Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 09:03:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31788.48 | 686.27 | 686.27 |
Net Site Energy | 31788.48 | 686.27 | 686.27 |
Total Source Energy | 97969.60 | 2115.04 | 2115.04 |
Net Source Energy | 97969.60 | 2115.04 | 2115.04 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 640.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4111.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3711.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 670.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1941.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2525.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 801.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1454.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7725.98 |
Humidification | 8.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
Heat Recovery | 50.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 657.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30490.10 | 1298.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10009.48 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 640.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 4111.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3711.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 670.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2525.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 801.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1454.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7725.98 |
Humidification | General | 8.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
Heat Recovery | General | 50.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 657.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 640.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 4111.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3711.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 670.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1941.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2525.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 801.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1454.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7725.98 |
Humidification | Unassigned | 8.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
Heat Recovery | Unassigned | 50.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 657.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 192.19 | 28.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Other | 371.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 658.24 | 28.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 192.19 | 28.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Other | 371.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 658.24 | 28.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 30490.104 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 30490.104 | 100.00 |
Total On-Site and Utility Electric Sources | 30490.104 | 100.00 |
Total Electricity End Uses | 30490.104 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 1232.78 | 57.10 |
Air to Air Heat Recovery for Heating | 926.28 | 42.90 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2159.06 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 10009.48 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 10009.48 | 100.00 |
Total Water End Uses | 10009.48 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 29.67 |
Time Setpoint Not Met During Occupied Cooling | 501.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5940.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.3279 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.3279 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.3279 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.3279 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 9.3279 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.3279 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 9.3279 | 18.58 | 484.4232 | |
Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.8860 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-15:50 | 13-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 14-APR-15:00 |
Heating | 0.00 | 1589015.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 453790.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84885.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 235348.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 68250.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 92421.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10207.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2051130.69 | 1599222.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1589015.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 453790.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5451.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 235348.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 68250.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 92421.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 10207.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 694.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13021.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11753.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2124.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6150.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7999.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2539.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4605.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 28.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 159.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 712.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 96562.16 | 1407.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 14.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 281.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 253.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 172.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 54.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 99.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2084.66 | 30.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 14.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 281.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 253.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 172.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 54.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 99.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2084.66 | 30.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.85 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.488735 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.65 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.469960 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 22.10 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.15 | 0.309238 | 0.315000 | 1.94 | 0.824634 | 0.500000 | 0.001232 | 0.000165 | 1.94 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 58.05 | 0.327633 | 0.327000 | 18.98 | 0.873689 | 0.500000 | 0.001163 | 0.004064 | 18.98 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.74 | 0.331613 | 0.337000 | 1.93 | 0.884301 | 0.500000 | 0.001149 | 0.000766 | 2.70 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.992262 | 0.240683 | 0.300000 | 0.297679 | 0.641821 | 0.500000 | 0.001583 | 0.000122 | 0.429468 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.955957 | 0.160996 | 0.300000 | 0.286787 | 0.429322 | 0.500000 | 0.002367 | 0.000084 | 0.295666 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.14 | 0.210042 | 0.300000 | 0.341112 | 0.560111 | 0.500000 | 0.001814 | 0.000137 | 0.484494 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.23 | 0.124964 | 0.300000 | 0.369477 | 0.333239 | 0.500000 | 0.003049 | 0.000076 | 0.369477 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.31 | 0.256515 | 0.300000 | 2.79 | 0.684040 | 0.500000 | 0.001485 | 0.002058 | 7.28 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 9.80 | 0.157001 | 0.300000 | 2.94 | 0.418669 | 0.500000 | 0.002427 | 0.001350 | 4.78 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 10.73 | 0.222482 | 0.300000 | 3.22 | 0.593285 | 0.500000 | 0.001712 | 0.002035 | 7.20 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.37 | 0.148442 | 0.300000 | 3.11 | 0.395847 | 0.500000 | 0.002567 | 0.001304 | 4.61 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.06 | 0.224395 | 0.300000 | 0.319286 | 0.598387 | 0.500000 | 0.001698 | 0.000266 | 0.940328 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.01 | 0.153067 | 0.300000 | 0.301643 | 0.408179 | 0.500000 | 0.002489 | 0.000174 | 0.614373 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.20 | 0.199092 | 0.300000 | 0.359873 | 0.530911 | 0.500000 | 0.001914 | 0.000263 | 0.930660 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.13 | 0.136626 | 0.300000 | 0.337940 | 0.364337 | 0.500000 | 0.002789 | 0.000171 | 0.604058 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18808.47 | 0.000165 | 379.16 |
CORE_MID VAV BOX REHEAT COIL | 464580.39 | 0.004064 | 11044.24 |
CORE_TOP VAV BOX REHEAT COIL | 87569.98 | 0.000766 | 2311.76 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13894.74 | 0.000122 | 366.60 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9564.50 | 0.000084 | 252.33 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 15671.90 | 0.000137 | 413.45 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8690.05 | 0.000076 | 204.17 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 235288.57 | 0.002058 | 6204.29 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 154368.28 | 0.001350 | 4070.45 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 232645.67 | 0.002035 | 6134.66 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 149044.56 | 0.001304 | 3930.16 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 30372.89 | 0.000266 | 800.75 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 19843.93 | 0.000174 | 523.16 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 30061.01 | 0.000263 | 792.53 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 19511.04 | 0.000171 | 514.39 |
VAV_BOT WITH REHEAT HEATING COIL | 56929.09 | 0.000498 | 933.50 |
VAV_MID WITH REHEAT HEATING COIL | 552647.74 | 0.004835 | 9026.33 |
VAV_TOP WITH REHEAT HEATING COIL | 53128.59 | 0.000465 | 876.29 |
CAV_BAS HEATING COIL | 281605.15 | 0.002464 | 6249.44 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.23 | 3.23 | 10.47 | 3.23 | 9.71 | 9.71 | 0.300000 | 0.333009 | 9.71 |
VAV_MID WITH REHEAT | 49.13 | 31.05 | 98.27 | 36.13 | 90.43 | 90.43 | 0.300000 | 0.399584 | 90.43 |
VAV_TOP WITH REHEAT | 5.07 | 3.25 | 10.13 | 5.79 | 9.66 | 9.66 | 0.300000 | 0.599935 | 9.66 |
CAV_BAS | 5.85 | 5.85 | 5.85 | 5.85 | 5.85 | 5.85 | 1.00 | 1.00 | 5.85 |
AIRLOOP DATACENTER BASEMENT | 22.10 | 22.10 | 22.10 | 22.10 | 22.10 | 22.10 | 1.00 | 0.999989 | 22.10 |
AIRLOOP DATACENTER BOT | 0.488735 | 0.488735 | 0.488735 | 0.488735 | 0.488735 | 0.488735 | 1.00 | 1.00 | 0.488735 |
AIRLOOP DATACENTER MID | 4.65 | 4.65 | 4.65 | 4.65 | 4.65 | 4.65 | 1.00 | 1.00 | 4.65 |
AIRLOOP DATACENTER TOP | 0.469960 | 0.469960 | 0.469960 | 0.469960 | 0.469960 | 0.469960 | 1.00 | 1.00 | 0.469960 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.71 | 2.54 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 90.43 | 25.38 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.66 | 2.54 |
CAV_BAS_OA_CONTROLLER | 5.85 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 22.10 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.488735 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.65 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.469960 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.86 | 6.67 | 10.98 | 0.010431 | 0.008500 | 238172.21 | 0.010132 | 9.71 |
VAV_MID WITH REHEAT COOLING COIL | 27.18 | 6.67 | 10.88 | 0.010679 | 0.008500 | 2330680.07 | 0.099153 | 90.43 |
VAV_TOP WITH REHEAT COOLING COIL | 26.75 | 6.67 | 10.98 | 0.010417 | 0.008500 | 235167.98 | 0.010005 | 9.66 |
CAV_BAS COOLING COIL | 25.83 | 6.67 | 11.37 | 0.010203 | 0.008500 | 129625.70 | 0.005515 | 5.85 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.71 |
VAV_MID WITH REHEAT FAN | 90.43 |
VAV_TOP WITH REHEAT FAN | 9.66 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010132 | 0.000047 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000498 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.099153 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004835 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.010005 | 0.000048 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000465 | |
CAV_BAS_COOLC_CONTROLLER | 0.005515 | 0.000086 |
CAV_BAS_HEATC_CONTROLLER | 0.002464 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.85 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 22.10 | 437646.58 | 303283.71 | 0.010718 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.488735 | 9630.22 | 6683.16 | 0.000236 |
AIRLOOP DATACENTER MID COOLING COIL | 4.65 | 91737.04 | 63598.28 | 0.002247 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.469960 | 9272.38 | 6430.23 | 0.000227 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 22.10 | 22.10 | 22.10 | 22.10 | 437646.58 | 437646.58 | 18278.08 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.488735 | 0.488735 | 0.488735 | 0.488735 | 9630.22 | 9630.22 | 844.37 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.65 | 4.65 | 4.65 | 4.65 | 91737.04 | 91737.04 | 8443.71 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.469960 | 0.469960 | 0.469960 | 0.469960 | 9272.38 | 9272.38 | 844.37 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 22.10 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.488735 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.65 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.469960 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 22.10 | 437646.58 | 0.010718 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.488735 | 9630.22 | 0.000236 |
AIRLOOP DATACENTER MID HEATING COIL | 4.65 | 91737.04 | 0.002247 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.469960 | 9272.38 | 0.000227 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 18278.08 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 844.37 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8443.71 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 844.37 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000153 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.124804 | 25717.50 | |
HEATSYS1 PUMP | 0.021296 | 6413.32 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.124804 | 14.98 |
HEATSYS1 | 0.021296 | 2.56 |
COOLSYS1_SUPPLY | 0.124804 | 14.98 |
SINGLE WATER PLANT LOOP | 0.013427 | 1.61 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.124804 | 0.124804 | 523865.35 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2434226.56 | 2434226.56 | 0.021296 |
CENTRAL BOILER | 553097.65 | 542182.77 | 0.013427 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.124804 | 17805.09 |
PLANT CIRC PUMP | 0.013427 | 3424.68 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.124804 | 0.062735 | 1478271.96 | 1485342.51 | 0.073504 |
COOLSYS1 CHILLER2 | 0.124804 | 0.062735 | 1478271.96 | 1485342.51 | 0.073504 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013427 | 139666.47 | 58751.96 | 69833.23 | 7879.72 | 21362.98 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.147008 | 17.64 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.147008 | 44275.67 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 58.93 | 1762320.86 | 11.79 | 220290.11 |
TOWERWATERSYS COOLTOWER 2 | 58.93 | 1762320.86 | 11.79 | 220290.11 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.076347 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.328 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 14.170 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 9.328 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.751 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 25926.330 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25926.330 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 7310.116 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7310.116 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.498 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.416 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.867 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5004 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5391 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3683 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.14091426E-14 | 0.48101397E-16 | -0.12271849E-09 | -0.49605034E-17 |
51 | 8 | 0.18065296E-07 | 0.19413100E-12 | 0.33649602E-03 | -0.20540863E-09 |
52 | 7 | -0.11004888E-01 | 0.10546945E-07 | -0.21303752E-01 | 0.12512956E-03 |
53 | 6 | 0.37174157 | 0.37425545E-05 | 0.44335749 | -0.43515980E-02 |
54 | 5 | -4.8625044 | 0.14213861E-03 | -4.2200868 | 0.59116134E-01 |
55 | 4 | 31.551289 | 0.11806248E-02 | 20.574731 | -0.40285082 |
56 | 3 | -108.13650 | 0.26081321E-02 | -53.912227 | 1.4705586 |
57 | 2 | 194.06739 | 0.14847903E-02 | 76.306869 | -2.8520668 |
58 | 1 | -170.03224 | 0.16027253E-03 | -54.802483 | 2.7257428 |
59 | 0 | 57.057407 | 0.92345258E-06 | 15.636386 | |
60 | 9 | 0.11726792E-14 | 0.46876770E-16 | -0.12664795E-09 | -0.40425794E-17 |
61 | 8 | 0.18621286E-07 | 0.18477046E-12 | 0.34269676E-03 | -0.21173044E-09 |
62 | 7 | -0.11191167E-01 | 0.99660246E-08 | -0.21572393E-01 | 0.12724763E-03 |
63 | 6 | 0.37680492 | 0.35261678E-05 | 0.44770143 | -0.44112820E-02 |
64 | 5 | -4.9119389 | 0.13358806E-03 | -4.2535898 | 0.59729078E-01 |
65 | 4 | 31.770087 | 0.11071467E-02 | 20.706000 | -0.40575564 |
66 | 3 | -108.60241 | 0.24410452E-02 | -54.171883 | 1.4772891 |
67 | 2 | 194.52961 | 0.13872791E-02 | 76.544434 | -2.8594062 |
68 | 1 | -170.20315 | 0.14950961E-03 | -54.870487 | 2.7287383 |
69 | 0 | 57.057407 | 0.85997654E-06 | 15.624277 | |
70 | 9 | 0.98458787E-15 | 0.55454857E-16 | -0.10492535E-09 | -0.15601002E-17 |
71 | 8 | 0.15540463E-07 | 0.23311053E-12 | 0.30746206E-03 | -0.17670042E-09 |
72 | 7 | -0.10129638E-01 | 0.13130386E-07 | -0.20040359E-01 | 0.11517765E-03 |
73 | 6 | 0.34794661 | 0.47273228E-05 | 0.42286390 | -0.40711180E-02 |
74 | 5 | -4.6301347 | 0.18177508E-03 | -4.0616887 | 0.56235001E-01 |
75 | 4 | 30.522476 | 0.15264987E-02 | 19.953355 | -0.38919251 |
76 | 3 | -105.94476 | 0.34047073E-02 | -52.682811 | 1.4388992 |
77 | 2 | 191.89184 | 0.19546755E-02 | 75.183526 | -2.8175246 |
78 | 1 | -169.22736 | 0.21263380E-03 | -54.483619 | 2.7116363 |
79 | 0 | 57.057407 | 0.12355163E-05 | 15.695393 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.4644_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.640 | 2.640 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.640 | 2.640 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.4644_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.640 | 2.640 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.640 | 2.640 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.48111E-002 | 0.16139 | 0.61554 | 0.61554 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11929 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.48111E-002 | 0.16139 | 0.61554 | 0.61554 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11929 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.48111E-002 | 0.16139 | 0.61554 | 0.61554 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11929 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.48111E-002 | 0.16139 | 0.61554 | 0.61554 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11929 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8576E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8588E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0627E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0636E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1965E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1972E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2452E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8841E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9574E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0842E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1455E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2138E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2647E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2574E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2891E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.9514E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5821E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.9420E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9097E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1838E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3924E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6042E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.1095E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8923E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9988E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0932E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1909E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2216E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2944E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2577E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2900E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8576E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8591E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0626E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0639E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1965E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1974E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2451E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9893E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1535E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9090E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0865E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6660E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7416E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1302E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1521E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6649E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7784E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5899E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6705E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6669E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5111E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6787E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.9865E-003 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9489E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0027E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8579E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8975E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6437E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6612E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1303E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1525E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2519E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2531E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0708E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0718E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.5534E-004 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.5613E-004 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2452E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2802E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3489E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0943E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1498E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.7508E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0180E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2577E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2900E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9763E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1285E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5382E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.6054E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5549E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.1673E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6042E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.1067E-003 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2777E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3470E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0909E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1437E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.6906E-004 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.9954E-004 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2574E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2891E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2518E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2530E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0707E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0716E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.5522E-004 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.5579E-004 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2451E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3645E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4222E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1390E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1805E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1397E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1547E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1303E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1525E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.5180E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3326E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1920E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1281E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6222E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1005E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6787E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.9865E-003 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3925E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4998E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1750E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2820E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1598E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2218E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1302E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1521E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.0715E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.7955E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.9227E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.2135E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.5812E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.3388E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.0133E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4574E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1810E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4404E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.0992E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3184E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1418E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1001E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.0820E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4729E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3737E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6608E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8955E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3196E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.9079E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0403E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0133E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4571E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9382E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8591E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.5823E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6090E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0182E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5792E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0820E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4729E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.0678E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.8033E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.9195E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.2230E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.5838E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.3458E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.0168E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4602E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1798E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4428E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.0990E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3211E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1435E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1038E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.0854E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4757E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3708E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6614E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8936E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3202E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.9089E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0418E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0168E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4599E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9362E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8605E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.5810E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6103E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0194E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5817E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0854E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4757E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 78267.83568 | 78267.83568 | 5.84563 | 5.84563 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -6.30000 | 2.29779E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 82357.66466 | 82357.66466 | 6.15075 | 6.15075 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -6.30000 | 2.29779E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 777519.50276 | 777519.50276 | 58.05404 | 58.05404 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 280293.32590 | 280293.32590 | 12.26174 | 12.26174 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 76821.34944 | 76821.34944 | 5.73574 | 5.73574 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 61327.70771 | 61327.70771 | 2.70325 | 2.70325 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13166.73446 | 13166.73446 | 0.99226 | 0.99226 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 9731.54397 | 9731.54397 | 0.42947 | 0.42947 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12685.03860 | 12685.03860 | 0.95596 | 0.95596 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 30.52083 | 1.44662E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 6698.01016 | 6698.01016 | 0.29567 | 0.29567 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 15087.87876 | 15087.87876 | 1.13704 | 1.13704 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 10973.99237 | 10973.99237 | 0.48449 | 0.48449 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 16342.64323 | 16342.64323 | 1.23159 | 1.23159 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 5110.99486 | 5110.99486 | 0.22530 | 0.22530 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 123533.85594 | 123533.85594 | 9.31020 | 9.31020 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 164701.69641 | 164701.69641 | 7.28144 | 7.28144 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 130070.93264 | 130070.93264 | 9.80282 | 9.80282 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.79000 | 1.44667E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 108056.77091 | 108056.77091 | 4.77739 | 4.77739 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 142434.17322 | 142434.17322 | 10.73462 | 10.73462 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 162853.90780 | 162853.90780 | 7.19951 | 7.19951 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 137570.30299 | 137570.30299 | 10.36800 | 10.36800 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 104334.41755 | 104334.41755 | 4.61240 | 4.61240 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14121.36146 | 14121.36146 | 1.06429 | 1.06429 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 34.11500 | 1.44727E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 21257.23883 | 21257.23883 | 0.94033 | 0.94033 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 13341.08105 | 13341.08105 | 1.00548 | 1.00548 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.26500 | 1.44675E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 13888.28767 | 13888.28767 | 0.61437 | 0.61437 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 15916.50222 | 15916.50222 | 1.19958 | 1.19958 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 21039.16912 | 21039.16912 | 0.93066 | 0.93066 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 14946.50153 | 14946.50153 | 1.12647 | 1.12647 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 13655.49406 | 13655.49406 | 0.60406 | 0.60406 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8223.53460 | 8223.53460 | 0.48874 | 0.48874 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 24.96333 | 1.44561E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | -6.30000 | 2.29779E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 78191.32816 | 78191.32816 | 4.64701 | 4.64701 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 24.96333 | 1.44561E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -6.30000 | 2.29779E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7906.68061 | 7906.68061 | 0.46996 | 0.46996 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -6.30000 | 2.29779E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371765.91078 | 371765.91078 | 22.09665 | 22.09665 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 25.75500 | 1.44575E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | -6.30000 | 2.29779E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 151251.17 | 9.70708 | 9.70708 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 55990.24 | 2.51276 | 2.51276 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1390568.76 | 90.42532 | 90.42532 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 564677.14 | 36.13248 | 36.13248 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 156248.21 | 9.65551 | 9.65551 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 56437.02 | 5.79267 | 5.79267 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 |
7 | CAV_BAS | Cooling | Sensible | 81661.53 | 5.84563 | 5.84563 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 64825.70 | 1.20016 | 1.20016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 368437.54 | 22.09688 | 22.09688 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 18278.08 | 0.33839 | 0.33839 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8090.26 | 0.48874 | 0.48874 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 844.37 | 1.56323E-002 | 1.56323E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 77007.88 | 4.64701 | 4.64701 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8443.71 | 0.15632 | 0.15632 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7851.83 | 0.46996 | 0.46996 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 844.37 | 1.56323E-002 | 1.56323E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.84563 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.15075 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30924 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31500 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93749 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82463 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.23206E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.64545E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.93749 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18808.46857 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.64545E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 379.16396 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 58.05404 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32763 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32700 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.98367 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87369 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16289E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.06435E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.98367 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 464580.38504 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.06435E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11044.24280 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.73574 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33161 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33700 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93294 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88430 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14893E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.66100E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.70325 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 87569.97557 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.66100E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2311.76452 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99226 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24068 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29768 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64182 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58300E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21557E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42947 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13894.74067 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21557E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 366.59553 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95596 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16100 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28679 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42932 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36652E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.36744E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29567 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9564.50200 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.36744E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 252.33184 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13704 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21004 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34111 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56011 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81393E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.37105E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.48449 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15671.90154 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37105E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 413.44606 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23159 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12496 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36948 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33324 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04887E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.60244E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36948 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8690.05454 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.60244E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 204.17281 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.31020 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25651 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.79306 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68404 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.48529E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.05841E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.28144 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 235288.57361 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.05841E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6204.29450 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.80282 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15700 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.94085 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41867 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42674E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35048E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.77739 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 154368.28094 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35048E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4070.44775 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.73462 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22248 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.22038 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59329 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71250E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.03529E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.19951 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 232645.67414 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.03529E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6134.65769 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.36800 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14844 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.11040 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39585 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56665E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.30391E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.61240 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 149044.55852 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30391E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3930.15904 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06429 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22440 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31929 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59839 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.69790E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.65715E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.94033 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30372.89293 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.65715E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 800.74996 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00548 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15307 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30164 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40818 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.48911E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.73603E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.61437 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19843.92747 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73603E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 523.15857 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19958 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19909 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.35987 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53091 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.91369E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.62987E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.93066 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30061.01215 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.62987E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 792.53230 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12647 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13663 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33794 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36434 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.78863E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.70691E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.60406 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19511.03770 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70691E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 514.38551 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48874 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.64701 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46996 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 22.09665 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.23380 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.23254 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.46760 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.23254 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.70708 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.70708 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33301 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 49.13484 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 31.04836 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 98.26968 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 36.13248 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 90.42532 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 90.42532 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.39958 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.06577 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.25169 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.13154 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.79267 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.65551 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.65551 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.59993 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.84563 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.84563 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.84563 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.84563 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.84563 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.84563 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 22.09665 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.09665 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.09665 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 22.09665 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.09688 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 22.09688 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48874 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48874 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48874 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48874 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48874 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.48874 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.64701 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.64701 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.64701 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.64701 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.64701 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.64701 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46996 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46996 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46996 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46996 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46996 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.46996 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.70708 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 90.42532 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.65551 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.84563 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 22.09688 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.48874 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.64701 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.46996 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.70708 |
289 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
290 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.86207 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.98272 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.04314E-002 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 238172.21058 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.01324E-002 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.70708 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 56929.08838 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.98040E-004 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 933.49856 |
302 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.70708 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.01324E-002 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.69968E-005 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.98040E-004 |
306 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 90.42532 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 25.38195 |
308 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.18436 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.88033 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.06792E-002 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2330680.07421 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.91525E-002 |
316 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 90.42532 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 552647.73889 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.83480E-003 |
319 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 9026.32914 |
320 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 90.42532 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.91525E-002 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.80261E-006 |
323 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.83480E-003 |
324 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.65551 |
325 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
326 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.74767 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.98267 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.04165E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 235167.98005 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.00046E-002 |
334 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.65551 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 53128.59326 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.64792E-004 |
337 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 876.28614 |
338 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.65551 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.00046E-002 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.75972E-005 |
341 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.64792E-004 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.84563 |
343 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.83494 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.37342 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.02027E-002 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 129625.69596 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.51458E-003 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.84563 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 281605.14914 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.46360E-003 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6249.43800 |
355 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.84563 |
356 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.51458E-003 |
357 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.63512E-005 |
358 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.46360E-003 |
359 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.09688 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 22.09688 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 437646.58193 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 303283.70780 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.07179E-002 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 22.09688 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 22.09688 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 22.09688 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 22.09688 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 437646.58193 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 437646.58193 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 18278.07505 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
373 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 22.09688 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 22.09688 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 437646.58193 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.07179E-002 |
377 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 18278.07505 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.53127E-004 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
381 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
382 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48874 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48874 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9630.21888 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6683.15852 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35843E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48874 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48874 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48874 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48874 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9630.21888 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9630.21888 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 844.37135 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48874 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48874 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9630.21888 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35843E-004 |
400 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 844.37135 |
401 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.64701 |
402 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.64701 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 91737.04096 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 63598.28180 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.24663E-003 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.64701 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.64701 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.64701 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.64701 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 91737.04096 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 91737.04096 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8443.71345 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
415 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.64701 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.64701 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 91737.04096 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.24663E-003 |
419 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8443.71345 |
420 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46996 |
421 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46996 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9272.38281 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6430.23126 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.27080E-004 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46996 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46996 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46996 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46996 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9272.38281 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9272.38281 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 844.37135 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
434 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46996 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46996 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9272.38281 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.27080E-004 |
438 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 844.37135 |
439 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.12480 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 25717.49539 |
441 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.12480 |
442 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 14.97649 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.12480 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.12480 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 523865.35014 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
447 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.12957E-002 |
448 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.55548 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.12957E-002 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 6413.32236 |
451 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2434226.55506 |
453 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2434226.56000 |
454 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.12957E-002 |
455 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.12480 |
456 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 14.97649 |
457 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.12480 |
458 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 17805.08957 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12480 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.27350E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1478271.96164 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1485342.51500 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.35041E-002 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12480 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.27350E-002 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1478271.96164 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1485342.51500 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.35041E-002 |
469 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.34275E-002 |
470 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.61130 |
471 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.34275E-002 |
472 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3424.68253 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.34275E-002 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 58751.95628 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21362.97914 |
479 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 553097.65271 |
480 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 542182.77000 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.34275E-002 |
482 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
483 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
484 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
486 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14701 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.64098 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14701 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 44275.66798 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 58.92701 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1762320.85944 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.78540 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 220290.10743 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 58.92701 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1762320.85944 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.78540 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 220290.10743 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.63475E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.63475E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17834.59 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 440151.45 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 82987.54 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13166.22 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9062.92 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 14849.95 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8233.51 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 222928.56 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 146258.65 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 220424.85 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 141215.20 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 28776.36 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 18800.80 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 28480.91 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 18485.43 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 43485.11 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 418709.39 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 41073.87 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 222338.86 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 258538.62 | 172079.06 | 86459.56 | 0.67 | 27464.34 | 278.56 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2461534.97 | 1627653.39 | 833881.58 | 0.66 | 263452.38 | 2672.08 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 256499.98 | 170866.23 | 85633.75 | 0.67 | 27254.69 | 276.43 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 148012.76 | 100023.06 | 47989.70 | 0.68 | 15428.15 | 156.48 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2476158841 | 0.2246361978 | Pass | Pass | 0.9996910148 | 2.3362964398 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 1.8907695253E-003 | 1.8975309608E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.4517077310E-003 | 2.5332331099E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.7421685817E-002 | 3.6212529428E-002 | Pass | Pass | 0.1110396668 | 0.3121997257 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.2104420815E-002 | 2.3121226802E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.2337211346E-002 | 2.3532330931E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.2110814238E-002 | 2.2482894990E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.2450234346E-002 | 2.3191308731E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.7466980893E-002 | 2.7648782144E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.8181422856E-002 | 2.8292352948E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.8572353946E-002 | 2.9109777498E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.8774464231E-002 | 2.8905650819E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.4589934703E-002 | 0.1249518912 | Pass | Pass | 3.0033600093 | 16.2335056278 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.3670046008E-002 | 0.1214861940 | Pass | Pass | 2.5209282543 | 13.6582599400 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.5991386160E-002 | 0.1015442306 | Pass | Pass | 2.3854081433 | 12.7332289348 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.6047352817E-002 | 3.9347962092E-002 | Pass | Pass | 4.2808966907 | 26.9828103503 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.7248577132E-003 | 4.0701018397E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.1325833253E-003 | 6.3854251476E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.7348637098E-002 | 4.6035129239E-002 | Pass | Pass | 0.1112134531 | 0.3072055742 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.2541744812E-006 | 7.2063473840E-006 | Pass | Pass | 1.8977196386E-003 | 1.3434863801E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.3356434474E-004 | 2.2725670083E-003 | Pass | Pass | 1.0451178780E-002 | 8.7707779352E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.4979224501E-002 | 1.0646683131E-002 | Pass | Pass | 2.3873808932E-003 | 3.0560659530E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.2246526621E-006 | 9.9272645880E-006 | Pass | Pass | 3.4408218018E-005 | 1.0830441649E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5637.03 | 110.21 | 0.00 | 12119.85 | 25718.57 | 43585.63 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.4644_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.4644_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.4644_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.4644_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.4644_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.4644_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.640 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4644_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.640 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.640 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4644_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.640 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.640 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4644_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.640 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.640 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4644_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.640 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.640 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 1043.06 | 2.640 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.640 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.3279 | 2779.43 | 25926.33 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 240.45 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.3279 | 24961.20 | 232836.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 2159.39 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.36 | 0.0000 | Y | 18.86 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.09 | 0.0000 | Y | 12.06 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.88 | 0.0000 | Y | 18.59 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.25 | 0.0000 | Y | 12.11 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.3279 | 3134.13 | 29234.97 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.41 | 0.0000 | Y | 188.81 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.11 | 0.0000 | Y | 120.63 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.3279 | 3134.20 | 29235.61 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.91 | 0.0000 | Y | 186.12 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.26 | 0.0000 | Y | 121.17 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.41 | 0.0000 | Y | 18.88 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.11 | 0.0000 | Y | 12.06 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.92 | 0.0000 | Y | 18.61 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.26 | 0.0000 | Y | 12.12 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 9.3279 | 783.68 | 7310.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 67.80 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 16.0861 | 362.03 | 5823.61 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 59.65 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
Interior Lighting Total | 9.3913 | 46320.38 | 435009.77 | 1158.93 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.01 | AstronomicalClock | - | 41.77 | 41.77 | 78.20 | |
EXTERIOR_LIGHTS_B | 44362.79 | AstronomicalClock | - | 83.77 | 71.17 | 592.67 | |
Exterior Lighting Total | 54335.80 | 670.87 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2926899.44 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2434226.56 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1485342.51 | 6.28 | 1421657.46 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1485342.51 | 6.28 | 1421657.46 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 542182.77 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1762320.86 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1762320.86 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 238172.21 | 258538.62 | 172079.06 | 86459.56 | 0.67 | - | 27464.34 | 278.56 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2330680.07 | 2461534.97 | 1627653.39 | 833881.58 | 0.66 | - | 263452.38 | 2672.08 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 235167.98 | 256499.98 | 170866.23 | 85633.75 | 0.67 | - | 27254.69 | 276.43 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 129625.70 | 148012.76 | 100023.06 | 47989.70 | 0.68 | - | 15428.15 | 156.48 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 437646.58 | 303283.71 | 134362.87 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9630.22 | 6683.16 | 2947.06 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 91737.04 | 63598.28 | 28138.76 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9272.38 | 6430.23 | 2842.15 | 0.69 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18808.47 | 17834.59 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 464580.39 | 440151.45 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 87569.98 | 82987.54 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13894.74 | 13166.22 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 9564.50 | 9062.92 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15671.90 | 14849.95 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 8690.05 | 8233.51 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 235288.57 | 222928.56 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 154368.28 | 146258.65 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 232645.67 | 220424.85 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 149044.56 | 141215.20 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 30372.89 | 28776.36 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 19843.93 | 18800.80 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 30061.01 | 28480.91 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 19511.04 | 18485.43 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 56929.09 | 43485.11 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 552647.74 | 418709.39 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 53128.59 | 41073.87 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 281605.15 | 222338.86 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 437646.58 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9630.22 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 91737.04 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9272.38 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 18278.08 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 844.37 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8443.71 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 844.37 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.71 | 20976.49 | 2160.95 | 1.00 | 1.12 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 90.43 | 206506.83 | 2283.73 | 1.00 | 1.07 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.66 | 20865.04 | 2160.95 | 1.00 | 1.12 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.85 | 9912.16 | 1695.65 | 1.00 | 1.16 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 22.10 | 36443.22 | 1649.25 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 547.44 | 1120.11 | 1.00 | 1.62 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.65 | 5205.15 | 1120.11 | 1.00 | 1.16 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 526.41 | 1120.11 | 1.00 | 1.63 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.124804 | 25717.50 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.021296 | 6413.32 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.124804 | 17805.09 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013427 | 3424.68 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.147008 | 44275.67 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 78267.84 | 78267.84 | 28.16 | 5.846 | 5.846 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 27.37 | 0.01446 | 1.200 | 0.00 |
CORE_BOTTOM | 82357.66 | 82357.66 | 32.99 | 6.151 | 6.151 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 27.37 | 0.01446 | 1.078 | 0.00 |
CORE_MID | 777519.50 | 777519.50 | 311.49 | 58.054 | 58.054 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 27.37 | 0.01446 | 10.778 | 0.00 |
CORE_TOP | 76821.35 | 76821.35 | 30.78 | 5.736 | 5.736 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 27.37 | 0.01446 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13166.73 | 13166.73 | 42.01 | 0.992 | 0.992 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00891 | 34.40 | 0.01447 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12685.04 | 12685.04 | 62.80 | 0.956 | 0.956 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00878 | 30.52 | 0.01447 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15087.88 | 15087.88 | 48.14 | 1.137 | 1.137 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00886 | 34.32 | 0.01447 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 16342.64 | 16342.64 | 80.91 | 1.232 | 1.232 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00872 | 32.91 | 0.01447 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 123533.86 | 123533.86 | 394.16 | 9.310 | 9.310 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00911 | 34.40 | 0.01447 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 130070.93 | 130070.93 | 643.99 | 9.803 | 9.803 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00889 | 30.79 | 0.01447 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 142434.17 | 142434.17 | 454.45 | 10.735 | 10.735 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00903 | 34.40 | 0.01447 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 137570.30 | 137570.30 | 681.12 | 10.368 | 10.368 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00887 | 32.75 | 0.01447 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14121.36 | 14121.36 | 45.06 | 1.064 | 1.064 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00910 | 34.12 | 0.01447 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13341.08 | 13341.08 | 66.05 | 1.005 | 1.005 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 24.00 | 24.00 | 0.00892 | 31.26 | 0.01447 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15916.50 | 15916.50 | 50.78 | 1.200 | 1.200 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00903 | 34.40 | 0.01447 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 14946.50 | 14946.50 | 74.00 | 1.126 | 1.126 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00888 | 32.75 | 0.01447 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8223.53 | 8223.53 | 227.15 | 0.489 | 0.489 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 24.96 | 0.01446 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78191.33 | 78191.33 | 2159.82 | 4.647 | 4.647 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 24.96 | 0.01446 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7906.68 | 7906.68 | 218.40 | 0.470 | 0.470 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.00 | 27.00 | 0.00859 | 30.70 | 0.01447 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371765.91 | 371765.91 | 474.39 | 22.097 | 22.097 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 25.75 | 0.01446 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | 21.00 | 23.45 | 0.00230 | -6.30 | 0.00230 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 17.60 | 21.02 | 0.00230 | -6.30 | 0.00230 | 1.078 | 0.00 |
CORE_MID | 280293.33 | 280293.33 | 112.29 | 12.262 | 12.262 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 10.778 | 0.00 |
CORE_TOP | 61327.71 | 61327.71 | 24.57 | 2.703 | 2.703 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 9731.54 | 9731.54 | 31.05 | 0.429 | 0.429 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00736 | -6.30 | 0.00230 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 6698.01 | 6698.01 | 33.16 | 0.296 | 0.296 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00742 | -6.30 | 0.00230 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 10973.99 | 10973.99 | 35.01 | 0.484 | 0.484 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -6.30 | 0.00230 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 5110.99 | 5110.99 | 25.31 | 0.225 | 0.225 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00701 | -6.30 | 0.00230 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 164701.70 | 164701.70 | 525.51 | 7.281 | 7.281 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00741 | -6.30 | 0.00230 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 108056.77 | 108056.77 | 535.00 | 4.777 | 4.777 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00740 | -6.30 | 0.00230 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 162853.91 | 162853.91 | 519.60 | 7.200 | 7.200 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00741 | -6.30 | 0.00230 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 104334.42 | 104334.42 | 516.57 | 4.612 | 4.612 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00738 | -6.30 | 0.00230 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 21257.24 | 21257.24 | 67.83 | 0.940 | 0.940 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -6.30 | 0.00230 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13888.29 | 13888.29 | 68.76 | 0.614 | 0.614 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00743 | -6.30 | 0.00230 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21039.17 | 21039.17 | 67.13 | 0.931 | 0.931 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -6.30 | 0.00230 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 13655.49 | 13655.49 | 67.61 | 0.604 | 0.604 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00742 | -6.30 | 0.00230 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | 18.00 | 25.42 | 0.00797 | -6.30 | 0.00230 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.89 | 0.00296 | -6.30 | 0.00230 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 21.00 | 0.00276 | -6.30 | 0.00230 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | 18.00 | 27.00 | 0.00850 | -6.30 | 0.00230 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.71 | 9.71 | 2.51 | 2.51 | 9.7071 | 3.2325 | 9.7071 | 0.3330 | 0.3000 |
VAV_MID WITH REHEAT | 90.43 | 90.43 | 36.13 | 36.13 | 90.4253 | 36.1325 | 90.4253 | 0.3996 | 0.3000 |
VAV_TOP WITH REHEAT | 9.66 | 9.66 | 5.79 | 5.79 | 9.6555 | 5.7927 | 9.6555 | 0.5999 | 0.3000 |
