Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 09:03:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 34930.34 | 754.10 | 754.10 |
Net Site Energy | 34930.34 | 754.10 | 754.10 |
Total Source Energy | 109412.95 | 2362.09 | 2362.09 |
Net Source Energy | 109412.95 | 2362.09 | 2362.09 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 22.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6662.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3705.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 670.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1941.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2768.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1329.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1974.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19163.14 |
Humidification | 82.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 559.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 34348.76 | 581.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21473.87 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 22.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 6662.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3705.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 670.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2768.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1329.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1974.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19163.14 |
Humidification | General | 82.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 559.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 22.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 6662.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3705.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 670.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1941.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2768.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1329.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1974.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19163.14 |
Humidification | Unassigned | 82.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 559.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 276.71 | 12.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Other | 370.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 741.55 | 12.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 276.71 | 12.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Other | 370.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 741.55 | 12.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 34348.759 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 34348.759 | 100.00 |
Total On-Site and Utility Electric Sources | 34348.759 | 100.00 |
Total Electricity End Uses | 34348.759 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 21473.87 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 21473.87 | 100.00 |
Total Water End Uses | 21473.87 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1069.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.3279 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.3279 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.3279 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.3279 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 9.3279 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.3279 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 9.3279 | 18.58 | 484.4232 | |
Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.8860 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-15:20 | 02-JAN-06:19 | - | - | - | - | - | - | - | - | - | - | 19-APR-15:09 |
Heating | 0.00 | 207455.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 573986.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84885.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 226054.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 69995.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 93058.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 21664.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2158800.56 | 229119.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 207455.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 573986.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5451.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 226054.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 69995.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 93058.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 21664.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 23.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 21101.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11734.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2124.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6150.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8767.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4210.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6252.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 260.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 606.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 108782.52 | 630.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 455.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 253.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 189.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 90.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 134.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2348.48 | 13.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 455.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 253.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 189.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 90.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 134.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2348.48 | 13.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.00 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.490269 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.67 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.469775 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.97 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.30 | 0.301693 | 0.312000 | 1.97 | 0.804514 | 0.500000 | 0.001263 | 0.000169 | 1.97 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 59.79 | 0.318117 | 0.324000 | 19.37 | 0.848313 | 0.500000 | 0.001198 | 0.003101 | 19.37 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.13 | 0.310288 | 0.327000 | 2.00 | 0.827433 | 0.500000 | 0.001228 | 0.000549 | 2.00 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.22 | 0.196091 | 0.300000 | 0.365373 | 0.522908 | 0.500000 | 0.001943 | 0.000046 | 0.365373 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.949727 | 0.162052 | 0.300000 | 0.284918 | 0.432138 | 0.500000 | 0.002351 | 0.000037 | 0.284918 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.24 | 0.192743 | 0.300000 | 0.371726 | 0.513982 | 0.500000 | 0.001977 | 0.000063 | 0.371726 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.24 | 0.124468 | 0.300000 | 0.370950 | 0.331916 | 0.500000 | 0.003061 | 0.000033 | 0.370950 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 11.81 | 0.202280 | 0.300000 | 3.54 | 0.539413 | 0.500000 | 0.001884 | 0.001070 | 3.74 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 9.80 | 0.157011 | 0.300000 | 2.94 | 0.418696 | 0.500000 | 0.002427 | 0.000752 | 2.94 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 11.91 | 0.200493 | 0.300000 | 3.57 | 0.534649 | 0.500000 | 0.001900 | 0.001070 | 3.74 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.48 | 0.146873 | 0.300000 | 3.14 | 0.391663 | 0.500000 | 0.002594 | 0.000702 | 3.14 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.38 | 0.172948 | 0.300000 | 0.414263 | 0.461196 | 0.500000 | 0.002203 | 0.000155 | 0.540259 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.05 | 0.146938 | 0.300000 | 0.314225 | 0.391835 | 0.500000 | 0.002593 | 0.000102 | 0.355715 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.38 | 0.172587 | 0.300000 | 0.415140 | 0.460232 | 0.500000 | 0.002208 | 0.000155 | 0.540265 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.18 | 0.130420 | 0.300000 | 0.354021 | 0.347788 | 0.500000 | 0.002921 | 0.000096 | 0.354021 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19305.91 | 0.000169 | 389.19 |
CORE_MID VAV BOX REHEAT COIL | 354464.71 | 0.003101 | 7814.76 |
CORE_TOP VAV BOX REHEAT COIL | 62750.60 | 0.000549 | 1623.88 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5254.70 | 0.000046 | 111.03 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4232.59 | 0.000037 | 89.87 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7182.26 | 0.000063 | 160.18 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3784.43 | 0.000033 | 76.59 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 122321.44 | 0.001070 | 3228.47 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 85910.31 | 0.000752 | 2161.68 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 122322.11 | 0.001070 | 3228.48 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 80227.15 | 0.000702 | 1925.62 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17668.25 | 0.000155 | 466.11 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11632.41 | 0.000102 | 306.87 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17668.43 | 0.000155 | 466.11 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11025.84 | 0.000096 | 284.71 |
VAV_BOT WITH REHEAT HEATING COIL | 23748.16 | 0.000208 | 415.27 |
VAV_MID WITH REHEAT HEATING COIL | 157846.57 | 0.001381 | 2799.19 |
VAV_TOP WITH REHEAT HEATING COIL | 12003.85 | 0.000105 | 215.28 |
CAV_BAS HEATING COIL | 274173.69 | 0.002399 | 6235.34 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.47 | 3.36 | 10.95 | 3.36 | 10.32 | 10.32 | 0.300000 | 0.325609 | 10.32 |
VAV_MID WITH REHEAT | 51.89 | 32.57 | 103.79 | 32.57 | 97.66 | 97.66 | 0.300000 | 0.333517 | 97.66 |
VAV_TOP WITH REHEAT | 5.56 | 3.50 | 11.12 | 3.64 | 11.03 | 11.03 | 0.300000 | 0.329863 | 11.03 |
CAV_BAS | 6.00 | 6.00 | 6.00 | 6.00 | 6.00 | 6.00 | 1.00 | 1.00 | 6.00 |
AIRLOOP DATACENTER BASEMENT | 21.97 | 21.97 | 21.97 | 21.97 | 21.97 | 21.97 | 1.00 | 0.999988 | 21.97 |
AIRLOOP DATACENTER BOT | 0.490269 | 0.490269 | 0.490269 | 0.490269 | 0.490269 | 0.490269 | 1.00 | 1.00 | 0.490269 |
AIRLOOP DATACENTER MID | 4.67 | 4.67 | 4.67 | 4.67 | 4.67 | 4.67 | 1.00 | 1.00 | 4.67 |
AIRLOOP DATACENTER TOP | 0.469775 | 0.469775 | 0.469775 | 0.469775 | 0.469775 | 0.469775 | 1.00 | 1.00 | 0.469775 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.32 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 97.66 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.03 | |
CAV_BAS_OA_CONTROLLER | 6.00 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.97 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.490269 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.67 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.469775 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 28.58 | 6.67 | 11.00 | 0.007797 | 0.007000 | 241356.59 | 0.010268 | 10.32 |
VAV_MID WITH REHEAT COOLING COIL | 29.01 | 6.67 | 10.99 | 0.007874 | 0.007000 | 2357913.58 | 0.100311 | 97.66 |
VAV_TOP WITH REHEAT COOLING COIL | 28.15 | 6.67 | 11.00 | 0.007744 | 0.007000 | 250531.59 | 0.010658 | 11.03 |
CAV_BAS COOLING COIL | 27.43 | 6.67 | 11.38 | 0.007827 | 0.007000 | 129929.42 | 0.005527 | 6.00 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.32 |
VAV_MID WITH REHEAT FAN | 97.66 |
VAV_TOP WITH REHEAT FAN | 11.03 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010268 | 0.000046 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000208 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.100311 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.001381 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.010658 | 0.000045 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000105 | |
CAV_BAS_COOLC_CONTROLLER | 0.005527 | 0.000086 |
CAV_BAS_HEATC_CONTROLLER | 0.002399 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.00 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.97 | 452498.18 | 281793.92 | 0.011082 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.490269 | 9816.00 | 6187.94 | 0.000240 |
AIRLOOP DATACENTER MID COOLING COIL | 4.67 | 93579.44 | 58964.62 | 0.002292 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.469775 | 9667.57 | 6011.05 | 0.000237 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.97 | 21.97 | 21.97 | 21.97 | 452498.18 | 452498.18 | 13450.69 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.490269 | 0.490269 | 0.490269 | 0.490269 | 9816.00 | 9816.00 | 621.37 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.67 | 4.67 | 4.67 | 4.67 | 93579.44 | 93579.44 | 6213.66 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.469775 | 0.469775 | 0.469775 | 0.469775 | 9667.57 | 9667.57 | 621.37 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.97 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.490269 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.67 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.469775 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.97 | 452498.18 | 0.011082 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.490269 | 9816.00 | 0.000240 |
AIRLOOP DATACENTER MID HEATING COIL | 4.67 | 93579.44 | 0.002292 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.469775 | 9667.57 | 0.000237 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 13450.69 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 621.37 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6213.66 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 621.37 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000048 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.126765 | 26121.50 | |
HEATSYS1 PUMP | 0.012191 | 3671.44 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.126765 | 15.21 |
HEATSYS1 | 0.012191 | 1.46 |
COOLSYS1_SUPPLY | 0.126765 | 15.21 |
SINGLE WATER PLANT LOOP | 0.013851 | 1.66 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.126765 | 0.126765 | 532094.85 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1393523.42 | 1393523.42 | 0.012191 |
CENTRAL BOILER | 570524.21 | 559477.15 | 0.013851 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.126765 | 18084.79 |
PLANT CIRC PUMP | 0.013851 | 3532.58 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.126765 | 0.064005 | 1508197.93 | 1515297.13 | 0.074986 |
COOLSYS1 CHILLER2 | 0.126765 | 0.064005 | 1508197.93 | 1515297.13 | 0.074986 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013851 | 139666.47 | 57235.65 | 69833.23 | 7879.72 | 21206.82 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.149973 | 18.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.149973 | 45168.57 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 59.14 | 1797868.51 | 11.83 | 224733.56 |
TOWERWATERSYS COOLTOWER 2 | 59.14 | 1797868.51 | 11.83 | 224733.56 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.077887 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.328 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 14.170 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 9.328 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.751 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 25926.330 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25926.330 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 7310.116 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7310.116 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.743 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.656 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 2.135 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4064 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4365 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3009 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | 0.76055735E-15 | 0.55973061E-16 | -0.11090261E-09 | -0.43371185E-17 |
51 | 8 | 0.16390423E-07 | 0.22068143E-12 | 0.31740643E-03 | -0.18636477E-09 |
52 | 7 | -0.10429999E-01 | 0.12271718E-07 | -0.20474149E-01 | 0.11859286E-03 |
53 | 6 | 0.35611320 | 0.43955117E-05 | 0.42991281 | -0.41673803E-02 |
54 | 5 | -4.7098961 | 0.16827687E-03 | -4.1162358 | 0.57223947E-01 |
55 | 4 | 30.875684 | 0.14076848E-02 | 20.167480 | -0.39388153 |
56 | 3 | -106.69740 | 0.31291265E-02 | -53.106522 | 1.4497707 |
57 | 2 | 192.63914 | 0.17911574E-02 | 75.570394 | -2.8293896 |
58 | 1 | -169.50392 | 0.19431750E-03 | -54.592911 | 2.7164834 |
59 | 0 | 57.057407 | 0.11257899E-05 | 15.674734 | |
60 | 9 | 0.11474244E-14 | 0.54197419E-16 | -0.11508650E-09 | -0.49945851E-17 |
61 | 8 | 0.16984416E-07 | 0.21156325E-12 | 0.32425024E-03 | -0.19311866E-09 |
62 | 7 | -0.10636353E-01 | 0.11664670E-07 | -0.20772028E-01 | 0.12093918E-03 |
63 | 6 | 0.36172330 | 0.41637772E-05 | 0.43474562 | -0.42335086E-02 |
64 | 5 | -4.7646824 | 0.15893927E-03 | -4.1535939 | 0.57903236E-01 |
65 | 4 | 31.118254 | 0.13261305E-02 | 20.314042 | -0.39710182 |
66 | 3 | -107.21418 | 0.29411649E-02 | -53.396504 | 1.4572354 |
67 | 2 | 193.15212 | 0.16802168E-02 | 75.835339 | -2.8375342 |
68 | 1 | -169.69371 | 0.18194848E-03 | -54.668081 | 2.7198097 |
69 | 0 | 57.057407 | 0.10520719E-05 | 15.660794 | |
70 | 9 | 0.66246833E-15 | 0.57738042E-16 | -0.92036509E-10 | -0.27018983E-17 |
71 | 8 | 0.13701644E-07 | 0.25726543E-12 | 0.28527343E-03 | -0.15579243E-09 |
72 | 7 | -0.94571194E-02 | 0.14940887E-07 | -0.19068097E-01 | 0.10753086E-03 |
73 | 6 | 0.32965778 | 0.54453531E-05 | 0.40701455 | -0.38555430E-02 |
74 | 5 | -4.4514676 | 0.21157254E-03 | -3.9387765 | 0.54019785E-01 |
75 | 4 | 29.731016 | 0.17930056E-02 | 19.470280 | -0.37868589 |
76 | 3 | -104.25747 | 0.40308508E-02 | -51.726693 | 1.4145289 |
77 | 2 | 190.21562 | 0.23301583E-02 | 74.311741 | -2.7909129 |
78 | 1 | -168.60668 | 0.25508611E-03 | -54.239505 | 2.7007581 |
79 | 0 | 57.057407 | 0.14924561E-05 | 15.743350 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6556E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6567E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8034E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8043E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1458E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1465E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2452E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6818E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7553E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8248E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8865E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1628E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2127E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2574E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2891E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3694E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0906E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1712E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2798E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.0286E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2382E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6042E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.1095E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6871E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7813E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8306E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9145E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1681E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2329E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2577E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2900E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6555E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6568E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8033E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8044E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1458E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1467E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2451E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7734E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9022E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6487E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7820E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5073E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5748E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1302E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1521E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2792E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5967E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1179E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4553E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3343E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.3602E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6787E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.9865E-003 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7433E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7949E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6113E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6492E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.4871E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5031E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1303E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1525E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2193E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2205E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0482E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0492E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.2927E-004 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.2997E-004 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2452E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2462E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3126E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0702E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1232E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.4683E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.8505E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2577E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2900E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8970E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0736E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4831E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.2182E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4618E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.7927E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6042E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.1067E-003 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2442E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3101E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0678E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1184E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.4273E-004 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.7257E-004 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2574E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2891E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2192E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2203E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0481E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0490E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.2918E-004 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.2973E-004 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2451E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3719E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4257E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1617E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2007E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1392E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1537E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1303E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1525E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.5554E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3237E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.2515E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1301E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6176E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0860E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6787E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.9865E-003 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3958E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4967E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1920E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2913E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1581E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2174E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1302E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1521E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.2526E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.2005E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.8513E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4500E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.3253E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.1602E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.0133E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4574E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7645E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2088E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.5896E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0428E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7878E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9148E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.0820E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4729E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2887E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5929E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8364E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2718E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8071E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 9.9091E-003 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0133E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4571E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9784E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8510E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.6470E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6146E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0155E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5644E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0820E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4729E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.2523E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.2071E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.8524E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.4578E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.3293E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.1668E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.0168E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4602E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7636E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2110E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.5896E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0450E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7898E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9182E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.0854E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4757E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2861E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5936E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8346E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2724E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8081E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 9.9234E-003 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0168E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4599E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9768E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8524E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.6462E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6160E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0169E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5670E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0854E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4757E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 80997.47746 | 80997.47746 | 6.00031 | 6.00031 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 6.30000 | 6.07234E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 85109.98323 | 85109.98323 | 6.30457 | 6.30457 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 807330.69511 | 807330.69511 | 59.79062 | 59.79062 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 164331.48709 | 164331.48709 | 7.04256 | 10.77825 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 82761.94199 | 82761.94199 | 6.12994 | 6.12994 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 43076.99797 | 43076.99797 | 1.87236 | 1.87236 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 16295.18124 | 16295.18124 | 1.21791 | 1.21791 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 41.80600 | 9.15758E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 1670.32548 | 1670.32548 | 7.25146E-002 | 0.13533 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12707.01997 | 12707.01997 | 0.94973 | 0.94973 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:10:00 | 38.55650 | 9.15215E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 1437.36817 | 1437.36817 | 6.21895E-002 | 8.72129E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 16578.53304 | 16578.53304 | 1.23909 | 1.23909 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 3534.94656 | 3534.94656 | 0.15294 | 0.15294 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 16544.01509 | 16544.01509 | 1.23650 | 1.23650 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 149.21061 | 149.21061 | 6.54944E-003 | 8.72129E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 157963.51643 | 157963.51643 | 11.80645 | 11.80645 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.70900 | 9.15741E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 85655.61543 | 85655.61543 | 3.73659 | 3.73659 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 131147.79722 | 131147.79722 | 9.80218 | 9.80218 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 38.79900 | 9.15255E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 57054.55283 | 57054.55283 | 2.48932 | 2.48932 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 159374.32940 | 159374.32940 | 11.91190 | 11.91190 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 85656.08753 | 85656.08753 | 3.73661 | 3.73661 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 140200.19665 | 140200.19665 | 10.47875 | 10.47875 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 49381.77448 | 49381.77448 | 2.15288 | 2.15288 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 18475.28620 | 18475.28620 | 1.38088 | 1.38088 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 41.61200 | 9.15725E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 12366.35462 | 12366.35462 | 0.54026 | 0.54026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14013.77129 | 14013.77129 | 1.04742 | 1.04742 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:40:00 | 39.28400 | 9.15337E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 8141.55349 | 8141.55349 | 0.35572 | 0.35572 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 18514.36401 | 18514.36401 | 1.38380 | 1.38380 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 12366.47583 | 12366.47583 | 0.54026 | 0.54026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 15788.63614 | 15788.63614 | 1.18007 | 1.18007 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 7551.69961 | 7551.69961 | 0.32985 | 0.32985 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8317.57586 | 8317.57586 | 0.49027 | 0.49027 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.14193E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 79223.02557 | 79223.02557 | 4.66970 | 4.66970 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.14193E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7969.88615 | 7969.88615 | 0.46978 | 0.46978 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.14193E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372677.23982 | 372677.23982 | 21.96910 | 21.96910 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:00:00 | 33.17300 | 9.14325E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 6.30000 | 6.07234E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 185614.19 | 10.31912 | 10.31912 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 11810.70 | 1.54052 | 1.54052 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1743599.86 | 97.66206 | 97.66206 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 175518.16 | 22.89365 | 22.89365 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 199321.47 | 11.03019 | 11.03019 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 19399.83 | 3.63846 | 3.63846 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
7 | CAV_BAS | Cooling | Sensible | 95111.21 | 6.00031 | 6.00031 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 47704.73 | 1.20016 | 1.20016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 373427.12 | 21.96936 | 21.96936 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 13450.69 | 0.33839 | 0.33839 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8310.31 | 0.49027 | 0.49027 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 621.37 | 1.56323E-002 | 1.56323E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 79200.80 | 4.66970 | 4.66970 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6213.66 | 0.15632 | 0.15632 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8121.28 | 0.46978 | 0.46978 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 621.37 | 1.56323E-002 | 1.56323E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.00031 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.30457 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30169 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31200 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.96703 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80451 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26287E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.68897E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.96703 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19305.91256 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.68897E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 389.19204 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 59.79062 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31812 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32400 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.37216 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84831 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19767E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.10101E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.37216 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 354464.71433 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.10101E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7814.75718 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.12994 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31029 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32700 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.00449 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82743 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22789E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.48970E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.00449 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 62750.59959 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.48970E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1623.88468 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.21791 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19609 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36537 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52291 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.94298E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.59704E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36537 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5254.69755 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.59704E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 111.02922 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94973 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16205 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28492 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43214 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35110E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.70286E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28492 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4232.59349 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.70286E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 89.87477 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23909 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19274 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37173 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51398 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97672E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.28335E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37173 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7182.25802 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.28335E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 160.17985 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23650 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12447 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37095 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33192 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.06102E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.31079E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37095 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3784.43454 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.31079E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 76.58780 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.80645 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20228 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.54194 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53941 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.88353E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07012E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.73659 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 122321.44301 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07012E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3228.46535 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.80218 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15701 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.94065 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41870 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42658E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.51581E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.94065 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 85910.30719 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.51581E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2161.68315 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.91190 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20049 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.57357 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53465 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.90031E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07013E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.73661 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 122322.11399 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07013E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3228.48315 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.47875 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14687 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.14363 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39166 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.59407E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.01862E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.14363 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 80227.14680 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.01862E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1925.62373 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38088 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17295 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41426 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46120 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20297E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54570E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54026 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17668.25253 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54570E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 466.10897 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04742 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14694 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31422 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39183 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.59293E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.01765E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35572 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11632.41214 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01765E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 306.86877 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38380 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17259 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41514 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46023 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20758E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54571E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54026 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17668.42545 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54571E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 466.11354 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18007 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13042 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.35402 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34779 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.92132E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.64588E-005 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35402 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11025.83731 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.64588E-005 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 284.70665 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49027 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.66970 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46978 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.96910 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.47390 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.35999 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.94780 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.35999 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.31912 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.31912 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32561 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 51.89495 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 32.57195 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 103.78990 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 32.57195 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 97.66206 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 97.66206 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33352 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.56105 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.50214 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.12210 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.63846 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.03019 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.03019 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32986 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.00031 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.00031 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.00031 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.00031 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.00031 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.00031 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.96910 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.96910 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.96910 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.96910 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.96936 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.96936 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49027 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49027 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49027 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49027 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49027 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.49027 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.66970 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.66970 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.66970 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.66970 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.66970 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.66970 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46978 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46978 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46978 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46978 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46978 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.46978 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.31912 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 97.66206 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.03019 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.00031 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.96936 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.49027 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.66970 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.46978 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.31912 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.58048 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00351 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.79700E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 241356.59277 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.02679E-002 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.31912 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 23748.15990 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07759E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 415.27267 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.31912 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.02679E-002 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.63768E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.07759E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 97.66206 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.00842 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.99417 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.87408E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2357913.57540 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 0.10031 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 97.66206 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 157846.56772 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.38091E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2799.18938 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 97.66206 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10031 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.74714E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.38091E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.03019 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.14853 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00334 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.74381E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 250531.58737 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.06582E-002 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.03019 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 12003.85018 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05015E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 215.27776 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.03019 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.06582E-002 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.46784E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.05015E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.00031 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.43335 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.38288 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.82714E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 129929.42170 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.52750E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.00031 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 274173.69394 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.39859E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6235.33659 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.00031 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.52750E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.61494E-005 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.39859E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.96936 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.96936 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 452498.17935 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 281793.92302 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.10817E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.96936 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.96936 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.96936 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.96936 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 452498.17935 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 452498.17935 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 13450.69260 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.96936 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.96936 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 452498.17935 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.10817E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 13450.69260 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 4.79680E-005 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49027 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49027 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9815.99603 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6187.93703 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.40393E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49027 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49027 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49027 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49027 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9815.99603 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9815.99603 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.36627 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49027 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49027 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9815.99603 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.40393E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 621.36627 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.66970 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.66970 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 93579.43888 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 58964.61639 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29175E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.66970 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.66970 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.66970 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.66970 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 93579.43888 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 93579.43888 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6213.66275 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.66970 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.66970 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 93579.43888 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29175E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6213.66275 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46978 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46978 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9667.56989 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6011.05370 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36758E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46978 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46978 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46978 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46978 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9667.56989 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9667.56989 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.36627 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46978 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46978 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9667.56989 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36758E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 621.36627 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.12676 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 26121.49654 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.12676 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.21176 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.12676 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.12676 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 532094.85308 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.21912E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.46294 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.21912E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3671.43924 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1393523.42025 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1393523.42000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.21912E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.12676 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.21176 |
451 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.12676 |
452 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 18084.79320 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12676 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.40050E-002 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1508197.92627 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1515297.13000 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.49864E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12676 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.40050E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1508197.92627 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1515297.13000 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.49864E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.38506E-002 |
464 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.66207 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.38506E-002 |
466 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3532.58467 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.38506E-002 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 57235.65209 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21206.81799 |
473 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 570524.20687 |
474 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 559477.15000 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.38506E-002 |
476 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
477 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
479 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
480 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
481 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14997 |
482 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.99675 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14997 |
484 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 45168.56681 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 59.14368 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1797868.50833 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.82874 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 224733.56354 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 59.14368 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1797868.50833 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.82874 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 224733.56354 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.78875E-002 |
494 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.78875E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18306.11 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 335948.34 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 59425.67 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4981.54 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4012.19 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6806.74 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3588.38 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 115913.30 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 81367.10 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 115913.94 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 76003.83 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16741.22 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11022.02 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16741.38 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10441.70 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 20587.86 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 140443.62 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 10901.62 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 222940.25 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 299652.41 | 197029.86 | 102622.55 | 0.66 | 39620.38 | 401.85 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2863121.85 | 1876541.53 | 986580.32 | 0.66 | 376814.65 | 3821.86 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 317512.27 | 209402.59 | 108109.68 | 0.66 | 42208.83 | 428.11 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 167887.83 | 111708.42 | 56179.41 | 0.67 | 21775.96 | 220.86 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.4280320945 | 0.1530026816 | Pass | Pass | 0.5976132940 | 0.5325469323 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.7337635684E-003 | 1.9562766559E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.7180802702E-003 | 1.9721523306E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.1261162874E-002 | 1.2432479400E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.1435016540E-002 | 1.4937118153E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.9226300171E-002 | 3.2584578127E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.0201021144E-002 | 3.8096652175E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.4675848196E-002 | 3.1130802620E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.2933855634E-002 | 1.4927967742E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.1497007180E-002 | 3.1020824174E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.6774554238E-002 | 4.1000894541E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.7253234422E-002 | 3.1671558669E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.5421802548E-002 | 2.1209316811E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.3184758995E-002 | 2.7979712960E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.8150328986E-002 | 4.4253274121E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.0528570428E-002 | 3.6492444470E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.7962427425E-003 | 3.0255200991E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.9177804348E-003 | 3.2881723605E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.3650241304E-002 | 4.8160798559E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.8671183059E-005 | 7.3405586830E-005 | Pass | Pass | 2.2839333565E-003 | 1.2874448111E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.2465811243E-005 | 4.8724899005E-005 | Pass | Pass | 7.6716630630E-003 | 4.0002602177E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.6162954691E-002 | 1.7994252821E-002 | Pass | Pass | 1.0467739042E-002 | 8.7036845776E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.5556399860E-004 | 2.0494683110E-004 | Pass | Pass | 5.8406980087E-005 | 1.0850276967E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4680.80 | -43.1 | 0.00 | -5232.3 | 41819.39 | 41224.83 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 1043.06 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.869 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.3279 | 2779.43 | 25926.33 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 240.45 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.3279 | 24961.20 | 232836.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 2159.39 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.96 | 0.0000 | Y | 18.64 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.93 | 0.0000 | Y | 12.00 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.76 | 0.0000 | Y | 18.53 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.90 | 0.0000 | Y | 11.99 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.3279 | 3134.13 | 29234.97 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.99 | 0.0000 | Y | 186.55 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.94 | 0.0000 | Y | 120.04 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.3279 | 3134.20 | 29235.61 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.79 | 0.0000 | Y | 185.41 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.91 | 0.0000 | Y | 119.94 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.99 | 0.0000 | Y | 18.66 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.94 | 0.0000 | Y | 12.00 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.79 | 0.0000 | Y | 18.54 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.91 | 0.0000 | Y | 11.99 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 9.3279 | 783.68 | 7310.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 67.80 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 16.0861 | 362.03 | 5823.61 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 59.65 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
Interior Lighting Total | 9.3913 | 46320.38 | 435009.77 | 1157.50 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.01 | AstronomicalClock | - | 41.75 | 41.75 | 78.17 | |
EXTERIOR_LIGHTS_B | 44362.79 | AstronomicalClock | - | 83.75 | 71.15 | 592.54 | |
Exterior Lighting Total | 54335.80 | 670.70 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2972878.68 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1393523.42 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1515297.13 | 6.28 | 1450347.10 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1515297.13 | 6.28 | 1450347.10 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 559477.15 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1797868.51 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1797868.51 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 241356.59 | 299652.41 | 197029.86 | 102622.55 | 0.66 | - | 39620.38 | 401.85 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2357913.58 | 2863121.85 | 1876541.53 | 986580.32 | 0.66 | - | 376814.65 | 3821.86 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 250531.59 | 317512.27 | 209402.59 | 108109.68 | 0.66 | - | 42208.83 | 428.11 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 129929.42 | 167887.83 | 111708.42 | 56179.41 | 0.67 | - | 21775.96 | 220.86 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 452498.18 | 281793.92 | 170704.26 | 0.62 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9816.00 | 6187.94 | 3628.06 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 93579.44 | 58964.62 | 34614.82 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9667.57 | 6011.05 | 3656.52 | 0.62 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19305.91 | 18306.11 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 354464.71 | 335948.34 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 62750.60 | 59425.67 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 5254.70 | 4981.54 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4232.59 | 4012.19 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7182.26 | 6806.74 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3784.43 | 3588.38 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 122321.44 | 115913.30 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 85910.31 | 81367.10 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 122322.11 | 115913.94 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 80227.15 | 76003.83 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17668.25 | 16741.22 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11632.41 | 11022.02 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17668.43 | 16741.38 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11025.84 | 10441.70 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 23748.16 | 20587.86 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 157846.57 | 140443.62 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 12003.85 | 10901.62 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 274173.69 | 222940.25 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 452498.18 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9816.00 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 93579.44 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9667.57 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 13450.69 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 621.37 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6213.66 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 621.37 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.32 | 22180.58 | 2149.46 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 97.66 | 211042.50 | 2160.95 | 1.00 | 1.08 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.03 | 23709.01 | 2149.46 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.00 | 10174.45 | 1695.65 | 1.00 | 1.15 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 21.97 | 36232.89 | 1649.25 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 549.15 | 1120.11 | 1.00 | 1.61 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.67 | 5230.57 | 1120.11 | 1.00 | 1.16 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 526.20 | 1120.11 | 1.00 | 1.63 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.126765 | 26121.50 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.012191 | 3671.44 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.126765 | 18084.79 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013851 | 3532.58 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.149973 | 45168.57 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 80997.48 | 80997.48 | 29.14 | 6.000 | 6.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 34.82 | 0.00915 | 1.200 | 0.00 |
CORE_BOTTOM | 85109.98 | 85109.98 | 34.10 | 6.305 | 6.305 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00737 | 34.82 | 0.00915 | 1.078 | 0.00 |
CORE_MID | 807330.70 | 807330.70 | 323.43 | 59.791 | 59.791 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00739 | 34.82 | 0.00915 | 10.778 | 0.00 |
CORE_TOP | 82761.94 | 82761.94 | 33.16 | 6.130 | 6.130 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00738 | 34.82 | 0.00915 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 16295.18 | 16295.18 | 51.99 | 1.218 | 1.218 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 24.00 | 24.00 | 0.00726 | 41.81 | 0.00916 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12707.02 | 12707.02 | 62.91 | 0.950 | 0.950 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:10:00 | 24.00 | 24.00 | 0.00722 | 38.56 | 0.00915 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 16578.53 | 16578.53 | 52.90 | 1.239 | 1.239 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 24.00 | 24.00 | 0.00726 | 42.00 | 0.00916 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 16544.02 | 16544.02 | 81.91 | 1.236 | 1.236 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00717 | 41.16 | 0.00916 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 157963.52 | 157963.52 | 504.01 | 11.806 | 11.806 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 24.00 | 24.00 | 0.00731 | 41.71 | 0.00916 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 131147.80 | 131147.80 | 649.33 | 9.802 | 9.802 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 24.00 | 24.00 | 0.00724 | 38.80 | 0.00915 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 159374.33 | 159374.33 | 508.50 | 11.912 | 11.912 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | 24.00 | 24.00 | 0.00730 | 42.00 | 0.00916 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 140200.20 | 140200.20 | 694.15 | 10.479 | 10.479 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 24.00 | 24.00 | 0.00723 | 41.03 | 0.00916 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 18475.29 | 18475.29 | 58.95 | 1.381 | 1.381 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 24.00 | 24.00 | 0.00728 | 41.61 | 0.00916 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14013.77 | 14013.77 | 69.38 | 1.047 | 1.047 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:40:00 | 24.00 | 24.00 | 0.00724 | 39.28 | 0.00915 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18514.36 | 18514.36 | 59.07 | 1.384 | 1.384 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 24.00 | 24.00 | 0.00728 | 42.00 | 0.00916 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15788.64 | 15788.64 | 78.17 | 1.180 | 1.180 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00721 | 41.16 | 0.00916 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8317.58 | 8317.58 | 229.75 | 0.490 | 0.490 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00914 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 79223.03 | 79223.03 | 2188.32 | 4.670 | 4.670 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00914 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7969.89 | 7969.89 | 220.15 | 0.470 | 0.470 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00914 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372677.24 | 372677.24 | 475.55 | 21.969 | 21.969 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 33.17 | 0.00914 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.81 | 0.00607 | 6.30 | 0.00607 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 23.39 | 0.00607 | 6.30 | 0.00607 | 1.078 | 0.00 | |
CORE_MID | 164331.49 | 164331.49 | 65.83 | 7.043 | 10.778 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 10.778 | 0.00 |
CORE_TOP | 43077.00 | 43077.00 | 17.26 | 1.872 | 1.872 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 1670.33 | 1670.33 | 5.33 | 0.073 | 0.135 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 1437.37 | 1437.37 | 7.12 | 0.062 | 0.087 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 3534.95 | 3534.95 | 11.28 | 0.153 | 0.153 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 149.21 | 149.21 | 0.74 | 0.007 | 0.087 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00717 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 85655.62 | 85655.62 | 273.30 | 3.737 | 3.737 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 57054.55 | 57054.55 | 282.48 | 2.489 | 2.489 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 85656.09 | 85656.09 | 273.30 | 3.737 | 3.737 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 49381.77 | 49381.77 | 244.49 | 2.153 | 2.153 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12366.35 | 12366.35 | 39.46 | 0.540 | 0.540 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 8141.55 | 8141.55 | 40.31 | 0.356 | 0.356 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 12366.48 | 12366.48 | 39.46 | 0.540 | 0.540 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 7551.70 | 7551.70 | 37.39 | 0.330 | 0.330 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 6.30 | 0.00607 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.16 | 0.00698 | 6.30 | 0.00607 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.11 | 0.00620 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 6.30 | 0.00607 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.32 | 10.32 | 1.54 | 1.54 | 10.3191 | 3.3600 | 10.3191 | 0.3256 | 0.3000 |
VAV_MID WITH REHEAT | 97.66 | 97.66 | 22.89 | 22.89 | 97.6621 | 32.5719 | 97.6621 | 0.3335 | 0.3000 |
VAV_TOP WITH REHEAT | 11.03 | 11.03 | 3.64 | 3.64 | 11.0302 | 3.6385 | 11.0302 | 0.3299 | 0.3000 |
