Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750

Simulation Timestamp: 2023-10-16 09:03:16


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 33686.75 727.26 727.26
Net Site Energy 33686.75 727.26 727.26
Total Source Energy 98001.72 2115.74 2115.74
Net Source Energy 98001.72 2115.74 2115.74


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 3397.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3205.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3711.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 671.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1941.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2703.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 416.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 812.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3188.49
Humidification 840.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312.78
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 771.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 29517.66 4169.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5781.45
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 3397.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 3205.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 3711.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 671.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5871.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 87.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2703.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 416.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 812.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3188.49
Humidification General 840.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312.78
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 771.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 3397.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 3205.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 3711.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 671.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1941.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2703.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 416.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 812.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3188.49
Humidification Unassigned 840.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312.78
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 771.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 94.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 172.28 90.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.12
Other 370.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 637.25 90.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.12


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 94.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 172.28 90.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.12
Other 370.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 637.25 90.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.12


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 29517.660 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 29517.660 100.00
     
Total On-Site and Utility Electric Sources 29517.660 100.00
Total Electricity End Uses 29517.660 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 5781.45 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 5781.45 100.00
Total Water End Uses 5781.45 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 115.33
Time Setpoint Not Met During Occupied Cooling 480.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 5942.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03
RunPeriod RUNPERIOD 1
Weather File Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Latitude [deg] 47.47
Longitude [deg] -111.4
Elevation [m] 1117.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 9.3279 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.3279 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 9.3279 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.3279 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.3279 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.3279 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 16.0861 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 16.0861 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 16.0861 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 9.3279 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.3913 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.3913 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.3279 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 9.3279 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 9.3279 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 9.3279 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 9.3279 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 9.3279 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 9.3279 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 9.3279 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 9.3279 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 9.3279 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 9.3279 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 9.3279 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 9.3279 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 9.3279 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 9.3279 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 9.3279 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 16.0861 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 16.0861 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 16.0861 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 9.3279 18.58 484.4232  
Total 46320.38             9.3913 9.29 17.8789  
Conditioned Total 46320.38             9.3913 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.8860 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 07-AUG-15:39 09-JAN-07:19 - - - - - - - - - - 25-JUL-11:50
Heating 0.00 2285209.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 426109.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 316816.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 794004.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 84885.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 301770.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 55015.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 81829.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 16223.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 27391.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2076655.13 2312600.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 2285209.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 426109.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 316816.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 5451.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 301770.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 55015.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 81829.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 16223.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 27391.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 3682.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 10152.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 11753.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2125.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48180.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6150.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8562.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1320.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 2574.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 2662.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 836.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 93482.43 4519.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 79.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 219.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 253.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 45.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 184.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 28.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 55.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 57.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 18.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2018.17 97.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 79.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 219.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 253.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 45.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 132.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 184.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 28.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 55.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 57.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 18.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2018.17 97.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 6.47
DATACENTER_BOT_ZN_6 DIRECT AIR 0.570008
DATACENTER_MID_ZN_6 DIRECT AIR 5.46
DATACENTER_TOP_ZN_6 DIRECT AIR 0.555614
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 24.47
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 6.79 0.279943 0.300000 2.04 0.746515 0.500000 0.001361 0.000238 2.04 12.80 0.008000
CORE_MID VAV BOX COMPONENT 63.87 0.297787 0.307000 19.61 0.794099 0.500000 0.001279 0.004597 19.61 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 6.18 0.307671 0.326000 2.02 0.820455 0.500000 0.001238 0.001001 3.90 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.08 0.220653 0.300000 0.324701 0.588407 0.500000 0.001727 0.000175 0.682446 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.34 0.114754 0.300000 0.402354 0.306009 0.500000 0.003320 0.000120 0.468499 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.70 0.140701 0.300000 0.509219 0.375203 0.500000 0.002708 0.000192 0.750352 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.67 0.092014 0.300000 0.501787 0.300000 0.500000 0.004141 0.000109 0.501787 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 10.19 0.234469 0.300000 3.06 0.625250 0.500000 0.001625 0.002504 9.77 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 14.10 0.109118 0.300000 4.23 0.300000 0.500000 0.003492 0.001661 6.48 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 17.07 0.139909 0.300000 5.12 0.373090 0.500000 0.002723 0.002534 9.89 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 15.16 0.101491 0.300000 4.55 0.300000 0.500000 0.003754 0.001628 6.35 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.29 0.185614 0.300000 0.385995 0.494972 0.500000 0.002053 0.000330 1.29 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.41 0.108849 0.300000 0.424179 0.300000 0.500000 0.003500 0.000218 0.848943 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.84 0.129706 0.300000 0.552386 0.345882 0.500000 0.002937 0.000333 1.30 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.61 0.095365 0.300000 0.484156 0.300000 0.500000 0.003995 0.000217 0.846961 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 27176.71 0.000238 577.10
CORE_MID VAV BOX REHEAT COIL 525448.40 0.004597 13336.12
CORE_TOP VAV BOX REHEAT COIL 114474.95 0.001001 3020.42
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 20010.40 0.000175 527.73
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 13735.44 0.000120 362.22
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 21997.98 0.000192 580.11
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 12407.03 0.000109 305.53
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 286203.60 0.002504 7545.67
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 189849.57 0.001661 5005.23
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 289677.87 0.002534 7637.22
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 186046.86 0.001628 4905.02
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 37689.39 0.000330 993.53
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 24867.16 0.000218 655.51
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 38120.11 0.000333 1004.88
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 24809.04 0.000217 653.98
VAV_BOT WITH REHEAT HEATING COIL 99832.45 0.000873 1534.40
VAV_MID WITH REHEAT HEATING COIL 1054592.05 0.009226 15670.25
VAV_TOP WITH REHEAT HEATING COIL 103926.02 0.000909 1594.65
CAV_BAS HEATING COIL 309103.33 0.002704 6611.30
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 6.29 3.78 12.59 3.78 10.93 10.93 0.300000 0.345557 10.93
VAV_MID WITH REHEAT 60.20 36.57 120.40 49.56 101.25 101.25 0.300000 0.489528 101.25
VAV_TOP WITH REHEAT 6.17 3.86 12.34 8.18 11.30 11.30 0.300000 0.724143 11.30
CAV_BAS 6.47 6.47 6.47 6.47 6.47 6.47 1.00 1.00 6.47
AIRLOOP DATACENTER BASEMENT 24.47 24.47 24.47 24.47 24.47 24.47 1.00 0.999991 24.47
AIRLOOP DATACENTER BOT 0.570008 0.570008 0.570008 0.570008 0.570008 0.570008 1.00 1.00 0.570008
AIRLOOP DATACENTER MID 5.46 5.46 5.46 5.46 5.46 5.46 1.00 1.00 5.46
AIRLOOP DATACENTER TOP 0.555614 0.555614 0.555614 0.555614 0.555614 0.555614 1.00 1.00 0.555614
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 10.93  
VAV_MID WITH REHEAT_OA_CONTROLLER 101.25  
VAV_TOP WITH REHEAT_OA_CONTROLLER 11.30  
CAV_BAS_OA_CONTROLLER 6.47 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 24.47 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.570008 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 5.46 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.555614 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 26.19 6.67 10.68 0.007088 0.007000 184210.74 0.007837 10.93
VAV_MID WITH REHEAT COOLING COIL 26.44 6.67 10.68 0.007076 0.007000 1730478.66 0.073619 101.25
VAV_TOP WITH REHEAT COOLING COIL 26.12 6.67 10.68 0.007074 0.007000 189241.84 0.008051 11.30
CAV_BAS COOLING COIL 25.80 6.67 11.22 0.007242 0.007000 105376.19 0.004483 6.47
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 10.93
VAV_MID WITH REHEAT FAN 101.25
VAV_TOP WITH REHEAT FAN 11.30
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.007837 0.000061
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000873  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.073619 0.000006
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.009226  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.008051 0.000059
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000909  
CAV_BAS_COOLC_CONTROLLER 0.004483 0.000106
CAV_BAS_HEATC_CONTROLLER 0.002704  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 6.47
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 24.47 465166.58 261784.15 0.011392
AIRLOOP DATACENTER BOT COOLING COIL 0.570008 10529.65 5988.34 0.000258
AIRLOOP DATACENTER MID COOLING COIL 5.46 100857.57 57346.94 0.002470
AIRLOOP DATACENTER TOP COOLING COIL 0.555614 10265.81 5837.55 0.000251
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 24.47 24.47 24.47 24.47 465166.58 465166.58 24207.99 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.570008 0.570008 0.570008 0.570008 10529.65 10529.65 1118.31 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 5.46 5.46 5.46 5.46 100857.57 100857.57 11183.09 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.555614 0.555614 0.555614 0.555614 10265.81 10265.81 1118.31 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 24.47
AIRLOOP DATACENTER BOT SUPPLY FAN 0.570008
AIRLOOP DATACENTER MID SUPPLY FAN 5.46
AIRLOOP DATACENTER TOP SUPPLY FAN 0.555614
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 24.47 465166.58 0.011392
AIRLOOP DATACENTER BOT HEATING COIL 0.570008 10529.65 0.000258
AIRLOOP DATACENTER MID HEATING COIL 5.46 100857.57 0.002470
AIRLOOP DATACENTER TOP HEATING COIL 0.555614 10265.81 0.000251
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 24207.99
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 1118.31
AIRLOOP DATACENTER MID_SUPPHEATCOIL 11183.09
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 1118.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000191 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.093989 19367.66  
HEATSYS1 PUMP 0.029569 8905.02 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.093989 11.28
HEATSYS1 0.029569 3.55
COOLSYS1_SUPPLY 0.093989 11.28
SINGLE WATER PLANT LOOP 0.014371 1.72
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.093989 0.093989 394519.18 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 3379968.34 3379968.34 0.029569
CENTRAL BOILER 591969.18 579237.53 0.014371
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.093989 13408.88
PLANT CIRC PUMP 0.014371 3665.37
SWHSYS1 PUMP 0.000440 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.093989 0.047347 1115664.70 1120956.40 0.055472
COOLSYS1 CHILLER2 0.093989 0.047347 1115664.70 1120956.40 0.055472
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.014371 139666.47 55634.27 69833.23 7879.72 21031.62
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.110944 13.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.110944 33413.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 49.02 1331643.43 9.80 166455.43
TOWERWATERSYS COOLTOWER 2 49.02 1331643.43 9.80 166455.43
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.057618
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 8.60 2.80 -4.10 -8.80 -2.20 0.30 6.70 10.10 16.50 20.60 19.20 14.70


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Great Falls Intl Arpt MT USA TMY3 WMO#=727750 47.47 -111.38 -7.00 1117.00 88606 1.0531


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 7.03 29.40 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 9.328 4.842 0.000 0.000 0.000 0.000 14.170 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 9.328 8.070 0.000 0.000 0.000 0.000 17.398 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 16.086 215.299 0.000 0.000 0.000 0.000 231.385 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 16.086 215.299 0.000 0.000 0.000 0.000 231.385 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 16.086 215.299 0.000 0.000 0.000 0.000 231.385 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 9.328 484.423 0.000 0.000 0.000 0.000 493.751 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 25926.330 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25926.330
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 23283.667 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 23283.667
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 23283.667 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 23283.667
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 23283.667 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 23283.667
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2923.497 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.497
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2923.561 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.561
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2923.497 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.497
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2923.561 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.561
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2923.497 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.497
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2923.561 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2923.561
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1884.012 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1884.012
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 7310.116 9.328 173.302 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 7310.116
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 582.361 16.086 298.861 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 582.361
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 582.361 16.086 298.861 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 582.361
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 582.361 16.086 298.861 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 582.361