CAV_BAS | 5.85 | 5.85 | 1.20 | 1.20 | 5.8456 | 5.8456 | 5.8456 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.10 | 22.10 | 0.34 | 0.34 | 22.0969 | 22.0966 | 22.0969 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.49 | 0.49 | 0.02 | 0.02 | 0.4887 | 0.4887 | 0.4887 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.65 | 4.65 | 0.16 | 0.16 | 4.6470 | 4.6470 | 4.6470 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.47 | 0.47 | 0.02 | 0.02 | 0.4700 | 0.4700 | 0.4700 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18808.469 | 18808.469 | 1.937487 | 0.00016454 | 379.164 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 18808.47 | 18808.47 | 1.937487 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 0.00 | 0.00 | 18877.82 | 18877.82 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 464580.385 | 464580.385 | 18.983670 | 0.00406435 | 11044.243 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 464580.39 | 464580.39 | 18.983670 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 280293.33 | 0.00 | 466094.00 | 466094.00 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 87569.976 | 87569.976 | 2.703253 | 0.00076610 | 2311.765 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 87569.98 | 87569.98 | 2.703253 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 61327.71 | 0.00 | 87873.91 | 87873.91 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 13894.741 | 13894.741 | 0.429468 | 0.00012156 | 366.596 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13894.74 | 13894.74 | 0.429468 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00736137 | 45.9345 | 9731.54 | 0.00 | 13941.44 | 13941.44 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9564.502 | 9564.502 | 0.295666 | 0.00008367 | 252.332 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9564.50 | 9564.50 | 0.295666 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00741999 | 46.2957 | 6698.01 | 0.00 | 9596.53 | 9596.53 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 15671.902 | 15671.902 | 0.484494 | 0.00013710 | 413.446 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15671.90 | 15671.90 | 0.484494 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00749196 | 46.7388 | 10973.99 | 0.00 | 15724.30 | 15724.30 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8690.055 | 8690.055 | 0.369477 | 0.00007602 | 204.173 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8690.05 | 8690.05 | 0.369477 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00700546 | 43.7400 | 5110.99 | 0.00 | 8718.54 | 8718.54 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 235288.574 | 235288.574 | 7.281439 | 0.00205841 | 6204.295 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 235288.57 | 235288.57 | 7.281439 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00741190 | 46.2477 | 164701.70 | 0.00 | 236054.14 | 236054.14 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 154368.281 | 154368.281 | 4.777390 | 0.00135048 | 4070.448 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 154368.28 | 154368.28 | 4.777390 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00740474 | 46.2037 | 108056.77 | 0.00 | 154870.05 | 154870.05 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 232645.674 | 232645.674 | 7.199512 | 0.00203529 | 6134.658 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 232645.67 | 232645.67 | 7.199512 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00740515 | 46.2061 | 162853.91 | 0.00 | 233403.03 | 233403.03 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 149044.559 | 149044.559 | 4.612402 | 0.00130391 | 3930.159 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 149044.56 | 149044.56 | 4.612402 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00738309 | 46.0703 | 104334.42 | 0.00 | 149529.67 | 149529.67 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 30372.893 | 30372.893 | 0.940328 | 0.00026572 | 800.750 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30372.89 | 30372.89 | 0.940328 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00744127 | 46.4300 | 21257.24 | 0.00 | 30470.64 | 30470.64 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 19843.927 | 19843.927 | 0.614373 | 0.00017360 | 523.159 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19843.93 | 19843.93 | 0.614373 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00743113 | 46.3676 | 13888.29 | 0.00 | 19907.75 | 19907.75 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 30061.012 | 30061.012 | 0.930660 | 0.00026299 | 792.532 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30061.01 | 30061.01 | 0.930660 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00743593 | 46.3970 | 21039.17 | 0.00 | 30157.79 | 30157.79 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 19511.038 | 19511.038 | 0.604058 | 0.00017069 | 514.386 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19511.04 | 19511.04 | 0.604058 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00742233 | 46.3134 | 13655.49 | 0.00 | 19573.81 | 19573.81 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 238172.211 | -999.000 | 9.707084 | 0.01013240 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 238172.21 | 182474.99 | 9.707084 | 26.86 | 18.54 | 0.01043139 | 10.98 | 10.98 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 26.1478 | 24.00 | 0.00889598 | 46.1452 | 122343.38 | 0.00 | 243868.37 | 177970.22 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 56929.088 | 56929.088 | 2.912125 | 0.00049804 | 933.499 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 56929.09 | 56929.09 | 2.912125 | -3.96 | -4.19 | 0.00266912 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 87.1594 | 21.02 | 0.00578879 | 36.1577 | 32514.54 | 0.00 | 52604.58 | 52604.58 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2330680.074 | -999.000 | 90.425325 | 0.09915252 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2330680.07 | 1742433.47 | 90.425325 | 27.18 | 18.83 | 0.01067923 | 10.88 | 10.88 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 28.0695 | 24.00 | 0.00900397 | 46.6982 | 1099566.21 | 0.00 | 2385079.72 | 1701728.33 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 552647.739 | 552647.739 | 27.127597 | 0.00483480 | 9026.329 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 552647.74 | 552647.74 | 27.127597 | -4.66 | -4.69 | 0.00262862 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 93.5650 | 19.62 | 0.00715767 | 48.6357 | 428469.23 | 0.00 | 506498.46 | 506498.46 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 235167.980 | -999.000 | 9.655506 | 0.01000459 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 235167.98 | 180197.09 | 9.655506 | 26.75 | 18.49 | 0.01041650 | 10.98 | 10.98 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 26.2875 | 24.00 | 0.00895892 | 46.4680 | 127417.81 | 0.00 | 240817.44 | 175700.63 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 53128.593 | 53128.593 | 2.896652 | 0.00046479 | 876.286 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 53128.59 | 53128.59 | 2.896652 | -2.92 | -3.15 | 0.00292893 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 87.6250 | 18.28 | 0.00735331 | 54.3330 | 53426.68 | 0.00 | 49692.76 | 49692.76 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 129625.696 | -999.000 | 5.845627 | 0.00551458 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 129625.70 | 100675.05 | 5.845627 | 25.83 | 18.03 | 0.01020270 | 11.37 | 11.18 | 0.00850000 | 32.21 | 0.01446927 | 22.96 | 20.5308 | 24.00 | 0.00897472 | 46.5476 | 77210.39 | 0.00 | 132916.33 | 98424.67 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 281605.149 | 281605.149 | 5.845627 | 0.00246360 | 6249.438 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 281605.15 | 281605.15 | 5.845627 | -1.29 | -3.23 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 20.5308 | 23.55 | 0.00229779 | 12.3755 | 0.00 | 0.00 | 234864.54 | 234864.54 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 437646.582 | 303283.708 | 22.096884 | 0.01071794 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 405671.70 | 398091.82 | -999.0 | 28.56 | 17.68 | 0.00863322 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | -999.0000 | 27.00 | 0.00854228 | 37.1024 | 371256.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9630.219 | 6683.159 | 0.488735 | 0.00023584 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 8918.20 | 8568.11 | -999.0 | 28.10 | 17.64 | 0.00877851 | 12.80 | 11.77 | 0.00850000 | 30.70 | 0.01446650 | 22.54 | -999.0000 | 27.00 | 0.00858881 | 37.2995 | 8148.86 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91737.041 | 63598.282 | 4.647012 | 0.00224663 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 84980.57 | 81483.57 | -999.0 | 28.10 | 17.65 | 0.00879254 | 12.80 | 11.77 | 0.00850000 | 30.52 | 0.01446618 | 22.49 | -999.0000 | 27.00 | 0.00859341 | 37.3194 | 77564.88 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9272.383 | 6430.231 | 0.469960 | 0.00022708 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8588.71 | 8241.76 | -999.0 | 28.10 | 17.65 | 0.00878701 | 12.80 | 11.77 | 0.00850000 | 30.70 | 0.01446650 | 22.54 | -999.0000 | 27.00 | 0.00859159 | 37.3115 | 7906.68 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 437646.582 | 437646.582 | 22.096884 | 0.01071794 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 437646.58 | 437646.58 | 22.096884 | -6.30 | -6.30 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 1.5314 | 27.00 | 0.00850000 | 36.9155 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9630.219 | 9630.219 | 0.488735 | 0.00023584 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9630.22 | 9630.22 | 0.488735 | -6.30 | -6.30 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.1985 | 25.97 | 0.00796565 | 36.7905 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91737.041 | 91737.041 | 4.647012 | 0.00224663 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 91737.04 | 91737.04 | 4.647012 | -6.30 | -6.30 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.3640 | 24.04 | 0.00295589 | 15.4409 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9272.383 | 9272.383 | 0.469960 | 0.00022708 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9272.38 | 9272.38 | 0.469960 | -6.30 | -6.30 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.3263 | 22.90 | 0.00276448 | 15.4755 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 18278.075 | 18278.075 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 18278.08 | 18278.08 | 22.096884 | -0.10 | -0.10 | 0.00840502 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 1.5314 | 27.00 | 0.00850000 | 36.9155 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 844.371 | 844.371 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 844.37 | 844.37 | 0.488735 | -0.20 | -0.20 | 0.00778436 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.1985 | 25.97 | 0.00796565 | 36.7905 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8443.713 | 8443.713 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8443.71 | 8443.71 | 4.647012 | -0.21 | -1.60 | 0.00293375 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.3640 | 24.04 | 0.00295589 | 15.4409 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 844.371 | 844.371 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 844.37 | 844.37 | 0.469960 | -0.21 | -1.88 | 0.00274895 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.3263 | 22.90 | 0.00276448 | 15.4755 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18808.469 | 18808.469 | 1.937487 | 0.00016454 | 379.164 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 0.7574 | 0.772667 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 18808.47 | 18808.47 | 1.0000 | 2.24937686 | 1.937487 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.16452790 | 60.00 | 32.22 | 27.78 | 0.000 | 18808.47 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 0.00 | 0.00 | 18877.82 | 18877.82 | 2.24937686 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 464580.385 | 464580.385 | 18.983670 | 0.00406435 | 11044.243 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 18.7088 | 19.085339 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 464580.39 | 464580.39 | 1.0000 | 22.03959590 | 18.983670 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 4.06393727 | 60.00 | 32.22 | 27.78 | 0.000 | 464580.39 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 280293.33 | 0.00 | 466094.00 | 466094.00 | 22.03959590 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.54 | 19.19 | 0.00800000 | 54207.9 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 87569.976 | 87569.976 | 2.703253 | 0.00076610 | 2311.765 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 3.5265 | 3.597446 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 87569.98 | 87569.98 | 1.0000 | 3.13841342 | 2.703253 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.76602220 | 60.00 | 32.22 | 27.78 | 0.000 | 87569.98 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 61327.71 | 0.00 | 87873.91 | 87873.91 | 3.13841342 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.26 | 21.26 | 0.00800000 | 61059.3 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13894.741 | 13894.741 | 0.429468 | 0.00012156 | 366.596 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 0.5595 | 0.570807 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13894.74 | 13894.74 | 1.0000 | 0.49860241 | 0.429468 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.12154485 | 60.00 | 32.22 | 27.78 | 0.000 | 13894.74 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00736137 | 21.00 | 0.00736137 | 45.9345 | 9731.54 | 0.00 | 13941.44 | 13941.44 | 0.49860241 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61020.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9564.502 | 9564.502 | 0.295666 | 0.00008367 | 252.332 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 0.3852 | 0.392917 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9564.50 | 9564.50 | 1.0000 | 0.34326168 | 0.295666 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.08366590 | 60.00 | 32.22 | 27.78 | 0.000 | 9564.50 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00741999 | 21.00 | 0.00741999 | 46.2957 | 6698.01 | 0.00 | 9596.53 | 9596.53 | 0.34326168 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61016.7 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15671.902 | 15671.902 | 0.484494 | 0.00013710 | 413.446 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 0.6311 | 0.643814 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15671.90 | 15671.90 | 1.0000 | 0.56248638 | 0.484494 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.13709065 | 60.00 | 32.22 | 27.78 | 0.000 | 15671.90 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00749196 | 21.00 | 0.00749196 | 46.7388 | 10973.99 | 0.00 | 15724.30 | 15724.30 | 0.56248638 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61014.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8690.055 | 8690.055 | 0.369477 | 0.00007602 | 204.173 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 0.3500 | 0.356994 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8690.05 | 8690.05 | 1.0000 | 0.42895442 | 0.369477 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07601663 | 60.00 | 32.22 | 27.78 | 0.000 | 8690.05 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00700546 | 21.00 | 0.00700546 | 43.7400 | 5110.99 | 0.00 | 8718.54 | 8718.54 | 0.42895442 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.73 | 18.93 | 0.00800000 | 53384.9 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 235288.574 | 235288.574 | 7.281439 | 0.00205841 | 6204.295 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 9.4752 | 9.665845 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 235288.57 | 235288.57 | 1.0000 | 8.45357959 | 7.281439 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 2.05819711 | 60.00 | 32.22 | 27.78 | 0.000 | 235288.57 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00741190 | 21.00 | 0.00741190 | 46.2477 | 164701.70 | 0.00 | 236054.14 | 236054.14 | 8.45357959 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.4 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 154368.281 | 154368.281 | 4.777390 | 0.00135048 | 4070.448 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 6.2165 | 6.341574 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 154368.28 | 154368.28 | 1.0000 | 5.54643824 | 4.777390 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 1.35034330 | 60.00 | 32.22 | 27.78 | 0.000 | 154368.28 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00740474 | 21.00 | 0.00740474 | 46.2037 | 108056.77 | 0.00 | 154870.05 | 154870.05 | 5.54643824 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 232645.674 | 232645.674 | 7.199512 | 0.00203529 | 6134.658 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 9.3687 | 9.557273 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 232645.67 | 232645.67 | 1.0000 | 8.35846461 | 7.199512 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 2.03507823 | 60.00 | 32.22 | 27.78 | 0.000 | 232645.67 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00740515 | 21.00 | 0.00740515 | 46.2061 | 162853.91 | 0.00 | 233403.03 | 233403.03 | 8.35846461 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60984.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 149044.559 | 149044.559 | 4.612402 | 0.00130391 | 3930.159 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 6.0021 | 6.122871 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 149044.56 | 149044.56 | 1.0000 | 5.35489070 | 4.612402 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 1.30377380 | 60.00 | 32.22 | 27.78 | 0.000 | 149044.56 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00738309 | 21.00 | 0.00738309 | 46.0703 | 104334.42 | 0.00 | 149529.67 | 149529.67 | 5.35489070 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30372.893 | 30372.893 | 0.940328 | 0.00026572 | 800.750 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 1.2231 | 1.247743 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30372.89 | 30372.89 | 1.0000 | 1.09169879 | 0.940328 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.26568821 | 60.00 | 32.22 | 27.78 | 0.000 | 30372.89 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00744127 | 21.00 | 0.00744127 | 46.4300 | 21257.24 | 0.00 | 30470.64 | 30470.64 | 1.09169879 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19843.927 | 19843.927 | 0.614373 | 0.00017360 | 523.159 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 0.7991 | 0.815205 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19843.93 | 19843.93 | 1.0000 | 0.71327230 | 0.614373 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.17358562 | 60.00 | 32.22 | 27.78 | 0.000 | 19843.93 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00743113 | 21.00 | 0.00743113 | 46.3676 | 13888.29 | 0.00 | 19907.75 | 19907.75 | 0.71327230 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60970.3 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30061.012 | 30061.012 | 0.930660 | 0.00026299 | 792.532 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 1.2106 | 1.234931 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30061.01 | 30061.01 | 1.0000 | 1.08047461 | 0.930660 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.26296002 | 60.00 | 32.22 | 27.78 | 0.000 | 30061.01 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00743593 | 21.00 | 0.00743593 | 46.3970 | 21039.17 | 0.00 | 30157.79 | 30157.79 | 1.08047461 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.4 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19511.038 | 19511.038 | 0.604058 | 0.00017069 | 514.386 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 0.7857 | 0.801529 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19511.04 | 19511.04 | 1.0000 | 0.70129752 | 0.604058 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.17067366 | 60.00 | 32.22 | 27.78 | 0.000 | 19511.04 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00742233 | 21.00 | 0.00742233 | 46.3134 | 13655.49 | 0.00 | 19573.81 | 19573.81 | 0.70129752 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60970.7 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 238172.211 | -999.000 | 9.707084 | 0.01013240 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2314 | 1004.8586 | 1.1610 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.707084 | 11.26969693 | 4197.9300 | 999.8980 | 124.79134958 | 12.27 | 6.67 | 5.60 | 2933645.96 | 8.1186 | 8.118642 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 238172.21 | 182474.99 | 1.0000 | 11.26969693 | 9.707084 | 26.86 | 18.54 | 0.01043139 | 53601.3 | 10.98 | 10.98 | 0.00850000 | 32467.4 | 10.13136281 | 6.67 | 12.27 | 5.60 | 20976.492 | 217195.72 | 34.40 | 0.01447326 | 23.54 | 2.53819000 | 26.1478 | 24.00 | 0.00889598 | 24.00 | 0.00889598 | 46.1452 | 122343.38 | 0.00 | 243868.37 | 177970.22 | 11.26969693 | 26.86 | 18.94 | 0.01043139 | 53601.3 | 11.44 | 11.14 | 0.00811304 | 31962.0 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 56929.088 | 56929.088 | 2.912125 | 0.00049804 | 933.499 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.707084 | 11.26969693 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 2.2926 | 2.338693 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 56929.09 | 56929.09 | 1.0000 | 3.38090908 | 2.912125 | -3.96 | -4.19 | 0.00266912 | 2679.5 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 0.49798969 | 60.00 | 32.22 | 27.78 | 0.000 | 56929.09 | -6.30 | 0.00229779 | -6.30 | 2.53819000 | 87.1594 | 11.95 | 0.00518956 | 21.02 | 0.00578879 | 36.1577 | 32514.54 | 0.00 | 52604.58 | 52604.58 | 3.38090908 | 2.80 | 0.04 | 0.00266912 | 9502.7 | 18.21 | 8.20 | 0.00266912 | 25062.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2330680.074 | -999.000 | 90.425325 | 0.09915252 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6922 | 1004.8586 | 1.1610 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 90.425325 | 104.98168082 | 4197.9300 | 999.8980 | 124.79134958 | 12.27 | 6.67 | 5.60 | 2933645.96 | 79.4465 | 79.446535 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2330680.07 | 1742433.47 | 1.0000 | 104.98168082 | 90.425325 | 27.18 | 18.83 | 0.01067923 | 54563.7 | 10.88 | 10.88 | 0.00850000 | 32362.9 | 99.14240361 | 6.67 | 12.27 | 5.60 | 206506.829 | 2124173.25 | 34.40 | 0.01447326 | 23.54 | 25.38195000 | 28.0695 | 24.00 | 0.00900397 | 24.00 | 0.00900397 | 46.6982 | 1099566.21 | 0.00 | 2385079.72 | 1701728.33 | 104.98168082 | 27.18 | 19.24 | 0.01067923 | 54563.7 | 11.37 | 11.09 | 0.00809832 | 31844.7 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 552647.739 | 552647.739 | 27.127597 | 0.00483480 | 9026.329 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 90.425325 | 104.98168082 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 22.2553 | 22.703217 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 552647.74 | 552647.74 | 1.0000 | 31.49450424 | 27.127597 | -4.66 | -4.69 | 0.00262862 | 1866.1 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 4.83431031 | 60.00 | 32.22 | 27.78 | 0.000 | 552647.74 | -6.30 | 0.00229779 | -6.30 | 25.38195000 | 93.5650 | 19.15 | 0.00743893 | 19.62 | 0.00715767 | 48.6357 | 428469.23 | 0.00 | 506498.46 | 506498.46 | 31.49450424 | 2.80 | -0.22 | 0.00262862 | 9401.3 | 18.73 | 8.39 | 0.00262862 | 25483.4 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 235167.980 | -999.000 | 9.655506 | 0.01000459 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2038 | 1004.8586 | 1.1610 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.655506 | 11.20981647 | 4197.9300 | 999.8980 | 124.79134958 | 12.27 | 6.67 | 5.60 | 2933645.96 | 8.0162 | 8.016236 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 235167.98 | 180197.09 | 1.0000 | 11.20981647 | 9.655506 | 26.75 | 18.49 | 0.01041650 | 53446.1 | 10.98 | 10.98 | 0.00850000 | 32467.4 | 10.00356894 | 6.67 | 12.27 | 5.60 | 20865.035 | 214302.94 | 34.40 | 0.01447326 | 23.54 | 2.53819000 | 26.2875 | 24.00 | 0.00895892 | 24.00 | 0.00895892 | 46.4680 | 127417.81 | 0.00 | 240817.44 | 175700.63 | 11.20981647 | 26.75 | 18.89 | 0.01041650 | 53446.1 | 11.44 | 11.14 | 0.00811340 | 31963.4 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 53128.593 | 53128.593 | 2.896652 | 0.00046479 | 876.286 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.655506 | 11.20981647 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 2.1395 | 2.182566 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 53128.59 | 53128.59 | 1.0000 | 3.36294494 | 2.896652 | -2.92 | -3.15 | 0.00292893 | 4373.2 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 0.46474470 | 60.00 | 32.22 | 27.78 | 0.000 | 53128.59 | -6.30 | 0.00229779 | -6.30 | 2.53819000 | 87.6250 | 21.00 | 0.00739787 | 18.28 | 0.00735331 | 54.3330 | 53426.68 | 0.00 | 49692.76 | 49692.76 | 3.36294494 | 2.80 | 0.42 | 0.00292893 | 10153.9 | 17.43 | 8.13 | 0.00292893 | 24930.4 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 129625.696 | -999.000 | 5.845627 | 0.00551458 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8063 | 1004.8586 | 1.1610 | CAV_BAS FAN | Fan:ConstantVolume | 5.845627 | 6.78663585 | 4197.9300 | 999.8980 | 124.79134958 | 12.27 | 6.67 | 5.60 | 2933645.96 | 4.4186 | 4.418587 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 129625.70 | 100675.05 | 1.0000 | 6.78663585 | 5.845627 | 25.83 | 18.03 | 0.01020270 | 51966.3 | 11.37 | 11.18 | 0.00850000 | 32866.2 | 5.51401422 | 6.67 | 12.27 | 5.60 | 9912.163 | 119713.53 | 32.21 | 0.01446927 | 22.96 | 1.20015641 | 20.5308 | 24.00 | 0.00897472 | 24.00 | 0.00897472 | 46.5476 | 77210.39 | 0.00 | 132916.33 | 98424.67 | 6.78663585 | 25.83 | 18.42 | 0.01020270 | 51966.3 | 11.67 | 11.31 | 0.00818802 | 32381.3 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 281605.149 | 281605.149 | 5.845627 | 0.00246360 | 6249.438 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | CAV_BAS FAN | Fan:ConstantVolume | 5.845627 | 6.78663585 | 4197.9300 | 999.8980 | 21.29350343 | 54.44 | 82.22 | 27.78 | 2483216.33 | 11.3403 | 11.568568 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 281605.15 | 281605.15 | 1.0000 | 6.78663585 | 5.845627 | -1.29 | -3.23 | 0.00229779 | 4441.4 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 2.46335338 | 60.00 | 32.22 | 27.78 | 0.000 | 281605.15 | -6.30 | 0.00229779 | -6.30 | 1.20015641 | 20.5308 | 0.00 | 0.00229779 | 23.55 | 0.00229779 | 12.3755 | 0.00 | 0.00 | 234864.54 | 234864.54 | 6.78663585 | 12.80 | 5.08 | 0.00229779 | 18663.3 | 47.09 | 19.05 | 0.00229779 | 53270.2 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 437646.582 | 303283.708 | 22.096884 | 0.01071794 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8887 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 405671.70 | 398091.82 | 0.9269 | -999.0 | -999.0 | 28.56 | 17.68 | 0.00863322 | 50743.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 405671.70 | 34.40 | 0.01447326 | 23.54 | 0.33839277 | -999.0000 | 27.00 | 0.00854228 | 27.00 | 0.00854228 | 37.1024 | 371256.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9630.219 | 6683.159 | 0.488735 | 0.00023584 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1588 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | Sensible | 8918.20 | 8568.11 | 0.9261 | -999.0 | -999.0 | 28.10 | 17.64 | 0.00877851 | 50648.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8918.20 | 30.70 | 0.01446650 | 22.54 | 0.01563234 | -999.0000 | 27.00 | 0.00858881 | 27.00 | 0.00858881 | 37.2995 | 8148.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 91737.041 | 63598.282 | 4.647012 | 0.00224663 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1849 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | Sensible | 84980.57 | 81483.57 | 0.9263 | -999.0 | -999.0 | 28.10 | 17.65 | 0.00879254 | 50684.0 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84980.57 | 30.52 | 0.01446618 | 22.49 | 0.15632344 | -999.0000 | 27.00 | 0.00859341 | 27.00 | 0.00859341 | 37.3194 | 77564.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9272.383 | 6430.231 | 0.469960 | 0.00022708 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1746 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8588.71 | 8241.76 | 0.9263 | -999.0 | -999.0 | 28.10 | 17.65 | 0.00878701 | 50673.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8588.71 | 30.70 | 0.01446650 | 22.54 | 0.01563234 | -999.0000 | 27.00 | 0.00859159 | 27.00 | 0.00859159 | 37.3115 | 7906.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 437646.582 | 437646.582 | 22.096884 | 0.01071794 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 437646.58 | 437646.58 | 1.0000 | 25.65396409 | 22.096884 | -6.30 | -6.30 | 0.00229779 | -610.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 437646.58 | -6.30 | 0.00229779 | -6.30 | 0.33839277 | 1.5314 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.9155 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9630.219 | 9630.219 | 0.488735 | 0.00023584 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9630.22 | 9630.22 | 1.0000 | 0.56741020 | 0.488735 | -6.30 | -6.30 | 0.00229779 | -610.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9630.22 | -6.30 | 0.00229779 | -6.30 | 0.01563234 | 3.1985 | 0.00 | 0.00796565 | 25.97 | 0.00796565 | 36.7905 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 91737.041 | 91737.041 | 4.647012 | 0.00224663 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 91737.04 | 91737.04 | 1.0000 | 5.39507149 | 4.647012 | -6.30 | -6.30 | 0.00229779 | -610.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91737.04 | -6.30 | 0.00229779 | -6.30 | 0.15632344 | 3.3640 | 0.00 | 0.00295589 | 24.04 | 0.00295589 | 15.4409 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9272.383 | 9272.383 | 0.469960 | 0.00022708 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9272.38 | 9272.38 | 1.0000 | 0.54561246 | 0.469960 | -6.30 | -6.30 | 0.00229779 | -610.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9272.38 | -6.30 | 0.00229779 | -6.30 | 0.01563234 | 3.3263 | 0.00 | 0.00276448 | 22.90 | 0.00276448 | 15.4755 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18278.075 | 18278.075 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 22.096884 | 25.65396409 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 18278.08 | 18278.08 | 1.0000 | 25.65396409 | 22.096884 | -0.10 | -0.10 | 0.00840502 | 20922.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18278.08 | -6.30 | 0.00229779 | -6.30 | 0.33839277 | 1.5314 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.9155 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 844.371 | 844.371 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.488735 | 0.56741020 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 844.37 | 844.37 | 1.0000 | 0.56741020 | 0.488735 | -0.20 | -0.20 | 0.00778436 | 19262.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 844.37 | -6.30 | 0.00229779 | -6.30 | 0.01563234 | 3.1985 | 0.00 | 0.00796565 | 25.97 | 0.00796565 | 36.7905 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8443.713 | 8443.713 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.647012 | 5.39507149 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8443.71 | 8443.71 | 1.0000 | 5.39507149 | 4.647012 | -0.21 | -1.60 | 0.00293375 | 7123.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8443.71 | -6.30 | 0.00229779 | -6.30 | 0.15632344 | 3.3640 | 0.00 | 0.00295589 | 24.04 | 0.00295589 | 15.4409 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 844.371 | 844.371 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.469960 | 0.54561246 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 844.37 | 844.37 | 1.0000 | 0.54561246 | 0.469960 | -0.21 | -1.88 | 0.00274895 | 6663.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 844.37 | -6.30 | 0.00229779 | -6.30 | 0.01563234 | 3.3263 | 0.00 | 0.00276448 | 22.90 | 0.00276448 | 15.4755 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.54 | 9.71 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 25.38 | 90.43 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.54 | 9.66 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 5.85 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3686.17 | 1684.33 | 1162.33 |
CORE_BOTTOM | 3685.17 | 656.67 | 38.50 |
CORE_MID | 3120.67 | 1837.67 | 81.50 |
CORE_TOP | 3215.33 | 2534.17 | 433.67 |
PERIMETER_BOT_ZN_3 | 3119.83 | 2438.83 | 271.50 |
PERIMETER_BOT_ZN_2 | 2998.33 | 2600.17 | 263.83 |
PERIMETER_BOT_ZN_1 | 3323.83 | 1950.00 | 241.67 |
PERIMETER_BOT_ZN_4 | 3776.33 | 1613.83 | 312.00 |
PERIMETER_MID_ZN_3 | 3371.00 | 3284.83 | 1058.00 |
PERIMETER_MID_ZN_2 | 2743.17 | 2794.83 | 862.33 |
PERIMETER_MID_ZN_1 | 3266.83 | 2531.17 | 581.17 |
PERIMETER_MID_ZN_4 | 3269.17 | 3064.17 | 798.50 |
PERIMETER_TOP_ZN_3 | 3644.00 | 3520.00 | 1538.17 |
PERIMETER_TOP_ZN_2 | 3569.17 | 3373.00 | 1362.33 |
PERIMETER_TOP_ZN_1 | 3437.00 | 2948.00 | 984.67 |
PERIMETER_TOP_ZN_4 | 3468.50 | 3343.00 | 1206.00 |
DATACENTER_BOT_ZN_6 | 5939.50 | 1226.33 | 1226.33 |
DATACENTER_MID_ZN_6 | 5736.67 | 177.83 | 162.33 |
DATACENTER_TOP_ZN_6 | 5445.17 | 567.50 | 397.50 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5723.67 | 5723.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5940.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 68.33 | 0.00 | 4.00 |
CORE_BOTTOM | 0.00 | 2.33 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.17 |
CORE_TOP | 4.50 | 0.00 | 0.50 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 1.00 | 0.00 | 0.33 |
PERIMETER_BOT_ZN_2 | 0.00 | 10.50 | 0.00 | 10.50 |
PERIMETER_BOT_ZN_1 | 0.33 | 16.67 | 0.00 | 16.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 94.17 | 0.00 | 31.83 |
PERIMETER_MID_ZN_3 | 17.50 | 0.33 | 3.67 | 0.33 |
PERIMETER_MID_ZN_2 | 11.17 | 15.50 | 0.33 | 15.50 |
PERIMETER_MID_ZN_1 | 8.67 | 13.33 | 0.50 | 13.33 |
PERIMETER_MID_ZN_4 | 9.17 | 21.50 | 0.50 | 11.17 |
PERIMETER_TOP_ZN_3 | 96.83 | 4.17 | 29.67 | 2.50 |
PERIMETER_TOP_ZN_2 | 55.33 | 26.17 | 7.33 | 24.00 |
PERIMETER_TOP_ZN_1 | 41.50 | 14.50 | 7.33 | 12.83 |
PERIMETER_TOP_ZN_4 | 35.50 | 26.17 | 5.83 | 13.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 40.67 | 0.00 | 40.67 |
DATACENTER_MID_ZN_6 | 0.00 | 45.33 | 0.00 | 45.33 |
DATACENTER_TOP_ZN_6 | 0.00 | 40.67 | 0.00 | 40.67 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 475.00 | 0.00 | 420.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 102.17 | 677.33 | 29.67 | 501.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 1.272 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.995 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.829 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.783 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.956 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.313 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 1.274 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 1.880 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.872 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.267 | 0.111 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 1.193 | 0.102 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.436 | 0.105 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.933 | 0.126 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.380 | 0.130 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 1.197 | 0.126 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.491 | 0.130 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.481 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.01 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.48 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1027.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 53344857.12 | 0.00 | 53344857.12 | 0.00 | 53344857.12 | 37848132.68 | 3941.69 | 1663.06 | 3155.26 | 361.19 |
CORE_BOTTOM | 41759731.82 | 0.00 | 41759731.82 | 0.00 | 41759731.82 | 33990283.35 | 3866.50 | 4.43 | 4889.07 | 328.63 |
CORE_MID | 0.34E+09 | 0.00 | 0.34E+09 | 0.00 | 0.34E+09 | 0.34E+09 | 4157.93 | 6.49 | 4595.59 | 162.56 |
CORE_TOP | 31722538.28 | 0.00 | 31722538.28 | 0.00 | 31722538.28 | 33990283.35 | 4245.48 | 1.24 | 4513.28 | 219.64 |
PERIMETER_BOT_ZN_3 | 5078351.26 | 0.00 | 5078351.26 | 439326.30 | 5517677.56 | 4267819.30 | 3850.27 | 11.54 | 4898.19 | 328.63 |
PERIMETER_BOT_ZN_2 | 4522936.78 | 0.00 | 4522936.78 | 292884.00 | 4815820.78 | 2750345.05 | 3775.70 | 2.09 | 4982.21 | 328.63 |
PERIMETER_BOT_ZN_1 | 6717689.94 | 0.00 | 6717689.94 | 439326.30 | 7157016.24 | 4267912.63 | 3809.34 | 3.33 | 4947.33 | 328.63 |
PERIMETER_BOT_ZN_4 | 6439126.76 | 0.00 | 6439126.76 | 292884.00 | 6732010.76 | 2750345.05 | 3760.97 | 0.00 | 4999.03 | 328.63 |
PERIMETER_MID_ZN_3 | 44820147.04 | 0.00 | 44820147.04 | 1030333.47 | 45850480.51 | 42678193.03 | 4139.30 | 2.94 | 4617.76 | 162.56 |
PERIMETER_MID_ZN_2 | 45203740.75 | 0.00 | 45203740.75 | 686888.51 | 45890629.26 | 27503450.52 | 4053.96 | 2.17 | 4703.87 | 1071.56 |
PERIMETER_MID_ZN_1 | 61056002.61 | 0.00 | 61056002.61 | 1030333.47 | 62086336.08 | 42679126.28 | 4110.97 | 4.01 | 4645.02 | 162.56 |
PERIMETER_MID_ZN_4 | 47661323.34 | 0.00 | 47661323.34 | 686888.51 | 48348211.85 | 27503450.52 | 4048.40 | 2.30 | 4709.30 | 162.56 |
PERIMETER_TOP_ZN_3 | 4768659.37 | 0.00 | 4768659.37 | 1279256.65 | 6047916.03 | 4267819.30 | 4205.84 | 3.22 | 4550.94 | 219.64 |
PERIMETER_TOP_ZN_2 | 4542867.72 | 0.00 | 4542867.72 | 852837.19 | 5395704.91 | 2750345.05 | 4152.16 | 5.36 | 4602.48 | 219.64 |
PERIMETER_TOP_ZN_1 | 6093203.34 | 0.00 | 6093203.34 | 1279256.65 | 7372459.99 | 4267912.63 | 4195.19 | 2.24 | 4562.57 | 219.64 |
PERIMETER_TOP_ZN_4 | 4912340.83 | 0.00 | 4912340.83 | 852837.19 | 5765178.02 | 2750345.05 | 4132.23 | 1.91 | 4625.86 | 219.64 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.56E+10 | 0.00 | 0.56E+10 | 40073047.80 | 0.56E+10 | 0.50E+10 | 4446.87 | 4385.28 | 5196.96 | 1574.51 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.3458 | 0.0000 | 2.3458 | 0.0000 | 2.3458 | 1.2002 | 1372.24 | 1660.58 | 2910.18 |
CORE_BOTTOM | 1.8544 | 0.0000 | 1.8544 | 0.0000 | 1.8544 | 1.0778 | 1329.24 | 2.09 | 4611.67 |
CORE_MID | 15.4546 | 0.0000 | 15.4546 | 0.0000 | 15.4546 | 10.7782 | 1431.84 | 5.64 | 4505.52 |
CORE_TOP | 1.4592 | 0.0000 | 1.4592 | 0.0000 | 1.4592 | 1.0778 | 1471.78 | 1.18 | 4470.04 |
PERIMETER_BOT_ZN_3 | 0.2238 | 0.0000 | 0.2238 | 0.0102 | 0.2340 | 0.1353 | 1340.98 | 8.24 | 4593.78 |
PERIMETER_BOT_ZN_2 | 0.1983 | 0.0000 | 0.1983 | 0.0068 | 0.2051 | 0.0872 | 1285.08 | 1.75 | 4656.16 |
PERIMETER_BOT_ZN_1 | 0.2984 | 0.0000 | 0.2984 | 0.0102 | 0.3086 | 0.1353 | 1311.49 | 1.33 | 4630.18 |
PERIMETER_BOT_ZN_4 | 0.2837 | 0.0000 | 0.2837 | 0.0068 | 0.2905 | 0.0872 | 1272.60 | 0.00 | 4670.40 |
PERIMETER_MID_ZN_3 | 2.0449 | 0.0000 | 2.0449 | 0.0239 | 2.0688 | 1.3533 | 1417.72 | 2.38 | 4522.90 |
PERIMETER_MID_ZN_2 | 1.9169 | 0.0000 | 1.9169 | 0.0169 | 1.9338 | 0.8721 | 1354.93 | 1.34 | 3677.73 |
PERIMETER_MID_ZN_1 | 2.7966 | 0.0000 | 2.7966 | 0.0239 | 2.8204 | 1.3533 | 1390.34 | 3.38 | 4549.28 |
PERIMETER_MID_ZN_4 | 2.1723 | 0.0000 | 2.1723 | 0.0159 | 2.1882 | 0.8721 | 1352.67 | 1.10 | 4589.23 |
PERIMETER_TOP_ZN_3 | 0.2192 | 0.0000 | 0.2192 | 0.0297 | 0.2488 | 0.1353 | 1439.97 | 1.77 | 4501.25 |
PERIMETER_TOP_ZN_2 | 0.2089 | 0.0000 | 0.2089 | 0.0198 | 0.2287 | 0.0872 | 1404.85 | 3.93 | 4534.22 |
PERIMETER_TOP_ZN_1 | 0.2807 | 0.0000 | 0.2807 | 0.0297 | 0.3103 | 0.1353 | 1430.48 | 1.18 | 4511.35 |
PERIMETER_TOP_ZN_4 | 0.2258 | 0.0000 | 0.2258 | 0.0198 | 0.2455 | 0.0872 | 1394.09 | 1.05 | 4547.86 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 252.8628 | 0.0000 | 252.8628 | 0.9383 | 253.8011 | 158.4706 | 1629.87 | 4366.48 | 4712.35 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 86956974.59 | 0.00 | 86956974.59 | 48026705.38 | 3785.79 | 2.10 | 4972.10 | 328.63 |
VAV_MID WITH REHEAT | 0.72E+09 | 0.00 | 0.72E+09 | 0.48E+09 | 4087.32 | 2.58 | 4670.10 | 162.56 |
VAV_TOP WITH REHEAT | 70130401.45 | 0.00 | 70130401.45 | 48026705.38 | 4185.21 | 3.35 | 4571.44 | 219.47 |
CAV_BAS | 71901747.33 | 0.00 | 71901747.33 | 37848132.68 | 3886.48 | 2.84 | 4870.68 | 361.19 |
AIRLOOP DATACENTER BASEMENT | 7127877.82 | 0.00 | 7127877.82 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 329278.43 | 0.00 | 329278.43 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3292784.26 | 0.00 | 3292784.26 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 329278.43 | 0.00 | 329278.43 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.8528 | 0.0000 | 3.8528 | 1.5229 | 1291.15 | 1.74 | 4650.10 |
VAV_MID WITH REHEAT | 33.0618 | 0.0000 | 33.0618 | 15.2292 | 1372.71 | 0.44 | 4569.85 |
VAV_TOP WITH REHEAT | 3.2258 | 0.0000 | 3.2258 | 1.5229 | 1425.32 | 2.21 | 4515.47 |
CAV_BAS | 3.1618 | 0.0000 | 3.1618 | 1.2002 | 1356.76 | 0.84 | 4585.40 |
AIRLOOP DATACENTER BASEMENT | 0.3332 | 0.0000 | 0.3332 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0154 | 0.0000 | 0.0154 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1539 | 0.0000 | 0.1539 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0154 | 0.0000 | 0.0154 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 2236.10 | 2762.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 2525.87 | 2251.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 2719.31 | 2137.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1657.78 | 3304.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 3.4252 | 6.2606 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 34.2290 | 52.7097 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 3.4250 | 5.1428 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6184 | 5.4737 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4562 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0211 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2108 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0211 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1386 |
Defaulted Fields | 1179 |
Fields with Defaults | 3922 |
Autosized Fields | 336 |
Autosizable Fields | 412 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 30490.10 | 367451.46 | 08-JAN-10:30 | 2051130.69 | 03-AUG-15:50 |
Electricity:Building | 18924.55 | 251811.03 | 01-JAN-09:20 | 1140760.82 | 06-DEC-08:10 |
Electricity:Zone:BASEMENT | 664.85 | 14623.97 | 01-JAN-00:10 | 34452.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18924.55 | 251811.03 | 01-JAN-09:20 | 1140760.82 | 06-DEC-08:10 |
InteriorLights:Electricity | 3711.13 | 17601.77 | 01-JAN-09:20 | 352689.08 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3711.13 | 17601.77 | 01-JAN-09:20 | 352689.08 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 3711.13 | 17601.77 | 01-JAN-09:20 | 352689.08 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3711.13 | 17601.77 | 01-JAN-09:20 | 352689.08 | 30-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 537.23 | 7090.40 | 01-JAN-00:10 | 36983.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5372.24 | 70903.72 | 01-JAN-00:10 | 369831.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 537.22 | 7090.37 | 01-JAN-00:10 | 36983.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 59.20 | 839.57 | 01-JAN-09:10 | 4639.46 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.86 | 80.80 | 01-JAN-09:10 | 2363.15 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.86 | 80.80 | 01-JAN-09:10 | 2363.15 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 38.06 | 541.05 | 01-JAN-08:50 | 2989.85 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.06 | 52.07 | 01-JAN-08:50 | 1522.90 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.06 | 52.07 | 01-JAN-08:50 | 1522.90 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 58.94 | 839.58 | 01-JAN-08:50 | 4639.55 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.59 | 80.80 | 01-JAN-08:50 | 2363.20 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.59 | 80.80 | 01-JAN-08:50 | 2363.20 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 38.11 | 541.05 | 01-JAN-09:20 | 2989.84 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 12.11 | 52.07 | 01-JAN-09:20 | 1522.90 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 12.11 | 52.07 | 01-JAN-09:20 | 1522.90 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 592.24 | 8395.70 | 01-JAN-09:10 | 46395.89 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 188.81 | 807.98 | 01-JAN-09:10 | 23632.71 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 188.81 | 807.98 | 01-JAN-09:10 | 23632.71 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 380.61 | 5410.51 | 01-JAN-08:50 | 29898.67 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 120.63 | 520.69 | 01-JAN-08:50 | 15229.21 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 120.63 | 520.69 | 01-JAN-08:50 | 15229.21 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 589.55 | 8395.84 | 01-JAN-08:50 | 46396.76 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 186.12 | 807.99 | 01-JAN-08:50 | 23633.23 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 186.12 | 807.99 | 01-JAN-08:50 | 23633.23 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 381.15 | 5410.48 | 01-JAN-09:20 | 29898.58 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 121.17 | 520.69 | 01-JAN-09:20 | 15229.21 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 121.17 | 520.69 | 01-JAN-09:20 | 15229.21 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 59.22 | 839.57 | 01-JAN-09:10 | 4639.58 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.88 | 80.80 | 01-JAN-09:10 | 2363.27 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.88 | 80.80 | 01-JAN-09:10 | 2363.27 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 38.06 | 541.05 | 01-JAN-08:50 | 2989.86 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.06 | 52.07 | 01-JAN-08:50 | 1522.92 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.06 | 52.07 | 01-JAN-08:50 | 1522.92 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 58.96 | 839.58 | 01-JAN-08:50 | 4639.67 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.61 | 80.80 | 01-JAN-08:50 | 2363.32 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.61 | 80.80 | 01-JAN-08:50 | 2363.32 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 38.12 | 541.05 | 01-JAN-09:20 | 2989.85 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 12.12 | 52.07 | 01-JAN-09:20 | 1522.92 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 12.12 | 52.07 | 01-JAN-09:20 | 1522.92 | 30-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7562.65 | 95237.01 | 01-JAN-00:10 | 385552.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1598.46 | 19775.43 | 01-JAN-00:10 | 83152.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 3640.67 | 5992.31 | 07-JAN-17:10 | 448738.32 | 21-AUG-10:50 |
HeatRejection:Electricity | 1454.27 | 2326.74 | 14-JAN-08:00 | 92421.41 | 29-MAR-15:50 |
General:HeatRejection:Electricity | 1454.27 | 2326.74 | 14-JAN-08:00 | 92421.41 | 29-MAR-15:50 |
Electricity:HVAC | 5399.41 | 75169.68 | 08-JAN-23:10 | 450902.24 | 13-APR-14:50 |
ExteriorEquipment:Electricity | 1941.94 | 28795.69 | 01-JAN-00:10 | 118959.08 | 30-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 87.33 | 1613.62 | 01-JAN-00:10 | 5481.12 | 30-OCT-07:20 |
ElectricityPurchased:Facility | 30490.10 | 367451.46 | 08-JAN-10:30 | 2051130.69 | 03-AUG-15:50 |
ElectricityPurchased:Plant | 30490.10 | 367451.46 | 08-JAN-10:30 | 2051130.69 | 03-AUG-15:50 |
Cogeneration:ElectricityPurchased | 30490.10 | 367451.46 | 08-JAN-10:30 | 2051130.69 | 03-AUG-15:50 |
General:Cogeneration:ElectricityPurchased | 30490.10 | 367451.46 | 08-JAN-10:30 | 2051130.69 | 03-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 30490.10 | 367451.46 | 08-JAN-10:30 | 2051130.69 | 03-AUG-15:50 |
ElectricityNet:Plant | 30490.10 | 367451.46 | 08-JAN-10:30 | 2051130.69 | 03-AUG-15:50 |
Cogeneration:ElectricityNet | 30490.10 | 367451.46 | 08-JAN-10:30 | 2051130.69 | 03-AUG-15:50 |
General:Cogeneration:ElectricityNet | 30490.10 | 367451.46 | 08-JAN-10:30 | 2051130.69 | 03-AUG-15:50 |
Fans:Electricity | 2525.85 | 42722.22 | 12-JAN-02:00 | 287700.46 | 02-JUN-13:40 |
General:Fans:Electricity | 2525.85 | 42722.22 | 12-JAN-02:00 | 287700.46 | 02-JUN-13:40 |
ExteriorLights:Electricity | 670.87 | 0.00 | 01-JAN-07:50 | 54335.80 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 670.87 | 0.00 | 01-JAN-07:50 | 54335.80 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 50.38 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 50.38 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
Cooling:Electricity | 4111.57 | 28117.05 | 09-JAN-07:10 | 456189.80 | 17-AUG-13:10 |
General:Cooling:Electricity | 4111.57 | 28117.05 | 09-JAN-07:10 | 456189.80 | 17-AUG-13:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 8.95 | 0.00 | 01-JAN-00:10 | 5867.99 | 05-JAN-18:10 |
General:Humidifier:Electricity | 8.95 | 0.00 | 01-JAN-00:10 | 5867.99 | 05-JAN-18:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 801.73 | 3424.68 | 01-JAN-01:40 | 73998.79 | 17-APR-14:20 |
General:Pumps:Electricity | 801.73 | 3424.68 | 01-JAN-01:40 | 73998.79 | 17-APR-14:20 |
WIRED_LTG_ELECTRICITY | 104.28 | 0.00 | 01-JAN-00:10 | 9910.56 | 30-OCT-07:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1298.37 | 5695.87 | 13-AUG-16:20 | 1599222.50 | 13-FEB-07:10 |
NaturalGas:Plant | 1298.37 | 5695.87 | 13-AUG-16:20 | 1599222.50 | 13-FEB-07:10 |
Heating:NaturalGas | 640.67 | 0.00 | 01-JAN-00:10 | 1589015.49 | 13-FEB-07:10 |
Boiler:Heating:NaturalGas | 640.67 | 0.00 | 01-JAN-00:10 | 1589015.49 | 13-FEB-07:10 |
WaterSystems:NaturalGas | 657.71 | 5695.87 | 06-JAN-05:20 | 79691.14 | 26-JAN-12:50 |
Water Heater:WaterSystems:NaturalGas | 657.71 | 5695.87 | 06-JAN-05:20 | 79691.14 | 26-JAN-12:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 22373.89 | 138568.20 | 09-JAN-07:10 | 2625822.64 | 21-AUG-10:50 |
PlantLoopCoolingDemand:HVAC | 22373.89 | 138568.20 | 09-JAN-07:10 | 2625822.64 | 21-AUG-10:50 |
CoolingCoils:PlantLoopCoolingDemand | 22373.89 | 138568.20 | 09-JAN-07:10 | 2625822.64 | 21-AUG-10:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 10009.48 | 0.00 | 01-JAN-00:10 | 0.00 | 14-APR-16:00 |
Water:HVAC | 3.33 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-18:10 |
Humidifier:Water | 3.33 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-18:10 |
General:Humidifier:Water | 3.33 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-18:10 |
MainsWater:Facility | 10009.48 | 0.00 | 01-JAN-00:10 | 0.00 | 14-APR-16:00 |
MainsWater:HVAC | 3.33 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-18:10 |
Humidifier:MainsWater | 3.33 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-18:10 |
General:Humidifier:MainsWater | 3.33 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-18:10 |
Water:Plant | 10006.15 | 0.00 | 01-JAN-00:10 | 0.00 | 14-APR-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 10006.15 | 0.00 | 01-JAN-00:10 | 0.00 | 14-APR-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 7725.98 | 0.00 | 01-JAN-00:10 | 0.00 | 13-APR-14:50 |
General:HeatRejection:Water | 7725.98 | 0.00 | 01-JAN-00:10 | 0.00 | 13-APR-14:50 |
HeatRejection:MainsWater | 7725.98 | 0.00 | 01-JAN-00:10 | 0.00 | 13-APR-14:50 |
General:HeatRejection:MainsWater | 7725.98 | 0.00 | 01-JAN-00:10 | 0.00 | 13-APR-14:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 72320.71 | 213874.70 | 09-JAN-01:50 | 10169515.45 | 10-AUG-16:00 |
EnergyTransfer:Building | 19756.12 | 88034.12 | 14-JAN-20:20 | 1610772.61 | 02-AUG-15:40 |
EnergyTransfer:Zone:BASEMENT | 695.85 | 0.00 | 01-JAN-00:10 | 71799.17 | 13-NOV-06:10 |
Heating:EnergyTransfer | 249.34 | 0.00 | 13-JAN-22:10 | 753054.04 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.14 | 0.00 | 01-JAN-00:10 | 23770.39 | 08-JUL-16:10 |
General:Heating:EnergyTransfer | 249.34 | 0.00 | 13-JAN-22:10 | 753054.04 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.14 | 0.00 | 01-JAN-00:10 | 23770.39 | 08-JUL-16:10 |
Cooling:EnergyTransfer | 19506.78 | 85563.31 | 09-JAN-01:50 | 1610772.61 | 02-AUG-15:40 |
Cooling:EnergyTransfer:Zone:BASEMENT | 691.71 | 0.00 | 01-JAN-00:10 | 71799.17 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer | 19506.78 | 85563.31 | 09-JAN-01:50 | 1610772.61 | 02-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 691.71 | 0.00 | 01-JAN-00:10 | 71799.17 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 681.25 | 0.00 | 01-JAN-00:10 | 55140.84 | 07-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 681.25 | 0.00 | 01-JAN-00:10 | 55140.84 | 07-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 681.25 | 0.00 | 01-JAN-00:10 | 55140.84 | 07-AUG-13:10 |
EnergyTransfer:Zone:CORE_MID | 5011.82 | 0.00 | 01-JAN-00:10 | 501549.49 | 15-MAY-14:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.76 | 0.00 | 01-JAN-00:10 | 158750.90 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.76 | 0.00 | 01-JAN-00:10 | 158750.90 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5011.06 | 0.00 | 01-JAN-00:10 | 501549.49 | 15-MAY-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5011.06 | 0.00 | 01-JAN-00:10 | 501549.49 | 15-MAY-14:10 |
EnergyTransfer:Zone:CORE_TOP | 474.43 | 0.00 | 01-JAN-00:10 | 66159.74 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 5.18 | 0.00 | 01-JAN-00:10 | 66159.74 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 5.18 | 0.00 | 01-JAN-00:10 | 66159.74 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 469.25 | 0.00 | 01-JAN-00:10 | 52770.66 | 25-AUG-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 469.25 | 0.00 | 01-JAN-00:10 | 52770.66 | 25-AUG-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 85.36 | 0.00 | 01-JAN-00:10 | 10293.76 | 09-AUG-14:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.21 | 0.00 | 01-JAN-00:10 | 4654.19 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.21 | 0.00 | 01-JAN-00:10 | 4654.19 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 85.15 | 0.00 | 01-JAN-00:10 | 10293.76 | 09-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 85.15 | 0.00 | 01-JAN-00:10 | 10293.76 | 09-AUG-14:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 72.02 | 0.00 | 01-JAN-00:10 | 10619.81 | 07-JUL-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.16 | 0.00 | 01-JAN-00:10 | 3125.84 | 14-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.16 | 0.00 | 01-JAN-00:10 | 3125.84 | 14-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.86 | 0.00 | 01-JAN-00:10 | 10619.81 | 07-JUL-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.86 | 0.00 | 01-JAN-00:10 | 10619.81 | 07-JUL-09:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 108.97 | 0.00 | 01-JAN-00:10 | 15429.01 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.29 | 0.00 | 01-JAN-00:10 | 7536.52 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.29 | 0.00 | 01-JAN-00:10 | 7536.52 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 108.68 | 0.00 | 01-JAN-00:10 | 15429.01 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 108.68 | 0.00 | 01-JAN-00:10 | 15429.01 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 108.08 | 0.00 | 01-JAN-00:10 | 14670.17 | 18-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 2030.06 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 2030.06 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 108.07 | 0.00 | 01-JAN-00:10 | 14670.17 | 18-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 108.07 | 0.00 | 01-JAN-00:10 | 14670.17 | 18-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 655.28 | 0.00 | 01-JAN-00:10 | 120626.12 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 49.65 | 0.00 | 01-JAN-00:10 | 120626.12 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 49.65 | 0.00 | 01-JAN-00:10 | 120626.12 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 605.63 | 0.00 | 01-JAN-00:10 | 95255.07 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 605.63 | 0.00 | 01-JAN-00:10 | 95255.07 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 612.13 | 0.00 | 01-JAN-00:10 | 109723.99 | 07-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 25.51 | 0.00 | 01-JAN-00:10 | 108526.76 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 25.51 | 0.00 | 01-JAN-00:10 | 108526.76 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 586.62 | 0.00 | 01-JAN-00:10 | 109723.99 | 07-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 586.62 | 0.00 | 01-JAN-00:10 | 109723.99 | 07-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 886.22 | 0.00 | 01-JAN-00:10 | 146940.49 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 21.78 | 0.00 | 01-JAN-00:10 | 133214.37 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 21.78 | 0.00 | 01-JAN-00:10 | 133214.37 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 864.43 | 0.00 | 01-JAN-00:10 | 146940.49 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 864.43 | 0.00 | 01-JAN-00:10 | 146940.49 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 645.33 | 0.00 | 01-JAN-00:10 | 113365.17 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 18.96 | 0.00 | 01-JAN-00:10 | 98078.36 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 18.96 | 0.00 | 01-JAN-00:10 | 98078.36 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 626.38 | 0.00 | 01-JAN-00:10 | 113365.17 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 626.38 | 0.00 | 01-JAN-00:10 | 113365.17 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 76.18 | 0.00 | 01-JAN-00:10 | 15157.73 | 13-FEB-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 15.96 | 0.00 | 01-JAN-00:10 | 15157.73 | 13-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 15.96 | 0.00 | 01-JAN-00:10 | 15157.73 | 13-FEB-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 60.22 | 0.00 | 01-JAN-00:10 | 10668.62 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 60.22 | 0.00 | 01-JAN-00:10 | 10668.62 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 65.72 | 0.00 | 01-JAN-00:10 | 12770.31 | 13-FEB-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 8.06 | 0.00 | 01-JAN-00:10 | 12770.31 | 13-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 8.06 | 0.00 | 01-JAN-00:10 | 12770.31 | 13-FEB-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.66 | 0.00 | 01-JAN-00:10 | 11461.14 | 07-JUL-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.66 | 0.00 | 01-JAN-00:10 | 11461.14 | 07-JUL-09:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 92.10 | 0.00 | 01-JAN-00:10 | 16446.00 | 13-FEB-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.32 | 0.00 | 01-JAN-00:10 | 16446.00 | 13-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.32 | 0.00 | 01-JAN-00:10 | 16446.00 | 13-FEB-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 83.78 | 0.00 | 01-JAN-00:10 | 16012.04 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 83.78 | 0.00 | 01-JAN-00:10 | 16012.04 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 68.18 | 0.00 | 01-JAN-00:10 | 12968.45 | 09-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 6.45 | 0.00 | 01-JAN-00:10 | 12968.45 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 6.45 | 0.00 | 01-JAN-00:10 | 12968.45 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 61.73 | 0.00 | 01-JAN-00:10 | 12163.29 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 61.73 | 0.00 | 01-JAN-00:10 | 12163.29 | 02-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 77.48 | 0.00 | 01-JAN-00:10 | 9892.70 | 07-AUG-14:40 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.60 | 0.00 | 01-JAN-00:10 | 4590.56 | 13-FEB-08:20 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.60 | 0.00 | 01-JAN-00:10 | 4590.56 | 13-FEB-08:20 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 75.87 | 0.00 | 01-JAN-00:10 | 9892.70 | 07-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 75.87 | 0.00 | 01-JAN-00:10 | 9892.70 | 07-AUG-14:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 578.14 | 0.00 | 01-JAN-00:10 | 81326.82 | 05-JAN-12:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 52.15 | 0.00 | 01-JAN-00:10 | 81326.82 | 05-JAN-12:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 52.15 | 0.00 | 01-JAN-00:10 | 81326.82 | 05-JAN-12:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 525.99 | 0.00 | 01-JAN-00:10 | 79357.92 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 525.99 | 0.00 | 01-JAN-00:10 | 79357.92 | 05-JUL-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 104.02 | 0.00 | 01-JAN-00:10 | 24537.75 | 13-FEB-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 27.04 | 0.00 | 01-JAN-00:10 | 24537.75 | 13-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 27.04 | 0.00 | 01-JAN-00:10 | 24537.75 | 13-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 76.98 | 0.00 | 01-JAN-00:10 | 21473.12 | 07-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 76.98 | 0.00 | 01-JAN-00:10 | 21473.12 | 07-JUL-15:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.59 | 335.30 | 08-JAN-08:00 | 7885.44 | 09-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.59 | 335.30 | 08-JAN-08:00 | 7885.44 | 09-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.59 | 335.30 | 08-JAN-08:00 | 7885.44 | 09-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1243.49 | 0.28 | 23-JAN-07:40 | 74169.61 | 13-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 2.41 | 0.00 | 02-JAN-09:00 | 5356.86 | 08-JAN-01:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 2.41 | 0.00 | 02-JAN-09:00 | 5356.86 | 08-JAN-01:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1241.08 | 0.00 | 01-JAN-00:10 | 74169.61 | 13-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1241.08 | 0.00 | 01-JAN-00:10 | 74169.61 | 13-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 118.11 | 0.13 | 14-JAN-10:40 | 7563.85 | 13-AUG-19:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.69 | 0.00 | 02-JAN-13:10 | 579.25 | 15-JAN-19:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.69 | 0.00 | 02-JAN-13:10 | 579.25 | 15-JAN-19:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 117.42 | 0.00 | 01-JAN-00:10 | 7563.85 | 13-AUG-19:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 117.42 | 0.00 | 01-JAN-00:10 | 7563.85 | 13-AUG-19:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7156.38 | 85087.16 | 09-JAN-05:00 | 369986.88 | 07-AUG-21:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7156.38 | 85087.16 | 09-JAN-05:00 | 369986.88 | 07-AUG-21:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7156.38 | 85087.16 | 09-JAN-05:00 | 369986.88 | 07-AUG-21:20 |
PlantLoopHeatingDemand:Facility | 829.05 | 0.00 | 01-JAN-00:10 | 1311075.39 | 13-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 371.93 | 0.00 | 01-JAN-00:10 | 47931.16 | 01-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 371.93 | 0.00 | 01-JAN-00:10 | 47931.16 | 01-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 371.93 | 0.00 | 01-JAN-00:10 | 47931.16 | 01-FEB-12:30 |
EnergyTransfer:HVAC | 22263.17 | 122553.96 | 09-JAN-01:50 | 2887962.26 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 457.12 | 0.00 | 01-JAN-00:10 | 1295248.29 | 13-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 457.12 | 0.00 | 01-JAN-00:10 | 1295248.29 | 13-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 457.12 | 0.00 | 01-JAN-00:10 | 1295248.29 | 13-FEB-07:10 |
CoolingCoils:EnergyTransfer | 19646.98 | 110451.15 | 09-JAN-07:10 | 2469512.45 | 21-AUG-10:50 |
HeatRecoveryForHeating:EnergyTransfer | 926.28 | 0.00 | 01-JAN-00:10 | 805188.63 | 03-FEB-07:20 |
HeatRecoveryForCooling:EnergyTransfer | 1232.78 | 0.00 | 01-JAN-00:10 | 589224.25 | 07-JUL-12:00 |
EnergyTransfer:Plant | 30301.43 | 0.00 | 01-JAN-00:10 | 6364503.37 | 17-APR-14:20 |
LoopToLoop:EnergyTransfer | 10056.84 | -714.93 | 05-JAN-13:10 | 2017060.51 | 17-APR-14:20 |
WaterSystems:EnergyTransfer | 371.93 | 0.00 | 01-JAN-00:10 | 47931.16 | 01-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 371.93 | 0.00 | 01-JAN-00:10 | 47931.16 | 01-FEB-12:30 |
Boilers:EnergyTransfer | 452.92 | 0.00 | 01-JAN-00:10 | 1323433.68 | 13-FEB-07:10 |
Chillers:EnergyTransfer | 9017.54 | 0.00 | 01-JAN-00:10 | 1999982.69 | 17-APR-14:20 |
HeatRejection:EnergyTransfer | 10402.20 | 0.00 | 01-JAN-00:10 | 2268211.89 | 17-APR-14:20 |
General:HeatRejection:EnergyTransfer | 10402.20 | 0.00 | 01-JAN-00:10 | 2268211.89 | 17-APR-14:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.138 | -691.714 | 0.000 | 0.000 | 92.715 | 240.449 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -69.986 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -681.243 | 0.000 | 0.000 | 83.434 | 215.940 | 321.286 | 0.000 | 0.000 | 0.000 | 60.583 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 0.762 | -5011.039 | 0.000 | 0.000 | 841.743 | 2159.397 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1203.707 |
CORE_TOP | 0.000 | 0.000 | 5.179 | -469.249 | 0.000 | 0.000 | 86.039 | 215.940 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -159.194 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.214 | -85.146 | 0.000 | 0.000 | 10.770 | 18.857 | 40.342 | 22.962 | 0.000 | 0.235 | 39.834 | 0.000 | -43.084 | 0.000 | -4.984 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.164 | -71.857 | 0.000 | 0.000 | 6.987 | 12.058 | 25.998 | 38.319 | 0.000 | 0.166 | 16.822 | 0.000 | -25.405 | 0.000 | -3.252 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.289 | -108.679 | 0.000 | 0.000 | 10.687 | 18.593 | 40.343 | 67.301 | 0.000 | 0.229 | 14.806 | 0.000 | -38.517 | 0.000 | -5.052 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.008 | -108.067 | 0.000 | 0.000 | 6.872 | 12.112 | 25.998 | 37.661 | 0.000 | 0.141 | 59.795 | 0.000 | -30.836 | 0.000 | -3.684 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 49.648 | -605.623 | 0.000 | 0.000 | 111.463 | 188.815 | 403.423 | 237.408 | 0.000 | 5.444 | 98.578 | 0.000 | -386.723 | 0.000 | -102.433 | -0.021 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 25.508 | -586.614 | 0.000 | 0.000 | 52.835 | 120.629 | 259.981 | 384.653 | 0.000 | 3.553 | 46.155 | 0.000 | -237.081 | 0.000 | -69.619 | -0.001 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 21.782 | -864.421 | 0.000 | 0.000 | 108.430 | 186.121 | 403.429 | 673.216 | 0.000 | 5.130 | 0.012 | 0.000 | -369.684 | 0.000 | -111.632 | -52.371 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 18.957 | -626.369 | 0.000 | 0.000 | 71.966 | 121.171 | 259.979 | 388.146 | 0.000 | 3.391 | 97.787 | 0.000 | -262.682 | 0.000 | -72.345 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 15.958 | -60.217 | 0.000 | 0.000 | 11.337 | 18.882 | 40.342 | 23.989 | 0.000 | 0.657 | 0.001 | 0.000 | -36.126 | 0.000 | -11.807 | -3.015 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 8.057 | -57.660 | 0.000 | 0.000 | 7.251 | 12.063 | 25.998 | 38.663 | 0.000 | 0.419 | 0.000 | 0.000 | -22.390 | 0.000 | -8.084 | -4.318 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 8.323 | -83.778 | 0.000 | 0.000 | 11.029 | 18.614 | 40.343 | 67.792 | 0.000 | 0.609 | 0.000 | 0.000 | -34.746 | 0.000 | -12.853 | -15.334 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 6.449 | -61.733 | 0.000 | 0.000 | 7.301 | 12.117 | 25.998 | 38.907 | 0.000 | 0.410 | 3.858 | 0.000 | -24.875 | 0.000 | -8.433 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -139.586 | 0.000 | 0.000 | 0.949 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -21.209 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 2.413 | -1241.083 | 0.000 | 0.000 | 9.488 | 59.652 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -369.276 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.694 | -117.420 | 0.000 | 0.000 | 0.951 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -44.071 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7156.386 | 0.000 | 0.000 | 20.226 | 67.796 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -426.493 |
GROUNDFLOOR_PLENUM | 1.603 | -75.873 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.407 | 84.715 | 0.000 | 0.000 | 0.000 | -10.851 | 0.000 |
MIDFLOOR_PLENUM | 52.150 | -525.984 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.443 | 648.249 | 0.000 | 0.000 | 0.000 | -181.859 | -0.004 |
TOPFLOOR_PLENUM | 27.042 | -76.979 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.650 | 67.976 | 0.000 | 0.000 | 0.000 | -18.689 | -0.002 |
Total Facility | 80.795 | -678.836 | 168.545 | -18827.884 | 0.000 | 0.000 | 1552.474 | 3711.135 | 15213.411 | 2019.017 | 0.000 | 28.884 | 1239.172 | 0.000 | -1512.148 | 0.000 | -625.578 | -2369.004 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 11-DEC-04:02 | 0.00 | 0.00 | 0.00 | -114923.87 | 0.00 | 0.00 | 0.00 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 100299.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 13-NOV-04:02 | 0.00 | 0.00 | 0.00 | -96104.66 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.15 | 0.00 | 0.00 | 0.00 | 86999.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 20-JUN-03:02 | 0.00 | 0.00 | 0.00 | -847754.36 | 0.00 | 0.00 | 0.00 | 10475.32 | 80571.20 | 0.00 | 0.00 | 0.00 | 756707.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 19-JUN-03:02 | 0.00 | 0.00 | 0.00 | -86780.79 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.12 | 0.00 | 0.00 | 0.00 | 77676.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 09-JUL-18:01 | 0.00 | 0.00 | 0.00 | -16292.46 | 0.00 | 0.00 | 0.00 | 80.80 | 758.77 | 3444.14 | 0.00 | 124.89 | 11883.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-09:32 | 0.00 | 0.00 | 0.00 | -16410.13 | 0.00 | 0.00 | 24.96 | 52.07 | 488.98 | 9431.24 | 0.00 | 0.00 | 6421.71 | 0.00 | -0.00 | 0.00 | -8.83 | 0.00 |
PERIMETER_BOT_ZN_1 | 08-OCT-14:02 | 0.00 | 0.00 | 0.00 | -19829.47 | 0.00 | 0.00 | 38.70 | 80.80 | 758.78 | 12962.54 | 0.00 | 0.00 | 6017.78 | 0.00 | -0.00 | 0.00 | -29.12 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-JUL-17:31 | 0.00 | 0.00 | 0.00 | -22957.82 | 0.00 | 0.00 | 0.00 | 52.07 | 488.98 | 8744.21 | 0.00 | 37.36 | 13635.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-16:41 | 0.00 | 0.00 | 0.00 | -151459.06 | 0.00 | 0.00 | 440.99 | 807.98 | 7587.73 | 39157.41 | 0.00 | 5387.03 | 98077.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-09:32 | 0.00 | 0.00 | 0.00 | -171132.03 | 0.00 | 0.00 | 241.33 | 520.69 | 4889.82 | 93032.38 | 0.00 | 0.00 | 72745.99 | 0.00 | -0.00 | 0.00 | -298.18 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-14:42 | 0.00 | 0.00 | 0.00 | -190768.24 | 0.00 | 0.00 | 379.31 | 807.99 | 7587.84 | 108087.80 | 0.00 | 0.00 | 74036.53 | 0.00 | -0.00 | 0.00 | -131.24 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUL-17:31 | 0.00 | 0.00 | 0.00 | -189853.81 | 0.00 | 0.00 | 0.00 | 520.69 | 4889.79 | 87696.98 | 0.00 | 977.70 | 95768.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 06-AUG-17:01 | 0.00 | 0.00 | 0.00 | -17794.06 | 0.00 | 0.00 | 0.00 | 80.80 | 758.77 | 2572.78 | 0.00 | 551.07 | 13830.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-11:02 | 0.00 | 0.00 | 0.00 | -17596.90 | 0.00 | 0.00 | 23.73 | 52.07 | 488.98 | 6181.08 | 0.00 | 109.06 | 10741.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-14:32 | 0.00 | 0.00 | 0.00 | -21119.71 | 0.00 | 0.00 | 38.06 | 80.80 | 758.78 | 11272.71 | 0.00 | 0.00 | 8990.95 | 0.00 | -0.00 | 0.00 | -21.59 | 0.00 |
PERIMETER_TOP_ZN_4 | 06-AUG-17:01 | 0.00 | 0.00 | 0.00 | -20636.84 | 0.00 | 0.00 | 0.00 | 52.07 | 488.98 | 7219.92 | 0.00 | 263.79 | 12612.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 09-APR-18:13 | 0.00 | 0.00 | 0.00 | -7885.44 | 0.00 | 0.00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 62.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 13-AUG-18:40 | 0.00 | 0.00 | 0.00 | -74169.61 | 0.00 | 0.00 | 0.00 | 289.38 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4063.99 |
DATACENTER_TOP_ZN_6 | 13-AUG-19:32 | 0.00 | 0.00 | 0.00 | -7566.92 | 0.00 | 0.00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -256.44 |
DATACENTER_BASEMENT_ZN_6 | 07-AUG-21:12 | 0.00 | 0.00 | 0.00 | -370323.42 | 0.00 | 0.00 | 113.48 | 657.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10080.34 |
GROUNDFLOOR_PLENUM | 14-AUG-05:15 | 0.00 | -13406.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13433.71 | 0.00 | -0.00 | 0.00 | -27.03 | 0.00 |
MIDFLOOR_PLENUM | 30-AUG-05:15 | 0.00 | -85973.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86725.77 | 0.00 | -0.00 | 0.00 | -752.62 | 0.00 |
TOPFLOOR_PLENUM | 07-JUL-15:10 | 0.00 | -21472.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.90 | 21357.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:03 | 0.00 | -57853.81 | 0.00 | -1885231.36 | 0.00 | 0.00 | 15730.14 | 39207.80 | 623236.89 | 0.00 | 0.00 | 0.00 | 1299294.97 | 0.00 | -33352.10 | 0.00 | -1032.53 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-JUL-16:02 | 0.00 | 0.00 | 25322.13 | 0.00 | 0.00 | 0.00 | 520.13 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -40466.23 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 09-JAN-05:01 | 0.00 | 0.00 | 401375.39 | 0.00 | 0.00 | 0.00 | 0.00 | 20950.64 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -502897.23 |
CORE_TOP | 09-JAN-04:01 | 0.00 | 0.00 | 79161.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -88266.20 |
PERIMETER_BOT_ZN_3 | 13-FEB-05:02 | 0.00 | 0.00 | 11825.97 | 0.00 | 0.00 | 0.00 | 0.00 | 263.06 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5087.74 | 0.00 | -1389.83 | -6623.15 |
PERIMETER_BOT_ZN_2 | 13-FEB-05:02 | 0.00 | 0.00 | 9386.04 | 0.00 | 0.00 | 0.00 | 0.00 | 169.52 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3384.22 | 0.00 | -928.63 | -5894.70 |
PERIMETER_BOT_ZN_1 | 09-JAN-05:01 | 0.00 | 0.00 | 14343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 263.06 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3957.11 | 0.00 | -881.67 | -10779.18 |
PERIMETER_BOT_ZN_4 | 13-FEB-06:01 | 0.00 | 0.00 | 7001.29 | 0.00 | 0.00 | 0.00 | 94.15 | 169.52 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3538.67 | 0.00 | -248.55 | -4129.70 |
PERIMETER_MID_ZN_3 | 12-FEB-05:22 | 0.00 | 0.00 | 136834.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.28 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -56729.76 | 0.00 | -37479.29 | -51528.69 |
PERIMETER_MID_ZN_2 | 12-FEB-05:22 | 0.00 | 0.00 | 142153.87 | 0.00 | 0.00 | 0.00 | 0.00 | 847.62 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -36433.59 | 0.00 | -25332.61 | -86125.11 |
PERIMETER_MID_ZN_1 | 12-FEB-05:22 | 0.00 | 0.00 | 154821.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.31 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -55331.51 | 0.00 | -38156.70 | -70236.20 |
PERIMETER_MID_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 144950.71 | 0.00 | 0.00 | 0.00 | 0.00 | 847.62 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24003.43 | 0.00 | -11303.50 | -117011.12 |
PERIMETER_TOP_ZN_3 | 12-FEB-05:22 | 0.00 | 0.00 | 16682.70 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 758.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5324.59 | 0.00 | -4384.04 | -7864.37 |
PERIMETER_TOP_ZN_2 | 12-FEB-05:22 | 0.00 | 0.00 | 15585.08 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3419.22 | 0.00 | -2962.95 | -9776.66 |
PERIMETER_TOP_ZN_1 | 12-FEB-05:22 | 0.00 | 0.00 | 18635.37 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 758.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5170.38 | 0.00 | -4432.83 | -9922.48 |
PERIMETER_TOP_ZN_4 | 12-FEB-05:22 | 0.00 | 0.00 | 17046.62 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3634.25 | 0.00 | -3031.56 | -10954.55 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 08-JAN-01:40 | 0.00 | 0.00 | 5356.86 | 0.00 | 0.00 | 0.00 | 0.00 | 289.38 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25132.29 |
DATACENTER_TOP_ZN_6 | 15-JAN-19:00 | 0.00 | 0.00 | 579.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2556.80 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-04:03 | 13738.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1809.59 | -11928.77 |
MIDFLOOR_PLENUM | 05-JAN-11:33 | 140286.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -10510.22 | -129776.39 |
TOPFLOOR_PLENUM | 13-FEB-05:32 | 25574.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5009.54 | -20564.72 |
Total Facility | 09-JAN-06:01 | -154712.91 | 203413.70 | 1054210.93 | -203413.70 | 0.00 | 0.00 | 21352.49 | 39207.80 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -157169.26 | 0.00 | -27941.05 | -1043310.69 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.4676 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.7071 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 98.2697 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 90.4253 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.1315 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.6555 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.8456 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.8456 | 0.2053 | 1.0000 | Not calculated | 1.2002 | 0.2053 | ||
AIRLOOP DATACENTER BASEMENT | 22.0966 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 22.0969 | 0.0153 | 1.0000 | Not calculated | 0.3384 | 0.0153 | ||
AIRLOOP DATACENTER BOT | 0.4887 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4887 | 0.0320 | 1.0000 | Not calculated | 0.0156 | 0.0320 | ||
AIRLOOP DATACENTER MID | 4.6470 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6470 | 0.0336 | 1.0000 | Not calculated | 0.1563 | 0.0336 | ||
AIRLOOP DATACENTER TOP | 0.4700 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4700 | 0.0333 | 1.0000 | Not calculated | 0.0156 | 0.0333 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.2338 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2325 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 49.1348 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 31.0484 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.0658 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2517 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.8456 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.8456 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2053 | ||
AIRLOOP DATACENTER BASEMENT | 22.0966 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 22.0966 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0153 | ||
AIRLOOP DATACENTER BOT | 0.4887 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4887 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0320 | ||
AIRLOOP DATACENTER MID | 4.6470 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6470 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0336 | ||
AIRLOOP DATACENTER TOP | 0.4700 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4700 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0333 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.8456 | 5.8456 | 5.8456 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1508 | 6.1508 | 1.9375 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 58.0540 | 58.0540 | 18.9837 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7357 | 5.7357 | 1.9329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9923 | 0.9923 | 0.2977 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9560 | 0.9560 | 0.2868 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1370 | 1.1370 | 0.3411 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2316 | 1.2316 | 0.3695 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.3102 | 9.3102 | 2.7931 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.8028 | 9.8028 | 2.9408 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.7346 | 10.7346 | 3.2204 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.3680 | 10.3680 | 3.1104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0643 | 1.0643 | 0.3193 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0055 | 1.0055 | 0.3016 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1996 | 1.1996 | 0.3599 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1265 | 1.1265 | 0.3379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4887 | 0.4887 | 0.4887 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6470 | 4.6470 | 4.6470 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4700 | 0.4700 | 0.4700 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 22.0966 | 22.0966 | 22.0966 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.4676 | 9.7071 | 10.4676 | 3.2325 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 98.2697 | 90.4253 | 98.2697 | 31.0484 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.1315 | 9.6555 | 10.1315 | 3.2517 | 0.0000 | 1.0000 |
CAV_BAS | 5.8456 | 5.8456 | 5.8456 | 5.8456 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.0966 | 22.0969 | 22.0966 | 22.0966 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4887 | 0.4887 | 0.4887 | 0.4887 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6470 | 4.6470 | 4.6470 | 4.6470 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4700 | 0.4700 | 0.4700 | 0.4700 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.8456 | 5.8456 | 5.8456 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0754 | 3.0754 | 1.9375 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 29.0270 | 29.0270 | 18.9837 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8679 | 2.8679 | 1.9329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4961 | 0.4961 | 0.2977 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4780 | 0.4780 | 0.2868 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5685 | 0.5685 | 0.3411 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6158 | 0.6158 | 0.3695 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6551 | 4.6551 | 2.7931 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9014 | 4.9014 | 2.9408 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3673 | 5.3673 | 3.2204 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1840 | 5.1840 | 3.1104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5321 | 0.5321 | 0.3193 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5027 | 0.5027 | 0.3016 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5998 | 0.5998 | 0.3599 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5632 | 0.5632 | 0.3379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4887 | 0.4887 | 0.4887 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6470 | 4.6470 | 4.6470 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4700 | 0.4700 | 0.4700 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 22.0966 | 22.0966 | 22.0966 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.2338 | 3.2325 | 3.2325 | 3.2325 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 49.1348 | 31.0484 | 31.0484 | 31.0484 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.0658 | 3.2517 | 3.2517 | 3.2517 | 0.0000 | 1.0000 |
