.60 | 0.00630558 | 16.10 | 18.5379 | 24.00 | 0.00748979 | 35.3211 | 68928.11 | 0.00 | 118909.91 | 116571.47 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 309103.329 | 309103.329 | 6.474075 | 0.00270417 | 6611.297 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 309103.33 | 309103.33 | 6.474075 | -5.12 | -9.52 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 18.5379 | 22.82 | 0.00034190 | 1.7515 | 0.00 | 0.00 | 246465.63 | 246465.63 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 465166.581 | 261784.148 | 24.471423 | 0.01139190 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 404200.60 | 402729.32 | -999.0 | 28.68 | 15.39 | 0.00703190 | 12.80 | 9.41 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | -999.0000 | 27.00 | 0.00704208 | 27.8119 | 371971.55 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10529.648 | 5988.336 | 0.570008 | 0.00025787 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 9101.03 | 9035.60 | -999.0 | 28.07 | 15.21 | 0.00706149 | 12.80 | 9.41 | 0.00700000 | 26.57 | 0.00629632 | 14.04 | -999.0000 | 27.00 | 0.00708308 | 27.9700 | 8675.44 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 100857.568 | 57346.939 | 5.457997 | 0.00247000 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 87178.65 | 86525.39 | -999.0 | 28.07 | 15.21 | 0.00706411 | 12.80 | 9.41 | 0.00700000 | 26.57 | 0.00629632 | 14.04 | -999.0000 | 27.00 | 0.00708676 | 27.9845 | 83069.49 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10265.811 | 5837.548 | 0.555614 | 0.00025141 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 8873.30 | 8807.87 | -999.0 | 28.07 | 15.21 | 0.00706308 | 12.80 | 9.41 | 0.00700000 | 26.57 | 0.00629632 | 14.04 | -999.0000 | 27.00 | 0.00708527 | 27.9786 | 8456.34 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 465166.581 | 465166.581 | 24.471423 | 0.01139190 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 465166.58 | 465166.58 | 24.471423 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.3828 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10529.648 | 10529.648 | 0.570008 | 0.00025787 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10529.65 | 10529.65 | 0.570008 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7425 | 25.05 | 0.00098406 | 4.4026 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 100857.568 | 100857.568 | 5.457997 | 0.00247000 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100857.57 | 100857.57 | 5.457997 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8641 | 23.48 | 0.00098407 | 4.8367 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10265.811 | 10265.811 | 0.555614 | 0.00025141 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10265.81 | 10265.81 | 0.555614 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8135 | 21.93 | 0.00098348 | 5.3126 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 24207.99 | 24207.99 | 24.471423 | -0.38 | -0.38 | 0.00690793 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.3828 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.570008 | -0.76 | -5.60 | 0.00096645 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7425 | 25.05 | 0.00098406 | 4.4026 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11183.09 | 11183.09 | 5.457997 | -0.79 | -5.62 | 0.00096568 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8641 | 23.48 | 0.00098407 | 4.8367 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.555614 | -0.78 | -5.61 | 0.00096542 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8135 | 21.93 | 0.00098348 | 5.3126 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 27176.709 | 27176.709 | 2.038317 | 0.00023775 | 577.099 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 0.7882 | 0.804052 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27176.71 | 27176.71 | 1.0000 | 2.14663287 | 2.038317 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.23772946 | 60.00 | 32.22 | 27.78 | 0.000 | 27176.71 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.76 | 0.00799999 | 21.00 | 0.00799999 | 45.2309 | 9227.35 | 0.00 | 27272.54 | 27272.54 | 2.14663287 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.26 | 16.41 | 0.00800000 | 45764.6 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 525448.405 | 525448.405 | 19.608877 | 0.00459685 | 13336.118 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 15.2393 | 15.545956 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 525448.40 | 525448.40 | 1.0000 | 20.65089050 | 19.608877 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 4.59638294 | 60.00 | 32.22 | 27.78 | 0.000 | 525448.40 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 352773.19 | 0.00 | 527073.53 | 527073.53 | 20.65089050 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.83 | 20.53 | 0.00800000 | 58582.9 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 114474.947 | 114474.947 | 3.900181 | 0.00100148 | 3020.418 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 3.3200 | 3.386864 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 114474.95 | 114474.95 | 1.0000 | 4.10743635 | 3.900181 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.00137462 | 60.00 | 32.22 | 27.78 | 0.000 | 114474.95 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 80130.06 | 0.00 | 114860.69 | 114860.69 | 4.10743635 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61023.9 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20010.399 | 20010.399 | 0.682446 | 0.00017506 | 527.730 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 0.5803 | 0.592029 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20010.40 | 20010.40 | 1.0000 | 0.71871098 | 0.682446 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.17504184 | 60.00 | 32.22 | 27.78 | 0.000 | 20010.40 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00777257 | 21.00 | 0.00777257 | 43.9637 | 14004.02 | 0.00 | 20076.07 | 20076.07 | 0.71871098 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60993.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13735.438 | 13735.438 | 0.468499 | 0.00012016 | 362.221 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 0.3984 | 0.406378 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13735.44 | 13735.44 | 1.0000 | 0.49339496 | 0.468499 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.12015135 | 60.00 | 32.22 | 27.78 | 0.000 | 13735.44 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00778445 | 21.00 | 0.00778445 | 44.0300 | 9611.96 | 0.00 | 13780.37 | 13780.37 | 0.49339496 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21997.976 | 21997.976 | 0.750352 | 0.00019245 | 580.106 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 0.6380 | 0.650834 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21997.98 | 21997.98 | 1.0000 | 0.79022525 | 0.750352 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.19242826 | 60.00 | 32.22 | 27.78 | 0.000 | 21997.98 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00780023 | 21.00 | 0.00780023 | 44.1180 | 15393.55 | 0.00 | 22069.87 | 22069.87 | 0.79022525 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60988.4 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12407.026 | 12407.026 | 0.501787 | 0.00010854 | 305.531 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 0.3598 | 0.367075 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12407.03 | 12407.03 | 1.0000 | 0.52845211 | 0.501787 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.10853101 | 60.00 | 32.22 | 27.78 | 0.000 | 12407.03 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00770102 | 21.00 | 0.00770102 | 43.5646 | 7991.39 | 0.00 | 12446.04 | 12446.04 | 0.52845211 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.90 | 19.94 | 0.00800000 | 56611.7 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 286203.600 | 286203.600 | 9.767409 | 0.00250383 | 7545.671 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 8.3006 | 8.467641 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 286203.60 | 286203.60 | 1.0000 | 10.28644820 | 9.767409 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.50357853 | 60.00 | 32.22 | 27.78 | 0.000 | 286203.60 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00765732 | 21.00 | 0.00765732 | 43.3222 | 200265.88 | 0.00 | 287126.21 | 287126.21 | 10.28644820 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.9 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 189849.567 | 189849.567 | 6.479353 | 0.00166089 | 5005.233 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 5.5061 | 5.616904 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 189849.57 | 189849.57 | 1.0000 | 6.82366491 | 6.479353 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.66071741 | 60.00 | 32.22 | 27.78 | 0.000 | 189849.57 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00765595 | 21.00 | 0.00765595 | 43.3146 | 132841.97 | 0.00 | 190460.89 | 190460.89 | 6.82366491 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 289677.868 | 289677.868 | 9.886126 | 0.00253423 | 7637.217 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 8.4014 | 8.570431 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 289677.87 | 289677.87 | 1.0000 | 10.41147385 | 9.886126 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.53396984 | 60.00 | 32.22 | 27.78 | 0.000 | 289677.87 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00766138 | 21.00 | 0.00766138 | 43.3448 | 202694.95 | 0.00 | 290611.30 | 290611.30 | 10.41147385 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 186046.864 | 186046.864 | 6.349451 | 0.00162762 | 4905.020 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 5.3958 | 5.504397 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 186046.86 | 186046.86 | 1.0000 | 6.68686049 | 6.349451 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.62745309 | 60.00 | 32.22 | 27.78 | 0.000 | 186046.86 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00764910 | 21.00 | 0.00764910 | 43.2764 | 130183.00 | 0.00 | 186646.25 | 186646.25 | 6.68686049 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37689.391 | 37689.391 | 1.286648 | 0.00032972 | 993.527 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 1.0931 | 1.115081 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37689.39 | 37583.07 | 1.0000 | 1.35502071 | 1.286648 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.32968960 | 60.00 | 32.22 | 27.78 | 0.000 | 37689.39 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767644 | 21.00 | 0.00767644 | 43.4299 | 26368.99 | 0.00 | 37809.86 | 37809.86 | 1.35502071 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.4 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24867.164 | 24867.164 | 0.848943 | 0.00021755 | 655.513 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 0.7212 | 0.735722 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24867.16 | 24867.16 | 1.0000 | 0.89405546 | 0.848943 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.21752661 | 60.00 | 32.22 | 27.78 | 0.000 | 24867.16 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767313 | 21.00 | 0.00767313 | 43.4115 | 17397.95 | 0.00 | 24946.59 | 24946.59 | 0.89405546 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38120.106 | 38120.106 | 1.301366 | 0.00033349 | 1004.876 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 1.1056 | 1.127824 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38120.11 | 38120.11 | 1.0000 | 1.37051994 | 1.301366 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.33345730 | 60.00 | 32.22 | 27.78 | 0.000 | 38120.11 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767993 | 21.00 | 0.00767993 | 43.4494 | 26670.14 | 0.00 | 38241.92 | 38241.92 | 1.37051994 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24809.039 | 24809.039 | 0.846961 | 0.00021704 | 653.980 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 0.7195 | 0.734002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24809.04 | 24809.04 | 1.0000 | 0.89196849 | 0.846961 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.21701816 | 60.00 | 32.22 | 27.78 | 0.000 | 24809.04 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767261 | 21.00 | 0.00767261 | 43.4087 | 17357.28 | 0.00 | 24888.27 | 24888.27 | 0.89196849 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.5 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 184210.738 | -999.000 | 10.928369 | 0.00783675 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0167 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.928369 | 11.50910120 | 4197.9300 | 999.8980 | 93.97945699 | 12.27 | 6.67 | 5.60 | 2209307.42 | 8.3379 | 8.337940 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 184210.74 | 182137.24 | 1.0000 | 11.50910120 | 10.928369 | 26.19 | 14.59 | 0.00708825 | 44384.1 | 10.68 | 8.51 | 0.00700000 | 28378.5 | 7.83595118 | 6.67 | 12.27 | 5.60 | 24824.809 | 159385.93 | 33.40 | 0.00630683 | 16.37 | 2.49424000 | 22.8235 | 24.00 | 0.00732504 | 24.00 | 0.00732504 | 34.5527 | 128751.81 | 0.00 | 207680.83 | 204565.70 | 11.50910120 | 26.19 | 15.94 | 0.00708825 | 44384.1 | 8.73 | 8.71 | 0.00698072 | 26339.2 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 99832.446 | 99832.446 | 3.278511 | 0.00087338 | 1534.400 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.928369 | 11.50910120 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 2.8954 | 2.953650 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 99832.45 | 99832.45 | 1.0000 | 3.45273036 | 3.278511 | -15.97 | -15.97 | 0.00213112 | -10785.0 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.87328870 | 60.00 | 32.22 | 27.78 | 0.000 | 99832.45 | -27.60 | 0.00034190 | -27.60 | 2.49424000 | 76.0784 | 21.00 | 0.00782146 | 19.41 | 0.00772660 | 48.2177 | 33826.76 | 0.00 | 81014.05 | 81014.05 | 3.45273036 | 2.80 | -0.98 | 0.00213112 | 8154.5 | 26.06 | 11.12 | 0.00213112 | 31618.2 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1730478.656 | -999.000 | 101.249077 | 0.07361856 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9935 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 101.249077 | 106.62944070 | 4197.9300 | 999.8980 | 93.97945699 | 12.27 | 6.67 | 5.60 | 2209307.42 | 78.3267 | 78.326748 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1730478.66 | 1713938.70 | 1.0000 | 106.62944070 | 101.249077 | 26.44 | 14.66 | 0.00707576 | 44607.3 | 10.68 | 8.51 | 0.00700000 | 28378.4 | 73.61105252 | 6.67 | 12.27 | 5.60 | 229996.718 | 1500481.94 | 33.40 | 0.00630683 | 16.37 | 25.38195000 | 25.0688 | 24.00 | 0.00734480 | 24.00 | 0.00734480 | 34.6448 | 1175525.39 | 0.00 | 1948421.16 | 1922548.22 | 106.62944070 | 26.44 | 16.02 | 0.00707576 | 44607.3 | 8.72 | 8.71 | 0.00697936 | 26334.5 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1054592.047 | 1054592.047 | 30.374723 | 0.00922603 | 15670.253 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 101.249077 | 106.62944070 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 30.5857 | 31.201240 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1054592.05 | 1054592.05 | 1.0000 | 31.98883221 | 30.374723 | -20.01 | -20.01 | 0.00153009 | -16335.2 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 9.22509013 | 60.00 | 32.22 | 27.78 | 0.000 | 1054592.05 | -27.60 | 0.00034190 | -27.60 | 25.38195000 | 83.5627 | 18.59 | 0.00757052 | 17.82 | 0.00755555 | 52.0890 | 368953.52 | 0.00 | 821867.45 | 821867.45 | 31.98883221 | 2.80 | -1.93 | 0.00153009 | 6648.2 | 28.30 | 11.43 | 0.00153009 | 32340.5 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 189241.840 | -999.000 | 11.301772 | 0.00805079 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9893 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.301772 | 11.90234670 | 4197.9300 | 999.8980 | 93.97945699 | 12.27 | 6.67 | 5.60 | 2209307.42 | 8.5657 | 8.565664 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 189241.84 | 187457.73 | 1.0000 | 11.90234670 | 11.301772 | 26.12 | 14.55 | 0.00707352 | 44278.0 | 10.68 | 8.51 | 0.00700000 | 28378.4 | 8.04996408 | 6.67 | 12.27 | 5.60 | 25673.029 | 163568.81 | 33.40 | 0.00630683 | 16.37 | 2.53819000 | 22.4583 | 24.00 | 0.00729659 | 24.00 | 0.00729659 | 34.4200 | 135194.17 | 0.00 | 213483.34 | 210721.82 | 11.90234670 | 26.12 | 15.91 | 0.00707352 | 44278.0 | 8.73 | 8.71 | 0.00698135 | 26341.7 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 103926.019 | 103926.019 | 3.390532 | 0.00090919 | 1594.652 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.301772 | 11.90234670 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 3.0141 | 3.074763 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:30:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 103926.02 | 103926.02 | 1.0000 | 3.57070401 | 3.390532 | -16.16 | -16.16 | 0.00213940 | -10956.5 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.90909740 | 60.00 | 32.22 | 27.78 | 0.000 | 103926.02 | -27.60 | 0.00034190 | -27.60 | 2.53819000 | 74.8611 | 17.89 | 0.00749217 | 15.76 | 0.00758378 | 59.5988 | 38318.26 | 0.00 | 84172.05 | 84172.05 | 3.57070401 | 2.80 | -0.97 | 0.00213940 | 8175.2 | 26.17 | 11.17 | 0.00213940 | 31748.2 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 105376.185 | -999.000 | 6.474075 | 0.00448295 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3030 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:ConstantVolume | 6.474075 | 6.81810613 | 4197.9300 | 999.8980 | 93.97945699 | 12.27 | 6.67 | 5.60 | 2209307.42 | 4.7696 | 4.769648 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 105376.19 | 102120.20 | 1.0000 | 6.81810613 | 6.474075 | 25.80 | 14.58 | 0.00724228 | 44381.1 | 11.22 | 8.74 | 0.00700000 | 28925.7 | 4.48248920 | 6.67 | 12.27 | 5.60 | 10977.793 | 94398.39 | 32.60 | 0.00630558 | 16.10 | 1.20015641 | 18.5379 | 24.00 | 0.00748979 | 24.00 | 0.00748979 | 35.3211 | 68928.11 | 0.00 | 118909.91 | 116571.47 | 6.81810613 | 25.80 | 15.94 | 0.00724228 | 44381.1 | 9.01 | 8.98 | 0.00710605 | 26940.7 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 309103.329 | 309103.329 | 6.474075 | 0.00270417 | 6611.297 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:ConstantVolume | 6.474075 | 6.81810613 | 4197.9300 | 999.8980 | 29.56642113 | 54.44 | 82.22 | 27.78 | 3447991.55 | 8.9647 | 9.145155 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 309103.33 | 309103.33 | 1.0000 | 6.81810613 | 6.474075 | -5.12 | -9.52 | 0.00034190 | -4289.4 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.70389492 | 60.00 | 32.22 | 27.78 | 0.000 | 309103.33 | -27.60 | 0.00034190 | -27.60 | 1.20015641 | 18.5379 | 0.00 | 0.00034190 | 22.82 | 0.00034190 | 1.7515 | 0.00 | 0.00 | 246465.63 | 246465.63 | 6.81810613 | 12.80 | 2.46 | 0.00034190 | 13725.2 | 48.75 | 18.00 | 0.00034190 | 49873.8 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 465166.581 | 261784.148 | 24.471423 | 0.01139190 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9119 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 404200.60 | 402729.32 | 0.8689 | -999.0 | -999.0 | 28.68 | 15.39 | 0.00703190 | 46779.3 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 404200.60 | 33.40 | 0.00630683 | 16.37 | 0.33839277 | -999.0000 | 27.00 | 0.00704208 | 27.00 | 0.00704208 | 27.8119 | 371971.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10529.648 | 5988.336 | 0.570008 | 0.00025787 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9670 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 9101.03 | 9035.60 | 0.8643 | -999.0 | -999.0 | 28.07 | 15.21 | 0.00706149 | 46233.3 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9101.03 | 26.57 | 0.00629632 | 14.04 | 0.01563234 | -999.0000 | 27.00 | 0.00708308 | 27.00 | 0.00708308 | 27.9700 | 8675.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 100857.568 | 57346.939 | 5.457997 | 0.00247000 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9718 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 87178.65 | 86525.39 | 0.8644 | -999.0 | -999.0 | 28.07 | 15.21 | 0.00706411 | 46239.3 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87178.65 | 26.57 | 0.00629632 | 14.04 | 0.15632344 | -999.0000 | 27.00 | 0.00708676 | 27.00 | 0.00708676 | 27.9845 | 83069.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10265.811 | 5837.548 | 0.555614 | 0.00025141 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9699 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 8873.30 | 8807.87 | 0.8644 | -999.0 | -999.0 | 28.07 | 15.21 | 0.00706308 | 46237.0 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8873.30 | 26.57 | 0.00629632 | 14.04 | 0.01563234 | -999.0000 | 27.00 | 0.00708527 | 27.00 | 0.00708527 | 27.9786 | 8456.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 465166.581 | 465166.581 | 24.471423 | 0.01139190 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 465166.58 | 465166.58 | 1.0000 | 25.77183149 | 24.471423 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 465166.58 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.3828 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10529.648 | 10529.648 | 0.570008 | 0.00025787 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10529.65 | 10529.65 | 1.0000 | 0.60029789 | 0.570008 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10529.65 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7425 | 0.00 | 0.00098406 | 25.05 | 0.00098406 | 4.4026 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 100857.568 | 100857.568 | 5.457997 | 0.00247000 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100857.57 | 100857.57 | 1.0000 | 5.74803442 | 5.457997 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 100857.57 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.8641 | 0.00 | 0.00098407 | 23.48 | 0.00098407 | 4.8367 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10265.811 | 10265.811 | 0.555614 | 0.00025141 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10265.81 | 10265.81 | 1.0000 | 0.58513972 | 0.555614 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10265.81 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.8135 | 0.00 | 0.00098348 | 21.93 | 0.00098348 | 5.3126 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.471423 | 25.77183149 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 24207.99 | 24207.99 | 1.0000 | 25.77183149 | 24.471423 | -0.38 | -0.38 | 0.00690793 | 16887.9 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24207.99 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.3828 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.570008 | 0.60029789 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.60029789 | 0.570008 | -0.76 | -5.60 | 0.00096645 | 1655.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7425 | 0.00 | 0.00098406 | 25.05 | 0.00098406 | 4.4026 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.457997 | 5.74803442 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11183.09 | 11183.09 | 1.0000 | 5.74803442 | 5.457997 | -0.79 | -5.62 | 0.00096568 | 1619.4 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11183.09 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.8641 | 0.00 | 0.00098407 | 23.48 | 0.00098407 | 4.8367 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.555614 | 0.58513972 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.58513972 | 0.555614 | -0.78 | -5.61 | 0.00096542 | 1632.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.8135 | 0.00 | 0.00098348 | 21.93 | 0.00098348 | 5.3126 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.93 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 101.25 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.30 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.47 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1511.00 | 1617.83 | 36.67 |
CORE_BOTTOM | 1387.17 | 1691.50 | 23.83 |
CORE_MID | 996.67 | 3503.00 | 236.50 |
CORE_TOP | 1861.00 | 4149.33 | 1134.83 |
PERIMETER_BOT_ZN_3 | 1628.33 | 3957.50 | 684.67 |
PERIMETER_BOT_ZN_2 | 1998.67 | 3961.33 | 814.67 |
PERIMETER_BOT_ZN_1 | 2152.33 | 3352.67 | 691.17 |
PERIMETER_BOT_ZN_4 | 2326.00 | 3063.00 | 443.33 |
PERIMETER_MID_ZN_3 | 2697.67 | 4527.17 | 2072.00 |
PERIMETER_MID_ZN_2 | 2469.00 | 3781.83 | 1658.00 |
PERIMETER_MID_ZN_1 | 2532.50 | 3805.50 | 1274.33 |
PERIMETER_MID_ZN_4 | 2655.83 | 4444.67 | 1691.33 |
PERIMETER_TOP_ZN_3 | 3355.33 | 4806.67 | 2786.67 |
PERIMETER_TOP_ZN_2 | 3449.67 | 4445.17 | 2437.50 |
PERIMETER_TOP_ZN_1 | 3017.83 | 4154.33 | 1916.17 |
PERIMETER_TOP_ZN_4 | 3192.67 | 4648.00 | 2302.17 |
DATACENTER_BOT_ZN_6 | 5811.50 | 418.33 | 417.67 |
DATACENTER_MID_ZN_6 | 5263.67 | 197.83 | 66.33 |
DATACENTER_TOP_ZN_6 | 4523.50 | 566.50 | 153.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5659.00 | 5659.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5942.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 59.67 | 0.00 | 2.83 |
CORE_BOTTOM | 0.00 | 4.50 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 15.83 | 0.00 | 3.17 | 0.00 |
PERIMETER_BOT_ZN_3 | 6.00 | 0.50 | 0.83 | 0.33 |
PERIMETER_BOT_ZN_2 | 5.83 | 14.33 | 0.00 | 14.33 |
PERIMETER_BOT_ZN_1 | 6.33 | 21.00 | 0.17 | 20.17 |
PERIMETER_BOT_ZN_4 | 2.67 | 49.83 | 0.00 | 19.50 |
PERIMETER_MID_ZN_3 | 116.83 | 0.00 | 38.67 | 0.00 |
PERIMETER_MID_ZN_2 | 66.17 | 15.33 | 9.00 | 15.33 |
PERIMETER_MID_ZN_1 | 47.33 | 20.17 | 6.00 | 19.00 |
PERIMETER_MID_ZN_4 | 52.33 | 17.67 | 7.83 | 8.00 |
PERIMETER_TOP_ZN_3 | 307.33 | 1.00 | 106.33 | 0.50 |
PERIMETER_TOP_ZN_2 | 191.67 | 17.33 | 38.00 | 16.67 |
PERIMETER_TOP_ZN_1 | 155.00 | 14.33 | 26.17 | 12.50 |
PERIMETER_TOP_ZN_4 | 147.17 | 18.33 | 29.17 | 8.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 16.50 | 0.00 | 11.83 |
DATACENTER_MID_ZN_6 | 0.00 | 6.50 | 0.00 | 3.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 6.83 | 0.00 | 3.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 521.33 | 0.00 | 403.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 348.83 | 684.50 | 115.33 | 480.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 1.328 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.987 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.743 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.687 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.933 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 1.680 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 1.598 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 2.134 | 0.061 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.775 | 0.137 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 1.561 | 0.151 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 1.510 | 0.138 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 1.690 | 0.142 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.895 | 0.170 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 1.648 | 0.176 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 1.508 | 0.171 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 1.749 | 0.176 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.57 | 42.18 | 1911.37 | 0.481 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.57 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.32 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.96 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.57 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1032.96 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 55200612.88 | 0.00 | 55200612.88 | 0.00 | 55200612.88 | 37848132.68 | 3922.68 | 931.43 | 3905.88 | 404.42 |
CORE_BOTTOM | 42332194.17 | 0.00 | 42332194.17 | 0.00 | 42332194.17 | 33990283.35 | 4899.68 | 46.22 | 3814.10 | 502.27 |
CORE_MID | 0.31E+09 | 0.00 | 0.31E+09 | 0.00 | 0.31E+09 | 0.34E+09 | 6131.20 | 46.37 | 2582.43 | 371.60 |
CORE_TOP | 28405504.34 | 0.00 | 28405504.34 | 0.00 | 28405504.34 | 33990283.35 | 6519.86 | 33.43 | 2206.71 | 428.44 |
PERIMETER_BOT_ZN_3 | 5122350.16 | 0.00 | 5122350.16 | 591585.02 | 5713935.18 | 4267819.30 | 4310.73 | 83.43 | 4365.84 | 502.27 |
PERIMETER_BOT_ZN_2 | 5989795.76 | 0.00 | 5989795.76 | 394389.74 | 6384185.50 | 2750345.05 | 3441.38 | 0.48 | 5318.14 | 502.27 |
PERIMETER_BOT_ZN_1 | 8716307.32 | 0.00 | 8716307.32 | 591585.02 | 9307892.34 | 4267912.63 | 3459.00 | 2.46 | 5298.53 | 502.27 |
PERIMETER_BOT_ZN_4 | 7601485.63 | 0.00 | 7601485.63 | 394389.74 | 7995875.37 | 2750345.05 | 3424.87 | 0.47 | 5334.66 | 502.27 |
PERIMETER_MID_ZN_3 | 40740653.62 | 0.00 | 40740653.62 | 1387434.57 | 42128088.19 | 42678193.03 | 4361.36 | 49.28 | 4349.35 | 371.60 |
PERIMETER_MID_ZN_2 | 56780835.66 | 0.00 | 56780835.66 | 924955.75 | 57705791.41 | 27503450.52 | 3829.57 | 5.07 | 4925.36 | 1280.60 |
PERIMETER_MID_ZN_1 | 78768417.74 | 0.00 | 78768417.74 | 1387434.57 | 80155852.31 | 42679126.28 | 3884.05 | 3.72 | 4872.23 | 371.60 |
PERIMETER_MID_ZN_4 | 57463662.19 | 0.00 | 57463662.19 | 924955.75 | 58388617.93 | 27503450.52 | 3817.48 | 3.19 | 4939.34 | 371.60 |
PERIMETER_TOP_ZN_3 | 4688596.35 | 0.00 | 4688596.35 | 1722650.34 | 6411246.70 | 4267819.30 | 4135.19 | 15.54 | 4609.27 | 428.44 |
PERIMETER_TOP_ZN_2 | 5537765.13 | 0.00 | 5537765.13 | 1148432.78 | 6686197.91 | 2750345.05 | 3954.61 | 4.29 | 4801.11 | 428.44 |
PERIMETER_TOP_ZN_1 | 7832471.97 | 0.00 | 7832471.97 | 1722650.34 | 9555122.32 | 4267912.63 | 4005.32 | 5.35 | 4749.33 | 428.44 |
PERIMETER_TOP_ZN_4 | 5904131.57 | 0.00 | 5904131.57 | 1148432.78 | 7052564.34 | 2750345.05 | 3926.43 | 4.86 | 4828.71 | 428.44 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.56E+10 | 0.00 | 0.56E+10 | 53961922.12 | 0.57E+10 | 0.50E+10 | 6861.83 | 4404.34 | 5544.19 | 1969.42 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.4546 | 0.0000 | 2.4546 | 0.0000 | 2.4546 | 1.2002 | 1339.29 | 927.87 | 3675.84 |
CORE_BOTTOM | 1.8428 | 0.0000 | 1.8428 | 0.0000 | 1.8428 | 1.0778 | 2455.68 | 42.28 | 3445.04 |
CORE_MID | 13.8789 | 0.0000 | 13.8789 | 0.0000 | 13.8789 | 10.7782 | 3432.93 | 45.70 | 2464.37 |
CORE_TOP | 1.2850 | 0.0000 | 1.2850 | 0.0000 | 1.2850 | 1.0778 | 3789.97 | 33.29 | 2119.74 |
PERIMETER_BOT_ZN_3 | 0.2190 | 0.0000 | 0.2190 | 0.0139 | 0.2329 | 0.1353 | 1907.42 | 77.67 | 3957.91 |
PERIMETER_BOT_ZN_2 | 0.2547 | 0.0000 | 0.2547 | 0.0092 | 0.2639 | 0.0872 | 1096.43 | 0.33 | 4846.24 |
PERIMETER_BOT_ZN_1 | 0.3754 | 0.0000 | 0.3754 | 0.0139 | 0.3893 | 0.1353 | 1108.24 | 1.35 | 4833.41 |
PERIMETER_BOT_ZN_4 | 0.3230 | 0.0000 | 0.3230 | 0.0092 | 0.3322 | 0.0872 | 1086.38 | 0.37 | 4856.25 |
PERIMETER_MID_ZN_3 | 1.8244 | 0.0000 | 1.8244 | 0.0325 | 1.8569 | 1.3533 | 1676.27 | 48.00 | 4218.72 |
PERIMETER_MID_ZN_2 | 2.3703 | 0.0000 | 2.3703 | 0.0230 | 2.3932 | 0.8721 | 1212.83 | 1.96 | 3819.21 |
PERIMETER_MID_ZN_1 | 3.5511 | 0.0000 | 3.5511 | 0.0325 | 3.5836 | 1.3533 | 1240.27 | 1.94 | 4700.79 |
PERIMETER_MID_ZN_4 | 2.5676 | 0.0000 | 2.5676 | 0.0217 | 2.5893 | 0.8721 | 1205.64 | 1.90 | 4735.47 |
PERIMETER_TOP_ZN_3 | 0.2111 | 0.0000 | 0.2111 | 0.0404 | 0.2515 | 0.1353 | 1418.26 | 15.18 | 4509.55 |
PERIMETER_TOP_ZN_2 | 0.2502 | 0.0000 | 0.2502 | 0.0269 | 0.2771 | 0.0872 | 1290.58 | 1.75 | 4650.67 |
PERIMETER_TOP_ZN_1 | 0.3548 | 0.0000 | 0.3548 | 0.0404 | 0.3951 | 0.1353 | 1317.34 | 3.38 | 4622.28 |
PERIMETER_TOP_ZN_4 | 0.2657 | 0.0000 | 0.2657 | 0.0269 | 0.2927 | 0.0872 | 1274.02 | 3.13 | 4665.86 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 251.1702 | 0.0000 | 251.1702 | 1.2778 | 252.4480 | 158.4706 | 4044.83 | 4376.29 | 4903.63 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 77373505.22 | 0.00 | 77373505.22 | 48026705.38 | 3516.08 | 9.09 | 5234.83 | 502.27 |
VAV_MID WITH REHEAT | 0.60E+09 | 0.00 | 0.60E+09 | 0.48E+09 | 3999.20 | 5.85 | 4754.95 | 371.60 |
VAV_TOP WITH REHEAT | 58082055.60 | 0.00 | 58082055.60 | 48026705.38 | 4090.89 | 2.94 | 4666.16 | 428.40 |
CAV_BAS | 61223198.86 | 0.00 | 61223198.86 | 37848132.68 | 3887.93 | 5.82 | 4866.25 | 404.40 |
AIRLOOP DATACENTER BASEMENT | 5865235.79 | 0.00 | 5865235.79 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2709495.95 | 0.00 | 2709495.95 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.3439 | 0.0000 | 3.3439 | 1.5229 | 1144.83 | 4.82 | 4793.34 |
VAV_MID WITH REHEAT | 27.0269 | 0.0000 | 27.0269 | 15.2292 | 1317.11 | 4.12 | 4621.78 |
VAV_TOP WITH REHEAT | 2.6249 | 0.0000 | 2.6249 | 1.5229 | 1370.04 | 2.46 | 4570.50 |
CAV_BAS | 2.7224 | 0.0000 | 2.7224 | 1.2002 | 1329.28 | 1.81 | 4611.92 |
AIRLOOP DATACENTER BASEMENT | 0.2741 | 0.0000 | 0.2741 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1266 | 0.0000 | 0.1266 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 4209.98 | 0.00 | 0.00 | 0.00 | 1164.85 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 3705.97 | 0.00 | 0.00 | 0.00 | 1478.25 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 3083.20 | 0.00 | 0.00 | 0.00 | 2159.31 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 919.33 | 4145.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 4.7663 | 0.0000 | 0.0000 | 0.0000 | 1.8936 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 39.5512 | 0.0000 | 0.0000 | 0.0000 | 19.4570 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.2851 | 0.0000 | 0.0000 | 0.0000 | 1.9580 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.3316 | 3.9987 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3754 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1734 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1380 |
Defaulted Fields | 1179 |
Fields with Defaults | 3862 |
Autosized Fields | 330 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 29517.66 | 391545.11 | 29-JAN-11:30 | 2076655.13 | 07-AUG-15:40 |
Electricity:Building | 18924.62 | 251811.03 | 01-JAN-09:50 | 1146857.44 | 01-DEC-16:40 |
Electricity:Zone:BASEMENT | 664.85 | 14623.97 | 01-JAN-00:10 | 34452.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18924.62 | 251811.03 | 01-JAN-09:50 | 1146857.44 | 01-DEC-16:40 |
InteriorLights:Electricity | 3711.21 | 17601.77 | 01-JAN-09:50 | 352853.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3711.21 | 17601.77 | 01-JAN-09:50 | 352853.36 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3711.21 | 17601.77 | 01-JAN-09:50 | 352853.36 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3711.21 | 17601.77 | 01-JAN-09:50 | 352853.36 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 537.23 | 7090.40 | 01-JAN-00:10 | 36983.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5372.24 | 70903.72 | 01-JAN-00:10 | 369831.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 537.22 | 7090.37 | 01-JAN-00:10 | 36983.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 59.18 | 839.57 | 01-JAN-09:40 | 4643.71 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.83 | 80.80 | 01-JAN-09:40 | 2367.39 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.83 | 80.80 | 01-JAN-09:40 | 2367.39 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 38.07 | 541.05 | 01-JAN-08:50 | 2992.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.07 | 52.07 | 01-JAN-08:50 | 1525.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.07 | 52.07 | 01-JAN-08:50 | 1525.64 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 58.99 | 839.58 | 01-JAN-08:50 | 4643.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.65 | 80.80 | 01-JAN-08:50 | 2367.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.65 | 80.80 | 01-JAN-08:50 | 2367.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 38.09 | 541.05 | 01-JAN-09:40 | 2992.57 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 12.09 | 52.07 | 01-JAN-09:40 | 1525.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 12.09 | 52.07 | 01-JAN-09:40 | 1525.64 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 591.94 | 8395.70 | 01-JAN-09:50 | 46437.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 188.52 | 807.98 | 01-JAN-09:50 | 23673.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 188.52 | 807.98 | 01-JAN-09:50 | 23673.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 380.73 | 5410.51 | 01-JAN-08:50 | 29925.82 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 120.74 | 520.69 | 01-JAN-08:50 | 15256.36 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 120.74 | 520.69 | 01-JAN-08:50 | 15256.36 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 590.01 | 8395.84 | 01-JAN-08:50 | 46437.94 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 186.58 | 807.99 | 01-JAN-08:50 | 23674.41 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 186.58 | 807.99 | 01-JAN-08:50 | 23674.41 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 380.92 | 5410.48 | 01-JAN-09:50 | 29925.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 120.94 | 520.69 | 01-JAN-09:50 | 15256.36 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 120.94 | 520.69 | 01-JAN-09:50 | 15256.36 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 59.19 | 839.57 | 01-JAN-09:50 | 4643.71 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.85 | 80.80 | 01-JAN-09:50 | 2367.39 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.85 | 80.80 | 01-JAN-09:50 | 2367.39 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 38.07 | 541.05 | 01-JAN-08:50 | 2992.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.07 | 52.07 | 01-JAN-08:50 | 1525.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.07 | 52.07 | 01-JAN-08:50 | 1525.64 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 59.00 | 839.58 | 01-JAN-08:50 | 4643.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.66 | 80.80 | 01-JAN-08:50 | 2367.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.66 | 80.80 | 01-JAN-08:50 | 2367.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 38.09 | 541.05 | 01-JAN-09:50 | 2992.57 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 12.09 | 52.07 | 01-JAN-09:50 | 1525.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 12.09 | 52.07 | 01-JAN-09:50 | 1525.64 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7562.65 | 95237.01 | 01-JAN-00:10 | 385552.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1598.46 | 19775.43 | 01-JAN-00:10 | 83152.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1722.83 | 5114.07 | 10-JAN-22:10 | 451081.94 | 07-SEP-15:00 |
HeatRejection:Electricity | 812.86 | 1248.20 | 10-JAN-22:00 | 81829.93 | 06-JUN-14:40 |
General:HeatRejection:Electricity | 812.86 | 1248.20 | 10-JAN-22:00 | 81829.93 | 06-JUN-14:40 |
Electricity:HVAC | 6344.44 | 96746.72 | 09-JAN-24:00 | 529435.95 | 11-AUG-15:30 |
ExteriorEquipment:Electricity | 1941.94 | 28795.69 | 01-JAN-00:10 | 118959.22 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.33 | 1613.62 | 01-JAN-00:10 | 5481.25 | 01-DEC-16:50 |
ElectricityPurchased:Facility | 29517.66 | 391545.11 | 29-JAN-11:30 | 2076655.13 | 07-AUG-15:40 |
ElectricityPurchased:Plant | 29517.66 | 391545.11 | 29-JAN-11:30 | 2076655.13 | 07-AUG-15:40 |
Cogeneration:ElectricityPurchased | 29517.66 | 391545.11 | 29-JAN-11:30 | 2076655.13 | 07-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 29517.66 | 391545.11 | 29-JAN-11:30 | 2076655.13 | 07-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 29517.66 | 391545.11 | 29-JAN-11:30 | 2076655.13 | 07-AUG-15:40 |
ElectricityNet:Plant | 29517.66 | 391545.11 | 29-JAN-11:30 | 2076655.13 | 07-AUG-15:40 |
Cogeneration:ElectricityNet | 29517.66 | 391545.11 | 29-JAN-11:30 | 2076655.13 | 07-AUG-15:40 |
General:Cogeneration:ElectricityNet | 29517.66 | 391545.11 | 29-JAN-11:30 | 2076655.13 | 07-AUG-15:40 |
Fans:Electricity | 2703.50 | 47733.78 | 26-JAN-22:10 | 324151.01 | 17-JUL-15:20 |
General:Fans:Electricity | 2703.50 | 47733.78 | 26-JAN-22:10 | 324151.01 | 17-JUL-15:20 |
ExteriorLights:Electricity | 671.16 | 0.00 | 01-JAN-08:20 | 54335.80 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 671.16 | 0.00 | 01-JAN-08:20 | 54335.80 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 3205.79 | 30232.37 | 09-JAN-07:10 | 426109.78 | 07-AUG-15:40 |
General:Cooling:Electricity | 3205.79 | 30232.37 | 09-JAN-07:10 | 426109.78 | 07-AUG-15:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 840.82 | 0.00 | 13-JUL-15:20 | 52016.10 | 28-DEC-19:00 |
General:Humidifier:Electricity | 840.82 | 0.00 | 13-JUL-15:20 | 52016.10 | 28-DEC-19:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 416.96 | 3665.37 | 01-JAN-00:10 | 56384.85 | 05-SEP-12:30 |
General:Pumps:Electricity | 416.96 | 3665.37 | 01-JAN-00:10 | 56384.85 | 05-SEP-12:30 |
WIRED_LTG_ELECTRICITY | 104.28 | 0.00 | 01-JAN-00:10 | 9915.18 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4169.09 | 5695.87 | 05-JAN-22:20 | 2312600.18 | 09-JAN-07:20 |
NaturalGas:Plant | 4169.09 | 5695.87 | 05-JAN-22:20 | 2312600.18 | 09-JAN-07:20 |
Heating:NaturalGas | 3397.54 | 0.00 | 01-JAN-00:10 | 2290324.49 | 09-JAN-07:10 |
Boiler:Heating:NaturalGas | 3397.54 | 0.00 | 01-JAN-00:10 | 2290324.49 | 09-JAN-07:10 |
WaterSystems:NaturalGas | 771.55 | 5695.87 | 05-JAN-22:20 | 85520.85 | 22-FEB-12:20 |
Water Heater:WaterSystems:NaturalGas | 771.55 | 5695.87 | 05-JAN-22:20 | 85520.85 | 22-FEB-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 16931.41 | 147152.11 | 09-JAN-07:10 | 2471253.92 | 07-SEP-15:00 |
PlantLoopCoolingDemand:HVAC | 16931.41 | 147152.11 | 09-JAN-07:10 | 2471253.92 | 07-SEP-15:00 |
CoolingCoils:PlantLoopCoolingDemand | 16931.41 | 147152.11 | 09-JAN-07:10 | 2471253.92 | 07-SEP-15:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 5781.45 | 0.00 | 31-AUG-23:20 | 0.00 | 25-JUL-11:50 |
Water:HVAC | 312.78 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
Humidifier:Water | 312.78 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
General:Humidifier:Water | 312.78 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
MainsWater:Facility | 5781.45 | 0.00 | 31-AUG-23:20 | 0.00 | 25-JUL-11:50 |
MainsWater:HVAC | 312.78 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
Humidifier:MainsWater | 312.78 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
General:Humidifier:MainsWater | 312.78 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
Water:Plant | 5468.66 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-11:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5468.66 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-11:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3188.49 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
General:HeatRejection:Water | 3188.49 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
HeatRejection:MainsWater | 3188.49 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
General:HeatRejection:MainsWater | 3188.49 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 49396.79 | 231196.80 | 12-JAN-03:40 | 10652464.62 | 07-SEP-15:00 |
EnergyTransfer:Building | 18690.04 | 87829.22 | 12-JAN-22:50 | 1727997.00 | 07-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 670.59 | 0.00 | 01-JAN-00:40 | 68683.10 | 07-AUG-05:10 |
Heating:EnergyTransfer | 917.23 | 0.00 | 13-JAN-22:10 | 1231218.64 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.28 | 0.00 | 01-JAN-00:40 | 21884.35 | 05-AUG-16:10 |
General:Heating:EnergyTransfer | 917.23 | 0.00 | 13-JAN-22:10 | 1231218.64 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.28 | 0.00 | 01-JAN-00:40 | 21884.35 | 05-AUG-16:10 |
Cooling:EnergyTransfer | 17772.81 | 83739.68 | 30-JAN-06:00 | 1727997.00 | 07-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 667.31 | 0.00 | 01-JAN-00:10 | 68683.10 | 07-AUG-05:10 |
General:Cooling:EnergyTransfer | 17772.81 | 83739.68 | 30-JAN-06:00 | 1727997.00 | 07-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 667.31 | 0.00 | 01-JAN-00:10 | 68683.10 | 07-AUG-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 602.48 | 0.00 | 01-JAN-00:10 | 56893.70 | 07-AUG-10:40 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 602.48 | 0.00 | 01-JAN-00:10 | 56893.70 | 07-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 602.48 | 0.00 | 01-JAN-00:10 | 56893.70 | 07-AUG-10:40 |
EnergyTransfer:Zone:CORE_MID | 4232.45 | 0.00 | 01-JAN-00:10 | 452872.44 | 05-SEP-14:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 7.07 | 0.00 | 01-JAN-00:10 | 327105.08 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 7.07 | 0.00 | 01-JAN-00:10 | 327105.08 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4225.38 | 0.00 | 01-JAN-00:10 | 452872.44 | 05-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4225.38 | 0.00 | 01-JAN-00:10 | 452872.44 | 05-SEP-14:00 |
EnergyTransfer:Zone:CORE_TOP | 375.39 | 0.00 | 01-JAN-00:10 | 70755.77 | 06-MAR-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 19.86 | 0.00 | 01-JAN-00:10 | 70755.77 | 06-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 19.86 | 0.00 | 01-JAN-00:10 | 70755.77 | 06-MAR-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 355.53 | 0.00 | 01-JAN-00:10 | 53857.27 | 17-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 355.53 | 0.00 | 01-JAN-00:10 | 53857.27 | 17-JUL-15:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 66.94 | 0.00 | 01-JAN-00:10 | 12271.87 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.96 | 0.00 | 01-JAN-00:10 | 12271.87 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.96 | 0.00 | 01-JAN-00:10 | 12271.87 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 63.97 | 0.00 | 01-JAN-00:10 | 10242.13 | 09-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 63.97 | 0.00 | 01-JAN-00:10 | 10242.13 | 09-AUG-14:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 69.84 | 0.00 | 01-JAN-00:10 | 14178.34 | 07-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.20 | 0.00 | 01-JAN-00:10 | 9809.64 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.20 | 0.00 | 01-JAN-00:10 | 9809.64 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.64 | 0.00 | 01-JAN-00:10 | 14178.34 | 07-AUG-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.64 | 0.00 | 01-JAN-00:10 | 14178.34 | 07-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 112.67 | 0.00 | 01-JAN-00:10 | 20393.87 | 18-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.11 | 0.00 | 01-JAN-00:10 | 15492.87 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.11 | 0.00 | 01-JAN-00:10 | 15492.87 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 109.56 | 0.00 | 01-JAN-00:10 | 20393.87 | 18-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 109.56 | 0.00 | 01-JAN-00:10 | 20393.87 | 18-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 99.67 | 0.00 | 01-JAN-00:10 | 18205.43 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.65 | 0.00 | 01-JAN-00:10 | 7224.16 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.65 | 0.00 | 01-JAN-00:10 | 7224.16 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 99.02 | 0.00 | 01-JAN-00:10 | 18205.43 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 99.02 | 0.00 | 01-JAN-00:10 | 18205.43 | 07-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 592.07 | 0.00 | 01-JAN-00:10 | 134098.08 | 30-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 192.23 | 0.00 | 01-JAN-00:10 | 134098.08 | 30-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 192.23 | 0.00 | 01-JAN-00:10 | 134098.08 | 30-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 399.84 | 0.00 | 01-JAN-00:10 | 93956.75 | 18-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 399.84 | 0.00 | 01-JAN-00:10 | 93956.75 | 18-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 642.82 | 0.00 | 01-JAN-00:10 | 150089.92 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 114.31 | 0.00 | 01-JAN-00:10 | 150089.92 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 114.31 | 0.00 | 01-JAN-00:10 | 150089.92 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 528.51 | 0.00 | 01-JAN-00:10 | 146905.52 | 07-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 528.51 | 0.00 | 01-JAN-00:10 | 146905.52 | 07-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1021.56 | 0.00 | 01-JAN-00:10 | 210798.97 | 18-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 114.30 | 0.00 | 01-JAN-00:10 | 193215.25 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 114.30 | 0.00 | 01-JAN-00:10 | 193215.25 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 907.26 | 0.00 | 01-JAN-00:10 | 210798.97 | 18-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 907.26 | 0.00 | 01-JAN-00:10 | 210798.97 | 18-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 643.70 | 0.00 | 01-JAN-00:10 | 154609.04 | 17-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 92.07 | 0.00 | 01-JAN-00:10 | 142272.78 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 92.07 | 0.00 | 01-JAN-00:10 | 142272.78 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 551.64 | 0.00 | 01-JAN-00:10 | 154609.04 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 551.64 | 0.00 | 01-JAN-00:10 | 154609.04 | 17-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 84.72 | 0.00 | 01-JAN-00:10 | 17480.01 | 30-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 47.88 | 0.00 | 01-JAN-00:10 | 17480.01 | 30-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 47.88 | 0.00 | 01-JAN-00:10 | 17480.01 | 30-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.84 | 0.00 | 01-JAN-00:10 | 10672.55 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.84 | 0.00 | 01-JAN-00:10 | 10672.55 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 75.10 | 0.00 | 01-JAN-00:10 | 17014.93 | 30-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 27.67 | 0.00 | 01-JAN-00:10 | 17014.93 | 30-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 27.67 | 0.00 | 01-JAN-00:10 | 17014.93 | 30-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.43 | 0.00 | 01-JAN-00:10 | 14917.11 | 07-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.43 | 0.00 | 01-JAN-00:10 | 14917.11 | 07-AUG-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 112.61 | 0.00 | 01-JAN-00:10 | 22413.48 | 30-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 31.76 | 0.00 | 01-JAN-00:10 | 22413.48 | 30-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 31.76 | 0.00 | 01-JAN-00:10 | 22413.48 | 30-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 80.85 | 0.00 | 01-JAN-00:10 | 22189.94 | 01-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 80.85 | 0.00 | 01-JAN-00:10 | 22189.94 | 01-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 73.04 | 0.00 | 01-JAN-00:10 | 17963.58 | 30-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.12 | 0.00 | 01-JAN-00:10 | 17963.58 | 30-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.12 | 0.00 | 01-JAN-00:10 | 17963.58 | 30-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 49.92 | 0.00 | 01-JAN-00:10 | 16369.87 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 49.92 | 0.00 | 01-JAN-00:10 | 16369.87 | 17-JUL-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 58.72 | 0.00 | 01-JAN-00:10 | 10314.63 | 07-AUG-15:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.81 | 0.00 | 01-JAN-00:10 | 6604.73 | 30-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.81 | 0.00 | 01-JAN-00:10 | 6604.73 | 30-JAN-13:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 53.91 | 0.00 | 01-JAN-00:10 | 10314.63 | 07-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 53.91 | 0.00 | 01-JAN-00:10 | 10314.63 | 07-AUG-15:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 488.43 | 0.00 | 01-JAN-00:10 | 118583.78 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 150.19 | 0.00 | 01-JAN-00:10 | 118583.78 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 150.19 | 0.00 | 01-JAN-00:10 | 118583.78 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 338.25 | 0.00 | 01-JAN-00:10 | 81563.23 | 07-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 338.25 | 0.00 | 01-JAN-00:10 | 81563.23 | 07-AUG-15:40 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 120.67 | 0.00 | 01-JAN-00:10 | 33742.90 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 72.91 | 0.00 | 01-JAN-00:10 | 33742.90 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 72.91 | 0.00 | 01-JAN-00:10 | 33742.90 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 47.75 | 0.00 | 01-JAN-00:10 | 22981.96 | 17-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 47.75 | 0.00 | 01-JAN-00:10 | 22981.96 | 17-JUL-15:00 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.49 | 6.23 | 29-JAN-13:50 | 8260.85 | 03-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.07 | 0.00 | 01-JAN-00:10 | 639.67 | 09-JAN-03:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.07 | 0.00 | 01-JAN-00:10 | 639.67 | 09-JAN-03:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.43 | 0.00 | 07-JAN-23:50 | 8260.85 | 03-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.43 | 0.00 | 07-JAN-23:50 | 8260.85 | 03-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1154.23 | 1.46 | 11-JAN-09:40 | 78941.18 | 03-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.66 | 0.00 | 01-JAN-15:40 | 6600.97 | 29-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.66 | 0.00 | 01-JAN-15:40 | 6600.97 | 29-JAN-17:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1148.57 | 0.00 | 01-JAN-00:10 | 78941.18 | 03-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1148.57 | 0.00 | 01-JAN-00:10 | 78941.18 | 03-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 104.06 | 1.29 | 18-JAN-11:50 | 7964.13 | 03-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.13 | 0.00 | 02-JAN-13:10 | 769.93 | 30-APR-23:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.13 | 0.00 | 02-JAN-13:10 | 769.93 | 30-APR-23:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 102.94 | 0.00 | 01-JAN-00:10 | 7964.13 | 03-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 102.94 | 0.00 | 01-JAN-00:10 | 7964.13 | 03-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7152.79 | 83131.18 | 09-JAN-05:00 | 369517.19 | 22-AUG-07:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7152.79 | 83131.18 | 09-JAN-05:00 | 369517.19 | 22-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7152.79 | 83131.18 | 09-JAN-05:00 | 369517.19 | 22-AUG-07:20 |
PlantLoopHeatingDemand:Facility | 3108.81 | 0.00 | 01-JAN-00:10 | 1964863.02 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 463.31 | 0.00 | 01-JAN-00:10 | 57404.05 | 17-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 463.31 | 0.00 | 01-JAN-00:10 | 57404.05 | 17-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 463.31 | 0.00 | 01-JAN-00:10 | 57404.05 | 17-FEB-12:50 |
EnergyTransfer:HVAC | 16864.12 | 138091.57 | 09-JAN-24:00 | 2413942.03 | 07-SEP-15:00 |
HeatingCoils:EnergyTransfer | 2645.50 | 0.00 | 01-JAN-00:10 | 1946247.42 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 2645.50 | 0.00 | 01-JAN-00:10 | 1946247.42 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 2645.50 | 0.00 | 01-JAN-00:10 | 1946247.42 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 14218.62 | 116919.74 | 09-JAN-07:10 | 2413942.03 | 07-SEP-15:00 |
EnergyTransfer:Plant | 13842.63 | 0.00 | 01-JAN-00:10 | 7073192.29 | 07-SEP-15:00 |
LoopToLoop:EnergyTransfer | 3610.52 | -1630.93 | 25-FEB-14:00 | 2248126.37 | 07-SEP-15:00 |
WaterSystems:EnergyTransfer | 463.31 | 0.00 | 01-JAN-00:10 | 57404.05 | 17-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 463.31 | 0.00 | 01-JAN-00:10 | 57404.05 | 17-FEB-12:50 |
Boilers:EnergyTransfer | 2622.30 | 0.00 | 01-JAN-00:10 | 1905651.34 | 09-JAN-07:10 |
Chillers:EnergyTransfer | 3326.75 | 0.00 | 01-JAN-00:10 | 2241912.80 | 07-SEP-15:00 |
HeatRejection:EnergyTransfer | 3819.75 | 0.00 | 01-JAN-00:10 | 2557070.85 | 07-SEP-15:00 |
General:HeatRejection:EnergyTransfer | 3819.75 | 0.00 | 01-JAN-00:10 | 2557070.85 | 07-SEP-15:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.280 | -667.311 | 0.000 | 0.000 | 93.213 | 240.449 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -94.028 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -602.483 | 0.000 | 0.000 | 83.580 | 215.940 | 321.286 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -18.323 |
CORE_MID | 0.000 | 0.000 | 7.071 | -4225.364 | 0.000 | 0.000 | 850.980 | 2159.397 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -2004.930 |
CORE_TOP | 0.000 | 0.000 | 19.862 | -355.524 | 0.000 | 0.000 | 88.526 | 215.940 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -290.088 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.963 | -63.972 | 0.000 | 0.000 | 11.049 | 18.834 | 40.342 | 22.612 | 0.000 | 0.090 | 40.637 | 0.000 | -62.221 | 0.000 | -10.335 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.204 | -67.635 | 0.000 | 0.000 | 7.243 | 12.070 | 25.998 | 52.582 | 0.000 | 0.064 | 12.187 | 0.000 | -37.950 | 0.000 | -6.763 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 3.107 | -109.564 | 0.000 | 0.000 | 11.021 | 18.648 | 40.343 | 113.839 | 0.000 | 0.087 | 0.000 | 0.000 | -56.449 | 0.000 | -10.362 | -10.670 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.646 | -99.019 | 0.000 | 0.000 | 7.097 | 12.090 | 25.998 | 49.201 | 0.000 | 0.057 | 54.553 | 0.000 | -43.256 | 0.000 | -7.368 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 192.228 | -399.840 | 0.000 | 0.000 | 115.753 | 188.522 | 403.423 | 237.170 | 0.000 | 2.141 | 46.456 | 0.000 | -570.411 | 0.000 | -215.441 | -0.014 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 114.308 | -528.513 | 0.000 | 0.000 | 54.926 | 120.744 | 259.981 | 529.304 | 0.000 | 1.424 | 0.001 | 0.000 | -357.727 | 0.000 | -145.618 | -48.829 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 114.300 | -907.254 | 0.000 | 0.000 | 112.614 | 186.584 | 403.429 | 1137.375 | 0.000 | 1.958 | 0.056 | 0.000 | -545.831 | 0.000 | -229.481 | -273.694 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 92.066 | -551.632 | 0.000 | 0.000 | 75.504 | 120.938 | 259.979 | 505.300 | 0.000 | 1.406 | 30.234 | 0.000 | -384.724 | 0.000 | -149.072 | -0.021 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 47.883 | -36.838 | 0.000 | 0.000 | 11.832 | 18.852 | 40.342 | 24.476 | 0.000 | 0.269 | 0.001 | 0.000 | -53.881 | 0.000 | -25.116 | -27.821 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 27.669 | -47.428 | 0.000 | 0.000 | 7.527 | 12.075 | 25.998 | 53.361 | 0.000 | 0.167 | 0.000 | 0.000 | -34.059 | 0.000 | -17.115 | -28.195 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 31.757 | -80.854 | 0.000 | 0.000 | 11.482 | 18.659 | 40.343 | 114.561 | 0.000 | 0.236 | 0.001 | 0.000 | -51.663 | 0.000 | -26.708 | -57.811 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 23.123 | -49.918 | 0.000 | 0.000 | 7.644 | 12.094 | 25.998 | 50.829 | 0.000 | 0.172 | 0.001 | 0.000 | -36.733 | 0.000 | -17.564 | -15.645 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.066 | -135.425 | 0.000 | 0.000 | 0.950 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -25.436 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 5.664 | -1148.566 | 0.000 | 0.000 | 9.519 | 59.652 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -465.074 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.127 | -102.935 | 0.000 | 0.000 | 0.957 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -58.995 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7152.792 | 0.000 | 0.000 | 20.234 | 67.796 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -430.095 |
GROUNDFLOOR_PLENUM | 4.807 | -53.914 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.161 | 70.933 | 0.000 | 0.000 | 0.000 | -21.986 | 0.000 |
MIDFLOOR_PLENUM | 150.190 | -338.247 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.967 | 556.068 | 0.000 | 0.000 | 0.000 | -370.978 | -0.006 |
TOPFLOOR_PLENUM | 72.915 | -47.751 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.264 | 13.412 | 0.000 | 0.000 | 0.000 | -38.840 | -0.001 |
Total Facility | 227.912 | -439.912 | 689.324 | -17332.866 | 0.000 | 0.000 | 1581.653 | 3711.212 | 15213.411 | 2890.610 | 0.000 | 11.462 | 824.544 | 0.000 | -2234.906 | 0.000 | -1292.747 | -3849.677 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-SEP-03:02 | 0.00 | 0.00 | 0.00 | -115332.94 | 0.00 | 0.00 | 0.00 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 100708.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 11-SEP-03:02 | 0.00 | 0.00 | 0.00 | -95351.91 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.15 | 0.00 | 0.00 | 0.00 | 86247.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-AUG-03:02 | 0.00 | 0.00 | 0.00 | -861736.68 | 0.00 | 0.00 | 0.00 | 10475.32 | 80571.20 | 0.00 | 0.00 | 0.00 | 770690.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-JUN-03:02 | 0.00 | 0.00 | 0.00 | -83024.04 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.12 | 0.00 | 0.00 | 0.00 | 73919.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-SEP-16:01 | 0.00 | 0.00 | 0.00 | -15721.96 | 0.00 | 0.00 | 44.68 | 80.80 | 758.77 | 2848.56 | 0.00 | 110.70 | 11878.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-08:42 | 0.00 | 0.00 | 0.00 | -21612.78 | 0.00 | 0.00 | 21.83 | 52.07 | 488.98 | 13376.05 | 0.00 | 0.00 | 7702.15 | 0.00 | -0.00 | 0.00 | -28.30 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-12:31 | 0.00 | 0.00 | 0.00 | -28546.53 | 0.00 | 0.00 | 33.06 | 80.80 | 758.78 | 29220.34 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -418.95 | -1127.51 |
PERIMETER_BOT_ZN_4 | 04-SEP-16:01 | 0.00 | 0.00 | 0.00 | -28775.45 | 0.00 | 0.00 | 18.07 | 52.07 | 488.98 | 17088.17 | 0.00 | 43.42 | 11084.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-18:31 | 0.00 | 0.00 | 0.00 | -150584.09 | 0.00 | 0.00 | 0.00 | 807.98 | 7587.73 | 59734.95 | 0.00 | 2112.97 | 80340.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-09:21 | 0.00 | 0.00 | 0.00 | -251010.34 | 0.00 | 0.00 | 181.20 | 520.69 | 4889.82 | 164071.53 | 0.00 | 0.00 | 81748.57 | 0.00 | -0.00 | 0.00 | -401.47 | 0.00 |
PERIMETER_MID_ZN_1 | 03-SEP-12:41 | 0.00 | 0.00 | 0.00 | -307321.30 | 0.00 | 0.00 | 280.74 | 807.99 | 7587.84 | 241776.23 | 0.00 | 3813.82 | 53054.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 16-JUL-17:11 | 0.00 | 0.00 | 0.00 | -276626.08 | 0.00 | 0.00 | 0.00 | 520.69 | 4889.79 | 185025.58 | 0.00 | 668.45 | 85521.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 06-AUG-16:11 | 0.00 | 0.00 | 0.00 | -19337.43 | 0.00 | 0.00 | 41.70 | 80.80 | 758.77 | 3798.83 | 0.00 | 739.69 | 13917.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-08:11 | 0.00 | 0.00 | 0.00 | -24302.50 | 0.00 | 0.00 | 19.70 | 52.07 | 488.98 | 19000.82 | 0.00 | 0.00 | 4892.10 | 0.00 | -0.00 | 0.00 | -151.18 | 0.00 |
PERIMETER_TOP_ZN_1 | 06-AUG-14:11 | 0.00 | 0.00 | 0.00 | -30913.93 | 0.00 | 0.00 | 30.91 | 80.80 | 758.78 | 15032.48 | 0.00 | 439.13 | 14571.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 06-AUG-16:11 | 0.00 | 0.00 | 0.00 | -28605.90 | 0.00 | 0.00 | 16.61 | 52.07 | 488.98 | 16858.90 | 0.00 | 335.11 | 10854.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 03-AUG-18:50 | 0.00 | 0.00 | 0.00 | -8260.54 | 0.00 | 0.00 | 10.53 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 281.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-AUG-18:50 | 0.00 | 0.00 | 0.00 | -78938.17 | 0.00 | 0.00 | 106.08 | 1736.14 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -848.26 |
DATACENTER_TOP_ZN_6 | 03-AUG-18:40 | 0.00 | 0.00 | 0.00 | -7963.81 | 0.00 | 0.00 | 10.62 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14.84 |
DATACENTER_BASEMENT_ZN_6 | 22-AUG-07:20 | 0.00 | 0.00 | 0.00 | -369522.43 | 0.00 | 0.00 | 2182.56 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18212.24 |
GROUNDFLOOR_PLENUM | 17-JUL-05:15 | 0.00 | -11926.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11972.87 | 0.00 | -0.00 | 0.00 | -46.71 | 0.00 |
MIDFLOOR_PLENUM | 04-MAR-04:01 | 0.00 | -111795.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143402.99 | 0.00 | -0.00 | 0.00 | -31607.24 | 0.00 |
TOPFLOOR_PLENUM | 17-JUL-15:00 | 0.00 | -22981.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22981.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-03:02 | 0.00 | 73527.95 | 0.00 | -1964195.45 | 0.00 | 0.00 | 0.00 | 19603.93 | 623236.89 | 0.00 | 0.00 | 0.00 | 1318557.34 | 0.00 | -52668.48 | 0.00 | -18062.18 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-AUG-16:01 | 0.00 | 0.00 | 23292.41 | 0.00 | 0.00 | 0.00 | 520.12 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -38436.51 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 09-JAN-05:01 | 0.00 | 0.00 | 540347.65 | 0.00 | 0.00 | 0.00 | 0.00 | 20950.64 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -641869.49 |
CORE_TOP | 09-JAN-04:01 | 0.00 | 0.00 | 80080.83 | 0.00 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -89185.48 |
PERIMETER_BOT_ZN_3 | 09-JAN-04:01 | 0.00 | 0.00 | 13736.79 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6558.91 | 0.00 | -842.57 | -7478.53 |
PERIMETER_BOT_ZN_2 | 09-JAN-04:01 | 0.00 | 0.00 | 15441.51 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4357.86 | 0.00 | -565.77 | -11254.61 |
PERIMETER_BOT_ZN_1 | 09-JAN-04:01 | 0.00 | 0.00 | 21401.51 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6327.92 | 0.00 | -846.47 | -15370.37 |
PERIMETER_BOT_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 13947.66 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4380.95 | 0.00 | -575.86 | -9727.57 |
PERIMETER_MID_ZN_3 | 30-JAN-04:11 | 0.00 | 0.00 | 144418.85 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.28 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -49409.72 | 0.00 | -30977.36 | -75464.02 |
PERIMETER_MID_ZN_2 | 30-JAN-04:11 | 0.00 | 0.00 | 195879.85 | 0.00 | 0.00 | 0.00 | 0.00 | 847.62 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33029.84 | 0.00 | -21026.06 | -149191.32 |
PERIMETER_MID_ZN_1 | 09-JAN-03:02 | 0.00 | 0.00 | 235136.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.31 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -61493.19 | 0.00 | -24945.13 | -160130.93 |
PERIMETER_MID_ZN_4 | 30-JAN-04:11 | 0.00 | 0.00 | 207502.17 | 0.00 | 0.00 | 0.00 | 0.00 | 847.62 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34472.27 | 0.00 | -21291.15 | -159106.09 |
PERIMETER_TOP_ZN_3 | 30-JAN-05:21 | 0.00 | 0.00 | 18996.04 | 0.00 | 0.00 | 0.00 | 0.00 | 263.06 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4622.18 | 0.00 | -3791.13 | -11857.47 |
PERIMETER_TOP_ZN_2 | 31-DEC-03:41 | 0.00 | 0.00 | 19953.44 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4039.59 | 0.00 | -2009.11 | -14478.49 |
PERIMETER_TOP_ZN_1 | 31-DEC-03:41 | 0.00 | 0.00 | 25934.66 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 758.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5908.71 | 0.00 | -3017.10 | -17899.16 |
PERIMETER_TOP_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 22214.51 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3948.90 | 0.00 | -1568.11 | -17434.24 |
DATACENTER_BOT_ZN_6 | 09-JAN-03:44 | 0.00 | 0.00 | 640.39 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2617.93 |
DATACENTER_MID_ZN_6 | 29-JAN-17:50 | 0.00 | 0.00 | 6628.76 | 0.00 | 0.00 | 0.00 | 54.13 | 289.38 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26458.32 |
DATACENTER_TOP_ZN_6 | 30-APR-23:05 | 0.00 | 0.00 | 778.84 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2756.38 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 19-DEC-05:01 | 14977.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1833.38 | -13144.14 |
MIDFLOOR_PLENUM | 09-JAN-06:12 | 144208.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -8452.67 | -135756.26 |
TOPFLOOR_PLENUM | 11-JAN-05:12 | 35014.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1465.21 | -33549.55 |
Total Facility | 30-JAN-05:01 | -5100.34 | 96520.32 | 1415958.07 | -96520.32 | 0.00 | 0.00 | 0.00 | 39207.80 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -210490.82 | 0.00 | -206307.45 | -1301629.96 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.5879 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.9284 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 120.3972 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 101.2491 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.3378 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.3018 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.4741 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.4741 | 0.1854 | 1.0000 | Not calculated | 1.2002 | 0.1854 | ||
AIRLOOP DATACENTER BASEMENT | 24.4712 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.4714 | 0.0138 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.5700 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5700 | 0.0274 | 1.0000 | Not calculated | 0.0156 | 0.0274 | ||
AIRLOOP DATACENTER MID | 5.4580 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.4580 | 0.0286 | 1.0000 | Not calculated | 0.1563 | 0.0286 | ||
AIRLOOP DATACENTER TOP | 0.5556 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5556 | 0.0281 | 1.0000 | Not calculated | 0.0156 | 0.0281 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.2940 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.7764 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 60.1986 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 36.5663 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.1689 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.8621 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.4741 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.4741 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1854 | ||
AIRLOOP DATACENTER BASEMENT | 24.4712 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.4712 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.5700 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5700 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0274 | ||
AIRLOOP DATACENTER MID | 5.4580 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.4580 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0286 | ||
AIRLOOP DATACENTER TOP | 0.5556 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5556 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0281 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.4741 | 6.4741 | 6.4741 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7944 | 6.7944 | 2.0383 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 63.8726 | 63.8726 | 19.6089 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1821 | 6.1821 | 2.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0823 | 1.0823 | 0.3247 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3412 | 1.3412 | 0.4024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6974 | 1.6974 | 0.5092 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6726 | 1.6726 | 0.5018 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.1856 | 10.1856 | 3.0557 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.1044 | 14.1044 | 4.2313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.0701 | 17.0701 | 5.1210 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.1645 | 15.1645 | 4.5493 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2866 | 1.2866 | 0.3860 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4139 | 1.4139 | 0.4242 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8413 | 1.8413 | 0.5524 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6139 | 1.6139 | 0.4842 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5700 | 0.5700 | 0.5700 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4580 | 5.4580 | 5.4580 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5556 | 0.5556 | 0.5556 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.4712 | 24.4712 | 24.4712 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.5879 | 10.9284 | 12.5879 | 3.7764 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 120.3972 | 101.2491 | 120.3972 | 36.5663 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.3378 | 11.3018 | 12.3378 | 3.8621 | 0.0000 | 1.0000 |