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.147 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.072 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.485 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.7043
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.7653
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5060
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.312
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 2.312
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
47 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
48 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
49 0 21.357363 0.71091016E-01 5.4032014  
50 9 0.18777991E-14 0.39318316E-16 -0.13945218E-09 -0.53504997E-17
51 8 0.20428582E-07 0.15263370E-12 0.36243033E-03 -0.23227999E-09
52 7 -0.11782580E-01 0.80534805E-08 -0.22424787E-01 0.13397222E-03
53 6 0.39287835 0.28244099E-05 0.46145507 -0.46007477E-02
54 5 -5.0688419 0.10619431E-03 -4.3595097 0.61674563E-01
55 4 32.464389 0.87416084E-03 21.120657 -0.41497362
56 3 -110.08041 0.19158287E-02 -54.991947 1.4986409
57 2 195.99541 0.10830235E-02 77.295382 -2.8826816
58 1 -170.74495 0.11614893E-03 -55.086664 2.7382339
59 0 57.057407 0.66454694E-06 15.586789  
60 9 -0.35772101E-15 0.35300796E-16 -0.14299885E-09 0.43432634E-17
61 8 0.20929462E-07 0.14329262E-12 0.36779278E-03 -0.23797519E-09
62 7 -0.11942934E-01 0.75175974E-08 -0.22655780E-01 0.13579551E-03
63 6 0.39723595 0.26304111E-05 0.46517473 -0.46521131E-02
64 5 -5.1113728 0.98704798E-04 -4.3881162 0.62201922E-01
65 4 32.652551 0.81106559E-03 21.232557 -0.41747184
66 3 -110.48086 0.17747443E-02 -55.213214 1.5044261
67 2 196.39242 0.10018625E-02 77.498162 -2.8889858
68 1 -170.89164 0.10730575E-03 -55.145342 2.7408049
69 0 57.057407 0.61309336E-06 15.576862  
70 9 0.62620750E-15 0.53459335E-16 -0.12331227E-09 -0.46720721E-17
71 8 0.18149323E-07 0.19273772E-12 0.33743729E-03 -0.20636407E-09
72 7 -0.11033179E-01 0.10459398E-07 -0.21344557E-01 0.12545125E-03
73 6 0.37251059 0.37098382E-05 0.44401761 -0.43606628E-02
74 5 -4.8700128 0.14084247E-03 -4.2251796 0.59209231E-01
75 4 31.584523 0.11694623E-02 20.594689 -0.40329204
76 3 -108.20727 0.25827026E-02 -53.951706 1.4715810
77 2 194.13760 0.14699268E-02 76.342983 -2.8531817
78 1 -170.05820 0.15862972E-03 -54.812808 2.7261979
79 0 57.057407 0.91374417E-06 15.634538  
80 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
81 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
82 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
83 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
84 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
85 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
86 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
87 0 0.43108349 0.21254961E-04 60.838472  
88 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
89 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
90 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
91 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
92 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
93 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
94 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
95 0 0.43108349 0.21254961E-04 60.838472  
96 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
97 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
98 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
99 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
100 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
101 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
102 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
103 0 0.43108349 0.21254961E-04 60.838472  
104 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
105 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
106 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
107 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
108 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
109 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
110 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
111 0 0.43108349 0.21254961E-04 60.838472  
112 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
113 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
114 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
115 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
116 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
117 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
118 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
119 0 0.43108349 0.21254961E-04 60.838472  
120 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
121 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
122 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
123 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
124 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
125 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
126 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
127 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.3622_SHGC_EAST_0.4 35 1 VerySmooth 2.058 2.058 1.000 0.401    
2 WINDOW_U_0.3622_SHGC_SOUTH_0.4 36 1 VerySmooth 2.058 2.058 1.000 0.401    
3 WINDOW_U_0.3622_SHGC_WEST_0.4 37 1 VerySmooth 2.058 2.058 1.000 0.401    
4 WINDOW_U_0.3622_SHGC_NORTH_0.4 38 1 VerySmooth 2.058 2.058 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.63487E-002 0.31435 0.48131 0.48131 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11603 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.63487E-002 0.31435 0.48131 0.48131 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11603 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.63487E-002 0.31435 0.48131 0.48131 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11603 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.63487E-002 0.31435 0.48131 0.48131 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11603 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.496 7.5104E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.4803E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.4823E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.1356E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 6.1372E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.5287E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.5299E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.9650E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.9658E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.5256E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.6567E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.1737E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 6.2878E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.5607E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6550E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.9845E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.0341E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1338
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.1635E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1537
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.5149E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 9.5460E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.1244E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1298E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.4495E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.5360E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.7125E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.1852E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 6.3502E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.5692E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6882E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.9850E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.0355E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.4802E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.4826E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.1354E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 6.1375E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.5286E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.5302E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.9650E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.9657E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.9356E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.3574E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.8593E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.3554E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.2341E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.3671E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.3625E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.3966E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.9134E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0176E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.8337E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.8818E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.8114E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.4776E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.2472E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.5878E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.8013E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.9010E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.6817E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.7553E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.1933E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.2235E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.3626E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.3972E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1610E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1631E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8300E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8318E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.6002E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6015E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9651E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9658E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2071E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3238E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8688E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9639E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.6326E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7051E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9850E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0356E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.5928E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0905E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7862E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5915E-002
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7858E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1027E-002
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.1298E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4491E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2047E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3243E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8651E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9584E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.6259E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6839E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9846E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0341E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1609E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1629E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8299E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8315E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.6000E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6011E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9650E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9657E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.0671E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.1729E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.7366E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.8133E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.6833E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.7100E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3627E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.3972E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.5138E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4180E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.0462E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1137E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.7632E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.0352E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.2472E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.5878E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.1557E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.4083E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.8546E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.1297E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.7200E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.8324E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3624E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.3966E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1307
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1040
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1464
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1201
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1017
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.6289E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 4.7714E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.3115E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.7452E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.1233E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.6590E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.9809E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.5532E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.4116E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.8823E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.3360E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.2473E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.0013E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.3722E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.3702E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.3677E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.8123E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.7714E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.3111E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.2277E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.3362E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.7188E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.9703E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.4291E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.8571E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.8823E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.3360E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1305
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1041
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1462
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1202
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1017
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.6394E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 4.7768E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.3160E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.7405E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.1270E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.6553E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.9849E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.5544E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.4174E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.8875E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.3404E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.2416E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.0024E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.3682E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.3712E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.3694E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.8151E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.7768E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.3156E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.2232E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.3386E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.7155E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.9726E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.4304E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.8618E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.8875E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.3404E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 78387.80853 78387.80853 6.47407 6.47407 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 21.56000 6.28881E-003 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 82273.91105 82273.91105 6.79439 6.79439 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 21.56000 6.28881E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 9227.34779 9227.34779 0.44638 1.07782 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 773613.85370 773613.85370 63.87256 63.87256 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 21.56000 6.28881E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 352773.19363 352773.19363 17.08187 17.08187 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 74880.97514 74880.97514 6.18208 6.18208 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 21.56000 6.28881E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 80130.06328 80130.06328 3.90018 3.90018 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 12992.98707 12992.98707 1.08234 1.08234 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.40000 6.30683E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 14004.02258 14004.02258 0.68245 0.68245 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 16100.42153 16100.42153 1.34118 1.34118 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 24.09333 6.29258E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 9611.96117 9611.96117 0.46850 0.46850 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 20376.61395 20376.61395 1.69740 1.69740 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 33.13333 6.30642E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 15393.54707 15393.54707 0.75035 0.75035 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 20079.35392 20079.35392 1.67262 1.67262 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 30.36000 6.30211E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 7991.39497 7991.39497 0.38927 0.38927 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 122275.10923 122275.10923 10.18560 10.18560 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.40000 6.30683E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 200265.88498 200265.88498 9.76741 9.76741 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 169321.00044 169321.00044 14.10443 14.10443 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 25.96000 6.29539E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 132841.97254 132841.97254 6.47935 6.47935 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 204922.66876 204922.66876 17.07013 17.07013 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 33.26667 6.30663E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 202694.95481 202694.95481 9.88613 9.88613 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 182046.26311 182046.26311 15.16446 15.16446 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 30.36000 6.30211E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 130183.00372 130183.00372 6.34945 6.34945 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 13915.48179 13915.48179 1.15916 1.15916 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 33.08000 6.30633E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 26368.98672 26368.98672 1.28665 1.28665 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 16974.00908 16974.00908 1.41393 1.41393 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 26.41333 6.29608E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 17397.95006 17397.95006 0.84894 0.84894 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 22104.30035 22104.30035 1.84129 1.84129 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.40000 6.30683E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 26670.13923 26670.13923 1.30137 1.30137 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 19374.05535 19374.05535 1.61385 1.61385 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 30.36000 6.30211E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 17357.27514 17357.27514 0.84696 0.84696 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8675.43569 8675.43569 0.57001 0.57001 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 26.28000 6.29588E-003 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -27.60000 3.41898E-004 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 83069.49152 83069.49152 5.45800 5.45800 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 26.28000 6.29588E-003 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -27.60000 3.41898E-004 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8456.34415 8456.34415 0.55561 0.55561 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 26.57333 6.29632E-003 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -27.60000 3.41898E-004 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 372452.66094 372452.66094 24.47120 24.47120 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.84000 6.28481E-003 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:50:00 -27.60000 3.41898E-004 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 151923.12 10.92837 10.92837 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 106253.88 3.36839 3.36839 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:10:00
3 VAV_MID WITH REHEAT Cooling Sensible 1413040.05 101.24908 101.24908 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 1083253.27 49.56421 49.56421 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00
5 VAV_TOP WITH REHEAT Cooling Sensible 158720.29 11.30177 11.30177 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 108507.10 8.18410 8.18410 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 02:30:00
7 CAV_BAS Cooling Sensible 78972.58 6.47407 6.47407 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 85856.97 1.20016 1.20016 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 369515.79 24.47142 24.47142 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 24207.99 0.33839 0.33839 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8553.12 0.57001 0.57001 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 1118.31 1.56323E-002 1.56323E-002 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 81892.91 5.45800 5.45800 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 11183.09 0.15632 0.15632 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 8341.36 0.55561 0.55561 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 1118.31 1.56323E-002 1.56323E-002 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.47407
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.79439
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27994
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.03832
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.74652
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.36099E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.37754E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.03832
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 27176.70936
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.37754E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 577.09924
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 63.87256
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.29779
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30700
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 19.60888
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.79410
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.27944E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.59685E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 19.60888
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 525448.40488
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.59685E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 13336.11814
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.18208
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30767
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32600
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.01536
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.82045
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.23834E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.00148E-003
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.90018
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 114474.94732
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.00148E-003
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3020.41839
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.08234
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22065
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.32470
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58841
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.72670E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.75060E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.68245
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 20010.39903
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.75060E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 527.73014
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.34118
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11475
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.40235
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30601
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.32016E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.20164E-004
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.46850
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13735.43802
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.20164E-004
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 362.22142
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.69740
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14070
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.50922
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37520
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.70786E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.92448E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.75035
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 21997.97573
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.92448E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 580.10556
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.67262
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.20141E-002
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.50179
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.14067E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.08542E-004
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.50179
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12407.02618
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.08542E-004
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 305.53127
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.18560
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23447
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.05568
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.62525
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.62495E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.50383E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.76741
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 286203.60007
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.50383E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7545.67122
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 14.10443
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10912
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.23133
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.49163E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.66089E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.47935
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 189849.56718
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.66089E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5005.23300
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 17.07013
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13991
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.12104
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37309
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.72321E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.53423E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.88613
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 289677.86801
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.53423E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7637.21666
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 15.16446
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10149
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.54934
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.75404E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.62762E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.34945
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 186046.86375
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.62762E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4905.01990
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.28665
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18561
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.38599
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.49497
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.05264E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.29723E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.28665
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 37689.39131
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.29723E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 993.52682
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.41393
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10885
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.42418
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.50025E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.17549E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.84894
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24867.16385
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.17549E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 655.51333
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.84129
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12971
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.55239
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34588
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.93741E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.33491E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.30137
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 38120.10621
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.33491E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1004.87616
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.61385
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.53650E-002
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.48416
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.99517E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.17040E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.84696
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24809.03901
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.17040E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 653.98018
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.57001
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.45800
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.55561
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 24.47120
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.29396
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.77638
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 12.58793
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.77638
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.92837
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.92837
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.34556
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 60.19859
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 36.56626
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 120.39719
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 49.56421
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 101.24908
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 101.24908
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.48953
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.16890
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.86207
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 12.33780
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 8.18410
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 11.30177
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 11.30177
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.72414
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.47407
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 6.47407
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 6.47407
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 6.47407
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 6.47407
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 6.47407
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 24.47120
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 24.47120
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 24.47120
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 24.47120
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 24.47142
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 24.47142
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.57001
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.57001
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.57001
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.57001
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.57001
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.57001
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.45800
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.45800
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 5.45800
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 5.45800
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 5.45800
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 5.45800
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.55561
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.55561
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.55561
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.55561
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.55561
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.55561
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.92837
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 101.24908
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 11.30177
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 6.47407
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 24.47142
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.57001
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 5.45800
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.55561
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.92837
289 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.18508
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.68120
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.08825E-003
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 184210.73752
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.83675E-003
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.92837
297 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 99832.44627
298 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.73378E-004
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1534.40011
300 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.92837
301 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.83675E-003
302 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.07638E-005
303 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.73378E-004
304 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 101.24908
305 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.43561
306 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.68115
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.07576E-003
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1730478.65595
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.36186E-002
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 101.24908
313 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 1054592.04677
314 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.22603E-003
315 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 15670.25308
316 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 101.24908
317 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.36186E-002
318 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.46835E-006
319 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 9.22603E-003
320 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 11.30177
321 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.11766
322 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
323 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.68114
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.07352E-003
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 189241.84000
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 8.05079E-003
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 11.30177
329 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 103926.01877
330 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.09190E-004
331 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1594.65176
332 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 11.30177
333 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 8.05079E-003
334 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 5.91483E-005
335 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 9.09190E-004
336 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 6.47407
337 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
338 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 25.79641
339 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
340 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.21885
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.24228E-003
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 105376.18502
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.48295E-003
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.47407
346 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 309103.32943
347 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.70417E-003
348 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 6611.29697
349 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 6.47407
350 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 4.48295E-003
351 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.06223E-004
352 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.70417E-003
353 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 24.47142
354 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
355 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 24.47142
356 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 465166.58148
357 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 261784.14821
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.13919E-002
359 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 24.47142
360 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 24.47142
361 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 24.47142
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 24.47142
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 465166.58148
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 465166.58148
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 24207.99248
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
367 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 24.47142
368 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 24.47142
369 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 465166.58148
370 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.13919E-002
371 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 24207.99248
372 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.90553E-004
373 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
374 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
375 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
376 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.57001
377 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
378 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.57001
379 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 10529.64782
380 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 5988.33615
381 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.57870E-004
382 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.57001
383 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.57001
384 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.57001
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.57001
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 10529.64782
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 10529.64782
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1118.30896
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
390 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.57001
391 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.57001
392 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 10529.64782
393 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.57870E-004
394 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 1118.30896
395 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.45800
396 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
397 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 5.45800
398 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 100857.56788
399 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 57346.93932
400 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.47000E-003
401 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 5.45800
402 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 5.45800
403 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 5.45800
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.45800
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 100857.56788
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 100857.56788
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 11183.08965
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
409 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 5.45800
410 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 5.45800
411 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 100857.56788
412 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.47000E-003
413 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 11183.08965
414 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.55561
415 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
416 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.55561
417 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 10265.81115
418 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 5837.54806
419 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.51409E-004
420 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.55561
421 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.55561
422 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.55561
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.55561
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 10265.81115
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 10265.81115
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1118.30896
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
428 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.55561
429 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.55561
430 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 10265.81115
431 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.51409E-004
432 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 1118.30896
433 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 9.39890E-002
434 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 19367.65858
435 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 9.39890E-002
436 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 11.27869
437 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 9.39890E-002
438 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 9.39890E-002
439 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 394519.18187
440 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
441 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.95694E-002
442 PlantLoop HEATSYS1 Plant Loop Volume [m3] 3.54833
443 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.95694E-002
444 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 8905.01604
445 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
446 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 3379968.34114
447 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 3379968.34000
448 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.95694E-002
449 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 9.39890E-002
450 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 11.27869
451 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 9.39890E-002
452 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 13408.88335
453 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 9.39890E-002
454 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.73467E-002
455 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1115664.70348
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1120956.40000
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 5.54720E-002
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 9.39890E-002
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.73467E-002
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1115664.70348
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1120956.40000
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 5.54720E-002
463 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.43712E-002
464 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.72454
465 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.43712E-002
466 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3665.36815
467 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.43712E-002
468 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
469 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 55634.27402
470 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
471 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
472 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21031.61623
473 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 591969.18212
474 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 579237.53000
475 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.43712E-002
476 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
477 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
478 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
479 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 5.95776
480 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
481 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.11094
482 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 13.31327
483 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.11094
484 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 33413.90480
485 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 49.02430
486 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1331643.42517
487 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 9.80486
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 166455.42815
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 49.02430
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1331643.42517
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 9.80486
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 166455.42815
493 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 5.76175E-002
494 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 5.76175E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 25765.14
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 497792.72
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 108495.51
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 18963.54
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 13016.72
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 20846.85
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 11755.19
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 271215.01
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 179906.44
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 274506.98
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 176303.19
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 35714.62
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 23564.17
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 36122.74
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 23509.09
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 66984.17
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 679761.59
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 69595.74
19 Coil:Heating:Water CAV_BAS HEATING COIL 233665.18