CAV_BAS | 5.8456 | 5.8456 | 5.8456 | 5.8456 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.0966 | 22.0966 | 22.0966 | 22.0966 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4887 | 0.4887 | 0.4887 | 0.4887 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6470 | 4.6470 | 4.6470 | 4.6470 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4700 | 0.4700 | 0.4700 | 0.4700 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 29.67 |
Number of hours cooling loads not met | 501.00 |
Number of hours not met | 530.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 640.67 | 1589015.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 4111.57 | 456189.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3711.13 | 352689.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 670.87 | 54335.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.33 | 5481.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2525.85 | 287700.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 801.73 | 73998.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1454.27 | 92421.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 8.95 | 5867.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 50.38 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 657.71 | 79691.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 30490.10 |
Natural Gas | 0.00 | 1298.37 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 31788.48 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 80.12 |
Space Heating | 0.00 |
Space Cooling | 88.76 |
Fans (All) | 54.53 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 658.24 |
Subtotal | 658.24 |
Natural Gas [MJ/m2] | |
Space Heating | 13.83 |
Service Water Heating | 14.20 |
Miscellaneous (All) | 28.03 |
Subtotal | 28.03 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.67 |
Space Heating | 2.02 |
Space Cooling | 12.93 |
Fans (All) | 7.95 |
Service Water Heating | 2.07 |
Receptacle Equipment | 47.86 |
Miscellaneous | 15.50 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2645. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8027.83 | 732.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8678.50 | 81.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8748.33 | 11.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8714.67 | 45.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8716.83 | 43.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8109.67 | 650.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8731.33 | 28.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8610.67 | 149.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8643.50 | 116.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8301.67 | 458.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8699.83 | 60.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8572.50 | 187.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8606.83 | 153.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8323.50 | 436.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6781.83 | 1978.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6771.50 | 1988.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6742.83 | 2017.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6628.83 | 2131.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8590.00 | 170.00 | 0.00 | 0.00 | 0.00 |
Min | 6628.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2131.17 | 0.00 | 0.00 | 0.00 |
Average | 8262.01 | 497.99 | 0.00 | 0.00 | 0.00 |
Sum | 190026.33 | 11453.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 366573.17 | 2042.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330687.00 | 126.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330807.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1240.83 | 1027.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1229.83 | 1038.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1220.67 | 1047.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 61354.00 | 42041.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 366573.17 | 42041.00 | 0.00 | 0.00 | 0.00 |
Average | 78277.15 | 2057.76 | 0.00 | 0.00 | 0.00 |
Sum | 1800374.50 | 47328.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 6295.00 | 2465.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7466.00 | 1294.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7463.00 | 1297.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7496.17 | 1263.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7551.17 | 1208.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7975.33 | 784.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7582.50 | 1177.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7124.83 | 1635.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7425.50 | 1334.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7472.00 | 1288.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7350.83 | 1409.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7337.67 | 1422.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7475.67 | 1284.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7484.00 | 1276.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7396.67 | 1363.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7380.00 | 1380.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7396.33 | 1363.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7358.17 | 1401.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7334.33 | 1425.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7482.33 | 1277.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7166.67 | 1593.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7238.67 | 1521.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 6423.33 | 2336.67 | 0.00 | 0.00 | 0.00 |
Min | 6295.00 | 784.67 | 0.00 | 0.00 | 0.00 |
Max | 7975.33 | 2465.00 | 0.00 | 0.00 | 0.00 |
Average | 7333.75 | 1426.25 | 0.00 | 0.00 | 0.00 |
Sum | 168676.17 | 32803.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 345199.83 | 23416.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 328414.33 | 2398.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328514.50 | 2298.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 328164.33 | 2648.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38920.33 | 4.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38922.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38919.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24908.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38921.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1473.33 | 794.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1457.00 | 811.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1443.67 | 824.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 75864.83 | 27530.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 345199.83 | 27530.17 | 0.00 | 0.00 | 0.00 |
Average | 77694.08 | 2640.83 | 0.00 | 0.00 | 0.00 |
Sum | 1786963.83 | 60739.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472557E+11 | 109093.15 | 02-JAN-04:03 | 3.30 | 2.57 | 0.565359E+10 | 7499.16 | 10-JAN-14:09 | 3.98 | 1.51 |
February | 0.441967E+11 | 109664.00 | 27-FEB-04:02 | 11.20 | 6.60 | 0.513240E+10 | 7499.15 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.559121E+11 | 111022.50 | 13-MAR-03:02 | 7.70 | 3.23 | 0.613087E+10 | 7499.46 | 08-MAR-10:20 | 7.70 | 3.23 |
April | 0.506788E+11 | 109035.55 | 10-APR-03:02 | 10.32 | 6.33 | 0.544633E+10 | 7499.26 | 03-APR-09:20 | 10.32 | 6.33 |
May | 0.553991E+11 | 107862.13 | 15-MAY-03:02 | 12.80 | 11.19 | 0.589995E+10 | 7499.39 | 11-MAY-09:00 | 12.80 | 11.19 |
June | 0.595708E+11 | 100968.31 | 10-JUN-05:02 | 11.28 | 8.79 | 0.588213E+10 | 7499.07 | 09-JUN-09:00 | 11.28 | 8.79 |
July | 0.610352E+11 | 92535.35 | 03-JUL-03:02 | 17.80 | 16.72 | 0.547419E+10 | 7498.78 | 28-JUL-09:20 | 19.40 | 19.40 |
August | 0.693769E+11 | 87250.99 | 26-AUG-03:02 | 21.70 | 17.57 | 0.613922E+10 | 7499.01 | 25-AUG-09:39 | 21.70 | 17.57 |
September | 0.632257E+11 | 100330.03 | 14-SEP-03:02 | 13.72 | 12.10 | 0.545431E+10 | 7499.17 | 22-SEP-13:09 | 26.20 | 16.90 |
October | 0.646852E+11 | 110967.27 | 30-OCT-03:02 | 8.90 | 8.90 | 0.567249E+10 | 7498.97 | 31-OCT-09:00 | 10.60 | 9.10 |
November | 0.627481E+11 | 112151.79 | 20-NOV-04:02 | 10.63 | 8.44 | 0.561649E+10 | 7499.35 | 16-NOV-10:20 | 10.63 | 8.44 |
December | 0.576283E+11 | 114909.02 | 11-DEC-04:02 | 7.12 | 6.27 | 0.547007E+10 | 7499.26 | 11-DEC-10:39 | 13.90 | 11.28 |
Annual Sum or Average | 0.691713E+12 | 0.679720E+11 | ||||||||
Minimum of Months | 0.441967E+11 | 87250.99 | 3.30 | 2.57 | 0.513240E+10 | 7498.78 | 3.98 | 1.51 | ||
Maximum of Months | 0.693769E+11 | 114909.02 | 21.70 | 17.57 | 0.613922E+10 | 7499.46 | 26.20 | 19.40 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367208E+11 | 87864.18 | 02-JAN-06:02 | 3.30 | 2.54 | 0.504922E+10 | 6750.38 | 03-JAN-14:00 | 2.80 | 2.54 |
February | 0.391809E+11 | 90363.19 | 21-FEB-04:03 | 6.70 | 4.44 | 0.459431E+10 | 6747.64 | 07-FEB-14:00 | 6.70 | 4.44 |
March | 0.573910E+11 | 92577.88 | 13-MAR-03:02 | 7.70 | 3.23 | 0.550026E+10 | 6735.22 | 08-MAR-10:09 | 7.70 | 3.23 |
April | 0.606136E+11 | 91042.64 | 05-APR-03:02 | 12.12 | 11.47 | 0.488278E+10 | 6839.87 | 14-APR-13:50 | 27.12 | 15.42 |
May | 0.572607E+11 | 93899.66 | 08-MAY-03:02 | 16.78 | 16.47 | 0.528829E+10 | 6818.86 | 18-MAY-13:20 | 28.70 | 18.38 |
June | 0.654536E+11 | 90526.79 | 01-JUN-03:02 | 19.73 | 17.88 | 0.526952E+10 | 6734.84 | 09-JUN-09:00 | 24.40 | 15.46 |
July | 0.703536E+11 | 89480.77 | 29-JUL-03:02 | 17.70 | 17.43 | 0.489452E+10 | 6734.56 | 05-JUL-09:00 | 17.70 | 17.43 |
August | 0.796125E+11 | 82140.59 | 08-AUG-04:23 | 20.60 | 20.43 | 0.549421E+10 | 6734.63 | 25-AUG-13:50 | 30.92 | 18.65 |
September | 0.573538E+11 | 95243.17 | 18-SEP-03:02 | 15.00 | 14.25 | 0.488482E+10 | 6734.83 | 22-SEP-13:30 | 26.40 | 17.18 |
October | 0.557873E+11 | 94071.26 | 16-OCT-03:02 | 13.90 | 13.26 | 0.508068E+10 | 6734.71 | 30-OCT-09:00 | 11.10 | 11.10 |
November | 0.529991E+11 | 96114.60 | 13-NOV-04:02 | 5.40 | 2.09 | 0.503221E+10 | 6735.03 | 16-NOV-10:09 | 10.68 | 10.03 |
December | 0.485181E+11 | 92234.92 | 11-DEC-04:02 | 7.12 | 6.27 | 0.490315E+10 | 6734.97 | 11-DEC-10:00 | 15.00 | 12.11 |
Annual Sum or Average | 0.681245E+12 | 0.608740E+11 | ||||||||
Minimum of Months | 0.367208E+11 | 82140.59 | 3.30 | 2.09 | 0.459431E+10 | 6734.56 | 2.80 | 2.54 | ||
Maximum of Months | 0.796125E+11 | 96114.60 | 20.60 | 20.43 | 0.550026E+10 | 6839.87 | 30.92 | 18.65 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254895E+11 | 65721.43 | 05-JAN-11:33 | 0.03 | -4.6 | 0.473986E+10 | 6832.63 | 05-JAN-11:00 | 0.60 | -4.3 |
February | 0.273172E+11 | 77635.86 | 23-FEB-06:03 | 5.50 | 3.99 | 0.442844E+10 | 7298.42 | 02-FEB-10:30 | 5.50 | 3.99 |
March | 0.409097E+11 | 81356.74 | 30-MAR-04:03 | 17.30 | 15.29 | 0.547163E+10 | 6737.49 | 22-MAR-13:09 | 17.30 | 15.29 |
April | 0.420835E+11 | 82417.86 | 21-APR-04:03 | 15.60 | 14.27 | 0.487310E+10 | 6782.37 | 14-APR-13:50 | 15.60 | 14.27 |
May | 0.494103E+11 | 84764.16 | 31-MAY-03:02 | 20.92 | 19.80 | 0.528347E+10 | 6864.74 | 15-MAY-13:39 | 20.92 | 19.80 |
June | 0.531776E+11 | 84794.05 | 20-JUN-03:02 | 20.40 | 19.67 | 0.526759E+10 | 6738.49 | 02-JUN-13:50 | 20.40 | 19.67 |
July | 0.530497E+11 | 84563.52 | 26-JUL-03:02 | 21.70 | 21.41 | 0.489411E+10 | 6734.55 | 05-JUL-09:20 | 21.70 | 21.41 |
August | 0.573491E+11 | 84261.34 | 25-AUG-03:02 | 20.50 | 18.92 | 0.549536E+10 | 6734.71 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.478129E+11 | 84617.26 | 11-SEP-03:02 | 20.00 | 18.85 | 0.487839E+10 | 6734.81 | 22-SEP-13:50 | 26.60 | 17.45 |
October | 0.410871E+11 | 82354.80 | 18-OCT-04:03 | 20.00 | 20.00 | 0.505581E+10 | 6760.86 | 25-OCT-09:50 | 8.22 | 6.77 |
November | 0.346327E+11 | 81820.84 | 04-NOV-05:02 | 16.60 | 15.28 | 0.498607E+10 | 6768.89 | 20-NOV-10:09 | 4.90 | 2.39 |
December | 0.287870E+11 | 79238.75 | 14-DEC-06:03 | 6.60 | 5.31 | 0.476036E+10 | 6805.48 | 01-DEC-10:09 | 6.60 | 5.31 |
Annual Sum or Average | 0.501106E+12 | 0.601342E+11 | ||||||||
Minimum of Months | 0.254895E+11 | 65721.43 | 0.03 | -4.6 | 0.442844E+10 | 6734.55 | 0.60 | -4.3 | ||
Maximum of Months | 0.573491E+11 | 84794.05 | 21.70 | 21.41 | 0.549536E+10 | 7298.42 | 30.18 | 21.41 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190323E+11 | 30488.72 | 20-JAN-17:00 | 16.70 | 11.48 | 0.423394E+10 | 6734.26 | 20-JAN-14:00 | 16.70 | 11.48 |
February | 0.215242E+11 | 38955.49 | 28-FEB-17:00 | 23.90 | 12.94 | 0.410107E+10 | 6734.75 | 22-FEB-14:00 | 23.90 | 12.94 |
March | 0.341955E+11 | 80162.48 | 31-MAR-04:03 | 17.12 | 14.83 | 0.533425E+10 | 6734.85 | 08-MAR-10:00 | 17.12 | 14.83 |
April | 0.383594E+11 | 81971.81 | 24-APR-04:03 | 13.90 | 13.90 | 0.481835E+10 | 6891.67 | 17-APR-13:00 | 13.90 | 13.90 |
May | 0.495072E+11 | 85140.36 | 30-MAY-03:02 | 20.00 | 17.77 | 0.527482E+10 | 6767.47 | 19-MAY-13:39 | 20.00 | 17.77 |
June | 0.565566E+11 | 86798.98 | 19-JUN-03:02 | 20.60 | 19.79 | 0.526817E+10 | 6734.80 | 09-JUN-09:00 | 20.60 | 19.79 |
July | 0.576697E+11 | 84643.21 | 03-JUL-03:02 | 17.80 | 16.72 | 0.489517E+10 | 6734.52 | 28-JUL-09:09 | 19.40 | 19.40 |
August | 0.621185E+11 | 84199.07 | 08-AUG-03:02 | 21.02 | 20.73 | 0.549771E+10 | 6742.39 | 25-AUG-13:50 | 30.92 | 18.65 |
September | 0.467118E+11 | 85801.98 | 05-SEP-03:02 | 22.02 | 20.50 | 0.486799E+10 | 6734.79 | 22-SEP-13:00 | 26.70 | 17.59 |
October | 0.350214E+11 | 81051.42 | 18-OCT-04:03 | 20.00 | 20.00 | 0.494371E+10 | 6750.04 | 04-OCT-09:20 | 20.00 | 20.00 |
November | 0.263046E+11 | 75235.52 | 04-NOV-05:02 | 16.60 | 15.28 | 0.473603E+10 | 6734.68 | 02-NOV-09:00 | 16.60 | 15.28 |
December | 0.222512E+11 | 61707.63 | 13-DEC-06:03 | 16.70 | 15.65 | 0.429783E+10 | 6734.52 | 14-DEC-14:00 | 15.00 | 10.54 |
Annual Sum or Average | 0.469252E+12 | 0.582690E+11 | ||||||||
Minimum of Months | 0.190323E+11 | 30488.72 | 13.90 | 11.48 | 0.410107E+10 | 6734.26 | 13.90 | 10.54 | ||
Maximum of Months | 0.621185E+11 | 86798.98 | 23.90 | 20.73 | 0.549771E+10 | 6891.67 | 30.92 | 20.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258109E+10 | 3738.25 | 31-JAN-15:00 | 21.10 | 12.97 | 0.529799E+09 | 845.60 | 19-JAN-14:00 | 21.10 | 12.97 |
February | 0.327032E+10 | 5987.05 | 28-FEB-15:00 | 25.00 | 13.71 | 0.512283E+09 | 845.64 | 22-FEB-14:09 | 25.00 | 13.71 |
March | 0.566302E+10 | 9132.41 | 30-MAR-05:03 | 17.80 | 16.10 | 0.670998E+09 | 845.64 | 08-MAR-10:00 | 17.80 | 16.10 |
April | 0.716516E+10 | 10617.15 | 19-APR-05:03 | 16.02 | 14.35 | 0.605383E+09 | 854.66 | 18-APR-13:39 | 16.02 | 14.35 |
May | 0.806542E+10 | 12398.95 | 30-MAY-05:03 | 18.68 | 17.36 | 0.662060E+09 | 857.03 | 18-MAY-13:20 | 18.68 | 17.36 |
June | 0.110192E+11 | 16106.91 | 25-JUN-16:41 | 32.88 | 22.29 | 0.661899E+09 | 845.64 | 09-JUN-09:00 | 32.88 | 22.29 |
July | 0.120973E+11 | 16295.45 | 09-JUL-18:01 | 32.70 | 22.56 | 0.615347E+09 | 845.63 | 05-JUL-13:39 | 32.70 | 22.56 |
August | 0.133133E+11 | 12345.25 | 14-AUG-05:03 | 23.30 | 20.62 | 0.690423E+09 | 846.05 | 10-AUG-13:39 | 23.30 | 20.62 |
September | 0.783026E+10 | 12045.38 | 05-SEP-03:02 | 22.02 | 20.50 | 0.611580E+09 | 845.65 | 22-SEP-13:30 | 26.40 | 17.18 |
October | 0.578443E+10 | 11399.33 | 18-OCT-05:03 | 20.00 | 20.00 | 0.622985E+09 | 845.62 | 12-OCT-09:09 | 20.00 | 20.00 |
November | 0.457799E+10 | 5685.05 | 02-NOV-14:00 | 23.30 | 17.05 | 0.604710E+09 | 845.63 | 06-NOV-10:09 | 14.87 | 12.62 |
December | 0.377912E+10 | 7211.23 | 13-DEC-06:03 | 16.70 | 15.65 | 0.562233E+09 | 845.62 | 12-DEC-10:00 | 16.70 | 15.65 |
Annual Sum or Average | 0.851467E+11 | 0.734970E+10 | ||||||||
Minimum of Months | 0.258109E+10 | 3738.25 | 16.02 | 12.97 | 0.512283E+09 | 845.60 | 14.87 | 12.62 | ||
Maximum of Months | 0.133133E+11 | 16295.45 | 32.88 | 22.56 | 0.690423E+09 | 857.03 | 32.88 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236632E+10 | 3099.59 | 31-JAN-06:02 | 10.00 | 8.54 | 0.338942E+09 | 534.14 | 31-JAN-10:00 | 14.40 | 11.88 |
February | 0.300477E+10 | 6232.97 | 27-FEB-09:40 | 12.23 | 5.46 | 0.326240E+09 | 544.96 | 28-FEB-10:00 | 20.60 | 11.95 |
March | 0.496324E+10 | 7103.79 | 14-MAR-09:30 | 16.95 | 13.93 | 0.425908E+09 | 545.00 | 08-MAR-10:09 | 16.95 | 13.93 |
April | 0.628561E+10 | 8650.84 | 17-APR-08:40 | 19.27 | 13.92 | 0.388277E+09 | 550.72 | 18-APR-13:39 | 27.40 | 16.07 |
May | 0.717531E+10 | 16058.82 | 07-MAY-09:23 | 24.15 | 19.65 | 0.425492E+09 | 553.76 | 18-MAY-13:20 | 28.70 | 18.38 |
June | 0.899868E+10 | 16295.78 | 25-JUN-10:02 | 29.50 | 22.85 | 0.426010E+09 | 545.25 | 05-JUN-09:00 | 29.50 | 22.85 |
July | 0.975426E+10 | 16417.45 | 04-JUL-09:32 | 26.47 | 23.26 | 0.395571E+09 | 545.42 | 05-JUL-09:30 | 29.15 | 23.71 |
August | 0.101731E+11 | 11289.96 | 27-AUG-09:43 | 26.83 | 21.78 | 0.443843E+09 | 545.37 | 07-AUG-09:00 | 26.83 | 21.78 |
September | 0.685713E+10 | 14803.05 | 24-SEP-09:43 | 25.63 | 18.45 | 0.391710E+09 | 545.44 | 08-SEP-09:00 | 25.63 | 18.45 |
October | 0.516258E+10 | 7662.42 | 10-OCT-09:30 | 21.95 | 18.16 | 0.396061E+09 | 544.95 | 05-OCT-09:00 | 21.95 | 18.16 |
November | 0.391683E+10 | 5862.82 | 06-NOV-09:30 | 13.30 | 11.71 | 0.380498E+09 | 544.96 | 06-NOV-10:09 | 14.87 | 12.62 |
December | 0.319955E+10 | 3611.55 | 13-DEC-04:02 | 17.20 | 15.19 | 0.351224E+09 | 544.97 | 11-DEC-10:00 | 17.20 | 15.19 |
Annual Sum or Average | 0.718574E+11 | 0.468978E+10 | ||||||||
Minimum of Months | 0.236632E+10 | 3099.59 | 10.00 | 5.46 | 0.326240E+09 | 534.14 | 14.40 | 11.88 | ||
Maximum of Months | 0.101731E+11 | 16417.45 | 29.50 | 23.26 | 0.443843E+09 | 553.76 | 29.50 | 23.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415955E+10 | 11186.28 | 26-JAN-13:40 | 0.00 | -3.9 | 0.567142E+09 | 845.64 | 10-JAN-14:09 | 0.00 | -3.9 |
February | 0.519165E+10 | 16062.58 | 26-FEB-12:43 | 23.72 | 12.50 | 0.529851E+09 | 847.14 | 02-FEB-14:30 | 23.72 | 12.50 |
March | 0.830328E+10 | 13802.25 | 30-MAR-13:30 | 27.25 | 18.02 | 0.672253E+09 | 847.00 | 30-MAR-13:50 | 27.62 | 17.92 |
April | 0.909990E+10 | 13594.02 | 17-APR-14:00 | 28.90 | 16.63 | 0.604293E+09 | 875.51 | 17-APR-13:20 | 28.90 | 16.63 |
May | 0.900199E+10 | 14006.53 | 30-MAY-03:02 | 20.00 | 17.77 | 0.660333E+09 | 863.81 | 16-MAY-13:39 | 20.00 | 17.77 |
June | 0.113926E+11 | 17343.17 | 25-JUN-16:41 | 32.88 | 22.29 | 0.661224E+09 | 845.65 | 09-JUN-09:00 | 32.88 | 22.29 |
July | 0.127532E+11 | 18627.18 | 09-JUL-16:01 | 33.80 | 23.13 | 0.615088E+09 | 846.00 | 31-JUL-13:00 | 30.60 | 24.81 |
August | 0.152465E+11 | 15137.59 | 27-AUG-15:02 | 31.70 | 21.48 | 0.690760E+09 | 846.52 | 14-AUG-13:20 | 31.70 | 21.48 |
September | 0.103977E+11 | 19428.00 | 24-SEP-13:02 | 28.80 | 19.88 | 0.611569E+09 | 846.72 | 22-SEP-13:39 | 28.80 | 19.88 |
October | 0.938522E+10 | 19828.97 | 08-OCT-14:02 | 26.78 | 18.72 | 0.624396E+09 | 865.23 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.753488E+10 | 19614.22 | 11-NOV-13:13 | 21.10 | 11.68 | 0.614650E+09 | 846.07 | 14-NOV-14:50 | 19.72 | 9.25 |
December | 0.621354E+10 | 13771.07 | 10-DEC-12:53 | 15.60 | 7.72 | 0.581291E+09 | 846.16 | 12-DEC-14:20 | 22.80 | 16.78 |
Annual Sum or Average | 0.108680E+12 | 0.743285E+10 | ||||||||
Minimum of Months | 0.415955E+10 | 11186.28 | 0.00 | -3.9 | 0.529851E+09 | 845.64 | 0.00 | -3.9 | ||
Maximum of Months | 0.152465E+11 | 19828.97 | 33.80 | 23.13 | 0.690760E+09 | 875.51 | 32.88 | 24.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361917E+10 | 4773.26 | 20-JAN-16:30 | 16.95 | 12.13 | 0.347202E+09 | 544.93 | 20-JAN-14:00 | 16.95 | 12.13 |
February | 0.462683E+10 | 9235.97 | 27-FEB-16:40 | 22.40 | 11.40 | 0.340664E+09 | 544.96 | 22-FEB-14:09 | 22.40 | 11.40 |
March | 0.831917E+10 | 15878.61 | 30-MAR-05:03 | 17.80 | 16.10 | 0.440936E+09 | 544.99 | 08-MAR-10:09 | 17.80 | 16.10 |
April | 0.107993E+11 | 20634.32 | 09-APR-16:32 | 21.70 | 10.73 | 0.395561E+09 | 552.98 | 18-APR-13:39 | 27.40 | 16.07 |
May | 0.898760E+10 | 16209.18 | 29-MAY-17:53 | 29.40 | 20.07 | 0.426534E+09 | 554.72 | 18-MAY-13:20 | 29.40 | 20.07 |
June | 0.121407E+11 | 22469.47 | 25-JUN-16:01 | 33.22 | 22.10 | 0.427256E+09 | 544.97 | 09-JUN-09:00 | 33.22 | 22.10 |
July | 0.141034E+11 | 22967.04 | 04-JUL-17:31 | 30.40 | 22.45 | 0.397397E+09 | 544.94 | 31-JUL-13:00 | 30.60 | 24.81 |
August | 0.168533E+11 | 21925.47 | 13-AUG-16:22 | 30.55 | 22.29 | 0.445974E+09 | 544.95 | 10-AUG-13:39 | 30.55 | 22.29 |
September | 0.871890E+10 | 20567.27 | 24-SEP-16:22 | 28.35 | 19.92 | 0.394031E+09 | 544.98 | 22-SEP-13:30 | 28.35 | 19.92 |
October | 0.752920E+10 | 20561.19 | 08-OCT-15:22 | 27.20 | 18.90 | 0.404662E+09 | 544.95 | 04-OCT-13:00 | 27.20 | 18.90 |
November | 0.653904E+10 | 12136.88 | 04-NOV-03:02 | 17.20 | 15.81 | 0.399807E+09 | 544.98 | 16-NOV-10:09 | 10.68 | 10.03 |
December | 0.583082E+10 | 16398.99 | 13-DEC-06:03 | 16.70 | 15.65 | 0.385104E+09 | 544.97 | 11-DEC-10:00 | 16.70 | 15.65 |
Annual Sum or Average | 0.108067E+12 | 0.480513E+10 | ||||||||
Minimum of Months | 0.361917E+10 | 4773.26 | 16.70 | 10.73 | 0.340664E+09 | 544.93 | 10.68 | 10.03 | ||
Maximum of Months | 0.168533E+11 | 22967.04 | 33.22 | 22.45 | 0.445974E+09 | 554.72 | 33.22 | 24.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.787259E+09 | 2536.78 | 20-JAN-15:50 | 17.30 | 12.80 | 0.477453E+09 | 783.58 | 20-JAN-14:00 | 17.30 | 12.80 |
February | 0.158744E+10 | 4205.37 | 28-FEB-15:00 | 25.00 | 13.71 | 0.458326E+09 | 845.61 | 28-FEB-14:09 | 25.00 | 13.71 |
March | 0.367825E+10 | 6423.60 | 30-MAR-16:00 | 27.80 | 17.47 | 0.619872E+09 | 845.60 | 29-MAR-13:09 | 27.80 | 17.47 |
April | 0.454666E+10 | 7562.71 | 12-APR-14:40 | 28.50 | 16.95 | 0.584158E+09 | 850.32 | 14-APR-13:50 | 27.12 | 15.42 |
May | 0.669695E+10 | 8534.72 | 30-MAY-15:00 | 30.60 | 21.44 | 0.657633E+09 | 862.43 | 15-MAY-13:39 | 30.60 | 21.44 |
June | 0.912169E+10 | 15148.92 | 25-JUN-16:41 | 32.88 | 22.29 | 0.661394E+09 | 850.16 | 02-JUN-13:50 | 32.88 | 22.29 |
July | 0.952975E+10 | 12120.27 | 15-JUL-03:02 | 23.90 | 20.50 | 0.615239E+09 | 845.60 | 03-JUL-13:30 | 23.90 | 20.50 |
August | 0.997690E+10 | 13329.16 | 06-AUG-17:01 | 32.20 | 23.07 | 0.690766E+09 | 845.62 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.635452E+10 | 11099.43 | 27-SEP-05:03 | 22.80 | 20.09 | 0.607472E+09 | 845.64 | 22-SEP-13:50 | 22.80 | 20.09 |
October | 0.403993E+10 | 6254.82 | 02-OCT-14:40 | 26.70 | 20.10 | 0.584428E+09 | 845.61 | 05-OCT-13:09 | 20.00 | 14.95 |
November | 0.266585E+10 | 3748.10 | 03-NOV-14:00 | 21.70 | 17.40 | 0.536482E+09 | 845.61 | 03-NOV-13:39 | 21.70 | 17.40 |
December | 0.157788E+10 | 3251.69 | 13-DEC-06:03 | 16.70 | 15.65 | 0.479827E+09 | 845.60 | 13-DEC-14:09 | 18.30 | 16.86 |
Annual Sum or Average | 0.605631E+11 | 0.697305E+10 | ||||||||
Minimum of Months | 0.787259E+09 | 2536.78 | 16.70 | 12.80 | 0.458326E+09 | 783.58 | 17.30 | 12.80 | ||
Maximum of Months | 0.997690E+10 | 15148.92 | 32.88 | 23.07 | 0.690766E+09 | 862.43 | 32.88 | 22.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.982459E+09 | 2742.90 | 26-JAN-13:38 | 0.00 | -3.9 | 0.224683E+09 | 456.90 | 31-JAN-16:00 | 19.40 | 13.37 |
February | 0.172928E+10 | 4633.63 | 02-FEB-11:45 | 0.92 | -1.6 | 0.219298E+09 | 521.21 | 28-FEB-11:09 | 20.87 | 12.02 |
March | 0.379110E+10 | 5573.89 | 14-MAR-11:00 | 20.60 | 15.46 | 0.295188E+09 | 522.63 | 07-MAR-09:39 | 20.60 | 15.46 |
April | 0.494101E+10 | 8472.37 | 17-APR-10:10 | 23.27 | 15.57 | 0.279654E+09 | 532.14 | 12-APR-14:00 | 23.27 | 15.57 |
May | 0.662489E+10 | 16566.35 | 07-MAY-09:32 | 24.43 | 19.78 | 0.309881E+09 | 532.50 | 15-MAY-14:09 | 28.30 | 17.25 |
June | 0.824629E+10 | 17090.83 | 25-JUN-10:02 | 29.50 | 22.85 | 0.312954E+09 | 524.26 | 02-JUN-12:39 | 29.50 | 22.85 |
July | 0.866361E+10 | 17120.02 | 04-JUL-09:32 | 26.47 | 23.26 | 0.291769E+09 | 521.75 | 07-JUL-10:50 | 32.02 | 24.15 |
August | 0.881585E+10 | 17004.03 | 06-AUG-11:02 | 30.68 | 23.75 | 0.326616E+09 | 521.84 | 01-AUG-10:50 | 30.68 | 23.75 |
September | 0.620773E+10 | 14463.72 | 24-SEP-10:13 | 26.67 | 18.72 | 0.285219E+09 | 521.22 | 15-SEP-12:20 | 26.67 | 18.72 |
October | 0.413295E+10 | 6658.27 | 11-OCT-10:20 | 23.73 | 19.29 | 0.276500E+09 | 521.21 | 05-OCT-12:09 | 23.73 | 19.29 |
November | 0.279671E+10 | 3842.96 | 06-NOV-09:50 | 14.03 | 12.24 | 0.251225E+09 | 521.19 | 06-NOV-09:00 | 14.40 | 12.50 |
December | 0.173012E+10 | 3836.87 | 01-DEC-10:45 | 3.95 | 0.75 | 0.225269E+09 | 482.51 | 13-DEC-11:00 | 20.00 | 17.41 |
Annual Sum or Average | 0.586620E+11 | 0.329826E+10 | ||||||||
Minimum of Months | 0.982459E+09 | 2742.90 | 0.00 | -3.9 | 0.219298E+09 | 456.90 | 14.40 | 12.02 | ||
Maximum of Months | 0.881585E+10 | 17120.02 | 30.68 | 23.75 | 0.326616E+09 | 532.50 | 32.02 | 24.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299807E+10 | 13959.58 | 26-JAN-13:38 | 0.00 | -3.9 | 0.539137E+09 | 879.01 | 05-JAN-11:00 | 0.00 | -3.9 |
February | 0.384332E+10 | 17422.17 | 26-FEB-13:03 | 23.98 | 12.59 | 0.504068E+09 | 858.05 | 03-FEB-14:39 | 23.98 | 12.59 |
March | 0.641754E+10 | 13246.66 | 30-MAR-13:30 | 27.25 | 18.02 | 0.652091E+09 | 846.84 | 30-MAR-13:00 | 27.80 | 17.87 |
April | 0.656460E+10 | 14036.06 | 17-APR-15:00 | 28.90 | 16.41 | 0.593936E+09 | 876.12 | 14-APR-13:50 | 28.90 | 16.41 |
May | 0.779806E+10 | 11273.90 | 15-MAY-14:10 | 28.30 | 17.25 | 0.656589E+09 | 867.68 | 15-MAY-13:39 | 28.30 | 17.25 |
June | 0.948210E+10 | 17362.02 | 25-JUN-16:41 | 32.88 | 22.29 | 0.660313E+09 | 851.11 | 02-JUN-13:50 | 32.88 | 22.29 |
July | 0.101214E+11 | 13970.14 | 15-JUL-03:02 | 23.90 | 20.50 | 0.614990E+09 | 845.76 | 14-JUL-13:39 | 23.90 | 20.50 |
August | 0.118917E+11 | 18216.02 | 06-AUG-13:42 | 32.70 | 23.92 | 0.691271E+09 | 864.52 | 25-AUG-13:00 | 31.10 | 18.60 |
September | 0.920950E+10 | 18435.74 | 24-SEP-12:53 | 28.90 | 19.89 | 0.609237E+09 | 863.14 | 22-SEP-13:39 | 28.90 | 19.89 |
October | 0.787937E+10 | 19076.74 | 09-OCT-14:42 | 27.70 | 19.55 | 0.611522E+09 | 873.05 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.584994E+10 | 18440.17 | 11-NOV-13:43 | 21.10 | 11.67 | 0.593648E+09 | 845.94 | 06-NOV-14:20 | 21.10 | 11.67 |
December | 0.438784E+10 | 11380.90 | 08-DEC-14:10 | 12.80 | 5.52 | 0.549948E+09 | 848.89 | 07-DEC-10:00 | 12.80 | 5.52 |
Annual Sum or Average | 0.864434E+11 | 0.727675E+10 | ||||||||
Minimum of Months | 0.299807E+10 | 11273.90 | 0.00 | -3.9 | 0.504068E+09 | 845.76 | 0.00 | -3.9 | ||
Maximum of Months | 0.118917E+11 | 19076.74 | 32.88 | 23.92 | 0.691271E+09 | 879.01 | 32.88 | 22.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124280E+10 | 3545.37 | 05-JAN-16:33 | 1.47 | -3.7 | 0.310690E+09 | 494.44 | 20-JAN-16:49 | 16.78 | 11.69 |
February | 0.202275E+10 | 6558.40 | 27-FEB-17:00 | 22.20 | 11.44 | 0.296799E+09 | 544.94 | 28-FEB-14:39 | 25.00 | 13.71 |
March | 0.440252E+10 | 9128.98 | 30-MAR-16:00 | 27.80 | 17.47 | 0.396248E+09 | 544.94 | 29-MAR-13:09 | 27.80 | 17.47 |
April | 0.537510E+10 | 17015.57 | 09-APR-17:01 | 21.60 | 10.86 | 0.373824E+09 | 549.12 | 14-APR-13:50 | 27.12 | 15.42 |
May | 0.678685E+10 | 17705.99 | 21-MAY-17:42 | 25.78 | 19.40 | 0.419508E+09 | 558.34 | 15-MAY-13:39 | 25.78 | 19.40 |
June | 0.838579E+10 | 18723.39 | 25-JUN-16:41 | 32.88 | 22.29 | 0.425044E+09 | 545.38 | 02-JUN-13:50 | 32.88 | 22.29 |
July | 0.886677E+10 | 18992.51 | 04-JUL-17:31 | 30.40 | 22.45 | 0.395995E+09 | 544.94 | 07-JUL-09:20 | 29.97 | 24.13 |
August | 0.947011E+10 | 18642.02 | 06-AUG-17:01 | 32.20 | 23.07 | 0.445302E+09 | 544.95 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.638115E+10 | 12086.02 | 27-SEP-05:03 | 22.80 | 20.09 | 0.387641E+09 | 544.96 | 22-SEP-13:50 | 22.80 | 20.09 |
October | 0.449813E+10 | 9329.71 | 11-OCT-16:00 | 26.10 | 17.12 | 0.371308E+09 | 544.94 | 16-OCT-13:50 | 24.90 | 19.07 |
November | 0.314409E+10 | 6016.06 | 06-NOV-16:00 | 20.60 | 10.48 | 0.344765E+09 | 544.88 | 06-NOV-14:00 | 20.60 | 10.48 |
December | 0.206152E+10 | 3710.80 | 13-DEC-06:03 | 16.70 | 15.65 | 0.313102E+09 | 542.28 | 12-DEC-14:00 | 16.70 | 15.65 |
Annual Sum or Average | 0.626376E+11 | 0.448023E+10 | ||||||||
Minimum of Months | 0.124280E+10 | 3545.37 | 1.47 | -3.7 | 0.296799E+09 | 494.44 | 16.70 | 10.48 | ||
Maximum of Months | 0.947011E+10 | 18992.51 | 32.88 | 23.07 | 0.445302E+09 | 558.34 | 32.88 | 24.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.464405E+09 | 2784.04 | 20-JAN-17:00 | 16.70 | 11.48 | 0.469747E+09 | 755.82 | 20-JAN-14:00 | 16.70 | 11.48 |
February | 0.114700E+10 | 3669.65 | 28-FEB-15:40 | 23.87 | 12.92 | 0.442768E+09 | 845.60 | 28-FEB-14:00 | 23.87 | 12.92 |
March | 0.325773E+10 | 7047.72 | 30-MAR-16:00 | 27.80 | 17.47 | 0.582821E+09 | 845.60 | 28-MAR-13:09 | 27.80 | 17.47 |
April | 0.441773E+10 | 7312.59 | 18-APR-14:20 | 26.67 | 16.26 | 0.561372E+09 | 845.64 | 12-APR-13:30 | 26.67 | 16.26 |
May | 0.690883E+10 | 9408.12 | 30-MAY-15:00 | 30.60 | 21.44 | 0.648727E+09 | 845.66 | 19-MAY-13:50 | 30.60 | 21.44 |
June | 0.976551E+10 | 13531.80 | 26-JUN-05:02 | 23.30 | 21.67 | 0.659802E+09 | 845.64 | 02-JUN-13:00 | 23.30 | 21.67 |
July | 0.104047E+11 | 17321.87 | 23-JUL-17:01 | 29.82 | 23.13 | 0.614638E+09 | 845.60 | 03-JUL-13:20 | 29.82 | 23.13 |
August | 0.108323E+11 | 17796.77 | 06-AUG-17:01 | 32.20 | 23.07 | 0.690454E+09 | 846.54 | 25-AUG-13:50 | 30.92 | 18.65 |
September | 0.646571E+10 | 12892.92 | 27-SEP-05:03 | 22.80 | 20.09 | 0.599106E+09 | 845.64 | 22-SEP-13:00 | 22.80 | 20.09 |
October | 0.355866E+10 | 6564.27 | 02-OCT-14:50 | 26.70 | 20.16 | 0.553587E+09 | 845.60 | 19-OCT-13:09 | 22.48 | 19.30 |
November | 0.206672E+10 | 3619.81 | 04-NOV-05:02 | 16.60 | 15.28 | 0.499091E+09 | 839.58 | 03-NOV-13:00 | 16.60 | 15.28 |
December | 0.928658E+09 | 3042.60 | 13-DEC-15:10 | 18.12 | 16.87 | 0.460319E+09 | 812.91 | 13-DEC-14:00 | 18.12 | 16.87 |
Annual Sum or Average | 0.602179E+11 | 0.678243E+10 | ||||||||
Minimum of Months | 0.464405E+09 | 2784.04 | 16.60 | 11.48 | 0.442768E+09 | 755.82 | 16.60 | 11.48 | ||
Maximum of Months | 0.108323E+11 | 17796.77 | 32.20 | 23.13 | 0.690454E+09 | 846.54 | 30.92 | 23.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.546216E+09 | 2421.86 | 31-JAN-17:00 | 19.40 | 13.37 | 0.302121E+09 | 462.34 | 31-JAN-14:00 | 19.40 | 13.37 |
February | 0.131196E+10 | 3421.08 | 28-FEB-15:00 | 25.00 | 13.71 | 0.292285E+09 | 544.94 | 28-FEB-14:30 | 25.00 | 13.71 |
March | 0.330507E+10 | 5339.66 | 30-MAR-11:00 | 22.20 | 17.83 | 0.391159E+09 | 544.97 | 08-MAR-10:00 | 22.20 | 17.83 |
April | 0.472023E+10 | 9781.82 | 16-APR-09:53 | 22.20 | 14.59 | 0.375758E+09 | 544.97 | 12-APR-13:30 | 22.20 | 14.59 |
May | 0.680887E+10 | 15897.72 | 07-MAY-09:53 | 25.00 | 20.03 | 0.420163E+09 | 545.00 | 11-MAY-09:00 | 17.20 | 13.27 |
June | 0.883041E+10 | 16865.62 | 04-JUN-11:23 | 29.40 | 19.71 | 0.425847E+09 | 545.20 | 05-JUN-09:00 | 28.90 | 20.65 |
July | 0.940981E+10 | 17123.55 | 23-JUL-08:22 | 25.30 | 22.43 | 0.395462E+09 | 545.28 | 05-JUL-09:39 | 25.30 | 22.43 |
August | 0.958510E+10 | 17604.16 | 06-AUG-11:02 | 30.68 | 23.75 | 0.444556E+09 | 545.26 | 07-AUG-09:00 | 29.40 | 23.41 |
September | 0.631132E+10 | 10041.68 | 08-SEP-09:40 | 26.83 | 22.22 | 0.386054E+09 | 545.24 | 08-SEP-09:50 | 27.02 | 22.34 |
October | 0.360953E+10 | 6420.15 | 11-OCT-10:30 | 24.20 | 19.54 | 0.369491E+09 | 544.95 | 20-OCT-13:09 | 18.22 | 11.22 |
November | 0.214872E+10 | 3377.36 | 04-NOV-05:02 | 16.60 | 15.28 | 0.325888E+09 | 531.64 | 06-NOV-10:00 | 17.20 | 13.02 |
December | 0.107384E+10 | 2657.70 | 13-DEC-15:10 | 18.12 | 16.87 | 0.296877E+09 | 494.97 | 13-DEC-14:00 | 18.12 | 16.87 |
Annual Sum or Average | 0.576611E+11 | 0.442566E+10 | ||||||||
Minimum of Months | 0.546216E+09 | 2421.86 | 16.60 | 13.37 | 0.292285E+09 | 462.34 | 17.20 | 11.22 | ||
Maximum of Months | 0.958510E+10 | 17604.16 | 30.68 | 23.75 | 0.444556E+09 | 545.28 | 29.40 | 23.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219310E+10 | 7336.26 | 11-JAN-14:50 | 6.70 | 2.05 | 0.517245E+09 | 845.64 | 27-JAN-14:39 | 3.53 | -2.0 |
February | 0.303194E+10 | 13498.14 | 21-FEB-14:30 | 22.25 | 10.82 | 0.484946E+09 | 845.79 | 21-FEB-14:00 | 22.80 | 11.27 |
March | 0.564130E+10 | 13794.26 | 30-MAR-13:50 | 27.62 | 17.92 | 0.624355E+09 | 845.74 | 30-MAR-13:00 | 27.80 | 17.87 |
April | 0.631444E+10 | 15200.04 | 17-APR-14:05 | 28.90 | 16.59 | 0.576373E+09 | 885.59 | 17-APR-13:00 | 28.90 | 16.59 |
May | 0.803122E+10 | 11023.85 | 30-MAY-14:30 | 30.60 | 21.24 | 0.647771E+09 | 850.47 | 19-MAY-13:39 | 30.60 | 21.24 |
June | 0.101650E+11 | 14042.79 | 29-JUN-05:03 | 22.20 | 20.68 | 0.657808E+09 | 845.66 | 02-JUN-13:00 | 22.20 | 20.68 |
July | 0.110396E+11 | 19390.10 | 23-JUL-17:01 | 29.82 | 23.13 | 0.613911E+09 | 845.62 | 18-JUL-13:20 | 29.82 | 23.13 |
August | 0.128680E+11 | 20533.56 | 06-AUG-13:42 | 32.70 | 23.92 | 0.690827E+09 | 852.95 | 25-AUG-13:00 | 31.10 | 18.60 |
September | 0.935621E+10 | 20628.08 | 24-SEP-14:32 | 28.70 | 20.36 | 0.603140E+09 | 849.16 | 22-SEP-13:50 | 28.70 | 20.36 |
October | 0.710447E+10 | 21119.79 | 09-OCT-14:32 | 27.60 | 19.53 | 0.591961E+09 | 850.55 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.477254E+10 | 17611.28 | 11-NOV-13:43 | 21.10 | 11.67 | 0.560496E+09 | 845.80 | 06-NOV-14:00 | 21.10 | 11.67 |
December | 0.326162E+10 | 9880.06 | 12-DEC-13:50 | 22.52 | 17.00 | 0.521502E+09 | 846.60 | 04-DEC-14:20 | 22.52 | 17.00 |
Annual Sum or Average | 0.837795E+11 | 0.709033E+10 | ||||||||
Minimum of Months | 0.219310E+10 | 7336.26 | 6.70 | 2.05 | 0.484946E+09 | 845.62 | 3.53 | -2.0 | ||
Maximum of Months | 0.128680E+11 | 21119.79 | 32.70 | 23.92 | 0.690827E+09 | 885.59 | 31.10 | 23.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.877709E+09 | 3048.51 | 20-JAN-16:40 | 16.87 | 11.91 | 0.304959E+09 | 484.10 | 20-JAN-16:49 | 16.78 | 11.69 |
February | 0.159166E+10 | 6289.79 | 27-FEB-17:00 | 22.20 | 11.44 | 0.288680E+09 | 544.48 | 28-FEB-14:00 | 25.00 | 13.71 |
March | 0.393018E+10 | 9560.51 | 30-MAR-16:00 | 27.80 | 17.47 | 0.378296E+09 | 544.93 | 09-MAR-14:50 | 27.80 | 17.47 |
April | 0.520853E+10 | 17582.73 | 09-APR-17:33 | 21.30 | 11.08 | 0.361176E+09 | 544.97 | 12-APR-13:30 | 28.35 | 16.82 |
May | 0.698372E+10 | 19310.26 | 21-MAY-17:42 | 25.78 | 19.40 | 0.412545E+09 | 552.32 | 16-MAY-15:00 | 25.78 | 19.40 |
June | 0.887383E+10 | 20179.44 | 11-JUN-17:12 | 32.20 | 20.99 | 0.422986E+09 | 544.97 | 02-JUN-13:00 | 32.20 | 20.99 |
July | 0.955421E+10 | 20520.56 | 23-JUL-17:01 | 29.82 | 23.13 | 0.394899E+09 | 544.94 | 03-JUL-13:09 | 29.82 | 23.13 |
August | 0.101722E+11 | 20643.38 | 06-AUG-17:01 | 32.20 | 23.07 | 0.444624E+09 | 547.14 | 25-AUG-13:50 | 30.92 | 18.65 |
September | 0.649339E+10 | 15117.86 | 03-SEP-15:32 | 29.80 | 23.28 | 0.381436E+09 | 544.96 | 22-SEP-13:00 | 26.70 | 17.59 |
October | 0.405670E+10 | 10863.14 | 09-OCT-16:33 | 27.07 | 19.44 | 0.356762E+09 | 544.93 | 19-OCT-13:09 | 22.48 | 19.30 |
November | 0.255680E+10 | 5661.05 | 06-NOV-16:10 | 20.32 | 10.34 | 0.327183E+09 | 544.82 | 06-NOV-14:00 | 20.32 | 10.34 |
December | 0.143453E+10 | 3192.92 | 12-DEC-14:50 | 22.80 | 16.32 | 0.301938E+09 | 522.11 | 12-DEC-14:00 | 22.80 | 16.17 |
Annual Sum or Average | 0.617335E+11 | 0.437548E+10 | ||||||||
Minimum of Months | 0.877709E+09 | 3048.51 | 16.87 | 10.34 | 0.288680E+09 | 484.10 | 16.78 | 10.34 | ||
Maximum of Months | 0.101722E+11 | 20643.38 | 32.20 | 23.28 | 0.444624E+09 | 552.32 | 32.20 | 23.13 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108382E+10 | 4952.59 | 02-JAN-06:08 | 3.30 | 2.54 | 0.00 | 0.00 | 01-JAN-00:10 | 3.30 | 2.54 |
February | 0.209277E+10 | 5638.68 | 21-FEB-06:15 | 5.60 | 3.82 | 0.00 | 0.00 | 01-FEB-00:10 | 5.60 | 3.82 |
March | 0.515601E+10 | 7023.93 | 13-MAR-05:15 | 6.70 | 2.88 | 0.00 | 0.00 | 01-MAR-00:10 | 6.70 | 2.88 |
April | 0.649359E+10 | 8310.96 | 17-APR-13:10 | 27.98 | 16.86 | 0.00 | 0.00 | 01-APR-00:10 | 27.98 | 16.86 |
May | 0.751225E+10 | 10962.25 | 30-MAY-05:15 | 19.07 | 17.52 | 0.00 | 0.00 | 01-MAY-00:10 | 19.07 | 17.52 |
June | 0.971613E+10 | 11125.54 | 26-JUN-05:15 | 23.30 | 21.67 | 0.00 | 0.00 | 01-JUN-00:10 | 23.30 | 21.67 |
July | 0.106680E+11 | 10602.35 | 03-JUL-05:15 | 17.97 | 16.43 | 0.00 | 0.00 | 01-JUL-00:10 | 17.97 | 16.43 |
August | 0.121473E+11 | 13408.52 | 14-AUG-05:15 | 23.30 | 20.62 | 0.00 | 0.00 | 01-AUG-00:10 | 23.30 | 20.62 |
September | 0.800264E+10 | 12465.49 | 05-SEP-05:13 | 21.70 | 20.50 | 0.00 | 0.00 | 01-SEP-00:10 | 21.70 | 20.50 |
October | 0.593327E+10 | 10779.22 | 10-OCT-05:13 | 15.73 | 14.81 | 0.00 | 0.00 | 01-OCT-00:10 | 15.73 | 14.81 |
November | 0.435774E+10 | 8321.76 | 06-NOV-06:15 | 9.23 | 8.65 | 0.00 | 0.00 | 01-NOV-00:10 | 9.23 | 8.65 |
December | 0.271026E+10 | 6830.15 | 13-DEC-06:13 | 16.70 | 15.65 | 0.00 | 0.00 | 01-DEC-00:10 | 16.70 | 15.65 |
Annual Sum or Average | 0.758738E+11 | 0.00 | ||||||||
Minimum of Months | 0.108382E+10 | 4952.59 | 3.30 | 2.54 | 0.00 | 0.00 | 3.30 | 2.54 | ||
Maximum of Months | 0.121473E+11 | 13408.52 | 27.98 | 21.67 | 0.00 | 0.00 | 27.98 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306373E+09 | 5428.65 | 27-JAN-05:01 | -5.7 | -7.2 | 0.00 | 0.00 | 01-JAN-00:10 | -5.7 | -7.2 |
February | 0.896636E+09 | 7959.34 | 12-FEB-05:22 | -11.9 | -13.2 | 0.00 | 0.00 | 01-FEB-00:10 | -11.9 | -13.2 |
March | 0.278789E+10 | 5057.09 | 15-MAR-05:10 | 8.22 | 4.19 | 0.00 | 0.00 | 01-MAR-00:10 | 8.22 | 4.19 |
April | 0.414831E+10 | 6190.98 | 17-APR-14:55 | 28.90 | 16.41 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 16.41 |
May | 0.593409E+10 | 8380.49 | 30-MAY-05:03 | 18.68 | 17.36 | 0.00 | 0.00 | 01-MAY-00:10 | 18.68 | 17.36 |
June | 0.795831E+10 | 8555.02 | 26-JUN-05:02 | 23.30 | 21.67 | 0.00 | 0.00 | 01-JUN-00:10 | 23.30 | 21.67 |
July | 0.845242E+10 | 8253.65 | 24-JUL-05:03 | 20.60 | 19.50 | 0.00 | 0.00 | 01-JUL-00:10 | 20.60 | 19.50 |
August | 0.924996E+10 | 8598.77 | 30-AUG-05:15 | 20.60 | 19.07 | 0.00 | 0.00 | 01-AUG-00:10 | 20.60 | 19.07 |
September | 0.645393E+10 | 7897.84 | 05-SEP-05:13 | 21.70 | 20.50 | 0.00 | 0.00 | 01-SEP-00:10 | 21.70 | 20.50 |
October | 0.367909E+10 | 5509.33 | 11-OCT-05:15 | 18.53 | 16.62 | 0.00 | 0.00 | 01-OCT-00:10 | 18.53 | 16.62 |
November | 0.188080E+10 | 4766.87 | 21-NOV-05:01 | -2.3 | -3.6 | 0.00 | 0.00 | 01-NOV-00:10 | -2.3 | -3.6 |
December | 0.850935E+09 | 5236.77 | 18-DEC-05:01 | -5.0 | -6.8 | 0.00 | 0.00 | 01-DEC-00:10 | -5.0 | -6.8 |
Annual Sum or Average | 0.525987E+11 | 0.00 | ||||||||
Minimum of Months | 0.306373E+09 | 4766.87 | -11.9 | -13.2 | 0.00 | 0.00 | -11.9 | -13.2 | ||
Maximum of Months | 0.924996E+10 | 8598.77 | 28.90 | 21.67 | 0.00 | 0.00 | 28.90 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123850E+09 | 2134.95 | 31-JAN-17:30 | 19.15 | 13.30 | 0.00 | 0.00 | 01-JAN-00:10 | 19.15 | 13.30 |
February | 0.763667E+09 | 7167.35 | 28-FEB-16:00 | 23.30 | 12.53 | 0.00 | 0.00 | 01-FEB-00:10 | 23.30 | 12.53 |
March | 0.309008E+10 | 13968.58 | 30-MAR-15:30 | 27.80 | 17.27 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.27 |
April | 0.593093E+10 | 18712.52 | 17-APR-14:55 | 28.90 | 16.41 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 16.41 |
May | 0.973675E+10 | 19033.05 | 16-MAY-15:23 | 29.40 | 17.75 | 0.00 | 0.00 | 01-MAY-00:10 | 29.40 | 17.75 |
June | 0.137442E+11 | 19401.19 | 12-JUN-15:00 | 33.30 | 22.72 | 0.00 | 0.00 | 01-JUN-00:10 | 33.30 | 22.72 |
July | 0.145465E+11 | 21473.12 | 07-JUL-15:10 | 35.10 | 23.86 | 0.00 | 0.00 | 01-JUL-00:10 | 35.10 | 23.86 |
August | 0.153230E+11 | 20461.65 | 01-AUG-14:20 | 34.27 | 23.72 | 0.00 | 0.00 | 01-AUG-00:10 | 34.27 | 23.72 |
September | 0.838100E+10 | 16953.81 | 06-SEP-14:40 | 29.97 | 23.06 | 0.00 | 0.00 | 01-SEP-00:10 | 29.97 | 23.06 |
October | 0.385387E+10 | 12443.83 | 10-OCT-14:50 | 28.98 | 20.71 | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 20.71 |
November | 0.122420E+10 | 5739.47 | 06-NOV-15:10 | 20.60 | 10.48 | 0.00 | 0.00 | 01-NOV-00:10 | 20.60 | 10.48 |
December | 0.261990E+09 | 4145.75 | 12-DEC-14:40 | 22.80 | 16.47 | 0.00 | 0.00 | 01-DEC-00:10 | 22.80 | 16.47 |
Annual Sum or Average | 0.769800E+11 | 0.00 | ||||||||
Minimum of Months | 0.123850E+09 | 2134.95 | 19.15 | 10.48 | 0.00 | 0.00 | 19.15 | 10.48 | ||
Maximum of Months | 0.153230E+11 | 21473.12 | 35.10 | 23.86 | 0.00 | 0.00 | 35.10 | 23.86 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291193E+10 | 1859.89 | 23-JAN-17:00 | 10.00 | 3.54 | 95230847.30 | 126.84 | 19-JAN-10:30 | 10.00 | 3.54 |
February | 0.776375E+10 | 3895.39 | 24-FEB-17:50 | 15.18 | 6.70 | 86397290.95 | 126.84 | 17-FEB-14:00 | 15.18 | 6.70 |
March | 0.144246E+11 | 7173.25 | 31-MAR-24:00 | 12.10 | 7.93 | 0.103239E+09 | 126.84 | 28-MAR-09:09 | 12.10 | 7.93 |
April | 0.189561E+11 | 7885.44 | 09-APR-18:13 | 19.80 | 10.92 | 91606058.19 | 126.83 | 03-APR-09:39 | 19.80 | 10.92 |
May | 0.455249E+10 | 3499.96 | 31-MAY-24:00 | 21.00 | 18.72 | 99242597.79 | 126.86 | 01-MAY-13:09 | 21.00 | 18.72 |
June | 0.939732E+10 | 5356.39 | 30-JUN-24:00 | 22.30 | 21.46 | 98974624.41 | 126.86 | 23-JUN-09:50 | 22.30 | 21.46 |
July | 0.147720E+11 | 7236.04 | 31-JUL-23:53 | 25.20 | 21.98 | 91891602.75 | 126.85 | 26-JUL-09:09 | 25.20 | 21.98 |
August | 0.198827E+11 | 7861.64 | 13-AUG-19:32 | 29.60 | 21.73 | 0.104648E+09 | 134.91 | 02-AUG-13:00 | 29.60 | 21.73 |
September | 0.446834E+10 | 3247.60 | 30-SEP-24:00 | 16.80 | 15.75 | 91612159.65 | 126.86 | 01-SEP-13:00 | 16.80 | 15.75 |
October | 0.945419E+10 | 5166.67 | 31-OCT-24:00 | 9.70 | 6.26 | 95238525.68 | 126.86 | 18-OCT-09:00 | 9.70 | 6.26 |
November | 0.138916E+11 | 5914.96 | 06-NOV-17:00 | 18.90 | 9.61 | 94302033.48 | 126.84 | 02-NOV-09:20 | 18.90 | 9.61 |
December | 0.191106E+11 | 7699.27 | 19-DEC-17:00 | 13.90 | 5.19 | 91881319.07 | 126.83 | 06-DEC-14:00 | 13.90 | 5.19 |
Annual Sum or Average | 0.139585E+12 | 0.114426E+10 | ||||||||
Minimum of Months | 0.291193E+10 | 1859.89 | 9.70 | 3.54 | 86397290.95 | 126.83 | 9.70 | 3.54 | ||
Maximum of Months | 0.198827E+11 | 7885.44 | 29.60 | 21.98 | 0.104648E+09 | 134.91 | 29.60 | 21.98 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.979315E+09 | 1527.92 | 27-JAN-17:00 | 4.40 | -1.6 | 95039361.33 | 126.83 | 20-JAN-14:09 | 4.40 | -1.6 |
February | 0.588230E+10 | 3616.38 | 24-FEB-17:50 | 15.18 | 6.70 | 86397236.72 | 126.84 | 17-FEB-14:00 | 15.18 | 6.70 |
March | 0.129876E+11 | 6725.37 | 31-MAR-24:00 | 12.10 | 7.93 | 0.103239E+09 | 126.84 | 31-MAR-13:09 | 12.10 | 7.93 |
April | 0.177621E+11 | 7351.78 | 14-APR-18:20 | 23.90 | 15.14 | 91606169.94 | 126.83 | 03-APR-13:00 | 23.90 | 15.14 |
May | 0.408230E+10 | 3309.83 | 31-MAY-24:00 | 21.00 | 18.72 | 99238714.04 | 126.85 | 30-MAY-13:00 | 21.00 | 18.72 |
June | 0.888930E+10 | 5146.10 | 30-JUN-24:00 | 22.30 | 21.46 | 98974487.92 | 126.86 | 26-JUN-13:00 | 22.30 | 21.46 |
July | 0.140648E+11 | 7016.36 | 31-JUL-23:53 | 25.20 | 21.98 | 91892752.90 | 126.85 | 26-JUL-09:09 | 25.20 | 21.98 |
August | 0.188977E+11 | 7416.96 | 13-AUG-18:35 | 30.37 | 21.91 | 0.104752E+09 | 135.65 | 02-AUG-13:00 | 30.37 | 21.91 |
September | 0.395458E+10 | 2744.13 | 30-SEP-24:00 | 16.80 | 15.75 | 91609436.37 | 126.85 | 25-SEP-09:00 | 16.80 | 15.75 |
October | 0.823541E+10 | 4483.19 | 31-OCT-24:00 | 9.70 | 6.26 | 95237747.13 | 126.86 | 18-OCT-13:30 | 9.70 | 6.26 |
November | 0.120761E+11 | 5514.27 | 06-NOV-17:00 | 18.90 | 9.61 | 94301926.04 | 126.83 | 03-NOV-13:50 | 18.90 | 9.61 |
December | 0.162967E+11 | 7111.63 | 08-DEC-17:00 | 11.10 | 4.72 | 91881379.77 | 126.83 | 13-DEC-14:30 | 18.30 | 16.86 |
Annual Sum or Average | 0.124108E+12 | 0.114417E+10 | ||||||||
Minimum of Months | 0.979315E+09 | 1527.92 | 4.40 | -1.6 | 86397236.72 | 126.83 | 4.40 | -1.6 | ||
Maximum of Months | 0.188977E+11 | 7416.96 | 30.37 | 21.98 | 0.104752E+09 | 135.65 | 30.37 | 21.98 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438461E+09 | 1531.88 | 20-JAN-17:00 | 16.70 | 11.48 | 92542061.07 | 127.72 | 24-JAN-10:30 | 6.10 | 2.41 |
February | 0.465852E+10 | 3626.26 | 28-FEB-17:00 | 23.90 | 12.94 | 86396601.44 | 126.84 | 17-FEB-14:00 | 23.90 | 12.94 |
March | 0.121965E+11 | 6464.41 | 31-MAR-23:20 | 12.23 | 7.91 | 0.103239E+09 | 126.84 | 31-MAR-13:09 | 12.23 | 7.91 |
April | 0.173732E+11 | 7415.28 | 14-APR-18:20 | 23.90 | 15.14 | 91606262.87 | 126.83 | 03-APR-09:50 | 23.90 | 15.14 |
May | 0.398559E+10 | 3262.56 | 31-MAY-24:00 | 21.00 | 18.72 | 99239842.07 | 126.86 | 30-MAY-13:50 | 21.00 | 18.72 |
June | 0.893478E+10 | 5120.83 | 30-JUN-24:00 | 22.30 | 21.46 | 98974858.25 | 126.86 | 26-JUN-13:39 | 22.30 | 21.46 |
July | 0.141390E+11 | 7047.42 | 31-JUL-23:53 | 25.20 | 21.98 | 91892406.74 | 126.85 | 26-JUL-09:09 | 25.20 | 21.98 |
August | 0.189796E+11 | 7566.92 | 13-AUG-19:32 | 29.60 | 21.73 | 0.104613E+09 | 135.84 | 02-AUG-13:00 | 29.60 | 21.73 |
September | 0.381719E+10 | 2278.30 | 30-SEP-24:00 | 16.80 | 15.75 | 91609511.41 | 126.85 | 25-SEP-09:00 | 16.80 | 15.75 |
October | 0.752545E+10 | 4048.28 | 31-OCT-23:20 | 9.63 | 5.89 | 95237747.43 | 126.86 | 18-OCT-13:00 | 9.63 | 5.89 |
November | 0.108707E+11 | 5502.06 | 06-NOV-17:00 | 18.90 | 9.61 | 94301944.14 | 126.83 | 03-NOV-13:50 | 18.90 | 9.61 |
December | 0.145013E+11 | 7028.82 | 07-DEC-17:00 | 14.40 | 6.55 | 91881432.71 | 126.83 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.117420E+12 | 0.114153E+10 | ||||||||
Minimum of Months | 0.438461E+09 | 1531.88 | 9.63 | 5.89 | 86396601.44 | 126.83 | 6.10 | 2.41 | ||
Maximum of Months | 0.189796E+11 | 7566.92 | 29.60 | 21.98 | 0.104613E+09 | 135.84 | 29.60 | 21.98 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235935E+12 | 91570.43 | 20-JAN-17:00 | 16.70 | 11.48 | 0.206172E+10 | 2747.27 | 12-JAN-10:00 | 16.70 | 11.48 |
February | 0.433456E+12 | 183221.00 | 28-FEB-17:00 | 23.90 | 12.94 | 0.187076E+10 | 2748.93 | 09-FEB-14:50 | 23.90 | 12.94 |
March | 0.726828E+12 | 357933.25 | 31-MAR-24:00 | 12.10 | 7.93 | 0.223509E+10 | 2747.32 | 20-MAR-13:09 | 12.10 | 7.93 |
April | 0.938478E+12 | 365785.66 | 20-APR-15:30 | 24.15 | 16.80 | 0.200694E+10 | 3014.81 | 12-APR-13:00 | 24.15 | 16.80 |
May | 0.239222E+12 | 175217.85 | 31-MAY-24:00 | 21.00 | 18.72 | 0.214857E+10 | 2746.59 | 31-MAY-13:00 | 21.00 | 18.72 |
June | 0.469340E+12 | 267283.91 | 30-JUN-24:00 | 22.30 | 21.46 | 0.214258E+10 | 2746.33 | 26-JUN-09:00 | 22.30 | 21.46 |
July | 0.731188E+12 | 359513.21 | 31-JUL-23:53 | 25.20 | 21.98 | 0.198919E+10 | 2745.89 | 26-JUL-09:09 | 25.20 | 21.98 |
August | 0.972528E+12 | 370334.94 | 07-AUG-21:12 | 22.60 | 21.54 | 0.254970E+10 | 3595.50 | 18-AUG-13:50 | 33.48 | 22.91 |
September | 0.236656E+12 | 175586.24 | 30-SEP-24:00 | 16.80 | 15.75 | 0.198355E+10 | 2746.99 | 28-SEP-13:00 | 16.80 | 15.75 |
October | 0.488015E+12 | 268167.23 | 31-OCT-24:00 | 9.70 | 6.26 | 0.206165E+10 | 2746.39 | 18-OCT-13:30 | 9.70 | 6.26 |
November | 0.709162E+12 | 277199.09 | 06-NOV-17:00 | 18.90 | 9.61 | 0.204177E+10 | 2747.81 | 22-NOV-14:09 | 11.28 | 3.90 |
December | 0.975567E+12 | 368140.31 | 12-DEC-17:00 | 21.70 | 16.13 | 0.198971E+10 | 2748.50 | 04-DEC-14:09 | 21.70 | 16.13 |
Annual Sum or Average | 0.715638E+13 | 0.250812E+11 | ||||||||
Minimum of Months | 0.235935E+12 | 91570.43 | 9.70 | 6.26 | 0.187076E+10 | 2745.89 | 9.70 | 3.90 | ||
Maximum of Months | 0.975567E+12 | 370334.94 | 25.20 | 21.98 | 0.254970E+10 | 3595.50 | 33.48 | 22.91 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259752E+09 | 12022.25 | 02-JAN-04:05 | 3.30 |
February | 0.142423E+09 | 12037.83 | 23-FEB-05:05 | 6.02 |
March | 0.202331E+09 | 13835.93 | 23-MAR-04:53 | 6.10 |
April | 0.233635E+09 | 14124.37 | 07-APR-04:53 | 3.30 |
May | 0.309426E+09 | 15595.64 | 06-MAY-16:03 | 29.63 |
June | 0.355816E+09 | 20776.37 | 24-JUN-16:02 | 33.22 |
July | 0.472346E+09 | 25322.00 | 08-JUL-16:02 | 36.32 |
August | 0.449670E+09 | 19424.60 | 19-AUG-16:02 | 32.33 |
September | 0.452001E+09 | 14159.81 | 27-SEP-03:53 | 22.80 |
October | 0.481698E+09 | 12200.68 | 31-OCT-03:15 | 8.90 |
November | 0.437340E+09 | 12100.77 | 07-NOV-04:05 | 7.12 |
December | 0.342092E+09 | 11761.63 | 27-DEC-04:03 | 2.20 |
Annual Sum or Average | 0.413853E+10 | |||
Minimum of Months | 0.142423E+09 | 11761.63 | 2.20 | |
Maximum of Months | 0.481698E+09 | 25322.00 | 36.32 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39148603.42 | 40137.59 | 09-JAN-05:01 | -2.2 |
February | 36398800.54 | 38964.27 | 13-FEB-06:01 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 620938.20 | 1938.51 | 18-DEC-09:53 | 0.60 |
Annual Sum or Average | 76168342.16 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 39148603.42 | 40137.59 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265402E+10 | 79161.57 | 09-JAN-04:01 | -1.8 |
February | 0.124417E+10 | 78451.83 | 13-FEB-04:01 | -5.0 |
March | 4576127.46 | 30507.52 | 20-MAR-05:03 | 5.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 31899044.78 | 64663.39 | 22-NOV-06:01 | -3.3 |
December | 0.124402E+10 | 75214.29 | 04-DEC-04:01 | -2.3 |
Annual Sum or Average | 0.517869E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.265402E+10 | 79161.57 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153234E+09 | 11789.98 | 09-JAN-05:01 | -2.2 |
February | 60197706.91 | 11825.81 | 13-FEB-05:02 | -5.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 89916.36 | 1198.88 | 22-NOV-06:01 | -3.3 |
December | 879907.34 | 9347.09 | 18-DEC-06:01 | -5.0 |
Annual Sum or Average | 0.214402E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.153234E+09 | 11825.81 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116911E+09 | 9331.22 | 09-JAN-05:01 | -2.2 |
February | 39565983.55 | 9385.86 | 13-FEB-05:02 | -5.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 1244650.72 | 6622.91 | 21-NOV-06:01 | -2.8 |
December | 6269672.68 | 7882.03 | 18-DEC-06:01 | -5.0 |
Annual Sum or Average | 0.163991E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.116911E+09 | 9385.86 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201197E+09 | 14343.34 | 09-JAN-05:01 | -2.2 |
February | 74243827.10 | 13757.89 | 13-FEB-05:02 | -5.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 1388188.29 | 10853.67 | 21-NOV-06:01 | -2.8 |
December | 12560218.13 | 12014.75 | 01-DEC-06:01 | -3.9 |
Annual Sum or Average | 0.289389E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.201197E+09 | 14343.34 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6921788.83 | 6995.12 | 09-JAN-06:01 | -2.4 |
February | 894132.59 | 7001.06 | 13-FEB-06:01 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 7815921.42 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 6921788.83 | 7001.06 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249295E+10 | 13320.48 | 09-JAN-04:01 | -1.8 |
February | 0.136041E+10 | 13683.59 | 12-FEB-05:22 | -11.9 |
March | 33931091.05 | 10555.51 | 18-MAR-05:03 | 3.22 |
April | 5383188.05 | 9603.85 | 06-APR-05:02 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 9233141.78 | 10518.14 | 26-OCT-05:03 | 2.20 |
November | 0.165725E+09 | 11730.83 | 22-NOV-05:01 | -2.9 |
December | 0.897145E+09 | 12580.21 | 18-DEC-04:01 | -4.1 |
Annual Sum or Average | 0.496477E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.249295E+10 | 13683.59 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135309E+10 | 13874.58 | 09-JAN-04:01 | -1.8 |
February | 0.665864E+09 | 14215.54 | 12-FEB-05:22 | -11.9 |
March | 18927289.47 | 10386.53 | 18-MAR-05:03 | 3.22 |
April | 2226767.41 | 5680.40 | 06-APR-05:02 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 6199057.34 | 7961.04 | 26-OCT-05:03 | 2.20 |
November | 71508729.78 | 12004.18 | 22-NOV-05:01 | -2.9 |
December | 0.433004E+09 | 12830.24 | 18-DEC-04:01 | -4.1 |
Annual Sum or Average | 0.255082E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.135309E+10 | 14215.54 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118891E+10 | 15206.81 | 09-JAN-04:01 | -1.8 |
February | 0.576922E+09 | 15482.26 | 12-FEB-05:22 | -11.9 |
March | 10012172.27 | 12046.12 | 22-MAR-05:03 | 6.02 |
April | 305938.63 | 2484.58 | 06-APR-05:02 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 209636.86 | 1397.58 | 31-OCT-05:03 | 8.30 |
November | 58765446.94 | 12973.89 | 21-NOV-05:01 | -2.3 |
December | 0.343074E+09 | 13718.37 | 26-DEC-05:01 | 3.80 |
Annual Sum or Average | 0.217820E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.118891E+10 | 15482.26 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100948E+10 | 14495.08 | 09-JAN-04:01 | -1.8 |
February | 0.501076E+09 | 14420.75 | 13-FEB-04:01 | -5.0 |
March | 3683368.85 | 7788.14 | 22-MAR-05:03 | 6.02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 350903.91 | 1701.22 | 26-OCT-05:03 | 2.20 |
November | 62331813.91 | 12593.31 | 22-NOV-05:01 | -2.9 |
December | 0.318706E+09 | 13080.78 | 26-DEC-05:01 | 3.80 |
Annual Sum or Average | 0.189563E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.100948E+10 | 14495.08 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.669141E+10 | 15901.79 | 09-JAN-03:53 | -1.7 |
February | 0.381432E+10 | 16683.35 | 12-FEB-05:22 | -11.9 |
March | 0.446771E+09 | 13485.55 | 20-MAR-04:01 | 6.42 |
April | 0.117368E+09 | 12995.58 | 06-APR-04:02 | 0.92 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.173238E+09 | 13263.62 | 26-OCT-04:02 | 2.70 |
November | 0.109833E+10 | 14818.34 | 22-NOV-04:01 | -2.8 |
December | 0.361623E+10 | 15464.87 | 18-DEC-04:01 | -4.1 |
Annual Sum or Average | 0.159577E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.669141E+10 | 16683.35 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351592E+10 | 14778.53 | 08-JAN-02:32 | -5.6 |
February | 0.195464E+10 | 15585.64 | 12-FEB-05:22 | -11.9 |
March | 0.202260E+09 | 12574.66 | 22-MAR-04:01 | 6.60 |
April | 47939152.43 | 11962.19 | 06-APR-04:02 | 0.92 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.100063E+09 | 12334.92 | 26-OCT-04:02 | 2.70 |
November | 0.480119E+09 | 13652.49 | 22-NOV-04:01 | -2.8 |
December | 0.175596E+10 | 14456.48 | 18-DEC-04:01 | -4.1 |
Annual Sum or Average | 0.805690E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.351592E+10 | 15585.64 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369101E+10 | 17704.76 | 09-JAN-03:53 | -1.7 |
February | 0.208486E+10 | 18636.17 | 12-FEB-05:22 | -11.9 |
March | 0.217285E+09 | 14929.40 | 22-MAR-04:01 | 6.60 |
April | 73313395.81 | 14190.91 | 06-APR-04:02 | 0.92 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.109167E+09 | 14234.58 | 30-OCT-04:03 | 8.90 |
November | 0.443106E+09 | 16004.14 | 21-NOV-04:02 | -1.8 |
December | 0.170426E+10 | 17192.22 | 26-DEC-04:11 | 3.90 |
Annual Sum or Average | 0.832300E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.369101E+10 | 18636.17 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299503E+10 | 16200.33 | 09-JAN-03:53 | -1.7 |
February | 0.154336E+10 | 17046.92 | 12-FEB-05:22 | -11.9 |
March | 0.115600E+09 | 13683.49 | 22-MAR-04:01 | 6.60 |
April | 29051402.95 | 11190.46 | 06-APR-05:02 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 56119825.19 | 11694.09 | 25-OCT-05:02 | 9.90 |
November | 0.399030E+09 | 14939.92 | 22-NOV-04:01 | -2.8 |
December | 0.131044E+10 | 15855.58 | 18-DEC-04:01 | -4.1 |
Annual Sum or Average | 0.644863E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.299503E+10 | 17046.92 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.457612E+09 | 12899.86 | 17-JAN-06:01 | 4.72 |
February | 0.302674E+09 | 12483.68 | 10-FEB-05:07 | 5.10 |
March | 0.100803E+09 | 10082.76 | 27-MAR-03:02 | 10.50 |
April | 0.121384E+09 | 10405.28 | 04-APR-03:02 | 15.10 |
May | 65864587.94 | 8905.58 | 01-MAY-03:02 | 16.27 |
June | 70841928.32 | 7724.01 | 16-JUN-03:02 | 21.02 |
July | 74864136.24 | 8400.06 | 29-JUL-03:02 | 17.70 |
August | 47057287.54 | 4680.53 | 27-AUG-15:02 | 31.70 |
September | 67335868.57 | 7686.52 | 18-SEP-03:02 | 15.00 |
October | 92123722.98 | 11728.60 | 02-OCT-03:02 | 19.82 |
November | 0.111363E+09 | 12197.76 | 24-NOV-04:03 | 8.90 |
December | 90797319.24 | 13723.34 | 26-DEC-04:03 | 3.90 |
Annual Sum or Average | 0.160272E+10 | |||
Minimum of Months | 47057287.54 | 4680.53 | 3.90 | |
Maximum of Months | 0.457612E+09 | 13723.34 | 31.70 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244381E+10 | 14027.70 | 05-JAN-11:33 | 0.03 |
February | 0.122297E+10 | 10192.73 | 03-FEB-13:20 | -0.7 |
March | 81619019.66 | 8022.62 | 21-MAR-05:03 | 11.52 |
April | 47483679.50 | 8195.46 | 03-APR-04:03 | 20.22 |
May | 54828742.51 | 7543.25 | 01-MAY-03:02 | 16.27 |
June | 40900173.80 | 6771.24 | 14-JUN-03:02 | 22.62 |
July | 43611559.04 | 7255.78 | 31-JUL-03:02 | 21.60 |
August | 39082799.03 | 7180.88 | 01-AUG-03:02 | 24.15 |
September | 44667872.81 | 6534.38 | 25-SEP-03:02 | 20.10 |
October | 63780917.42 | 7881.91 | 25-OCT-05:02 | 9.90 |
November | 0.155972E+09 | 8544.03 | 28-NOV-06:03 | 11.52 |
December | 0.976193E+09 | 8048.98 | 12-DEC-06:03 | 12.70 |
Annual Sum or Average | 0.521493E+10 | |||
Minimum of Months | 39082799.03 | 6534.38 | -0.7 | |
Maximum of Months | 0.244381E+10 | 14027.70 | 24.15 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.931608E+10 | 24348.92 | 09-JAN-05:18 | -2.2 |
February | 0.563225E+10 | 25574.28 | 13-FEB-05:32 | -5.4 |
March | 0.151926E+10 | 16194.31 | 01-MAR-06:03 | 8.40 |
April | 0.732236E+09 | 17868.07 | 25-APR-05:03 | 9.40 |
May | 0.214955E+09 | 18902.18 | 11-MAY-05:02 | 8.22 |
June | 0.109154E+09 | 16231.79 | 08-JUN-05:03 | 11.70 |
July | 64504434.44 | 10578.48 | 03-JUL-03:02 | 17.80 |
August | 51098492.63 | 9960.65 | 28-AUG-03:02 | 21.60 |
September | 0.167868E+09 | 15706.63 | 29-SEP-05:03 | 12.30 |
October | 0.113691E+10 | 17158.11 | 20-OCT-05:03 | 9.90 |
November | 0.245286E+10 | 14470.87 | 22-NOV-06:13 | -3.3 |
December | 0.564384E+10 | 23801.61 | 18-DEC-05:33 | -5.0 |
Annual Sum or Average | 0.270410E+11 | |||
Minimum of Months | 51098492.63 | 9960.65 | -5.4 | |
Maximum of Months | 0.931608E+10 | 25574.28 | 21.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241339E+09 | 535.69 | 08-JAN-01:40 | -5.8 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.241339E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.8 | |
Maximum of Months | 0.241339E+09 | 535.69 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.651424E+09 | 579.25 | 15-JAN-19:00 | 3.90 |
February | 42996212.39 | 535.43 | 12-FEB-07:45 | -12.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.694420E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.3 | |
Maximum of Months | 0.651424E+09 | 579.25 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200626E+11 | 20994.62 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.181982E+11 | 20994.62 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.216246E+11 | 20994.62 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.193152E+11 | 20994.62 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.208436E+11 | 20994.62 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.207428E+11 | 20994.62 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.194159E+11 | 20994.62 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.216246E+11 | 20994.62 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.193152E+11 | 20994.62 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.200626E+11 | 20994.62 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.198274E+11 | 20994.62 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.194159E+11 | 20994.62 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.240449E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.181982E+11 | 20994.62 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.216246E+11 | 20994.62 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.166997E+10 | 2217.83 | 03-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.151325E+10 | 2318.86 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.167794E+10 | 2230.65 | 21-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146459E+10 | 2078.82 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.155027E+10 | 1626.14 | 24-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.153128E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.144454E+10 | 1766.67 | 27-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.162533E+10 | 2008.73 | 24-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.149135E+10 | 2143.20 | 29-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.163458E+10 | 2363.15 | 30-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.162553E+10 | 2341.95 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.162874E+10 | 2221.92 | 06-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.188574E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.144454E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.167794E+10 | 2363.15 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105497E+10 | 1409.07 | 03-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.954609E+09 | 1494.36 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107397E+10 | 1427.69 | 21-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.944524E+09 | 1302.63 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.100328E+10 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.992018E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.934583E+09 | 1055.50 | 27-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.104940E+10 | 1254.33 | 24-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.957652E+09 | 1356.03 | 29-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.102890E+10 | 1522.90 | 30-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.103648E+10 | 1500.56 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.102713E+10 | 1411.95 | 06-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120575E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.934583E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.107397E+10 | 1522.90 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160508E+10 | 2196.45 | 03-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.145987E+10 | 2318.91 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166544E+10 | 2228.45 | 21-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.146823E+10 | 2084.50 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.155963E+10 | 1746.80 | 24-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.154193E+10 | 1629.84 | 23-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.145496E+10 | 1835.92 | 27-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.163024E+10 | 2024.82 | 24-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148738E+10 | 2130.41 | 29-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.158236E+10 | 2363.20 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.157840E+10 | 2333.33 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.155932E+10 | 2198.55 | 06-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.185929E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.145496E+10 | 1629.84 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.166544E+10 | 2363.20 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105686E+10 | 1433.50 | 03-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.963790E+09 | 1494.36 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.108405E+10 | 1443.43 | 21-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.948947E+09 | 1366.10 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.100522E+10 | 1266.53 | 24-MAY-07:30 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.992378E+09 | 1119.04 | 23-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.937768E+09 | 1225.96 | 27-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.105257E+10 | 1327.51 | 24-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.966316E+09 | 1392.40 | 29-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.104697E+10 | 1522.90 | 30-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.103093E+10 | 1511.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.102666E+10 | 1435.03 | 06-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.121125E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.937768E+09 | 1119.04 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.108405E+10 | 1522.90 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.167367E+10 | 2222.17 | 03-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.151672E+10 | 2320.29 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.167969E+10 | 2234.71 | 21-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146568E+10 | 2087.33 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.155091E+10 | 1646.65 | 24-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.153171E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.144532E+10 | 1784.22 | 27-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.162653E+10 | 2019.30 | 24-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.149291E+10 | 2149.80 | 29-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.163661E+10 | 2363.27 | 30-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.162888E+10 | 2342.66 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.163284E+10 | 2226.11 | 06-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.188815E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.144532E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.167969E+10 | 2363.27 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105625E+10 | 1410.52 | 03-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.955139E+09 | 1494.59 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107444E+10 | 1428.82 | 21-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.944900E+09 | 1306.19 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.100349E+10 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.992188E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.934786E+09 | 1062.47 | 27-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.104965E+10 | 1258.36 | 24-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.958106E+09 | 1358.15 | 29-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.102926E+10 | 1522.92 | 30-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.103703E+10 | 1500.98 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.102769E+10 | 1413.34 | 06-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120629E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.934786E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.107444E+10 | 1522.92 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160919E+10 | 2201.81 | 03-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.146171E+10 | 2320.34 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166663E+10 | 2232.60 | 21-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.146915E+10 | 2092.76 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.156076E+10 | 1763.21 | 24-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.154279E+10 | 1650.07 | 23-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.145609E+10 | 1850.90 | 27-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.163126E+10 | 2034.74 | 24-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148841E+10 | 2137.58 | 29-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.158565E+10 | 2363.32 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.157959E+10 | 2334.43 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.156084E+10 | 2203.86 | 06-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.186121E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.145609E+10 | 1650.07 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.166663E+10 | 2363.32 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105727E+10 | 1434.22 | 03-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.963950E+09 | 1494.59 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.108455E+10 | 1444.03 | 21-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.949366E+09 | 1367.28 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.100561E+10 | 1268.01 | 24-MAY-07:30 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.992613E+09 | 1121.93 | 23-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.937996E+09 | 1228.19 | 27-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.105291E+10 | 1328.97 | 24-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.966902E+09 | 1393.40 | 29-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.104722E+10 | 1522.92 | 30-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.103140E+10 | 1511.17 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.102729E+10 | 1435.74 | 06-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.121171E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.937996E+09 | 1121.93 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.108455E+10 | 1522.92 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.167369E+10 | 2222.03 | 03-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.151670E+10 | 2320.24 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.167970E+10 | 2234.58 | 21-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146569E+10 | 2087.09 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.155090E+10 | 1646.39 | 24-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.153171E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.144531E+10 | 1783.80 | 27-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.162652E+10 | 2019.00 | 24-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.149291E+10 | 2149.60 | 29-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.163661E+10 | 2363.27 | 30-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.162890E+10 | 2342.64 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.163296E+10 | 2225.98 | 06-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.188816E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.144531E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.167970E+10 | 2363.27 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105627E+10 | 1410.45 | 03-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.955124E+09 | 1494.56 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107445E+10 | 1428.75 | 21-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.944909E+09 | 1306.08 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.100349E+10 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.992189E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.934785E+09 | 1062.32 | 27-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.104965E+10 | 1258.23 | 24-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.958138E+09 | 1358.05 | 29-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.102927E+10 | 1522.92 | 30-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.103704E+10 | 1500.98 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.102770E+10 | 1413.27 | 06-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120630E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.934785E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.107445E+10 | 1522.92 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160911E+10 | 2201.69 | 03-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.146341E+10 | 2320.29 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166662E+10 | 2232.47 | 21-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.146916E+10 | 2092.53 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.156075E+10 | 1762.93 | 24-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.154278E+10 | 1649.51 | 23-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.145609E+10 | 1850.47 | 27-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.163125E+10 | 2034.43 | 24-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148841E+10 | 2137.38 | 29-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.158563E+10 | 2363.32 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.157967E+10 | 2334.42 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.156084E+10 | 2203.74 | 06-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.186137E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.145609E+10 | 1649.51 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.166662E+10 | 2363.32 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105730E+10 | 1434.13 | 03-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.963948E+09 | 1494.56 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.108456E+10 | 1443.95 | 21-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.949452E+09 | 1367.13 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.100561E+10 | 1267.89 | 24-MAY-07:30 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.992633E+09 | 1121.58 | 23-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.937999E+09 | 1227.92 | 27-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.105291E+10 | 1328.79 | 24-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.966913E+09 | 1393.27 | 29-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.104723E+10 | 1522.92 | 30-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.103146E+10 | 1511.16 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.102731E+10 | 1435.65 | 06-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.121173E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.937999E+09 | 1121.58 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.108456E+10 | 1522.92 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.565679E+10 | 5919.59 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.513113E+10 | 5919.59 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.609720E+10 | 5919.59 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.544605E+10 | 5919.59 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.587700E+10 | 5919.59 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.584858E+10 | 5919.59 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.547447E+10 | 5919.59 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.609720E+10 | 5919.59 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.544605E+10 | 5919.59 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.565679E+10 | 5919.59 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.559049E+10 | 5919.59 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.547447E+10 | 5919.59 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.677962E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.513113E+10 | 5919.59 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.609720E+10 | 5919.59 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.208436E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.207428E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.198274E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.240449E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.166997E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970326E+09 |
February | 0.136985E+10 | 0.151325E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 512908.03 | 0.826551E+09 |
March | 0.163685E+10 | 0.167794E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1629968.41 | 0.539230E+09 |
April | 0.145243E+10 | 0.146459E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4842532.95 | 0.319943E+09 |
May | 0.157338E+10 | 0.155027E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14352137.39 | 0.204644E+09 |
June | 0.156900E+10 | 0.153128E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59835975.96 | 91368449.31 |
July | 0.145680E+10 | 0.144454E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66839429.22 | 55913901.05 |
August | 0.163685E+10 | 0.162533E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64750481.22 | 25741084.00 |
September | 0.145243E+10 | 0.149135E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17881379.50 | 0.106607E+09 |
October | 0.150991E+10 | 0.163458E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4101739.44 | 0.366704E+09 |
November | 0.149516E+10 | 0.162553E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26094.34 | 0.539859E+09 |
December | 0.145680E+10 | 0.162874E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937566E+09 |
Annual Sum or Average | 0.181194E+11 | 0.188574E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234773E+09 | 0.498445E+10 |
Minimum of Months | 0.136985E+10 | 0.144454E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25741084.00 |
Maximum of Months | 0.163685E+10 | 0.167794E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66839429.22 | 0.970326E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.105497E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648024E+09 |
February | 0.882782E+09 | 0.954609E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249353.04 | 0.548392E+09 |
March | 0.105485E+10 | 0.107397E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1376927.44 | 0.351346E+09 |
April | 0.936002E+09 | 0.944524E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3568506.82 | 0.202840E+09 |
May | 0.101394E+10 | 0.100328E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9552159.08 | 0.136710E+09 |
June | 0.101113E+10 | 0.992018E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40881665.52 | 56343618.54 |
July | 0.938820E+09 | 0.934583E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47227248.20 | 31734004.47 |
August | 0.105485E+10 | 0.104940E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48039751.86 | 10626897.98 |
September | 0.936002E+09 | 0.957652E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12322422.31 | 67530212.12 |
October | 0.973041E+09 | 0.102890E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2725825.59 | 0.238607E+09 |
November | 0.963541E+09 | 0.103648E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 168481.55 | 0.351433E+09 |
December | 0.938820E+09 | 0.102713E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608255E+09 |
Annual Sum or Average | 0.116768E+11 | 0.120575E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166112E+09 | 0.325184E+10 |
Minimum of Months | 0.882782E+09 | 0.934583E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10626897.98 |
Maximum of Months | 0.105485E+10 | 0.107397E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48039751.86 | 0.648024E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.160508E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983584E+09 |
February | 0.136988E+10 | 0.145987E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95570.58 | 0.843213E+09 |
March | 0.163688E+10 | 0.166544E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1574516.27 | 0.556711E+09 |
April | 0.145246E+10 | 0.146823E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4112108.66 | 0.319675E+09 |
May | 0.157341E+10 | 0.155963E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13985607.02 | 0.204022E+09 |
June | 0.156904E+10 | 0.154193E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60499370.44 | 88950457.08 |
July | 0.145684E+10 | 0.145496E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67495517.49 | 53764617.04 |
August | 0.163688E+10 | 0.163024E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63028413.34 | 25759964.47 |
September | 0.145246E+10 | 0.148738E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15528025.15 | 0.108156E+09 |
October | 0.150994E+10 | 0.158236E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2487238.26 | 0.378426E+09 |
November | 0.149520E+10 | 0.157840E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555930E+09 |
December | 0.145684E+10 | 0.155932E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934113E+09 |
Annual Sum or Average | 0.181198E+11 | 0.185929E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228806E+09 | 0.505231E+10 |
Minimum of Months | 0.136988E+10 | 0.145496E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25759964.47 |
Maximum of Months | 0.163688E+10 | 0.166544E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67495517.49 | 0.983584E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.105686E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678414E+09 |
February | 0.882782E+09 | 0.963790E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94817.93 | 0.596052E+09 |
March | 0.105485E+10 | 0.108405E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1039176.42 | 0.411813E+09 |
April | 0.936002E+09 | 0.948947E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2609429.44 | 0.248512E+09 |
May | 0.101394E+10 | 0.100522E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8706313.14 | 0.151759E+09 |
June | 0.101113E+10 | 0.992378E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37638206.60 | 71087878.46 |
July | 0.938820E+09 | 0.937768E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40594297.60 | 45629186.93 |
August | 0.105485E+10 | 0.105257E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37680145.06 | 27310904.60 |
September | 0.936002E+09 | 0.966316E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11123174.22 | 80175045.99 |
October | 0.973041E+09 | 0.104697E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1873056.38 | 0.272752E+09 |
November | 0.963541E+09 | 0.103093E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401760E+09 |
December | 0.938820E+09 | 0.102666E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699097E+09 |
Annual Sum or Average | 0.116768E+11 | 0.121125E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141359E+09 | 0.368436E+10 |
Minimum of Months | 0.882782E+09 | 0.937768E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27310904.60 |
Maximum of Months | 0.105485E+10 | 0.108405E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40594297.60 | 0.699097E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.167367E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196992E+10 |