CAV_BAS | 6.00 | 6.00 | 1.20 | 1.20 | 6.0003 | 6.0003 | 6.0003 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.97 | 21.97 | 0.34 | 0.34 | 21.9694 | 21.9691 | 21.9694 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.49 | 0.49 | 0.02 | 0.02 | 0.4903 | 0.4903 | 0.4903 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.67 | 4.67 | 0.16 | 0.16 | 4.6697 | 4.6697 | 4.6697 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.47 | 0.47 | 0.02 | 0.02 | 0.4698 | 0.4698 | 0.4698 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19305.913 | 19305.913 | 1.967027 | 0.00016890 | 389.192 | 1/21 00:10:00 | 1/21 00:10:00 | 19305.91 | 19305.91 | 1.967027 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 19377.10 | 19377.10 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 354464.714 | 354464.714 | 19.372161 | 0.00310101 | 7814.757 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 354464.71 | 354464.71 | 19.372161 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 164331.49 | 0.00 | 355688.04 | 355688.04 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 62750.600 | 62750.600 | 2.004490 | 0.00054897 | 1623.885 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 62750.60 | 62750.60 | 2.004490 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 43077.00 | 0.00 | 62943.01 | 62943.01 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5254.698 | 5254.698 | 0.365373 | 0.00004597 | 111.029 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5254.70 | 5254.70 | 0.365373 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00775217 | 48.8704 | 1670.33 | 0.00 | 5273.65 | 5273.65 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4232.593 | 4232.593 | 0.284918 | 0.00003703 | 89.875 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4232.59 | 4232.59 | 0.284918 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00777922 | 49.0390 | 1437.37 | 0.00 | 4247.52 | 4247.52 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 7182.258 | 7182.258 | 0.371726 | 0.00006283 | 160.180 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7182.26 | 7182.26 | 0.371726 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00784759 | 49.4646 | 3534.95 | 0.00 | 7206.91 | 7206.91 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3784.435 | 3784.435 | 0.370950 | 0.00003311 | 76.588 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3784.43 | 3784.43 | 0.370950 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00716599 | 45.2170 | 149.21 | 0.00 | 3798.36 | 3798.36 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 122321.443 | 122321.443 | 3.736591 | 0.00107012 | 3228.465 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 122321.44 | 122321.44 | 3.736591 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00790031 | 49.7931 | 85655.62 | 0.00 | 122740.94 | 122740.94 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 85910.307 | 85910.307 | 2.940653 | 0.00075158 | 2161.683 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 85910.31 | 85910.31 | 2.940653 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00790358 | 49.8134 | 57054.55 | 0.00 | 86177.19 | 86177.19 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 122322.114 | 122322.114 | 3.736611 | 0.00107013 | 3228.483 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 122322.11 | 122322.11 | 3.736611 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00790031 | 49.7931 | 85656.09 | 0.00 | 122741.61 | 122741.61 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 80227.147 | 80227.147 | 3.143626 | 0.00070186 | 1925.624 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 80227.15 | 80227.15 | 3.143626 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00786997 | 49.6044 | 49381.77 | 0.00 | 80487.34 | 80487.34 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 17668.253 | 17668.253 | 0.540259 | 0.00015457 | 466.109 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17668.25 | 17668.25 | 0.540259 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794874 | 50.0942 | 12366.35 | 0.00 | 17727.30 | 17727.30 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11632.412 | 11632.412 | 0.355715 | 0.00010177 | 306.869 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11632.41 | 11632.41 | 0.355715 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794965 | 50.0999 | 8141.55 | 0.00 | 11671.23 | 11671.23 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 17668.425 | 17668.425 | 0.540265 | 0.00015457 | 466.114 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17668.43 | 17668.43 | 0.540265 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794874 | 50.0942 | 12366.48 | 0.00 | 17727.48 | 17727.48 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11025.837 | 11025.837 | 0.354021 | 0.00009646 | 284.707 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11025.84 | 11025.84 | 0.354021 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00793757 | 50.0248 | 7551.70 | 0.00 | 11059.67 | 11059.67 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 241356.593 | -999.000 | 10.319117 | 0.01026787 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 241356.59 | 219638.36 | 10.319117 | 28.58 | 17.12 | 0.00779700 | 11.00 | 9.55 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 24.5970 | 24.00 | 0.00733236 | 38.5491 | 133425.99 | 0.00 | 245909.77 | 232462.97 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 23748.160 | 23748.160 | 3.095735 | 0.00020776 | 415.273 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23748.16 | 23748.16 | 3.095735 | 6.30 | 6.30 | 0.00615922 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 81.9899 | 22.62 | 0.00659670 | 37.7261 | 6791.85 | 0.00 | 24925.48 | 24925.48 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2357913.575 | -999.000 | 97.662056 | 0.10031109 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 2357913.58 | 2131484.75 | 97.662056 | 29.01 | 17.33 | 0.00787408 | 10.99 | 9.55 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 25.9896 | 24.00 | 0.00737901 | 38.7918 | 1220258.72 | 0.00 | 2400789.09 | 2250877.93 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 157846.568 | 157846.568 | 29.298617 | 0.00138091 | 2799.189 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 157846.57 | 157846.57 | 29.298617 | 8.23 | 7.53 | 0.00632265 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 86.6319 | 21.00 | 0.00793397 | 50.0022 | 442079.52 | 0.00 | 170034.66 | 170034.66 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 250531.587 | -999.000 | 11.030192 | 0.01065819 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 250531.59 | 228949.23 | 11.030192 | 28.15 | 16.93 | 0.00774381 | 11.00 | 9.55 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 23.0113 | 24.00 | 0.00732015 | 38.4859 | 147310.24 | 0.00 | 255351.06 | 242746.17 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 12003.850 | 12003.850 | 3.309057 | 0.00010501 | 215.278 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12003.85 | 12003.85 | 3.309057 | 9.72 | 8.44 | 0.00651626 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 76.7043 | 21.00 | 0.00797793 | 50.2754 | 57545.58 | 0.00 | 13198.58 | 13198.58 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 129929.422 | -999.000 | 6.000309 | 0.00552750 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 129929.42 | 117190.69 | 6.000309 | 27.43 | 16.75 | 0.00782714 | 11.38 | 9.72 | 0.00700000 | 39.77 | 0.00915417 | 21.63 | 20.0016 | 24.00 | 0.00745765 | 39.2002 | 79880.86 | 0.00 | 132494.66 | 125499.34 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 274173.694 | 274173.694 | 6.000309 | 0.00239859 | 6235.337 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 274173.69 | 274173.69 | 6.000309 | 1.26 | 1.26 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 20.0016 | 25.81 | 0.00607234 | 28.7199 | 0.00 | 0.00 | 235929.42 | 235929.42 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 452498.179 | 281793.923 | 21.969355 | 0.01108165 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 | 406431.02 | 402713.71 | -999.0 | 28.66 | 16.55 | 0.00707469 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | -999.0000 | 27.00 | 0.00704205 | 30.9975 | 372190.56 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9815.996 | 6187.937 | 0.490269 | 0.00024039 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 8770.51 | 8695.23 | -999.0 | 28.14 | 16.36 | 0.00706830 | 12.80 | 10.34 | 0.00700000 | 32.36 | 0.00914193 | 19.41 | -999.0000 | 27.00 | 0.00700000 | 30.8097 | 8269.80 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93579.439 | 58964.616 | 4.669705 | 0.00229175 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 83626.46 | 82873.44 | -999.0 | 28.15 | 16.37 | 0.00707170 | 12.80 | 10.34 | 0.00700000 | 32.36 | 0.00914193 | 19.41 | -999.0000 | 27.00 | 0.00700000 | 30.8097 | 78812.63 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9667.570 | 6011.054 | 0.469775 | 0.00023676 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 8682.90 | 8513.18 | -999.0 | 28.45 | 16.54 | 0.00715964 | 12.80 | 10.34 | 0.00700000 | 41.29 | 0.00915671 | 22.06 | -999.0000 | 27.00 | 0.00709081 | 31.2079 | 7959.40 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 452498.179 | 452498.179 | 21.969355 | 0.01108165 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 452498.18 | 452498.18 | 21.969355 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5403 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9815.996 | 9815.996 | 0.490269 | 0.00024039 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9816.00 | 9816.00 | 0.490269 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.1885 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93579.439 | 93579.439 | 4.669705 | 0.00229175 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 93579.44 | 93579.44 | 4.669705 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3476 | 25.16 | 0.00698209 | 34.2539 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9667.570 | 9667.570 | 0.469775 | 0.00023676 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9667.57 | 9667.57 | 0.469775 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3276 | 24.11 | 0.00620124 | 32.4414 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 13450.693 | 13450.693 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 13450.69 | 13450.69 | 21.969355 | 0.10 | 0.10 | 0.00698571 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5403 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.37 | 621.37 | 0.490269 | 0.20 | 0.20 | 0.00697042 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.1885 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6213.663 | 6213.663 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6213.66 | 6213.66 | 4.669705 | 0.21 | 0.21 | 0.00695164 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3476 | 25.16 | 0.00698209 | 34.2539 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.37 | 621.37 | 0.469775 | 0.21 | 0.21 | 0.00619695 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3276 | 24.11 | 0.00620124 | 32.4414 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19305.913 | 19305.913 | 1.967027 | 0.00016890 | 389.192 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 1.3581 | 1.385403 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 19305.91 | 19305.91 | 1.0000 | 2.30886810 | 1.967027 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.16887932 | 60.00 | 32.22 | 27.78 | 0.000 | 19305.91 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 19377.10 | 19377.10 | 2.30886810 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 354464.714 | 354464.714 | 19.372161 | 0.00310101 | 7814.757 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 24.9348 | 25.436581 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 354464.71 | 354464.71 | 1.0000 | 22.73876087 | 19.372161 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 3.10069562 | 60.00 | 32.22 | 27.78 | 0.000 | 354464.71 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 164331.49 | 0.00 | 355688.04 | 355688.04 | 22.73876087 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.14 | 17.41 | 0.00800000 | 48702.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 62750.600 | 62750.600 | 2.004490 | 0.00054897 | 1623.885 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 4.4142 | 4.503017 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 62750.60 | 62750.60 | 1.0000 | 2.35284144 | 2.004490 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.54891362 | 60.00 | 32.22 | 27.78 | 0.000 | 62750.60 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 43077.00 | 0.00 | 62943.01 | 62943.01 | 2.35284144 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.03 | 20.89 | 0.00800000 | 59811.7 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5254.698 | 5254.698 | 0.365373 | 0.00004597 | 111.029 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 0.3696 | 0.377080 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5254.70 | 5254.70 | 1.0000 | 0.42886945 | 0.365373 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.04596570 | 60.00 | 32.22 | 27.78 | 0.000 | 5254.70 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00775217 | 21.00 | 0.00775217 | 48.8704 | 1670.33 | 0.00 | 5273.65 | 5273.65 | 0.42886945 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.86 | 16.26 | 0.00800000 | 45356.5 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4232.593 | 4232.593 | 0.284918 | 0.00003703 | 89.875 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 0.2977 | 0.303733 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4232.59 | 4232.59 | 1.0000 | 0.33443276 | 0.284918 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03702480 | 60.00 | 32.22 | 27.78 | 0.000 | 4232.59 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.87 | 0.00777922 | 21.00 | 0.00777922 | 49.0390 | 1437.37 | 0.00 | 4247.52 | 4247.52 | 0.33443276 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.26 | 16.40 | 0.00800000 | 45760.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7182.258 | 7182.258 | 0.371726 | 0.00006283 | 160.180 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 0.5052 | 0.515403 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7182.26 | 7182.26 | 1.0000 | 0.43632692 | 0.371726 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.06282712 | 60.00 | 32.22 | 27.78 | 0.000 | 7182.26 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.87 | 0.00784759 | 21.00 | 0.00784759 | 49.4646 | 3534.95 | 0.00 | 7206.91 | 7206.91 | 0.43632692 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.00 | 17.70 | 0.00800000 | 49577.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3784.435 | 3784.435 | 0.370950 | 0.00003311 | 76.588 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 0.2662 | 0.271573 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3784.43 | 3784.43 | 1.0000 | 0.43541566 | 0.370950 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03310451 | 60.00 | 32.22 | 27.78 | 0.000 | 3784.43 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.99 | 0.00716599 | 21.00 | 0.00716599 | 45.2170 | 149.21 | 0.00 | 3798.36 | 3798.36 | 0.43541566 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.35 | 14.98 | 0.00800000 | 41783.4 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 122321.443 | 122321.443 | 3.736591 | 0.00107012 | 3228.465 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 8.6047 | 8.777853 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 122321.44 | 122321.44 | 1.0000 | 4.38595607 | 3.736591 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.07001218 | 60.00 | 32.22 | 27.78 | 0.000 | 122321.44 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00790031 | 21.00 | 0.00790031 | 49.7931 | 85655.62 | 0.00 | 122740.94 | 122740.94 | 4.38595607 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61044.8 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 85910.307 | 85910.307 | 2.940653 | 0.00075158 | 2161.683 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 6.0433 | 6.164970 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 85910.31 | 85910.31 | 1.0000 | 3.45169573 | 2.940653 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.75150418 | 60.00 | 32.22 | 27.78 | 0.000 | 85910.31 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00790358 | 21.00 | 0.00790358 | 49.8134 | 57054.55 | 0.00 | 86177.19 | 86177.19 | 3.45169573 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.28 | 20.36 | 0.00800000 | 58026.5 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 122322.114 | 122322.114 | 3.736611 | 0.00107013 | 3228.483 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 8.6047 | 8.777902 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 122322.11 | 122322.11 | 1.0000 | 4.38597986 | 3.736611 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.07001805 | 60.00 | 32.22 | 27.78 | 0.000 | 122322.11 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00790031 | 21.00 | 0.00790031 | 49.7931 | 85656.09 | 0.00 | 122741.61 | 122741.61 | 4.38597986 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61044.8 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 80227.147 | 80227.147 | 3.143626 | 0.00070186 | 1925.624 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 5.6436 | 5.757144 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 80227.15 | 80227.15 | 1.0000 | 3.68994256 | 3.143626 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.70179048 | 60.00 | 32.22 | 27.78 | 0.000 | 80227.15 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00786997 | 21.00 | 0.00786997 | 49.6044 | 49381.77 | 0.00 | 80487.34 | 80487.34 | 3.68994256 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.19 | 19.40 | 0.00800000 | 54872.5 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17668.253 | 17668.253 | 0.540259 | 0.00015457 | 466.109 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 1.2429 | 1.267883 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17668.25 | 17668.25 | 1.0000 | 0.63414873 | 0.540259 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.15455381 | 60.00 | 32.22 | 27.78 | 0.000 | 17668.25 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00794874 | 21.00 | 0.00794874 | 50.0942 | 12366.35 | 0.00 | 17727.30 | 17727.30 | 0.63414873 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61014.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11632.412 | 11632.412 | 0.355715 | 0.00010177 | 306.869 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 0.8183 | 0.834748 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11632.41 | 11632.41 | 1.0000 | 0.41753340 | 0.355715 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.10175503 | 60.00 | 32.22 | 27.78 | 0.000 | 11632.41 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00794965 | 21.00 | 0.00794965 | 50.0999 | 8141.55 | 0.00 | 11671.23 | 11671.23 | 0.41753340 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61012.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17668.425 | 17668.425 | 0.540265 | 0.00015457 | 466.114 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 1.2429 | 1.267896 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17668.43 | 17668.43 | 1.0000 | 0.63415491 | 0.540265 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.15455533 | 60.00 | 32.22 | 27.78 | 0.000 | 17668.43 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00794874 | 21.00 | 0.00794874 | 50.0942 | 12366.48 | 0.00 | 17727.48 | 17727.48 | 0.63415491 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61014.3 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11025.837 | 11025.837 | 0.354021 | 0.00009646 | 284.707 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 0.7756 | 0.791220 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11025.84 | 11025.84 | 1.0000 | 0.41554447 | 0.354021 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.09644899 | 60.00 | 32.22 | 27.78 | 0.000 | 11025.84 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00793757 | 21.00 | 0.00793757 | 50.0248 | 7551.70 | 0.00 | 11059.67 | 11059.67 | 0.41554447 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.90 | 20.85 | 0.00800000 | 59674.7 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 241356.593 | -999.000 | 10.319117 | 0.01026787 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3342 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.319117 | 12.11242912 | 4197.9300 | 999.8980 | 126.75172122 | 12.27 | 6.67 | 5.60 | 2979731.18 | 8.0999 | 8.099945 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 241356.59 | 219638.36 | 1.0000 | 12.11242912 | 10.319117 | 28.58 | 17.12 | 0.00779700 | 48632.9 | 11.00 | 9.55 | 0.00700000 | 28706.5 | 10.26681997 | 6.67 | 12.27 | 5.60 | 22180.576 | 219176.02 | 42.00 | 0.00915790 | 22.26 | 2.53819000 | 24.5970 | 24.00 | 0.00733236 | 24.00 | 0.00733236 | 38.5491 | 133425.99 | 0.00 | 245909.77 | 232462.97 | 12.11242912 | 28.58 | 17.39 | 0.00779700 | 48632.9 | 9.75 | 9.59 | 0.00735629 | 28330.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 23748.160 | 23748.160 | 3.095735 | 0.00020776 | 415.273 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.319117 | 12.11242912 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 1.6706 | 1.704181 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23748.16 | 23748.16 | 1.0000 | 3.63372874 | 3.095735 | 6.30 | 6.30 | 0.00615922 | 21802.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.20773807 | 60.00 | 32.22 | 27.78 | 0.000 | 23748.16 | 6.30 | 0.00607234 | 6.30 | 2.53819000 | 81.9899 | 6.28 | 0.00655470 | 22.62 | 0.00659670 | 37.7261 | 6791.85 | 0.00 | 24925.48 | 24925.48 | 3.63372874 | 2.80 | 2.80 | 0.00615922 | 18249.4 | 9.55 | 8.16 | 0.00615922 | 25108.9 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2357913.575 | -999.000 | 97.662056 | 0.10031109 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4775 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 97.662056 | 114.63430087 | 4197.9300 | 999.8980 | 126.75172122 | 12.27 | 6.67 | 5.60 | 2979731.18 | 79.1318 | 79.131755 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 2357913.58 | 2131484.75 | 1.0000 | 114.63430087 | 97.662056 | 29.01 | 17.33 | 0.00787408 | 49266.0 | 10.99 | 9.55 | 0.00700000 | 28697.0 | 100.30086152 | 6.67 | 12.27 | 5.60 | 211042.501 | 2146871.07 | 42.00 | 0.00915790 | 22.26 | 25.38195000 | 25.9896 | 24.00 | 0.00737901 | 24.00 | 0.00737901 | 38.7918 | 1220258.72 | 0.00 | 2400789.09 | 2250877.93 | 114.63430087 | 29.01 | 17.60 | 0.00787408 | 49266.0 | 9.75 | 9.59 | 0.00735494 | 28323.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 157846.568 | 157846.568 | 29.298617 | 0.00138091 | 2799.189 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 97.662056 | 114.63430087 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 11.1037 | 11.327156 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 157846.57 | 157846.57 | 1.0000 | 34.39029026 | 29.298617 | 8.23 | 7.53 | 0.00632265 | 24181.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 1.38076977 | 60.00 | 32.22 | 27.78 | 0.000 | 157846.57 | 6.30 | 0.00607234 | 6.30 | 25.38195000 | 86.6319 | 20.75 | 0.00794474 | 21.00 | 0.00793397 | 50.0022 | 442079.52 | 0.00 | 170034.66 | 170034.66 | 34.39029026 | 2.80 | 2.80 | 0.00632265 | 18659.0 | 7.66 | 7.45 | 0.00632265 | 23603.3 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 250531.587 | -999.000 | 11.030192 | 0.01065819 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2354 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.030192 | 12.94707848 | 4197.9300 | 999.8980 | 126.75172122 | 12.27 | 6.67 | 5.60 | 2979731.18 | 8.4079 | 8.407859 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | Sensible | 250531.59 | 228949.23 | 1.0000 | 12.94707848 | 11.030192 | 28.15 | 16.93 | 0.00774381 | 48056.8 | 11.00 | 9.55 | 0.00700000 | 28706.4 | 10.65710564 | 6.67 | 12.27 | 5.60 | 23709.006 | 226822.58 | 42.00 | 0.00915790 | 22.26 | 2.53819000 | 23.0113 | 24.00 | 0.00732015 | 24.00 | 0.00732015 | 38.4859 | 147310.24 | 0.00 | 255351.06 | 242746.17 | 12.94707848 | 28.15 | 17.20 | 0.00774381 | 48056.8 | 9.75 | 9.59 | 0.00735733 | 28334.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 12003.850 | 12003.850 | 3.309057 | 0.00010501 | 215.278 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.030192 | 12.94707848 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 0.8444 | 0.861403 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12003.85 | 12003.85 | 1.0000 | 3.88412354 | 3.309057 | 9.72 | 8.44 | 0.00651626 | 26186.1 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.10500421 | 60.00 | 32.22 | 27.78 | 0.000 | 12003.85 | 6.30 | 0.00607234 | 6.30 | 2.53819000 | 76.7043 | 21.00 | 0.00797793 | 21.00 | 0.00797793 | 50.2754 | 57545.58 | 0.00 | 13198.58 | 13198.58 | 3.88412354 | 2.80 | 2.80 | 0.00651626 | 19144.2 | 6.14 | 6.14 | 0.00651626 | 22542.3 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 129929.422 | -999.000 | 6.000309 | 0.00552750 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3903 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:ConstantVolume | 6.000309 | 7.04307530 | 4197.9300 | 999.8980 | 126.75172122 | 12.27 | 6.67 | 5.60 | 2979731.18 | 4.3604 | 4.360441 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 129929.42 | 117190.69 | 1.0000 | 7.04307530 | 6.000309 | 27.43 | 16.75 | 0.00782714 | 47540.5 | 11.38 | 9.72 | 0.00700000 | 29092.7 | 5.52693410 | 6.67 | 12.27 | 5.60 | 10174.450 | 119754.97 | 39.77 | 0.00915417 | 21.63 | 1.20015641 | 20.0016 | 24.00 | 0.00745765 | 24.00 | 0.00745765 | 39.2002 | 79880.86 | 0.00 | 132494.66 | 125499.34 | 7.04307530 | 27.43 | 17.02 | 0.00782714 | 47540.5 | 9.95 | 9.77 | 0.00743292 | 28728.4 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 274173.694 | 274173.694 | 6.000309 | 0.00239859 | 6235.337 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:ConstantVolume | 6.000309 | 7.04307530 | 4197.9300 | 999.8980 | 12.18990717 | 54.44 | 82.22 | 27.78 | 1421568.63 | 19.2867 | 19.674854 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 274173.69 | 274173.69 | 1.0000 | 7.04307530 | 6.000309 | 1.26 | 1.26 | 0.00607234 | 16467.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.39834640 | 60.00 | 32.22 | 27.78 | 0.000 | 274173.69 | 6.30 | 0.00607234 | 6.30 | 1.20015641 | 20.0016 | 0.00 | 0.00607234 | 25.81 | 0.00607234 | 28.7199 | 0.00 | 0.00 | 235929.42 | 235929.42 | 7.04307530 | 12.80 | 9.56 | 0.00607234 | 28193.0 | 45.77 | 21.49 | 0.00607234 | 61691.1 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 452498.179 | 281793.923 | 21.969355 | 0.01108165 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9915 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 | Sensible | 406431.02 | 402713.71 | 0.8982 | -999.0 | -999.0 | 28.66 | 16.55 | 0.00707469 | 46868.1 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 406431.02 | 42.00 | 0.00915790 | 22.26 | 0.33839277 | -999.0000 | 27.00 | 0.00704205 | 27.00 | 0.00704205 | 30.9975 | 372190.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9815.996 | 6187.937 | 0.490269 | 0.00024039 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9796 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 06:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | Sensible | 8770.51 | 8695.23 | 0.8935 | -999.0 | -999.0 | 28.14 | 16.36 | 0.00706830 | 46325.7 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8770.51 | 32.36 | 0.00914193 | 19.41 | 0.01563234 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 8269.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 93579.439 | 58964.616 | 4.669705 | 0.00229175 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9859 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 06:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | Sensible | 83626.46 | 82873.44 | 0.8936 | -999.0 | -999.0 | 28.15 | 16.37 | 0.00707170 | 46343.1 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83626.46 | 32.36 | 0.00914193 | 19.41 | 0.15632344 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 78812.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9667.570 | 6011.054 | 0.469775 | 0.00023676 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.1494 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | Sensible | 8682.90 | 8513.18 | 0.8981 | -999.0 | -999.0 | 28.45 | 16.54 | 0.00715964 | 46868.8 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8682.90 | 41.29 | 0.00915671 | 22.06 | 0.01563234 | -999.0000 | 27.00 | 0.00709081 | 27.00 | 0.00709081 | 31.2079 | 7959.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 452498.179 | 452498.179 | 21.969355 | 0.01108165 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 452498.18 | 452498.18 | 1.0000 | 25.78730951 | 21.969355 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 452498.18 | 6.30 | 0.00607234 | 6.30 | 0.33839277 | 1.5403 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9815.996 | 9815.996 | 0.490269 | 0.00024039 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9816.00 | 9816.00 | 1.0000 | 0.57547109 | 0.490269 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9816.00 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.1885 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 93579.439 | 93579.439 | 4.669705 | 0.00229175 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 93579.44 | 93579.44 | 1.0000 | 5.48123179 | 4.669705 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93579.44 | 6.30 | 0.00607234 | 6.30 | 0.15632344 | 3.3476 | 0.00 | 0.00698209 | 25.16 | 0.00698209 | 34.2539 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9667.570 | 9667.570 | 0.469775 | 0.00023676 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9667.57 | 9667.57 | 1.0000 | 0.55141536 | 0.469775 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9667.57 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.3276 | 0.00 | 0.00620124 | 24.11 | 0.00620124 | 32.4414 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13450.693 | 13450.693 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.969355 | 25.78730951 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 13450.69 | 13450.69 | 1.0000 | 25.78730951 | 21.969355 | 0.10 | 0.10 | 0.00698571 | 17569.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13450.69 | 6.30 | 0.00607234 | 6.30 | 0.33839277 | 1.5403 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.490269 | 0.57547109 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 621.37 | 621.37 | 1.0000 | 0.57547109 | 0.490269 | 0.20 | 0.20 | 0.00697042 | 17637.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.37 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.1885 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6213.663 | 6213.663 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.669705 | 5.48123179 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6213.66 | 6213.66 | 1.0000 | 5.48123179 | 4.669705 | 0.21 | 0.21 | 0.00695164 | 17600.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6213.66 | 6.30 | 0.00607234 | 6.30 | 0.15632344 | 3.3476 | 0.00 | 0.00698209 | 25.16 | 0.00698209 | 34.2539 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.469775 | 0.55141536 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 621.37 | 621.37 | 1.0000 | 0.55141536 | 0.469775 | 0.21 | 0.21 | 0.00619695 | 15711.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.37 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.3276 | 0.00 | 0.00620124 | 24.11 | 0.00620124 | 32.4414 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5406.17 | 1646.50 | 1646.50 |
CORE_BOTTOM | 5435.00 | 20.33 | 13.00 |
CORE_MID | 4811.33 | 270.17 | 22.00 |
CORE_TOP | 4334.50 | 1015.67 | 28.50 |
PERIMETER_BOT_ZN_3 | 4502.83 | 926.50 | 101.00 |
PERIMETER_BOT_ZN_2 | 4590.67 | 957.00 | 160.00 |
PERIMETER_BOT_ZN_1 | 5187.33 | 635.50 | 259.00 |
PERIMETER_BOT_ZN_4 | 5401.17 | 728.83 | 472.50 |
PERIMETER_MID_ZN_3 | 3841.50 | 1887.33 | 223.17 |
PERIMETER_MID_ZN_2 | 3450.50 | 1503.00 | 301.67 |
PERIMETER_MID_ZN_1 | 4955.17 | 956.50 | 375.50 |
PERIMETER_MID_ZN_4 | 4255.67 | 1589.33 | 304.83 |
PERIMETER_TOP_ZN_3 | 3776.83 | 2269.67 | 402.67 |
PERIMETER_TOP_ZN_2 | 4068.00 | 1974.00 | 406.83 |
PERIMETER_TOP_ZN_1 | 4661.33 | 1343.67 | 405.33 |
PERIMETER_TOP_ZN_4 | 4047.50 | 1954.17 | 393.50 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1685.17 | 1685.17 |
DATACENTER_MID_ZN_6 | 5943.00 | 489.83 | 489.83 |
DATACENTER_TOP_ZN_6 | 5909.00 | 752.50 | 740.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 100.50 | 0.00 | 8.00 |
CORE_BOTTOM | 0.00 | 8.67 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 0.17 | 0.67 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 30.50 | 0.00 | 12.50 |
PERIMETER_BOT_ZN_2 | 0.00 | 33.50 | 0.00 | 25.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 78.17 | 0.00 | 55.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 223.83 | 0.00 | 70.17 |
PERIMETER_MID_ZN_3 | 0.00 | 22.17 | 0.00 | 8.33 |
PERIMETER_MID_ZN_2 | 0.00 | 40.33 | 0.00 | 31.00 |
PERIMETER_MID_ZN_1 | 0.00 | 70.33 | 0.00 | 51.67 |
PERIMETER_MID_ZN_4 | 0.00 | 66.50 | 0.00 | 28.83 |
PERIMETER_TOP_ZN_3 | 0.33 | 46.50 | 0.00 | 21.17 |
PERIMETER_TOP_ZN_2 | 0.33 | 71.00 | 0.00 | 44.83 |
PERIMETER_TOP_ZN_1 | 0.33 | 84.17 | 0.00 | 52.00 |
PERIMETER_TOP_ZN_4 | 0.33 | 86.17 | 0.00 | 34.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 545.00 | 0.00 | 449.50 |
DATACENTER_MID_ZN_6 | 0.00 | 451.00 | 0.00 | 399.67 |
DATACENTER_TOP_ZN_6 | 0.00 | 309.00 | 0.00 | 277.50 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1282.17 | 0.00 | 919.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.33 | 1636.17 | 0.00 | 1069.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.75 | 149.60 | 6779.02 | 0.535 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.35 | 134.35 | 6849.35 | 0.469 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.35 | 134.35 | 6849.35 | 0.449 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.35 | 134.35 | 6849.35 | 0.436 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.08 | 16.87 | 860.00 | 0.614 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.56 | 10.87 | 554.22 | 0.717 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.08 | 16.87 | 860.02 | 0.762 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.56 | 10.87 | 554.22 | 1.050 | 0.017 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.08 | 16.87 | 860.00 | 0.639 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.99 | 10.87 | 554.22 | 0.796 | 0.042 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.08 | 16.87 | 860.02 | 0.824 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.56 | 10.87 | 554.22 | 0.885 | 0.041 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.08 | 16.87 | 860.00 | 0.673 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.56 | 10.87 | 554.22 | 0.835 | 0.050 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.08 | 16.87 | 860.02 | 0.824 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.56 | 10.87 | 554.22 | 0.903 | 0.050 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.82 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.82 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.82 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.69 | 42.18 | 1911.37 | 0.665 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.75 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.35 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.35 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.35 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.08 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.56 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.08 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.56 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.08 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.99 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.08 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.56 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.08 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.56 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.08 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.56 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.82 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.82 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.82 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.69 | 42.18 | 1911.37 | 0.613 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.75 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 56.35 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 56.35 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 56.35 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.08 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.56 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.08 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.56 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.08 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.99 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.08 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.56 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.08 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.56 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.08 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.56 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.82 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.82 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.82 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.69 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1040.03 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 24045975.87 | 0.00 | 24045975.87 | 0.00 | 24045975.87 | 37848132.68 | 3194.53 | 5565.47 | 0.00 | 748.77 |
CORE_BOTTOM | 23002973.66 | 0.00 | 23002973.66 | 0.00 | 23002973.66 | 33990283.35 | 8091.59 | 92.89 | 575.52 | 1289.78 |
CORE_MID | 0.20E+09 | 0.00 | 0.20E+09 | 0.00 | 0.20E+09 | 0.34E+09 | 8135.83 | 86.93 | 537.24 | 744.20 |
CORE_TOP | 19713247.91 | 0.00 | 19713247.91 | 0.00 | 19713247.91 | 33990283.35 | 8700.82 | 34.40 | 24.78 | 735.67 |
PERIMETER_BOT_ZN_3 | 3866899.62 | 0.00 | 3866899.62 | 135485.55 | 4002385.18 | 4267819.30 | 3607.66 | 108.66 | 5043.68 | 1289.78 |
PERIMETER_BOT_ZN_2 | 2932653.22 | 0.00 | 2932653.22 | 90323.64 | 3022976.86 | 2750345.05 | 2743.97 | 80.78 | 5935.25 | 1289.78 |
PERIMETER_BOT_ZN_1 | 4618345.88 | 0.00 | 4618345.88 | 135485.55 | 4753831.44 | 4267912.63 | 2498.56 | 55.89 | 6205.55 | 1289.78 |
PERIMETER_BOT_ZN_4 | 4233477.40 | 0.00 | 4233477.40 | 90323.64 | 4323801.04 | 2750345.05 | 2218.38 | 0.00 | 6541.62 | 1289.78 |
PERIMETER_MID_ZN_3 | 36420877.03 | 0.00 | 36420877.03 | 317743.67 | 36738620.70 | 42678193.03 | 3954.68 | 38.75 | 4766.58 | 744.20 |
PERIMETER_MID_ZN_2 | 30054298.27 | 0.00 | 30054298.27 | 211828.97 | 30266127.24 | 27503450.52 | 3013.61 | 46.68 | 5699.71 | 1653.20 |
PERIMETER_MID_ZN_1 | 45625166.60 | 0.00 | 45625166.60 | 317743.67 | 45942910.27 | 42679126.28 | 3089.27 | 10.04 | 5660.69 | 744.20 |
PERIMETER_MID_ZN_4 | 32573291.61 | 0.00 | 32573291.61 | 211828.97 | 32785120.58 | 27503450.52 | 2977.93 | 14.05 | 5768.01 | 744.20 |
PERIMETER_TOP_ZN_3 | 3858725.50 | 0.00 | 3858725.50 | 394502.81 | 4253228.30 | 4267819.30 | 3547.26 | 54.73 | 5158.01 | 735.67 |
PERIMETER_TOP_ZN_2 | 3063161.55 | 0.00 | 3063161.55 | 263001.69 | 3326163.24 | 2750345.05 | 2999.45 | 16.32 | 5744.23 | 735.67 |
PERIMETER_TOP_ZN_1 | 4610989.49 | 0.00 | 4610989.49 | 394502.81 | 5005492.29 | 4267912.63 | 2993.99 | 5.91 | 5760.10 | 735.67 |
PERIMETER_TOP_ZN_4 | 3343814.53 | 0.00 | 3343814.53 | 263001.69 | 3606816.22 | 2750345.05 | 2972.44 | 2.38 | 5785.19 | 735.67 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.36E+10 | 0.00 | 0.36E+10 | 12358080.11 | 0.36E+10 | 0.50E+10 | 8760.00 | 8760.00 | 6949.17 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9727 | 0.0000 | 0.9727 | 0.0000 | 0.9727 | 1.2002 | 1126.30 | 4816.70 | 0.00 |
CORE_BOTTOM | 0.8625 | 0.0000 | 0.8625 | 0.0000 | 0.8625 | 1.0778 | 5291.02 | 92.06 | 559.92 |
CORE_MID | 8.2571 | 0.0000 | 8.2571 | 0.0000 | 8.2571 | 10.7782 | 5330.59 | 86.60 | 525.81 |
CORE_TOP | 0.8025 | 0.0000 | 0.8025 | 0.0000 | 0.8025 | 1.0778 | 5887.62 | 34.04 | 21.34 |
PERIMETER_BOT_ZN_3 | 0.1415 | 0.0000 | 0.1415 | 0.0039 | 0.1454 | 0.1353 | 2063.22 | 107.86 | 3771.92 |
PERIMETER_BOT_ZN_2 | 0.1066 | 0.0000 | 0.1066 | 0.0026 | 0.1092 | 0.0872 | 1201.29 | 80.30 | 4661.41 |
PERIMETER_BOT_ZN_1 | 0.1758 | 0.0000 | 0.1758 | 0.0039 | 0.1797 | 0.1353 | 955.74 | 55.45 | 4931.80 |
PERIMETER_BOT_ZN_4 | 0.1561 | 0.0000 | 0.1561 | 0.0026 | 0.1587 | 0.0872 | 691.16 | 0.00 | 5251.84 |
PERIMETER_MID_ZN_3 | 1.4759 | 0.0000 | 1.4759 | 0.0091 | 1.4850 | 1.3533 | 1869.76 | 38.72 | 4034.53 |
PERIMETER_MID_ZN_2 | 1.1849 | 0.0000 | 1.1849 | 0.0062 | 1.1911 | 0.8721 | 907.22 | 27.67 | 4099.11 |
PERIMETER_MID_ZN_1 | 1.9020 | 0.0000 | 1.9020 | 0.0091 | 1.9111 | 1.3533 | 1007.70 | 10.00 | 4925.30 |
PERIMETER_MID_ZN_4 | 1.3166 | 0.0000 | 1.3166 | 0.0060 | 1.3227 | 0.8721 | 900.78 | 13.59 | 5028.63 |
PERIMETER_TOP_ZN_3 | 0.1555 | 0.0000 | 0.1555 | 0.0113 | 0.1668 | 0.1353 | 1461.55 | 54.47 | 4426.99 |
PERIMETER_TOP_ZN_2 | 0.1244 | 0.0000 | 0.1244 | 0.0075 | 0.1319 | 0.0872 | 915.31 | 16.11 | 5011.58 |
PERIMETER_TOP_ZN_1 | 0.1904 | 0.0000 | 0.1904 | 0.0113 | 0.2017 | 0.1353 | 910.78 | 5.87 | 5026.35 |
PERIMETER_TOP_ZN_4 | 0.1346 | 0.0000 | 0.1346 | 0.0075 | 0.1421 | 0.0872 | 890.53 | 2.25 | 5050.22 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 147.1199 | 0.0000 | 147.1199 | 0.3545 | 147.4745 | 158.4706 | 5943.00 | 5943.00 | 5397.14 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 53256913.86 | 0.00 | 53256913.86 | 48026705.38 | 2218.20 | 0.00 | 6541.80 | 1289.78 |
VAV_MID WITH REHEAT | 0.48E+09 | 0.00 | 0.48E+09 | 0.48E+09 | 2950.21 | 0.00 | 5809.79 | 744.20 |
VAV_TOP WITH REHEAT | 47657061.12 | 0.00 | 47657061.12 | 48026705.38 | 2967.33 | 0.00 | 5792.67 | 735.67 |
CAV_BAS | 33129879.64 | 0.00 | 33129879.64 | 37848132.68 | 3194.53 | 0.00 | 5565.47 | 748.77 |
AIRLOOP DATACENTER BASEMENT | 14702971.99 | 0.00 | 14702971.99 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 679216.39 | 0.00 | 679216.39 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 6792163.95 | 0.00 | 6792163.95 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 679216.39 | 0.00 | 679216.39 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 1.9875 | 0.0000 | 1.9875 | 1.5229 | 690.98 | 0.00 | 5252.02 |
VAV_MID WITH REHEAT | 19.5227 | 0.0000 | 19.5227 | 15.2292 | 877.41 | 0.00 | 5065.59 |
VAV_TOP WITH REHEAT | 1.9391 | 0.0000 | 1.9391 | 1.5229 | 886.00 | 0.00 | 5057.00 |
CAV_BAS | 1.3402 | 0.0000 | 1.3402 | 1.2002 | 1126.30 | 0.00 | 4816.70 |
AIRLOOP DATACENTER BASEMENT | 0.4662 | 0.0000 | 0.4662 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0215 | 0.0000 | 0.0215 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2154 | 0.0000 | 0.2154 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0215 | 0.0000 | 0.0215 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6541.80 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5809.79 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5792.67 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5565.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.2490 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 22.9068 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.2789 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6538 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4662 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1380 |
Defaulted Fields | 1179 |
Fields with Defaults | 3862 |
Autosized Fields | 330 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 34348.76 | 380994.45 | 01-JAN-10:20 | 2158800.56 | 07-AUG-15:20 |
Electricity:Building | 18918.81 | 251811.03 | 01-JAN-08:50 | 1136695.02 | 29-DEC-17:00 |
Electricity:Zone:BASEMENT | 664.85 | 14623.97 | 01-JAN-00:10 | 34452.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18918.81 | 251811.03 | 01-JAN-08:50 | 1136695.02 | 29-DEC-17:00 |
InteriorLights:Electricity | 3705.40 | 17601.77 | 01-JAN-08:50 | 344557.66 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3705.40 | 17601.77 | 01-JAN-08:50 | 344557.66 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 3705.40 | 17601.77 | 01-JAN-08:50 | 344557.66 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3705.40 | 17601.77 | 01-JAN-08:50 | 344557.66 | 11-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 537.23 | 7090.40 | 01-JAN-00:10 | 36983.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5372.24 | 70903.72 | 01-JAN-00:10 | 369831.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 537.22 | 7090.37 | 01-JAN-00:10 | 36983.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 58.98 | 839.57 | 01-JAN-08:40 | 4434.82 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.64 | 80.80 | 01-JAN-08:40 | 2158.51 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.64 | 80.80 | 01-JAN-08:40 | 2158.51 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 38.00 | 541.05 | 01-JAN-07:50 | 2859.76 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.00 | 52.07 | 01-JAN-07:50 | 1392.81 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.00 | 52.07 | 01-JAN-07:50 | 1392.81 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 58.87 | 839.58 | 01-JAN-07:50 | 4426.36 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.53 | 80.80 | 01-JAN-07:50 | 2150.01 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.53 | 80.80 | 01-JAN-07:50 | 2150.01 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 37.99 | 541.05 | 01-JAN-08:50 | 2864.08 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.99 | 52.07 | 01-JAN-08:50 | 1397.15 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.99 | 52.07 | 01-JAN-08:50 | 1397.15 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 589.98 | 8395.70 | 01-JAN-08:40 | 44409.33 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 186.55 | 807.98 | 01-JAN-08:40 | 21646.15 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 186.55 | 807.98 | 01-JAN-08:40 | 21646.15 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 380.02 | 5410.51 | 01-JAN-07:50 | 28609.47 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 120.04 | 520.69 | 01-JAN-07:50 | 13940.01 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 120.04 | 520.69 | 01-JAN-07:50 | 13940.01 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 588.84 | 8395.84 | 01-JAN-08:00 | 44328.26 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 185.42 | 807.99 | 01-JAN-08:00 | 21564.73 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 185.42 | 807.99 | 01-JAN-08:00 | 21564.73 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 379.92 | 5410.48 | 01-JAN-08:50 | 28650.36 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 119.94 | 520.69 | 01-JAN-08:50 | 13980.99 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 119.94 | 520.69 | 01-JAN-08:50 | 13980.99 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 59.00 | 839.57 | 01-JAN-08:40 | 4440.72 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.66 | 80.80 | 01-JAN-08:40 | 2164.41 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.66 | 80.80 | 01-JAN-08:40 | 2164.41 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 38.00 | 541.05 | 01-JAN-07:50 | 2860.88 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.00 | 52.07 | 01-JAN-07:50 | 1393.93 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.00 | 52.07 | 01-JAN-07:50 | 1393.93 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 58.88 | 839.58 | 01-JAN-08:00 | 4432.62 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.54 | 80.80 | 01-JAN-08:00 | 2156.27 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.54 | 80.80 | 01-JAN-08:00 | 2156.27 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 37.99 | 541.05 | 01-JAN-08:50 | 2864.91 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.99 | 52.07 | 01-JAN-08:50 | 1397.97 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.99 | 52.07 | 01-JAN-08:50 | 1397.97 | 11-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7562.65 | 95237.01 | 01-JAN-00:10 | 385552.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1598.46 | 19775.43 | 01-JAN-00:10 | 83152.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 6533.09 | 8215.67 | 05-JAN-06:00 | 562660.38 | 22-JUN-15:40 |
HeatRejection:Electricity | 1974.33 | 4598.82 | 05-JAN-07:00 | 93058.23 | 06-MAR-14:40 |
General:HeatRejection:Electricity | 1974.33 | 4598.82 | 05-JAN-07:00 | 93058.23 | 06-MAR-14:40 |
Electricity:HVAC | 6371.55 | 82634.38 | 16-JAN-04:40 | 439378.88 | 07-JUL-14:50 |
ExteriorEquipment:Electricity | 1941.93 | 28795.69 | 01-JAN-00:10 | 118952.28 | 11-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 87.32 | 1613.62 | 01-JAN-00:10 | 5474.32 | 11-OCT-07:20 |
ElectricityPurchased:Facility | 34348.76 | 380994.45 | 01-JAN-10:20 | 2158800.56 | 07-AUG-15:20 |
ElectricityPurchased:Plant | 34348.76 | 380994.45 | 01-JAN-10:20 | 2158800.56 | 07-AUG-15:20 |
Cogeneration:ElectricityPurchased | 34348.76 | 380994.45 | 01-JAN-10:20 | 2158800.56 | 07-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 34348.76 | 380994.45 | 01-JAN-10:20 | 2158800.56 | 07-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 34348.76 | 380994.45 | 01-JAN-10:20 | 2158800.56 | 07-AUG-15:20 |
ElectricityNet:Plant | 34348.76 | 380994.45 | 01-JAN-10:20 | 2158800.56 | 07-AUG-15:20 |
Cogeneration:ElectricityNet | 34348.76 | 380994.45 | 01-JAN-10:20 | 2158800.56 | 07-AUG-15:20 |
General:Cogeneration:ElectricityNet | 34348.76 | 380994.45 | 01-JAN-10:20 | 2158800.56 | 07-AUG-15:20 |
Fans:Electricity | 2768.50 | 42538.82 | 11-JUN-15:00 | 245998.42 | 06-JUN-14:00 |
General:Fans:Electricity | 2768.50 | 42538.82 | 11-JUN-15:00 | 245998.42 | 06-JUN-14:00 |
ExteriorLights:Electricity | 670.70 | 0.00 | 01-JAN-07:20 | 54335.80 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 670.70 | 0.00 | 01-JAN-07:20 | 54335.80 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 6662.79 | 33742.87 | 08-JAN-07:00 | 583147.84 | 28-AUG-14:50 |
General:Cooling:Electricity | 6662.79 | 33742.87 | 08-JAN-07:00 | 583147.84 | 28-AUG-14:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 82.17 | 0.00 | 12-JAN-13:10 | 28596.21 | 22-DEC-06:00 |
General:Humidifier:Electricity | 82.17 | 0.00 | 12-JAN-13:10 | 28596.21 | 22-DEC-06:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 1329.53 | 3532.58 | 01-JAN-00:10 | 71743.86 | 28-AUG-05:10 |
General:Pumps:Electricity | 1329.53 | 3532.58 | 01-JAN-00:10 | 71743.86 | 28-AUG-05:10 |
WIRED_LTG_ELECTRICITY | 104.12 | 0.00 | 01-JAN-00:10 | 9682.07 | 11-OCT-07:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 581.58 | 5695.87 | 16-APR-15:00 | 229119.80 | 02-JAN-06:20 |
NaturalGas:Plant | 581.58 | 5695.87 | 16-APR-15:00 | 229119.80 | 02-JAN-06:20 |
Heating:NaturalGas | 22.01 | 0.00 | 01-JAN-00:10 | 207455.14 | 02-JAN-06:20 |
Boiler:Heating:NaturalGas | 22.01 | 0.00 | 01-JAN-00:10 | 207455.14 | 02-JAN-06:20 |
WaterSystems:NaturalGas | 559.57 | 5695.87 | 16-APR-15:00 | 72853.16 | 23-JAN-12:50 |
Water Heater:WaterSystems:NaturalGas | 559.57 | 5695.87 | 16-APR-15:00 | 72853.16 | 23-JAN-12:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 36544.29 | 166124.82 | 22-JAN-07:00 | 3175446.85 | 28-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 36544.29 | 166124.82 | 22-JAN-07:00 | 3175446.85 | 28-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 36544.29 | 166124.82 | 22-JAN-07:00 | 3175446.85 | 28-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 21473.87 | 0.00 | 11-MAR-00:20 | 0.00 | 19-APR-15:10 |
Water:HVAC | 30.57 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Humidifier:Water | 30.57 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
General:Humidifier:Water | 30.57 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
MainsWater:Facility | 21473.87 | 0.00 | 11-MAR-00:20 | 0.00 | 19-APR-15:10 |
MainsWater:HVAC | 30.57 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Humidifier:MainsWater | 30.57 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
General:Humidifier:MainsWater | 30.57 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Water:Plant | 21443.30 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-15:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 21443.30 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-15:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 19163.14 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-15:00 |
General:HeatRejection:Water | 19163.14 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-15:00 |
HeatRejection:MainsWater | 19163.14 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-15:00 |
General:HeatRejection:MainsWater | 19163.14 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-15:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 126050.24 | 230221.84 | 22-JAN-06:00 | 12410525.63 | 28-AUG-14:40 |
EnergyTransfer:Building | 23808.33 | 97452.71 | 08-JAN-08:00 | 1700887.49 | 27-APR-15:30 |
EnergyTransfer:Zone:BASEMENT | 803.12 | 0.00 | 01-JAN-00:10 | 76533.69 | 07-AUG-05:20 |
Heating:EnergyTransfer | 17.72 | 0.00 | 02-JAN-12:20 | 91697.74 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.77 | 0.00 | 01-JAN-00:10 | 33524.56 | 10-JUN-16:10 |
General:Heating:EnergyTransfer | 17.72 | 0.00 | 02-JAN-12:20 | 91697.74 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.77 | 0.00 | 01-JAN-00:10 | 33524.56 | 10-JUN-16:10 |
Cooling:EnergyTransfer | 23790.62 | 97291.08 | 01-JAN-07:40 | 1700887.49 | 27-APR-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 798.35 | 0.00 | 01-JAN-00:10 | 76533.69 | 07-AUG-05:20 |
General:Cooling:EnergyTransfer | 23790.62 | 97291.08 | 01-JAN-07:40 | 1700887.49 | 27-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 798.35 | 0.00 | 01-JAN-00:10 | 76533.69 | 07-AUG-05:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 802.22 | 0.00 | 01-JAN-00:10 | 60494.61 | 07-AUG-09:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 802.22 | 0.00 | 01-JAN-00:10 | 60494.61 | 07-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 802.22 | 0.00 | 01-JAN-00:10 | 60494.61 | 07-AUG-09:20 |
EnergyTransfer:Zone:CORE_MID | 6152.48 | 0.00 | 01-JAN-00:10 | 476404.24 | 05-SEP-09:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 6152.48 | 0.00 | 01-JAN-00:10 | 476404.24 | 05-SEP-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 6152.48 | 0.00 | 01-JAN-00:10 | 476404.24 | 05-SEP-09:20 |
EnergyTransfer:Zone:CORE_TOP | 629.07 | 0.00 | 01-JAN-00:10 | 59337.72 | 12-JUN-15:30 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.21 | 0.00 | 01-JAN-00:10 | 35320.08 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.21 | 0.00 | 01-JAN-00:10 | 35320.08 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 628.86 | 0.00 | 01-JAN-00:10 | 59337.72 | 12-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 628.86 | 0.00 | 01-JAN-00:10 | 59337.72 | 12-JUN-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 132.40 | 0.00 | 01-JAN-00:10 | 13056.35 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 132.40 | 0.00 | 01-JAN-00:10 | 13056.35 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 132.40 | 0.00 | 01-JAN-00:10 | 13056.35 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 99.04 | 0.00 | 01-JAN-00:10 | 12385.40 | 12-JUN-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 99.04 | 0.00 | 01-JAN-00:10 | 12385.40 | 12-JUN-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 99.04 | 0.00 | 01-JAN-00:10 | 12385.40 | 12-JUN-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 164.76 | 0.00 | 01-JAN-00:10 | 17047.26 | 02-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 164.76 | 0.00 | 01-JAN-00:10 | 17047.26 | 02-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 164.76 | 0.00 | 01-JAN-00:10 | 17047.26 | 02-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 147.66 | 0.00 | 01-JAN-00:10 | 16711.97 | 27-APR-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 147.66 | 0.00 | 01-JAN-00:10 | 16711.97 | 27-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 147.66 | 0.00 | 01-JAN-00:10 | 16711.97 | 27-APR-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1074.28 | 0.00 | 01-JAN-00:10 | 123083.58 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.01 | 0.00 | 01-JAN-00:10 | 6322.33 | 21-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.01 | 0.00 | 01-JAN-00:10 | 6322.33 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1074.28 | 0.00 | 01-JAN-00:10 | 123083.58 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1074.28 | 0.00 | 01-JAN-00:10 | 123083.58 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 892.66 | 0.00 | 01-JAN-00:10 | 123379.75 | 03-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 3371.48 | 21-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 3371.48 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 892.65 | 0.00 | 01-JAN-00:10 | 123379.75 | 03-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 892.65 | 0.00 | 01-JAN-00:10 | 123379.75 | 03-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1427.09 | 0.00 | 01-JAN-00:10 | 165566.51 | 02-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1427.09 | 0.00 | 01-JAN-00:10 | 165566.51 | 02-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1427.09 | 0.00 | 01-JAN-00:10 | 165566.51 | 02-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 964.21 | 0.00 | 01-JAN-00:10 | 137298.53 | 06-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 130.06 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 130.06 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 964.21 | 0.00 | 01-JAN-00:10 | 137298.53 | 06-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 964.21 | 0.00 | 01-JAN-00:10 | 137298.53 | 06-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 116.34 | 0.00 | 01-JAN-00:10 | 14404.07 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.76 | 0.00 | 01-JAN-00:10 | 11246.70 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.76 | 0.00 | 01-JAN-00:10 | 11246.70 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 115.58 | 0.00 | 01-JAN-00:10 | 14404.07 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 115.58 | 0.00 | 01-JAN-00:10 | 14404.07 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 95.40 | 0.00 | 01-JAN-00:10 | 13503.04 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.28 | 0.00 | 01-JAN-00:10 | 7016.81 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.28 | 0.00 | 01-JAN-00:10 | 7016.81 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 95.12 | 0.00 | 01-JAN-00:10 | 13503.04 | 12-JUN-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 95.12 | 0.00 | 01-JAN-00:10 | 13503.04 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 149.57 | 0.00 | 01-JAN-00:10 | 18704.39 | 02-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.17 | 0.00 | 01-JAN-00:10 | 8480.98 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.17 | 0.00 | 01-JAN-00:10 | 8480.98 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 149.40 | 0.00 | 01-JAN-00:10 | 18704.39 | 02-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 149.40 | 0.00 | 01-JAN-00:10 | 18704.39 | 02-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 102.27 | 0.00 | 01-JAN-00:10 | 15121.03 | 06-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.16 | 0.00 | 01-JAN-00:10 | 5322.09 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.16 | 0.00 | 01-JAN-00:10 | 5322.09 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 102.10 | 0.00 | 01-JAN-00:10 | 15121.03 | 06-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 102.10 | 0.00 | 01-JAN-00:10 | 15121.03 | 06-JUN-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 125.18 | 0.00 | 01-JAN-00:10 | 14842.18 | 07-AUG-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.77 | 0.00 | 01-JAN-00:10 | 3072.99 | 24-DEC-10:50 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.77 | 0.00 | 01-JAN-00:10 | 3072.99 | 24-DEC-10:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 124.40 | 0.00 | 01-JAN-00:10 | 14842.18 | 07-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 124.40 | 0.00 | 01-JAN-00:10 | 14842.18 | 07-AUG-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 966.55 | 0.00 | 01-JAN-00:10 | 102157.26 | 05-JUL-15:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.95 | 0.00 | 01-JAN-00:10 | 21829.92 | 12-FEB-13:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.95 | 0.00 | 01-JAN-00:10 | 21829.92 | 12-FEB-13:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 961.61 | 0.00 | 01-JAN-00:10 | 102157.26 | 05-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 961.61 | 0.00 | 01-JAN-00:10 | 102157.26 | 05-JUL-15:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 169.34 | 0.00 | 01-JAN-00:10 | 31890.04 | 12-JUN-13:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.56 | 0.00 | 01-JAN-00:10 | 15109.25 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.56 | 0.00 | 01-JAN-00:10 | 15109.25 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 163.78 | 0.00 | 01-JAN-00:10 | 31890.04 | 12-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 163.78 | 0.00 | 01-JAN-00:10 | 31890.04 | 12-JUN-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.58 | 1129.53 | 07-JAN-08:00 | 7751.97 | 16-APR-22:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.58 | 1129.53 | 07-JAN-08:00 | 7751.97 | 16-APR-22:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.58 | 1129.53 | 07-JAN-08:00 | 7751.97 | 16-APR-22:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1331.36 | 6147.12 | 01-JAN-07:50 | 73381.61 | 12-APR-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1331.36 | 6147.12 | 01-JAN-07:50 | 73381.61 | 12-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1331.36 | 6147.12 | 01-JAN-07:50 | 73381.61 | 12-APR-16:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 130.21 | 4.65 | 29-JAN-01:50 | 7474.21 | 12-APR-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.06 | 0.00 | 02-JAN-11:00 | 329.09 | 01-JAN-14:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.06 | 0.00 | 02-JAN-11:00 | 329.09 | 01-JAN-14:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 130.15 | 0.00 | 01-JAN-00:10 | 7474.21 | 12-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 130.15 | 0.00 | 01-JAN-00:10 | 7474.21 | 12-APR-16:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7189.54 | 88610.81 | 14-MAY-02:00 | 369990.54 | 15-AUG-23:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7189.54 | 88610.81 | 14-MAY-02:00 | 369990.54 | 15-AUG-23:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7189.54 | 88610.81 | 14-MAY-02:00 | 369990.54 | 15-AUG-23:50 |
PlantLoopHeatingDemand:Facility | 307.79 | 0.00 | 01-JAN-00:10 | 168761.40 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 293.17 | 0.00 | 01-JAN-00:10 | 40154.25 | 17-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 293.17 | 0.00 | 01-JAN-00:10 | 40154.25 | 17-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 293.17 | 0.00 | 01-JAN-00:10 | 40154.25 | 17-JAN-12:10 |
EnergyTransfer:HVAC | 33125.35 | 132363.64 | 22-JAN-07:00 | 2977459.74 | 28-AUG-14:40 |
HeatingCoils:EnergyTransfer | 14.62 | 0.00 | 01-JAN-00:10 | 163820.71 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 14.62 | 0.00 | 01-JAN-00:10 | 163820.71 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 14.62 | 0.00 | 01-JAN-00:10 | 163820.71 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 33110.73 | 132363.64 | 22-JAN-07:00 | 2977459.74 | 28-AUG-14:40 |
EnergyTransfer:Plant | 69116.55 | 0.00 | 01-JAN-00:10 | 8079045.27 | 22-JUN-15:40 |
LoopToLoop:EnergyTransfer | 23379.69 | 0.00 | 01-JAN-00:10 | 2545254.36 | 22-JUN-15:40 |
WaterSystems:EnergyTransfer | 293.17 | 0.00 | 01-JAN-00:10 | 40154.25 | 17-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 293.17 | 0.00 | 01-JAN-00:10 | 40154.25 | 17-JAN-12:10 |
Boilers:EnergyTransfer | 14.31 | 0.00 | 01-JAN-00:10 | 155766.48 | 02-JAN-06:20 |
Chillers:EnergyTransfer | 21100.08 | 0.00 | 01-JAN-00:10 | 2557582.00 | 22-JUN-15:40 |
HeatRejection:EnergyTransfer | 24329.30 | 0.00 | 01-JAN-00:10 | 2956607.79 | 22-JUN-15:40 |
General:HeatRejection:EnergyTransfer | 24329.30 | 0.00 | 01-JAN-00:10 | 2956607.79 | 22-JUN-15:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.770 | -798.351 | 0.000 | 0.000 | 92.651 | 240.449 | 424.397 | 0.000 | 0.000 | 0.000 | 36.085 | 0.000 | 0.000 | 0.000 | 0.000 | -0.014 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -802.218 | 0.000 | 0.000 | 83.411 | 215.940 | 321.286 | 0.000 | 0.000 | 0.000 | 181.583 | 0.000 | 0.000 | 0.000 | 0.000 | -0.008 |
CORE_MID | 0.000 | 0.000 | 0.000 | -6152.465 | 0.000 | 0.000 | 835.283 | 2159.397 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.032 | 0.000 | 0.000 | 0.000 | 0.000 | -55.061 |
CORE_TOP | 0.000 | 0.000 | 0.214 | -628.853 | 0.000 | 0.000 | 84.143 | 215.940 | 321.285 | 0.000 | 0.000 | 0.000 | 7.271 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -132.396 | 0.000 | 0.000 | 10.540 | 18.636 | 40.342 | 42.541 | 0.000 | 0.652 | 41.018 | 0.000 | -20.977 | 0.000 | -0.356 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -99.037 | 0.000 | 0.000 | 6.788 | 12.000 | 25.998 | 50.547 | 0.000 | 0.444 | 16.197 | 0.000 | -12.702 | 0.000 | -0.234 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -164.757 | 0.000 | 0.000 | 10.493 | 18.528 | 40.343 | 90.446 | 0.000 | 0.637 | 25.103 | 0.000 | -20.408 | 0.000 | -0.387 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -147.657 | 0.000 | 0.000 | 6.760 | 11.990 | 25.998 | 49.064 | 0.000 | 0.407 | 69.750 | 0.000 | -16.031 | 0.000 | -0.281 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.009 | -1074.265 | 0.000 | 0.000 | 107.061 | 186.553 | 403.423 | 435.888 | 0.000 | 14.732 | 127.101 | 0.000 | -193.035 | 0.000 | -7.466 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.005 | -892.646 | 0.000 | 0.000 | 50.394 | 120.037 | 259.981 | 504.998 | 0.000 | 9.674 | 76.251 | 0.000 | -123.408 | 0.000 | -5.286 | -0.007 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1427.078 | 0.000 | 0.000 | 105.134 | 185.416 | 403.429 | 904.975 | 0.000 | 14.222 | 25.811 | 0.000 | -202.804 | 0.000 | -9.104 | -0.001 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -964.198 | 0.000 | 0.000 | 68.805 | 119.941 | 259.979 | 506.840 | 0.000 | 9.480 | 142.076 | 0.000 | -137.406 | 0.000 | -5.517 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.760 | -115.578 | 0.000 | 0.000 | 10.889 | 18.655 | 40.342 | 43.524 | 0.000 | 1.804 | 18.115 | 0.000 | -17.696 | 0.000 | -0.815 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.283 | -95.119 | 0.000 | 0.000 | 6.926 | 12.004 | 25.998 | 50.396 | 0.000 | 1.172 | 10.508 | 0.000 | -11.571 | 0.000 | -0.597 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.169 | -149.395 | 0.000 | 0.000 | 10.606 | 18.542 | 40.343 | 90.259 | 0.000 | 1.735 | 7.902 | 0.000 | -19.113 | 0.000 | -1.047 | -0.002 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.165 | -102.102 | 0.000 | 0.000 | 6.973 | 11.994 | 25.998 | 50.555 | 0.000 | 1.166 | 18.780 | 0.000 | -12.899 | 0.000 | -0.630 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -143.584 | 0.000 | 0.000 | 0.938 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -17.199 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1331.365 | 0.000 | 0.000 | 9.390 | 59.652 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -276.483 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.062 | -130.152 | 0.000 | 0.000 | 0.943 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -30.698 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7189.558 | 0.000 | 0.000 | 19.442 | 67.796 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -392.538 |
GROUNDFLOOR_PLENUM | 0.772 | -124.404 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.181 | 123.257 | 0.000 | 0.000 | 0.000 | -0.807 | -0.000 |
MIDFLOOR_PLENUM | 4.946 | -961.602 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21.298 | 949.149 | 0.000 | 0.000 | 0.000 | -13.792 | -0.000 |
TOPFLOOR_PLENUM | 5.563 | -163.776 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.208 | 157.380 | 0.000 | 0.000 | 0.000 | -1.375 | -0.001 |
Total Facility | 11.282 | -1249.782 | 6.437 | -22540.774 | 0.000 | 0.000 | 1527.567 | 3705.397 | 15213.411 | 2820.034 | 0.000 | 80.813 | 2033.371 | 0.000 | -788.051 | 0.000 | -47.692 | -772.016 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-FEB-04:02 | 0.00 | 0.00 | 0.00 | -109231.06 | 0.00 | 0.00 | 0.00 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 94607.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 | -99789.01 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.15 | 0.00 | 0.00 | 0.00 | 90684.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 27-FEB-04:02 | 0.00 | 0.00 | 0.00 | -890837.08 | 0.00 | 0.00 | 0.00 | 10475.32 | 80571.20 | 0.00 | 0.00 | 0.00 | 799790.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 11-SEP-03:02 | 0.00 | 0.00 | 0.00 | -91301.90 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.12 | 0.00 | 0.00 | 0.00 | 82197.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 02-JUL-16:21 | 0.00 | 0.00 | 0.00 | -21466.24 | 0.00 | 0.00 | 39.58 | 80.80 | 758.77 | 5390.93 | 0.00 | 171.23 | 15024.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-08:51 | 0.00 | 0.00 | 0.00 | -17868.71 | 0.00 | 0.00 | 21.52 | 52.07 | 488.98 | 11250.29 | 0.00 | 222.01 | 5833.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-12:52 | 0.00 | 0.00 | 0.00 | -23066.86 | 0.00 | 0.00 | 35.04 | 80.80 | 758.78 | 14069.67 | 0.00 | 13.28 | 8109.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JUL-16:21 | 0.00 | 0.00 | 0.00 | -24559.73 | 0.00 | 0.00 | 18.06 | 52.07 | 488.98 | 10410.88 | 0.00 | 97.32 | 13492.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 28-MAY-15:31 | 0.00 | 0.00 | 0.00 | -207574.06 | 0.00 | 0.00 | 392.53 | 807.98 | 7587.73 | 50272.25 | 0.00 | 12620.26 | 135893.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-08:51 | 0.00 | 0.00 | 0.00 | -185364.56 | 0.00 | 0.00 | 210.24 | 520.69 | 4889.82 | 111631.50 | 0.00 | 4952.86 | 63159.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-13:11 | 0.00 | 0.00 | 0.00 | -228705.66 | 0.00 | 0.00 | 331.45 | 807.99 | 7587.84 | 146075.27 | 0.00 | 1502.42 | 72400.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 28-MAY-15:31 | 0.00 | 0.00 | 0.00 | -206359.79 | 0.00 | 0.00 | 186.46 | 520.69 | 4889.79 | 126275.94 | 0.00 | 7377.21 | 67109.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JUL-13:12 | 0.00 | 0.00 | 0.00 | -23767.01 | 0.00 | 0.00 | 38.41 | 80.80 | 758.77 | 4759.96 | 0.00 | 634.05 | 17495.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 30-APR-10:02 | 0.00 | 0.00 | 0.00 | -19303.98 | 0.00 | 0.00 | 21.97 | 52.07 | 488.98 | 9143.91 | 0.00 | 94.15 | 9502.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-15:21 | 0.00 | 0.00 | 0.00 | -26295.84 | 0.00 | 0.00 | 32.42 | 80.80 | 758.78 | 8340.73 | 0.00 | 148.10 | 16935.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 28-MAY-16:31 | 0.00 | 0.00 | 0.00 | -21894.95 | 0.00 | 0.00 | 15.63 | 52.07 | 488.98 | 11229.91 | 0.00 | 893.41 | 9214.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-22:35 | 0.00 | 0.00 | 0.00 | -7756.40 | 0.00 | 0.00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -66.96 |
DATACENTER_MID_ZN_6 | 12-APR-16:00 | 0.00 | 0.00 | 0.00 | -73376.97 | 0.00 | 0.00 | 993.76 | 5208.47 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10769.47 |
DATACENTER_TOP_ZN_6 | 16-APR-20:52 | 0.00 | 0.00 | 0.00 | -7487.81 | 0.00 | 0.00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -335.55 |
DATACENTER_BASEMENT_ZN_6 | 15-AUG-23:42 | 0.00 | 0.00 | 0.00 | -370173.97 | 0.00 | 0.00 | 0.00 | 328.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9787.44 |
GROUNDFLOOR_PLENUM | 03-JUL-05:13 | 0.00 | -19317.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.88 | 19241.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-JUL-05:02 | 0.00 | -143773.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 929.83 | 142843.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 12-JUN-13:50 | 0.00 | -31891.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.39 | 31523.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-APR-05:02 | 0.00 | -88134.89 | 0.00 | -2165464.61 | 0.00 | 0.00 | 15599.09 | 39207.80 | 623236.89 | 0.00 | 0.00 | 0.00 | 1606915.55 | 0.00 | -31355.54 | 0.00 | -4.30 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 10-JUN-16:01 | 0.00 | 0.00 | 35445.80 | 0.00 | 0.00 | 0.00 | 520.12 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -50589.89 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:01 | 0.00 | 0.00 | 61811.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2095.06 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -71963.61 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 21-DEC-06:02 | 0.00 | 0.00 | 31611.91 | 0.00 | 0.00 | 0.00 | 1418.66 | 2630.56 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35244.56 | 0.00 | -103.66 | -10429.89 |
PERIMETER_MID_ZN_2 | 21-DEC-06:02 | 0.00 | 0.00 | 16857.55 | 0.00 | 0.00 | 0.00 | 914.61 | 1695.23 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23478.36 | 0.00 | -69.09 | -2439.69 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JAN-06:06 | 0.00 | 0.00 | 636.34 | 0.00 | 0.00 | 0.00 | 871.44 | 1695.23 | 6519.72 | 0.00 | 0.00 | 0.00 | 12438.60 | 0.00 | -22161.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JAN-04:02 | 0.00 | 0.00 | 16886.51 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2285.30 | 0.00 | 0.00 | -15744.43 |
PERIMETER_TOP_ZN_2 | 02-JAN-04:02 | 0.00 | 0.00 | 11556.07 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1562.58 | 0.00 | 0.00 | -10730.22 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 16403.13 | 0.00 | 0.00 | 0.00 | 0.00 | 263.06 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2556.55 | 0.00 | 0.00 | -15121.36 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 11135.95 | 0.00 | 0.00 | 0.00 | 0.00 | 169.52 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1712.87 | 0.00 | 0.00 | -10244.57 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 01-JAN-14:00 | 0.00 | 0.00 | 334.99 | 0.00 | 0.00 | 0.00 | 6.16 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2318.70 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 29-DEC-04:02 | 10769.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -582.05 | -10187.56 |
MIDFLOOR_PLENUM | 11-SEP-03:02 | 97402.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -97402.57 |
TOPFLOOR_PLENUM | 27-FEB-06:03 | 19838.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -22.62 | -19815.44 |
Total Facility | 02-JAN-06:01 | -1124064.14 | 1208717.09 | 113117.65 | -1208717.09 | 0.00 | 0.00 | 17496.38 | 39207.80 | 268362.69 | 0.00 | 0.00 | 0.00 | 816459.66 | 0.00 | -130580.04 | 0.00 | 0.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.9478 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.3191 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 103.7899 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 97.6621 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.1221 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.0302 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.0003 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.0003 | 0.2000 | 1.0000 | Not calculated | 1.2002 | 0.2000 | ||
AIRLOOP DATACENTER BASEMENT | 21.9691 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.9694 | 0.0154 | 1.0000 | Not calculated | 0.3384 | 0.0154 | ||
AIRLOOP DATACENTER BOT | 0.4903 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4903 | 0.0319 | 1.0000 | Not calculated | 0.0156 | 0.0319 | ||
AIRLOOP DATACENTER MID | 4.6697 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6697 | 0.0335 | 1.0000 | Not calculated | 0.1563 | 0.0335 | ||
AIRLOOP DATACENTER TOP | 0.4698 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4698 | 0.0333 | 1.0000 | Not calculated | 0.0156 | 0.0333 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.4739 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.3600 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 51.8950 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 32.5719 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.5611 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.5021 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.0003 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.0003 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2000 | ||
AIRLOOP DATACENTER BASEMENT | 21.9691 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.9691 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0154 | ||
AIRLOOP DATACENTER BOT | 0.4903 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4903 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0319 | ||
AIRLOOP DATACENTER MID | 4.6697 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6697 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0335 | ||
AIRLOOP DATACENTER TOP | 0.4698 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4698 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0333 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.0003 | 6.0003 | 6.0003 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3046 | 6.3046 | 1.9670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 59.7906 | 59.7906 | 19.3722 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1299 | 6.1299 | 2.0045 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2179 | 1.2179 | 0.3654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9497 | 0.9497 | 0.2849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2391 | 1.2391 | 0.3717 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2365 | 1.2365 | 0.3709 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.8065 | 11.8065 | 3.5419 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.8022 | 9.8022 | 2.9407 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.9119 | 11.9119 | 3.5736 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.4788 | 10.4788 | 3.1436 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3809 | 1.3809 | 0.4143 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0474 | 1.0474 | 0.3142 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3838 | 1.3838 | 0.4151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1801 | 1.1801 | 0.3540 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4903 | 0.4903 | 0.4903 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6697 | 4.6697 | 4.6697 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4698 | 0.4698 | 0.4698 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.9691 | 21.9691 | 21.9691 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.9478 | 10.3191 | 10.9478 | 3.3600 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 103.7899 | 97.6621 | 103.7899 | 32.5719 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.1221 | 11.0302 | 11.1221 | 3.5021 | 0.0000 | 1.0000 |
CAV_BAS | 6.0003 | 6.0003 | 6.0003 | 6.0003 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.9691 | 21.9694 | 21.9691 | 21.9691 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4903 | 0.4903 | 0.4903 | 0.4903 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6697 | 4.6697 | 4.6697 | 4.6697 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4698 | 0.4698 | 0.4698 | 0.4698 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.0003 | 6.0003 | 6.0003 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1523 | 3.1523 | 1.9670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 29.8953 | 29.8953 | 19.3722 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0650 | 3.0650 | 2.0045 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6090 | 0.6090 | 0.3654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4749 | 0.4749 | 0.2849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6195 | 0.6195 | 0.3717 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6182 | 0.6182 | 0.3709 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9032 | 5.9032 | 3.5419 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9011 | 4.9011 | 2.9407 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9559 | 5.9559 | 3.5736 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2394 | 5.2394 | 3.1436 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6904 | 0.6904 | 0.4143 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5237 | 0.5237 | 0.3142 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6919 | 0.6919 | 0.4151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5900 | 0.5900 | 0.3540 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4903 | 0.4903 | 0.4903 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6697 | 4.6697 | 4.6697 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4698 | 0.4698 | 0.4698 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.9691 | 21.9691 | 21.9691 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.4739 | 3.3600 | 3.3600 | 3.3600 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 51.8950 | 32.5719 | 32.5719 | 32.5719 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.5611 | 3.5021 | 3.5021 | 3.5021 | 0.0000 | 1.0000 |
CAV_BAS | 6.0003 | 6.0003 | 6.0003 | 6.0003 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.9691 | 21.9691 | 21.9691 | 21.9691 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4903 | 0.4903 | 0.4903 | 0.4903 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6697 | 4.6697 | 4.6697 | 4.6697 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4698 | 0.4698 | 0.4698 | 0.4698 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1069.17 |