CAV_BAS | 6.4741 | 6.4741 | 6.4741 | 6.4741 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.4712 | 24.4714 | 24.4712 | 24.4712 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5700 | 0.5700 | 0.5700 | 0.5700 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.4580 | 5.4580 | 5.4580 | 5.4580 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5556 | 0.5556 | 0.5556 | 0.5556 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.4741 | 6.4741 | 6.4741 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3972 | 3.3972 | 2.0383 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 31.9363 | 31.9363 | 19.6089 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0910 | 3.0910 | 2.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5412 | 0.5412 | 0.3247 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6706 | 0.6706 | 0.4024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8487 | 0.8487 | 0.5092 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8363 | 0.8363 | 0.5018 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0928 | 5.0928 | 3.0557 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0522 | 7.0522 | 4.2313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.5351 | 8.5351 | 5.1210 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5822 | 7.5822 | 4.5493 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6433 | 0.6433 | 0.3860 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7070 | 0.7070 | 0.4242 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9206 | 0.9206 | 0.5524 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8069 | 0.8069 | 0.4842 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5700 | 0.5700 | 0.5700 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4580 | 5.4580 | 5.4580 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5556 | 0.5556 | 0.5556 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.4712 | 24.4712 | 24.4712 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.2940 | 3.7764 | 3.7764 | 3.7764 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 60.1986 | 36.5663 | 36.5663 | 36.5663 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.1689 | 3.8621 | 3.8621 | 3.8621 | 0.0000 | 1.0000 |
CAV_BAS | 6.4741 | 6.4741 | 6.4741 | 6.4741 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.4712 | 24.4712 | 24.4712 | 24.4712 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5700 | 0.5700 | 0.5700 | 0.5700 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.4580 | 5.4580 | 5.4580 | 5.4580 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5556 | 0.5556 | 0.5556 | 0.5556 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 115.33 |
Number of hours cooling loads not met | 480.50 |
Number of hours not met | 595.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3397.54 | 2290324.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3205.79 | 426109.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3711.21 | 352853.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 671.16 | 54335.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.33 | 5481.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2703.50 | 324151.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 416.96 | 56384.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 812.86 | 81829.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 840.82 | 52016.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 771.55 | 85520.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 29517.66 |
Natural Gas | 0.00 | 4169.09 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 33686.75 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 80.12 |
Space Heating | 0.00 |
Space Cooling | 69.21 |
Fans (All) | 58.37 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 637.25 |
Subtotal | 637.25 |
Natural Gas [MJ/m2] | |
Space Heating | 73.35 |
Service Water Heating | 16.66 |
Miscellaneous (All) | 90.01 |
Subtotal | 90.01 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.02 |
Space Heating | 10.09 |
Space Cooling | 9.52 |
Fans (All) | 8.03 |
Service Water Heating | 2.29 |
Receptacle Equipment | 45.16 |
Miscellaneous | 13.90 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2645. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8718.67 | 41.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8746.83 | 13.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8747.67 | 12.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8699.00 | 61.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8741.00 | 19.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8738.83 | 21.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8205.33 | 554.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
Min | 8205.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 554.67 | 0.00 | 0.00 | 0.00 |
Average | 8723.99 | 36.01 | 0.00 | 0.00 | 0.00 |
Sum | 200651.67 | 828.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368438.67 | 177.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330793.00 | 20.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2265.50 | 2.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 95508.33 | 7886.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368438.67 | 7886.67 | 0.00 | 0.00 | 0.00 |
Average | 79983.33 | 351.59 | 0.00 | 0.00 | 0.00 |
Sum | 1839616.50 | 8086.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8685.33 | 74.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8725.33 | 34.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8720.00 | 40.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8733.17 | 26.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8744.33 | 15.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8708.83 | 51.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8751.17 | 8.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8743.17 | 16.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8734.67 | 25.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8751.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8742.67 | 17.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8743.33 | 16.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8735.17 | 24.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8394.50 | 365.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8745.17 | 14.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8721.33 | 38.67 | 0.00 | 0.00 | 0.00 |
Min | 8394.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 365.50 | 0.00 | 0.00 | 0.00 |
Average | 8723.88 | 36.12 | 0.00 | 0.00 | 0.00 |
Sum | 200649.33 | 830.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368336.17 | 279.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330734.00 | 79.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330707.00 | 106.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330757.00 | 56.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 98025.33 | 5369.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368336.17 | 5369.67 | 0.00 | 0.00 | 0.00 |
Average | 80078.80 | 256.11 | 0.00 | 0.00 | 0.00 |
Sum | 1841812.50 | 5890.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:16
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.483369E+11 | 109422.06 | 02-JAN-04:03 | -0.5 | -3.0 | 0.533861E+10 | 7499.16 | 12-JAN-10:09 | 6.78 | 3.19 |
February | 0.432255E+11 | 108714.50 | 27-FEB-04:02 | 4.82 | 0.54 | 0.503687E+10 | 7499.22 | 06-FEB-10:00 | 4.82 | 0.54 |
March | 0.534522E+11 | 109493.07 | 27-MAR-03:01 | 2.02 | -1.7 | 0.611548E+10 | 7499.21 | 01-MAR-10:09 | 2.02 | -1.7 |
April | 0.513995E+11 | 111076.76 | 24-APR-03:02 | 4.82 | 3.52 | 0.544567E+10 | 7499.19 | 04-APR-09:09 | 4.82 | 3.52 |
May | 0.543533E+11 | 111369.96 | 30-MAY-03:02 | 15.60 | 10.52 | 0.589965E+10 | 7499.77 | 02-MAY-13:20 | 15.60 | 10.52 |
June | 0.589045E+11 | 113748.30 | 05-JUN-03:02 | 8.62 | 5.44 | 0.588123E+10 | 7499.12 | 20-JUN-13:20 | 27.77 | 18.21 |
July | 0.612236E+11 | 114647.14 | 24-JUL-02:52 | 12.20 | 8.81 | 0.547408E+10 | 7499.22 | 03-JUL-13:09 | 12.20 | 8.81 |
August | 0.682817E+11 | 111020.31 | 28-AUG-03:02 | 9.90 | 5.61 | 0.613858E+10 | 7499.06 | 01-AUG-13:20 | 9.90 | 5.61 |
September | 0.589181E+11 | 115330.66 | 25-SEP-03:02 | 13.22 | 9.31 | 0.545243E+10 | 7499.35 | 07-SEP-09:00 | 13.22 | 9.31 |
October | 0.602410E+11 | 111018.82 | 23-OCT-03:02 | 8.98 | 3.95 | 0.567031E+10 | 7499.08 | 06-OCT-09:00 | 8.98 | 3.95 |
November | 0.557484E+11 | 113763.15 | 20-NOV-04:01 | -1.7 | -4.9 | 0.561261E+10 | 7499.08 | 03-NOV-09:20 | -1.7 | -4.9 |
December | 0.532276E+11 | 112017.84 | 11-DEC-04:01 | -2.6 | -4.7 | 0.540854E+10 | 7499.17 | 07-DEC-10:09 | -2.6 | -4.7 |
Annual Sum or Average | 0.667312E+12 | 0.674740E+11 | ||||||||
Minimum of Months | 0.432255E+11 | 108714.50 | -2.6 | -4.9 | 0.503687E+10 | 7499.06 | -2.6 | -4.9 | ||
Maximum of Months | 0.682817E+11 | 115330.66 | 15.60 | 10.52 | 0.613858E+10 | 7499.77 | 27.77 | 18.21 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316212E+11 | 85470.72 | 02-JAN-05:01 | -0.2 | -2.7 | 0.495077E+10 | 6734.75 | 02-JAN-10:09 | 2.48 | -0.4 |
February | 0.338215E+11 | 87271.24 | 28-FEB-05:01 | -3.4 | -4.0 | 0.457101E+10 | 6734.73 | 28-FEB-10:09 | 1.57 | -0.3 |
March | 0.474270E+11 | 87990.47 | 29-MAR-04:01 | -0.1 | -2.6 | 0.549132E+10 | 6734.78 | 01-MAR-10:09 | -0.1 | -2.6 |
April | 0.519398E+11 | 91365.05 | 10-APR-03:02 | 4.40 | 0.24 | 0.488335E+10 | 6734.79 | 04-APR-09:09 | 4.40 | 0.24 |
May | 0.489443E+11 | 94325.69 | 30-MAY-03:02 | 15.60 | 10.52 | 0.528951E+10 | 6735.16 | 02-MAY-13:09 | 15.60 | 10.52 |
June | 0.598851E+11 | 92244.87 | 05-JUN-03:02 | 8.62 | 5.44 | 0.526940E+10 | 6734.79 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.662231E+11 | 95202.99 | 05-JUL-03:02 | 9.90 | 9.28 | 0.489747E+10 | 6734.96 | 03-JUL-13:09 | 9.90 | 9.28 |
August | 0.743198E+11 | 91027.10 | 23-AUG-03:02 | 11.20 | 7.14 | 0.549787E+10 | 6734.79 | 01-AUG-13:09 | 11.20 | 7.14 |
September | 0.520086E+11 | 95353.02 | 11-SEP-03:02 | 11.10 | 10.41 | 0.488210E+10 | 6735.13 | 07-SEP-09:50 | 11.10 | 10.41 |
October | 0.497970E+11 | 90648.56 | 02-OCT-03:02 | 5.00 | 2.94 | 0.507958E+10 | 6734.74 | 27-OCT-09:20 | 8.13 | 3.61 |
November | 0.451588E+11 | 91324.31 | 06-NOV-04:02 | -2.8 | -3.9 | 0.502805E+10 | 6734.75 | 03-NOV-09:20 | -2.8 | -3.9 |
December | 0.413374E+11 | 88067.31 | 07-DEC-05:01 | -1.6 | -2.7 | 0.488809E+10 | 6734.78 | 07-DEC-10:09 | 3.35 | 1.22 |
Annual Sum or Average | 0.602484E+12 | 0.607285E+11 | ||||||||
Minimum of Months | 0.316212E+11 | 85470.72 | -3.4 | -4.0 | 0.457101E+10 | 6734.73 | -2.8 | -3.9 | ||
Maximum of Months | 0.743198E+11 | 95353.02 | 15.60 | 10.52 | 0.549787E+10 | 6735.16 | 27.48 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227886E+11 | 22197.39 | 05-JAN-17:00 | -20.0 | -20.5 | 0.453387E+10 | 6734.50 | 04-JAN-14:00 | -20.0 | -20.5 |
February | 0.227223E+11 | 32974.19 | 28-FEB-17:00 | 10.00 | 4.31 | 0.430103E+10 | 6734.74 | 28-FEB-10:09 | 10.00 | 4.31 |
March | 0.309130E+11 | 72251.87 | 30-MAR-05:02 | 0.00 | -2.1 | 0.532813E+10 | 6734.77 | 01-MAR-10:09 | 0.00 | -2.1 |
April | 0.329764E+11 | 79501.27 | 25-APR-05:02 | 1.10 | -0.7 | 0.483230E+10 | 6734.75 | 04-APR-09:09 | 1.10 | -0.7 |
May | 0.373035E+11 | 82557.55 | 30-MAY-03:02 | 15.60 | 10.52 | 0.525350E+10 | 6735.19 | 02-MAY-13:09 | 15.60 | 10.52 |
June | 0.470721E+11 | 82945.55 | 23-JUN-03:02 | 17.38 | 11.72 | 0.526088E+10 | 6734.81 | 20-JUN-13:09 | 17.38 | 11.72 |
July | 0.494647E+11 | 84115.05 | 19-JUL-03:02 | 21.02 | 16.34 | 0.489297E+10 | 6734.96 | 03-JUL-13:09 | 21.02 | 16.34 |
August | 0.514817E+11 | 86169.38 | 14-AUG-03:02 | 12.20 | 10.20 | 0.549501E+10 | 6734.80 | 01-AUG-13:09 | 12.20 | 10.20 |
September | 0.410082E+11 | 84765.63 | 11-SEP-03:02 | 11.10 | 10.41 | 0.486653E+10 | 6735.14 | 07-SEP-09:00 | 11.10 | 10.41 |
October | 0.340989E+11 | 77892.21 | 17-OCT-05:02 | 3.90 | 1.71 | 0.503328E+10 | 6734.73 | 27-OCT-09:20 | 8.13 | 3.61 |
November | 0.278594E+11 | 73286.14 | 08-NOV-06:02 | 10.13 | 4.88 | 0.486675E+10 | 6734.74 | 03-NOV-09:20 | 10.13 | 4.88 |
December | 0.248492E+11 | 28782.98 | 07-DEC-16:30 | 5.55 | 1.71 | 0.454622E+10 | 6734.76 | 07-DEC-10:09 | 5.55 | 1.71 |
Annual Sum or Average | 0.422538E+12 | 0.592105E+11 | ||||||||
Minimum of Months | 0.227223E+11 | 22197.39 | -20.0 | -20.5 | 0.430103E+10 | 6734.50 | -20.0 | -20.5 | ||
Maximum of Months | 0.514817E+11 | 86169.38 | 21.02 | 16.34 | 0.549501E+10 | 6735.19 | 21.02 | 16.34 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139895E+11 | 17269.51 | 13-JAN-17:00 | 7.80 | 3.93 | 0.396855E+10 | 6250.00 | 13-JAN-14:00 | 7.80 | 3.93 |
February | 0.162533E+11 | 25420.93 | 28-FEB-17:00 | 10.00 | 4.31 | 0.382337E+10 | 6734.33 | 28-FEB-14:00 | 10.00 | 4.31 |
March | 0.224858E+11 | 28756.00 | 23-MAR-15:40 | 7.40 | 0.85 | 0.487108E+10 | 6734.59 | 02-MAR-14:30 | 7.40 | 0.85 |
April | 0.259464E+11 | 42101.24 | 25-APR-16:00 | 17.80 | 7.70 | 0.459338E+10 | 6734.63 | 13-APR-13:00 | 17.80 | 7.70 |
May | 0.325175E+11 | 77318.18 | 20-MAY-05:02 | 11.47 | 8.41 | 0.506190E+10 | 6735.18 | 02-MAY-13:09 | 11.47 | 8.41 |
June | 0.460665E+11 | 83055.98 | 21-JUN-03:02 | 19.22 | 13.03 | 0.523545E+10 | 6734.77 | 20-JUN-13:00 | 19.22 | 13.03 |
July | 0.507598E+11 | 82170.91 | 19-JUL-03:02 | 21.02 | 16.34 | 0.488489E+10 | 6734.96 | 03-JUL-13:09 | 21.02 | 16.34 |
August | 0.503834E+11 | 81277.97 | 10-AUG-03:02 | 17.38 | 10.51 | 0.547944E+10 | 6734.78 | 01-AUG-13:09 | 17.38 | 10.51 |
September | 0.359145E+11 | 82121.42 | 05-SEP-03:02 | 18.30 | 12.34 | 0.476573E+10 | 6735.09 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.255535E+11 | 48080.75 | 19-OCT-05:03 | 12.20 | 5.54 | 0.474916E+10 | 6734.68 | 20-OCT-09:30 | 8.35 | 4.25 |
November | 0.196923E+11 | 27154.23 | 03-NOV-16:00 | 14.30 | 7.69 | 0.435755E+10 | 6734.45 | 17-NOV-14:00 | 16.50 | 8.23 |
December | 0.159645E+11 | 19521.72 | 06-DEC-17:00 | 6.70 | 2.38 | 0.399208E+10 | 6688.62 | 07-DEC-14:00 | 8.30 | 2.55 |
Annual Sum or Average | 0.355527E+12 | 0.557826E+11 | ||||||||
Minimum of Months | 0.139895E+11 | 17269.51 | 6.70 | 0.85 | 0.382337E+10 | 6250.00 | 7.40 | 0.85 | ||
Maximum of Months | 0.507598E+11 | 83055.98 | 21.02 | 16.34 | 0.547944E+10 | 6735.18 | 21.02 | 16.34 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142923E+10 | 3099.00 | 02-JAN-05:01 | -0.2 | -2.7 | 0.490361E+09 | 783.89 | 02-JAN-14:50 | 6.20 | 1.19 |
February | 0.222864E+10 | 3977.28 | 27-FEB-16:00 | 18.90 | 7.06 | 0.477128E+09 | 845.60 | 21-FEB-14:00 | 18.90 | 7.06 |
March | 0.372776E+10 | 4409.57 | 27-MAR-14:40 | 9.63 | 2.75 | 0.624067E+09 | 845.61 | 02-MAR-14:20 | 9.63 | 2.75 |
April | 0.492516E+10 | 6875.62 | 07-APR-14:30 | 22.50 | 9.29 | 0.589346E+09 | 845.62 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.553327E+10 | 12818.70 | 30-MAY-05:03 | 15.60 | 11.34 | 0.643051E+09 | 845.68 | 02-MAY-13:09 | 15.60 | 11.34 |
June | 0.873312E+10 | 12630.23 | 26-JUN-05:03 | 9.87 | 8.82 | 0.658928E+09 | 845.64 | 20-JUN-13:09 | 9.87 | 8.82 |
July | 0.105437E+11 | 12434.53 | 26-JUL-05:02 | 19.50 | 10.94 | 0.614691E+09 | 846.91 | 18-JUL-13:20 | 19.50 | 10.94 |
August | 0.104857E+11 | 12913.10 | 06-AUG-15:41 | 35.40 | 16.19 | 0.688922E+09 | 845.64 | 01-AUG-13:09 | 35.40 | 16.19 |
September | 0.597643E+10 | 15722.04 | 04-SEP-16:01 | 32.80 | 16.54 | 0.599638E+09 | 845.67 | 07-SEP-09:50 | 16.52 | 15.26 |
October | 0.449033E+10 | 5758.45 | 19-OCT-14:30 | 21.40 | 10.24 | 0.608455E+09 | 845.62 | 18-OCT-13:20 | 21.40 | 10.24 |
November | 0.339134E+10 | 4019.59 | 24-NOV-14:30 | 14.90 | 6.43 | 0.564161E+09 | 845.61 | 17-NOV-14:09 | 14.90 | 6.43 |
December | 0.250767E+10 | 3191.03 | 06-DEC-05:01 | 7.20 | 4.06 | 0.511399E+09 | 830.36 | 06-DEC-14:39 | 11.30 | 5.42 |
Annual Sum or Average | 0.639724E+11 | 0.707015E+10 | ||||||||
Minimum of Months | 0.142923E+10 | 3099.00 | -0.2 | -2.7 | 0.477128E+09 | 783.89 | 6.20 | 1.19 | ||
Maximum of Months | 0.105437E+11 | 15722.04 | 35.40 | 16.54 | 0.688922E+09 | 846.91 | 35.40 | 16.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146107E+10 | 3740.98 | 02-JAN-05:01 | -0.2 | -2.7 | 0.310655E+09 | 511.83 | 17-JAN-10:30 | 5.25 | 1.27 |
February | 0.243029E+10 | 6388.57 | 27-FEB-10:00 | 11.70 | 4.23 | 0.303144E+09 | 544.95 | 28-FEB-10:09 | 1.57 | -0.3 |
March | 0.419219E+10 | 8998.90 | 28-MAR-09:20 | 5.73 | 0.86 | 0.386615E+09 | 544.95 | 01-MAR-10:09 | 5.73 | 0.86 |
April | 0.554662E+10 | 11271.55 | 24-APR-08:30 | 10.30 | 6.86 | 0.363616E+09 | 544.95 | 25-APR-09:09 | 9.87 | 4.86 |
May | 0.632613E+10 | 11467.98 | 19-MAY-08:30 | 16.95 | 11.09 | 0.406852E+09 | 544.99 | 02-MAY-13:09 | 16.95 | 11.09 |
June | 0.906108E+10 | 21345.19 | 25-JUN-07:52 | 15.60 | 11.35 | 0.420817E+09 | 546.34 | 23-JUN-09:50 | 15.60 | 11.35 |
July | 0.109119E+11 | 20922.12 | 02-JUL-08:32 | 21.67 | 15.15 | 0.394291E+09 | 546.39 | 03-JUL-09:00 | 23.30 | 14.49 |
August | 0.105755E+11 | 20982.84 | 06-AUG-08:22 | 25.25 | 14.09 | 0.439550E+09 | 546.19 | 07-AUG-09:00 | 30.60 | 15.43 |
September | 0.659308E+10 | 21612.54 | 04-SEP-08:42 | 26.52 | 14.78 | 0.378475E+09 | 544.97 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.492595E+10 | 8583.53 | 18-OCT-09:20 | 18.13 | 8.00 | 0.378526E+09 | 544.95 | 16-OCT-09:09 | 18.13 | 8.00 |
November | 0.341907E+10 | 5880.64 | 06-NOV-09:35 | 1.20 | -1.1 | 0.341742E+09 | 544.95 | 03-NOV-09:20 | 1.20 | -1.1 |
December | 0.219249E+10 | 3620.85 | 01-DEC-06:02 | 1.70 | -2.2 | 0.309683E+09 | 513.62 | 20-DEC-10:30 | 3.85 | -0.4 |
Annual Sum or Average | 0.676353E+11 | 0.443397E+10 | ||||||||
Minimum of Months | 0.146107E+10 | 3620.85 | -0.2 | -2.7 | 0.303144E+09 | 511.83 | 1.20 | -1.1 | ||
Maximum of Months | 0.109119E+11 | 21612.54 | 26.52 | 15.15 | 0.439550E+09 | 546.39 | 30.60 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321116E+10 | 11419.37 | 19-JAN-13:30 | -6.2 | -7.9 | 0.519275E+09 | 845.64 | 31-JAN-14:20 | -0.8 | -4.4 |
February | 0.547852E+10 | 25758.13 | 26-FEB-14:02 | 15.78 | 5.88 | 0.512421E+09 | 847.27 | 27-FEB-14:39 | 18.70 | 7.17 |
March | 0.786447E+10 | 18751.34 | 01-MAR-13:40 | 6.33 | 2.52 | 0.623369E+09 | 847.97 | 23-MAR-13:00 | 10.00 | 2.51 |
April | 0.842445E+10 | 18544.08 | 16-APR-12:02 | 17.38 | 7.48 | 0.569363E+09 | 846.37 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.845513E+10 | 14809.00 | 19-MAY-13:30 | 26.65 | 14.96 | 0.622891E+09 | 845.71 | 02-MAY-13:09 | 26.65 | 14.96 |
June | 0.114272E+11 | 15479.01 | 25-JUN-15:12 | 24.80 | 13.02 | 0.649594E+09 | 845.68 | 19-JUN-13:30 | 24.80 | 13.02 |
July | 0.144730E+11 | 22873.94 | 16-JUL-15:22 | 33.05 | 18.62 | 0.611858E+09 | 846.60 | 14-JUL-13:00 | 33.05 | 18.62 |
August | 0.166138E+11 | 25917.72 | 06-AUG-13:42 | 34.32 | 15.27 | 0.684270E+09 | 848.46 | 22-AUG-13:50 | 24.13 | 15.51 |
September | 0.118259E+11 | 28169.66 | 04-SEP-15:21 | 32.50 | 16.58 | 0.592582E+09 | 846.76 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.993421E+10 | 28542.76 | 15-OCT-12:31 | 21.83 | 10.70 | 0.607568E+09 | 851.72 | 18-OCT-13:30 | 24.70 | 11.11 |
November | 0.703991E+10 | 22898.53 | 12-NOV-13:32 | -0.6 | -3.6 | 0.574276E+09 | 846.99 | 06-NOV-14:39 | -0.6 | -3.6 |
December | 0.481657E+10 | 13178.46 | 12-DEC-12:30 | -2.8 | -5.7 | 0.531271E+09 | 845.64 | 19-DEC-14:09 | 10.97 | 6.81 |
Annual Sum or Average | 0.109564E+12 | 0.709874E+10 | ||||||||
Minimum of Months | 0.321116E+10 | 11419.37 | -6.2 | -7.9 | 0.512421E+09 | 845.64 | -0.8 | -4.4 | ||
Maximum of Months | 0.166138E+11 | 28542.76 | 34.32 | 18.62 | 0.684270E+09 | 851.72 | 33.05 | 18.62 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248505E+10 | 4895.35 | 02-JAN-05:01 | -0.2 | -2.7 | 0.314418E+09 | 521.79 | 02-JAN-14:00 | 6.10 | 1.11 |
February | 0.426120E+10 | 9917.43 | 28-FEB-16:40 | 10.37 | 4.49 | 0.314936E+09 | 544.93 | 27-FEB-14:00 | 10.37 | 4.49 |
March | 0.676626E+10 | 12444.23 | 28-MAR-16:00 | 10.60 | 3.09 | 0.409165E+09 | 544.95 | 14-MAR-13:00 | 10.60 | 3.09 |
April | 0.883160E+10 | 25973.33 | 16-APR-17:22 | 19.70 | 8.86 | 0.386872E+09 | 544.96 | 13-APR-13:00 | 19.70 | 8.86 |
May | 0.823204E+10 | 25802.33 | 13-MAY-18:22 | 21.95 | 8.73 | 0.403154E+09 | 544.96 | 25-MAY-13:09 | 17.20 | 8.78 |
June | 0.115362E+11 | 25757.82 | 18-JUN-17:02 | 25.50 | 14.50 | 0.422974E+09 | 544.97 | 19-JUN-13:30 | 24.70 | 12.18 |
July | 0.144932E+11 | 27760.02 | 16-JUL-17:21 | 33.05 | 17.12 | 0.396947E+09 | 544.98 | 13-JUL-09:00 | 33.05 | 17.12 |
August | 0.160256E+11 | 27667.00 | 06-AUG-16:21 | 35.30 | 16.02 | 0.445344E+09 | 544.97 | 15-AUG-13:30 | 25.00 | 13.67 |
September | 0.843008E+10 | 28775.52 | 04-SEP-16:01 | 32.80 | 16.54 | 0.376059E+09 | 544.99 | 07-SEP-09:50 | 16.52 | 15.26 |
October | 0.703203E+10 | 17848.21 | 15-OCT-15:11 | 22.60 | 10.96 | 0.387701E+09 | 544.96 | 20-OCT-13:00 | 13.30 | 6.77 |
November | 0.587873E+10 | 9275.45 | 03-NOV-15:40 | 14.40 | 7.69 | 0.372365E+09 | 544.94 | 17-NOV-14:30 | 16.30 | 8.01 |
December | 0.504731E+10 | 8501.44 | 06-DEC-15:30 | 10.25 | 4.94 | 0.349426E+09 | 544.94 | 12-DEC-14:00 | -2.8 | -5.6 |
Annual Sum or Average | 0.990193E+11 | 0.457936E+10 | ||||||||
Minimum of Months | 0.248505E+10 | 4895.35 | -0.2 | -2.7 | 0.314418E+09 | 521.79 | -2.8 | -5.6 | ||
Maximum of Months | 0.160256E+11 | 28775.52 | 35.30 | 17.12 | 0.445344E+09 | 544.99 | 33.05 | 17.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119807E+09 | 1778.31 | 13-JAN-17:00 | 7.80 | 3.93 | 0.462912E+09 | 626.02 | 10-JAN-10:50 | 7.80 | 3.93 |
February | 0.635928E+09 | 2893.83 | 27-FEB-13:30 | 17.75 | 6.76 | 0.428214E+09 | 731.95 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.172371E+10 | 2808.87 | 23-MAR-13:30 | 9.70 | 2.18 | 0.535506E+09 | 774.20 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.269710E+10 | 4918.91 | 07-APR-14:30 | 22.50 | 9.29 | 0.525198E+09 | 845.60 | 26-APR-13:00 | 11.10 | 4.95 |
May | 0.391550E+10 | 7053.07 | 19-MAY-16:00 | 27.80 | 14.54 | 0.599524E+09 | 845.62 | 25-MAY-13:09 | 17.20 | 8.78 |
June | 0.674903E+10 | 11399.41 | 21-JUN-05:03 | 15.87 | 11.84 | 0.651206E+09 | 845.64 | 27-JUN-13:00 | 25.00 | 13.11 |
July | 0.803598E+10 | 15058.68 | 16-JUL-18:31 | 32.40 | 17.11 | 0.612498E+09 | 846.34 | 18-JUL-13:20 | 33.17 | 17.33 |
August | 0.708744E+10 | 14214.44 | 06-AUG-17:21 | 34.15 | 15.38 | 0.680997E+09 | 845.64 | 01-AUG-13:09 | 34.15 | 15.38 |
September | 0.444613E+10 | 11882.22 | 04-SEP-14:11 | 30.73 | 16.07 | 0.570044E+09 | 845.67 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.276229E+10 | 4186.86 | 19-OCT-14:40 | 21.50 | 10.24 | 0.542818E+09 | 845.61 | 19-OCT-13:09 | 21.50 | 10.24 |
November | 0.141170E+10 | 2799.71 | 03-NOV-13:30 | 14.35 | 7.74 | 0.485226E+09 | 772.17 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.399587E+09 | 1999.14 | 06-DEC-16:20 | 8.50 | 3.80 | 0.449902E+09 | 669.95 | 06-DEC-14:00 | 8.50 | 3.80 |
Annual Sum or Average | 0.399842E+11 | 0.654404E+10 | ||||||||
Minimum of Months | 0.119807E+09 | 1778.31 | 7.80 | 2.18 | 0.428214E+09 | 626.02 | 7.80 | 3.80 | ||
Maximum of Months | 0.803598E+10 | 15058.68 | 34.15 | 17.11 | 0.680997E+09 | 846.34 | 34.15 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258075E+09 | 2508.06 | 13-JAN-06:03 | 0.50 | -2.4 | 0.219648E+09 | 385.84 | 10-JAN-09:30 | 0.50 | -2.4 |
February | 0.113448E+10 | 4578.83 | 26-FEB-11:52 | 13.30 | 4.89 | 0.205397E+09 | 514.26 | 28-FEB-09:00 | 1.10 | -0.5 |
March | 0.253030E+10 | 6868.85 | 28-MAR-10:05 | 7.38 | 1.58 | 0.257887E+09 | 521.20 | 22-MAR-10:20 | 7.38 | 1.58 |
April | 0.404820E+10 | 10382.86 | 25-APR-09:00 | 9.40 | 4.65 | 0.250072E+09 | 521.20 | 06-APR-10:30 | 9.40 | 4.65 |
May | 0.535520E+10 | 11855.12 | 19-MAY-08:50 | 17.52 | 11.29 | 0.284590E+09 | 521.26 | 02-MAY-12:09 | 17.52 | 11.29 |
June | 0.843727E+10 | 20821.35 | 04-JUN-07:42 | 15.63 | 13.07 | 0.305122E+09 | 521.61 | 23-JUN-10:09 | 27.98 | 15.45 |
July | 0.101466E+11 | 24537.22 | 16-JUL-09:11 | 22.57 | 16.22 | 0.288991E+09 | 522.87 | 14-JUL-10:30 | 22.57 | 16.22 |
August | 0.924419E+10 | 25100.89 | 06-AUG-09:21 | 28.60 | 14.63 | 0.319998E+09 | 523.29 | 07-AUG-10:50 | 30.60 | 14.99 |
September | 0.576648E+10 | 22391.49 | 04-SEP-08:52 | 26.70 | 14.88 | 0.265152E+09 | 521.21 | 06-SEP-12:09 | 22.07 | 17.08 |
October | 0.363482E+10 | 7088.57 | 18-OCT-10:10 | 20.28 | 8.90 | 0.253487E+09 | 521.20 | 19-OCT-10:09 | 19.18 | 9.33 |
November | 0.176813E+10 | 3813.69 | 03-NOV-13:00 | 13.70 | 7.60 | 0.226606E+09 | 508.28 | 03-NOV-10:30 | 13.70 | 7.60 |
December | 0.527450E+09 | 2652.07 | 20-DEC-10:00 | 3.30 | -0.6 | 0.212117E+09 | 406.47 | 07-DEC-11:30 | 3.30 | -0.6 |
Annual Sum or Average | 0.528512E+11 | 0.308907E+10 | ||||||||
Minimum of Months | 0.258075E+09 | 2508.06 | 0.50 | -2.4 | 0.205397E+09 | 385.84 | 0.50 | -2.4 | ||
Maximum of Months | 0.101466E+11 | 25100.89 | 28.60 | 16.22 | 0.319998E+09 | 523.29 | 30.60 | 17.08 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214311E+10 | 10904.24 | 19-JAN-14:00 | -5.6 | -7.5 | 0.500800E+09 | 845.64 | 19-JAN-14:30 | -5.3 | -7.2 |
February | 0.440719E+10 | 28055.29 | 26-FEB-13:12 | 15.20 | 5.59 | 0.491963E+09 | 846.11 | 27-FEB-14:39 | 18.70 | 7.17 |
March | 0.622283E+10 | 19948.17 | 01-MAR-13:50 | 6.52 | 2.64 | 0.590756E+09 | 846.64 | 23-MAR-13:00 | 10.00 | 2.51 |
April | 0.640843E+10 | 17735.91 | 16-APR-13:52 | 19.40 | 8.41 | 0.539762E+09 | 845.82 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.724695E+10 | 15124.33 | 19-MAY-13:40 | 26.83 | 14.98 | 0.601623E+09 | 845.71 | 02-MAY-13:09 | 26.83 | 14.98 |
June | 0.990686E+10 | 14907.61 | 30-JUN-13:30 | 28.05 | 13.89 | 0.637559E+09 | 845.68 | 19-JUN-13:09 | 28.05 | 13.89 |
July | 0.123108E+11 | 27487.61 | 16-JUL-13:52 | 31.70 | 18.44 | 0.606559E+09 | 846.26 | 18-JUL-13:00 | 31.70 | 17.43 |
August | 0.137359E+11 | 27696.65 | 06-AUG-14:41 | 34.40 | 15.36 | 0.675312E+09 | 854.75 | 30-AUG-13:39 | 26.33 | 14.35 |
September | 0.111401E+11 | 30732.60 | 03-SEP-12:41 | 33.22 | 15.94 | 0.578774E+09 | 865.68 | 01-SEP-13:50 | 33.22 | 15.94 |
October | 0.886618E+10 | 27282.21 | 15-OCT-13:22 | 22.75 | 10.91 | 0.587479E+09 | 875.79 | 18-OCT-13:39 | 24.80 | 11.21 |
November | 0.541218E+10 | 24315.79 | 12-NOV-13:32 | -0.6 | -3.6 | 0.548639E+09 | 846.25 | 06-NOV-14:50 | -0.6 | -3.6 |
December | 0.292548E+10 | 11219.99 | 12-DEC-14:30 | -2.2 | -5.4 | 0.499122E+09 | 845.63 | 12-DEC-14:20 | -2.2 | -5.4 |
Annual Sum or Average | 0.907259E+11 | 0.685835E+10 | ||||||||
Minimum of Months | 0.214311E+10 | 10904.24 | -5.6 | -7.5 | 0.491963E+09 | 845.63 | -5.3 | -7.2 | ||
Maximum of Months | 0.137359E+11 | 30732.60 | 34.40 | 18.44 | 0.675312E+09 | 875.79 | 33.22 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.436258E+09 | 3386.28 | 13-JAN-15:50 | 9.08 | 4.76 | 0.300990E+09 | 453.77 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.138149E+10 | 6693.60 | 28-FEB-16:40 | 10.37 | 4.49 | 0.281565E+09 | 521.20 | 27-FEB-16:30 | 10.37 | 4.49 |
March | 0.279185E+10 | 8340.89 | 28-MAR-17:00 | 10.60 | 2.97 | 0.344190E+09 | 544.85 | 02-MAR-14:00 | 10.60 | 2.97 |
April | 0.435108E+10 | 22865.17 | 16-APR-17:11 | 19.80 | 8.90 | 0.325477E+09 | 540.75 | 07-APR-13:00 | 19.80 | 8.90 |
May | 0.588951E+10 | 23168.34 | 28-MAY-17:52 | 20.00 | 10.33 | 0.369196E+09 | 544.94 | 19-MAY-13:30 | 20.00 | 10.33 |
June | 0.826535E+10 | 23796.50 | 18-JUN-17:31 | 25.20 | 14.48 | 0.402821E+09 | 544.96 | 27-JUN-13:00 | 25.00 | 13.11 |
July | 0.974864E+10 | 27664.98 | 16-JUL-17:11 | 33.13 | 17.22 | 0.386743E+09 | 544.97 | 03-JUL-13:09 | 33.13 | 17.22 |
August | 0.908122E+10 | 24794.91 | 06-AUG-16:41 | 35.10 | 15.80 | 0.424823E+09 | 544.96 | 01-AUG-13:09 | 35.10 | 15.80 |
September | 0.614916E+10 | 26400.92 | 04-SEP-16:51 | 32.80 | 16.77 | 0.347428E+09 | 544.94 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.402715E+10 | 9677.05 | 16-OCT-16:00 | 19.40 | 8.07 | 0.336098E+09 | 531.07 | 13-OCT-13:00 | 19.40 | 8.07 |
November | 0.218316E+10 | 5093.91 | 03-NOV-15:50 | 14.35 | 7.69 | 0.314379E+09 | 522.38 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.858996E+09 | 3693.53 | 06-DEC-15:50 | 9.68 | 4.65 | 0.292651E+09 | 482.87 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.551639E+11 | 0.412636E+10 | ||||||||
Minimum of Months | 0.436258E+09 | 3386.28 | 9.08 | 2.97 | 0.281565E+09 | 453.77 | 8.90 | 2.97 | ||
Maximum of Months | 0.974864E+10 | 27664.98 | 35.10 | 17.22 | 0.424823E+09 | 544.97 | 35.10 | 17.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28595646.44 | 2087.53 | 14-JAN-17:03 | 8.90 | 4.06 | 0.458969E+09 | 626.05 | 09-JAN-14:30 | 8.90 | 4.06 |
February | 0.231349E+09 | 2622.12 | 27-FEB-16:10 | 17.78 | 6.92 | 0.421849E+09 | 670.30 | 27-FEB-14:00 | 17.78 | 6.92 |
March | 0.935659E+09 | 2821.68 | 29-MAR-16:00 | 12.20 | 4.07 | 0.511549E+09 | 703.28 | 29-MAR-13:00 | 12.20 | 4.07 |
April | 0.214659E+10 | 4425.28 | 07-APR-14:30 | 22.50 | 9.29 | 0.484754E+09 | 845.60 | 07-APR-13:50 | 22.50 | 9.29 |
May | 0.371830E+10 | 7709.16 | 19-MAY-16:00 | 27.80 | 14.54 | 0.562775E+09 | 845.63 | 19-MAY-13:09 | 27.80 | 14.54 |
June | 0.687946E+10 | 9530.52 | 29-JUN-15:10 | 32.02 | 14.63 | 0.633031E+09 | 845.63 | 21-JUN-13:09 | 32.02 | 14.63 |
July | 0.846756E+10 | 15130.90 | 16-JUL-18:41 | 32.30 | 17.18 | 0.605987E+09 | 845.65 | 03-JUL-13:09 | 32.30 | 17.18 |
August | 0.729852E+10 | 19338.03 | 06-AUG-16:11 | 35.40 | 16.13 | 0.663961E+09 | 845.64 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.428284E+10 | 8066.96 | 05-SEP-14:00 | 24.40 | 15.14 | 0.536253E+09 | 845.62 | 05-SEP-09:09 | 24.40 | 15.14 |
October | 0.205354E+10 | 4115.68 | 18-OCT-13:50 | 24.90 | 11.31 | 0.497626E+09 | 826.58 | 19-OCT-13:00 | 21.10 | 10.22 |
November | 0.673898E+09 | 2665.86 | 17-NOV-17:00 | 17.20 | 8.89 | 0.463598E+09 | 693.63 | 08-NOV-14:00 | 17.20 | 8.89 |
December | 0.121714E+09 | 2181.97 | 06-DEC-16:20 | 8.50 | 3.80 | 0.446542E+09 | 626.02 | 29-DEC-14:50 | -19.5 | -20.1 |
Annual Sum or Average | 0.368380E+11 | 0.628689E+10 | ||||||||
Minimum of Months | 28595646.44 | 2087.53 | 8.50 | 3.80 | 0.421849E+09 | 626.02 | -19.5 | -20.1 | ||
Maximum of Months | 0.846756E+10 | 19338.03 | 35.40 | 17.18 | 0.663961E+09 | 845.65 | 35.40 | 17.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65819451.08 | 2513.67 | 19-JAN-06:04 | -14.9 | -15.6 | 0.298656E+09 | 403.47 | 10-JAN-10:50 | -14.9 | -15.6 |
February | 0.668312E+09 | 3276.85 | 28-FEB-10:30 | 2.50 | 0.37 | 0.275084E+09 | 487.83 | 28-FEB-10:39 | 2.97 | 0.62 |
March | 0.173132E+10 | 5190.53 | 23-MAR-10:30 | 8.60 | 1.66 | 0.343013E+09 | 544.95 | 28-MAR-09:39 | 6.47 | 1.20 |
April | 0.317380E+10 | 9357.45 | 25-APR-09:40 | 11.27 | 5.45 | 0.333308E+09 | 544.95 | 25-APR-09:09 | 11.27 | 5.45 |
May | 0.478880E+10 | 11400.37 | 19-MAY-09:20 | 18.53 | 11.74 | 0.381764E+09 | 544.99 | 02-MAY-13:09 | 18.53 | 11.74 |
June | 0.830770E+10 | 22632.36 | 25-JUN-09:02 | 17.15 | 11.95 | 0.413772E+09 | 545.98 | 23-JUN-09:00 | 17.15 | 11.95 |
July | 0.103461E+11 | 22351.13 | 16-JUL-09:22 | 22.75 | 16.30 | 0.391788E+09 | 545.73 | 03-JUL-09:00 | 22.75 | 16.30 |
August | 0.921965E+10 | 24303.86 | 06-AUG-08:11 | 24.60 | 14.01 | 0.435031E+09 | 546.09 | 11-AUG-09:00 | 27.80 | 12.62 |
September | 0.516773E+10 | 16405.27 | 04-SEP-09:02 | 26.88 | 14.90 | 0.356500E+09 | 544.95 | 15-SEP-13:09 | 19.08 | 11.71 |
October | 0.275087E+10 | 5935.97 | 18-OCT-10:00 | 20.00 | 8.80 | 0.332275E+09 | 544.95 | 18-OCT-09:20 | 20.00 | 8.80 |
November | 0.994073E+09 | 3210.92 | 03-NOV-10:00 | 8.70 | 5.33 | 0.299979E+09 | 479.07 | 03-NOV-09:00 | 8.70 | 5.33 |
December | 0.213554E+09 | 2489.13 | 09-DEC-06:04 | -5.1 | -5.7 | 0.288222E+09 | 403.43 | 27-DEC-10:00 | -12.2 | -12.7 |
Annual Sum or Average | 0.474277E+11 | 0.414939E+10 | ||||||||
Minimum of Months | 65819451.08 | 2489.13 | -14.9 | -15.6 | 0.275084E+09 | 403.43 | -14.9 | -15.6 | ||
Maximum of Months | 0.103461E+11 | 24303.86 | 26.88 | 16.30 | 0.435031E+09 | 546.09 | 27.80 | 16.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144381E+10 | 8957.88 | 31-JAN-13:40 | -0.8 | -4.5 | 0.485424E+09 | 845.63 | 31-JAN-14:00 | -1.1 | -4.4 |
February | 0.333083E+10 | 27507.63 | 26-FEB-14:21 | 16.15 | 6.12 | 0.470774E+09 | 845.86 | 28-FEB-14:39 | 10.40 | 4.69 |
March | 0.473577E+10 | 17910.34 | 01-MAR-14:10 | 6.97 | 2.89 | 0.569424E+09 | 846.20 | 23-MAR-13:50 | 9.90 | 2.40 |
April | 0.518975E+10 | 16948.28 | 25-APR-13:40 | 16.30 | 6.98 | 0.517864E+09 | 845.93 | 24-APR-13:20 | 16.30 | 6.98 |
May | 0.652726E+10 | 15685.85 | 19-MAY-13:50 | 27.02 | 15.00 | 0.582296E+09 | 845.71 | 02-MAY-13:09 | 27.02 | 15.00 |
June | 0.978493E+10 | 17968.33 | 25-JUN-15:02 | 24.90 | 13.05 | 0.623853E+09 | 845.66 | 21-JUN-13:09 | 24.90 | 13.05 |
July | 0.126601E+11 | 27884.71 | 16-JUL-14:02 | 31.97 | 18.55 | 0.599840E+09 | 846.65 | 18-JUL-13:00 | 31.70 | 17.43 |
August | 0.137872E+11 | 30915.84 | 06-AUG-14:11 | 34.40 | 15.37 | 0.664933E+09 | 846.58 | 31-AUG-13:39 | 25.37 | 13.99 |
September | 0.103255E+11 | 30633.58 | 03-SEP-13:31 | 33.70 | 16.17 | 0.560733E+09 | 848.84 | 01-SEP-13:50 | 33.70 | 16.17 |
October | 0.714543E+10 | 30022.91 | 15-OCT-14:22 | 23.05 | 11.10 | 0.561241E+09 | 845.76 | 23-OCT-13:39 | 20.77 | 9.63 |
November | 0.398203E+10 | 17302.60 | 03-NOV-13:30 | 14.35 | 7.74 | 0.521539E+09 | 845.82 | 03-NOV-13:00 | 15.00 | 7.85 |
December | 0.194211E+10 | 8609.56 | 06-DEC-14:40 | 11.30 | 5.42 | 0.480003E+09 | 845.63 | 01-DEC-14:00 | 11.30 | 5.42 |
Annual Sum or Average | 0.808547E+11 | 0.663793E+10 | ||||||||
Minimum of Months | 0.144381E+10 | 8609.56 | -0.8 | -4.5 | 0.470774E+09 | 845.63 | -1.1 | -4.4 | ||
Maximum of Months | 0.137872E+11 | 30915.84 | 34.40 | 18.55 | 0.664933E+09 | 848.84 | 33.70 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227232E+09 | 3377.10 | 13-JAN-15:50 | 9.08 | 4.76 | 0.299155E+09 | 434.37 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.914164E+09 | 6085.77 | 28-FEB-16:40 | 10.37 | 4.49 | 0.277817E+09 | 521.18 | 28-FEB-16:00 | 10.00 | 4.31 |
March | 0.191771E+10 | 7911.71 | 28-MAR-17:00 | 10.60 | 2.97 | 0.338149E+09 | 531.11 | 02-MAR-14:00 | 10.60 | 2.97 |
April | 0.356248E+10 | 17634.83 | 16-APR-17:11 | 19.80 | 8.90 | 0.313902E+09 | 536.38 | 25-APR-13:00 | 16.10 | 6.69 |
May | 0.539540E+10 | 24383.89 | 28-MAY-17:52 | 20.00 | 10.33 | 0.357709E+09 | 544.95 | 19-MAY-13:50 | 20.00 | 10.33 |
June | 0.818649E+10 | 26299.55 | 18-JUN-16:41 | 25.50 | 14.47 | 0.393168E+09 | 544.96 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.998672E+10 | 27979.85 | 09-JUL-17:31 | 27.97 | 13.10 | 0.381483E+09 | 544.97 | 03-JUL-13:09 | 27.97 | 13.10 |
August | 0.910991E+10 | 28607.14 | 06-AUG-16:11 | 35.40 | 16.13 | 0.416015E+09 | 544.96 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.565537E+10 | 25445.69 | 04-SEP-16:22 | 32.80 | 16.63 | 0.336924E+09 | 544.94 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.309750E+10 | 9471.34 | 18-OCT-16:00 | 24.40 | 11.02 | 0.322964E+09 | 521.18 | 11-OCT-15:00 | 24.40 | 11.02 |
November | 0.139780E+10 | 4337.77 | 03-NOV-16:00 | 14.30 | 7.69 | 0.305681E+09 | 520.31 | 03-NOV-15:00 | 14.30 | 7.69 |
December | 0.467476E+09 | 3678.20 | 06-DEC-15:50 | 9.68 | 4.65 | 0.289630E+09 | 460.53 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.499183E+11 | 0.403260E+10 | ||||||||
Minimum of Months | 0.227232E+09 | 3377.10 | 9.08 | 2.97 | 0.277817E+09 | 434.37 | 8.90 | 2.97 | ||
Maximum of Months | 0.998672E+10 | 28607.14 | 35.40 | 16.63 | 0.416015E+09 | 544.97 | 35.40 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.664186E+09 | 7642.15 | 06-JAN-05:01 | -24.5 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.5 | -24.9 |
February | 0.994793E+09 | 5618.53 | 28-FEB-06:08 | -3.9 | -4.3 | 0.00 | 0.00 | 01-FEB-00:10 | -3.9 | -4.3 |
March | 0.249003E+10 | 5445.36 | 01-MAR-06:08 | -12.2 | -12.7 | 0.00 | 0.00 | 01-MAR-00:10 | -12.2 | -12.7 |
April | 0.416925E+10 | 5853.81 | 25-APR-05:08 | 1.10 | -0.7 | 0.00 | 0.00 | 01-APR-00:10 | 1.10 | -0.7 |
May | 0.422889E+10 | 9655.13 | 30-MAY-05:15 | 15.60 | 11.34 | 0.00 | 0.00 | 01-MAY-00:10 | 15.60 | 11.34 |
June | 0.763454E+10 | 8736.68 | 26-JUN-05:15 | 10.33 | 9.12 | 0.00 | 0.00 | 01-JUN-00:10 | 10.33 | 9.12 |
July | 0.965296E+10 | 11925.90 | 17-JUL-05:15 | 16.83 | 12.38 | 0.00 | 0.00 | 01-JUL-00:10 | 16.83 | 12.38 |
August | 0.100594E+11 | 10771.09 | 07-AUG-05:25 | 18.05 | 10.23 | 0.00 | 0.00 | 01-AUG-00:10 | 18.05 | 10.23 |
September | 0.595347E+10 | 10073.69 | 06-SEP-05:13 | 15.00 | 12.76 | 0.00 | 0.00 | 01-SEP-00:10 | 15.00 | 12.76 |
October | 0.430051E+10 | 5671.83 | 02-OCT-05:15 | 4.80 | 2.86 | 0.00 | 0.00 | 01-OCT-00:10 | 4.80 | 2.86 |
November | 0.252724E+10 | 6023.33 | 06-NOV-06:07 | -3.5 | -4.3 | 0.00 | 0.00 | 01-NOV-00:10 | -3.5 | -4.3 |
December | 0.123930E+10 | 4374.40 | 09-DEC-06:07 | -5.1 | -5.7 | 0.00 | 0.00 | 01-DEC-00:10 | -5.1 | -5.7 |
Annual Sum or Average | 0.539146E+11 | 0.00 | ||||||||
Minimum of Months | 0.664186E+09 | 4374.40 | -24.5 | -24.9 | 0.00 | 0.00 | -24.5 | -24.9 | ||
Maximum of Months | 0.100594E+11 | 11925.90 | 18.05 | 12.76 | 0.00 | 0.00 | 18.05 | 12.76 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.437145E+09 | 10304.67 | 06-JAN-04:11 | -24.4 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.4 | -24.9 |
February | 0.343269E+09 | 9223.57 | 04-FEB-04:11 | -21.7 | -22.0 | 0.00 | 0.00 | 01-FEB-00:10 | -21.7 | -22.0 |
March | 0.998663E+09 | 11179.56 | 04-MAR-04:01 | -18.4 | -18.9 | 0.00 | 0.00 | 01-MAR-00:10 | -18.4 | -18.9 |
April | 0.174361E+10 | 6667.10 | 29-APR-04:01 | -7.8 | -8.7 | 0.00 | 0.00 | 01-APR-00:10 | -7.8 | -8.7 |
May | 0.242779E+10 | 6448.79 | 08-MAY-04:01 | -2.3 | -2.7 | 0.00 | 0.00 | 01-MAY-00:10 | -2.3 | -2.7 |
June | 0.554971E+10 | 6698.62 | 23-JUN-15:30 | 27.50 | 14.33 | 0.00 | 0.00 | 01-JUN-00:10 | 27.50 | 14.33 |
July | 0.722867E+10 | 8154.85 | 17-JUL-15:20 | 36.47 | 17.10 | 0.00 | 0.00 | 01-JUL-00:10 | 36.47 | 17.10 |
August | 0.710100E+10 | 8156.32 | 07-AUG-15:40 | 32.40 | 16.10 | 0.00 | 0.00 | 01-AUG-00:10 | 32.40 | 16.10 |
September | 0.427619E+10 | 7728.48 | 05-SEP-14:40 | 24.40 | 14.90 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 14.90 |
October | 0.214994E+10 | 6029.53 | 10-OCT-04:01 | -5.2 | -5.7 | 0.00 | 0.00 | 01-OCT-00:10 | -5.2 | -5.7 |
November | 0.985698E+09 | 8747.41 | 27-NOV-04:01 | -15.8 | -16.7 | 0.00 | 0.00 | 01-NOV-00:10 | -15.8 | -16.7 |
December | 0.583042E+09 | 8033.56 | 29-DEC-04:01 | -24.5 | -24.8 | 0.00 | 0.00 | 01-DEC-00:10 | -24.5 | -24.8 |
Annual Sum or Average | 0.338247E+11 | 0.00 | ||||||||
Minimum of Months | 0.343269E+09 | 6029.53 | -24.5 | -24.9 | 0.00 | 0.00 | -24.5 | -24.9 | ||
Maximum of Months | 0.722867E+10 | 11179.56 | 36.47 | 17.10 | 0.00 | 0.00 | 36.47 | 17.10 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12354.73 | 82.36 | 14-JAN-17:10 | 8.90 | 4.06 | 0.00 | 0.00 | 01-JAN-00:10 | 8.90 | 4.06 |
February | 94367182.19 | 2545.11 | 26-FEB-14:26 | 16.15 | 6.12 | 0.00 | 0.00 | 01-FEB-00:10 | 16.15 | 6.12 |
March | 0.563955E+09 | 4410.76 | 23-MAR-13:40 | 9.80 | 2.29 | 0.00 | 0.00 | 01-MAR-00:10 | 9.80 | 2.29 |
April | 0.217949E+10 | 10711.34 | 25-APR-15:00 | 17.00 | 7.46 | 0.00 | 0.00 | 01-APR-00:10 | 17.00 | 7.46 |
May | 0.467572E+10 | 16442.43 | 19-MAY-15:00 | 28.30 | 14.88 | 0.00 | 0.00 | 01-MAY-00:10 | 28.30 | 14.88 |
June | 0.968488E+10 | 19298.83 | 23-JUN-13:30 | 31.40 | 15.21 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 15.21 |
July | 0.128960E+11 | 22981.96 | 17-JUL-15:00 | 36.10 | 17.00 | 0.00 | 0.00 | 01-JUL-00:10 | 36.10 | 17.00 |
August | 0.110028E+11 | 20527.83 | 07-AUG-15:40 | 32.40 | 16.10 | 0.00 | 0.00 | 01-AUG-00:10 | 32.40 | 16.10 |
September | 0.518587E+10 | 15022.49 | 01-SEP-15:40 | 28.30 | 14.15 | 0.00 | 0.00 | 01-SEP-00:10 | 28.30 | 14.15 |
October | 0.137413E+10 | 8533.89 | 18-OCT-15:10 | 24.90 | 11.51 | 0.00 | 0.00 | 01-OCT-00:10 | 24.90 | 11.51 |
November | 94553154.05 | 1924.04 | 03-NOV-14:20 | 14.87 | 7.79 | 0.00 | 0.00 | 01-NOV-00:10 | 14.87 | 7.79 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.477518E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.00 | 0.00 | -2.1 | -4.2 | ||
Maximum of Months | 0.128960E+11 | 22981.96 | 36.10 | 17.00 | 0.00 | 0.00 | 36.10 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203709E+10 | 2000.09 | 19-JAN-16:50 | -6.4 | -8.0 | 95189148.19 | 126.82 | 02-JAN-10:09 | -6.4 | -8.0 |
February | 0.724141E+10 | 4351.56 | 28-FEB-17:00 | 10.00 | 4.31 | 86396455.50 | 126.82 | 09-FEB-14:20 | 10.00 | 4.31 |
March | 0.137836E+11 | 6820.26 | 31-MAR-24:00 | 2.50 | 0.99 | 0.103236E+09 | 126.82 | 29-MAR-13:09 | 2.50 | 0.99 |
April | 0.187626E+11 | 8237.58 | 25-APR-18:10 | 16.73 | 7.64 | 91605248.45 | 126.82 | 21-APR-09:00 | 16.73 | 7.64 |
May | 0.422608E+10 | 3506.78 | 31-MAY-24:00 | 15.50 | 10.27 | 99234985.04 | 126.84 | 30-MAY-09:30 | 15.50 | 10.27 |
June | 0.935433E+10 | 5350.58 | 30-JUN-23:12 | 20.20 | 12.29 | 98962590.25 | 126.85 | 01-JUN-13:00 | 20.20 | 12.29 |
July | 0.148553E+11 | 7256.02 | 31-JUL-23:40 | 19.77 | 11.91 | 91883731.97 | 126.84 | 03-JUL-13:09 | 19.77 | 11.91 |
August | 0.199388E+11 | 8260.85 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103466E+09 | 132.67 | 11-AUG-13:00 | 32.20 | 13.16 |
September | 0.421326E+10 | 3314.41 | 30-SEP-24:00 | 11.80 | 6.26 | 91611124.86 | 126.86 | 06-SEP-13:39 | 11.80 | 6.26 |
October | 0.917216E+10 | 4956.61 | 31-OCT-24:00 | 4.70 | 1.47 | 95230936.12 | 126.83 | 25-OCT-09:00 | 4.70 | 1.47 |
November | 0.134260E+11 | 6112.93 | 13-NOV-16:20 | 3.27 | -2.5 | 94300334.74 | 126.83 | 08-NOV-14:00 | 3.27 | -2.5 |
December | 0.184149E+11 | 7887.99 | 06-DEC-16:10 | 8.95 | 4.16 | 91880819.54 | 126.82 | 15-DEC-14:39 | -10.6 | -10.9 |
Annual Sum or Average | 0.135425E+12 | 0.114300E+10 | ||||||||
Minimum of Months | 0.203709E+10 | 2000.09 | -6.4 | -8.0 | 86396455.50 | 126.82 | -10.6 | -10.9 | ||
Maximum of Months | 0.199388E+11 | 8260.85 | 24.60 | 12.54 | 0.103466E+09 | 132.67 | 32.20 | 13.16 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.531494E+09 | 1638.84 | 19-JAN-16:50 | -6.4 | -8.0 | 93479354.29 | 126.82 | 04-JAN-10:09 | -6.4 | -8.0 |
February | 0.500080E+10 | 3967.54 | 28-FEB-17:00 | 10.00 | 4.31 | 86396467.54 | 126.82 | 03-FEB-14:30 | 10.00 | 4.31 |
March | 0.113652E+11 | 5898.77 | 31-MAR-23:30 | 2.00 | 0.53 | 0.103236E+09 | 126.82 | 29-MAR-13:09 | 2.00 | 0.53 |
April | 0.167655E+11 | 7816.14 | 25-APR-18:10 | 16.73 | 7.64 | 91605285.46 | 126.82 | 24-APR-09:09 | 16.73 | 7.64 |
May | 0.321674E+10 | 3305.33 | 31-MAY-24:00 | 15.50 | 10.27 | 99234851.51 | 126.84 | 30-MAY-09:30 | 15.50 | 10.27 |
June | 0.855243E+10 | 5241.42 | 30-JUN-23:55 | 19.60 | 12.23 | 98962372.41 | 126.85 | 01-JUN-13:50 | 19.60 | 12.23 |
July | 0.140068E+11 | 7067.46 | 31-JUL-23:53 | 19.20 | 11.32 | 91883994.61 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.187065E+11 | 7894.12 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103320E+09 | 130.18 | 11-AUG-13:00 | 32.20 | 13.16 |
September | 0.338162E+10 | 2869.57 | 30-SEP-23:40 | 12.27 | 6.64 | 91609841.68 | 126.84 | 11-SEP-13:00 | 12.27 | 6.64 |
October | 0.748440E+10 | 4140.53 | 31-OCT-24:00 | 4.70 | 1.47 | 95230858.11 | 126.83 | 25-OCT-09:00 | 4.70 | 1.47 |
November | 0.109556E+11 | 5570.73 | 03-NOV-16:00 | 14.30 | 7.69 | 94300354.64 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.148897E+11 | 7159.06 | 06-DEC-16:20 | 8.50 | 3.80 | 91880842.46 | 126.82 | 18-DEC-14:39 | 0.60 | -2.8 |
Annual Sum or Average | 0.114857E+12 | 0.114114E+10 | ||||||||
Minimum of Months | 0.531494E+09 | 1638.84 | -6.4 | -8.0 | 86396467.54 | 126.82 | -6.4 | -8.0 | ||
Maximum of Months | 0.187065E+11 | 7894.12 | 24.60 | 12.54 | 0.103320E+09 | 130.18 | 32.20 | 13.16 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207777E+09 | 1412.46 | 13-JAN-16:30 | 8.35 | 4.30 | 88646654.17 | 126.87 | 24-JAN-10:09 | 0.60 | -0.8 |
February | 0.340319E+10 | 3906.11 | 28-FEB-17:00 | 10.00 | 4.31 | 86391631.66 | 126.82 | 01-FEB-14:20 | 10.00 | 4.31 |
March | 0.968651E+10 | 5836.58 | 28-MAR-17:50 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 29-MAR-13:09 | 12.30 | 4.26 |
April | 0.155485E+11 | 7866.44 | 25-APR-18:10 | 16.73 | 7.64 | 91605313.83 | 126.82 | 21-APR-09:00 | 16.73 | 7.64 |
May | 0.261452E+10 | 3221.75 | 31-MAY-24:00 | 15.50 | 10.27 | 98949549.85 | 126.84 | 30-MAY-09:39 | 15.50 | 10.27 |
June | 0.830384E+10 | 5241.25 | 30-JUN-23:55 | 19.60 | 12.23 | 98962418.46 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.139207E+11 | 7020.76 | 31-JUL-23:53 | 19.20 | 11.32 | 91884005.65 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.185383E+11 | 7964.13 | 03-AUG-18:40 | 24.80 | 12.58 | 0.103296E+09 | 128.68 | 11-AUG-13:00 | 32.20 | 13.16 |
September | 0.282002E+10 | 2744.97 | 04-SEP-17:32 | 32.07 | 16.48 | 91608048.39 | 126.84 | 05-SEP-09:00 | 17.20 | 11.96 |
October | 0.604409E+10 | 4046.38 | 18-OCT-17:00 | 21.70 | 10.27 | 95230836.49 | 126.83 | 25-OCT-09:00 | 13.30 | 8.54 |
November | 0.902619E+10 | 5486.74 | 03-NOV-16:00 | 14.30 | 7.69 | 94300359.98 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.128215E+11 | 7056.03 | 06-DEC-16:20 | 8.50 | 3.80 | 91880849.26 | 126.82 | 27-DEC-14:30 | -15.6 | -16.1 |
Annual Sum or Average | 0.102935E+12 | 0.113599E+10 | ||||||||
Minimum of Months | 0.207777E+09 | 1412.46 | 8.35 | 2.32 | 86391631.66 | 126.82 | -15.6 | -16.1 | ||
Maximum of Months | 0.185383E+11 | 7964.13 | 32.07 | 16.48 | 0.103296E+09 | 128.68 | 32.20 | 13.16 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234172E+12 | 91678.72 | 02-JAN-17:00 | 2.20 | -1.7 | 0.206142E+10 | 2745.29 | 02-JAN-14:00 | 2.20 | -1.7 |
February | 0.433230E+12 | 183625.84 | 28-FEB-17:00 | 10.00 | 4.31 | 0.187202E+10 | 2748.45 | 10-FEB-10:20 | 10.00 | 4.31 |
March | 0.726873E+12 | 357551.65 | 31-MAR-24:00 | 2.50 | 0.99 | 0.223630E+10 | 2747.51 | 03-MAR-10:00 | 2.50 | 0.99 |
April | 0.940985E+12 | 367104.14 | 26-APR-16:00 | 9.40 | 4.24 | 0.199568E+10 | 3007.30 | 07-APR-13:00 | 9.40 | 4.24 |
May | 0.239915E+12 | 176036.66 | 31-MAY-24:00 | 15.50 | 10.27 | 0.214841E+10 | 2747.90 | 30-MAY-13:00 | 15.50 | 10.27 |
June | 0.469940E+12 | 267990.03 | 30-JUN-24:00 | 19.60 | 12.23 | 0.214398E+10 | 2748.92 | 22-JUN-13:09 | 19.60 | 12.23 |
July | 0.732530E+12 | 359143.61 | 31-JUL-23:12 | 20.33 | 12.51 | 0.198986E+10 | 2750.00 | 18-JUL-09:00 | 20.33 | 12.51 |
August | 0.972124E+12 | 369523.53 | 22-AUG-07:20 | 12.77 | 9.84 | 0.254667E+10 | 3859.23 | 07-AUG-13:00 | 12.77 | 9.84 |
September | 0.235574E+12 | 175705.64 | 30-SEP-24:00 | 11.80 | 6.26 | 0.198353E+10 | 2748.16 | 06-SEP-13:39 | 11.80 | 6.26 |
October | 0.486854E+12 | 267688.27 | 31-OCT-24:00 | 4.70 | 1.47 | 0.206339E+10 | 2748.51 | 24-OCT-13:09 | 4.70 | 1.47 |
November | 0.707049E+12 | 276683.89 | 06-NOV-16:55 | 6.70 | 2.26 | 0.204275E+10 | 2747.58 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.973541E+12 | 367834.76 | 07-DEC-17:00 | 4.40 | 1.14 | 0.198912E+10 | 2745.72 | 29-DEC-10:09 | -23.5 | -23.9 |
Annual Sum or Average | 0.715279E+13 | 0.250731E+11 | ||||||||
Minimum of Months | 0.234172E+12 | 91678.72 | 2.20 | -1.7 | 0.187202E+10 | 2745.29 | -23.5 | -23.9 | ||
Maximum of Months | 0.973541E+12 | 369523.53 | 20.33 | 12.51 | 0.254667E+10 | 3859.23 | 20.33 | 12.51 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301584E+09 | 13047.72 | 02-JAN-04:05 | -0.5 |
February | 78653578.47 | 13085.06 | 27-FEB-04:04 | 4.82 |
March | 0.134655E+09 | 12977.11 | 15-MAR-04:04 | -1.1 |
April | 0.137253E+09 | 13088.66 | 03-APR-03:04 | 1.88 |
May | 0.284582E+09 | 15765.98 | 20-MAY-16:03 | 29.82 |
June | 0.265307E+09 | 14481.83 | 24-JUN-16:02 | 28.22 |
July | 0.408255E+09 | 20391.58 | 15-JUL-16:01 | 32.80 |
August | 0.404490E+09 | 23292.48 | 05-AUG-16:01 | 35.22 |
September | 0.481548E+09 | 21093.72 | 02-SEP-16:02 | 33.98 |
October | 0.389405E+09 | 13225.42 | 16-OCT-03:45 | 12.30 |
November | 0.270651E+09 | 12983.38 | 20-NOV-04:44 | -1.7 |
December | 0.123748E+09 | 12711.28 | 30-DEC-06:04 | -20.5 |
Annual Sum or Average | 0.328013E+10 | |||
Minimum of Months | 78653578.47 | 12711.28 | -20.5 | |
Maximum of Months | 0.481548E+09 | 23292.48 | 35.22 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423125E+09 | 54034.84 | 09-JAN-05:01 | -27.2 |
February | 0.143289E+09 | 52188.75 | 06-FEB-05:01 | -0.4 |
March | 34530066.70 | 50710.21 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 5391611.82 | 47264.98 | 27-NOV-06:01 | -14.5 |
December | 0.100799E+09 | 51362.20 | 26-DEC-05:11 | -7.4 |
Annual Sum or Average | 0.707135E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.423125E+09 | 54034.84 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.832726E+10 | 80080.93 | 09-JAN-04:01 | -27.2 |
February | 0.289604E+10 | 79068.21 | 06-FEB-04:11 | -0.6 |
March | 0.165733E+10 | 78871.35 | 06-MAR-04:01 | -18.4 |
April | 42111400.19 | 64096.14 | 10-APR-05:01 | 3.90 |
May | 0.526948E+09 | 71741.53 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.271047E+09 | 71496.44 | 10-OCT-04:01 | -5.2 |
November | 0.197885E+10 | 78725.86 | 27-NOV-04:01 | -15.8 |
December | 0.416207E+10 | 78587.15 | 26-DEC-04:01 | -6.3 |
Annual Sum or Average | 0.198617E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.832726E+10 | 80080.93 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207579E+10 | 13736.79 | 09-JAN-04:01 | -27.2 |
February | 0.477819E+09 | 12244.76 | 04-FEB-05:01 | -20.4 |
March | 83842469.87 | 12437.51 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 28943984.30 | 11655.47 | 27-NOV-05:01 | -15.4 |
December | 0.296234E+09 | 12112.04 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.296263E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.207579E+10 | 13736.79 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137111E+10 | 15441.51 | 09-JAN-04:01 | -27.2 |
February | 0.376444E+09 | 13800.66 | 04-FEB-05:01 | -20.4 |
March | 76167110.74 | 13901.58 | 06-MAR-05:01 | -18.4 |
April | 1304394.21 | 7979.91 | 29-APR-05:01 | -7.7 |
May | 756500.85 | 10573.28 | 22-MAY-05:01 | -0.6 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 484025.34 | 2519.07 | 10-OCT-05:03 | -6.1 |
November | 43964110.85 | 13273.28 | 27-NOV-05:01 | -15.4 |
December | 0.334159E+09 | 13888.89 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.220438E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.137111E+10 | 15441.51 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194849E+10 | 21401.51 | 09-JAN-04:01 | -27.2 |
February | 0.441711E+09 | 19618.78 | 04-FEB-05:01 | -20.4 |
March | 0.140663E+09 | 20215.03 | 06-MAR-04:01 | -18.4 |
April | 2962893.07 | 16382.12 | 29-APR-05:01 | -7.7 |
May | 15550128.32 | 16475.60 | 08-MAY-05:02 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 3316984.83 | 11310.79 | 10-OCT-05:03 | -6.1 |
November | 0.102690E+09 | 19240.24 | 27-NOV-05:01 | -15.4 |
December | 0.451459E+09 | 19446.68 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.310685E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.194849E+10 | 21401.51 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.601901E+09 | 13947.66 | 09-JAN-04:01 | -27.2 |
February | 33162460.92 | 10825.85 | 10-FEB-06:01 | -19.9 |
March | 4806836.58 | 11563.78 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 285749.86 | 4286.25 | 22-MAY-05:01 | -0.6 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 1510040.08 | 10814.36 | 27-NOV-06:01 | -14.5 |
December | 4074133.22 | 10723.64 | 29-DEC-06:01 | -25.1 |
Annual Sum or Average | 0.645740E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.601901E+09 | 13947.66 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.766619E+10 | 14441.97 | 30-JAN-04:11 | -17.6 |
February | 0.351477E+10 | 13752.34 | 06-FEB-01:32 | -2.4 |
March | 0.157057E+10 | 13771.78 | 06-MAR-03:23 | -18.6 |
April | 0.153438E+09 | 11400.27 | 29-APR-04:01 | -7.8 |
May | 0.176671E+09 | 11843.75 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 18436649.93 | 10498.83 | 20-SEP-05:03 | 3.30 |
October | 0.138277E+09 | 11741.58 | 10-OCT-04:01 | -5.2 |
November | 0.148759E+10 | 13545.43 | 27-NOV-04:01 | -15.8 |
December | 0.449676E+10 | 13765.33 | 31-DEC-07:31 | -28.0 |
Annual Sum or Average | 0.192227E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.0 | |
Maximum of Months | 0.766619E+10 | 14441.97 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.463994E+10 | 19588.13 | 30-JAN-04:11 | -17.6 |
February | 0.196633E+10 | 18417.42 | 05-FEB-04:52 | -20.0 |
March | 0.875646E+09 | 18532.15 | 06-MAR-04:01 | -18.4 |
April | 90621297.98 | 15433.66 | 29-APR-04:01 | -7.8 |
May | 0.113660E+09 | 16107.43 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 11068969.11 | 8932.05 | 20-SEP-05:03 | 3.30 |
October | 79238020.63 | 15861.80 | 10-OCT-04:01 | -5.2 |
November | 0.927575E+09 | 18417.11 | 27-NOV-04:01 | -15.8 |
December | 0.272680E+10 | 18710.09 | 31-DEC-07:31 | -28.0 |
Annual Sum or Average | 0.114309E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.0 | |
Maximum of Months | 0.463994E+10 | 19588.13 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490378E+10 | 23513.84 | 09-JAN-03:02 | -27.2 |
February | 0.177176E+10 | 22407.19 | 05-FEB-04:52 | -20.0 |
March | 0.908919E+09 | 22473.14 | 06-MAR-04:01 | -18.4 |
April | 0.122316E+09 | 18722.58 | 29-APR-04:01 | -7.8 |
May | 0.175680E+09 | 19613.89 | 08-MAY-04:01 | -2.3 |
June | 47981.25 | 319.88 | 17-JUN-05:03 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 10150942.15 | 9971.36 | 19-SEP-05:03 | 2.20 |
October | 66345016.38 | 19074.92 | 10-OCT-04:01 | -5.2 |
November | 0.854189E+09 | 22225.23 | 27-NOV-04:01 | -15.8 |
December | 0.261679E+10 | 22748.66 | 31-DEC-07:31 | -28.0 |
Annual Sum or Average | 0.114300E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.0 | |
Maximum of Months | 0.490378E+10 | 23513.84 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.413037E+10 | 20750.35 | 30-JAN-04:11 | -17.6 |
February | 0.152055E+10 | 19212.46 | 06-FEB-04:11 | -0.6 |
March | 0.677066E+09 | 19629.12 | 06-MAR-04:01 | -18.4 |
April | 54238530.87 | 15364.09 | 29-APR-05:01 | -7.7 |
May | 82894289.40 | 16979.88 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 7532999.77 | 7495.85 | 19-SEP-05:03 | 2.20 |
October | 52339416.61 | 16226.19 | 10-OCT-04:01 | -5.2 |
November | 0.646624E+09 | 19538.55 | 27-NOV-04:01 | -15.8 |
December | 0.203501E+10 | 19846.83 | 31-DEC-07:31 | -28.0 |
Annual Sum or Average | 0.920663E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.0 | |
Maximum of Months | 0.413037E+10 | 20750.35 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152191E+11 | 18996.18 | 30-JAN-05:21 | -16.6 |
February | 0.780276E+10 | 18144.69 | 06-FEB-01:32 | -2.4 |
March | 0.484183E+10 | 18265.78 | 06-MAR-05:01 | -18.4 |
April | 0.128561E+10 | 15819.18 | 29-APR-03:02 | -6.9 |
May | 0.102507E+10 | 16336.08 | 08-MAY-03:01 | -2.7 |
June | 21992497.23 | 14070.49 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 15459986.70 | 13198.02 | 18-AUG-05:02 | 7.30 |
September | 0.320100E+09 | 15077.21 | 19-SEP-04:01 | 2.20 |
October | 0.124167E+10 | 16739.36 | 10-OCT-03:11 | -4.3 |
November | 0.513253E+10 | 18111.04 | 26-NOV-18:42 | -13.9 |
December | 0.109770E+11 | 18497.93 | 31-DEC-03:41 | -24.9 |
Annual Sum or Average | 0.478831E+11 | |||
Minimum of Months | 0.00 | 0.00 | -24.9 | |
Maximum of Months | 0.152191E+11 | 18996.18 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.920962E+10 | 19717.39 | 09-JAN-04:01 | -27.2 |
February | 0.432887E+10 | 19482.66 | 05-FEB-06:52 | -20.0 |
March | 0.261626E+10 | 19434.94 | 06-MAR-05:01 | -18.4 |
April | 0.627936E+09 | 17005.94 | 29-APR-03:02 | -6.9 |
May | 0.571066E+09 | 17550.37 | 08-MAY-03:01 | -2.7 |
June | 11853648.70 | 15189.89 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 8391072.61 | 9762.80 | 18-AUG-05:02 | 7.30 |
September | 0.160061E+09 | 16212.17 | 19-SEP-04:01 | 2.20 |
October | 0.631875E+09 | 18097.84 | 10-OCT-03:11 | -4.3 |
November | 0.290580E+10 | 19350.63 | 26-NOV-18:42 | -13.9 |
December | 0.659684E+10 | 19953.91 | 31-DEC-03:41 | -24.9 |
Annual Sum or Average | 0.276686E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.920962E+10 | 19953.91 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106632E+11 | 25650.26 | 09-JAN-04:01 | -27.2 |
February | 0.463241E+10 | 25407.39 | 05-FEB-06:52 | -20.0 |
March | 0.323022E+10 | 25284.05 | 06-MAR-05:01 | -18.4 |
April | 0.969029E+09 | 22169.00 | 29-APR-03:02 | -6.9 |
May | 0.964722E+09 | 23040.31 | 08-MAY-03:01 | -2.7 |
June | 36856164.44 | 19889.78 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 20153161.82 | 15066.42 | 18-AUG-05:02 | 7.30 |
September | 0.200556E+09 | 20977.16 | 19-SEP-04:01 | 2.20 |
October | 0.659536E+09 | 23603.57 | 10-OCT-03:11 | -4.3 |
November | 0.309382E+10 | 25104.82 | 27-NOV-04:01 | -15.8 |
December | 0.728679E+10 | 25935.30 | 31-DEC-03:41 | -24.9 |
Annual Sum or Average | 0.317572E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.106632E+11 | 25935.30 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.852739E+10 | 22214.46 | 09-JAN-04:01 | -27.2 |
February | 0.354706E+10 | 21616.71 | 05-FEB-08:12 | -20.2 |
March | 0.214604E+10 | 21683.62 | 06-MAR-05:01 | -18.4 |
April | 0.464646E+09 | 18032.92 | 29-APR-04:01 | -7.8 |
May | 0.439470E+09 | 19818.23 | 08-MAY-03:01 | -2.7 |
June | 14742318.89 | 10187.12 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 9459312.34 | 9574.54 | 18-AUG-05:02 | 7.30 |
September | 0.116778E+09 | 18011.85 | 19-SEP-04:01 | 2.20 |
October | 0.445764E+09 | 20150.90 | 10-OCT-03:11 | -4.3 |
November | 0.219463E+10 | 21626.04 | 27-NOV-04:01 | -15.8 |
December | 0.521703E+10 | 22161.70 | 31-DEC-03:41 | -24.9 |
Annual Sum or Average | 0.231230E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.852739E+10 | 22214.46 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219929E+10 | 12869.87 | 24-JAN-06:03 | 8.22 |
February | 0.901693E+09 | 14023.53 | 13-FEB-06:01 | 2.80 |
March | 0.355999E+09 | 13969.24 | 09-MAR-06:01 | 2.30 |
April | 0.139565E+09 | 12514.28 | 17-APR-03:02 | 9.40 |
May | 76571375.79 | 11289.14 | 01-MAY-04:02 | -0.6 |
June | 91676016.20 | 9835.52 | 19-JUN-03:02 | 13.53 |
July | 0.116219E+09 | 10707.47 | 05-JUL-03:02 | 9.90 |
August | 0.117760E+09 | 11052.32 | 23-AUG-03:02 | 11.20 |
September | 84716979.22 | 10111.73 | 20-SEP-04:01 | 3.30 |
October | 95393863.72 | 10984.45 | 30-OCT-03:02 | 5.82 |
November | 0.211252E+09 | 14248.76 | 30-NOV-06:01 | 1.10 |
December | 0.416540E+09 | 14976.91 | 19-DEC-05:01 | 3.40 |
Annual Sum or Average | 0.480667E+10 | |||
Minimum of Months | 76571375.79 | 9835.52 | -0.6 | |
Maximum of Months | 0.219929E+10 | 14976.91 | 13.53 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.522055E+10 | 14420.89 | 09-JAN-06:12 | -27.2 |
February | 0.291042E+10 | 10394.59 | 06-FEB-06:03 | 0.60 |
March | 0.149631E+10 | 8273.31 | 06-MAR-13:30 | -0.3 |
April | 0.136226E+09 | 8065.10 | 16-APR-17:11 | 19.80 |
May | 0.393593E+09 | 8533.81 | 03-MAY-05:03 | 0.92 |
June | 61500443.99 | 7065.50 | 19-JUN-05:02 | 11.78 |
July | 71214996.40 | 8869.62 | 16-JUL-16:31 | 33.13 |
August | 58538310.94 | 9600.87 | 06-AUG-16:01 | 35.50 |
September | 79332405.17 | 8183.59 | 15-SEP-05:02 | 12.80 |
October | 0.256128E+09 | 8708.93 | 13-OCT-05:02 | 14.03 |
November | 0.131129E+10 | 7627.45 | 12-NOV-13:32 | -0.6 |
December | 0.302360E+10 | 8723.15 | 26-DEC-06:04 | -7.9 |
Annual Sum or Average | 0.150187E+11 | |||
Minimum of Months | 58538310.94 | 7065.50 | -27.2 | |
Maximum of Months | 0.522055E+10 | 14420.89 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208053E+11 | 35014.76 | 11-JAN-05:12 | -30.2 |
February | 0.110759E+11 | 29159.56 | 04-FEB-05:13 | -20.2 |
March | 0.769377E+10 | 33132.90 | 06-MAR-05:08 | -18.4 |
April | 0.285824E+10 | 15206.08 | 29-APR-05:13 | -7.6 |
May | 0.215487E+10 | 22498.21 | 08-MAY-04:12 | -2.4 |
June | 0.368333E+09 | 17752.95 | 14-JUN-05:02 | 7.30 |
July | 0.137864E+09 | 16908.68 | 12-JUL-05:03 | 6.85 |
August | 0.263193E+09 | 16951.20 | 03-AUG-05:03 | 8.12 |
September | 0.104570E+10 | 17738.60 | 28-SEP-05:03 | 8.90 |
October | 0.283722E+10 | 21033.93 | 10-OCT-04:13 | -5.4 |
November | 0.804937E+10 | 31305.07 | 27-NOV-05:09 | -15.4 |
December | 0.156245E+11 | 32169.85 | 29-DEC-05:22 | -25.0 |
Annual Sum or Average | 0.729143E+11 | |||
Minimum of Months | 0.137864E+09 | 15206.08 | -30.2 | |
Maximum of Months | 0.208053E+11 | 35014.76 | 8.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65778145.37 | 640.39 | 09-JAN-03:44 | -27.2 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 65778145.37 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 65778145.37 | 640.39 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.563361E+09 | 662.87 | 29-JAN-17:50 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 3007558.18 | 173.25 | 08-MAY-04:12 | -2.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.566368E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.9 | |
Maximum of Months | 0.563361E+09 | 662.87 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.895974E+09 | 694.06 | 29-JAN-17:50 | -21.9 |
February | 69885876.91 | 644.48 | 05-FEB-18:40 | -18.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 2514822.08 | 778.84 | 30-APR-23:05 | -1.3 |
May | 0.127606E+09 | 668.29 | 01-MAY-00:15 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 31059390.17 | 530.57 | 17-SEP-07:25 | 3.60 |
October | 388126.45 | 462.65 | 10-OCT-03:40 | -4.6 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.112743E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.9 | |
Maximum of Months | 0.895974E+09 | 778.84 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200626E+11 | 20994.62 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.181982E+11 | 20994.62 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.216246E+11 | 20994.62 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.193152E+11 | 20994.62 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.208436E+11 | 20994.62 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.207428E+11 | 20994.62 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.194159E+11 | 20994.62 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.216246E+11 | 20994.62 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.193152E+11 | 20994.62 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.200626E+11 | 20994.62 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.198274E+11 | 20994.62 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.194159E+11 | 20994.62 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.240449E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.181982E+11 | 20994.62 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.216246E+11 | 20994.62 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.174291E+10 | 2367.39 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.146587E+10 | 2130.26 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.167143E+10 | 2276.96 | 17-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.145175E+10 | 1870.19 | 14-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.153397E+10 | 1667.18 | 03-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.150617E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.142879E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.159751E+10 | 1454.29 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.147368E+10 | 1903.66 | 11-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.159298E+10 | 2367.39 | 30-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.167149E+10 | 2367.39 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.169739E+10 | 2367.39 | 01-DEC-16:40 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.188339E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.142879E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.174291E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110380E+10 | 1525.64 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.936931E+09 | 1325.94 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107152E+10 | 1467.36 | 17-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.934366E+09 | 1168.51 | 14-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.990416E+09 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.975320E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.922519E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.103231E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.948439E+09 | 1113.40 | 13-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.101533E+10 | 1525.64 | 30-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.106365E+10 | 1525.64 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.107574E+10 | 1525.64 | 01-DEC-16:40 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120704E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.922519E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.110380E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.169573E+10 | 2367.44 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.144019E+10 | 1935.52 | 02-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166019E+10 | 2277.01 | 17-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145334E+10 | 1867.37 | 14-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.153879E+10 | 1678.53 | 03-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.151417E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.143419E+10 | 1454.32 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.160307E+10 | 1454.32 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147153E+10 | 1866.72 | 11-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.156703E+10 | 2367.44 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.162683E+10 | 2367.44 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.164265E+10 | 2367.44 | 01-DEC-16:40 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.186477E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.143419E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.169573E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.111120E+10 | 1525.64 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.937270E+09 | 1379.11 | 02-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107607E+10 | 1467.36 | 17-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.937539E+09 | 1226.09 | 14-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.990351E+09 | 1115.36 | 03-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.972386E+09 | 937.20 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.923109E+09 | 937.20 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103173E+10 | 1074.29 | 17-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.950334E+09 | 1298.16 | 11-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.102285E+10 | 1525.64 | 30-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.106132E+10 | 1525.64 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.107549E+10 | 1525.64 | 01-DEC-16:40 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.120896E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.923109E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.111120E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.174560E+10 | 2367.39 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.146807E+10 | 2138.92 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.167265E+10 | 2279.69 | 17-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.145247E+10 | 1885.11 | 14-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.153433E+10 | 1687.96 | 03-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.150653E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.142906E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.159787E+10 | 1454.29 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.147463E+10 | 1917.27 | 11-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.159484E+10 | 2367.39 | 30-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.167452E+10 | 2367.39 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.170163E+10 | 2367.39 | 01-DEC-16:40 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.188522E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.142906E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.174560E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110432E+10 | 1525.64 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.937324E+09 | 1330.59 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107181E+10 | 1467.80 | 17-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.934523E+09 | 1172.96 | 14-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.990563E+09 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.975505E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.922648E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.103252E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.948667E+09 | 1119.23 | 13-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.101588E+10 | 1525.64 | 30-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.106419E+10 | 1525.64 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.107649E+10 | 1525.64 | 01-DEC-16:40 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120744E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.922648E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.110432E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.169686E+10 | 2367.44 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.144112E+10 | 1950.52 | 02-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166122E+10 | 2279.74 | 17-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145403E+10 | 1882.39 | 14-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.153939E+10 | 1698.88 | 03-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.151482E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.143465E+10 | 1454.32 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.160378E+10 | 1593.65 | 17-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147210E+10 | 1881.74 | 11-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.156814E+10 | 2367.44 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.162821E+10 | 2367.44 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.164406E+10 | 2367.44 | 01-DEC-16:40 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.186584E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.143465E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.169686E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.111163E+10 | 1525.64 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.937696E+09 | 1380.86 | 02-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107625E+10 | 1467.80 | 17-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.937740E+09 | 1228.37 | 14-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.990470E+09 | 1118.46 | 03-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.972570E+09 | 937.20 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.923209E+09 | 937.20 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103194E+10 | 1077.70 | 17-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.950707E+09 | 1299.84 | 11-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.102344E+10 | 1525.64 | 30-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.106194E+10 | 1525.64 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.107617E+10 | 1525.64 | 01-DEC-16:40 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.120938E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.923209E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.111163E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.174560E+10 | 2367.39 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.146809E+10 | 2139.17 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.167265E+10 | 2279.59 | 17-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.145247E+10 | 1884.63 | 14-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.153432E+10 | 1687.30 | 03-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.150654E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.142906E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.159786E+10 | 1454.29 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.147463E+10 | 1917.03 | 11-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.159487E+10 | 2367.39 | 30-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.167455E+10 | 2367.39 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.170168E+10 | 2367.39 | 01-DEC-16:40 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.188523E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.142906E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.174560E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110432E+10 | 1525.64 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.937335E+09 | 1330.86 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107175E+10 | 1467.74 | 17-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.934523E+09 | 1172.70 | 14-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.990567E+09 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.975509E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.922651E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.103252E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.948670E+09 | 1119.02 | 13-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.101589E+10 | 1525.64 | 30-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.106442E+10 | 1525.64 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.107651E+10 | 1525.64 | 01-DEC-16:40 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120747E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.922651E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.110432E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.169687E+10 | 2367.44 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.144112E+10 | 1950.66 | 02-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166122E+10 | 2279.64 | 17-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145403E+10 | 1881.91 | 14-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.153939E+10 | 1698.22 | 03-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.151482E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.143466E+10 | 1454.32 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.160376E+10 | 1592.97 | 17-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147210E+10 | 1881.50 | 11-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.156826E+10 | 2367.44 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.162822E+10 | 2367.44 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.164408E+10 | 2367.44 | 01-DEC-16:40 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.186585E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.143466E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.169687E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.111164E+10 | 1525.64 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.937705E+09 | 1380.84 | 02-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107625E+10 | 1467.74 | 17-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.937751E+09 | 1228.07 | 14-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.990471E+09 | 1118.06 | 03-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.972574E+09 | 937.20 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.923211E+09 | 937.20 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103194E+10 | 1077.28 | 17-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.950710E+09 | 1299.68 | 11-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.102346E+10 | 1525.64 | 30-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.106197E+10 | 1525.64 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.107619E+10 | 1525.64 | 01-DEC-16:40 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.120939E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.923211E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.111164E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.565679E+10 | 5919.59 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.513113E+10 | 5919.59 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.609720E+10 | 5919.59 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.544605E+10 | 5919.59 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.587700E+10 | 5919.59 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.584858E+10 | 5919.59 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.547447E+10 | 5919.59 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.609720E+10 | 5919.59 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.544605E+10 | 5919.59 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.565679E+10 | 5919.59 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.559049E+10 | 5919.59 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.547447E+10 | 5919.59 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.677962E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.513113E+10 | 5919.59 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.609720E+10 | 5919.59 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.208436E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.207428E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.198274E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.240449E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.174291E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153900E+10 |