February | 0.136985E+10 | 0.151672E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3672111.50 | 0.168131E+10 |
March | 0.163685E+10 | 0.167969E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4624322.65 | 0.110675E+10 |
April | 0.145243E+10 | 0.146568E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12801238.69 | 0.695853E+09 |
May | 0.157338E+10 | 0.155091E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33501791.78 | 0.454760E+09 |
June | 0.156900E+10 | 0.153171E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136717E+09 | 0.226972E+09 |
July | 0.145680E+10 | 0.144532E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150281E+09 | 0.147113E+09 |
August | 0.163685E+10 | 0.162653E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146246E+09 | 91718736.89 |
September | 0.145243E+10 | 0.149291E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42473640.82 | 0.232808E+09 |
October | 0.150991E+10 | 0.163661E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13437729.08 | 0.750094E+09 |
November | 0.149516E+10 | 0.162888E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 600964.18 | 0.107379E+10 |
December | 0.145680E+10 | 0.163284E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181222E+10 |
Annual Sum or Average | 0.181194E+11 | 0.188815E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544356E+09 | 0.102433E+11 |
Minimum of Months | 0.136985E+10 | 0.144532E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91718736.89 |
Maximum of Months | 0.163685E+10 | 0.167969E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150281E+09 | 0.196992E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.105625E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133585E+10 |
February | 0.649041E+09 | 0.955139E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1138899.45 | 0.114573E+10 |
March | 0.773965E+09 | 0.107444E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3632032.56 | 0.761211E+09 |
April | 0.688021E+09 | 0.944900E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7429464.81 | 0.475582E+09 |
May | 0.744847E+09 | 0.100349E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20712391.21 | 0.314674E+09 |
June | 0.742030E+09 | 0.992188E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90210495.11 | 0.154674E+09 |
July | 0.690839E+09 | 0.934786E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99479340.53 | 98909108.31 |
August | 0.773965E+09 | 0.104965E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97232764.09 | 61395920.70 |
September | 0.688021E+09 | 0.958106E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27979618.68 | 0.153118E+09 |
October | 0.715730E+09 | 0.102926E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7151976.38 | 0.509840E+09 |
November | 0.708685E+09 | 0.103703E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 306698.39 | 0.729962E+09 |
December | 0.690839E+09 | 0.102769E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122097E+10 |
Annual Sum or Average | 0.858171E+10 | 0.120629E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355274E+09 | 0.696192E+10 |
Minimum of Months | 0.649041E+09 | 0.934786E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61395920.70 |
Maximum of Months | 0.773965E+09 | 0.107444E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99479340.53 | 0.133585E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.160919E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214367E+10 |
February | 0.136988E+10 | 0.146171E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 191690.37 | 0.183269E+10 |
March | 0.163688E+10 | 0.166663E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3488204.80 | 0.123813E+10 |
April | 0.145246E+10 | 0.146915E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9183066.50 | 0.732254E+09 |
May | 0.157341E+10 | 0.156076E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31585588.16 | 0.462695E+09 |
June | 0.156904E+10 | 0.154279E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137857E+09 | 0.224553E+09 |
July | 0.145684E+10 | 0.145609E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151133E+09 | 0.145835E+09 |
August | 0.163688E+10 | 0.163126E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139566E+09 | 98074347.52 |
September | 0.145246E+10 | 0.148841E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34707140.62 | 0.247928E+09 |
October | 0.150994E+10 | 0.158565E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5285255.36 | 0.842494E+09 |
November | 0.149520E+10 | 0.157959E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122438E+10 |
December | 0.145684E+10 | 0.156084E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197052E+10 |
Annual Sum or Average | 0.181198E+11 | 0.186121E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512998E+09 | 0.111632E+11 |
Minimum of Months | 0.136988E+10 | 0.145609E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98074347.52 |
Maximum of Months | 0.163688E+10 | 0.166663E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151133E+09 | 0.214367E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.105727E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136728E+10 |
February | 0.882782E+09 | 0.963950E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1361781.36 | 0.116900E+10 |
March | 0.105485E+10 | 0.108455E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2560902.87 | 0.807155E+09 |
April | 0.936002E+09 | 0.949366E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6992052.03 | 0.503247E+09 |
May | 0.101394E+10 | 0.100561E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20371243.74 | 0.325841E+09 |
June | 0.101113E+10 | 0.992613E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87913416.25 | 0.165114E+09 |
July | 0.938820E+09 | 0.937996E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96633101.17 | 0.106216E+09 |
August | 0.105485E+10 | 0.105291E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90737826.04 | 75260917.43 |
September | 0.936002E+09 | 0.966902E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26600204.33 | 0.164887E+09 |
October | 0.973041E+09 | 0.104722E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5908723.95 | 0.532879E+09 |
November | 0.963541E+09 | 0.103140E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758287E+09 |
December | 0.938820E+09 | 0.102729E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125933E+10 |
Annual Sum or Average | 0.116768E+11 | 0.121171E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339079E+09 | 0.723450E+10 |
Minimum of Months | 0.882782E+09 | 0.937996E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75260917.43 |
Maximum of Months | 0.105485E+10 | 0.108455E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96633101.17 | 0.136728E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.167369E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229355E+10 |
February | 0.136985E+10 | 0.151670E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6738870.32 | 0.196905E+10 |
March | 0.163685E+10 | 0.167970E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6491985.29 | 0.125818E+10 |
April | 0.145243E+10 | 0.146569E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15823281.63 | 0.808506E+09 |
May | 0.157338E+10 | 0.155090E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39772086.06 | 0.550845E+09 |
June | 0.156900E+10 | 0.153171E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163243E+09 | 0.285117E+09 |
July | 0.145680E+10 | 0.144531E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178138E+09 | 0.183705E+09 |
August | 0.163685E+10 | 0.162652E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173073E+09 | 0.117546E+09 |
September | 0.145243E+10 | 0.149291E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50888483.07 | 0.274440E+09 |
October | 0.150991E+10 | 0.163661E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19039761.27 | 0.845699E+09 |
November | 0.149516E+10 | 0.162890E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3832291.06 | 0.118900E+10 |
December | 0.145680E+10 | 0.163296E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203131E+10 |
Annual Sum or Average | 0.181194E+11 | 0.188816E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657040E+09 | 0.118070E+11 |
Minimum of Months | 0.136985E+10 | 0.144531E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117546E+09 |
Maximum of Months | 0.163685E+10 | 0.167970E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178138E+09 | 0.229355E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.105627E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154635E+10 |
February | 0.882782E+09 | 0.955124E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1895940.51 | 0.134120E+10 |
March | 0.105485E+10 | 0.107445E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4543930.92 | 0.882151E+09 |
April | 0.936002E+09 | 0.944909E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8318045.69 | 0.564490E+09 |
May | 0.101394E+10 | 0.100349E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23775664.76 | 0.387735E+09 |
June | 0.101113E+10 | 0.992189E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106943E+09 | 0.197153E+09 |
July | 0.938820E+09 | 0.934785E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116711E+09 | 0.125127E+09 |
August | 0.105485E+10 | 0.104965E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114061E+09 | 79840883.24 |
September | 0.936002E+09 | 0.958138E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32128060.39 | 0.184968E+09 |
October | 0.973041E+09 | 0.102927E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8995661.99 | 0.589627E+09 |
November | 0.963541E+09 | 0.103704E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1976550.12 | 0.819938E+09 |
December | 0.938820E+09 | 0.102770E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136504E+10 |
Annual Sum or Average | 0.116768E+11 | 0.120630E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419348E+09 | 0.808362E+10 |
Minimum of Months | 0.882782E+09 | 0.934785E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79840883.24 |
Maximum of Months | 0.105485E+10 | 0.107445E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116711E+09 | 0.154635E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.160911E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244547E+10 |
February | 0.136988E+10 | 0.146341E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201226.37 | 0.212265E+10 |
March | 0.163688E+10 | 0.166662E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4196722.91 | 0.143528E+10 |
April | 0.145246E+10 | 0.146916E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10719530.96 | 0.861072E+09 |
May | 0.157341E+10 | 0.156075E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37170890.36 | 0.563131E+09 |
June | 0.156904E+10 | 0.154278E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164489E+09 | 0.282156E+09 |
July | 0.145684E+10 | 0.145609E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178826E+09 | 0.181827E+09 |
August | 0.163688E+10 | 0.163125E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166531E+09 | 0.126106E+09 |
September | 0.145246E+10 | 0.148841E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41188346.50 | 0.296816E+09 |
October | 0.150994E+10 | 0.158563E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6151946.80 | 0.976522E+09 |
November | 0.149520E+10 | 0.157967E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138014E+10 |
December | 0.145684E+10 | 0.156084E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218192E+10 |
Annual Sum or Average | 0.181198E+11 | 0.186137E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609475E+09 | 0.128531E+11 |
Minimum of Months | 0.136988E+10 | 0.145609E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126106E+09 |
Maximum of Months | 0.163688E+10 | 0.166662E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178826E+09 | 0.244547E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.105730E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158167E+10 |
February | 0.882782E+09 | 0.963948E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2140976.07 | 0.137417E+10 |
March | 0.105485E+10 | 0.108456E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3251396.66 | 0.942736E+09 |
April | 0.936002E+09 | 0.949452E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8343382.73 | 0.597543E+09 |
May | 0.101394E+10 | 0.100561E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24667674.06 | 0.398352E+09 |
June | 0.101113E+10 | 0.992633E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106327E+09 | 0.207365E+09 |
July | 0.938820E+09 | 0.937999E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116336E+09 | 0.131553E+09 |
August | 0.105485E+10 | 0.105291E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109550E+09 | 95121122.42 |
September | 0.936002E+09 | 0.966913E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31907401.46 | 0.197799E+09 |
October | 0.973041E+09 | 0.104723E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7779576.65 | 0.619790E+09 |
November | 0.963541E+09 | 0.103146E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14771.46 | 0.862557E+09 |
December | 0.938820E+09 | 0.102731E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142484E+10 |
Annual Sum or Average | 0.116768E+11 | 0.121173E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410319E+09 | 0.843349E+10 |
Minimum of Months | 0.882782E+09 | 0.937999E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95121122.42 |
Maximum of Months | 0.105485E+10 | 0.108456E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116336E+09 | 0.158167E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.565679E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.513113E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.609720E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.544605E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.587700E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.584858E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.547447E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.609720E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.544605E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.565679E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.559049E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.547447E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.677962E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.513113E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.609720E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212422E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87413.85 | 0.180796E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2080349.92 | 0.116980E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6392438.39 | 0.692464E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22618052.22 | 0.431367E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106781E+09 | 0.199414E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122489E+09 | 0.127915E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113361E+09 | 73841163.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28092026.09 | 0.228880E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4815119.03 | 0.792329E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117248E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203004E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406716E+09 | 0.108507E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73841163.30 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122489E+09 | 0.212422E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349607E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1188412.33 | 0.299942E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4268535.72 | 0.198715E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13017044.65 | 0.119837E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42417053.24 | 0.758836E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192750E+09 | 0.359746E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221360E+09 | 0.232649E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204603E+09 | 0.144503E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53076042.67 | 0.398436E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11316652.97 | 0.134437E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331529.65 | 0.195449E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331188E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744328E+09 | 0.181859E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144503E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221360E+09 | 0.349607E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349049E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1329808.61 | 0.306061E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2952799.74 | 0.209629E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6297537.47 | 0.130913E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27450139.27 | 0.870472E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174286E+09 | 0.419257E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198152E+09 | 0.277999E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188062E+09 | 0.177904E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41979088.59 | 0.431862E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7856579.43 | 0.139833E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1790605.79 | 0.195026E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320627E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650156E+09 | 0.186889E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177904E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198152E+09 | 0.349049E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 20994.62 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 20994.62 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 20994.62 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 20994.62 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 20994.62 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 20994.62 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 20994.62 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 20994.62 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 20994.62 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 20994.62 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 20994.62 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 20994.62 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2217.83 | 03-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1727.90 | 07-JAN-18:03 |
February | 2010.79 | 01-FEB-10:09 | 2318.86 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.76 | 26-FEB-14:50 | 2129.33 | 12-FEB-00:55 |
March | 2010.79 | 01-MAR-10:09 | 2230.65 | 21-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 30-MAR-16:00 | 1402.74 | 22-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 2078.82 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.63 | 16-APR-12:10 | 714.38 | 05-APR-05:00 |
May | 2010.79 | 01-MAY-09:09 | 1626.14 | 24-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.05 | 07-MAY-12:10 | 551.93 | 10-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.08 | 11-JUN-15:00 | 406.35 | 07-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1766.67 | 27-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.28 | 08-JUL-18:53 | 300.36 | 28-JUL-22:00 |
August | 2010.79 | 01-AUG-09:09 | 2008.73 | 24-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.58 | 06-AUG-14:00 | 164.89 | 31-AUG-05:00 |
September | 2010.79 | 01-SEP-09:09 | 2143.20 | 29-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.76 | 17-SEP-15:00 | 380.90 | 30-SEP-19:00 |
October | 2010.79 | 02-OCT-09:09 | 2363.15 | 30-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.27 | 09-OCT-15:43 | 833.25 | 28-OCT-03:53 |
November | 2010.79 | 01-NOV-09:09 | 2341.95 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 | 19-NOV-15:10 | 1187.95 | 07-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2221.92 | 06-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2076.09 | 17-DEC-03:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.89 | |||||
Maximum of Months | 2010.79 | 2363.15 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 324.58 | 2129.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.07 | 03-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1134.74 | 07-JAN-18:10 |
February | 1295.83 | 01-FEB-10:09 | 1494.36 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.03 | 26-FEB-15:30 | 1402.78 | 12-FEB-00:55 |
March | 1295.83 | 01-MAR-10:09 | 1427.69 | 21-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.97 | 11-MAR-16:00 | 901.04 | 22-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 1302.63 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.47 | 16-APR-14:10 | 450.74 | 05-APR-05:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.48 | 29-MAY-18:00 | 364.41 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.86 | 25-JUN-16:10 | 267.98 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1055.50 | 27-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.60 | 08-JUL-18:53 | 185.20 | 28-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 1254.33 | 24-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.39 | 06-AUG-14:00 | 87.94 | 31-AUG-05:00 |
September | 1295.83 | 01-SEP-09:09 | 1356.03 | 29-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.30 | 17-SEP-15:00 | 239.53 | 30-SEP-19:00 |
October | 1295.83 | 02-OCT-09:09 | 1522.90 | 30-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.85 | 09-OCT-15:43 | 540.30 | 28-OCT-03:53 |
November | 1295.83 | 01-NOV-09:09 | 1500.56 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.17 | 19-NOV-15:10 | 779.18 | 07-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1411.95 | 06-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1345.25 | 17-DEC-03:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.94 | |||||
Maximum of Months | 1295.83 | 1522.90 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 234.39 | 1402.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2196.45 | 03-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1710.14 | 07-JAN-18:03 |
February | 2010.83 | 01-FEB-10:09 | 2318.91 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 28-FEB-15:00 | 2092.81 | 12-FEB-00:55 |
March | 2010.83 | 01-MAR-10:09 | 2228.45 | 21-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.40 | 30-MAR-16:00 | 1359.84 | 22-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 2084.50 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.30 | 16-APR-14:10 | 701.36 | 05-APR-05:00 |
May | 2010.83 | 01-MAY-09:09 | 1746.80 | 24-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.97 | 07-MAY-12:10 | 548.31 | 10-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1629.84 | 23-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.89 | 11-JUN-15:00 | 407.60 | 07-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1835.92 | 27-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.13 | 08-JUL-18:53 | 296.83 | 28-JUL-22:00 |
August | 2010.83 | 01-AUG-09:09 | 2024.82 | 24-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.61 | 06-AUG-13:58 | 165.80 | 31-AUG-05:00 |
September | 2010.83 | 01-SEP-09:09 | 2130.41 | 29-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 17-SEP-15:00 | 362.77 | 30-SEP-19:00 |
October | 2010.83 | 02-OCT-09:09 | 2363.20 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.49 | 09-OCT-15:38 | 839.88 | 28-OCT-03:53 |
November | 2010.83 | 01-NOV-09:09 | 2333.33 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1225.63 | 07-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2198.55 | 06-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2011.72 | 17-DEC-03:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1629.84 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.80 | |||||
Maximum of Months | 2010.83 | 2363.20 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 323.89 | 2092.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1433.50 | 03-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1182.97 | 07-JAN-18:10 |
February | 1295.83 | 01-FEB-10:09 | 1494.36 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 | 26-FEB-13:30 | 1499.58 | 12-FEB-00:55 |
March | 1295.83 | 01-MAR-10:09 | 1443.43 | 21-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.95 | 30-MAR-16:00 | 1035.43 | 22-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 1366.10 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.86 | 16-APR-12:10 | 532.73 | 05-APR-05:00 |
May | 1295.83 | 01-MAY-09:09 | 1266.53 | 24-MAY-07:30 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.09 | 07-MAY-12:10 | 393.17 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 1119.04 | 23-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.99 | 25-JUN-16:04 | 312.37 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1225.96 | 27-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.86 | 08-JUL-18:50 | 238.12 | 28-JUL-22:00 |
August | 1295.83 | 01-AUG-09:09 | 1327.51 | 24-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.10 | 06-AUG-13:58 | 155.90 | 31-AUG-05:00 |
September | 1295.83 | 01-SEP-09:09 | 1392.40 | 29-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.51 | 17-SEP-12:20 | 279.81 | 30-SEP-19:00 |
October | 1295.83 | 02-OCT-09:09 | 1522.90 | 30-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.06 | 09-OCT-13:43 | 619.97 | 28-OCT-03:53 |
November | 1295.83 | 01-NOV-09:09 | 1511.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 888.22 | 07-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1435.03 | 06-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1525.68 | 17-DEC-03:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1119.04 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.90 | |||||
Maximum of Months | 1295.83 | 1522.90 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 213.10 | 1525.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2222.17 | 03-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3769.70 | 07-JAN-18:03 |
February | 2010.79 | 01-FEB-10:09 | 2320.29 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 220.76 | 26-FEB-13:10 | 4432.83 | 12-FEB-00:55 |
March | 2010.79 | 01-MAR-10:09 | 2234.71 | 21-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 134.81 | 11-MAR-16:00 | 2733.97 | 22-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 2087.33 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.51 | 16-APR-12:10 | 1524.13 | 05-APR-05:00 |
May | 2010.79 | 01-MAY-09:09 | 1646.65 | 24-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.52 | 07-MAY-12:00 | 1223.14 | 10-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 737.23 | 11-JUN-14:52 | 906.67 | 07-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1784.22 | 27-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 712.44 | 08-JUL-18:53 | 631.12 | 28-JUL-22:00 |
August | 2010.79 | 01-AUG-09:09 | 2019.30 | 24-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 750.00 | 06-AUG-14:00 | 391.12 | 25-AUG-04:47 |
September | 2010.79 | 01-SEP-09:09 | 2149.80 | 29-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.47 | 17-SEP-15:00 | 828.49 | 29-SEP-04:57 |
October | 2010.79 | 02-OCT-09:09 | 2363.27 | 30-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.48 | 08-OCT-13:52 | 1652.06 | 28-OCT-03:53 |
November | 2010.79 | 01-NOV-09:09 | 2342.66 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.60 | 19-NOV-14:52 | 2560.04 | 30-NOV-22:03 |
December | 2010.79 | 01-DEC-10:09 | 2226.11 | 06-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3943.51 | 17-DEC-03:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.12 | |||||
Maximum of Months | 2010.79 | 2363.27 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 750.00 | 4432.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1410.52 | 03-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2491.17 | 07-JAN-18:03 |
February | 1239.33 | 01-FEB-08:09 | 1494.59 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 104.66 | 26-FEB-15:50 | 2955.19 | 12-FEB-01:00 |
March | 1239.33 | 01-MAR-08:09 | 1428.82 | 21-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.27 | 11-MAR-18:03 | 1797.30 | 22-MAR-05:00 |
April | 1239.33 | 03-APR-07:10 | 1306.19 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.43 | 08-APR-17:02 | 1002.22 | 05-APR-05:00 |
May | 1239.33 | 01-MAY-07:10 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.09 | 29-MAY-17:50 | 823.06 | 10-MAY-04:00 |
June | 1239.33 | 01-JUN-07:10 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 496.98 | 11-JUN-15:10 | 622.83 | 07-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 1062.47 | 27-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 497.67 | 08-JUL-18:53 | 420.01 | 02-JUL-03:00 |
August | 1239.33 | 01-AUG-07:10 | 1258.36 | 24-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 496.93 | 06-AUG-13:53 | 260.48 | 29-AUG-01:53 |
September | 1239.33 | 01-SEP-07:10 | 1358.15 | 29-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.29 | 17-SEP-14:50 | 541.77 | 29-SEP-04:57 |
October | 1239.33 | 02-OCT-07:10 | 1522.92 | 30-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.19 | 09-OCT-15:30 | 1095.97 | 28-OCT-03:53 |
November | 1239.33 | 01-NOV-07:10 | 1500.98 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.15 | 19-NOV-14:52 | 1703.52 | 30-NOV-22:03 |
December | 1239.33 | 01-DEC-08:09 | 1413.34 | 06-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2625.13 | 17-DEC-03:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.48 | |||||
Maximum of Months | 1239.33 | 1522.92 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 497.67 | 2955.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2201.81 | 03-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3814.85 | 07-JAN-18:03 |
February | 2010.83 | 01-FEB-10:09 | 2320.34 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 | 28-FEB-15:00 | 4640.03 | 11-FEB-18:03 |
March | 2010.83 | 01-MAR-10:09 | 2232.60 | 21-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.44 | 30-MAR-16:00 | 2764.72 | 22-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 2092.76 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.90 | 08-APR-17:02 | 1528.51 | 05-APR-05:00 |
May | 2010.83 | 01-MAY-09:09 | 1763.21 | 24-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.47 | 07-MAY-12:00 | 1243.93 | 10-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1650.07 | 23-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 736.82 | 11-JUN-15:20 | 914.14 | 07-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1850.90 | 27-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 718.00 | 08-JUL-18:53 | 629.25 | 28-JUL-22:00 |
August | 2010.83 | 01-AUG-09:09 | 2034.74 | 24-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 679.10 | 06-AUG-13:53 | 399.92 | 25-AUG-04:47 |
September | 2010.83 | 01-SEP-09:09 | 2137.58 | 29-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.93 | 17-SEP-15:00 | 830.83 | 29-SEP-04:57 |
October | 2010.83 | 02-OCT-09:09 | 2363.32 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.11 | 09-OCT-16:06 | 1765.60 | 28-OCT-03:53 |
November | 2010.83 | 01-NOV-09:09 | 2334.43 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2601.77 | 07-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2203.86 | 06-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4086.63 | 17-DEC-03:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1650.07 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.92 | |||||
Maximum of Months | 2010.83 | 2363.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 736.82 | 4640.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1434.22 | 03-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2546.31 | 07-JAN-18:03 |
February | 1295.83 | 01-FEB-10:09 | 1494.59 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 159.36 | 26-FEB-13:10 | 3165.40 | 11-FEB-18:03 |
March | 1295.83 | 01-MAR-10:09 | 1444.03 | 21-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.52 | 30-MAR-16:00 | 1852.09 | 22-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 1367.28 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.22 | 16-APR-12:10 | 1024.22 | 05-APR-05:00 |
May | 1295.83 | 01-MAY-09:09 | 1268.01 | 24-MAY-07:30 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.37 | 07-MAY-12:00 | 854.81 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 1121.93 | 23-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.50 | 11-JUN-15:06 | 643.70 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1228.19 | 27-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 444.39 | 08-JUL-18:50 | 428.99 | 28-JUL-22:00 |
August | 1295.83 | 01-AUG-09:09 | 1328.97 | 24-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 507.89 | 06-AUG-14:00 | 300.82 | 29-AUG-01:53 |
September | 1295.83 | 01-SEP-09:09 | 1393.40 | 29-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.74 | 17-SEP-12:10 | 548.64 | 29-SEP-04:57 |
October | 1295.83 | 02-OCT-09:09 | 1522.92 | 30-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.57 | 08-OCT-13:52 | 1141.45 | 28-OCT-03:53 |
November | 1295.83 | 01-NOV-09:09 | 1511.17 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1709.11 | 30-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 1435.74 | 06-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2692.89 | 17-DEC-03:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1121.93 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.82 | |||||
Maximum of Months | 1295.83 | 1522.92 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 507.89 | 3165.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2222.03 | 03-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4463.71 | 07-JAN-18:03 |
February | 2010.79 | 01-FEB-10:09 | 2320.24 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 385.71 | 26-FEB-13:20 | 5527.45 | 12-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 2234.58 | 21-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 199.58 | 11-MAR-18:03 | 3374.22 | 22-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 2087.09 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.80 | 16-APR-12:10 | 1828.92 | 05-APR-04:53 |
May | 2010.79 | 01-MAY-09:09 | 1646.39 | 24-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.19 | 07-MAY-12:00 | 1402.79 | 10-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 906.14 | 11-JUN-15:00 | 1112.81 | 07-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1783.80 | 27-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 802.05 | 08-JUL-18:53 | 765.13 | 01-JUL-20:00 |
August | 2010.79 | 01-AUG-09:09 | 2019.00 | 24-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 886.43 | 06-AUG-13:53 | 513.03 | 25-AUG-04:53 |
September | 2010.79 | 01-SEP-09:09 | 2149.60 | 29-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 374.87 | 17-SEP-14:50 | 930.09 | 29-SEP-04:53 |
October | 2010.79 | 02-OCT-09:09 | 2363.27 | 30-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.70 | 08-OCT-13:52 | 1849.45 | 28-OCT-03:53 |
November | 2010.79 | 01-NOV-09:09 | 2342.64 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.27 | 19-NOV-14:52 | 3166.02 | 30-NOV-22:03 |
December | 2010.79 | 01-DEC-10:09 | 2225.98 | 06-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4462.04 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.03 | |||||
Maximum of Months | 2010.79 | 2363.27 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 906.14 | 5527.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1410.45 | 03-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3092.21 | 07-JAN-05:10 |
February | 1295.83 | 01-FEB-10:09 | 1494.56 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 173.27 | 26-FEB-15:50 | 3684.98 | 12-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1428.75 | 21-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 134.92 | 11-MAR-18:03 | 2249.37 | 22-MAR-05:00 |
April | 1295.83 | 03-APR-09:09 | 1306.08 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.00 | 16-APR-14:00 | 1214.79 | 05-APR-04:53 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.91 | 29-MAY-17:42 | 949.50 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 592.49 | 11-JUN-15:20 | 768.51 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1062.32 | 27-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 549.55 | 08-JUL-18:50 | 551.59 | 01-JUL-20:00 |
August | 1295.83 | 01-AUG-09:09 | 1258.23 | 24-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 578.48 | 06-AUG-13:53 | 336.08 | 25-AUG-04:53 |
September | 1295.83 | 01-SEP-09:09 | 1358.05 | 29-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.14 | 17-SEP-14:50 | 613.35 | 29-SEP-04:53 |
October | 1295.83 | 02-OCT-09:09 | 1522.92 | 30-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.62 | 08-OCT-13:52 | 1236.61 | 28-OCT-03:53 |
November | 1295.83 | 01-NOV-09:09 | 1500.98 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.09 | 19-NOV-14:52 | 2108.62 | 30-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 1413.27 | 06-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2973.19 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.08 | |||||
Maximum of Months | 1295.83 | 1522.92 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 592.49 | 3684.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2201.69 | 03-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4523.47 | 07-JAN-18:03 |
February | 2010.83 | 01-FEB-10:09 | 2320.29 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.24 | 28-FEB-15:00 | 5527.24 | 12-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 2232.47 | 21-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 127.29 | 30-MAR-16:00 | 3374.10 | 22-MAR-05:00 |
April | 2010.83 | 03-APR-09:09 | 2092.53 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.06 | 16-APR-14:00 | 1837.65 | 05-APR-04:53 |
May | 2010.83 | 01-MAY-09:09 | 1762.93 | 24-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 283.68 | 07-MAY-12:00 | 1432.72 | 10-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1649.51 | 23-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 896.59 | 11-JUN-15:00 | 1123.60 | 07-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1850.47 | 27-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 803.91 | 08-JUL-18:53 | 766.99 | 01-JUL-20:00 |
August | 2010.83 | 01-AUG-09:09 | 2034.43 | 24-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 827.29 | 06-AUG-13:58 | 528.12 | 25-AUG-04:53 |
September | 2010.83 | 01-SEP-09:09 | 2137.38 | 29-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.55 | 17-SEP-14:50 | 936.10 | 29-SEP-04:53 |
October | 2010.83 | 02-OCT-09:09 | 2363.32 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.27 | 09-OCT-15:58 | 2009.40 | 28-OCT-03:53 |
November | 2010.83 | 01-NOV-09:09 | 2334.42 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3168.34 | 30-NOV-22:03 |
December | 2010.83 | 01-DEC-10:09 | 2203.74 | 06-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4459.99 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1649.51 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.12 | |||||
Maximum of Months | 2010.83 | 2363.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 896.59 | 5527.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1434.13 | 03-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3092.18 | 07-JAN-05:08 |
February | 1295.83 | 01-FEB-10:09 | 1494.56 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 220.37 | 26-FEB-13:20 | 3787.95 | 11-FEB-18:03 |
March | 1295.83 | 01-MAR-10:09 | 1443.95 | 21-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.96 | 30-MAR-16:00 | 2249.34 | 22-MAR-05:00 |
April | 1295.83 | 03-APR-09:09 | 1367.13 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.78 | 16-APR-12:10 | 1241.96 | 05-APR-04:53 |
May | 1295.83 | 01-MAY-09:09 | 1267.89 | 24-MAY-07:30 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.19 | 07-MAY-12:00 | 992.56 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 1121.58 | 23-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 550.08 | 11-JUN-15:16 | 792.21 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1227.92 | 27-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 510.75 | 08-JUL-18:50 | 528.13 | 01-JUL-20:00 |
August | 1295.83 | 01-AUG-09:09 | 1328.79 | 24-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 611.77 | 06-AUG-13:53 | 379.82 | 29-AUG-01:53 |
September | 1295.83 | 01-SEP-09:09 | 1393.27 | 29-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.51 | 24-SEP-12:40 | 625.58 | 29-SEP-04:53 |
October | 1295.83 | 02-OCT-09:09 | 1522.92 | 30-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.05 | 08-OCT-13:52 | 1301.13 | 28-OCT-03:53 |
November | 1295.83 | 01-NOV-09:09 | 1511.16 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.79 | 19-NOV-14:52 | 2115.94 | 30-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 1435.65 | 06-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2973.16 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1121.58 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.82 | |||||
Maximum of Months | 1295.83 | 1522.92 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 611.77 | 3787.95 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5919.59 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5919.59 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5919.59 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5919.59 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5919.59 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5919.59 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5919.59 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5919.59 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5919.59 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5919.59 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5919.59 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5919.59 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3798.06 | 07-JAN-18:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 | 28-FEB-15:00 | 4739.89 | 12-FEB-00:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.03 | 30-MAR-16:00 | 3037.11 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.02 | 16-APR-13:52 | 1522.92 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.30 | 07-MAY-12:30 | 1206.22 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.18 | 11-JUN-15:00 | 826.96 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.67 | 08-JUL-18:53 | 597.96 | 28-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.04 | 06-AUG-14:00 | 366.42 | 25-AUG-04:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.18 | 17-SEP-14:55 | 833.96 | 29-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.77 | 09-OCT-16:00 | 1780.06 | 28-OCT-03:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2594.39 | 21-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4573.64 | 17-DEC-03:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.04 | 4739.89 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6521.85 | 07-JAN-18:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.35 | 26-FEB-14:53 | 8061.38 | 12-FEB-00:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.68 | 11-MAR-16:00 | 5119.65 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.94 | 16-APR-11:52 | 2646.68 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.91 | 07-MAY-12:00 | 2149.14 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1167.15 | 11-JUN-14:52 | 1468.96 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.90 | 08-JUL-18:53 | 1043.44 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1190.85 | 06-AUG-14:00 | 698.23 | 25-AUG-04:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.62 | 17-SEP-15:00 | 1480.51 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.99 | 09-OCT-15:53 | 3018.66 | 28-OCT-03:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.55 | 19-NOV-14:52 | 4436.36 | 21-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7606.79 | 17-DEC-03:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 698.23 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1190.85 | 8061.38 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7112.05 | 07-JAN-18:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.60 | 26-FEB-14:50 | 8444.89 | 11-FEB-18:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.00 | 11-MAR-16:00 | 5024.26 | 22-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.21 | 16-APR-14:00 | 2868.63 | 05-APR-04:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.28 | 29-MAY-18:00 | 2152.78 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 969.78 | 11-JUN-15:00 | 1683.83 | 07-JUN-03:04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1041.91 | 08-JUL-18:53 | 1189.95 | 01-JUL-20:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 947.26 | 06-AUG-14:00 | 755.37 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.58 | 17-SEP-15:00 | 1406.18 | 29-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.93 | 08-OCT-13:54 | 3082.85 | 28-OCT-03:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.11 | 19-NOV-14:52 | 4729.77 | 30-NOV-22:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7098.90 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 755.37 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1041.91 | 8444.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 109093.15 | 02-JAN-04:03 | 0.00 | 4665.70 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 109664.00 | 27-FEB-04:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 111022.50 | 13-MAR-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 109035.55 | 10-APR-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 107862.13 | 15-MAY-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 100968.31 | 10-JUN-05:02 | 8976.13 | 11664.26 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 92535.35 | 03-JUL-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87250.99 | 26-AUG-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 100330.03 | 14-SEP-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 110967.27 | 30-OCT-03:02 | 0.00 | 4665.70 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 112151.79 | 20-NOV-04:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 114909.02 | 11-DEC-04:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 87250.99 | 0.00 | 4665.70 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 114909.02 | 8976.13 | 11664.26 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 87864.18 | 02-JAN-06:02 | 8061.19 | 10475.32 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90363.19 | 21-FEB-04:03 | 0.00 | 4190.13 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 92577.88 | 13-MAR-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91042.64 | 05-APR-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 93899.66 | 08-MAY-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 90526.79 | 01-JUN-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 89480.77 | 29-JUL-03:02 | 0.00 | 5237.66 | 30214.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82140.59 | 08-AUG-04:23 | 0.00 | 8380.26 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 95243.17 | 18-SEP-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 94071.26 | 16-OCT-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 96114.60 | 13-NOV-04:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 92234.92 | 11-DEC-04:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 82140.59 | 0.00 | 4190.13 | 30214.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96114.60 | 8061.19 | 10475.32 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 65721.43 | 05-JAN-11:33 | 45948.79 | 56563.94 | 54385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77635.86 | 23-FEB-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81356.74 | 30-MAR-04:03 | 0.00 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82417.86 | 21-APR-04:03 | 0.00 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84764.16 | 31-MAY-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84794.05 | 20-JUN-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84563.52 | 26-JUL-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84261.34 | 25-AUG-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84617.26 | 11-SEP-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82354.80 | 18-OCT-04:03 | 0.00 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 81820.84 | 04-NOV-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79238.75 | 14-DEC-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 65721.43 | 0.00 | 5237.66 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84794.05 | 45948.79 | 56563.94 | 54385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 30488.72 | 20-JAN-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38955.49 | 28-FEB-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80162.48 | 31-MAR-04:03 | 0.00 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81971.81 | 24-APR-04:03 | 0.00 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85140.36 | 30-MAY-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86798.98 | 19-JUN-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84643.21 | 03-JUL-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84199.07 | 08-AUG-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85801.98 | 05-SEP-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81051.42 | 18-OCT-04:03 | 0.00 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75235.52 | 04-NOV-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 61707.63 | 13-DEC-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 30488.72 | 0.00 | 5237.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86798.98 | 15316.26 | 18854.65 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3738.25 | 31-JAN-15:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.97 |
February | 5987.05 | 28-FEB-15:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 0.00 |
March | 9132.41 | 30-MAR-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.84 |
April | 10617.15 | 19-APR-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.82 |
May | 12398.95 | 30-MAY-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.18 |
June | 16106.91 | 25-JUN-16:41 | 708.51 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 238.56 | 0.00 |
July | 16295.45 | 09-JUL-18:01 | 0.00 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 124.89 | 0.00 |
August | 12345.25 | 14-AUG-05:03 | 1214.60 | 1578.34 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 |
September | 12045.38 | 05-SEP-03:02 | 0.00 | 657.64 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.94 |
October | 11399.33 | 18-OCT-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.15 |
November | 5685.05 | 02-NOV-14:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.53 |
December | 7211.23 | 13-DEC-06:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3738.25 | 0.00 | 565.58 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16295.45 | 2010.79 | 1578.34 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 238.56 | 104.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3099.59 | 31-JAN-06:02 | 652.28 | 847.62 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.13 |
February | 6232.97 | 27-FEB-09:40 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.24 |
March | 7103.79 | 14-MAR-09:30 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.09 |
April | 8650.84 | 17-APR-08:40 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.79 |
May | 16058.82 | 07-MAY-09:23 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.77 |
June | 16295.78 | 25-JUN-10:02 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 42.05 | 0.00 |
July | 16417.45 | 04-JUL-09:32 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 |
August | 11289.96 | 27-AUG-09:43 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 0.00 |
September | 14803.05 | 24-SEP-09:43 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.12 |
October | 7662.42 | 10-OCT-09:30 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 |
November | 5862.82 | 06-NOV-09:30 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.39 |
December | 3611.55 | 13-DEC-04:02 | 0.00 | 423.81 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3099.59 | 0.00 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16417.45 | 1295.83 | 937.20 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 42.05 | 162.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11186.28 | 26-JAN-13:40 | 9615.76 | 7271.59 | 11381.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.43 |
February | 16062.58 | 26-FEB-12:43 | 303.66 | 242.40 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.11 |
March | 13802.25 | 30-MAR-13:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 31.40 | 0.00 |
April | 13594.02 | 17-APR-14:00 | 4021.67 | 2908.64 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 | 0.00 |
May | 14006.53 | 30-MAY-03:02 | 0.00 | 657.65 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.09 |
June | 17343.17 | 25-JUN-16:41 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 238.53 | 0.00 |
July | 18627.18 | 09-JUL-16:01 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 189.65 | 0.00 |
August | 15137.59 | 27-AUG-15:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 138.92 | 0.00 |
September | 19428.00 | 24-SEP-13:02 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 44.71 | 0.00 |
October | 19828.97 | 08-OCT-14:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 |
November | 19614.22 | 11-NOV-13:13 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.66 |
December | 13771.07 | 10-DEC-12:53 | 303.66 | 242.40 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11186.28 | 0.00 | 242.40 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19828.97 | 9615.76 | 7271.59 | 11381.76 | 0.00 | 0.00 | 0.00 | 0.00 | 238.53 | 233.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4773.26 | 20-JAN-16:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.51 |
February | 9235.97 | 27-FEB-16:40 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 |
March | 15878.61 | 30-MAR-05:03 | 521.82 | 678.09 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 |
April | 20634.32 | 09-APR-16:32 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.76 |
May | 16209.18 | 29-MAY-17:53 | 0.00 | 208.28 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 41.05 | 0.00 |
June | 22469.47 | 25-JUN-16:01 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 131.49 | 0.00 |
July | 22967.04 | 04-JUL-17:31 | 0.00 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 37.36 | 0.00 |
August | 21925.47 | 13-AUG-16:22 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 50.77 | 0.00 |
September | 20567.27 | 24-SEP-16:22 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 13.31 | 0.00 |
October | 20561.19 | 08-OCT-15:22 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 | 0.00 |
November | 12136.88 | 04-NOV-03:02 | 0.00 | 423.81 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.33 |
December | 16398.99 | 13-DEC-06:03 | 521.82 | 678.09 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4773.26 | 0.00 | 208.28 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22967.04 | 1239.33 | 937.20 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 131.49 | 84.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2536.78 | 20-JAN-15:50 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.53 |
February | 4205.37 | 28-FEB-15:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 | 0.00 |
March | 6423.60 | 30-MAR-16:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 105.78 | 0.00 |
April | 7562.71 | 12-APR-14:40 | 3846.22 | 2908.57 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 57.43 | 0.00 |
May | 8534.72 | 30-MAY-15:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 92.33 | 0.00 |
June | 15148.92 | 25-JUN-16:41 | 708.51 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 538.70 | 0.00 |
July | 12120.27 | 15-JUL-03:02 | 0.00 | 657.64 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.78 |
August | 13329.16 | 06-AUG-17:01 | 0.00 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 496.17 | 0.00 |
September | 11099.43 | 27-SEP-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.61 |
October | 6254.82 | 02-OCT-14:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 56.82 | 0.00 |
November | 3748.10 | 03-NOV-14:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.58 |
December | 3251.69 | 13-DEC-06:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2536.78 | 0.00 | 565.58 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15148.92 | 3846.22 | 2908.57 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 538.70 | 150.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2742.90 | 26-JAN-13:38 | 6196.63 | 4685.99 | 7334.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.82 |
February | 4633.63 | 02-FEB-11:45 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.75 |
March | 5573.89 | 14-MAR-11:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.21 |
April | 8472.37 | 17-APR-10:10 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.78 |
May | 16566.35 | 07-MAY-09:32 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.98 |
June | 17090.83 | 25-JUN-10:02 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 80.65 | 0.00 |
July | 17120.02 | 04-JUL-09:32 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.82 |
August | 17004.03 | 06-AUG-11:02 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 95.35 | 0.00 |
September | 14463.72 | 24-SEP-10:13 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 |
October | 6658.27 | 11-OCT-10:20 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 |
November | 3842.96 | 06-NOV-09:50 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.34 |
December | 3836.87 | 01-DEC-10:45 | 0.00 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2742.90 | 0.00 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17120.02 | 6196.63 | 4685.99 | 7334.73 | 0.00 | 0.00 | 0.00 | 0.00 | 95.35 | 459.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13959.58 | 26-JAN-13:38 | 9615.76 | 7271.59 | 11381.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.24 |
February | 17422.17 | 26-FEB-13:03 | 303.66 | 242.40 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.68 |
March | 13246.66 | 30-MAR-13:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 71.45 | 0.00 |
April | 14036.06 | 17-APR-15:00 | 3846.30 | 2908.64 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 58.48 | 0.00 |
May | 11273.90 | 15-MAY-14:10 | 3846.30 | 2908.64 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 0.00 |
June | 17362.02 | 25-JUN-16:41 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 545.87 | 0.00 |
July | 13970.14 | 15-JUL-03:02 | 0.00 | 657.65 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.96 |
August | 18216.02 | 06-AUG-13:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 546.27 | 0.00 |
September | 18435.74 | 24-SEP-12:53 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 99.43 | 0.00 |
October | 19076.74 | 09-OCT-14:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 |
November | 18440.17 | 11-NOV-13:43 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.06 |
December | 11380.90 | 08-DEC-14:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11273.90 | 0.00 | 242.40 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19076.74 | 9615.76 | 7271.59 | 11381.76 | 0.00 | 0.00 | 0.00 | 0.00 | 546.27 | 557.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3545.37 | 05-JAN-16:33 | 3717.98 | 2811.59 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.66 |
February | 6558.40 | 27-FEB-17:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.89 |
March | 9128.98 | 30-MAR-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 70.52 | 0.00 |
April | 17015.57 | 09-APR-17:01 | 0.00 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.28 |
May | 17705.99 | 21-MAY-17:42 | 0.00 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.31 |
June | 18723.39 | 25-JUN-16:41 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 267.89 | 0.00 |
July | 18992.51 | 04-JUL-17:31 | 0.00 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 97.77 | 0.00 |
August | 18642.02 | 06-AUG-17:01 | 0.00 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 236.86 | 0.00 |
September | 12086.02 | 27-SEP-05:03 | 521.82 | 678.09 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 |
October | 9329.71 | 11-OCT-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 27.59 | 0.00 |
November | 6016.06 | 06-NOV-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.92 |
December | 3710.80 | 13-DEC-06:03 | 521.82 | 678.09 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3545.37 | 0.00 | 260.35 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18992.51 | 3717.98 | 2811.59 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 267.89 | 378.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2784.04 | 20-JAN-17:00 | 1923.11 | 1788.54 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.44 |
February | 3669.65 | 28-FEB-15:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 |
March | 7047.72 | 30-MAR-16:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 127.45 | 0.00 |
April | 7312.59 | 18-APR-14:20 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 28.78 | 0.00 |
May | 9408.12 | 30-MAY-15:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 112.71 | 0.00 |
June | 13531.80 | 26-JUN-05:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.27 |
July | 17321.87 | 23-JUL-17:01 | 0.00 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 327.06 | 0.00 |
August | 17796.77 | 06-AUG-17:01 | 0.00 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 551.07 | 0.00 |
September | 12892.92 | 27-SEP-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.21 |
October | 6564.27 | 02-OCT-14:50 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 71.88 | 0.00 |
November | 3619.81 | 04-NOV-05:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.50 |
December | 3042.60 | 13-DEC-15:10 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2784.04 | 0.00 | 565.58 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17796.77 | 1923.11 | 1788.54 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 551.07 | 152.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2421.86 | 31-JAN-17:00 | 1239.33 | 1173.56 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.52 |
February | 3421.08 | 28-FEB-15:00 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 28.16 | 0.00 |
March | 5339.66 | 30-MAR-11:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.68 |
April | 9781.82 | 16-APR-09:53 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.37 |
May | 15897.72 | 07-MAY-09:53 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.98 |
June | 16865.62 | 04-JUN-11:23 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 76.59 | 0.00 |
July | 17123.55 | 23-JUL-08:22 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.96 |
August | 17604.16 | 06-AUG-11:02 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 109.06 | 0.00 |
September | 10041.68 | 08-SEP-09:40 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 26.80 | 0.00 |
October | 6420.15 | 11-OCT-10:30 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
November | 3377.36 | 04-NOV-05:02 | 652.28 | 847.62 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.45 |
December | 2657.70 | 13-DEC-15:10 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2421.86 | 260.91 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17604.16 | 1295.83 | 1173.56 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 109.06 | 166.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7336.26 | 11-JAN-14:50 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.56 |
February | 13498.14 | 21-FEB-14:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.40 |
March | 13794.26 | 30-MAR-13:50 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 95.79 | 0.00 |
April | 15200.04 | 17-APR-14:05 | 3846.30 | 2908.64 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 40.57 | 0.00 |
May | 11023.85 | 30-MAY-14:30 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 120.53 | 0.00 |
June | 14042.79 | 29-JUN-05:03 | 809.75 | 1052.25 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.06 |
July | 19390.10 | 23-JUL-17:01 | 0.00 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 337.62 | 0.00 |
August | 20533.56 | 06-AUG-13:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 633.40 | 0.00 |
September | 20628.08 | 24-SEP-14:32 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 88.91 | 0.00 |
October | 21119.79 | 09-OCT-14:32 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.59 |
November | 17611.28 | 11-NOV-13:43 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.76 |
December | 9880.06 | 12-DEC-13:50 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7336.26 | 0.00 | 323.20 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21119.79 | 3846.30 | 2908.64 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 633.40 | 618.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3048.51 | 20-JAN-16:40 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.90 |
February | 6289.79 | 27-FEB-17:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.29 |
March | 9560.51 | 30-MAR-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 84.96 | 0.00 |
April | 17582.73 | 09-APR-17:33 | 0.00 | 208.28 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.25 |
May | 19310.26 | 21-MAY-17:42 | 0.00 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.48 |
June | 20179.44 | 11-JUN-17:12 | 0.00 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 201.58 | 0.00 |
July | 20520.56 | 23-JUL-17:01 | 0.00 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 89.15 | 0.00 |
August | 20643.38 | 06-AUG-17:01 | 0.00 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 263.79 | 0.00 |
September | 15117.86 | 03-SEP-15:32 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 69.78 | 0.00 |
October | 10863.14 | 09-OCT-16:33 | 260.91 | 208.28 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 0.00 |
November | 5661.05 | 06-NOV-16:10 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.58 |
December | 3192.92 | 12-DEC-14:50 | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3048.51 | 0.00 | 208.28 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20643.38 | 1295.83 | 937.20 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 263.79 | 149.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4952.59 | 02-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.67 |
February | 5638.68 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.72 |
March | 7023.93 | 13-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.79 |
April | 8310.96 | 17-APR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.60 | 0.00 |
May | 10962.25 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.69 |
June | 11125.54 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 |
July | 10602.35 | 03-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 |
August | 13408.52 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 |
September | 12465.49 | 05-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.20 |
October | 10779.22 | 10-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.47 |
November | 8321.76 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.12 |
December | 6830.15 | 13-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4952.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13408.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.60 | 282.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5428.65 | 27-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2801.92 |
February | 7959.34 | 12-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6806.23 |
March | 5057.09 | 15-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.56 |
April | 6190.98 | 17-APR-14:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.74 | 0.00 |
May | 8380.49 | 30-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.74 |
June | 8555.02 | 26-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.52 |
July | 8253.65 | 24-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.61 |
August | 8598.77 | 30-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.26 |
September | 7897.84 | 05-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.75 |
October | 5509.33 | 11-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.38 |
November | 4766.87 | 21-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3739.19 |
December | 5236.77 | 18-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2116.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4766.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8598.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.74 | 6806.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2134.95 | 31-JAN-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.68 |
February | 7167.35 | 28-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.41 |
March | 13968.58 | 30-MAR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.66 | 0.00 |
April | 18712.52 | 17-APR-14:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.05 | 0.00 |
May | 19033.05 | 16-MAY-15:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.80 | 0.00 |
June | 19401.19 | 12-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.98 | 0.00 |
July | 21473.12 | 07-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.90 | 0.00 |
August | 20461.65 | 01-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.39 | 0.00 |
September | 16953.81 | 06-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.05 | 0.00 |
October | 12443.83 | 10-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.16 | 0.00 |
November | 5739.47 | 06-NOV-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.91 |
December | 4145.75 | 12-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2134.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21473.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.98 | 275.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1859.89 | 23-JAN-17:00 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3895.39 | 24-FEB-17:50 | 70.15 | 289.36 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7173.25 | 31-MAR-24:00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7885.44 | 09-APR-18:13 | 0.00 | 86.81 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3499.96 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5356.39 | 30-JUN-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7236.04 | 31-JUL-23:53 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7861.64 | 13-AUG-19:32 | 0.00 | 144.69 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3247.60 | 30-SEP-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5166.67 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5914.96 | 06-NOV-17:00 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7699.27 | 19-DEC-17:00 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1859.89 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7885.44 | 222.14 | 520.85 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1527.92 | 27-JAN-17:00 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3616.38 | 24-FEB-17:50 | 70.15 | 289.36 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6725.37 | 31-MAR-24:00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7351.78 | 14-APR-18:20 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3309.83 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5146.10 | 30-JUN-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7016.36 | 31-JUL-23:53 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7416.96 | 13-AUG-18:35 | 0.00 | 57.88 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2744.13 | 30-SEP-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4483.19 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5514.27 | 06-NOV-17:00 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7111.63 | 08-DEC-17:00 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1527.92 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7416.96 | 222.14 | 520.85 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1531.88 | 20-JAN-17:00 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3626.26 | 28-FEB-17:00 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6464.41 | 31-MAR-23:20 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7415.28 | 14-APR-18:20 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3262.56 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5120.83 | 30-JUN-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7047.42 | 31-JUL-23:53 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7566.92 | 13-AUG-19:32 | 0.00 | 144.69 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2278.30 | 30-SEP-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4048.28 | 31-OCT-23:20 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5502.06 | 06-NOV-17:00 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7028.82 | 07-DEC-17:00 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1531.88 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7566.92 | 222.14 | 520.85 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91570.43 | 20-JAN-17:00 | 4808.68 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183221.00 | 28-FEB-17:00 | 4808.68 | 5919.59 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357933.25 | 31-MAR-24:00 | 0.00 | 328.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 365785.66 | 20-APR-15:30 | 4808.68 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175217.85 | 31-MAY-24:00 | 0.00 | 328.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267283.91 | 30-JUN-24:00 | 0.00 | 328.88 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359513.21 | 31-JUL-23:53 | 0.00 | 1315.53 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370334.94 | 07-AUG-21:12 | 1265.44 | 3288.82 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175586.24 | 30-SEP-24:00 | 0.00 | 328.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268167.23 | 31-OCT-24:00 | 0.00 | 328.88 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277199.09 | 06-NOV-17:00 | 4808.68 | 5919.59 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368140.31 | 12-DEC-17:00 | 4808.68 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91570.43 | 0.00 | 328.88 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370334.94 | 4808.68 | 5919.59 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.167172E+13 | 1134900.15 | 31-JAN-16:00 | 0.325995E+12 | 1559351.01 | 09-JAN-07:10 |
February | 0.191697E+13 | 1376166.00 | 27-FEB-16:30 | 0.212654E+12 | 1599222.50 | 13-FEB-07:10 |
March | 0.265730E+13 | 1762364.59 | 29-MAR-15:50 | 0.865959E+11 | 656971.21 | 18-MAR-06:10 |
April | 0.301480E+13 | 2018713.57 | 12-APR-15:09 | 0.625374E+11 | 745834.77 | 06-APR-06:10 |
May | 0.207622E+13 | 1586520.64 | 16-MAY-15:39 | 0.584747E+11 | 268979.39 | 11-MAY-06:10 |
June | 0.261561E+13 | 1712724.82 | 19-JUN-15:00 | 0.521492E+11 | 128934.32 | 03-JUN-11:00 |
July | 0.312169E+13 | 1910194.72 | 07-JUL-15:20 | 0.483364E+11 | 66680.97 | 07-JUL-11:30 |
August | 0.366896E+13 | 2051130.69 | 03-AUG-15:50 | 0.512757E+11 | 70462.62 | 25-AUG-13:50 |
September | 0.206387E+13 | 1522680.10 | 05-SEP-15:20 | 0.495716E+11 | 189594.16 | 14-SEP-14:00 |
October | 0.229729E+13 | 1619975.52 | 02-OCT-15:00 | 0.654302E+11 | 707441.57 | 26-OCT-06:10 |
November | 0.251032E+13 | 1521432.58 | 27-NOV-16:00 | 0.100687E+12 | 1128143.48 | 22-NOV-07:10 |
December | 0.287534E+13 | 1645685.23 | 12-DEC-16:00 | 0.184666E+12 | 1311098.38 | 18-DEC-07:10 |
Annual Sum or Average | 0.304901E+14 | 0.129837E+13 | ||||
Minimum of Months | 0.167172E+13 | 1134900.15 | 0.483364E+11 | 66680.97 | ||
Maximum of Months | 0.366896E+13 | 2051130.69 | 0.325995E+12 | 1599222.50 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.312650E+12 | 0.689787E+11 | 0.811612E+12 | 0.164871E+12 | 0.170947E+12 | 0.225934E+11 | 0.00 | 0.924887E+11 | 0.192115E+11 | 0.261356E+10 | 0.575761E+10 | 0.00 | 0.00 |
February | 0.283633E+12 | 0.580988E+11 | 0.102011E+13 | 0.148927E+12 | 0.160822E+12 | 0.279201E+11 | 0.00 | 0.161428E+12 | 0.505042E+11 | 0.183575E+10 | 0.369348E+10 | 0.00 | 0.00 |
March | 0.333264E+12 | 0.582202E+11 | 0.146267E+13 | 0.165151E+12 | 0.196678E+12 | 0.471699E+11 | 0.00 | 0.287151E+12 | 0.104195E+12 | 0.934868E+09 | 0.187303E+10 | 0.00 | 0.00 |
April | 0.296614E+12 | 0.502467E+11 | 0.170311E+13 | 0.159525E+12 | 0.203786E+12 | 0.664587E+11 | 0.00 | 0.408205E+12 | 0.125026E+12 | 0.295935E+09 | 0.153716E+10 | 0.00 | 0.00 |
May | 0.319000E+12 | 0.466141E+11 | 0.820521E+12 | 0.165009E+12 | 0.229264E+12 | 0.828557E+11 | 0.00 | 0.265424E+12 | 0.144240E+12 | 52100105.45 | 0.324272E+10 | 0.00 | 0.00 |
June | 0.317018E+12 | 0.427810E+11 | 0.110677E+13 | 0.159787E+12 | 0.252068E+12 | 0.104173E+12 | 0.00 | 0.454243E+12 | 0.172485E+12 | 14620867.52 | 0.626239E+10 | 0.00 | 0.00 |
July | 0.297201E+12 | 0.450818E+11 | 0.143888E+13 | 0.164745E+12 | 0.258660E+12 | 0.118010E+12 | 0.00 | 0.597831E+12 | 0.194324E+12 | 0.00 | 0.696296E+10 | 0.00 | 0.00 |
August | 0.331525E+12 | 0.495156E+11 | 0.177780E+13 | 0.165150E+12 | 0.274450E+12 | 0.128724E+12 | 0.00 | 0.729556E+12 | 0.204519E+12 | 373973.73 | 0.772583E+10 | 0.00 | 0.00 |
September | 0.297540E+12 | 0.537025E+11 | 0.784732E+12 | 0.159523E+12 | 0.223429E+12 | 0.875610E+11 | 0.00 | 0.296503E+12 | 0.156541E+12 | 0.00 | 0.433473E+10 | 0.00 | 0.00 |
October | 0.311482E+12 | 0.618064E+11 | 0.112899E+13 | 0.164872E+12 | 0.199912E+12 | 0.560752E+11 | 0.00 | 0.260440E+12 | 0.111031E+12 | 40908317.60 | 0.264049E+10 | 0.00 | 0.00 |
November | 0.308315E+12 | 0.653412E+11 | 0.140306E+13 | 0.159633E+12 | 0.180385E+12 | 0.381132E+11 | 0.00 | 0.261490E+12 | 0.904909E+11 | 0.121863E+10 | 0.226869E+10 | 0.00 | 0.00 |
December | 0.302890E+12 | 0.704784E+11 | 0.175516E+13 | 0.164747E+12 | 0.175452E+12 | 0.220750E+11 | 0.00 | 0.296815E+12 | 0.817060E+11 | 0.193880E+10 | 0.408231E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.371113E+13 | 0.670866E+12 | 0.152134E+14 | 0.194194E+13 | 0.252585E+13 | 0.801729E+12 | 0.00 | 0.411157E+13 | 0.145427E+13 | 0.894555E+10 | 0.503814E+11 | 0.00 | 0.00 |
Minimum of Months | 0.283633E+12 | 0.427810E+11 | 0.784732E+12 | 0.148927E+12 | 0.160822E+12 | 0.220750E+11 | 0.00 | 0.924887E+11 | 0.192115E+11 | 0.00 | 0.153716E+10 | 0.00 | 0.00 |
Maximum of Months | 0.333264E+12 | 0.704784E+11 | 0.177780E+13 | 0.165151E+12 | 0.274450E+12 | 0.128724E+12 | 0.00 | 0.729556E+12 | 0.204519E+12 | 0.261356E+10 | 0.772583E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.264655E+12 | 0.00 | 0.613396E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.156916E+12 | 0.00 | 0.557376E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.236842E+11 | 0.00 | 0.629117E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.717924E+10 | 0.00 | 0.553581E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.327461E+10 | 0.00 | 0.552001E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.885605E+09 | 0.00 | 0.512636E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.483364E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 44854437.23 | 0.00 | 0.512309E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.558145E+09 | 0.00 | 0.490135E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.120352E+11 | 0.00 | 0.533949E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.453086E+11 | 0.00 | 0.553787E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.126126E+12 | 0.00 | 0.585404E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.640668E+12 | 0.00 | 0.657705E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.483364E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.264655E+12 | 0.00 | 0.629117E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 346632.45 | 03-JAN-08:09 | 54335.80 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 118954.02 | 03-JAN-08:20 | 195800.45 | 26-JAN-13:09 | 45955.96 | 07-JAN-05:10 | 0.00 | 01-JAN-00:10 |
February | 350974.44 | 01-FEB-08:09 | 54335.80 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 118957.65 | 01-FEB-08:20 | 147177.39 | 28-FEB-15:39 | 65820.21 | 28-FEB-15:39 | 0.00 | 01-FEB-00:10 |
March | 347491.78 | 21-MAR-07:10 | 54335.80 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 118954.74 | 21-MAR-07:19 | 181979.29 | 29-MAR-15:50 | 69360.56 | 30-MAR-14:39 | 0.00 | 01-MAR-00:10 |
April | 341640.55 | 03-APR-07:10 | 54335.80 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 118949.85 | 03-APR-07:19 | 280932.24 | 13-APR-14:50 | 73998.79 | 17-APR-14:20 | 0.00 | 01-APR-00:10 |
May | 326430.59 | 24-MAY-07:10 | 54335.80 | 01-MAY-05:10 | 439129.89 | 01-MAY-07:10 | 118937.15 | 24-MAY-07:19 | 276227.21 | 16-MAY-15:39 | 69808.60 | 16-MAY-15:39 | 0.00 | 01-MAY-00:10 |
June | 321357.89 | 23-JUN-07:10 | 54335.80 | 01-JUN-05:10 | 557421.28 | 01-JUN-07:10 | 118932.93 | 23-JUN-07:19 | 287700.46 | 02-JUN-13:39 | 68262.45 | 02-JUN-14:09 | 0.00 | 01-JUN-00:10 |