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 308458.20 189374.49 119083.72 0.61 61181.39 620.54
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2868045.49 1758557.19 1109488.30 0.61 561573.82 5695.79
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 318350.79 195588.76 122762.03 0.61 63457.87 643.62
4 Coil:Cooling:Water CAV_BAS COOLING COIL 176197.98 109542.43 66655.54 0.62 32123.51 325.81


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.147 0.979   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.147 0.979   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_EAST_0.4 N/A 2.058 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_EAST_0.4 N/A 2.058 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_EAST_0.4 N/A 2.058 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.147 0.979   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.147 0.979   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_WEST_0.4 N/A 2.058 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_WEST_0.4 N/A 2.058 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_WEST_0.4 N/A 2.058 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.072 0.924   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.072 0.924   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_EAST_0.4 N/A 2.058 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.072 0.924   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.072 0.924   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_WEST_0.4 N/A 2.058 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.485 1.215   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.485 1.215   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_EAST_0.4 N/A 2.058 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.485 1.215   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.485 1.215   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_WEST_0.4 N/A 2.058 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.147 0.979   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.147 0.979   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.147 0.979   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.147 0.979   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.072 0.924   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.072 0.924   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.072 0.924   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.072 0.924   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.485 1.215   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.485 1.215   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.485 1.215   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.485 1.215   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.419 0.394   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.2735157663 0.2049469965 Pass Pass 15.6346840116 71.1059399734 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 4.8838971254E-002 0.1315599782 Pass Pass 5.0075414263E-002 0.2171181934 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 6.1576407246E-003 4.4733498081E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 2.9125455290E-002 2.2500655220E-002 Pass Pass 0.5117472514 0.4950104399 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 4.6535007458E-002 9.5462690874E-002 Pass Pass 4.9485986230E-002 0.2154014305 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.1005643163 0.1925875195 Pass Pass 5.0947688795E-002 0.2194513436 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.1492119725 0.2319705725 Pass Pass 5.0774361966E-002 0.2184788125 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 9.6956029983E-002 0.2326829007 Pass Pass 4.9795610908E-002 0.2149279415 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 2.4725048441E-002 2.4965462429E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 4.7735291897E-002 7.0257213492E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.1259374367 0.1206953959 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 4.9874998841E-002 5.3998252048E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.3420562075 0.3550422560 Pass Pass 5.9485957611 16.9753277118 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.2345889194 0.3306408682 Pass Pass 8.5729839216 34.4670213226 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.2196254729 0.2417741011 Pass Pass 0.7840771080 1.1091685840 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.1977896593 0.2599585075 Pass Pass 5.4754361298 27.3850567234 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 1.3678268075E-002 2.1381896761E-002 Pass Pass 7.2489767127 76.5823880480 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 1.0701941294E-002 1.2456517783E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.1091216160 8.4485632501E-002 Pass Pass 0.5125480752 0.4805148290 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 3.5751914354E-006 4.4876915815E-006 Pass Pass 4.1383857214E-003 4.0260454370E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 2.3248388476E-003 5.0817095637E-003 Pass Pass 0.1266417630 0.5911756408 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 2.5303422289E-002 1.9830125643E-002 Pass Pass 4.4604567185E-003 4.3632711518E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 8.2374463879E-005 7.9493992305E-005 Pass Pass 4.5157799499E-005 1.0582862621E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 7021.03 305.28 0.00 21315.02 19633.47 48274.79



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB -27.60 0.00 -27.60 Wetbulb [C] 2.70 230.00
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 33.40 16.00 16.30 Wetbulb [C] 4.90 240.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 11.00 18      
May 24.00 14      
Jun 29.00 21      
Jul 6.00 9      
Aug 0.00 0      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.979 1.147 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.979 1.147 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.979 1.147 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.979 1.147 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.924 1.072 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.924 1.072 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.924 1.072 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.924 1.072 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.215 1.485 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.215 1.485 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.215 1.485 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.215 1.485 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.979 1.147 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 0.979 1.147 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.979 1.147 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.979 1.147 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.924 1.072 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.924 1.072 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.924 1.072 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.924 1.072 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.215 1.485 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.215 1.485 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.215 1.485 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.215 1.485 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.399 0.419 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.3622_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.3622_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.3622_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.3622_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.3622_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.3622_SHGC_EAST_0.4   19.32 0.00 0.00 19.32 19.32 2.058 0.401 0.402             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.3622_SHGC_EAST_0.4   19.32 0.00 0.00 19.32 19.32 2.058 0.401 0.402             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.3622_SHGC_EAST_0.4   19.32 0.00 0.00 19.32 19.32 2.058 0.401 0.402             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.3622_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.3622_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.3622_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.3622_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.3622_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.3622_SHGC_WEST_0.4   19.32 0.00 0.00 19.32 19.32 2.058 0.401 0.402             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.3622_SHGC_WEST_0.4   19.32 0.00 0.00 19.32 19.32 2.058 0.401 0.402             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.3622_SHGC_WEST_0.4   19.32 0.00 0.00 19.32 19.32 2.058 0.401 0.402             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.3622_SHGC_NORTH_0.4   86.92 0.00 0.00 86.92 869.21 2.058 0.401 0.402             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.3622_SHGC_EAST_0.4   57.95 0.00 0.00 57.95 579.48 2.058 0.401 0.402             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.3622_SHGC_SOUTH_0.4   86.92 0.00 0.00 86.92 869.21 2.058 0.401 0.402             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.3622_SHGC_WEST_0.4   57.95 0.00 0.00 57.95 579.48 2.058 0.401 0.402             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.3622_SHGC_NORTH_0.4   86.92 0.00 0.00 86.92 86.92 2.058 0.401 0.402             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.3622_SHGC_EAST_0.4   57.95 0.00 0.00 57.95 57.95 2.058 0.401 0.402             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.3622_SHGC_SOUTH_0.4   86.92 0.00 0.00 86.92 86.92 2.058 0.401 0.402             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.3622_SHGC_WEST_0.4   57.95 0.00 0.00 57.95 57.95 2.058 0.401 0.402             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 2.058 0.401 0.402                      
North Total or Average             1043.06 2.058 0.401 0.402                      
Non-North Total or Average             2433.80 2.058 0.401 0.402                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.3279 2779.43 25926.33 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 240.45
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 9.3279 2496.12 23283.67 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 215.94
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 9.3279 24961.20 232836.67 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 2159.39
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 9.3279 2496.12 23283.67 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 215.94
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 9.3279 313.41 2923.50 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.32 0.0000 Y 18.83
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.13 0.0000 Y 12.07
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 9.3279 313.42 2923.56 LightsWired LTG_SCH_OFFICE 50.72 168.00 33.98 0.0000 Y 18.65
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.18 0.0000 Y 12.09
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 9.3279 3134.13 29234.97 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.35 0.0000 Y 188.52
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 9.3279 2019.75 18840.12 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.14 0.0000 Y 120.74
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 9.3279 3134.20 29235.61 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.00 0.0000 Y 186.58
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 9.3279 2019.75 18840.12 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.20 0.0000 Y 120.94
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 9.3279 313.41 2923.50 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.35 0.0000 Y 18.85
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.14 0.0000 Y 12.07
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 9.3279 313.42 2923.56 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.00 0.0000 Y 18.66
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 9.3279 201.98 1884.01 LightsWired LTG_SCH_OFFICE 50.72 168.00 34.20 0.0000 Y 12.09
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 9.3279 783.68 7310.12 LightsWired LTG_SCH_OFFICE 50.72 168.00 49.41 0.0000 Y 67.80
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 16.0861 36.20 582.36 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 5.97
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 16.0861 362.03 5823.61 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 59.65
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 16.0861 36.20 582.36 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 5.97
Interior Lighting Total       9.3913 46320.38 435009.77               1158.96


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.56 1127.62
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.56 0.00
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.50 1127.59
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.50 0.00
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.56 1127.62
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.56 0.00
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.50 1127.59
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.50 0.00
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.56 1127.62
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.56 0.00
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2923.50 1127.59
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2923.50 0.00
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1884.01 726.66
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1884.01 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 9973.01 AstronomicalClock -   42.11 42.11 78.82
EXTERIOR_LIGHTS_B 44362.79 AstronomicalClock -   83.57 71.13 592.33
Exterior Lighting Total 54335.80           671.16



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2204226.66          
HEATSYS1 BOILER Boiler:HotWater 3379968.34 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1120956.40 6.28 1072902.17 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1120956.40 6.28 1072902.17 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 579237.53 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1331643.43          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1331643.43          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 184210.74 308458.20 189374.49 119083.72 0.61 - 61181.39 620.54
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 1730478.66 2868045.49 1758557.19 1109488.30 0.61 - 561573.82 5695.79
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 189241.84 318350.79 195588.76 122762.03 0.61 - 63457.87 643.62
CAV_BAS COOLING COIL Coil:Cooling:Water 105376.19 176197.98 109542.43 66655.54 0.62 - 32123.51 325.81
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   465166.58 261784.15 203382.43 0.56 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   10529.65 5988.34 4541.31 0.57 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   100857.57 57346.94 43510.63 0.57 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   10265.81 5837.55 4428.26 0.57 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 27176.71 25765.14 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 525448.40 497792.72 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 114474.95 108495.51 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 20010.40 18963.54 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 13735.44 13016.72 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 21997.98 20846.85 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 12407.03 11755.19 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 286203.60 271215.01 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 189849.57 179906.44 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 289677.87 274506.98 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 186046.86 176303.19 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 37689.39 35714.62 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 24867.16 23564.17 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 38120.11 36122.74 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 24809.04 23509.09 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 99832.45 66984.17 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 1054592.05 679761.59 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 103926.02 69595.74 -
CAV_BAS HEATING COIL Coil:Heating:Water 309103.33 233665.18 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   465166.58 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   10529.65 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   100857.57 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   10265.81 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   24207.99 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   1118.31 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   11183.09 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   1118.31 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 10.93 24824.81 2271.59 1.00 1.12 General GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 101.25 229996.72 2271.59 1.00 1.08 General GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 11.30 25673.03 2271.59 1.00 1.11 General GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 6.47 10977.79 1695.65 1.00 1.15 General GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 24.47 40359.42 1649.25 1.00 1.14 General GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.57 638.47 1120.11 1.00 1.55 General GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 5.46 6113.55 1120.11 1.00 1.15 General GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.56 622.35 1120.11 1.00 1.56 General GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.093989 19367.66 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.029569 8905.02 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.093989 13408.88 142664.32 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.014371 3665.37 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 3168.45 0.000440 5.96 13540.37 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.110944 33413.90 301178.23 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.50 0.08



