Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700

Simulation Timestamp: 2023-10-16 09:03:13


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 32661.91 705.13 705.13
Net Site Energy 32661.91 705.13 705.13
Total Source Energy 101474.78 2190.72 2190.72
Net Source Energy 101474.78 2190.72 2190.72


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 301.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4465.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3707.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 670.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1941.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2838.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 753.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1398.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9030.75
Humidification 726.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 270.42
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 641.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 31718.32 943.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11581.34
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 301.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 4465.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 3707.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 670.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5871.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 87.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2838.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 753.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1398.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9030.75
Humidification General 726.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 270.42
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 641.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 301.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 4465.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 3707.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 670.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1941.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2838.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 753.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1398.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9030.75
Humidification Unassigned 726.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 270.42
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 641.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 94.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 219.87 20.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25
Other 370.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 684.76 20.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 94.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 219.87 20.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25
Other 370.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 684.76 20.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 31718.322 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 31718.322 100.00
     
Total On-Site and Utility Electric Sources 31718.322 100.00
Total Electricity End Uses 31718.322 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 11581.34 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 11581.34 100.00
Total Water End Uses 11581.34 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1.17
Time Setpoint Not Met During Occupied Cooling 979.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03
RunPeriod RUNPERIOD 1
Weather File El Paso International Ap Ut TX USA TMY3 WMO#=722700
Latitude [deg] 31.77
Longitude [deg] -106.5
Elevation [m] 1186.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 9.3279 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.3279 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 9.3279 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.3279 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 16.0861 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 16.0861 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 16.0861 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 9.3279 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.3913 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.3913 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.3279 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 9.3279 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 9.3279 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 9.3279 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 9.3279 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 9.3279 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 9.3279 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 9.3279 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 9.3279 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 9.3279 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 9.3279 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 9.3279 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 9.3279 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 9.3279 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 9.3279 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 9.3279 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 16.0861 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 16.0861 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 16.0861 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 9.3279 18.58 484.4232  
Total 46320.38             9.3913 9.29 17.8789  
Conditioned Total 46320.38             9.3913 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.8860 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 20-JUL-15:09 27-DEC-07:10 - - - - - - - - - - 15-JUN-12:30
Heating 0.00 627244.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 469530.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 316816.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 675712.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 84885.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 327323.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 76523.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 85424.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 7150.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 12452.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2043367.57 639696.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 627244.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 469530.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 316816.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 354874.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 5451.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 327323.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 76523.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 85424.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 7150.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 12452.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 327.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 14143.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 11742.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2124.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48180.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6150.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8990.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 2387.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 4430.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 2302.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 695.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 100451.93 1022.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 7.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 305.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 253.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 45.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 194.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 51.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 95.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 49.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2168.63 22.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 7.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 305.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 253.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 45.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 194.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 51.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 95.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 49.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2168.63 22.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 6.59
DATACENTER_BOT_ZN_6 DIRECT AIR 0.545575
DATACENTER_MID_ZN_6 DIRECT AIR 5.19
DATACENTER_TOP_ZN_6 DIRECT AIR 0.524932
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 24.65
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 6.90 0.275528 0.300000 2.07 0.734742 0.500000 0.001383 0.000158 2.07 12.80 0.008000
CORE_MID VAV BOX COMPONENT 65.19 0.291778 0.302000 19.69 0.778075 0.500000 0.001306 0.003637 19.69 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 6.46 0.294443 0.312000 2.02 0.785180 0.500000 0.001294 0.000724 2.84 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.18 0.201568 0.300000 0.355444 0.537516 0.500000 0.001890 0.000091 0.357607 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.07 0.143659 0.300000 0.321396 0.383092 0.500000 0.002652 0.000070 0.321396 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.30 0.183385 0.300000 0.390697 0.489026 0.500000 0.002078 0.000110 0.433814 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.41 0.109400 0.300000 0.422045 0.300000 0.500000 0.003483 0.000063 0.422045 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 11.25 0.212214 0.300000 3.38 0.565905 0.500000 0.001795 0.001738 6.83 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 11.03 0.139537 0.300000 3.31 0.372099 0.500000 0.002730 0.001153 4.53 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 12.37 0.193065 0.300000 3.71 0.514841 0.500000 0.001973 0.001721 6.77 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 11.95 0.128827 0.300000 3.58 0.343538 0.500000 0.002957 0.001076 4.23 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.29 0.184718 0.300000 0.387867 0.492582 0.500000 0.002063 0.000228 0.897981 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.14 0.135470 0.300000 0.340825 0.361253 0.500000 0.002812 0.000151 0.592373 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.39 0.171208 0.300000 0.418483 0.456555 0.500000 0.002225 0.000226 0.890102 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.31 0.117655 0.300000 0.392432 0.313747 0.500000 0.003238 0.000144 0.567106 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 18084.44 0.000158 364.57
CORE_MID VAV BOX REHEAT COIL 415731.93 0.003637 9762.38
CORE_TOP VAV BOX REHEAT COIL 82750.01 0.000724 2184.31
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 10415.18 0.000091 274.89
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 7981.05 0.000070 197.43
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 12628.20 0.000110 333.22
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 7193.45 0.000063 160.13
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 198631.58 0.001738 5238.46
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 131841.87 0.001153 3476.94
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 196737.74 0.001721 5188.56
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 123010.91 0.001076 3244.24
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 26097.83 0.000228 688.13
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 17215.37 0.000151 453.91
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 25869.17 0.000226 682.10
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 16481.98 0.000144 434.59
VAV_BOT WITH REHEAT HEATING COIL 48095.57 0.000421 801.99
VAV_MID WITH REHEAT HEATING COIL 441299.86 0.003861 7369.33
VAV_TOP WITH REHEAT HEATING COIL 43804.14 0.000383 736.97
CAV_BAS HEATING COIL 283149.33 0.002477 6303.87
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.93 3.56 11.87 3.56 11.03 11.03 0.300000 0.322685 11.03
VAV_MID WITH REHEAT 55.89 33.67 111.79 34.22 103.10 103.10 0.300000 0.331868 103.10
VAV_TOP WITH REHEAT 5.80 3.56 11.59 5.79 11.25 11.25 0.300000 0.514443 11.25
CAV_BAS 6.59 6.59 6.59 6.59 6.59 6.59 1.00 1.00 6.59
AIRLOOP DATACENTER BASEMENT 24.65 24.65 24.65 24.65 24.65 24.65 1.00 0.999986 24.65
AIRLOOP DATACENTER BOT 0.545575 0.545575 0.545575 0.545575 0.545575 0.545575 1.00 1.00 0.545575
AIRLOOP DATACENTER MID 5.19 5.19 5.19 5.19 5.19 5.19 1.00 1.00 5.19
AIRLOOP DATACENTER TOP 0.524932 0.524932 0.524932 0.524932 0.524932 0.524932 1.00 1.00 0.524932
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 11.03  
VAV_MID WITH REHEAT_OA_CONTROLLER 103.10  
VAV_TOP WITH REHEAT_OA_CONTROLLER 11.25  
CAV_BAS_OA_CONTROLLER 6.59 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 24.65 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.545575 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 5.19 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.524932 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 27.28 6.67 10.78 0.007229 0.007000 200241.47 0.008519 11.03
VAV_MID WITH REHEAT COOLING COIL 27.73 6.67 10.78 0.007237 0.007000 1922978.56 0.081808 103.10
VAV_TOP WITH REHEAT COOLING COIL 27.19 6.67 10.78 0.007214 0.007000 202662.09 0.008622 11.25
CAV_BAS COOLING COIL 26.51 6.67 11.22 0.007355 0.007000 113351.07 0.004822 6.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 11.03
VAV_MID WITH REHEAT FAN 103.10
VAV_TOP WITH REHEAT FAN 11.25
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.008519 0.000056
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000421  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.081808 0.000006
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.003861  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.008622 0.000055
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000383  
CAV_BAS_COOLC_CONTROLLER 0.004822 0.000099
CAV_BAS_HEATC_CONTROLLER 0.002477  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 6.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 24.65 468177.58 260807.64 0.011466
AIRLOOP DATACENTER BOT COOLING COIL 0.545575 10168.68 5698.97 0.000249
AIRLOOP DATACENTER MID COOLING COIL 5.19 96799.67 54220.49 0.002371
AIRLOOP DATACENTER TOP COOLING COIL 0.524932 9794.57 5486.50 0.000240
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 24.65 24.65 24.65 24.65 468177.58 468177.58 16051.03 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.545575 0.545575 0.545575 0.545575 10168.68 10168.68 741.49 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 5.19 5.19 5.19 5.19 96799.67 96799.67 7414.91 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.524932 0.524932 0.524932 0.524932 9794.57 9794.57 741.49 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 24.65
AIRLOOP DATACENTER BOT SUPPLY FAN 0.545575
AIRLOOP DATACENTER MID SUPPLY FAN 5.19
AIRLOOP DATACENTER TOP SUPPLY FAN 0.524932
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 24.65 468177.58 0.011466
AIRLOOP DATACENTER BOT HEATING COIL 0.545575 10168.68 0.000249
AIRLOOP DATACENTER MID HEATING COIL 5.19 96799.67 0.002371
AIRLOOP DATACENTER TOP HEATING COIL 0.524932 9794.57 0.000240
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 16051.03
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 741.49
AIRLOOP DATACENTER MID_SUPPHEATCOIL 7414.91
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 741.49
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000129 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.103771 21383.28  
HEATSYS1 PUMP 0.018433 5551.25 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.103771 12.45
HEATSYS1 0.018433 2.21
COOLSYS1_SUPPLY 0.103771 12.45
SINGLE WATER PLANT LOOP 0.014325 1.72
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.103771 0.103771 435577.35 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 2107019.60 2107019.60 0.018433
CENTRAL BOILER 590073.58 577236.29 0.014325
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.103771 14804.36
PLANT CIRC PUMP 0.014325 3653.63
SWHSYS1 PUMP 0.000440 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.103771 0.052570 1238746.43 1244624.78 0.061592
COOLSYS1 CHILLER2 0.103771 0.052570 1238746.43 1244624.78 0.061592
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.014325 139666.47 55766.50 69833.23 7879.72 21046.50
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.123184 14.78
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.123184 37100.26
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 54.89 1477958.59 10.98 184744.82
TOWERWATERSYS COOLTOWER 2 54.89 1477958.59 10.98 184744.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.063975
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.30 11.20 6.80 8.10 10.30 12.50 19.20 23.80 27.90 27.50 26.30 23.40


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 El Paso International Ap Ut TX USA TMY3 WMO#=722700 31.77 -106.50 -7.00 1186.00 87865 1.0443


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 17.94 21.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 9.328 4.842 0.000 0.000 0.000 0.000 14.170 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 16.086 215.299 0.000 0.000 0.000 0.000 231.385 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 16.086 215.299 0.000 0.000 0.000 0.000 231.385 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 16.086 215.299 0.000 0.000 0.000 0.000 231.385 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 9.328 484.423 0.000 0.000 0.000 0.000 493.751 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 25926.330 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25926.330
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 23283.667 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 23283.667
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 23283.667 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 23283.667
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 23283.667 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 23283.667
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2923.497 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.497
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2923.561 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.561
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2923.497 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.497
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2923.561 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.561
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2923.497 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.497
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2923.561 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.561
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 7310.116 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 7310.116
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 582.361 16.086 298.861 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 582.361
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 582.361 16.086 298.861 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 582.361
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 582.361 16.086 298.861 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 582.361


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.498 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.416 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.867 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.5004
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5391
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.3683
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
47 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
48 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
49 0 21.361010 0.87247630E-01 5.4456762  
50 9 0.14091426E-14 0.48101397E-16 -0.12271849E-09 -0.49605034E-17
51 8 0.18065296E-07 0.19413100E-12 0.33649602E-03 -0.20540863E-09
52 7 -0.11004888E-01 0.10546945E-07 -0.21303752E-01 0.12512956E-03
53 6 0.37174157 0.37425545E-05 0.44335749 -0.43515980E-02
54 5 -4.8625044 0.14213861E-03 -4.2200868 0.59116134E-01
55 4 31.551289 0.11806248E-02 20.574731 -0.40285082
56 3 -108.13650 0.26081321E-02 -53.912227 1.4705586
57 2 194.06739 0.14847903E-02 76.306869 -2.8520668
58 1 -170.03224 0.16027253E-03 -54.802483 2.7257428
59 0 57.057407 0.92345258E-06 15.636386  
60 9 0.11726792E-14 0.46876770E-16 -0.12664795E-09 -0.40425794E-17
61 8 0.18621286E-07 0.18477046E-12 0.34269676E-03 -0.21173044E-09
62 7 -0.11191167E-01 0.99660246E-08 -0.21572393E-01 0.12724763E-03
63 6 0.37680492 0.35261678E-05 0.44770143 -0.44112820E-02
64 5 -4.9119389 0.13358806E-03 -4.2535898 0.59729078E-01
65 4 31.770087 0.11071467E-02 20.706000 -0.40575564
66 3 -108.60241 0.24410452E-02 -54.171883 1.4772891
67 2 194.52961 0.13872791E-02 76.544434 -2.8594062
68 1 -170.20315 0.14950961E-03 -54.870487 2.7287383
69 0 57.057407 0.85997654E-06 15.624277  
70 9 0.98458787E-15 0.55454857E-16 -0.10492535E-09 -0.15601002E-17
71 8 0.15540463E-07 0.23311053E-12 0.30746206E-03 -0.17670042E-09
72 7 -0.10129638E-01 0.13130386E-07 -0.20040359E-01 0.11517765E-03
73 6 0.34794661 0.47273228E-05 0.42286390 -0.40711180E-02
74 5 -4.6301347 0.18177508E-03 -4.0616887 0.56235001E-01
75 4 30.522476 0.15264987E-02 19.953355 -0.38919251
76 3 -105.94476 0.34047073E-02 -52.682811 1.4388992
77 2 191.89184 0.19546755E-02 75.183526 -2.8175246
78 1 -169.22736 0.21263380E-03 -54.483619 2.7116363
79 0 57.057407 0.12355163E-05 15.695393  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.4644_SHGC_EAST_0.25 35 1 VerySmooth 2.640 2.640 1.000 0.251    
2 WINDOW_U_0.4644_SHGC_SOUTH_0.25 36 1 VerySmooth 2.640 2.640 1.000 0.251    
3 WINDOW_U_0.4644_SHGC_WEST_0.25 37 1 VerySmooth 2.640 2.640 1.000 0.251    
4 WINDOW_U_0.4644_SHGC_NORTH_0.25 38 1 VerySmooth 2.640 2.640 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.496 7.5104E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9226E-003
2 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9238E-003
3 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1412E-003
4 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.1422E-003
5 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2295E-003
6 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2303E-003
7 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
8 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2452E-003
9 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9511E-003
10 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0348E-003
11 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1652E-003
12 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2379E-003
13 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2499E-003
14 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.3097E-003
15 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2574E-003
16 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2891E-003
17 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.1305E-002
18 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.7294E-002
19 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 9.1591E-002
20 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.0913E-002
21 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.3066E-002
22 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.4553E-002
23 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6042E-002
24 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.1095E-003
25 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9523E-003
26 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0398E-003
27 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1664E-003
28 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2429E-003
29 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2509E-003
30 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.3134E-003
31 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2577E-003
32 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2900E-003
33 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9225E-003
34 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9237E-003
35 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1411E-003
36 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.1422E-003
37 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2294E-003
38 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2302E-003
39 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
40 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2451E-003
41 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6475E-003
42 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7899E-003
43 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.4897E-003
44 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.6398E-003
45 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.4121E-003
46 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.4832E-003
47 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1302E-003
48 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1521E-003
49 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9914E-002
50 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.5128E-002
51 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.7649E-002
52 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.3486E-002
53 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.1333E-002
54 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.3044E-002
55 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6787E-002
56 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 9.9865E-003
57 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6081E-003
58 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.6643E-003
59 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.4394E-003
60 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.4801E-003
61 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.3895E-003
62 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.4054E-003
63 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1303E-003
64 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1525E-003
65 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2520E-003
66 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2532E-003
67 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0683E-003
68 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0693E-003
69 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.4647E-004
70 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.4715E-004
71 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
72 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2452E-003
73 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2785E-003
74 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3466E-003
75 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0898E-003
76 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1431E-003
77 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.6337E-004
78 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0002E-003
79 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2577E-003
80 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2900E-003
81 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9710E-002
82 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1317E-002
83 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5282E-002
84 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 8.5965E-003
85 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5263E-002
86 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 6.0508E-003
87 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6042E-002
88 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.1067E-003
89 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2779E-003
90 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3448E-003
91 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0891E-003
92 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1415E-003
93 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.6260E-004
94 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.9799E-004
95 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2574E-003
96 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2891E-003
97 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2519E-003
98 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2531E-003
99 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0683E-003
100 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0692E-003
101 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.4643E-004
102 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.4708E-004
103 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
104 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2451E-003
105 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.5674E-003
106 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.6239E-003
107 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3893E-003
108 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4302E-003
109 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3538E-003
110 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.3696E-003
111 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1303E-003
112 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1525E-003
113 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9124E-002
114 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.4820E-002
115 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6688E-002
116 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.3112E-002
117 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0597E-002
118 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.2753E-002
119 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6787E-002
120 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 9.9865E-003
121 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6057E-003
122 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.7434E-003
123 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.4382E-003
124 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.5826E-003
125 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3762E-003
126 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4462E-003
127 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1302E-003
128 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1521E-003
129 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 7.4533E-002
130 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.8801E-002
131 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.1027E-002
132 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.3117E-002
133 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 6.5013E-002
134 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.4003E-002
135 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.0133E-002
136 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.4574E-002
137 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.4531E-002
138 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.0987E-002
139 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.2066E-002
140 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.9027E-002
141 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.5685E-002
142 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.8381E-002
143 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.0820E-002
144 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.4729E-002
145 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.3667E-002
146 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.6629E-002
147 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8837E-002
148 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.3168E-002
149 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8766E-002
150 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.0248E-002
151 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.0133E-002
152 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.4571E-002
153 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.3673E-002
154 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.0583E-002
155 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.1021E-002
156 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.8535E-002
157 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.4893E-002
158 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.8013E-002
159 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.0820E-002
160 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.4729E-002
161 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 7.4490E-002
162 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.8875E-002
163 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.0988E-002
164 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.3205E-002
165 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 6.5036E-002
166 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.4073E-002
167 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.0168E-002
168 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.4602E-002
169 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.4514E-002
170 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.1005E-002
171 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.2057E-002
172 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.9045E-002
173 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.5699E-002
174 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.8413E-002
175 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.0854E-002
176 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.4757E-002
177 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.3638E-002
178 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.6636E-002
179 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8817E-002
180 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.3174E-002
181 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8776E-002
182 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.0263E-002
183 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.0168E-002
184 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.4599E-002
185 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.3656E-002
186 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.0601E-002
187 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.1012E-002
188 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.8552E-002
189 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.4906E-002
190 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.8043E-002
191 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.0854E-002
192 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.4757E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 79113.13626 79113.13626 6.58945 6.58945 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.48000 6.85626E-003 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 82888.55576 82888.55576 6.90326 6.90326 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.48000 6.85626E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:20:00 -5.20000 2.80840E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 782887.45787 782887.45787 65.18798 65.18798 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.48000 6.85626E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 243820.72216 243820.72216 11.85325 11.85325 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 77580.11001 77580.11001 6.45981 6.45981 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.48000 6.85626E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 57947.01955 57947.01955 2.84037 2.84037 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 14104.12008 14104.12008 1.18481 1.18481 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 38.10000 6.87148E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 7295.17130 7295.17130 0.35761 0.35761 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 12753.14360 12753.14360 1.07132 1.07132 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 32.05500 6.86186E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 5176.59467 5176.59467 0.25388 0.25388 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 15502.98328 15502.98328 1.30232 1.30232 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 37.77500 6.87096E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 8842.21460 8842.21460 0.43381 0.43381 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 16747.01389 16747.01389 1.40682 1.40682 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 36.80000 6.86940E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 3513.54015 3513.54015 0.17186 0.17186 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 133966.05229 133966.05229 11.25374 11.25374 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 38.10000 6.87148E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 139012.96946 139012.96946 6.83140 6.83140 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 131299.45178 131299.45178 11.02967 11.02967 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 32.42333 6.86244E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 92267.63614 92267.63614 4.53462 4.53462 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 147256.67444 147256.67444 12.37020 12.37020 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 37.88333 6.87114E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 137689.03584 137689.03584 6.76614 6.76614 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 142215.61027 142215.61027 11.94667 11.94667 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 36.62667 6.86912E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 86093.85556 86093.85556 4.23035 4.23035 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 15390.79297 15390.79297 1.29289 1.29289 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 37.84000 6.87107E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 18260.81853 18260.81853 0.89798 0.89798 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 13524.18983 13524.18983 1.13608 1.13608 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 33.16000 6.86360E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 12045.55230 12045.55230 0.59237 0.59237 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 16605.66391 16605.66391 1.39494 1.39494 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 38.10000 6.87148E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 18100.96120 18100.96120 0.89010 0.89010 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 15571.99227 15571.99227 1.30811 1.30811 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 36.62667 6.86912E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 11532.78045 11532.78045 0.56711 0.56711 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8235.04759 8235.04759 0.54557 0.54557 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 25.18667 6.85117E-003 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:30:00 -5.20000 2.80840E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 78307.76557 78307.76557 5.18792 5.18792 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 25.18667 6.85117E-003 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 05:40:00 -5.20000 2.80840E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7922.47903 7922.47903 0.52493 0.52493 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 34.33000 6.86546E-003 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 05:40:00 -5.20000 2.80840E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 372073.03901 372073.03901 24.65245 24.65245 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 26.27000 6.85284E-003 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:30:00 -5.20000 2.80840E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 161125.17 11.03416 11.03416 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 43350.65 2.29498 2.29498 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1502724.92 103.10052 103.10052 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 473920.35 34.21575 34.21575 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:40:00
5 VAV_TOP WITH REHEAT Cooling Sensible 169475.50 11.25086 11.25086 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 47753.26 5.78793 5.78793 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:00:00
7 CAV_BAS Cooling Sensible 85339.44 6.58945 6.58945 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 56927.18 1.20016 1.20016 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 370786.01 24.65279 24.65279 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 16051.03 0.33839 0.33839 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8158.24 0.54557 0.54557 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 741.49 1.56323E-002 1.56323E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 77676.19 5.18792 5.18792 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 7414.91 0.15632 0.15632 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 7944.79 0.52493 0.52493 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 741.49 1.56323E-002 1.56323E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.58945
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.90326
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27553
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.07098
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.73474
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.38280E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.58211E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.07098
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18084.44029
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.58211E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 364.56812
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 65.18798
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.29178
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30200
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 19.68677
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.77808
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.30579E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.63700E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 19.68677
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 415731.92650
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.63700E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 9762.38095
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.45981
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.29444
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31200
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.01546
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.78518
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.29397E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.23933E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.84037
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 82750.00922
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.23933E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2184.31465
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.18481
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20157
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.35544
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53752
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.89018E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.11165E-005
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.35761
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10415.17533
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.11165E-005
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 274.88608
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.07132
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14366
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.32140
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.38309
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.65210E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.98217E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.32140
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7981.04810
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.98217E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 197.43214
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.30232
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18338
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.39070
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.48903
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.07760E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.10477E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.43381
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12628.19525
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.10477E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 333.21567
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.40682
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10940
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.42204
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.48264E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.29314E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.42204
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7193.44773
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.29314E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 160.13117
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.25374
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21221
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.37612
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.56591
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.79535E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.73772E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.83140
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 198631.57691
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.73772E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5238.46244
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.02967
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13954
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.30890
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37210
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.73045E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.15341E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.53462
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 131841.86952
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.15341E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3476.93948
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 12.37020
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19307
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.71106
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51484
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.97342E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.72115E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.76614
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 196737.73653
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.72115E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5188.56161
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.94667
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12883
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.58400
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34354
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.95746E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.07615E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.23035
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 123010.91354
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.07615E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3244.23612
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.29289
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18472
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.38787
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.49258
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.06260E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.28315E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.89798
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 26097.82574
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.28315E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 688.12565
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.13608
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13547
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.34083
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36125
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.81243E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.50608E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.59237
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17215.36879
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.50608E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 453.91276
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.39494
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17121
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.41848
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.45656
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.22536E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.26315E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.89010
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 25869.17481
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.26315E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 682.10084
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.30811
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11765
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.39243
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31375
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.23828E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.44192E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.56711
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16481.98142
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.44192E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 434.58677
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.54557
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.18792
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.52493
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 24.65245
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.93426
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.56056
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.86853
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.56056
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 11.03416
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 11.03416
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.32269
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 55.89414
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 33.66686
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 111.78827
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 34.21575
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 103.10052
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 103.10052
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.33187
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.79592
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.55507
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.59183
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 5.78793
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 11.25086
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 11.25086
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.51444
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.58945
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 6.58945
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 6.58945
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 6.58945
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 6.58945
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 6.58945
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 24.65245
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 24.65245
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 24.65245
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 24.65245
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 24.65279
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 24.65279
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.54557
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.54557
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.54557
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.54557
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.54557
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.54557
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.18792
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.18792
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 5.18792
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 5.18792
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 5.18792
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 5.18792
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.52493
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.52493
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.52493
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.52493
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.52493
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.52493
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 11.03416
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 103.10052
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 11.25086
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 6.58945
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 24.65279
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.54557
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 5.18792
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.52493
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 11.03416
289 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.27757
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.77872
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.22874E-003
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 200241.47174
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 8.51874E-003
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 11.03416
297 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 48095.57471
298 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.20761E-004
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 801.99357
300 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 11.03416
301 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 8.51874E-003
302 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 5.58992E-005
303 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.20761E-004
304 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 103.10052
305 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.73058
306 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.77876
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.23713E-003
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1922978.55802
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 8.18080E-002
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 103.10052
313 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 441299.86312
314 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.86068E-003
315 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 7369.32766
316 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 103.10052
317 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 8.18080E-002
318 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 5.82083E-006
319 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 3.86068E-003
320 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 11.25086
321 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.18735
322 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
323 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.77867
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.21430E-003
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 202662.08730
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 8.62171E-003
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 11.25086
329 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 43804.14346
330 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.83218E-004
331 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 736.97361
332 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 11.25086
333 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 8.62171E-003
334 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 5.52315E-005
335 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 3.83218E-004
336 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 6.58945
337 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
338 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 26.50981
339 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
340 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.21612
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.35486E-003
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 113351.06844
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.82222E-003
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.58945
346 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 283149.33253
347 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.47711E-003
348 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 6303.86607
349 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 6.58945
350 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 4.82222E-003
351 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 9.87493E-005
352 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.47711E-003
353 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 24.65279
354 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
355 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 24.65279
356 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 468177.57767
357 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 260807.63592
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.14656E-002
359 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 24.65279
360 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 24.65279
361 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 24.65279
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 24.65279
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 468177.57767
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 468177.57767
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 16051.03087
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
367 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 24.65279
368 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 24.65279
369 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 468177.57767
370 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.14656E-002
371 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 16051.03087
372 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.29020E-004
373 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
374 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
375 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
376 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.54557
377 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
378 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.54557
379 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 10168.68336
380 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 5698.96860
381 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.49030E-004
382 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.54557
383 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.54557
384 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.54557
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.54557
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 10168.68336
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 10168.68336
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 741.49113
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
390 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.54557
391 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.54557
392 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 10168.68336
393 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.49030E-004
394 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 741.49113
395 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.18792
396 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
397 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 5.18792
398 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 96799.66919
399 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 54220.49320
400 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.37062E-003
401 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 5.18792
402 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 5.18792
403 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 5.18792
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.18792
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 96799.66919
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 96799.66919
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 7414.91130
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
409 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 5.18792
410 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 5.18792
411 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 96799.66919
412 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.37062E-003
413 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 7414.91130
414 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.52493
415 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
416 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.52493
417 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9794.57011
418 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 5486.50338
419 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.39868E-004
420 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.52493
421 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.52493
422 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.52493
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.52493
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9794.57011
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9794.57011
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 741.49113
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
428 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.52493
429 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.52493
430 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9794.57011
431 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.39868E-004
432 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 741.49113
433 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.10377
434 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 21383.27837
435 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.10377
436 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 12.45247
437 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.10377
438 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.10377
439 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 435577.35455
440 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
441 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.84331E-002
442 PlantLoop HEATSYS1 Plant Loop Volume [m3] 2.21198
443 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.84331E-002
444 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 5551.24826
445 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
446 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 2107019.60350
447 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 2107019.60000
448 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.84331E-002
449 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.10377
450 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 12.45247
451 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 0.10377
452 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 14804.36492
453 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.10377
454 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 5.25700E-002
455 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1238746.42581
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1244624.78500
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 6.15919E-002
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.10377
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 5.25700E-002
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1238746.42581
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1244624.78500
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 6.15919E-002
463 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.43252E-002
464 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.71902
465 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.43252E-002
466 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3653.63094
467 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.43252E-002
468 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
469 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 55766.50107
470 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
471 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
472 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21046.49714
473 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 590073.58419
474 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 577236.29000
475 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.43252E-002
476 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
477 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
478 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
479 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 5.95776
480 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
481 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.12318
482 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 14.78205
483 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.12318
484 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 37100.26017
485 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 54.89274
486 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1477958.58825
487 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 10.97855
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 184744.82353
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 54.89274
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1477958.58825
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 10.97855
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 184744.82353
493 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 6.39750E-002
494 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 6.39750E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 17149.57
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 393981.41
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 78435.55
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 9871.88
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 7561.80
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 11968.94
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 6818.74
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 188243.39
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 124946.07
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 186448.90
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 116578.27
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 24731.96
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 16314.32
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 24515.30
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 15619.40
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 38023.56
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 349918.83
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 35254.50
19 Coil:Heating:Water CAV_BAS HEATING COIL 224508.07


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 318318.64 192693.24 125625.40 0.61 60289.17 611.49
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2995181.38 1808789.07 1186392.31 0.60 555936.37 5638.62
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 323893.22 196208.08 127685.15 0.61 61650.53 625.29
4 Coil:Cooling:Water CAV_BAS COOLING COIL 183594.96 112450.46 71144.49 0.61 33193.76 336.67


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.2728269958 0.2457223644 Pass Pass 1.2461513590 1.8552331920 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 9.0641363049E-002 0.1778251424 Pass Pass 0.1190254564 0.3238452674 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 5.0471819849E-002 0.1093854315 Pass Pass 9.1359169945E-002 0.2878980088 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 2.1891179457E-002 1.4047255545E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 9.7211318868E-002 0.1676967231 Pass Pass 0.1186572405 0.3229390227 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.1528632980 0.2532769089 Pass Pass 0.1199799365 0.3255821503 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.1827897759 0.2927548957 Pass Pass 0.1208799443 0.3211012673 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.1796907770 0.3399629245 Pass Pass 0.1183732387 0.3184781729 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 5.6476698300E-002 8.1717353679E-002 Pass Pass 9.0933065753E-002 0.2865341116 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.1017683898 0.1542818064 Pass Pass 9.1408971908E-002 0.2886814045 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.1597932309 0.2089430518 Pass Pass 9.2196482225E-002 0.2881847565 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.1144899381 0.2006231542 Pass Pass 8.9332097142E-002 0.2793267238 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 3.7695126891E-002 2.6493813166E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 5.1373793194E-002 6.9898738237E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.1107240610 9.7572363493E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 7.6825467655E-002 7.4640467883E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 2.0453710633E-002 2.6778167422E-002 Pass Pass 0.1275626896 0.3308188560 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 1.5071002843E-002 1.7847730839E-002 Pass Pass 0.1544397953 0.5234593951 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.0740158218E-002 5.2426744217E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 6.0328812332E-006 7.0698492787E-006 Pass Pass 4.0578530385E-003 4.6108001397E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 5.2069010897E-006 5.8895014211E-006 Pass Pass 1.4058124524E-002 1.2283302153E-002 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 3.2090588454E-003 7.4496791629E-003 Pass Pass 0.1667502850 0.5353967326 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 3.2265975312E-005 6.3176054420E-005 Pass Pass 4.0967436072E-005 1.0573199554E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 6267.76 84.81 0.00 14315.38 26587.69 47255.62



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB -5.20 0.00 -5.20 Wetbulb [C] 2.20 20.00
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 38.10 13.00 18.10 Wetbulb [C] 3.90 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 3.00 6      
Feb 3.00 4      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 18.00 7      
Jul 27.00 16      
Aug 41.00 15      
Sep 0.00 0      
Oct 23.00 18      
Nov 0.00 0      
Dec 7.00 7      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.168 1.416 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.168 1.416 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.168 1.416 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.168 1.416 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.221 0.228 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.4644_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.4644_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.4644_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.4644_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.4644_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.4644_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.4644_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 869.21 2.640 0.251 0.251             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.4644_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 579.48 2.640 0.251 0.251             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.4644_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 869.21 2.640 0.251 0.251             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.4644_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 579.48 2.640 0.251 0.251             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.4644_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 86.92 2.640 0.251 0.251             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.4644_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 57.95 2.640 0.251 0.251             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.4644_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 86.92 2.640 0.251 0.251             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.4644_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 57.95 2.640 0.251 0.251             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 2.640 0.251 0.251                      
North Total or Average             1043.06 2.640 0.251 0.251                      
Non-North Total or Average             2433.80 2.640 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.3279 2779.43 25926.33 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 240.45
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 9.3279 2496.12 23283.67 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 215.94
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 9.3279 24961.20 232836.67 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 2159.39
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 9.3279 2496.12 23283.67 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 215.94
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 9.3279 313.41 2923.50 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.15 0.0000 Y 18.74
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.14 0.0000 Y 12.07
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 9.3279 313.42 2923.56 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.79 0.0000 Y 18.54
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.88 0.0000 Y 11.98
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 9.3279 3134.13 29234.97 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.18 0.0000 Y 187.57
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 9.3279 2019.75 18840.12 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.15 0.0000 Y 120.79
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 9.3279 3134.20 29235.61 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.82 0.0000 Y 185.60
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 9.3279 2019.75 18840.12 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.89 0.0000 Y 119.87
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 9.3279 313.41 2923.50 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.18 0.0000 Y 18.76
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.15 0.0000 Y 12.08
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 9.3279 313.42 2923.56 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.82 0.0000 Y 18.56
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.90 0.0000 Y 11.99
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 9.3279 783.68 7310.12 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 67.80
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 16.0861 36.20 582.36 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 5.97
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 16.0861 362.03 5823.61 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 59.65
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 16.0861 36.20 582.36 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 5.97
Interior Lighting Total       9.3913 46320.38 435009.77               1158.06


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.56 1127.62
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.56 0.00
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.50 1127.59
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.50 0.00
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.56 1127.62
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.56 0.00
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.50 1127.59
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.50 0.00
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.56 1127.62
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.56 0.00
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.50 1127.59
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.50 0.00
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 9973.01 AstronomicalClock -   41.77 41.77 78.19
EXTERIOR_LIGHTS_B 44362.79 AstronomicalClock -   83.77 71.17 592.64
Exterior Lighting Total 54335.80           670.83



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2433623.67          
HEATSYS1 BOILER Boiler:HotWater 2107019.60 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1244624.78 6.28 1191268.53 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1244624.78 6.28 1191268.53 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 577236.29 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1477958.59          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1477958.59          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 200241.47 318318.64 192693.24 125625.40 0.61 - 60289.17 611.49
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 1922978.56 2995181.38 1808789.07 1186392.31 0.60 - 555936.37 5638.62
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 202662.09 323893.22 196208.08 127685.15 0.61 - 61650.53 625.29
CAV_BAS COOLING COIL Coil:Cooling:Water 113351.07 183594.96 112450.46 71144.49 0.61 - 33193.76 336.67
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   468177.58 260807.64 207369.94 0.56 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   10168.68 5698.97 4469.71 0.56 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   96799.67 54220.49 42579.18 0.56 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9794.57 5486.50 4308.07 0.56 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 18084.44 17149.57 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 415731.93 393981.41 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 82750.01 78435.55 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 10415.18 9871.88 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 7981.05 7561.80 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 12628.20 11968.94 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 7193.45 6818.74 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 198631.58 188243.39 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 131841.87 124946.07 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 196737.74 186448.90 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 123010.91 116578.27 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 26097.83 24731.96 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 17215.37 16314.32 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 25869.17 24515.30 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 16481.98 15619.40 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 48095.57 38023.56 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 441299.86 349918.83 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 43804.14 35254.50 -
CAV_BAS HEATING COIL Coil:Heating:Water 283149.33 224508.07 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   468177.58 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   10168.68 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   96799.67 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9794.57 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   16051.03 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   741.49 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   7414.91 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   741.49 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 11.03 23717.53 2149.46 1.00 1.12 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 103.10 221610.91 2149.46 1.00 1.08 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 11.25 24183.32 2149.46 1.00 1.12 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 6.59 11101.34 1684.71 1.00 1.16 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 24.65 40658.54 1649.25 1.00 1.14 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.55 611.10 1120.11 1.00 1.57 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 5.19 5811.03 1120.11 1.00 1.15 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.52 587.98 1120.11 1.00 1.58 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.103771 21383.28 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.018433 5551.25 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.103771 14804.36 142664.32 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.014325 3653.63 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 3168.45 0.000440 5.96 13540.37 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.123184 37100.26 301178.23 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.50 0.08



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 79113.14 79113.14 28.46 6.589 6.589 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00744 28.48 0.00686 1.200 0.00
CORE_BOTTOM 82888.56 82888.56 33.21 6.903 6.903 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00738 28.48 0.00686 1.078 0.00
CORE_MID 782887.46 782887.46 313.64 65.188 65.188 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00740 28.48 0.00686 10.778 0.00
CORE_TOP 77580.11 77580.11 31.08 6.460 6.460 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00740 28.48 0.00686 1.078 0.00
PERIMETER_BOT_ZN_3 14104.12 14104.12 45.00 1.185 1.185 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00726 38.10 0.00687 0.135 0.00
PERIMETER_BOT_ZN_2 12753.14 12753.14 63.14 1.071 1.071 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00719 32.05 0.00686 0.087 0.00
PERIMETER_BOT_ZN_1 15502.98 15502.98 49.46 1.302 1.302 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 24.00 24.00 0.00724 37.77 0.00687 0.135 0.00
PERIMETER_BOT_ZN_4 16747.01 16747.01 82.92 1.407 1.407 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 24.00 24.00 0.00714 36.80 0.00687 0.087 0.00
PERIMETER_MID_ZN_3 133966.05 133966.05 427.44 11.254 11.254 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00727 38.10 0.00687 1.353 0.00
PERIMETER_MID_ZN_2 131299.45 131299.45 650.08 11.030 11.030 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 24.00 24.00 0.00718 32.42 0.00686 0.872 0.00
PERIMETER_MID_ZN_1 147256.67 147256.67 469.84 12.370 12.370 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 24.00 0.00724 37.88 0.00687 1.353 0.00
PERIMETER_MID_ZN_4 142215.61 142215.61 704.12 11.947 11.947 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 24.00 24.00 0.00716 36.63 0.00687 0.872 0.00
PERIMETER_TOP_ZN_3 15390.79 15390.79 49.11 1.293 1.293 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00723 37.84 0.00687 0.135 0.00
PERIMETER_TOP_ZN_2 13524.19 13524.19 66.96 1.136 1.136 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 24.00 24.00 0.00717 33.16 0.00686 0.087 0.00
PERIMETER_TOP_ZN_1 16605.66 16605.66 52.98 1.395 1.395 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00721 38.10 0.00687 0.135 0.00
PERIMETER_TOP_ZN_4 15571.99 15571.99 77.10 1.308 1.308 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 24.00 24.00 0.00715 36.63 0.00687 0.087 0.00
DATACENTER_BOT_ZN_6 8235.05 8235.05 227.47 0.546 0.546 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 27.00 27.00 0.00700 25.19 0.00685 0.016 0.00
DATACENTER_MID_ZN_6 78307.77 78307.77 2163.03 5.188 5.188 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 27.00 27.00 0.00700 25.19 0.00685 0.156 0.00
DATACENTER_TOP_ZN_6 7922.48 7922.48 218.84 0.525 0.525 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 27.00 27.00 0.00709 34.33 0.00687 0.016 0.00
DATACENTER_BASEMENT_ZN_6 372073.04 372073.04 474.78 24.652 24.652 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00704 26.27 0.00685 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 24.37 0.00281 -5.20 0.00281 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:20:00 19.60 21.77 0.00281 -5.20 0.00281 1.078 0.00
CORE_MID 243820.72 243820.72 97.68 11.853 11.853 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -5.20 0.00281 10.778 0.00
CORE_TOP 57947.02 57947.02 23.21 2.840 2.840 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -5.20 0.00281 1.078 0.00
PERIMETER_BOT_ZN_3 7295.17 7295.17 23.28 0.358 0.358 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00759 -5.20 0.00281 0.135 0.00
PERIMETER_BOT_ZN_2 5176.59 5176.59 25.63 0.254 0.254 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00766 -5.20 0.00281 0.087 0.00
PERIMETER_BOT_ZN_1 8842.21 8842.21 28.21 0.434 0.434 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00773 -5.20 0.00281 0.135 0.00
PERIMETER_BOT_ZN_4 3513.54 3513.54 17.40 0.172 0.172 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00728 -5.20 0.00281 0.087 0.00
PERIMETER_MID_ZN_3 139012.97 139012.97 443.55 6.831 6.831 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00775 -5.20 0.00281 1.353 0.00
PERIMETER_MID_ZN_2 92267.64 92267.64 456.83 4.535 4.535 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00775 -5.20 0.00281 0.872 0.00
PERIMETER_MID_ZN_1 137689.04 137689.04 439.31 6.766 6.766 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00774 -5.20 0.00281 1.353 0.00
PERIMETER_MID_ZN_4 86093.86 86093.86 426.26 4.230 4.230 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00772 -5.20 0.00281 0.872 0.00
PERIMETER_TOP_ZN_3 18260.82 18260.82 58.26 0.898 0.898 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 -5.20 0.00281 0.135 0.00
PERIMETER_TOP_ZN_2 12045.55 12045.55 59.64 0.592 0.592 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00776 -5.20 0.00281 0.087 0.00
PERIMETER_TOP_ZN_1 18100.96 18100.96 57.75 0.890 0.890 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00776 -5.20 0.00281 0.135 0.00
PERIMETER_TOP_ZN_4 11532.78 11532.78 57.10 0.567 0.567 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00775 -5.20 0.00281 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:30:00 18.00 26.18 0.00700 -5.20 0.00281 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 05:40:00 18.00 23.13 0.00438 -5.20 0.00281 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 05:40:00 18.00 21.23 0.00321 -5.20 0.00281 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:30:00 18.00 27.00 0.00700 -5.20 0.00281 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 11.03 11.03 2.29 2.29 11.0342 3.5606 11.0342 0.3227 0.3000
VAV_MID WITH REHEAT 103.10 103.10 34.22 34.22 103.1005 34.2157 103.1005 0.3319 0.3000
VAV_TOP WITH REHEAT 11.25 11.25 5.79 5.79 11.2509 5.7879 11.2509 0.5144 0.3000
CAV_BAS 6.59 6.59 1.20 1.20 6.5894 6.5894 6.5894 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 24.65 24.65 0.34 0.34 24.6528 24.6525 24.6528 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.55 0.55 0.02 0.02 0.5456 0.5456 0.5456 1.0000 1.0000
AIRLOOP DATACENTER MID 5.19 5.19 0.16 0.16 5.1879 5.1879 5.1879 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.52 0.52 0.02 0.02 0.5249 0.5249 0.5249 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 18084.440 18084.440 2.070978 0.00015821 364.568 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:20:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:20:00 18084.44 18084.44 2.070978 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00800000 44.8527 0.00 0.00 18151.12 18151.12
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 415731.926 415731.926 19.686771 0.00363700 9762.381 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 415731.93 415731.93 19.686771 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00800000 44.8527 243820.72 0.00 417095.05 417095.05
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 82750.009 82750.009 2.840366 0.00072393 2184.315 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 82750.01 82750.01 2.840366 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00800000 44.8527 57947.02 0.00 83035.73 83035.73
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 10415.175 10415.175 0.357607 0.00009112 274.886 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 10415.18 10415.18 0.357607 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00759458 42.6100 7295.17 0.00 10450.86 10450.86
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 7981.048 7981.048 0.321396 0.00006982 197.432 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 7981.05 7981.05 0.321396 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00766183 42.9824 5176.59 0.00 8006.08 8006.08
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 12628.195 12628.195 0.433814 0.00011048 333.216 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 12628.20 12628.20 0.433814 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00773487 43.3867 8842.21 0.00 12670.90 12670.90
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 7193.448 7193.448 0.422045 0.00006293 160.131 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 7193.45 7193.45 0.422045 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00727595 40.8438 3513.54 0.00 7218.16 7218.16
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 198631.577 198631.577 6.831399 0.00173772 5238.462 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 198631.58 198631.58 6.831399 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00774537 43.4454 139012.97 0.00 199283.43 199283.43
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 131841.870 131841.870 4.534616 0.00115341 3476.939 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 131841.87 131841.87 4.534616 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00774612 43.4496 92267.64 0.00 132273.86 132273.86
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 196737.737 196737.737 6.766138 0.00172115 5188.562 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 196737.74 196737.74 6.766138 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00774237 43.4288 137689.04 0.00 197383.70 197383.70
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 123010.914 123010.914 4.230347 0.00107615 3244.236 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 123010.91 123010.91 4.230347 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00772300 43.3217 86093.86 0.00 123415.32 123415.32
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 26097.826 26097.826 0.897981 0.00022832 688.126 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 26097.83 26097.83 0.897981 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00776699 43.5655 18260.82 0.00 26182.42 26182.42
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 17215.369 17215.369 0.592373 0.00015061 453.913 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 17215.37 17215.37 0.592373 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00776476 43.5533 12045.55 0.00 17271.12 17271.12
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 25869.175 25869.175 0.890102 0.00022631 682.101 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 25869.17 25869.17 0.890102 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00776496 43.5543 18100.96 0.00 25953.06 25953.06
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 16481.981 16481.981 0.567106 0.00014419 434.587 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 16481.98 16481.98 0.567106 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00775441 43.4959 11532.78 0.00 16535.43 16535.43
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 200241.472 -999.000 11.034158 0.00851874 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 200241.47 194826.52 11.034158 27.28 14.99 0.00722874 10.78 8.48 0.00700000 38.10 0.00687148 18.17 22.3484 24.00 0.00733698 34.3191 126245.69 0.00 225753.80 218068.93
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 48095.575 48095.575 3.310247 0.00042076 801.994 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 48095.57 48095.57 3.310247 -1.05 -1.83 0.00345839 12.80 10.33 0.00800000 -5.20 0.00280840 -5.20 74.4947 21.30 0.00583997 32.2527 24827.52 0.00 46004.57 46004.57
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1922978.558 -999.000 103.100516 0.08180795 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 1922978.56 1870231.18 103.100516 27.73 15.15 0.00723713 10.78 8.48 0.00700000 38.10 0.00687148 18.17 24.6186 24.00 0.00736873 34.4658 1141699.12 0.00 2162412.44 2087608.33
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 441299.863 441299.863 30.930155 0.00386068 7369.328 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 441299.86 441299.86 30.930155 -0.80 -1.36 0.00368770 12.80 10.33 0.00800000 -5.20 0.00280840 -5.20 82.0621 19.60 0.00756300 46.2718 371641.40 0.00 423388.75 423388.75
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 202662.087 -999.000 11.250858 0.00862171 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 202662.09 197497.36 11.250858 27.19 14.95 0.00721430 10.78 8.48 0.00700000 38.10 0.00687148 18.17 22.5600 24.00 0.00731446 34.2149 133621.38 0.00 228641.78 221254.39
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 43804.143 43804.143 3.375257 0.00038322 736.974 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 43804.14 43804.14 3.375257 0.43 -0.25 0.00402114 12.80 10.33 0.00800000 -5.20 0.00280840 -5.20 75.1999 17.60 0.00762379 52.8607 49738.79 0.00 42661.24 42661.24
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 113351.068 -999.000 6.589448 0.00482222 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 113351.07 108494.93 6.589448 26.51 14.84 0.00735486 11.22 8.66 0.00700000 36.41 0.00686877 17.66 18.2133 24.00 0.00747816 34.9719 70609.30 0.00 128227.08 123259.75
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 283149.333 283149.333 6.589448 0.00247711 6303.866 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 283149.33 283149.33 6.589448 -0.95 -2.76 0.00280840 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 18.2133 24.44 0.00280840 12.8888 0.00 0.00 237140.65 237140.65
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 468177.578 260807.636 24.652793 0.01146564 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 406165.40 404339.97 -999.0 28.76 15.34 0.00703978 12.80 9.33 0.00700000 38.10 0.00687148 18.17 -999.0000 27.00 0.00704212 27.5795 371587.01 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10168.683 5698.969 0.545575 0.00024903 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 8791.38 8708.44 -999.0 28.30 15.22 0.00708222 12.80 9.33 0.00700000 34.33 0.00686546 17.01 -999.0000 27.00 0.00708869 27.7579 8141.91 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 96799.669 54220.493 5.187918 0.00237062 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 83705.67 82877.97 -999.0 28.31 15.23 0.00708625 12.80 9.33 0.00700000 34.33 0.00686546 17.01 -999.0000 27.00 0.00709319 27.7756 77462.33 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9794.570 5486.503 0.524932 0.00023987 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 8469.71 8387.71 -999.0 28.32 15.23 0.00708445 12.80 9.33 0.00700000 34.66 0.00686598 17.11 -999.0000 27.00 0.00709116 27.7676 7920.29 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 468177.578 468177.578 24.652793 0.01146564 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 468177.58 468177.58 24.652793 -5.20 -5.20 0.00280840 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 1.3726 27.00 0.00700000 27.4118 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10168.683 10168.683 0.545575 0.00024903 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 10168.68 10168.68 0.545575 -5.20 -5.20 0.00280840 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 2.8653 26.58 0.00699756 28.0954 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 96799.669 96799.669 5.187918 0.00237062 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 96799.67 96799.67 5.187918 -5.20 -5.20 0.00280840 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 3.0132 24.34 0.00438158 20.1803 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9794.570 9794.570 0.524932 0.00023987 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 9794.57 9794.57 0.524932 -5.20 -5.20 0.00280840 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 2.9780 23.10 0.00320690 15.9387 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 16051.031 16051.031 -999.0 -999.0 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 16051.03 16051.03 24.652793 -0.07 -0.07 0.00694246 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 1.3726 27.00 0.00700000 27.4118 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 741.491 741.491 -999.0 -999.0 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 741.49 741.49 0.545575 -0.15 -0.15 0.00687753 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 2.8653 26.58 0.00699756 28.0954 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 7414.911 7414.911 -999.0 -999.0 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 7414.91 7414.91 5.187918 -0.16 -0.16 0.00433418 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 3.0132 24.34 0.00438158 20.1803 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 741.491 741.491 -999.0 -999.0 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 741.49 741.49 0.524932 -0.15 -1.75 0.00319503 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 2.9780 23.10 0.00320690 15.9387 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 18084.440 18084.440 2.070978 0.00015821 364.568 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 0.8414 0.858295 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:20:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:20:00 Sensible 18084.44 18084.44 1.0000 2.16278754 2.070978 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.15819443 60.00 32.22 27.78 0.000 18084.44 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 44.8527 0.00 0.00 18151.12 18151.12 2.16278754 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 415731.926 415731.926 19.686771 0.00363700 9762.381 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 19.3415 19.730805 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 415731.93 415731.93 1.0000 20.55951998 19.686771 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 3.63663324 60.00 32.22 27.78 0.000 415731.93 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.81 0.00800000 21.00 0.00800000 44.8527 243820.72 0.00 417095.05 417095.05 20.55951998 12.80 11.60 0.00800000 33059.8 32.70 18.92 0.00800000 53347.0
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 82750.009 82750.009 2.840366 0.00072393 2184.315 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 3.8499 3.927349 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 82750.01 82750.01 1.0000 2.96628462 2.840366 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.72385933 60.00 32.22 27.78 0.000 82750.01 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 44.8527 57947.02 0.00 83035.73 83035.73 2.96628462 12.80 11.60 0.00800000 33059.8 40.25 21.26 0.00800000 61053.0
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 10415.175 10415.175 0.357607 0.00009112 274.886 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 0.4846 0.494308 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 10415.18 10415.18 1.0000 0.37346022 0.357607 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.09110720 60.00 32.22 27.78 0.000 10415.18 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.91 0.00759458 21.00 0.00759458 42.6100 7295.17 0.00 10450.86 10450.86 0.37346022 12.80 11.60 0.00800000 33059.8 40.24 21.25 0.00800000 61043.7
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 7981.048 7981.048 0.321396 0.00006982 197.432 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 0.3713 0.378784 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 7981.05 7981.05 1.0000 0.33564359 0.321396 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.06981457 60.00 32.22 27.78 0.000 7981.05 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.91 0.00766183 21.00 0.00766183 42.9824 5176.59 0.00 8006.08 8006.08 0.33564359 12.80 11.60 0.00800000 33059.8 36.19 20.03 0.00800000 56912.7
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 12628.195 12628.195 0.433814 0.00011048 333.216 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 0.5875 0.599339 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 12628.20 12628.20 1.0000 0.45304538 0.433814 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.11046569 60.00 32.22 27.78 0.000 12628.20 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.91 0.00773487 21.00 0.00773487 43.3867 8842.21 0.00 12670.90 12670.90 0.45304538 12.80 11.60 0.00800000 33059.8 40.23 21.25 0.00800000 61028.1
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 7193.448 7193.448 0.422045 0.00006293 160.131 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 0.3347 0.341404 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 7193.45 7193.45 1.0000 0.44075459 0.422045 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.06292500 60.00 32.22 27.78 0.000 7193.45 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.92 0.00727595 21.00 0.00727595 40.8438 3513.54 0.00 7218.16 7218.16 0.44075459 12.80 11.60 0.00800000 33059.8 28.86 17.65 0.00800000 49436.6
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 198631.577 198631.577 6.831399 0.00173772 5238.462 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 9.2412 9.427135 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 198631.58 198631.58 1.0000 7.13424713 6.831399 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 1.73753842 60.00 32.22 27.78 0.000 198631.58 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00774537 21.00 0.00774537 43.4454 139012.97 0.00 199283.43 199283.43 7.13424713 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60993.2
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 131841.870 131841.870 4.534616 0.00115341 3476.939 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 6.1338 6.257268 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 131841.87 131841.87 1.0000 4.73564287 4.534616 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 1.15329253 60.00 32.22 27.78 0.000 131841.87 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00774612 21.00 0.00774612 43.4496 92267.64 0.00 132273.86 132273.86 4.73564287 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60991.4
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 196737.737 196737.737 6.766138 0.00172115 5188.562 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 9.1530 9.337252 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 196737.74 196737.74 1.0000 7.06609218 6.766138 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 1.72097197 60.00 32.22 27.78 0.000 196737.74 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00774237 21.00 0.00774237 43.4288 137689.04 0.00 197383.70 197383.70 7.06609218 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60993.8
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 123010.914 123010.914 4.230347 0.00107615 3244.236 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 5.7230 5.838148 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 123010.91 123010.91 1.0000 4.41788582 4.230347 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 1.07604336 60.00 32.22 27.78 0.000 123010.91 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00772300 21.00 0.00772300 43.3217 86093.86 0.00 123415.32 123415.32 4.41788582 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60995.2
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 26097.826 26097.826 0.897981 0.00022832 688.126 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 1.2142 1.238613 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 26097.83 26097.83 1.0000 0.93779030 0.897981 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.22829187 60.00 32.22 27.78 0.000 26097.83 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00776699 21.00 0.00776699 43.5655 18260.82 0.00 26182.42 26182.42 0.93779030 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60979.1
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 17215.369 17215.369 0.592373 0.00015061 453.913 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 0.8009 0.817048 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 17215.37 17215.37 1.0000 0.61863407 0.592373 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.15059219 60.00 32.22 27.78 0.000 17215.37 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00776476 21.00 0.00776476 43.5533 12045.55 0.00 17271.12 17271.12 0.61863407 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60978.0
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 25869.175 25869.175 0.890102 0.00022631 682.101 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 1.2035 1.227761 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 25869.17 25869.17 1.0000 0.92956190 0.890102 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.22629174 60.00 32.22 27.78 0.000 25869.17 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00776496 21.00 0.00776496 43.5543 18100.96 0.00 25953.06 25953.06 0.92956190 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60979.5
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 16481.981 16481.981 0.567106 0.00014419 434.587 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 0.7668 0.782241 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 16481.98 16481.98 1.0000 0.59224694 0.567106 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.14417685 60.00 32.22 27.78 0.000 16481.98 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00775441 21.00 0.00775441 43.4959 11532.78 0.00 16535.43 16535.43 0.59224694 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60979.7
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 200241.472 -999.000 11.034158 0.00851874 -999.000 -999.0000 1.00000 1.00000 1018.2779 1004.8586 1.0443 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 11.034158 11.52332155   4197.9300 999.8980 103.76003281 12.27 6.67 5.60 2439233.19 8.2092 8.209198 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 200241.47 194826.52 1.0000 11.52332155 11.034158 27.28 14.99 0.00722874 45854.8 10.78 8.48 0.00700000 28477.7 8.51786611 6.67 12.27 5.60 23717.532 176523.94 38.10 0.00687148 18.17 2.46596000 22.3484 24.00 0.00733698 24.00 0.00733698 34.3191 126245.69 0.00 225753.80 218068.93 11.52332155 27.28 16.46 0.00722874 45854.8 8.69 8.67 0.00696380 26263.8
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 48095.575 48095.575 3.310247 0.00042076 801.994 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 11.034158 11.52332155   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 2.2376 2.282635 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 48095.57 48095.57 1.0000 3.45699646 3.310247 -1.05 -1.83 0.00345839 7592.2 12.80 10.33 0.00800000 33059.8 0.42071815 60.00 32.22 27.78 0.000 48095.57 -5.20 0.00280840 -5.20 2.46596000 74.4947 11.09 0.00535688 21.30 0.00583997 32.2527 24827.52 0.00 46004.57 46004.57 3.45699646 2.80 1.18 0.00345839 11480.8 15.96 8.06 0.00345839 24788.5
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1922978.558 -999.000 103.100516 0.08180795 -999.000 -999.0000 1.00000 1.00000 1018.2935 1004.8586 1.0443 VAV_MID WITH REHEAT FAN Fan:VariableVolume 103.100516 107.67114068   4197.9300 999.8980 103.76003281 12.27 6.67 5.60 2439233.19 78.8354 78.835372 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 1922978.56 1870231.18 1.0000 107.67114068 103.100516 27.73 15.15 0.00723713 46337.5 10.78 8.48 0.00700000 28477.8 81.79960795 6.67 12.27 5.60 221610.906 1701367.65 38.10 0.00687148 18.17 25.38195000 24.6186 24.00 0.00736873 24.00 0.00736873 34.4658 1141699.12 0.00 2162412.44 2087608.33 107.67114068 27.73 16.62 0.00723713 46337.5 8.69 8.67 0.00696112 26254.0
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 441299.863 441299.863 30.930155 0.00386068 7369.328 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 VAV_MID WITH REHEAT FAN Fan:VariableVolume 103.100516 107.67114068   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 20.5311 20.944269 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 441299.86 441299.86 1.0000 32.30134221 30.930155 -0.80 -1.36 0.00368770 8417.5 12.80 10.33 0.00800000 33059.8 3.86028988 60.00 32.22 27.78 0.000 441299.86 -5.20 0.00280840 -5.20 25.38195000 82.0621 19.35 0.00771033 19.60 0.00756300 46.2718 371641.40 0.00 423388.75 423388.75 32.30134221 2.80 1.51 0.00368770 12055.5 15.76 8.23 0.00368770 25162.9
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 202662.087 -999.000 11.250858 0.00862171 -999.000 -999.0000 1.00000 1.00000 1018.2510 1004.8586 1.0443 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 11.250858 11.74962809   4197.9300 999.8980 103.76003281 12.27 6.67 5.60 2439233.19 8.3084 8.308434 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 Sensible 202662.09 197497.36 1.0000 11.74962809 11.250858 27.19 14.95 0.00721430 45726.1 10.78 8.48 0.00700000 28477.7 8.62083418 6.67 12.27 5.60 24183.321 178478.77 38.10 0.00687148 18.17 2.53819000 22.5600 24.00 0.00731446 24.00 0.00731446 34.2149 133621.38 0.00 228641.78 221254.39 11.74962809 27.19 16.41 0.00721430 45726.1 8.69 8.68 0.00696451 26266.6
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 43804.143 43804.143 3.375257 0.00038322 736.974 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 11.250858 11.74962809   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 2.0379 2.078962 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 43804.14 43804.14 1.0000 3.52488843 3.375257 0.43 -0.25 0.00402114 10495.0 12.80 10.33 0.00800000 33059.8 0.38317866 60.00 32.22 27.78 0.000 43804.14 -5.20 0.00280840 -5.20 2.53819000 75.1999 17.51 0.00769849 17.60 0.00762379 52.8607 49738.79 0.00 42661.24 42661.24 3.52488843 2.80 1.98 0.00402114 12891.1 14.76 8.14 0.00402114 24994.0
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 113351.068 -999.000 6.589448 0.00482222 -999.000 -999.0000 1.00000 1.00000 1018.5123 1004.8586 1.0443 CAV_BAS FAN Fan:ConstantVolume 6.589448 6.88156996   4197.9300 999.8980 103.76003281 12.27 6.67 5.60 2439233.19 4.6470 4.646996 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 113351.07 108494.93 1.0000 6.88156996 6.589448 26.51 14.84 0.00735486 45394.6 11.22 8.66 0.00700000 28922.9 4.82172457 6.67 12.27 5.60 11101.340 102249.73 36.41 0.00686877 17.66 1.20015641 18.2133 24.00 0.00747816 24.00 0.00747816 34.9719 70609.30 0.00 128227.08 123259.75 6.88156996 26.51 16.29 0.00735486 45394.6 8.92 8.90 0.00706814 26761.2
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 283149.333 283149.333 6.589448 0.00247711 6303.866 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 CAV_BAS FAN Fan:ConstantVolume 6.589448 6.88156996   4197.9300 999.8980 18.43124628 54.44 82.22 27.78 2149424.21 13.1733 13.438381 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 283149.33 283149.33 1.0000 6.88156996 6.589448 -0.95 -2.76 0.00280840 6067.0 40.00 19.53 0.00800000 60796.0 2.47686119 60.00 32.22 27.78 0.000 283149.33 -5.20 0.00280840 -5.20 1.20015641 18.2133 0.00 0.00280840 24.44 0.00280840 12.8888 0.00 0.00 237140.65 237140.65 6.88156996 12.80 5.73 0.00280840 19952.4 46.92 19.39 0.00280840 54412.7
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 468177.578 260807.636 24.652793 0.01146564 -999.000 -999.0000 -999.00000 -999.00000 1017.9266 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 406165.40 404339.97 0.8675 -999.0 -999.0 28.76 15.34 0.00703978 46878.6 12.80 9.33 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 406165.40 38.10 0.00687148 18.17 0.33839277 -999.0000 27.00 0.00704212 27.00 0.00704212 27.5795 371587.01 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 10168.683 5698.969 0.545575 0.00024903 -999.000 -999.0000 -999.00000 -999.00000 1018.0055 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 Sensible 8791.38 8708.44 0.8646 -999.0 -999.0 28.30 15.22 0.00708222 46524.3 12.80 9.33 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8791.38 34.33 0.00686546 17.01 0.01563234 -999.0000 27.00 0.00708869 27.00 0.00708869 27.7579 8141.91 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 96799.669 54220.493 5.187918 0.00237062 -999.000 -999.0000 -999.00000 -999.00000 1018.0130 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 Sensible 83705.67 82877.97 0.8647 -999.0 -999.0 28.31 15.23 0.00708625 46545.6 12.80 9.33 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 83705.67 34.33 0.00686546 17.01 0.15632344 -999.0000 27.00 0.00709319 27.00 0.00709319 27.7756 77462.33 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9794.570 5486.503 0.524932 0.00023987 -999.000 -999.0000 -999.00000 -999.00000 1018.0096 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 Sensible 8469.71 8387.71 0.8647 -999.0 -999.0 28.32 15.23 0.00708445 46546.0 12.80 9.33 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8469.71 34.66 0.00686598 17.11 0.01563234 -999.0000 27.00 0.00709116 27.00 0.00709116 27.7676 7920.29 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 468177.578 468177.578 24.652793 0.01146564 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 468177.58 468177.58 1.0000 25.74569362 24.652793 -5.20 -5.20 0.00280840 1771.3 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 468177.58 -5.20 0.00280840 -5.20 0.33839277 1.3726 0.00 0.00700000 27.00 0.00700000 27.4118 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 10168.683 10168.683 0.545575 0.00024903 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 10168.68 10168.68 1.0000 0.56976118 0.545575 -5.20 -5.20 0.00280840 1771.3 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10168.68 -5.20 0.00280840 -5.20 0.01563234 2.8653 0.00 0.00699756 26.58 0.00699756 28.0954 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 96799.669 96799.669 5.187918 0.00237062 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 96799.67 96799.67 1.0000 5.41790737 5.187918 -5.20 -5.20 0.00280840 1771.3 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 96799.67 -5.20 0.00280840 -5.20 0.15632344 3.0132 0.00 0.00438158 24.34 0.00438158 20.1803 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9794.570 9794.570 0.524932 0.00023987 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 9794.57 9794.57 1.0000 0.54820296 0.524932 -5.20 -5.20 0.00280840 1771.3 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9794.57 -5.20 0.00280840 -5.20 0.01563234 2.9780 0.00 0.00320690 23.10 0.00320690 15.9387 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 16051.031 16051.031 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 24.652793 25.74569362   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 16051.03 16051.03 1.0000 25.74569362 24.652793 -0.07 -0.07 0.00694246 17290.0 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 16051.03 -5.20 0.00280840 -5.20 0.33839277 1.3726 0.00 0.00700000 27.00 0.00700000 27.4118 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 741.491 741.491 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.545575 0.56976118   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 741.49 741.49 1.0000 0.56976118 0.545575 -0.15 -0.15 0.00687753 17048.7 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 741.49 -5.20 0.00280840 -5.20 0.01563234 2.8653 0.00 0.00699756 26.58 0.00699756 28.0954 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 7414.911 7414.911 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 5.187918 5.41790737   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 7414.91 7414.91 1.0000 5.41790737 5.187918 -0.16 -0.16 0.00433418 10680.8 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7414.91 -5.20 0.00280840 -5.20 0.15632344 3.0132 0.00 0.00438158 24.34 0.00438158 20.1803 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 741.491 741.491 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.524932 0.54820296   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 741.49 741.49 1.0000 0.54820296 0.524932 -0.15 -1.75 0.00319503 7834.1 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 741.49 -5.20 0.00280840 -5.20 0.01563234 2.9780 0.00 0.00320690 23.10 0.00320690 15.9387 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 11.03 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 103.10 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 11.25 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 1.20 6.59 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2858.17 1701.67 749.17
CORE_BOTTOM 2715.83 1449.33 636.83
CORE_MID 2182.17 2857.83 733.83
CORE_TOP 2353.50 3508.33 922.83
PERIMETER_BOT_ZN_3 2287.50 3268.50 492.83
PERIMETER_BOT_ZN_2 2605.00 2898.00 519.17
PERIMETER_BOT_ZN_1 2838.50 2144.17 529.50
PERIMETER_BOT_ZN_4 3287.50 1850.83 577.83
PERIMETER_MID_ZN_3 2681.83 3831.50 1220.83
PERIMETER_MID_ZN_2 2367.33 2901.33 810.50
PERIMETER_MID_ZN_1 2733.50 2557.50 701.67
PERIMETER_MID_ZN_4 2712.67 3391.33 863.83
PERIMETER_TOP_ZN_3 3406.17 3990.67 1965.33
PERIMETER_TOP_ZN_2 3303.17 3521.17 1489.00
PERIMETER_TOP_ZN_1 2969.83 2974.67 1085.67
PERIMETER_TOP_ZN_4 3196.00 3616.67 1439.67
DATACENTER_BOT_ZN_6 5943.00 727.67 727.67
DATACENTER_MID_ZN_6 5924.50 129.17 129.17
DATACENTER_TOP_ZN_6 5554.83 262.33 227.83
DATACENTER_BASEMENT_ZN_6 5943.00 5934.83 5934.83
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 82.00 0.00 3.67
CORE_BOTTOM 0.00 7.33 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 2.67 0.00 0.67
PERIMETER_BOT_ZN_2 0.00 24.83 0.00 24.67
PERIMETER_BOT_ZN_1 0.00 34.00 0.00 31.83
PERIMETER_BOT_ZN_4 0.00 142.33 0.00 49.83
PERIMETER_MID_ZN_3 1.17 0.83 0.00 0.17
PERIMETER_MID_ZN_2 1.00 31.33 0.00 31.00
PERIMETER_MID_ZN_1 0.00 24.33 0.00 23.67
PERIMETER_MID_ZN_4 0.00 37.33 0.00 22.00
PERIMETER_TOP_ZN_3 21.17 7.33 1.17 3.67
PERIMETER_TOP_ZN_2 15.67 51.33 0.00 46.17
PERIMETER_TOP_ZN_1 10.17 28.17 0.00 23.33
PERIMETER_TOP_ZN_4 10.83 46.17 0.00 25.33
DATACENTER_BOT_ZN_6 0.00 179.00 0.00 146.33
DATACENTER_MID_ZN_6 0.00 110.50 0.00 93.67
DATACENTER_TOP_ZN_6 0.00 113.33 0.00 93.00
DATACENTER_BASEMENT_ZN_6 0.00 1205.00 0.00 837.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 22.50 1474.00 1.17 979.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.54 149.60 6779.02 1.491 0.000 0.000 0.000
CORE_BOTTOM 56.16 134.35 6849.35 1.093 0.000 0.000 0.000
CORE_MID 56.16 134.35 6849.35 0.848 0.000 0.000 0.000
CORE_TOP 56.16 134.35 6849.35 0.762 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.05 16.87 860.00 1.041 0.040 0.000 0.000
PERIMETER_BOT_ZN_2 4.54 10.87 554.22 1.523 0.041 0.000 0.000
PERIMETER_BOT_ZN_1 7.05 16.87 860.02 1.531 0.040 0.000 0.000
PERIMETER_BOT_ZN_4 4.54 10.87 554.22 2.120 0.042 0.000 0.000
PERIMETER_MID_ZN_3 7.05 16.87 860.00 0.898 0.094 0.000 0.000
PERIMETER_MID_ZN_2 3.97 10.87 554.22 1.406 0.103 0.000 0.000
PERIMETER_MID_ZN_1 7.05 16.87 860.02 1.367 0.094 0.000 0.000
PERIMETER_MID_ZN_4 4.54 10.87 554.22 1.488 0.097 0.000 0.000
PERIMETER_TOP_ZN_3 7.05 16.87 860.00 0.948 0.116 0.000 0.000
PERIMETER_TOP_ZN_2 4.54 10.87 554.22 1.451 0.120 0.000 0.000
PERIMETER_TOP_ZN_1 7.05 16.87 860.02 1.322 0.116 0.000 0.000
PERIMETER_TOP_ZN_4 4.54 10.87 554.22 1.522 0.120 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.63 42.18 1911.37 0.481 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.54 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 56.16 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 56.16 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 56.16 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.05 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.05 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.05 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.97 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.05 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.05 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.05 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.54 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.63 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.54 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 56.16 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 56.16 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 56.16 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.05 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.05 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.05 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.97 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.05 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.05 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.05 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.63 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1036.48 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 64746469.38 0.00 64746469.38 0.00 64746469.38 37848132.68 3711.87 1682.32 3365.81 515.25
CORE_BOTTOM 48579354.02 0.00 48579354.02 0.00 48579354.02 33990283.35 4880.97 10.82 3868.21 701.63
CORE_MID 0.36E+09 0.00 0.36E+09 0.00 0.36E+09 0.34E+09 5702.96 31.72 3025.32 243.55
CORE_TOP 32004975.41 0.00 32004975.41 0.00 32004975.41 33990283.35 6008.57 22.64 2728.79 274.68
PERIMETER_BOT_ZN_3 6032048.45 0.00 6032048.45 398322.03 6430370.48 4267819.30 3323.02 40.91 5396.06 701.63
PERIMETER_BOT_ZN_2 5658482.12 0.00 5658482.12 265547.84 5924029.96 2750345.05 3178.16 8.83 5573.00 701.63
PERIMETER_BOT_ZN_1 8576355.69 0.00 8576355.69 398322.03 8974677.73 4267912.63 3183.01 9.44 5567.56 701.63
PERIMETER_BOT_ZN_4 7842591.73 0.00 7842591.73 265547.84 8108139.57 2750345.05 3159.50 0.00 5600.50 701.63
PERIMETER_MID_ZN_3 47856245.06 0.00 47856245.06 934163.77 48790408.83 42678193.03 3944.16 38.36 4777.48 243.55
PERIMETER_MID_ZN_2 50289689.45 0.00 50289689.45 622775.42 50912464.87 27503450.52 3732.60 1.50 5025.90 1152.55
PERIMETER_MID_ZN_1 71621860.99 0.00 71621860.99 934163.77 72556024.76 42679126.28 3779.30 7.92 4972.77 243.55
PERIMETER_MID_ZN_4 51130505.01 0.00 51130505.01 622775.42 51753280.43 27503450.52 3729.77 1.17 5029.06 243.55
PERIMETER_TOP_ZN_3 5053850.52 0.00 5053850.52 1159847.75 6213698.26 4267819.30 4035.39 33.02 4691.59 274.68
PERIMETER_TOP_ZN_2 4945613.29 0.00 4945613.29 773231.30 5718844.59 2750345.05 3837.70 4.13 4918.17 274.68
PERIMETER_TOP_ZN_1 6945265.51 0.00 6945265.51 1159847.75 8105113.26 4267912.63 3898.42 5.56 4856.02 274.68
PERIMETER_TOP_ZN_4 5221892.49 0.00 5221892.49 773231.30 5995123.79 2750345.05 3819.56 4.90 4935.54 274.68
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5288266.81 0.00 5288266.81 0.00 5288266.81 10671554.30 4419.00 4341.00 0.00 0.00
Total Facility 0.60E+10 0.00 0.60E+10 36332681.67 0.60E+10 0.50E+10 6532.06 4383.73 5848.80 1876.17


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.7552 0.0000 2.7552 0.0000 2.7552 1.2002 1283.78 1679.07 2980.15
CORE_BOTTOM 2.0401 0.0000 2.0401 0.0000 2.0401 1.0778 2699.49 8.30 3235.21
CORE_MID 15.8262 0.0000 15.8262 0.0000 15.8262 10.7782 3102.69 31.34 2808.97
CORE_TOP 1.4235 0.0000 1.4235 0.0000 1.4235 1.0778 3365.30 22.58 2555.11
PERIMETER_BOT_ZN_3 0.2442 0.0000 0.2442 0.0094 0.2536 0.1353 1195.76 37.28 4709.96
PERIMETER_BOT_ZN_2 0.2304 0.0000 0.2304 0.0063 0.2367 0.0872 1062.79 8.83 4871.37
PERIMETER_BOT_ZN_1 0.3594 0.0000 0.3594 0.0094 0.3687 0.1353 1061.95 8.63 4872.43
PERIMETER_BOT_ZN_4 0.3205 0.0000 0.3205 0.0063 0.3267 0.0872 1044.13 0.00 4898.87
PERIMETER_MID_ZN_3 2.1101 0.0000 2.1101 0.0220 2.1321 1.3533 1349.68 37.94 4555.37
PERIMETER_MID_ZN_2 2.1278 0.0000 2.1278 0.0156 2.1434 0.8721 1155.48 0.17 3878.35
PERIMETER_MID_ZN_1 3.2079 0.0000 3.2079 0.0220 3.2299 1.3533 1187.51 7.53 4747.96
PERIMETER_MID_ZN_4 2.2533 0.0000 2.2533 0.0147 2.2680 0.8721 1156.32 1.17 4785.52
PERIMETER_TOP_ZN_3 0.2231 0.0000 0.2231 0.0273 0.2505 0.1353 1410.80 31.94 4500.25
PERIMETER_TOP_ZN_2 0.2197 0.0000 0.2197 0.0182 0.2379 0.0872 1237.74 2.04 4703.22
PERIMETER_TOP_ZN_1 0.3105 0.0000 0.3105 0.0273 0.3378 0.1353 1276.21 4.55 4662.25
PERIMETER_TOP_ZN_4 0.2307 0.0000 0.2307 0.0182 0.2489 0.0872 1227.33 3.56 4712.11
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 0.2472 0.0000 0.2472 0.0000 0.2472 0.3384 1602.00 4341.00 0.00
Total Facility 265.0221 0.0000 265.0221 0.8655 265.8877 158.4706 3715.06 4367.02 4969.83