July | 330486.50 | 27-JUL-07:10 | 54335.80 | 01-JUL-05:10 | 675712.68 | 03-JUL-07:10 | 118940.54 | 27-JUL-07:19 | 238506.86 | 07-JUL-15:20 | 68424.05 | 07-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 339089.73 | 24-AUG-07:10 | 54335.80 | 01-AUG-05:10 | 794004.08 | 01-AUG-07:10 | 118947.72 | 24-AUG-07:19 | 241762.26 | 25-AUG-10:39 | 69327.91 | 25-AUG-13:50 | 0.00 | 01-AUG-00:10 |
September | 343869.80 | 29-SEP-07:10 | 54335.80 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 118951.71 | 29-SEP-07:19 | 255461.63 | 22-SEP-14:00 | 69667.27 | 13-SEP-14:50 | 0.00 | 01-SEP-00:10 |
October | 352689.08 | 30-OCT-07:10 | 54335.80 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 118959.08 | 30-OCT-07:19 | 182132.67 | 02-OCT-15:00 | 70083.33 | 10-OCT-13:30 | 0.00 | 01-OCT-00:10 |
November | 351688.64 | 01-NOV-07:10 | 54335.80 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 118958.25 | 01-NOV-07:19 | 147483.43 | 06-NOV-16:19 | 44750.85 | 21-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 346756.74 | 06-DEC-08:09 | 54335.80 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 118954.12 | 06-DEC-08:20 | 126125.02 | 14-DEC-08:30 | 45706.12 | 26-DEC-07:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 321357.89 | 54335.80 | 439129.89 | 118932.93 | 126125.02 | 44750.85 | 0.00 | |||||||
Maximum of Months | 352689.08 | 54335.80 | 794004.08 | 118959.08 | 287700.46 | 73998.79 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 119418.28 | 31-JAN-15:50 | 50484.77 | 19-JAN-15:00 | 5867.99 | 05-JAN-18:10 | 5613.48 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 195409.24 | 28-FEB-14:50 | 51473.78 | 28-FEB-14:00 | 5743.42 | 03-FEB-18:00 | 5613.48 | 01-FEB-07:10 | 0.00 | 0.00 |
March | 373662.49 | 30-MAR-14:39 | 92421.41 | 29-MAR-15:50 | 5583.23 | 18-MAR-16:10 | 5613.48 | 01-MAR-07:10 | 0.00 | 0.00 |
April | 437284.10 | 17-APR-14:20 | 92421.41 | 04-APR-13:30 | 4004.77 | 05-APR-18:00 | 5613.48 | 04-APR-08:00 | 0.00 | 0.00 |
May | 323288.67 | 19-MAY-13:09 | 92421.41 | 03-MAY-14:20 | 2994.85 | 10-MAY-18:00 | 5613.48 | 02-MAY-11:00 | 0.00 | 0.00 |
June | 362631.97 | 19-JUN-15:00 | 92421.41 | 01-JUN-08:20 | 2980.52 | 10-JUN-16:00 | 5613.48 | 01-JUN-06:40 | 0.00 | 0.00 |
July | 436071.58 | 07-JUL-15:00 | 92421.41 | 01-JUL-06:10 | 0.00 | 01-JUL-00:10 | 5613.48 | 01-JUL-06:10 | 0.00 | 0.00 |
August | 456189.80 | 17-AUG-13:09 | 92421.41 | 01-AUG-05:30 | 264.19 | 06-AUG-16:10 | 5613.48 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 329306.85 | 06-SEP-12:20 | 92421.41 | 01-SEP-10:09 | 0.00 | 01-SEP-00:10 | 5613.48 | 01-SEP-08:00 | 0.00 | 0.00 |
October | 346337.74 | 10-OCT-13:30 | 92421.41 | 02-OCT-09:50 | 2663.41 | 31-OCT-20:00 | 5613.48 | 02-OCT-08:39 | 0.00 | 0.00 |
November | 218208.27 | 02-NOV-13:50 | 70834.84 | 27-NOV-16:10 | 4329.13 | 22-NOV-18:10 | 5613.48 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 243200.64 | 12-DEC-14:30 | 52705.17 | 13-DEC-11:09 | 5337.55 | 02-DEC-17:00 | 5613.48 | 01-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 119418.28 | 50484.77 | 0.00 | 5613.48 | 0.00 | 0.00 | ||||
Maximum of Months | 456189.80 | 92421.41 | 5867.99 | 5613.48 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1134900.15 | 31-JAN-16:00 | 323165.75 | 439129.89 | 0.00 | 84889.13 | 94703.41 | 43528.69 | 0.00 | 99815.13 | 49668.15 |
February | 1376166.00 | 27-FEB-16:30 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 140915.42 | 43691.79 | 0.00 | 182128.98 | 50109.82 |
March | 1762364.59 | 29-MAR-15:50 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 181979.29 | 67053.01 | 0.00 | 341625.13 | 92421.41 |
April | 2018713.57 | 12-APR-15:09 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 260940.64 | 69507.41 | 0.00 | 398266.95 | 92421.41 |
May | 1586520.64 | 16-MAY-15:39 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 276227.21 | 69808.60 | 0.00 | 305360.46 | 92421.41 |
June | 1712724.82 | 19-JUN-15:00 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 225146.74 | 67788.01 | 0.00 | 362631.97 | 92421.41 |
July | 1910194.72 | 07-JUL-15:20 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 238506.86 | 68038.93 | 0.00 | 428199.44 | 92421.41 |
August | 2051130.69 | 03-AUG-15:50 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 235348.48 | 68250.44 | 0.00 | 453790.90 | 92421.41 |
September | 1522680.10 | 05-SEP-15:20 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 214086.03 | 67530.04 | 0.00 | 302197.33 | 92421.41 |
October | 1619975.52 | 02-OCT-15:00 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 182132.67 | 67126.53 | 0.00 | 313558.23 | 92421.41 |
November | 1521432.58 | 27-NOV-16:00 | 339848.75 | 675712.68 | 0.00 | 84902.80 | 98495.07 | 43713.22 | 0.00 | 207925.22 | 70834.84 |
December | 1645685.23 | 12-DEC-16:00 | 336240.19 | 794004.08 | 0.00 | 84898.77 | 110235.50 | 43659.09 | 0.00 | 225127.10 | 51520.50 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1134900.15 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 94703.41 | 43528.69 | 0.00 | 99815.13 | 49668.15 | |
Maximum of Months | 2051130.69 | 339848.75 | 794004.08 | 0.00 | 84902.80 | 276227.21 | 69808.60 | 0.00 | 453790.90 | 92421.41 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1530223.80 | 09-JAN-07:10 | 0.00 | 79691.14 | 26-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 1589015.49 | 13-FEB-07:10 | 0.00 | 79681.57 | 03-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 646849.14 | 18-MAR-06:10 | 0.00 | 79100.29 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 717004.95 | 06-APR-06:10 | 0.00 | 76977.49 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 240536.32 | 11-MAY-06:10 | 0.00 | 73997.68 | 02-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 100251.03 | 03-JUN-11:00 | 0.00 | 70363.16 | 01-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 66680.97 | 07-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 36074.67 | 25-AUG-13:50 | 0.00 | 65927.67 | 15-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 158357.94 | 14-SEP-14:00 | 0.00 | 69715.16 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 682233.93 | 26-OCT-06:10 | 0.00 | 73489.30 | 30-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 1099396.46 | 22-NOV-07:10 | 0.00 | 76493.81 | 27-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 1282117.36 | 18-DEC-07:10 | 0.00 | 78817.47 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 65927.67 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1589015.49 | 0.00 | 79691.14 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.12 | 2.00 | 27.21 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.38 | 0.00 | 26.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.72 | 0.00 | 25.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.67 | 0.00 | 25.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.89 | 0.00 | 25.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.09 | 0.00 | 26.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.05 | 0.00 | 26.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 26.23 | 0.00 | 26.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.32 | 0.50 | 26.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.54 | 0.33 | 26.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.69 | 0.17 | 26.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.64 | 1.00 | 26.73 |
Annual Sum or Average | 0.00 | 0.00 | 68.33 | 26.43 | 4.00 | 26.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.67 | 0.00 | 25.67 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.12 | 2.00 | 27.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.62 | 0.00 | 25.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.61 | 0.00 | 25.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.59 | 0.00 | 25.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.62 | 0.00 | 25.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 25.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 25.60 | 0.00 | 25.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.62 | 0.00 | 25.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.60 | 0.17 | 24.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.60 | 0.17 | 24.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.60 | 0.17 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 18.86 | 0.17 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
February | 1.17 | 18.93 | 0.17 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 19.12 | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Annual Sum or Average | 4.50 | 18.95 | 0.50 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.12 | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.73 | 0.33 | 26.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.69 | 0.00 | 25.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 26.21 | 0.33 | 26.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.73 | 0.33 | 26.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.49 | 1.33 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.74 | 2.50 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.72 | 3.00 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.64 | 2.17 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.50 | 1.17 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.50 | 27.64 | 10.50 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.74 | 3.00 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
February | 0.17 | 19.39 | 0.00 | 19.39 | 1.83 | 26.82 | 1.83 | 27.14 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.38 | 0.33 | 27.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.37 | 0.50 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.29 | 4.00 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.68 | 1.00 | 27.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.72 | 4.50 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.67 | 3.00 | 27.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.39 | 0.83 | 27.39 |
Annual Sum or Average | 0.33 | 19.30 | 0.00 | 19.30 | 16.67 | 27.37 | 16.17 | 27.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.39 | 0.00 | 19.39 | 4.50 | 27.72 | 4.50 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.36 | 0.33 | 27.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.62 | 2.00 | 27.63 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.36 | 4.33 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.68 | 1.33 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.36 | 4.50 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.31 | 6.67 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 27.30 | 6.67 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.53 | 2.33 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.76 | 2.00 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.45 | 1.67 | 27.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 94.17 | 27.37 | 31.83 | 27.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 27.76 | 6.67 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.50 | 18.81 | 1.17 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
February | 7.00 | 17.57 | 2.17 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
December | 2.67 | 18.98 | 0.33 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Annual Sum or Average | 17.50 | 18.35 | 3.67 | 18.44 | 0.33 | 18.58 | 0.33 | 18.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.50 | 19.20 | 2.17 | 19.20 | 0.33 | 27.27 | 0.33 | 27.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
February | 4.00 | 17.27 | 0.33 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.33 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.54 | 1.17 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.76 | 3.33 | 27.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.71 | 5.50 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.67 | 4.33 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.43 | 0.83 | 27.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
December | 1.83 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
Annual Sum or Average | 11.17 | 18.16 | 0.33 | 18.06 | 15.50 | 23.58 | 15.50 | 25.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.00 | 19.24 | 0.33 | 19.24 | 5.50 | 27.76 | 5.50 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 18.88 | 0.17 | 18.93 | 0.17 | 19.12 | 0.17 | 19.30 |
February | 2.83 | 17.70 | 0.33 | 17.40 | 1.00 | 19.86 | 1.00 | 21.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.33 | 0.50 | 27.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.43 | 3.33 | 27.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.56 | 1.33 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.69 | 4.33 | 27.69 |
November | 0.17 | 19.44 | 0.00 | 19.44 | 2.17 | 27.06 | 2.17 | 27.35 |
December | 1.17 | 19.11 | 0.00 | 19.11 | 0.50 | 21.58 | 0.50 | 22.91 |
Annual Sum or Average | 8.67 | 18.53 | 0.50 | 18.43 | 13.33 | 23.83 | 13.33 | 25.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 19.44 | 0.33 | 19.44 | 4.33 | 27.69 | 4.33 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
February | 3.00 | 17.77 | 0.50 | 17.36 | 0.00 | 17.36 | 0.00 | 17.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.56 | 0.67 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.64 | 1.17 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.88 | 2.17 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.01 | 3.50 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.82 | 2.83 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.49 | 0.67 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
December | 1.50 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Annual Sum or Average | 9.17 | 18.50 | 0.50 | 18.32 | 21.50 | 24.89 | 11.17 | 25.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.33 | 19.28 | 0.50 | 19.28 | 7.33 | 28.01 | 3.50 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.83 | 16.92 | 13.50 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
February | 26.83 | 16.49 | 8.83 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
March | 0.83 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
April | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.44 | 0.33 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.51 | 1.67 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.35 | 0.50 | 27.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
November | 2.67 | 18.70 | 0.33 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
December | 23.33 | 17.15 | 7.00 | 17.32 | 0.00 | 17.32 | 0.00 | 17.32 |
Annual Sum or Average | 96.83 | 16.93 | 29.67 | 17.05 | 4.17 | 17.39 | 2.50 | 17.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.83 | 19.33 | 13.50 | 19.33 | 2.83 | 27.51 | 1.67 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.00 | 16.09 | 4.50 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
February | 14.67 | 16.10 | 1.67 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 |
March | 0.67 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
April | 0.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.49 | 0.83 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.71 | 5.33 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.67 | 10.67 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.74 | 6.50 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.37 | 0.67 | 27.37 |
October | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
November | 2.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
December | 12.67 | 16.86 | 1.17 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
Annual Sum or Average | 55.33 | 16.41 | 7.33 | 16.32 | 26.17 | 19.67 | 24.00 | 21.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.99 | 0.00 | 15.99 |
Maximum of Months | 25.00 | 19.37 | 4.50 | 19.37 | 11.83 | 27.74 | 10.67 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.17 | 16.93 | 4.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
February | 12.50 | 16.60 | 2.50 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
March | 0.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.38 | 1.00 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.54 | 2.17 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.62 | 4.83 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.67 | 1.33 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.65 | 2.83 | 27.65 |
November | 1.17 | 18.34 | 0.00 | 18.34 | 0.50 | 21.05 | 0.50 | 22.50 |
December | 7.33 | 18.26 | 0.83 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
Annual Sum or Average | 41.50 | 17.12 | 7.33 | 17.10 | 14.50 | 19.50 | 12.83 | 20.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.17 | 19.24 | 4.00 | 19.24 | 5.50 | 27.67 | 4.83 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.83 | 16.24 | 3.33 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
February | 10.50 | 16.19 | 2.17 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
March | 0.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.52 | 0.67 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.41 | 1.50 | 27.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.03 | 2.50 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.07 | 4.33 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.04 | 3.67 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.53 | 0.83 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
December | 5.67 | 18.13 | 0.33 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
Annual Sum or Average | 35.50 | 16.61 | 5.83 | 16.39 | 26.17 | 20.87 | 13.50 | 22.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.83 | 19.20 | 3.33 | 19.20 | 9.50 | 28.07 | 4.33 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 27.76 | 40.67 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40.67 | 27.76 | 40.67 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 27.76 | 40.67 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 45.33 | 27.78 | 45.33 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 45.33 | 27.78 | 45.33 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.33 | 27.78 | 45.33 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 27.81 | 40.67 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40.67 | 27.81 | 40.67 | 27.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 27.81 | 40.67 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 56.67 | 28.00 | 53.00 | 28.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 418.33 | 29.00 | 367.00 | 29.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 475.00 | 28.88 | 420.00 | 28.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 418.33 | 29.00 | 367.00 | 29.03 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 213.50 | 23.96 | 80.50 | 24.34 | 0.00 | 24.34 |
February | 147.00 | 24.22 | 90.00 | 24.66 | 12.67 | 24.77 |
March | 56.33 | 24.01 | 179.50 | 24.71 | 1.00 | 24.70 |
April | 55.67 | 24.55 | 261.50 | 24.76 | 34.83 | 24.77 |
May | 146.67 | 24.62 | 435.83 | 24.56 | 139.83 | 24.58 |
June | 222.83 | 24.59 | 455.67 | 24.52 | 222.83 | 24.54 |
July | 282.83 | 25.07 | 497.00 | 24.78 | 282.83 | 24.85 |
August | 243.33 | 25.01 | 514.00 | 24.66 | 243.33 | 24.74 |
September | 158.83 | 25.24 | 475.33 | 24.74 | 158.83 | 24.84 |
October | 41.83 | 25.43 | 314.00 | 25.02 | 41.83 | 25.06 |
November | 39.33 | 25.09 | 217.83 | 25.29 | 23.17 | 25.33 |
December | 76.17 | 24.00 | 165.00 | 25.04 | 1.17 | 25.04 |
Annual Sum or Average | 1684.33 | 24.67 | 3686.17 | 24.72 | 1162.33 | 24.77 |
Minimum of Months | 39.33 | 23.96 | 80.50 | 24.34 | 0.00 | 24.34 |
Maximum of Months | 282.83 | 25.43 | 514.00 | 25.29 | 282.83 | 25.33 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.17 | 23.95 | 55.00 | 24.06 | 12.67 | 24.13 |
February | 168.50 | 24.07 | 80.00 | 24.34 | 9.67 | 24.40 |
March | 41.17 | 23.99 | 196.17 | 24.54 | 0.00 | 24.54 |
April | 6.33 | 24.00 | 296.17 | 24.47 | 0.00 | 24.47 |
May | 1.17 | 24.00 | 448.33 | 24.35 | 0.00 | 24.35 |
June | 0.00 | 0.00 | 457.00 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 497.00 | 24.26 | 0.00 | 24.26 |
August | 0.00 | 0.00 | 514.00 | 24.19 | 0.00 | 24.19 |
September | 3.83 | 26.72 | 477.83 | 24.38 | 3.83 | 24.39 |
October | 13.33 | 25.85 | 312.17 | 24.68 | 11.33 | 24.73 |
November | 35.33 | 24.06 | 209.50 | 24.79 | 1.00 | 24.80 |
December | 86.83 | 23.99 | 142.00 | 24.72 | 0.00 | 24.72 |
Annual Sum or Average | 656.67 | 24.05 | 3685.17 | 24.38 | 38.50 | 24.39 |
Minimum of Months | 0.00 | 0.00 | 55.00 | 24.06 | 0.00 | 24.13 |
Maximum of Months | 300.17 | 26.72 | 514.00 | 24.79 | 12.67 | 24.80 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 474.17 | 22.83 | 36.83 | 22.77 | 32.50 | 22.71 |
February | 365.83 | 23.20 | 39.50 | 23.22 | 22.50 | 23.20 |
March | 176.50 | 23.75 | 128.00 | 24.02 | 0.00 | 24.02 |
April | 61.50 | 23.79 | 225.00 | 24.31 | 1.33 | 24.31 |
May | 14.50 | 23.84 | 432.50 | 24.27 | 0.00 | 24.27 |
June | 5.50 | 23.76 | 444.67 | 24.24 | 0.00 | 24.24 |
July | 0.00 | 0.00 | 496.00 | 24.26 | 0.00 | 24.26 |
August | 0.00 | 0.00 | 514.00 | 24.22 | 0.00 | 24.22 |
September | 8.67 | 25.63 | 457.67 | 24.31 | 7.50 | 24.34 |
October | 84.67 | 23.75 | 220.50 | 24.23 | 14.00 | 24.26 |
November | 237.67 | 23.77 | 86.83 | 23.90 | 3.67 | 23.91 |
December | 408.67 | 23.34 | 39.17 | 23.41 | 0.00 | 23.41 |
Annual Sum or Average | 1837.67 | 23.33 | 3120.67 | 23.91 | 81.50 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 36.83 | 22.77 | 0.00 | 22.71 |
Maximum of Months | 474.17 | 25.63 | 514.00 | 24.31 | 32.50 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.67 | 21.31 | 179.33 | 20.94 | 177.50 | 20.72 |
February | 418.17 | 22.11 | 97.00 | 21.85 | 87.67 | 21.64 |
March | 314.33 | 23.13 | 105.50 | 23.32 | 9.00 | 23.27 |
April | 144.00 | 23.39 | 193.83 | 23.91 | 3.33 | 23.92 |
May | 28.67 | 23.61 | 424.83 | 24.21 | 0.00 | 24.21 |
June | 6.67 | 23.67 | 444.67 | 24.26 | 0.00 | 24.26 |
July | 0.83 | 23.14 | 488.83 | 24.30 | 0.00 | 24.30 |
August | 0.00 | 0.00 | 514.00 | 24.26 | 0.00 | 24.26 |
September | 25.50 | 23.81 | 430.33 | 24.26 | 7.17 | 24.28 |
October | 237.83 | 23.10 | 147.17 | 23.46 | 13.67 | 23.46 |
November | 406.50 | 22.83 | 61.50 | 22.87 | 26.00 | 22.82 |
December | 461.00 | 21.80 | 128.33 | 21.57 | 109.33 | 21.35 |
Annual Sum or Average | 2534.17 | 22.34 | 3215.33 | 23.13 | 433.67 | 22.94 |
Minimum of Months | 0.00 | 0.00 | 61.50 | 20.94 | 0.00 | 20.72 |
Maximum of Months | 490.67 | 23.81 | 514.00 | 24.30 | 177.50 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 476.50 | 21.63 | 139.67 | 21.45 | 134.00 | 21.32 |
February | 403.67 | 22.24 | 77.00 | 22.06 | 66.83 | 21.88 |
March | 313.50 | 23.24 | 95.33 | 23.46 | 0.00 | 23.46 |
April | 127.50 | 23.39 | 214.67 | 23.94 | 0.00 | 23.94 |
May | 35.33 | 24.00 | 411.83 | 24.28 | 6.67 | 24.30 |
June | 10.00 | 24.71 | 453.50 | 24.33 | 4.67 | 24.35 |
July | 12.83 | 26.05 | 497.00 | 24.41 | 12.83 | 24.45 |
August | 3.33 | 26.68 | 514.00 | 24.28 | 3.33 | 24.29 |
September | 39.83 | 24.83 | 425.17 | 24.39 | 24.00 | 24.46 |
October | 222.33 | 23.29 | 175.83 | 23.72 | 9.00 | 23.76 |
November | 358.67 | 23.13 | 73.83 | 23.32 | 0.00 | 23.32 |
December | 435.33 | 22.55 | 42.00 | 22.61 | 10.17 | 22.58 |
Annual Sum or Average | 2438.83 | 22.70 | 3119.83 | 23.46 | 271.50 | 23.38 |
Minimum of Months | 3.33 | 21.63 | 42.00 | 21.45 | 0.00 | 21.32 |
Maximum of Months | 476.50 | 26.68 | 514.00 | 24.41 | 134.00 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.83 | 21.72 | 99.00 | 21.54 | 99.00 | 21.42 |
February | 392.50 | 22.04 | 51.50 | 22.00 | 40.50 | 21.89 |
March | 308.50 | 22.83 | 97.83 | 23.19 | 0.00 | 23.19 |
April | 138.67 | 22.94 | 222.33 | 23.69 | 0.67 | 23.70 |
May | 61.83 | 24.16 | 406.00 | 24.34 | 19.33 | 24.43 |
June | 20.83 | 25.31 | 457.50 | 24.34 | 12.33 | 24.40 |
July | 29.67 | 25.94 | 483.17 | 24.41 | 25.17 | 24.51 |
August | 16.50 | 26.57 | 504.00 | 24.25 | 16.00 | 24.32 |
September | 68.00 | 24.15 | 403.00 | 24.29 | 28.67 | 24.39 |
October | 226.67 | 22.88 | 188.83 | 23.54 | 8.67 | 23.58 |
November | 376.67 | 22.76 | 54.50 | 22.96 | 1.33 | 22.95 |
December | 463.50 | 22.20 | 30.67 | 22.23 | 12.17 | 22.19 |
Annual Sum or Average | 2600.17 | 22.53 | 2998.33 | 23.37 | 263.83 | 23.36 |
Minimum of Months | 16.50 | 21.72 | 30.67 | 21.54 | 0.00 | 21.42 |
Maximum of Months | 496.83 | 26.57 | 504.00 | 24.41 | 99.00 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 411.50 | 21.94 | 92.33 | 21.82 | 76.50 | 21.64 |
February | 327.33 | 22.32 | 59.83 | 22.45 | 26.33 | 22.33 |
March | 212.50 | 23.07 | 155.00 | 23.66 | 0.17 | 23.66 |
April | 109.50 | 23.20 | 257.00 | 23.98 | 0.67 | 23.99 |
May | 43.50 | 23.90 | 404.17 | 24.28 | 8.83 | 24.31 |
June | 12.33 | 24.23 | 443.67 | 24.30 | 3.67 | 24.31 |
July | 20.17 | 26.15 | 494.50 | 24.43 | 20.17 | 24.49 |
August | 22.00 | 26.71 | 514.00 | 24.39 | 22.00 | 24.48 |
September | 63.33 | 24.87 | 438.33 | 24.48 | 35.83 | 24.60 |
October | 155.33 | 23.47 | 271.00 | 24.11 | 25.50 | 24.24 |
November | 232.67 | 23.17 | 133.00 | 23.71 | 10.17 | 23.76 |
December | 339.83 | 22.55 | 61.00 | 22.75 | 11.83 | 22.70 |
Annual Sum or Average | 1950.00 | 22.82 | 3323.83 | 23.72 | 241.67 | 23.72 |
Minimum of Months | 12.33 | 21.94 | 59.83 | 21.82 | 0.17 | 21.64 |
Maximum of Months | 411.50 | 26.71 | 514.00 | 24.48 | 76.50 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 454.17 | 21.94 | 43.00 | 21.91 | 32.67 | 21.84 |
February | 307.00 | 22.48 | 73.83 | 22.81 | 13.00 | 22.74 |
March | 100.17 | 23.45 | 257.50 | 24.30 | 4.33 | 24.34 |
April | 39.17 | 25.74 | 397.00 | 24.71 | 26.67 | 24.84 |
May | 33.17 | 25.10 | 461.67 | 24.46 | 18.33 | 24.54 |
June | 36.83 | 26.87 | 484.33 | 24.61 | 36.83 | 24.76 |
July | 53.67 | 26.81 | 497.00 | 24.75 | 53.67 | 24.93 |
August | 61.17 | 26.68 | 514.00 | 24.69 | 61.17 | 24.88 |
September | 47.33 | 26.16 | 450.83 | 24.62 | 41.33 | 24.77 |
October | 107.33 | 23.68 | 301.83 | 24.40 | 19.00 | 24.50 |
November | 142.83 | 23.30 | 191.00 | 24.16 | 5.00 | 24.20 |
December | 231.00 | 23.19 | 104.33 | 23.69 | 0.00 | 23.69 |
Annual Sum or Average | 1613.83 | 23.29 | 3776.33 | 24.13 | 312.00 | 24.23 |
Minimum of Months | 33.17 | 21.94 | 43.00 | 21.91 | 0.00 | 21.84 |
Maximum of Months | 454.17 | 26.87 | 514.00 | 24.75 | 61.17 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.46 | 357.50 | 20.29 | 357.50 | 20.22 |
February | 450.33 | 21.14 | 167.83 | 20.85 | 167.83 | 20.68 |
March | 434.67 | 22.30 | 93.83 | 22.39 | 33.33 | 22.29 |
April | 257.67 | 22.87 | 140.83 | 23.32 | 10.00 | 23.33 |
May | 84.00 | 23.48 | 369.67 | 24.10 | 11.83 | 24.12 |
June | 35.50 | 25.19 | 434.33 | 24.39 | 25.00 | 24.47 |
July | 60.00 | 25.53 | 490.83 | 24.53 | 56.33 | 24.64 |
August | 53.33 | 25.69 | 514.00 | 24.45 | 53.33 | 24.56 |
September | 87.17 | 24.00 | 381.67 | 24.21 | 36.50 | 24.31 |
October | 371.00 | 22.48 | 116.00 | 22.83 | 19.67 | 22.87 |
November | 463.50 | 21.89 | 73.50 | 21.78 | 62.00 | 21.65 |
December | 485.67 | 20.84 | 231.00 | 20.64 | 224.67 | 20.52 |
Annual Sum or Average | 3284.83 | 21.87 | 3371.00 | 22.57 | 1058.00 | 22.38 |
Minimum of Months | 35.50 | 20.46 | 73.50 | 20.29 | 10.00 | 20.22 |
Maximum of Months | 502.00 | 25.69 | 514.00 | 24.53 | 357.50 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.50 | 282.33 | 20.34 | 282.33 | 20.27 |
February | 368.00 | 21.18 | 133.00 | 20.92 | 131.50 | 20.76 |
March | 343.17 | 22.30 | 56.00 | 22.49 | 8.50 | 22.46 |
April | 179.33 | 22.70 | 144.33 | 23.47 | 8.00 | 23.50 |
May | 94.33 | 23.75 | 301.33 | 24.30 | 25.50 | 24.42 |
June | 44.17 | 25.55 | 378.17 | 24.56 | 32.33 | 24.69 |
July | 78.00 | 25.75 | 405.17 | 24.76 | 65.50 | 24.95 |
August | 61.17 | 26.25 | 427.67 | 24.65 | 61.17 | 24.83 |
September | 105.50 | 23.74 | 298.50 | 24.24 | 37.17 | 24.38 |
October | 276.50 | 22.29 | 113.00 | 22.84 | 17.83 | 22.88 |
November | 396.00 | 21.86 | 40.00 | 21.83 | 28.83 | 21.75 |
December | 421.67 | 20.87 | 163.67 | 20.64 | 163.67 | 20.51 |
Annual Sum or Average | 2794.83 | 21.96 | 2743.17 | 22.71 | 862.33 | 22.59 |
Minimum of Months | 44.17 | 20.50 | 40.00 | 20.34 | 8.00 | 20.27 |
Maximum of Months | 427.00 | 26.25 | 427.67 | 24.76 | 282.33 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 444.17 | 21.33 | 178.00 | 21.04 | 171.83 | 20.84 |
February | 373.00 | 21.76 | 99.00 | 21.71 | 77.33 | 21.52 |
March | 284.17 | 22.63 | 125.83 | 23.17 | 5.83 | 23.15 |
April | 176.33 | 22.92 | 204.83 | 23.70 | 6.50 | 23.73 |
May | 76.33 | 23.41 | 376.00 | 24.12 | 11.33 | 24.15 |
June | 43.83 | 24.70 | 431.67 | 24.34 | 23.17 | 24.42 |
July | 60.50 | 25.52 | 485.83 | 24.53 | 55.83 | 24.64 |
August | 60.00 | 26.08 | 514.00 | 24.56 | 60.00 | 24.70 |
September | 84.33 | 24.54 | 419.17 | 24.43 | 44.00 | 24.56 |
October | 216.33 | 22.98 | 233.33 | 23.74 | 33.67 | 23.87 |
November | 313.33 | 22.64 | 96.17 | 23.04 | 18.67 | 23.02 |
December | 398.83 | 21.71 | 103.00 | 21.63 | 73.00 | 21.41 |
Annual Sum or Average | 2531.17 | 22.45 | 3266.83 | 23.30 | 581.17 | 23.24 |
Minimum of Months | 43.83 | 21.33 | 96.17 | 21.04 | 5.83 | 20.84 |
Maximum of Months | 444.17 | 26.08 | 514.00 | 24.56 | 171.83 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.75 | 275.50 | 20.55 | 275.50 | 20.46 |
February | 432.83 | 21.27 | 127.17 | 21.06 | 122.67 | 20.89 |
March | 357.67 | 22.24 | 101.17 | 22.64 | 8.83 | 22.61 |
April | 192.00 | 22.80 | 218.33 | 23.64 | 8.50 | 23.69 |
May | 84.17 | 23.45 | 381.83 | 24.16 | 16.50 | 24.22 |
June | 46.33 | 25.10 | 448.50 | 24.44 | 28.00 | 24.55 |
July | 64.17 | 25.81 | 481.50 | 24.61 | 57.33 | 24.76 |
August | 52.67 | 26.52 | 514.00 | 24.60 | 52.67 | 24.76 |
September | 98.50 | 23.82 | 378.50 | 24.24 | 37.67 | 24.36 |
October | 315.17 | 22.40 | 143.33 | 22.97 | 16.17 | 23.02 |
November | 434.50 | 21.95 | 51.00 | 21.98 | 29.50 | 21.90 |
December | 484.17 | 21.12 | 148.33 | 20.92 | 145.17 | 20.79 |
Annual Sum or Average | 3064.17 | 21.97 | 3269.17 | 22.83 | 798.50 | 22.71 |
Minimum of Months | 46.33 | 20.75 | 51.00 | 20.55 | 8.50 | 20.46 |
Maximum of Months | 502.00 | 26.52 | 514.00 | 24.61 | 275.50 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 415.67 | 19.91 | 415.67 | 19.87 |
February | 451.50 | 20.72 | 252.17 | 20.48 | 252.17 | 20.36 |
March | 449.50 | 21.63 | 128.50 | 21.64 | 80.17 | 21.47 |
April | 298.50 | 22.34 | 130.33 | 22.71 | 29.00 | 22.65 |
May | 122.83 | 23.07 | 342.33 | 23.91 | 15.83 | 23.94 |
June | 57.00 | 24.69 | 429.67 | 24.37 | 31.50 | 24.46 |
July | 77.00 | 25.32 | 482.17 | 24.54 | 67.50 | 24.66 |
August | 63.50 | 25.67 | 511.17 | 24.47 | 63.50 | 24.59 |
September | 126.83 | 23.42 | 326.83 | 24.03 | 38.33 | 24.13 |
October | 399.83 | 21.84 | 106.67 | 22.17 | 31.83 | 22.17 |
November | 479.00 | 21.15 | 180.83 | 20.92 | 175.00 | 20.77 |
December | 492.50 | 20.28 | 337.67 | 20.07 | 337.67 | 19.99 |
Annual Sum or Average | 3520.00 | 21.43 | 3644.00 | 22.10 | 1538.17 | 21.87 |
Minimum of Months | 57.00 | 20.04 | 106.67 | 19.91 | 15.83 | 19.87 |
Maximum of Months | 502.00 | 25.67 | 511.17 | 24.54 | 415.67 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.13 | 396.00 | 20.00 | 396.00 | 19.96 |
February | 447.17 | 20.94 | 208.00 | 20.64 | 208.00 | 20.49 |
March | 420.33 | 21.95 | 95.67 | 22.05 | 40.83 | 21.94 |
April | 233.67 | 22.44 | 174.33 | 23.16 | 16.33 | 23.14 |
May | 114.33 | 23.51 | 364.17 | 24.16 | 30.00 | 24.27 |
June | 54.50 | 25.52 | 450.50 | 24.51 | 40.00 | 24.66 |
July | 93.33 | 25.62 | 473.67 | 24.68 | 77.17 | 24.87 |
August | 72.00 | 26.19 | 504.67 | 24.60 | 70.67 | 24.78 |
September | 133.67 | 23.35 | 348.50 | 24.07 | 40.83 | 24.20 |
October | 332.83 | 21.91 | 133.83 | 22.43 | 27.50 | 22.42 |
November | 472.17 | 21.33 | 117.83 | 21.15 | 113.00 | 21.02 |
December | 497.00 | 20.37 | 302.00 | 20.14 | 302.00 | 20.04 |
Annual Sum or Average | 3373.00 | 21.61 | 3569.17 | 22.34 | 1362.33 | 22.15 |
Minimum of Months | 54.50 | 20.13 | 95.67 | 20.00 | 16.33 | 19.96 |
Maximum of Months | 502.00 | 26.19 | 504.67 | 24.68 | 396.00 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 480.67 | 20.80 | 268.33 | 20.44 | 268.33 | 20.27 |
February | 393.17 | 21.23 | 172.83 | 21.04 | 155.83 | 20.83 |
March | 333.67 | 22.10 | 135.50 | 22.47 | 35.83 | 22.32 |
April | 229.50 | 22.49 | 187.17 | 23.23 | 17.50 | 23.22 |
May | 119.17 | 23.10 | 344.50 | 23.96 | 18.17 | 24.00 |
June | 63.17 | 24.42 | 421.50 | 24.33 | 29.17 | 24.43 |
July | 80.17 | 25.29 | 481.17 | 24.53 | 68.33 | 24.66 |
August | 66.83 | 26.03 | 512.17 | 24.57 | 66.83 | 24.72 |
September | 109.17 | 23.95 | 390.67 | 24.29 | 46.83 | 24.44 |
October | 261.50 | 22.32 | 206.00 | 23.18 | 33.17 | 23.24 |
November | 368.00 | 21.92 | 112.83 | 22.05 | 62.50 | 21.88 |
December | 443.00 | 21.03 | 204.33 | 20.74 | 182.17 | 20.49 |
Annual Sum or Average | 2948.00 | 21.97 | 3437.00 | 22.76 | 984.67 | 22.59 |
Minimum of Months | 63.17 | 20.80 | 112.83 | 20.44 | 17.50 | 20.27 |
Maximum of Months | 480.67 | 26.03 | 512.17 | 24.57 | 268.33 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.28 | 350.67 | 20.10 | 350.67 | 20.03 |
February | 438.33 | 20.91 | 191.50 | 20.68 | 187.83 | 20.54 |
March | 391.50 | 21.79 | 117.33 | 22.05 | 42.17 | 21.92 |
April | 240.50 | 22.40 | 192.50 | 23.21 | 18.00 | 23.23 |
May | 126.00 | 23.12 | 354.33 | 23.98 | 20.67 | 24.06 |
June | 63.83 | 24.76 | 436.17 | 24.42 | 34.50 | 24.55 |
July | 83.67 | 25.50 | 475.50 | 24.59 | 69.00 | 24.76 |
August | 61.17 | 26.44 | 509.83 | 24.61 | 61.17 | 24.78 |
September | 137.33 | 23.34 | 343.17 | 24.07 | 41.33 | 24.20 |
October | 350.67 | 21.95 | 126.50 | 22.49 | 20.50 | 22.53 |
November | 454.00 | 21.40 | 114.00 | 21.27 | 103.17 | 21.13 |
December | 494.00 | 20.61 | 257.00 | 20.35 | 257.00 | 20.22 |
Annual Sum or Average | 3343.00 | 21.63 | 3468.50 | 22.41 | 1206.00 | 22.23 |
Minimum of Months | 61.17 | 20.28 | 114.00 | 20.10 | 18.00 | 20.03 |
Maximum of Months | 502.00 | 26.44 | 509.83 | 24.61 | 350.67 | 24.78 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 498.50 | 27.00 | 0.00 | 27.00 |
February | 0.83 | 27.00 | 454.00 | 27.00 | 0.83 | 27.00 |
March | 38.50 | 27.00 | 514.00 | 27.00 | 38.50 | 27.00 |
April | 188.50 | 27.00 | 485.00 | 27.00 | 188.50 | 27.00 |
May | 2.50 | 27.00 | 508.00 | 27.00 | 2.50 | 27.00 |
June | 149.17 | 27.00 | 496.00 | 27.00 | 149.17 | 27.00 |
July | 259.33 | 27.00 | 497.00 | 27.00 | 259.33 | 27.00 |
August | 485.17 | 27.12 | 514.00 | 27.11 | 485.17 | 27.11 |
September | 32.00 | 27.00 | 485.00 | 27.00 | 32.00 | 27.00 |
October | 27.50 | 27.00 | 502.00 | 27.00 | 27.50 | 27.00 |
November | 18.17 | 27.00 | 489.00 | 27.00 | 18.17 | 27.00 |
December | 24.67 | 27.00 | 497.00 | 27.00 | 24.67 | 27.00 |
Annual Sum or Average | 1226.33 | 27.05 | 5939.50 | 27.02 | 1226.33 | 27.02 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 485.17 | 27.12 | 514.00 | 27.11 | 485.17 | 27.11 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.50 | 25.78 | 364.50 | 26.95 | 0.00 | 26.95 |
February | 0.00 | 0.00 | 397.17 | 27.00 | 0.00 | 27.00 |
March | 0.33 | 27.00 | 514.00 | 27.00 | 0.33 | 27.00 |
April | 3.83 | 27.00 | 485.00 | 27.00 | 3.83 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 22.50 | 27.00 | 497.00 | 27.00 | 22.50 | 27.00 |
August | 134.33 | 27.44 | 514.00 | 27.18 | 134.33 | 27.23 |
September | 1.33 | 27.00 | 485.00 | 27.00 | 1.33 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 177.83 | 27.22 | 5736.67 | 27.02 | 162.33 | 27.03 |
Minimum of Months | 0.00 | 0.00 | 364.50 | 26.95 | 0.00 | 26.95 |
Maximum of Months | 134.33 | 27.44 | 514.00 | 27.18 | 134.33 | 27.23 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 153.50 | 24.81 | 255.83 | 25.97 | 19.67 | 25.83 |
February | 26.17 | 26.99 | 347.50 | 27.00 | 0.00 | 27.00 |
March | 2.83 | 27.00 | 499.17 | 27.00 | 2.83 | 27.00 |
April | 17.83 | 27.00 | 485.00 | 27.00 | 17.83 | 27.00 |
May | 1.83 | 27.00 | 508.00 | 27.00 | 1.83 | 27.00 |
June | 48.00 | 27.00 | 496.00 | 27.00 | 48.00 | 27.00 |
July | 114.67 | 27.00 | 497.00 | 27.00 | 114.67 | 27.00 |
August | 176.50 | 27.31 | 514.00 | 27.16 | 176.50 | 27.19 |
September | 15.33 | 27.00 | 485.00 | 27.00 | 15.33 | 27.00 |
October | 0.83 | 27.00 | 502.00 | 27.00 | 0.83 | 27.00 |
November | 0.00 | 0.00 | 458.83 | 27.00 | 0.00 | 27.00 |
December | 10.00 | 27.00 | 396.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 567.50 | 26.50 | 5445.17 | 26.95 | 397.50 | 26.95 |
Minimum of Months | 0.00 | 0.00 | 255.83 | 25.97 | 0.00 | 25.83 |
Maximum of Months | 176.50 | 27.31 | 514.00 | 27.16 | 176.50 | 27.19 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 285.50 | 27.00 | 502.00 | 27.00 | 285.50 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.14 | 485.00 | 27.14 | 485.00 | 27.14 |
May | 505.17 | 27.00 | 508.00 | 27.00 | 505.17 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 28.52 | 514.00 | 28.52 | 514.00 | 28.52 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
Annual Sum or Average | 5723.67 | 27.15 | 5943.00 | 27.15 | 5723.67 | 27.15 |
Minimum of Months | 285.50 | 27.00 | 454.00 | 27.00 | 285.50 | 27.00 |
Maximum of Months | 514.00 | 28.52 | 514.00 | 28.52 | 514.00 | 28.52 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00007 | 21.64979 | 0.72791 | 16.36507 |
February | 454.00000 | 27.00011 | 24.16533 | 0.81340 | 19.14950 |
March | 514.00000 | 27.00018 | 29.03942 | 0.93500 | 23.57720 |
April | 485.00000 | 27.00010 | 32.61407 | 1.01220 | 26.69237 |
May | 508.00000 | 27.00087 | 36.67141 | 0.29009 | 6.82504 |
June | 496.00000 | 27.00153 | 37.48103 | 0.36209 | 7.79643 |
July | 497.00000 | 27.00104 | 37.95938 | 0.41487 | 8.63857 |
August | 514.00000 | 27.11037 | 37.91760 | 0.49821 | 10.36098 |
September | 485.00000 | 27.00076 | 38.49002 | 0.31448 | 7.13116 |
October | 502.00000 | 27.00070 | 33.71341 | 0.95081 | 24.15222 |
November | 489.00000 | 27.00017 | 27.48488 | 0.91618 | 22.83932 |
December | 497.00000 | 27.00005 | 24.82671 | 0.89921 | 22.20321 |
Annual Sum or Average | 5943.00000 | 27.01001 | 31.89117 | 0.67646 | 16.27345 |
Minimum of Months | 454.00000 | 27.00005 | 21.64979 | 0.29009 | 6.82504 |
Maximum of Months | 514.00000 | 27.11037 | 38.49002 | 1.01220 | 26.69237 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.94953 | 21.78731 | 0.60206 | 12.98417 |
February | 454.00000 | 27.00010 | 24.15649 | 0.68909 | 15.26956 |
March | 514.00000 | 27.00018 | 29.00430 | 0.82594 | 19.56557 |
April | 485.00000 | 27.00010 | 32.57681 | 0.90711 | 22.47736 |
May | 508.00000 | 27.00058 | 36.78108 | 0.23221 | 6.22056 |
June | 496.00000 | 27.00152 | 37.51431 | 0.28851 | 6.81736 |
July | 497.00000 | 27.00110 | 37.97872 | 0.32033 | 7.20103 |
August | 514.00000 | 27.11552 | 37.92066 | 0.37903 | 8.18947 |
September | 485.00000 | 27.00046 | 38.69303 | 0.24950 | 6.39819 |
October | 502.00000 | 27.00064 | 33.73700 | 0.85960 | 20.69386 |
November | 489.00000 | 27.00016 | 27.45143 | 0.78277 | 18.07432 |
December | 497.00000 | 27.00005 | 24.79688 | 0.71796 | 16.03812 |
Annual Sum or Average | 5943.00000 | 27.00614 | 31.92338 | 0.56988 | 13.29954 |
Minimum of Months | 454.00000 | 26.94953 | 21.78731 | 0.23221 | 6.22056 |
Maximum of Months | 514.00000 | 27.11552 | 38.69303 | 0.90711 | 22.47736 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.29191 | 22.50476 | 0.40753 | 10.83142 |
February | 454.00000 | 26.99945 | 24.18069 | 0.63051 | 13.79193 |
March | 514.00000 | 27.00018 | 29.02348 | 0.78582 | 18.32922 |
April | 485.00000 | 27.00011 | 32.59502 | 0.88549 | 21.75241 |
May | 508.00000 | 27.00067 | 36.80130 | 0.23006 | 6.28662 |
June | 496.00000 | 27.00155 | 37.51634 | 0.30166 | 7.03953 |
July | 497.00000 | 27.00109 | 37.99035 | 0.33606 | 7.47544 |
August | 514.00000 | 27.10715 | 37.94016 | 0.39267 | 8.47071 |
September | 485.00000 | 27.00049 | 38.75782 | 0.24214 | 6.40348 |
October | 502.00000 | 27.00064 | 33.79415 | 0.82333 | 19.49198 |
November | 489.00000 | 27.00016 | 27.47730 | 0.72093 | 16.22605 |
December | 497.00000 | 27.00005 | 24.81244 | 0.64021 | 13.94520 |
Annual Sum or Average | 5943.00000 | 26.94983 | 32.00708 | 0.53189 | 12.48199 |
Minimum of Months | 454.00000 | 26.29191 | 22.50476 | 0.23006 | 6.28662 |
Maximum of Months | 514.00000 | 27.10715 | 38.75782 | 0.88549 | 21.75241 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00093 | 30.99149 | 1.02719 | 27.30666 |
February | 454.00000 | 27.00242 | 31.23583 | 1.19513 | 35.02691 |
March | 514.00000 | 27.00234 | 32.56622 | 1.36358 | 43.58966 |
April | 485.00000 | 27.13562 | 33.84518 | 1.52763 | 52.40133 |
May | 508.00000 | 27.00201 | 36.12551 | 0.50662 | 10.42246 |
June | 496.00000 | 27.00191 | 37.12860 | 0.76220 | 17.27145 |
July | 497.00000 | 27.00108 | 37.67098 | 0.97850 | 25.24709 |
August | 514.00000 | 28.51798 | 36.69802 | 1.60437 | 56.31656 |
September | 485.00000 | 27.00272 | 37.29103 | 0.60523 | 12.72996 |
October | 502.00000 | 27.00091 | 34.05330 | 1.28987 | 39.76327 |
November | 489.00000 | 27.00345 | 32.02293 | 1.40843 | 45.96698 |
December | 497.00000 | 27.00525 | 31.28108 | 1.51085 | 51.49157 |
Annual Sum or Average | 5943.00000 | 27.14426 | 34.26424 | 1.14876 | 34.82921 |
Minimum of Months | 454.00000 | 27.00091 | 30.99149 | 0.50662 | 10.42246 |
Maximum of Months | 514.00000 | 28.51798 | 37.67098 | 1.60437 | 56.31656 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.39225 | 22.40999 | 0.32225 | 7.68947 |
February | 454.00000 | 24.41228 | 25.93810 | 0.35704 | 8.39617 |
March | 514.00000 | 24.38034 | 32.42063 | 0.40736 | 8.92246 |
April | 485.00000 | 24.45370 | 39.81206 | 0.47326 | 10.25812 |
May | 508.00000 | 24.46779 | 52.89798 | -0.2828 | 7.73040 |
June | 496.00000 | 24.45184 | 56.73001 | -0.2435 | 7.17832 |
July | 497.00000 | 24.60936 | 62.27014 | -0.1482 | 6.93476 |
August | 514.00000 | 24.48914 | 60.93934 | -0.1792 | 6.88981 |
September | 485.00000 | 24.56429 | 56.95709 | -0.1894 | 7.34050 |
October | 502.00000 | 24.60405 | 41.90038 | 0.54773 | 12.16900 |
November | 489.00000 | 24.60592 | 29.96105 | 0.46123 | 10.30789 |
December | 497.00000 | 24.54864 | 26.15408 | 0.41000 | 9.28425 |
Annual Sum or Average | 5943.00000 | 24.49832 | 42.50174 | 0.15900 | 8.58700 |
Minimum of Months | 454.00000 | 24.38034 | 22.40999 | -0.2828 | 6.88981 |
Maximum of Months | 514.00000 | 24.60936 | 62.27014 | 0.54773 | 12.16900 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.08971 | 26.54735 | 0.27412 | 7.40712 |
February | 454.00000 | 24.20616 | 27.50235 | 0.32606 | 7.75517 |
March | 514.00000 | 24.29658 | 32.91113 | 0.41525 | 9.00204 |
April | 485.00000 | 24.30726 | 39.89893 | 0.47807 | 10.14532 |
May | 508.00000 | 24.31133 | 50.89618 | -0.3100 | 7.56068 |
June | 496.00000 | 24.24112 | 52.11868 | -0.3025 | 7.23727 |
July | 497.00000 | 24.25777 | 55.65767 | -0.2631 | 6.68569 |
August | 514.00000 | 24.18619 | 55.28996 | -0.2714 | 6.68375 |
September | 485.00000 | 24.35150 | 53.79292 | -0.2674 | 7.11531 |
October | 502.00000 | 24.39746 | 42.30477 | 0.50729 | 10.88465 |
November | 489.00000 | 24.42357 | 31.03426 | 0.42856 | 9.36153 |
December | 497.00000 | 24.41100 | 27.83381 | 0.38959 | 8.78436 |
Annual Sum or Average | 5943.00000 | 24.28993 | 41.42737 | 0.11464 | 8.21708 |
Minimum of Months | 454.00000 | 24.08971 | 26.54735 | -0.3100 | 6.68375 |
Maximum of Months | 514.00000 | 24.42357 | 55.65767 | 0.50729 | 10.88465 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.89840 | 28.82358 | -0.0405 | 6.18454 |
February | 454.00000 | 23.37175 | 29.49772 | 0.09822 | 6.49270 |
March | 514.00000 | 24.04667 | 34.27399 | 0.32715 | 7.65821 |
April | 485.00000 | 24.20315 | 40.80000 | 0.42197 | 9.11394 |
May | 508.00000 | 24.23958 | 51.29896 | -0.3562 | 8.09001 |
June | 496.00000 | 24.21813 | 52.56862 | -0.3388 | 7.79857 |
July | 497.00000 | 24.25520 | 56.31812 | -0.3018 | 7.23597 |
August | 514.00000 | 24.21654 | 56.14453 | -0.3078 | 7.25854 |
September | 485.00000 | 24.26060 | 54.36121 | -0.3243 | 7.67686 |
October | 502.00000 | 24.12264 | 43.58663 | 0.41456 | 8.91946 |
November | 489.00000 | 23.96716 | 32.65346 | 0.28420 | 7.13473 |
December | 497.00000 | 23.46589 | 30.78183 | 0.12771 | 6.04028 |
Annual Sum or Average | 5943.00000 | 23.94258 | 42.69903 | -0.0012 | 7.47192 |
Minimum of Months | 454.00000 | 22.89840 | 28.82358 | -0.3562 | 6.04028 |
Maximum of Months | 514.00000 | 24.26060 | 56.31812 | 0.42197 | 9.11394 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.37002 | 29.37571 | -0.4333 | 12.78828 |
February | 454.00000 | 22.26229 | 32.07409 | -0.1786 | 9.21382 |
March | 514.00000 | 23.51106 | 35.89461 | 0.18791 | 7.16848 |
April | 485.00000 | 23.93656 | 41.58279 | 0.35306 | 8.33294 |
May | 508.00000 | 24.20301 | 51.40264 | -0.3641 | 8.34009 |
June | 496.00000 | 24.24812 | 52.37595 | -0.3141 | 7.54318 |
July | 497.00000 | 24.29125 | 56.11137 | -0.2723 | 6.96687 |
August | 514.00000 | 24.25567 | 55.99929 | -0.2780 | 6.94120 |
September | 485.00000 | 24.19744 | 54.84441 | -0.3446 | 8.10225 |
October | 502.00000 | 23.61562 | 45.48748 | 0.28406 | 7.54835 |
November | 489.00000 | 23.02235 | 35.22122 | 0.04208 | 6.77792 |
December | 497.00000 | 21.96028 | 32.89803 | -0.2515 | 9.34102 |
Annual Sum or Average | 5943.00000 | 23.41479 | 43.69771 | -0.1310 | 8.24720 |
Minimum of Months | 454.00000 | 21.37002 | 29.37571 | -0.4333 | 6.77792 |
Maximum of Months | 514.00000 | 24.29125 | 56.11137 | 0.35306 | 12.78828 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.74551 | 26.18038 | -0.3185 | 9.08479 |
February | 454.00000 | 22.44610 | 28.12269 | -0.1229 | 7.82788 |
March | 514.00000 | 23.56491 | 33.59862 | 0.20595 | 6.93978 |
April | 485.00000 | 23.95925 | 40.16893 | 0.37065 | 8.61264 |
May | 508.00000 | 24.21656 | 50.63667 | -0.3464 | 8.32596 |
June | 496.00000 | 24.29184 | 51.51423 | -0.2575 | 6.99154 |
July | 497.00000 | 24.37103 | 55.15713 | -0.1910 | 6.42855 |
August | 514.00000 | 24.26304 | 54.83803 | -0.2170 | 6.42658 |
September | 485.00000 | 24.25679 | 54.17645 | -0.3090 | 7.91903 |
October | 502.00000 | 23.76443 | 43.57249 | 0.32588 | 8.07995 |
November | 489.00000 | 23.38987 | 32.42203 | 0.14284 | 6.67352 |
December | 497.00000 | 22.72724 | 28.59728 | -0.0508 | 6.49440 |
Annual Sum or Average | 5943.00000 | 23.59097 | 41.68810 | -0.0643 | 7.47807 |
Minimum of Months | 454.00000 | 21.74551 | 26.18038 | -0.3464 | 6.42658 |
Maximum of Months | 514.00000 | 24.37103 | 55.15713 | 0.37065 | 9.08479 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.74284 | 25.89344 | -0.3042 | 8.55858 |
February | 454.00000 | 22.34576 | 28.05144 | -0.1225 | 7.65780 |
March | 514.00000 | 23.34767 | 33.71801 | 0.18734 | 7.07858 |
April | 485.00000 | 23.73575 | 40.50401 | 0.35765 | 8.62664 |
May | 508.00000 | 24.18337 | 50.45276 | -0.2980 | 8.44691 |
June | 496.00000 | 24.25200 | 51.40523 | -0.2212 | 6.98860 |
July | 497.00000 | 24.28089 | 55.19197 | -0.1740 | 6.80603 |
August | 514.00000 | 24.15343 | 55.03749 | -0.2183 | 6.82495 |
September | 485.00000 | 24.11318 | 54.28699 | -0.3007 | 8.47506 |
October | 502.00000 | 23.57550 | 43.65243 | 0.31578 | 8.44915 |
November | 489.00000 | 23.08539 | 32.64890 | 0.09730 | 6.59571 |
December | 497.00000 | 22.31888 | 28.93809 | -0.1249 | 6.65237 |
Annual Sum or Average | 5943.00000 | 23.43598 | 41.75438 | -0.0673 | 7.59326 |
Minimum of Months | 454.00000 | 21.74284 | 25.89344 | -0.3042 | 6.59571 |
Maximum of Months | 514.00000 | 24.28089 | 55.19197 | 0.35765 | 8.62664 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.36734 | 25.35630 | -0.1570 | 8.44501 |
February | 454.00000 | 22.88743 | 27.43394 | 0.00639 | 7.93142 |
March | 514.00000 | 23.77136 | 32.89848 | 0.29083 | 8.18546 |
April | 485.00000 | 23.97733 | 39.89574 | 0.40227 | 9.34672 |
May | 508.00000 | 24.18234 | 50.61710 | -0.3396 | 8.49049 |
June | 496.00000 | 24.25411 | 51.57217 | -0.2658 | 7.20329 |
July | 497.00000 | 24.35046 | 55.15804 | -0.1897 | 6.51252 |
August | 514.00000 | 24.29232 | 54.60046 | -0.1758 | 6.36157 |
September | 485.00000 | 24.31706 | 53.70731 | -0.2375 | 7.63585 |
October | 502.00000 | 23.98909 | 42.56346 | 0.42821 | 10.32741 |
November | 489.00000 | 23.76382 | 31.28753 | 0.27159 | 8.33262 |
December | 497.00000 | 23.08127 | 27.86487 | 0.06389 | 7.10078 |
Annual Sum or Average | 5943.00000 | 23.77555 | 41.18761 | 0.00741 | 7.98667 |
Minimum of Months | 454.00000 | 22.36734 | 25.35630 | -0.3396 | 6.36157 |
Maximum of Months | 514.00000 | 24.35046 | 55.15804 | 0.42821 | 10.32741 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.15269 | 25.02017 | -0.1798 | 7.48011 |
February | 454.00000 | 23.08473 | 26.47037 | 0.08389 | 7.45347 |
March | 514.00000 | 24.19730 | 31.75492 | 0.44381 | 10.19347 |
April | 485.00000 | 24.48116 | 38.46459 | 0.61083 | 13.81010 |
May | 508.00000 | 24.33948 | 49.86477 | -0.1995 | 7.23180 |
June | 496.00000 | 24.42800 | 50.71221 | -0.0859 | 6.38994 |
July | 497.00000 | 24.52712 | 54.12495 | 0.00681 | 6.43226 |
August | 514.00000 | 24.45237 | 53.67462 | 0.03279 | 6.32623 |
September | 485.00000 | 24.36559 | 53.30489 | -0.1682 | 7.23225 |
October | 502.00000 | 24.18869 | 41.83404 | 0.50004 | 11.40334 |
November | 489.00000 | 24.10832 | 30.34113 | 0.38223 | 9.40872 |
December | 497.00000 | 23.85968 | 26.15468 | 0.27700 | 7.75729 |
Annual Sum or Average | 5943.00000 | 24.02127 | 40.25201 | 0.14177 | 8.42273 |
Minimum of Months | 454.00000 | 22.15269 | 25.02017 | -0.1995 | 6.32623 |
Maximum of Months | 514.00000 | 24.52712 | 54.12495 | 0.61083 | 13.81010 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.46003 | 28.31116 | -0.6830 | 17.54031 |
February | 454.00000 | 21.16521 | 30.06462 | -0.4678 | 12.88111 |
March | 514.00000 | 22.55802 | 35.73580 | -0.0466 | 7.17068 |
April | 485.00000 | 23.42958 | 41.93374 | 0.22386 | 7.61011 |
May | 508.00000 | 24.04326 | 51.59386 | -0.4243 | 9.80196 |
June | 496.00000 | 24.27403 | 52.51136 | -0.2864 | 7.51843 |
July | 497.00000 | 24.39240 | 56.87187 | -0.2097 | 6.80640 |
August | 514.00000 | 24.32237 | 56.81581 | -0.2315 | 6.77650 |
September | 485.00000 | 24.07799 | 55.69842 | -0.3884 | 9.31559 |
October | 502.00000 | 22.86480 | 46.53118 | 0.10240 | 6.92258 |
November | 489.00000 | 21.98657 | 35.50561 | -0.2040 | 7.82345 |
December | 497.00000 | 20.91213 | 31.69877 | -0.5128 | 13.03675 |
Annual Sum or Average | 5943.00000 | 22.88700 | 43.71201 | -0.2596 | 9.40644 |
Minimum of Months | 454.00000 | 20.46003 | 28.31116 | -0.6830 | 6.77650 |
Maximum of Months | 514.00000 | 24.39240 | 56.87187 | 0.22386 | 17.54031 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.49960 | 27.18193 | -0.6570 | 16.12478 |
February | 385.00000 | 21.31971 | 29.18766 | -0.4082 | 11.71719 |
March | 433.00000 | 22.66557 | 34.56490 | 0.00607 | 6.95665 |
April | 410.00000 | 23.52200 | 41.15295 | 0.28485 | 8.37057 |
May | 430.00000 | 24.08899 | 50.86739 | -0.3527 | 10.01959 |
June | 418.00000 | 24.36774 | 51.90296 | -0.2058 | 7.43572 |
July | 422.00000 | 24.49746 | 56.19789 | -0.1245 | 7.40252 |
August | 433.00000 | 24.40415 | 56.29468 | -0.1587 | 7.03977 |
September | 410.00000 | 24.00111 | 55.57507 | -0.3586 | 10.14058 |
October | 427.00000 | 22.91722 | 45.57105 | 0.14458 | 7.62114 |
November | 417.00000 | 21.97069 | 34.57631 | -0.1835 | 7.31253 |
December | 422.00000 | 20.87420 | 30.91557 | -0.5014 | 12.13213 |
Annual Sum or Average | 5034.00000 | 22.93709 | 42.91857 | -0.2087 | 9.33853 |
Minimum of Months | 385.00000 | 20.49960 | 27.18193 | -0.6570 | 6.95665 |
Maximum of Months | 433.00000 | 24.49746 | 56.29468 | 0.28485 | 16.12478 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.67810 | 26.62935 | -0.3422 | 11.55490 |
February | 454.00000 | 22.23577 | 28.45223 | -0.1676 | 9.53255 |
March | 514.00000 | 23.36830 | 33.91423 | 0.18204 | 7.87990 |
April | 485.00000 | 23.73452 | 40.94109 | 0.32570 | 8.74516 |
May | 508.00000 | 24.05607 | 51.36760 | -0.3974 | 9.57530 |
June | 496.00000 | 24.23985 | 52.53520 | -0.2919 | 7.73585 |
July | 497.00000 | 24.38290 | 56.76292 | -0.2036 | 6.87194 |
August | 514.00000 | 24.37734 | 56.32739 | -0.1789 | 6.65019 |
September | 485.00000 | 24.23231 | 54.73715 | -0.2782 | 8.41910 |
October | 502.00000 | 23.66135 | 43.92682 | 0.34218 | 9.69402 |
November | 489.00000 | 23.24780 | 32.72240 | 0.13923 | 8.01360 |
December | 497.00000 | 22.20175 | 29.59638 | -0.1584 | 9.03100 |
Annual Sum or Average | 5943.00000 | 23.46034 | 42.43626 | -0.0858 | 8.63394 |
Minimum of Months | 454.00000 | 21.67810 | 26.62935 | -0.3974 | 6.65019 |
Maximum of Months | 514.00000 | 24.38290 | 56.76292 | 0.34218 | 11.55490 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.74961 | 27.37580 | -0.5811 | 14.25359 |
February | 454.00000 | 21.41383 | 29.18390 | -0.3720 | 10.96395 |
March | 514.00000 | 22.82331 | 34.66208 | 0.06262 | 7.40778 |
April | 485.00000 | 23.62567 | 41.05358 | 0.32669 | 8.98513 |
May | 508.00000 | 24.03720 | 51.19407 | -0.3517 | 9.33855 |
June | 496.00000 | 24.28954 | 52.08730 | -0.2123 | 7.36974 |
July | 497.00000 | 24.39797 | 56.29586 | -0.1386 | 6.94538 |
August | 514.00000 | 24.39854 | 55.92522 | -0.1283 | 6.62774 |
September | 485.00000 | 24.03427 | 55.31362 | -0.3308 | 9.43588 |
October | 502.00000 | 23.00812 | 45.48215 | 0.17907 | 7.77045 |
November | 489.00000 | 22.18761 | 34.46114 | -0.1200 | 7.28187 |
December | 497.00000 | 21.17783 | 30.75744 | -0.4165 | 10.68748 |
Annual Sum or Average | 5943.00000 | 23.02453 | 42.92159 | -0.1725 | 8.90222 |
Minimum of Months | 454.00000 | 20.74961 | 27.37580 | -0.5811 | 6.62774 |
Maximum of Months | 514.00000 | 24.39854 | 56.29586 | 0.32669 | 14.25359 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.03915 | 29.43544 | -0.8377 | 23.41923 |
February | 454.00000 | 20.73668 | 31.21982 | -0.6105 | 16.27068 |
March | 514.00000 | 21.91813 | 36.93268 | -0.2092 | 9.09744 |
April | 485.00000 | 22.97698 | 42.92760 | 0.11670 | 7.69682 |
May | 508.00000 | 23.86685 | 52.12075 | -0.4736 | 11.49145 |
June | 496.00000 | 24.23868 | 52.59646 | -0.2820 | 7.83717 |
July | 497.00000 | 24.36924 | 57.02261 | -0.1981 | 7.01084 |
August | 514.00000 | 24.32166 | 56.98183 | -0.2140 | 6.78566 |
September | 485.00000 | 23.87759 | 56.63922 | -0.4473 | 11.14809 |
October | 502.00000 | 22.25517 | 48.33536 | -0.0493 | 7.61241 |
November | 489.00000 | 21.20215 | 37.19946 | -0.4151 | 11.28444 |
December | 497.00000 | 20.30515 | 33.18201 | -0.7053 | 19.07388 |
Annual Sum or Average | 5943.00000 | 22.52325 | 44.65154 | -0.3589 | 11.52205 |
Minimum of Months | 454.00000 | 20.03915 | 29.43544 | -0.8377 | 6.78566 |
Maximum of Months | 514.00000 | 24.36924 | 57.02261 | 0.11670 | 23.41923 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13029 | 28.97512 | -0.7881 | 21.32044 |
February | 454.00000 | 20.98379 | 30.55880 | -0.5203 | 14.40416 |
March | 514.00000 | 22.30963 | 35.95433 | -0.0851 | 7.78675 |
April | 485.00000 | 23.30987 | 41.95558 | 0.24088 | 8.37148 |
May | 508.00000 | 23.99397 | 51.32743 | -0.3588 | 10.30576 |
June | 496.00000 | 24.31060 | 51.95430 | -0.1858 | 7.32742 |
July | 497.00000 | 24.40623 | 56.29586 | -0.1134 | 7.53065 |
August | 514.00000 | 24.35239 | 56.28104 | -0.1366 | 6.91468 |
September | 485.00000 | 23.87624 | 56.05453 | -0.3788 | 10.99421 |
October | 502.00000 | 22.61314 | 46.93956 | 0.06601 | 7.89477 |
November | 489.00000 | 21.40312 | 36.42675 | -0.3388 | 9.49406 |
December | 497.00000 | 20.37243 | 32.77726 | -0.6596 | 17.42045 |
Annual Sum or Average | 5943.00000 | 22.68576 | 43.89238 | -0.2699 | 10.78032 |
Minimum of Months | 454.00000 | 20.13029 | 28.97512 | -0.7881 | 6.91468 |
Maximum of Months | 514.00000 | 24.40623 | 56.29586 | 0.24088 | 21.32044 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.94321 | 28.13144 | -0.5544 | 16.46107 |
February | 454.00000 | 21.66614 | 29.77336 | -0.3331 | 12.38583 |
March | 514.00000 | 22.84378 | 35.03043 | 0.04578 | 8.39916 |
April | 485.00000 | 23.35992 | 41.86304 | 0.23586 | 8.56850 |
May | 508.00000 | 23.89467 | 51.86860 | -0.4412 | 11.12925 |
June | 496.00000 | 24.19421 | 52.64855 | -0.2900 | 8.16609 |
July | 497.00000 | 24.34918 | 56.96429 | -0.1946 | 7.17665 |
August | 514.00000 | 24.37044 | 56.51603 | -0.1617 | 6.71761 |
September | 485.00000 | 24.07788 | 55.54480 | -0.3213 | 9.82195 |
October | 502.00000 | 23.21927 | 45.44875 | 0.22733 | 9.49088 |
November | 489.00000 | 22.51501 | 34.41224 | -0.0559 | 8.71795 |
December | 497.00000 | 21.36578 | 31.41720 | -0.3899 | 13.43987 |
Annual Sum or Average | 5943.00000 | 23.07764 | 43.40706 | -0.1855 | 10.02086 |
Minimum of Months | 454.00000 | 20.94321 | 28.13144 | -0.5544 | 6.71761 |
Maximum of Months | 514.00000 | 24.37044 | 56.96429 | 0.23586 | 16.46107 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.28273 | 28.61370 | -0.7365 | 19.72984 |
February | 454.00000 | 21.02948 | 30.32852 | -0.4951 | 13.78581 |
March | 514.00000 | 22.34465 | 35.71623 | -0.0616 | 8.33260 |
April | 485.00000 | 23.26726 | 41.90589 | 0.24158 | 8.78048 |
May | 508.00000 | 23.86752 | 51.72065 | -0.3964 | 10.85064 |
June | 496.00000 | 24.23327 | 52.24817 | -0.2133 | 7.84427 |
July | 497.00000 | 24.35056 | 56.55134 | -0.1335 | 7.31305 |
August | 514.00000 | 24.37653 | 56.16524 | -0.1161 | 6.78992 |
September | 485.00000 | 23.85153 | 56.17804 | -0.3820 | 11.11768 |
October | 502.00000 | 22.56844 | 46.93238 | 0.06660 | 7.88307 |
November | 489.00000 | 21.58602 | 35.91463 | -0.2854 | 9.25664 |
December | 497.00000 | 20.62373 | 32.19384 | -0.5853 | 15.30996 |
Annual Sum or Average | 5943.00000 | 22.71212 | 43.80765 | -0.2565 | 10.55310 |
Minimum of Months | 454.00000 | 20.28273 | 28.61370 | -0.7365 | 6.78992 |
Maximum of Months | 514.00000 | 24.37653 | 56.55134 | 0.24158 | 19.72984 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.493930E+10 | 78000.59 | 31-JAN-15:50 | 87.32 | 0.233681E+11 | 0.00 | 0.283074E+11 | 0.54 | 6.66 | 31-JAN-15:50 | 0.00 | 0.00 |
February | 0.153096E+11 | 109101.67 | 28-FEB-14:50 | 132.09 | 0.852461E+11 | 0.00 | 0.100556E+12 | 0.97 | 7.27 | 28-FEB-13:40 | 0.00 | 0.00 |
March | 0.430645E+11 | 121393.62 | 30-MAR-14:40 | 260.23 | 0.255336E+12 | 0.00 | 0.298401E+12 | 1.85 | 7.34 | 30-MAR-11:00 | 0.00 | 0.00 |
April | 0.754984E+11 | 134114.60 | 17-APR-14:20 | 384.12 | 0.471968E+12 | 0.00 | 0.547467E+12 | 2.98 | 7.46 | 17-APR-14:20 | 0.00 | 0.00 |
May | 0.127096E+12 | 148888.83 | 31-MAY-03:02 | 470.75 | 0.828373E+12 | 0.00 | 0.955469E+12 | 3.89 | 7.62 | 31-MAY-05:03 | 0.00 | 0.00 |
June | 0.168685E+12 | 180268.40 | 26-JUN-05:02 | 554.15 | 0.111229E+13 | 0.00 | 0.128098E+13 | 4.80 | 7.78 | 21-JUN-05:02 | 0.00 | 0.00 |
July | 0.189447E+12 | 190916.72 | 27-JUL-05:02 | 636.52 | 0.123141E+13 | 0.00 | 0.142086E+13 | 5.21 | 7.69 | 28-JUL-05:03 | 0.00 | 0.00 |
August | 0.206126E+12 | 208101.97 | 24-AUG-05:04 | 686.22 | 0.133779E+13 | 0.00 | 0.154392E+13 | 5.55 | 7.66 | 30-AUG-05:02 | 0.00 | 0.00 |
September | 0.138400E+12 | 170085.19 | 05-SEP-05:03 | 478.33 | 0.909793E+12 | 0.00 | 0.104819E+13 | 4.12 | 7.69 | 11-SEP-04:33 | 0.00 | 0.00 |
October | 0.680332E+11 | 132591.02 | 19-OCT-05:03 | 305.49 | 0.426336E+12 | 0.00 | 0.494370E+12 | 2.34 | 7.56 | 18-OCT-04:03 | 0.00 | 0.00 |
November | 0.312021E+11 | 102700.24 | 02-NOV-13:50 | 202.34 | 0.177396E+12 | 0.00 | 0.208598E+12 | 1.45 | 7.23 | 02-NOV-13:50 | 0.00 | 0.00 |
December | 0.913421E+10 | 96347.58 | 12-DEC-14:30 | 86.99 | 0.518563E+11 | 0.00 | 0.609905E+11 | 0.58 | 7.11 | 12-DEC-14:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.107694E+13 | 4284.56 | 0.691117E+13 | 0.00 | 0.798811E+13 | 2.87 | 0.00 | 0.00 | ||||
Minimum of Months | 0.493930E+10 | 78000.59 | 86.99 | 0.233681E+11 | 0.00 | 0.283074E+11 | 0.54 | 6.66 | 0.00 | 0.00 | ||
Maximum of Months | 0.206126E+12 | 208101.97 | 686.22 | 0.133779E+13 | 0.00 | 0.154392E+13 | 5.55 | 7.78 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.995695E+09 | 121393.62 | 30-MAR-14:40 | 2.50 | 0.710569E+10 | 0.00 | 0.810138E+10 | 0.02 | 7.22 | 30-MAR-14:50 | 0.00 | 0.00 |
April | 0.609060E+10 | 134114.60 | 17-APR-14:20 | 15.25 | 0.436231E+11 | 0.00 | 0.497137E+11 | 0.15 | 7.46 | 17-APR-14:20 | 0.00 | 0.00 |
May | 0.208509E+11 | 148888.83 | 31-MAY-03:02 | 52.26 | 0.146358E+12 | 0.00 | 0.167209E+12 | 0.49 | 7.62 | 31-MAY-05:03 | 0.00 | 0.00 |
June | 0.643046E+11 | 180268.40 | 26-JUN-05:02 | 154.02 | 0.439378E+12 | 0.00 | 0.503682E+12 | 1.46 | 7.78 | 21-JUN-05:02 | 0.00 | 0.00 |
July | 0.736632E+11 | 190916.72 | 27-JUL-05:02 | 172.93 | 0.501553E+12 | 0.00 | 0.575216E+12 | 1.58 | 7.69 | 28-JUL-05:03 | 0.00 | 0.00 |
August | 0.931019E+11 | 208101.97 | 24-AUG-05:04 | 213.41 | 0.630709E+12 | 0.00 | 0.723811E+12 | 1.94 | 7.66 | 30-AUG-05:02 | 0.00 | 0.00 |
September | 0.370927E+11 | 170085.19 | 05-SEP-05:03 | 89.68 | 0.256337E+12 | 0.00 | 0.293429E+12 | 0.86 | 7.69 | 11-SEP-04:33 | 0.00 | 0.00 |
October | 0.116310E+11 | 132591.02 | 19-OCT-05:03 | 28.79 | 0.813052E+11 | 0.00 | 0.929362E+11 | 0.27 | 7.56 | 18-OCT-04:03 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.307731E+12 | 728.84 | 0.210637E+13 | 0.00 | 0.241410E+13 | 0.57 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.931019E+11 | 208101.97 | 213.41 | 0.630709E+12 | 0.00 | 0.723811E+12 | 1.94 | 7.78 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.191628E+11 | 744.00 | 49248.27 | 19-JAN-12:00 | 382529.50 | 26-JAN-13:32 | 21.83 | 18.38 | 14.12 |
February | 0.504229E+11 | 672.00 | 49248.27 | 01-FEB-19:00 | 437074.54 | 03-FEB-15:43 | 25.23 | 18.91 | 14.22 |
March | 0.102560E+12 | 744.00 | 49248.27 | 01-MAR-00:10 | 597204.45 | 31-MAR-24:00 | 29.87 | 20.50 | 14.28 |
April | 0.120217E+12 | 720.00 | 49248.27 | 01-APR-09:40 | 674037.10 | 17-APR-16:10 | 35.99 | 23.62 | 14.30 |
May | 0.122402E+12 | 744.00 | 49248.27 | 01-MAY-00:02 | 340525.86 | 31-MAY-23:40 | 27.07 | 23.05 | 14.30 |
June | 0.126531E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 489911.58 | 30-JUN-24:00 | 35.31 | 28.12 | 14.30 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 653613.91 | 31-JUL-23:53 | 41.01 | 30.75 | 14.30 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 709339.73 | 11-AUG-16:30 | 45.77 | 32.60 | 14.30 |
September | 0.123492E+12 | 720.00 | 49248.27 | 01-SEP-00:02 | 320106.67 | 30-SEP-24:00 | 28.69 | 24.54 | 14.30 |
October | 0.101212E+12 | 744.00 | 49248.27 | 01-OCT-00:10 | 455936.68 | 31-OCT-24:00 | 27.76 | 21.04 | 14.27 |
November | 0.898852E+11 | 720.00 | 49248.27 | 01-NOV-10:35 | 512537.02 | 02-NOV-14:10 | 29.16 | 19.83 | 14.28 |
December | 0.815131E+11 | 744.00 | 49248.27 | 04-DEC-15:30 | 656978.98 | 12-DEC-15:10 | 30.70 | 18.86 | 14.29 |
Annual Sum or Average | 0.120121E+13 | 8760.00 | 31.58 | 23.38 | 14.27 | ||||
Minimum of Months | 0.191628E+11 | 672.00 | 49248.27 | 320106.67 | 21.83 | 18.38 | 14.12 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 709339.73 | 45.77 | 32.60 | 14.30 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 48723034.05 | 22.43 | 1236.50 | 19-JAN-16:00 | 585716.84 | 31-JAN-15:50 | 21.06 | 21.02 | 3.81 |
February | 81353946.58 | 58.24 | 2225.51 | 28-FEB-15:00 | 1056961.35 | 28-FEB-13:20 | 21.21 | 21.07 | 9.51 |
March | 0.146710E+10 | 163.23 | 21586.57 | 28-MAR-15:50 | 1166555.86 | 30-MAR-15:20 | 21.52 | 21.13 | 21.36 |
April | 0.426203E+10 | 287.57 | 21586.57 | 03-APR-04:05 | 1609281.52 | 14-APR-15:50 | 21.93 | 21.15 | 35.32 |
May | 0.178047E+11 | 447.18 | 21586.57 | 01-MAY-13:10 | 1177166.32 | 12-MAY-15:40 | 22.99 | 21.73 | 45.92 |
June | 0.324991E+11 | 537.27 | 21586.57 | 01-JUN-03:02 | 1334590.23 | 08-JUN-15:50 | 24.56 | 22.86 | 55.62 |
July | 0.448789E+11 | 635.58 | 21586.57 | 01-JUL-00:32 | 1190891.35 | 27-JUL-05:04 | 25.55 | 23.72 | 60.98 |
August | 0.513593E+11 | 686.18 | 21586.57 | 01-AUG-00:08 | 1243929.21 | 24-AUG-05:04 | 26.29 | 24.31 | 65.47 |
September | 0.251966E+11 | 462.43 | 21586.57 | 01-SEP-04:08 | 1325377.29 | 13-SEP-15:40 | 24.11 | 22.69 | 48.14 |
October | 0.751021E+10 | 252.65 | 21586.57 | 02-OCT-04:03 | 1148444.57 | 11-OCT-16:10 | 22.18 | 21.53 | 27.96 |
November | 0.605715E+09 | 135.66 | 21586.57 | 27-NOV-16:10 | 863281.99 | 02-NOV-13:50 | 21.42 | 21.14 | 17.23 |
December | 0.192820E+09 | 37.63 | 3456.90 | 13-DEC-11:10 | 801044.11 | 12-DEC-14:30 | 21.08 | 21.00 | 5.11 |
Annual Sum or Average | 0.185906E+12 | 3726.05 | 22.84 | 21.95 | 33.16 | ||||
Minimum of Months | 48723034.05 | 22.43 | 1236.50 | 585716.84 | 21.06 | 21.00 | 3.81 | ||
Maximum of Months | 0.513593E+11 | 686.18 | 21586.57 | 1609281.52 | 26.29 | 24.31 | 65.47 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.06 | 21.06 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.21 | 21.21 | 0.00 |
March | 0.168375E+09 | 2.17 | 21586.57 | 29-MAR-15:50 | 1166555.86 | 30-MAR-15:20 | 21.52 | 21.51 | 0.21 |
April | 0.546405E+09 | 7.86 | 21586.57 | 04-APR-13:30 | 1412166.88 | 13-APR-14:50 | 21.93 | 21.89 | 0.80 |
May | 0.403259E+10 | 51.89 | 21586.57 | 03-MAY-14:20 | 1175503.57 | 15-MAY-15:50 | 22.99 | 22.77 | 5.11 |
June | 0.134554E+11 | 173.14 | 21586.57 | 01-JUN-05:04 | 1175483.04 | 02-JUN-10:40 | 24.56 | 23.85 | 17.32 |
July | 0.175384E+11 | 225.69 | 21586.57 | 01-JUL-05:03 | 1190891.35 | 27-JUL-05:04 | 25.55 | 24.63 | 20.54 |
August | 0.212529E+11 | 273.48 | 21586.57 | 01-AUG-03:02 | 1243929.21 | 24-AUG-05:04 | 26.29 | 25.17 | 24.85 |
September | 0.785298E+10 | 101.05 | 21586.57 | 01-SEP-05:05 | 1325377.29 | 13-SEP-15:40 | 24.11 | 23.69 | 10.09 |
October | 0.230868E+10 | 29.71 | 21586.57 | 02-OCT-09:50 | 1012484.10 | 11-OCT-15:20 | 22.18 | 22.05 | 2.91 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.42 | 21.42 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.08 | 21.08 | 0.00 |
Annual Sum or Average | 0.671557E+11 | 865.00 | 22.84 | 22.54 | 6.87 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 | 21.06 | 0.00 | ||
Maximum of Months | 0.212529E+11 | 273.48 | 21586.57 | 1412166.88 | 26.29 | 25.17 | 24.85 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.189541E+12 | 0.00 | 478.83 | 1538862.95 | 02-JAN-06:02 | 0.00 | 29.09 | 61.07 | 0.38 | 0.00 | 0.03 | 0.63 | 02-JAN-06:02 |
February | 0.112108E+12 | 0.00 | 338.77 | 1377556.71 | 13-FEB-06:01 | 0.00 | 26.85 | 52.40 | 0.25 | 0.00 | 0.02 | 0.57 | 13-FEB-06:01 |
March | 0.161308E+11 | 0.00 | 159.21 | 845252.55 | 22-MAR-05:03 | 0.00 | 27.39 | 38.59 | 0.03 | 0.00 | 0.00 | 0.35 | 22-MAR-05:03 |
April | 0.490352E+10 | 0.00 | 72.91 | 594456.89 | 06-APR-06:10 | 0.00 | 38.65 | 42.95 | 0.01 | 0.00 | 0.00 | 0.24 | 06-APR-06:10 |
May | 0.217959E+10 | 0.00 | 31.63 | 167072.52 | 11-MAY-06:10 | 0.00 | 44.63 | 46.14 | 0.01 | 0.00 | 0.00 | 0.07 | 11-MAY-06:10 |
June | 0.578803E+09 | 0.00 | 11.17 | 64231.07 | 03-JUN-12:00 | 0.00 | 53.71 | 54.18 | 0.00 | 0.00 | 0.00 | 0.03 | 03-JUN-12:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 54.52 | 54.52 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 29286204.54 | 0.00 | 1.75 | 23113.13 | 25-AUG-13:50 | 0.00 | 54.05 | 54.11 | 0.00 | 0.00 | 0.00 | 0.01 | 25-AUG-13:50 |
September | 0.362495E+09 | 0.00 | 15.92 | 101460.30 | 14-SEP-15:00 | 0.00 | 52.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.04 | 14-SEP-15:00 |
October | 0.803075E+10 | 0.00 | 118.66 | 578351.45 | 26-OCT-05:03 | 0.00 | 30.04 | 38.37 | 0.01 | 0.00 | 0.00 | 0.24 | 26-OCT-05:03 |
November | 0.310109E+11 | 0.00 | 221.04 | 1127967.28 | 25-NOV-06:01 | 0.00 | 25.80 | 41.97 | 0.06 | 0.00 | 0.00 | 0.46 | 25-NOV-06:01 |
December | 0.880430E+11 | 0.00 | 393.00 | 1176088.85 | 26-DEC-05:01 | 0.00 | 25.29 | 53.27 | 0.17 | 0.00 | 0.01 | 0.48 | 26-DEC-05:01 |
Annual Sum or Average | 0.452918E+12 | 0.00 | 1842.88 | 0.00 | 38.55 | 49.17 | 0.08 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.29 | 38.37 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.189541E+12 | 0.00 | 478.83 | 1538862.95 | 0.00 | 54.52 | 61.07 | 0.38 | 0.00 | 0.03 | 0.63 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 21.83 | 21.83 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 25.23 | 25.23 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 29.87 | 29.87 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 35.99 | 35.99 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 27.07 | 27.07 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 35.31 | 35.31 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 41.01 | 41.01 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 45.77 | 45.77 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 28.69 | 28.69 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 27.76 | 27.76 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 29.16 | 29.16 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 30.70 | 30.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 | 31.58 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 21.83 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.77 | 45.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.198280E+10 | 0.00 | 60.89 | 0.187542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41599.57 | 31-JAN-15:00 | 41599.57 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.848749E+10 | 0.00 | 111.98 | 0.848331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92211.38 | 28-FEB-15:00 | 92211.38 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.270838E+11 | 0.00 | 246.69 | 0.261654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126352.88 | 30-MAR-05:03 | 125419.18 | 30-MAR-14:30 | 0.00 | 0.00 | 0.00 |
April | 0.593506E+11 | 0.00 | 375.29 | 0.565493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 166868.64 | 17-APR-15:00 | 166868.64 | 17-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.948286E+11 | 0.00 | 453.60 | 0.804717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 212907.75 | 31-MAY-03:02 | 164182.70 | 16-MAY-15:40 | 0.00 | 0.00 | 0.00 |
June | 0.149290E+12 | 0.00 | 535.03 | 0.125402E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 220342.84 | 26-JUN-05:02 | 156456.50 | 26-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.177982E+12 | 0.00 | 602.72 | 0.142759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 215751.27 | 17-JUL-05:03 | 154744.50 | 10-JUL-04:03 | 0.00 | 0.00 | 0.00 |
August | 0.207460E+12 | 0.00 | 653.37 | 0.165899E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 221848.30 | 07-AUG-05:03 | 182638.23 | 25-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.113116E+12 | 0.00 | 455.15 | 0.919298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 227672.48 | 05-SEP-03:02 | 157742.07 | 05-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.517056E+11 | 0.00 | 279.35 | 0.420874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 217641.84 | 19-OCT-05:03 | 146174.62 | 18-OCT-05:03 | 0.00 | 0.00 | 0.00 |
November | 0.183662E+11 | 0.00 | 172.79 | 0.169287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118267.43 | 27-NOV-06:03 | 118267.43 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.569561E+10 | 0.00 | 62.28 | 0.478798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 110224.97 | 13-DEC-06:03 | 75593.27 | 12-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.915349E+12 | 0.00 | 4009.14 | 0.763340E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.198280E+10 | 0.00 | 60.89 | 0.187542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41599.57 | 41599.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.207460E+12 | 0.00 | 653.37 | 0.165899E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 227672.48 | 182638.23 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.144249E+11 | 0.00 | 66.38 | 0.137684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 309146.43 | 31-JAN-15:00 | 309146.43 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.633944E+11 | 0.00 | 102.66 | 0.633944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 727541.52 | 28-FEB-15:00 | 727541.52 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.201860E+12 | 0.00 | 225.49 | 0.195986E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1156652.07 | 30-MAR-15:20 | 1156652.07 | 30-MAR-15:20 | 0.00 | 0.00 | 0.00 |
April | 0.429048E+12 | 0.00 | 306.52 | 0.411037E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1553135.93 | 12-APR-14:40 | 1553135.93 | 12-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.830103E+12 | 0.00 | 433.13 | 0.702445E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1765834.77 | 31-MAY-03:02 | 1567064.58 | 19-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.126985E+13 | 0.00 | 467.70 | 0.103091E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2161595.29 | 24-JUN-05:03 | 1459354.34 | 14-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.144371E+13 | 0.00 | 493.17 | 0.109503E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2242378.74 | 14-JUL-03:02 | 1473104.19 | 15-JUL-05:03 | 0.00 | 0.00 | 0.00 |
August | 0.162546E+13 | 0.00 | 513.92 | 0.120836E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2517226.01 | 23-AUG-03:02 | 1575389.64 | 25-AUG-13:50 | 0.00 | 0.00 | 0.00 |
September | 0.974399E+12 | 0.00 | 423.39 | 0.769309E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2155005.74 | 27-SEP-05:03 | 1435590.22 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.403308E+12 | 0.00 | 263.05 | 0.319247E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1837833.88 | 18-OCT-04:03 | 1078298.03 | 18-OCT-04:03 | 0.00 | 0.00 | 0.00 |
November | 0.125975E+12 | 0.00 | 165.30 | 0.118555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 771822.99 | 04-NOV-05:02 | 556029.91 | 02-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.349632E+11 | 0.00 | 59.31 | 0.297104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 836741.85 | 13-DEC-06:03 | 502054.09 | 12-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.741648E+13 | 0.00 | 3520.02 | 0.595776E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.144249E+11 | 0.00 | 59.31 | 0.137684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 309146.43 | 309146.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.162546E+13 | 0.00 | 513.92 | 0.120836E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2517226.01 | 1575389.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.133325E+10 | 0.00 | 72.41 | 0.126813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24819.03 | 31-JAN-15:00 | 24819.03 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.549883E+10 | 0.00 | 106.10 | 0.549883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69599.68 | 28-FEB-15:00 | 69599.68 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.194692E+11 | 0.00 | 220.04 | 0.190508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127836.40 | 30-MAR-15:30 | 127836.40 | 30-MAR-15:30 | 0.00 | 0.00 | 0.00 |
April | 0.440849E+11 | 0.00 | 299.29 | 0.423593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167531.78 | 17-APR-15:00 | 167531.78 | 17-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.897048E+11 | 0.00 | 427.89 | 0.768287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169693.82 | 16-MAY-15:40 | 169693.82 | 16-MAY-15:40 | 0.00 | 0.00 | 0.00 |
June | 0.140246E+12 | 0.00 | 469.67 | 0.115584E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 222371.00 | 29-JUN-05:03 | 149489.60 | 14-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.159566E+12 | 0.00 | 501.61 | 0.123878E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 239690.96 | 14-JUL-03:02 | 157723.39 | 15-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.178030E+12 | 0.00 | 523.67 | 0.135335E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 269757.61 | 23-AUG-03:02 | 178789.56 | 25-AUG-13:40 | 0.00 | 0.00 | 0.00 |
September | 0.100559E+12 | 0.00 | 418.48 | 0.803705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 224550.45 | 27-SEP-05:03 | 148261.22 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.394586E+11 | 0.00 | 252.92 | 0.310869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 209629.00 | 19-OCT-04:03 | 109815.32 | 18-OCT-05:03 | 0.00 | 0.00 | 0.00 |
November | 0.107436E+11 | 0.00 | 168.74 | 0.101097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69268.52 | 04-NOV-05:02 | 54267.11 | 02-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.298258E+10 | 0.00 | 68.86 | 0.252223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44724.07 | 12-DEC-14:40 | 44724.07 | 12-DEC-14:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.791677E+12 | 0.00 | 3529.68 | 0.643892E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.133325E+10 | 0.00 | 68.86 | 0.126813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24819.03 | 24819.03 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.178030E+12 | 0.00 | 523.67 | 0.135335E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 269757.61 | 178789.56 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.654960E+09 | 0.00 | 19.08 | 0.638719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51712.16 | 19-JAN-05:02 | 31134.54 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.429000E+10 | 0.00 | 48.50 | 0.427141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60831.06 | 28-FEB-14:20 | 60831.06 | 28-FEB-14:20 | 0.00 | 0.00 | 0.00 |
March | 0.133790E+11 | 0.00 | 145.46 | 0.133359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84394.81 | 29-MAR-04:03 | 78391.21 | 30-MAR-14:30 | 0.00 | 0.00 | 0.00 |
April | 0.281709E+11 | 0.00 | 224.61 | 0.277378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91436.89 | 17-APR-14:20 | 91436.89 | 17-APR-14:20 | 0.00 | 0.00 | 0.00 |
May | 0.509565E+11 | 0.00 | 344.08 | 0.466949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134085.00 | 31-MAY-03:02 | 93423.50 | 29-MAY-15:42 | 0.00 | 0.00 | 0.00 |
June | 0.871638E+11 | 0.00 | 398.78 | 0.736925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160487.35 | 26-JUN-03:02 | 109811.09 | 12-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.997131E+11 | 0.00 | 411.40 | 0.793583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160904.56 | 09-JUL-19:58 | 94047.93 | 06-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.119852E+12 | 0.00 | 467.80 | 0.938395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170939.38 | 06-AUG-17:00 | 99308.08 | 14-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.740994E+11 | 0.00 | 378.53 | 0.627840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170246.34 | 17-SEP-15:30 | 95108.68 | 04-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.326725E+11 | 0.00 | 220.63 | 0.276098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147025.23 | 19-OCT-03:02 | 93299.44 | 09-OCT-14:42 | 0.00 | 0.00 | 0.00 |
November | 0.105825E+11 | 0.00 | 119.07 | 0.989265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82619.10 | 27-NOV-06:03 | 82530.39 | 20-NOV-00:52 | 0.00 | 0.00 | 0.00 |
December | 0.304282E+10 | 0.00 | 37.27 | 0.281530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78224.66 | 13-DEC-06:03 | 50315.27 | 12-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.524577E+12 | 0.00 | 2815.19 | 0.442671E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.654960E+09 | 0.00 | 19.08 | 0.638719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51712.16 | 31134.54 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.119852E+12 | 0.00 | 467.80 | 0.938395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170939.38 | 109811.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.322966E+12 | 0.816798E+11 | 744.00 | 0.322464E+12 | 0.502097E+09 | 0.00 | 0.35 | 24-JAN-16:00 | 0.30 | 09-JAN-07:10 | 130083.10 | 19-JAN-17:00 | 125397.23 | 31-JAN-15:00 | 6021.32 | 19-JAN-17:10 | 37668.51 | 24-JAN-16:00 | 0.00 |
February | 0.513952E+12 | 0.125231E+12 | 672.00 | 0.513402E+12 | 0.549722E+09 | 0.00 | 0.59 | 28-FEB-14:10 | 0.51 | 01-FEB-07:10 | 220175.47 | 17-FEB-17:00 | 218635.45 | 28-FEB-15:00 | 5771.76 | 17-FEB-17:10 | 71004.96 | 28-FEB-14:20 | 0.00 |
March | 0.819449E+12 | 0.200918E+12 | 744.00 | 0.817911E+12 | 0.153868E+10 | 0.00 | 0.92 | 31-MAR-24:00 | 0.72 | 06-MAR-07:20 | 394376.47 | 31-MAR-24:00 | 394376.47 | 31-MAR-24:00 | 8561.71 | 31-MAR-11:50 | 106824.49 | 30-MAR-16:00 | 0.00 |
April | 0.103082E+13 | 0.267539E+12 | 720.00 | 0.102886E+13 | 0.196602E+10 | 0.00 | 1.00 | 02-APR-13:05 | 0.36 | 30-APR-24:00 | 406828.74 | 21-APR-15:00 | 403055.58 | 16-APR-18:45 | 7159.23 | 04-APR-10:00 | 137038.88 | 17-APR-16:00 | 0.00 |
May | 0.340757E+12 | 0.981646E+11 | 744.00 | 0.334600E+12 | 0.615763E+10 | 0.00 | 0.55 | 31-MAY-23:20 | 0.31 | 12-MAY-07:00 | 213073.78 | 31-MAY-23:10 | 211664.28 | 31-MAY-24:00 | 8679.58 | 23-MAY-14:00 | 60373.34 | 31-MAY-23:20 | 0.00 |
June | 0.572826E+12 | 0.181490E+12 | 720.00 | 0.563876E+12 | 0.894952E+10 | 0.00 | 0.77 | 30-JUN-24:00 | 0.53 | 10-JUN-06:30 | 303977.93 | 30-JUN-23:03 | 303727.15 | 30-JUN-24:00 | 13129.37 | 26-JUN-17:00 | 92499.63 | 06-JUN-15:00 | 0.00 |
July | 0.840267E+12 | 0.273456E+12 | 744.00 | 0.829354E+12 | 0.109132E+11 | 0.00 | 0.99 | 31-JUL-23:43 | 0.75 | 29-JUL-04:00 | 396710.96 | 31-JUL-23:53 | 395957.48 | 31-JUL-23:53 | 13964.44 | 25-JUL-16:50 | 134920.06 | 08-JUL-15:40 | 0.00 |
August | 0.108066E+13 | 0.349535E+12 | 744.00 | 0.106955E+13 | 0.111073E+11 | 0.00 | 1.00 | 01-AUG-07:10 | 0.38 | 31-AUG-24:00 | 422669.57 | 08-AUG-17:00 | 407577.21 | 07-AUG-21:03 | 19211.25 | 11-AUG-17:00 | 153696.90 | 01-AUG-16:10 | 0.00 |
September | 0.337763E+12 | 0.101184E+12 | 720.00 | 0.329527E+12 | 0.823614E+10 | 0.00 | 0.53 | 30-SEP-24:00 | 0.32 | 29-SEP-06:10 | 212264.84 | 30-SEP-23:20 | 212029.51 | 30-SEP-24:00 | 10501.09 | 28-SEP-13:20 | 53670.95 | 07-SEP-16:00 | 0.00 |
October | 0.584208E+12 | 0.151093E+12 | 744.00 | 0.580533E+12 | 0.367482E+10 | 0.00 | 0.74 | 31-OCT-24:00 | 0.53 | 31-OCT-07:00 | 304610.49 | 31-OCT-24:00 | 304610.49 | 31-OCT-24:00 | 11882.95 | 18-OCT-16:10 | 82720.49 | 10-OCT-16:00 | 0.00 |
November | 0.798227E+12 | 0.191548E+12 | 720.00 | 0.796774E+12 | 0.145284E+10 | 0.00 | 0.81 | 19-NOV-15:00 | 0.72 | 13-NOV-07:20 | 317828.33 | 27-NOV-17:00 | 311352.73 | 02-NOV-14:00 | 6768.71 | 27-NOV-17:10 | 98090.86 | 19-NOV-15:00 | 0.00 |
December | 0.106526E+13 | 0.239279E+12 | 744.00 | 0.106452E+13 | 0.744764E+09 | 0.00 | 1.00 | 12-DEC-14:40 | 0.90 | 01-DEC-07:10 | 408607.11 | 13-DEC-14:00 | 402753.98 | 12-DEC-15:00 | 7806.47 | 13-DEC-14:00 | 120257.93 | 12-DEC-14:40 | 0.00 |