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 78387.81 78387.81 28.20 6.474 6.474 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00744 21.56 0.00629 1.200 0.00
CORE_BOTTOM 82273.91 82273.91 32.96 6.794 6.794 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00738 21.56 0.00629 1.078 0.00
CORE_MID 773613.85 773613.85 309.93 63.873 63.873 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00740 21.56 0.00629 10.778 0.00
CORE_TOP 74880.98 74880.98 30.00 6.182 6.182 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00742 21.56 0.00629 1.078 0.00
PERIMETER_BOT_ZN_3 12992.99 12992.99 41.46 1.082 1.082 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00727 33.40 0.00631 0.135 0.00
PERIMETER_BOT_ZN_2 16100.42 16100.42 79.71 1.341 1.341 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 24.00 24.00 0.00714 24.09 0.00629 0.087 0.00
PERIMETER_BOT_ZN_1 20376.61 20376.61 65.01 1.697 1.697 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 24.00 0.00717 33.13 0.00631 0.135 0.00
PERIMETER_BOT_ZN_4 20079.35 20079.35 99.41 1.673 1.673 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 24.00 0.00711 30.36 0.00630 0.087 0.00
PERIMETER_MID_ZN_3 122275.11 122275.11 390.14 10.186 10.186 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00725 33.40 0.00631 1.353 0.00
PERIMETER_MID_ZN_2 169321.00 169321.00 838.33 14.104 14.104 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00712 25.96 0.00630 0.872 0.00
PERIMETER_MID_ZN_1 204922.67 204922.67 653.83 17.070 17.070 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 24.00 0.00715 33.27 0.00631 1.353 0.00
PERIMETER_MID_ZN_4 182046.26 182046.26 901.33 15.164 15.164 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 24.00 0.00711 30.36 0.00630 0.872 0.00
PERIMETER_TOP_ZN_3 13915.48 13915.48 44.40 1.159 1.159 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00721 33.08 0.00631 0.135 0.00
PERIMETER_TOP_ZN_2 16974.01 16974.01 84.04 1.414 1.414 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 24.00 24.00 0.00711 26.41 0.00630 0.087 0.00
PERIMETER_TOP_ZN_1 22104.30 22104.30 70.53 1.841 1.841 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00714 33.40 0.00631 0.135 0.00
PERIMETER_TOP_ZN_4 19374.06 19374.06 95.92 1.614 1.614 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 24.00 0.00710 30.36 0.00630 0.087 0.00
DATACENTER_BOT_ZN_6 8675.44 8675.44 239.63 0.570 0.570 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 27.00 27.00 0.00708 26.28 0.00630 0.016 0.00
DATACENTER_MID_ZN_6 83069.49 83069.49 2294.56 5.458 5.458 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 27.00 27.00 0.00709 26.28 0.00630 0.156 0.00
DATACENTER_TOP_ZN_6 8456.34 8456.34 233.58 0.556 0.556 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 27.00 27.00 0.00709 26.57 0.00630 0.016 0.00
DATACENTER_BASEMENT_ZN_6 372452.66 372452.66 475.26 24.471 24.471 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00704 18.84 0.00628 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 22.70 0.00034 -27.60 0.00034 1.200 0.00
CORE_BOTTOM 9227.35 9227.35 3.70 0.446 1.078 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -27.60 0.00034 1.078 0.00
CORE_MID 352773.19 352773.19 141.33 17.082 17.082 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -27.60 0.00034 10.778 0.00
CORE_TOP 80130.06 80130.06 32.10 3.900 3.900 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -27.60 0.00034 1.078 0.00
PERIMETER_BOT_ZN_3 14004.02 14004.02 44.68 0.682 0.682 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00777 -27.60 0.00034 0.135 0.00
PERIMETER_BOT_ZN_2 9611.96 9611.96 47.59 0.468 0.468 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00778 -27.60 0.00034 0.087 0.00
PERIMETER_BOT_ZN_1 15393.55 15393.55 49.11 0.750 0.750 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00780 -27.60 0.00034 0.135 0.00
PERIMETER_BOT_ZN_4 7991.39 7991.39 39.57 0.389 0.389 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00770 -27.60 0.00034 0.087 0.00
PERIMETER_MID_ZN_3 200265.88 200265.88 638.98 9.767 9.767 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00766 -27.60 0.00034 1.353 0.00
PERIMETER_MID_ZN_2 132841.97 132841.97 657.71 6.479 6.479 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00766 -27.60 0.00034 0.872 0.00
PERIMETER_MID_ZN_1 202694.95 202694.95 646.72 9.886 9.886 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00766 -27.60 0.00034 1.353 0.00
PERIMETER_MID_ZN_4 130183.00 130183.00 644.55 6.349 6.349 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00765 -27.60 0.00034 0.872 0.00
PERIMETER_TOP_ZN_3 26368.99 26368.99 84.13 1.287 1.287 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00768 -27.60 0.00034 0.135 0.00
PERIMETER_TOP_ZN_2 17397.95 17397.95 86.14 0.849 0.849 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00767 -27.60 0.00034 0.087 0.00
PERIMETER_TOP_ZN_1 26670.14 26670.14 85.09 1.301 1.301 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00768 -27.60 0.00034 0.135 0.00
PERIMETER_TOP_ZN_4 17357.28 17357.28 85.94 0.847 0.847 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00767 -27.60 0.00034 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 24.21 0.00098 -27.60 0.00034 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.23 0.00098 -27.60 0.00034 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 19.68 0.00098 -27.60 0.00034 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:50:00 18.00 27.00 0.00700 -27.60 0.00034 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 10.93 10.93 3.37 3.37 10.9284 3.7764 10.9284 0.3456 0.3000
VAV_MID WITH REHEAT 101.25 101.25 49.56 49.56 101.2491 49.5642 101.2491 0.4895 0.3000
VAV_TOP WITH REHEAT 11.30 11.30 8.18 8.18 11.3018 8.1841 11.3018 0.7241 0.3000
CAV_BAS 6.47 6.47 1.20 1.20 6.4741 6.4741 6.4741 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 24.47 24.47 0.34 0.34 24.4714 24.4712 24.4714 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.57 0.57 0.02 0.02 0.5700 0.5700 0.5700 1.0000 1.0000
AIRLOOP DATACENTER MID 5.46 5.46 0.16 0.16 5.4580 5.4580 5.4580 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.56 0.56 0.02 0.02 0.5556 0.5556 0.5556 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 27176.709 27176.709 2.038317 0.00023775 577.099 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 27176.71 27176.71 2.038317 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00799999 45.2309 9227.35 0.00 27272.54 27272.54
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 525448.405 525448.405 19.608877 0.00459685 13336.118 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 525448.40 525448.40 19.608877 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00800000 45.2310 352773.19 0.00 527073.53 527073.53
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 114474.947 114474.947 3.900181 0.00100148 3020.418 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 114474.95 114474.95 3.900181 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00800000 45.2310 80130.06 0.00 114860.69 114860.69
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 20010.399 20010.399 0.682446 0.00017506 527.730 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 20010.40 20010.40 0.682446 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00777257 43.9637 14004.02 0.00 20076.07 20076.07
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 13735.438 13735.438 0.468499 0.00012016 362.221 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13735.44 13735.44 0.468499 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00778445 44.0300 9611.96 0.00 13780.37 13780.37
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 21997.976 21997.976 0.750352 0.00019245 580.106 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21997.98 21997.98 0.750352 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00780023 44.1180 15393.55 0.00 22069.87 22069.87
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 12407.026 12407.026 0.501787 0.00010854 305.531 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12407.03 12407.03 0.501787 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00770102 43.5646 7991.39 0.00 12446.04 12446.04
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 286203.600 286203.600 9.767409 0.00250383 7545.671 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 286203.60 286203.60 9.767409 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00765732 43.3222 200265.88 0.00 287126.21 287126.21
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 189849.567 189849.567 6.479353 0.00166089 5005.233 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 189849.57 189849.57 6.479353 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00765595 43.3146 132841.97 0.00 190460.89 190460.89
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 289677.868 289677.868 9.886126 0.00253423 7637.217 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 289677.87 289677.87 9.886126 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00766138 43.3448 202694.95 0.00 290611.30 290611.30
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 186046.864 186046.864 6.349451 0.00162762 4905.020 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 186046.86 186046.86 6.349451 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00764910 43.2764 130183.00 0.00 186646.25 186646.25
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 37689.391 37689.391 1.286648 0.00032972 993.527 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 37689.39 37583.07 1.286648 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00767644 43.4299 26368.99 0.00 37809.86 37809.86
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 24867.164 24867.164 0.848943 0.00021755 655.513 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24867.16 24867.16 0.848943 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00767313 43.4115 17397.95 0.00 24946.59 24946.59
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 38120.106 38120.106 1.301366 0.00033349 1004.876 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 38120.11 38120.11 1.301366 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00767993 43.4494 26670.14 0.00 38241.92 38241.92
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 24809.039 24809.039 0.846961 0.00021704 653.980 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24809.04 24809.04 0.846961 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00767261 43.4087 17357.28 0.00 24888.27 24888.27
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 184210.738 -999.000 10.928369 0.00783675 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 184210.74 182137.24 10.928369 26.19 14.59 0.00708825 10.68 8.51 0.00700000 33.40 0.00630683 16.37 22.8235 24.00 0.00732504 34.5527 128751.81 0.00 207680.83 204565.70
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 99832.446 99832.446 3.278511 0.00087338 1534.400 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 99832.45 99832.45 3.278511 -15.97 -15.97 0.00213112 12.80 10.41 0.00800000 -27.60 0.00034190 -27.60 76.0784 19.41 0.00772660 48.2177 33826.76 0.00 81014.05 81014.05
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1730478.656 -999.000 101.249077 0.07361856 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 1730478.66 1713938.70 101.249077 26.44 14.66 0.00707576 10.68 8.51 0.00700000 33.40 0.00630683 16.37 25.0688 24.00 0.00734480 34.6448 1175525.39 0.00 1948421.16 1922548.22
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 1054592.047 1054592.047 30.374723 0.00922603 15670.253 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1054592.05 1054592.05 30.374723 -20.01 -20.01 0.00153009 12.80 10.41 0.00800000 -27.60 0.00034190 -27.60 83.5627 17.82 0.00755555 52.0890 368953.52 0.00 821867.45 821867.45
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 189241.840 -999.000 11.301772 0.00805079 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 189241.84 187457.73 11.301772 26.12 14.55 0.00707352 10.68 8.51 0.00700000 33.40 0.00630683 16.37 22.4583 24.00 0.00729659 34.4200 135194.17 0.00 213483.34 210721.82
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 103926.019 103926.019 3.390532 0.00090919 1594.652 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 02:30:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 103926.02 103926.02 3.390532 -16.16 -16.16 0.00213940 12.80 10.41 0.00800000 -27.60 0.00034190 -27.60 74.8611 15.76 0.00758378 59.5988 38318.26 0.00 84172.05 84172.05
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 105376.185 -999.000 6.474075 0.00448295 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 105376.19 102120.20 6.474075 25.80 14.58 0.00724228 11.22 8.74 0.00700000 32.60 0.00630558 16.10 18.5379 24.00 0.00748979 35.3211 68928.11 0.00 118909.91 116571.47
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 309103.329 309103.329 6.474075 0.00270417 6611.297 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 309103.33 309103.33 6.474075 -5.12 -9.52 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 18.5379 22.82 0.00034190 1.7515 0.00 0.00 246465.63 246465.63
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 465166.581 261784.148 24.471423 0.01139190 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 404200.60 402729.32 -999.0 28.68 15.39 0.00703190 12.80 9.41 0.00700000 33.40 0.00630683 16.37 -999.0000 27.00 0.00704208 27.8119 371971.55 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10529.648 5988.336 0.570008 0.00025787 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 9101.03 9035.60 -999.0 28.07 15.21 0.00706149 12.80 9.41 0.00700000 26.57 0.00629632 14.04 -999.0000 27.00 0.00708308 27.9700 8675.44 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 100857.568 57346.939 5.457997 0.00247000 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 87178.65 86525.39 -999.0 28.07 15.21 0.00706411 12.80 9.41 0.00700000 26.57 0.00629632 14.04 -999.0000 27.00 0.00708676 27.9845 83069.49 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 10265.811 5837.548 0.555614 0.00025141 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 8873.30 8807.87 -999.0 28.07 15.21 0.00706308 12.80 9.41 0.00700000 26.57 0.00629632 14.04 -999.0000 27.00 0.00708527 27.9786 8456.34 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 465166.581 465166.581 24.471423 0.01139190 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 465166.58 465166.58 24.471423 -27.60 -27.60 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 1.3828 27.00 0.00700000 27.6430 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10529.648 10529.648 0.570008 0.00025787 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10529.65 10529.65 0.570008 -27.60 -27.60 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.7425 25.05 0.00098406 4.4026 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 100857.568 100857.568 5.457997 0.00247000 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 100857.57 100857.57 5.457997 -27.60 -27.60 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.8641 23.48 0.00098407 4.8367 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 10265.811 10265.811 0.555614 0.00025141 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10265.81 10265.81 0.555614 -27.60 -27.60 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.8135 21.93 0.00098348 5.3126 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 24207.992 24207.992 -999.0 -999.0 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 24207.99 24207.99 24.471423 -0.38 -0.38 0.00690793 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 1.3828 27.00 0.00700000 27.6430 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 1118.309 1118.309 -999.0 -999.0 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1118.31 1118.31 0.570008 -0.76 -5.60 0.00096645 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.7425 25.05 0.00098406 4.4026 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 11183.090 11183.090 -999.0 -999.0 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 11183.09 11183.09 5.457997 -0.79 -5.62 0.00096568 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.8641 23.48 0.00098407 4.8367 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 1118.309 1118.309 -999.0 -999.0 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1118.31 1118.31 0.555614 -0.78 -5.61 0.00096542 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.8135 21.93 0.00098348 5.3126 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 27176.709 27176.709 2.038317 0.00023775 577.099 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 0.7882 0.804052 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 27176.71 27176.71 1.0000 2.14663287 2.038317 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.23772946 60.00 32.22 27.78 0.000 27176.71 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.76 0.00799999 21.00 0.00799999 45.2309 9227.35 0.00 27272.54 27272.54 2.14663287 12.80 11.60 0.00800000 33059.8 25.26 16.41 0.00800000 45764.6
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 525448.405 525448.405 19.608877 0.00459685 13336.118 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 15.2393 15.545956 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 525448.40 525448.40 1.0000 20.65089050 19.608877 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 4.59638294 60.00 32.22 27.78 0.000 525448.40 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.86 0.00800000 21.00 0.00800000 45.2310 352773.19 0.00 527073.53 527073.53 20.65089050 12.80 11.60 0.00800000 33059.8 37.83 20.53 0.00800000 58582.9
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 114474.947 114474.947 3.900181 0.00100148 3020.418 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 3.3200 3.386864 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 114474.95 114474.95 1.0000 4.10743635 3.900181 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 1.00137462 60.00 32.22 27.78 0.000 114474.95 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00800000 21.00 0.00800000 45.2310 80130.06 0.00 114860.69 114860.69 4.10743635 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61023.9
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 20010.399 20010.399 0.682446 0.00017506 527.730 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 0.5803 0.592029 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 20010.40 20010.40 1.0000 0.71871098 0.682446 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.17504184 60.00 32.22 27.78 0.000 20010.40 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00777257 21.00 0.00777257 43.9637 14004.02 0.00 20076.07 20076.07 0.71871098 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60993.3
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 13735.438 13735.438 0.468499 0.00012016 362.221 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 0.3984 0.406378 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13735.44 13735.44 1.0000 0.49339496 0.468499 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.12015135 60.00 32.22 27.78 0.000 13735.44 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00778445 21.00 0.00778445 44.0300 9611.96 0.00 13780.37 13780.37 0.49339496 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60989.5
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 21997.976 21997.976 0.750352 0.00019245 580.106 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 0.6380 0.650834 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 21997.98 21997.98 1.0000 0.79022525 0.750352 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.19242826 60.00 32.22 27.78 0.000 21997.98 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00780023 21.00 0.00780023 44.1180 15393.55 0.00 22069.87 22069.87 0.79022525 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60988.4
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 12407.026 12407.026 0.501787 0.00010854 305.531 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 0.3598 0.367075 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12407.03 12407.03 1.0000 0.52845211 0.501787 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.10853101 60.00 32.22 27.78 0.000 12407.03 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00770102 21.00 0.00770102 43.5646 7991.39 0.00 12446.04 12446.04 0.52845211 12.80 11.60 0.00800000 33059.8 35.90 19.94 0.00800000 56611.7
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 286203.600 286203.600 9.767409 0.00250383 7545.671 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 8.3006 8.467641 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 286203.60 286203.60 1.0000 10.28644820 9.767409 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 2.50357853 60.00 32.22 27.78 0.000 286203.60 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00765732 21.00 0.00765732 43.3222 200265.88 0.00 287126.21 287126.21 10.28644820 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60972.9