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 83639125.57 0.00 83639125.57 48026705.38 3191.15 4.27 5564.58 701.63
VAV_MID WITH REHEAT 0.63E+09 0.00 0.63E+09 0.48E+09 3804.20 5.88 4949.91 243.55
VAV_TOP WITH REHEAT 59081097.15 0.00 59081097.15 48026705.38 3920.57 2.92 4836.52 274.68
CAV_BAS 70614362.00 0.00 70614362.00 37848132.68 3692.91 4.46 5062.64 515.25
AIRLOOP DATACENTER BASEMENT 5767535.90 0.00 5767535.90 10671554.30 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER BOT 266436.27 0.00 266436.27 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 2664362.65 0.00 2664362.65 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 266436.27 0.00 266436.27 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.4841 0.0000 3.4841 1.5229 1059.97 1.61 4881.42
VAV_MID WITH REHEAT 27.9471 0.0000 27.9471 15.2292 1208.20 5.69 4729.11
VAV_TOP WITH REHEAT 2.6257 0.0000 2.6257 1.5229 1286.55 0.75 4655.70
CAV_BAS 3.0049 0.0000 3.0049 1.2002 1281.88 0.52 4660.60
AIRLOOP DATACENTER BASEMENT 0.2696 0.0000 0.2696 0.3384 1602.00 0.00 4341.00
AIRLOOP DATACENTER BOT 0.0125 0.0000 0.0125 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1245 0.0000 0.1245 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0125 0.0000 0.0125 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 0.38 4040.79 0.00 0.00 0.00 1559.33 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 0.09 3299.61 0.00 0.00 0.00 1731.36 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 0.06 3073.62 0.00 0.00 0.00 1950.08 0.00 0.00 0.00
CAV_BAS 0.00 1677.83 3512.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 0.0000 5.3766 0.0000 0.0000 0.0000 1.7634 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 0.0000 44.1249 0.0000 0.0000 0.0000 18.0497 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 0.0000 4.3248 0.0000 0.0000 0.0000 1.7965 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.3096 5.2258 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.3691 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0171 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.1705 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0171 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1380
Defaulted Fields 1179
Fields with Defaults 3862
Autosized Fields 330
Autosizable Fields 409
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 31718.32 398659.32 16-JAN-10:10 2043367.57 20-JUL-15:10
Electricity:Building 18921.07 251811.03 01-JAN-08:40 1146857.44 01-DEC-17:00
Electricity:Zone:BASEMENT 664.85 14623.97 01-JAN-00:10 34452.17 02-JAN-08:10
Electricity:SpaceType:GENERAL 18921.07 251811.03 01-JAN-08:40 1146857.44 01-DEC-17:00
InteriorLights:Electricity 3707.66 17601.77 01-JAN-08:40 352853.36 22-NOV-17:00
InteriorLights:Electricity:Zone:BASEMENT 240.45 1166.43 01-JAN-00:10 20994.62 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 3707.66 17601.77 01-JAN-08:40 352853.36 22-NOV-17:00
LightsWired:InteriorLights:Electricity 3707.66 17601.77 01-JAN-08:40 352853.36 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 240.45 1166.43 01-JAN-00:10 20994.62 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 3707.66 17601.77 01-JAN-08:40 352853.36 22-NOV-17:00
Electricity:Zone:CORE_BOTTOM 537.23 7090.40 01-JAN-00:10 36983.24 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
Electricity:Zone:CORE_MID 5372.24 70903.72 01-JAN-00:10 369831.68 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2159.40 10475.32 01-JAN-00:10 188546.48 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 2159.40 10475.32 01-JAN-00:10 188546.48 02-JAN-08:10
Electricity:Zone:CORE_TOP 537.22 7090.37 01-JAN-00:10 36983.17 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 59.08 839.57 01-JAN-08:30 4643.71 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 18.74 80.80 01-JAN-08:30 2367.39 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 18.74 80.80 01-JAN-08:30 2367.39 22-NOV-17:00
Electricity:Zone:PERIMETER_BOT_ZN_2 38.07 541.05 01-JAN-08:10 2992.58 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 12.08 52.07 01-JAN-08:10 1525.64 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 12.08 52.07 01-JAN-08:10 1525.64 22-NOV-17:00
Electricity:Zone:PERIMETER_BOT_ZN_1 58.89 839.58 01-JAN-08:00 4643.79 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 18.54 80.80 01-JAN-08:00 2367.44 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 18.54 80.80 01-JAN-08:00 2367.44 22-NOV-17:00
Electricity:Zone:PERIMETER_BOT_ZN_4 37.98 541.05 01-JAN-08:40 2992.57 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.98 52.07 01-JAN-08:40 1525.64 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 11.98 52.07 01-JAN-08:40 1525.64 22-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_3 591.00 8395.70 01-JAN-08:40 46437.07 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 187.57 807.98 01-JAN-08:40 23673.89 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 187.57 807.98 01-JAN-08:40 23673.89 22-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_2 380.77 5410.51 01-JAN-08:10 29925.82 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 120.79 520.69 01-JAN-08:10 15256.36 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 120.79 520.69 01-JAN-08:10 15256.36 22-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_1 589.03 8395.84 01-JAN-08:10 46437.94 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 185.60 807.99 01-JAN-08:10 23674.41 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 185.60 807.99 01-JAN-08:10 23674.41 22-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_4 379.85 5410.48 01-JAN-08:40 29925.72 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 119.87 520.69 01-JAN-08:40 15256.36 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 119.87 520.69 01-JAN-08:40 15256.36 22-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_3 59.10 839.57 01-JAN-08:40 4643.71 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 18.76 80.80 01-JAN-08:40 2367.39 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 18.76 80.80 01-JAN-08:40 2367.39 22-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_2 38.08 541.05 01-JAN-08:10 2992.58 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 12.08 52.07 01-JAN-08:10 1525.64 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 12.08 52.07 01-JAN-08:10 1525.64 22-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_1 58.90 839.58 01-JAN-08:10 4643.79 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 18.56 80.80 01-JAN-08:10 2367.44 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 18.56 80.80 01-JAN-08:10 2367.44 22-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_4 37.99 541.05 01-JAN-08:40 2992.57 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 11.99 52.07 01-JAN-08:40 1525.64 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 11.99 52.07 01-JAN-08:40 1525.64 22-NOV-17:00
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7562.65 95237.01 01-JAN-00:10 385552.11 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 67.80 328.88 01-JAN-00:10 5919.59 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 67.80 328.88 01-JAN-00:10 5919.59 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 159.85 1977.54 01-JAN-00:10 8315.27 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1598.46 19775.43 01-JAN-00:10 83152.69 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 59.65 289.38 01-JAN-00:10 5208.47 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 59.65 289.38 01-JAN-00:10 5208.47 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 159.85 1977.54 01-JAN-00:10 8315.27 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
InteriorEquipment:Electricity 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 3464.22 7300.62 28-JAN-05:00 519166.40 20-JUL-15:30
HeatRejection:Electricity 1398.97 3111.03 27-JAN-07:20 85424.98 21-APR-14:00
General:HeatRejection:Electricity 1398.97 3111.03 27-JAN-07:20 85424.98 21-APR-14:00
Electricity:HVAC 6807.59 102076.68 16-JAN-08:00 477576.75 20-JUL-15:10
ExteriorEquipment:Electricity 1941.93 28795.69 01-JAN-00:10 118951.09 13-OCT-07:20
Transformer:ExteriorEquipment:Electricity 87.32 1613.62 01-JAN-00:10 5480.49 11-DEC-17:00
ElectricityPurchased:Facility 31718.32 398659.32 16-JAN-10:10 2043367.57 20-JUL-15:10
ElectricityPurchased:Plant 31718.32 398659.32 16-JAN-10:10 2043367.57 20-JUL-15:10
Cogeneration:ElectricityPurchased 31718.32 398659.32 16-JAN-10:10 2043367.57 20-JUL-15:10
General:Cogeneration:ElectricityPurchased 31718.32 398659.32 16-JAN-10:10 2043367.57 20-JUL-15:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 31718.32 398659.32 16-JAN-10:10 2043367.57 20-JUL-15:10
ElectricityNet:Plant 31718.32 398659.32 16-JAN-10:10 2043367.57 20-JUL-15:10
Cogeneration:ElectricityNet 31718.32 398659.32 16-JAN-10:10 2043367.57 20-JUL-15:10
General:Cogeneration:ElectricityNet 31718.32 398659.32 16-JAN-10:10 2043367.57 20-JUL-15:10
Fans:Electricity 2838.76 47668.65 01-JAN-06:50 327323.05 20-JUL-15:10
General:Fans:Electricity 2838.76 47668.65 01-JAN-06:50 327323.05 20-JUL-15:10
ExteriorLights:Electricity 670.83 0.00 01-JAN-07:20 54335.80 01-JAN-06:10
General:ExteriorLights:Electricity 670.83 0.00 01-JAN-07:20 54335.80 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
Cooling:Electricity 4465.95 35433.97 28-JAN-07:10 514525.07 20-JUL-15:30
General:Cooling:Electricity 4465.95 35433.97 28-JAN-07:10 514525.07 20-JUL-15:30
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 726.93 0.00 18-MAY-15:30 54705.71 18-DEC-20:00
General:Humidifier:Electricity 726.93 0.00 18-MAY-15:30 54705.71 18-DEC-20:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 753.87 3653.63 01-JAN-00:10 76523.30 20-JUL-15:10
General:Pumps:Electricity 753.87 3653.63 01-JAN-00:10 76523.30 20-JUL-15:10
WIRED_LTG_ELECTRICITY 104.18 0.00 01-JAN-00:10 9915.18 22-NOV-17:10
WIRED_INT_EQUIP 5871.99 115917.86 04-MAR-00:10 320838.49 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 943.59 5695.87 16-APR-17:00 639696.87 27-DEC-07:10
NaturalGas:Plant 943.59 5695.87 16-APR-17:00 639696.87 27-DEC-07:10
Heating:NaturalGas 301.85 0.00 01-JAN-00:10 627244.64 27-DEC-07:10
Boiler:Heating:NaturalGas 301.85 0.00 01-JAN-00:10 627244.64 27-DEC-07:10
WaterSystems:NaturalGas 641.74 5695.87 05-JAN-05:10 78497.47 02-FEB-12:40
Water Heater:WaterSystems:NaturalGas 641.74 5695.87 05-JAN-05:10 78497.47 02-FEB-12:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 23539.14 172805.12 28-JAN-07:10 3638415.63 20-JUL-15:10
PlantLoopCoolingDemand:HVAC 23539.14 172805.12 28-JAN-07:10 3638415.63 20-JUL-15:10
CoolingCoils:PlantLoopCoolingDemand 23539.14 172805.12 28-JAN-07:10 3638415.63 20-JUL-15:10


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 11581.34 0.00 03-JUL-00:10 0.00 15-JUN-12:30
Water:HVAC 270.42 0.00 18-MAY-15:30 0.00 18-DEC-20:00
Humidifier:Water 270.42 0.00 18-MAY-15:30 0.00 18-DEC-20:00
General:Humidifier:Water 270.42 0.00 18-MAY-15:30 0.00 18-DEC-20:00
MainsWater:Facility 11581.34 0.00 03-JUL-00:10 0.00 15-JUN-12:30
MainsWater:HVAC 270.42 0.00 18-MAY-15:30 0.00 18-DEC-20:00
Humidifier:MainsWater 270.42 0.00 18-MAY-15:30 0.00 18-DEC-20:00
General:Humidifier:MainsWater 270.42 0.00 18-MAY-15:30 0.00 18-DEC-20:00
Water:Plant 11310.92 0.00 01-JAN-00:10 0.00 15-JUN-12:30
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 11310.92 0.00 01-JAN-00:10 0.00 15-JUN-12:30
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 9030.75 0.00 01-JAN-00:10 0.00 01-JUN-15:10
General:HeatRejection:Water 9030.75 0.00 01-JAN-00:10 0.00 01-JUN-15:10
HeatRejection:MainsWater 9030.75 0.00 01-JAN-00:10 0.00 01-JUN-15:10
General:HeatRejection:MainsWater 9030.75 0.00 01-JAN-00:10 0.00 01-JUN-15:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 70648.09 242991.70 16-JAN-04:00 12918751.55 20-JUL-15:10
EnergyTransfer:Building 20749.17 91039.34 16-JAN-08:40 1641340.61 07-AUG-16:00
EnergyTransfer:Zone:BASEMENT 722.58 0.00 01-JAN-00:10 74599.01 10-OCT-05:10
Heating:EnergyTransfer 78.10 0.00 01-JAN-14:00 250158.11 26-DEC-06:10
Heating:EnergyTransfer:Zone:BASEMENT 4.65 0.00 01-JAN-00:10 24920.75 01-JUL-16:10
General:Heating:EnergyTransfer 78.10 0.00 01-JAN-14:00 250158.11 26-DEC-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 4.65 0.00 01-JAN-00:10 24920.75 01-JUL-16:10
Cooling:EnergyTransfer 20671.07 90444.52 16-JAN-08:40 1641340.61 07-AUG-16:00
Cooling:EnergyTransfer:Zone:BASEMENT 717.92 0.00 01-JAN-00:10 74599.01 10-OCT-05:10
General:Cooling:EnergyTransfer 20671.07 90444.52 16-JAN-08:40 1641340.61 07-AUG-16:00
General:Cooling:EnergyTransfer:Zone:BASEMENT 717.92 0.00 01-JAN-00:10 74599.01 10-OCT-05:10
EnergyTransfer:Zone:CORE_BOTTOM 714.53 0.00 01-JAN-00:10 59565.27 07-AUG-09:20
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 714.53 0.00 01-JAN-00:10 59565.27 07-AUG-09:20
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 714.53 0.00 01-JAN-00:10 59565.27 07-AUG-09:20
EnergyTransfer:Zone:CORE_MID 5275.78 0.00 01-JAN-00:10 475779.02 20-JUL-15:20
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 5275.78 0.00 01-JAN-00:10 475779.02 20-JUL-15:20
General:Cooling:EnergyTransfer:Zone:CORE_MID 5275.78 0.00 01-JAN-00:10 475779.02 20-JUL-15:20
EnergyTransfer:Zone:CORE_TOP 496.64 0.00 01-JAN-00:10 54045.66 03-JUL-13:10
Heating:EnergyTransfer:Zone:CORE_TOP 1.00 0.00 01-JAN-00:10 37630.12 04-DEC-05:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 1.00 0.00 01-JAN-00:10 37630.12 04-DEC-05:10
Cooling:EnergyTransfer:Zone:CORE_TOP 495.63 0.00 01-JAN-00:10 54045.66 03-JUL-13:10
General:Cooling:EnergyTransfer:Zone:CORE_TOP 495.63 0.00 01-JAN-00:10 54045.66 03-JUL-13:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 93.85 0.00 01-JAN-00:10 11259.04 03-JUL-14:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 849.99 28-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 849.99 28-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 93.85 0.00 01-JAN-00:10 11259.04 03-JUL-14:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 93.85 0.00 01-JAN-00:10 11259.04 03-JUL-14:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 82.99 0.00 01-JAN-00:10 11028.03 03-JUL-09:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 907.41 28-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 907.41 28-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 82.99 0.00 01-JAN-00:10 11028.03 03-JUL-09:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 82.99 0.00 01-JAN-00:10 11028.03 03-JUL-09:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 128.55 0.00 01-JAN-00:10 15854.44 30-OCT-13:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 1586.52 27-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 1586.52 27-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 128.55 0.00 01-JAN-00:10 15854.44 30-OCT-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 128.55 0.00 01-JAN-00:10 15854.44 30-OCT-13:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 124.13 0.00 01-JAN-00:10 16555.68 07-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 124.13 0.00 01-JAN-00:10 16555.68 07-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 124.13 0.00 01-JAN-00:10 16555.68 07-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 704.52 0.00 01-JAN-00:10 101695.18 03-JUL-13:50
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 12.49 0.00 01-JAN-00:10 59857.43 26-DEC-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 12.49 0.00 01-JAN-00:10 59857.43 26-DEC-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 692.03 0.00 01-JAN-00:10 101695.18 03-JUL-13:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 692.03 0.00 01-JAN-00:10 101695.18 03-JUL-13:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 719.21 0.00 01-JAN-00:10 111121.33 07-JUN-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 5.66 0.00 01-JAN-00:10 39295.09 28-JAN-05:50
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 5.66 0.00 01-JAN-00:10 39295.09 28-JAN-05:50
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 713.55 0.00 01-JAN-00:10 111121.33 07-JUN-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 713.55 0.00 01-JAN-00:10 111121.33 07-JUN-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1070.30 0.00 01-JAN-00:10 152687.11 30-OCT-13:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 2.40 0.00 01-JAN-00:10 48532.53 27-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 2.40 0.00 01-JAN-00:10 48532.53 27-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1067.90 0.00 01-JAN-00:10 152687.11 30-OCT-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1067.90 0.00 01-JAN-00:10 152687.11 30-OCT-13:20
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 765.64 0.00 01-JAN-00:10 129613.26 15-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 3.05 0.00 01-JAN-00:10 29953.67 27-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 3.05 0.00 01-JAN-00:10 29953.67 27-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 762.60 0.00 01-JAN-00:10 129613.26 15-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 762.60 0.00 01-JAN-00:10 129613.26 15-JUN-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 76.49 0.00 01-JAN-00:10 13960.20 26-DEC-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 7.71 0.00 01-JAN-00:10 13960.20 26-DEC-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 7.71 0.00 01-JAN-00:10 13960.20 26-DEC-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 68.78 0.00 01-JAN-00:10 11573.73 03-JUL-13:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 68.78 0.00 01-JAN-00:10 11573.73 03-JUL-13:50
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 73.83 0.00 01-JAN-00:10 11824.54 03-JUL-09:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 3.34 0.00 01-JAN-00:10 9985.99 04-DEC-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 3.34 0.00 01-JAN-00:10 9985.99 04-DEC-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 70.49 0.00 01-JAN-00:10 11824.54 03-JUL-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 70.49 0.00 01-JAN-00:10 11824.54 03-JUL-09:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 106.60 0.00 01-JAN-00:10 16746.40 03-OCT-13:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 2.94 0.00 01-JAN-00:10 12964.72 26-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 2.94 0.00 01-JAN-00:10 12964.72 26-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 103.66 0.00 01-JAN-00:10 16746.40 03-OCT-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 103.66 0.00 01-JAN-00:10 16746.40 03-OCT-13:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 77.95 0.00 01-JAN-00:10 13951.17 15-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 2.41 0.00 01-JAN-00:10 7746.70 26-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 2.41 0.00 01-JAN-00:10 7746.70 26-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 75.54 0.00 01-JAN-00:10 13951.17 15-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 75.54 0.00 01-JAN-00:10 13951.17 15-JUN-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 88.06 0.00 01-JAN-00:10 12312.33 07-AUG-07:10
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.94 0.00 01-JAN-00:10 3094.00 31-DEC-14:50
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.94 0.00 01-JAN-00:10 3094.00 31-DEC-14:50
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 87.12 0.00 01-JAN-00:10 12312.33 07-AUG-07:10
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 87.12 0.00 01-JAN-00:10 12312.33 07-AUG-07:10
EnergyTransfer:Zone:MIDFLOOR_PLENUM 621.79 0.00 01-JAN-00:10 84538.06 03-JUL-14:30
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 14.56 0.00 01-JAN-00:10 25241.60 04-DEC-14:10
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 14.56 0.00 01-JAN-00:10 25241.60 04-DEC-14:10
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 607.23 0.00 01-JAN-00:10 84538.06 03-JUL-14:30
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 607.23 0.00 01-JAN-00:10 84538.06 03-JUL-14:30
EnergyTransfer:Zone:TOPFLOOR_PLENUM 111.33 0.00 01-JAN-00:10 22612.29 03-JUL-13:10
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 16.51 0.00 01-JAN-00:10 16916.86 04-DEC-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 16.51 0.00 01-JAN-00:10 16916.86 04-DEC-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 94.82 0.00 01-JAN-00:10 22612.29 03-JUL-13:10
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 94.82 0.00 01-JAN-00:10 22612.29 03-JUL-13:10
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 141.68 870.08 28-JAN-08:00 7862.59 27-AUG-21:00
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 141.68 870.08 28-JAN-08:00 7862.59 27-AUG-21:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 141.68 870.08 28-JAN-08:00 7862.59 27-AUG-21:00
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1278.64 2034.74 16-JAN-08:40 73712.50 26-APR-17:50
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1278.64 2034.74 16-JAN-08:40 73712.50 26-APR-17:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1278.64 2034.74 16-JAN-08:40 73712.50 26-APR-17:50
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 121.36 0.70 14-JAN-16:40 7451.15 27-APR-17:50
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.42 0.00 01-JAN-14:00 609.34 08-JAN-07:30
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.42 0.00 01-JAN-14:00 609.34 08-JAN-07:30
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 120.94 0.00 01-JAN-00:10 7451.15 27-APR-17:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 120.94 0.00 01-JAN-00:10 7451.15 27-APR-17:50
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7152.74 87155.05 15-JAN-06:00 368205.15 17-APR-07:40
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7152.74 87155.05 15-JAN-06:00 368205.15 17-APR-07:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7152.74 87155.05 15-JAN-06:00 368205.15 17-APR-07:40
PlantLoopHeatingDemand:Facility 572.58 0.00 01-JAN-00:10 530146.85 27-DEC-07:10
PlantLoopHeatingDemand:Plant 359.12 0.00 01-JAN-00:10 46366.40 30-JAN-12:50
WaterSystems:PlantLoopHeatingDemand 359.12 0.00 01-JAN-00:10 46366.40 30-JAN-12:50
General:WaterSystems:PlantLoopHeatingDemand 359.12 0.00 01-JAN-00:10 46366.40 30-JAN-12:50
EnergyTransfer:HVAC 20598.01 146939.96 14-JAN-18:00 3500764.10 20-JUL-15:10
HeatingCoils:EnergyTransfer 213.46 0.00 01-JAN-00:10 515176.10 27-DEC-07:10
PlantLoopHeatingDemand:HVAC 213.46 0.00 01-JAN-00:10 515176.10 27-DEC-07:10
HeatingCoils:PlantLoopHeatingDemand 213.46 0.00 01-JAN-00:10 515176.10 27-DEC-07:10
CoolingCoils:EnergyTransfer 20384.56 137371.16 28-JAN-07:10 3500764.10 20-JUL-15:10
EnergyTransfer:Plant 29300.90 0.00 01-JAN-00:10 8203814.23 20-JUL-15:10
LoopToLoop:EnergyTransfer 9798.57 0.00 01-JAN-00:10 2867988.92 20-JUL-15:10
WaterSystems:EnergyTransfer 359.12 0.00 01-JAN-00:10 46366.40 30-JAN-12:50
WaterUse:WaterSystems:EnergyTransfer 359.12 0.00 01-JAN-00:10 46366.40 30-JAN-12:50
Boilers:EnergyTransfer 211.34 0.00 01-JAN-00:10 520487.54 27-DEC-07:10
Chillers:EnergyTransfer 8810.25 0.00 01-JAN-00:10 2489249.57 20-JUL-15:00
HeatRejection:EnergyTransfer 10121.62 0.00 01-JAN-00:10 2864197.06 20-JUL-15:30
General:HeatRejection:EnergyTransfer 10121.62 0.00 01-JAN-00:10 2864197.06 20-JUL-15:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 4.652 -717.922 0.000 0.000 92.688 240.449 424.397 0.000 0.000 0.000 0.006 0.000 0.000 0.000 0.000 -44.263
CORE_BOTTOM 0.000 0.000 0.000 -714.526 0.000 0.000 83.413 215.940 321.286 0.000 0.000 0.000 93.888 0.000 0.000 0.000 0.000 -0.006
CORE_MID 0.000 0.000 0.000 -5275.766 0.000 0.000 836.663 2159.397 3212.845 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -933.139
CORE_TOP 0.000 0.000 1.004 -495.631 0.000 0.000 85.203 215.940 321.285 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -127.801
PERIMETER_BOT_ZN_3 0.000 0.000 0.001 -93.848 0.000 0.000 10.710 18.739 40.342 24.625 0.000 0.431 42.313 0.000 -40.262 0.000 -3.051 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.004 -82.986 0.000 0.000 6.887 12.075 25.998 50.657 0.000 0.300 13.150 0.000 -24.074 0.000 -2.011 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.003 -128.551 0.000 0.000 10.567 18.543 40.343 86.388 0.000 0.423 12.576 0.000 -37.111 0.000 -3.182 -0.000
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -124.125 0.000 0.000 6.820 11.982 25.998 49.959 0.000 0.253 60.770 0.000 -29.349 0.000 -2.309 0.000
PERIMETER_MID_ZN_3 0.000 0.000 12.490 -692.025 0.000 0.000 110.928 187.574 403.423 256.626 0.000 9.828 139.911 0.000 -364.789 0.000 -63.965 0.000
PERIMETER_MID_ZN_2 0.000 0.000 5.662 -713.546 0.000 0.000 51.835 120.787 259.981 506.960 0.000 6.360 35.025 0.000 -228.502 0.000 -44.562 -0.005
PERIMETER_MID_ZN_1 0.000 0.000 2.400 -1067.889 0.000 0.000 106.489 185.597 403.429 862.710 0.000 9.398 0.040 0.000 -362.008 0.000 -72.602 -67.523
PERIMETER_MID_ZN_4 0.000 0.000 3.049 -762.584 0.000 0.000 71.047 119.870 259.979 511.884 0.000 5.940 91.765 0.000 -254.331 0.000 -46.621 -0.006
PERIMETER_TOP_ZN_3 0.000 0.000 7.712 -68.780 0.000 0.000 11.298 18.758 40.342 25.951 0.000 1.181 4.586 0.000 -33.792 0.000 -7.256 -0.000
PERIMETER_TOP_ZN_2 0.000 0.000 3.344 -70.487 0.000 0.000 7.140 12.079 25.998 50.903 0.000 0.748 0.001 0.000 -21.497 0.000 -5.147 -3.081
PERIMETER_TOP_ZN_1 0.000 0.000 2.945 -103.656 0.000 0.000 10.815 18.560 40.343 86.647 0.000 1.123 0.003 0.000 -34.065 0.000 -8.388 -14.323
PERIMETER_TOP_ZN_4 0.000 0.000 2.405 -75.542 0.000 0.000 7.210 11.987 25.998 51.241 0.000 0.720 5.467 0.000 -24.050 0.000 -5.436 -0.000
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -141.675 0.000 0.000 0.947 5.965 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -19.117
DATACENTER_MID_ZN_6 0.000 0.000 0.000 -1278.637 0.000 0.000 9.477 59.652 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -329.297
DATACENTER_TOP_ZN_6 0.000 0.000 0.420 -120.937 0.000 0.000 0.948 5.965 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -40.277
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7152.748 0.000 0.000 19.634 67.796 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -429.539
GROUNDFLOOR_PLENUM 0.938 -87.118 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.754 92.180 0.000 0.000 0.000 -6.754 0.000
MIDFLOOR_PLENUM 14.558 -607.233 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 13.703 694.601 0.000 0.000 0.000 -115.629 0.000
TOPFLOOR_PLENUM 16.513 -94.815 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.308 88.845 0.000 0.000 0.000 -11.851 -0.000
Total Facility 32.009 -789.165 46.093 -19881.862 0.000 0.000 1540.718 3707.655 15213.411 2564.550 0.000 52.470 1375.126 0.000 -1453.830 0.000 -398.765 -2008.380


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 26-DEC-04:01 0.00 0.00 0.00 -117075.70 0.00 0.00 0.00 1166.43 13457.54 0.00 0.00 0.00 102451.73 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 26-DEC-04:01 0.00 0.00 0.00 -95907.99 0.00 0.00 0.00 1047.53 8057.15 0.00 0.00 0.00 86803.31 0.00 -0.00 0.00 0.00 0.00
CORE_MID 05-JUL-03:02 0.00 0.00 0.00 -873100.96 0.00 0.00 0.00 10475.32 80571.20 0.00 0.00 0.00 782054.44 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 05-JUL-03:02 0.00 0.00 0.00 -88271.64 0.00 0.00 0.00 1047.53 8057.12 0.00 0.00 0.00 79166.99 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 04-JUN-16:41 0.00 0.00 0.00 -16499.31 0.00 0.00 44.45 80.80 758.77 4309.00 0.00 25.92 11280.37 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 04-SEP-08:12 0.00 0.00 0.00 -16923.57 0.00 0.00 23.54 52.07 488.98 10964.86 0.00 0.00 5464.28 0.00 -0.00 0.00 -70.17 0.00
PERIMETER_BOT_ZN_1 29-OCT-12:52 0.00 0.00 0.00 -21320.27 0.00 0.00 35.41 80.80 758.78 16706.24 0.00 0.00 3894.04 0.00 -0.00 0.00 -155.00 0.00
PERIMETER_BOT_ZN_4 04-JUN-16:01 0.00 0.00 0.00 -23854.05 0.00 0.00 19.62 52.07 488.98 12028.30 0.00 68.23 11196.85 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 03-JUL-04:22 0.00 0.00 0.00 -146566.49 0.00 0.00 0.00 2630.56 10116.97 0.00 0.00 626.88 133491.97 0.00 -299.89 0.00 0.00 0.00
PERIMETER_MID_ZN_2 29-MAY-08:52 0.00 0.00 0.00 -173780.42 0.00 0.00 233.61 520.69 4889.82 101183.05 0.00 0.00 68348.23 0.00 -0.00 0.00 -1394.99 0.00
PERIMETER_MID_ZN_1 22-OCT-13:22 0.00 0.00 0.00 -202823.03 0.00 0.00 357.74 807.99 7587.84 136372.38 0.00 0.00 57934.60 0.00 -0.00 0.00 -237.54 0.00
PERIMETER_MID_ZN_4 25-JUN-18:11 0.00 0.00 0.00 -197898.32 0.00 0.00 0.00 520.69 4889.79 76342.36 0.00 492.96 115652.52 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 18-JUN-14:51 0.00 0.00 0.00 -19423.03 0.00 0.00 40.90 80.80 758.77 3991.37 0.00 240.94 14310.25 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 25-JUN-09:02 0.00 0.00 0.00 -17847.40 0.00 0.00 23.35 52.07 488.98 9483.22 0.00 0.00 7916.85 0.00 -0.00 0.00 -117.07 0.00
PERIMETER_TOP_ZN_1 22-OCT-13:22 0.00 0.00 0.00 -22705.50 0.00 0.00 35.71 80.80 758.78 13600.19 0.00 0.00 8259.50 0.00 -0.00 0.00 -29.48 0.00
PERIMETER_TOP_ZN_4 25-JUN-17:01 0.00 0.00 0.00 -22406.57 0.00 0.00 0.00 52.07 488.98 11317.93 0.00 109.90 10437.69 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 27-AUG-21:03 0.00 0.00 0.00 -7879.04 0.00 0.00 0.00 28.94 7794.42 0.00 0.00 0.00 55.68 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 26-APR-17:50 0.00 0.00 0.00 -73707.95 0.00 0.00 106.16 1736.14 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -6078.57
DATACENTER_TOP_ZN_6 27-AUG-20:12 0.00 0.00 0.00 -7459.97 0.00 0.00 0.00 28.94 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -363.38
DATACENTER_BASEMENT_ZN_6 17-APR-07:55 0.00 0.00 0.00 -368202.24 0.00 0.00 2182.17 5919.59 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -19532.04
GROUNDFLOOR_PLENUM 07-AUG-05:15 0.00 -16843.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.65 16841.39 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 17-JUN-05:02 0.00 -90442.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90712.79 0.00 -0.00 0.00 -269.96 0.00
TOPFLOOR_PLENUM 03-JUL-13:10 0.00 -22611.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 139.43 22472.21 0.00 -0.00 0.00 0.00 0.00
Total Facility 11-AUG-05:02 0.00 -49212.02 0.00 -2026829.02 0.00 0.00 15507.06 39207.80 623236.89 0.00 0.00 0.00 1436789.44 0.00 -38137.13 0.00 -563.01 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 01-JUL-16:02 0.00 0.00 26349.42 0.00 0.00 0.00 520.13 1166.43 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -41493.52
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP 04-DEC-05:01 0.00 0.00 73247.52 0.00 0.00 0.00 0.00 2095.06 8057.12 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -83399.71
PERIMETER_BOT_ZN_3 28-JAN-06:01 0.00 0.00 6221.32 0.00 0.00 0.00 141.55 263.06 1011.70 0.00 0.00 0.00 0.00 0.00 -4970.63 0.00 -186.49 -2480.52
PERIMETER_BOT_ZN_2 30-DEC-06:01 0.00 0.00 5812.61 0.00 0.00 0.00 93.85 169.52 651.98 0.00 0.00 0.00 0.00 0.00 -3188.53 0.00 -79.09 -3460.33
PERIMETER_BOT_ZN_1 27-DEC-06:01 0.00 0.00 9980.09 0.00 0.00 0.00 143.95 263.06 1011.71 0.00 0.00 0.00 0.00 0.00 -4838.95 0.00 -105.36 -6454.51
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 26-DEC-05:02 0.00 0.00 123971.09 0.00 0.00 0.00 0.00 2630.56 10116.97 0.00 0.00 0.00 0.00 0.00 -38608.79 0.00 -13188.63 -84921.20
PERIMETER_MID_ZN_2 28-NOV-05:01 0.00 0.00 116370.50 0.00 0.00 0.00 0.00 1695.23 6519.76 0.00 0.00 0.00 0.00 0.00 -26303.60 0.00 -9511.68 -88770.22
PERIMETER_MID_ZN_1 28-NOV-05:01 0.00 0.00 131422.37 0.00 0.00 0.00 0.00 2630.62 10117.12 0.00 0.00 0.00 0.00 0.00 -39575.56 0.00 -14652.30 -89942.25
PERIMETER_MID_ZN_4 27-DEC-06:01 0.00 0.00 108936.91 0.00 0.00 0.00 941.51 1695.23 6519.72 0.00 0.00 0.00 0.00 0.00 -30773.11 0.00 -1633.58 -85686.69
PERIMETER_TOP_ZN_3 27-NOV-04:01 0.00 0.00 16415.60 0.00 0.00 0.00 0.00 131.53 1011.70 0.00 0.00 0.00 0.00 0.00 -2350.27 0.00 -424.44 -14784.11
PERIMETER_TOP_ZN_2 04-DEC-04:01 0.00 0.00 14270.36 0.00 0.00 0.00 0.00 84.76 651.98 0.00 0.00 0.00 0.00 0.00 -2050.58 0.00 0.00 -12956.51
PERIMETER_TOP_ZN_1 26-DEC-04:01 0.00 0.00 17380.20 0.00 0.00 0.00 0.00 131.53 1011.71 0.00 0.00 0.00 0.00 0.00 -3113.08 0.00 -1342.76 -14067.61
PERIMETER_TOP_ZN_4 26-DEC-04:01 0.00 0.00 15433.72 0.00 0.00 0.00 0.00 84.76 651.97 0.00 0.00 0.00 0.00 0.00 -2135.82 0.00 -935.36 -13099.28
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 08-JAN-07:30 0.00 0.00 609.34 0.00 0.00 0.00 5.54 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2592.43
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 18-DEC-04:02 12867.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -2399.55 -10467.96
MIDFLOOR_PLENUM 07-MAR-06:02 75425.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -3654.92 -71771.04
TOPFLOOR_PLENUM 04-DEC-06:13 20492.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -276.70 -20215.66
Total Facility 27-DEC-06:01 -786376.69 777372.54 601253.38 -777372.54 0.00 0.00 19223.98 39207.80 623236.89 0.00 0.00 0.00 0.00 0.00 -185742.07 0.00 -14011.22 -296792.06



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 11.8685 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.0342 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 111.7883 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 103.1005 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 11.5918 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.2509 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.5894 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.5894 0.1821 1.0000 Not calculated 1.2002 0.1821    
AIRLOOP DATACENTER BASEMENT 24.6525 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 24.6528 0.0137 1.0000 Not calculated 0.3384 0.0137    
AIRLOOP DATACENTER BOT 0.5456 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5456 0.0287 1.0000 Not calculated 0.0156 0.0287    
AIRLOOP DATACENTER MID 5.1879 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 5.1879 0.0301 1.0000 Not calculated 0.1563 0.0301    
AIRLOOP DATACENTER TOP 0.5249 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5249 0.0298 1.0000 Not calculated 0.0156 0.0298    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.9343 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.5606 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 55.8941 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 33.6669 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.7959 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.5551 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.5894 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.5894 1.0000 1.0000 Not calculated 1.2002 0.1821    
AIRLOOP DATACENTER BASEMENT 24.6525 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 24.6525 1.0000 1.0000 Not calculated 0.3384 0.0137    
AIRLOOP DATACENTER BOT 0.5456 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5456 1.0000 1.0000 Not calculated 0.0156 0.0287    
AIRLOOP DATACENTER MID 5.1879 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 5.1879 1.0000 1.0000 Not calculated 0.1563 0.0301    
AIRLOOP DATACENTER TOP 0.5249 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5249 1.0000 1.0000 Not calculated 0.0156 0.0298    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.5894 6.5894 6.5894 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.9033 6.9033 2.0710 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 65.1880 65.1880 19.6868 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.4598 6.4598 2.0155 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1848 1.1848 0.3554 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0713 1.0713 0.3214 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3023 1.3023 0.3907 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4068 1.4068 0.4220 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.2537 11.2537 3.3761 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.0297 11.0297 3.3089 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 12.3702 12.3702 3.7111 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.9467 11.9467 3.5840 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2929 1.2929 0.3879 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1361 1.1361 0.3408 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3949 1.3949 0.4185 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3081 1.3081 0.3924 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5456 0.5456 0.5456 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.1879 5.1879 5.1879 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5249 0.5249 0.5249 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 24.6525 24.6525 24.6525 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 11.8685 11.0342 11.8685 3.5606 0.0000 1.0000
VAV_MID WITH REHEAT 111.7883 103.1005 111.7883 33.6669 0.0000 1.0000
VAV_TOP WITH REHEAT 11.5918 11.2509 11.5918 3.5551 0.0000 1.0000
CAV_BAS 6.5894 6.5894 6.5894 6.5894 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 24.6525 24.6528 24.6525 24.6525 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5456 0.5456 0.5456 0.5456 0.0156 1.0000
AIRLOOP DATACENTER MID 5.1879 5.1879 5.1879 5.1879 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.5249 0.5249 0.5249 0.5249 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.5894 6.5894 6.5894 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.4516 3.4516 2.0710 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 32.5940 32.5940 19.6868 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2299 3.2299 2.0155 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5924 0.5924 0.3554 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5357 0.5357 0.3214 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6512 0.6512 0.3907 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7034 0.7034 0.4220 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.6269 5.6269 3.3761 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.5148 5.5148 3.3089 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.1851 6.1851 3.7111 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.9733 5.9733 3.5840 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6464 0.6464 0.3879 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5680 0.5680 0.3408 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6975 0.6975 0.4185 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6541 0.6541 0.3924 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5456 0.5456 0.5456 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.1879 5.1879 5.1879 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5249 0.5249 0.5249 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 24.6525 24.6525 24.6525 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.9343 3.5606 3.5606 3.5606 0.0000 1.0000
VAV_MID WITH REHEAT 55.8941 33.6669 33.6669 33.6669 0.0000 1.0000
VAV_TOP WITH REHEAT 5.7959 3.5551 3.5551 3.5551 0.0000 1.0000
CAV_BAS 6.5894 6.5894 6.5894 6.5894 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 24.6525 24.6525 24.6525 24.6525 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5456 0.5456 0.5456 0.5456 0.0156 1.0000
AIRLOOP DATACENTER MID 5.1879 5.1879 5.1879 5.1879 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.5249 0.5249 0.5249 0.5249 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 1.17
Number of hours cooling loads not met 979.00
Number of hours not met 980.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 301.85 627244.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 4465.95 514525.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 3707.66 352853.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 670.83 54335.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5871.99 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 87.32 5480.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2838.76 327323.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 753.87 76523.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1398.97 85424.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 726.93 54705.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 641.74 78497.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 15213.41 31718.32
Natural Gas 0.00 943.59
Additional 0.00 0.00
Total 15213.41 32661.91


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 80.04
Space Heating 0.00
Space Cooling 96.41
Fans (All) 61.29
Service Water Heating 0.00
Receptacle Equipment 328.44
Miscellaneous (All) 684.76
Subtotal 684.76


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 6.52
Service Water Heating 13.85
Miscellaneous (All) 20.37
Subtotal 20.37


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 11.35
Space Heating 0.92
Space Cooling 13.67
Fans (All) 8.69
Service Water Heating 1.96
Receptacle Equipment 46.58
Miscellaneous 16.82


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2645. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4487. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 2347. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8422.83 337.17 0.00 0.00 0.00
CORE_BOTTOM 8731.83 28.17 0.00 0.00 0.00
CORE_MID 8758.50 1.50 0.00 0.00 0.00
CORE_TOP 8753.50 6.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8751.00 9.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8709.33 50.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8710.17 49.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8391.83 368.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8757.33 2.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8683.83 76.17 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8712.33 47.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8493.50 266.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8742.17 17.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8650.50 109.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8695.33 64.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8493.50 266.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8598.17 161.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8652.50 107.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8648.33 111.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7525.00 1235.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8594.50 165.50 0.00 0.00 0.00
Min 7525.00 0.00 0.00 0.00 0.00
Max 8760.00 1235.00 0.00 0.00 0.00
Average 8608.52 151.48 0.00 0.00 0.00
Sum 197996.00 3484.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 367426.00 1190.00 0.00 0.00 0.00
CORE_BOTTOM 330761.00 52.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2198.67 69.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2211.50 56.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2217.50 50.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 88188.67 15206.33 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 367426.00 15206.33 0.00 0.00 0.00
Average 79612.10 722.81 0.00 0.00 0.00
Sum 1831078.33 16624.67 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 7948.33 811.67 0.00 0.00 0.00
CORE_BOTTOM 8381.83 378.17 0.00 0.00 0.00
CORE_MID 8392.33 367.67 0.00 0.00 0.00
CORE_TOP 8342.83 417.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8434.17 325.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8475.17 284.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8382.00 378.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8043.00 717.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8377.67 382.33 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8297.17 462.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8280.83 479.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8182.67 577.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8372.83 387.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8258.50 501.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8281.83 478.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8180.33 579.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8734.33 25.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8745.00 15.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8740.83 19.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7682.67 1077.33 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8232.67 527.33 0.00 0.00 0.00
MIDFLOOR_PLENUM 8316.67 443.33 0.00 0.00 0.00
TOPFLOOR_PLENUM 7768.67 991.33 0.00 0.00 0.00
Min 7682.67 15.00 0.00 0.00 0.00
Max 8745.00 1077.33 0.00 0.00 0.00
Average 8297.93 462.07 0.00 0.00 0.00
Sum 190852.33 10627.67 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 364314.00 4302.00 0.00 0.00 0.00
CORE_BOTTOM 330119.00 694.00 0.00 0.00 0.00
CORE_MID 330318.00 495.00 0.00 0.00 0.00
CORE_TOP 330135.00 678.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2253.17 14.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2257.83 10.17 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2257.33 10.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 90271.00 13124.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 364314.00 13124.00 0.00 0.00 0.00
Average 79494.54 840.38 0.00 0.00 0.00
Sum 1828374.33 19328.67 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:13

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.539977E+11 112546.00 17-JAN-04:02 5.60 4.12 0.566520E+10 7499.11 02-JAN-10:20 5.60 4.12
February 0.469788E+11 109505.63 13-FEB-04:02 11.13 6.50 0.513769E+10 7499.37 13-FEB-10:20 10.73 9.09
March 0.551015E+11 110121.09 13-MAR-03:02 5.82 2.38 0.613055E+10 7499.06 22-MAR-09:09 15.15 5.68
April 0.537470E+11 112745.75 24-APR-03:12 13.13 5.04 0.544896E+10 7499.18 10-APR-13:39 13.13 5.04
May 0.576292E+11 112443.88 01-MAY-03:02 16.68 5.86 0.590154E+10 7499.06 08-MAY-09:09 24.87 11.71
June 0.589315E+11 112791.42 12-JUN-03:02 17.38 6.37 0.588187E+10 7499.03 29-JUN-13:09 25.68 17.54
July 0.620739E+11 102264.60 10-JUL-03:02 24.40 16.39 0.547520E+10 7498.98 11-JUL-09:09 29.18 18.50
August 0.732426E+11 113788.15 27-AUG-16:20 35.00 16.49 0.613998E+10 7499.07 11-AUG-09:09 35.00 16.49
September 0.660986E+11 112225.97 11-SEP-03:02 18.03 11.88 0.545528E+10 7499.16 06-SEP-09:39 18.03 11.88
October 0.675009E+11 111364.18 10-OCT-03:02 12.30 8.79 0.567403E+10 7499.21 17-OCT-09:00 21.10 16.29
November 0.632906E+11 115524.57 27-NOV-04:01 3.80 -0.8 0.561722E+10 7498.90 03-NOV-09:20 3.80 -0.8
December 0.593320E+11 117084.58 26-DEC-04:01 -0.1 -2.0 0.547221E+10 7499.04 20-DEC-10:20 -0.1 -2.0
                     
Annual Sum or Average 0.717924E+12         0.679997E+11        
Minimum of Months 0.469788E+11 102264.60   -0.1 -2.0 0.513769E+10 7498.90   -0.1 -2.0
Maximum of Months 0.732426E+11 117084.58   35.00 16.49 0.613998E+10 7499.37   35.00 18.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.434056E+11 91891.08 02-JAN-04:03 2.98 1.95 0.507385E+10 6734.84 02-JAN-10:09 10.97 7.20
February 0.436852E+11 92531.26 21-FEB-04:02 4.40 -0.5 0.460294E+10 6735.10 13-FEB-10:09 4.40 -0.5
March 0.566810E+11 90353.30 13-MAR-03:02 5.82 2.38 0.549921E+10 6734.72 22-MAR-09:09 15.15 5.68
April 0.651018E+11 89712.46 26-APR-03:02 12.70 8.47 0.487971E+10 6734.84 27-APR-09:09 20.87 11.97
May 0.609595E+11 91059.57 22-MAY-03:02 18.80 14.03 0.528578E+10 6734.88 08-MAY-09:09 18.80 14.03
June 0.675829E+11 90132.47 29-JUN-03:02 18.23 16.01 0.526667E+10 6734.78 22-JUN-09:09 18.23 16.01
July 0.711978E+11 87035.16 05-JUL-04:03 19.08 16.04 0.489317E+10 6734.72 11-JUL-09:09 29.18 18.50
August 0.817015E+11 89980.66 14-AUG-05:03 17.30 16.19 0.549537E+10 6734.76 17-AUG-13:30 25.00 17.14
September 0.598432E+11 94649.79 25-SEP-03:02 11.02 9.18 0.488344E+10 6734.78 06-SEP-09:20 11.02 9.18
October 0.596525E+11 94444.15 23-OCT-03:02 12.80 10.14 0.507999E+10 6735.04 17-OCT-09:00 12.80 10.14
November 0.540341E+11 94969.79 13-NOV-04:02 3.30 0.86 0.503153E+10 6734.68 24-NOV-10:09 17.48 6.61
December 0.506823E+11 95923.70 26-DEC-04:01 -0.1 -2.0 0.490390E+10 6734.72 20-DEC-10:20 -0.1 -2.0
                     
Annual Sum or Average 0.714527E+12         0.608956E+11        
Minimum of Months 0.434056E+11 87035.16   -0.1 -2.0 0.460294E+10 6734.68   -0.1 -2.0
Maximum of Months 0.817015E+11 95923.70   19.08 16.19 0.549921E+10 6735.10   29.18 18.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.312799E+11 77763.83 13-JAN-06:02 3.22 0.84 0.501411E+10 6734.67 02-JAN-10:09 3.22 0.84
February 0.314267E+11 80120.70 08-FEB-06:02 10.60 6.52 0.456428E+10 6735.02 13-FEB-10:09 10.92 9.01
March 0.403801E+11 80099.79 07-MAR-06:02 12.20 5.51 0.547613E+10 6734.71 22-MAR-09:09 15.15 5.68
April 0.443318E+11 82628.63 27-APR-04:02 13.98 6.06 0.487405E+10 6734.82 27-APR-09:09 20.87 11.97
May 0.525715E+11 84667.29 23-MAY-03:02 21.52 15.26 0.528222E+10 6734.85 08-MAY-09:09 21.52 15.26
June 0.555947E+11 84199.25 20-JUN-03:02 20.00 16.00 0.526601E+10 6734.78 22-JUN-09:09 22.88 16.93
July 0.540004E+11 87331.30 05-JUL-03:02 18.90 16.84 0.489174E+10 6734.72 11-JUL-09:09 29.18 18.50
August 0.566277E+11 84010.75 29-AUG-03:02 20.92 16.24 0.549422E+10 6734.78 17-AUG-13:20 20.92 16.24
September 0.497168E+11 85781.10 05-SEP-03:02 17.12 14.86 0.487909E+10 6734.76 06-SEP-09:09 25.28 18.43
October 0.453109E+11 85086.71 06-OCT-03:02 14.32 13.24 0.506811E+10 6734.99 17-OCT-09:00 21.10 16.29
November 0.360105E+11 80502.92 08-NOV-06:02 12.30 5.81 0.499976E+10 6734.61 03-NOV-09:09 12.30 5.81
December 0.303268E+11 74159.18 14-DEC-06:03 2.70 1.71 0.483249E+10 6734.71 20-DEC-10:20 8.00 0.09
                     
Annual Sum or Average 0.527578E+12         0.606422E+11        
Minimum of Months 0.303268E+11 74159.18   2.70 0.84 0.456428E+10 6734.61   3.22 0.09
Maximum of Months 0.566277E+11 87331.30   21.52 16.84 0.549422E+10 6735.02   29.18 18.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.222770E+11 32538.43 12-JAN-17:00 17.80 9.80 0.461923E+10 6734.46 12-JAN-14:09 17.80 9.80
February 0.235383E+11 35597.94 22-FEB-17:00 21.70 8.09 0.432307E+10 6734.61 23-FEB-10:09 13.48 7.26
March 0.325998E+11 74623.96 16-MAR-05:03 14.43 5.41 0.532851E+10 6734.70 22-MAR-09:09 15.15 5.68
April 0.417689E+11 81275.30 03-APR-04:02 19.53 8.46 0.484600E+10 6734.80 27-APR-09:09 20.87 11.97
May 0.539449E+11 85363.75 22-MAY-03:02 18.80 14.03 0.527917E+10 6734.82 08-MAY-09:09 18.80 14.03
June 0.615331E+11 84720.02 09-JUN-03:02 21.70 14.88 0.526808E+10 6734.77 22-JUN-09:09 22.88 16.93
July 0.600367E+11 88292.75 05-JUL-03:02 18.90 16.84 0.489627E+10 6734.71 11-JUL-09:09 29.18 18.50
August 0.607401E+11 87520.63 14-AUG-03:02 17.30 16.84 0.549623E+10 6734.80 11-AUG-09:09 17.30 16.84
September 0.502964E+11 86646.45 05-SEP-03:02 17.12 14.86 0.487742E+10 6734.76 06-SEP-09:09 25.28 18.43
October 0.407810E+11 82385.01 03-OCT-04:02 19.32 14.48 0.502729E+10 6734.93 17-OCT-09:00 21.10 16.29
November 0.270587E+11 75083.88 10-NOV-06:03 17.87 11.05 0.476083E+10 6734.61 01-NOV-09:09 17.87 11.05
December 0.210593E+11 27489.79 01-DEC-16:50 10.87 4.97 0.438316E+10 6734.49 01-DEC-14:09 10.87 4.97
                     
Annual Sum or Average 0.495634E+12         0.591053E+11        
Minimum of Months 0.210593E+11 27489.79   10.87 4.97 0.432307E+10 6734.46   10.87 4.97
Maximum of Months 0.615331E+11 88292.75   21.70 16.84 0.549623E+10 6734.93   29.18 18.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.374763E+10 3693.53 02-JAN-04:03 2.98 1.95 0.568942E+09 842.90 13-JAN-14:00 18.30 8.81
February 0.396393E+10 5285.05 21-FEB-15:00 22.80 8.17 0.534920E+09 845.60 14-FEB-14:00 22.80 8.17
March 0.552989E+10 6127.67 22-MAR-14:30 24.15 9.01 0.664147E+09 845.62 22-MAR-09:09 24.15 9.01
April 0.830606E+10 8679.08 21-APR-15:00 32.20 15.49 0.607564E+09 845.64 27-APR-09:09 20.87 11.97
May 0.953262E+10 13153.19 23-MAY-05:03 20.10 14.79 0.662929E+09 845.64 08-MAY-09:09 20.10 14.79
June 0.124555E+11 16500.73 04-JUN-16:41 35.10 16.97 0.661885E+09 845.63 27-JUN-09:09 25.10 15.77
July 0.127529E+11 13968.01 03-JUL-04:12 28.53 17.94 0.615264E+09 846.24 03-JUL-13:20 37.07 18.70
August 0.131504E+11 14715.97 07-AUG-03:01 27.02 16.26 0.690256E+09 845.64 17-AUG-13:30 25.00 17.14
September 0.864218E+10 13302.31 18-SEP-05:03 18.30 13.86 0.611643E+09 845.63 11-SEP-09:50 18.30 13.86
October 0.692453E+10 13704.38 02-OCT-05:02 23.72 15.10 0.630182E+09 845.65 17-OCT-09:00 21.10 16.29
November 0.481470E+10 5483.69 09-NOV-15:00 23.30 12.64 0.603673E+09 845.61 30-NOV-14:00 17.80 10.67
December 0.402826E+10 3947.76 11-DEC-04:02 9.27 4.65 0.558417E+09 845.61 11-DEC-14:09 13.90 7.45
                     
Annual Sum or Average 0.938486E+11         0.740982E+10        
Minimum of Months 0.374763E+10 3693.53   2.98 1.95 0.534920E+09 842.90   13.90 7.45
Maximum of Months 0.131504E+11 16500.73   35.10 17.94 0.690256E+09 846.24   37.07 18.70



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.345655E+10 4719.48 04-JAN-09:20 9.07 3.28 0.375867E+09 544.96 02-JAN-10:09 9.07 3.28
February 0.376329E+10 6916.82 21-FEB-08:50 11.68 4.50 0.352323E+09 544.95 07-FEB-10:09 11.68 4.50
March 0.535518E+10 7222.03 07-MAR-09:10 15.18 7.16 0.430748E+09 544.95 06-MAR-10:09 15.18 7.16
April 0.763540E+10 16015.20 30-APR-09:32 21.47 13.12 0.392111E+09 544.98 19-APR-09:09 21.47 13.12
May 0.895429E+10 16873.64 29-MAY-08:52 22.20 15.42 0.427577E+09 545.65 30-MAY-09:00 28.90 14.30
June 0.106777E+11 16635.49 04-JUN-08:62 24.27 16.88 0.426459E+09 545.57 07-JUN-09:00 32.80 15.59
July 0.104383E+11 16397.08 16-JUL-08:32 27.60 18.83 0.396341E+09 545.87 03-JUL-09:00 27.60 18.83
August 0.104443E+11 16412.10 20-AUG-09:02 26.47 16.50 0.443741E+09 545.85 04-AUG-09:00 26.47 16.50
September 0.816035E+10 16935.38 04-SEP-08:12 21.83 17.83 0.394463E+09 545.64 05-SEP-09:39 24.27 18.06
October 0.621761E+10 10158.40 22-OCT-08:53 19.40 11.77 0.404738E+09 544.99 17-OCT-09:00 19.40 11.77
November 0.442302E+10 7627.02 10-NOV-08:40 18.13 11.62 0.386628E+09 544.95 24-NOV-10:09 17.48 6.61
December 0.346024E+10 3759.58 07-DEC-09:25 5.30 0.63 0.359048E+09 544.95 04-DEC-10:09 5.30 0.63
                     
Annual Sum or Average 0.829863E+11         0.479004E+10        
Minimum of Months 0.345655E+10 3759.58   5.30 0.63 0.352323E+09 544.95   5.30 0.63
Maximum of Months 0.106777E+11 16935.38   27.60 18.83 0.443741E+09 545.87   32.80 18.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.760795E+10 13931.92 12-JAN-14:10 18.40 9.78 0.614524E+09 846.26 03-JAN-14:50 18.40 9.78
February 0.734784E+10 20322.76 20-FEB-13:42 22.02 8.45 0.561988E+09 847.19 22-FEB-14:30 21.95 7.96
March 0.891847E+10 12672.44 16-MAR-12:50 22.02 8.91 0.674988E+09 846.70 22-MAR-13:50 24.50 9.16
April 0.106563E+11 12512.91 30-APR-14:12 29.60 12.57 0.607738E+09 846.25 21-APR-13:20 29.60 12.57
May 0.103090E+11 14240.14 22-MAY-05:03 17.98 13.97 0.661991E+09 845.66 08-MAY-09:09 17.98 13.97
June 0.124757E+11 14740.09 19-JUN-05:02 22.80 15.92 0.661494E+09 845.65 22-JUN-09:09 22.88 16.93
July 0.131460E+11 15182.99 03-JUL-04:12 28.53 17.94 0.615122E+09 846.44 31-JUL-13:20 32.60 19.85
August 0.151350E+11 19471.52 06-AUG-15:01 36.10 18.50 0.690558E+09 847.10 29-AUG-13:00 31.70 19.58
September 0.127817E+11 20491.26 17-SEP-13:12 31.87 15.88 0.613408E+09 846.31 15-SEP-13:00 31.87 15.88
October 0.122125E+11 21315.03 29-OCT-12:52 23.90 11.53 0.635005E+09 869.39 30-OCT-13:20 23.30 11.27
November 0.994724E+10 19925.29 12-NOV-13:02 13.98 7.41 0.619014E+09 857.59 09-NOV-14:09 13.98 7.41
December 0.801400E+10 13277.67 07-DEC-13:40 15.20 6.59 0.596521E+09 846.27 01-DEC-14:20 15.20 6.59
                     
Annual Sum or Average 0.128552E+12         0.755235E+10        
Minimum of Months 0.734784E+10 12512.91   13.98 6.59 0.561988E+09 845.65   13.98 6.59
Maximum of Months 0.151350E+11 21315.03   36.10 18.50 0.690558E+09 869.39   32.60 19.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.500979E+10 7318.48 12-JAN-15:30 18.90 10.10 0.374274E+09 544.94 11-JAN-14:00 18.90 10.10
February 0.553774E+10 10712.53 20-FEB-16:23 22.75 8.45 0.355060E+09 544.94 14-FEB-14:00 22.75 8.45
March 0.851820E+10 16868.22 26-MAR-16:32 22.60 9.13 0.439713E+09 544.95 06-MAR-10:09 22.60 9.13
April 0.128935E+11 22457.83 16-APR-16:21 30.00 11.59 0.395838E+09 544.97 24-APR-13:39 24.80 9.97
May 0.110779E+11 23118.44 29-MAY-15:31 32.93 16.65 0.427672E+09 544.97 08-MAY-09:09 32.93 16.65
June 0.141183E+11 23858.48 04-JUN-16:01 35.50 17.23 0.427237E+09 544.97 30-JUN-09:39 25.17 17.65
July 0.151003E+11 22125.19 09-JUL-16:42 32.88 19.22 0.397422E+09 544.96 11-JUL-09:09 29.18 18.50
August 0.182730E+11 23341.44 06-AUG-16:21 36.10 18.53 0.446254E+09 544.98 17-AUG-13:30 25.00 17.14
September 0.104805E+11 22619.62 10-SEP-15:32 31.10 16.94 0.395002E+09 544.97 25-SEP-13:50 24.90 13.77
October 0.926363E+10 21042.32 29-OCT-15:32 23.50 11.40 0.409709E+09 544.98 17-OCT-09:00 23.50 11.40
November 0.738151E+10 13385.19 10-NOV-06:03 17.87 11.05 0.401261E+09 544.95 30-NOV-14:00 17.80 10.67
December 0.647198E+10 11599.05 11-DEC-06:03 10.68 5.95 0.387375E+09 544.95 11-DEC-14:09 13.90 7.45
                     
Annual Sum or Average 0.124126E+12         0.485682E+10        
Minimum of Months 0.500979E+10 7318.48   10.68 5.95 0.355060E+09 544.94   13.90 7.45
Maximum of Months 0.182730E+11 23858.48   36.10 19.22 0.446254E+09 544.98   32.93 18.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.212077E+10 3315.12 12-JAN-14:30 18.60 9.87 0.499203E+09 770.17 13-JAN-14:00 18.30 8.81
February 0.247274E+10 3462.41 20-FEB-15:53 23.30 8.66 0.476111E+09 839.09 23-FEB-14:00 21.10 7.10
March 0.363032E+10 4363.61 22-MAR-14:40 24.07 8.96 0.608721E+09 845.61 22-MAR-13:09 24.07 8.96
April 0.534932E+10 7662.63 21-APR-15:00 32.20 15.49 0.590715E+09 845.63 27-APR-09:09 20.87 11.97
May 0.821371E+10 12660.64 31-MAY-03:02 26.70 12.65 0.660815E+09 845.63 08-MAY-09:09 26.70 12.65
June 0.107267E+11 14614.09 18-JUN-14:51 36.70 16.60 0.662000E+09 845.63 27-JUN-09:09 25.10 15.77
July 0.102048E+11 14657.25 03-JUL-04:22 28.35 17.94 0.615434E+09 845.74 03-JUL-13:50 37.62 18.87
August 0.935585E+10 12374.14 08-AUG-05:02 24.82 17.61 0.689541E+09 845.63 17-AUG-13:20 24.80 17.12
September 0.708180E+10 10652.04 01-SEP-05:02 19.50 16.27 0.608630E+09 845.63 11-SEP-09:39 25.03 12.12
October 0.508307E+10 7930.71 05-OCT-05:03 21.32 16.10 0.609136E+09 845.63 02-OCT-09:09 21.32 16.10
November 0.312678E+10 3924.79 09-NOV-15:10 23.30 12.70 0.532010E+09 823.22 09-NOV-14:00 23.30 12.70
December 0.183708E+10 2713.38 07-DEC-14:20 15.77 6.80 0.474250E+09 740.66 08-DEC-14:00 17.20 7.54
                     
Annual Sum or Average 0.692030E+11         0.702657E+10        
Minimum of Months 0.183708E+10 2713.38   15.77 6.80 0.474250E+09 740.66   17.20 7.10
Maximum of Months 0.107267E+11 14657.25   36.70 17.94 0.689541E+09 845.74   37.62 18.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.240538E+10 3269.05 12-JAN-14:00 18.30 9.73 0.246531E+09 514.83 04-JAN-09:00 18.30 9.73
February 0.286452E+10 4801.42 21-FEB-10:00 16.70 6.62 0.239076E+09 521.20 22-FEB-11:20 17.03 6.18
March 0.420665E+10 6220.87 07-MAR-09:40 15.73 7.28 0.303082E+09 521.21 17-MAR-10:09 8.48 2.02
April 0.620413E+10 17276.68 30-APR-09:12 20.73 12.92 0.286607E+09 521.23 19-APR-08:00 20.73 12.92
May 0.854824E+10 17377.36 29-MAY-08:52 22.20 15.42 0.314046E+09 521.57 30-MAY-07:40 26.33 12.74
June 0.101742E+11 17355.64 25-JUN-08:52 25.00 16.16 0.313644E+09 522.28 07-JUN-10:30 25.00 16.16
July 0.949679E+10 17124.87 16-JUL-08:42 27.70 18.98 0.292602E+09 527.91 20-JUL-15:20 24.97 22.86
August 0.912982E+10 17281.52 06-AUG-08:12 27.23 17.51 0.325846E+09 521.43 09-AUG-08:00 28.30 18.95
September 0.752092E+10 17337.26 04-SEP-09:02 23.77 18.19 0.289536E+09 521.32 18-SEP-08:00 25.00 17.03
October 0.528583E+10 9080.99 01-OCT-08:23 20.25 12.11 0.291014E+09 521.24 17-OCT-10:09 21.47 16.47
November 0.335157E+10 6430.33 10-NOV-09:10 18.48 11.84 0.263420E+09 521.21 09-NOV-11:20 18.48 11.84
December 0.216659E+10 2797.25 07-DEC-13:50 15.40 6.66 0.232814E+09 490.89 07-DEC-09:00 15.40 6.66
                     
Annual Sum or Average 0.713546E+11         0.339822E+10        
Minimum of Months 0.216659E+10 2797.25   15.40 6.62 0.232814E+09 490.89   8.48 2.02
Maximum of Months 0.101742E+11 17377.36   27.70 18.98 0.325846E+09 527.91   28.30 22.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.668233E+10 14262.71 12-JAN-14:20 18.50 9.82 0.602246E+09 845.96 03-JAN-14:00 18.50 9.82
February 0.625069E+10 18955.13 20-FEB-15:13 23.30 8.81 0.550416E+09 846.62 07-FEB-14:00 23.30 8.81
March 0.719276E+10 12072.17 16-MAR-13:30 22.50 9.16 0.660391E+09 846.34 22-MAR-13:50 24.50 9.16
April 0.773140E+10 18282.69 30-APR-13:52 29.40 12.55 0.600407E+09 845.90 21-APR-13:00 29.40 12.55
May 0.908488E+10 13815.66 31-MAY-03:02 26.70 12.65 0.660046E+09 845.66 05-MAY-13:00 26.70 12.65
June 0.106681E+11 14624.97 18-JUN-14:51 36.70 16.60 0.661489E+09 845.65 22-JUN-09:09 22.88 16.93
July 0.105364E+11 15928.58 03-JUL-04:22 28.35 17.94 0.615210E+09 845.65 26-JUL-09:20 30.37 18.98
August 0.114478E+11 18570.23 06-AUG-14:51 36.10 18.55 0.690056E+09 846.69 29-AUG-13:00 31.70 19.58
September 0.115672E+11 19316.62 04-SEP-13:02 30.60 18.77 0.612674E+09 857.55 29-SEP-13:39 28.13 14.71
October 0.108233E+11 20281.82 22-OCT-13:22 26.15 14.67 0.631335E+09 881.80 30-OCT-13:30 23.30 11.23
November 0.852664E+10 19597.56 11-NOV-13:12 18.30 8.08 0.606636E+09 872.04 09-NOV-14:09 18.30 8.08
December 0.627873E+10 12727.61 07-DEC-14:10 15.68 6.76 0.579975E+09 845.92 01-DEC-14:20 15.68 6.76
                     
Annual Sum or Average 0.106790E+12         0.747088E+10        
Minimum of Months 0.625069E+10 12072.17   15.68 6.76 0.550416E+09 845.65   15.68 6.76
Maximum of Months 0.115672E+11 20281.82   36.70 18.77 0.690056E+09 881.80   31.70 19.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.275258E+10 4809.58 12-JAN-15:30 18.90 10.10 0.335192E+09 536.55 12-JAN-14:00 18.90 10.10
February 0.303879E+10 7093.82 21-FEB-16:50 22.30 7.87 0.313514E+09 544.93 23-FEB-14:00 21.10 7.10
March 0.468570E+10 8684.76 21-MAR-16:00 25.00 9.53 0.395963E+09 544.95 22-MAR-13:00 24.40 9.14
April 0.653939E+10 19658.86 30-APR-16:31 30.20 12.69 0.380372E+09 544.96 24-APR-13:20 30.20 12.69
May 0.878600E+10 19701.64 14-MAY-17:01 31.52 13.41 0.424001E+09 544.96 08-MAY-09:09 31.52 13.41
June 0.104323E+11 19790.34 25-JUN-18:11 30.93 16.45 0.426617E+09 544.96 30-JUN-09:39 25.17 17.65
July 0.986748E+10 19428.85 23-JUL-15:31 31.50 21.33 0.396662E+09 544.96 26-JUL-09:20 30.37 18.98
August 0.966446E+10 19417.10 06-AUG-16:51 36.10 18.82 0.443995E+09 544.97 29-AUG-13:00 31.70 19.58
September 0.795473E+10 18151.05 04-SEP-16:22 30.00 17.98 0.391695E+09 544.96 25-SEP-13:39 24.80 13.70
October 0.603613E+10 13186.96 22-OCT-16:02 27.12 14.71 0.390260E+09 544.96 02-OCT-09:09 27.12 14.71
November 0.395017E+10 7692.18 09-NOV-15:40 23.30 12.89 0.352644E+09 544.93 09-NOV-14:00 23.30 12.89
December 0.255178E+10 4187.10 15-DEC-16:00 15.60 6.14 0.321177E+09 540.84 15-DEC-14:00 15.60 6.14
                     
Annual Sum or Average 0.762595E+11         0.457209E+10        
Minimum of Months 0.255178E+10 4187.10   15.60 6.14 0.313514E+09 536.55   15.60 6.14
Maximum of Months 0.104323E+11 19790.34   36.10 21.33 0.443995E+09 544.97   31.70 19.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.116045E+10 3043.21 12-JAN-14:30 18.60 9.87 0.474123E+09 714.45 13-JAN-14:00 18.30 8.81
February 0.166200E+10 3174.84 07-FEB-14:20 20.00 9.36 0.446893E+09 792.34 23-FEB-14:00 21.10 7.10
March 0.311907E+10 4255.06 16-MAR-16:00 22.20 8.37 0.569781E+09 845.60 16-MAR-13:00 22.20 8.37
April 0.536566E+10 8440.39 21-APR-15:00 32.20 15.49 0.571604E+09 845.63 03-APR-13:09 32.20 15.49
May 0.865033E+10 14316.23 31-MAY-05:03 24.22 11.57 0.655782E+09 845.63 15-MAY-09:00 24.22 11.57
June 0.118582E+11 19424.11 18-JUN-14:51 36.70 16.60 0.661624E+09 845.64 28-JUN-13:09 25.87 17.21
July 0.113508E+11 18982.59 02-JUL-16:12 38.13 18.77 0.615326E+09 845.63 11-JUL-09:09 29.18 18.50
August 0.101629E+11 19107.72 06-AUG-17:31 35.77 18.42 0.687648E+09 845.63 11-AUG-09:09 27.57 18.90
September 0.741634E+10 9551.66 20-SEP-05:02 18.12 13.48 0.602843E+09 845.63 26-SEP-13:09 25.78 15.08
October 0.492953E+10 8848.73 05-OCT-05:03 21.32 16.10 0.583467E+09 845.63 02-OCT-09:09 21.32 16.10
November 0.226280E+10 4209.88 09-NOV-14:10 23.30 12.48 0.498854E+09 805.11 09-NOV-14:00 23.30 12.64
December 0.842532E+09 2567.59 01-DEC-15:00 13.30 5.89 0.453226E+09 684.74 01-DEC-14:00 13.30 5.89
                     
Annual Sum or Average 0.687806E+11         0.682117E+10        
Minimum of Months 0.842532E+09 2567.59   13.30 5.89 0.446893E+09 684.74   13.30 5.89
Maximum of Months 0.118582E+11 19424.11   38.13 18.77 0.687648E+09 845.64   32.20 18.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.166748E+10 2846.71 12-JAN-14:30 18.60 9.87 0.315410E+09 487.82 04-JAN-10:30 18.60 9.87
February 0.220505E+10 3357.73 21-FEB-10:30 18.35 7.04 0.308392E+09 544.92 21-FEB-10:50 19.45 7.26
March 0.356952E+10 5491.20 16-MAR-10:00 18.90 7.68 0.403589E+09 544.95 06-MAR-10:09 18.90 7.68
April 0.605344E+10 17502.56 30-APR-08:42 19.72 12.65 0.388294E+09 544.99 19-APR-09:09 19.72 12.65
May 0.889170E+10 16704.14 21-MAY-14:22 34.70 17.80 0.426761E+09 545.55 30-MAY-09:00 28.90 14.30
June 0.111266E+11 17845.32 25-JUN-09:02 25.28 16.19 0.426755E+09 545.50 09-JUN-09:00 25.28 16.19
July 0.104274E+11 17636.36 23-JUL-10:52 28.30 20.11 0.396893E+09 545.71 28-JUL-09:00 30.60 19.45
August 0.984416E+10 17825.64 06-AUG-08:12 27.23 17.51 0.443313E+09 545.51 01-AUG-09:00 27.23 17.51
September 0.780126E+10 17686.30 17-SEP-09:42 26.65 16.10 0.393304E+09 544.99 11-SEP-09:50 26.65 16.10
October 0.494321E+10 8780.73 05-OCT-08:50 24.63 17.73 0.392544E+09 544.98 17-OCT-09:00 21.10 16.29
November 0.259676E+10 5676.34 10-NOV-09:30 18.85 11.99 0.343898E+09 544.95 09-NOV-10:00 18.85 11.99
December 0.136023E+10 2399.14 01-DEC-10:30 13.05 5.08 0.297901E+09 460.23 01-DEC-10:39 13.33 5.28
                     
Annual Sum or Average 0.704868E+11         0.453705E+10        
Minimum of Months 0.136023E+10 2399.14   13.05 5.08 0.297901E+09 460.23   13.33 5.28
Maximum of Months 0.111266E+11 17845.32   34.70 20.11 0.443313E+09 545.71   30.60 19.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.513542E+10 13827.18 12-JAN-14:30 18.60 9.87 0.574759E+09 845.72 12-JAN-14:50 18.80 9.97
February 0.500731E+10 13090.27 22-FEB-13:30 21.15 7.71 0.526077E+09 845.93 07-FEB-14:39 21.15 7.71
March 0.619491E+10 12277.72 16-MAR-14:10 22.80 9.24 0.633402E+09 845.64 09-MAR-14:09 22.80 9.24
April 0.762351E+10 20651.84 30-APR-13:22 29.40 12.42 0.587709E+09 845.67 03-APR-13:09 29.40 12.42
May 0.954063E+10 20049.27 21-MAY-14:22 34.70 17.80 0.654842E+09 845.65 03-MAY-13:00 34.70 17.80
June 0.118207E+11 20855.50 18-JUN-14:51 36.70 16.60 0.660475E+09 845.66 28-JUN-13:09 25.87 17.21
July 0.117171E+11 20427.12 02-JUL-16:12 38.13 18.77 0.614628E+09 845.64 11-JUL-09:09 29.18 18.50
August 0.123711E+11 21135.03 06-AUG-14:51 36.10 18.55 0.688187E+09 846.97 29-AUG-13:00 31.70 19.58
September 0.119981E+11 22388.91 17-SEP-14:22 32.50 16.13 0.609875E+09 846.32 15-SEP-13:00 32.50 16.13
October 0.104275E+11 22705.73 22-OCT-13:22 26.15 14.67 0.620031E+09 848.99 03-OCT-13:39 26.15 14.67
November 0.715162E+10 16221.73 09-NOV-13:50 23.22 12.39 0.584219E+09 846.48 08-NOV-14:00 23.22 12.39
December 0.466968E+10 11408.09 07-DEC-14:30 15.85 6.83 0.550771E+09 845.64 01-DEC-14:09 15.85 6.83
                     
Annual Sum or Average 0.103657E+12         0.730498E+10        
Minimum of Months 0.466968E+10 11408.09   15.85 6.83 0.526077E+09 845.64   15.85 6.83
Maximum of Months 0.123711E+11 22705.73   38.13 18.77 0.688187E+09 848.99   34.70 19.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.196242E+10 4448.78 12-JAN-15:30 18.90 10.10 0.322180E+09 531.27 12-JAN-14:00 18.90 10.10
February 0.235196E+10 6757.61 21-FEB-16:50 22.30 7.87 0.300242E+09 544.93 23-FEB-14:00 21.10 7.10
March 0.408813E+10 8580.03 16-MAR-15:40 22.40 8.49 0.377860E+09 544.94 22-MAR-13:00 24.40 9.14
April 0.649925E+10 20629.91 30-APR-16:41 30.10 12.63 0.370402E+09 544.96 26-APR-13:50 30.10 12.63
May 0.912759E+10 20912.46 07-MAY-16:52 28.90 14.00 0.419888E+09 544.96 15-MAY-09:00 25.60 12.62
June 0.113397E+11 22407.40 25-JUN-17:01 31.60 16.78 0.425730E+09 544.96 28-JUN-13:09 25.87 17.21
July 0.107821E+11 21349.64 23-JUL-15:31 31.50 21.33 0.395895E+09 544.95 11-JUL-09:09 31.50 21.33
August 0.103446E+11 21382.08 06-AUG-16:51 36.10 18.82 0.441930E+09 544.96 29-AUG-13:00 31.70 19.58
September 0.825279E+10 21637.29 17-SEP-15:41 32.80 15.93 0.387945E+09 544.96 11-SEP-09:50 32.80 15.93
October 0.583511E+10 13359.99 01-OCT-15:02 32.62 15.84 0.378317E+09 544.96 02-OCT-09:00 25.60 16.62
November 0.322315E+10 7663.70 09-NOV-15:40 23.30 12.89 0.338464E+09 544.94 08-NOV-14:00 23.30 12.89
December 0.173601E+10 3443.86 15-DEC-16:10 15.50 6.10 0.307733E+09 516.85 15-DEC-16:19 15.40 6.06
                     
Annual Sum or Average 0.755428E+11         0.446659E+10        
Minimum of Months 0.173601E+10 3443.86   15.50 6.10 0.300242E+09 516.85   15.40 6.06
Maximum of Months 0.113397E+11 22407.40   36.10 21.33 0.441930E+09 544.96   32.80 21.33



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.292817E+10 7204.18 02-JAN-06:15 -0.2 -1.0 0.00 0.00 01-JAN-00:10 -0.2 -1.0
February 0.329587E+10 6748.90 21-FEB-06:15 5.20 0.40 0.00 0.00 01-FEB-00:10 5.20 0.40
March 0.508326E+10 6328.76 16-MAR-05:13 12.77 4.73 0.00 0.00 01-MAR-00:10 12.77 4.73
April 0.746241E+10 8313.36 04-APR-05:13 12.80 4.13 0.00 0.00 01-APR-00:10 12.80 4.13
May 0.890769E+10 9471.14 30-MAY-15:20 34.23 17.67 0.00 0.00 01-MAY-00:10 34.23 17.67
June 0.110071E+11 9916.21 05-JUN-05:03 21.38 13.55 0.00 0.00 01-JUN-00:10 21.38 13.55
July 0.111828E+11 13162.50 03-JUL-05:02 27.62 17.62 0.00 0.00 01-JUL-00:10 27.62 17.62
August 0.123702E+11 16844.86 07-AUG-05:15 25.73 16.21 0.00 0.00 01-AUG-00:10 25.73 16.21
September 0.913533E+10 10532.21 25-SEP-05:13 9.27 8.54 0.00 0.00 01-SEP-00:10 9.27 8.54
October 0.748153E+10 9719.87 10-OCT-05:15 12.97 8.53 0.00 0.00 01-OCT-00:10 12.97 8.53
November 0.494743E+10 8654.38 13-NOV-06:15 2.40 0.12 0.00 0.00 01-NOV-00:10 2.40 0.12
December 0.331650E+10 6348.29 11-DEC-06:15 10.77 5.99 0.00 0.00 01-DEC-00:10 10.77 5.99
                     