Number of hours not met | 1069.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 22.01 | 207455.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6662.79 | 583147.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3705.40 | 344557.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 670.70 | 54335.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.32 | 5474.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2768.50 | 245998.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1329.53 | 71743.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1974.33 | 93058.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 82.17 | 28596.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 559.57 | 72853.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 34348.76 |
Natural Gas | 0.00 | 581.58 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 34930.34 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 79.99 |
Space Heating | 0.00 |
Space Cooling | 143.84 |
Fans (All) | 59.77 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 741.55 |
Subtotal | 741.55 |
Natural Gas [MJ/m2] | |
Space Heating | 0.48 |
Service Water Heating | 12.08 |
Miscellaneous (All) | 12.56 |
Subtotal | 12.56 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.61 |
Space Heating | 0.06 |
Space Cooling | 19.07 |
Fans (All) | 7.93 |
Service Water Heating | 1.60 |
Receptacle Equipment | 43.55 |
Miscellaneous | 17.17 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2645. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7320.33 | 1439.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8633.33 | 126.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8749.50 | 10.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8740.33 | 19.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8698.00 | 62.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8679.67 | 80.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8584.67 | 175.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7827.67 | 932.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8521.33 | 238.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8421.00 | 339.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8207.67 | 552.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8014.00 | 746.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8489.50 | 270.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8374.67 | 385.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8212.50 | 547.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8091.33 | 668.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6201.00 | 2559.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6191.00 | 2569.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6778.17 | 1981.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7285.17 | 1474.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8309.00 | 451.00 | 0.00 | 0.00 | 0.00 |
Min | 6191.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2569.00 | 0.00 | 0.00 | 0.00 |
Average | 8080.08 | 679.92 | 0.00 | 0.00 | 0.00 |
Sum | 185841.83 | 15638.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 365035.50 | 3580.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330570.00 | 243.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330790.00 | 23.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330786.00 | 27.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1360.17 | 907.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1348.67 | 919.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1506.17 | 761.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 82005.17 | 21389.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 365035.50 | 21389.83 | 0.00 | 0.00 | 0.00 |
Average | 79123.94 | 1210.97 | 0.00 | 0.00 | 0.00 |
Sum | 1819850.67 | 27852.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 5379.33 | 3380.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7243.83 | 1516.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7392.33 | 1367.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7270.17 | 1489.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7173.33 | 1586.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7548.83 | 1211.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6879.17 | 1880.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6441.17 | 2318.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6985.83 | 1774.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6946.33 | 1813.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6658.67 | 2101.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6785.83 | 1974.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7023.33 | 1736.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6935.17 | 1824.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6713.00 | 2047.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6835.67 | 1924.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7153.17 | 1606.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7143.17 | 1616.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7542.50 | 1217.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7549.50 | 1210.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 6158.33 | 2601.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5782.17 | 2977.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4774.50 | 3985.50 | 0.00 | 0.00 | 0.00 |
Min | 4774.50 | 1210.50 | 0.00 | 0.00 | 0.00 |
Max | 7549.50 | 3985.50 | 0.00 | 0.00 | 0.00 |
Average | 6796.32 | 1963.68 | 0.00 | 0.00 | 0.00 |
Sum | 156315.33 | 45164.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 335155.67 | 33460.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 328051.67 | 2761.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328380.17 | 2432.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 327806.00 | 3007.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38923.50 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18353.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38923.50 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38923.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38923.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1655.83 | 612.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1646.33 | 621.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1792.50 | 475.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 87390.67 | 16004.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 335155.67 | 33460.33 | 0.00 | 0.00 | 0.00 |
Average | 77753.14 | 2581.78 | 0.00 | 0.00 | 0.00 |
Sum | 1788322.17 | 59380.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:25
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.618984E+11 | 103951.05 | 02-JAN-04:02 | 6.67 | 6.44 | 0.567015E+10 | 7499.04 | 04-JAN-10:39 | 14.27 | 11.27 |
February | 0.551110E+11 | 109229.72 | 06-FEB-04:02 | 10.55 | 9.45 | 0.514293E+10 | 7499.07 | 02-FEB-10:09 | 10.55 | 9.45 |
March | 0.633248E+11 | 99597.32 | 20-MAR-03:02 | 16.45 | 11.38 | 0.613622E+10 | 7499.00 | 16-MAR-09:00 | 16.45 | 11.38 |
April | 0.593189E+11 | 103960.08 | 28-APR-03:02 | 28.85 | 17.10 | 0.545287E+10 | 7499.03 | 04-APR-09:09 | 28.85 | 17.10 |
May | 0.633768E+11 | 101121.25 | 29-MAY-17:30 | 40.55 | 21.29 | 0.590449E+10 | 7498.86 | 05-MAY-09:00 | 40.55 | 21.29 |
June | 0.661049E+11 | 97197.30 | 04-JUN-16:18 | 42.13 | 22.34 | 0.588556E+10 | 7498.86 | 07-JUN-09:20 | 37.90 | 20.70 |
July | 0.701452E+11 | 90226.06 | 04-JUL-17:50 | 40.15 | 24.18 | 0.547769E+10 | 7498.75 | 27-JUL-13:20 | 30.70 | 26.49 |
August | 0.800719E+11 | 89891.21 | 22-AUG-03:02 | 25.88 | 25.10 | 0.614087E+10 | 7498.73 | 24-AUG-09:20 | 29.43 | 26.79 |
September | 0.701609E+11 | 91295.74 | 26-SEP-03:02 | 25.65 | 21.91 | 0.545596E+10 | 7498.75 | 15-SEP-13:20 | 25.65 | 21.91 |
October | 0.723871E+11 | 101896.69 | 22-OCT-14:58 | 31.00 | 17.63 | 0.567501E+10 | 7498.92 | 17-OCT-09:30 | 31.00 | 17.63 |
November | 0.695645E+11 | 100328.77 | 25-NOV-04:02 | 10.85 | 9.43 | 0.561917E+10 | 7498.96 | 09-NOV-10:09 | 10.85 | 9.43 |
December | 0.668903E+11 | 104029.50 | 04-DEC-04:02 | 8.72 | 8.07 | 0.547563E+10 | 7498.95 | 13-DEC-10:20 | 18.53 | 13.02 |
Annual Sum or Average | 0.798355E+12 | 0.680365E+11 | ||||||||
Minimum of Months | 0.551110E+11 | 89891.21 | 6.67 | 6.44 | 0.514293E+10 | 7498.73 | 10.55 | 9.43 | ||
Maximum of Months | 0.800719E+11 | 109229.72 | 42.13 | 25.10 | 0.614087E+10 | 7499.07 | 40.55 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487554E+11 | 99916.88 | 02-JAN-04:02 | 6.67 | 6.44 | 0.508167E+10 | 6734.74 | 09-JAN-10:09 | 12.05 | 10.60 |
February | 0.504797E+11 | 99228.75 | 27-FEB-04:02 | 11.72 | 10.91 | 0.460714E+10 | 6734.76 | 02-FEB-10:09 | 11.72 | 10.91 |
March | 0.686045E+11 | 96286.94 | 20-MAR-03:02 | 16.45 | 11.38 | 0.549929E+10 | 6734.76 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.751122E+11 | 91047.23 | 03-APR-05:03 | 22.60 | 18.05 | 0.487679E+10 | 6734.75 | 04-APR-09:09 | 26.87 | 18.01 |
May | 0.709245E+11 | 90543.43 | 23-MAY-03:02 | 28.47 | 24.77 | 0.528197E+10 | 6734.55 | 08-MAY-13:09 | 28.47 | 24.77 |
June | 0.723878E+11 | 89334.66 | 12-JUN-05:02 | 34.12 | 19.12 | 0.526629E+10 | 6734.60 | 12-JUN-13:09 | 43.40 | 22.40 |
July | 0.755286E+11 | 88616.29 | 03-JUL-05:05 | 29.37 | 24.69 | 0.489326E+10 | 6734.54 | 17-JUL-13:00 | 33.90 | 27.72 |
August | 0.852228E+11 | 89718.17 | 07-AUG-05:01 | 29.53 | 24.79 | 0.549526E+10 | 6734.54 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.645272E+11 | 92135.53 | 09-SEP-03:02 | 24.35 | 23.85 | 0.488218E+10 | 6734.55 | 05-SEP-09:09 | 24.35 | 23.85 |
October | 0.679997E+11 | 96183.40 | 31-OCT-03:02 | 16.50 | 14.83 | 0.507809E+10 | 6734.66 | 24-OCT-09:09 | 16.50 | 14.83 |
November | 0.634625E+11 | 98643.62 | 27-NOV-04:02 | 10.65 | 9.14 | 0.503182E+10 | 6734.70 | 16-NOV-10:09 | 10.65 | 9.14 |
December | 0.592137E+11 | 97215.02 | 04-DEC-04:02 | 8.72 | 8.07 | 0.490419E+10 | 6734.72 | 18-DEC-10:00 | 21.70 | 14.67 |
Annual Sum or Average | 0.802218E+12 | 0.608980E+11 | ||||||||
Minimum of Months | 0.487554E+11 | 88616.29 | 6.67 | 6.44 | 0.460714E+10 | 6734.54 | 10.65 | 9.14 | ||
Maximum of Months | 0.852228E+11 | 99916.88 | 34.12 | 24.79 | 0.549929E+10 | 6734.76 | 43.40 | 27.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.373440E+11 | 84447.06 | 14-JAN-06:02 | 14.50 | 12.49 | 0.504779E+10 | 6734.71 | 04-JAN-10:00 | 14.50 | 12.49 |
February | 0.386929E+11 | 89117.55 | 27-FEB-04:02 | 11.72 | 10.91 | 0.458968E+10 | 6734.74 | 02-FEB-10:09 | 11.72 | 10.91 |
March | 0.525900E+11 | 88362.11 | 14-MAR-03:02 | 20.88 | 16.42 | 0.549435E+10 | 6734.76 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.550784E+11 | 88104.09 | 10-APR-03:02 | 18.93 | 13.53 | 0.487506E+10 | 6734.75 | 04-APR-09:09 | 18.93 | 13.53 |
May | 0.611170E+11 | 85296.08 | 23-MAY-03:02 | 28.47 | 24.77 | 0.527746E+10 | 6734.64 | 01-MAY-09:20 | 28.47 | 24.77 |
June | 0.596061E+11 | 85511.90 | 28-JUN-03:02 | 26.40 | 25.45 | 0.526387E+10 | 6734.62 | 12-JUN-13:09 | 26.40 | 25.45 |
July | 0.579266E+11 | 86492.59 | 19-JUL-03:02 | 23.42 | 23.42 | 0.488985E+10 | 6734.56 | 18-JUL-13:09 | 23.42 | 23.42 |
August | 0.598551E+11 | 85206.90 | 24-AUG-03:02 | 25.58 | 24.96 | 0.549398E+10 | 6734.56 | 21-AUG-13:09 | 25.58 | 24.96 |
September | 0.532801E+11 | 86005.11 | 05-SEP-03:02 | 26.38 | 25.08 | 0.488087E+10 | 6734.57 | 08-SEP-13:30 | 28.50 | 25.88 |
October | 0.535129E+11 | 88145.15 | 24-OCT-03:02 | 18.57 | 14.45 | 0.507382E+10 | 6734.66 | 16-OCT-09:09 | 18.57 | 14.45 |
November | 0.468661E+11 | 85450.51 | 21-NOV-05:03 | 13.53 | 10.41 | 0.502049E+10 | 6734.70 | 06-NOV-10:09 | 13.53 | 10.41 |
December | 0.393783E+11 | 84218.72 | 16-DEC-06:02 | 14.32 | 11.10 | 0.487296E+10 | 6734.67 | 13-DEC-10:09 | 14.32 | 11.10 |
Annual Sum or Average | 0.615248E+12 | 0.607802E+11 | ||||||||
Minimum of Months | 0.373440E+11 | 84218.72 | 11.72 | 10.41 | 0.458968E+10 | 6734.56 | 11.72 | 10.41 | ||
Maximum of Months | 0.611170E+11 | 89117.55 | 28.47 | 25.45 | 0.549435E+10 | 6734.76 | 28.50 | 25.88 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273149E+11 | 38168.36 | 26-JAN-16:20 | 19.67 | 13.02 | 0.474876E+10 | 6734.60 | 13-JAN-10:00 | 19.67 | 13.02 |
February | 0.321693E+11 | 83378.14 | 23-FEB-06:03 | 15.05 | 13.57 | 0.449975E+10 | 6734.64 | 24-FEB-10:09 | 20.63 | 14.93 |
March | 0.510000E+11 | 90633.37 | 30-MAR-03:02 | 21.95 | 16.80 | 0.547620E+10 | 6734.75 | 27-MAR-09:09 | 21.95 | 16.80 |
April | 0.609669E+11 | 88943.51 | 17-APR-05:03 | 24.22 | 18.83 | 0.487673E+10 | 6734.74 | 04-APR-09:09 | 24.22 | 18.83 |
May | 0.715239E+11 | 88053.44 | 30-MAY-05:02 | 30.25 | 21.57 | 0.528342E+10 | 6734.59 | 01-MAY-09:09 | 30.25 | 21.57 |
June | 0.701220E+11 | 89421.07 | 12-JUN-05:02 | 34.12 | 19.12 | 0.526811E+10 | 6734.62 | 12-JUN-13:09 | 43.40 | 22.40 |
July | 0.669360E+11 | 88435.22 | 28-JUL-03:02 | 27.00 | 25.79 | 0.489626E+10 | 6734.53 | 17-JUL-13:00 | 27.00 | 25.79 |
August | 0.671953E+11 | 90084.88 | 21-AUG-03:02 | 25.87 | 25.24 | 0.549750E+10 | 6734.54 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.578177E+11 | 91320.89 | 11-SEP-03:02 | 26.07 | 25.28 | 0.488246E+10 | 6734.54 | 08-SEP-13:00 | 26.07 | 25.28 |
October | 0.535585E+11 | 89812.63 | 05-OCT-03:02 | 22.73 | 17.70 | 0.506646E+10 | 6734.65 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.405833E+11 | 85308.42 | 01-NOV-05:02 | 15.60 | 12.04 | 0.497118E+10 | 6734.68 | 06-NOV-10:09 | 23.13 | 17.24 |
December | 0.296680E+11 | 64695.22 | 29-DEC-06:03 | 16.53 | 12.55 | 0.469849E+10 | 6734.61 | 29-DEC-14:00 | 19.50 | 14.92 |
Annual Sum or Average | 0.628856E+12 | 0.601653E+11 | ||||||||
Minimum of Months | 0.273149E+11 | 38168.36 | 15.05 | 12.04 | 0.449975E+10 | 6734.53 | 19.50 | 13.02 | ||
Maximum of Months | 0.715239E+11 | 91320.89 | 34.12 | 25.79 | 0.549750E+10 | 6734.75 | 43.40 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.502521E+10 | 5168.16 | 26-JAN-14:10 | 22.35 | 13.84 | 0.605802E+09 | 845.61 | 13-JAN-14:09 | 22.35 | 13.84 |
February | 0.586892E+10 | 6947.13 | 23-FEB-14:30 | 26.10 | 14.00 | 0.564956E+09 | 845.61 | 27-FEB-10:09 | 16.10 | 13.56 |
March | 0.976868E+10 | 14150.29 | 14-MAR-05:03 | 20.70 | 16.42 | 0.687091E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.135760E+11 | 17247.52 | 17-APR-05:02 | 24.22 | 18.83 | 0.612643E+09 | 845.63 | 04-APR-09:09 | 24.22 | 18.83 |
May | 0.149771E+11 | 20475.13 | 29-MAY-16:11 | 41.17 | 21.49 | 0.664734E+09 | 845.61 | 08-MAY-13:09 | 41.17 | 21.49 |
June | 0.155686E+11 | 20164.92 | 11-JUN-17:02 | 42.88 | 23.08 | 0.662379E+09 | 845.64 | 12-JUN-13:00 | 43.90 | 22.36 |
July | 0.154121E+11 | 21474.38 | 02-JUL-16:21 | 40.35 | 26.46 | 0.615987E+09 | 845.60 | 10-JUL-13:09 | 39.20 | 26.78 |
August | 0.161640E+11 | 19657.47 | 06-AUG-15:01 | 36.30 | 26.24 | 0.690769E+09 | 845.60 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.115971E+11 | 17183.10 | 05-SEP-03:02 | 26.38 | 25.08 | 0.613523E+09 | 845.61 | 08-SEP-13:30 | 28.50 | 25.88 |
October | 0.104546E+11 | 15461.45 | 11-OCT-05:03 | 23.85 | 20.24 | 0.636253E+09 | 845.62 | 10-OCT-13:00 | 23.85 | 20.24 |
November | 0.780053E+10 | 9034.84 | 06-NOV-06:03 | 14.70 | 13.68 | 0.625963E+09 | 845.63 | 06-NOV-14:50 | 28.48 | 18.19 |
December | 0.618403E+10 | 6111.32 | 26-DEC-14:10 | 22.68 | 14.39 | 0.599645E+09 | 845.62 | 18-DEC-10:00 | 22.68 | 14.39 |
Annual Sum or Average | 0.132397E+12 | 0.757975E+10 | ||||||||
Minimum of Months | 0.502521E+10 | 5168.16 | 14.70 | 13.68 | 0.564956E+09 | 845.60 | 16.10 | 13.56 | ||
Maximum of Months | 0.161640E+11 | 21474.38 | 42.88 | 26.46 | 0.690769E+09 | 845.64 | 43.90 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403047E+10 | 4508.41 | 26-JAN-10:20 | 18.10 | 12.94 | 0.397721E+09 | 544.95 | 04-JAN-10:00 | 18.10 | 12.94 |
February | 0.479077E+10 | 7097.53 | 21-FEB-09:50 | 18.65 | 13.10 | 0.364827E+09 | 544.95 | 02-FEB-10:09 | 18.65 | 13.10 |
March | 0.785013E+10 | 11885.31 | 26-MAR-09:32 | 24.67 | 14.70 | 0.442377E+09 | 544.96 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.106403E+11 | 17253.71 | 16-APR-09:42 | 34.62 | 21.58 | 0.394585E+09 | 545.37 | 28-APR-09:50 | 33.47 | 18.33 |
May | 0.120288E+11 | 17873.96 | 29-MAY-08:51 | 33.70 | 20.93 | 0.428584E+09 | 545.25 | 26-MAY-09:00 | 33.70 | 20.93 |
June | 0.113207E+11 | 15997.03 | 11-JUN-10:22 | 37.75 | 25.19 | 0.426636E+09 | 545.14 | 12-JUN-09:00 | 40.00 | 22.14 |
July | 0.105026E+11 | 16552.48 | 02-JUL-15:41 | 40.33 | 26.36 | 0.396534E+09 | 545.09 | 07-JUL-09:00 | 36.90 | 24.55 |
August | 0.103761E+11 | 16125.85 | 06-AUG-10:22 | 32.90 | 25.51 | 0.444449E+09 | 545.01 | 07-AUG-09:00 | 33.20 | 25.77 |
September | 0.861180E+10 | 11630.22 | 11-SEP-05:03 | 25.73 | 25.09 | 0.394924E+09 | 544.94 | 08-SEP-13:30 | 25.73 | 25.09 |
October | 0.818900E+10 | 13649.40 | 09-OCT-10:13 | 28.37 | 20.42 | 0.409585E+09 | 544.95 | 23-OCT-09:00 | 25.70 | 17.02 |
November | 0.609505E+10 | 6745.81 | 13-NOV-09:50 | 21.78 | 14.28 | 0.402908E+09 | 544.95 | 06-NOV-14:50 | 21.78 | 14.28 |
December | 0.460184E+10 | 5008.55 | 01-DEC-10:00 | 18.30 | 11.37 | 0.385825E+09 | 544.95 | 18-DEC-10:00 | 21.70 | 14.67 |
Annual Sum or Average | 0.990376E+11 | 0.488895E+10 | ||||||||
Minimum of Months | 0.403047E+10 | 4508.41 | 18.10 | 11.37 | 0.364827E+09 | 544.94 | 18.10 | 12.94 | ||
Maximum of Months | 0.120288E+11 | 17873.96 | 40.33 | 26.36 | 0.444449E+09 | 545.37 | 40.00 | 25.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.839025E+10 | 12576.52 | 12-JAN-13:40 | 22.93 | 13.82 | 0.623645E+09 | 845.89 | 12-JAN-14:20 | 23.40 | 14.05 |
February | 0.925672E+10 | 22076.29 | 20-FEB-14:02 | 26.38 | 13.56 | 0.571615E+09 | 846.13 | 07-FEB-14:50 | 26.38 | 13.56 |
March | 0.138044E+11 | 21384.44 | 12-MAR-12:13 | 30.03 | 18.68 | 0.689519E+09 | 846.07 | 08-MAR-14:00 | 30.03 | 18.68 |
April | 0.160840E+11 | 21642.96 | 16-APR-11:42 | 37.98 | 21.94 | 0.613511E+09 | 845.96 | 06-APR-13:00 | 37.98 | 21.94 |
May | 0.156255E+11 | 20920.49 | 29-MAY-16:11 | 41.17 | 21.49 | 0.664917E+09 | 845.92 | 05-MAY-13:20 | 41.17 | 21.49 |
June | 0.155457E+11 | 20152.06 | 11-JUN-16:22 | 43.25 | 23.12 | 0.662366E+09 | 846.12 | 12-JUN-13:20 | 43.50 | 22.39 |
July | 0.155323E+11 | 21826.65 | 02-JUL-16:21 | 40.35 | 26.46 | 0.616014E+09 | 846.08 | 05-JUL-13:20 | 37.90 | 25.56 |
August | 0.167710E+11 | 20805.29 | 06-AUG-15:01 | 36.30 | 26.24 | 0.690937E+09 | 846.16 | 09-AUG-13:20 | 34.53 | 26.23 |
September | 0.137941E+11 | 21889.53 | 24-SEP-13:22 | 34.85 | 24.63 | 0.614076E+09 | 846.02 | 19-SEP-13:00 | 34.85 | 24.63 |
October | 0.157945E+11 | 23070.20 | 09-OCT-12:52 | 32.30 | 19.97 | 0.639227E+09 | 867.46 | 02-OCT-13:30 | 32.30 | 19.97 |
November | 0.139213E+11 | 21636.63 | 19-NOV-12:53 | 25.80 | 16.93 | 0.631367E+09 | 846.27 | 24-NOV-14:00 | 24.80 | 13.62 |
December | 0.102379E+11 | 21285.83 | 03-DEC-12:02 | 22.92 | 14.22 | 0.609543E+09 | 846.21 | 04-DEC-14:00 | 23.20 | 14.27 |
Annual Sum or Average | 0.164758E+12 | 0.762674E+10 | ||||||||
Minimum of Months | 0.839025E+10 | 12576.52 | 22.92 | 13.56 | 0.571615E+09 | 845.89 | 23.20 | 13.56 | ||
Maximum of Months | 0.167710E+11 | 23070.20 | 43.25 | 26.46 | 0.690937E+09 | 867.46 | 43.50 | 26.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.567662E+10 | 7243.53 | 31-JAN-16:00 | 21.10 | 11.23 | 0.393570E+09 | 544.95 | 13-JAN-14:09 | 21.10 | 11.23 |
February | 0.689408E+10 | 20874.59 | 20-FEB-16:02 | 25.43 | 14.23 | 0.369178E+09 | 544.95 | 15-FEB-14:50 | 25.43 | 14.23 |
March | 0.121444E+11 | 19808.32 | 26-MAR-16:12 | 29.73 | 16.34 | 0.445786E+09 | 544.96 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.174553E+11 | 22754.91 | 30-APR-16:21 | 37.45 | 18.00 | 0.396404E+09 | 544.96 | 04-APR-09:09 | 37.45 | 18.00 |
May | 0.146943E+11 | 22379.18 | 28-MAY-16:21 | 42.00 | 19.52 | 0.428841E+09 | 544.94 | 05-MAY-09:00 | 42.00 | 19.52 |
June | 0.156288E+11 | 22436.19 | 18-JUN-15:52 | 33.10 | 23.21 | 0.427463E+09 | 544.95 | 12-JUN-13:09 | 33.10 | 23.21 |
July | 0.155865E+11 | 24575.11 | 02-JUL-16:21 | 40.35 | 26.46 | 0.397692E+09 | 544.94 | 05-JUL-13:00 | 37.90 | 25.56 |
August | 0.185566E+11 | 22365.96 | 06-AUG-15:41 | 36.30 | 26.24 | 0.446266E+09 | 544.94 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.112580E+11 | 22119.60 | 24-SEP-15:22 | 34.95 | 25.05 | 0.395821E+09 | 544.94 | 08-SEP-13:30 | 34.95 | 25.05 |
October | 0.115501E+11 | 22262.12 | 15-OCT-15:22 | 32.35 | 19.26 | 0.411777E+09 | 544.95 | 10-OCT-13:00 | 32.35 | 19.26 |
November | 0.980347E+10 | 16368.41 | 06-NOV-06:03 | 14.70 | 13.68 | 0.407572E+09 | 544.97 | 06-NOV-14:50 | 28.48 | 18.19 |
December | 0.840906E+10 | 16473.23 | 29-DEC-06:03 | 16.53 | 12.55 | 0.396329E+09 | 544.95 | 18-DEC-10:00 | 16.53 | 12.55 |
Annual Sum or Average | 0.147657E+12 | 0.491670E+10 | ||||||||
Minimum of Months | 0.567662E+10 | 7243.53 | 14.70 | 11.23 | 0.369178E+09 | 544.94 | 16.53 | 11.23 | ||
Maximum of Months | 0.185566E+11 | 24575.11 | 42.00 | 26.46 | 0.446266E+09 | 544.97 | 42.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.381768E+10 | 4060.34 | 14-JAN-06:02 | 14.50 | 12.49 | 0.549984E+09 | 845.60 | 26-JAN-14:00 | 21.60 | 13.66 |
February | 0.440536E+10 | 5793.28 | 24-FEB-15:00 | 26.40 | 17.38 | 0.536227E+09 | 845.61 | 24-FEB-14:20 | 26.40 | 17.38 |
March | 0.734410E+10 | 14190.40 | 11-MAR-06:02 | 23.80 | 17.15 | 0.678988E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.105327E+11 | 15096.75 | 16-APR-17:12 | 37.53 | 22.72 | 0.612480E+09 | 845.63 | 04-APR-09:09 | 37.53 | 22.72 |
May | 0.139282E+11 | 20757.40 | 28-MAY-15:31 | 42.27 | 19.32 | 0.664932E+09 | 845.62 | 01-MAY-09:20 | 42.27 | 19.32 |
June | 0.139811E+11 | 19544.74 | 11-JUN-17:02 | 42.88 | 23.08 | 0.662714E+09 | 845.76 | 12-JUN-13:00 | 43.90 | 22.36 |
July | 0.129739E+11 | 19519.38 | 02-JUL-16:42 | 40.32 | 26.53 | 0.616541E+09 | 845.60 | 10-JUL-13:09 | 39.20 | 26.78 |
August | 0.123814E+11 | 16589.55 | 07-AUG-05:03 | 29.53 | 24.79 | 0.691316E+09 | 845.60 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.995001E+10 | 16677.96 | 05-SEP-03:02 | 26.38 | 25.08 | 0.613654E+09 | 845.60 | 08-SEP-13:30 | 28.50 | 25.88 |
October | 0.827476E+10 | 14472.00 | 03-OCT-05:03 | 22.92 | 17.52 | 0.633279E+09 | 845.61 | 16-OCT-09:09 | 26.53 | 17.36 |
November | 0.566611E+10 | 6134.11 | 09-NOV-14:30 | 29.30 | 17.79 | 0.607934E+09 | 845.61 | 15-NOV-14:39 | 26.43 | 17.71 |
December | 0.417224E+10 | 4268.30 | 03-DEC-14:13 | 24.20 | 14.19 | 0.545230E+09 | 833.63 | 29-DEC-14:00 | 19.50 | 14.92 |
Annual Sum or Average | 0.107428E+12 | 0.741328E+10 | ||||||||
Minimum of Months | 0.381768E+10 | 4060.34 | 14.50 | 12.49 | 0.536227E+09 | 833.63 | 19.50 | 13.66 | ||
Maximum of Months | 0.139811E+11 | 20757.40 | 42.88 | 26.53 | 0.691316E+09 | 845.76 | 43.90 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336714E+10 | 3555.07 | 08-JAN-13:32 | 21.57 | 12.76 | 0.269474E+09 | 521.19 | 26-JAN-11:20 | 20.27 | 13.36 |
February | 0.400092E+10 | 6183.97 | 22-FEB-10:00 | 20.60 | 13.92 | 0.260065E+09 | 521.21 | 15-FEB-11:20 | 20.60 | 13.92 |
March | 0.683039E+10 | 12412.53 | 12-MAR-11:23 | 28.95 | 18.26 | 0.323022E+09 | 521.21 | 16-MAR-10:20 | 20.53 | 15.55 |
April | 0.974388E+10 | 18167.11 | 16-APR-09:12 | 33.47 | 21.34 | 0.291157E+09 | 521.78 | 17-APR-10:50 | 34.22 | 22.89 |
May | 0.119064E+11 | 18541.85 | 29-MAY-08:51 | 33.70 | 20.93 | 0.315638E+09 | 521.76 | 26-MAY-10:00 | 33.70 | 20.93 |
June | 0.109092E+11 | 16682.48 | 11-JUN-10:22 | 37.75 | 25.19 | 0.313884E+09 | 521.72 | 12-JUN-10:00 | 41.40 | 22.35 |
July | 0.962571E+10 | 16519.72 | 02-JUL-12:02 | 37.38 | 26.47 | 0.292971E+09 | 521.62 | 06-JUL-10:50 | 37.57 | 25.52 |
August | 0.905638E+10 | 13720.98 | 06-AUG-15:31 | 36.30 | 26.24 | 0.327247E+09 | 521.20 | 21-AUG-12:09 | 30.20 | 27.51 |
September | 0.788013E+10 | 15032.16 | 24-SEP-10:13 | 31.60 | 25.28 | 0.290869E+09 | 521.20 | 29-SEP-14:20 | 33.83 | 22.63 |
October | 0.725084E+10 | 17084.87 | 01-OCT-09:52 | 29.70 | 19.34 | 0.300714E+09 | 521.22 | 10-OCT-14:20 | 31.63 | 20.81 |
November | 0.508741E+10 | 6180.83 | 09-NOV-10:00 | 24.50 | 17.90 | 0.291967E+09 | 521.21 | 06-NOV-15:20 | 24.50 | 17.90 |
December | 0.360696E+10 | 4094.76 | 01-DEC-10:00 | 18.30 | 11.37 | 0.265341E+09 | 521.20 | 01-DEC-11:20 | 20.70 | 12.30 |
Annual Sum or Average | 0.892654E+11 | 0.354235E+10 | ||||||||
Minimum of Months | 0.336714E+10 | 3555.07 | 18.30 | 11.37 | 0.260065E+09 | 521.19 | 20.27 | 12.30 | ||
Maximum of Months | 0.119064E+11 | 18541.85 | 37.75 | 26.47 | 0.327247E+09 | 521.78 | 41.40 | 27.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.766998E+10 | 19532.51 | 08-JAN-13:32 | 21.57 | 12.76 | 0.616705E+09 | 845.91 | 11-JAN-14:00 | 22.20 | 11.82 |
February | 0.815938E+10 | 21358.36 | 20-FEB-13:52 | 26.40 | 13.47 | 0.565694E+09 | 846.03 | 07-FEB-14:00 | 26.40 | 13.47 |
March | 0.117338E+11 | 21297.94 | 12-MAR-13:22 | 30.95 | 19.20 | 0.687742E+09 | 847.90 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.132010E+11 | 20807.26 | 16-APR-11:52 | 38.20 | 21.94 | 0.613952E+09 | 845.86 | 21-APR-13:00 | 35.00 | 19.79 |
May | 0.145327E+11 | 21077.93 | 28-MAY-15:31 | 42.27 | 19.32 | 0.665105E+09 | 845.83 | 04-MAY-13:00 | 42.27 | 19.32 |
June | 0.138828E+11 | 18514.64 | 11-JUN-16:22 | 43.25 | 23.12 | 0.662691E+09 | 845.68 | 12-JUN-13:00 | 43.90 | 22.36 |
July | 0.130703E+11 | 19866.79 | 30-JUL-15:32 | 34.73 | 27.14 | 0.616565E+09 | 845.62 | 10-JUL-13:09 | 34.73 | 27.14 |
August | 0.130662E+11 | 20003.02 | 06-AUG-14:51 | 36.30 | 26.24 | 0.691566E+09 | 845.78 | 07-AUG-13:00 | 37.20 | 26.26 |
September | 0.123332E+11 | 20757.08 | 24-SEP-16:12 | 34.57 | 25.35 | 0.614391E+09 | 850.66 | 28-SEP-13:39 | 35.37 | 22.75 |
October | 0.142197E+11 | 22870.36 | 01-OCT-13:11 | 35.43 | 19.93 | 0.639662E+09 | 877.09 | 02-OCT-13:50 | 36.37 | 21.07 |
November | 0.124258E+11 | 21631.53 | 11-NOV-12:02 | 27.58 | 17.19 | 0.629846E+09 | 856.02 | 01-NOV-13:39 | 27.58 | 17.19 |
December | 0.841440E+10 | 20688.27 | 03-DEC-12:53 | 24.00 | 14.17 | 0.602447E+09 | 845.93 | 04-DEC-14:00 | 23.20 | 14.27 |
Annual Sum or Average | 0.142709E+12 | 0.760637E+10 | ||||||||
Minimum of Months | 0.766998E+10 | 18514.64 | 21.57 | 12.76 | 0.565694E+09 | 845.62 | 22.20 | 11.82 | ||
Maximum of Months | 0.145327E+11 | 22870.36 | 43.25 | 27.14 | 0.691566E+09 | 877.09 | 43.90 | 27.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371254E+10 | 5129.19 | 31-JAN-16:10 | 20.95 | 11.21 | 0.361895E+09 | 544.94 | 25-JAN-14:00 | 20.95 | 11.21 |
February | 0.429337E+10 | 7454.26 | 21-FEB-16:00 | 26.10 | 15.66 | 0.346046E+09 | 544.95 | 24-FEB-14:30 | 26.15 | 17.19 |
March | 0.730679E+10 | 16641.04 | 12-MAR-16:02 | 31.18 | 19.88 | 0.438106E+09 | 544.96 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.104776E+11 | 19104.66 | 30-APR-16:11 | 37.57 | 18.06 | 0.395632E+09 | 544.95 | 04-APR-09:09 | 37.57 | 18.06 |
May | 0.123459E+11 | 20637.36 | 28-MAY-15:31 | 42.27 | 19.32 | 0.428818E+09 | 544.95 | 01-MAY-09:20 | 42.27 | 19.32 |
June | 0.119966E+11 | 18671.21 | 11-JUN-16:22 | 43.25 | 23.12 | 0.427335E+09 | 544.95 | 07-JUN-09:20 | 43.25 | 23.12 |
July | 0.103893E+11 | 18492.31 | 02-JUL-16:42 | 40.32 | 26.53 | 0.397430E+09 | 544.94 | 10-JUL-09:30 | 33.55 | 26.55 |
August | 0.100215E+11 | 18437.69 | 06-AUG-16:11 | 36.20 | 26.31 | 0.445712E+09 | 544.94 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.844681E+10 | 18845.57 | 24-SEP-16:12 | 34.57 | 25.35 | 0.395371E+09 | 544.94 | 08-SEP-13:30 | 34.57 | 25.35 |
October | 0.768865E+10 | 18836.35 | 01-OCT-16:32 | 34.77 | 20.19 | 0.408469E+09 | 544.95 | 16-OCT-09:09 | 26.53 | 17.36 |
November | 0.567622E+10 | 8153.10 | 11-NOV-15:22 | 28.00 | 17.36 | 0.392440E+09 | 544.95 | 06-NOV-14:00 | 28.00 | 17.36 |
December | 0.406548E+10 | 5567.63 | 01-DEC-15:30 | 22.85 | 13.56 | 0.359046E+09 | 544.94 | 18-DEC-14:00 | 22.10 | 15.00 |
Annual Sum or Average | 0.964207E+11 | 0.479630E+10 | ||||||||
Minimum of Months | 0.371254E+10 | 5129.19 | 20.95 | 11.21 | 0.346046E+09 | 544.94 | 20.95 | 11.21 | ||
Maximum of Months | 0.123459E+11 | 20637.36 | 43.25 | 26.53 | 0.445712E+09 | 544.96 | 43.25 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294144E+10 | 3935.55 | 26-JAN-15:10 | 21.37 | 13.58 | 0.503140E+09 | 807.53 | 26-JAN-14:00 | 21.37 | 13.58 |
February | 0.406488E+10 | 5857.82 | 23-FEB-14:50 | 25.90 | 14.07 | 0.502174E+09 | 845.61 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.757042E+10 | 13337.96 | 30-MAR-05:02 | 21.37 | 16.59 | 0.662846E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.117869E+11 | 22585.54 | 30-APR-16:01 | 37.68 | 18.13 | 0.610509E+09 | 845.63 | 28-APR-13:20 | 37.68 | 18.13 |
May | 0.160112E+11 | 23646.01 | 28-MAY-16:31 | 41.90 | 19.53 | 0.664845E+09 | 845.61 | 05-MAY-09:00 | 41.90 | 19.53 |
June | 0.160306E+11 | 23411.41 | 11-JUN-16:22 | 43.25 | 23.12 | 0.662637E+09 | 845.62 | 12-JUN-13:09 | 43.40 | 22.40 |
July | 0.148449E+11 | 23774.53 | 02-JUL-13:12 | 38.63 | 26.37 | 0.616567E+09 | 845.60 | 10-JUL-09:09 | 32.98 | 26.50 |
August | 0.138302E+11 | 19555.61 | 21-AUG-03:02 | 25.87 | 25.24 | 0.691260E+09 | 845.60 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.109634E+11 | 22757.80 | 17-SEP-15:22 | 34.15 | 26.07 | 0.612504E+09 | 845.60 | 08-SEP-13:39 | 34.15 | 26.07 |
October | 0.871994E+10 | 17338.00 | 01-OCT-15:21 | 35.75 | 20.04 | 0.625377E+09 | 845.61 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.543937E+10 | 6498.77 | 09-NOV-14:50 | 29.23 | 17.74 | 0.579664E+09 | 845.61 | 15-NOV-14:30 | 26.40 | 17.66 |
December | 0.337656E+10 | 3904.05 | 28-DEC-16:30 | 23.30 | 15.06 | 0.499145E+09 | 798.71 | 28-DEC-14:00 | 23.30 | 15.06 |
Annual Sum or Average | 0.115580E+12 | 0.723067E+10 | ||||||||
Minimum of Months | 0.294144E+10 | 3904.05 | 21.37 | 13.58 | 0.499145E+09 | 798.71 | 21.37 | 13.58 | ||
Maximum of Months | 0.160306E+11 | 23774.53 | 43.25 | 26.37 | 0.691260E+09 | 845.63 | 43.40 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.275722E+10 | 3123.41 | 26-JAN-14:50 | 21.75 | 13.69 | 0.341464E+09 | 539.57 | 26-JAN-14:00 | 21.60 | 13.66 |
February | 0.362577E+10 | 5712.13 | 23-FEB-10:40 | 22.80 | 14.32 | 0.343956E+09 | 544.95 | 15-FEB-10:39 | 22.80 | 14.32 |
March | 0.694573E+10 | 10150.85 | 30-MAR-05:02 | 21.37 | 16.59 | 0.437969E+09 | 544.96 | 27-MAR-09:20 | 21.37 | 16.59 |
April | 0.107530E+11 | 19303.45 | 30-APR-10:02 | 31.85 | 16.40 | 0.395132E+09 | 545.27 | 17-APR-09:20 | 31.85 | 16.40 |
May | 0.134762E+11 | 18767.72 | 29-MAY-09:42 | 35.45 | 21.98 | 0.428849E+09 | 545.22 | 26-MAY-09:00 | 35.45 | 21.98 |
June | 0.124140E+11 | 18001.42 | 11-JUN-10:22 | 37.75 | 25.19 | 0.427028E+09 | 545.21 | 13-JUN-09:20 | 35.17 | 26.05 |
July | 0.109683E+11 | 18647.13 | 02-JUL-09:12 | 34.77 | 25.77 | 0.397300E+09 | 545.22 | 05-JUL-09:20 | 35.67 | 25.11 |
August | 0.101604E+11 | 14173.33 | 06-AUG-15:12 | 36.30 | 26.24 | 0.445300E+09 | 544.94 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.868065E+10 | 17654.60 | 17-SEP-15:22 | 34.15 | 26.07 | 0.394655E+09 | 544.94 | 08-SEP-13:39 | 34.15 | 26.07 |
October | 0.758432E+10 | 18087.22 | 01-OCT-10:42 | 31.62 | 19.69 | 0.406986E+09 | 544.95 | 16-OCT-09:30 | 27.20 | 17.62 |
November | 0.476902E+10 | 5822.99 | 09-NOV-10:30 | 25.75 | 18.10 | 0.391960E+09 | 544.95 | 06-NOV-14:50 | 25.75 | 18.10 |
December | 0.298584E+10 | 3136.89 | 01-DEC-15:10 | 23.22 | 13.42 | 0.340549E+09 | 542.19 | 01-DEC-14:00 | 23.22 | 13.42 |
Annual Sum or Average | 0.951204E+11 | 0.475115E+10 | ||||||||
Minimum of Months | 0.275722E+10 | 3123.41 | 21.37 | 13.42 | 0.340549E+09 | 539.57 | 21.37 | 13.42 | ||
Maximum of Months | 0.134762E+11 | 19303.45 | 37.75 | 26.24 | 0.445300E+09 | 545.27 | 35.67 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.625814E+10 | 12079.49 | 12-JAN-14:20 | 23.40 | 14.05 | 0.585102E+09 | 845.64 | 25-JAN-14:00 | 23.00 | 13.41 |
February | 0.745148E+10 | 23757.35 | 20-FEB-13:32 | 26.23 | 13.43 | 0.547508E+09 | 845.97 | 21-FEB-14:00 | 26.30 | 15.42 |
March | 0.118779E+11 | 23817.90 | 12-MAR-12:13 | 30.03 | 18.68 | 0.680499E+09 | 846.03 | 09-MAR-14:00 | 30.03 | 18.68 |
April | 0.146171E+11 | 24374.25 | 30-APR-13:22 | 37.15 | 18.65 | 0.612793E+09 | 846.03 | 25-APR-13:20 | 37.15 | 18.65 |
May | 0.166551E+11 | 23759.38 | 28-MAY-15:51 | 42.30 | 19.48 | 0.665006E+09 | 846.07 | 04-MAY-13:20 | 42.30 | 19.48 |
June | 0.159184E+11 | 23354.92 | 11-JUN-16:22 | 43.25 | 23.12 | 0.662616E+09 | 845.95 | 12-JUN-13:39 | 43.70 | 22.38 |
July | 0.149361E+11 | 24004.33 | 02-JUL-13:12 | 38.63 | 26.37 | 0.616586E+09 | 845.62 | 10-JUL-13:09 | 39.20 | 26.78 |
August | 0.145606E+11 | 21165.32 | 06-AUG-15:12 | 36.30 | 26.24 | 0.691491E+09 | 845.62 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.134624E+11 | 24663.08 | 17-SEP-15:22 | 34.15 | 26.07 | 0.613672E+09 | 845.83 | 26-SEP-13:00 | 35.70 | 22.91 |
October | 0.147642E+11 | 26297.07 | 01-OCT-15:21 | 35.75 | 20.04 | 0.636535E+09 | 851.95 | 02-OCT-13:50 | 36.37 | 21.07 |
November | 0.118049E+11 | 25516.90 | 12-NOV-13:42 | 28.12 | 16.00 | 0.622038E+09 | 846.09 | 17-NOV-14:00 | 28.00 | 17.86 |
December | 0.709011E+10 | 13620.39 | 01-DEC-13:50 | 23.35 | 13.02 | 0.580381E+09 | 845.64 | 04-DEC-14:00 | 23.20 | 14.27 |
Annual Sum or Average | 0.149396E+12 | 0.751423E+10 | ||||||||
Minimum of Months | 0.625814E+10 | 12079.49 | 23.35 | 13.02 | 0.547508E+09 | 845.62 | 23.00 | 13.41 | ||
Maximum of Months | 0.166551E+11 | 26297.07 | 43.25 | 26.37 | 0.691491E+09 | 851.95 | 43.70 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308031E+10 | 4618.69 | 31-JAN-16:10 | 20.95 | 11.21 | 0.338653E+09 | 544.61 | 12-JAN-14:00 | 20.95 | 11.21 |
February | 0.399393E+10 | 7456.53 | 21-FEB-16:00 | 26.10 | 15.66 | 0.329410E+09 | 544.95 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.744793E+10 | 15940.38 | 12-MAR-16:12 | 31.07 | 19.87 | 0.429216E+09 | 544.96 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.114254E+11 | 21431.11 | 30-APR-16:01 | 37.68 | 18.13 | 0.394606E+09 | 544.95 | 04-APR-09:09 | 37.68 | 18.13 |
May | 0.138441E+11 | 21894.48 | 28-MAY-16:31 | 41.90 | 19.53 | 0.428597E+09 | 544.95 | 05-MAY-09:00 | 41.90 | 19.53 |
June | 0.134583E+11 | 21419.54 | 11-JUN-16:22 | 43.25 | 23.12 | 0.427127E+09 | 544.95 | 12-JUN-13:09 | 43.40 | 22.40 |
July | 0.116779E+11 | 21663.92 | 02-JUL-16:31 | 40.33 | 26.50 | 0.397246E+09 | 544.94 | 10-JUL-09:09 | 32.98 | 26.50 |
August | 0.110084E+11 | 20156.40 | 06-AUG-16:32 | 36.10 | 26.38 | 0.445414E+09 | 544.94 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.921544E+10 | 21246.26 | 17-SEP-16:02 | 34.13 | 26.16 | 0.394350E+09 | 544.94 | 08-SEP-13:39 | 34.13 | 26.16 |
October | 0.802642E+10 | 21833.44 | 01-OCT-15:21 | 35.75 | 20.04 | 0.403626E+09 | 544.95 | 16-OCT-09:30 | 27.20 | 17.62 |
November | 0.545336E+10 | 8263.12 | 08-NOV-15:30 | 29.55 | 18.29 | 0.379179E+09 | 544.95 | 06-NOV-14:50 | 29.55 | 18.29 |
December | 0.347157E+10 | 5237.79 | 28-DEC-15:40 | 24.03 | 15.27 | 0.336885E+09 | 544.94 | 28-DEC-14:00 | 24.03 | 15.27 |
Annual Sum or Average | 0.102103E+12 | 0.470431E+10 | ||||||||
Minimum of Months | 0.308031E+10 | 4618.69 | 20.95 | 11.21 | 0.329410E+09 | 544.61 | 20.95 | 11.21 | ||
Maximum of Months | 0.138441E+11 | 21894.48 | 43.25 | 26.50 | 0.445414E+09 | 544.96 | 43.40 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471145E+10 | 8730.68 | 02-JAN-06:13 | 6.50 | 6.28 | 0.00 | 0.00 | 01-JAN-00:10 | 6.50 | 6.28 |
February | 0.580980E+10 | 11725.83 | 21-FEB-06:13 | 11.70 | 10.89 | 0.00 | 0.00 | 01-FEB-00:10 | 11.70 | 10.89 |
March | 0.957692E+10 | 11356.57 | 06-MAR-06:13 | 15.77 | 13.93 | 0.00 | 0.00 | 01-MAR-00:10 | 15.77 | 13.93 |
April | 0.127158E+11 | 17284.87 | 17-APR-05:15 | 24.33 | 18.88 | 0.00 | 0.00 | 01-APR-00:10 | 24.33 | 18.88 |
May | 0.136869E+11 | 17187.45 | 01-MAY-05:15 | 32.50 | 19.11 | 0.00 | 0.00 | 01-MAY-00:10 | 32.50 | 19.11 |
June | 0.136879E+11 | 17622.67 | 12-JUN-05:15 | 34.23 | 19.16 | 0.00 | 0.00 | 01-JUN-00:10 | 34.23 | 19.16 |
July | 0.133998E+11 | 19320.30 | 03-JUL-05:13 | 29.33 | 24.63 | 0.00 | 0.00 | 01-JUL-00:10 | 29.33 | 24.63 |
August | 0.145531E+11 | 18127.66 | 07-AUG-05:13 | 29.57 | 24.74 | 0.00 | 0.00 | 01-AUG-00:10 | 29.57 | 24.74 |
September | 0.107566E+11 | 15021.85 | 05-SEP-05:15 | 26.20 | 25.15 | 0.00 | 0.00 | 01-SEP-00:10 | 26.20 | 25.15 |
October | 0.106116E+11 | 14093.22 | 10-OCT-05:15 | 19.90 | 18.09 | 0.00 | 0.00 | 01-OCT-00:10 | 19.90 | 18.09 |
November | 0.854179E+10 | 12959.81 | 13-NOV-06:13 | 15.27 | 12.05 | 0.00 | 0.00 | 01-NOV-00:10 | 15.27 | 12.05 |
December | 0.635253E+10 | 10585.62 | 26-DEC-06:13 | 10.23 | 8.49 | 0.00 | 0.00 | 01-DEC-00:10 | 10.23 | 8.49 |
Annual Sum or Average | 0.124404E+12 | 0.00 | ||||||||
Minimum of Months | 0.471145E+10 | 8730.68 | 6.50 | 6.28 | 0.00 | 0.00 | 6.50 | 6.28 | ||
Maximum of Months | 0.145531E+11 | 19320.30 | 34.23 | 25.15 | 0.00 | 0.00 | 34.23 | 25.15 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285880E+10 | 5083.61 | 21-JAN-06:08 | 5.50 | 5.15 | 0.00 | 0.00 | 01-JAN-00:10 | 5.50 | 5.15 |
February | 0.393191E+10 | 6836.17 | 23-FEB-06:13 | 15.10 | 13.65 | 0.00 | 0.00 | 01-FEB-00:10 | 15.10 | 13.65 |
March | 0.727288E+10 | 7962.68 | 15-MAR-05:03 | 18.17 | 15.10 | 0.00 | 0.00 | 01-MAR-00:10 | 18.17 | 15.10 |
April | 0.987035E+10 | 9651.62 | 21-APR-05:03 | 26.98 | 17.68 | 0.00 | 0.00 | 01-APR-00:10 | 26.98 | 17.68 |
May | 0.119263E+11 | 11915.05 | 31-MAY-05:03 | 31.72 | 21.12 | 0.00 | 0.00 | 01-MAY-00:10 | 31.72 | 21.12 |
June | 0.115875E+11 | 11252.69 | 09-JUN-05:03 | 31.20 | 23.77 | 0.00 | 0.00 | 01-JUN-00:10 | 31.20 | 23.77 |
July | 0.107167E+11 | 14378.42 | 05-JUL-05:02 | 32.57 | 24.73 | 0.00 | 0.00 | 01-JUL-00:10 | 32.57 | 24.73 |
August | 0.106468E+11 | 11853.16 | 08-AUG-05:02 | 30.10 | 25.30 | 0.00 | 0.00 | 01-AUG-00:10 | 30.10 | 25.30 |
September | 0.918615E+10 | 12616.52 | 05-SEP-05:15 | 26.20 | 25.15 | 0.00 | 0.00 | 01-SEP-00:10 | 26.20 | 25.15 |
October | 0.852256E+10 | 9259.85 | 20-OCT-05:02 | 20.15 | 17.63 | 0.00 | 0.00 | 01-OCT-00:10 | 20.15 | 17.63 |
November | 0.597566E+10 | 8965.11 | 13-NOV-06:13 | 15.27 | 12.05 | 0.00 | 0.00 | 01-NOV-00:10 | 15.27 | 12.05 |
December | 0.366519E+10 | 5446.69 | 02-DEC-06:10 | 8.72 | 8.46 | 0.00 | 0.00 | 01-DEC-00:10 | 8.72 | 8.46 |
Annual Sum or Average | 0.961608E+11 | 0.00 | ||||||||
Minimum of Months | 0.285880E+10 | 5083.61 | 5.50 | 5.15 | 0.00 | 0.00 | 5.50 | 5.15 | ||
Maximum of Months | 0.119263E+11 | 14378.42 | 32.57 | 25.30 | 0.00 | 0.00 | 32.57 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230813E+10 | 7274.40 | 12-JAN-14:50 | 23.55 | 14.16 | 0.00 | 0.00 | 01-JAN-00:10 | 23.55 | 14.16 |
February | 0.457124E+10 | 13930.36 | 22-FEB-14:40 | 27.07 | 16.24 | 0.00 | 0.00 | 01-FEB-00:10 | 27.07 | 16.24 |
March | 0.111903E+11 | 21896.13 | 28-MAR-15:20 | 35.57 | 18.58 | 0.00 | 0.00 | 01-MAR-00:10 | 35.57 | 18.58 |
April | 0.191848E+11 | 26854.17 | 26-APR-14:50 | 39.22 | 22.03 | 0.00 | 0.00 | 01-APR-00:10 | 39.22 | 22.03 |
May | 0.248545E+11 | 30383.45 | 01-MAY-14:20 | 43.93 | 22.01 | 0.00 | 0.00 | 01-MAY-00:10 | 43.93 | 22.01 |
June | 0.247666E+11 | 31890.04 | 12-JUN-13:50 | 43.80 | 22.37 | 0.00 | 0.00 | 01-JUN-00:10 | 43.80 | 22.37 |
July | 0.204144E+11 | 28449.61 | 07-JUL-14:00 | 40.30 | 24.54 | 0.00 | 0.00 | 01-JUL-00:10 | 40.30 | 24.54 |
August | 0.188552E+11 | 25400.53 | 07-AUG-14:00 | 37.20 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 37.20 | 26.26 |
September | 0.149114E+11 | 22285.97 | 26-SEP-14:40 | 35.97 | 22.76 | 0.00 | 0.00 | 01-SEP-00:10 | 35.97 | 22.76 |
October | 0.128028E+11 | 21182.08 | 02-OCT-14:00 | 36.40 | 21.05 | 0.00 | 0.00 | 01-OCT-00:10 | 36.40 | 21.05 |
November | 0.714902E+10 | 14879.60 | 09-NOV-14:10 | 29.37 | 17.83 | 0.00 | 0.00 | 01-NOV-00:10 | 29.37 | 17.83 |
December | 0.276974E+10 | 8626.81 | 01-DEC-14:30 | 23.45 | 13.21 | 0.00 | 0.00 | 01-DEC-00:10 | 23.45 | 13.21 |
Annual Sum or Average | 0.163778E+12 | 0.00 | ||||||||
Minimum of Months | 0.230813E+10 | 7274.40 | 23.45 | 13.21 | 0.00 | 0.00 | 23.45 | 13.21 | ||
Maximum of Months | 0.248545E+11 | 31890.04 | 43.93 | 26.26 | 0.00 | 0.00 | 43.93 | 26.26 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.407200E+10 | 1950.12 | 30-JAN-17:00 | 19.20 | 10.80 | 95236931.08 | 126.85 | 17-JAN-14:00 | 19.20 | 10.80 |
February | 0.852571E+10 | 3916.24 | 21-FEB-17:00 | 25.40 | 15.70 | 86404198.12 | 126.85 | 09-FEB-14:00 | 25.40 | 15.70 |
March | 0.147028E+11 | 7207.09 | 31-MAR-23:55 | 23.70 | 16.75 | 0.103241E+09 | 126.84 | 23-MAR-09:09 | 23.70 | 16.75 |
April | 0.191796E+11 | 7756.45 | 16-APR-22:35 | 27.57 | 19.98 | 95186930.25 | 145.20 | 27-APR-13:00 | 39.60 | 19.54 |
May | 0.481678E+10 | 3509.96 | 31-MAY-24:00 | 28.10 | 22.60 | 99241500.94 | 126.86 | 30-MAY-09:20 | 28.10 | 22.60 |
June | 0.953363E+10 | 5382.56 | 30-JUN-23:57 | 33.10 | 24.67 | 98979051.96 | 126.88 | 27-JUN-09:09 | 33.10 | 24.67 |
July | 0.148770E+11 | 7269.26 | 31-JUL-23:57 | 29.40 | 26.34 | 91893405.44 | 126.85 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.196850E+11 | 7616.83 | 16-AUG-09:40 | 25.23 | 24.59 | 0.112180E+09 | 151.26 | 07-AUG-13:00 | 25.23 | 24.59 |
September | 0.460734E+10 | 3506.22 | 30-SEP-23:47 | 26.60 | 21.97 | 91606879.69 | 126.86 | 26-SEP-13:00 | 26.60 | 21.97 |
October | 0.976349E+10 | 5408.90 | 31-OCT-24:00 | 17.80 | 15.13 | 95244614.69 | 126.87 | 12-OCT-09:39 | 17.80 | 15.13 |
November | 0.142445E+11 | 5828.83 | 13-NOV-16:30 | 27.00 | 16.63 | 94304826.12 | 126.83 | 10-NOV-10:09 | 27.00 | 16.63 |
December | 0.195760E+11 | 7687.46 | 28-DEC-17:00 | 22.80 | 14.91 | 91882189.92 | 126.83 | 11-DEC-10:09 | 22.80 | 14.91 |
Annual Sum or Average | 0.143584E+12 | 0.115540E+10 | ||||||||
Minimum of Months | 0.407200E+10 | 1950.12 | 17.80 | 10.80 | 86404198.12 | 126.83 | 17.80 | 10.80 | ||
Maximum of Months | 0.196850E+11 | 7756.45 | 33.10 | 26.34 | 0.112180E+09 | 151.26 | 39.60 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292708E+10 | 1787.32 | 12-JAN-17:00 | 22.30 | 14.53 | 95235296.59 | 126.84 | 13-JAN-14:00 | 21.50 | 15.25 |
February | 0.754040E+10 | 3680.77 | 21-FEB-17:00 | 25.40 | 15.70 | 86403614.12 | 126.84 | 09-FEB-14:00 | 25.40 | 15.70 |
March | 0.138642E+11 | 6965.49 | 31-MAR-23:55 | 23.70 | 16.75 | 0.103242E+09 | 126.84 | 29-MAR-09:09 | 23.70 | 16.75 |
April | 0.181825E+11 | 7338.16 | 12-APR-16:00 | 28.10 | 17.52 | 95003097.88 | 144.07 | 26-APR-13:00 | 38.80 | 22.02 |
May | 0.448503E+10 | 3382.31 | 31-MAY-24:00 | 28.10 | 22.60 | 99238933.94 | 126.85 | 30-MAY-13:09 | 28.10 | 22.60 |
June | 0.903350E+10 | 5209.02 | 30-JUN-23:42 | 33.12 | 24.58 | 98980134.82 | 126.87 | 28-JUN-13:20 | 33.12 | 24.58 |
July | 0.141311E+11 | 6987.17 | 31-JUL-24:00 | 29.40 | 26.34 | 91895044.64 | 126.85 | 18-JUL-13:00 | 29.40 | 26.34 |
August | 0.185810E+11 | 7182.48 | 16-AUG-10:50 | 25.82 | 25.06 | 0.110916E+09 | 147.54 | 07-AUG-13:00 | 25.82 | 25.06 |
September | 0.425242E+10 | 3402.17 | 30-SEP-23:47 | 26.60 | 21.97 | 91605872.17 | 126.85 | 27-SEP-13:00 | 26.60 | 21.97 |
October | 0.914898E+10 | 5089.52 | 31-OCT-24:00 | 17.80 | 15.13 | 95244476.58 | 126.86 | 13-OCT-09:20 | 17.80 | 15.13 |
November | 0.131751E+11 | 5502.47 | 08-NOV-16:40 | 28.33 | 18.82 | 94305004.47 | 126.83 | 10-NOV-10:09 | 23.57 | 17.22 |
December | 0.178152E+11 | 7247.83 | 01-DEC-17:00 | 21.20 | 14.26 | 91882401.60 | 126.83 | 11-DEC-10:00 | 10.00 | 9.32 |
Annual Sum or Average | 0.133136E+12 | 0.115395E+10 | ||||||||
Minimum of Months | 0.292708E+10 | 1787.32 | 17.80 | 14.26 | 86403614.12 | 126.83 | 10.00 | 9.32 | ||
Maximum of Months | 0.185810E+11 | 7338.16 | 33.12 | 26.34 | 0.110916E+09 | 147.54 | 38.80 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157049E+10 | 1790.41 | 12-JAN-17:00 | 22.30 | 14.53 | 95061612.91 | 126.84 | 13-JAN-14:00 | 21.50 | 15.25 |
February | 0.684371E+10 | 3710.93 | 22-FEB-17:00 | 25.70 | 15.75 | 86404283.59 | 126.84 | 15-FEB-14:50 | 25.70 | 15.75 |
March | 0.136683E+11 | 6911.88 | 31-MAR-23:55 | 23.70 | 16.75 | 0.103242E+09 | 126.84 | 29-MAR-09:09 | 23.70 | 16.75 |
April | 0.183139E+11 | 7487.94 | 16-APR-20:52 | 28.40 | 20.06 | 93957075.30 | 142.43 | 26-APR-13:00 | 38.80 | 22.02 |
May | 0.469774E+10 | 3354.11 | 31-MAY-24:00 | 28.10 | 22.60 | 99239481.17 | 126.85 | 10-MAY-13:00 | 28.10 | 22.60 |
June | 0.923095E+10 | 5249.71 | 30-JUN-23:57 | 33.10 | 24.67 | 98980799.82 | 126.88 | 26-JUN-09:00 | 33.10 | 24.67 |
July | 0.143274E+11 | 7042.96 | 31-JUL-23:57 | 29.40 | 26.34 | 91896142.19 | 126.86 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.188494E+11 | 7296.57 | 20-AUG-16:22 | 27.25 | 25.83 | 0.108433E+09 | 146.05 | 07-AUG-13:00 | 27.25 | 25.83 |
September | 0.430917E+10 | 3382.09 | 30-SEP-23:34 | 26.60 | 22.02 | 91605938.98 | 126.86 | 27-SEP-13:00 | 26.60 | 22.02 |
October | 0.905063E+10 | 4940.77 | 31-OCT-24:00 | 17.80 | 15.13 | 95245478.22 | 126.86 | 12-OCT-13:00 | 17.80 | 15.13 |
November | 0.126557E+11 | 5557.69 | 08-NOV-16:30 | 28.55 | 18.76 | 94305645.39 | 126.83 | 10-NOV-10:09 | 23.57 | 17.22 |
December | 0.166347E+11 | 7241.78 | 28-DEC-17:00 | 22.80 | 14.91 | 91882977.10 | 126.83 | 11-DEC-10:50 | 22.80 | 14.91 |
Annual Sum or Average | 0.130152E+12 | 0.115025E+10 | ||||||||
Minimum of Months | 0.157049E+10 | 1790.41 | 17.80 | 14.53 | 86404283.59 | 126.83 | 17.80 | 14.91 | ||
Maximum of Months | 0.188494E+11 | 7487.94 | 33.10 | 26.34 | 0.108433E+09 | 146.05 | 38.80 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242031E+12 | 93285.70 | 26-JAN-17:00 | 18.60 | 12.70 | 0.206241E+10 | 2748.30 | 26-JAN-10:09 | 18.60 | 12.70 |
February | 0.438528E+12 | 184671.54 | 21-FEB-17:00 | 25.40 | 15.70 | 0.187106E+10 | 2749.10 | 28-FEB-10:09 | 18.42 | 14.43 |
March | 0.730503E+12 | 359056.19 | 31-MAR-23:55 | 23.70 | 16.75 | 0.223525E+10 | 2749.75 | 20-MAR-09:00 | 23.70 | 16.75 |
April | 0.935252E+12 | 368482.41 | 30-APR-04:25 | 23.15 | 16.67 | 0.240535E+10 | 4044.43 | 28-APR-13:00 | 23.15 | 16.67 |
May | 0.243004E+12 | 176395.08 | 31-MAY-24:00 | 28.10 | 22.60 | 0.214884E+10 | 2747.23 | 24-MAY-09:00 | 28.10 | 22.60 |
June | 0.472699E+12 | 268595.66 | 30-JUN-24:00 | 33.10 | 24.67 | 0.214278E+10 | 2746.95 | 27-JUN-09:00 | 33.10 | 24.67 |
July | 0.735783E+12 | 356264.77 | 31-JUL-23:23 | 29.40 | 26.34 | 0.198927E+10 | 2746.02 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.968189E+12 | 370180.76 | 15-AUG-23:42 | 23.53 | 22.96 | 0.293157E+10 | 4080.49 | 07-AUG-13:00 | 23.53 | 22.96 |
September | 0.240169E+12 | 177656.23 | 30-SEP-23:53 | 26.60 | 21.92 | 0.198369E+10 | 2747.28 | 14-SEP-13:09 | 26.60 | 21.92 |
October | 0.491305E+12 | 269769.60 | 31-OCT-24:00 | 17.80 | 15.13 | 0.206191E+10 | 2746.43 | 13-OCT-09:09 | 17.80 | 15.13 |
November | 0.712049E+12 | 277921.28 | 13-NOV-17:00 | 26.40 | 16.65 | 0.204192E+10 | 2749.64 | 28-NOV-10:30 | 18.60 | 13.96 |
December | 0.980030E+12 | 369279.31 | 04-DEC-17:00 | 20.10 | 14.52 | 0.199058E+10 | 2819.26 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.718954E+13 | 0.258646E+11 | ||||||||
Minimum of Months | 0.240169E+12 | 93285.70 | 17.80 | 12.70 | 0.187106E+10 | 2746.02 | 17.80 | 12.70 | ||
Maximum of Months | 0.980030E+12 | 370180.76 | 33.10 | 26.34 | 0.293157E+10 | 4080.49 | 33.10 | 26.34 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5304976.04 | 2885.00 | 14-JAN-17:25 | 20.25 |
February | 72178275.55 | 11359.91 | 20-FEB-13:54 | 26.40 |
March | 0.144591E+09 | 15727.80 | 11-MAR-17:03 | 29.70 |
April | 0.495071E+09 | 30323.79 | 15-APR-16:01 | 39.58 |
May | 0.699186E+09 | 33641.50 | 27-MAY-16:01 | 42.00 |
June | 0.610514E+09 | 35445.22 | 10-JUN-16:01 | 43.12 |
July | 0.807686E+09 | 29797.30 | 02-JUL-17:13 | 40.07 |
August | 0.515003E+09 | 24643.02 | 05-AUG-16:02 | 35.70 |
September | 0.700923E+09 | 23310.25 | 17-SEP-20:10 | 37.37 |
October | 0.536185E+09 | 23599.32 | 01-OCT-13:13 | 35.43 |
November | 0.163791E+09 | 14744.62 | 04-NOV-16:03 | 29.18 |
December | 19048372.55 | 6871.43 | 03-DEC-12:34 | 23.57 |
Annual Sum or Average | 0.476948E+10 | |||
Minimum of Months | 5304976.04 | 2885.00 | 20.25 | |
Maximum of Months | 0.807686E+09 | 35445.22 | 43.12 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213754E+09 | 61816.21 | 02-JAN-05:01 | 6.48 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.213754E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.48 | |
Maximum of Months | 0.213754E+09 | 61816.21 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 388878.10 | 866.17 | 04-JAN-06:06 | 5.65 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 525951.65 | 3161.17 | 21-DEC-06:02 | 5.27 |
Annual Sum or Average | 914829.76 | |||
Minimum of Months | 0.00 | 0.00 | 5.27 | |
Maximum of Months | 525951.65 | 3161.17 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 275671.88 | 1295.46 | 02-JAN-06:03 | 6.45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 211385.47 | 1685.74 | 21-DEC-06:02 | 5.27 |
Annual Sum or Average | 487057.35 | |||
Minimum of Months | 0.00 | 0.00 | 5.27 | |
Maximum of Months | 275671.88 | 1685.74 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13258.43 | 63.64 | 02-JAN-06:06 | 6.45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 13258.43 | |||
Minimum of Months | 0.00 | 0.00 | 6.45 | |
Maximum of Months | 13258.43 | 63.64 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.524939E+09 | 16889.17 | 02-JAN-04:02 | 6.67 |
February | 62815946.89 | 14548.63 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 150598.69 | 1003.99 | 27-NOV-06:05 | 9.55 |
December | 0.172279E+09 | 14760.32 | 21-DEC-06:02 | 5.27 |
Annual Sum or Average | 0.760184E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.27 | |
Maximum of Months | 0.524939E+09 | 16889.17 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213649E+09 | 11558.26 | 02-JAN-04:02 | 6.67 |
February | 17172610.77 | 10063.68 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 52280058.49 | 9962.70 | 21-DEC-06:02 | 5.27 |
Annual Sum or Average | 0.283102E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.27 | |
Maximum of Months | 0.213649E+09 | 11558.26 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135930E+09 | 16402.62 | 02-JAN-05:01 | 6.48 |
February | 14099320.05 | 14539.04 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 19042766.27 | 13168.77 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.169073E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.135930E+09 | 16402.62 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132198E+09 | 11135.38 | 02-JAN-05:01 | 6.48 |
February | 8502235.34 | 9332.46 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 24288928.48 | 8770.27 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.164989E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.132198E+09 | 11135.38 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62735782.19 | 9502.06 | 17-JAN-04:02 | 11.75 |
February | 75948447.63 | 9578.85 | 13-FEB-04:02 | 11.62 |
March | 78625899.78 | 8809.87 | 22-MAR-03:02 | 17.73 |
April | 40611402.68 | 6485.51 | 16-APR-15:01 | 39.63 |
May | 33609943.53 | 6638.71 | 23-MAY-03:02 | 28.47 |
June | 38227238.37 | 6146.39 | 11-JUN-16:22 | 43.25 |
July | 46798007.53 | 5930.67 | 02-JUL-17:01 | 40.18 |
August | 43577048.35 | 6198.35 | 06-AUG-15:01 | 36.30 |
September | 73927733.22 | 8970.93 | 11-SEP-03:02 | 26.07 |
October | 82098626.36 | 8047.52 | 13-OCT-03:02 | 21.62 |
November | 90538828.57 | 8955.83 | 29-NOV-04:02 | 14.55 |
December | 0.105750E+09 | 10769.36 | 29-DEC-04:02 | 16.07 |
Annual Sum or Average | 0.772449E+09 | |||
Minimum of Months | 33609943.53 | 5930.67 | 11.62 | |
Maximum of Months | 0.105750E+09 | 10769.36 | 43.25 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33096618.26 | 6994.09 | 18-JAN-06:02 | 13.58 |
February | 46997298.52 | 6612.17 | 27-FEB-04:02 | 11.72 |
March | 40788910.58 | 6665.58 | 29-MAR-03:02 | 21.75 |
April | 35733557.33 | 7060.86 | 13-APR-03:02 | 24.18 |
May | 36497816.99 | 7447.12 | 24-MAY-03:02 | 26.12 |
June | 32326965.84 | 7701.80 | 21-JUN-03:02 | 28.25 |
July | 43873878.77 | 7760.43 | 28-JUL-03:02 | 27.00 |
August | 40315339.05 | 7758.66 | 17-AUG-03:02 | 27.35 |
September | 52031879.58 | 9740.65 | 11-SEP-03:02 | 26.07 |
October | 44629353.85 | 6335.78 | 11-OCT-03:02 | 24.45 |
November | 43218713.45 | 5990.06 | 28-NOV-05:03 | 15.20 |
December | 45118047.90 | 6799.23 | 22-DEC-06:03 | 12.42 |
Annual Sum or Average | 0.494628E+09 | |||
Minimum of Months | 32326965.84 | 5990.06 | 11.72 | |
Maximum of Months | 52031879.58 | 9740.65 | 28.25 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207829E+10 | 19204.98 | 02-JAN-06:13 | 6.50 |
February | 0.848482E+09 | 19839.23 | 27-FEB-06:03 | 10.82 |
March | 0.281191E+09 | 18415.24 | 02-MAR-06:02 | 14.48 |
April | 83496241.93 | 14581.13 | 10-APR-03:02 | 18.93 |
May | 28171619.45 | 7264.75 | 16-MAY-03:02 | 27.05 |
June | 13273741.18 | 9267.15 | 28-JUN-03:02 | 26.40 |
July | 14467513.80 | 7476.25 | 19-JUL-03:02 | 23.42 |
August | 22204597.61 | 9429.48 | 21-AUG-03:02 | 25.87 |
September | 53615935.55 | 11495.34 | 11-SEP-03:02 | 26.07 |
October | 0.171835E+09 | 17420.98 | 31-OCT-05:02 | 15.53 |
November | 0.512813E+09 | 18295.82 | 13-NOV-06:02 | 15.13 |
December | 0.145542E+10 | 15278.79 | 29-DEC-06:03 | 16.53 |
Annual Sum or Average | 0.556326E+10 | |||
Minimum of Months | 13273741.18 | 7264.75 | 6.50 | |
Maximum of Months | 0.207829E+10 | 19839.23 | 27.05 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61856676.18 | 334.98 | 01-JAN-14:00 | 16.20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 61856676.18 | |||
Minimum of Months | 0.00 | 0.00 | 9.73 | |
Maximum of Months | 61856676.18 | 334.98 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200626E+11 | 20994.62 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.181982E+11 | 20994.62 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.216246E+11 | 20994.62 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.193152E+11 | 20994.62 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.208436E+11 | 20994.62 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.207428E+11 | 20994.62 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.194159E+11 | 20994.62 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.216246E+11 | 20994.62 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.193152E+11 | 20994.62 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.200626E+11 | 20994.62 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.198274E+11 | 20994.62 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.194159E+11 | 20994.62 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.240449E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.181982E+11 | 20994.62 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.216246E+11 | 20994.62 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161367E+10 | 2053.69 | 18-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.143559E+10 | 2020.68 | 10-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.165968E+10 | 2037.36 | 14-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146632E+10 | 1454.29 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.156139E+10 | 1690.49 | 24-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.155299E+10 | 1678.00 | 23-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.147268E+10 | 1974.74 | 26-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.164706E+10 | 2023.33 | 16-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.148954E+10 | 2071.97 | 08-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.157160E+10 | 2158.51 | 11-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.158822E+10 | 2124.33 | 27-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.157724E+10 | 2135.26 | 29-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.186360E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.143559E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.165968E+10 | 2158.51 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103404E+10 | 1316.68 | 17-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.923933E+09 | 1309.00 | 09-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.106837E+10 | 1230.05 | 14-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.946046E+09 | 937.20 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.100982E+10 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.100417E+10 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.950100E+09 | 1241.75 | 26-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.106129E+10 | 1276.47 | 16-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.959766E+09 | 1310.06 | 07-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100873E+10 | 1375.35 | 11-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.102196E+10 | 1392.81 | 27-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.101139E+10 | 1385.08 | 29-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.119996E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.923933E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.106837E+10 | 1392.81 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.157987E+10 | 1993.21 | 18-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.141978E+10 | 1970.72 | 10-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.165425E+10 | 2019.13 | 14-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.146821E+10 | 1454.32 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.156895E+10 | 1742.03 | 24-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.155965E+10 | 1754.19 | 23-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.147808E+10 | 1997.05 | 26-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.164987E+10 | 2033.20 | 16-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148816E+10 | 2069.09 | 08-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.155981E+10 | 2150.01 | 11-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.156167E+10 | 1997.86 | 27-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.153979E+10 | 2079.48 | 29-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.185281E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.141978E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.165425E+10 | 2150.01 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.102971E+10 | 1332.60 | 18-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.919572E+09 | 1315.32 | 10-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107117E+10 | 1346.92 | 14-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.946746E+09 | 1161.65 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.101081E+10 | 1172.53 | 24-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.100409E+10 | 1174.34 | 23-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.952733E+09 | 1301.32 | 26-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.106572E+10 | 1325.08 | 16-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.962276E+09 | 1349.18 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.101505E+10 | 1397.15 | 11-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.101120E+10 | 1298.06 | 03-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.100043E+10 | 1322.25 | 29-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119895E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.919572E+09 | 1161.65 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107117E+10 | 1397.15 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161666E+10 | 2062.64 | 18-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.143698E+10 | 2030.61 | 10-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166082E+10 | 2047.04 | 14-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146672E+10 | 1454.29 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.156301E+10 | 1710.01 | 24-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.155414E+10 | 1697.89 | 23-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.147360E+10 | 1986.21 | 26-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.164848E+10 | 2033.40 | 16-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.149098E+10 | 2080.61 | 08-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.157336E+10 | 2164.62 | 11-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.159039E+10 | 2131.35 | 27-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.158013E+10 | 2141.99 | 29-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.186553E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.143698E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166082E+10 | 2164.62 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103461E+10 | 1318.37 | 17-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.924273E+09 | 1310.64 | 09-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.106879E+10 | 1233.40 | 14-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.946252E+09 | 937.20 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101004E+10 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.100432E+10 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.950449E+09 | 1246.24 | 26-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.106159E+10 | 1279.69 | 16-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.960005E+09 | 1312.79 | 08-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100892E+10 | 1376.92 | 11-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.102246E+10 | 1394.00 | 27-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.101200E+10 | 1386.20 | 29-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120037E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.924273E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.106879E+10 | 1394.00 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158408E+10 | 2006.26 | 18-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.142041E+10 | 1982.43 | 10-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.165504E+10 | 2029.53 | 14-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.146869E+10 | 1454.32 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.156974E+10 | 1759.65 | 24-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.156068E+10 | 1771.33 | 23-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.147944E+10 | 2007.69 | 26-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.165097E+10 | 2042.89 | 16-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148901E+10 | 2077.84 | 08-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.155906E+10 | 2156.47 | 11-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.156263E+10 | 2009.34 | 27-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.154181E+10 | 2088.27 | 29-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.185416E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.142041E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.165504E+10 | 2156.47 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103033E+10 | 1334.11 | 18-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.920065E+09 | 1316.91 | 10-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107162E+10 | 1348.23 | 14-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.946999E+09 | 1165.32 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.101099E+10 | 1175.10 | 24-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.100423E+10 | 1176.91 | 23-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.953207E+09 | 1302.96 | 26-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.106602E+10 | 1326.56 | 16-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.962585E+09 | 1350.48 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.101548E+10 | 1398.10 | 11-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.101159E+10 | 1300.59 | 03-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.100094E+10 | 1324.39 | 29-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119941E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.920065E+09 | 1165.32 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107162E+10 | 1398.10 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161667E+10 | 2062.35 | 18-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.143697E+10 | 2030.29 | 10-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166082E+10 | 2046.81 | 14-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146673E+10 | 1454.29 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.156300E+10 | 1709.49 | 24-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.155410E+10 | 1697.36 | 23-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.147358E+10 | 1985.85 | 26-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.164837E+10 | 2033.08 | 16-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.149096E+10 | 2080.33 | 08-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.157335E+10 | 2164.41 | 11-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.159039E+10 | 2131.24 | 27-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.158015E+10 | 2141.79 | 29-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.186551E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.143697E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166082E+10 | 2164.41 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103462E+10 | 1318.22 | 17-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.924276E+09 | 1310.43 | 09-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.106879E+10 | 1233.32 | 14-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.946256E+09 | 937.20 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101004E+10 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.100432E+10 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.950438E+09 | 1246.05 | 26-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.106158E+10 | 1279.53 | 16-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.960000E+09 | 1312.64 | 08-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100892E+10 | 1376.81 | 11-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.102247E+10 | 1393.93 | 27-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.101202E+10 | 1386.08 | 29-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120037E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.924276E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.106879E+10 | 1393.93 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158409E+10 | 2006.00 | 18-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.142041E+10 | 1982.11 | 10-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.165505E+10 | 2029.30 | 14-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.146869E+10 | 1454.32 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.156973E+10 | 1759.12 | 24-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.156066E+10 | 1770.81 | 23-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.147941E+10 | 2007.33 | 26-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.165095E+10 | 2042.57 | 16-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148899E+10 | 2077.55 | 08-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.155905E+10 | 2156.27 | 11-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.156264E+10 | 2009.29 | 27-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.154185E+10 | 2088.10 | 29-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.185415E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.142041E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.165505E+10 | 2156.27 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103035E+10 | 1333.93 | 18-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.920071E+09 | 1316.71 | 10-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107166E+10 | 1348.07 | 14-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.947004E+09 | 1165.33 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.101099E+10 | 1174.77 | 24-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.100422E+10 | 1176.59 | 23-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.953190E+09 | 1302.74 | 26-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.106600E+10 | 1326.36 | 16-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.962577E+09 | 1350.30 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.101547E+10 | 1397.97 | 11-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.101166E+10 | 1300.54 | 03-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.100095E+10 | 1324.31 | 29-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119941E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.920071E+09 | 1165.33 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107166E+10 | 1397.97 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.565679E+10 | 5919.59 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.513113E+10 | 5919.59 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.609720E+10 | 5919.59 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.544605E+10 | 5919.59 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.587700E+10 | 5919.59 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.584858E+10 | 5919.59 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.547447E+10 | 5919.59 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.609720E+10 | 5919.59 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.544605E+10 | 5919.59 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.565679E+10 | 5919.59 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.559049E+10 | 5919.59 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.547447E+10 | 5919.59 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.677962E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.513113E+10 | 5919.59 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.609720E+10 | 5919.59 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.208436E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.207428E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.198274E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.240449E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.161367E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91304863.12 |
February | 0.136985E+10 | 0.143559E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1566589.00 | 95171720.83 |
March | 0.163685E+10 | 0.165968E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19133966.66 | 55886759.81 |
April | 0.145243E+10 | 0.146632E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74536167.75 | 3040210.32 |
May | 0.157338E+10 | 0.156139E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158472E+09 | 1049217.18 |
June | 0.156900E+10 | 0.155299E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107614E+09 | 597771.53 |
July | 0.145680E+10 | 0.147268E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137585E+09 | 223536.32 |
August | 0.163685E+10 | 0.164706E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79139384.06 | 249796.28 |
September | 0.145243E+10 | 0.148954E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45186489.00 | 1288808.60 |
October | 0.150991E+10 | 0.157160E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23926045.53 | 4489850.26 |
November | 0.149516E+10 | 0.158822E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5199730.54 | 19840662.95 |
December | 0.145680E+10 | 0.157724E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99038.81 | 82692100.26 |
Annual Sum or Average | 0.181194E+11 | 0.186360E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652458E+09 | 0.355835E+09 |
Minimum of Months | 0.136985E+10 | 0.143559E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223536.32 |
Maximum of Months | 0.163685E+10 | 0.165968E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158472E+09 | 95171720.83 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103404E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61284264.03 |
February | 0.882782E+09 | 0.923933E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 913833.91 | 63552372.87 |
March | 0.105485E+10 | 0.106837E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12394280.01 | 35840404.66 |
April | 0.936002E+09 | 0.946046E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49682528.08 | 1657206.07 |
May | 0.101394E+10 | 0.100982E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105203E+09 | 621262.09 |
June | 0.101113E+10 | 0.100417E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73459023.26 | 297084.82 |
July | 0.938820E+09 | 0.950100E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95802374.57 | 83032.77 |
August | 0.105485E+10 | 0.106129E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56369294.33 | 62017.67 |
September | 0.936002E+09 | 0.959766E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30850525.99 | 634952.56 |
October | 0.973041E+09 | 0.100873E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15446076.28 | 2887726.32 |
November | 0.963541E+09 | 0.102196E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3402157.89 | 13244572.56 |
December | 0.938820E+09 | 0.101139E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67097.31 | 54026713.85 |
Annual Sum or Average | 0.116768E+11 | 0.119996E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443591E+09 | 0.234192E+09 |
Minimum of Months | 0.882782E+09 | 0.923933E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62017.67 |
Maximum of Months | 0.105485E+10 | 0.106837E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105203E+09 | 63552372.87 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.157987E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96481646.89 |
February | 0.136988E+10 | 0.141978E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 871612.67 | 0.103999E+09 |
March | 0.163688E+10 | 0.165425E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15994705.66 | 61376942.30 |
April | 0.145246E+10 | 0.146821E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71008675.37 | 3401374.73 |
May | 0.157341E+10 | 0.156895E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157344E+09 | 1065684.72 |
June | 0.156904E+10 | 0.155965E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107693E+09 | 599989.17 |
July | 0.145684E+10 | 0.147808E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137539E+09 | 214376.71 |
August | 0.163688E+10 | 0.164987E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78597771.04 | 269311.55 |
September | 0.145246E+10 | 0.148816E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43557913.71 | 1242886.74 |
October | 0.150994E+10 | 0.155981E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20859138.78 | 5074467.89 |
November | 0.149520E+10 | 0.156167E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3778500.89 | 22765186.51 |
December | 0.145684E+10 | 0.153979E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17145.13 | 90054340.11 |
Annual Sum or Average | 0.181198E+11 | 0.185281E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637261E+09 | 0.386545E+09 |
Minimum of Months | 0.136988E+10 | 0.141978E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214376.71 |
Maximum of Months | 0.163688E+10 | 0.165425E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157344E+09 | 0.103999E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.102971E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66398456.27 |
February | 0.882782E+09 | 0.919572E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 617677.06 | 73682212.14 |
March | 0.105485E+10 | 0.107117E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10668908.02 | 47958503.18 |
April | 0.936002E+09 | 0.946746E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44443698.15 | 4032401.43 |
May | 0.101394E+10 | 0.101081E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102912E+09 | 1032166.42 |
June | 0.101113E+10 | 0.100409E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68828749.92 | 720692.65 |
July | 0.938820E+09 | 0.952733E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86319395.62 | 294048.56 |
August | 0.105485E+10 | 0.106572E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46760439.83 | 534462.71 |
September | 0.936002E+09 | 0.962276E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28918910.86 | 1550481.97 |
October | 0.973041E+09 | 0.101505E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14666875.48 | 3754091.36 |
November | 0.963541E+09 | 0.101120E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2741323.19 | 15762475.66 |
December | 0.938820E+09 | 0.100043E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11545.02 | 65024649.24 |
Annual Sum or Average | 0.116768E+11 | 0.119895E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406889E+09 | 0.280745E+09 |
Minimum of Months | 0.882782E+09 | 0.919572E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294048.56 |
Maximum of Months | 0.105485E+10 | 0.107117E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102912E+09 | 73682212.14 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.161666E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 141065.03 | 0.182132E+09 |
February | 0.136985E+10 | 0.143698E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6258745.23 | 0.195400E+09 |
March | 0.163685E+10 | 0.166082E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45844568.21 | 0.129575E+09 |
April | 0.145243E+10 | 0.146672E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171170E+09 | 11707174.23 |
May | 0.157338E+10 | 0.156301E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360290E+09 | 2924016.12 |
June | 0.156900E+10 | 0.155414E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242925E+09 | 2356919.46 |
July | 0.145680E+10 | 0.147360E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300212E+09 | 942081.89 |
August | 0.163685E+10 | 0.164848E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172813E+09 | 1893888.13 |
September | 0.145243E+10 | 0.149098E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100703E+09 | 3555333.98 |
October | 0.150991E+10 | 0.157336E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56438318.81 | 11013829.80 |
November | 0.149516E+10 | 0.159039E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14718343.46 | 41176133.91 |
December | 0.145680E+10 | 0.158013E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1675484.44 | 0.163904E+09 |
Annual Sum or Average | 0.181194E+11 | 0.186553E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147319E+10 | 0.746581E+09 |
Minimum of Months | 0.136985E+10 | 0.143698E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 141065.03 | 942081.89 |
Maximum of Months | 0.163685E+10 | 0.166082E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360290E+09 | 0.195400E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.103461E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13325.40 | 0.127237E+09 |
February | 0.649041E+09 | 0.924273E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2551445.51 | 0.139059E+09 |
March | 0.773965E+09 | 0.106879E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27058181.48 | 92435310.90 |
April | 0.688021E+09 | 0.946252E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108661E+09 | 8992819.97 |
May | 0.744847E+09 | 0.101004E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237533E+09 | 2035115.90 |
June | 0.742030E+09 | 0.100432E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162825E+09 | 1602713.19 |
July | 0.690839E+09 | 0.950449E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202080E+09 | 600874.99 |