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 189849.567 189849.567 6.479353 0.00166089 5005.233 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 5.5061 5.616904 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 189849.57 189849.57 1.0000 6.82366491 6.479353 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 1.66071741 60.00 32.22 27.78 0.000 189849.57 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00765595 21.00 0.00765595 43.3146 132841.97 0.00 190460.89 190460.89 6.82366491 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.6
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 289677.868 289677.868 9.886126 0.00253423 7637.217 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 8.4014 8.570431 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 289677.87 289677.87 1.0000 10.41147385 9.886126 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 2.53396984 60.00 32.22 27.78 0.000 289677.87 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00766138 21.00 0.00766138 43.3448 202694.95 0.00 290611.30 290611.30 10.41147385 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60972.4
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 186046.864 186046.864 6.349451 0.00162762 4905.020 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 5.3958 5.504397 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 186046.86 186046.86 1.0000 6.68686049 6.349451 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 1.62745309 60.00 32.22 27.78 0.000 186046.86 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00764910 21.00 0.00764910 43.2764 130183.00 0.00 186646.25 186646.25 6.68686049 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60972.2
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 37689.391 37689.391 1.286648 0.00032972 993.527 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 1.0931 1.115081 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 37689.39 37583.07 1.0000 1.35502071 1.286648 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.32968960 60.00 32.22 27.78 0.000 37689.39 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00767644 21.00 0.00767644 43.4299 26368.99 0.00 37809.86 37809.86 1.35502071 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60963.4
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 24867.164 24867.164 0.848943 0.00021755 655.513 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 0.7212 0.735722 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24867.16 24867.16 1.0000 0.89405546 0.848943 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.21752661 60.00 32.22 27.78 0.000 24867.16 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00767313 21.00 0.00767313 43.4115 17397.95 0.00 24946.59 24946.59 0.89405546 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60962.6
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 38120.106 38120.106 1.301366 0.00033349 1004.876 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 1.1056 1.127824 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 38120.11 38120.11 1.0000 1.37051994 1.301366 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.33345730 60.00 32.22 27.78 0.000 38120.11 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00767993 21.00 0.00767993 43.4494 26670.14 0.00 38241.92 38241.92 1.37051994 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60963.0
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 24809.039 24809.039 0.846961 0.00021704 653.980 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 0.7195 0.734002 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24809.04 24809.04 1.0000 0.89196849 0.846961 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.21701816 60.00 32.22 27.78 0.000 24809.04 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00767261 21.00 0.00767261 43.4087 17357.28 0.00 24888.27 24888.27 0.89196849 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60962.5
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 184210.738 -999.000 10.928369 0.00783675 -999.000 -999.0000 1.00000 1.00000 1018.0167 1004.8586 1.0531 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.928369 11.50910120   4197.9300 999.8980 93.97945699 12.27 6.67 5.60 2209307.42 8.3379 8.337940 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 184210.74 182137.24 1.0000 11.50910120 10.928369 26.19 14.59 0.00708825 44384.1 10.68 8.51 0.00700000 28378.5 7.83595118 6.67 12.27 5.60 24824.809 159385.93 33.40 0.00630683 16.37 2.49424000 22.8235 24.00 0.00732504 24.00 0.00732504 34.5527 128751.81 0.00 207680.83 204565.70 11.50910120 26.19 15.94 0.00708825 44384.1 8.73 8.71 0.00698072 26339.2
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 99832.446 99832.446 3.278511 0.00087338 1534.400 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.928369 11.50910120   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 2.8954 2.953650 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 99832.45 99832.45 1.0000 3.45273036 3.278511 -15.97 -15.97 0.00213112 -10785.0 12.80 10.41 0.00800000 33059.8 0.87328870 60.00 32.22 27.78 0.000 99832.45 -27.60 0.00034190 -27.60 2.49424000 76.0784 21.00 0.00782146 19.41 0.00772660 48.2177 33826.76 0.00 81014.05 81014.05 3.45273036 2.80 -0.98 0.00213112 8154.5 26.06 11.12 0.00213112 31618.2
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1730478.656 -999.000 101.249077 0.07361856 -999.000 -999.0000 1.00000 1.00000 1017.9935 1004.8586 1.0531 VAV_MID WITH REHEAT FAN Fan:VariableVolume 101.249077 106.62944070   4197.9300 999.8980 93.97945699 12.27 6.67 5.60 2209307.42 78.3267 78.326748 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 1730478.66 1713938.70 1.0000 106.62944070 101.249077 26.44 14.66 0.00707576 44607.3 10.68 8.51 0.00700000 28378.4 73.61105252 6.67 12.27 5.60 229996.718 1500481.94 33.40 0.00630683 16.37 25.38195000 25.0688 24.00 0.00734480 24.00 0.00734480 34.6448 1175525.39 0.00 1948421.16 1922548.22 106.62944070 26.44 16.02 0.00707576 44607.3 8.72 8.71 0.00697936 26334.5
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 1054592.047 1054592.047 30.374723 0.00922603 15670.253 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 VAV_MID WITH REHEAT FAN Fan:VariableVolume 101.249077 106.62944070   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 30.5857 31.201240 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1054592.05 1054592.05 1.0000 31.98883221 30.374723 -20.01 -20.01 0.00153009 -16335.2 12.80 10.41 0.00800000 33059.8 9.22509013 60.00 32.22 27.78 0.000 1054592.05 -27.60 0.00034190 -27.60 25.38195000 83.5627 18.59 0.00757052 17.82 0.00755555 52.0890 368953.52 0.00 821867.45 821867.45 31.98883221 2.80 -1.93 0.00153009 6648.2 28.30 11.43 0.00153009 32340.5
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 189241.840 -999.000 11.301772 0.00805079 -999.000 -999.0000 1.00000 1.00000 1017.9893 1004.8586 1.0531 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 11.301772 11.90234670   4197.9300 999.8980 93.97945699 12.27 6.67 5.60 2209307.42 8.5657 8.565664 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 Sensible 189241.84 187457.73 1.0000 11.90234670 11.301772 26.12 14.55 0.00707352 44278.0 10.68 8.51 0.00700000 28378.4 8.04996408 6.67 12.27 5.60 25673.029 163568.81 33.40 0.00630683 16.37 2.53819000 22.4583 24.00 0.00729659 24.00 0.00729659 34.4200 135194.17 0.00 213483.34 210721.82 11.90234670 26.12 15.91 0.00707352 44278.0 8.73 8.71 0.00698135 26341.7
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 103926.019 103926.019 3.390532 0.00090919 1594.652 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 11.301772 11.90234670   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 3.0141 3.074763 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 02:30:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 103926.02 103926.02 1.0000 3.57070401 3.390532 -16.16 -16.16 0.00213940 -10956.5 12.80 10.41 0.00800000 33059.8 0.90909740 60.00 32.22 27.78 0.000 103926.02 -27.60 0.00034190 -27.60 2.53819000 74.8611 17.89 0.00749217 15.76 0.00758378 59.5988 38318.26 0.00 84172.05 84172.05 3.57070401 2.80 -0.97 0.00213940 8175.2 26.17 11.17 0.00213940 31748.2
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 105376.185 -999.000 6.474075 0.00448295 -999.000 -999.0000 1.00000 1.00000 1018.3030 1004.8586 1.0531 CAV_BAS FAN Fan:ConstantVolume 6.474075 6.81810613   4197.9300 999.8980 93.97945699 12.27 6.67 5.60 2209307.42 4.7696 4.769648 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 105376.19 102120.20 1.0000 6.81810613 6.474075 25.80 14.58 0.00724228 44381.1 11.22 8.74 0.00700000 28925.7 4.48248920 6.67 12.27 5.60 10977.793 94398.39 32.60 0.00630558 16.10 1.20015641 18.5379 24.00 0.00748979 24.00 0.00748979 35.3211 68928.11 0.00 118909.91 116571.47 6.81810613 25.80 15.94 0.00724228 44381.1 9.01 8.98 0.00710605 26940.7
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 309103.329 309103.329 6.474075 0.00270417 6611.297 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 CAV_BAS FAN Fan:ConstantVolume 6.474075 6.81810613   4197.9300 999.8980 29.56642113 54.44 82.22 27.78 3447991.55 8.9647 9.145155 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 309103.33 309103.33 1.0000 6.81810613 6.474075 -5.12 -9.52 0.00034190 -4289.4 40.00 19.63 0.00800000 60796.0 2.70389492 60.00 32.22 27.78 0.000 309103.33 -27.60 0.00034190 -27.60 1.20015641 18.5379 0.00 0.00034190 22.82 0.00034190 1.7515 0.00 0.00 246465.63 246465.63 6.81810613 12.80 2.46 0.00034190 13725.2 48.75 18.00 0.00034190 49873.8
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 465166.581 261784.148 24.471423 0.01139190 -999.000 -999.0000 -999.00000 -999.00000 1017.9119 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 404200.60 402729.32 0.8689 -999.0 -999.0 28.68 15.39 0.00703190 46779.3 12.80 9.41 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 404200.60 33.40 0.00630683 16.37 0.33839277 -999.0000 27.00 0.00704208 27.00 0.00704208 27.8119 371971.55 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 10529.648 5988.336 0.570008 0.00025787 -999.000 -999.0000 -999.00000 -999.00000 1017.9670 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 Sensible 9101.03 9035.60 0.8643 -999.0 -999.0 28.07 15.21 0.00706149 46233.3 12.80 9.41 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 9101.03 26.57 0.00629632 14.04 0.01563234 -999.0000 27.00 0.00708308 27.00 0.00708308 27.9700 8675.44 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 100857.568 57346.939 5.457997 0.00247000 -999.000 -999.0000 -999.00000 -999.00000 1017.9718 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 Sensible 87178.65 86525.39 0.8644 -999.0 -999.0 28.07 15.21 0.00706411 46239.3 12.80 9.41 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 87178.65 26.57 0.00629632 14.04 0.15632344 -999.0000 27.00 0.00708676 27.00 0.00708676 27.9845 83069.49 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 10265.811 5837.548 0.555614 0.00025141 -999.000 -999.0000 -999.00000 -999.00000 1017.9699 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 Sensible 8873.30 8807.87 0.8644 -999.0 -999.0 28.07 15.21 0.00706308 46237.0 12.80 9.41 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8873.30 26.57 0.00629632 14.04 0.01563234 -999.0000 27.00 0.00708527 27.00 0.00708527 27.9786 8456.34 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 465166.581 465166.581 24.471423 0.01139190 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 465166.58 465166.58 1.0000 25.77183149 24.471423 -27.60 -27.60 0.00034190 -26896.1 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 465166.58 -27.60 0.00034190 -27.60 0.33839277 1.3828 0.00 0.00700000 27.00 0.00700000 27.6430 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 10529.648 10529.648 0.570008 0.00025787 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 10529.65 10529.65 1.0000 0.60029789 0.570008 -27.60 -27.60 0.00034190 -26896.1 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10529.65 -27.60 0.00034190 -27.60 0.01563234 2.7425 0.00 0.00098406 25.05 0.00098406 4.4026 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 100857.568 100857.568 5.457997 0.00247000 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 100857.57 100857.57 1.0000 5.74803442 5.457997 -27.60 -27.60 0.00034190 -26896.1 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 100857.57 -27.60 0.00034190 -27.60 0.15632344 2.8641 0.00 0.00098407 23.48 0.00098407 4.8367 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 10265.811 10265.811 0.555614 0.00025141 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 10265.81 10265.81 1.0000 0.58513972 0.555614 -27.60 -27.60 0.00034190 -26896.1 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10265.81 -27.60 0.00034190 -27.60 0.01563234 2.8135 0.00 0.00098348 21.93 0.00098348 5.3126 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 24207.992 24207.992 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 24.471423 25.77183149   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 24207.99 24207.99 1.0000 25.77183149 24.471423 -0.38 -0.38 0.00690793 16887.9 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 24207.99 -27.60 0.00034190 -27.60 0.33839277 1.3828 0.00 0.00700000 27.00 0.00700000 27.6430 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1118.309 1118.309 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.570008 0.60029789   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1118.31 1118.31 1.0000 0.60029789 0.570008 -0.76 -5.60 0.00096645 1655.1 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1118.31 -27.60 0.00034190 -27.60 0.01563234 2.7425 0.00 0.00098406 25.05 0.00098406 4.4026 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 11183.090 11183.090 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 5.457997 5.74803442   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 11183.09 11183.09 1.0000 5.74803442 5.457997 -0.79 -5.62 0.00096568 1619.4 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 11183.09 -27.60 0.00034190 -27.60 0.15632344 2.8641 0.00 0.00098407 23.48 0.00098407 4.8367 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1118.309 1118.309 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.555614 0.58513972   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1118.31 1118.31 1.0000 0.58513972 0.555614 -0.78 -5.61 0.00096542 1632.8 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1118.31 -27.60 0.00034190 -27.60 0.01563234 2.8135 0.00 0.00098348 21.93 0.00098348 5.3126 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 10.93 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 101.25 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 11.30 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 1.20 6.47 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 1511.00 1617.83 36.67
CORE_BOTTOM 1387.17 1691.50 23.83
CORE_MID 996.67 3503.00 236.50
CORE_TOP 1861.00 4149.33 1134.83
PERIMETER_BOT_ZN_3 1628.33 3957.50 684.67
PERIMETER_BOT_ZN_2 1998.67 3961.33 814.67
PERIMETER_BOT_ZN_1 2152.33 3352.67 691.17
PERIMETER_BOT_ZN_4 2326.00 3063.00 443.33
PERIMETER_MID_ZN_3 2697.67 4527.17 2072.00
PERIMETER_MID_ZN_2 2469.00 3781.83 1658.00
PERIMETER_MID_ZN_1 2532.50 3805.50 1274.33
PERIMETER_MID_ZN_4 2655.83 4444.67 1691.33
PERIMETER_TOP_ZN_3 3355.33 4806.67 2786.67
PERIMETER_TOP_ZN_2 3449.67 4445.17 2437.50
PERIMETER_TOP_ZN_1 3017.83 4154.33 1916.17
PERIMETER_TOP_ZN_4 3192.67 4648.00 2302.17
DATACENTER_BOT_ZN_6 5811.50 418.33 417.67
DATACENTER_MID_ZN_6 5263.67 197.83 66.33
DATACENTER_TOP_ZN_6 4523.50 566.50 153.83
DATACENTER_BASEMENT_ZN_6 5943.00 5659.00 5659.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5942.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 59.67 0.00 2.83
CORE_BOTTOM 0.00 4.50 0.00 0.00
CORE_MID 0.17 0.17 0.00 0.00
CORE_TOP 15.83 0.00 3.17 0.00
PERIMETER_BOT_ZN_3 6.00 0.50 0.83 0.33
PERIMETER_BOT_ZN_2 5.83 14.33 0.00 14.33
PERIMETER_BOT_ZN_1 6.33 21.00 0.17 20.17
PERIMETER_BOT_ZN_4 2.67 49.83 0.00 19.50
PERIMETER_MID_ZN_3 116.83 0.00 38.67 0.00
PERIMETER_MID_ZN_2 66.17 15.33 9.00 15.33
PERIMETER_MID_ZN_1 47.33 20.17 6.00 19.00
PERIMETER_MID_ZN_4 52.33 17.67 7.83 8.00
PERIMETER_TOP_ZN_3 307.33 1.00 106.33 0.50
PERIMETER_TOP_ZN_2 191.67 17.33 38.00 16.67
PERIMETER_TOP_ZN_1 155.00 14.33 26.17 12.50
PERIMETER_TOP_ZN_4 147.17 18.33 29.17 8.00
DATACENTER_BOT_ZN_6 0.00 16.50 0.00 11.83
DATACENTER_MID_ZN_6 0.00 6.50 0.00 3.83
DATACENTER_TOP_ZN_6 0.00 6.83 0.00 3.00
DATACENTER_BASEMENT_ZN_6 0.00 521.33 0.00 403.17
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 348.83 684.50 115.33 480.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.32 149.60 6779.02 1.328 0.000 0.000 0.000
CORE_BOTTOM 55.97 134.35 6849.35 0.987 0.000 0.000 0.000
CORE_MID 55.97 134.35 6849.35 0.743 0.000 0.000 0.000
CORE_TOP 55.97 134.35 6849.35 0.687 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.03 16.87 860.00 0.933 0.059 0.000 0.000
PERIMETER_BOT_ZN_2 4.53 10.87 554.22 1.680 0.061 0.000 0.000
PERIMETER_BOT_ZN_1 7.03 16.87 860.02 1.598 0.059 0.000 0.000
PERIMETER_BOT_ZN_4 4.53 10.87 554.22 2.134 0.061 0.000 0.000
PERIMETER_MID_ZN_3 7.03 16.87 860.00 0.775 0.137 0.000 0.000
PERIMETER_MID_ZN_2 3.96 10.87 554.22 1.561 0.151 0.000 0.000
PERIMETER_MID_ZN_1 7.03 16.87 860.02 1.510 0.138 0.000 0.000
PERIMETER_MID_ZN_4 4.53 10.87 554.22 1.690 0.142 0.000 0.000
PERIMETER_TOP_ZN_3 7.03 16.87 860.00 0.895 0.170 0.000 0.000
PERIMETER_TOP_ZN_2 4.53 10.87 554.22 1.648 0.176 0.000 0.000
PERIMETER_TOP_ZN_1 7.03 16.87 860.02 1.508 0.171 0.000 0.000
PERIMETER_TOP_ZN_4 4.53 10.87 554.22 1.749 0.176 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.57 42.18 1911.37 0.481 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.32 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.97 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.97 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.97 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.03 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.53 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.03 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.53 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.03 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.96 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.03 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.53 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.03 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.53 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.03 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.53 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.57 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.32 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.97 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.97 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.97 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.03 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.03 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.03 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.96 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.03 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.03 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.03 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.57 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1032.96 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 55200612.88 0.00 55200612.88 0.00 55200612.88 37848132.68 3922.68 931.43 3905.88 404.42
CORE_BOTTOM 42332194.17 0.00 42332194.17 0.00 42332194.17 33990283.35 4899.68 46.22 3814.10 502.27
CORE_MID 0.31E+09 0.00 0.31E+09 0.00 0.31E+09 0.34E+09 6131.20 46.37 2582.43 371.60
CORE_TOP 28405504.34 0.00 28405504.34 0.00 28405504.34 33990283.35 6519.86 33.43 2206.71 428.44
PERIMETER_BOT_ZN_3 5122350.16 0.00 5122350.16 591585.02 5713935.18 4267819.30 4310.73 83.43 4365.84 502.27
PERIMETER_BOT_ZN_2 5989795.76 0.00 5989795.76 394389.74 6384185.50 2750345.05 3441.38 0.48 5318.14 502.27
PERIMETER_BOT_ZN_1 8716307.32 0.00 8716307.32 591585.02 9307892.34 4267912.63 3459.00 2.46 5298.53 502.27
PERIMETER_BOT_ZN_4 7601485.63 0.00 7601485.63 394389.74 7995875.37 2750345.05 3424.87 0.47 5334.66 502.27
PERIMETER_MID_ZN_3 40740653.62 0.00 40740653.62 1387434.57 42128088.19 42678193.03 4361.36 49.28 4349.35 371.60
PERIMETER_MID_ZN_2 56780835.66 0.00 56780835.66 924955.75 57705791.41 27503450.52 3829.57 5.07 4925.36 1280.60
PERIMETER_MID_ZN_1 78768417.74 0.00 78768417.74 1387434.57 80155852.31 42679126.28 3884.05 3.72 4872.23 371.60
PERIMETER_MID_ZN_4 57463662.19 0.00 57463662.19 924955.75 58388617.93 27503450.52 3817.48 3.19 4939.34 371.60
PERIMETER_TOP_ZN_3 4688596.35 0.00 4688596.35 1722650.34 6411246.70 4267819.30 4135.19 15.54 4609.27 428.44
PERIMETER_TOP_ZN_2 5537765.13 0.00 5537765.13 1148432.78 6686197.91 2750345.05 3954.61 4.29 4801.11 428.44
PERIMETER_TOP_ZN_1 7832471.97 0.00 7832471.97 1722650.34 9555122.32 4267912.63 4005.32 5.35 4749.33 428.44
PERIMETER_TOP_ZN_4 5904131.57 0.00 5904131.57 1148432.78 7052564.34 2750345.05 3926.43 4.86 4828.71 428.44
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5288266.81 0.00 5288266.81 0.00 5288266.81 10671554.30 4419.00 4341.00 0.00 0.00
Total Facility 0.56E+10 0.00 0.56E+10 53961922.12 0.57E+10 0.50E+10 6861.83 4404.34 5544.19 1969.42