Annual Sum or Average 0.871183E+11         0.00        
Minimum of Months 0.292817E+10 6328.76   -0.2 -1.0 0.00 0.00   -0.2 -1.0
Maximum of Months 0.123702E+11 16844.86   34.23 17.67 0.00 0.00   34.23 17.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.116831E+10 4890.66 07-JAN-06:02 -1.8 -4.7 0.00 0.00 01-JAN-00:10 -1.8 -4.7
February 0.156296E+10 5086.54 10-FEB-06:01 -2.8 -5.6 0.00 0.00 01-FEB-00:10 -2.8 -5.6
March 0.267545E+10 4955.34 02-MAR-06:01 -3.5 -6.2 0.00 0.00 01-MAR-00:10 -3.5 -6.2
April 0.480375E+10 6009.52 21-APR-15:20 31.83 15.27 0.00 0.00 01-APR-00:10 31.83 15.27
May 0.739441E+10 7841.66 30-MAY-05:03 25.00 11.62 0.00 0.00 01-MAY-00:10 25.00 11.62
June 0.932651E+10 9044.00 17-JUN-05:02 24.13 13.85 0.00 0.00 01-JUN-00:10 24.13 13.85
July 0.886722E+10 8706.69 18-JUL-05:03 23.22 19.38 0.00 0.00 01-JUL-00:10 23.22 19.38
August 0.883989E+10 8083.16 07-AUG-14:50 35.00 18.73 0.00 0.00 01-AUG-00:10 35.00 18.73
September 0.740443E+10 7814.40 05-SEP-15:30 31.10 19.25 0.00 0.00 01-SEP-00:10 31.10 19.25
October 0.509911E+10 6576.28 05-OCT-05:15 20.93 15.98 0.00 0.00 01-OCT-00:10 20.93 15.98
November 0.247097E+10 4815.51 15-NOV-06:10 4.40 0.63 0.00 0.00 01-NOV-00:10 4.40 0.63
December 0.111034E+10 4921.17 22-DEC-06:01 -3.8 -5.5 0.00 0.00 01-DEC-00:10 -3.8 -5.5
                     
Annual Sum or Average 0.607233E+11         0.00        
Minimum of Months 0.111034E+10 4815.51   -3.8 -6.2 0.00 0.00   -3.8 -6.2
Maximum of Months 0.932651E+10 9044.00   35.00 19.38 0.00 0.00   35.00 19.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.510922E+09 4917.14 12-JAN-15:20 18.90 10.07 0.00 0.00 01-JAN-00:10 18.90 10.07
February 0.132825E+10 7282.31 22-FEB-14:10 21.78 7.94 0.00 0.00 01-FEB-00:10 21.78 7.94
March 0.334225E+10 10504.57 16-MAR-14:30 22.80 9.03 0.00 0.00 01-MAR-00:10 22.80 9.03
April 0.775143E+10 17062.77 28-APR-14:30 28.90 14.03 0.00 0.00 01-APR-00:10 28.90 14.03
May 0.127041E+11 20478.47 30-MAY-14:20 34.40 17.58 0.00 0.00 01-MAY-00:10 34.40 17.58
June 0.174097E+11 22249.18 15-JUN-14:30 38.05 15.77 0.00 0.00 01-JUN-00:10 38.05 15.77
July 0.163780E+11 22612.29 03-JUL-13:10 36.88 18.64 0.00 0.00 01-JUL-00:10 36.88 18.64
August 0.151707E+11 21426.96 07-AUG-14:30 35.00 18.73 0.00 0.00 01-AUG-00:10 35.00 18.73
September 0.116616E+11 18214.65 15-SEP-14:00 32.20 17.96 0.00 0.00 01-SEP-00:10 32.20 17.96
October 0.630539E+10 15976.34 03-OCT-14:20 32.43 19.47 0.00 0.00 01-OCT-00:10 32.43 19.47
November 0.197967E+10 8479.94 09-NOV-14:50 23.30 12.61 0.00 0.00 01-NOV-00:10 23.30 12.61
December 0.274022E+09 2501.75 09-DEC-13:40 17.40 7.21 0.00 0.00 01-DEC-00:10 17.40 7.21
                     
Annual Sum or Average 0.948161E+11         0.00        
Minimum of Months 0.274022E+09 2501.75   17.40 7.21 0.00 0.00   17.40 7.21
Maximum of Months 0.174097E+11 22612.29   38.05 19.47 0.00 0.00   38.05 19.47



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.362369E+10 2075.35 02-JAN-16:50 16.88 8.72 95231192.34 126.83 17-JAN-10:00 8.90 5.56
February 0.814058E+10 4033.32 21-FEB-17:00 22.20 7.81 86397383.63 126.84 13-FEB-14:00 22.20 7.81
March 0.144085E+11 7138.08 31-MAR-24:00 11.20 2.36 0.103236E+09 126.82 13-MAR-09:09 11.20 2.36
April 0.190490E+11 7791.67 26-APR-17:50 25.78 12.75 92284317.65 139.46 21-APR-13:00 25.78 12.75
May 0.467703E+10 3501.51 31-MAY-23:40 25.53 11.91 99237527.98 126.86 24-MAY-13:30 25.53 11.91
June 0.945230E+10 5337.58 30-JUN-23:55 27.70 17.05 98962994.47 126.85 29-JUN-09:30 27.70 17.05
July 0.148145E+11 7258.93 31-JUL-23:57 27.50 18.10 91888503.92 126.85 19-JUL-09:09 27.50 18.10
August 0.200664E+11 7879.04 27-AUG-21:03 26.20 14.02 0.105823E+09 140.94 07-AUG-13:00 26.20 14.02
September 0.459244E+10 3513.03 30-SEP-24:00 16.10 8.62 91616369.04 126.86 05-SEP-09:00 16.10 8.62
October 0.964800E+10 5317.32 31-OCT-24:00 10.60 4.98 95238258.51 126.86 04-OCT-09:00 10.60 4.98
November 0.139679E+11 6032.51 09-NOV-16:40 22.97 12.88 94301872.84 126.84 01-NOV-09:00 22.97 12.88
December 0.192349E+11 7799.74 18-DEC-16:40 9.27 0.10 91880955.00 126.82 14-DEC-10:00 9.27 0.10
                     
Annual Sum or Average 0.141675E+12         0.114610E+10        
Minimum of Months 0.362369E+10 2075.35   9.27 0.10 86397383.63 126.82   8.90 0.10
Maximum of Months 0.200664E+11 7879.04   27.70 18.10 0.105823E+09 140.94   27.70 18.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.212152E+10 1816.69 30-JAN-17:00 15.60 6.12 95231060.90 126.83 02-JAN-14:39 15.60 6.12
February 0.674631E+10 3736.57 21-FEB-17:00 22.20 7.81 86397318.90 126.84 13-FEB-14:00 22.20 7.81
March 0.129566E+11 6614.46 31-MAR-24:00 11.20 2.36 0.103236E+09 126.82 13-MAR-09:09 11.20 2.36
April 0.178904E+11 7371.25 26-APR-17:50 25.78 12.75 92172474.43 138.28 21-APR-13:00 25.78 12.75
May 0.429104E+10 3432.78 31-MAY-23:55 25.20 11.70 99237066.77 126.85 24-MAY-13:39 25.20 11.70
June 0.901151E+10 5188.93 30-JUN-23:55 27.70 17.05 98962887.99 126.85 29-JUN-09:00 27.70 17.05
July 0.141268E+11 7008.77 31-JUL-23:57 27.50 18.10 91889329.56 126.85 19-JUL-09:09 27.50 18.10
August 0.188212E+11 7347.17 31-AUG-17:50 27.98 16.89 0.105148E+09 138.10 04-AUG-13:00 27.98 16.89
September 0.415598E+10 3307.37 30-SEP-24:00 16.10 8.62 91614274.27 126.85 13-SEP-13:00 16.10 8.62
October 0.868832E+10 4856.95 31-OCT-24:00 10.60 4.98 95237666.87 126.85 04-OCT-09:00 10.60 4.98
November 0.122670E+11 5663.07 09-NOV-16:50 22.88 12.85 94301782.10 126.83 01-NOV-13:00 22.88 12.85
December 0.167871E+11 7260.71 15-DEC-16:50 15.10 5.92 91880989.82 126.82 14-DEC-10:00 15.10 5.92
                     
Annual Sum or Average 0.127864E+12         0.114531E+10        
Minimum of Months 0.212152E+10 1816.69   10.60 2.36 86397318.90 126.82   10.60 2.36
Maximum of Months 0.188212E+11 7371.25   27.98 18.10 0.105148E+09 138.28   27.98 18.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.939368E+09 1765.08 12-JAN-16:50 17.98 9.87 94967479.67 126.86 23-JAN-10:09 5.78 4.06
February 0.555760E+10 3723.14 21-FEB-17:00 22.20 7.81 86397294.77 126.84 13-FEB-14:00 22.20 7.81
March 0.120539E+11 6301.77 31-MAR-23:20 11.33 2.45 0.103236E+09 126.82 13-MAR-09:09 11.33 2.45
April 0.176321E+11 7451.15 27-APR-17:50 27.30 12.72 92076577.11 138.41 21-APR-13:00 27.30 12.72
May 0.426103E+10 3466.77 31-MAY-23:55 25.20 11.70 99237210.92 126.86 24-MAY-13:39 25.20 11.70
June 0.910300E+10 5208.26 30-JUN-23:55 27.70 17.05 98962980.13 126.85 28-JUN-09:00 27.70 17.05
July 0.142532E+11 7024.59 31-JUL-23:57 27.50 18.10 91889152.06 126.85 19-JUL-09:20 27.50 18.10
August 0.188766E+11 7459.97 27-AUG-20:12 27.57 14.58 0.105047E+09 138.56 04-AUG-13:00 27.57 14.58
September 0.411627E+10 3184.20 30-SEP-23:30 16.40 9.13 91614509.20 126.86 13-SEP-13:00 16.40 9.13
October 0.822814E+10 4525.82 31-OCT-23:30 10.60 4.77 95237698.29 126.85 04-OCT-09:00 10.60 4.77
November 0.110056E+11 5690.48 09-NOV-16:50 22.88 12.85 94301803.18 126.83 01-NOV-13:00 22.88 12.85
December 0.149106E+11 7170.15 15-DEC-16:50 15.10 5.92 91881010.26 126.82 14-DEC-10:00 15.10 5.92
                     
Annual Sum or Average 0.120937E+12         0.114485E+10        
Minimum of Months 0.939368E+09 1765.08   10.60 2.45 86397294.77 126.82   5.78 2.45
Maximum of Months 0.188766E+11 7459.97   27.70 18.10 0.105047E+09 138.56   27.70 18.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.238639E+12 92468.66 02-JAN-17:00 16.70 8.66 0.206151E+10 2747.81 03-JAN-14:00 20.60 8.39
February 0.434534E+12 183235.75 21-FEB-17:00 22.20 7.81 0.187218E+10 2748.80 28-FEB-14:39 14.27 7.56
March 0.726368E+12 357622.40 31-MAR-24:00 11.20 2.36 0.223623E+10 2747.66 24-MAR-13:20 11.20 2.36
April 0.935338E+12 368208.04 17-APR-07:55 12.20 7.83 0.219043E+10 3564.25 21-APR-13:00 32.20 15.21
May 0.240455E+12 175578.41 31-MAY-23:55 25.20 11.70 0.214931E+10 2747.93 18-MAY-13:50 25.20 11.70
June 0.469067E+12 267181.76 30-JUN-24:00 27.70 17.05 0.214336E+10 2749.52 30-JUN-13:09 27.70 17.05
July 0.731898E+12 355054.88 31-JUL-23:23 28.00 17.89 0.198983E+10 2750.74 20-JUL-13:00 28.00 17.89
August 0.963193E+12 366870.73 14-AUG-07:20 17.97 16.72 0.294662E+10 4108.99 07-AUG-13:00 17.97 16.72
September 0.238250E+12 176844.98 30-SEP-24:00 16.10 8.62 0.198414E+10 2749.03 22-SEP-09:50 16.10 8.62
October 0.489238E+12 268991.04 31-OCT-24:00 10.60 4.98 0.206329E+10 2749.35 05-OCT-13:09 10.60 4.98
November 0.709372E+12 277204.79 10-NOV-17:00 14.40 9.20 0.204271E+10 2747.73 01-NOV-13:09 14.40 9.20
December 0.976386E+12 368154.08 11-DEC-17:00 12.20 6.69 0.199358E+10 2858.88 08-DEC-14:00 12.20 6.69
                     
Annual Sum or Average 0.715274E+13         0.256732E+11        
Minimum of Months 0.238250E+12 92468.66   10.60 2.36 0.187218E+10 2747.66   10.60 2.36
Maximum of Months 0.976386E+12 368208.04   28.00 17.89 0.294662E+10 4108.99   32.20 17.89



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.264576E+09 13373.68 12-JAN-05:05 6.10
February 0.179605E+09 13257.36 13-FEB-04:04 11.13
March 0.179048E+09 13290.38 13-MAR-03:04 5.82
April 0.370179E+09 17649.04 29-APR-16:02 31.02
May 0.458702E+09 19475.02 20-MAY-16:02 32.20
June 0.395977E+09 23650.22 17-JUN-16:02 35.68
July 0.523947E+09 26349.64 01-JUL-16:02 37.88
August 0.497228E+09 21940.09 05-AUG-16:01 33.98
September 0.601211E+09 18935.05 02-SEP-16:02 32.23
October 0.479482E+09 14810.90 09-OCT-13:02 23.48
November 0.362044E+09 13600.38 27-NOV-04:45 3.40
December 0.340479E+09 13304.89 02-DEC-04:14 5.00
         
Annual Sum or Average 0.465248E+10      
Minimum of Months 0.179048E+09 13257.36   3.40
Maximum of Months 0.601211E+09 26349.64   37.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.296582E+09 71062.18 17-JAN-05:01 5.40
February 11636176.85 56225.09 27-FEB-06:03 8.80
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.148311E+09 70390.78 27-NOV-05:01 3.30
December 0.547979E+09 73247.56 04-DEC-05:01 -0.7
         
Annual Sum or Average 0.100451E+10      
Minimum of Months 0.00 0.00   -0.7
Maximum of Months 0.547979E+09 73247.56   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 721695.42 6221.33 28-JAN-06:01 -3.3
February 40837.05 364.46 02-FEB-06:03 -3.5
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 762532.47      
Minimum of Months 0.00 0.00   -3.5
Maximum of Months 721695.42 6221.33   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 995975.39 4616.69 28-JAN-06:01 -3.3
February 115329.32 1284.76 02-FEB-06:01 -3.5
March 493394.91 5190.95 02-MAR-06:01 -3.5
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 2571840.53 5812.63 30-DEC-06:01 -2.9
         
Annual Sum or Average 4176540.16      
Minimum of Months 0.00 0.00   -3.5
Maximum of Months 2571840.53 5812.63   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 15358.85 204.78 28-NOV-06:01 1.02
December 3054472.64 9980.16 27-DEC-06:01 -3.5
         
Annual Sum or Average 3069831.49      
Minimum of Months 0.00 0.00   -3.5
Maximum of Months 3054472.64 9980.16   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.382201E+09 12345.12 28-JAN-05:01 -2.9
February 0.197519E+09 12258.37 02-FEB-05:01 -2.4
March 49651008.97 11990.24 02-MAR-05:01 -3.9
April 55880.60 372.54 11-APR-05:03 4.90
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 98989483.32 12363.49 28-NOV-05:01 -0.3
December 0.520586E+09 12397.65 26-DEC-05:02 -0.6
         
Annual Sum or Average 0.124900E+10      
Minimum of Months 0.00 0.00   -3.9
Maximum of Months 0.520586E+09 12397.65   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.178401E+09 11415.96 28-JAN-05:01 -2.9
February 78738447.25 11383.59 02-FEB-05:01 -2.4
March 20637702.55 11003.33 02-MAR-06:01 -3.5
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 41435418.78 11636.77 28-NOV-05:01 -0.3
December 0.247009E+09 11580.32 27-DEC-05:01 -3.8
         
Annual Sum or Average 0.566222E+09      
Minimum of Months 0.00 0.00   -3.8
Maximum of Months 0.247009E+09 11636.77   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 57476188.08 12675.49 26-JAN-06:01 1.52
February 37440986.92 12628.28 02-FEB-06:01 -3.5
March 11322649.86 12610.95 02-MAR-06:01 -3.5
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 25324698.61 13142.04 28-NOV-05:01 -0.3
December 0.108467E+09 13139.60 27-DEC-05:01 -3.8
         
Annual Sum or Average 0.240032E+09      
Minimum of Months 0.00 0.00   -3.8
Maximum of Months 0.108467E+09 13142.04   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 95543208.97 10854.70 28-JAN-06:01 -3.3
February 55994592.95 10794.48 02-FEB-06:01 -3.5
March 11044117.76 10796.38 02-MAR-06:01 -3.5
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 19779961.14 10711.26 28-NOV-06:01 1.02
December 0.122587E+09 10893.60 27-DEC-06:01 -3.5
         
Annual Sum or Average 0.304948E+09      
Minimum of Months 0.00 0.00   -3.5
Maximum of Months 0.122587E+09 10893.60   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.215252E+10 16047.73 09-JAN-04:01 0.55
February 0.124194E+10 15081.56 03-FEB-05:01 -3.8
March 0.585899E+09 14728.37 01-MAR-05:01 1.20
April 34805443.76 12620.29 12-APR-05:03 4.22
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 5943319.43 9192.60 25-OCT-05:02 7.12
November 0.950507E+09 16415.29 27-NOV-04:01 3.80
December 0.274002E+10 16397.94 04-DEC-04:01 -0.1
         
Annual Sum or Average 0.771164E+10      
Minimum of Months 0.00 0.00   -3.8
Maximum of Months 0.274002E+10 16415.29   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.974339E+09 13760.40 09-JAN-04:01 0.55
February 0.480884E+09 13055.21 03-FEB-05:01 -3.8
March 0.223982E+09 12770.84 02-MAR-05:01 -3.9
April 10793780.24 7865.31 11-APR-05:03 4.90
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 3389911.11 6561.73 25-OCT-05:02 7.12
November 0.415424E+09 14193.83 27-NOV-04:01 3.80
December 0.123490E+10 14270.36 04-DEC-04:01 -0.1
         
Annual Sum or Average 0.334371E+10      
Minimum of Months 0.00 0.00   -3.9
Maximum of Months 0.123490E+10 14270.36   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.807477E+09 15906.64 17-JAN-05:01 5.40
February 0.485555E+09 15840.66 09-FEB-05:01 -0.4
March 0.216827E+09 15745.63 02-MAR-05:01 -3.9
April 20705825.34 12163.57 11-APR-05:03 4.90
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.358064E+09 17017.09 27-NOV-04:01 3.80
December 0.105623E+10 17380.07 26-DEC-04:01 -0.1
         
Annual Sum or Average 0.294486E+10      
Minimum of Months 0.00 0.00   -3.9
Maximum of Months 0.105623E+10 17380.07   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.718912E+09 14538.59 28-JAN-05:01 -2.9
February 0.415108E+09 14613.01 02-FEB-05:01 -2.4
March 0.126111E+09 14568.66 02-MAR-05:01 -3.9
April 7136344.58 7642.52 11-APR-05:03 4.90
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.262958E+09 14617.00 28-NOV-05:01 -0.3
December 0.875045E+09 15433.59 26-DEC-04:01 -0.1
         
Annual Sum or Average 0.240527E+10      
Minimum of Months 0.00 0.00   -3.9
Maximum of Months 0.875045E+09 15433.59   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 60759685.73 10460.34 17-JAN-05:01 5.40
February 76485805.17 10126.08 13-FEB-04:02 11.13
March 99780326.10 10597.87 20-MAR-03:02 9.22
April 0.116171E+09 9667.50 13-APR-03:02 9.22
May 59205543.03 7615.44 04-MAY-03:02 17.20
June 52863884.56 7896.65 29-JUN-03:02 18.23
July 61789606.71 5698.46 19-JUL-03:02 19.50
August 61779427.37 6351.08 06-AUG-15:41 36.10
September 59132402.95 7780.76 29-SEP-03:02 19.82
October 91049709.90 10533.32 16-OCT-03:02 13.98
November 91215562.75 11699.55 27-NOV-04:01 3.80
December 0.108219E+09 12866.63 18-DEC-04:02 5.40
         
Annual Sum or Average 0.938452E+09      
Minimum of Months 52863884.56 5698.46   3.80
Maximum of Months 0.116171E+09 12866.63   36.10



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.397987E+09 7477.78 31-JAN-06:03 5.97
February 0.123482E+09 7478.48 07-FEB-06:03 13.72
March 71165122.26 7542.61 07-MAR-06:02 12.20
April 49660503.58 6655.57 03-APR-04:02 19.53
May 44811659.84 6958.94 04-MAY-04:03 17.02
June 40342693.32 6768.14 22-JUN-03:02 25.10
July 41716711.70 6098.04 11-JUL-03:02 23.80
August 38800033.48 6634.87 04-AUG-03:02 24.22
September 37963541.85 6262.94 13-SEP-03:02 23.30
October 63366965.76 6504.78 10-OCT-04:03 12.98
November 0.121114E+09 7379.11 30-NOV-06:03 3.90
December 0.425366E+09 7491.99 01-DEC-06:03 4.68
         
Annual Sum or Average 0.145578E+10      
Minimum of Months 37963541.85 6098.04   3.90
Maximum of Months 0.425366E+09 7542.61   25.10



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.378273E+10 14227.98 09-JAN-06:03 2.98
February 0.256475E+10 10809.81 02-FEB-06:15 -3.7
March 0.185593E+10 14290.10 16-MAR-05:03 14.43
April 0.501209E+09 16378.95 22-APR-05:03 8.80
May 0.159233E+09 16695.39 08-MAY-05:02 14.40
June 82039299.82 11127.91 12-JUN-03:02 17.38
July 59146464.86 11997.29 05-JUL-03:02 18.90
August 72857486.31 11876.38 17-AUG-05:02 17.20
September 0.152697E+09 17645.98 25-SEP-05:02 9.08
October 0.495301E+09 17174.72 27-OCT-05:03 11.02
November 0.214558E+10 15658.46 09-NOV-06:02 13.40
December 0.464094E+10 20492.38 04-DEC-06:13 -0.9
         
Annual Sum or Average 0.165124E+11      
Minimum of Months 59146464.86 10809.81   -3.7
Maximum of Months 0.464094E+10 20492.38   18.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.420480E+09 609.34 08-JAN-07:30 3.05
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.420480E+09      
Minimum of Months 0.00 0.00   3.05
Maximum of Months 0.420480E+09 609.34   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:02 20.40
June 0.00 0.00 01-JUN-00:05 25.03
July 0.00 0.00 01-JUL-00:02 27.63
August 0.00 0.00 01-AUG-00:05 27.32
September 0.00 0.00 01-SEP-00:05 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.200626E+11 20994.62 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.181982E+11 20994.62 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.216246E+11 20994.62 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.193152E+11 20994.62 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.208436E+11 20994.62 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.207428E+11 20994.62 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.194159E+11 20994.62 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.216246E+11 20994.62 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.193152E+11 20994.62 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.200626E+11 20994.62 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.198274E+11 20994.62 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.194159E+11 20994.62 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.240449E+12     0.424397E+12    
Minimum of Months 0.181982E+11 20994.62   0.325565E+11 13457.54  
Maximum of Months 0.216246E+11 20994.62   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.180176E+11 18854.65 02-JAN-08:09 0.270551E+11 18128.59 02-JAN-08:09
February 0.163433E+11 18854.65 01-FEB-08:09 0.244881E+11 18128.59 01-FEB-08:09
March 0.194204E+11 18854.65 01-MAR-08:09 0.280558E+11 18128.59 01-MAR-08:09
April 0.173464E+11 18854.65 03-APR-07:10 0.261305E+11 18128.59 03-APR-07:10
May 0.187190E+11 18854.65 01-MAY-07:10 0.275555E+11 18128.59 01-MAY-07:10
June 0.186285E+11 18854.65 01-JUN-07:10 0.270261E+11 18128.59 01-JUN-07:10
July 0.174369E+11 18854.65 03-JUL-07:10 0.266527E+11 18128.59 03-JUL-07:10
August 0.194204E+11 18854.65 01-AUG-07:10 0.280558E+11 18128.59 01-AUG-07:10
September 0.173464E+11 18854.65 01-SEP-07:10 0.261160E+11 18128.59 01-SEP-07:10
October 0.180176E+11 18854.65 02-OCT-07:10 0.270624E+11 18128.59 02-OCT-07:10
November 0.178064E+11 18854.65 01-NOV-07:10 0.264424E+11 18128.59 01-NOV-07:10
December 0.174369E+11 18854.65 01-DEC-08:09 0.266454E+11 18128.59 01-DEC-08:09
             
Annual Sum or Average 0.215940E+12     0.321286E+12    
Minimum of Months 0.163433E+11 18854.65   0.244881E+11 18128.59  
Maximum of Months 0.194204E+11 18854.65   0.280558E+11 18128.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.180176E+11 18854.65 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.163433E+11 18854.65 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.194204E+11 18854.65 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.173464E+11 18854.65 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.187190E+11 18854.65 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.186285E+11 18854.65 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.174369E+11 18854.65 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.194204E+11 18854.65 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.173464E+11 18854.65 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.180176E+11 18854.65 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.178064E+11 18854.65 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.174369E+11 18854.65 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.215940E+12     0.321285E+12    
Minimum of Months 0.163433E+11 18854.65   0.244880E+11 18128.52  
Maximum of Months 0.194204E+11 18854.65   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.180176E+11 18854.65 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.163433E+11 18854.65 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.194204E+11 18854.65 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.173464E+11 18854.65 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.187190E+11 18854.65 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.186285E+11 18854.65 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.174369E+11 18854.65 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.194204E+11 18854.65 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.173464E+11 18854.65 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.180176E+11 18854.65 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.178064E+11 18854.65 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.174369E+11 18854.65 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.215940E+12     0.321285E+12    
Minimum of Months 0.163433E+11 18854.65   0.244880E+11 18128.52  
Maximum of Months 0.194204E+11 18854.65   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.166189E+10 2255.83 17-JAN-16:00 0.339718E+10 2276.32 02-JAN-08:09
February 0.146329E+10 2097.14 01-FEB-16:00 0.307485E+10 2276.32 01-FEB-08:09
March 0.167280E+10 2016.00 10-MAR-16:00 0.352283E+10 2276.32 01-MAR-08:09
April 0.145673E+10 1675.34 20-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.155716E+10 1454.29 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.153832E+10 1454.29 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.144682E+10 1624.53 07-JUL-07:30 0.334664E+10 2276.32 03-JUL-07:10
August 0.162734E+10 1610.17 17-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.147920E+10 1786.67 29-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.158182E+10 2122.31 13-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.163038E+10 2367.39 22-NOV-16:00 0.332024E+10 2276.32 01-NOV-07:10
December 0.162348E+10 2367.39 01-DEC-16:00 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.187392E+11     0.403423E+11    
Minimum of Months 0.144682E+10 1454.29   0.307485E+10 2276.32  
Maximum of Months 0.167280E+10 2367.39   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105983E+10 1455.49 17-JAN-16:00 0.218927E+10 1466.95 02-JAN-08:09
February 0.938735E+09 1360.39 13-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.107655E+10 1314.41 10-MAR-16:00 0.227025E+10 1466.95 01-MAR-08:09
April 0.943628E+09 937.20 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.101073E+10 937.20 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.999315E+09 937.20 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.940765E+09 937.20 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.105360E+10 937.20 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.951936E+09 1062.85 29-SEP-15:00 0.211328E+10 1466.95 01-SEP-07:10
October 0.101635E+10 1352.21 13-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.104498E+10 1525.64 22-NOV-16:00 0.213969E+10 1466.95 01-NOV-07:10
December 0.103862E+10 1525.64 01-DEC-16:00 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.120750E+11     0.259981E+11    
Minimum of Months 0.938735E+09 937.20   0.198155E+10 1466.95  
Maximum of Months 0.107655E+10 1525.64   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.160156E+10 2248.44 17-JAN-16:00 0.339723E+10 2276.35 02-JAN-08:09
February 0.142970E+10 2002.11 23-FEB-16:00 0.307490E+10 2276.35 01-FEB-08:09
March 0.165904E+10 1999.35 10-MAR-16:00 0.352288E+10 2276.35 01-MAR-08:09
April 0.146238E+10 1674.10 20-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.156760E+10 1454.32 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.155036E+10 1454.32 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.145963E+10 1661.54 07-JUL-07:30 0.334669E+10 2276.35 03-JUL-07:10
August 0.163347E+10 1640.67 17-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.147350E+10 1630.08 18-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.155976E+10 2112.65 13-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.157662E+10 2367.44 22-NOV-16:00 0.332029E+10 2276.35 01-NOV-07:10
December 0.156971E+10 2367.44 01-DEC-16:00 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.185433E+11     0.403429E+11    
Minimum of Months 0.142970E+10 1454.32   0.307490E+10 2276.35  
Maximum of Months 0.165904E+10 2367.44   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104330E+10 1446.33 17-JAN-16:00 0.218926E+10 1466.94 02-JAN-08:09
February 0.929175E+09 1304.86 03-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.107292E+10 1265.09 27-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.940578E+09 1147.23 20-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.100528E+10 937.20 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.993176E+09 937.20 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.934598E+09 1133.98 07-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.105110E+10 1162.34 24-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.953619E+09 1178.96 18-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.101036E+10 1372.94 13-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.102435E+10 1525.64 22-NOV-16:00 0.213967E+10 1466.94 01-NOV-07:10
December 0.102401E+10 1525.64 01-DEC-16:00 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.119825E+11     0.259979E+11    
Minimum of Months 0.929175E+09 937.20   0.198154E+10 1466.94  
Maximum of Months 0.107292E+10 1525.64   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.166503E+10 2259.11 17-JAN-16:00 0.339718E+10 2276.32 02-JAN-08:09
February 0.146574E+10 2104.30 01-FEB-16:00 0.307485E+10 2276.32 01-FEB-08:09
March 0.167432E+10 2026.28 10-MAR-16:00 0.352283E+10 2276.32 01-MAR-08:09
April 0.145718E+10 1695.22 20-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.155742E+10 1454.29 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.153866E+10 1454.29 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.144730E+10 1645.63 07-JUL-07:30 0.334664E+10 2276.32 03-JUL-07:10
August 0.162777E+10 1631.70 17-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.148081E+10 1797.62 29-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.158333E+10 2129.46 13-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.163373E+10 2367.39 22-NOV-16:00 0.332024E+10 2276.32 01-NOV-07:10
December 0.162607E+10 2367.39 01-DEC-16:00 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.187574E+11     0.403423E+11    
Minimum of Months 0.144730E+10 1454.29   0.307485E+10 2276.32  
Maximum of Months 0.167432E+10 2367.39   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.106027E+10 1456.02 17-JAN-16:00 0.218927E+10 1466.95 02-JAN-08:09
February 0.939142E+09 1361.68 13-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.107668E+10 1315.97 10-MAR-16:00 0.227025E+10 1466.95 01-MAR-08:09
April 0.943844E+09 937.20 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.101093E+10 937.20 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.999544E+09 937.20 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.940969E+09 937.20 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.105388E+10 1026.01 16-AUG-15:00 0.227025E+10 1466.95 01-AUG-07:10
September 0.952268E+09 1062.56 29-SEP-15:00 0.211328E+10 1466.95 01-SEP-07:10
October 0.101670E+10 1353.91 13-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.104534E+10 1525.64 22-NOV-16:00 0.213969E+10 1466.95 01-NOV-07:10
December 0.103916E+10 1525.64 01-DEC-16:00 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.120787E+11     0.259981E+11    
Minimum of Months 0.939142E+09 937.20   0.198155E+10 1466.95  
Maximum of Months 0.107668E+10 1525.64   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.160392E+10 2252.09 17-JAN-16:00 0.339723E+10 2276.35 02-JAN-08:09
February 0.143048E+10 2013.34 23-FEB-16:00 0.307490E+10 2276.35 01-FEB-08:09
March 0.165980E+10 2010.32 10-MAR-16:00 0.352288E+10 2276.35 01-MAR-08:09
April 0.146317E+10 1693.98 20-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.156820E+10 1454.32 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.155103E+10 1454.32 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.146072E+10 1681.40 07-JUL-07:30 0.334669E+10 2276.35 03-JUL-07:10
August 0.163444E+10 1661.07 17-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.147398E+10 1639.29 18-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.155739E+10 2120.20 13-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.157830E+10 2367.44 22-NOV-16:00 0.332029E+10 2276.35 01-NOV-07:10
December 0.157827E+10 2367.44 01-DEC-16:00 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.185597E+11     0.403429E+11    
Minimum of Months 0.143048E+10 1454.32   0.307490E+10 2276.35  
Maximum of Months 0.165980E+10 2367.44   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104375E+10 1447.13 17-JAN-16:00 0.218926E+10 1466.94 02-JAN-08:09
February 0.929509E+09 1306.31 03-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.107337E+10 1267.57 27-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.940833E+09 1149.99 20-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.100546E+10 937.20 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.993435E+09 937.20 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.934989E+09 1136.36 07-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.105149E+10 1164.51 24-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.953994E+09 1181.19 18-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.101080E+10 1374.07 13-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.102500E+10 1525.64 22-NOV-16:00 0.213967E+10 1466.94 01-NOV-07:10
December 0.102437E+10 1525.64 01-DEC-16:00 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.119870E+11     0.259979E+11    
Minimum of Months 0.929509E+09 937.20   0.198154E+10 1466.94  
Maximum of Months 0.107337E+10 1525.64   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.166510E+10 2258.99 17-JAN-16:00 0.339718E+10 2276.32 02-JAN-08:09
February 0.146577E+10 2104.55 01-FEB-16:00 0.307485E+10 2276.32 01-FEB-08:09
March 0.167434E+10 2025.94 10-MAR-16:00 0.352283E+10 2276.32 01-MAR-08:09
April 0.145718E+10 1694.66 20-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.155743E+10 1454.29 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.153866E+10 1454.29 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.144733E+10 1644.96 07-JUL-07:30 0.334664E+10 2276.32 03-JUL-07:10
August 0.162777E+10 1631.13 17-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.148084E+10 1798.11 29-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.158347E+10 2129.20 13-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.163386E+10 2367.39 22-NOV-16:00 0.332024E+10 2276.32 01-NOV-07:10
December 0.162612E+10 2367.39 01-DEC-16:00 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.187579E+11     0.403423E+11    
Minimum of Months 0.144733E+10 1454.29   0.307485E+10 2276.32  
Maximum of Months 0.167434E+10 2367.39   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.106030E+10 1455.95 17-JAN-16:00 0.218927E+10 1466.95 02-JAN-08:09
February 0.939151E+09 1361.58 13-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.107671E+10 1315.76 10-MAR-16:00 0.227025E+10 1466.95 01-MAR-08:09
April 0.943853E+09 937.20 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.101094E+10 937.20 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.999553E+09 937.20 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.940975E+09 937.20 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.105388E+10 1025.51 16-AUG-15:00 0.227025E+10 1466.95 01-AUG-07:10
September 0.952289E+09 1063.02 29-SEP-15:00 0.211328E+10 1466.95 01-SEP-07:10
October 0.101672E+10 1353.77 13-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.104543E+10 1525.64 22-NOV-16:00 0.213969E+10 1466.95 01-NOV-07:10
December 0.103924E+10 1525.64 01-DEC-16:00 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.120790E+11     0.259981E+11    
Minimum of Months 0.939151E+09 937.20   0.198155E+10 1466.95  
Maximum of Months 0.107671E+10 1525.64   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.160394E+10 2251.98 17-JAN-16:00 0.339723E+10 2276.35 02-JAN-08:09
February 0.143048E+10 2013.04 23-FEB-16:00 0.307490E+10 2276.35 01-FEB-08:09
March 0.165980E+10 2009.99 10-MAR-16:00 0.352288E+10 2276.35 01-MAR-08:09
April 0.146318E+10 1693.41 20-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.156821E+10 1454.32 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.155104E+10 1454.32 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.146072E+10 1680.73 07-JUL-07:30 0.334669E+10 2276.35 03-JUL-07:10
August 0.163444E+10 1660.49 17-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.147400E+10 1639.79 18-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.155739E+10 2119.94 13-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.157831E+10 2367.44 22-NOV-16:00 0.332029E+10 2276.35 01-NOV-07:10
December 0.157829E+10 2367.44 01-DEC-16:00 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.185598E+11     0.403429E+11    
Minimum of Months 0.143048E+10 1454.32   0.307490E+10 2276.35  
Maximum of Months 0.165980E+10 2367.44   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.104378E+10 1447.06 17-JAN-16:00 0.218926E+10 1466.94 02-JAN-08:09
February 0.929579E+09 1306.56 03-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.107339E+10 1267.54 27-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.940840E+09 1149.64 20-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.100547E+10 937.20 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.993445E+09 937.20 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.935033E+09 1136.13 07-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.105149E+10 1164.32 24-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.954040E+09 1181.58 18-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.101081E+10 1373.91 13-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.102506E+10 1525.64 22-NOV-16:00 0.213967E+10 1466.94 01-NOV-07:10
December 0.102439E+10 1525.64 01-DEC-16:00 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.119873E+11     0.259979E+11    
Minimum of Months 0.929579E+09 937.20   0.198154E+10 1466.94  
Maximum of Months 0.107339E+10 1525.64   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.497722E+09 520.85 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.451470E+09 520.85 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.536472E+09 520.85 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.479179E+09 520.85 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.517097E+09 520.85 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.514597E+09 520.85 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.481680E+09 520.85 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.536472E+09 520.85 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.479179E+09 520.85 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.497722E+09 520.85 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.491888E+09 520.85 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.481680E+09 520.85 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.596516E+10     0.153881E+12    
Minimum of Months 0.451470E+09 520.85   0.505780E+10 1948.61  
Maximum of Months 0.536472E+09 520.85   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.497722E+09 520.85 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.451470E+09 520.85 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.536472E+09 520.85 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.479179E+09 520.85 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.517097E+09 520.85 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.514597E+09 520.85 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.481680E+09 520.85 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.536472E+09 520.85 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.479179E+09 520.85 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.497722E+09 520.85 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.491888E+09 520.85 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.481680E+09 520.85 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.596516E+10     0.153881E+12    
Minimum of Months 0.451470E+09 520.85   0.505780E+10 1948.61  
Maximum of Months 0.536472E+09 520.85   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.497722E+09 520.85 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.451470E+09 520.85 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.536472E+09 520.85 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.479179E+09 520.85 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.517097E+09 520.85 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.514597E+09 520.85 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.481680E+09 520.85 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.536472E+09 520.85 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.479179E+09 520.85 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.497722E+09 520.85 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.491888E+09 520.85 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.481680E+09 520.85 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.596516E+10     0.153881E+12    
Minimum of Months 0.451470E+09 520.85   0.505780E+10 1948.61  
Maximum of Months 0.536472E+09 520.85   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.565679E+10 5919.59 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.513113E+10 5919.59 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.609720E+10 5919.59 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.544605E+10 5919.59 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.587700E+10 5919.59 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.584858E+10 5919.59 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.547447E+10 5919.59 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.609720E+10 5919.59 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.544605E+10 5919.59 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.565679E+10 5919.59 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.559049E+10 5919.59 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.547447E+10 5919.59 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.677962E+11     0.749486E+13    
Minimum of Months 0.513113E+10 5919.59   0.246344E+12 94908.13  
Maximum of Months 0.609720E+10 5919.59   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.200626E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.181982E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.216246E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.193152E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.208436E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.207428E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.194159E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.216246E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.193152E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.200626E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.198274E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.194159E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.240449E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.181982E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.216246E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.180176E+11 0.270551E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.163433E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.194204E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.173464E+11 0.261305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.187190E+11 0.275555E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.186285E+11 0.270261E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.174369E+11 0.266527E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.194204E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.173464E+11 0.261160E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.180176E+11 0.270624E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.178064E+11 0.264424E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.174369E+11 0.266454E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.215940E+12 0.321286E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.163433E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.194204E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.180176E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.173464E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.187190E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.186285E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.174369E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.173464E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.180176E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.178064E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.174369E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.215940E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.180176E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.173464E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.187190E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.186285E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.174369E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.173464E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.180176E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.178064E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.174369E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.215940E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.166189E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.517624E+09
February 0.136985E+10 0.146329E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.436767E+09
March 0.163685E+10 0.167280E+10 0.352283E+10 0.00 0.00 0.00 0.00 142435.23 0.457782E+09
April 0.145243E+10 0.145673E+10 0.328108E+10 0.00 0.00 0.00 0.00 26439409.53 0.232958E+09
May 0.157338E+10 0.155716E+10 0.346000E+10 0.00 0.00 0.00 0.00 75207112.42 0.131608E+09
June 0.156900E+10 0.153832E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.117441E+09 39229458.35
July 0.145680E+10 0.144682E+10 0.334664E+10 0.00 0.00 0.00 0.00 98962030.19 26231797.44
August 0.163685E+10 0.162734E+10 0.352283E+10 0.00 0.00 0.00 0.00 78121596.75 37152834.11
September 0.145243E+10 0.147920E+10 0.327926E+10 0.00 0.00 0.00 0.00 25153979.61 64712570.17
October 0.150991E+10 0.158182E+10 0.339809E+10 0.00 0.00 0.00 0.00 9798291.30 0.216732E+09
November 0.149516E+10 0.163038E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.428470E+09
December 0.145680E+10 0.162348E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.461900E+09
                   
Annual Sum or Average 0.181194E+11 0.187392E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.431265E+09 0.305117E+10
Minimum of Months 0.136985E+10 0.144682E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 26231797.44
Maximum of Months 0.163685E+10 0.167280E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.117441E+09 0.517624E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.105983E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.346154E+09
February 0.882782E+09 0.938735E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.290796E+09
March 0.105485E+10 0.107655E+10 0.227025E+10 0.00 0.00 0.00 0.00 98940.03 0.305211E+09
April 0.936002E+09 0.943628E+09 0.211446E+10 0.00 0.00 0.00 0.00 18434710.98 0.149603E+09
May 0.101394E+10 0.101073E+10 0.222976E+10 0.00 0.00 0.00 0.00 50362868.17 88499609.62
June 0.101113E+10 0.999315E+09 0.218692E+10 0.00 0.00 0.00 0.00 81214150.87 23441409.12
July 0.938820E+09 0.940765E+09 0.215670E+10 0.00 0.00 0.00 0.00 70405346.14 14069270.52
August 0.105485E+10 0.105360E+10 0.227025E+10 0.00 0.00 0.00 0.00 56569104.21 19716810.10
September 0.936002E+09 0.951936E+09 0.211328E+10 0.00 0.00 0.00 0.00 16339372.46 43908233.35
October 0.973041E+09 0.101635E+10 0.218986E+10 0.00 0.00 0.00 0.00 6579078.56 0.142871E+09
November 0.963541E+09 0.104498E+10 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.284164E+09
December 0.938820E+09 0.103862E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.302558E+09
                   
Annual Sum or Average 0.116768E+11 0.120750E+11 0.259981E+11 0.00 0.00 0.00 0.00 0.300004E+09 0.201099E+10
Minimum of Months 0.882782E+09 0.938735E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 14069270.52
Maximum of Months 0.105485E+10 0.107655E+10 0.227025E+10 0.00 0.00 0.00 0.00 81214150.87 0.346154E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.160156E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.540935E+09
February 0.136988E+10 0.142970E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.456905E+09
March 0.163688E+10 0.165904E+10 0.352288E+10 0.00 0.00 0.00 0.00 140171.63 0.479275E+09
April 0.145246E+10 0.146238E+10 0.328113E+10 0.00 0.00 0.00 0.00 22560720.65 0.237969E+09
May 0.157341E+10 0.156760E+10 0.346006E+10 0.00 0.00 0.00 0.00 74832383.95 0.130660E+09
June 0.156904E+10 0.155036E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.119863E+09 37781623.95
July 0.145684E+10 0.145963E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.100497E+09 24970485.94
August 0.163688E+10 0.163347E+10 0.352288E+10 0.00 0.00 0.00 0.00 76241390.46 37500972.45
September 0.145246E+10 0.147350E+10 0.327931E+10 0.00 0.00 0.00 0.00 21741177.11 71237962.38
October 0.150994E+10 0.155976E+10 0.339814E+10 0.00 0.00 0.00 0.00 7187369.64 0.234864E+09
November 0.149520E+10 0.157662E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.452787E+09
December 0.145684E+10 0.156971E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.477560E+09
                   
Annual Sum or Average 0.181198E+11 0.185433E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.423063E+09 0.318245E+10
Minimum of Months 0.136988E+10 0.142970E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 24970485.94
Maximum of Months 0.163688E+10 0.165904E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.119863E+09 0.540935E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.104330E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.367302E+09
February 0.882782E+09 0.929175E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.319928E+09
March 0.105485E+10 0.107292E+10 0.227023E+10 0.00 0.00 0.00 0.00 93841.80 0.350378E+09
April 0.936002E+09 0.940578E+09 0.211444E+10 0.00 0.00 0.00 0.00 12732718.36 0.187328E+09
May 0.101394E+10 0.100528E+10 0.222974E+10 0.00 0.00 0.00 0.00 45012780.55 0.102396E+09
June 0.101113E+10 0.993176E+09 0.218691E+10 0.00 0.00 0.00 0.00 72448328.34 32811789.97
July 0.938820E+09 0.934598E+09 0.215669E+10 0.00 0.00 0.00 0.00 58944818.79 24459993.62
August 0.105485E+10 0.105110E+10 0.227023E+10 0.00 0.00 0.00 0.00 43424465.17 36235573.95
September 0.936002E+09 0.953619E+09 0.211327E+10 0.00 0.00 0.00 0.00 15269093.40 51020832.97
October 0.973041E+09 0.101036E+10 0.218984E+10 0.00 0.00 0.00 0.00 5175974.83 0.167023E+09
November 0.963541E+09 0.102435E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.323082E+09
December 0.938820E+09 0.102401E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.346657E+09
                   
Annual Sum or Average 0.116768E+11 0.119825E+11 0.259979E+11 0.00 0.00 0.00 0.00 0.253102E+09 0.230862E+10
Minimum of Months 0.882782E+09 0.929175E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 24459993.62
Maximum of Months 0.105485E+10 0.107292E+10 0.227023E+10 0.00 0.00 0.00 0.00 72448328.34 0.367302E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.166503E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.105592E+10
February 0.136985E+10 0.146574E+10 0.307485E+10 0.00 0.00 0.00 0.00 1113003.74 0.895747E+09
March 0.163685E+10 0.167432E+10 0.352283E+10 0.00 0.00 0.00 0.00 1059803.44 0.939388E+09
April 0.145243E+10 0.145718E+10 0.328108E+10 0.00 0.00 0.00 0.00 65168957.71 0.519383E+09
May 0.157338E+10 0.155742E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.170723E+09 0.300830E+09
June 0.156900E+10 0.153866E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.259679E+09 0.109439E+09
July 0.145680E+10 0.144730E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.219175E+09 83138799.59
August 0.163685E+10 0.162777E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.178442E+09 0.108586E+09
September 0.145243E+10 0.148081E+10 0.327926E+10 0.00 0.00 0.00 0.00 60454199.03 0.148514E+09
October 0.150991E+10 0.158333E+10 0.339809E+10 0.00 0.00 0.00 0.00 27015766.92 0.454145E+09
November 0.149516E+10 0.163373E+10 0.332024E+10 0.00 0.00 0.00 0.00 861.55 0.858114E+09
December 0.145680E+10 0.162607E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.923277E+09
                   
Annual Sum or Average 0.181194E+11 0.187574E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.982832E+09 0.639648E+10
Minimum of Months 0.136985E+10 0.144730E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 83138799.59
Maximum of Months 0.163685E+10 0.167432E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.259679E+09 0.105592E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.106027E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.722687E+09
February 0.649041E+09 0.939142E+09 0.198155E+10 0.00 0.00 0.00 0.00 27067.42 0.618746E+09
March 0.773965E+09 0.107668E+10 0.227025E+10 0.00 0.00 0.00 0.00 210822.73 0.667765E+09
April 0.688021E+09 0.943844E+09 0.211446E+10 0.00 0.00 0.00 0.00 38173091.16 0.370611E+09
May 0.744847E+09 0.101093E+10 0.222976E+10 0.00 0.00 0.00 0.00 0.110274E+09 0.212223E+09
June 0.742030E+09 0.999544E+09 0.218692E+10 0.00 0.00 0.00 0.00 0.172961E+09 74853985.82
July 0.690839E+09 0.940969E+09 0.215670E+10 0.00 0.00 0.00 0.00 0.145946E+09 57240211.75
August 0.773965E+09 0.105388E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.115659E+09 75694267.42
September 0.688021E+09 0.952268E+09 0.211328E+10 0.00 0.00 0.00 0.00 37038777.08 0.107622E+09
October 0.715730E+09 0.101670E+10 0.218986E+10 0.00 0.00 0.00 0.00 15678215.22 0.316582E+09
November 0.708685E+09 0.104534E+10 0.213969E+10 0.00 0.00 0.00 0.00 6595.78 0.599202E+09
December 0.690839E+09 0.103916E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.633020E+09
                   
Annual Sum or Average 0.858171E+10 0.120787E+11 0.259981E+11 0.00 0.00 0.00 0.00 0.635975E+09 0.445625E+10
Minimum of Months 0.649041E+09 0.939142E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 57240211.75
Maximum of Months 0.773965E+09 0.107668E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.172961E+09 0.722687E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.160392E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.121212E+10
February 0.136988E+10 0.143048E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.102360E+10
March 0.163688E+10 0.165980E+10 0.352288E+10 0.00 0.00 0.00 0.00 260231.07 0.107421E+10
April 0.145246E+10 0.146317E+10 0.328113E+10 0.00 0.00 0.00 0.00 50304469.94 0.561426E+09
May 0.157341E+10 0.156820E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.167707E+09 0.304157E+09
June 0.156904E+10 0.155103E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.265114E+09 0.106543E+09
July 0.145684E+10 0.146072E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.221987E+09 81480863.41
August 0.163688E+10 0.163444E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.169769E+09 0.115290E+09
September 0.145246E+10 0.147398E+10 0.327931E+10 0.00 0.00 0.00 0.00 48930093.97 0.172164E+09
October 0.150994E+10 0.155739E+10 0.339814E+10 0.00 0.00 0.00 0.00 15683351.23 0.538563E+09
November 0.149520E+10 0.157830E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.101160E+10
December 0.145684E+10 0.157827E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.105903E+10
                   
Annual Sum or Average 0.181198E+11 0.185597E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.939755E+09 0.726020E+10
Minimum of Months 0.136988E+10 0.143048E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 81480863.41
Maximum of Months 0.163688E+10 0.165980E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.265114E+09 0.121212E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.104375E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.745806E+09
February 0.882782E+09 0.929509E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.637564E+09
March 0.105485E+10 0.107337E+10 0.227023E+10 0.00 0.00 0.00 0.00 218492.96 0.692039E+09
April 0.936002E+09 0.940833E+09 0.211444E+10 0.00 0.00 0.00 0.00 32313875.99 0.392125E+09
May 0.101394E+10 0.100546E+10 0.222974E+10 0.00 0.00 0.00 0.00 0.101553E+09 0.226594E+09
June 0.101113E+10 0.993435E+09 0.218691E+10 0.00 0.00 0.00 0.00 0.164799E+09 85241051.11
July 0.938820E+09 0.934989E+09 0.215669E+10 0.00 0.00 0.00 0.00 0.137557E+09 67665100.59
August 0.105485E+10 0.105149E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.108325E+09 85670137.02
September 0.936002E+09 0.953994E+09 0.211327E+10 0.00 0.00 0.00 0.00 36127740.24 0.114851E+09
October 0.973041E+09 0.101080E+10 0.218984E+10 0.00 0.00 0.00 0.00 13150782.63 0.338224E+09
November 0.963541E+09 0.102500E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.621265E+09
December 0.938820E+09 0.102437E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.655070E+09
                   
Annual Sum or Average 0.116768E+11 0.119870E+11 0.259979E+11 0.00 0.00 0.00 0.00 0.594047E+09 0.466211E+10
Minimum of Months 0.882782E+09 0.929509E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 67665100.59
Maximum of Months 0.105485E+10 0.107337E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.164799E+09 0.745806E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.166510E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.116640E+10
February 0.136985E+10 0.146577E+10 0.307485E+10 0.00 0.00 0.00 0.00 3272919.24 0.100913E+10
March 0.163685E+10 0.167434E+10 0.352283E+10 0.00 0.00 0.00 0.00 1714123.89 0.105941E+10
April 0.145243E+10 0.145718E+10 0.328108E+10 0.00 0.00 0.00 0.00 78571440.60 0.610351E+09
May 0.157338E+10 0.155743E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.204542E+09 0.365169E+09
June 0.156900E+10 0.153866E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.312643E+09 0.137221E+09
July 0.145680E+10 0.144733E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.260103E+09 0.105970E+09
August 0.163685E+10 0.162777E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.213180E+09 0.135106E+09
September 0.145243E+10 0.148084E+10 0.327926E+10 0.00 0.00 0.00 0.00 71618028.50 0.182083E+09
October 0.150991E+10 0.158347E+10 0.339809E+10 0.00 0.00 0.00 0.00 35009033.10 0.521037E+09
November 0.149516E+10 0.163386E+10 0.332024E+10 0.00 0.00 0.00 0.00 74180.52 0.941990E+09
December 0.145680E+10 0.162612E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.102199E+10
                   
Annual Sum or Average 0.181194E+11 0.187579E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.118073E+10 0.725587E+10
Minimum of Months 0.136985E+10 0.144733E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.105970E+09
Maximum of Months 0.163685E+10 0.167434E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.312643E+09 0.116640E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.106030E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.803763E+09
February 0.882782E+09 0.939151E+09 0.198155E+10 0.00 0.00 0.00 0.00 252565.85 0.704704E+09
March 0.105485E+10 0.107671E+10 0.227025E+10 0.00 0.00 0.00 0.00 213328.08 0.773275E+09
April 0.936002E+09 0.943853E+09 0.211446E+10 0.00 0.00 0.00 0.00 43755281.10 0.449566E+09
May 0.101394E+10 0.101094E+10 0.222976E+10 0.00 0.00 0.00 0.00 0.128591E+09 0.264379E+09
June 0.101113E+10 0.999553E+09 0.218692E+10 0.00 0.00 0.00 0.00 0.205992E+09 95161933.68
July 0.938820E+09 0.940975E+09 0.215670E+10 0.00 0.00 0.00 0.00 0.171099E+09 74211566.11
August 0.105485E+10 0.105388E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.136558E+09 96195222.04
September 0.936002E+09 0.952289E+09 0.211328E+10 0.00 0.00 0.00 0.00 42796651.75 0.135572E+09
October 0.973041E+09 0.101672E+10 0.218986E+10 0.00 0.00 0.00 0.00 18747549.18 0.375781E+09
November 0.963541E+09 0.104543E+10 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.670159E+09
December 0.938820E+09 0.103924E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.703835E+09
                   
Annual Sum or Average 0.116768E+11 0.120790E+11 0.259981E+11 0.00 0.00 0.00 0.00 0.748005E+09 0.514660E+10
Minimum of Months 0.882782E+09 0.939151E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 74211566.11
Maximum of Months 0.105485E+10 0.107671E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.205992E+09 0.803763E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.160394E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.136143E+10
February 0.136988E+10 0.143048E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.117287E+10
March 0.163688E+10 0.165980E+10 0.352288E+10 0.00 0.00 0.00 0.00 247170.75 0.124344E+10
April 0.145246E+10 0.146318E+10 0.328113E+10 0.00 0.00 0.00 0.00 59597510.29 0.670874E+09
May 0.157341E+10 0.156821E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.200558E+09 0.370533E+09
June 0.156904E+10 0.155104E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.318976E+09 0.133282E+09
July 0.145684E+10 0.146072E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.263268E+09 0.103864E+09
August 0.163688E+10 0.163444E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.203396E+09 0.144641E+09
September 0.145246E+10 0.147400E+10 0.327931E+10 0.00 0.00 0.00 0.00 58359083.51 0.214252E+09
October 0.150994E+10 0.155739E+10 0.339814E+10 0.00 0.00 0.00 0.00 18884261.30 0.640382E+09
November 0.149520E+10 0.157831E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.114667E+10
December 0.145684E+10 0.157829E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.118589E+10
                   
Annual Sum or Average 0.181198E+11 0.185598E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.112329E+10 0.838814E+10
Minimum of Months 0.136988E+10 0.143048E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.103864E+09
Maximum of Months 0.163688E+10 0.165980E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.318976E+09 0.136143E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.104378E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.848187E+09
February 0.882782E+09 0.929579E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.736688E+09
March 0.105485E+10 0.107339E+10 0.227023E+10 0.00 0.00 0.00 0.00 289482.62 0.807768E+09
April 0.936002E+09 0.940840E+09 0.211444E+10 0.00 0.00 0.00 0.00 38754433.85 0.471948E+09
May 0.101394E+10 0.100547E+10 0.222974E+10 0.00 0.00 0.00 0.00 0.123105E+09 0.278732E+09
June 0.101113E+10 0.993445E+09 0.218691E+10 0.00 0.00 0.00 0.00 0.200700E+09 0.106166E+09
July 0.938820E+09 0.935033E+09 0.215669E+10 0.00 0.00 0.00 0.00 0.165949E+09 84902203.94
August 0.105485E+10 0.105149E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.131319E+09 0.106916E+09
September 0.936002E+09 0.954040E+09 0.211327E+10 0.00 0.00 0.00 0.00 43387952.81 0.142978E+09
October 0.973041E+09 0.101081E+10 0.218984E+10 0.00 0.00 0.00 0.00 16383235.27 0.402394E+09
November 0.963541E+09 0.102506E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.705919E+09
December 0.938820E+09 0.102439E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.743453E+09
                   
Annual Sum or Average 0.116768E+11 0.119873E+11 0.259979E+11 0.00 0.00 0.00 0.00 0.719888E+09 0.543605E+10
Minimum of Months 0.882782E+09 0.929579E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 84902203.94
Maximum of Months 0.105485E+10 0.107339E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.200700E+09 0.848187E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.497722E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.451470E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.536472E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.479179E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.517097E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.514597E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.481680E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.536472E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.479179E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.497722E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.491888E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.481680E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.596516E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.451470E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.536472E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.497722E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.451470E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.536472E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.479179E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.517097E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.514597E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.481680E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.536472E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.479179E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.497722E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.491888E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.481680E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.596516E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.451470E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.536472E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.497722E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.451470E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.536472E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.479179E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.517097E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.514597E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.481680E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.536472E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.479179E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.497722E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.491888E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.481680E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.596516E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.451470E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.536472E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.565679E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.513113E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.609720E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.544605E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.587700E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.584858E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.547447E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.609720E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.544605E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.565679E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.559049E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.547447E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.677962E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.513113E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.609720E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.113885E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.960388E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58135.24 0.100572E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40498639.94 0.525539E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.131108E+09 0.286302E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.211848E+09 93475684.36
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.177920E+09 67333752.59
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.136976E+09 97459433.56
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40970388.19 0.144400E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14624840.76 0.479761E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.943651E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.101130E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.754004E+09 0.675418E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67333752.59
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.211848E+09 0.113885E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.193220E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.163778E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 173467.13 0.171420E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78803431.69 0.919207E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.237767E+09 0.507390E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.376621E+09 0.174027E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.319929E+09 0.126622E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.251874E+09 0.179874E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76065070.60 0.256231E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29032101.33 0.822920E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.160046E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.169202E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.137027E+10 0.115629E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.126622E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.376621E+09 0.193220E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.189885E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.165613E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.179844E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 60129303.58 0.996855E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.216944E+09 0.550587E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.383624E+09 0.202739E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.308378E+09 0.155813E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.248205E+09 0.207749E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 63821633.47 0.291122E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26934221.25 0.876503E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.157730E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.163887E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.130804E+10 0.118510E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.155813E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.383624E+09 0.189885E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 20994.62 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 20994.62 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 20994.62 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 20994.62 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 20994.62 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 20994.62 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 20994.62 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 20994.62 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 20994.62 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 20994.62 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 20994.62 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 20994.62 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   20994.62   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   20994.62   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18854.65 02-JAN-08:09 18128.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18854.65 01-FEB-08:09 18128.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18854.65 01-MAR-08:09 18128.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18854.65 03-APR-07:10 18128.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18854.65 01-MAY-07:10 18128.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18854.65 01-JUN-07:10 18128.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18854.65 03-JUL-07:10 18128.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18854.65 01-AUG-07:10 18128.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18854.65 01-SEP-07:10 18128.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18854.65 02-OCT-07:10 18128.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18854.65 01-NOV-07:10 18128.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18854.65 01-DEC-08:09 18128.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18854.65   18128.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18854.65   18128.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18854.65 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18854.65 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18854.65 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18854.65 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18854.65 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18854.65 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18854.65 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18854.65 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18854.65 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18854.65 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18854.65 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18854.65 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18854.65 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18854.65 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18854.65 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18854.65 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18854.65 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18854.65 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18854.65 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18854.65 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18854.65 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18854.65 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18854.65 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18854.65 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2255.83 17-JAN-16:00 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1388.07 25-JAN-23:00
February 2010.79 01-FEB-10:09 2097.14 01-FEB-16:00 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1727.47 09-FEB-01:00
March 2010.79 01-MAR-10:09 2016.00 10-MAR-16:00 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 12.51 22-MAR-13:00 1385.55 19-MAR-24:00
April 2010.79 03-APR-09:09 1675.34 20-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 240.23 01-APR-17:20 1417.84 10-APR-24:00
May 2010.79 01-MAY-09:09 1454.29 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 463.50 14-MAY-16:00 673.90 04-MAY-02:00
June 2010.79 01-JUN-09:09 1454.29 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 437.60 04-JUN-19:00 474.56 28-JUN-02:00
July 2010.79 03-JUL-09:09 1624.53 07-JUL-07:30 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 515.83 02-JUL-21:00 240.54 18-JUL-21:10
August 2010.79 01-AUG-09:09 1610.17 17-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 325.54 26-AUG-18:00 390.49 14-AUG-01:00
September 2010.79 01-SEP-09:09 1786.67 29-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 193.87 10-SEP-15:00 247.76 24-SEP-07:00
October 2010.79 02-OCT-09:09 2122.31 13-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 267.78 01-OCT-15:00 644.25 24-OCT-02:00
November 2010.79 01-NOV-09:09 2367.39 22-NOV-16:00 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 883.33 26-NOV-09:00
December 2010.79 01-DEC-10:09 2367.39 01-DEC-16:00 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1181.95 18-DEC-05:20
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1454.29   2276.32   0.00 0.00 0.00 0.00 0.00   240.54  
Maximum of Months 2010.79   2367.39   2276.32   0.00 0.00 0.00 0.00 515.83   1727.47  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1455.49 17-JAN-16:00 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 908.69 25-JAN-23:00
February 1295.83 01-FEB-10:09 1360.39 13-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1141.21 09-FEB-01:00
March 1295.83 01-MAR-10:09 1314.41 10-MAR-16:00 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 8.34 22-MAR-13:00 934.32 19-MAR-24:00
April 1295.83 03-APR-09:09 937.20 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 169.42 01-APR-17:20 926.02 10-APR-24:00
May 1295.83 01-MAY-09:09 937.20 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 326.96 14-MAY-15:50 436.35 04-MAY-02:00
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 304.54 04-JUN-19:00 307.02 28-JUN-02:00
July 1295.83 03-JUL-09:09 937.20 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 385.30 02-JUL-21:00 151.68 18-JUL-21:10
August 1295.83 01-AUG-09:09 937.20 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 238.24 26-AUG-17:50 240.93 14-AUG-01:00
September 1295.83 01-SEP-09:09 1062.85 29-SEP-15:00 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 136.35 10-SEP-15:00 183.15 24-SEP-10:15
October 1295.83 02-OCT-09:09 1352.21 13-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 175.10 01-OCT-14:53 426.88 24-OCT-02:00
November 1295.83 01-NOV-09:09 1525.64 22-NOV-16:00 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 645.17 26-NOV-09:00
December 1295.83 01-DEC-10:09 1525.64 01-DEC-16:00 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 772.24 18-DEC-05:20
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.95   0.00 0.00 0.00 0.00 0.00   151.68  
Maximum of Months 1295.83   1525.64   1466.95   0.00 0.00 0.00 0.00 385.30   1141.21  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2248.44 17-JAN-16:00 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1378.40 25-JAN-23:00
February 2010.83 01-FEB-10:09 2002.11 23-FEB-16:00 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1743.94 09-FEB-01:00
March 2010.83 01-MAR-10:09 1999.35 10-MAR-16:00 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 12.47 22-MAR-13:00 1429.46 19-MAR-24:00
April 2010.83 03-APR-09:09 1674.10 20-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 220.03 01-APR-17:20 1413.47 10-APR-24:00
May 2010.83 01-MAY-09:09 1454.32 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 461.87 14-MAY-15:50 666.75 04-MAY-02:00
June 2010.83 01-JUN-09:09 1454.32 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 442.77 04-JUN-19:00 470.58 28-JUN-02:00
July 2010.83 03-JUL-09:09 1661.54 07-JUL-07:30 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 527.29 02-JUL-21:00 242.09 18-JUL-21:10
August 2010.83 01-AUG-09:09 1640.67 17-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 319.97 26-AUG-18:00 400.60 14-AUG-01:00
September 2010.83 01-SEP-09:09 1630.08 18-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 172.82 10-SEP-17:00 258.24 24-SEP-10:55
October 2010.83 02-OCT-09:09 2112.65 13-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 209.68 01-OCT-14:57 667.07 24-OCT-02:00
November 2010.83 01-NOV-09:09 2367.44 22-NOV-16:00 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 952.15 26-NOV-09:00
December 2010.83 01-DEC-10:09 2367.44 01-DEC-16:00 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1182.64 18-DEC-05:20
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1454.32   2276.35   0.00 0.00 0.00 0.00 0.00   242.09  
Maximum of Months 2010.83   2367.44   2276.35   0.00 0.00 0.00 0.00 527.29   1743.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1446.33 17-JAN-16:00 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 966.43 25-JAN-24:00
February 1295.83 01-FEB-10:09 1304.86 03-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1230.57 09-FEB-01:00
March 1295.83 01-MAR-10:09 1265.09 27-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 8.34 22-MAR-13:00 1063.21 19-MAR-24:00
April 1295.83 03-APR-09:09 1147.23 20-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 122.06 21-APR-15:00 1061.47 10-APR-24:00
May 1295.83 01-MAY-09:09 937.20 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 274.03 14-MAY-15:44 518.41 04-MAY-02:00
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 285.07 04-JUN-18:53 372.14 28-JUN-02:00
July 1295.83 03-JUL-09:09 1133.98 07-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 353.96 02-JUL-21:00 207.57 04-JUL-19:20
August 1295.83 01-AUG-09:09 1162.34 24-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 193.41 26-AUG-17:47 331.14 14-AUG-01:00
September 1295.83 01-SEP-09:09 1178.96 18-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 118.19 10-SEP-14:55 180.52 24-SEP-07:00
October 1295.83 02-OCT-09:09 1372.94 13-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 139.98 01-OCT-14:52 480.92 24-OCT-02:00
November 1295.83 01-NOV-09:09 1525.64 22-NOV-16:00 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 660.07 26-NOV-14:00
December 1295.83 01-DEC-10:09 1525.64 01-DEC-16:00 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 876.83 18-DEC-05:20
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.94   0.00 0.00 0.00 0.00 0.00   180.52  
Maximum of Months 1295.83   1525.64   1466.94   0.00 0.00 0.00 0.00 353.96   1230.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2259.11 17-JAN-16:00 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2835.02 25-JAN-23:00
February 2010.79 01-FEB-10:09 2104.30 01-FEB-16:00 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 125.66 20-FEB-16:00 3572.01 09-FEB-01:00
March 2010.79 01-MAR-10:09 2026.28 10-MAR-16:00 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 143.15 19-MAR-14:20 2640.03 19-MAR-24:00
April 2010.79 03-APR-09:09 1695.22 20-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 667.02 01-APR-17:02 2927.19 10-APR-24:00
May 2010.79 01-MAY-09:09 1454.29 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 1043.77 14-MAY-16:00 1373.06 04-MAY-02:00
June 2010.79 01-JUN-09:09 1454.29 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 1015.46 04-JUN-19:00 1112.59 28-JUN-01:55
July 2010.79 03-JUL-09:09 1645.63 07-JUL-07:30 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 1152.45 02-JUL-21:00 536.73 18-JUL-21:10
August 2010.79 01-AUG-09:09 1631.70 17-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 782.83 26-AUG-17:01 863.85 14-AUG-00:52
September 2010.79 01-SEP-09:09 1797.62 29-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 468.28 10-SEP-15:10 530.40 24-SEP-07:00
October 2010.79 02-OCT-09:09 2129.46 13-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 667.41 01-OCT-14:52 1344.81 24-OCT-02:00
November 2010.79 01-NOV-09:09 2367.39 22-NOV-16:00 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 1.04 03-NOV-16:00 1692.99 26-NOV-09:00
December 2010.79 01-DEC-10:09 2367.39 01-DEC-16:00 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2454.43 18-DEC-05:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1454.29   2276.32   0.00 0.00 0.00 0.00 0.00   530.40  
Maximum of Months 2010.79   2367.39   2276.32   0.00 0.00 0.00 0.00 1152.45   3572.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1456.02 17-JAN-16:00 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1883.97 25-JAN-23:00
February 1239.33 01-FEB-08:09 1361.68 13-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 29.92 20-FEB-16:00 2399.29 09-FEB-01:00
March 1239.33 01-MAR-08:09 1315.97 10-MAR-16:00 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 17.43 22-MAR-13:00 1894.71 19-MAR-24:00
April 1239.33 03-APR-07:10 937.20 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 403.65 01-APR-17:02 1970.54 10-APR-24:00
May 1239.33 01-MAY-07:10 937.20 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 718.74 14-MAY-15:50 906.99 04-MAY-02:00
June 1239.33 01-JUN-07:10 937.20 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 718.32 04-JUN-19:00 753.63 28-JUN-01:55
July 1239.33 03-JUL-07:10 937.20 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 833.12 02-JUL-21:00 346.81 18-JUL-21:10
August 1239.33 01-AUG-07:10 1026.01 16-AUG-15:00 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 537.48 26-AUG-17:50 595.94 14-AUG-00:52
September 1239.33 01-SEP-07:10 1062.56 29-SEP-15:00 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 323.11 10-SEP-15:10 433.88 24-SEP-10:28
October 1239.33 02-OCT-07:10 1353.91 13-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 400.46 01-OCT-15:10 912.14 24-OCT-02:00
November 1239.33 01-NOV-07:10 1525.64 22-NOV-16:00 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 2.07 08-NOV-15:00 1290.04 26-NOV-09:00
December 1239.33 01-DEC-08:09 1525.64 01-DEC-16:00 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1636.32 18-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   937.20   1466.95   0.00 0.00 0.00 0.00 0.00   346.81  
Maximum of Months 1239.33   1525.64   1466.95   0.00 0.00 0.00 0.00 833.12   2399.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2252.09 17-JAN-16:00 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2916.23 25-JAN-23:00
February 2010.83 01-FEB-10:09 2013.34 23-FEB-16:00 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3740.17 09-FEB-01:00
March 2010.83 01-MAR-10:09 2010.32 10-MAR-16:00 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 26.10 22-MAR-13:00 2997.72 19-MAR-24:00
April 2010.83 03-APR-09:09 1693.98 20-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 525.39 01-APR-17:02 2992.79 10-APR-24:00
May 2010.83 01-MAY-09:09 1454.32 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 1028.62 14-MAY-15:50 1389.53 04-MAY-02:00
June 2010.83 01-JUN-09:09 1454.32 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 1047.67 04-JUN-19:00 1102.63 28-JUN-01:55
July 2010.83 03-JUL-09:09 1681.40 07-JUL-07:30 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 1192.02 02-JUL-21:00 540.29 18-JUL-21:10
August 2010.83 01-AUG-09:09 1661.07 17-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 757.15 26-AUG-18:00 913.38 14-AUG-00:52
September 2010.83 01-SEP-09:09 1639.29 18-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 374.50 10-SEP-15:08 601.02 24-SEP-10:28
October 2010.83 02-OCT-09:09 2120.20 13-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 446.55 01-OCT-15:10 1467.04 23-OCT-21:10
November 2010.83 01-NOV-09:09 2367.44 22-NOV-16:00 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2022.23 26-NOV-09:00
December 2010.83 01-DEC-10:09 2367.44 01-DEC-16:00 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2550.09 18-DEC-04:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1454.32   2276.35   0.00 0.00 0.00 0.00 0.00   540.29  
Maximum of Months 2010.83   2367.44   2276.35   0.00 0.00 0.00 0.00 1192.02   3740.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1447.13 17-JAN-16:00 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1907.69 25-JAN-23:00
February 1295.83 01-FEB-10:09 1306.31 03-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2439.78 09-FEB-01:00
March 1295.83 01-MAR-10:09 1267.57 27-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 19.39 22-MAR-12:00 1948.14 19-MAR-24:00
April 1295.83 03-APR-09:09 1149.99 20-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 302.95 29-APR-17:02 2010.78 10-APR-24:00
May 1295.83 01-MAY-09:09 937.20 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 630.65 14-MAY-15:44 970.93 04-MAY-02:00
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 669.18 04-JUN-19:00 820.57 28-JUN-01:55
July 1295.83 03-JUL-09:09 1136.36 07-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 806.16 02-JUL-21:00 396.79 04-JUL-19:20
August 1295.83 01-AUG-09:09 1164.51 24-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 497.88 27-AUG-12:52 665.15 14-AUG-00:52
September 1295.83 01-SEP-09:09 1181.19 18-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 276.45 10-SEP-11:55 364.36 25-SEP-03:00
October 1295.83 02-OCT-09:09 1374.07 13-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 319.66 01-OCT-15:06 957.42 24-OCT-02:00
November 1295.83 01-NOV-09:09 1525.64 22-NOV-16:00 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1202.42 26-NOV-09:00
December 1295.83 01-DEC-10:09 1525.64 01-DEC-16:00 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1636.31 18-DEC-05:57
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.94   0.00 0.00 0.00 0.00 0.00   364.36  
Maximum of Months 1295.83   1525.64   1466.94   0.00 0.00 0.00 0.00 806.16   2439.78  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2258.99 17-JAN-16:00 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3303.32 25-JAN-22:03
February 2010.79 01-FEB-10:09 2104.55 01-FEB-16:00 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 214.36 20-FEB-15:50 4055.14 09-FEB-01:00
March 2010.79 01-MAR-10:09 2025.94 10-MAR-16:00 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 106.21 26-MAR-16:50 2855.86 01-MAR-22:03
April 2010.79 03-APR-09:09 1694.66 20-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 851.90 01-APR-17:02 3358.17 10-APR-24:00
May 2010.79 01-MAY-09:09 1454.29 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 1248.68 14-MAY-16:00 1575.76 04-MAY-02:00
June 2010.79 01-JUN-09:09 1454.29 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 1178.25 04-JUN-19:00 1377.07 28-JUN-01:55
July 2010.79 03-JUL-09:09 1644.96 07-JUL-07:30 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 1383.98 02-JUL-21:00 679.23 18-JUL-21:10
August 2010.79 01-AUG-09:09 1631.13 17-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 937.69 26-AUG-17:01 1127.17 14-AUG-00:52
September 2010.79 01-SEP-09:09 1798.11 29-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 551.39 10-SEP-15:10 624.11 23-SEP-17:10
October 2010.79 02-OCT-09:09 2129.20 13-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 819.24 01-OCT-14:52 1560.71 23-OCT-21:10
November 2010.79 01-NOV-09:09 2367.39 22-NOV-16:00 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 25.58 23-NOV-15:10 1840.44 28-NOV-05:10
December 2010.79 01-DEC-10:09 2367.39 01-DEC-16:00 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3060.15 18-DEC-05:47
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1454.29   2276.32   0.00 0.00 0.00 0.00 0.00   624.11  
Maximum of Months 2010.79   2367.39   2276.32   0.00 0.00 0.00 0.00 1383.98   4055.14  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1455.95 17-JAN-16:00 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2201.73 25-JAN-22:03
February 1295.83 01-FEB-10:09 1361.58 13-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 53.73 20-FEB-15:30 2739.47 09-FEB-01:00
March 1295.83 01-MAR-10:09 1315.76 10-MAR-16:00 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 19.01 22-MAR-13:00 2084.35 19-MAR-24:00
April 1295.83 03-APR-09:09 937.20 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 483.88 01-APR-17:02 2276.76 10-APR-24:00
May 1295.83 01-MAY-09:09 937.20 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 840.40 14-MAY-16:00 1047.47 04-MAY-02:00
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 818.29 04-JUN-19:00 932.62 28-JUN-01:55
July 1295.83 03-JUL-09:09 937.20 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 964.12 02-JUL-21:00 470.65 04-JUL-19:50
August 1295.83 01-AUG-09:09 1025.51 16-AUG-15:00 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 627.68 26-AUG-17:50 778.98 14-AUG-00:52
September 1295.83 01-SEP-09:09 1063.02 29-SEP-15:00 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 365.15 10-SEP-15:10 506.96 24-SEP-10:30
October 1295.83 02-OCT-09:09 1353.77 13-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 477.85 01-OCT-15:10 1072.56 23-OCT-21:10
November 1295.83 01-NOV-09:09 1525.64 22-NOV-16:00 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1319.34 26-NOV-09:00
December 1295.83 01-DEC-10:09 1525.64 01-DEC-16:00 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2040.23 18-DEC-05:43
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.95   0.00 0.00 0.00 0.00 0.00   470.65  
Maximum of Months 1295.83   1525.64   1466.95   0.00 0.00 0.00 0.00 964.12   2739.47  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2251.98 17-JAN-16:00 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3315.50 25-JAN-23:00
February 2010.83 01-FEB-10:09 2013.04 23-FEB-16:00 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 4263.25 09-FEB-01:00
March 2010.83 01-MAR-10:09 2009.99 10-MAR-16:00 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 28.52 22-MAR-13:00 3317.84 19-MAR-24:00
April 2010.83 03-APR-09:09 1693.41 20-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 652.17 01-APR-17:02 3448.96 10-APR-24:00
May 2010.83 01-MAY-09:09 1454.32 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 1239.99 14-MAY-16:00 1596.75 04-MAY-02:00
June 2010.83 01-JUN-09:09 1454.32 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 1197.43 04-JUN-19:00 1363.03 28-JUN-01:55
July 2010.83 03-JUL-09:09 1680.73 07-JUL-07:30 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 1402.73 02-JUL-21:00 684.44 18-JUL-21:10
August 2010.83 01-AUG-09:09 1660.49 17-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 901.15 26-AUG-17:01 1186.02 14-AUG-00:52
September 2010.83 01-SEP-09:09 1639.79 18-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 461.68 10-SEP-15:08 717.45 24-SEP-10:50
October 2010.83 02-OCT-09:09 2119.94 13-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 544.02 01-OCT-15:10 1765.60 23-OCT-21:10
November 2010.83 01-NOV-09:09 2367.44 22-NOV-16:00 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2099.80 26-NOV-09:00
December 2010.83 01-DEC-10:09 2367.44 01-DEC-16:00 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3060.18 18-DEC-05:43
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1454.32   2276.35   0.00 0.00 0.00 0.00 0.00   684.44  
Maximum of Months 2010.83   2367.44   2276.35   0.00 0.00 0.00 0.00 1402.73   4263.25  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1447.06 17-JAN-16:00 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2205.97 25-JAN-22:03
February 1295.83 01-FEB-10:09 1306.56 03-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2795.85 09-FEB-01:00
March 1295.83 01-MAR-10:09 1267.54 27-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 33.43 22-MAR-12:00 2187.01 19-MAR-24:00
April 1295.83 03-APR-09:09 1149.64 20-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 358.61 29-APR-17:02 2322.71 10-APR-24:00
May 1295.83 01-MAY-09:09 937.20 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 754.58 14-MAY-15:54 1124.07 04-MAY-02:00
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 817.14 04-JUN-19:00 1017.59 28-JUN-01:55
July 1295.83 03-JUL-09:09 1136.13 07-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 974.51 02-JUL-21:00 538.18 04-JUL-19:20
August 1295.83 01-AUG-09:09 1164.32 24-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 588.77 27-AUG-12:52 848.80 14-AUG-00:52
September 1295.83 01-SEP-09:09 1181.58 18-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 334.55 10-SEP-11:55 467.00 04-SEP-20:00
October 1295.83 02-OCT-09:09 1373.91 13-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 393.76 01-OCT-15:06 1136.37 23-OCT-21:10
November 1295.83 01-NOV-09:09 1525.64 22-NOV-16:00 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1270.36 04-NOV-03:55
December 1295.83 01-DEC-10:09 1525.64 01-DEC-16:00 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2040.11 18-DEC-05:43
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.94   0.00 0.00 0.00 0.00 0.00   467.00  
Maximum of Months 1295.83   1525.64   1466.94   0.00 0.00 0.00 0.00 974.51   2795.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 520.85 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 520.85 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 520.85 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 520.85 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 520.85 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 520.85 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 520.85 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 520.85 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 520.85 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 520.85 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 520.85 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 520.85 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   520.85   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   520.85   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 520.85 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 520.85 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 520.85 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 520.85 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 520.85 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 520.85 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 520.85 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 520.85 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 520.85 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 520.85 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 520.85 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 520.85 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   520.85   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   520.85   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 520.85 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 520.85 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 520.85 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 520.85 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 520.85 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 520.85 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 520.85 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 520.85 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 520.85 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 520.85 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 520.85 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 520.85 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   520.85   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   520.85   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 5919.59 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 5919.59 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 5919.59 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 5919.59 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 5919.59 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 5919.59 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 5919.59 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 5919.59 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 5919.59 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 5919.59 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 5919.59 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 5919.59 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   5919.59   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   5919.59   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3037.51 25-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3792.13 09-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.44 22-MAR-13:00 3031.11 19-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 415.93 01-APR-17:02 3042.44 10-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 892.20 14-MAY-16:00 1394.54 04-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 832.84 04-JUN-19:00 990.96 28-JUN-01:55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 983.09 02-JUL-21:10 490.23 18-JUL-21:10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 626.34 26-AUG-17:01 797.88 14-AUG-01:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 344.67 10-SEP-15:00 515.18 24-SEP-07:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 474.88 01-OCT-15:00 1391.57 24-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1913.72 26-NOV-09:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2625.34 18-DEC-04:53
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   490.23  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 983.09   3792.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 5173.64 25-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 6579.95 09-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.65 22-MAR-13:00 5051.35 19-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 849.93 01-APR-17:02 5276.40 10-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1619.58 14-MAY-16:00 2402.14 04-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1527.38 04-JUN-19:00 1795.36 28-JUN-01:55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1821.92 02-JUL-21:00 880.73 18-JUL-21:10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1156.81 27-AUG-12:52 1381.74 14-AUG-00:52
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 675.52 10-SEP-14:52 908.15 24-SEP-07:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 895.40 01-OCT-14:52 2418.47 24-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3209.16 26-NOV-09:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4281.07 18-DEC-05:12
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   880.73  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1821.92   6579.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 5238.79 25-JAN-23:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 6586.30 09-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4794.65 19-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 852.51 01-APR-17:02 5294.26 10-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1382.27 14-MAY-16:00 2444.77 04-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1454.32 10-JUN-17:02 2132.17 28-JUN-01:55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1846.42 02-JUL-21:20 1048.51 18-JUL-21:10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1169.95 26-AUG-18:00 1753.79 14-AUG-00:52
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 541.32 10-SEP-14:52 1007.68 23-SEP-17:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 847.07 01-OCT-14:52 2570.17 23-OCT-21:03
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2889.87 04-NOV-03:55
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4052.56 18-DEC-05:50
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1007.68  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1846.42   6586.30  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 112546.00 17-JAN-04:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
February 109505.63 13-FEB-04:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
March 110121.09 13-MAR-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
April 112745.75 24-APR-03:12 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
May 112443.88 01-MAY-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
June 112791.42 12-JUN-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 102264.60 10-JUL-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
August 113788.15 27-AUG-16:20 8976.13 11664.26 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
September 112225.97 11-SEP-03:02 0.00 6998.55 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
October 111364.18 10-OCT-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
November 115524.57 27-NOV-04:01 0.00 9331.40 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
December 117084.58 26-DEC-04:01 0.00 8164.98 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 102264.60   0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 117084.58   8976.13 11664.26 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 91891.08 02-JAN-04:03 0.00 4190.13 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
February 92531.26 21-FEB-04:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
March 90353.30 13-MAR-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
April 89712.46 26-APR-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
May 91059.57 22-MAY-03:02 0.00 6285.19 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
June 90132.47 29-JUN-03:02 0.00 6285.19 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
July 87035.16 05-JUL-04:03 0.00 8380.26 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
August 89980.66 14-AUG-05:03 9673.43 12570.39 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
September 94649.79 25-SEP-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
October 94444.15 23-OCT-03:02 0.00 6285.19 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
November 94969.79 13-NOV-04:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
December 95923.70 26-DEC-04:01 0.00 7332.73 56400.06 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 87035.16   0.00 4190.13 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 95923.70   9673.43 12570.39 56400.06 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 77763.83 13-JAN-06:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
February 80120.70 08-FEB-06:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
March 80099.79 07-MAR-06:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
April 82628.63 27-APR-04:02 0.00 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
May 84667.29 23-MAY-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
June 84199.25 20-JUN-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 87331.30 05-JUL-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 84010.75 29-AUG-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 85781.10 05-SEP-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
October 85086.71 06-OCT-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
November 80502.92 08-NOV-06:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
December 74159.18 14-DEC-06:03 6448.95 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 74159.18   0.00 5237.66 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 87331.30   8061.19 10475.32 48342.72 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 32538.43 12-JAN-17:00 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 35597.94 22-FEB-17:00 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
March 74623.96 16-MAR-05:03 6448.95 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
April 81275.30 03-APR-04:02 0.00 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
May 85363.75 22-MAY-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
June 84720.02 09-JUN-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 88292.75 05-JUL-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 87520.63 14-AUG-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 86646.45 05-SEP-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
October 82385.01 03-OCT-04:02 0.00 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
November 75083.88 10-NOV-06:03 6448.95 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
December 27489.79 01-DEC-16:50 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 27489.79   0.00 5237.66 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 88292.75   15316.26 18854.65 48342.72 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3693.53 02-JAN-04:03 0.00 526.11 4046.79 0.00 0.00 0.00 0.00 0.00 0.00
February 5285.05 21-FEB-15:00 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 12.56
March 6127.67 22-MAR-14:30 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 2.08 0.00
April 8679.08 21-APR-15:00 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 183.09 0.00
May 13153.19 23-MAY-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 11.30
June 16500.73 04-JUN-16:41 809.73 646.38 6070.18 0.00 0.00 0.00 0.00 25.92 0.00
July 13968.01 03-JUL-04:12 0.00 1315.28 5058.48 0.00 0.00 0.00 0.00 24.83 0.00
August 14715.97 07-AUG-03:01 0.00 920.70 7081.88 0.00 0.00 0.00 0.00 31.73 0.00
September 13302.31 18-SEP-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 15.61
October 13704.38 02-OCT-05:02 1012.16 1315.28 5058.48 0.00 0.00 0.00 0.00 0.00 2.72
November 5483.69 09-NOV-15:00 2010.79 1613.87 2276.32 0.00 0.00 0.00 0.00 0.00 5.63
December 3947.76 11-DEC-04:02 0.00 657.64 5058.48 0.00 0.00 0.00 0.00 0.00 183.77
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3693.53   0.00 526.11 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16500.73   2010.79 1613.87 7081.88 0.00 0.00 0.00 0.00 183.09 183.77