Annual Sum or Average | 0.830716E+13 | 0.226112E+13 | 8760.00 | 0.825137E+13 | 0.557927E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.322966E+12 | 0.816798E+11 | 672.00 | 0.322464E+12 | 0.502097E+09 | 0.00 | 0.35 | 0.30 | 130083.10 | 125397.23 | 5771.76 | 37668.51 | 0.00 | ||||||
Maximum of Months | 0.108066E+13 | 0.349535E+12 | 744.00 | 0.106955E+13 | 0.111073E+11 | 0.00 | 1.00 | 0.90 | 422669.57 | 407577.21 | 19211.25 | 153696.90 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.388000E+10 | 0.103832E+10 | 744.00 | 0.386082E+10 | 19172887.66 | 0.00 | 0.29 | 15-JAN-17:35 | 0.06 | 09-JAN-07:10 | 2286.82 | 20-JAN-17:00 | 2184.50 | 20-JAN-17:00 | 224.95 | 19-JAN-17:00 | 623.04 | 31-JAN-15:00 | 0.00 |
February | 0.872691E+10 | 0.218294E+10 | 672.00 | 0.870482E+10 | 22097426.29 | 0.00 | 0.58 | 26-FEB-17:33 | 0.33 | 13-FEB-07:10 | 4453.16 | 20-FEB-17:57 | 4421.18 | 20-FEB-17:57 | 230.32 | 17-FEB-17:00 | 1394.61 | 26-FEB-17:12 | 0.00 |
March | 0.156533E+11 | 0.384236E+10 | 744.00 | 0.155876E+11 | 65707574.37 | 0.00 | 0.84 | 31-MAR-24:00 | 0.59 | 22-MAR-06:30 | 7720.69 | 31-MAR-24:00 | 7720.69 | 31-MAR-24:00 | 305.38 | 31-MAR-11:40 | 2127.89 | 30-MAR-16:00 | 0.00 |
April | 0.202801E+11 | 0.521182E+10 | 720.00 | 0.201905E+11 | 89602271.97 | 0.00 | 0.98 | 08-APR-18:12 | 0.30 | 30-APR-24:00 | 8432.87 | 09-APR-18:13 | 8432.87 | 09-APR-18:13 | 332.43 | 04-APR-10:00 | 2833.99 | 17-APR-16:00 | 0.00 |
May | 0.614787E+10 | 0.174437E+10 | 744.00 | 0.591563E+10 | 0.232242E+09 | 0.00 | 0.49 | 31-MAY-24:00 | 0.20 | 11-MAY-06:10 | 4101.81 | 31-MAY-24:00 | 4047.65 | 31-MAY-24:00 | 339.64 | 31-MAY-11:00 | 1135.83 | 31-MAY-23:20 | 0.00 |
June | 0.111893E+11 | 0.347399E+10 | 720.00 | 0.108197E+11 | 0.369590E+09 | 0.00 | 0.69 | 30-JUN-24:00 | 0.43 | 10-JUN-06:50 | 5924.57 | 30-JUN-23:03 | 5903.83 | 30-JUN-24:00 | 481.36 | 26-JUN-16:50 | 1869.53 | 06-JUN-15:10 | 0.00 |
July | 0.167372E+11 | 0.533069E+10 | 744.00 | 0.162639E+11 | 0.473312E+09 | 0.00 | 0.91 | 31-JUL-23:53 | 0.66 | 29-JUL-06:10 | 7802.82 | 31-JUL-23:53 | 7783.51 | 31-JUL-23:53 | 548.65 | 26-JUL-09:00 | 2743.91 | 07-JUL-16:00 | 0.00 |
August | 0.219282E+11 | 0.704147E+10 | 744.00 | 0.213794E+11 | 0.548867E+09 | 0.00 | 1.00 | 01-AUG-10:10 | 0.31 | 31-AUG-23:50 | 8910.23 | 04-AUG-15:00 | 8424.63 | 13-AUG-19:34 | 643.76 | 11-AUG-16:50 | 3243.57 | 01-AUG-16:10 | 0.00 |
September | 0.612801E+10 | 0.180415E+10 | 720.00 | 0.581391E+10 | 0.314102E+09 | 0.00 | 0.45 | 30-SEP-24:00 | 0.21 | 29-SEP-06:10 | 3809.52 | 30-SEP-24:00 | 3795.04 | 30-SEP-24:00 | 419.16 | 05-SEP-11:00 | 1099.21 | 07-SEP-16:00 | 0.00 |
October | 0.108360E+11 | 0.276590E+10 | 744.00 | 0.106852E+11 | 0.150796E+09 | 0.00 | 0.66 | 31-OCT-24:00 | 0.39 | 26-OCT-07:00 | 5714.11 | 31-OCT-24:00 | 5714.11 | 31-OCT-24:00 | 505.42 | 18-OCT-16:00 | 1661.56 | 10-OCT-16:00 | 0.00 |
November | 0.150491E+11 | 0.363472E+10 | 720.00 | 0.149919E+11 | 57154858.80 | 0.00 | 0.78 | 19-NOV-16:50 | 0.59 | 30-NOV-22:00 | 6351.58 | 11-NOV-17:00 | 6351.58 | 11-NOV-17:00 | 281.70 | 27-NOV-17:10 | 1978.00 | 19-NOV-15:00 | 0.00 |
December | 0.202053E+11 | 0.461241E+10 | 744.00 | 0.201732E+11 | 32074955.37 | 0.00 | 0.97 | 10-DEC-16:35 | 0.75 | 01-DEC-07:10 | 8238.83 | 11-DEC-16:50 | 8089.39 | 17-DEC-17:10 | 330.84 | 13-DEC-16:00 | 2360.68 | 12-DEC-14:50 | 0.00 |
Annual Sum or Average | 0.156761E+12 | 0.426831E+11 | 8760.00 | 0.154387E+12 | 0.237472E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.388000E+10 | 0.103832E+10 | 672.00 | 0.386082E+10 | 19172887.66 | 0.00 | 0.29 | 0.06 | 2286.82 | 2184.50 | 224.95 | 623.04 | 0.00 | ||||||
Maximum of Months | 0.219282E+11 | 0.704147E+10 | 744.00 | 0.213794E+11 | 0.548867E+09 | 0.00 | 1.00 | 0.75 | 8910.23 | 8432.87 | 643.76 | 3243.57 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.163281E+11 | 0.463079E+10 | 654.11 | 0.161539E+11 | 0.174256E+09 | 0.00 | 0.25 | 20-JAN-17:00 | 0.00 | 01-JAN-00:05 | 19530.52 | 20-JAN-17:00 | 18500.76 | 20-JAN-17:00 | 2118.61 | 19-JAN-17:00 | 5080.24 | 31-JAN-15:00 | 0.00 |
February | 0.677968E+11 | 0.172764E+11 | 672.00 | 0.675829E+11 | 0.213917E+09 | 0.00 | 0.54 | 27-FEB-17:00 | 0.16 | 13-FEB-07:10 | 40685.97 | 28-FEB-17:00 | 40685.97 | 28-FEB-17:00 | 2243.60 | 17-FEB-17:00 | 12715.09 | 28-FEB-15:00 | 0.00 |
March | 0.141442E+12 | 0.349919E+11 | 744.00 | 0.140785E+12 | 0.656478E+09 | 0.00 | 0.83 | 31-MAR-24:00 | 0.53 | 22-MAR-06:30 | 72458.81 | 31-MAR-24:00 | 72458.81 | 31-MAR-24:00 | 3024.72 | 31-MAR-11:40 | 20254.32 | 30-MAR-16:00 | 0.00 |
April | 0.190165E+12 | 0.490304E+11 | 720.00 | 0.189267E+12 | 0.897917E+09 | 0.00 | 0.98 | 17-APR-16:00 | 0.27 | 30-APR-24:00 | 79426.71 | 04-APR-15:30 | 78436.75 | 17-APR-16:00 | 3327.66 | 04-APR-10:00 | 26907.43 | 17-APR-16:00 | 0.00 |
May | 0.560115E+11 | 0.159838E+11 | 744.00 | 0.537319E+11 | 0.227964E+10 | 0.00 | 0.49 | 31-MAY-24:00 | 0.18 | 11-MAY-06:10 | 38870.98 | 31-MAY-24:00 | 38306.23 | 31-MAY-24:00 | 3377.93 | 31-MAY-11:00 | 10767.99 | 31-MAY-23:30 | 0.00 |
June | 0.106096E+12 | 0.329672E+11 | 720.00 | 0.102419E+12 | 0.367678E+10 | 0.00 | 0.70 | 30-JUN-24:00 | 0.41 | 10-JUN-07:00 | 56867.18 | 30-JUN-24:00 | 56666.29 | 30-JUN-24:00 | 4793.58 | 23-JUN-10:10 | 17842.99 | 06-JUN-15:10 | 0.00 |
July | 0.159566E+12 | 0.508156E+11 | 744.00 | 0.154846E+12 | 0.472044E+10 | 0.00 | 0.92 | 31-JUL-23:53 | 0.64 | 29-JUL-06:10 | 75557.80 | 31-JUL-23:53 | 75369.05 | 31-JUL-23:53 | 5481.10 | 26-JUL-09:00 | 26178.28 | 07-JUL-16:00 | 0.00 |
August | 0.208708E+12 | 0.670100E+11 | 744.00 | 0.203221E+12 | 0.548640E+10 | 0.00 | 1.00 | 01-AUG-09:50 | 0.27 | 31-AUG-24:00 | 84473.89 | 04-AUG-14:50 | 79374.76 | 13-AUG-18:35 | 6392.27 | 11-AUG-16:50 | 30903.59 | 01-AUG-16:10 | 0.00 |
September | 0.553801E+11 | 0.164078E+11 | 720.00 | 0.523021E+11 | 0.307803E+10 | 0.00 | 0.41 | 30-SEP-24:00 | 0.17 | 30-SEP-17:00 | 32864.18 | 30-SEP-24:00 | 32646.88 | 30-SEP-24:00 | 4148.34 | 05-SEP-11:00 | 10459.35 | 07-SEP-16:00 | 0.00 |
October | 0.954332E+11 | 0.246084E+11 | 744.00 | 0.939438E+11 | 0.148948E+10 | 0.00 | 0.61 | 31-OCT-24:00 | 0.33 | 31-OCT-07:00 | 50037.09 | 31-OCT-24:00 | 50037.09 | 31-OCT-24:00 | 5030.77 | 18-OCT-16:00 | 15678.14 | 10-OCT-16:00 | 0.00 |
November | 0.131632E+12 | 0.321450E+11 | 720.00 | 0.131067E+12 | 0.565633E+09 | 0.00 | 0.76 | 08-NOV-17:00 | 0.52 | 25-NOV-07:10 | 59251.80 | 02-NOV-16:00 | 58871.43 | 08-NOV-17:00 | 2791.11 | 27-NOV-17:00 | 17683.00 | 19-NOV-16:53 | 0.00 |
December | 0.173194E+12 | 0.401347E+11 | 744.00 | 0.172872E+12 | 0.321952E+09 | 0.00 | 0.91 | 12-DEC-15:10 | 0.65 | 26-DEC-07:30 | 76764.68 | 11-DEC-17:00 | 74873.81 | 11-DEC-17:00 | 3293.92 | 13-DEC-16:00 | 22121.17 | 12-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.140175E+13 | 0.386002E+12 | 8670.11 | 0.137819E+13 | 0.235609E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.163281E+11 | 0.463079E+10 | 654.11 | 0.161539E+11 | 0.174256E+09 | 0.00 | 0.25 | 0.00 | 19530.52 | 18500.76 | 2118.61 | 5080.24 | 0.00 | ||||||
Maximum of Months | 0.208708E+12 | 0.670100E+11 | 744.00 | 0.203221E+12 | 0.548640E+10 | 0.00 | 1.00 | 0.65 | 84473.89 | 79374.76 | 6392.27 | 30903.59 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.703677E+09 | 0.200533E+09 | 331.40 | 0.687387E+09 | 16290418.65 | 0.00 | 0.25 | 20-JAN-17:00 | 0.00 | 01-JAN-00:05 | 1973.82 | 20-JAN-17:00 | 1868.80 | 20-JAN-17:00 | 216.91 | 19-JAN-17:00 | 485.47 | 31-JAN-17:00 | 0.00 |
February | 0.552683E+10 | 0.142777E+10 | 663.89 | 0.550586E+10 | 20968092.39 | 0.00 | 0.54 | 27-FEB-17:00 | 0.00 | 05-FEB-05:23 | 4095.19 | 28-FEB-17:00 | 4095.19 | 28-FEB-17:00 | 222.89 | 17-FEB-17:00 | 1271.39 | 28-FEB-15:00 | 0.00 |
March | 0.133685E+11 | 0.333794E+10 | 744.00 | 0.133033E+11 | 65201313.23 | 0.00 | 0.80 | 31-MAR-23:20 | 0.45 | 23-MAR-06:10 | 6990.82 | 31-MAR-23:20 | 6990.82 | 31-MAR-23:20 | 302.61 | 31-MAR-11:40 | 2051.25 | 30-MAR-16:00 | 0.00 |
April | 0.186427E+11 | 0.483479E+10 | 720.00 | 0.185532E+11 | 89463170.26 | 0.00 | 0.98 | 17-APR-16:00 | 0.26 | 30-APR-24:00 | 7986.02 | 17-APR-16:00 | 7949.96 | 17-APR-16:00 | 332.84 | 04-APR-10:00 | 2725.79 | 17-APR-16:00 | 0.00 |
May | 0.551972E+10 | 0.158454E+10 | 744.00 | 0.529231E+10 | 0.227404E+09 | 0.00 | 0.48 | 31-MAY-23:50 | 0.12 | 11-MAY-07:00 | 3847.58 | 31-MAY-23:20 | 3789.24 | 31-MAY-24:00 | 342.31 | 31-MAY-11:00 | 1068.85 | 31-MAY-23:20 | 0.00 |
June | 0.106704E+11 | 0.332227E+10 | 720.00 | 0.103026E+11 | 0.367771E+09 | 0.00 | 0.69 | 30-JUN-24:00 | 0.38 | 08-JUN-06:50 | 5667.46 | 30-JUN-24:00 | 5647.25 | 30-JUN-24:00 | 480.95 | 23-JUN-10:10 | 1818.39 | 06-JUN-15:10 | 0.00 |
July | 0.160464E+11 | 0.511794E+10 | 744.00 | 0.155745E+11 | 0.471868E+09 | 0.00 | 0.91 | 31-JUL-23:53 | 0.62 | 29-JUL-07:00 | 7592.84 | 31-JUL-23:53 | 7573.86 | 31-JUL-23:53 | 548.49 | 26-JUL-09:00 | 2667.68 | 07-JUL-16:00 | 0.00 |
August | 0.209686E+11 | 0.674115E+10 | 744.00 | 0.204201E+11 | 0.548496E+09 | 0.00 | 1.00 | 01-AUG-10:10 | 0.26 | 31-AUG-24:00 | 8556.78 | 04-AUG-15:00 | 8109.63 | 13-AUG-19:32 | 637.73 | 11-AUG-16:50 | 3123.81 | 01-AUG-16:10 | 0.00 |
September | 0.541425E+10 | 0.161460E+10 | 720.00 | 0.510815E+10 | 0.306100E+09 | 0.00 | 0.39 | 07-SEP-16:00 | 0.12 | 29-SEP-07:00 | 2972.15 | 07-SEP-16:00 | 2804.90 | 30-SEP-24:00 | 417.20 | 05-SEP-11:00 | 1075.08 | 07-SEP-16:00 | 0.00 |
October | 0.884832E+10 | 0.230827E+10 | 744.00 | 0.870021E+10 | 0.148115E+09 | 0.00 | 0.58 | 10-OCT-16:00 | 0.23 | 30-OCT-06:10 | 4596.63 | 18-OCT-16:00 | 4574.69 | 31-OCT-23:20 | 503.65 | 18-OCT-16:00 | 1588.04 | 10-OCT-16:00 | 0.00 |
November | 0.119724E+11 | 0.296019E+10 | 720.00 | 0.119165E+11 | 55930218.19 | 0.00 | 0.74 | 08-NOV-17:00 | 0.40 | 22-NOV-07:10 | 5955.09 | 02-NOV-16:00 | 5878.44 | 06-NOV-17:00 | 278.54 | 27-NOV-17:00 | 1726.69 | 02-NOV-14:00 | 0.00 |
December | 0.155396E+11 | 0.365460E+10 | 744.00 | 0.155076E+11 | 31966906.42 | 0.00 | 0.90 | 12-DEC-15:20 | 0.48 | 18-DEC-04:13 | 7637.30 | 13-DEC-16:00 | 7422.15 | 12-DEC-15:40 | 328.92 | 13-DEC-16:00 | 2205.41 | 12-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.133221E+12 | 0.371046E+11 | 8339.29 | 0.130872E+12 | 0.234957E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.703677E+09 | 0.200533E+09 | 331.40 | 0.687387E+09 | 16290418.65 | 0.00 | 0.25 | 0.00 | 1973.82 | 1868.80 | 216.91 | 485.47 | 0.00 | ||||||
Maximum of Months | 0.209686E+11 | 0.674115E+10 | 744.00 | 0.204201E+11 | 0.548496E+09 | 0.00 | 1.00 | 0.62 | 8556.78 | 8109.63 | 637.73 | 3123.81 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.22 | 0.00 | 74.22 | 6.60 | 594.35 | 0.00 | 0.00 | 0.00 |
February | 82.27 | 0.00 | 82.27 | 27.05 | 489.95 | 0.00 | 0.00 | 0.00 |
March | 115.50 | 0.00 | 115.50 | 67.31 | 309.58 | 0.00 | 0.00 | 0.00 |
April | 139.70 | 0.62 | 139.08 | 145.20 | 234.52 | 0.00 | 0.00 | 0.00 |
May | 167.08 | 5.33 | 161.75 | 232.04 | 146.16 | 0.00 | 0.00 | 0.00 |
June | 183.88 | 12.14 | 171.74 | 337.13 | 88.28 | 0.00 | 0.00 | 0.00 |
July | 173.49 | 8.43 | 165.06 | 338.00 | 62.11 | 0.00 | 0.00 | 0.00 |
August | 154.29 | 1.68 | 152.61 | 307.92 | 50.76 | 0.00 | 0.00 | 0.00 |
September | 116.63 | 0.02 | 116.62 | 173.13 | 126.75 | 0.00 | 0.00 | 0.00 |
October | 88.68 | 0.00 | 88.68 | 70.44 | 282.05 | 0.00 | 0.00 | 0.00 |
November | 79.36 | 0.00 | 79.36 | 29.10 | 393.90 | 0.00 | 0.00 | 0.00 |
December | 68.61 | 0.00 | 68.61 | 5.40 | 513.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 120.52 | 2.36 | 118.16 | 145.63 | 273.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.61 | 0.00 | 68.61 | 5.40 | 50.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.88 | 12.14 | 171.74 | 338.00 | 594.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.22 | 0.00 | 74.22 | 6.60 | 594.35 | 0.00 | 0.00 | 0.00 |
February | 82.26 | 0.00 | 82.26 | 27.05 | 489.95 | 0.00 | 0.00 | 0.00 |
March | 115.49 | 0.00 | 115.49 | 67.31 | 309.58 | 0.00 | 0.00 | 0.00 |
April | 139.70 | 0.62 | 139.08 | 145.20 | 234.52 | 0.00 | 0.00 | 0.00 |
May | 167.08 | 5.33 | 161.75 | 232.04 | 146.16 | 0.00 | 0.00 | 0.00 |
June | 183.88 | 12.14 | 171.74 | 337.13 | 88.28 | 0.00 | 0.00 | 0.00 |
July | 173.49 | 8.43 | 165.06 | 338.00 | 62.11 | 0.00 | 0.00 | 0.00 |
August | 154.29 | 1.68 | 152.61 | 307.92 | 50.76 | 0.00 | 0.00 | 0.00 |
September | 116.63 | 0.02 | 116.61 | 173.13 | 126.75 | 0.00 | 0.00 | 0.00 |
October | 88.68 | 0.00 | 88.68 | 70.44 | 282.05 | 0.00 | 0.00 | 0.00 |
November | 79.36 | 0.00 | 79.36 | 29.10 | 393.90 | 0.00 | 0.00 | 0.00 |
December | 68.61 | 0.00 | 68.61 | 5.40 | 513.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 120.52 | 2.36 | 118.15 | 145.62 | 273.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.61 | 0.00 | 68.61 | 5.40 | 50.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.88 | 12.14 | 171.74 | 338.00 | 594.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.22 | 0.00 | 74.22 | 6.60 | 594.35 | 0.00 | 0.00 | 0.00 |
February | 82.26 | 0.00 | 82.26 | 27.05 | 489.95 | 0.00 | 0.00 | 0.00 |
March | 115.50 | 0.00 | 115.50 | 67.31 | 309.58 | 0.00 | 0.00 | 0.00 |
April | 139.70 | 0.62 | 139.08 | 145.20 | 234.52 | 0.00 | 0.00 | 0.00 |
May | 167.08 | 5.33 | 161.75 | 232.04 | 146.16 | 0.00 | 0.00 | 0.00 |
June | 183.88 | 12.14 | 171.74 | 337.13 | 88.28 | 0.00 | 0.00 | 0.00 |
July | 173.49 | 8.43 | 165.06 | 338.00 | 62.11 | 0.00 | 0.00 | 0.00 |
August | 154.29 | 1.68 | 152.61 | 307.92 | 50.76 | 0.00 | 0.00 | 0.00 |
September | 116.63 | 0.02 | 116.61 | 173.13 | 126.75 | 0.00 | 0.00 | 0.00 |
October | 88.68 | 0.00 | 88.68 | 70.44 | 282.05 | 0.00 | 0.00 | 0.00 |
November | 79.36 | 0.00 | 79.36 | 29.10 | 393.90 | 0.00 | 0.00 | 0.00 |
December | 68.61 | 0.00 | 68.61 | 5.40 | 513.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 120.52 | 2.36 | 118.15 | 145.62 | 273.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.61 | 0.00 | 68.61 | 5.40 | 50.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.88 | 12.14 | 171.74 | 338.00 | 594.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.22 | 0.00 | 74.22 | 6.60 | 594.35 | 0.00 | 0.00 | 0.00 |
February | 82.26 | 0.00 | 82.26 | 27.05 | 489.95 | 0.00 | 0.00 | 0.00 |
March | 115.49 | 0.00 | 115.49 | 67.31 | 309.58 | 0.00 | 0.00 | 0.00 |
April | 139.70 | 0.62 | 139.08 | 145.20 | 234.52 | 0.00 | 0.00 | 0.00 |
May | 167.08 | 5.33 | 161.75 | 232.04 | 146.16 | 0.00 | 0.00 | 0.00 |
June | 183.88 | 12.14 | 171.74 | 337.13 | 88.28 | 0.00 | 0.00 | 0.00 |
July | 173.49 | 8.43 | 165.06 | 338.00 | 62.11 | 0.00 | 0.00 | 0.00 |
August | 154.29 | 1.68 | 152.61 | 307.92 | 50.76 | 0.00 | 0.00 | 0.00 |
September | 116.63 | 0.02 | 116.61 | 173.13 | 126.75 | 0.00 | 0.00 | 0.00 |
October | 88.68 | 0.00 | 88.68 | 70.44 | 282.05 | 0.00 | 0.00 | 0.00 |
November | 79.36 | 0.00 | 79.36 | 29.10 | 393.90 | 0.00 | 0.00 | 0.00 |
December | 68.61 | 0.00 | 68.61 | 5.40 | 513.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 120.52 | 2.36 | 118.15 | 145.62 | 273.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.61 | 0.00 | 68.61 | 5.40 | 50.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.88 | 12.14 | 171.74 | 338.00 | 594.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.22 | 0.00 | 74.22 | 6.60 | 594.33 | 0.00 | 0.00 | 0.00 |
February | 82.26 | 0.00 | 82.26 | 27.05 | 489.93 | 0.00 | 0.00 | 0.00 |
March | 115.49 | 0.00 | 115.49 | 67.31 | 309.57 | 0.00 | 0.00 | 0.00 |
April | 139.70 | 0.62 | 139.08 | 145.19 | 234.51 | 0.00 | 0.00 | 0.00 |
May | 167.07 | 5.33 | 161.74 | 232.03 | 146.16 | 0.00 | 0.00 | 0.00 |
June | 183.87 | 12.14 | 171.73 | 337.12 | 88.28 | 0.00 | 0.00 | 0.00 |
July | 173.48 | 8.43 | 165.05 | 337.98 | 62.10 | 0.00 | 0.00 | 0.00 |
August | 154.29 | 1.68 | 152.61 | 307.91 | 50.76 | 0.00 | 0.00 | 0.00 |
September | 116.63 | 0.02 | 116.61 | 173.12 | 126.75 | 0.00 | 0.00 | 0.00 |
October | 88.67 | 0.00 | 88.67 | 70.44 | 282.03 | 0.00 | 0.00 | 0.00 |
November | 79.36 | 0.00 | 79.36 | 29.10 | 393.88 | 0.00 | 0.00 | 0.00 |
December | 68.61 | 0.00 | 68.61 | 5.40 | 513.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 120.51 | 2.36 | 118.15 | 145.62 | 273.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.61 | 0.00 | 68.61 | 5.40 | 50.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.87 | 12.14 | 171.73 | 337.98 | 594.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 181.11 | 81.69 | 99.42 | 114.23 | 585.41 | 0.00 | 0.00 | 0.00 |
February | 228.32 | 122.67 | 105.65 | 209.02 | 479.03 | 0.00 | 0.00 | 0.00 |
March | 287.25 | 130.77 | 156.49 | 316.16 | 302.09 | 0.00 | 0.00 | 0.00 |
April | 347.36 | 158.39 | 188.97 | 478.30 | 232.10 | 0.00 | 0.00 | 0.00 |
May | 381.43 | 161.30 | 220.13 | 588.34 | 156.87 | 0.00 | 0.00 | 0.00 |
June | 394.91 | 165.52 | 229.39 | 700.36 | 93.42 | 0.00 | 0.00 | 0.00 |
July | 385.05 | 161.88 | 223.17 | 708.73 | 62.49 | 0.00 | 0.00 | 0.00 |
August | 352.20 | 139.73 | 212.47 | 660.57 | 47.01 | 0.00 | 0.00 | 0.00 |
September | 289.46 | 128.25 | 161.21 | 465.47 | 131.20 | 0.00 | 0.00 | 0.00 |
October | 246.93 | 128.48 | 118.45 | 311.13 | 279.08 | 0.00 | 0.00 | 0.00 |
November | 197.42 | 89.39 | 108.03 | 180.83 | 377.69 | 0.00 | 0.00 | 0.00 |
December | 171.01 | 77.95 | 93.06 | 114.87 | 488.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 288.83 | 128.81 | 160.01 | 405.03 | 268.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 171.01 | 77.95 | 93.06 | 114.23 | 47.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.91 | 165.52 | 229.39 | 708.73 | 585.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 181.11 | 81.69 | 99.42 | 114.23 | 585.41 | 0.00 | 0.00 | 0.00 |
February | 228.32 | 122.67 | 105.65 | 209.02 | 479.03 | 0.00 | 0.00 | 0.00 |
March | 287.25 | 130.77 | 156.49 | 316.16 | 302.09 | 0.00 | 0.00 | 0.00 |
April | 347.36 | 158.39 | 188.97 | 478.30 | 232.10 | 0.00 | 0.00 | 0.00 |
May | 381.43 | 161.30 | 220.13 | 588.34 | 156.87 | 0.00 | 0.00 | 0.00 |
June | 394.91 | 165.52 | 229.39 | 700.36 | 93.42 | 0.00 | 0.00 | 0.00 |
July | 385.05 | 161.88 | 223.17 | 708.73 | 62.49 | 0.00 | 0.00 | 0.00 |
August | 352.20 | 139.73 | 212.47 | 660.57 | 47.01 | 0.00 | 0.00 | 0.00 |
September | 289.46 | 128.25 | 161.21 | 465.47 | 131.20 | 0.00 | 0.00 | 0.00 |
October | 246.93 | 128.48 | 118.45 | 311.13 | 279.08 | 0.00 | 0.00 | 0.00 |
November | 197.42 | 89.39 | 108.03 | 180.83 | 377.69 | 0.00 | 0.00 | 0.00 |
December | 171.01 | 77.95 | 93.06 | 114.87 | 488.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 288.83 | 128.81 | 160.01 | 405.03 | 268.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 171.01 | 77.95 | 93.06 | 114.23 | 47.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.91 | 165.52 | 229.39 | 708.73 | 585.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 181.10 | 81.69 | 99.42 | 114.23 | 585.40 | 0.00 | 0.00 | 0.00 |
February | 228.32 | 122.67 | 105.64 | 209.02 | 479.02 | 0.00 | 0.00 | 0.00 |
March | 287.25 | 130.76 | 156.48 | 316.16 | 302.08 | 0.00 | 0.00 | 0.00 |
April | 347.36 | 158.39 | 188.97 | 478.29 | 232.09 | 0.00 | 0.00 | 0.00 |
May | 381.42 | 161.30 | 220.12 | 588.33 | 156.87 | 0.00 | 0.00 | 0.00 |
June | 394.90 | 165.51 | 229.39 | 700.34 | 93.42 | 0.00 | 0.00 | 0.00 |
July | 385.04 | 161.88 | 223.17 | 708.72 | 62.49 | 0.00 | 0.00 | 0.00 |
August | 352.19 | 139.73 | 212.46 | 660.56 | 47.01 | 0.00 | 0.00 | 0.00 |
September | 289.45 | 128.25 | 161.20 | 465.46 | 131.20 | 0.00 | 0.00 | 0.00 |
October | 246.93 | 128.48 | 118.44 | 311.13 | 279.07 | 0.00 | 0.00 | 0.00 |
November | 197.42 | 89.39 | 108.03 | 180.83 | 377.68 | 0.00 | 0.00 | 0.00 |
December | 171.00 | 77.95 | 93.05 | 114.87 | 488.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 288.82 | 128.81 | 160.01 | 405.02 | 268.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 171.00 | 77.95 | 93.05 | 114.23 | 47.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.90 | 165.51 | 229.39 | 708.72 | 585.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 396.93 | 276.74 | 120.19 | 438.41 | 478.56 | 0.00 | 0.00 | 0.00 |
February | 370.47 | 248.33 | 122.13 | 448.70 | 415.66 | 0.00 | 0.00 | 0.00 |
March | 333.18 | 173.63 | 159.55 | 440.51 | 289.51 | 0.00 | 0.00 | 0.00 |
April | 249.53 | 81.23 | 168.30 | 369.21 | 235.90 | 0.00 | 0.00 | 0.00 |
May | 201.61 | 23.43 | 178.18 | 318.67 | 153.94 | 0.00 | 0.00 | 0.00 |
June | 186.41 | 10.37 | 176.04 | 354.31 | 94.04 | 0.00 | 0.00 | 0.00 |
July | 188.46 | 14.05 | 174.40 | 377.29 | 64.26 | 0.00 | 0.00 | 0.00 |
August | 225.00 | 42.03 | 182.97 | 457.93 | 53.33 | 0.00 | 0.00 | 0.00 |
September | 247.45 | 92.04 | 155.41 | 425.95 | 128.44 | 0.00 | 0.00 | 0.00 |
October | 358.73 | 232.38 | 126.34 | 527.64 | 263.16 | 0.00 | 0.00 | 0.00 |
November | 385.92 | 256.09 | 129.83 | 503.03 | 345.10 | 0.00 | 0.00 | 0.00 |
December | 391.26 | 275.26 | 116.01 | 460.62 | 420.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 294.25 | 143.31 | 150.94 | 426.83 | 244.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.41 | 10.37 | 116.01 | 318.67 | 53.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 396.93 | 276.74 | 182.97 | 527.64 | 478.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 396.93 | 276.74 | 120.19 | 438.41 | 478.56 | 0.00 | 0.00 | 0.00 |
February | 370.47 | 248.33 | 122.13 | 448.70 | 415.66 | 0.00 | 0.00 | 0.00 |
March | 333.18 | 173.63 | 159.55 | 440.50 | 289.51 | 0.00 | 0.00 | 0.00 |
April | 249.53 | 81.23 | 168.30 | 369.21 | 235.90 | 0.00 | 0.00 | 0.00 |
May | 201.61 | 23.43 | 178.18 | 318.67 | 153.94 | 0.00 | 0.00 | 0.00 |
June | 186.41 | 10.37 | 176.04 | 354.31 | 94.04 | 0.00 | 0.00 | 0.00 |
July | 188.46 | 14.05 | 174.40 | 377.29 | 64.26 | 0.00 | 0.00 | 0.00 |
August | 225.00 | 42.03 | 182.97 | 457.92 | 53.33 | 0.00 | 0.00 | 0.00 |
September | 247.45 | 92.04 | 155.41 | 425.94 | 128.44 | 0.00 | 0.00 | 0.00 |
October | 358.72 | 232.38 | 126.34 | 527.63 | 263.16 | 0.00 | 0.00 | 0.00 |
November | 385.92 | 256.09 | 129.83 | 503.03 | 345.10 | 0.00 | 0.00 | 0.00 |
December | 391.26 | 275.25 | 116.01 | 460.61 | 420.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 294.25 | 143.31 | 150.94 | 426.82 | 244.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.41 | 10.37 | 116.01 | 318.67 | 53.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 396.93 | 276.74 | 182.97 | 527.63 | 478.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 396.93 | 276.74 | 120.19 | 438.41 | 478.56 | 0.00 | 0.00 | 0.00 |
February | 370.47 | 248.33 | 122.13 | 448.70 | 415.66 | 0.00 | 0.00 | 0.00 |
March | 333.18 | 173.63 | 159.55 | 440.51 | 289.51 | 0.00 | 0.00 | 0.00 |
April | 249.53 | 81.23 | 168.30 | 369.21 | 235.90 | 0.00 | 0.00 | 0.00 |
May | 201.61 | 23.43 | 178.18 | 318.67 | 153.94 | 0.00 | 0.00 | 0.00 |
June | 186.41 | 10.37 | 176.04 | 354.31 | 94.04 | 0.00 | 0.00 | 0.00 |
July | 188.46 | 14.05 | 174.40 | 377.29 | 64.26 | 0.00 | 0.00 | 0.00 |
August | 225.00 | 42.03 | 182.97 | 457.93 | 53.33 | 0.00 | 0.00 | 0.00 |
September | 247.45 | 92.04 | 155.41 | 425.95 | 128.44 | 0.00 | 0.00 | 0.00 |
October | 358.73 | 232.38 | 126.34 | 527.64 | 263.16 | 0.00 | 0.00 | 0.00 |
November | 385.92 | 256.09 | 129.83 | 503.03 | 345.10 | 0.00 | 0.00 | 0.00 |
December | 391.26 | 275.26 | 116.01 | 460.62 | 420.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 294.25 | 143.31 | 150.94 | 426.83 | 244.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.41 | 10.37 | 116.01 | 318.67 | 53.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 396.93 | 276.74 | 182.97 | 527.64 | 478.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 396.93 | 276.74 | 120.19 | 438.41 | 478.56 | 0.00 | 0.00 | 0.00 |
February | 370.47 | 248.33 | 122.13 | 448.70 | 415.66 | 0.00 | 0.00 | 0.00 |
March | 333.18 | 173.63 | 159.55 | 440.50 | 289.51 | 0.00 | 0.00 | 0.00 |
April | 249.53 | 81.23 | 168.30 | 369.21 | 235.90 | 0.00 | 0.00 | 0.00 |
May | 201.61 | 23.43 | 178.18 | 318.67 | 153.94 | 0.00 | 0.00 | 0.00 |
June | 186.41 | 10.37 | 176.04 | 354.31 | 94.04 | 0.00 | 0.00 | 0.00 |
July | 188.46 | 14.05 | 174.40 | 377.29 | 64.26 | 0.00 | 0.00 | 0.00 |
August | 225.00 | 42.03 | 182.97 | 457.92 | 53.33 | 0.00 | 0.00 | 0.00 |
September | 247.45 | 92.04 | 155.41 | 425.94 | 128.44 | 0.00 | 0.00 | 0.00 |
October | 358.72 | 232.38 | 126.34 | 527.63 | 263.16 | 0.00 | 0.00 | 0.00 |
November | 385.92 | 256.09 | 129.83 | 503.03 | 345.10 | 0.00 | 0.00 | 0.00 |
December | 391.26 | 275.25 | 116.01 | 460.61 | 420.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 294.25 | 143.31 | 150.94 | 426.82 | 244.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.41 | 10.37 | 116.01 | 318.67 | 53.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 396.93 | 276.74 | 182.97 | 527.63 | 478.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 396.91 | 276.73 | 120.19 | 438.39 | 478.54 | 0.00 | 0.00 | 0.00 |
February | 370.45 | 248.32 | 122.13 | 448.68 | 415.64 | 0.00 | 0.00 | 0.00 |
March | 333.16 | 173.62 | 159.54 | 440.49 | 289.50 | 0.00 | 0.00 | 0.00 |
April | 249.52 | 81.22 | 168.29 | 369.19 | 235.89 | 0.00 | 0.00 | 0.00 |
May | 201.60 | 23.43 | 178.17 | 318.65 | 153.93 | 0.00 | 0.00 | 0.00 |
June | 186.40 | 10.37 | 176.03 | 354.29 | 94.03 | 0.00 | 0.00 | 0.00 |
July | 188.45 | 14.05 | 174.40 | 377.27 | 64.26 | 0.00 | 0.00 | 0.00 |
August | 224.99 | 42.03 | 182.96 | 457.91 | 53.33 | 0.00 | 0.00 | 0.00 |
September | 247.44 | 92.03 | 155.40 | 425.93 | 128.44 | 0.00 | 0.00 | 0.00 |
October | 358.71 | 232.37 | 126.34 | 527.61 | 263.15 | 0.00 | 0.00 | 0.00 |
November | 385.91 | 256.08 | 129.83 | 503.01 | 345.09 | 0.00 | 0.00 | 0.00 |
December | 391.25 | 275.24 | 116.00 | 460.60 | 420.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 294.24 | 143.30 | 150.94 | 426.81 | 244.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.40 | 10.37 | 116.00 | 318.65 | 53.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 396.91 | 276.73 | 182.96 | 527.61 | 478.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 186.02 | 86.29 | 99.73 | 131.88 | 635.38 | 0.00 | 0.00 | 0.00 |
February | 213.55 | 99.85 | 113.70 | 200.89 | 552.40 | 0.00 | 0.00 | 0.00 |
March | 314.76 | 152.10 | 162.66 | 368.25 | 376.44 | 0.00 | 0.00 | 0.00 |
April | 354.10 | 162.04 | 192.07 | 482.67 | 301.53 | 0.00 | 0.00 | 0.00 |
May | 355.89 | 134.83 | 221.05 | 551.71 | 188.14 | 0.00 | 0.00 | 0.00 |
June | 374.26 | 143.98 | 230.28 | 658.34 | 123.89 | 0.00 | 0.00 | 0.00 |
July | 353.01 | 130.89 | 222.13 | 639.86 | 92.18 | 0.00 | 0.00 | 0.00 |
August | 345.90 | 129.35 | 216.55 | 630.12 | 85.07 | 0.00 | 0.00 | 0.00 |
September | 281.82 | 117.39 | 164.43 | 449.00 | 157.68 | 0.00 | 0.00 | 0.00 |
October | 251.06 | 130.33 | 120.73 | 328.87 | 340.65 | 0.00 | 0.00 | 0.00 |
November | 200.37 | 89.94 | 110.43 | 202.39 | 467.76 | 0.00 | 0.00 | 0.00 |
December | 165.30 | 72.30 | 93.00 | 120.29 | 603.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 283.36 | 120.86 | 162.50 | 398.08 | 325.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 165.30 | 72.30 | 93.00 | 120.29 | 85.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.26 | 162.04 | 230.28 | 658.34 | 635.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 186.02 | 86.29 | 99.73 | 131.88 | 635.38 | 0.00 | 0.00 | 0.00 |
February | 213.55 | 99.85 | 113.70 | 200.89 | 552.40 | 0.00 | 0.00 | 0.00 |
March | 314.76 | 152.10 | 162.66 | 368.25 | 376.44 | 0.00 | 0.00 | 0.00 |
April | 354.10 | 162.04 | 192.07 | 482.67 | 301.53 | 0.00 | 0.00 | 0.00 |
May | 355.89 | 134.83 | 221.05 | 551.71 | 188.14 | 0.00 | 0.00 | 0.00 |
June | 374.26 | 143.98 | 230.28 | 658.34 | 123.89 | 0.00 | 0.00 | 0.00 |
July | 353.01 | 130.89 | 222.13 | 639.86 | 92.18 | 0.00 | 0.00 | 0.00 |
August | 345.90 | 129.35 | 216.55 | 630.12 | 85.07 | 0.00 | 0.00 | 0.00 |
September | 281.82 | 117.39 | 164.43 | 449.00 | 157.68 | 0.00 | 0.00 | 0.00 |
October | 251.06 | 130.33 | 120.73 | 328.87 | 340.65 | 0.00 | 0.00 | 0.00 |
November | 200.37 | 89.94 | 110.43 | 202.39 | 467.76 | 0.00 | 0.00 | 0.00 |
December | 165.30 | 72.30 | 93.00 | 120.29 | 603.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 283.36 | 120.86 | 162.50 | 398.08 | 325.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 165.30 | 72.30 | 93.00 | 120.29 | 85.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.26 | 162.04 | 230.28 | 658.34 | 635.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 186.02 | 86.29 | 99.73 | 131.88 | 635.36 | 0.00 | 0.00 | 0.00 |
February | 213.55 | 99.85 | 113.70 | 200.89 | 552.39 | 0.00 | 0.00 | 0.00 |
March | 314.76 | 152.10 | 162.66 | 368.24 | 376.44 | 0.00 | 0.00 | 0.00 |
April | 354.10 | 162.03 | 192.06 | 482.66 | 301.52 | 0.00 | 0.00 | 0.00 |
May | 355.88 | 134.83 | 221.05 | 551.70 | 188.13 | 0.00 | 0.00 | 0.00 |
June | 374.25 | 143.97 | 230.28 | 658.33 | 123.89 | 0.00 | 0.00 | 0.00 |
July | 353.01 | 130.88 | 222.12 | 639.85 | 92.18 | 0.00 | 0.00 | 0.00 |
August | 345.90 | 129.35 | 216.54 | 630.11 | 85.07 | 0.00 | 0.00 | 0.00 |
September | 281.81 | 117.39 | 164.42 | 448.99 | 157.68 | 0.00 | 0.00 | 0.00 |
October | 251.06 | 130.33 | 120.73 | 328.86 | 340.64 | 0.00 | 0.00 | 0.00 |
November | 200.36 | 89.93 | 110.43 | 202.39 | 467.76 | 0.00 | 0.00 | 0.00 |
December | 165.30 | 72.30 | 93.00 | 120.29 | 603.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 283.35 | 120.86 | 162.49 | 398.07 | 325.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 165.30 | 72.30 | 93.00 | 120.29 | 85.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.25 | 162.03 | 230.28 | 658.33 | 635.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 371.10 | 0.00 | 371.10 | 49.29 | 2641.84 | 0.00 | 0.00 | 0.00 |
February | 411.33 | 0.00 | 411.33 | 168.33 | 2173.89 | 0.00 | 0.00 | 0.00 |
March | 577.48 | 0.00 | 577.48 | 379.58 | 1385.65 | 0.00 | 0.00 | 0.00 |
April | 698.52 | 3.10 | 695.42 | 760.05 | 1093.88 | 0.00 | 0.00 | 0.00 |
May | 835.42 | 26.66 | 808.75 | 1169.89 | 704.82 | 0.00 | 0.00 | 0.00 |
June | 919.41 | 60.70 | 858.71 | 1694.48 | 440.58 | 0.00 | 0.00 | 0.00 |
July | 867.47 | 42.17 | 825.30 | 1701.53 | 314.46 | 0.00 | 0.00 | 0.00 |
August | 771.47 | 8.40 | 763.07 | 1556.70 | 259.43 | 0.00 | 0.00 | 0.00 |
September | 583.16 | 0.08 | 583.08 | 880.14 | 599.61 | 0.00 | 0.00 | 0.00 |
October | 443.39 | 0.00 | 443.39 | 388.95 | 1261.01 | 0.00 | 0.00 | 0.00 |
November | 396.82 | 0.00 | 396.82 | 195.66 | 1726.38 | 0.00 | 0.00 | 0.00 |
December | 343.05 | 0.00 | 343.05 | 49.38 | 2171.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 602.59 | 11.81 | 590.78 | 752.82 | 1226.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 343.05 | 0.00 | 343.05 | 49.29 | 259.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 919.41 | 60.70 | 858.71 | 1701.53 | 2641.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 543.32 | 245.06 | 298.25 | 367.95 | 1580.23 | 0.00 | 0.00 | 0.00 |
February | 684.95 | 368.02 | 316.93 | 650.00 | 1309.56 | 0.00 | 0.00 | 0.00 |
March | 861.75 | 392.29 | 469.46 | 959.64 | 850.08 | 0.00 | 0.00 | 0.00 |
April | 1042.08 | 475.16 | 566.92 | 1428.64 | 687.60 | 0.00 | 0.00 | 0.00 |
May | 1144.28 | 483.90 | 660.38 | 1752.18 | 464.63 | 0.00 | 0.00 | 0.00 |
June | 1184.71 | 496.54 | 688.17 | 2084.79 | 296.20 | 0.00 | 0.00 | 0.00 |
July | 1155.14 | 485.64 | 669.50 | 2107.83 | 210.87 | 0.00 | 0.00 | 0.00 |
August | 1056.57 | 419.18 | 637.39 | 1963.86 | 173.30 | 0.00 | 0.00 | 0.00 |
September | 868.36 | 384.75 | 483.61 | 1392.54 | 383.85 | 0.00 | 0.00 | 0.00 |
October | 740.78 | 385.45 | 355.34 | 944.18 | 777.31 | 0.00 | 0.00 | 0.00 |
November | 592.26 | 268.17 | 324.09 | 575.69 | 1030.10 | 0.00 | 0.00 | 0.00 |
December | 513.01 | 233.85 | 279.16 | 373.75 | 1291.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 866.47 | 386.44 | 480.03 | 1219.73 | 751.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 513.01 | 233.85 | 279.16 | 367.95 | 173.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1184.71 | 496.54 | 688.17 | 2107.83 | 1580.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1984.69 | 1383.72 | 600.97 | 2198.90 | 2277.06 | 0.00 | 0.00 | 0.00 |
February | 1852.38 | 1241.70 | 610.68 | 2246.19 | 1971.66 | 0.00 | 0.00 | 0.00 |
March | 1665.92 | 868.18 | 797.74 | 2192.73 | 1389.56 | 0.00 | 0.00 | 0.00 |
April | 1247.66 | 406.14 | 841.52 | 1843.54 | 1146.60 | 0.00 | 0.00 | 0.00 |
May | 1008.06 | 117.16 | 890.89 | 1590.88 | 752.83 | 0.00 | 0.00 | 0.00 |
June | 932.06 | 51.87 | 880.19 | 1777.78 | 470.98 | 0.00 | 0.00 | 0.00 |
July | 942.29 | 70.26 | 872.03 | 1894.82 | 328.68 | 0.00 | 0.00 | 0.00 |
August | 1125.03 | 210.16 | 914.87 | 2294.65 | 279.75 | 0.00 | 0.00 | 0.00 |
September | 1237.25 | 460.19 | 777.06 | 2122.27 | 630.02 | 0.00 | 0.00 | 0.00 |
October | 1793.66 | 1161.94 | 631.73 | 2624.88 | 1266.92 | 0.00 | 0.00 | 0.00 |
November | 1929.66 | 1280.49 | 649.17 | 2515.16 | 1647.76 | 0.00 | 0.00 | 0.00 |
December | 1956.35 | 1376.31 | 580.04 | 2317.00 | 1957.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1471.29 | 716.57 | 754.72 | 2134.75 | 1172.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 932.06 | 51.87 | 580.04 | 1590.88 | 279.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1984.69 | 1383.72 | 914.87 | 2624.88 | 2277.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 558.06 | 258.87 | 299.19 | 426.49 | 1680.91 | 0.00 | 0.00 | 0.00 |
February | 640.65 | 299.54 | 341.11 | 644.49 | 1418.42 | 0.00 | 0.00 | 0.00 |
March | 944.28 | 456.30 | 487.98 | 1150.78 | 951.91 | 0.00 | 0.00 | 0.00 |
April | 1062.30 | 486.10 | 576.20 | 1497.76 | 781.17 | 0.00 | 0.00 | 0.00 |
May | 1067.64 | 404.49 | 663.16 | 1668.04 | 523.20 | 0.00 | 0.00 | 0.00 |
June | 1122.77 | 431.92 | 690.84 | 1995.04 | 341.95 | 0.00 | 0.00 | 0.00 |
July | 1059.03 | 392.65 | 666.38 | 1954.17 | 242.80 | 0.00 | 0.00 | 0.00 |
August | 1037.70 | 388.06 | 649.64 | 1933.07 | 211.06 | 0.00 | 0.00 | 0.00 |
September | 845.44 | 352.16 | 493.28 | 1364.83 | 424.98 | 0.00 | 0.00 | 0.00 |
October | 753.19 | 390.99 | 362.20 | 1020.89 | 871.08 | 0.00 | 0.00 | 0.00 |
November | 601.10 | 269.80 | 331.29 | 664.92 | 1158.68 | 0.00 | 0.00 | 0.00 |
December | 495.90 | 216.91 | 278.99 | 411.75 | 1425.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 850.07 | 362.58 | 487.49 | 1230.80 | 832.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 495.90 | 216.91 | 278.99 | 411.75 | 211.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1122.77 | 486.10 | 690.84 | 1995.04 | 1680.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 371.10 | 0.00 | 371.10 | 62.59 | 2468.48 | 0.00 | 0.00 | 0.00 |
February | 411.33 | 0.00 | 411.33 | 185.94 | 2034.24 | 0.00 | 0.00 | 0.00 |
March | 577.48 | 0.00 | 577.48 | 410.43 | 1274.52 | 0.00 | 0.00 | 0.00 |
April | 698.52 | 3.10 | 695.42 | 779.65 | 1036.32 | 0.00 | 0.00 | 0.00 |
May | 835.42 | 26.66 | 808.75 | 1166.37 | 690.85 | 0.00 | 0.00 | 0.00 |
June | 919.41 | 60.70 | 858.71 | 1676.14 | 445.72 | 0.00 | 0.00 | 0.00 |
July | 867.47 | 42.17 | 825.30 | 1679.37 | 319.90 | 0.00 | 0.00 | 0.00 |
August | 771.47 | 8.40 | 763.07 | 1534.99 | 266.23 | 0.00 | 0.00 | 0.00 |
September | 583.16 | 0.08 | 583.08 | 879.79 | 578.50 | 0.00 | 0.00 | 0.00 |
October | 443.39 | 0.00 | 443.39 | 414.33 | 1156.35 | 0.00 | 0.00 | 0.00 |
November | 396.82 | 0.00 | 396.82 | 234.58 | 1563.22 | 0.00 | 0.00 | 0.00 |
December | 343.05 | 0.00 | 343.05 | 65.33 | 1967.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 602.59 | 11.81 | 590.78 | 760.68 | 1145.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 343.05 | 0.00 | 343.05 | 62.59 | 266.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 919.41 | 60.70 | 858.71 | 1679.37 | 2468.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 543.32 | 245.06 | 298.25 | 389.48 | 1473.12 | 0.00 | 0.00 | 0.00 |
February | 684.95 | 368.02 | 316.93 | 670.32 | 1228.81 | 0.00 | 0.00 | 0.00 |
March | 861.75 | 392.29 | 469.46 | 981.01 | 797.69 | 0.00 | 0.00 | 0.00 |
April | 1042.08 | 475.16 | 566.92 | 1435.62 | 664.33 | 0.00 | 0.00 | 0.00 |
May | 1144.28 | 483.90 | 660.38 | 1743.66 | 462.71 | 0.00 | 0.00 | 0.00 |
June | 1184.71 | 496.54 | 688.17 | 2068.43 | 302.74 | 0.00 | 0.00 | 0.00 |
July | 1155.14 | 485.64 | 669.50 | 2088.91 | 216.22 | 0.00 | 0.00 | 0.00 |
August | 1056.57 | 419.18 | 637.39 | 1945.71 | 179.42 | 0.00 | 0.00 | 0.00 |
September | 868.36 | 384.75 | 483.61 | 1387.06 | 377.86 | 0.00 | 0.00 | 0.00 |
October | 740.78 | 385.45 | 355.34 | 958.92 | 730.00 | 0.00 | 0.00 | 0.00 |
November | 592.26 | 268.17 | 324.09 | 610.04 | 946.61 | 0.00 | 0.00 | 0.00 |
December | 513.01 | 233.85 | 279.16 | 398.45 | 1172.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 866.47 | 386.44 | 480.03 | 1226.01 | 709.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 513.01 | 233.85 | 279.16 | 389.48 | 179.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1184.71 | 496.54 | 688.17 | 2088.91 | 1473.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1984.69 | 1383.72 | 600.97 | 2257.56 | 2105.55 | 0.00 | 0.00 | 0.00 |
February | 1852.38 | 1241.70 | 610.68 | 2285.10 | 1839.68 | 0.00 | 0.00 | 0.00 |
March | 1665.92 | 868.18 | 797.74 | 2219.49 | 1300.06 | 0.00 | 0.00 | 0.00 |
April | 1247.66 | 406.14 | 841.52 | 1855.01 | 1096.94 | 0.00 | 0.00 | 0.00 |
May | 1008.06 | 117.16 | 890.89 | 1583.35 | 740.05 | 0.00 | 0.00 | 0.00 |
June | 932.06 | 51.87 | 880.19 | 1758.89 | 475.31 | 0.00 | 0.00 | 0.00 |
July | 942.29 | 70.26 | 872.03 | 1872.01 | 333.66 | 0.00 | 0.00 | 0.00 |
August | 1125.03 | 210.16 | 914.87 | 2271.06 | 287.51 | 0.00 | 0.00 | 0.00 |
September | 1237.25 | 460.19 | 777.06 | 2115.91 | 615.89 | 0.00 | 0.00 | 0.00 |
October | 1793.66 | 1161.94 | 631.73 | 2640.84 | 1187.73 | 0.00 | 0.00 | 0.00 |
November | 1929.66 | 1280.49 | 649.17 | 2564.29 | 1514.90 | 0.00 | 0.00 | 0.00 |
December | 1956.35 | 1376.31 | 580.04 | 2375.94 | 1772.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1471.29 | 716.57 | 754.72 | 2149.68 | 1101.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 932.06 | 51.87 | 580.04 | 1583.35 | 287.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1984.69 | 1383.72 | 914.87 | 2640.84 | 2105.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 558.06 | 258.87 | 299.19 | 442.29 | 1571.98 | 0.00 | 0.00 | 0.00 |
February | 640.65 | 299.54 | 341.11 | 655.15 | 1339.36 | 0.00 | 0.00 | 0.00 |
March | 944.28 | 456.30 | 487.98 | 1162.71 | 894.90 | 0.00 | 0.00 | 0.00 |
April | 1062.30 | 486.10 | 576.20 | 1503.30 | 751.85 | 0.00 | 0.00 | 0.00 |
May | 1067.64 | 404.49 | 663.16 | 1662.43 | 516.27 | 0.00 | 0.00 | 0.00 |
June | 1122.77 | 431.92 | 690.84 | 1980.60 | 344.82 | 0.00 | 0.00 | 0.00 |
July | 1059.03 | 392.65 | 666.38 | 1939.30 | 245.25 | 0.00 | 0.00 | 0.00 |
August | 1037.70 | 388.06 | 649.64 | 1918.25 | 214.78 | 0.00 | 0.00 | 0.00 |
September | 845.44 | 352.16 | 493.28 | 1362.00 | 415.25 | 0.00 | 0.00 | 0.00 |
October | 753.19 | 390.99 | 362.20 | 1029.83 | 819.15 | 0.00 | 0.00 | 0.00 |
November | 601.10 | 269.80 | 331.29 | 685.43 | 1074.20 | 0.00 | 0.00 | 0.00 |
December | 495.90 | 216.91 | 278.99 | 426.66 | 1312.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 850.07 | 362.58 | 487.49 | 1233.73 | 788.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 495.90 | 216.91 | 278.99 | 426.66 | 214.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1122.77 | 486.10 | 690.84 | 1980.60 | 1571.98 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198791E+09 | 0.00 | 0.198791E+09 | 17678423.19 | 0.159192E+10 |
February | 0.199017E+09 | 0.00 | 0.199017E+09 | 65431587.98 | 0.118528E+10 |
March | 0.309346E+09 | 0.00 | 0.309346E+09 | 0.180281E+09 | 0.829177E+09 |
April | 0.362112E+09 | 1606061.20 | 0.360506E+09 | 0.376360E+09 | 0.607880E+09 |
May | 0.447516E+09 | 14282166.31 | 0.433234E+09 | 0.621497E+09 | 0.391484E+09 |
June | 0.476624E+09 | 31468210.52 | 0.445155E+09 | 0.873846E+09 | 0.228828E+09 |
July | 0.464685E+09 | 22588531.99 | 0.442097E+09 | 0.905303E+09 | 0.166348E+09 |
August | 0.413261E+09 | 4501801.68 | 0.408759E+09 | 0.824740E+09 | 0.135968E+09 |
September | 0.302309E+09 | 42556.45 | 0.302267E+09 | 0.448748E+09 | 0.328538E+09 |
October | 0.237518E+09 | 0.00 | 0.237518E+09 | 0.188668E+09 | 0.755433E+09 |
November | 0.205713E+09 | 0.00 | 0.205713E+09 | 75437397.74 | 0.102098E+10 |
December | 0.183767E+09 | 0.00 | 0.183767E+09 | 14453234.12 | 0.137496E+10 |
Annual Sum or Average | 0.380066E+10 | 74489328.14 | 0.372617E+10 | 0.459244E+10 | 0.861680E+10 |
Minimum of Months | 0.183767E+09 | 0.00 | 0.183767E+09 | 14453234.12 | 0.135968E+09 |
Maximum of Months | 0.476624E+09 | 31468210.52 | 0.445155E+09 | 0.905303E+09 | 0.159192E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198788E+09 | 0.00 | 0.198788E+09 | 17677743.18 | 0.159192E+10 |
February | 0.199014E+09 | 0.00 | 0.199014E+09 | 65430064.09 | 0.118528E+10 |
March | 0.309342E+09 | 0.00 | 0.309342E+09 | 0.180277E+09 | 0.829176E+09 |
April | 0.362107E+09 | 1606025.89 | 0.360501E+09 | 0.376354E+09 | 0.607879E+09 |
May | 0.447510E+09 | 14281852.33 | 0.433228E+09 | 0.621488E+09 | 0.391483E+09 |
June | 0.476617E+09 | 31467518.73 | 0.445149E+09 | 0.873836E+09 | 0.228826E+09 |
July | 0.464678E+09 | 22588035.41 | 0.442090E+09 | 0.905293E+09 | 0.166347E+09 |
August | 0.413255E+09 | 4501702.71 | 0.408754E+09 | 0.824732E+09 | 0.135967E+09 |
September | 0.302305E+09 | 42555.51 | 0.302263E+09 | 0.448743E+09 | 0.328536E+09 |
October | 0.237515E+09 | 0.00 | 0.237515E+09 | 0.188666E+09 | 0.755432E+09 |
November | 0.205710E+09 | 0.00 | 0.205710E+09 | 75435236.01 | 0.102098E+10 |
December | 0.183765E+09 | 0.00 | 0.183765E+09 | 14452551.87 | 0.137496E+10 |
Annual Sum or Average | 0.380061E+10 | 74487690.58 | 0.372612E+10 | 0.459238E+10 | 0.861678E+10 |
Minimum of Months | 0.183765E+09 | 0.00 | 0.183765E+09 | 14452551.87 | 0.135967E+09 |
Maximum of Months | 0.476617E+09 | 31467518.73 | 0.445149E+09 | 0.905293E+09 | 0.159192E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198789E+09 | 0.00 | 0.198789E+09 | 17677969.85 | 0.159192E+10 |
February | 0.199015E+09 | 0.00 | 0.199015E+09 | 65430572.06 | 0.118528E+10 |
March | 0.309343E+09 | 0.00 | 0.309343E+09 | 0.180279E+09 | 0.829176E+09 |
April | 0.362109E+09 | 1606037.66 | 0.360502E+09 | 0.376356E+09 | 0.607879E+09 |
May | 0.447512E+09 | 14281956.99 | 0.433230E+09 | 0.621491E+09 | 0.391484E+09 |
June | 0.476619E+09 | 31467749.32 | 0.445151E+09 | 0.873839E+09 | 0.228827E+09 |
July | 0.464681E+09 | 22588200.93 | 0.442092E+09 | 0.905296E+09 | 0.166347E+09 |
August | 0.413257E+09 | 4501735.70 | 0.408755E+09 | 0.824734E+09 | 0.135967E+09 |
September | 0.302307E+09 | 42555.83 | 0.302264E+09 | 0.448745E+09 | 0.328537E+09 |
October | 0.237516E+09 | 0.00 | 0.237516E+09 | 0.188667E+09 | 0.755432E+09 |
November | 0.205711E+09 | 0.00 | 0.205711E+09 | 75435956.58 | 0.102098E+10 |
December | 0.183766E+09 | 0.00 | 0.183766E+09 | 14452779.29 | 0.137496E+10 |
Annual Sum or Average | 0.380062E+10 | 74488236.43 | 0.372613E+10 | 0.459240E+10 | 0.861679E+10 |
Minimum of Months | 0.183766E+09 | 0.00 | 0.183766E+09 | 14452779.29 | 0.135967E+09 |
Maximum of Months | 0.476619E+09 | 31467749.32 | 0.445151E+09 | 0.905296E+09 | 0.159192E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198788E+09 | 0.00 | 0.198788E+09 | 17677743.18 | 0.159192E+10 |
February | 0.199014E+09 | 0.00 | 0.199014E+09 | 65430064.09 | 0.118528E+10 |
March | 0.309342E+09 | 0.00 | 0.309342E+09 | 0.180277E+09 | 0.829176E+09 |
April | 0.362107E+09 | 1606025.89 | 0.360501E+09 | 0.376354E+09 | 0.607879E+09 |
May | 0.447510E+09 | 14281852.33 | 0.433228E+09 | 0.621488E+09 | 0.391483E+09 |
June | 0.476617E+09 | 31467518.73 | 0.445149E+09 | 0.873836E+09 | 0.228826E+09 |
July | 0.464678E+09 | 22588035.41 | 0.442090E+09 | 0.905293E+09 | 0.166347E+09 |
August | 0.413255E+09 | 4501702.71 | 0.408754E+09 | 0.824732E+09 | 0.135967E+09 |
September | 0.302305E+09 | 42555.51 | 0.302263E+09 | 0.448743E+09 | 0.328536E+09 |
October | 0.237515E+09 | 0.00 | 0.237515E+09 | 0.188666E+09 | 0.755432E+09 |
November | 0.205710E+09 | 0.00 | 0.205710E+09 | 75435236.01 | 0.102098E+10 |
December | 0.183765E+09 | 0.00 | 0.183765E+09 | 14452551.87 | 0.137496E+10 |
Annual Sum or Average | 0.380061E+10 | 74487690.58 | 0.372612E+10 | 0.459238E+10 | 0.861678E+10 |
Minimum of Months | 0.183765E+09 | 0.00 | 0.183765E+09 | 14452551.87 | 0.135967E+09 |
Maximum of Months | 0.476617E+09 | 31467518.73 | 0.445149E+09 | 0.905293E+09 | 0.159192E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198780E+09 | 0.00 | 0.198780E+09 | 17677144.02 | 0.159185E+10 |
February | 0.199007E+09 | 0.00 | 0.199007E+09 | 65427680.94 | 0.118523E+10 |
March | 0.309330E+09 | 0.00 | 0.309330E+09 | 0.180271E+09 | 0.829142E+09 |
April | 0.362093E+09 | 1605967.04 | 0.360487E+09 | 0.376340E+09 | 0.607854E+09 |
May | 0.447493E+09 | 14281329.04 | 0.433212E+09 | 0.621465E+09 | 0.391468E+09 |
June | 0.476599E+09 | 31466365.74 | 0.445132E+09 | 0.873803E+09 | 0.228817E+09 |
July | 0.464661E+09 | 22587207.77 | 0.442074E+09 | 0.905258E+09 | 0.166340E+09 |
August | 0.413240E+09 | 4501537.77 | 0.408738E+09 | 0.824700E+09 | 0.135961E+09 |
September | 0.302294E+09 | 42553.96 | 0.302251E+09 | 0.448726E+09 | 0.328523E+09 |
October | 0.237506E+09 | 0.00 | 0.237506E+09 | 0.188658E+09 | 0.755401E+09 |
November | 0.205702E+09 | 0.00 | 0.205702E+09 | 75432555.91 | 0.102094E+10 |
December | 0.183758E+09 | 0.00 | 0.183758E+09 | 14452083.07 | 0.137491E+10 |
Annual Sum or Average | 0.380046E+10 | 74484961.31 | 0.372598E+10 | 0.459221E+10 | 0.861644E+10 |
Minimum of Months | 0.183758E+09 | 0.00 | 0.183758E+09 | 14452083.07 | 0.135961E+09 |
Maximum of Months | 0.476599E+09 | 31466365.74 | 0.445132E+09 | 0.905258E+09 | 0.159185E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.485078E+09 | 0.218795E+09 | 0.266283E+09 | 0.305954E+09 | 0.156797E+10 |
February | 0.552351E+09 | 0.296774E+09 | 0.255577E+09 | 0.505664E+09 | 0.115886E+10 |
March | 0.769377E+09 | 0.350243E+09 | 0.419134E+09 | 0.846811E+09 | 0.809113E+09 |
April | 0.900364E+09 | 0.410543E+09 | 0.489821E+09 | 0.123975E+10 | 0.601593E+09 |
May | 0.102162E+10 | 0.432029E+09 | 0.589593E+09 | 0.157581E+10 | 0.420168E+09 |
June | 0.102360E+10 | 0.429017E+09 | 0.594585E+09 | 0.181532E+10 | 0.242157E+09 |
July | 0.103132E+10 | 0.433583E+09 | 0.597740E+09 | 0.189826E+10 | 0.167384E+09 |
August | 0.943319E+09 | 0.374248E+09 | 0.569071E+09 | 0.176927E+10 | 0.125920E+09 |
September | 0.750271E+09 | 0.332425E+09 | 0.417845E+09 | 0.120649E+10 | 0.340069E+09 |
October | 0.661379E+09 | 0.344132E+09 | 0.317248E+09 | 0.833336E+09 | 0.747486E+09 |
November | 0.511721E+09 | 0.231705E+09 | 0.280016E+09 | 0.468724E+09 | 0.978974E+09 |
December | 0.458024E+09 | 0.208785E+09 | 0.249239E+09 | 0.307680E+09 | 0.130866E+10 |
Annual Sum or Average | 0.910843E+10 | 0.406228E+10 | 0.504615E+10 | 0.127731E+11 | 0.846835E+10 |
Minimum of Months | 0.458024E+09 | 0.208785E+09 | 0.249239E+09 | 0.305954E+09 | 0.125920E+09 |
Maximum of Months | 0.103132E+10 | 0.433583E+09 | 0.597740E+09 | 0.189826E+10 | 0.156797E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.485078E+09 | 0.218795E+09 | 0.266283E+09 | 0.305954E+09 | 0.156797E+10 |
February | 0.552351E+09 | 0.296774E+09 | 0.255577E+09 | 0.505664E+09 | 0.115886E+10 |
March | 0.769377E+09 | 0.350243E+09 | 0.419134E+09 | 0.846811E+09 | 0.809113E+09 |
April | 0.900364E+09 | 0.410543E+09 | 0.489821E+09 | 0.123975E+10 | 0.601593E+09 |
May | 0.102162E+10 | 0.432029E+09 | 0.589593E+09 | 0.157581E+10 | 0.420168E+09 |
June | 0.102360E+10 | 0.429017E+09 | 0.594585E+09 | 0.181532E+10 | 0.242157E+09 |
July | 0.103132E+10 | 0.433583E+09 | 0.597740E+09 | 0.189826E+10 | 0.167384E+09 |
August | 0.943319E+09 | 0.374248E+09 | 0.569071E+09 | 0.176927E+10 | 0.125920E+09 |
September | 0.750271E+09 | 0.332425E+09 | 0.417845E+09 | 0.120649E+10 | 0.340069E+09 |
October | 0.661379E+09 | 0.344132E+09 | 0.317248E+09 | 0.833336E+09 | 0.747486E+09 |
November | 0.511721E+09 | 0.231705E+09 | 0.280016E+09 | 0.468724E+09 | 0.978974E+09 |
December | 0.458024E+09 | 0.208785E+09 | 0.249239E+09 | 0.307680E+09 | 0.130866E+10 |
Annual Sum or Average | 0.910843E+10 | 0.406228E+10 | 0.504615E+10 | 0.127731E+11 | 0.846835E+10 |
Minimum of Months | 0.458024E+09 | 0.208785E+09 | 0.249239E+09 | 0.305954E+09 | 0.125920E+09 |
Maximum of Months | 0.103132E+10 | 0.433583E+09 | 0.597740E+09 | 0.189826E+10 | 0.156797E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.485069E+09 | 0.218791E+09 | 0.266279E+09 | 0.305949E+09 | 0.156794E+10 |
February | 0.552341E+09 | 0.296769E+09 | 0.255572E+09 | 0.505655E+09 | 0.115884E+10 |
March | 0.769363E+09 | 0.350237E+09 | 0.419127E+09 | 0.846796E+09 | 0.809098E+09 |
April | 0.900347E+09 | 0.410535E+09 | 0.489812E+09 | 0.123973E+10 | 0.601582E+09 |
May | 0.102160E+10 | 0.432021E+09 | 0.589582E+09 | 0.157578E+10 | 0.420161E+09 |
June | 0.102358E+10 | 0.429009E+09 | 0.594575E+09 | 0.181529E+10 | 0.242152E+09 |
July | 0.103130E+10 | 0.433575E+09 | 0.597729E+09 | 0.189822E+10 | 0.167381E+09 |
August | 0.943302E+09 | 0.374241E+09 | 0.569060E+09 | 0.176923E+10 | 0.125917E+09 |
September | 0.750257E+09 | 0.332419E+09 | 0.417838E+09 | 0.120646E+10 | 0.340062E+09 |
October | 0.661367E+09 | 0.344126E+09 | 0.317242E+09 | 0.833321E+09 | 0.747473E+09 |
November | 0.511712E+09 | 0.231701E+09 | 0.280011E+09 | 0.468716E+09 | 0.978956E+09 |
December | 0.458016E+09 | 0.208781E+09 | 0.249234E+09 | 0.307674E+09 | 0.130864E+10 |
Annual Sum or Average | 0.910827E+10 | 0.406221E+10 | 0.504606E+10 | 0.127728E+11 | 0.846820E+10 |
Minimum of Months | 0.458016E+09 | 0.208781E+09 | 0.249234E+09 | 0.305949E+09 | 0.125917E+09 |
Maximum of Months | 0.103130E+10 | 0.433575E+09 | 0.597729E+09 | 0.189822E+10 | 0.156794E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106314E+10 | 0.741215E+09 | 0.321924E+09 | 0.117424E+10 | 0.128177E+10 |
February | 0.896239E+09 | 0.600772E+09 | 0.295467E+09 | 0.108550E+10 | 0.100556E+10 |
March | 0.892383E+09 | 0.465055E+09 | 0.427328E+09 | 0.117986E+10 | 0.775423E+09 |
April | 0.646778E+09 | 0.210538E+09 | 0.436239E+09 | 0.956995E+09 | 0.611443E+09 |
May | 0.539991E+09 | 62760903.20 | 0.477230E+09 | 0.853517E+09 | 0.412308E+09 |
June | 0.483173E+09 | 26886366.83 | 0.456287E+09 | 0.918363E+09 | 0.243749E+09 |
July | 0.504761E+09 | 37637437.05 | 0.467123E+09 | 0.101053E+10 | 0.172127E+09 |
August | 0.602647E+09 | 0.112576E+09 | 0.490071E+09 | 0.122651E+10 | 0.142841E+09 |
September | 0.641382E+09 | 0.238559E+09 | 0.402823E+09 | 0.110405E+10 | 0.332920E+09 |
October | 0.960813E+09 | 0.622414E+09 | 0.338400E+09 | 0.141322E+10 | 0.704841E+09 |
November | 0.100032E+10 | 0.663792E+09 | 0.336525E+09 | 0.130387E+10 | 0.894506E+09 |
December | 0.104796E+10 | 0.737246E+09 | 0.310714E+09 | 0.123372E+10 | 0.112589E+10 |
Annual Sum or Average | 0.927958E+10 | 0.451945E+10 | 0.476013E+10 | 0.134604E+11 | 0.770338E+10 |
Minimum of Months | 0.483173E+09 | 26886366.83 | 0.295467E+09 | 0.853517E+09 | 0.142841E+09 |
Maximum of Months | 0.106314E+10 | 0.741215E+09 | 0.490071E+09 | 0.141322E+10 | 0.128177E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106313E+10 | 0.741209E+09 | 0.321922E+09 | 0.117423E+10 | 0.128177E+10 |
February | 0.896233E+09 | 0.600768E+09 | 0.295465E+09 | 0.108549E+10 | 0.100556E+10 |
March | 0.892377E+09 | 0.465052E+09 | 0.427325E+09 | 0.117985E+10 | 0.775423E+09 |
April | 0.646774E+09 | 0.210537E+09 | 0.436237E+09 | 0.956988E+09 | 0.611443E+09 |
May | 0.539988E+09 | 62760443.29 | 0.477227E+09 | 0.853513E+09 | 0.412307E+09 |
June | 0.483171E+09 | 26886169.80 | 0.456284E+09 | 0.918360E+09 | 0.243748E+09 |
July | 0.504758E+09 | 37637161.24 | 0.467121E+09 | 0.101052E+10 | 0.172126E+09 |
August | 0.602644E+09 | 0.112575E+09 | 0.490069E+09 | 0.122650E+10 | 0.142840E+09 |
September | 0.641378E+09 | 0.238558E+09 | 0.402821E+09 | 0.110405E+10 | 0.332919E+09 |
October | 0.960807E+09 | 0.622409E+09 | 0.338398E+09 | 0.141321E+10 | 0.704840E+09 |
November | 0.100031E+10 | 0.663787E+09 | 0.336523E+09 | 0.130385E+10 | 0.894506E+09 |
December | 0.104795E+10 | 0.737241E+09 | 0.310712E+09 | 0.123371E+10 | 0.112589E+10 |
Annual Sum or Average | 0.927952E+10 | 0.451942E+10 | 0.476010E+10 | 0.134603E+11 | 0.770338E+10 |
Minimum of Months | 0.483171E+09 | 26886169.80 | 0.295465E+09 | 0.853513E+09 | 0.142840E+09 |
Maximum of Months | 0.106313E+10 | 0.741209E+09 | 0.490069E+09 | 0.141321E+10 | 0.128177E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106314E+10 | 0.741215E+09 | 0.321924E+09 | 0.117424E+10 | 0.128177E+10 |
February | 0.896239E+09 | 0.600772E+09 | 0.295467E+09 | 0.108550E+10 | 0.100556E+10 |
March | 0.892383E+09 | 0.465055E+09 | 0.427328E+09 | 0.117986E+10 | 0.775423E+09 |
April | 0.646778E+09 | 0.210538E+09 | 0.436239E+09 | 0.956995E+09 | 0.611443E+09 |
May | 0.539991E+09 | 62760903.20 | 0.477230E+09 | 0.853517E+09 | 0.412308E+09 |
June | 0.483173E+09 | 26886366.83 | 0.456287E+09 | 0.918363E+09 | 0.243749E+09 |
July | 0.504761E+09 | 37637437.05 | 0.467123E+09 | 0.101053E+10 | 0.172127E+09 |
August | 0.602647E+09 | 0.112576E+09 | 0.490071E+09 | 0.122651E+10 | 0.142841E+09 |
September | 0.641382E+09 | 0.238559E+09 | 0.402823E+09 | 0.110405E+10 | 0.332920E+09 |
October | 0.960813E+09 | 0.622414E+09 | 0.338400E+09 | 0.141322E+10 | 0.704841E+09 |
November | 0.100032E+10 | 0.663792E+09 | 0.336525E+09 | 0.130387E+10 | 0.894506E+09 |
December | 0.104796E+10 | 0.737246E+09 | 0.310714E+09 | 0.123372E+10 | 0.112589E+10 |
Annual Sum or Average | 0.927958E+10 | 0.451945E+10 | 0.476013E+10 | 0.134604E+11 | 0.770338E+10 |
Minimum of Months | 0.483173E+09 | 26886366.83 | 0.295467E+09 | 0.853517E+09 | 0.142841E+09 |
Maximum of Months | 0.106314E+10 | 0.741215E+09 | 0.490071E+09 | 0.141322E+10 | 0.128177E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106313E+10 | 0.741209E+09 | 0.321922E+09 | 0.117423E+10 | 0.128177E+10 |
February | 0.896233E+09 | 0.600768E+09 | 0.295465E+09 | 0.108549E+10 | 0.100556E+10 |
March | 0.892377E+09 | 0.465052E+09 | 0.427325E+09 | 0.117985E+10 | 0.775423E+09 |
April | 0.646774E+09 | 0.210537E+09 | 0.436237E+09 | 0.956988E+09 | 0.611443E+09 |
May | 0.539988E+09 | 62760443.29 | 0.477227E+09 | 0.853513E+09 | 0.412307E+09 |
June | 0.483171E+09 | 26886169.80 | 0.456284E+09 | 0.918360E+09 | 0.243748E+09 |
July | 0.504758E+09 | 37637161.24 | 0.467121E+09 | 0.101052E+10 | 0.172126E+09 |
August | 0.602644E+09 | 0.112575E+09 | 0.490069E+09 | 0.122650E+10 | 0.142840E+09 |
September | 0.641378E+09 | 0.238558E+09 | 0.402821E+09 | 0.110405E+10 | 0.332919E+09 |
October | 0.960807E+09 | 0.622409E+09 | 0.338398E+09 | 0.141321E+10 | 0.704840E+09 |
November | 0.100031E+10 | 0.663787E+09 | 0.336523E+09 | 0.130385E+10 | 0.894506E+09 |
December | 0.104795E+10 | 0.737241E+09 | 0.310712E+09 | 0.123371E+10 | 0.112589E+10 |
Annual Sum or Average | 0.927952E+10 | 0.451942E+10 | 0.476010E+10 | 0.134603E+11 | 0.770338E+10 |
Minimum of Months | 0.483171E+09 | 26886169.80 | 0.295465E+09 | 0.853513E+09 | 0.142840E+09 |
Maximum of Months | 0.106313E+10 | 0.741209E+09 | 0.490069E+09 | 0.141321E+10 | 0.128177E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106309E+10 | 0.741182E+09 | 0.321910E+09 | 0.117419E+10 | 0.128172E+10 |
February | 0.896200E+09 | 0.600746E+09 | 0.295454E+09 | 0.108545E+10 | 0.100552E+10 |
March | 0.892344E+09 | 0.465035E+09 | 0.427309E+09 | 0.117980E+10 | 0.775392E+09 |
April | 0.646750E+09 | 0.210529E+09 | 0.436221E+09 | 0.956953E+09 | 0.611419E+09 |
May | 0.539967E+09 | 62758143.71 | 0.477209E+09 | 0.853480E+09 | 0.412291E+09 |
June | 0.483152E+09 | 26885184.68 | 0.456267E+09 | 0.918324E+09 | 0.243738E+09 |
July | 0.504739E+09 | 37635782.20 | 0.467103E+09 | 0.101049E+10 | 0.172120E+09 |
August | 0.602621E+09 | 0.112571E+09 | 0.490050E+09 | 0.122646E+10 | 0.142835E+09 |
September | 0.641354E+09 | 0.238549E+09 | 0.402805E+09 | 0.110400E+10 | 0.332906E+09 |
October | 0.960772E+09 | 0.622387E+09 | 0.338385E+09 | 0.141316E+10 | 0.704812E+09 |
November | 0.100027E+10 | 0.663763E+09 | 0.336510E+09 | 0.130381E+10 | 0.894470E+09 |
December | 0.104791E+10 | 0.737214E+09 | 0.310700E+09 | 0.123366E+10 | 0.112584E+10 |
Annual Sum or Average | 0.927918E+10 | 0.451925E+10 | 0.475992E+10 | 0.134598E+11 | 0.770307E+10 |
Minimum of Months | 0.483152E+09 | 26885184.68 | 0.295454E+09 | 0.853480E+09 | 0.142835E+09 |
Maximum of Months | 0.106309E+10 | 0.741182E+09 | 0.490050E+09 | 0.141316E+10 | 0.128172E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.498243E+09 | 0.231120E+09 | 0.267123E+09 | 0.353235E+09 | 0.170179E+10 |
February | 0.516627E+09 | 0.241554E+09 | 0.275072E+09 | 0.485994E+09 | 0.133636E+10 |
March | 0.843065E+09 | 0.407388E+09 | 0.435677E+09 | 0.986309E+09 | 0.100826E+10 |
April | 0.917838E+09 | 0.419999E+09 | 0.497839E+09 | 0.125109E+10 | 0.781560E+09 |
May | 0.953203E+09 | 0.361131E+09 | 0.592072E+09 | 0.147770E+10 | 0.503903E+09 |
June | 0.970082E+09 | 0.373186E+09 | 0.596896E+09 | 0.170641E+10 | 0.321118E+09 |
July | 0.945509E+09 | 0.350563E+09 | 0.594946E+09 | 0.171381E+10 | 0.246892E+09 |
August | 0.926464E+09 | 0.346461E+09 | 0.580003E+09 | 0.168772E+10 | 0.227843E+09 |
September | 0.730466E+09 | 0.304271E+09 | 0.426195E+09 | 0.116381E+10 | 0.408710E+09 |
October | 0.672451E+09 | 0.349076E+09 | 0.323375E+09 | 0.880835E+09 | 0.912398E+09 |
November | 0.519353E+09 | 0.233112E+09 | 0.286240E+09 | 0.524603E+09 | 0.121244E+10 |
December | 0.442744E+09 | 0.193657E+09 | 0.249087E+09 | 0.322191E+09 | 0.161738E+10 |
Annual Sum or Average | 0.893604E+10 | 0.381152E+10 | 0.512453E+10 | 0.125537E+11 | 0.102787E+11 |
Minimum of Months | 0.442744E+09 | 0.193657E+09 | 0.249087E+09 | 0.322191E+09 | 0.227843E+09 |
Maximum of Months | 0.970082E+09 | 0.419999E+09 | 0.596896E+09 | 0.171381E+10 | 0.170179E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.498243E+09 | 0.231120E+09 | 0.267123E+09 | 0.353235E+09 | 0.170179E+10 |
February | 0.516627E+09 | 0.241554E+09 | 0.275072E+09 | 0.485994E+09 | 0.133636E+10 |
March | 0.843065E+09 | 0.407388E+09 | 0.435677E+09 | 0.986309E+09 | 0.100826E+10 |
April | 0.917838E+09 | 0.419999E+09 | 0.497839E+09 | 0.125109E+10 | 0.781560E+09 |
May | 0.953203E+09 | 0.361131E+09 | 0.592072E+09 | 0.147770E+10 | 0.503903E+09 |
June | 0.970082E+09 | 0.373186E+09 | 0.596896E+09 | 0.170641E+10 | 0.321118E+09 |
July | 0.945509E+09 | 0.350563E+09 | 0.594946E+09 | 0.171381E+10 | 0.246892E+09 |
August | 0.926464E+09 | 0.346461E+09 | 0.580003E+09 | 0.168772E+10 | 0.227843E+09 |
September | 0.730466E+09 | 0.304271E+09 | 0.426195E+09 | 0.116381E+10 | 0.408710E+09 |
October | 0.672451E+09 | 0.349076E+09 | 0.323375E+09 | 0.880835E+09 | 0.912398E+09 |
November | 0.519353E+09 | 0.233112E+09 | 0.286240E+09 | 0.524603E+09 | 0.121244E+10 |
December | 0.442744E+09 | 0.193657E+09 | 0.249087E+09 | 0.322191E+09 | 0.161738E+10 |
Annual Sum or Average | 0.893604E+10 | 0.381152E+10 | 0.512453E+10 | 0.125537E+11 | 0.102787E+11 |
Minimum of Months | 0.442744E+09 | 0.193657E+09 | 0.249087E+09 | 0.322191E+09 | 0.227843E+09 |
Maximum of Months | 0.970082E+09 | 0.419999E+09 | 0.596896E+09 | 0.171381E+10 | 0.170179E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.498234E+09 | 0.231116E+09 | 0.267118E+09 | 0.353228E+09 | 0.170176E+10 |
February | 0.516617E+09 | 0.241550E+09 | 0.275067E+09 | 0.485985E+09 | 0.133634E+10 |
March | 0.843049E+09 | 0.407380E+09 | 0.435669E+09 | 0.986291E+09 | 0.100824E+10 |
April | 0.917821E+09 | 0.419991E+09 | 0.497830E+09 | 0.125107E+10 | 0.781546E+09 |
May | 0.953186E+09 | 0.361124E+09 | 0.592061E+09 | 0.147767E+10 | 0.503894E+09 |
June | 0.970064E+09 | 0.373179E+09 | 0.596885E+09 | 0.170638E+10 | 0.321112E+09 |
July | 0.945492E+09 | 0.350556E+09 | 0.594936E+09 | 0.171378E+10 | 0.246888E+09 |
August | 0.926447E+09 | 0.346455E+09 | 0.579993E+09 | 0.168769E+10 | 0.227839E+09 |
September | 0.730453E+09 | 0.304266E+09 | 0.426187E+09 | 0.116379E+10 | 0.408702E+09 |
October | 0.672438E+09 | 0.349069E+09 | 0.323369E+09 | 0.880818E+09 | 0.912381E+09 |
November | 0.519343E+09 | 0.233108E+09 | 0.286235E+09 | 0.524594E+09 | 0.121242E+10 |
December | 0.442736E+09 | 0.193653E+09 | 0.249083E+09 | 0.322185E+09 | 0.161735E+10 |
Annual Sum or Average | 0.893588E+10 | 0.381145E+10 | 0.512443E+10 | 0.125535E+11 | 0.102785E+11 |
Minimum of Months | 0.442736E+09 | 0.193653E+09 | 0.249083E+09 | 0.322185E+09 | 0.227839E+09 |
Maximum of Months | 0.970064E+09 | 0.419991E+09 | 0.596885E+09 | 0.171378E+10 | 0.170176E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.993954E+09 | 0.00 | 0.993954E+09 | 0.132010E+09 | 0.707592E+10 |
February | 0.995084E+09 | 0.00 | 0.995084E+09 | 0.407213E+09 | 0.525908E+10 |
March | 0.154673E+10 | 0.00 | 0.154673E+10 | 0.101667E+10 | 0.371131E+10 |
April | 0.181056E+10 | 8030357.15 | 0.180253E+10 | 0.197004E+10 | 0.283534E+10 |
May | 0.223758E+10 | 71411286.64 | 0.216617E+10 | 0.313343E+10 | 0.188778E+10 |
June | 0.238312E+10 | 0.157342E+09 | 0.222578E+10 | 0.439209E+10 | 0.114199E+10 |
July | 0.232342E+10 | 0.112943E+09 | 0.221048E+10 | 0.455737E+10 | 0.842242E+09 |
August | 0.206630E+10 | 22509151.83 | 0.204380E+10 | 0.416946E+10 | 0.694860E+09 |
September | 0.151155E+10 | 212783.61 | 0.151133E+10 | 0.228133E+10 | 0.155418E+10 |
October | 0.118759E+10 | 0.00 | 0.118759E+10 | 0.104177E+10 | 0.337748E+10 |
November | 0.102856E+10 | 0.00 | 0.102856E+10 | 0.507155E+09 | 0.447478E+10 |
December | 0.918837E+09 | 0.00 | 0.918837E+09 | 0.132250E+09 | 0.581729E+10 |
Annual Sum or Average | 0.190033E+11 | 0.372449E+09 | 0.186308E+11 | 0.237408E+11 | 0.386723E+11 |
Minimum of Months | 0.918837E+09 | 0.00 | 0.918837E+09 | 0.132010E+09 | 0.694860E+09 |
Maximum of Months | 0.238312E+10 | 0.157342E+09 | 0.222578E+10 | 0.455737E+10 | 0.707592E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.145522E+10 | 0.656378E+09 | 0.798842E+09 | 0.985514E+09 | 0.423248E+10 |
February | 0.165704E+10 | 0.890313E+09 | 0.766723E+09 | 0.157248E+10 | 0.316810E+10 |
March | 0.230811E+10 | 0.105072E+10 | 0.125739E+10 | 0.257030E+10 | 0.227684E+10 |
April | 0.270106E+10 | 0.123161E+10 | 0.146945E+10 | 0.370303E+10 | 0.178226E+10 |
May | 0.306484E+10 | 0.129607E+10 | 0.176876E+10 | 0.469303E+10 | 0.124447E+10 |
June | 0.307078E+10 | 0.128704E+10 | 0.178374E+10 | 0.540377E+10 | 0.767744E+09 |
July | 0.309394E+10 | 0.130073E+10 | 0.179320E+10 | 0.564561E+10 | 0.564806E+09 |
August | 0.282993E+10 | 0.112273E+10 | 0.170720E+10 | 0.526000E+10 | 0.464158E+09 |
September | 0.225079E+10 | 0.997266E+09 | 0.125352E+10 | 0.360948E+10 | 0.994950E+09 |
October | 0.198412E+10 | 0.103239E+10 | 0.951733E+09 | 0.252890E+10 | 0.208195E+10 |
November | 0.153515E+10 | 0.695109E+09 | 0.840039E+09 | 0.149218E+10 | 0.267003E+10 |
December | 0.137406E+10 | 0.626349E+09 | 0.747709E+09 | 0.100105E+10 | 0.346033E+10 |
Annual Sum or Average | 0.273250E+11 | 0.121867E+11 | 0.151383E+11 | 0.384653E+11 | 0.237081E+11 |
Minimum of Months | 0.137406E+10 | 0.626349E+09 | 0.747709E+09 | 0.985514E+09 | 0.464158E+09 |
Maximum of Months | 0.309394E+10 | 0.130073E+10 | 0.179320E+10 | 0.564561E+10 | 0.423248E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.531579E+10 | 0.370615E+10 | 0.160964E+10 | 0.588953E+10 | 0.609888E+10 |
February | 0.448128E+10 | 0.300392E+10 | 0.147735E+10 | 0.543398E+10 | 0.476984E+10 |
March | 0.446199E+10 | 0.232533E+10 | 0.213666E+10 | 0.587301E+10 | 0.372179E+10 |
April | 0.323393E+10 | 0.105271E+10 | 0.218122E+10 | 0.477846E+10 | 0.297198E+10 |
May | 0.269998E+10 | 0.313811E+09 | 0.238617E+10 | 0.426100E+10 | 0.201637E+10 |
June | 0.241589E+10 | 0.134435E+09 | 0.228145E+10 | 0.460800E+10 | 0.122079E+10 |
July | 0.252383E+10 | 0.188191E+09 | 0.233564E+10 | 0.507507E+10 | 0.880345E+09 |
August | 0.301327E+10 | 0.562890E+09 | 0.245038E+10 | 0.614598E+10 | 0.749294E+09 |
September | 0.320696E+10 | 0.119282E+10 | 0.201414E+10 | 0.550093E+10 | 0.163301E+10 |
October | 0.480415E+10 | 0.311213E+10 | 0.169202E+10 | 0.703049E+10 | 0.339332E+10 |
November | 0.500168E+10 | 0.331903E+10 | 0.168265E+10 | 0.651930E+10 | 0.427100E+10 |
December | 0.523990E+10 | 0.368631E+10 | 0.155359E+10 | 0.620586E+10 | 0.524180E+10 |
Annual Sum or Average | 0.463986E+11 | 0.225977E+11 | 0.238009E+11 | 0.673216E+11 | 0.369684E+11 |
Minimum of Months | 0.241589E+10 | 0.134435E+09 | 0.147735E+10 | 0.426100E+10 | 0.749294E+09 |
Maximum of Months | 0.531579E+10 | 0.370615E+10 | 0.245038E+10 | 0.703049E+10 | 0.609888E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149471E+10 | 0.693353E+09 | 0.801361E+09 | 0.114232E+10 | 0.450216E+10 |
February | 0.154986E+10 | 0.724655E+09 | 0.825209E+09 | 0.155914E+10 | 0.343143E+10 |
March | 0.252917E+10 | 0.122215E+10 | 0.130702E+10 | 0.308226E+10 | 0.254959E+10 |
April | 0.275349E+10 | 0.125998E+10 | 0.149350E+10 | 0.388218E+10 | 0.202480E+10 |
May | 0.285958E+10 | 0.108338E+10 | 0.177620E+10 | 0.446767E+10 | 0.140135E+10 |
June | 0.291021E+10 | 0.111955E+10 | 0.179067E+10 | 0.517115E+10 | 0.886336E+09 |
July | 0.283650E+10 | 0.105168E+10 | 0.178482E+10 | 0.523404E+10 | 0.650321E+09 |
August | 0.277936E+10 | 0.103937E+10 | 0.173999E+10 | 0.517755E+10 | 0.565316E+09 |
September | 0.219138E+10 | 0.912804E+09 | 0.127857E+10 | 0.353764E+10 | 0.110154E+10 |
October | 0.201733E+10 | 0.104722E+10 | 0.970115E+09 | 0.273435E+10 | 0.233311E+10 |
November | 0.155804E+10 | 0.699329E+09 | 0.858712E+09 | 0.172348E+10 | 0.300331E+10 |
December | 0.132822E+10 | 0.580965E+09 | 0.747255E+09 | 0.110283E+10 | 0.381896E+10 |
Annual Sum or Average | 0.268079E+11 | 0.114344E+11 | 0.153734E+11 | 0.388146E+11 | 0.262682E+11 |
Minimum of Months | 0.132822E+10 | 0.580965E+09 | 0.747255E+09 | 0.110283E+10 | 0.565316E+09 |
Maximum of Months | 0.291021E+10 | 0.125998E+10 | 0.179067E+10 | 0.523404E+10 | 0.450216E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.993954E+09 | 0.00 | 0.993954E+09 | 0.167648E+09 | 0.661158E+10 |
February | 0.995084E+09 | 0.00 | 0.995084E+09 | 0.449825E+09 | 0.492124E+10 |
March | 0.154673E+10 | 0.00 | 0.154673E+10 | 0.109930E+10 | 0.341367E+10 |
April | 0.181056E+10 | 8030357.15 | 0.180253E+10 | 0.202084E+10 | 0.268615E+10 |
May | 0.223758E+10 | 71411286.64 | 0.216617E+10 | 0.312401E+10 | 0.185036E+10 |
June | 0.238312E+10 | 0.157342E+09 | 0.222578E+10 | 0.434456E+10 | 0.115531E+10 |
July | 0.232342E+10 | 0.112943E+09 | 0.221048E+10 | 0.449804E+10 | 0.856812E+09 |
August | 0.206630E+10 | 22509151.83 | 0.204380E+10 | 0.411133E+10 | 0.713067E+09 |
September | 0.151155E+10 | 212783.61 | 0.151133E+10 | 0.228041E+10 | 0.149946E+10 |
October | 0.118759E+10 | 0.00 | 0.118759E+10 | 0.110974E+10 | 0.309717E+10 |
November | 0.102856E+10 | 0.00 | 0.102856E+10 | 0.608030E+09 | 0.405187E+10 |
December | 0.918837E+09 | 0.00 | 0.918837E+09 | 0.174979E+09 | 0.526941E+10 |
Annual Sum or Average | 0.190033E+11 | 0.372449E+09 | 0.186308E+11 | 0.239887E+11 | 0.361261E+11 |
Minimum of Months | 0.918837E+09 | 0.00 | 0.918837E+09 | 0.167648E+09 | 0.713067E+09 |
Maximum of Months | 0.238312E+10 | 0.157342E+09 | 0.222578E+10 | 0.449804E+10 | 0.661158E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.145522E+10 | 0.656378E+09 | 0.798842E+09 | 0.104319E+10 | 0.394561E+10 |
February | 0.165704E+10 | 0.890313E+09 | 0.766723E+09 | 0.162164E+10 | 0.297274E+10 |
March | 0.230811E+10 | 0.105072E+10 | 0.125739E+10 | 0.262754E+10 | 0.213653E+10 |
April | 0.270106E+10 | 0.123161E+10 | 0.146945E+10 | 0.372112E+10 | 0.172193E+10 |
May | 0.306484E+10 | 0.129607E+10 | 0.176876E+10 | 0.467022E+10 | 0.123932E+10 |
June | 0.307078E+10 | 0.128704E+10 | 0.178374E+10 | 0.536137E+10 | 0.784697E+09 |
July | 0.309394E+10 | 0.130073E+10 | 0.179320E+10 | 0.559493E+10 | 0.579127E+09 |
August | 0.282993E+10 | 0.112273E+10 | 0.170720E+10 | 0.521140E+10 | 0.480559E+09 |
September | 0.225079E+10 | 0.997266E+09 | 0.125352E+10 | 0.359527E+10 | 0.979416E+09 |
October | 0.198412E+10 | 0.103239E+10 | 0.951733E+09 | 0.256837E+10 | 0.195523E+10 |
November | 0.153515E+10 | 0.695109E+09 | 0.840039E+09 | 0.158121E+10 | 0.245362E+10 |
December | 0.137406E+10 | 0.626349E+09 | 0.747709E+09 | 0.106722E+10 | 0.314157E+10 |
Annual Sum or Average | 0.273250E+11 | 0.121867E+11 | 0.151383E+11 | 0.386635E+11 | 0.223903E+11 |
Minimum of Months | 0.137406E+10 | 0.626349E+09 | 0.747709E+09 | 0.104319E+10 | 0.480559E+09 |
Maximum of Months | 0.309394E+10 | 0.130073E+10 | 0.179320E+10 | 0.559493E+10 | 0.394561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.531579E+10 | 0.370615E+10 | 0.160964E+10 | 0.604666E+10 | 0.563950E+10 |
February | 0.448128E+10 | 0.300392E+10 | 0.147735E+10 | 0.552812E+10 | 0.445056E+10 |
March | 0.446199E+10 | 0.232533E+10 | 0.213666E+10 | 0.594468E+10 | 0.348209E+10 |
April | 0.323393E+10 | 0.105271E+10 | 0.218122E+10 | 0.480819E+10 | 0.284326E+10 |
May | 0.269998E+10 | 0.313811E+09 | 0.238617E+10 | 0.424084E+10 | 0.198215E+10 |
June | 0.241589E+10 | 0.134435E+09 | 0.228145E+10 | 0.455903E+10 | 0.123201E+10 |
July | 0.252383E+10 | 0.188191E+09 | 0.233564E+10 | 0.501399E+10 | 0.893670E+09 |
August | 0.301327E+10 | 0.562890E+09 | 0.245038E+10 | 0.608280E+10 | 0.770059E+09 |
September | 0.320696E+10 | 0.119282E+10 | 0.201414E+10 | 0.548443E+10 | 0.159639E+10 |
October | 0.480415E+10 | 0.311213E+10 | 0.169202E+10 | 0.707322E+10 | 0.318122E+10 |
November | 0.500168E+10 | 0.331903E+10 | 0.168265E+10 | 0.664663E+10 | 0.392663E+10 |
December | 0.523990E+10 | 0.368631E+10 | 0.155359E+10 | 0.636373E+10 | 0.474862E+10 |
Annual Sum or Average | 0.463986E+11 | 0.225977E+11 | 0.238009E+11 | 0.677923E+11 | 0.347462E+11 |
Minimum of Months | 0.241589E+10 | 0.134435E+09 | 0.147735E+10 | 0.424084E+10 | 0.770059E+09 |
Maximum of Months | 0.531579E+10 | 0.370615E+10 | 0.245038E+10 | 0.707322E+10 | 0.563950E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149471E+10 | 0.693353E+09 | 0.801361E+09 | 0.118463E+10 | 0.421038E+10 |
February | 0.154986E+10 | 0.724655E+09 | 0.825209E+09 | 0.158494E+10 | 0.324018E+10 |
March | 0.252917E+10 | 0.122215E+10 | 0.130702E+10 | 0.311421E+10 | 0.239690E+10 |
April | 0.275349E+10 | 0.125998E+10 | 0.149350E+10 | 0.389657E+10 | 0.194879E+10 |
May | 0.285958E+10 | 0.108338E+10 | 0.177620E+10 | 0.445265E+10 | 0.138278E+10 |
June | 0.291021E+10 | 0.111955E+10 | 0.179067E+10 | 0.513372E+10 | 0.893773E+09 |
July | 0.283650E+10 | 0.105168E+10 | 0.178482E+10 | 0.519421E+10 | 0.656873E+09 |
August | 0.277936E+10 | 0.103937E+10 | 0.173999E+10 | 0.513784E+10 | 0.575260E+09 |
September | 0.219138E+10 | 0.912804E+09 | 0.127857E+10 | 0.353031E+10 | 0.107632E+10 |
October | 0.201733E+10 | 0.104722E+10 | 0.970115E+09 | 0.275829E+10 | 0.219400E+10 |
November | 0.155804E+10 | 0.699329E+09 | 0.858712E+09 | 0.177663E+10 | 0.278433E+10 |
December | 0.132822E+10 | 0.580965E+09 | 0.747255E+09 | 0.114277E+10 | 0.351497E+10 |
Annual Sum or Average | 0.268079E+11 | 0.114344E+11 | 0.153734E+11 | 0.389068E+11 | 0.248746E+11 |
Minimum of Months | 0.132822E+10 | 0.580965E+09 | 0.747255E+09 | 0.114277E+10 | 0.575260E+09 |
Maximum of Months | 0.291021E+10 | 0.125998E+10 | 0.179067E+10 | 0.519421E+10 | 0.421038E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 33.00 | 2971.75 | 371.09 | 0.00 | 371.09 | 0.00 | 0.00 |
February | 135.23 | 2449.72 | 411.32 | 0.00 | 411.32 | 0.00 | 0.00 |
March | 336.54 | 1547.88 | 577.47 | 0.00 | 577.47 | 0.00 | 0.00 |
April | 725.99 | 1172.60 | 698.51 | 3.10 | 695.41 | 0.00 | 0.00 |
May | 1160.18 | 730.81 | 835.40 | 26.66 | 808.74 | 0.00 | 0.00 |
June | 1685.63 | 441.41 | 919.40 | 60.70 | 858.70 | 0.00 | 0.00 |
July | 1689.98 | 310.53 | 867.45 | 42.17 | 825.28 | 0.00 | 0.00 |
August | 1539.59 | 253.82 | 771.46 | 8.40 | 763.05 | 0.00 | 0.00 |
September | 865.63 | 633.75 | 583.15 | 0.08 | 583.07 | 0.00 | 0.00 |
October | 352.20 | 1410.22 | 443.39 | 0.00 | 443.39 | 0.00 | 0.00 |
November | 145.52 | 1969.46 | 396.82 | 0.00 | 396.82 | 0.00 | 0.00 |
December | 26.98 | 2566.74 | 343.05 | 0.00 | 343.05 | 0.00 | 0.00 |
Annual Sum or Average | 728.11 | 1366.17 | 602.58 | 11.81 | 590.77 | 0.00 | 0.00 |
Minimum of Months | 26.98 | 253.82 | 343.05 | 0.00 | 343.05 | 0.00 | 0.00 |
Maximum of Months | 1689.98 | 2971.75 | 919.40 | 60.70 | 858.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 342.69 | 1756.22 | 543.32 | 245.06 | 298.25 | 0.00 | 0.00 |
February | 627.06 | 1437.07 | 684.95 | 368.02 | 316.93 | 0.00 | 0.00 |
March | 948.48 | 906.26 | 861.75 | 392.29 | 469.46 | 0.00 | 0.00 |
April | 1434.88 | 696.28 | 1042.08 | 475.16 | 566.92 | 0.00 | 0.00 |
May | 1765.01 | 470.62 | 1144.28 | 483.90 | 660.38 | 0.00 | 0.00 |
June | 2101.05 | 280.27 | 1184.72 | 496.54 | 688.17 | 0.00 | 0.00 |
July | 2126.17 | 187.48 | 1155.15 | 485.64 | 669.51 | 0.00 | 0.00 |
August | 1981.69 | 141.04 | 1056.58 | 419.18 | 637.40 | 0.00 | 0.00 |
September | 1396.39 | 393.60 | 868.36 | 384.75 | 483.61 | 0.00 | 0.00 |
October | 933.39 | 837.23 | 740.79 | 385.45 | 355.34 | 0.00 | 0.00 |
November | 542.50 | 1133.06 | 592.27 | 268.18 | 324.09 | 0.00 | 0.00 |
December | 344.62 | 1465.79 | 513.02 | 233.85 | 279.16 | 0.00 | 0.00 |
Annual Sum or Average | 1215.09 | 805.58 | 866.47 | 386.44 | 480.03 | 0.00 | 0.00 |
Minimum of Months | 342.69 | 141.04 | 513.02 | 233.85 | 279.16 | 0.00 | 0.00 |
Maximum of Months | 2126.17 | 1756.22 | 1184.72 | 496.54 | 688.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2192.03 | 2392.77 | 1984.63 | 1383.67 | 600.96 | 0.00 | 0.00 |
February | 2243.48 | 2078.28 | 1852.32 | 1241.66 | 610.66 | 0.00 | 0.00 |
March | 2202.51 | 1447.54 | 1665.87 | 868.15 | 797.72 | 0.00 | 0.00 |
April | 1846.03 | 1179.47 | 1247.63 | 406.13 | 841.50 | 0.00 | 0.00 |
May | 1593.32 | 769.68 | 1008.04 | 117.16 | 890.88 | 0.00 | 0.00 |
June | 1771.52 | 470.19 | 932.04 | 51.86 | 880.17 | 0.00 | 0.00 |
July | 1886.42 | 321.32 | 942.27 | 70.26 | 872.01 | 0.00 | 0.00 |
August | 2289.61 | 266.65 | 1125.00 | 210.15 | 914.85 | 0.00 | 0.00 |
September | 2129.71 | 642.20 | 1237.22 | 460.18 | 777.04 | 0.00 | 0.00 |
October | 2638.15 | 1315.78 | 1793.61 | 1161.90 | 631.71 | 0.00 | 0.00 |
November | 2515.14 | 1725.50 | 1929.60 | 1280.45 | 649.15 | 0.00 | 0.00 |
December | 2303.06 | 2101.78 | 1956.29 | 1376.26 | 580.03 | 0.00 | 0.00 |
Annual Sum or Average | 2134.10 | 1221.35 | 1471.25 | 716.55 | 754.71 | 0.00 | 0.00 |
Minimum of Months | 1593.32 | 266.65 | 932.04 | 51.86 | 580.03 | 0.00 | 0.00 |
Maximum of Months | 2638.15 | 2392.77 | 1984.63 | 1383.67 | 914.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 395.65 | 1906.11 | 558.06 | 258.87 | 299.19 | 0.00 | 0.00 |
February | 602.67 | 1657.18 | 640.65 | 299.54 | 341.11 | 0.00 | 0.00 |
March | 1104.73 | 1129.32 | 944.29 | 456.30 | 487.99 | 0.00 | 0.00 |
April | 1448.01 | 904.58 | 1062.31 | 486.11 | 576.20 | 0.00 | 0.00 |
May | 1655.12 | 564.40 | 1067.65 | 404.49 | 663.16 | 0.00 | 0.00 |
June | 1975.00 | 371.66 | 1122.77 | 431.93 | 690.85 | 0.00 | 0.00 |
July | 1919.58 | 276.54 | 1059.03 | 392.65 | 666.38 | 0.00 | 0.00 |
August | 1890.36 | 255.20 | 1037.70 | 388.06 | 649.64 | 0.00 | 0.00 |
September | 1346.99 | 473.04 | 845.44 | 352.16 | 493.28 | 0.00 | 0.00 |
October | 986.59 | 1021.94 | 753.19 | 390.99 | 362.20 | 0.00 | 0.00 |
November | 607.18 | 1403.28 | 601.10 | 269.80 | 331.29 | 0.00 | 0.00 |
December | 360.87 | 1811.58 | 495.90 | 216.91 | 278.99 | 0.00 | 0.00 |
Annual Sum or Average | 1194.22 | 977.80 | 850.08 | 362.59 | 487.49 | 0.00 | 0.00 |
Minimum of Months | 360.87 | 255.20 | 495.90 | 216.91 | 278.99 | 0.00 | 0.00 |
Maximum of Months | 1975.00 | 1906.11 | 1122.77 | 486.11 | 690.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 49.29 | 2641.84 | 371.10 | 0.00 | 371.10 | 0.00 | 0.00 |
February | 168.33 | 2173.89 | 411.33 | 0.00 | 411.33 | 0.00 | 0.00 |
March | 379.58 | 1385.65 | 577.48 | 0.00 | 577.48 | 0.00 | 0.00 |
April | 760.05 | 1093.88 | 698.52 | 3.10 | 695.42 | 0.00 | 0.00 |
May | 1169.89 | 704.82 | 835.42 | 26.66 | 808.75 | 0.00 | 0.00 |
June | 1694.48 | 440.58 | 919.41 | 60.70 | 858.71 | 0.00 | 0.00 |
July | 1701.53 | 314.46 | 867.47 | 42.17 | 825.30 | 0.00 | 0.00 |
August | 1556.70 | 259.43 | 771.47 | 8.40 | 763.07 | 0.00 | 0.00 |
September | 880.14 | 599.61 | 583.16 | 0.08 | 583.08 | 0.00 | 0.00 |
October | 388.95 | 1261.01 | 443.39 | 0.00 | 443.39 | 0.00 | 0.00 |
November | 195.66 | 1726.38 | 396.82 | 0.00 | 396.82 | 0.00 | 0.00 |
December | 49.38 | 2171.93 | 343.05 | 0.00 | 343.05 | 0.00 | 0.00 |
Annual Sum or Average | 752.82 | 1226.29 | 602.59 | 11.81 | 590.78 | 0.00 | 0.00 |
Minimum of Months | 49.29 | 259.43 | 343.05 | 0.00 | 343.05 | 0.00 | 0.00 |
Maximum of Months | 1701.53 | 2641.84 | 919.41 | 60.70 | 858.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 367.95 | 1580.23 | 543.32 | 245.06 | 298.25 | 0.00 | 0.00 |
February | 650.00 | 1309.56 | 684.95 | 368.02 | 316.93 | 0.00 | 0.00 |
March | 959.64 | 850.08 | 861.75 | 392.29 | 469.46 | 0.00 | 0.00 |
April | 1428.64 | 687.60 | 1042.08 | 475.16 | 566.92 | 0.00 | 0.00 |
May | 1752.18 | 464.63 | 1144.28 | 483.90 | 660.38 | 0.00 | 0.00 |
June | 2084.79 | 296.20 | 1184.71 | 496.54 | 688.17 | 0.00 | 0.00 |
July | 2107.83 | 210.87 | 1155.14 | 485.64 | 669.50 | 0.00 | 0.00 |
August | 1963.86 | 173.30 | 1056.57 | 419.18 | 637.39 | 0.00 | 0.00 |
September | 1392.54 | 383.85 | 868.36 | 384.75 | 483.61 | 0.00 | 0.00 |
October | 944.18 | 777.31 | 740.78 | 385.45 | 355.34 | 0.00 | 0.00 |
November | 575.69 | 1030.10 | 592.26 | 268.17 | 324.09 | 0.00 | 0.00 |
December | 373.75 | 1291.94 | 513.01 | 233.85 | 279.16 | 0.00 | 0.00 |
Annual Sum or Average | 1219.73 | 751.78 | 866.47 | 386.44 | 480.03 | 0.00 | 0.00 |
Minimum of Months | 367.95 | 173.30 | 513.01 | 233.85 | 279.16 | 0.00 | 0.00 |
Maximum of Months | 2107.83 | 1580.23 | 1184.71 | 496.54 | 688.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2198.90 | 2277.06 | 1984.69 | 1383.72 | 600.97 | 0.00 | 0.00 |
February | 2246.19 | 1971.66 | 1852.38 | 1241.70 | 610.68 | 0.00 | 0.00 |
March | 2192.73 | 1389.56 | 1665.92 | 868.18 | 797.74 | 0.00 | 0.00 |
April | 1843.54 | 1146.60 | 1247.66 | 406.14 | 841.52 | 0.00 | 0.00 |
May | 1590.88 | 752.83 | 1008.06 | 117.16 | 890.89 | 0.00 | 0.00 |
June | 1777.78 | 470.98 | 932.06 | 51.87 | 880.19 | 0.00 | 0.00 |
July | 1894.82 | 328.68 | 942.29 | 70.26 | 872.03 | 0.00 | 0.00 |
August | 2294.65 | 279.75 | 1125.03 | 210.16 | 914.87 | 0.00 | 0.00 |
September | 2122.27 | 630.02 | 1237.25 | 460.19 | 777.06 | 0.00 | 0.00 |
October | 2624.88 | 1266.92 | 1793.66 | 1161.94 | 631.73 | 0.00 | 0.00 |
November | 2515.16 | 1647.76 | 1929.66 | 1280.49 | 649.17 | 0.00 | 0.00 |
December | 2317.00 | 1957.06 | 1956.35 | 1376.31 | 580.04 | 0.00 | 0.00 |
Annual Sum or Average | 2134.75 | 1172.26 | 1471.29 | 716.57 | 754.72 | 0.00 | 0.00 |
Minimum of Months | 1590.88 | 279.75 | 932.06 | 51.87 | 580.04 | 0.00 | 0.00 |
Maximum of Months | 2624.88 | 2277.06 | 1984.69 | 1383.72 | 914.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 426.49 | 1680.91 | 558.06 | 258.87 | 299.19 | 0.00 | 0.00 |
February | 644.49 | 1418.42 | 640.65 | 299.54 | 341.11 | 0.00 | 0.00 |
March | 1150.78 | 951.91 | 944.28 | 456.30 | 487.98 | 0.00 | 0.00 |
April | 1497.76 | 781.17 | 1062.30 | 486.10 | 576.20 | 0.00 | 0.00 |
May | 1668.04 | 523.20 | 1067.64 | 404.49 | 663.16 | 0.00 | 0.00 |
June | 1995.04 | 341.95 | 1122.77 | 431.92 | 690.84 | 0.00 | 0.00 |
July | 1954.17 | 242.80 | 1059.03 | 392.65 | 666.38 | 0.00 | 0.00 |
August | 1933.07 | 211.06 | 1037.70 | 388.06 | 649.64 | 0.00 | 0.00 |
September | 1364.83 | 424.98 | 845.44 | 352.16 | 493.28 | 0.00 | 0.00 |
October | 1020.89 | 871.08 | 753.19 | 390.99 | 362.20 | 0.00 | 0.00 |
November | 664.92 | 1158.68 | 601.10 | 269.80 | 331.29 | 0.00 | 0.00 |
December | 411.75 | 1425.84 | 495.90 | 216.91 | 278.99 | 0.00 | 0.00 |
Annual Sum or Average | 1230.80 | 832.96 | 850.07 | 362.58 | 487.49 | 0.00 | 0.00 |
Minimum of Months | 411.75 | 211.06 | 495.90 | 216.91 | 278.99 | 0.00 | 0.00 |
Maximum of Months | 1995.04 | 1680.91 | 1122.77 | 486.10 | 690.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 62.59 | 2468.48 | 371.10 | 0.00 | 371.10 | 0.00 | 0.00 |
February | 185.94 | 2034.24 | 411.33 | 0.00 | 411.33 | 0.00 | 0.00 |
March | 410.43 | 1274.52 | 577.48 | 0.00 | 577.48 | 0.00 | 0.00 |
April | 779.65 | 1036.32 | 698.52 | 3.10 | 695.42 | 0.00 | 0.00 |
May | 1166.37 | 690.85 | 835.42 | 26.66 | 808.75 | 0.00 | 0.00 |
June | 1676.14 | 445.72 | 919.41 | 60.70 | 858.71 | 0.00 | 0.00 |
July | 1679.37 | 319.90 | 867.47 | 42.17 | 825.30 | 0.00 | 0.00 |
August | 1534.99 | 266.23 | 771.47 | 8.40 | 763.07 | 0.00 | 0.00 |
September | 879.79 | 578.50 | 583.16 | 0.08 | 583.08 | 0.00 | 0.00 |
October | 414.33 | 1156.35 | 443.39 | 0.00 | 443.39 | 0.00 | 0.00 |
November | 234.58 | 1563.22 | 396.82 | 0.00 | 396.82 | 0.00 | 0.00 |
December | 65.33 | 1967.37 | 343.05 | 0.00 | 343.05 | 0.00 | 0.00 |
Annual Sum or Average | 760.68 | 1145.55 | 602.59 | 11.81 | 590.78 | 0.00 | 0.00 |
Minimum of Months | 62.59 | 266.23 | 343.05 | 0.00 | 343.05 | 0.00 | 0.00 |
Maximum of Months | 1679.37 | 2468.48 | 919.41 | 60.70 | 858.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 389.48 | 1473.12 | 543.32 | 245.06 | 298.25 | 0.00 | 0.00 |
February | 670.32 | 1228.81 | 684.95 | 368.02 | 316.93 | 0.00 | 0.00 |
March | 981.01 | 797.69 | 861.75 | 392.29 | 469.46 | 0.00 | 0.00 |
April | 1435.62 | 664.33 | 1042.08 | 475.16 | 566.92 | 0.00 | 0.00 |
May | 1743.66 | 462.71 | 1144.28 | 483.90 | 660.38 | 0.00 | 0.00 |
June | 2068.43 | 302.74 | 1184.71 | 496.54 | 688.17 | 0.00 | 0.00 |
July | 2088.91 | 216.22 | 1155.14 | 485.64 | 669.50 | 0.00 | 0.00 |
August | 1945.71 | 179.42 | 1056.57 | 419.18 | 637.39 | 0.00 | 0.00 |
September | 1387.06 | 377.86 | 868.36 | 384.75 | 483.61 | 0.00 | 0.00 |
October | 958.92 | 730.00 | 740.78 | 385.45 | 355.34 | 0.00 | 0.00 |
November | 610.04 | 946.61 | 592.26 | 268.17 | 324.09 | 0.00 | 0.00 |
December | 398.45 | 1172.93 | 513.01 | 233.85 | 279.16 | 0.00 | 0.00 |
Annual Sum or Average | 1226.01 | 709.99 | 866.47 | 386.44 | 480.03 | 0.00 | 0.00 |