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.4546 0.0000 2.4546 0.0000 2.4546 1.2002 1339.29 927.87 3675.84
CORE_BOTTOM 1.8428 0.0000 1.8428 0.0000 1.8428 1.0778 2455.68 42.28 3445.04
CORE_MID 13.8789 0.0000 13.8789 0.0000 13.8789 10.7782 3432.93 45.70 2464.37
CORE_TOP 1.2850 0.0000 1.2850 0.0000 1.2850 1.0778 3789.97 33.29 2119.74
PERIMETER_BOT_ZN_3 0.2190 0.0000 0.2190 0.0139 0.2329 0.1353 1907.42 77.67 3957.91
PERIMETER_BOT_ZN_2 0.2547 0.0000 0.2547 0.0092 0.2639 0.0872 1096.43 0.33 4846.24
PERIMETER_BOT_ZN_1 0.3754 0.0000 0.3754 0.0139 0.3893 0.1353 1108.24 1.35 4833.41
PERIMETER_BOT_ZN_4 0.3230 0.0000 0.3230 0.0092 0.3322 0.0872 1086.38 0.37 4856.25
PERIMETER_MID_ZN_3 1.8244 0.0000 1.8244 0.0325 1.8569 1.3533 1676.27 48.00 4218.72
PERIMETER_MID_ZN_2 2.3703 0.0000 2.3703 0.0230 2.3932 0.8721 1212.83 1.96 3819.21
PERIMETER_MID_ZN_1 3.5511 0.0000 3.5511 0.0325 3.5836 1.3533 1240.27 1.94 4700.79
PERIMETER_MID_ZN_4 2.5676 0.0000 2.5676 0.0217 2.5893 0.8721 1205.64 1.90 4735.47
PERIMETER_TOP_ZN_3 0.2111 0.0000 0.2111 0.0404 0.2515 0.1353 1418.26 15.18 4509.55
PERIMETER_TOP_ZN_2 0.2502 0.0000 0.2502 0.0269 0.2771 0.0872 1290.58 1.75 4650.67
PERIMETER_TOP_ZN_1 0.3548 0.0000 0.3548 0.0404 0.3951 0.1353 1317.34 3.38 4622.28
PERIMETER_TOP_ZN_4 0.2657 0.0000 0.2657 0.0269 0.2927 0.0872 1274.02 3.13 4665.86
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 0.2472 0.0000 0.2472 0.0000 0.2472 0.3384 1602.00 4341.00 0.00
Total Facility 251.1702 0.0000 251.1702 1.2778 252.4480 158.4706 4044.83 4376.29 4903.63