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4719.48 04-JAN-09:20 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 92.38
February 6916.82 21-FEB-08:50 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 16.66
March 7222.03 07-MAR-09:10 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 72.24
April 16015.20 30-APR-09:32 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 0.00 34.04
May 16873.64 29-MAY-08:52 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 58.20
June 16635.49 04-JUN-08:62 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 5.53
July 16397.08 16-JUL-08:32 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 7.49 0.00
August 16412.10 20-AUG-09:02 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 5.03
September 16935.38 04-SEP-08:12 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 70.17
October 10158.40 22-OCT-08:53 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 0.00 80.37
November 7627.02 10-NOV-08:40 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 70.90
December 3759.58 07-DEC-09:25 2478.65 1874.40 2933.89 0.00 0.00 0.00 0.00 0.00 15.48
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3759.58   260.91 208.28 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16935.38   2478.65 1874.40 2933.89 0.00 0.00 0.00 0.00 7.49 92.38



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13931.92 12-JAN-14:10 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 11.13
February 20322.76 20-FEB-13:42 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 0.00 185.96
March 12672.44 16-MAR-12:50 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 31.12
April 12512.91 30-APR-14:12 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 32.50 0.00
May 14240.14 22-MAY-05:03 809.75 1052.25 4046.85 0.00 0.00 0.00 0.00 0.00 20.34
June 14740.09 19-JUN-05:02 1012.19 1315.31 5058.56 0.00 0.00 0.00 0.00 0.00 6.00
July 15182.99 03-JUL-04:12 0.00 1315.31 5058.56 0.00 0.00 0.00 0.00 26.04 0.00
August 19471.52 06-AUG-15:01 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 178.76 0.00
September 20491.26 17-SEP-13:12 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 67.59 0.00
October 21315.03 29-OCT-12:52 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 0.00 155.00
November 19925.29 12-NOV-13:02 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 0.00 275.11
December 13277.67 07-DEC-13:40 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 84.93
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12512.91   0.00 323.20 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21315.03   2010.83 1454.32 5311.49 0.00 0.00 0.00 0.00 178.76 275.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7318.48 12-JAN-15:30 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 9.72
February 10712.53 20-FEB-16:23 260.91 208.28 1955.92 0.00 0.00 0.00 0.00 0.00 113.94
March 16868.22 26-MAR-16:32 326.14 260.35 2444.89 0.00 0.00 0.00 0.00 0.00 104.49
April 22457.83 16-APR-16:21 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 19.74 0.00
May 23118.44 29-MAY-15:31 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 102.61 0.00
June 23858.48 04-JUN-16:01 521.82 416.55 3911.83 0.00 0.00 0.00 0.00 68.23 0.00
July 22125.19 09-JUL-16:42 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 51.02 0.00
August 23341.44 06-AUG-16:21 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 85.37 0.00
September 22619.62 10-SEP-15:32 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 68.41 0.00
October 21042.32 29-OCT-15:32 326.14 260.35 2444.89 0.00 0.00 0.00 0.00 0.00 80.86
November 13385.19 10-NOV-06:03 521.82 678.09 2607.89 0.00 0.00 0.00 0.00 0.00 101.52
December 11599.05 11-DEC-06:03 521.82 678.09 2607.89 0.00 0.00 0.00 0.00 0.00 36.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7318.48   260.91 208.28 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23858.48   1239.33 937.20 3911.83 0.00 0.00 0.00 0.00 102.61 113.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3315.12 12-JAN-14:30 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 10.89
February 3462.41 20-FEB-15:53 404.87 368.97 3035.09 0.00 0.00 0.00 0.00 60.92 0.00
March 4363.61 22-MAR-14:40 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 1.37
April 7662.63 21-APR-15:00 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 423.68 0.00
May 12660.64 31-MAY-03:02 0.00 657.64 5058.48 0.00 0.00 0.00 0.00 69.67 0.00
June 14614.09 18-JUN-14:51 708.51 565.58 5311.41 0.00 0.00 0.00 0.00 207.88 0.00
July 14657.25 03-JUL-04:22 0.00 1315.28 5058.48 0.00 0.00 0.00 0.00 62.69 0.00
August 12374.14 08-AUG-05:02 1214.60 1578.34 6070.18 0.00 0.00 0.00 0.00 0.00 0.06
September 10652.04 01-SEP-05:02 1012.16 1315.28 5058.48 0.00 0.00 0.00 0.00 0.00 25.78
October 7930.71 05-OCT-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 12.97
November 3924.79 09-NOV-15:10 1923.11 1641.33 2276.32 0.00 0.00 0.00 0.00 0.00 11.83
December 2713.38 07-DEC-14:20 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 128.15
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2713.38   0.00 368.97 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14657.25   2010.79 1641.33 6070.18 0.00 0.00 0.00 0.00 423.68 128.15



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3269.05 12-JAN-14:00 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 16.05
February 4801.42 21-FEB-10:00 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 57.41
March 6220.87 07-MAR-09:40 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 192.80
April 17276.68 30-APR-09:12 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 102.38
May 17377.36 29-MAY-08:52 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 139.50
June 17355.64 25-JUN-08:52 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 106.43
July 17124.87 16-JUL-08:42 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 9.64 0.00
August 17281.52 06-AUG-08:12 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 5.00
September 17337.26 04-SEP-09:02 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 99.87
October 9080.99 01-OCT-08:23 260.91 208.28 1955.93 0.00 0.00 0.00 0.00 0.00 100.24
November 6430.33 10-NOV-09:10 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 130.86
December 2797.25 07-DEC-13:50 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 106.68
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2797.25   260.91 208.28 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17377.36   1239.33 937.20 2444.91 0.00 0.00 0.00 0.00 9.64 192.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 14262.71 12-JAN-14:20 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 20.91
February 18955.13 20-FEB-15:13 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 0.00 303.97
March 12072.17 16-MAR-13:30 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 66.19
April 18282.69 30-APR-13:52 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 54.37 0.00
May 13815.66 31-MAY-03:02 0.00 657.65 5058.56 0.00 0.00 0.00 0.00 68.48 0.00
June 14624.97 18-JUN-14:51 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 207.91 0.00
July 15928.58 03-JUL-04:22 0.00 1315.31 5058.56 0.00 0.00 0.00 0.00 65.67 0.00
August 18570.23 06-AUG-14:51 1012.19 807.99 7587.84 0.00 0.00 0.00 0.00 453.79 0.00
September 19316.62 04-SEP-13:02 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 73.87 0.00
October 20281.82 22-OCT-13:22 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 0.00 23.75
November 19597.56 11-NOV-13:12 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 0.00 637.13
December 12727.61 07-DEC-14:10 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 184.63
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12072.17   0.00 323.20 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20281.82   2010.83 1454.32 7587.84 0.00 0.00 0.00 0.00 453.79 637.13



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4809.58 12-JAN-15:30 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 23.28
February 7093.82 21-FEB-16:50 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 15.58
March 8684.76 21-MAR-16:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 13.26 0.00
April 19658.86 30-APR-16:31 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 67.79 0.00
May 19701.64 14-MAY-17:01 0.00 364.48 3422.85 0.00 0.00 0.00 0.00 265.12 0.00
June 19790.34 25-JUN-18:11 0.00 364.48 3422.85 0.00 0.00 0.00 0.00 49.30 0.00
July 19428.85 23-JUL-15:31 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 136.80 0.00
August 19417.10 06-AUG-16:51 652.28 520.69 4889.79 0.00 0.00 0.00 0.00 299.50 0.00
September 18151.05 04-SEP-16:22 326.14 260.35 2444.89 0.00 0.00 0.00 0.00 19.86 0.00
October 13186.96 22-OCT-16:02 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 3.73 0.00
November 7692.18 09-NOV-15:40 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 16.17
December 4187.10 15-DEC-16:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 120.88
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4187.10   0.00 260.35 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19790.34   1239.33 937.20 4889.79 0.00 0.00 0.00 0.00 299.50 120.88



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3043.21 12-JAN-14:30 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 12.71
February 3174.84 07-FEB-14:20 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 85.00
March 4255.06 16-MAR-16:00 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 74.44
April 8440.39 21-APR-15:00 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 518.95 0.00
May 14316.23 31-MAY-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 3.43
June 19424.11 18-JUN-14:51 708.51 565.58 5311.41 0.00 0.00 0.00 0.00 240.94 0.00
July 18982.59 02-JUL-16:12 607.30 484.79 4552.64 0.00 0.00 0.00 0.00 585.72 0.00
August 19107.72 06-AUG-17:31 0.00 807.98 7587.73 0.00 0.00 0.00 0.00 612.57 0.00
September 9551.66 20-SEP-05:02 1012.16 1315.28 5058.48 0.00 0.00 0.00 0.00 0.00 0.00
October 8848.73 05-OCT-05:03 809.73 1052.22 4046.79 0.00 0.00 0.00 0.00 0.00 16.68
November 4209.88 09-NOV-14:10 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 6.98
December 2567.59 01-DEC-15:00 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 235.62
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2567.59   0.00 484.79 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19424.11   2010.79 1454.29 7587.73 0.00 0.00 0.00 0.00 612.57 235.62



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2846.71 12-JAN-14:30 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 9.58
February 3357.73 21-FEB-10:30 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 69.66
March 5491.20 16-MAR-10:00 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 124.70
April 17502.56 30-APR-08:42 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 143.65
May 16704.14 21-MAY-14:22 391.37 312.41 2933.89 0.00 0.00 0.00 0.00 429.34 0.00
June 17845.32 25-JUN-09:02 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 117.07
July 17636.36 23-JUL-10:52 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 38.81 0.00
August 17825.64 06-AUG-08:12 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 8.46
September 17686.30 17-SEP-09:42 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 29.61
October 8780.73 05-OCT-08:50 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 3.02 0.00
November 5676.34 10-NOV-09:30 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 143.37
December 2399.14 01-DEC-10:30 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 130.62
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2399.14   326.14 260.35 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17845.32   1295.83 937.20 2933.89 0.00 0.00 0.00 0.00 429.34 143.65



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13827.18 12-JAN-14:30 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 19.50
February 13090.27 22-FEB-13:30 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 10.47
March 12277.72 16-MAR-14:10 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 77.23
April 20651.84 30-APR-13:22 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 86.00 0.00
May 20049.27 21-MAY-14:22 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 662.26 0.00
June 20855.50 18-JUN-14:51 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 242.74 0.00
July 20427.12 02-JUL-16:12 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 587.64 0.00
August 21135.03 06-AUG-14:51 1012.19 807.99 7587.84 0.00 0.00 0.00 0.00 538.79 0.00
September 22388.91 17-SEP-14:22 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 232.28 0.00
October 22705.73 22-OCT-13:22 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 0.00 29.48
November 16221.73 09-NOV-13:50 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 33.69
December 11408.09 07-DEC-14:30 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 200.21
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11408.09   506.09 404.00 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22705.73   2010.83 1454.32 7587.84 0.00 0.00 0.00 0.00 662.26 200.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4448.78 12-JAN-15:30 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 29.51
February 6757.61 21-FEB-16:50 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 20.52
March 8580.03 16-MAR-15:40 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 49.40
April 20629.91 30-APR-16:41 587.05 468.62 4400.81 0.00 0.00 0.00 0.00 98.80 0.00
May 20912.46 07-MAY-16:52 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 35.93 0.00
June 22407.40 25-JUN-17:01 0.00 416.55 3911.83 0.00 0.00 0.00 0.00 109.90 0.00
July 21349.64 23-JUL-15:31 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 147.61 0.00
August 21382.08 06-AUG-16:51 652.28 520.69 4889.79 0.00 0.00 0.00 0.00 353.67 0.00
September 21637.29 17-SEP-15:41 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 164.85 0.00
October 13359.99 01-OCT-15:02 326.14 260.35 2444.89 0.00 0.00 0.00 0.00 355.53 0.00
November 7663.70 09-NOV-15:40 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 22.79
December 3443.86 15-DEC-16:10 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 154.44
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3443.86   0.00 260.35 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22407.40   1239.33 937.20 4889.79 0.00 0.00 0.00 0.00 355.53 154.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7204.18 02-JAN-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 143.68
February 6748.90 21-FEB-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 143.83
March 6328.76 16-MAR-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 118.50
April 8313.36 04-APR-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.82
May 9471.14 30-MAY-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 118.92 0.00
June 9916.21 05-JUN-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.80
July 13162.50 03-JUL-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.90 0.00
August 16844.86 07-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.65 0.00
September 10532.21 25-SEP-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.86
October 9719.87 10-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 126.37
November 8654.38 13-NOV-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 244.09
December 6348.29 11-DEC-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 109.05
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 6328.76   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16844.86   0.00 0.00 0.00 0.00 0.00 0.00 0.00 118.92 244.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4890.66 07-JAN-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 314.96
February 5086.54 10-FEB-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 485.84
March 4955.34 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 357.02
April 6009.52 21-APR-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 547.26 0.00
May 7841.66 30-MAY-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.25
June 9044.00 17-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.00
July 8706.69 18-JUL-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.67
August 8083.16 07-AUG-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 113.46 0.00
September 7814.40 05-SEP-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.07 0.00
October 6576.28 05-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.63
November 4815.51 15-NOV-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 4921.17 22-DEC-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 424.59
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4815.51   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9044.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 547.26 485.84



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4917.14 12-JAN-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49.56
February 7282.31 22-FEB-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 10504.57 16-MAR-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 212.46
April 17062.77 28-APR-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.58 0.00
May 20478.47 30-MAY-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 205.87 0.00
June 22249.18 15-JUN-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 475.62 0.00
July 22612.29 03-JUL-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 139.43 0.00
August 21426.96 07-AUG-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 122.11 0.00
September 18214.65 15-SEP-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 60.70 0.00
October 15976.34 03-OCT-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 102.63 0.00
November 8479.94 09-NOV-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 79.87
December 2501.75 09-DEC-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 238.62
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2501.75   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22612.29   0.00 0.00 0.00 0.00 0.00 0.00 0.00 475.62 238.62



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2075.35 02-JAN-16:50 222.14 520.85 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4033.32 21-FEB-17:00 222.14 520.85 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 7138.08 31-MAR-24:00 0.00 28.94 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7791.67 26-APR-17:50 23.38 173.61 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3501.51 31-MAY-23:40 0.00 57.88 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
June 5337.58 30-JUN-23:55 0.00 57.88 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 7258.93 31-JUL-23:57 0.00 86.81 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7879.04 27-AUG-21:03 0.00 115.75 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 3513.03 30-SEP-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5317.32 31-OCT-24:00 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 6032.51 09-NOV-16:40 222.14 520.85 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7799.74 18-DEC-16:40 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2075.35   0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7879.04   222.14 520.85 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1816.69 30-JAN-17:00 222.14 520.85 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3736.57 21-FEB-17:00 222.14 520.85 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6614.46 31-MAR-24:00 0.00 28.94 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7371.25 26-APR-17:50 23.38 173.61 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3432.78 31-MAY-23:55 0.00 115.75 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
June 5188.93 30-JUN-23:55 0.00 57.88 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 7008.77 31-JUL-23:57 0.00 86.81 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7347.17 31-AUG-17:50 23.38 173.61 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3307.37 30-SEP-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4856.95 31-OCT-24:00 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5663.07 09-NOV-16:50 222.14 520.85 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7260.71 15-DEC-16:50 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1816.69   0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7371.25   222.14 520.85 23383.27 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1765.08 12-JAN-16:50 222.14 520.85 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3723.14 21-FEB-17:00 222.14 520.85 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6301.77 31-MAR-23:20 0.00 28.94 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7451.15 27-APR-17:50 23.38 173.61 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3466.77 31-MAY-23:55 0.00 115.75 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
June 5208.26 30-JUN-23:55 0.00 57.88 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 7024.59 31-JUL-23:57 0.00 86.81 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7459.97 27-AUG-20:12 0.00 144.69 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
September 3184.20 30-SEP-23:30 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4525.82 31-OCT-23:30 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5690.48 09-NOV-16:50 222.14 520.85 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7170.15 15-DEC-16:50 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1765.08   0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7459.97   222.14 520.85 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 92468.66 02-JAN-17:00 4808.68 5919.59 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 183235.75 21-FEB-17:00 4808.68 5919.59 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 357622.40 31-MAR-24:00 0.00 328.88 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 368208.04 17-APR-07:55 9617.36 11839.17 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
May 175578.41 31-MAY-23:55 0.00 1315.53 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
June 267181.76 30-JUN-24:00 0.00 657.76 569448.78 0.00 0.00 0.00 0.00 0.00 0.00
July 355054.88 31-JUL-23:23 0.00 1315.53 1518530.09 0.00 0.00 0.00 0.00 0.00 0.00
August 366870.73 14-AUG-07:20 4808.68 5919.59 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
September 176844.98 30-SEP-24:00 0.00 328.88 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 268991.04 31-OCT-24:00 0.00 328.88 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 277204.79 10-NOV-17:00 4808.68 5919.59 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 368154.08 11-DEC-17:00 4808.68 5919.59 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 92468.66   0.00 328.88 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 368208.04   9617.36 11839.17 1518530.09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.176309E+13 1199960.57 03-JAN-16:00 0.144704E+12 597363.69 27-JAN-07:10
February 0.203499E+13 1415015.83 21-FEB-16:49 0.103573E+12 607026.06 03-FEB-07:10
March 0.278082E+13 1572303.20 15-MAR-15:09 0.841823E+11 469191.82 02-MAR-07:19
April 0.321174E+13 1962865.46 21-APR-15:09 0.550699E+11 115828.82 12-APR-06:19
May 0.217053E+13 1510237.14 30-MAY-15:50 0.535934E+11 72403.13 01-MAY-11:39
June 0.267159E+13 1705968.02 02-JUN-15:30 0.498102E+11 67950.43 05-JUN-11:20
July 0.317267E+13 2043367.57 20-JUL-15:09 0.470953E+11 64801.60 06-JUL-11:39
August 0.365046E+13 2028885.92 08-AUG-15:09 0.500403E+11 64401.65 28-AUG-11:00
September 0.211378E+13 1492358.80 05-SEP-15:39 0.480009E+11 67444.11 28-SEP-11:09
October 0.244814E+13 1609055.69 03-OCT-15:50 0.528733E+11 71719.06 25-OCT-11:39
November 0.264527E+13 1590551.20 22-NOV-16:00 0.843433E+11 418600.55 28-NOV-06:10
December 0.305524E+13 1686457.04 08-DEC-16:00 0.170307E+12 639696.87 27-DEC-07:10
             
Annual Sum or Average 0.317183E+14     0.943593E+12    
Minimum of Months 0.176309E+13 1199960.57   0.470953E+11 64401.65  
Maximum of Months 0.365046E+13 2043367.57   0.170307E+12 639696.87  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.312373E+12 0.683267E+11 0.811612E+12 0.164871E+12 0.196809E+12 0.232262E+11 0.00 0.113543E+12 0.297847E+11 0.425411E+11 0.00 0.00 0.00
February 0.282041E+12 0.577076E+11 0.102011E+13 0.148926E+12 0.182915E+12 0.280799E+11 0.00 0.188452E+12 0.651189E+11 0.616405E+11 0.00 0.00 0.00
March 0.333011E+12 0.581876E+11 0.146267E+13 0.165150E+12 0.216702E+12 0.410268E+11 0.00 0.311502E+12 0.103771E+12 0.888028E+11 0.00 0.00 0.00
April 0.296327E+12 0.505727E+11 0.170311E+13 0.159525E+12 0.231926E+12 0.691894E+11 0.00 0.486605E+12 0.125503E+12 0.889801E+11 0.00 0.00 0.00
May 0.319257E+12 0.473313E+11 0.820521E+12 0.165009E+12 0.266411E+12 0.829268E+11 0.00 0.308375E+12 0.135727E+12 0.249716E+11 0.00 0.00 0.00
June 0.317299E+12 0.433352E+11 0.110677E+13 0.159787E+12 0.286229E+12 0.995863E+11 0.00 0.488809E+12 0.146211E+12 0.235617E+11 0.00 0.00 0.00
July 0.297319E+12 0.458643E+11 0.143888E+13 0.164745E+12 0.281332E+12 0.105466E+12 0.00 0.636416E+12 0.175711E+12 0.269426E+11 0.00 0.00 0.00
August 0.331613E+12 0.500699E+11 0.177780E+13 0.165150E+12 0.289877E+12 0.106481E+12 0.00 0.691094E+12 0.162385E+12 0.759990E+11 0.00 0.00 0.00
September 0.296998E+12 0.537677E+11 0.784732E+12 0.159522E+12 0.254432E+12 0.814810E+11 0.00 0.315934E+12 0.145103E+12 0.218134E+11 0.00 0.00 0.00
October 0.309922E+12 0.615456E+11 0.112899E+13 0.164870E+12 0.231414E+12 0.606352E+11 0.00 0.310267E+12 0.126765E+12 0.537245E+11 0.00 0.00 0.00
November 0.308380E+12 0.645588E+11 0.140306E+13 0.159633E+12 0.203437E+12 0.335170E+11 0.00 0.287903E+12 0.941630E+11 0.906125E+11 0.00 0.00 0.00
December 0.303116E+12 0.695655E+11 0.175516E+13 0.164747E+12 0.197278E+12 0.222545E+11 0.00 0.327054E+12 0.887322E+11 0.127338E+12 0.00 0.00 0.00
                           
Annual Sum or Average 0.370766E+13 0.670833E+12 0.152134E+14 0.194193E+13 0.283876E+13 0.753870E+12 0.00 0.446595E+13 0.139897E+13 0.726928E+12 0.00 0.00 0.00
Minimum of Months 0.282041E+12 0.433352E+11 0.784732E+12 0.148926E+12 0.182915E+12 0.222545E+11 0.00 0.113543E+12 0.297847E+11 0.218134E+11 0.00 0.00 0.00
Maximum of Months 0.333011E+12 0.695655E+11 0.177780E+13 0.165150E+12 0.289877E+12 0.106481E+12 0.00 0.691094E+12 0.175711E+12 0.127338E+12 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.847750E+11 0.00 0.599292E+11 0.00 0.00
February 0.00 0.00 0.492438E+11 0.00 0.543290E+11 0.00 0.00
March 0.00 0.00 0.229954E+11 0.00 0.611869E+11 0.00 0.00
April 0.00 0.00 0.128046E+10 0.00 0.537894E+11 0.00 0.00
May 0.00 0.00 0.00 0.00 0.535934E+11 0.00 0.00
June 0.00 0.00 0.00 0.00 0.498102E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.470953E+11 0.00 0.00
August 0.00 0.00 0.00 0.00 0.500403E+11 0.00 0.00
September 0.00 0.00 0.00 0.00 0.480009E+11 0.00 0.00
October 0.00 0.00 0.525041E+09 0.00 0.523483E+11 0.00 0.00
November 0.00 0.00 0.300552E+11 0.00 0.542881E+11 0.00 0.00
December 0.00 0.00 0.112974E+12 0.00 0.573327E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.301849E+12 0.00 0.641744E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.470953E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.112974E+12 0.00 0.611869E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 348383.67 17-JAN-16:00 54335.80 01-JAN-06:10 439129.89 02-JAN-08:09 118938.95 09-JAN-08:20 134475.65 12-JAN-15:00 38110.38 09-JAN-06:10 0.00 01-JAN-00:10
February 339262.50 23-FEB-16:00 54335.80 01-FEB-06:10 557421.28 01-FEB-08:09 118945.56 13-FEB-08:20 153393.65 21-FEB-16:30 55636.88 22-FEB-13:39 0.00 01-FEB-00:10
March 338793.60 10-MAR-16:00 54335.80 01-MAR-06:10 675712.68 01-MAR-08:09 118941.89 22-MAR-07:19 180284.79 16-MAR-15:30 55664.30 16-MAR-13:50 0.00 01-MAR-00:10
April 325092.87 20-APR-07:10 54335.80 01-APR-05:10 794004.08 03-APR-07:10 118936.04 20-APR-07:19 224865.87 21-APR-14:30 58157.35 28-APR-13:20 0.00 01-APR-00:10
May 316816.17 01-MAY-07:10 54335.80 01-MAY-05:10 439129.89 01-MAY-07:10 118929.14 01-MAY-07:19 244826.01 30-MAY-14:00 58311.87 30-MAY-12:39 0.00 01-MAY-00:10
June 316816.17 01-JUN-07:10 54335.80 01-JUN-19:10 557421.28 01-JUN-07:10 118929.14 01-JUN-07:19 256711.22 15-JUN-14:30 58876.13 07-JUN-14:39 0.00 01-JUN-00:10
July 323927.60 07-JUL-07:30 54335.80 01-JUL-19:19 675712.68 03-JUL-07:10 118935.07 07-JUL-07:40 327323.05 20-JUL-15:09 76523.30 20-JUL-15:09 0.00 01-JUL-00:10
August 323760.54 17-AUG-07:10 54335.80 01-AUG-05:10 794004.08 01-AUG-07:10 118934.93 17-AUG-07:19 248744.42 07-AUG-14:50 58143.22 23-AUG-09:30 0.00 01-AUG-00:10
September 325405.65 18-SEP-07:10 54335.80 01-SEP-05:10 439129.89 01-SEP-07:10 118936.30 18-SEP-07:19 232042.14 12-SEP-15:39 57892.68 29-SEP-13:20 0.00 01-SEP-00:10
October 343133.37 13-OCT-07:10 54335.80 01-OCT-05:10 557421.28 02-OCT-07:10 118951.09 13-OCT-07:19 208419.60 03-OCT-15:50 57188.89 03-OCT-13:50 0.00 01-OCT-00:10
November 352853.36 22-NOV-16:00 54335.80 01-NOV-05:10 675712.68 01-NOV-07:10 118950.24 01-NOV-07:19 169499.80 09-NOV-16:30 55776.91 03-NOV-13:39 0.00 01-NOV-00:10
December 352853.36 01-DEC-16:00 54335.80 01-DEC-06:10 794004.08 01-DEC-08:09 118936.20 13-DEC-08:20 130950.91 07-DEC-15:30 38547.05 26-DEC-06:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 316816.17   54335.80   439129.89   118929.14   130950.91   38110.38   0.00  
Maximum of Months 352853.36   54335.80   794004.08   118951.09   327323.05   76523.30   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 119290.67 03-JAN-14:00 49886.39 03-JAN-13:50 20608.00 05-JAN-21:00 0.00 0.00 0.00
February 180012.96 21-FEB-14:50 50007.49 21-FEB-17:10 31048.39 02-FEB-18:10 0.00 0.00 0.00
March 222273.32 21-MAR-16:30 50205.55 14-MAR-18:10 45009.45 31-MAR-23:00 0.00 0.00 0.00
April 390907.13 21-APR-14:00 85424.98 21-APR-13:00 52434.10 17-APR-19:40 0.00 0.00 0.00
May 287471.74 31-MAY-12:50 85424.98 08-MAY-12:09 19440.78 01-MAY-06:10 0.00 0.00 0.00
June 359169.25 15-JUN-14:39 85424.98 01-JUN-15:09 26586.91 13-JUN-06:10 0.00 0.00 0.00
July 514525.07 20-JUL-15:30 85424.98 01-JUL-15:30 27679.53 05-JUL-05:00 0.00 0.00 0.00
August 459205.61 02-AUG-08:20 85424.98 01-AUG-07:40 45382.13 16-AUG-18:19 0.00 0.00 0.00
September 338356.04 14-SEP-09:50 85424.98 01-SEP-07:19 23088.57 30-SEP-23:00 0.00 0.00 0.00
October 333690.60 03-OCT-13:00 85424.98 02-OCT-11:39 37422.52 31-OCT-23:10 0.00 0.00 0.00
November 223185.77 08-NOV-15:30 51586.08 03-NOV-14:39 42131.14 20-NOV-18:00 0.00 0.00 0.00
December 193003.64 20-DEC-14:00 49343.89 08-DEC-14:09 54705.71 18-DEC-19:00 0.00 0.00 0.00
                   
Annual Sum or Average             0.00 0.00 0.00
Minimum of Months 119290.67   49343.89   19440.78   0.00 0.00 0.00
Maximum of Months 514525.07   85424.98   54705.71   0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1199960.57 03-JAN-16:00 340245.06 439129.89 0.00 84899.55 117552.15 37036.16 0.00 117591.26 49456.33
February 1415015.83 21-FEB-16:49 322064.67 557421.28 0.00 84888.61 151118.47 55612.87 0.00 176136.26 49499.88
March 1572303.20 15-MAR-15:09 316816.17 675712.68 0.00 84885.75 150008.98 55619.58 0.00 220474.77 49975.10
April 1962865.46 21-APR-15:09 316816.17 794004.08 0.00 84885.75 223559.03 55976.63 0.00 389842.31 85424.98
May 1510237.14 30-MAY-15:50 316816.17 439129.89 0.00 84885.75 242123.95 57790.40 0.00 284065.99 85424.98
June 1705968.02 02-JUN-15:30 316816.17 557421.28 0.00 84885.75 248510.03 56100.83 0.00 356339.85 85424.98
July 2043367.57 20-JUL-15:09 316816.17 675712.68 0.00 84885.75 327323.05 76523.30 0.00 469530.64 85424.98
August 2028885.92 08-AUG-15:09 316816.17 794004.08 0.00 84885.75 247031.09 56961.29 0.00 430540.43 85424.98
September 1492358.80 05-SEP-15:39 316816.17 439129.89 0.00 84885.75 229257.18 56742.76 0.00 280102.07 85424.98
October 1609055.69 03-OCT-15:50 316816.17 557421.28 0.00 84885.75 208419.60 56470.66 0.00 296543.73 85424.98
November 1590551.20 22-NOV-16:00 352853.36 675712.68 54335.80 84906.26 127866.58 37025.43 0.00 181593.82 49471.11
December 1686457.04 08-DEC-16:00 352853.36 794004.08 54335.80 84914.96 112667.55 36903.36 0.00 161860.89 49248.27
                       
Annual Sum or Average                      
Minimum of Months 1199960.57   316816.17 439129.89 0.00 84885.75 112667.55 36903.36 0.00 117591.26 49248.27
Maximum of Months 2043367.57   352853.36 794004.08 54335.80 84914.96 327323.05 76523.30 0.00 469530.64 85424.98



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 568342.49 27-JAN-07:10 0.00 78487.66 30-JAN-12:20 0.00
February 0.00 0.00 578000.30 03-FEB-07:10 0.00 78497.47 02-FEB-12:39 0.00
March 0.00 0.00 451583.98 02-MAR-07:10 0.00 77777.72 01-MAR-12:00 0.00
April 0.00 0.00 108343.95 12-APR-06:10 0.00 75449.21 03-APR-11:39 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 72403.13 01-MAY-11:39 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 67950.43 05-JUN-11:20 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 64801.60 06-JUL-11:39 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 64401.65 28-AUG-11:00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 67444.11 28-SEP-11:09 0.00
October 0.00 0.00 28472.58 25-OCT-06:10 0.00 71719.06 25-OCT-11:39 0.00
November 0.00 0.00 412904.68 28-NOV-06:10 0.00 75705.81 30-NOV-12:30 0.00
December 0.00 0.00 627244.64 27-DEC-07:10 0.00 77714.22 29-DEC-12:50 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 64401.65   0.00
Maximum of Months 0.00 0.00 627244.64   0.00 78497.47   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 6.50 26.73 1.00 26.83
February 0.00 0.00 0.00 0.00 3.33 26.36 0.00 26.36
March 0.00 0.00 0.00 0.00 1.33 25.64 0.00 25.64
April 0.00 0.00 0.00 0.00 2.33 26.00 0.00 26.00
May 0.00 0.00 0.00 0.00 2.33 26.04 0.00 26.04
June 0.00 0.00 0.00 0.00 2.83 25.88 0.00 25.88
July 0.00 0.00 0.00 0.00 6.83 25.97 0.00 25.97
August 0.00 0.00 0.00 0.00 10.33 25.86 0.17 25.89
September 0.00 0.00 0.00 0.00 11.00 26.12 0.17 26.14
October 0.00 0.00 0.00 0.00 12.50 26.26 0.33 26.29
November 0.00 0.00 0.00 0.00 11.83 26.43 0.67 26.49
December 0.00 0.00 0.00 0.00 10.83 26.57 1.33 26.66
                 
Annual Sum or Average 0.00   0.00   82.00 26.24 3.67 26.29
Minimum of Months 0.00 0.00 0.00 0.00 1.33 25.64 0.00 25.64
Maximum of Months 0.00 0.00 0.00 0.00 12.50 26.73 1.33 26.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.50 25.61 0.00 25.61
February 0.00 0.00 0.00 0.00 0.50 25.64 0.00 25.64
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 25.58 0.00 25.58
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.67 25.60 0.00 25.60
August 0.00 0.00 0.00 0.00 1.67 25.72 0.00 25.72
September 0.00 0.00 0.00 0.00 0.83 25.63 0.00 25.63
October 0.00 0.00 0.00 0.00 1.33 25.62 0.00 25.62
November 0.00 0.00 0.00 0.00 0.83 25.74 0.00 25.74
December 0.00 0.00 0.00 0.00 0.83 25.72 0.00 25.72
                 
Annual Sum or Average 0.00   0.00   7.33 25.67 0.00 25.67
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.67 25.74 0.00 25.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 18.82 0.00 18.82 0.00 18.82 0.00 18.82
                 
Annual Sum or Average 0.33 18.82 0.00 18.82 0.00 18.82 0.00 18.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 18.82 0.00 18.82 0.00 18.82 0.00 18.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.17 26.81 0.33 26.92
August 0.00 0.00 0.00 0.00 1.50 26.54 0.33 26.68
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.67 26.66 0.67 26.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.50 26.81 0.33 26.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 27.31 0.17 27.31
March 0.00 0.00 0.00 0.00 0.50 27.31 0.50 27.31
April 0.00 0.00 0.00 0.00 2.00 27.63 2.00 27.63
May 0.00 0.00 0.00 0.00 4.67 27.78 4.67 27.78
June 0.00 0.00 0.00 0.00 4.33 27.85 4.33 27.85
July 0.00 0.00 0.00 0.00 5.83 27.73 5.67 27.76
August 0.00 0.00 0.00 0.00 3.50 27.80 3.50 27.80
September 0.00 0.00 0.00 0.00 3.17 27.80 3.17 27.80
October 0.00 0.00 0.00 0.00 0.67 27.52 0.67 27.52
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   24.83 27.75 24.67 27.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.83 27.85 5.67 27.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.17 27.52 1.17 27.52
February 0.00 0.00 0.00 0.00 2.67 27.59 2.67 27.59
March 0.00 0.00 0.00 0.00 0.17 27.28 0.17 27.28
April 0.00 0.00 0.00 0.00 0.67 27.48 0.67 27.48
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.83 27.00 1.33 27.15
August 0.00 0.00 0.00 0.00 6.50 27.35 5.17 27.45
September 0.00 0.00 0.00 0.00 5.83 27.70 5.83 27.70
October 0.00 0.00 0.00 0.00 7.50 27.84 7.17 27.88
November 0.00 0.00 0.00 0.00 6.33 27.71 6.33 27.71
December 0.00 0.00 0.00 0.00 1.33 27.39 1.33 27.39
                 
Annual Sum or Average 0.00   0.00   34.00 27.59 31.83 27.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.50 27.84 7.17 27.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.50 27.64 1.50 27.64
March 0.00 0.00 0.00 0.00 2.83 28.02 2.33 28.00
April 0.00 0.00 0.00 0.00 17.50 27.53 6.00 27.77
May 0.00 0.00 0.00 0.00 9.67 27.84 5.17 27.96
June 0.00 0.00 0.00 0.00 17.83 27.28 5.00 27.51
July 0.00 0.00 0.00 0.00 27.17 27.40 6.83 27.62
August 0.00 0.00 0.00 0.00 50.67 27.65 12.67 27.78
September 0.00 0.00 0.00 0.00 6.83 27.73 4.00 27.84
October 0.00 0.00 0.00 0.00 5.67 27.74 3.67 27.90
November 0.00 0.00 0.00 0.00 2.33 27.61 2.33 27.61
December 0.00 0.00 0.00 0.00 0.33 27.30 0.33 27.30
                 
Annual Sum or Average 0.00   0.00   142.33 27.57 49.83 27.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 50.67 28.02 12.67 28.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.23 0.00 19.23 0.00 19.23 0.00 19.23
February 0.17 19.42 0.00 19.42 0.00 19.42 0.00 19.42
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.83 26.66 0.17 26.76
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.43 0.00 19.43 0.00 19.43 0.00 19.43
December 0.67 19.33 0.00 19.33 0.00 19.33 0.00 19.33
                 
Annual Sum or Average 1.17 19.34 0.00 19.34 0.83 22.39 0.17 22.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 19.43 0.00 19.43 0.83 26.66 0.17 26.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.28 0.00 19.28 0.00 19.28 0.00 19.28
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.83 27.82 1.83 27.82
May 0.00 0.00 0.00 0.00 4.83 27.84 4.83 27.84
June 0.00 0.00 0.00 0.00 6.50 27.88 6.50 27.88
July 0.00 0.00 0.00 0.00 8.50 27.89 8.17 27.90
August 0.00 0.00 0.00 0.00 6.17 27.80 6.17 27.80
September 0.00 0.00 0.00 0.00 3.17 27.83 3.17 27.83
October 0.00 0.00 0.00 0.00 0.33 27.40 0.33 27.40
November 0.17 19.38 0.00 19.38 0.00 19.38 0.00 19.38
December 0.67 19.37 0.00 19.37 0.00 19.37 0.00 19.37
                 
Annual Sum or Average 1.00 19.36 0.00 19.36 31.33 27.58 31.00 27.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 19.38 0.00 19.38 8.50 27.89 8.17 27.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.33 27.37 0.33 27.37
February 0.00 0.00 0.00 0.00 2.50 27.63 2.50 27.63
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 27.30 0.17 27.30
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 26.76 0.33 26.97
August 0.00 0.00 0.00 0.00 2.50 27.50 2.33 27.51
September 0.00 0.00 0.00 0.00 5.33 27.73 5.33 27.73
October 0.00 0.00 0.00 0.00 7.17 27.92 6.83 27.95
November 0.00 0.00 0.00 0.00 5.33 27.71 5.33 27.71
December 0.00 0.00 0.00 0.00 0.50 27.37 0.50 27.37
                 
Annual Sum or Average 0.00   0.00   24.33 27.71 23.67 27.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.17 27.92 6.83 27.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 3.50 28.08 2.00 28.09
May 0.00 0.00 0.00 0.00 7.00 28.07 4.50 28.10
June 0.00 0.00 0.00 0.00 6.00 28.29 3.33 28.36
July 0.00 0.00 0.00 0.00 9.50 27.95 4.50 28.04
August 0.00 0.00 0.00 0.00 6.33 28.17 3.50 28.27
September 0.00 0.00 0.00 0.00 3.50 27.94 2.67 27.96
October 0.00 0.00 0.00 0.00 1.50 27.68 1.50 27.68
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   37.33 28.06 22.00 28.12
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.50 28.29 4.50 28.36



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.33 18.62 0.17 18.68 0.00 18.68 0.00 18.68
February 3.50 18.59 0.00 18.59 0.00 18.59 0.00 18.59
March 0.83 18.93 0.00 18.93 0.00 18.93 0.00 18.93
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.83 27.50 1.33 27.51
July 0.00 0.00 0.00 0.00 4.17 27.37 1.67 27.42
August 0.00 0.00 0.00 0.00 1.33 27.23 0.67 27.29
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 3.00 18.75 0.17 18.83 0.00 18.83 0.00 18.83
December 8.50 18.31 0.83 18.50 0.00 18.50 0.00 18.50
                 
Annual Sum or Average 21.17 18.52 1.17 18.62 7.33 20.78 3.67 21.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8.50 18.93 0.83 18.93 4.17 27.50 1.67 27.51



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.33 18.57 0.00 18.57 0.00 18.57 0.00 18.57
February 2.17 18.84 0.00 18.84 0.00 18.84 0.00 18.84
March 0.67 18.88 0.00 18.88 0.00 18.88 0.00 18.88
April 0.00 0.00 0.00 0.00 1.00 27.92 1.00 27.92
May 0.00 0.00 0.00 0.00 9.50 27.65 9.33 27.66
June 0.00 0.00 0.00 0.00 11.17 27.86 9.83 27.88
July 0.00 0.00 0.00 0.00 16.00 27.81 13.33 27.85
August 0.00 0.00 0.00 0.00 10.17 27.86 9.17 27.87
September 0.00 0.00 0.00 0.00 3.50 27.75 3.50 27.75
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 2.17 18.49 0.00 18.49 0.00 18.49 0.00 18.49
December 6.33 18.23 0.00 18.23 0.00 18.23 0.00 18.23
                 
Annual Sum or Average 15.67 18.47 0.00 18.47 51.33 25.62 46.17 26.53
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.33 18.88 0.00 18.88 16.00 27.92 13.33 27.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.83 18.97 0.00 18.97 0.00 18.97 0.00 18.97
February 1.67 19.04 0.00 19.04 0.83 21.88 0.83 23.30
March 0.50 18.98 0.00 18.98 0.00 18.98 0.00 18.98
April 0.00 0.00 0.00 0.00 0.83 27.47 0.83 27.47
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.33 27.54 1.00 27.56
July 0.00 0.00 0.00 0.00 5.83 27.42 3.33 27.49
August 0.00 0.00 0.00 0.00 6.50 27.57 5.17 27.63
September 0.00 0.00 0.00 0.00 6.17 27.85 5.83 27.86
October 0.00 0.00 0.00 0.00 5.67 27.96 5.33 28.00
November 1.00 17.93 0.00 17.93 1.00 22.79 1.00 24.41
December 4.17 18.61 0.00 18.61 0.00 18.61 0.00 18.61
                 
Annual Sum or Average 10.17 18.73 0.00 18.73 28.17 25.30 23.33 26.24
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.17 19.04 0.00 19.04 6.50 27.96 5.83 28.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.33 18.95 0.00 18.95 0.00 18.95 0.00 18.95
February 2.00 19.05 0.00 19.05 0.00 19.05 0.00 19.05
March 0.50 19.00 0.00 19.00 0.00 19.00 0.00 19.00
April 0.00 0.00 0.00 0.00 3.83 28.11 2.50 28.10
May 0.00 0.00 0.00 0.00 7.33 28.24 4.33 28.30
June 0.00 0.00 0.00 0.00 8.33 28.30 4.17 28.37
July 0.00 0.00 0.00 0.00 12.67 28.09 5.50 28.19
August 0.00 0.00 0.00 0.00 8.33 28.26 4.17 28.37
September 0.00 0.00 0.00 0.00 4.33 27.99 3.33 28.01
October 0.00 0.00 0.00 0.00 1.33 27.65 1.33 27.65
November 1.00 18.81 0.00 18.81 0.00 18.81 0.00 18.81
December 4.00 18.68 0.00 18.68 0.00 18.68 0.00 18.68
                 
Annual Sum or Average 10.83 18.86 0.00 18.86 46.17 26.39 25.33 26.99
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.68 0.00 18.68
Maximum of Months 4.00 19.05 0.00 19.05 12.67 28.30 5.50 28.37



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 49.83 28.00 35.17 27.97
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 129.17 28.02 111.17 28.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   179.00 28.01 146.33 28.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 129.17 28.02 111.17 28.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 30.67 27.90 22.17 27.87
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 79.83 27.92 71.50 27.91
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   110.50 27.92 93.67 27.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 79.83 27.92 71.50 27.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 29.67 27.92 21.17 27.89
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 83.67 28.01 71.83 27.98
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   113.33 27.99 93.00 27.96
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 83.67 28.01 71.83 27.98



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 456.50 28.81 318.50 28.86
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.00 28.43 0.00 28.43
August 0.00 0.00 0.00 0.00 743.00 30.58 514.00 30.64
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 4.50 27.62 4.50 27.62
                 
Annual Sum or Average 0.00   0.00   1205.00 29.90 837.00 29.95
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 743.00 30.58 514.00 30.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 163.83 24.00 94.17 24.82 0.00 24.82
February 212.50 24.00 76.83 24.50 0.00 24.50
March 262.50 24.00 59.00 24.39 0.00 24.39
April 120.33 24.00 99.50 24.92 0.00 24.92
May 41.00 24.00 213.17 24.93 14.17 24.88
June 40.00 24.54 312.50 24.68 34.67 24.67
July 270.67 24.44 493.17 24.56 270.67 24.53
August 197.50 24.18 498.83 24.42 197.50 24.36
September 176.83 24.68 446.83 24.64 176.83 24.65
October 59.50 24.56 315.00 24.92 55.33 24.88
November 31.50 24.00 150.67 25.58 0.00 25.58
December 125.50 24.00 98.50 25.12 0.00 25.12
             
Annual Sum or Average 1701.67 24.19 2858.17 24.69 749.17 24.66
Minimum of Months 31.50 24.00 59.00 24.39 0.00 24.36
Maximum of Months 270.67 24.68 498.83 25.58 270.67 25.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 193.33 23.95 61.00 24.35 0.00 24.35
February 185.17 23.99 39.50 24.20 0.00 24.20
March 143.83 24.00 48.67 24.49 0.00 24.49
April 73.83 24.00 94.83 24.39 0.00 24.39
May 38.50 23.99 200.50 24.48 19.17 24.44
June 31.50 24.00 319.83 24.23 29.83 24.21
July 270.50 24.26 495.17 24.24 270.50 24.25
August 127.17 24.13 506.67 24.19 127.17 24.18
September 159.83 24.46 436.67 24.38 159.83 24.40
October 34.33 24.49 299.83 24.61 30.33 24.61
November 51.00 24.00 135.00 24.93 0.00 24.93
December 140.33 24.00 78.17 24.76 0.00 24.76
             
Annual Sum or Average 1449.33 24.11 2715.83 24.38 636.83 24.36
Minimum of Months 31.50 23.95 39.50 24.19 0.00 24.18
Maximum of Months 270.50 24.49 506.67 24.93 270.50 24.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 419.50 23.71 0.00 23.71 0.00 23.71
February 367.00 23.81 7.17 23.82 0.00 23.82
March 352.67 23.89 1.67 23.90 0.00 23.90
April 170.00 23.96 42.50 24.12 0.00 24.12
May 61.17 23.97 173.33 24.37 15.17 24.35
June 43.17 24.07 296.50 24.24 31.17 24.23
July 297.00 24.16 491.00 24.19 297.00 24.19
August 203.67 24.13 480.83 24.18 203.67 24.17
September 159.00 24.31 413.50 24.30 153.83 24.30
October 69.17 24.08 236.83 24.35 33.00 24.35
November 270.33 23.84 38.83 23.92 0.00 23.92
December 445.17 23.72 0.00 23.72 0.00 23.72
             
Annual Sum or Average 2857.83 23.90 2182.17 24.07 733.83 24.09
Minimum of Months 43.17 23.71 0.00 23.71 0.00 23.71
Maximum of Months 445.17 24.31 491.00 24.37 297.00 24.35



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 495.17 22.42 74.67 22.19 74.67 22.02
February 442.83 22.87 20.50 22.79 20.50 22.72
March 468.50 23.40 2.00 23.39 2.00 23.38
April 218.00 23.79 47.83 23.91 0.00 23.91
May 84.83 23.91 196.17 24.27 17.67 24.25
June 39.33 24.08 325.17 24.28 28.17 24.26
July 280.33 24.26 493.67 24.28 280.33 24.27
August 195.00 24.11 491.17 24.20 195.00 24.18
September 179.33 24.30 413.50 24.31 167.00 24.31
October 195.17 23.55 173.50 23.84 38.83 23.88
November 413.83 22.94 27.67 22.93 11.00 22.88
December 496.00 22.22 87.67 21.96 87.67 21.76
             
Annual Sum or Average 3508.33 23.18 2353.50 23.50 922.83 23.50
Minimum of Months 39.33 22.22 2.00 21.96 0.00 21.76
Maximum of Months 496.00 24.30 493.67 24.31 280.33 24.31



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 22.51 12.17 22.47 12.17 22.44
February 438.50 22.86 6.00 22.83 6.00 22.81
March 481.00 23.34 1.67 23.33 1.67 23.33
April 214.50 23.72 55.67 23.84 0.00 23.84
May 68.00 23.81 226.50 24.35 12.00 24.33
June 20.50 24.11 388.00 24.34 16.50 24.33
July 195.83 24.55 495.83 24.41 195.83 24.44
August 88.17 24.28 508.67 24.25 88.17 24.26
September 155.83 24.32 400.33 24.30 134.00 24.33
October 182.67 23.52 187.33 23.88 25.17 23.90
November 427.00 23.17 4.00 23.18 0.00 23.18
December 494.50 22.70 1.33 22.69 1.33 22.69
             
Annual Sum or Average 3268.50 23.22 2287.50 23.66 492.83 23.71
Minimum of Months 20.50 22.51 1.33 22.47 0.00 22.44
Maximum of Months 502.00 24.55 508.67 24.41 195.83 24.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 472.67 22.51 11.50 22.49 9.83 22.46
February 380.17 22.78 15.17 22.86 4.17 22.84
March 343.67 22.98 20.50 23.13 2.00 23.12
April 157.50 23.45 119.83 23.97 3.67 24.01
May 61.33 24.36 318.67 24.52 24.00 24.60
June 38.33 25.27 428.67 24.43 31.00 24.51
July 191.17 24.72 495.50 24.45 191.00 24.51
August 104.33 24.34 497.50 24.20 99.50 24.23
September 135.50 24.65 429.67 24.43 119.33 24.51
October 172.17 23.18 233.33 23.85 24.67 23.88
November 371.50 22.87 22.67 23.01 0.00 23.01
December 469.67 22.44 12.00 22.43 10.00 22.40
             
Annual Sum or Average 2898.00 23.11 2605.00 23.70 519.17 23.78
Minimum of Months 38.33 22.44 11.50 22.43 0.00 22.40
Maximum of Months 472.67 25.27 497.50 24.52 191.00 24.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 306.83 22.75 63.33 23.10 7.00 23.07
February 258.83 23.02 46.50 23.38 5.33 23.36
March 284.00 23.31 28.50 23.54 1.83 23.52
April 145.17 23.60 115.50 24.08 1.00 24.09
May 75.67 23.68 242.17 24.31 11.50 24.30
June 26.33 24.08 379.50 24.29 16.67 24.29
July 196.83 24.57 495.33 24.40 196.83 24.44
August 102.50 24.69 509.17 24.35 102.50 24.40
September 139.67 24.87 441.17 24.56 129.67 24.64
October 109.83 24.36 335.17 24.53 47.17 24.66
November 209.50 23.28 137.33 23.94 5.67 24.00
December 289.00 22.89 44.83 23.17 4.33 23.14
             
Annual Sum or Average 2144.17 23.51 2838.50 24.07 529.50 24.13
Minimum of Months 26.33 22.75 28.50 23.10 1.00 23.07
Maximum of Months 306.83 24.87 509.17 24.56 196.83 24.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 409.17 22.70 18.50 22.81 0.00 22.81
February 271.17 23.06 27.17 23.30 0.83 23.32
March 142.33 23.47 117.50 24.23 5.33 24.29
April 33.00 25.83 302.33 24.90 20.67 25.03
May 53.50 24.90 351.00 24.65 29.00 24.75
June 35.83 26.26 462.50 24.57 35.83 24.68
July 192.17 25.12 497.00 24.69 192.17 24.79
August 123.50 25.65 514.00 24.72 123.50 24.87
September 139.17 24.87 445.00 24.56 131.83 24.64
October 66.00 24.62 342.17 24.66 37.00 24.75
November 147.50 23.38 154.83 24.12 1.67 24.14
December 237.50 23.32 55.50 23.79 0.00 23.79
             
Annual Sum or Average 1850.83 23.81 3287.50 24.33 577.83 24.44
Minimum of Months 33.00 22.70 18.50 22.81 0.00 22.81
Maximum of Months 409.17 26.26 514.00 24.90 192.17 25.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.16 185.50 21.02 185.50 20.93
February 454.00 21.64 115.17 21.47 115.17 21.36
March 514.00 22.34 38.00 22.24 38.00 22.15
April 319.50 23.20 17.17 23.26 0.67 23.26
May 111.33 23.67 193.50 24.19 11.17 24.18
June 24.33 24.07 363.67 24.39 18.83 24.38
July 231.00 24.42 495.67 24.40 231.00 24.40
August 145.50 24.07 490.67 24.21 145.50 24.19
September 188.50 24.00 366.33 24.14 140.17 24.16
October 357.17 23.03 108.67 23.26 27.33 23.29
November 487.17 21.82 63.67 21.67 63.67 21.56
December 497.00 21.02 243.83 20.88 243.83 20.81
             
Annual Sum or Average 3831.50 22.32 2681.83 22.78 1220.83 22.71
Minimum of Months 24.33 21.02 17.17 20.88 0.67 20.81
Maximum of Months 514.00 24.42 495.67 24.40 243.83 24.40



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 21.42 95.50 21.27 95.50 21.17
February 367.50 21.99 51.33 21.91 46.67 21.80
March 360.50 22.47 28.50 22.52 16.33 22.46
April 165.33 23.21 99.83 23.90 4.50 23.96
May 70.00 24.22 252.67 24.63 20.83 24.73
June 40.33 25.69 351.83 24.68 33.17 24.80
July 190.00 24.89 420.83 24.67 189.83 24.72
August 122.50 24.54 419.17 24.42 121.83 24.44
September 134.00 24.49 340.17 24.45 105.00 24.53
October 222.17 22.78 144.50 23.40 21.00 23.43
November 380.00 22.04 32.50 21.99 25.33 21.91
December 422.00 21.32 130.50 21.15 130.50 21.05
             
Annual Sum or Average 2901.33 22.52 2367.33 23.20 810.50 23.21
Minimum of Months 40.33 21.32 28.50 21.15 4.50 21.05
Maximum of Months 427.00 25.69 420.83 24.68 189.83 24.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 328.50 22.31 80.17 22.49 35.00 22.35
February 289.17 22.61 52.00 22.92 15.67 22.86
March 332.00 22.90 30.50 23.10 5.50 23.07
April 202.17 23.29 91.67 23.77 0.50 23.77
May 106.33 23.57 217.33 24.20 11.00 24.19
June 30.33 23.97 353.50 24.35 18.50 24.34
July 227.67 24.43 495.17 24.39 227.67 24.40
August 141.17 24.30 498.33 24.32 141.17 24.31
September 153.00 24.71 431.83 24.52 137.67 24.59
October 157.67 23.89 292.67 24.33 49.00 24.48
November 256.83 22.76 113.50 23.40 12.33 23.41
December 332.67 22.34 76.83 22.38 47.67 22.20
             
Annual Sum or Average 2557.50 23.16 2733.50 23.79 701.67 23.81
Minimum of Months 30.33 22.31 30.50 22.38 0.50 22.20
Maximum of Months 332.67 24.71 498.33 24.52 227.67 24.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 488.50 21.59 77.67 21.48 77.67 21.40
February 425.67 21.93 47.00 21.89 42.00 21.81
March 417.17 22.43 22.17 22.50 9.00 22.46
April 209.50 23.14 117.83 23.73 5.17 23.78
May 106.17 23.91 286.00 24.41 24.67 24.50
June 37.00 25.34 413.50 24.52 30.67 24.59
July 230.17 24.62 495.83 24.50 230.17 24.53
August 148.83 24.46 503.50 24.37 147.50 24.39
September 169.83 24.20 412.17 24.31 141.50 24.34
October 243.00 22.99 194.83 23.57 29.33 23.62
November 422.17 22.08 34.00 22.10 18.00 22.05
December 493.33 21.56 108.17 21.40 108.17 21.30
             
Annual Sum or Average 3391.33 22.56 2712.67 23.24 863.83 23.28
Minimum of Months 37.00 21.56 22.17 21.40 5.17 21.30
Maximum of Months 493.33 25.34 503.50 24.52 230.17 24.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.47 342.67 20.33 342.67 20.27
February 454.00 20.99 256.50 20.81 256.50 20.73
March 514.00 21.68 144.83 21.45 144.83 21.31
April 344.17 22.77 41.00 22.80 15.83 22.73
May 136.67 23.35 205.17 24.00 10.33 24.00
June 33.00 24.39 381.67 24.40 21.83 24.42
July 231.67 24.50 495.67 24.43 231.67 24.45
August 163.50 24.01 481.67 24.19 154.33 24.16
September 231.33 23.77 357.50 24.01 153.33 24.04
October 395.50 22.45 93.17 22.74 27.67 22.78
November 487.83 21.08 208.33 20.83 208.33 20.70
December 497.00 20.33 398.00 20.24 398.00 20.20
             
Annual Sum or Average 3990.67 21.84 3406.17 22.23 1965.33 22.08
Minimum of Months 33.00 20.33 41.00 20.24 10.33 20.20
Maximum of Months 514.00 24.50 495.67 24.43 398.00 24.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.77 255.00 20.56 255.00 20.45
February 451.83 21.55 123.83 21.31 123.83 21.16
March 444.50 22.22 61.00 22.04 61.00 21.89
April 184.83 23.00 125.17 23.70 7.50 23.70
May 92.00 24.32 325.83 24.53 33.67 24.66
June 58.17 25.56 440.17 24.60 46.67 24.73
July 228.17 24.85 495.67 24.62 228.17 24.67
August 163.83 24.54 499.33 24.38 159.83 24.42
September 177.00 24.37 409.67 24.37 144.50 24.44
October 267.33 22.45 157.33 23.12 23.83 23.15
November 454.50 21.53 107.83 21.33 102.67 21.17
December 497.00 20.61 302.33 20.45 302.33 20.37
             
Annual Sum or Average 3521.17 22.17 3303.17 22.75 1489.00 22.66
Minimum of Months 58.17 20.61 61.00 20.45 7.50 20.37
Maximum of Months 502.00 25.56 499.33 24.62 302.33 24.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 387.50 21.66 140.83 21.45 118.50 21.19
February 332.67 21.97 101.17 21.97 76.17 21.76
March 371.17 22.33 79.67 22.26 62.50 22.08
April 233.83 22.90 100.00 23.34 10.67 23.29
May 130.33 23.33 230.00 24.05 11.17 24.07
June 45.50 24.14 369.33 24.36 22.00 24.38
July 230.17 24.48 494.33 24.41 230.17 24.42
August 164.33 24.32 487.00 24.31 158.00 24.32
September 174.83 24.45 419.17 24.43 147.00 24.49
October 203.50 23.21 261.00 23.95 45.00 24.09
November 302.17 22.02 143.67 22.32 63.83 22.08
December 398.67 21.65 143.67 21.31 140.67 21.10
             
Annual Sum or Average 2974.67 22.66 2969.83 23.24 1085.67 23.16
Minimum of Months 45.50 21.65 79.67 21.31 10.67 21.10
Maximum of Months 398.67 24.48 494.33 24.43 230.17 24.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 496.67 21.05 217.33 20.81 217.33 20.69
February 436.00 21.47 142.00 21.30 139.17 21.18
March 429.67 21.91 86.83 21.84 74.83 21.71
April 245.67 22.79 120.67 23.38 11.17 23.40
May 137.33 23.65 283.17 24.27 27.33 24.37
June 44.83 25.12 413.17 24.51 31.67 24.59
July 233.50 24.63 495.67 24.49 233.50 24.52
August 166.00 24.34 492.83 24.32 159.00 24.34
September 200.50 23.97 398.17 24.20 154.17 24.24
October 293.17 22.60 170.33 23.21 28.67 23.26
November 436.33 21.52 115.50 21.37 102.50 21.22
December 497.00 20.95 260.33 20.74 260.33 20.64
             
Annual Sum or Average 3616.67 22.18 3196.00 22.76 1439.67 22.68
Minimum of Months 44.83 20.95 86.83 20.74 11.17 20.64
Maximum of Months 497.00 25.12 495.67 24.51 260.33 24.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 0.17 27.00 514.00 27.00 0.17 27.00
April 104.00 27.39 485.00 27.15 104.00 27.19
May 0.00 0.00 508.00 27.00 0.00 27.00
June 22.50 27.00 496.00 27.00 22.50 27.00
July 165.83 27.00 497.00 27.00 165.83 27.00
August 391.67 27.35 514.00 27.30 391.67 27.32
September 6.33 27.00 485.00 27.00 6.33 27.00
October 15.33 27.00 502.00 27.00 15.33 27.00
November 15.50 27.00 489.00 27.00 15.50 27.00
December 6.33 27.00 497.00 27.00 6.33 27.00
             
Annual Sum or Average 727.67 27.24 5943.00 27.05 727.67 27.07
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 391.67 27.39 514.00 27.30 391.67 27.32



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 483.50 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 0.00 0.00 514.00 27.00 0.00 27.00
April 13.50 27.76 485.00 27.09 13.50 27.11
May 0.00 0.00 508.00 27.00 0.00 27.00
June 0.00 0.00 496.00 27.00 0.00 27.00
July 1.50 27.00 497.00 27.00 1.50 27.00
August 113.50 27.71 514.00 27.27 113.50 27.34
September 0.00 0.00 485.00 27.00 0.00 27.00
October 0.67 27.00 502.00 27.00 0.67 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 497.00 27.00 0.00 27.00
             
Annual Sum or Average 129.17 27.71 5924.50 27.04 129.17 27.05
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 113.50 27.76 514.00 27.27 113.50 27.34



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 34.50 26.04 363.83 26.92 0.00 26.92
February 0.00 0.00 371.83 27.00 0.00 27.00
March 0.00 0.00 497.33 27.00 0.00 27.00
April 24.83 27.53 485.00 27.09 24.83 27.11
May 0.00 0.00 508.00 27.00 0.00 27.00
June 9.00 27.00 496.00 27.00 9.00 27.00
July 57.50 27.00 497.00 27.00 57.50 27.00
August 131.67 27.68 514.00 27.28 131.67 27.35
September 2.00 27.00 485.00 27.00 2.00 27.00
October 2.83 27.00 502.00 27.00 2.83 27.00
November 0.00 0.00 456.33 27.00 0.00 27.00
December 0.00 0.00 378.50 27.00 0.00 27.00
             
Annual Sum or Average 262.33 27.26 5554.83 27.03 227.83 27.05
Minimum of Months 0.00 0.00 363.83 26.92 0.00 26.92
Maximum of Months 131.67 27.68 514.00 27.28 131.67 27.35



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 493.83 27.00 502.00 27.00 493.83 27.00
February 454.00 27.01 454.00 27.01 454.00 27.01
March 514.00 27.01 514.00 27.01 514.00 27.01
April 485.00 28.31 485.00 28.31 485.00 28.31
May 508.00 27.01 508.00 27.01 508.00 27.01
June 496.00 27.01 496.00 27.01 496.00 27.01
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 30.72 514.00 30.72 514.00 30.72
September 485.00 27.01 485.00 27.01 485.00 27.01
October 502.00 27.01 502.00 27.01 502.00 27.01
November 489.00 27.01 489.00 27.01 489.00 27.01
December 497.00 27.02 497.00 27.02 497.00 27.02
             
Annual Sum or Average 5934.83 27.44 5943.00 27.44 5934.83 27.44
Minimum of Months 454.00 27.00 454.00 27.00 454.00 27.00
Maximum of Months 514.00 30.72 514.00 30.72 514.00 30.72



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00009 19.45765 0.75294 17.03431
February 454.00000 27.00009 17.63651 0.78574 18.09489
March 514.00000 27.00001 18.46542 0.84750 20.21472
April 485.00000 27.10268 20.34532 0.94139 23.84146
May 508.00000 27.00035 25.32945 0.21464 6.04454
June 496.00000 27.00046 26.68489 0.28355 6.73768
July 497.00000 27.00072 29.29833 0.34996 7.60266
August 514.00000 27.26530 28.59780 0.48462 10.35837
September 485.00000 27.00108 28.37773 0.24938 6.37323
October 502.00000 27.00072 25.63527 0.90269 22.25510
November 489.00000 27.00013 21.11203 0.87203 21.13020
December 497.00000 27.00001 17.83788 0.85194 20.39036
           
Annual Sum or Average 5943.00000 27.03163 23.27416 0.62654 14.96967
Minimum of Months 454.00000 27.00001 17.63651 0.21464 6.04454
Maximum of Months 514.00000 27.26530 29.29833 0.94139 23.84146



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00008 19.48138 0.66353 14.36410
February 454.00000 27.00008 17.62375 0.68338 14.92929
March 514.00000 27.00001 18.44310 0.73974 16.60954
April 485.00000 27.07037 20.33982 0.83070 19.71401
May 508.00000 27.00032 25.33605 0.16249 5.66117
June 496.00000 27.00045 26.68902 0.21727 6.05289
July 497.00000 27.00076 29.32435 0.25765 6.44185
August 514.00000 27.17652 28.69457 0.31207 7.35813
September 485.00000 27.00089 28.49662 0.18962 5.84782
October 502.00000 27.00068 25.66568 0.82460 19.41632
November 489.00000 27.00012 21.10005 0.74647 16.85973
December 497.00000 27.00001 17.80097 0.68598 15.01965
           
Annual Sum or Average 5943.00000 27.02129 23.29246 0.52450 12.32398
Minimum of Months 454.00000 27.00001 17.62375 0.16249 5.66117
Maximum of Months 514.00000 27.17652 29.32435 0.83070 19.71401



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.90478 19.76659 0.57225 12.24280
February 454.00000 27.00008 17.64562 0.62156 13.32752
March 514.00000 27.00001 18.45066 0.69529 15.35932
April 485.00000 27.06316 20.34926 0.81707 19.32973
May 508.00000 27.00034 25.33826 0.16831 5.78887
June 496.00000 27.00046 26.68805 0.23774 6.30310
July 497.00000 27.00075 29.32085 0.28039 6.74674
August 514.00000 27.18045 28.68298 0.32749 7.70897
September 485.00000 27.00092 28.49360 0.19378 5.95822
October 502.00000 27.00068 25.69961 0.80167 18.70141
November 489.00000 27.00012 21.11395 0.68483 15.12431
December 497.00000 27.00001 17.81098 0.59947 12.79789
           
Annual Sum or Average 5943.00000 27.01300 23.32306 0.49864 11.59061
Minimum of Months 454.00000 26.90478 17.64562 0.16831 5.78887
Maximum of Months 514.00000 27.18045 29.32085 0.81707 19.32973



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00022 30.00087 1.05562 28.53009
February 454.00000 27.01181 30.00120 1.19960 35.23478
March 514.00000 27.00775 29.99745 1.33986 42.33997
April 485.00000 28.31146 29.89128 1.74880 63.90252
May 508.00000 27.00588 30.00725 0.47794 9.82997
June 496.00000 27.00624 30.05863 0.70176 15.37330
July 497.00000 27.00490 30.17787 0.92593 23.12513
August 514.00000 30.71899 29.87729 2.22804 83.98861
September 485.00000 27.00621 30.04016 0.56830 11.82156
October 502.00000 27.01015 30.00189 1.26983 38.73223
November 489.00000 27.00786 29.99966 1.39511 45.25382
December 497.00000 27.02380 29.99852 1.51022 51.45662
           