February | 0.136985E+10 | 0.146587E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123247E+10 |
March | 0.163685E+10 | 0.167143E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112437E+10 |
April | 0.145243E+10 | 0.145175E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817039E+09 |
May | 0.157338E+10 | 0.153397E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1862219.08 | 0.800693E+09 |
June | 0.156900E+10 | 0.150617E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9446304.45 | 0.395919E+09 |
July | 0.145680E+10 | 0.142879E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33091435.56 | 0.258816E+09 |
August | 0.163685E+10 | 0.159751E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27483426.73 | 0.284711E+09 |
September | 0.145243E+10 | 0.147368E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18254302.96 | 0.527194E+09 |
October | 0.150991E+10 | 0.159298E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109487.54 | 0.795643E+09 |
November | 0.149516E+10 | 0.167149E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112722E+10 |
December | 0.145680E+10 | 0.169739E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143156E+10 |
Annual Sum or Average | 0.181194E+11 | 0.188339E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90247176.32 | 0.103346E+11 |
Minimum of Months | 0.136985E+10 | 0.142879E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258816E+09 |
Maximum of Months | 0.163685E+10 | 0.174291E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33091435.56 | 0.153900E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.110380E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102340E+10 |
February | 0.882782E+09 | 0.936931E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820191E+09 |
March | 0.105485E+10 | 0.107152E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738782E+09 |
April | 0.936002E+09 | 0.934366E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531741E+09 |
May | 0.101394E+10 | 0.990416E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1393951.39 | 0.522185E+09 |
June | 0.101113E+10 | 0.975320E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6718324.70 | 0.256089E+09 |
July | 0.938820E+09 | 0.922519E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23443329.88 | 0.161622E+09 |
August | 0.105485E+10 | 0.103231E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19180440.38 | 0.173177E+09 |
September | 0.936002E+09 | 0.948439E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12692114.81 | 0.346369E+09 |
October | 0.973041E+09 | 0.101533E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106231.29 | 0.522424E+09 |
November | 0.963541E+09 | 0.106365E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732419E+09 |
December | 0.938820E+09 | 0.107574E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934372E+09 |
Annual Sum or Average | 0.116768E+11 | 0.120704E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63534392.44 | 0.676278E+10 |
Minimum of Months | 0.882782E+09 | 0.922519E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161622E+09 |
Maximum of Months | 0.105485E+10 | 0.110380E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23443329.88 | 0.102340E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.169573E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154822E+10 |
February | 0.136988E+10 | 0.144019E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126346E+10 |
March | 0.163688E+10 | 0.166019E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112896E+10 |
April | 0.145246E+10 | 0.145334E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811174E+09 |
May | 0.157341E+10 | 0.153879E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1894239.02 | 0.784367E+09 |
June | 0.156904E+10 | 0.151417E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9585417.22 | 0.386917E+09 |
July | 0.145684E+10 | 0.143419E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32277700.27 | 0.251090E+09 |
August | 0.163688E+10 | 0.160307E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27015640.32 | 0.279335E+09 |
September | 0.145246E+10 | 0.147153E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15747337.83 | 0.533820E+09 |
October | 0.150994E+10 | 0.156703E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104084.84 | 0.812795E+09 |
November | 0.149520E+10 | 0.162683E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112886E+10 |
December | 0.145684E+10 | 0.164265E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143286E+10 |
Annual Sum or Average | 0.181198E+11 | 0.186477E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86624419.50 | 0.103619E+11 |
Minimum of Months | 0.136988E+10 | 0.143419E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251090E+09 |
Maximum of Months | 0.163688E+10 | 0.169573E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32277700.27 | 0.154822E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.111120E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105395E+10 |
February | 0.882782E+09 | 0.937270E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876418E+09 |
March | 0.105485E+10 | 0.107607E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801065E+09 |
April | 0.936002E+09 | 0.937539E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603266E+09 |
May | 0.101394E+10 | 0.990351E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1224856.78 | 0.563421E+09 |
June | 0.101113E+10 | 0.972386E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6060798.71 | 0.284133E+09 |
July | 0.938820E+09 | 0.923109E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20341913.37 | 0.192864E+09 |
August | 0.105485E+10 | 0.103173E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17377724.52 | 0.210849E+09 |
September | 0.936002E+09 | 0.950334E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12203675.18 | 0.368332E+09 |
October | 0.973041E+09 | 0.102285E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78043.58 | 0.569464E+09 |
November | 0.963541E+09 | 0.106132E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808360E+09 |
December | 0.938820E+09 | 0.107549E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103608E+10 |
Annual Sum or Average | 0.116768E+11 | 0.120896E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57287012.14 | 0.736819E+10 |
Minimum of Months | 0.882782E+09 | 0.923109E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192864E+09 |
Maximum of Months | 0.105485E+10 | 0.111120E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20341913.37 | 0.105395E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.174560E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328485E+10 |
February | 0.136985E+10 | 0.146807E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252416E+10 |
March | 0.163685E+10 | 0.167265E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234215E+10 |
April | 0.145243E+10 | 0.145247E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168117E+10 |
May | 0.157338E+10 | 0.153433E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4140923.43 | 0.170647E+10 |
June | 0.156900E+10 | 0.150653E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22193700.66 | 0.881057E+09 |
July | 0.145680E+10 | 0.142906E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78657649.30 | 0.593988E+09 |
August | 0.163685E+10 | 0.159787E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64109500.13 | 0.647294E+09 |
September | 0.145243E+10 | 0.147463E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42953648.19 | 0.112759E+10 |
October | 0.150991E+10 | 0.159484E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2068727.57 | 0.160258E+10 |
November | 0.149516E+10 | 0.167452E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227687E+10 |
December | 0.145680E+10 | 0.170163E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287598E+10 |
Annual Sum or Average | 0.181194E+11 | 0.188522E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214124E+09 | 0.215441E+11 |
Minimum of Months | 0.136985E+10 | 0.142906E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593988E+09 |
Maximum of Months | 0.163685E+10 | 0.174560E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78657649.30 | 0.328485E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.110432E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221153E+10 |
February | 0.649041E+09 | 0.937324E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172304E+10 |
March | 0.773965E+09 | 0.107181E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159154E+10 |
April | 0.688021E+09 | 0.934523E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115481E+10 |
May | 0.744847E+09 | 0.990563E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3043120.60 | 0.113551E+10 |
June | 0.742030E+09 | 0.975505E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15210191.91 | 0.590359E+09 |
July | 0.690839E+09 | 0.922648E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51859719.12 | 0.402535E+09 |
August | 0.773965E+09 | 0.103252E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42925100.46 | 0.431475E+09 |
September | 0.688021E+09 | 0.948667E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28594114.95 | 0.762729E+09 |
October | 0.715730E+09 | 0.101588E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 732055.87 | 0.109553E+10 |
November | 0.708685E+09 | 0.106419E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152934E+10 |
December | 0.690839E+09 | 0.107649E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193343E+10 |
Annual Sum or Average | 0.858171E+10 | 0.120744E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142364E+09 | 0.145618E+11 |
Minimum of Months | 0.649041E+09 | 0.922648E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402535E+09 |
Maximum of Months | 0.773965E+09 | 0.110432E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51859719.12 | 0.221153E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.169686E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344980E+10 |
February | 0.136988E+10 | 0.144112E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278248E+10 |
March | 0.163688E+10 | 0.166122E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250202E+10 |
April | 0.145246E+10 | 0.145403E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179425E+10 |
May | 0.157341E+10 | 0.153939E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4071243.12 | 0.174106E+10 |
June | 0.156904E+10 | 0.151482E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21803794.15 | 0.879139E+09 |
July | 0.145684E+10 | 0.143465E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73171464.57 | 0.601758E+09 |
August | 0.163688E+10 | 0.160378E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61689625.27 | 0.669528E+09 |
September | 0.145246E+10 | 0.147210E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34922487.81 | 0.120524E+10 |
October | 0.150994E+10 | 0.156814E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 154752.03 | 0.180145E+10 |
November | 0.149520E+10 | 0.162821E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245713E+10 |
December | 0.145684E+10 | 0.164406E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306429E+10 |
Annual Sum or Average | 0.181198E+11 | 0.186584E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195813E+09 | 0.229481E+11 |
Minimum of Months | 0.136988E+10 | 0.143465E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601758E+09 |
Maximum of Months | 0.163688E+10 | 0.169686E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73171464.57 | 0.344980E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.111163E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223373E+10 |
February | 0.882782E+09 | 0.937696E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175715E+10 |
March | 0.105485E+10 | 0.107625E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161747E+10 |
April | 0.936002E+09 | 0.937740E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119167E+10 |
May | 0.101394E+10 | 0.990470E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2814552.95 | 0.119580E+10 |
June | 0.101113E+10 | 0.972570E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14248041.73 | 0.610353E+09 |
July | 0.938820E+09 | 0.923209E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51075701.59 | 0.428529E+09 |
August | 0.105485E+10 | 0.103194E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42163258.29 | 0.449173E+09 |
September | 0.936002E+09 | 0.950707E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29565124.08 | 0.775092E+09 |
October | 0.973041E+09 | 0.102344E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 686327.39 | 0.111569E+10 |
November | 0.963541E+09 | 0.106194E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156441E+10 |
December | 0.938820E+09 | 0.107617E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196809E+10 |
Annual Sum or Average | 0.116768E+11 | 0.120938E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140553E+09 | 0.149072E+11 |
Minimum of Months | 0.882782E+09 | 0.923209E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428529E+09 |
Maximum of Months | 0.105485E+10 | 0.111163E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51075701.59 | 0.223373E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.174560E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396069E+10 |
February | 0.136985E+10 | 0.146809E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292819E+10 |
March | 0.163685E+10 | 0.167265E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273296E+10 |
April | 0.145243E+10 | 0.145247E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190044E+10 |
May | 0.157338E+10 | 0.153432E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5134859.16 | 0.197595E+10 |
June | 0.156900E+10 | 0.150654E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27006209.05 | 0.104818E+10 |
July | 0.145680E+10 | 0.142906E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97911685.83 | 0.712220E+09 |
August | 0.163685E+10 | 0.159786E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77775112.42 | 0.767145E+09 |
September | 0.145243E+10 | 0.147463E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54576293.87 | 0.129095E+10 |
October | 0.150991E+10 | 0.159487E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6810949.41 | 0.175291E+10 |
November | 0.149516E+10 | 0.167455E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260751E+10 |
December | 0.145680E+10 | 0.170168E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343875E+10 |
Annual Sum or Average | 0.181194E+11 | 0.188523E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269215E+09 | 0.251159E+11 |
Minimum of Months | 0.136985E+10 | 0.142906E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712220E+09 |
Maximum of Months | 0.163685E+10 | 0.174560E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97911685.83 | 0.396069E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.110432E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265991E+10 |
February | 0.882782E+09 | 0.937335E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199311E+10 |
March | 0.105485E+10 | 0.107175E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186432E+10 |
April | 0.936002E+09 | 0.934523E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133018E+10 |
May | 0.101394E+10 | 0.990567E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3489844.61 | 0.133698E+10 |
June | 0.101113E+10 | 0.975509E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17764221.02 | 0.720440E+09 |
July | 0.938820E+09 | 0.922651E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60905035.59 | 0.497525E+09 |
August | 0.105485E+10 | 0.103252E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50665395.88 | 0.528423E+09 |
September | 0.936002E+09 | 0.948670E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32855774.14 | 0.900596E+09 |
October | 0.973041E+09 | 0.101589E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1770321.13 | 0.122246E+10 |
November | 0.963541E+09 | 0.106442E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175729E+10 |
December | 0.938820E+09 | 0.107651E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230356E+10 |
Annual Sum or Average | 0.116768E+11 | 0.120747E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167451E+09 | 0.171148E+11 |
Minimum of Months | 0.882782E+09 | 0.922651E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497525E+09 |
Maximum of Months | 0.105485E+10 | 0.110432E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60905035.59 | 0.265991E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.169687E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407933E+10 |
February | 0.136988E+10 | 0.144112E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319385E+10 |
March | 0.163688E+10 | 0.166122E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292218E+10 |
April | 0.145246E+10 | 0.145403E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205864E+10 |
May | 0.157341E+10 | 0.153939E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4843004.36 | 0.203909E+10 |
June | 0.156904E+10 | 0.151482E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25963442.62 | 0.105968E+10 |
July | 0.145684E+10 | 0.143466E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88678024.88 | 0.732740E+09 |
August | 0.163688E+10 | 0.160376E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74270583.60 | 0.811253E+09 |
September | 0.145246E+10 | 0.147210E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41787211.61 | 0.141595E+10 |
October | 0.150994E+10 | 0.156826E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 221301.19 | 0.202884E+10 |
November | 0.149520E+10 | 0.162822E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279442E+10 |
December | 0.145684E+10 | 0.164408E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357241E+10 |
Annual Sum or Average | 0.181198E+11 | 0.186585E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235764E+09 | 0.267084E+11 |
Minimum of Months | 0.136988E+10 | 0.143466E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732740E+09 |
Maximum of Months | 0.163688E+10 | 0.169687E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88678024.88 | 0.407933E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.111164E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267763E+10 |
February | 0.882782E+09 | 0.937705E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204711E+10 |
March | 0.105485E+10 | 0.107625E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190818E+10 |
April | 0.936002E+09 | 0.937751E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138140E+10 |
May | 0.101394E+10 | 0.990471E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3371888.32 | 0.140866E+10 |
June | 0.101113E+10 | 0.972574E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17211831.06 | 0.739467E+09 |
July | 0.938820E+09 | 0.923211E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62509058.37 | 0.523924E+09 |
August | 0.105485E+10 | 0.103194E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51152357.23 | 0.545221E+09 |
September | 0.936002E+09 | 0.950710E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36116128.94 | 0.914169E+09 |
October | 0.973041E+09 | 0.102346E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1640111.82 | 0.126641E+10 |
November | 0.963541E+09 | 0.106197E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181186E+10 |
December | 0.938820E+09 | 0.107619E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233993E+10 |
Annual Sum or Average | 0.116768E+11 | 0.120939E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172001E+09 | 0.175640E+11 |
Minimum of Months | 0.882782E+09 | 0.923211E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523924E+09 |
Maximum of Months | 0.105485E+10 | 0.111164E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62509058.37 | 0.267763E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.565679E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.513113E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.609720E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.544605E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.587700E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.584858E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.547447E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.609720E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.544605E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.565679E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.559049E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.547447E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.677962E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.513113E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.609720E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328148E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263885E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238236E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172396E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2914567.06 | 0.167644E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15285826.70 | 0.826866E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59053999.16 | 0.550850E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50000525.51 | 0.611704E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33544081.19 | 0.112338E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71841.01 | 0.169552E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240910E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306560E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160871E+09 | 0.219861E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550850E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59053999.16 | 0.328148E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551985E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438270E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403224E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292160E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5459477.99 | 0.289278E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28154225.78 | 0.144866E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109688E+09 | 0.973734E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91106338.41 | 0.108137E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62055606.32 | 0.195694E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199086.92 | 0.285896E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401557E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501341E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296663E+09 | 0.370978E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973734E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109688E+09 | 0.551985E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579931E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450078E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424787E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306359E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3363265.96 | 0.313772E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23056400.20 | 0.165081E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96676047.94 | 0.111990E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85797199.33 | 0.121811E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54696039.93 | 0.209194E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286852E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402922E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511201E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263589E+09 | 0.388398E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111990E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96676047.94 | 0.579931E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 20994.62 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 20994.62 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 20994.62 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 20994.62 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 20994.62 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 20994.62 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 20994.62 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 20994.62 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 20994.62 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 20994.62 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 20994.62 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 20994.62 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2367.39 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2513.50 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 2130.26 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1587.93 | 17-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 2276.96 | 17-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1930.03 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1870.19 | 14-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1386.85 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1667.18 | 03-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.38 | 20-MAY-17:02 | 2620.39 | 22-MAY-03:53 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.69 | 29-JUN-15:00 | 1112.70 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 283.72 | 30-JUL-12:00 | 667.65 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 1454.29 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.05 | 06-AUG-17:52 | 858.06 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1903.66 | 11-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 416.41 | 03-SEP-12:52 | 1479.49 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2367.39 | 30-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | 18-OCT-14:00 | 1262.75 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1506.87 | 26-NOV-19:51 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-16:40 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2346.50 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.65 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 416.41 | 2620.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1675.05 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1325.94 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1038.94 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1467.36 | 17-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1258.87 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1168.51 | 14-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 905.25 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.27 | 20-MAY-17:02 | 1713.52 | 22-MAY-04:30 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.96 | 24-JUN-17:10 | 719.97 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.34 | 30-JUL-12:00 | 429.41 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.08 | 06-AUG-17:52 | 550.00 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1113.40 | 13-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.97 | 03-SEP-12:52 | 966.31 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1525.64 | 30-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.02 | 15-OCT-14:00 | 821.76 | 30-OCT-22:10 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1003.92 | 28-NOV-05:58 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:40 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1513.90 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.41 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 287.97 | 1713.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2367.44 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2512.57 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1935.52 | 02-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1562.86 | 17-FEB-04:00 |
March | 2010.83 | 01-MAR-10:09 | 2277.01 | 17-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1956.59 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1867.37 | 14-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1368.43 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1678.53 | 03-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.03 | 20-MAY-17:02 | 2530.42 | 22-MAY-03:53 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.69 | 29-JUN-15:00 | 1088.98 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 1454.32 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.36 | 30-JUL-14:00 | 652.44 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 1454.32 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.97 | 06-AUG-17:50 | 853.96 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1866.72 | 11-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.25 | 03-SEP-12:55 | 1433.70 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2367.44 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.91 | 18-OCT-14:10 | 1279.77 | 30-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1505.90 | 28-NOV-05:55 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-16:40 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2262.50 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.44 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 351.25 | 2530.42 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1677.25 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1379.11 | 02-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1127.82 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1467.36 | 17-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1371.68 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1226.09 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1012.39 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 1115.36 | 03-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.05 | 20-MAY-17:02 | 1761.69 | 22-MAY-04:30 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.13 | 29-JUN-15:00 | 806.18 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.15 | 30-JUL-12:00 | 499.42 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 1074.29 | 17-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.57 | 06-AUG-17:45 | 668.18 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1298.16 | 11-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.40 | 03-SEP-12:52 | 1016.15 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1525.64 | 30-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 18-OCT-14:00 | 896.67 | 30-OCT-22:50 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1066.98 | 26-NOV-19:51 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:40 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1707.89 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.42 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 308.40 | 1761.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2367.39 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5881.77 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 2138.92 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3236.95 | 08-FEB-22:02 |
March | 2010.79 | 01-MAR-10:09 | 2279.69 | 17-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4113.67 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1885.11 | 14-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2911.46 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1687.96 | 03-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.86 | 20-MAY-17:02 | 5691.66 | 22-MAY-04:53 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.49 | 29-JUN-15:00 | 2341.11 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 693.71 | 30-JUL-12:00 | 1405.09 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 1454.29 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 771.82 | 06-AUG-17:50 | 1737.03 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1917.27 | 11-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 947.96 | 03-SEP-13:00 | 3034.09 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2367.39 | 30-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.47 | 15-OCT-14:10 | 2578.73 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3528.95 | 28-NOV-05:50 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-16:40 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5043.08 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1405.09 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 947.96 | 5881.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1525.64 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3920.83 | 05-JAN-22:01 |
February | 1239.33 | 01-FEB-08:09 | 1330.59 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2157.37 | 08-FEB-22:02 |
March | 1239.33 | 01-MAR-08:09 | 1467.80 | 17-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2731.66 | 02-MAR-23:00 |
April | 1239.33 | 03-APR-07:10 | 1172.96 | 14-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1937.63 | 27-APR-02:00 |
May | 1239.33 | 01-MAY-07:10 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.35 | 20-MAY-17:02 | 3794.48 | 22-MAY-05:00 |
June | 1239.33 | 01-JUN-07:10 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.10 | 24-JUN-17:10 | 1524.41 | 14-JUN-02:00 |
July | 1239.33 | 03-JUL-07:10 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 461.88 | 30-JUL-14:30 | 934.06 | 05-JUL-01:00 |
August | 1239.33 | 01-AUG-07:10 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 576.01 | 06-AUG-17:30 | 1152.79 | 23-AUG-03:00 |
September | 1239.33 | 01-SEP-07:10 | 1119.23 | 13-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 642.20 | 03-SEP-12:52 | 1976.91 | 12-SEP-03:00 |
October | 1239.33 | 02-OCT-07:10 | 1525.64 | 30-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.90 | 15-OCT-14:10 | 1718.74 | 30-OCT-22:00 |
November | 1239.33 | 01-NOV-07:10 | 1525.64 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2352.70 | 28-NOV-05:47 |
December | 1239.33 | 01-DEC-08:09 | 1525.64 | 01-DEC-16:40 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3362.23 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.06 | |||||
Maximum of Months | 1239.33 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 642.20 | 3920.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2367.44 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5884.54 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1950.52 | 02-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3375.39 | 19-FEB-13:00 |
March | 2010.83 | 01-MAR-10:09 | 2279.74 | 17-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4290.66 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1882.39 | 14-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2941.61 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1698.88 | 03-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.14 | 20-MAY-17:02 | 5691.72 | 22-MAY-04:53 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.49 | 29-JUN-15:00 | 2315.61 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 1454.32 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 642.39 | 30-JUL-12:00 | 1418.34 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 1593.65 | 17-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 767.76 | 06-AUG-17:30 | 1782.68 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1881.74 | 11-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 810.14 | 03-SEP-13:00 | 3008.07 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2367.44 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.47 | 18-OCT-15:00 | 2761.72 | 30-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3529.15 | 28-NOV-05:45 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-16:40 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5043.23 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.34 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 810.14 | 5884.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3921.89 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1380.86 | 02-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2163.68 | 17-FEB-05:45 |
March | 1295.83 | 01-MAR-10:09 | 1467.80 | 17-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2824.43 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1228.37 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1965.08 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 1118.46 | 03-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.32 | 20-MAY-17:02 | 3794.49 | 22-MAY-04:57 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.99 | 29-JUN-15:00 | 1583.37 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 592.96 | 30-JUL-11:50 | 1001.53 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 1077.70 | 17-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 568.57 | 06-AUG-12:10 | 1199.80 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1299.84 | 11-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 709.21 | 03-SEP-12:55 | 1982.08 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1525.64 | 30-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.59 | 15-OCT-12:50 | 1760.48 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2352.65 | 28-NOV-05:45 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:40 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3362.21 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1001.53 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 709.21 | 3921.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2367.39 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7293.37 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 2139.17 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4018.66 | 17-FEB-05:50 |
March | 2010.79 | 01-MAR-10:09 | 2279.59 | 17-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4958.09 | 17-MAR-04:45 |
April | 2010.79 | 03-APR-09:09 | 1884.63 | 14-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3310.80 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1687.30 | 03-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.00 | 20-MAY-17:02 | 7102.37 | 22-MAY-04:47 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.92 | 29-JUN-15:00 | 2686.28 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 889.60 | 30-JUL-12:00 | 1610.44 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 1454.29 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 953.01 | 06-AUG-17:40 | 1985.93 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1917.03 | 11-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1192.46 | 03-SEP-13:00 | 3302.78 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2367.39 | 30-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.02 | 15-OCT-14:00 | 3157.47 | 30-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4315.46 | 28-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-16:40 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6180.41 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1610.44 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1192.46 | 7293.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4861.13 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1330.86 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2679.22 | 17-FEB-05:47 |
March | 1295.83 | 01-MAR-10:09 | 1467.74 | 17-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3305.34 | 17-MAR-04:50 |
April | 1295.83 | 03-APR-09:09 | 1172.70 | 14-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2230.30 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.63 | 20-MAY-17:02 | 4734.47 | 22-MAY-04:43 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.28 | 29-JUN-15:00 | 1839.07 | 04-JUN-14:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 569.92 | 30-JUL-14:40 | 1077.62 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 711.59 | 06-AUG-17:40 | 1318.12 | 22-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1119.02 | 13-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 801.42 | 03-SEP-13:00 | 2178.67 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1525.64 | 30-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.76 | 15-OCT-13:50 | 2108.47 | 30-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2948.75 | 28-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:40 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4198.70 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1077.62 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 801.42 | 4861.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2367.44 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7295.80 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1950.66 | 02-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4029.27 | 08-FEB-22:02 |
March | 2010.83 | 01-MAR-10:09 | 2279.64 | 17-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5080.16 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1881.91 | 14-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3372.02 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1698.22 | 03-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 328.46 | 20-MAY-17:02 | 7102.30 | 22-MAY-04:47 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.92 | 29-JUN-15:00 | 2661.21 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 1454.32 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 810.38 | 30-JUL-12:00 | 1634.59 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 1592.97 | 17-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 949.43 | 06-AUG-17:40 | 2049.87 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1881.50 | 11-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 990.91 | 03-SEP-12:55 | 3300.23 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2367.44 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.25 | 18-OCT-14:10 | 3211.15 | 30-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4423.25 | 28-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-16:40 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6297.98 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1634.59 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 990.91 | 7295.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4862.36 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1380.84 | 02-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2682.56 | 08-FEB-22:02 |
March | 1295.83 | 01-MAR-10:09 | 1467.74 | 17-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3358.91 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1228.07 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2264.76 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 1118.06 | 03-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.80 | 20-MAY-17:02 | 4735.00 | 22-MAY-04:47 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.28 | 29-JUN-15:00 | 1826.27 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 739.33 | 30-JUL-12:00 | 1167.39 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 1077.28 | 17-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 684.43 | 06-AUG-12:00 | 1378.72 | 22-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1299.68 | 11-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 903.32 | 03-SEP-13:00 | 2201.44 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1525.64 | 30-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.92 | 15-OCT-12:31 | 2122.88 | 30-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2948.87 | 28-NOV-05:58 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:40 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4198.67 | 01-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1167.39 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 903.32 | 4862.36 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5919.59 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5919.59 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5919.59 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5919.59 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5919.59 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5919.59 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5919.59 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5919.59 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5919.59 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5919.59 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5919.59 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5919.59 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5185.15 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3460.67 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4103.31 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2930.34 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.66 | 20-MAY-17:02 | 5818.28 | 22-MAY-03:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.19 | 29-JUN-15:00 | 2327.57 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.04 | 30-JUL-11:55 | 1367.03 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 669.70 | 06-AUG-17:58 | 1784.74 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 800.18 | 03-SEP-13:00 | 3183.06 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 | 18-OCT-15:00 | 2692.94 | 30-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3279.06 | 26-NOV-19:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5128.39 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1367.03 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 800.18 | 5818.28 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9173.95 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5846.99 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7142.53 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 5092.52 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.50 | 20-MAY-17:02 | 10050.29 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.58 | 29-JUN-15:00 | 4048.43 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.05 | 30-JUL-12:00 | 2373.36 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1246.28 | 06-AUG-17:52 | 3066.91 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1427.84 | 03-SEP-13:00 | 5526.77 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.95 | 18-OCT-14:00 | 4585.81 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5428.91 | 26-NOV-20:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8282.87 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2373.36 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1427.84 | 10050.29 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 10284.09 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5780.34 | 08-FEB-22:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7747.03 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 5315.40 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.09 | 20-MAY-17:02 | 10122.59 | 22-MAY-04:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.27 | 29-JUN-15:00 | 4182.55 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.02 | 30-JUL-11:55 | 2520.59 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1146.84 | 06-AUG-18:00 | 3167.29 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1341.96 | 03-SEP-13:00 | 5422.04 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4845.83 | 30-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5761.72 | 28-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8341.77 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2520.59 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1341.96 | 10284.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 109422.06 | 02-JAN-04:03 | 0.00 | 4665.70 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 108714.50 | 27-FEB-04:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 109493.07 | 27-MAR-03:01 | 0.00 | 9331.40 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 111076.76 | 24-APR-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 111369.96 | 30-MAY-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 113748.30 | 05-JUN-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 114647.14 | 24-JUL-02:52 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 111020.31 | 28-AUG-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 115330.66 | 25-SEP-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 111018.82 | 23-OCT-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 113763.15 | 20-NOV-04:01 | 0.00 | 10497.83 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 112017.84 | 11-DEC-04:01 | 0.00 | 8164.98 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 108714.50 | 0.00 | 4665.70 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 115330.66 | 0.00 | 10497.83 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 85470.72 | 02-JAN-05:01 | 0.00 | 16760.51 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87271.24 | 28-FEB-05:01 | 0.00 | 16760.51 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 87990.47 | 29-MAR-04:01 | 0.00 | 16760.51 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91365.05 | 10-APR-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 94325.69 | 30-MAY-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92244.87 | 05-JUN-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 95202.99 | 05-JUL-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 91027.10 | 23-AUG-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 95353.02 | 11-SEP-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90648.56 | 02-OCT-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 91324.31 | 06-NOV-04:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 88067.31 | 07-DEC-05:01 | 0.00 | 18855.58 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 85470.72 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95353.02 | 0.00 | 18855.58 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22197.39 | 05-JAN-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 32974.19 | 28-FEB-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 72251.87 | 30-MAR-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79501.27 | 25-APR-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82557.55 | 30-MAY-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82945.55 | 23-JUN-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84115.05 | 19-JUL-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86169.38 | 14-AUG-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84765.63 | 11-SEP-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 77892.21 | 17-OCT-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 73286.14 | 08-NOV-06:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28782.98 | 07-DEC-16:30 | 30632.53 | 37709.30 | 36257.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 22197.39 | 0.00 | 5237.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86169.38 | 30632.53 | 37709.30 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17269.51 | 13-JAN-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25420.93 | 28-FEB-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28756.00 | 23-MAR-15:40 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42101.24 | 25-APR-16:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77318.18 | 20-MAY-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83055.98 | 21-JUN-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82170.91 | 19-JUL-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81277.97 | 10-AUG-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82121.42 | 05-SEP-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48080.75 | 19-OCT-05:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27154.23 | 03-NOV-16:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19521.72 | 06-DEC-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17269.51 | 0.00 | 6285.19 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83055.98 | 15316.26 | 18854.65 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3099.00 | 02-JAN-05:01 | 0.00 | 2104.45 | 8093.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.20 |
February | 3977.28 | 27-FEB-16:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.22 |
March | 4409.57 | 27-MAR-14:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.41 |
April | 6875.62 | 07-APR-14:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.97 |
May | 12818.70 | 30-MAY-05:03 | 809.73 | 1004.05 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.02 |
June | 12630.23 | 26-JUN-05:03 | 809.73 | 646.38 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.28 |
July | 12434.53 | 26-JUL-05:02 | 1012.16 | 1069.19 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.32 |
August | 12913.10 | 06-AUG-15:41 | 708.51 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 262.48 | 0.00 |
September | 15722.04 | 04-SEP-16:01 | 910.95 | 727.18 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 110.70 | 0.00 |
October | 5758.45 | 19-OCT-14:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 |
November | 4019.59 | 24-NOV-14:30 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.86 |
December | 3191.03 | 06-DEC-05:01 | 0.00 | 2104.45 | 8093.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 830.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3099.00 | 0.00 | 565.58 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15722.04 | 2010.79 | 2104.45 | 8093.57 | 0.00 | 0.00 | 0.00 | 0.00 | 262.48 | 830.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3740.98 | 02-JAN-05:01 | 0.00 | 1356.19 | 5215.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.76 |
February | 6388.57 | 27-FEB-10:00 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.07 |
March | 8998.90 | 28-MAR-09:20 | 2591.66 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.10 |
April | 11271.55 | 24-APR-08:30 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 |
May | 11467.98 | 19-MAY-08:30 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 |
June | 21345.19 | 25-JUN-07:52 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.51 |
July | 20922.12 | 02-JUL-08:32 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.74 |
August | 20982.84 | 06-AUG-08:22 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.16 |
September | 21612.54 | 04-SEP-08:42 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 |
October | 8583.53 | 18-OCT-09:20 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.01 |
November | 5880.64 | 06-NOV-09:35 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.71 |
December | 3620.85 | 01-DEC-06:02 | 1174.10 | 1525.71 | 5867.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3620.85 | 0.00 | 312.41 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.16 | |
Maximum of Months | 21612.54 | 2591.66 | 1874.40 | 5867.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11419.37 | 19-JAN-13:30 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.04 |
February | 25758.13 | 26-FEB-14:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.67 |
March | 18751.34 | 01-MAR-13:40 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.43 |
April | 18544.08 | 16-APR-12:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.36 |
May | 14809.00 | 19-MAY-13:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 33.90 | 0.00 |
June | 15479.01 | 25-JUN-15:12 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.18 |
July | 22873.94 | 16-JUL-15:22 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 118.39 | 0.00 |
August | 25917.72 | 06-AUG-13:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 225.16 | 0.00 |
September | 28169.66 | 04-SEP-15:21 | 809.75 | 646.40 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 83.67 | 0.00 |
October | 28542.76 | 15-OCT-12:31 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.95 |
November | 22898.53 | 12-NOV-13:32 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.85 |
December | 13178.46 | 12-DEC-12:30 | 1058.33 | 1454.32 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11419.37 | 404.87 | 323.20 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28542.76 | 2010.83 | 1454.32 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 225.16 | 475.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4895.35 | 02-JAN-05:01 | 0.00 | 1356.19 | 5215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.45 |
February | 9917.43 | 28-FEB-16:40 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.32 |
March | 12444.23 | 28-MAR-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.13 |
April | 25973.33 | 16-APR-17:22 | 0.00 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.92 |
May | 25802.33 | 13-MAY-18:22 | 0.00 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.37 |
June | 25757.82 | 18-JUN-17:02 | 0.00 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 |
July | 27760.02 | 16-JUL-17:21 | 0.00 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 45.99 | 0.00 |
August | 27667.00 | 06-AUG-16:21 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 149.60 | 0.00 |
September | 28775.52 | 04-SEP-16:01 | 587.05 | 468.62 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 43.42 | 0.00 |
October | 17848.21 | 15-OCT-15:11 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.31 |
November | 9275.45 | 03-NOV-15:40 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.93 |
December | 8501.44 | 06-DEC-15:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4895.35 | 0.00 | 312.41 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28775.52 | 1239.33 | 1356.19 | 5215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 149.60 | 214.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1778.31 | 13-JAN-17:00 | 1923.11 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.96 |
February | 2893.83 | 27-FEB-13:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.05 |
March | 2808.87 | 23-MAR-13:30 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.74 |
April | 4918.91 | 07-APR-14:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.30 |
May | 7053.07 | 19-MAY-16:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 178.84 | 0.00 |
June | 11399.41 | 21-JUN-05:03 | 809.73 | 646.38 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.11 |
July | 15058.68 | 16-JUL-18:31 | 0.00 | 807.98 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 211.30 | 0.00 |
August | 14214.44 | 06-AUG-17:21 | 0.00 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 697.79 | 0.00 |
September | 11882.22 | 04-SEP-14:11 | 708.51 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 308.33 | 0.00 |
October | 4186.86 | 19-OCT-14:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.97 |
November | 2799.71 | 03-NOV-13:30 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.39 |
December | 1999.14 | 06-DEC-16:20 | 1923.11 | 2192.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1778.31 | 0.00 | 565.58 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15058.68 | 2010.79 | 2367.39 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 697.79 | 542.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2508.06 | 13-JAN-06:03 | 913.19 | 1186.66 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.29 |
February | 4578.83 | 26-FEB-11:52 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 723.93 |
March | 6868.85 | 28-MAR-10:05 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.50 |
April | 10382.86 | 25-APR-09:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.65 |
May | 11855.12 | 19-MAY-08:50 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.37 |
June | 20821.35 | 04-JUN-07:42 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.06 |
July | 24537.22 | 16-JUL-09:11 | 521.82 | 416.55 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.38 |
August | 25100.89 | 06-AUG-09:21 | 587.05 | 468.62 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.15 |
September | 22391.49 | 04-SEP-08:52 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.64 |
October | 7088.57 | 18-OCT-10:10 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.83 |
November | 3813.69 | 03-NOV-13:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.95 |
December | 2652.07 | 20-DEC-10:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2508.06 | 326.14 | 260.35 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.15 | |
Maximum of Months | 25100.89 | 2478.65 | 1874.40 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 723.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10904.24 | 19-JAN-14:00 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.93 |
February | 28055.29 | 26-FEB-13:12 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1241.22 |
March | 19948.17 | 01-MAR-13:50 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.03 |
April | 17735.91 | 16-APR-13:52 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 802.38 |
May | 15124.33 | 19-MAY-13:40 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 85.14 | 0.00 |
June | 14907.61 | 30-JUN-13:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 40.55 | 0.00 |
July | 27487.61 | 16-JUL-13:52 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 137.42 | 0.00 |
August | 27696.65 | 06-AUG-14:41 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 351.82 | 0.00 |
September | 30732.60 | 03-SEP-12:41 | 910.97 | 727.20 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 381.38 | 0.00 |
October | 27282.21 | 15-OCT-13:22 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.56 |
November | 24315.79 | 12-NOV-13:32 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.00 |
December | 11219.99 | 12-DEC-14:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10904.24 | 404.87 | 323.20 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30732.60 | 2010.83 | 1454.32 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 381.38 | 1241.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3386.28 | 13-JAN-15:50 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.87 |
February | 6693.60 | 28-FEB-16:40 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.78 |
March | 8340.89 | 28-MAR-17:00 | 391.37 | 520.67 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.46 |
April | 22865.17 | 16-APR-17:11 | 0.00 | 468.62 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.84 |
May | 23168.34 | 28-MAY-17:52 | 0.00 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 670.28 |
June | 23796.50 | 18-JUN-17:31 | 0.00 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.49 |
July | 27664.98 | 16-JUL-17:11 | 0.00 | 520.69 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 66.84 | 0.00 |
August | 24794.91 | 06-AUG-16:41 | 652.28 | 520.69 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 353.44 | 0.00 |
September | 26400.92 | 04-SEP-16:51 | 587.05 | 468.62 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 82.76 | 0.00 |
October | 9677.05 | 16-OCT-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.46 |
November | 5093.91 | 03-NOV-15:50 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.24 |
December | 3693.53 | 06-DEC-15:50 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3386.28 | 0.00 | 312.41 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27664.98 | 1239.33 | 937.20 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 353.44 | 670.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2087.53 | 14-JAN-17:03 | 404.87 | 526.11 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.86 |