August | 0.773965E+09 | 0.106159E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115603E+09 | 1277114.74 |
September | 0.688021E+09 | 0.960005E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67116457.49 | 2197837.49 |
October | 0.715730E+09 | 0.100892E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35034467.86 | 7895208.01 |
November | 0.708685E+09 | 0.102246E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8331634.98 | 29723660.25 |
December | 0.690839E+09 | 0.101200E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 601373.24 | 0.115511E+09 |
Annual Sum or Average | 0.858171E+10 | 0.120037E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.967409E+09 | 0.528567E+09 |
Minimum of Months | 0.649041E+09 | 0.924273E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13325.40 | 600874.99 |
Maximum of Months | 0.773965E+09 | 0.106879E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237533E+09 | 0.139059E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.158408E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219980E+09 |
February | 0.136988E+10 | 0.142041E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1854000.10 | 0.238970E+09 |
March | 0.163688E+10 | 0.165504E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35439110.64 | 0.152453E+09 |
April | 0.145246E+10 | 0.146869E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161189E+09 | 13798674.78 |
May | 0.157341E+10 | 0.156974E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358090E+09 | 3050543.97 |
June | 0.156904E+10 | 0.156068E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243340E+09 | 2300992.48 |
July | 0.145684E+10 | 0.147944E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300233E+09 | 943169.63 |
August | 0.163688E+10 | 0.165097E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170260E+09 | 1981065.23 |
September | 0.145246E+10 | 0.148901E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96183661.46 | 3891443.38 |
October | 0.150994E+10 | 0.155906E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47208642.59 | 13347837.12 |
November | 0.149520E+10 | 0.156263E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8392227.18 | 53439035.31 |
December | 0.145684E+10 | 0.154181E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29237.36 | 0.206209E+09 |
Annual Sum or Average | 0.181198E+11 | 0.185416E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142222E+10 | 0.910365E+09 |
Minimum of Months | 0.136988E+10 | 0.142041E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 943169.63 |
Maximum of Months | 0.163688E+10 | 0.165504E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358090E+09 | 0.238970E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103033E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131170E+09 |
February | 0.882782E+09 | 0.920065E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2091928.69 | 0.142461E+09 |
March | 0.105485E+10 | 0.107162E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26251045.14 | 0.100582E+09 |
April | 0.936002E+09 | 0.946999E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107209E+09 | 10552830.86 |
May | 0.101394E+10 | 0.101099E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235112E+09 | 2695314.55 |
June | 0.101113E+10 | 0.100423E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158827E+09 | 2121673.65 |
July | 0.938820E+09 | 0.953207E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197143E+09 | 784003.02 |
August | 0.105485E+10 | 0.106602E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112337E+09 | 1635716.68 |
September | 0.936002E+09 | 0.962585E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65389353.78 | 2905783.35 |
October | 0.973041E+09 | 0.101548E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35039359.78 | 8042921.97 |
November | 0.963541E+09 | 0.101159E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8179788.57 | 29731396.30 |
December | 0.938820E+09 | 0.100094E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 404557.99 | 0.118975E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119941E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947985E+09 | 0.551659E+09 |
Minimum of Months | 0.882782E+09 | 0.920065E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 784003.02 |
Maximum of Months | 0.105485E+10 | 0.107162E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235112E+09 | 0.142461E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.161667E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 392441.64 | 0.188412E+09 |
February | 0.136985E+10 | 0.143697E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10215370.88 | 0.213175E+09 |
March | 0.163685E+10 | 0.166082E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56647777.02 | 0.152624E+09 |
April | 0.145243E+10 | 0.146673E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207446E+09 | 14138246.33 |
May | 0.157338E+10 | 0.156300E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439974E+09 | 3678819.84 |
June | 0.156900E+10 | 0.155410E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297038E+09 | 3123361.73 |
July | 0.145680E+10 | 0.147358E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366610E+09 | 1187027.41 |
August | 0.163685E+10 | 0.164837E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209827E+09 | 2599283.24 |
September | 0.145243E+10 | 0.149096E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123180E+09 | 4396860.02 |
October | 0.150991E+10 | 0.157335E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69480443.45 | 12934859.21 |
November | 0.149516E+10 | 0.159039E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20257287.69 | 45222591.56 |
December | 0.145680E+10 | 0.158015E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3324962.99 | 0.173229E+09 |
Annual Sum or Average | 0.181194E+11 | 0.186551E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180439E+10 | 0.814721E+09 |
Minimum of Months | 0.136985E+10 | 0.143697E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 392441.64 | 1187027.41 |
Maximum of Months | 0.163685E+10 | 0.166082E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439974E+09 | 0.213175E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103462E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65011.45 | 0.135266E+09 |
February | 0.882782E+09 | 0.924276E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3781845.48 | 0.157629E+09 |
March | 0.105485E+10 | 0.106879E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32201356.84 | 0.112750E+09 |
April | 0.936002E+09 | 0.946256E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130823E+09 | 11340395.52 |
May | 0.101394E+10 | 0.101004E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288024E+09 | 2666413.11 |
June | 0.101113E+10 | 0.100432E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197875E+09 | 2138722.30 |
July | 0.938820E+09 | 0.950438E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245144E+09 | 774820.56 |
August | 0.105485E+10 | 0.106158E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139331E+09 | 1757266.62 |
September | 0.936002E+09 | 0.960000E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81415394.92 | 2825649.85 |
October | 0.973041E+09 | 0.100892E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42190021.37 | 9676490.44 |
November | 0.963541E+09 | 0.102247E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10507531.78 | 34321856.79 |
December | 0.938820E+09 | 0.101202E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1086303.66 | 0.126078E+09 |
Annual Sum or Average | 0.116768E+11 | 0.120037E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117244E+10 | 0.597223E+09 |
Minimum of Months | 0.882782E+09 | 0.924276E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65011.45 | 774820.56 |
Maximum of Months | 0.105485E+10 | 0.106879E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288024E+09 | 0.157629E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.158409E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243475E+09 |
February | 0.136988E+10 | 0.142041E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2076604.50 | 0.274561E+09 |
March | 0.163688E+10 | 0.165505E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42835129.17 | 0.185194E+09 |
April | 0.145246E+10 | 0.146869E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196374E+09 | 17145867.70 |
May | 0.157341E+10 | 0.156973E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437146E+09 | 3857179.41 |
June | 0.156904E+10 | 0.156066E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297320E+09 | 3067846.98 |
July | 0.145684E+10 | 0.147941E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366426E+09 | 1188676.94 |
August | 0.163688E+10 | 0.165095E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206868E+09 | 2722521.55 |
September | 0.145246E+10 | 0.148899E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117920E+09 | 4913728.41 |
October | 0.150994E+10 | 0.155905E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57575980.20 | 16266024.03 |
November | 0.149520E+10 | 0.156264E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9980671.68 | 62882782.85 |
December | 0.145684E+10 | 0.154185E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24857.13 | 0.232157E+09 |
Annual Sum or Average | 0.181198E+11 | 0.185415E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173455E+10 | 0.104743E+10 |
Minimum of Months | 0.136988E+10 | 0.142041E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1188676.94 |
Maximum of Months | 0.163688E+10 | 0.165505E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437146E+09 | 0.274561E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103035E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12891.05 | 0.144105E+09 |
February | 0.882782E+09 | 0.920071E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3289615.06 | 0.162435E+09 |
March | 0.105485E+10 | 0.107166E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32186575.14 | 0.121527E+09 |
April | 0.936002E+09 | 0.947004E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131230E+09 | 13076826.83 |
May | 0.101394E+10 | 0.101099E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288672E+09 | 3320563.28 |
June | 0.101113E+10 | 0.100422E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195331E+09 | 2596998.40 |
July | 0.938820E+09 | 0.953190E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242818E+09 | 988145.35 |
August | 0.105485E+10 | 0.106600E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137596E+09 | 2172285.51 |
September | 0.936002E+09 | 0.962577E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80638832.02 | 3577089.34 |
October | 0.973041E+09 | 0.101547E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43290897.59 | 9669843.24 |
November | 0.963541E+09 | 0.101166E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10652120.50 | 34170683.54 |
December | 0.938820E+09 | 0.100095E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 667347.26 | 0.132629E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119941E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116638E+10 | 0.630269E+09 |
Minimum of Months | 0.882782E+09 | 0.920071E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12891.05 | 988145.35 |
Maximum of Months | 0.105485E+10 | 0.107166E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288672E+09 | 0.162435E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.565679E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.513113E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.609720E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.544605E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.587700E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.584858E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.547447E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.609720E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.544605E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.565679E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.559049E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.547447E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.677962E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.513113E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.609720E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201323E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1018758.60 | 0.213512E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29708988.62 | 0.130886E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133306E+09 | 9858134.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296153E+09 | 2771589.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200598E+09 | 1460523.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253396E+09 | 694790.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139513E+09 | 1046417.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79944417.28 | 2056090.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40800243.27 | 11184538.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6807208.04 | 46252444.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185859E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118125E+10 | 0.806905E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 694790.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296153E+09 | 0.213512E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341267E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2742506.10 | 0.363278E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54990182.84 | 0.230750E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241294E+09 | 19811319.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535096E+09 | 4976983.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359830E+09 | 2831530.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454209E+09 | 1321640.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250811E+09 | 2195303.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142919E+09 | 3669925.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74032155.07 | 20159522.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13681760.37 | 78591918.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234224.81 | 0.310330E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212984E+10 | 0.137918E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1321640.19 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535096E+09 | 0.363278E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329755E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 716501.58 | 0.368207E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46160419.26 | 0.243634E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239612E+09 | 19079598.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570072E+09 | 5684846.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388214E+09 | 3564368.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475315E+09 | 1379858.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260946E+09 | 3633068.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145497E+09 | 4717351.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70416828.26 | 19795243.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10375023.62 | 76961890.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330795.55 | 0.298426E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220766E+10 | 0.137484E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1379858.09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570072E+09 | 0.368207E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 20994.62 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 20994.62 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 20994.62 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 20994.62 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 20994.62 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 20994.62 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 20994.62 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 20994.62 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 20994.62 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 20994.62 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 20994.62 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 20994.62 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2053.69 | 18-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 237.61 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 2020.68 | 10-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.68 | 19-FEB-15:10 | 311.69 | 09-FEB-22:20 |
March | 2010.79 | 01-MAR-10:09 | 2037.36 | 14-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 221.92 | 26-MAR-15:00 | 688.33 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1454.29 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.35 | 15-APR-17:02 | 99.18 | 22-APR-17:50 |
May | 2010.79 | 01-MAY-09:09 | 1690.49 | 24-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 612.38 | 28-MAY-14:25 | 47.38 | 13-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 1678.00 | 23-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 307.61 | 17-JUN-20:50 | 48.67 | 18-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 1974.74 | 26-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.30 | 02-JUL-11:50 | 41.56 | 19-JUL-02:30 |
August | 2010.79 | 01-AUG-09:09 | 2023.33 | 16-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.88 | 06-AUG-13:47 | 40.43 | 15-AUG-23:50 |
September | 2010.79 | 01-SEP-09:09 | 2071.97 | 08-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.85 | 24-SEP-14:50 | 28.22 | 08-SEP-22:20 |
October | 2010.79 | 02-OCT-09:09 | 2158.51 | 11-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.60 | 15-OCT-12:10 | 95.91 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2124.33 | 27-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.44 | 12-NOV-14:00 | 156.22 | 28-NOV-04:43 |
December | 2010.79 | 01-DEC-10:09 | 2135.26 | 29-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 | 24-DEC-14:10 | 367.18 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.22 | |||||
Maximum of Months | 2010.79 | 2158.51 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 612.38 | 688.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1316.68 | 17-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 155.11 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1309.00 | 09-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 | 19-FEB-15:10 | 197.95 | 09-FEB-22:20 |
March | 1295.83 | 01-MAR-10:09 | 1230.05 | 14-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 141.67 | 26-MAR-15:00 | 451.85 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 937.20 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.87 | 15-APR-17:02 | 59.75 | 22-APR-17:50 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 406.33 | 28-MAY-14:24 | 30.95 | 15-MAY-02:40 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.59 | 17-JUN-21:10 | 28.22 | 18-JUN-05:10 |
July | 1295.83 | 03-JUL-09:09 | 1241.75 | 26-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.85 | 02-JUL-11:45 | 22.43 | 19-JUL-02:30 |
August | 1295.83 | 01-AUG-09:09 | 1276.47 | 16-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.73 | 06-AUG-13:50 | 20.64 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 1310.06 | 07-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.23 | 24-SEP-14:10 | 15.83 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1375.35 | 11-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.55 | 15-OCT-12:10 | 59.05 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1392.81 | 27-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.89 | 12-NOV-14:00 | 100.71 | 28-NOV-04:43 |
December | 1295.83 | 01-DEC-10:09 | 1385.08 | 29-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.80 | 24-DEC-14:10 | 230.16 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | |||||
Maximum of Months | 1295.83 | 1392.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 406.33 | 451.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1993.21 | 18-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 241.52 | 22-JAN-14:13 |
February | 2010.83 | 01-FEB-10:09 | 1970.72 | 10-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 | 21-FEB-15:00 | 307.14 | 09-FEB-22:20 |
March | 2010.83 | 01-MAR-10:09 | 2019.13 | 14-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.17 | 26-MAR-14:58 | 746.89 | 24-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1454.32 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.70 | 15-APR-17:02 | 104.79 | 22-APR-17:50 |
May | 2010.83 | 01-MAY-09:09 | 1742.03 | 24-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 604.46 | 28-MAY-14:24 | 49.27 | 15-MAY-02:40 |
June | 2010.83 | 01-JUN-09:09 | 1754.19 | 23-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.43 | 17-JUN-20:35 | 49.22 | 18-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 1997.05 | 26-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 301.28 | 02-JUL-11:47 | 40.99 | 19-JUL-02:30 |
August | 2010.83 | 01-AUG-09:09 | 2033.20 | 16-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.66 | 06-AUG-13:45 | 41.73 | 15-AUG-23:50 |
September | 2010.83 | 01-SEP-09:09 | 2069.09 | 08-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.52 | 24-SEP-14:06 | 27.09 | 08-SEP-22:20 |
October | 2010.83 | 02-OCT-09:09 | 2150.01 | 11-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.63 | 15-OCT-12:45 | 96.17 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1997.86 | 27-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.90 | 12-NOV-14:35 | 170.47 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 2079.48 | 29-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 | 28-DEC-14:00 | 405.43 | 31-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 | |||||
Maximum of Months | 2010.83 | 2150.01 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 604.46 | 746.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1332.60 | 18-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 170.84 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1315.32 | 10-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 | 21-FEB-15:00 | 229.10 | 09-FEB-22:20 |
March | 1295.83 | 01-MAR-10:09 | 1346.92 | 14-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.74 | 26-MAR-13:00 | 616.82 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1161.65 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.74 | 15-APR-17:07 | 115.48 | 22-APR-17:50 |
May | 1295.83 | 01-MAY-09:09 | 1172.53 | 24-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.70 | 28-MAY-13:44 | 45.28 | 15-MAY-02:40 |
June | 1295.83 | 01-JUN-09:09 | 1174.34 | 23-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.90 | 17-JUN-21:10 | 47.14 | 18-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 1301.32 | 26-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.44 | 02-JUL-11:47 | 41.55 | 19-JUL-02:30 |
August | 1295.83 | 01-AUG-09:09 | 1325.08 | 16-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.13 | 06-AUG-09:46 | 47.85 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 1349.18 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.89 | 24-SEP-14:06 | 26.93 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1397.15 | 11-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.15 | 15-OCT-12:10 | 78.78 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1298.06 | 03-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.70 | 12-NOV-12:40 | 128.35 | 29-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 1322.25 | 29-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 | 28-DEC-14:00 | 293.23 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1161.65 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.93 | |||||
Maximum of Months | 1295.83 | 1397.15 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 405.70 | 616.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2062.64 | 18-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.81 | 08-JAN-15:00 | 476.68 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 2030.61 | 10-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 208.65 | 19-FEB-15:00 | 652.28 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 2047.04 | 14-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 553.85 | 26-MAR-15:00 | 1327.01 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1454.29 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 856.86 | 15-APR-17:02 | 207.48 | 22-APR-18:30 |
May | 2010.79 | 01-MAY-09:09 | 1710.01 | 24-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1426.61 | 28-MAY-14:56 | 119.57 | 15-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 1697.89 | 23-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 703.88 | 17-JUN-20:50 | 119.22 | 18-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 1986.21 | 26-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 710.95 | 02-JUL-12:08 | 107.25 | 19-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 2033.40 | 16-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.16 | 06-AUG-09:00 | 125.16 | 15-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 2080.61 | 08-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.55 | 24-SEP-14:20 | 53.43 | 08-SEP-22:20 |
October | 2010.79 | 02-OCT-09:09 | 2164.62 | 11-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 511.96 | 15-OCT-12:10 | 211.35 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2131.35 | 27-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.34 | 12-NOV-14:00 | 337.17 | 28-NOV-04:53 |
December | 2010.79 | 01-DEC-10:09 | 2141.99 | 29-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 141.18 | 24-DEC-14:10 | 720.80 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 29.81 | 53.43 | |||||
Maximum of Months | 2010.79 | 2164.62 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1426.61 | 1327.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1318.37 | 17-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 | 08-JAN-15:00 | 316.88 | 15-JAN-17:00 |
February | 1239.33 | 01-FEB-08:09 | 1310.64 | 09-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 107.20 | 19-FEB-15:00 | 425.96 | 18-FEB-06:00 |
March | 1239.33 | 01-MAR-08:09 | 1233.40 | 14-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.87 | 26-MAR-15:00 | 941.06 | 24-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 937.20 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 561.90 | 15-APR-17:02 | 157.03 | 22-APR-18:10 |
May | 1239.33 | 01-MAY-07:10 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 956.08 | 28-MAY-14:54 | 89.34 | 15-MAY-03:00 |
June | 1239.33 | 01-JUN-07:10 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.83 | 17-JUN-20:50 | 79.17 | 18-JUN-05:00 |
July | 1239.33 | 03-JUL-07:10 | 1246.24 | 26-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.41 | 02-JUL-12:08 | 69.74 | 19-JUL-02:55 |
August | 1239.33 | 01-AUG-07:10 | 1279.69 | 16-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.39 | 06-AUG-14:20 | 86.02 | 15-AUG-24:00 |
September | 1239.33 | 01-SEP-07:10 | 1312.79 | 08-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.39 | 24-SEP-15:00 | 32.24 | 08-SEP-22:20 |
October | 1239.33 | 02-OCT-07:10 | 1376.92 | 11-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.55 | 15-OCT-12:50 | 140.43 | 12-OCT-03:00 |
November | 1239.33 | 01-NOV-07:10 | 1394.00 | 27-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.61 | 12-NOV-14:00 | 232.34 | 28-NOV-04:53 |
December | 1239.33 | 01-DEC-08:09 | 1386.20 | 29-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.91 | 24-DEC-14:10 | 470.90 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 | 32.24 | |||||
Maximum of Months | 1239.33 | 1394.00 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 956.08 | 941.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2006.26 | 18-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 574.19 | 22-JAN-14:50 |
February | 2010.83 | 01-FEB-10:09 | 1982.43 | 10-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.20 | 21-FEB-15:00 | 677.82 | 18-FEB-05:53 |
March | 2010.83 | 01-MAR-10:09 | 2029.53 | 14-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 355.75 | 26-MAR-14:58 | 1528.21 | 24-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1454.32 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 817.93 | 15-APR-17:02 | 234.31 | 22-APR-18:10 |
May | 2010.83 | 01-MAY-09:09 | 1759.65 | 24-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1429.77 | 28-MAY-14:54 | 129.34 | 15-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 1771.33 | 23-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 709.81 | 17-JUN-20:50 | 118.05 | 18-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 2007.69 | 26-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 710.81 | 02-JUL-12:08 | 106.87 | 19-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 2042.89 | 16-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.15 | 06-AUG-09:00 | 128.43 | 15-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 2077.84 | 08-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 371.86 | 24-SEP-14:55 | 54.18 | 08-SEP-22:20 |
October | 2010.83 | 02-OCT-09:09 | 2156.47 | 11-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.08 | 15-OCT-13:24 | 218.73 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2009.34 | 27-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.22 | 13-NOV-14:00 | 388.12 | 28-NOV-04:53 |
December | 2010.83 | 01-DEC-10:09 | 2088.27 | 29-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 28-DEC-14:00 | 933.47 | 31-DEC-14:27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.18 | |||||
Maximum of Months | 2010.83 | 2156.47 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1429.77 | 1528.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1334.11 | 18-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 330.84 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1316.91 | 10-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.08 | 19-FEB-14:20 | 437.83 | 18-FEB-06:00 |
March | 1295.83 | 01-MAR-10:09 | 1348.23 | 14-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 328.18 | 26-MAR-13:00 | 1037.32 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1165.32 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 530.89 | 15-APR-17:08 | 162.98 | 22-APR-18:10 |
May | 1295.83 | 01-MAY-09:09 | 1175.10 | 24-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 940.55 | 28-MAY-14:15 | 114.16 | 15-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 1176.91 | 23-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 453.78 | 17-JUN-20:35 | 95.41 | 18-JUN-04:03 |
July | 1295.83 | 03-JUL-09:09 | 1302.96 | 26-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 488.10 | 02-JUL-12:10 | 75.50 | 19-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 1326.56 | 16-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.67 | 06-AUG-09:40 | 93.62 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1350.48 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.21 | 24-SEP-14:15 | 36.68 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1398.10 | 11-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.71 | 15-OCT-12:10 | 146.53 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1300.59 | 03-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.07 | 12-NOV-13:20 | 242.16 | 28-NOV-04:53 |
December | 1295.83 | 01-DEC-10:09 | 1324.39 | 29-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.10 | 24-DEC-13:43 | 493.06 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1165.32 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.68 | |||||
Maximum of Months | 1295.83 | 1398.10 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 940.55 | 1037.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2062.35 | 18-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.35 | 08-JAN-15:00 | 502.41 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 2030.29 | 10-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 279.84 | 19-FEB-15:10 | 735.41 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 2046.81 | 14-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 675.22 | 26-MAR-15:00 | 1525.99 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1454.29 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1027.08 | 15-APR-17:02 | 235.01 | 22-APR-18:30 |
May | 2010.79 | 01-MAY-09:09 | 1709.49 | 24-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1738.15 | 28-MAY-13:56 | 154.86 | 15-MAY-02:28 |
June | 2010.79 | 01-JUN-09:09 | 1697.36 | 23-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 833.43 | 17-JUN-20:50 | 158.38 | 18-JUN-04:03 |
July | 2010.79 | 03-JUL-09:09 | 1985.85 | 26-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 869.57 | 02-JUL-11:58 | 130.63 | 19-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 2033.08 | 16-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.84 | 06-AUG-09:20 | 171.20 | 15-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 2080.33 | 08-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 487.17 | 24-SEP-14:30 | 59.39 | 08-SEP-22:20 |
October | 2010.79 | 02-OCT-09:09 | 2164.41 | 11-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 639.38 | 15-OCT-12:20 | 246.90 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2131.24 | 27-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.50 | 12-NOV-13:50 | 367.41 | 28-NOV-04:53 |
December | 2010.79 | 01-DEC-10:09 | 2141.79 | 29-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 231.72 | 24-DEC-14:10 | 790.05 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 63.35 | 59.39 | |||||
Maximum of Months | 2010.79 | 2164.41 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1738.15 | 1525.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1318.22 | 17-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 08-JAN-15:00 | 334.40 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1310.43 | 09-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 140.59 | 19-FEB-15:10 | 486.04 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 1233.32 | 14-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 392.78 | 26-MAR-15:00 | 1104.25 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 937.20 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 663.71 | 15-APR-17:02 | 184.80 | 22-APR-18:10 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.07 | 28-MAY-14:54 | 116.68 | 15-MAY-02:28 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 567.43 | 17-JUN-21:10 | 106.21 | 18-JUN-04:03 |
July | 1295.83 | 03-JUL-09:09 | 1246.05 | 26-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 583.79 | 02-JUL-11:58 | 85.40 | 19-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 1279.53 | 16-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.56 | 06-AUG-14:00 | 117.77 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1312.64 | 08-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.20 | 24-SEP-14:30 | 36.55 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1376.81 | 11-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.50 | 15-OCT-13:00 | 165.06 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1393.93 | 27-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.90 | 12-NOV-13:50 | 258.70 | 28-NOV-04:53 |
December | 1295.83 | 01-DEC-10:09 | 1386.08 | 29-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.29 | 24-DEC-14:40 | 523.70 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 36.55 | |||||
Maximum of Months | 1295.83 | 1393.93 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.07 | 1104.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2006.00 | 18-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 664.79 | 22-JAN-15:00 |
February | 2010.83 | 01-FEB-10:09 | 1982.11 | 10-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.31 | 21-FEB-15:00 | 777.64 | 18-FEB-05:53 |
March | 2010.83 | 01-MAR-10:09 | 2029.30 | 14-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 442.80 | 26-MAR-14:58 | 1804.80 | 24-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1454.32 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 975.31 | 15-APR-17:02 | 271.56 | 22-APR-18:10 |
May | 2010.83 | 01-MAY-09:09 | 1759.12 | 24-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1720.61 | 28-MAY-14:53 | 166.88 | 15-MAY-02:28 |
June | 2010.83 | 01-JUN-09:09 | 1770.81 | 23-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 838.79 | 17-JUN-20:50 | 156.91 | 18-JUN-04:03 |
July | 2010.83 | 03-JUL-09:09 | 2007.33 | 26-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 867.64 | 02-JUL-11:58 | 130.15 | 19-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 2042.57 | 16-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 587.68 | 06-AUG-09:20 | 175.58 | 15-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 2077.55 | 08-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.23 | 24-SEP-14:28 | 60.42 | 08-SEP-22:20 |
October | 2010.83 | 02-OCT-09:09 | 2156.27 | 11-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 475.92 | 15-OCT-12:15 | 256.95 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2009.29 | 27-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.43 | 12-NOV-14:25 | 440.75 | 28-NOV-04:53 |
December | 2010.83 | 01-DEC-10:09 | 2088.10 | 29-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 28-DEC-14:00 | 1074.19 | 31-DEC-14:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.42 | |||||
Maximum of Months | 2010.83 | 2156.27 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1720.61 | 1804.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1333.93 | 18-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 | 08-JAN-13:57 | 362.78 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1316.71 | 10-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 111.13 | 19-FEB-13:50 | 503.76 | 18-FEB-05:53 |
March | 1295.83 | 01-MAR-10:09 | 1348.07 | 14-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 400.61 | 26-MAR-13:00 | 1219.68 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1165.33 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 652.30 | 15-APR-17:08 | 187.56 | 22-APR-18:10 |
May | 1295.83 | 01-MAY-09:09 | 1174.77 | 24-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.07 | 28-MAY-14:54 | 139.10 | 15-MAY-02:28 |
June | 1295.83 | 01-JUN-09:09 | 1176.59 | 23-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 546.47 | 17-JUN-21:10 | 123.17 | 18-JUN-03:55 |
July | 1295.83 | 03-JUL-09:09 | 1302.74 | 26-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 597.34 | 02-JUL-12:00 | 91.89 | 19-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 1326.36 | 16-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.10 | 06-AUG-09:20 | 126.41 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1350.30 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.03 | 24-SEP-14:28 | 40.67 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1397.97 | 11-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 445.74 | 15-OCT-12:20 | 172.53 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1300.54 | 03-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.53 | 12-NOV-13:10 | 273.49 | 28-NOV-04:53 |
December | 1295.83 | 01-DEC-10:09 | 1324.31 | 29-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.56 | 24-DEC-13:40 | 549.94 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1165.33 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 | 40.67 | |||||
Maximum of Months | 1295.83 | 1397.97 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.07 | 1219.68 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5919.59 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5919.59 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5919.59 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5919.59 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5919.59 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5919.59 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5919.59 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5919.59 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5919.59 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5919.59 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5919.59 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5919.59 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 491.45 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.26 | 19-FEB-14:52 | 696.13 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.37 | 26-MAR-14:42 | 1458.00 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 715.93 | 15-APR-17:02 | 208.45 | 22-APR-17:56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1227.71 | 28-MAY-14:51 | 86.97 | 13-MAY-03:04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.17 | 03-JUN-17:02 | 92.41 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.38 | 02-JUL-12:00 | 78.68 | 19-JUL-02:38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.58 | 06-AUG-14:00 | 77.81 | 15-AUG-23:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.42 | 24-SEP-14:30 | 38.85 | 08-SEP-22:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.71 | 15-OCT-12:30 | 185.27 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.63 | 12-NOV-14:20 | 352.21 | 28-NOV-04:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 776.90 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.85 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1227.71 | 1458.00 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 827.14 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.84 | 19-FEB-15:00 | 1213.61 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 694.90 | 26-MAR-14:42 | 2473.87 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1310.19 | 15-APR-17:02 | 354.96 | 22-APR-18:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2204.89 | 28-MAY-14:40 | 155.78 | 13-MAY-03:04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.19 | 03-JUN-17:02 | 166.49 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1107.28 | 02-JUL-11:50 | 144.71 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 739.89 | 06-AUG-14:00 | 153.28 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.19 | 24-SEP-14:00 | 67.09 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.55 | 15-OCT-12:30 | 327.30 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.35 | 12-NOV-14:00 | 607.37 | 28-NOV-05:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.21 | 24-DEC-13:52 | 1318.72 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.09 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2204.89 | 2473.87 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 809.17 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.54 | 19-FEB-14:52 | 1230.15 | 09-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.26 | 26-MAR-14:40 | 2445.47 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.94 | 15-APR-17:02 | 302.69 | 22-APR-18:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2164.30 | 28-MAY-15:00 | 179.96 | 13-MAY-03:04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1127.02 | 17-JUN-20:50 | 201.13 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1032.49 | 02-JUL-10:52 | 156.97 | 19-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 698.32 | 06-AUG-08:52 | 225.39 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 535.44 | 24-SEP-14:10 | 64.37 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 628.77 | 15-OCT-11:52 | 350.27 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.09 | 12-NOV-14:10 | 569.61 | 28-NOV-04:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.42 | 24-DEC-15:00 | 1261.40 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.37 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2164.30 | 2445.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 103951.05 | 02-JAN-04:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 109229.72 | 06-FEB-04:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 99597.32 | 20-MAR-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 103960.08 | 28-APR-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 101121.25 | 29-MAY-17:30 | 0.00 | 8164.98 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 97197.30 | 04-JUN-16:18 | 8078.51 | 10497.83 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 90226.06 | 04-JUL-17:50 | 0.00 | 8164.98 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89891.21 | 22-AUG-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 91295.74 | 26-SEP-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 101896.69 | 22-OCT-14:58 | 5385.68 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 100328.77 | 25-NOV-04:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 104029.50 | 04-DEC-04:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 89891.21 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 109229.72 | 8078.51 | 10497.83 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 99916.88 | 02-JAN-04:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 99228.75 | 27-FEB-04:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96286.94 | 20-MAR-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91047.23 | 03-APR-05:03 | 9673.43 | 12570.39 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 90543.43 | 23-MAY-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89334.66 | 12-JUN-05:02 | 9673.43 | 12570.39 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88616.29 | 03-JUL-05:05 | 9673.43 | 12570.39 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89718.17 | 07-AUG-05:01 | 11285.67 | 14665.45 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92135.53 | 09-SEP-03:02 | 0.00 | 5237.66 | 30214.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96183.40 | 31-OCT-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98643.62 | 27-NOV-04:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 97215.02 | 04-DEC-04:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 88616.29 | 0.00 | 5237.66 | 30214.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99916.88 | 11285.67 | 14665.45 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 84447.06 | 14-JAN-06:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 89117.55 | 27-FEB-04:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88362.11 | 14-MAR-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88104.09 | 10-APR-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85296.08 | 23-MAY-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85511.90 | 28-JUN-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 86492.59 | 19-JUL-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85206.90 | 24-AUG-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86005.11 | 05-SEP-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88145.15 | 24-OCT-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 85450.51 | 21-NOV-05:03 | 0.00 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 84218.72 | 16-DEC-06:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 84218.72 | 0.00 | 5237.66 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89117.55 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 38168.36 | 26-JAN-16:20 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83378.14 | 23-FEB-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90633.37 | 30-MAR-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88943.51 | 17-APR-05:03 | 9673.43 | 12570.39 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88053.44 | 30-MAY-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89421.07 | 12-JUN-05:02 | 9673.43 | 12570.39 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88435.22 | 28-JUL-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 90084.88 | 21-AUG-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 91320.89 | 11-SEP-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89812.63 | 05-OCT-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 85308.42 | 01-NOV-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 64695.22 | 29-DEC-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 38168.36 | 0.00 | 5237.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91320.89 | 15316.26 | 18854.65 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5168.16 | 26-JAN-14:10 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 |
February | 6947.13 | 23-FEB-14:30 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 | 0.00 |
March | 14150.29 | 14-MAR-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.63 |
April | 17247.52 | 17-APR-05:02 | 1214.60 | 1578.34 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
May | 20475.13 | 29-MAY-16:11 | 1012.16 | 807.98 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 196.83 | 0.00 |
June | 20164.92 | 11-JUN-17:02 | 0.00 | 484.79 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 99.48 | 0.00 |
July | 21474.38 | 02-JUL-16:21 | 910.95 | 727.18 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 171.23 | 0.00 |
August | 19657.47 | 06-AUG-15:01 | 708.51 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 179.84 | 0.00 |
September | 17183.10 | 05-SEP-03:02 | 0.00 | 657.64 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 | 0.00 |
October | 15461.45 | 11-OCT-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 |
November | 9034.84 | 06-NOV-06:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6111.32 | 26-DEC-14:10 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5168.16 | 0.00 | 484.79 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21474.38 | 2010.79 | 1578.34 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 196.83 | 9.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4508.41 | 26-JAN-10:20 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 |
February | 7097.53 | 21-FEB-09:50 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 |
March | 11885.31 | 26-MAR-09:32 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 |
April | 17253.71 | 16-APR-09:42 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 13.04 | 0.00 |
May | 17873.96 | 29-MAY-08:51 | 456.59 | 364.48 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 222.01 | 0.00 |
June | 15997.03 | 11-JUN-10:22 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 64.26 | 0.00 |
July | 16552.48 | 02-JUL-15:41 | 587.05 | 468.62 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 115.57 | 0.00 |
August | 16125.85 | 06-AUG-10:22 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 101.42 | 0.00 |
September | 11630.22 | 11-SEP-05:03 | 521.82 | 678.09 | 2607.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 0.00 |
October | 13649.40 | 09-OCT-10:13 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6745.81 | 13-NOV-09:50 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
December | 5008.55 | 01-DEC-10:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4508.41 | 260.91 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17873.96 | 1295.83 | 937.20 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 222.01 | 23.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12576.52 | 12-JAN-13:40 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.07 |
February | 22076.29 | 20-FEB-14:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 |
March | 21384.44 | 12-MAR-12:13 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 |
April | 21642.96 | 16-APR-11:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 66.24 | 0.00 |
May | 20920.49 | 29-MAY-16:11 | 1012.19 | 807.99 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 195.98 | 0.00 |
June | 20152.06 | 11-JUN-16:22 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 110.76 | 0.00 |
July | 21826.65 | 02-JUL-16:21 | 910.97 | 727.20 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 171.42 | 0.00 |
August | 20805.29 | 06-AUG-15:01 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 175.64 | 0.00 |
September | 21889.53 | 24-SEP-13:22 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 123.13 | 0.00 |
October | 23070.20 | 09-OCT-12:52 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 13.28 | 0.00 |
November | 21636.63 | 19-NOV-12:53 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 |
December | 21285.83 | 03-DEC-12:02 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12576.52 | 404.87 | 323.20 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23070.20 | 1923.15 | 1454.32 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 195.98 | 10.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7243.53 | 31-JAN-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 |
February | 20874.59 | 20-FEB-16:02 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 |
March | 19808.32 | 26-MAR-16:12 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 72.61 | 0.00 |
April | 22754.91 | 30-APR-16:21 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 155.31 | 0.00 |
May | 22379.18 | 28-MAY-16:21 | 652.28 | 520.69 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 324.90 | 0.00 |
June | 22436.19 | 18-JUN-15:52 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 18.29 | 0.00 |
July | 24575.11 | 02-JUL-16:21 | 587.05 | 468.62 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 97.32 | 0.00 |
August | 22365.96 | 06-AUG-15:41 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 96.25 | 0.00 |
September | 22119.60 | 24-SEP-15:22 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 80.21 | 0.00 |
October | 22262.12 | 15-OCT-15:22 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 64.48 | 0.00 |
November | 16368.41 | 06-NOV-06:03 | 521.82 | 678.09 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16473.23 | 29-DEC-06:03 | 521.82 | 678.09 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7243.53 | 326.14 | 260.35 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24575.11 | 1239.33 | 937.20 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 324.90 | 52.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4060.34 | 14-JAN-06:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.04 |
February | 5793.28 | 24-FEB-15:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 0.00 |
March | 14190.40 | 11-MAR-06:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 |
April | 15096.75 | 16-APR-17:12 | 0.00 | 484.79 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 71.66 | 0.00 |
May | 20757.40 | 28-MAY-15:31 | 809.73 | 646.38 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 1262.03 | 0.00 |
June | 19544.74 | 11-JUN-17:02 | 0.00 | 484.79 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 231.83 | 0.00 |
July | 19519.38 | 02-JUL-16:42 | 607.30 | 484.79 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 427.01 | 0.00 |
August | 16589.55 | 07-AUG-05:03 | 1417.03 | 1841.39 | 7081.88 | 0.00 | 0.00 | 0.00 | 0.00 | 27.56 | 0.00 |
September | 16677.96 | 05-SEP-03:02 | 0.00 | 657.64 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 0.00 |
October | 14472.00 | 03-OCT-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
November | 6134.11 | 09-NOV-14:30 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 | 0.00 |
December | 4268.30 | 03-DEC-14:13 | 404.87 | 323.19 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4060.34 | 0.00 | 323.19 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20757.40 | 2010.79 | 1841.39 | 7081.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1262.03 | 90.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3555.07 | 08-JAN-13:32 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.30 |
February | 6183.97 | 22-FEB-10:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 |
March | 12412.53 | 12-MAR-11:23 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 21.05 | 0.00 |
April | 18167.11 | 16-APR-09:12 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 16.09 | 0.00 |
May | 18541.85 | 29-MAY-08:51 | 456.59 | 364.48 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 495.29 | 0.00 |
June | 16682.48 | 11-JUN-10:22 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 147.67 | 0.00 |
July | 16519.72 | 02-JUL-12:02 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 423.74 | 0.00 |
August | 13720.98 | 06-AUG-15:31 | 587.05 | 468.62 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 263.55 | 0.00 |
September | 15032.16 | 24-SEP-10:13 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 74.13 | 0.00 |
October | 17084.87 | 01-OCT-09:52 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 | 0.00 |
November | 6180.83 | 09-NOV-10:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 0.00 |
December | 4094.76 | 01-DEC-10:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3555.07 | 260.91 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18541.85 | 1239.33 | 937.20 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 495.29 | 24.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19532.51 | 08-JAN-13:32 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.92 |
February | 21358.36 | 20-FEB-13:52 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.79 |
March | 21297.94 | 12-MAR-13:22 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 34.57 | 0.00 |
April | 20807.26 | 16-APR-11:52 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 164.33 | 0.00 |
May | 21077.93 | 28-MAY-15:31 | 809.75 | 646.40 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1253.64 | 0.00 |
June | 18514.64 | 11-JUN-16:22 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 258.23 | 0.00 |
July | 19866.79 | 30-JUL-15:32 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 320.64 | 0.00 |
August | 20003.02 | 06-AUG-14:51 | 809.75 | 646.40 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 416.38 | 0.00 |
September | 20757.08 | 24-SEP-16:12 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 233.53 | 0.00 |
October | 22870.36 | 01-OCT-13:11 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 150.24 | 0.00 |
November | 21631.53 | 11-NOV-12:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 |
December | 20688.27 | 03-DEC-12:53 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18514.64 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22870.36 | 809.75 | 646.40 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1253.64 | 113.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5129.19 | 31-JAN-16:10 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 |
February | 7454.26 | 21-FEB-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 | 0.00 |
March | 16641.04 | 12-MAR-16:02 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 87.79 | 0.00 |
April | 19104.66 | 30-APR-16:11 | 652.28 | 520.69 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 365.88 | 0.00 |
May | 20637.36 | 28-MAY-15:31 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 737.72 | 0.00 |
June | 18671.21 | 11-JUN-16:22 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 160.60 | 0.00 |
July | 18492.31 | 02-JUL-16:42 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 264.95 | 0.00 |
August | 18437.69 | 06-AUG-16:11 | 587.05 | 468.62 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 218.49 | 0.00 |
September | 18845.57 | 24-SEP-16:12 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 145.32 | 0.00 |
October | 18836.35 | 01-OCT-16:32 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 56.22 | 0.00 |
November | 8153.10 | 11-NOV-15:22 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 13.42 | 0.00 |
December | 5567.63 | 01-DEC-15:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5129.19 | 326.14 | 260.35 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20637.36 | 1239.33 | 937.20 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 737.72 | 20.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3935.55 | 26-JAN-15:10 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.76 |
February | 5857.82 | 23-FEB-14:50 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 | 0.00 |
March | 13337.96 | 30-MAR-05:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 |
April | 22585.54 | 30-APR-16:01 | 809.73 | 646.38 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 785.45 | 0.00 |
May | 23646.01 | 28-MAY-16:31 | 708.51 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.40 | 0.00 |
June | 23411.41 | 11-JUN-16:22 | 607.30 | 484.79 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 311.27 | 0.00 |
July | 23774.53 | 02-JUL-13:12 | 506.08 | 403.99 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 634.05 | 0.00 |
August | 19555.61 | 21-AUG-03:02 | 0.00 | 657.64 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22757.80 | 17-SEP-15:22 | 607.30 | 484.79 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 331.47 | 0.00 |
October | 17338.00 | 01-OCT-15:21 | 708.51 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 196.62 | 0.00 |
November | 6498.77 | 09-NOV-14:50 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 | 0.00 |
December | 3904.05 | 28-DEC-16:30 | 1923.11 | 1740.80 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3904.05 | 0.00 | 403.99 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23774.53 | 2010.79 | 1740.80 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.40 | 32.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3123.41 | 26-JAN-14:50 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.92 |
February | 5712.13 | 23-FEB-10:40 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 |
March | 10150.85 | 30-MAR-05:02 | 652.28 | 847.62 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 |
April | 19303.45 | 30-APR-10:02 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 94.15 | 0.00 |
May | 18767.72 | 29-MAY-09:42 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 795.92 | 0.00 |
June | 18001.42 | 11-JUN-10:22 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 179.11 | 0.00 |
July | 18647.13 | 02-JUL-09:12 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 369.26 | 0.00 |
August | 14173.33 | 06-AUG-15:12 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 332.47 | 0.00 |
September | 17654.60 | 17-SEP-15:22 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 211.22 | 0.00 |
October | 18087.22 | 01-OCT-10:42 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 68.19 | 0.00 |
November | 5822.99 | 09-NOV-10:30 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2.57 | 0.00 |
December | 3136.89 | 01-DEC-15:10 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3123.41 | 326.14 | 260.35 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19303.45 | 1295.83 | 937.20 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 795.92 | 22.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12079.49 | 12-JAN-14:20 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 |
February | 23757.35 | 20-FEB-13:32 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 |
March | 23817.90 | 12-MAR-12:13 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 45.02 | 0.00 |
April | 24374.25 | 30-APR-13:22 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 604.08 | 0.00 |
May | 23759.38 | 28-MAY-15:51 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1571.95 | 0.00 |
June | 23354.92 | 11-JUN-16:22 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 312.52 | 0.00 |
July | 24004.33 | 02-JUL-13:12 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 627.82 | 0.00 |
August | 21165.32 | 06-AUG-15:12 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 499.23 | 0.00 |
September | 24663.08 | 17-SEP-15:22 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 279.51 | 0.00 |
October | 26297.07 | 01-OCT-15:21 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 148.10 | 0.00 |
November | 25516.90 | 12-NOV-13:42 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 |
December | 13620.39 | 01-DEC-13:50 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12079.49 | 404.87 | 323.20 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26297.07 | 2010.83 | 1454.32 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1571.95 | 19.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4618.69 | 31-JAN-16:10 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.46 |
February | 7456.53 | 21-FEB-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 21.35 | 0.00 |
March | 15940.38 | 12-MAR-16:12 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 109.60 | 0.00 |
April | 21431.11 | 30-APR-16:01 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 449.43 | 0.00 |
May | 21894.48 | 28-MAY-16:31 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 893.41 | 0.00 |
June | 21419.54 | 11-JUN-16:22 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 194.54 | 0.00 |
July | 21663.92 | 02-JUL-16:31 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 311.27 | 0.00 |
August | 20156.40 | 06-AUG-16:32 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 268.27 | 0.00 |
September | 21246.26 | 17-SEP-16:02 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 141.91 | 0.00 |
October | 21833.44 | 01-OCT-15:21 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 104.95 | 0.00 |
November | 8263.12 | 08-NOV-15:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 | 0.00 |
December | 5237.79 | 28-DEC-15:40 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4618.69 | 326.14 | 260.35 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21894.48 | 1239.33 | 937.20 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 893.41 | 26.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8730.68 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11725.83 | 21-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 |
March | 11356.57 | 06-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 |
April | 17284.87 | 17-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
May | 17187.45 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.89 | 0.00 |
June | 17622.67 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.72 | 0.00 |
July | 19320.30 | 03-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.88 | 0.00 |
August | 18127.66 | 07-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 0.00 |
September | 15021.85 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | 0.00 |
October | 14093.22 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12959.81 | 13-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.06 |
December | 10585.62 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8730.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19320.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.88 | 24.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5083.61 | 21-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6836.17 | 23-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 |
March | 7962.68 | 15-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.37 |
April | 9651.62 | 21-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.49 | 0.00 |
May | 11915.05 | 31-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.96 | 0.00 |
June | 11252.69 | 09-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.02 | 0.00 |
July | 14378.42 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.98 | 0.00 |
August | 11853.16 | 08-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.71 | 0.00 |
September | 12616.52 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 | 0.00 |
October | 9259.85 | 20-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 |
November | 8965.11 | 13-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.51 |
December | 5446.69 | 02-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5083.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14378.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.96 | 85.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7274.40 | 12-JAN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.76 |
February | 13930.36 | 22-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 0.00 |
March | 21896.13 | 28-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26854.17 | 26-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.78 | 0.00 |
May | 30383.45 | 01-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.26 | 0.00 |
June | 31890.04 | 12-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.39 | 0.00 |
July | 28449.61 | 07-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.56 | 0.00 |
August | 25400.53 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.08 | 0.00 |
September | 22285.97 | 26-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.82 | 0.00 |
October | 21182.08 | 02-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.72 | 0.00 |
November | 14879.60 | 09-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.14 | 0.00 |
December | 8626.81 | 01-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7274.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31890.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.39 | 47.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1950.12 | 30-JAN-17:00 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3916.24 | 21-FEB-17:00 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7207.09 | 31-MAR-23:55 | 0.00 | 57.88 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7756.45 | 16-APR-22:35 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3509.96 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5382.56 | 30-JUN-23:57 | 0.00 | 86.81 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7269.26 | 31-JUL-23:57 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7616.83 | 16-AUG-09:40 | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3506.22 | 30-SEP-23:47 | 0.00 | 86.81 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5408.90 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5828.83 | 13-NOV-16:30 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7687.46 | 28-DEC-17:00 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1950.12 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7756.45 | 232.27 | 520.85 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1787.32 | 12-JAN-17:00 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3680.77 | 21-FEB-17:00 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6965.49 | 31-MAR-23:55 | 0.00 | 57.88 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7338.16 | 12-APR-16:00 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3382.31 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5209.02 | 30-JUN-23:42 | 0.00 | 144.69 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6987.17 | 31-JUL-24:00 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7182.48 | 16-AUG-10:50 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3402.17 | 30-SEP-23:47 | 0.00 | 86.81 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5089.52 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5502.47 | 08-NOV-16:40 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7247.83 | 01-DEC-17:00 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1787.32 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7338.16 | 222.14 | 520.85 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1790.41 | 12-JAN-17:00 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3710.93 | 22-FEB-17:00 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6911.88 | 31-MAR-23:55 | 0.00 | 57.88 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7487.94 | 16-APR-20:52 | 0.00 | 144.69 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3354.11 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5249.71 | 30-JUN-23:57 | 0.00 | 86.81 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7042.96 | 31-JUL-23:57 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7296.57 | 20-AUG-16:22 | 58.46 | 144.69 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3382.09 | 30-SEP-23:34 | 0.00 | 144.69 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4940.77 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5557.69 | 08-NOV-16:30 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7241.78 | 28-DEC-17:00 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1790.41 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7487.94 | 222.14 | 520.85 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 93285.70 | 26-JAN-17:00 | 4808.68 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184671.54 | 21-FEB-17:00 | 4808.68 | 5919.59 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359056.19 | 31-MAR-23:55 | 0.00 | 657.76 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368482.41 | 30-APR-04:25 | 0.00 | 657.76 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176395.08 | 31-MAY-24:00 | 0.00 | 328.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268595.66 | 30-JUN-24:00 | 0.00 | 986.65 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 356264.77 | 31-JUL-23:23 | 0.00 | 986.65 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370180.76 | 15-AUG-23:42 | 0.00 | 1644.41 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177656.23 | 30-SEP-23:53 | 0.00 | 1315.53 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269769.60 | 31-OCT-24:00 | 0.00 | 328.88 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277921.28 | 13-NOV-17:00 | 4808.68 | 5919.59 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369279.31 | 04-DEC-17:00 | 4808.68 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93285.70 | 0.00 | 328.88 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370180.76 | 4808.68 | 5919.59 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.188259E+13 | 1239063.77 | 12-JAN-16:40 | 0.684854E+11 | 229119.80 | 02-JAN-06:19 |
February | 0.214632E+13 | 1417125.51 | 28-FEB-16:49 | 0.505675E+11 | 120959.28 | 11-FEB-06:10 |
March | 0.297401E+13 | 1821714.73 | 13-MAR-15:00 | 0.533281E+11 | 70167.58 | 06-MAR-12:00 |
April | 0.345631E+13 | 2056558.06 | 18-APR-15:09 | 0.459330E+11 | 65830.89 | 04-APR-11:20 |
May | 0.250998E+13 | 1623426.74 | 09-MAY-15:00 | 0.447756E+11 | 60223.49 | 01-MAY-11:39 |
June | 0.297248E+13 | 1866585.05 | 22-JUN-15:09 | 0.410898E+11 | 53095.15 | 01-JUN-11:20 |
July | 0.350314E+13 | 2028655.29 | 05-JUL-15:00 | 0.392825E+11 | 47728.87 | 03-JUL-11:30 |
August | 0.395827E+13 | 2158800.56 | 07-AUG-15:20 | 0.423317E+11 | 52099.36 | 31-AUG-11:00 |
September | 0.237849E+13 | 1645849.57 | 14-SEP-15:20 | 0.418917E+11 | 58215.59 | 27-SEP-11:39 |
October | 0.263762E+13 | 1664821.09 | 03-OCT-15:00 | 0.467954E+11 | 65535.49 | 31-OCT-11:00 |
November | 0.278181E+13 | 1694780.59 | 01-NOV-15:20 | 0.493766E+11 | 69832.76 | 29-NOV-12:39 |
December | 0.314776E+13 | 1713651.65 | 28-DEC-16:00 | 0.577241E+11 | 166303.50 | 21-DEC-06:10 |
Annual Sum or Average | 0.343488E+14 | 0.581581E+12 | ||||
Minimum of Months | 0.188259E+13 | 1239063.77 | 0.392825E+11 | 47728.87 | ||
Maximum of Months | 0.395827E+13 | 2158800.56 | 0.684854E+11 | 229119.80 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.311083E+12 | 0.665010E+11 | 0.811612E+12 | 0.164870E+12 | 0.185224E+12 | 0.736513E+11 | 0.00 | 0.190855E+12 | 0.667904E+11 | 0.120010E+11 | 0.00 | 0.00 | 0.00 |
February | 0.281284E+12 | 0.569578E+11 | 0.102011E+13 | 0.148925E+12 | 0.178861E+12 | 0.723554E+11 | 0.00 | 0.272619E+12 | 0.102125E+12 | 0.130839E+11 | 0.00 | 0.00 | 0.00 |
March | 0.332677E+12 | 0.580246E+11 | 0.146267E+13 | 0.165150E+12 | 0.228734E+12 | 0.979183E+11 | 0.00 | 0.480948E+12 | 0.141142E+12 | 0.674613E+10 | 0.00 | 0.00 | 0.00 |
April | 0.296610E+12 | 0.512248E+11 | 0.170311E+13 | 0.159525E+12 | 0.248770E+12 | 0.122444E+12 | 0.00 | 0.714617E+12 | 0.159080E+12 | 0.935151E+09 | 0.00 | 0.00 | 0.00 |
May | 0.319396E+12 | 0.486028E+11 | 0.820521E+12 | 0.165009E+12 | 0.271283E+12 | 0.134250E+12 | 0.00 | 0.547620E+12 | 0.203280E+12 | 16492772.22 | 0.00 | 0.00 | 0.00 |
June | 0.317786E+12 | 0.447045E+11 | 0.110677E+13 | 0.159787E+12 | 0.267376E+12 | 0.135422E+12 | 0.00 | 0.725974E+12 | 0.214653E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.298190E+12 | 0.474617E+11 | 0.143888E+13 | 0.164746E+12 | 0.259328E+12 | 0.147651E+12 | 0.00 | 0.913289E+12 | 0.233593E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.332326E+12 | 0.509501E+11 | 0.177780E+13 | 0.165150E+12 | 0.267601E+12 | 0.149010E+12 | 0.00 | 0.983870E+12 | 0.231562E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.297496E+12 | 0.540285E+11 | 0.784732E+12 | 0.159523E+12 | 0.237564E+12 | 0.120858E+12 | 0.00 | 0.517138E+12 | 0.207147E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.309783E+12 | 0.609588E+11 | 0.112899E+13 | 0.164870E+12 | 0.228723E+12 | 0.108924E+12 | 0.00 | 0.470735E+12 | 0.163316E+12 | 0.131635E+10 | 0.00 | 0.00 | 0.00 |
November | 0.307239E+12 | 0.632547E+11 | 0.140306E+13 | 0.159632E+12 | 0.203384E+12 | 0.871684E+11 | 0.00 | 0.415502E+12 | 0.128936E+12 | 0.136297E+11 | 0.00 | 0.00 | 0.00 |
December | 0.301526E+12 | 0.680333E+11 | 0.175516E+13 | 0.164746E+12 | 0.191649E+12 | 0.798765E+11 | 0.00 | 0.429621E+12 | 0.122706E+12 | 0.344439E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370540E+13 | 0.670702E+12 | 0.152134E+14 | 0.194193E+13 | 0.276850E+13 | 0.132953E+13 | 0.00 | 0.666279E+13 | 0.197433E+13 | 0.821727E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.281284E+12 | 0.447045E+11 | 0.784732E+12 | 0.148925E+12 | 0.178861E+12 | 0.723554E+11 | 0.00 | 0.190855E+12 | 0.667904E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.332677E+12 | 0.680333E+11 | 0.177780E+13 | 0.165150E+12 | 0.271283E+12 | 0.149010E+12 | 0.00 | 0.983870E+12 | 0.233593E+12 | 0.344439E+11 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.142735E+11 | 0.00 | 0.542120E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.211367E+10 | 0.00 | 0.484538E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 3045324.56 | 0.00 | 0.533250E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.459330E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.447756E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.410898E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.392825E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.423317E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.418917E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.467954E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.152325E+09 | 0.00 | 0.492243E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.547094E+10 | 0.00 | 0.522531E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.220134E+11 | 0.00 | 0.559568E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.392825E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.142735E+11 | 0.00 | 0.542120E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 339503.01 | 18-JAN-08:09 | 54335.80 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 118948.06 | 18-JAN-08:20 | 126883.81 | 12-JAN-14:00 | 67731.31 | 12-JAN-14:50 | 0.00 | 01-JAN-00:10 |
February | 338358.91 | 10-FEB-08:09 | 54335.80 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 118947.11 | 10-FEB-08:20 | 161821.43 | 22-FEB-15:50 | 68195.95 | 17-FEB-11:00 | 0.00 | 01-FEB-00:10 |