Annual Sum or Average 5943.00000 27.43570 30.00413 1.20369 37.56291
Minimum of Months 454.00000 27.00022 29.87729 0.47794 9.82997
Maximum of Months 514.00000 30.71899 30.17787 2.22804 83.98861



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.50506 18.36344 0.33627 7.97664
February 454.00000 24.47363 16.29019 0.30846 7.42912
March 514.00000 24.37603 15.76364 0.28746 7.05763
April 485.00000 24.48930 20.36141 0.34865 7.98549
May 508.00000 24.48626 30.24844 -0.4319 9.93787
June 496.00000 24.44860 36.98602 -0.3871 9.04245
July 497.00000 24.61819 55.00004 -0.1964 7.00276
August 514.00000 24.49762 50.31783 -0.2453 7.15036
September 485.00000 24.57653 47.49149 -0.2463 7.69808
October 502.00000 24.62353 35.98196 0.51483 11.40991
November 489.00000 24.61302 20.88044 0.39901 9.02207
December 497.00000 24.57650 15.70180 0.34422 8.05942
           
Annual Sum or Average 5943.00000 24.52341 30.39076 0.08342 8.31996
Minimum of Months 454.00000 24.37603 15.70180 -0.4319 7.00276
Maximum of Months 514.00000 24.62353 55.00004 0.51483 11.40991



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.29747 20.16517 0.29737 7.19079
February 454.00000 24.28438 17.10985 0.28533 6.92033
March 514.00000 24.28155 16.39066 0.29520 7.04112
April 485.00000 24.25620 20.99572 0.34119 7.62149
May 508.00000 24.26622 31.20662 -0.4536 9.80959
June 496.00000 24.19170 38.52182 -0.4086 8.82242
July 497.00000 24.23146 53.94845 -0.2809 6.85192
August 514.00000 24.20265 50.51105 -0.2916 6.97056
September 485.00000 24.32305 47.65567 -0.3110 7.61749
October 502.00000 24.37826 36.78848 0.47381 10.17499
November 489.00000 24.40978 21.84963 0.36466 8.15168
December 497.00000 24.42054 17.03966 0.32055 7.52410
           
Annual Sum or Average 5943.00000 24.29495 31.12357 0.05015 7.89881
Minimum of Months 454.00000 24.19170 16.39066 -0.4536 6.85192
Maximum of Months 514.00000 24.42054 53.94845 0.47381 10.17499



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.78402 21.74889 0.15082 5.71781
February 454.00000 23.89358 18.17061 0.16502 5.82264
March 514.00000 24.05539 17.44850 0.21110 6.06572
April 485.00000 24.17666 21.64975 0.28897 6.94377
May 508.00000 24.21184 31.41621 -0.4948 10.55079
June 496.00000 24.18519 38.37424 -0.4418 9.43173
July 497.00000 24.20886 54.19913 -0.3287 7.48660
August 514.00000 24.19110 50.95787 -0.3557 7.88618
September 485.00000 24.25493 47.79897 -0.3632 8.22414
October 502.00000 24.20671 37.54703 0.40485 8.72229
November 489.00000 24.04880 23.24028 0.24358 6.50139
December 497.00000 23.76844 19.02802 0.12708 5.61513
           
Annual Sum or Average 5943.00000 24.08331 31.90492 -0.0350 7.42871
Minimum of Months 454.00000 23.76844 17.44850 -0.4948 5.61513
Maximum of Months 514.00000 24.25493 54.19913 0.40485 10.55079



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.44249 25.76827 -0.1822 7.24384
February 454.00000 22.89800 20.04875 -0.0913 6.45607
March 514.00000 23.45830 18.73706 0.05277 5.81709
April 485.00000 24.03020 21.75997 0.24969 6.68588
May 508.00000 24.20267 31.42389 -0.4872 10.49233
June 496.00000 24.22209 38.34981 -0.4054 8.86632
July 497.00000 24.28338 54.00897 -0.2804 6.99594
August 514.00000 24.23080 50.97661 -0.3252 7.48750
September 485.00000 24.25963 47.99884 -0.3544 8.16553
October 502.00000 23.91760 38.44963 0.32863 7.74055
November 489.00000 23.10982 25.10863 -0.0014 6.43146
December 497.00000 22.22592 21.44721 -0.2626 8.31864
           
Annual Sum or Average 5943.00000 23.61201 32.94128 -0.1477 7.56837
Minimum of Months 454.00000 22.22592 18.73706 -0.4872 5.81709
Maximum of Months 514.00000 24.28338 54.00897 0.32863 10.49233



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.50665 21.29909 -0.1550 6.29163
February 454.00000 22.89163 18.04796 -0.0752 6.00603
March 514.00000 23.38958 16.76277 0.04729 5.62629
April 485.00000 23.97337 20.78746 0.25182 6.72187
May 508.00000 24.24055 30.29492 -0.4548 10.10405
June 496.00000 24.28368 37.43508 -0.3338 7.87154
July 497.00000 24.35493 52.97348 -0.2010 6.42687
August 514.00000 24.24662 49.74276 -0.2649 6.94443
September 485.00000 24.22714 47.21619 -0.3498 8.28180
October 502.00000 23.92291 37.24698 0.33805 7.93073
November 489.00000 23.27621 22.73577 0.05329 5.71386
December 497.00000 22.70856 18.23725 -0.1253 6.02801
           
Annual Sum or Average 5943.00000 23.67394 31.16552 -0.1067 7.00417
Minimum of Months 454.00000 22.50665 16.76277 -0.4548 5.62629
Maximum of Months 514.00000 24.35493 52.97348 0.33805 10.10405



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.61558 20.76627 -0.1040 6.36934
February 454.00000 23.04859 17.49824 -0.0052 6.29832
March 514.00000 23.40761 16.26074 0.09484 6.40322
April 485.00000 23.98299 20.48335 0.30584 7.85448
May 508.00000 24.32162 29.94974 -0.3461 9.06458
June 496.00000 24.29141 37.27275 -0.2606 7.58711
July 497.00000 24.35077 52.86048 -0.1462 6.75647
August 514.00000 24.15324 49.93628 -0.2442 7.36438
September 485.00000 24.28935 46.72761 -0.2495 7.84681
October 502.00000 23.85509 37.10165 0.36292 8.84781
November 489.00000 23.20832 22.45718 0.07200 6.27918
December 497.00000 22.56002 17.95036 -0.1366 6.51495
           
Annual Sum or Average 5943.00000 23.67797 30.87545 -0.0559 7.27319
Minimum of Months 454.00000 22.56002 16.26074 -0.3461 6.27918
Maximum of Months 514.00000 24.35077 52.86048 0.36292 9.06458



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.37933 19.77426 0.10270 7.27353
February 454.00000 23.62827 16.80310 0.14895 7.15792
March 514.00000 23.75584 15.87683 0.18078 6.81193
April 485.00000 24.08633 20.43384 0.31166 7.80129
May 508.00000 24.21937 30.26768 -0.4474 10.21309
June 496.00000 24.24723 37.51148 -0.3486 8.12336
July 497.00000 24.33852 53.00710 -0.2024 6.55932
August 514.00000 24.27754 49.56390 -0.2202 6.79033
September 485.00000 24.40864 46.40075 -0.2059 7.35994
October 502.00000 24.29429 35.97023 0.49797 11.43450
November 489.00000 23.93549 21.30173 0.28097 8.41507
December 497.00000 23.50508 16.82718 0.11659 7.10206
           
Annual Sum or Average 5943.00000 24.00831 30.41722 0.01593 7.92664
Minimum of Months 454.00000 23.37933 15.87683 -0.4474 6.55932
Maximum of Months 514.00000 24.40864 53.00710 0.49797 11.43450



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.99905 19.97258 0.01585 6.18898
February 454.00000 23.59663 16.66770 0.15756 6.62140
March 514.00000 24.13906 15.28115 0.31997 7.95393
April 485.00000 24.48964 19.69907 0.51235 11.43310
May 508.00000 24.38806 29.75108 -0.2734 8.33400
June 496.00000 24.40755 36.92944 -0.1419 6.78262
July 497.00000 24.52496 52.18790 0.01829 6.51888
August 514.00000 24.49152 48.74148 0.04123 6.65508
September 485.00000 24.40178 46.38792 -0.1524 6.99418
October 502.00000 24.38365 35.73794 0.54093 12.14552
November 489.00000 24.12907 20.89301 0.34020 8.26652
December 497.00000 23.98844 16.21277 0.24711 7.11328
           
Annual Sum or Average 5943.00000 24.16507 29.97409 0.13465 7.92052
Minimum of Months 454.00000 22.99905 15.28115 -0.2734 6.18898
Maximum of Months 514.00000 24.52496 52.18790 0.54093 12.14552



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.16120 23.13486 -0.4945 10.74240
February 454.00000 21.63632 19.64351 -0.3882 9.13504
March 514.00000 22.33674 18.04724 -0.2167 7.03091
April 485.00000 23.51998 21.46567 0.11862 6.23989
May 508.00000 24.14609 30.25336 -0.5107 11.40444
June 496.00000 24.31280 37.02762 -0.3537 8.19826
July 497.00000 24.38474 53.21420 -0.2264 6.68768
August 514.00000 24.24063 50.07741 -0.3233 7.63886
September 485.00000 24.08535 47.53267 -0.4244 9.61980
October 502.00000 23.30858 38.89316 0.17568 6.59763
November 489.00000 21.82474 24.74480 -0.3014 8.16691
December 497.00000 21.02460 20.39545 -0.5507 12.09350
           
Annual Sum or Average 5943.00000 23.00895 32.13109 -0.2912 8.62727
Minimum of Months 454.00000 21.02460 18.04724 -0.5507 6.23989
Maximum of Months 514.00000 24.38474 53.21420 0.17568 12.09350



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 21.42338 22.10243 -0.4084 9.34788
February 385.00000 22.11904 18.15796 -0.2445 7.82504
March 433.00000 22.80829 16.62842 -0.0683 6.89671
April 410.00000 23.94958 20.21039 0.27292 8.04575
May 430.00000 24.36394 29.33028 -0.3583 9.81022
June 418.00000 24.45513 36.11806 -0.2349 7.81266
July 422.00000 24.56535 52.21245 -0.1029 7.15816
August 433.00000 24.35380 49.08633 -0.2175 7.61226
September 410.00000 24.29564 46.20140 -0.2790 8.74408
October 427.00000 23.46249 37.87337 0.25091 7.93736
November 417.00000 22.23199 23.34411 -0.1768 7.29659
December 422.00000 21.31773 19.23648 -0.4592 10.33431
           
Annual Sum or Average 5034.00000 23.28486 30.96526 -0.1690 8.23763
Minimum of Months 385.00000 21.31773 16.62842 -0.4592 6.89671
Maximum of Months 433.00000 24.56535 52.21245 0.27292 10.33431



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.01835 20.40071 0.01203 7.80828
February 454.00000 23.29155 17.48133 0.06155 7.51020
March 514.00000 23.40781 16.41097 0.08539 6.87179
April 485.00000 23.90772 20.72382 0.24536 7.40567
May 508.00000 24.15599 30.16273 -0.4900 11.19505
June 496.00000 24.27522 37.11091 -0.3693 8.46616
July 497.00000 24.37050 53.22833 -0.2265 6.79643
August 514.00000 24.30973 49.74238 -0.2604 7.24344
September 485.00000 24.38209 46.33011 -0.2334 7.73168
October 502.00000 24.13649 36.40058 0.44896 10.81333
November 489.00000 23.55911 21.95132 0.18282 8.40605
December 497.00000 23.00610 17.83858 -0.0149 7.79875
           
Annual Sum or Average 5943.00000 23.82160 30.75196 -0.0484 8.17856
Minimum of Months 454.00000 23.00610 16.41097 -0.4900 6.79643
Maximum of Months 514.00000 24.38209 53.22833 0.44896 11.19505



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.65941 21.96416 -0.3390 8.66507
February 454.00000 22.09136 18.67685 -0.2407 7.73213
March 514.00000 22.77395 16.95375 -0.0597 6.71367
April 485.00000 23.81796 20.65579 0.25800 7.94317
May 508.00000 24.22459 29.88072 -0.3848 10.28104
June 496.00000 24.36745 36.76028 -0.2414 7.61443
July 497.00000 24.44168 52.84117 -0.1201 6.71508
August 514.00000 24.32769 49.63817 -0.1956 7.20954
September 485.00000 24.21240 46.86201 -0.2779 8.30504
October 502.00000 23.59495 37.66061 0.30394 8.35502
November 489.00000 22.35285 23.43764 -0.1293 7.10757
December 497.00000 21.57594 19.27852 -0.3817 9.28523
           
Annual Sum or Average 5943.00000 23.29561 31.31454 -0.1507 7.99574
Minimum of Months 454.00000 21.57594 16.95375 -0.3848 6.71367
Maximum of Months 514.00000 24.44168 52.84117 0.30394 10.28104



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.47036 24.28956 -0.7048 17.02332
February 454.00000 20.98757 20.31244 -0.5778 13.36293
March 514.00000 21.67684 18.57141 -0.3896 9.69909
April 485.00000 23.16309 21.58595 0.03617 6.71512
May 508.00000 24.02850 30.39959 -0.5355 12.60172
June 496.00000 24.30550 37.17374 -0.3322 8.09712
July 497.00000 24.39665 53.30087 -0.1984 6.71352
August 514.00000 24.20595 50.34914 -0.3164 7.87328
September 485.00000 23.95860 48.08260 -0.4537 10.79072
October 502.00000 22.78156 40.02206 0.05232 6.80962
November 489.00000 21.08876 25.65950 -0.5057 12.49897
December 497.00000 20.33116 21.28990 -0.7699 19.38560
           
Annual Sum or Average 5943.00000 22.62876 32.68063 -0.3905 10.94641
Minimum of Months 454.00000 20.33116 18.57141 -0.7699 6.71352
Maximum of Months 514.00000 24.39665 53.30087 0.05232 19.38560



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.76787 23.54690 -0.5961 14.07036
February 454.00000 21.56642 19.39127 -0.3975 10.17042
March 514.00000 22.47830 17.40191 -0.1594 7.72328
April 485.00000 23.84520 20.43773 0.25657 8.09106
May 508.00000 24.29438 29.71326 -0.3478 9.73374
June 496.00000 24.39561 36.79569 -0.2043 7.49311
July 497.00000 24.50870 52.71824 -0.0748 7.11850
August 514.00000 24.30092 49.86423 -0.1917 7.50902
September 485.00000 24.23624 46.91412 -0.2654 8.62329
October 502.00000 23.25006 38.64669 0.20247 7.96621
November 489.00000 21.69989 24.55575 -0.3267 9.59505
December 497.00000 20.60994 20.62726 -0.6650 15.98640
           
Annual Sum or Average 5943.00000 23.00675 31.81402 -0.2302 9.49891
Minimum of Months 454.00000 20.60994 17.40191 -0.6650 7.11850
Maximum of Months 514.00000 24.50870 52.71824 0.25657 15.98640



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.25534 21.78022 -0.2044 10.21492
February 454.00000 22.64965 18.40421 -0.1191 9.00277
March 514.00000 22.88342 17.01142 -0.0561 7.81993
April 485.00000 23.64828 20.81733 0.18419 7.61950
May 508.00000 24.04152 30.31441 -0.5131 12.39462
June 496.00000 24.25474 37.28807 -0.3515 8.48903
July 497.00000 24.36897 53.36506 -0.2018 6.92397
August 514.00000 24.27352 50.03110 -0.2518 7.52548
September 485.00000 24.30749 46.80241 -0.2439 8.36032
October 502.00000 23.82337 37.22803 0.37212 10.35402
November 489.00000 22.94679 22.86446 0.01043 9.21393
December 497.00000 22.14979 19.04239 -0.2570 10.64046
           
Annual Sum or Average 5943.00000 23.47230 31.34695 -0.1371 9.05145
Minimum of Months 454.00000 22.14979 17.01142 -0.5131 6.92397
Maximum of Months 514.00000 24.36897 53.36506 0.37212 12.39462



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.07913 22.99409 -0.5145 12.50909
February 454.00000 21.59514 19.30090 -0.3893 10.14325
March 514.00000 22.30282 17.42847 -0.1877 8.13191
April 485.00000 23.55434 20.74584 0.19745 8.11923
May 508.00000 24.10769 30.05704 -0.4070 11.45111
June 496.00000 24.33229 36.99775 -0.2267 7.78963
July 497.00000 24.42200 53.04788 -0.1004 6.97553
August 514.00000 24.27331 49.98034 -0.1926 7.62809
September 485.00000 24.11410 47.37858 -0.2953 9.19043
October 502.00000 23.23500 38.49265 0.21829 8.15815
November 489.00000 21.79813 24.23540 -0.2865 9.39750
December 497.00000 20.94633 20.14907 -0.5733 13.83969
           
Annual Sum or Average 5943.00000 22.99042 31.83027 -0.2292 9.43920
Minimum of Months 454.00000 20.94633 17.42847 -0.5733 6.97553
Maximum of Months 514.00000 24.42200 53.04788 0.21829 13.83969



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.635376E+10 70980.20 03-JAN-14:30 110.13 0.336298E+11 0.00 0.399835E+11 0.70 6.91 03-JAN-14:30 0.00 0.00
February 0.183252E+11 90028.71 21-FEB-14:50 157.72 0.103796E+12 0.00 0.122122E+12 1.18 7.33 21-FEB-14:50 0.00 0.00
March 0.387289E+11 91236.56 06-MAR-15:10 255.04 0.232201E+12 0.00 0.270930E+12 1.85 7.36 16-MAR-13:50 0.00 0.00
April 0.857005E+11 103777.09 27-APR-12:00 468.82 0.550807E+12 0.00 0.636507E+12 3.75 7.38 28-APR-09:50 0.00 0.00
May 0.128891E+12 109576.85 31-MAY-12:50 535.30 0.860450E+12 0.00 0.989340E+12 4.53 7.43 31-MAY-05:03 0.00 0.00
June 0.156493E+12 118376.47 08-JUN-05:02 626.80 0.105663E+13 0.00 0.121312E+13 5.52 7.55 08-JUN-05:02 0.00 0.00
July 0.172313E+12 187473.75 20-JUL-15:30 660.95 0.116047E+13 0.00 0.133278E+13 5.60 8.15 22-JUL-05:02 0.00 0.00
August 0.161645E+12 164220.49 08-AUG-05:03 689.29 0.108431E+13 0.00 0.124596E+13 5.73 7.87 14-AUG-05:03 0.00 0.00
September 0.126762E+12 140233.10 14-SEP-09:50 506.19 0.853916E+12 0.00 0.980678E+12 4.47 7.69 22-SEP-05:03 0.00 0.00
October 0.808642E+11 107167.61 03-OCT-14:00 392.22 0.520032E+12 0.00 0.600897E+12 3.13 7.41 23-OCT-14:50 0.00 0.00
November 0.288611E+11 91863.48 08-NOV-15:30 198.23 0.173230E+12 0.00 0.202091E+12 1.48 7.35 10-NOV-12:00 0.00 0.00
December 0.336025E+10 49156.30 08-DEC-14:00 101.30 0.152044E+11 0.00 0.185646E+11 0.62 4.72 08-DEC-14:10 0.00 0.00
                         
Annual Sum or Average 0.100830E+13     4702.00 0.664468E+13 0.00 0.765298E+13 3.22     0.00 0.00
Minimum of Months 0.336025E+10 49156.30   101.30 0.152044E+11 0.00 0.185646E+11 0.62 4.72   0.00 0.00
Maximum of Months 0.172313E+12 187473.75   689.29 0.116047E+13 0.00 0.133278E+13 5.73 8.15   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.110095E+11 101493.59 27-APR-13:20 33.67 0.785533E+11 0.00 0.895628E+11 0.33 7.35 27-APR-13:20 0.00 0.00
May 0.327803E+11 109576.85 31-MAY-12:50 98.66 0.234158E+12 0.00 0.266938E+12 0.95 7.43 31-MAY-05:03 0.00 0.00
June 0.643506E+11 118376.47 08-JUN-05:02 186.41 0.463385E+12 0.00 0.527735E+12 1.86 7.55 08-JUN-05:02 0.00 0.00
July 0.760798E+11 187473.75 20-JUL-15:30 204.90 0.540073E+12 0.00 0.616153E+12 1.95 8.15 22-JUL-05:02 0.00 0.00
August 0.597129E+11 164220.49 08-AUG-05:03 168.48 0.426318E+12 0.00 0.486031E+12 1.62 7.87 14-AUG-05:03 0.00 0.00
September 0.464987E+11 140233.10 14-SEP-09:50 135.11 0.332767E+12 0.00 0.379266E+12 1.34 7.69 22-SEP-05:03 0.00 0.00
October 0.126450E+11 107167.61 03-OCT-14:00 37.41 0.903134E+11 0.00 0.102958E+12 0.36 7.34 05-OCT-05:03 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.303077E+12     864.64 0.216557E+13 0.00 0.246864E+13 0.71     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.760798E+11 187473.75   204.90 0.540073E+12 0.00 0.616153E+12 1.95 8.15   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.297734E+11 744.00 49248.27 02-JAN-12:50 226180.50 02-JAN-17:05 22.18 18.40 15.26
February 0.650707E+11 672.00 49248.27 03-FEB-13:20 388955.82 20-FEB-18:13 25.90 19.19 15.26
March 0.103624E+12 744.00 49248.27 03-MAR-11:10 660060.92 31-MAR-24:00 30.21 20.55 15.26
April 0.124408E+12 720.00 49248.27 01-APR-07:15 727562.69 15-APR-02:42 39.29 26.59 15.26
May 0.128083E+12 744.00 49248.27 01-MAY-00:02 381534.71 31-MAY-23:42 30.54 26.30 15.26
June 0.127652E+12 720.00 49248.27 01-JUN-00:05 539981.68 30-JUN-23:32 39.15 31.87 15.26
July 0.131907E+12 744.00 49248.27 01-JUL-00:02 694910.17 31-JUL-23:53 43.45 33.22 15.26
August 0.131907E+12 744.00 49248.27 01-AUG-00:05 743410.17 08-AUG-16:00 46.64 33.57 15.26
September 0.123833E+12 720.00 49248.27 01-SEP-00:05 369821.16 30-SEP-24:00 30.21 25.90 15.26
October 0.120890E+12 744.00 49248.27 01-OCT-00:10 515488.00 31-OCT-24:00 29.89 22.83 15.26
November 0.940054E+11 720.00 49248.27 01-NOV-09:50 553488.69 03-NOV-16:10 29.55 19.86 15.26
December 0.887311E+11 744.00 49248.27 01-DEC-09:50 687757.41 07-DEC-16:55 31.22 18.86 15.26
                   
Annual Sum or Average 0.126988E+13 8760.00         33.23 24.79 15.26
Minimum of Months 0.297734E+11 672.00 49248.27   226180.50   22.18 18.40 15.26
Maximum of Months 0.131907E+12 744.00 49248.27   743410.17   46.64 33.57 15.26



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 11247483.29 17.58 638.12 03-JAN-13:50 576828.01 03-JAN-14:30 21.05 20.98 4.01
February 48271902.44 74.89 759.22 21-FEB-17:10 884967.81 23-FEB-14:10 21.28 21.07 10.21
March 0.147558E+09 160.48 957.28 14-MAR-18:10 1045461.83 21-MAR-16:00 21.45 21.02 17.24
April 0.922085E+09 323.92 18088.36 21-APR-14:00 1223632.57 27-APR-13:20 22.17 21.07 34.39
May 0.550341E+10 482.03 18088.36 08-MAY-12:10 1191263.14 15-MAY-15:10 23.01 21.34 43.12
June 0.125726E+11 577.78 18088.36 01-JUN-15:10 1277197.91 01-JUN-14:20 23.42 21.28 52.91
July 0.305204E+11 660.06 18088.36 01-JUL-05:04 1442386.20 20-JUL-15:30 24.27 22.23 54.58
August 0.211907E+11 637.16 18088.36 01-AUG-05:03 1202685.63 23-AUG-09:00 23.53 21.54 56.35
September 0.148831E+11 482.73 18088.36 01-SEP-06:50 1216595.32 25-SEP-16:00 23.28 21.63 42.95
October 0.431082E+10 340.09 18088.36 02-OCT-09:20 1131469.78 30-OCT-15:10 22.32 21.34 31.02
November 0.157547E+09 120.90 2337.81 03-NOV-14:40 1007108.06 09-NOV-15:00 21.32 20.98 13.61
December 1107418.67 8.33 95.62 08-DEC-14:10 296925.85 08-DEC-14:10 20.98 20.94 2.79
                   
Annual Sum or Average 0.902689E+11 3885.96         22.35 21.29 30.37
Minimum of Months 1107418.67 8.33 95.62   296925.85   20.98 20.94 2.79
Maximum of Months 0.305204E+11 660.06 18088.36   1442386.20   24.27 22.23 56.35



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 21.05 21.05 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 21.28 21.28 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 21.45 21.45 0.00
April 0.173441E+09 10.33 18088.36 21-APR-14:00 1223632.57 27-APR-13:20 22.17 22.11 0.88
May 0.214091E+10 54.71 18088.36 08-MAY-12:10 1191263.14 15-MAY-15:10 23.01 22.73 4.51
June 0.598666E+10 135.63 18088.36 01-JUN-15:10 1277197.91 01-JUN-14:20 23.42 22.70 11.56
July 0.132837E+11 203.99 18088.36 01-JUL-15:30 1442386.20 20-JUL-15:30 24.27 23.35 16.82
August 0.928730E+10 145.04 18088.36 01-AUG-05:05 1202685.63 23-AUG-09:00 23.53 22.88 11.96
September 0.638711E+10 108.70 18088.36 01-SEP-07:10 1216595.32 25-SEP-16:00 23.28 22.76 9.26
October 0.156354E+10 24.17 18088.36 02-OCT-11:40 1089561.24 12-OCT-15:50 22.32 22.21 1.99
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 21.32 21.32 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 20.98 20.98 0.00
                   
Annual Sum or Average 0.388227E+11 682.57         22.35 22.07 4.78
Minimum of Months 0.00 0.00 0.00   0.00   20.98 20.98 0.00
Maximum of Months 0.132837E+11 203.99 18088.36   1442386.20   24.27 23.35 16.82



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.593691E+11 0.00 334.08 1159890.15 26-JAN-05:01 0.00 25.71 50.37 0.10 0.00 0.01 0.55 26-JAN-05:01
February 0.342231E+11 0.00 246.77 1066144.80 09-FEB-06:02 0.00 23.28 43.55 0.06 0.00 0.01 0.51 09-FEB-06:02
March 0.157172E+11 0.00 158.50 1090603.17 01-MAR-06:02 0.00 23.50 35.34 0.03 0.00 0.00 0.52 01-MAR-06:02
April 0.822596E+09 0.00 21.00 156668.83 11-APR-05:03 0.00 23.03 24.68 0.00 0.00 0.00 0.07 11-APR-05:03
May 0.00 0.00 0.00 0.00 01-MAY-00:02 0.00 22.49 22.49 0.00 0.00 0.00 0.00 01-MAY-00:02
June 0.00 0.00 0.00 0.00 01-JUN-00:05 0.00 22.49 22.49 0.00 0.00 0.00 0.00 01-JUN-00:05
July 0.00 0.00 0.00 0.00 01-JUL-00:02 0.00 22.49 22.49 0.00 0.00 0.00 0.00 01-JUL-00:02
August 0.00 0.00 0.00 0.00 01-AUG-00:05 0.00 22.49 22.49 0.00 0.00 0.00 0.00 01-AUG-00:05
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 22.49 22.49 0.00 0.00 0.00 0.00 01-SEP-00:05
October 0.336395E+09 0.00 44.80 36932.13 25-OCT-05:02 0.00 21.21 24.72 0.00 0.00 0.00 0.02 25-OCT-05:02
November 0.203927E+11 0.00 204.25 1123411.26 28-NOV-06:01 0.00 23.20 39.01 0.04 0.00 0.00 0.53 28-NOV-06:01
December 0.804793E+11 0.00 364.83 1130353.62 27-DEC-06:01 0.00 24.01 50.73 0.14 0.00 0.01 0.54 27-DEC-06:01
                           
Annual Sum or Average 0.211340E+12 0.00 1374.24     0.00 23.04 31.69 0.03 0.00 0.00    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 21.21 22.49 0.00 0.00 0.00 0.00  
Maximum of Months 0.804793E+11 0.00 364.83 1159890.15   0.00 25.71 50.73 0.14 0.00 0.01 0.55  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 22.18 22.18 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 25.90 25.90 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 30.21 30.21 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 39.29 39.29 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:02 0.00 30.54 30.54 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:05 0.00 39.15 39.15 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:02 0.00 43.45 43.45 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:05 0.00 46.64 46.64 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 30.21 30.21 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 29.89 29.89 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 29.55 29.55 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 31.22 31.22 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 33.23 33.23 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 22.18 22.18 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 46.64 46.64 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.290096E+10 0.00 55.62 0.290096E+10 0.00 0.00 0.00 0.00 47949.72 03-JAN-15:00 47949.72 03-JAN-15:00 0.00 0.00 0.00
February 0.103041E+11 0.00 120.76 0.103041E+11 0.00 0.00 0.00 0.00 79626.11 21-FEB-15:00 79626.11 21-FEB-15:00 0.00 0.00 0.00
March 0.257351E+11 0.00 231.11 0.257351E+11 0.00 0.00 0.00 0.00 94286.40 21-MAR-16:00 94286.40 21-MAR-16:00 0.00 0.00 0.00
April 0.739542E+11 0.00 451.29 0.739542E+11 0.00 0.00 0.00 0.00 126305.01 21-APR-14:30 126305.01 21-APR-14:30 0.00 0.00 0.00
May 0.106927E+12 0.00 506.76 0.106805E+12 0.00 0.00 0.00 0.00 148349.62 31-MAY-05:03 148349.62 31-MAY-05:03 0.00 0.00 0.00
June 0.147463E+12 0.00 586.14 0.147001E+12 0.00 0.00 0.00 0.00 163338.30 08-JUN-05:02 163338.30 08-JUN-05:02 0.00 0.00 0.00
July 0.178679E+12 0.00 622.57 0.151849E+12 0.00 0.00 0.00 0.00 306458.18 21-JUL-05:03 165656.34 03-JUL-04:12 0.00 0.00 0.00
August 0.171692E+12 0.00 655.09 0.160337E+12 0.00 0.00 0.00 0.00 258697.54 05-AUG-05:03 178188.83 07-AUG-05:02 0.00 0.00 0.00
September 0.114534E+12 0.00 480.22 0.106882E+12 0.00 0.00 0.00 0.00 263935.71 22-SEP-05:03 129039.14 18-SEP-15:40 0.00 0.00 0.00
October 0.638360E+11 0.00 369.82 0.619870E+11 0.00 0.00 0.00 0.00 149024.76 02-OCT-05:02 149024.76 02-OCT-05:02 0.00 0.00 0.00
November 0.184959E+11 0.00 175.06 0.184959E+11 0.00 0.00 0.00 0.00 89618.37 03-NOV-16:00 89618.37 03-NOV-16:00 0.00 0.00 0.00
December 0.129178E+10 0.00 41.62 0.129178E+10 0.00 0.00 0.00 0.00 27815.61 20-DEC-15:00 27815.61 20-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.915813E+12 0.00 4296.07 0.867542E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.129178E+10 0.00 41.62 0.129178E+10 0.00 0.00 0.00 0.00 27815.61   27815.61   0.00 0.00 0.00
Maximum of Months 0.178679E+12 0.00 655.09 0.160337E+12 0.00 0.00 0.00 0.00 306458.18   178188.83   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.224260E+11 0.00 106.62 0.224260E+11 0.00 0.00 0.00 0.00 379464.32 03-JAN-14:30 379464.32 03-JAN-14:30 0.00 0.00 0.00
February 0.797845E+11 0.00 146.46 0.797845E+11 0.00 0.00 0.00 0.00 579662.15 21-FEB-16:00 579662.15 21-FEB-16:00 0.00 0.00 0.00
March 0.191497E+12 0.00 234.19 0.191497E+12 0.00 0.00 0.00 0.00 739909.75 21-MAR-16:00 739909.75 21-MAR-16:00 0.00 0.00 0.00
April 0.527686E+12 0.00 356.87 0.527686E+12 0.00 0.00 0.00 0.00 1083524.15 21-APR-15:00 1083524.15 21-APR-15:00 0.00 0.00 0.00
May 0.943912E+12 0.00 478.22 0.942876E+12 0.00 0.00 0.00 0.00 1497340.78 31-MAY-03:02 1497340.78 31-MAY-03:02 0.00 0.00 0.00
June 0.126226E+13 0.00 514.97 0.125946E+13 0.00 0.00 0.00 0.00 1483895.43 15-JUN-05:02 1483895.43 15-JUN-05:02 0.00 0.00 0.00
July 0.140009E+13 0.00 518.95 0.120665E+13 0.00 0.00 0.00 0.00 2864410.75 21-JUL-05:03 1532319.84 03-JUL-05:02 0.00 0.00 0.00
August 0.122246E+13 0.00 522.53 0.115650E+13 0.00 0.00 0.00 0.00 2428632.70 03-AUG-05:03 1509173.36 07-AUG-05:02 0.00 0.00 0.00
September 0.979308E+12 0.00 443.48 0.916648E+12 0.00 0.00 0.00 0.00 2096271.61 22-SEP-03:02 1160171.53 20-SEP-15:40 0.00 0.00 0.00
October 0.512471E+12 0.00 348.93 0.497348E+12 0.00 0.00 0.00 0.00 1182754.51 03-OCT-14:00 1181894.12 02-OCT-05:02 0.00 0.00 0.00
November 0.138898E+12 0.00 182.91 0.138898E+12 0.00 0.00 0.00 0.00 710703.13 03-NOV-16:00 710703.13 03-NOV-16:00 0.00 0.00 0.00
December 0.824353E+10 0.00 93.11 0.824353E+10 0.00 0.00 0.00 0.00 178140.17 08-DEC-14:00 178140.17 08-DEC-14:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.728903E+13 0.00 3947.23 0.694802E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.824353E+10 0.00 93.11 0.824353E+10 0.00 0.00 0.00 0.00 178140.17   178140.17   0.00 0.00 0.00
Maximum of Months 0.140009E+13 0.00 522.53 0.125946E+13 0.00 0.00 0.00 0.00 2864410.75   1532319.84   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.163433E+10 0.00 48.12 0.163433E+10 0.00 0.00 0.00 0.00 29665.63 03-JAN-15:00 29665.63 03-JAN-15:00 0.00 0.00 0.00
February 0.661478E+10 0.00 104.37 0.661478E+10 0.00 0.00 0.00 0.00 52512.77 21-FEB-16:00 52512.77 21-FEB-16:00 0.00 0.00 0.00
March 0.174752E+11 0.00 202.17 0.174752E+11 0.00 0.00 0.00 0.00 78700.97 21-MAR-16:00 78700.97 21-MAR-16:00 0.00 0.00 0.00
April 0.566612E+11 0.00 345.85 0.566612E+11 0.00 0.00 0.00 0.00 127621.18 21-APR-15:00 127621.18 21-APR-15:00 0.00 0.00 0.00
May 0.104488E+12 0.00 469.57 0.104377E+12 0.00 0.00 0.00 0.00 156561.77 31-MAY-03:02 156561.77 31-MAY-03:02 0.00 0.00 0.00
June 0.144941E+12 0.00 524.26 0.144653E+12 0.00 0.00 0.00 0.00 158159.67 15-JUN-14:40 158159.67 15-JUN-14:40 0.00 0.00 0.00
July 0.158949E+12 0.00 529.50 0.138651E+12 0.00 0.00 0.00 0.00 304905.62 22-JUL-05:02 167660.24 03-JUL-04:12 0.00 0.00 0.00
August 0.136480E+12 0.00 525.87 0.129876E+12 0.00 0.00 0.00 0.00 242822.05 05-AUG-05:02 168065.10 07-AUG-05:02 0.00 0.00 0.00
September 0.106326E+12 0.00 437.34 0.100348E+12 0.00 0.00 0.00 0.00 220473.85 22-SEP-05:03 138270.65 20-SEP-15:40 0.00 0.00 0.00
October 0.520712E+11 0.00 335.28 0.507779E+11 0.00 0.00 0.00 0.00 138991.83 03-OCT-13:40 126329.70 05-OCT-16:00 0.00 0.00 0.00
November 0.114726E+11 0.00 153.74 0.114726E+11 0.00 0.00 0.00 0.00 72650.83 09-NOV-15:00 72650.83 09-NOV-15:00 0.00 0.00 0.00
December 0.561952E+09 0.00 29.83 0.561952E+09 0.00 0.00 0.00 0.00 12673.72 23-DEC-15:00 12673.72 23-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.797676E+12 0.00 3705.89 0.763103E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.561952E+09 0.00 29.83 0.561952E+09 0.00 0.00 0.00 0.00 12673.72   12673.72   0.00 0.00 0.00
Maximum of Months 0.158949E+12 0.00 529.50 0.144653E+12 0.00 0.00 0.00 0.00 304905.62   168065.10   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.130517E+10 0.00 26.87 0.130517E+10 0.00 0.00 0.00 0.00 33254.36 03-JAN-15:00 33254.36 03-JAN-15:00 0.00 0.00 0.00
February 0.456754E+10 0.00 55.76 0.456754E+10 0.00 0.00 0.00 0.00 55614.32 21-FEB-15:00 55614.32 21-FEB-15:00 0.00 0.00 0.00
March 0.123944E+11 0.00 141.90 0.123944E+11 0.00 0.00 0.00 0.00 54615.21 21-MAR-16:00 54615.21 21-MAR-16:00 0.00 0.00 0.00
April 0.368188E+11 0.00 266.89 0.368188E+11 0.00 0.00 0.00 0.00 77274.93 20-APR-05:03 77274.93 20-APR-05:03 0.00 0.00 0.00
May 0.636084E+11 0.00 378.67 0.635893E+11 0.00 0.00 0.00 0.00 115856.32 29-MAY-17:29 113616.69 29-MAY-17:29 0.00 0.00 0.00
June 0.807094E+11 0.00 413.71 0.806356E+11 0.00 0.00 0.00 0.00 121351.32 15-JUN-04:03 121351.32 15-JUN-04:03 0.00 0.00 0.00
July 0.936124E+11 0.00 415.73 0.828436E+11 0.00 0.00 0.00 0.00 181434.21 21-JUL-03:02 119167.75 03-JUL-03:03 0.00 0.00 0.00
August 0.918851E+11 0.00 464.70 0.884115E+11 0.00 0.00 0.00 0.00 174128.94 02-AUG-03:02 128116.29 27-AUG-16:20 0.00 0.00 0.00
September 0.735674E+11 0.00 390.39 0.709868E+11 0.00 0.00 0.00 0.00 161829.96 22-SEP-03:02 113824.20 17-SEP-15:46 0.00 0.00 0.00
October 0.409108E+11 0.00 290.41 0.404966E+11 0.00 0.00 0.00 0.00 125693.67 02-OCT-03:02 125693.67 02-OCT-03:02 0.00 0.00 0.00
November 0.106912E+11 0.00 126.21 0.106909E+11 0.00 0.00 0.00 0.00 63869.43 10-NOV-04:02 63869.43 10-NOV-04:02 0.00 0.00 0.00
December 0.224755E+09 0.00 11.22 0.224755E+09 0.00 0.00 0.00 0.00 17473.36 11-DEC-05:02 17473.36 11-DEC-05:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.510295E+12 0.00 2982.45 0.492965E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.224755E+09 0.00 11.22 0.224755E+09 0.00 0.00 0.00 0.00 17473.36   17473.36   0.00 0.00 0.00
Maximum of Months 0.936124E+11 0.00 464.70 0.884115E+11 0.00 0.00 0.00 0.00 181434.21   128116.29   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.379090E+12 0.961254E+11 744.00 0.342019E+12 0.370712E+11 0.00 0.37 03-JAN-15:00 0.34 28-JAN-07:10 145154.83 12-JAN-22:03 131374.74 03-JAN-17:00 14748.13 09-JAN-23:00 41741.21 03-JAN-17:00 0.00
February 0.584964E+12 0.144780E+12 672.00 0.529900E+12 0.550640E+11 0.00 0.61 21-FEB-16:00 0.56 01-FEB-07:10 246446.23 21-FEB-22:03 223230.59 21-FEB-16:00 25184.63 17-FEB-05:00 74881.82 20-FEB-16:00 0.00
March 0.913862E+12 0.227301E+12 744.00 0.834073E+12 0.797884E+11 0.00 0.98 31-MAR-24:00 0.77 01-MAR-07:10 443118.33 31-MAR-24:00 400824.48 31-MAR-24:00 42293.85 31-MAR-24:00 110648.25 21-MAR-16:00 0.00
April 0.112265E+13 0.319019E+12 720.00 0.104206E+13 0.805822E+11 0.00 1.00 01-APR-09:10 0.41 30-APR-24:00 457843.44 22-APR-03:13 412728.25 22-APR-03:17 48976.11 17-APR-19:40 158876.23 21-APR-15:00 0.00
May 0.373575E+12 0.122766E+12 744.00 0.350206E+12 0.233692E+11 0.00 0.60 31-MAY-23:23 0.35 06-MAY-06:10 228836.97 31-MAY-24:00 216940.29 31-MAY-24:00 14951.43 01-MAY-04:53 78352.18 31-MAY-23:20 0.00
June 0.600803E+12 0.220272E+12 720.00 0.577334E+12 0.234694E+11 0.00 0.82 30-JUN-23:32 0.58 01-JUN-06:10 319437.88 30-JUN-23:03 308451.19 30-JUN-24:00 23450.34 13-JUN-05:00 116694.45 30-JUN-23:20 0.00
July 0.875839E+12 0.318265E+12 744.00 0.843475E+12 0.323643E+11 0.00 1.00 31-JUL-23:02 0.81 05-JUL-06:10 410763.87 31-JUL-24:00 393547.75 31-JUL-24:00 28405.66 05-JUL-06:10 154957.05 03-JUL-16:00 0.00
August 0.114950E+13 0.382313E+12 744.00 0.107430E+13 0.751992E+11 0.00 1.00 01-AUG-00:05 0.43 31-AUG-24:00 454939.76 14-AUG-00:05 410187.00 13-AUG-24:00 49222.29 16-AUG-18:20 173387.53 07-AUG-16:10 0.00
September 0.369167E+12 0.119565E+12 720.00 0.344481E+12 0.246865E+11 0.00 0.58 30-SEP-23:40 0.35 30-SEP-06:10 240435.32 30-SEP-24:00 218779.07 30-SEP-24:00 21656.25 30-SEP-24:00 62010.66 01-SEP-15:10 0.00
October 0.650194E+12 0.181443E+12 744.00 0.597870E+12 0.523239E+11 0.00 0.79 31-OCT-23:40 0.58 11-OCT-06:10 346596.57 31-OCT-23:20 311734.45 31-OCT-24:00 35212.66 31-OCT-23:10 97345.78 03-OCT-14:10 0.00
November 0.897255E+12 0.217432E+12 720.00 0.813820E+12 0.834347E+11 0.00 0.83 03-NOV-16:00 0.78 17-NOV-07:10 352175.16 12-NOV-10:53 317316.11 03-NOV-16:00 36704.31 16-NOV-11:00 109163.99 03-NOV-16:00 0.00
December 0.120041E+13 0.271121E+12 744.00 0.108406E+13 0.116352E+12 0.00 1.00 01-DEC-13:00 0.98 30-DEC-07:10 455126.57 18-DEC-23:00 408603.67 10-DEC-18:40 47585.74 04-DEC-11:00 119425.25 10-DEC-15:00 0.00
                                       
Annual Sum or Average 0.911730E+13 0.262040E+13 8760.00 0.843360E+13 0.683705E+12 0.00                         0.00
Minimum of Months 0.369167E+12 0.961254E+11 672.00 0.342019E+12 0.233692E+11 0.00 0.37   0.34   145154.83   131374.74   14748.13   41741.21   0.00
Maximum of Months 0.120041E+13 0.382313E+12 744.00 0.108406E+13 0.116352E+12 0.00 1.00   0.98   457843.44   412728.25   49222.29   173387.53   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.490799E+10 0.132543E+10 744.00 0.489639E+10 11600516.96 0.00 0.31 30-JAN-17:00 0.15 28-JAN-08:00 2576.56 02-JAN-16:50 2519.33 02-JAN-16:50 71.08 02-JAN-12:10 724.95 03-JAN-17:00 0.00
February 0.933706E+10 0.246680E+10 672.00 0.932322E+10 13841680.94 0.00 0.58 21-FEB-17:00 0.39 01-FEB-07:50 4578.68 20-FEB-17:20 4578.68 20-FEB-17:20 221.39 13-FEB-16:20 1469.37 21-FEB-17:00 0.00
March 0.157651E+11 0.414691E+10 744.00 0.157619E+11 3144292.12 0.00 0.89 31-MAR-24:00 0.59 01-MAR-07:05 7749.18 31-MAR-24:00 7749.18 31-MAR-24:00 112.34 11-MAR-10:20 2213.09 21-MAR-16:00 0.00
April 0.205189E+11 0.623508E+10 720.00 0.205052E+11 13757694.25 0.00 1.00 01-APR-12:10 0.34 30-APR-24:00 8412.83 28-APR-16:00 8384.61 22-APR-18:12 135.85 18-APR-09:10 3301.62 21-APR-15:00 0.00
May 0.634470E+10 0.212990E+10 744.00 0.628948E+10 55225043.71 0.00 0.52 31-MAY-23:23 0.22 06-MAY-06:20 4112.62 31-MAY-23:40 4112.62 31-MAY-23:40 248.41 24-MAY-13:00 1413.19 31-MAY-23:23 0.00
June 0.112088E+11 0.414719E+10 720.00 0.111094E+11 99357062.34 0.00 0.74 30-JUN-23:23 0.47 13-JUN-06:05 5948.68 30-JUN-23:55 5948.68 30-JUN-23:55 308.82 19-JUN-18:00 2343.42 02-JUN-16:00 0.00
July 0.168267E+11 0.606573E+10 744.00 0.165066E+11 0.320091E+09 0.00 0.94 31-JUL-23:23 0.69 05-JUL-06:10 7880.39 31-JUL-23:57 7870.04 31-JUL-23:57 620.48 20-JUL-15:00 3103.63 03-JUL-16:00 0.00
August 0.219819E+11 0.768479E+10 744.00 0.217134E+11 0.268510E+09 0.00 1.00 01-AUG-10:00 0.34 31-AUG-24:00 8677.19 08-AUG-17:00 8509.59 27-AUG-20:54 472.74 01-AUG-21:00 3604.64 07-AUG-16:10 0.00
September 0.635934E+10 0.207242E+10 720.00 0.615942E+10 0.199922E+09 0.00 0.49 30-SEP-23:40 0.22 30-SEP-06:40 4124.13 30-SEP-24:00 4124.13 30-SEP-24:00 352.15 14-SEP-10:30 1229.03 01-SEP-16:00 0.00
October 0.112737E+11 0.320373E+10 744.00 0.111345E+11 0.139285E+09 0.00 0.69 31-OCT-24:00 0.43 25-OCT-07:00 5928.42 31-OCT-24:00 5928.42 31-OCT-24:00 361.97 04-OCT-10:00 1927.92 03-OCT-14:10 0.00
November 0.153093E+11 0.387032E+10 720.00 0.152752E+11 34081698.85 0.00 0.79 19-NOV-16:43 0.60 28-NOV-07:10 6676.82 09-NOV-16:40 6576.75 09-NOV-16:40 201.20 01-NOV-11:10 2115.68 03-NOV-16:00 0.00
December 0.204914E+11 0.492414E+10 744.00 0.204863E+11 5102647.72 0.00 0.97 20-DEC-16:20 0.79 05-DEC-07:10 8197.17 15-DEC-16:40 8197.17 15-DEC-16:40 100.73 14-DEC-17:05 2339.24 20-DEC-15:00 0.00
                                       
Annual Sum or Average 0.160325E+12 0.482724E+11 8760.00 0.159161E+12 0.116392E+10 0.00                         0.00
Minimum of Months 0.490799E+10 0.132543E+10 672.00 0.489639E+10 3144292.12 0.00 0.31   0.15   2576.56   2519.33   71.08   724.95   0.00
Maximum of Months 0.219819E+11 0.768479E+10 744.00 0.217134E+11 0.320091E+09 0.00 1.00   0.79   8677.19   8509.59   620.48   3604.64   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.332493E+11 0.923621E+10 744.00 0.331391E+11 0.110209E+09 0.00 0.29 30-JAN-17:00 0.07 28-JAN-07:05 22631.21 12-JAN-16:50 22095.87 30-JAN-17:00 658.19 12-JAN-17:05 6508.89 03-JAN-17:00 0.00
February 0.787024E+11 0.210572E+11 672.00 0.785641E+11 0.138286E+09 0.00 0.57 21-FEB-17:00 0.32 02-FEB-07:10 42380.37 21-FEB-17:00 42380.37 21-FEB-17:00 2173.12 13-FEB-16:20 13681.68 21-FEB-17:00 0.00
March 0.142329E+12 0.377446E+11 744.00 0.142297E+12 31821947.64 0.00 0.87 31-MAR-24:00 0.54 01-MAR-07:05 71955.67 31-MAR-24:00 71955.67 31-MAR-24:00 1112.59 11-MAR-10:20 20881.74 21-MAR-16:00 0.00
April 0.192834E+12 0.588001E+11 720.00 0.192693E+12 0.140625E+09 0.00 1.00 01-APR-13:50 0.30 30-APR-24:00 79805.85 28-APR-16:00 79552.38 27-APR-17:50 1356.58 18-APR-09:10 31428.34 21-APR-15:00 0.00
May 0.587811E+11 0.198195E+11 744.00 0.582314E+11 0.549783E+09 0.00 0.53 31-MAY-23:53 0.20 06-MAY-06:30 40138.82 31-MAY-23:55 40138.82 31-MAY-23:55 2479.25 24-MAY-13:00 13684.69 31-MAY-23:23 0.00
June 0.106901E+12 0.395451E+11 720.00 0.105909E+12 0.992748E+09 0.00 0.75 30-JUN-23:20 0.46 29-JUN-06:10 57700.38 30-JUN-23:55 57700.38 30-JUN-23:55 3054.98 28-JUN-11:00 22382.72 02-JUN-16:00 0.00
July 0.160582E+12 0.578476E+11 744.00 0.157385E+12 0.319698E+10 0.00 0.95 31-JUL-23:12 0.69 05-JUL-06:10 76002.77 31-JUL-23:57 75898.82 31-JUL-23:57 6175.18 20-JUL-15:00 29546.13 03-JUL-16:00 0.00
August 0.206590E+12 0.724544E+11 744.00 0.203899E+12 0.269108E+10 0.00 1.00 01-AUG-10:00 0.30 31-AUG-24:00 82309.29 08-AUG-17:00 79623.67 31-AUG-18:10 4657.05 01-AUG-21:00 34303.52 07-AUG-16:10 0.00
September 0.584310E+11 0.191217E+11 720.00 0.564518E+11 0.197921E+10 0.00 0.49 30-SEP-23:40 0.20 30-SEP-07:00 38884.68 30-SEP-24:00 38884.68 30-SEP-24:00 3504.02 14-SEP-10:30 11376.52 19-SEP-16:00 0.00
October 0.102330E+12 0.292825E+11 744.00 0.100944E+12 0.138611E+10 0.00 0.67 31-OCT-24:00 0.39 25-OCT-07:00 54380.56 31-OCT-24:00 54380.56 31-OCT-24:00 3615.26 04-OCT-10:00 18283.14 03-OCT-14:10 0.00
November 0.135307E+12 0.345570E+11 720.00 0.134966E+12 0.341048E+09 0.00 0.77 09-NOV-16:40 0.52 28-NOV-07:10 62766.27 09-NOV-16:50 61759.45 09-NOV-16:50 2009.09 01-NOV-11:10 19880.45 03-NOV-16:00 0.00
December 0.179634E+12 0.436735E+11 744.00 0.179581E+12 52838326.84 0.00 0.95 20-DEC-16:30 0.71 27-DEC-07:10 76443.66 15-DEC-16:50 76443.66 15-DEC-16:50 994.52 14-DEC-17:05 21650.04 20-DEC-15:10 0.00
                                       
Annual Sum or Average 0.145567E+13 0.443139E+12 8760.00 0.144406E+13 0.116107E+11 0.00                         0.00
Minimum of Months 0.332493E+11 0.923621E+10 672.00 0.331391E+11 31821947.64 0.00 0.29   0.07   22631.21   22095.87   658.19   6508.89   0.00
Maximum of Months 0.206590E+12 0.724544E+11 744.00 0.203899E+12 0.319698E+10 0.00 1.00   0.71   82309.29   79623.67   6175.18   34303.52   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.174049E+10 0.502485E+09 605.56 0.173116E+10 9326663.93 0.00 0.29 12-JAN-16:40 0.00 01-JAN-06:15 2266.08 12-JAN-16:50 2205.99 12-JAN-16:40 65.33 12-JAN-17:05 626.96 03-JAN-17:00 0.00
February 0.669791E+10 0.182205E+10 672.00 0.668437E+10 13540247.74 0.00 0.56 21-FEB-17:00 0.20 02-FEB-07:10 4231.50 21-FEB-17:00 4231.50 21-FEB-17:00 214.23 13-FEB-17:00 1367.95 21-FEB-17:00 0.00
March 0.133486E+11 0.358028E+10 744.00 0.133454E+11 3136714.46 0.00 0.83 31-MAR-23:30 0.44 02-MAR-07:10 6889.75 31-MAR-23:20 6889.75 31-MAR-23:20 109.92 11-MAR-10:20 2101.53 21-MAR-16:00 0.00
April 0.190431E+11 0.584055E+10 720.00 0.190291E+11 13982697.94 0.00 1.00 01-APR-14:30 0.29 30-APR-24:00 8092.21 28-APR-16:00 8050.25 28-APR-16:00 135.49 18-APR-09:10 3180.06 21-APR-15:00 0.00
May 0.586656E+10 0.198916E+10 744.00 0.581154E+10 55012409.96 0.00 0.52 31-MAY-23:53 0.15 02-MAY-06:40 4054.75 31-MAY-23:55 4054.75 31-MAY-23:55 250.91 24-MAY-13:00 1382.88 31-MAY-23:23 0.00
June 0.107995E+11 0.400150E+10 720.00 0.107002E+11 99317463.93 0.00 0.75 30-JUN-23:55 0.44 13-JUN-06:05 5796.24 30-JUN-23:55 5796.24 30-JUN-23:55 306.57 28-JUN-11:00 2283.91 02-JUN-16:00 0.00
July 0.162031E+11 0.584422E+10 744.00 0.158834E+11 0.319735E+09 0.00 0.95 31-JUL-23:10 0.67 05-JUL-06:10 7622.99 31-JUL-23:57 7612.57 31-JUL-23:57 618.03 20-JUL-15:00 3050.50 02-JUL-16:00 0.00
August 0.207331E+11 0.728429E+10 744.00 0.204640E+11 0.269103E+09 0.00 1.00 01-AUG-10:40 0.30 31-AUG-24:00 8325.70 08-AUG-17:00 8077.21 27-AUG-20:14 465.42 01-AUG-21:00 3471.22 07-AUG-16:10 0.00
September 0.582139E+10 0.191512E+10 720.00 0.562330E+10 0.198092E+09 0.00 0.47 30-SEP-23:20 0.16 30-SEP-07:00 3772.18 30-SEP-23:30 3772.18 30-SEP-23:30 355.81 14-SEP-10:30 1172.75 19-SEP-16:00 0.00
October 0.979080E+10 0.282881E+10 744.00 0.965268E+10 0.138115E+09 0.00 0.62 31-OCT-23:40 0.32 25-OCT-07:00 5113.80 31-OCT-23:30 5113.80 31-OCT-23:30 361.69 04-OCT-10:00 1857.43 03-OCT-14:10 0.00
November 0.122870E+11 0.318290E+10 720.00 0.122531E+11 33930989.34 0.00 0.77 09-NOV-16:40 0.37 27-NOV-04:01 6310.87 09-NOV-16:50 6210.23 09-NOV-16:50 200.07 01-NOV-11:10 1997.48 03-NOV-16:00 0.00
December 0.161053E+11 0.397538E+10 744.00 0.161001E+11 5211471.30 0.00 0.93 20-DEC-16:30 0.57 04-DEC-04:13 7560.71 15-DEC-16:50 7560.71 15-DEC-16:50 98.58 14-DEC-17:05 2117.89 20-DEC-16:00 0.00
                                       
Annual Sum or Average 0.138437E+12 0.427668E+11 8621.56 0.137278E+12 0.115850E+10 0.00                         0.00
Minimum of Months 0.174049E+10 0.502485E+09 605.56 0.173116E+10 3136714.46 0.00 0.29   0.00   2266.08   2205.99   65.33   626.96   0.00
Maximum of Months 0.207331E+11 0.728429E+10 744.00 0.204640E+11 0.319735E+09 0.00 1.00   0.67   8325.70   8077.21   618.03   3471.22   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.11 0.00 77.11 7.78 478.79 0.00 0.00 0.00
February 94.16 0.00 94.16 30.81 424.80 0.00 0.00 0.00
March 123.22 0.00 123.22 71.95 357.12 0.00 0.00 0.00
April 142.27 1.12 141.15 154.82 202.76 0.00 0.00 0.00
May 168.74 12.20 156.54 270.52 114.86 0.00 0.00 0.00
June 179.43 22.09 157.34 382.54 57.80 0.00 0.00 0.00
July 165.83 16.14 149.68 351.58 45.54 0.00 0.00 0.00
August 139.83 2.86 136.97 269.25 65.47 0.00 0.00 0.00
September 122.01 0.05 121.96 204.46 136.51 0.00 0.00 0.00
October 101.30 0.00 101.30 99.44 230.88 0.00 0.00 0.00
November 81.78 0.00 81.78 18.64 414.69 0.00 0.00 0.00
December 76.51 0.00 76.51 4.54 544.52 0.00 0.00 0.00
                 
Annual Sum or Average 122.82 4.56 118.26 156.17 255.34 0.00 0.00 0.00
Minimum of Months 76.51 0.00 76.51 4.54 45.54 0.00 0.00 0.00
Maximum of Months 179.43 22.09 157.34 382.54 544.52 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.11 0.00 77.11 7.78 478.79 0.00 0.00 0.00
February 94.16 0.00 94.16 30.81 424.80 0.00 0.00 0.00
March 123.22 0.00 123.22 71.95 357.12 0.00 0.00 0.00
April 142.27 1.12 141.15 154.82 202.76 0.00 0.00 0.00
May 168.74 12.20 156.54 270.52 114.86 0.00 0.00 0.00
June 179.43 22.09 157.34 382.54 57.80 0.00 0.00 0.00
July 165.82 16.14 149.68 351.57 45.54 0.00 0.00 0.00
August 139.83 2.86 136.97 269.25 65.47 0.00 0.00 0.00
September 122.01 0.05 121.96 204.46 136.51 0.00 0.00 0.00
October 101.30 0.00 101.30 99.44 230.88 0.00 0.00 0.00
November 81.78 0.00 81.78 18.64 414.69 0.00 0.00 0.00
December 76.51 0.00 76.51 4.54 544.51 0.00 0.00 0.00
                 
Annual Sum or Average 122.82 4.56 118.26 156.17 255.34 0.00 0.00 0.00
Minimum of Months 76.51 0.00 76.51 4.54 45.54 0.00 0.00 0.00
Maximum of Months 179.43 22.09 157.34 382.54 544.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.11 0.00 77.11 7.78 478.79 0.00 0.00 0.00
February 94.16 0.00 94.16 30.81 424.80 0.00 0.00 0.00
March 123.22 0.00 123.22 71.95 357.12 0.00 0.00 0.00
April 142.27 1.12 141.15 154.82 202.76 0.00 0.00 0.00
May 168.74 12.20 156.54 270.52 114.86 0.00 0.00 0.00
June 179.43 22.09 157.34 382.54 57.80 0.00 0.00 0.00
July 165.82 16.14 149.68 351.57 45.54 0.00 0.00 0.00
August 139.83 2.86 136.97 269.25 65.47 0.00 0.00 0.00
September 122.01 0.05 121.96 204.46 136.51 0.00 0.00 0.00
October 101.30 0.00 101.30 99.44 230.88 0.00 0.00 0.00
November 81.78 0.00 81.78 18.64 414.69 0.00 0.00 0.00
December 76.51 0.00 76.51 4.54 544.52 0.00 0.00 0.00
                 
Annual Sum or Average 122.82 4.56 118.26 156.17 255.34 0.00 0.00 0.00
Minimum of Months 76.51 0.00 76.51 4.54 45.54 0.00 0.00 0.00
Maximum of Months 179.43 22.09 157.34 382.54 544.52 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.11 0.00 77.11 7.78 478.79 0.00 0.00 0.00
February 94.16 0.00 94.16 30.81 424.80 0.00 0.00 0.00
March 123.22 0.00 123.22 71.95 357.12 0.00 0.00 0.00
April 142.27 1.12 141.15 154.82 202.76 0.00 0.00 0.00
May 168.74 12.20 156.54 270.52 114.86 0.00 0.00 0.00
June 179.43 22.09 157.34 382.54 57.80 0.00 0.00 0.00
July 165.82 16.14 149.68 351.57 45.54 0.00 0.00 0.00
August 139.83 2.86 136.97 269.25 65.47 0.00 0.00 0.00
September 122.01 0.05 121.96 204.46 136.51 0.00 0.00 0.00
October 101.30 0.00 101.30 99.44 230.88 0.00 0.00 0.00
November 81.78 0.00 81.78 18.64 414.69 0.00 0.00 0.00
December 76.51 0.00 76.51 4.54 544.51 0.00 0.00 0.00
                 
Annual Sum or Average 122.82 4.56 118.26 156.17 255.34 0.00 0.00 0.00
Minimum of Months 76.51 0.00 76.51 4.54 45.54 0.00 0.00 0.00
Maximum of Months 179.43 22.09 157.34 382.54 544.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.10 0.00 77.10 7.78 478.77 0.00 0.00 0.00
February 94.15 0.00 94.15 30.81 424.78 0.00 0.00 0.00
March 123.22 0.00 123.22 71.95 357.11 0.00 0.00 0.00
April 142.27 1.12 141.15 154.82 202.76 0.00 0.00 0.00
May 168.73 12.20 156.53 270.51 114.86 0.00 0.00 0.00
June 179.42 22.09 157.33 382.52 57.79 0.00 0.00 0.00
July 165.82 16.14 149.68 351.56 45.53 0.00 0.00 0.00
August 139.82 2.86 136.96 269.24 65.47 0.00 0.00 0.00
September 122.01 0.05 121.96 204.46 136.50 0.00 0.00 0.00
October 101.30 0.00 101.30 99.44 230.87 0.00 0.00 0.00
November 81.78 0.00 81.78 18.64 414.68 0.00 0.00 0.00
December 76.51 0.00 76.51 4.54 544.49 0.00 0.00 0.00
                 
Annual Sum or Average 122.82 4.56 118.25 156.17 255.33 0.00 0.00 0.00
Minimum of Months 76.51 0.00 76.51 4.54 45.53 0.00 0.00 0.00
Maximum of Months 179.42 22.09 157.33 382.52 544.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 229.15 124.31 104.85 206.59 480.03 0.00 0.00 0.00
February 306.59 174.75 131.83 330.50 422.34 0.00 0.00 0.00
March 378.53 208.56 169.97 452.84 353.14 0.00 0.00 0.00
April 456.11 253.04 203.07 663.12 201.26 0.00 0.00 0.00
May 470.68 255.80 214.88 775.70 126.01 0.00 0.00 0.00
June 470.95 262.00 208.95 882.86 59.38 0.00 0.00 0.00
July 422.34 220.79 201.55 796.79 45.10 0.00 0.00 0.00
August 401.88 205.68 196.20 728.82 62.85 0.00 0.00 0.00
September 398.15 227.17 170.98 669.09 140.52 0.00 0.00 0.00
October 306.20 165.26 140.95 428.10 236.41 0.00 0.00 0.00
November 274.48 159.80 114.69 289.85 406.15 0.00 0.00 0.00
December 228.96 121.31 107.65 193.00 529.82 0.00 0.00 0.00
                 
Annual Sum or Average 362.04 198.10 163.94 535.45 254.46 0.00 0.00 0.00
Minimum of Months 228.96 121.31 104.85 193.00 45.10 0.00 0.00 0.00
Maximum of Months 470.95 262.00 214.88 882.86 529.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 229.15 124.31 104.85 206.59 480.03 0.00 0.00 0.00
February 306.59 174.75 131.83 330.50 422.34 0.00 0.00 0.00
March 378.53 208.56 169.97 452.84 353.14 0.00 0.00 0.00
April 456.11 253.04 203.07 663.12 201.26 0.00 0.00 0.00
May 470.68 255.80 214.88 775.70 126.01 0.00 0.00 0.00
June 470.95 262.00 208.95 882.86 59.38 0.00 0.00 0.00
July 422.34 220.79 201.55 796.79 45.10 0.00 0.00 0.00
August 401.88 205.68 196.20 728.82 62.85 0.00 0.00 0.00
September 398.15 227.17 170.98 669.09 140.52 0.00 0.00 0.00
October 306.20 165.26 140.95 428.10 236.41 0.00 0.00 0.00
November 274.48 159.80 114.69 289.85 406.15 0.00 0.00 0.00
December 228.96 121.31 107.65 193.00 529.82 0.00 0.00 0.00
                 
Annual Sum or Average 362.04 198.10 163.94 535.45 254.46 0.00 0.00 0.00
Minimum of Months 228.96 121.31 104.85 193.00 45.10 0.00 0.00 0.00
Maximum of Months 470.95 262.00 214.88 882.86 529.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 229.15 124.31 104.84 206.59 480.02 0.00 0.00 0.00
February 306.58 174.75 131.83 330.49 422.33 0.00 0.00 0.00
March 378.53 208.56 169.97 452.83 353.14 0.00 0.00 0.00
April 456.10 253.04 203.07 663.10 201.26 0.00 0.00 0.00
May 470.68 255.79 214.88 775.68 126.01 0.00 0.00 0.00
June 470.94 261.99 208.95 882.84 59.38 0.00 0.00 0.00
July 422.33 220.79 201.54 796.77 45.10 0.00 0.00 0.00
August 401.87 205.67 196.20 728.80 62.85 0.00 0.00 0.00
September 398.14 227.17 170.97 669.08 140.52 0.00 0.00 0.00
October 306.20 165.25 140.95 428.09 236.40 0.00 0.00 0.00
November 274.48 159.79 114.69 289.85 406.14 0.00 0.00 0.00
December 228.95 121.30 107.65 193.00 529.81 0.00 0.00 0.00
                 
Annual Sum or Average 362.04 198.09 163.94 535.44 254.46 0.00 0.00 0.00
Minimum of Months 228.95 121.30 104.84 193.00 45.10 0.00 0.00 0.00
Maximum of Months 470.94 261.99 214.88 882.84 529.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 527.48 399.62 127.86 693.06 419.37 0.00 0.00 0.00
February 489.30 344.95 144.35 654.05 380.06 0.00 0.00 0.00
March 397.66 229.29 168.37 547.12 336.51 0.00 0.00 0.00
April 269.61 100.60 169.01 422.35 208.16 0.00 0.00 0.00
May 190.53 26.67 163.86 336.21 123.03 0.00 0.00 0.00
June 164.38 10.43 153.95 362.05 59.04 0.00 0.00 0.00
July 167.57 15.53 152.04 365.86 47.10 0.00 0.00 0.00
August 213.60 56.54 157.06 434.04 69.20 0.00 0.00 0.00
September 333.41 173.22 160.19 616.16 141.52 0.00 0.00 0.00
October 453.01 306.26 146.74 710.10 225.72 0.00 0.00 0.00
November 545.15 415.61 129.54 751.77 365.14 0.00 0.00 0.00
December 540.26 405.55 134.72 690.77 458.07 0.00 0.00 0.00
                 
Annual Sum or Average 356.91 206.24 150.67 547.88 235.36 0.00 0.00 0.00
Minimum of Months 164.38 10.43 127.86 336.21 47.10 0.00 0.00 0.00
Maximum of Months 545.15 415.61 169.01 751.77 458.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 527.48 399.62 127.86 693.05 419.37 0.00 0.00 0.00
February 489.30 344.95 144.35 654.04 380.06 0.00 0.00 0.00
March 397.66 229.29 168.37 547.11 336.51 0.00 0.00 0.00
April 269.61 100.60 169.01 422.35 208.16 0.00 0.00 0.00
May 190.53 26.67 163.86 336.20 123.02 0.00 0.00 0.00
June 164.38 10.43 153.95 362.05 59.04 0.00 0.00 0.00
July 167.57 15.53 152.03 365.86 47.10 0.00 0.00 0.00
August 213.60 56.54 157.06 434.04 69.20 0.00 0.00 0.00
September 333.41 173.22 160.19 616.16 141.52 0.00 0.00 0.00
October 453.00 306.26 146.74 710.09 225.72 0.00 0.00 0.00
November 545.15 415.61 129.54 751.77 365.13 0.00 0.00 0.00
December 540.26 405.54 134.72 690.76 458.07 0.00 0.00 0.00
                 
Annual Sum or Average 356.90 206.24 150.67 547.87 235.36 0.00 0.00 0.00
Minimum of Months 164.38 10.43 127.86 336.20 47.10 0.00 0.00 0.00
Maximum of Months 545.15 415.61 169.01 751.77 458.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 527.48 399.62 127.86 693.06 419.37 0.00 0.00 0.00
February 489.30 344.95 144.35 654.05 380.06 0.00 0.00 0.00
March 397.66 229.29 168.37 547.12 336.51 0.00 0.00 0.00
April 269.61 100.60 169.01 422.35 208.16 0.00 0.00 0.00
May 190.53 26.67 163.86 336.21 123.03 0.00 0.00 0.00
June 164.38 10.43 153.95 362.05 59.04 0.00 0.00 0.00
July 167.57 15.53 152.04 365.86 47.10 0.00 0.00 0.00
August 213.60 56.54 157.06 434.04 69.20 0.00 0.00 0.00
September 333.41 173.22 160.19 616.16 141.52 0.00 0.00 0.00
October 453.01 306.26 146.74 710.10 225.72 0.00 0.00 0.00
November 545.15 415.61 129.54 751.77 365.14 0.00 0.00 0.00
December 540.26 405.55 134.72 690.77 458.07 0.00 0.00 0.00
                 
Annual Sum or Average 356.91 206.24 150.67 547.88 235.36 0.00 0.00 0.00
Minimum of Months 164.38 10.43 127.86 336.21 47.10 0.00 0.00 0.00
Maximum of Months 545.15 415.61 169.01 751.77 458.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 527.48 399.62 127.86 693.05 419.37 0.00 0.00 0.00
February 489.30 344.95 144.35 654.04 380.06 0.00 0.00 0.00
March 397.66 229.29 168.37 547.11 336.51 0.00 0.00 0.00
April 269.61 100.60 169.01 422.35 208.16 0.00 0.00 0.00
May 190.53 26.67 163.86 336.20 123.02 0.00 0.00 0.00
June 164.38 10.43 153.95 362.05 59.04 0.00 0.00 0.00
July 167.57 15.53 152.03 365.86 47.10 0.00 0.00 0.00
August 213.60 56.54 157.06 434.04 69.20 0.00 0.00 0.00
September 333.41 173.22 160.19 616.16 141.52 0.00 0.00 0.00
October 453.00 306.26 146.74 710.09 225.72 0.00 0.00 0.00
November 545.15 415.61 129.54 751.77 365.13 0.00 0.00 0.00
December 540.26 405.54 134.72 690.76 458.07 0.00 0.00 0.00
                 
Annual Sum or Average 356.90 206.24 150.67 547.87 235.36 0.00 0.00 0.00
Minimum of Months 164.38 10.43 127.86 336.20 47.10 0.00 0.00 0.00
Maximum of Months 545.15 415.61 169.01 751.77 458.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 527.46 399.61 127.86 693.02 419.35 0.00 0.00 0.00
February 489.28 344.93 144.35 654.02 380.04 0.00 0.00 0.00
March 397.64 229.28 168.36 547.09 336.50 0.00 0.00 0.00
April 269.60 100.59 169.01 422.33 208.15 0.00 0.00 0.00
May 190.52 26.67 163.86 336.19 123.02 0.00 0.00 0.00
June 164.38 10.43 153.95 362.03 59.04 0.00 0.00 0.00
July 167.56 15.53 152.03 365.84 47.09 0.00 0.00 0.00
August 213.59 56.54 157.06 434.03 69.20 0.00 0.00 0.00
September 333.40 173.21 160.19 616.13 141.52 0.00 0.00 0.00
October 452.99 306.25 146.74 710.07 225.71 0.00 0.00 0.00
November 545.13 415.59 129.54 751.74 365.12 0.00 0.00 0.00
December 540.24 405.53 134.71 690.74 458.05 0.00 0.00 0.00
                 
Annual Sum or Average 356.89 206.23 150.66 547.85 235.35 0.00 0.00 0.00
Minimum of Months 164.38 10.43 127.86 336.19 47.09 0.00 0.00 0.00
Maximum of Months 545.13 415.59 169.01 751.74 458.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.39 135.94 105.44 246.71 533.76 0.00 0.00 0.00
February 272.38 144.78 127.60 296.98 494.54 0.00 0.00 0.00
March 371.18 198.94 172.24 451.79 431.25 0.00 0.00 0.00
April 426.64 230.43 196.20 615.61 270.05 0.00 0.00 0.00
May 459.53 245.87 213.66 762.17 156.03 0.00 0.00 0.00
June 447.32 240.26 207.06 835.07 83.64 0.00 0.00 0.00
July 396.96 197.26 199.70 737.78 71.76 0.00 0.00 0.00
August 384.44 195.92 188.51 677.01 108.05 0.00 0.00 0.00
September 393.15 219.02 174.12 671.24 173.51 0.00 0.00 0.00
October 338.43 197.52 140.91 490.74 285.81 0.00 0.00 0.00
November 284.07 172.97 111.10 328.59 490.36 0.00 0.00 0.00
December 228.92 124.35 104.56 211.65 634.46 0.00 0.00 0.00
                 
Annual Sum or Average 353.99 192.07 161.93 528.07 310.22 0.00 0.00 0.00
Minimum of Months 228.92 124.35 104.56 211.65 71.76 0.00 0.00 0.00
Maximum of Months 459.53 245.87 213.66 835.07 634.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.39 135.94 105.44 246.71 533.76 0.00 0.00 0.00
February 272.38 144.78 127.60 296.98 494.54 0.00 0.00 0.00
March 371.18 198.94 172.24 451.79 431.25 0.00 0.00 0.00
April 426.64 230.43 196.20 615.61 270.05 0.00 0.00 0.00
May 459.53 245.87 213.66 762.17 156.03 0.00 0.00 0.00
June 447.32 240.26 207.06 835.07 83.64 0.00 0.00 0.00
July 396.96 197.26 199.70 737.78 71.76 0.00 0.00 0.00
August 384.44 195.92 188.51 677.01 108.05 0.00 0.00 0.00
September 393.15 219.02 174.12 671.24 173.51 0.00 0.00 0.00
October 338.43 197.52 140.91 490.74 285.81 0.00 0.00 0.00
November 284.07 172.97 111.10 328.59 490.36 0.00 0.00 0.00
December 228.92 124.35 104.56 211.65 634.46 0.00 0.00 0.00
                 
Annual Sum or Average 353.99 192.07 161.93 528.07 310.22 0.00 0.00 0.00
Minimum of Months 228.92 124.35 104.56 211.65 71.76 0.00 0.00 0.00
Maximum of Months 459.53 245.87 213.66 835.07 634.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.38 135.94 105.44 246.70 533.75 0.00 0.00 0.00
February 272.38 144.77 127.60 296.97 494.53 0.00 0.00 0.00
March 371.17 198.93 172.24 451.79 431.24 0.00 0.00 0.00
April 426.63 230.43 196.20 615.60 270.05 0.00 0.00 0.00
May 459.52 245.86 213.66 762.16 156.03 0.00 0.00 0.00
June 447.31 240.25 207.05 835.05 83.64 0.00 0.00 0.00
July 396.95 197.25 199.70 737.76 71.75 0.00 0.00 0.00
August 384.43 195.92 188.51 677.00 108.05 0.00 0.00 0.00
September 393.14 219.02 174.12 671.23 173.51 0.00 0.00 0.00
October 338.43 197.52 140.91 490.73 285.80 0.00 0.00 0.00
November 284.06 172.96 111.10 328.59 490.36 0.00 0.00 0.00
December 228.91 124.35 104.56 211.65 634.44 0.00 0.00 0.00
                 
Annual Sum or Average 353.99 192.06 161.92 528.06 310.21 0.00 0.00 0.00
Minimum of Months 228.91 124.35 104.56 211.65 71.75 0.00 0.00 0.00
Maximum of Months 459.52 245.86 213.66 835.05 634.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 385.54 0.00 385.54 71.86 2138.49 0.00 0.00 0.00
February 470.79 0.00 470.79 202.31 1909.23 0.00 0.00 0.00
March 616.11 0.00 616.11 412.80 1617.12 0.00 0.00 0.00
April 711.37 5.60 705.76 816.42 948.90 0.00 0.00 0.00
May 843.71 61.01 782.69 1369.40 555.20 0.00 0.00 0.00
June 897.14 110.45 786.69 1928.61 296.47 0.00 0.00 0.00
July 829.13 80.71 748.42 1777.12 235.11 0.00 0.00 0.00
August 699.14 14.30 684.84 1383.27 320.30 0.00 0.00 0.00
September 610.06 0.24 609.81 1041.70 657.63 0.00 0.00 0.00
October 506.52 0.00 506.52 537.08 1053.15 0.00 0.00 0.00
November 408.91 0.00 408.91 138.75 1820.59 0.00 0.00 0.00
December 382.56 0.00 382.56 48.19 2372.37 0.00 0.00 0.00
                 