February | 2622.12 | 27-FEB-16:10 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.98 |
March | 2821.68 | 29-MAR-16:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 635.94 |
April | 4425.28 | 07-APR-14:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.94 |
May | 7709.16 | 19-MAY-16:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 215.48 | 0.00 |
June | 9530.52 | 29-JUN-15:10 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 350.96 | 0.00 |
July | 15130.90 | 16-JUL-18:41 | 0.00 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 279.53 | 0.00 |
August | 19338.03 | 06-AUG-16:11 | 1012.16 | 807.98 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 739.69 | 0.00 |
September | 8066.96 | 05-SEP-14:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 0.00 |
October | 4115.68 | 18-OCT-13:50 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 60.48 | 0.00 |
November | 2665.86 | 17-NOV-17:00 | 1923.11 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.30 |
December | 2181.97 | 06-DEC-16:20 | 1923.11 | 2192.21 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2087.53 | 0.00 | 526.11 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19338.03 | 2010.79 | 2367.39 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 739.69 | 635.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2513.67 | 19-JAN-06:04 | 1174.10 | 1525.71 | 5867.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.81 |
February | 3276.85 | 28-FEB-10:30 | 2591.66 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.23 |
March | 5190.53 | 23-MAR-10:30 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.21 |
April | 9357.45 | 25-APR-09:40 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.71 |
May | 11400.37 | 19-MAY-09:20 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.00 |
June | 22632.36 | 25-JUN-09:02 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.17 |
July | 22351.13 | 16-JUL-09:22 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.28 |
August | 24303.86 | 06-AUG-08:11 | 521.82 | 416.55 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.18 |
September | 16405.27 | 04-SEP-09:02 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 |
October | 5935.97 | 18-OCT-10:00 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.46 |
November | 3210.92 | 03-NOV-10:00 | 2591.66 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.56 |
December | 2489.13 | 09-DEC-06:04 | 913.19 | 1186.66 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2489.13 | 326.14 | 260.35 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24303.86 | 2591.66 | 1874.40 | 5867.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8957.88 | 31-JAN-13:40 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 853.90 |
February | 27507.63 | 26-FEB-14:21 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1174.29 |
March | 17910.34 | 01-MAR-14:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.85 |
April | 16948.28 | 25-APR-13:40 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.43 |
May | 15685.85 | 19-MAY-13:50 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 112.92 | 0.00 |
June | 17968.33 | 25-JUN-15:02 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.40 |
July | 27884.71 | 16-JUL-14:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 245.37 | 0.00 |
August | 30915.84 | 06-AUG-14:11 | 809.75 | 646.40 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 439.13 | 0.00 |
September | 30633.58 | 03-SEP-13:31 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 575.92 | 0.00 |
October | 30022.91 | 15-OCT-14:22 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.93 |
November | 17302.60 | 03-NOV-13:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.02 |
December | 8609.56 | 06-DEC-14:40 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8609.56 | 506.09 | 404.00 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30915.84 | 2010.83 | 1454.32 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 575.92 | 1174.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3377.10 | 13-JAN-15:50 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.75 |
February | 6085.77 | 28-FEB-16:40 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.20 |
March | 7911.71 | 28-MAR-17:00 | 391.37 | 520.67 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.15 |
April | 17634.83 | 16-APR-17:11 | 0.00 | 468.62 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.82 |
May | 24383.89 | 28-MAY-17:52 | 0.00 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.93 |
June | 26299.55 | 18-JUN-16:41 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.60 |
July | 27979.85 | 09-JUL-17:31 | 0.00 | 468.62 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.87 |
August | 28607.14 | 06-AUG-16:11 | 652.28 | 520.69 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 335.11 | 0.00 |
September | 25445.69 | 04-SEP-16:22 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 164.68 | 0.00 |
October | 9471.34 | 18-OCT-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | 0.00 |
November | 4337.77 | 03-NOV-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.91 |
December | 3678.20 | 06-DEC-15:50 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3377.10 | 0.00 | 312.41 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28607.14 | 1239.33 | 937.20 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 335.11 | 825.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7642.15 | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2594.12 |
February | 5618.53 | 28-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.78 |
March | 5445.36 | 01-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5853.81 | 25-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.23 |
May | 9655.13 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.90 |
June | 8736.68 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.40 |
July | 11925.90 | 17-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.71 |
August | 10771.09 | 07-AUG-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.87 |
September | 10073.69 | 06-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.98 |
October | 5671.83 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.15 |
November | 6023.33 | 06-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.64 |
December | 4374.40 | 09-DEC-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4374.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11925.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2594.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10304.67 | 06-JAN-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5986.82 |
February | 9223.57 | 04-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2912.12 |
March | 11179.56 | 04-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.72 |
April | 6667.10 | 29-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3267.67 |
May | 6448.79 | 08-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4185.32 |
June | 6698.62 | 23-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.70 | 0.00 |
July | 8154.85 | 17-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.35 | 0.00 |
August | 8156.32 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.32 | 0.00 |
September | 7728.48 | 05-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.62 |
October | 6029.53 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2703.96 |
November | 8747.41 | 27-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5017.44 |
December | 8033.56 | 29-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6029.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11179.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.32 | 5986.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 82.36 | 14-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.37 |
February | 2545.11 | 26-FEB-14:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 915.50 |
March | 4410.76 | 23-MAR-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1172.99 |
April | 10711.34 | 25-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.88 |
May | 16442.43 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.42 | 0.00 |
June | 19298.83 | 23-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.93 | 0.00 |
July | 22981.96 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20527.83 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.57 | 0.00 |
September | 15022.49 | 01-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.91 | 0.00 |
October | 8533.89 | 18-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.16 |
November | 1924.04 | 03-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.36 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5142.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22981.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.42 | 5142.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2000.09 | 19-JAN-16:50 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4351.56 | 28-FEB-17:00 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6820.26 | 31-MAR-24:00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8237.58 | 25-APR-18:10 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3506.78 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5350.58 | 30-JUN-23:12 | 0.00 | 115.75 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7256.02 | 31-JUL-23:40 | 0.00 | 57.88 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8260.85 | 03-AUG-18:50 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3314.41 | 30-SEP-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4956.61 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6112.93 | 13-NOV-16:20 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7887.99 | 06-DEC-16:10 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2000.09 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8260.85 | 222.14 | 520.85 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1638.84 | 19-JAN-16:50 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3967.54 | 28-FEB-17:00 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5898.77 | 31-MAR-23:30 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7816.14 | 25-APR-18:10 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3305.33 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5241.42 | 30-JUN-23:55 | 0.00 | 57.88 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7067.46 | 31-JUL-23:53 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7894.12 | 03-AUG-18:50 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2869.57 | 30-SEP-23:40 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4140.53 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5570.73 | 03-NOV-16:00 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7159.06 | 06-DEC-16:20 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1638.84 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7894.12 | 222.14 | 520.85 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1412.46 | 13-JAN-16:30 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3906.11 | 28-FEB-17:00 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5836.58 | 28-MAR-17:50 | 23.38 | 173.61 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7866.44 | 25-APR-18:10 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3221.75 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5241.25 | 30-JUN-23:55 | 0.00 | 57.88 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7020.76 | 31-JUL-23:53 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7964.13 | 03-AUG-18:40 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2744.97 | 04-SEP-17:32 | 0.00 | 260.44 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4046.38 | 18-OCT-17:00 | 70.15 | 289.36 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5486.74 | 03-NOV-16:00 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7056.03 | 06-DEC-16:20 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1412.46 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7964.13 | 222.14 | 520.85 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91678.72 | 02-JAN-17:00 | 4808.68 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183625.84 | 28-FEB-17:00 | 4808.68 | 5919.59 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357551.65 | 31-MAR-24:00 | 0.00 | 328.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367104.14 | 26-APR-16:00 | 4808.68 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176036.66 | 31-MAY-24:00 | 0.00 | 328.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267990.03 | 30-JUN-24:00 | 0.00 | 657.76 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359143.61 | 31-JUL-23:12 | 0.00 | 1315.53 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369523.53 | 22-AUG-07:20 | 9617.36 | 11839.17 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175705.64 | 30-SEP-24:00 | 0.00 | 328.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267688.27 | 31-OCT-24:00 | 0.00 | 328.88 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276683.89 | 06-NOV-16:55 | 9617.36 | 11839.17 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367834.76 | 07-DEC-17:00 | 4808.68 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91678.72 | 0.00 | 328.88 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369523.53 | 9617.36 | 11839.17 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.172878E+13 | 1118183.89 | 13-JAN-16:00 | 0.120550E+13 | 2312600.18 | 09-JAN-07:19 |
February | 0.195189E+13 | 1318307.10 | 27-FEB-16:10 | 0.667591E+12 | 1587928.39 | 01-FEB-07:10 |
March | 0.262755E+13 | 1419859.85 | 16-MAR-15:30 | 0.431289E+12 | 1662964.84 | 06-MAR-07:10 |
April | 0.295818E+13 | 1743546.65 | 06-APR-15:09 | 0.156661E+12 | 663030.05 | 29-APR-06:10 |
May | 0.183464E+13 | 1441912.00 | 19-MAY-15:30 | 0.128849E+12 | 761928.97 | 08-MAY-04:10 |
June | 0.238369E+13 | 1656963.57 | 29-JUN-15:09 | 0.652655E+11 | 206282.66 | 16-JUN-06:00 |
July | 0.296599E+13 | 1961886.96 | 17-JUL-15:20 | 0.588336E+11 | 78804.62 | 05-JUL-11:30 |
August | 0.342631E+13 | 2076655.13 | 07-AUG-15:39 | 0.626446E+11 | 142038.55 | 18-AUG-05:10 |
September | 0.185895E+13 | 1532670.76 | 07-SEP-14:00 | 0.757554E+11 | 395687.78 | 19-SEP-05:10 |
October | 0.223932E+13 | 1523275.77 | 18-OCT-15:00 | 0.135665E+12 | 758595.46 | 10-OCT-06:19 |
November | 0.254807E+13 | 1537631.62 | 17-NOV-16:00 | 0.371771E+12 | 1419432.90 | 27-NOV-07:19 |
December | 0.299430E+13 | 1626727.63 | 06-DEC-16:30 | 0.809265E+12 | 1687417.24 | 29-DEC-07:00 |
Annual Sum or Average | 0.295177E+14 | 0.416909E+13 | ||||
Minimum of Months | 0.172878E+13 | 1118183.89 | 0.588336E+11 | 78804.62 | ||
Maximum of Months | 0.342631E+13 | 2076655.13 | 0.120550E+13 | 2312600.18 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.315800E+12 | 0.768683E+11 | 0.811612E+12 | 0.164873E+12 | 0.199097E+12 | 0.153119E+11 | 0.00 | 0.956387E+11 | 0.853760E+10 | 0.410426E+11 | 0.00 | 0.00 | 0.00 |
February | 0.282273E+12 | 0.623044E+11 | 0.102011E+13 | 0.148926E+12 | 0.179752E+12 | 0.163878E+11 | 0.00 | 0.159183E+12 | 0.215578E+11 | 0.614006E+11 | 0.00 | 0.00 | 0.00 |
March | 0.332984E+12 | 0.590027E+11 | 0.146267E+13 | 0.165150E+12 | 0.208440E+12 | 0.193541E+11 | 0.00 | 0.248424E+12 | 0.389759E+11 | 0.925469E+11 | 0.00 | 0.00 | 0.00 |
April | 0.296011E+12 | 0.470192E+11 | 0.170311E+13 | 0.159524E+12 | 0.207578E+12 | 0.254750E+11 | 0.00 | 0.324970E+12 | 0.831990E+11 | 0.111297E+12 | 0.00 | 0.00 | 0.00 |
May | 0.318209E+12 | 0.400984E+11 | 0.820521E+12 | 0.165009E+12 | 0.222905E+12 | 0.340451E+11 | 0.00 | 0.143615E+12 | 0.532230E+11 | 0.370105E+11 | 0.00 | 0.00 | 0.00 |
June | 0.315940E+12 | 0.349424E+11 | 0.110677E+13 | 0.159786E+12 | 0.262211E+12 | 0.542555E+11 | 0.00 | 0.293831E+12 | 0.106620E+12 | 0.493325E+11 | 0.00 | 0.00 | 0.00 |
July | 0.296427E+12 | 0.375927E+11 | 0.143888E+13 | 0.164745E+12 | 0.290979E+12 | 0.736343E+11 | 0.00 | 0.474610E+12 | 0.134358E+12 | 0.547636E+11 | 0.00 | 0.00 | 0.00 |
August | 0.330396E+12 | 0.445602E+11 | 0.177780E+13 | 0.165149E+12 | 0.290795E+12 | 0.709632E+11 | 0.00 | 0.528540E+12 | 0.132076E+12 | 0.860316E+11 | 0.00 | 0.00 | 0.00 |
September | 0.296819E+12 | 0.526918E+11 | 0.784732E+12 | 0.159522E+12 | 0.231612E+12 | 0.449880E+11 | 0.00 | 0.179587E+12 | 0.774669E+11 | 0.315279E+11 | 0.00 | 0.00 | 0.00 |
October | 0.310327E+12 | 0.648057E+11 | 0.112899E+13 | 0.164871E+12 | 0.213945E+12 | 0.277201E+11 | 0.00 | 0.202911E+12 | 0.613945E+11 | 0.643582E+11 | 0.00 | 0.00 | 0.00 |
November | 0.310139E+12 | 0.718289E+11 | 0.140306E+13 | 0.159634E+12 | 0.196971E+12 | 0.182486E+11 | 0.00 | 0.243575E+12 | 0.528489E+11 | 0.917602E+11 | 0.00 | 0.00 | 0.00 |
December | 0.305886E+12 | 0.794438E+11 | 0.175516E+13 | 0.164749E+12 | 0.199220E+12 | 0.165813E+11 | 0.00 | 0.310904E+12 | 0.426063E+11 | 0.119747E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371121E+13 | 0.671158E+12 | 0.152134E+14 | 0.194194E+13 | 0.270350E+13 | 0.416965E+12 | 0.00 | 0.320579E+13 | 0.812864E+12 | 0.840818E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.282273E+12 | 0.349424E+11 | 0.784732E+12 | 0.148926E+12 | 0.179752E+12 | 0.153119E+11 | 0.00 | 0.956387E+11 | 0.853760E+10 | 0.315279E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.332984E+12 | 0.794438E+11 | 0.177780E+13 | 0.165150E+12 | 0.290979E+12 | 0.736343E+11 | 0.00 | 0.528540E+12 | 0.134358E+12 | 0.119747E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.113587E+13 | 0.00 | 0.696306E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.603572E+12 | 0.00 | 0.640187E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.357620E+12 | 0.00 | 0.736690E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.907589E+11 | 0.00 | 0.659025E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.619418E+11 | 0.00 | 0.669075E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.242476E+10 | 0.00 | 0.628408E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 32213096.08 | 0.00 | 0.588014E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.865777E+09 | 0.00 | 0.617788E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.181576E+11 | 0.00 | 0.575977E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.742052E+11 | 0.00 | 0.614602E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.308900E+12 | 0.00 | 0.628711E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.743192E+12 | 0.00 | 0.660724E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.339754E+13 | 0.00 | 0.771551E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 32213096.08 | 0.00 | 0.575977E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.113587E+13 | 0.00 | 0.736690E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 352853.36 | 02-JAN-08:09 | 54335.80 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 118959.22 | 02-JAN-08:20 | 113119.89 | 09-JAN-06:10 | 36605.46 | 25-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 338792.62 | 02-FEB-08:09 | 54335.80 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 118947.47 | 02-FEB-08:20 | 150673.86 | 28-FEB-15:00 | 36954.08 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 349353.81 | 17-MAR-07:10 | 54335.80 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 118956.29 | 17-MAR-07:19 | 159301.19 | 28-MAR-15:39 | 36880.72 | 04-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 333407.84 | 14-APR-07:10 | 54335.80 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 118942.97 | 14-APR-07:19 | 211188.89 | 25-APR-15:39 | 50608.93 | 06-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 324684.10 | 03-MAY-07:10 | 54335.80 | 01-MAY-05:10 | 439129.89 | 01-MAY-07:10 | 118935.70 | 03-MAY-07:19 | 245353.78 | 19-MAY-15:30 | 53174.75 | 19-MAY-12:09 | 0.00 | 01-MAY-00:10 |
June | 316816.17 | 01-JUN-07:10 | 54335.80 | 01-JUN-20:10 | 557421.28 | 01-JUN-07:10 | 118929.14 | 01-JUN-07:19 | 276989.67 | 29-JUN-14:30 | 54017.37 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 316816.17 | 03-JUL-07:10 | 54335.80 | 01-JUL-20:30 | 675712.68 | 03-JUL-07:10 | 118929.14 | 03-JUL-07:19 | 324151.01 | 17-JUL-15:20 | 55364.25 | 31-JUL-15:20 | 0.00 | 01-JUL-00:10 |
August | 320030.31 | 17-AUG-07:10 | 54335.80 | 01-AUG-19:00 | 794004.08 | 01-AUG-07:10 | 118931.82 | 17-AUG-07:19 | 315966.19 | 11-AUG-15:30 | 55496.83 | 07-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 333129.14 | 11-SEP-07:10 | 54335.80 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 118942.74 | 11-SEP-07:19 | 258653.69 | 05-SEP-14:39 | 56384.85 | 05-SEP-12:30 | 0.00 | 01-SEP-00:10 |
October | 352853.36 | 30-OCT-07:10 | 54335.80 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 118959.22 | 30-OCT-07:19 | 191997.27 | 18-OCT-15:00 | 51049.12 | 18-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 352853.36 | 01-NOV-07:10 | 54335.80 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 118959.22 | 01-NOV-07:19 | 155545.77 | 03-NOV-15:20 | 36454.99 | 13-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 352853.36 | 01-DEC-16:40 | 54335.80 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 118959.22 | 13-DEC-08:20 | 120437.62 | 07-DEC-14:09 | 36783.45 | 27-DEC-16:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 316816.17 | 54335.80 | 439129.89 | 118929.14 | 113119.89 | 36454.99 | 0.00 | |||||||
Maximum of Months | 352853.36 | 54335.80 | 794004.08 | 118959.22 | 324151.01 | 56384.85 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 43209.98 | 13-JAN-16:40 | 7436.44 | 14-JAN-14:00 | 20103.49 | 26-JAN-18:00 | 0.00 | 0.00 | 0.00 |
February | 137839.13 | 27-FEB-15:30 | 49248.27 | 20-FEB-15:39 | 31480.82 | 04-FEB-07:40 | 0.00 | 0.00 | 0.00 |
March | 116445.58 | 31-MAR-23:00 | 49248.27 | 14-MAR-11:20 | 43072.45 | 31-MAR-23:00 | 0.00 | 0.00 | 0.00 |
April | 242316.19 | 07-APR-14:39 | 50128.65 | 06-APR-15:39 | 50208.67 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 246537.85 | 19-MAY-15:30 | 53190.21 | 19-MAY-11:00 | 21872.30 | 31-MAY-23:00 | 0.00 | 0.00 | 0.00 |
June | 322093.69 | 29-JUN-14:00 | 81829.93 | 06-JUN-14:39 | 27061.62 | 08-JUN-20:00 | 0.00 | 0.00 | 0.00 |
July | 425587.55 | 17-JUL-15:30 | 81829.93 | 13-JUL-13:09 | 36644.71 | 12-JUL-06:19 | 0.00 | 0.00 | 0.00 |
August | 426109.78 | 07-AUG-15:39 | 81829.93 | 05-AUG-12:00 | 49233.96 | 01-AUG-20:00 | 0.00 | 0.00 | 0.00 |
September | 372469.93 | 07-SEP-14:00 | 81829.93 | 02-SEP-10:50 | 22843.25 | 30-SEP-23:00 | 0.00 | 0.00 | 0.00 |
October | 264571.91 | 18-OCT-14:30 | 51033.48 | 18-OCT-15:09 | 33042.50 | 31-OCT-23:00 | 0.00 | 0.00 | 0.00 |
November | 148130.83 | 17-NOV-16:00 | 49316.91 | 17-NOV-16:00 | 41304.61 | 20-NOV-21:00 | 0.00 | 0.00 | 0.00 |
December | 125107.23 | 10-DEC-01:00 | 49248.27 | 05-DEC-11:00 | 52016.10 | 28-DEC-18:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 43209.98 | 7436.44 | 20103.49 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 426109.78 | 81829.93 | 52016.10 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1118183.89 | 13-JAN-16:00 | 352853.36 | 439129.89 | 54335.80 | 84914.28 | 90626.64 | 33715.72 | 0.00 | 43026.01 | 6403.97 |
February | 1318307.10 | 27-FEB-16:10 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 128154.56 | 33758.52 | 0.00 | 126684.05 | 49248.27 |
March | 1419859.85 | 16-MAR-15:30 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 154803.78 | 33663.86 | 0.00 | 97491.98 | 19674.87 |
April | 1743546.65 | 06-APR-15:09 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 182803.22 | 50574.82 | 0.00 | 238176.49 | 49855.51 |
May | 1441912.00 | 19-MAY-15:30 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 245353.78 | 52513.26 | 0.00 | 246537.85 | 52887.37 |
June | 1656963.57 | 29-JUN-15:09 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 273781.58 | 51098.08 | 0.00 | 320955.25 | 51272.64 |
July | 1961886.96 | 17-JUL-15:20 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 324151.01 | 54475.53 | 0.00 | 424015.89 | 81829.93 |
August | 2076655.13 | 07-AUG-15:39 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 301770.59 | 55015.81 | 0.00 | 426109.78 | 81829.93 |
September | 1532670.76 | 07-SEP-14:00 | 316816.17 | 439129.89 | 0.00 | 39494.57 | 228836.31 | 54093.96 | 0.00 | 372469.93 | 81829.93 |
October | 1523275.77 | 18-OCT-15:00 | 320848.56 | 557421.28 | 0.00 | 84888.31 | 191997.27 | 50830.49 | 0.00 | 255259.77 | 49999.01 |
November | 1537631.62 | 17-NOV-16:00 | 352853.36 | 675712.68 | 54335.80 | 84915.83 | 112792.50 | 33717.52 | 0.00 | 148130.83 | 49316.91 |
December | 1626727.63 | 06-DEC-16:30 | 352853.36 | 794004.08 | 54335.80 | 84905.03 | 105171.46 | 33668.37 | 0.00 | 121890.35 | 36495.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1118183.89 | 316816.17 | 439129.89 | 0.00 | 39494.57 | 90626.64 | 33663.86 | 0.00 | 43026.01 | 6403.97 | |
Maximum of Months | 2076655.13 | 352853.36 | 794004.08 | 54335.80 | 84915.83 | 324151.01 | 55015.81 | 0.00 | 426109.78 | 81829.93 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2290324.49 | 09-JAN-07:10 | 0.00 | 85363.68 | 30-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 1558403.84 | 01-FEB-07:10 | 0.00 | 85520.85 | 22-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 1632342.91 | 06-MAR-07:10 | 0.00 | 85470.31 | 02-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 635188.25 | 29-APR-06:10 | 0.00 | 84643.89 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 756233.10 | 08-MAY-04:10 | 0.00 | 83179.15 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 176680.99 | 16-JUN-06:00 | 0.00 | 81111.10 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 3489.77 | 08-JUL-05:10 | 0.00 | 78804.62 | 05-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 136342.68 | 18-AUG-05:10 | 0.00 | 77551.31 | 01-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 389991.91 | 19-SEP-05:10 | 0.00 | 78382.67 | 28-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 729958.18 | 10-OCT-06:30 | 0.00 | 80550.48 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 1389429.21 | 27-NOV-07:19 | 0.00 | 82614.83 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 1657082.82 | 29-DEC-07:00 | 0.00 | 84265.96 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 3489.77 | 0.00 | 77551.31 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 2290324.49 | 0.00 | 85520.85 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.19 | 1.50 | 27.22 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.95 | 0.00 | 25.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.95 | 0.00 | 25.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.85 | 0.00 | 25.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.06 | 0.00 | 26.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.88 | 0.00 | 25.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.15 | 0.00 | 26.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 25.86 | 0.00 | 25.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.41 | 0.33 | 26.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.44 | 0.83 | 26.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.43 | 0.17 | 26.45 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.99 | 0.00 | 25.99 |
Annual Sum or Average | 0.00 | 0.00 | 59.67 | 26.31 | 2.83 | 26.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.85 | 0.00 | 25.85 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.19 | 1.50 | 27.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.93 | 0.00 | 25.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.71 | 0.00 | 25.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.60 | 0.00 | 25.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.63 | 0.00 | 25.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.62 | 0.00 | 25.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.66 | 0.00 | 25.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 25.66 | 0.00 | 25.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.93 | 0.00 | 25.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Annual Sum or Average | 0.17 | 19.35 | 0.00 | 19.35 | 0.17 | 22.46 | 0.00 | 22.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.35 | 0.00 | 19.35 | 0.17 | 25.56 | 0.00 | 25.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.17 | 18.81 | 2.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
February | 1.50 | 18.60 | 0.17 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
March | 1.33 | 18.59 | 0.33 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
November | 1.67 | 18.92 | 0.33 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
December | 2.67 | 18.65 | 0.33 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
Annual Sum or Average | 15.83 | 18.76 | 3.17 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.17 | 19.39 | 2.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 18.57 | 0.83 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
February | 0.50 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
March | 0.33 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.72 | 0.33 | 26.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Annual Sum or Average | 6.00 | 18.67 | 0.83 | 18.86 | 0.50 | 19.40 | 0.33 | 19.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.00 | 19.31 | 0.83 | 19.31 | 0.50 | 26.72 | 0.33 | 26.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 18.07 | 0.00 | 18.07 | 0.00 | 18.07 | 0.00 | 18.07 |
February | 0.83 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
March | 0.50 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.57 | 0.50 | 27.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.90 | 4.00 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.17 | 5.50 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.30 | 1.67 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.80 | 2.50 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
December | 0.50 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Annual Sum or Average | 5.83 | 18.45 | 0.00 | 18.45 | 14.33 | 25.25 | 14.33 | 26.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 19.44 | 0.00 | 19.44 | 5.50 | 28.30 | 5.50 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 18.16 | 0.17 | 18.24 | 0.17 | 18.56 | 0.17 | 18.85 |
February | 0.67 | 19.15 | 0.00 | 19.15 | 1.50 | 25.35 | 1.50 | 26.48 |
March | 0.50 | 18.84 | 0.00 | 18.84 | 0.33 | 22.27 | 0.33 | 23.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.60 | 1.00 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.71 | 4.50 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.93 | 3.33 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.06 | 5.33 | 28.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.15 | 2.50 | 28.15 |
November | 0.17 | 19.06 | 0.00 | 19.06 | 1.17 | 26.46 | 1.17 | 26.95 |
December | 0.50 | 19.06 | 0.00 | 19.06 | 0.17 | 21.11 | 0.17 | 22.34 |
Annual Sum or Average | 6.33 | 18.42 | 0.17 | 18.47 | 21.00 | 25.67 | 20.17 | 26.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 19.15 | 0.17 | 19.15 | 5.83 | 28.15 | 5.33 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.57 | 0.33 | 27.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.42 | 1.50 | 28.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.29 | 1.17 | 28.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.97 | 3.00 | 27.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 28.02 | 5.83 | 28.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.54 | 4.83 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.31 | 2.00 | 28.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.28 | 0.50 | 28.30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.67 | 18.74 | 0.00 | 18.74 | 49.83 | 27.44 | 19.50 | 27.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 18.74 | 0.00 | 18.74 | 16.83 | 28.42 | 5.83 | 28.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.33 | 17.13 | 23.50 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
February | 19.50 | 17.16 | 5.50 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
March | 8.67 | 17.57 | 2.17 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
April | 0.33 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
May | 0.67 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
November | 8.33 | 17.35 | 1.83 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 |
December | 21.67 | 17.04 | 5.67 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
Annual Sum or Average | 116.83 | 17.19 | 38.67 | 17.41 | 0.00 | 17.41 | 0.00 | 17.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.33 | 19.25 | 23.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.83 | 15.59 | 4.17 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
February | 12.17 | 16.57 | 1.17 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
March | 6.17 | 16.56 | 0.33 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
April | 0.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
May | 0.67 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.97 | 3.67 | 27.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.24 | 6.50 | 28.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.32 | 2.50 | 28.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.82 | 2.67 | 27.82 |
October | 0.33 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
November | 5.33 | 16.67 | 0.17 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
December | 14.33 | 16.21 | 3.17 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
Annual Sum or Average | 66.17 | 16.15 | 9.00 | 16.01 | 15.33 | 18.06 | 15.33 | 19.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.45 | 0.00 | 15.45 |
Maximum of Months | 26.83 | 19.25 | 4.17 | 19.25 | 6.50 | 28.32 | 6.50 | 28.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.50 | 16.06 | 2.83 | 15.97 | 0.00 | 15.97 | 0.00 | 15.97 |
February | 7.33 | 17.27 | 0.83 | 17.13 | 1.33 | 18.70 | 1.33 | 19.89 |
March | 3.83 | 17.22 | 0.17 | 17.33 | 0.33 | 18.09 | 0.33 | 18.75 |
April | 0.33 | 19.29 | 0.00 | 19.29 | 0.67 | 24.78 | 0.67 | 25.88 |
May | 0.50 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.71 | 4.00 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.98 | 2.83 | 27.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.17 | 5.83 | 28.20 |
October | 0.17 | 19.21 | 0.00 | 19.21 | 2.83 | 27.68 | 2.83 | 27.92 |
November | 2.67 | 17.37 | 0.17 | 17.53 | 1.17 | 20.45 | 1.17 | 22.05 |
December | 11.00 | 16.64 | 2.00 | 16.38 | 0.00 | 16.38 | 0.00 | 16.38 |
Annual Sum or Average | 47.33 | 16.62 | 6.00 | 16.49 | 20.17 | 19.65 | 19.00 | 21.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.50 | 19.29 | 2.83 | 19.29 | 6.50 | 28.17 | 5.83 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.00 | 15.73 | 3.83 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
February | 8.50 | 16.96 | 1.00 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
March | 3.83 | 17.21 | 0.17 | 17.34 | 0.00 | 17.34 | 0.00 | 17.34 |
April | 0.17 | 19.38 | 0.00 | 19.38 | 0.83 | 26.54 | 0.33 | 26.89 |
May | 0.33 | 19.02 | 0.00 | 19.02 | 2.17 | 26.86 | 0.83 | 27.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.23 | 1.17 | 28.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.50 | 3.17 | 28.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.49 | 1.00 | 28.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.52 | 1.50 | 28.55 |
October | 0.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
November | 3.67 | 17.31 | 0.17 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
December | 11.67 | 16.46 | 2.67 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
Annual Sum or Average | 52.33 | 16.36 | 7.83 | 16.17 | 17.67 | 18.94 | 8.00 | 19.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 0.00 | 15.58 |
Maximum of Months | 24.00 | 19.38 | 3.83 | 19.38 | 7.00 | 28.52 | 3.17 | 28.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 113.33 | 16.29 | 46.33 | 16.68 | 0.00 | 16.68 | 0.00 | 16.68 |
February | 46.83 | 16.77 | 14.33 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
March | 26.83 | 16.67 | 7.50 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
April | 3.83 | 18.55 | 0.17 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 |
May | 6.50 | 17.52 | 0.83 | 17.71 | 0.00 | 17.71 | 0.00 | 17.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.46 | 0.00 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.36 | 0.50 | 27.36 |
September | 0.83 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
October | 3.83 | 18.11 | 0.17 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
November | 31.50 | 16.14 | 10.00 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
December | 73.83 | 16.00 | 27.00 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
Annual Sum or Average | 307.33 | 16.39 | 106.33 | 16.62 | 1.00 | 16.65 | 0.50 | 16.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 113.33 | 19.16 | 46.33 | 19.16 | 0.83 | 27.46 | 0.50 | 27.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.33 | 15.15 | 13.67 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
February | 26.33 | 15.59 | 4.00 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
March | 18.67 | 15.99 | 3.17 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 |
April | 3.33 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
May | 4.50 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.78 | 2.67 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.10 | 7.33 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.43 | 2.67 | 28.47 |
September | 0.67 | 19.15 | 0.00 | 19.15 | 4.00 | 26.52 | 4.00 | 27.09 |
October | 2.83 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
November | 21.33 | 15.68 | 4.00 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
December | 52.67 | 15.06 | 13.17 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
Annual Sum or Average | 191.67 | 15.48 | 38.00 | 15.36 | 17.33 | 16.25 | 16.67 | 17.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 | 0.00 | 14.92 |
Maximum of Months | 61.33 | 19.15 | 13.67 | 19.15 | 7.67 | 28.43 | 7.33 | 28.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.17 | 15.69 | 12.50 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
February | 20.17 | 16.17 | 1.50 | 16.08 | 0.83 | 16.52 | 0.83 | 16.92 |
March | 16.00 | 16.39 | 1.83 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
April | 2.67 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
May | 4.33 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.84 | 4.00 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.32 | 2.17 | 28.35 |
September | 0.67 | 19.22 | 0.00 | 19.22 | 5.17 | 27.33 | 4.33 | 27.82 |
October | 1.50 | 18.12 | 0.00 | 18.12 | 1.17 | 22.56 | 1.17 | 24.29 |
November | 15.00 | 16.33 | 2.17 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
December | 40.50 | 15.44 | 8.17 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
Annual Sum or Average | 155.00 | 15.95 | 26.17 | 15.92 | 14.33 | 16.82 | 12.50 | 17.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.17 | 19.22 | 12.50 | 19.22 | 5.17 | 28.32 | 4.33 | 28.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.17 | 15.00 | 11.00 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
February | 20.50 | 15.95 | 3.00 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
March | 14.50 | 16.20 | 1.83 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
April | 2.00 | 18.82 | 0.00 | 18.82 | 0.67 | 21.02 | 0.33 | 21.74 |
May | 2.67 | 17.47 | 0.00 | 17.47 | 2.00 | 21.99 | 0.67 | 22.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.29 | 1.17 | 28.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.62 | 2.83 | 28.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.56 | 1.17 | 28.62 |
September | 0.50 | 19.24 | 0.00 | 19.24 | 2.83 | 27.09 | 1.83 | 27.63 |
October | 1.50 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 |
November | 15.50 | 15.99 | 3.33 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
December | 39.83 | 15.29 | 10.00 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
Annual Sum or Average | 147.17 | 15.58 | 29.17 | 15.42 | 18.33 | 16.65 | 8.00 | 17.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | 0.00 | 14.94 |
Maximum of Months | 50.17 | 19.24 | 11.00 | 19.24 | 7.17 | 28.62 | 2.83 | 28.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.57 | 0.00 | 27.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.91 | 11.83 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.50 | 27.91 | 11.83 | 27.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.91 | 11.83 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.82 | 3.83 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.50 | 27.82 | 3.83 | 27.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.82 | 3.83 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.92 | 3.00 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.83 | 27.92 | 3.00 | 27.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.92 | 3.00 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.88 | 22.50 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 497.00 | 29.07 | 380.67 | 29.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 521.33 | 29.01 | 403.17 | 29.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 497.00 | 29.07 | 380.67 | 29.11 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 394.33 | 23.29 | 33.67 | 23.53 | 0.50 | 23.52 |
February | 311.83 | 23.73 | 35.17 | 23.99 | 0.00 | 23.99 |
March | 279.67 | 23.96 | 35.33 | 24.20 | 0.00 | 24.20 |
April | 100.33 | 24.01 | 76.50 | 24.93 | 0.00 | 24.93 |
May | 97.00 | 24.00 | 102.17 | 25.01 | 0.00 | 25.01 |
June | 11.00 | 24.33 | 220.67 | 24.93 | 8.50 | 24.92 |
July | 11.17 | 25.14 | 334.00 | 24.91 | 11.17 | 24.91 |
August | 0.00 | 0.00 | 215.00 | 25.13 | 0.00 | 25.13 |
September | 25.17 | 24.00 | 209.17 | 25.09 | 16.50 | 25.02 |
October | 15.67 | 24.00 | 109.17 | 26.17 | 0.00 | 26.17 |
November | 114.17 | 24.00 | 89.33 | 25.09 | 0.00 | 25.09 |
December | 257.50 | 23.80 | 50.83 | 24.21 | 0.00 | 24.21 |
Annual Sum or Average | 1617.83 | 23.75 | 1511.00 | 24.58 | 36.67 | 24.58 |
Minimum of Months | 0.00 | 0.00 | 33.67 | 23.53 | 0.00 | 23.52 |
Maximum of Months | 394.33 | 25.14 | 334.00 | 26.17 | 16.50 | 26.17 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 435.17 | 23.51 | 10.33 | 23.57 | 0.00 | 23.57 |
February | 318.83 | 23.79 | 6.17 | 23.83 | 0.00 | 23.83 |
March | 242.17 | 23.95 | 22.00 | 24.11 | 0.00 | 24.11 |
April | 74.83 | 23.98 | 57.50 | 24.85 | 0.00 | 24.85 |
May | 98.83 | 23.97 | 87.50 | 24.68 | 0.00 | 24.68 |
June | 7.67 | 24.35 | 224.17 | 24.50 | 5.50 | 24.50 |
July | 3.17 | 24.99 | 359.00 | 24.41 | 3.17 | 24.42 |
August | 0.00 | 0.00 | 262.17 | 24.47 | 0.00 | 24.47 |
September | 37.50 | 24.05 | 199.17 | 24.58 | 15.17 | 24.56 |
October | 50.83 | 23.98 | 82.50 | 25.21 | 0.00 | 25.21 |
November | 158.83 | 23.98 | 54.50 | 24.49 | 0.00 | 24.49 |
December | 263.67 | 23.92 | 22.17 | 24.07 | 0.00 | 24.07 |
Annual Sum or Average | 1691.50 | 23.81 | 1387.17 | 24.27 | 23.83 | 24.27 |
Minimum of Months | 0.00 | 0.00 | 6.17 | 23.57 | 0.00 | 23.57 |
Maximum of Months | 435.17 | 24.99 | 359.00 | 25.21 | 15.17 | 25.21 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.31 | 99.00 | 22.05 | 99.00 | 21.87 |
February | 450.50 | 22.84 | 29.17 | 22.69 | 29.17 | 22.56 |
March | 502.00 | 23.39 | 16.83 | 23.31 | 16.83 | 23.24 |
April | 337.83 | 23.67 | 0.00 | 23.67 | 0.00 | 23.67 |
May | 233.33 | 23.72 | 56.00 | 24.04 | 0.00 | 24.04 |
June | 70.67 | 23.80 | 155.33 | 24.21 | 6.83 | 24.21 |
July | 28.83 | 24.19 | 273.00 | 24.38 | 7.33 | 24.40 |
August | 19.50 | 23.78 | 160.50 | 24.55 | 0.00 | 24.55 |
September | 129.33 | 23.79 | 140.33 | 24.20 | 15.83 | 24.19 |
October | 294.50 | 23.71 | 5.00 | 23.74 | 0.00 | 23.74 |
November | 437.50 | 23.43 | 4.33 | 23.41 | 4.33 | 23.39 |
December | 497.00 | 22.67 | 57.17 | 22.44 | 57.17 | 22.26 |
Annual Sum or Average | 3503.00 | 23.17 | 996.67 | 23.30 | 236.50 | 23.19 |
Minimum of Months | 19.50 | 22.31 | 0.00 | 22.05 | 0.00 | 21.87 |
Maximum of Months | 502.00 | 24.19 | 273.00 | 24.55 | 99.00 | 24.55 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.72 | 316.50 | 20.47 | 316.50 | 20.35 |
February | 454.00 | 21.40 | 190.67 | 21.06 | 190.67 | 20.87 |
March | 514.00 | 22.13 | 115.67 | 21.78 | 115.67 | 21.54 |
April | 443.17 | 22.77 | 43.83 | 22.58 | 43.83 | 22.42 |
May | 321.67 | 23.07 | 62.00 | 23.12 | 22.33 | 22.97 |
June | 119.83 | 23.48 | 156.00 | 23.94 | 5.50 | 23.95 |
July | 50.33 | 23.78 | 282.83 | 24.26 | 9.33 | 24.27 |
August | 68.67 | 23.59 | 161.67 | 24.21 | 0.00 | 24.21 |
September | 238.83 | 23.21 | 118.33 | 23.62 | 17.50 | 23.64 |
October | 453.00 | 22.73 | 25.50 | 22.60 | 25.50 | 22.48 |
November | 486.83 | 21.89 | 128.17 | 21.55 | 128.17 | 21.33 |
December | 497.00 | 21.04 | 259.83 | 20.68 | 259.83 | 20.50 |
Annual Sum or Average | 4149.33 | 22.07 | 1861.00 | 22.02 | 1134.83 | 21.74 |
Minimum of Months | 50.33 | 20.72 | 25.50 | 20.47 | 0.00 | 20.35 |
Maximum of Months | 514.00 | 23.78 | 316.50 | 24.26 | 316.50 | 24.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.94 | 291.50 | 20.74 | 291.50 | 20.64 |
February | 454.00 | 21.65 | 139.33 | 21.40 | 139.33 | 21.24 |
March | 514.00 | 22.50 | 47.17 | 22.33 | 47.17 | 22.19 |
April | 416.00 | 23.24 | 0.00 | 23.24 | 0.00 | 23.24 |
May | 303.17 | 23.24 | 56.33 | 23.51 | 0.00 | 23.51 |
June | 72.33 | 23.63 | 214.00 | 24.13 | 4.17 | 24.14 |
July | 9.33 | 24.12 | 349.67 | 24.39 | 2.17 | 24.39 |
August | 38.17 | 23.62 | 212.00 | 24.26 | 0.33 | 24.26 |
September | 239.33 | 23.25 | 123.83 | 23.71 | 10.00 | 23.72 |
October | 431.83 | 23.15 | 4.50 | 23.17 | 0.00 | 23.17 |
November | 480.33 | 22.45 | 33.67 | 22.34 | 33.67 | 22.24 |
December | 497.00 | 21.60 | 156.33 | 21.35 | 156.33 | 21.20 |
Annual Sum or Average | 3957.50 | 22.37 | 1628.33 | 22.50 | 684.67 | 22.29 |
Minimum of Months | 9.33 | 20.94 | 0.00 | 20.74 | 0.00 | 20.64 |
Maximum of Months | 514.00 | 24.12 | 349.67 | 24.39 | 291.50 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.17 | 20.88 | 295.50 | 20.71 | 295.50 | 20.63 |
February | 434.50 | 21.46 | 149.83 | 21.27 | 147.50 | 21.14 |
March | 473.00 | 21.90 | 59.67 | 21.80 | 54.00 | 21.69 |
April | 354.17 | 22.39 | 44.17 | 22.63 | 1.17 | 22.63 |
May | 263.67 | 22.56 | 94.00 | 23.09 | 0.00 | 23.09 |
June | 130.17 | 23.43 | 268.17 | 24.05 | 18.67 | 24.15 |
July | 64.33 | 24.38 | 369.17 | 24.38 | 23.17 | 24.50 |
August | 125.83 | 23.17 | 278.67 | 23.89 | 6.00 | 23.94 |
September | 240.50 | 22.79 | 174.17 | 23.52 | 17.00 | 23.58 |
October | 402.33 | 22.51 | 13.67 | 22.60 | 0.00 | 22.60 |
November | 475.67 | 21.87 | 55.67 | 21.76 | 55.67 | 21.66 |
December | 497.00 | 21.16 | 196.00 | 20.99 | 196.00 | 20.89 |
Annual Sum or Average | 3961.33 | 21.96 | 1998.67 | 22.29 | 814.67 | 22.14 |
Minimum of Months | 64.33 | 20.88 | 13.67 | 20.71 | 0.00 | 20.63 |
Maximum of Months | 500.17 | 24.38 | 369.17 | 24.38 | 295.50 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 461.00 | 21.20 | 260.17 | 21.00 | 250.67 | 20.85 |
February | 358.00 | 21.79 | 151.00 | 21.79 | 117.67 | 21.61 |
March | 395.83 | 22.07 | 95.50 | 22.13 | 50.83 | 21.98 |
April | 318.67 | 22.53 | 56.83 | 22.82 | 4.33 | 22.81 |
May | 274.33 | 22.50 | 103.50 | 23.00 | 9.50 | 22.94 |
June | 139.67 | 23.10 | 217.50 | 23.86 | 5.00 | 23.87 |
July | 59.50 | 24.08 | 355.33 | 24.35 | 15.67 | 24.44 |
August | 86.33 | 23.56 | 308.33 | 24.16 | 9.33 | 24.22 |
September | 191.17 | 23.13 | 226.83 | 23.94 | 24.00 | 24.06 |
October | 282.83 | 22.77 | 108.67 | 23.25 | 7.33 | 23.30 |
November | 358.67 | 22.16 | 101.00 | 22.35 | 45.50 | 22.20 |
December | 426.67 | 21.51 | 167.67 | 21.34 | 151.33 | 21.15 |
Annual Sum or Average | 3352.67 | 22.17 | 2152.33 | 22.63 | 691.17 | 22.46 |
Minimum of Months | 59.50 | 21.20 | 56.83 | 21.00 | 4.33 | 20.85 |
Maximum of Months | 461.00 | 24.08 | 355.33 | 24.35 | 250.67 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.50 | 21.17 | 216.00 | 20.98 | 216.00 | 20.89 |
February | 409.50 | 21.96 | 86.00 | 21.89 | 72.67 | 21.75 |
March | 391.00 | 22.69 | 48.67 | 22.78 | 14.83 | 22.72 |
April | 146.67 | 23.23 | 140.00 | 24.12 | 5.33 | 24.18 |
May | 224.50 | 22.80 | 166.17 | 23.66 | 4.67 | 23.70 |
June | 60.00 | 23.75 | 357.17 | 24.34 | 14.33 | 24.40 |
July | 32.33 | 26.83 | 464.50 | 24.67 | 32.17 | 24.80 |
August | 22.00 | 26.09 | 471.17 | 24.51 | 17.33 | 24.59 |
September | 200.67 | 22.94 | 200.50 | 23.79 | 17.67 | 23.87 |
October | 276.00 | 22.89 | 85.00 | 23.37 | 2.00 | 23.39 |
November | 360.33 | 22.63 | 39.67 | 22.89 | 2.00 | 22.88 |
December | 439.50 | 22.32 | 51.17 | 22.22 | 44.33 | 22.11 |
Annual Sum or Average | 3063.00 | 22.44 | 2326.00 | 23.12 | 443.33 | 23.03 |
Minimum of Months | 22.00 | 21.17 | 39.67 | 20.98 | 2.00 | 20.89 |
Maximum of Months | 500.50 | 26.83 | 471.17 | 24.67 | 216.00 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.98 | 491.67 | 19.97 | 491.67 | 19.96 |
February | 454.00 | 20.41 | 376.67 | 20.33 | 376.67 | 20.30 |
March | 514.00 | 20.90 | 267.17 | 20.68 | 267.17 | 20.58 |
April | 482.67 | 21.89 | 86.17 | 21.67 | 86.17 | 21.50 |
May | 402.00 | 22.46 | 60.50 | 22.41 | 35.67 | 22.24 |
June | 166.33 | 23.24 | 143.83 | 23.69 | 4.67 | 23.70 |
July | 53.50 | 23.54 | 260.83 | 24.22 | 2.67 | 24.22 |
August | 138.83 | 23.27 | 129.83 | 23.83 | 0.00 | 23.83 |
September | 327.17 | 22.54 | 95.00 | 22.92 | 21.33 | 22.90 |
October | 500.67 | 21.86 | 68.17 | 21.68 | 68.17 | 21.54 |
November | 489.00 | 20.77 | 274.67 | 20.54 | 274.67 | 20.44 |
December | 497.00 | 20.07 | 443.17 | 20.01 | 443.17 | 19.99 |
Annual Sum or Average | 4527.17 | 21.30 | 2697.67 | 21.24 | 2072.00 | 20.99 |
Minimum of Months | 53.50 | 19.98 | 60.50 | 19.97 | 0.00 | 19.96 |
Maximum of Months | 514.00 | 23.54 | 491.67 | 24.22 | 491.67 | 24.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.99 | 398.83 | 19.96 | 398.83 | 19.95 |
February | 384.17 | 20.56 | 274.17 | 20.41 | 274.17 | 20.35 |
March | 424.83 | 20.95 | 193.00 | 20.74 | 193.00 | 20.62 |
April | 351.33 | 21.66 | 73.00 | 21.62 | 56.33 | 21.48 |
May | 302.17 | 22.02 | 80.00 | 22.23 | 28.83 | 22.06 |
June | 155.67 | 23.06 | 196.50 | 23.88 | 19.17 | 24.00 |
July | 88.00 | 24.10 | 289.83 | 24.48 | 28.17 | 24.64 |
August | 137.00 | 22.94 | 211.50 | 23.88 | 7.67 | 23.96 |
September | 264.67 | 22.28 | 116.83 | 23.00 | 19.67 | 23.06 |
October | 408.17 | 21.67 | 47.50 | 21.57 | 44.33 | 21.47 |
November | 416.83 | 20.76 | 222.50 | 20.58 | 222.50 | 20.50 |
December | 422.00 | 20.00 | 365.33 | 19.92 | 365.33 | 19.90 |
Annual Sum or Average | 3781.83 | 21.23 | 2469.00 | 21.41 | 1658.00 | 21.19 |
Minimum of Months | 88.00 | 19.99 | 47.50 | 19.92 | 7.67 | 19.90 |
Maximum of Months | 427.00 | 24.10 | 398.83 | 24.48 | 398.83 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 475.67 | 20.73 | 337.17 | 20.54 | 331.00 | 20.43 |
February | 378.33 | 21.26 | 229.17 | 21.18 | 198.33 | 21.00 |
March | 414.83 | 21.35 | 191.00 | 21.32 | 149.50 | 21.13 |
April | 366.17 | 21.88 | 100.00 | 22.02 | 55.83 | 21.87 |
May | 323.50 | 22.11 | 104.33 | 22.35 | 36.67 | 22.18 |
June | 197.83 | 22.74 | 187.67 | 23.53 | 4.67 | 23.54 |
July | 97.00 | 23.44 | 309.33 | 24.20 | 13.50 | 24.28 |
August | 135.67 | 23.08 | 278.50 | 24.00 | 8.17 | 24.06 |
September | 226.67 | 22.73 | 214.00 | 23.66 | 29.17 | 23.79 |
October | 334.67 | 22.25 | 121.67 | 22.67 | 30.67 | 22.65 |
November | 396.83 | 21.55 | 174.67 | 21.52 | 132.83 | 21.31 |
December | 458.33 | 20.75 | 285.00 | 20.48 | 284.00 | 20.35 |
Annual Sum or Average | 3805.50 | 21.68 | 2532.50 | 22.00 | 1274.33 | 21.76 |
Minimum of Months | 97.00 | 20.73 | 100.00 | 20.48 | 4.67 | 20.35 |
Maximum of Months | 475.67 | 23.44 | 337.17 | 24.20 | 331.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.21 | 452.50 | 20.16 | 452.50 | 20.14 |
February | 445.33 | 20.70 | 290.17 | 20.53 | 290.00 | 20.46 |
March | 492.83 | 21.01 | 194.17 | 20.83 | 192.33 | 20.72 |
April | 420.83 | 21.70 | 76.67 | 21.76 | 49.83 | 21.67 |
May | 342.83 | 22.04 | 112.00 | 22.42 | 30.83 | 22.32 |
June | 202.83 | 22.68 | 202.17 | 23.53 | 10.17 | 23.59 |
July | 112.83 | 23.37 | 316.00 | 24.17 | 16.67 | 24.26 |
August | 169.50 | 22.78 | 241.17 | 23.77 | 4.83 | 23.80 |
September | 318.33 | 22.17 | 133.33 | 22.86 | 19.83 | 22.93 |
October | 456.67 | 21.66 | 52.67 | 21.64 | 39.33 | 21.56 |
November | 483.67 | 20.97 | 204.00 | 20.76 | 204.00 | 20.64 |
December | 497.00 | 20.27 | 381.00 | 20.15 | 381.00 | 20.10 |
Annual Sum or Average | 4444.67 | 21.30 | 2655.83 | 21.50 | 1691.33 | 21.28 |
Minimum of Months | 112.83 | 20.21 | 52.67 | 20.15 | 4.83 | 20.10 |
Maximum of Months | 502.00 | 23.37 | 452.50 | 24.17 | 452.50 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.65 | 496.50 | 19.65 | 496.50 | 19.64 |
February | 454.00 | 19.99 | 436.17 | 19.97 | 436.17 | 19.96 |
March | 514.00 | 20.36 | 385.33 | 20.23 | 385.33 | 20.18 |
April | 484.17 | 21.05 | 209.50 | 20.75 | 209.50 | 20.58 |
May | 437.00 | 21.85 | 126.00 | 21.66 | 103.00 | 21.43 |
June | 231.00 | 22.69 | 131.00 | 23.21 | 6.00 | 23.22 |
July | 112.50 | 23.09 | 238.00 | 23.91 | 3.50 | 23.92 |
August | 210.83 | 22.83 | 128.50 | 23.39 | 1.67 | 23.38 |
September | 373.17 | 21.93 | 117.67 | 22.16 | 58.33 | 22.04 |
October | 502.00 | 20.92 | 217.67 | 20.66 | 217.67 | 20.51 |
November | 489.00 | 20.13 | 388.17 | 20.01 | 388.17 | 19.96 |
December | 497.00 | 19.81 | 480.83 | 19.79 | 480.83 | 19.79 |
Annual Sum or Average | 4806.67 | 20.84 | 3355.33 | 20.77 | 2786.67 | 20.56 |
Minimum of Months | 112.50 | 19.65 | 117.67 | 19.65 | 1.67 | 19.64 |
Maximum of Months | 514.00 | 23.09 | 496.50 | 23.91 | 496.50 | 23.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 488.33 | 19.80 | 488.33 | 19.80 |
February | 454.00 | 20.22 | 376.00 | 20.11 | 376.00 | 20.07 |
March | 509.33 | 20.64 | 309.33 | 20.42 | 309.33 | 20.32 |
April | 416.67 | 21.24 | 146.50 | 20.99 | 137.33 | 20.79 |
May | 354.50 | 21.75 | 129.50 | 21.80 | 70.67 | 21.55 |
June | 163.67 | 22.62 | 250.50 | 23.69 | 14.33 | 23.74 |
July | 102.83 | 23.92 | 357.33 | 24.34 | 29.00 | 24.48 |
August | 149.50 | 22.78 | 287.00 | 23.81 | 11.50 | 23.87 |
September | 313.67 | 22.10 | 149.17 | 22.70 | 45.00 | 22.71 |
October | 493.00 | 21.20 | 139.17 | 20.93 | 139.17 | 20.76 |
November | 489.00 | 20.26 | 350.00 | 20.12 | 350.00 | 20.06 |
December | 497.00 | 19.87 | 466.83 | 19.84 | 466.83 | 19.83 |
Annual Sum or Average | 4445.17 | 20.91 | 3449.67 | 21.09 | 2437.50 | 20.86 |
Minimum of Months | 102.83 | 19.82 | 129.50 | 19.80 | 11.50 | 19.80 |
Maximum of Months | 509.33 | 23.92 | 488.33 | 24.34 | 488.33 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.17 | 20.24 | 400.17 | 20.06 | 400.17 | 19.99 |
February | 409.17 | 20.78 | 275.00 | 20.59 | 260.33 | 20.44 |
March | 440.83 | 20.85 | 270.67 | 20.69 | 247.17 | 20.53 |
April | 392.67 | 21.30 | 171.83 | 21.19 | 138.33 | 20.97 |
May | 357.83 | 21.73 | 147.00 | 21.82 | 83.67 | 21.57 |
June | 226.33 | 22.38 | 182.33 | 23.23 | 8.33 | 23.22 |
July | 135.67 | 23.11 | 294.00 | 24.00 | 14.33 | 24.08 |
August | 165.50 | 22.73 | 273.50 | 23.76 | 9.83 | 23.80 |
September | 255.17 | 22.26 | 217.83 | 23.12 | 50.83 | 23.12 |
October | 367.83 | 21.51 | 171.17 | 21.63 | 104.67 | 21.41 |
November | 433.00 | 20.89 | 249.67 | 20.69 | 233.83 | 20.53 |
December | 477.17 | 20.26 | 364.67 | 20.05 | 364.67 | 19.97 |
Annual Sum or Average | 4154.33 | 21.20 | 3017.83 | 21.41 | 1916.17 | 21.14 |
Minimum of Months | 135.67 | 20.24 | 147.00 | 20.05 | 8.33 | 19.97 |
Maximum of Months | 493.17 | 23.11 | 400.17 | 24.00 | 400.17 | 24.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.87 | 473.50 | 19.83 | 473.50 | 19.82 |
February | 449.83 | 20.34 | 354.17 | 20.21 | 354.17 | 20.15 |
March | 498.50 | 20.65 | 297.33 | 20.46 | 297.33 | 20.37 |
April | 433.00 | 21.21 | 156.33 | 21.09 | 134.50 | 20.92 |
May | 378.00 | 21.77 | 144.33 | 21.97 | 69.67 | 21.78 |
June | 237.67 | 22.41 | 197.33 | 23.29 | 11.50 | 23.34 |
July | 146.50 | 23.03 | 296.50 | 23.96 | 17.67 | 24.06 |
August | 204.00 | 22.53 | 229.00 | 23.52 | 7.00 | 23.56 |
September | 338.83 | 21.85 | 145.00 | 22.41 | 47.83 | 22.39 |
October | 474.67 | 21.15 | 146.67 | 20.97 | 136.50 | 20.82 |
November | 488.00 | 20.48 | 314.83 | 20.29 | 314.83 | 20.21 |
December | 497.00 | 19.98 | 437.67 | 19.91 | 437.67 | 19.88 |
Annual Sum or Average | 4648.00 | 20.98 | 3192.67 | 21.11 | 2302.17 | 20.88 |
Minimum of Months | 146.50 | 19.87 | 144.33 | 19.83 | 7.00 | 19.82 |
Maximum of Months | 502.00 | 23.03 | 473.50 | 23.96 | 473.50 | 24.06 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 26.27 | 389.17 | 27.00 | 0.00 | 27.00 |
February | 1.50 | 27.00 | 436.83 | 27.00 | 1.50 | 27.00 |
March | 5.33 | 27.00 | 512.50 | 27.00 | 5.33 | 27.00 |
April | 22.67 | 27.00 | 485.00 | 27.00 | 22.67 | 27.00 |
May | 1.50 | 27.00 | 508.00 | 27.00 | 1.50 | 27.00 |
June | 16.83 | 27.00 | 496.00 | 27.00 | 16.83 | 27.00 |
July | 116.17 | 27.00 | 497.00 | 27.00 | 116.17 | 27.00 |
August | 227.83 | 27.08 | 514.00 | 27.05 | 227.83 | 27.06 |
September | 8.17 | 27.00 | 485.00 | 27.00 | 8.17 | 27.00 |
October | 8.50 | 27.00 | 502.00 | 27.00 | 8.50 | 27.00 |
November | 6.17 | 27.00 | 489.00 | 27.00 | 6.17 | 27.00 |
December | 3.00 | 27.00 | 497.00 | 27.00 | 3.00 | 27.00 |
Annual Sum or Average | 418.33 | 27.04 | 5811.50 | 27.01 | 417.67 | 27.01 |
Minimum of Months | 0.67 | 26.27 | 389.17 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 227.83 | 27.08 | 514.00 | 27.05 | 227.83 | 27.06 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 99.83 | 25.62 | 214.00 | 26.56 | 0.00 | 26.56 |
February | 13.17 | 27.00 | 312.33 | 27.00 | 0.00 | 27.00 |
March | 6.50 | 27.00 | 463.17 | 27.00 | 0.00 | 27.00 |
April | 3.33 | 27.00 | 480.33 | 27.00 | 3.33 | 27.00 |
May | 0.83 | 27.00 | 498.33 | 27.00 | 0.83 | 27.00 |
June | 7.17 | 27.00 | 496.00 | 27.00 | 7.17 | 27.00 |
July | 16.50 | 27.00 | 497.00 | 27.00 | 16.50 | 27.00 |
August | 34.50 | 27.19 | 514.00 | 27.03 | 34.50 | 27.03 |
September | 4.00 | 27.00 | 485.00 | 27.00 | 4.00 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 455.33 | 27.00 | 0.00 | 27.00 |
December | 12.00 | 27.00 | 346.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 197.83 | 26.34 | 5263.67 | 26.98 | 66.33 | 26.98 |
Minimum of Months | 0.00 | 0.00 | 214.00 | 26.56 | 0.00 | 26.56 |
Maximum of Months | 99.83 | 27.19 | 514.00 | 27.03 | 34.50 | 27.03 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 267.33 | 24.62 | 124.50 | 24.96 | 32.33 | 24.72 |
February | 46.33 | 26.94 | 183.67 | 26.99 | 0.00 | 26.99 |
March | 21.83 | 27.00 | 355.17 | 27.00 | 0.00 | 27.00 |
April | 4.17 | 27.00 | 421.67 | 27.00 | 4.17 | 27.00 |
May | 22.67 | 25.75 | 472.83 | 26.94 | 1.50 | 26.94 |
June | 9.67 | 27.00 | 496.00 | 27.00 | 9.67 | 27.00 |
July | 42.17 | 27.00 | 497.00 | 27.00 | 42.17 | 27.00 |
August | 58.00 | 27.10 | 514.00 | 27.02 | 58.00 | 27.03 |
September | 6.00 | 27.00 | 476.17 | 27.00 | 6.00 | 27.00 |
October | 0.00 | 0.00 | 455.67 | 27.00 | 0.00 | 27.00 |
November | 22.50 | 27.00 | 320.67 | 27.00 | 0.00 | 27.00 |
December | 65.83 | 27.00 | 206.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 566.50 | 25.83 | 4523.50 | 26.84 | 153.83 | 26.81 |
Minimum of Months | 0.00 | 0.00 | 124.50 | 24.96 | 0.00 | 24.72 |
Maximum of Months | 267.33 | 27.10 | 514.00 | 27.02 | 58.00 | 27.03 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 236.00 | 27.00 | 502.00 | 27.00 | 236.00 | 27.00 |
February | 454.00 | 27.01 | 454.00 | 27.01 | 454.00 | 27.01 |
March | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
April | 485.00 | 27.07 | 485.00 | 27.07 | 485.00 | 27.07 |
May | 490.00 | 27.00 | 508.00 | 27.00 | 490.00 | 27.00 |
June | 496.00 | 27.01 | 496.00 | 27.01 | 496.00 | 27.01 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 28.64 | 514.00 | 28.64 | 514.00 | 28.64 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.01 | 502.00 | 27.01 | 502.00 | 27.01 |
November | 489.00 | 27.01 | 489.00 | 27.01 | 489.00 | 27.01 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5659.00 | 27.16 | 5943.00 | 27.16 | 5659.00 | 27.16 |
Minimum of Months | 236.00 | 27.00 | 454.00 | 27.00 | 236.00 | 27.00 |
Maximum of Months | 514.00 | 28.64 | 514.00 | 28.64 | 514.00 | 28.64 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99490 | 13.62839 | 0.61185 | 13.07136 |
February | 454.00000 | 27.00000 | 14.88765 | 0.70540 | 15.64095 |
March | 514.00000 | 27.00000 | 16.83473 | 0.78876 | 18.24563 |
April | 485.00000 | 27.00001 | 20.01035 | 0.88618 | 21.66965 |
May | 508.00000 | 27.00015 | 22.20497 | 0.14169 | 5.59476 |
June | 496.00000 | 27.00044 | 25.70015 | 0.25807 | 6.49326 |
July | 497.00000 | 27.00025 | 26.88201 | 0.33213 | 7.38715 |
August | 514.00000 | 27.03490 | 26.43124 | 0.38575 | 8.27403 |
September | 485.00000 | 27.00051 | 25.35453 | 0.17738 | 5.82274 |
October | 502.00000 | 27.00006 | 22.37184 | 0.83699 | 19.85120 |
November | 489.00000 | 27.00000 | 18.49119 | 0.80724 | 18.85041 |
December | 497.00000 | 27.00000 | 14.80780 | 0.76736 | 17.56590 |
Annual Sum or Average | 5943.00000 | 27.00271 | 20.67327 | 0.55667 | 13.17101 |
Minimum of Months | 454.00000 | 26.99490 | 13.62839 | 0.14169 | 5.59476 |
Maximum of Months | 514.00000 | 27.03490 | 26.88201 | 0.88618 | 21.66965 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.69802 | 13.63789 | 0.44205 | 9.94706 |
February | 454.00000 | 27.00000 | 14.87950 | 0.57003 | 12.03889 |
March | 514.00000 | 27.00000 | 16.81832 | 0.64243 | 13.88428 |
April | 485.00000 | 27.00002 | 19.97972 | 0.73735 | 16.61523 |
May | 508.00000 | 27.00014 | 22.22341 | 0.04219 | 5.34040 |
June | 496.00000 | 27.00042 | 25.71351 | 0.15852 | 5.71168 |
July | 497.00000 | 27.00027 | 26.88319 | 0.22156 | 6.17603 |
August | 514.00000 | 27.01421 | 26.44788 | 0.23247 | 6.33618 |
September | 485.00000 | 27.00042 | 25.45500 | 0.08602 | 5.40635 |
October | 502.00000 | 27.00006 | 22.35327 | 0.72628 | 16.21667 |
November | 489.00000 | 27.00000 | 18.46547 | 0.65253 | 14.12632 |
December | 497.00000 | 27.00000 | 14.78128 | 0.57110 | 12.08892 |
Annual Sum or Average | 5943.00000 | 26.97583 | 20.67605 | 0.42191 | 10.29867 |
Minimum of Months | 454.00000 | 26.69802 | 13.63789 | 0.04219 | 5.34040 |
Maximum of Months | 514.00000 | 27.01421 | 26.88319 | 0.73735 | 16.61523 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.69245 | 13.96200 | 0.17581 | 8.81200 |
February | 454.00000 | 26.99433 | 14.88094 | 0.49591 | 10.49331 |
March | 514.00000 | 27.00000 | 16.82506 | 0.57320 | 12.24657 |
April | 485.00000 | 27.00002 | 19.99553 | 0.67789 | 15.00140 |
May | 508.00000 | 26.94141 | 22.28278 | -0.0233 | 6.04910 |
June | 496.00000 | 27.00043 | 25.72724 | 0.14533 | 5.79274 |
July | 497.00000 | 27.00027 | 26.89229 | 0.22152 | 6.30109 |
August | 514.00000 | 27.01218 | 26.45819 | 0.22232 | 6.38359 |
September | 485.00000 | 27.00025 | 25.53745 | 0.04511 | 5.52958 |
October | 502.00000 | 27.00006 | 22.37649 | 0.66004 | 14.39732 |
November | 489.00000 | 27.00001 | 18.47708 | 0.56792 | 12.06912 |
December | 497.00000 | 27.00000 | 14.79243 | 0.48961 | 10.38469 |
Annual Sum or Average | 5943.00000 | 26.88525 | 20.72386 | 0.35263 | 9.43787 |
Minimum of Months | 454.00000 | 25.69245 | 13.96200 | -0.0233 | 5.52958 |
Maximum of Months | 514.00000 | 27.01218 | 26.89229 | 0.67789 | 15.00140 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99981 | 30.00049 | 0.99374 | 25.89664 |
February | 454.00000 | 27.01078 | 29.99966 | 1.18262 | 34.42412 |
March | 514.00000 | 27.00795 | 29.99988 | 1.34234 | 42.47348 |
April | 485.00000 | 27.06675 | 29.99907 | 1.49883 | 50.83931 |
May | 508.00000 | 27.00179 | 30.00194 | 0.46759 | 9.61113 |
June | 496.00000 | 27.00948 | 29.99933 | 0.71320 | 15.72080 |
July | 497.00000 | 27.00531 | 30.02780 | 0.93155 | 23.34487 |
August | 514.00000 | 28.64486 | 29.87838 | 1.59673 | 55.38967 |
September | 485.00000 | 27.00302 | 30.00174 | 0.52492 | 10.82973 |
October | 502.00000 | 27.01100 | 29.99906 | 1.24779 | 37.62196 |
November | 489.00000 | 27.00798 | 29.99859 | 1.37396 | 44.13327 |
December | 497.00000 | 27.00097 | 30.00028 | 1.48221 | 49.93784 |
Annual Sum or Average | 5943.00000 | 27.15251 | 29.99182 | 1.11343 | 33.38527 |
Minimum of Months | 454.00000 | 26.99981 | 29.87838 | 0.46759 | 9.61113 |
Maximum of Months | 514.00000 | 28.64486 | 30.02780 | 1.59673 | 55.38967 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.70856 | 12.38623 | 0.09392 | 6.75309 |
February | 454.00000 | 24.13296 | 14.08573 | 0.20466 | 6.53852 |
March | 514.00000 | 24.27482 | 15.10745 | 0.25555 | 6.66082 |
April | 485.00000 | 24.44224 | 18.68000 | 0.32108 | 7.48544 |
May | 508.00000 | 24.46415 | 22.37733 | -0.5046 | 11.30397 |
June | 496.00000 | 24.43836 | 31.09925 | -0.4325 | 9.70754 |
July | 497.00000 | 24.60675 | 35.53865 | -0.3413 | 8.73746 |
August | 514.00000 | 24.47978 | 30.66511 | -0.4032 | 9.34697 |
September | 485.00000 | 24.54025 | 30.25048 | -0.4028 | 9.54345 |
October | 502.00000 | 24.57326 | 20.84148 | 0.38143 | 8.61691 |
November | 489.00000 | 24.54907 | 16.29411 | 0.33627 | 7.87166 |
December | 497.00000 | 24.29826 | 13.41643 | 0.25174 | 6.91087 |
Annual Sum or Average | 5943.00000 | 24.37653 | 21.77772 | -0.0227 | 8.30474 |
Minimum of Months | 454.00000 | 23.70856 | 12.38623 | -0.5046 | 6.53852 |
Maximum of Months | 514.00000 | 24.60675 | 35.53865 | 0.38143 | 11.30397 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.67350 | 14.38255 | 0.06957 | 5.99637 |
February | 454.00000 | 24.00541 | 15.76540 | 0.17759 | 6.05796 |
March | 514.00000 | 24.20043 | 16.44079 | 0.25195 | 6.54396 |
April | 485.00000 | 24.32866 | 19.69834 | 0.32329 | 7.44150 |
May | 508.00000 | 24.33576 | 23.61159 | -0.5251 | 11.45788 |
June | 496.00000 | 24.24353 | 32.39644 | -0.4515 | 9.63282 |
July | 497.00000 | 24.30374 | 36.45446 | -0.3885 | 8.61598 |
August | 514.00000 | 24.24943 | 31.76956 | -0.4264 | 9.10833 |
September | 485.00000 | 24.30446 | 31.46318 | -0.4586 | 9.98963 |
October | 502.00000 | 24.38017 | 22.45818 | 0.34791 | 7.83842 |
November | 489.00000 | 24.36954 | 17.89279 | 0.30144 | 7.17527 |
December | 497.00000 | 24.22258 | 15.14635 | 0.23450 | 6.46131 |
Annual Sum or Average | 5943.00000 | 24.21897 | 23.17070 | -0.0479 | 8.04229 |
Minimum of Months | 454.00000 | 23.67350 | 14.38255 | -0.5251 | 5.99637 |
Maximum of Months | 514.00000 | 24.38017 | 36.45446 | 0.34791 | 11.45788 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.30568 | 16.86609 | -0.2744 | 8.19720 |
February | 454.00000 | 22.84615 | 17.59246 | -0.1280 | 6.72346 |
March | 514.00000 | 23.40222 | 18.27499 | 0.02740 | 5.96262 |
April | 485.00000 | 23.84274 | 21.33002 | 0.17238 | 5.97375 |
May | 508.00000 | 24.08543 | 24.53332 | -0.6463 | 14.66046 |
June | 496.00000 | 24.12970 | 32.94674 | -0.5258 | 11.15946 |
July | 497.00000 | 24.23274 | 36.90761 | -0.4545 | 9.76981 |
August | 514.00000 | 24.21580 | 32.08386 | -0.4940 | 10.43834 |
September | 485.00000 | 24.13765 | 32.16960 | -0.5487 | 11.91860 |
October | 502.00000 | 23.93933 | 24.05068 | 0.21380 | 6.17869 |
November | 489.00000 | 23.50918 | 19.85775 | 0.05957 | 5.81210 |
December | 497.00000 | 22.66998 | 17.04837 | -0.1738 | 7.36702 |
Annual Sum or Average | 5943.00000 | 23.61495 | 24.51456 | -0.2327 | 8.70247 |
Minimum of Months | 454.00000 | 22.30568 | 16.86609 | -0.6463 | 5.81210 |
Maximum of Months | 514.00000 | 24.23274 | 36.90761 | 0.21380 | 14.66046 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.72390 | 15.84935 | -0.6978 | 18.18191 |
February | 454.00000 | 21.39875 | 18.35209 | -0.5011 | 12.86868 |
March | 514.00000 | 22.12515 | 19.77100 | -0.2999 | 9.61325 |
April | 485.00000 | 22.88517 | 22.98520 | -0.0719 | 6.96531 |
May | 508.00000 | 23.53415 | 25.47651 | -0.8488 | 22.88321 |
June | 496.00000 | 23.98613 | 33.09636 | -0.5739 | 12.75974 |
July | 497.00000 | 24.17048 | 36.88961 | -0.4657 | 10.04620 |
August | 514.00000 | 24.13629 | 32.18786 | -0.5212 | 11.22352 |
September | 485.00000 | 23.74401 | 33.20886 | -0.6972 | 17.24152 |
October | 502.00000 | 22.85629 | 26.26057 | -0.0637 | 6.65617 |
November | 489.00000 | 21.90431 | 21.59987 | -0.3479 | 10.31112 |
December | 497.00000 | 21.03866 | 17.93101 | -0.5953 | 16.02068 |
Annual Sum or Average | 5943.00000 | 22.71890 | 25.34041 | -0.4742 | 12.90803 |
Minimum of Months | 454.00000 | 20.72390 | 15.84935 | -0.8488 | 6.65617 |
Maximum of Months | 514.00000 | 24.17048 | 36.88961 | -0.0637 | 22.88321 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.93659 | 14.08719 | -0.6258 | 15.31817 |
February | 454.00000 | 21.64948 | 16.28270 | -0.4088 | 10.27672 |
March | 514.00000 | 22.49879 | 17.04854 | -0.1818 | 7.11893 |
April | 485.00000 | 23.35826 | 20.22475 | 0.06158 | 5.78746 |
May | 508.00000 | 23.68274 | 23.90017 | -0.7632 | 19.28761 |
June | 496.00000 | 24.10500 | 31.97485 | -0.4949 | 10.75618 |
July | 497.00000 | 24.29325 | 35.67876 | -0.3758 | 8.52616 |
August | 514.00000 | 24.15952 | 31.32959 | -0.4673 | 10.09933 |
September | 485.00000 | 23.79277 | 31.81349 | -0.6601 | 16.13472 |
October | 502.00000 | 23.28437 | 23.13973 | 0.05448 | 5.72240 |
November | 489.00000 | 22.48587 | 18.65002 | -0.1772 | 6.96485 |
December | 497.00000 | 21.60372 | 15.67503 | -0.4174 | 10.27917 |
Annual Sum or Average | 5943.00000 | 22.99709 | 23.36003 | -0.3719 | 10.53267 |
Minimum of Months | 454.00000 | 20.93659 | 14.08719 | -0.7632 | 5.72240 |
Maximum of Months | 514.00000 | 24.29325 | 35.67876 | 0.06158 | 19.28761 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.89423 | 13.41916 | -0.6249 | 15.27781 |
February | 454.00000 | 21.58728 | 15.61802 | -0.3992 | 10.51605 |
March | 514.00000 | 22.08464 | 16.65656 | -0.2353 | 8.13270 |
April | 485.00000 | 22.88199 | 20.21822 | 0.01002 | 6.88559 |
May | 508.00000 | 23.35970 | 23.73402 | -0.7781 | 21.05061 |
June | 496.00000 | 23.95010 | 31.94301 | -0.4416 | 11.60703 |
July | 497.00000 | 24.18219 | 35.70118 | -0.2983 | 8.87849 |
August | 514.00000 | 23.85389 | 31.56527 | -0.4620 | 11.45880 |
September | 485.00000 | 23.53051 | 31.86682 | -0.6529 | 17.60474 |
October | 502.00000 | 22.85222 | 23.05945 | 0.00409 | 6.39245 |
November | 489.00000 | 21.93796 | 18.48665 | -0.2739 | 7.90251 |
December | 497.00000 | 21.16299 | 15.35236 | -0.5092 | 11.74430 |
Annual Sum or Average | 5943.00000 | 22.69796 | 23.18094 | -0.3891 | 11.46984 |
Minimum of Months | 454.00000 | 20.89423 | 13.41916 | -0.7781 | 6.39245 |
Maximum of Months | 514.00000 | 24.18219 | 35.70118 | 0.01002 | 21.05061 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.47797 | 13.16279 | -0.4734 | 13.85572 |
February | 454.00000 | 22.34819 | 15.01570 | -0.1972 | 10.10257 |
March | 514.00000 | 22.55611 | 16.21317 | -0.1126 | 8.31767 |