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 77373505.22 0.00 77373505.22 48026705.38 3516.08 9.09 5234.83 502.27
VAV_MID WITH REHEAT 0.60E+09 0.00 0.60E+09 0.48E+09 3999.20 5.85 4754.95 371.60
VAV_TOP WITH REHEAT 58082055.60 0.00 58082055.60 48026705.38 4090.89 2.94 4666.16 428.40
CAV_BAS 61223198.86 0.00 61223198.86 37848132.68 3887.93 5.82 4866.25 404.40
AIRLOOP DATACENTER BASEMENT 5865235.79 0.00 5865235.79 10671554.30 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER BOT 270949.60 0.00 270949.60 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 2709495.95 0.00 2709495.95 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 270949.60 0.00 270949.60 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.3439 0.0000 3.3439 1.5229 1144.83 4.82 4793.34
VAV_MID WITH REHEAT 27.0269 0.0000 27.0269 15.2292 1317.11 4.12 4621.78
VAV_TOP WITH REHEAT 2.6249 0.0000 2.6249 1.5229 1370.04 2.46 4570.50
CAV_BAS 2.7224 0.0000 2.7224 1.2002 1329.28 1.81 4611.92
AIRLOOP DATACENTER BASEMENT 0.2741 0.0000 0.2741 0.3384 1602.00 0.00 4341.00
AIRLOOP DATACENTER BOT 0.0127 0.0000 0.0127 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1266 0.0000 0.1266 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0127 0.0000 0.0127 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 0.00 4209.98 0.00 0.00 0.00 1164.85 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 0.00 3705.97 0.00 0.00 0.00 1478.25 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 0.00 3083.20 0.00 0.00 0.00 2159.31 0.00 0.00 0.00
CAV_BAS 0.00 919.33 4145.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 0.0000 4.7663 0.0000 0.0000 0.0000 1.8936 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 0.0000 39.5512 0.0000 0.0000 0.0000 19.4570 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 0.0000 4.2851 0.0000 0.0000 0.0000 1.9580 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.3316 3.9987 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.3754 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0173 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.1734 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0173 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1380
Defaulted Fields 1179
Fields with Defaults 3862
Autosized Fields 330
Autosizable Fields 409
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 29517.66 391545.11 29-JAN-11:30 2076655.13 07-AUG-15:40
Electricity:Building 18924.62 251811.03 01-JAN-09:50 1146857.44 01-DEC-16:40
Electricity:Zone:BASEMENT 664.85 14623.97 01-JAN-00:10 34452.17 02-JAN-08:10
Electricity:SpaceType:GENERAL 18924.62 251811.03 01-JAN-09:50 1146857.44 01-DEC-16:40
InteriorLights:Electricity 3711.21 17601.77 01-JAN-09:50 352853.36 02-JAN-08:10
InteriorLights:Electricity:Zone:BASEMENT 240.45 1166.43 01-JAN-00:10 20994.62 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 3711.21 17601.77 01-JAN-09:50 352853.36 02-JAN-08:10
LightsWired:InteriorLights:Electricity 3711.21 17601.77 01-JAN-09:50 352853.36 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 240.45 1166.43 01-JAN-00:10 20994.62 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 3711.21 17601.77 01-JAN-09:50 352853.36 02-JAN-08:10
Electricity:Zone:CORE_BOTTOM 537.23 7090.40 01-JAN-00:10 36983.24 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
Electricity:Zone:CORE_MID 5372.24 70903.72 01-JAN-00:10 369831.68 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2159.40 10475.32 01-JAN-00:10 188546.48 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 2159.40 10475.32 01-JAN-00:10 188546.48 02-JAN-08:10
Electricity:Zone:CORE_TOP 537.22 7090.37 01-JAN-00:10 36983.17 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 215.94 1047.53 01-JAN-00:10 18854.65 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 59.18 839.57 01-JAN-09:40 4643.71 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 18.83 80.80 01-JAN-09:40 2367.39 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 18.83 80.80 01-JAN-09:40 2367.39 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 38.07 541.05 01-JAN-08:50 2992.58 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 12.07 52.07 01-JAN-08:50 1525.64 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 12.07 52.07 01-JAN-08:50 1525.64 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 58.99 839.58 01-JAN-08:50 4643.79 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 18.65 80.80 01-JAN-08:50 2367.44 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 18.65 80.80 01-JAN-08:50 2367.44 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 38.09 541.05 01-JAN-09:40 2992.57 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 12.09 52.07 01-JAN-09:40 1525.64 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 12.09 52.07 01-JAN-09:40 1525.64 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 591.94 8395.70 01-JAN-09:50 46437.07 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 188.52 807.98 01-JAN-09:50 23673.89 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 188.52 807.98 01-JAN-09:50 23673.89 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 380.73 5410.51 01-JAN-08:50 29925.82 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 120.74 520.69 01-JAN-08:50 15256.36 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 120.74 520.69 01-JAN-08:50 15256.36 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 590.01 8395.84 01-JAN-08:50 46437.94 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 186.58 807.99 01-JAN-08:50 23674.41 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 186.58 807.99 01-JAN-08:50 23674.41 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 380.92 5410.48 01-JAN-09:50 29925.72 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 120.94 520.69 01-JAN-09:50 15256.36 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 120.94 520.69 01-JAN-09:50 15256.36 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 59.19 839.57 01-JAN-09:50 4643.71 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 18.85 80.80 01-JAN-09:50 2367.39 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 18.85 80.80 01-JAN-09:50 2367.39 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 38.07 541.05 01-JAN-08:50 2992.58 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 12.07 52.07 01-JAN-08:50 1525.64 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 12.07 52.07 01-JAN-08:50 1525.64 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 59.00 839.58 01-JAN-08:50 4643.79 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 18.66 80.80 01-JAN-08:50 2367.44 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 18.66 80.80 01-JAN-08:50 2367.44 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 38.09 541.05 01-JAN-09:50 2992.57 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 12.09 52.07 01-JAN-09:50 1525.64 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 12.09 52.07 01-JAN-09:50 1525.64 02-JAN-08:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7562.65 95237.01 01-JAN-00:10 385552.11 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 67.80 328.88 01-JAN-00:10 5919.59 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 67.80 328.88 01-JAN-00:10 5919.59 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 159.85 1977.54 01-JAN-00:10 8315.27 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1598.46 19775.43 01-JAN-00:10 83152.69 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 59.65 289.38 01-JAN-00:10 5208.47 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 59.65 289.38 01-JAN-00:10 5208.47 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 159.85 1977.54 01-JAN-00:10 8315.27 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 5.97 28.94 01-JAN-00:10 520.85 02-JAN-08:10
InteriorEquipment:Electricity 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 1722.83 5114.07 10-JAN-22:10 451081.94 07-SEP-15:00
HeatRejection:Electricity 812.86 1248.20 10-JAN-22:00 81829.93 06-JUN-14:40
General:HeatRejection:Electricity 812.86 1248.20 10-JAN-22:00 81829.93 06-JUN-14:40
Electricity:HVAC 6344.44 96746.72 09-JAN-24:00 529435.95 11-AUG-15:30
ExteriorEquipment:Electricity 1941.94 28795.69 01-JAN-00:10 118959.22 02-JAN-08:20
Transformer:ExteriorEquipment:Electricity 87.33 1613.62 01-JAN-00:10 5481.25 01-DEC-16:50
ElectricityPurchased:Facility 29517.66 391545.11 29-JAN-11:30 2076655.13 07-AUG-15:40
ElectricityPurchased:Plant 29517.66 391545.11 29-JAN-11:30 2076655.13 07-AUG-15:40
Cogeneration:ElectricityPurchased 29517.66 391545.11 29-JAN-11:30 2076655.13 07-AUG-15:40
General:Cogeneration:ElectricityPurchased 29517.66 391545.11 29-JAN-11:30 2076655.13 07-AUG-15:40
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 29517.66 391545.11 29-JAN-11:30 2076655.13 07-AUG-15:40
ElectricityNet:Plant 29517.66 391545.11 29-JAN-11:30 2076655.13 07-AUG-15:40
Cogeneration:ElectricityNet 29517.66 391545.11 29-JAN-11:30 2076655.13 07-AUG-15:40
General:Cogeneration:ElectricityNet 29517.66 391545.11 29-JAN-11:30 2076655.13 07-AUG-15:40
Fans:Electricity 2703.50 47733.78 26-JAN-22:10 324151.01 17-JUL-15:20
General:Fans:Electricity 2703.50 47733.78 26-JAN-22:10 324151.01 17-JUL-15:20
ExteriorLights:Electricity 671.16 0.00 01-JAN-08:20 54335.80 01-JAN-06:10
General:ExteriorLights:Electricity 671.16 0.00 01-JAN-08:20 54335.80 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
Cooling:Electricity 3205.79 30232.37 09-JAN-07:10 426109.78 07-AUG-15:40
General:Cooling:Electricity 3205.79 30232.37 09-JAN-07:10 426109.78 07-AUG-15:40
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 840.82 0.00 13-JUL-15:20 52016.10 28-DEC-19:00
General:Humidifier:Electricity 840.82 0.00 13-JUL-15:20 52016.10 28-DEC-19:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 416.96 3665.37 01-JAN-00:10 56384.85 05-SEP-12:30
General:Pumps:Electricity 416.96 3665.37 01-JAN-00:10 56384.85 05-SEP-12:30
WIRED_LTG_ELECTRICITY 104.28 0.00 01-JAN-00:10 9915.18 02-JAN-08:20
WIRED_INT_EQUIP 5871.99 115917.86 04-MAR-00:10 320838.49 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 4169.09 5695.87 05-JAN-22:20 2312600.18 09-JAN-07:20
NaturalGas:Plant 4169.09 5695.87 05-JAN-22:20 2312600.18 09-JAN-07:20
Heating:NaturalGas 3397.54 0.00 01-JAN-00:10 2290324.49 09-JAN-07:10
Boiler:Heating:NaturalGas 3397.54 0.00 01-JAN-00:10 2290324.49 09-JAN-07:10
WaterSystems:NaturalGas 771.55 5695.87 05-JAN-22:20 85520.85 22-FEB-12:20
Water Heater:WaterSystems:NaturalGas 771.55 5695.87 05-JAN-22:20 85520.85 22-FEB-12:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 16931.41 147152.11 09-JAN-07:10 2471253.92 07-SEP-15:00
PlantLoopCoolingDemand:HVAC 16931.41 147152.11 09-JAN-07:10 2471253.92 07-SEP-15:00
CoolingCoils:PlantLoopCoolingDemand 16931.41 147152.11 09-JAN-07:10 2471253.92 07-SEP-15:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 5781.45 0.00 31-AUG-23:20 0.00 25-JUL-11:50
Water:HVAC 312.78 0.00 13-JUL-15:20 0.00 28-DEC-19:00
Humidifier:Water 312.78 0.00 13-JUL-15:20 0.00 28-DEC-19:00
General:Humidifier:Water 312.78 0.00 13-JUL-15:20 0.00 28-DEC-19:00
MainsWater:Facility 5781.45 0.00 31-AUG-23:20 0.00 25-JUL-11:50
MainsWater:HVAC 312.78 0.00 13-JUL-15:20 0.00 28-DEC-19:00
Humidifier:MainsWater 312.78 0.00 13-JUL-15:20 0.00 28-DEC-19:00
General:Humidifier:MainsWater 312.78 0.00 13-JUL-15:20 0.00 28-DEC-19:00
Water:Plant 5468.66 0.00 01-JAN-00:10 0.00 25-JUL-11:50
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 5468.66 0.00 01-JAN-00:10 0.00 25-JUL-11:50
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 3188.49 0.00 01-JAN-00:10 0.00 17-JUL-16:00
General:HeatRejection:Water 3188.49 0.00 01-JAN-00:10 0.00 17-JUL-16:00
HeatRejection:MainsWater 3188.49 0.00 01-JAN-00:10 0.00 17-JUL-16:00
General:HeatRejection:MainsWater 3188.49 0.00 01-JAN-00:10 0.00 17-JUL-16:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 49396.79 231196.80 12-JAN-03:40 10652464.62 07-SEP-15:00
EnergyTransfer:Building 18690.04 87829.22 12-JAN-22:50 1727997.00 07-AUG-15:20
EnergyTransfer:Zone:BASEMENT 670.59 0.00 01-JAN-00:40 68683.10 07-AUG-05:10
Heating:EnergyTransfer 917.23 0.00 13-JAN-22:10 1231218.64 09-JAN-06:10
Heating:EnergyTransfer:Zone:BASEMENT 3.28 0.00 01-JAN-00:40 21884.35 05-AUG-16:10
General:Heating:EnergyTransfer 917.23 0.00 13-JAN-22:10 1231218.64 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 3.28 0.00 01-JAN-00:40 21884.35 05-AUG-16:10
Cooling:EnergyTransfer 17772.81 83739.68 30-JAN-06:00 1727997.00 07-AUG-15:20
Cooling:EnergyTransfer:Zone:BASEMENT 667.31 0.00 01-JAN-00:10 68683.10 07-AUG-05:10
General:Cooling:EnergyTransfer 17772.81 83739.68 30-JAN-06:00 1727997.00 07-AUG-15:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 667.31 0.00 01-JAN-00:10 68683.10 07-AUG-05:10
EnergyTransfer:Zone:CORE_BOTTOM 602.48 0.00 01-JAN-00:10 56893.70 07-AUG-10:40
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 602.48 0.00 01-JAN-00:10 56893.70 07-AUG-10:40
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 602.48 0.00 01-JAN-00:10 56893.70 07-AUG-10:40
EnergyTransfer:Zone:CORE_MID 4232.45 0.00 01-JAN-00:10 452872.44 05-SEP-14:00
Heating:EnergyTransfer:Zone:CORE_MID 7.07 0.00 01-JAN-00:10 327105.08 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_MID 7.07 0.00 01-JAN-00:10 327105.08 09-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_MID 4225.38 0.00 01-JAN-00:10 452872.44 05-SEP-14:00
General:Cooling:EnergyTransfer:Zone:CORE_MID 4225.38 0.00 01-JAN-00:10 452872.44 05-SEP-14:00
EnergyTransfer:Zone:CORE_TOP 375.39 0.00 01-JAN-00:10 70755.77 06-MAR-05:10
Heating:EnergyTransfer:Zone:CORE_TOP 19.86 0.00 01-JAN-00:10 70755.77 06-MAR-05:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 19.86 0.00 01-JAN-00:10 70755.77 06-MAR-05:10