Annual Sum or Average 614.11 22.81 591.30 813.75 1156.74 0.00 0.00 0.00
Minimum of Months 382.56 0.00 382.56 48.19 235.11 0.00 0.00 0.00
Maximum of Months 897.14 110.45 786.69 1928.61 2372.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 687.45 372.92 314.53 645.18 1316.96 0.00 0.00 0.00
February 919.75 524.25 395.50 1011.70 1177.97 0.00 0.00 0.00
March 1135.59 625.67 509.91 1365.94 1005.59 0.00 0.00 0.00
April 1368.33 759.12 609.21 1973.55 609.77 0.00 0.00 0.00
May 1412.04 767.39 644.65 2312.18 376.61 0.00 0.00 0.00
June 1412.83 785.99 626.85 2631.59 195.64 0.00 0.00 0.00
July 1267.00 662.37 604.64 2373.22 157.55 0.00 0.00 0.00
August 1205.62 617.03 588.60 2171.98 213.76 0.00 0.00 0.00
September 1194.44 681.52 512.93 1997.28 421.89 0.00 0.00 0.00
October 918.60 495.76 422.84 1287.90 673.30 0.00 0.00 0.00
November 823.45 479.38 344.06 890.33 1121.89 0.00 0.00 0.00
December 686.86 363.92 322.95 606.47 1450.12 0.00 0.00 0.00
                 
Annual Sum or Average 1086.12 594.29 491.83 1607.56 724.57 0.00 0.00 0.00
Minimum of Months 686.86 363.92 314.53 606.47 157.55 0.00 0.00 0.00
Maximum of Months 1412.83 785.99 644.65 2631.59 1450.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2637.47 1998.16 639.31 3440.91 2047.04 0.00 0.00 0.00
February 2446.55 1724.78 721.77 3248.58 1850.46 0.00 0.00 0.00
March 1988.33 1146.46 841.86 2719.24 1628.42 0.00 0.00 0.00
April 1348.08 503.00 845.08 2111.28 1016.50 0.00 0.00 0.00
May 952.67 133.34 819.33 1688.20 600.68 0.00 0.00 0.00
June 821.92 52.15 769.77 1831.92 301.33 0.00 0.00 0.00
July 837.85 77.67 760.18 1849.31 243.73 0.00 0.00 0.00
August 1068.03 282.71 785.32 2190.02 347.28 0.00 0.00 0.00
September 1667.08 866.10 800.97 3066.82 705.69 0.00 0.00 0.00
October 2265.07 1531.34 733.73 3529.69 1104.51 0.00 0.00 0.00
November 2725.80 2078.09 647.71 3743.96 1768.14 0.00 0.00 0.00
December 2701.37 2027.77 673.60 3451.23 2203.42 0.00 0.00 0.00
                 
Annual Sum or Average 1784.56 1031.22 753.34 2735.63 1147.92 0.00 0.00 0.00
Minimum of Months 821.92 52.15 639.31 1688.20 243.73 0.00 0.00 0.00
Maximum of Months 2725.80 2078.09 845.08 3743.96 2203.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 724.16 407.82 316.33 771.80 1425.58 0.00 0.00 0.00
February 817.13 434.32 382.81 934.96 1293.38 0.00 0.00 0.00
March 1113.52 596.81 516.71 1405.58 1117.69 0.00 0.00 0.00
April 1279.90 691.30 588.60 1896.88 704.76 0.00 0.00 0.00
May 1378.57 737.60 640.97 2293.87 438.09 0.00 0.00 0.00
June 1341.93 720.77 621.17 2530.72 234.80 0.00 0.00 0.00
July 1190.87 591.77 599.10 2252.79 191.54 0.00 0.00 0.00
August 1153.30 587.77 565.53 2092.12 255.48 0.00 0.00 0.00
September 1179.43 657.06 522.37 2027.21 488.34 0.00 0.00 0.00
October 1015.29 592.56 422.74 1508.25 752.97 0.00 0.00 0.00
November 852.19 518.89 333.30 1037.24 1237.59 0.00 0.00 0.00
December 686.74 373.06 313.68 692.28 1566.56 0.00 0.00 0.00
                 
Annual Sum or Average 1061.97 576.19 485.78 1623.17 806.48 0.00 0.00 0.00
Minimum of Months 686.74 373.06 313.68 692.28 191.54 0.00 0.00 0.00
Maximum of Months 1378.57 737.60 640.97 2530.72 1566.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 385.54 0.00 385.54 102.59 1930.70 0.00 0.00 0.00
February 470.79 0.00 470.79 237.17 1747.28 0.00 0.00 0.00
March 616.11 0.00 616.11 451.02 1494.48 0.00 0.00 0.00
April 711.37 5.60 705.76 828.55 903.22 0.00 0.00 0.00
May 843.71 61.01 782.69 1362.44 548.11 0.00 0.00 0.00
June 897.14 110.45 786.69 1904.77 300.06 0.00 0.00 0.00
July 829.13 80.71 748.42 1748.03 241.32 0.00 0.00 0.00
August 699.14 14.30 684.84 1362.89 320.69 0.00 0.00 0.00
September 610.06 0.24 609.81 1035.05 647.38 0.00 0.00 0.00
October 506.52 0.00 506.52 560.20 980.31 0.00 0.00 0.00
November 408.91 0.00 408.91 170.69 1639.81 0.00 0.00 0.00
December 382.56 0.00 382.56 75.55 2144.80 0.00 0.00 0.00
                 
Annual Sum or Average 614.11 22.81 591.30 822.90 1071.54 0.00 0.00 0.00
Minimum of Months 382.56 0.00 382.56 75.55 241.32 0.00 0.00 0.00
Maximum of Months 897.14 110.45 786.69 1904.77 2144.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 687.45 372.92 314.53 681.06 1196.75 0.00 0.00 0.00
February 919.75 524.25 395.50 1047.06 1089.66 0.00 0.00 0.00
March 1135.59 625.67 509.91 1390.28 948.15 0.00 0.00 0.00
April 1368.33 759.12 609.21 1970.95 595.34 0.00 0.00 0.00
May 1412.04 767.39 644.65 2297.88 377.39 0.00 0.00 0.00
June 1412.83 785.99 626.85 2609.75 199.62 0.00 0.00 0.00
July 1267.00 662.37 604.64 2348.04 163.11 0.00 0.00 0.00
August 1205.62 617.03 588.60 2152.43 217.50 0.00 0.00 0.00
September 1194.44 681.52 512.93 1985.88 423.40 0.00 0.00 0.00
October 918.60 495.76 422.84 1294.50 643.27 0.00 0.00 0.00
November 823.45 479.38 344.06 923.39 1029.96 0.00 0.00 0.00
December 686.86 363.92 322.95 646.65 1319.78 0.00 0.00 0.00
                 
Annual Sum or Average 1086.12 594.29 491.83 1614.12 681.66 0.00 0.00 0.00
Minimum of Months 686.86 363.92 314.53 646.65 163.11 0.00 0.00 0.00
Maximum of Months 1412.83 785.99 644.65 2609.75 1319.78 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2637.47 1998.16 639.31 3492.59 1870.84 0.00 0.00 0.00
February 2446.55 1724.78 721.77 3290.38 1713.28 0.00 0.00 0.00
March 1988.33 1146.46 841.86 2750.48 1530.19 0.00 0.00 0.00
April 1348.08 503.00 845.08 2111.75 979.69 0.00 0.00 0.00
May 952.67 133.34 819.33 1676.48 592.18 0.00 0.00 0.00
June 821.92 52.15 769.77 1809.23 303.77 0.00 0.00 0.00
July 837.85 77.67 760.18 1820.30 249.61 0.00 0.00 0.00
August 1068.03 282.71 785.32 2167.06 349.47 0.00 0.00 0.00
September 1667.08 866.10 800.97 3051.14 703.24 0.00 0.00 0.00
October 2265.07 1531.34 733.73 3537.24 1057.16 0.00 0.00 0.00
November 2725.80 2078.09 647.71 3788.69 1635.85 0.00 0.00 0.00
December 2701.37 2027.77 673.60 3520.62 2015.94 0.00 0.00 0.00
                 
Annual Sum or Average 1784.56 1031.22 753.34 2747.57 1080.21 0.00 0.00 0.00
Minimum of Months 821.92 52.15 639.31 1676.48 249.61 0.00 0.00 0.00
Maximum of Months 2725.80 2078.09 845.08 3788.69 2015.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 724.16 407.82 316.33 790.60 1315.76 0.00 0.00 0.00
February 817.13 434.32 382.81 950.83 1207.80 0.00 0.00 0.00
March 1113.52 596.81 516.71 1418.40 1053.75 0.00 0.00 0.00
April 1279.90 691.30 588.60 1895.89 682.54 0.00 0.00 0.00
May 1378.57 737.60 640.97 2283.01 434.38 0.00 0.00 0.00
June 1341.93 720.77 621.17 2514.11 236.67 0.00 0.00 0.00
July 1190.87 591.77 599.10 2234.22 194.92 0.00 0.00 0.00
August 1153.30 587.77 565.53 2077.81 256.69 0.00 0.00 0.00
September 1179.43 657.06 522.37 2018.74 486.39 0.00 0.00 0.00
October 1015.29 592.56 422.74 1514.10 719.22 0.00 0.00 0.00
November 852.19 518.89 333.30 1053.14 1145.11 0.00 0.00 0.00
December 686.74 373.06 313.68 713.65 1445.35 0.00 0.00 0.00
                 
Annual Sum or Average 1061.97 576.19 485.78 1624.84 762.64 0.00 0.00 0.00
Minimum of Months 686.74 373.06 313.68 713.65 194.92 0.00 0.00 0.00
Maximum of Months 1378.57 737.60 640.97 2514.11 1445.35 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206527E+09 0.00 0.206527E+09 20846709.56 0.128239E+10
February 0.227786E+09 0.00 0.227786E+09 74546979.61 0.102768E+10
March 0.330037E+09 0.00 0.330037E+09 0.192715E+09 0.956519E+09
April 0.368773E+09 2905369.36 0.365867E+09 0.401301E+09 0.525564E+09
May 0.451957E+09 32682516.96 0.419274E+09 0.724556E+09 0.307647E+09
June 0.465076E+09 57255850.15 0.407820E+09 0.991544E+09 0.149808E+09
July 0.444148E+09 43234059.10 0.400914E+09 0.941659E+09 0.121965E+09
August 0.374514E+09 7657767.65 0.366856E+09 0.721157E+09 0.175366E+09
September 0.316255E+09 126196.05 0.316129E+09 0.529973E+09 0.353828E+09
October 0.271332E+09 0.00 0.271332E+09 0.266351E+09 0.618399E+09
November 0.211979E+09 0.00 0.211979E+09 48321523.48 0.107489E+10
December 0.204928E+09 0.00 0.204928E+09 12157394.07 0.145843E+10
           
Annual Sum or Average 0.387331E+10 0.143862E+09 0.372945E+10 0.492513E+10 0.805249E+10
Minimum of Months 0.204928E+09 0.00 0.204928E+09 12157394.07 0.121965E+09
Maximum of Months 0.465076E+09 57255850.15 0.419274E+09 0.991544E+09 0.145843E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206524E+09 0.00 0.206524E+09 20845542.23 0.128239E+10
February 0.227783E+09 0.00 0.227783E+09 74545288.73 0.102768E+10
March 0.330033E+09 0.00 0.330033E+09 0.192712E+09 0.956517E+09
April 0.368768E+09 2905305.49 0.365863E+09 0.401297E+09 0.525562E+09
May 0.451951E+09 32681798.47 0.419269E+09 0.724550E+09 0.307644E+09
June 0.465070E+09 57254591.45 0.407816E+09 0.991537E+09 0.149806E+09
July 0.444142E+09 43233108.65 0.400909E+09 0.941651E+09 0.121964E+09
August 0.374509E+09 7657599.30 0.366851E+09 0.721151E+09 0.175364E+09
September 0.316252E+09 126193.27 0.316125E+09 0.529969E+09 0.353825E+09
October 0.271328E+09 0.00 0.271328E+09 0.266348E+09 0.618397E+09
November 0.211976E+09 0.00 0.211976E+09 48320463.61 0.107489E+10
December 0.204925E+09 0.00 0.204925E+09 12156735.74 0.145843E+10
           
Annual Sum or Average 0.387326E+10 0.143859E+09 0.372940E+10 0.492508E+10 0.805246E+10
Minimum of Months 0.204925E+09 0.00 0.204925E+09 12156735.74 0.121964E+09
Maximum of Months 0.465070E+09 57254591.45 0.419269E+09 0.991537E+09 0.145843E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206525E+09 0.00 0.206525E+09 20845931.34 0.128239E+10
February 0.227784E+09 0.00 0.227784E+09 74545852.36 0.102768E+10
March 0.330035E+09 0.00 0.330035E+09 0.192713E+09 0.956518E+09
April 0.368770E+09 2905326.78 0.365865E+09 0.401299E+09 0.525563E+09
May 0.451953E+09 32682037.96 0.419271E+09 0.724552E+09 0.307645E+09
June 0.465072E+09 57255011.02 0.407817E+09 0.991539E+09 0.149807E+09
July 0.444144E+09 43233425.47 0.400911E+09 0.941653E+09 0.121964E+09
August 0.374511E+09 7657655.41 0.366853E+09 0.721153E+09 0.175365E+09
September 0.316253E+09 126194.20 0.316127E+09 0.529971E+09 0.353826E+09
October 0.271329E+09 0.00 0.271329E+09 0.266349E+09 0.618397E+09
November 0.211977E+09 0.00 0.211977E+09 48320816.89 0.107489E+10
December 0.204926E+09 0.00 0.204926E+09 12156955.18 0.145843E+10
           
Annual Sum or Average 0.387328E+10 0.143860E+09 0.372942E+10 0.492510E+10 0.805247E+10
Minimum of Months 0.204926E+09 0.00 0.204926E+09 12156955.18 0.121964E+09
Maximum of Months 0.465072E+09 57255011.02 0.419271E+09 0.991539E+09 0.145843E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206524E+09 0.00 0.206524E+09 20845542.23 0.128239E+10
February 0.227783E+09 0.00 0.227783E+09 74545288.73 0.102768E+10
March 0.330033E+09 0.00 0.330033E+09 0.192712E+09 0.956517E+09
April 0.368768E+09 2905305.49 0.365863E+09 0.401297E+09 0.525562E+09
May 0.451951E+09 32681798.47 0.419269E+09 0.724550E+09 0.307644E+09
June 0.465070E+09 57254591.45 0.407816E+09 0.991537E+09 0.149806E+09
July 0.444142E+09 43233108.65 0.400909E+09 0.941651E+09 0.121964E+09
August 0.374509E+09 7657599.30 0.366851E+09 0.721151E+09 0.175364E+09
September 0.316252E+09 126193.27 0.316125E+09 0.529969E+09 0.353825E+09
October 0.271328E+09 0.00 0.271328E+09 0.266348E+09 0.618397E+09
November 0.211976E+09 0.00 0.211976E+09 48320463.61 0.107489E+10
December 0.204925E+09 0.00 0.204925E+09 12156735.74 0.145843E+10
           
Annual Sum or Average 0.387326E+10 0.143859E+09 0.372940E+10 0.492508E+10 0.805246E+10
Minimum of Months 0.204925E+09 0.00 0.204925E+09 12156735.74 0.121964E+09
Maximum of Months 0.465070E+09 57254591.45 0.419269E+09 0.991537E+09 0.145843E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206517E+09 0.00 0.206517E+09 20844896.61 0.128234E+10
February 0.227774E+09 0.00 0.227774E+09 74542566.03 0.102764E+10
March 0.330021E+09 0.00 0.330021E+09 0.192704E+09 0.956479E+09
April 0.368754E+09 2905199.04 0.365849E+09 0.401282E+09 0.525541E+09
May 0.451934E+09 32680600.99 0.419253E+09 0.724522E+09 0.307632E+09
June 0.465053E+09 57252493.61 0.407800E+09 0.991498E+09 0.149800E+09
July 0.444125E+09 43231524.57 0.400894E+09 0.941614E+09 0.121959E+09
August 0.374495E+09 7657318.72 0.366837E+09 0.721123E+09 0.175357E+09
September 0.316239E+09 126188.65 0.316113E+09 0.529949E+09 0.353811E+09
October 0.271318E+09 0.00 0.271318E+09 0.266337E+09 0.618372E+09
November 0.211968E+09 0.00 0.211968E+09 48318692.72 0.107484E+10
December 0.204917E+09 0.00 0.204917E+09 12156355.49 0.145837E+10
           
Annual Sum or Average 0.387311E+10 0.143853E+09 0.372926E+10 0.492489E+10 0.805214E+10
Minimum of Months 0.204917E+09 0.00 0.204917E+09 12156355.49 0.121959E+09
Maximum of Months 0.465053E+09 57252493.61 0.419253E+09 0.991498E+09 0.145837E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.613765E+09 0.332946E+09 0.280820E+09 0.553329E+09 0.128570E+10
February 0.741692E+09 0.422760E+09 0.318932E+09 0.799540E+09 0.102172E+10
March 0.101386E+10 0.558606E+09 0.455257E+09 0.121288E+10 0.945856E+09
April 0.118225E+10 0.655882E+09 0.526363E+09 0.171879E+10 0.521673E+09
May 0.126068E+10 0.685133E+09 0.575547E+09 0.207763E+10 0.337505E+09
June 0.122070E+10 0.679099E+09 0.541601E+09 0.228836E+10 0.153919E+09
July 0.113119E+10 0.591368E+09 0.539824E+09 0.213412E+10 0.120785E+09
August 0.107639E+10 0.550887E+09 0.525504E+09 0.195206E+10 0.168338E+09
September 0.103201E+10 0.588837E+09 0.443173E+09 0.173427E+10 0.364240E+09
October 0.820137E+09 0.442620E+09 0.377517E+09 0.114662E+10 0.633188E+09
November 0.711465E+09 0.414192E+09 0.297273E+09 0.751294E+09 0.105274E+10
December 0.613238E+09 0.324907E+09 0.288331E+09 0.516941E+09 0.141906E+10
           
Annual Sum or Average 0.114174E+11 0.624724E+10 0.517014E+10 0.168858E+11 0.802472E+10
Minimum of Months 0.613238E+09 0.324907E+09 0.280820E+09 0.516941E+09 0.120785E+09
Maximum of Months 0.126068E+10 0.685133E+09 0.575547E+09 0.228836E+10 0.141906E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.613765E+09 0.332946E+09 0.280820E+09 0.553329E+09 0.128570E+10
February 0.741692E+09 0.422760E+09 0.318932E+09 0.799540E+09 0.102172E+10
March 0.101386E+10 0.558606E+09 0.455257E+09 0.121288E+10 0.945856E+09
April 0.118225E+10 0.655882E+09 0.526363E+09 0.171879E+10 0.521673E+09
May 0.126068E+10 0.685133E+09 0.575547E+09 0.207763E+10 0.337505E+09
June 0.122070E+10 0.679099E+09 0.541601E+09 0.228836E+10 0.153919E+09
July 0.113119E+10 0.591368E+09 0.539824E+09 0.213412E+10 0.120785E+09
August 0.107639E+10 0.550887E+09 0.525504E+09 0.195206E+10 0.168338E+09
September 0.103201E+10 0.588837E+09 0.443173E+09 0.173427E+10 0.364240E+09
October 0.820137E+09 0.442620E+09 0.377517E+09 0.114662E+10 0.633188E+09
November 0.711465E+09 0.414192E+09 0.297273E+09 0.751294E+09 0.105274E+10
December 0.613238E+09 0.324907E+09 0.288331E+09 0.516941E+09 0.141906E+10
           
Annual Sum or Average 0.114174E+11 0.624724E+10 0.517014E+10 0.168858E+11 0.802472E+10
Minimum of Months 0.613238E+09 0.324907E+09 0.280820E+09 0.516941E+09 0.120785E+09
Maximum of Months 0.126068E+10 0.685133E+09 0.575547E+09 0.228836E+10 0.141906E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.613754E+09 0.332939E+09 0.280815E+09 0.553319E+09 0.128568E+10
February 0.741678E+09 0.422752E+09 0.318926E+09 0.799525E+09 0.102170E+10
March 0.101384E+10 0.558595E+09 0.455248E+09 0.121285E+10 0.945839E+09
April 0.118222E+10 0.655870E+09 0.526354E+09 0.171876E+10 0.521663E+09
May 0.126066E+10 0.685120E+09 0.575537E+09 0.207759E+10 0.337499E+09
June 0.122068E+10 0.679086E+09 0.541591E+09 0.228832E+10 0.153916E+09
July 0.113117E+10 0.591357E+09 0.539814E+09 0.213408E+10 0.120783E+09
August 0.107637E+10 0.550877E+09 0.525494E+09 0.195202E+10 0.168335E+09
September 0.103199E+10 0.588826E+09 0.443165E+09 0.173424E+10 0.364233E+09
October 0.820122E+09 0.442612E+09 0.377510E+09 0.114659E+10 0.633176E+09
November 0.711452E+09 0.414185E+09 0.297267E+09 0.751280E+09 0.105272E+10
December 0.613227E+09 0.324901E+09 0.288326E+09 0.516932E+09 0.141904E+10
           
Annual Sum or Average 0.114172E+11 0.624712E+10 0.517005E+10 0.168855E+11 0.802457E+10
Minimum of Months 0.613227E+09 0.324901E+09 0.280815E+09 0.516932E+09 0.120783E+09
Maximum of Months 0.126066E+10 0.685120E+09 0.575537E+09 0.228832E+10 0.141904E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141281E+10 0.107035E+10 0.342462E+09 0.185628E+10 0.112323E+10
February 0.118372E+10 0.834499E+09 0.349217E+09 0.158227E+10 0.919439E+09
March 0.106509E+10 0.614125E+09 0.450965E+09 0.146540E+10 0.901308E+09
April 0.698835E+09 0.260751E+09 0.438084E+09 0.109473E+10 0.539557E+09
May 0.510323E+09 71427610.45 0.438896E+09 0.900493E+09 0.329510E+09
June 0.426079E+09 27034416.55 0.399045E+09 0.938426E+09 0.153026E+09
July 0.448818E+09 41605610.16 0.407212E+09 0.979909E+09 0.126142E+09
August 0.572117E+09 0.151441E+09 0.420675E+09 0.116254E+10 0.185348E+09
September 0.864199E+09 0.448979E+09 0.415220E+09 0.159708E+10 0.366822E+09
October 0.121333E+10 0.820289E+09 0.393040E+09 0.190193E+10 0.604562E+09
November 0.141303E+10 0.107726E+10 0.335770E+09 0.194860E+10 0.946430E+09
December 0.144704E+10 0.108621E+10 0.360829E+09 0.185015E+10 0.122689E+10
           
Annual Sum or Average 0.112554E+11 0.650398E+10 0.475142E+10 0.172778E+11 0.742227E+10
Minimum of Months 0.426079E+09 27034416.55 0.335770E+09 0.900493E+09 0.126142E+09
Maximum of Months 0.144704E+10 0.108621E+10 0.450965E+09 0.194860E+10 0.122689E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141280E+10 0.107034E+10 0.342460E+09 0.185626E+10 0.112323E+10
February 0.118371E+10 0.834493E+09 0.349215E+09 0.158226E+10 0.919438E+09
March 0.106508E+10 0.614120E+09 0.450963E+09 0.146539E+10 0.901307E+09
April 0.698831E+09 0.260749E+09 0.438082E+09 0.109473E+10 0.539556E+09
May 0.510321E+09 71427087.03 0.438894E+09 0.900489E+09 0.329509E+09
June 0.426077E+09 27034218.44 0.399043E+09 0.938424E+09 0.153026E+09
July 0.448816E+09 41605305.28 0.407210E+09 0.979907E+09 0.126141E+09
August 0.572114E+09 0.151440E+09 0.420674E+09 0.116254E+10 0.185347E+09
September 0.864194E+09 0.448976E+09 0.415218E+09 0.159707E+10 0.366822E+09
October 0.121332E+10 0.820283E+09 0.393038E+09 0.190192E+10 0.604561E+09
November 0.141302E+10 0.107725E+10 0.335768E+09 0.194858E+10 0.946429E+09
December 0.144703E+10 0.108621E+10 0.360827E+09 0.185013E+10 0.122689E+10
           
Annual Sum or Average 0.112553E+11 0.650393E+10 0.475139E+10 0.172777E+11 0.742226E+10
Minimum of Months 0.426077E+09 27034218.44 0.335768E+09 0.900489E+09 0.126141E+09
Maximum of Months 0.144703E+10 0.108621E+10 0.450963E+09 0.194858E+10 0.122689E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141281E+10 0.107035E+10 0.342462E+09 0.185628E+10 0.112323E+10
February 0.118372E+10 0.834499E+09 0.349217E+09 0.158227E+10 0.919439E+09
March 0.106509E+10 0.614125E+09 0.450965E+09 0.146540E+10 0.901308E+09
April 0.698835E+09 0.260751E+09 0.438084E+09 0.109473E+10 0.539557E+09
May 0.510323E+09 71427610.45 0.438896E+09 0.900493E+09 0.329510E+09
June 0.426079E+09 27034416.55 0.399045E+09 0.938426E+09 0.153026E+09
July 0.448818E+09 41605610.16 0.407212E+09 0.979909E+09 0.126142E+09
August 0.572117E+09 0.151441E+09 0.420675E+09 0.116254E+10 0.185348E+09
September 0.864199E+09 0.448979E+09 0.415220E+09 0.159708E+10 0.366822E+09
October 0.121333E+10 0.820289E+09 0.393040E+09 0.190193E+10 0.604562E+09
November 0.141303E+10 0.107726E+10 0.335770E+09 0.194860E+10 0.946430E+09
December 0.144704E+10 0.108621E+10 0.360829E+09 0.185015E+10 0.122689E+10
           
Annual Sum or Average 0.112554E+11 0.650398E+10 0.475142E+10 0.172778E+11 0.742227E+10
Minimum of Months 0.426079E+09 27034416.55 0.335770E+09 0.900493E+09 0.126142E+09
Maximum of Months 0.144704E+10 0.108621E+10 0.450965E+09 0.194860E+10 0.122689E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141280E+10 0.107034E+10 0.342460E+09 0.185626E+10 0.112323E+10
February 0.118371E+10 0.834493E+09 0.349215E+09 0.158226E+10 0.919438E+09
March 0.106508E+10 0.614120E+09 0.450963E+09 0.146539E+10 0.901307E+09
April 0.698831E+09 0.260749E+09 0.438082E+09 0.109473E+10 0.539556E+09
May 0.510321E+09 71427087.03 0.438894E+09 0.900489E+09 0.329509E+09
June 0.426077E+09 27034218.44 0.399043E+09 0.938424E+09 0.153026E+09
July 0.448816E+09 41605305.28 0.407210E+09 0.979907E+09 0.126141E+09
August 0.572114E+09 0.151440E+09 0.420674E+09 0.116254E+10 0.185347E+09
September 0.864194E+09 0.448976E+09 0.415218E+09 0.159707E+10 0.366822E+09
October 0.121332E+10 0.820283E+09 0.393038E+09 0.190192E+10 0.604561E+09
November 0.141302E+10 0.107725E+10 0.335768E+09 0.194858E+10 0.946429E+09
December 0.144703E+10 0.108621E+10 0.360827E+09 0.185013E+10 0.122689E+10
           
Annual Sum or Average 0.112553E+11 0.650393E+10 0.475139E+10 0.172777E+11 0.742226E+10
Minimum of Months 0.426077E+09 27034218.44 0.335768E+09 0.900489E+09 0.126141E+09
Maximum of Months 0.144703E+10 0.108621E+10 0.450963E+09 0.194858E+10 0.122689E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141275E+10 0.107030E+10 0.342447E+09 0.185620E+10 0.112318E+10
February 0.118366E+10 0.834462E+09 0.349202E+09 0.158220E+10 0.919402E+09
March 0.106504E+10 0.614098E+09 0.450946E+09 0.146534E+10 0.901272E+09
April 0.698805E+09 0.260739E+09 0.438066E+09 0.109469E+10 0.539534E+09
May 0.510301E+09 71424469.90 0.438877E+09 0.900455E+09 0.329497E+09
June 0.426061E+09 27033227.90 0.399028E+09 0.938387E+09 0.153020E+09
July 0.448799E+09 41603780.84 0.407195E+09 0.979869E+09 0.126136E+09
August 0.572092E+09 0.151435E+09 0.420658E+09 0.116249E+10 0.185340E+09
September 0.864162E+09 0.448959E+09 0.415203E+09 0.159701E+10 0.366807E+09
October 0.121328E+10 0.820253E+09 0.393024E+09 0.190185E+10 0.604537E+09
November 0.141297E+10 0.107721E+10 0.335756E+09 0.194851E+10 0.946392E+09
December 0.144698E+10 0.108617E+10 0.360813E+09 0.185007E+10 0.122684E+10
           
Annual Sum or Average 0.112549E+11 0.650369E+10 0.475121E+10 0.172771E+11 0.742196E+10
Minimum of Months 0.426061E+09 27033227.90 0.335756E+09 0.900455E+09 0.126136E+09
Maximum of Months 0.144698E+10 0.108617E+10 0.450946E+09 0.194851E+10 0.122684E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.646533E+09 0.364109E+09 0.282424E+09 0.660776E+09 0.142963E+10
February 0.658944E+09 0.350243E+09 0.308701E+09 0.718447E+09 0.119639E+10
March 0.994160E+09 0.532836E+09 0.461325E+09 0.121009E+10 0.115506E+10
April 0.110584E+10 0.597286E+09 0.508558E+09 0.159567E+10 0.699972E+09
May 0.123080E+10 0.658535E+09 0.572268E+09 0.204140E+10 0.417916E+09
June 0.115944E+10 0.622749E+09 0.536695E+09 0.216450E+10 0.216803E+09
July 0.106322E+10 0.528336E+09 0.534886E+09 0.197606E+10 0.192191E+09
August 0.102968E+10 0.524762E+09 0.504913E+09 0.181331E+10 0.289395E+09
September 0.101904E+10 0.567706E+09 0.451330E+09 0.173985E+10 0.449740E+09
October 0.906464E+09 0.529042E+09 0.377422E+09 0.131439E+10 0.765514E+09
November 0.736300E+09 0.448328E+09 0.287971E+09 0.851717E+09 0.127102E+10
December 0.613128E+09 0.333071E+09 0.280057E+09 0.566882E+09 0.169933E+10
           
Annual Sum or Average 0.111636E+11 0.605700E+10 0.510655E+10 0.166531E+11 0.978297E+10
Minimum of Months 0.613128E+09 0.333071E+09 0.280057E+09 0.566882E+09 0.192191E+09
Maximum of Months 0.123080E+10 0.658535E+09 0.572268E+09 0.216450E+10 0.169933E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.646533E+09 0.364109E+09 0.282424E+09 0.660776E+09 0.142963E+10
February 0.658944E+09 0.350243E+09 0.308701E+09 0.718447E+09 0.119639E+10
March 0.994160E+09 0.532836E+09 0.461325E+09 0.121009E+10 0.115506E+10
April 0.110584E+10 0.597286E+09 0.508558E+09 0.159567E+10 0.699972E+09
May 0.123080E+10 0.658535E+09 0.572268E+09 0.204140E+10 0.417916E+09
June 0.115944E+10 0.622749E+09 0.536695E+09 0.216450E+10 0.216803E+09
July 0.106322E+10 0.528336E+09 0.534886E+09 0.197606E+10 0.192191E+09
August 0.102968E+10 0.524762E+09 0.504913E+09 0.181331E+10 0.289395E+09
September 0.101904E+10 0.567706E+09 0.451330E+09 0.173985E+10 0.449740E+09
October 0.906464E+09 0.529042E+09 0.377422E+09 0.131439E+10 0.765514E+09
November 0.736300E+09 0.448328E+09 0.287971E+09 0.851717E+09 0.127102E+10
December 0.613128E+09 0.333071E+09 0.280057E+09 0.566882E+09 0.169933E+10
           
Annual Sum or Average 0.111636E+11 0.605700E+10 0.510655E+10 0.166531E+11 0.978297E+10
Minimum of Months 0.613128E+09 0.333071E+09 0.280057E+09 0.566882E+09 0.192191E+09
Maximum of Months 0.123080E+10 0.658535E+09 0.572268E+09 0.216450E+10 0.169933E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.646521E+09 0.364102E+09 0.282419E+09 0.660764E+09 0.142961E+10
February 0.658932E+09 0.350237E+09 0.308695E+09 0.718434E+09 0.119637E+10
March 0.994142E+09 0.532826E+09 0.461316E+09 0.121006E+10 0.115504E+10
April 0.110582E+10 0.597276E+09 0.508549E+09 0.159564E+10 0.699959E+09
May 0.123078E+10 0.658523E+09 0.572257E+09 0.204136E+10 0.417909E+09
June 0.115942E+10 0.622737E+09 0.536685E+09 0.216446E+10 0.216799E+09
July 0.106320E+10 0.528326E+09 0.534876E+09 0.197602E+10 0.192187E+09
August 0.102966E+10 0.524753E+09 0.504904E+09 0.181328E+10 0.289389E+09
September 0.101902E+10 0.567695E+09 0.451321E+09 0.173982E+10 0.449731E+09
October 0.906447E+09 0.529032E+09 0.377415E+09 0.131437E+10 0.765500E+09
November 0.736286E+09 0.448320E+09 0.287966E+09 0.851702E+09 0.127100E+10
December 0.613117E+09 0.333065E+09 0.280052E+09 0.566872E+09 0.169930E+10
           
Annual Sum or Average 0.111633E+11 0.605689E+10 0.510646E+10 0.166528E+11 0.978279E+10
Minimum of Months 0.613117E+09 0.333065E+09 0.280052E+09 0.566872E+09 0.192187E+09
Maximum of Months 0.123078E+10 0.658523E+09 0.572257E+09 0.216446E+10 0.169930E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.103263E+10 0.00 0.103263E+10 0.192462E+09 0.572773E+10
February 0.113893E+10 0.00 0.113893E+10 0.489431E+09 0.461881E+10
March 0.165018E+10 0.00 0.165018E+10 0.110564E+10 0.433129E+10
April 0.184386E+10 14526939.37 0.182933E+10 0.211616E+10 0.245954E+10
May 0.225978E+10 0.163414E+09 0.209637E+10 0.366779E+10 0.148704E+10
June 0.232538E+10 0.286281E+09 0.203910E+10 0.499897E+10 0.768447E+09
July 0.222074E+10 0.216172E+09 0.200456E+10 0.475984E+10 0.629713E+09
August 0.187256E+10 38289082.23 0.183427E+10 0.370494E+10 0.857897E+09
September 0.158127E+10 630984.26 0.158064E+10 0.270008E+10 0.170458E+10
October 0.135666E+10 0.00 0.135666E+10 0.143851E+10 0.282076E+10
November 0.105989E+10 0.00 0.105989E+10 0.359651E+09 0.471896E+10
December 0.102464E+10 0.00 0.102464E+10 0.129082E+09 0.635415E+10
           
Annual Sum or Average 0.193665E+11 0.719313E+09 0.186472E+11 0.256626E+11 0.364789E+11
Minimum of Months 0.102464E+10 0.00 0.102464E+10 0.129082E+09 0.629713E+09
Maximum of Months 0.232538E+10 0.286281E+09 0.209637E+10 0.499897E+10 0.635415E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.184128E+10 0.998827E+09 0.842450E+09 0.172806E+10 0.352734E+10
February 0.222505E+10 0.126827E+10 0.956787E+09 0.244751E+10 0.284974E+10
March 0.304156E+10 0.167580E+10 0.136576E+10 0.365854E+10 0.269338E+10
April 0.354670E+10 0.196763E+10 0.157907E+10 0.511544E+10 0.158054E+10
May 0.378200E+10 0.205538E+10 0.172662E+10 0.619295E+10 0.100871E+10
June 0.366206E+10 0.203728E+10 0.162479E+10 0.682108E+10 0.507104E+09
July 0.339354E+10 0.177408E+10 0.161946E+10 0.635642E+10 0.421982E+09
August 0.322914E+10 0.165264E+10 0.157649E+10 0.581743E+10 0.572537E+09
September 0.309600E+10 0.176649E+10 0.132951E+10 0.517695E+10 0.109353E+10
October 0.246039E+10 0.132785E+10 0.113254E+10 0.344952E+10 0.180337E+10
November 0.213437E+10 0.124256E+10 0.891809E+09 0.230774E+10 0.290794E+10
December 0.183970E+10 0.974712E+09 0.864984E+09 0.162437E+10 0.388400E+10
           
Annual Sum or Average 0.342518E+11 0.187415E+11 0.155103E+11 0.506960E+11 0.228502E+11
Minimum of Months 0.183970E+10 0.974712E+09 0.842450E+09 0.162437E+10 0.421982E+09
Maximum of Months 0.378200E+10 0.205538E+10 0.172662E+10 0.682108E+10 0.388400E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.706420E+10 0.535187E+10 0.171233E+10 0.921613E+10 0.548278E+10
February 0.591869E+10 0.417258E+10 0.174610E+10 0.785897E+10 0.447664E+10
March 0.532554E+10 0.307069E+10 0.225485E+10 0.728322E+10 0.436157E+10
April 0.349422E+10 0.130378E+10 0.219044E+10 0.547244E+10 0.263476E+10
May 0.255164E+10 0.357146E+09 0.219449E+10 0.452168E+10 0.160886E+10
June 0.213041E+10 0.135175E+09 0.199523E+10 0.474833E+10 0.781053E+09
July 0.224411E+10 0.208032E+09 0.203607E+10 0.495318E+10 0.652803E+09
August 0.286062E+10 0.757222E+09 0.210339E+10 0.586575E+10 0.930149E+09
September 0.432106E+10 0.224494E+10 0.207612E+10 0.794920E+10 0.182916E+10
October 0.606675E+10 0.410153E+10 0.196522E+10 0.945392E+10 0.295832E+10
November 0.706527E+10 0.538640E+10 0.167887E+10 0.970436E+10 0.458302E+10
December 0.723536E+10 0.543119E+10 0.180417E+10 0.924377E+10 0.590164E+10
           
Annual Sum or Average 0.562779E+11 0.325206E+11 0.237573E+11 0.862710E+11 0.362008E+11
Minimum of Months 0.213041E+10 0.135175E+09 0.167887E+10 0.452168E+10 0.652803E+09
Maximum of Months 0.723536E+10 0.543119E+10 0.225485E+10 0.970436E+10 0.590164E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.193958E+10 0.109232E+10 0.847263E+09 0.206719E+10 0.381827E+10
February 0.197681E+10 0.105072E+10 0.926094E+09 0.226187E+10 0.312894E+10
March 0.298245E+10 0.159849E+10 0.138396E+10 0.376471E+10 0.299361E+10
April 0.331750E+10 0.179184E+10 0.152566E+10 0.491672E+10 0.182673E+10
May 0.369237E+10 0.197559E+10 0.171679E+10 0.614391E+10 0.117339E+10
June 0.347829E+10 0.186823E+10 0.161007E+10 0.655963E+10 0.608609E+09
July 0.318963E+10 0.158499E+10 0.160464E+10 0.603386E+10 0.513033E+09
August 0.308900E+10 0.157427E+10 0.151472E+10 0.560354E+10 0.684275E+09
September 0.305708E+10 0.170310E+10 0.135398E+10 0.525452E+10 0.126577E+10
October 0.271936E+10 0.158711E+10 0.113225E+10 0.403970E+10 0.201675E+10
November 0.220888E+10 0.134497E+10 0.863906E+09 0.268853E+10 0.320783E+10
December 0.183936E+10 0.999202E+09 0.840163E+09 0.185419E+10 0.419587E+10
           
Annual Sum or Average 0.334903E+11 0.181708E+11 0.153195E+11 0.511884E+11 0.254331E+11
Minimum of Months 0.183936E+10 0.999202E+09 0.840163E+09 0.185419E+10 0.513033E+09
Maximum of Months 0.369237E+10 0.197559E+10 0.171679E+10 0.655963E+10 0.419587E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.103263E+10 0.00 0.103263E+10 0.274776E+09 0.517119E+10
February 0.113893E+10 0.00 0.113893E+10 0.573769E+09 0.422703E+10
March 0.165018E+10 0.00 0.165018E+10 0.120801E+10 0.400283E+10
April 0.184386E+10 14526939.37 0.182933E+10 0.214760E+10 0.234116E+10
May 0.225978E+10 0.163414E+09 0.209637E+10 0.364916E+10 0.146805E+10
June 0.232538E+10 0.286281E+09 0.203910E+10 0.493717E+10 0.777744E+09
July 0.222074E+10 0.216172E+09 0.200456E+10 0.468193E+10 0.646356E+09
August 0.187256E+10 38289082.23 0.183427E+10 0.365036E+10 0.858942E+09
September 0.158127E+10 630984.26 0.158064E+10 0.268285E+10 0.167801E+10
October 0.135666E+10 0.00 0.135666E+10 0.150043E+10 0.262567E+10
November 0.105989E+10 0.00 0.105989E+10 0.442430E+09 0.425038E+10
December 0.102464E+10 0.00 0.102464E+10 0.202361E+09 0.574463E+10
           
Annual Sum or Average 0.193665E+11 0.719313E+09 0.186472E+11 0.259508E+11 0.337920E+11
Minimum of Months 0.102464E+10 0.00 0.102464E+10 0.202361E+09 0.646356E+09
Maximum of Months 0.232538E+10 0.286281E+09 0.209637E+10 0.493717E+10 0.574463E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.184128E+10 0.998827E+09 0.842450E+09 0.182415E+10 0.320537E+10
February 0.222505E+10 0.126827E+10 0.956787E+09 0.253305E+10 0.263610E+10
March 0.304156E+10 0.167580E+10 0.136576E+10 0.372372E+10 0.253952E+10
April 0.354670E+10 0.196763E+10 0.157907E+10 0.510870E+10 0.154311E+10
May 0.378200E+10 0.205538E+10 0.172662E+10 0.615464E+10 0.101081E+10
June 0.366206E+10 0.203728E+10 0.162479E+10 0.676448E+10 0.517402E+09
July 0.339354E+10 0.177408E+10 0.161946E+10 0.628900E+10 0.436883E+09
August 0.322914E+10 0.165264E+10 0.157649E+10 0.576508E+10 0.582550E+09
September 0.309600E+10 0.176649E+10 0.132951E+10 0.514740E+10 0.109746E+10
October 0.246039E+10 0.132785E+10 0.113254E+10 0.346718E+10 0.172294E+10
November 0.213437E+10 0.124256E+10 0.891809E+09 0.239343E+10 0.266965E+10
December 0.183970E+10 0.974712E+09 0.864984E+09 0.173199E+10 0.353490E+10
           
Annual Sum or Average 0.342518E+11 0.187415E+11 0.155103E+11 0.509028E+11 0.214967E+11
Minimum of Months 0.183970E+10 0.974712E+09 0.842450E+09 0.173199E+10 0.436883E+09
Maximum of Months 0.378200E+10 0.205538E+10 0.172662E+10 0.676448E+10 0.353490E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.706420E+10 0.535187E+10 0.171233E+10 0.935456E+10 0.501085E+10
February 0.591869E+10 0.417258E+10 0.174610E+10 0.796009E+10 0.414477E+10
March 0.532554E+10 0.307069E+10 0.225485E+10 0.736688E+10 0.409846E+10
April 0.349422E+10 0.130378E+10 0.219044E+10 0.547366E+10 0.253935E+10
May 0.255164E+10 0.357146E+09 0.219449E+10 0.449030E+10 0.158610E+10
June 0.213041E+10 0.135175E+09 0.199523E+10 0.468952E+10 0.787381E+09
July 0.224411E+10 0.208032E+09 0.203607E+10 0.487549E+10 0.668567E+09
August 0.286062E+10 0.757222E+09 0.210339E+10 0.580427E+10 0.936019E+09
September 0.432106E+10 0.224494E+10 0.207612E+10 0.790855E+10 0.182279E+10
October 0.606675E+10 0.410153E+10 0.196522E+10 0.947414E+10 0.283151E+10
November 0.706527E+10 0.538640E+10 0.167887E+10 0.982027E+10 0.424011E+10
December 0.723536E+10 0.543119E+10 0.180417E+10 0.942964E+10 0.539948E+10
           
Annual Sum or Average 0.562779E+11 0.325206E+11 0.237573E+11 0.866473E+11 0.340654E+11
Minimum of Months 0.213041E+10 0.135175E+09 0.167887E+10 0.449030E+10 0.668567E+09
Maximum of Months 0.723536E+10 0.543119E+10 0.225485E+10 0.982027E+10 0.539948E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.193958E+10 0.109232E+10 0.847263E+09 0.211755E+10 0.352414E+10
February 0.197681E+10 0.105072E+10 0.926094E+09 0.230024E+10 0.292190E+10
March 0.298245E+10 0.159849E+10 0.138396E+10 0.379905E+10 0.282238E+10
April 0.331750E+10 0.179184E+10 0.152566E+10 0.491415E+10 0.176915E+10
May 0.369237E+10 0.197559E+10 0.171679E+10 0.611480E+10 0.116345E+10
June 0.347829E+10 0.186823E+10 0.161007E+10 0.651656E+10 0.613456E+09
July 0.318963E+10 0.158499E+10 0.160464E+10 0.598414E+10 0.522072E+09
August 0.308900E+10 0.157427E+10 0.151472E+10 0.556522E+10 0.687521E+09
September 0.305708E+10 0.170310E+10 0.135398E+10 0.523258E+10 0.126072E+10
October 0.271936E+10 0.158711E+10 0.113225E+10 0.405537E+10 0.192635E+10
November 0.220888E+10 0.134497E+10 0.863906E+09 0.272974E+10 0.296811E+10
December 0.183936E+10 0.999202E+09 0.840163E+09 0.191145E+10 0.387124E+10
           
Annual Sum or Average 0.334903E+11 0.181708E+11 0.153195E+11 0.512409E+11 0.240505E+11
Minimum of Months 0.183936E+10 0.999202E+09 0.840163E+09 0.191145E+10 0.522072E+09
Maximum of Months 0.369237E+10 0.197559E+10 0.171679E+10 0.651656E+10 0.387124E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 38.91 2393.93 385.54 0.00 385.54 0.00 0.00
February 154.07 2123.98 470.78 0.00 470.78 0.00 0.00
March 359.75 1785.60 616.10 0.00 616.10 0.00 0.00
April 774.10 1013.81 711.36 5.60 705.75 0.00 0.00
May 1352.57 574.30 843.69 61.01 782.68 0.00 0.00
June 1912.68 288.98 897.12 110.44 786.68 0.00 0.00
July 1757.85 227.68 829.11 80.71 748.41 0.00 0.00
August 1346.23 327.37 699.13 14.30 684.83 0.00 0.00
September 1022.31 682.53 610.05 0.24 609.81 0.00 0.00
October 497.21 1154.41 506.51 0.00 506.51 0.00 0.00
November 93.21 2073.46 408.90 0.00 408.90 0.00 0.00
December 22.69 2722.55 382.55 0.00 382.55 0.00 0.00
               
Annual Sum or Average 780.86 1276.70 614.10 22.81 591.29 0.00 0.00
Minimum of Months 22.69 227.68 382.55 0.00 382.55 0.00 0.00
Maximum of Months 1912.68 2722.55 897.12 110.44 786.68 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 619.76 1440.07 687.46 372.92 314.54 0.00 0.00
February 991.49 1267.01 919.75 524.25 395.50 0.00 0.00
March 1358.50 1059.42 1135.59 625.67 509.92 0.00 0.00
April 1989.33 603.78 1368.33 759.12 609.21 0.00 0.00
May 2327.08 378.03 1412.04 767.39 644.65 0.00 0.00
June 2648.55 178.15 1412.84 785.99 626.85 0.00 0.00
July 2390.35 135.29 1267.01 662.37 604.64 0.00 0.00
August 2186.43 188.55 1205.63 617.03 588.60 0.00 0.00
September 2007.25 421.57 1194.45 681.52 512.93 0.00 0.00
October 1284.28 709.21 918.61 495.76 422.84 0.00 0.00
November 869.55 1218.44 823.45 479.39 344.06 0.00 0.00
December 579.01 1589.44 686.87 363.92 322.95 0.00 0.00
               
Annual Sum or Average 1606.33 763.38 1086.12 594.29 491.83 0.00 0.00
Minimum of Months 579.01 135.29 686.87 363.92 314.54 0.00 0.00
Maximum of Months 2648.55 1589.44 1412.84 785.99 644.65 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3465.23 2096.81 2637.39 1998.09 639.30 0.00 0.00
February 3270.20 1900.28 2446.48 1724.72 721.75 0.00 0.00
March 2735.56 1682.54 1988.27 1146.43 841.85 0.00 0.00
April 2111.73 1040.80 1348.05 502.99 845.06 0.00 0.00
May 1681.01 615.12 952.65 133.34 819.32 0.00 0.00
June 1810.22 295.19 821.90 52.15 769.75 0.00 0.00
July 1829.26 235.48 837.84 77.67 760.17 0.00 0.00
August 2170.20 346.00 1068.01 282.71 785.30 0.00 0.00
September 3080.76 707.60 1667.03 866.08 800.96 0.00 0.00
October 3550.46 1128.58 2265.00 1531.29 733.71 0.00 0.00
November 3758.82 1825.66 2725.72 2078.02 647.70 0.00 0.00
December 3453.79 2290.33 2701.29 2027.71 673.58 0.00 0.00
               
Annual Sum or Average 2739.35 1176.78 1784.51 1031.19 753.32 0.00 0.00
Minimum of Months 1681.01 235.48 821.90 52.15 639.30 0.00 0.00
Maximum of Months 3758.82 2290.33 2725.72 2078.02 845.06 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 740.11 1601.28 724.16 407.83 316.33 0.00 0.00
February 890.93 1483.61 817.14 434.33 382.81 0.00 0.00
March 1355.37 1293.75 1113.52 596.81 516.71 0.00 0.00
April 1846.83 810.15 1279.90 691.30 588.61 0.00 0.00
May 2286.50 468.09 1378.58 737.60 640.98 0.00 0.00
June 2505.19 250.93 1341.94 720.77 621.17 0.00 0.00
July 2213.32 215.27 1190.88 591.77 599.11 0.00 0.00
August 2031.03 324.14 1153.30 587.77 565.54 0.00 0.00
September 2013.70 520.53 1179.43 657.06 522.37 0.00 0.00
October 1472.21 857.42 1015.30 592.56 422.74 0.00 0.00
November 985.78 1471.08 852.19 518.90 333.30 0.00 0.00
December 634.94 1903.36 686.74 373.06 313.68 0.00 0.00
               
Annual Sum or Average 1584.19 930.64 1061.98 576.20 485.78 0.00 0.00
Minimum of Months 634.94 215.27 686.74 373.06 313.68 0.00 0.00
Maximum of Months 2505.19 1903.36 1378.58 737.60 640.98 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 71.86 2138.49 385.54 0.00 385.54 0.00 0.00
February 202.31 1909.23 470.79 0.00 470.79 0.00 0.00
March 412.80 1617.12 616.11 0.00 616.11 0.00 0.00
April 816.42 948.90 711.37 5.60 705.76 0.00 0.00
May 1369.40 555.20 843.71 61.01 782.69 0.00 0.00
June 1928.61 296.47 897.14 110.45 786.69 0.00 0.00
July 1777.12 235.11 829.13 80.71 748.42 0.00 0.00
August 1383.27 320.30 699.14 14.30 684.84 0.00 0.00
September 1041.70 657.63 610.06 0.24 609.81 0.00 0.00
October 537.08 1053.15 506.52 0.00 506.52 0.00 0.00
November 138.75 1820.59 408.91 0.00 408.91 0.00 0.00
December 48.19 2372.37 382.56 0.00 382.56 0.00 0.00
               
Annual Sum or Average 813.75 1156.74 614.11 22.81 591.30 0.00 0.00
Minimum of Months 48.19 235.11 382.56 0.00 382.56 0.00 0.00
Maximum of Months 1928.61 2372.37 897.14 110.45 786.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 645.18 1316.96 687.45 372.92 314.53 0.00 0.00
February 1011.70 1177.97 919.75 524.25 395.50 0.00 0.00
March 1365.94 1005.59 1135.59 625.67 509.91 0.00 0.00
April 1973.55 609.77 1368.33 759.12 609.21 0.00 0.00
May 2312.18 376.61 1412.04 767.39 644.65 0.00 0.00
June 2631.59 195.64 1412.83 785.99 626.85 0.00 0.00
July 2373.22 157.55 1267.00 662.37 604.64 0.00 0.00
August 2171.98 213.76 1205.62 617.03 588.60 0.00 0.00
September 1997.28 421.89 1194.44 681.52 512.93 0.00 0.00
October 1287.90 673.30 918.60 495.76 422.84 0.00 0.00
November 890.33 1121.89 823.45 479.38 344.06 0.00 0.00
December 606.47 1450.12 686.86 363.92 322.95 0.00 0.00
               
Annual Sum or Average 1607.56 724.57 1086.12 594.29 491.83 0.00 0.00
Minimum of Months 606.47 157.55 686.86 363.92 314.53 0.00 0.00
Maximum of Months 2631.59 1450.12 1412.83 785.99 644.65 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3440.91 2047.04 2637.47 1998.16 639.31 0.00 0.00
February 3248.58 1850.46 2446.55 1724.78 721.77 0.00 0.00
March 2719.24 1628.42 1988.33 1146.46 841.86 0.00 0.00
April 2111.28 1016.50 1348.08 503.00 845.08 0.00 0.00
May 1688.20 600.68 952.67 133.34 819.33 0.00 0.00
June 1831.92 301.33 821.92 52.15 769.77 0.00 0.00
July 1849.31 243.73 837.85 77.67 760.18 0.00 0.00
August 2190.02 347.28 1068.03 282.71 785.32 0.00 0.00
September 3066.82 705.69 1667.08 866.10 800.97 0.00 0.00
October 3529.69 1104.51 2265.07 1531.34 733.73 0.00 0.00
November 3743.96 1768.14 2725.80 2078.09 647.71 0.00 0.00
December 3451.23 2203.42 2701.37 2027.77 673.60 0.00 0.00
               
Annual Sum or Average 2735.63 1147.92 1784.56 1031.22 753.34 0.00 0.00
Minimum of Months 1688.20 243.73 821.92 52.15 639.31 0.00 0.00
Maximum of Months 3743.96 2203.42 2725.80 2078.09 845.08 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 771.80 1425.58 724.16 407.82 316.33 0.00 0.00
February 934.96 1293.38 817.13 434.32 382.81 0.00 0.00
March 1405.58 1117.69 1113.52 596.81 516.71 0.00 0.00
April 1896.88 704.76 1279.90 691.30 588.60 0.00 0.00
May 2293.87 438.09 1378.57 737.60 640.97 0.00 0.00
June 2530.72 234.80 1341.93 720.77 621.17 0.00 0.00
July 2252.79 191.54 1190.87 591.77 599.10 0.00 0.00
August 2092.12 255.48 1153.30 587.77 565.53 0.00 0.00
September 2027.21 488.34 1179.43 657.06 522.37 0.00 0.00
October 1508.25 752.97 1015.29 592.56 422.74 0.00 0.00
November 1037.24 1237.59 852.19 518.89 333.30 0.00 0.00
December 692.28 1566.56 686.74 373.06 313.68 0.00 0.00
               
Annual Sum or Average 1623.17 806.48 1061.97 576.19 485.78 0.00 0.00
Minimum of Months 692.28 191.54 686.74 373.06 313.68 0.00 0.00
Maximum of Months 2530.72 1566.56 1378.57 737.60 640.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 102.59 1930.70 385.54 0.00 385.54 0.00 0.00
February 237.17 1747.28 470.79 0.00 470.79 0.00 0.00
March 451.02 1494.48 616.11 0.00 616.11 0.00 0.00
April 828.55 903.22 711.37 5.60 705.76 0.00 0.00
May 1362.44 548.11 843.71 61.01 782.69 0.00 0.00
June 1904.77 300.06 897.14 110.45 786.69 0.00 0.00
July 1748.03 241.32 829.13 80.71 748.42 0.00 0.00
August 1362.89 320.69 699.14 14.30 684.84 0.00 0.00
September 1035.05 647.38 610.06 0.24 609.81 0.00 0.00
October 560.20 980.31 506.52 0.00 506.52 0.00 0.00
November 170.69 1639.81 408.91 0.00 408.91 0.00 0.00
December 75.55 2144.80 382.56 0.00 382.56 0.00 0.00
               
Annual Sum or Average 822.90 1071.54 614.11 22.81 591.30 0.00 0.00
Minimum of Months 75.55 241.32 382.56 0.00 382.56 0.00 0.00
Maximum of Months 1904.77 2144.80 897.14 110.45 786.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 681.06 1196.75 687.45 372.92 314.53 0.00 0.00
February 1047.06 1089.66 919.75 524.25 395.50 0.00 0.00
March 1390.28 948.15 1135.59 625.67 509.91 0.00 0.00
April 1970.95 595.34 1368.33 759.12 609.21 0.00 0.00
May 2297.88 377.39 1412.04 767.39 644.65 0.00 0.00
June 2609.75 199.62 1412.83 785.99 626.85 0.00 0.00
July 2348.04 163.11 1267.00 662.37 604.64 0.00 0.00
August 2152.43 217.50 1205.62 617.03 588.60 0.00 0.00
September 1985.88 423.40 1194.44 681.52 512.93 0.00 0.00
October 1294.50 643.27 918.60 495.76 422.84 0.00 0.00
November 923.39 1029.96 823.45 479.38 344.06 0.00 0.00
December 646.65 1319.78 686.86 363.92 322.95 0.00 0.00
               
Annual Sum or Average 1614.12 681.66 1086.12 594.29 491.83 0.00 0.00
Minimum of Months 646.65 163.11 686.86 363.92 314.53 0.00 0.00
Maximum of Months 2609.75 1319.78 1412.83 785.99 644.65 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3492.59 1870.84 2637.47 1998.16 639.31 0.00 0.00
February 3290.38 1713.28 2446.55 1724.78 721.77 0.00 0.00
March 2750.48 1530.19 1988.33 1146.46 841.86 0.00 0.00
April 2111.75 979.69 1348.08 503.00 845.08 0.00 0.00
May 1676.48 592.18 952.67 133.34 819.33 0.00 0.00
June 1809.23 303.77 821.92 52.15 769.77 0.00 0.00
July 1820.30 249.61 837.85 77.67 760.18 0.00 0.00
August 2167.06 349.47 1068.03 282.71 785.32 0.00 0.00
September 3051.14 703.24 1667.08 866.10 800.97 0.00 0.00
October 3537.24 1057.16 2265.07 1531.34 733.73 0.00 0.00
November 3788.69 1635.85 2725.80 2078.09 647.71 0.00 0.00
December 3520.62 2015.94 2701.37 2027.77 673.60 0.00 0.00
               
Annual Sum or Average 2747.57 1080.21 1784.56 1031.22 753.34 0.00 0.00
Minimum of Months 1676.48 249.61 821.92 52.15 639.31 0.00 0.00
Maximum of Months 3788.69 2015.94 2725.80 2078.09 845.08 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 790.60 1315.76 724.16 407.82 316.33 0.00 0.00
February 950.83 1207.80 817.13 434.32 382.81 0.00 0.00
March 1418.40 1053.75 1113.52 596.81 516.71 0.00 0.00
April 1895.89 682.54 1279.90 691.30 588.60 0.00 0.00
May 2283.01 434.38 1378.57 737.60 640.97 0.00 0.00
June 2514.11 236.67 1341.93 720.77 621.17 0.00 0.00
July 2234.22 194.92 1190.87 591.77 599.10 0.00 0.00
August 2077.81 256.69 1153.30 587.77 565.53 0.00 0.00
September 2018.74 486.39 1179.43 657.06 522.37 0.00 0.00
October 1514.10 719.22 1015.29 592.56 422.74 0.00 0.00
November 1053.14 1145.11 852.19 518.89 333.30 0.00 0.00
December 713.65 1445.35 686.74 373.06 313.68 0.00 0.00
               
Annual Sum or Average 1624.84 762.64 1061.97 576.19 485.78 0.00 0.00
Minimum of Months 713.65 194.92 686.74 373.06 313.68 0.00 0.00
Maximum of Months 2514.11 1445.35 1378.57 737.60 640.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.104229E+09 0.641191E+10 0.103262E+10 0.00 0.103262E+10 0.00 0.00
February 0.372726E+09 0.513834E+10 0.113891E+10 0.00 0.113891E+10 0.00 0.00
March 0.963555E+09 0.478255E+10 0.165016E+10 0.00 0.165016E+10 0.00 0.00
April 0.200648E+10 0.262779E+10 0.184383E+10 14526506.15 0.182931E+10 0.00 0.00
May 0.362273E+10 0.153821E+10 0.225975E+10 0.163409E+09 0.209634E+10 0.00 0.00
June 0.495766E+10 0.749028E+09 0.232534E+10 0.286273E+09 0.203907E+10 0.00 0.00
July 0.470823E+10 0.609816E+09 0.222070E+10 0.216165E+09 0.200454E+10 0.00 0.00
August 0.360574E+10 0.876815E+09 0.187254E+10 38287940.38 0.183425E+10 0.00 0.00
September 0.264983E+10 0.176912E+10 0.158125E+10 630965.44 0.158062E+10 0.00 0.00
October 0.133173E+10 0.309196E+10 0.135664E+10 0.00 0.135664E+10 0.00 0.00
November 0.241602E+09 0.537440E+10 0.105988E+10 0.00 0.105988E+10 0.00 0.00
December 60784176.22 0.729209E+10 0.102462E+10 0.00 0.102462E+10 0.00 0.00
               
Annual Sum or Average 0.246253E+11 0.402620E+11 0.193662E+11 0.719292E+09 0.186469E+11 0.00 0.00
Minimum of Months 60784176.22 0.609816E+09 0.102462E+10 0.00 0.102462E+10 0.00 0.00
Maximum of Months 0.495766E+10 0.729209E+10 0.232534E+10 0.286273E+09 0.209634E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.165998E+10 0.385707E+10 0.184128E+10 0.998831E+09 0.842454E+09 0.00 0.00
February 0.239861E+10 0.306514E+10 0.222506E+10 0.126827E+10 0.956791E+09 0.00 0.00
March 0.363860E+10 0.283755E+10 0.304157E+10 0.167581E+10 0.136576E+10 0.00 0.00
April 0.515635E+10 0.156501E+10 0.354671E+10 0.196763E+10 0.157908E+10 0.00 0.00
May 0.623286E+10 0.101251E+10 0.378202E+10 0.205539E+10 0.172663E+10 0.00 0.00
June 0.686505E+10 0.461755E+09 0.366208E+10 0.203728E+10 0.162479E+10 0.00 0.00
July 0.640232E+10 0.362353E+09 0.339355E+10 0.177409E+10 0.161946E+10 0.00 0.00
August 0.585614E+10 0.505010E+09 0.322915E+10 0.165265E+10 0.157650E+10 0.00 0.00
September 0.520279E+10 0.109271E+10 0.309601E+10 0.176650E+10 0.132951E+10 0.00 0.00
October 0.343982E+10 0.189955E+10 0.246040E+10 0.132785E+10 0.113254E+10 0.00 0.00
November 0.225387E+10 0.315820E+10 0.213438E+10 0.124257E+10 0.891813E+09 0.00 0.00
December 0.155081E+10 0.425716E+10 0.183970E+10 0.974716E+09 0.864987E+09 0.00 0.00
               
Annual Sum or Average 0.506572E+11 0.240740E+11 0.342519E+11 0.187416E+11 0.155103E+11 0.00 0.00
Minimum of Months 0.155081E+10 0.362353E+09 0.183970E+10 0.974716E+09 0.842454E+09 0.00 0.00
Maximum of Months 0.686505E+10 0.425716E+10 0.378202E+10 0.205539E+10 0.172663E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.928128E+10 0.561610E+10 0.706398E+10 0.535169E+10 0.171229E+10 0.00 0.00
February 0.791126E+10 0.459716E+10 0.591851E+10 0.417245E+10 0.174607E+10 0.00 0.00
March 0.732693E+10 0.450650E+10 0.532539E+10 0.307059E+10 0.225480E+10 0.00 0.00
April 0.547361E+10 0.269776E+10 0.349414E+10 0.130374E+10 0.219040E+10 0.00 0.00
May 0.450242E+10 0.164754E+10 0.255159E+10 0.357134E+09 0.219446E+10 0.00 0.00
June 0.469209E+10 0.765124E+09 0.213037E+10 0.135170E+09 0.199520E+10 0.00 0.00
July 0.489950E+10 0.630702E+09 0.224407E+10 0.208026E+09 0.203604E+10 0.00 0.00
August 0.581265E+10 0.926729E+09 0.286055E+10 0.757197E+09 0.210336E+10 0.00 0.00
September 0.798533E+10 0.183410E+10 0.432095E+10 0.224487E+10 0.207608E+10 0.00 0.00
October 0.950954E+10 0.302278E+10 0.606658E+10 0.410140E+10 0.196518E+10 0.00 0.00
November 0.974287E+10 0.473211E+10 0.706506E+10 0.538623E+10 0.167883E+10 0.00 0.00
December 0.925063E+10 0.613442E+10 0.723513E+10 0.543101E+10 0.180412E+10 0.00 0.00
               
Annual Sum or Average 0.863881E+11 0.371110E+11 0.562763E+11 0.325195E+11 0.237568E+11 0.00 0.00
Minimum of Months 0.450242E+10 0.630702E+09 0.213037E+10 0.135170E+09 0.167883E+10 0.00 0.00
Maximum of Months 0.974287E+10 0.613442E+10 0.723513E+10 0.543101E+10 0.225480E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.198232E+10 0.428887E+10 0.193959E+10 0.109232E+10 0.847266E+09 0.00 0.00
February 0.215533E+10 0.358916E+10 0.197682E+10 0.105072E+10 0.926098E+09 0.00 0.00
March 0.363023E+10 0.346517E+10 0.298246E+10 0.159850E+10 0.138397E+10 0.00 0.00
April 0.478697E+10 0.209990E+10 0.331751E+10 0.179185E+10 0.152566E+10 0.00 0.00
May 0.612415E+10 0.125374E+10 0.369239E+10 0.197559E+10 0.171679E+10 0.00 0.00
June 0.649346E+10 0.650405E+09 0.347831E+10 0.186823E+10 0.161007E+10 0.00 0.00
July 0.592814E+10 0.576569E+09 0.318965E+10 0.158500E+10 0.160465E+10 0.00 0.00
August 0.543990E+10 0.868179E+09 0.308901E+10 0.157428E+10 0.151473E+10 0.00 0.00
September 0.521951E+10 0.134921E+10 0.305709E+10 0.170311E+10 0.135398E+10 0.00 0.00
October 0.394316E+10 0.229653E+10 0.271937E+10 0.158712E+10 0.113226E+10 0.00 0.00
November 0.255514E+10 0.381305E+10 0.220889E+10 0.134498E+10 0.863909E+09 0.00 0.00
December 0.170064E+10 0.509795E+10 0.183937E+10 0.999206E+09 0.840166E+09 0.00 0.00
               
Annual Sum or Average 0.499590E+11 0.293487E+11 0.334905E+11 0.181709E+11 0.153196E+11 0.00 0.00
Minimum of Months 0.170064E+10 0.576569E+09 0.183937E+10 0.999206E+09 0.840166E+09 0.00 0.00
Maximum of Months 0.649346E+10 0.509795E+10 0.369239E+10 0.197559E+10 0.171679E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.192462E+09 0.572773E+10 0.103263E+10 0.00 0.103263E+10 0.00 0.00
February 0.489431E+09 0.461881E+10 0.113893E+10 0.00 0.113893E+10 0.00 0.00
March 0.110564E+10 0.433129E+10 0.165018E+10 0.00 0.165018E+10 0.00 0.00
April 0.211616E+10 0.245954E+10 0.184386E+10 14526939.37 0.182933E+10 0.00 0.00
May 0.366779E+10 0.148704E+10 0.225978E+10 0.163414E+09 0.209637E+10 0.00 0.00
June 0.499897E+10 0.768447E+09 0.232538E+10 0.286281E+09 0.203910E+10 0.00 0.00
July 0.475984E+10 0.629713E+09 0.222074E+10 0.216172E+09 0.200456E+10 0.00 0.00
August 0.370494E+10 0.857897E+09 0.187256E+10 38289082.23 0.183427E+10 0.00 0.00
September 0.270008E+10 0.170458E+10 0.158127E+10 630984.26 0.158064E+10 0.00 0.00
October 0.143851E+10 0.282076E+10 0.135666E+10 0.00 0.135666E+10 0.00 0.00
November 0.359651E+09 0.471896E+10 0.105989E+10 0.00 0.105989E+10 0.00 0.00
December 0.129082E+09 0.635415E+10 0.102464E+10 0.00 0.102464E+10 0.00 0.00
               
Annual Sum or Average 0.256626E+11 0.364789E+11 0.193665E+11 0.719313E+09 0.186472E+11 0.00 0.00
Minimum of Months 0.129082E+09 0.629713E+09 0.102464E+10 0.00 0.102464E+10 0.00 0.00
Maximum of Months 0.499897E+10 0.635415E+10 0.232538E+10 0.286281E+09 0.209637E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.172806E+10 0.352734E+10 0.184128E+10 0.998827E+09 0.842450E+09 0.00 0.00
February 0.244751E+10 0.284974E+10 0.222505E+10 0.126827E+10 0.956787E+09 0.00 0.00
March 0.365854E+10 0.269338E+10 0.304156E+10 0.167580E+10 0.136576E+10 0.00 0.00
April 0.511544E+10 0.158054E+10 0.354670E+10 0.196763E+10 0.157907E+10 0.00 0.00
May 0.619295E+10 0.100871E+10 0.378200E+10 0.205538E+10 0.172662E+10 0.00 0.00
June 0.682108E+10 0.507104E+09 0.366206E+10 0.203728E+10 0.162479E+10 0.00 0.00
July 0.635642E+10 0.421982E+09 0.339354E+10 0.177408E+10 0.161946E+10 0.00 0.00
August 0.581743E+10 0.572537E+09 0.322914E+10 0.165264E+10 0.157649E+10 0.00 0.00
September 0.517695E+10 0.109353E+10 0.309600E+10 0.176649E+10 0.132951E+10 0.00 0.00
October 0.344952E+10 0.180337E+10 0.246039E+10 0.132785E+10 0.113254E+10 0.00 0.00
November 0.230774E+10 0.290794E+10 0.213437E+10 0.124256E+10 0.891809E+09 0.00 0.00
December 0.162437E+10 0.388400E+10 0.183970E+10 0.974712E+09 0.864984E+09 0.00 0.00
               
Annual Sum or Average 0.506960E+11 0.228502E+11 0.342518E+11 0.187415E+11 0.155103E+11 0.00 0.00
Minimum of Months 0.162437E+10 0.421982E+09 0.183970E+10 0.974712E+09 0.842450E+09 0.00 0.00
Maximum of Months 0.682108E+10 0.388400E+10 0.378200E+10 0.205538E+10 0.172662E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.921613E+10 0.548278E+10 0.706420E+10 0.535187E+10 0.171233E+10 0.00 0.00
February 0.785897E+10 0.447664E+10 0.591869E+10 0.417258E+10 0.174610E+10 0.00 0.00
March 0.728322E+10 0.436157E+10 0.532554E+10 0.307069E+10 0.225485E+10 0.00 0.00
April 0.547244E+10 0.263476E+10 0.349422E+10 0.130378E+10 0.219044E+10 0.00 0.00
May 0.452168E+10 0.160886E+10 0.255164E+10 0.357146E+09 0.219449E+10 0.00 0.00
June 0.474833E+10 0.781053E+09 0.213041E+10 0.135175E+09 0.199523E+10 0.00 0.00
July 0.495318E+10 0.652803E+09 0.224411E+10 0.208032E+09 0.203607E+10 0.00 0.00
August 0.586575E+10 0.930149E+09 0.286062E+10 0.757222E+09 0.210339E+10 0.00 0.00
September 0.794920E+10 0.182916E+10 0.432106E+10 0.224494E+10 0.207612E+10 0.00 0.00
October 0.945392E+10 0.295832E+10 0.606675E+10 0.410153E+10 0.196522E+10 0.00 0.00
November 0.970436E+10 0.458302E+10 0.706527E+10 0.538640E+10 0.167887E+10 0.00 0.00
December 0.924377E+10 0.590164E+10 0.723536E+10 0.543119E+10 0.180417E+10 0.00 0.00
               
Annual Sum or Average 0.862710E+11 0.362008E+11 0.562779E+11 0.325206E+11 0.237573E+11 0.00 0.00
Minimum of Months 0.452168E+10 0.652803E+09 0.213041E+10 0.135175E+09 0.167887E+10 0.00 0.00
Maximum of Months 0.970436E+10 0.590164E+10 0.723536E+10 0.543119E+10 0.225485E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.206719E+10 0.381827E+10 0.193958E+10 0.109232E+10 0.847263E+09 0.00 0.00
February 0.226187E+10 0.312894E+10 0.197681E+10 0.105072E+10 0.926094E+09 0.00 0.00
March 0.376471E+10 0.299361E+10 0.298245E+10 0.159849E+10 0.138396E+10 0.00 0.00
April 0.491672E+10 0.182673E+10 0.331750E+10 0.179184E+10 0.152566E+10 0.00 0.00
May 0.614391E+10 0.117339E+10 0.369237E+10 0.197559E+10 0.171679E+10 0.00 0.00
June 0.655963E+10 0.608609E+09 0.347829E+10 0.186823E+10 0.161007E+10 0.00 0.00
July 0.603386E+10 0.513033E+09 0.318963E+10 0.158499E+10 0.160464E+10 0.00 0.00
August 0.560354E+10 0.684275E+09 0.308900E+10 0.157427E+10 0.151472E+10 0.00 0.00
September 0.525452E+10 0.126577E+10 0.305708E+10 0.170310E+10 0.135398E+10 0.00 0.00
October 0.403970E+10 0.201675E+10 0.271936E+10 0.158711E+10 0.113225E+10 0.00 0.00
November 0.268853E+10 0.320783E+10 0.220888E+10 0.134497E+10 0.863906E+09 0.00 0.00
December 0.185419E+10 0.419587E+10 0.183936E+10 0.999202E+09 0.840163E+09 0.00 0.00
               
Annual Sum or Average 0.511884E+11 0.254331E+11 0.334903E+11 0.181708E+11 0.153195E+11 0.00 0.00
Minimum of Months 0.185419E+10 0.513033E+09 0.183936E+10 0.999202E+09 0.840163E+09 0.00 0.00
Maximum of Months 0.655963E+10 0.419587E+10 0.369237E+10 0.197559E+10 0.171679E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.274776E+09 0.517119E+10 0.103263E+10 0.00 0.103263E+10 0.00 0.00
February 0.573769E+09 0.422703E+10 0.113893E+10 0.00 0.113893E+10 0.00 0.00
March 0.120801E+10 0.400283E+10 0.165018E+10 0.00 0.165018E+10 0.00 0.00
April 0.214760E+10 0.234116E+10 0.184386E+10 14526939.37 0.182933E+10 0.00 0.00
May 0.364916E+10 0.146805E+10 0.225978E+10 0.163414E+09 0.209637E+10 0.00 0.00
June 0.493717E+10 0.777744E+09 0.232538E+10 0.286281E+09 0.203910E+10 0.00 0.00
July 0.468193E+10 0.646356E+09 0.222074E+10 0.216172E+09 0.200456E+10 0.00 0.00
August 0.365036E+10 0.858942E+09 0.187256E+10 38289082.23 0.183427E+10 0.00 0.00
September 0.268285E+10 0.167801E+10 0.158127E+10 630984.26 0.158064E+10 0.00 0.00
October 0.150043E+10 0.262567E+10 0.135666E+10 0.00 0.135666E+10 0.00 0.00
November 0.442430E+09 0.425038E+10 0.105989E+10 0.00 0.105989E+10 0.00 0.00
December 0.202361E+09 0.574463E+10 0.102464E+10 0.00 0.102464E+10 0.00 0.00
               
Annual Sum or Average 0.259508E+11 0.337920E+11 0.193665E+11 0.719313E+09 0.186472E+11 0.00 0.00
Minimum of Months 0.202361E+09 0.646356E+09 0.102464E+10 0.00 0.102464E+10 0.00 0.00
Maximum of Months 0.493717E+10 0.574463E+10 0.232538E+10 0.286281E+09 0.209637E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.182415E+10 0.320537E+10 0.184128E+10 0.998827E+09 0.842450E+09 0.00 0.00
February 0.253305E+10 0.263610E+10 0.222505E+10 0.126827E+10 0.956787E+09 0.00 0.00
March 0.372372E+10 0.253952E+10 0.304156E+10 0.167580E+10 0.136576E+10 0.00 0.00
April 0.510870E+10 0.154311E+10 0.354670E+10 0.196763E+10 0.157907E+10 0.00 0.00
May 0.615464E+10 0.101081E+10 0.378200E+10 0.205538E+10 0.172662E+10 0.00 0.00
June 0.676448E+10 0.517402E+09 0.366206E+10 0.203728E+10 0.162479E+10 0.00 0.00
July 0.628900E+10 0.436883E+09 0.339354E+10 0.177408E+10 0.161946E+10 0.00 0.00
August 0.576508E+10 0.582550E+09 0.322914E+10 0.165264E+10 0.157649E+10 0.00 0.00
September 0.514740E+10 0.109746E+10 0.309600E+10 0.176649E+10 0.132951E+10 0.00 0.00
October 0.346718E+10 0.172294E+10 0.246039E+10 0.132785E+10 0.113254E+10 0.00 0.00
November 0.239343E+10 0.266965E+10 0.213437E+10 0.124256E+10 0.891809E+09 0.00 0.00
December 0.173199E+10 0.353490E+10 0.183970E+10 0.974712E+09 0.864984E+09 0.00 0.00
               