April | 485.00000 | 23.11852 | 19.98044 | 0.05758 | 7.14243 |
May | 508.00000 | 23.33474 | 23.84171 | -0.8159 | 22.95013 |
June | 496.00000 | 23.88195 | 32.17702 | -0.5165 | 12.62624 |
July | 497.00000 | 24.19401 | 35.72988 | -0.3401 | 8.97959 |
August | 514.00000 | 24.06837 | 31.16991 | -0.3902 | 9.97256 |
September | 485.00000 | 23.84195 | 31.23842 | -0.5221 | 15.19343 |
October | 502.00000 | 23.41671 | 22.24350 | 0.16308 | 7.75957 |
November | 489.00000 | 22.76721 | 17.67216 | -0.0600 | 8.22552 |
December | 497.00000 | 21.91742 | 14.77186 | -0.3152 | 10.90437 |
Annual Sum or Average | 5943.00000 | 23.08162 | 22.81669 | -0.2953 | 11.35746 |
Minimum of Months | 454.00000 | 21.47797 | 13.16279 | -0.8159 | 7.14243 |
Maximum of Months | 514.00000 | 24.19401 | 35.72988 | 0.16308 | 22.95013 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.17574 | 13.08421 | -0.5198 | 12.32272 |
February | 454.00000 | 22.20986 | 14.87227 | -0.2047 | 8.18463 |
March | 514.00000 | 23.08482 | 15.55306 | 0.04233 | 6.62851 |
April | 485.00000 | 24.07273 | 18.69494 | 0.34105 | 8.53225 |
May | 508.00000 | 23.70611 | 23.16999 | -0.6165 | 16.68288 |
June | 496.00000 | 24.18685 | 31.47661 | -0.3069 | 8.80630 |
July | 497.00000 | 24.47445 | 35.03296 | -0.1280 | 7.11538 |
August | 514.00000 | 24.38686 | 30.46038 | -0.1708 | 7.08115 |
September | 485.00000 | 23.73050 | 31.31603 | -0.5403 | 14.75420 |
October | 502.00000 | 23.56875 | 21.91553 | 0.20695 | 7.09435 |
November | 489.00000 | 23.14146 | 17.07746 | 0.05180 | 6.65717 |
December | 497.00000 | 22.55762 | 14.01692 | -0.1248 | 7.09664 |
Annual Sum or Average | 5943.00000 | 23.36539 | 22.26813 | -0.1646 | 9.24877 |
Minimum of Months | 454.00000 | 21.17574 | 13.08421 | -0.6165 | 6.62851 |
Maximum of Months | 514.00000 | 24.47445 | 35.03296 | 0.34105 | 16.68288 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97723 | 14.25844 | -0.9404 | 25.85463 |
February | 454.00000 | 20.41274 | 17.12537 | -0.7696 | 19.17661 |
March | 514.00000 | 20.89903 | 18.58482 | -0.5932 | 14.19847 |
April | 485.00000 | 21.90056 | 22.39242 | -0.2978 | 8.56149 |
May | 508.00000 | 22.83862 | 25.33342 | -1.0643 | 31.83290 |
June | 496.00000 | 23.81947 | 32.69581 | -0.6196 | 14.36619 |
July | 497.00000 | 24.14908 | 35.89608 | -0.4616 | 10.17951 |
August | 514.00000 | 23.94231 | 31.79365 | -0.5880 | 13.36146 |
September | 485.00000 | 23.13061 | 33.11813 | -0.9009 | 25.73983 |
October | 502.00000 | 21.86266 | 25.35158 | -0.2915 | 8.17780 |
November | 489.00000 | 20.76955 | 20.22525 | -0.6199 | 15.22038 |
December | 497.00000 | 20.07062 | 16.80845 | -0.8637 | 23.20101 |
Annual Sum or Average | 5943.00000 | 21.99387 | 24.50734 | -0.6674 | 17.48646 |
Minimum of Months | 454.00000 | 19.97723 | 14.25844 | -1.0643 | 8.17780 |
Maximum of Months | 514.00000 | 24.14908 | 35.89608 | -0.2915 | 31.83290 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.99326 | 13.14845 | -0.9211 | 25.04471 |
February | 385.00000 | 20.56596 | 15.89631 | -0.7072 | 17.64837 |
March | 433.00000 | 21.01078 | 17.23484 | -0.5370 | 13.32505 |
April | 410.00000 | 22.03612 | 21.13663 | -0.2164 | 8.68810 |
May | 430.00000 | 22.69746 | 24.57197 | -1.0262 | 31.44550 |
June | 418.00000 | 23.78089 | 32.02084 | -0.5201 | 14.68318 |
July | 422.00000 | 24.22304 | 35.21646 | -0.3128 | 10.09880 |
August | 433.00000 | 23.84467 | 31.06142 | -0.5017 | 13.54526 |
September | 410.00000 | 23.04139 | 32.58756 | -0.8410 | 25.45281 |
October | 427.00000 | 21.78483 | 24.29756 | -0.2697 | 8.03661 |
November | 417.00000 | 20.76221 | 18.99034 | -0.6039 | 14.35457 |
December | 422.00000 | 19.99828 | 15.64177 | -0.8690 | 23.33436 |
Annual Sum or Average | 5034.00000 | 21.98667 | 23.51620 | -0.6105 | 17.14476 |
Minimum of Months | 385.00000 | 19.99326 | 13.14845 | -1.0262 | 8.03661 |
Maximum of Months | 433.00000 | 24.22304 | 35.21646 | -0.2164 | 31.44550 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.93421 | 13.01990 | -0.6417 | 18.10011 |
February | 454.00000 | 21.78548 | 15.25048 | -0.3552 | 13.11540 |
March | 514.00000 | 21.89766 | 16.91697 | -0.2852 | 10.97328 |
April | 485.00000 | 22.48019 | 21.00612 | -0.1050 | 8.47920 |
May | 508.00000 | 22.89410 | 24.60854 | -0.9729 | 29.56350 |
June | 496.00000 | 23.62020 | 32.70652 | -0.6187 | 16.05601 |
July | 497.00000 | 24.08093 | 35.84287 | -0.4001 | 10.54804 |
August | 514.00000 | 23.94766 | 31.25513 | -0.4577 | 12.25817 |
September | 485.00000 | 23.58043 | 31.74137 | -0.6111 | 19.11299 |
October | 502.00000 | 22.91108 | 23.09689 | 0.04346 | 8.44111 |
November | 489.00000 | 22.08519 | 18.23643 | -0.2410 | 10.67283 |
December | 497.00000 | 21.00581 | 15.36623 | -0.5734 | 16.57430 |
Annual Sum or Average | 5943.00000 | 22.60784 | 23.30295 | -0.4364 | 14.51828 |
Minimum of Months | 454.00000 | 20.93421 | 13.01990 | -0.9729 | 8.44111 |
Maximum of Months | 514.00000 | 24.08093 | 35.84287 | 0.04346 | 29.56350 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.20839 | 13.33832 | -0.8571 | 22.55879 |
February | 454.00000 | 20.75928 | 15.98346 | -0.6414 | 16.06516 |
March | 514.00000 | 21.13454 | 17.53401 | -0.4903 | 12.35397 |
April | 485.00000 | 22.04032 | 21.41564 | -0.2001 | 8.21609 |
May | 508.00000 | 22.78528 | 24.66355 | -0.9717 | 29.99625 |
June | 496.00000 | 23.54563 | 32.79936 | -0.5894 | 16.01497 |
July | 497.00000 | 23.99796 | 36.03479 | -0.3827 | 10.76644 |
August | 514.00000 | 23.74704 | 31.65541 | -0.5198 | 13.78187 |
September | 485.00000 | 22.89615 | 32.90768 | -0.8667 | 26.44313 |
October | 502.00000 | 21.87513 | 24.43023 | -0.2323 | 7.89073 |
November | 489.00000 | 21.00588 | 19.18231 | -0.5241 | 12.84249 |
December | 497.00000 | 20.27404 | 15.83872 | -0.7809 | 20.27073 |
Annual Sum or Average | 5943.00000 | 22.03308 | 23.86090 | -0.5881 | 16.44115 |
Minimum of Months | 454.00000 | 20.20839 | 13.33832 | -0.9717 | 7.89073 |
Maximum of Months | 514.00000 | 23.99796 | 36.03479 | -0.2001 | 29.99625 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.65330 | 14.10673 | -1.0932 | 32.48294 |
February | 454.00000 | 19.99323 | 17.19038 | -0.9318 | 25.65421 |
March | 514.00000 | 20.35663 | 18.84577 | -0.7765 | 20.06017 |
April | 485.00000 | 21.05409 | 23.18807 | -0.5238 | 13.47240 |
May | 508.00000 | 22.17772 | 26.02146 | -1.2983 | 41.56313 |
June | 496.00000 | 23.43471 | 33.24437 | -0.7395 | 19.31221 |
July | 497.00000 | 23.92614 | 36.26760 | -0.5217 | 12.23048 |
August | 514.00000 | 23.61876 | 32.29005 | -0.6863 | 17.21255 |
September | 485.00000 | 22.48843 | 34.17203 | -1.1208 | 35.51506 |
October | 502.00000 | 20.92335 | 26.53482 | -0.5423 | 13.36506 |
November | 489.00000 | 20.12574 | 20.83278 | -0.8338 | 22.39329 |
December | 497.00000 | 19.81335 | 16.64572 | -1.0062 | 28.86730 |
Annual Sum or Average | 5943.00000 | 21.47700 | 24.98792 | -0.8391 | 23.49801 |
Minimum of Months | 454.00000 | 19.65330 | 14.10673 | -1.2983 | 12.23048 |
Maximum of Months | 514.00000 | 23.92614 | 36.26760 | -0.5217 | 41.56313 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.81879 | 13.67424 | -1.0321 | 29.81375 |
February | 454.00000 | 20.21505 | 16.51655 | -0.8405 | 22.39449 |
March | 514.00000 | 20.66950 | 18.07375 | -0.6590 | 17.10474 |
April | 485.00000 | 21.64018 | 21.93211 | -0.3355 | 11.48941 |
May | 508.00000 | 22.47489 | 25.11854 | -1.1144 | 34.50547 |
June | 496.00000 | 23.68307 | 32.30263 | -0.5360 | 15.48661 |
July | 497.00000 | 24.13509 | 35.51840 | -0.3071 | 10.04445 |
August | 514.00000 | 23.78095 | 31.47246 | -0.4958 | 13.87385 |
September | 485.00000 | 22.86594 | 33.19595 | -0.9099 | 28.52277 |
October | 502.00000 | 21.24608 | 25.57532 | -0.4232 | 11.15271 |
November | 489.00000 | 20.26345 | 20.22556 | -0.7734 | 20.10052 |
December | 497.00000 | 19.87451 | 16.17855 | -0.9722 | 27.52421 |
Annual Sum or Average | 5943.00000 | 21.73496 | 24.19176 | -0.6993 | 20.15347 |
Minimum of Months | 454.00000 | 19.81879 | 13.67424 | -1.1144 | 10.04445 |
Maximum of Months | 514.00000 | 24.13509 | 35.51840 | -0.3071 | 34.50547 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.31257 | 13.35778 | -0.8514 | 24.42411 |
February | 454.00000 | 21.13325 | 15.74807 | -0.5597 | 17.42011 |
March | 514.00000 | 21.30802 | 17.47882 | -0.4728 | 15.12952 |
April | 485.00000 | 21.87005 | 21.76430 | -0.2814 | 11.57841 |
May | 508.00000 | 22.47370 | 25.19744 | -1.1385 | 36.08289 |
June | 496.00000 | 23.37038 | 33.05305 | -0.7003 | 19.64634 |
July | 497.00000 | 23.91398 | 36.10240 | -0.4427 | 12.28631 |
August | 514.00000 | 23.76268 | 31.56512 | -0.5139 | 14.69950 |
September | 485.00000 | 23.23099 | 32.46089 | -0.7468 | 24.70777 |
October | 502.00000 | 22.22500 | 24.19713 | -0.1521 | 10.50772 |
November | 489.00000 | 21.25780 | 19.19103 | -0.4849 | 14.93322 |
December | 497.00000 | 20.40717 | 15.76055 | -0.7789 | 22.46275 |
Annual Sum or Average | 5943.00000 | 22.11337 | 23.87092 | -0.5946 | 18.68126 |
Minimum of Months | 454.00000 | 20.31257 | 13.35778 | -1.1385 | 10.50772 |
Maximum of Months | 514.00000 | 23.91398 | 36.10240 | -0.1521 | 36.08289 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.86742 | 13.55840 | -1.0062 | 28.84375 |
February | 454.00000 | 20.37585 | 16.27959 | -0.7843 | 20.95125 |
March | 514.00000 | 20.75190 | 17.88774 | -0.6301 | 16.46453 |
April | 485.00000 | 21.53053 | 22.03797 | -0.3508 | 11.10647 |
May | 508.00000 | 22.40550 | 25.17928 | -1.1207 | 35.94052 |
June | 496.00000 | 23.30874 | 33.11788 | -0.6657 | 19.32560 |
July | 497.00000 | 23.82567 | 36.29768 | -0.4264 | 12.50441 |
August | 514.00000 | 23.54091 | 31.99225 | -0.5822 | 16.39295 |
September | 485.00000 | 22.57138 | 33.58443 | -0.9926 | 32.13746 |
October | 502.00000 | 21.31159 | 25.35438 | -0.3985 | 10.92184 |
November | 489.00000 | 20.48866 | 19.87984 | -0.6984 | 18.07029 |
December | 497.00000 | 19.98005 | 15.99102 | -0.9165 | 25.45648 |
Annual Sum or Average | 5943.00000 | 21.67457 | 24.30870 | -0.7142 | 20.67684 |
Minimum of Months | 454.00000 | 19.86742 | 13.55840 | -1.1207 | 10.92184 |
Maximum of Months | 514.00000 | 23.82567 | 36.29768 | -0.3508 | 35.94052 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.146005E+09 | 2653.17 | 25-JAN-06:13 | 15.31 | 0.664844E+09 | 0.00 | 0.810849E+09 | 0.09 | 4.56 | 18-JAN-05:00 | 0.00 | 0.00 |
February | 0.139478E+10 | 57932.15 | 27-FEB-15:30 | 51.20 | 0.766623E+10 | 0.00 | 0.906101E+10 | 0.36 | 6.69 | 27-FEB-13:40 | 0.00 | 0.00 |
March | 0.780301E+09 | 10218.29 | 14-MAR-13:30 | 78.03 | 0.355391E+10 | 0.00 | 0.433422E+10 | 0.48 | 4.56 | 16-MAR-12:20 | 0.00 | 0.00 |
April | 0.105760E+11 | 82261.61 | 07-APR-14:40 | 144.38 | 0.609212E+11 | 0.00 | 0.714972E+11 | 0.99 | 7.42 | 06-APR-15:10 | 0.00 | 0.00 |
May | 0.281768E+11 | 91967.84 | 19-MAY-15:30 | 215.98 | 0.175064E+12 | 0.00 | 0.203241E+12 | 1.59 | 7.40 | 30-MAY-14:50 | 0.00 | 0.00 |
June | 0.695462E+11 | 103253.02 | 29-JUN-15:00 | 368.56 | 0.456624E+12 | 0.00 | 0.526170E+12 | 3.07 | 7.48 | 29-JUN-15:00 | 0.00 | 0.00 |
July | 0.106459E+12 | 121498.27 | 17-JUL-15:30 | 500.23 | 0.724024E+12 | 0.00 | 0.830483E+12 | 4.21 | 7.54 | 25-JUL-15:20 | 0.00 | 0.00 |
August | 0.931619E+11 | 113497.38 | 07-AUG-15:40 | 489.66 | 0.628117E+12 | 0.00 | 0.721279E+12 | 3.98 | 7.53 | 10-AUG-15:40 | 0.00 | 0.00 |
September | 0.517400E+11 | 157579.02 | 07-SEP-15:00 | 300.64 | 0.337901E+12 | 0.00 | 0.389641E+12 | 2.45 | 7.51 | 07-SEP-14:00 | 0.00 | 0.00 |
October | 0.158366E+11 | 84343.56 | 18-OCT-14:30 | 158.33 | 0.966509E+11 | 0.00 | 0.112487E+12 | 1.11 | 7.44 | 16-OCT-13:30 | 0.00 | 0.00 |
November | 0.180340E+10 | 39794.97 | 17-NOV-17:00 | 72.04 | 0.816699E+10 | 0.00 | 0.997039E+10 | 0.46 | 4.56 | 13-NOV-06:50 | 0.00 | 0.00 |
December | 0.382181E+09 | 2657.27 | 27-DEC-17:00 | 40.07 | 0.174066E+10 | 0.00 | 0.212284E+10 | 0.25 | 4.56 | 24-DEC-00:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.380003E+12 | 2434.43 | 0.250109E+13 | 0.00 | 0.288110E+13 | 1.59 | 0.00 | 0.00 | ||||
Minimum of Months | 0.146005E+09 | 2653.17 | 15.31 | 0.664844E+09 | 0.00 | 0.810849E+09 | 0.09 | 4.56 | 0.00 | 0.00 | ||
Maximum of Months | 0.106459E+12 | 157579.02 | 500.23 | 0.724024E+12 | 0.00 | 0.830483E+12 | 4.21 | 7.54 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.202547E+10 | 91967.84 | 19-MAY-15:30 | 6.67 | 0.146942E+11 | 0.00 | 0.167197E+11 | 0.06 | 7.36 | 19-MAY-12:10 | 0.00 | 0.00 |
June | 0.206999E+11 | 103253.02 | 29-JUN-15:00 | 65.69 | 0.150532E+12 | 0.00 | 0.171232E+12 | 0.66 | 7.48 | 29-JUN-15:00 | 0.00 | 0.00 |
July | 0.427509E+11 | 121498.27 | 17-JUL-15:30 | 130.56 | 0.312821E+12 | 0.00 | 0.355572E+12 | 1.28 | 7.54 | 25-JUL-15:20 | 0.00 | 0.00 |
August | 0.359727E+11 | 113497.38 | 07-AUG-15:40 | 110.76 | 0.263948E+12 | 0.00 | 0.299921E+12 | 1.09 | 7.53 | 10-AUG-15:40 | 0.00 | 0.00 |
September | 0.104827E+11 | 157579.02 | 07-SEP-15:00 | 33.30 | 0.760114E+11 | 0.00 | 0.864941E+11 | 0.34 | 7.51 | 07-SEP-14:00 | 0.00 | 0.00 |
October | 0.106160E+10 | 84343.56 | 18-OCT-14:30 | 3.67 | 0.764948E+10 | 0.00 | 0.871108E+10 | 0.04 | 7.25 | 18-OCT-12:40 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.112993E+12 | 350.64 | 0.825656E+12 | 0.00 | 0.938649E+12 | 0.29 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.427509E+11 | 157579.02 | 130.56 | 0.312821E+12 | 0.00 | 0.355572E+12 | 1.28 | 7.54 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.853760E+10 | 744.00 | 7436.44 | 14-JAN-15:00 | 203429.85 | 13-JAN-16:30 | 21.70 | 18.33 | 15.31 |
February | 0.215578E+11 | 672.00 | 49248.27 | 20-FEB-15:40 | 387904.83 | 26-FEB-17:03 | 24.70 | 18.36 | 15.31 |
March | 0.389759E+11 | 744.00 | 49248.27 | 14-MAR-11:20 | 646331.74 | 31-MAR-24:00 | 27.62 | 18.34 | 15.31 |
April | 0.831700E+11 | 720.00 | 49248.27 | 01-APR-11:00 | 704607.28 | 16-APR-18:02 | 31.45 | 19.20 | 15.31 |
May | 0.529996E+11 | 744.00 | 49248.27 | 02-MAY-10:20 | 365958.40 | 31-MAY-24:00 | 23.16 | 19.26 | 15.31 |
June | 0.103375E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 529048.27 | 30-JUN-23:33 | 29.08 | 22.15 | 15.31 |
July | 0.127835E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 686446.65 | 31-JUL-23:42 | 36.34 | 26.41 | 15.31 |
August | 0.129415E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 759557.43 | 05-AUG-19:32 | 39.16 | 26.48 | 15.31 |
September | 0.754933E+11 | 720.00 | 49248.27 | 01-SEP-00:02 | 353867.39 | 30-SEP-24:00 | 24.70 | 20.68 | 15.31 |
October | 0.613285E+11 | 744.00 | 49248.27 | 02-OCT-13:10 | 498622.67 | 31-OCT-24:00 | 25.59 | 18.90 | 15.31 |
November | 0.528484E+11 | 720.00 | 49248.27 | 01-NOV-10:50 | 529487.65 | 03-NOV-16:00 | 27.81 | 18.45 | 15.31 |
December | 0.426063E+11 | 744.00 | 49248.27 | 05-DEC-12:00 | 665192.42 | 06-DEC-16:10 | 30.28 | 18.35 | 15.31 |
Annual Sum or Average | 0.798142E+12 | 8760.00 | 28.50 | 20.43 | 15.31 | ||||
Minimum of Months | 0.853760E+10 | 672.00 | 7436.44 | 203429.85 | 21.70 | 18.33 | 15.31 | ||
Maximum of Months | 0.129415E+12 | 744.00 | 49248.27 | 759557.43 | 39.16 | 26.48 | 15.31 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 219537.27 | 17-JAN-07:00 | 21.02 | 21.02 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 458702.71 | 27-FEB-15:30 | 21.00 | 20.98 | 0.98 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 219587.20 | 16-MAR-13:00 | 20.95 | 20.94 | 0.84 |
April | 29053086.52 | 41.51 | 880.38 | 06-APR-15:40 | 883898.27 | 06-APR-16:00 | 21.13 | 21.00 | 5.82 |
May | 0.195868E+09 | 128.43 | 2092.39 | 19-MAY-17:50 | 1135948.74 | 19-MAY-15:30 | 21.54 | 21.16 | 12.13 |
June | 0.213470E+10 | 297.13 | 16290.83 | 06-JUN-14:40 | 1152126.20 | 30-JUN-14:40 | 22.21 | 21.17 | 26.05 |
July | 0.417225E+10 | 419.81 | 16290.83 | 13-JUL-13:10 | 1152052.90 | 24-JUL-14:30 | 22.75 | 21.16 | 35.04 |
August | 0.175826E+10 | 365.68 | 16290.83 | 05-AUG-11:40 | 1149917.89 | 24-AUG-15:00 | 22.51 | 21.08 | 31.99 |
September | 0.140373E+10 | 221.91 | 16290.83 | 02-SEP-10:50 | 1273486.46 | 07-SEP-15:00 | 21.89 | 21.15 | 20.07 |
October | 64002721.12 | 67.48 | 944.18 | 18-OCT-16:20 | 997413.79 | 18-OCT-12:10 | 21.22 | 21.02 | 7.43 |
November | 452312.65 | 5.17 | 68.64 | 17-NOV-17:00 | 231704.75 | 17-NOV-17:00 | 20.99 | 20.96 | 1.64 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 219518.39 | 20-DEC-07:00 | 21.00 | 20.99 | 0.32 |
Annual Sum or Average | 0.975831E+10 | 1547.12 | 21.52 | 21.05 | 11.94 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 219518.39 | 20.95 | 20.94 | 0.12 | ||
Maximum of Months | 0.417225E+10 | 419.81 | 16290.83 | 1273486.46 | 22.75 | 21.17 | 35.04 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.02 | 21.02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.00 | 21.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.95 | 20.95 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.13 | 21.13 | 0.00 |
May | 27517676.95 | 4.83 | 1970.97 | 19-MAY-12:00 | 1135948.74 | 19-MAY-15:30 | 21.54 | 21.51 | 0.36 |
June | 0.111044E+10 | 51.83 | 16290.83 | 06-JUN-14:40 | 1152126.20 | 30-JUN-14:40 | 22.21 | 21.92 | 3.98 |
July | 0.235124E+10 | 106.58 | 16290.83 | 13-JUL-13:10 | 1152052.90 | 24-JUL-14:30 | 22.75 | 22.15 | 7.91 |
August | 0.903030E+09 | 91.83 | 16290.83 | 05-AUG-13:00 | 1149917.89 | 24-AUG-15:00 | 22.51 | 21.99 | 6.82 |
September | 0.569917E+09 | 25.33 | 16290.83 | 02-SEP-10:50 | 1273486.46 | 07-SEP-15:00 | 21.89 | 21.74 | 1.94 |
October | 2001419.40 | 0.67 | 892.61 | 18-OCT-15:10 | 969131.76 | 18-OCT-14:50 | 21.22 | 21.22 | 0.05 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.99 | 20.99 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.00 | 21.00 | 0.00 |
Annual Sum or Average | 0.496414E+10 | 281.08 | 21.52 | 21.39 | 1.77 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 | 20.95 | 0.00 | ||
Maximum of Months | 0.235124E+10 | 106.58 | 16290.83 | 1273486.46 | 22.75 | 22.15 | 7.91 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.908041E+12 | 0.00 | 613.56 | 1926652.15 | 09-JAN-07:10 | 0.00 | 32.45 | 72.17 | 1.83 | 0.00 | 0.10 | 0.57 | 09-JAN-07:10 |
February | 0.471065E+12 | 0.00 | 456.86 | 1989661.92 | 07-FEB-06:01 | 0.00 | 28.30 | 63.48 | 0.97 | 0.00 | 0.06 | 0.59 | 07-FEB-06:01 |
March | 0.264416E+12 | 0.00 | 448.88 | 1928193.29 | 06-MAR-05:01 | 0.00 | 25.32 | 58.19 | 0.47 | 0.00 | 0.03 | 0.57 | 06-MAR-05:01 |
April | 0.617474E+11 | 0.00 | 249.57 | 1360847.79 | 29-APR-05:01 | 0.00 | 22.52 | 42.28 | 0.10 | 0.00 | 0.01 | 0.40 | 29-APR-05:01 |
May | 0.434825E+11 | 0.00 | 170.12 | 1555198.13 | 22-MAY-04:01 | 0.00 | 22.67 | 35.57 | 0.07 | 0.00 | 0.00 | 0.46 | 22-MAY-04:01 |
June | 0.157475E+10 | 0.00 | 35.42 | 183589.52 | 17-JUN-05:03 | 0.00 | 21.18 | 24.05 | 0.00 | 0.00 | 0.00 | 0.05 | 17-JUN-05:03 |
July | 20912399.13 | 0.00 | 4.54 | 3713.59 | 08-JUL-05:05 | 0.00 | 20.87 | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 | 08-JUL-05:05 |
August | 0.562214E+09 | 0.00 | 15.13 | 173688.76 | 18-AUG-05:02 | 0.00 | 20.84 | 22.03 | 0.00 | 0.00 | 0.00 | 0.05 | 18-AUG-05:02 |
September | 0.119485E+11 | 0.00 | 118.81 | 867742.81 | 19-SEP-05:03 | 0.00 | 20.91 | 30.49 | 0.02 | 0.00 | 0.00 | 0.26 | 19-SEP-05:03 |
October | 0.508915E+11 | 0.00 | 266.33 | 1598765.11 | 10-OCT-04:01 | 0.00 | 21.93 | 42.42 | 0.08 | 0.00 | 0.01 | 0.47 | 10-OCT-04:01 |
November | 0.229836E+12 | 0.00 | 437.44 | 1698994.42 | 27-NOV-06:01 | 0.00 | 25.08 | 58.26 | 0.42 | 0.00 | 0.03 | 0.50 | 27-NOV-06:01 |
December | 0.578719E+12 | 0.00 | 566.08 | 2009651.10 | 26-DEC-05:11 | 0.00 | 29.60 | 68.59 | 1.08 | 0.00 | 0.06 | 0.59 | 26-DEC-05:11 |
Annual Sum or Average | 0.262230E+13 | 0.00 | 3382.72 | 0.00 | 24.29 | 44.81 | 0.42 | 0.00 | 0.02 | ||||
Minimum of Months | 20912399.13 | 0.00 | 4.54 | 3713.59 | 0.00 | 20.84 | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.908041E+12 | 0.00 | 613.56 | 2009651.10 | 0.00 | 32.45 | 72.17 | 1.83 | 0.00 | 0.10 | 0.59 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 21.70 | 21.70 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 24.70 | 24.70 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.62 | 27.62 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 31.45 | 31.45 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 23.16 | 23.16 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 29.08 | 29.08 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 36.34 | 36.34 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 39.16 | 39.16 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 24.70 | 24.70 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 25.59 | 25.59 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.81 | 27.81 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 30.28 | 30.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 28.50 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 | 21.70 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.16 | 39.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.631469E+09 | 0.00 | 11.70 | 0.631469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42298.79 | 27-FEB-15:30 | 42298.79 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 34245100.02 | 0.00 | 4.24 | 34245100.02 | 0.00 | 0.00 | 0.00 | 0.00 | 6873.66 | 14-MAR-13:30 | 6873.66 | 14-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.661475E+10 | 0.00 | 77.94 | 0.661475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84147.20 | 07-APR-14:00 | 84147.20 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.181362E+11 | 0.00 | 167.52 | 0.181362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110739.54 | 19-MAY-15:20 | 110739.54 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.599180E+11 | 0.00 | 348.79 | 0.598665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127546.54 | 29-JUN-14:50 | 127546.54 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.102793E+12 | 0.00 | 479.42 | 0.102626E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 153583.55 | 17-JUL-15:20 | 153583.55 | 17-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.950781E+11 | 0.00 | 470.22 | 0.950781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153907.64 | 07-AUG-15:20 | 153907.64 | 07-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.388729E+11 | 0.00 | 261.29 | 0.376260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 195729.35 | 07-SEP-15:00 | 125610.52 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.105474E+11 | 0.00 | 109.72 | 0.105474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102919.20 | 18-OCT-15:50 | 102919.20 | 18-OCT-15:50 | 0.00 | 0.00 | 0.00 |
November | 0.560038E+09 | 0.00 | 22.93 | 0.560038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18833.65 | 17-NOV-17:00 | 18833.65 | 17-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.333186E+12 | 0.00 | 1953.76 | 0.331721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.102793E+12 | 0.00 | 479.42 | 0.102626E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 195729.35 | 153907.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 22025.30 | 0.00 | 12.40 | 22025.30 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 | 02-JAN-05:43 | 3.82 | 02-JAN-05:43 | 0.00 | 0.00 | 0.00 |
February | 0.449454E+10 | 0.00 | 47.53 | 0.449454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 298207.97 | 27-FEB-13:50 | 298207.97 | 27-FEB-13:50 | 0.00 | 0.00 | 0.00 |
March | 95868854.75 | 0.00 | 77.28 | 95868854.75 | 0.00 | 0.00 | 0.00 | 0.00 | 21490.08 | 14-MAR-13:40 | 21490.08 | 14-MAR-13:40 | 0.00 | 0.00 | 0.00 |
April | 0.465868E+11 | 0.00 | 134.08 | 0.465868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 634436.50 | 06-APR-16:00 | 634436.50 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.153363E+12 | 0.00 | 199.87 | 0.153363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1047502.37 | 19-MAY-15:30 | 1047502.37 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.507393E+12 | 0.00 | 329.45 | 0.506952E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1202902.78 | 29-JUN-14:50 | 1202902.78 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.851486E+12 | 0.00 | 417.66 | 0.850458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1392153.47 | 17-JUL-15:30 | 1392153.47 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.737744E+12 | 0.00 | 389.04 | 0.737744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1322502.29 | 10-AUG-15:40 | 1322502.29 | 10-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.339029E+12 | 0.00 | 272.26 | 0.327943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1792594.27 | 07-SEP-15:00 | 1142540.98 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.830409E+11 | 0.00 | 144.29 | 0.830409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 851650.27 | 18-OCT-15:00 | 851650.27 | 18-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.402796E+10 | 0.00 | 69.04 | 0.402796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 131398.09 | 17-NOV-17:00 | 131398.09 | 17-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 85216.38 | 0.00 | 38.21 | 85216.38 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 | 21-DEC-15:00 | 1.39 | 21-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272726E+13 | 0.00 | 2131.12 | 0.271471E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 22025.30 | 0.00 | 12.40 | 22025.30 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 | 1.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.851486E+12 | 0.00 | 417.66 | 0.850458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1792594.27 | 1392153.47 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 59233.01 | 0.00 | 2.43 | 59233.01 | 0.00 | 0.00 | 0.00 | 0.00 | 471.39 | 17-JAN-04:52 | 471.39 | 17-JAN-04:52 | 0.00 | 0.00 | 0.00 |
February | 0.319283E+09 | 0.00 | 12.65 | 0.319283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21923.36 | 26-FEB-14:21 | 21923.36 | 26-FEB-14:21 | 0.00 | 0.00 | 0.00 |
March | 2115474.09 | 0.00 | 1.58 | 2115474.09 | 0.00 | 0.00 | 0.00 | 0.00 | 1667.83 | 04-MAR-05:41 | 1667.83 | 04-MAR-05:41 | 0.00 | 0.00 | 0.00 |
April | 0.433904E+10 | 0.00 | 65.15 | 0.433904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64046.14 | 06-APR-16:00 | 64046.14 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.159500E+11 | 0.00 | 153.57 | 0.159500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125734.12 | 19-MAY-15:30 | 125734.12 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.557763E+11 | 0.00 | 318.70 | 0.557211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143214.45 | 29-JUN-15:00 | 143214.45 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.941281E+11 | 0.00 | 416.96 | 0.940337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169657.20 | 17-JUL-15:30 | 169657.20 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.794769E+11 | 0.00 | 379.64 | 0.794769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 157975.35 | 07-AUG-15:40 | 157975.35 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.347387E+11 | 0.00 | 241.90 | 0.336262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 183238.71 | 07-SEP-15:20 | 131239.44 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.713518E+10 | 0.00 | 93.46 | 0.713518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88699.86 | 18-OCT-15:00 | 88699.86 | 18-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.301718E+09 | 0.00 | 16.05 | 0.301718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10754.42 | 17-NOV-17:00 | 10754.42 | 17-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 1767.86 | 0.00 | 1.52 | 1767.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 01-DEC-06:25 | 0.37 | 01-DEC-06:25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.292167E+12 | 0.00 | 1703.61 | 0.290905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1767.86 | 0.00 | 1.52 | 1767.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 0.37 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.941281E+11 | 0.00 | 416.96 | 0.940337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 183238.71 | 169657.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 483334.78 | 0.00 | 0.52 | 483334.78 | 0.00 | 0.00 | 0.00 | 0.00 | 5566.60 | 24-JAN-05:01 | 5566.60 | 24-JAN-05:01 | 0.00 | 0.00 | 0.00 |
February | 0.261761E+09 | 0.00 | 5.00 | 0.261761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23743.59 | 27-FEB-15:00 | 23743.59 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 10369.74 | 0.00 | 0.17 | 10369.74 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 | 06-MAR-20:00 | 17.28 | 06-MAR-20:00 | 0.00 | 0.00 | 0.00 |
April | 0.231208E+10 | 0.00 | 37.08 | 0.231208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49353.32 | 07-APR-14:00 | 49353.32 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.883342E+10 | 0.00 | 104.91 | 0.883342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70670.19 | 29-MAY-14:30 | 70670.19 | 29-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.311339E+11 | 0.00 | 231.49 | 0.311222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67672.65 | 26-JUN-11:00 | 67672.65 | 26-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.530670E+11 | 0.00 | 322.92 | 0.530396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109277.90 | 19-JUL-03:02 | 84644.13 | 25-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.493011E+11 | 0.00 | 317.32 | 0.493011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107536.15 | 06-AUG-17:27 | 107536.15 | 06-AUG-17:27 | 0.00 | 0.00 | 0.00 |
September | 0.203694E+11 | 0.00 | 180.99 | 0.200026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123411.10 | 04-SEP-17:21 | 123411.10 | 04-SEP-17:21 | 0.00 | 0.00 | 0.00 |
October | 0.573405E+10 | 0.00 | 60.39 | 0.573405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59639.08 | 18-OCT-14:00 | 59639.08 | 18-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 68497280.37 | 0.00 | 4.31 | 68497280.37 | 0.00 | 0.00 | 0.00 | 0.00 | 25354.47 | 17-NOV-06:03 | 25354.47 | 17-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 60297.63 | 0.00 | 0.33 | 60297.63 | 0.00 | 0.00 | 0.00 | 0.00 | 59.02 | 27-DEC-17:00 | 59.02 | 27-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171082E+12 | 0.00 | 1265.44 | 0.170676E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10369.74 | 0.00 | 0.17 | 10369.74 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 | 17.28 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.530670E+11 | 0.00 | 322.92 | 0.530396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123411.10 | 123411.10 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.361894E+12 | 0.918927E+11 | 744.00 | 0.328237E+12 | 0.336571E+11 | 0.00 | 0.36 | 03-JAN-22:02 | 0.30 | 09-JAN-07:02 | 142941.73 | 18-JAN-22:01 | 129770.01 | 02-JAN-22:03 | 13973.15 | 18-JAN-22:01 | 35976.17 | 03-JAN-22:02 | 0.00 |
February | 0.575724E+12 | 0.138529E+12 | 672.00 | 0.521962E+12 | 0.537618E+11 | 0.00 | 0.59 | 27-FEB-16:00 | 0.54 | 01-FEB-07:07 | 245398.86 | 27-FEB-22:03 | 222161.37 | 28-FEB-22:03 | 23908.55 | 05-FEB-00:52 | 66529.05 | 27-FEB-16:00 | 0.00 |
March | 0.910631E+12 | 0.209937E+12 | 744.00 | 0.827777E+12 | 0.828536E+11 | 0.00 | 0.98 | 31-MAR-24:00 | 0.76 | 06-MAR-07:07 | 440819.95 | 31-MAR-24:00 | 400344.89 | 31-MAR-24:00 | 40475.07 | 31-MAR-24:00 | 97766.24 | 31-MAR-24:00 | 0.00 |
April | 0.114518E+13 | 0.261672E+12 | 720.00 | 0.104327E+13 | 0.101913E+12 | 0.00 | 1.00 | 06-APR-09:50 | 0.39 | 30-APR-24:00 | 449692.72 | 24-APR-21:02 | 407738.89 | 06-APR-22:55 | 44489.66 | 21-APR-16:00 | 132528.56 | 07-APR-14:00 | 0.00 |
May | 0.375766E+12 | 0.982215E+11 | 744.00 | 0.342794E+12 | 0.329723E+11 | 0.00 | 0.58 | 31-MAY-23:40 | 0.33 | 08-MAY-06:10 | 238067.17 | 31-MAY-24:00 | 217604.10 | 31-MAY-24:00 | 20463.07 | 31-MAY-24:00 | 59624.41 | 31-MAY-23:20 | 0.00 |
June | 0.620352E+12 | 0.169569E+12 | 720.00 | 0.573444E+12 | 0.469081E+11 | 0.00 | 0.80 | 30-JUN-23:12 | 0.57 | 01-JUN-06:10 | 330249.59 | 30-JUN-23:02 | 309564.52 | 30-JUN-24:00 | 23537.90 | 01-JUN-19:00 | 95949.24 | 30-JUN-23:12 | 0.00 |
July | 0.894884E+12 | 0.267843E+12 | 744.00 | 0.842211E+12 | 0.526731E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.78 | 08-JUL-06:10 | 427103.05 | 31-JUL-24:00 | 400837.94 | 31-JUL-23:57 | 34344.47 | 05-JUL-09:00 | 150134.95 | 17-JUL-16:00 | 0.00 |
August | 0.116120E+13 | 0.327110E+12 | 744.00 | 0.108112E+13 | 0.800772E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.41 | 31-AUG-24:00 | 456734.48 | 04-AUG-00:25 | 412410.78 | 12-AUG-05:00 | 47140.61 | 01-AUG-21:00 | 167883.90 | 06-AUG-16:00 | 0.00 |
September | 0.366935E+12 | 0.100677E+12 | 720.00 | 0.336783E+12 | 0.301515E+11 | 0.00 | 0.57 | 30-SEP-24:00 | 0.34 | 18-SEP-07:00 | 238748.02 | 30-SEP-24:00 | 217328.36 | 30-SEP-24:00 | 21419.66 | 30-SEP-24:00 | 59175.14 | 02-SEP-17:00 | 0.00 |
October | 0.649195E+12 | 0.158766E+12 | 744.00 | 0.590735E+12 | 0.584605E+11 | 0.00 | 0.78 | 31-OCT-24:00 | 0.56 | 10-OCT-06:10 | 340945.21 | 31-OCT-24:00 | 309906.43 | 31-OCT-24:00 | 31038.78 | 31-OCT-24:00 | 79111.49 | 18-OCT-15:00 | 0.00 |
November | 0.889805E+12 | 0.205448E+12 | 720.00 | 0.806754E+12 | 0.830507E+11 | 0.00 | 0.81 | 17-NOV-17:00 | 0.77 | 27-NOV-07:10 | 349085.01 | 06-NOV-22:03 | 315596.37 | 06-NOV-22:03 | 34462.23 | 03-NOV-08:00 | 89865.99 | 17-NOV-17:00 | 0.00 |
December | 0.118267E+13 | 0.263000E+12 | 744.00 | 0.107452E+13 | 0.108149E+12 | 0.00 | 0.99 | 07-DEC-24:00 | 0.96 | 30-DEC-07:10 | 448631.08 | 07-DEC-24:00 | 407061.91 | 07-DEC-22:03 | 43514.42 | 16-DEC-17:00 | 105040.09 | 10-DEC-02:00 | 0.00 |
Annual Sum or Average | 0.913423E+13 | 0.229267E+13 | 8760.00 | 0.836961E+13 | 0.764628E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.361894E+12 | 0.918927E+11 | 672.00 | 0.328237E+12 | 0.301515E+11 | 0.00 | 0.36 | 0.30 | 142941.73 | 129770.01 | 13973.15 | 35976.17 | 0.00 | ||||||
Maximum of Months | 0.118267E+13 | 0.327110E+12 | 744.00 | 0.108112E+13 | 0.108149E+12 | 0.00 | 1.00 | 0.96 | 456734.48 | 412410.78 | 47140.61 | 167883.90 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.292943E+10 | 0.842232E+09 | 731.18 | 0.292912E+10 | 319508.34 | 0.00 | 0.27 | 13-JAN-16:20 | 0.00 | 07-JAN-23:22 | 2213.04 | 13-JAN-16:20 | 2213.04 | 13-JAN-16:20 | 12.48 | 02-JAN-07:10 | 579.60 | 13-JAN-16:20 | 0.00 |
February | 0.821852E+10 | 0.216357E+10 | 672.00 | 0.821852E+10 | -0.0 | 0.00 | 0.58 | 26-FEB-17:03 | 0.27 | 01-FEB-07:03 | 4835.78 | 26-FEB-17:14 | 4835.78 | 26-FEB-17:14 | 0.00 | 17-FEB-06:50 | 1273.03 | 27-FEB-16:00 | 0.00 |
March | 0.149235E+11 | 0.369842E+10 | 744.00 | 0.149235E+11 | 0.00 | 0.00 | 0.81 | 31-MAR-24:00 | 0.52 | 06-MAR-07:03 | 7458.73 | 31-MAR-24:00 | 7458.73 | 31-MAR-24:00 | 0.00 | 14-MAR-16:20 | 1758.08 | 31-MAR-24:00 | 0.00 |
April | 0.200314E+11 | 0.483299E+10 | 720.00 | 0.200239E+11 | 7423479.97 | 0.00 | 1.00 | 16-APR-17:11 | 0.30 | 30-APR-24:00 | 8875.20 | 22-APR-18:10 | 8875.20 | 22-APR-18:10 | 128.44 | 17-APR-16:10 | 2708.89 | 07-APR-14:00 | 0.00 |
May | 0.562191E+10 | 0.153555E+10 | 744.00 | 0.560040E+10 | 21504642.77 | 0.00 | 0.48 | 31-MAY-24:00 | 0.14 | 08-MAY-06:10 | 4145.25 | 31-MAY-24:00 | 4145.25 | 31-MAY-24:00 | 137.92 | 30-MAY-09:10 | 1075.41 | 31-MAY-23:30 | 0.00 |
June | 0.109113E+11 | 0.304603E+10 | 720.00 | 0.108315E+11 | 79834224.45 | 0.00 | 0.68 | 30-JUN-23:12 | 0.39 | 17-JUN-06:40 | 5989.05 | 30-JUN-23:12 | 5989.05 | 30-JUN-23:12 | 305.90 | 06-JUN-16:50 | 1890.32 | 29-JUN-15:00 | 0.00 |
July | 0.165864E+11 | 0.504171E+10 | 744.00 | 0.164977E+11 | 88748177.02 | 0.00 | 0.88 | 16-JUL-18:55 | 0.62 | 08-JUL-06:20 | 7894.49 | 31-JUL-23:40 | 7894.49 | 31-JUL-23:40 | 313.64 | 03-JUL-17:00 | 3075.87 | 17-JUL-16:00 | 0.00 |
August | 0.215881E+11 | 0.635677E+10 | 744.00 | 0.215254E+11 | 62711067.08 | 0.00 | 1.00 | 03-AUG-18:20 | 0.31 | 31-AUG-24:00 | 8876.31 | 05-AUG-19:57 | 8876.31 | 05-AUG-19:57 | 369.31 | 22-AUG-16:00 | 3631.15 | 06-AUG-16:00 | 0.00 |
September | 0.571231E+10 | 0.161785E+10 | 720.00 | 0.563016E+10 | 82144932.12 | 0.00 | 0.45 | 30-SEP-24:00 | 0.16 | 19-SEP-07:00 | 3952.88 | 30-SEP-24:00 | 3952.88 | 30-SEP-24:00 | 343.94 | 07-SEP-15:30 | 1354.93 | 04-SEP-17:31 | 0.00 |
October | 0.105331E+11 | 0.267977E+10 | 744.00 | 0.105225E+11 | 10577683.61 | 0.00 | 0.64 | 31-OCT-24:00 | 0.36 | 10-OCT-06:10 | 5595.08 | 31-OCT-24:00 | 5595.08 | 31-OCT-24:00 | 111.27 | 25-OCT-11:00 | 1568.18 | 15-OCT-16:43 | 0.00 |
November | 0.146199E+11 | 0.359111E+10 | 720.00 | 0.146182E+11 | 1644586.47 | 0.00 | 0.72 | 13-NOV-16:20 | 0.53 | 27-NOV-07:10 | 6539.94 | 03-NOV-16:00 | 6485.12 | 03-NOV-16:00 | 84.08 | 08-NOV-15:20 | 1662.11 | 17-NOV-16:50 | 0.00 |
December | 0.194867E+11 | 0.472659E+10 | 744.00 | 0.194865E+11 | 197339.12 | 0.00 | 0.90 | 10-DEC-16:05 | 0.73 | 29-DEC-07:03 | 8258.67 | 10-DEC-16:10 | 8258.67 | 10-DEC-16:10 | 47.84 | 19-DEC-17:05 | 1981.65 | 10-DEC-02:00 | 0.00 |
Annual Sum or Average | 0.151163E+12 | 0.401326E+11 | 8747.18 | 0.150808E+12 | 0.355106E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.292943E+10 | 0.842232E+09 | 672.00 | 0.292912E+10 | -0.0 | 0.00 | 0.27 | 0.00 | 2213.04 | 2213.04 | 0.00 | 579.60 | 0.00 | ||||||
Maximum of Months | 0.215881E+11 | 0.635677E+10 | 744.00 | 0.215254E+11 | 88748177.02 | 0.00 | 1.00 | 0.73 | 8876.31 | 8876.31 | 369.31 | 3631.15 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.857650E+10 | 0.267915E+10 | 485.78 | 0.857355E+10 | 2950457.18 | 0.00 | 0.23 | 13-JAN-16:30 | 0.00 | 01-JAN-06:13 | 18216.38 | 13-JAN-16:30 | 18216.38 | 13-JAN-16:30 | 113.24 | 01-JAN-15:45 | 4827.52 | 13-JAN-16:30 | 0.00 |
February | 0.591237E+11 | 0.159221E+11 | 672.00 | 0.591237E+11 | -0.0 | 0.00 | 0.51 | 24-FEB-17:00 | 0.12 | 06-FEB-04:11 | 42953.71 | 28-FEB-17:00 | 42953.71 | 28-FEB-17:00 | 0.00 | 20-FEB-11:17 | 11558.16 | 27-FEB-16:00 | 0.00 |
March | 0.124326E+12 | 0.312603E+11 | 744.00 | 0.124326E+12 | 0.00 | 0.00 | 0.75 | 31-MAR-23:30 | 0.37 | 06-MAR-07:03 | 65101.25 | 31-MAR-23:30 | 65101.25 | 31-MAR-23:30 | 0.00 | 10-MAR-23:20 | 15535.33 | 31-MAR-23:30 | 0.00 |
April | 0.179642E+12 | 0.437564E+11 | 720.00 | 0.179566E+12 | 75967418.34 | 0.00 | 0.99 | 16-APR-17:51 | 0.14 | 30-APR-24:00 | 82573.71 | 25-APR-18:00 | 82573.71 | 25-APR-18:00 | 1279.10 | 17-APR-16:10 | 25589.72 | 07-APR-14:00 | 0.00 |
May | 0.453654E+11 | 0.125784E+11 | 744.00 | 0.451545E+11 | 0.210900E+09 | 0.00 | 0.47 | 31-MAY-24:00 | 0.02 | 08-MAY-06:10 | 39166.80 | 31-MAY-24:00 | 39166.80 | 31-MAY-24:00 | 1321.41 | 30-MAY-09:10 | 10187.82 | 31-MAY-23:30 | 0.00 |
June | 0.100389E+12 | 0.281921E+11 | 720.00 | 0.995931E+11 | 0.795620E+09 | 0.00 | 0.69 | 30-JUN-23:12 | 0.34 | 17-JUN-06:10 | 58527.79 | 30-JUN-23:55 | 58527.79 | 30-JUN-23:55 | 2997.84 | 06-JUN-16:50 | 17994.60 | 29-JUN-15:00 | 0.00 |
July | 0.156653E+12 | 0.477361E+11 | 744.00 | 0.155766E+12 | 0.887617E+09 | 0.00 | 0.89 | 31-JUL-23:12 | 0.58 | 08-JUL-06:30 | 76788.16 | 31-JUL-23:53 | 76788.16 | 31-JUL-23:53 | 3079.89 | 03-JUL-17:00 | 29290.49 | 17-JUL-16:00 | 0.00 |
August | 0.202839E+12 | 0.599522E+11 | 744.00 | 0.202210E+12 | 0.628492E+09 | 0.00 | 1.00 | 03-AUG-18:30 | 0.27 | 31-AUG-24:00 | 84672.67 | 03-AUG-18:50 | 84672.67 | 03-AUG-18:50 | 3625.50 | 22-AUG-16:00 | 34760.66 | 06-AUG-16:00 | 0.00 |
September | 0.480861E+11 | 0.138244E+11 | 720.00 | 0.472823E+11 | 0.803724E+09 | 0.00 | 0.42 | 04-SEP-17:42 | 0.10 | 19-SEP-06:10 | 34809.25 | 30-SEP-23:40 | 34809.25 | 30-SEP-23:40 | 3442.26 | 07-SEP-15:30 | 12669.00 | 04-SEP-17:31 | 0.00 |
October | 0.877275E+11 | 0.226340E+11 | 744.00 | 0.876218E+11 | 0.105715E+09 | 0.00 | 0.58 | 31-OCT-24:00 | 0.25 | 10-OCT-06:10 | 47518.81 | 31-OCT-24:00 | 47518.81 | 31-OCT-24:00 | 1088.71 | 25-OCT-11:00 | 14603.24 | 18-OCT-16:00 | 0.00 |
November | 0.120793E+12 | 0.301485E+11 | 720.00 | 0.120776E+12 | 17115694.31 | 0.00 | 0.68 | 03-NOV-16:00 | 0.37 | 27-NOV-07:10 | 60246.14 | 03-NOV-16:00 | 59699.37 | 03-NOV-16:00 | 836.52 | 08-NOV-15:20 | 15304.01 | 17-NOV-17:00 | 0.00 |
December | 0.158891E+12 | 0.393130E+11 | 744.00 | 0.158888E+12 | 2820246.17 | 0.00 | 0.83 | 12-DEC-16:00 | 0.56 | 31-DEC-23:55 | 74945.28 | 06-DEC-16:10 | 74671.23 | 06-DEC-16:10 | 515.32 | 19-DEC-17:05 | 17094.54 | 06-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.129241E+13 | 0.347997E+12 | 8501.78 | 0.128888E+13 | 0.353092E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.857650E+10 | 0.267915E+10 | 485.78 | 0.857355E+10 | -0.0 | 0.00 | 0.23 | 0.00 | 18216.38 | 18216.38 | 0.00 | 4827.52 | 0.00 | ||||||
Maximum of Months | 0.202839E+12 | 0.599522E+11 | 744.00 | 0.202210E+12 | 0.887617E+09 | 0.00 | 1.00 | 0.58 | 84672.67 | 84672.67 | 3625.50 | 34760.66 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.243203E+09 | 78608724.00 | 174.35 | 0.243203E+09 | 0.00 | 0.00 | 0.22 | 13-JAN-16:30 | 0.00 | 01-JAN-00:05 | 1723.69 | 13-JAN-16:30 | 1723.69 | 13-JAN-16:30 | 0.00 | 24-JAN-15:20 | 459.70 | 13-JAN-16:30 | 0.00 |
February | 0.427161E+10 | 0.117389E+10 | 650.05 | 0.427161E+10 | -0.0 | 0.00 | 0.49 | 28-FEB-17:00 | 0.00 | 04-FEB-02:42 | 4244.96 | 28-FEB-17:00 | 4244.96 | 28-FEB-17:00 | 0.00 | 21-FEB-03:00 | 1132.77 | 27-FEB-16:00 | 0.00 |
March | 0.107834E+11 | 0.274816E+10 | 744.00 | 0.107834E+11 | 0.00 | 0.00 | 0.71 | 28-MAR-17:50 | 0.19 | 06-MAR-04:03 | 6162.30 | 28-MAR-17:50 | 6162.30 | 28-MAR-17:50 | 0.00 | 02-MAR-06:20 | 1494.64 | 28-MAR-17:50 | 0.00 |
April | 0.167733E+11 | 0.413232E+10 | 719.00 | 0.167658E+11 | 7470022.72 | 0.00 | 0.96 | 16-APR-17:51 | 0.00 | 30-APR-23:05 | 8322.34 | 25-APR-18:00 | 8322.34 | 25-APR-18:00 | 126.71 | 17-APR-16:10 | 2567.55 | 07-APR-14:00 | 0.00 |
May | 0.383926E+10 | 0.107777E+10 | 691.18 | 0.381852E+10 | 20739497.80 | 0.00 | 0.46 | 31-MAY-23:40 | 0.00 | 01-MAY-00:05 | 3844.10 | 31-MAY-24:00 | 3844.10 | 31-MAY-24:00 | 127.61 | 30-MAY-09:20 | 1005.28 | 31-MAY-23:20 | 0.00 |
June | 0.981859E+10 | 0.277704E+10 | 720.00 | 0.973923E+10 | 79363723.30 | 0.00 | 0.68 | 30-JUN-23:12 | 0.25 | 17-JUN-06:10 | 5863.59 | 30-JUN-23:55 | 5863.59 | 30-JUN-23:55 | 302.13 | 06-JUN-16:50 | 1840.37 | 29-JUN-15:00 | 0.00 |
July | 0.156086E+11 | 0.477948E+10 | 744.00 | 0.155200E+11 | 88595047.62 | 0.00 | 0.90 | 16-JUL-18:55 | 0.53 | 08-JUL-06:40 | 7643.11 | 31-JUL-23:53 | 7643.11 | 31-JUL-23:53 | 308.76 | 03-JUL-17:00 | 2996.88 | 17-JUL-16:00 | 0.00 |
August | 0.201452E+11 | 0.598609E+10 | 744.00 | 0.200825E+11 | 62694564.17 | 0.00 | 1.00 | 04-AUG-17:30 | 0.26 | 31-AUG-24:00 | 8604.14 | 05-AUG-19:53 | 8604.14 | 05-AUG-19:53 | 363.81 | 22-AUG-16:00 | 3538.92 | 06-AUG-16:00 | 0.00 |
September | 0.424334E+10 | 0.124454E+10 | 718.36 | 0.416419E+10 | 79154891.55 | 0.00 | 0.44 | 04-SEP-17:21 | 0.00 | 12-SEP-03:25 | 3367.31 | 04-SEP-17:32 | 3367.31 | 04-SEP-17:32 | 346.95 | 07-SEP-15:30 | 1365.28 | 04-SEP-17:21 | 0.00 |
October | 0.736129E+10 | 0.193234E+10 | 743.78 | 0.735096E+10 | 10334594.73 | 0.00 | 0.56 | 18-OCT-16:50 | 0.00 | 10-OCT-02:55 | 4584.13 | 18-OCT-16:50 | 4584.13 | 18-OCT-16:50 | 107.76 | 25-OCT-11:00 | 1471.31 | 18-OCT-16:00 | 0.00 |
November | 0.101784E+11 | 0.258401E+10 | 720.00 | 0.101767E+11 | 1666974.25 | 0.00 | 0.67 | 03-NOV-16:00 | 0.19 | 27-NOV-04:12 | 5951.50 | 03-NOV-16:00 | 5896.96 | 03-NOV-16:00 | 82.80 | 08-NOV-15:20 | 1506.88 | 17-NOV-16:50 | 0.00 |
December | 0.138504E+11 | 0.348254E+10 | 744.00 | 0.138502E+11 | 242074.50 | 0.00 | 0.80 | 06-DEC-16:10 | 0.40 | 31-DEC-23:55 | 7397.97 | 06-DEC-16:10 | 7372.79 | 06-DEC-16:10 | 48.49 | 19-DEC-17:05 | 1694.22 | 06-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.117117E+12 | 0.319968E+11 | 8112.72 | 0.116766E+12 | 0.350261E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.243203E+09 | 78608724.00 | 174.35 | 0.243203E+09 | -0.0 | 0.00 | 0.22 | 0.00 | 1723.69 | 1723.69 | 0.00 | 459.70 | 0.00 | ||||||
Maximum of Months | 0.201452E+11 | 0.598609E+10 | 744.00 | 0.200825E+11 | 88595047.62 | 0.00 | 1.00 | 0.53 | 8604.14 | 8604.14 | 363.81 | 3538.92 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.50 | 793.07 | 0.00 | 0.00 | 0.00 |
February | 127.65 | 0.00 | 127.65 | 15.59 | 597.73 | 0.00 | 0.00 | 0.00 |
March | 207.35 | 0.00 | 207.35 | 62.53 | 487.21 | 0.00 | 0.00 | 0.00 |
April | 236.43 | 1.38 | 235.05 | 115.41 | 350.04 | 0.00 | 0.00 | 0.00 |
May | 310.49 | 18.40 | 292.09 | 225.36 | 252.82 | 0.00 | 0.00 | 0.00 |
June | 361.54 | 41.56 | 319.99 | 366.57 | 158.44 | 0.00 | 0.00 | 0.00 |
July | 330.29 | 30.94 | 299.35 | 398.37 | 130.42 | 0.00 | 0.00 | 0.00 |
August | 264.66 | 7.09 | 257.57 | 288.14 | 150.85 | 0.00 | 0.00 | 0.00 |
September | 198.21 | 0.07 | 198.14 | 167.43 | 234.60 | 0.00 | 0.00 | 0.00 |
October | 144.59 | 0.00 | 144.59 | 58.40 | 360.06 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.55 | 521.78 | 0.00 | 0.00 | 0.00 |
December | 75.81 | 0.00 | 75.81 | 0.49 | 707.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.22 | 8.33 | 195.89 | 143.41 | 394.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 0.00 | 75.81 | 0.49 | 130.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.54 | 41.56 | 319.99 | 398.37 | 793.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.50 | 793.07 | 0.00 | 0.00 | 0.00 |
February | 127.64 | 0.00 | 127.64 | 15.59 | 597.73 | 0.00 | 0.00 | 0.00 |
March | 207.35 | 0.00 | 207.35 | 62.53 | 487.21 | 0.00 | 0.00 | 0.00 |
April | 236.42 | 1.38 | 235.04 | 115.41 | 350.04 | 0.00 | 0.00 | 0.00 |
May | 310.48 | 18.40 | 292.08 | 225.36 | 252.82 | 0.00 | 0.00 | 0.00 |
June | 361.54 | 41.56 | 319.98 | 366.56 | 158.44 | 0.00 | 0.00 | 0.00 |
July | 330.29 | 30.93 | 299.35 | 398.37 | 130.42 | 0.00 | 0.00 | 0.00 |
August | 264.66 | 7.09 | 257.57 | 288.14 | 150.85 | 0.00 | 0.00 | 0.00 |
September | 198.21 | 0.07 | 198.14 | 167.43 | 234.60 | 0.00 | 0.00 | 0.00 |
October | 144.58 | 0.00 | 144.58 | 58.40 | 360.06 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.55 | 521.78 | 0.00 | 0.00 | 0.00 |
December | 75.81 | 0.00 | 75.81 | 0.49 | 707.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.22 | 8.33 | 195.89 | 143.41 | 394.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 0.00 | 75.81 | 0.49 | 130.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.54 | 41.56 | 319.98 | 398.37 | 793.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.50 | 793.07 | 0.00 | 0.00 | 0.00 |
February | 127.64 | 0.00 | 127.64 | 15.59 | 597.73 | 0.00 | 0.00 | 0.00 |
March | 207.35 | 0.00 | 207.35 | 62.53 | 487.21 | 0.00 | 0.00 | 0.00 |
April | 236.43 | 1.38 | 235.05 | 115.41 | 350.04 | 0.00 | 0.00 | 0.00 |
May | 310.48 | 18.40 | 292.08 | 225.36 | 252.82 | 0.00 | 0.00 | 0.00 |
June | 361.54 | 41.56 | 319.98 | 366.57 | 158.44 | 0.00 | 0.00 | 0.00 |
July | 330.29 | 30.93 | 299.35 | 398.37 | 130.42 | 0.00 | 0.00 | 0.00 |
August | 264.66 | 7.09 | 257.57 | 288.14 | 150.85 | 0.00 | 0.00 | 0.00 |
September | 198.21 | 0.07 | 198.14 | 167.43 | 234.60 | 0.00 | 0.00 | 0.00 |
October | 144.58 | 0.00 | 144.58 | 58.40 | 360.06 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.55 | 521.78 | 0.00 | 0.00 | 0.00 |
December | 75.81 | 0.00 | 75.81 | 0.49 | 707.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.22 | 8.33 | 195.89 | 143.41 | 394.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 0.00 | 75.81 | 0.49 | 130.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.54 | 41.56 | 319.98 | 398.37 | 793.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.50 | 793.07 | 0.00 | 0.00 | 0.00 |
February | 127.64 | 0.00 | 127.64 | 15.59 | 597.73 | 0.00 | 0.00 | 0.00 |
March | 207.35 | 0.00 | 207.35 | 62.53 | 487.21 | 0.00 | 0.00 | 0.00 |
April | 236.42 | 1.38 | 235.04 | 115.41 | 350.04 | 0.00 | 0.00 | 0.00 |
May | 310.48 | 18.40 | 292.08 | 225.36 | 252.82 | 0.00 | 0.00 | 0.00 |
June | 361.54 | 41.56 | 319.98 | 366.56 | 158.44 | 0.00 | 0.00 | 0.00 |
July | 330.29 | 30.93 | 299.35 | 398.37 | 130.42 | 0.00 | 0.00 | 0.00 |
August | 264.66 | 7.09 | 257.57 | 288.14 | 150.85 | 0.00 | 0.00 | 0.00 |
September | 198.21 | 0.07 | 198.14 | 167.43 | 234.60 | 0.00 | 0.00 | 0.00 |
October | 144.58 | 0.00 | 144.58 | 58.40 | 360.06 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.55 | 521.78 | 0.00 | 0.00 | 0.00 |
December | 75.81 | 0.00 | 75.81 | 0.49 | 707.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.22 | 8.33 | 195.89 | 143.41 | 394.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 0.00 | 75.81 | 0.49 | 130.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.54 | 41.56 | 319.98 | 398.37 | 793.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.50 | 793.04 | 0.00 | 0.00 | 0.00 |
February | 127.64 | 0.00 | 127.64 | 15.59 | 597.71 | 0.00 | 0.00 | 0.00 |
March | 207.34 | 0.00 | 207.34 | 62.52 | 487.19 | 0.00 | 0.00 | 0.00 |
April | 236.41 | 1.38 | 235.04 | 115.40 | 350.02 | 0.00 | 0.00 | 0.00 |
May | 310.47 | 18.40 | 292.07 | 225.35 | 252.81 | 0.00 | 0.00 | 0.00 |
June | 361.52 | 41.55 | 319.97 | 366.55 | 158.43 | 0.00 | 0.00 | 0.00 |
July | 330.27 | 30.93 | 299.34 | 398.35 | 130.41 | 0.00 | 0.00 | 0.00 |
August | 264.65 | 7.09 | 257.56 | 288.13 | 150.85 | 0.00 | 0.00 | 0.00 |
September | 198.20 | 0.07 | 198.13 | 167.42 | 234.59 | 0.00 | 0.00 | 0.00 |
October | 144.58 | 0.00 | 144.58 | 58.39 | 360.05 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.55 | 521.76 | 0.00 | 0.00 | 0.00 |
December | 75.80 | 0.00 | 75.80 | 0.49 | 707.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.21 | 8.33 | 195.88 | 143.40 | 394.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.80 | 0.00 | 75.80 | 0.49 | 130.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.52 | 41.55 | 319.97 | 398.35 | 793.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 230.66 | 105.75 | 124.91 | 118.69 | 803.80 | 0.00 | 0.00 | 0.00 |
February | 360.77 | 179.11 | 181.66 | 264.04 | 600.52 | 0.00 | 0.00 | 0.00 |
March | 485.09 | 200.72 | 284.37 | 389.87 | 496.05 | 0.00 | 0.00 | 0.00 |
April | 618.92 | 306.73 | 312.19 | 595.09 | 356.61 | 0.00 | 0.00 | 0.00 |
May | 683.68 | 304.20 | 379.49 | 708.16 | 277.59 | 0.00 | 0.00 | 0.00 |
June | 884.94 | 455.39 | 429.55 | 1057.90 | 175.42 | 0.00 | 0.00 | 0.00 |
July | 928.77 | 525.06 | 403.71 | 1198.16 | 138.42 | 0.00 | 0.00 | 0.00 |
August | 807.14 | 449.71 | 357.43 | 1017.44 | 154.66 | 0.00 | 0.00 | 0.00 |
September | 570.97 | 294.73 | 276.24 | 651.46 | 239.63 | 0.00 | 0.00 | 0.00 |
October | 409.64 | 208.01 | 201.63 | 383.68 | 363.81 | 0.00 | 0.00 | 0.00 |
November | 259.62 | 121.21 | 138.41 | 174.00 | 512.16 | 0.00 | 0.00 | 0.00 |
December | 191.49 | 82.24 | 109.24 | 91.05 | 703.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 536.89 | 269.87 | 267.02 | 555.79 | 401.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 191.49 | 82.24 | 109.24 | 91.05 | 138.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.77 | 525.06 | 429.55 | 1198.16 | 803.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 230.66 | 105.75 | 124.91 | 118.69 | 803.80 | 0.00 | 0.00 | 0.00 |
February | 360.77 | 179.11 | 181.66 | 264.04 | 600.52 | 0.00 | 0.00 | 0.00 |
March | 485.09 | 200.72 | 284.37 | 389.87 | 496.05 | 0.00 | 0.00 | 0.00 |
April | 618.92 | 306.73 | 312.19 | 595.09 | 356.61 | 0.00 | 0.00 | 0.00 |
May | 683.68 | 304.20 | 379.49 | 708.16 | 277.59 | 0.00 | 0.00 | 0.00 |
June | 884.94 | 455.39 | 429.55 | 1057.90 | 175.42 | 0.00 | 0.00 | 0.00 |
July | 928.77 | 525.06 | 403.71 | 1198.16 | 138.42 | 0.00 | 0.00 | 0.00 |
August | 807.14 | 449.71 | 357.43 | 1017.44 | 154.66 | 0.00 | 0.00 | 0.00 |
September | 570.97 | 294.73 | 276.24 | 651.46 | 239.63 | 0.00 | 0.00 | 0.00 |
October | 409.64 | 208.01 | 201.63 | 383.68 | 363.81 | 0.00 | 0.00 | 0.00 |
November | 259.62 | 121.21 | 138.41 | 174.00 | 512.16 | 0.00 | 0.00 | 0.00 |
December | 191.49 | 82.24 | 109.24 | 91.05 | 703.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 536.89 | 269.87 | 267.02 | 555.79 | 401.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 191.49 | 82.24 | 109.24 | 91.05 | 138.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.77 | 525.06 | 429.55 | 1198.16 | 803.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 230.65 | 105.75 | 124.91 | 118.69 | 803.79 | 0.00 | 0.00 | 0.00 |
February | 360.76 | 179.11 | 181.65 | 264.03 | 600.51 | 0.00 | 0.00 | 0.00 |
March | 485.08 | 200.71 | 284.37 | 389.86 | 496.04 | 0.00 | 0.00 | 0.00 |
April | 618.91 | 306.73 | 312.18 | 595.08 | 356.61 | 0.00 | 0.00 | 0.00 |
May | 683.67 | 304.19 | 379.48 | 708.14 | 277.59 | 0.00 | 0.00 | 0.00 |
June | 884.92 | 455.38 | 429.54 | 1057.88 | 175.42 | 0.00 | 0.00 | 0.00 |
July | 928.75 | 525.05 | 403.70 | 1198.14 | 138.42 | 0.00 | 0.00 | 0.00 |
August | 807.13 | 449.71 | 357.42 | 1017.42 | 154.66 | 0.00 | 0.00 | 0.00 |
September | 570.96 | 294.73 | 276.23 | 651.45 | 239.63 | 0.00 | 0.00 | 0.00 |
October | 409.64 | 208.01 | 201.63 | 383.67 | 363.80 | 0.00 | 0.00 | 0.00 |
November | 259.62 | 121.21 | 138.41 | 173.99 | 512.16 | 0.00 | 0.00 | 0.00 |
December | 191.48 | 82.24 | 109.24 | 91.05 | 703.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 536.88 | 269.87 | 267.02 | 555.78 | 401.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 191.48 | 82.24 | 109.24 | 91.05 | 138.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.75 | 525.05 | 429.54 | 1198.14 | 803.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.24 | 455.13 | 182.11 | 591.53 | 665.66 | 0.00 | 0.00 | 0.00 |
February | 811.51 | 583.67 | 227.84 | 828.78 | 508.27 | 0.00 | 0.00 | 0.00 |
March | 725.39 | 407.34 | 318.04 | 738.23 | 456.65 | 0.00 | 0.00 | 0.00 |
April | 583.09 | 278.89 | 304.20 | 615.76 | 343.50 | 0.00 | 0.00 | 0.00 |
May | 518.06 | 172.06 | 346.00 | 559.33 | 266.06 | 0.00 | 0.00 | 0.00 |
June | 514.75 | 150.12 | 364.62 | 635.26 | 179.63 | 0.00 | 0.00 | 0.00 |
July | 554.95 | 204.99 | 349.95 | 763.69 | 141.06 | 0.00 | 0.00 | 0.00 |
August | 659.52 | 332.52 | 327.00 | 879.82 | 159.63 | 0.00 | 0.00 | 0.00 |
September | 731.48 | 448.20 | 283.28 | 905.82 | 232.31 | 0.00 | 0.00 | 0.00 |
October | 764.73 | 528.80 | 235.93 | 866.18 | 333.74 | 0.00 | 0.00 | 0.00 |
November | 697.20 | 505.03 | 192.18 | 717.12 | 434.32 | 0.00 | 0.00 | 0.00 |
December | 605.98 | 437.58 | 168.40 | 572.04 | 581.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.20 | 373.97 | 275.23 | 721.97 | 358.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.75 | 150.12 | 168.40 | 559.33 | 141.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.51 | 583.67 | 364.62 | 905.82 | 665.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.23 | 455.12 | 182.11 | 591.53 | 665.66 | 0.00 | 0.00 | 0.00 |
February | 811.51 | 583.66 | 227.84 | 828.78 | 508.27 | 0.00 | 0.00 | 0.00 |
March | 725.38 | 407.34 | 318.04 | 738.22 | 456.65 | 0.00 | 0.00 | 0.00 |
April | 583.09 | 278.89 | 304.19 | 615.76 | 343.50 | 0.00 | 0.00 | 0.00 |
May | 518.06 | 172.06 | 346.00 | 559.33 | 266.06 | 0.00 | 0.00 | 0.00 |
June | 514.74 | 150.12 | 364.62 | 635.25 | 179.63 | 0.00 | 0.00 | 0.00 |
July | 554.95 | 204.99 | 349.95 | 763.69 | 141.06 | 0.00 | 0.00 | 0.00 |
August | 659.51 | 332.51 | 327.00 | 879.81 | 159.63 | 0.00 | 0.00 | 0.00 |
September | 731.48 | 448.20 | 283.28 | 905.81 | 232.31 | 0.00 | 0.00 | 0.00 |
October | 764.72 | 528.79 | 235.93 | 866.17 | 333.74 | 0.00 | 0.00 | 0.00 |
November | 697.20 | 505.02 | 192.18 | 717.11 | 434.32 | 0.00 | 0.00 | 0.00 |
December | 605.97 | 437.57 | 168.40 | 572.03 | 581.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.20 | 373.97 | 275.23 | 721.97 | 358.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.74 | 150.12 | 168.40 | 559.33 | 141.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.51 | 583.66 | 364.62 | 905.81 | 665.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.24 | 455.13 | 182.11 | 591.53 | 665.66 | 0.00 | 0.00 | 0.00 |
February | 811.51 | 583.67 | 227.84 | 828.78 | 508.27 | 0.00 | 0.00 | 0.00 |
March | 725.39 | 407.34 | 318.04 | 738.23 | 456.65 | 0.00 | 0.00 | 0.00 |
April | 583.09 | 278.89 | 304.20 | 615.76 | 343.50 | 0.00 | 0.00 | 0.00 |
May | 518.06 | 172.06 | 346.00 | 559.33 | 266.06 | 0.00 | 0.00 | 0.00 |
June | 514.75 | 150.12 | 364.62 | 635.26 | 179.63 | 0.00 | 0.00 | 0.00 |
July | 554.95 | 204.99 | 349.95 | 763.69 | 141.06 | 0.00 | 0.00 | 0.00 |
August | 659.52 | 332.52 | 327.00 | 879.82 | 159.63 | 0.00 | 0.00 | 0.00 |
September | 731.48 | 448.20 | 283.28 | 905.82 | 232.31 | 0.00 | 0.00 | 0.00 |
October | 764.73 | 528.80 | 235.93 | 866.18 | 333.74 | 0.00 | 0.00 | 0.00 |
November | 697.20 | 505.03 | 192.18 | 717.12 | 434.32 | 0.00 | 0.00 | 0.00 |
December | 605.98 | 437.58 | 168.40 | 572.04 | 581.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.20 | 373.97 | 275.23 | 721.97 | 358.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.75 | 150.12 | 168.40 | 559.33 | 141.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.51 | 583.67 | 364.62 | 905.82 | 665.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.23 | 455.12 | 182.11 | 591.53 | 665.66 | 0.00 | 0.00 | 0.00 |
February | 811.51 | 583.66 | 227.84 | 828.78 | 508.27 | 0.00 | 0.00 | 0.00 |
March | 725.38 | 407.34 | 318.04 | 738.22 | 456.65 | 0.00 | 0.00 | 0.00 |
April | 583.09 | 278.89 | 304.19 | 615.76 | 343.50 | 0.00 | 0.00 | 0.00 |
May | 518.06 | 172.06 | 346.00 | 559.33 | 266.06 | 0.00 | 0.00 | 0.00 |
June | 514.74 | 150.12 | 364.62 | 635.25 | 179.63 | 0.00 | 0.00 | 0.00 |
July | 554.95 | 204.99 | 349.95 | 763.69 | 141.06 | 0.00 | 0.00 | 0.00 |
August | 659.51 | 332.51 | 327.00 | 879.81 | 159.63 | 0.00 | 0.00 | 0.00 |
September | 731.48 | 448.20 | 283.28 | 905.81 | 232.31 | 0.00 | 0.00 | 0.00 |
October | 764.72 | 528.79 | 235.93 | 866.17 | 333.74 | 0.00 | 0.00 | 0.00 |
November | 697.20 | 505.02 | 192.18 | 717.11 | 434.32 | 0.00 | 0.00 | 0.00 |
December | 605.97 | 437.57 | 168.40 | 572.03 | 581.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.20 | 373.97 | 275.23 | 721.97 | 358.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.74 | 150.12 | 168.40 | 559.33 | 141.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.51 | 583.66 | 364.62 | 905.81 | 665.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.21 | 455.11 | 182.10 | 591.51 | 665.63 | 0.00 | 0.00 | 0.00 |
February | 811.48 | 583.64 | 227.83 | 828.75 | 508.25 | 0.00 | 0.00 | 0.00 |
March | 725.35 | 407.32 | 318.03 | 738.20 | 456.63 | 0.00 | 0.00 | 0.00 |
April | 583.06 | 278.88 | 304.18 | 615.74 | 343.49 | 0.00 | 0.00 | 0.00 |
May | 518.04 | 172.05 | 345.99 | 559.31 | 266.05 | 0.00 | 0.00 | 0.00 |
June | 514.72 | 150.12 | 364.61 | 635.23 | 179.63 | 0.00 | 0.00 | 0.00 |
July | 554.92 | 204.99 | 349.94 | 763.66 | 141.06 | 0.00 | 0.00 | 0.00 |
August | 659.49 | 332.50 | 326.99 | 879.78 | 159.62 | 0.00 | 0.00 | 0.00 |
September | 731.45 | 448.18 | 283.27 | 905.78 | 232.30 | 0.00 | 0.00 | 0.00 |
October | 764.69 | 528.77 | 235.92 | 866.14 | 333.73 | 0.00 | 0.00 | 0.00 |
November | 697.17 | 505.00 | 192.17 | 717.09 | 434.30 | 0.00 | 0.00 | 0.00 |
December | 605.95 | 437.56 | 168.39 | 572.01 | 581.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.18 | 373.96 | 275.22 | 721.94 | 357.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.72 | 150.12 | 168.39 | 559.31 | 141.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.48 | 583.64 | 364.61 | 905.78 | 665.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.93 | 84.20 | 124.73 | 102.51 | 863.49 | 0.00 | 0.00 | 0.00 |
February | 356.61 | 175.29 | 181.32 | 259.88 | 655.07 | 0.00 | 0.00 | 0.00 |
March | 456.37 | 167.22 | 289.15 | 345.33 | 564.47 | 0.00 | 0.00 | 0.00 |
April | 595.79 | 263.96 | 331.83 | 557.81 | 428.71 | 0.00 | 0.00 | 0.00 |
May | 736.96 | 336.09 | 400.86 | 778.40 | 312.85 | 0.00 | 0.00 | 0.00 |
June | 801.78 | 368.29 | 433.49 | 947.17 | 214.94 | 0.00 | 0.00 | 0.00 |
July | 821.33 | 415.03 | 406.30 | 1052.76 | 180.14 | 0.00 | 0.00 | 0.00 |
August | 697.42 | 342.28 | 355.14 | 863.05 | 202.99 | 0.00 | 0.00 | 0.00 |
September | 561.03 | 283.64 | 277.40 | 643.34 | 274.75 | 0.00 | 0.00 | 0.00 |
October | 400.98 | 199.23 | 201.76 | 374.99 | 417.42 | 0.00 | 0.00 | 0.00 |
November | 283.86 | 140.82 | 143.04 | 207.70 | 584.85 | 0.00 | 0.00 | 0.00 |
December | 190.81 | 80.53 | 110.27 | 91.45 | 795.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 510.02 | 238.28 | 271.74 | 520.06 | 457.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 190.81 | 80.53 | 110.27 | 91.45 | 180.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 821.33 | 415.03 | 433.49 | 1052.76 | 863.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.93 | 84.20 | 124.73 | 102.51 | 863.49 | 0.00 | 0.00 | 0.00 |
February | 356.61 | 175.29 | 181.32 | 259.88 | 655.07 | 0.00 | 0.00 | 0.00 |
March | 456.37 | 167.22 | 289.15 | 345.33 | 564.47 | 0.00 | 0.00 | 0.00 |
April | 595.79 | 263.96 | 331.83 | 557.81 | 428.71 | 0.00 | 0.00 | 0.00 |
May | 736.96 | 336.09 | 400.86 | 778.40 | 312.85 | 0.00 | 0.00 | 0.00 |
June | 801.78 | 368.29 | 433.49 | 947.17 | 214.94 | 0.00 | 0.00 | 0.00 |
July | 821.33 | 415.03 | 406.30 | 1052.76 | 180.14 | 0.00 | 0.00 | 0.00 |
August | 697.42 | 342.28 | 355.14 | 863.05 | 202.99 | 0.00 | 0.00 | 0.00 |
September | 561.03 | 283.64 | 277.40 | 643.34 | 274.75 | 0.00 | 0.00 | 0.00 |
October | 400.98 | 199.23 | 201.76 | 374.99 | 417.42 | 0.00 | 0.00 | 0.00 |
November | 283.86 | 140.82 | 143.04 | 207.70 | 584.85 | 0.00 | 0.00 | 0.00 |
December | 190.81 | 80.53 | 110.27 | 91.45 | 795.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 510.02 | 238.28 | 271.74 | 520.06 | 457.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 190.81 | 80.53 | 110.27 | 91.45 | 180.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 821.33 | 415.03 | 433.49 | 1052.76 | 863.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.92 | 84.20 | 124.73 | 102.50 | 863.47 | 0.00 | 0.00 | 0.00 |
February | 356.60 | 175.29 | 181.31 | 259.87 | 655.06 | 0.00 | 0.00 | 0.00 |
March | 456.36 | 167.22 | 289.14 | 345.32 | 564.46 | 0.00 | 0.00 | 0.00 |
April | 595.78 | 263.96 | 331.82 | 557.80 | 428.71 | 0.00 | 0.00 | 0.00 |
May | 736.94 | 336.09 | 400.86 | 778.39 | 312.85 | 0.00 | 0.00 | 0.00 |
June | 801.76 | 368.28 | 433.48 | 947.15 | 214.93 | 0.00 | 0.00 | 0.00 |
July | 821.32 | 415.02 | 406.29 | 1052.74 | 180.14 | 0.00 | 0.00 | 0.00 |
August | 697.41 | 342.27 | 355.14 | 863.03 | 202.99 | 0.00 | 0.00 | 0.00 |
September | 561.02 | 283.63 | 277.39 | 643.33 | 274.75 | 0.00 | 0.00 | 0.00 |
October | 400.98 | 199.22 | 201.75 | 374.99 | 417.41 | 0.00 | 0.00 | 0.00 |
November | 283.85 | 140.82 | 143.04 | 207.69 | 584.84 | 0.00 | 0.00 | 0.00 |
December | 190.80 | 80.53 | 110.27 | 91.45 | 795.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 510.01 | 238.27 | 271.73 | 520.05 | 457.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 190.80 | 80.53 | 110.27 | 91.45 | 180.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 821.32 | 415.02 | 433.48 | 1052.74 | 863.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 452.02 | 0.00 | 452.02 | 15.63 | 3731.01 | 0.00 | 0.00 | 0.00 |
February | 638.23 | 0.00 | 638.23 | 118.93 | 2750.25 | 0.00 | 0.00 | 0.00 |
March | 1036.77 | 0.00 | 1036.77 | 380.09 | 2214.13 | 0.00 | 0.00 | 0.00 |
April | 1182.14 | 6.90 | 1175.24 | 645.80 | 1570.63 | 0.00 | 0.00 | 0.00 |
May | 1552.43 | 91.99 | 1460.44 | 1171.77 | 1171.82 | 0.00 | 0.00 | 0.00 |
June | 1807.72 | 207.78 | 1599.93 | 1857.11 | 759.29 | 0.00 | 0.00 | 0.00 |
July | 1651.45 | 154.68 | 1496.77 | 2013.80 | 633.73 | 0.00 | 0.00 | 0.00 |
August | 1323.31 | 35.47 | 1287.84 | 1466.98 | 723.54 | 0.00 | 0.00 | 0.00 |
September | 991.07 | 0.36 | 990.71 | 867.83 | 1091.94 | 0.00 | 0.00 | 0.00 |
October | 722.93 | 0.00 | 722.93 | 345.89 | 1612.59 | 0.00 | 0.00 | 0.00 |
November | 491.45 | 0.00 | 491.45 | 85.80 | 2309.03 | 0.00 | 0.00 | 0.00 |
December | 379.05 | 0.00 | 379.05 | 8.28 | 3179.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1021.09 | 41.64 | 979.45 | 752.06 | 1808.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.05 | 0.00 | 379.05 | 8.28 | 633.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1807.72 | 207.78 | 1599.93 | 2013.80 | 3731.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 691.97 | 317.24 | 374.73 | 372.00 | 2293.42 | 0.00 | 0.00 | 0.00 |
February | 1082.30 | 537.34 | 544.96 | 820.42 | 1690.96 | 0.00 | 0.00 | 0.00 |
March | 1455.25 | 602.14 | 853.11 | 1198.32 | 1394.39 | 0.00 | 0.00 | 0.00 |
April | 1856.76 | 920.19 | 936.56 | 1802.15 | 1004.63 | 0.00 | 0.00 | 0.00 |
May | 2051.03 | 912.58 | 1138.45 | 2132.25 | 783.58 | 0.00 | 0.00 | 0.00 |
June | 2654.79 | 1366.15 | 1288.64 | 3163.32 | 516.02 | 0.00 | 0.00 | 0.00 |
July | 2786.28 | 1575.16 | 1211.12 | 3578.93 | 422.59 | 0.00 | 0.00 | 0.00 |
August | 2421.40 | 1349.13 | 1072.27 | 3038.28 | 475.49 | 0.00 | 0.00 | 0.00 |
September | 1712.90 | 884.19 | 828.71 | 1958.30 | 684.67 | 0.00 | 0.00 | 0.00 |
October | 1228.92 | 624.03 | 604.89 | 1176.39 | 1009.63 | 0.00 | 0.00 | 0.00 |
November | 778.86 | 363.63 | 415.24 | 548.89 | 1409.87 | 0.00 | 0.00 | 0.00 |
December | 574.46 | 246.73 | 327.73 | 293.16 | 1951.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1610.66 | 809.61 | 801.05 | 1678.41 | 1134.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 574.46 | 246.73 | 327.73 | 293.16 | 422.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2786.28 | 1575.16 | 1288.64 | 3578.93 | 2293.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3186.24 | 2275.68 | 910.56 | 2955.62 | 3254.46 | 0.00 | 0.00 | 0.00 |
February | 4057.63 | 2918.40 | 1139.23 | 4135.80 | 2460.93 | 0.00 | 0.00 | 0.00 |
March | 3627.00 | 2036.75 | 1590.24 | 3686.92 | 2200.42 | 0.00 | 0.00 | 0.00 |
April | 2915.50 | 1394.50 | 1521.00 | 3082.21 | 1639.69 | 0.00 | 0.00 | 0.00 |
May | 2590.34 | 860.32 | 1730.02 | 2794.20 | 1281.27 | 0.00 | 0.00 | 0.00 |
June | 2573.77 | 750.63 | 1823.13 | 3174.12 | 875.44 | 0.00 | 0.00 | 0.00 |
July | 2774.78 | 1025.00 | 1749.79 | 3814.63 | 700.60 | 0.00 | 0.00 | 0.00 |
August | 3297.64 | 1662.61 | 1635.03 | 4389.02 | 794.49 | 0.00 | 0.00 | 0.00 |
September | 3657.48 | 2241.06 | 1416.43 | 4502.97 | 1136.37 | 0.00 | 0.00 | 0.00 |
October | 3823.70 | 2644.04 | 1179.66 | 4316.23 | 1612.24 | 0.00 | 0.00 | 0.00 |
November | 3486.08 | 2525.18 | 960.91 | 3591.19 | 2080.04 | 0.00 | 0.00 | 0.00 |
December | 3029.94 | 2187.92 | 842.02 | 2884.94 | 2766.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3246.08 | 1869.91 | 1376.16 | 3606.59 | 1730.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2573.77 | 750.63 | 842.02 | 2794.20 | 700.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4057.63 | 2918.40 | 1823.13 | 4502.97 | 3254.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 626.78 | 252.60 | 374.18 | 322.02 | 2420.90 | 0.00 | 0.00 | 0.00 |
February | 1069.81 | 525.87 | 543.95 | 823.15 | 1769.49 | 0.00 | 0.00 | 0.00 |
March | 1369.10 | 501.66 | 867.44 | 1099.23 | 1487.11 | 0.00 | 0.00 | 0.00 |
April | 1787.37 | 791.89 | 995.48 | 1746.76 | 1096.24 | 0.00 | 0.00 | 0.00 |
May | 2210.84 | 1008.26 | 1202.58 | 2364.57 | 861.61 | 0.00 | 0.00 | 0.00 |
June | 2405.31 | 1104.85 | 1300.46 | 2874.72 | 593.67 | 0.00 | 0.00 | 0.00 |
July | 2463.98 | 1245.08 | 1218.89 | 3193.82 | 498.88 | 0.00 | 0.00 | 0.00 |
August | 2092.25 | 1026.83 | 1065.42 | 2639.25 | 538.33 | 0.00 | 0.00 | 0.00 |
September | 1683.08 | 850.90 | 832.18 | 1956.64 | 754.32 | 0.00 | 0.00 | 0.00 |
October | 1202.94 | 597.68 | 605.26 | 1177.93 | 1091.93 | 0.00 | 0.00 | 0.00 |
November | 851.57 | 422.45 | 429.12 | 672.06 | 1501.35 | 0.00 | 0.00 | 0.00 |
December | 572.41 | 241.60 | 330.81 | 309.12 | 2048.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1530.03 | 714.83 | 815.21 | 1602.30 | 1219.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 572.41 | 241.60 | 330.81 | 309.12 | 498.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2463.98 | 1245.08 | 1300.46 | 3193.82 | 2420.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 452.02 | 0.00 | 452.02 | 22.12 | 3598.48 | 0.00 | 0.00 | 0.00 |
February | 638.23 | 0.00 | 638.23 | 141.17 | 2618.94 | 0.00 | 0.00 | 0.00 |
March | 1036.77 | 0.00 | 1036.77 | 416.00 | 2082.47 | 0.00 | 0.00 | 0.00 |
April | 1182.14 | 6.90 | 1175.24 | 697.53 | 1445.79 | 0.00 | 0.00 | 0.00 |
May | 1552.43 | 91.99 | 1460.44 | 1211.51 | 1093.97 | 0.00 | 0.00 | 0.00 |
June | 1807.72 | 207.78 | 1599.93 | 1876.32 | 732.54 | 0.00 | 0.00 | 0.00 |
July | 1651.45 | 154.68 | 1496.77 | 2018.11 | 621.30 | 0.00 | 0.00 | 0.00 |
August | 1323.31 | 35.47 | 1287.84 | 1477.13 | 698.19 | 0.00 | 0.00 | 0.00 |
September | 991.07 | 0.36 | 990.71 | 896.32 | 1018.79 | 0.00 | 0.00 | 0.00 |
October | 722.93 | 0.00 | 722.93 | 394.75 | 1462.36 | 0.00 | 0.00 | 0.00 |
November | 491.45 | 0.00 | 491.45 | 105.76 | 2131.69 | 0.00 | 0.00 | 0.00 |
December | 379.05 | 0.00 | 379.05 | 10.75 | 3037.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1021.09 | 41.64 | 979.45 | 776.14 | 1708.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.05 | 0.00 | 379.05 | 10.75 | 621.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1807.72 | 207.78 | 1599.93 | 2018.11 | 3598.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 691.97 | 317.24 | 374.73 | 384.08 | 2212.40 | 0.00 | 0.00 | 0.00 |
February | 1082.30 | 537.34 | 544.96 | 844.91 | 1612.39 | 0.00 | 0.00 | 0.00 |
March | 1455.25 | 602.14 | 853.11 | 1226.41 | 1317.90 | 0.00 | 0.00 | 0.00 |
April | 1856.76 | 920.19 | 936.56 | 1828.68 | 939.32 | 0.00 | 0.00 | 0.00 |
May | 2051.03 | 912.58 | 1138.45 | 2144.57 | 743.14 | 0.00 | 0.00 | 0.00 |
June | 2654.79 | 1366.15 | 1288.64 | 3161.46 | 507.17 | 0.00 | 0.00 | 0.00 |
July | 2786.28 | 1575.16 | 1211.12 | 3570.43 | 421.20 | 0.00 | 0.00 | 0.00 |
August | 2421.40 | 1349.13 | 1072.27 | 3033.03 | 469.25 | 0.00 | 0.00 | 0.00 |
September | 1712.90 | 884.19 | 828.71 | 1966.01 | 655.69 | 0.00 | 0.00 | 0.00 |
October | 1228.92 | 624.03 | 604.89 | 1209.20 | 931.08 | 0.00 | 0.00 | 0.00 |
November | 778.86 | 363.63 | 415.24 | 574.42 | 1308.33 | 0.00 | 0.00 | 0.00 |
December | 574.46 | 246.73 | 327.73 | 304.00 | 1864.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1610.66 | 809.61 | 801.05 | 1692.05 | 1080.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 574.46 | 246.73 | 327.73 | 304.00 | 421.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2786.28 | 1575.16 | 1288.64 | 3570.43 | 2212.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3186.24 | 2275.68 | 910.56 | 2994.04 | 3113.04 | 0.00 | 0.00 | 0.00 |
February | 4057.63 | 2918.40 | 1139.23 | 4180.14 | 2328.42 | 0.00 | 0.00 | 0.00 |
March | 3627.00 | 2036.75 | 1590.24 | 3724.64 | 2072.31 | 0.00 | 0.00 | 0.00 |
April | 2915.50 | 1394.50 | 1521.00 | 3118.71 | 1527.97 | 0.00 | 0.00 | 0.00 |
May | 2590.34 | 860.32 | 1730.02 | 2812.84 | 1209.30 | 0.00 | 0.00 | 0.00 |
June | 2573.77 | 750.63 | 1823.13 | 3176.65 | 851.08 | 0.00 | 0.00 | 0.00 |
July | 2774.78 | 1025.00 | 1749.79 | 3808.16 | 691.10 | 0.00 | 0.00 | 0.00 |
August | 3297.64 | 1662.61 | 1635.03 | 4383.62 | 777.19 | 0.00 | 0.00 | 0.00 |
September | 3657.48 | 2241.06 | 1416.43 | 4511.98 | 1083.13 | 0.00 | 0.00 | 0.00 |
October | 3823.70 | 2644.04 | 1179.66 | 4356.22 | 1488.10 | 0.00 | 0.00 | 0.00 |