March | 339293.08 | 14-MAR-07:10 | 54335.80 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 118947.89 | 14-MAR-07:19 | 199432.64 | 13-MAR-15:00 | 68785.43 | 28-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 319549.97 | 03-APR-07:10 | 54335.80 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 118931.42 | 03-APR-07:19 | 218529.07 | 17-APR-15:09 | 70907.26 | 10-APR-14:09 | 0.00 | 01-APR-00:10 |
May | 326362.57 | 24-MAY-07:10 | 54335.80 | 01-MAY-05:10 | 439129.89 | 01-MAY-07:10 | 118937.10 | 24-MAY-07:19 | 237009.98 | 03-MAY-14:09 | 70317.99 | 03-MAY-15:50 | 0.00 | 01-MAY-00:10 |
June | 326379.08 | 23-JUN-07:10 | 54335.80 | 01-JUN-05:10 | 557421.28 | 01-JUN-07:10 | 118937.11 | 23-JUN-07:19 | 245998.42 | 06-JUN-13:00 | 70634.16 | 09-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 337908.04 | 26-JUL-07:10 | 54335.80 | 01-JUL-05:10 | 675712.68 | 03-JUL-07:10 | 118946.73 | 26-JUL-07:19 | 239344.97 | 05-JUL-15:20 | 71599.91 | 31-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 339585.16 | 16-AUG-07:10 | 54335.80 | 01-AUG-05:10 | 794004.08 | 01-AUG-07:10 | 118948.13 | 16-AUG-07:19 | 226054.35 | 07-AUG-15:20 | 71743.86 | 28-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 341258.41 | 08-SEP-07:10 | 54335.80 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 118949.53 | 08-SEP-07:19 | 213932.08 | 25-SEP-15:50 | 69814.91 | 28-SEP-14:09 | 0.00 | 01-SEP-00:10 |
October | 344557.66 | 11-OCT-07:10 | 54335.80 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 118952.28 | 11-OCT-07:19 | 194325.92 | 04-OCT-15:00 | 69834.51 | 04-OCT-12:20 | 0.00 | 01-OCT-00:10 |
November | 340730.57 | 27-NOV-16:00 | 54335.80 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 118939.87 | 03-NOV-07:19 | 167227.66 | 09-NOV-15:00 | 69321.28 | 13-NOV-14:09 | 0.00 | 01-NOV-00:10 |
December | 342690.94 | 29-DEC-16:00 | 54335.80 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 118936.85 | 29-DEC-08:20 | 139614.13 | 01-DEC-15:30 | 68447.74 | 04-DEC-13:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 319549.97 | 54335.80 | 439129.89 | 118931.42 | 126883.81 | 67731.31 | 0.00 | |||||||
Maximum of Months | 344557.66 | 54335.80 | 794004.08 | 118952.28 | 245998.42 | 71743.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 156247.97 | 25-JAN-15:09 | 50613.09 | 25-JAN-14:00 | 7523.25 | 21-JAN-17:40 | 0.00 | 0.00 | 0.00 |
February | 203132.86 | 07-FEB-15:20 | 53243.76 | 24-FEB-16:19 | 11145.70 | 04-FEB-05:00 | 0.00 | 0.00 | 0.00 |
March | 395490.04 | 28-MAR-13:00 | 93058.23 | 06-MAR-14:39 | 13979.04 | 01-MAR-05:00 | 0.00 | 0.00 | 0.00 |
April | 496677.85 | 18-APR-15:39 | 93058.23 | 03-APR-09:09 | 7548.28 | 11-APR-04:00 | 0.00 | 0.00 | 0.00 |
May | 429935.06 | 17-MAY-15:30 | 93058.23 | 01-MAY-07:10 | 2126.21 | 28-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 540360.71 | 22-JUN-15:50 | 93058.23 | 01-JUN-05:40 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 551148.18 | 10-JUL-13:00 | 93058.23 | 01-JUL-06:30 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 583147.84 | 28-AUG-14:50 | 93058.23 | 01-AUG-00:40 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 440548.62 | 14-SEP-15:30 | 93058.23 | 01-SEP-00:40 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 398667.54 | 04-OCT-12:20 | 93058.23 | 02-OCT-08:20 | 7216.98 | 31-OCT-04:00 | 0.00 | 0.00 | 0.00 |
November | 372232.55 | 06-NOV-13:09 | 93058.23 | 06-NOV-11:20 | 15187.16 | 30-NOV-22:00 | 0.00 | 0.00 | 0.00 |
December | 262980.62 | 01-DEC-15:20 | 50859.45 | 27-DEC-13:50 | 28596.21 | 22-DEC-05:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 156247.97 | 50613.09 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 583147.84 | 93058.23 | 28596.21 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1239063.77 | 12-JAN-16:40 | 322304.13 | 439129.89 | 0.00 | 84888.71 | 120387.65 | 67505.23 | 0.00 | 154560.89 | 50287.27 |
February | 1417125.51 | 28-FEB-16:49 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 138493.24 | 67478.06 | 0.00 | 200954.17 | 51076.84 |
March | 1821714.73 | 13-MAR-15:00 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 199432.64 | 68200.58 | 0.00 | 383608.68 | 93058.23 |
April | 2056558.06 | 18-APR-15:09 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 205424.27 | 68983.83 | 0.00 | 493385.74 | 93058.23 |
May | 1623426.74 | 09-MAY-15:00 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 216886.69 | 69201.83 | 0.00 | 403448.18 | 93058.23 |
June | 1866585.05 | 22-JUN-15:09 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 210780.62 | 70265.64 | 0.00 | 533357.37 | 93058.23 |
July | 2028655.29 | 05-JUL-15:00 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 237193.79 | 69934.88 | 0.00 | 551053.79 | 93058.23 |
August | 2158800.56 | 07-AUG-15:20 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 226054.35 | 69995.90 | 0.00 | 573986.09 | 93058.23 |
September | 1645849.57 | 14-SEP-15:20 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 202167.15 | 69681.05 | 0.00 | 440111.34 | 93058.23 |
October | 1664821.09 | 03-OCT-15:00 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 177434.00 | 68443.63 | 0.00 | 366762.03 | 93058.23 |
November | 1694780.59 | 01-NOV-15:20 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 142547.15 | 68781.27 | 0.00 | 353065.05 | 52972.53 |
December | 1713651.65 | 28-DEC-16:00 | 327070.15 | 794004.08 | 0.00 | 84892.76 | 126707.76 | 67434.74 | 0.00 | 262916.00 | 50626.16 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1239063.77 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 120387.65 | 67434.74 | 0.00 | 154560.89 | 50287.27 | |
Maximum of Months | 2158800.56 | 327070.15 | 794004.08 | 0.00 | 84892.76 | 237193.79 | 70265.64 | 0.00 | 573986.09 | 93058.23 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 207455.14 | 02-JAN-06:19 | 0.00 | 72853.16 | 23-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 94402.55 | 11-FEB-06:10 | 0.00 | 72391.72 | 07-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 1016.70 | 01-MAR-06:49 | 0.00 | 70167.58 | 06-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 65830.89 | 04-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 60223.49 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 53095.15 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 47728.87 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 52099.36 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 58215.59 | 27-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 65535.49 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 7514.73 | 27-NOV-06:00 | 0.00 | 69832.76 | 29-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 142653.91 | 21-DEC-06:10 | 0.00 | 72354.25 | 27-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 47728.87 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 207455.14 | 0.00 | 72853.16 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 26.87 | 2.83 | 26.97 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.56 | 0.33 | 26.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 26.00 | 0.00 | 26.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.95 | 0.17 | 25.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.09 | 0.00 | 26.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 25.92 | 0.00 | 25.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 25.85 | 0.83 | 25.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 25.94 | 1.33 | 26.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.04 | 0.33 | 26.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.06 | 0.33 | 26.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.25 | 1.17 | 26.28 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.30 | 0.67 | 26.32 |
Annual Sum or Average | 0.00 | 0.00 | 100.50 | 26.17 | 8.00 | 26.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.85 | 0.00 | 25.89 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.87 | 2.83 | 26.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.58 | 0.00 | 25.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.69 | 0.00 | 25.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.62 | 0.00 | 25.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.63 | 0.00 | 25.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.69 | 0.00 | 25.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.65 | 0.00 | 25.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.62 | 0.00 | 25.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.61 | 0.00 | 25.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.63 | 0.00 | 25.63 |
Annual Sum or Average | 0.00 | 0.00 | 8.67 | 25.64 | 0.00 | 25.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.69 | 0.00 | 25.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.21 | 0.00 | 19.21 | 0.67 | 24.30 | 0.00 | 24.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.21 | 0.00 | 19.21 | 0.33 | 25.59 | 0.00 | 25.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.65 | 0.83 | 26.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 26.95 | 3.17 | 27.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.79 | 1.67 | 26.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.94 | 3.83 | 27.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 26.57 | 3.00 | 26.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.67 | 0.00 | 25.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 30.50 | 26.79 | 12.50 | 26.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.95 | 3.83 | 27.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.70 | 4.83 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.69 | 8.17 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.13 | 2.83 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.31 | 5.17 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.95 | 1.83 | 27.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.55 | 1.33 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 33.50 | 27.44 | 25.00 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.70 | 8.17 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.74 | 3.33 | 27.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.70 | 4.17 | 27.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.32 | 4.83 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.06 | 4.33 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.85 | 2.17 | 27.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.00 | 5.50 | 27.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.89 | 4.67 | 27.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.25 | 3.00 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.95 | 10.67 | 28.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.92 | 8.83 | 27.92 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.60 | 3.33 | 27.60 |
Annual Sum or Average | 0.00 | 0.00 | 78.17 | 27.37 | 55.17 | 27.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.85 | 0.33 | 27.05 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.95 | 10.67 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.62 | 1.17 | 27.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.30 | 4.33 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 47.17 | 27.58 | 12.50 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.39 | 5.67 | 27.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.22 | 5.33 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 35.83 | 27.46 | 11.83 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 55.17 | 27.61 | 14.17 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.18 | 3.50 | 27.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.43 | 6.50 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.64 | 3.83 | 27.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.37 | 1.33 | 27.37 |
Annual Sum or Average | 0.00 | 0.00 | 223.83 | 27.47 | 70.17 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 55.17 | 27.64 | 14.17 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.12 | 4.00 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.60 | 1.67 | 26.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 26.70 | 2.67 | 26.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.62 | 0.00 | 25.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.17 | 26.75 | 8.33 | 26.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.12 | 4.00 | 27.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.44 | 0.67 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.86 | 5.83 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.77 | 8.50 | 27.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.19 | 4.17 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.51 | 5.67 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.58 | 2.17 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.45 | 1.33 | 27.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.55 | 2.67 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40.33 | 27.59 | 31.00 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.86 | 8.50 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.41 | 0.50 | 27.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.76 | 3.33 | 27.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.73 | 3.83 | 27.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.61 | 4.33 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.18 | 4.67 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.57 | 2.00 | 26.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.81 | 4.33 | 27.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.77 | 3.33 | 27.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.31 | 3.17 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.04 | 10.67 | 28.09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.92 | 9.17 | 27.92 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.60 | 2.33 | 27.60 |
Annual Sum or Average | 0.00 | 0.00 | 70.33 | 27.41 | 51.67 | 27.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.57 | 0.50 | 26.80 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.04 | 10.67 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.75 | 1.00 | 27.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.65 | 4.50 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.65 | 5.83 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.28 | 4.17 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.43 | 5.00 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.04 | 2.83 | 27.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.84 | 1.67 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.85 | 3.83 | 27.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 66.50 | 27.49 | 28.83 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.85 | 5.83 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.57 | 1.83 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.45 | 6.33 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.01 | 3.00 | 27.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.32 | 6.50 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.99 | 3.00 | 27.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.47 | 0.00 | 18.47 | 46.50 | 27.20 | 21.17 | 27.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.47 | 0.00 | 18.47 | 15.67 | 27.57 | 6.50 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.44 | 0.50 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.00 | 7.00 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.86 | 10.83 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.28 | 4.67 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.62 | 9.50 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.50 | 5.50 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.65 | 3.83 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.57 | 3.00 | 27.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.56 | 0.00 | 18.56 | 71.00 | 27.62 | 44.83 | 27.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.56 | 0.00 | 18.56 | 18.33 | 28.00 | 10.83 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.71 | 1.83 | 27.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.84 | 3.50 | 27.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.91 | 4.67 | 27.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.48 | 7.50 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.99 | 3.00 | 27.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.33 | 7.00 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.17 | 4.00 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.68 | 3.17 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.19 | 10.33 | 28.23 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.92 | 6.83 | 27.92 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
Annual Sum or Average | 0.33 | 18.91 | 0.00 | 18.91 | 84.17 | 27.54 | 52.00 | 27.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 | 0.00 | 18.91 |
Maximum of Months | 0.33 | 18.91 | 0.00 | 18.91 | 16.00 | 28.19 | 10.33 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.86 | 1.17 | 27.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.89 | 4.83 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.79 | 7.33 | 28.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.42 | 5.17 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.69 | 6.67 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.38 | 3.17 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.96 | 2.17 | 28.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.01 | 4.00 | 28.03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.94 | 0.00 | 18.94 | 86.17 | 27.65 | 34.50 | 27.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.94 | 0.00 | 18.94 | 20.50 | 28.01 | 7.33 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 154.00 | 28.23 | 137.50 | 28.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 391.00 | 28.24 | 312.00 | 28.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 545.00 | 28.24 | 449.50 | 28.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 391.00 | 28.24 | 312.00 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 140.00 | 28.17 | 129.00 | 28.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 311.00 | 28.14 | 270.67 | 28.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 451.00 | 28.15 | 399.67 | 28.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 311.00 | 28.17 | 270.67 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 104.33 | 28.18 | 94.00 | 28.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 204.67 | 28.13 | 183.50 | 28.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 309.00 | 28.14 | 277.50 | 28.14 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 204.67 | 28.18 | 183.50 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 538.00 | 29.49 | 405.50 | 29.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.31 | 0.00 | 28.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 30.22 | 514.00 | 30.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1282.17 | 29.91 | 919.50 | 30.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 30.22 | 514.00 | 30.30 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 27.26 | 323.33 | 24.90 | 1.83 | 24.92 |
February | 12.00 | 26.81 | 365.50 | 24.75 | 12.00 | 24.81 |
March | 34.33 | 25.14 | 446.33 | 24.56 | 34.33 | 24.60 |
April | 31.00 | 24.23 | 422.83 | 24.60 | 31.00 | 24.57 |
May | 284.33 | 24.49 | 494.33 | 24.52 | 284.33 | 24.51 |
June | 335.00 | 24.59 | 496.00 | 24.54 | 335.00 | 24.55 |
July | 297.67 | 25.09 | 497.00 | 24.81 | 297.67 | 24.89 |
August | 264.50 | 24.99 | 514.00 | 24.67 | 264.50 | 24.75 |
September | 279.50 | 25.02 | 485.00 | 24.74 | 279.50 | 24.82 |
October | 105.83 | 25.13 | 502.00 | 24.72 | 105.83 | 24.78 |
November | 0.50 | 27.41 | 470.00 | 24.67 | 0.50 | 24.67 |
December | 0.00 | 0.00 | 389.83 | 24.79 | 0.00 | 24.79 |
Annual Sum or Average | 1646.50 | 24.86 | 5406.17 | 24.68 | 1646.50 | 24.71 |
Minimum of Months | 0.00 | 0.00 | 323.33 | 24.52 | 0.00 | 24.51 |
Maximum of Months | 335.00 | 27.41 | 514.00 | 24.90 | 335.00 | 24.92 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.83 | 25.74 | 298.33 | 24.77 | 12.33 | 24.84 |
February | 1.17 | 25.41 | 372.33 | 24.44 | 0.67 | 24.44 |
March | 0.00 | 0.00 | 467.50 | 24.30 | 0.00 | 24.30 |
April | 0.00 | 0.00 | 450.33 | 24.22 | 0.00 | 24.22 |
May | 0.00 | 0.00 | 494.33 | 24.21 | 0.00 | 24.21 |
June | 0.00 | 0.00 | 496.00 | 24.19 | 0.00 | 24.19 |
July | 0.00 | 0.00 | 497.00 | 24.23 | 0.00 | 24.23 |
August | 0.00 | 0.00 | 514.00 | 24.20 | 0.00 | 24.20 |
September | 0.00 | 0.00 | 485.00 | 24.30 | 0.00 | 24.30 |
October | 0.00 | 0.00 | 502.00 | 24.35 | 0.00 | 24.35 |
November | 0.00 | 0.00 | 470.17 | 24.42 | 0.00 | 24.42 |
December | 0.33 | 23.96 | 388.00 | 24.53 | 0.00 | 24.53 |
Annual Sum or Average | 20.33 | 25.69 | 5435.00 | 24.33 | 13.00 | 24.33 |
Minimum of Months | 0.00 | 0.00 | 298.33 | 24.19 | 0.00 | 24.19 |
Maximum of Months | 18.83 | 25.74 | 514.00 | 24.77 | 12.33 | 24.84 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 118.17 | 23.65 | 160.00 | 24.11 | 13.17 | 24.13 |
February | 55.33 | 23.85 | 274.33 | 24.24 | 7.83 | 24.28 |
March | 6.17 | 23.68 | 415.67 | 24.25 | 0.17 | 24.25 |
April | 2.50 | 23.84 | 400.83 | 24.22 | 0.00 | 24.22 |
May | 0.00 | 0.00 | 483.67 | 24.14 | 0.00 | 24.14 |
June | 0.00 | 0.00 | 496.00 | 24.15 | 0.00 | 24.15 |
July | 0.00 | 0.00 | 497.00 | 24.18 | 0.00 | 24.18 |
August | 0.00 | 0.00 | 514.00 | 24.19 | 0.00 | 24.19 |
September | 0.83 | 26.22 | 484.67 | 24.29 | 0.83 | 24.29 |
October | 0.00 | 0.00 | 492.00 | 24.30 | 0.00 | 24.30 |
November | 8.83 | 23.57 | 403.50 | 24.28 | 0.00 | 24.28 |
December | 78.33 | 23.50 | 189.67 | 24.10 | 0.00 | 24.10 |
Annual Sum or Average | 270.17 | 23.66 | 4811.33 | 24.21 | 22.00 | 24.21 |
Minimum of Months | 0.00 | 0.00 | 160.00 | 24.10 | 0.00 | 24.10 |
Maximum of Months | 118.17 | 26.22 | 514.00 | 24.30 | 13.17 | 24.30 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 375.17 | 22.58 | 50.67 | 22.61 | 15.50 | 22.52 |
February | 190.33 | 23.10 | 167.50 | 23.59 | 7.83 | 23.62 |
March | 33.17 | 23.54 | 373.33 | 24.15 | 1.67 | 24.15 |
April | 0.00 | 0.00 | 425.83 | 24.26 | 0.00 | 24.26 |
May | 0.00 | 0.00 | 502.67 | 24.23 | 0.00 | 24.23 |
June | 0.00 | 0.00 | 496.00 | 24.22 | 0.00 | 24.22 |
July | 0.00 | 0.00 | 497.00 | 24.29 | 0.00 | 24.29 |
August | 0.00 | 0.00 | 514.00 | 24.25 | 0.00 | 24.25 |
September | 3.67 | 26.78 | 481.50 | 24.34 | 3.50 | 24.36 |
October | 0.00 | 0.00 | 478.00 | 24.28 | 0.00 | 24.28 |
November | 94.83 | 23.18 | 285.33 | 23.91 | 0.00 | 23.91 |
December | 318.50 | 22.78 | 62.67 | 22.98 | 0.00 | 22.98 |
Annual Sum or Average | 1015.67 | 22.84 | 4334.50 | 23.96 | 28.50 | 23.96 |
Minimum of Months | 0.00 | 0.00 | 50.67 | 22.61 | 0.00 | 22.52 |
Maximum of Months | 375.17 | 26.78 | 514.00 | 24.34 | 15.50 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 335.83 | 22.89 | 64.00 | 23.13 | 0.00 | 23.13 |
February | 161.17 | 23.05 | 176.17 | 23.63 | 0.00 | 23.63 |
March | 31.00 | 23.27 | 391.83 | 24.15 | 0.00 | 24.15 |
April | 5.17 | 26.64 | 450.67 | 24.32 | 5.17 | 24.34 |
May | 14.00 | 26.78 | 508.00 | 24.46 | 14.00 | 24.52 |
June | 14.67 | 26.43 | 496.00 | 24.40 | 14.67 | 24.45 |
July | 34.00 | 26.60 | 497.00 | 24.58 | 34.00 | 24.70 |
August | 19.33 | 26.60 | 514.00 | 24.38 | 19.33 | 24.46 |
September | 13.83 | 26.16 | 485.00 | 24.43 | 13.83 | 24.48 |
October | 0.00 | 0.00 | 487.83 | 24.29 | 0.00 | 24.29 |
November | 62.50 | 23.24 | 333.50 | 24.05 | 0.00 | 24.05 |
December | 235.00 | 23.10 | 98.83 | 23.40 | 0.00 | 23.40 |
Annual Sum or Average | 926.50 | 23.41 | 4502.83 | 24.16 | 101.00 | 24.20 |
Minimum of Months | 0.00 | 0.00 | 64.00 | 23.13 | 0.00 | 23.13 |
Maximum of Months | 335.83 | 26.78 | 514.00 | 24.58 | 34.00 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 260.00 | 22.75 | 91.67 | 23.18 | 0.00 | 23.18 |
February | 146.33 | 22.86 | 218.17 | 23.70 | 0.00 | 23.70 |
March | 50.33 | 23.25 | 398.17 | 24.13 | 2.83 | 24.15 |
April | 29.00 | 25.76 | 445.67 | 24.39 | 20.33 | 24.49 |
May | 39.33 | 26.89 | 508.00 | 24.61 | 39.33 | 24.77 |
June | 17.33 | 26.64 | 496.00 | 24.38 | 17.33 | 24.45 |
July | 32.00 | 26.66 | 497.00 | 24.51 | 32.00 | 24.63 |
August | 15.83 | 26.55 | 514.00 | 24.26 | 15.83 | 24.33 |
September | 18.17 | 26.24 | 484.83 | 24.41 | 18.17 | 24.47 |
October | 21.50 | 25.38 | 468.33 | 24.39 | 14.00 | 24.45 |
November | 80.50 | 23.00 | 334.67 | 24.01 | 0.17 | 24.01 |
December | 246.67 | 22.83 | 134.17 | 23.33 | 0.00 | 23.33 |
Annual Sum or Average | 957.00 | 23.49 | 4590.67 | 24.17 | 160.00 | 24.24 |
Minimum of Months | 15.83 | 22.75 | 91.67 | 23.18 | 0.00 | 23.18 |
Maximum of Months | 260.00 | 26.89 | 514.00 | 24.61 | 39.33 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 168.83 | 22.95 | 221.00 | 23.73 | 0.17 | 23.74 |
February | 87.67 | 23.31 | 310.67 | 24.20 | 8.33 | 24.26 |
March | 35.83 | 25.04 | 446.83 | 24.42 | 17.17 | 24.51 |
April | 21.50 | 26.89 | 468.83 | 24.48 | 21.50 | 24.59 |
May | 24.83 | 26.76 | 508.00 | 24.53 | 24.83 | 24.63 |
June | 15.67 | 26.46 | 496.00 | 24.40 | 15.67 | 24.46 |
July | 34.83 | 26.66 | 497.00 | 24.58 | 34.83 | 24.71 |
August | 21.67 | 26.77 | 514.00 | 24.41 | 21.67 | 24.50 |
September | 28.33 | 26.50 | 485.00 | 24.56 | 28.33 | 24.66 |
October | 46.17 | 26.96 | 498.67 | 24.75 | 46.17 | 24.92 |
November | 48.33 | 25.92 | 433.83 | 24.69 | 34.67 | 24.85 |
December | 101.83 | 23.28 | 307.50 | 24.18 | 5.67 | 24.23 |
Annual Sum or Average | 635.50 | 24.55 | 5187.33 | 24.44 | 259.00 | 24.54 |
Minimum of Months | 15.67 | 22.95 | 221.00 | 23.73 | 0.17 | 23.74 |
Maximum of Months | 168.83 | 26.96 | 514.00 | 24.75 | 46.17 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 197.33 | 22.84 | 180.67 | 23.62 | 0.00 | 23.62 |
February | 52.17 | 23.38 | 349.50 | 24.34 | 5.17 | 24.37 |
March | 24.00 | 26.97 | 503.83 | 24.57 | 24.00 | 24.67 |
April | 65.33 | 26.83 | 485.00 | 24.82 | 65.33 | 25.04 |
May | 47.83 | 26.89 | 508.00 | 24.69 | 47.83 | 24.86 |
June | 55.33 | 26.72 | 496.00 | 24.68 | 55.33 | 24.86 |
July | 82.33 | 26.67 | 497.00 | 24.87 | 82.33 | 25.09 |
August | 83.67 | 26.68 | 514.00 | 24.80 | 83.67 | 25.03 |
September | 40.67 | 26.80 | 485.00 | 24.65 | 40.67 | 24.81 |
October | 43.17 | 26.94 | 502.00 | 24.72 | 43.17 | 24.88 |
November | 22.33 | 26.86 | 475.67 | 24.65 | 22.33 | 24.75 |
December | 14.67 | 24.00 | 404.50 | 24.58 | 2.67 | 24.60 |
Annual Sum or Average | 728.83 | 25.41 | 5401.17 | 24.62 | 472.50 | 24.77 |
Minimum of Months | 14.67 | 22.84 | 180.67 | 23.62 | 0.00 | 23.62 |
Maximum of Months | 197.33 | 26.97 | 514.00 | 24.87 | 83.67 | 25.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.17 | 22.13 | 0.00 | 22.13 | 0.00 | 22.13 |
February | 328.00 | 22.59 | 59.50 | 22.83 | 0.00 | 22.83 |
March | 117.33 | 23.11 | 281.83 | 23.84 | 0.00 | 23.84 |
April | 5.83 | 24.35 | 426.17 | 24.36 | 1.67 | 24.37 |
May | 16.67 | 26.74 | 508.00 | 24.50 | 16.67 | 24.57 |
June | 29.00 | 26.19 | 496.00 | 24.48 | 29.00 | 24.57 |
July | 79.33 | 26.23 | 497.00 | 24.75 | 79.33 | 24.93 |
August | 55.17 | 26.10 | 514.00 | 24.55 | 55.17 | 24.69 |
September | 41.33 | 26.16 | 485.00 | 24.55 | 41.33 | 24.67 |
October | 20.00 | 23.00 | 435.83 | 24.21 | 0.00 | 24.21 |
November | 230.67 | 22.90 | 138.17 | 23.32 | 0.00 | 23.32 |
December | 473.83 | 22.31 | 0.00 | 22.31 | 0.00 | 22.31 |
Annual Sum or Average | 1887.33 | 22.91 | 3841.50 | 23.88 | 223.17 | 23.97 |
Minimum of Months | 5.83 | 22.13 | 0.00 | 22.13 | 0.00 | 22.13 |
Maximum of Months | 490.17 | 26.74 | 514.00 | 24.75 | 79.33 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 403.17 | 22.36 | 2.50 | 22.37 | 0.00 | 22.37 |
February | 210.67 | 22.55 | 100.67 | 23.12 | 0.00 | 23.12 |
March | 73.50 | 23.10 | 289.67 | 24.11 | 4.33 | 24.15 |
April | 30.00 | 26.47 | 373.83 | 24.73 | 26.83 | 24.86 |
May | 44.33 | 26.92 | 430.00 | 24.79 | 44.33 | 24.97 |
June | 35.67 | 26.54 | 418.00 | 24.63 | 35.67 | 24.77 |
July | 73.17 | 26.42 | 422.00 | 24.88 | 73.17 | 25.07 |
August | 47.50 | 26.32 | 433.00 | 24.64 | 47.50 | 24.79 |
September | 53.50 | 26.19 | 403.33 | 24.70 | 53.50 | 24.86 |
October | 35.17 | 24.64 | 375.67 | 24.51 | 16.17 | 24.59 |
November | 142.67 | 22.80 | 197.17 | 23.67 | 0.17 | 23.67 |
December | 353.67 | 22.40 | 4.67 | 22.44 | 0.00 | 22.44 |
Annual Sum or Average | 1503.00 | 23.30 | 3450.50 | 24.13 | 301.67 | 24.27 |
Minimum of Months | 30.00 | 22.36 | 2.50 | 22.37 | 0.00 | 22.37 |
Maximum of Months | 403.17 | 26.92 | 433.00 | 24.88 | 73.17 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 230.17 | 22.84 | 192.50 | 23.52 | 0.67 | 23.53 |
February | 122.33 | 23.04 | 264.50 | 24.02 | 8.67 | 24.09 |
March | 50.83 | 24.33 | 415.00 | 24.39 | 16.33 | 24.47 |
April | 18.67 | 26.86 | 451.33 | 24.57 | 18.50 | 24.66 |
May | 24.83 | 26.76 | 508.00 | 24.55 | 24.83 | 24.65 |
June | 29.00 | 26.19 | 496.00 | 24.48 | 29.00 | 24.57 |
July | 80.00 | 26.25 | 497.00 | 24.76 | 80.00 | 24.94 |
August | 55.67 | 26.29 | 514.00 | 24.59 | 55.67 | 24.74 |
September | 54.17 | 26.40 | 485.00 | 24.69 | 54.17 | 24.84 |
October | 46.33 | 27.03 | 491.17 | 24.81 | 46.33 | 24.98 |
November | 73.33 | 25.04 | 407.33 | 24.63 | 36.17 | 24.80 |
December | 171.17 | 22.97 | 233.33 | 23.89 | 5.17 | 23.93 |
Annual Sum or Average | 956.50 | 24.31 | 4955.17 | 24.45 | 375.50 | 24.57 |
Minimum of Months | 18.67 | 22.84 | 192.50 | 23.52 | 0.67 | 23.53 |
Maximum of Months | 230.17 | 27.03 | 514.00 | 24.81 | 80.00 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 424.17 | 22.28 | 25.17 | 22.38 | 0.00 | 22.38 |
February | 252.00 | 22.55 | 125.17 | 23.14 | 0.00 | 23.14 |
March | 72.67 | 23.17 | 368.00 | 24.12 | 4.67 | 24.15 |
April | 22.83 | 26.96 | 465.33 | 24.61 | 22.83 | 24.71 |
May | 39.67 | 26.98 | 508.00 | 24.67 | 39.67 | 24.82 |
June | 49.17 | 26.65 | 496.00 | 24.64 | 49.17 | 24.80 |
July | 71.67 | 26.58 | 497.00 | 24.80 | 71.67 | 25.00 |
August | 49.17 | 26.55 | 514.00 | 24.61 | 49.17 | 24.77 |
September | 52.33 | 26.44 | 481.33 | 24.65 | 52.33 | 24.81 |
October | 30.17 | 24.92 | 462.67 | 24.43 | 15.33 | 24.51 |
November | 139.33 | 22.80 | 254.83 | 23.72 | 0.00 | 23.72 |
December | 386.17 | 22.47 | 58.17 | 22.69 | 0.00 | 22.69 |
Annual Sum or Average | 1589.33 | 23.29 | 4255.67 | 24.12 | 304.83 | 24.24 |
Minimum of Months | 22.83 | 22.28 | 25.17 | 22.38 | 0.00 | 22.38 |
Maximum of Months | 424.17 | 26.98 | 514.00 | 24.80 | 71.67 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.67 | 21.22 | 76.50 | 21.03 | 76.50 | 20.89 |
February | 387.67 | 21.99 | 41.00 | 22.11 | 8.50 | 22.06 |
March | 188.67 | 22.76 | 238.00 | 23.53 | 0.00 | 23.53 |
April | 28.83 | 24.08 | 419.67 | 24.34 | 7.50 | 24.38 |
May | 34.00 | 26.72 | 506.67 | 24.57 | 34.00 | 24.70 |
June | 37.17 | 26.30 | 496.00 | 24.51 | 37.17 | 24.63 |
July | 84.50 | 26.28 | 497.00 | 24.78 | 84.50 | 24.97 |
August | 55.00 | 26.18 | 514.00 | 24.56 | 55.00 | 24.70 |
September | 49.00 | 26.08 | 475.17 | 24.55 | 48.50 | 24.68 |
October | 67.33 | 22.81 | 382.17 | 24.02 | 0.50 | 24.02 |
November | 338.83 | 22.43 | 82.50 | 22.71 | 2.33 | 22.69 |
December | 497.00 | 21.48 | 48.17 | 21.34 | 48.17 | 21.22 |
Annual Sum or Average | 2269.67 | 22.38 | 3776.83 | 23.52 | 402.67 | 23.55 |
Minimum of Months | 28.83 | 21.22 | 41.00 | 21.03 | 0.00 | 20.89 |
Maximum of Months | 501.67 | 26.72 | 514.00 | 24.78 | 84.50 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 488.83 | 21.58 | 38.17 | 21.45 | 38.17 | 21.33 |
February | 301.50 | 22.26 | 102.17 | 22.70 | 3.00 | 22.68 |
March | 105.00 | 22.89 | 343.17 | 23.96 | 4.50 | 23.99 |
April | 44.33 | 25.78 | 451.17 | 24.61 | 31.50 | 24.74 |
May | 52.00 | 26.91 | 506.33 | 24.72 | 52.00 | 24.91 |
June | 45.00 | 26.51 | 496.00 | 24.57 | 45.00 | 24.72 |
July | 85.33 | 26.42 | 497.00 | 24.81 | 85.33 | 25.02 |
August | 50.17 | 26.42 | 514.00 | 24.57 | 50.17 | 24.72 |
September | 60.17 | 25.97 | 469.33 | 24.60 | 56.00 | 24.75 |
October | 59.67 | 24.02 | 430.50 | 24.36 | 20.17 | 24.46 |
November | 200.17 | 22.49 | 199.17 | 23.31 | 0.00 | 23.31 |
December | 481.83 | 21.93 | 21.00 | 21.86 | 21.00 | 21.79 |
Annual Sum or Average | 1974.00 | 22.82 | 4068.00 | 23.84 | 406.83 | 23.95 |
Minimum of Months | 44.33 | 21.58 | 21.00 | 21.45 | 0.00 | 21.33 |
Maximum of Months | 488.83 | 26.91 | 514.00 | 24.81 | 85.33 | 25.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 323.17 | 22.01 | 141.50 | 22.53 | 18.50 | 22.42 |
February | 192.00 | 22.42 | 207.67 | 23.46 | 4.50 | 23.50 |
March | 94.00 | 23.50 | 376.33 | 24.19 | 15.00 | 24.27 |
April | 28.67 | 25.87 | 444.67 | 24.55 | 20.33 | 24.65 |
May | 37.00 | 26.78 | 506.67 | 24.60 | 37.00 | 24.74 |
June | 36.83 | 26.29 | 496.00 | 24.51 | 36.83 | 24.62 |
July | 84.50 | 26.30 | 497.00 | 24.78 | 84.50 | 24.98 |
August | 55.67 | 26.32 | 514.00 | 24.60 | 55.67 | 24.75 |
September | 55.17 | 26.33 | 477.33 | 24.67 | 54.83 | 24.83 |
October | 59.50 | 26.00 | 467.50 | 24.74 | 44.33 | 24.92 |
November | 112.83 | 23.71 | 355.50 | 24.31 | 27.17 | 24.45 |
December | 264.33 | 22.27 | 177.17 | 23.09 | 6.67 | 23.05 |
Annual Sum or Average | 1343.67 | 23.50 | 4661.33 | 24.22 | 405.33 | 24.34 |
Minimum of Months | 28.67 | 22.01 | 141.50 | 22.53 | 4.50 | 22.42 |
Maximum of Months | 323.17 | 26.78 | 514.00 | 24.78 | 84.50 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 456.17 | 21.56 | 41.00 | 21.49 | 31.17 | 21.38 |
February | 317.00 | 22.11 | 95.00 | 22.60 | 0.00 | 22.60 |
March | 130.83 | 22.86 | 316.33 | 23.86 | 5.50 | 23.90 |
April | 32.33 | 26.25 | 453.00 | 24.60 | 26.67 | 24.72 |
May | 49.50 | 26.92 | 507.17 | 24.69 | 49.50 | 24.88 |
June | 52.50 | 26.64 | 496.00 | 24.63 | 52.50 | 24.80 |
July | 82.17 | 26.50 | 497.00 | 24.81 | 82.17 | 25.02 |
August | 56.17 | 26.49 | 514.00 | 24.61 | 56.17 | 24.78 |
September | 59.33 | 26.16 | 469.33 | 24.63 | 55.67 | 24.80 |
October | 60.00 | 23.87 | 418.50 | 24.32 | 17.33 | 24.41 |
November | 228.33 | 22.46 | 189.33 | 23.22 | 0.00 | 23.22 |
December | 429.83 | 21.81 | 50.83 | 21.92 | 16.83 | 21.86 |
Annual Sum or Average | 1954.17 | 22.81 | 4047.50 | 23.85 | 393.50 | 23.97 |
Minimum of Months | 32.33 | 21.56 | 41.00 | 21.49 | 0.00 | 21.38 |
Maximum of Months | 456.17 | 26.92 | 514.00 | 24.81 | 82.17 | 25.02 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 79.50 | 27.00 | 514.00 | 27.00 | 79.50 | 27.00 |
April | 361.17 | 27.54 | 485.00 | 27.46 | 361.17 | 27.49 |
May | 49.67 | 27.00 | 508.00 | 27.00 | 49.67 | 27.00 |
June | 189.50 | 27.00 | 496.00 | 27.00 | 189.50 | 27.00 |
July | 285.00 | 27.00 | 497.00 | 27.00 | 285.00 | 27.00 |
August | 499.67 | 27.86 | 514.00 | 27.85 | 499.67 | 27.86 |
September | 49.83 | 27.00 | 485.00 | 27.00 | 49.83 | 27.00 |
October | 45.17 | 27.00 | 502.00 | 27.00 | 45.17 | 27.00 |
November | 70.17 | 27.00 | 489.00 | 27.00 | 70.17 | 27.00 |
December | 55.50 | 27.00 | 497.00 | 27.00 | 55.50 | 27.00 |
Annual Sum or Average | 1685.17 | 27.37 | 5943.00 | 27.17 | 1685.17 | 27.20 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 499.67 | 27.86 | 514.00 | 27.85 | 499.67 | 27.86 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 162.67 | 28.00 | 485.00 | 27.52 | 162.67 | 27.62 |
May | 0.83 | 27.00 | 508.00 | 27.00 | 0.83 | 27.00 |
June | 12.50 | 27.00 | 496.00 | 27.00 | 12.50 | 27.00 |
July | 17.00 | 27.00 | 497.00 | 27.00 | 17.00 | 27.00 |
August | 296.50 | 28.11 | 514.00 | 27.84 | 296.50 | 27.91 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.33 | 27.00 | 502.00 | 27.00 | 0.33 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 489.83 | 28.00 | 5943.00 | 27.16 | 489.83 | 27.22 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 296.50 | 28.11 | 514.00 | 27.84 | 296.50 | 27.91 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.17 | 24.59 | 468.00 | 26.94 | 0.00 | 26.94 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 6.33 | 27.00 | 514.00 | 27.00 | 6.33 | 27.00 |
April | 154.83 | 27.80 | 485.00 | 27.39 | 154.83 | 27.47 |
May | 79.17 | 27.00 | 508.00 | 27.00 | 79.17 | 27.00 |
June | 117.83 | 27.00 | 496.00 | 27.00 | 117.83 | 27.00 |
July | 101.17 | 27.00 | 497.00 | 27.00 | 101.17 | 27.00 |
August | 242.67 | 27.94 | 514.00 | 27.62 | 242.67 | 27.70 |
September | 27.83 | 27.00 | 485.00 | 27.00 | 27.83 | 27.00 |
October | 10.50 | 27.00 | 502.00 | 27.00 | 10.50 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 752.50 | 27.43 | 5909.00 | 27.10 | 740.33 | 27.14 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 26.94 | 0.00 | 26.94 |
Maximum of Months | 242.67 | 27.94 | 514.00 | 27.62 | 242.67 | 27.70 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.01 | 502.00 | 27.01 | 502.00 | 27.01 |
February | 454.00 | 27.01 | 454.00 | 27.01 | 454.00 | 27.01 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 29.31 | 485.00 | 29.31 | 485.00 | 29.31 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 30.43 | 514.00 | 30.43 | 514.00 | 30.43 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
Annual Sum or Average | 5943.00 | 27.49 | 5943.00 | 27.49 | 5943.00 | 27.49 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 30.43 | 514.00 | 30.43 | 514.00 | 30.43 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00072 | 29.14011 | 0.86088 | 20.68628 |
February | 454.00000 | 27.00091 | 29.62669 | 0.91711 | 22.80368 |
March | 514.00000 | 27.00054 | 31.23450 | 0.98372 | 25.47058 |
April | 485.00000 | 27.40295 | 32.55602 | 1.12323 | 31.84709 |
May | 508.00000 | 27.00079 | 37.38577 | 0.33778 | 7.42628 |
June | 496.00000 | 27.00234 | 37.17537 | 0.38305 | 8.10142 |
July | 497.00000 | 27.00154 | 36.38610 | 0.41573 | 8.64529 |
August | 514.00000 | 27.84063 | 34.76086 | 0.67860 | 15.51010 |
September | 485.00000 | 27.00015 | 40.15412 | 0.34995 | 7.58807 |
October | 502.00000 | 27.00160 | 33.22966 | 0.97941 | 25.28925 |
November | 489.00000 | 27.00059 | 30.48441 | 0.97781 | 25.22834 |
December | 497.00000 | 27.00017 | 28.25814 | 0.96936 | 24.88606 |
Annual Sum or Average | 5943.00000 | 27.10637 | 33.38587 | 0.74663 | 18.57905 |
Minimum of Months | 454.00000 | 27.00015 | 28.25814 | 0.33778 | 7.42628 |
Maximum of Months | 514.00000 | 27.84063 | 40.15412 | 1.12323 | 31.84709 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00052 | 29.42895 | 0.78710 | 18.12306 |
February | 454.00000 | 27.00085 | 29.71436 | 0.83503 | 19.77600 |
March | 514.00000 | 27.00054 | 31.25270 | 0.90813 | 22.46411 |
April | 485.00000 | 27.36346 | 32.60403 | 1.02845 | 27.60834 |
May | 508.00000 | 27.00054 | 37.59655 | 0.29134 | 6.81897 |
June | 496.00000 | 27.00238 | 37.32999 | 0.31321 | 7.09042 |
July | 497.00000 | 27.00162 | 36.51790 | 0.32007 | 7.17362 |
August | 514.00000 | 27.68536 | 34.97247 | 0.49486 | 10.84069 |
September | 485.00000 | 27.00007 | 40.64669 | 0.30033 | 6.91637 |
October | 502.00000 | 27.00156 | 33.33641 | 0.92115 | 22.95682 |
November | 489.00000 | 27.00058 | 30.51208 | 0.88328 | 21.52526 |
December | 497.00000 | 27.00018 | 28.25535 | 0.83192 | 19.67436 |
Annual Sum or Average | 5943.00000 | 27.08967 | 33.53396 | 0.65793 | 15.86972 |
Minimum of Months | 454.00000 | 27.00007 | 28.25535 | 0.29134 | 6.81897 |
Maximum of Months | 514.00000 | 27.68536 | 40.64669 | 1.02845 | 27.60834 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.91961 | 29.82819 | 0.70289 | 15.82164 |
February | 454.00000 | 27.00093 | 29.20742 | 0.79212 | 18.37296 |
March | 514.00000 | 27.00061 | 30.62016 | 0.89585 | 22.04891 |
April | 485.00000 | 27.26354 | 32.11160 | 1.02092 | 27.30957 |
May | 508.00000 | 27.00060 | 36.94132 | 0.32152 | 7.26539 |
June | 496.00000 | 27.00249 | 36.65314 | 0.34334 | 7.56221 |
July | 497.00000 | 27.00178 | 35.83286 | 0.34520 | 7.57130 |
August | 514.00000 | 27.46495 | 34.40980 | 0.45871 | 10.14665 |
September | 485.00000 | 27.00007 | 39.99818 | 0.30907 | 7.06868 |
October | 502.00000 | 27.00167 | 32.72368 | 0.91510 | 22.76297 |
November | 489.00000 | 27.00066 | 29.89260 | 0.85036 | 20.38499 |
December | 497.00000 | 27.00024 | 27.70765 | 0.76595 | 17.53049 |
Annual Sum or Average | 5943.00000 | 27.05568 | 33.01415 | 0.64190 | 15.28156 |
Minimum of Months | 454.00000 | 26.91961 | 27.70765 | 0.30907 | 7.06868 |
Maximum of Months | 514.00000 | 27.46495 | 39.99818 | 1.02092 | 27.30957 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00513 | 30.03527 | 1.09590 | 30.33343 |
February | 454.00000 | 27.00589 | 30.19842 | 1.24092 | 37.27707 |
March | 514.00000 | 27.00304 | 31.02997 | 1.38238 | 44.57894 |
April | 485.00000 | 29.30881 | 31.14036 | 1.98357 | 74.29898 |
May | 508.00000 | 27.00345 | 34.95621 | 0.56285 | 11.70843 |
June | 496.00000 | 27.00317 | 35.09126 | 0.78994 | 18.17770 |
July | 497.00000 | 27.00170 | 34.50539 | 1.00238 | 26.23808 |
August | 514.00000 | 30.42832 | 31.93572 | 2.19963 | 83.26724 |
September | 485.00000 | 27.00419 | 35.50384 | 0.63856 | 13.62670 |
October | 502.00000 | 27.00273 | 32.00682 | 1.30197 | 40.37678 |
November | 489.00000 | 27.00422 | 30.64767 | 1.42214 | 46.69788 |
December | 497.00000 | 27.00668 | 30.05369 | 1.53457 | 52.78114 |
Annual Sum or Average | 5943.00000 | 27.48826 | 32.26949 | 1.26435 | 40.02171 |
Minimum of Months | 454.00000 | 27.00170 | 30.03527 | 0.56285 | 11.70843 |
Maximum of Months | 514.00000 | 30.42832 | 35.50384 | 2.19963 | 83.26724 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.57583 | 39.66639 | 0.51892 | 11.27526 |
February | 454.00000 | 24.54944 | 44.29399 | 0.54447 | 11.76741 |
March | 514.00000 | 24.45027 | 48.12555 | 0.55120 | 11.85104 |
April | 485.00000 | 24.54390 | 47.50027 | 0.56683 | 12.28872 |
May | 508.00000 | 24.52874 | 58.25629 | -0.2019 | 6.88209 |
June | 496.00000 | 24.49860 | 61.96334 | -0.1715 | 6.84703 |
July | 497.00000 | 24.65087 | 62.90484 | -0.1040 | 7.14001 |
August | 514.00000 | 24.50823 | 61.73300 | -0.1372 | 6.98172 |
September | 485.00000 | 24.58650 | 62.82090 | -0.1197 | 7.09070 |
October | 502.00000 | 24.63548 | 55.64772 | 0.66810 | 15.09308 |
November | 489.00000 | 24.64004 | 46.84334 | 0.60366 | 13.32727 |
December | 497.00000 | 24.62476 | 39.75811 | 0.54160 | 11.79960 |
Annual Sum or Average | 5943.00000 | 24.56559 | 52.53039 | 0.26884 | 10.17678 |
Minimum of Months | 454.00000 | 24.45027 | 39.66639 | -0.2019 | 6.84703 |
Maximum of Months | 514.00000 | 24.65087 | 62.90484 | 0.66810 | 15.09308 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.41929 | 42.42926 | 0.49793 | 10.89102 |
February | 454.00000 | 24.36019 | 45.45331 | 0.52182 | 11.02094 |
March | 514.00000 | 24.27266 | 48.86171 | 0.54388 | 11.42074 |
April | 485.00000 | 24.20387 | 48.66174 | 0.54261 | 11.30311 |
May | 508.00000 | 24.20222 | 54.32670 | -0.2925 | 6.97465 |
June | 496.00000 | 24.18641 | 56.11245 | -0.2757 | 6.75028 |
July | 497.00000 | 24.23233 | 56.37679 | -0.2530 | 6.52425 |
August | 514.00000 | 24.20159 | 56.08780 | -0.2438 | 6.41962 |
September | 485.00000 | 24.30469 | 56.58026 | -0.2480 | 6.70851 |
October | 502.00000 | 24.34989 | 53.98583 | 0.60108 | 12.83387 |
November | 489.00000 | 24.40718 | 47.96903 | 0.57002 | 12.14570 |
December | 497.00000 | 24.41995 | 41.05898 | 0.51335 | 10.88475 |
Annual Sum or Average | 5943.00000 | 24.29590 | 50.70415 | 0.20336 | 9.47363 |
Minimum of Months | 454.00000 | 24.18641 | 41.05898 | -0.2925 | 6.41962 |
Maximum of Months | 514.00000 | 24.41995 | 56.58026 | 0.60108 | 12.83387 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.06438 | 43.49560 | 0.39005 | 8.51063 |
February | 454.00000 | 24.14180 | 45.92017 | 0.44126 | 9.38417 |
March | 514.00000 | 24.20778 | 48.95639 | 0.50021 | 10.45188 |
April | 485.00000 | 24.18401 | 48.79398 | 0.50223 | 10.43940 |
May | 508.00000 | 24.13290 | 54.67013 | -0.3421 | 7.61246 |
June | 496.00000 | 24.15428 | 56.62953 | -0.3204 | 7.33527 |
July | 497.00000 | 24.18406 | 57.28152 | -0.3116 | 7.23574 |
August | 514.00000 | 24.19437 | 57.37620 | -0.3033 | 7.15754 |
September | 485.00000 | 24.28632 | 56.94065 | -0.2828 | 7.12010 |
October | 502.00000 | 24.28711 | 54.34092 | 0.56140 | 11.82625 |
November | 489.00000 | 24.23305 | 48.38138 | 0.49523 | 10.36280 |
December | 497.00000 | 24.06198 | 42.05651 | 0.38723 | 8.37666 |
Annual Sum or Average | 5943.00000 | 24.17768 | 51.28523 | 0.14011 | 8.81193 |
Minimum of Months | 454.00000 | 24.06198 | 42.05651 | -0.3421 | 7.12010 |
Maximum of Months | 514.00000 | 24.28711 | 57.37620 | 0.56140 | 11.82625 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.93168 | 46.58799 | 0.09425 | 6.66226 |
February | 454.00000 | 23.63005 | 47.76919 | 0.30809 | 7.83026 |
March | 514.00000 | 24.10100 | 49.66703 | 0.47778 | 10.04687 |
April | 485.00000 | 24.22786 | 48.99780 | 0.53129 | 11.10347 |
May | 508.00000 | 24.23120 | 54.25609 | -0.2727 | 6.83771 |
June | 496.00000 | 24.22260 | 56.17026 | -0.2589 | 6.70744 |
July | 497.00000 | 24.29033 | 56.79764 | -0.2459 | 6.62384 |
August | 514.00000 | 24.24954 | 57.15733 | -0.2592 | 6.71975 |
September | 485.00000 | 24.31950 | 57.04440 | -0.2539 | 6.87891 |
October | 502.00000 | 24.24763 | 55.14796 | 0.55908 | 11.74372 |
November | 489.00000 | 23.89666 | 50.09410 | 0.40925 | 8.91314 |
December | 497.00000 | 23.21100 | 44.80654 | 0.16601 | 6.71578 |
Annual Sum or Average | 5943.00000 | 23.96554 | 52.08021 | 0.10234 | 8.06377 |
Minimum of Months | 454.00000 | 22.93168 | 44.80654 | -0.2727 | 6.62384 |
Maximum of Months | 514.00000 | 24.31950 | 57.15733 | 0.55908 | 11.74372 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.28900 | 43.50460 | 0.19529 | 6.57904 |
February | 454.00000 | 23.70319 | 46.36509 | 0.34070 | 8.01749 |
March | 514.00000 | 24.08996 | 48.60011 | 0.49019 | 10.30271 |
April | 485.00000 | 24.26435 | 47.64394 | 0.58157 | 12.40544 |
May | 508.00000 | 24.39942 | 52.88873 | -0.1524 | 6.22539 |
June | 496.00000 | 24.33710 | 54.90135 | -0.1400 | 6.01441 |
July | 497.00000 | 24.43885 | 55.41611 | -0.1122 | 6.23792 |
August | 514.00000 | 24.29834 | 55.37595 | -0.1532 | 6.12229 |
September | 485.00000 | 24.38038 | 56.00557 | -0.1846 | 6.43308 |
October | 502.00000 | 24.26413 | 53.50691 | 0.58011 | 12.29755 |
November | 489.00000 | 24.00510 | 48.42199 | 0.44816 | 9.48141 |
December | 497.00000 | 23.58988 | 42.41999 | 0.27892 | 7.12904 |
Annual Sum or Average | 5943.00000 | 24.09088 | 50.45679 | 0.17918 | 8.09701 |
Minimum of Months | 454.00000 | 23.28900 | 42.41999 | -0.1846 | 6.01441 |
Maximum of Months | 514.00000 | 24.43885 | 56.00557 | 0.58157 | 12.40544 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.40767 | 43.00136 | 0.24267 | 7.09759 |
February | 454.00000 | 23.72349 | 46.14724 | 0.37257 | 8.70338 |
March | 514.00000 | 24.06298 | 48.48698 | 0.51641 | 11.13271 |
April | 485.00000 | 24.25535 | 47.51033 | 0.61602 | 13.56918 |
May | 508.00000 | 24.43593 | 52.62967 | -0.0812 | 6.34985 |
June | 496.00000 | 24.30063 | 54.91498 | -0.1225 | 6.03167 |
July | 497.00000 | 24.36651 | 55.61840 | -0.1264 | 6.38755 |
August | 514.00000 | 24.19225 | 55.76925 | -0.1938 | 6.38727 |
September | 485.00000 | 24.33675 | 56.00562 | -0.1699 | 6.42077 |
October | 502.00000 | 24.27174 | 53.29960 | 0.61010 | 13.34004 |
November | 489.00000 | 23.95400 | 48.36114 | 0.46204 | 10.01402 |
December | 497.00000 | 23.46276 | 42.60172 | 0.26767 | 7.28786 |
Annual Sum or Average | 5943.00000 | 24.06648 | 50.39956 | 0.19747 | 8.55164 |
Minimum of Months | 454.00000 | 23.40767 | 42.60172 | -0.1938 | 6.03167 |
Maximum of Months | 514.00000 | 24.43593 | 56.00562 | 0.61602 | 13.56918 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.79108 | 41.89171 | 0.35992 | 8.78599 |
February | 454.00000 | 24.11069 | 45.03053 | 0.48783 | 11.00844 |
March | 514.00000 | 24.28312 | 47.77491 | 0.58826 | 12.87152 |
April | 485.00000 | 24.35996 | 47.23995 | 0.63665 | 14.04003 |
May | 508.00000 | 24.41803 | 52.80480 | -0.1353 | 6.25307 |
June | 496.00000 | 24.33294 | 54.91447 | -0.1423 | 6.04419 |
July | 497.00000 | 24.43918 | 55.40822 | -0.1105 | 6.27979 |
August | 514.00000 | 24.31347 | 55.28478 | -0.1382 | 6.15922 |
September | 485.00000 | 24.44498 | 55.65630 | -0.1214 | 6.36047 |
October | 502.00000 | 24.53534 | 52.34175 | 0.71317 | 16.53606 |
November | 489.00000 | 24.45034 | 46.70254 | 0.63624 | 14.42515 |
December | 497.00000 | 24.10741 | 40.80752 | 0.45731 | 10.39647 |
Annual Sum or Average | 5943.00000 | 24.29960 | 49.69638 | 0.26681 | 9.91116 |
Minimum of Months | 454.00000 | 23.79108 | 40.80752 | -0.1423 | 6.04419 |
Maximum of Months | 514.00000 | 24.53534 | 55.65630 | 0.71317 | 16.53606 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.68776 | 41.94532 | 0.33905 | 8.33823 |
February | 454.00000 | 24.21552 | 44.56468 | 0.52928 | 11.64760 |
March | 514.00000 | 24.43996 | 47.21988 | 0.67771 | 15.28207 |
April | 485.00000 | 24.55498 | 46.51747 | 0.79736 | 19.19822 |
May | 508.00000 | 24.48305 | 52.42333 | -0.0079 | 6.33060 |
June | 496.00000 | 24.45040 | 54.27365 | 0.02891 | 6.26182 |
July | 497.00000 | 24.57109 | 54.63447 | 0.05846 | 6.72483 |
August | 514.00000 | 24.49557 | 54.35312 | 0.09069 | 6.67788 |
September | 485.00000 | 24.47297 | 55.36249 | -0.0582 | 6.21100 |
October | 502.00000 | 24.53082 | 52.33862 | 0.72867 | 16.84605 |
November | 489.00000 | 24.52522 | 46.47368 | 0.66225 | 14.88360 |
December | 497.00000 | 24.44889 | 39.81798 | 0.56547 | 12.35983 |
Annual Sum or Average | 5943.00000 | 24.40713 | 49.20116 | 0.36581 | 10.87437 |
Minimum of Months | 454.00000 | 23.68776 | 39.81798 | -0.0582 | 6.21100 |
Maximum of Months | 514.00000 | 24.57109 | 55.36249 | 0.79736 | 19.19822 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.17086 | 45.94754 | -0.0796 | 5.99965 |
February | 454.00000 | 22.96336 | 47.97609 | 0.14700 | 6.54477 |
March | 514.00000 | 23.85124 | 49.01750 | 0.40917 | 9.00679 |
April | 485.00000 | 24.30071 | 47.48387 | 0.55607 | 11.82774 |
May | 508.00000 | 24.42404 | 53.01776 | -0.1628 | 6.39263 |
June | 496.00000 | 24.38254 | 55.53137 | -0.1476 | 6.21274 |
July | 497.00000 | 24.51703 | 56.78774 | -0.1148 | 6.51643 |
August | 514.00000 | 24.38271 | 56.92529 | -0.1711 | 6.43607 |
September | 485.00000 | 24.41321 | 57.12092 | -0.1915 | 6.77282 |
October | 502.00000 | 24.14322 | 53.98306 | 0.52954 | 11.17351 |
November | 489.00000 | 23.43774 | 49.82565 | 0.29075 | 7.36298 |
December | 497.00000 | 22.37212 | 45.02651 | -0.0286 | 5.95482 |
Annual Sum or Average | 5943.00000 | 23.78591 | 51.58627 | 0.08527 | 7.51789 |
Minimum of Months | 454.00000 | 22.17086 | 45.02651 | -0.1915 | 5.95482 |
Maximum of Months | 514.00000 | 24.51703 | 57.12092 | 0.55607 | 11.82774 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.44179 | 44.57469 | 0.00037 | 5.85039 |
February | 385.00000 | 23.26180 | 46.44778 | 0.23913 | 7.43303 |
March | 433.00000 | 24.03580 | 47.68338 | 0.48329 | 10.75114 |
April | 410.00000 | 24.51193 | 46.16202 | 0.64609 | 14.62939 |
May | 430.00000 | 24.56636 | 52.33464 | -0.0619 | 6.73520 |
June | 418.00000 | 24.46318 | 55.16831 | -0.0922 | 6.35366 |
July | 422.00000 | 24.60832 | 56.45570 | -0.0703 | 6.84157 |
August | 433.00000 | 24.45277 | 56.64605 | -0.1373 | 6.58316 |
September | 410.00000 | 24.48059 | 56.90399 | -0.1442 | 6.89652 |
October | 427.00000 | 24.33463 | 53.12284 | 0.60148 | 13.40768 |
November | 417.00000 | 23.66835 | 48.56868 | 0.37030 | 8.71600 |
December | 422.00000 | 22.64981 | 43.79562 | 0.05394 | 6.09779 |
Annual Sum or Average | 5034.00000 | 23.95979 | 50.68621 | 0.15633 | 8.35583 |
Minimum of Months | 385.00000 | 22.44179 | 43.79562 | -0.1442 | 5.85039 |
Maximum of Months | 433.00000 | 24.60832 | 56.90399 | 0.64609 | 14.62939 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.58843 | 42.06051 | 0.30519 | 8.32907 |
February | 454.00000 | 23.94714 | 45.02302 | 0.43399 | 10.36394 |
March | 514.00000 | 24.24525 | 47.53600 | 0.55974 | 12.32942 |
April | 485.00000 | 24.44047 | 46.92503 | 0.62534 | 13.81119 |
May | 508.00000 | 24.44166 | 52.92959 | -0.1463 | 6.39157 |
June | 496.00000 | 24.37772 | 55.54863 | -0.1513 | 6.23294 |
July | 497.00000 | 24.51762 | 56.76844 | -0.1129 | 6.53575 |
August | 514.00000 | 24.40909 | 56.76304 | -0.1500 | 6.46412 |
September | 485.00000 | 24.49402 | 56.63175 | -0.1184 | 6.69373 |
October | 502.00000 | 24.57250 | 52.21291 | 0.70808 | 16.51763 |
November | 489.00000 | 24.38060 | 46.47355 | 0.60351 | 13.76894 |
December | 497.00000 | 23.86956 | 40.97338 | 0.37984 | 9.57172 |
Annual Sum or Average | 5943.00000 | 24.27538 | 50.03265 | 0.24240 | 9.73581 |
Minimum of Months | 454.00000 | 23.58843 | 40.97338 | -0.1513 | 6.23294 |
Maximum of Months | 514.00000 | 24.57250 | 56.76844 | 0.70808 | 16.51763 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.54103 | 44.60593 | 0.03617 | 6.15340 |
February | 454.00000 | 23.23515 | 46.88848 | 0.24685 | 7.60982 |
March | 514.00000 | 24.03819 | 48.16540 | 0.50565 | 11.12450 |
April | 485.00000 | 24.46191 | 46.85218 | 0.66519 | 15.02597 |
May | 508.00000 | 24.48822 | 52.64908 | -0.0612 | 6.53211 |
June | 496.00000 | 24.43878 | 55.13759 | -0.0560 | 6.35052 |
July | 497.00000 | 24.54543 | 56.35193 | -0.0593 | 6.68115 |
August | 514.00000 | 24.42853 | 56.46513 | -0.1064 | 6.40466 |
September | 485.00000 | 24.45021 | 56.66215 | -0.1242 | 6.75453 |
October | 502.00000 | 24.30403 | 53.23781 | 0.61390 | 13.59194 |
November | 489.00000 | 23.70117 | 48.59981 | 0.39714 | 9.07271 |
December | 497.00000 | 22.80381 | 43.51165 | 0.10395 | 6.38835 |
Annual Sum or Average | 5943.00000 | 23.95816 | 50.79605 | 0.17896 | 8.47061 |
Minimum of Months | 454.00000 | 22.54103 | 43.51165 | -0.1242 | 6.15340 |
Maximum of Months | 514.00000 | 24.54543 | 56.66215 | 0.66519 | 15.02597 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.21710 | 48.03899 | -0.3337 | 8.89581 |
February | 454.00000 | 22.26723 | 49.86649 | -0.0215 | 6.69480 |
March | 514.00000 | 23.55555 | 50.09448 | 0.34916 | 8.54773 |
April | 485.00000 | 24.25024 | 48.04199 | 0.56580 | 12.25700 |
May | 508.00000 | 24.42704 | 53.00939 | -0.1238 | 6.42084 |
June | 496.00000 | 24.37819 | 55.46715 | -0.1098 | 6.18655 |
July | 497.00000 | 24.52461 | 56.75447 | -0.0795 | 6.63310 |
August | 514.00000 | 24.38635 | 56.98932 | -0.1433 | 6.41564 |
September | 485.00000 | 24.36572 | 57.50065 | -0.1864 | 6.90269 |
October | 502.00000 | 23.95799 | 55.19894 | 0.49899 | 10.78527 |
November | 489.00000 | 22.85365 | 51.92086 | 0.15780 | 6.75599 |
December | 497.00000 | 21.47687 | 47.11609 | -0.2576 | 7.80184 |
Annual Sum or Average | 5943.00000 | 23.48086 | 52.52356 | 0.02614 | 7.85986 |
Minimum of Months | 454.00000 | 21.21710 | 47.11609 | -0.3337 | 6.18655 |
Maximum of Months | 514.00000 | 24.52461 | 57.50065 | 0.56580 | 12.25700 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.63776 | 46.77365 | -0.2082 | 7.44620 |
February | 454.00000 | 22.84101 | 48.13740 | 0.13988 | 7.17470 |
March | 514.00000 | 23.90425 | 48.84393 | 0.47367 | 10.77832 |
April | 485.00000 | 24.42098 | 47.32208 | 0.66867 | 15.26954 |
May | 508.00000 | 24.49441 | 52.60632 | -0.0215 | 6.72123 |
June | 496.00000 | 24.39375 | 55.23639 | -0.0534 | 6.30359 |
July | 497.00000 | 24.53365 | 56.52188 | -0.0441 | 6.88134 |
August | 514.00000 | 24.38888 | 56.79223 | -0.1133 | 6.50082 |
September | 485.00000 | 24.37942 | 57.18507 | -0.1375 | 6.88833 |
October | 502.00000 | 24.20690 | 54.12590 | 0.59666 | 13.35640 |
November | 489.00000 | 23.37649 | 50.11778 | 0.30879 | 8.25314 |
December | 497.00000 | 21.98638 | 45.64129 | -0.1157 | 6.70970 |
Annual Sum or Average | 5943.00000 | 23.72013 | 51.63939 | 0.12376 | 8.52427 |
Minimum of Months | 454.00000 | 21.63776 | 45.64129 | -0.2082 | 6.30359 |
Maximum of Months | 514.00000 | 24.53365 | 57.18507 | 0.66867 | 15.26954 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.78254 | 43.89004 | 0.08763 | 8.08646 |
February | 454.00000 | 23.47868 | 46.39355 | 0.31458 | 9.47695 |
March | 514.00000 | 24.07810 | 48.31668 | 0.52805 | 12.01701 |
April | 485.00000 | 24.40030 | 47.47665 | 0.63898 | 14.33298 |
May | 508.00000 | 24.44310 | 52.93076 | -0.1072 | 6.45623 |
June | 496.00000 | 24.37442 | 55.48374 | -0.1132 | 6.20743 |
July | 497.00000 | 24.52547 | 56.74188 | -0.0776 | 6.66381 |
August | 514.00000 | 24.41034 | 56.84022 | -0.1224 | 6.46538 |
September | 485.00000 | 24.45869 | 56.98461 | -0.1081 | 6.82704 |
October | 502.00000 | 24.48583 | 53.15880 | 0.70064 | 16.47985 |
November | 489.00000 | 24.11661 | 47.77529 | 0.53939 | 12.79827 |
December | 497.00000 | 23.23359 | 42.50425 | 0.20898 | 8.59970 |
Annual Sum or Average | 5943.00000 | 24.06929 | 50.74739 | 0.20579 | 9.52387 |
Minimum of Months | 454.00000 | 22.78254 | 42.50425 | -0.1224 | 6.20743 |
Maximum of Months | 514.00000 | 24.52547 | 56.98461 | 0.70064 | 16.47985 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.77023 | 46.27938 | -0.1695 | 7.47100 |
February | 454.00000 | 22.70059 | 48.40947 | 0.11655 | 7.28478 |
March | 514.00000 | 23.80631 | 49.09615 | 0.46072 | 10.70602 |
April | 485.00000 | 24.41232 | 47.43103 | 0.67584 | 15.50955 |
May | 508.00000 | 24.47407 | 52.72439 | -0.0273 | 6.76541 |
June | 496.00000 | 24.41580 | 55.16085 | -0.0233 | 6.48546 |
July | 497.00000 | 24.53347 | 56.42899 | -0.0306 | 6.86759 |
August | 514.00000 | 24.40946 | 56.63391 | -0.0866 | 6.47532 |
September | 485.00000 | 24.38831 | 57.11785 | -0.1223 | 6.97547 |
October | 502.00000 | 24.14663 | 54.37335 | 0.59081 | 13.28434 |
November | 489.00000 | 23.27280 | 50.30611 | 0.30003 | 8.28400 |
December | 497.00000 | 22.10203 | 45.18875 | -0.0769 | 6.92874 |
Annual Sum or Average | 5943.00000 | 23.71005 | 51.62452 | 0.13343 | 8.58559 |
Minimum of Months | 454.00000 | 21.77023 | 45.18875 | -0.1695 | 6.47532 |
Maximum of Months | 514.00000 | 24.53347 | 57.11785 | 0.67584 | 15.50955 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.910608E+11 | 107943.83 | 25-JAN-15:10 | 434.64 | 0.556646E+12 | 0.00 | 0.647707E+12 | 3.30 | 7.36 | 18-JAN-06:04 | 0.00 | 0.00 |
February | 0.102960E+12 | 112659.78 | 07-FEB-15:20 | 425.05 | 0.651563E+12 | 0.00 | 0.754523E+12 | 3.77 | 7.56 | 25-FEB-06:02 | 0.00 | 0.00 |
March | 0.154579E+12 | 137315.90 | 11-MAR-06:02 | 565.69 | 0.102575E+13 | 0.00 | 0.118033E+13 | 4.76 | 7.54 | 30-MAR-05:02 | 0.00 | 0.00 |
April | 0.197485E+12 | 199993.45 | 17-APR-05:03 | 671.95 | 0.131774E+13 | 0.00 | 0.151523E+13 | 5.82 | 7.63 | 19-APR-05:03 | 0.00 | 0.00 |
May | 0.250512E+12 | 217356.56 | 25-MAY-05:03 | 687.27 | 0.166412E+13 | 0.00 | 0.191463E+13 | 5.93 | 7.55 | 11-MAY-05:03 | 0.00 | 0.00 |
June | 0.267291E+12 | 229085.48 | 27-JUN-05:03 | 663.17 | 0.173728E+13 | 0.00 | 0.200457E+13 | 5.79 | 7.52 | 02-JUN-05:03 | 0.00 | 0.00 |
July | 0.292315E+12 | 235708.26 | 31-JUL-05:03 | 702.31 | 0.184818E+13 | 0.00 | 0.214050E+13 | 5.71 | 7.26 | 19-JUL-03:02 | 0.00 | 0.00 |
August | 0.290000E+12 | 236330.70 | 28-AUG-05:03 | 710.13 | 0.183266E+13 | 0.00 | 0.212266E+13 | 5.70 | 7.30 | 07-AUG-05:03 | 0.00 | 0.00 |
September | 0.226910E+12 | 226435.65 | 11-SEP-05:05 | 597.04 | 0.146487E+13 | 0.00 | 0.169178E+13 | 5.10 | 7.60 | 27-SEP-05:03 | 0.00 | 0.00 |
October | 0.177474E+12 | 205326.84 | 04-OCT-05:02 | 589.91 | 0.119353E+13 | 0.00 | 0.137101E+13 | 5.04 | 7.77 | 18-OCT-05:02 | 0.00 | 0.00 |
November | 0.132918E+12 | 115526.25 | 06-NOV-13:10 | 515.46 | 0.862757E+12 | 0.00 | 0.995675E+12 | 4.37 | 7.63 | 13-NOV-06:04 | 0.00 | 0.00 |
December | 0.103093E+12 | 108815.30 | 01-DEC-15:20 | 474.46 | 0.638369E+12 | 0.00 | 0.741462E+12 | 3.64 | 7.36 | 01-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.228660E+13 | 7037.06 | 0.147935E+14 | 0.00 | 0.170801E+14 | 4.92 | 0.00 | 0.00 | ||||
Minimum of Months | 0.910608E+11 | 107943.83 | 425.05 | 0.556646E+12 | 0.00 | 0.647707E+12 | 3.30 | 7.26 | 0.00 | 0.00 | ||
Maximum of Months | 0.292315E+12 | 236330.70 | 710.13 | 0.184818E+13 | 0.00 | 0.214050E+13 | 5.93 | 7.77 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 13382786.40 | 111523.22 | 25-FEB-06:02 | 0.03 | 0.101166E+09 | 0.00 | 0.114549E+09 | 0.00 | 7.56 | 25-FEB-06:02 | 0.00 | 0.00 |
March | 0.159118E+11 | 137315.90 | 11-MAR-06:02 | 40.14 | 0.113052E+12 | 0.00 | 0.128964E+12 | 0.38 | 7.54 | 30-MAR-05:02 | 0.00 | 0.00 |
April | 0.604766E+11 | 199993.45 | 17-APR-05:03 | 144.74 | 0.427766E+12 | 0.00 | 0.488242E+12 | 1.42 | 7.63 | 19-APR-05:03 | 0.00 | 0.00 |
May | 0.115238E+12 | 217356.56 | 25-MAY-05:03 | 250.53 | 0.792423E+12 | 0.00 | 0.907662E+12 | 2.32 | 7.55 | 11-MAY-05:03 | 0.00 | 0.00 |
June | 0.156401E+12 | 229085.48 | 27-JUN-05:03 | 314.62 | 0.104326E+13 | 0.00 | 0.119966E+13 | 2.92 | 7.52 | 02-JUN-05:03 | 0.00 | 0.00 |
July | 0.202612E+12 | 235708.26 | 31-JUL-05:03 | 400.38 | 0.132301E+13 | 0.00 | 0.152563E+13 | 3.51 | 7.26 | 19-JUL-03:02 | 0.00 | 0.00 |
August | 0.207602E+12 | 236330.70 | 28-AUG-05:03 | 402.46 | 0.135459E+13 | 0.00 | 0.156219E+13 | 3.53 | 7.30 | 07-AUG-05:03 | 0.00 | 0.00 |
September | 0.128654E+12 | 226435.65 | 11-SEP-05:05 | 266.59 | 0.858805E+12 | 0.00 | 0.987458E+12 | 2.47 | 7.60 | 27-SEP-05:03 | 0.00 | 0.00 |
October | 0.521608E+11 | 205326.84 | 04-OCT-05:02 | 125.88 | 0.368173E+12 | 0.00 | 0.420334E+12 | 1.19 | 7.77 | 18-OCT-05:02 | 0.00 | 0.00 |
November | 0.356331E+10 | 115526.25 | 06-NOV-13:10 | 9.11 | 0.254228E+11 | 0.00 | 0.289861E+11 | 0.09 | 7.63 | 13-NOV-06:04 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.942632E+12 | 1954.49 | 0.630660E+13 | 0.00 | 0.724924E+13 | 1.50 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.207602E+12 | 236330.70 | 402.46 | 0.135459E+13 | 0.00 | 0.156219E+13 | 3.53 | 7.77 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.663863E+11 | 744.00 | 49248.27 | 02-JAN-13:30 | 216017.63 | 12-JAN-17:00 | 22.67 | 19.07 | 14.75 |
February | 0.101253E+12 | 672.00 | 49248.27 | 01-FEB-10:20 | 380277.07 | 24-FEB-16:10 | 28.03 | 21.43 | 14.75 |
March | 0.131872E+12 | 744.00 | 49248.27 | 01-MAR-00:10 | 650723.08 | 31-MAR-24:00 | 36.96 | 27.23 | 14.75 |
April | 0.127652E+12 | 720.00 | 49248.27 | 01-APR-00:03 | 721001.50 | 16-APR-17:12 | 48.63 | 35.70 | 14.75 |
May | 0.131907E+12 | 744.00 | 49248.27 | 01-MAY-00:03 | 380038.19 | 31-MAY-23:50 | 39.88 | 35.28 | 14.75 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 558519.48 | 30-JUN-23:53 | 45.37 | 37.55 | 14.75 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:03 | 691314.85 | 31-JUL-24:00 | 48.04 | 37.18 | 14.75 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 724442.51 | 25-AUG-14:30 | 50.17 | 36.83 | 14.75 |
September | 0.127652E+12 | 720.00 | 49248.27 | 01-SEP-00:05 | 378738.22 | 30-SEP-23:20 | 35.72 | 31.07 | 14.75 |
October | 0.131907E+12 | 744.00 | 49248.27 | 01-OCT-00:03 | 488108.12 | 31-OCT-23:40 | 35.81 | 28.65 | 14.75 |
November | 0.125556E+12 | 720.00 | 49248.27 | 01-NOV-00:10 | 551748.18 | 08-NOV-16:20 | 34.20 | 24.57 | 14.75 |
December | 0.122191E+12 | 744.00 | 49248.27 | 01-DEC-07:00 | 671951.82 | 28-DEC-16:30 | 33.56 | 21.45 | 14.75 |
Annual Sum or Average | 0.145784E+13 | 8760.00 | 38.31 | 29.71 | 14.75 | ||||
Minimum of Months | 0.663863E+11 | 672.00 | 49248.27 | 216017.63 | 22.67 | 19.07 | 14.75 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 724442.51 | 50.17 | 37.55 | 14.75 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.404185E+09 | 323.58 | 1364.81 | 25-JAN-15:00 | 1138789.27 | 25-JAN-15:50 | 22.10 | 21.29 | 38.69 |
February | 0.872536E+09 | 366.48 | 3995.49 | 24-FEB-16:20 | 1298716.05 | 22-FEB-15:30 | 22.53 | 21.42 | 44.94 |
March | 0.748649E+10 | 506.42 | 21904.98 | 06-MAR-12:50 | 1390471.32 | 08-MAR-13:50 | 22.97 | 21.31 | 55.50 |
April | 0.232772E+11 | 623.53 | 21904.98 | 01-APR-09:10 | 1433744.14 | 10-APR-15:40 | 23.68 | 21.60 | 68.76 |
May | 0.485966E+11 | 687.27 | 21904.98 | 01-MAY-04:07 | 1477696.28 | 24-MAY-05:05 | 26.13 | 23.75 | 67.67 |
June | 0.519638E+11 | 663.17 | 21904.98 | 01-JUN-00:12 | 1498338.52 | 22-JUN-15:50 | 28.36 | 25.78 | 62.77 |
July | 0.553829E+11 | 702.31 | 21904.98 | 01-JUL-00:03 | 1507072.39 | 31-JUL-05:03 | 30.06 | 27.38 | 61.29 |
August | 0.559991E+11 | 710.13 | 21904.98 | 01-AUG-00:03 | 1525685.01 | 28-AUG-05:03 | 29.89 | 27.23 | 63.81 |
September | 0.470020E+11 | 597.04 | 21904.98 | 01-SEP-00:05 | 1573238.90 | 05-SEP-05:06 | 28.31 | 26.10 | 54.73 |
October | 0.235512E+11 | 564.99 | 21904.98 | 01-OCT-00:33 | 1388525.85 | 04-OCT-05:04 | 23.56 | 21.77 | 59.09 |
November | 0.324328E+10 | 450.55 | 21904.98 | 06-NOV-10:40 | 1388331.25 | 01-NOV-15:50 | 22.80 | 21.29 | 51.34 |
December | 0.514988E+09 | 364.85 | 1611.18 | 27-DEC-13:50 | 1182753.60 | 01-DEC-15:40 | 22.24 | 21.29 | 43.65 |
Annual Sum or Average | 0.318294E+12 | 6560.33 | 25.23 | 23.36 | 56.08 | ||||
Minimum of Months | 0.404185E+09 | 323.58 | 1364.81 | 1138789.27 | 22.10 | 21.29 | 38.69 | ||
Maximum of Months | 0.559991E+11 | 710.13 | 21904.98 | 1573238.90 | 30.06 | 27.38 | 68.76 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 22.10 | 22.10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 22.53 | 22.53 | 0.00 |
March | 0.178307E+10 | 23.57 | 21904.98 | 06-MAR-14:40 | 1348890.29 | 14-MAR-14:20 | 22.97 | 22.86 | 2.37 |
April | 0.815090E+10 | 105.94 | 21904.98 | 03-APR-05:03 | 1433744.14 | 10-APR-15:40 | 23.68 | 23.20 | 10.99 |
May | 0.227764E+11 | 288.87 | 21904.98 | 01-MAY-05:02 | 1477696.28 | 24-MAY-05:05 | 26.13 | 24.88 | 27.63 |
June | 0.350378E+11 | 444.32 | 21904.98 | 01-JUN-03:02 | 1498338.52 | 22-JUN-15:50 | 28.36 | 26.35 | 40.05 |
July | 0.463036E+11 | 587.18 | 21904.98 | 01-JUL-00:23 | 1507072.39 | 31-JUL-05:03 | 30.06 | 27.54 | 49.73 |
August | 0.436567E+11 | 553.61 | 21904.98 | 01-AUG-00:30 | 1525685.01 | 28-AUG-05:03 | 29.89 | 27.43 | 48.10 |
September | 0.324932E+11 | 412.05 | 21904.98 | 01-SEP-00:28 | 1573238.90 | 05-SEP-05:06 | 28.31 | 26.50 | 35.53 |
October | 0.785800E+10 | 99.79 | 21904.98 | 01-OCT-14:02 | 1388525.85 | 04-OCT-05:04 | 23.56 | 23.14 | 10.02 |
November | 0.136569E+09 | 4.00 | 21904.98 | 06-NOV-11:20 | 1382133.35 | 13-NOV-14:30 | 22.80 | 22.77 | 0.41 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 22.24 | 22.24 | 0.00 |
Annual Sum or Average | 0.198196E+12 | 2519.32 | 25.23 | 24.31 | 18.86 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.10 | 22.10 | 0.00 | ||
Maximum of Months | 0.463036E+11 | 587.18 | 21904.98 | 1573238.90 | 30.06 | 27.54 | 49.73 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.937313E+10 | 0.00 | 188.15 | 214389.78 | 03-JAN-06:03 | 0.00 | 26.42 | 39.99 | 0.02 | 0.00 | 0.00 | 0.15 | 03-JAN-06:03 |
February | 0.133847E+10 | 0.00 | 66.45 | 121606.28 | 11-FEB-06:02 | 0.00 | 21.91 | 27.53 | 0.00 | 0.00 | 0.00 | 0.09 | 11-FEB-06:02 |
March | 1925490.69 | 0.00 | 1.50 | 642.83 | 01-MAR-06:50 | 0.00 | 20.68 | 20.80 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-06:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 20.68 | 20.68 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 20.68 | 20.68 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 20.68 | 20.68 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 20.68 | 20.68 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 20.68 | 20.68 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 20.68 | 20.68 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 20.68 | 20.68 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 96311779.32 | 0.00 | 17.20 | 5007.30 | 27-NOV-06:20 | 0.00 | 20.58 | 21.99 | 0.00 | 0.00 | 0.00 | 0.00 | 27-NOV-06:20 |
December | 0.350425E+10 | 0.00 | 141.17 | 195903.17 | 21-DEC-06:02 | 0.00 | 22.43 | 33.11 | 0.01 | 0.00 | 0.00 | 0.14 | 21-DEC-06:02 |
Annual Sum or Average | 0.143141E+11 | 0.00 | 414.47 | 0.00 | 21.40 | 24.02 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.58 | 20.68 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.937313E+10 | 0.00 | 188.15 | 214389.78 | 0.00 | 26.42 | 39.99 | 0.02 | 0.00 | 0.00 | 0.15 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 22.67 | 22.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 28.03 | 28.03 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 36.96 | 36.96 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 48.63 | 48.63 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 39.88 | 39.88 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 45.37 | 45.37 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 48.04 | 48.04 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 50.17 | 50.17 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 35.72 | 35.72 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 35.81 | 35.81 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 34.20 | 34.20 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 33.56 | 33.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 38.31 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 22.67 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 50.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.551477E+11 | 0.00 | 413.05 | 0.550594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124272.76 | 02-JAN-06:03 | 94445.01 | 14-JAN-05:02 | 0.00 | 0.00 | 0.00 |
February | 0.727524E+11 | 0.00 | 410.76 | 0.725854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152978.55 | 25-FEB-04:02 | 112523.37 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.129389E+12 | 0.00 | 549.99 | 0.127435E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 218056.73 | 29-MAR-05:02 | 161086.79 | 14-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.185927E+12 | 0.00 | 625.32 | 0.179024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 266193.40 | 17-APR-05:03 | 185838.51 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.225479E+12 | 0.00 | 612.64 | 0.192353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 281586.37 | 22-MAY-05:02 | 200216.03 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.264382E+12 | 0.00 | 608.12 | 0.197548E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 301171.54 | 29-JUN-05:02 | 204726.69 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.305430E+12 | 0.00 | 636.65 | 0.191305E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 305776.95 | 17-JUL-05:03 | 193798.14 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.330330E+12 | 0.00 | 660.08 | 0.203546E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 311690.62 | 28-AUG-05:03 | 191625.16 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.227887E+12 | 0.00 | 537.52 | 0.148271E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 290773.28 | 05-SEP-03:02 | 178538.81 | 05-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.156275E+12 | 0.00 | 545.78 | 0.139563E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 262460.46 | 04-OCT-05:02 | 172680.96 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.107927E+12 | 0.00 | 481.22 | 0.106676E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 171389.39 | 06-NOV-06:03 | 139989.89 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.763068E+11 | 0.00 | 454.39 | 0.763068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117445.95 | 29-DEC-06:03 | 117445.95 | 29-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213723E+13 | 0.00 | 6535.53 | 0.168967E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.551477E+11 | 0.00 | 410.76 | 0.550594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117445.95 | 94445.01 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.330330E+12 | 0.00 | 660.08 | 0.203546E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 311690.62 | 204726.69 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.399574E+12 | 0.00 | 378.68 | 0.399137E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1039018.35 | 18-JAN-06:02 | 866772.41 | 14-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.539654E+12 | 0.00 | 380.28 | 0.538463E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1442929.56 | 25-FEB-06:02 | 999008.09 | 25-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.998560E+12 | 0.00 | 472.85 | 0.984494E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2153112.37 | 11-MAR-06:02 | 1551814.83 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.144127E+13 | 0.00 | 515.89 | 0.139021E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2321106.57 | 27-APR-05:03 | 1705165.89 | 27-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.206128E+13 | 0.00 | 585.51 | 0.174580E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2827145.56 | 24-MAY-03:02 | 1690995.84 | 19-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.233610E+13 | 0.00 | 561.27 | 0.171968E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2944871.51 | 27-JUN-05:03 | 1801751.82 | 07-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.255859E+13 | 0.00 | 555.97 | 0.154365E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3275022.81 | 20-JUL-03:02 | 1768407.75 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.254024E+13 | 0.00 | 543.86 | 0.148349E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2990989.56 | 11-AUG-03:02 | 1689898.36 | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.198051E+13 | 0.00 | 479.09 | 0.126414E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2943218.74 | 11-SEP-03:02 | 1672094.99 | 05-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.128008E+13 | 0.00 | 479.40 | 0.113594E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2474623.86 | 04-OCT-05:02 | 1624675.56 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.801234E+12 | 0.00 | 432.08 | 0.792170E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1599715.86 | 09-NOV-06:03 | 1082554.35 | 09-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.466031E+12 | 0.00 | 402.46 | 0.466031E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 898420.44 | 29-DEC-06:03 | 898420.44 | 29-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174031E+14 | 0.00 | 5787.34 | 0.134632E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.399574E+12 | 0.00 | 378.68 | 0.399137E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 898420.44 | 866772.41 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.255859E+13 | 0.00 | 585.51 | 0.174580E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3275022.81 | 1801751.82 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.292588E+11 | 0.00 | 338.64 | 0.292482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67572.36 | 12-JAN-15:30 | 67572.36 | 12-JAN-15:30 | 0.00 | 0.00 | 0.00 |
February | 0.477579E+11 | 0.00 | 355.16 | 0.476534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130621.65 | 25-FEB-06:02 | 101035.28 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.102628E+12 | 0.00 | 456.88 | 0.101264E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 215562.06 | 11-MAR-06:02 | 156297.93 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.162918E+12 | 0.00 | 521.62 | 0.157648E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 253548.83 | 27-APR-05:03 | 186687.28 | 27-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.236869E+12 | 0.00 | 598.46 | 0.203960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 306118.38 | 24-MAY-03:02 | 202711.36 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.265561E+12 | 0.00 | 573.64 | 0.201746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 322630.92 | 23-JUN-05:02 | 218204.54 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.283916E+12 | 0.00 | 573.20 | 0.178471E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 331090.40 | 22-JUL-05:03 | 205648.28 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.276710E+12 | 0.00 | 556.15 | 0.167952E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 323165.85 | 12-AUG-03:02 | 192103.78 | 14-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.213524E+12 | 0.00 | 491.11 | 0.139667E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 335060.70 | 11-SEP-03:02 | 185105.53 | 11-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.132816E+12 | 0.00 | 471.62 | 0.119173E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 243803.48 | 04-OCT-03:02 | 161741.40 | 04-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.744814E+11 | 0.00 | 406.11 | 0.740300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145290.04 | 10-NOV-06:02 | 112778.99 | 09-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.357410E+11 | 0.00 | 372.33 | 0.357410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74196.35 | 01-DEC-15:00 | 74196.35 | 01-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186218E+13 | 0.00 | 5714.91 | 0.145655E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.292588E+11 | 0.00 | 338.64 | 0.292482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67572.36 | 67572.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.283916E+12 | 0.00 | 598.46 | 0.203960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 335060.70 | 218204.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.560333E+11 | 0.00 | 402.35 | 0.559598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110961.60 | 18-JAN-04:03 | 91184.16 | 23-JAN-04:03 | 0.00 | 0.00 | 0.00 |
February | 0.573217E+11 | 0.00 | 375.75 | 0.572663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129214.42 | 25-FEB-04:02 | 108071.47 | 20-FEB-15:12 | 0.00 | 0.00 | 0.00 |
March | 0.787844E+11 | 0.00 | 444.40 | 0.785347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162720.99 | 11-MAR-04:02 | 102553.30 | 13-MAR-03:02 | 0.00 | 0.00 | 0.00 |
April | 0.900437E+11 | 0.00 | 418.88 | 0.881115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168329.96 | 27-APR-03:02 | 126911.21 | 16-APR-17:40 | 0.00 | 0.00 | 0.00 |
May | 0.115380E+12 | 0.00 | 451.26 | 0.103035E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 201736.51 | 22-MAY-03:02 | 133437.85 | 29-MAY-17:30 | 0.00 | 0.00 | 0.00 |
June | 0.134888E+12 | 0.00 | 454.42 | 0.107085E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 225203.45 | 26-JUN-03:02 | 131226.91 | 04-JUN-16:18 | 0.00 | 0.00 | 0.00 |
July | 0.155844E+12 | 0.00 | 470.02 | 0.106407E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 245465.76 | 30-JUL-20:57 | 121758.86 | 04-JUL-17:50 | 0.00 | 0.00 | 0.00 |
August | 0.174314E+12 | 0.00 | 503.86 | 0.115266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 257505.02 | 27-AUG-14:59 | 107512.11 | 08-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.139122E+12 | 0.00 | 467.81 | 0.996875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 239604.66 | 11-SEP-00:22 | 111237.54 | 24-SEP-14:08 | 0.00 | 0.00 | 0.00 |
October | 0.101533E+12 | 0.00 | 478.10 | 0.947397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 179649.53 | 04-OCT-03:02 | 125757.84 | 01-OCT-14:36 | 0.00 | 0.00 | 0.00 |
November | 0.787329E+11 | 0.00 | 442.12 | 0.784526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140973.37 | 09-NOV-04:03 | 109218.57 | 11-NOV-13:18 | 0.00 | 0.00 | 0.00 |
December | 0.635985E+11 | 0.00 | 417.86 | 0.635899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106326.79 | 30-DEC-04:02 | 96268.31 | 29-DEC-04:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124560E+13 | 0.00 | 5326.83 | 0.104814E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.560333E+11 | 0.00 | 375.75 | 0.559598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106326.79 | 91184.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.174314E+12 | 0.00 | 503.86 | 0.115266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 257505.02 | 133437.85 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.338687E+12 | 0.877633E+11 | 744.00 | 0.325039E+12 | 0.136477E+11 | 0.00 | 0.36 | 12-JAN-16:00 | 0.32 | 22-JAN-06:00 | 132584.48 | 17-JAN-17:00 | 127940.65 | 12-JAN-15:00 | 6872.97 | 17-JAN-17:00 | 41428.62 | 12-JAN-15:00 | 0.00 |