Annual Sum or Average 0.509028E+11 0.214967E+11 0.342518E+11 0.187415E+11 0.155103E+11 0.00 0.00
Minimum of Months 0.173199E+10 0.436883E+09 0.183970E+10 0.974712E+09 0.842450E+09 0.00 0.00
Maximum of Months 0.676448E+10 0.353490E+10 0.378200E+10 0.205538E+10 0.172662E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.935456E+10 0.501085E+10 0.706420E+10 0.535187E+10 0.171233E+10 0.00 0.00
February 0.796009E+10 0.414477E+10 0.591869E+10 0.417258E+10 0.174610E+10 0.00 0.00
March 0.736688E+10 0.409846E+10 0.532554E+10 0.307069E+10 0.225485E+10 0.00 0.00
April 0.547366E+10 0.253935E+10 0.349422E+10 0.130378E+10 0.219044E+10 0.00 0.00
May 0.449030E+10 0.158610E+10 0.255164E+10 0.357146E+09 0.219449E+10 0.00 0.00
June 0.468952E+10 0.787381E+09 0.213041E+10 0.135175E+09 0.199523E+10 0.00 0.00
July 0.487549E+10 0.668567E+09 0.224411E+10 0.208032E+09 0.203607E+10 0.00 0.00
August 0.580427E+10 0.936019E+09 0.286062E+10 0.757222E+09 0.210339E+10 0.00 0.00
September 0.790855E+10 0.182279E+10 0.432106E+10 0.224494E+10 0.207612E+10 0.00 0.00
October 0.947414E+10 0.283151E+10 0.606675E+10 0.410153E+10 0.196522E+10 0.00 0.00
November 0.982027E+10 0.424011E+10 0.706527E+10 0.538640E+10 0.167887E+10 0.00 0.00
December 0.942964E+10 0.539948E+10 0.723536E+10 0.543119E+10 0.180417E+10 0.00 0.00
               
Annual Sum or Average 0.866473E+11 0.340654E+11 0.562779E+11 0.325206E+11 0.237573E+11 0.00 0.00
Minimum of Months 0.449030E+10 0.668567E+09 0.213041E+10 0.135175E+09 0.167887E+10 0.00 0.00
Maximum of Months 0.982027E+10 0.539948E+10 0.723536E+10 0.543119E+10 0.225485E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.211755E+10 0.352414E+10 0.193958E+10 0.109232E+10 0.847263E+09 0.00 0.00
February 0.230024E+10 0.292190E+10 0.197681E+10 0.105072E+10 0.926094E+09 0.00 0.00
March 0.379905E+10 0.282238E+10 0.298245E+10 0.159849E+10 0.138396E+10 0.00 0.00
April 0.491415E+10 0.176915E+10 0.331750E+10 0.179184E+10 0.152566E+10 0.00 0.00
May 0.611480E+10 0.116345E+10 0.369237E+10 0.197559E+10 0.171679E+10 0.00 0.00
June 0.651656E+10 0.613456E+09 0.347829E+10 0.186823E+10 0.161007E+10 0.00 0.00
July 0.598414E+10 0.522072E+09 0.318963E+10 0.158499E+10 0.160464E+10 0.00 0.00
August 0.556522E+10 0.687521E+09 0.308900E+10 0.157427E+10 0.151472E+10 0.00 0.00
September 0.523258E+10 0.126072E+10 0.305708E+10 0.170310E+10 0.135398E+10 0.00 0.00
October 0.405537E+10 0.192635E+10 0.271936E+10 0.158711E+10 0.113225E+10 0.00 0.00
November 0.272974E+10 0.296811E+10 0.220888E+10 0.134497E+10 0.863906E+09 0.00 0.00
December 0.191145E+10 0.387124E+10 0.183936E+10 0.999202E+09 0.840163E+09 0.00 0.00
               
Annual Sum or Average 0.512409E+11 0.240505E+11 0.334903E+11 0.181708E+11 0.153195E+11 0.00 0.00
Minimum of Months 0.191145E+10 0.522072E+09 0.183936E+10 0.999202E+09 0.840163E+09 0.00 0.00
Maximum of Months 0.651656E+10 0.387124E+10 0.369237E+10 0.197559E+10 0.171679E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 8.14 3.28 -3.0 3.49 -5.4 41.12 223.64 0.00
February 10.27 3.71 -4.6 3.82 -5.0 51.61 245.22 0.00
March 12.55 4.68 -5.5 4.62 -3.1 72.41 273.25 0.00
April 19.23 8.50 -2.7 4.72 3.38 79.21 314.56 0.00
May 23.84 12.23 2.64 5.25 8.38 86.83 326.20 0.00
June 27.86 15.03 5.88 4.15 14.09 80.19 344.14 0.01
July 27.54 18.92 14.64 3.53 17.44 86.25 283.04 0.01
August 26.28 17.11 12.00 3.28 15.48 80.55 269.68 0.02
September 23.38 15.82 11.20 2.23 11.29 66.71 294.09 0.00
October 18.30 12.02 7.27 3.24 6.21 54.59 257.93 0.01
November 11.18 5.22 -1.5 3.40 -3.3 40.23 258.80 0.00
December 6.79 1.84 -4.8 2.82 -8.9 42.65 217.21 0.00
                 
Annual Sum or Average 17.98 9.90 2.67 3.71 4.26 65.29 275.60 0.00
Minimum of Months 6.79 1.84 -5.5 2.23 -8.9 40.23 217.21 0.00
Maximum of Months 27.86 18.92 14.64 5.25 17.44 86.83 344.14 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 20.60 03-JAN-14:00 8.39 -5.0 9.80 2.22 118.50 530.50
February 23.30 20-FEB-14:00 8.88 -7.8 4.10 4.10 55.00 955.00
March 25.00 21-MAR-15:00 9.53 -8.3 6.20 5.54 50.00 873.00
April 32.20 21-APR-13:00 15.21 2.80 13.90 18.28 265.50 638.50
May 35.00 19-MAY-13:00 17.23 6.10 10.30 21.78 145.00 874.50
June 38.90 02-JUN-15:00 16.22 -1.1 4.60 20.40 234.50 284.00
July 38.30 01-JUL-16:00 19.19 8.90 3.60 26.81 165.50 256.50
August 37.20 07-AUG-15:00 17.89 6.70 5.70 24.66 143.50 615.00
September 33.90 19-SEP-13:00 16.85 6.70 3.10 17.75 113.00 912.00
October 32.80 01-OCT-14:00 15.90 4.40 5.70 16.12 127.50 736.50
November 23.90 03-NOV-15:00 13.45 6.10 5.70 12.22 48.50 648.50
December 18.30 10-DEC-14:00 7.97 -2.8 7.20 4.10 123.00 52.50
                 
Annual Sum or Average                
Minimum of Months 18.30   7.97 -8.3 3.10 2.22 48.50 52.50
Maximum of Months 38.90   19.19 8.90 13.90 26.81 265.50 955.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -4.4 27-JAN-06:00 -7.5 -15.0 3.60 -23.6 0.00 0.00
February -5.6 03-FEB-06:00 -7.5 -11.7 1.50 -23.9 0.00 0.00
March -3.9 02-MAR-04:00 -6.5 -12.8 1.50 -21.3 0.00 0.00
April 3.30 12-APR-05:00 -1.8 -9.4 2.10 -14.9 37.00 217.50
May 9.40 02-MAY-05:00 3.98 -2.2 3.60 -7.6 51.00 277.50
June 15.00 13-JUN-04:00 4.43 -10.6 2.10 -4.3 0.00 0.00
July 17.80 05-JUL-05:00 15.98 15.00 4.10 4.31 39.00 249.00
August 16.70 31-AUG-05:00 13.89 12.20 4.10 2.64 36.00 126.50
September 8.30 30-SEP-05:00 5.77 3.30 1.50 -7.3 0.00 0.00
October 6.70 11-OCT-05:00 5.82 5.00 1.50 -5.5 0.00 0.00
November -0.6 17-NOV-03:00 -3.1 -6.7 1.50 -18.1 0.00 0.00
December -4.4 27-DEC-06:00 -5.1 -6.1 2.10 -18.6 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -5.6   -7.5 -15.0 1.50 -23.9 0.00 0.00
Maximum of Months 17.80   15.98 15.00 4.10 4.31 51.00 277.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.18 12-JAN-15:00 18.90 2.80 3.60 6.15 70.50 491.50
February 11.42 13-FEB-16:00 12.80 10.60 4.10 6.55 34.00 18.50
March 10.75 10-MAR-18:00 13.30 8.90 1.50 8.54 0.00 0.00
April 15.74 29-APR-13:00 30.00 6.70 4.10 18.28 336.50 432.50
May 19.12 24-MAY-12:00 27.80 15.00 5.20 17.57 188.50 862.00
June 20.21 03-JUN-14:00 33.90 13.90 8.80 23.66 264.50 316.00
July 22.88 20-JUL-15:39 25.53 21.87 2.93 18.99 184.00 15.83
August 21.18 02-AUG-11:00 30.60 17.20 3.60 20.75 154.50 850.00
September 20.65 14-SEP-09:00 25.00 18.90 2.10 14.47 126.50 835.50
October 19.64 03-OCT-13:00 32.80 13.30 2.60 21.44 224.50 577.50
November 13.57 03-NOV-14:00 23.30 7.20 0.00 10.88 72.50 802.00
December 8.30 10-DEC-12:00 17.20 -0.6 5.70 1.58 198.50 507.50
                 
Annual Sum or Average                
Minimum of Months 8.30   12.80 -0.6 0.00 1.58 0.00 0.00
Maximum of Months 22.88   33.90 21.87 8.80 23.66 336.50 862.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.00 16-JAN-01:00 9.00 9.00 2.10 4.51 0.00 0.00
February 10.60 13-FEB-13:09 12.20 11.24 5.53 5.71 147.33 0.00
March 10.00 11-MAR-00:00 10.60 10.24 2.10 6.15 0.00 0.00
April 10.60 17-APR-01:00 17.80 13.38 7.20 3.48 0.00 0.00
May 15.00 24-MAY-10:00 25.60 18.41 7.20 15.39 171.00 872.50
June 17.20 19-JUN-17:00 23.90 19.20 3.60 15.39 86.00 324.00
July 22.20 20-JUL-14:00 24.40 22.82 4.60 17.93 283.00 59.50
August 18.90 01-AUG-20:00 22.20 19.91 4.60 17.75 0.00 0.00
September 19.40 22-SEP-01:00 20.60 19.76 1.50 16.30 0.00 0.00
October 17.20 03-OCT-19:00 23.30 19.11 4.60 18.46 0.00 0.00
November 10.00 01-NOV-09:00 13.30 11.28 3.10 8.94 123.50 0.00
December 6.10 13-DEC-00:00 8.30 7.10 7.70 3.06 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.10   8.30 7.10 1.50 3.06 0.00 0.00
Maximum of Months 22.20   25.60 22.82 7.70 18.46 283.00 872.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 15.16 28.38 0.00
February 18.00 13.00 16.00 15.21 35.58 0.00
March 18.00 13.00 16.00 16.80 47.71 0.00
April 18.00 13.00 16.00 19.62 58.45 0.00
May 18.00 13.00 16.00 22.88 63.58 0.00
June 18.00 13.00 16.00 25.71 66.73 0.00
July 18.00 13.00 16.00 27.35 58.19 0.00
August 18.00 13.00 16.00 27.33 54.44 0.00
September 18.00 13.00 16.00 25.68 50.89 0.00
October 18.00 13.00 16.00 22.83 39.37 0.00
November 18.00 13.00 16.00 19.57 32.11 0.00
December 18.00 13.00 16.00 16.77 26.90 0.00
             
Annual Sum or Average 18.00 13.00 16.00 21.28 46.90 0.00
Minimum of Months 18.00 13.00 16.00 15.16 26.90 0.00
Maximum of Months 18.00 13.00 16.00 27.35 66.73 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.359152E+11 -0.348912E+11 0.00 0.00 744.00 0.00 -0.102402E+10 58.98 0.00 0.00
February 0.326067E+11 -0.316807E+11 0.00 0.00 672.00 0.00 -926019512.6 58.97 0.00 0.00
March 0.369200E+11 -0.358913E+11 0.00 0.00 744.00 0.00 -0.102870E+10 58.98 0.00 0.00
April 0.313742E+11 -0.303834E+11 0.00 0.00 720.00 0.00 -990796921.9 58.97 0.00 0.00
May 0.308179E+11 -0.297938E+11 0.00 0.00 744.00 0.00 -0.102410E+10 58.97 0.00 0.00
June 0.281777E+11 -0.271859E+11 0.00 0.00 720.00 0.00 -991795257.5 58.97 0.00 0.00
July 0.255975E+11 -0.245789E+11 0.00 0.00 744.00 0.00 -0.101857E+10 58.97 0.00 0.00
August 0.279610E+11 -0.269388E+11 0.00 0.00 744.00 0.00 -0.102222E+10 58.97 0.00 0.00
September 0.267217E+11 -0.257351E+11 0.00 0.00 720.00 0.00 -986648414.3 58.98 0.00 0.00
October 0.298224E+11 -0.288039E+11 0.00 0.00 744.00 0.00 -0.101850E+10 58.97 0.00 0.00
November 0.317727E+11 -0.307864E+11 0.00 0.00 720.00 0.00 -986343163.0 58.97 0.00 0.00
December 0.338234E+11 -0.328033E+11 0.00 0.00 744.00 0.00 -0.102009E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.371510E+12 -0.359473E+12 0.00 0.00 8760.00 0.00 -0.120378E+11 58.97 0.00 0.00
Minimum of Months 0.255975E+11 -0.358913E+11 0.00 0.00 672.00 0.00 -0.102870E+10 58.97 0.00 0.00
Maximum of Months 0.369200E+11 -0.245789E+11 0.00 0.00 744.00 0.00 -926019512.6 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.63 0.61 01-JAN-07:00 7632.87 36.80 265.17 273.17 1471.33 26.29 152.50 256.83
February 268.33 0.63 0.61 01-FEB-07:49 8317.43 36.28 261.50 263.83 1040.74 21.94 101.50 235.83
March 351.83 0.64 0.61 01-MAR-07:10 1578.99 16.90 10.67 309.00 783.54 19.31 73.83 272.83
April 373.83 0.64 0.61 01-APR-06:30 969.56 16.09 0.00 321.33 591.14 19.01 13.00 271.33
May 408.83 0.65 0.61 01-MAY-06:19 796.43 15.65 0.00 345.00 486.66 18.59 0.17 285.00
June 398.00 0.64 0.61 01-JUN-06:19 711.75 15.45 0.00 337.00 448.17 18.52 0.00 266.67
July 400.17 0.65 0.61 01-JUL-06:19 761.56 15.53 0.00 341.17 459.64 18.52 0.67 256.83
August 377.83 0.64 0.61 01-AUG-06:19 899.52 16.02 0.00 330.83 538.97 18.93 7.00 268.83
September 365.83 0.64 0.61 01-SEP-06:00 1148.48 16.56 11.00 302.00 663.64 18.99 43.33 259.00
October 318.83 0.63 0.61 01-OCT-06:49 2977.83 23.65 128.33 302.50 917.04 19.95 65.83 269.50
November 295.83 0.63 0.61 01-NOV-12:39 7831.14 35.91 278.50 279.00 1148.67 22.89 94.67 263.33
December 289.50 0.63 0.61 01-DEC-07:19 6907.55 37.20 284.00 272.17 1450.99 26.32 160.00 264.33
                         
Annual Sum or Average 4125.67 0.64     2957.68 22.23 1239.17 3677.00 786.10 20.43 712.50 3170.33
Minimum of Months 268.33 0.63 0.61   711.75 15.45 0.00 263.83 448.17 18.52 0.00 235.83
Maximum of Months 408.83 0.65 0.61   8317.43 37.20 284.00 345.00 1471.33 26.32 160.00 285.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.65 0.61 01-JAN-08:09 1903.85 18.15 79.33 223.00 1089.13 18.56 63.33 158.83
February 268.33 0.65 0.61 01-FEB-07:49 2210.92 17.46 68.67 229.00 850.09 16.51 40.67 169.17
March 351.83 0.64 0.61 01-MAR-06:00 2085.96 14.48 51.83 284.33 1140.36 13.00 1.83 241.67
April 373.83 0.64 0.61 01-APR-06:10 2794.88 11.33 0.00 318.83 1000.78 12.93 0.00 277.83
May 408.83 0.64 0.61 01-MAY-05:49 2121.79 11.36 0.00 347.33 1174.42 12.89 0.00 303.00
June 398.00 0.64 0.61 01-JUN-05:49 2164.46 11.32 0.00 341.83 1208.59 12.86 0.00 298.00
July 400.17 0.64 0.61 01-JUL-05:49 1921.68 11.40 0.00 345.17 1035.80 12.89 0.00 291.17
August 377.83 0.64 0.61 01-AUG-05:49 2493.94 11.87 5.50 328.00 925.69 13.11 0.00 280.17
September 365.83 0.64 0.61 01-SEP-06:10 2258.49 14.43 57.50 291.50 888.57 13.04 5.50 253.17
October 318.83 0.65 0.61 01-OCT-06:49 2012.36 16.75 77.50 266.00 1108.43 16.11 48.67 203.50
November 295.83 0.66 0.61 01-NOV-12:39 1651.92 16.80 73.33 225.83 838.99 16.37 50.33 160.83
December 289.50 0.65 0.61 01-DEC-07:10 1347.52 16.71 61.83 225.17 748.27 17.48 50.33 169.50
                         
Annual Sum or Average 4125.67 0.65     2105.33 13.98 475.50 3426.00 1011.63 14.37 260.67 2806.83
Minimum of Months 268.33 0.64 0.61   1347.52 11.32 0.00 223.00 748.27 12.86 0.00 158.83
Maximum of Months 408.83 0.66 0.61   2794.88 18.15 79.33 347.33 1208.59 18.56 63.33 303.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.67 0.61 01-JAN-08:30 391.59 0.00 0.00 170.83 265.12 0.00 0.00 36.50
February 268.33 0.66 0.61 01-FEB-08:39 446.95 0.00 0.00 193.00 301.59 0.00 0.00 83.17
March 351.83 0.65 0.61 01-MAR-07:30 531.99 0.00 0.00 269.67 344.07 0.00 0.00 168.33
April 373.83 0.63 0.61 01-APR-06:19 631.42 0.00 0.00 341.50 406.26 0.00 0.00 262.33
May 408.83 0.63 0.61 01-MAY-05:00 786.06 0.00 0.00 379.33 452.06 0.00 0.00 337.00
June 398.00 0.62 0.61 01-JUN-05:49 846.77 0.00 0.00 377.00 475.03 0.00 0.00 342.50
July 400.17 0.63 0.61 01-JUL-05:49 799.66 0.00 0.00 381.00 482.02 0.00 0.00 326.33
August 377.83 0.63 0.61 01-AUG-05:00 669.30 0.00 0.00 349.17 422.76 0.00 0.00 282.33
September 365.83 0.65 0.61 01-SEP-07:19 526.42 0.00 0.00 276.83 348.06 0.00 0.00 175.83
October 318.83 0.65 0.61 01-OCT-07:19 471.23 0.00 0.00 248.33 314.64 0.00 0.00 109.67
November 295.83 0.67 0.61 01-NOV-12:39 379.77 0.00 0.00 171.83 260.10 0.00 0.00 29.67
December 289.50 0.67 0.61 01-DEC-08:09 392.01 0.00 0.00 180.00 260.50 0.00 0.00 24.67
                         
Annual Sum or Average 4125.67 0.64     594.20 0.00 0.00 3338.50 371.76 0.00 0.00 2178.33
Minimum of Months 268.33 0.62 0.61   379.77 0.00 0.00 170.83 260.10 0.00 0.00 24.67
Maximum of Months 408.83 0.67 0.61   846.77 0.00 0.00 381.00 482.02 0.00 0.00 342.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.64 0.61 01-JAN-08:39 1622.75 18.54 81.00 231.17 830.85 17.61 52.33 166.50
February 268.33 0.64 0.61 01-FEB-08:50 1838.02 17.40 70.17 226.33 1024.39 18.39 59.33 177.33
March 351.83 0.64 0.61 01-MAR-07:49 2270.20 16.59 83.83 293.83 882.81 13.17 2.83 244.50
April 373.83 0.64 0.61 01-APR-07:19 2748.34 14.27 55.00 320.67 983.79 12.98 0.00 277.67
May 408.83 0.64 0.61 01-MAY-06:30 2017.87 11.41 0.00 355.67 1145.36 13.06 1.67 315.33
June 398.00 0.63 0.61 01-JUN-06:30 2095.22 11.43 0.00 351.83 1182.72 15.18 45.00 305.33
July 400.17 0.63 0.61 01-JUL-06:40 1867.11 11.56 0.00 352.83 1053.40 13.06 0.00 290.50
August 377.83 0.64 0.61 01-AUG-06:30 1928.99 11.77 4.67 326.83 1008.71 13.04 0.00 280.67
September 365.83 0.64 0.61 01-SEP-07:49 2252.86 14.46 57.67 289.83 880.24 13.13 5.50 245.17
October 318.83 0.64 0.61 01-OCT-07:30 1967.08 17.38 81.83 276.33 1008.48 16.80 55.00 220.83
November 295.83 0.65 0.61 01-NOV-12:39 1314.11 15.56 56.50 226.83 739.61 16.97 53.17 172.00
December 289.50 0.65 0.61 01-DEC-08:20 1543.30 17.80 77.83 226.83 660.17 17.89 50.50 166.67
                         
Annual Sum or Average 4125.67 0.64     1985.21 14.50 568.50 3479.00 964.30 14.83 325.33 2862.50
Minimum of Months 268.33 0.63 0.61   1314.11 11.41 0.00 226.33 660.17 12.98 0.00 166.50
Maximum of Months 408.83 0.65 0.61   2748.34 18.54 83.83 355.67 1182.72 18.39 59.33 315.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.63 0.61 01-JAN-08:09 7535.71 34.77 252.50 268.33 1483.35 20.92 86.33 253.67
February 268.33 0.63 0.61 01-FEB-07:49 8317.29 35.93 261.17 263.17 1085.69 17.56 34.67 236.67
March 351.83 0.64 0.61 01-MAR-07:10 1571.59 10.89 10.67 308.00 817.29 15.17 1.83 274.83
April 373.83 0.64 0.61 01-APR-06:30 961.24 10.59 0.00 319.33 613.76 15.49 0.00 273.33
May 408.83 0.65 0.61 01-MAY-06:19 786.60 10.51 0.00 343.00 503.10 15.33 0.00 290.17
June 398.00 0.64 0.61 01-JUN-06:19 703.58 10.19 0.00 336.50 463.24 15.17 0.00 274.00
July 400.17 0.65 0.61 01-JUL-06:30 750.69 10.27 0.00 340.17 474.47 15.16 0.00 263.33
August 377.83 0.64 0.61 01-AUG-06:19 888.79 10.65 0.00 328.00 557.73 15.48 0.00 271.83
September 365.83 0.64 0.61 01-SEP-06:00 1147.76 10.87 11.00 302.17 691.15 15.19 0.00 261.67
October 318.83 0.63 0.61 01-OCT-06:49 2999.59 19.41 127.83 306.17 966.81 15.90 13.33 272.00
November 295.83 0.63 0.61 01-NOV-12:39 7823.79 34.96 274.83 278.33 1228.71 20.37 90.00 269.00
December 289.50 0.63 0.61 01-DEC-07:19 6766.92 34.14 259.83 265.33 1497.47 22.17 101.33 264.83
                         
Annual Sum or Average 4125.67 0.64     2937.19 17.92 1197.83 3658.50 816.28 16.71 327.50 3205.33
Minimum of Months 268.33 0.63 0.61   703.58 10.19 0.00 263.17 463.24 15.16 0.00 236.67
Maximum of Months 408.83 0.65 0.61   8317.29 35.93 274.83 343.00 1497.47 22.17 101.33 290.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.65 0.61 01-JAN-08:09 1906.76 16.15 79.33 223.00 1111.17 16.79 63.33 163.50
February 268.33 0.65 0.61 01-FEB-07:49 2214.48 15.27 68.67 228.50 874.39 14.52 40.67 174.83
March 351.83 0.65 0.61 01-MAR-06:00 2098.34 11.73 51.83 284.67 1074.90 10.44 1.83 245.17
April 373.83 0.64 0.61 01-APR-06:10 2569.91 7.83 0.00 318.50 1032.08 10.47 0.00 283.17
May 408.83 0.64 0.61 01-MAY-05:49 2111.61 7.93 0.00 346.83 1207.13 10.56 0.00 309.50
June 398.00 0.64 0.61 01-JUN-05:49 2165.07 7.80 0.00 340.67 1240.14 10.51 0.00 303.17
July 400.17 0.64 0.61 01-JUL-05:49 1900.26 7.94 0.00 344.00 1064.33 10.56 0.00 295.17
August 377.83 0.64 0.61 01-AUG-05:49 2318.44 8.50 5.50 328.00 953.96 10.74 0.00 285.50
September 365.83 0.64 0.61 01-SEP-06:10 2268.97 11.65 57.50 290.50 916.41 10.57 5.50 258.83
October 318.83 0.65 0.61 01-OCT-06:49 2020.19 14.55 77.50 266.17 1133.49 14.20 48.67 210.17
November 295.83 0.66 0.61 01-NOV-12:39 1656.59 14.62 73.33 227.00 861.93 14.43 50.33 166.00
December 289.50 0.65 0.61 01-DEC-07:10 1347.85 14.45 61.83 224.67 767.56 15.50 50.33 174.17
                         
Annual Sum or Average 4125.67 0.65     2069.22 11.09 475.50 3422.50 1030.99 12.13 260.67 2869.17
Minimum of Months 268.33 0.64 0.61   1347.85 7.80 0.00 223.00 767.56 10.44 0.00 163.50
Maximum of Months 408.83 0.66 0.61   2569.91 16.15 79.33 346.83 1240.14 16.79 63.33 309.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.67 0.61 01-JAN-08:39 385.15 0.00 0.00 164.67 272.80 0.00 0.00 46.50
February 268.33 0.66 0.61 01-FEB-08:39 440.54 0.00 0.00 190.83 310.78 0.00 0.00 92.17
March 351.83 0.65 0.61 01-MAR-07:40 525.60 0.00 0.00 267.67 355.35 0.00 0.00 183.17
April 373.83 0.63 0.61 01-APR-06:19 624.51 0.00 0.00 340.50 419.48 0.00 0.00 270.67
May 408.83 0.63 0.61 01-MAY-05:00 777.86 0.00 0.00 379.17 467.21 0.00 0.00 341.67
June 398.00 0.62 0.61 01-JUN-05:49 839.33 0.00 0.00 376.50 491.41 0.00 0.00 345.17
July 400.17 0.63 0.61 01-JUL-05:49 791.37 0.00 0.00 380.50 496.79 0.00 0.00 332.00
August 377.83 0.63 0.61 01-AUG-05:00 668.86 0.00 0.00 351.00 436.01 0.00 0.00 289.67
September 365.83 0.65 0.61 01-SEP-07:19 520.30 0.00 0.00 275.00 359.36 0.00 0.00 191.33
October 318.83 0.65 0.61 01-OCT-07:19 464.98 0.00 0.00 243.83 324.50 0.00 0.00 129.33
November 295.83 0.67 0.61 01-NOV-12:39 374.21 0.00 0.00 168.33 267.95 0.00 0.00 40.67
December 289.50 0.67 0.61 01-DEC-08:09 384.65 0.00 0.00 175.33 267.63 0.00 0.00 33.33
                         
Annual Sum or Average 4125.67 0.65     587.87 0.00 0.00 3313.33 383.59 0.00 0.00 2295.67
Minimum of Months 268.33 0.62 0.61   374.21 0.00 0.00 164.67 267.63 0.00 0.00 33.33
Maximum of Months 408.83 0.67 0.61   839.33 0.00 0.00 380.50 496.79 0.00 0.00 345.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.64 0.61 01-JAN-08:39 1348.87 13.53 54.67 230.33 853.90 15.66 52.33 173.50
February 268.33 0.64 0.61 01-FEB-08:50 1841.59 15.28 70.17 226.17 1048.22 16.63 59.50 181.67
March 351.83 0.64 0.61 01-MAR-07:49 2281.14 14.24 83.83 293.50 910.51 10.66 2.83 252.33
April 373.83 0.64 0.61 01-APR-07:19 2750.82 11.46 55.00 319.50 1013.32 10.51 0.00 283.17
May 408.83 0.64 0.61 01-MAY-06:30 2010.90 7.98 0.00 354.00 1176.65 10.71 1.67 319.50
June 398.00 0.63 0.61 01-JUN-06:30 2095.88 7.95 0.00 350.50 1213.12 13.26 45.17 309.67
July 400.17 0.64 0.61 01-JUL-06:40 1861.46 8.11 0.00 351.83 1080.27 10.75 0.00 296.00
August 377.83 0.64 0.61 01-AUG-06:30 1921.87 8.40 4.67 326.33 1036.19 10.66 0.00 284.00
September 365.83 0.64 0.61 01-SEP-07:49 2262.55 11.66 57.67 289.50 907.52 10.67 5.50 251.67
October 318.83 0.64 0.61 01-OCT-07:30 2100.88 15.56 85.83 275.83 1035.62 14.89 55.00 226.67
November 295.83 0.65 0.61 01-NOV-12:39 2034.17 15.51 82.17 227.00 762.38 15.05 53.17 179.50
December 289.50 0.65 0.61 01-DEC-08:20 1544.64 15.74 77.83 227.83 678.97 15.86 50.50 173.17
                         
Annual Sum or Average 4125.67 0.64     2029.32 11.72 571.83 3472.33 991.06 12.64 325.67 2930.83
Minimum of Months 268.33 0.63 0.61   1348.87 7.95 0.00 226.17 678.97 10.51 0.00 173.17
Maximum of Months 408.83 0.65 0.61   2750.82 15.74 85.83 354.00 1213.12 16.63 59.50 319.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.63 0.61 01-JAN-08:09 7535.20 34.76 252.50 268.50 1484.27 20.90 86.33 253.67
February 268.33 0.63 0.61 01-FEB-07:49 8317.42 35.91 261.17 263.17 1086.56 17.55 34.67 237.00
March 351.83 0.64 0.61 01-MAR-07:10 1572.06 10.85 10.67 308.00 818.04 15.15 1.83 274.83
April 373.83 0.64 0.61 01-APR-06:30 961.49 10.55 0.00 319.17 614.29 15.47 0.00 273.33
May 408.83 0.65 0.61 01-MAY-06:19 786.73 10.47 0.00 342.83 503.52 15.31 0.00 290.33
June 398.00 0.64 0.61 01-JUN-06:19 703.60 10.14 0.00 336.67 463.58 15.15 0.00 274.17
July 400.17 0.65 0.61 01-JUL-06:30 750.83 10.23 0.00 340.17 474.87 15.14 0.00 263.33
August 377.83 0.64 0.61 01-AUG-06:19 889.02 10.61 0.00 328.00 558.23 15.46 0.00 272.00
September 365.83 0.64 0.61 01-SEP-06:00 1148.10 10.83 11.00 302.17 691.74 15.18 0.00 261.67
October 318.83 0.63 0.61 01-OCT-06:49 2999.82 19.38 127.83 306.17 967.58 15.88 13.33 272.17
November 295.83 0.63 0.61 01-NOV-12:39 7823.42 34.94 274.83 278.33 1229.46 20.35 90.00 269.00
December 289.50 0.63 0.61 01-DEC-07:19 6765.97 34.12 259.83 265.33 1498.45 22.15 101.33 265.00
                         
Annual Sum or Average 4125.67 0.64     2937.23 17.89 1197.83 3658.50 816.91 16.69 327.50 3206.50
Minimum of Months 268.33 0.63 0.61   703.60 10.14 0.00 263.17 463.58 15.14 0.00 237.00
Maximum of Months 408.83 0.65 0.61   8317.42 35.91 274.83 342.83 1498.45 22.15 101.33 290.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.65 0.61 01-JAN-08:09 1906.41 16.14 79.33 223.17 1111.55 16.79 63.33 163.50
February 268.33 0.65 0.61 01-FEB-07:49 2214.03 15.26 68.67 228.50 874.82 14.51 40.67 175.33
March 351.83 0.65 0.61 01-MAR-06:00 2098.04 11.71 51.83 284.67 1075.39 10.43 1.83 245.17
April 373.83 0.64 0.61 01-APR-06:10 2569.62 7.81 0.00 318.50 1032.62 10.46 0.00 283.17
May 408.83 0.64 0.61 01-MAY-05:49 2111.25 7.91 0.00 346.83 1207.66 10.55 0.00 309.50
June 398.00 0.64 0.61 01-JUN-05:49 2164.67 7.78 0.00 340.67 1237.62 10.50 0.00 303.17
July 400.17 0.64 0.61 01-JUL-05:49 1899.94 7.92 0.00 343.83 1013.64 10.55 0.00 291.83
August 377.83 0.64 0.61 01-AUG-05:49 2318.16 8.49 5.50 327.83 954.54 10.73 0.00 285.50
September 365.83 0.64 0.61 01-SEP-06:10 2268.70 11.63 57.50 290.50 916.88 10.56 5.50 258.83
October 318.83 0.65 0.61 01-OCT-06:49 2019.76 14.54 77.50 266.17 1133.94 14.19 48.67 210.33
November 295.83 0.66 0.61 01-NOV-12:39 1683.66 14.83 76.33 226.67 862.26 14.42 50.33 166.00
December 289.50 0.65 0.61 01-DEC-07:10 1812.16 16.62 87.33 224.67 767.96 15.49 50.33 174.33
                         
Annual Sum or Average 4125.67 0.65     2103.45 11.25 504.00 3422.00 1026.21 12.13 260.67 2866.67
Minimum of Months 268.33 0.64 0.61   1683.66 7.78 0.00 223.17 767.96 10.43 0.00 163.50
Maximum of Months 408.83 0.66 0.61   2569.62 16.62 87.33 346.83 1237.62 16.79 63.33 309.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.67 0.61 01-JAN-08:39 384.95 0.00 0.00 164.33 272.94 0.00 0.00 46.50
February 268.33 0.66 0.61 01-FEB-08:39 440.34 0.00 0.00 190.33 310.95 0.00 0.00 92.50
March 351.83 0.65 0.61 01-MAR-07:40 525.51 0.00 0.00 267.67 355.60 0.00 0.00 183.33
April 373.83 0.63 0.61 01-APR-06:19 624.37 0.00 0.00 340.50 419.76 0.00 0.00 271.00
May 408.83 0.63 0.61 01-MAY-05:00 777.77 0.00 0.00 379.17 467.57 0.00 0.00 342.00
June 398.00 0.62 0.61 01-JUN-05:49 839.22 0.00 0.00 376.50 491.77 0.00 0.00 345.33
July 400.17 0.63 0.61 01-JUL-05:49 791.31 0.00 0.00 380.33 497.16 0.00 0.00 332.17
August 377.83 0.63 0.61 01-AUG-05:00 668.76 0.00 0.00 351.00 436.33 0.00 0.00 289.83
September 365.83 0.65 0.61 01-SEP-07:19 520.14 0.00 0.00 275.00 359.58 0.00 0.00 191.50
October 318.83 0.65 0.61 01-OCT-07:19 464.81 0.00 0.00 243.83 324.69 0.00 0.00 129.50
November 295.83 0.67 0.61 01-NOV-12:39 374.02 0.00 0.00 168.33 268.09 0.00 0.00 40.83
December 289.50 0.67 0.61 01-DEC-08:09 384.46 0.00 0.00 175.33 267.79 0.00 0.00 33.83
                         
Annual Sum or Average 4125.67 0.65     587.73 0.00 0.00 3312.33 383.85 0.00 0.00 2298.33
Minimum of Months 268.33 0.62 0.61   374.02 0.00 0.00 164.33 267.79 0.00 0.00 33.83
Maximum of Months 408.83 0.67 0.61   839.22 0.00 0.00 380.33 497.16 0.00 0.00 345.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.64 0.61 01-JAN-08:39 1348.48 13.52 54.67 230.33 854.26 15.65 52.33 173.50
February 268.33 0.64 0.61 01-FEB-08:00 1841.27 15.27 70.17 226.00 1048.64 16.62 59.50 181.67
March 351.83 0.64 0.61 01-MAR-07:49 2280.96 14.23 83.83 293.17 911.04 10.65 2.83 252.33
April 373.83 0.64 0.61 01-APR-07:19 2750.64 11.44 55.00 319.50 1013.85 10.50 0.00 283.17
May 408.83 0.64 0.61 01-MAY-06:30 2010.62 7.97 0.00 353.67 1177.18 10.70 1.67 319.67
June 398.00 0.63 0.61 01-JUN-06:30 2095.57 7.93 0.00 350.50 1213.64 13.25 45.17 309.67
July 400.17 0.64 0.61 01-JUL-06:40 1861.26 8.09 0.00 351.67 1080.82 10.74 0.00 296.17
August 377.83 0.64 0.61 01-AUG-06:30 1921.69 8.39 4.67 326.33 1036.73 10.65 0.00 284.00
September 365.83 0.64 0.61 01-SEP-07:49 2262.25 11.65 57.67 289.17 908.01 10.66 5.50 251.83
October 318.83 0.64 0.61 01-OCT-07:30 2100.40 15.55 85.83 275.83 1036.06 14.88 55.00 226.67
November 295.83 0.65 0.61 01-NOV-12:39 2033.82 15.49 82.17 226.83 762.70 15.04 53.17 179.67
December 289.50 0.65 0.61 01-DEC-08:20 1544.32 15.73 77.83 227.67 679.34 15.85 50.50 173.67
                         
Annual Sum or Average 4125.67 0.64     2029.04 11.71 571.83 3470.67 991.54 12.63 325.67 2932.00
Minimum of Months 268.33 0.63 0.61   1348.48 7.93 0.00 226.00 679.34 10.50 0.00 173.50
Maximum of Months 408.83 0.65 0.61   2750.64 15.73 85.83 353.67 1213.64 16.62 59.50 319.67



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.525132E+09 18194.38 27-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.302191E+09 19358.48 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 61187117.35 8947.48 02-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 1999926.83 1601.18 28-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.170893E+09 10797.40 30-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.106140E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.525132E+09 19358.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 46955674.98 9110.79 28-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 24011365.39 3434.31 02-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 2954388.28 1068.68 02-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 9495690.74 1901.78 30-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 83417119.40     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 46955674.98 9110.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 65111458.38 7228.57 28-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 34498995.58 3898.84 02-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 9766332.00 7727.86 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 4889198.19 2303.62 28-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 84560912.17 9967.56 30-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.198827E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 84560912.17 9967.56   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 40688797.22 2481.51 28-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 21328388.70 2490.26 02-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 4801836.47 2096.81 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 8009660.16 3419.63 28-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 36248375.94 15327.17 27-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.111077E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 40688797.22 15327.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 6931948.46 597.81 28-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 6931948.46     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 6931948.46 597.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.138610E+11 213382.51 27-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.912712E+10 225730.46 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.500228E+10 164101.06 02-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.193029E+09 46398.16 12-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.392078E+10 126326.15 28-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.242372E+11 223707.11 27-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.563414E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.242372E+11 225730.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.123865E+11 156360.59 11-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.680046E+10 158461.23 24-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.264372E+10 156287.99 01-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 59180578.19 30979.27 11-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.381332E+10 156350.97 20-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.155063E+11 157802.98 08-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.412094E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.155063E+11 158461.23   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.820127E+10 140211.23 11-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.361584E+10 141912.42 09-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.161888E+10 140645.59 01-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 45785375.26 24460.73 11-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 32174061.13 10999.74 25-OCT-05:08 0.00 0.00 0.00 0.00 0.00
November 0.284665E+10 140201.52 20-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.996736E+10 139869.79 27-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.263280E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.996736E+10 141912.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.306848E+10 158962.55 26-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.175738E+10 171641.09 09-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.625470E+09 160966.35 01-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 26659975.29 14609.04 11-APR-05:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.101738E+10 159136.35 28-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.406115E+10 159594.29 05-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.105565E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.406115E+10 171641.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.723854E+10 140129.83 28-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.400878E+10 142482.29 09-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.113245E+10 141199.16 01-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 52261792.46 17569.69 11-APR-05:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.219441E+10 138863.50 28-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.824806E+10 140412.49 27-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.228745E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.824806E+10 142482.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.328985E+10 27744.80 27-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.218823E+10 29447.51 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.128490E+10 23272.08 02-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 93208608.16 9261.25 12-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 11166474.08 2987.68 25-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.116268E+10 18645.91 28-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.502131E+10 28849.48 27-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.130513E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.502131E+10 29447.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.101123E+10 83080.79 02-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.168795E+09 72004.25 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 19846511.10 8231.85 02-MAR-06:06 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.429516E+09 83294.96 27-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.146449E+10 83523.46 04-DEC-05:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.309388E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.146449E+10 83523.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.427052E+10 16875.51 17-JAN-05:23 0.00 0.00 0.00 0.00 0.00
February 0.272797E+10 16776.42 27-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.140582E+10 16695.60 04-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.142708E+09 16161.03 12-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.119383E+09 11790.09 25-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.215184E+10 16764.35 28-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.513068E+10 16795.25 26-DEC-05:14 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.159489E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.513068E+10 16875.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.225906E+10 14760.16 23-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.123406E+10 14715.72 27-FEB-05:01 0.00 0.00 0.00 0.00 0.00
March 0.659374E+09 14645.39 04-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 51682884.07 10071.68 11-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.107226E+09 8504.43 25-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.112016E+10 14736.47 28-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.274198E+10 14760.41 05-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.817354E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.274198E+10 14760.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.163182E+10 18120.18 17-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.104396E+10 18049.57 27-FEB-05:01 0.00 0.00 0.00 0.00 0.00
March 0.668485E+09 17962.74 01-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.103777E+09 15569.60 11-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 29801716.95 1982.85 25-OCT-05:08 0.00 0.00 0.00 0.00 0.00
November 0.854075E+09 18107.03 27-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.194951E+10 18121.30 05-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.628142E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.194951E+10 18121.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.225248E+10 16857.94 28-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.147183E+10 16817.17 09-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.698467E+09 16794.89 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 71733861.59 9852.64 11-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 50683020.19 1752.74 25-OCT-05:20 0.00 0.00 0.00 0.00 0.00
November 0.103539E+10 16862.91 28-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.255763E+10 16865.46 04-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.813821E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.255763E+10 16865.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.290096E+10 0.290096E+10 47949.72 03-JAN-15:00 47949.72 0.00
February 0.00 0.00 0.103041E+11 0.103041E+11 79626.11 21-FEB-15:00 79626.11 0.00
March 0.00 0.00 0.257351E+11 0.257351E+11 94286.40 21-MAR-16:00 94286.40 0.00
April 0.00 0.00 0.739542E+11 0.739542E+11 126305.01 21-APR-14:30 126305.01 0.04
May 0.00 0.00 0.106927E+12 0.106805E+12 148349.62 31-MAY-05:03 148349.62 0.20
June 0.00 0.00 0.147463E+12 0.147001E+12 163338.30 08-JUN-05:02 163338.30 0.47
July 0.00 0.00 0.178679E+12 0.151849E+12 306458.18 21-JUL-05:03 97041.68 0.83
August 0.00 0.00 0.171692E+12 0.160337E+12 258697.54 05-AUG-05:03 148350.95 0.82
September 0.00 0.00 0.114534E+12 0.106882E+12 263935.71 22-SEP-05:03 96698.63 0.56
October 0.00 0.00 0.638360E+11 0.619870E+11 149024.76 02-OCT-05:02 149024.76 0.23
November 0.00 0.00 0.184959E+11 0.184959E+11 89618.37 03-NOV-16:00 89618.37 0.01
December 0.00 0.00 0.129178E+10 0.129178E+10 27815.61 20-DEC-15:00 27815.61 0.00
                 
Annual Sum or Average 0.00 0.00 0.915813E+12 0.867542E+12       0.27
Minimum of Months 0.00 0.00 0.129178E+10 0.129178E+10 27815.61   27815.61 0.00
Maximum of Months 0.00 0.00 0.178679E+12 0.160337E+12 306458.18   163338.30 0.83



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.224260E+11 0.224260E+11 379464.32 03-JAN-14:30 379464.32 0.00
February 0.00 0.00 0.797845E+11 0.797845E+11 579662.15 21-FEB-16:00 579662.15 0.00
March 0.00 0.00 0.191497E+12 0.191497E+12 739909.75 21-MAR-16:00 739909.75 0.00
April 0.00 0.00 0.527686E+12 0.527686E+12 1083524.15 21-APR-15:00 1083524.15 0.03
May 0.00 0.00 0.943912E+12 0.942876E+12 1497340.78 31-MAY-03:02 1497340.78 0.20
June 0.00 0.00 0.126226E+13 0.125946E+13 1483895.43 15-JUN-05:02 1483895.43 0.41
July 0.00 0.00 0.140009E+13 0.120665E+13 2864410.75 21-JUL-05:03 909650.76 0.69
August 0.00 0.00 0.122246E+13 0.115650E+13 2428632.70 03-AUG-05:03 1100188.14 0.65
September 0.00 0.00 0.979308E+12 0.916648E+12 2096271.61 22-SEP-03:02 766390.61 0.51
October 0.00 0.00 0.512471E+12 0.497348E+12 1182754.51 03-OCT-14:00 1051905.04 0.21
November 0.00 0.00 0.138898E+12 0.138898E+12 710703.13 03-NOV-16:00 710703.13 0.02
December 0.00 0.00 0.824353E+10 0.824353E+10 178140.17 08-DEC-14:00 178140.17 0.00
                 
Annual Sum or Average 0.00 0.00 0.728903E+13 0.694802E+13       0.23
Minimum of Months 0.00 0.00 0.824353E+10 0.824353E+10 178140.17   178140.17 0.00
Maximum of Months 0.00 0.00 0.140009E+13 0.125946E+13 2864410.75   1497340.78 0.69



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.163433E+10 0.163433E+10 29665.63 03-JAN-15:00 29665.63 0.00
February 0.00 0.00 0.661478E+10 0.661478E+10 52512.77 21-FEB-16:00 52512.77 0.00
March 0.00 0.00 0.174752E+11 0.174752E+11 78700.97 21-MAR-16:00 78700.97 0.00
April 0.00 0.00 0.566612E+11 0.566612E+11 127621.18 21-APR-15:00 127621.18 0.03
May 0.00 0.00 0.104488E+12 0.104377E+12 156561.77 31-MAY-03:02 156561.77 0.20
June 0.00 0.00 0.144941E+12 0.144653E+12 158159.67 15-JUN-14:40 158159.67 0.42
July 0.00 0.00 0.158949E+12 0.138651E+12 304905.62 22-JUL-05:02 100961.66 0.71
August 0.00 0.00 0.136480E+12 0.129876E+12 242822.05 05-AUG-05:02 145477.98 0.66
September 0.00 0.00 0.106326E+12 0.100348E+12 220473.85 22-SEP-05:03 80733.84 0.51
October 0.00 0.00 0.520712E+11 0.507779E+11 138991.83 03-OCT-13:40 121297.60 0.20
November 0.00 0.00 0.114726E+11 0.114726E+11 72650.83 09-NOV-15:00 72650.83 0.01
December 0.00 0.00 0.561952E+09 0.561952E+09 12673.72 23-DEC-15:00 12673.72 0.00
                 
Annual Sum or Average 0.00 0.00 0.797676E+12 0.763103E+12       0.23
Minimum of Months 0.00 0.00 0.561952E+09 0.561952E+09 12673.72   12673.72 0.00
Maximum of Months 0.00 0.00 0.158949E+12 0.144653E+12 304905.62   158159.67 0.71



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.130517E+10 0.130517E+10 33254.36 03-JAN-15:00 33254.36 0.00
February 0.00 0.00 0.456754E+10 0.456754E+10 55614.32 21-FEB-15:00 55614.32 0.00
March 0.00 0.00 0.123944E+11 0.123944E+11 54615.21 21-MAR-16:00 54615.21 0.00
April 0.00 0.00 0.368188E+11 0.368188E+11 77274.93 20-APR-05:03 77274.93 0.03
May 0.00 0.00 0.636084E+11 0.635893E+11 115856.32 29-MAY-17:29 113616.69 0.16
June 0.00 0.00 0.807094E+11 0.806356E+11 121351.32 15-JUN-04:03 121351.32 0.33
July 0.00 0.00 0.936124E+11 0.828436E+11 181434.21 21-JUL-03:02 57372.35 0.55
August 0.00 0.00 0.918851E+11 0.884115E+11 174128.94 02-AUG-03:02 78079.51 0.59
September 0.00 0.00 0.735674E+11 0.709868E+11 161829.96 22-SEP-03:02 59319.03 0.45
October 0.00 0.00 0.409108E+11 0.404966E+11 125693.67 02-OCT-03:02 125693.67 0.17
November 0.00 0.00 0.106912E+11 0.106909E+11 63869.43 10-NOV-04:02 63869.43 0.01
December 0.00 0.00 0.224755E+09 0.224755E+09 17473.36 11-DEC-05:02 17473.36 0.00
                 
Annual Sum or Average 0.00 0.00 0.510295E+12 0.492965E+12       0.19
Minimum of Months 0.00 0.00 0.224755E+09 0.224755E+09 17473.36   17473.36 0.00
Maximum of Months 0.00 0.00 0.936124E+11 0.884115E+11 181434.21   125693.67 0.59



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.379090E+12 0.342019E+12 145154.83 12-JAN-22:03 130634.05 0.00
February 0.00 0.00 0.584964E+12 0.529900E+12 246446.23 21-FEB-22:03 222324.26 0.00
March 0.00 0.00 0.913862E+12 0.834073E+12 443118.33 31-MAR-24:00 400824.48 0.00
April 0.00 0.00 0.112265E+13 0.104206E+13 457843.44 22-APR-03:13 412247.63 0.00
May 0.00 0.00 0.373575E+12 0.350206E+12 228836.97 31-MAY-24:00 216940.29 0.00
June 0.00 0.00 0.600803E+12 0.577334E+12 319437.88 30-JUN-23:03 307897.42 0.00
July 0.00 0.00 0.875839E+12 0.843475E+12 410763.87 31-JUL-24:00 393547.75 0.00
August 0.00 0.00 0.114950E+13 0.107430E+13 454939.76 14-AUG-00:05 409718.16 0.00
September 0.00 0.00 0.369167E+12 0.344481E+12 240435.32 30-SEP-24:00 218779.07 0.00
October 0.00 0.00 0.650194E+12 0.597870E+12 346596.57 31-OCT-23:20 311474.41 0.00
November 0.00 0.00 0.897255E+12 0.813820E+12 352175.16 12-NOV-10:53 316004.84 0.00
December 0.00 0.00 0.120041E+13 0.108406E+13 455126.57 18-DEC-23:00 407819.70 0.00
                 
Annual Sum or Average 0.00 0.00 0.911730E+13 0.843360E+13       0.00
Minimum of Months 0.00 0.00 0.369167E+12 0.342019E+12 145154.83   130634.05 0.00
Maximum of Months 0.00 0.00 0.120041E+13 0.108406E+13 457843.44   412247.63 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.490799E+10 0.489639E+10 2576.56 02-JAN-16:50 2519.33 0.00
February 0.00 0.00 0.933706E+10 0.932322E+10 4578.68 20-FEB-17:20 4578.68 0.00
March 0.00 0.00 0.157651E+11 0.157619E+11 7749.18 31-MAR-24:00 7749.18 0.00
April 0.00 0.00 0.205189E+11 0.205052E+11 8412.83 28-APR-16:00 8374.04 0.00
May 0.00 0.00 0.634470E+10 0.628948E+10 4112.62 31-MAY-23:40 4112.62 0.00
June 0.00 0.00 0.112088E+11 0.111094E+11 5948.68 30-JUN-23:55 5948.68 0.00
July 0.00 0.00 0.168267E+11 0.165066E+11 7880.39 31-JUL-23:57 7870.04 0.00
August 0.00 0.00 0.219819E+11 0.217134E+11 8677.19 08-AUG-17:00 8256.92 0.00
September 0.00 0.00 0.635934E+10 0.615942E+10 4124.13 30-SEP-24:00 4124.13 0.00
October 0.00 0.00 0.112737E+11 0.111345E+11 5928.42 31-OCT-24:00 5928.42 0.00
November 0.00 0.00 0.153093E+11 0.152752E+11 6676.82 09-NOV-16:40 6576.75 0.00
December 0.00 0.00 0.204914E+11 0.204863E+11 8197.17 15-DEC-16:40 8197.17 0.00
                 
Annual Sum or Average 0.00 0.00 0.160325E+12 0.159161E+12       0.00
Minimum of Months 0.00 0.00 0.490799E+10 0.489639E+10 2576.56   2519.33 0.00
Maximum of Months 0.00 0.00 0.219819E+11 0.217134E+11 8677.19   8374.04 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.332493E+11 0.331391E+11 22631.21 12-JAN-16:50 22007.02 0.00
February 0.00 0.00 0.787024E+11 0.785641E+11 42380.37 21-FEB-17:00 42380.37 0.00
March 0.00 0.00 0.142329E+12 0.142297E+12 71955.67 31-MAR-24:00 71955.67 0.00
April 0.00 0.00 0.192834E+12 0.192693E+12 79805.85 28-APR-16:00 79387.74 0.00
May 0.00 0.00 0.587811E+11 0.582314E+11 40138.82 31-MAY-23:55 40138.82 0.00
June 0.00 0.00 0.106901E+12 0.105909E+12 57700.38 30-JUN-23:55 57700.38 0.00
July 0.00 0.00 0.160582E+12 0.157385E+12 76002.77 31-JUL-23:57 75898.82 0.00
August 0.00 0.00 0.206590E+12 0.203899E+12 82309.29 08-AUG-17:00 78137.54 0.00
September 0.00 0.00 0.584310E+11 0.564518E+11 38884.68 30-SEP-24:00 38884.68 0.00
October 0.00 0.00 0.102330E+12 0.100944E+12 54380.56 31-OCT-24:00 54380.56 0.00
November 0.00 0.00 0.135307E+12 0.134966E+12 62766.27 09-NOV-16:50 61759.45 0.00
December 0.00 0.00 0.179634E+12 0.179581E+12 76443.66 15-DEC-16:50 76443.66 0.00
                 
Annual Sum or Average 0.00 0.00 0.145567E+13 0.144406E+13       0.00
Minimum of Months 0.00 0.00 0.332493E+11 0.331391E+11 22631.21   22007.02 0.00
Maximum of Months 0.00 0.00 0.206590E+12 0.203899E+12 82309.29   79387.74 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.174049E+10 0.173116E+10 2266.08 12-JAN-16:50 2204.08 0.00
February 0.00 0.00 0.669791E+10 0.668437E+10 4231.50 21-FEB-17:00 4231.50 0.00
March 0.00 0.00 0.133486E+11 0.133454E+11 6889.75 31-MAR-23:20 6889.75 0.00
April 0.00 0.00 0.190431E+11 0.190291E+11 8092.21 28-APR-16:00 8050.25 0.00
May 0.00 0.00 0.586656E+10 0.581154E+10 4054.75 31-MAY-23:55 4054.75 0.00
June 0.00 0.00 0.107995E+11 0.107002E+11 5796.24 30-JUN-23:55 5796.24 0.00
July 0.00 0.00 0.162031E+11 0.158834E+11 7622.99 31-JUL-23:57 7612.57 0.00
August 0.00 0.00 0.207331E+11 0.204640E+11 8325.70 08-AUG-17:00 7902.93 0.00
September 0.00 0.00 0.582139E+10 0.562330E+10 3772.18 30-SEP-23:30 3772.18 0.00
October 0.00 0.00 0.979080E+10 0.965268E+10 5113.80 31-OCT-23:30 5113.80 0.00
November 0.00 0.00 0.122870E+11 0.122531E+11 6310.87 09-NOV-16:50 6210.23 0.00
December 0.00 0.00 0.161053E+11 0.161001E+11 7560.71 15-DEC-16:50 7560.71 0.00
                 
Annual Sum or Average 0.00 0.00 0.138437E+12 0.137278E+12       0.00
Minimum of Months 0.00 0.00 0.174049E+10 0.173116E+10 2266.08   2204.08 0.00
Maximum of Months 0.00 0.00 0.207331E+11 0.204640E+11 8325.70   8050.25 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 22165.89 1159890.15 26-JAN-05:01
February 0.00 0.00 01-FEB-00:10 14146.45 1066144.80 09-FEB-06:02
March 0.00 0.00 01-MAR-00:10 5868.14 1090603.17 01-MAR-06:02
April 0.00 0.00 01-APR-00:10 317.36 156668.83 11-APR-05:03
May 0.00 0.00 01-MAY-00:02 0.00 0.00 01-MAY-00:02
June 0.00 0.00 01-JUN-00:05 0.00 0.00 01-JUN-00:05
July 0.00 0.00 01-JUL-00:02 0.00 0.00 01-JUL-00:02
August 0.00 0.00 01-AUG-00:05 0.00 0.00 01-AUG-00:05
September 0.00 0.00 01-SEP-00:05 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:10 125.60 36932.13 25-OCT-05:02
November 0.00 0.00 01-NOV-00:10 7867.54 1123411.26 28-NOV-06:01
December 0.00 0.00 01-DEC-00:10 30047.54 1130353.62 27-DEC-06:01
             
Annual Sum or Average 0.00     6701.56    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   30047.54 1159890.15  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 24784.77 967667.60 03-JAN-14:30 0.00 0.00 01-JAN-00:05
February 84737.98 1319478.75 21-FEB-14:50 228.72 228442.92 21-FEB-08:00
March 171307.34 1337256.60 15-MAR-15:10 110.53 223482.40 19-MAR-09:03
April 420613.55 1508065.85 27-APR-12:00 94.67 128429.16 08-APR-23:42
May 637017.85 1605202.70 31-MAY-05:03 213.43 515613.29 07-MAY-07:12
June 809856.59 1787180.03 08-JUN-05:02 31.24 114151.35 28-JUN-01:02
July 862915.90 5525334.59 20-JUL-15:10 0.00 0.00 01-JUL-00:02
August 803916.30 2925922.21 03-AUG-05:03 1.80 23683.78 13-AUG-23:43
September 654138.56 2006716.21 14-SEP-09:50 101.73 322890.22 17-SEP-06:32
October 384447.61 1527678.23 03-OCT-14:00 399.87 419126.61 01-OCT-07:30
November 131975.12 1347245.94 08-NOV-15:30 31.10 230665.47 24-NOV-04:02
December 11205.47 457516.39 08-DEC-14:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 418174.33     100.44    
Minimum of Months 11205.47 457516.39   0.00 0.00  
Maximum of Months 862915.90 5525334.59   399.87 515613.29  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 12918.46 577933.58 03-JAN-14:30 0.00 0.00 01-JAN-00:05
February 48946.04 871558.36 21-FEB-16:10 0.00 0.00 01-FEB-00:10
March 106893.77 1069504.60 21-MAR-16:00 0.00 0.00 01-MAR-00:10
April 296236.26 1539444.25 20-APR-05:03 0.00 0.00 01-APR-00:10
May 495582.37 2517659.66 31-MAY-05:03 0.00 0.00 01-MAY-00:02
June 673941.68 2560924.84 15-JUN-05:02 0.00 0.00 01-JUN-00:05
July 728018.34 5811874.31 20-JUL-15:10 0.00 0.00 01-JUL-00:02
August 656423.39 4098845.23 03-AUG-05:03 0.00 0.00 01-AUG-00:05
September 536225.90 3228769.85 22-SEP-03:02 0.00 0.00 01-SEP-00:05
October 284724.92 2016186.18 02-OCT-05:02 0.00 0.00 01-OCT-00:10
November 84284.87 1131625.51 03-NOV-12:30 0.00 0.00 01-NOV-00:10
December 4726.84 267125.34 08-DEC-14:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 328928.99     0.00    
Minimum of Months 4726.84 267125.34   0.00 0.00  
Maximum of Months 728018.34 5811874.31   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 204002.24 463275.88 03-JAN-17:00 0.00 0.00 01-JAN-00:05
February 403284.25 848817.37 20-FEB-16:00 0.00 0.00 01-FEB-00:10
March 635303.49 1203642.47 21-MAR-16:00 0.00 0.00 01-MAR-00:10
April 1131587.51 1861767.92 21-APR-15:00 0.00 0.00 01-APR-00:10
May 653882.35 1291684.99 19-MAY-16:00 0.00 0.00 01-MAY-00:02
June 1123737.84 1790658.70 02-JUN-16:00 0.00 0.00 01-JUN-00:05
July 1360694.27 2028276.06 03-JUL-16:00 0.00 0.00 01-JUL-00:02
August 1537990.38 2170643.76 07-AUG-16:10 0.00 0.00 01-AUG-00:05
September 636232.75 1231441.86 19-SEP-16:00 0.00 0.00 01-SEP-00:05
October 618508.69 1423002.79 03-OCT-14:10 0.00 0.00 01-OCT-00:10
November 599520.55 1153611.04 03-NOV-16:00 0.00 0.00 01-NOV-00:10
December 689514.53 1042329.42 10-DEC-15:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 801975.60     0.00    
Minimum of Months 204002.24 463275.88   0.00 0.00  
Maximum of Months 1537990.38 2170643.76   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 14445.66 48134.75 31-JAN-13:00
February 0.00 0.00 01-FEB-00:10 14508.28 48135.89 01-FEB-13:00
March 0.00 0.00 01-MAR-00:10 14811.58 47252.47 01-MAR-12:30
April 0.00 0.00 01-APR-00:10 13133.85 44557.09 03-APR-12:00
May 0.00 0.00 01-MAY-00:02 12540.80 41477.82 01-MAY-12:00
June 0.00 0.00 01-JUN-00:05 11904.90 38081.66 01-JUN-11:40
July 0.00 0.00 01-JUL-00:02 10599.37 35590.61 03-JUL-11:20
August 0.00 0.00 01-AUG-00:05 11479.08 35726.54 31-AUG-11:40
September 0.00 0.00 01-SEP-00:05 11352.80 38040.33 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 12173.61 41529.02 31-OCT-11:30
November 0.00 0.00 01-NOV-00:10 13294.34 44813.83 30-NOV-12:50
December 0.00 0.00 01-DEC-00:10 13665.86 47167.20 29-DEC-12:20
             
Annual Sum or Average 0.00     12816.45    
Minimum of Months 0.00 0.00   10599.37 35590.61  
Maximum of Months 0.00 0.00   14811.58 48135.89  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 12250.80 576828.01 03-JAN-14:30 3015.84 117451.28 09-JAN-11:00
February 49231.36 884967.81 23-FEB-14:10 2429.72 133932.55 09-FEB-13:40
March 108107.01 1045461.83 21-MAR-16:00 1887.07 124094.33 01-MAR-12:50
April 320519.93 2447265.14 27-APR-13:20 2069.63 114450.12 05-APR-05:40
May 574231.55 2535237.46 19-MAY-14:40 474.83 86487.15 05-MAY-06:00
June 845406.10 2686065.08 20-JUN-15:00 132.40 61121.33 11-JUN-03:45
July 1191006.87 6335792.98 20-JUL-15:30 0.00 0.00 01-JUL-00:02
August 893787.56 4519801.08 02-AUG-08:20 58.40 25819.29 25-AUG-05:00
September 703984.35 4213102.11 14-SEP-09:50 63.81 47104.68 28-SEP-03:30
October 321056.05 2993054.69 03-OCT-14:00 486.81 75633.81 10-OCT-07:50
November 81734.25 1007108.06 09-NOV-15:00 1847.99 130639.74 06-NOV-06:40
December 3936.76 296925.85 08-DEC-14:10 3087.17 132666.80 22-DEC-06:50
             
Annual Sum or Average 427845.18     1289.76    
Minimum of Months 3936.76 296925.85   0.00 0.00  
Maximum of Months 1191006.87 6335792.98   3087.17 133932.55  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.173303E+11 0.93 11101.34 01-JAN-00:13 1.59
February 0.151622E+11 0.90 11101.34 01-FEB-05:00 1.60
March 0.177311E+11 0.95 11101.34 01-MAR-05:01 1.60
April 0.165632E+11 0.92 11101.34 01-APR-04:02 1.60
May 0.178209E+11 0.95 11101.34 01-MAY-03:02 1.60
June 0.174552E+11 0.96 11101.34 01-JUN-03:02 1.60
July 0.176099E+11 0.93 11101.34 01-JUL-03:02 1.59
August 0.197342E+11 1.04 11101.34 01-AUG-03:02 1.58
September 0.188069E+11 1.03 11101.34 01-SEP-03:02 1.58
October 0.190095E+11 1.01 11101.34 01-OCT-12:30 1.59
November 0.180068E+11 1.00 11101.34 01-NOV-03:02 1.58
December 0.176489E+11 0.95 11101.34 01-DEC-04:03 1.59
           
Annual Sum or Average 0.212879E+12 0.96      
Minimum of Months 0.151622E+11 0.90 11101.34   1.58
Maximum of Months 0.197342E+11 1.04 11101.34   1.60



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.609476E+10 0.40 11404.35 02-JAN-04:03 1.28
February 0.635283E+10 0.45 13035.76 21-FEB-16:20 1.40
March 0.916595E+10 0.53 14033.44 16-MAR-05:03 1.46
April 0.119890E+11 0.67 17960.53 21-APR-14:30 1.70
May 0.116080E+11 0.62 23708.05 22-MAY-05:03 2.01
June 0.142294E+11 0.75 23708.05 08-JUN-05:02 2.02
July 0.147592E+11 0.75 23708.05 03-JUL-05:02 2.01
August 0.177695E+11 0.85 23708.05 07-AUG-04:22 2.01
September 0.114275E+11 0.61 23708.05 14-SEP-05:03 2.01
October 0.100340E+11 0.55 23708.05 02-OCT-05:02 2.01
November 0.827204E+10 0.49 15254.45 10-NOV-06:03 1.53
December 0.757087E+10 0.46 13471.18 11-DEC-06:03 1.42
           
Annual Sum or Average 0.129273E+12 0.60      
Minimum of Months 0.609476E+10 0.40 11404.35   1.28
Maximum of Months 0.177695E+11 0.85 23708.05   2.02



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.421904E+11 0.35 125826.83 11-JAN-06:02 1.43
February 0.426380E+11 0.38 146099.09 09-FEB-06:02 1.57
March 0.575167E+11 0.42 144397.07 01-MAR-06:02 1.55
April 0.730413E+11 0.49 173789.48 03-APR-05:02 1.74
May 0.991191E+11 0.57 221522.26 31-MAY-03:02 2.02
June 0.117768E+12 0.66 221522.26 02-JUN-05:02 2.03
July 0.109067E+12 0.61 221522.26 17-JUL-05:02 2.01
August 0.112575E+12 0.63 221522.26 01-AUG-05:03 2.01
September 0.912446E+11 0.55 221522.26 01-SEP-05:02 2.01
October 0.684350E+11 0.45 171633.73 02-OCT-05:02 1.71
November 0.495571E+11 0.39 125826.83 20-NOV-06:01 1.43
December 0.409075E+11 0.35 121319.34 21-DEC-06:03 1.40
           
Annual Sum or Average 0.904059E+12 0.49      
Minimum of Months 0.409075E+11 0.35 121319.34   1.40
Maximum of Months 0.117768E+12 0.66 221522.26   2.03



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.351831E+10 0.33 5275.96 12-JAN-15:40 0.82
February 0.344236E+10 0.34 5946.50 07-FEB-14:40 0.87
March 0.461217E+10 0.37 9950.48 16-MAR-15:30 1.17
April 0.677574E+10 0.44 15375.30 21-APR-15:00 1.52
May 0.101876E+11 0.55 24173.65 31-MAY-05:03 2.03
June 0.132197E+11 0.68 24173.65 07-JUN-03:02 2.03
July 0.122204E+11 0.63 24173.65 03-JUL-04:12 2.01
August 0.121222E+11 0.62 24173.65 05-AUG-05:02 2.01
September 0.939541E+10 0.52 20156.47 20-SEP-05:02 1.79
October 0.625938E+10 0.41 18018.37 05-OCT-05:03 1.67
November 0.404378E+10 0.35 9811.48 09-NOV-06:02 1.16
December 0.347485E+10 0.33 4735.17 04-DEC-05:01 0.77
           
Annual Sum or Average 0.892720E+11 0.47      
Minimum of Months 0.344236E+10 0.33 4735.17   0.77
Maximum of Months 0.132197E+11 0.68 24173.65   2.03



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.108900E+12 1.55 40658.54 01-JAN-00:10 1.55
February 0.983611E+11 1.55 40658.54 01-FEB-00:10 1.55
March 0.108900E+12 1.55 40658.54 01-MAR-00:10 1.55
April 0.105387E+12 1.55 40658.54 01-APR-00:10 1.55
May 0.108900E+12 1.55 40658.54 01-MAY-00:02 1.55
June 0.105387E+12 1.55 40658.54 01-JUN-00:05 1.55
July 0.108900E+12 1.55 40658.54 01-JUL-00:02 1.55
August 0.108900E+12 1.54 40658.54 01-AUG-00:05 1.55
September 0.105387E+12 1.55 40658.54 01-SEP-00:05 1.55
October 0.108900E+12 1.55 40658.54 01-OCT-00:10 1.55
November 0.105387E+12 1.55 40658.54 01-NOV-00:10 1.55
December 0.108900E+12 1.55 40658.54 01-DEC-00:10 1.55
           
Annual Sum or Average 0.128221E+13 1.55      
Minimum of Months 0.983611E+11 1.54 40658.54   1.55
Maximum of Months 0.108900E+12 1.55 40658.54   1.55



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.163678E+10 1.06 611.10 01-JAN-00:05 1.06
February 0.147838E+10 1.06 611.10 01-FEB-00:10 1.06
March 0.163678E+10 1.06 611.10 01-MAR-00:10 1.06
April 0.158398E+10 1.06 611.10 01-APR-00:10 1.06
May 0.163678E+10 1.06 611.10 01-MAY-00:02 1.05
June 0.158398E+10 1.05 611.10 01-JUN-00:05 1.05
July 0.163678E+10 1.05 611.10 01-JUL-00:02 1.05
August 0.163678E+10 1.05 611.10 01-AUG-00:05 1.05
September 0.158398E+10 1.05 611.10 01-SEP-00:05 1.05
October 0.163678E+10 1.05 611.10 01-OCT-00:10 1.06
November 0.158398E+10 1.06 611.10 01-NOV-00:10 1.06
December 0.163678E+10 1.06 611.10 01-DEC-00:10 1.06
           
Annual Sum or Average 0.192717E+11 1.06      
Minimum of Months 0.147838E+10 1.05 611.10   1.05
Maximum of Months 0.163678E+10 1.06 611.10   1.06



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.155643E+11 1.06 5811.03 01-JAN-00:05 1.06
February 0.140580E+11 1.06 5811.03 01-FEB-00:10 1.06
March 0.155643E+11 1.06 5811.03 01-MAR-00:10 1.06
April 0.150622E+11 1.06 5811.03 01-APR-00:10 1.06
May 0.155643E+11 1.06 5811.03 01-MAY-00:02 1.05
June 0.150622E+11 1.05 5811.03 01-JUN-00:05 1.05
July 0.155643E+11 1.05 5811.03 01-JUL-00:02 1.05
August 0.155643E+11 1.05 5811.03 01-AUG-00:05 1.05
September 0.150622E+11 1.05 5811.03 01-SEP-00:05 1.05
October 0.155643E+11 1.05 5811.03 01-OCT-00:10 1.06
November 0.150622E+11 1.06 5811.03 01-NOV-00:10 1.06
December 0.155643E+11 1.06 5811.03 01-DEC-00:10 1.06
           
Annual Sum or Average 0.183257E+12 1.06      
Minimum of Months 0.140580E+11 1.05 5811.03   1.05
Maximum of Months 0.155643E+11 1.06 5811.03   1.06



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.157485E+10 1.06 587.98 01-JAN-00:05 1.06
February 0.142244E+10 1.06 587.98 01-FEB-00:10 1.06
March 0.157485E+10 1.06 587.98 01-MAR-00:20 1.06
April 0.152404E+10 1.06 587.98 01-APR-00:10 1.06
May 0.157485E+10 1.06 587.98 01-MAY-00:02 1.05
June 0.152404E+10 1.05 587.98 01-JUN-00:05 1.05
July 0.157485E+10 1.05 587.98 01-JUL-00:02 1.05
August 0.157485E+10 1.05 587.98 01-AUG-00:05 1.05
September 0.152404E+10 1.05 587.98 01-SEP-00:05 1.05
October 0.157485E+10 1.05 587.98 01-OCT-00:10 1.06
November 0.152404E+10 1.06 587.98 01-NOV-00:10 1.06
December 0.157485E+10 1.06 587.98 01-DEC-00:10 1.06
           
Annual Sum or Average 0.185425E+11 1.06      
Minimum of Months 0.142244E+10 1.05 587.98   1.05
Maximum of Months 0.157485E+10 1.06 587.98   1.06



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.249547E+09 0.224592E+09 3556.32 09-JAN-06:01 3200.69 3200.69 35.21 5.94
February 0.143554E+09 0.129198E+09 3423.90 09-FEB-06:02 3081.51 3081.51 34.71 5.51
March 65254575.30 58729117.77 3405.08 01-MAR-06:02 3064.57 3064.57 33.01 5.46
April 3368037.24 3031233.52 628.55 11-APR-05:03 565.69 565.69 24.82 0.68
May 0.00 0.00 0.00 01-MAY-00:02 0.00 0.00 22.49 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00 0.00 22.49 0.00
July 0.00 0.00 0.00 01-JUL-00:02 0.00 0.00 22.49 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00 0.00 22.49 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00 0.00 22.49 0.00
October 1346641.65 1211977.48 144.49 25-OCT-05:02 130.04 130.04 20.66 0.15
November 85450285.57 76905257.01 3559.95 27-NOV-06:01 3203.95 3203.95 35.66 5.95
December 0.340106E+09 0.306095E+09 3569.92 04-DEC-06:01 3212.93 3212.93 37.97 5.98
                 
Annual Sum or Average 0.888625E+09 0.799763E+09            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 20.66 0.00
Maximum of Months 0.340106E+09 0.306095E+09 3569.92   3212.93 3212.93 37.97 5.98



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 8172912.44 7355621.20 210.97 12-JAN-14:30 189.87 189.87 8.91 12.81
February 28197326.91 25377594.22 308.48 22-FEB-13:30 277.64 277.64 8.88 15.67
March 71783087.95 64604779.16 365.73 21-MAR-16:00 329.16 329.16 7.63 17.10
April 0.280163E+09 0.252147E+09 2780.42 28-APR-13:20 2502.38 2502.38 6.71 44.56
May 0.694185E+09 0.624767E+09 2896.40 30-MAY-12:40 2606.76 2606.76 6.71 45.36
June 0.120830E+10 0.108747E+10 10774.37 05-JUN-05:03 9696.94 9696.94 8.27 78.78
July 0.132157E+10 0.118941E+10 21509.44 17-JUL-05:02 19358.50 19358.50 8.88 103.76
August 0.122132E+10 0.109919E+10 15580.96 03-AUG-05:03 14022.87 14022.87 8.48 91.35
September 0.994120E+09 0.894708E+09 9337.46 22-SEP-03:02 8403.72 8403.72 7.68 74.32
October 0.399202E+09 0.359282E+09 6015.65 02-OCT-05:02 5414.09 5414.09 7.98 61.98
November 77017249.27 69315524.34 2123.73 03-NOV-12:30 1911.36 1911.36 8.94 39.55
December 2269675.44 2042707.90 58.76 08-DEC-14:00 52.88 52.88 8.54 6.11
                 
Annual Sum or Average 0.630630E+10 0.567567E+10            
Minimum of Months 2269675.44 2042707.90 58.76   52.88 52.88 6.71 6.11
Maximum of Months 0.132157E+10 0.118941E+10 21509.44   19358.50 19358.50 8.94 103.76



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.586930E+10 0.528237E+10 14804.36 01-JAN-11:47 13323.93 13323.93 8.43 103.76
February 0.847618E+10 0.762856E+10 14804.36 01-FEB-09:40 13323.93 13323.93 8.43 103.76
March 0.136515E+11 0.122864E+11 14804.36 01-MAR-06:08 13323.93 13323.93 8.44 103.76
April 0.250784E+11 0.225705E+11 14804.36 01-APR-04:02 13323.93 13323.93 8.68 103.76
May 0.285801E+11 0.257221E+11 14804.36 01-MAY-00:15 13323.93 13323.93 7.81 103.76
June 0.334323E+11 0.300891E+11 14804.36 01-JUN-00:42 13323.93 13323.93 7.15 103.76
July 0.352260E+11 0.317034E+11 14804.36 01-JUL-00:02 13323.93 13323.93 6.95 103.76
August 0.367411E+11 0.330670E+11 14804.36 01-AUG-00:05 13323.93 13323.93 7.13 103.76
September 0.270175E+11 0.243158E+11 14804.36 01-SEP-00:05 13323.93 13323.93 7.50 103.76
October 0.210072E+11 0.189065E+11 14804.36 01-OCT-07:30 13323.93 13323.93 7.29 103.76
November 0.105783E+11 0.952048E+10 14804.36 01-NOV-03:02 13323.93 13323.93 8.77 103.76
December 0.539900E+10 0.485910E+10 14804.36 01-DEC-06:50 13323.93 13323.93 8.45 103.76
                 