November | 3486.08 | 2525.18 | 960.91 | 3649.54 | 1921.70 | 0.00 | 0.00 | 0.00 |
December | 3029.94 | 2187.92 | 842.02 | 2926.35 | 2624.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3246.08 | 1869.91 | 1376.16 | 3632.69 | 1638.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2573.77 | 750.63 | 842.02 | 2812.84 | 691.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4057.63 | 2918.40 | 1823.13 | 4511.98 | 3113.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 626.78 | 252.60 | 374.18 | 330.37 | 2336.46 | 0.00 | 0.00 | 0.00 |
February | 1069.81 | 525.87 | 543.95 | 837.47 | 1692.28 | 0.00 | 0.00 | 0.00 |
March | 1369.10 | 501.66 | 867.44 | 1114.95 | 1413.68 | 0.00 | 0.00 | 0.00 |
April | 1787.37 | 791.89 | 995.48 | 1766.80 | 1031.07 | 0.00 | 0.00 | 0.00 |
May | 2210.84 | 1008.26 | 1202.58 | 2374.14 | 817.99 | 0.00 | 0.00 | 0.00 |
June | 2405.31 | 1104.85 | 1300.46 | 2874.94 | 579.68 | 0.00 | 0.00 | 0.00 |
July | 2463.98 | 1245.08 | 1218.89 | 3189.73 | 493.20 | 0.00 | 0.00 | 0.00 |
August | 2092.25 | 1026.83 | 1065.42 | 2638.29 | 527.48 | 0.00 | 0.00 | 0.00 |
September | 1683.08 | 850.90 | 832.18 | 1963.24 | 721.00 | 0.00 | 0.00 | 0.00 |
October | 1202.94 | 597.68 | 605.26 | 1198.84 | 1015.93 | 0.00 | 0.00 | 0.00 |
November | 851.57 | 422.45 | 429.12 | 688.64 | 1405.12 | 0.00 | 0.00 | 0.00 |
December | 572.41 | 241.60 | 330.81 | 316.23 | 1965.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1530.03 | 714.83 | 815.21 | 1611.77 | 1164.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 572.41 | 241.60 | 330.81 | 316.23 | 493.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2463.98 | 1245.08 | 1300.46 | 3189.73 | 2336.46 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242139E+09 | 0.00 | 0.242139E+09 | 4019776.27 | 0.212416E+10 |
February | 0.308799E+09 | 0.00 | 0.308799E+09 | 37717438.67 | 0.144603E+10 |
March | 0.555376E+09 | 0.00 | 0.555376E+09 | 0.167477E+09 | 0.130495E+10 |
April | 0.612820E+09 | 3576254.47 | 0.609243E+09 | 0.299147E+09 | 0.907298E+09 |
May | 0.831604E+09 | 49277394.08 | 0.782327E+09 | 0.603605E+09 | 0.677141E+09 |
June | 0.937120E+09 | 0.107713E+09 | 0.829407E+09 | 0.950152E+09 | 0.410666E+09 |
July | 0.884648E+09 | 82857303.69 | 0.801791E+09 | 0.106700E+10 | 0.349312E+09 |
August | 0.708873E+09 | 19000970.75 | 0.689872E+09 | 0.771757E+09 | 0.404050E+09 |
September | 0.513771E+09 | 184367.60 | 0.513587E+09 | 0.433988E+09 | 0.608081E+09 |
October | 0.387258E+09 | 0.00 | 0.387258E+09 | 0.156413E+09 | 0.964389E+09 |
November | 0.254769E+09 | 0.00 | 0.254769E+09 | 29944615.62 | 0.135246E+10 |
December | 0.203047E+09 | 0.00 | 0.203047E+09 | 1321142.19 | 0.189569E+10 |
Annual Sum or Average | 0.644022E+10 | 0.262610E+09 | 0.617761E+10 | 0.452254E+10 | 0.124442E+11 |
Minimum of Months | 0.203047E+09 | 0.00 | 0.203047E+09 | 1321142.19 | 0.349312E+09 |
Maximum of Months | 0.937120E+09 | 0.107713E+09 | 0.829407E+09 | 0.106700E+10 | 0.212416E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242135E+09 | 0.00 | 0.242135E+09 | 4019392.08 | 0.212416E+10 |
February | 0.308795E+09 | 0.00 | 0.308795E+09 | 37715617.64 | 0.144603E+10 |
March | 0.555368E+09 | 0.00 | 0.555368E+09 | 0.167470E+09 | 0.130495E+10 |
April | 0.612811E+09 | 3576175.85 | 0.609235E+09 | 0.299140E+09 | 0.907299E+09 |
May | 0.831592E+09 | 49276310.77 | 0.782316E+09 | 0.603591E+09 | 0.677142E+09 |
June | 0.937106E+09 | 0.107711E+09 | 0.829396E+09 | 0.950135E+09 | 0.410665E+09 |
July | 0.884636E+09 | 82855482.17 | 0.801781E+09 | 0.106699E+10 | 0.349311E+09 |
August | 0.708864E+09 | 19000553.03 | 0.689863E+09 | 0.771747E+09 | 0.404049E+09 |
September | 0.513764E+09 | 184363.55 | 0.513580E+09 | 0.433981E+09 | 0.608080E+09 |
October | 0.387253E+09 | 0.00 | 0.387253E+09 | 0.156408E+09 | 0.964388E+09 |
November | 0.254766E+09 | 0.00 | 0.254766E+09 | 29943097.09 | 0.135246E+10 |
December | 0.203044E+09 | 0.00 | 0.203044E+09 | 1320974.89 | 0.189569E+10 |
Annual Sum or Average | 0.644013E+10 | 0.262604E+09 | 0.617753E+10 | 0.452246E+10 | 0.124442E+11 |
Minimum of Months | 0.203044E+09 | 0.00 | 0.203044E+09 | 1320974.89 | 0.349311E+09 |
Maximum of Months | 0.937106E+09 | 0.107711E+09 | 0.829396E+09 | 0.106699E+10 | 0.212416E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242136E+09 | 0.00 | 0.242136E+09 | 4019520.15 | 0.212416E+10 |
February | 0.308796E+09 | 0.00 | 0.308796E+09 | 37716224.65 | 0.144603E+10 |
March | 0.555371E+09 | 0.00 | 0.555371E+09 | 0.167473E+09 | 0.130495E+10 |
April | 0.612814E+09 | 3576202.05 | 0.609237E+09 | 0.299142E+09 | 0.907299E+09 |
May | 0.831596E+09 | 49276671.88 | 0.782319E+09 | 0.603596E+09 | 0.677142E+09 |
June | 0.937111E+09 | 0.107712E+09 | 0.829399E+09 | 0.950141E+09 | 0.410665E+09 |
July | 0.884640E+09 | 82856089.35 | 0.801784E+09 | 0.106699E+10 | 0.349311E+09 |
August | 0.708867E+09 | 19000692.27 | 0.689866E+09 | 0.771750E+09 | 0.404049E+09 |
September | 0.513767E+09 | 184364.90 | 0.513582E+09 | 0.433983E+09 | 0.608080E+09 |
October | 0.387254E+09 | 0.00 | 0.387254E+09 | 0.156410E+09 | 0.964388E+09 |
November | 0.254767E+09 | 0.00 | 0.254767E+09 | 29943603.27 | 0.135246E+10 |
December | 0.203045E+09 | 0.00 | 0.203045E+09 | 1321030.66 | 0.189569E+10 |
Annual Sum or Average | 0.644016E+10 | 0.262606E+09 | 0.617756E+10 | 0.452249E+10 | 0.124442E+11 |
Minimum of Months | 0.203045E+09 | 0.00 | 0.203045E+09 | 1321030.66 | 0.349311E+09 |
Maximum of Months | 0.937111E+09 | 0.107712E+09 | 0.829399E+09 | 0.106699E+10 | 0.212416E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242135E+09 | 0.00 | 0.242135E+09 | 4019392.08 | 0.212416E+10 |
February | 0.308795E+09 | 0.00 | 0.308795E+09 | 37715617.64 | 0.144603E+10 |
March | 0.555368E+09 | 0.00 | 0.555368E+09 | 0.167470E+09 | 0.130495E+10 |
April | 0.612811E+09 | 3576175.85 | 0.609235E+09 | 0.299140E+09 | 0.907299E+09 |
May | 0.831592E+09 | 49276310.77 | 0.782316E+09 | 0.603591E+09 | 0.677142E+09 |
June | 0.937106E+09 | 0.107711E+09 | 0.829396E+09 | 0.950135E+09 | 0.410665E+09 |
July | 0.884636E+09 | 82855482.17 | 0.801781E+09 | 0.106699E+10 | 0.349311E+09 |
August | 0.708864E+09 | 19000553.03 | 0.689863E+09 | 0.771747E+09 | 0.404049E+09 |
September | 0.513764E+09 | 184363.55 | 0.513580E+09 | 0.433981E+09 | 0.608080E+09 |
October | 0.387253E+09 | 0.00 | 0.387253E+09 | 0.156408E+09 | 0.964388E+09 |
November | 0.254766E+09 | 0.00 | 0.254766E+09 | 29943097.09 | 0.135246E+10 |
December | 0.203044E+09 | 0.00 | 0.203044E+09 | 1320974.89 | 0.189569E+10 |
Annual Sum or Average | 0.644013E+10 | 0.262604E+09 | 0.617753E+10 | 0.452246E+10 | 0.124442E+11 |
Minimum of Months | 0.203044E+09 | 0.00 | 0.203044E+09 | 1320974.89 | 0.349311E+09 |
Maximum of Months | 0.937106E+09 | 0.107711E+09 | 0.829396E+09 | 0.106699E+10 | 0.212416E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242126E+09 | 0.00 | 0.242126E+09 | 4019294.11 | 0.212408E+10 |
February | 0.308783E+09 | 0.00 | 0.308783E+09 | 37714401.03 | 0.144598E+10 |
March | 0.555347E+09 | 0.00 | 0.555347E+09 | 0.167465E+09 | 0.130490E+10 |
April | 0.612788E+09 | 3576044.81 | 0.609211E+09 | 0.299129E+09 | 0.907262E+09 |
May | 0.831561E+09 | 49274505.26 | 0.782286E+09 | 0.603569E+09 | 0.677114E+09 |
June | 0.937071E+09 | 0.107707E+09 | 0.829364E+09 | 0.950100E+09 | 0.410649E+09 |
July | 0.884602E+09 | 82852446.31 | 0.801750E+09 | 0.106694E+10 | 0.349297E+09 |
August | 0.708837E+09 | 18999856.84 | 0.689837E+09 | 0.771718E+09 | 0.404032E+09 |
September | 0.513745E+09 | 184356.80 | 0.513560E+09 | 0.433964E+09 | 0.608056E+09 |
October | 0.387238E+09 | 0.00 | 0.387238E+09 | 0.156403E+09 | 0.964349E+09 |
November | 0.254756E+09 | 0.00 | 0.254756E+09 | 29942143.33 | 0.135240E+10 |
December | 0.203036E+09 | 0.00 | 0.203036E+09 | 1320949.53 | 0.189561E+10 |
Annual Sum or Average | 0.643989E+10 | 0.262594E+09 | 0.617729E+10 | 0.452229E+10 | 0.124437E+11 |
Minimum of Months | 0.203036E+09 | 0.00 | 0.203036E+09 | 1320949.53 | 0.349297E+09 |
Maximum of Months | 0.937071E+09 | 0.107707E+09 | 0.829364E+09 | 0.106694E+10 | 0.212408E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.617795E+09 | 0.283234E+09 | 0.334561E+09 | 0.317893E+09 | 0.215290E+10 |
February | 0.872775E+09 | 0.433312E+09 | 0.439463E+09 | 0.638756E+09 | 0.145279E+10 |
March | 0.129926E+10 | 0.537598E+09 | 0.761663E+09 | 0.104422E+10 | 0.132861E+10 |
April | 0.160425E+10 | 0.795056E+09 | 0.809197E+09 | 0.154248E+10 | 0.924344E+09 |
May | 0.183118E+10 | 0.814759E+09 | 0.101642E+10 | 0.189673E+10 | 0.743502E+09 |
June | 0.229376E+10 | 0.118037E+10 | 0.111339E+10 | 0.274207E+10 | 0.454688E+09 |
July | 0.248761E+10 | 0.140631E+10 | 0.108130E+10 | 0.320916E+10 | 0.370746E+09 |
August | 0.216185E+10 | 0.120451E+10 | 0.957333E+09 | 0.272511E+10 | 0.414240E+09 |
September | 0.147996E+10 | 0.763951E+09 | 0.716011E+09 | 0.168859E+10 | 0.621124E+09 |
October | 0.109719E+10 | 0.557135E+09 | 0.540053E+09 | 0.102765E+10 | 0.974431E+09 |
November | 0.672946E+09 | 0.314177E+09 | 0.358768E+09 | 0.451000E+09 | 0.132753E+10 |
December | 0.512881E+09 | 0.220284E+09 | 0.292597E+09 | 0.243861E+09 | 0.188523E+10 |
Annual Sum or Average | 0.169315E+11 | 0.851070E+10 | 0.842076E+10 | 0.175275E+11 | 0.126501E+11 |
Minimum of Months | 0.512881E+09 | 0.220284E+09 | 0.292597E+09 | 0.243861E+09 | 0.370746E+09 |
Maximum of Months | 0.248761E+10 | 0.140631E+10 | 0.111339E+10 | 0.320916E+10 | 0.215290E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.617795E+09 | 0.283234E+09 | 0.334561E+09 | 0.317893E+09 | 0.215290E+10 |
February | 0.872775E+09 | 0.433312E+09 | 0.439463E+09 | 0.638756E+09 | 0.145279E+10 |
March | 0.129926E+10 | 0.537598E+09 | 0.761663E+09 | 0.104422E+10 | 0.132861E+10 |
April | 0.160425E+10 | 0.795056E+09 | 0.809197E+09 | 0.154248E+10 | 0.924344E+09 |
May | 0.183118E+10 | 0.814759E+09 | 0.101642E+10 | 0.189673E+10 | 0.743502E+09 |
June | 0.229376E+10 | 0.118037E+10 | 0.111339E+10 | 0.274207E+10 | 0.454688E+09 |
July | 0.248761E+10 | 0.140631E+10 | 0.108130E+10 | 0.320916E+10 | 0.370746E+09 |
August | 0.216185E+10 | 0.120451E+10 | 0.957333E+09 | 0.272511E+10 | 0.414240E+09 |
September | 0.147996E+10 | 0.763951E+09 | 0.716011E+09 | 0.168859E+10 | 0.621124E+09 |
October | 0.109719E+10 | 0.557135E+09 | 0.540053E+09 | 0.102765E+10 | 0.974431E+09 |
November | 0.672946E+09 | 0.314177E+09 | 0.358768E+09 | 0.451000E+09 | 0.132753E+10 |
December | 0.512881E+09 | 0.220284E+09 | 0.292597E+09 | 0.243861E+09 | 0.188523E+10 |
Annual Sum or Average | 0.169315E+11 | 0.851070E+10 | 0.842076E+10 | 0.175275E+11 | 0.126501E+11 |
Minimum of Months | 0.512881E+09 | 0.220284E+09 | 0.292597E+09 | 0.243861E+09 | 0.370746E+09 |
Maximum of Months | 0.248761E+10 | 0.140631E+10 | 0.111339E+10 | 0.320916E+10 | 0.215290E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.617784E+09 | 0.283229E+09 | 0.334555E+09 | 0.317887E+09 | 0.215286E+10 |
February | 0.872759E+09 | 0.433304E+09 | 0.439455E+09 | 0.638744E+09 | 0.145276E+10 |
March | 0.129924E+10 | 0.537588E+09 | 0.761649E+09 | 0.104420E+10 | 0.132859E+10 |
April | 0.160422E+10 | 0.795042E+09 | 0.809182E+09 | 0.154245E+10 | 0.924327E+09 |
May | 0.183114E+10 | 0.814744E+09 | 0.101640E+10 | 0.189669E+10 | 0.743488E+09 |
June | 0.229372E+10 | 0.118035E+10 | 0.111337E+10 | 0.274202E+10 | 0.454680E+09 |
July | 0.248757E+10 | 0.140629E+10 | 0.108128E+10 | 0.320911E+10 | 0.370740E+09 |
August | 0.216181E+10 | 0.120449E+10 | 0.957315E+09 | 0.272506E+10 | 0.414233E+09 |
September | 0.147994E+10 | 0.763937E+09 | 0.715998E+09 | 0.168856E+10 | 0.621112E+09 |
October | 0.109717E+10 | 0.557125E+09 | 0.540043E+09 | 0.102763E+10 | 0.974413E+09 |
November | 0.672933E+09 | 0.314171E+09 | 0.358762E+09 | 0.450992E+09 | 0.132751E+10 |
December | 0.512872E+09 | 0.220279E+09 | 0.292592E+09 | 0.243857E+09 | 0.188519E+10 |
Annual Sum or Average | 0.169312E+11 | 0.851055E+10 | 0.842060E+10 | 0.175272E+11 | 0.126499E+11 |
Minimum of Months | 0.512872E+09 | 0.220279E+09 | 0.292592E+09 | 0.243857E+09 | 0.370740E+09 |
Maximum of Months | 0.248757E+10 | 0.140629E+10 | 0.111337E+10 | 0.320911E+10 | 0.215286E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170677E+10 | 0.121901E+10 | 0.487764E+09 | 0.158436E+10 | 0.178290E+10 |
February | 0.196321E+10 | 0.141201E+10 | 0.551198E+09 | 0.200499E+10 | 0.122961E+10 |
March | 0.194287E+10 | 0.109103E+10 | 0.851849E+09 | 0.197727E+10 | 0.122308E+10 |
April | 0.151137E+10 | 0.722894E+09 | 0.788475E+09 | 0.159606E+10 | 0.890361E+09 |
May | 0.138758E+10 | 0.460849E+09 | 0.926727E+09 | 0.149811E+10 | 0.712616E+09 |
June | 0.133422E+10 | 0.389120E+09 | 0.945104E+09 | 0.164659E+10 | 0.465613E+09 |
July | 0.148637E+10 | 0.549058E+09 | 0.937317E+09 | 0.204548E+10 | 0.377824E+09 |
August | 0.176645E+10 | 0.890610E+09 | 0.875845E+09 | 0.235651E+10 | 0.427540E+09 |
September | 0.189601E+10 | 0.116174E+10 | 0.734266E+09 | 0.234788E+10 | 0.602140E+09 |
October | 0.204824E+10 | 0.141633E+10 | 0.631912E+09 | 0.231997E+10 | 0.893899E+09 |
November | 0.180715E+10 | 0.130903E+10 | 0.498126E+09 | 0.185877E+10 | 0.112575E+10 |
December | 0.162305E+10 | 0.117200E+10 | 0.451044E+09 | 0.153214E+10 | 0.155845E+10 |
Annual Sum or Average | 0.204733E+11 | 0.117937E+11 | 0.867963E+10 | 0.227681E+11 | 0.112898E+11 |
Minimum of Months | 0.133422E+10 | 0.389120E+09 | 0.451044E+09 | 0.149811E+10 | 0.377824E+09 |
Maximum of Months | 0.204824E+10 | 0.141633E+10 | 0.945104E+09 | 0.235651E+10 | 0.178290E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170676E+10 | 0.121900E+10 | 0.487761E+09 | 0.158435E+10 | 0.178290E+10 |
February | 0.196319E+10 | 0.141200E+10 | 0.551195E+09 | 0.200498E+10 | 0.122961E+10 |
March | 0.194286E+10 | 0.109102E+10 | 0.851844E+09 | 0.197726E+10 | 0.122308E+10 |
April | 0.151136E+10 | 0.722889E+09 | 0.788471E+09 | 0.159605E+10 | 0.890361E+09 |
May | 0.138757E+10 | 0.460846E+09 | 0.926722E+09 | 0.149810E+10 | 0.712616E+09 |
June | 0.133422E+10 | 0.389117E+09 | 0.945099E+09 | 0.164658E+10 | 0.465613E+09 |
July | 0.148637E+10 | 0.549054E+09 | 0.937312E+09 | 0.204546E+10 | 0.377823E+09 |
August | 0.176644E+10 | 0.890603E+09 | 0.875840E+09 | 0.235650E+10 | 0.427540E+09 |
September | 0.189599E+10 | 0.116173E+10 | 0.734262E+09 | 0.234786E+10 | 0.602140E+09 |
October | 0.204823E+10 | 0.141632E+10 | 0.631909E+09 | 0.231995E+10 | 0.893899E+09 |
November | 0.180714E+10 | 0.130902E+10 | 0.498123E+09 | 0.185875E+10 | 0.112575E+10 |
December | 0.162303E+10 | 0.117199E+10 | 0.451041E+09 | 0.153213E+10 | 0.155845E+10 |
Annual Sum or Average | 0.204732E+11 | 0.117936E+11 | 0.867958E+10 | 0.227680E+11 | 0.112898E+11 |
Minimum of Months | 0.133422E+10 | 0.389117E+09 | 0.451041E+09 | 0.149810E+10 | 0.377823E+09 |
Maximum of Months | 0.204823E+10 | 0.141632E+10 | 0.945099E+09 | 0.235650E+10 | 0.178290E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170677E+10 | 0.121901E+10 | 0.487764E+09 | 0.158436E+10 | 0.178290E+10 |
February | 0.196321E+10 | 0.141201E+10 | 0.551198E+09 | 0.200499E+10 | 0.122961E+10 |
March | 0.194287E+10 | 0.109103E+10 | 0.851849E+09 | 0.197727E+10 | 0.122308E+10 |
April | 0.151137E+10 | 0.722894E+09 | 0.788475E+09 | 0.159606E+10 | 0.890361E+09 |
May | 0.138758E+10 | 0.460849E+09 | 0.926727E+09 | 0.149811E+10 | 0.712616E+09 |
June | 0.133422E+10 | 0.389120E+09 | 0.945104E+09 | 0.164659E+10 | 0.465613E+09 |
July | 0.148637E+10 | 0.549058E+09 | 0.937317E+09 | 0.204548E+10 | 0.377824E+09 |
August | 0.176645E+10 | 0.890610E+09 | 0.875845E+09 | 0.235651E+10 | 0.427540E+09 |
September | 0.189601E+10 | 0.116174E+10 | 0.734266E+09 | 0.234788E+10 | 0.602140E+09 |
October | 0.204824E+10 | 0.141633E+10 | 0.631912E+09 | 0.231997E+10 | 0.893899E+09 |
November | 0.180715E+10 | 0.130903E+10 | 0.498126E+09 | 0.185877E+10 | 0.112575E+10 |
December | 0.162305E+10 | 0.117200E+10 | 0.451044E+09 | 0.153214E+10 | 0.155845E+10 |
Annual Sum or Average | 0.204733E+11 | 0.117937E+11 | 0.867963E+10 | 0.227681E+11 | 0.112898E+11 |
Minimum of Months | 0.133422E+10 | 0.389120E+09 | 0.451044E+09 | 0.149811E+10 | 0.377824E+09 |
Maximum of Months | 0.204824E+10 | 0.141633E+10 | 0.945104E+09 | 0.235651E+10 | 0.178290E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170676E+10 | 0.121900E+10 | 0.487761E+09 | 0.158435E+10 | 0.178290E+10 |
February | 0.196319E+10 | 0.141200E+10 | 0.551195E+09 | 0.200498E+10 | 0.122961E+10 |
March | 0.194286E+10 | 0.109102E+10 | 0.851844E+09 | 0.197726E+10 | 0.122308E+10 |
April | 0.151136E+10 | 0.722889E+09 | 0.788471E+09 | 0.159605E+10 | 0.890361E+09 |
May | 0.138757E+10 | 0.460846E+09 | 0.926722E+09 | 0.149810E+10 | 0.712616E+09 |
June | 0.133422E+10 | 0.389117E+09 | 0.945099E+09 | 0.164658E+10 | 0.465613E+09 |
July | 0.148637E+10 | 0.549054E+09 | 0.937312E+09 | 0.204546E+10 | 0.377823E+09 |
August | 0.176644E+10 | 0.890603E+09 | 0.875840E+09 | 0.235650E+10 | 0.427540E+09 |
September | 0.189599E+10 | 0.116173E+10 | 0.734262E+09 | 0.234786E+10 | 0.602140E+09 |
October | 0.204823E+10 | 0.141632E+10 | 0.631909E+09 | 0.231995E+10 | 0.893899E+09 |
November | 0.180714E+10 | 0.130902E+10 | 0.498123E+09 | 0.185875E+10 | 0.112575E+10 |
December | 0.162303E+10 | 0.117199E+10 | 0.451041E+09 | 0.153213E+10 | 0.155845E+10 |
Annual Sum or Average | 0.204732E+11 | 0.117936E+11 | 0.867958E+10 | 0.227680E+11 | 0.112898E+11 |
Minimum of Months | 0.133422E+10 | 0.389117E+09 | 0.451041E+09 | 0.149810E+10 | 0.377823E+09 |
Maximum of Months | 0.204823E+10 | 0.141632E+10 | 0.945099E+09 | 0.235650E+10 | 0.178290E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170670E+10 | 0.121896E+10 | 0.487742E+09 | 0.158429E+10 | 0.178283E+10 |
February | 0.196312E+10 | 0.141195E+10 | 0.551174E+09 | 0.200490E+10 | 0.122956E+10 |
March | 0.194279E+10 | 0.109098E+10 | 0.851812E+09 | 0.197718E+10 | 0.122303E+10 |
April | 0.151130E+10 | 0.722862E+09 | 0.788441E+09 | 0.159599E+10 | 0.890325E+09 |
May | 0.138752E+10 | 0.460829E+09 | 0.926687E+09 | 0.149804E+10 | 0.712587E+09 |
June | 0.133417E+10 | 0.389103E+09 | 0.945063E+09 | 0.164652E+10 | 0.465594E+09 |
July | 0.148631E+10 | 0.549034E+09 | 0.937277E+09 | 0.204539E+10 | 0.377808E+09 |
August | 0.176638E+10 | 0.890571E+09 | 0.875807E+09 | 0.235641E+10 | 0.427523E+09 |
September | 0.189592E+10 | 0.116169E+10 | 0.734234E+09 | 0.234778E+10 | 0.602116E+09 |
October | 0.204815E+10 | 0.141627E+10 | 0.631885E+09 | 0.231986E+10 | 0.893863E+09 |
November | 0.180707E+10 | 0.130897E+10 | 0.498104E+09 | 0.185869E+10 | 0.112571E+10 |
December | 0.162297E+10 | 0.117195E+10 | 0.451025E+09 | 0.153207E+10 | 0.155839E+10 |
Annual Sum or Average | 0.204724E+11 | 0.117932E+11 | 0.867925E+10 | 0.227671E+11 | 0.112893E+11 |
Minimum of Months | 0.133417E+10 | 0.389103E+09 | 0.451025E+09 | 0.149804E+10 | 0.377808E+09 |
Maximum of Months | 0.204815E+10 | 0.141627E+10 | 0.945063E+09 | 0.235641E+10 | 0.178283E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559591E+09 | 0.225519E+09 | 0.334072E+09 | 0.274550E+09 | 0.231277E+10 |
February | 0.862705E+09 | 0.424063E+09 | 0.438642E+09 | 0.628694E+09 | 0.158474E+10 |
March | 0.122234E+10 | 0.447885E+09 | 0.774459E+09 | 0.924927E+09 | 0.151189E+10 |
April | 0.154430E+10 | 0.684197E+09 | 0.860104E+09 | 0.144584E+10 | 0.111123E+10 |
May | 0.197386E+10 | 0.900187E+09 | 0.107368E+10 | 0.208488E+10 | 0.837942E+09 |
June | 0.207821E+10 | 0.954601E+09 | 0.112361E+10 | 0.245505E+10 | 0.557122E+09 |
July | 0.219986E+10 | 0.111162E+10 | 0.108824E+10 | 0.281971E+10 | 0.482499E+09 |
August | 0.186798E+10 | 0.916764E+09 | 0.951214E+09 | 0.231159E+10 | 0.543694E+09 |
September | 0.145420E+10 | 0.735184E+09 | 0.719015E+09 | 0.166755E+10 | 0.712156E+09 |
October | 0.107400E+10 | 0.533611E+09 | 0.540386E+09 | 0.100438E+10 | 0.111802E+10 |
November | 0.735763E+09 | 0.365001E+09 | 0.370762E+09 | 0.538352E+09 | 0.151594E+10 |
December | 0.511052E+09 | 0.215701E+09 | 0.295352E+09 | 0.244940E+09 | 0.213071E+10 |
Annual Sum or Average | 0.160839E+11 | 0.751434E+10 | 0.856953E+10 | 0.164005E+11 | 0.144187E+11 |
Minimum of Months | 0.511052E+09 | 0.215701E+09 | 0.295352E+09 | 0.244940E+09 | 0.482499E+09 |
Maximum of Months | 0.219986E+10 | 0.111162E+10 | 0.112361E+10 | 0.281971E+10 | 0.231277E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559591E+09 | 0.225519E+09 | 0.334072E+09 | 0.274550E+09 | 0.231277E+10 |
February | 0.862705E+09 | 0.424063E+09 | 0.438642E+09 | 0.628694E+09 | 0.158474E+10 |
March | 0.122234E+10 | 0.447885E+09 | 0.774459E+09 | 0.924927E+09 | 0.151189E+10 |
April | 0.154430E+10 | 0.684197E+09 | 0.860104E+09 | 0.144584E+10 | 0.111123E+10 |
May | 0.197386E+10 | 0.900187E+09 | 0.107368E+10 | 0.208488E+10 | 0.837942E+09 |
June | 0.207821E+10 | 0.954601E+09 | 0.112361E+10 | 0.245505E+10 | 0.557122E+09 |
July | 0.219986E+10 | 0.111162E+10 | 0.108824E+10 | 0.281971E+10 | 0.482499E+09 |
August | 0.186798E+10 | 0.916764E+09 | 0.951214E+09 | 0.231159E+10 | 0.543694E+09 |
September | 0.145420E+10 | 0.735184E+09 | 0.719015E+09 | 0.166755E+10 | 0.712156E+09 |
October | 0.107400E+10 | 0.533611E+09 | 0.540386E+09 | 0.100438E+10 | 0.111802E+10 |
November | 0.735763E+09 | 0.365001E+09 | 0.370762E+09 | 0.538352E+09 | 0.151594E+10 |
December | 0.511052E+09 | 0.215701E+09 | 0.295352E+09 | 0.244940E+09 | 0.213071E+10 |
Annual Sum or Average | 0.160839E+11 | 0.751434E+10 | 0.856953E+10 | 0.164005E+11 | 0.144187E+11 |
Minimum of Months | 0.511052E+09 | 0.215701E+09 | 0.295352E+09 | 0.244940E+09 | 0.482499E+09 |
Maximum of Months | 0.219986E+10 | 0.111162E+10 | 0.112361E+10 | 0.281971E+10 | 0.231277E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559581E+09 | 0.225515E+09 | 0.334066E+09 | 0.274545E+09 | 0.231272E+10 |
February | 0.862689E+09 | 0.424056E+09 | 0.438634E+09 | 0.628683E+09 | 0.158471E+10 |
March | 0.122232E+10 | 0.447877E+09 | 0.774445E+09 | 0.924910E+09 | 0.151186E+10 |
April | 0.154427E+10 | 0.684184E+09 | 0.860088E+09 | 0.144581E+10 | 0.111121E+10 |
May | 0.197383E+10 | 0.900170E+09 | 0.107366E+10 | 0.208484E+10 | 0.837926E+09 |
June | 0.207817E+10 | 0.954583E+09 | 0.112359E+10 | 0.245501E+10 | 0.557111E+09 |
July | 0.219982E+10 | 0.111160E+10 | 0.108822E+10 | 0.281966E+10 | 0.482490E+09 |
August | 0.186794E+10 | 0.916748E+09 | 0.951197E+09 | 0.231155E+10 | 0.543684E+09 |
September | 0.145417E+10 | 0.735170E+09 | 0.719002E+09 | 0.166752E+10 | 0.712143E+09 |
October | 0.107398E+10 | 0.533602E+09 | 0.540376E+09 | 0.100436E+10 | 0.111800E+10 |
November | 0.735749E+09 | 0.364994E+09 | 0.370755E+09 | 0.538342E+09 | 0.151591E+10 |
December | 0.511043E+09 | 0.215697E+09 | 0.295346E+09 | 0.244936E+09 | 0.213067E+10 |
Annual Sum or Average | 0.160836E+11 | 0.751420E+10 | 0.856937E+10 | 0.164002E+11 | 0.144184E+11 |
Minimum of Months | 0.511043E+09 | 0.215697E+09 | 0.295346E+09 | 0.244936E+09 | 0.482490E+09 |
Maximum of Months | 0.219982E+10 | 0.111160E+10 | 0.112359E+10 | 0.281966E+10 | 0.231272E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121069E+10 | 0.00 | 0.121069E+10 | 41869899.32 | 0.999314E+10 |
February | 0.154399E+10 | 0.00 | 0.154399E+10 | 0.287706E+09 | 0.665340E+10 |
March | 0.277688E+10 | 0.00 | 0.277688E+10 | 0.101803E+10 | 0.593033E+10 |
April | 0.306410E+10 | 17881386.28 | 0.304622E+10 | 0.167392E+10 | 0.407108E+10 |
May | 0.415802E+10 | 0.246389E+09 | 0.391163E+10 | 0.313847E+10 | 0.313861E+10 |
June | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.481362E+10 | 0.196808E+10 |
July | 0.442324E+10 | 0.414289E+09 | 0.400895E+10 | 0.539375E+10 | 0.169738E+10 |
August | 0.354436E+10 | 95005459.17 | 0.344936E+10 | 0.392917E+10 | 0.193794E+10 |
September | 0.256885E+10 | 921843.89 | 0.256793E+10 | 0.224942E+10 | 0.283030E+10 |
October | 0.193629E+10 | 0.00 | 0.193629E+10 | 0.926435E+09 | 0.431917E+10 |
November | 0.127385E+10 | 0.00 | 0.127385E+10 | 0.222386E+09 | 0.598501E+10 |
December | 0.101523E+10 | 0.00 | 0.101523E+10 | 22179672.85 | 0.851669E+10 |
Annual Sum or Average | 0.322011E+11 | 0.131306E+10 | 0.308881E+11 | 0.237170E+11 | 0.570411E+11 |
Minimum of Months | 0.101523E+10 | 0.00 | 0.101523E+10 | 22179672.85 | 0.169738E+10 |
Maximum of Months | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.539375E+10 | 0.999314E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185337E+10 | 0.849694E+09 | 0.100367E+10 | 0.996365E+09 | 0.614268E+10 |
February | 0.261830E+10 | 0.129992E+10 | 0.131838E+10 | 0.198477E+10 | 0.409077E+10 |
March | 0.389774E+10 | 0.161278E+10 | 0.228496E+10 | 0.320958E+10 | 0.373474E+10 |
April | 0.481271E+10 | 0.238514E+10 | 0.242757E+10 | 0.467118E+10 | 0.260400E+10 |
May | 0.549347E+10 | 0.244425E+10 | 0.304922E+10 | 0.571102E+10 | 0.209874E+10 |
June | 0.688122E+10 | 0.354107E+10 | 0.334015E+10 | 0.819933E+10 | 0.133751E+10 |
July | 0.746276E+10 | 0.421890E+10 | 0.324386E+10 | 0.958580E+10 | 0.113187E+10 |
August | 0.648547E+10 | 0.361351E+10 | 0.287197E+10 | 0.813773E+10 | 0.127356E+10 |
September | 0.443984E+10 | 0.229183E+10 | 0.214801E+10 | 0.507591E+10 | 0.177466E+10 |
October | 0.329153E+10 | 0.167139E+10 | 0.162014E+10 | 0.315085E+10 | 0.270419E+10 |
November | 0.201882E+10 | 0.942522E+09 | 0.107629E+10 | 0.142272E+10 | 0.365437E+10 |
December | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.785192E+09 | 0.522563E+10 |
Annual Sum or Average | 0.507939E+11 | 0.255318E+11 | 0.252620E+11 | 0.529304E+11 | 0.357727E+11 |
Minimum of Months | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.785192E+09 | 0.113187E+10 |
Maximum of Months | 0.746276E+10 | 0.421890E+10 | 0.334015E+10 | 0.958580E+10 | 0.614268E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.853404E+10 | 0.609518E+10 | 0.243886E+10 | 0.791633E+10 | 0.871674E+10 |
February | 0.981623E+10 | 0.706020E+10 | 0.275603E+10 | 0.100053E+11 | 0.595349E+10 |
March | 0.971455E+10 | 0.545524E+10 | 0.425930E+10 | 0.987506E+10 | 0.589361E+10 |
April | 0.755697E+10 | 0.361455E+10 | 0.394242E+10 | 0.798910E+10 | 0.425008E+10 |
May | 0.693798E+10 | 0.230429E+10 | 0.463369E+10 | 0.748399E+10 | 0.343176E+10 |
June | 0.667121E+10 | 0.194564E+10 | 0.472556E+10 | 0.822733E+10 | 0.226915E+10 |
July | 0.743197E+10 | 0.274535E+10 | 0.468662E+10 | 0.102171E+11 | 0.187648E+10 |
August | 0.883241E+10 | 0.445314E+10 | 0.437927E+10 | 0.117556E+11 | 0.212796E+10 |
September | 0.948020E+10 | 0.580882E+10 | 0.367137E+10 | 0.116717E+11 | 0.294546E+10 |
October | 0.102414E+11 | 0.708180E+10 | 0.315960E+10 | 0.115606E+11 | 0.431821E+10 |
November | 0.903593E+10 | 0.654527E+10 | 0.249067E+10 | 0.930836E+10 | 0.539146E+10 |
December | 0.811539E+10 | 0.586013E+10 | 0.225526E+10 | 0.772703E+10 | 0.740869E+10 |
Annual Sum or Average | 0.102368E+12 | 0.589696E+11 | 0.433987E+11 | 0.113737E+12 | 0.545831E+11 |
Minimum of Months | 0.667121E+10 | 0.194564E+10 | 0.225526E+10 | 0.748399E+10 | 0.187648E+10 |
Maximum of Months | 0.102414E+11 | 0.708180E+10 | 0.472556E+10 | 0.117556E+11 | 0.871674E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167876E+10 | 0.676552E+09 | 0.100221E+10 | 0.862497E+09 | 0.648415E+10 |
February | 0.258809E+10 | 0.127218E+10 | 0.131591E+10 | 0.199136E+10 | 0.428075E+10 |
March | 0.366700E+10 | 0.134364E+10 | 0.232335E+10 | 0.294418E+10 | 0.398307E+10 |
April | 0.463285E+10 | 0.205257E+10 | 0.258029E+10 | 0.452760E+10 | 0.284145E+10 |
May | 0.592153E+10 | 0.270053E+10 | 0.322099E+10 | 0.633327E+10 | 0.230774E+10 |
June | 0.623457E+10 | 0.286377E+10 | 0.337080E+10 | 0.745126E+10 | 0.153879E+10 |
July | 0.659951E+10 | 0.333483E+10 | 0.326468E+10 | 0.855434E+10 | 0.133619E+10 |
August | 0.560388E+10 | 0.275026E+10 | 0.285361E+10 | 0.706896E+10 | 0.144186E+10 |
September | 0.436255E+10 | 0.220553E+10 | 0.215702E+10 | 0.507161E+10 | 0.195519E+10 |
October | 0.322196E+10 | 0.160082E+10 | 0.162114E+10 | 0.315497E+10 | 0.292463E+10 |
November | 0.220727E+10 | 0.109499E+10 | 0.111227E+10 | 0.174199E+10 | 0.389151E+10 |
December | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.827943E+09 | 0.548703E+10 |
Annual Sum or Average | 0.482511E+11 | 0.225428E+11 | 0.257083E+11 | 0.505300E+11 | 0.384724E+11 |
Minimum of Months | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.827943E+09 | 0.133619E+10 |
Maximum of Months | 0.659951E+10 | 0.333483E+10 | 0.337080E+10 | 0.855434E+10 | 0.648415E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121069E+10 | 0.00 | 0.121069E+10 | 59255395.68 | 0.963816E+10 |
February | 0.154399E+10 | 0.00 | 0.154399E+10 | 0.341519E+09 | 0.633575E+10 |
March | 0.277688E+10 | 0.00 | 0.277688E+10 | 0.111422E+10 | 0.557768E+10 |
April | 0.306410E+10 | 17881386.28 | 0.304622E+10 | 0.180800E+10 | 0.374749E+10 |
May | 0.415802E+10 | 0.246389E+09 | 0.391163E+10 | 0.324491E+10 | 0.293009E+10 |
June | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.486343E+10 | 0.189875E+10 |
July | 0.442324E+10 | 0.414289E+09 | 0.400895E+10 | 0.540530E+10 | 0.166410E+10 |
August | 0.354436E+10 | 95005459.17 | 0.344936E+10 | 0.395636E+10 | 0.187003E+10 |
September | 0.256885E+10 | 921843.89 | 0.256793E+10 | 0.232325E+10 | 0.264072E+10 |
October | 0.193629E+10 | 0.00 | 0.193629E+10 | 0.105730E+10 | 0.391679E+10 |
November | 0.127385E+10 | 0.00 | 0.127385E+10 | 0.274128E+09 | 0.552533E+10 |
December | 0.101523E+10 | 0.00 | 0.101523E+10 | 28789739.25 | 0.813653E+10 |
Annual Sum or Average | 0.322011E+11 | 0.131306E+10 | 0.308881E+11 | 0.244765E+11 | 0.538814E+11 |
Minimum of Months | 0.101523E+10 | 0.00 | 0.101523E+10 | 28789739.25 | 0.166410E+10 |
Maximum of Months | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.540530E+10 | 0.963816E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185337E+10 | 0.849694E+09 | 0.100367E+10 | 0.102873E+10 | 0.592569E+10 |
February | 0.261830E+10 | 0.129992E+10 | 0.131838E+10 | 0.204401E+10 | 0.390070E+10 |
March | 0.389774E+10 | 0.161278E+10 | 0.228496E+10 | 0.328483E+10 | 0.352986E+10 |
April | 0.481271E+10 | 0.238514E+10 | 0.242757E+10 | 0.473994E+10 | 0.243472E+10 |
May | 0.549347E+10 | 0.244425E+10 | 0.304922E+10 | 0.574402E+10 | 0.199043E+10 |
June | 0.688122E+10 | 0.354107E+10 | 0.334015E+10 | 0.819451E+10 | 0.131459E+10 |
July | 0.746276E+10 | 0.421890E+10 | 0.324386E+10 | 0.956304E+10 | 0.112814E+10 |
August | 0.648547E+10 | 0.361351E+10 | 0.287197E+10 | 0.812366E+10 | 0.125685E+10 |
September | 0.443984E+10 | 0.229183E+10 | 0.214801E+10 | 0.509591E+10 | 0.169954E+10 |
October | 0.329153E+10 | 0.167139E+10 | 0.162014E+10 | 0.323873E+10 | 0.249382E+10 |
November | 0.201882E+10 | 0.942522E+09 | 0.107629E+10 | 0.148891E+10 | 0.339118E+10 |
December | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.814236E+09 | 0.499397E+10 |
Annual Sum or Average | 0.507939E+11 | 0.255318E+11 | 0.252620E+11 | 0.533605E+11 | 0.340595E+11 |
Minimum of Months | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.814236E+09 | 0.112814E+10 |
Maximum of Months | 0.746276E+10 | 0.421890E+10 | 0.334015E+10 | 0.956304E+10 | 0.592569E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.853404E+10 | 0.609518E+10 | 0.243886E+10 | 0.801925E+10 | 0.833798E+10 |
February | 0.981623E+10 | 0.706020E+10 | 0.275603E+10 | 0.101126E+11 | 0.563292E+10 |
March | 0.971455E+10 | 0.545524E+10 | 0.425930E+10 | 0.997606E+10 | 0.555047E+10 |
April | 0.755697E+10 | 0.361455E+10 | 0.394242E+10 | 0.808368E+10 | 0.396049E+10 |
May | 0.693798E+10 | 0.230429E+10 | 0.463369E+10 | 0.753390E+10 | 0.323899E+10 |
June | 0.667121E+10 | 0.194564E+10 | 0.472556E+10 | 0.823388E+10 | 0.220600E+10 |
July | 0.743197E+10 | 0.274535E+10 | 0.468662E+10 | 0.101998E+11 | 0.185105E+10 |
August | 0.883241E+10 | 0.445314E+10 | 0.437927E+10 | 0.117411E+11 | 0.208161E+10 |
September | 0.948020E+10 | 0.580882E+10 | 0.367137E+10 | 0.116951E+11 | 0.280748E+10 |
October | 0.102414E+11 | 0.708180E+10 | 0.315960E+10 | 0.116677E+11 | 0.398572E+10 |
November | 0.903593E+10 | 0.654527E+10 | 0.249067E+10 | 0.945961E+10 | 0.498105E+10 |
December | 0.811539E+10 | 0.586013E+10 | 0.225526E+10 | 0.783793E+10 | 0.702929E+10 |
Annual Sum or Average | 0.102368E+12 | 0.589696E+11 | 0.433987E+11 | 0.114561E+12 | 0.516630E+11 |
Minimum of Months | 0.667121E+10 | 0.194564E+10 | 0.225526E+10 | 0.753390E+10 | 0.185105E+10 |
Maximum of Months | 0.102414E+11 | 0.708180E+10 | 0.472556E+10 | 0.117411E+11 | 0.833798E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167876E+10 | 0.676552E+09 | 0.100221E+10 | 0.884871E+09 | 0.625798E+10 |
February | 0.258809E+10 | 0.127218E+10 | 0.131591E+10 | 0.202600E+10 | 0.409397E+10 |
March | 0.366700E+10 | 0.134364E+10 | 0.232335E+10 | 0.298628E+10 | 0.378639E+10 |
April | 0.463285E+10 | 0.205257E+10 | 0.258029E+10 | 0.457955E+10 | 0.267254E+10 |
May | 0.592153E+10 | 0.270053E+10 | 0.322099E+10 | 0.635889E+10 | 0.219090E+10 |
June | 0.623457E+10 | 0.286377E+10 | 0.337080E+10 | 0.745184E+10 | 0.150252E+10 |
July | 0.659951E+10 | 0.333483E+10 | 0.326468E+10 | 0.854337E+10 | 0.132098E+10 |
August | 0.560388E+10 | 0.275026E+10 | 0.285361E+10 | 0.706640E+10 | 0.141279E+10 |
September | 0.436255E+10 | 0.220553E+10 | 0.215702E+10 | 0.508871E+10 | 0.186883E+10 |
October | 0.322196E+10 | 0.160082E+10 | 0.162114E+10 | 0.321099E+10 | 0.272107E+10 |
November | 0.220727E+10 | 0.109499E+10 | 0.111227E+10 | 0.178495E+10 | 0.364207E+10 |
December | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.847004E+09 | 0.526337E+10 |
Annual Sum or Average | 0.482511E+11 | 0.225428E+11 | 0.257083E+11 | 0.508289E+11 | 0.367334E+11 |
Minimum of Months | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.847004E+09 | 0.132098E+10 |
Maximum of Months | 0.659951E+10 | 0.333483E+10 | 0.337080E+10 | 0.854337E+10 | 0.625798E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.50 | 3965.33 | 452.01 | 0.00 | 452.01 | 0.00 | 0.00 |
February | 77.95 | 2988.64 | 638.21 | 0.00 | 638.21 | 0.00 | 0.00 |
March | 312.63 | 2436.05 | 1036.75 | 0.00 | 1036.75 | 0.00 | 0.00 |
April | 577.04 | 1750.18 | 1182.12 | 6.90 | 1175.22 | 0.00 | 0.00 |
May | 1126.77 | 1264.07 | 1552.40 | 91.99 | 1460.41 | 0.00 | 0.00 |
June | 1832.82 | 792.17 | 1807.68 | 207.78 | 1599.91 | 0.00 | 0.00 |
July | 1991.83 | 652.08 | 1651.42 | 154.67 | 1496.75 | 0.00 | 0.00 |
August | 1440.68 | 754.27 | 1323.29 | 35.47 | 1287.82 | 0.00 | 0.00 |
September | 837.15 | 1172.99 | 991.05 | 0.36 | 990.70 | 0.00 | 0.00 |
October | 291.98 | 1800.29 | 722.92 | 0.00 | 722.92 | 0.00 | 0.00 |
November | 57.76 | 2608.89 | 491.44 | 0.00 | 491.44 | 0.00 | 0.00 |
December | 2.47 | 3538.81 | 379.04 | 0.00 | 379.04 | 0.00 | 0.00 |
Annual Sum or Average | 717.03 | 1973.00 | 1021.07 | 41.64 | 979.44 | 0.00 | 0.00 |
Minimum of Months | 2.47 | 652.08 | 379.04 | 0.00 | 379.04 | 0.00 | 0.00 |
Maximum of Months | 1991.83 | 3965.33 | 1807.68 | 207.78 | 1599.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 356.06 | 2411.39 | 691.97 | 317.24 | 374.73 | 0.00 | 0.00 |
February | 792.10 | 1801.56 | 1082.30 | 537.34 | 544.97 | 0.00 | 0.00 |
March | 1169.59 | 1488.13 | 1455.26 | 602.14 | 853.11 | 0.00 | 0.00 |
April | 1785.26 | 1069.84 | 1856.76 | 920.20 | 936.56 | 0.00 | 0.00 |
May | 2124.46 | 832.77 | 2051.04 | 912.58 | 1138.45 | 0.00 | 0.00 |
June | 3173.67 | 526.26 | 2654.80 | 1366.16 | 1288.64 | 0.00 | 0.00 |
July | 3594.47 | 415.26 | 2786.29 | 1575.16 | 1211.13 | 0.00 | 0.00 |
August | 3052.30 | 463.98 | 2421.41 | 1349.13 | 1072.27 | 0.00 | 0.00 |
September | 1954.37 | 718.89 | 1712.91 | 884.20 | 828.71 | 0.00 | 0.00 |
October | 1151.03 | 1091.43 | 1228.92 | 624.03 | 604.89 | 0.00 | 0.00 |
November | 521.99 | 1536.49 | 778.87 | 363.63 | 415.24 | 0.00 | 0.00 |
December | 273.14 | 2111.57 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Annual Sum or Average | 1667.37 | 1203.39 | 1610.67 | 809.61 | 801.06 | 0.00 | 0.00 |
Minimum of Months | 273.14 | 415.26 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Maximum of Months | 3594.47 | 2411.39 | 2786.29 | 1575.16 | 1288.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2957.62 | 3328.27 | 3186.14 | 2275.60 | 910.54 | 0.00 | 0.00 |
February | 4143.87 | 2541.33 | 4057.51 | 2918.31 | 1139.20 | 0.00 | 0.00 |
March | 3691.10 | 2283.22 | 3626.89 | 2036.69 | 1590.20 | 0.00 | 0.00 |
April | 3078.79 | 1717.50 | 2915.42 | 1394.46 | 1520.96 | 0.00 | 0.00 |
May | 2796.62 | 1330.29 | 2590.28 | 860.30 | 1729.98 | 0.00 | 0.00 |
June | 3176.25 | 898.17 | 2573.71 | 750.61 | 1823.10 | 0.00 | 0.00 |
July | 3818.42 | 705.31 | 2774.71 | 1024.96 | 1749.75 | 0.00 | 0.00 |
August | 4399.05 | 798.12 | 3297.56 | 1662.56 | 1635.00 | 0.00 | 0.00 |
September | 4529.04 | 1161.53 | 3657.38 | 2240.99 | 1416.39 | 0.00 | 0.00 |
October | 4330.83 | 1668.70 | 3823.59 | 2643.96 | 1179.63 | 0.00 | 0.00 |
November | 3585.55 | 2171.57 | 3485.98 | 2525.10 | 960.88 | 0.00 | 0.00 |
December | 2860.15 | 2909.27 | 3029.84 | 2187.85 | 841.99 | 0.00 | 0.00 |
Annual Sum or Average | 3609.82 | 1789.97 | 3245.98 | 1869.85 | 1376.13 | 0.00 | 0.00 |
Minimum of Months | 2796.62 | 705.31 | 2573.71 | 750.61 | 841.99 | 0.00 | 0.00 |
Maximum of Months | 4529.04 | 3328.27 | 4057.51 | 2918.31 | 1823.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 307.51 | 2590.45 | 626.78 | 252.60 | 374.18 | 0.00 | 0.00 |
February | 779.63 | 1965.20 | 1069.82 | 525.87 | 543.95 | 0.00 | 0.00 |
March | 1035.98 | 1693.41 | 1369.10 | 501.66 | 867.44 | 0.00 | 0.00 |
April | 1673.42 | 1286.14 | 1787.37 | 791.89 | 995.48 | 0.00 | 0.00 |
May | 2335.20 | 938.55 | 2210.85 | 1008.27 | 1202.59 | 0.00 | 0.00 |
June | 2841.48 | 644.81 | 2405.32 | 1104.86 | 1300.47 | 0.00 | 0.00 |
July | 3158.26 | 540.43 | 2463.99 | 1245.09 | 1218.90 | 0.00 | 0.00 |
August | 2589.13 | 608.97 | 2092.26 | 1026.84 | 1065.42 | 0.00 | 0.00 |
September | 1930.02 | 824.25 | 1683.09 | 850.90 | 832.19 | 0.00 | 0.00 |
October | 1124.97 | 1252.26 | 1202.95 | 597.68 | 605.27 | 0.00 | 0.00 |
November | 623.09 | 1754.55 | 851.57 | 422.45 | 429.12 | 0.00 | 0.00 |
December | 274.35 | 2386.53 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Annual Sum or Average | 1560.16 | 1371.63 | 1530.04 | 714.83 | 815.21 | 0.00 | 0.00 |
Minimum of Months | 274.35 | 540.43 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Maximum of Months | 3158.26 | 2590.45 | 2463.99 | 1245.09 | 1300.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15.63 | 3731.01 | 452.02 | 0.00 | 452.02 | 0.00 | 0.00 |
February | 118.93 | 2750.25 | 638.23 | 0.00 | 638.23 | 0.00 | 0.00 |
March | 380.09 | 2214.13 | 1036.77 | 0.00 | 1036.77 | 0.00 | 0.00 |
April | 645.80 | 1570.63 | 1182.14 | 6.90 | 1175.24 | 0.00 | 0.00 |
May | 1171.77 | 1171.82 | 1552.43 | 91.99 | 1460.44 | 0.00 | 0.00 |
June | 1857.11 | 759.29 | 1807.72 | 207.78 | 1599.93 | 0.00 | 0.00 |
July | 2013.80 | 633.73 | 1651.45 | 154.68 | 1496.77 | 0.00 | 0.00 |
August | 1466.98 | 723.54 | 1323.31 | 35.47 | 1287.84 | 0.00 | 0.00 |
September | 867.83 | 1091.94 | 991.07 | 0.36 | 990.71 | 0.00 | 0.00 |
October | 345.89 | 1612.59 | 722.93 | 0.00 | 722.93 | 0.00 | 0.00 |
November | 85.80 | 2309.03 | 491.45 | 0.00 | 491.45 | 0.00 | 0.00 |
December | 8.28 | 3179.77 | 379.05 | 0.00 | 379.05 | 0.00 | 0.00 |
Annual Sum or Average | 752.06 | 1808.76 | 1021.09 | 41.64 | 979.45 | 0.00 | 0.00 |
Minimum of Months | 8.28 | 633.73 | 379.05 | 0.00 | 379.05 | 0.00 | 0.00 |
Maximum of Months | 2013.80 | 3731.01 | 1807.72 | 207.78 | 1599.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 372.00 | 2293.42 | 691.97 | 317.24 | 374.73 | 0.00 | 0.00 |
February | 820.42 | 1690.96 | 1082.30 | 537.34 | 544.96 | 0.00 | 0.00 |
March | 1198.32 | 1394.39 | 1455.25 | 602.14 | 853.11 | 0.00 | 0.00 |
April | 1802.15 | 1004.63 | 1856.76 | 920.19 | 936.56 | 0.00 | 0.00 |
May | 2132.25 | 783.58 | 2051.03 | 912.58 | 1138.45 | 0.00 | 0.00 |
June | 3163.32 | 516.02 | 2654.79 | 1366.15 | 1288.64 | 0.00 | 0.00 |
July | 3578.93 | 422.59 | 2786.28 | 1575.16 | 1211.12 | 0.00 | 0.00 |
August | 3038.28 | 475.49 | 2421.40 | 1349.13 | 1072.27 | 0.00 | 0.00 |
September | 1958.30 | 684.67 | 1712.90 | 884.19 | 828.71 | 0.00 | 0.00 |
October | 1176.39 | 1009.63 | 1228.92 | 624.03 | 604.89 | 0.00 | 0.00 |
November | 548.89 | 1409.87 | 778.86 | 363.63 | 415.24 | 0.00 | 0.00 |
December | 293.16 | 1951.03 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Annual Sum or Average | 1678.41 | 1134.35 | 1610.66 | 809.61 | 801.05 | 0.00 | 0.00 |
Minimum of Months | 293.16 | 422.59 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Maximum of Months | 3578.93 | 2293.42 | 2786.28 | 1575.16 | 1288.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2955.62 | 3254.46 | 3186.24 | 2275.68 | 910.56 | 0.00 | 0.00 |
February | 4135.80 | 2460.93 | 4057.63 | 2918.40 | 1139.23 | 0.00 | 0.00 |
March | 3686.92 | 2200.42 | 3627.00 | 2036.75 | 1590.24 | 0.00 | 0.00 |
April | 3082.21 | 1639.69 | 2915.50 | 1394.50 | 1521.00 | 0.00 | 0.00 |
May | 2794.20 | 1281.27 | 2590.34 | 860.32 | 1730.02 | 0.00 | 0.00 |
June | 3174.12 | 875.44 | 2573.77 | 750.63 | 1823.13 | 0.00 | 0.00 |
July | 3814.63 | 700.60 | 2774.78 | 1025.00 | 1749.79 | 0.00 | 0.00 |
August | 4389.02 | 794.49 | 3297.64 | 1662.61 | 1635.03 | 0.00 | 0.00 |
September | 4502.97 | 1136.37 | 3657.48 | 2241.06 | 1416.43 | 0.00 | 0.00 |
October | 4316.23 | 1612.24 | 3823.70 | 2644.04 | 1179.66 | 0.00 | 0.00 |
November | 3591.19 | 2080.04 | 3486.08 | 2525.18 | 960.91 | 0.00 | 0.00 |
December | 2884.94 | 2766.09 | 3029.94 | 2187.92 | 842.02 | 0.00 | 0.00 |
Annual Sum or Average | 3606.59 | 1730.82 | 3246.08 | 1869.91 | 1376.16 | 0.00 | 0.00 |
Minimum of Months | 2794.20 | 700.60 | 2573.77 | 750.63 | 842.02 | 0.00 | 0.00 |
Maximum of Months | 4502.97 | 3254.46 | 4057.63 | 2918.40 | 1823.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.02 | 2420.90 | 626.78 | 252.60 | 374.18 | 0.00 | 0.00 |
February | 823.15 | 1769.49 | 1069.81 | 525.87 | 543.95 | 0.00 | 0.00 |
March | 1099.23 | 1487.11 | 1369.10 | 501.66 | 867.44 | 0.00 | 0.00 |
April | 1746.76 | 1096.24 | 1787.37 | 791.89 | 995.48 | 0.00 | 0.00 |
May | 2364.57 | 861.61 | 2210.84 | 1008.26 | 1202.58 | 0.00 | 0.00 |
June | 2874.72 | 593.67 | 2405.31 | 1104.85 | 1300.46 | 0.00 | 0.00 |
July | 3193.82 | 498.88 | 2463.98 | 1245.08 | 1218.89 | 0.00 | 0.00 |
August | 2639.25 | 538.33 | 2092.25 | 1026.83 | 1065.42 | 0.00 | 0.00 |
September | 1956.64 | 754.32 | 1683.08 | 850.90 | 832.18 | 0.00 | 0.00 |
October | 1177.93 | 1091.93 | 1202.94 | 597.68 | 605.26 | 0.00 | 0.00 |
November | 672.06 | 1501.35 | 851.57 | 422.45 | 429.12 | 0.00 | 0.00 |
December | 309.12 | 2048.62 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Annual Sum or Average | 1602.30 | 1219.95 | 1530.03 | 714.83 | 815.21 | 0.00 | 0.00 |
Minimum of Months | 309.12 | 498.88 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Maximum of Months | 3193.82 | 2420.90 | 2463.98 | 1245.08 | 1300.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.12 | 3598.48 | 452.02 | 0.00 | 452.02 | 0.00 | 0.00 |
February | 141.17 | 2618.94 | 638.23 | 0.00 | 638.23 | 0.00 | 0.00 |
March | 416.00 | 2082.47 | 1036.77 | 0.00 | 1036.77 | 0.00 | 0.00 |
April | 697.53 | 1445.79 | 1182.14 | 6.90 | 1175.24 | 0.00 | 0.00 |
May | 1211.51 | 1093.97 | 1552.43 | 91.99 | 1460.44 | 0.00 | 0.00 |
June | 1876.32 | 732.54 | 1807.72 | 207.78 | 1599.93 | 0.00 | 0.00 |
July | 2018.11 | 621.30 | 1651.45 | 154.68 | 1496.77 | 0.00 | 0.00 |
August | 1477.13 | 698.19 | 1323.31 | 35.47 | 1287.84 | 0.00 | 0.00 |
September | 896.32 | 1018.79 | 991.07 | 0.36 | 990.71 | 0.00 | 0.00 |
October | 394.75 | 1462.36 | 722.93 | 0.00 | 722.93 | 0.00 | 0.00 |
November | 105.76 | 2131.69 | 491.45 | 0.00 | 491.45 | 0.00 | 0.00 |
December | 10.75 | 3037.83 | 379.05 | 0.00 | 379.05 | 0.00 | 0.00 |
Annual Sum or Average | 776.14 | 1708.57 | 1021.09 | 41.64 | 979.45 | 0.00 | 0.00 |
Minimum of Months | 10.75 | 621.30 | 379.05 | 0.00 | 379.05 | 0.00 | 0.00 |
Maximum of Months | 2018.11 | 3598.48 | 1807.72 | 207.78 | 1599.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 384.08 | 2212.40 | 691.97 | 317.24 | 374.73 | 0.00 | 0.00 |
February | 844.91 | 1612.39 | 1082.30 | 537.34 | 544.96 | 0.00 | 0.00 |
March | 1226.41 | 1317.90 | 1455.25 | 602.14 | 853.11 | 0.00 | 0.00 |
April | 1828.68 | 939.32 | 1856.76 | 920.19 | 936.56 | 0.00 | 0.00 |
May | 2144.57 | 743.14 | 2051.03 | 912.58 | 1138.45 | 0.00 | 0.00 |
June | 3161.46 | 507.17 | 2654.79 | 1366.15 | 1288.64 | 0.00 | 0.00 |
July | 3570.43 | 421.20 | 2786.28 | 1575.16 | 1211.12 | 0.00 | 0.00 |
August | 3033.03 | 469.25 | 2421.40 | 1349.13 | 1072.27 | 0.00 | 0.00 |
September | 1966.01 | 655.69 | 1712.90 | 884.19 | 828.71 | 0.00 | 0.00 |
October | 1209.20 | 931.08 | 1228.92 | 624.03 | 604.89 | 0.00 | 0.00 |
November | 574.42 | 1308.33 | 778.86 | 363.63 | 415.24 | 0.00 | 0.00 |
December | 304.00 | 1864.53 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Annual Sum or Average | 1692.05 | 1080.02 | 1610.66 | 809.61 | 801.05 | 0.00 | 0.00 |
Minimum of Months | 304.00 | 421.20 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Maximum of Months | 3570.43 | 2212.40 | 2786.28 | 1575.16 | 1288.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2994.04 | 3113.04 | 3186.24 | 2275.68 | 910.56 | 0.00 | 0.00 |
February | 4180.14 | 2328.42 | 4057.63 | 2918.40 | 1139.23 | 0.00 | 0.00 |
March | 3724.64 | 2072.31 | 3627.00 | 2036.75 | 1590.24 | 0.00 | 0.00 |
April | 3118.71 | 1527.97 | 2915.50 | 1394.50 | 1521.00 | 0.00 | 0.00 |
May | 2812.84 | 1209.30 | 2590.34 | 860.32 | 1730.02 | 0.00 | 0.00 |
June | 3176.65 | 851.08 | 2573.77 | 750.63 | 1823.13 | 0.00 | 0.00 |
July | 3808.16 | 691.10 | 2774.78 | 1025.00 | 1749.79 | 0.00 | 0.00 |
August | 4383.62 | 777.19 | 3297.64 | 1662.61 | 1635.03 | 0.00 | 0.00 |
September | 4511.98 | 1083.13 | 3657.48 | 2241.06 | 1416.43 | 0.00 | 0.00 |
October | 4356.22 | 1488.10 | 3823.70 | 2644.04 | 1179.66 | 0.00 | 0.00 |
November | 3649.54 | 1921.70 | 3486.08 | 2525.18 | 960.91 | 0.00 | 0.00 |
December | 2926.35 | 2624.44 | 3029.94 | 2187.92 | 842.02 | 0.00 | 0.00 |
Annual Sum or Average | 3632.69 | 1638.22 | 3246.08 | 1869.91 | 1376.16 | 0.00 | 0.00 |
Minimum of Months | 2812.84 | 691.10 | 2573.77 | 750.63 | 842.02 | 0.00 | 0.00 |
Maximum of Months | 4511.98 | 3113.04 | 4057.63 | 2918.40 | 1823.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 330.37 | 2336.46 | 626.78 | 252.60 | 374.18 | 0.00 | 0.00 |
February | 837.47 | 1692.28 | 1069.81 | 525.87 | 543.95 | 0.00 | 0.00 |
March | 1114.95 | 1413.68 | 1369.10 | 501.66 | 867.44 | 0.00 | 0.00 |
April | 1766.80 | 1031.07 | 1787.37 | 791.89 | 995.48 | 0.00 | 0.00 |
May | 2374.14 | 817.99 | 2210.84 | 1008.26 | 1202.58 | 0.00 | 0.00 |
June | 2874.94 | 579.68 | 2405.31 | 1104.85 | 1300.46 | 0.00 | 0.00 |
July | 3189.73 | 493.20 | 2463.98 | 1245.08 | 1218.89 | 0.00 | 0.00 |
August | 2638.29 | 527.48 | 2092.25 | 1026.83 | 1065.42 | 0.00 | 0.00 |
September | 1963.24 | 721.00 | 1683.08 | 850.90 | 832.18 | 0.00 | 0.00 |
October | 1198.84 | 1015.93 | 1202.94 | 597.68 | 605.26 | 0.00 | 0.00 |
November | 688.64 | 1405.12 | 851.57 | 422.45 | 429.12 | 0.00 | 0.00 |
December | 316.23 | 1965.12 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Annual Sum or Average | 1611.77 | 1164.81 | 1530.03 | 714.83 | 815.21 | 0.00 | 0.00 |
Minimum of Months | 316.23 | 493.20 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Maximum of Months | 3189.73 | 2336.46 | 2463.98 | 1245.08 | 1300.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 20097374.69 | 0.106207E+11 | 0.121067E+10 | 0.00 | 0.121067E+10 | 0.00 | 0.00 |
February | 0.188579E+09 | 0.723011E+10 | 0.154397E+10 | 0.00 | 0.154397E+10 | 0.00 | 0.00 |
March | 0.837355E+09 | 0.652472E+10 | 0.277683E+10 | 0.00 | 0.277683E+10 | 0.00 | 0.00 |
April | 0.149570E+10 | 0.453646E+10 | 0.306404E+10 | 17880853.02 | 0.304616E+10 | 0.00 | 0.00 |
May | 0.301795E+10 | 0.338568E+10 | 0.415795E+10 | 0.246381E+09 | 0.391156E+10 | 0.00 | 0.00 |
June | 0.475066E+10 | 0.205331E+10 | 0.468551E+10 | 0.538554E+09 | 0.414696E+10 | 0.00 | 0.00 |
July | 0.533491E+10 | 0.174654E+10 | 0.442316E+10 | 0.414277E+09 | 0.400889E+10 | 0.00 | 0.00 |
August | 0.385872E+10 | 0.202023E+10 | 0.354431E+10 | 95002625.92 | 0.344930E+10 | 0.00 | 0.00 |
September | 0.216990E+10 | 0.304038E+10 | 0.256881E+10 | 921816.40 | 0.256789E+10 | 0.00 | 0.00 |
October | 0.782041E+09 | 0.482190E+10 | 0.193626E+10 | 0.00 | 0.193626E+10 | 0.00 | 0.00 |
November | 0.149717E+09 | 0.676223E+10 | 0.127382E+10 | 0.00 | 0.127382E+10 | 0.00 | 0.00 |
December | 6605072.17 | 0.947836E+10 | 0.101522E+10 | 0.00 | 0.101522E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.226122E+11 | 0.622206E+11 | 0.322005E+11 | 0.131302E+10 | 0.308875E+11 | 0.00 | 0.00 |
Minimum of Months | 6605072.17 | 0.174654E+10 | 0.101522E+10 | 0.00 | 0.101522E+10 | 0.00 | 0.00 |
Maximum of Months | 0.533491E+10 | 0.106207E+11 | 0.468551E+10 | 0.538554E+09 | 0.414696E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.953672E+09 | 0.645866E+10 | 0.185337E+10 | 0.849697E+09 | 0.100368E+10 | 0.00 | 0.00 |
February | 0.191626E+10 | 0.435834E+10 | 0.261831E+10 | 0.129993E+10 | 0.131838E+10 | 0.00 | 0.00 |
March | 0.313264E+10 | 0.398581E+10 | 0.389776E+10 | 0.161278E+10 | 0.228497E+10 | 0.00 | 0.00 |
April | 0.462740E+10 | 0.277301E+10 | 0.481273E+10 | 0.238515E+10 | 0.242758E+10 | 0.00 | 0.00 |
May | 0.569015E+10 | 0.223049E+10 | 0.549350E+10 | 0.244426E+10 | 0.304924E+10 | 0.00 | 0.00 |
June | 0.822615E+10 | 0.136406E+10 | 0.688124E+10 | 0.354108E+10 | 0.334016E+10 | 0.00 | 0.00 |
July | 0.962744E+10 | 0.111223E+10 | 0.746279E+10 | 0.421892E+10 | 0.324388E+10 | 0.00 | 0.00 |
August | 0.817528E+10 | 0.124271E+10 | 0.648550E+10 | 0.361352E+10 | 0.287198E+10 | 0.00 | 0.00 |
September | 0.506573E+10 | 0.186336E+10 | 0.443986E+10 | 0.229184E+10 | 0.214802E+10 | 0.00 | 0.00 |
October | 0.308292E+10 | 0.292327E+10 | 0.329155E+10 | 0.167140E+10 | 0.162015E+10 | 0.00 | 0.00 |
November | 0.135299E+10 | 0.398257E+10 | 0.201882E+10 | 0.942526E+09 | 0.107630E+10 | 0.00 | 0.00 |
December | 0.731579E+09 | 0.565564E+10 | 0.153863E+10 | 0.660846E+09 | 0.877787E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.525822E+11 | 0.379502E+11 | 0.507941E+11 | 0.255320E+11 | 0.252621E+11 | 0.00 | 0.00 |
Minimum of Months | 0.731579E+09 | 0.111223E+10 | 0.153863E+10 | 0.660846E+09 | 0.877787E+09 | 0.00 | 0.00 |
Maximum of Months | 0.962744E+10 | 0.645866E+10 | 0.746279E+10 | 0.421892E+10 | 0.334016E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.792170E+10 | 0.891444E+10 | 0.853377E+10 | 0.609498E+10 | 0.243879E+10 | 0.00 | 0.00 |
February | 0.100248E+11 | 0.614798E+10 | 0.981593E+10 | 0.705997E+10 | 0.275596E+10 | 0.00 | 0.00 |
March | 0.988624E+10 | 0.611537E+10 | 0.971426E+10 | 0.545506E+10 | 0.425920E+10 | 0.00 | 0.00 |
April | 0.798021E+10 | 0.445177E+10 | 0.755676E+10 | 0.361443E+10 | 0.394233E+10 | 0.00 | 0.00 |
May | 0.749046E+10 | 0.356305E+10 | 0.693780E+10 | 0.230422E+10 | 0.463359E+10 | 0.00 | 0.00 |
June | 0.823285E+10 | 0.232805E+10 | 0.667105E+10 | 0.194558E+10 | 0.472547E+10 | 0.00 | 0.00 |
July | 0.102273E+11 | 0.188910E+10 | 0.743179E+10 | 0.274526E+10 | 0.468653E+10 | 0.00 | 0.00 |
August | 0.117824E+11 | 0.213768E+10 | 0.883217E+10 | 0.445300E+10 | 0.437918E+10 | 0.00 | 0.00 |
September | 0.117393E+11 | 0.301067E+10 | 0.947992E+10 | 0.580863E+10 | 0.367129E+10 | 0.00 | 0.00 |
October | 0.115997E+11 | 0.446946E+10 | 0.102411E+11 | 0.708157E+10 | 0.315953E+10 | 0.00 | 0.00 |
November | 0.929374E+10 | 0.562872E+10 | 0.903565E+10 | 0.654505E+10 | 0.249060E+10 | 0.00 | 0.00 |
December | 0.766061E+10 | 0.779220E+10 | 0.811513E+10 | 0.585994E+10 | 0.225520E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113839E+12 | 0.564485E+11 | 0.102365E+12 | 0.589677E+11 | 0.433977E+11 | 0.00 | 0.00 |
Minimum of Months | 0.749046E+10 | 0.188910E+10 | 0.667105E+10 | 0.194558E+10 | 0.225520E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117824E+11 | 0.891444E+10 | 0.102411E+11 | 0.708157E+10 | 0.472547E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.823644E+09 | 0.693826E+10 | 0.167876E+10 | 0.676554E+09 | 0.100221E+10 | 0.00 | 0.00 |
February | 0.188607E+10 | 0.475420E+10 | 0.258810E+10 | 0.127218E+10 | 0.131592E+10 | 0.00 | 0.00 |
March | 0.277476E+10 | 0.453563E+10 | 0.366701E+10 | 0.134365E+10 | 0.232336E+10 | 0.00 | 0.00 |
April | 0.433750E+10 | 0.333367E+10 | 0.463287E+10 | 0.205258E+10 | 0.258030E+10 | 0.00 | 0.00 |
May | 0.625459E+10 | 0.251381E+10 | 0.592155E+10 | 0.270054E+10 | 0.322101E+10 | 0.00 | 0.00 |
June | 0.736512E+10 | 0.167135E+10 | 0.623460E+10 | 0.286378E+10 | 0.337081E+10 | 0.00 | 0.00 |
July | 0.845909E+10 | 0.144749E+10 | 0.659954E+10 | 0.333485E+10 | 0.326470E+10 | 0.00 | 0.00 |
August | 0.693473E+10 | 0.163107E+10 | 0.560390E+10 | 0.275028E+10 | 0.285362E+10 | 0.00 | 0.00 |
September | 0.500261E+10 | 0.213645E+10 | 0.436257E+10 | 0.220554E+10 | 0.215703E+10 | 0.00 | 0.00 |
October | 0.301313E+10 | 0.335404E+10 | 0.322197E+10 | 0.160082E+10 | 0.162115E+10 | 0.00 | 0.00 |
November | 0.161505E+10 | 0.454779E+10 | 0.220727E+10 | 0.109500E+10 | 0.111228E+10 | 0.00 | 0.00 |
December | 0.734816E+09 | 0.639209E+10 | 0.153315E+10 | 0.647098E+09 | 0.886049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.492011E+11 | 0.432559E+11 | 0.482513E+11 | 0.225429E+11 | 0.257084E+11 | 0.00 | 0.00 |
Minimum of Months | 0.734816E+09 | 0.144749E+10 | 0.153315E+10 | 0.647098E+09 | 0.886049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.845909E+10 | 0.693826E+10 | 0.659954E+10 | 0.333485E+10 | 0.337081E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 41869899.32 | 0.999314E+10 | 0.121069E+10 | 0.00 | 0.121069E+10 | 0.00 | 0.00 |
February | 0.287706E+09 | 0.665340E+10 | 0.154399E+10 | 0.00 | 0.154399E+10 | 0.00 | 0.00 |
March | 0.101803E+10 | 0.593033E+10 | 0.277688E+10 | 0.00 | 0.277688E+10 | 0.00 | 0.00 |
April | 0.167392E+10 | 0.407108E+10 | 0.306410E+10 | 17881386.28 | 0.304622E+10 | 0.00 | 0.00 |
May | 0.313847E+10 | 0.313861E+10 | 0.415802E+10 | 0.246389E+09 | 0.391163E+10 | 0.00 | 0.00 |
June | 0.481362E+10 | 0.196808E+10 | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.00 | 0.00 |
July | 0.539375E+10 | 0.169738E+10 | 0.442324E+10 | 0.414289E+09 | 0.400895E+10 | 0.00 | 0.00 |
August | 0.392917E+10 | 0.193794E+10 | 0.354436E+10 | 95005459.17 | 0.344936E+10 | 0.00 | 0.00 |
September | 0.224942E+10 | 0.283030E+10 | 0.256885E+10 | 921843.89 | 0.256793E+10 | 0.00 | 0.00 |
October | 0.926435E+09 | 0.431917E+10 | 0.193629E+10 | 0.00 | 0.193629E+10 | 0.00 | 0.00 |
November | 0.222386E+09 | 0.598501E+10 | 0.127385E+10 | 0.00 | 0.127385E+10 | 0.00 | 0.00 |
December | 22179672.85 | 0.851669E+10 | 0.101523E+10 | 0.00 | 0.101523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.237170E+11 | 0.570411E+11 | 0.322011E+11 | 0.131306E+10 | 0.308881E+11 | 0.00 | 0.00 |
Minimum of Months | 22179672.85 | 0.169738E+10 | 0.101523E+10 | 0.00 | 0.101523E+10 | 0.00 | 0.00 |
Maximum of Months | 0.539375E+10 | 0.999314E+10 | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.996365E+09 | 0.614268E+10 | 0.185337E+10 | 0.849694E+09 | 0.100367E+10 | 0.00 | 0.00 |
February | 0.198477E+10 | 0.409077E+10 | 0.261830E+10 | 0.129992E+10 | 0.131838E+10 | 0.00 | 0.00 |
March | 0.320958E+10 | 0.373474E+10 | 0.389774E+10 | 0.161278E+10 | 0.228496E+10 | 0.00 | 0.00 |
April | 0.467118E+10 | 0.260400E+10 | 0.481271E+10 | 0.238514E+10 | 0.242757E+10 | 0.00 | 0.00 |
May | 0.571102E+10 | 0.209874E+10 | 0.549347E+10 | 0.244425E+10 | 0.304922E+10 | 0.00 | 0.00 |
June | 0.819933E+10 | 0.133751E+10 | 0.688122E+10 | 0.354107E+10 | 0.334015E+10 | 0.00 | 0.00 |
July | 0.958580E+10 | 0.113187E+10 | 0.746276E+10 | 0.421890E+10 | 0.324386E+10 | 0.00 | 0.00 |
August | 0.813773E+10 | 0.127356E+10 | 0.648547E+10 | 0.361351E+10 | 0.287197E+10 | 0.00 | 0.00 |
September | 0.507591E+10 | 0.177466E+10 | 0.443984E+10 | 0.229183E+10 | 0.214801E+10 | 0.00 | 0.00 |
October | 0.315085E+10 | 0.270419E+10 | 0.329153E+10 | 0.167139E+10 | 0.162014E+10 | 0.00 | 0.00 |
November | 0.142272E+10 | 0.365437E+10 | 0.201882E+10 | 0.942522E+09 | 0.107629E+10 | 0.00 | 0.00 |
December | 0.785192E+09 | 0.522563E+10 | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.529304E+11 | 0.357727E+11 | 0.507939E+11 | 0.255318E+11 | 0.252620E+11 | 0.00 | 0.00 |
Minimum of Months | 0.785192E+09 | 0.113187E+10 | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.00 | 0.00 |
Maximum of Months | 0.958580E+10 | 0.614268E+10 | 0.746276E+10 | 0.421890E+10 | 0.334015E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.791633E+10 | 0.871674E+10 | 0.853404E+10 | 0.609518E+10 | 0.243886E+10 | 0.00 | 0.00 |
February | 0.100053E+11 | 0.595349E+10 | 0.981623E+10 | 0.706020E+10 | 0.275603E+10 | 0.00 | 0.00 |
March | 0.987506E+10 | 0.589361E+10 | 0.971455E+10 | 0.545524E+10 | 0.425930E+10 | 0.00 | 0.00 |
April | 0.798910E+10 | 0.425008E+10 | 0.755697E+10 | 0.361455E+10 | 0.394242E+10 | 0.00 | 0.00 |
May | 0.748399E+10 | 0.343176E+10 | 0.693798E+10 | 0.230429E+10 | 0.463369E+10 | 0.00 | 0.00 |
June | 0.822733E+10 | 0.226915E+10 | 0.667121E+10 | 0.194564E+10 | 0.472556E+10 | 0.00 | 0.00 |
July | 0.102171E+11 | 0.187648E+10 | 0.743197E+10 | 0.274535E+10 | 0.468662E+10 | 0.00 | 0.00 |
August | 0.117556E+11 | 0.212796E+10 | 0.883241E+10 | 0.445314E+10 | 0.437927E+10 | 0.00 | 0.00 |
September | 0.116717E+11 | 0.294546E+10 | 0.948020E+10 | 0.580882E+10 | 0.367137E+10 | 0.00 | 0.00 |
October | 0.115606E+11 | 0.431821E+10 | 0.102414E+11 | 0.708180E+10 | 0.315960E+10 | 0.00 | 0.00 |
November | 0.930836E+10 | 0.539146E+10 | 0.903593E+10 | 0.654527E+10 | 0.249067E+10 | 0.00 | 0.00 |
December | 0.772703E+10 | 0.740869E+10 | 0.811539E+10 | 0.586013E+10 | 0.225526E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113737E+12 | 0.545831E+11 | 0.102368E+12 | 0.589696E+11 | 0.433987E+11 | 0.00 | 0.00 |
Minimum of Months | 0.748399E+10 | 0.187648E+10 | 0.667121E+10 | 0.194564E+10 | 0.225526E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117556E+11 | 0.871674E+10 | 0.102414E+11 | 0.708180E+10 | 0.472556E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.862497E+09 | 0.648415E+10 | 0.167876E+10 | 0.676552E+09 | 0.100221E+10 | 0.00 | 0.00 |
February | 0.199136E+10 | 0.428075E+10 | 0.258809E+10 | 0.127218E+10 | 0.131591E+10 | 0.00 | 0.00 |
March | 0.294418E+10 | 0.398307E+10 | 0.366700E+10 | 0.134364E+10 | 0.232335E+10 | 0.00 | 0.00 |
April | 0.452760E+10 | 0.284145E+10 | 0.463285E+10 | 0.205257E+10 | 0.258029E+10 | 0.00 | 0.00 |
May | 0.633327E+10 | 0.230774E+10 | 0.592153E+10 | 0.270053E+10 | 0.322099E+10 | 0.00 | 0.00 |
June | 0.745126E+10 | 0.153879E+10 | 0.623457E+10 | 0.286377E+10 | 0.337080E+10 | 0.00 | 0.00 |
July | 0.855434E+10 | 0.133619E+10 | 0.659951E+10 | 0.333483E+10 | 0.326468E+10 | 0.00 | 0.00 |
August | 0.706896E+10 | 0.144186E+10 | 0.560388E+10 | 0.275026E+10 | 0.285361E+10 | 0.00 | 0.00 |
September | 0.507161E+10 | 0.195519E+10 | 0.436255E+10 | 0.220553E+10 | 0.215702E+10 | 0.00 | 0.00 |
October | 0.315497E+10 | 0.292463E+10 | 0.322196E+10 | 0.160082E+10 | 0.162114E+10 | 0.00 | 0.00 |
November | 0.174199E+10 | 0.389151E+10 | 0.220727E+10 | 0.109499E+10 | 0.111227E+10 | 0.00 | 0.00 |
December | 0.827943E+09 | 0.548703E+10 | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.505300E+11 | 0.384724E+11 | 0.482511E+11 | 0.225428E+11 | 0.257083E+11 | 0.00 | 0.00 |
Minimum of Months | 0.827943E+09 | 0.133619E+10 | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.00 | 0.00 |
Maximum of Months | 0.855434E+10 | 0.648415E+10 | 0.659951E+10 | 0.333483E+10 | 0.337080E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 59255395.68 | 0.963816E+10 | 0.121069E+10 | 0.00 | 0.121069E+10 | 0.00 | 0.00 |
February | 0.341519E+09 | 0.633575E+10 | 0.154399E+10 | 0.00 | 0.154399E+10 | 0.00 | 0.00 |
March | 0.111422E+10 | 0.557768E+10 | 0.277688E+10 | 0.00 | 0.277688E+10 | 0.00 | 0.00 |
April | 0.180800E+10 | 0.374749E+10 | 0.306410E+10 | 17881386.28 | 0.304622E+10 | 0.00 | 0.00 |
May | 0.324491E+10 | 0.293009E+10 | 0.415802E+10 | 0.246389E+09 | 0.391163E+10 | 0.00 | 0.00 |
June | 0.486343E+10 | 0.189875E+10 | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.00 | 0.00 |
July | 0.540530E+10 | 0.166410E+10 | 0.442324E+10 | 0.414289E+09 | 0.400895E+10 | 0.00 | 0.00 |
August | 0.395636E+10 | 0.187003E+10 | 0.354436E+10 | 95005459.17 | 0.344936E+10 | 0.00 | 0.00 |
September | 0.232325E+10 | 0.264072E+10 | 0.256885E+10 | 921843.89 | 0.256793E+10 | 0.00 | 0.00 |
October | 0.105730E+10 | 0.391679E+10 | 0.193629E+10 | 0.00 | 0.193629E+10 | 0.00 | 0.00 |
November | 0.274128E+09 | 0.552533E+10 | 0.127385E+10 | 0.00 | 0.127385E+10 | 0.00 | 0.00 |
December | 28789739.25 | 0.813653E+10 | 0.101523E+10 | 0.00 | 0.101523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.244765E+11 | 0.538814E+11 | 0.322011E+11 | 0.131306E+10 | 0.308881E+11 | 0.00 | 0.00 |
Minimum of Months | 28789739.25 | 0.166410E+10 | 0.101523E+10 | 0.00 | 0.101523E+10 | 0.00 | 0.00 |
Maximum of Months | 0.540530E+10 | 0.963816E+10 | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102873E+10 | 0.592569E+10 | 0.185337E+10 | 0.849694E+09 | 0.100367E+10 | 0.00 | 0.00 |
February | 0.204401E+10 | 0.390070E+10 | 0.261830E+10 | 0.129992E+10 | 0.131838E+10 | 0.00 | 0.00 |
March | 0.328483E+10 | 0.352986E+10 | 0.389774E+10 | 0.161278E+10 | 0.228496E+10 | 0.00 | 0.00 |
April | 0.473994E+10 | 0.243472E+10 | 0.481271E+10 | 0.238514E+10 | 0.242757E+10 | 0.00 | 0.00 |
May | 0.574402E+10 | 0.199043E+10 | 0.549347E+10 | 0.244425E+10 | 0.304922E+10 | 0.00 | 0.00 |
June | 0.819451E+10 | 0.131459E+10 | 0.688122E+10 | 0.354107E+10 | 0.334015E+10 | 0.00 | 0.00 |
July | 0.956304E+10 | 0.112814E+10 | 0.746276E+10 | 0.421890E+10 | 0.324386E+10 | 0.00 | 0.00 |
August | 0.812366E+10 | 0.125685E+10 | 0.648547E+10 | 0.361351E+10 | 0.287197E+10 | 0.00 | 0.00 |
September | 0.509591E+10 | 0.169954E+10 | 0.443984E+10 | 0.229183E+10 | 0.214801E+10 | 0.00 | 0.00 |
October | 0.323873E+10 | 0.249382E+10 | 0.329153E+10 | 0.167139E+10 | 0.162014E+10 | 0.00 | 0.00 |
November | 0.148891E+10 | 0.339118E+10 | 0.201882E+10 | 0.942522E+09 | 0.107629E+10 | 0.00 | 0.00 |
December | 0.814236E+09 | 0.499397E+10 | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.533605E+11 | 0.340595E+11 | 0.507939E+11 | 0.255318E+11 | 0.252620E+11 | 0.00 | 0.00 |
Minimum of Months | 0.814236E+09 | 0.112814E+10 | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.00 | 0.00 |
Maximum of Months | 0.956304E+10 | 0.592569E+10 | 0.746276E+10 | 0.421890E+10 | 0.334015E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.801925E+10 | 0.833798E+10 | 0.853404E+10 | 0.609518E+10 | 0.243886E+10 | 0.00 | 0.00 |
February | 0.101126E+11 | 0.563292E+10 | 0.981623E+10 | 0.706020E+10 | 0.275603E+10 | 0.00 | 0.00 |
March | 0.997606E+10 | 0.555047E+10 | 0.971455E+10 | 0.545524E+10 | 0.425930E+10 | 0.00 | 0.00 |
April | 0.808368E+10 | 0.396049E+10 | 0.755697E+10 | 0.361455E+10 | 0.394242E+10 | 0.00 | 0.00 |
May | 0.753390E+10 | 0.323899E+10 | 0.693798E+10 | 0.230429E+10 | 0.463369E+10 | 0.00 | 0.00 |
June | 0.823388E+10 | 0.220600E+10 | 0.667121E+10 | 0.194564E+10 | 0.472556E+10 | 0.00 | 0.00 |
July | 0.101998E+11 | 0.185105E+10 | 0.743197E+10 | 0.274535E+10 | 0.468662E+10 | 0.00 | 0.00 |
August | 0.117411E+11 | 0.208161E+10 | 0.883241E+10 | 0.445314E+10 | 0.437927E+10 | 0.00 | 0.00 |
September | 0.116951E+11 | 0.280748E+10 | 0.948020E+10 | 0.580882E+10 | 0.367137E+10 | 0.00 | 0.00 |
October | 0.116677E+11 | 0.398572E+10 | 0.102414E+11 | 0.708180E+10 | 0.315960E+10 | 0.00 | 0.00 |
November | 0.945961E+10 | 0.498105E+10 | 0.903593E+10 | 0.654527E+10 | 0.249067E+10 | 0.00 | 0.00 |
December | 0.783793E+10 | 0.702929E+10 | 0.811539E+10 | 0.586013E+10 | 0.225526E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.114561E+12 | 0.516630E+11 | 0.102368E+12 | 0.589696E+11 | 0.433987E+11 | 0.00 | 0.00 |
Minimum of Months | 0.753390E+10 | 0.185105E+10 | 0.667121E+10 | 0.194564E+10 | 0.225526E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117411E+11 | 0.833798E+10 | 0.102414E+11 | 0.708180E+10 | 0.472556E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.884871E+09 | 0.625798E+10 | 0.167876E+10 | 0.676552E+09 | 0.100221E+10 | 0.00 | 0.00 |
February | 0.202600E+10 | 0.409397E+10 | 0.258809E+10 | 0.127218E+10 | 0.131591E+10 | 0.00 | 0.00 |
March | 0.298628E+10 | 0.378639E+10 | 0.366700E+10 | 0.134364E+10 | 0.232335E+10 | 0.00 | 0.00 |
April | 0.457955E+10 | 0.267254E+10 | 0.463285E+10 | 0.205257E+10 | 0.258029E+10 | 0.00 | 0.00 |
May | 0.635889E+10 | 0.219090E+10 | 0.592153E+10 | 0.270053E+10 | 0.322099E+10 | 0.00 | 0.00 |
June | 0.745184E+10 | 0.150252E+10 | 0.623457E+10 | 0.286377E+10 | 0.337080E+10 | 0.00 | 0.00 |
July | 0.854337E+10 | 0.132098E+10 | 0.659951E+10 | 0.333483E+10 | 0.326468E+10 | 0.00 | 0.00 |
August | 0.706640E+10 | 0.141279E+10 | 0.560388E+10 | 0.275026E+10 | 0.285361E+10 | 0.00 | 0.00 |
September | 0.508871E+10 | 0.186883E+10 | 0.436255E+10 | 0.220553E+10 | 0.215702E+10 | 0.00 | 0.00 |
October | 0.321099E+10 | 0.272107E+10 | 0.322196E+10 | 0.160082E+10 | 0.162114E+10 | 0.00 | 0.00 |
November | 0.178495E+10 | 0.364207E+10 | 0.220727E+10 | 0.109499E+10 | 0.111227E+10 | 0.00 | 0.00 |
December | 0.847004E+09 | 0.526337E+10 | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.508289E+11 | 0.367334E+11 | 0.482511E+11 | 0.225428E+11 | 0.257083E+11 | 0.00 | 0.00 |
Minimum of Months | 0.847004E+09 | 0.132098E+10 | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.00 | 0.00 |
Maximum of Months | 0.854337E+10 | 0.625798E+10 | 0.659951E+10 | 0.333483E+10 | 0.337080E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.437175E+11 | -0.426679E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.104954E+10 | 58.98 | 0.00 | 0.00 |
February | 0.403890E+11 | -0.394524E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -936616652.6 | 58.98 | 0.00 | 0.00 |
March | 0.469608E+11 | -0.459284E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103244E+10 | 58.97 | 0.00 | 0.00 |
April | 0.411161E+11 | -0.401232E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992933268.5 | 58.97 | 0.00 | 0.00 |
May | 0.415208E+11 | -0.404953E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102546E+10 | 58.98 | 0.00 | 0.00 |
June | 0.386510E+11 | -0.376584E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992537841.9 | 58.98 | 0.00 | 0.00 |
July | 0.350100E+11 | -0.339907E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101922E+10 | 58.98 | 0.00 | 0.00 |
August | 0.373965E+11 | -0.363731E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102341E+10 | 58.98 | 0.00 | 0.00 |
September | 0.344383E+11 | -0.334497E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988546487.4 | 58.98 | 0.00 | 0.00 |
October | 0.371413E+11 | -0.361207E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102060E+10 | 58.98 | 0.00 | 0.00 |
November | 0.386802E+11 | -0.376911E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989053281.2 | 58.98 | 0.00 | 0.00 |
December | 0.408551E+11 | -0.398248E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103031E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.475876E+12 | -0.463776E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.121007E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.344383E+11 | -0.459284E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.104954E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.469608E+11 | -0.334497E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -936616652.6 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.64 | 0.61 | 01-JAN-08:50 | 5097.18 | 32.67 | 186.00 | 222.00 | 4508.42 | 37.63 | 218.67 | 207.17 |
February | 275.00 | 0.63 | 0.61 | 01-FEB-08:20 | 7187.51 | 34.27 | 240.83 | 249.83 | 3012.65 | 31.09 | 228.67 | 239.83 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:49 | 8536.88 | 32.08 | 253.50 | 316.17 | 1586.52 | 22.09 | 194.67 | 285.17 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 1939.33 | 18.00 | 0.00 | 339.83 | 1094.23 | 21.03 | 159.17 | 297.33 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-06:10 | 1718.33 | 17.69 | 0.00 | 385.83 | 953.00 | 20.69 | 170.50 | 336.33 |
June | 434.17 | 0.64 | 0.61 | 01-JUN-13:39 | 1461.07 | 17.04 | 0.00 | 394.17 | 842.21 | 20.09 | 183.17 | 341.67 |
July | 417.33 | 0.63 | 0.61 | 01-JUL-06:40 | 1565.82 | 17.48 | 0.00 | 393.33 | 928.13 | 20.55 | 142.50 | 350.17 |
August | 421.33 | 0.64 | 0.61 | 01-AUG-06:19 | 1676.86 | 17.06 | 0.00 | 370.83 | 991.36 | 20.07 | 147.00 | 328.17 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:49 | 2439.00 | 18.71 | 29.50 | 318.67 | 1163.65 | 20.35 | 140.67 | 285.50 |
October | 317.67 | 0.63 | 0.61 | 01-OCT-07:40 | 7376.52 | 33.51 | 276.67 | 294.67 | 1885.38 | 23.09 | 168.33 | 272.50 |
November | 269.50 | 0.63 | 0.61 | 01-NOV-07:49 | 5291.25 | 33.17 | 223.50 | 240.67 | 4880.05 | 38.16 | 261.50 | 236.17 |
December | 236.83 | 0.64 | 0.61 | 01-DEC-08:50 | 3827.25 | 30.55 | 166.50 | 221.83 | 3680.55 | 37.33 | 224.50 | 210.67 |
Annual Sum or Average | 3965.83 | 0.63 | 3668.97 | 23.84 | 1376.50 | 3747.83 | 1871.79 | 24.71 | 2239.33 | 3390.67 | ||
Minimum of Months | 226.83 | 0.63 | 0.61 | 1461.07 | 17.04 | 0.00 | 221.83 | 842.21 | 20.07 | 140.67 | 207.17 | |
Maximum of Months | 434.17 | 0.64 | 0.61 | 8536.88 | 34.27 | 276.67 | 394.17 | 4880.05 | 38.16 | 261.50 | 350.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.65 | 0.61 | 01-JAN-08:50 | 1515.70 | 19.87 | 73.83 | 201.50 | 909.48 | 20.73 | 61.50 | 159.33 |
February | 275.00 | 0.64 | 0.61 | 01-FEB-08:09 | 1512.39 | 16.70 | 48.83 | 232.00 | 897.48 | 18.14 | 46.17 | 192.50 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:40 | 2643.32 | 18.73 | 70.33 | 309.50 | 1543.82 | 18.41 | 44.83 | 270.67 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 2661.32 | 16.14 | 42.50 | 346.83 | 1551.95 | 15.15 | 0.00 | 297.33 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-05:40 | 3060.56 | 13.63 | 0.00 | 394.67 | 1315.48 | 15.00 | 0.00 | 347.00 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 3714.72 | 13.03 | 0.00 | 406.33 | 1589.50 | 14.54 | 0.00 | 369.50 |
July | 417.33 | 0.62 | 0.61 | 01-JUL-06:40 | 4046.93 | 13.47 | 3.67 | 409.33 | 1706.80 | 14.95 | 0.00 | 377.67 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-05:40 | 3022.20 | 15.49 | 55.83 | 378.50 | 1838.33 | 14.30 | 0.00 | 338.50 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:30 | 2350.16 | 15.89 | 52.50 | 313.00 | 1343.76 | 14.94 | 8.50 | 274.00 |
October | 317.67 | 0.64 | 0.61 | 01-OCT-07:40 | 2076.98 | 18.31 | 80.17 | 273.17 | 1248.14 | 19.32 | 73.33 | 229.83 |
November | 269.50 | 0.65 | 0.61 | 01-NOV-07:49 | 1373.22 | 18.88 | 81.33 | 215.00 | 727.59 | 18.22 | 53.83 | 170.83 |
December | 236.83 | 0.65 | 0.61 | 01-DEC-08:50 | 1174.43 | 19.62 | 80.33 | 190.00 | 738.18 | 20.91 | 72.50 | 142.17 |
Annual Sum or Average | 3965.83 | 0.64 | 2602.30 | 16.20 | 589.33 | 3669.83 | 1349.58 | 16.60 | 360.67 | 3169.33 | ||