February | 0.534019E+12 | 0.142106E+12 | 672.00 | 0.517130E+12 | 0.168886E+11 | 0.00 | 0.60 | 22-FEB-15:00 | 0.53 | 01-FEB-00:10 | 226157.43 | 24-FEB-17:00 | 220704.51 | 22-FEB-15:00 | 10353.56 | 27-FEB-09:40 | 77934.92 | 22-FEB-15:00 | 0.00 |
March | 0.836897E+12 | 0.254946E+12 | 744.00 | 0.822943E+12 | 0.139534E+11 | 0.00 | 0.98 | 31-MAR-24:00 | 0.74 | 01-MAR-02:70 | 396209.03 | 31-MAR-24:00 | 393971.56 | 31-MAR-23:55 | 13898.93 | 05-MAR-06:00 | 136907.14 | 28-MAR-15:30 | 0.00 |
April | 0.103528E+13 | 0.370554E+12 | 720.00 | 0.102909E+13 | 0.619589E+10 | 0.00 | 1.00 | 01-APR-08:20 | 0.42 | 30-APR-24:00 | 410074.23 | 25-APR-04:55 | 403756.52 | 30-APR-04:25 | 8780.38 | 26-APR-21:00 | 174123.26 | 15-APR-15:00 | 0.00 |
May | 0.363541E+12 | 0.149095E+12 | 744.00 | 0.346709E+12 | 0.168320E+11 | 0.00 | 0.60 | 31-MAY-23:13 | 0.35 | 28-MAY-05:00 | 226648.48 | 31-MAY-23:03 | 213153.01 | 31-MAY-24:00 | 15211.74 | 22-MAY-23:10 | 79266.62 | 31-MAY-23:13 | 0.00 |
June | 0.599562E+12 | 0.246185E+12 | 720.00 | 0.573831E+12 | 0.257310E+11 | 0.00 | 0.85 | 30-JUN-24:00 | 0.58 | 18-JUN-05:00 | 318783.06 | 30-JUN-23:02 | 307423.31 | 30-JUN-24:00 | 18595.09 | 28-JUN-13:30 | 127808.70 | 30-JUN-24:00 | 0.00 |
July | 0.874908E+12 | 0.340176E+12 | 744.00 | 0.838308E+12 | 0.365997E+11 | 0.00 | 1.00 | 31-JUL-23:02 | 0.80 | 19-JUL-02:55 | 402165.42 | 31-JUL-24:00 | 390442.05 | 31-JUL-24:00 | 19572.30 | 18-JUL-08:30 | 158006.70 | 07-JUL-15:00 | 0.00 |
August | 0.110066E+13 | 0.392627E+12 | 744.00 | 0.106513E+13 | 0.355226E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.45 | 31-AUG-24:00 | 422167.53 | 10-AUG-14:00 | 405159.56 | 15-AUG-23:55 | 20781.92 | 25-AUG-16:00 | 166798.64 | 07-AUG-15:00 | 0.00 |
September | 0.367475E+12 | 0.132707E+12 | 720.00 | 0.336224E+12 | 0.312510E+11 | 0.00 | 0.59 | 30-SEP-23:05 | 0.36 | 27-SEP-05:00 | 227309.79 | 30-SEP-23:05 | 213808.29 | 30-SEP-23:53 | 18116.48 | 12-SEP-16:00 | 76428.56 | 30-SEP-23:20 | 0.00 |
October | 0.602836E+12 | 0.198279E+12 | 744.00 | 0.586451E+12 | 0.163847E+11 | 0.00 | 0.76 | 31-OCT-23:30 | 0.55 | 31-OCT-05:00 | 311062.02 | 31-OCT-24:00 | 302638.89 | 31-OCT-24:00 | 11516.79 | 13-OCT-08:30 | 102133.97 | 02-OCT-15:00 | 0.00 |
November | 0.818523E+12 | 0.230316E+12 | 720.00 | 0.799030E+12 | 0.194939E+11 | 0.00 | 0.84 | 08-NOV-15:00 | 0.75 | 26-NOV-06:00 | 321970.29 | 24-NOV-08:15 | 314991.31 | 08-NOV-15:00 | 14619.93 | 23-NOV-08:00 | 119035.72 | 08-NOV-15:00 | 0.00 |
December | 0.110010E+13 | 0.270608E+12 | 744.00 | 0.106551E+13 | 0.345844E+11 | 0.00 | 1.00 | 25-DEC-13:57 | 0.93 | 01-DEC-00:10 | 422262.40 | 22-DEC-06:03 | 404478.53 | 28-DEC-17:00 | 25569.76 | 22-DEC-06:03 | 130708.24 | 28-DEC-14:10 | 0.00 |
Annual Sum or Average | 0.857248E+13 | 0.281536E+13 | 8760.00 | 0.830540E+13 | 0.267085E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.338687E+12 | 0.877633E+11 | 672.00 | 0.325039E+12 | 0.619589E+10 | 0.00 | 0.36 | 0.32 | 132584.48 | 127940.65 | 6872.97 | 41428.62 | 0.00 | ||||||
Maximum of Months | 0.110066E+13 | 0.392627E+12 | 744.00 | 0.106551E+13 | 0.365997E+11 | 0.00 | 1.00 | 0.93 | 422262.40 | 405159.56 | 25569.76 | 174123.26 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.500855E+10 | 0.130589E+10 | 744.00 | 0.486377E+10 | 0.144779E+09 | 0.00 | 0.32 | 12-JAN-17:00 | 0.17 | 07-JAN-08:00 | 2535.93 | 12-JAN-17:00 | 2405.11 | 12-JAN-17:00 | 253.59 | 17-JAN-17:00 | 756.13 | 12-JAN-16:00 | 0.00 |
February | 0.962832E+10 | 0.254379E+10 | 672.00 | 0.940246E+10 | 0.225860E+09 | 0.00 | 0.56 | 21-FEB-17:00 | 0.40 | 01-FEB-07:00 | 4586.17 | 21-FEB-17:00 | 4436.12 | 21-FEB-17:00 | 262.69 | 15-FEB-17:10 | 1515.15 | 22-FEB-15:00 | 0.00 |
March | 0.162732E+11 | 0.486739E+10 | 744.00 | 0.159437E+11 | 0.329528E+09 | 0.00 | 0.90 | 31-MAR-24:00 | 0.63 | 01-MAR-07:00 | 7794.97 | 31-MAR-24:00 | 7695.35 | 31-MAR-23:55 | 336.17 | 30-MAR-16:10 | 2757.94 | 28-MAR-16:00 | 0.00 |
April | 0.210003E+11 | 0.750660E+10 | 720.00 | 0.206930E+11 | 0.307348E+09 | 0.00 | 1.00 | 01-APR-15:00 | 0.39 | 30-APR-24:00 | 8548.31 | 16-APR-20:54 | 8320.25 | 16-APR-22:35 | 382.71 | 26-APR-08:00 | 3616.15 | 15-APR-15:00 | 0.00 |
May | 0.725726E+10 | 0.287000E+10 | 744.00 | 0.659478E+10 | 0.662475E+09 | 0.00 | 0.56 | 31-MAY-23:03 | 0.28 | 13-MAY-07:00 | 4650.35 | 31-MAY-23:03 | 4083.37 | 31-MAY-24:00 | 643.08 | 22-MAY-23:10 | 1628.11 | 01-MAY-15:50 | 0.00 |
June | 0.123709E+11 | 0.487687E+10 | 720.00 | 0.112895E+11 | 0.108139E+10 | 0.00 | 0.80 | 30-JUN-23:12 | 0.53 | 18-JUN-04:25 | 6545.17 | 30-JUN-23:02 | 6051.33 | 30-JUN-23:57 | 812.81 | 28-JUN-13:40 | 2579.17 | 08-JUN-16:00 | 0.00 |
July | 0.182093E+11 | 0.679429E+10 | 744.00 | 0.166004E+11 | 0.160887E+10 | 0.00 | 1.00 | 31-JUL-23:02 | 0.75 | 19-JUL-03:02 | 8653.05 | 31-JUL-23:02 | 7870.11 | 31-JUL-24:00 | 846.46 | 18-JUL-08:20 | 3281.30 | 02-JUL-16:50 | 0.00 |
August | 0.229816E+11 | 0.815018E+10 | 744.00 | 0.212870E+11 | 0.169453E+10 | 0.00 | 1.00 | 01-AUG-07:30 | 0.38 | 31-AUG-23:05 | 8877.56 | 10-AUG-14:10 | 8138.05 | 29-AUG-03:32 | 863.21 | 21-AUG-14:00 | 3470.31 | 07-AUG-15:00 | 0.00 |
September | 0.739861E+10 | 0.254184E+10 | 720.00 | 0.612792E+10 | 0.127068E+10 | 0.00 | 0.55 | 30-SEP-23:05 | 0.30 | 27-SEP-06:00 | 4621.76 | 30-SEP-23:05 | 4051.24 | 30-SEP-23:47 | 734.98 | 12-SEP-16:00 | 1480.54 | 30-SEP-23:20 | 0.00 |
October | 0.117609E+11 | 0.376527E+10 | 744.00 | 0.111429E+11 | 0.617990E+09 | 0.00 | 0.68 | 31-OCT-23:20 | 0.46 | 31-OCT-06:00 | 5988.36 | 31-OCT-23:10 | 5787.03 | 31-OCT-24:00 | 494.68 | 06-OCT-09:40 | 2067.73 | 02-OCT-15:10 | 0.00 |
November | 0.156218E+11 | 0.433842E+10 | 720.00 | 0.153125E+11 | 0.309341E+09 | 0.00 | 0.80 | 08-NOV-16:20 | 0.63 | 25-NOV-08:00 | 6643.26 | 08-NOV-16:40 | 6394.67 | 08-NOV-16:30 | 283.16 | 08-NOV-20:00 | 2354.99 | 08-NOV-15:00 | 0.00 |
December | 0.205933E+11 | 0.505868E+10 | 744.00 | 0.204236E+11 | 0.169681E+09 | 0.00 | 0.95 | 28-DEC-16:40 | 0.80 | 23-DEC-08:00 | 8318.76 | 28-DEC-17:00 | 8158.39 | 28-DEC-17:00 | 252.66 | 29-DEC-17:10 | 2585.35 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.168104E+12 | 0.546192E+11 | 8760.00 | 0.159682E+12 | 0.842248E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.500855E+10 | 0.130589E+10 | 672.00 | 0.486377E+10 | 0.144779E+09 | 0.00 | 0.32 | 0.17 | 2535.93 | 2405.11 | 252.66 | 756.13 | 0.00 | ||||||
Maximum of Months | 0.229816E+11 | 0.815018E+10 | 744.00 | 0.212870E+11 | 0.169453E+10 | 0.00 | 1.00 | 0.80 | 8877.56 | 8320.25 | 863.21 | 3616.15 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.378506E+11 | 0.100677E+11 | 744.00 | 0.364888E+11 | 0.136175E+10 | 0.00 | 0.31 | 12-JAN-17:00 | 0.11 | 01-JAN-06:55 | 23519.28 | 13-JAN-17:00 | 22233.48 | 12-JAN-17:00 | 2444.23 | 17-JAN-17:00 | 6987.39 | 12-JAN-16:50 | 0.00 |
February | 0.857714E+11 | 0.228533E+11 | 672.00 | 0.835400E+11 | 0.223139E+10 | 0.00 | 0.56 | 22-FEB-17:00 | 0.35 | 11-FEB-08:00 | 43267.32 | 22-FEB-17:00 | 41745.54 | 21-FEB-17:00 | 2601.68 | 15-FEB-17:00 | 14348.64 | 22-FEB-15:00 | 0.00 |
March | 0.153635E+12 | 0.460445E+11 | 744.00 | 0.150352E+12 | 0.328374E+10 | 0.00 | 0.91 | 31-MAR-24:00 | 0.61 | 01-MAR-07:00 | 75278.30 | 31-MAR-24:00 | 74276.65 | 31-MAR-23:55 | 3339.79 | 10-MAR-17:10 | 26283.44 | 28-MAR-16:00 | 0.00 |
April | 0.199385E+12 | 0.713424E+11 | 720.00 | 0.196304E+12 | 0.308105E+10 | 0.00 | 1.00 | 01-APR-14:50 | 0.33 | 30-APR-24:00 | 81280.53 | 12-APR-16:00 | 79024.97 | 12-APR-16:00 | 3826.54 | 26-APR-08:00 | 34468.43 | 15-APR-15:00 | 0.00 |
May | 0.684750E+11 | 0.270851E+11 | 744.00 | 0.619288E+11 | 0.654623E+10 | 0.00 | 0.56 | 31-MAY-23:13 | 0.27 | 13-MAY-07:00 | 44872.84 | 31-MAY-23:03 | 39296.57 | 31-MAY-24:00 | 6293.99 | 22-MAY-23:20 | 15030.94 | 01-MAY-16:00 | 0.00 |
June | 0.117971E+12 | 0.464575E+11 | 720.00 | 0.107217E+12 | 0.107537E+11 | 0.00 | 0.81 | 30-JUN-23:23 | 0.53 | 02-JUN-06:00 | 63359.21 | 30-JUN-23:02 | 58520.51 | 30-JUN-23:42 | 8092.84 | 28-JUN-13:30 | 24590.64 | 08-JUN-16:00 | 0.00 |
July | 0.173886E+12 | 0.647873E+11 | 744.00 | 0.157845E+12 | 0.160410E+11 | 0.00 | 1.00 | 31-JUL-23:02 | 0.75 | 19-JUL-02:50 | 82778.59 | 31-JUL-23:02 | 75591.78 | 31-JUL-24:00 | 8439.38 | 18-JUL-08:20 | 30886.56 | 02-JUL-17:00 | 0.00 |
August | 0.218200E+12 | 0.775549E+11 | 744.00 | 0.201224E+12 | 0.169754E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.34 | 31-AUG-23:05 | 84519.27 | 10-AUG-14:10 | 76964.94 | 10-AUG-16:10 | 8605.14 | 21-AUG-14:00 | 33073.80 | 07-AUG-15:00 | 0.00 |
September | 0.696018E+11 | 0.238924E+11 | 720.00 | 0.570511E+11 | 0.125507E+11 | 0.00 | 0.56 | 30-SEP-23:05 | 0.28 | 09-SEP-17:20 | 45100.20 | 30-SEP-23:05 | 39211.09 | 30-SEP-23:47 | 7275.45 | 12-SEP-16:00 | 14378.35 | 30-SEP-23:20 | 0.00 |
October | 0.110715E+12 | 0.354976E+11 | 744.00 | 0.104585E+12 | 0.613008E+10 | 0.00 | 0.68 | 31-OCT-23:20 | 0.44 | 31-OCT-06:00 | 56464.50 | 31-OCT-23:10 | 54415.42 | 31-OCT-24:00 | 4936.58 | 06-OCT-09:40 | 19618.00 | 02-OCT-15:10 | 0.00 |
November | 0.144834E+12 | 0.404091E+11 | 720.00 | 0.141754E+12 | 0.307967E+10 | 0.00 | 0.80 | 08-NOV-16:30 | 0.59 | 25-NOV-08:00 | 63051.60 | 08-NOV-16:50 | 60549.53 | 08-NOV-16:30 | 2791.21 | 08-NOV-20:00 | 22327.51 | 08-NOV-15:00 | 0.00 |
December | 0.187626E+12 | 0.464298E+11 | 744.00 | 0.185929E+12 | 0.169760E+10 | 0.00 | 0.94 | 28-DEC-16:40 | 0.75 | 23-DEC-08:00 | 78455.51 | 28-DEC-17:00 | 76860.60 | 28-DEC-17:00 | 2516.77 | 29-DEC-17:10 | 24429.99 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.156795E+13 | 0.512422E+12 | 8760.00 | 0.148422E+13 | 0.837323E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.378506E+11 | 0.100677E+11 | 672.00 | 0.364888E+11 | 0.136175E+10 | 0.00 | 0.31 | 0.11 | 23519.28 | 22233.48 | 2444.23 | 6987.39 | 0.00 | ||||||
Maximum of Months | 0.218200E+12 | 0.775549E+11 | 744.00 | 0.201224E+12 | 0.169754E+11 | 0.00 | 1.00 | 0.75 | 84519.27 | 79024.97 | 8605.14 | 34468.43 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.236917E+10 | 0.657129E+09 | 669.78 | 0.224348E+10 | 0.125685E+09 | 0.00 | 0.30 | 12-JAN-17:00 | 0.00 | 01-JAN-00:05 | 2366.30 | 12-JAN-17:00 | 2229.68 | 12-JAN-17:00 | 252.88 | 17-JAN-16:20 | 706.63 | 12-JAN-16:40 | 0.00 |
February | 0.790104E+10 | 0.214177E+10 | 672.00 | 0.766512E+10 | 0.235918E+09 | 0.00 | 0.55 | 22-FEB-17:00 | 0.26 | 11-FEB-05:55 | 4374.65 | 22-FEB-17:00 | 4213.59 | 22-FEB-17:00 | 267.68 | 15-FEB-17:00 | 1458.53 | 22-FEB-15:00 | 0.00 |
March | 0.151950E+11 | 0.460039E+10 | 744.00 | 0.148479E+11 | 0.347089E+09 | 0.00 | 0.89 | 31-MAR-24:00 | 0.55 | 01-MAR-08:00 | 7484.67 | 31-MAR-24:00 | 7377.29 | 31-MAR-23:55 | 341.73 | 10-MAR-17:10 | 2700.81 | 28-MAR-16:00 | 0.00 |
April | 0.200991E+11 | 0.725302E+10 | 720.00 | 0.197737E+11 | 0.325387E+09 | 0.00 | 1.00 | 01-APR-16:50 | 0.33 | 30-APR-24:00 | 8328.97 | 16-APR-20:45 | 8058.99 | 16-APR-20:45 | 389.85 | 26-APR-08:00 | 3560.48 | 15-APR-15:00 | 0.00 |
May | 0.708995E+10 | 0.281889E+10 | 744.00 | 0.641440E+10 | 0.675549E+09 | 0.00 | 0.55 | 31-MAY-23:13 | 0.26 | 13-MAY-07:00 | 4470.53 | 31-MAY-23:03 | 3904.77 | 31-MAY-24:00 | 640.61 | 31-MAY-23:03 | 1630.48 | 28-MAY-16:41 | 0.00 |
June | 0.120234E+11 | 0.476283E+10 | 720.00 | 0.109277E+11 | 0.109569E+10 | 0.00 | 0.80 | 30-JUN-23:12 | 0.50 | 24-JUN-14:00 | 6403.03 | 30-JUN-23:02 | 5895.66 | 30-JUN-24:00 | 820.51 | 28-JUN-13:30 | 2573.10 | 11-JUN-16:50 | 0.00 |
July | 0.176142E+11 | 0.660460E+10 | 744.00 | 0.159897E+11 | 0.162452E+10 | 0.00 | 0.99 | 31-JUL-23:02 | 0.73 | 19-JUL-02:55 | 8401.04 | 31-JUL-23:02 | 7621.05 | 31-JUL-24:00 | 850.97 | 18-JUL-08:20 | 3303.24 | 02-JUL-17:00 | 0.00 |
August | 0.221336E+11 | 0.793704E+10 | 744.00 | 0.204100E+11 | 0.172357E+10 | 0.00 | 1.00 | 01-AUG-09:00 | 0.34 | 31-AUG-23:12 | 8626.26 | 10-AUG-14:10 | 7841.64 | 20-AUG-16:15 | 872.38 | 21-AUG-14:00 | 3415.70 | 07-AUG-15:00 | 0.00 |
September | 0.704468E+10 | 0.243260E+10 | 720.00 | 0.577045E+10 | 0.127424E+10 | 0.00 | 0.55 | 30-SEP-23:05 | 0.26 | 09-SEP-17:12 | 4502.76 | 30-SEP-23:05 | 3904.67 | 30-SEP-23:34 | 734.59 | 12-SEP-16:00 | 1444.66 | 30-SEP-23:20 | 0.00 |
October | 0.109998E+11 | 0.355879E+10 | 744.00 | 0.103688E+11 | 0.630952E+09 | 0.00 | 0.65 | 31-OCT-23:20 | 0.40 | 28-OCT-07:00 | 5526.58 | 31-OCT-23:10 | 5296.07 | 31-OCT-24:00 | 502.87 | 06-OCT-09:50 | 2024.74 | 02-OCT-15:10 | 0.00 |
November | 0.139896E+11 | 0.395676E+10 | 720.00 | 0.136645E+11 | 0.325164E+09 | 0.00 | 0.78 | 08-NOV-16:20 | 0.50 | 26-NOV-07:30 | 6368.32 | 08-NOV-16:40 | 6114.37 | 08-NOV-16:30 | 285.92 | 08-NOV-20:00 | 2268.12 | 08-NOV-15:00 | 0.00 |
December | 0.176063E+11 | 0.443145E+10 | 744.00 | 0.174211E+11 | 0.185240E+09 | 0.00 | 0.92 | 28-DEC-16:40 | 0.61 | 31-DEC-08:00 | 7856.84 | 28-DEC-17:00 | 7689.88 | 28-DEC-17:00 | 258.22 | 29-DEC-17:10 | 2462.46 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.154066E+12 | 0.511553E+11 | 8685.78 | 0.145497E+12 | 0.856900E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.236917E+10 | 0.657129E+09 | 669.78 | 0.224348E+10 | 0.125685E+09 | 0.00 | 0.30 | 0.00 | 2366.30 | 2229.68 | 252.88 | 706.63 | 0.00 | ||||||
Maximum of Months | 0.221336E+11 | 0.793704E+10 | 744.00 | 0.204100E+11 | 0.172357E+10 | 0.00 | 1.00 | 0.73 | 8626.26 | 8058.99 | 872.38 | 3560.48 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.15 | 0.00 | 91.15 | 48.60 | 364.15 | 0.00 | 0.00 | 0.00 |
February | 108.09 | 0.00 | 108.09 | 101.14 | 276.67 | 0.00 | 0.00 | 0.00 |
March | 130.25 | 0.00 | 130.25 | 198.15 | 157.20 | 0.00 | 0.00 | 0.00 |
April | 141.33 | 0.48 | 140.85 | 341.82 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 156.58 | 4.39 | 152.19 | 477.69 | 7.31 | 0.00 | 0.00 | 0.00 |
June | 162.09 | 6.00 | 156.08 | 517.82 | 5.57 | 0.00 | 0.00 | 0.00 |
July | 159.85 | 2.53 | 157.32 | 462.03 | 1.15 | 0.00 | 0.00 | 0.00 |
August | 146.75 | 0.46 | 146.29 | 386.34 | 4.17 | 0.00 | 0.00 | 0.00 |
September | 130.76 | 0.01 | 130.75 | 303.33 | 20.03 | 0.00 | 0.00 | 0.00 |
October | 113.28 | 0.00 | 113.28 | 219.98 | 119.12 | 0.00 | 0.00 | 0.00 |
November | 95.95 | 0.00 | 95.95 | 117.38 | 243.55 | 0.00 | 0.00 | 0.00 |
December | 88.92 | 0.00 | 88.92 | 53.44 | 355.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.18 | 1.16 | 126.02 | 269.80 | 133.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.92 | 0.00 | 88.92 | 48.60 | 1.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.09 | 6.00 | 157.32 | 517.82 | 364.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.15 | 0.00 | 91.15 | 48.60 | 364.15 | 0.00 | 0.00 | 0.00 |
February | 108.09 | 0.00 | 108.09 | 101.14 | 276.67 | 0.00 | 0.00 | 0.00 |
March | 130.24 | 0.00 | 130.24 | 198.15 | 157.20 | 0.00 | 0.00 | 0.00 |
April | 141.33 | 0.48 | 140.85 | 341.82 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 156.58 | 4.39 | 152.18 | 477.69 | 7.31 | 0.00 | 0.00 | 0.00 |
June | 162.08 | 6.00 | 156.08 | 517.82 | 5.57 | 0.00 | 0.00 | 0.00 |
July | 159.85 | 2.53 | 157.32 | 462.02 | 1.15 | 0.00 | 0.00 | 0.00 |
August | 146.75 | 0.46 | 146.29 | 386.34 | 4.17 | 0.00 | 0.00 | 0.00 |
September | 130.76 | 0.01 | 130.75 | 303.33 | 20.02 | 0.00 | 0.00 | 0.00 |
October | 113.28 | 0.00 | 113.28 | 219.98 | 119.11 | 0.00 | 0.00 | 0.00 |
November | 95.95 | 0.00 | 95.95 | 117.38 | 243.55 | 0.00 | 0.00 | 0.00 |
December | 88.92 | 0.00 | 88.92 | 53.44 | 355.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.18 | 1.16 | 126.02 | 269.79 | 133.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.92 | 0.00 | 88.92 | 48.60 | 1.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.08 | 6.00 | 157.32 | 517.82 | 364.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.15 | 0.00 | 91.15 | 48.60 | 364.15 | 0.00 | 0.00 | 0.00 |
February | 108.09 | 0.00 | 108.09 | 101.14 | 276.67 | 0.00 | 0.00 | 0.00 |
March | 130.24 | 0.00 | 130.24 | 198.15 | 157.20 | 0.00 | 0.00 | 0.00 |
April | 141.33 | 0.48 | 140.85 | 341.82 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 156.58 | 4.39 | 152.19 | 477.69 | 7.31 | 0.00 | 0.00 | 0.00 |
June | 162.08 | 6.00 | 156.08 | 517.82 | 5.57 | 0.00 | 0.00 | 0.00 |
July | 159.85 | 2.53 | 157.32 | 462.02 | 1.15 | 0.00 | 0.00 | 0.00 |
August | 146.75 | 0.46 | 146.29 | 386.34 | 4.17 | 0.00 | 0.00 | 0.00 |
September | 130.76 | 0.01 | 130.75 | 303.33 | 20.03 | 0.00 | 0.00 | 0.00 |
October | 113.28 | 0.00 | 113.28 | 219.98 | 119.11 | 0.00 | 0.00 | 0.00 |
November | 95.95 | 0.00 | 95.95 | 117.38 | 243.55 | 0.00 | 0.00 | 0.00 |
December | 88.92 | 0.00 | 88.92 | 53.44 | 355.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.18 | 1.16 | 126.02 | 269.80 | 133.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.92 | 0.00 | 88.92 | 48.60 | 1.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.08 | 6.00 | 157.32 | 517.82 | 364.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.15 | 0.00 | 91.15 | 48.60 | 364.15 | 0.00 | 0.00 | 0.00 |
February | 108.09 | 0.00 | 108.09 | 101.14 | 276.67 | 0.00 | 0.00 | 0.00 |
March | 130.24 | 0.00 | 130.24 | 198.15 | 157.20 | 0.00 | 0.00 | 0.00 |
April | 141.33 | 0.48 | 140.85 | 341.82 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 156.58 | 4.39 | 152.18 | 477.69 | 7.31 | 0.00 | 0.00 | 0.00 |
June | 162.08 | 6.00 | 156.08 | 517.82 | 5.57 | 0.00 | 0.00 | 0.00 |
July | 159.85 | 2.53 | 157.32 | 462.02 | 1.15 | 0.00 | 0.00 | 0.00 |
August | 146.75 | 0.46 | 146.29 | 386.34 | 4.17 | 0.00 | 0.00 | 0.00 |
September | 130.76 | 0.01 | 130.75 | 303.33 | 20.02 | 0.00 | 0.00 | 0.00 |
October | 113.28 | 0.00 | 113.28 | 219.98 | 119.11 | 0.00 | 0.00 | 0.00 |
November | 95.95 | 0.00 | 95.95 | 117.38 | 243.55 | 0.00 | 0.00 | 0.00 |
December | 88.92 | 0.00 | 88.92 | 53.44 | 355.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.18 | 1.16 | 126.02 | 269.79 | 133.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.92 | 0.00 | 88.92 | 48.60 | 1.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.08 | 6.00 | 157.32 | 517.82 | 364.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.14 | 0.00 | 91.14 | 48.60 | 364.13 | 0.00 | 0.00 | 0.00 |
February | 108.08 | 0.00 | 108.08 | 101.13 | 276.66 | 0.00 | 0.00 | 0.00 |
March | 130.24 | 0.00 | 130.24 | 198.14 | 157.19 | 0.00 | 0.00 | 0.00 |
April | 141.32 | 0.48 | 140.84 | 341.81 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 156.57 | 4.39 | 152.18 | 477.67 | 7.31 | 0.00 | 0.00 | 0.00 |
June | 162.08 | 6.00 | 156.07 | 517.80 | 5.57 | 0.00 | 0.00 | 0.00 |
July | 159.84 | 2.53 | 157.31 | 462.00 | 1.15 | 0.00 | 0.00 | 0.00 |
August | 146.74 | 0.46 | 146.28 | 386.33 | 4.17 | 0.00 | 0.00 | 0.00 |
September | 130.75 | 0.01 | 130.74 | 303.32 | 20.02 | 0.00 | 0.00 | 0.00 |
October | 113.27 | 0.00 | 113.27 | 219.97 | 119.11 | 0.00 | 0.00 | 0.00 |
November | 95.94 | 0.00 | 95.94 | 117.38 | 243.54 | 0.00 | 0.00 | 0.00 |
December | 88.91 | 0.00 | 88.91 | 53.43 | 355.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.17 | 1.16 | 126.01 | 269.78 | 133.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.91 | 0.00 | 88.91 | 48.60 | 1.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.08 | 6.00 | 157.31 | 517.80 | 364.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.96 | 87.08 | 129.87 | 219.21 | 365.79 | 0.00 | 0.00 | 0.00 |
February | 263.57 | 108.82 | 154.76 | 341.29 | 280.55 | 0.00 | 0.00 | 0.00 |
March | 321.53 | 132.72 | 188.81 | 524.69 | 160.38 | 0.00 | 0.00 | 0.00 |
April | 382.54 | 178.36 | 204.18 | 782.09 | 49.31 | 0.00 | 0.00 | 0.00 |
May | 376.52 | 166.93 | 209.59 | 887.54 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 306.44 | 101.68 | 204.76 | 805.15 | 5.23 | 0.00 | 0.00 | 0.00 |
July | 257.56 | 54.39 | 203.17 | 666.55 | 0.76 | 0.00 | 0.00 | 0.00 |
August | 232.07 | 40.39 | 191.68 | 565.49 | 2.44 | 0.00 | 0.00 | 0.00 |
September | 247.94 | 69.14 | 178.79 | 521.24 | 19.75 | 0.00 | 0.00 | 0.00 |
October | 271.22 | 109.55 | 161.66 | 502.66 | 124.82 | 0.00 | 0.00 | 0.00 |
November | 240.47 | 103.22 | 137.25 | 356.57 | 247.42 | 0.00 | 0.00 | 0.00 |
December | 209.68 | 83.08 | 126.60 | 230.83 | 354.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.13 | 102.79 | 174.35 | 534.28 | 134.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.68 | 40.39 | 126.60 | 219.21 | 0.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.54 | 178.36 | 209.59 | 887.54 | 365.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.96 | 87.08 | 129.87 | 219.21 | 365.79 | 0.00 | 0.00 | 0.00 |
February | 263.57 | 108.82 | 154.76 | 341.29 | 280.55 | 0.00 | 0.00 | 0.00 |
March | 321.53 | 132.72 | 188.81 | 524.69 | 160.38 | 0.00 | 0.00 | 0.00 |
April | 382.54 | 178.36 | 204.18 | 782.09 | 49.31 | 0.00 | 0.00 | 0.00 |
May | 376.52 | 166.93 | 209.59 | 887.54 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 306.44 | 101.68 | 204.76 | 805.15 | 5.23 | 0.00 | 0.00 | 0.00 |
July | 257.56 | 54.39 | 203.17 | 666.55 | 0.76 | 0.00 | 0.00 | 0.00 |
August | 232.07 | 40.39 | 191.68 | 565.49 | 2.44 | 0.00 | 0.00 | 0.00 |
September | 247.94 | 69.14 | 178.79 | 521.24 | 19.75 | 0.00 | 0.00 | 0.00 |
October | 271.22 | 109.55 | 161.66 | 502.66 | 124.82 | 0.00 | 0.00 | 0.00 |
November | 240.47 | 103.22 | 137.25 | 356.57 | 247.42 | 0.00 | 0.00 | 0.00 |
December | 209.68 | 83.08 | 126.60 | 230.83 | 354.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.13 | 102.79 | 174.35 | 534.28 | 134.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.68 | 40.39 | 126.60 | 219.21 | 0.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.54 | 178.36 | 209.59 | 887.54 | 365.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.95 | 87.08 | 129.87 | 219.21 | 365.78 | 0.00 | 0.00 | 0.00 |
February | 263.57 | 108.81 | 154.75 | 341.28 | 280.54 | 0.00 | 0.00 | 0.00 |
March | 321.53 | 132.71 | 188.81 | 524.68 | 160.37 | 0.00 | 0.00 | 0.00 |
April | 382.53 | 178.36 | 204.18 | 782.08 | 49.31 | 0.00 | 0.00 | 0.00 |
May | 376.52 | 166.93 | 209.59 | 887.52 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 306.43 | 101.67 | 204.76 | 805.13 | 5.23 | 0.00 | 0.00 | 0.00 |
July | 257.55 | 54.39 | 203.16 | 666.54 | 0.76 | 0.00 | 0.00 | 0.00 |
August | 232.06 | 40.38 | 191.68 | 565.48 | 2.44 | 0.00 | 0.00 | 0.00 |
September | 247.93 | 69.14 | 178.79 | 521.23 | 19.75 | 0.00 | 0.00 | 0.00 |
October | 271.21 | 109.55 | 161.66 | 502.65 | 124.82 | 0.00 | 0.00 | 0.00 |
November | 240.47 | 103.22 | 137.25 | 356.56 | 247.42 | 0.00 | 0.00 | 0.00 |
December | 209.68 | 83.08 | 126.60 | 230.83 | 354.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.13 | 102.78 | 174.34 | 534.27 | 134.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.68 | 40.38 | 126.60 | 219.21 | 0.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.53 | 178.36 | 209.59 | 887.52 | 365.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.54 | 251.88 | 162.65 | 568.27 | 332.84 | 0.00 | 0.00 | 0.00 |
February | 394.17 | 218.93 | 175.24 | 588.59 | 267.96 | 0.00 | 0.00 | 0.00 |
March | 337.02 | 148.86 | 188.16 | 589.09 | 161.73 | 0.00 | 0.00 | 0.00 |
April | 236.73 | 66.81 | 169.92 | 549.36 | 53.97 | 0.00 | 0.00 | 0.00 |
May | 170.24 | 12.60 | 157.64 | 511.34 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.07 | 505.61 | 5.55 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.20 | 469.00 | 1.07 | 0.00 | 0.00 | 0.00 |
August | 172.31 | 9.20 | 163.11 | 438.83 | 4.40 | 0.00 | 0.00 | 0.00 |
September | 230.99 | 59.95 | 171.04 | 496.69 | 22.56 | 0.00 | 0.00 | 0.00 |
October | 397.40 | 221.90 | 175.49 | 736.26 | 127.20 | 0.00 | 0.00 | 0.00 |
November | 496.37 | 328.09 | 168.28 | 804.33 | 244.21 | 0.00 | 0.00 | 0.00 |
December | 443.00 | 277.59 | 165.40 | 629.42 | 331.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.37 | 132.90 | 167.47 | 573.61 | 129.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.07 | 438.83 | 1.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.37 | 328.09 | 188.16 | 804.33 | 332.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.53 | 251.88 | 162.65 | 568.26 | 332.84 | 0.00 | 0.00 | 0.00 |
February | 394.16 | 218.93 | 175.23 | 588.58 | 267.96 | 0.00 | 0.00 | 0.00 |
March | 337.02 | 148.86 | 188.16 | 589.08 | 161.73 | 0.00 | 0.00 | 0.00 |
April | 236.72 | 66.81 | 169.91 | 549.36 | 53.97 | 0.00 | 0.00 | 0.00 |
May | 170.24 | 12.60 | 157.64 | 511.34 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.07 | 505.61 | 5.55 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.20 | 469.00 | 1.07 | 0.00 | 0.00 | 0.00 |
August | 172.31 | 9.20 | 163.10 | 438.83 | 4.40 | 0.00 | 0.00 | 0.00 |
September | 230.99 | 59.95 | 171.04 | 496.69 | 22.56 | 0.00 | 0.00 | 0.00 |
October | 397.39 | 221.90 | 175.49 | 736.26 | 127.20 | 0.00 | 0.00 | 0.00 |
November | 496.37 | 328.09 | 168.28 | 804.32 | 244.21 | 0.00 | 0.00 | 0.00 |
December | 442.99 | 277.59 | 165.40 | 629.42 | 331.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.37 | 132.90 | 167.47 | 573.61 | 129.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.07 | 438.83 | 1.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.37 | 328.09 | 188.16 | 804.32 | 332.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.54 | 251.88 | 162.65 | 568.27 | 332.84 | 0.00 | 0.00 | 0.00 |
February | 394.17 | 218.93 | 175.24 | 588.59 | 267.96 | 0.00 | 0.00 | 0.00 |
March | 337.02 | 148.86 | 188.16 | 589.09 | 161.73 | 0.00 | 0.00 | 0.00 |
April | 236.73 | 66.81 | 169.92 | 549.36 | 53.97 | 0.00 | 0.00 | 0.00 |
May | 170.24 | 12.60 | 157.64 | 511.34 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.07 | 505.61 | 5.55 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.20 | 469.00 | 1.07 | 0.00 | 0.00 | 0.00 |
August | 172.31 | 9.20 | 163.11 | 438.83 | 4.40 | 0.00 | 0.00 | 0.00 |
September | 230.99 | 59.95 | 171.04 | 496.69 | 22.56 | 0.00 | 0.00 | 0.00 |
October | 397.40 | 221.90 | 175.49 | 736.26 | 127.20 | 0.00 | 0.00 | 0.00 |
November | 496.37 | 328.09 | 168.28 | 804.33 | 244.21 | 0.00 | 0.00 | 0.00 |
December | 443.00 | 277.59 | 165.40 | 629.42 | 331.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.37 | 132.90 | 167.47 | 573.61 | 129.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.07 | 438.83 | 1.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.37 | 328.09 | 188.16 | 804.33 | 332.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.53 | 251.88 | 162.65 | 568.26 | 332.84 | 0.00 | 0.00 | 0.00 |
February | 394.16 | 218.93 | 175.23 | 588.58 | 267.96 | 0.00 | 0.00 | 0.00 |
March | 337.02 | 148.86 | 188.16 | 589.08 | 161.73 | 0.00 | 0.00 | 0.00 |
April | 236.72 | 66.81 | 169.91 | 549.36 | 53.97 | 0.00 | 0.00 | 0.00 |
May | 170.24 | 12.60 | 157.64 | 511.34 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.07 | 505.61 | 5.55 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.20 | 469.00 | 1.07 | 0.00 | 0.00 | 0.00 |
August | 172.31 | 9.20 | 163.10 | 438.83 | 4.40 | 0.00 | 0.00 | 0.00 |
September | 230.99 | 59.95 | 171.04 | 496.69 | 22.56 | 0.00 | 0.00 | 0.00 |
October | 397.39 | 221.90 | 175.49 | 736.26 | 127.20 | 0.00 | 0.00 | 0.00 |
November | 496.37 | 328.09 | 168.28 | 804.32 | 244.21 | 0.00 | 0.00 | 0.00 |
December | 442.99 | 277.59 | 165.40 | 629.42 | 331.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.37 | 132.90 | 167.47 | 573.61 | 129.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.07 | 438.83 | 1.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.37 | 328.09 | 188.16 | 804.32 | 332.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.52 | 251.87 | 162.65 | 568.24 | 332.82 | 0.00 | 0.00 | 0.00 |
February | 394.15 | 218.92 | 175.23 | 588.56 | 267.95 | 0.00 | 0.00 | 0.00 |
March | 337.01 | 148.85 | 188.15 | 589.06 | 161.72 | 0.00 | 0.00 | 0.00 |
April | 236.72 | 66.81 | 169.91 | 549.34 | 53.97 | 0.00 | 0.00 | 0.00 |
May | 170.23 | 12.60 | 157.63 | 511.32 | 7.39 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.06 | 505.59 | 5.55 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.19 | 468.98 | 1.07 | 0.00 | 0.00 | 0.00 |
August | 172.30 | 9.20 | 163.10 | 438.81 | 4.40 | 0.00 | 0.00 | 0.00 |
September | 230.98 | 59.95 | 171.03 | 496.67 | 22.55 | 0.00 | 0.00 | 0.00 |
October | 397.38 | 221.89 | 175.49 | 736.23 | 127.19 | 0.00 | 0.00 | 0.00 |
November | 496.35 | 328.07 | 168.27 | 804.29 | 244.20 | 0.00 | 0.00 | 0.00 |
December | 442.98 | 277.58 | 165.40 | 629.39 | 331.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.36 | 132.89 | 167.47 | 573.59 | 129.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.06 | 438.81 | 1.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.35 | 328.07 | 188.15 | 804.29 | 332.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 212.26 | 82.60 | 129.65 | 235.54 | 421.97 | 0.00 | 0.00 | 0.00 |
February | 242.72 | 89.45 | 153.27 | 316.69 | 339.87 | 0.00 | 0.00 | 0.00 |
March | 314.75 | 125.82 | 188.93 | 507.04 | 208.81 | 0.00 | 0.00 | 0.00 |
April | 382.57 | 179.41 | 203.16 | 753.74 | 85.05 | 0.00 | 0.00 | 0.00 |
May | 362.26 | 153.66 | 208.60 | 847.23 | 13.37 | 0.00 | 0.00 | 0.00 |
June | 340.26 | 132.17 | 208.09 | 834.80 | 10.77 | 0.00 | 0.00 | 0.00 |
July | 252.49 | 49.11 | 203.38 | 613.79 | 4.29 | 0.00 | 0.00 | 0.00 |
August | 231.88 | 41.21 | 190.67 | 513.19 | 16.98 | 0.00 | 0.00 | 0.00 |
September | 254.90 | 74.83 | 180.07 | 520.96 | 33.50 | 0.00 | 0.00 | 0.00 |
October | 265.31 | 105.65 | 159.67 | 487.26 | 157.26 | 0.00 | 0.00 | 0.00 |
November | 240.02 | 102.29 | 137.72 | 360.71 | 309.08 | 0.00 | 0.00 | 0.00 |
December | 205.39 | 78.32 | 127.07 | 225.55 | 441.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.35 | 101.08 | 174.27 | 518.60 | 169.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 205.39 | 41.21 | 127.07 | 225.55 | 4.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.57 | 179.41 | 208.60 | 847.23 | 441.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 212.26 | 82.60 | 129.65 | 235.54 | 421.97 | 0.00 | 0.00 | 0.00 |
February | 242.72 | 89.45 | 153.27 | 316.69 | 339.87 | 0.00 | 0.00 | 0.00 |
March | 314.75 | 125.82 | 188.93 | 507.04 | 208.81 | 0.00 | 0.00 | 0.00 |
April | 382.57 | 179.41 | 203.16 | 753.74 | 85.05 | 0.00 | 0.00 | 0.00 |
May | 362.26 | 153.66 | 208.60 | 847.23 | 13.37 | 0.00 | 0.00 | 0.00 |
June | 340.26 | 132.17 | 208.09 | 834.80 | 10.77 | 0.00 | 0.00 | 0.00 |
July | 252.49 | 49.11 | 203.38 | 613.79 | 4.29 | 0.00 | 0.00 | 0.00 |
August | 231.88 | 41.21 | 190.67 | 513.19 | 16.98 | 0.00 | 0.00 | 0.00 |
September | 254.90 | 74.83 | 180.07 | 520.96 | 33.50 | 0.00 | 0.00 | 0.00 |
October | 265.31 | 105.65 | 159.67 | 487.26 | 157.26 | 0.00 | 0.00 | 0.00 |
November | 240.02 | 102.29 | 137.72 | 360.71 | 309.08 | 0.00 | 0.00 | 0.00 |
December | 205.39 | 78.32 | 127.07 | 225.55 | 441.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.35 | 101.08 | 174.27 | 518.60 | 169.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 205.39 | 41.21 | 127.07 | 225.55 | 4.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.57 | 179.41 | 208.60 | 847.23 | 441.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 212.25 | 82.60 | 129.65 | 235.53 | 421.97 | 0.00 | 0.00 | 0.00 |
February | 242.72 | 89.45 | 153.27 | 316.68 | 339.86 | 0.00 | 0.00 | 0.00 |
March | 314.74 | 125.81 | 188.93 | 507.03 | 208.81 | 0.00 | 0.00 | 0.00 |
April | 382.56 | 179.41 | 203.16 | 753.72 | 85.05 | 0.00 | 0.00 | 0.00 |
May | 362.25 | 153.66 | 208.59 | 847.21 | 13.37 | 0.00 | 0.00 | 0.00 |
June | 340.25 | 132.16 | 208.09 | 834.78 | 10.77 | 0.00 | 0.00 | 0.00 |
July | 252.48 | 49.11 | 203.38 | 613.77 | 4.29 | 0.00 | 0.00 | 0.00 |
August | 231.88 | 41.21 | 190.67 | 513.18 | 16.98 | 0.00 | 0.00 | 0.00 |
September | 254.90 | 74.83 | 180.07 | 520.95 | 33.50 | 0.00 | 0.00 | 0.00 |
October | 265.31 | 105.65 | 159.66 | 487.25 | 157.25 | 0.00 | 0.00 | 0.00 |
November | 240.02 | 102.29 | 137.72 | 360.70 | 309.08 | 0.00 | 0.00 | 0.00 |
December | 205.38 | 78.32 | 127.07 | 225.54 | 441.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.35 | 101.08 | 174.27 | 518.59 | 169.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 205.38 | 41.21 | 127.07 | 225.54 | 4.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.56 | 179.41 | 208.59 | 847.21 | 441.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 455.75 | 0.00 | 455.75 | 294.09 | 1637.52 | 0.00 | 0.00 | 0.00 |
February | 540.44 | 0.00 | 540.44 | 551.59 | 1259.55 | 0.00 | 0.00 | 0.00 |
March | 651.23 | 0.00 | 651.23 | 1017.26 | 748.95 | 0.00 | 0.00 | 0.00 |
April | 706.64 | 2.40 | 704.24 | 1746.58 | 251.70 | 0.00 | 0.00 | 0.00 |
May | 782.90 | 21.97 | 760.93 | 2412.64 | 38.28 | 0.00 | 0.00 | 0.00 |
June | 810.43 | 30.02 | 780.41 | 2610.30 | 31.32 | 0.00 | 0.00 | 0.00 |
July | 799.27 | 12.66 | 786.61 | 2325.30 | 8.43 | 0.00 | 0.00 | 0.00 |
August | 733.75 | 2.29 | 731.46 | 1962.47 | 27.74 | 0.00 | 0.00 | 0.00 |
September | 653.79 | 0.05 | 653.75 | 1528.59 | 106.50 | 0.00 | 0.00 | 0.00 |
October | 566.40 | 0.00 | 566.40 | 1124.93 | 578.01 | 0.00 | 0.00 | 0.00 |
November | 479.74 | 0.00 | 479.74 | 630.87 | 1120.57 | 0.00 | 0.00 | 0.00 |
December | 444.59 | 0.00 | 444.59 | 333.15 | 1569.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 635.89 | 5.80 | 630.09 | 1382.19 | 612.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 444.59 | 0.00 | 444.59 | 294.09 | 8.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.43 | 30.02 | 786.61 | 2610.30 | 1637.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 650.86 | 261.25 | 389.61 | 690.14 | 1014.34 | 0.00 | 0.00 | 0.00 |
February | 790.71 | 326.44 | 464.27 | 1036.29 | 798.87 | 0.00 | 0.00 | 0.00 |
March | 964.58 | 398.15 | 566.44 | 1567.94 | 488.92 | 0.00 | 0.00 | 0.00 |
April | 1147.61 | 535.07 | 612.53 | 2330.49 | 175.70 | 0.00 | 0.00 | 0.00 |
May | 1129.56 | 500.78 | 628.77 | 2654.06 | 25.82 | 0.00 | 0.00 | 0.00 |
June | 919.31 | 305.03 | 614.29 | 2401.88 | 20.78 | 0.00 | 0.00 | 0.00 |
July | 772.66 | 163.16 | 609.49 | 1976.00 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 696.20 | 121.15 | 575.04 | 1671.30 | 18.40 | 0.00 | 0.00 | 0.00 |
September | 743.81 | 207.43 | 536.38 | 1555.82 | 72.45 | 0.00 | 0.00 | 0.00 |
October | 813.64 | 328.66 | 484.98 | 1504.40 | 385.33 | 0.00 | 0.00 | 0.00 |
November | 721.41 | 309.66 | 411.75 | 1079.14 | 719.30 | 0.00 | 0.00 | 0.00 |
December | 629.04 | 249.23 | 379.81 | 724.92 | 991.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.39 | 308.36 | 523.03 | 1601.34 | 391.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 629.04 | 121.15 | 379.81 | 690.14 | 4.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.61 | 535.07 | 628.77 | 2654.06 | 1014.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2072.73 | 1259.44 | 813.28 | 2825.23 | 1639.43 | 0.00 | 0.00 | 0.00 |
February | 1970.86 | 1094.67 | 876.19 | 2927.25 | 1314.03 | 0.00 | 0.00 | 0.00 |
March | 1685.13 | 744.31 | 940.82 | 2935.71 | 810.24 | 0.00 | 0.00 | 0.00 |
April | 1183.64 | 334.06 | 849.58 | 2757.84 | 284.37 | 0.00 | 0.00 | 0.00 |
May | 851.20 | 63.01 | 788.18 | 2578.84 | 38.38 | 0.00 | 0.00 | 0.00 |
June | 778.63 | 13.29 | 765.34 | 2550.64 | 30.88 | 0.00 | 0.00 | 0.00 |
July | 812.18 | 11.17 | 801.01 | 2362.08 | 7.47 | 0.00 | 0.00 | 0.00 |
August | 861.55 | 46.01 | 815.54 | 2216.64 | 29.02 | 0.00 | 0.00 | 0.00 |
September | 1154.98 | 299.78 | 855.20 | 2478.89 | 124.70 | 0.00 | 0.00 | 0.00 |
October | 1987.02 | 1109.54 | 877.48 | 3667.91 | 650.56 | 0.00 | 0.00 | 0.00 |
November | 2481.90 | 1640.48 | 841.42 | 4005.99 | 1212.62 | 0.00 | 0.00 | 0.00 |
December | 2215.03 | 1388.00 | 827.03 | 3144.57 | 1610.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1501.89 | 664.51 | 837.38 | 2869.66 | 643.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 778.63 | 11.17 | 765.34 | 2216.64 | 7.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2481.90 | 1640.48 | 940.82 | 4005.99 | 1639.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.76 | 247.80 | 388.96 | 746.80 | 1123.44 | 0.00 | 0.00 | 0.00 |
February | 728.15 | 268.34 | 459.81 | 994.36 | 884.19 | 0.00 | 0.00 | 0.00 |
March | 944.23 | 377.44 | 566.79 | 1557.88 | 549.28 | 0.00 | 0.00 | 0.00 |
April | 1147.70 | 538.23 | 609.47 | 2322.74 | 206.38 | 0.00 | 0.00 | 0.00 |
May | 1086.77 | 460.98 | 625.78 | 2570.25 | 35.31 | 0.00 | 0.00 | 0.00 |
June | 1020.76 | 396.49 | 624.27 | 2555.83 | 27.12 | 0.00 | 0.00 | 0.00 |
July | 757.46 | 147.33 | 610.13 | 1913.74 | 7.80 | 0.00 | 0.00 | 0.00 |
August | 695.65 | 123.64 | 572.01 | 1646.20 | 24.10 | 0.00 | 0.00 | 0.00 |
September | 764.70 | 224.49 | 540.20 | 1584.15 | 87.72 | 0.00 | 0.00 | 0.00 |
October | 795.93 | 316.94 | 478.99 | 1490.17 | 424.86 | 0.00 | 0.00 | 0.00 |
November | 720.05 | 306.88 | 413.17 | 1131.30 | 797.39 | 0.00 | 0.00 | 0.00 |
December | 616.15 | 234.95 | 381.20 | 751.00 | 1084.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 826.04 | 303.23 | 522.82 | 1607.18 | 435.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 616.15 | 123.64 | 381.20 | 746.80 | 7.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.70 | 538.23 | 625.78 | 2570.25 | 1123.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 455.75 | 0.00 | 455.75 | 350.80 | 1434.86 | 0.00 | 0.00 | 0.00 |
February | 540.44 | 0.00 | 540.44 | 592.24 | 1147.75 | 0.00 | 0.00 | 0.00 |
March | 651.23 | 0.00 | 651.23 | 1024.00 | 714.46 | 0.00 | 0.00 | 0.00 |
April | 706.64 | 2.40 | 704.24 | 1722.45 | 248.57 | 0.00 | 0.00 | 0.00 |
May | 782.90 | 21.97 | 760.93 | 2370.19 | 40.79 | 0.00 | 0.00 | 0.00 |
June | 810.43 | 30.02 | 780.41 | 2566.82 | 33.79 | 0.00 | 0.00 | 0.00 |
July | 799.27 | 12.66 | 786.61 | 2280.58 | 8.74 | 0.00 | 0.00 | 0.00 |
August | 733.75 | 2.29 | 731.46 | 1926.58 | 30.35 | 0.00 | 0.00 | 0.00 |
September | 653.79 | 0.05 | 653.75 | 1510.04 | 107.23 | 0.00 | 0.00 | 0.00 |
October | 566.40 | 0.00 | 566.40 | 1122.00 | 558.62 | 0.00 | 0.00 | 0.00 |
November | 479.74 | 0.00 | 479.74 | 662.03 | 1037.83 | 0.00 | 0.00 | 0.00 |
December | 444.59 | 0.00 | 444.59 | 387.84 | 1401.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 635.89 | 5.80 | 630.09 | 1380.12 | 561.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 444.59 | 0.00 | 444.59 | 350.80 | 8.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.43 | 30.02 | 786.61 | 2566.82 | 1434.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 650.86 | 261.25 | 389.61 | 742.42 | 902.50 | 0.00 | 0.00 | 0.00 |
February | 790.71 | 326.44 | 464.27 | 1062.29 | 745.35 | 0.00 | 0.00 | 0.00 |
March | 964.58 | 398.15 | 566.44 | 1565.65 | 477.85 | 0.00 | 0.00 | 0.00 |
April | 1147.61 | 535.07 | 612.53 | 2309.11 | 177.69 | 0.00 | 0.00 | 0.00 |
May | 1129.56 | 500.78 | 628.77 | 2619.68 | 28.56 | 0.00 | 0.00 | 0.00 |
June | 919.31 | 305.03 | 614.29 | 2367.68 | 22.89 | 0.00 | 0.00 | 0.00 |
July | 772.66 | 163.16 | 609.49 | 1941.60 | 4.98 | 0.00 | 0.00 | 0.00 |
August | 696.20 | 121.15 | 575.04 | 1644.30 | 20.47 | 0.00 | 0.00 | 0.00 |
September | 743.81 | 207.43 | 536.38 | 1539.92 | 74.79 | 0.00 | 0.00 | 0.00 |
October | 813.64 | 328.66 | 484.98 | 1497.75 | 380.59 | 0.00 | 0.00 | 0.00 |
November | 721.41 | 309.66 | 411.75 | 1094.99 | 683.46 | 0.00 | 0.00 | 0.00 |
December | 629.04 | 249.23 | 379.81 | 769.15 | 904.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.39 | 308.36 | 523.03 | 1598.06 | 366.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 629.04 | 121.15 | 379.81 | 742.42 | 4.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.61 | 535.07 | 628.77 | 2619.68 | 904.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2072.73 | 1259.44 | 813.28 | 2887.24 | 1472.64 | 0.00 | 0.00 | 0.00 |
February | 1970.86 | 1094.67 | 876.19 | 2953.51 | 1229.30 | 0.00 | 0.00 | 0.00 |
March | 1685.13 | 744.31 | 940.82 | 2929.66 | 788.87 | 0.00 | 0.00 | 0.00 |
April | 1183.64 | 334.06 | 849.58 | 2729.93 | 284.80 | 0.00 | 0.00 | 0.00 |
May | 851.20 | 63.01 | 788.18 | 2535.53 | 41.03 | 0.00 | 0.00 | 0.00 |
June | 778.63 | 13.29 | 765.34 | 2506.51 | 33.42 | 0.00 | 0.00 | 0.00 |
July | 812.18 | 11.17 | 801.01 | 2316.77 | 7.63 | 0.00 | 0.00 | 0.00 |
August | 861.55 | 46.01 | 815.54 | 2180.37 | 31.87 | 0.00 | 0.00 | 0.00 |
September | 1154.98 | 299.78 | 855.20 | 2456.72 | 127.69 | 0.00 | 0.00 | 0.00 |
October | 1987.02 | 1109.54 | 877.48 | 3655.02 | 643.56 | 0.00 | 0.00 | 0.00 |
November | 2481.90 | 1640.48 | 841.42 | 4015.35 | 1161.92 | 0.00 | 0.00 | 0.00 |
December | 2215.03 | 1388.00 | 827.03 | 3195.93 | 1484.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1501.89 | 664.51 | 837.38 | 2862.11 | 606.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 778.63 | 11.17 | 765.34 | 2180.37 | 7.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2481.90 | 1640.48 | 940.82 | 4015.35 | 1484.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.76 | 247.80 | 388.96 | 776.40 | 1014.22 | 0.00 | 0.00 | 0.00 |
February | 728.15 | 268.34 | 459.81 | 1011.72 | 825.63 | 0.00 | 0.00 | 0.00 |
March | 944.23 | 377.44 | 566.79 | 1556.72 | 532.74 | 0.00 | 0.00 | 0.00 |
April | 1147.70 | 538.23 | 609.47 | 2305.30 | 205.49 | 0.00 | 0.00 | 0.00 |
May | 1086.77 | 460.98 | 625.78 | 2544.10 | 36.85 | 0.00 | 0.00 | 0.00 |
June | 1020.76 | 396.49 | 624.27 | 2528.42 | 28.35 | 0.00 | 0.00 | 0.00 |
July | 757.46 | 147.33 | 610.13 | 1887.98 | 7.82 | 0.00 | 0.00 | 0.00 |
August | 695.65 | 123.64 | 572.01 | 1626.04 | 25.49 | 0.00 | 0.00 | 0.00 |
September | 764.70 | 224.49 | 540.20 | 1572.11 | 87.88 | 0.00 | 0.00 | 0.00 |
October | 795.93 | 316.94 | 478.99 | 1485.74 | 415.53 | 0.00 | 0.00 | 0.00 |
November | 720.05 | 306.88 | 413.17 | 1143.14 | 755.85 | 0.00 | 0.00 | 0.00 |
December | 616.15 | 234.95 | 381.20 | 778.94 | 994.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 826.04 | 303.23 | 522.82 | 1603.10 | 409.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 616.15 | 123.64 | 381.20 | 776.40 | 7.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.70 | 538.23 | 625.78 | 2544.10 | 1014.22 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244134E+09 | 0.00 | 0.244134E+09 | 0.130182E+09 | 0.975338E+09 |
February | 0.261485E+09 | 0.00 | 0.261485E+09 | 0.244673E+09 | 0.669321E+09 |
March | 0.348851E+09 | 0.00 | 0.348851E+09 | 0.530726E+09 | 0.421036E+09 |
April | 0.366321E+09 | 1242306.39 | 0.365078E+09 | 0.886010E+09 | 0.127767E+09 |
May | 0.419386E+09 | 11768647.88 | 0.407617E+09 | 0.127944E+10 | 19589653.05 |
June | 0.420126E+09 | 15561451.75 | 0.404565E+09 | 0.134220E+10 | 14444425.28 |
July | 0.428151E+09 | 6779998.49 | 0.421371E+09 | 0.123749E+10 | 3067051.66 |
August | 0.393055E+09 | 1224970.50 | 0.391830E+09 | 0.103478E+10 | 11160836.65 |
September | 0.338926E+09 | 23798.53 | 0.338902E+09 | 0.786234E+09 | 51906013.73 |
October | 0.303407E+09 | 0.00 | 0.303407E+09 | 0.589186E+09 | 0.319039E+09 |
November | 0.248699E+09 | 0.00 | 0.248699E+09 | 0.304258E+09 | 0.631275E+09 |
December | 0.238157E+09 | 0.00 | 0.238157E+09 | 0.143126E+09 | 0.951538E+09 |
Annual Sum or Average | 0.401070E+10 | 36601173.55 | 0.397410E+10 | 0.850831E+10 | 0.419548E+10 |
Minimum of Months | 0.238157E+09 | 0.00 | 0.238157E+09 | 0.130182E+09 | 3067051.66 |
Maximum of Months | 0.428151E+09 | 15561451.75 | 0.421371E+09 | 0.134220E+10 | 0.975338E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244130E+09 | 0.00 | 0.244130E+09 | 0.130179E+09 | 0.975336E+09 |
February | 0.261481E+09 | 0.00 | 0.261481E+09 | 0.244669E+09 | 0.669319E+09 |
March | 0.348846E+09 | 0.00 | 0.348846E+09 | 0.530720E+09 | 0.421033E+09 |
April | 0.366316E+09 | 1242279.08 | 0.365074E+09 | 0.886006E+09 | 0.127765E+09 |
May | 0.419380E+09 | 11768389.16 | 0.407612E+09 | 0.127944E+10 | 19588960.19 |
June | 0.420121E+09 | 15561109.65 | 0.404560E+09 | 0.134219E+10 | 14444184.46 |
July | 0.428145E+09 | 6779849.44 | 0.421365E+09 | 0.123748E+10 | 3066927.04 |
August | 0.393049E+09 | 1224943.57 | 0.391824E+09 | 0.103478E+10 | 11160486.79 |
September | 0.338921E+09 | 23798.01 | 0.338897E+09 | 0.786228E+09 | 51904656.19 |
October | 0.303403E+09 | 0.00 | 0.303403E+09 | 0.589182E+09 | 0.319036E+09 |
November | 0.248696E+09 | 0.00 | 0.248696E+09 | 0.304255E+09 | 0.631271E+09 |
December | 0.238154E+09 | 0.00 | 0.238154E+09 | 0.143123E+09 | 0.951535E+09 |
Annual Sum or Average | 0.401064E+10 | 36600368.92 | 0.397404E+10 | 0.850825E+10 | 0.419546E+10 |
Minimum of Months | 0.238154E+09 | 0.00 | 0.238154E+09 | 0.130179E+09 | 3066927.04 |
Maximum of Months | 0.428145E+09 | 15561109.65 | 0.421365E+09 | 0.134219E+10 | 0.975336E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244132E+09 | 0.00 | 0.244132E+09 | 0.130180E+09 | 0.975337E+09 |
February | 0.261483E+09 | 0.00 | 0.261483E+09 | 0.244671E+09 | 0.669320E+09 |
March | 0.348848E+09 | 0.00 | 0.348848E+09 | 0.530722E+09 | 0.421034E+09 |
April | 0.366318E+09 | 1242288.19 | 0.365075E+09 | 0.886008E+09 | 0.127765E+09 |
May | 0.419382E+09 | 11768475.40 | 0.407614E+09 | 0.127944E+10 | 19589191.15 |
June | 0.420122E+09 | 15561223.69 | 0.404561E+09 | 0.134220E+10 | 14444264.73 |
July | 0.428147E+09 | 6779899.12 | 0.421367E+09 | 0.123748E+10 | 3066968.58 |
August | 0.393051E+09 | 1224952.55 | 0.391826E+09 | 0.103478E+10 | 11160603.41 |
September | 0.338923E+09 | 23798.18 | 0.338899E+09 | 0.786230E+09 | 51905108.69 |
October | 0.303405E+09 | 0.00 | 0.303405E+09 | 0.589183E+09 | 0.319037E+09 |
November | 0.248697E+09 | 0.00 | 0.248697E+09 | 0.304256E+09 | 0.631272E+09 |
December | 0.238155E+09 | 0.00 | 0.238155E+09 | 0.143124E+09 | 0.951536E+09 |
Annual Sum or Average | 0.401066E+10 | 36600637.13 | 0.397406E+10 | 0.850827E+10 | 0.419547E+10 |
Minimum of Months | 0.238155E+09 | 0.00 | 0.238155E+09 | 0.130180E+09 | 3066968.58 |
Maximum of Months | 0.428147E+09 | 15561223.69 | 0.421367E+09 | 0.134220E+10 | 0.975337E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244130E+09 | 0.00 | 0.244130E+09 | 0.130179E+09 | 0.975336E+09 |
February | 0.261481E+09 | 0.00 | 0.261481E+09 | 0.244669E+09 | 0.669319E+09 |
March | 0.348846E+09 | 0.00 | 0.348846E+09 | 0.530720E+09 | 0.421033E+09 |
April | 0.366316E+09 | 1242279.08 | 0.365074E+09 | 0.886006E+09 | 0.127765E+09 |
May | 0.419380E+09 | 11768389.16 | 0.407612E+09 | 0.127944E+10 | 19588960.19 |
June | 0.420121E+09 | 15561109.65 | 0.404560E+09 | 0.134219E+10 | 14444184.46 |
July | 0.428145E+09 | 6779849.44 | 0.421365E+09 | 0.123748E+10 | 3066927.04 |
August | 0.393049E+09 | 1224943.57 | 0.391824E+09 | 0.103478E+10 | 11160486.79 |
September | 0.338921E+09 | 23798.01 | 0.338897E+09 | 0.786228E+09 | 51904656.19 |
October | 0.303403E+09 | 0.00 | 0.303403E+09 | 0.589182E+09 | 0.319036E+09 |
November | 0.248696E+09 | 0.00 | 0.248696E+09 | 0.304255E+09 | 0.631271E+09 |
December | 0.238154E+09 | 0.00 | 0.238154E+09 | 0.143123E+09 | 0.951535E+09 |
Annual Sum or Average | 0.401064E+10 | 36600368.92 | 0.397404E+10 | 0.850825E+10 | 0.419546E+10 |
Minimum of Months | 0.238154E+09 | 0.00 | 0.238154E+09 | 0.130179E+09 | 3066927.04 |
Maximum of Months | 0.428145E+09 | 15561109.65 | 0.421365E+09 | 0.134219E+10 | 0.975336E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244121E+09 | 0.00 | 0.244121E+09 | 0.130174E+09 | 0.975297E+09 |
February | 0.261472E+09 | 0.00 | 0.261472E+09 | 0.244660E+09 | 0.669292E+09 |
March | 0.348833E+09 | 0.00 | 0.348833E+09 | 0.530700E+09 | 0.421016E+09 |
April | 0.366302E+09 | 1242233.56 | 0.365060E+09 | 0.885971E+09 | 0.127760E+09 |
May | 0.419364E+09 | 11767957.96 | 0.407596E+09 | 0.127939E+10 | 19588286.14 |
June | 0.420105E+09 | 15560539.49 | 0.404544E+09 | 0.134214E+10 | 14443642.43 |
July | 0.428128E+09 | 6779601.02 | 0.421349E+09 | 0.123743E+10 | 3066824.20 |
August | 0.393034E+09 | 1224898.69 | 0.391809E+09 | 0.103474E+10 | 11160095.28 |
September | 0.338908E+09 | 23797.13 | 0.338884E+09 | 0.786197E+09 | 51902790.44 |
October | 0.303392E+09 | 0.00 | 0.303392E+09 | 0.589159E+09 | 0.319023E+09 |
November | 0.248686E+09 | 0.00 | 0.248686E+09 | 0.304244E+09 | 0.631246E+09 |
December | 0.238145E+09 | 0.00 | 0.238145E+09 | 0.143118E+09 | 0.951497E+09 |
Annual Sum or Average | 0.401049E+10 | 36599027.86 | 0.397389E+10 | 0.850792E+10 | 0.419529E+10 |
Minimum of Months | 0.238145E+09 | 0.00 | 0.238145E+09 | 0.130174E+09 | 3066824.20 |
Maximum of Months | 0.428128E+09 | 15560539.49 | 0.421349E+09 | 0.134214E+10 | 0.975297E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581093E+09 | 0.233243E+09 | 0.347850E+09 | 0.587138E+09 | 0.979722E+09 |
February | 0.637636E+09 | 0.263246E+09 | 0.374390E+09 | 0.825649E+09 | 0.678698E+09 |
March | 0.861189E+09 | 0.355469E+09 | 0.505720E+09 | 0.140533E+10 | 0.429551E+09 |
April | 0.991541E+09 | 0.462307E+09 | 0.529234E+09 | 0.202718E+10 | 0.127813E+09 |
May | 0.100848E+10 | 0.447105E+09 | 0.561375E+09 | 0.237718E+10 | 19805665.93 |
June | 0.794294E+09 | 0.263546E+09 | 0.530748E+09 | 0.208694E+10 | 13560202.90 |
July | 0.689836E+09 | 0.145675E+09 | 0.544161E+09 | 0.178528E+10 | 2046330.05 |
August | 0.621571E+09 | 0.108168E+09 | 0.513403E+09 | 0.151462E+10 | 6530810.10 |
September | 0.642656E+09 | 0.179221E+09 | 0.463435E+09 | 0.135105E+10 | 51188234.25 |
October | 0.726423E+09 | 0.293427E+09 | 0.432996E+09 | 0.134633E+10 | 0.334320E+09 |
November | 0.623303E+09 | 0.267550E+09 | 0.355753E+09 | 0.924229E+09 | 0.641322E+09 |
December | 0.561610E+09 | 0.222513E+09 | 0.339097E+09 | 0.618259E+09 | 0.949605E+09 |
Annual Sum or Average | 0.873963E+10 | 0.324147E+10 | 0.549816E+10 | 0.168492E+11 | 0.423416E+10 |
Minimum of Months | 0.561610E+09 | 0.108168E+09 | 0.339097E+09 | 0.587138E+09 | 2046330.05 |
Maximum of Months | 0.100848E+10 | 0.462307E+09 | 0.561375E+09 | 0.237718E+10 | 0.979722E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581093E+09 | 0.233243E+09 | 0.347850E+09 | 0.587138E+09 | 0.979722E+09 |
February | 0.637636E+09 | 0.263246E+09 | 0.374390E+09 | 0.825649E+09 | 0.678698E+09 |
March | 0.861189E+09 | 0.355469E+09 | 0.505720E+09 | 0.140533E+10 | 0.429551E+09 |
April | 0.991541E+09 | 0.462307E+09 | 0.529234E+09 | 0.202718E+10 | 0.127813E+09 |
May | 0.100848E+10 | 0.447105E+09 | 0.561375E+09 | 0.237718E+10 | 19805665.93 |
June | 0.794294E+09 | 0.263546E+09 | 0.530748E+09 | 0.208694E+10 | 13560202.90 |
July | 0.689836E+09 | 0.145675E+09 | 0.544161E+09 | 0.178528E+10 | 2046330.05 |
August | 0.621571E+09 | 0.108168E+09 | 0.513403E+09 | 0.151462E+10 | 6530810.10 |
September | 0.642656E+09 | 0.179221E+09 | 0.463435E+09 | 0.135105E+10 | 51188234.25 |
October | 0.726423E+09 | 0.293427E+09 | 0.432996E+09 | 0.134633E+10 | 0.334320E+09 |
November | 0.623303E+09 | 0.267550E+09 | 0.355753E+09 | 0.924229E+09 | 0.641322E+09 |
December | 0.561610E+09 | 0.222513E+09 | 0.339097E+09 | 0.618259E+09 | 0.949605E+09 |
Annual Sum or Average | 0.873963E+10 | 0.324147E+10 | 0.549816E+10 | 0.168492E+11 | 0.423416E+10 |
Minimum of Months | 0.561610E+09 | 0.108168E+09 | 0.339097E+09 | 0.587138E+09 | 2046330.05 |
Maximum of Months | 0.100848E+10 | 0.462307E+09 | 0.561375E+09 | 0.237718E+10 | 0.979722E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581082E+09 | 0.233238E+09 | 0.347844E+09 | 0.587127E+09 | 0.979704E+09 |
February | 0.637624E+09 | 0.263241E+09 | 0.374383E+09 | 0.825634E+09 | 0.678685E+09 |
March | 0.861174E+09 | 0.355463E+09 | 0.505711E+09 | 0.140530E+10 | 0.429543E+09 |
April | 0.991523E+09 | 0.462299E+09 | 0.529224E+09 | 0.202714E+10 | 0.127810E+09 |
May | 0.100846E+10 | 0.447097E+09 | 0.561365E+09 | 0.237714E+10 | 19805304.04 |
June | 0.794279E+09 | 0.263541E+09 | 0.530738E+09 | 0.208690E+10 | 13559955.12 |
July | 0.689824E+09 | 0.145672E+09 | 0.544151E+09 | 0.178525E+10 | 2046292.66 |
August | 0.621560E+09 | 0.108166E+09 | 0.513394E+09 | 0.151459E+10 | 6530690.77 |
September | 0.642644E+09 | 0.179218E+09 | 0.463427E+09 | 0.135102E+10 | 51187298.93 |
October | 0.726410E+09 | 0.293422E+09 | 0.432988E+09 | 0.134631E+10 | 0.334314E+09 |
November | 0.623291E+09 | 0.267545E+09 | 0.355746E+09 | 0.924212E+09 | 0.641311E+09 |
December | 0.561600E+09 | 0.222509E+09 | 0.339091E+09 | 0.618248E+09 | 0.949588E+09 |
Annual Sum or Average | 0.873947E+10 | 0.324141E+10 | 0.549806E+10 | 0.168489E+11 | 0.423408E+10 |
Minimum of Months | 0.561600E+09 | 0.108166E+09 | 0.339091E+09 | 0.587127E+09 | 2046292.66 |
Maximum of Months | 0.100846E+10 | 0.462299E+09 | 0.561365E+09 | 0.237714E+10 | 0.979704E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111030E+10 | 0.674644E+09 | 0.435654E+09 | 0.152205E+10 | 0.891470E+09 |
February | 0.953565E+09 | 0.529635E+09 | 0.423930E+09 | 0.142391E+10 | 0.648247E+09 |
March | 0.902678E+09 | 0.398704E+09 | 0.503975E+09 | 0.157781E+10 | 0.433181E+09 |
April | 0.613594E+09 | 0.173173E+09 | 0.440420E+09 | 0.142394E+10 | 0.139887E+09 |
May | 0.455965E+09 | 33753370.59 | 0.422212E+09 | 0.136958E+10 | 19805066.96 |
June | 0.403636E+09 | 6887849.73 | 0.396748E+09 | 0.131054E+10 | 14387328.12 |
July | 0.435064E+09 | 5983889.20 | 0.429080E+09 | 0.125618E+10 | 2853905.27 |
August | 0.461510E+09 | 24647909.05 | 0.436862E+09 | 0.117537E+10 | 11776735.47 |
September | 0.598732E+09 | 0.155401E+09 | 0.443331E+09 | 0.128741E+10 | 58464256.17 |
October | 0.106439E+10 | 0.594348E+09 | 0.470041E+09 | 0.197201E+10 | 0.340683E+09 |
November | 0.128659E+10 | 0.850407E+09 | 0.436184E+09 | 0.208482E+10 | 0.632988E+09 |
December | 0.118652E+10 | 0.743507E+09 | 0.443017E+09 | 0.168584E+10 | 0.887826E+09 |
Annual Sum or Average | 0.947255E+10 | 0.419109E+10 | 0.528145E+10 | 0.180895E+11 | 0.408157E+10 |
Minimum of Months | 0.403636E+09 | 5983889.20 | 0.396748E+09 | 0.117537E+10 | 2853905.27 |
Maximum of Months | 0.128659E+10 | 0.850407E+09 | 0.503975E+09 | 0.208482E+10 | 0.891470E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111029E+10 | 0.674639E+09 | 0.435651E+09 | 0.152204E+10 | 0.891469E+09 |
February | 0.953558E+09 | 0.529631E+09 | 0.423927E+09 | 0.142390E+10 | 0.648246E+09 |
March | 0.902673E+09 | 0.398701E+09 | 0.503972E+09 | 0.157780E+10 | 0.433180E+09 |
April | 0.613590E+09 | 0.173172E+09 | 0.440418E+09 | 0.142393E+10 | 0.139886E+09 |
May | 0.455963E+09 | 33753123.25 | 0.422210E+09 | 0.136958E+10 | 19804837.89 |
June | 0.403635E+09 | 6887799.25 | 0.396747E+09 | 0.131054E+10 | 14387253.31 |
July | 0.435061E+09 | 5983845.35 | 0.429078E+09 | 0.125618E+10 | 2853870.87 |
August | 0.461507E+09 | 24647728.43 | 0.436859E+09 | 0.117537E+10 | 11776613.91 |
September | 0.598729E+09 | 0.155400E+09 | 0.443328E+09 | 0.128741E+10 | 58463778.42 |
October | 0.106438E+10 | 0.594344E+09 | 0.470039E+09 | 0.197199E+10 | 0.340682E+09 |
November | 0.128658E+10 | 0.850401E+09 | 0.436181E+09 | 0.208481E+10 | 0.632987E+09 |
December | 0.118652E+10 | 0.743502E+09 | 0.443014E+09 | 0.168583E+10 | 0.887825E+09 |
Annual Sum or Average | 0.947249E+10 | 0.419106E+10 | 0.528143E+10 | 0.180894E+11 | 0.408156E+10 |
Minimum of Months | 0.403635E+09 | 5983845.35 | 0.396747E+09 | 0.117537E+10 | 2853870.87 |
Maximum of Months | 0.128658E+10 | 0.850401E+09 | 0.503972E+09 | 0.208481E+10 | 0.891469E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111030E+10 | 0.674644E+09 | 0.435654E+09 | 0.152205E+10 | 0.891470E+09 |
February | 0.953565E+09 | 0.529635E+09 | 0.423930E+09 | 0.142391E+10 | 0.648247E+09 |
March | 0.902678E+09 | 0.398704E+09 | 0.503975E+09 | 0.157781E+10 | 0.433181E+09 |
April | 0.613594E+09 | 0.173173E+09 | 0.440420E+09 | 0.142394E+10 | 0.139887E+09 |
May | 0.455965E+09 | 33753370.59 | 0.422212E+09 | 0.136958E+10 | 19805066.96 |
June | 0.403636E+09 | 6887849.73 | 0.396748E+09 | 0.131054E+10 | 14387328.12 |
July | 0.435064E+09 | 5983889.20 | 0.429080E+09 | 0.125618E+10 | 2853905.27 |
August | 0.461510E+09 | 24647909.05 | 0.436862E+09 | 0.117537E+10 | 11776735.47 |
September | 0.598732E+09 | 0.155401E+09 | 0.443331E+09 | 0.128741E+10 | 58464256.17 |
October | 0.106439E+10 | 0.594348E+09 | 0.470041E+09 | 0.197201E+10 | 0.340683E+09 |
November | 0.128659E+10 | 0.850407E+09 | 0.436184E+09 | 0.208482E+10 | 0.632988E+09 |
December | 0.118652E+10 | 0.743507E+09 | 0.443017E+09 | 0.168584E+10 | 0.887826E+09 |
Annual Sum or Average | 0.947255E+10 | 0.419109E+10 | 0.528145E+10 | 0.180895E+11 | 0.408157E+10 |
Minimum of Months | 0.403636E+09 | 5983889.20 | 0.396748E+09 | 0.117537E+10 | 2853905.27 |
Maximum of Months | 0.128659E+10 | 0.850407E+09 | 0.503975E+09 | 0.208482E+10 | 0.891470E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111029E+10 | 0.674639E+09 | 0.435651E+09 | 0.152204E+10 | 0.891469E+09 |
February | 0.953558E+09 | 0.529631E+09 | 0.423927E+09 | 0.142390E+10 | 0.648246E+09 |
March | 0.902673E+09 | 0.398701E+09 | 0.503972E+09 | 0.157780E+10 | 0.433180E+09 |
April | 0.613590E+09 | 0.173172E+09 | 0.440418E+09 | 0.142393E+10 | 0.139886E+09 |
May | 0.455963E+09 | 33753123.25 | 0.422210E+09 | 0.136958E+10 | 19804837.89 |
June | 0.403635E+09 | 6887799.25 | 0.396747E+09 | 0.131054E+10 | 14387253.31 |
July | 0.435061E+09 | 5983845.35 | 0.429078E+09 | 0.125618E+10 | 2853870.87 |
August | 0.461507E+09 | 24647728.43 | 0.436859E+09 | 0.117537E+10 | 11776613.91 |
September | 0.598729E+09 | 0.155400E+09 | 0.443328E+09 | 0.128741E+10 | 58463778.42 |
October | 0.106438E+10 | 0.594344E+09 | 0.470039E+09 | 0.197199E+10 | 0.340682E+09 |
November | 0.128658E+10 | 0.850401E+09 | 0.436181E+09 | 0.208481E+10 | 0.632987E+09 |
December | 0.118652E+10 | 0.743502E+09 | 0.443014E+09 | 0.168583E+10 | 0.887825E+09 |
Annual Sum or Average | 0.947249E+10 | 0.419106E+10 | 0.528143E+10 | 0.180894E+11 | 0.408156E+10 |
Minimum of Months | 0.403635E+09 | 5983845.35 | 0.396747E+09 | 0.117537E+10 | 2853870.87 |
Maximum of Months | 0.128658E+10 | 0.850401E+09 | 0.503972E+09 | 0.208481E+10 | 0.891469E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111025E+10 | 0.674614E+09 | 0.435635E+09 | 0.152198E+10 | 0.891433E+09 |
February | 0.953523E+09 | 0.529612E+09 | 0.423911E+09 | 0.142385E+10 | 0.648220E+09 |
March | 0.902639E+09 | 0.398686E+09 | 0.503953E+09 | 0.157774E+10 | 0.433163E+09 |
April | 0.613567E+09 | 0.173166E+09 | 0.440401E+09 | 0.142388E+10 | 0.139881E+09 |
May | 0.455946E+09 | 33751886.52 | 0.422194E+09 | 0.136952E+10 | 19804154.20 |
June | 0.403619E+09 | 6887546.88 | 0.396732E+09 | 0.131049E+10 | 14386710.84 |
July | 0.435045E+09 | 5983626.10 | 0.429061E+09 | 0.125613E+10 | 2853773.05 |
August | 0.461490E+09 | 24646825.33 | 0.436843E+09 | 0.117532E+10 | 11776200.04 |
September | 0.598706E+09 | 0.155394E+09 | 0.443312E+09 | 0.128736E+10 | 58461660.94 |
October | 0.106434E+10 | 0.594322E+09 | 0.470021E+09 | 0.197192E+10 | 0.340669E+09 |
November | 0.128653E+10 | 0.850370E+09 | 0.436165E+09 | 0.208473E+10 | 0.632962E+09 |
December | 0.118647E+10 | 0.743475E+09 | 0.442998E+09 | 0.168577E+10 | 0.887789E+09 |
Annual Sum or Average | 0.947214E+10 | 0.419091E+10 | 0.528123E+10 | 0.180887E+11 | 0.408140E+10 |
Minimum of Months | 0.403619E+09 | 5983626.10 | 0.396732E+09 | 0.117532E+10 | 2853773.05 |
Maximum of Months | 0.128653E+10 | 0.850370E+09 | 0.503953E+09 | 0.208473E+10 | 0.891433E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.568506E+09 | 0.221241E+09 | 0.347265E+09 | 0.630866E+09 | 0.113022E+10 |
February | 0.587189E+09 | 0.216395E+09 | 0.370794E+09 | 0.766132E+09 | 0.822206E+09 |
March | 0.843016E+09 | 0.336983E+09 | 0.506033E+09 | 0.135805E+10 | 0.559282E+09 |
April | 0.991624E+09 | 0.465034E+09 | 0.526590E+09 | 0.195369E+10 | 0.220459E+09 |
May | 0.970274E+09 | 0.411570E+09 | 0.558703E+09 | 0.226921E+10 | 35807931.47 |
June | 0.881948E+09 | 0.342572E+09 | 0.539376E+09 | 0.216380E+10 | 27919116.69 |
July | 0.676266E+09 | 0.131534E+09 | 0.544732E+09 | 0.164396E+10 | 11494086.85 |
August | 0.621079E+09 | 0.110385E+09 | 0.510694E+09 | 0.137454E+10 | 45479557.40 |
September | 0.660705E+09 | 0.193964E+09 | 0.466741E+09 | 0.135033E+10 | 86826852.37 |
October | 0.710616E+09 | 0.282966E+09 | 0.427650E+09 | 0.130507E+10 | 0.421197E+09 |
November | 0.622131E+09 | 0.265149E+09 | 0.356983E+09 | 0.934957E+09 | 0.801144E+09 |
December | 0.550107E+09 | 0.209768E+09 | 0.340339E+09 | 0.604100E+09 | 0.118155E+10 |
Annual Sum or Average | 0.868346E+10 | 0.318756E+10 | 0.549590E+10 | 0.163547E+11 | 0.534359E+10 |
Minimum of Months | 0.550107E+09 | 0.110385E+09 | 0.340339E+09 | 0.604100E+09 | 11494086.85 |
Maximum of Months | 0.991624E+09 | 0.465034E+09 | 0.558703E+09 | 0.226921E+10 | 0.118155E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.568506E+09 | 0.221241E+09 | 0.347265E+09 | 0.630866E+09 | 0.113022E+10 |
February | 0.587189E+09 | 0.216395E+09 | 0.370794E+09 | 0.766132E+09 | 0.822206E+09 |
March | 0.843016E+09 | 0.336983E+09 | 0.506033E+09 | 0.135805E+10 | 0.559282E+09 |
April | 0.991624E+09 | 0.465034E+09 | 0.526590E+09 | 0.195369E+10 | 0.220459E+09 |
May | 0.970274E+09 | 0.411570E+09 | 0.558703E+09 | 0.226921E+10 | 35807931.47 |
June | 0.881948E+09 | 0.342572E+09 | 0.539376E+09 | 0.216380E+10 | 27919116.69 |
July | 0.676266E+09 | 0.131534E+09 | 0.544732E+09 | 0.164396E+10 | 11494086.85 |
August | 0.621079E+09 | 0.110385E+09 | 0.510694E+09 | 0.137454E+10 | 45479557.40 |
September | 0.660705E+09 | 0.193964E+09 | 0.466741E+09 | 0.135033E+10 | 86826852.37 |
October | 0.710616E+09 | 0.282966E+09 | 0.427650E+09 | 0.130507E+10 | 0.421197E+09 |
November | 0.622131E+09 | 0.265149E+09 | 0.356983E+09 | 0.934957E+09 | 0.801144E+09 |
December | 0.550107E+09 | 0.209768E+09 | 0.340339E+09 | 0.604100E+09 | 0.118155E+10 |
Annual Sum or Average | 0.868346E+10 | 0.318756E+10 | 0.549590E+10 | 0.163547E+11 | 0.534359E+10 |
Minimum of Months | 0.550107E+09 | 0.110385E+09 | 0.340339E+09 | 0.604100E+09 | 11494086.85 |
Maximum of Months | 0.991624E+09 | 0.465034E+09 | 0.558703E+09 | 0.226921E+10 | 0.118155E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.568496E+09 | 0.221237E+09 | 0.347259E+09 | 0.630855E+09 | 0.113020E+10 |
February | 0.587178E+09 | 0.216391E+09 | 0.370787E+09 | 0.766118E+09 | 0.822191E+09 |
March | 0.843001E+09 | 0.336977E+09 | 0.506024E+09 | 0.135803E+10 | 0.559272E+09 |
April | 0.991605E+09 | 0.465025E+09 | 0.526580E+09 | 0.195365E+10 | 0.220455E+09 |
May | 0.970256E+09 | 0.411563E+09 | 0.558693E+09 | 0.226917E+10 | 35807277.18 |
June | 0.881932E+09 | 0.342566E+09 | 0.539366E+09 | 0.216376E+10 | 27918606.54 |
July | 0.676253E+09 | 0.131532E+09 | 0.544722E+09 | 0.164393E+10 | 11493876.82 |
August | 0.621068E+09 | 0.110383E+09 | 0.510685E+09 | 0.137451E+10 | 45478726.39 |
September | 0.660693E+09 | 0.193961E+09 | 0.466732E+09 | 0.135031E+10 | 86825265.85 |
October | 0.710603E+09 | 0.282961E+09 | 0.427642E+09 | 0.130504E+10 | 0.421190E+09 |
November | 0.622120E+09 | 0.265144E+09 | 0.356976E+09 | 0.934940E+09 | 0.801129E+09 |
December | 0.550097E+09 | 0.209764E+09 | 0.340333E+09 | 0.604089E+09 | 0.118153E+10 |
Annual Sum or Average | 0.868330E+10 | 0.318750E+10 | 0.549580E+10 | 0.163544E+11 | 0.534349E+10 |
Minimum of Months | 0.550097E+09 | 0.110383E+09 | 0.340333E+09 | 0.604089E+09 | 11493876.82 |
Maximum of Months | 0.991605E+09 | 0.465025E+09 | 0.558693E+09 | 0.226917E+10 | 0.118153E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122067E+10 | 0.00 | 0.122067E+10 | 0.787704E+09 | 0.438594E+10 |
February | 0.130743E+10 | 0.00 | 0.130743E+10 | 0.133441E+10 | 0.304711E+10 |
March | 0.174425E+10 | 0.00 | 0.174425E+10 | 0.272462E+10 | 0.200599E+10 |
April | 0.183160E+10 | 6211571.55 | 0.182539E+10 | 0.452714E+10 | 0.652407E+09 |
May | 0.209692E+10 | 58843614.39 | 0.203808E+10 | 0.646201E+10 | 0.102538E+09 |
June | 0.210063E+10 | 77807754.61 | 0.202282E+10 | 0.676589E+10 | 81186150.52 |
July | 0.214076E+10 | 33900208.49 | 0.210686E+10 | 0.622808E+10 | 22587717.29 |
August | 0.196528E+10 | 6124891.54 | 0.195915E+10 | 0.525628E+10 | 74296566.66 |
September | 0.169463E+10 | 118993.41 | 0.169451E+10 | 0.396211E+10 | 0.276058E+09 |
October | 0.151703E+10 | 0.00 | 0.151703E+10 | 0.301302E+10 | 0.154814E+10 |
November | 0.124349E+10 | 0.00 | 0.124349E+10 | 0.163522E+10 | 0.290451E+10 |
December | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.892305E+09 | 0.420274E+10 |
Annual Sum or Average | 0.200535E+11 | 0.183007E+09 | 0.198705E+11 | 0.435888E+11 | 0.193035E+11 |
Minimum of Months | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.787704E+09 | 22587717.29 |
Maximum of Months | 0.214076E+10 | 77807754.61 | 0.210686E+10 | 0.676589E+10 | 0.438594E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174326E+10 | 0.699721E+09 | 0.104354E+10 | 0.184848E+10 | 0.271680E+10 |
February | 0.191289E+10 | 0.789730E+09 | 0.112316E+10 | 0.250699E+10 | 0.193262E+10 |
March | 0.258354E+10 | 0.106640E+10 | 0.151715E+10 | 0.419958E+10 | 0.130952E+10 |
April | 0.297459E+10 | 0.138691E+10 | 0.158769E+10 | 0.604063E+10 | 0.455427E+09 |
May | 0.302541E+10 | 0.134130E+10 | 0.168411E+10 | 0.710865E+10 | 69153025.91 |
June | 0.238286E+10 | 0.790630E+09 | 0.159223E+10 | 0.622568E+10 | 53855834.36 |
July | 0.206949E+10 | 0.437021E+09 | 0.163247E+10 | 0.529251E+10 | 12924606.31 |
August | 0.186469E+10 | 0.324501E+09 | 0.154019E+10 | 0.447640E+10 | 49289897.03 |
September | 0.192795E+10 | 0.537657E+09 | 0.139029E+10 | 0.403269E+10 | 0.187788E+09 |
October | 0.217925E+10 | 0.880272E+09 | 0.129897E+10 | 0.402938E+10 | 0.103206E+10 |
November | 0.186989E+10 | 0.802641E+09 | 0.106725E+10 | 0.279714E+10 | 0.186442E+10 |
December | 0.168481E+10 | 0.667533E+09 | 0.101728E+10 | 0.194163E+10 | 0.265692E+10 |
Annual Sum or Average | 0.262186E+11 | 0.972431E+10 | 0.164943E+11 | 0.504998E+11 | 0.123408E+11 |
Minimum of Months | 0.168481E+10 | 0.324501E+09 | 0.101728E+10 | 0.184848E+10 | 12924606.31 |
Maximum of Months | 0.302541E+10 | 0.138691E+10 | 0.168411E+10 | 0.710865E+10 | 0.271680E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555159E+10 | 0.337329E+10 | 0.217830E+10 | 0.756709E+10 | 0.439105E+10 |
February | 0.476791E+10 | 0.264823E+10 | 0.211968E+10 | 0.708161E+10 | 0.317891E+10 |
March | 0.451346E+10 | 0.199356E+10 | 0.251990E+10 | 0.786302E+10 | 0.217015E+10 |
April | 0.306800E+10 | 0.865885E+09 | 0.220212E+10 | 0.714833E+10 | 0.737085E+09 |
May | 0.227984E+10 | 0.168770E+09 | 0.211107E+10 | 0.690717E+10 | 0.102794E+09 |
June | 0.201820E+10 | 34439972.86 | 0.198376E+10 | 0.661126E+10 | 80049606.88 |
July | 0.217534E+10 | 29920075.17 | 0.214542E+10 | 0.632658E+10 | 20011221.71 |
August | 0.230758E+10 | 0.123242E+09 | 0.218434E+10 | 0.593705E+10 | 77714619.05 |
September | 0.299371E+10 | 0.777023E+09 | 0.221668E+10 | 0.642529E+10 | 0.323219E+09 |
October | 0.532204E+10 | 0.297180E+10 | 0.235023E+10 | 0.982414E+10 | 0.174246E+10 |
November | 0.643307E+10 | 0.425213E+10 | 0.218095E+10 | 0.103835E+11 | 0.314311E+10 |
December | 0.593273E+10 | 0.371762E+10 | 0.221512E+10 | 0.842242E+10 | 0.431390E+10 |
Annual Sum or Average | 0.473635E+11 | 0.209559E+11 | 0.264076E+11 | 0.904975E+11 | 0.202804E+11 |
Minimum of Months | 0.201820E+10 | 29920075.17 | 0.198376E+10 | 0.593705E+10 | 20011221.71 |
Maximum of Months | 0.643307E+10 | 0.425213E+10 | 0.251990E+10 | 0.103835E+11 | 0.439105E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170550E+10 | 0.663716E+09 | 0.104178E+10 | 0.200024E+10 | 0.300901E+10 |
February | 0.176155E+10 | 0.649178E+09 | 0.111237E+10 | 0.240556E+10 | 0.213904E+10 |
March | 0.252902E+10 | 0.101094E+10 | 0.151808E+10 | 0.417263E+10 | 0.147118E+10 |
April | 0.297484E+10 | 0.139509E+10 | 0.157975E+10 | 0.602055E+10 | 0.534943E+09 |
May | 0.291079E+10 | 0.123470E+10 | 0.167609E+10 | 0.688415E+10 | 94580319.99 |
June | 0.264582E+10 | 0.102771E+10 | 0.161811E+10 | 0.662471E+10 | 70298217.95 |
July | 0.202878E+10 | 0.394598E+09 | 0.163418E+10 | 0.512577E+10 | 20898399.94 |
August | 0.186322E+10 | 0.331151E+09 | 0.153207E+10 | 0.440919E+10 | 64540666.80 |
September | 0.198210E+10 | 0.581887E+09 | 0.140021E+10 | 0.410613E+10 | 0.227363E+09 |
October | 0.213182E+10 | 0.848889E+09 | 0.128294E+10 | 0.399128E+10 | 0.113794E+10 |
November | 0.186638E+10 | 0.795438E+09 | 0.107094E+10 | 0.293233E+10 | 0.206683E+10 |
December | 0.165030E+10 | 0.629299E+09 | 0.102101E+10 | 0.201149E+10 | 0.290401E+10 |
Annual Sum or Average | 0.260501E+11 | 0.956259E+10 | 0.164875E+11 | 0.506840E+11 | 0.137406E+11 |
Minimum of Months | 0.165030E+10 | 0.331151E+09 | 0.102101E+10 | 0.200024E+10 | 20898399.94 |
Maximum of Months | 0.297484E+10 | 0.139509E+10 | 0.167609E+10 | 0.688415E+10 | 0.300901E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122067E+10 | 0.00 | 0.122067E+10 | 0.939590E+09 | 0.384313E+10 |
February | 0.130743E+10 | 0.00 | 0.130743E+10 | 0.143274E+10 | 0.277664E+10 |
March | 0.174425E+10 | 0.00 | 0.174425E+10 | 0.274269E+10 | 0.191360E+10 |
April | 0.183160E+10 | 6211571.55 | 0.182539E+10 | 0.446458E+10 | 0.644289E+09 |
May | 0.209692E+10 | 58843614.39 | 0.203808E+10 | 0.634831E+10 | 0.109265E+09 |
June | 0.210063E+10 | 77807754.61 | 0.202282E+10 | 0.665320E+10 | 87572832.08 |
July | 0.214076E+10 | 33900208.49 | 0.210686E+10 | 0.610829E+10 | 23400604.58 |
August | 0.196528E+10 | 6124891.54 | 0.195915E+10 | 0.516014E+10 | 81300455.28 |
September | 0.169463E+10 | 118993.41 | 0.169451E+10 | 0.391401E+10 | 0.277935E+09 |
October | 0.151703E+10 | 0.00 | 0.151703E+10 | 0.300516E+10 | 0.149621E+10 |
November | 0.124349E+10 | 0.00 | 0.124349E+10 | 0.171599E+10 | 0.269005E+10 |
December | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.103879E+10 | 0.375264E+10 |
Annual Sum or Average | 0.200535E+11 | 0.183007E+09 | 0.198705E+11 | 0.435235E+11 | 0.176960E+11 |
Minimum of Months | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.939590E+09 | 23400604.58 |
Maximum of Months | 0.214076E+10 | 77807754.61 | 0.210686E+10 | 0.665320E+10 | 0.384313E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174326E+10 | 0.699721E+09 | 0.104354E+10 | 0.198851E+10 | 0.241726E+10 |
February | 0.191289E+10 | 0.789730E+09 | 0.112316E+10 | 0.256989E+10 | 0.180315E+10 |
March | 0.258354E+10 | 0.106640E+10 | 0.151715E+10 | 0.419343E+10 | 0.127986E+10 |
April | 0.297459E+10 | 0.138691E+10 | 0.158769E+10 | 0.598521E+10 | 0.460568E+09 |
May | 0.302541E+10 | 0.134130E+10 | 0.168411E+10 | 0.701654E+10 | 76503274.79 |
June | 0.238286E+10 | 0.790630E+09 | 0.159223E+10 | 0.613702E+10 | 59323828.07 |
July | 0.206949E+10 | 0.437021E+09 | 0.163247E+10 | 0.520037E+10 | 13351592.25 |
August | 0.186469E+10 | 0.324501E+09 | 0.154019E+10 | 0.440409E+10 | 54822785.64 |
September | 0.192795E+10 | 0.537657E+09 | 0.139029E+10 | 0.399146E+10 | 0.193869E+09 |
October | 0.217925E+10 | 0.880272E+09 | 0.129897E+10 | 0.401157E+10 | 0.101937E+10 |
November | 0.186989E+10 | 0.802641E+09 | 0.106725E+10 | 0.283821E+10 | 0.177154E+10 |
December | 0.168481E+10 | 0.667533E+09 | 0.101728E+10 | 0.206010E+10 | 0.242134E+10 |
Annual Sum or Average | 0.262186E+11 | 0.972431E+10 | 0.164943E+11 | 0.503964E+11 | 0.115710E+11 |
Minimum of Months | 0.168481E+10 | 0.324501E+09 | 0.101728E+10 | 0.198851E+10 | 13351592.25 |
Maximum of Months | 0.302541E+10 | 0.138691E+10 | 0.168411E+10 | 0.701654E+10 | 0.242134E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555159E+10 | 0.337329E+10 | 0.217830E+10 | 0.773319E+10 | 0.394431E+10 |
February | 0.476791E+10 | 0.264823E+10 | 0.211968E+10 | 0.714514E+10 | 0.297393E+10 |
March | 0.451346E+10 | 0.199356E+10 | 0.251990E+10 | 0.784680E+10 | 0.211291E+10 |
April | 0.306800E+10 | 0.865885E+09 | 0.220212E+10 | 0.707598E+10 | 0.738200E+09 |
May | 0.227984E+10 | 0.168770E+09 | 0.211107E+10 | 0.679117E+10 | 0.109889E+09 |
June | 0.201820E+10 | 34439972.86 | 0.198376E+10 | 0.649688E+10 | 86626236.95 |
July | 0.217534E+10 | 29920075.17 | 0.214542E+10 | 0.620523E+10 | 20431277.23 |
August | 0.230758E+10 | 0.123242E+09 | 0.218434E+10 | 0.583991E+10 | 85365602.64 |
September | 0.299371E+10 | 0.777023E+09 | 0.221668E+10 | 0.636781E+10 | 0.330972E+09 |
October | 0.532204E+10 | 0.297180E+10 | 0.235023E+10 | 0.978961E+10 | 0.172370E+10 |
November | 0.643307E+10 | 0.425213E+10 | 0.218095E+10 | 0.104078E+11 | 0.301170E+10 |
December | 0.593273E+10 | 0.371762E+10 | 0.221512E+10 | 0.855999E+10 | 0.397510E+10 |
Annual Sum or Average | 0.473635E+11 | 0.209559E+11 | 0.264076E+11 | 0.902595E+11 | 0.191131E+11 |
Minimum of Months | 0.201820E+10 | 29920075.17 | 0.198376E+10 | 0.583991E+10 | 20431277.23 |
Maximum of Months | 0.643307E+10 | 0.425213E+10 | 0.251990E+10 | 0.104078E+11 | 0.397510E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170550E+10 | 0.663716E+09 | 0.104178E+10 | 0.207950E+10 | 0.271648E+10 |
February | 0.176155E+10 | 0.649178E+09 | 0.111237E+10 | 0.244756E+10 | 0.199735E+10 |
March | 0.252902E+10 | 0.101094E+10 | 0.151808E+10 | 0.416951E+10 | 0.142688E+10 |
April | 0.297484E+10 | 0.139509E+10 | 0.157975E+10 | 0.597533E+10 | 0.532618E+09 |
May | 0.291079E+10 | 0.123470E+10 | 0.167609E+10 | 0.681412E+10 | 98710896.68 |
June | 0.264582E+10 | 0.102771E+10 | 0.161811E+10 | 0.655366E+10 | 73479914.97 |
July | 0.202878E+10 | 0.394598E+09 | 0.163418E+10 | 0.505677E+10 | 20955766.78 |
August | 0.186322E+10 | 0.331151E+09 | 0.153207E+10 | 0.435517E+10 | 68284712.84 |
September | 0.198210E+10 | 0.581887E+09 | 0.140021E+10 | 0.407490E+10 | 0.227787E+09 |
October | 0.213182E+10 | 0.848889E+09 | 0.128294E+10 | 0.397941E+10 | 0.111295E+10 |
November | 0.186638E+10 | 0.795438E+09 | 0.107094E+10 | 0.296303E+10 | 0.195916E+10 |
December | 0.165030E+10 | 0.629299E+09 | 0.102101E+10 | 0.208632E+10 | 0.266446E+10 |
Annual Sum or Average | 0.260501E+11 | 0.956259E+10 | 0.164875E+11 | 0.505553E+11 | 0.128991E+11 |
Minimum of Months | 0.165030E+10 | 0.331151E+09 | 0.102101E+10 | 0.207950E+10 | 20955766.78 |
Maximum of Months | 0.297484E+10 | 0.139509E+10 | 0.167609E+10 | 0.681412E+10 | 0.271648E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 243.02 | 1820.73 | 455.74 | 0.00 | 455.74 | 0.00 | 0.00 |
February | 505.68 | 1383.34 | 540.43 | 0.00 | 540.43 | 0.00 | 0.00 |
March | 990.74 | 785.97 | 651.22 | 0.00 | 651.22 | 0.00 | 0.00 |
April | 1709.11 | 246.46 | 706.63 | 2.40 | 704.23 | 0.00 | 0.00 |
May | 2388.42 | 36.57 | 782.89 | 21.97 | 760.92 | 0.00 | 0.00 |
June | 2589.09 | 27.86 | 810.41 | 30.02 | 780.40 | 0.00 | 0.00 |
July | 2310.10 | 5.73 | 799.25 | 12.66 | 786.60 | 0.00 | 0.00 |
August | 1931.69 | 20.83 | 733.74 | 2.29 | 731.45 | 0.00 | 0.00 |
September | 1516.63 | 100.12 | 653.78 | 0.05 | 653.73 | 0.00 | 0.00 |
October | 1099.87 | 595.57 | 566.39 | 0.00 | 566.39 | 0.00 | 0.00 |
November | 586.91 | 1217.72 | 479.74 | 0.00 | 479.74 | 0.00 | 0.00 |
December | 267.18 | 1776.30 | 444.58 | 0.00 | 444.58 | 0.00 | 0.00 |
Annual Sum or Average | 1348.97 | 665.18 | 635.88 | 5.80 | 630.08 | 0.00 | 0.00 |
Minimum of Months | 243.02 | 5.73 | 444.58 | 0.00 | 444.58 | 0.00 | 0.00 |
Maximum of Months | 2589.09 | 1820.73 | 810.41 | 30.02 | 786.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 657.63 | 1097.35 | 650.86 | 261.25 | 389.61 | 0.00 | 0.00 |
February | 1023.86 | 841.63 | 790.71 | 326.44 | 464.27 | 0.00 | 0.00 |
March | 1574.06 | 481.13 | 964.59 | 398.15 | 566.44 | 0.00 | 0.00 |
April | 2346.26 | 147.93 | 1147.61 | 535.07 | 612.54 | 0.00 | 0.00 |
May | 2662.60 | 22.18 | 1129.56 | 500.79 | 628.78 | 0.00 | 0.00 |
June | 2415.43 | 15.69 | 919.32 | 305.03 | 614.29 | 0.00 | 0.00 |
July | 1999.63 | 2.29 | 772.66 | 163.17 | 609.50 | 0.00 | 0.00 |
August | 1696.47 | 7.31 | 696.20 | 121.16 | 575.04 | 0.00 | 0.00 |
September | 1563.70 | 59.25 | 743.81 | 207.43 | 536.38 | 0.00 | 0.00 |
October | 1507.98 | 374.46 | 813.64 | 328.66 | 484.98 | 0.00 | 0.00 |
November | 1069.70 | 742.27 | 721.41 | 309.66 | 411.75 | 0.00 | 0.00 |
December | 692.49 | 1063.62 | 629.04 | 249.23 | 379.81 | 0.00 | 0.00 |
Annual Sum or Average | 1602.84 | 402.79 | 831.39 | 308.36 | 523.03 | 0.00 | 0.00 |
Minimum of Months | 657.63 | 2.29 | 629.04 | 121.16 | 379.81 | 0.00 | 0.00 |
Maximum of Months | 2662.60 | 1097.35 | 1147.61 | 535.07 | 628.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2841.31 | 1664.17 | 2072.66 | 1259.40 | 813.26 | 0.00 | 0.00 |
February | 2942.91 | 1339.78 | 1970.80 | 1094.64 | 876.17 | 0.00 | 0.00 |
March | 2945.41 | 808.65 | 1685.09 | 744.29 | 940.80 | 0.00 | 0.00 |
April | 2746.77 | 269.84 | 1183.62 | 334.05 | 849.57 | 0.00 | 0.00 |
May | 2556.69 | 36.97 | 851.18 | 63.01 | 788.17 | 0.00 | 0.00 |
June | 2528.03 | 27.75 | 778.61 | 13.29 | 765.32 | 0.00 | 0.00 |
July | 2345.00 | 5.33 | 812.16 | 11.17 | 800.99 | 0.00 | 0.00 |
August | 2194.14 | 21.98 | 861.53 | 46.01 | 815.52 | 0.00 | 0.00 |
September | 2483.41 | 112.78 | 1154.95 | 299.77 | 855.18 | 0.00 | 0.00 |
October | 3681.27 | 635.98 | 1986.97 | 1109.51 | 877.46 | 0.00 | 0.00 |
November | 4021.60 | 1221.03 | 2481.82 | 1640.43 | 841.39 | 0.00 | 0.00 |
December | 3147.07 | 1657.37 | 2214.96 | 1387.95 | 827.01 | 0.00 | 0.00 |
Annual Sum or Average | 2868.04 | 647.12 | 1501.85 | 664.49 | 837.36 | 0.00 | 0.00 |
Minimum of Months | 2194.14 | 5.33 | 778.61 | 11.17 | 765.32 | 0.00 | 0.00 |
Maximum of Months | 4021.60 | 1664.17 | 2481.82 | 1640.43 | 940.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 706.61 | 1265.92 | 636.76 | 247.80 | 388.96 | 0.00 | 0.00 |
February | 950.06 | 1019.59 | 728.16 | 268.35 | 459.81 | 0.00 | 0.00 |
March | 1521.10 | 626.43 | 944.23 | 377.44 | 566.79 | 0.00 | 0.00 |
April | 2261.20 | 255.16 | 1147.71 | 538.23 | 609.48 | 0.00 | 0.00 |
May | 2541.67 | 40.11 | 1086.77 | 460.99 | 625.78 | 0.00 | 0.00 |
June | 2504.38 | 32.31 | 1020.77 | 396.49 | 624.27 | 0.00 | 0.00 |
July | 1841.35 | 12.87 | 757.46 | 147.33 | 610.13 | 0.00 | 0.00 |
August | 1539.57 | 50.94 | 695.65 | 123.64 | 572.01 | 0.00 | 0.00 |
September | 1562.88 | 100.49 | 764.70 | 224.49 | 540.21 | 0.00 | 0.00 |
October | 1461.76 | 471.77 | 795.94 | 316.94 | 479.00 | 0.00 | 0.00 |
November | 1082.12 | 927.24 | 720.06 | 306.88 | 413.17 | 0.00 | 0.00 |
December | 676.63 | 1323.41 | 616.16 | 234.95 | 381.20 | 0.00 | 0.00 |
Annual Sum or Average | 1555.80 | 508.33 | 826.05 | 303.23 | 522.82 | 0.00 | 0.00 |
Minimum of Months | 676.63 | 12.87 | 616.16 | 123.64 | 381.20 | 0.00 | 0.00 |
Maximum of Months | 2541.67 | 1323.41 | 1147.71 | 538.23 | 625.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 294.09 | 1637.52 | 455.75 | 0.00 | 455.75 | 0.00 | 0.00 |
February | 551.59 | 1259.55 | 540.44 | 0.00 | 540.44 | 0.00 | 0.00 |
March | 1017.26 | 748.95 | 651.23 | 0.00 | 651.23 | 0.00 | 0.00 |
April | 1746.58 | 251.70 | 706.64 | 2.40 | 704.24 | 0.00 | 0.00 |
May | 2412.64 | 38.28 | 782.90 | 21.97 | 760.93 | 0.00 | 0.00 |
June | 2610.30 | 31.32 | 810.43 | 30.02 | 780.41 | 0.00 | 0.00 |
July | 2325.30 | 8.43 | 799.27 | 12.66 | 786.61 | 0.00 | 0.00 |
August | 1962.47 | 27.74 | 733.75 | 2.29 | 731.46 | 0.00 | 0.00 |
September | 1528.59 | 106.50 | 653.79 | 0.05 | 653.75 | 0.00 | 0.00 |
October | 1124.93 | 578.01 | 566.40 | 0.00 | 566.40 | 0.00 | 0.00 |
November | 630.87 | 1120.57 | 479.74 | 0.00 | 479.74 | 0.00 | 0.00 |
December | 333.15 | 1569.12 | 444.59 | 0.00 | 444.59 | 0.00 | 0.00 |
Annual Sum or Average | 1382.19 | 612.11 | 635.89 | 5.80 | 630.09 | 0.00 | 0.00 |
Minimum of Months | 294.09 | 8.43 | 444.59 | 0.00 | 444.59 | 0.00 | 0.00 |
Maximum of Months | 2610.30 | 1637.52 | 810.43 | 30.02 | 786.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 690.14 | 1014.34 | 650.86 | 261.25 | 389.61 | 0.00 | 0.00 |