Annual Sum or Average 0.251057E+12 0.225951E+12            
Minimum of Months 0.539900E+10 0.485910E+10 14804.36   13323.93 13323.93 6.95 103.76
Maximum of Months 0.367411E+11 0.330670E+11 14804.36   13323.93 13323.93 8.77 103.76



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.978589E+10 0.880730E+10 3653.63 01-JAN-00:05 3288.27 3288.27 22.17 15.26
February 0.883886E+10 0.795498E+10 3653.63 01-FEB-00:10 3288.27 3288.27 24.62 15.26
March 0.978589E+10 0.880730E+10 3653.63 01-MAR-00:10 3288.27 3288.27 27.45 15.26
April 0.947021E+10 0.852319E+10 3653.63 01-APR-00:10 3288.27 3288.27 30.68 15.26
May 0.978589E+10 0.880730E+10 3653.63 01-MAY-00:02 3288.27 3288.27 27.80 15.26
June 0.947021E+10 0.852319E+10 3653.63 01-JUN-00:05 3288.27 3288.27 35.98 15.26
July 0.978589E+10 0.880730E+10 3653.63 01-JUL-00:02 3288.27 3288.27 43.17 15.26
August 0.978589E+10 0.880730E+10 3653.63 01-AUG-00:05 3288.27 3288.27 47.27 15.26
September 0.947021E+10 0.852319E+10 3653.63 01-SEP-00:05 3288.27 3288.27 30.10 15.26
October 0.978589E+10 0.880730E+10 3653.63 01-OCT-00:10 3288.27 3288.27 26.71 15.26
November 0.947021E+10 0.852319E+10 3653.63 01-NOV-00:10 3288.27 3288.27 27.99 15.26
December 0.978589E+10 0.880730E+10 3653.63 01-DEC-00:10 3288.27 3288.27 30.35 15.26
                 
Annual Sum or Average 0.115221E+12 0.103699E+12            
Minimum of Months 0.883886E+10 0.795498E+10 3653.63   3288.27 3288.27 22.17 15.26
Maximum of Months 0.978589E+10 0.880730E+10 3653.63   3288.27 3288.27 47.27 15.26



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 11967951.72 3590385.52 5.96 01-JAN-06:05 1.79 1.79 55.92 0.44
February 10809762.85 3242928.85 5.96 01-FEB-06:03 1.79 1.79 56.22 0.44
March 11967951.72 3590385.52 5.96 01-MAR-06:02 1.79 1.79 55.67 0.44
April 11581888.76 3474566.63 5.96 01-APR-05:02 1.79 1.79 57.08 0.44
May 11967951.72 3590385.52 5.96 01-MAY-05:02 1.79 1.79 57.28 0.44
June 11581888.76 3474566.63 5.96 01-JUN-05:03 1.79 1.79 56.12 0.44
July 11967951.72 3590385.52 5.96 01-JUL-05:02 1.79 1.79 57.43 0.44
August 11967951.72 3590385.52 5.96 01-AUG-05:03 1.79 1.79 57.24 0.44
September 11581888.76 3474566.63 5.96 01-SEP-05:02 1.79 1.79 56.63 0.44
October 11967951.72 3590385.52 5.96 01-OCT-05:10 1.79 1.79 57.09 0.44
November 11581888.76 3474566.63 5.96 01-NOV-05:03 1.79 1.79 56.66 0.44
December 11967951.72 3590385.52 5.96 01-DEC-06:03 1.79 1.79 56.59 0.44
                 
Annual Sum or Average 0.140913E+09 42273893.99            
Minimum of Months 10809762.85 3242928.85 5.96   1.79 1.79 55.67 0.44
Maximum of Months 11967951.72 3590385.52 5.96   1.79 1.79 57.43 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.730136E+10 0.657122E+10 18443.10 03-JAN-14:30 16598.79 16598.79 23.35 61.34
February 0.105823E+11 0.952404E+10 36870.45 21-FEB-14:50 33183.41 33183.41 22.74 122.68
March 0.174403E+11 0.156963E+11 36872.51 16-MAR-13:50 33185.26 33185.26 22.82 122.68
April 0.343458E+11 0.309112E+11 36957.19 27-APR-13:20 33261.47 33261.47 25.87 122.68
May 0.438547E+11 0.394692E+11 36962.50 19-MAY-14:40 33266.25 33266.25 26.04 122.68
June 0.554639E+11 0.499175E+11 36971.62 20-JUN-15:00 33274.46 33274.46 26.34 122.68
July 0.591210E+11 0.532089E+11 37048.32 17-JUL-05:04 33343.49 33343.49 29.34 122.68
August 0.587203E+11 0.528483E+11 37048.32 02-AUG-07:50 33343.49 33343.49 29.08 122.68
September 0.439875E+11 0.395888E+11 37048.32 14-SEP-09:50 33343.49 33343.49 29.32 122.68
October 0.294295E+11 0.264866E+11 36990.19 03-OCT-14:00 33291.17 33291.17 26.94 122.68
November 0.132944E+11 0.119650E+11 36872.67 08-NOV-15:30 33185.40 33185.40 22.83 122.68
December 0.671526E+10 0.604373E+10 18428.63 08-DEC-14:10 16585.77 16585.77 22.26 61.34
                 
Annual Sum or Average 0.380256E+12 0.342231E+12            
Minimum of Months 0.671526E+10 0.604373E+10 18428.63   16585.77 16585.77 22.26 61.34
Maximum of Months 0.591210E+11 0.532089E+11 37048.32   33343.49 33343.49 29.34 122.68



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 79.95 79.95 22165.89 1159890.15 26-JAN-05:01
February 0.00 0.00 01-FEB-00:10 22.48 22.48 14146.45 1066144.80 09-FEB-06:02
March 0.00 0.00 01-MAR-00:10 21.54 21.54 5868.14 1090603.17 01-MAR-06:02
April 0.00 0.00 01-APR-00:10 24.69 24.69 317.36 156668.83 11-APR-05:03
May 0.00 0.00 01-MAY-00:02 22.49 22.49 0.00 0.00 01-MAY-00:02
June 0.00 0.00 01-JUN-00:05 22.49 22.49 0.00 0.00 01-JUN-00:05
July 0.00 0.00 01-JUL-00:02 22.49 22.49 0.00 0.00 01-JUL-00:02
August 0.00 0.00 01-AUG-00:05 22.49 22.49 0.00 0.00 01-AUG-00:05
September 0.00 0.00 01-SEP-00:05 22.49 22.49 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:10 22.49 22.49 125.60 36932.13 25-OCT-05:02
November 0.00 0.00 01-NOV-00:10 20.48 20.48 7867.54 1123411.26 28-NOV-06:01
December 0.00 0.00 01-DEC-00:10 22.23 22.23 30047.54 1130353.62 27-DEC-06:01
                 
Annual Sum or Average 0.00         6701.56    
Minimum of Months 0.00 0.00   20.48 20.48 0.00 0.00  
Maximum of Months 0.00 0.00   79.95 79.95 30047.54 1159890.15  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 24784.77 967667.60 03-JAN-14:30 9.89 8.76 0.00 0.00 01-JAN-00:05
February 84737.98 1319478.75 21-FEB-14:50 10.35 8.70 228.72 228442.92 21-FEB-08:00
March 171307.34 1337256.60 15-MAR-15:10 10.30 8.63 110.53 223482.40 19-MAR-09:03
April 420613.55 1508065.85 27-APR-12:00 10.33 8.17 94.67 128429.16 08-APR-23:42
May 637017.85 1605202.70 31-MAY-05:03 10.77 7.07 213.43 515613.29 07-MAY-07:12
June 809856.59 1787180.03 08-JUN-05:02 10.98 6.87 31.24 114151.35 28-JUN-01:02
July 862915.90 5525334.59 20-JUL-15:10 19.74 14.00 0.00 0.00 01-JUL-00:02
August 803916.30 2925922.21 03-AUG-05:03 14.04 8.31 1.80 23683.78 13-AUG-23:43
September 654138.56 2006716.21 14-SEP-09:50 11.63 7.01 101.73 322890.22 17-SEP-06:32
October 384447.61 1527678.23 03-OCT-14:00 10.21 6.70 399.87 419126.61 01-OCT-07:30
November 131975.12 1347245.94 08-NOV-15:30 10.26 8.58 31.10 230665.47 24-NOV-04:02
December 11205.47 457516.39 08-DEC-14:10 9.11 8.57 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 418174.33         100.44    
Minimum of Months 11205.47 457516.39   9.11 6.70 0.00 0.00  
Maximum of Months 862915.90 5525334.59   19.74 14.00 399.87 515613.29  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 12918.46 577933.58 03-JAN-14:30 18.75 8.74 0.00 0.00 01-JAN-00:05
February 48946.04 871558.36 21-FEB-16:10 20.68 8.28 0.00 0.00 01-FEB-00:10
March 106893.77 1069504.60 21-MAR-16:00 21.66 8.17 0.00 0.00 01-MAR-00:10
April 296236.26 1539444.25 20-APR-05:03 18.48 8.51 0.00 0.00 01-APR-00:10
May 495582.37 2517659.66 31-MAY-05:03 21.02 7.12 0.00 0.00 01-MAY-00:02
June 673941.68 2560924.84 15-JUN-05:02 21.63 6.77 0.00 0.00 01-JUN-00:05
July 728018.34 5811874.31 20-JUL-15:10 20.23 13.55 0.00 0.00 01-JUL-00:02
August 656423.39 4098845.23 03-AUG-05:03 17.43 8.46 0.00 0.00 01-AUG-00:05
September 536225.90 3228769.85 22-SEP-03:02 17.08 7.73 0.00 0.00 01-SEP-00:05
October 284724.92 2016186.18 02-OCT-05:02 14.47 7.95 0.00 0.00 01-OCT-00:10
November 84284.87 1131625.51 03-NOV-12:30 13.53 8.97 0.00 0.00 01-NOV-00:10
December 4726.84 267125.34 08-DEC-14:10 17.29 8.58 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 328928.99         0.00    
Minimum of Months 4726.84 267125.34   13.53 6.77 0.00 0.00  
Maximum of Months 728018.34 5811874.31   21.66 13.55 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 204002.24 463275.88 03-JAN-17:00 27.02 22.86 0.00 0.00 01-JAN-00:05
February 403284.25 848817.37 20-FEB-16:00 34.15 27.14 0.00 0.00 01-FEB-00:10
March 635303.49 1203642.47 21-MAR-16:00 40.63 30.56 0.00 0.00 01-MAR-00:10
April 1131587.51 1861767.92 21-APR-15:00 52.44 39.49 0.00 0.00 01-APR-00:10
May 653882.35 1291684.99 19-MAY-16:00 42.23 37.58 0.00 0.00 01-MAY-00:02
June 1123737.84 1790658.70 02-JUN-16:00 51.18 43.31 0.00 0.00 01-JUN-00:05
July 1360694.27 2028276.06 03-JUL-16:00 55.39 44.47 0.00 0.00 01-JUL-00:02
August 1537990.38 2170643.76 07-AUG-16:10 57.90 44.64 0.00 0.00 01-AUG-00:05
September 636232.75 1231441.86 19-SEP-16:00 41.13 36.48 0.00 0.00 01-SEP-00:05
October 618508.69 1423002.79 03-OCT-14:10 44.59 36.90 0.00 0.00 01-OCT-00:10
November 599520.55 1153611.04 03-NOV-16:00 39.72 29.53 0.00 0.00 01-NOV-00:10
December 689514.53 1042329.42 10-DEC-15:00 37.70 25.18 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 801975.60         0.00    
Minimum of Months 204002.24 463275.88   27.02 22.86 0.00 0.00  
Maximum of Months 1537990.38 2170643.76   57.90 44.64 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 57.72 57.72 14445.66 48134.75 31-JAN-13:00
February 0.00 0.00 01-FEB-00:10 56.63 56.63 14508.28 48135.89 01-FEB-13:00
March 0.00 0.00 01-MAR-00:10 56.19 56.19 14811.58 47252.47 01-MAR-12:30
April 0.00 0.00 01-APR-00:10 57.49 57.49 13133.85 44557.09 03-APR-12:00
May 0.00 0.00 01-MAY-00:02 57.89 57.89 12540.80 41477.82 01-MAY-12:00
June 0.00 0.00 01-JUN-00:05 56.77 56.77 11904.90 38081.66 01-JUN-11:40
July 0.00 0.00 01-JUL-00:02 57.76 57.76 10599.37 35590.61 03-JUL-11:20
August 0.00 0.00 01-AUG-00:05 57.59 57.59 11479.08 35726.54 31-AUG-11:40
September 0.00 0.00 01-SEP-00:05 57.20 57.20 11352.80 38040.33 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 57.79 57.79 12173.61 41529.02 31-OCT-11:30
November 0.00 0.00 01-NOV-00:10 57.18 57.18 13294.34 44813.83 30-NOV-12:50
December 0.00 0.00 01-DEC-00:10 57.16 57.16 13665.86 47167.20 29-DEC-12:20
                 
Annual Sum or Average 0.00         12816.45    
Minimum of Months 0.00 0.00   56.19 56.19 10599.37 35590.61  
Maximum of Months 0.00 0.00   57.89 57.89 14811.58 48135.89  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 12250.80 576828.01 03-JAN-14:30 23.35 21.10 3015.84 117451.28 09-JAN-11:00
February 49231.36 884967.81 23-FEB-14:10 24.55 21.10 2429.72 133932.55 09-FEB-13:40
March 108107.01 1045461.83 21-MAR-16:00 25.18 21.10 1887.07 124094.33 01-MAR-12:50
April 320519.93 2447265.14 27-APR-13:20 25.87 21.10 2069.63 114450.12 05-APR-05:40
May 574231.55 2535237.46 19-MAY-14:40 26.04 22.01 474.83 86487.15 05-MAY-06:00
June 845406.10 2686065.08 20-JUN-15:00 26.34 22.87 132.40 61121.33 11-JUN-03:45
July 1191006.87 6335792.98 20-JUL-15:30 33.45 27.83 0.00 0.00 01-JUL-00:02
August 893787.56 4519801.08 02-AUG-08:20 29.91 25.30 58.40 25819.29 25-AUG-05:00
September 703984.35 4213102.11 14-SEP-09:50 29.32 24.92 63.81 47104.68 28-SEP-03:30
October 321056.05 2993054.69 03-OCT-14:00 26.94 23.49 486.81 75633.81 10-OCT-07:50
November 81734.25 1007108.06 09-NOV-15:00 25.03 21.10 1847.99 130639.74 06-NOV-06:40
December 3936.76 296925.85 08-DEC-14:10 22.26 21.10 3087.17 132666.80 22-DEC-06:50
                 
Annual Sum or Average 427845.18         1289.76    
Minimum of Months 3936.76 296925.85   22.26 21.10 0.00 0.00  
Maximum of Months 1191006.87 6335792.98   33.45 27.83 3087.17 133932.55  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.684820E+09 0.00 0.290096E+10 0.609476E+10 0.00 0.00
February 0.382030E+09 0.00 0.103041E+11 0.635283E+10 0.00 0.00
March 78709674.10 0.00 0.257351E+11 0.916595E+10 0.00 0.00
April 0.00 0.00 0.739542E+11 0.119890E+11 0.00 0.00
May 0.00 0.00 0.106927E+12 0.116080E+11 0.00 0.00
June 0.00 0.00 0.147463E+12 0.142294E+11 0.00 0.00
July 0.00 0.00 0.178679E+12 0.147592E+11 0.00 0.00
August 0.00 0.00 0.171692E+12 0.177695E+11 0.00 0.00
September 0.00 0.00 0.114534E+12 0.114275E+11 0.00 0.00
October 0.00 0.00 0.638360E+11 0.100340E+11 0.00 0.00
November 14898785.18 0.00 0.184959E+11 0.827204E+10 0.00 0.00
December 0.301198E+09 0.00 0.129178E+10 0.757087E+10 0.00 0.00
             
Annual Sum or Average 0.146166E+10 0.00 0.915813E+12 0.129273E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.129178E+10 0.609476E+10 0.00 0.00
Maximum of Months 0.684820E+09 0.00 0.178679E+12 0.177695E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.447558E+11 0.00 0.224260E+11 0.421904E+11 0.00 0.00
February 0.253096E+11 0.00 0.797845E+11 0.426380E+11 0.00 0.00
March 0.110228E+11 0.00 0.191497E+12 0.575167E+11 0.00 0.00
April 0.376917E+09 0.00 0.527686E+12 0.730413E+11 0.00 0.00
May 0.00 0.00 0.943912E+12 0.991191E+11 0.00 0.00
June 0.00 0.00 0.126226E+13 0.117768E+12 0.00 0.00
July 0.00 0.00 0.140009E+13 0.109067E+12 0.00 0.00
August 0.00 0.00 0.122246E+13 0.112575E+12 0.00 0.00
September 0.00 0.00 0.979308E+12 0.912446E+11 0.00 0.00
October 32174061.13 0.00 0.512471E+12 0.684350E+11 0.00 0.00
November 0.137925E+11 0.00 0.138898E+12 0.495571E+11 0.00 0.00
December 0.620201E+11 0.00 0.824353E+10 0.409075E+11 0.00 0.00
             
Annual Sum or Average 0.157310E+12 0.00 0.728903E+13 0.904059E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.824353E+10 0.409075E+11 0.00 0.00
Maximum of Months 0.620201E+11 0.00 0.140009E+13 0.117768E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.147150E+11 0.00 0.163433E+10 0.351831E+10 0.00 0.00
February 0.883484E+10 0.00 0.661478E+10 0.344236E+10 0.00 0.00
March 0.473689E+10 0.00 0.174752E+11 0.461217E+10 0.00 0.00
April 0.463110E+09 0.00 0.566612E+11 0.677574E+10 0.00 0.00
May 0.00 0.00 0.104488E+12 0.101876E+11 0.00 0.00
June 0.00 0.00 0.144941E+12 0.132197E+11 0.00 0.00
July 0.00 0.00 0.158949E+12 0.122204E+11 0.00 0.00
August 0.00 0.00 0.136480E+12 0.121222E+11 0.00 0.00
September 0.00 0.00 0.106326E+12 0.939541E+10 0.00 0.00
October 0.318260E+09 0.00 0.520712E+11 0.625938E+10 0.00 0.00
November 0.675366E+10 0.00 0.114726E+11 0.404378E+10 0.00 0.00
December 0.188656E+11 0.00 0.561952E+09 0.347485E+10 0.00 0.00
             
Annual Sum or Average 0.546873E+11 0.00 0.797676E+12 0.892720E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.561952E+09 0.344236E+10 0.00 0.00
Maximum of Months 0.188656E+11 0.00 0.158949E+12 0.132197E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.130517E+10 0.173303E+11 0.00 0.00
February 0.00 0.00 0.456754E+10 0.151622E+11 0.00 0.00
March 0.00 0.00 0.123944E+11 0.177311E+11 0.00 0.00
April 0.00 0.00 0.368188E+11 0.165632E+11 0.00 0.00
May 0.00 0.00 0.636084E+11 0.178209E+11 0.00 0.00
June 0.00 0.00 0.807094E+11 0.174552E+11 0.00 0.00
July 0.00 0.00 0.936124E+11 0.176099E+11 0.00 0.00
August 0.00 0.00 0.918851E+11 0.197342E+11 0.00 0.00
September 0.00 0.00 0.735674E+11 0.188069E+11 0.00 0.00
October 0.00 0.00 0.409108E+11 0.190095E+11 0.00 0.00
November 0.00 0.00 0.106912E+11 0.180068E+11 0.00 0.00
December 0.00 0.00 0.224755E+09 0.176489E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.510295E+12 0.212879E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.224755E+09 0.151622E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.936124E+11 0.197342E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.475215E+12 0.247566E+12 0.00 15.83
February 0.00 0.00 0.729744E+12 0.304782E+12 0.00 22.93
March 0.00 0.00 0.114116E+13 0.425004E+12 0.00 33.03
April 0.00 0.00 0.144166E+13 0.513386E+12 0.00 33.10
May 0.00 0.00 0.496341E+12 0.256637E+12 0.00 9.29
June 0.00 0.00 0.821075E+12 0.349220E+12 0.00 8.76
July 0.00 0.00 0.119410E+13 0.454108E+12 0.00 10.02
August 0.00 0.00 0.153181E+13 0.567212E+12 0.00 28.27
September 0.00 0.00 0.488732E+12 0.246765E+12 0.00 8.11
October 0.00 0.00 0.831637E+12 0.344067E+12 0.00 19.99
November 0.00 0.00 0.111469E+13 0.413431E+12 0.00 33.71
December 0.00 0.00 0.147153E+13 0.507359E+12 0.00 47.37
             
Annual Sum or Average 0.00 0.00 0.117377E+14 0.462954E+13 0.00 270.42
Minimum of Months 0.00 0.00 0.475215E+12 0.246765E+12 0.00 8.11
Maximum of Months 0.00 0.00 0.153181E+13 0.567212E+12 0.00 47.37



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.623342E+10 0.296221E+10 0.00 0.00
February 0.00 0.00 0.118039E+11 0.394518E+10 0.00 0.00
March 0.00 0.00 0.199120E+11 0.578369E+10 0.00 0.00
April 0.00 0.00 0.267540E+11 0.781906E+10 0.00 0.00
May 0.00 0.00 0.847460E+10 0.376668E+10 0.00 0.00
June 0.00 0.00 0.153560E+11 0.573117E+10 0.00 0.00
July 0.00 0.00 0.228924E+11 0.770250E+10 0.00 0.00
August 0.00 0.00 0.296667E+11 0.932157E+10 0.00 0.00
September 0.00 0.00 0.843176E+10 0.365639E+10 0.00 0.00
October 0.00 0.00 0.144775E+11 0.484050E+10 0.00 0.00
November 0.00 0.00 0.191796E+11 0.545430E+10 0.00 0.00
December 0.00 0.00 0.254155E+11 0.656092E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.208597E+12 0.675442E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.623342E+10 0.296221E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.296667E+11 0.932157E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.424855E+11 0.248005E+11 0.00 0.00
February 0.00 0.00 0.997595E+11 0.351152E+11 0.00 0.00
March 0.00 0.00 0.180073E+12 0.533088E+11 0.00 0.00
April 0.00 0.00 0.251634E+12 0.738623E+11 0.00 0.00
May 0.00 0.00 0.786006E+11 0.353838E+11 0.00 0.00
June 0.00 0.00 0.146447E+12 0.546073E+11 0.00 0.00
July 0.00 0.00 0.218430E+12 0.734119E+11 0.00 0.00
August 0.00 0.00 0.279044E+12 0.880186E+11 0.00 0.00
September 0.00 0.00 0.775527E+11 0.341838E+11 0.00 0.00
October 0.00 0.00 0.131613E+12 0.448467E+11 0.00 0.00
November 0.00 0.00 0.169864E+12 0.496192E+11 0.00 0.00
December 0.00 0.00 0.223307E+12 0.592378E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.189881E+13 0.626396E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.424855E+11 0.248005E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.279044E+12 0.880186E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.224297E+10 0.207733E+10 0.00 0.00
February 0.00 0.00 0.851996E+10 0.324449E+10 0.00 0.00
March 0.00 0.00 0.169289E+11 0.515513E+10 0.00 0.00
April 0.00 0.00 0.248837E+11 0.736459E+10 0.00 0.00
May 0.00 0.00 0.785572E+10 0.356401E+10 0.00 0.00
June 0.00 0.00 0.148010E+11 0.552555E+10 0.00 0.00
July 0.00 0.00 0.220473E+11 0.741907E+10 0.00 0.00
August 0.00 0.00 0.280174E+11 0.885914E+10 0.00 0.00
September 0.00 0.00 0.773651E+10 0.343916E+10 0.00 0.00
October 0.00 0.00 0.126196E+11 0.440366E+10 0.00 0.00
November 0.00 0.00 0.154699E+11 0.470695E+10 0.00 0.00
December 0.00 0.00 0.200807E+11 0.555023E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.181204E+12 0.613093E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.224297E+10 0.207733E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.280174E+11 0.885914E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.609476E+10 0.290096E+10 0.684820E+09 0.00 0.00 0.00 0.00 0.00
February 0.635283E+10 0.103041E+11 0.382030E+09 0.00 0.00 0.00 0.00 0.00
March 0.916595E+10 0.257351E+11 78709674.10 0.00 0.00 0.00 0.00 0.00
April 0.119890E+11 0.739542E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.116080E+11 0.106927E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142294E+11 0.147463E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147592E+11 0.178679E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.177695E+11 0.171692E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.114275E+11 0.114534E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.100340E+11 0.638360E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.827204E+10 0.184959E+11 14898785.18 0.00 0.00 0.00 0.00 0.00
December 0.757087E+10 0.129178E+10 0.301198E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.129273E+12 0.915813E+12 0.146166E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.609476E+10 0.129178E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.177695E+11 0.178679E+12 0.684820E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.421904E+11 0.224260E+11 0.447558E+11 0.00 0.00 0.00 0.00 0.00
February 0.426380E+11 0.797845E+11 0.253096E+11 0.00 0.00 0.00 0.00 0.00
March 0.575167E+11 0.191497E+12 0.110228E+11 0.00 0.00 0.00 0.00 0.00
April 0.730413E+11 0.527686E+12 0.376917E+09 0.00 0.00 0.00 0.00 0.00
May 0.991191E+11 0.943912E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.117768E+12 0.126226E+13 0.00 0.00 0.00 0.00 0.00 0.00
July 0.109067E+12 0.140009E+13 0.00 0.00 0.00 0.00 0.00 0.00
August 0.112575E+12 0.122246E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.912446E+11 0.979308E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.684350E+11 0.512471E+12 32174061.13 0.00 0.00 0.00 0.00 0.00
November 0.495571E+11 0.138898E+12 0.137925E+11 0.00 0.00 0.00 0.00 0.00
December 0.409075E+11 0.824353E+10 0.620201E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.904059E+12 0.728903E+13 0.157310E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.409075E+11 0.824353E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117768E+12 0.140009E+13 0.620201E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.351831E+10 0.163433E+10 0.147150E+11 0.00 0.00 0.00 0.00 0.00
February 0.344236E+10 0.661478E+10 0.883484E+10 0.00 0.00 0.00 0.00 0.00
March 0.461217E+10 0.174752E+11 0.473689E+10 0.00 0.00 0.00 0.00 0.00
April 0.677574E+10 0.566612E+11 0.463110E+09 0.00 0.00 0.00 0.00 0.00
May 0.101876E+11 0.104488E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.132197E+11 0.144941E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.122204E+11 0.158949E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.121222E+11 0.136480E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.939541E+10 0.106326E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.625938E+10 0.520712E+11 0.318260E+09 0.00 0.00 0.00 0.00 0.00
November 0.404378E+10 0.114726E+11 0.675366E+10 0.00 0.00 0.00 0.00 0.00
December 0.347485E+10 0.561952E+09 0.188656E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.892720E+11 0.797676E+12 0.546873E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.344236E+10 0.561952E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.132197E+11 0.158949E+12 0.188656E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.173303E+11 0.130517E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.151622E+11 0.456754E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.177311E+11 0.123944E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.165632E+11 0.368188E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.178209E+11 0.636084E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.174552E+11 0.807094E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.176099E+11 0.936124E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.197342E+11 0.918851E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.188069E+11 0.735674E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.190095E+11 0.409108E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.180068E+11 0.106912E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.176489E+11 0.224755E+09 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.212879E+12 0.510295E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.151622E+11 0.224755E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.197342E+11 0.936124E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.108900E+12 0.379090E+12 0.00 0.00 0.00 0.423505E+11 0.00 0.00
February 0.983611E+11 0.584964E+12 0.00 0.00 0.00 0.613643E+11 0.00 0.00
March 0.108900E+12 0.913862E+12 0.00 0.00 0.00 0.884049E+11 0.00 0.00
April 0.105387E+12 0.112265E+13 0.00 0.00 0.00 0.885814E+11 0.00 0.00
May 0.108900E+12 0.373575E+12 0.00 0.00 0.00 0.248597E+11 0.00 0.00
June 0.105387E+12 0.600803E+12 0.00 0.00 0.00 0.234561E+11 0.00 0.00
July 0.108900E+12 0.875839E+12 0.00 0.00 0.00 0.268219E+11 0.00 0.00
August 0.108900E+12 0.114950E+13 0.00 0.00 0.00 0.756585E+11 0.00 0.00
September 0.105387E+12 0.369167E+12 0.00 0.00 0.00 0.217156E+11 0.00 0.00
October 0.108900E+12 0.650194E+12 0.00 0.00 0.00 0.534837E+11 0.00 0.00
November 0.105387E+12 0.897255E+12 0.00 0.00 0.00 0.902065E+11 0.00 0.00
December 0.108900E+12 0.120041E+13 0.00 0.00 0.00 0.126767E+12 0.00 0.00
                 
Annual Sum or Average 0.128221E+13 0.911730E+13 0.00 0.00 0.00 0.723670E+12 0.00 0.00
Minimum of Months 0.983611E+11 0.369167E+12 0.00 0.00 0.00 0.217156E+11 0.00 0.00
Maximum of Months 0.108900E+12 0.120041E+13 0.00 0.00 0.00 0.126767E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.163678E+10 0.490799E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.147838E+10 0.933706E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.163678E+10 0.157651E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.158398E+10 0.205189E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.163678E+10 0.634470E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.158398E+10 0.112088E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.163678E+10 0.168267E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.163678E+10 0.219819E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.158398E+10 0.635934E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.163678E+10 0.112737E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.158398E+10 0.153093E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.163678E+10 0.204914E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.192717E+11 0.160325E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.147838E+10 0.490799E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.163678E+10 0.219819E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.155643E+11 0.332493E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.140580E+11 0.787024E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.155643E+11 0.142329E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.150622E+11 0.192834E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.155643E+11 0.587811E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.150622E+11 0.106901E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.155643E+11 0.160582E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.155643E+11 0.206590E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.150622E+11 0.584310E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.155643E+11 0.102330E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.150622E+11 0.135307E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.155643E+11 0.179634E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.183257E+12 0.145567E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.140580E+11 0.332493E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.155643E+11 0.206590E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.157485E+10 0.174049E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.142244E+10 0.669791E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.157485E+10 0.133486E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.152404E+10 0.190431E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.157485E+10 0.586656E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.152404E+10 0.107995E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.157485E+10 0.162031E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.157485E+10 0.207331E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.152404E+10 0.582139E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.157485E+10 0.979080E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.152404E+10 0.122870E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.157485E+10 0.161053E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.185425E+11 0.138437E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.142244E+10 0.174049E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.157485E+10 0.207331E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.609476E+10 0.684820E+09 0.290096E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.635283E+10 0.382030E+09 0.103041E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.916595E+10 78709674.10 0.257351E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.119890E+11 0.00 0.739542E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.116080E+11 0.00 0.106927E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142294E+11 0.00 0.147463E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147592E+11 0.00 0.178679E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.177695E+11 0.00 0.171692E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.114275E+11 0.00 0.114534E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.100340E+11 0.00 0.638360E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.827204E+10 14898785.18 0.184959E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.757087E+10 0.301198E+09 0.129178E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.129273E+12 0.146166E+10 0.915813E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.609476E+10 0.00 0.129178E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.177695E+11 0.684820E+09 0.178679E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.421904E+11 0.447558E+11 0.224260E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.426380E+11 0.253096E+11 0.797845E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.575167E+11 0.110228E+11 0.191497E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.730413E+11 0.376917E+09 0.527686E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.991191E+11 0.00 0.943912E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.117768E+12 0.00 0.126226E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.109067E+12 0.00 0.140009E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.112575E+12 0.00 0.122246E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.912446E+11 0.00 0.979308E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.684350E+11 32174061.13 0.512471E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.495571E+11 0.137925E+11 0.138898E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.409075E+11 0.620201E+11 0.824353E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.904059E+12 0.157310E+12 0.728903E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.409075E+11 0.00 0.824353E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117768E+12 0.620201E+11 0.140009E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.351831E+10 0.147150E+11 0.163433E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.344236E+10 0.883484E+10 0.661478E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.461217E+10 0.473689E+10 0.174752E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677574E+10 0.463110E+09 0.566612E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.101876E+11 0.00 0.104488E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.132197E+11 0.00 0.144941E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.122204E+11 0.00 0.158949E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.121222E+11 0.00 0.136480E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.939541E+10 0.00 0.106326E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.625938E+10 0.318260E+09 0.520712E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.404378E+10 0.675366E+10 0.114726E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.347485E+10 0.188656E+11 0.561952E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.892720E+11 0.546873E+11 0.797676E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.344236E+10 0.00 0.561952E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.132197E+11 0.188656E+11 0.158949E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.173303E+11 0.00 0.130517E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.151622E+11 0.00 0.456754E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.177311E+11 0.00 0.123944E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.165632E+11 0.00 0.368188E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.178209E+11 0.00 0.636084E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.174552E+11 0.00 0.807094E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.176099E+11 0.00 0.936124E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.197342E+11 0.00 0.918851E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.188069E+11 0.00 0.735674E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.190095E+11 0.00 0.409108E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.180068E+11 0.00 0.106912E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.176489E+11 0.00 0.224755E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.212879E+12 0.00 0.510295E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.151622E+11 0.00 0.224755E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.197342E+11 0.00 0.936124E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.108900E+12 0.00 0.475215E+12 0.00 0.961254E+11 0.00 0.00 0.00 0.425411E+11 0.00 0.00 0.00
February 0.983611E+11 0.00 0.729744E+12 0.00 0.144780E+12 0.00 0.00 0.00 0.616405E+11 0.00 0.00 0.00
March 0.108900E+12 0.00 0.114116E+13 0.00 0.227301E+12 0.00 0.00 0.00 0.888028E+11 0.00 0.00 0.00
April 0.105387E+12 0.00 0.144166E+13 0.00 0.319019E+12 0.00 0.00 0.00 0.889801E+11 0.00 0.00 0.00
May 0.108900E+12 0.00 0.496341E+12 0.00 0.122766E+12 0.00 0.00 0.00 0.249716E+11 0.00 0.00 0.00
June 0.105387E+12 0.00 0.821075E+12 0.00 0.220272E+12 0.00 0.00 0.00 0.235617E+11 0.00 0.00 0.00
July 0.108900E+12 0.00 0.119410E+13 0.00 0.318265E+12 0.00 0.00 0.00 0.269426E+11 0.00 0.00 0.00
August 0.108900E+12 0.00 0.153181E+13 0.00 0.382313E+12 0.00 0.00 0.00 0.759990E+11 0.00 0.00 0.00
September 0.105387E+12 0.00 0.488732E+12 0.00 0.119565E+12 0.00 0.00 0.00 0.218134E+11 0.00 0.00 0.00
October 0.108900E+12 0.00 0.831637E+12 0.00 0.181443E+12 0.00 0.00 0.00 0.537245E+11 0.00 0.00 0.00
November 0.105387E+12 0.00 0.111469E+13 0.00 0.217432E+12 0.00 0.00 0.00 0.906125E+11 0.00 0.00 0.00
December 0.108900E+12 0.00 0.147153E+13 0.00 0.271121E+12 0.00 0.00 0.00 0.127338E+12 0.00 0.00 0.00
                         
Annual Sum or Average 0.128221E+13 0.00 0.117377E+14 0.00 0.262040E+13 0.00 0.00 0.00 0.726928E+12 0.00 0.00 0.00
Minimum of Months 0.983611E+11 0.00 0.475215E+12 0.00 0.961254E+11 0.00 0.00 0.00 0.218134E+11 0.00 0.00 0.00
Maximum of Months 0.108900E+12 0.00 0.153181E+13 0.00 0.382313E+12 0.00 0.00 0.00 0.127338E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.163678E+10 0.00 0.623342E+10 0.00 0.132543E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.147838E+10 0.00 0.118039E+11 0.00 0.246680E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.163678E+10 0.00 0.199120E+11 0.00 0.414691E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.158398E+10 0.00 0.267540E+11 0.00 0.623508E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.163678E+10 0.00 0.847460E+10 0.00 0.212990E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.158398E+10 0.00 0.153560E+11 0.00 0.414719E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.163678E+10 0.00 0.228924E+11 0.00 0.606573E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.163678E+10 0.00 0.296667E+11 0.00 0.768479E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.158398E+10 0.00 0.843176E+10 0.00 0.207242E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.163678E+10 0.00 0.144775E+11 0.00 0.320373E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.158398E+10 0.00 0.191796E+11 0.00 0.387032E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.163678E+10 0.00 0.254155E+11 0.00 0.492414E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.192717E+11 0.00 0.208597E+12 0.00 0.482724E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.147838E+10 0.00 0.623342E+10 0.00 0.132543E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.163678E+10 0.00 0.296667E+11 0.00 0.768479E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.155643E+11 0.00 0.424855E+11 0.00 0.923621E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.140580E+11 0.00 0.997595E+11 0.00 0.210572E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.155643E+11 0.00 0.180073E+12 0.00 0.377446E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.150622E+11 0.00 0.251634E+12 0.00 0.588001E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.155643E+11 0.00 0.786006E+11 0.00 0.198195E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.150622E+11 0.00 0.146447E+12 0.00 0.395451E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.155643E+11 0.00 0.218430E+12 0.00 0.578476E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.155643E+11 0.00 0.279044E+12 0.00 0.724544E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.150622E+11 0.00 0.775527E+11 0.00 0.191217E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.155643E+11 0.00 0.131613E+12 0.00 0.292825E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.150622E+11 0.00 0.169864E+12 0.00 0.345570E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.155643E+11 0.00 0.223307E+12 0.00 0.436735E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.183257E+12 0.00 0.189881E+13 0.00 0.443139E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.140580E+11 0.00 0.424855E+11 0.00 0.923621E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.155643E+11 0.00 0.279044E+12 0.00 0.724544E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.157485E+10 0.00 0.224297E+10 0.00 0.502485E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.142244E+10 0.00 0.851996E+10 0.00 0.182205E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.157485E+10 0.00 0.169289E+11 0.00 0.358028E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.152404E+10 0.00 0.248837E+11 0.00 0.584055E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.157485E+10 0.00 0.785572E+10 0.00 0.198916E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.152404E+10 0.00 0.148010E+11 0.00 0.400150E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.157485E+10 0.00 0.220473E+11 0.00 0.584422E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.157485E+10 0.00 0.280174E+11 0.00 0.728429E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.152404E+10 0.00 0.773651E+10 0.00 0.191512E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.157485E+10 0.00 0.126196E+11 0.00 0.282881E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.152404E+10 0.00 0.154699E+11 0.00 0.318290E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.157485E+10 0.00 0.200807E+11 0.00 0.397538E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.185425E+11 0.00 0.181204E+12 0.00 0.427668E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.142244E+10 0.00 0.224297E+10 0.00 0.502485E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.157485E+10 0.00 0.280174E+11 0.00 0.728429E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.414193E+09 0.00 0.00 0.115887E+09 0.00 0.00 0.751231E+11 0.00 1.01
February 0.217715E+09 0.00 0.00 96897803.50 0.00 0.00 0.622728E+11 0.00 1.13
March 0.165079E+09 0.00 0.00 0.110306E+09 0.00 0.00 0.663082E+11 0.00 1.40
April 80502808.39 0.526003E+09 0.00 98417282.92 29204059.34 0.00 0.388898E+11 0.00 1.21
May 73786370.88 0.185222E+10 0.00 74482840.13 84650279.86 0.00 0.192754E+11 0.00 0.98
June 27936924.26 0.626914E+10 0.00 48952562.98 0.121106E+09 0.00 0.753423E+10 0.00 0.77
July 44205187.08 0.119370E+11 0.00 27690123.36 0.103769E+09 0.00 0.242734E+10 0.00 0.77
August 38666721.52 0.457065E+10 0.00 79387747.18 85202002.55 0.00 0.110068E+11 0.00 1.01
September 0.189090E+09 0.216515E+10 0.00 98081991.57 40728298.30 0.00 0.180623E+11 0.00 1.06
October 0.233140E+09 0.356418E+09 0.00 0.133649E+09 5219731.31 0.00 0.511051E+11 0.00 1.57
November 0.340552E+09 0.00 0.00 0.136193E+09 0.00 0.00 0.755446E+11 0.00 1.42
December 0.475998E+09 0.00 0.00 0.129846E+09 0.00 0.00 0.815073E+11 0.00 1.00
                   
Annual Sum or Average 0.230087E+10 0.276766E+11 0.00 0.114979E+10 0.469879E+09 0.00 0.509057E+12 0.00 1.11
Minimum of Months 27936924.26 0.00 0.00 27690123.36 0.00 0.00 0.242734E+10 0.00 0.77
Maximum of Months 0.475998E+09 0.119370E+11 0.00 0.136193E+09 0.121106E+09 0.00 0.815073E+11 0.00 1.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.218510E+10 0.00 0.00 81194720.54 0.00 0.00 0.497258E+11 0.00 0.67
February 0.242472E+10 0.00 0.00 78750944.33 0.00 0.00 0.455158E+11 0.00 0.82
March 0.339487E+10 0.00 0.00 0.101400E+09 0.00 0.00 0.519915E+11 0.00 1.06
April 0.729820E+10 0.291148E+09 0.00 88473459.72 93330102.58 0.00 0.308530E+11 0.00 1.08
May 0.322816E+10 0.988389E+09 0.00 65587162.37 0.184349E+09 0.00 0.130755E+11 0.00 0.72
June 0.253495E+10 0.351065E+10 0.00 39795898.47 0.280928E+09 0.00 0.449545E+10 0.00 0.60
July 0.618705E+09 0.115434E+11 0.00 11613880.04 0.224880E+10 0.00 0.737766E+09 0.00 0.60
August 0.250633E+10 0.404005E+10 0.00 55745250.04 0.795176E+09 0.00 0.717899E+10 0.00 0.86
September 0.216811E+10 0.197451E+10 0.00 62730525.38 0.331932E+09 0.00 0.996400E+10 0.00 0.73
October 0.354524E+10 0.512508E+09 0.00 93033166.01 14635925.61 0.00 0.345923E+11 0.00 1.05
November 0.401098E+10 0.00 0.00 98630165.03 0.00 0.00 0.519109E+11 0.00 0.98
December 0.327316E+10 0.00 0.00 96592967.33 0.00 0.00 0.582937E+11 0.00 0.73
                   
Annual Sum or Average 0.371885E+11 0.228606E+11 0.00 0.873548E+09 0.394915E+10 0.00 0.358335E+12 0.00 0.83
Minimum of Months 0.618705E+09 0.00 0.00 11613880.04 0.00 0.00 0.737766E+09 0.00 0.60
Maximum of Months 0.729820E+10 0.115434E+11 0.00 0.101400E+09 0.224880E+10 0.00 0.582937E+11 0.00 1.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.874652E+11 0.00 0.00 0.394163E+09 0.00 0.00 0.280172E+12 0.00 0.49
February 0.590480E+11 0.00 0.00 0.424788E+09 0.00 0.00 0.280047E+12 0.00 0.60
March 0.295733E+11 0.00 0.00 0.646773E+09 0.00 0.00 0.354875E+12 0.00 0.77
April 0.179793E+11 0.294303E+10 0.00 0.676643E+09 0.558008E+09 0.00 0.229189E+12 0.00 0.72
May 0.198176E+11 0.103944E+11 0.00 0.576701E+09 0.126858E+10 0.00 0.112638E+12 0.00 0.62
June 0.117480E+11 0.362601E+11 0.00 0.357615E+09 0.202721E+10 0.00 0.414136E+11 0.00 0.49
July 0.246393E+10 0.102718E+12 0.00 94492930.50 0.692007E+10 0.00 0.563463E+10 0.00 0.46
August 0.660085E+10 0.337853E+11 0.00 0.427856E+09 0.312480E+10 0.00 0.570609E+11 0.00 0.59
September 0.149087E+11 0.193417E+11 0.00 0.512661E+09 0.179417E+10 0.00 0.786705E+11 0.00 0.60
October 0.209039E+11 0.462009E+10 0.00 0.673880E+09 0.417050E+09 0.00 0.254511E+12 0.00 0.80
November 0.457363E+11 0.00 0.00 0.549871E+09 0.00 0.00 0.312815E+12 0.00 0.67
December 0.996488E+11 0.00 0.00 0.361673E+09 0.00 0.00 0.269415E+12 0.00 0.46
                   
Annual Sum or Average 0.415894E+12 0.210062E+12 0.00 0.569712E+10 0.161099E+11 0.00 0.227644E+13 0.00 0.61
Minimum of Months 0.246393E+10 0.00 0.00 94492930.50 0.00 0.00 0.563463E+10 0.00 0.46
Maximum of Months 0.996488E+11 0.102718E+12 0.00 0.676643E+09 0.692007E+10 0.00 0.354875E+12 0.00 0.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.168758E+11 0.00 0.00 10769532.38 0.00 0.373651E+09 0.979676E+10 0.00 0.38
February 0.122365E+11 0.00 0.00 17085509.38 0.00 7508652.85 0.130621E+11 0.00 0.48
March 0.902547E+10 0.00 0.00 36301652.36 0.00 0.00 0.212615E+11 0.00 0.65
April 0.273173E+10 0.161141E+09 0.00 57241181.59 63029177.62 0.00 0.179898E+11 0.00 0.68
May 0.154059E+10 0.688701E+09 0.00 59020426.64 0.112897E+09 0.00 0.972868E+10 0.00 0.61
June 0.110594E+10 0.301161E+10 0.00 42278190.26 0.192301E+09 0.00 0.391151E+10 0.00 0.49
July 0.256659E+09 0.986578E+10 0.00 11064403.72 0.747005E+09 0.00 0.496907E+09 0.00 0.46
August 0.526172E+09 0.288174E+10 0.00 47610664.41 0.321519E+09 0.00 0.549459E+10 0.00 0.58
September 0.127263E+10 0.155083E+10 0.00 53960719.74 0.183324E+09 0.00 0.625882E+10 0.00 0.57
October 0.403688E+10 0.319962E+09 0.00 51248137.77 59956992.53 0.00 0.182996E+11 0.00 0.73
November 0.115377E+11 0.00 0.00 24719762.77 0.00 0.152114E+09 0.150820E+11 0.00 0.54
December 0.185245E+11 0.00 0.00 7839441.35 0.00 0.409594E+09 0.782397E+10 0.00 0.35
                   
Annual Sum or Average 0.796705E+11 0.184798E+11 0.00 0.419140E+09 0.168003E+10 0.942867E+09 0.129206E+12 0.00 0.54
Minimum of Months 0.256659E+09 0.00 0.00 7839441.35 0.00 0.00 0.496907E+09 0.00 0.35
Maximum of Months 0.185245E+11 0.986578E+10 0.00 59020426.64 0.747005E+09 0.409594E+09 0.212615E+11 0.00 0.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.469554E+10 0.00 0.00 427685.82 0.00 13667033.92 0.803829E+09 0.00 0.55
February 0.357856E+10 0.00 0.00 1673510.95 0.00 729794.91 0.139099E+10 0.00 0.68
March 0.312182E+10 0.00 0.00 4316542.81 0.00 0.00 0.260737E+10 0.00 0.90
April 0.198814E+10 48137233.41 0.00 7682673.06 16018324.54 0.00 0.253126E+10 0.00 1.08
May 0.762361E+09 0.191244E+09 0.00 7787487.25 31754577.76 0.00 0.140404E+10 0.00 0.83
June 0.459168E+09 0.752241E+09 0.00 6096436.87 48365567.96 0.00 0.638705E+09 0.00 0.83
July 0.116876E+09 0.195367E+10 0.00 1668667.76 0.398515E+09 0.00 97554348.48 0.00 0.82
August 0.494811E+09 0.661967E+09 0.00 7066070.45 0.145464E+09 0.00 0.855281E+09 0.00 1.03
September 0.602019E+09 0.300768E+09 0.00 6273055.65 58795579.01 0.00 0.898765E+09 0.00 0.78
October 0.180194E+10 75058238.89 0.00 6323191.08 4071186.13 0.00 0.239613E+10 0.00 0.97
November 0.335918E+10 0.00 0.00 3161302.65 0.00 0.00 0.214448E+10 0.00 0.77
December 0.474580E+10 0.00 0.00 740609.96 0.00 0.00 0.109503E+10 0.00 0.55
                   
Annual Sum or Average 0.257262E+11 0.398309E+10 0.00 53217234.32 0.702984E+09 14396828.84 0.168634E+11 0.00 0.82
Minimum of Months 0.116876E+09 0.00 0.00 427685.82 0.00 0.00 97554348.48 0.00 0.55
Maximum of Months 0.474580E+10 0.195367E+10 0.00 7787487.25 0.398515E+09 13667033.92 0.260737E+10 0.00 1.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.349138E+10 0.00 0.00 1246446.60 0.00 20127185.49 0.155333E+10 0.00 0.79
February 0.266547E+10 0.00 0.00 2526660.63 0.00 1142375.72 0.204403E+10 0.00 0.99
March 0.257613E+10 0.00 0.00 5265548.27 0.00 628514.13 0.321652E+10 0.00 1.34
April 0.179813E+10 36565964.42 0.00 7995214.63 13974278.70 0.00 0.286809E+10 0.00 1.64
May 0.664296E+09 0.161433E+09 0.00 8499537.07 28630496.36 0.00 0.174046E+10 0.00 1.35
June 0.460949E+09 0.571869E+09 0.00 5582078.03 43467085.97 0.00 0.559262E+09 0.00 1.15
July 0.112534E+09 0.150031E+10 0.00 1275012.57 0.389500E+09 0.00 77826090.41 0.00 1.07
August 0.549379E+09 0.524150E+09 0.00 4863134.68 0.137925E+09 0.00 0.606432E+09 0.00 1.33
September 0.537268E+09 0.300118E+09 0.00 6749326.12 49649783.23 0.00 0.108146E+10 0.00 1.26
October 0.176530E+10 53892746.42 0.00 6008363.68 4028759.90 0.00 0.236771E+10 0.00 1.41
November 0.296075E+10 0.00 0.00 3411966.50 0.00 0.00 0.226904E+10 0.00 1.11
December 0.395210E+10 0.00 0.00 858148.10 0.00 8642910.44 0.133246E+10 0.00 0.77
                   
Annual Sum or Average 0.215337E+11 0.314834E+10 0.00 54281436.89 0.667176E+09 30540985.78 0.197166E+11 0.00 1.19
Minimum of Months 0.112534E+09 0.00 0.00 858148.10 0.00 0.00 77826090.41 0.00 0.77
Maximum of Months 0.395210E+10 0.150031E+10 0.00 8499537.07 0.389500E+09 20127185.49 0.321652E+10 0.00 1.64



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.250195E+10 0.00 0.00 9793619.12 0.00 0.00 0.713600E+10 0.00 1.03
February 0.223843E+10 0.00 0.00 9593987.95 0.00 0.00 0.598897E+10 0.00 1.19
March 0.231416E+10 0.00 0.00 11290054.74 0.00 0.00 0.627463E+10 0.00 1.42
April 0.217969E+10 74644832.07 0.00 10502610.49 17607021.89 0.00 0.329426E+10 0.00 1.34
May 0.978639E+09 0.218230E+09 0.00 7826127.63 35014238.02 0.00 0.133301E+10 0.00 0.89
June 0.519615E+09 0.750893E+09 0.00 5585520.54 53162464.74 0.00 0.582422E+09 0.00 0.81
July 0.129623E+09 0.193988E+10 0.00 1567810.29 0.440089E+09 0.00 86450276.43 0.00 0.82
August 0.545048E+09 0.767229E+09 0.00 7695971.88 0.158151E+09 0.00 0.903588E+09 0.00 1.13
September 0.571570E+09 0.468022E+09 0.00 9974308.44 64372532.15 0.00 0.130503E+10 0.00 1.06
October 0.144967E+10 0.135763E+09 0.00 16295582.49 1365857.46 0.00 0.506368E+10 0.00 1.65
November 0.203138E+10 0.00 0.00 15320238.69 0.00 400614.70 0.788006E+10 0.00 1.53
December 0.266159E+10 0.00 0.00 10272514.46 0.00 23435547.85 0.773503E+10 0.00 1.04
                   
Annual Sum or Average 0.181214E+11 0.435466E+10 0.00 0.115718E+09 0.769762E+09 23836162.55 0.475831E+11 0.00 1.16
Minimum of Months 0.129623E+09 0.00 0.00 1567810.29 0.00 0.00 86450276.43 0.00 0.81
Maximum of Months 0.266159E+10 0.193988E+10 0.00 16295582.49 0.440089E+09 23435547.85 0.788006E+10 0.00 1.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.437193E+10 0.00 0.00 2667161.65 0.00 0.00 0.255165E+10 0.00 1.10
February 0.269106E+10 0.00 0.00 4865588.05 0.00 0.00 0.370276E+10 0.00 1.39
March 0.138487E+10 0.00 0.00 11980781.12 0.00 0.00 0.663746E+10 0.00 2.05
April 0.121479E+10 88352772.45 0.00 17442229.18 12587666.14 0.00 0.525391E+10 0.00 2.43
May 0.703698E+09 0.243204E+09 0.00 9206332.28 24195813.79 0.00 0.173406E+10 0.00 1.44
June 0.442462E+09 0.898086E+09 0.00 7343559.44 37480967.25 0.00 0.769001E+09 0.00 1.40
July 0.100628E+09 0.234448E+10 0.00 2608565.95 0.369854E+09 0.00 0.145659E+09 0.00 1.45
August 0.303848E+09 0.102547E+10 0.00 12994880.58 56467741.56 0.00 0.147862E+10 0.00 2.12
September 0.536603E+09 0.345263E+09 0.00 8661880.78 62419008.36 0.00 0.121551E+10 0.00 1.41
October 0.970649E+09 95618189.54 0.00 11498464.50 2579484.53 0.00 0.430678E+10 0.00 1.96
November 0.158066E+10 0.00 0.00 9545978.33 0.00 0.00 0.600669E+10 0.00 1.73
December 0.192436E+10 0.00 0.00 7136734.04 0.00 0.00 0.624762E+10 0.00 1.25
                   
Annual Sum or Average 0.162256E+11 0.504047E+10 0.00 0.105952E+09 0.565585E+09 0.00 0.400497E+11 0.00 1.65
Minimum of Months 0.100628E+09 0.00 0.00 2608565.95 0.00 0.00 0.145659E+09 0.00 1.10
Maximum of Months 0.437193E+10 0.234448E+10 0.00 17442229.18 0.369854E+09 0.00 0.663746E+10 0.00 2.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.406900E+11 0.00 0.00 0.00 0.00 0.842003E+10 0.00 0.00 0.51
February 0.370638E+11 0.00 0.00 1192195.88 0.00 0.445162E+10 0.815159E+09 0.00 0.59
March 0.379564E+11 0.00 0.00 10179813.31 0.00 0.166631E+10 0.535244E+10 0.00 0.70
April 0.178444E+11 0.413069E+09 0.00 40598812.35 0.189805E+09 6377580.50 0.106476E+11 0.00 0.69
May 0.691635E+10 0.209370E+10 0.00 61186497.49 0.218547E+09 0.00 0.993027E+10 0.00 0.71
June 0.219699E+10 0.844894E+10 0.00 53188364.08 0.337910E+09 0.00 0.576857E+10 0.00 0.71
July 0.457359E+09 0.185266E+11 0.00 15160895.03 0.122370E+10 0.00 0.808254E+09 0.00 0.65
August 0.175464E+10 0.593726E+10 0.00 51838024.01 0.573576E+09 0.00 0.652124E+10 0.00 0.71
September 0.605430E+10 0.294429E+10 0.00 43963400.61 0.330798E+09 0.00 0.553569E+10 0.00 0.64
October 0.211463E+11 0.687701E+09 0.00 28564032.64 75054751.56 0.00 0.103376E+11 0.00 0.74
November 0.395796E+11 0.00 0.00 2174447.03 0.00 0.276160E+10 0.220483E+10 0.00 0.64
December 0.380867E+11 0.00 0.00 0.00 0.00 0.118509E+11 0.00 0.00 0.48
                   
Annual Sum or Average 0.249747E+12 0.390515E+11 0.00 0.308046E+09 0.294939E+10 0.291568E+11 0.579216E+11 0.00 0.65
Minimum of Months 0.457359E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.48
Maximum of Months 0.406900E+11 0.185266E+11 0.00 61186497.49 0.122370E+10 0.118509E+11 0.106476E+11 0.00 0.74



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.416150E+11 0.00 0.00 616623.13 0.00 0.512340E+10 0.136564E+10 0.00 0.77
February 0.323015E+11 0.00 0.00 7744972.16 0.00 0.211797E+10 0.749795E+10 0.00 0.91
March 0.266180E+11 0.00 0.00 33433446.35 0.00 0.626926E+09 0.208051E+11 0.00 1.15
April 0.104992E+11 0.486666E+09 0.00 71970065.57 63059705.57 0.00 0.242767E+11 0.00 1.28
May 0.529701E+10 0.194063E+10 0.00 78354219.02 0.205335E+09 0.00 0.159930E+11 0.00 1.28
June 0.239041E+10 0.702955E+10 0.00 56882774.88 0.314699E+09 0.00 0.589514E+10 0.00 1.09
July 0.475006E+09 0.163664E+11 0.00 14509747.60 0.139144E+10 0.00 0.829699E+09 0.00 0.95
August 0.227196E+10 0.578804E+10 0.00 49503716.52 0.585646E+09 0.00 0.619132E+10 0.00 1.11
September 0.459808E+10 0.328964E+10 0.00 58361116.82 0.265557E+09 0.00 0.929204E+10 0.00 1.15
October 0.177350E+11 0.567646E+09 0.00 42415977.53 68204068.80 0.00 0.166030E+11 0.00 1.23
November 0.339392E+11 0.00 0.00 12242444.24 0.00 0.158748E+10 0.900080E+10 0.00 1.00
December 0.414577E+11 0.00 0.00 33579.63 0.00 0.722933E+10 0.205871E+09 0.00 0.72
                   
Annual Sum or Average 0.219198E+12 0.354686E+11 0.00 0.426069E+09 0.289394E+10 0.166851E+11 0.117956E+12 0.00 1.05
Minimum of Months 0.475006E+09 0.00 0.00 33579.63 0.00 0.00 0.205871E+09 0.00 0.72
Maximum of Months 0.416150E+11 0.163664E+11 0.00 78354219.02 0.139144E+10 0.722933E+10 0.242767E+11 0.00 1.28



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.234708E+11 0.00 0.00 85273434.34 0.00 0.218487E+10 0.594271E+11 0.00 0.94
February 0.207885E+11 0.00 0.00 82563057.68 0.00 0.127934E+10 0.474970E+11 0.00 1.05
March 0.233313E+11 0.00 0.00 86211377.32 0.00 0.411170E+09 0.447308E+11 0.00 1.17
April 0.145458E+11 0.891200E+09 0.00 77772749.53 70723873.74 0.00 0.220769E+11 0.00 0.94
May 0.784180E+10 0.243132E+10 0.00 64767454.91 0.240229E+09 0.00 0.107188E+11 0.00 0.77
June 0.281157E+10 0.840498E+10 0.00 48231106.00 0.379309E+09 0.00 0.508417E+10 0.00 0.69
July 0.524070E+09 0.186853E+11 0.00 14395575.53 0.138836E+10 0.00 0.737176E+09 0.00 0.65
August 0.182105E+10 0.734590E+10 0.00 62719437.49 0.615201E+09 0.00 0.753757E+10 0.00 0.83
September 0.425831E+10 0.509684E+10 0.00 86825635.96 0.339833E+09 0.00 0.109810E+11 0.00 0.94
October 0.124213E+11 0.148380E+10 0.00 0.139177E+09 18413764.68 0.00 0.411392E+11 0.00 1.43
November 0.184955E+11 0.00 0.00 0.131372E+09 0.00 0.738188E+09 0.627836E+11 0.00 1.34
December 0.241845E+11 0.00 0.00 78831108.72 0.00 0.321456E+10 0.571573E+11 0.00 0.86
                   
Annual Sum or Average 0.154494E+12 0.443393E+11 0.00 0.958140E+09 0.305206E+10 0.782812E+10 0.369871E+12 0.00 0.97
Minimum of Months 0.524070E+09 0.00 0.00 14395575.53 0.00 0.00 0.737176E+09 0.00 0.65
Maximum of Months 0.241845E+11 0.186853E+11 0.00 0.139177E+09 0.138836E+10 0.321456E+10 0.627836E+11 0.00 1.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.411374E+11 0.00 0.00 6800375.23 0.00 0.493991E+10 0.637237E+10 0.00 0.84
February 0.362987E+11 0.00 0.00 10088043.45 0.00 0.253217E+10 0.681879E+10 0.00 1.00
March 0.342773E+11 0.00 0.00 31414754.12 0.00 0.627233E+09 0.164538E+11 0.00 1.28
April 0.152414E+11 0.665779E+09 0.00 63004072.07 78846378.21 0.00 0.173257E+11 0.00 1.24
May 0.677583E+10 0.243814E+10 0.00 60646328.43 0.129098E+09 0.00 0.103227E+11 0.00 1.12
June 0.215448E+10 0.883123E+10 0.00 46044808.05 0.228682E+09 0.00 0.520076E+10 0.00 1.02
July 0.469968E+09 0.174510E+11 0.00 13156408.32 0.111660E+10 0.00 0.695508E+09 0.00 0.93
August 0.187772E+10 0.619431E+10 0.00 51079046.91 0.438233E+09 0.00 0.601626E+10 0.00 1.08
September 0.538944E+10 0.308967E+10 0.00 54755419.45 0.321977E+09 0.00 0.697553E+10 0.00 1.05
October 0.194097E+11 0.791529E+09 0.00 43534070.92 73623100.82 0.00 0.159202E+11 0.00 1.34
November 0.376512E+11 0.00 0.00 19351631.90 0.00 0.873350E+09 0.111375E+11 0.00 1.14
December 0.412511E+11 0.00 0.00 5062764.38 0.00 0.576871E+10 0.611139E+10 0.00 0.79
                   
Annual Sum or Average 0.241934E+12 0.394617E+11 0.00 0.404938E+09 0.238706E+10 0.147414E+11 0.109350E+12 0.00 1.07
Minimum of Months 0.469968E+09 0.00 0.00 5062764.38 0.00 0.00 0.695508E+09 0.00 0.79
Maximum of Months 0.412511E+11 0.174510E+11 0.00 63004072.07 0.111660E+10 0.576871E+10 0.173257E+11 0.00 1.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.278609E+10 0.00 0.00 0.00 0.00 0.221860E+10 0.00 0.00 0.55
February 0.306111E+10 0.00 0.00 35.18 0.00 0.132147E+10 3098954.28 0.00 0.64
March 0.373656E+10 0.00 0.00 498924.05 0.00 0.690693E+09 0.298235E+09 0.00 0.76
April 0.193775E+10 23446588.75 0.00 3821992.96 16034322.14 64282972.34 0.852440E+09 0.00 0.75
May 0.767707E+09 0.132493E+09 0.00 6615514.04 23269542.35 0.00 0.833513E+09 0.00 0.73
June 0.276526E+09 0.668919E+09 0.00 6279332.63 36476270.37 0.00 0.528517E+09 0.00 0.72
July 54857454.38 0.169312E+10 0.00 1723830.62 0.180435E+09 0.00 70246855.74 0.00 0.66
August 0.284511E+09 0.487720E+09 0.00 5769689.94 65363701.29 0.00 0.562934E+09 0.00 0.72
September 0.682872E+09 0.218740E+09 0.00 5173921.32 47294010.18 0.00 0.421535E+09 0.00 0.66
October 0.244052E+10 47284626.74 0.00 2168431.53 12430443.93 21047182.17 0.633378E+09 0.00 0.79
November 0.339793E+10 0.00 0.00 79605.72 0.00 0.980294E+09 0.102218E+09 0.00 0.69
December 0.235854E+10 0.00 0.00 0.00 0.00 0.269013E+10 0.00 0.00 0.52
                   
Annual Sum or Average 0.217850E+11 0.327173E+10 0.00 32131278.00 0.381303E+09 0.798651E+10 0.430611E+10 0.00 0.68
Minimum of Months 54857454.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.52
Maximum of Months 0.373656E+10 0.169312E+10 0.00 6615514.04 0.180435E+09 0.269013E+10 0.852440E+09 0.00 0.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.329113E+10 0.00 0.00 0.00 0.00 0.109422E+10 0.00 0.00 0.74
February 0.303267E+10 0.00 0.00 337183.66 0.00 0.511664E+09 0.304033E+09 0.00 0.87
March 0.232637E+10 0.00 0.00 2518933.60 0.00 0.354816E+09 0.163726E+10 0.00 1.09
April 0.885490E+09 30622047.19 0.00 7199511.77 4350491.40 21647667.62 0.217180E+10 0.00 1.27
May 0.428090E+09 0.128145E+09 0.00 8636732.33 18881384.15 0.00 0.148853E+10 0.00 1.29
June 0.239245E+09 0.565405E+09 0.00 6780239.07 30752339.03 0.00 0.571816E+09 0.00 1.09
July 46462655.62 0.154201E+10 0.00 1741852.10 0.158445E+09 0.00 74377493.56 0.00 0.96
August 0.221698E+09 0.485251E+09 0.00 6043148.74 61100890.42 0.00 0.607727E+09 0.00 1.11
September 0.389799E+09 0.270890E+09 0.00 6940423.13 30300455.11 0.00 0.814748E+09 0.00 1.14
October 0.152396E+10 39368794.60 0.00 4088539.42 10391636.33 11694469.77 0.146353E+10 0.00 1.19
November 0.294762E+10 0.00 0.00 785386.43 0.00 0.498769E+09 0.516560E+09 0.00 0.95
December 0.301196E+10 0.00 0.00 0.00 0.00 0.140017E+10 0.00 0.00 0.71
                   
Annual Sum or Average 0.183445E+11 0.306169E+10 0.00 45071950.26 0.314222E+09 0.389299E+10 0.965039E+10 0.00 1.04
Minimum of Months 46462655.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.71
Maximum of Months 0.329113E+10 0.154201E+10 0.00 8636732.33 0.158445E+09 0.140017E+10 0.217180E+10 0.00 1.29



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.227957E+10 0.00 0.00 5643875.53 0.00 0.775952E+09 0.412497E+10 0.00 0.82
February 0.206195E+10 0.00 0.00 5561601.61 0.00 0.476065E+09 0.353469E+10 0.00 0.94
March 0.243144E+10 0.00 0.00 6640832.53 0.00 0.364523E+09 0.368093E+10 0.00 1.12
April 0.154324E+10 52072305.37 0.00 7832764.69 5341765.27 47066311.66 0.194582E+10 0.00 0.98
May 0.835294E+09 0.152545E+09 0.00 7233478.14 24324559.00 0.00 0.935243E+09 0.00 0.80
June 0.344504E+09 0.661701E+09 0.00 5729562.74 39403876.95 0.00 0.477189E+09 0.00 0.71
July 71794376.48 0.168181E+10 0.00 1685037.14 0.228477E+09 0.00 58349120.75 0.00 0.67
August 0.274143E+09 0.588754E+09 0.00 7229532.55 69373658.31 0.00 0.693290E+09 0.00 0.84
September 0.491642E+09 0.370276E+09 0.00 10563599.37 39632342.60 0.00 0.963288E+09 0.00 0.95
October 0.130641E+10 98513001.71 0.00 13113528.70 7300813.47 0.00 0.378242E+10 0.00 1.44
November 0.197772E+10 0.00 0.00 9431025.36 0.00 0.428558E+09 0.499409E+10 0.00 1.26
December 0.235454E+10 0.00 0.00 4893673.44 0.00 0.849414E+09 0.368992E+10 0.00 0.73
                   
Annual Sum or Average 0.159722E+11 0.360567E+10 0.00 85558511.82 0.413854E+09 0.294158E+10 0.288802E+11 0.00 0.94
Minimum of Months 71794376.48 0.00 0.00 1685037.14 0.00 0.00 58349120.75 0.00 0.67
Maximum of Months 0.243144E+10 0.168181E+10 0.00 13113528.70 0.228477E+09 0.849414E+09 0.499409E+10 0.00 1.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.342253E+10 0.00 0.00 318249.82 0.00 0.118669E+10 0.438684E+09 0.00 0.86
February 0.326410E+10 0.00 0.00 615549.24 0.00 0.654262E+09 0.530337E+09 0.00 1.01
March 0.344186E+10 0.00 0.00 2567880.63 0.00 0.287665E+09 0.133615E+10 0.00 1.31
April 0.160874E+10 37112638.59 0.00 6298301.91 6858964.47 22808840.48 0.153162E+10 0.00 1.31
May 0.759319E+09 0.150747E+09 0.00 6885706.11 13056306.15 0.00 0.863442E+09 0.00 1.15
June 0.258338E+09 0.670522E+09 0.00 5585273.56 25388156.32 0.00 0.494645E+09 0.00 1.03
July 60954012.33 0.154453E+10 0.00 1624291.08 0.186177E+09 0.00 58024255.36 0.00 0.94
August 0.257081E+09 0.493352E+09 0.00 5881180.17 51491804.65 0.00 0.557324E+09 0.00 1.10
September 0.567681E+09 0.225434E+09 0.00 6622819.56 41438494.24 0.00 0.593209E+09 0.00 1.08
October 0.210938E+10 53893783.40 0.00 4071280.78 11766677.10 0.00 0.124792E+10 0.00 1.37
November 0.328953E+10 0.00 0.00 1559159.45 0.00 0.502727E+09 0.897544E+09 0.00 1.14
December 0.341163E+10 0.00 0.00 145996.30 0.00 0.139763E+10 0.263704E+09 0.00 0.81
                   
Annual Sum or Average 0.224511E+11 0.317559E+10 0.00 42175688.61 0.336177E+09 0.405178E+10 0.881260E+10 0.00 1.09
Minimum of Months 60954012.33 0.00 0.00 145996.30 0.00 0.00 58024255.36 0.00 0.81
Maximum of Months 0.344186E+10 0.154453E+10 0.00 6885706.11 0.186177E+09 0.139763E+10 0.153162E+10 0.00 1.37



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 3424585.92 0.00 0.00 0.447424E+09 0.00 0.28
February 0.00 0.00 0.00 7335062.47 0.00 0.00 0.359928E+09 0.00 0.29
March 0.00 0.00 0.00 13606138.71 0.00 0.00 0.372649E+09 0.00 0.31
April 0.00 724385.87 0.00 16045157.74 0.00 0.00 0.187770E+09 0.00 0.29
May 0.00 29771154.21 0.00 2778037.40 0.00 0.00 96253792.87 0.00 0.29
June 0.00 87683779.63 0.00 1213653.32 0.00 0.00 12099972.35 0.00 0.30
July 0.00 0.286294E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.179272E+09 0.00 501583.56 0.00 0.00 1031573.63 0.00 0.31
September 0.00 0.117000E+09 0.00 1091019.20 0.00 0.00 26427084.88 0.00 0.29
October 0.00 39055718.19 0.00 6016376.26 0.00 0.00 0.140947E+09 0.00 0.28
November 0.00 0.00 0.00 12183617.41 0.00 0.00 0.323206E+09 0.00 0.28
December 0.00 0.00 0.00 16778166.17 0.00 0.00 0.457368E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.739801E+09 0.00 80973398.15 0.00 0.00 0.242511E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.286294E+09 0.00 16778166.17 0.00 0.00 0.457368E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 24146535.35 0.00 0.00 0.448914E+10 0.00 0.28
February 0.00 0.00 0.00 63072006.45 0.00 0.00 0.361012E+10 0.00 0.29
March 0.00 0.00 0.00 0.124192E+09 0.00 0.00 0.373690E+10 0.00 0.31
April 0.00 7949961.49 0.00 0.150092E+09 0.00 0.00 0.188200E+10 0.00 0.29
May 0.00 0.293593E+09 0.00 25594131.29 0.00 0.00 0.963395E+09 0.00 0.29
June 0.00 0.873618E+09 0.00 11498315.38 0.00 0.00 0.120683E+09 0.00 0.30
July 0.00 0.285729E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.181881E+10 0.00 4234344.72 0.00 0.00 10024810.10 0.00 0.30
September 0.00 0.115119E+10 0.00 9894749.54 0.00 0.00 0.267151E+09 0.00 0.29
October 0.00 0.386182E+09 0.00 54641709.18 0.00 0.00 0.141742E+10 0.00 0.28
November 0.00 0.00 0.00 0.109530E+09 0.00 0.00 0.324438E+10 0.00 0.28
December 0.00 0.00 0.00 0.150347E+09 0.00 0.00 0.458824E+10 0.00 0.28
                   
Annual Sum or Average 0.00 0.738863E+10 0.00 0.727242E+09 0.00 0.00 0.243295E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.285729E+10 0.00 0.150347E+09 0.00 0.00 0.458824E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 73227252.80 0.00 0.00 1487101.88 0.00 0.00 0.377358E+09 0.00 0.28
February 0.00 0.00 0.00 5552582.34 0.00 0.00 0.362047E+09 0.00 0.29
March 0.00 0.00 0.00 11813324.22 0.00 0.00 0.374369E+09 0.00 0.31
April 0.00 819164.88 0.00 14812865.56 0.00 0.00 0.188133E+09 0.00 0.29
May 0.00 29416554.59 0.00 2538963.87 0.00 0.00 96405976.06 0.00 0.29
June 0.00 87430601.36 0.00 1145067.86 0.00 0.00 12094758.04 0.00 0.30
July 0.00 0.285799E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.182299E+09 0.00 416013.48 0.00 0.00 999517.28 0.00 0.30
September 0.00 0.115278E+09 0.00 957830.79 0.00 0.00 26835255.71 0.00 0.29
October 0.00 38536813.60 0.00 5205081.32 0.00 0.00 0.142456E+09 0.00 0.28
November 0.00 0.00 0.00 10238276.65 0.00 0.00 0.325332E+09 0.00 0.28
December 0.00 0.00 0.00 13971990.59 0.00 0.00 0.459980E+09 0.00 0.28
                   
Annual Sum or Average 73227252.80 0.739579E+09 0.00 68139098.56 0.00 0.00 0.236601E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 73227252.80 0.285799E+09 0.00 14812865.56 0.00 0.00 0.459980E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.212855E+09 0.00 0.00 0.126355E+11 0.00 0.32
February 0.00 0.00 0.00 0.387259E+09 0.00 0.00 0.107459E+11 0.00 0.32
March 0.00 0.00 0.00 0.683173E+09 0.00 0.00 0.113280E+11 0.00 0.34
April 0.00 0.00 0.00 0.853996E+09 0.00 0.00 0.740695E+10 0.00 0.33
May 0.00 0.551710E+09 0.00 0.155235E+09 0.00 0.00 0.319163E+10 0.00 0.33
June 0.00 0.141024E+10 0.00 0.119699E+09 0.00 0.00 0.597672E+09 0.00 0.34
July 0.00 0.612669E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
August 0.00 0.779003E+09 0.00 0.439138E+09 0.00 0.00 0.709195E+09 0.00 0.35
September 0.00 0.257957E+10 0.00 62480354.06 0.00 0.00 0.809040E+09 0.00 0.32
October 0.00 0.749571E+09 0.00 0.311988E+09 0.00 0.00 0.391307E+10 0.00 0.32
November 0.00 0.00 0.00 0.615693E+09 0.00 0.00 0.909749E+10 0.00 0.32
December 0.00 0.00 0.00 0.848461E+09 0.00 0.00 0.127536E+11 0.00 0.31
                   
Annual Sum or Average 0.00 0.121968E+11 0.00 0.468998E+10 0.00 0.00 0.731881E+11 0.00 0.33
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.00 0.612669E+10 0.00 0.853996E+09 0.00 0.00 0.127536E+11 0.00 0.35



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:03:13

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.396122E+12 0.155010E+11 0.00 0.204056E+13 0.637764E+12
February 0.408356E+12 0.127458E+11 0.00 0.173331E+13 0.107645E+13
March 0.589867E+12 0.140569E+11 0.00 0.200734E+13 0.179109E+13
April 0.614055E+12 0.761197E+10 0.00 0.137933E+13 0.267775E+13
May 0.645800E+12 0.418197E+10 0.00 0.940924E+12 0.209205E+13
June 0.632772E+12 -608493352.1 0.00 0.232280E+12 0.307549E+13
July 0.626678E+12 -0.292185E+10 0.00 -0.366757E+12 0.369588E+13
August 0.587257E+12 -364045600.4 0.00 0.160325E+12 0.388586E+13
September 0.533749E+12 0.160659E+10 0.00 0.511917E+12 0.218411E+13
October 0.493837E+12 0.669143E+10 0.00 0.160689E+13 0.188555E+13
November 0.399445E+12 0.129110E+11 0.00 0.206379E+13 0.167019E+13
December 0.339817E+12 0.133938E+11 0.00 0.200512E+13 0.191544E+13
           
Annual Sum or Average 0.626776E+13 0.848060E+11 0.00 0.143150E+14 0.265876E+14
Minimum of Months 0.339817E+12 -0.292185E+10 0.00 -0.366757E+12 0.637764E+12
Maximum of Months 0.645800E+12 0.155010E+11 0.00 0.206379E+13 0.388586E+13