Minimum of Months | 226.83 | 0.62 | 0.61 | 1174.43 | 13.03 | 0.00 | 190.00 | 727.59 | 14.30 | 0.00 | 142.17 | |
Maximum of Months | 434.17 | 0.65 | 0.61 | 4046.93 | 19.87 | 81.33 | 409.33 | 1838.33 | 20.91 | 73.33 | 377.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.67 | 0.61 | 01-JAN-09:39 | 494.54 | 0.00 | 0.00 | 170.83 | 293.92 | 0.00 | 0.00 | 68.67 |
February | 275.00 | 0.65 | 0.61 | 01-FEB-10:20 | 538.64 | 0.00 | 0.00 | 209.83 | 334.67 | 0.00 | 0.00 | 129.00 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:00 | 858.79 | 0.00 | 0.00 | 299.67 | 505.19 | 0.00 | 0.00 | 245.67 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 892.96 | 0.00 | 0.00 | 342.50 | 533.87 | 0.00 | 0.00 | 281.00 |
May | 385.83 | 0.62 | 0.61 | 01-MAY-05:49 | 1114.37 | 0.00 | 0.00 | 404.17 | 651.57 | 0.00 | 0.00 | 363.00 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 1155.10 | 0.00 | 0.00 | 432.33 | 637.69 | 0.00 | 0.00 | 395.83 |
July | 417.33 | 0.62 | 0.61 | 01-JUL-06:40 | 1129.94 | 0.00 | 0.00 | 419.17 | 646.37 | 0.00 | 0.00 | 386.00 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-05:40 | 869.82 | 0.00 | 0.00 | 391.67 | 558.50 | 0.00 | 0.00 | 357.67 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:49 | 707.70 | 0.00 | 0.00 | 310.67 | 442.60 | 0.00 | 0.00 | 241.50 |
October | 317.67 | 0.65 | 0.61 | 01-OCT-07:49 | 584.73 | 0.00 | 0.00 | 249.83 | 358.91 | 0.00 | 0.00 | 166.50 |
November | 269.50 | 0.66 | 0.61 | 01-NOV-08:09 | 462.77 | 0.00 | 0.00 | 181.17 | 280.42 | 0.00 | 0.00 | 61.17 |
December | 236.83 | 0.67 | 0.61 | 01-DEC-09:09 | 401.05 | 0.00 | 0.00 | 148.67 | 242.56 | 0.00 | 0.00 | 15.83 |
Annual Sum or Average | 3965.83 | 0.64 | 815.95 | 0.00 | 0.00 | 3560.50 | 484.67 | 0.00 | 0.00 | 2711.83 | ||
Minimum of Months | 226.83 | 0.62 | 0.61 | 401.05 | 0.00 | 0.00 | 148.67 | 242.56 | 0.00 | 0.00 | 15.83 | |
Maximum of Months | 434.17 | 0.67 | 0.61 | 1155.10 | 0.00 | 0.00 | 432.33 | 651.57 | 0.00 | 0.00 | 395.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.66 | 0.61 | 01-JAN-09:39 | 1396.40 | 18.96 | 69.17 | 194.83 | 866.64 | 19.81 | 58.83 | 148.83 |
February | 275.00 | 0.64 | 0.61 | 01-FEB-10:20 | 1854.80 | 19.00 | 76.33 | 229.83 | 955.29 | 18.25 | 48.83 | 192.67 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:00 | 2492.22 | 18.53 | 69.00 | 305.00 | 1412.19 | 19.45 | 62.00 | 268.33 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 2604.19 | 16.34 | 48.50 | 335.17 | 1512.15 | 15.24 | 0.00 | 295.50 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-06:19 | 3076.06 | 13.72 | 0.00 | 389.50 | 1774.73 | 15.20 | 1.33 | 348.00 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 3145.79 | 13.15 | 0.00 | 409.50 | 1403.52 | 16.71 | 47.50 | 369.67 |
July | 417.33 | 0.63 | 0.61 | 01-JUL-06:40 | 3662.35 | 13.44 | 3.67 | 397.50 | 1634.67 | 16.31 | 31.50 | 360.67 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-06:30 | 2705.64 | 15.41 | 56.83 | 374.00 | 1540.18 | 14.36 | 0.00 | 337.00 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:00 | 2876.75 | 17.35 | 75.33 | 314.50 | 1113.30 | 14.77 | 5.50 | 274.50 |
October | 317.67 | 0.64 | 0.61 | 01-OCT-07:00 | 1853.40 | 18.27 | 77.67 | 270.83 | 991.50 | 18.09 | 53.33 | 228.50 |
November | 269.50 | 0.65 | 0.61 | 01-NOV-08:20 | 1582.40 | 19.14 | 82.33 | 212.17 | 941.30 | 20.18 | 71.83 | 169.83 |
December | 236.83 | 0.65 | 0.61 | 01-DEC-09:09 | 1122.44 | 19.52 | 79.17 | 194.00 | 608.57 | 18.53 | 49.83 | 139.83 |
Annual Sum or Average | 3965.83 | 0.64 | 2508.03 | 16.46 | 638.00 | 3626.83 | 1288.60 | 16.93 | 430.50 | 3133.33 | ||
Minimum of Months | 226.83 | 0.63 | 0.61 | 1122.44 | 13.15 | 0.00 | 194.00 | 608.57 | 14.36 | 0.00 | 139.83 | |
Maximum of Months | 434.17 | 0.66 | 0.61 | 3662.35 | 19.52 | 82.33 | 409.50 | 1774.73 | 20.18 | 71.83 | 369.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.64 | 0.61 | 01-JAN-08:50 | 4462.85 | 25.63 | 138.83 | 220.83 | 4554.30 | 37.18 | 214.33 | 207.67 |
February | 275.00 | 0.63 | 0.61 | 01-FEB-08:20 | 7152.76 | 33.30 | 239.33 | 249.17 | 3067.03 | 28.60 | 169.67 | 240.17 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:49 | 8490.01 | 31.08 | 250.17 | 314.33 | 1637.51 | 17.40 | 6.67 | 286.83 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 1908.40 | 12.00 | 0.00 | 338.17 | 1134.03 | 16.87 | 0.00 | 299.17 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-06:10 | 1687.13 | 11.93 | 0.00 | 384.83 | 984.97 | 16.71 | 0.00 | 339.83 |
June | 434.17 | 0.64 | 0.61 | 01-JUN-13:39 | 1437.92 | 11.48 | 0.00 | 392.17 | 870.55 | 16.33 | 0.00 | 345.00 |
July | 417.33 | 0.63 | 0.61 | 01-JUL-06:40 | 1545.48 | 11.87 | 0.00 | 391.17 | 961.96 | 16.80 | 0.00 | 352.33 |
August | 421.33 | 0.64 | 0.61 | 01-AUG-06:19 | 1659.43 | 11.18 | 0.00 | 368.33 | 1030.17 | 16.05 | 0.00 | 330.83 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:49 | 2418.58 | 12.96 | 29.50 | 317.50 | 1225.17 | 16.21 | 5.50 | 287.17 |
October | 317.67 | 0.63 | 0.61 | 01-OCT-07:40 | 7290.95 | 32.29 | 270.17 | 293.83 | 2020.28 | 20.65 | 76.17 | 278.50 |
November | 269.50 | 0.64 | 0.61 | 01-NOV-07:49 | 5031.46 | 28.74 | 191.00 | 240.17 | 4886.22 | 36.56 | 248.83 | 233.00 |
December | 236.83 | 0.64 | 0.61 | 01-DEC-08:50 | 3085.67 | 21.26 | 108.67 | 220.67 | 3717.67 | 36.67 | 218.00 | 211.50 |
Annual Sum or Average | 3965.83 | 0.63 | 3543.98 | 18.96 | 1227.67 | 3731.17 | 1918.16 | 21.48 | 939.17 | 3412.00 | ||
Minimum of Months | 226.83 | 0.63 | 0.61 | 1437.92 | 11.18 | 0.00 | 220.67 | 870.55 | 16.05 | 0.00 | 207.67 | |
Maximum of Months | 434.17 | 0.64 | 0.61 | 8490.01 | 33.30 | 270.17 | 392.17 | 4886.22 | 37.18 | 248.83 | 352.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.65 | 0.61 | 01-JAN-08:50 | 1511.97 | 18.02 | 74.00 | 200.67 | 843.63 | 16.72 | 46.17 | 160.00 |
February | 275.00 | 0.64 | 0.61 | 01-FEB-08:09 | 1512.87 | 14.14 | 48.83 | 231.00 | 922.21 | 15.98 | 46.50 | 194.67 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:40 | 2640.82 | 16.41 | 70.33 | 308.50 | 1578.00 | 16.18 | 44.50 | 272.67 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 2666.43 | 13.26 | 42.50 | 345.67 | 1588.35 | 12.52 | 0.00 | 300.83 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-05:40 | 3058.86 | 10.22 | 0.00 | 394.33 | 1352.32 | 12.53 | 0.00 | 350.50 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 3705.48 | 9.52 | 0.00 | 405.83 | 1632.30 | 12.07 | 0.00 | 372.33 |
July | 417.33 | 0.62 | 0.61 | 01-JUL-06:40 | 4046.95 | 9.92 | 3.67 | 408.33 | 1754.47 | 12.39 | 0.00 | 380.17 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-05:40 | 3030.38 | 12.59 | 55.83 | 378.50 | 1879.80 | 11.71 | 0.00 | 341.83 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:30 | 2353.22 | 13.22 | 52.50 | 312.33 | 1375.63 | 12.40 | 8.50 | 277.50 |
October | 317.67 | 0.64 | 0.61 | 01-OCT-07:40 | 2022.78 | 15.71 | 76.50 | 272.67 | 1272.19 | 17.45 | 73.67 | 233.67 |
November | 269.50 | 0.65 | 0.61 | 01-NOV-07:49 | 1167.73 | 14.33 | 56.67 | 214.67 | 745.98 | 16.16 | 53.67 | 174.33 |
December | 236.83 | 0.66 | 0.61 | 01-DEC-08:50 | 1169.49 | 17.76 | 80.33 | 188.67 | 752.12 | 19.15 | 72.67 | 144.50 |
Annual Sum or Average | 3965.83 | 0.64 | 2583.71 | 13.24 | 561.17 | 3661.17 | 1377.67 | 14.16 | 345.67 | 3203.00 | ||
Minimum of Months | 226.83 | 0.62 | 0.61 | 1167.73 | 9.52 | 0.00 | 188.67 | 745.98 | 11.71 | 0.00 | 144.50 | |
Maximum of Months | 434.17 | 0.66 | 0.61 | 4046.95 | 18.02 | 80.33 | 408.33 | 1879.80 | 19.15 | 73.67 | 380.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.67 | 0.61 | 01-JAN-09:50 | 482.82 | 0.00 | 0.00 | 168.17 | 301.22 | 0.00 | 0.00 | 75.83 |
February | 275.00 | 0.65 | 0.61 | 01-FEB-10:20 | 527.36 | 0.00 | 0.00 | 207.67 | 343.55 | 0.00 | 0.00 | 137.67 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:00 | 841.75 | 0.00 | 0.00 | 297.50 | 519.31 | 0.00 | 0.00 | 249.50 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 877.01 | 0.00 | 0.00 | 340.50 | 549.67 | 0.00 | 0.00 | 286.00 |
May | 385.83 | 0.62 | 0.61 | 01-MAY-05:49 | 1096.75 | 0.00 | 0.00 | 403.00 | 670.62 | 0.00 | 0.00 | 366.50 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 1139.92 | 0.00 | 0.00 | 431.00 | 657.69 | 0.00 | 0.00 | 397.00 |
July | 417.33 | 0.62 | 0.61 | 01-JUL-06:40 | 1116.82 | 0.00 | 0.00 | 418.50 | 667.34 | 0.00 | 0.00 | 387.83 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-05:40 | 857.49 | 0.00 | 0.00 | 390.17 | 575.05 | 0.00 | 0.00 | 361.17 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:49 | 695.45 | 0.00 | 0.00 | 307.67 | 455.59 | 0.00 | 0.00 | 248.00 |
October | 317.67 | 0.65 | 0.61 | 01-OCT-07:49 | 572.75 | 0.00 | 0.00 | 247.50 | 368.69 | 0.00 | 0.00 | 174.67 |
November | 269.50 | 0.67 | 0.61 | 01-NOV-08:09 | 452.19 | 0.00 | 0.00 | 178.67 | 287.50 | 0.00 | 0.00 | 72.33 |
December | 236.83 | 0.68 | 0.61 | 01-DEC-09:09 | 390.42 | 0.00 | 0.00 | 144.83 | 247.99 | 0.00 | 0.00 | 20.67 |
Annual Sum or Average | 3965.83 | 0.64 | 802.42 | 0.00 | 0.00 | 3535.17 | 498.83 | 0.00 | 0.00 | 2777.17 | ||
Minimum of Months | 226.83 | 0.62 | 0.61 | 390.42 | 0.00 | 0.00 | 144.83 | 247.99 | 0.00 | 0.00 | 20.67 | |
Maximum of Months | 434.17 | 0.68 | 0.61 | 1139.92 | 0.00 | 0.00 | 431.00 | 670.62 | 0.00 | 0.00 | 397.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.66 | 0.61 | 01-JAN-09:50 | 1391.45 | 17.13 | 69.17 | 194.50 | 883.82 | 17.99 | 58.17 | 151.83 |
February | 275.00 | 0.64 | 0.61 | 01-FEB-10:20 | 1853.11 | 16.87 | 76.50 | 229.00 | 979.31 | 16.09 | 48.67 | 196.00 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:00 | 2486.70 | 16.15 | 68.83 | 304.50 | 1442.85 | 17.44 | 62.17 | 270.50 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 2604.96 | 13.56 | 48.50 | 334.00 | 1547.88 | 12.66 | 0.00 | 297.83 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-06:19 | 2823.08 | 10.24 | 0.00 | 388.33 | 1813.43 | 12.69 | 1.33 | 350.00 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 3133.75 | 9.71 | 0.00 | 408.17 | 1440.99 | 14.66 | 47.83 | 372.50 |
July | 417.33 | 0.63 | 0.61 | 01-JUL-06:40 | 3655.10 | 10.00 | 3.67 | 396.67 | 1678.84 | 14.09 | 31.50 | 364.17 |
August | 421.33 | 0.64 | 0.61 | 01-AUG-06:30 | 2672.63 | 12.61 | 56.83 | 373.00 | 1577.08 | 11.85 | 0.00 | 339.83 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:00 | 2626.87 | 14.72 | 72.33 | 314.00 | 1145.72 | 12.21 | 5.50 | 277.17 |
October | 317.67 | 0.64 | 0.61 | 01-OCT-07:00 | 1611.16 | 13.92 | 53.67 | 270.33 | 1000.05 | 15.62 | 49.33 | 231.17 |
November | 269.50 | 0.65 | 0.61 | 01-NOV-08:20 | 1570.29 | 16.79 | 78.83 | 211.67 | 866.97 | 16.21 | 52.50 | 170.33 |
December | 236.83 | 0.66 | 0.61 | 01-DEC-09:09 | 953.39 | 14.75 | 54.00 | 192.83 | 622.98 | 16.45 | 49.83 | 145.00 |
Annual Sum or Average | 3965.83 | 0.64 | 2424.56 | 13.39 | 582.33 | 3617.00 | 1312.34 | 14.52 | 406.83 | 3166.33 | ||
Minimum of Months | 226.83 | 0.63 | 0.61 | 953.39 | 9.71 | 0.00 | 192.83 | 622.98 | 11.85 | 0.00 | 145.00 | |
Maximum of Months | 434.17 | 0.66 | 0.61 | 3655.10 | 17.13 | 78.83 | 408.17 | 1813.43 | 17.99 | 62.17 | 372.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.64 | 0.61 | 01-JAN-08:50 | 4461.26 | 25.61 | 138.83 | 220.83 | 4555.28 | 37.17 | 214.33 | 207.83 |
February | 275.00 | 0.63 | 0.61 | 01-FEB-08:20 | 7151.54 | 33.28 | 239.33 | 249.17 | 3068.36 | 28.59 | 169.67 | 240.17 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:49 | 8490.16 | 31.07 | 250.17 | 314.33 | 1639.37 | 17.38 | 6.67 | 287.00 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 1909.27 | 11.96 | 0.00 | 338.17 | 1135.34 | 16.85 | 0.00 | 299.17 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-06:10 | 1688.03 | 11.89 | 0.00 | 384.67 | 986.12 | 16.70 | 0.00 | 340.00 |
June | 434.17 | 0.64 | 0.61 | 01-JUN-13:39 | 1438.50 | 11.44 | 0.00 | 392.17 | 871.44 | 16.31 | 0.00 | 345.00 |
July | 417.33 | 0.63 | 0.61 | 01-JUL-06:40 | 1546.04 | 11.83 | 0.00 | 391.17 | 962.87 | 16.78 | 0.00 | 352.50 |
August | 421.33 | 0.64 | 0.61 | 01-AUG-06:19 | 1660.07 | 11.14 | 0.00 | 368.33 | 1031.19 | 16.03 | 0.00 | 330.83 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:49 | 2419.04 | 12.92 | 29.50 | 317.50 | 1226.41 | 16.19 | 5.50 | 287.17 |
October | 317.67 | 0.63 | 0.61 | 01-OCT-07:40 | 7290.12 | 32.27 | 270.17 | 293.83 | 2021.62 | 20.63 | 76.17 | 278.50 |
November | 269.50 | 0.64 | 0.61 | 01-NOV-07:49 | 5029.92 | 28.72 | 191.00 | 240.17 | 4887.26 | 36.55 | 248.83 | 233.00 |
December | 236.83 | 0.64 | 0.61 | 01-DEC-08:50 | 3083.93 | 21.23 | 108.67 | 220.67 | 3718.34 | 36.67 | 218.00 | 211.50 |
Annual Sum or Average | 3965.83 | 0.63 | 3543.93 | 18.92 | 1227.67 | 3731.00 | 1919.30 | 21.47 | 939.17 | 3412.67 | ||
Minimum of Months | 226.83 | 0.63 | 0.61 | 1438.50 | 11.14 | 0.00 | 220.67 | 871.44 | 16.03 | 0.00 | 207.83 | |
Maximum of Months | 434.17 | 0.64 | 0.61 | 8490.16 | 33.28 | 270.17 | 392.17 | 4887.26 | 37.17 | 248.83 | 352.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.65 | 0.61 | 01-JAN-08:50 | 1511.69 | 18.01 | 74.00 | 200.67 | 844.16 | 16.71 | 46.17 | 160.00 |
February | 275.00 | 0.64 | 0.61 | 01-FEB-08:09 | 1512.44 | 14.12 | 48.83 | 231.00 | 922.76 | 15.97 | 46.50 | 194.67 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:40 | 2640.59 | 16.40 | 70.33 | 308.50 | 1579.01 | 16.17 | 44.50 | 272.83 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 2666.21 | 13.25 | 42.50 | 345.67 | 1589.22 | 12.51 | 0.00 | 300.67 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-05:40 | 3058.92 | 10.20 | 0.00 | 394.33 | 1353.32 | 12.52 | 0.00 | 350.67 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 3705.14 | 9.51 | 0.00 | 405.67 | 1633.17 | 12.06 | 0.00 | 372.50 |
July | 417.33 | 0.62 | 0.61 | 01-JUL-06:40 | 4046.53 | 9.91 | 3.67 | 408.17 | 1755.30 | 12.38 | 0.00 | 380.00 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-05:40 | 3030.04 | 12.58 | 55.83 | 378.33 | 1880.61 | 11.70 | 0.00 | 341.83 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:30 | 2352.79 | 13.21 | 52.50 | 312.33 | 1376.37 | 12.40 | 8.50 | 277.67 |
October | 317.67 | 0.64 | 0.61 | 01-OCT-07:40 | 2022.38 | 15.69 | 76.50 | 272.67 | 1272.81 | 17.45 | 73.67 | 233.67 |
November | 269.50 | 0.65 | 0.61 | 01-NOV-07:49 | 1167.42 | 14.32 | 56.67 | 214.50 | 746.46 | 16.15 | 53.67 | 174.33 |
December | 236.83 | 0.66 | 0.61 | 01-DEC-08:50 | 1169.18 | 17.75 | 80.33 | 188.67 | 752.52 | 19.15 | 72.67 | 144.67 |
Annual Sum or Average | 3965.83 | 0.64 | 2583.41 | 13.23 | 561.17 | 3660.50 | 1378.42 | 14.15 | 345.67 | 3203.50 | ||
Minimum of Months | 226.83 | 0.62 | 0.61 | 1167.42 | 9.51 | 0.00 | 188.67 | 746.46 | 11.70 | 0.00 | 144.67 | |
Maximum of Months | 434.17 | 0.66 | 0.61 | 4046.53 | 18.01 | 80.33 | 408.17 | 1880.61 | 19.15 | 73.67 | 380.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.67 | 0.61 | 01-JAN-09:50 | 482.76 | 0.00 | 0.00 | 168.17 | 301.50 | 0.00 | 0.00 | 76.00 |
February | 275.00 | 0.65 | 0.61 | 01-FEB-10:20 | 527.23 | 0.00 | 0.00 | 207.67 | 343.83 | 0.00 | 0.00 | 137.83 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:00 | 841.78 | 0.00 | 0.00 | 297.50 | 519.84 | 0.00 | 0.00 | 249.50 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 877.01 | 0.00 | 0.00 | 340.67 | 550.19 | 0.00 | 0.00 | 286.00 |
May | 385.83 | 0.62 | 0.61 | 01-MAY-05:49 | 1096.79 | 0.00 | 0.00 | 403.00 | 671.24 | 0.00 | 0.00 | 366.50 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 1139.75 | 0.00 | 0.00 | 431.00 | 658.23 | 0.00 | 0.00 | 397.00 |
July | 417.33 | 0.62 | 0.61 | 01-JUL-06:40 | 1116.59 | 0.00 | 0.00 | 418.50 | 667.83 | 0.00 | 0.00 | 387.83 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-05:40 | 857.34 | 0.00 | 0.00 | 390.17 | 575.47 | 0.00 | 0.00 | 361.17 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:49 | 695.32 | 0.00 | 0.00 | 307.67 | 455.96 | 0.00 | 0.00 | 248.33 |
October | 317.67 | 0.65 | 0.61 | 01-OCT-07:49 | 572.65 | 0.00 | 0.00 | 247.17 | 369.00 | 0.00 | 0.00 | 175.17 |
November | 269.50 | 0.67 | 0.61 | 01-NOV-08:09 | 452.11 | 0.00 | 0.00 | 178.67 | 287.75 | 0.00 | 0.00 | 72.67 |
December | 236.83 | 0.68 | 0.61 | 01-DEC-09:09 | 390.32 | 0.00 | 0.00 | 144.33 | 248.21 | 0.00 | 0.00 | 20.67 |
Annual Sum or Average | 3965.83 | 0.64 | 802.32 | 0.00 | 0.00 | 3534.50 | 499.25 | 0.00 | 0.00 | 2778.67 | ||
Minimum of Months | 226.83 | 0.62 | 0.61 | 390.32 | 0.00 | 0.00 | 144.33 | 248.21 | 0.00 | 0.00 | 20.67 | |
Maximum of Months | 434.17 | 0.68 | 0.61 | 1139.75 | 0.00 | 0.00 | 431.00 | 671.24 | 0.00 | 0.00 | 397.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.66 | 0.61 | 01-JAN-09:50 | 1391.20 | 17.12 | 69.17 | 194.67 | 884.35 | 17.98 | 58.17 | 152.17 |
February | 275.00 | 0.64 | 0.61 | 01-FEB-10:20 | 1852.71 | 16.86 | 76.50 | 229.00 | 979.87 | 16.08 | 48.67 | 196.00 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:00 | 2486.49 | 16.14 | 68.83 | 304.50 | 1443.87 | 17.43 | 62.17 | 270.67 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 2604.61 | 13.55 | 48.50 | 333.83 | 1548.87 | 12.65 | 0.00 | 297.83 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-06:19 | 2822.92 | 10.23 | 0.00 | 388.33 | 1814.51 | 12.68 | 1.33 | 350.33 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 3133.54 | 9.69 | 0.00 | 408.17 | 1441.93 | 14.65 | 47.83 | 372.50 |
July | 417.33 | 0.63 | 0.61 | 01-JUL-06:40 | 3654.71 | 9.99 | 3.67 | 396.67 | 1679.75 | 14.08 | 31.50 | 364.17 |
August | 421.33 | 0.64 | 0.61 | 01-AUG-06:30 | 2672.36 | 12.59 | 56.83 | 372.83 | 1577.92 | 11.84 | 0.00 | 339.83 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:00 | 2626.42 | 14.71 | 72.33 | 314.00 | 1146.45 | 12.21 | 5.50 | 277.17 |
October | 317.67 | 0.64 | 0.61 | 01-OCT-07:00 | 1610.76 | 13.91 | 53.67 | 270.33 | 1000.67 | 15.61 | 49.33 | 231.33 |
November | 269.50 | 0.65 | 0.61 | 01-NOV-08:20 | 1569.91 | 16.78 | 78.83 | 211.67 | 867.46 | 16.20 | 52.50 | 170.67 |
December | 236.83 | 0.66 | 0.61 | 01-DEC-09:09 | 953.07 | 14.74 | 54.00 | 192.67 | 623.38 | 16.44 | 49.83 | 145.50 |
Annual Sum or Average | 3965.83 | 0.64 | 2424.25 | 13.38 | 582.33 | 3616.67 | 1313.13 | 14.51 | 406.83 | 3168.17 | ||
Minimum of Months | 226.83 | 0.63 | 0.61 | 953.07 | 9.69 | 0.00 | 192.67 | 623.38 | 11.84 | 0.00 | 145.50 | |
Maximum of Months | 434.17 | 0.66 | 0.61 | 3654.71 | 17.12 | 78.83 | 408.17 | 1814.51 | 17.98 | 62.17 | 372.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.307740E+11 | 78379.64 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144052E+11 | 60096.07 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.551863E+10 | 49910.69 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341869E+09 | 21350.25 | 29-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.347120E+09 | 15750.31 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23429063.58 | 3229.47 | 20-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261805E+09 | 11494.23 | 05-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.292663E+10 | 37294.45 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140900E+11 | 64499.47 | 29-DEC-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.686887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.307740E+11 | 78379.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.350505E+10 | 15101.01 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111393E+10 | 15330.00 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252386E+09 | 14039.86 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 258923.08 | 750.01 | 29-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3232001.54 | 1041.21 | 08-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136052E+09 | 14052.35 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.837442E+09 | 15138.26 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.584835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.350505E+10 | 15330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.334058E+10 | 16329.77 | 18-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143250E+10 | 16360.49 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.524933E+09 | 15936.79 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67796317.61 | 11212.01 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39677463.37 | 15593.71 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5460753.98 | 1073.48 | 13-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 47787231.71 | 5320.48 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.492060E+09 | 15913.36 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160253E+10 | 16383.04 | 14-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.755332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.334058E+10 | 16383.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.390686E+10 | 23248.46 | 18-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135058E+10 | 23391.35 | 23-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.552121E+09 | 22004.34 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81272889.73 | 23019.90 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125868E+09 | 23125.32 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 60391.77 | 402.61 | 17-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12985109.20 | 2127.23 | 19-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 55922434.18 | 15178.61 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.486619E+09 | 23233.98 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146394E+10 | 23332.40 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.803622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.390686E+10 | 23391.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.247536E+10 | 15236.59 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.553614E+09 | 15221.11 | 09-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 75727768.96 | 15221.91 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9565486.91 | 8328.73 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40909678.65 | 15221.46 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195088E+09 | 15217.33 | 29-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.247536E+10 | 15236.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.403999E+12 | 833963.52 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220774E+12 | 655764.29 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115505E+12 | 557085.36 | 06-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219481E+11 | 263998.85 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144372E+11 | 202179.07 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.229272E+09 | 68273.86 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216361E+10 | 87116.10 | 19-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174230E+11 | 265625.57 | 10-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.900261E+11 | 441046.85 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254949E+12 | 709780.43 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114145E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.403999E+12 | 833963.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117826E+11 | 642875.84 | 10-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.333629E+10 | 635078.82 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137260E+10 | 642124.48 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.712175E+09 | 640199.09 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386562E+10 | 642282.23 | 26-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117826E+11 | 642875.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102670E+12 | 133107.39 | 31-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.533363E+11 | 133412.94 | 06-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.277940E+11 | 142909.14 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.520309E+10 | 143001.23 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.365258E+10 | 143247.66 | 04-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1419473.38 | 5854.62 | 17-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 186887.26 | 1557.39 | 18-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.899916E+09 | 138161.90 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.452204E+10 | 143704.09 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.266756E+11 | 143632.44 | 09-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.668704E+11 | 133447.29 | 18-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.291625E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102670E+12 | 143704.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.793490E+11 | 184149.74 | 30-JAN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421824E+11 | 184608.36 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.254396E+11 | 184124.82 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.715376E+10 | 182610.23 | 15-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.465947E+10 | 193036.84 | 23-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190430E+09 | 24793.72 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 68960200.81 | 34470.55 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191898E+10 | 119092.67 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.671163E+10 | 183062.07 | 11-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.266599E+11 | 190651.09 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.568988E+11 | 184206.92 | 26-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251233E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.793490E+11 | 193036.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.777151E+11 | 223159.04 | 31-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.347284E+11 | 223555.38 | 06-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225111E+11 | 222416.67 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.691952E+10 | 221063.58 | 15-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.593935E+10 | 237501.07 | 22-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.232104E+09 | 44469.25 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100252E+09 | 26342.15 | 18-AUG-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125527E+10 | 133719.14 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341821E+10 | 221059.37 | 11-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207624E+11 | 222439.38 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.485561E+11 | 223053.34 | 26-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222138E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.777151E+11 | 237501.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.752637E+11 | 197527.64 | 30-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.383262E+11 | 196213.65 | 09-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240793E+11 | 197873.96 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.625283E+10 | 195847.52 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.439794E+10 | 198322.92 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.230554E+09 | 29807.32 | 17-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122898E+09 | 26769.74 | 18-AUG-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.198519E+10 | 105074.18 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.631465E+10 | 192079.96 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232151E+11 | 197894.85 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.496445E+11 | 196250.95 | 16-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229833E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.752637E+11 | 198322.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.475527E+11 | 89110.48 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260495E+11 | 71469.67 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165262E+11 | 62893.92 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.501516E+10 | 33551.74 | 29-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.293757E+10 | 25563.45 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112422E+09 | 10150.22 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 434926.66 | 749.25 | 18-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.793977E+09 | 14422.64 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.373162E+10 | 32380.73 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126137E+11 | 47193.63 | 27-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.320975E+11 | 78742.78 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147431E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.475527E+11 | 89110.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150748E+11 | 80751.44 | 02-JAN-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.642978E+10 | 80671.88 | 21-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.355996E+10 | 80468.65 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.407157E+09 | 79617.08 | 10-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.921421E+09 | 80639.09 | 08-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1116086.75 | 730.39 | 19-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.543820E+09 | 80601.59 | 10-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.393014E+10 | 80599.99 | 20-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.927172E+10 | 80480.68 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.150748E+11 | 80751.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187292E+11 | 16871.31 | 13-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107020E+11 | 16848.64 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.750368E+10 | 16852.57 | 13-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.266452E+10 | 16860.79 | 10-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181082E+10 | 16847.64 | 01-MAY-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89248435.13 | 16730.20 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 51136479.22 | 16775.31 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.823461E+09 | 16828.90 | 14-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.267787E+10 | 16889.96 | 10-OCT-04:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.765841E+10 | 16863.45 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142313E+11 | 16840.24 | 09-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.669417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187292E+11 | 16889.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127779E+11 | 18510.74 | 12-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.701136E+10 | 18519.88 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.494976E+10 | 18484.67 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186969E+10 | 18422.18 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126142E+10 | 18500.99 | 08-MAY-04:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92708234.54 | 18391.86 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6315839.09 | 1929.68 | 05-JUL-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 54906063.51 | 12495.54 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.648484E+09 | 18398.53 | 13-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184745E+10 | 18483.33 | 10-OCT-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.539429E+10 | 18482.03 | 29-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.992310E+10 | 18473.88 | 02-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6315839.09 | 1929.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127779E+11 | 18519.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144157E+11 | 24081.77 | 23-JAN-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705826E+10 | 24123.42 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.563984E+10 | 24102.45 | 10-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.249950E+10 | 24057.79 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199787E+10 | 24115.19 | 08-MAY-04:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.241683E+09 | 23969.97 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13369674.08 | 2521.05 | 08-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88997247.17 | 19281.09 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.753252E+09 | 24017.62 | 12-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176070E+10 | 24133.50 | 10-OCT-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.523980E+10 | 24098.75 | 22-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105058E+11 | 24105.11 | 19-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.502148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13369674.08 | 2521.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144157E+11 | 24133.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124166E+11 | 21052.79 | 18-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.650844E+10 | 21048.25 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.493395E+10 | 21001.75 | 04-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189034E+10 | 21046.00 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132890E+10 | 21056.53 | 22-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174499E+09 | 12411.80 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2735678.76 | 464.77 | 08-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80894238.45 | 12330.69 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.771192E+09 | 20911.02 | 19-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196356E+10 | 21040.87 | 10-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.486095E+10 | 21091.19 | 29-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.878715E+10 | 21033.08 | 04-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.437192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2735678.76 | 464.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124166E+11 | 21091.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.388718E+09 | 24991.53 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.388718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.388718E+09 | 24991.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.631469E+09 | 0.631469E+09 | 42298.79 | 27-FEB-15:30 | 42298.79 | 0.00 |
March | 0.00 | 0.00 | 34245100.02 | 34245100.02 | 6873.66 | 14-MAR-13:30 | 6873.66 | 0.00 |
April | 0.00 | 0.00 | 0.661475E+10 | 0.661475E+10 | 84147.20 | 07-APR-14:00 | 84147.20 | 0.00 |
May | 0.00 | 0.00 | 0.181362E+11 | 0.181362E+11 | 110739.54 | 19-MAY-15:20 | 110739.54 | 0.02 |
June | 0.00 | 0.00 | 0.599180E+11 | 0.598665E+11 | 127546.54 | 29-JUN-14:50 | 127546.54 | 0.17 |
July | 0.00 | 0.00 | 0.102793E+12 | 0.102626E+12 | 153583.55 | 17-JUL-15:20 | 153583.55 | 0.30 |
August | 0.00 | 0.00 | 0.950781E+11 | 0.950781E+11 | 153907.64 | 07-AUG-15:20 | 153907.64 | 0.14 |
September | 0.00 | 0.00 | 0.388729E+11 | 0.376260E+11 | 195729.35 | 07-SEP-15:00 | 103894.21 | 0.10 |
October | 0.00 | 0.00 | 0.105474E+11 | 0.105474E+11 | 102919.20 | 18-OCT-15:50 | 102919.20 | 0.00 |
November | 0.00 | 0.00 | 0.560038E+09 | 0.560038E+09 | 18833.65 | 17-NOV-17:00 | 18833.65 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.333186E+12 | 0.331721E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102793E+12 | 0.102626E+12 | 195729.35 | 153907.64 | 0.30 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 22025.30 | 22025.30 | 3.82 | 02-JAN-05:43 | 3.82 | 0.00 |
February | 0.00 | 0.00 | 0.449454E+10 | 0.449454E+10 | 298207.97 | 27-FEB-13:50 | 298207.97 | 0.00 |
March | 0.00 | 0.00 | 95868854.75 | 95868854.75 | 21490.08 | 14-MAR-13:40 | 21490.08 | 0.00 |
April | 0.00 | 0.00 | 0.465868E+11 | 0.465868E+11 | 634436.50 | 06-APR-16:00 | 634436.50 | 0.00 |
May | 0.00 | 0.00 | 0.153363E+12 | 0.153363E+12 | 1047502.37 | 19-MAY-15:30 | 1047502.37 | 0.02 |
June | 0.00 | 0.00 | 0.507393E+12 | 0.506952E+12 | 1202902.78 | 29-JUN-14:50 | 1202902.78 | 0.15 |
July | 0.00 | 0.00 | 0.851486E+12 | 0.850458E+12 | 1392153.47 | 17-JUL-15:30 | 1392153.47 | 0.27 |
August | 0.00 | 0.00 | 0.737744E+12 | 0.737744E+12 | 1322502.29 | 10-AUG-15:40 | 1322502.29 | 0.12 |
September | 0.00 | 0.00 | 0.339029E+12 | 0.327943E+12 | 1792594.27 | 07-SEP-15:00 | 952755.13 | 0.09 |
October | 0.00 | 0.00 | 0.830409E+11 | 0.830409E+11 | 851650.27 | 18-OCT-15:00 | 851650.27 | 0.00 |
November | 0.00 | 0.00 | 0.402796E+10 | 0.402796E+10 | 131398.09 | 17-NOV-17:00 | 131398.09 | 0.00 |
December | 0.00 | 0.00 | 85216.38 | 85216.38 | 1.39 | 21-DEC-15:00 | 1.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.272726E+13 | 0.271471E+13 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 22025.30 | 22025.30 | 1.39 | 1.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.851486E+12 | 0.850458E+12 | 1792594.27 | 1392153.47 | 0.27 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 59233.01 | 59233.01 | 471.39 | 17-JAN-04:52 | 471.39 | 0.00 |
February | 0.00 | 0.00 | 0.319283E+09 | 0.319283E+09 | 21923.36 | 26-FEB-14:21 | 21923.36 | 0.00 |
March | 0.00 | 0.00 | 2115474.09 | 2115474.09 | 1667.83 | 04-MAR-05:41 | 1667.83 | 0.00 |
April | 0.00 | 0.00 | 0.433904E+10 | 0.433904E+10 | 64046.14 | 06-APR-16:00 | 64046.14 | 0.00 |
May | 0.00 | 0.00 | 0.159500E+11 | 0.159500E+11 | 125734.12 | 19-MAY-15:30 | 125734.12 | 0.02 |
June | 0.00 | 0.00 | 0.557763E+11 | 0.557211E+11 | 143214.45 | 29-JUN-15:00 | 143214.45 | 0.15 |
July | 0.00 | 0.00 | 0.941281E+11 | 0.940337E+11 | 169657.20 | 17-JUL-15:30 | 169657.20 | 0.27 |
August | 0.00 | 0.00 | 0.794769E+11 | 0.794769E+11 | 157975.35 | 07-AUG-15:40 | 157975.35 | 0.12 |
September | 0.00 | 0.00 | 0.347387E+11 | 0.336262E+11 | 183238.71 | 07-SEP-15:20 | 105335.70 | 0.09 |
October | 0.00 | 0.00 | 0.713518E+10 | 0.713518E+10 | 88699.86 | 18-OCT-15:00 | 88699.86 | 0.00 |
November | 0.00 | 0.00 | 0.301718E+09 | 0.301718E+09 | 10754.42 | 17-NOV-17:00 | 10754.42 | 0.00 |
December | 0.00 | 0.00 | 1767.86 | 1767.86 | 0.37 | 01-DEC-06:25 | 0.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.292167E+12 | 0.290905E+12 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 1767.86 | 1767.86 | 0.37 | 0.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.941281E+11 | 0.940337E+11 | 183238.71 | 169657.20 | 0.27 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 483334.78 | 483334.78 | 5566.60 | 24-JAN-05:01 | 5566.60 | 0.00 |
February | 0.00 | 0.00 | 0.261761E+09 | 0.261761E+09 | 23743.59 | 27-FEB-15:00 | 23743.59 | 0.00 |
March | 0.00 | 0.00 | 10369.74 | 10369.74 | 17.28 | 06-MAR-20:00 | 17.28 | 0.00 |
April | 0.00 | 0.00 | 0.231208E+10 | 0.231208E+10 | 49353.32 | 07-APR-14:00 | 49353.32 | 0.00 |
May | 0.00 | 0.00 | 0.883342E+10 | 0.883342E+10 | 70670.19 | 29-MAY-14:30 | 70670.19 | 0.02 |
June | 0.00 | 0.00 | 0.311339E+11 | 0.311222E+11 | 67672.65 | 26-JUN-11:00 | 67672.65 | 0.12 |
July | 0.00 | 0.00 | 0.530670E+11 | 0.530396E+11 | 109277.90 | 19-JUL-03:02 | 71895.67 | 0.22 |
August | 0.00 | 0.00 | 0.493011E+11 | 0.493011E+11 | 107536.15 | 06-AUG-17:27 | 107536.15 | 0.12 |
September | 0.00 | 0.00 | 0.203694E+11 | 0.200026E+11 | 123411.10 | 04-SEP-17:21 | 123411.10 | 0.08 |
October | 0.00 | 0.00 | 0.573405E+10 | 0.573405E+10 | 59639.08 | 18-OCT-14:00 | 59639.08 | 0.00 |
November | 0.00 | 0.00 | 68497280.37 | 68497280.37 | 25354.47 | 17-NOV-06:03 | 25354.47 | 0.00 |
December | 0.00 | 0.00 | 60297.63 | 60297.63 | 59.02 | 27-DEC-17:00 | 59.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.171082E+12 | 0.170676E+12 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 10369.74 | 10369.74 | 17.28 | 17.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.530670E+11 | 0.530396E+11 | 123411.10 | 123411.10 | 0.22 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.361894E+12 | 0.328237E+12 | 142941.73 | 18-JAN-22:01 | 128968.58 | 0.00 |
February | 0.00 | 0.00 | 0.575724E+12 | 0.521962E+12 | 245398.86 | 27-FEB-22:03 | 222099.23 | 0.00 |
March | 0.00 | 0.00 | 0.910631E+12 | 0.827777E+12 | 440819.95 | 31-MAR-24:00 | 400344.89 | 0.00 |
April | 0.00 | 0.00 | 0.114518E+13 | 0.104327E+13 | 449692.72 | 24-APR-21:02 | 407430.76 | 0.00 |
May | 0.00 | 0.00 | 0.375766E+12 | 0.342794E+12 | 238067.17 | 31-MAY-24:00 | 217604.10 | 0.00 |
June | 0.00 | 0.00 | 0.620352E+12 | 0.573444E+12 | 330249.59 | 30-JUN-23:02 | 309039.51 | 0.00 |
July | 0.00 | 0.00 | 0.894884E+12 | 0.842211E+12 | 427103.05 | 31-JUL-24:00 | 400827.11 | 0.00 |
August | 0.00 | 0.00 | 0.116120E+13 | 0.108112E+13 | 456734.48 | 04-AUG-00:25 | 411628.79 | 0.00 |
September | 0.00 | 0.00 | 0.366935E+12 | 0.336783E+12 | 238748.02 | 30-SEP-24:00 | 217328.36 | 0.00 |
October | 0.00 | 0.00 | 0.649195E+12 | 0.590735E+12 | 340945.21 | 31-OCT-24:00 | 309906.43 | 0.00 |
November | 0.00 | 0.00 | 0.889805E+12 | 0.806754E+12 | 349085.01 | 06-NOV-22:03 | 315596.37 | 0.00 |
December | 0.00 | 0.00 | 0.118267E+13 | 0.107452E+13 | 448631.08 | 07-DEC-24:00 | 406789.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.913423E+13 | 0.836961E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.361894E+12 | 0.328237E+12 | 142941.73 | 128968.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.118267E+13 | 0.108112E+13 | 456734.48 | 411628.79 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.292943E+10 | 0.292912E+10 | 2213.04 | 13-JAN-16:20 | 2213.04 | 0.00 |
February | 0.00 | 0.00 | 0.821852E+10 | 0.821852E+10 | 4835.78 | 26-FEB-17:14 | 4835.78 | 0.00 |
March | 0.00 | 0.00 | 0.149235E+11 | 0.149235E+11 | 7458.73 | 31-MAR-24:00 | 7458.73 | 0.00 |
April | 0.00 | 0.00 | 0.200314E+11 | 0.200239E+11 | 8875.20 | 22-APR-18:10 | 8875.20 | 0.00 |
May | 0.00 | 0.00 | 0.562191E+10 | 0.560040E+10 | 4145.25 | 31-MAY-24:00 | 4145.25 | 0.00 |
June | 0.00 | 0.00 | 0.109113E+11 | 0.108315E+11 | 5989.05 | 30-JUN-23:12 | 5989.05 | 0.00 |
July | 0.00 | 0.00 | 0.165864E+11 | 0.164977E+11 | 7894.49 | 31-JUL-23:40 | 7894.49 | 0.00 |
August | 0.00 | 0.00 | 0.215881E+11 | 0.215254E+11 | 8876.31 | 05-AUG-19:57 | 8876.31 | 0.00 |
September | 0.00 | 0.00 | 0.571231E+10 | 0.563016E+10 | 3952.88 | 30-SEP-24:00 | 3952.88 | 0.00 |
October | 0.00 | 0.00 | 0.105331E+11 | 0.105225E+11 | 5595.08 | 31-OCT-24:00 | 5595.08 | 0.00 |
November | 0.00 | 0.00 | 0.146199E+11 | 0.146182E+11 | 6539.94 | 03-NOV-16:00 | 6485.12 | 0.00 |
December | 0.00 | 0.00 | 0.194867E+11 | 0.194865E+11 | 8258.67 | 10-DEC-16:10 | 8258.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151163E+12 | 0.150808E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.292943E+10 | 0.292912E+10 | 2213.04 | 2213.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.215881E+11 | 0.215254E+11 | 8876.31 | 8876.31 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.857650E+10 | 0.857355E+10 | 18216.38 | 13-JAN-16:30 | 18216.38 | 0.00 |
February | 0.00 | 0.00 | 0.591237E+11 | 0.591237E+11 | 42953.71 | 28-FEB-17:00 | 42953.71 | 0.00 |
March | 0.00 | 0.00 | 0.124326E+12 | 0.124326E+12 | 65101.25 | 31-MAR-23:30 | 65101.25 | 0.00 |
April | 0.00 | 0.00 | 0.179642E+12 | 0.179566E+12 | 82573.71 | 25-APR-18:00 | 82573.71 | 0.00 |
May | 0.00 | 0.00 | 0.453654E+11 | 0.451545E+11 | 39166.80 | 31-MAY-24:00 | 39166.80 | 0.00 |
June | 0.00 | 0.00 | 0.100389E+12 | 0.995931E+11 | 58527.79 | 30-JUN-23:55 | 58527.79 | 0.00 |
July | 0.00 | 0.00 | 0.156653E+12 | 0.155766E+12 | 76788.16 | 31-JUL-23:53 | 76788.16 | 0.00 |
August | 0.00 | 0.00 | 0.202839E+12 | 0.202210E+12 | 84672.67 | 03-AUG-18:50 | 84672.67 | 0.00 |
September | 0.00 | 0.00 | 0.480861E+11 | 0.472823E+11 | 34809.25 | 30-SEP-23:40 | 34809.25 | 0.00 |
October | 0.00 | 0.00 | 0.877275E+11 | 0.876218E+11 | 47518.81 | 31-OCT-24:00 | 47518.81 | 0.00 |
November | 0.00 | 0.00 | 0.120793E+12 | 0.120776E+12 | 60246.14 | 03-NOV-16:00 | 59699.37 | 0.00 |
December | 0.00 | 0.00 | 0.158891E+12 | 0.158888E+12 | 74945.28 | 06-DEC-16:10 | 74671.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129241E+13 | 0.128888E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.857650E+10 | 0.857355E+10 | 18216.38 | 18216.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202839E+12 | 0.202210E+12 | 84672.67 | 84672.67 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.243203E+09 | 0.243203E+09 | 1723.69 | 13-JAN-16:30 | 1723.69 | 0.00 |
February | 0.00 | 0.00 | 0.427161E+10 | 0.427161E+10 | 4244.96 | 28-FEB-17:00 | 4244.96 | 0.00 |
March | 0.00 | 0.00 | 0.107834E+11 | 0.107834E+11 | 6162.30 | 28-MAR-17:50 | 6162.30 | 0.00 |
April | 0.00 | 0.00 | 0.167733E+11 | 0.167658E+11 | 8322.34 | 25-APR-18:00 | 8322.34 | 0.00 |
May | 0.00 | 0.00 | 0.383926E+10 | 0.381852E+10 | 3844.10 | 31-MAY-24:00 | 3844.10 | 0.00 |
June | 0.00 | 0.00 | 0.981859E+10 | 0.973923E+10 | 5863.59 | 30-JUN-23:55 | 5863.59 | 0.00 |
July | 0.00 | 0.00 | 0.156086E+11 | 0.155200E+11 | 7643.11 | 31-JUL-23:53 | 7643.11 | 0.00 |
August | 0.00 | 0.00 | 0.201452E+11 | 0.200825E+11 | 8604.14 | 05-AUG-19:53 | 8604.14 | 0.00 |
September | 0.00 | 0.00 | 0.424334E+10 | 0.416419E+10 | 3367.31 | 04-SEP-17:32 | 3367.31 | 0.00 |
October | 0.00 | 0.00 | 0.736129E+10 | 0.735096E+10 | 4584.13 | 18-OCT-16:50 | 4584.13 | 0.00 |
November | 0.00 | 0.00 | 0.101784E+11 | 0.101767E+11 | 5951.50 | 03-NOV-16:00 | 5896.96 | 0.00 |
December | 0.00 | 0.00 | 0.138504E+11 | 0.138502E+11 | 7397.97 | 06-DEC-16:10 | 7372.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117117E+12 | 0.116766E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.243203E+09 | 0.243203E+09 | 1723.69 | 1723.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201452E+11 | 0.200825E+11 | 8604.14 | 8604.14 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 339023.58 | 1926652.15 | 09-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 194719.19 | 1989661.92 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 98721.51 | 1928193.29 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23822.29 | 1360847.79 | 29-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16234.50 | 1555198.13 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 607.54 | 183589.52 | 17-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 7.81 | 3713.59 | 08-JUL-05:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 209.91 | 173688.76 | 18-AUG-05:02 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 4609.77 | 867742.81 | 19-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 19000.69 | 1598765.11 | 10-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 88671.10 | 1698994.42 | 27-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 216068.91 | 2009651.10 | 26-DEC-05:11 |
Annual Sum or Average | 0.00 | 83152.69 | ||||
Minimum of Months | 0.00 | 0.00 | 7.81 | 3713.59 | ||
Maximum of Months | 0.00 | 0.00 | 339023.58 | 2009651.10 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 492.76 | 23956.38 | 18-JAN-04:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 6290.69 | 767570.65 | 27-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 2634.02 | 92255.96 | 14-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46677.36 | 1218246.89 | 06-APR-15:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 129871.09 | 1352656.72 | 19-MAY-15:30 | 6.53 | 61494.16 | 14-MAY-10:22 |
June | 350670.30 | 1544209.36 | 29-JUN-15:00 | 16.05 | 69554.18 | 12-JUN-03:02 |
July | 538512.08 | 1804877.51 | 17-JUL-15:30 | 63.19 | 163386.19 | 15-JUL-02:52 |
August | 467117.07 | 1708601.32 | 07-AUG-15:40 | 54.45 | 126076.41 | 20-AUG-20:23 |
September | 259380.66 | 2396542.22 | 07-SEP-15:00 | 36.76 | 132020.91 | 24-SEP-08:53 |
October | 71738.30 | 1216199.05 | 16-OCT-13:30 | 0.24 | 5264.00 | 22-OCT-17:02 |
November | 6254.82 | 353838.65 | 17-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1290.11 | 24000.82 | 27-DEC-17:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 157882.06 | 14.91 | ||||
Minimum of Months | 492.76 | 23956.38 | 0.00 | 0.00 | ||
Maximum of Months | 538512.08 | 2396542.22 | 63.19 | 163386.19 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 34.41 | 24-JAN-05:01 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2825.94 | 481998.94 | 27-FEB-13:40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 75.00 | 42390.25 | 14-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27727.77 | 944406.12 | 06-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84618.46 | 1342256.31 | 19-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 281411.46 | 1534118.04 | 29-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 447169.61 | 1795623.09 | 17-JUL-15:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 390756.16 | 1700251.12 | 07-AUG-15:40 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 188723.01 | 2397394.92 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 47084.92 | 1218975.67 | 18-OCT-14:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2414.33 | 203637.87 | 17-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.06 | 58.19 | 27-DEC-17:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 123693.85 | 0.00 | ||||
Minimum of Months | 0.00 | 34.41 | 0.00 | 0.00 | ||
Maximum of Months | 447169.61 | 2397394.92 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 179034.94 | 203429.85 | 13-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 339907.49 | 611324.26 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 496610.59 | 646331.74 | 31-MAR-24:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 704405.74 | 1331712.83 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 257424.13 | 977536.06 | 20-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 577175.23 | 1382428.54 | 29-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 973324.80 | 1963229.89 | 17-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1128273.56 | 2079262.87 | 06-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 340455.72 | 1248242.38 | 02-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 387534.22 | 964208.46 | 18-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 506922.86 | 752941.62 | 17-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 640762.49 | 770295.67 | 10-DEC-02:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 546131.79 | 0.00 | ||||
Minimum of Months | 179034.94 | 203429.85 | 0.00 | 0.00 | ||
Maximum of Months | 1128273.56 | 2079262.87 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17330.34 | 58856.19 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17710.01 | 59175.84 | 23-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 18546.15 | 59076.98 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 16883.10 | 57464.84 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16524.78 | 54983.52 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15933.46 | 51687.31 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14098.76 | 48649.95 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 14985.47 | 46963.74 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 14315.64 | 48068.79 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14900.62 | 50877.81 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15950.63 | 54068.05 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 16274.20 | 56868.56 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 16111.88 | ||||
Minimum of Months | 0.00 | 0.00 | 14098.76 | 46963.74 | ||
Maximum of Months | 0.00 | 0.00 | 18546.15 | 59175.84 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 18.01 | 25051.42 | 17-JAN-07:00 | 528.57 | 116000.37 | 19-JAN-06:30 |
February | 2575.33 | 458702.71 | 27-FEB-15:30 | 1778.14 | 138377.22 | 16-FEB-14:40 |
March | 150.96 | 52307.38 | 14-MAR-13:20 | 2823.17 | 137969.83 | 30-MAR-12:30 |
April | 27118.59 | 883898.27 | 06-APR-16:00 | 3109.58 | 138706.99 | 28-APR-15:20 |
May | 90919.87 | 2271897.48 | 19-MAY-15:30 | 2253.60 | 137986.30 | 03-MAY-13:40 |
June | 329930.68 | 2560561.27 | 20-JUN-15:40 | 889.27 | 87488.84 | 14-JUN-17:20 |
July | 543119.95 | 2607154.70 | 19-JUL-12:20 | 550.89 | 61079.90 | 05-JUL-12:10 |
August | 469393.00 | 2300545.91 | 05-AUG-14:20 | 1415.82 | 75695.57 | 12-AUG-02:55 |
September | 221813.06 | 4512479.33 | 07-SEP-15:00 | 1787.05 | 111934.85 | 18-SEP-11:40 |
October | 47414.29 | 1938263.51 | 18-OCT-14:50 | 2553.75 | 121425.93 | 03-OCT-09:00 |
November | 2070.83 | 231704.75 | 17-NOV-17:00 | 2314.02 | 141333.30 | 26-NOV-22:02 |
December | 77.57 | 24700.86 | 08-DEC-14:10 | 1431.62 | 137204.81 | 14-DEC-13:50 |
Annual Sum or Average | 145709.61 | 1783.74 | ||||
Minimum of Months | 18.01 | 24700.86 | 528.57 | 61079.90 | ||
Maximum of Months | 543119.95 | 4512479.33 | 3109.58 | 141333.30 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162493E+11 | 0.88 | 10977.79 | 01-JAN-00:10 | 1.59 |
February | 0.144709E+11 | 0.87 | 10977.79 | 01-FEB-06:03 | 1.60 |
March | 0.174156E+11 | 0.94 | 10977.79 | 01-MAR-04:30 | 1.59 |
April | 0.161896E+11 | 0.91 | 10977.79 | 01-APR-04:01 | 1.60 |
May | 0.172389E+11 | 0.93 | 10977.79 | 01-MAY-03:01 | 1.59 |
June | 0.172626E+11 | 0.96 | 10977.79 | 01-JUN-03:02 | 1.58 |
July | 0.172372E+11 | 0.93 | 10977.79 | 01-JUL-03:02 | 1.57 |
August | 0.188642E+11 | 1.02 | 10977.79 | 01-AUG-03:02 | 1.58 |
September | 0.176503E+11 | 0.98 | 10977.79 | 01-SEP-03:02 | 1.58 |
October | 0.173438E+11 | 0.94 | 10977.79 | 01-OCT-24:00 | 1.58 |
November | 0.165060E+11 | 0.92 | 10977.79 | 01-NOV-03:10 | 1.60 |
December | 0.160803E+11 | 0.87 | 10977.79 | 01-DEC-05:01 | 1.60 |
Annual Sum or Average | 0.202509E+12 | 0.93 | |||
Minimum of Months | 0.144709E+11 | 0.87 | 10977.79 | 1.57 | |
Maximum of Months | 0.188642E+11 | 1.02 | 10977.79 | 1.60 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.467664E+10 | 0.38 | 16259.86 | 18-JAN-06:01 | 1.64 |
February | 0.518639E+10 | 0.40 | 16259.86 | 07-FEB-06:01 | 1.63 |
March | 0.768867E+10 | 0.48 | 13925.18 | 07-MAR-06:01 | 1.48 |
April | 0.933259E+10 | 0.54 | 18698.99 | 24-APR-14:50 | 1.78 |
May | 0.852548E+10 | 0.50 | 18636.64 | 30-MAY-05:03 | 1.76 |
June | 0.129105E+11 | 0.68 | 24814.88 | 22-JUN-05:02 | 2.11 |
July | 0.158946E+11 | 0.76 | 24814.88 | 17-JUL-05:02 | 2.11 |
August | 0.174352E+11 | 0.83 | 24814.88 | 07-AUG-05:02 | 2.12 |
September | 0.955195E+10 | 0.56 | 20542.00 | 01-SEP-16:00 | 1.87 |
October | 0.853678E+10 | 0.49 | 16714.64 | 16-OCT-15:50 | 1.66 |
November | 0.722493E+10 | 0.46 | 14605.94 | 13-NOV-06:01 | 1.53 |
December | 0.623312E+10 | 0.41 | 16259.86 | 16-DEC-06:02 | 1.64 |
Annual Sum or Average | 0.113197E+12 | 0.54 | |||
Minimum of Months | 0.467664E+10 | 0.38 | 13925.18 | 1.48 | |
Maximum of Months | 0.174352E+11 | 0.83 | 24814.88 | 2.12 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.445872E+11 | 0.42 | 61109.06 | 09-JAN-05:01 | 0.96 |
February | 0.401120E+11 | 0.40 | 75899.62 | 28-FEB-16:00 | 1.08 |
March | 0.506749E+11 | 0.42 | 140377.59 | 30-MAR-05:02 | 1.56 |
April | 0.537990E+11 | 0.41 | 146523.60 | 10-APR-05:01 | 1.61 |
May | 0.636069E+11 | 0.44 | 177469.14 | 22-MAY-04:01 | 1.80 |
June | 0.989918E+11 | 0.59 | 214937.32 | 21-JUN-05:03 | 2.02 |
July | 0.118348E+12 | 0.63 | 229904.72 | 18-JUL-05:02 | 2.12 |
August | 0.115825E+12 | 0.63 | 217455.37 | 07-AUG-03:02 | 2.05 |
September | 0.743134E+11 | 0.49 | 212890.07 | 05-SEP-03:02 | 2.01 |
October | 0.557654E+11 | 0.40 | 136861.24 | 05-OCT-05:03 | 1.54 |
November | 0.450663E+11 | 0.38 | 155568.53 | 06-NOV-06:01 | 1.67 |
December | 0.437815E+11 | 0.40 | 61109.06 | 26-DEC-05:11 | 0.96 |
Annual Sum or Average | 0.804871E+12 | 0.47 | |||
Minimum of Months | 0.401120E+11 | 0.38 | 61109.06 | 0.96 | |
Maximum of Months | 0.118348E+12 | 0.63 | 229904.72 | 2.12 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.573410E+10 | 0.50 | 5663.00 | 02-JAN-04:11 | 0.86 |
February | 0.450550E+10 | 0.44 | 5663.00 | 01-FEB-05:01 | 0.87 |
March | 0.481016E+10 | 0.42 | 5694.99 | 28-MAR-16:00 | 0.87 |
April | 0.453039E+10 | 0.38 | 11621.02 | 25-APR-16:00 | 1.30 |
May | 0.568372E+10 | 0.41 | 17143.44 | 19-MAY-15:40 | 1.64 |
June | 0.932005E+10 | 0.53 | 20232.69 | 29-JUN-14:50 | 1.82 |
July | 0.116491E+11 | 0.58 | 25662.76 | 17-JUL-15:00 | 2.11 |
August | 0.108198E+11 | 0.57 | 24038.74 | 10-AUG-15:50 | 2.03 |
September | 0.637016E+10 | 0.44 | 17965.07 | 01-SEP-16:00 | 1.69 |
October | 0.444869E+10 | 0.36 | 10377.51 | 18-OCT-16:00 | 1.21 |
November | 0.444823E+10 | 0.40 | 5663.00 | 06-NOV-06:01 | 0.86 |
December | 0.527489E+10 | 0.47 | 5663.00 | 01-DEC-06:01 | 0.86 |
Annual Sum or Average | 0.775948E+11 | 0.46 | |||
Minimum of Months | 0.444823E+10 | 0.36 | 5663.00 | 0.86 | |
Maximum of Months | 0.116491E+11 | 0.58 | 25662.76 | 2.11 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108099E+12 | 1.54 | 40359.42 | 01-JAN-00:10 | 1.54 |
February | 0.976375E+11 | 1.54 | 40359.42 | 01-FEB-00:10 | 1.54 |
March | 0.108099E+12 | 1.54 | 40359.42 | 01-MAR-00:10 | 1.54 |
April | 0.104612E+12 | 1.54 | 40359.42 | 01-APR-00:10 | 1.54 |
May | 0.108099E+12 | 1.54 | 40359.42 | 01-MAY-00:05 | 1.54 |
June | 0.104612E+12 | 1.54 | 40359.42 | 01-JUN-00:10 | 1.54 |
July | 0.108099E+12 | 1.54 | 40359.42 | 01-JUL-00:10 | 1.54 |
August | 0.108099E+12 | 1.54 | 40359.42 | 01-AUG-00:05 | 1.54 |
September | 0.104612E+12 | 1.54 | 40359.42 | 01-SEP-00:02 | 1.54 |
October | 0.108099E+12 | 1.54 | 40359.42 | 01-OCT-00:10 | 1.54 |
November | 0.104612E+12 | 1.54 | 40359.42 | 01-NOV-00:10 | 1.54 |
December | 0.108099E+12 | 1.54 | 40359.42 | 01-DEC-00:10 | 1.54 |
Annual Sum or Average | 0.127277E+13 | 1.54 | |||
Minimum of Months | 0.976375E+11 | 1.54 | 40359.42 | 1.54 | |
Maximum of Months | 0.108099E+12 | 1.54 | 40359.42 | 1.54 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.171008E+10 | 1.05 | 638.47 | 01-JAN-00:05 | 1.05 |
February | 0.154459E+10 | 1.05 | 638.47 | 01-FEB-00:10 | 1.05 |
March | 0.171008E+10 | 1.05 | 638.47 | 01-MAR-00:10 | 1.05 |
April | 0.165491E+10 | 1.05 | 638.47 | 01-APR-00:10 | 1.05 |
May | 0.171008E+10 | 1.05 | 638.47 | 01-MAY-00:05 | 1.05 |
June | 0.165491E+10 | 1.05 | 638.47 | 01-JUN-00:10 | 1.05 |
July | 0.171008E+10 | 1.05 | 638.47 | 01-JUL-00:10 | 1.05 |
August | 0.171008E+10 | 1.05 | 638.47 | 01-AUG-00:05 | 1.05 |
September | 0.165491E+10 | 1.05 | 638.47 | 01-SEP-00:02 | 1.05 |
October | 0.171008E+10 | 1.05 | 638.47 | 01-OCT-00:20 | 1.05 |
November | 0.165491E+10 | 1.05 | 638.47 | 01-NOV-00:10 | 1.05 |
December | 0.171008E+10 | 1.05 | 638.47 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.201348E+11 | 1.05 | |||
Minimum of Months | 0.154459E+10 | 1.05 | 638.47 | 1.05 | |
Maximum of Months | 0.171008E+10 | 1.05 | 638.47 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163745E+11 | 1.05 | 6113.55 | 01-JAN-00:05 | 1.05 |
February | 0.147899E+11 | 1.05 | 6113.55 | 01-FEB-00:15 | 1.05 |
March | 0.163745E+11 | 1.05 | 6113.55 | 01-MAR-00:10 | 1.05 |
April | 0.158463E+11 | 1.05 | 6113.55 | 01-APR-00:10 | 1.05 |
May | 0.163745E+11 | 1.05 | 6113.55 | 01-MAY-00:05 | 1.05 |
June | 0.158463E+11 | 1.05 | 6113.55 | 01-JUN-00:10 | 1.05 |
July | 0.163745E+11 | 1.05 | 6113.55 | 01-JUL-00:10 | 1.05 |
August | 0.163745E+11 | 1.05 | 6113.55 | 01-AUG-00:10 | 1.05 |
September | 0.158463E+11 | 1.05 | 6113.55 | 01-SEP-00:02 | 1.05 |
October | 0.163745E+11 | 1.05 | 6113.55 | 01-OCT-00:10 | 1.05 |
November | 0.158463E+11 | 1.05 | 6113.55 | 01-NOV-00:10 | 1.05 |
December | 0.163745E+11 | 1.05 | 6113.55 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.192797E+12 | 1.05 | |||
Minimum of Months | 0.147899E+11 | 1.05 | 6113.55 | 1.05 | |
Maximum of Months | 0.163745E+11 | 1.05 | 6113.55 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166690E+10 | 1.05 | 622.35 | 01-JAN-00:05 | 1.05 |
February | 0.150558E+10 | 1.05 | 622.35 | 01-FEB-00:10 | 1.05 |
March | 0.166690E+10 | 1.05 | 622.35 | 01-MAR-00:10 | 1.05 |
April | 0.161313E+10 | 1.05 | 622.35 | 01-APR-00:10 | 1.05 |
May | 0.166690E+10 | 1.05 | 622.35 | 01-MAY-00:05 | 1.05 |
June | 0.161313E+10 | 1.05 | 622.35 | 01-JUN-00:10 | 1.05 |
July | 0.166690E+10 | 1.05 | 622.35 | 01-JUL-00:10 | 1.05 |
August | 0.166690E+10 | 1.05 | 622.35 | 01-AUG-00:05 | 1.05 |
September | 0.161313E+10 | 1.05 | 622.35 | 01-SEP-00:02 | 1.05 |
October | 0.166690E+10 | 1.05 | 622.35 | 01-OCT-00:10 | 1.05 |
November | 0.161313E+10 | 1.05 | 622.35 | 01-NOV-00:10 | 1.05 |
December | 0.166690E+10 | 1.05 | 622.35 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.196264E+11 | 1.05 | |||
Minimum of Months | 0.150558E+10 | 1.05 | 622.35 | 1.05 | |
Maximum of Months | 0.166690E+10 | 1.05 | 622.35 | 1.05 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.382936E+10 | 0.344643E+10 | 6404.75 | 09-JAN-07:02 | 5764.27 | 5764.27 | 46.63 | 12.50 |
February | 0.197898E+10 | 0.178108E+10 | 6309.81 | 06-FEB-05:03 | 5678.83 | 5678.83 | 46.20 | 11.99 |
March | 0.110024E+10 | 0.990215E+09 | 6283.28 | 06-MAR-05:01 | 5654.95 | 5654.95 | 43.34 | 11.87 |
April | 0.251030E+09 | 0.225927E+09 | 4820.70 | 29-APR-05:01 | 4338.63 | 4338.63 | 36.03 | 7.05 |
May | 0.181308E+09 | 0.163178E+09 | 4907.11 | 22-MAY-05:01 | 4416.40 | 4416.40 | 38.66 | 7.25 |
June | 6245492.40 | 5620943.16 | 715.12 | 17-JUN-05:03 | 643.61 | 643.61 | 22.68 | 0.76 |
July | 83592.67 | 75233.40 | 14.72 | 08-JUL-05:05 | 13.25 | 13.25 | 20.93 | 0.02 |
August | 2231147.71 | 2008032.94 | 670.92 | 18-AUG-05:02 | 603.82 | 603.82 | 21.25 | 0.71 |
September | 47950752.15 | 43155676.94 | 3203.67 | 19-SEP-05:03 | 2883.30 | 2883.30 | 28.76 | 4.00 |
October | 0.206870E+09 | 0.186183E+09 | 4863.47 | 10-OCT-04:01 | 4377.13 | 4377.13 | 28.60 | 7.17 |
November | 0.956863E+09 | 0.861177E+09 | 6278.26 | 27-NOV-06:01 | 5650.43 | 5650.43 | 47.82 | 11.82 |
December | 0.242609E+10 | 0.218348E+10 | 6262.11 | 18-DEC-06:02 | 5635.90 | 5635.90 | 46.00 | 11.75 |
Annual Sum or Average | 0.109872E+11 | 0.988852E+10 | ||||||
Minimum of Months | 83592.67 | 75233.40 | 14.72 | 13.25 | 13.25 | 20.93 | 0.02 | |
Maximum of Months | 0.382936E+10 | 0.344643E+10 | 6404.75 | 5764.27 | 5764.27 | 47.82 | 12.50 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 209.41 | 188.47 | 2.58 | 24-JAN-05:01 | 2.33 | 2.33 | 6.71 | 0.55 |
February | 2017178.01 | 1815460.21 | 195.34 | 27-FEB-13:40 | 175.81 | 175.81 | 8.98 | 11.74 |
March | 25313.42 | 22782.08 | 5.53 | 14-MAR-13:30 | 4.98 | 4.98 | 8.64 | 1.06 |
April | 19798686.55 | 17818817.89 | 384.19 | 06-APR-16:00 | 345.77 | 345.77 | 7.99 | 16.70 |
May | 98274110.25 | 88446699.23 | 2848.37 | 19-MAY-12:10 | 2563.53 | 2563.53 | 7.13 | 42.59 |
June | 0.489459E+09 | 0.440513E+09 | 3679.79 | 30-JUN-16:00 | 3311.81 | 3311.81 | 6.72 | 47.56 |
July | 0.106374E+10 | 0.957366E+09 | 5019.76 | 31-JUL-15:20 | 4517.78 | 4517.78 | 6.72 | 54.25 |
August | 0.939353E+09 | 0.845418E+09 | 5156.33 | 07-AUG-13:00 | 4640.70 | 4640.70 | 6.72 | 54.86 |
September | 0.342613E+09 | 0.308352E+09 | 6052.29 | 05-SEP-12:30 | 5447.06 | 5447.06 | 7.52 | 58.66 |
October | 43627842.93 | 39265058.64 | 725.29 | 18-OCT-14:30 | 652.76 | 652.76 | 7.44 | 22.83 |
November | 1168879.76 | 1051991.78 | 54.75 | 03-NOV-14:00 | 49.27 | 49.27 | 8.71 | 5.63 |
December | 20.86 | 18.78 | 0.01 | 27-DEC-17:00 | 0.01 | 0.01 | 8.48 | 0.00 |
Annual Sum or Average | 0.300008E+10 | 0.270007E+10 | ||||||
Minimum of Months | 20.86 | 18.78 | 0.01 | 0.01 | 0.01 | 6.71 | 0.00 | |
Maximum of Months | 0.106374E+10 | 0.957366E+09 | 6052.29 | 5447.06 | 5447.06 | 8.98 | 58.66 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.739139E+09 | 0.665225E+09 | 13408.88 | 01-JAN-13:32 | 12068.00 | 12068.00 | 8.43 | 93.98 |
February | 0.247169E+10 | 0.222452E+10 | 13408.88 | 01-FEB-03:55 | 12068.00 | 12068.00 | 8.43 | 93.98 |
March | 0.376656E+10 | 0.338990E+10 | 13408.88 | 01-MAR-05:01 | 12068.00 | 12068.00 | 8.43 | 93.98 |
April | 0.696954E+10 | 0.627259E+10 | 13408.88 | 01-APR-12:15 | 12068.00 | 12068.00 | 8.43 | 93.98 |
May | 0.104325E+11 | 0.938926E+10 | 13408.88 | 01-MAY-12:10 | 12068.00 | 12068.00 | 8.43 | 93.98 |
June | 0.178197E+11 | 0.160377E+11 | 13408.88 | 01-JUN-03:02 | 12068.00 | 12068.00 | 8.74 | 93.98 |
July | 0.242069E+11 | 0.217862E+11 | 13408.88 | 01-JUL-00:22 | 12068.00 | 12068.00 | 7.91 | 93.98 |
August | 0.236964E+11 | 0.213267E+11 | 13408.88 | 01-AUG-00:12 | 12068.00 | 12068.00 | 7.98 | 93.98 |
September | 0.145354E+11 | 0.130818E+11 | 13408.88 | 01-SEP-00:02 | 12068.00 | 12068.00 | 8.06 | 93.98 |
October | 0.764440E+10 | 0.687996E+10 | 13408.88 | 02-OCT-05:05 | 12068.00 | 12068.00 | 8.72 | 93.98 |
November | 0.347750E+10 | 0.312975E+10 | 13408.88 | 01-NOV-04:01 | 12068.00 | 12068.00 | 8.64 | 93.98 |
December | 0.193407E+10 | 0.174066E+10 | 13408.88 | 01-DEC-05:43 | 12068.00 | 12068.00 | 8.43 | 93.98 |
Annual Sum or Average | 0.117694E+12 | 0.105924E+12 | ||||||
Minimum of Months | 0.739139E+09 | 0.665225E+09 | 13408.88 | 12068.00 | 12068.00 | 7.91 | 93.98 | |
Maximum of Months | 0.242069E+11 | 0.217862E+11 | 13408.88 | 12068.00 | 12068.00 | 8.74 | 93.98 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.981732E+10 | 0.883559E+10 | 3665.37 | 01-JAN-00:05 | 3298.83 | 3298.83 | 21.85 | 15.31 |
February | 0.886726E+10 | 0.798053E+10 | 3665.37 | 01-FEB-00:10 | 3298.83 | 3298.83 | 24.23 | 15.31 |
March | 0.981732E+10 | 0.883559E+10 | 3665.37 | 01-MAR-00:10 | 3298.83 | 3298.83 | 27.41 | 15.31 |
April | 0.950063E+10 | 0.855057E+10 | 3665.37 | 01-APR-00:10 | 3298.83 | 3298.83 | 30.39 | 15.31 |
May | 0.981732E+10 | 0.883559E+10 | 3665.37 | 01-MAY-00:05 | 3298.83 | 3298.83 | 22.35 | 15.31 |
June | 0.950063E+10 | 0.855057E+10 | 3665.37 | 01-JUN-00:10 | 3298.83 | 3298.83 | 26.00 | 15.31 |
July | 0.981732E+10 | 0.883559E+10 | 3665.37 | 01-JUL-00:10 | 3298.83 | 3298.83 | 34.65 | 15.31 |
August | 0.981732E+10 | 0.883559E+10 | 3665.37 | 01-AUG-00:05 | 3298.83 | 3298.83 | 38.59 | 15.31 |
September | 0.950063E+10 | 0.855057E+10 | 3665.37 | 01-SEP-00:02 | 3298.83 | 3298.83 | 25.52 | 15.31 |
October | 0.981732E+10 | 0.883559E+10 | 3665.37 | 01-OCT-00:10 | 3298.83 | 3298.83 | 24.97 | 15.31 |
November | 0.950063E+10 | 0.855057E+10 | 3665.37 | 01-NOV-00:10 | 3298.83 | 3298.83 | 27.65 | 15.31 |
December | 0.981732E+10 | 0.883559E+10 | 3665.37 | 01-DEC-00:10 | 3298.83 | 3298.83 | 30.04 | 15.31 |
Annual Sum or Average | 0.115591E+12 | 0.104032E+12 | ||||||
Minimum of Months | 0.886726E+10 | 0.798053E+10 | 3665.37 | 3298.83 | 3298.83 | 21.85 | 15.31 | |
Maximum of Months | 0.981732E+10 | 0.883559E+10 | 3665.37 | 3298.83 | 3298.83 | 38.59 | 15.31 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:03 | 1.79 | 1.79 | 55.15 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:03 | 1.79 | 1.79 | 56.00 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:02 | 1.79 | 1.79 | 56.09 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:01 | 1.79 | 1.79 | 56.22 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:02 | 1.79 | 1.79 | 55.87 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 56.57 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 56.58 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 56.27 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.24 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.19 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 55.37 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:01 | 1.79 | 1.79 | 56.05 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.15 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 56.58 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.914075E+09 | 0.822667E+09 | 16585.00 | 17-JAN-07:00 | 14926.50 | 14926.50 | 21.21 | 55.25 |
February | 0.305701E+10 | 0.275131E+10 | 16607.41 | 27-FEB-15:30 | 14946.67 | 14946.67 | 23.09 | 55.25 |
March | 0.465799E+10 | 0.419220E+10 | 16586.41 | 14-MAR-13:20 | 14927.77 | 14927.77 | 21.33 | 55.25 |
April | 0.872245E+10 | 0.785020E+10 | 33208.99 | 07-APR-14:40 | 29888.09 | 29888.09 | 22.83 | 110.49 |
May | 0.135037E+11 | 0.121533E+11 | 33289.14 | 19-MAY-15:30 | 29960.23 | 29960.23 | 26.02 | 110.49 |
June | 0.264279E+11 | 0.237851E+11 | 33306.59 | 20-JUN-15:40 | 29975.93 | 29975.93 | 26.64 | 110.49 |
July | 0.385343E+11 | 0.346808E+11 | 33309.41 | 19-JUL-12:20 | 29978.47 | 29978.47 | 26.75 | 110.49 |
August | 0.364960E+11 | 0.328464E+11 | 33290.87 | 05-AUG-14:20 | 29961.79 | 29961.79 | 26.08 | 110.49 |
September | 0.205499E+11 | 0.184949E+11 | 33367.13 | 07-SEP-14:40 | 30030.41 | 30030.41 | 29.39 | 110.49 |
October | 0.999592E+10 | 0.899632E+10 | 33268.99 | 18-OCT-14:50 | 29942.09 | 29942.09 | 25.30 | 110.49 |
November | 0.430083E+10 | 0.387075E+10 | 16595.68 | 17-NOV-17:00 | 14936.11 | 14936.11 | 22.10 | 55.25 |
December | 0.239182E+10 | 0.215263E+10 | 16584.99 | 08-DEC-14:10 | 14926.49 | 14926.49 | 21.21 | 55.25 |
Annual Sum or Average | 0.169552E+12 | 0.152597E+12 | ||||||
Minimum of Months | 0.914075E+09 | 0.822667E+09 | 16584.99 | 14926.49 | 14926.49 | 21.21 | 55.25 | |
Maximum of Months | 0.385343E+11 | 0.346808E+11 | 33367.13 | 30030.41 | 30030.41 | 29.39 | 110.49 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 35.01 | 35.01 | 339023.58 | 1926652.15 | 09-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 30.91 | 30.91 | 194719.19 | 1989661.92 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24.06 | 24.06 | 98721.51 | 1928193.29 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.44 | 25.44 | 23822.29 | 1360847.79 | 29-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.12 | 22.12 | 16234.50 | 1555198.13 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 21.57 | 21.57 | 607.54 | 183589.52 | 17-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.00 | 21.00 | 7.81 | 3713.59 | 08-JUL-05:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.84 | 20.84 | 209.91 | 173688.76 | 18-AUG-05:02 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 20.82 | 20.82 | 4609.77 | 867742.81 | 19-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20.00 | 20.00 | 19000.69 | 1598765.11 | 10-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.28 | 25.28 | 88671.10 | 1698994.42 | 27-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 28.78 | 28.78 | 216068.91 | 2009651.10 | 26-DEC-05:11 |
Annual Sum or Average | 0.00 | 83152.69 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.00 | 20.00 | 7.81 | 3713.59 | ||
Maximum of Months | 0.00 | 0.00 | 35.01 | 35.01 | 339023.58 | 2009651.10 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 492.76 | 23956.38 | 18-JAN-04:30 | 8.43 | 8.40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 6290.69 | 767570.65 | 27-FEB-15:30 | 9.82 | 8.84 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 2634.02 | 92255.96 | 14-MAR-13:30 | 8.60 | 8.49 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46677.36 | 1218246.89 | 06-APR-15:10 | 10.61 | 8.94 | 0.00 | 0.00 | 01-APR-00:10 |
May | 129871.09 | 1352656.72 | 19-MAY-15:30 | 10.13 | 6.70 | 6.53 | 61494.16 | 14-MAY-10:22 |
June | 350670.30 | 1544209.36 | 29-JUN-15:00 | 10.62 | 6.70 | 16.05 | 69554.18 | 12-JUN-03:02 |
July | 538512.08 | 1804877.51 | 17-JUL-15:30 | 11.28 | 6.70 | 63.19 | 163386.19 | 15-JUL-02:52 |
August | 467117.07 | 1708601.32 | 07-AUG-15:40 | 11.04 | 6.70 | 54.45 | 126076.41 | 20-AUG-20:23 |
September | 259380.66 | 2396542.22 | 07-SEP-15:00 | 13.14 | 7.44 | 36.76 | 132020.91 | 24-SEP-08:53 |