February | 1036.29 | 798.87 | 790.71 | 326.44 | 464.27 | 0.00 | 0.00 |
March | 1567.94 | 488.92 | 964.58 | 398.15 | 566.44 | 0.00 | 0.00 |
April | 2330.49 | 175.70 | 1147.61 | 535.07 | 612.53 | 0.00 | 0.00 |
May | 2654.06 | 25.82 | 1129.56 | 500.78 | 628.77 | 0.00 | 0.00 |
June | 2401.88 | 20.78 | 919.31 | 305.03 | 614.29 | 0.00 | 0.00 |
July | 1976.00 | 4.83 | 772.66 | 163.16 | 609.49 | 0.00 | 0.00 |
August | 1671.30 | 18.40 | 696.20 | 121.15 | 575.04 | 0.00 | 0.00 |
September | 1555.82 | 72.45 | 743.81 | 207.43 | 536.38 | 0.00 | 0.00 |
October | 1504.40 | 385.33 | 813.64 | 328.66 | 484.98 | 0.00 | 0.00 |
November | 1079.14 | 719.30 | 721.41 | 309.66 | 411.75 | 0.00 | 0.00 |
December | 724.92 | 991.98 | 629.04 | 249.23 | 379.81 | 0.00 | 0.00 |
Annual Sum or Average | 1601.34 | 391.32 | 831.39 | 308.36 | 523.03 | 0.00 | 0.00 |
Minimum of Months | 690.14 | 4.83 | 629.04 | 121.15 | 379.81 | 0.00 | 0.00 |
Maximum of Months | 2654.06 | 1014.34 | 1147.61 | 535.07 | 628.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2825.23 | 1639.43 | 2072.73 | 1259.44 | 813.28 | 0.00 | 0.00 |
February | 2927.25 | 1314.03 | 1970.86 | 1094.67 | 876.19 | 0.00 | 0.00 |
March | 2935.71 | 810.24 | 1685.13 | 744.31 | 940.82 | 0.00 | 0.00 |
April | 2757.84 | 284.37 | 1183.64 | 334.06 | 849.58 | 0.00 | 0.00 |
May | 2578.84 | 38.38 | 851.20 | 63.01 | 788.18 | 0.00 | 0.00 |
June | 2550.64 | 30.88 | 778.63 | 13.29 | 765.34 | 0.00 | 0.00 |
July | 2362.08 | 7.47 | 812.18 | 11.17 | 801.01 | 0.00 | 0.00 |
August | 2216.64 | 29.02 | 861.55 | 46.01 | 815.54 | 0.00 | 0.00 |
September | 2478.89 | 124.70 | 1154.98 | 299.78 | 855.20 | 0.00 | 0.00 |
October | 3667.91 | 650.56 | 1987.02 | 1109.54 | 877.48 | 0.00 | 0.00 |
November | 4005.99 | 1212.62 | 2481.90 | 1640.48 | 841.42 | 0.00 | 0.00 |
December | 3144.57 | 1610.62 | 2215.03 | 1388.00 | 827.03 | 0.00 | 0.00 |
Annual Sum or Average | 2869.66 | 643.09 | 1501.89 | 664.51 | 837.38 | 0.00 | 0.00 |
Minimum of Months | 2216.64 | 7.47 | 778.63 | 11.17 | 765.34 | 0.00 | 0.00 |
Maximum of Months | 4005.99 | 1639.43 | 2481.90 | 1640.48 | 940.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 746.80 | 1123.44 | 636.76 | 247.80 | 388.96 | 0.00 | 0.00 |
February | 994.36 | 884.19 | 728.15 | 268.34 | 459.81 | 0.00 | 0.00 |
March | 1557.88 | 549.28 | 944.23 | 377.44 | 566.79 | 0.00 | 0.00 |
April | 2322.74 | 206.38 | 1147.70 | 538.23 | 609.47 | 0.00 | 0.00 |
May | 2570.25 | 35.31 | 1086.77 | 460.98 | 625.78 | 0.00 | 0.00 |
June | 2555.83 | 27.12 | 1020.76 | 396.49 | 624.27 | 0.00 | 0.00 |
July | 1913.74 | 7.80 | 757.46 | 147.33 | 610.13 | 0.00 | 0.00 |
August | 1646.20 | 24.10 | 695.65 | 123.64 | 572.01 | 0.00 | 0.00 |
September | 1584.15 | 87.72 | 764.70 | 224.49 | 540.20 | 0.00 | 0.00 |
October | 1490.17 | 424.86 | 795.93 | 316.94 | 478.99 | 0.00 | 0.00 |
November | 1131.30 | 797.39 | 720.05 | 306.88 | 413.17 | 0.00 | 0.00 |
December | 751.00 | 1084.23 | 616.15 | 234.95 | 381.20 | 0.00 | 0.00 |
Annual Sum or Average | 1607.18 | 435.71 | 826.04 | 303.23 | 522.82 | 0.00 | 0.00 |
Minimum of Months | 746.80 | 7.80 | 616.15 | 123.64 | 381.20 | 0.00 | 0.00 |
Maximum of Months | 2570.25 | 1123.44 | 1147.70 | 538.23 | 625.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 350.80 | 1434.86 | 455.75 | 0.00 | 455.75 | 0.00 | 0.00 |
February | 592.24 | 1147.75 | 540.44 | 0.00 | 540.44 | 0.00 | 0.00 |
March | 1024.00 | 714.46 | 651.23 | 0.00 | 651.23 | 0.00 | 0.00 |
April | 1722.45 | 248.57 | 706.64 | 2.40 | 704.24 | 0.00 | 0.00 |
May | 2370.19 | 40.79 | 782.90 | 21.97 | 760.93 | 0.00 | 0.00 |
June | 2566.82 | 33.79 | 810.43 | 30.02 | 780.41 | 0.00 | 0.00 |
July | 2280.58 | 8.74 | 799.27 | 12.66 | 786.61 | 0.00 | 0.00 |
August | 1926.58 | 30.35 | 733.75 | 2.29 | 731.46 | 0.00 | 0.00 |
September | 1510.04 | 107.23 | 653.79 | 0.05 | 653.75 | 0.00 | 0.00 |
October | 1122.00 | 558.62 | 566.40 | 0.00 | 566.40 | 0.00 | 0.00 |
November | 662.03 | 1037.83 | 479.74 | 0.00 | 479.74 | 0.00 | 0.00 |
December | 387.84 | 1401.08 | 444.59 | 0.00 | 444.59 | 0.00 | 0.00 |
Annual Sum or Average | 1380.12 | 561.14 | 635.89 | 5.80 | 630.09 | 0.00 | 0.00 |
Minimum of Months | 350.80 | 8.74 | 444.59 | 0.00 | 444.59 | 0.00 | 0.00 |
Maximum of Months | 2566.82 | 1434.86 | 810.43 | 30.02 | 786.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 742.42 | 902.50 | 650.86 | 261.25 | 389.61 | 0.00 | 0.00 |
February | 1062.29 | 745.35 | 790.71 | 326.44 | 464.27 | 0.00 | 0.00 |
March | 1565.65 | 477.85 | 964.58 | 398.15 | 566.44 | 0.00 | 0.00 |
April | 2309.11 | 177.69 | 1147.61 | 535.07 | 612.53 | 0.00 | 0.00 |
May | 2619.68 | 28.56 | 1129.56 | 500.78 | 628.77 | 0.00 | 0.00 |
June | 2367.68 | 22.89 | 919.31 | 305.03 | 614.29 | 0.00 | 0.00 |
July | 1941.60 | 4.98 | 772.66 | 163.16 | 609.49 | 0.00 | 0.00 |
August | 1644.30 | 20.47 | 696.20 | 121.15 | 575.04 | 0.00 | 0.00 |
September | 1539.92 | 74.79 | 743.81 | 207.43 | 536.38 | 0.00 | 0.00 |
October | 1497.75 | 380.59 | 813.64 | 328.66 | 484.98 | 0.00 | 0.00 |
November | 1094.99 | 683.46 | 721.41 | 309.66 | 411.75 | 0.00 | 0.00 |
December | 769.15 | 904.03 | 629.04 | 249.23 | 379.81 | 0.00 | 0.00 |
Annual Sum or Average | 1598.06 | 366.91 | 831.39 | 308.36 | 523.03 | 0.00 | 0.00 |
Minimum of Months | 742.42 | 4.98 | 629.04 | 121.15 | 379.81 | 0.00 | 0.00 |
Maximum of Months | 2619.68 | 904.03 | 1147.61 | 535.07 | 628.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2887.24 | 1472.64 | 2072.73 | 1259.44 | 813.28 | 0.00 | 0.00 |
February | 2953.51 | 1229.30 | 1970.86 | 1094.67 | 876.19 | 0.00 | 0.00 |
March | 2929.66 | 788.87 | 1685.13 | 744.31 | 940.82 | 0.00 | 0.00 |
April | 2729.93 | 284.80 | 1183.64 | 334.06 | 849.58 | 0.00 | 0.00 |
May | 2535.53 | 41.03 | 851.20 | 63.01 | 788.18 | 0.00 | 0.00 |
June | 2506.51 | 33.42 | 778.63 | 13.29 | 765.34 | 0.00 | 0.00 |
July | 2316.77 | 7.63 | 812.18 | 11.17 | 801.01 | 0.00 | 0.00 |
August | 2180.37 | 31.87 | 861.55 | 46.01 | 815.54 | 0.00 | 0.00 |
September | 2456.72 | 127.69 | 1154.98 | 299.78 | 855.20 | 0.00 | 0.00 |
October | 3655.02 | 643.56 | 1987.02 | 1109.54 | 877.48 | 0.00 | 0.00 |
November | 4015.35 | 1161.92 | 2481.90 | 1640.48 | 841.42 | 0.00 | 0.00 |
December | 3195.93 | 1484.13 | 2215.03 | 1388.00 | 827.03 | 0.00 | 0.00 |
Annual Sum or Average | 2862.11 | 606.07 | 1501.89 | 664.51 | 837.38 | 0.00 | 0.00 |
Minimum of Months | 2180.37 | 7.63 | 778.63 | 11.17 | 765.34 | 0.00 | 0.00 |
Maximum of Months | 4015.35 | 1484.13 | 2481.90 | 1640.48 | 940.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 776.40 | 1014.22 | 636.76 | 247.80 | 388.96 | 0.00 | 0.00 |
February | 1011.72 | 825.63 | 728.15 | 268.34 | 459.81 | 0.00 | 0.00 |
March | 1556.72 | 532.74 | 944.23 | 377.44 | 566.79 | 0.00 | 0.00 |
April | 2305.30 | 205.49 | 1147.70 | 538.23 | 609.47 | 0.00 | 0.00 |
May | 2544.10 | 36.85 | 1086.77 | 460.98 | 625.78 | 0.00 | 0.00 |
June | 2528.42 | 28.35 | 1020.76 | 396.49 | 624.27 | 0.00 | 0.00 |
July | 1887.98 | 7.82 | 757.46 | 147.33 | 610.13 | 0.00 | 0.00 |
August | 1626.04 | 25.49 | 695.65 | 123.64 | 572.01 | 0.00 | 0.00 |
September | 1572.11 | 87.88 | 764.70 | 224.49 | 540.20 | 0.00 | 0.00 |
October | 1485.74 | 415.53 | 795.93 | 316.94 | 478.99 | 0.00 | 0.00 |
November | 1143.14 | 755.85 | 720.05 | 306.88 | 413.17 | 0.00 | 0.00 |
December | 778.94 | 994.79 | 616.15 | 234.95 | 381.20 | 0.00 | 0.00 |
Annual Sum or Average | 1603.10 | 409.03 | 826.04 | 303.23 | 522.82 | 0.00 | 0.00 |
Minimum of Months | 776.40 | 7.82 | 616.15 | 123.64 | 381.20 | 0.00 | 0.00 |
Maximum of Months | 2544.10 | 1014.22 | 1147.70 | 538.23 | 625.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.650892E+09 | 0.487664E+10 | 0.122065E+10 | 0.00 | 0.122065E+10 | 0.00 | 0.00 |
February | 0.122334E+10 | 0.334657E+10 | 0.130740E+10 | 0.00 | 0.130740E+10 | 0.00 | 0.00 |
March | 0.265359E+10 | 0.210515E+10 | 0.174422E+10 | 0.00 | 0.174422E+10 | 0.00 | 0.00 |
April | 0.443000E+10 | 0.638822E+09 | 0.183157E+10 | 6211386.31 | 0.182536E+10 | 0.00 | 0.00 |
May | 0.639715E+10 | 97945050.72 | 0.209689E+10 | 58841859.56 | 0.203805E+10 | 0.00 | 0.00 |
June | 0.671092E+10 | 72220701.36 | 0.210059E+10 | 77805434.24 | 0.202279E+10 | 0.00 | 0.00 |
July | 0.618736E+10 | 15334698.52 | 0.214072E+10 | 33899197.52 | 0.210682E+10 | 0.00 | 0.00 |
August | 0.517385E+10 | 55802508.90 | 0.196524E+10 | 6124708.88 | 0.195911E+10 | 0.00 | 0.00 |
September | 0.393112E+10 | 0.259523E+09 | 0.169460E+10 | 118989.86 | 0.169448E+10 | 0.00 | 0.00 |
October | 0.294589E+10 | 0.159517E+10 | 0.151701E+10 | 0.00 | 0.151701E+10 | 0.00 | 0.00 |
November | 0.152127E+10 | 0.315633E+10 | 0.124347E+10 | 0.00 | 0.124347E+10 | 0.00 | 0.00 |
December | 0.715615E+09 | 0.475764E+10 | 0.119076E+10 | 0.00 | 0.119076E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.425410E+11 | 0.209772E+11 | 0.200531E+11 | 0.183002E+09 | 0.198701E+11 | 0.00 | 0.00 |
Minimum of Months | 0.650892E+09 | 15334698.52 | 0.119076E+10 | 0.00 | 0.119076E+10 | 0.00 | 0.00 |
Maximum of Months | 0.671092E+10 | 0.487664E+10 | 0.214072E+10 | 77805434.24 | 0.210682E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.176140E+10 | 0.293915E+10 | 0.174327E+10 | 0.699724E+09 | 0.104354E+10 | 0.00 | 0.00 |
February | 0.247693E+10 | 0.203608E+10 | 0.191290E+10 | 0.789733E+09 | 0.112316E+10 | 0.00 | 0.00 |
March | 0.421595E+10 | 0.128865E+10 | 0.258355E+10 | 0.106640E+10 | 0.151715E+10 | 0.00 | 0.00 |
April | 0.608150E+10 | 0.383436E+09 | 0.297461E+10 | 0.138691E+10 | 0.158769E+10 | 0.00 | 0.00 |
May | 0.713151E+10 | 59416635.90 | 0.302542E+10 | 0.134131E+10 | 0.168411E+10 | 0.00 | 0.00 |
June | 0.626078E+10 | 40680360.91 | 0.238287E+10 | 0.790633E+09 | 0.159223E+10 | 0.00 | 0.00 |
July | 0.535581E+10 | 6138952.76 | 0.206950E+10 | 0.437022E+09 | 0.163247E+10 | 0.00 | 0.00 |
August | 0.454382E+10 | 19592310.97 | 0.186470E+10 | 0.324502E+09 | 0.154020E+10 | 0.00 | 0.00 |
September | 0.405312E+10 | 0.153564E+09 | 0.192796E+10 | 0.537659E+09 | 0.139030E+10 | 0.00 | 0.00 |
October | 0.403896E+10 | 0.100295E+10 | 0.217926E+10 | 0.880276E+09 | 0.129898E+10 | 0.00 | 0.00 |
November | 0.277267E+10 | 0.192396E+10 | 0.186990E+10 | 0.802644E+09 | 0.106725E+10 | 0.00 | 0.00 |
December | 0.185477E+10 | 0.284880E+10 | 0.168482E+10 | 0.667536E+09 | 0.101729E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.505472E+11 | 0.127024E+11 | 0.262187E+11 | 0.972435E+10 | 0.164944E+11 | 0.00 | 0.00 |
Minimum of Months | 0.176140E+10 | 6138952.76 | 0.168482E+10 | 0.324502E+09 | 0.101729E+10 | 0.00 | 0.00 |
Maximum of Months | 0.713151E+10 | 0.293915E+10 | 0.302542E+10 | 0.138691E+10 | 0.168411E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.761016E+10 | 0.445731E+10 | 0.555142E+10 | 0.337318E+10 | 0.217825E+10 | 0.00 | 0.00 |
February | 0.711948E+10 | 0.324120E+10 | 0.476777E+10 | 0.264814E+10 | 0.211962E+10 | 0.00 | 0.00 |
March | 0.788897E+10 | 0.216588E+10 | 0.451334E+10 | 0.199349E+10 | 0.251985E+10 | 0.00 | 0.00 |
April | 0.711963E+10 | 0.699425E+09 | 0.306794E+10 | 0.865857E+09 | 0.220208E+10 | 0.00 | 0.00 |
May | 0.684783E+10 | 99023963.90 | 0.227980E+10 | 0.168765E+09 | 0.211104E+10 | 0.00 | 0.00 |
June | 0.655266E+10 | 71935873.70 | 0.201816E+10 | 34438844.85 | 0.198372E+10 | 0.00 | 0.00 |
July | 0.628084E+10 | 14269325.33 | 0.217530E+10 | 29919095.19 | 0.214538E+10 | 0.00 | 0.00 |
August | 0.587679E+10 | 58882898.80 | 0.230752E+10 | 0.123238E+09 | 0.218429E+10 | 0.00 | 0.00 |
September | 0.643700E+10 | 0.292318E+09 | 0.299363E+10 | 0.776997E+09 | 0.221663E+10 | 0.00 | 0.00 |
October | 0.985992E+10 | 0.170340E+10 | 0.532189E+10 | 0.297171E+10 | 0.235018E+10 | 0.00 | 0.00 |
November | 0.104240E+11 | 0.316491E+10 | 0.643288E+10 | 0.425199E+10 | 0.218090E+10 | 0.00 | 0.00 |
December | 0.842912E+10 | 0.443909E+10 | 0.593256E+10 | 0.371749E+10 | 0.221506E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.904464E+11 | 0.204077E+11 | 0.473622E+11 | 0.209552E+11 | 0.264070E+11 | 0.00 | 0.00 |
Minimum of Months | 0.587679E+10 | 14269325.33 | 0.201816E+10 | 29919095.19 | 0.198372E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104240E+11 | 0.445731E+10 | 0.643288E+10 | 0.425199E+10 | 0.251985E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.189259E+10 | 0.339063E+10 | 0.170551E+10 | 0.663719E+09 | 0.104179E+10 | 0.00 | 0.00 |
February | 0.229838E+10 | 0.246660E+10 | 0.176155E+10 | 0.649181E+09 | 0.111237E+10 | 0.00 | 0.00 |
March | 0.407413E+10 | 0.167784E+10 | 0.252903E+10 | 0.101094E+10 | 0.151809E+10 | 0.00 | 0.00 |
April | 0.586102E+10 | 0.661373E+09 | 0.297485E+10 | 0.139509E+10 | 0.157976E+10 | 0.00 | 0.00 |
May | 0.680760E+10 | 0.107423E+09 | 0.291080E+10 | 0.123470E+10 | 0.167610E+10 | 0.00 | 0.00 |
June | 0.649135E+10 | 83756839.92 | 0.264583E+10 | 0.102771E+10 | 0.161812E+10 | 0.00 | 0.00 |
July | 0.493186E+10 | 34482050.52 | 0.202878E+10 | 0.394599E+09 | 0.163419E+10 | 0.00 | 0.00 |
August | 0.412359E+10 | 0.136438E+09 | 0.186323E+10 | 0.331152E+09 | 0.153207E+10 | 0.00 | 0.00 |
September | 0.405097E+10 | 0.260479E+09 | 0.198210E+10 | 0.581889E+09 | 0.140021E+10 | 0.00 | 0.00 |
October | 0.391518E+10 | 0.126358E+10 | 0.213183E+10 | 0.848893E+09 | 0.128294E+10 | 0.00 | 0.00 |
November | 0.280485E+10 | 0.240342E+10 | 0.186638E+10 | 0.795441E+09 | 0.107094E+10 | 0.00 | 0.00 |
December | 0.181229E+10 | 0.354463E+10 | 0.165031E+10 | 0.629301E+09 | 0.102101E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.490638E+11 | 0.160307E+11 | 0.260502E+11 | 0.956263E+10 | 0.164876E+11 | 0.00 | 0.00 |
Minimum of Months | 0.181229E+10 | 34482050.52 | 0.165031E+10 | 0.331152E+09 | 0.102101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.680760E+10 | 0.354463E+10 | 0.297485E+10 | 0.139509E+10 | 0.167610E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.787704E+09 | 0.438594E+10 | 0.122067E+10 | 0.00 | 0.122067E+10 | 0.00 | 0.00 |
February | 0.133441E+10 | 0.304711E+10 | 0.130743E+10 | 0.00 | 0.130743E+10 | 0.00 | 0.00 |
March | 0.272462E+10 | 0.200599E+10 | 0.174425E+10 | 0.00 | 0.174425E+10 | 0.00 | 0.00 |
April | 0.452714E+10 | 0.652407E+09 | 0.183160E+10 | 6211571.55 | 0.182539E+10 | 0.00 | 0.00 |
May | 0.646201E+10 | 0.102538E+09 | 0.209692E+10 | 58843614.39 | 0.203808E+10 | 0.00 | 0.00 |
June | 0.676589E+10 | 81186150.52 | 0.210063E+10 | 77807754.61 | 0.202282E+10 | 0.00 | 0.00 |
July | 0.622808E+10 | 22587717.29 | 0.214076E+10 | 33900208.49 | 0.210686E+10 | 0.00 | 0.00 |
August | 0.525628E+10 | 74296566.66 | 0.196528E+10 | 6124891.54 | 0.195915E+10 | 0.00 | 0.00 |
September | 0.396211E+10 | 0.276058E+09 | 0.169463E+10 | 118993.41 | 0.169451E+10 | 0.00 | 0.00 |
October | 0.301302E+10 | 0.154814E+10 | 0.151703E+10 | 0.00 | 0.151703E+10 | 0.00 | 0.00 |
November | 0.163522E+10 | 0.290451E+10 | 0.124349E+10 | 0.00 | 0.124349E+10 | 0.00 | 0.00 |
December | 0.892305E+09 | 0.420274E+10 | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.435888E+11 | 0.193035E+11 | 0.200535E+11 | 0.183007E+09 | 0.198705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.787704E+09 | 22587717.29 | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.00 | 0.00 |
Maximum of Months | 0.676589E+10 | 0.438594E+10 | 0.214076E+10 | 77807754.61 | 0.210686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.184848E+10 | 0.271680E+10 | 0.174326E+10 | 0.699721E+09 | 0.104354E+10 | 0.00 | 0.00 |
February | 0.250699E+10 | 0.193262E+10 | 0.191289E+10 | 0.789730E+09 | 0.112316E+10 | 0.00 | 0.00 |
March | 0.419958E+10 | 0.130952E+10 | 0.258354E+10 | 0.106640E+10 | 0.151715E+10 | 0.00 | 0.00 |
April | 0.604063E+10 | 0.455427E+09 | 0.297459E+10 | 0.138691E+10 | 0.158769E+10 | 0.00 | 0.00 |
May | 0.710865E+10 | 69153025.91 | 0.302541E+10 | 0.134130E+10 | 0.168411E+10 | 0.00 | 0.00 |
June | 0.622568E+10 | 53855834.36 | 0.238286E+10 | 0.790630E+09 | 0.159223E+10 | 0.00 | 0.00 |
July | 0.529251E+10 | 12924606.31 | 0.206949E+10 | 0.437021E+09 | 0.163247E+10 | 0.00 | 0.00 |
August | 0.447640E+10 | 49289897.03 | 0.186469E+10 | 0.324501E+09 | 0.154019E+10 | 0.00 | 0.00 |
September | 0.403269E+10 | 0.187788E+09 | 0.192795E+10 | 0.537657E+09 | 0.139029E+10 | 0.00 | 0.00 |
October | 0.402938E+10 | 0.103206E+10 | 0.217925E+10 | 0.880272E+09 | 0.129897E+10 | 0.00 | 0.00 |
November | 0.279714E+10 | 0.186442E+10 | 0.186989E+10 | 0.802641E+09 | 0.106725E+10 | 0.00 | 0.00 |
December | 0.194163E+10 | 0.265692E+10 | 0.168481E+10 | 0.667533E+09 | 0.101728E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.504998E+11 | 0.123408E+11 | 0.262186E+11 | 0.972431E+10 | 0.164943E+11 | 0.00 | 0.00 |
Minimum of Months | 0.184848E+10 | 12924606.31 | 0.168481E+10 | 0.324501E+09 | 0.101728E+10 | 0.00 | 0.00 |
Maximum of Months | 0.710865E+10 | 0.271680E+10 | 0.302541E+10 | 0.138691E+10 | 0.168411E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.756709E+10 | 0.439105E+10 | 0.555159E+10 | 0.337329E+10 | 0.217830E+10 | 0.00 | 0.00 |
February | 0.708161E+10 | 0.317891E+10 | 0.476791E+10 | 0.264823E+10 | 0.211968E+10 | 0.00 | 0.00 |
March | 0.786302E+10 | 0.217015E+10 | 0.451346E+10 | 0.199356E+10 | 0.251990E+10 | 0.00 | 0.00 |
April | 0.714833E+10 | 0.737085E+09 | 0.306800E+10 | 0.865885E+09 | 0.220212E+10 | 0.00 | 0.00 |
May | 0.690717E+10 | 0.102794E+09 | 0.227984E+10 | 0.168770E+09 | 0.211107E+10 | 0.00 | 0.00 |
June | 0.661126E+10 | 80049606.88 | 0.201820E+10 | 34439972.86 | 0.198376E+10 | 0.00 | 0.00 |
July | 0.632658E+10 | 20011221.71 | 0.217534E+10 | 29920075.17 | 0.214542E+10 | 0.00 | 0.00 |
August | 0.593705E+10 | 77714619.05 | 0.230758E+10 | 0.123242E+09 | 0.218434E+10 | 0.00 | 0.00 |
September | 0.642529E+10 | 0.323219E+09 | 0.299371E+10 | 0.777023E+09 | 0.221668E+10 | 0.00 | 0.00 |
October | 0.982414E+10 | 0.174246E+10 | 0.532204E+10 | 0.297180E+10 | 0.235023E+10 | 0.00 | 0.00 |
November | 0.103835E+11 | 0.314311E+10 | 0.643307E+10 | 0.425213E+10 | 0.218095E+10 | 0.00 | 0.00 |
December | 0.842242E+10 | 0.431390E+10 | 0.593273E+10 | 0.371762E+10 | 0.221512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.904975E+11 | 0.202804E+11 | 0.473635E+11 | 0.209559E+11 | 0.264076E+11 | 0.00 | 0.00 |
Minimum of Months | 0.593705E+10 | 20011221.71 | 0.201820E+10 | 29920075.17 | 0.198376E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103835E+11 | 0.439105E+10 | 0.643307E+10 | 0.425213E+10 | 0.251990E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.200024E+10 | 0.300901E+10 | 0.170550E+10 | 0.663716E+09 | 0.104178E+10 | 0.00 | 0.00 |
February | 0.240556E+10 | 0.213904E+10 | 0.176155E+10 | 0.649178E+09 | 0.111237E+10 | 0.00 | 0.00 |
March | 0.417263E+10 | 0.147118E+10 | 0.252902E+10 | 0.101094E+10 | 0.151808E+10 | 0.00 | 0.00 |
April | 0.602055E+10 | 0.534943E+09 | 0.297484E+10 | 0.139509E+10 | 0.157975E+10 | 0.00 | 0.00 |
May | 0.688415E+10 | 94580319.99 | 0.291079E+10 | 0.123470E+10 | 0.167609E+10 | 0.00 | 0.00 |
June | 0.662471E+10 | 70298217.95 | 0.264582E+10 | 0.102771E+10 | 0.161811E+10 | 0.00 | 0.00 |
July | 0.512577E+10 | 20898399.94 | 0.202878E+10 | 0.394598E+09 | 0.163418E+10 | 0.00 | 0.00 |
August | 0.440919E+10 | 64540666.80 | 0.186322E+10 | 0.331151E+09 | 0.153207E+10 | 0.00 | 0.00 |
September | 0.410613E+10 | 0.227363E+09 | 0.198210E+10 | 0.581887E+09 | 0.140021E+10 | 0.00 | 0.00 |
October | 0.399128E+10 | 0.113794E+10 | 0.213182E+10 | 0.848889E+09 | 0.128294E+10 | 0.00 | 0.00 |
November | 0.293233E+10 | 0.206683E+10 | 0.186638E+10 | 0.795438E+09 | 0.107094E+10 | 0.00 | 0.00 |
December | 0.201149E+10 | 0.290401E+10 | 0.165030E+10 | 0.629299E+09 | 0.102101E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.506840E+11 | 0.137406E+11 | 0.260501E+11 | 0.956259E+10 | 0.164875E+11 | 0.00 | 0.00 |
Minimum of Months | 0.200024E+10 | 20898399.94 | 0.165030E+10 | 0.331151E+09 | 0.102101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.688415E+10 | 0.300901E+10 | 0.297484E+10 | 0.139509E+10 | 0.167609E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.939590E+09 | 0.384313E+10 | 0.122067E+10 | 0.00 | 0.122067E+10 | 0.00 | 0.00 |
February | 0.143274E+10 | 0.277664E+10 | 0.130743E+10 | 0.00 | 0.130743E+10 | 0.00 | 0.00 |
March | 0.274269E+10 | 0.191360E+10 | 0.174425E+10 | 0.00 | 0.174425E+10 | 0.00 | 0.00 |
April | 0.446458E+10 | 0.644289E+09 | 0.183160E+10 | 6211571.55 | 0.182539E+10 | 0.00 | 0.00 |
May | 0.634831E+10 | 0.109265E+09 | 0.209692E+10 | 58843614.39 | 0.203808E+10 | 0.00 | 0.00 |
June | 0.665320E+10 | 87572832.08 | 0.210063E+10 | 77807754.61 | 0.202282E+10 | 0.00 | 0.00 |
July | 0.610829E+10 | 23400604.58 | 0.214076E+10 | 33900208.49 | 0.210686E+10 | 0.00 | 0.00 |
August | 0.516014E+10 | 81300455.28 | 0.196528E+10 | 6124891.54 | 0.195915E+10 | 0.00 | 0.00 |
September | 0.391401E+10 | 0.277935E+09 | 0.169463E+10 | 118993.41 | 0.169451E+10 | 0.00 | 0.00 |
October | 0.300516E+10 | 0.149621E+10 | 0.151703E+10 | 0.00 | 0.151703E+10 | 0.00 | 0.00 |
November | 0.171599E+10 | 0.269005E+10 | 0.124349E+10 | 0.00 | 0.124349E+10 | 0.00 | 0.00 |
December | 0.103879E+10 | 0.375264E+10 | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.435235E+11 | 0.176960E+11 | 0.200535E+11 | 0.183007E+09 | 0.198705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.939590E+09 | 23400604.58 | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.00 | 0.00 |
Maximum of Months | 0.665320E+10 | 0.384313E+10 | 0.214076E+10 | 77807754.61 | 0.210686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.198851E+10 | 0.241726E+10 | 0.174326E+10 | 0.699721E+09 | 0.104354E+10 | 0.00 | 0.00 |
February | 0.256989E+10 | 0.180315E+10 | 0.191289E+10 | 0.789730E+09 | 0.112316E+10 | 0.00 | 0.00 |
March | 0.419343E+10 | 0.127986E+10 | 0.258354E+10 | 0.106640E+10 | 0.151715E+10 | 0.00 | 0.00 |
April | 0.598521E+10 | 0.460568E+09 | 0.297459E+10 | 0.138691E+10 | 0.158769E+10 | 0.00 | 0.00 |
May | 0.701654E+10 | 76503274.79 | 0.302541E+10 | 0.134130E+10 | 0.168411E+10 | 0.00 | 0.00 |
June | 0.613702E+10 | 59323828.07 | 0.238286E+10 | 0.790630E+09 | 0.159223E+10 | 0.00 | 0.00 |
July | 0.520037E+10 | 13351592.25 | 0.206949E+10 | 0.437021E+09 | 0.163247E+10 | 0.00 | 0.00 |
August | 0.440409E+10 | 54822785.64 | 0.186469E+10 | 0.324501E+09 | 0.154019E+10 | 0.00 | 0.00 |
September | 0.399146E+10 | 0.193869E+09 | 0.192795E+10 | 0.537657E+09 | 0.139029E+10 | 0.00 | 0.00 |
October | 0.401157E+10 | 0.101937E+10 | 0.217925E+10 | 0.880272E+09 | 0.129897E+10 | 0.00 | 0.00 |
November | 0.283821E+10 | 0.177154E+10 | 0.186989E+10 | 0.802641E+09 | 0.106725E+10 | 0.00 | 0.00 |
December | 0.206010E+10 | 0.242134E+10 | 0.168481E+10 | 0.667533E+09 | 0.101728E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.503964E+11 | 0.115710E+11 | 0.262186E+11 | 0.972431E+10 | 0.164943E+11 | 0.00 | 0.00 |
Minimum of Months | 0.198851E+10 | 13351592.25 | 0.168481E+10 | 0.324501E+09 | 0.101728E+10 | 0.00 | 0.00 |
Maximum of Months | 0.701654E+10 | 0.242134E+10 | 0.302541E+10 | 0.138691E+10 | 0.168411E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.773319E+10 | 0.394431E+10 | 0.555159E+10 | 0.337329E+10 | 0.217830E+10 | 0.00 | 0.00 |
February | 0.714514E+10 | 0.297393E+10 | 0.476791E+10 | 0.264823E+10 | 0.211968E+10 | 0.00 | 0.00 |
March | 0.784680E+10 | 0.211291E+10 | 0.451346E+10 | 0.199356E+10 | 0.251990E+10 | 0.00 | 0.00 |
April | 0.707598E+10 | 0.738200E+09 | 0.306800E+10 | 0.865885E+09 | 0.220212E+10 | 0.00 | 0.00 |
May | 0.679117E+10 | 0.109889E+09 | 0.227984E+10 | 0.168770E+09 | 0.211107E+10 | 0.00 | 0.00 |
June | 0.649688E+10 | 86626236.95 | 0.201820E+10 | 34439972.86 | 0.198376E+10 | 0.00 | 0.00 |
July | 0.620523E+10 | 20431277.23 | 0.217534E+10 | 29920075.17 | 0.214542E+10 | 0.00 | 0.00 |
August | 0.583991E+10 | 85365602.64 | 0.230758E+10 | 0.123242E+09 | 0.218434E+10 | 0.00 | 0.00 |
September | 0.636781E+10 | 0.330972E+09 | 0.299371E+10 | 0.777023E+09 | 0.221668E+10 | 0.00 | 0.00 |
October | 0.978961E+10 | 0.172370E+10 | 0.532204E+10 | 0.297180E+10 | 0.235023E+10 | 0.00 | 0.00 |
November | 0.104078E+11 | 0.301170E+10 | 0.643307E+10 | 0.425213E+10 | 0.218095E+10 | 0.00 | 0.00 |
December | 0.855999E+10 | 0.397510E+10 | 0.593273E+10 | 0.371762E+10 | 0.221512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.902595E+11 | 0.191131E+11 | 0.473635E+11 | 0.209559E+11 | 0.264076E+11 | 0.00 | 0.00 |
Minimum of Months | 0.583991E+10 | 20431277.23 | 0.201820E+10 | 29920075.17 | 0.198376E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104078E+11 | 0.397510E+10 | 0.643307E+10 | 0.425213E+10 | 0.251990E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.207950E+10 | 0.271648E+10 | 0.170550E+10 | 0.663716E+09 | 0.104178E+10 | 0.00 | 0.00 |
February | 0.244756E+10 | 0.199735E+10 | 0.176155E+10 | 0.649178E+09 | 0.111237E+10 | 0.00 | 0.00 |
March | 0.416951E+10 | 0.142688E+10 | 0.252902E+10 | 0.101094E+10 | 0.151808E+10 | 0.00 | 0.00 |
April | 0.597533E+10 | 0.532618E+09 | 0.297484E+10 | 0.139509E+10 | 0.157975E+10 | 0.00 | 0.00 |
May | 0.681412E+10 | 98710896.68 | 0.291079E+10 | 0.123470E+10 | 0.167609E+10 | 0.00 | 0.00 |
June | 0.655366E+10 | 73479914.97 | 0.264582E+10 | 0.102771E+10 | 0.161811E+10 | 0.00 | 0.00 |
July | 0.505677E+10 | 20955766.78 | 0.202878E+10 | 0.394598E+09 | 0.163418E+10 | 0.00 | 0.00 |
August | 0.435517E+10 | 68284712.84 | 0.186322E+10 | 0.331151E+09 | 0.153207E+10 | 0.00 | 0.00 |
September | 0.407490E+10 | 0.227787E+09 | 0.198210E+10 | 0.581887E+09 | 0.140021E+10 | 0.00 | 0.00 |
October | 0.397941E+10 | 0.111295E+10 | 0.213182E+10 | 0.848889E+09 | 0.128294E+10 | 0.00 | 0.00 |
November | 0.296303E+10 | 0.195916E+10 | 0.186638E+10 | 0.795438E+09 | 0.107094E+10 | 0.00 | 0.00 |
December | 0.208632E+10 | 0.266446E+10 | 0.165030E+10 | 0.629299E+09 | 0.102101E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.505553E+11 | 0.128991E+11 | 0.260501E+11 | 0.956259E+10 | 0.164875E+11 | 0.00 | 0.00 |
Minimum of Months | 0.207950E+10 | 20955766.78 | 0.165030E+10 | 0.331151E+09 | 0.102101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.681412E+10 | 0.271648E+10 | 0.297484E+10 | 0.139509E+10 | 0.167609E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.313245E+11 | -0.303042E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102032E+10 | 58.97 | 0.00 | 0.00 |
February | 0.278778E+11 | -0.269554E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -922328717.7 | 58.97 | 0.00 | 0.00 |
March | 0.305995E+11 | -0.295748E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102473E+10 | 58.98 | 0.00 | 0.00 |
April | 0.250564E+11 | -0.240684E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987953811.3 | 58.97 | 0.00 | 0.00 |
May | 0.237327E+11 | -0.227111E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102161E+10 | 58.97 | 0.00 | 0.00 |
June | 0.211658E+11 | -0.201766E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989229059.1 | 58.96 | 0.00 | 0.00 |
July | 0.193127E+11 | -0.182960E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101665E+10 | 58.96 | 0.00 | 0.00 |
August | 0.217655E+11 | -0.207448E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102071E+10 | 58.97 | 0.00 | 0.00 |
September | 0.218144E+11 | -0.208288E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985584850.1 | 58.97 | 0.00 | 0.00 |
October | 0.253561E+11 | -0.243388E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101738E+10 | 58.97 | 0.00 | 0.00 |
November | 0.277040E+11 | -0.267188E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985113992.5 | 58.98 | 0.00 | 0.00 |
December | 0.297406E+11 | -0.287224E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101817E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.305450E+12 | -0.293440E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120098E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.193127E+11 | -0.303042E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102473E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.313245E+11 | -0.182960E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -922328717.7 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.64 | 0.61 | 01-JAN-07:49 | 5229.40 | 34.80 | 297.00 | 284.33 | 1049.42 | 24.95 | 250.50 | 263.50 |
February | 303.83 | 0.64 | 0.61 | 01-FEB-07:49 | 3042.78 | 28.08 | 195.67 | 268.33 | 918.85 | 20.43 | 147.00 | 236.00 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:40 | 1477.59 | 17.65 | 7.50 | 315.00 | 789.00 | 20.23 | 129.17 | 279.83 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:10 | 982.72 | 16.01 | 0.00 | 322.67 | 578.92 | 18.84 | 10.17 | 280.50 |
May | 406.00 | 0.65 | 0.61 | 01-MAY-06:49 | 833.18 | 15.69 | 0.00 | 340.50 | 488.09 | 18.64 | 0.67 | 292.67 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-06:00 | 829.12 | 15.40 | 0.00 | 326.00 | 473.29 | 18.30 | 0.00 | 274.67 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:40 | 948.58 | 15.96 | 0.00 | 324.17 | 486.34 | 18.75 | 3.33 | 260.67 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-06:49 | 1073.85 | 16.05 | 0.00 | 313.50 | 530.54 | 18.80 | 51.17 | 252.33 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-06:00 | 1299.80 | 16.77 | 0.00 | 294.33 | 664.41 | 19.62 | 123.67 | 248.67 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-06:00 | 2269.30 | 18.78 | 39.33 | 300.17 | 883.15 | 19.96 | 131.00 | 269.67 |
November | 317.83 | 0.64 | 0.61 | 01-NOV-07:19 | 7147.17 | 34.42 | 292.17 | 279.00 | 1080.60 | 22.63 | 172.83 | 259.17 |
December | 315.50 | 0.64 | 0.61 | 01-DEC-07:30 | 5499.61 | 34.82 | 293.00 | 280.17 | 1253.63 | 27.25 | 275.83 | 276.00 |
Annual Sum or Average | 4237.50 | 0.64 | 2399.52 | 21.42 | 1124.67 | 3648.17 | 745.67 | 20.52 | 1295.33 | 3193.67 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 829.12 | 15.40 | 0.00 | 268.33 | 473.29 | 18.30 | 0.00 | 236.00 | |
Maximum of Months | 406.00 | 0.65 | 0.61 | 7147.17 | 34.82 | 297.00 | 340.50 | 1253.63 | 27.25 | 275.83 | 292.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.66 | 0.61 | 01-JAN-07:49 | 1408.41 | 17.63 | 83.67 | 252.17 | 757.96 | 18.92 | 74.33 | 200.50 |
February | 303.83 | 0.65 | 0.61 | 01-FEB-07:49 | 1747.84 | 17.40 | 75.00 | 246.17 | 948.69 | 18.63 | 69.50 | 199.00 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:40 | 1690.85 | 15.45 | 57.83 | 305.67 | 849.32 | 14.19 | 2.67 | 264.67 |
April | 379.83 | 0.65 | 0.61 | 01-APR-06:49 | 2045.00 | 11.68 | 0.00 | 316.00 | 1092.67 | 13.06 | 0.00 | 279.50 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-06:10 | 2207.47 | 11.81 | 0.00 | 344.83 | 801.02 | 13.00 | 0.00 | 301.00 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-06:40 | 1740.72 | 11.88 | 0.00 | 329.00 | 689.86 | 12.82 | 0.00 | 278.83 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:10 | 1427.28 | 12.51 | 0.00 | 328.33 | 612.22 | 13.14 | 0.00 | 260.00 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-06:19 | 1286.70 | 12.44 | 0.00 | 311.50 | 583.45 | 13.09 | 0.00 | 246.83 |
September | 344.33 | 0.65 | 0.61 | 01-SEP-06:49 | 1436.76 | 13.06 | 8.50 | 289.17 | 722.50 | 13.86 | 5.50 | 230.67 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-06:49 | 1588.53 | 17.03 | 85.83 | 283.83 | 776.70 | 16.43 | 55.00 | 240.67 |
November | 317.83 | 0.65 | 0.61 | 01-NOV-07:10 | 1431.06 | 17.88 | 82.50 | 254.67 | 711.90 | 17.54 | 56.17 | 210.67 |
December | 315.50 | 0.65 | 0.61 | 01-DEC-07:40 | 1471.06 | 18.19 | 87.83 | 247.67 | 805.64 | 19.64 | 79.67 | 206.17 |
Annual Sum or Average | 4237.50 | 0.65 | 1635.41 | 14.54 | 481.17 | 3509.00 | 777.75 | 15.15 | 342.83 | 2918.50 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 1286.70 | 11.68 | 0.00 | 246.17 | 583.45 | 12.82 | 0.00 | 199.00 | |
Maximum of Months | 406.00 | 0.66 | 0.61 | 2207.47 | 18.19 | 87.83 | 344.83 | 1092.67 | 19.64 | 79.67 | 301.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.67 | 0.61 | 01-JAN-08:39 | 450.37 | 0.00 | 0.00 | 225.50 | 281.20 | 0.00 | 0.00 | 101.67 |
February | 303.83 | 0.66 | 0.61 | 01-FEB-08:20 | 520.95 | 0.00 | 0.00 | 237.00 | 323.35 | 0.00 | 0.00 | 146.67 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:00 | 616.84 | 0.00 | 0.00 | 302.83 | 381.62 | 0.00 | 0.00 | 236.67 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:10 | 664.67 | 0.00 | 0.00 | 325.67 | 417.80 | 0.00 | 0.00 | 278.67 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-06:19 | 802.65 | 0.00 | 0.00 | 360.00 | 471.90 | 0.00 | 0.00 | 322.83 |
June | 386.67 | 0.64 | 0.61 | 01-JUN-06:49 | 896.14 | 0.00 | 0.00 | 342.50 | 498.79 | 0.00 | 0.00 | 300.17 |
July | 379.83 | 0.63 | 0.61 | 01-JUL-06:19 | 922.74 | 0.00 | 0.00 | 336.83 | 477.54 | 0.00 | 0.00 | 278.83 |
August | 372.50 | 0.64 | 0.61 | 01-AUG-06:40 | 827.49 | 0.00 | 0.00 | 317.17 | 427.45 | 0.00 | 0.00 | 249.33 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-06:00 | 710.28 | 0.00 | 0.00 | 290.67 | 393.92 | 0.00 | 0.00 | 216.67 |
October | 347.33 | 0.66 | 0.61 | 01-OCT-07:10 | 543.29 | 0.00 | 0.00 | 279.17 | 345.60 | 0.00 | 0.00 | 198.00 |
November | 317.83 | 0.66 | 0.61 | 01-NOV-07:40 | 456.83 | 0.00 | 0.00 | 235.17 | 304.39 | 0.00 | 0.00 | 132.33 |
December | 315.50 | 0.67 | 0.61 | 01-DEC-08:20 | 442.31 | 0.00 | 0.00 | 223.17 | 279.49 | 0.00 | 0.00 | 89.33 |
Annual Sum or Average | 4237.50 | 0.65 | 667.50 | 0.00 | 0.00 | 3475.67 | 389.74 | 0.00 | 0.00 | 2551.17 | ||
Minimum of Months | 303.83 | 0.63 | 0.61 | 442.31 | 0.00 | 0.00 | 223.17 | 279.49 | 0.00 | 0.00 | 89.33 | |
Maximum of Months | 406.00 | 0.67 | 0.61 | 922.74 | 0.00 | 0.00 | 360.00 | 498.79 | 0.00 | 0.00 | 322.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.66 | 0.61 | 01-JAN-08:50 | 1413.08 | 17.63 | 82.50 | 250.33 | 745.72 | 18.67 | 71.50 | 201.67 |
February | 303.83 | 0.65 | 0.61 | 01-FEB-08:39 | 1662.73 | 17.31 | 77.00 | 247.67 | 663.34 | 16.83 | 44.00 | 201.83 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-08:09 | 1645.38 | 15.39 | 57.33 | 306.00 | 822.80 | 14.13 | 1.83 | 264.50 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:30 | 1881.74 | 11.68 | 0.00 | 319.50 | 978.65 | 13.07 | 0.00 | 282.83 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-07:10 | 1807.33 | 11.79 | 0.00 | 342.00 | 934.99 | 12.97 | 0.00 | 301.67 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-07:10 | 1804.63 | 11.96 | 0.00 | 329.83 | 716.76 | 12.90 | 0.00 | 284.17 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:00 | 1378.71 | 12.53 | 0.00 | 325.67 | 605.46 | 13.16 | 0.00 | 263.17 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-07:10 | 1272.69 | 12.41 | 0.00 | 311.33 | 626.22 | 13.05 | 0.00 | 248.17 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-07:30 | 1410.50 | 13.13 | 8.50 | 290.00 | 698.44 | 13.92 | 5.50 | 236.00 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-07:30 | 1689.01 | 16.96 | 84.83 | 281.00 | 848.39 | 16.34 | 54.00 | 242.00 |
November | 317.83 | 0.65 | 0.61 | 01-NOV-07:00 | 1480.96 | 17.90 | 84.83 | 257.67 | 720.42 | 17.28 | 55.00 | 211.83 |
December | 315.50 | 0.65 | 0.61 | 01-DEC-08:20 | 1293.14 | 18.30 | 87.33 | 252.17 | 650.84 | 17.73 | 56.33 | 204.50 |
Annual Sum or Average | 4237.50 | 0.65 | 1569.62 | 14.54 | 482.33 | 3513.17 | 755.35 | 14.83 | 288.17 | 2942.33 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 1272.69 | 11.68 | 0.00 | 247.67 | 605.46 | 12.90 | 0.00 | 201.67 | |
Maximum of Months | 406.00 | 0.66 | 0.61 | 1881.74 | 18.30 | 87.33 | 342.00 | 978.65 | 18.67 | 71.50 | 301.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.64 | 0.61 | 01-JAN-07:00 | 5130.05 | 30.67 | 258.67 | 276.50 | 1080.85 | 20.87 | 85.17 | 263.83 |
February | 303.83 | 0.64 | 0.61 | 01-FEB-07:49 | 3016.51 | 25.57 | 194.00 | 267.83 | 950.11 | 15.67 | 0.00 | 237.17 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:40 | 1455.73 | 11.86 | 7.50 | 313.67 | 815.73 | 16.26 | 0.00 | 281.83 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:10 | 970.59 | 10.73 | 0.00 | 320.17 | 598.55 | 15.38 | 0.00 | 283.17 |
May | 406.00 | 0.65 | 0.61 | 01-MAY-06:49 | 820.23 | 10.24 | 0.00 | 338.33 | 503.19 | 14.95 | 0.00 | 296.17 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-06:00 | 814.68 | 9.84 | 0.00 | 325.33 | 487.37 | 14.45 | 0.00 | 277.50 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:40 | 926.96 | 9.83 | 0.00 | 322.50 | 499.91 | 14.41 | 0.00 | 264.33 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-06:49 | 1046.53 | 9.89 | 0.00 | 312.00 | 544.67 | 14.35 | 0.00 | 254.50 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-06:00 | 1270.45 | 10.66 | 0.00 | 294.00 | 683.06 | 15.30 | 0.00 | 250.67 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-06:00 | 2255.69 | 13.22 | 39.33 | 301.83 | 915.79 | 15.53 | 5.33 | 271.67 |
November | 317.83 | 0.64 | 0.61 | 01-NOV-07:19 | 7119.93 | 33.41 | 288.33 | 277.83 | 1123.69 | 18.15 | 45.17 | 263.67 |
December | 315.50 | 0.64 | 0.61 | 01-DEC-07:40 | 5415.75 | 32.21 | 273.33 | 276.17 | 1276.95 | 22.72 | 113.50 | 272.50 |
Annual Sum or Average | 4237.50 | 0.64 | 2368.49 | 16.61 | 1061.17 | 3626.17 | 768.69 | 16.35 | 249.17 | 3217.00 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 814.68 | 9.83 | 0.00 | 267.83 | 487.37 | 14.35 | 0.00 | 237.17 | |
Maximum of Months | 406.00 | 0.65 | 0.61 | 7119.93 | 33.41 | 288.33 | 338.33 | 1276.95 | 22.72 | 113.50 | 296.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.66 | 0.61 | 01-JAN-07:49 | 1401.92 | 15.60 | 84.33 | 251.83 | 733.15 | 15.14 | 55.17 | 201.00 |
February | 303.83 | 0.65 | 0.61 | 01-FEB-07:49 | 1742.61 | 15.21 | 75.33 | 245.67 | 968.45 | 16.85 | 70.00 | 201.83 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:40 | 1697.60 | 12.81 | 57.83 | 304.83 | 872.79 | 11.71 | 2.83 | 267.33 |
April | 379.83 | 0.65 | 0.61 | 01-APR-06:49 | 2033.91 | 8.42 | 0.00 | 314.83 | 1117.79 | 10.77 | 0.00 | 282.50 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-06:10 | 2100.19 | 8.45 | 0.00 | 344.33 | 827.26 | 10.77 | 0.00 | 305.17 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-06:40 | 1728.87 | 8.66 | 0.00 | 328.33 | 712.17 | 10.73 | 0.00 | 283.50 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:10 | 1389.78 | 9.10 | 0.00 | 327.17 | 635.10 | 10.93 | 0.00 | 264.00 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-06:19 | 1272.50 | 9.07 | 0.00 | 311.00 | 658.83 | 10.81 | 0.00 | 251.17 |
September | 344.33 | 0.65 | 0.61 | 01-SEP-06:49 | 1432.36 | 9.82 | 8.50 | 288.17 | 740.98 | 11.49 | 5.50 | 237.00 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-06:49 | 1572.48 | 14.64 | 81.83 | 283.50 | 797.34 | 14.52 | 55.50 | 244.17 |
November | 317.83 | 0.65 | 0.61 | 01-NOV-07:10 | 1329.36 | 13.75 | 59.00 | 253.67 | 731.65 | 15.56 | 56.50 | 214.67 |
December | 315.50 | 0.66 | 0.61 | 01-DEC-07:40 | 1464.61 | 16.15 | 87.83 | 247.33 | 822.19 | 17.81 | 79.83 | 210.17 |
Annual Sum or Average | 4237.50 | 0.65 | 1608.38 | 11.57 | 454.67 | 3500.67 | 800.71 | 12.88 | 325.33 | 2962.50 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 1272.50 | 8.42 | 0.00 | 245.67 | 635.10 | 10.73 | 0.00 | 201.00 | |
Maximum of Months | 406.00 | 0.66 | 0.61 | 2100.19 | 16.15 | 87.83 | 344.33 | 1117.79 | 17.81 | 79.83 | 305.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.67 | 0.61 | 01-JAN-08:39 | 441.09 | 0.00 | 0.00 | 221.50 | 288.57 | 0.00 | 0.00 | 116.67 |
February | 303.83 | 0.66 | 0.61 | 01-FEB-08:20 | 511.05 | 0.00 | 0.00 | 234.33 | 332.25 | 0.00 | 0.00 | 152.83 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:00 | 606.20 | 0.00 | 0.00 | 300.33 | 392.55 | 0.00 | 0.00 | 241.00 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:10 | 655.23 | 0.00 | 0.00 | 324.83 | 430.59 | 0.00 | 0.00 | 282.33 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-06:30 | 787.27 | 0.00 | 0.00 | 356.17 | 486.43 | 0.00 | 0.00 | 325.00 |
June | 386.67 | 0.64 | 0.61 | 01-JUN-06:49 | 879.81 | 0.00 | 0.00 | 340.50 | 515.22 | 0.00 | 0.00 | 304.33 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:19 | 903.51 | 0.00 | 0.00 | 334.17 | 490.83 | 0.00 | 0.00 | 281.33 |
August | 372.50 | 0.64 | 0.61 | 01-AUG-06:40 | 809.72 | 0.00 | 0.00 | 315.33 | 439.36 | 0.00 | 0.00 | 253.50 |
September | 344.33 | 0.65 | 0.61 | 01-SEP-06:00 | 695.82 | 0.00 | 0.00 | 289.00 | 404.84 | 0.00 | 0.00 | 220.83 |
October | 347.33 | 0.66 | 0.61 | 01-OCT-07:19 | 533.66 | 0.00 | 0.00 | 276.50 | 355.31 | 0.00 | 0.00 | 205.67 |
November | 317.83 | 0.66 | 0.61 | 01-NOV-07:49 | 448.06 | 0.00 | 0.00 | 233.00 | 312.52 | 0.00 | 0.00 | 144.17 |
December | 315.50 | 0.67 | 0.61 | 01-DEC-08:20 | 432.98 | 0.00 | 0.00 | 219.33 | 286.65 | 0.00 | 0.00 | 103.33 |
Annual Sum or Average | 4237.50 | 0.65 | 654.76 | 0.00 | 0.00 | 3445.00 | 400.97 | 0.00 | 0.00 | 2631.00 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 432.98 | 0.00 | 0.00 | 219.33 | 286.65 | 0.00 | 0.00 | 103.33 | |
Maximum of Months | 406.00 | 0.67 | 0.61 | 903.51 | 0.00 | 0.00 | 356.17 | 515.22 | 0.00 | 0.00 | 325.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.66 | 0.61 | 01-JAN-08:50 | 1406.70 | 15.58 | 82.83 | 249.50 | 761.98 | 16.83 | 72.00 | 204.17 |
February | 303.83 | 0.65 | 0.61 | 01-FEB-08:39 | 1656.77 | 15.12 | 77.00 | 246.67 | 681.65 | 14.81 | 44.33 | 205.50 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-08:09 | 1651.00 | 12.76 | 57.33 | 305.50 | 845.71 | 11.66 | 1.83 | 268.50 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:30 | 1870.60 | 8.42 | 0.00 | 318.83 | 964.50 | 10.78 | 0.00 | 283.17 |
May | 406.00 | 0.65 | 0.61 | 01-MAY-07:10 | 1792.11 | 8.45 | 0.00 | 341.17 | 960.72 | 10.75 | 0.00 | 304.50 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-07:10 | 1794.68 | 8.64 | 0.00 | 329.67 | 741.16 | 10.74 | 0.00 | 288.33 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:00 | 1347.38 | 9.13 | 0.00 | 324.50 | 623.83 | 10.95 | 0.00 | 268.17 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-07:10 | 1258.54 | 9.05 | 0.00 | 310.17 | 643.06 | 10.78 | 0.00 | 252.83 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-07:30 | 1405.39 | 9.87 | 8.50 | 290.00 | 717.02 | 11.55 | 5.50 | 240.33 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-07:30 | 1689.90 | 14.87 | 85.00 | 280.33 | 868.71 | 14.44 | 54.17 | 246.00 |
November | 317.83 | 0.65 | 0.61 | 01-NOV-07:00 | 1476.23 | 15.84 | 85.00 | 256.83 | 739.90 | 15.26 | 55.00 | 216.67 |
December | 315.50 | 0.65 | 0.61 | 01-DEC-08:20 | 1287.98 | 16.29 | 87.33 | 251.67 | 667.01 | 15.64 | 56.33 | 208.50 |
Annual Sum or Average | 4237.50 | 0.65 | 1560.70 | 11.74 | 483.00 | 3504.83 | 772.25 | 12.67 | 289.17 | 2986.67 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 1258.54 | 8.42 | 0.00 | 246.67 | 623.83 | 10.74 | 0.00 | 204.17 | |
Maximum of Months | 406.00 | 0.66 | 0.61 | 1870.60 | 16.29 | 87.33 | 341.17 | 964.50 | 16.83 | 72.00 | 304.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.64 | 0.61 | 01-JAN-07:00 | 5129.79 | 30.66 | 258.67 | 276.50 | 1082.07 | 20.86 | 85.17 | 263.83 |
February | 303.83 | 0.64 | 0.61 | 01-FEB-07:49 | 3017.09 | 25.55 | 194.00 | 267.83 | 951.25 | 15.65 | 0.00 | 237.33 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:40 | 1456.41 | 11.82 | 7.50 | 313.67 | 816.67 | 16.24 | 0.00 | 281.83 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:10 | 970.87 | 10.69 | 0.00 | 320.17 | 599.12 | 15.37 | 0.00 | 283.33 |
May | 406.00 | 0.65 | 0.61 | 01-MAY-06:49 | 820.44 | 10.20 | 0.00 | 338.33 | 503.68 | 14.93 | 0.00 | 296.17 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-06:00 | 814.96 | 9.80 | 0.00 | 325.33 | 487.88 | 14.43 | 0.00 | 277.67 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:40 | 927.68 | 9.80 | 0.00 | 322.50 | 500.61 | 14.39 | 0.00 | 265.00 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-06:49 | 1047.44 | 9.85 | 0.00 | 312.00 | 545.51 | 14.34 | 0.00 | 254.67 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-06:00 | 1271.35 | 10.62 | 0.00 | 294.00 | 684.03 | 15.28 | 0.00 | 250.67 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-06:00 | 2256.24 | 13.18 | 39.33 | 301.83 | 916.80 | 15.52 | 5.33 | 271.67 |
November | 317.83 | 0.64 | 0.61 | 01-NOV-07:19 | 7119.82 | 33.40 | 288.33 | 277.83 | 1124.81 | 18.13 | 45.17 | 263.67 |
December | 315.50 | 0.64 | 0.61 | 01-DEC-07:40 | 5415.31 | 32.19 | 273.33 | 276.17 | 1278.23 | 22.71 | 113.50 | 272.50 |
Annual Sum or Average | 4237.50 | 0.64 | 2368.86 | 16.58 | 1061.17 | 3626.17 | 769.57 | 16.33 | 249.17 | 3218.33 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 814.96 | 9.80 | 0.00 | 267.83 | 487.88 | 14.34 | 0.00 | 237.33 | |
Maximum of Months | 406.00 | 0.65 | 0.61 | 7119.82 | 33.40 | 288.33 | 338.33 | 1278.23 | 22.71 | 113.50 | 296.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.66 | 0.61 | 01-JAN-07:49 | 1401.67 | 15.59 | 84.33 | 251.83 | 733.67 | 15.13 | 55.17 | 201.33 |
February | 303.83 | 0.65 | 0.61 | 01-FEB-07:49 | 1742.37 | 15.20 | 75.33 | 245.50 | 969.07 | 16.85 | 70.00 | 201.83 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:40 | 1697.34 | 12.79 | 57.83 | 304.83 | 873.48 | 11.70 | 2.83 | 267.33 |
April | 379.83 | 0.65 | 0.61 | 01-APR-06:49 | 2033.75 | 8.41 | 0.00 | 314.83 | 1118.43 | 10.76 | 0.00 | 282.67 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-06:10 | 2100.13 | 8.44 | 0.00 | 344.33 | 827.95 | 10.76 | 0.00 | 305.17 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-06:40 | 1729.09 | 8.64 | 0.00 | 328.33 | 712.90 | 10.72 | 0.00 | 283.67 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:10 | 1390.42 | 9.09 | 0.00 | 327.17 | 635.96 | 10.92 | 0.00 | 264.33 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-06:19 | 1273.19 | 9.06 | 0.00 | 311.00 | 659.70 | 10.81 | 0.00 | 251.17 |
September | 344.33 | 0.65 | 0.61 | 01-SEP-06:49 | 1432.68 | 9.81 | 8.50 | 288.17 | 741.81 | 11.48 | 5.50 | 237.17 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-06:49 | 1572.17 | 14.63 | 81.83 | 283.50 | 797.95 | 14.51 | 55.50 | 244.17 |
November | 317.83 | 0.65 | 0.61 | 01-NOV-07:10 | 1329.00 | 13.74 | 59.00 | 253.67 | 732.15 | 15.55 | 56.50 | 214.67 |
December | 315.50 | 0.66 | 0.61 | 01-DEC-07:40 | 1464.34 | 16.14 | 87.83 | 247.33 | 822.71 | 17.80 | 79.83 | 210.17 |
Annual Sum or Average | 4237.50 | 0.65 | 1608.39 | 11.55 | 454.67 | 3500.50 | 801.39 | 12.87 | 325.33 | 2963.67 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 1273.19 | 8.41 | 0.00 | 245.50 | 635.96 | 10.72 | 0.00 | 201.33 | |
Maximum of Months | 406.00 | 0.66 | 0.61 | 2100.13 | 16.14 | 87.83 | 344.33 | 1118.43 | 17.80 | 79.83 | 305.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.67 | 0.61 | 01-JAN-08:39 | 440.97 | 0.00 | 0.00 | 221.50 | 288.80 | 0.00 | 0.00 | 117.17 |
February | 303.83 | 0.66 | 0.61 | 01-FEB-08:20 | 510.95 | 0.00 | 0.00 | 234.33 | 332.51 | 0.00 | 0.00 | 153.33 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:00 | 606.11 | 0.00 | 0.00 | 300.33 | 392.86 | 0.00 | 0.00 | 241.00 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:10 | 655.12 | 0.00 | 0.00 | 324.83 | 430.92 | 0.00 | 0.00 | 282.33 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-06:30 | 787.31 | 0.00 | 0.00 | 356.17 | 486.87 | 0.00 | 0.00 | 325.00 |
June | 386.67 | 0.64 | 0.61 | 01-JUN-06:49 | 880.04 | 0.00 | 0.00 | 340.50 | 515.77 | 0.00 | 0.00 | 304.50 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:19 | 904.08 | 0.00 | 0.00 | 334.17 | 491.50 | 0.00 | 0.00 | 281.67 |
August | 372.50 | 0.64 | 0.61 | 01-AUG-06:40 | 810.24 | 0.00 | 0.00 | 315.33 | 439.99 | 0.00 | 0.00 | 253.50 |
September | 344.33 | 0.65 | 0.61 | 01-SEP-06:00 | 696.04 | 0.00 | 0.00 | 289.00 | 405.31 | 0.00 | 0.00 | 221.00 |
October | 347.33 | 0.66 | 0.61 | 01-OCT-07:19 | 533.51 | 0.00 | 0.00 | 276.50 | 355.57 | 0.00 | 0.00 | 206.00 |
November | 317.83 | 0.66 | 0.61 | 01-NOV-07:49 | 447.82 | 0.00 | 0.00 | 233.00 | 312.70 | 0.00 | 0.00 | 144.33 |
December | 315.50 | 0.67 | 0.61 | 01-DEC-08:20 | 432.83 | 0.00 | 0.00 | 219.33 | 286.86 | 0.00 | 0.00 | 103.50 |
Annual Sum or Average | 4237.50 | 0.65 | 654.83 | 0.00 | 0.00 | 3445.00 | 401.36 | 0.00 | 0.00 | 2633.33 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 432.83 | 0.00 | 0.00 | 219.33 | 286.86 | 0.00 | 0.00 | 103.50 | |
Maximum of Months | 406.00 | 0.67 | 0.61 | 904.08 | 0.00 | 0.00 | 356.17 | 515.77 | 0.00 | 0.00 | 325.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.66 | 0.61 | 01-JAN-08:50 | 1406.46 | 15.57 | 82.83 | 249.33 | 762.50 | 16.83 | 72.00 | 204.17 |
February | 303.83 | 0.65 | 0.61 | 01-FEB-08:39 | 1656.59 | 15.11 | 77.00 | 246.67 | 682.26 | 14.81 | 44.33 | 205.67 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-08:09 | 1650.77 | 12.75 | 57.33 | 305.33 | 846.40 | 11.65 | 1.83 | 268.50 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:30 | 1870.45 | 8.41 | 0.00 | 318.83 | 965.12 | 10.77 | 0.00 | 283.17 |
May | 406.00 | 0.65 | 0.61 | 01-MAY-07:10 | 1792.07 | 8.44 | 0.00 | 341.17 | 961.41 | 10.74 | 0.00 | 304.83 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-07:10 | 1794.84 | 8.62 | 0.00 | 329.67 | 741.91 | 10.73 | 0.00 | 288.33 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:00 | 1348.05 | 9.11 | 0.00 | 324.50 | 624.69 | 10.94 | 0.00 | 268.33 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-07:10 | 1259.24 | 9.04 | 0.00 | 310.17 | 643.93 | 10.77 | 0.00 | 253.00 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-07:30 | 1405.74 | 9.86 | 8.50 | 290.00 | 717.85 | 11.54 | 5.50 | 240.50 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-07:30 | 1689.70 | 14.86 | 85.00 | 280.33 | 869.31 | 14.44 | 54.17 | 246.00 |
November | 317.83 | 0.65 | 0.61 | 01-NOV-07:00 | 1475.88 | 15.83 | 85.00 | 256.83 | 740.39 | 15.25 | 55.00 | 216.83 |
December | 315.50 | 0.65 | 0.61 | 01-DEC-08:20 | 1287.74 | 16.28 | 87.33 | 251.33 | 667.52 | 15.64 | 56.33 | 208.50 |
Annual Sum or Average | 4237.50 | 0.65 | 1560.73 | 11.73 | 483.00 | 3504.17 | 772.92 | 12.66 | 289.17 | 2987.83 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 1259.24 | 8.41 | 0.00 | 246.67 | 624.69 | 10.73 | 0.00 | 204.17 | |
Maximum of Months | 406.00 | 0.66 | 0.61 | 1870.45 | 16.28 | 87.33 | 341.17 | 965.12 | 16.83 | 72.00 | 304.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 9289584.61 | 2187.61 | 05-JAN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5407126.38 | 1406.81 | 23-DEC-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14696711.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9289584.61 | 2187.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148577E+10 | 48618.94 | 05-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 705417.59 | 793.05 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.403160E+09 | 32724.15 | 21-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148577E+10 | 48618.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144119E+10 | 36830.44 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127732E+09 | 18595.42 | 11-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.417489E+09 | 54282.01 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144119E+10 | 54282.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.698593E+09 | 33413.02 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114089E+09 | 16456.67 | 11-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228041E+09 | 35672.38 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.698593E+09 | 35672.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 21434756.99 | 5489.90 | 03-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43345650.50 | 14802.39 | 11-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64780407.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43345650.50 | 14802.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.650368E+09 | 20942.91 | 02-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 99794552.68 | 15495.28 | 11-FEB-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188810E+09 | 19186.18 | 23-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.938972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.650368E+09 | 20942.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110795E+10 | 12395.21 | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 79686612.90 | 6165.88 | 02-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263313E+09 | 11673.30 | 23-DEC-05:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110795E+10 | 12395.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.499266E+09 | 72331.39 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.499266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.499266E+09 | 72331.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.166130E+10 | 18850.48 | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.395577E+09 | 18567.81 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1854131.43 | 503.80 | 01-MAR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 64166451.96 | 3676.09 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.962798E+09 | 18667.45 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.308569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.166130E+10 | 18850.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.727174E+09 | 13276.34 | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171514E+09 | 13075.36 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 212782.67 | 183.82 | 01-MAR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19177636.26 | 1965.31 | 27-NOV-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.430842E+09 | 13139.61 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.727174E+09 | 13276.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.547569E+09 | 18767.79 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133029E+09 | 18587.29 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218993E+09 | 16839.66 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.899590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.547569E+09 | 18767.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.775182E+09 | 13171.09 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198498E+09 | 13043.70 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14826396.31 | 997.49 | 25-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.412591E+09 | 11643.62 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.775182E+09 | 13171.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.551477E+11 | 0.550594E+11 | 124272.76 | 02-JAN-06:03 | 81435.71 | 0.31 |
February | 0.00 | 0.00 | 0.727524E+11 | 0.725854E+11 | 152978.55 | 25-FEB-04:02 | 109610.20 | 0.49 |
March | 0.00 | 0.00 | 0.129389E+12 | 0.127435E+12 | 218056.73 | 29-MAR-05:02 | 153225.56 | 0.67 |
April | 0.00 | 0.00 | 0.185927E+12 | 0.179024E+12 | 266193.40 | 17-APR-05:03 | 185838.51 | 0.81 |
May | 0.00 | 0.00 | 0.225479E+12 | 0.192353E+12 | 281586.37 | 22-MAY-05:02 | 180519.56 | 0.82 |
June | 0.00 | 0.00 | 0.264382E+12 | 0.197548E+12 | 301171.54 | 29-JUN-05:02 | 177714.34 | 0.84 |
July | 0.00 | 0.00 | 0.305430E+12 | 0.191305E+12 | 305776.95 | 17-JUL-05:03 | 186611.97 | 0.86 |
August | 0.00 | 0.00 | 0.330330E+12 | 0.203546E+12 | 311690.62 | 28-AUG-05:03 | 183803.46 | 0.89 |
September | 0.00 | 0.00 | 0.227887E+12 | 0.148271E+12 | 290773.28 | 05-SEP-03:02 | 178538.81 | 0.75 |
October | 0.00 | 0.00 | 0.156275E+12 | 0.139563E+12 | 262460.46 | 04-OCT-05:02 | 172680.96 | 0.73 |
November | 0.00 | 0.00 | 0.107927E+12 | 0.106676E+12 | 171389.39 | 06-NOV-06:03 | 139989.89 | 0.63 |
December | 0.00 | 0.00 | 0.763068E+11 | 0.763068E+11 | 117445.95 | 29-DEC-06:03 | 117445.95 | 0.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.213723E+13 | 0.168967E+13 | 0.68 | |||
Minimum of Months | 0.00 | 0.00 | 0.551477E+11 | 0.550594E+11 | 117445.95 | 81435.71 | 0.31 | |
Maximum of Months | 0.00 | 0.00 | 0.330330E+12 | 0.203546E+12 | 311690.62 | 186611.97 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.399574E+12 | 0.399137E+12 | 1039018.35 | 18-JAN-06:02 | 826873.97 | 0.30 |
February | 0.00 | 0.00 | 0.539654E+12 | 0.538463E+12 | 1442929.56 | 25-FEB-06:02 | 999008.09 | 0.44 |
March | 0.00 | 0.00 | 0.998560E+12 | 0.984494E+12 | 2153112.37 | 11-MAR-06:02 | 1551814.83 | 0.57 |
April | 0.00 | 0.00 | 0.144127E+13 | 0.139021E+13 | 2321106.57 | 27-APR-05:03 | 1705165.89 | 0.65 |
May | 0.00 | 0.00 | 0.206128E+13 | 0.174580E+13 | 2827145.56 | 24-MAY-03:02 | 1616577.22 | 0.78 |
June | 0.00 | 0.00 | 0.233610E+13 | 0.171968E+13 | 2944871.51 | 27-JUN-05:03 | 1679413.12 | 0.78 |
July | 0.00 | 0.00 | 0.255859E+13 | 0.154365E+13 | 3275022.81 | 20-JUL-03:02 | 1663227.92 | 0.75 |
August | 0.00 | 0.00 | 0.254024E+13 | 0.148349E+13 | 2990989.56 | 11-AUG-03:02 | 1616253.80 | 0.73 |
September | 0.00 | 0.00 | 0.198051E+13 | 0.126414E+13 | 2943218.74 | 11-SEP-03:02 | 1620852.87 | 0.67 |
October | 0.00 | 0.00 | 0.128008E+13 | 0.113594E+13 | 2474623.86 | 04-OCT-05:02 | 1624675.56 | 0.64 |
November | 0.00 | 0.00 | 0.801234E+12 | 0.792170E+12 | 1599715.86 | 09-NOV-06:03 | 1082554.35 | 0.56 |
December | 0.00 | 0.00 | 0.466031E+12 | 0.466031E+12 | 898420.44 | 29-DEC-06:03 | 898420.44 | 0.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.174031E+14 | 0.134632E+14 | 0.60 | |||
Minimum of Months | 0.00 | 0.00 | 0.399574E+12 | 0.399137E+12 | 898420.44 | 826873.97 | 0.30 | |
Maximum of Months | 0.00 | 0.00 | 0.255859E+13 | 0.174580E+13 | 3275022.81 | 1705165.89 | 0.78 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.292588E+11 | 0.292482E+11 | 67572.36 | 12-JAN-15:30 | 67572.36 | 0.27 |
February | 0.00 | 0.00 | 0.477579E+11 | 0.476534E+11 | 130621.65 | 25-FEB-06:02 | 88612.94 | 0.42 |
March | 0.00 | 0.00 | 0.102628E+12 | 0.101264E+12 | 215562.06 | 11-MAR-06:02 | 156297.93 | 0.55 |
April | 0.00 | 0.00 | 0.162918E+12 | 0.157648E+12 | 253548.83 | 27-APR-05:03 | 186687.28 | 0.67 |
May | 0.00 | 0.00 | 0.236869E+12 | 0.203960E+12 | 306118.38 | 24-MAY-03:02 | 178899.05 | 0.80 |
June | 0.00 | 0.00 | 0.265561E+12 | 0.201746E+12 | 322630.92 | 23-JUN-05:02 | 196905.72 | 0.80 |
July | 0.00 | 0.00 | 0.283916E+12 | 0.178471E+12 | 331090.40 | 22-JUL-05:03 | 190874.73 | 0.77 |
August | 0.00 | 0.00 | 0.276710E+12 | 0.167952E+12 | 323165.85 | 12-AUG-03:02 | 186409.65 | 0.75 |
September | 0.00 | 0.00 | 0.213524E+12 | 0.139667E+12 | 335060.70 | 11-SEP-03:02 | 185105.53 | 0.68 |
October | 0.00 | 0.00 | 0.132816E+12 | 0.119173E+12 | 243803.48 | 04-OCT-03:02 | 161741.40 | 0.63 |
November | 0.00 | 0.00 | 0.744814E+11 | 0.740300E+11 | 145290.04 | 10-NOV-06:02 | 101398.25 | 0.53 |
December | 0.00 | 0.00 | 0.357410E+11 | 0.357410E+11 | 74196.35 | 01-DEC-15:00 | 74196.35 | 0.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.186218E+13 | 0.145655E+13 | 0.60 | |||
Minimum of Months | 0.00 | 0.00 | 0.292588E+11 | 0.292482E+11 | 67572.36 | 67572.36 | 0.27 | |
Maximum of Months | 0.00 | 0.00 | 0.283916E+12 | 0.203960E+12 | 335060.70 | 196905.72 | 0.80 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.560333E+11 | 0.559598E+11 | 110961.60 | 18-JAN-04:03 | 88544.27 | 0.31 |
February | 0.00 | 0.00 | 0.573217E+11 | 0.572663E+11 | 129214.42 | 25-FEB-04:02 | 91034.56 | 0.46 |
March | 0.00 | 0.00 | 0.787844E+11 | 0.785347E+11 | 162720.99 | 11-MAR-04:02 | 96672.73 | 0.54 |
April | 0.00 | 0.00 | 0.900437E+11 | 0.881115E+11 | 168329.96 | 27-APR-03:02 | 103432.25 | 0.53 |
May | 0.00 | 0.00 | 0.115380E+12 | 0.103035E+12 | 201736.51 | 22-MAY-03:02 | 98357.54 | 0.61 |
June | 0.00 | 0.00 | 0.134888E+12 | 0.107085E+12 | 225203.45 | 26-JUN-03:02 | 90967.26 | 0.63 |
July | 0.00 | 0.00 | 0.155844E+12 | 0.106407E+12 | 245465.76 | 30-JUL-20:57 | 96221.69 | 0.63 |
August | 0.00 | 0.00 | 0.174314E+12 | 0.115266E+12 | 257505.02 | 27-AUG-14:59 | 103362.04 | 0.68 |
September | 0.00 | 0.00 | 0.139122E+12 | 0.996875E+11 | 239604.66 | 11-SEP-00:22 | 94365.29 | 0.65 |
October | 0.00 | 0.00 | 0.101533E+12 | 0.947397E+11 | 179649.53 | 04-OCT-03:02 | 102088.10 | 0.64 |
November | 0.00 | 0.00 | 0.787329E+11 | 0.784526E+11 | 140973.37 | 09-NOV-04:03 | 91288.51 | 0.58 |
December | 0.00 | 0.00 | 0.635985E+11 | 0.635899E+11 | 106326.79 | 30-DEC-04:02 | 85325.49 | 0.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.124560E+13 | 0.104814E+13 | 0.55 | |||
Minimum of Months | 0.00 | 0.00 | 0.560333E+11 | 0.559598E+11 | 106326.79 | 85325.49 | 0.31 | |
Maximum of Months | 0.00 | 0.00 | 0.174314E+12 | 0.115266E+12 | 257505.02 | 103432.25 | 0.68 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.338687E+12 | 0.325039E+12 | 132584.48 | 17-JAN-17:00 | 125711.52 | 0.00 |
February | 0.00 | 0.00 | 0.534019E+12 | 0.517130E+12 | 226157.43 | 24-FEB-17:00 | 220120.41 | 0.00 |
March | 0.00 | 0.00 | 0.836897E+12 | 0.822943E+12 | 396209.03 | 31-MAR-24:00 | 393969.12 | 0.00 |
April | 0.00 | 0.00 | 0.103528E+13 | 0.102909E+13 | 410074.23 | 25-APR-04:55 | 402292.70 | 0.00 |
May | 0.00 | 0.00 | 0.363541E+12 | 0.346709E+12 | 226648.48 | 31-MAY-23:03 | 212595.43 | 0.00 |
June | 0.00 | 0.00 | 0.599562E+12 | 0.573831E+12 | 318783.06 | 30-JUN-23:02 | 306809.50 | 0.00 |
July | 0.00 | 0.00 | 0.874908E+12 | 0.838308E+12 | 402165.42 | 31-JUL-24:00 | 390442.05 | 0.00 |
August | 0.00 | 0.00 | 0.110066E+13 | 0.106513E+13 | 422167.53 | 10-AUG-14:00 | 402368.36 | 0.00 |
September | 0.00 | 0.00 | 0.367475E+12 | 0.336224E+12 | 227309.79 | 30-SEP-23:05 | 213126.49 | 0.00 |
October | 0.00 | 0.00 | 0.602836E+12 | 0.586451E+12 | 311062.02 | 31-OCT-24:00 | 302638.89 | 0.00 |
November | 0.00 | 0.00 | 0.818523E+12 | 0.799030E+12 | 321970.29 | 24-NOV-08:15 | 307788.00 | 0.00 |
December | 0.00 | 0.00 | 0.110010E+13 | 0.106551E+13 | 422262.40 | 22-DEC-06:03 | 396692.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.857248E+13 | 0.830540E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.338687E+12 | 0.325039E+12 | 132584.48 | 125711.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.110066E+13 | 0.106551E+13 | 422262.40 | 402368.36 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.500855E+10 | 0.486377E+10 | 2535.93 | 12-JAN-17:00 | 2405.11 | 0.00 |
February | 0.00 | 0.00 | 0.962832E+10 | 0.940246E+10 | 4586.17 | 21-FEB-17:00 | 4436.12 | 0.00 |
March | 0.00 | 0.00 | 0.162732E+11 | 0.159437E+11 | 7794.97 | 31-MAR-24:00 | 7695.27 | 0.00 |
April | 0.00 | 0.00 | 0.210003E+11 | 0.206930E+11 | 8548.31 | 16-APR-20:54 | 8292.25 | 0.00 |
May | 0.00 | 0.00 | 0.725726E+10 | 0.659478E+10 | 4650.35 | 31-MAY-23:03 | 4042.97 | 0.00 |
June | 0.00 | 0.00 | 0.123709E+11 | 0.112895E+11 | 6545.17 | 30-JUN-23:02 | 6030.46 | 0.00 |
July | 0.00 | 0.00 | 0.182093E+11 | 0.166004E+11 | 8653.05 | 31-JUL-23:02 | 7844.40 | 0.00 |
August | 0.00 | 0.00 | 0.229816E+11 | 0.212870E+11 | 8877.56 | 10-AUG-14:10 | 8058.43 | 0.00 |
September | 0.00 | 0.00 | 0.739861E+10 | 0.612792E+10 | 4621.76 | 30-SEP-23:05 | 4003.81 | 0.00 |
October | 0.00 | 0.00 | 0.117609E+11 | 0.111429E+11 | 5988.36 | 31-OCT-23:10 | 5739.75 | 0.00 |
November | 0.00 | 0.00 | 0.156218E+11 | 0.153125E+11 | 6643.26 | 08-NOV-16:40 | 6389.67 | 0.00 |
December | 0.00 | 0.00 | 0.205933E+11 | 0.204236E+11 | 8318.76 | 28-DEC-17:00 | 8158.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168104E+12 | 0.159682E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.500855E+10 | 0.486377E+10 | 2535.93 | 2405.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.229816E+11 | 0.212870E+11 | 8877.56 | 8292.25 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.378506E+11 | 0.364888E+11 | 23519.28 | 13-JAN-17:00 | 21624.62 | 0.00 |
February | 0.00 | 0.00 | 0.857714E+11 | 0.835400E+11 | 43267.32 | 22-FEB-17:00 | 41734.44 | 0.00 |
March | 0.00 | 0.00 | 0.153635E+12 | 0.150352E+12 | 75278.30 | 31-MAR-24:00 | 74275.81 | 0.00 |
April | 0.00 | 0.00 | 0.199385E+12 | 0.196304E+12 | 81280.53 | 12-APR-16:00 | 79024.97 | 0.00 |
May | 0.00 | 0.00 | 0.684750E+11 | 0.619288E+11 | 44872.84 | 31-MAY-23:03 | 38613.76 | 0.00 |
June | 0.00 | 0.00 | 0.117971E+12 | 0.107217E+12 | 63359.21 | 30-JUN-23:02 | 58169.03 | 0.00 |
July | 0.00 | 0.00 | 0.173886E+12 | 0.157845E+12 | 82778.59 | 31-JUL-23:02 | 74714.26 | 0.00 |
August | 0.00 | 0.00 | 0.218200E+12 | 0.201224E+12 | 84519.27 | 10-AUG-14:10 | 76367.98 | 0.00 |
September | 0.00 | 0.00 | 0.696018E+11 | 0.570511E+11 | 45100.20 | 30-SEP-23:05 | 38758.11 | 0.00 |
October | 0.00 | 0.00 | 0.110715E+12 | 0.104585E+12 | 56464.50 | 31-OCT-23:10 | 53907.70 | 0.00 |
November | 0.00 | 0.00 | 0.144834E+12 | 0.141754E+12 | 63051.60 | 08-NOV-16:50 | 60450.04 | 0.00 |
December | 0.00 | 0.00 | 0.187626E+12 | 0.185929E+12 | 78455.51 | 28-DEC-17:00 | 76860.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156795E+13 | 0.148422E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.378506E+11 | 0.364888E+11 | 23519.28 | 21624.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.218200E+12 | 0.201224E+12 | 84519.27 | 79024.97 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.236917E+10 | 0.224348E+10 | 2366.30 | 12-JAN-17:00 | 2229.68 | 0.00 |
February | 0.00 | 0.00 | 0.790104E+10 | 0.766512E+10 | 4374.65 | 22-FEB-17:00 | 4213.59 | 0.00 |
March | 0.00 | 0.00 | 0.151950E+11 | 0.148479E+11 | 7484.67 | 31-MAR-24:00 | 7377.20 | 0.00 |
April | 0.00 | 0.00 | 0.200991E+11 | 0.197737E+11 | 8328.97 | 16-APR-20:45 | 8058.99 | 0.00 |
May | 0.00 | 0.00 | 0.708995E+10 | 0.641440E+10 | 4470.53 | 31-MAY-23:03 | 3829.93 | 0.00 |
June | 0.00 | 0.00 | 0.120234E+11 | 0.109277E+11 | 6403.03 | 30-JUN-23:02 | 5874.74 | 0.00 |
July | 0.00 | 0.00 | 0.176142E+11 | 0.159897E+11 | 8401.04 | 31-JUL-23:02 | 7577.21 | 0.00 |
August | 0.00 | 0.00 | 0.221336E+11 | 0.204100E+11 | 8626.26 | 10-AUG-14:10 | 7796.95 | 0.00 |
September | 0.00 | 0.00 | 0.704468E+10 | 0.577045E+10 | 4502.76 | 30-SEP-23:05 | 3859.66 | 0.00 |
October | 0.00 | 0.00 | 0.109998E+11 | 0.103688E+11 | 5526.58 | 31-OCT-23:10 | 5258.66 | 0.00 |
November | 0.00 | 0.00 | 0.139896E+11 | 0.136645E+11 | 6368.32 | 08-NOV-16:40 | 6109.16 | 0.00 |
December | 0.00 | 0.00 | 0.176063E+11 | 0.174211E+11 | 7856.84 | 28-DEC-17:00 | 7689.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.154066E+12 | 0.145497E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.236917E+10 | 0.224348E+10 | 2366.30 | 2229.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.221336E+11 | 0.204100E+11 | 8626.26 | 8058.99 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 3499.52 | 214389.78 | 03-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 553.27 | 121606.28 | 11-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.72 | 642.83 | 01-MAR-06:50 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 37.16 | 5007.30 | 27-NOV-06:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1308.34 | 195903.17 | 21-DEC-06:02 |
Annual Sum or Average | 0.00 | 453.90 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 3499.52 | 214389.78 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 411691.87 | 1576675.02 | 25-JAN-15:10 | 15.24 | 79654.43 | 30-JAN-03:25 |
February | 533734.27 | 1686102.13 | 25-FEB-06:02 | 226.75 | 403043.43 | 06-FEB-02:55 |
March | 759702.12 | 2062647.19 | 11-MAR-06:02 | 6.17 | 75056.23 | 05-MAR-08:62 |
April | 1010586.50 | 3172067.73 | 17-APR-05:03 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1236806.15 | 3470543.18 | 24-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1335682.18 | 3479936.18 | 14-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1376548.86 | 3577045.24 | 25-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1365252.90 | 4050799.93 | 07-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1126118.84 | 4340337.56 | 05-SEP-05:04 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 885693.57 | 3280572.65 | 04-OCT-05:02 | 11.08 | 104806.99 | 28-OCT-20:42 |
November | 659670.46 | 1674325.97 | 06-NOV-13:10 | 19.41 | 80784.30 | 26-NOV-20:45 |
December | 472196.23 | 1591082.45 | 01-DEC-15:20 | 0.58 | 10298.37 | 03-DEC-17:42 |
Annual Sum or Average | 933290.25 | 21.80 | ||||
Minimum of Months | 411691.87 | 1576675.02 | 0.00 | 0.00 | ||
Maximum of Months | 1376548.86 | 4340337.56 | 226.75 | 403043.43 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 266398.89 | 2053215.46 | 18-JAN-06:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 373616.31 | 2821064.45 | 25-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 575436.73 | 3728296.69 | 11-MAR-06:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 796015.36 | 4177766.42 | 17-APR-05:02 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1040063.26 | 4956669.74 | 24-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1206173.90 | 5004998.43 | 23-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1272885.70 | 5127806.82 | 31-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1275799.08 | 5149122.84 | 28-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1037190.49 | 5175404.37 | 05-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 695245.46 | 4747675.18 | 04-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 500564.00 | 3037722.87 | 09-NOV-06:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 316610.20 | 1899994.18 | 29-DEC-06:03 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 781849.83 | 0.00 | ||||
Minimum of Months | 266398.89 | 1899994.18 | 0.00 | 0.00 | ||
Maximum of Months | 1275799.08 | 5175404.37 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 222968.87 | 587948.98 | 12-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 500647.69 | 1023886.66 | 22-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 970475.90 | 1771608.43 | 28-MAR-15:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1594566.23 | 2235167.67 | 15-APR-15:00 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1125053.44 | 1788767.04 | 01-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1418913.01 | 2077062.60 | 08-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1562214.74 | 2099724.66 | 07-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1677298.29 | 2097242.06 | 07-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 903977.83 | 1401087.29 | 17-SEP-20:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 909464.99 | 1585426.29 | 02-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 824512.51 | 1432582.66 | 08-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 790137.70 | 1330929.74 | 28-DEC-14:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1044556.86 | 0.00 | ||||
Minimum of Months | 222968.87 | 587948.98 | 0.00 | 0.00 | ||
Maximum of Months | 1677298.29 | 2235167.67 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 12736.38 | 41939.78 | 18-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 12565.30 | 41685.69 | 01-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 12460.90 | 39954.81 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:03 | 10707.24 | 36293.94 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 9907.69 | 32609.11 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9215.80 | 29022.62 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 8271.59 | 26830.22 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 9179.75 | 28572.30 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 9468.39 | 31771.68 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 10512.63 | 35911.19 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 11729.89 | 39429.38 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12146.27 | 41510.39 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 10731.89 | ||||
Minimum of Months | 0.00 | 0.00 | 8271.59 | 26830.22 | ||
Maximum of Months | 0.00 | 0.00 | 12736.38 | 41939.78 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 244589.05 | 1138789.27 | 25-JAN-15:50 | 2780.89 | 142006.95 | 21-JAN-06:30 |
February | 351751.30 | 1572203.41 | 25-FEB-06:02 | 952.10 | 132838.06 | 02-FEB-07:00 |
March | 605254.13 | 3340521.99 | 10-MAR-17:00 | 210.17 | 78791.98 | 01-MAR-04:30 |
April | 1095135.57 | 5094516.93 | 18-APR-14:00 | 116.49 | 31528.10 | 09-APR-23:27 |
May | 2269400.51 | 6858010.74 | 17-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 3402094.33 | 7900866.08 | 22-JUN-15:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 4395535.27 | 7926461.46 | 31-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 4401664.96 | 7980936.25 | 28-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3000791.17 | 7547560.56 | 14-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 982297.67 | 4800260.76 | 04-OCT-05:04 | 29.97 | 30147.33 | 30-OCT-01:50 |
November | 487846.39 | 2764266.70 | 13-NOV-14:30 | 493.63 | 84869.05 | 27-NOV-03:30 |
December | 287802.45 | 1182753.60 | 01-DEC-15:40 | 1490.54 | 144666.78 | 23-DEC-07:00 |
Annual Sum or Average | 1803309.38 | 506.36 | ||||
Minimum of Months | 244589.05 | 1138789.27 | 0.00 | 0.00 | ||
Maximum of Months | 4401664.96 | 7980936.25 | 2780.89 | 144666.78 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167064E+11 | 0.87 | 10174.45 | 01-JAN-00:20 | 1.42 |
February | 0.148366E+11 | 0.85 | 10174.45 | 01-FEB-04:03 | 1.42 |
March | 0.167797E+11 | 0.87 | 10174.45 | 01-MAR-04:02 | 1.42 |
April | 0.156489E+11 | 0.84 | 10174.45 | 01-APR-03:02 | 1.42 |
May | 0.167857E+11 | 0.87 | 10174.45 | 01-MAY-00:03 | 1.42 |
June | 0.168586E+11 | 0.90 | 10174.45 | 01-JUN-03:02 | 1.41 |
July | 0.174745E+11 | 0.90 | 10174.45 | 01-JUL-03:02 | 1.41 |
August | 0.186617E+11 | 0.96 | 10174.45 | 01-AUG-03:02 | 1.41 |
September | 0.175204E+11 | 0.93 | 10174.45 | 01-SEP-03:02 | 1.41 |
October | 0.180738E+11 | 0.93 | 10174.45 | 01-OCT-09:25 | 1.40 |
November | 0.173156E+11 | 0.93 | 10174.45 | 01-NOV-03:02 | 1.41 |
December | 0.171902E+11 | 0.89 | 10174.45 | 01-DEC-04:02 | 1.42 |
Annual Sum or Average | 0.203852E+12 | 0.90 | |||
Minimum of Months | 0.148366E+11 | 0.84 | 10174.45 | 1.40 | |
Maximum of Months | 0.186617E+11 | 0.96 | 10174.45 | 1.42 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.613777E+10 | 0.37 | 10149.55 | 02-JAN-04:02 | 1.10 |
February | 0.711973E+10 | 0.44 | 13970.45 | 21-FEB-06:03 | 1.34 |
March | 0.111338E+11 | 0.57 | 22171.70 | 14-MAR-05:03 | 1.79 |
April | 0.138470E+11 | 0.70 | 22171.70 | 17-APR-04:22 | 1.79 |
May | 0.132897E+11 | 0.65 | 22171.70 | 01-MAY-04:22 | 1.79 |
June | 0.140456E+11 | 0.69 | 22171.70 | 05-JUN-05:02 | 1.79 |
July | 0.141774E+11 | 0.69 | 22171.70 | 01-JUL-05:03 | 1.79 |
August | 0.173631E+11 | 0.78 | 22171.70 | 07-AUG-05:01 | 1.79 |
September | 0.109296E+11 | 0.57 | 22171.70 | 06-SEP-05:03 | 1.79 |
October | 0.105351E+11 | 0.55 | 22171.70 | 03-OCT-05:03 | 1.79 |
November | 0.930219E+10 | 0.50 | 19023.46 | 06-NOV-06:03 | 1.63 |
December | 0.842569E+10 | 0.45 | 13874.36 | 29-DEC-06:03 | 1.33 |
Annual Sum or Average | 0.136307E+12 | 0.58 | |||
Minimum of Months | 0.613777E+10 | 0.37 | 10149.55 | 1.10 | |
Maximum of Months | 0.173631E+11 | 0.78 | 22171.70 | 1.79 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.449800E+11 | 0.32 | 97039.59 | 02-JAN-06:01 | 1.11 |
February | 0.499375E+11 | 0.37 | 114060.78 | 21-FEB-06:03 | 1.23 |
March | 0.793905E+11 | 0.46 | 210958.08 | 11-MAR-06:02 | 1.80 |
April | 0.981349E+11 | 0.55 | 210958.08 | 15-APR-05:03 | 1.80 |
May | 0.113842E+12 | 0.61 | 210958.08 | 03-MAY-05:03 | 1.80 |
June | 0.112808E+12 | 0.61 | 210958.08 | 01-JUN-05:03 | 1.80 |
July | 0.102204E+12 | 0.56 | 210958.08 | 05-JUL-05:02 | 1.80 |
August | 0.106187E+12 | 0.57 | 210958.08 | 01-AUG-05:03 | 1.80 |
September | 0.894786E+11 | 0.51 | 210958.08 | 02-SEP-05:03 | 1.80 |
October | 0.782988E+11 | 0.46 | 210958.08 | 03-OCT-05:03 | 1.80 |
November | 0.611042E+11 | 0.40 | 128423.05 | 13-NOV-06:02 | 1.32 |
December | 0.484460E+11 | 0.34 | 97039.59 | 01-DEC-05:03 | 1.11 |
Annual Sum or Average | 0.984812E+12 | 0.48 | |||
Minimum of Months | 0.449800E+11 | 0.32 | 97039.59 | 1.11 | |
Maximum of Months | 0.113842E+12 | 0.61 | 210958.08 | 1.80 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.346403E+10 | 0.28 | 4945.93 | 12-JAN-15:30 | 0.70 |
February | 0.405743E+10 | 0.31 | 8982.37 | 09-FEB-06:02 | 0.98 |
March | 0.749354E+10 | 0.41 | 20639.43 | 30-MAR-05:02 | 1.64 |
April | 0.108785E+11 | 0.55 | 23699.52 | 17-APR-05:02 | 1.79 |
May | 0.134300E+11 | 0.63 | 23699.52 | 01-MAY-05:02 | 1.79 |
June | 0.134036E+11 | 0.64 | 23699.52 | 03-JUN-05:02 | 1.79 |
July | 0.115360E+11 | 0.57 | 23699.52 | 01-JUL-05:03 | 1.79 |
August | 0.114524E+11 | 0.56 | 23699.52 | 01-AUG-05:03 | 1.79 |
September | 0.937494E+10 | 0.49 | 23699.52 | 11-SEP-03:02 | 1.79 |
October | 0.787926E+10 | 0.43 | 18614.79 | 04-OCT-03:02 | 1.54 |
November | 0.540165E+10 | 0.35 | 11669.82 | 10-NOV-06:02 | 1.15 |
December | 0.365090E+10 | 0.28 | 8982.37 | 29-DEC-06:03 | 0.98 |
Annual Sum or Average | 0.102022E+12 | 0.46 | |||
Minimum of Months | 0.346403E+10 | 0.28 | 4945.93 | 0.70 | |
Maximum of Months | 0.134300E+11 | 0.64 | 23699.52 | 1.79 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.970462E+11 | 1.38 | 36232.89 | 01-JAN-00:05 | 1.38 |
February | 0.876546E+11 | 1.38 | 36232.89 | 01-FEB-00:10 | 1.38 |
March | 0.970462E+11 | 1.38 | 36232.89 | 01-MAR-00:10 | 1.38 |
April | 0.939157E+11 | 1.38 | 36232.89 | 01-APR-00:03 | 1.38 |
May | 0.970462E+11 | 1.38 | 36232.89 | 01-MAY-00:03 | 1.38 |
June | 0.939157E+11 | 1.38 | 36232.89 | 01-JUN-00:10 | 1.38 |
July | 0.970462E+11 | 1.38 | 36232.89 | 01-JUL-00:03 | 1.38 |
August | 0.970462E+11 | 1.38 | 36232.89 | 01-AUG-00:03 | 1.38 |
September | 0.939157E+11 | 1.38 | 36232.89 | 01-SEP-00:05 | 1.38 |
October | 0.970462E+11 | 1.38 | 36232.89 | 01-OCT-00:03 | 1.38 |
November | 0.939157E+11 | 1.38 | 36232.89 | 01-NOV-00:10 | 1.38 |
December | 0.970462E+11 | 1.38 | 36232.89 | 01-DEC-00:10 | 1.38 |
Annual Sum or Average | 0.114264E+13 | 1.38 | |||
Minimum of Months | 0.876546E+11 | 1.38 | 36232.89 | 1.38 | |
Maximum of Months | 0.970462E+11 | 1.38 | 36232.89 | 1.38 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147086E+10 | 0.94 | 549.15 | 01-JAN-00:05 | 0.94 |
February | 0.132851E+10 | 0.94 | 549.15 | 01-FEB-00:10 | 0.94 |
March | 0.147086E+10 | 0.94 | 549.15 | 01-MAR-00:10 | 0.94 |
April | 0.142341E+10 | 0.94 | 549.15 | 01-APR-00:03 | 0.94 |
May | 0.147086E+10 | 0.93 | 549.15 | 01-MAY-00:03 | 0.94 |
June | 0.142341E+10 | 0.93 | 549.15 | 01-JUN-00:10 | 0.94 |
July | 0.147086E+10 | 0.93 | 549.15 | 01-JUL-00:03 | 0.93 |
August | 0.147086E+10 | 0.93 | 549.15 | 01-AUG-00:03 | 0.94 |
September | 0.142341E+10 | 0.93 | 549.15 | 01-SEP-00:05 | 0.93 |
October | 0.147086E+10 | 0.94 | 549.15 | 01-OCT-00:07 | 0.94 |
November | 0.142341E+10 | 0.94 | 549.15 | 01-NOV-00:10 | 0.94 |
December | 0.147086E+10 | 0.94 | 549.15 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.173181E+11 | 0.94 | |||
Minimum of Months | 0.132851E+10 | 0.93 | 549.15 | 0.93 | |
Maximum of Months | 0.147086E+10 | 0.94 | 549.15 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140096E+11 | 0.94 | 5230.57 | 01-JAN-00:05 | 0.94 |
February | 0.126538E+11 | 0.94 | 5230.57 | 01-FEB-00:10 | 0.94 |
March | 0.140096E+11 | 0.94 | 5230.57 | 01-MAR-00:10 | 0.94 |
April | 0.135576E+11 | 0.94 | 5230.57 | 01-APR-00:03 | 0.94 |
May | 0.140096E+11 | 0.93 | 5230.57 | 01-MAY-00:03 | 0.94 |
June | 0.135576E+11 | 0.93 | 5230.57 | 01-JUN-00:10 | 0.94 |
July | 0.140096E+11 | 0.93 | 5230.57 | 01-JUL-00:03 | 0.93 |
August | 0.140096E+11 | 0.93 | 5230.57 | 01-AUG-00:03 | 0.93 |
September | 0.135576E+11 | 0.93 | 5230.57 | 01-SEP-00:05 | 0.93 |
October | 0.140096E+11 | 0.94 | 5230.57 | 01-OCT-00:03 | 0.94 |
November | 0.135576E+11 | 0.94 | 5230.57 | 01-NOV-00:10 | 0.94 |