Minimum of Months | 389.48 | 179.42 | 513.01 | 233.85 | 279.16 | 0.00 | 0.00 |
Maximum of Months | 2088.91 | 1473.12 | 1184.71 | 496.54 | 688.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2257.56 | 2105.55 | 1984.69 | 1383.72 | 600.97 | 0.00 | 0.00 |
February | 2285.10 | 1839.68 | 1852.38 | 1241.70 | 610.68 | 0.00 | 0.00 |
March | 2219.49 | 1300.06 | 1665.92 | 868.18 | 797.74 | 0.00 | 0.00 |
April | 1855.01 | 1096.94 | 1247.66 | 406.14 | 841.52 | 0.00 | 0.00 |
May | 1583.35 | 740.05 | 1008.06 | 117.16 | 890.89 | 0.00 | 0.00 |
June | 1758.89 | 475.31 | 932.06 | 51.87 | 880.19 | 0.00 | 0.00 |
July | 1872.01 | 333.66 | 942.29 | 70.26 | 872.03 | 0.00 | 0.00 |
August | 2271.06 | 287.51 | 1125.03 | 210.16 | 914.87 | 0.00 | 0.00 |
September | 2115.91 | 615.89 | 1237.25 | 460.19 | 777.06 | 0.00 | 0.00 |
October | 2640.84 | 1187.73 | 1793.66 | 1161.94 | 631.73 | 0.00 | 0.00 |
November | 2564.29 | 1514.90 | 1929.66 | 1280.49 | 649.17 | 0.00 | 0.00 |
December | 2375.94 | 1772.93 | 1956.35 | 1376.31 | 580.04 | 0.00 | 0.00 |
Annual Sum or Average | 2149.68 | 1101.79 | 1471.29 | 716.57 | 754.72 | 0.00 | 0.00 |
Minimum of Months | 1583.35 | 287.51 | 932.06 | 51.87 | 580.04 | 0.00 | 0.00 |
Maximum of Months | 2640.84 | 2105.55 | 1984.69 | 1383.72 | 914.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 442.29 | 1571.98 | 558.06 | 258.87 | 299.19 | 0.00 | 0.00 |
February | 655.15 | 1339.36 | 640.65 | 299.54 | 341.11 | 0.00 | 0.00 |
March | 1162.71 | 894.90 | 944.28 | 456.30 | 487.98 | 0.00 | 0.00 |
April | 1503.30 | 751.85 | 1062.30 | 486.10 | 576.20 | 0.00 | 0.00 |
May | 1662.43 | 516.27 | 1067.64 | 404.49 | 663.16 | 0.00 | 0.00 |
June | 1980.60 | 344.82 | 1122.77 | 431.92 | 690.84 | 0.00 | 0.00 |
July | 1939.30 | 245.25 | 1059.03 | 392.65 | 666.38 | 0.00 | 0.00 |
August | 1918.25 | 214.78 | 1037.70 | 388.06 | 649.64 | 0.00 | 0.00 |
September | 1362.00 | 415.25 | 845.44 | 352.16 | 493.28 | 0.00 | 0.00 |
October | 1029.83 | 819.15 | 753.19 | 390.99 | 362.20 | 0.00 | 0.00 |
November | 685.43 | 1074.20 | 601.10 | 269.80 | 331.29 | 0.00 | 0.00 |
December | 426.66 | 1312.34 | 495.90 | 216.91 | 278.99 | 0.00 | 0.00 |
Annual Sum or Average | 1233.73 | 788.77 | 850.07 | 362.58 | 487.49 | 0.00 | 0.00 |
Minimum of Months | 426.66 | 214.78 | 495.90 | 216.91 | 278.99 | 0.00 | 0.00 |
Maximum of Months | 1980.60 | 1571.98 | 1122.77 | 486.10 | 690.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 88389023.41 | 0.795953E+10 | 0.993936E+09 | 0.00 | 0.993936E+09 | 0.00 | 0.00 |
February | 0.327150E+09 | 0.592636E+10 | 0.995068E+09 | 0.00 | 0.995068E+09 | 0.00 | 0.00 |
March | 0.901385E+09 | 0.414585E+10 | 0.154670E+10 | 0.00 | 0.154670E+10 | 0.00 | 0.00 |
April | 0.188176E+10 | 0.303937E+10 | 0.181053E+10 | 8030117.67 | 0.180250E+10 | 0.00 | 0.00 |
May | 0.310743E+10 | 0.195740E+10 | 0.223754E+10 | 71409157.01 | 0.216613E+10 | 0.00 | 0.00 |
June | 0.436916E+10 | 0.114412E+10 | 0.238307E+10 | 0.157337E+09 | 0.222574E+10 | 0.00 | 0.00 |
July | 0.452644E+10 | 0.831730E+09 | 0.232338E+10 | 0.112940E+09 | 0.221044E+10 | 0.00 | 0.00 |
August | 0.412364E+10 | 0.679830E+09 | 0.206627E+10 | 22508480.56 | 0.204376E+10 | 0.00 | 0.00 |
September | 0.224370E+10 | 0.164267E+10 | 0.151152E+10 | 212777.26 | 0.151131E+10 | 0.00 | 0.00 |
October | 0.943325E+09 | 0.377713E+10 | 0.118757E+10 | 0.00 | 0.118757E+10 | 0.00 | 0.00 |
November | 0.377176E+09 | 0.510485E+10 | 0.102854E+10 | 0.00 | 0.102854E+10 | 0.00 | 0.00 |
December | 72263200.22 | 0.687475E+10 | 0.918820E+09 | 0.00 | 0.918820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.229618E+11 | 0.430836E+11 | 0.190030E+11 | 0.372438E+09 | 0.186305E+11 | 0.00 | 0.00 |
Minimum of Months | 72263200.22 | 0.679830E+09 | 0.918820E+09 | 0.00 | 0.918820E+09 | 0.00 | 0.00 |
Maximum of Months | 0.452644E+10 | 0.795953E+10 | 0.238307E+10 | 0.157337E+09 | 0.222574E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.917857E+09 | 0.470387E+10 | 0.145523E+10 | 0.656381E+09 | 0.798846E+09 | 0.00 | 0.00 |
February | 0.151698E+10 | 0.347656E+10 | 0.165704E+10 | 0.890317E+09 | 0.766726E+09 | 0.00 | 0.00 |
March | 0.254042E+10 | 0.242732E+10 | 0.230812E+10 | 0.105072E+10 | 0.125740E+10 | 0.00 | 0.00 |
April | 0.371922E+10 | 0.180477E+10 | 0.270108E+10 | 0.123162E+10 | 0.146946E+10 | 0.00 | 0.00 |
May | 0.472739E+10 | 0.126050E+10 | 0.306485E+10 | 0.129608E+10 | 0.176877E+10 | 0.00 | 0.00 |
June | 0.544593E+10 | 0.726465E+09 | 0.307079E+10 | 0.128704E+10 | 0.178375E+10 | 0.00 | 0.00 |
July | 0.569474E+10 | 0.502149E+09 | 0.309395E+10 | 0.130074E+10 | 0.179321E+10 | 0.00 | 0.00 |
August | 0.530777E+10 | 0.377757E+09 | 0.282994E+10 | 0.112274E+10 | 0.170720E+10 | 0.00 | 0.00 |
September | 0.361943E+10 | 0.102020E+10 | 0.225080E+10 | 0.997270E+09 | 0.125353E+10 | 0.00 | 0.00 |
October | 0.249999E+10 | 0.224244E+10 | 0.198413E+10 | 0.103239E+10 | 0.951737E+09 | 0.00 | 0.00 |
November | 0.140616E+10 | 0.293690E+10 | 0.153515E+10 | 0.695112E+09 | 0.840042E+09 | 0.00 | 0.00 |
December | 0.923034E+09 | 0.392597E+10 | 0.137406E+10 | 0.626351E+09 | 0.747712E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.383189E+11 | 0.254049E+11 | 0.273251E+11 | 0.121868E+11 | 0.151384E+11 | 0.00 | 0.00 |
Minimum of Months | 0.917857E+09 | 0.377757E+09 | 0.137406E+10 | 0.626351E+09 | 0.747712E+09 | 0.00 | 0.00 |
Maximum of Months | 0.569474E+10 | 0.470387E+10 | 0.309395E+10 | 0.130074E+10 | 0.179321E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.587112E+10 | 0.640880E+10 | 0.531563E+10 | 0.370603E+10 | 0.160960E+10 | 0.00 | 0.00 |
February | 0.542743E+10 | 0.502778E+10 | 0.448114E+10 | 0.300382E+10 | 0.147732E+10 | 0.00 | 0.00 |
March | 0.589921E+10 | 0.387708E+10 | 0.446186E+10 | 0.232525E+10 | 0.213662E+10 | 0.00 | 0.00 |
April | 0.478492E+10 | 0.305719E+10 | 0.323385E+10 | 0.105268E+10 | 0.218117E+10 | 0.00 | 0.00 |
May | 0.426754E+10 | 0.206152E+10 | 0.269992E+10 | 0.313801E+09 | 0.238612E+10 | 0.00 | 0.00 |
June | 0.459177E+10 | 0.121873E+10 | 0.241584E+10 | 0.134430E+09 | 0.228141E+10 | 0.00 | 0.00 |
July | 0.505259E+10 | 0.860626E+09 | 0.252378E+10 | 0.188185E+09 | 0.233559E+10 | 0.00 | 0.00 |
August | 0.613249E+10 | 0.714197E+09 | 0.301320E+10 | 0.562872E+09 | 0.245033E+10 | 0.00 | 0.00 |
September | 0.552020E+10 | 0.166458E+10 | 0.320688E+10 | 0.119278E+10 | 0.201409E+10 | 0.00 | 0.00 |
October | 0.706602E+10 | 0.352417E+10 | 0.480401E+10 | 0.311203E+10 | 0.169198E+10 | 0.00 | 0.00 |
November | 0.651925E+10 | 0.447249E+10 | 0.500153E+10 | 0.331892E+10 | 0.168261E+10 | 0.00 | 0.00 |
December | 0.616851E+10 | 0.562940E+10 | 0.523974E+10 | 0.368619E+10 | 0.155355E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.673011E+11 | 0.385166E+11 | 0.463974E+11 | 0.225970E+11 | 0.238004E+11 | 0.00 | 0.00 |
Minimum of Months | 0.426754E+10 | 0.714197E+09 | 0.241584E+10 | 0.134430E+09 | 0.147732E+10 | 0.00 | 0.00 |
Maximum of Months | 0.706602E+10 | 0.640880E+10 | 0.531563E+10 | 0.370603E+10 | 0.245033E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105970E+10 | 0.510533E+10 | 0.149472E+10 | 0.693356E+09 | 0.801364E+09 | 0.00 | 0.00 |
February | 0.145797E+10 | 0.400906E+10 | 0.154987E+10 | 0.724658E+09 | 0.825212E+09 | 0.00 | 0.00 |
March | 0.295891E+10 | 0.302477E+10 | 0.252918E+10 | 0.122216E+10 | 0.130702E+10 | 0.00 | 0.00 |
April | 0.375324E+10 | 0.234467E+10 | 0.275350E+10 | 0.125999E+10 | 0.149351E+10 | 0.00 | 0.00 |
May | 0.443307E+10 | 0.151170E+10 | 0.285959E+10 | 0.108339E+10 | 0.177621E+10 | 0.00 | 0.00 |
June | 0.511920E+10 | 0.963348E+09 | 0.291023E+10 | 0.111955E+10 | 0.179068E+10 | 0.00 | 0.00 |
July | 0.514141E+10 | 0.740672E+09 | 0.283651E+10 | 0.105168E+10 | 0.178483E+10 | 0.00 | 0.00 |
August | 0.506313E+10 | 0.683526E+09 | 0.277938E+10 | 0.103938E+10 | 0.174000E+10 | 0.00 | 0.00 |
September | 0.349141E+10 | 0.122612E+10 | 0.219139E+10 | 0.912808E+09 | 0.127858E+10 | 0.00 | 0.00 |
October | 0.264249E+10 | 0.273718E+10 | 0.201734E+10 | 0.104722E+10 | 0.970119E+09 | 0.00 | 0.00 |
November | 0.157380E+10 | 0.363731E+10 | 0.155805E+10 | 0.699332E+09 | 0.858716E+09 | 0.00 | 0.00 |
December | 0.966566E+09 | 0.485212E+10 | 0.132823E+10 | 0.580967E+09 | 0.747258E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.376609E+11 | 0.308358E+11 | 0.268080E+11 | 0.114345E+11 | 0.153735E+11 | 0.00 | 0.00 |
Minimum of Months | 0.966566E+09 | 0.683526E+09 | 0.132823E+10 | 0.580967E+09 | 0.747258E+09 | 0.00 | 0.00 |
Maximum of Months | 0.514141E+10 | 0.510533E+10 | 0.291023E+10 | 0.125999E+10 | 0.179068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.132010E+09 | 0.707592E+10 | 0.993954E+09 | 0.00 | 0.993954E+09 | 0.00 | 0.00 |
February | 0.407213E+09 | 0.525908E+10 | 0.995084E+09 | 0.00 | 0.995084E+09 | 0.00 | 0.00 |
March | 0.101667E+10 | 0.371131E+10 | 0.154673E+10 | 0.00 | 0.154673E+10 | 0.00 | 0.00 |
April | 0.197004E+10 | 0.283534E+10 | 0.181056E+10 | 8030357.15 | 0.180253E+10 | 0.00 | 0.00 |
May | 0.313343E+10 | 0.188778E+10 | 0.223758E+10 | 71411286.64 | 0.216617E+10 | 0.00 | 0.00 |
June | 0.439209E+10 | 0.114199E+10 | 0.238312E+10 | 0.157342E+09 | 0.222578E+10 | 0.00 | 0.00 |
July | 0.455737E+10 | 0.842242E+09 | 0.232342E+10 | 0.112943E+09 | 0.221048E+10 | 0.00 | 0.00 |
August | 0.416946E+10 | 0.694860E+09 | 0.206630E+10 | 22509151.83 | 0.204380E+10 | 0.00 | 0.00 |
September | 0.228133E+10 | 0.155418E+10 | 0.151155E+10 | 212783.61 | 0.151133E+10 | 0.00 | 0.00 |
October | 0.104177E+10 | 0.337748E+10 | 0.118759E+10 | 0.00 | 0.118759E+10 | 0.00 | 0.00 |
November | 0.507155E+09 | 0.447478E+10 | 0.102856E+10 | 0.00 | 0.102856E+10 | 0.00 | 0.00 |
December | 0.132250E+09 | 0.581729E+10 | 0.918837E+09 | 0.00 | 0.918837E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.237408E+11 | 0.386723E+11 | 0.190033E+11 | 0.372449E+09 | 0.186308E+11 | 0.00 | 0.00 |
Minimum of Months | 0.132010E+09 | 0.694860E+09 | 0.918837E+09 | 0.00 | 0.918837E+09 | 0.00 | 0.00 |
Maximum of Months | 0.455737E+10 | 0.707592E+10 | 0.238312E+10 | 0.157342E+09 | 0.222578E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.985514E+09 | 0.423248E+10 | 0.145522E+10 | 0.656378E+09 | 0.798842E+09 | 0.00 | 0.00 |
February | 0.157248E+10 | 0.316810E+10 | 0.165704E+10 | 0.890313E+09 | 0.766723E+09 | 0.00 | 0.00 |
March | 0.257030E+10 | 0.227684E+10 | 0.230811E+10 | 0.105072E+10 | 0.125739E+10 | 0.00 | 0.00 |
April | 0.370303E+10 | 0.178226E+10 | 0.270106E+10 | 0.123161E+10 | 0.146945E+10 | 0.00 | 0.00 |
May | 0.469303E+10 | 0.124447E+10 | 0.306484E+10 | 0.129607E+10 | 0.176876E+10 | 0.00 | 0.00 |
June | 0.540377E+10 | 0.767744E+09 | 0.307078E+10 | 0.128704E+10 | 0.178374E+10 | 0.00 | 0.00 |
July | 0.564561E+10 | 0.564806E+09 | 0.309394E+10 | 0.130073E+10 | 0.179320E+10 | 0.00 | 0.00 |
August | 0.526000E+10 | 0.464158E+09 | 0.282993E+10 | 0.112273E+10 | 0.170720E+10 | 0.00 | 0.00 |
September | 0.360948E+10 | 0.994950E+09 | 0.225079E+10 | 0.997266E+09 | 0.125352E+10 | 0.00 | 0.00 |
October | 0.252890E+10 | 0.208195E+10 | 0.198412E+10 | 0.103239E+10 | 0.951733E+09 | 0.00 | 0.00 |
November | 0.149218E+10 | 0.267003E+10 | 0.153515E+10 | 0.695109E+09 | 0.840039E+09 | 0.00 | 0.00 |
December | 0.100105E+10 | 0.346033E+10 | 0.137406E+10 | 0.626349E+09 | 0.747709E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.384653E+11 | 0.237081E+11 | 0.273250E+11 | 0.121867E+11 | 0.151383E+11 | 0.00 | 0.00 |
Minimum of Months | 0.985514E+09 | 0.464158E+09 | 0.137406E+10 | 0.626349E+09 | 0.747709E+09 | 0.00 | 0.00 |
Maximum of Months | 0.564561E+10 | 0.423248E+10 | 0.309394E+10 | 0.130073E+10 | 0.179320E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.588953E+10 | 0.609888E+10 | 0.531579E+10 | 0.370615E+10 | 0.160964E+10 | 0.00 | 0.00 |
February | 0.543398E+10 | 0.476984E+10 | 0.448128E+10 | 0.300392E+10 | 0.147735E+10 | 0.00 | 0.00 |
March | 0.587301E+10 | 0.372179E+10 | 0.446199E+10 | 0.232533E+10 | 0.213666E+10 | 0.00 | 0.00 |
April | 0.477846E+10 | 0.297198E+10 | 0.323393E+10 | 0.105271E+10 | 0.218122E+10 | 0.00 | 0.00 |
May | 0.426100E+10 | 0.201637E+10 | 0.269998E+10 | 0.313811E+09 | 0.238617E+10 | 0.00 | 0.00 |
June | 0.460800E+10 | 0.122079E+10 | 0.241589E+10 | 0.134435E+09 | 0.228145E+10 | 0.00 | 0.00 |
July | 0.507507E+10 | 0.880345E+09 | 0.252383E+10 | 0.188191E+09 | 0.233564E+10 | 0.00 | 0.00 |
August | 0.614598E+10 | 0.749294E+09 | 0.301327E+10 | 0.562890E+09 | 0.245038E+10 | 0.00 | 0.00 |
September | 0.550093E+10 | 0.163301E+10 | 0.320696E+10 | 0.119282E+10 | 0.201414E+10 | 0.00 | 0.00 |
October | 0.703049E+10 | 0.339332E+10 | 0.480415E+10 | 0.311213E+10 | 0.169202E+10 | 0.00 | 0.00 |
November | 0.651930E+10 | 0.427100E+10 | 0.500168E+10 | 0.331903E+10 | 0.168265E+10 | 0.00 | 0.00 |
December | 0.620586E+10 | 0.524180E+10 | 0.523990E+10 | 0.368631E+10 | 0.155359E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.673216E+11 | 0.369684E+11 | 0.463986E+11 | 0.225977E+11 | 0.238009E+11 | 0.00 | 0.00 |
Minimum of Months | 0.426100E+10 | 0.749294E+09 | 0.241589E+10 | 0.134435E+09 | 0.147735E+10 | 0.00 | 0.00 |
Maximum of Months | 0.703049E+10 | 0.609888E+10 | 0.531579E+10 | 0.370615E+10 | 0.245038E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114232E+10 | 0.450216E+10 | 0.149471E+10 | 0.693353E+09 | 0.801361E+09 | 0.00 | 0.00 |
February | 0.155914E+10 | 0.343143E+10 | 0.154986E+10 | 0.724655E+09 | 0.825209E+09 | 0.00 | 0.00 |
March | 0.308226E+10 | 0.254959E+10 | 0.252917E+10 | 0.122215E+10 | 0.130702E+10 | 0.00 | 0.00 |
April | 0.388218E+10 | 0.202480E+10 | 0.275349E+10 | 0.125998E+10 | 0.149350E+10 | 0.00 | 0.00 |
May | 0.446767E+10 | 0.140135E+10 | 0.285958E+10 | 0.108338E+10 | 0.177620E+10 | 0.00 | 0.00 |
June | 0.517115E+10 | 0.886336E+09 | 0.291021E+10 | 0.111955E+10 | 0.179067E+10 | 0.00 | 0.00 |
July | 0.523404E+10 | 0.650321E+09 | 0.283650E+10 | 0.105168E+10 | 0.178482E+10 | 0.00 | 0.00 |
August | 0.517755E+10 | 0.565316E+09 | 0.277936E+10 | 0.103937E+10 | 0.173999E+10 | 0.00 | 0.00 |
September | 0.353764E+10 | 0.110154E+10 | 0.219138E+10 | 0.912804E+09 | 0.127857E+10 | 0.00 | 0.00 |
October | 0.273435E+10 | 0.233311E+10 | 0.201733E+10 | 0.104722E+10 | 0.970115E+09 | 0.00 | 0.00 |
November | 0.172348E+10 | 0.300331E+10 | 0.155804E+10 | 0.699329E+09 | 0.858712E+09 | 0.00 | 0.00 |
December | 0.110283E+10 | 0.381896E+10 | 0.132822E+10 | 0.580965E+09 | 0.747255E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.388146E+11 | 0.262682E+11 | 0.268079E+11 | 0.114344E+11 | 0.153734E+11 | 0.00 | 0.00 |
Minimum of Months | 0.110283E+10 | 0.565316E+09 | 0.132822E+10 | 0.580965E+09 | 0.747255E+09 | 0.00 | 0.00 |
Maximum of Months | 0.523404E+10 | 0.450216E+10 | 0.291021E+10 | 0.125998E+10 | 0.179067E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167648E+09 | 0.661158E+10 | 0.993954E+09 | 0.00 | 0.993954E+09 | 0.00 | 0.00 |
February | 0.449825E+09 | 0.492124E+10 | 0.995084E+09 | 0.00 | 0.995084E+09 | 0.00 | 0.00 |
March | 0.109930E+10 | 0.341367E+10 | 0.154673E+10 | 0.00 | 0.154673E+10 | 0.00 | 0.00 |
April | 0.202084E+10 | 0.268615E+10 | 0.181056E+10 | 8030357.15 | 0.180253E+10 | 0.00 | 0.00 |
May | 0.312401E+10 | 0.185036E+10 | 0.223758E+10 | 71411286.64 | 0.216617E+10 | 0.00 | 0.00 |
June | 0.434456E+10 | 0.115531E+10 | 0.238312E+10 | 0.157342E+09 | 0.222578E+10 | 0.00 | 0.00 |
July | 0.449804E+10 | 0.856812E+09 | 0.232342E+10 | 0.112943E+09 | 0.221048E+10 | 0.00 | 0.00 |
August | 0.411133E+10 | 0.713067E+09 | 0.206630E+10 | 22509151.83 | 0.204380E+10 | 0.00 | 0.00 |
September | 0.228041E+10 | 0.149946E+10 | 0.151155E+10 | 212783.61 | 0.151133E+10 | 0.00 | 0.00 |
October | 0.110974E+10 | 0.309717E+10 | 0.118759E+10 | 0.00 | 0.118759E+10 | 0.00 | 0.00 |
November | 0.608030E+09 | 0.405187E+10 | 0.102856E+10 | 0.00 | 0.102856E+10 | 0.00 | 0.00 |
December | 0.174979E+09 | 0.526941E+10 | 0.918837E+09 | 0.00 | 0.918837E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239887E+11 | 0.361261E+11 | 0.190033E+11 | 0.372449E+09 | 0.186308E+11 | 0.00 | 0.00 |
Minimum of Months | 0.167648E+09 | 0.713067E+09 | 0.918837E+09 | 0.00 | 0.918837E+09 | 0.00 | 0.00 |
Maximum of Months | 0.449804E+10 | 0.661158E+10 | 0.238312E+10 | 0.157342E+09 | 0.222578E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104319E+10 | 0.394561E+10 | 0.145522E+10 | 0.656378E+09 | 0.798842E+09 | 0.00 | 0.00 |
February | 0.162164E+10 | 0.297274E+10 | 0.165704E+10 | 0.890313E+09 | 0.766723E+09 | 0.00 | 0.00 |
March | 0.262754E+10 | 0.213653E+10 | 0.230811E+10 | 0.105072E+10 | 0.125739E+10 | 0.00 | 0.00 |
April | 0.372112E+10 | 0.172193E+10 | 0.270106E+10 | 0.123161E+10 | 0.146945E+10 | 0.00 | 0.00 |
May | 0.467022E+10 | 0.123932E+10 | 0.306484E+10 | 0.129607E+10 | 0.176876E+10 | 0.00 | 0.00 |
June | 0.536137E+10 | 0.784697E+09 | 0.307078E+10 | 0.128704E+10 | 0.178374E+10 | 0.00 | 0.00 |
July | 0.559493E+10 | 0.579127E+09 | 0.309394E+10 | 0.130073E+10 | 0.179320E+10 | 0.00 | 0.00 |
August | 0.521140E+10 | 0.480559E+09 | 0.282993E+10 | 0.112273E+10 | 0.170720E+10 | 0.00 | 0.00 |
September | 0.359527E+10 | 0.979416E+09 | 0.225079E+10 | 0.997266E+09 | 0.125352E+10 | 0.00 | 0.00 |
October | 0.256837E+10 | 0.195523E+10 | 0.198412E+10 | 0.103239E+10 | 0.951733E+09 | 0.00 | 0.00 |
November | 0.158121E+10 | 0.245362E+10 | 0.153515E+10 | 0.695109E+09 | 0.840039E+09 | 0.00 | 0.00 |
December | 0.106722E+10 | 0.314157E+10 | 0.137406E+10 | 0.626349E+09 | 0.747709E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.386635E+11 | 0.223903E+11 | 0.273250E+11 | 0.121867E+11 | 0.151383E+11 | 0.00 | 0.00 |
Minimum of Months | 0.104319E+10 | 0.480559E+09 | 0.137406E+10 | 0.626349E+09 | 0.747709E+09 | 0.00 | 0.00 |
Maximum of Months | 0.559493E+10 | 0.394561E+10 | 0.309394E+10 | 0.130073E+10 | 0.179320E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.604666E+10 | 0.563950E+10 | 0.531579E+10 | 0.370615E+10 | 0.160964E+10 | 0.00 | 0.00 |
February | 0.552812E+10 | 0.445056E+10 | 0.448128E+10 | 0.300392E+10 | 0.147735E+10 | 0.00 | 0.00 |
March | 0.594468E+10 | 0.348209E+10 | 0.446199E+10 | 0.232533E+10 | 0.213666E+10 | 0.00 | 0.00 |
April | 0.480819E+10 | 0.284326E+10 | 0.323393E+10 | 0.105271E+10 | 0.218122E+10 | 0.00 | 0.00 |
May | 0.424084E+10 | 0.198215E+10 | 0.269998E+10 | 0.313811E+09 | 0.238617E+10 | 0.00 | 0.00 |
June | 0.455903E+10 | 0.123201E+10 | 0.241589E+10 | 0.134435E+09 | 0.228145E+10 | 0.00 | 0.00 |
July | 0.501399E+10 | 0.893670E+09 | 0.252383E+10 | 0.188191E+09 | 0.233564E+10 | 0.00 | 0.00 |
August | 0.608280E+10 | 0.770059E+09 | 0.301327E+10 | 0.562890E+09 | 0.245038E+10 | 0.00 | 0.00 |
September | 0.548443E+10 | 0.159639E+10 | 0.320696E+10 | 0.119282E+10 | 0.201414E+10 | 0.00 | 0.00 |
October | 0.707322E+10 | 0.318122E+10 | 0.480415E+10 | 0.311213E+10 | 0.169202E+10 | 0.00 | 0.00 |
November | 0.664663E+10 | 0.392663E+10 | 0.500168E+10 | 0.331903E+10 | 0.168265E+10 | 0.00 | 0.00 |
December | 0.636373E+10 | 0.474862E+10 | 0.523990E+10 | 0.368631E+10 | 0.155359E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.677923E+11 | 0.347462E+11 | 0.463986E+11 | 0.225977E+11 | 0.238009E+11 | 0.00 | 0.00 |
Minimum of Months | 0.424084E+10 | 0.770059E+09 | 0.241589E+10 | 0.134435E+09 | 0.147735E+10 | 0.00 | 0.00 |
Maximum of Months | 0.707322E+10 | 0.563950E+10 | 0.531579E+10 | 0.370615E+10 | 0.245038E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118463E+10 | 0.421038E+10 | 0.149471E+10 | 0.693353E+09 | 0.801361E+09 | 0.00 | 0.00 |
February | 0.158494E+10 | 0.324018E+10 | 0.154986E+10 | 0.724655E+09 | 0.825209E+09 | 0.00 | 0.00 |
March | 0.311421E+10 | 0.239690E+10 | 0.252917E+10 | 0.122215E+10 | 0.130702E+10 | 0.00 | 0.00 |
April | 0.389657E+10 | 0.194879E+10 | 0.275349E+10 | 0.125998E+10 | 0.149350E+10 | 0.00 | 0.00 |
May | 0.445265E+10 | 0.138278E+10 | 0.285958E+10 | 0.108338E+10 | 0.177620E+10 | 0.00 | 0.00 |
June | 0.513372E+10 | 0.893773E+09 | 0.291021E+10 | 0.111955E+10 | 0.179067E+10 | 0.00 | 0.00 |
July | 0.519421E+10 | 0.656873E+09 | 0.283650E+10 | 0.105168E+10 | 0.178482E+10 | 0.00 | 0.00 |
August | 0.513784E+10 | 0.575260E+09 | 0.277936E+10 | 0.103937E+10 | 0.173999E+10 | 0.00 | 0.00 |
September | 0.353031E+10 | 0.107632E+10 | 0.219138E+10 | 0.912804E+09 | 0.127857E+10 | 0.00 | 0.00 |
October | 0.275829E+10 | 0.219400E+10 | 0.201733E+10 | 0.104722E+10 | 0.970115E+09 | 0.00 | 0.00 |
November | 0.177663E+10 | 0.278433E+10 | 0.155804E+10 | 0.699329E+09 | 0.858712E+09 | 0.00 | 0.00 |
December | 0.114277E+10 | 0.351497E+10 | 0.132822E+10 | 0.580965E+09 | 0.747255E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.389068E+11 | 0.248746E+11 | 0.268079E+11 | 0.114344E+11 | 0.153734E+11 | 0.00 | 0.00 |
Minimum of Months | 0.114277E+10 | 0.575260E+09 | 0.132822E+10 | 0.580965E+09 | 0.747255E+09 | 0.00 | 0.00 |
Maximum of Months | 0.519421E+10 | 0.421038E+10 | 0.291021E+10 | 0.125998E+10 | 0.179067E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.370517E+11 | -0.360225E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102917E+10 | 58.97 | 0.00 | 0.00 |
February | 0.337318E+11 | -0.328031E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -928689857.1 | 58.98 | 0.00 | 0.00 |
March | 0.383089E+11 | -0.372807E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102824E+10 | 58.97 | 0.00 | 0.00 |
April | 0.326406E+11 | -0.316483E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992289264.1 | 58.97 | 0.00 | 0.00 |
May | 0.321098E+11 | -0.310845E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102524E+10 | 58.98 | 0.00 | 0.00 |
June | 0.293463E+11 | -0.283547E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991558263.1 | 58.97 | 0.00 | 0.00 |
July | 0.265865E+11 | -0.255676E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101883E+10 | 58.97 | 0.00 | 0.00 |
August | 0.289272E+11 | -0.279041E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102310E+10 | 58.98 | 0.00 | 0.00 |
September | 0.275328E+11 | -0.265456E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987188961.4 | 58.97 | 0.00 | 0.00 |
October | 0.306577E+11 | -0.296385E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101925E+10 | 58.97 | 0.00 | 0.00 |
November | 0.326505E+11 | -0.316641E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986405512.1 | 58.97 | 0.00 | 0.00 |
December | 0.348015E+11 | -0.337800E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102147E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.384345E+12 | -0.372294E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120514E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.265865E+11 | -0.372807E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102917E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.383089E+11 | -0.255676E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -928689857.1 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.63 | 0.61 | 01-JAN-08:50 | 5135.26 | 32.94 | 258.50 | 264.50 | 1312.65 | 25.39 | 169.67 | 238.83 |
February | 263.00 | 0.64 | 0.61 | 01-FEB-10:09 | 6070.35 | 32.98 | 229.00 | 235.83 | 860.67 | 20.49 | 86.33 | 208.17 |
March | 351.67 | 0.64 | 0.61 | 01-MAR-08:20 | 1281.08 | 16.72 | 6.67 | 303.17 | 727.60 | 19.52 | 81.67 | 261.67 |
April | 369.33 | 0.64 | 0.61 | 01-APR-07:00 | 1065.79 | 16.18 | 0.00 | 307.83 | 595.38 | 19.06 | 43.33 | 256.83 |
May | 407.00 | 0.64 | 0.61 | 01-MAY-07:10 | 969.25 | 16.28 | 0.00 | 340.33 | 533.72 | 19.18 | 14.33 | 284.17 |
June | 411.67 | 0.64 | 0.61 | 01-JUN-06:40 | 900.25 | 15.97 | 0.00 | 342.33 | 502.31 | 18.89 | 5.67 | 280.67 |
July | 411.00 | 0.64 | 0.61 | 01-JUL-06:00 | 949.53 | 16.18 | 0.00 | 343.83 | 522.58 | 19.06 | 19.17 | 282.67 |
August | 390.50 | 0.64 | 0.61 | 01-AUG-06:00 | 1160.38 | 16.90 | 0.00 | 337.17 | 623.04 | 19.77 | 73.67 | 287.50 |
September | 298.50 | 0.64 | 0.61 | 01-SEP-07:10 | 1232.52 | 17.09 | 6.50 | 294.50 | 674.77 | 19.66 | 68.83 | 239.33 |
October | 293.50 | 0.63 | 0.61 | 01-OCT-07:40 | 2333.42 | 22.85 | 116.50 | 283.83 | 793.20 | 18.88 | 57.83 | 232.67 |
November | 299.00 | 0.64 | 0.61 | 01-NOV-07:00 | 5037.34 | 32.73 | 268.00 | 263.67 | 888.30 | 22.15 | 116.17 | 233.83 |
December | 285.17 | 0.63 | 0.61 | 01-DEC-07:00 | 4771.83 | 32.10 | 248.33 | 255.67 | 1256.60 | 26.37 | 168.67 | 233.00 |
Annual Sum or Average | 4071.00 | 0.64 | 2324.11 | 21.44 | 1133.50 | 3572.67 | 742.80 | 20.48 | 905.33 | 3039.33 | ||
Minimum of Months | 263.00 | 0.63 | 0.61 | 900.25 | 15.97 | 0.00 | 235.83 | 502.31 | 18.88 | 5.67 | 208.17 | |
Maximum of Months | 411.67 | 0.64 | 0.61 | 6070.35 | 32.98 | 268.00 | 343.83 | 1312.65 | 26.37 | 169.67 | 287.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.65 | 0.61 | 01-JAN-08:50 | 1150.59 | 16.61 | 66.00 | 215.50 | 567.26 | 15.83 | 39.33 | 138.17 |
February | 263.00 | 0.66 | 0.61 | 01-FEB-10:09 | 1547.56 | 16.26 | 58.33 | 198.17 | 769.54 | 15.38 | 36.50 | 144.50 |
March | 351.67 | 0.64 | 0.61 | 01-MAR-08:09 | 1758.97 | 15.99 | 74.00 | 286.00 | 688.23 | 13.18 | 1.17 | 231.50 |
April | 369.33 | 0.64 | 0.61 | 01-APR-07:49 | 1720.30 | 11.66 | 0.00 | 305.83 | 929.61 | 13.00 | 0.00 | 255.33 |
May | 407.00 | 0.64 | 0.61 | 01-MAY-06:49 | 1945.92 | 12.24 | 0.00 | 348.00 | 789.72 | 13.41 | 0.00 | 292.17 |
June | 411.67 | 0.64 | 0.61 | 01-JUN-06:19 | 2057.22 | 12.20 | 0.00 | 350.83 | 800.40 | 13.33 | 0.00 | 298.33 |
July | 411.00 | 0.64 | 0.61 | 01-JUL-05:00 | 1946.81 | 12.35 | 0.00 | 354.50 | 809.76 | 13.50 | 0.00 | 303.33 |
August | 390.50 | 0.64 | 0.61 | 01-AUG-06:40 | 1800.03 | 12.67 | 0.00 | 335.17 | 945.55 | 13.89 | 0.00 | 285.33 |
September | 298.50 | 0.65 | 0.61 | 01-SEP-06:00 | 1702.25 | 12.18 | 3.83 | 286.33 | 854.92 | 13.53 | 2.83 | 223.50 |
October | 293.50 | 0.65 | 0.61 | 01-OCT-07:30 | 2100.80 | 17.88 | 88.00 | 240.50 | 728.49 | 15.33 | 39.83 | 172.50 |
November | 299.00 | 0.66 | 0.61 | 01-NOV-07:00 | 1350.97 | 16.88 | 75.67 | 224.67 | 746.19 | 17.70 | 64.67 | 160.83 |
December | 285.17 | 0.65 | 0.61 | 01-DEC-07:00 | 1182.96 | 17.30 | 70.33 | 212.67 | 589.97 | 16.47 | 44.00 | 140.83 |
Annual Sum or Average | 4071.00 | 0.64 | 1720.29 | 14.23 | 436.17 | 3358.17 | 777.69 | 14.38 | 228.33 | 2646.33 | ||
Minimum of Months | 263.00 | 0.64 | 0.61 | 1150.59 | 11.66 | 0.00 | 198.17 | 567.26 | 13.00 | 0.00 | 138.17 | |
Maximum of Months | 411.67 | 0.66 | 0.61 | 2100.80 | 17.88 | 88.00 | 354.50 | 945.55 | 17.70 | 64.67 | 303.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.67 | 0.61 | 01-JAN-09:09 | 394.64 | 0.00 | 0.00 | 154.67 | 238.41 | 0.00 | 0.00 | 22.67 |
February | 263.00 | 0.68 | 0.61 | 01-FEB-10:20 | 418.16 | 0.00 | 0.00 | 144.50 | 260.32 | 0.00 | 0.00 | 56.83 |
March | 351.67 | 0.65 | 0.61 | 01-MAR-08:39 | 534.33 | 0.00 | 0.00 | 272.50 | 325.77 | 0.00 | 0.00 | 147.33 |
April | 369.33 | 0.64 | 0.61 | 01-APR-07:00 | 640.11 | 0.00 | 0.00 | 308.33 | 382.25 | 0.00 | 0.00 | 222.33 |
May | 407.00 | 0.63 | 0.61 | 01-MAY-06:00 | 792.30 | 0.00 | 0.00 | 365.33 | 467.79 | 0.00 | 0.00 | 317.83 |
June | 411.67 | 0.63 | 0.61 | 01-JUN-06:30 | 865.26 | 0.00 | 0.00 | 376.00 | 502.46 | 0.00 | 0.00 | 339.83 |
July | 411.00 | 0.63 | 0.61 | 01-JUL-06:10 | 878.77 | 0.00 | 0.00 | 373.83 | 488.83 | 0.00 | 0.00 | 328.17 |
August | 390.50 | 0.63 | 0.61 | 01-AUG-06:49 | 781.93 | 0.00 | 0.00 | 349.67 | 454.17 | 0.00 | 0.00 | 290.50 |
September | 298.50 | 0.65 | 0.61 | 01-SEP-07:10 | 591.65 | 0.00 | 0.00 | 282.17 | 358.67 | 0.00 | 0.00 | 161.83 |
October | 293.50 | 0.67 | 0.61 | 01-OCT-07:00 | 435.87 | 0.00 | 0.00 | 181.67 | 280.35 | 0.00 | 0.00 | 74.83 |
November | 299.00 | 0.67 | 0.61 | 01-NOV-08:20 | 407.13 | 0.00 | 0.00 | 185.33 | 247.91 | 0.00 | 0.00 | 23.50 |
December | 285.17 | 0.67 | 0.61 | 01-DEC-09:20 | 380.11 | 0.00 | 0.00 | 147.33 | 230.80 | 0.00 | 0.00 | 2.50 |
Annual Sum or Average | 4071.00 | 0.65 | 621.19 | 0.00 | 0.00 | 3141.33 | 368.04 | 0.00 | 0.00 | 1988.17 | ||
Minimum of Months | 263.00 | 0.63 | 0.61 | 380.11 | 0.00 | 0.00 | 144.50 | 230.80 | 0.00 | 0.00 | 2.50 | |
Maximum of Months | 411.67 | 0.68 | 0.61 | 878.77 | 0.00 | 0.00 | 376.00 | 502.46 | 0.00 | 0.00 | 339.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.65 | 0.61 | 01-JAN-09:20 | 1355.63 | 16.91 | 68.50 | 217.17 | 781.20 | 17.81 | 60.00 | 147.50 |
February | 263.00 | 0.66 | 0.61 | 01-FEB-10:20 | 1344.91 | 16.16 | 59.50 | 185.00 | 674.52 | 15.38 | 37.00 | 137.33 |
March | 351.67 | 0.64 | 0.61 | 01-MAR-08:39 | 1775.01 | 14.62 | 47.33 | 288.67 | 948.45 | 13.25 | 0.00 | 230.83 |
April | 369.33 | 0.64 | 0.61 | 01-APR-08:20 | 1860.99 | 11.76 | 0.00 | 307.83 | 1056.72 | 13.10 | 0.00 | 259.67 |
May | 407.00 | 0.64 | 0.61 | 01-MAY-07:30 | 1954.43 | 12.31 | 0.00 | 345.83 | 778.65 | 13.55 | 1.33 | 294.33 |
June | 411.67 | 0.64 | 0.61 | 01-JUN-06:00 | 2044.68 | 12.27 | 0.00 | 350.17 | 838.62 | 15.32 | 37.83 | 300.33 |
July | 411.00 | 0.64 | 0.61 | 01-JUL-07:30 | 2030.64 | 12.34 | 0.00 | 349.17 | 818.61 | 15.02 | 27.83 | 297.00 |
August | 390.50 | 0.64 | 0.61 | 01-AUG-07:30 | 1988.68 | 12.97 | 4.83 | 338.33 | 819.73 | 14.00 | 0.00 | 289.67 |
September | 298.50 | 0.64 | 0.61 | 01-SEP-07:30 | 1741.64 | 15.11 | 49.67 | 285.50 | 917.00 | 13.58 | 0.00 | 218.00 |
October | 293.50 | 0.65 | 0.61 | 01-OCT-08:20 | 1840.40 | 16.22 | 70.50 | 231.67 | 701.56 | 12.66 | 2.17 | 172.83 |
November | 299.00 | 0.65 | 0.61 | 01-NOV-08:20 | 1313.70 | 17.02 | 79.50 | 226.00 | 652.50 | 16.30 | 51.67 | 162.00 |
December | 285.17 | 0.65 | 0.61 | 01-DEC-09:20 | 1143.04 | 17.04 | 70.83 | 209.67 | 577.15 | 16.33 | 44.00 | 139.00 |
Annual Sum or Average | 4071.00 | 0.65 | 1740.71 | 14.26 | 450.67 | 3335.00 | 807.25 | 14.61 | 261.83 | 2648.50 | ||
Minimum of Months | 263.00 | 0.64 | 0.61 | 1143.04 | 11.76 | 0.00 | 185.00 | 577.15 | 12.66 | 0.00 | 137.33 | |
Maximum of Months | 411.67 | 0.66 | 0.61 | 2044.68 | 17.04 | 79.50 | 350.17 | 1056.72 | 17.81 | 60.00 | 300.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.64 | 0.61 | 01-JAN-08:50 | 5045.08 | 30.47 | 233.00 | 259.83 | 1347.48 | 21.60 | 100.50 | 240.17 |
February | 263.00 | 0.64 | 0.61 | 01-FEB-10:09 | 6053.42 | 32.50 | 227.50 | 234.00 | 895.79 | 15.72 | 25.83 | 208.67 |
March | 351.67 | 0.64 | 0.61 | 01-MAR-08:20 | 1263.71 | 10.58 | 6.50 | 302.33 | 755.03 | 15.21 | 0.00 | 264.33 |
April | 369.33 | 0.64 | 0.61 | 01-APR-07:00 | 1048.79 | 10.33 | 0.00 | 306.67 | 615.77 | 15.14 | 0.00 | 259.33 |
May | 407.00 | 0.64 | 0.61 | 01-MAY-07:10 | 950.46 | 10.60 | 0.00 | 338.17 | 549.68 | 15.36 | 0.00 | 287.67 |
June | 411.67 | 0.64 | 0.61 | 01-JUN-06:40 | 882.89 | 10.44 | 0.00 | 340.50 | 517.04 | 15.16 | 0.00 | 283.67 |
July | 411.00 | 0.64 | 0.61 | 01-JUL-06:00 | 930.38 | 10.63 | 0.00 | 342.00 | 537.66 | 15.32 | 0.00 | 286.67 |
August | 390.50 | 0.64 | 0.61 | 01-AUG-06:00 | 1135.99 | 11.29 | 0.00 | 335.17 | 641.03 | 15.98 | 0.00 | 290.33 |
September | 298.50 | 0.64 | 0.61 | 01-SEP-07:10 | 1210.33 | 11.47 | 6.50 | 293.33 | 696.93 | 15.79 | 0.00 | 242.83 |
October | 293.50 | 0.64 | 0.61 | 01-OCT-07:49 | 2321.95 | 18.72 | 115.00 | 281.33 | 832.05 | 14.36 | 2.00 | 236.00 |
November | 299.00 | 0.64 | 0.61 | 01-NOV-07:00 | 5016.18 | 32.05 | 266.33 | 262.83 | 943.91 | 19.77 | 79.33 | 241.00 |
December | 285.17 | 0.63 | 0.61 | 01-DEC-07:00 | 4747.47 | 31.25 | 241.33 | 254.67 | 1246.24 | 21.07 | 97.50 | 228.17 |
Annual Sum or Average | 4071.00 | 0.64 | 2299.92 | 17.13 | 1096.17 | 3550.83 | 765.89 | 16.51 | 305.17 | 3068.83 | ||
Minimum of Months | 263.00 | 0.63 | 0.61 | 882.89 | 10.33 | 0.00 | 234.00 | 517.04 | 14.36 | 0.00 | 208.67 | |
Maximum of Months | 411.67 | 0.64 | 0.61 | 6053.42 | 32.50 | 266.33 | 342.00 | 1347.48 | 21.60 | 100.50 | 290.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.65 | 0.61 | 01-JAN-08:50 | 1009.75 | 12.28 | 45.00 | 213.33 | 582.50 | 13.79 | 40.00 | 144.33 |
February | 263.00 | 0.66 | 0.61 | 01-FEB-10:09 | 1552.29 | 14.00 | 58.50 | 198.00 | 790.91 | 13.33 | 37.00 | 149.67 |
March | 351.67 | 0.64 | 0.61 | 01-MAR-08:09 | 1763.32 | 13.61 | 74.33 | 284.83 | 709.62 | 10.68 | 1.17 | 236.83 |
April | 369.33 | 0.64 | 0.61 | 01-APR-07:49 | 1718.65 | 8.18 | 0.00 | 305.50 | 953.59 | 10.53 | 0.00 | 259.67 |
May | 407.00 | 0.64 | 0.61 | 01-MAY-06:49 | 1930.85 | 8.76 | 0.00 | 347.17 | 815.20 | 11.06 | 0.00 | 298.67 |
June | 411.67 | 0.64 | 0.61 | 01-JUN-06:19 | 1949.25 | 8.80 | 0.00 | 349.50 | 825.67 | 11.08 | 0.00 | 301.83 |
July | 411.00 | 0.64 | 0.61 | 01-JUL-05:00 | 1931.72 | 8.92 | 0.00 | 353.50 | 834.79 | 11.20 | 0.00 | 307.50 |
August | 390.50 | 0.64 | 0.61 | 01-AUG-06:40 | 1784.64 | 9.29 | 0.00 | 334.33 | 968.44 | 11.51 | 0.00 | 288.83 |
September | 298.50 | 0.65 | 0.61 | 01-SEP-06:00 | 1705.07 | 8.76 | 2.67 | 285.00 | 878.49 | 11.09 | 2.83 | 227.83 |
October | 293.50 | 0.65 | 0.61 | 01-OCT-07:30 | 1933.03 | 13.74 | 67.33 | 241.00 | 751.26 | 13.31 | 40.00 | 177.67 |
November | 299.00 | 0.66 | 0.61 | 01-NOV-07:00 | 1348.79 | 14.75 | 75.83 | 224.33 | 762.09 | 15.92 | 66.50 | 167.50 |
December | 285.17 | 0.65 | 0.61 | 01-DEC-07:00 | 1169.58 | 14.79 | 67.33 | 211.50 | 605.57 | 14.40 | 44.33 | 145.50 |
Annual Sum or Average | 4071.00 | 0.65 | 1682.35 | 11.01 | 391.00 | 3348.00 | 799.63 | 12.13 | 231.83 | 2705.83 | ||
Minimum of Months | 263.00 | 0.64 | 0.61 | 1009.75 | 8.18 | 0.00 | 198.00 | 582.50 | 10.53 | 0.00 | 144.33 | |
Maximum of Months | 411.67 | 0.66 | 0.61 | 1949.25 | 14.79 | 75.83 | 353.50 | 968.44 | 15.92 | 66.50 | 307.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.68 | 0.61 | 01-JAN-09:09 | 387.32 | 0.00 | 0.00 | 151.83 | 245.31 | 0.00 | 0.00 | 27.50 |
February | 263.00 | 0.68 | 0.61 | 01-FEB-10:30 | 411.46 | 0.00 | 0.00 | 142.33 | 268.29 | 0.00 | 0.00 | 65.50 |
March | 351.67 | 0.65 | 0.61 | 01-MAR-08:39 | 525.69 | 0.00 | 0.00 | 269.33 | 335.69 | 0.00 | 0.00 | 165.00 |
April | 369.33 | 0.64 | 0.61 | 01-APR-07:00 | 630.18 | 0.00 | 0.00 | 307.00 | 394.14 | 0.00 | 0.00 | 229.67 |
May | 407.00 | 0.63 | 0.61 | 01-MAY-06:00 | 778.83 | 0.00 | 0.00 | 364.17 | 481.55 | 0.00 | 0.00 | 323.33 |
June | 411.67 | 0.63 | 0.61 | 01-JUN-06:30 | 850.86 | 0.00 | 0.00 | 375.33 | 524.92 | 0.00 | 0.00 | 349.83 |
July | 411.00 | 0.63 | 0.61 | 01-JUL-06:10 | 863.87 | 0.00 | 0.00 | 372.67 | 502.95 | 0.00 | 0.00 | 331.50 |
August | 390.50 | 0.63 | 0.61 | 01-AUG-06:49 | 764.99 | 0.00 | 0.00 | 346.17 | 467.03 | 0.00 | 0.00 | 296.17 |
September | 298.50 | 0.65 | 0.61 | 01-SEP-07:10 | 581.54 | 0.00 | 0.00 | 280.17 | 369.13 | 0.00 | 0.00 | 170.17 |
October | 293.50 | 0.67 | 0.61 | 01-OCT-08:09 | 429.84 | 0.00 | 0.00 | 181.33 | 289.21 | 0.00 | 0.00 | 81.67 |
November | 299.00 | 0.67 | 0.61 | 01-NOV-08:20 | 399.32 | 0.00 | 0.00 | 181.50 | 254.89 | 0.00 | 0.00 | 33.17 |
December | 285.17 | 0.68 | 0.61 | 01-DEC-09:20 | 372.42 | 0.00 | 0.00 | 144.00 | 237.17 | 0.00 | 0.00 | 8.33 |
Annual Sum or Average | 4071.00 | 0.65 | 610.36 | 0.00 | 0.00 | 3115.83 | 379.65 | 0.00 | 0.00 | 2081.83 | ||
Minimum of Months | 263.00 | 0.63 | 0.61 | 372.42 | 0.00 | 0.00 | 142.33 | 237.17 | 0.00 | 0.00 | 8.33 | |
Maximum of Months | 411.67 | 0.68 | 0.61 | 863.87 | 0.00 | 0.00 | 375.33 | 524.92 | 0.00 | 0.00 | 349.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.65 | 0.61 | 01-JAN-09:20 | 1354.76 | 14.66 | 68.00 | 216.67 | 797.92 | 15.99 | 60.17 | 152.83 |
February | 263.00 | 0.66 | 0.61 | 01-FEB-10:20 | 1186.53 | 11.63 | 41.17 | 185.00 | 694.20 | 13.39 | 37.00 | 140.00 |
March | 351.67 | 0.64 | 0.61 | 01-MAR-08:39 | 1780.49 | 11.79 | 47.33 | 288.00 | 910.80 | 10.67 | 0.00 | 233.67 |
April | 369.33 | 0.64 | 0.61 | 01-APR-08:20 | 1859.15 | 8.28 | 0.00 | 307.50 | 1080.68 | 10.65 | 0.00 | 264.17 |
May | 407.00 | 0.64 | 0.61 | 01-MAY-07:30 | 1848.58 | 8.88 | 0.00 | 344.83 | 802.13 | 11.16 | 0.00 | 299.00 |
June | 411.67 | 0.64 | 0.61 | 01-JUN-06:00 | 2031.51 | 8.90 | 0.00 | 349.67 | 842.29 | 11.17 | 0.00 | 301.17 |
July | 411.00 | 0.64 | 0.61 | 01-JUL-07:30 | 2006.01 | 8.96 | 0.00 | 348.67 | 825.82 | 11.20 | 0.00 | 299.17 |
August | 390.50 | 0.64 | 0.61 | 01-AUG-07:30 | 1896.20 | 9.65 | 4.83 | 337.33 | 842.74 | 11.63 | 0.00 | 294.50 |
September | 298.50 | 0.65 | 0.61 | 01-SEP-07:30 | 1745.67 | 12.49 | 49.67 | 284.83 | 940.03 | 11.09 | 0.00 | 223.67 |
October | 293.50 | 0.65 | 0.61 | 01-OCT-08:20 | 1844.44 | 13.93 | 70.50 | 232.17 | 723.30 | 10.12 | 2.17 | 179.33 |
November | 299.00 | 0.66 | 0.61 | 01-NOV-08:20 | 1311.61 | 14.88 | 79.67 | 225.67 | 668.62 | 14.31 | 51.83 | 167.33 |
December | 285.17 | 0.65 | 0.61 | 01-DEC-09:20 | 1141.42 | 14.88 | 70.83 | 209.50 | 592.21 | 14.27 | 44.50 | 142.67 |
Annual Sum or Average | 4071.00 | 0.65 | 1707.77 | 11.24 | 432.00 | 3329.83 | 819.78 | 11.98 | 195.67 | 2697.50 | ||
Minimum of Months | 263.00 | 0.64 | 0.61 | 1141.42 | 8.28 | 0.00 | 185.00 | 592.21 | 10.12 | 0.00 | 140.00 | |
Maximum of Months | 411.67 | 0.66 | 0.61 | 2031.51 | 14.88 | 79.67 | 349.67 | 1080.68 | 15.99 | 60.17 | 301.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.64 | 0.61 | 01-JAN-08:50 | 5044.69 | 30.46 | 233.00 | 259.83 | 1348.41 | 21.59 | 100.50 | 240.17 |
February | 263.00 | 0.64 | 0.61 | 01-FEB-10:09 | 6018.43 | 31.23 | 217.00 | 230.17 | 896.64 | 15.70 | 25.83 | 208.67 |
March | 351.67 | 0.64 | 0.61 | 01-MAR-08:20 | 1264.30 | 10.53 | 6.33 | 302.33 | 755.88 | 15.19 | 0.00 | 264.33 |
April | 369.33 | 0.64 | 0.61 | 01-APR-07:00 | 1049.35 | 10.29 | 0.00 | 306.67 | 616.47 | 15.12 | 0.00 | 259.67 |
May | 407.00 | 0.64 | 0.61 | 01-MAY-07:10 | 950.94 | 10.56 | 0.00 | 338.17 | 550.31 | 15.34 | 0.00 | 287.83 |
June | 411.67 | 0.64 | 0.61 | 01-JUN-06:40 | 883.29 | 10.40 | 0.00 | 340.50 | 517.61 | 15.14 | 0.00 | 284.00 |
July | 411.00 | 0.64 | 0.61 | 01-JUL-06:00 | 930.84 | 10.59 | 0.00 | 342.00 | 538.26 | 15.30 | 0.00 | 287.00 |
August | 390.50 | 0.64 | 0.61 | 01-AUG-06:00 | 1136.63 | 11.25 | 0.00 | 335.17 | 641.82 | 15.96 | 0.00 | 290.33 |
September | 298.50 | 0.64 | 0.61 | 01-SEP-07:10 | 1210.97 | 11.43 | 6.50 | 293.33 | 697.76 | 15.78 | 0.00 | 242.83 |
October | 293.50 | 0.64 | 0.61 | 01-OCT-07:49 | 2322.34 | 18.69 | 115.00 | 281.33 | 832.83 | 14.34 | 2.00 | 236.33 |
November | 299.00 | 0.64 | 0.61 | 01-NOV-07:00 | 5016.03 | 32.04 | 266.33 | 262.83 | 944.86 | 19.76 | 79.33 | 241.00 |
December | 285.17 | 0.63 | 0.61 | 01-DEC-07:00 | 4746.91 | 31.24 | 241.17 | 254.67 | 1247.16 | 21.06 | 97.50 | 228.17 |
Annual Sum or Average | 4071.00 | 0.64 | 2297.95 | 17.02 | 1085.33 | 3547.00 | 766.65 | 16.50 | 305.17 | 3070.33 | ||
Minimum of Months | 263.00 | 0.63 | 0.61 | 883.29 | 10.29 | 0.00 | 230.17 | 517.61 | 14.34 | 0.00 | 208.67 | |
Maximum of Months | 411.67 | 0.64 | 0.61 | 6018.43 | 32.04 | 266.33 | 342.00 | 1348.41 | 21.59 | 100.50 | 290.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.65 | 0.61 | 01-JAN-08:50 | 1009.65 | 12.26 | 45.00 | 213.33 | 582.94 | 13.78 | 40.00 | 144.83 |
February | 263.00 | 0.66 | 0.61 | 01-FEB-10:09 | 1552.17 | 13.99 | 58.50 | 197.83 | 791.31 | 13.32 | 37.00 | 150.00 |
March | 351.67 | 0.64 | 0.61 | 01-MAR-08:09 | 1763.27 | 13.60 | 74.33 | 284.83 | 710.18 | 10.67 | 1.17 | 236.83 |
April | 369.33 | 0.64 | 0.61 | 01-APR-07:49 | 1718.74 | 8.17 | 0.00 | 305.50 | 954.22 | 10.52 | 0.00 | 259.83 |
May | 407.00 | 0.64 | 0.61 | 01-MAY-06:49 | 1930.98 | 8.75 | 0.00 | 347.33 | 815.93 | 11.05 | 0.00 | 298.67 |
June | 411.67 | 0.64 | 0.61 | 01-JUN-06:19 | 1949.34 | 8.79 | 0.00 | 349.33 | 826.41 | 11.07 | 0.00 | 301.83 |
July | 411.00 | 0.64 | 0.61 | 01-JUL-05:00 | 1931.79 | 8.90 | 0.00 | 353.50 | 835.55 | 11.19 | 0.00 | 307.50 |
August | 390.50 | 0.64 | 0.61 | 01-AUG-06:40 | 1784.78 | 9.27 | 0.00 | 334.33 | 969.22 | 11.50 | 0.00 | 289.17 |
September | 298.50 | 0.65 | 0.61 | 01-SEP-06:00 | 1704.94 | 8.75 | 2.67 | 285.00 | 879.10 | 11.08 | 2.83 | 228.00 |
October | 293.50 | 0.65 | 0.61 | 01-OCT-07:30 | 1932.81 | 13.73 | 67.33 | 241.00 | 751.69 | 13.30 | 40.00 | 177.83 |
November | 299.00 | 0.66 | 0.61 | 01-NOV-07:00 | 1348.65 | 14.74 | 75.83 | 224.33 | 762.53 | 15.92 | 66.50 | 167.67 |
December | 285.17 | 0.65 | 0.61 | 01-DEC-07:00 | 1169.44 | 14.78 | 67.33 | 211.50 | 605.97 | 14.39 | 44.33 | 145.67 |
Annual Sum or Average | 4071.00 | 0.65 | 1682.34 | 11.00 | 391.00 | 3347.83 | 800.23 | 12.13 | 231.83 | 2707.83 | ||
Minimum of Months | 263.00 | 0.64 | 0.61 | 1009.65 | 8.17 | 0.00 | 197.83 | 582.94 | 10.52 | 0.00 | 144.83 | |
Maximum of Months | 411.67 | 0.66 | 0.61 | 1949.34 | 14.78 | 75.83 | 353.50 | 969.22 | 15.92 | 66.50 | 307.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.68 | 0.61 | 01-JAN-09:09 | 387.32 | 0.00 | 0.00 | 151.50 | 245.53 | 0.00 | 0.00 | 27.67 |
February | 263.00 | 0.68 | 0.61 | 01-FEB-10:30 | 411.42 | 0.00 | 0.00 | 142.33 | 268.51 | 0.00 | 0.00 | 65.67 |
March | 351.67 | 0.65 | 0.61 | 01-MAR-08:39 | 525.68 | 0.00 | 0.00 | 269.50 | 335.98 | 0.00 | 0.00 | 165.50 |
April | 369.33 | 0.64 | 0.61 | 01-APR-07:00 | 630.24 | 0.00 | 0.00 | 307.00 | 394.51 | 0.00 | 0.00 | 229.67 |
May | 407.00 | 0.63 | 0.61 | 01-MAY-06:00 | 778.97 | 0.00 | 0.00 | 364.17 | 482.03 | 0.00 | 0.00 | 323.67 |
June | 411.67 | 0.63 | 0.61 | 01-JUN-06:30 | 851.03 | 0.00 | 0.00 | 375.33 | 525.44 | 0.00 | 0.00 | 349.83 |
July | 411.00 | 0.63 | 0.61 | 01-JUL-06:10 | 864.03 | 0.00 | 0.00 | 372.67 | 503.46 | 0.00 | 0.00 | 331.50 |
August | 390.50 | 0.63 | 0.61 | 01-AUG-06:49 | 765.08 | 0.00 | 0.00 | 346.33 | 467.50 | 0.00 | 0.00 | 296.33 |
September | 298.50 | 0.65 | 0.61 | 01-SEP-07:10 | 581.51 | 0.00 | 0.00 | 280.00 | 369.45 | 0.00 | 0.00 | 170.33 |
October | 293.50 | 0.67 | 0.61 | 01-OCT-08:09 | 429.76 | 0.00 | 0.00 | 181.50 | 289.42 | 0.00 | 0.00 | 81.67 |
November | 299.00 | 0.67 | 0.61 | 01-NOV-08:20 | 399.29 | 0.00 | 0.00 | 181.50 | 255.12 | 0.00 | 0.00 | 33.17 |
December | 285.17 | 0.68 | 0.61 | 01-DEC-09:20 | 372.39 | 0.00 | 0.00 | 143.67 | 237.38 | 0.00 | 0.00 | 8.33 |
Annual Sum or Average | 4071.00 | 0.65 | 610.41 | 0.00 | 0.00 | 3115.50 | 380.01 | 0.00 | 0.00 | 2083.33 | ||
Minimum of Months | 263.00 | 0.63 | 0.61 | 372.39 | 0.00 | 0.00 | 142.33 | 237.38 | 0.00 | 0.00 | 8.33 | |
Maximum of Months | 411.67 | 0.68 | 0.61 | 864.03 | 0.00 | 0.00 | 375.33 | 525.44 | 0.00 | 0.00 | 349.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.65 | 0.61 | 01-JAN-09:20 | 1354.66 | 14.65 | 68.00 | 216.67 | 798.35 | 15.98 | 60.17 | 153.00 |
February | 263.00 | 0.66 | 0.61 | 01-FEB-10:20 | 1186.37 | 11.62 | 41.17 | 185.00 | 694.68 | 13.38 | 37.00 | 140.00 |
March | 351.67 | 0.64 | 0.61 | 01-MAR-08:39 | 1780.28 | 11.78 | 47.33 | 288.00 | 911.38 | 10.67 | 0.00 | 234.00 |
April | 369.33 | 0.64 | 0.61 | 01-APR-08:20 | 1859.22 | 8.26 | 0.00 | 307.67 | 1081.34 | 10.64 | 0.00 | 264.33 |
May | 407.00 | 0.64 | 0.61 | 01-MAY-07:30 | 1848.72 | 8.86 | 0.00 | 344.83 | 802.88 | 11.16 | 0.00 | 299.00 |
June | 411.67 | 0.64 | 0.61 | 01-JUN-06:00 | 2031.61 | 8.88 | 0.00 | 349.67 | 843.04 | 11.16 | 0.00 | 301.33 |
July | 411.00 | 0.64 | 0.61 | 01-JUL-07:30 | 2006.15 | 8.95 | 0.00 | 348.67 | 826.58 | 11.19 | 0.00 | 299.33 |
August | 390.50 | 0.64 | 0.61 | 01-AUG-07:30 | 1896.36 | 9.64 | 4.83 | 337.33 | 839.50 | 11.62 | 0.00 | 294.50 |
September | 298.50 | 0.65 | 0.61 | 01-SEP-07:30 | 1745.68 | 12.48 | 49.67 | 284.83 | 898.59 | 11.08 | 0.00 | 221.17 |
October | 293.50 | 0.65 | 0.61 | 01-OCT-08:20 | 1844.23 | 13.92 | 70.50 | 232.17 | 723.76 | 10.11 | 2.17 | 179.33 |
November | 299.00 | 0.66 | 0.61 | 01-NOV-08:20 | 1311.47 | 14.87 | 79.67 | 225.67 | 669.08 | 14.31 | 51.83 | 167.33 |
December | 285.17 | 0.65 | 0.61 | 01-DEC-09:20 | 1141.29 | 14.87 | 70.83 | 209.17 | 592.62 | 14.27 | 44.50 | 143.17 |
Annual Sum or Average | 4071.00 | 0.65 | 1707.76 | 11.23 | 432.00 | 3329.67 | 816.93 | 11.97 | 195.67 | 2696.50 | ||
Minimum of Months | 263.00 | 0.64 | 0.61 | 1141.29 | 8.26 | 0.00 | 185.00 | 592.62 | 10.11 | 0.00 | 140.00 | |
Maximum of Months | 411.67 | 0.66 | 0.61 | 2031.61 | 14.87 | 79.67 | 349.67 | 1081.34 | 15.98 | 60.17 | 301.33 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125490E+10 | 51378.81 | 06-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.831263E+09 | 58109.47 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190869E+09 | 27257.73 | 18-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295089E+09 | 27164.08 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171670E+09 | 9833.09 | 15-MAY-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46717691.54 | 7396.97 | 02-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1509395.83 | 4560.58 | 25-AUG-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29117668.01 | 8279.74 | 14-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95833582.56 | 27727.19 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.344881E+09 | 45052.04 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.706857E+09 | 46657.59 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.396871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125490E+10 | 58109.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.642481E+09 | 14892.62 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237656E+09 | 14935.22 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8377109.88 | 3945.55 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31025966.41 | 13200.50 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.919540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.642481E+09 | 14935.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.629239E+09 | 12050.94 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.261730E+09 | 12086.46 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3597460.54 | 527.23 | 18-MAR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 831391.80 | 611.29 | 06-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1905554.99 | 432.19 | 26-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20136751.80 | 9253.84 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106311E+09 | 12049.33 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.629239E+09 | 12086.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.669461E+09 | 16935.56 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241742E+09 | 16984.07 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19508713.17 | 15165.54 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 90763389.60 | 16935.19 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.669461E+09 | 16984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.288141E+09 | 10457.20 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39087211.13 | 10553.28 | 13-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.288141E+09 | 10553.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.262322E+11 | 538473.62 | 06-JAN-17:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.238430E+11 | 590996.28 | 03-FEB-17:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.713028E+10 | 315280.92 | 22-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.266692E+10 | 355492.35 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174408E+10 | 145017.40 | 11-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.514811E+09 | 50133.53 | 02-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30192064.67 | 30086.69 | 25-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.334371E+09 | 118816.18 | 14-SEP-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.328712E+10 | 328828.48 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.929287E+10 | 493859.92 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129090E+11 | 546024.12 | 18-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.879848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.262322E+11 | 590996.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.205186E+10 | 541261.90 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.829214E+09 | 546043.98 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205186E+10 | 546043.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.438496E+11 | 135246.79 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237310E+11 | 145024.27 | 25-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183851E+10 | 144687.45 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368941E+09 | 135784.18 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.514835E+09 | 145876.85 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.544976E+10 | 136782.48 | 18-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201323E+11 | 145707.70 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.958849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.438496E+11 | 145876.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.314144E+11 | 141111.02 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170551E+11 | 140739.27 | 13-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175395E+10 | 144478.37 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.271350E+09 | 83981.35 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112762E+10 | 111251.23 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.394660E+10 | 140211.59 | 25-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149570E+11 | 149347.48 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.705260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.314144E+11 | 149347.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.224798E+11 | 154777.70 | 09-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119634E+11 | 155160.41 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.753011E+09 | 149440.17 | 22-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.209647E+09 | 54652.75 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.407053E+09 | 39119.96 | 31-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173748E+10 | 153487.62 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.830069E+10 | 164315.22 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.224798E+11 | 164315.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.275133E+11 | 149460.23 | 09-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146006E+11 | 148660.63 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126485E+10 | 96704.89 | 22-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184114E+09 | 23232.09 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.621124E+09 | 44821.88 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.385294E+10 | 148440.51 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129015E+11 | 151521.54 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.609385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.275133E+11 | 151521.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187434E+10 | 54372.63 | 06-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113896E+10 | 57542.67 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.250014E+09 | 32545.74 | 18-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.229605E+09 | 37404.54 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125096E+09 | 15119.13 | 11-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33053327.54 | 6757.36 | 02-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9937221.65 | 6527.22 | 25-AUG-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13734484.32 | 2723.99 | 22-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170400E+09 | 34544.05 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371732E+09 | 51279.73 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.735600E+09 | 56174.29 | 18-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.495248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187434E+10 | 57542.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.639639E+10 | 82584.56 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292135E+10 | 82117.51 | 08-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 48586089.58 | 42625.71 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19014382.94 | 4166.44 | 30-OCT-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.349020E+09 | 81918.38 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282878E+10 | 82627.88 | 26-DEC-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.639639E+10 | 82627.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.934813E+10 | 15410.68 | 02-JAN-05:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.556354E+10 | 16750.36 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107426E+10 | 15336.07 | 02-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280075E+09 | 15266.42 | 26-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7127625.29 | 1410.29 | 11-MAY-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 926522.87 | 258.16 | 29-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.643591E+09 | 15347.68 | 31-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.217790E+10 | 15361.81 | 25-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.572328E+10 | 15379.86 | 26-DEC-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.934813E+10 | 16750.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.581572E+10 | 14543.54 | 19-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.341172E+10 | 14498.12 | 11-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.665420E+09 | 14484.35 | 22-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145459E+09 | 14363.16 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4819230.85 | 1431.74 | 11-MAY-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7602815.45 | 1304.48 | 29-SEP-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.499377E+09 | 14489.71 | 25-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131063E+10 | 14514.06 | 25-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.351001E+10 | 14504.12 | 26-DEC-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.581572E+10 | 14543.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.553113E+10 | 17370.41 | 02-JAN-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.337392E+10 | 17303.91 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.634226E+09 | 17306.56 | 22-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197703E+09 | 17181.84 | 07-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7195466.33 | 1058.94 | 11-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1698458.35 | 373.37 | 29-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.392964E+09 | 17310.31 | 31-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100217E+10 | 17282.58 | 25-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292954E+10 | 17337.15 | 26-DEC-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.553113E+10 | 17370.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.533783E+10 | 16290.81 | 02-JAN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308317E+10 | 16246.13 | 11-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.618415E+09 | 16189.03 | 22-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140306E+09 | 14298.56 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2530784.78 | 342.09 | 11-MAY-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5121561.78 | 1466.08 | 29-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.437969E+09 | 14936.60 | 25-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128565E+10 | 16202.78 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.310999E+10 | 16211.68 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.533783E+10 | 16290.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.198280E+10 | 0.187542E+10 | 41599.57 | 31-JAN-15:00 | 41599.57 | 0.03 |
February | 0.00 | 0.00 | 0.848749E+10 | 0.848331E+10 | 92211.38 | 28-FEB-15:00 | 92211.38 | 0.04 |
March | 0.00 | 0.00 | 0.270838E+11 | 0.261654E+11 | 126352.88 | 30-MAR-05:03 | 65283.66 | 0.17 |
April | 0.00 | 0.00 | 0.593506E+11 | 0.565493E+11 | 166868.64 | 17-APR-15:00 | 166868.64 | 0.37 |
May | 0.00 | 0.00 | 0.948286E+11 | 0.804717E+11 | 212907.75 | 31-MAY-03:02 | 144239.18 | 0.56 |
June | 0.00 | 0.00 | 0.149290E+12 | 0.125402E+12 | 220342.84 | 26-JUN-05:02 | 156456.50 | 0.68 |
July | 0.00 | 0.00 | 0.177982E+12 | 0.142759E+12 | 215751.27 | 17-JUL-05:03 | 154510.50 | 0.81 |
August | 0.00 | 0.00 | 0.207460E+12 | 0.165899E+12 | 221848.30 | 07-AUG-05:03 | 157766.82 | 0.88 |
September | 0.00 | 0.00 | 0.113116E+12 | 0.919298E+11 | 227672.48 | 05-SEP-03:02 | 157742.07 | 0.63 |
October | 0.00 | 0.00 | 0.517056E+11 | 0.420874E+11 | 217641.84 | 19-OCT-05:03 | 143870.29 | 0.24 |
November | 0.00 | 0.00 | 0.183662E+11 | 0.169287E+11 | 118267.43 | 27-NOV-06:03 | 118267.43 | 0.12 |
December | 0.00 | 0.00 | 0.569561E+10 | 0.478798E+10 | 110224.97 | 13-DEC-06:03 | 52442.93 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.915349E+12 | 0.763340E+12 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 0.198280E+10 | 0.187542E+10 | 41599.57 | 41599.57 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.207460E+12 | 0.165899E+12 | 227672.48 | 166868.64 | 0.88 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.144249E+11 | 0.137684E+11 | 309146.43 | 31-JAN-15:00 | 309146.43 | 0.03 |
February | 0.00 | 0.00 | 0.633944E+11 | 0.633944E+11 | 727541.52 | 28-FEB-15:00 | 727541.52 | 0.03 |
March | 0.00 | 0.00 | 0.201860E+12 | 0.195986E+12 | 1156652.07 | 30-MAR-15:20 | 1156652.07 | 0.16 |
April | 0.00 | 0.00 | 0.429048E+12 | 0.411037E+12 | 1553135.93 | 12-APR-14:40 | 1553135.93 | 0.29 |
May | 0.00 | 0.00 | 0.830103E+12 | 0.702445E+12 | 1765834.77 | 31-MAY-03:02 | 1132766.70 | 0.54 |
June | 0.00 | 0.00 | 0.126985E+13 | 0.103091E+13 | 2161595.29 | 24-JUN-05:03 | 1415551.21 | 0.59 |
July | 0.00 | 0.00 | 0.144371E+13 | 0.109503E+13 | 2242378.74 | 14-JUL-03:02 | 1465605.21 | 0.66 |
August | 0.00 | 0.00 | 0.162546E+13 | 0.120836E+13 | 2517226.01 | 23-AUG-03:02 | 1449689.63 | 0.69 |
September | 0.00 | 0.00 | 0.974399E+12 | 0.769309E+12 | 2155005.74 | 27-SEP-05:03 | 1435590.22 | 0.58 |
October | 0.00 | 0.00 | 0.403308E+12 | 0.319247E+12 | 1837833.88 | 18-OCT-04:03 | 1078298.03 | 0.21 |
November | 0.00 | 0.00 | 0.125975E+12 | 0.118555E+12 | 771822.99 | 04-NOV-05:02 | 401232.80 | 0.11 |
December | 0.00 | 0.00 | 0.349632E+11 | 0.297104E+11 | 836741.85 | 13-DEC-06:03 | 401710.15 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.741648E+13 | 0.595776E+13 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.144249E+11 | 0.137684E+11 | 309146.43 | 309146.43 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.162546E+13 | 0.120836E+13 | 2517226.01 | 1553135.93 | 0.69 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.133325E+10 | 0.126813E+10 | 24819.03 | 31-JAN-15:00 | 24819.03 | 0.03 |
February | 0.00 | 0.00 | 0.549883E+10 | 0.549883E+10 | 69599.68 | 28-FEB-15:00 | 69599.68 | 0.03 |
March | 0.00 | 0.00 | 0.194692E+11 | 0.190508E+11 | 127836.40 | 30-MAR-15:30 | 127836.40 | 0.15 |
April | 0.00 | 0.00 | 0.440849E+11 | 0.423593E+11 | 167531.78 | 17-APR-15:00 | 167531.78 | 0.28 |
May | 0.00 | 0.00 | 0.897048E+11 | 0.768287E+11 | 169693.82 | 16-MAY-15:40 | 169693.82 | 0.53 |
June | 0.00 | 0.00 | 0.140246E+12 | 0.115584E+12 | 222371.00 | 29-JUN-05:03 | 145057.48 | 0.60 |
July | 0.00 | 0.00 | 0.159566E+12 | 0.123878E+12 | 239690.96 | 14-JUL-03:02 | 154666.68 | 0.67 |
August | 0.00 | 0.00 | 0.178030E+12 | 0.135335E+12 | 269757.61 | 23-AUG-03:02 | 153231.68 | 0.70 |
September | 0.00 | 0.00 | 0.100559E+12 | 0.803705E+11 | 224550.45 | 27-SEP-05:03 | 148261.22 | 0.58 |
October | 0.00 | 0.00 | 0.394586E+11 | 0.310869E+11 | 209629.00 | 19-OCT-04:03 | 103993.49 | 0.21 |
November | 0.00 | 0.00 | 0.107436E+11 | 0.101097E+11 | 69268.52 | 04-NOV-05:02 | 36937.49 | 0.10 |
December | 0.00 | 0.00 | 0.298258E+10 | 0.252223E+10 | 44724.07 | 12-DEC-14:40 | 44724.07 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.791677E+12 | 0.643892E+12 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.133325E+10 | 0.126813E+10 | 24819.03 | 24819.03 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.178030E+12 | 0.135335E+12 | 269757.61 | 169693.82 | 0.70 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.654960E+09 | 0.638719E+09 | 51712.16 | 19-JAN-05:02 | 21872.50 | 0.02 |
February | 0.00 | 0.00 | 0.429000E+10 | 0.427141E+10 | 60831.06 | 28-FEB-14:20 | 60831.06 | 0.01 |
March | 0.00 | 0.00 | 0.133790E+11 | 0.133359E+11 | 84394.81 | 29-MAR-04:03 | 48177.77 | 0.12 |
April | 0.00 | 0.00 | 0.281709E+11 | 0.277378E+11 | 91436.89 | 17-APR-14:20 | 91436.89 | 0.23 |
May | 0.00 | 0.00 | 0.509565E+11 | 0.466949E+11 | 134085.00 | 31-MAY-03:02 | 53339.07 | 0.43 |
June | 0.00 | 0.00 | 0.871638E+11 | 0.736925E+11 | 160487.35 | 26-JUN-03:02 | 93879.61 | 0.51 |
July | 0.00 | 0.00 | 0.997131E+11 | 0.793583E+11 | 160904.56 | 09-JUL-19:58 | 90415.30 | 0.55 |
August | 0.00 | 0.00 | 0.119852E+12 | 0.938395E+11 | 170939.38 | 06-AUG-17:00 | 90563.37 | 0.63 |
September | 0.00 | 0.00 | 0.740994E+11 | 0.627840E+11 | 170246.34 | 17-SEP-15:30 | 91581.25 | 0.52 |
October | 0.00 | 0.00 | 0.326725E+11 | 0.276098E+11 | 147025.23 | 19-OCT-03:02 | 89449.06 | 0.19 |
November | 0.00 | 0.00 | 0.105825E+11 | 0.989265E+10 | 82619.10 | 27-NOV-06:03 | 41080.11 | 0.08 |
December | 0.00 | 0.00 | 0.304282E+10 | 0.281530E+10 | 78224.66 | 13-DEC-06:03 | 36877.32 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.524577E+12 | 0.442671E+12 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.654960E+09 | 0.638719E+09 | 51712.16 | 21872.50 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.119852E+12 | 0.938395E+11 | 170939.38 | 93879.61 | 0.63 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.322966E+12 | 0.322464E+12 | 130083.10 | 19-JAN-17:00 | 124069.89 | 0.00 |
February | 0.00 | 0.00 | 0.513952E+12 | 0.513402E+12 | 220175.47 | 17-FEB-17:00 | 214473.75 | 0.00 |
March | 0.00 | 0.00 | 0.819449E+12 | 0.817911E+12 | 394376.47 | 31-MAR-24:00 | 394376.47 | 0.00 |
April | 0.00 | 0.00 | 0.103082E+13 | 0.102886E+13 | 406828.74 | 21-APR-15:00 | 400382.54 | 0.00 |
May | 0.00 | 0.00 | 0.340757E+12 | 0.334600E+12 | 213073.78 | 31-MAY-23:10 | 211091.89 | 0.00 |
June | 0.00 | 0.00 | 0.572826E+12 | 0.563876E+12 | 303977.93 | 30-JUN-23:03 | 303070.61 | 0.00 |
July | 0.00 | 0.00 | 0.840267E+12 | 0.829354E+12 | 396710.96 | 31-JUL-23:53 | 395957.48 | 0.00 |
August | 0.00 | 0.00 | 0.108066E+13 | 0.106955E+13 | 422669.57 | 08-AUG-17:00 | 404110.58 | 0.00 |
September | 0.00 | 0.00 | 0.337763E+12 | 0.329527E+12 | 212264.84 | 30-SEP-23:20 | 211758.45 | 0.00 |
October | 0.00 | 0.00 | 0.584208E+12 | 0.580533E+12 | 304610.49 | 31-OCT-24:00 | 304610.49 | 0.00 |
November | 0.00 | 0.00 | 0.798227E+12 | 0.796774E+12 | 317828.33 | 27-NOV-17:00 | 311185.01 | 0.00 |
December | 0.00 | 0.00 | 0.106526E+13 | 0.106452E+13 | 408607.11 | 13-DEC-14:00 | 400800.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.830716E+13 | 0.825137E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.322966E+12 | 0.322464E+12 | 130083.10 | 124069.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108066E+13 | 0.106955E+13 | 422669.57 | 404110.58 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.388000E+10 | 0.386082E+10 | 2286.82 | 20-JAN-17:00 | 2184.50 | 0.00 |
February | 0.00 | 0.00 | 0.872691E+10 | 0.870482E+10 | 4453.16 | 20-FEB-17:57 | 4421.18 | 0.00 |
March | 0.00 | 0.00 | 0.156533E+11 | 0.155876E+11 | 7720.69 | 31-MAR-24:00 | 7720.69 | 0.00 |
April | 0.00 | 0.00 | 0.202801E+11 | 0.201905E+11 | 8432.87 | 09-APR-18:13 | 8432.87 | 0.00 |
May | 0.00 | 0.00 | 0.614787E+10 | 0.591563E+10 | 4101.81 | 31-MAY-24:00 | 4047.65 | 0.00 |
June | 0.00 | 0.00 | 0.111893E+11 | 0.108197E+11 | 5924.57 | 30-JUN-23:03 | 5872.78 | 0.00 |
July | 0.00 | 0.00 | 0.167372E+11 | 0.162639E+11 | 7802.82 | 31-JUL-23:53 | 7783.51 | 0.00 |
August | 0.00 | 0.00 | 0.219282E+11 | 0.213794E+11 | 8910.23 | 04-AUG-15:00 | 8286.90 | 0.00 |
September | 0.00 | 0.00 | 0.612801E+10 | 0.581391E+10 | 3809.52 | 30-SEP-24:00 | 3795.04 | 0.00 |
October | 0.00 | 0.00 | 0.108360E+11 | 0.106852E+11 | 5714.11 | 31-OCT-24:00 | 5714.11 | 0.00 |
November | 0.00 | 0.00 | 0.150491E+11 | 0.149919E+11 | 6351.58 | 11-NOV-17:00 | 6351.58 | 0.00 |
December | 0.00 | 0.00 | 0.202053E+11 | 0.201732E+11 | 8238.83 | 11-DEC-16:50 | 8050.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156761E+12 | 0.154387E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.388000E+10 | 0.386082E+10 | 2286.82 | 2184.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219282E+11 | 0.213794E+11 | 8910.23 | 8432.87 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.163281E+11 | 0.161539E+11 | 19530.52 | 20-JAN-17:00 | 18500.76 | 0.00 |
February | 0.00 | 0.00 | 0.677968E+11 | 0.675829E+11 | 40685.97 | 28-FEB-17:00 | 40685.97 | 0.00 |
March | 0.00 | 0.00 | 0.141442E+12 | 0.140785E+12 | 72458.81 | 31-MAR-24:00 | 72458.81 | 0.00 |
April | 0.00 | 0.00 | 0.190165E+12 | 0.189267E+12 | 79426.71 | 04-APR-15:30 | 76484.20 | 0.00 |
May | 0.00 | 0.00 | 0.560115E+11 | 0.537319E+11 | 38870.98 | 31-MAY-24:00 | 38306.23 | 0.00 |
June | 0.00 | 0.00 | 0.106096E+12 | 0.102419E+12 | 56867.18 | 30-JUN-24:00 | 56666.29 | 0.00 |
July | 0.00 | 0.00 | 0.159566E+12 | 0.154846E+12 | 75557.80 | 31-JUL-23:53 | 75369.05 | 0.00 |
August | 0.00 | 0.00 | 0.208708E+12 | 0.203221E+12 | 84473.89 | 04-AUG-14:50 | 78354.88 | 0.00 |
September | 0.00 | 0.00 | 0.553801E+11 | 0.523021E+11 | 32864.18 | 30-SEP-24:00 | 32646.88 | 0.00 |
October | 0.00 | 0.00 | 0.954332E+11 | 0.939438E+11 | 50037.09 | 31-OCT-24:00 | 50037.09 | 0.00 |
November | 0.00 | 0.00 | 0.131632E+12 | 0.131067E+12 | 59251.80 | 02-NOV-16:00 | 57406.38 | 0.00 |
December | 0.00 | 0.00 | 0.173194E+12 | 0.172872E+12 | 76764.68 | 11-DEC-17:00 | 74873.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.140175E+13 | 0.137819E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.163281E+11 | 0.161539E+11 | 19530.52 | 18500.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208708E+12 | 0.203221E+12 | 84473.89 | 78354.88 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.703677E+09 | 0.687387E+09 | 1973.82 | 20-JAN-17:00 | 1868.80 | 0.00 |
February | 0.00 | 0.00 | 0.552683E+10 | 0.550586E+10 | 4095.19 | 28-FEB-17:00 | 4095.19 | 0.00 |
March | 0.00 | 0.00 | 0.133685E+11 | 0.133033E+11 | 6990.82 | 31-MAR-23:20 | 6990.82 | 0.00 |
April | 0.00 | 0.00 | 0.186427E+11 | 0.185532E+11 | 7986.02 | 17-APR-16:00 | 7949.96 | 0.00 |
May | 0.00 | 0.00 | 0.551972E+10 | 0.529231E+10 | 3847.58 | 31-MAY-23:20 | 3755.70 | 0.00 |
June | 0.00 | 0.00 | 0.106704E+11 | 0.103026E+11 | 5667.46 | 30-JUN-24:00 | 5647.25 | 0.00 |
July | 0.00 | 0.00 | 0.160464E+11 | 0.155745E+11 | 7592.84 | 31-JUL-23:53 | 7573.86 | 0.00 |
August | 0.00 | 0.00 | 0.209686E+11 | 0.204201E+11 | 8556.78 | 04-AUG-15:00 | 7936.87 | 0.00 |
September | 0.00 | 0.00 | 0.541425E+10 | 0.510815E+10 | 2972.15 | 07-SEP-16:00 | 2591.45 | 0.00 |
October | 0.00 | 0.00 | 0.884832E+10 | 0.870021E+10 | 4596.63 | 18-OCT-16:00 | 4092.98 | 0.00 |
November | 0.00 | 0.00 | 0.119724E+11 | 0.119165E+11 | 5955.09 | 02-NOV-16:00 | 5770.32 | 0.00 |
December | 0.00 | 0.00 | 0.155396E+11 | 0.155076E+11 | 7637.30 | 13-DEC-16:00 | 7308.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.133221E+12 | 0.130872E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.703677E+09 | 0.687387E+09 | 1973.82 | 1868.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.209686E+11 | 0.204201E+11 | 8556.78 | 7949.96 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 70766.49 | 1538862.95 | 02-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 46340.84 | 1377556.71 | 13-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 6022.53 | 845252.55 | 22-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1891.79 | 594456.89 | 06-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 813.76 | 167072.52 | 11-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 223.30 | 64231.07 | 03-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 10.93 | 23113.13 | 25-AUG-13:50 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 139.85 | 101460.30 | 14-SEP-15:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 2998.34 | 578351.45 | 26-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 11964.10 | 1127967.28 | 25-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 32871.49 | 1176088.85 | 26-DEC-05:01 |
Annual Sum or Average | 0.00 | 14361.93 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 70766.49 | 1538862.95 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 17348.96 | 1032955.60 | 31-JAN-15:50 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 70101.72 | 1584029.14 | 28-FEB-14:50 | 46.17 | 231201.10 | 27-FEB-04:02 |
March | 189690.67 | 1736171.16 | 30-MAR-14:40 | 112.39 | 250873.72 | 12-MAR-09:02 |
April | 362501.79 | 1999982.69 | 17-APR-14:20 | 38.53 | 82802.49 | 13-APR-23:53 |
May | 615987.90 | 2228548.90 | 31-MAY-03:02 | 286.63 | 564710.83 | 21-MAY-07:00 |
June | 855749.64 | 2713352.57 | 15-JUN-05:03 | 130.58 | 293653.70 | 10-JUN-04:05 |
July | 916874.13 | 2764532.01 | 27-JUL-05:02 | 5.42 | 89687.98 | 01-JUL-20:22 |
August | 996407.91 | 3243385.68 | 24-AUG-05:04 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 699543.03 | 2550798.41 | 05-SEP-05:03 | 23.28 | 143386.02 | 24-SEP-07:50 |
October | 317005.45 | 1958930.45 | 18-OCT-04:03 | 152.84 | 265117.07 | 08-OCT-08:32 |
November | 136135.83 | 1476152.59 | 02-NOV-13:50 | 27.86 | 222313.15 | 27-NOV-04:02 |
December | 38496.39 | 1363127.86 | 12-DEC-14:30 | 4.21 | 37582.59 | 11-DEC-10:05 |
Annual Sum or Average | 436786.06 | 69.33 | ||||
Minimum of Months | 17348.96 | 1032955.60 | 0.00 | 0.00 | ||
Maximum of Months | 996407.91 | 3243385.68 | 286.63 | 564710.83 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8749.86 | 718859.87 | 31-JAN-15:50 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 40605.16 | 1084421.26 | 28-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 120492.09 | 2248578.75 | 30-MAR-05:03 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 257869.10 | 2711416.62 | 03-APR-05:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 468687.18 | 3638253.25 | 31-MAY-03:02 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 704072.13 | 4190160.83 | 26-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 768636.82 | 4332760.77 | 27-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 858189.61 | 4327220.44 | 14-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 560482.09 | 4033142.99 | 27-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 238736.19 | 3395039.35 | 18-OCT-04:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80145.71 | 1896543.43 | 04-NOV-05:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 22338.05 | 1784218.57 | 13-DEC-06:03 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 345958.19 | 0.00 | ||||
Minimum of Months | 8749.86 | 718859.87 | 0.00 | 0.00 | ||
Maximum of Months | 858189.61 | 4332760.77 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 167227.08 | 420261.63 | 31-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 340960.61 | 858129.45 | 28-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 577447.12 | 1250528.13 | 30-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 890525.47 | 1523681.86 | 17-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 437428.51 | 961360.02 | 30-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 856147.77 | 1408051.73 | 06-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1148829.01 | 1769834.07 | 08-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1395774.08 | 1878069.76 | 01-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 518847.75 | 1036202.57 | 07-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 470672.21 | 1159829.27 | 10-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 541085.16 | 1034793.13 | 05-NOV-16:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 619572.40 | 1182296.85 | 12-DEC-14:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 665946.70 | 0.00 | ||||
Minimum of Months | 167227.08 | 420261.63 | 0.00 | 0.00 | ||
Maximum of Months | 1395774.08 | 1878069.76 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 14860.45 | 49748.26 | 26-JAN-12:35 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 14973.08 | 49704.19 | 02-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15328.52 | 48924.72 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13621.54 | 46281.64 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 13024.40 | 43153.19 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12357.15 | 39663.05 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 10969.10 | 36973.10 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11839.37 | 36862.36 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 11664.40 | 39124.33 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12488.54 | 42651.66 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13633.80 | 46038.58 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14030.32 | 48554.06 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 13222.78 | ||||
Minimum of Months | 0.00 | 0.00 | 10969.10 | 36862.36 | ||
Maximum of Months | 0.00 | 0.00 | 15328.52 | 49748.26 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8740.11 | 585716.84 | 31-JAN-15:50 | 3090.07 | 178679.33 | 14-JAN-04:42 |
February | 40713.47 | 1056961.35 | 28-FEB-13:20 | 2500.33 | 181730.19 | 01-FEB-07:20 |
March | 119904.10 | 2726888.03 | 30-MAR-15:20 | 1956.64 | 131491.02 | 22-MAR-12:20 |
April | 270379.82 | 2990626.19 | 04-APR-13:30 | 1148.08 | 120470.25 | 06-APR-18:00 |
May | 600764.79 | 4261116.14 | 31-MAY-12:40 | 141.95 | 111734.00 | 09-MAY-20:10 |
June | 1480711.40 | 5527364.99 | 23-JUN-12:10 | 86.67 | 39239.11 | 10-JUN-22:30 |
July | 1850441.03 | 5924986.93 | 07-JUL-12:20 | 0.10 | 1347.87 | 03-JUL-02:33 |
August | 2264496.55 | 6176701.56 | 10-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1001871.01 | 5467199.45 | 06-SEP-12:30 | 40.36 | 41371.92 | 18-SEP-06:50 |
October | 335493.07 | 4840762.12 | 18-OCT-16:00 | 966.78 | 121429.91 | 06-OCT-05:40 |
November | 80723.28 | 863281.99 | 02-NOV-13:50 | 1907.10 | 154707.89 | 22-NOV-11:10 |
December | 21694.83 | 801044.11 | 12-DEC-14:30 | 2328.51 | 155031.44 | 18-DEC-16:50 |
Annual Sum or Average | 677803.04 | 1173.92 | ||||
Minimum of Months | 8740.11 | 585716.84 | 0.00 | 0.00 | ||
Maximum of Months | 2264496.55 | 6176701.56 | 3090.07 | 181730.19 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149601E+11 | 0.81 | 9912.16 | 01-JAN-00:25 | 1.44 |
February | 0.133392E+11 | 0.80 | 9912.16 | 01-FEB-05:01 | 1.44 |
March | 0.158923E+11 | 0.86 | 9912.16 | 01-MAR-04:02 | 1.44 |
April | 0.144668E+11 | 0.81 | 9912.16 | 01-APR-04:03 | 1.44 |
May | 0.155128E+11 | 0.83 | 9912.16 | 01-MAY-03:02 | 1.43 |
June | 0.155993E+11 | 0.86 | 9912.16 | 01-JUN-03:02 | 1.43 |
July | 0.155070E+11 | 0.83 | 9912.16 | 01-JUL-03:02 | 1.43 |
August | 0.170704E+11 | 0.91 | 9912.16 | 01-AUG-03:02 | 1.43 |
September | 0.163282E+11 | 0.91 | 9912.16 | 01-SEP-03:02 | 1.43 |
October | 0.164144E+11 | 0.89 | 9912.16 | 01-OCT-21:50 | 1.42 |
November | 0.158782E+11 | 0.89 | 9912.16 | 01-NOV-03:02 | 1.44 |
December | 0.153103E+11 | 0.83 | 9912.16 | 01-DEC-04:02 | 1.44 |
Annual Sum or Average | 0.186279E+12 | 0.85 | |||
Minimum of Months | 0.133392E+11 | 0.80 | 9912.16 | 1.42 | |
Maximum of Months | 0.170704E+11 | 0.91 | 9912.16 | 1.44 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.427838E+10 | 0.32 | 13436.69 | 05-JAN-12:00 | 1.39 |
February | 0.490341E+10 | 0.37 | 14934.93 | 02-FEB-16:40 | 1.48 |
March | 0.812801E+10 | 0.48 | 17903.48 | 30-MAR-05:03 | 1.65 |
April | 0.965127E+10 | 0.55 | 20968.10 | 11-APR-15:33 | 1.83 |
May | 0.935758E+10 | 0.51 | 20968.10 | 15-MAY-13:40 | 1.82 |
June | 0.121280E+11 | 0.64 | 20968.10 | 02-JUN-15:10 | 1.82 |
July | 0.134205E+11 | 0.68 | 20968.10 | 03-JUL-05:02 | 1.82 |
August | 0.159098E+11 | 0.77 | 20968.10 | 08-AUG-05:02 | 1.82 |
September | 0.947181E+10 | 0.52 | 20968.10 | 05-SEP-05:03 | 1.82 |
October | 0.808396E+10 | 0.46 | 20968.10 | 18-OCT-05:03 | 1.82 |
November | 0.712264E+10 | 0.44 | 13194.57 | 06-NOV-16:20 | 1.37 |
December | 0.633009E+10 | 0.39 | 15737.14 | 13-DEC-06:03 | 1.52 |
Annual Sum or Average | 0.108786E+12 | 0.51 | |||
Minimum of Months | 0.427838E+10 | 0.32 | 13194.57 | 1.37 | |
Maximum of Months | 0.159098E+11 | 0.77 | 20968.10 | 1.83 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.334349E+11 | 0.33 | 136251.90 | 05-JAN-11:55 | 1.50 |
February | 0.358138E+11 | 0.35 | 136251.90 | 03-FEB-13:20 | 1.50 |
March | 0.539419E+11 | 0.40 | 118673.14 | 18-MAR-05:03 | 1.37 |
April | 0.635527E+11 | 0.43 | 206424.23 | 12-APR-14:40 | 1.93 |
May | 0.821157E+11 | 0.50 | 206424.23 | 15-MAY-14:05 | 1.93 |
June | 0.103021E+12 | 0.59 | 206424.23 | 02-JUN-13:40 | 1.93 |
July | 0.104345E+12 | 0.58 | 206424.23 | 06-JUL-03:02 | 1.92 |
August | 0.115055E+12 | 0.62 | 206424.23 | 03-AUG-03:02 | 1.92 |
September | 0.795036E+11 | 0.49 | 206424.23 | 16-SEP-05:03 | 1.93 |
October | 0.563773E+11 | 0.40 | 118790.91 | 10-OCT-05:03 | 1.36 |
November | 0.433129E+11 | 0.35 | 110561.55 | 18-NOV-06:03 | 1.31 |
December | 0.358618E+11 | 0.32 | 138744.17 | 16-DEC-06:02 | 1.51 |
Annual Sum or Average | 0.806336E+12 | 0.45 | |||
Minimum of Months | 0.334349E+11 | 0.32 | 110561.55 | 1.31 | |
Maximum of Months | 0.115055E+12 | 0.62 | 206424.23 | 1.93 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.384657E+10 | 0.37 | 4239.51 | 02-JAN-04:11 | 0.71 |
February | 0.341155E+10 | 0.35 | 6587.75 | 28-FEB-16:20 | 0.90 |
March | 0.428847E+10 | 0.34 | 12260.70 | 30-MAR-15:50 | 1.30 |
April | 0.537923E+10 | 0.37 | 20856.69 | 12-APR-14:30 | 1.83 |
May | 0.785033E+10 | 0.45 | 20856.69 | 15-MAY-15:10 | 1.82 |
June | 0.105839E+11 | 0.56 | 20856.69 | 02-JUN-14:20 | 1.82 |
July | 0.109597E+11 | 0.56 | 20856.69 | 05-JUL-05:03 | 1.82 |
August | 0.119873E+11 | 0.60 | 20856.69 | 10-AUG-03:02 | 1.82 |
September | 0.738967E+10 | 0.44 | 20856.69 | 27-SEP-05:03 | 1.82 |
October | 0.460939E+10 | 0.34 | 10902.86 | 02-OCT-15:20 | 1.21 |
November | 0.333572E+10 | 0.30 | 9060.18 | 03-NOV-05:03 | 1.08 |
December | 0.352213E+10 | 0.33 | 9060.18 | 13-DEC-06:03 | 1.08 |
Annual Sum or Average | 0.771640E+11 | 0.42 | |||
Minimum of Months | 0.333572E+10 | 0.30 | 4239.51 | 0.71 | |
Maximum of Months | 0.119873E+11 | 0.60 | 20856.69 | 1.83 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.976095E+11 | 1.40 | 36443.22 | 01-JAN-00:05 | 1.39 |
February | 0.881634E+11 | 1.40 | 36443.22 | 01-FEB-00:10 | 1.39 |
March | 0.976095E+11 | 1.39 | 36443.22 | 01-MAR-00:10 | 1.40 |
April | 0.944608E+11 | 1.39 | 36443.22 | 01-APR-00:10 | 1.39 |
May | 0.976095E+11 | 1.39 | 36443.22 | 01-MAY-00:02 | 1.39 |
June | 0.944608E+11 | 1.39 | 36443.22 | 01-JUN-00:10 | 1.39 |
July | 0.976095E+11 | 1.39 | 36443.22 | 01-JUL-00:10 | 1.39 |
August | 0.976095E+11 | 1.39 | 36443.22 | 01-AUG-00:03 | 1.39 |
September | 0.944608E+11 | 1.39 | 36443.22 | 01-SEP-00:02 | 1.39 |
October | 0.976095E+11 | 1.39 | 36443.22 | 01-OCT-00:10 | 1.39 |
November | 0.944608E+11 | 1.39 | 36443.22 | 01-NOV-00:10 | 1.40 |
December | 0.976095E+11 | 1.40 | 36443.22 | 01-DEC-00:10 | 1.39 |
Annual Sum or Average | 0.114927E+13 | 1.39 | |||
Minimum of Months | 0.881634E+11 | 1.39 | 36443.22 | 1.39 | |
Maximum of Months | 0.976095E+11 | 1.40 | 36443.22 | 1.40 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146625E+10 | 0.95 | 547.44 | 01-JAN-00:05 | 0.95 |
February | 0.132436E+10 | 0.95 | 547.44 | 01-FEB-00:10 | 0.95 |
March | 0.146625E+10 | 0.95 | 547.44 | 01-MAR-00:10 | 0.95 |
April | 0.141895E+10 | 0.95 | 547.44 | 01-APR-00:10 | 0.95 |
May | 0.146625E+10 | 0.95 | 547.44 | 01-MAY-00:02 | 0.95 |
June | 0.141895E+10 | 0.95 | 547.44 | 01-JUN-00:10 | 0.95 |
July | 0.146625E+10 | 0.95 | 547.44 | 01-JUL-00:10 | 0.95 |
August | 0.146625E+10 | 0.94 | 547.44 | 01-AUG-00:03 | 0.95 |
September | 0.141895E+10 | 0.95 | 547.44 | 01-SEP-00:02 | 0.95 |
October | 0.146625E+10 | 0.95 | 547.44 | 01-OCT-00:10 | 0.95 |
November | 0.141895E+10 | 0.95 | 547.44 | 01-NOV-00:10 | 0.95 |
December | 0.146625E+10 | 0.95 | 547.44 | 01-DEC-00:10 | 0.95 |
Annual Sum or Average | 0.172640E+11 | 0.95 | |||
Minimum of Months | 0.132436E+10 | 0.94 | 547.44 | 0.95 | |
Maximum of Months | 0.146625E+10 | 0.95 | 547.44 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139415E+11 | 0.95 | 5205.15 | 01-JAN-00:05 | 0.95 |
February | 0.125923E+11 | 0.95 | 5205.15 | 01-FEB-00:20 | 0.95 |
March | 0.139415E+11 | 0.95 | 5205.15 | 01-MAR-00:10 | 0.95 |
April | 0.134918E+11 | 0.95 | 5205.15 | 01-APR-00:10 | 0.95 |
May | 0.139415E+11 | 0.95 | 5205.15 | 01-MAY-00:02 | 0.95 |
June | 0.134918E+11 | 0.95 | 5205.15 | 01-JUN-00:10 | 0.95 |
July | 0.139415E+11 | 0.95 | 5205.15 | 01-JUL-00:10 | 0.95 |
August | 0.139415E+11 | 0.94 | 5205.15 | 01-AUG-00:03 | 0.95 |
September | 0.134918E+11 | 0.94 | 5205.15 | 01-SEP-00:02 | 0.95 |
October | 0.139415E+11 | 0.95 | 5205.15 | 01-OCT-00:10 | 0.95 |
November | 0.134918E+11 | 0.95 | 5205.15 | 01-NOV-00:10 | 0.95 |
December | 0.139415E+11 | 0.95 | 5205.15 | 01-DEC-00:10 | 0.95 |
Annual Sum or Average | 0.164150E+12 | 0.95 | |||
Minimum of Months | 0.125923E+11 | 0.94 | 5205.15 | 0.95 | |
Maximum of Months | 0.139415E+11 | 0.95 | 5205.15 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140993E+10 | 0.95 | 526.41 | 01-JAN-00:05 | 0.95 |
February | 0.127348E+10 | 0.95 | 526.41 | 01-FEB-00:10 | 0.95 |
March | 0.140993E+10 | 0.95 | 526.41 | 01-MAR-00:10 | 0.95 |
April | 0.136444E+10 | 0.95 | 526.41 | 01-APR-00:10 | 0.95 |
May | 0.140993E+10 | 0.95 | 526.41 | 01-MAY-00:02 | 0.95 |
June | 0.136444E+10 | 0.95 | 526.41 | 01-JUN-00:20 | 0.95 |
July | 0.140993E+10 | 0.95 | 526.41 | 01-JUL-00:10 | 0.95 |
August | 0.140993E+10 | 0.94 | 526.41 | 01-AUG-00:03 | 0.95 |
September | 0.136444E+10 | 0.94 | 526.41 | 01-SEP-00:02 | 0.95 |
October | 0.140993E+10 | 0.95 | 526.41 | 01-OCT-00:10 | 0.95 |
November | 0.136444E+10 | 0.95 | 526.41 | 01-NOV-00:10 | 0.95 |
December | 0.140993E+10 | 0.95 | 526.41 | 01-DEC-00:10 | 0.95 |
Annual Sum or Average | 0.166007E+11 | 0.95 | |||
Minimum of Months | 0.127348E+10 | 0.94 | 526.41 | 0.95 | |
Maximum of Months | 0.140993E+10 | 0.95 | 526.41 | 0.95 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.894547E+09 | 0.805092E+09 | 4779.05 | 09-JAN-06:01 | 4301.14 | 4301.14 | 47.83 | 10.07 |