October | 71738.30 | 1216199.05 | 16-OCT-13:30 | 10.63 | 8.96 | 0.24 | 5264.00 | 22-OCT-17:02 |
November | 6254.82 | 353838.65 | 17-NOV-17:00 | 9.03 | 8.57 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1290.11 | 24000.82 | 27-DEC-17:00 | 8.43 | 8.40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 157882.06 | 14.91 | ||||||
Minimum of Months | 492.76 | 23956.38 | 8.43 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 538512.08 | 2396542.22 | 13.14 | 8.96 | 63.19 | 163386.19 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 34.41 | 24-JAN-05:01 | 6.71 | 8.40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2825.94 | 481998.94 | 27-FEB-13:40 | 16.51 | 8.99 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 75.00 | 42390.25 | 14-MAR-13:30 | 16.23 | 8.49 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27727.77 | 944406.12 | 06-APR-16:00 | 20.22 | 8.52 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84618.46 | 1342256.31 | 19-MAY-15:30 | 15.23 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 281411.46 | 1534118.04 | 29-JUN-14:50 | 22.35 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 447169.61 | 1795623.09 | 17-JUL-15:30 | 15.29 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 390756.16 | 1700251.12 | 07-AUG-15:40 | 14.42 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 188723.01 | 2397394.92 | 07-SEP-15:00 | 18.80 | 7.57 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 47084.92 | 1218975.67 | 18-OCT-14:30 | 19.47 | 6.96 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2414.33 | 203637.87 | 17-NOV-17:00 | 16.97 | 8.58 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.06 | 58.19 | 27-DEC-17:00 | 14.51 | 8.40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 123693.85 | 0.00 | ||||||
Minimum of Months | 0.00 | 34.41 | 6.71 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 447169.61 | 2397394.92 | 22.35 | 8.99 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 179034.94 | 203429.85 | 13-JAN-16:30 | 22.15 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 339907.49 | 611324.26 | 27-FEB-16:00 | 29.74 | 22.74 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 496610.59 | 646331.74 | 31-MAR-24:00 | 30.38 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 704405.74 | 1331712.83 | 07-APR-14:00 | 42.87 | 30.32 | 0.00 | 0.00 | 01-APR-00:10 |
May | 257424.13 | 977536.06 | 20-MAY-16:00 | 36.46 | 32.30 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 577175.23 | 1382428.54 | 29-JUN-15:00 | 43.78 | 36.36 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 973324.80 | 1963229.89 | 17-JUL-16:00 | 54.13 | 43.34 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1128273.56 | 2079262.87 | 06-AUG-16:00 | 56.18 | 43.08 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 340455.72 | 1248242.38 | 02-SEP-17:00 | 41.37 | 36.90 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 387534.22 | 964208.46 | 18-OCT-15:00 | 36.21 | 29.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 506922.86 | 752941.62 | 17-NOV-17:00 | 32.35 | 22.58 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 640762.49 | 770295.67 | 10-DEC-02:00 | 32.66 | 20.56 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 546131.79 | 0.00 | ||||||
Minimum of Months | 179034.94 | 203429.85 | 22.15 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1128273.56 | 2079262.87 | 56.18 | 43.34 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.14 | 56.14 | 17330.34 | 58856.19 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.72 | 56.72 | 17710.01 | 59175.84 | 23-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.70 | 56.70 | 18546.15 | 59076.98 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.62 | 56.62 | 16883.10 | 57464.84 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 56.72 | 56.72 | 16524.78 | 54983.52 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.12 | 57.12 | 15933.46 | 51687.31 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.22 | 57.22 | 14098.76 | 48649.95 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 56.79 | 56.79 | 14985.47 | 46963.74 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 57.13 | 57.13 | 14315.64 | 48068.79 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.20 | 57.20 | 14900.62 | 50877.81 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.01 | 56.01 | 15950.63 | 54068.05 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.48 | 56.48 | 16274.20 | 56868.56 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 16111.88 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.01 | 56.01 | 14098.76 | 46963.74 | ||
Maximum of Months | 0.00 | 0.00 | 57.22 | 57.22 | 18546.15 | 59175.84 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 18.01 | 25051.42 | 17-JAN-07:00 | 21.21 | 20.26 | 528.57 | 116000.37 | 19-JAN-06:30 |
February | 2575.33 | 458702.71 | 27-FEB-15:30 | 23.09 | 21.10 | 1778.14 | 138377.22 | 16-FEB-14:40 |
March | 150.96 | 52307.38 | 14-MAR-13:20 | 21.33 | 20.64 | 2823.17 | 137969.83 | 30-MAR-12:30 |
April | 27118.59 | 883898.27 | 06-APR-16:00 | 24.93 | 21.10 | 3109.58 | 138706.99 | 28-APR-15:20 |
May | 90919.87 | 2271897.48 | 19-MAY-15:30 | 26.02 | 21.10 | 2253.60 | 137986.30 | 03-MAY-13:40 |
June | 329930.68 | 2560561.27 | 20-JUN-15:40 | 26.64 | 22.96 | 889.27 | 87488.84 | 14-JUN-17:20 |
July | 543119.95 | 2607154.70 | 19-JUL-12:20 | 26.75 | 22.93 | 550.89 | 61079.90 | 05-JUL-12:10 |
August | 469393.00 | 2300545.91 | 05-AUG-14:20 | 26.08 | 21.92 | 1415.82 | 75695.57 | 12-AUG-02:55 |
September | 221813.06 | 4512479.33 | 07-SEP-15:00 | 30.87 | 25.36 | 1787.05 | 111934.85 | 18-SEP-11:40 |
October | 47414.29 | 1938263.51 | 18-OCT-14:50 | 25.30 | 21.10 | 2553.75 | 121425.93 | 03-OCT-09:00 |
November | 2070.83 | 231704.75 | 17-NOV-17:00 | 22.10 | 21.10 | 2314.02 | 141333.30 | 26-NOV-22:02 |
December | 77.57 | 24700.86 | 08-DEC-14:10 | 21.21 | 20.27 | 1431.62 | 137204.81 | 14-DEC-13:50 |
Annual Sum or Average | 145709.61 | 1783.74 | ||||||
Minimum of Months | 18.01 | 24700.86 | 21.21 | 20.26 | 528.57 | 61079.90 | ||
Maximum of Months | 543119.95 | 4512479.33 | 30.87 | 25.36 | 3109.58 | 141333.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.440019E+11 | 0.00 | 0.00 | 0.467664E+10 | 0.00 | 0.00 |
February | 0.188558E+11 | 0.00 | 0.631469E+09 | 0.518639E+10 | 0.00 | 0.00 |
March | 0.692379E+10 | 0.00 | 34245100.02 | 0.768867E+10 | 0.00 | 0.00 |
April | 0.491197E+09 | 0.00 | 0.661475E+10 | 0.933259E+10 | 0.00 | 0.00 |
May | 0.525464E+09 | 0.00 | 0.181362E+11 | 0.852548E+10 | 0.00 | 0.00 |
June | 60391.77 | 0.00 | 0.599180E+11 | 0.129105E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.102793E+12 | 0.158946E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.950781E+11 | 0.174352E+11 | 0.00 | 0.00 |
September | 41874926.76 | 0.00 | 0.388729E+11 | 0.955195E+10 | 0.00 | 0.00 |
October | 0.365514E+09 | 0.00 | 0.105474E+11 | 0.853678E+10 | 0.00 | 0.00 |
November | 0.408227E+10 | 0.00 | 0.560038E+09 | 0.722493E+10 | 0.00 | 0.00 |
December | 0.181890E+11 | 0.00 | 0.00 | 0.623312E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.934769E+11 | 0.00 | 0.333186E+12 | 0.113197E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.467664E+10 | 0.00 | 0.00 |
Maximum of Months | 0.440019E+11 | 0.00 | 0.102793E+12 | 0.174352E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.750779E+12 | 0.00 | 22025.30 | 0.445872E+11 | 0.00 | 0.00 |
February | 0.392684E+12 | 0.00 | 0.449454E+10 | 0.401120E+11 | 0.00 | 0.00 |
March | 0.216701E+12 | 0.00 | 95868854.75 | 0.506749E+11 | 0.00 | 0.00 |
April | 0.474773E+11 | 0.00 | 0.465868E+11 | 0.537990E+11 | 0.00 | 0.00 |
May | 0.330866E+11 | 0.00 | 0.153363E+12 | 0.636069E+11 | 0.00 | 0.00 |
June | 0.883779E+09 | 0.00 | 0.507393E+12 | 0.989918E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.851486E+12 | 0.118348E+12 | 0.00 | 0.00 |
August | 0.292297E+09 | 0.00 | 0.737744E+12 | 0.115825E+12 | 0.00 | 0.00 |
September | 0.822296E+10 | 0.00 | 0.339029E+12 | 0.743134E+11 | 0.00 | 0.00 |
October | 0.383895E+11 | 0.00 | 0.830409E+11 | 0.557654E+11 | 0.00 | 0.00 |
November | 0.188051E+12 | 0.00 | 0.402796E+10 | 0.450663E+11 | 0.00 | 0.00 |
December | 0.480785E+12 | 0.00 | 85216.38 | 0.437815E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.215735E+13 | 0.00 | 0.272726E+13 | 0.804871E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 22025.30 | 0.401120E+11 | 0.00 | 0.00 |
Maximum of Months | 0.750779E+12 | 0.00 | 0.851486E+12 | 0.118348E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.120967E+12 | 0.00 | 59233.01 | 0.573410E+10 | 0.00 | 0.00 |
February | 0.637594E+11 | 0.00 | 0.319283E+09 | 0.450550E+10 | 0.00 | 0.00 |
March | 0.431134E+11 | 0.00 | 2115474.09 | 0.481016E+10 | 0.00 | 0.00 |
April | 0.143464E+11 | 0.00 | 0.433904E+10 | 0.453039E+10 | 0.00 | 0.00 |
May | 0.102580E+11 | 0.00 | 0.159500E+11 | 0.568372E+10 | 0.00 | 0.00 |
June | 0.710561E+09 | 0.00 | 0.557763E+11 | 0.932005E+10 | 0.00 | 0.00 |
July | 22421191.93 | 0.00 | 0.941281E+11 | 0.116491E+11 | 0.00 | 0.00 |
August | 0.276369E+09 | 0.00 | 0.794769E+11 | 0.108198E+11 | 0.00 | 0.00 |
September | 0.379148E+10 | 0.00 | 0.347387E+11 | 0.637016E+10 | 0.00 | 0.00 |
October | 0.125250E+11 | 0.00 | 0.713518E+10 | 0.444869E+10 | 0.00 | 0.00 |
November | 0.396973E+11 | 0.00 | 0.301718E+09 | 0.444823E+10 | 0.00 | 0.00 |
December | 0.848166E+11 | 0.00 | 1767.86 | 0.527489E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.394284E+12 | 0.00 | 0.292167E+12 | 0.775948E+11 | 0.00 | 0.00 |
Minimum of Months | 22421191.93 | 0.00 | 1767.86 | 0.444823E+10 | 0.00 | 0.00 |
Maximum of Months | 0.120967E+12 | 0.00 | 0.941281E+11 | 0.116491E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.388718E+09 | 0.00 | 483334.78 | 0.162493E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.261761E+09 | 0.144709E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 10369.74 | 0.174156E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.231208E+10 | 0.161896E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.883342E+10 | 0.172389E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.311339E+11 | 0.172626E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.530670E+11 | 0.172372E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.493011E+11 | 0.188642E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.203694E+11 | 0.176503E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.573405E+10 | 0.173438E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 68497280.37 | 0.165060E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 60297.63 | 0.160803E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.388718E+09 | 0.00 | 0.171082E+12 | 0.202509E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 10369.74 | 0.144709E+11 | 0.00 | 0.00 |
Maximum of Months | 0.388718E+09 | 0.00 | 0.530670E+11 | 0.188642E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.453786E+12 | 0.241034E+12 | 0.00 | 15.27 |
February | 0.00 | 0.00 | 0.714253E+12 | 0.297567E+12 | 0.00 | 22.84 |
March | 0.00 | 0.00 | 0.112057E+13 | 0.410583E+12 | 0.00 | 34.43 |
April | 0.00 | 0.00 | 0.140686E+13 | 0.477581E+12 | 0.00 | 41.40 |
May | 0.00 | 0.00 | 0.473988E+12 | 0.243331E+12 | 0.00 | 13.77 |
June | 0.00 | 0.00 | 0.789921E+12 | 0.323513E+12 | 0.00 | 18.35 |
July | 0.00 | 0.00 | 0.116273E+13 | 0.430705E+12 | 0.00 | 20.37 |
August | 0.00 | 0.00 | 0.148831E+13 | 0.521240E+12 | 0.00 | 32.00 |
September | 0.00 | 0.00 | 0.467612E+12 | 0.236817E+12 | 0.00 | 11.73 |
October | 0.00 | 0.00 | 0.807962E+12 | 0.331223E+12 | 0.00 | 23.94 |
November | 0.00 | 0.00 | 0.109525E+13 | 0.401819E+12 | 0.00 | 34.13 |
December | 0.00 | 0.00 | 0.144567E+13 | 0.490845E+12 | 0.00 | 44.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.114269E+14 | 0.440626E+13 | 0.00 | 312.78 |
Minimum of Months | 0.00 | 0.00 | 0.453786E+12 | 0.236817E+12 | 0.00 | 11.73 |
Maximum of Months | 0.00 | 0.00 | 0.148831E+13 | 0.521240E+12 | 0.00 | 44.55 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.377167E+10 | 0.255231E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.103821E+11 | 0.370816E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.186220E+11 | 0.540850E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.248643E+11 | 0.648790E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.715745E+10 | 0.324562E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.139573E+11 | 0.470094E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.216282E+11 | 0.675179E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.279449E+11 | 0.806685E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.733016E+10 | 0.327277E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.132129E+11 | 0.438985E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.182110E+11 | 0.524603E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.242133E+11 | 0.643666E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.191295E+12 | 0.602674E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.377167E+10 | 0.255231E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.279449E+11 | 0.806685E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.112556E+11 | 0.190537E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.750458E+11 | 0.307120E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.155586E+12 | 0.476348E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.223398E+12 | 0.596027E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.579438E+11 | 0.289529E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.128581E+12 | 0.440384E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.204389E+12 | 0.641106E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.262791E+12 | 0.763267E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.619105E+11 | 0.296707E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.110362E+12 | 0.390086E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.150941E+12 | 0.459949E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.198204E+12 | 0.556875E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.164041E+13 | 0.540793E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.112556E+11 | 0.190537E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.262791E+12 | 0.763267E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.321811E+09 | 0.174551E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.544551E+10 | 0.267948E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.135316E+11 | 0.441505E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.209056E+11 | 0.574544E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.491702E+10 | 0.274466E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.125956E+11 | 0.439017E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203881E+11 | 0.644638E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.261312E+11 | 0.765298E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.548788E+10 | 0.285766E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.929364E+10 | 0.359924E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.127624E+11 | 0.419714E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.173330E+11 | 0.514944E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.149113E+12 | 0.516232E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.321811E+09 | 0.174551E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.261312E+11 | 0.765298E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.467664E+10 | 0.00 | 0.440019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.518639E+10 | 0.631469E+09 | 0.188558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.768867E+10 | 34245100.02 | 0.692379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.933259E+10 | 0.661475E+10 | 0.491197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.852548E+10 | 0.181362E+11 | 0.525464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129105E+11 | 0.599180E+11 | 60391.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158946E+11 | 0.102793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174352E+11 | 0.950781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.955195E+10 | 0.388729E+11 | 41874926.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.853678E+10 | 0.105474E+11 | 0.365514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.722493E+10 | 0.560038E+09 | 0.408227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.623312E+10 | 0.00 | 0.181890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113197E+12 | 0.333186E+12 | 0.934769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.467664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174352E+11 | 0.102793E+12 | 0.440019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.445872E+11 | 22025.30 | 0.750779E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.401120E+11 | 0.449454E+10 | 0.392684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.506749E+11 | 95868854.75 | 0.216701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.537990E+11 | 0.465868E+11 | 0.474773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.636069E+11 | 0.153363E+12 | 0.330866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.989918E+11 | 0.507393E+12 | 0.883779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118348E+12 | 0.851486E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115825E+12 | 0.737744E+12 | 0.292297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.743134E+11 | 0.339029E+12 | 0.822296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.557654E+11 | 0.830409E+11 | 0.383895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.450663E+11 | 0.402796E+10 | 0.188051E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.437815E+11 | 85216.38 | 0.480785E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.804871E+12 | 0.272726E+13 | 0.215735E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.401120E+11 | 22025.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118348E+12 | 0.851486E+12 | 0.750779E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.573410E+10 | 59233.01 | 0.120967E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.450550E+10 | 0.319283E+09 | 0.637594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.481016E+10 | 2115474.09 | 0.431134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453039E+10 | 0.433904E+10 | 0.143464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.568372E+10 | 0.159500E+11 | 0.102580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.932005E+10 | 0.557763E+11 | 0.710561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116491E+11 | 0.941281E+11 | 22421191.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108198E+11 | 0.794769E+11 | 0.276369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.637016E+10 | 0.347387E+11 | 0.379148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.444869E+10 | 0.713518E+10 | 0.125250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.444823E+10 | 0.301718E+09 | 0.396973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.527489E+10 | 1767.86 | 0.848166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.775948E+11 | 0.292167E+12 | 0.394284E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.444823E+10 | 1767.86 | 22421191.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116491E+11 | 0.941281E+11 | 0.120967E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162493E+11 | 483334.78 | 0.388718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144709E+11 | 0.261761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174156E+11 | 10369.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161896E+11 | 0.231208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172389E+11 | 0.883342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172626E+11 | 0.311339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.172372E+11 | 0.530670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.188642E+11 | 0.493011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176503E+11 | 0.203694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173438E+11 | 0.573405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165060E+11 | 68497280.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160803E+11 | 60297.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202509E+12 | 0.171082E+12 | 0.388718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144709E+11 | 10369.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188642E+11 | 0.530670E+11 | 0.388718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108099E+12 | 0.361894E+12 | 0.00 | 0.00 | 0.00 | 0.408587E+11 | 0.00 | 0.00 |
February | 0.976375E+11 | 0.575724E+12 | 0.00 | 0.00 | 0.00 | 0.611255E+11 | 0.00 | 0.00 |
March | 0.108099E+12 | 0.910631E+12 | 0.00 | 0.00 | 0.00 | 0.921321E+11 | 0.00 | 0.00 |
April | 0.104612E+12 | 0.114518E+13 | 0.00 | 0.00 | 0.00 | 0.110798E+12 | 0.00 | 0.00 |
May | 0.108099E+12 | 0.375766E+12 | 0.00 | 0.00 | 0.00 | 0.368446E+11 | 0.00 | 0.00 |
June | 0.104612E+12 | 0.620352E+12 | 0.00 | 0.00 | 0.00 | 0.491114E+11 | 0.00 | 0.00 |
July | 0.108099E+12 | 0.894884E+12 | 0.00 | 0.00 | 0.00 | 0.545182E+11 | 0.00 | 0.00 |
August | 0.108099E+12 | 0.116120E+13 | 0.00 | 0.00 | 0.00 | 0.856461E+11 | 0.00 | 0.00 |
September | 0.104612E+12 | 0.366935E+12 | 0.00 | 0.00 | 0.00 | 0.313866E+11 | 0.00 | 0.00 |
October | 0.108099E+12 | 0.649195E+12 | 0.00 | 0.00 | 0.00 | 0.640698E+11 | 0.00 | 0.00 |
November | 0.104612E+12 | 0.889805E+12 | 0.00 | 0.00 | 0.00 | 0.913490E+11 | 0.00 | 0.00 |
December | 0.108099E+12 | 0.118267E+13 | 0.00 | 0.00 | 0.00 | 0.119210E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.127277E+13 | 0.913423E+13 | 0.00 | 0.00 | 0.00 | 0.837050E+12 | 0.00 | 0.00 |
Minimum of Months | 0.976375E+11 | 0.361894E+12 | 0.00 | 0.00 | 0.00 | 0.313866E+11 | 0.00 | 0.00 |
Maximum of Months | 0.108099E+12 | 0.118267E+13 | 0.00 | 0.00 | 0.00 | 0.119210E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.171008E+10 | 0.292943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154459E+10 | 0.821852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171008E+10 | 0.149235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165491E+10 | 0.200314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171008E+10 | 0.562191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165491E+10 | 0.109113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171008E+10 | 0.165864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171008E+10 | 0.215881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165491E+10 | 0.571231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171008E+10 | 0.105331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165491E+10 | 0.146199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171008E+10 | 0.194867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201348E+11 | 0.151163E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154459E+10 | 0.292943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171008E+10 | 0.215881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.163745E+11 | 0.857650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147899E+11 | 0.591237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163745E+11 | 0.124326E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158463E+11 | 0.179642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163745E+11 | 0.453654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158463E+11 | 0.100389E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163745E+11 | 0.156653E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163745E+11 | 0.202839E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158463E+11 | 0.480861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163745E+11 | 0.877275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158463E+11 | 0.120793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163745E+11 | 0.158891E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192797E+12 | 0.129241E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147899E+11 | 0.857650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163745E+11 | 0.202839E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166690E+10 | 0.243203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150558E+10 | 0.427161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166690E+10 | 0.107834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161313E+10 | 0.167733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166690E+10 | 0.383926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161313E+10 | 0.981859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166690E+10 | 0.156086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166690E+10 | 0.201452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161313E+10 | 0.424334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166690E+10 | 0.736129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161313E+10 | 0.101784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166690E+10 | 0.138504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196264E+11 | 0.117117E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150558E+10 | 0.243203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166690E+10 | 0.201452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.467664E+10 | 0.440019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.518639E+10 | 0.188558E+11 | 0.631469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.768867E+10 | 0.692379E+10 | 34245100.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.933259E+10 | 0.491197E+09 | 0.661475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.852548E+10 | 0.525464E+09 | 0.181362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129105E+11 | 60391.77 | 0.599180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158946E+11 | 0.00 | 0.102793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174352E+11 | 0.00 | 0.950781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.955195E+10 | 41874926.76 | 0.388729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.853678E+10 | 0.365514E+09 | 0.105474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.722493E+10 | 0.408227E+10 | 0.560038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.623312E+10 | 0.181890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113197E+12 | 0.934769E+11 | 0.333186E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.467664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174352E+11 | 0.440019E+11 | 0.102793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.445872E+11 | 0.750779E+12 | 22025.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.401120E+11 | 0.392684E+12 | 0.449454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.506749E+11 | 0.216701E+12 | 95868854.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.537990E+11 | 0.474773E+11 | 0.465868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.636069E+11 | 0.330866E+11 | 0.153363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.989918E+11 | 0.883779E+09 | 0.507393E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118348E+12 | 0.00 | 0.851486E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115825E+12 | 0.292297E+09 | 0.737744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.743134E+11 | 0.822296E+10 | 0.339029E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.557654E+11 | 0.383895E+11 | 0.830409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.450663E+11 | 0.188051E+12 | 0.402796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.437815E+11 | 0.480785E+12 | 85216.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.804871E+12 | 0.215735E+13 | 0.272726E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.401120E+11 | 0.00 | 22025.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118348E+12 | 0.750779E+12 | 0.851486E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.573410E+10 | 0.120967E+12 | 59233.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.450550E+10 | 0.637594E+11 | 0.319283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.481016E+10 | 0.431134E+11 | 2115474.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453039E+10 | 0.143464E+11 | 0.433904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.568372E+10 | 0.102580E+11 | 0.159500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.932005E+10 | 0.710561E+09 | 0.557763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116491E+11 | 22421191.93 | 0.941281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108198E+11 | 0.276369E+09 | 0.794769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.637016E+10 | 0.379148E+10 | 0.347387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.444869E+10 | 0.125250E+11 | 0.713518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.444823E+10 | 0.396973E+11 | 0.301718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.527489E+10 | 0.848166E+11 | 1767.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.775948E+11 | 0.394284E+12 | 0.292167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.444823E+10 | 22421191.93 | 1767.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116491E+11 | 0.120967E+12 | 0.941281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.162493E+11 | 0.388718E+09 | 483334.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144709E+11 | 0.00 | 0.261761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174156E+11 | 0.00 | 10369.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161896E+11 | 0.00 | 0.231208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172389E+11 | 0.00 | 0.883342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172626E+11 | 0.00 | 0.311339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.172372E+11 | 0.00 | 0.530670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.188642E+11 | 0.00 | 0.493011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176503E+11 | 0.00 | 0.203694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173438E+11 | 0.00 | 0.573405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165060E+11 | 0.00 | 68497280.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160803E+11 | 0.00 | 60297.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202509E+12 | 0.388718E+09 | 0.171082E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144709E+11 | 0.00 | 10369.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188642E+11 | 0.388718E+09 | 0.530670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108099E+12 | 0.00 | 0.453786E+12 | 0.00 | 0.918927E+11 | 0.00 | 0.00 | 0.00 | 0.410426E+11 | 0.00 | 0.00 | 0.00 |
February | 0.976375E+11 | 0.00 | 0.714253E+12 | 0.00 | 0.138529E+12 | 0.00 | 0.00 | 0.00 | 0.614006E+11 | 0.00 | 0.00 | 0.00 |
March | 0.108099E+12 | 0.00 | 0.112057E+13 | 0.00 | 0.209937E+12 | 0.00 | 0.00 | 0.00 | 0.925469E+11 | 0.00 | 0.00 | 0.00 |
April | 0.104612E+12 | 0.00 | 0.140686E+13 | 0.00 | 0.261672E+12 | 0.00 | 0.00 | 0.00 | 0.111297E+12 | 0.00 | 0.00 | 0.00 |
May | 0.108099E+12 | 0.00 | 0.473988E+12 | 0.00 | 0.982215E+11 | 0.00 | 0.00 | 0.00 | 0.370105E+11 | 0.00 | 0.00 | 0.00 |
June | 0.104612E+12 | 0.00 | 0.789921E+12 | 0.00 | 0.169569E+12 | 0.00 | 0.00 | 0.00 | 0.493325E+11 | 0.00 | 0.00 | 0.00 |
July | 0.108099E+12 | 0.00 | 0.116273E+13 | 0.00 | 0.267843E+12 | 0.00 | 0.00 | 0.00 | 0.547636E+11 | 0.00 | 0.00 | 0.00 |
August | 0.108099E+12 | 0.00 | 0.148831E+13 | 0.00 | 0.327110E+12 | 0.00 | 0.00 | 0.00 | 0.860316E+11 | 0.00 | 0.00 | 0.00 |
September | 0.104612E+12 | 0.00 | 0.467612E+12 | 0.00 | 0.100677E+12 | 0.00 | 0.00 | 0.00 | 0.315279E+11 | 0.00 | 0.00 | 0.00 |
October | 0.108099E+12 | 0.00 | 0.807962E+12 | 0.00 | 0.158766E+12 | 0.00 | 0.00 | 0.00 | 0.643582E+11 | 0.00 | 0.00 | 0.00 |
November | 0.104612E+12 | 0.00 | 0.109525E+13 | 0.00 | 0.205448E+12 | 0.00 | 0.00 | 0.00 | 0.917602E+11 | 0.00 | 0.00 | 0.00 |
December | 0.108099E+12 | 0.00 | 0.144567E+13 | 0.00 | 0.263000E+12 | 0.00 | 0.00 | 0.00 | 0.119747E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127277E+13 | 0.00 | 0.114269E+14 | 0.00 | 0.229267E+13 | 0.00 | 0.00 | 0.00 | 0.840818E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.976375E+11 | 0.00 | 0.453786E+12 | 0.00 | 0.918927E+11 | 0.00 | 0.00 | 0.00 | 0.315279E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108099E+12 | 0.00 | 0.148831E+13 | 0.00 | 0.327110E+12 | 0.00 | 0.00 | 0.00 | 0.119747E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.171008E+10 | 0.00 | 0.377167E+10 | 0.00 | 0.842232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154459E+10 | 0.00 | 0.103821E+11 | 0.00 | 0.216357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171008E+10 | 0.00 | 0.186220E+11 | 0.00 | 0.369842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165491E+10 | 0.00 | 0.248643E+11 | 0.00 | 0.483299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171008E+10 | 0.00 | 0.715745E+10 | 0.00 | 0.153555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165491E+10 | 0.00 | 0.139573E+11 | 0.00 | 0.304603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171008E+10 | 0.00 | 0.216282E+11 | 0.00 | 0.504171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171008E+10 | 0.00 | 0.279449E+11 | 0.00 | 0.635677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165491E+10 | 0.00 | 0.733016E+10 | 0.00 | 0.161785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171008E+10 | 0.00 | 0.132129E+11 | 0.00 | 0.267977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165491E+10 | 0.00 | 0.182110E+11 | 0.00 | 0.359111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171008E+10 | 0.00 | 0.242133E+11 | 0.00 | 0.472659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201348E+11 | 0.00 | 0.191295E+12 | 0.00 | 0.401326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154459E+10 | 0.00 | 0.377167E+10 | 0.00 | 0.842232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171008E+10 | 0.00 | 0.279449E+11 | 0.00 | 0.635677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.163745E+11 | 0.00 | 0.112556E+11 | 0.00 | 0.267915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147899E+11 | 0.00 | 0.750458E+11 | 0.00 | 0.159221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163745E+11 | 0.00 | 0.155586E+12 | 0.00 | 0.312603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158463E+11 | 0.00 | 0.223398E+12 | 0.00 | 0.437564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163745E+11 | 0.00 | 0.579438E+11 | 0.00 | 0.125784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158463E+11 | 0.00 | 0.128581E+12 | 0.00 | 0.281921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163745E+11 | 0.00 | 0.204389E+12 | 0.00 | 0.477361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163745E+11 | 0.00 | 0.262791E+12 | 0.00 | 0.599522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158463E+11 | 0.00 | 0.619105E+11 | 0.00 | 0.138244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163745E+11 | 0.00 | 0.110362E+12 | 0.00 | 0.226340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158463E+11 | 0.00 | 0.150941E+12 | 0.00 | 0.301485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163745E+11 | 0.00 | 0.198204E+12 | 0.00 | 0.393130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192797E+12 | 0.00 | 0.164041E+13 | 0.00 | 0.347997E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147899E+11 | 0.00 | 0.112556E+11 | 0.00 | 0.267915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163745E+11 | 0.00 | 0.262791E+12 | 0.00 | 0.599522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166690E+10 | 0.00 | 0.321811E+09 | 0.00 | 78608724.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150558E+10 | 0.00 | 0.544551E+10 | 0.00 | 0.117389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166690E+10 | 0.00 | 0.135316E+11 | 0.00 | 0.274816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161313E+10 | 0.00 | 0.209056E+11 | 0.00 | 0.413232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166690E+10 | 0.00 | 0.491702E+10 | 0.00 | 0.107777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161313E+10 | 0.00 | 0.125956E+11 | 0.00 | 0.277704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166690E+10 | 0.00 | 0.203881E+11 | 0.00 | 0.477948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166690E+10 | 0.00 | 0.261312E+11 | 0.00 | 0.598609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161313E+10 | 0.00 | 0.548788E+10 | 0.00 | 0.124454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166690E+10 | 0.00 | 0.929364E+10 | 0.00 | 0.193234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161313E+10 | 0.00 | 0.127624E+11 | 0.00 | 0.258401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166690E+10 | 0.00 | 0.173330E+11 | 0.00 | 0.348254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196264E+11 | 0.00 | 0.149113E+12 | 0.00 | 0.319968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150558E+10 | 0.00 | 0.321811E+09 | 0.00 | 78608724.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166690E+10 | 0.00 | 0.261312E+11 | 0.00 | 0.598609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.255807E+11 | 0.00 | 0.00 | 60904153.32 | 0.00 | 0.00 | 0.445738E+11 | 0.00 | 0.42 |
February | 0.920522E+10 | 0.00 | 0.00 | 74905898.41 | 0.00 | 0.00 | 0.531874E+11 | 0.00 | 0.54 |
March | 0.271066E+10 | 0.00 | 0.00 | 0.111422E+09 | 0.00 | 0.00 | 0.741796E+11 | 0.00 | 0.67 |
April | 0.322909E+09 | 0.00 | 0.00 | 0.108324E+09 | 0.00 | 0.00 | 0.703401E+11 | 0.00 | 0.94 |
May | 0.135583E+09 | 42041095.72 | 0.00 | 0.113916E+09 | 6524016.38 | 0.00 | 0.683122E+11 | 0.00 | 1.14 |
June | 0.107123E+09 | 0.377210E+09 | 0.00 | 0.107366E+09 | 357699.19 | 0.00 | 0.508381E+11 | 0.00 | 1.34 |
July | 0.134483E+09 | 0.132364E+10 | 0.00 | 0.104457E+09 | 30691129.14 | 0.00 | 0.317188E+11 | 0.00 | 1.13 |
August | 89896047.93 | 0.931127E+09 | 0.00 | 0.123060E+09 | 49730553.65 | 0.00 | 0.444720E+11 | 0.00 | 1.36 |
September | 0.249436E+09 | 0.358599E+09 | 0.00 | 0.120326E+09 | 37632052.85 | 0.00 | 0.614325E+11 | 0.00 | 1.33 |
October | 0.398575E+09 | 0.00 | 0.00 | 0.129042E+09 | 0.00 | 0.00 | 0.769013E+11 | 0.00 | 1.11 |
November | 0.373693E+09 | 0.00 | 0.00 | 0.125741E+09 | 0.00 | 0.00 | 0.772043E+11 | 0.00 | 0.82 |
December | 0.594994E+10 | 0.00 | 0.00 | 0.105172E+09 | 0.00 | 0.00 | 0.687076E+11 | 0.00 | 0.54 |
Annual Sum or Average | 0.452582E+11 | 0.303262E+10 | 0.00 | 0.128464E+10 | 0.124935E+09 | 0.00 | 0.721868E+12 | 0.00 | 0.95 |
Minimum of Months | 89896047.93 | 0.00 | 0.00 | 60904153.32 | 0.00 | 0.00 | 0.317188E+11 | 0.00 | 0.42 |
Maximum of Months | 0.255807E+11 | 0.132364E+10 | 0.00 | 0.129042E+09 | 49730553.65 | 0.00 | 0.772043E+11 | 0.00 | 1.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194306E+11 | 0.00 | 0.00 | 36547066.71 | 0.00 | 0.00 | 0.324939E+11 | 0.00 | 0.30 |
February | 0.781778E+10 | 0.00 | 0.00 | 57007154.39 | 0.00 | 0.00 | 0.389759E+11 | 0.00 | 0.40 |
March | 0.311246E+10 | 0.00 | 0.00 | 91282716.69 | 0.00 | 0.00 | 0.568748E+11 | 0.00 | 0.52 |
April | 0.405471E+10 | 0.00 | 0.00 | 95898615.13 | 0.00 | 0.00 | 0.567000E+11 | 0.00 | 0.78 |
May | 0.247470E+10 | 17208373.75 | 0.00 | 88549606.12 | 7828632.48 | 0.00 | 0.487550E+11 | 0.00 | 0.79 |
June | 0.477442E+10 | 0.215250E+09 | 0.00 | 91963222.15 | 12701503.76 | 0.00 | 0.388690E+11 | 0.00 | 1.05 |
July | 0.721042E+10 | 0.576019E+09 | 0.00 | 81648166.22 | 65129007.37 | 0.00 | 0.221614E+11 | 0.00 | 0.95 |
August | 0.933712E+10 | 0.422835E+09 | 0.00 | 99487470.73 | 47477099.10 | 0.00 | 0.337341E+11 | 0.00 | 1.18 |
September | 0.306931E+10 | 0.379260E+09 | 0.00 | 86402271.75 | 35952527.31 | 0.00 | 0.413278E+11 | 0.00 | 0.89 |
October | 0.280369E+10 | 0.00 | 0.00 | 93563831.27 | 0.00 | 0.00 | 0.531238E+11 | 0.00 | 0.78 |
November | 0.213379E+10 | 0.00 | 0.00 | 86814238.41 | 0.00 | 0.00 | 0.534573E+11 | 0.00 | 0.58 |
December | 0.363746E+10 | 0.00 | 0.00 | 77422307.24 | 0.00 | 0.00 | 0.524489E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.698564E+11 | 0.161057E+10 | 0.00 | 0.986587E+09 | 0.169089E+09 | 0.00 | 0.528922E+12 | 0.00 | 0.72 |
Minimum of Months | 0.213379E+10 | 0.00 | 0.00 | 36547066.71 | 0.00 | 0.00 | 0.221614E+11 | 0.00 | 0.30 |
Maximum of Months | 0.194306E+11 | 0.576019E+09 | 0.00 | 99487470.73 | 65129007.37 | 0.00 | 0.568748E+11 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.364605E+12 | 0.00 | 0.00 | 51607363.83 | 0.00 | 0.595075E+10 | 0.860742E+11 | 0.00 | 0.27 |
February | 0.241452E+12 | 0.00 | 0.00 | 0.132644E+09 | 0.00 | 0.103681E+10 | 0.122097E+12 | 0.00 | 0.31 |
March | 0.171607E+12 | 0.00 | 0.00 | 0.318166E+09 | 0.00 | 0.146827E+10 | 0.240612E+12 | 0.00 | 0.36 |
April | 0.708865E+11 | 0.00 | 0.00 | 0.461839E+09 | 0.00 | 0.00 | 0.310493E+12 | 0.00 | 0.51 |
May | 0.475470E+11 | 0.204988E+09 | 0.00 | 0.561112E+09 | 89262658.02 | 0.00 | 0.334046E+12 | 0.00 | 0.61 |
June | 0.262539E+11 | 0.229578E+10 | 0.00 | 0.714361E+09 | 0.141253E+09 | 0.00 | 0.302424E+12 | 0.00 | 0.82 |
July | 0.268519E+11 | 0.630499E+10 | 0.00 | 0.655019E+09 | 0.361157E+09 | 0.00 | 0.167896E+12 | 0.00 | 0.69 |
August | 0.248757E+11 | 0.445655E+10 | 0.00 | 0.750860E+09 | 0.478210E+09 | 0.00 | 0.249923E+12 | 0.00 | 0.80 |
September | 0.268756E+11 | 0.367285E+10 | 0.00 | 0.616482E+09 | 0.378650E+09 | 0.00 | 0.307702E+12 | 0.00 | 0.70 |
October | 0.558117E+11 | 0.00 | 0.00 | 0.497032E+09 | 0.00 | 0.00 | 0.319312E+12 | 0.00 | 0.55 |
November | 0.151267E+12 | 0.00 | 0.00 | 0.290669E+09 | 0.00 | 38256804.68 | 0.212771E+12 | 0.00 | 0.38 |
December | 0.278660E+12 | 0.00 | 0.00 | 0.133193E+09 | 0.00 | 0.185611E+10 | 0.125004E+12 | 0.00 | 0.28 |
Annual Sum or Average | 0.148669E+13 | 0.169351E+11 | 0.00 | 0.518299E+10 | 0.144853E+10 | 0.103502E+11 | 0.277835E+13 | 0.00 | 0.52 |
Minimum of Months | 0.248757E+11 | 0.00 | 0.00 | 51607363.83 | 0.00 | 0.00 | 0.860742E+11 | 0.00 | 0.27 |
Maximum of Months | 0.364605E+12 | 0.630499E+10 | 0.00 | 0.750860E+09 | 0.478210E+09 | 0.595075E+10 | 0.334046E+12 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.291021E+11 | 0.00 | 0.00 | 28784.68 | 0.00 | 0.950703E+10 | 91755677.12 | 0.00 | 0.25 |
February | 0.266413E+11 | 0.00 | 0.00 | 1222401.60 | 0.00 | 0.310742E+10 | 0.154928E+10 | 0.00 | 0.28 |
March | 0.241784E+11 | 0.00 | 0.00 | 6930824.09 | 0.00 | 0.210434E+10 | 0.734762E+10 | 0.00 | 0.30 |
April | 0.143295E+11 | 0.00 | 0.00 | 20770154.35 | 0.00 | 54617758.37 | 0.165004E+11 | 0.00 | 0.43 |
May | 0.101680E+11 | 10396694.80 | 0.00 | 35946240.26 | 5963137.65 | 0.267759E+09 | 0.230464E+11 | 0.00 | 0.57 |
June | 0.427299E+10 | 0.134029E+09 | 0.00 | 63416072.49 | 15136605.60 | 0.00 | 0.259393E+11 | 0.00 | 0.82 |
July | 0.298755E+10 | 0.413024E+09 | 0.00 | 63933813.86 | 28212412.56 | 0.00 | 0.150184E+11 | 0.00 | 0.71 |
August | 0.304325E+10 | 0.281089E+09 | 0.00 | 69547997.66 | 38638778.59 | 0.00 | 0.210024E+11 | 0.00 | 0.78 |
September | 0.712368E+10 | 0.325542E+09 | 0.00 | 40709133.81 | 29653261.88 | 0.00 | 0.198903E+11 | 0.00 | 0.63 |
October | 0.145597E+11 | 0.00 | 0.00 | 19058580.38 | 680691.99 | 0.179488E+09 | 0.133241E+11 | 0.00 | 0.44 |
November | 0.211928E+11 | 0.00 | 0.00 | 5075546.90 | 0.00 | 0.163206E+10 | 0.512314E+10 | 0.00 | 0.31 |
December | 0.272854E+11 | 0.00 | 0.00 | 1032481.53 | 0.00 | 0.507671E+10 | 0.131866E+10 | 0.00 | 0.25 |
Annual Sum or Average | 0.184885E+12 | 0.116408E+10 | 0.00 | 0.327672E+09 | 0.118285E+09 | 0.219294E+11 | 0.150152E+12 | 0.00 | 0.48 |
Minimum of Months | 0.298755E+10 | 0.00 | 0.00 | 28784.68 | 0.00 | 0.00 | 91755677.12 | 0.00 | 0.25 |
Maximum of Months | 0.291021E+11 | 0.413024E+09 | 0.00 | 69547997.66 | 38638778.59 | 0.950703E+10 | 0.259393E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.312830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382816E+10 | 0.00 | 0.00 | 0.31 |
February | 0.387837E+10 | 0.00 | 0.00 | 245600.01 | 0.00 | 0.132494E+10 | 0.227942E+09 | 0.00 | 0.36 |
March | 0.429784E+10 | 0.00 | 0.00 | 1274028.46 | 0.00 | 0.251920E+09 | 0.141439E+10 | 0.00 | 0.40 |
April | 0.288072E+10 | 0.00 | 0.00 | 4218808.98 | 0.00 | 0.00 | 0.326047E+10 | 0.00 | 0.65 |
May | 0.206493E+10 | 4636406.26 | 0.00 | 5908695.90 | 1247090.22 | 0.00 | 0.364618E+10 | 0.00 | 0.76 |
June | 0.114044E+10 | 38514099.37 | 0.00 | 10975693.68 | 2023331.82 | 0.00 | 0.460524E+10 | 0.00 | 1.19 |
July | 0.131894E+10 | 0.119890E+09 | 0.00 | 11013694.01 | 10374959.94 | 0.00 | 0.279409E+10 | 0.00 | 1.14 |
August | 0.182350E+10 | 85347292.17 | 0.00 | 11089388.07 | 7563035.60 | 0.00 | 0.362068E+10 | 0.00 | 1.28 |
September | 0.188722E+10 | 64318401.77 | 0.00 | 5593661.02 | 5727187.40 | 0.00 | 0.292922E+10 | 0.00 | 0.83 |
October | 0.308544E+10 | 0.00 | 0.00 | 3216929.08 | 0.00 | 0.00 | 0.237133E+10 | 0.00 | 0.62 |
November | 0.409027E+10 | 0.00 | 0.00 | 944199.16 | 0.00 | 0.106757E+09 | 0.102914E+10 | 0.00 | 0.42 |
December | 0.460165E+10 | 0.00 | 0.00 | 86300.06 | 0.00 | 0.968686E+09 | 0.183399E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.341976E+11 | 0.312706E+09 | 0.00 | 54566998.43 | 26935604.98 | 0.648046E+10 | 0.260821E+11 | 0.00 | 0.69 |
Minimum of Months | 0.114044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.460165E+10 | 0.119890E+09 | 0.00 | 11089388.07 | 10374959.94 | 0.382816E+10 | 0.460524E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.417003E+10 | 0.00 | 0.00 | 6218.41 | 0.00 | 0.436956E+10 | 23019414.14 | 0.00 | 0.60 |
February | 0.450733E+10 | 0.00 | 0.00 | 745774.54 | 0.00 | 0.162026E+10 | 0.653515E+09 | 0.00 | 0.69 |
March | 0.530264E+10 | 0.00 | 0.00 | 2128466.15 | 0.00 | 0.475653E+09 | 0.181078E+10 | 0.00 | 0.79 |
April | 0.420830E+10 | 0.00 | 0.00 | 4623051.54 | 0.00 | 8251446.30 | 0.340305E+10 | 0.00 | 1.20 |
May | 0.287537E+10 | 3207808.54 | 0.00 | 6702454.15 | 1545333.38 | 1620523.63 | 0.428156E+10 | 0.00 | 1.39 |
June | 0.190472E+10 | 32248609.71 | 0.00 | 11375537.36 | 2507214.10 | 0.00 | 0.466317E+10 | 0.00 | 2.04 |
July | 0.186065E+10 | 90952262.85 | 0.00 | 12100078.29 | 12856144.35 | 0.00 | 0.320525E+10 | 0.00 | 2.06 |
August | 0.292990E+10 | 69704458.75 | 0.00 | 9816527.89 | 9130593.08 | 0.00 | 0.356703E+10 | 0.00 | 2.21 |
September | 0.281155E+10 | 52793787.29 | 0.00 | 5626285.41 | 7021611.47 | 0.00 | 0.309173E+10 | 0.00 | 1.50 |
October | 0.399891E+10 | 0.00 | 0.00 | 3174993.39 | 0.00 | 2639028.27 | 0.258990E+10 | 0.00 | 1.13 |
November | 0.557521E+10 | 0.00 | 0.00 | 552098.38 | 0.00 | 0.274360E+09 | 0.583436E+09 | 0.00 | 0.80 |
December | 0.527781E+10 | 0.00 | 0.00 | 8314.68 | 0.00 | 0.181320E+10 | 38480124.25 | 0.00 | 0.60 |
Annual Sum or Average | 0.454224E+11 | 0.248907E+09 | 0.00 | 56859800.18 | 33060896.39 | 0.856555E+10 | 0.279109E+11 | 0.00 | 1.25 |
Minimum of Months | 0.186065E+10 | 0.00 | 0.00 | 6218.41 | 0.00 | 0.00 | 23019414.14 | 0.00 | 0.60 |
Maximum of Months | 0.557521E+10 | 90952262.85 | 0.00 | 12100078.29 | 12856144.35 | 0.436956E+10 | 0.466317E+10 | 0.00 | 2.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.486264E+10 | 0.00 | 0.00 | 2137888.49 | 0.00 | 0.454325E+10 | 0.197827E+10 | 0.00 | 0.52 |
February | 0.456452E+10 | 0.00 | 0.00 | 6717689.49 | 0.00 | 0.150808E+10 | 0.422847E+10 | 0.00 | 0.75 |
March | 0.551994E+10 | 0.00 | 0.00 | 8162527.28 | 0.00 | 0.450152E+09 | 0.619297E+10 | 0.00 | 0.87 |
April | 0.479370E+10 | 0.00 | 0.00 | 8477643.77 | 0.00 | 17125860.89 | 0.598573E+10 | 0.00 | 1.19 |
May | 0.394204E+10 | 6467470.60 | 0.00 | 8489629.07 | 1955773.91 | 68890740.50 | 0.513367E+10 | 0.00 | 1.22 |
June | 0.281051E+10 | 55364636.90 | 0.00 | 11800835.33 | 3173130.13 | 0.00 | 0.475228E+10 | 0.00 | 1.57 |
July | 0.253727E+10 | 0.171406E+09 | 0.00 | 12868923.59 | 16270736.10 | 0.00 | 0.300668E+10 | 0.00 | 1.54 |
August | 0.341235E+10 | 0.156666E+09 | 0.00 | 16062462.18 | 11860880.14 | 0.00 | 0.467730E+10 | 0.00 | 1.97 |
September | 0.296739E+10 | 0.163685E+09 | 0.00 | 12711447.43 | 3950001.96 | 0.00 | 0.585558E+10 | 0.00 | 1.63 |
October | 0.367867E+10 | 0.00 | 0.00 | 13914373.63 | 0.00 | 24362432.81 | 0.768161E+10 | 0.00 | 1.38 |
November | 0.463103E+10 | 0.00 | 0.00 | 7361263.53 | 0.00 | 0.402908E+09 | 0.554240E+10 | 0.00 | 0.88 |
December | 0.545518E+10 | 0.00 | 0.00 | 3761698.99 | 0.00 | 0.173329E+10 | 0.295629E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.491752E+11 | 0.553588E+09 | 0.00 | 0.112466E+09 | 37210522.24 | 0.874805E+10 | 0.579912E+11 | 0.00 | 1.18 |
Minimum of Months | 0.253727E+10 | 0.00 | 0.00 | 2137888.49 | 0.00 | 0.00 | 0.197827E+10 | 0.00 | 0.52 |
Maximum of Months | 0.551994E+10 | 0.171406E+09 | 0.00 | 16062462.18 | 16270736.10 | 0.454325E+10 | 0.768161E+10 | 0.00 | 1.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.668222E+10 | 0.00 | 0.00 | 113059.69 | 0.00 | 0.379628E+10 | 0.194955E+09 | 0.00 | 0.75 |
February | 0.673375E+10 | 0.00 | 0.00 | 1591035.31 | 0.00 | 0.283330E+09 | 0.158401E+10 | 0.00 | 0.89 |
March | 0.474091E+10 | 0.00 | 0.00 | 5029124.03 | 0.00 | 47180032.04 | 0.513823E+10 | 0.00 | 1.07 |
April | 0.200645E+10 | 0.00 | 0.00 | 12207522.14 | 0.00 | 0.00 | 0.832426E+10 | 0.00 | 1.76 |
May | 0.283392E+10 | 5214380.93 | 0.00 | 9681170.92 | 1927230.98 | 519899.16 | 0.581518E+10 | 0.00 | 1.75 |
June | 0.158638E+10 | 52788546.85 | 0.00 | 14876621.19 | 1031923.05 | 0.00 | 0.589240E+10 | 0.00 | 2.40 |
July | 0.170196E+10 | 0.185750E+09 | 0.00 | 17056349.92 | 10020957.35 | 0.00 | 0.383000E+10 | 0.00 | 2.37 |
August | 0.211345E+10 | 0.138018E+09 | 0.00 | 20435395.29 | 2747770.54 | 0.00 | 0.590296E+10 | 0.00 | 2.92 |
September | 0.293421E+10 | 0.106247E+09 | 0.00 | 6997629.71 | 1431833.38 | 0.00 | 0.401536E+10 | 0.00 | 1.83 |
October | 0.354438E+10 | 0.00 | 0.00 | 6110186.67 | 0.00 | 0.00 | 0.494758E+10 | 0.00 | 1.50 |
November | 0.457008E+10 | 0.00 | 0.00 | 3579822.13 | 0.00 | 1900091.15 | 0.387295E+10 | 0.00 | 1.07 |
December | 0.670109E+10 | 0.00 | 0.00 | 1837747.47 | 0.00 | 18718832.62 | 0.231819E+10 | 0.00 | 0.77 |
Annual Sum or Average | 0.461488E+11 | 0.488018E+09 | 0.00 | 99515664.46 | 17159715.31 | 0.414793E+10 | 0.518361E+11 | 0.00 | 1.59 |
Minimum of Months | 0.158638E+10 | 0.00 | 0.00 | 113059.69 | 0.00 | 0.00 | 0.194955E+09 | 0.00 | 0.75 |
Maximum of Months | 0.673375E+10 | 0.185750E+09 | 0.00 | 20435395.29 | 10020957.35 | 0.379628E+10 | 0.832426E+10 | 0.00 | 2.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.669828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715821E+11 | 0.00 | 0.00 | 0.35 |
February | 0.155743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404298E+11 | 0.00 | 0.00 | 0.36 |
March | 0.357662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200378E+11 | 0.00 | 0.00 | 0.37 |
April | 0.348378E+11 | 0.00 | 0.00 | 6058347.12 | 0.00 | 0.401295E+10 | 0.513094E+10 | 0.00 | 0.46 |
May | 0.271667E+11 | 50125622.77 | 0.00 | 27390747.28 | 15865301.27 | 0.218023E+10 | 0.154655E+11 | 0.00 | 0.60 |
June | 0.117510E+11 | 0.428359E+09 | 0.00 | 77772621.50 | 22011652.29 | 0.00 | 0.296109E+11 | 0.00 | 0.91 |
July | 0.672541E+10 | 0.144372E+10 | 0.00 | 81936275.65 | 57336382.63 | 0.00 | 0.191159E+11 | 0.00 | 0.82 |
August | 0.119867E+11 | 0.100756E+10 | 0.00 | 68084110.75 | 74520250.42 | 0.00 | 0.203465E+11 | 0.00 | 0.83 |
September | 0.242844E+11 | 0.608719E+09 | 0.00 | 29059113.19 | 59005535.64 | 0.547113E+09 | 0.124984E+11 | 0.00 | 0.65 |
October | 0.359407E+11 | 0.00 | 0.00 | 4318065.10 | 0.00 | 0.329460E+10 | 0.381713E+10 | 0.00 | 0.49 |
November | 0.284020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202560E+11 | 0.00 | 0.00 | 0.39 |
December | 0.128411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496138E+11 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.251975E+12 | 0.353849E+10 | 0.00 | 0.294619E+09 | 0.228739E+09 | 0.211954E+12 | 0.105985E+12 | 0.00 | 0.55 |
Minimum of Months | 0.669828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.359407E+11 | 0.144372E+10 | 0.00 | 81936275.65 | 74520250.42 | 0.715821E+11 | 0.296109E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.158343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825772E+11 | 0.00 | 0.00 | 0.71 |
February | 0.276569E+11 | 0.00 | 0.00 | 954763.85 | 0.00 | 0.470283E+11 | 0.976058E+09 | 0.00 | 0.77 |
March | 0.489606E+11 | 0.00 | 0.00 | 7187092.49 | 0.00 | 0.224258E+11 | 0.596486E+10 | 0.00 | 0.81 |
April | 0.396768E+11 | 0.00 | 0.00 | 28574476.04 | 0.00 | 0.413511E+10 | 0.221108E+11 | 0.00 | 1.06 |
May | 0.316626E+11 | 43167519.19 | 0.00 | 48111549.96 | 19261667.88 | 0.300591E+10 | 0.311237E+11 | 0.00 | 1.31 |
June | 0.173470E+11 | 0.415507E+09 | 0.00 | 0.104636E+09 | 30096141.98 | 0.00 | 0.405012E+11 | 0.00 | 1.89 |
July | 0.106266E+11 | 0.126936E+10 | 0.00 | 0.124864E+09 | 79396090.01 | 0.00 | 0.297143E+11 | 0.00 | 1.83 |
August | 0.178378E+11 | 0.103039E+10 | 0.00 | 92118744.70 | 0.102257E+09 | 0.00 | 0.317831E+11 | 0.00 | 1.84 |
September | 0.318063E+11 | 0.600992E+09 | 0.00 | 41059516.51 | 89297201.34 | 0.542034E+09 | 0.208777E+11 | 0.00 | 1.38 |
October | 0.487139E+11 | 0.00 | 0.00 | 10623839.88 | 0.00 | 0.293261E+10 | 0.841447E+10 | 0.00 | 1.05 |
November | 0.420970E+11 | 0.00 | 0.00 | 306044.65 | 0.00 | 0.240927E+11 | 0.531918E+09 | 0.00 | 0.83 |
December | 0.231654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608965E+11 | 0.00 | 0.00 | 0.71 |
Annual Sum or Average | 0.355385E+12 | 0.335941E+10 | 0.00 | 0.458437E+09 | 0.320308E+09 | 0.247636E+12 | 0.191998E+12 | 0.00 | 1.19 |
Minimum of Months | 0.106266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 |
Maximum of Months | 0.489606E+11 | 0.126936E+10 | 0.00 | 0.124864E+09 | 0.102257E+09 | 0.825772E+11 | 0.405012E+11 | 0.00 | 1.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.360632E+11 | 0.00 | 0.00 | 13610708.53 | 0.00 | 0.718813E+11 | 0.152285E+11 | 0.00 | 0.57 |
February | 0.395991E+11 | 0.00 | 0.00 | 57833586.85 | 0.00 | 0.334648E+11 | 0.335616E+11 | 0.00 | 0.78 |
March | 0.497103E+11 | 0.00 | 0.00 | 66381914.04 | 0.00 | 0.198294E+11 | 0.477056E+11 | 0.00 | 0.84 |
April | 0.430330E+11 | 0.00 | 0.00 | 63219791.18 | 0.00 | 0.423884E+10 | 0.427322E+11 | 0.00 | 1.01 |
May | 0.395495E+11 | 85283330.15 | 0.00 | 69025728.78 | 23311765.00 | 0.381672E+10 | 0.389143E+11 | 0.00 | 1.12 |
June | 0.273294E+11 | 0.667767E+09 | 0.00 | 95391014.37 | 35411343.53 | 11091195.49 | 0.354848E+11 | 0.00 | 1.35 |
July | 0.163479E+11 | 0.224713E+10 | 0.00 | 0.108096E+09 | 96090484.16 | 0.00 | 0.233117E+11 | 0.00 | 1.25 |
August | 0.219963E+11 | 0.218718E+10 | 0.00 | 0.135343E+09 | 0.124889E+09 | 0.00 | 0.358523E+11 | 0.00 | 1.57 |
September | 0.304537E+11 | 0.192851E+10 | 0.00 | 0.117379E+09 | 44144981.85 | 0.704563E+09 | 0.482675E+11 | 0.00 | 1.52 |
October | 0.376644E+11 | 0.00 | 0.00 | 0.124835E+09 | 0.00 | 0.238707E+10 | 0.615212E+11 | 0.00 | 1.28 |
November | 0.413038E+11 | 0.00 | 0.00 | 55579053.83 | 0.00 | 0.177669E+11 | 0.406947E+11 | 0.00 | 0.83 |
December | 0.438514E+11 | 0.00 | 0.00 | 19957479.13 | 0.00 | 0.462122E+11 | 0.168343E+11 | 0.00 | 0.60 |
Annual Sum or Average | 0.426902E+12 | 0.711587E+10 | 0.00 | 0.926653E+09 | 0.323848E+09 | 0.200313E+12 | 0.440109E+12 | 0.00 | 1.06 |
Minimum of Months | 0.163479E+11 | 0.00 | 0.00 | 13610708.53 | 0.00 | 0.00 | 0.152285E+11 | 0.00 | 0.57 |
Maximum of Months | 0.497103E+11 | 0.224713E+10 | 0.00 | 0.135343E+09 | 0.124889E+09 | 0.718813E+11 | 0.615212E+11 | 0.00 | 1.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836079E+11 | 0.00 | 0.00 | 0.76 |
February | 0.350441E+11 | 0.00 | 0.00 | 3003082.34 | 0.00 | 0.438375E+11 | 0.265884E+10 | 0.00 | 0.83 |
March | 0.550138E+11 | 0.00 | 0.00 | 8993738.49 | 0.00 | 0.210409E+11 | 0.777244E+10 | 0.00 | 0.88 |
April | 0.503824E+11 | 0.00 | 0.00 | 25186933.09 | 0.00 | 0.304422E+10 | 0.162696E+11 | 0.00 | 1.17 |
May | 0.402035E+11 | 48352200.10 | 0.00 | 54224615.79 | 23620475.45 | 0.273027E+10 | 0.265342E+11 | 0.00 | 1.43 |
June | 0.245262E+11 | 0.543188E+09 | 0.00 | 77460401.09 | 16031045.81 | 0.00 | 0.290722E+11 | 0.00 | 1.77 |
July | 0.141798E+11 | 0.205626E+10 | 0.00 | 82852341.01 | 33012684.35 | 0.00 | 0.187658E+11 | 0.00 | 1.57 |
August | 0.211050E+11 | 0.131346E+10 | 0.00 | 73996372.31 | 58709799.71 | 0.00 | 0.224170E+11 | 0.00 | 1.68 |
September | 0.386472E+11 | 0.995166E+09 | 0.00 | 33947125.42 | 29228661.36 | 0.584287E+09 | 0.158879E+11 | 0.00 | 1.46 |
October | 0.524040E+11 | 0.00 | 0.00 | 14159115.30 | 0.00 | 0.286202E+10 | 0.997401E+10 | 0.00 | 1.15 |
November | 0.470629E+11 | 0.00 | 0.00 | 2564054.82 | 0.00 | 0.208922E+11 | 0.378560E+10 | 0.00 | 0.90 |
December | 0.328760E+11 | 0.00 | 0.00 | 41797.85 | 0.00 | 0.572443E+11 | 0.202106E+09 | 0.00 | 0.77 |
Annual Sum or Average | 0.433422E+12 | 0.495643E+10 | 0.00 | 0.376430E+09 | 0.160603E+09 | 0.235844E+12 | 0.153340E+12 | 0.00 | 1.20 |
Minimum of Months | 0.141798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
Maximum of Months | 0.550138E+11 | 0.205626E+10 | 0.00 | 82852341.01 | 58709799.71 | 0.836079E+11 | 0.290722E+11 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.182796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855653E+10 | 0.00 | 0.00 | 0.43 |
February | 0.924702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536849E+10 | 0.00 | 0.00 | 0.44 |
March | 0.260330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381671E+10 | 0.00 | 0.00 | 0.46 |
April | 0.361652E+10 | 0.00 | 0.00 | 203153.46 | 0.00 | 0.145078E+10 | 0.188361E+09 | 0.00 | 0.55 |
May | 0.341286E+10 | 2783034.46 | 0.00 | 1765509.35 | 1142099.00 | 0.884125E+09 | 0.988490E+09 | 0.00 | 0.70 |
June | 0.181840E+10 | 23470991.91 | 0.00 | 6890902.57 | 2899061.38 | 48412349.02 | 0.248242E+10 | 0.00 | 0.99 |
July | 0.107932E+10 | 88224040.01 | 0.00 | 7863284.94 | 5551005.43 | 0.00 | 0.161898E+10 | 0.00 | 0.89 |
August | 0.175103E+10 | 60792310.19 | 0.00 | 6410976.80 | 7400350.76 | 24838927.50 | 0.162557E+10 | 0.00 | 0.89 |
September | 0.287092E+10 | 50875932.00 | 0.00 | 1972111.13 | 7774584.85 | 0.439386E+09 | 0.801053E+09 | 0.00 | 0.74 |
October | 0.338770E+10 | 0.00 | 0.00 | 65474.86 | 130370.57 | 0.148525E+10 | 50213572.43 | 0.00 | 0.59 |
November | 0.173475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363841E+10 | 0.00 | 0.00 | 0.47 |
December | 0.533284E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635810E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.239156E+11 | 0.226146E+09 | 0.00 | 25171413.12 | 24897471.99 | 0.320710E+11 | 0.775509E+10 | 0.00 | 0.63 |
Minimum of Months | 0.182796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.361652E+10 | 88224040.01 | 0.00 | 7863284.94 | 7774584.85 | 0.855653E+10 | 0.248242E+10 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.459244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777040E+10 | 0.00 | 0.00 | 0.65 |
February | 0.191894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466876E+10 | 0.00 | 0.00 | 0.73 |
March | 0.365643E+10 | 0.00 | 0.00 | 277927.33 | 0.00 | 0.301137E+10 | 0.276261E+09 | 0.00 | 0.77 |
April | 0.323373E+10 | 0.00 | 0.00 | 2130905.37 | 0.00 | 0.110921E+10 | 0.175973E+10 | 0.00 | 1.01 |
May | 0.282996E+10 | 2125495.11 | 0.00 | 4175563.28 | 1255079.63 | 0.703508E+09 | 0.270114E+10 | 0.00 | 1.28 |
June | 0.160010E+10 | 22760373.11 | 0.00 | 10423133.16 | 3185847.20 | 37167740.32 | 0.383379E+10 | 0.00 | 1.91 |
July | 0.893551E+09 | 77222697.05 | 0.00 | 12931553.56 | 6100131.32 | 0.00 | 0.297053E+10 | 0.00 | 1.88 |
August | 0.150029E+10 | 65083063.06 | 0.00 | 9943622.03 | 7910376.87 | 13660458.15 | 0.307031E+10 | 0.00 | 1.83 |
September | 0.258915E+10 | 52960400.15 | 0.00 | 3596627.88 | 6346964.95 | 0.325042E+09 | 0.183815E+10 | 0.00 | 1.33 |
October | 0.390391E+10 | 0.00 | 0.00 | 486430.66 | 143267.30 | 0.109797E+10 | 0.403140E+09 | 0.00 | 1.01 |
November | 0.258224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321863E+10 | 0.00 | 0.00 | 0.80 |
December | 0.101128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609773E+10 | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.261788E+11 | 0.220152E+09 | 0.00 | 43965763.26 | 24941667.28 | 0.280534E+11 | 0.168530E+11 | 0.00 | 1.16 |
Minimum of Months | 0.459244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 0.390391E+10 | 77222697.05 | 0.00 | 12931553.56 | 7910376.87 | 0.777040E+10 | 0.383379E+10 | 0.00 | 1.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243566E+10 | 0.00 | 0.00 | 510749.99 | 0.00 | 0.783844E+10 | 0.627022E+09 | 0.00 | 0.55 |
February | 0.303680E+10 | 0.00 | 0.00 | 3333344.38 | 0.00 | 0.423534E+10 | 0.221200E+10 | 0.00 | 0.72 |
March | 0.382168E+10 | 0.00 | 0.00 | 4902524.13 | 0.00 | 0.323182E+10 | 0.371713E+10 | 0.00 | 0.80 |
April | 0.377116E+10 | 0.00 | 0.00 | 4733105.43 | 0.00 | 0.149052E+10 | 0.355974E+10 | 0.00 | 0.99 |
May | 0.366970E+10 | 4166375.48 | 0.00 | 5951483.05 | 1634426.32 | 0.110815E+10 | 0.354919E+10 | 0.00 | 1.15 |
June | 0.286160E+10 | 35494444.54 | 0.00 | 9627543.80 | 4148766.64 | 82190275.84 | 0.340153E+10 | 0.00 | 1.43 |
July | 0.174098E+10 | 0.130958E+09 | 0.00 | 11637277.22 | 7943890.50 | 0.00 | 0.232056E+10 | 0.00 | 1.33 |
August | 0.221738E+10 | 0.132447E+09 | 0.00 | 14617636.08 | 7979473.04 | 34895410.28 | 0.353249E+10 | 0.00 | 1.62 |
September | 0.280020E+10 | 0.158601E+09 | 0.00 | 10350438.60 | 3343258.21 | 0.413874E+09 | 0.441398E+10 | 0.00 | 1.51 |
October | 0.362336E+10 | 200798.30 | 0.00 | 8986429.19 | 7364.03 | 0.915183E+09 | 0.453226E+10 | 0.00 | 1.21 |
November | 0.336503E+10 | 0.00 | 0.00 | 3312821.13 | 0.00 | 0.276826E+10 | 0.245615E+10 | 0.00 | 0.77 |
December | 0.288802E+10 | 0.00 | 0.00 | 1029615.89 | 0.00 | 0.566106E+10 | 0.894700E+09 | 0.00 | 0.57 |
Annual Sum or Average | 0.362316E+11 | 0.461868E+09 | 0.00 | 78992968.89 | 25057178.75 | 0.277797E+11 | 0.352167E+11 | 0.00 | 1.06 |
Minimum of Months | 0.174098E+10 | 0.00 | 0.00 | 510749.99 | 0.00 | 0.00 | 0.627022E+09 | 0.00 | 0.55 |
Maximum of Months | 0.382168E+10 | 0.158601E+09 | 0.00 | 14617636.08 | 7979473.04 | 0.783844E+10 | 0.453226E+10 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.852480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846077E+10 | 0.00 | 0.00 | 0.73 |
February | 0.223845E+10 | 0.00 | 0.00 | 173638.79 | 0.00 | 0.508893E+10 | 0.184445E+09 | 0.00 | 0.83 |
March | 0.407331E+10 | 0.00 | 0.00 | 653385.48 | 0.00 | 0.331442E+10 | 0.618612E+09 | 0.00 | 0.89 |
April | 0.449985E+10 | 0.00 | 0.00 | 2054503.84 | 0.00 | 0.104432E+10 | 0.144985E+10 | 0.00 | 1.19 |
May | 0.382493E+10 | 2634391.09 | 0.00 | 4900999.32 | 1432542.71 | 0.741549E+09 | 0.253770E+10 | 0.00 | 1.49 |
June | 0.261554E+10 | 30150507.94 | 0.00 | 8664209.68 | 1052714.46 | 33984668.75 | 0.274844E+10 | 0.00 | 1.89 |
July | 0.159477E+10 | 0.120455E+09 | 0.00 | 9110321.78 | 2459475.92 | 0.00 | 0.172027E+10 | 0.00 | 1.66 |
August | 0.224719E+10 | 76918834.34 | 0.00 | 7948448.61 | 4730646.38 | 30825472.54 | 0.198850E+10 | 0.00 | 1.74 |
September | 0.359250E+10 | 83150791.53 | 0.00 | 3085685.00 | 3610663.52 | 0.351227E+09 | 0.138603E+10 | 0.00 | 1.50 |
October | 0.438864E+10 | 0.00 | 0.00 | 1012905.70 | 163524.71 | 0.106168E+10 | 0.796774E+09 | 0.00 | 1.18 |
November | 0.328544E+10 | 0.00 | 0.00 | 74189.78 | 0.00 | 0.315027E+10 | 0.174611E+09 | 0.00 | 0.91 |
December | 0.171706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636996E+10 | 0.00 | 0.00 | 0.75 |
Annual Sum or Average | 0.349302E+11 | 0.313309E+09 | 0.00 | 37678287.96 | 13449567.70 | 0.296479E+11 | 0.136052E+11 | 0.00 | 1.23 |
Minimum of Months | 0.852480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
Maximum of Months | 0.449985E+10 | 0.120455E+09 | 0.00 | 9110321.78 | 4730646.38 | 0.846077E+10 | 0.274844E+10 | 0.00 | 1.89 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 15410289.54 | 0.00 | 0.00 | 2256734.46 | 0.00 | 0.00 | 0.834250E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7052333.67 | 0.00 | 0.00 | 0.645448E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 13681121.56 | 0.00 | 0.00 | 0.660984E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 17279878.96 | 0.00 | 0.00 | 0.462926E+09 | 0.00 | 0.29 |
May | 0.00 | 143487.60 | 0.00 | 3936002.93 | 0.00 | 0.00 | 0.407839E+09 | 0.00 | 0.29 |
June | 0.00 | 13410891.66 | 0.00 | 7425200.44 | 0.00 | 0.00 | 0.201173E+09 | 0.00 | 0.30 |
July | 0.00 | 21308024.34 | 0.00 | 9006717.74 | 0.00 | 0.00 | 81849224.59 | 0.00 | 0.28 |
August | 0.00 | 5701230.98 | 0.00 | 16477813.00 | 0.00 | 0.00 | 0.152119E+09 | 0.00 | 0.31 |
September | 0.00 | 11412500.15 | 0.00 | 3473154.57 | 0.00 | 0.00 | 0.257517E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8241061.12 | 0.00 | 0.00 | 0.439875E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12010426.08 | 0.00 | 0.00 | 0.544004E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16542730.20 | 0.00 | 0.00 | 0.716620E+09 | 0.00 | 0.28 |
Annual Sum or Average | 15410289.54 | 51976134.73 | 0.00 | 0.117383E+09 | 0.00 | 0.00 | 0.540460E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2256734.46 | 0.00 | 0.00 | 81849224.59 | 0.00 | 0.28 |
Maximum of Months | 15410289.54 | 21308024.34 | 0.00 | 17279878.96 | 0.00 | 0.00 | 0.834250E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.276700E+10 | 0.00 | 0.00 | 8516546.13 | 0.00 | 0.00 | 0.567473E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 54718792.81 | 0.00 | 0.00 | 0.647056E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.118059E+09 | 0.00 | 0.00 | 0.662823E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.157199E+09 | 0.00 | 0.00 | 0.464235E+10 | 0.00 | 0.29 |
May | 3116017.78 | 1351117.57 | 0.00 | 31426571.58 | 0.00 | 0.00 | 0.408828E+10 | 0.00 | 0.29 |
June | 0.00 | 0.132799E+09 | 0.00 | 68455882.12 | 0.00 | 0.00 | 0.201966E+10 | 0.00 | 0.30 |
July | 0.00 | 0.212127E+09 | 0.00 | 85042773.36 | 0.00 | 0.00 | 0.823797E+09 | 0.00 | 0.28 |
August | 0.00 | 59141413.42 | 0.00 | 0.154032E+09 | 0.00 | 0.00 | 0.152735E+10 | 0.00 | 0.31 |
September | 0.00 | 0.111260E+09 | 0.00 | 28290952.03 | 0.00 | 0.00 | 0.259664E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 70418724.84 | 0.00 | 0.00 | 0.441007E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.102983E+09 | 0.00 | 0.00 | 0.545621E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.142073E+09 | 0.00 | 0.00 | 0.718733E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.277012E+10 | 0.516678E+09 | 0.00 | 0.102122E+10 | 0.00 | 0.00 | 0.515252E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 8516546.13 | 0.00 | 0.00 | 0.823797E+09 | 0.00 | 0.28 |
Maximum of Months | 0.276700E+10 | 0.212127E+09 | 0.00 | 0.157199E+09 | 0.00 | 0.00 | 0.718733E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.594096E+09 | 0.00 | 0.00 | 262203.49 | 0.00 | 0.00 | 0.231786E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4496603.71 | 0.00 | 0.00 | 0.647970E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 10786132.05 | 0.00 | 0.00 | 0.663858E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 14987829.63 | 0.00 | 0.00 | 0.465127E+09 | 0.00 | 0.29 |
May | 28471239.60 | 137052.79 | 0.00 | 2674850.00 | 0.00 | 0.00 | 0.380488E+09 | 0.00 | 0.29 |
June | 0.00 | 13316223.30 | 0.00 | 6695939.49 | 0.00 | 0.00 | 0.202332E+09 | 0.00 | 0.30 |
July | 0.00 | 21216637.23 | 0.00 | 8470642.74 | 0.00 | 0.00 | 82528963.91 | 0.00 | 0.28 |
August | 0.00 | 5944231.94 | 0.00 | 15262939.52 | 0.00 | 0.00 | 0.152904E+09 | 0.00 | 0.31 |
September | 6915588.09 | 11101535.41 | 0.00 | 2412387.06 | 0.00 | 0.00 | 0.254420E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6208490.48 | 0.00 | 0.00 | 0.442107E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9236528.92 | 0.00 | 0.00 | 0.546739E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13071763.66 | 0.00 | 0.00 | 0.719964E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.629483E+09 | 51715680.67 | 0.00 | 94566310.75 | 0.00 | 0.00 | 0.479022E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 262203.49 | 0.00 | 0.00 | 82528963.91 | 0.00 | 0.28 |
Maximum of Months | 0.594096E+09 | 21216637.23 | 0.00 | 15262939.52 | 0.00 | 0.00 | 0.719964E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.215937E+09 | 0.00 | 0.00 | 0.230711E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.405446E+09 | 0.00 | 0.00 | 0.176946E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.709385E+09 | 0.00 | 0.00 | 0.179629E+11 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.00 | 0.864518E+09 | 0.00 | 0.00 | 0.123135E+11 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.00 | 0.219845E+09 | 0.00 | 0.00 | 0.110015E+11 | 0.00 | 0.33 |
June | 0.00 | 0.269527E+09 | 0.00 | 0.375971E+09 | 0.00 | 0.00 | 0.532229E+10 | 0.00 | 0.34 |
July | 0.00 | 0.421728E+09 | 0.00 | 0.457379E+09 | 0.00 | 0.00 | 0.221282E+10 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.00 | 0.932258E+09 | 0.00 | 0.00 | 0.548417E+10 | 0.00 | 0.35 |
September | 0.00 | 0.251472E+09 | 0.00 | 0.194660E+09 | 0.00 | 0.00 | 0.667136E+10 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.00 | 0.432038E+09 | 0.00 | 0.00 | 0.114227E+11 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.624857E+09 | 0.00 | 0.00 | 0.145889E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.862760E+09 | 0.00 | 0.00 | 0.192799E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.942727E+09 | 0.00 | 0.629505E+10 | 0.00 | 0.00 | 0.147026E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.194660E+09 | 0.00 | 0.00 | 0.221282E+10 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.421728E+09 | 0.00 | 0.932258E+09 | 0.00 | 0.00 | 0.230711E+11 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:03:16
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.279651E+12 | 0.462992E+11 | 0.00 | 0.171713E+13 | 0.717032E+12 |
February | 0.371703E+12 | 0.360246E+11 | 0.00 | 0.159986E+13 | 0.983357E+12 |
March | 0.634466E+12 | 0.336870E+11 | 0.00 | 0.191077E+13 | 0.146951E+13 |
April | 0.679243E+12 | 0.239997E+11 | 0.00 | 0.202963E+13 | 0.189895E+13 |
May | 0.893305E+12 | 0.237161E+11 | 0.00 | 0.198381E+13 | 0.876175E+12 |
June | 0.976493E+12 | 0.122704E+11 | 0.00 | 0.169700E+13 | 0.187525E+13 |
July | 0.967083E+12 | 0.800698E+10 | 0.00 | 0.136687E+13 | 0.292642E+13 |
August | 0.805174E+12 | 0.868640E+10 | 0.00 | 0.153158E+13 | 0.318198E+13 |
September | 0.607431E+12 | 0.157350E+11 | 0.00 | 0.175665E+13 | 0.116861E+13 |
October | 0.400755E+12 | 0.230487E+11 | 0.00 | 0.212382E+13 | 0.116854E+13 |
November | 0.221759E+12 | 0.324985E+11 | 0.00 | 0.188930E+13 | 0.144328E+13 |
December | 0.183967E+12 | 0.413115E+11 | 0.00 | 0.170839E+13 | 0.192431E+13 |
Annual Sum or Average | 0.702103E+13 | 0.305284E+12 | 0.00 | 0.213148E+14 | 0.196334E+14 |
Minimum of Months | 0.183967E+12 | 0.800698E+10 | 0.00 | 0.136687E+13 | 0.717032E+12 |
Maximum of Months | 0.976493E+12 | 0.462992E+11 | 0.00 | 0.212382E+13 | 0.318198E+13 |