December | 0.140096E+11 | 0.94 | 5230.57 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.164951E+12 | 0.94 | |||
Minimum of Months | 0.126538E+11 | 0.93 | 5230.57 | 0.93 | |
Maximum of Months | 0.140096E+11 | 0.94 | 5230.57 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140937E+10 | 0.94 | 526.20 | 01-JAN-00:05 | 0.94 |
February | 0.127298E+10 | 0.94 | 526.20 | 01-FEB-00:10 | 0.94 |
March | 0.140937E+10 | 0.94 | 526.20 | 01-MAR-00:10 | 0.94 |
April | 0.136391E+10 | 0.94 | 526.20 | 01-APR-00:03 | 0.94 |
May | 0.140937E+10 | 0.93 | 526.20 | 01-MAY-00:03 | 0.94 |
June | 0.136391E+10 | 0.93 | 526.20 | 01-JUN-00:10 | 0.94 |
July | 0.140937E+10 | 0.93 | 526.20 | 01-JUL-00:03 | 0.94 |
August | 0.140937E+10 | 0.93 | 526.20 | 01-AUG-00:03 | 0.94 |
September | 0.136391E+10 | 0.93 | 526.20 | 01-SEP-00:05 | 0.93 |
October | 0.140937E+10 | 0.94 | 526.20 | 01-OCT-00:03 | 0.94 |
November | 0.136391E+10 | 0.94 | 526.20 | 01-NOV-00:10 | 0.94 |
December | 0.140937E+10 | 0.94 | 526.20 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.165942E+11 | 0.94 | |||
Minimum of Months | 0.127298E+10 | 0.93 | 526.20 | 0.93 | |
Maximum of Months | 0.140937E+10 | 0.94 | 526.20 | 0.94 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 42491359.24 | 38242223.31 | 1119.14 | 02-JAN-06:03 | 1007.23 | 1007.23 | 46.58 | 1.33 |
February | 5533847.06 | 4980462.35 | 467.83 | 11-FEB-06:02 | 421.05 | 421.05 | 22.17 | 0.51 |
March | 7689.25 | 6920.33 | 2.57 | 01-MAR-06:50 | 2.31 | 2.31 | 20.71 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 20.68 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 20.68 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 20.68 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 20.68 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 20.68 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 20.68 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 20.68 | 0.00 |
November | 382181.65 | 343963.49 | 19.80 | 27-NOV-06:20 | 17.82 | 17.82 | 20.33 | 0.02 |
December | 14871169.30 | 13384052.37 | 746.87 | 21-DEC-06:02 | 672.19 | 672.19 | 24.62 | 0.84 |
Annual Sum or Average | 63286246.50 | 56957621.85 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 0.00 | |
Maximum of Months | 42491359.24 | 38242223.31 | 1119.14 | 1007.23 | 1007.23 | 46.58 | 1.33 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.393436E+09 | 0.354092E+09 | 5296.92 | 28-JAN-06:03 | 4767.23 | 4767.23 | 8.74 | 65.95 |
February | 0.592101E+09 | 0.532890E+09 | 7389.47 | 17-FEB-06:02 | 6650.52 | 6650.52 | 8.90 | 75.89 |
March | 0.109859E+10 | 0.988732E+09 | 19798.77 | 27-MAR-05:02 | 17818.90 | 17818.90 | 8.05 | 113.35 |
April | 0.164206E+10 | 0.147785E+10 | 16744.89 | 17-APR-05:02 | 15070.40 | 15070.40 | 7.64 | 106.03 |
May | 0.209080E+10 | 0.188172E+10 | 26275.61 | 24-MAY-05:03 | 23648.05 | 23648.05 | 7.93 | 126.75 |
June | 0.243552E+10 | 0.219197E+10 | 23087.78 | 23-JUN-05:02 | 20779.00 | 20779.00 | 7.30 | 120.46 |
July | 0.267156E+10 | 0.240440E+10 | 25363.25 | 28-JUL-05:03 | 22826.92 | 22826.92 | 7.40 | 125.00 |
August | 0.280364E+10 | 0.252327E+10 | 25256.09 | 01-AUG-05:03 | 22730.48 | 22730.48 | 7.38 | 124.79 |
September | 0.205988E+10 | 0.185389E+10 | 26275.61 | 05-SEP-05:02 | 23648.05 | 23648.05 | 7.97 | 126.75 |
October | 0.136227E+10 | 0.122604E+10 | 23161.63 | 04-OCT-05:02 | 20845.47 | 20845.47 | 8.04 | 120.61 |
November | 0.107705E+10 | 0.969346E+09 | 10951.82 | 13-NOV-06:02 | 9856.63 | 9856.63 | 9.06 | 89.29 |
December | 0.547058E+09 | 0.492352E+09 | 4956.26 | 14-DEC-06:03 | 4460.64 | 4460.64 | 8.74 | 64.10 |
Annual Sum or Average | 0.187740E+11 | 0.168966E+11 | ||||||
Minimum of Months | 0.393436E+09 | 0.354092E+09 | 4956.26 | 4460.64 | 4460.64 | 7.30 | 64.10 | |
Maximum of Months | 0.280364E+10 | 0.252327E+10 | 26275.61 | 23648.05 | 23648.05 | 9.06 | 126.75 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.283083E+11 | 0.254775E+11 | 18084.79 | 01-JAN-00:25 | 16276.31 | 16276.31 | 8.46 | 126.75 |
February | 0.277348E+11 | 0.249614E+11 | 18084.79 | 01-FEB-04:03 | 16276.31 | 16276.31 | 8.85 | 126.75 |
March | 0.368358E+11 | 0.331522E+11 | 18084.79 | 01-MAR-04:02 | 16276.31 | 16276.31 | 9.34 | 126.75 |
April | 0.437472E+11 | 0.393725E+11 | 18084.79 | 01-APR-00:03 | 16276.31 | 16276.31 | 7.35 | 126.75 |
May | 0.447446E+11 | 0.402702E+11 | 18084.79 | 01-MAY-00:03 | 16276.31 | 16276.31 | 8.12 | 126.75 |
June | 0.431759E+11 | 0.388583E+11 | 18084.79 | 01-JUN-00:12 | 16276.31 | 16276.31 | 7.05 | 126.75 |
July | 0.457242E+11 | 0.411518E+11 | 18084.79 | 01-JUL-00:03 | 16276.31 | 16276.31 | 7.22 | 126.75 |
August | 0.462330E+11 | 0.416097E+11 | 18084.79 | 01-AUG-00:03 | 16276.31 | 16276.31 | 7.27 | 126.75 |
September | 0.388706E+11 | 0.349835E+11 | 18084.79 | 01-SEP-00:05 | 16276.31 | 16276.31 | 7.15 | 126.75 |
October | 0.384193E+11 | 0.345774E+11 | 18084.79 | 01-OCT-00:33 | 16276.31 | 16276.31 | 8.54 | 126.75 |
November | 0.335817E+11 | 0.302235E+11 | 18084.79 | 01-NOV-03:02 | 16276.31 | 16276.31 | 10.73 | 126.75 |
December | 0.308923E+11 | 0.278030E+11 | 18084.79 | 01-DEC-04:02 | 16276.31 | 16276.31 | 9.43 | 126.75 |
Annual Sum or Average | 0.458268E+12 | 0.412441E+12 | ||||||
Minimum of Months | 0.277348E+11 | 0.249614E+11 | 18084.79 | 16276.31 | 16276.31 | 7.05 | 126.75 | |
Maximum of Months | 0.462330E+11 | 0.416097E+11 | 18084.79 | 16276.31 | 16276.31 | 10.73 | 126.75 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.946167E+10 | 0.851551E+10 | 3532.58 | 01-JAN-00:05 | 3179.33 | 3179.33 | 21.72 | 14.75 |
February | 0.854603E+10 | 0.769143E+10 | 3532.58 | 01-FEB-00:10 | 3179.33 | 3179.33 | 24.23 | 14.75 |
March | 0.946167E+10 | 0.851551E+10 | 3532.58 | 01-MAR-00:10 | 3179.33 | 3179.33 | 28.60 | 14.75 |
April | 0.915646E+10 | 0.824081E+10 | 3532.58 | 01-APR-00:03 | 3179.33 | 3179.33 | 42.42 | 14.75 |
May | 0.946167E+10 | 0.851551E+10 | 3532.58 | 01-MAY-00:03 | 3179.33 | 3179.33 | 37.75 | 14.75 |
June | 0.915646E+10 | 0.824081E+10 | 3532.58 | 01-JUN-00:10 | 3179.33 | 3179.33 | 38.99 | 14.75 |
July | 0.946167E+10 | 0.851551E+10 | 3532.58 | 01-JUL-00:03 | 3179.33 | 3179.33 | 49.06 | 14.75 |
August | 0.946167E+10 | 0.851551E+10 | 3532.58 | 01-AUG-00:03 | 3179.33 | 3179.33 | 49.19 | 14.75 |
September | 0.915646E+10 | 0.824081E+10 | 3532.58 | 01-SEP-00:05 | 3179.33 | 3179.33 | 36.31 | 14.75 |
October | 0.946167E+10 | 0.851551E+10 | 3532.58 | 01-OCT-00:03 | 3179.33 | 3179.33 | 37.34 | 14.75 |
November | 0.915646E+10 | 0.824081E+10 | 3532.58 | 01-NOV-00:10 | 3179.33 | 3179.33 | 31.82 | 14.75 |
December | 0.946167E+10 | 0.851551E+10 | 3532.58 | 01-DEC-00:10 | 3179.33 | 3179.33 | 29.89 | 14.75 |
Annual Sum or Average | 0.111404E+12 | 0.100263E+12 | ||||||
Minimum of Months | 0.854603E+10 | 0.769143E+10 | 3532.58 | 3179.33 | 3179.33 | 21.72 | 14.75 | |
Maximum of Months | 0.946167E+10 | 0.851551E+10 | 3532.58 | 3179.33 | 3179.33 | 49.19 | 14.75 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 55.78 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:02 | 1.79 | 1.79 | 56.50 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 56.08 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 57.55 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:02 | 1.79 | 1.79 | 57.71 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 58.08 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 57.81 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 57.60 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.62 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.89 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:02 | 1.79 | 1.79 | 56.84 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:03 | 1.79 | 1.79 | 56.28 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.78 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 58.08 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.354335E+11 | 0.318901E+11 | 44888.81 | 12-JAN-15:10 | 40399.93 | 40399.93 | 22.75 | 149.36 |
February | 0.354661E+11 | 0.319195E+11 | 44916.91 | 25-FEB-06:02 | 40425.22 | 40425.22 | 23.62 | 149.36 |
March | 0.505102E+11 | 0.454592E+11 | 45016.20 | 10-MAR-17:00 | 40514.58 | 40514.58 | 26.45 | 149.36 |
April | 0.678862E+11 | 0.610976E+11 | 45105.33 | 18-APR-12:30 | 40594.80 | 40594.80 | 28.84 | 149.36 |
May | 0.779412E+11 | 0.701471E+11 | 45105.33 | 09-MAY-13:10 | 40594.80 | 40594.80 | 28.87 | 149.36 |
June | 0.806425E+11 | 0.725783E+11 | 45105.33 | 05-JUN-15:00 | 40594.80 | 40594.80 | 28.87 | 149.36 |
July | 0.897819E+11 | 0.808037E+11 | 45105.33 | 01-JUL-07:10 | 40594.80 | 40594.80 | 29.33 | 149.36 |
August | 0.904997E+11 | 0.814498E+11 | 45105.33 | 01-AUG-00:40 | 40594.80 | 40594.80 | 30.13 | 149.36 |
September | 0.707598E+11 | 0.636838E+11 | 45105.33 | 01-SEP-00:40 | 40594.80 | 40594.80 | 29.93 | 149.36 |
October | 0.596691E+11 | 0.537022E+11 | 45104.63 | 04-OCT-05:04 | 40594.17 | 40594.17 | 28.79 | 149.36 |
November | 0.433413E+11 | 0.390072E+11 | 44981.38 | 13-NOV-14:30 | 40483.24 | 40483.24 | 25.53 | 149.36 |
December | 0.389487E+11 | 0.350538E+11 | 44889.91 | 01-DEC-15:20 | 40400.92 | 40400.92 | 22.78 | 149.36 |
Annual Sum or Average | 0.740880E+12 | 0.666792E+12 | ||||||
Minimum of Months | 0.354335E+11 | 0.318901E+11 | 44888.81 | 40399.93 | 40399.93 | 22.75 | 149.36 | |
Maximum of Months | 0.904997E+11 | 0.814498E+11 | 45105.33 | 40594.80 | 40594.80 | 30.13 | 149.36 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 79.76 | 79.76 | 3499.52 | 214389.78 | 03-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 24.88 | 24.88 | 553.27 | 121606.28 | 11-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 20.72 | 20.72 | 0.72 | 642.83 | 01-MAR-06:50 |
April | 0.00 | 0.00 | 01-APR-00:03 | 20.68 | 20.68 | 0.00 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.68 | 20.68 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.68 | 20.68 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 20.68 | 20.68 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.68 | 20.68 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 20.68 | 20.68 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 20.68 | 20.68 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 20.68 | 20.68 | 37.16 | 5007.30 | 27-NOV-06:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 20.32 | 20.32 | 1308.34 | 195903.17 | 21-DEC-06:02 |
Annual Sum or Average | 0.00 | 453.90 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.32 | 20.32 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 79.76 | 79.76 | 3499.52 | 214389.78 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 411691.87 | 1576675.02 | 25-JAN-15:10 | 10.24 | 8.68 | 15.24 | 79654.43 | 30-JAN-03:25 |
February | 533734.27 | 1686102.13 | 25-FEB-06:02 | 11.24 | 8.07 | 226.75 | 403043.43 | 06-FEB-02:55 |
March | 759702.12 | 2062647.19 | 11-MAR-06:02 | 11.02 | 7.14 | 6.17 | 75056.23 | 05-MAR-08:62 |
April | 1010586.50 | 3172067.73 | 17-APR-05:03 | 13.05 | 7.34 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1236806.15 | 3470543.18 | 24-MAY-05:03 | 13.47 | 7.76 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1335682.18 | 3479936.18 | 14-JUN-05:03 | 13.26 | 7.55 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1376548.86 | 3577045.24 | 25-JUL-05:03 | 13.44 | 7.73 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1365252.90 | 4050799.93 | 07-AUG-05:03 | 14.33 | 8.62 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1126118.84 | 4340337.56 | 05-SEP-05:04 | 14.96 | 9.24 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 885693.57 | 3280572.65 | 04-OCT-05:02 | 13.13 | 7.42 | 11.08 | 104806.99 | 28-OCT-20:42 |
November | 659670.46 | 1674325.97 | 06-NOV-13:10 | 9.85 | 6.70 | 19.41 | 80784.30 | 26-NOV-20:45 |
December | 472196.23 | 1591082.45 | 01-DEC-15:20 | 10.25 | 8.66 | 0.58 | 10298.37 | 03-DEC-17:42 |
Annual Sum or Average | 933290.25 | 21.80 | ||||||
Minimum of Months | 411691.87 | 1576675.02 | 9.85 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1376548.86 | 4340337.56 | 14.96 | 9.24 | 226.75 | 403043.43 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 266398.89 | 2053215.46 | 18-JAN-06:02 | 15.10 | 8.97 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 373616.31 | 2821064.45 | 25-FEB-06:02 | 15.88 | 8.28 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 575436.73 | 3728296.69 | 11-MAR-06:02 | 16.04 | 7.17 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 796015.36 | 4177766.42 | 17-APR-05:02 | 16.12 | 7.16 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1040063.26 | 4956669.74 | 24-MAY-05:03 | 16.05 | 7.85 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1206173.90 | 5004998.43 | 23-JUN-05:02 | 16.63 | 6.83 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1272885.70 | 5127806.82 | 31-JUL-05:02 | 17.04 | 7.73 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1275799.08 | 5149122.84 | 28-AUG-05:02 | 16.98 | 7.20 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1037190.49 | 5175404.37 | 05-SEP-05:02 | 16.46 | 7.88 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 695245.46 | 4747675.18 | 04-OCT-05:02 | 16.11 | 7.81 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 500564.00 | 3037722.87 | 09-NOV-06:03 | 15.66 | 8.12 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 316610.20 | 1899994.18 | 29-DEC-06:03 | 13.91 | 8.94 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 781849.83 | 0.00 | ||||||
Minimum of Months | 266398.89 | 1899994.18 | 13.91 | 6.83 | 0.00 | 0.00 | ||
Maximum of Months | 1275799.08 | 5175404.37 | 17.04 | 8.97 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 222968.87 | 587948.98 | 12-JAN-15:00 | 29.71 | 25.62 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 500647.69 | 1023886.66 | 22-FEB-15:00 | 38.00 | 30.73 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 970475.90 | 1771608.43 | 28-MAR-15:20 | 51.92 | 41.09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1594566.23 | 2235167.67 | 15-APR-15:00 | 60.38 | 47.14 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1125053.44 | 1788767.04 | 01-MAY-15:00 | 52.23 | 46.92 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1418913.01 | 2077062.60 | 08-JUN-16:00 | 57.51 | 48.99 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1562214.74 | 2099724.66 | 07-JUL-15:00 | 57.92 | 46.36 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1677298.29 | 2097242.06 | 07-AUG-15:00 | 57.87 | 44.29 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 903977.83 | 1401087.29 | 17-SEP-20:00 | 45.06 | 40.04 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 909464.99 | 1585426.29 | 02-OCT-15:00 | 48.48 | 40.47 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 824512.51 | 1432582.66 | 08-NOV-15:00 | 45.65 | 35.19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 790137.70 | 1330929.74 | 28-DEC-14:20 | 43.76 | 31.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1044556.86 | 0.00 | ||||||
Minimum of Months | 222968.87 | 587948.98 | 29.71 | 25.62 | 0.00 | 0.00 | ||
Maximum of Months | 1677298.29 | 2235167.67 | 60.38 | 48.99 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.67 | 56.67 | 12736.38 | 41939.78 | 18-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.95 | 56.95 | 12565.30 | 41685.69 | 01-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.56 | 56.56 | 12460.90 | 39954.81 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:03 | 57.93 | 57.93 | 10707.24 | 36293.94 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.57 | 58.57 | 9907.69 | 32609.11 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.38 | 58.38 | 9215.80 | 29022.62 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 58.06 | 58.06 | 8271.59 | 26830.22 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 58.57 | 58.57 | 9179.75 | 28572.30 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 56.89 | 56.89 | 9468.39 | 31771.68 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 57.43 | 57.43 | 10512.63 | 35911.19 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.21 | 57.21 | 11729.89 | 39429.38 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.75 | 56.75 | 12146.27 | 41510.39 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 10731.89 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.56 | 56.56 | 8271.59 | 26830.22 | ||
Maximum of Months | 0.00 | 0.00 | 58.57 | 58.57 | 12736.38 | 41939.78 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 244589.05 | 1138789.27 | 25-JAN-15:50 | 24.75 | 21.10 | 2780.89 | 142006.95 | 21-JAN-06:30 |
February | 351751.30 | 1572203.41 | 25-FEB-06:02 | 23.62 | 22.31 | 952.10 | 132838.06 | 02-FEB-07:00 |
March | 605254.13 | 3340521.99 | 10-MAR-17:00 | 26.45 | 23.33 | 210.17 | 78791.98 | 01-MAR-04:30 |
April | 1095135.57 | 5094516.93 | 18-APR-14:00 | 29.26 | 25.58 | 116.49 | 31528.10 | 09-APR-23:27 |
May | 2269400.51 | 6858010.74 | 17-MAY-15:30 | 32.08 | 27.83 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 3402094.33 | 7900866.08 | 22-JUN-15:50 | 33.75 | 28.96 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 4395535.27 | 7926461.46 | 31-JUL-05:03 | 33.80 | 28.97 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 4401664.96 | 7980936.25 | 28-AUG-05:03 | 33.88 | 29.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3000791.17 | 7547560.56 | 14-SEP-15:30 | 33.19 | 28.77 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 982297.67 | 4800260.76 | 04-OCT-05:04 | 28.79 | 24.34 | 29.97 | 30147.33 | 30-OCT-01:50 |
November | 487846.39 | 2764266.70 | 13-NOV-14:30 | 25.53 | 21.10 | 493.63 | 84869.05 | 27-NOV-03:30 |
December | 287802.45 | 1182753.60 | 01-DEC-15:40 | 24.89 | 21.10 | 1490.54 | 144666.78 | 23-DEC-07:00 |
Annual Sum or Average | 1803309.38 | 506.36 | ||||||
Minimum of Months | 244589.05 | 1138789.27 | 23.62 | 21.10 | 0.00 | 0.00 | ||
Maximum of Months | 4401664.96 | 7980936.25 | 33.88 | 29.00 | 2780.89 | 144666.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 9289584.61 | 0.00 | 0.551477E+11 | 0.613777E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.727524E+11 | 0.711973E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.129389E+12 | 0.111338E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.185927E+12 | 0.138470E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.225479E+12 | 0.132897E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.264382E+12 | 0.140456E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.305430E+12 | 0.141774E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.330330E+12 | 0.173631E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.227887E+12 | 0.109296E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.156275E+12 | 0.105351E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.107927E+12 | 0.930219E+10 | 0.00 | 0.00 |
December | 5407126.38 | 0.00 | 0.763068E+11 | 0.842569E+10 | 0.00 | 0.00 |
Annual Sum or Average | 14696711.00 | 0.00 | 0.213723E+13 | 0.136307E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.551477E+11 | 0.613777E+10 | 0.00 | 0.00 |
Maximum of Months | 9289584.61 | 0.00 | 0.330330E+12 | 0.173631E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.429736E+10 | 0.00 | 0.399574E+12 | 0.449800E+11 | 0.00 | 0.00 |
February | 0.385667E+09 | 0.00 | 0.539654E+12 | 0.499375E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.998560E+12 | 0.793905E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.144127E+13 | 0.981349E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.206128E+13 | 0.113842E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.233610E+13 | 0.112808E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.255859E+13 | 0.102204E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.254024E+13 | 0.106187E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.198051E+13 | 0.894786E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.128008E+13 | 0.782988E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.801234E+12 | 0.611042E+11 | 0.00 | 0.00 |
December | 0.123750E+10 | 0.00 | 0.466031E+12 | 0.484460E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.592053E+10 | 0.00 | 0.174031E+14 | 0.984812E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.399574E+12 | 0.449800E+11 | 0.00 | 0.00 |
Maximum of Months | 0.429736E+10 | 0.00 | 0.255859E+13 | 0.113842E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.531844E+10 | 0.00 | 0.292588E+11 | 0.346403E+10 | 0.00 | 0.00 |
February | 0.978304E+09 | 0.00 | 0.477579E+11 | 0.405743E+10 | 0.00 | 0.00 |
March | 2066914.10 | 0.00 | 0.102628E+12 | 0.749354E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.162918E+12 | 0.108785E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.236869E+12 | 0.134300E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.265561E+12 | 0.134036E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.283916E+12 | 0.115360E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.276710E+12 | 0.114524E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.213524E+12 | 0.937494E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.132816E+12 | 0.787926E+10 | 0.00 | 0.00 |
November | 98170484.54 | 0.00 | 0.744814E+11 | 0.540165E+10 | 0.00 | 0.00 |
December | 0.228854E+10 | 0.00 | 0.357410E+11 | 0.365090E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.868552E+10 | 0.00 | 0.186218E+13 | 0.102022E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.292588E+11 | 0.346403E+10 | 0.00 | 0.00 |
Maximum of Months | 0.531844E+10 | 0.00 | 0.283916E+12 | 0.134300E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.560333E+11 | 0.167064E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.573217E+11 | 0.148366E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.787844E+11 | 0.167797E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.900437E+11 | 0.156489E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.115380E+12 | 0.167857E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.134888E+12 | 0.168586E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.155844E+12 | 0.174745E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.174314E+12 | 0.186617E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.139122E+12 | 0.175204E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.101533E+12 | 0.180738E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.787329E+11 | 0.173156E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.635985E+11 | 0.171902E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124560E+13 | 0.203852E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.560333E+11 | 0.148366E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.174314E+12 | 0.186617E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.426450E+12 | 0.196810E+12 | 0.00 | 4.46 |
February | 0.00 | 0.00 | 0.676125E+12 | 0.242845E+12 | 0.00 | 4.87 |
March | 0.00 | 0.00 | 0.109184E+13 | 0.358738E+12 | 0.00 | 2.51 |
April | 0.00 | 0.00 | 0.140584E+13 | 0.465405E+12 | 0.00 | 0.35 |
May | 0.00 | 0.00 | 0.512636E+12 | 0.246158E+12 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.845747E+12 | 0.340101E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.121508E+13 | 0.437222E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.149328E+13 | 0.489673E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.500182E+12 | 0.226623E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.801115E+12 | 0.296642E+12 | 0.00 | 0.49 |
November | 0.00 | 0.00 | 0.104884E+13 | 0.337862E+12 | 0.00 | 5.07 |
December | 0.00 | 0.00 | 0.137071E+13 | 0.402098E+12 | 0.00 | 12.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.113878E+14 | 0.404018E+13 | 0.00 | 30.57 |
Minimum of Months | 0.00 | 0.00 | 0.426450E+12 | 0.196810E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.149328E+13 | 0.489673E+12 | 0.00 | 12.81 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.631444E+10 | 0.277674E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.121721E+11 | 0.387231E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.211406E+11 | 0.633824E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.285069E+11 | 0.893001E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.101273E+11 | 0.434086E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.172478E+11 | 0.630028E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.250036E+11 | 0.826515E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.311317E+11 | 0.962103E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.994044E+10 | 0.396524E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.155262E+11 | 0.523613E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.199603E+11 | 0.576183E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.256520E+11 | 0.652953E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.222723E+12 | 0.719374E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.631444E+10 | 0.277674E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.311317E+11 | 0.962103E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.479183E+11 | 0.240772E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108625E+12 | 0.355071E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.199680E+12 | 0.600541E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.270727E+12 | 0.849000E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.955601E+11 | 0.410947E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.164428E+12 | 0.600152E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.238673E+12 | 0.787969E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.295755E+12 | 0.915644E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.934942E+11 | 0.374501E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.146212E+12 | 0.495072E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.185243E+12 | 0.539667E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.234056E+12 | 0.604393E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208037E+13 | 0.677373E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.479183E+11 | 0.240772E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.295755E+12 | 0.915644E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.302630E+10 | 0.206650E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.100428E+11 | 0.341475E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.197954E+11 | 0.600976E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.273521E+11 | 0.861692E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.990884E+10 | 0.422826E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.167862E+11 | 0.612674E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.242188E+11 | 0.801397E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.300706E+11 | 0.934641E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.947728E+10 | 0.379651E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.145586E+11 | 0.496816E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.179464E+11 | 0.532066E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.220378E+11 | 0.584083E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.205221E+12 | 0.677495E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.302630E+10 | 0.206650E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.300706E+11 | 0.934641E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.613777E+10 | 0.551477E+11 | 9289584.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.711973E+10 | 0.727524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111338E+11 | 0.129389E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138470E+11 | 0.185927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132897E+11 | 0.225479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140456E+11 | 0.264382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141774E+11 | 0.305430E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173631E+11 | 0.330330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109296E+11 | 0.227887E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105351E+11 | 0.156275E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.930219E+10 | 0.107927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.842569E+10 | 0.763068E+11 | 5407126.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136307E+12 | 0.213723E+13 | 14696711.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.613777E+10 | 0.551477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173631E+11 | 0.330330E+12 | 9289584.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.449800E+11 | 0.399574E+12 | 0.429736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.499375E+11 | 0.539654E+12 | 0.385667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.793905E+11 | 0.998560E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.981349E+11 | 0.144127E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113842E+12 | 0.206128E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112808E+12 | 0.233610E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102204E+12 | 0.255859E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106187E+12 | 0.254024E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.894786E+11 | 0.198051E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.782988E+11 | 0.128008E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.611042E+11 | 0.801234E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.484460E+11 | 0.466031E+12 | 0.123750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.984812E+12 | 0.174031E+14 | 0.592053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.449800E+11 | 0.399574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113842E+12 | 0.255859E+13 | 0.429736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.346403E+10 | 0.292588E+11 | 0.531844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.405743E+10 | 0.477579E+11 | 0.978304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749354E+10 | 0.102628E+12 | 2066914.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108785E+11 | 0.162918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134300E+11 | 0.236869E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134036E+11 | 0.265561E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115360E+11 | 0.283916E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114524E+11 | 0.276710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.937494E+10 | 0.213524E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.787926E+10 | 0.132816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.540165E+10 | 0.744814E+11 | 98170484.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365090E+10 | 0.357410E+11 | 0.228854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102022E+12 | 0.186218E+13 | 0.868552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.346403E+10 | 0.292588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134300E+11 | 0.283916E+12 | 0.531844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.167064E+11 | 0.560333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148366E+11 | 0.573217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167797E+11 | 0.787844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156489E+11 | 0.900437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167857E+11 | 0.115380E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168586E+11 | 0.134888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174745E+11 | 0.155844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.186617E+11 | 0.174314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175204E+11 | 0.139122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180738E+11 | 0.101533E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173156E+11 | 0.787329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171902E+11 | 0.635985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203852E+12 | 0.124560E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148366E+11 | 0.560333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.186617E+11 | 0.174314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.970462E+11 | 0.338687E+12 | 0.00 | 0.00 | 0.00 | 0.119472E+11 | 0.00 | 0.00 |
February | 0.876546E+11 | 0.534019E+12 | 0.00 | 0.00 | 0.00 | 0.130253E+11 | 0.00 | 0.00 |
March | 0.970462E+11 | 0.836897E+12 | 0.00 | 0.00 | 0.00 | 0.671590E+10 | 0.00 | 0.00 |
April | 0.939157E+11 | 0.103528E+13 | 0.00 | 0.00 | 0.00 | 0.930960E+09 | 0.00 | 0.00 |
May | 0.970462E+11 | 0.363541E+12 | 0.00 | 0.00 | 0.00 | 16418864.26 | 0.00 | 0.00 |
June | 0.939157E+11 | 0.599562E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.970462E+11 | 0.874908E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.970462E+11 | 0.110066E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.939157E+11 | 0.367475E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.970462E+11 | 0.602836E+12 | 0.00 | 0.00 | 0.00 | 0.131045E+10 | 0.00 | 0.00 |
November | 0.939157E+11 | 0.818523E+12 | 0.00 | 0.00 | 0.00 | 0.135687E+11 | 0.00 | 0.00 |
December | 0.970462E+11 | 0.110010E+13 | 0.00 | 0.00 | 0.00 | 0.342896E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.114264E+13 | 0.857248E+13 | 0.00 | 0.00 | 0.00 | 0.818045E+11 | 0.00 | 0.00 |
Minimum of Months | 0.876546E+11 | 0.338687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.970462E+11 | 0.110066E+13 | 0.00 | 0.00 | 0.00 | 0.342896E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147086E+10 | 0.500855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132851E+10 | 0.962832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147086E+10 | 0.162732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142341E+10 | 0.210003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147086E+10 | 0.725726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142341E+10 | 0.123709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147086E+10 | 0.182093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147086E+10 | 0.229816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142341E+10 | 0.739861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147086E+10 | 0.117609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142341E+10 | 0.156218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147086E+10 | 0.205933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173181E+11 | 0.168104E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132851E+10 | 0.500855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147086E+10 | 0.229816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140096E+11 | 0.378506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126538E+11 | 0.857714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140096E+11 | 0.153635E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135576E+11 | 0.199385E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140096E+11 | 0.684750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135576E+11 | 0.117971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140096E+11 | 0.173886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140096E+11 | 0.218200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135576E+11 | 0.696018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140096E+11 | 0.110715E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135576E+11 | 0.144834E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140096E+11 | 0.187626E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164951E+12 | 0.156795E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126538E+11 | 0.378506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140096E+11 | 0.218200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140937E+10 | 0.236917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127298E+10 | 0.790104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140937E+10 | 0.151950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136391E+10 | 0.200991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140937E+10 | 0.708995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136391E+10 | 0.120234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140937E+10 | 0.176142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140937E+10 | 0.221336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136391E+10 | 0.704468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140937E+10 | 0.109998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136391E+10 | 0.139896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140937E+10 | 0.176063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165942E+11 | 0.154066E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127298E+10 | 0.236917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140937E+10 | 0.221336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.613777E+10 | 9289584.61 | 0.551477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.711973E+10 | 0.00 | 0.727524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111338E+11 | 0.00 | 0.129389E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138470E+11 | 0.00 | 0.185927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132897E+11 | 0.00 | 0.225479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140456E+11 | 0.00 | 0.264382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141774E+11 | 0.00 | 0.305430E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173631E+11 | 0.00 | 0.330330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109296E+11 | 0.00 | 0.227887E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105351E+11 | 0.00 | 0.156275E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.930219E+10 | 0.00 | 0.107927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.842569E+10 | 5407126.38 | 0.763068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136307E+12 | 14696711.00 | 0.213723E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.613777E+10 | 0.00 | 0.551477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173631E+11 | 9289584.61 | 0.330330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.449800E+11 | 0.429736E+10 | 0.399574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.499375E+11 | 0.385667E+09 | 0.539654E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.793905E+11 | 0.00 | 0.998560E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.981349E+11 | 0.00 | 0.144127E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113842E+12 | 0.00 | 0.206128E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112808E+12 | 0.00 | 0.233610E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102204E+12 | 0.00 | 0.255859E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106187E+12 | 0.00 | 0.254024E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.894786E+11 | 0.00 | 0.198051E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.782988E+11 | 0.00 | 0.128008E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.611042E+11 | 0.00 | 0.801234E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.484460E+11 | 0.123750E+10 | 0.466031E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.984812E+12 | 0.592053E+10 | 0.174031E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.449800E+11 | 0.00 | 0.399574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113842E+12 | 0.429736E+10 | 0.255859E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.346403E+10 | 0.531844E+10 | 0.292588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.405743E+10 | 0.978304E+09 | 0.477579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749354E+10 | 2066914.10 | 0.102628E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108785E+11 | 0.00 | 0.162918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134300E+11 | 0.00 | 0.236869E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134036E+11 | 0.00 | 0.265561E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115360E+11 | 0.00 | 0.283916E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114524E+11 | 0.00 | 0.276710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.937494E+10 | 0.00 | 0.213524E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.787926E+10 | 0.00 | 0.132816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.540165E+10 | 98170484.54 | 0.744814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365090E+10 | 0.228854E+10 | 0.357410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102022E+12 | 0.868552E+10 | 0.186218E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.346403E+10 | 0.00 | 0.292588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134300E+11 | 0.531844E+10 | 0.283916E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.167064E+11 | 0.00 | 0.560333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148366E+11 | 0.00 | 0.573217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167797E+11 | 0.00 | 0.787844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156489E+11 | 0.00 | 0.900437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167857E+11 | 0.00 | 0.115380E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168586E+11 | 0.00 | 0.134888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174745E+11 | 0.00 | 0.155844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.186617E+11 | 0.00 | 0.174314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175204E+11 | 0.00 | 0.139122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180738E+11 | 0.00 | 0.101533E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173156E+11 | 0.00 | 0.787329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171902E+11 | 0.00 | 0.635985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203852E+12 | 0.00 | 0.124560E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148366E+11 | 0.00 | 0.560333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.186617E+11 | 0.00 | 0.174314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.970462E+11 | 0.00 | 0.426450E+12 | 0.00 | 0.877633E+11 | 0.00 | 0.00 | 0.00 | 0.120010E+11 | 0.00 | 0.00 | 0.00 |
February | 0.876546E+11 | 0.00 | 0.676125E+12 | 0.00 | 0.142106E+12 | 0.00 | 0.00 | 0.00 | 0.130839E+11 | 0.00 | 0.00 | 0.00 |
March | 0.970462E+11 | 0.00 | 0.109184E+13 | 0.00 | 0.254946E+12 | 0.00 | 0.00 | 0.00 | 0.674613E+10 | 0.00 | 0.00 | 0.00 |
April | 0.939157E+11 | 0.00 | 0.140584E+13 | 0.00 | 0.370554E+12 | 0.00 | 0.00 | 0.00 | 0.935151E+09 | 0.00 | 0.00 | 0.00 |
May | 0.970462E+11 | 0.00 | 0.512636E+12 | 0.00 | 0.149095E+12 | 0.00 | 0.00 | 0.00 | 16492772.22 | 0.00 | 0.00 | 0.00 |
June | 0.939157E+11 | 0.00 | 0.845747E+12 | 0.00 | 0.246185E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.970462E+11 | 0.00 | 0.121508E+13 | 0.00 | 0.340176E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.970462E+11 | 0.00 | 0.149328E+13 | 0.00 | 0.392627E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.939157E+11 | 0.00 | 0.500182E+12 | 0.00 | 0.132707E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.970462E+11 | 0.00 | 0.801115E+12 | 0.00 | 0.198279E+12 | 0.00 | 0.00 | 0.00 | 0.131635E+10 | 0.00 | 0.00 | 0.00 |
November | 0.939157E+11 | 0.00 | 0.104884E+13 | 0.00 | 0.230316E+12 | 0.00 | 0.00 | 0.00 | 0.136297E+11 | 0.00 | 0.00 | 0.00 |
December | 0.970462E+11 | 0.00 | 0.137071E+13 | 0.00 | 0.270608E+12 | 0.00 | 0.00 | 0.00 | 0.344439E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114264E+13 | 0.00 | 0.113878E+14 | 0.00 | 0.281536E+13 | 0.00 | 0.00 | 0.00 | 0.821727E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.876546E+11 | 0.00 | 0.426450E+12 | 0.00 | 0.877633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.970462E+11 | 0.00 | 0.149328E+13 | 0.00 | 0.392627E+12 | 0.00 | 0.00 | 0.00 | 0.344439E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147086E+10 | 0.00 | 0.631444E+10 | 0.00 | 0.130589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132851E+10 | 0.00 | 0.121721E+11 | 0.00 | 0.254379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147086E+10 | 0.00 | 0.211406E+11 | 0.00 | 0.486739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142341E+10 | 0.00 | 0.285069E+11 | 0.00 | 0.750660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147086E+10 | 0.00 | 0.101273E+11 | 0.00 | 0.287000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142341E+10 | 0.00 | 0.172478E+11 | 0.00 | 0.487687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147086E+10 | 0.00 | 0.250036E+11 | 0.00 | 0.679429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147086E+10 | 0.00 | 0.311317E+11 | 0.00 | 0.815018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142341E+10 | 0.00 | 0.994044E+10 | 0.00 | 0.254184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147086E+10 | 0.00 | 0.155262E+11 | 0.00 | 0.376527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142341E+10 | 0.00 | 0.199603E+11 | 0.00 | 0.433842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147086E+10 | 0.00 | 0.256520E+11 | 0.00 | 0.505868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173181E+11 | 0.00 | 0.222723E+12 | 0.00 | 0.546192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132851E+10 | 0.00 | 0.631444E+10 | 0.00 | 0.130589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147086E+10 | 0.00 | 0.311317E+11 | 0.00 | 0.815018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140096E+11 | 0.00 | 0.479183E+11 | 0.00 | 0.100677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126538E+11 | 0.00 | 0.108625E+12 | 0.00 | 0.228533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140096E+11 | 0.00 | 0.199680E+12 | 0.00 | 0.460445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135576E+11 | 0.00 | 0.270727E+12 | 0.00 | 0.713424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140096E+11 | 0.00 | 0.955601E+11 | 0.00 | 0.270851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135576E+11 | 0.00 | 0.164428E+12 | 0.00 | 0.464575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140096E+11 | 0.00 | 0.238673E+12 | 0.00 | 0.647873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140096E+11 | 0.00 | 0.295755E+12 | 0.00 | 0.775549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135576E+11 | 0.00 | 0.934942E+11 | 0.00 | 0.238924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140096E+11 | 0.00 | 0.146212E+12 | 0.00 | 0.354976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135576E+11 | 0.00 | 0.185243E+12 | 0.00 | 0.404091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140096E+11 | 0.00 | 0.234056E+12 | 0.00 | 0.464298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164951E+12 | 0.00 | 0.208037E+13 | 0.00 | 0.512422E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126538E+11 | 0.00 | 0.479183E+11 | 0.00 | 0.100677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140096E+11 | 0.00 | 0.295755E+12 | 0.00 | 0.775549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140937E+10 | 0.00 | 0.302630E+10 | 0.00 | 0.657129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127298E+10 | 0.00 | 0.100428E+11 | 0.00 | 0.214177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140937E+10 | 0.00 | 0.197954E+11 | 0.00 | 0.460039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136391E+10 | 0.00 | 0.273521E+11 | 0.00 | 0.725302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140937E+10 | 0.00 | 0.990884E+10 | 0.00 | 0.281889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136391E+10 | 0.00 | 0.167862E+11 | 0.00 | 0.476283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140937E+10 | 0.00 | 0.242188E+11 | 0.00 | 0.660460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140937E+10 | 0.00 | 0.300706E+11 | 0.00 | 0.793704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136391E+10 | 0.00 | 0.947728E+10 | 0.00 | 0.243260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140937E+10 | 0.00 | 0.145586E+11 | 0.00 | 0.355879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136391E+10 | 0.00 | 0.179464E+11 | 0.00 | 0.395676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140937E+10 | 0.00 | 0.220378E+11 | 0.00 | 0.443145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165942E+11 | 0.00 | 0.205221E+12 | 0.00 | 0.511553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127298E+10 | 0.00 | 0.302630E+10 | 0.00 | 0.657129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140937E+10 | 0.00 | 0.300706E+11 | 0.00 | 0.793704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.253534E+10 | 0.00 | 0.00 | 0.123213E+09 | 0.00 | 0.00 | 0.260623E+11 | 0.00 | 0.40 |
February | 0.951979E+09 | 0.00 | 0.00 | 0.112811E+09 | 0.00 | 0.00 | 0.168316E+11 | 0.00 | 0.39 |
March | 0.371806E+09 | 0.152888E+10 | 0.00 | 0.101890E+09 | 27128244.13 | 0.00 | 0.854217E+10 | 0.00 | 0.40 |
April | 20277093.79 | 0.106481E+11 | 0.00 | 23278920.19 | 0.275363E+09 | 0.00 | 0.550787E+09 | 0.00 | 0.39 |
May | 7980773.40 | 0.299847E+11 | 0.00 | 3655843.92 | 0.512674E+09 | 0.00 | 55938996.63 | 0.00 | 0.41 |
June | 0.00 | 0.464983E+11 | 0.00 | 761958.80 | 0.823218E+09 | 0.00 | 1204386.27 | 0.00 | 0.43 |
July | 0.00 | 0.635183E+11 | 0.00 | 0.00 | 0.151967E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.707933E+11 | 0.00 | 0.00 | 0.118707E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.467536E+11 | 0.00 | 0.00 | 0.105432E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.199071E+09 | 0.882792E+10 | 0.00 | 64773967.69 | 0.147078E+09 | 0.00 | 0.291520E+10 | 0.00 | 0.44 |
November | 0.939481E+09 | 0.242066E+09 | 0.00 | 0.144728E+09 | 20523950.90 | 0.00 | 0.133170E+11 | 0.00 | 0.43 |
December | 0.195219E+10 | 0.00 | 0.00 | 0.136110E+09 | 0.00 | 0.00 | 0.244035E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.697812E+10 | 0.278795E+12 | 0.00 | 0.711222E+09 | 0.556705E+10 | 0.00 | 0.926796E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.253534E+10 | 0.707933E+11 | 0.00 | 0.144728E+09 | 0.151967E+10 | 0.00 | 0.260623E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197533E+10 | 0.00 | 0.00 | 85993123.41 | 0.00 | 0.00 | 0.221948E+11 | 0.00 | 0.33 |
February | 0.189135E+10 | 0.00 | 0.00 | 87065429.11 | 2793699.20 | 0.00 | 0.146707E+11 | 0.00 | 0.35 |
March | 0.225627E+10 | 0.114489E+10 | 0.00 | 87252076.75 | 0.370551E+09 | 0.00 | 0.793563E+10 | 0.00 | 0.40 |
April | 0.586023E+09 | 0.702941E+10 | 0.00 | 24046421.98 | 0.381400E+10 | 0.00 | 0.769844E+09 | 0.00 | 0.44 |
May | 11775318.21 | 0.236038E+11 | 0.00 | 734918.95 | 0.978374E+10 | 0.00 | 11818269.12 | 0.00 | 0.42 |
June | 0.00 | 0.357910E+11 | 0.00 | 0.00 | 0.176203E+11 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.457924E+11 | 0.00 | 0.00 | 0.304622E+11 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.527069E+11 | 0.00 | 0.00 | 0.278592E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.359314E+11 | 0.00 | 0.00 | 0.144480E+11 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 0.786213E+09 | 0.759374E+10 | 0.00 | 32844093.99 | 0.177336E+10 | 0.00 | 0.209787E+10 | 0.00 | 0.39 |
November | 0.233219E+10 | 0.168018E+09 | 0.00 | 99890310.25 | 77225309.60 | 0.00 | 0.110264E+11 | 0.00 | 0.37 |
December | 0.297583E+10 | 0.00 | 0.00 | 0.101984E+09 | 0.00 | 0.00 | 0.207251E+11 | 0.00 | 0.36 |
Annual Sum or Average | 0.128150E+11 | 0.209761E+12 | 0.00 | 0.519811E+09 | 0.106211E+12 | 0.00 | 0.794321E+11 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.297583E+10 | 0.527069E+11 | 0.00 | 0.101984E+09 | 0.304622E+11 | 0.00 | 0.221948E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243682E+11 | 0.00 | 0.00 | 0.544189E+09 | 0.00 | 0.00 | 0.179442E+12 | 0.00 | 0.30 |
February | 0.129813E+11 | 0.00 | 0.00 | 0.622423E+09 | 0.104852E+09 | 0.00 | 0.126757E+12 | 0.00 | 0.32 |
March | 0.985024E+10 | 0.116764E+11 | 0.00 | 0.721428E+09 | 0.322335E+10 | 0.00 | 0.736467E+11 | 0.00 | 0.34 |
April | 0.212018E+10 | 0.679617E+11 | 0.00 | 0.188959E+09 | 0.304634E+11 | 0.00 | 0.609001E+10 | 0.00 | 0.36 |
May | 85829221.13 | 0.232176E+12 | 0.00 | 4143289.54 | 0.867108E+11 | 0.00 | 0.107212E+09 | 0.00 | 0.40 |
June | 0.00 | 0.349762E+12 | 0.00 | 0.00 | 0.137766E+12 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.440936E+12 | 0.00 | 0.00 | 0.214576E+12 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.500496E+12 | 0.00 | 0.00 | 0.158129E+12 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.352204E+12 | 0.00 | 0.00 | 0.936240E+11 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.489358E+10 | 0.751065E+11 | 0.00 | 0.259417E+09 | 0.128150E+11 | 0.00 | 0.183813E+11 | 0.00 | 0.34 |
November | 0.146162E+11 | 0.178693E+10 | 0.00 | 0.720146E+09 | 0.954637E+09 | 0.00 | 0.923153E+11 | 0.00 | 0.33 |
December | 0.192555E+11 | 0.00 | 0.00 | 0.579215E+09 | 12399877.70 | 0.00 | 0.168171E+12 | 0.00 | 0.31 |
Annual Sum or Average | 0.881710E+11 | 0.203211E+13 | 0.00 | 0.363992E+10 | 0.738379E+12 | 0.00 | 0.664911E+12 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.243682E+11 | 0.500496E+12 | 0.00 | 0.721428E+09 | 0.214576E+12 | 0.00 | 0.179442E+12 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104298E+11 | 0.00 | 0.00 | 19355079.83 | 0.00 | 0.233782E+09 | 0.616089E+10 | 0.00 | 0.27 |
February | 0.431127E+10 | 0.00 | 0.00 | 37247640.85 | 4642977.54 | 0.00 | 0.729740E+10 | 0.00 | 0.29 |
March | 0.104493E+10 | 0.841021E+09 | 0.00 | 62558856.14 | 0.231846E+09 | 0.00 | 0.634234E+10 | 0.00 | 0.32 |
April | 0.180806E+09 | 0.595976E+10 | 0.00 | 23882923.88 | 0.269314E+10 | 0.00 | 0.707526E+09 | 0.00 | 0.37 |
May | 6788607.89 | 0.223713E+11 | 0.00 | 299995.44 | 0.836285E+10 | 0.00 | 9253967.79 | 0.00 | 0.40 |
June | 0.00 | 0.343220E+11 | 0.00 | 0.00 | 0.138710E+11 | 0.00 | 0.00 | 0.00 | 0.40 |
July | 0.00 | 0.438972E+11 | 0.00 | 0.00 | 0.216475E+11 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.495737E+11 | 0.00 | 0.00 | 0.161728E+11 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.341007E+11 | 0.00 | 0.00 | 0.102331E+11 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.397465E+09 | 0.659159E+10 | 0.00 | 23741757.23 | 0.106768E+10 | 0.00 | 0.148508E+10 | 0.00 | 0.33 |
November | 0.259380E+10 | 50009841.54 | 0.00 | 52509383.08 | 77500709.36 | 0.00 | 0.617079E+10 | 0.00 | 0.30 |
December | 0.800829E+10 | 0.00 | 0.00 | 26020864.35 | 40838.80 | 0.00 | 0.695354E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.269731E+11 | 0.197707E+12 | 0.00 | 0.245617E+09 | 0.743621E+11 | 0.233782E+09 | 0.351268E+11 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.104298E+11 | 0.495737E+11 | 0.00 | 62558856.14 | 0.216475E+11 | 0.233782E+09 | 0.729740E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.231095E+10 | 0.00 | 0.00 | 2757354.67 | 0.00 | 0.00 | 0.767901E+09 | 0.00 | 0.33 |
February | 0.128259E+10 | 0.00 | 0.00 | 5281737.33 | 518926.24 | 0.00 | 0.850520E+09 | 0.00 | 0.36 |
March | 0.660845E+09 | 0.196850E+09 | 0.00 | 8652596.97 | 68829429.03 | 0.00 | 0.770233E+09 | 0.00 | 0.47 |
April | 0.119898E+09 | 0.140366E+10 | 0.00 | 3350977.36 | 0.698894E+09 | 0.00 | 98912131.87 | 0.00 | 0.64 |
May | 1465443.78 | 0.531235E+10 | 0.00 | 149236.96 | 0.166977E+10 | 0.00 | 3214692.43 | 0.00 | 0.68 |
June | 0.00 | 0.824392E+10 | 0.00 | 0.00 | 0.296490E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
July | 0.00 | 0.102078E+11 | 0.00 | 0.00 | 0.510513E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.103319E+11 | 0.00 | 0.00 | 0.495472E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 0.00 | 0.649231E+10 | 0.00 | 0.00 | 0.269341E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 0.208445E+09 | 0.122728E+10 | 0.00 | 2778564.75 | 0.336612E+09 | 0.00 | 0.197357E+09 | 0.00 | 0.49 |
November | 0.994323E+09 | 24333294.65 | 0.00 | 7541347.25 | 14344507.77 | 0.00 | 0.760002E+09 | 0.00 | 0.39 |
December | 0.196301E+10 | 0.00 | 0.00 | 4766538.95 | 0.00 | 0.00 | 0.916537E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.754152E+10 | 0.434404E+11 | 0.00 | 35278354.24 | 0.185071E+11 | 0.00 | 0.436468E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.231095E+10 | 0.103319E+11 | 0.00 | 8652596.97 | 0.510513E+10 | 0.00 | 0.916537E+09 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161366E+10 | 0.00 | 0.00 | 3086918.09 | 0.00 | 0.00 | 0.823326E+09 | 0.00 | 0.40 |
February | 0.952392E+09 | 0.00 | 0.00 | 4717963.25 | 404659.12 | 0.00 | 0.791621E+09 | 0.00 | 0.45 |
March | 0.533269E+09 | 0.142668E+09 | 0.00 | 7061536.47 | 53265042.97 | 0.00 | 0.639289E+09 | 0.00 | 0.59 |
April | 98418988.37 | 0.109186E+10 | 0.00 | 2710703.04 | 0.525594E+09 | 0.00 | 80896817.59 | 0.00 | 0.78 |
May | 1285150.13 | 0.423510E+10 | 0.00 | 92335.62 | 0.123381E+10 | 0.00 | 2156235.73 | 0.00 | 0.84 |
June | 0.00 | 0.571388E+10 | 0.00 | 0.00 | 0.242525E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
July | 0.00 | 0.650516E+10 | 0.00 | 0.00 | 0.423036E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
August | 0.00 | 0.600667E+10 | 0.00 | 0.00 | 0.422392E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 0.00 | 0.466171E+10 | 0.00 | 0.00 | 0.212463E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 0.197541E+09 | 0.913172E+09 | 0.00 | 2355478.13 | 0.260791E+09 | 0.00 | 0.139987E+09 | 0.00 | 0.60 |
November | 0.844612E+09 | 17112082.90 | 0.00 | 5858458.65 | 11185859.23 | 0.00 | 0.568937E+09 | 0.00 | 0.48 |
December | 0.156783E+10 | 0.00 | 0.00 | 3521339.94 | 0.00 | 0.00 | 0.668003E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.580900E+10 | 0.292873E+11 | 0.00 | 29404733.20 | 0.150892E+11 | 0.00 | 0.371422E+10 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.161366E+10 | 0.650516E+10 | 0.00 | 7061536.47 | 0.423036E+10 | 0.00 | 0.823326E+09 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160248E+10 | 0.00 | 0.00 | 10672673.74 | 0.00 | 0.00 | 0.250283E+10 | 0.00 | 0.47 |
February | 0.985412E+09 | 380532.15 | 0.00 | 13421918.21 | 188379.28 | 0.00 | 0.180561E+10 | 0.00 | 0.51 |
March | 0.599987E+09 | 0.332331E+09 | 0.00 | 13970252.42 | 39060233.10 | 0.00 | 0.116444E+10 | 0.00 | 0.62 |
April | 0.119607E+09 | 0.185601E+10 | 0.00 | 4243889.51 | 0.600852E+09 | 0.00 | 0.115606E+09 | 0.00 | 0.73 |
May | 1467343.88 | 0.565292E+10 | 0.00 | 159690.72 | 0.160666E+10 | 0.00 | 3265661.44 | 0.00 | 0.71 |
June | 0.00 | 0.817889E+10 | 0.00 | 0.00 | 0.304859E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
July | 0.00 | 0.103379E+11 | 0.00 | 0.00 | 0.511993E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
August | 0.00 | 0.109049E+11 | 0.00 | 0.00 | 0.488716E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
September | 0.00 | 0.807424E+10 | 0.00 | 0.00 | 0.243380E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 0.178065E+09 | 0.204208E+10 | 0.00 | 5932322.31 | 0.233019E+09 | 0.00 | 0.299057E+09 | 0.00 | 0.69 |
November | 0.708566E+09 | 61316501.30 | 0.00 | 21138051.05 | 9446436.12 | 0.00 | 0.170211E+10 | 0.00 | 0.61 |
December | 0.136832E+10 | 0.00 | 0.00 | 14160524.39 | 0.00 | 0.00 | 0.248643E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.556390E+10 | 0.474410E+11 | 0.00 | 83699322.35 | 0.179787E+11 | 0.00 | 0.100794E+11 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.160248E+10 | 0.109049E+11 | 0.00 | 21138051.05 | 0.511993E+10 | 0.00 | 0.250283E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.185380E+10 | 0.00 | 0.00 | 4619056.41 | 0.00 | 0.00 | 0.139590E+10 | 0.00 | 0.54 |
February | 0.778598E+09 | 484732.86 | 0.00 | 8957023.29 | 75495.09 | 0.00 | 0.151536E+10 | 0.00 | 0.62 |
March | 0.412867E+09 | 0.297705E+09 | 0.00 | 14419421.12 | 33595532.31 | 0.00 | 0.124071E+10 | 0.00 | 0.88 |
April | 74596548.11 | 0.240504E+10 | 0.00 | 6115965.33 | 0.256153E+09 | 0.00 | 0.179241E+09 | 0.00 | 1.23 |
May | 1157262.32 | 0.564736E+10 | 0.00 | 212680.08 | 0.127983E+10 | 0.00 | 3387559.23 | 0.00 | 1.06 |
June | 0.00 | 0.912121E+10 | 0.00 | 0.00 | 0.219439E+10 | 0.00 | 0.00 | 0.00 | 1.12 |
July | 0.00 | 0.120283E+11 | 0.00 | 0.00 | 0.359645E+10 | 0.00 | 0.00 | 0.00 | 1.11 |
August | 0.00 | 0.151664E+11 | 0.00 | 0.00 | 0.224736E+10 | 0.00 | 0.00 | 0.00 | 1.22 |
September | 0.00 | 0.670685E+10 | 0.00 | 0.00 | 0.230932E+10 | 0.00 | 0.00 | 0.00 | 0.86 |
October | 0.164873E+09 | 0.145083E+10 | 0.00 | 4354255.67 | 0.250547E+09 | 0.00 | 0.258978E+09 | 0.00 | 0.83 |
November | 0.565082E+09 | 41799301.37 | 0.00 | 13863125.01 | 9145046.07 | 0.00 | 0.139971E+10 | 0.00 | 0.72 |
December | 0.746402E+09 | 0.00 | 0.00 | 12517636.71 | 0.00 | 0.00 | 0.262448E+10 | 0.00 | 0.65 |
Annual Sum or Average | 0.459738E+10 | 0.528660E+11 | 0.00 | 65059163.63 | 0.121769E+11 | 0.00 | 0.861777E+10 | 0.00 | 0.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.185380E+10 | 0.151664E+11 | 0.00 | 14419421.12 | 0.359645E+10 | 0.00 | 0.262448E+10 | 0.00 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.284279E+11 | 0.00 | 0.00 | 2123190.67 | 0.00 | 0.196742E+09 | 0.117039E+10 | 0.00 | 0.34 |
February | 0.158227E+11 | 0.00 | 0.00 | 20991540.24 | 19170682.94 | 0.00 | 0.374341E+10 | 0.00 | 0.35 |
March | 0.588590E+10 | 0.208005E+10 | 0.00 | 55308261.62 | 0.589652E+09 | 0.00 | 0.565885E+10 | 0.00 | 0.41 |
April | 0.473584E+09 | 0.148873E+11 | 0.00 | 24595304.68 | 0.555279E+10 | 0.00 | 0.807901E+09 | 0.00 | 0.55 |
May | 7914912.33 | 0.578275E+11 | 0.00 | 1308600.68 | 0.134949E+11 | 0.00 | 34185029.46 | 0.00 | 0.69 |
June | 0.00 | 0.894130E+11 | 0.00 | 0.00 | 0.215078E+11 | 0.00 | 0.00 | 0.00 | 0.71 |
July | 0.00 | 0.110797E+12 | 0.00 | 0.00 | 0.328464E+11 | 0.00 | 0.00 | 0.00 | 0.66 |
August | 0.00 | 0.109325E+12 | 0.00 | 0.00 | 0.265219E+11 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.674123E+11 | 0.00 | 0.00 | 0.168230E+11 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.220197E+10 | 0.124418E+11 | 0.00 | 16073032.87 | 0.246591E+10 | 0.00 | 0.110708E+10 | 0.00 | 0.43 |
November | 0.115571E+11 | 0.202279E+09 | 0.00 | 35777821.65 | 0.233257E+09 | 0.00 | 0.354159E+10 | 0.00 | 0.37 |
December | 0.251515E+11 | 0.00 | 0.00 | 4751549.07 | 2267148.67 | 11957299.20 | 0.203394E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.895286E+11 | 0.464386E+12 | 0.00 | 0.160929E+09 | 0.120057E+12 | 0.208699E+09 | 0.180973E+11 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.284279E+11 | 0.110797E+12 | 0.00 | 55308261.62 | 0.328464E+11 | 0.196742E+09 | 0.565885E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212819E+11 | 0.00 | 0.00 | 6403059.24 | 0.00 | 18706693.77 | 0.344187E+10 | 0.00 | 0.43 |
February | 0.109747E+11 | 0.00 | 0.00 | 31730435.11 | 15916247.97 | 0.00 | 0.590740E+10 | 0.00 | 0.47 |
March | 0.408941E+10 | 0.175587E+10 | 0.00 | 63382270.59 | 0.476766E+09 | 0.00 | 0.649825E+10 | 0.00 | 0.58 |
April | 0.320222E+09 | 0.141648E+11 | 0.00 | 27409266.30 | 0.392591E+10 | 0.00 | 0.906775E+09 | 0.00 | 0.78 |
May | 7696151.61 | 0.489514E+11 | 0.00 | 878173.10 | 0.103389E+11 | 0.00 | 24343719.87 | 0.00 | 0.91 |
June | 0.00 | 0.676055E+11 | 0.00 | 0.00 | 0.182164E+11 | 0.00 | 0.00 | 0.00 | 0.86 |
July | 0.00 | 0.808939E+11 | 0.00 | 0.00 | 0.270296E+11 | 0.00 | 0.00 | 0.00 | 0.78 |
August | 0.00 | 0.779928E+11 | 0.00 | 0.00 | 0.219776E+11 | 0.00 | 0.00 | 0.00 | 0.71 |
September | 0.00 | 0.523811E+11 | 0.00 | 0.00 | 0.137832E+11 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 0.168796E+10 | 0.102642E+11 | 0.00 | 20377071.50 | 0.204804E+10 | 0.00 | 0.134390E+10 | 0.00 | 0.58 |
November | 0.835533E+10 | 0.206108E+09 | 0.00 | 43840927.53 | 0.150045E+09 | 0.00 | 0.481233E+10 | 0.00 | 0.49 |
December | 0.183777E+11 | 0.00 | 0.00 | 10073176.42 | 1882275.16 | 8827734.39 | 0.421154E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.650949E+11 | 0.354216E+12 | 0.00 | 0.204094E+09 | 0.979642E+11 | 27534428.16 | 0.271464E+11 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.212819E+11 | 0.808939E+11 | 0.00 | 63382270.59 | 0.270296E+11 | 18706693.77 | 0.649825E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161570E+11 | 0.00 | 0.00 | 97244609.72 | 0.00 | 0.00 | 0.239477E+11 | 0.00 | 0.49 |
February | 0.950332E+10 | 14846985.51 | 0.00 | 0.117769E+09 | 7504382.35 | 0.00 | 0.172018E+11 | 0.00 | 0.53 |
March | 0.400164E+10 | 0.389251E+10 | 0.00 | 0.123877E+09 | 0.202269E+09 | 0.00 | 0.114385E+11 | 0.00 | 0.59 |
April | 0.401232E+09 | 0.206136E+11 | 0.00 | 35232376.65 | 0.444278E+10 | 0.00 | 0.104191E+10 | 0.00 | 0.67 |
May | 7887307.41 | 0.610687E+11 | 0.00 | 1425213.32 | 0.130773E+11 | 0.00 | 34796267.87 | 0.00 | 0.72 |
June | 0.00 | 0.881837E+11 | 0.00 | 0.00 | 0.221975E+11 | 0.00 | 0.00 | 0.00 | 0.70 |
July | 0.00 | 0.111993E+12 | 0.00 | 0.00 | 0.327308E+11 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.118295E+12 | 0.00 | 0.00 | 0.242621E+11 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.868138E+11 | 0.00 | 0.00 | 0.136327E+11 | 0.00 | 0.00 | 0.00 | 0.62 |
October | 0.973045E+09 | 0.229434E+11 | 0.00 | 48613603.58 | 0.117706E+10 | 0.00 | 0.319814E+10 | 0.00 | 0.69 |
November | 0.545391E+10 | 0.840785E+09 | 0.00 | 0.193361E+09 | 84856967.12 | 0.00 | 0.172365E+11 | 0.00 | 0.66 |
December | 0.138828E+11 | 770864.63 | 0.00 | 0.114795E+09 | 1516532.78 | 0.00 | 0.233144E+11 | 0.00 | 0.52 |
Annual Sum or Average | 0.503808E+11 | 0.514660E+12 | 0.00 | 0.732317E+09 | 0.111816E+12 | 0.00 | 0.974136E+11 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.161570E+11 | 0.118295E+12 | 0.00 | 0.193361E+09 | 0.327308E+11 | 0.00 | 0.239477E+11 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.229629E+11 | 0.00 | 0.00 | 14023598.52 | 0.00 | 11390569.37 | 0.380750E+10 | 0.00 | 0.47 |
February | 0.129564E+11 | 387049.71 | 0.00 | 29408298.79 | 16627787.47 | 0.00 | 0.493368E+10 | 0.00 | 0.51 |
March | 0.433800E+10 | 0.240654E+10 | 0.00 | 64232871.51 | 0.359297E+09 | 0.00 | 0.646300E+10 | 0.00 | 0.62 |
April | 0.337330E+09 | 0.172464E+11 | 0.00 | 26180070.24 | 0.334337E+10 | 0.00 | 0.788577E+09 | 0.00 | 0.85 |
May | 6247731.91 | 0.549170E+11 | 0.00 | 1277310.62 | 0.908152E+10 | 0.00 | 28489331.33 | 0.00 | 0.96 |
June | 0.00 | 0.799669E+11 | 0.00 | 0.00 | 0.155721E+11 | 0.00 | 0.00 | 0.00 | 0.95 |
July | 0.00 | 0.917101E+11 | 0.00 | 0.00 | 0.252106E+11 | 0.00 | 0.00 | 0.00 | 0.84 |
August | 0.00 | 0.916036E+11 | 0.00 | 0.00 | 0.202799E+11 | 0.00 | 0.00 | 0.00 | 0.79 |
September | 0.00 | 0.592349E+11 | 0.00 | 0.00 | 0.130485E+11 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 0.165515E+10 | 0.120177E+11 | 0.00 | 17295173.67 | 0.182891E+10 | 0.00 | 0.125802E+10 | 0.00 | 0.62 |
November | 0.887343E+10 | 0.310467E+09 | 0.00 | 44160280.42 | 0.157111E+09 | 0.00 | 0.487985E+10 | 0.00 | 0.54 |
December | 0.205431E+11 | 0.00 | 0.00 | 17727332.66 | 2012195.68 | 0.00 | 0.400296E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.716725E+11 | 0.409414E+12 | 0.00 | 0.214305E+09 | 0.888999E+11 | 11390569.37 | 0.261621E+11 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.229629E+11 | 0.917101E+11 | 0.00 | 64232871.51 | 0.252106E+11 | 11390569.37 | 0.646300E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.248933E+10 | 0.00 | 0.00 | 24223.78 | 0.00 | 0.788502E+09 | 17673453.18 | 0.00 | 0.42 |
February | 0.166850E+10 | 0.00 | 0.00 | 1186458.97 | 959553.66 | 0.172611E+09 | 0.209397E+09 | 0.00 | 0.40 |
March | 0.657018E+09 | 0.147157E+09 | 0.00 | 4890352.74 | 50366783.18 | 0.00 | 0.503267E+09 | 0.00 | 0.43 |
April | 61280533.95 | 0.126292E+10 | 0.00 | 3205689.08 | 0.539324E+09 | 0.00 | 94630041.19 | 0.00 | 0.57 |
May | 652758.86 | 0.539722E+10 | 0.00 | 107076.86 | 0.137945E+10 | 0.00 | 3023061.09 | 0.00 | 0.71 |
June | 0.00 | 0.848286E+10 | 0.00 | 0.00 | 0.231253E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
July | 0.00 | 0.109335E+11 | 0.00 | 0.00 | 0.347036E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
August | 0.00 | 0.107267E+11 | 0.00 | 0.00 | 0.288500E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
September | 0.00 | 0.650516E+10 | 0.00 | 0.00 | 0.209685E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.246374E+09 | 0.104600E+10 | 0.00 | 1757652.80 | 0.302394E+09 | 0.00 | 78577764.14 | 0.00 | 0.46 |
November | 0.124054E+10 | 2447789.74 | 0.00 | 2715416.05 | 22569410.78 | 387641.49 | 0.255971E+09 | 0.00 | 0.39 |
December | 0.234047E+10 | 0.00 | 0.00 | 26546.30 | 8440.06 | 0.482550E+09 | 15173461.70 | 0.00 | 0.40 |
Annual Sum or Average | 0.870417E+10 | 0.445040E+11 | 0.00 | 13913416.59 | 0.130598E+11 | 0.144405E+10 | 0.117771E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.248933E+10 | 0.109335E+11 | 0.00 | 4890352.74 | 0.347036E+10 | 0.788502E+09 | 0.503267E+09 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.200494E+10 | 0.00 | 0.00 | 150334.34 | 0.00 | 0.415200E+09 | 77471343.17 | 0.00 | 0.50 |
February | 0.105702E+10 | 0.00 | 0.00 | 2479878.63 | 727834.66 | 66765337.12 | 0.475802E+09 | 0.00 | 0.49 |
March | 0.345482E+09 | 0.124715E+09 | 0.00 | 6557308.70 | 35637137.77 | 0.00 | 0.656006E+09 | 0.00 | 0.57 |
April | 35542943.26 | 0.123019E+10 | 0.00 | 3685320.66 | 0.336438E+09 | 0.00 | 0.107926E+09 | 0.00 | 0.79 |
May | 519024.54 | 0.460013E+10 | 0.00 | 79030.69 | 0.936856E+09 | 0.00 | 2206329.01 | 0.00 | 0.91 |
June | 0.00 | 0.648844E+10 | 0.00 | 0.00 | 0.174912E+10 | 0.00 | 0.00 | 0.00 | 0.85 |
July | 0.00 | 0.806989E+10 | 0.00 | 0.00 | 0.258246E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
August | 0.00 | 0.784138E+10 | 0.00 | 0.00 | 0.213251E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 0.00 | 0.509977E+10 | 0.00 | 0.00 | 0.157482E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
October | 0.151541E+09 | 0.896415E+09 | 0.00 | 2434564.55 | 0.209009E+09 | 0.00 | 0.124655E+09 | 0.00 | 0.59 |
November | 0.723682E+09 | 7299360.38 | 0.00 | 4230202.50 | 11783916.41 | 0.00 | 0.458334E+09 | 0.00 | 0.48 |
December | 0.185210E+10 | 0.00 | 0.00 | 238095.76 | 6401.90 | 0.175561E+09 | 0.124408E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.617083E+10 | 0.343582E+11 | 0.00 | 19854735.82 | 0.956937E+10 | 0.657526E+09 | 0.202681E+10 | 0.00 | 0.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.200494E+10 | 0.806989E+10 | 0.00 | 6557308.70 | 0.258246E+10 | 0.415200E+09 | 0.656006E+09 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.176195E+10 | 0.00 | 0.00 | 6590715.49 | 0.00 | 0.350470E+09 | 0.181608E+10 | 0.00 | 0.52 |
February | 0.110467E+10 | 540443.06 | 0.00 | 9564071.48 | 436263.32 | 41283274.49 | 0.148483E+10 | 0.00 | 0.53 |
March | 0.411289E+09 | 0.260823E+09 | 0.00 | 12317850.31 | 21584150.09 | 0.00 | 0.114609E+10 | 0.00 | 0.59 |
April | 48220438.72 | 0.172114E+10 | 0.00 | 4692423.22 | 0.427331E+09 | 0.00 | 0.136152E+09 | 0.00 | 0.68 |
May | 654139.65 | 0.569630E+10 | 0.00 | 118441.37 | 0.130398E+10 | 0.00 | 3076655.56 | 0.00 | 0.73 |
June | 0.00 | 0.838707E+10 | 0.00 | 0.00 | 0.234776E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
July | 0.00 | 0.110298E+11 | 0.00 | 0.00 | 0.344948E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
August | 0.00 | 0.115172E+11 | 0.00 | 0.00 | 0.270306E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.830667E+10 | 0.00 | 0.00 | 0.172174E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 0.139734E+09 | 0.189349E+10 | 0.00 | 7648784.24 | 0.153030E+09 | 0.00 | 0.278440E+09 | 0.00 | 0.69 |
November | 0.567053E+09 | 33873314.76 | 0.00 | 18308304.88 | 8791890.04 | 0.00 | 0.166940E+10 | 0.00 | 0.64 |
December | 0.156566E+10 | 5275.34 | 0.00 | 8090655.93 | 4157.25 | 97347157.29 | 0.183625E+10 | 0.00 | 0.52 |
Annual Sum or Average | 0.559924E+10 | 0.488469E+11 | 0.00 | 67331246.92 | 0.121372E+11 | 0.489101E+09 | 0.837031E+10 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.176195E+10 | 0.115172E+11 | 0.00 | 18308304.88 | 0.344948E+10 | 0.350470E+09 | 0.183625E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209001E+10 | 0.00 | 0.00 | 800277.95 | 0.00 | 0.439425E+09 | 0.286569E+09 | 0.00 | 0.56 |
February | 0.137272E+10 | 0.00 | 0.00 | 2285772.37 | 820014.30 | 46198656.98 | 0.382998E+09 | 0.00 | 0.55 |
March | 0.457539E+09 | 0.167355E+09 | 0.00 | 6121923.94 | 28145930.75 | 0.00 | 0.614746E+09 | 0.00 | 0.62 |
April | 37747010.55 | 0.140037E+10 | 0.00 | 3543786.63 | 0.325709E+09 | 0.00 | 0.100799E+09 | 0.00 | 0.84 |
May | 514119.27 | 0.492269E+10 | 0.00 | 105168.06 | 0.955483E+09 | 0.00 | 2466227.60 | 0.00 | 0.95 |
June | 0.00 | 0.734402E+10 | 0.00 | 0.00 | 0.171224E+10 | 0.00 | 0.00 | 0.00 | 0.94 |
July | 0.00 | 0.873110E+10 | 0.00 | 0.00 | 0.278031E+10 | 0.00 | 0.00 | 0.00 | 0.85 |
August | 0.00 | 0.876424E+10 | 0.00 | 0.00 | 0.224213E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
September | 0.00 | 0.554039E+10 | 0.00 | 0.00 | 0.171939E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
October | 0.186108E+09 | 0.996257E+09 | 0.00 | 2150864.84 | 0.218085E+09 | 0.00 | 94856892.29 | 0.00 | 0.64 |
November | 0.934490E+09 | 11189420.17 | 0.00 | 4163006.93 | 13181578.52 | 0.00 | 0.394738E+09 | 0.00 | 0.55 |
December | 0.205312E+10 | 0.00 | 0.00 | 1072862.03 | 7212.70 | 0.100380E+09 | 0.280255E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.713224E+10 | 0.378776E+11 | 0.00 | 20243662.76 | 0.999550E+10 | 0.586004E+09 | 0.215743E+10 | 0.00 | 0.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.209001E+10 | 0.876424E+10 | 0.00 | 6121923.94 | 0.278031E+10 | 0.439425E+09 | 0.614746E+09 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 8654138.35 | 0.00 | 0.00 | 0.623222E+09 | 0.00 | 0.58 |
February | 0.00 | 5571301.20 | 0.00 | 18067452.19 | 0.00 | 0.00 | 0.307573E+09 | 0.00 | 0.59 |
March | 0.00 | 0.106276E+09 | 0.00 | 19626366.74 | 0.00 | 0.00 | 0.106832E+09 | 0.00 | 0.59 |
April | 0.00 | 0.323166E+09 | 0.00 | 9086480.20 | 0.00 | 0.00 | 8942789.34 | 0.00 | 0.59 |
May | 0.00 | 0.840680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.127956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.174888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.171928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.124890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.404048E+09 | 0.00 | 2219262.78 | 0.00 | 0.00 | 5839348.59 | 0.00 | 0.59 |
November | 0.00 | 37191948.77 | 0.00 | 26484438.20 | 0.00 | 0.00 | 0.163138E+09 | 0.00 | 0.59 |
December | 0.00 | 4599.62 | 0.00 | 46138839.67 | 0.00 | 0.00 | 0.502317E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.771357E+10 | 0.00 | 0.130277E+09 | 0.00 | 0.00 | 0.171786E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.174888E+10 | 0.00 | 46138839.67 | 0.00 | 0.00 | 0.623222E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 60765976.05 | 0.00 | 0.00 | 0.634309E+10 | 0.00 | 0.58 |
February | 0.00 | 53132929.88 | 0.00 | 0.159618E+09 | 0.00 | 0.00 | 0.311668E+10 | 0.00 | 0.59 |
March | 0.00 | 0.105924E+10 | 0.00 | 0.185134E+09 | 0.00 | 0.00 | 0.108017E+10 | 0.00 | 0.59 |
April | 0.00 | 0.325654E+10 | 0.00 | 87817332.28 | 0.00 | 0.00 | 91257827.14 | 0.00 | 0.59 |
May | 0.00 | 0.834591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.127519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.174510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.173244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.123487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.401234E+10 | 0.00 | 20968437.19 | 0.00 | 0.00 | 62012636.72 | 0.00 | 0.59 |
November | 0.00 | 0.369014E+09 | 0.00 | 0.244604E+09 | 0.00 | 0.00 | 0.165634E+10 | 0.00 | 0.59 |
December | 0.00 | 36387.21 | 0.00 | 0.418980E+09 | 0.00 | 0.00 | 0.506321E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.769723E+11 | 0.00 | 0.117789E+10 | 0.00 | 0.00 | 0.174128E+11 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.174510E+11 | 0.00 | 0.418980E+09 | 0.00 | 0.00 | 0.634309E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125770E+09 | 0.00 | 0.00 | 2956206.50 | 0.00 | 0.00 | 0.517453E+09 | 0.00 | 0.58 |
February | 0.00 | 6411699.49 | 0.00 | 14112916.01 | 0.00 | 0.00 | 0.301920E+09 | 0.00 | 0.59 |
March | 0.00 | 0.114766E+09 | 0.00 | 17204437.23 | 0.00 | 0.00 | 99943182.08 | 0.00 | 0.59 |
April | 0.00 | 0.345201E+09 | 0.00 | 7790812.56 | 0.00 | 0.00 | 7675519.72 | 0.00 | 0.59 |
May | 0.00 | 0.853782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.129449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.176536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.177071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.125325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.417533E+09 | 0.00 | 1803225.79 | 0.00 | 0.00 | 5185530.55 | 0.00 | 0.59 |
November | 0.00 | 41936525.12 | 0.00 | 22458367.38 | 0.00 | 0.00 | 0.155443E+09 | 0.00 | 0.59 |
December | 0.00 | 33346.54 | 0.00 | 38810433.98 | 0.00 | 0.00 | 0.493602E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.125770E+09 | 0.786348E+10 | 0.00 | 0.105136E+09 | 0.00 | 0.00 | 0.158122E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.125770E+09 | 0.177071E+10 | 0.00 | 38810433.98 | 0.00 | 0.00 | 0.517453E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.518074E+09 | 0.00 | 0.00 | 0.139754E+11 | 0.00 | 0.66 |
February | 0.00 | 0.161721E+09 | 0.00 | 0.909772E+09 | 0.00 | 0.00 | 0.671620E+10 | 0.00 | 0.66 |
March | 0.00 | 0.246917E+10 | 0.00 | 0.879791E+09 | 0.00 | 0.00 | 0.202313E+10 | 0.00 | 0.66 |
April | 0.00 | 0.467584E+10 | 0.00 | 0.630141E+09 | 0.00 | 0.00 | 0.361787E+09 | 0.00 | 0.67 |
May | 0.00 | 0.197030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
June | 0.00 | 0.289782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.390304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.330377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.299069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.949115E+10 | 0.00 | 90104904.49 | 0.00 | 0.00 | 87005648.59 | 0.00 | 0.66 |
November | 0.00 | 0.891780E+09 | 0.00 | 0.123634E+10 | 0.00 | 0.00 | 0.325384E+10 | 0.00 | 0.66 |
December | 0.00 | 0.00 | 0.00 | 0.224999E+10 | 0.00 | 0.00 | 0.110048E+11 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.168346E+12 | 0.00 | 0.651421E+10 | 0.00 | 0.00 | 0.374221E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.390304E+11 | 0.00 | 0.224999E+10 | 0.00 | 0.00 | 0.139754E+11 | 0.00 | 0.68 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:03:25
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.290801E+12 | 0.297082E+10 | 0.00 | 0.841500E+12 | 0.124387E+13 |
February | 0.336479E+12 | 0.346056E+10 | 0.00 | 0.545281E+12 | 0.176774E+13 |
March | 0.456868E+12 | 0.203902E+10 | 0.00 | 0.251530E+12 | 0.298370E+13 |
April | 0.496319E+12 | -0.161950E+10 | 0.00 | -0.267228E+12 | 0.400853E+13 |
May | 0.540680E+12 | -0.736528E+10 | 0.00 | -0.912278E+12 | 0.379056E+13 |
June | 0.504740E+12 | -0.833458E+10 | 0.00 | -0.142033E+13 | 0.461809E+13 |
July | 0.410556E+12 | -0.177739E+11 | 0.00 | -0.195028E+13 | 0.555892E+13 |
August | 0.343882E+12 | -0.124289E+11 | 0.00 | -0.195881E+13 | 0.592804E+13 |
September | 0.371757E+12 | -0.716932E+10 | 0.00 | -0.142695E+13 | 0.364143E+13 |
October | 0.354566E+12 | -653284901.4 | 0.00 | -0.154198E+12 | 0.301859E+13 |
November | 0.307619E+12 | 0.856992E+09 | 0.00 | 0.436688E+12 | 0.266316E+13 |
December | 0.266531E+12 | 0.295404E+10 | 0.00 | 0.782655E+12 | 0.259671E+13 |
Annual Sum or Average | 0.468080E+13 | -0.430633E+11 | 0.00 | -0.523243E+13 | 0.418193E+14 |
Minimum of Months | 0.266531E+12 | -0.177739E+11 | 0.00 | -0.195881E+13 | 0.124387E+13 |