February | 0.528670E+09 | 0.475803E+09 | 4757.53 | 13-FEB-06:01 | 4281.78 | 4281.78 | 48.78 | 9.91 |
March | 70803031.25 | 63722728.12 | 3094.32 | 22-MAR-05:03 | 2784.88 | 2784.88 | 32.67 | 4.27 |
April | 26664680.90 | 23998212.81 | 2397.34 | 06-APR-06:10 | 2157.61 | 2157.61 | 33.74 | 3.02 |
May | 15126795.22 | 13614115.70 | 764.88 | 11-MAY-06:10 | 688.39 | 688.39 | 31.20 | 0.82 |
June | 4444405.82 | 3999965.24 | 413.93 | 03-JUN-12:00 | 372.53 | 372.53 | 43.82 | 0.43 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 54.52 | 0.00 |
August | 262381.09 | 236142.99 | 203.80 | 25-AUG-13:50 | 183.42 | 183.42 | 52.90 | 0.21 |
September | 3208355.79 | 2887520.21 | 887.89 | 14-SEP-15:00 | 799.10 | 799.10 | 54.06 | 0.96 |
October | 34530718.89 | 31077647.00 | 2289.37 | 26-OCT-05:03 | 2060.44 | 2060.44 | 32.11 | 2.85 |
November | 0.134971E+09 | 0.121474E+09 | 3752.86 | 25-NOV-06:01 | 3377.58 | 3377.58 | 34.34 | 5.79 |
December | 0.396765E+09 | 0.357088E+09 | 4283.85 | 18-DEC-07:10 | 3855.46 | 3855.46 | 47.60 | 7.46 |
Annual Sum or Average | 0.210999E+10 | 0.189899E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.20 | 0.00 | |
Maximum of Months | 0.894547E+09 | 0.805092E+09 | 4779.05 | 4301.14 | 4301.14 | 54.52 | 10.07 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 8051891.26 | 7246702.13 | 445.44 | 31-JAN-15:50 | 400.89 | 400.89 | 8.51 | 20.70 |
February | 34802627.34 | 31322364.61 | 657.91 | 21-FEB-14:30 | 592.12 | 592.12 | 8.59 | 25.19 |
March | 0.197703E+09 | 0.177933E+09 | 7371.45 | 30-MAR-05:03 | 6634.30 | 6634.30 | 8.60 | 75.13 |
April | 0.671035E+09 | 0.603932E+09 | 10458.87 | 03-APR-05:03 | 9412.98 | 9412.98 | 8.69 | 86.82 |
May | 0.102979E+10 | 0.926807E+09 | 15433.93 | 31-MAY-03:02 | 13890.54 | 13890.54 | 8.16 | 101.66 |
June | 0.170076E+10 | 0.153069E+10 | 25869.23 | 15-JUN-05:03 | 23282.31 | 23282.31 | 7.82 | 124.79 |
July | 0.191115E+10 | 0.172003E+10 | 25869.23 | 10-JUL-05:03 | 23282.31 | 23282.31 | 8.00 | 124.79 |
August | 0.229711E+10 | 0.206740E+10 | 25869.23 | 07-AUG-05:03 | 23282.31 | 23282.31 | 7.65 | 124.79 |
September | 0.139564E+10 | 0.125608E+10 | 25869.23 | 27-SEP-05:03 | 23282.31 | 23282.31 | 7.65 | 124.79 |
October | 0.541396E+09 | 0.487256E+09 | 13974.54 | 18-OCT-04:03 | 12577.08 | 12577.08 | 7.97 | 97.68 |
November | 87243064.44 | 78518758.00 | 4132.98 | 04-NOV-05:02 | 3719.69 | 3719.69 | 8.45 | 58.76 |
December | 27358267.16 | 24622440.44 | 4673.64 | 13-DEC-06:03 | 4206.27 | 4206.27 | 8.52 | 61.96 |
Annual Sum or Average | 0.990204E+10 | 0.891184E+10 | ||||||
Minimum of Months | 8051891.26 | 7246702.13 | 445.44 | 400.89 | 400.89 | 7.65 | 20.70 | |
Maximum of Months | 0.229711E+10 | 0.206740E+10 | 25869.23 | 23282.31 | 23282.31 | 8.69 | 124.79 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.559733E+10 | 0.503759E+10 | 17805.09 | 02-JAN-07:20 | 16024.58 | 16024.58 | 8.42 | 124.79 |
February | 0.850104E+10 | 0.765094E+10 | 17805.09 | 01-FEB-06:03 | 16024.58 | 16024.58 | 8.45 | 124.79 |
March | 0.167316E+11 | 0.150585E+11 | 17805.09 | 01-MAR-05:10 | 16024.58 | 16024.58 | 8.47 | 124.79 |
April | 0.246894E+11 | 0.222205E+11 | 17805.09 | 01-APR-04:03 | 16024.58 | 16024.58 | 8.71 | 124.79 |
May | 0.302243E+11 | 0.272019E+11 | 17805.09 | 01-MAY-00:02 | 16024.58 | 16024.58 | 8.32 | 124.79 |
June | 0.355676E+11 | 0.320109E+11 | 17805.09 | 01-JUN-03:02 | 16024.58 | 16024.58 | 11.04 | 124.79 |
July | 0.408045E+11 | 0.367240E+11 | 17805.09 | 01-JUL-00:32 | 16024.58 | 16024.58 | 7.59 | 124.79 |
August | 0.439856E+11 | 0.395870E+11 | 17805.09 | 01-AUG-00:08 | 16024.58 | 16024.58 | 7.15 | 124.79 |
September | 0.306741E+11 | 0.276067E+11 | 17805.09 | 01-SEP-00:02 | 16024.58 | 16024.58 | 7.72 | 124.79 |
October | 0.196379E+11 | 0.176742E+11 | 17805.09 | 01-OCT-12:42 | 16024.58 | 16024.58 | 8.35 | 124.79 |
November | 0.129854E+11 | 0.116869E+11 | 17805.09 | 01-NOV-05:03 | 16024.58 | 16024.58 | 8.76 | 124.79 |
December | 0.558157E+10 | 0.502342E+10 | 17805.09 | 01-DEC-04:10 | 16024.58 | 16024.58 | 8.49 | 124.79 |
Annual Sum or Average | 0.274980E+12 | 0.247482E+12 | ||||||
Minimum of Months | 0.558157E+10 | 0.502342E+10 | 17805.09 | 16024.58 | 16024.58 | 7.15 | 124.79 | |
Maximum of Months | 0.439856E+11 | 0.395870E+11 | 17805.09 | 16024.58 | 16024.58 | 11.04 | 124.79 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.917267E+10 | 0.825540E+10 | 3424.68 | 01-JAN-00:05 | 3082.21 | 3082.21 | 21.57 | 14.30 |
February | 0.828499E+10 | 0.745649E+10 | 3424.68 | 01-FEB-00:10 | 3082.21 | 3082.21 | 24.31 | 14.30 |
March | 0.917267E+10 | 0.825540E+10 | 3424.68 | 01-MAR-00:10 | 3082.21 | 3082.21 | 28.10 | 14.30 |
April | 0.887678E+10 | 0.798910E+10 | 3424.68 | 01-APR-00:10 | 3082.21 | 3082.21 | 30.25 | 14.30 |
May | 0.917267E+10 | 0.825540E+10 | 3424.68 | 01-MAY-00:02 | 3082.21 | 3082.21 | 22.72 | 14.30 |
June | 0.887678E+10 | 0.798910E+10 | 3424.68 | 01-JUN-00:10 | 3082.21 | 3082.21 | 30.77 | 14.30 |
July | 0.917267E+10 | 0.825540E+10 | 3424.68 | 01-JUL-00:10 | 3082.21 | 3082.21 | 36.41 | 14.30 |
August | 0.917267E+10 | 0.825540E+10 | 3424.68 | 01-AUG-00:03 | 3082.21 | 3082.21 | 43.91 | 14.30 |
September | 0.887678E+10 | 0.798910E+10 | 3424.68 | 01-SEP-00:02 | 3082.21 | 3082.21 | 27.71 | 14.30 |
October | 0.917267E+10 | 0.825540E+10 | 3424.68 | 01-OCT-00:10 | 3082.21 | 3082.21 | 26.12 | 14.30 |
November | 0.887678E+10 | 0.798910E+10 | 3424.68 | 01-NOV-00:10 | 3082.21 | 3082.21 | 27.46 | 14.30 |
December | 0.917267E+10 | 0.825540E+10 | 3424.68 | 01-DEC-00:10 | 3082.21 | 3082.21 | 29.78 | 14.30 |
Annual Sum or Average | 0.108001E+12 | 0.972007E+11 | ||||||
Minimum of Months | 0.828499E+10 | 0.745649E+10 | 3424.68 | 3082.21 | 3082.21 | 21.57 | 14.30 | |
Maximum of Months | 0.917267E+10 | 0.825540E+10 | 3424.68 | 3082.21 | 3082.21 | 43.91 | 14.30 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:10 | 1.79 | 1.79 | 55.78 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:03 | 1.79 | 1.79 | 56.53 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 56.46 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 55.65 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 56.57 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:02 | 1.79 | 1.79 | 57.23 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 56.68 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 56.34 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 57.07 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.90 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 55.84 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:01 | 1.79 | 1.79 | 55.95 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.65 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 57.23 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.690884E+10 | 0.621796E+10 | 22004.80 | 31-JAN-15:50 | 19804.32 | 19804.32 | 23.01 | 73.21 |
February | 0.105598E+11 | 0.950382E+10 | 44002.88 | 28-FEB-15:40 | 39602.59 | 39602.59 | 22.79 | 146.41 |
March | 0.209851E+11 | 0.188866E+11 | 44093.22 | 30-MAR-15:20 | 39683.90 | 39683.90 | 25.56 | 146.41 |
April | 0.321832E+11 | 0.289649E+11 | 44109.15 | 04-APR-13:30 | 39698.24 | 39698.24 | 25.99 | 146.41 |
May | 0.424019E+11 | 0.381617E+11 | 44186.05 | 31-MAY-12:40 | 39767.44 | 39767.44 | 28.06 | 146.41 |
June | 0.580121E+11 | 0.522109E+11 | 44213.68 | 12-JUN-11:10 | 39792.31 | 39792.31 | 28.82 | 146.41 |
July | 0.661093E+11 | 0.594984E+11 | 44213.68 | 05-JUL-08:20 | 39792.31 | 39792.31 | 28.85 | 146.41 |
August | 0.732560E+11 | 0.659304E+11 | 44213.68 | 01-AUG-09:20 | 39792.31 | 39792.31 | 28.96 | 146.41 |
September | 0.465997E+11 | 0.419397E+11 | 44213.68 | 05-SEP-15:00 | 39792.31 | 39792.31 | 28.83 | 146.41 |
October | 0.266767E+11 | 0.240090E+11 | 44213.68 | 18-OCT-15:00 | 39792.31 | 39792.31 | 28.84 | 146.41 |
November | 0.160172E+11 | 0.144155E+11 | 22019.16 | 02-NOV-13:50 | 19817.25 | 19817.25 | 23.92 | 73.21 |
December | 0.688471E+10 | 0.619623E+10 | 22015.94 | 12-DEC-14:30 | 19814.35 | 19814.35 | 23.72 | 73.21 |
Annual Sum or Average | 0.406594E+12 | 0.365935E+12 | ||||||
Minimum of Months | 0.688471E+10 | 0.619623E+10 | 22004.80 | 19804.32 | 19804.32 | 22.79 | 73.21 | |
Maximum of Months | 0.732560E+11 | 0.659304E+11 | 44213.68 | 39792.31 | 39792.31 | 28.96 | 146.41 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 30.99 | 30.99 | 70766.49 | 1538862.95 | 02-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 23.40 | 23.40 | 46340.84 | 1377556.71 | 13-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.23 | 25.23 | 6022.53 | 845252.55 | 22-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 37.28 | 37.28 | 1891.79 | 594456.89 | 06-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 29.55 | 29.55 | 813.76 | 167072.52 | 11-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.24 | 56.24 | 223.30 | 64231.07 | 03-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.52 | 54.52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 54.52 | 54.52 | 10.93 | 23113.13 | 25-AUG-13:50 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 52.28 | 52.28 | 139.85 | 101460.30 | 14-SEP-15:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 47.50 | 47.50 | 2998.34 | 578351.45 | 26-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.21 | 25.21 | 11964.10 | 1127967.28 | 25-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 46.09 | 46.09 | 32871.49 | 1176088.85 | 26-DEC-05:01 |
Annual Sum or Average | 0.00 | 14361.93 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.40 | 23.40 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 56.24 | 56.24 | 70766.49 | 1538862.95 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 17348.96 | 1032955.60 | 31-JAN-15:50 | 9.66 | 8.66 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 70101.72 | 1584029.14 | 28-FEB-14:50 | 9.98 | 8.35 | 46.17 | 231201.10 | 27-FEB-04:02 |
March | 189690.67 | 1736171.16 | 30-MAR-14:40 | 10.02 | 6.70 | 112.39 | 250873.72 | 12-MAR-09:02 |
April | 362501.79 | 1999982.69 | 17-APR-14:20 | 10.52 | 6.70 | 38.53 | 82802.49 | 13-APR-23:53 |
May | 615987.90 | 2228548.90 | 31-MAY-03:02 | 11.83 | 7.57 | 286.63 | 564710.83 | 21-MAY-07:00 |
June | 855749.64 | 2713352.57 | 15-JUN-05:03 | 12.57 | 7.38 | 130.58 | 293653.70 | 10-JUN-04:05 |
July | 916874.13 | 2764532.01 | 27-JUL-05:02 | 12.68 | 7.39 | 5.42 | 89687.98 | 01-JUL-20:22 |
August | 996407.91 | 3243385.68 | 24-AUG-05:04 | 13.48 | 7.80 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 699543.03 | 2550798.41 | 05-SEP-05:03 | 12.33 | 7.45 | 23.28 | 143386.02 | 24-SEP-07:50 |
October | 317005.45 | 1958930.45 | 18-OCT-04:03 | 11.46 | 7.71 | 152.84 | 265117.07 | 08-OCT-08:32 |
November | 136135.83 | 1476152.59 | 02-NOV-13:50 | 10.03 | 8.62 | 27.86 | 222313.15 | 27-NOV-04:02 |
December | 38496.39 | 1363127.86 | 12-DEC-14:30 | 9.89 | 8.58 | 4.21 | 37582.59 | 11-DEC-10:05 |
Annual Sum or Average | 436786.06 | 69.33 | ||||||
Minimum of Months | 17348.96 | 1032955.60 | 9.66 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 996407.91 | 3243385.68 | 13.48 | 8.66 | 286.63 | 564710.83 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8749.86 | 718859.87 | 31-JAN-15:50 | 15.00 | 8.64 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 40605.16 | 1084421.26 | 28-FEB-15:00 | 17.79 | 8.06 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 120492.09 | 2248578.75 | 30-MAR-05:03 | 13.85 | 8.84 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 257869.10 | 2711416.62 | 03-APR-05:03 | 14.16 | 8.92 | 0.00 | 0.00 | 01-APR-00:10 |
May | 468687.18 | 3638253.25 | 31-MAY-03:02 | 15.25 | 7.81 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 704072.13 | 4190160.83 | 26-JUN-05:02 | 14.85 | 7.60 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 768636.82 | 4332760.77 | 27-JUL-05:02 | 15.00 | 7.87 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 858189.61 | 4327220.44 | 14-AUG-05:02 | 14.99 | 7.69 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 560482.09 | 4033142.99 | 27-SEP-05:03 | 14.42 | 7.35 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 238736.19 | 3395039.35 | 18-OCT-04:03 | 15.01 | 7.76 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80145.71 | 1896543.43 | 04-NOV-05:02 | 14.41 | 8.75 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 22338.05 | 1784218.57 | 13-DEC-06:03 | 13.58 | 8.82 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 345958.19 | 0.00 | ||||||
Minimum of Months | 8749.86 | 718859.87 | 13.58 | 7.35 | 0.00 | 0.00 | ||
Maximum of Months | 858189.61 | 4332760.77 | 17.79 | 8.92 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 167227.08 | 420261.63 | 31-JAN-15:00 | 26.75 | 22.84 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 340960.61 | 858129.45 | 28-FEB-15:00 | 35.38 | 28.23 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 577447.12 | 1250528.13 | 30-MAR-16:00 | 42.99 | 32.57 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 890525.47 | 1523681.86 | 17-APR-16:00 | 48.23 | 35.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 437428.51 | 961360.02 | 30-MAY-15:00 | 37.39 | 32.72 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 856147.77 | 1408051.73 | 06-JUN-15:00 | 46.02 | 38.06 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1148829.01 | 1769834.07 | 08-JUL-16:00 | 52.91 | 41.84 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1395774.08 | 1878069.76 | 01-AUG-16:10 | 54.96 | 41.35 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 518847.75 | 1036202.57 | 07-SEP-16:00 | 38.85 | 33.93 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 470672.21 | 1159829.27 | 10-OCT-16:00 | 41.24 | 33.52 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 541085.16 | 1034793.13 | 05-NOV-16:00 | 38.82 | 28.91 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 619572.40 | 1182296.85 | 12-DEC-14:50 | 41.68 | 28.72 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 665946.70 | 0.00 | ||||||
Minimum of Months | 167227.08 | 420261.63 | 26.75 | 22.84 | 0.00 | 0.00 | ||
Maximum of Months | 1395774.08 | 1878069.76 | 54.96 | 41.84 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.88 | 56.88 | 14860.45 | 49748.26 | 26-JAN-12:35 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.11 | 57.11 | 14973.08 | 49704.19 | 02-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.04 | 57.04 | 15328.52 | 48924.72 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.24 | 56.24 | 13621.54 | 46281.64 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 57.28 | 57.28 | 13024.40 | 43153.19 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.61 | 57.61 | 12357.15 | 39663.05 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.08 | 57.08 | 10969.10 | 36973.10 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 56.76 | 56.76 | 11839.37 | 36862.36 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 57.46 | 57.46 | 11664.40 | 39124.33 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.67 | 57.67 | 12488.54 | 42651.66 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.36 | 56.36 | 13633.80 | 46038.58 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.41 | 56.41 | 14030.32 | 48554.06 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 13222.78 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.24 | 56.24 | 10969.10 | 36862.36 | ||
Maximum of Months | 0.00 | 0.00 | 57.67 | 57.67 | 15328.52 | 49748.26 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8740.11 | 585716.84 | 31-JAN-15:50 | 23.01 | 21.10 | 3090.07 | 178679.33 | 14-JAN-04:42 |
February | 40713.47 | 1056961.35 | 28-FEB-13:20 | 24.55 | 21.10 | 2500.33 | 181730.19 | 01-FEB-07:20 |
March | 119904.10 | 2726888.03 | 30-MAR-15:20 | 25.56 | 21.74 | 1956.64 | 131491.02 | 22-MAR-12:20 |
April | 270379.82 | 2990626.19 | 04-APR-13:30 | 25.99 | 22.98 | 1148.08 | 120470.25 | 06-APR-18:00 |
May | 600764.79 | 4261116.14 | 31-MAY-12:40 | 28.06 | 24.90 | 141.95 | 111734.00 | 09-MAY-20:10 |
June | 1480711.40 | 5527364.99 | 23-JUN-12:10 | 30.13 | 26.92 | 86.67 | 39239.11 | 10-JUN-22:30 |
July | 1850441.03 | 5924986.93 | 07-JUL-12:20 | 30.78 | 27.46 | 0.10 | 1347.87 | 03-JUL-02:33 |
August | 2264496.55 | 6176701.56 | 10-AUG-16:00 | 31.19 | 27.75 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1001871.01 | 5467199.45 | 06-SEP-12:30 | 30.03 | 26.63 | 40.36 | 41371.92 | 18-SEP-06:50 |
October | 335493.07 | 4840762.12 | 18-OCT-16:00 | 29.01 | 25.91 | 966.78 | 121429.91 | 06-OCT-05:40 |
November | 80723.28 | 863281.99 | 02-NOV-13:50 | 23.92 | 21.10 | 1907.10 | 154707.89 | 22-NOV-11:10 |
December | 21694.83 | 801044.11 | 12-DEC-14:30 | 23.72 | 21.10 | 2328.51 | 155031.44 | 18-DEC-16:50 |
Annual Sum or Average | 677803.04 | 1173.92 | ||||||
Minimum of Months | 8740.11 | 585716.84 | 23.01 | 21.10 | 0.00 | 0.00 | ||
Maximum of Months | 2264496.55 | 6176701.56 | 31.19 | 27.75 | 3090.07 | 181730.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.348422E+10 | 0.00 | 0.198280E+10 | 0.427838E+10 | 0.00 | 0.00 |
February | 0.161148E+10 | 0.00 | 0.848749E+10 | 0.490341E+10 | 0.00 | 0.00 |
March | 0.194467E+09 | 0.00 | 0.270838E+11 | 0.812801E+10 | 0.00 | 0.00 |
April | 0.295920E+09 | 0.00 | 0.593506E+11 | 0.965127E+10 | 0.00 | 0.00 |
May | 0.171670E+09 | 0.00 | 0.948286E+11 | 0.935758E+10 | 0.00 | 0.00 |
June | 46717691.54 | 0.00 | 0.149290E+12 | 0.121280E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.177982E+12 | 0.134205E+11 | 0.00 | 0.00 |
August | 1509395.83 | 0.00 | 0.207460E+12 | 0.159098E+11 | 0.00 | 0.00 |
September | 29117668.01 | 0.00 | 0.113116E+12 | 0.947181E+10 | 0.00 | 0.00 |
October | 97739137.55 | 0.00 | 0.517056E+11 | 0.808396E+10 | 0.00 | 0.00 |
November | 0.392904E+09 | 0.00 | 0.183662E+11 | 0.712264E+10 | 0.00 | 0.00 |
December | 0.934958E+09 | 0.00 | 0.569561E+10 | 0.633009E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.726070E+10 | 0.00 | 0.915349E+12 | 0.108786E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.198280E+10 | 0.427838E+10 | 0.00 | 0.00 |
Maximum of Months | 0.348422E+10 | 0.00 | 0.207460E+12 | 0.159098E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.153541E+12 | 0.00 | 0.144249E+11 | 0.334349E+11 | 0.00 | 0.00 |
February | 0.920222E+11 | 0.00 | 0.633944E+11 | 0.358138E+11 | 0.00 | 0.00 |
March | 0.127406E+11 | 0.00 | 0.201860E+12 | 0.539419E+11 | 0.00 | 0.00 |
April | 0.370097E+10 | 0.00 | 0.429048E+12 | 0.635527E+11 | 0.00 | 0.00 |
May | 0.174408E+10 | 0.00 | 0.830103E+12 | 0.821157E+11 | 0.00 | 0.00 |
June | 0.514811E+09 | 0.00 | 0.126985E+13 | 0.103021E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.144371E+13 | 0.104345E+12 | 0.00 | 0.00 |
August | 30192064.67 | 0.00 | 0.162546E+13 | 0.115055E+12 | 0.00 | 0.00 |
September | 0.334371E+09 | 0.00 | 0.974399E+12 | 0.795036E+11 | 0.00 | 0.00 |
October | 0.595775E+10 | 0.00 | 0.403308E+12 | 0.563773E+11 | 0.00 | 0.00 |
November | 0.242797E+11 | 0.00 | 0.125975E+12 | 0.433129E+11 | 0.00 | 0.00 |
December | 0.692005E+11 | 0.00 | 0.349632E+11 | 0.358618E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.364066E+12 | 0.00 | 0.741648E+13 | 0.806336E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.144249E+11 | 0.334349E+11 | 0.00 | 0.00 |
Maximum of Months | 0.153541E+12 | 0.00 | 0.162546E+13 | 0.115055E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.343036E+11 | 0.00 | 0.133325E+10 | 0.384657E+10 | 0.00 | 0.00 |
February | 0.194927E+11 | 0.00 | 0.549883E+10 | 0.341155E+10 | 0.00 | 0.00 |
March | 0.329092E+10 | 0.00 | 0.194692E+11 | 0.428847E+10 | 0.00 | 0.00 |
April | 0.993147E+09 | 0.00 | 0.440849E+11 | 0.537923E+10 | 0.00 | 0.00 |
May | 0.146769E+09 | 0.00 | 0.897048E+11 | 0.785033E+10 | 0.00 | 0.00 |
June | 33053327.54 | 0.00 | 0.140246E+12 | 0.105839E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.159566E+12 | 0.109597E+11 | 0.00 | 0.00 |
August | 9937221.65 | 0.00 | 0.178030E+12 | 0.119873E+11 | 0.00 | 0.00 |
September | 29083842.77 | 0.00 | 0.100559E+12 | 0.738967E+10 | 0.00 | 0.00 |
October | 0.216332E+10 | 0.00 | 0.394586E+11 | 0.460939E+10 | 0.00 | 0.00 |
November | 0.649711E+10 | 0.00 | 0.107436E+11 | 0.333572E+10 | 0.00 | 0.00 |
December | 0.188372E+11 | 0.00 | 0.298258E+10 | 0.352213E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.857968E+11 | 0.00 | 0.791677E+12 | 0.771640E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.133325E+10 | 0.333572E+10 | 0.00 | 0.00 |
Maximum of Months | 0.343036E+11 | 0.00 | 0.178030E+12 | 0.119873E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.654960E+09 | 0.149601E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.429000E+10 | 0.133392E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.133790E+11 | 0.158923E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.281709E+11 | 0.144668E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.509565E+11 | 0.155128E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.871638E+11 | 0.155993E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.997131E+11 | 0.155070E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.119852E+12 | 0.170704E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.740994E+11 | 0.163282E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.326725E+11 | 0.164144E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.105825E+11 | 0.158782E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.304282E+10 | 0.153103E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.524577E+12 | 0.186279E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.654960E+09 | 0.133392E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.119852E+12 | 0.170704E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.404646E+12 | 0.181903E+12 | 0.00 | 0.97 |
February | 0.00 | 0.00 | 0.639183E+12 | 0.215231E+12 | 0.00 | 0.68 |
March | 0.00 | 0.00 | 0.102037E+13 | 0.299463E+12 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.129836E+13 | 0.362296E+12 | 0.00 | 0.11 |
May | 0.00 | 0.00 | 0.438922E+12 | 0.195826E+12 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.754315E+12 | 0.275965E+12 | 0.00 | 0.01 |
July | 0.00 | 0.00 | 0.111372E+13 | 0.371066E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.143019E+13 | 0.447145E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.438947E+12 | 0.195645E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.735301E+12 | 0.248744E+12 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.989775E+12 | 0.287228E+12 | 0.00 | 0.45 |
December | 0.00 | 0.00 | 0.130454E+13 | 0.338827E+12 | 0.00 | 0.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.105683E+14 | 0.341934E+13 | 0.00 | 3.33 |
Minimum of Months | 0.00 | 0.00 | 0.404646E+12 | 0.181903E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.143019E+13 | 0.447145E+12 | 0.00 | 0.97 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.491832E+10 | 0.250458E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.109099E+11 | 0.350729E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.194957E+11 | 0.530862E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.254919E+11 | 0.663078E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.789224E+10 | 0.321063E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.146633E+11 | 0.489294E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.220679E+11 | 0.679694E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.289697E+11 | 0.850773E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.793216E+10 | 0.322310E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.136019E+11 | 0.423215E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.186838E+11 | 0.505368E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.248177E+11 | 0.607866E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.199444E+12 | 0.599471E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.491832E+10 | 0.250458E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.289697E+11 | 0.850773E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.209589E+11 | 0.185723E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.850732E+11 | 0.298687E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.176434E+12 | 0.489334E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.239196E+12 | 0.625222E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.719954E+11 | 0.299253E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.139063E+12 | 0.464590E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.210382E+12 | 0.647571E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.275718E+12 | 0.809515E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.717880E+11 | 0.298996E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.120042E+12 | 0.385499E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.163777E+12 | 0.456368E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.213329E+12 | 0.540762E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.178776E+13 | 0.550152E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.209589E+11 | 0.185723E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.275718E+12 | 0.809515E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.904210E+09 | 0.161046E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.695460E+10 | 0.270125E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.167064E+11 | 0.474787E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.234774E+11 | 0.619923E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.710425E+10 | 0.299446E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.139927E+11 | 0.468671E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.211644E+11 | 0.652786E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.277098E+11 | 0.815108E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.702885E+10 | 0.297904E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.111566E+11 | 0.371820E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.149326E+11 | 0.432464E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.191942E+11 | 0.506452E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.170326E+12 | 0.537053E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.904210E+09 | 0.161046E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.277098E+11 | 0.815108E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.427838E+10 | 0.198280E+10 | 0.348422E+10 | 0.245134E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.490341E+10 | 0.848749E+10 | 0.161148E+10 | 0.124114E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.812801E+10 | 0.270838E+11 | 0.194467E+09 | 0.144332E+10 | 0.102544E+09 | 0.00 | 0.00 | 0.00 |
April | 0.965127E+10 | 0.593506E+11 | 0.295920E+09 | 0.367470E+09 | 0.508830E+09 | 0.00 | 0.00 | 0.00 |
May | 0.935758E+10 | 0.948286E+11 | 0.171670E+09 | 24039215.86 | 0.356452E+10 | 0.00 | 0.00 | 0.00 |
June | 0.121280E+11 | 0.149290E+12 | 46717691.54 | 0.00 | 0.216615E+11 | 0.00 | 0.00 | 0.00 |
July | 0.134205E+11 | 0.177982E+12 | 0.00 | 0.00 | 0.296588E+11 | 0.00 | 0.00 | 0.00 |
August | 0.159098E+11 | 0.207460E+12 | 1509395.83 | 0.00 | 0.370630E+11 | 0.00 | 0.00 | 0.00 |
September | 0.947181E+10 | 0.113116E+12 | 29117668.01 | 0.00 | 0.101394E+11 | 0.00 | 0.00 | 0.00 |
October | 0.808396E+10 | 0.517056E+11 | 97739137.55 | 0.577703E+09 | 0.196621E+10 | 0.00 | 0.00 | 0.00 |
November | 0.712264E+10 | 0.183662E+11 | 0.392904E+09 | 0.255648E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.633009E+10 | 0.569561E+10 | 0.934958E+09 | 0.618246E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108786E+12 | 0.915349E+12 | 0.726070E+10 | 0.480762E+11 | 0.104665E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427838E+10 | 0.198280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159098E+11 | 0.207460E+12 | 0.348422E+10 | 0.245134E+11 | 0.370630E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.334349E+11 | 0.144251E+11 | 0.153541E+12 | 0.335979E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358138E+11 | 0.633944E+11 | 0.920222E+11 | 0.176997E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.539419E+11 | 0.201860E+12 | 0.127406E+11 | 0.336610E+11 | 0.131049E+10 | 0.00 | 0.00 | 0.00 |
April | 0.635527E+11 | 0.429048E+12 | 0.370097E+10 | 0.104265E+11 | 0.504137E+10 | 0.00 | 0.00 | 0.00 |
May | 0.821157E+11 | 0.830103E+12 | 0.174408E+10 | 0.657557E+09 | 0.360079E+11 | 0.00 | 0.00 | 0.00 |
June | 0.103021E+12 | 0.126985E+13 | 0.514811E+09 | 0.00 | 0.214824E+12 | 0.00 | 0.00 | 0.00 |
July | 0.104345E+12 | 0.144371E+13 | 0.00 | 0.00 | 0.291620E+12 | 0.00 | 0.00 | 0.00 |
August | 0.115055E+12 | 0.162546E+13 | 30192064.67 | 0.00 | 0.359739E+12 | 0.00 | 0.00 | 0.00 |
September | 0.795036E+11 | 0.974399E+12 | 0.334371E+09 | 0.00 | 0.102623E+12 | 0.00 | 0.00 | 0.00 |
October | 0.563773E+11 | 0.403308E+12 | 0.595775E+10 | 0.181913E+11 | 0.198782E+11 | 0.00 | 0.00 | 0.00 |
November | 0.433129E+11 | 0.125975E+12 | 0.242797E+11 | 0.616430E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358618E+11 | 0.349632E+11 | 0.692005E+11 | 0.144933E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.806336E+12 | 0.741648E+13 | 0.364066E+12 | 0.782488E+12 | 0.103104E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.334349E+11 | 0.144251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115055E+12 | 0.162546E+13 | 0.153541E+12 | 0.335979E+12 | 0.359739E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.384657E+10 | 0.133325E+10 | 0.343036E+11 | 0.367266E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.341155E+10 | 0.549883E+10 | 0.194927E+11 | 0.209871E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.428847E+10 | 0.194692E+11 | 0.329092E+10 | 0.605439E+10 | 85578573.62 | 0.00 | 0.00 | 0.00 |
April | 0.537923E+10 | 0.440849E+11 | 0.993147E+09 | 0.163417E+10 | 0.259226E+09 | 0.00 | 0.00 | 0.00 |
May | 0.785033E+10 | 0.897048E+11 | 0.146769E+09 | 0.127897E+09 | 0.274562E+10 | 0.00 | 0.00 | 0.00 |
June | 0.105839E+11 | 0.140246E+12 | 33053327.54 | 1479476.81 | 0.201217E+11 | 0.00 | 0.00 | 0.00 |
July | 0.109597E+11 | 0.159566E+12 | 0.00 | 0.00 | 0.280225E+11 | 0.00 | 0.00 | 0.00 |
August | 0.119873E+11 | 0.178030E+12 | 9937221.65 | 0.00 | 0.347742E+11 | 0.00 | 0.00 | 0.00 |
September | 0.738967E+10 | 0.100559E+12 | 29083842.77 | 4118484.68 | 0.960337E+10 | 0.00 | 0.00 | 0.00 |
October | 0.460939E+10 | 0.394586E+11 | 0.216332E+10 | 0.326652E+10 | 0.145475E+10 | 0.00 | 0.00 | 0.00 |
November | 0.333572E+10 | 0.107436E+11 | 0.649711E+10 | 0.958046E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352213E+10 | 0.298258E+10 | 0.188372E+11 | 0.173364E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.771640E+11 | 0.791677E+12 | 0.857968E+11 | 0.957192E+11 | 0.970670E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.333572E+10 | 0.133325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119873E+11 | 0.178030E+12 | 0.343036E+11 | 0.367266E+11 | 0.347742E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149601E+11 | 0.654960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133392E+11 | 0.429000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158923E+11 | 0.133790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144668E+11 | 0.281709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155128E+11 | 0.509565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155993E+11 | 0.871638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155070E+11 | 0.997131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170704E+11 | 0.119852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163282E+11 | 0.740994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164144E+11 | 0.326725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158782E+11 | 0.105825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153103E+11 | 0.304282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186279E+12 | 0.524577E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133392E+11 | 0.654960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170704E+11 | 0.119852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.976095E+11 | 0.322966E+12 | 0.00 | 0.00 | 0.00 | 0.260185E+10 | 0.00 | 0.00 |
February | 0.881634E+11 | 0.513952E+12 | 0.00 | 0.00 | 0.00 | 0.182752E+10 | 0.00 | 0.00 |
March | 0.976095E+11 | 0.819449E+12 | 0.00 | 0.00 | 0.00 | 0.930679E+09 | 0.00 | 0.00 |
April | 0.944608E+11 | 0.103082E+13 | 0.00 | 0.00 | 0.00 | 0.294609E+09 | 0.00 | 0.00 |
May | 0.976095E+11 | 0.340757E+12 | 0.00 | 0.00 | 0.00 | 51866632.71 | 0.00 | 0.00 |
June | 0.944608E+11 | 0.572826E+12 | 0.00 | 0.00 | 0.00 | 14555348.00 | 0.00 | 0.00 |
July | 0.976095E+11 | 0.840267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.976095E+11 | 0.108066E+13 | 0.00 | 0.00 | 0.00 | 372297.87 | 0.00 | 0.00 |
September | 0.944608E+11 | 0.337763E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.976095E+11 | 0.584208E+12 | 0.00 | 0.00 | 0.00 | 40724997.87 | 0.00 | 0.00 |
November | 0.944608E+11 | 0.798227E+12 | 0.00 | 0.00 | 0.00 | 0.121317E+10 | 0.00 | 0.00 |
December | 0.976095E+11 | 0.106526E+13 | 0.00 | 0.00 | 0.00 | 0.193011E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.114927E+13 | 0.830716E+13 | 0.00 | 0.00 | 0.00 | 0.890546E+10 | 0.00 | 0.00 |
Minimum of Months | 0.881634E+11 | 0.322966E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.976095E+11 | 0.108066E+13 | 0.00 | 0.00 | 0.00 | 0.260185E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146625E+10 | 0.388000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132436E+10 | 0.872691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146625E+10 | 0.156533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141895E+10 | 0.202801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146625E+10 | 0.614787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141895E+10 | 0.111893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146625E+10 | 0.167372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146625E+10 | 0.219282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141895E+10 | 0.612801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146625E+10 | 0.108360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141895E+10 | 0.150491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146625E+10 | 0.202053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172640E+11 | 0.156761E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132436E+10 | 0.388000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146625E+10 | 0.219282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139415E+11 | 0.163281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125923E+11 | 0.677968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139415E+11 | 0.141442E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134918E+11 | 0.190165E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139415E+11 | 0.560115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134918E+11 | 0.106096E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139415E+11 | 0.159566E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139415E+11 | 0.208708E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134918E+11 | 0.553801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139415E+11 | 0.954332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134918E+11 | 0.131632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139415E+11 | 0.173194E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164150E+12 | 0.140175E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125923E+11 | 0.163281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139415E+11 | 0.208708E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140993E+10 | 0.703677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127348E+10 | 0.552683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140993E+10 | 0.133685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136444E+10 | 0.186427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140993E+10 | 0.551972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136444E+10 | 0.106704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140993E+10 | 0.160464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140993E+10 | 0.209686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136444E+10 | 0.541425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140993E+10 | 0.884832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136444E+10 | 0.119724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140993E+10 | 0.155396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166007E+11 | 0.133221E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127348E+10 | 0.703677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140993E+10 | 0.209686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.427838E+10 | 0.348422E+10 | 0.198280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.490341E+10 | 0.161148E+10 | 0.848749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.812801E+10 | 0.194467E+09 | 0.270838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.965127E+10 | 0.295920E+09 | 0.593506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.935758E+10 | 0.171670E+09 | 0.948286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121280E+11 | 46717691.54 | 0.149290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134205E+11 | 0.00 | 0.177982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159098E+11 | 1509395.83 | 0.207460E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.947181E+10 | 29117668.01 | 0.113116E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.808396E+10 | 97739137.55 | 0.517056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.712264E+10 | 0.392904E+09 | 0.183662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.633009E+10 | 0.934958E+09 | 0.569561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108786E+12 | 0.726070E+10 | 0.915349E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427838E+10 | 0.00 | 0.198280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159098E+11 | 0.348422E+10 | 0.207460E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.334349E+11 | 0.153541E+12 | 0.144249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358138E+11 | 0.920222E+11 | 0.633944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.539419E+11 | 0.127406E+11 | 0.201860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.635527E+11 | 0.370097E+10 | 0.429048E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.821157E+11 | 0.174408E+10 | 0.830103E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103021E+12 | 0.514811E+09 | 0.126985E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104345E+12 | 0.00 | 0.144371E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115055E+12 | 30192064.67 | 0.162546E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.795036E+11 | 0.334371E+09 | 0.974399E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.563773E+11 | 0.595775E+10 | 0.403308E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.433129E+11 | 0.242797E+11 | 0.125975E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358618E+11 | 0.692005E+11 | 0.349632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.806336E+12 | 0.364066E+12 | 0.741648E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.334349E+11 | 0.00 | 0.144249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115055E+12 | 0.153541E+12 | 0.162546E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.384657E+10 | 0.343036E+11 | 0.133325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.341155E+10 | 0.194927E+11 | 0.549883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.428847E+10 | 0.329092E+10 | 0.194692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.537923E+10 | 0.993147E+09 | 0.440849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.785033E+10 | 0.146769E+09 | 0.897048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105839E+11 | 33053327.54 | 0.140246E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109597E+11 | 0.00 | 0.159566E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119873E+11 | 9937221.65 | 0.178030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.738967E+10 | 29083842.77 | 0.100559E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.460939E+10 | 0.216332E+10 | 0.394586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.333572E+10 | 0.649711E+10 | 0.107436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352213E+10 | 0.188372E+11 | 0.298258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.771640E+11 | 0.857968E+11 | 0.791677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.333572E+10 | 0.00 | 0.133325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119873E+11 | 0.343036E+11 | 0.178030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149601E+11 | 0.00 | 0.654960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133392E+11 | 0.00 | 0.429000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158923E+11 | 0.00 | 0.133790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144668E+11 | 0.00 | 0.281709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155128E+11 | 0.00 | 0.509565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155993E+11 | 0.00 | 0.871638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155070E+11 | 0.00 | 0.997131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170704E+11 | 0.00 | 0.119852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163282E+11 | 0.00 | 0.740994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164144E+11 | 0.00 | 0.326725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158782E+11 | 0.00 | 0.105825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153103E+11 | 0.00 | 0.304282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186279E+12 | 0.00 | 0.524577E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133392E+11 | 0.00 | 0.654960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170704E+11 | 0.00 | 0.119852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.976095E+11 | 0.00 | 0.404646E+12 | 0.00 | 0.816798E+11 | 0.00 | 0.00 | 0.00 | 0.261356E+10 | 0.00 | 0.00 | 0.00 |
February | 0.881634E+11 | 0.00 | 0.639183E+12 | 0.00 | 0.125231E+12 | 0.00 | 0.00 | 0.00 | 0.183575E+10 | 0.00 | 0.00 | 0.00 |
March | 0.976095E+11 | 0.00 | 0.102037E+13 | 0.00 | 0.200918E+12 | 0.00 | 0.00 | 0.00 | 0.934868E+09 | 0.00 | 0.00 | 0.00 |
April | 0.944608E+11 | 0.00 | 0.129836E+13 | 0.00 | 0.267539E+12 | 0.00 | 0.00 | 0.00 | 0.295935E+09 | 0.00 | 0.00 | 0.00 |
May | 0.976095E+11 | 0.00 | 0.438922E+12 | 0.00 | 0.981646E+11 | 0.00 | 0.00 | 0.00 | 52100105.45 | 0.00 | 0.00 | 0.00 |
June | 0.944608E+11 | 0.00 | 0.754315E+12 | 0.00 | 0.181490E+12 | 0.00 | 0.00 | 0.00 | 14620867.52 | 0.00 | 0.00 | 0.00 |
July | 0.976095E+11 | 0.00 | 0.111372E+13 | 0.00 | 0.273456E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.976095E+11 | 0.00 | 0.143019E+13 | 0.00 | 0.349535E+12 | 0.00 | 0.00 | 0.00 | 373973.73 | 0.00 | 0.00 | 0.00 |
September | 0.944608E+11 | 0.00 | 0.438947E+12 | 0.00 | 0.101184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.976095E+11 | 0.00 | 0.735301E+12 | 0.00 | 0.151093E+12 | 0.00 | 0.00 | 0.00 | 40908317.60 | 0.00 | 0.00 | 0.00 |
November | 0.944608E+11 | 0.00 | 0.989775E+12 | 0.00 | 0.191548E+12 | 0.00 | 0.00 | 0.00 | 0.121863E+10 | 0.00 | 0.00 | 0.00 |
December | 0.976095E+11 | 0.00 | 0.130454E+13 | 0.00 | 0.239279E+12 | 0.00 | 0.00 | 0.00 | 0.193880E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114927E+13 | 0.00 | 0.105683E+14 | 0.00 | 0.226112E+13 | 0.00 | 0.00 | 0.00 | 0.894555E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.881634E+11 | 0.00 | 0.404646E+12 | 0.00 | 0.816798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.976095E+11 | 0.00 | 0.143019E+13 | 0.00 | 0.349535E+12 | 0.00 | 0.00 | 0.00 | 0.261356E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146625E+10 | 0.00 | 0.491832E+10 | 0.00 | 0.103832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132436E+10 | 0.00 | 0.109099E+11 | 0.00 | 0.218294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146625E+10 | 0.00 | 0.194957E+11 | 0.00 | 0.384236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141895E+10 | 0.00 | 0.254919E+11 | 0.00 | 0.521182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146625E+10 | 0.00 | 0.789224E+10 | 0.00 | 0.174437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141895E+10 | 0.00 | 0.146633E+11 | 0.00 | 0.347399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146625E+10 | 0.00 | 0.220679E+11 | 0.00 | 0.533069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146625E+10 | 0.00 | 0.289697E+11 | 0.00 | 0.704147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141895E+10 | 0.00 | 0.793216E+10 | 0.00 | 0.180415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146625E+10 | 0.00 | 0.136019E+11 | 0.00 | 0.276590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141895E+10 | 0.00 | 0.186838E+11 | 0.00 | 0.363472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146625E+10 | 0.00 | 0.248177E+11 | 0.00 | 0.461241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172640E+11 | 0.00 | 0.199444E+12 | 0.00 | 0.426831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132436E+10 | 0.00 | 0.491832E+10 | 0.00 | 0.103832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146625E+10 | 0.00 | 0.289697E+11 | 0.00 | 0.704147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.139415E+11 | 0.00 | 0.209589E+11 | 0.00 | 0.463079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125923E+11 | 0.00 | 0.850732E+11 | 0.00 | 0.172764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139415E+11 | 0.00 | 0.176434E+12 | 0.00 | 0.349919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134918E+11 | 0.00 | 0.239196E+12 | 0.00 | 0.490304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139415E+11 | 0.00 | 0.719954E+11 | 0.00 | 0.159838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134918E+11 | 0.00 | 0.139063E+12 | 0.00 | 0.329672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139415E+11 | 0.00 | 0.210382E+12 | 0.00 | 0.508156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139415E+11 | 0.00 | 0.275718E+12 | 0.00 | 0.670100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134918E+11 | 0.00 | 0.717880E+11 | 0.00 | 0.164078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139415E+11 | 0.00 | 0.120042E+12 | 0.00 | 0.246084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134918E+11 | 0.00 | 0.163777E+12 | 0.00 | 0.321450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139415E+11 | 0.00 | 0.213329E+12 | 0.00 | 0.401347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164150E+12 | 0.00 | 0.178776E+13 | 0.00 | 0.386002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125923E+11 | 0.00 | 0.209589E+11 | 0.00 | 0.463079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139415E+11 | 0.00 | 0.275718E+12 | 0.00 | 0.670100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140993E+10 | 0.00 | 0.904210E+09 | 0.00 | 0.200533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127348E+10 | 0.00 | 0.695460E+10 | 0.00 | 0.142777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140993E+10 | 0.00 | 0.167064E+11 | 0.00 | 0.333794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136444E+10 | 0.00 | 0.234774E+11 | 0.00 | 0.483479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140993E+10 | 0.00 | 0.710425E+10 | 0.00 | 0.158454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136444E+10 | 0.00 | 0.139927E+11 | 0.00 | 0.332227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140993E+10 | 0.00 | 0.211644E+11 | 0.00 | 0.511794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140993E+10 | 0.00 | 0.277098E+11 | 0.00 | 0.674115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136444E+10 | 0.00 | 0.702885E+10 | 0.00 | 0.161460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140993E+10 | 0.00 | 0.111566E+11 | 0.00 | 0.230827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136444E+10 | 0.00 | 0.149326E+11 | 0.00 | 0.296019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140993E+10 | 0.00 | 0.191942E+11 | 0.00 | 0.365460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166007E+11 | 0.00 | 0.170326E+12 | 0.00 | 0.371046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127348E+10 | 0.00 | 0.904210E+09 | 0.00 | 0.200533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140993E+10 | 0.00 | 0.277098E+11 | 0.00 | 0.674115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.964459E+09 | 0.00 | 0.00 | 0.103496E+09 | 0.00 | 0.00 | 0.660024E+11 | 0.00 | 0.65 |
February | 0.348535E+09 | 376705.72 | 0.00 | 92720109.15 | 0.00 | 0.00 | 0.579710E+11 | 0.00 | 0.86 |
March | 0.167421E+09 | 99922217.53 | 0.00 | 0.107283E+09 | 759274.81 | 0.00 | 0.643287E+11 | 0.00 | 1.24 |
April | 77028629.23 | 0.300567E+09 | 0.00 | 85570379.06 | 10637641.09 | 0.00 | 0.422279E+11 | 0.00 | 1.21 |
May | 73195358.28 | 0.223218E+10 | 0.00 | 75782051.43 | 20519042.49 | 0.00 | 0.277049E+11 | 0.00 | 1.21 |
June | 33286171.28 | 0.144792E+11 | 0.00 | 33619924.80 | 71178069.68 | 0.00 | 0.789676E+10 | 0.00 | 0.67 |
July | 29880214.49 | 0.213171E+11 | 0.00 | 18717267.37 | 0.231179E+09 | 0.00 | 0.319297E+10 | 0.00 | 0.47 |
August | 495235.85 | 0.284617E+11 | 0.00 | 4663354.71 | 0.188375E+09 | 0.00 | 0.819166E+09 | 0.00 | 0.39 |
September | 0.149373E+09 | 0.876050E+10 | 0.00 | 65134403.83 | 72729544.41 | 0.00 | 0.191518E+11 | 0.00 | 0.99 |
October | 0.240347E+09 | 0.247936E+10 | 0.00 | 0.109740E+09 | 3501.08 | 0.00 | 0.561803E+11 | 0.00 | 1.18 |
November | 0.300381E+09 | 3185699.29 | 0.00 | 0.132772E+09 | 0.00 | 0.00 | 0.728872E+11 | 0.00 | 1.24 |
December | 0.573106E+09 | 0.00 | 0.00 | 0.128843E+09 | 0.00 | 0.00 | 0.744206E+11 | 0.00 | 0.92 |
Annual Sum or Average | 0.295751E+10 | 0.781341E+11 | 0.00 | 0.958340E+09 | 0.595381E+09 | 0.00 | 0.492784E+12 | 0.00 | 0.92 |
Minimum of Months | 495235.85 | 0.00 | 0.00 | 4663354.71 | 0.00 | 0.00 | 0.819166E+09 | 0.00 | 0.39 |
Maximum of Months | 0.964459E+09 | 0.284617E+11 | 0.00 | 0.132772E+09 | 0.231179E+09 | 0.00 | 0.744206E+11 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.385410E+10 | 0.00 | 0.00 | 62026825.19 | 0.00 | 0.00 | 0.389130E+11 | 0.00 | 0.51 |
February | 0.275207E+10 | 0.00 | 0.00 | 69355541.29 | 0.00 | 0.00 | 0.394672E+11 | 0.00 | 0.66 |
March | 0.432565E+10 | 55368609.74 | 0.00 | 97820548.38 | 210084.50 | 0.00 | 0.507104E+11 | 0.00 | 0.97 |
April | 0.610130E+10 | 0.355640E+09 | 0.00 | 83302952.38 | 9770740.39 | 0.00 | 0.341051E+11 | 0.00 | 1.04 |
May | 0.190543E+10 | 0.206444E+10 | 0.00 | 56431279.35 | 39259059.33 | 0.00 | 0.156341E+11 | 0.00 | 0.82 |
June | 0.131891E+10 | 0.983425E+10 | 0.00 | 18324464.71 | 0.103187E+09 | 0.00 | 0.475622E+10 | 0.00 | 0.58 |
July | 0.236921E+09 | 0.140686E+11 | 0.00 | 3761197.88 | 0.287820E+09 | 0.00 | 0.367103E+09 | 0.00 | 0.42 |
August | 0.109554E+09 | 0.188833E+11 | 0.00 | 1940362.66 | 0.153612E+09 | 0.00 | 0.245332E+09 | 0.00 | 0.44 |
September | 0.100272E+10 | 0.719022E+10 | 0.00 | 38752379.29 | 0.188308E+09 | 0.00 | 0.107610E+11 | 0.00 | 0.70 |
October | 0.199370E+10 | 0.257766E+10 | 0.00 | 76407755.60 | 0.00 | 0.00 | 0.389424E+11 | 0.00 | 0.81 |
November | 0.281822E+10 | 224326.95 | 0.00 | 96422027.85 | 0.00 | 0.00 | 0.513704E+11 | 0.00 | 0.88 |
December | 0.214614E+10 | 0.00 | 0.00 | 95367329.56 | 0.00 | 0.00 | 0.531753E+11 | 0.00 | 0.70 |
Annual Sum or Average | 0.285647E+11 | 0.550297E+11 | 0.00 | 0.699913E+09 | 0.782167E+09 | 0.00 | 0.338447E+12 | 0.00 | 0.71 |
Minimum of Months | 0.109554E+09 | 0.00 | 0.00 | 1940362.66 | 0.00 | 0.00 | 0.245332E+09 | 0.00 | 0.42 |
Maximum of Months | 0.610130E+10 | 0.188833E+11 | 0.00 | 97820548.38 | 0.287820E+09 | 0.00 | 0.531753E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.182388E+12 | 0.00 | 0.00 | 0.137707E+09 | 0.00 | 0.769090E+09 | 0.112186E+12 | 0.00 | 0.44 |
February | 0.121748E+12 | 0.00 | 0.00 | 0.266019E+09 | 0.00 | 0.115423E+09 | 0.170849E+12 | 0.00 | 0.53 |
March | 0.377408E+11 | 0.461185E+09 | 0.00 | 0.613103E+09 | 0.142183E+09 | 0.00 | 0.346645E+12 | 0.00 | 0.73 |
April | 0.176513E+11 | 0.338665E+10 | 0.00 | 0.603523E+09 | 0.193120E+09 | 0.00 | 0.254004E+12 | 0.00 | 0.77 |
May | 0.135718E+11 | 0.202226E+11 | 0.00 | 0.485634E+09 | 0.387138E+09 | 0.00 | 0.133705E+12 | 0.00 | 0.73 |
June | 0.690969E+10 | 0.954659E+11 | 0.00 | 0.166868E+09 | 0.916839E+09 | 0.00 | 0.408485E+11 | 0.00 | 0.53 |
July | 0.987562E+09 | 0.135020E+12 | 0.00 | 30251527.75 | 0.283942E+10 | 0.00 | 0.277770E+10 | 0.00 | 0.40 |
August | 0.499873E+09 | 0.180907E+12 | 0.00 | 21870007.13 | 0.154458E+10 | 0.00 | 0.247218E+10 | 0.00 | 0.44 |
September | 0.105876E+11 | 0.696077E+11 | 0.00 | 0.327518E+09 | 0.184872E+10 | 0.00 | 0.869009E+11 | 0.00 | 0.62 |
October | 0.241551E+11 | 0.233677E+11 | 0.00 | 0.484077E+09 | 0.00 | 0.00 | 0.268231E+12 | 0.00 | 0.63 |
November | 0.496184E+11 | 36673767.56 | 0.00 | 0.485210E+09 | 0.474146E+09 | 0.00 | 0.298729E+12 | 0.00 | 0.62 |
December | 0.124401E+12 | 0.00 | 0.00 | 0.281714E+09 | 0.00 | 0.00 | 0.194507E+12 | 0.00 | 0.49 |
Annual Sum or Average | 0.590260E+12 | 0.528475E+12 | 0.00 | 0.390349E+10 | 0.834614E+10 | 0.884512E+09 | 0.191186E+13 | 0.00 | 0.58 |
Minimum of Months | 0.499873E+09 | 0.00 | 0.00 | 21870007.13 | 0.00 | 0.00 | 0.247218E+10 | 0.00 | 0.40 |
Maximum of Months | 0.182388E+12 | 0.180907E+12 | 0.00 | 0.613103E+09 | 0.283942E+10 | 0.769090E+09 | 0.346645E+12 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184492E+11 | 0.00 | 0.00 | 2157355.32 | 0.00 | 0.172042E+10 | 0.212034E+10 | 0.00 | 0.42 |
February | 0.144187E+11 | 0.00 | 0.00 | 10030765.33 | 0.00 | 0.631934E+09 | 0.680061E+10 | 0.00 | 0.48 |
March | 0.888695E+10 | 14557590.96 | 0.00 | 37557199.33 | 13292569.95 | 1347374.31 | 0.210065E+11 | 0.00 | 0.64 |
April | 0.420996E+10 | 0.227621E+09 | 0.00 | 46056579.21 | 13239387.42 | 0.00 | 0.181195E+11 | 0.00 | 0.72 |
May | 0.128916E+10 | 0.184136E+10 | 0.00 | 44938778.38 | 37147421.61 | 0.00 | 0.113506E+11 | 0.00 | 0.74 |
June | 0.422061E+09 | 0.947998E+10 | 0.00 | 14904555.68 | 0.102404E+09 | 0.00 | 0.360135E+10 | 0.00 | 0.53 |
July | 90523533.13 | 0.130568E+11 | 0.00 | 2309499.57 | 0.576243E+09 | 0.00 | 0.203287E+09 | 0.00 | 0.40 |
August | 38620339.40 | 0.178205E+11 | 0.00 | 2418172.75 | 0.144608E+09 | 0.00 | 0.192216E+09 | 0.00 | 0.44 |
September | 0.109729E+10 | 0.665130E+10 | 0.00 | 27117430.08 | 0.262045E+09 | 0.00 | 0.675968E+10 | 0.00 | 0.59 |
October | 0.690474E+10 | 0.227717E+10 | 0.00 | 26680801.52 | 0.00 | 0.00 | 0.152669E+11 | 0.00 | 0.56 |
November | 0.119428E+11 | 0.00 | 0.00 | 19278519.32 | 83197716.43 | 16242841.89 | 0.129013E+11 | 0.00 | 0.52 |
December | 0.171513E+11 | 0.00 | 0.00 | 7127824.97 | 0.00 | 0.527662E+09 | 0.589436E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.849013E+11 | 0.513692E+11 | 0.00 | 0.240577E+09 | 0.123218E+10 | 0.289761E+10 | 0.104217E+12 | 0.00 | 0.54 |
Minimum of Months | 38620339.40 | 0.00 | 0.00 | 2157355.32 | 0.00 | 0.00 | 0.192216E+09 | 0.00 | 0.40 |
Maximum of Months | 0.184492E+11 | 0.178205E+11 | 0.00 | 46056579.21 | 0.576243E+09 | 0.172042E+10 | 0.210065E+11 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.393669E+10 | 0.00 | 0.00 | 363328.48 | 0.00 | 0.445659E+09 | 0.301103E+09 | 0.00 | 0.45 |
February | 0.341535E+10 | 0.00 | 0.00 | 1377496.39 | 0.00 | 0.125712E+09 | 0.844081E+09 | 0.00 | 0.56 |
March | 0.260999E+10 | 7431387.89 | 0.00 | 4982752.60 | 32277.74 | 0.00 | 0.289421E+10 | 0.00 | 0.82 |
April | 0.184153E+10 | 51074240.21 | 0.00 | 6358525.94 | 1501192.97 | 0.00 | 0.255597E+10 | 0.00 | 1.00 |
May | 0.570187E+09 | 0.334978E+09 | 0.00 | 5079613.98 | 6031827.83 | 0.00 | 0.148509E+10 | 0.00 | 0.89 |
June | 0.264859E+09 | 0.175465E+10 | 0.00 | 1987433.81 | 15853836.94 | 0.00 | 0.517465E+09 | 0.00 | 0.76 |
July | 43676525.92 | 0.253428E+10 | 0.00 | 347311.02 | 44221224.76 | 0.00 | 37292308.05 | 0.00 | 0.59 |
August | 17559475.88 | 0.320639E+10 | 0.00 | 223640.50 | 23601131.03 | 0.00 | 27993832.00 | 0.00 | 0.60 |
September | 0.508094E+09 | 0.106973E+10 | 0.00 | 3127639.14 | 28931928.33 | 0.00 | 0.818734E+09 | 0.00 | 0.73 |
October | 0.193752E+10 | 0.347547E+09 | 0.00 | 3176773.95 | 0.00 | 0.00 | 0.197803E+10 | 0.00 | 0.67 |
November | 0.277213E+10 | 22285.79 | 0.00 | 3377629.72 | 0.00 | 323816.88 | 0.217006E+10 | 0.00 | 0.67 |
December | 0.390473E+10 | 0.00 | 0.00 | 1359954.49 | 0.00 | 1213569.59 | 0.112694E+10 | 0.00 | 0.52 |
Annual Sum or Average | 0.218223E+11 | 0.930610E+10 | 0.00 | 31762100.00 | 0.120173E+09 | 0.572909E+09 | 0.147570E+11 | 0.00 | 0.69 |
Minimum of Months | 17559475.88 | 0.00 | 0.00 | 223640.50 | 0.00 | 0.00 | 27993832.00 | 0.00 | 0.45 |
Maximum of Months | 0.393669E+10 | 0.320639E+10 | 0.00 | 6358525.94 | 44221224.76 | 0.445659E+09 | 0.289421E+10 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.382669E+10 | 0.00 | 0.00 | 127476.98 | 0.00 | 0.424692E+09 | 0.245200E+09 | 0.00 | 0.67 |
February | 0.334125E+10 | 0.00 | 0.00 | 1329748.58 | 0.00 | 0.113383E+09 | 0.853996E+09 | 0.00 | 0.84 |
March | 0.278716E+10 | 5713551.29 | 0.00 | 3858738.99 | 31096.74 | 0.00 | 0.245824E+10 | 0.00 | 1.15 |
April | 0.206956E+10 | 33810561.28 | 0.00 | 5330463.44 | 1446266.50 | 0.00 | 0.222833E+10 | 0.00 | 1.42 |
May | 0.737911E+09 | 0.271070E+09 | 0.00 | 4389920.49 | 7311142.97 | 0.00 | 0.134442E+10 | 0.00 | 1.27 |
June | 0.299070E+09 | 0.133901E+10 | 0.00 | 1870085.44 | 15273768.12 | 0.00 | 0.523955E+09 | 0.00 | 0.99 |
July | 56710504.91 | 0.195342E+10 | 0.00 | 107108.61 | 50001512.10 | 0.00 | 15277547.74 | 0.00 | 0.71 |
August | 27117058.38 | 0.227851E+10 | 0.00 | 119954.35 | 24247074.26 | 0.00 | 14434196.03 | 0.00 | 0.69 |
September | 0.586689E+09 | 0.889782E+09 | 0.00 | 2651840.57 | 33327421.34 | 0.00 | 0.751506E+09 | 0.00 | 1.02 |
October | 0.202712E+10 | 0.245006E+09 | 0.00 | 2903606.56 | 6243129.28 | 0.00 | 0.190572E+10 | 0.00 | 0.98 |
November | 0.299317E+10 | 19517.77 | 0.00 | 1918044.65 | 0.00 | 3996716.68 | 0.160372E+10 | 0.00 | 0.93 |
December | 0.408870E+10 | 0.00 | 0.00 | 608882.09 | 0.00 | 54934291.65 | 0.628894E+09 | 0.00 | 0.74 |
Annual Sum or Average | 0.228412E+11 | 0.701634E+10 | 0.00 | 25215870.74 | 0.137881E+09 | 0.597006E+09 | 0.125737E+11 | 0.00 | 0.95 |
Minimum of Months | 27117058.38 | 0.00 | 0.00 | 107108.61 | 0.00 | 0.00 | 14434196.03 | 0.00 | 0.67 |
Maximum of Months | 0.408870E+10 | 0.227851E+10 | 0.00 | 5330463.44 | 50001512.10 | 0.424692E+09 | 0.245824E+10 | 0.00 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.322408E+10 | 0.00 | 0.00 | 3870279.21 | 0.00 | 0.498539E+09 | 0.262783E+10 | 0.00 | 0.60 |
February | 0.294560E+10 | 0.00 | 0.00 | 5387106.31 | 0.00 | 0.173220E+09 | 0.306554E+10 | 0.00 | 0.83 |
March | 0.251284E+10 | 14905975.53 | 0.00 | 9351645.10 | 36987.29 | 0.00 | 0.513094E+10 | 0.00 | 1.20 |
April | 0.218338E+10 | 61312845.38 | 0.00 | 8413824.01 | 1720227.61 | 0.00 | 0.315492E+10 | 0.00 | 1.27 |
May | 0.822409E+09 | 0.375720E+09 | 0.00 | 5019160.88 | 6911914.04 | 0.00 | 0.143268E+10 | 0.00 | 0.99 |
June | 0.373088E+09 | 0.177037E+10 | 0.00 | 1762078.23 | 18167023.53 | 0.00 | 0.438580E+09 | 0.00 | 0.78 |
July | 54831528.00 | 0.259466E+10 | 0.00 | 268315.65 | 50673413.24 | 0.00 | 32710217.06 | 0.00 | 0.60 |
August | 20121527.22 | 0.358632E+10 | 0.00 | 224712.30 | 27044702.45 | 0.00 | 28945761.46 | 0.00 | 0.68 |
September | 0.589479E+09 | 0.135083E+10 | 0.00 | 4446114.17 | 33153300.66 | 0.00 | 0.104994E+10 | 0.00 | 0.97 |
October | 0.174849E+10 | 0.454630E+09 | 0.00 | 8404736.29 | 0.00 | 0.00 | 0.446689E+10 | 0.00 | 1.11 |
November | 0.226157E+10 | 23214.95 | 0.00 | 9774224.95 | 0.00 | 4667212.47 | 0.541912E+10 | 0.00 | 1.08 |
December | 0.304952E+10 | 0.00 | 0.00 | 6836096.56 | 0.00 | 83024693.21 | 0.469348E+10 | 0.00 | 0.82 |
Annual Sum or Average | 0.197854E+11 | 0.102088E+11 | 0.00 | 63758293.67 | 0.137708E+09 | 0.759451E+09 | 0.315416E+11 | 0.00 | 0.91 |
Minimum of Months | 20121527.22 | 0.00 | 0.00 | 224712.30 | 0.00 | 0.00 | 28945761.46 | 0.00 | 0.60 |
Maximum of Months | 0.322408E+10 | 0.358632E+10 | 0.00 | 9774224.95 | 50673413.24 | 0.498539E+09 | 0.541912E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.495548E+10 | 0.00 | 0.00 | 738482.51 | 0.00 | 37580550.19 | 0.822531E+09 | 0.00 | 0.87 |
February | 0.340878E+10 | 0.00 | 0.00 | 3118586.91 | 0.00 | 3299843.55 | 0.218044E+10 | 0.00 | 1.12 |
March | 0.129620E+10 | 14580271.72 | 0.00 | 10988512.69 | 40062.95 | 0.00 | 0.622252E+10 | 0.00 | 1.79 |
April | 0.112734E+10 | 71290298.37 | 0.00 | 14032955.40 | 1143962.35 | 0.00 | 0.514907E+10 | 0.00 | 2.26 |
May | 0.590008E+09 | 0.334281E+09 | 0.00 | 6108034.53 | 6839604.33 | 0.00 | 0.180015E+10 | 0.00 | 1.56 |
June | 0.255634E+09 | 0.180248E+10 | 0.00 | 2743211.73 | 14762870.92 | 0.00 | 0.661696E+09 | 0.00 | 1.30 |
July | 37269278.09 | 0.278645E+10 | 0.00 | 681799.59 | 42891648.65 | 0.00 | 65108719.59 | 0.00 | 1.02 |
August | 11011430.96 | 0.394175E+10 | 0.00 | 469402.21 | 8361096.02 | 0.00 | 51459623.32 | 0.00 | 1.15 |
September | 0.428554E+09 | 0.111423E+10 | 0.00 | 3749316.44 | 34004771.78 | 0.00 | 0.108045E+10 | 0.00 | 1.27 |
October | 0.133278E+10 | 0.371620E+09 | 0.00 | 6232199.45 | 0.00 | 0.00 | 0.379711E+10 | 0.00 | 1.36 |
November | 0.160632E+10 | 29023.91 | 0.00 | 7942967.92 | 0.00 | 0.00 | 0.501563E+10 | 0.00 | 1.41 |
December | 0.184474E+10 | 0.00 | 0.00 | 6248353.16 | 0.00 | 0.00 | 0.507892E+10 | 0.00 | 1.12 |
Annual Sum or Average | 0.168941E+11 | 0.104367E+11 | 0.00 | 63053822.55 | 0.108044E+09 | 40880393.75 | 0.319251E+11 | 0.00 | 1.35 |
Minimum of Months | 11011430.96 | 0.00 | 0.00 | 469402.21 | 0.00 | 0.00 | 51459623.32 | 0.00 | 0.87 |
Maximum of Months | 0.495548E+10 | 0.394175E+10 | 0.00 | 14032955.40 | 42891648.65 | 37580550.19 | 0.622252E+10 | 0.00 | 2.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234000E+11 | 0.00 | 0.00 | 0.50 |
February | 0.227739E+11 | 0.00 | 0.00 | 2129929.29 | 0.00 | 0.144751E+11 | 0.642770E+09 | 0.00 | 0.53 |
March | 0.326735E+11 | 44646531.23 | 0.00 | 14730410.96 | 40248106.76 | 0.128229E+10 | 0.697958E+10 | 0.00 | 0.63 |
April | 0.182556E+11 | 0.455244E+09 | 0.00 | 28642228.20 | 24401651.73 | 0.353041E+09 | 0.101952E+11 | 0.00 | 0.70 |
May | 0.744533E+10 | 0.322112E+10 | 0.00 | 33941637.97 | 69153754.18 | 0.00 | 0.905060E+10 | 0.00 | 0.77 |
June | 0.215372E+10 | 0.175643E+11 | 0.00 | 15069120.69 | 0.134894E+09 | 0.00 | 0.359694E+10 | 0.00 | 0.71 |
July | 0.280549E+09 | 0.253191E+11 | 0.00 | 2005315.03 | 0.417763E+09 | 0.00 | 0.214409E+09 | 0.00 | 0.58 |
August | 75581894.92 | 0.319210E+11 | 0.00 | 1854373.69 | 0.227253E+09 | 0.00 | 0.274200E+09 | 0.00 | 0.61 |
September | 0.571218E+10 | 0.102889E+11 | 0.00 | 20917284.15 | 0.284251E+09 | 0.00 | 0.516280E+10 | 0.00 | 0.64 |
October | 0.259539E+11 | 0.303192E+10 | 0.00 | 7956954.73 | 38245593.60 | 0.238331E+09 | 0.468296E+10 | 0.00 | 0.55 |
November | 0.328887E+11 | 0.00 | 0.00 | 3130712.22 | 75156728.52 | 0.343186E+10 | 0.214825E+10 | 0.00 | 0.54 |
December | 0.286235E+11 | 0.00 | 0.00 | 1239070.70 | 0.00 | 0.118285E+11 | 0.567303E+09 | 0.00 | 0.49 |
Annual Sum or Average | 0.195448E+12 | 0.918462E+11 | 0.00 | 0.131617E+09 | 0.131137E+10 | 0.550091E+11 | 0.435150E+11 | 0.00 | 0.61 |
Minimum of Months | 75581894.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.328887E+11 | 0.319210E+11 | 0.00 | 33941637.97 | 0.417763E+09 | 0.234000E+11 | 0.101952E+11 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.247684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190443E+11 | 0.00 | 0.00 | 0.81 |
February | 0.251160E+11 | 0.00 | 0.00 | 4968262.13 | 0.00 | 0.111402E+11 | 0.357277E+10 | 0.00 | 0.87 |
March | 0.284234E+11 | 49808274.28 | 0.00 | 20105828.61 | 27760347.88 | 0.874704E+09 | 0.138831E+11 | 0.00 | 1.01 |
April | 0.155809E+11 | 0.373145E+09 | 0.00 | 40000735.80 | 36292235.15 | 0.159719E+09 | 0.168968E+11 | 0.00 | 1.20 |
May | 0.799968E+10 | 0.284064E+10 | 0.00 | 35193119.50 | 85435215.45 | 0.00 | 0.107830E+11 | 0.00 | 1.22 |
June | 0.222192E+10 | 0.147853E+11 | 0.00 | 17706398.11 | 0.179146E+09 | 0.00 | 0.486605E+10 | 0.00 | 1.02 |
July | 0.335071E+09 | 0.219383E+11 | 0.00 | 1127300.68 | 0.978483E+09 | 0.00 | 0.167034E+09 | 0.00 | 0.81 |
August | 0.175475E+09 | 0.268706E+11 | 0.00 | 1617508.48 | 0.299129E+09 | 0.00 | 0.200680E+09 | 0.00 | 0.83 |
September | 0.674953E+10 | 0.820269E+10 | 0.00 | 21665005.33 | 0.174466E+10 | 0.00 | 0.559987E+10 | 0.00 | 1.01 |
October | 0.234187E+11 | 0.209622E+10 | 0.00 | 17038679.62 | 0.535178E+09 | 0.313858E+09 | 0.103891E+11 | 0.00 | 0.91 |
November | 0.351864E+11 | 0.00 | 0.00 | 2862538.08 | 79133419.92 | 0.202140E+10 | 0.322874E+10 | 0.00 | 0.88 |
December | 0.346458E+11 | 0.00 | 0.00 | 329.41 | 0.00 | 0.835952E+10 | 7603416.65 | 0.00 | 0.80 |
Annual Sum or Average | 0.204621E+12 | 0.771567E+11 | 0.00 | 0.162286E+09 | 0.396522E+10 | 0.419137E+11 | 0.695947E+11 | 0.00 | 0.95 |
Minimum of Months | 0.175475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
Maximum of Months | 0.351864E+11 | 0.268706E+11 | 0.00 | 40000735.80 | 0.174466E+10 | 0.190443E+11 | 0.168968E+11 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239063E+11 | 0.00 | 0.00 | 27172423.30 | 0.00 | 0.119230E+11 | 0.191564E+11 | 0.00 | 0.63 |
February | 0.246587E+11 | 0.00 | 0.00 | 37362652.69 | 0.00 | 0.686202E+10 | 0.206756E+11 | 0.00 | 0.78 |
March | 0.242627E+11 | 0.178504E+09 | 0.00 | 65128628.35 | 874199.39 | 0.684326E+09 | 0.340300E+11 | 0.00 | 0.99 |
April | 0.171390E+11 | 0.658434E+09 | 0.00 | 57159067.33 | 21023633.49 | 9920039.39 | 0.198142E+11 | 0.00 | 0.98 |
May | 0.898476E+10 | 0.373840E+10 | 0.00 | 37991125.70 | 79733923.27 | 0.00 | 0.998413E+10 | 0.00 | 0.89 |
June | 0.309747E+10 | 0.178645E+11 | 0.00 | 13625535.57 | 0.155532E+09 | 0.00 | 0.309333E+10 | 0.00 | 0.74 |
July | 0.338554E+09 | 0.262752E+11 | 0.00 | 1696020.54 | 0.603619E+09 | 0.00 | 0.208436E+09 | 0.00 | 0.61 |
August | 84886393.30 | 0.371320E+11 | 0.00 | 2238076.65 | 0.262021E+09 | 0.00 | 0.310255E+09 | 0.00 | 0.73 |
September | 0.616503E+10 | 0.139058E+11 | 0.00 | 38903214.46 | 0.313616E+09 | 0.00 | 0.812573E+10 | 0.00 | 0.93 |
October | 0.173980E+11 | 0.443129E+10 | 0.00 | 68128777.90 | 49134954.17 | 6785800.31 | 0.341233E+11 | 0.00 | 0.99 |
November | 0.231095E+11 | 0.00 | 0.00 | 70315904.75 | 86655321.84 | 0.104755E+10 | 0.362679E+11 | 0.00 | 0.91 |
December | 0.263991E+11 | 0.00 | 0.00 | 43363268.93 | 0.00 | 0.518126E+10 | 0.281936E+11 | 0.00 | 0.73 |
Annual Sum or Average | 0.175544E+12 | 0.104184E+12 | 0.00 | 0.463085E+09 | 0.157221E+10 | 0.257149E+11 | 0.213983E+12 | 0.00 | 0.83 |
Minimum of Months | 84886393.30 | 0.00 | 0.00 | 1696020.54 | 0.00 | 0.00 | 0.208436E+09 | 0.00 | 0.61 |
Maximum of Months | 0.263991E+11 | 0.371320E+11 | 0.00 | 70315904.75 | 0.603619E+09 | 0.119230E+11 | 0.362679E+11 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.285685E+11 | 0.00 | 0.00 | 69572.74 | 0.00 | 0.175126E+11 | 0.210485E+09 | 0.00 | 0.85 |
February | 0.308143E+11 | 0.00 | 0.00 | 5042587.25 | 0.00 | 0.894753E+10 | 0.246334E+10 | 0.00 | 0.93 |
March | 0.343632E+11 | 0.135813E+09 | 0.00 | 23979746.89 | 6534436.11 | 0.273950E+09 | 0.120988E+11 | 0.00 | 1.14 |
April | 0.179464E+11 | 0.546227E+09 | 0.00 | 39388952.92 | 16267943.76 | 0.00 | 0.146023E+11 | 0.00 | 1.27 |
May | 0.844350E+10 | 0.293790E+10 | 0.00 | 31927424.06 | 74158078.71 | 0.00 | 0.939241E+10 | 0.00 | 1.24 |
June | 0.291831E+10 | 0.151595E+11 | 0.00 | 13401855.67 | 0.127754E+09 | 0.00 | 0.295725E+10 | 0.00 | 1.04 |
July | 0.315129E+09 | 0.219091E+11 | 0.00 | 1900686.55 | 0.787062E+09 | 0.00 | 0.222209E+09 | 0.00 | 0.82 |
August | 81902243.05 | 0.294346E+11 | 0.00 | 1723887.78 | 0.175015E+09 | 0.00 | 0.271761E+09 | 0.00 | 0.89 |
September | 0.687730E+10 | 0.927953E+10 | 0.00 | 19957694.91 | 0.909738E+09 | 0.00 | 0.459915E+10 | 0.00 | 1.03 |
October | 0.270314E+11 | 0.258488E+10 | 0.00 | 15585637.78 | 0.284007E+09 | 68920878.21 | 0.857803E+10 | 0.00 | 0.98 |
November | 0.365270E+11 | 0.00 | 0.00 | 8446728.22 | 83695773.64 | 0.135516E+10 | 0.542946E+10 | 0.00 | 0.96 |
December | 0.364975E+11 | 0.00 | 0.00 | 1646010.04 | 0.00 | 0.733854E+10 | 0.161549E+10 | 0.00 | 0.85 |
Annual Sum or Average | 0.230384E+12 | 0.819875E+11 | 0.00 | 0.163071E+09 | 0.246423E+10 | 0.354967E+11 | 0.624407E+11 | 0.00 | 1.00 |
Minimum of Months | 81902243.05 | 0.00 | 0.00 | 69572.74 | 0.00 | 0.00 | 0.210485E+09 | 0.00 | 0.82 |
Maximum of Months | 0.365270E+11 | 0.294346E+11 | 0.00 | 39388952.92 | 0.909738E+09 | 0.175126E+11 | 0.146023E+11 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.953063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283307E+10 | 0.00 | 0.00 | 0.56 |
February | 0.172722E+10 | 0.00 | 0.00 | 85087.52 | 0.00 | 0.176915E+10 | 25741455.71 | 0.00 | 0.59 |
March | 0.310061E+10 | 1118713.17 | 0.00 | 1121107.12 | 3211503.23 | 0.539620E+09 | 0.477710E+09 | 0.00 | 0.69 |
April | 0.205765E+10 | 29508340.80 | 0.00 | 2511491.87 | 2562593.33 | 96772054.40 | 0.716050E+09 | 0.00 | 0.75 |
May | 0.850102E+09 | 0.285135E+09 | 0.00 | 3239373.53 | 9208933.89 | 0.00 | 0.750408E+09 | 0.00 | 0.81 |
June | 0.247497E+09 | 0.170309E+10 | 0.00 | 1361689.29 | 17840366.01 | 0.00 | 0.292815E+09 | 0.00 | 0.71 |
July | 25968329.06 | 0.239530E+10 | 0.00 | 122130.11 | 0.101996E+09 | 0.00 | 16227573.31 | 0.00 | 0.58 |
August | 14533161.00 | 0.309220E+10 | 0.00 | 178015.25 | 23886458.05 | 0.00 | 16529264.19 | 0.00 | 0.61 |
September | 0.628710E+09 | 0.903292E+09 | 0.00 | 1772872.82 | 0.144671E+09 | 0.00 | 0.384888E+09 | 0.00 | 0.65 |
October | 0.250403E+10 | 0.287363E+09 | 0.00 | 360852.47 | 16361069.44 | 0.308478E+09 | 0.230788E+09 | 0.00 | 0.60 |
November | 0.285589E+10 | 0.00 | 8831901.77 | 116697.60 | 4900492.47 | 0.849058E+09 | 62400493.36 | 10288.05 | 0.61 |
December | 0.178462E+10 | 0.00 | 0.00 | 21260.79 | 0.00 | 0.203414E+10 | 29963918.13 | 0.00 | 0.56 |
Annual Sum or Average | 0.167499E+11 | 0.869701E+10 | 8831901.77 | 10890578.36 | 0.324639E+09 | 0.843028E+10 | 0.300352E+10 | 10288.05 | 0.64 |
Minimum of Months | 14533161.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.310061E+10 | 0.309220E+10 | 8831901.77 | 3239373.53 | 0.144671E+09 | 0.283307E+10 | 0.750408E+09 | 10288.05 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201920E+10 | 0.00 | 0.00 | 0.80 |
February | 0.179479E+10 | 0.00 | 0.00 | 269824.68 | 0.00 | 0.129790E+10 | 0.182918E+09 | 0.00 | 0.86 |
March | 0.266899E+10 | 1772505.29 | 0.00 | 1551850.58 | 2107149.57 | 0.289664E+09 | 0.931539E+09 | 0.00 | 1.01 |
April | 0.141337E+10 | 25770914.10 | 0.00 | 3976658.88 | 2626814.97 | 59281457.22 | 0.145386E+10 | 0.00 | 1.20 |
May | 0.671671E+09 | 0.255793E+09 | 0.00 | 3909906.44 | 13192763.96 | 0.00 | 0.103036E+10 | 0.00 | 1.27 |
June | 0.178565E+09 | 0.144625E+10 | 0.00 | 1752252.83 | 34185012.73 | 0.00 | 0.462200E+09 | 0.00 | 1.03 |
July | 26023031.04 | 0.215132E+10 | 0.00 | 72721.61 | 0.100330E+09 | 0.00 | 13643352.10 | 0.00 | 0.81 |
August | 16839902.98 | 0.262489E+10 | 0.00 | 208626.08 | 54125551.20 | 0.00 | 15128421.88 | 0.00 | 0.84 |
September | 0.536384E+09 | 0.787325E+09 | 0.00 | 2256100.86 | 0.201609E+09 | 0.00 | 0.548385E+09 | 0.00 | 1.01 |
October | 0.192592E+10 | 0.210028E+09 | 0.00 | 1368866.76 | 52142462.91 | 0.204159E+09 | 0.834279E+09 | 0.00 | 0.90 |
November | 0.287343E+10 | 0.00 | 8349856.93 | 126615.72 | 4629701.58 | 0.514643E+09 | 0.159178E+09 | 3732.11 | 0.90 |
December | 0.219008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140288E+10 | 0.00 | 0.00 | 0.81 |
Annual Sum or Average | 0.157494E+11 | 0.750315E+10 | 8349856.93 | 15493424.44 | 0.464948E+09 | 0.578772E+10 | 0.563149E+10 | 3732.11 | 0.95 |
Minimum of Months | 16839902.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
Maximum of Months | 0.287343E+10 | 0.262489E+10 | 8349856.93 | 3976658.88 | 0.201609E+09 | 0.201920E+10 | 0.145386E+10 | 3732.11 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.196744E+10 | 0.00 | 0.00 | 1208310.19 | 0.00 | 0.149748E+10 | 0.857566E+09 | 0.00 | 0.63 |
February | 0.192101E+10 | 0.00 | 0.00 | 2548489.11 | 0.00 | 0.109943E+10 | 0.141125E+10 | 0.00 | 0.78 |
March | 0.248973E+10 | 8037082.35 | 0.00 | 5232020.93 | 60518.07 | 0.315914E+09 | 0.265638E+10 | 0.00 | 0.97 |
April | 0.177387E+10 | 43464540.91 | 0.00 | 5502490.63 | 2028030.74 | 91791046.94 | 0.168686E+10 | 0.00 | 1.01 |
May | 0.951235E+09 | 0.327764E+09 | 0.00 | 3848547.60 | 11582197.73 | 0.00 | 0.890506E+09 | 0.00 | 0.94 |
June | 0.313464E+09 | 0.173038E+10 | 0.00 | 1281998.58 | 26337449.58 | 0.00 | 0.278678E+09 | 0.00 | 0.74 |
July | 29765785.78 | 0.249958E+10 | 0.00 | 93058.39 | 0.114962E+09 | 0.00 | 17544316.69 | 0.00 | 0.61 |
August | 15764780.44 | 0.359052E+10 | 0.00 | 242423.92 | 26922920.53 | 0.00 | 19220481.77 | 0.00 | 0.72 |
September | 0.582972E+09 | 0.128808E+10 | 0.00 | 3833401.24 | 99657518.25 | 0.00 | 0.771801E+09 | 0.00 | 0.93 |
October | 0.173798E+10 | 0.424193E+09 | 0.00 | 5397159.62 | 9513454.18 | 0.162886E+09 | 0.278328E+10 | 0.00 | 0.97 |
November | 0.237770E+10 | 0.00 | 0.00 | 4463709.26 | 15489661.23 | 0.418956E+09 | 0.245899E+10 | 0.00 | 0.89 |
December | 0.226824E+10 | 0.00 | 0.00 | 2471280.41 | 0.00 | 0.892647E+09 | 0.167030E+10 | 0.00 | 0.70 |
Annual Sum or Average | 0.164292E+11 | 0.991202E+10 | 0.00 | 36122889.86 | 0.306554E+09 | 0.447910E+10 | 0.155024E+11 | 0.00 | 0.82 |
Minimum of Months | 15764780.44 | 0.00 | 0.00 | 93058.39 | 0.00 | 0.00 | 17544316.69 | 0.00 | 0.61 |
Maximum of Months | 0.248973E+10 | 0.359052E+10 | 0.00 | 5502490.63 | 0.114962E+09 | 0.149748E+10 | 0.278328E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.180062E+10 | 0.00 | 0.00 | 1721.11 | 0.00 | 0.205768E+10 | 15578807.25 | 0.00 | 0.89 |
February | 0.224407E+10 | 0.00 | 0.00 | 388792.37 | 0.00 | 0.123951E+10 | 0.201598E+09 | 0.00 | 0.97 |
March | 0.306953E+10 | 5211530.83 | 0.00 | 2120312.99 | 921000.21 | 0.292144E+09 | 0.108915E+10 | 0.00 | 1.18 |
April | 0.185311E+10 | 35465946.36 | 0.00 | 3855679.65 | 2616467.05 | 62839036.51 | 0.121895E+10 | 0.00 | 1.32 |
May | 0.897731E+09 | 0.251602E+09 | 0.00 | 3266394.05 | 15000547.05 | 0.00 | 0.833681E+09 | 0.00 | 1.30 |
June | 0.285683E+09 | 0.143676E+10 | 0.00 | 1296834.08 | 36040375.50 | 0.00 | 0.273618E+09 | 0.00 | 1.03 |
July | 26785095.67 | 0.207315E+10 | 0.00 | 144297.49 | 0.113993E+09 | 0.00 | 18174123.67 | 0.00 | 0.80 |
August | 14015884.00 | 0.283663E+10 | 0.00 | 170360.95 | 17814667.46 | 0.00 | 16866063.78 | 0.00 | 0.87 |
September | 0.650445E+09 | 0.834137E+09 | 0.00 | 1886252.76 | 0.173408E+09 | 0.00 | 0.411262E+09 | 0.00 | 1.04 |
October | 0.252719E+10 | 0.238667E+09 | 0.00 | 1223611.18 | 49551726.60 | 0.130955E+09 | 0.683867E+09 | 0.00 | 1.01 |
November | 0.302892E+10 | 0.00 | 0.00 | 539445.88 | 14545602.24 | 0.570109E+09 | 0.406512E+09 | 0.00 | 1.02 |
December | 0.274677E+10 | 0.00 | 0.00 | 33704.59 | 0.00 | 0.120188E+10 | 65547404.00 | 0.00 | 0.91 |
Annual Sum or Average | 0.191449E+11 | 0.771163E+10 | 0.00 | 14927407.11 | 0.423892E+09 | 0.555512E+10 | 0.523481E+10 | 0.00 | 1.03 |
Minimum of Months | 14015884.00 | 0.00 | 0.00 | 1721.11 | 0.00 | 0.00 | 15578807.25 | 0.00 | 0.80 |
Maximum of Months | 0.306953E+10 | 0.283663E+10 | 0.00 | 3855679.65 | 0.173408E+09 | 0.205768E+10 | 0.121895E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2986913.38 | 0.00 | 0.00 | 0.592752E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7237022.17 | 0.00 | 0.00 | 0.444832E+09 | 0.00 | 0.28 |
March | 0.00 | 4296492.00 | 0.00 | 12079555.68 | 0.00 | 0.00 | 0.341301E+09 | 0.00 | 0.31 |
April | 0.00 | 11302990.37 | 0.00 | 14441425.65 | 0.00 | 0.00 | 0.186619E+09 | 0.00 | 0.29 |
May | 0.00 | 66560490.23 | 0.00 | 1444277.91 | 0.00 | 0.00 | 59774772.58 | 0.00 | 0.29 |
June | 0.00 | 0.278944E+09 | 0.00 | 1319537.84 | 0.00 | 0.00 | 27365874.69 | 0.00 | 0.30 |
July | 0.00 | 0.392022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.479363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.156540E+09 | 0.00 | 1273454.01 | 0.00 | 0.00 | 34031301.67 | 0.00 | 0.29 |
October | 0.00 | 50450521.09 | 0.00 | 6005871.20 | 0.00 | 0.00 | 0.241300E+09 | 0.00 | 0.28 |
November | 0.00 | 3590752.49 | 0.00 | 11056224.13 | 0.00 | 0.00 | 0.355661E+09 | 0.00 | 0.28 |
December | 0.00 | 442616.74 | 0.00 | 16463960.50 | 0.00 | 0.00 | 0.448645E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.144351E+10 | 0.00 | 74308242.48 | 0.00 | 0.00 | 0.273228E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.479363E+09 | 0.00 | 16463960.50 | 0.00 | 0.00 | 0.592752E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.551031E+09 | 0.00 | 0.00 | 14899125.43 | 0.00 | 0.00 | 0.539992E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 58766809.99 | 0.00 | 0.00 | 0.446328E+10 | 0.00 | 0.28 |
March | 0.00 | 42643861.66 | 0.00 | 0.109862E+09 | 0.00 | 0.00 | 0.341968E+10 | 0.00 | 0.31 |
April | 0.00 | 0.113227E+09 | 0.00 | 0.135776E+09 | 0.00 | 0.00 | 0.187095E+10 | 0.00 | 0.29 |
May | 0.00 | 0.647930E+09 | 0.00 | 13271965.25 | 0.00 | 0.00 | 0.602108E+09 | 0.00 | 0.29 |
June | 0.00 | 0.278031E+10 | 0.00 | 12343170.97 | 0.00 | 0.00 | 0.273571E+09 | 0.00 | 0.30 |
July | 0.00 | 0.391455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.478665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.153930E+10 | 0.00 | 11341628.07 | 0.00 | 0.00 | 0.350069E+09 | 0.00 | 0.29 |
October | 0.00 | 0.499039E+09 | 0.00 | 52716722.75 | 0.00 | 0.00 | 0.242067E+10 | 0.00 | 0.28 |
November | 0.00 | 34884040.00 | 0.00 | 98598077.26 | 0.00 | 0.00 | 0.356536E+10 | 0.00 | 0.28 |
December | 0.00 | 4334768.86 | 0.00 | 0.145205E+09 | 0.00 | 0.00 | 0.450258E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.551031E+09 | 0.143629E+11 | 0.00 | 0.652780E+09 | 0.00 | 0.00 | 0.268682E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.551031E+09 | 0.478665E+10 | 0.00 | 0.145205E+09 | 0.00 | 0.00 | 0.539992E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.251656E+09 | 0.00 | 0.00 | 751640.36 | 0.00 | 0.00 | 0.335898E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5122689.64 | 0.00 | 0.00 | 0.447356E+09 | 0.00 | 0.28 |
March | 0.00 | 4244044.74 | 0.00 | 10456385.49 | 0.00 | 0.00 | 0.342769E+09 | 0.00 | 0.31 |
April | 0.00 | 11264458.16 | 0.00 | 13334245.67 | 0.00 | 0.00 | 0.187536E+09 | 0.00 | 0.29 |
May | 0.00 | 64778423.35 | 0.00 | 1263741.09 | 0.00 | 0.00 | 60544190.10 | 0.00 | 0.29 |
June | 0.00 | 0.278105E+09 | 0.00 | 1220575.42 | 0.00 | 0.00 | 27413570.42 | 0.00 | 0.30 |
July | 0.00 | 0.391315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.479053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.153718E+09 | 0.00 | 1061605.79 | 0.00 | 0.00 | 35820093.97 | 0.00 | 0.29 |
October | 0.00 | 49723750.31 | 0.00 | 4848265.70 | 0.00 | 0.00 | 0.243135E+09 | 0.00 | 0.28 |
November | 0.00 | 3410828.33 | 0.00 | 9169669.55 | 0.00 | 0.00 | 0.357505E+09 | 0.00 | 0.28 |
December | 0.00 | 420484.63 | 0.00 | 13533887.68 | 0.00 | 0.00 | 0.451441E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.251656E+09 | 0.143603E+10 | 0.00 | 60762706.40 | 0.00 | 0.00 | 0.248942E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.251656E+09 | 0.479053E+09 | 0.00 | 13533887.68 | 0.00 | 0.00 | 0.451441E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.215857E+09 | 0.00 | 0.00 | 0.151409E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.395105E+09 | 0.00 | 0.00 | 0.111571E+11 | 0.00 | 0.32 |
March | 0.00 | 84336128.46 | 0.00 | 0.603080E+09 | 0.00 | 0.00 | 0.799192E+10 | 0.00 | 0.34 |
April | 0.00 | 0.231659E+09 | 0.00 | 0.721661E+09 | 0.00 | 0.00 | 0.408951E+10 | 0.00 | 0.32 |
May | 0.00 | 0.174547E+10 | 0.00 | 71049066.76 | 0.00 | 0.00 | 0.128923E+10 | 0.00 | 0.33 |
June | 0.00 | 0.628302E+10 | 0.00 | 65278277.36 | 0.00 | 0.00 | 0.583801E+09 | 0.00 | 0.34 |
July | 0.00 | 0.864861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.874883E+10 | 0.00 | 35051.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.380397E+10 | 0.00 | 62729723.98 | 0.00 | 0.00 | 0.641238E+09 | 0.00 | 0.33 |
October | 0.00 | 0.116854E+10 | 0.00 | 0.310848E+09 | 0.00 | 0.00 | 0.516441E+10 | 0.00 | 0.32 |
November | 0.00 | 69138415.71 | 0.00 | 0.560300E+09 | 0.00 | 0.00 | 0.855038E+10 | 0.00 | 0.32 |
December | 0.00 | 9766119.94 | 0.00 | 0.834081E+09 | 0.00 | 0.00 | 0.110667E+11 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.307934E+11 | 0.00 | 0.384002E+10 | 0.00 | 0.00 | 0.656751E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.874883E+10 | 0.00 | 0.834081E+09 | 0.00 | 0.00 | 0.151409E+11 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:03:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.352921E+12 | 0.288310E+11 | 0.00 | 0.191974E+13 | 0.568375E+12 |
February | 0.353626E+12 | 0.254947E+11 | 0.00 | 0.179699E+13 | 0.959473E+12 |
March | 0.515988E+12 | 0.167877E+11 | 0.00 | 0.197915E+13 | 0.169750E+13 |
April | 0.578332E+12 | 0.915696E+10 | 0.00 | 0.152643E+13 | 0.239826E+13 |
May | 0.637104E+12 | 0.437477E+10 | 0.00 | 0.878618E+12 | 0.189135E+13 |
June | 0.619142E+12 | -0.440618E+10 | 0.00 | -0.142412E+12 | 0.301034E+13 |
July | 0.596713E+12 | -0.900969E+10 | 0.00 | -0.617512E+12 | 0.370701E+13 |
August | 0.554827E+12 | -0.116921E+11 | 0.00 | -0.832913E+12 | 0.439933E+13 |
September | 0.429168E+12 | -525685573.1 | 0.00 | 0.269871E+12 | 0.213998E+13 |
October | 0.408891E+12 | 0.908929E+10 | 0.00 | 0.149587E+13 | 0.163837E+13 |
November | 0.302150E+12 | 0.151711E+11 | 0.00 | 0.187838E+13 | 0.153411E+13 |
December | 0.288168E+12 | 0.269343E+11 | 0.00 | 0.196743E+13 | 0.177441E+13 |
Annual Sum or Average | 0.563703E+13 | 0.110206E+12 | 0.00 | 0.121196E+14 | 0.257185E+14 |
Minimum of Months | 0.288168E+12 | -0.116921E+11 | 0.00 | -0.832913E+12 | 0.568375E+12 |