Cooling:EnergyTransfer:Zone:CORE_TOP 355.53 0.00 01-JAN-00:10 53857.27 17-JUL-15:40
General:Cooling:EnergyTransfer:Zone:CORE_TOP 355.53 0.00 01-JAN-00:10 53857.27 17-JUL-15:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 66.94 0.00 01-JAN-00:10 12271.87 09-JAN-05:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.96 0.00 01-JAN-00:10 12271.87 09-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.96 0.00 01-JAN-00:10 12271.87 09-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 63.97 0.00 01-JAN-00:10 10242.13 09-AUG-14:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 63.97 0.00 01-JAN-00:10 10242.13 09-AUG-14:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 69.84 0.00 01-JAN-00:10 14178.34 07-AUG-08:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 2.20 0.00 01-JAN-00:10 9809.64 09-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 2.20 0.00 01-JAN-00:10 9809.64 09-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 67.64 0.00 01-JAN-00:10 14178.34 07-AUG-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 67.64 0.00 01-JAN-00:10 14178.34 07-AUG-08:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 112.67 0.00 01-JAN-00:10 20393.87 18-OCT-13:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 3.11 0.00 01-JAN-00:10 15492.87 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 3.11 0.00 01-JAN-00:10 15492.87 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 109.56 0.00 01-JAN-00:10 20393.87 18-OCT-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 109.56 0.00 01-JAN-00:10 20393.87 18-OCT-13:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 99.67 0.00 01-JAN-00:10 18205.43 07-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.65 0.00 01-JAN-00:10 7224.16 09-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.65 0.00 01-JAN-00:10 7224.16 09-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 99.02 0.00 01-JAN-00:10 18205.43 07-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 99.02 0.00 01-JAN-00:10 18205.43 07-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 592.07 0.00 01-JAN-00:10 134098.08 30-JAN-04:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 192.23 0.00 01-JAN-00:10 134098.08 30-JAN-04:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 192.23 0.00 01-JAN-00:10 134098.08 30-JAN-04:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 399.84 0.00 01-JAN-00:10 93956.75 18-JUL-15:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 399.84 0.00 01-JAN-00:10 93956.75 18-JUL-15:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 642.82 0.00 01-JAN-00:10 150089.92 30-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 114.31 0.00 01-JAN-00:10 150089.92 30-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 114.31 0.00 01-JAN-00:10 150089.92 30-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 528.51 0.00 01-JAN-00:10 146905.52 07-AUG-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 528.51 0.00 01-JAN-00:10 146905.52 07-AUG-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1021.56 0.00 01-JAN-00:10 210798.97 18-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 114.30 0.00 01-JAN-00:10 193215.25 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 114.30 0.00 01-JAN-00:10 193215.25 09-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 907.26 0.00 01-JAN-00:10 210798.97 18-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 907.26 0.00 01-JAN-00:10 210798.97 18-OCT-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 643.70 0.00 01-JAN-00:10 154609.04 17-JUL-17:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 92.07 0.00 01-JAN-00:10 142272.78 30-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 92.07 0.00 01-JAN-00:10 142272.78 30-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 551.64 0.00 01-JAN-00:10 154609.04 17-JUL-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 551.64 0.00 01-JAN-00:10 154609.04 17-JUL-17:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 84.72 0.00 01-JAN-00:10 17480.01 30-JAN-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 47.88 0.00 01-JAN-00:10 17480.01 30-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 47.88 0.00 01-JAN-00:10 17480.01 30-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 36.84 0.00 01-JAN-00:10 10672.55 17-JUL-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 36.84 0.00 01-JAN-00:10 10672.55 17-JUL-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 75.10 0.00 01-JAN-00:10 17014.93 30-JAN-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 27.67 0.00 01-JAN-00:10 17014.93 30-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 27.67 0.00 01-JAN-00:10 17014.93 30-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 47.43 0.00 01-JAN-00:10 14917.11 07-AUG-09:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 47.43 0.00 01-JAN-00:10 14917.11 07-AUG-09:20
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 112.61 0.00 01-JAN-00:10 22413.48 30-JAN-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 31.76 0.00 01-JAN-00:10 22413.48 30-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 31.76 0.00 01-JAN-00:10 22413.48 30-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 80.85 0.00 01-JAN-00:10 22189.94 01-SEP-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 80.85 0.00 01-JAN-00:10 22189.94 01-SEP-13:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 73.04 0.00 01-JAN-00:10 17963.58 30-JAN-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 23.12 0.00 01-JAN-00:10 17963.58 30-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 23.12 0.00 01-JAN-00:10 17963.58 30-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 49.92 0.00 01-JAN-00:10 16369.87 17-JUL-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 49.92 0.00 01-JAN-00:10 16369.87 17-JUL-17:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 58.72 0.00 01-JAN-00:10 10314.63 07-AUG-15:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 4.81 0.00 01-JAN-00:10 6604.73 30-JAN-13:40
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 4.81 0.00 01-JAN-00:10 6604.73 30-JAN-13:40
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 53.91 0.00 01-JAN-00:10 10314.63 07-AUG-15:20
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 53.91 0.00 01-JAN-00:10 10314.63 07-AUG-15:20
EnergyTransfer:Zone:MIDFLOOR_PLENUM 488.43 0.00 01-JAN-00:10 118583.78 09-JAN-06:10
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 150.19 0.00 01-JAN-00:10 118583.78 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 150.19 0.00 01-JAN-00:10 118583.78 09-JAN-06:10
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 338.25 0.00 01-JAN-00:10 81563.23 07-AUG-15:40
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 338.25 0.00 01-JAN-00:10 81563.23 07-AUG-15:40
EnergyTransfer:Zone:TOPFLOOR_PLENUM 120.67 0.00 01-JAN-00:10 33742.90 09-JAN-05:10
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 72.91 0.00 01-JAN-00:10 33742.90 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 72.91 0.00 01-JAN-00:10 33742.90 09-JAN-05:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 47.75 0.00 01-JAN-00:10 22981.96 17-JUL-15:00
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 47.75 0.00 01-JAN-00:10 22981.96 17-JUL-15:00
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 135.49 6.23 29-JAN-13:50 8260.85 03-AUG-18:50
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.07 0.00 01-JAN-00:10 639.67 09-JAN-03:50
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.07 0.00 01-JAN-00:10 639.67 09-JAN-03:50
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 135.43 0.00 07-JAN-23:50 8260.85 03-AUG-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 135.43 0.00 07-JAN-23:50 8260.85 03-AUG-18:50
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1154.23 1.46 11-JAN-09:40 78941.18 03-AUG-18:50
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 5.66 0.00 01-JAN-15:40 6600.97 29-JAN-17:50
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 5.66 0.00 01-JAN-15:40 6600.97 29-JAN-17:50
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1148.57 0.00 01-JAN-00:10 78941.18 03-AUG-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1148.57 0.00 01-JAN-00:10 78941.18 03-AUG-18:50
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 104.06 1.29 18-JAN-11:50 7964.13 03-AUG-18:40
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 1.13 0.00 02-JAN-13:10 769.93 30-APR-23:10
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 1.13 0.00 02-JAN-13:10 769.93 30-APR-23:10
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 102.94 0.00 01-JAN-00:10 7964.13 03-AUG-18:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 102.94 0.00 01-JAN-00:10 7964.13 03-AUG-18:40
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7152.79 83131.18 09-JAN-05:00 369517.19 22-AUG-07:20
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7152.79 83131.18 09-JAN-05:00 369517.19 22-AUG-07:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7152.79 83131.18 09-JAN-05:00 369517.19 22-AUG-07:20
PlantLoopHeatingDemand:Facility 3108.81 0.00 01-JAN-00:10 1964863.02 09-JAN-07:10
PlantLoopHeatingDemand:Plant 463.31 0.00 01-JAN-00:10 57404.05 17-FEB-12:50
WaterSystems:PlantLoopHeatingDemand 463.31 0.00 01-JAN-00:10 57404.05 17-FEB-12:50
General:WaterSystems:PlantLoopHeatingDemand 463.31 0.00 01-JAN-00:10 57404.05 17-FEB-12:50
EnergyTransfer:HVAC 16864.12 138091.57 09-JAN-24:00 2413942.03 07-SEP-15:00
HeatingCoils:EnergyTransfer 2645.50 0.00 01-JAN-00:10 1946247.42 09-JAN-07:10
PlantLoopHeatingDemand:HVAC 2645.50 0.00 01-JAN-00:10 1946247.42 09-JAN-07:10
HeatingCoils:PlantLoopHeatingDemand 2645.50 0.00 01-JAN-00:10 1946247.42 09-JAN-07:10
CoolingCoils:EnergyTransfer 14218.62 116919.74 09-JAN-07:10 2413942.03 07-SEP-15:00
EnergyTransfer:Plant 13842.63 0.00 01-JAN-00:10 7073192.29 07-SEP-15:00
LoopToLoop:EnergyTransfer 3610.52 -1630.93 25-FEB-14:00 2248126.37 07-SEP-15:00
WaterSystems:EnergyTransfer 463.31 0.00 01-JAN-00:10 57404.05 17-FEB-12:50
WaterUse:WaterSystems:EnergyTransfer 463.31 0.00 01-JAN-00:10 57404.05 17-FEB-12:50
Boilers:EnergyTransfer 2622.30 0.00 01-JAN-00:10 1905651.34 09-JAN-07:10
Chillers:EnergyTransfer 3326.75 0.00 01-JAN-00:10 2241912.80 07-SEP-15:00
HeatRejection:EnergyTransfer 3819.75 0.00 01-JAN-00:10 2557070.85 07-SEP-15:00
General:HeatRejection:EnergyTransfer 3819.75 0.00 01-JAN-00:10 2557070.85 07-SEP-15:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 3.280 -667.311 0.000 0.000 93.213 240.449 424.397 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -94.028
CORE_BOTTOM 0.000 0.000 0.000 -602.483 0.000 0.000 83.580 215.940 321.286 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -18.323
CORE_MID 0.000 0.000 7.071 -4225.364 0.000 0.000 850.980 2159.397 3212.845 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -2004.930
CORE_TOP 0.000 0.000 19.862 -355.524 0.000 0.000 88.526 215.940 321.285 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -290.088
PERIMETER_BOT_ZN_3 0.000 0.000 2.963 -63.972 0.000 0.000 11.049 18.834 40.342 22.612 0.000 0.090 40.637 0.000 -62.221 0.000 -10.335 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 2.204 -67.635 0.000 0.000 7.243 12.070 25.998 52.582 0.000 0.064 12.187 0.000 -37.950 0.000 -6.763 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 3.107 -109.564 0.000 0.000 11.021 18.648 40.343 113.839 0.000 0.087 0.000 0.000 -56.449 0.000 -10.362 -10.670
PERIMETER_BOT_ZN_4 0.000 0.000 0.646 -99.019 0.000 0.000 7.097 12.090 25.998 49.201 0.000 0.057 54.553 0.000 -43.256 0.000 -7.368 0.000
PERIMETER_MID_ZN_3 0.000 0.000 192.228 -399.840 0.000 0.000 115.753 188.522 403.423 237.170 0.000 2.141 46.456 0.000 -570.411 0.000 -215.441 -0.014
PERIMETER_MID_ZN_2 0.000 0.000 114.308 -528.513 0.000 0.000 54.926 120.744 259.981 529.304 0.000 1.424 0.001 0.000 -357.727 0.000 -145.618 -48.829
PERIMETER_MID_ZN_1 0.000 0.000 114.300 -907.254 0.000 0.000 112.614 186.584 403.429 1137.375 0.000 1.958 0.056 0.000 -545.831 0.000 -229.481 -273.694
PERIMETER_MID_ZN_4 0.000 0.000 92.066 -551.632 0.000 0.000 75.504 120.938 259.979 505.300 0.000 1.406 30.234 0.000 -384.724 0.000 -149.072 -0.021
PERIMETER_TOP_ZN_3 0.000 0.000 47.883 -36.838 0.000 0.000 11.832 18.852 40.342 24.476 0.000 0.269 0.001 0.000 -53.881 0.000 -25.116 -27.821
PERIMETER_TOP_ZN_2 0.000 0.000 27.669 -47.428 0.000 0.000 7.527 12.075 25.998 53.361 0.000 0.167 0.000 0.000 -34.059 0.000 -17.115 -28.195
PERIMETER_TOP_ZN_1 0.000 0.000 31.757 -80.854 0.000 0.000 11.482 18.659 40.343 114.561 0.000 0.236 0.001 0.000 -51.663 0.000 -26.708 -57.811
PERIMETER_TOP_ZN_4 0.000 0.000 23.123 -49.918 0.000 0.000 7.644 12.094 25.998 50.829 0.000 0.172 0.001 0.000 -36.733 0.000 -17.564 -15.645
DATACENTER_BOT_ZN_6 0.000 0.000 0.066 -135.425 0.000 0.000 0.950 5.965 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -25.436
DATACENTER_MID_ZN_6 0.000 0.000 5.664 -1148.566 0.000 0.000 9.519 59.652 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -465.074
DATACENTER_TOP_ZN_6 0.000 0.000 1.127 -102.935 0.000 0.000 0.957 5.965 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -58.995
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7152.792 0.000 0.000 20.234 67.796 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -430.095
GROUNDFLOOR_PLENUM 4.807 -53.914 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.161 70.933 0.000 0.000 0.000 -21.986 0.000
MIDFLOOR_PLENUM 150.190 -338.247 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.967 556.068 0.000 0.000 0.000 -370.978 -0.006
TOPFLOOR_PLENUM 72.915 -47.751 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.264 13.412 0.000 0.000 0.000 -38.840 -0.001
Total Facility 227.912 -439.912 689.324 -17332.866 0.000 0.000 1581.653 3711.212 15213.411 2890.610 0.000 11.462 824.544 0.000 -2234.906 0.000 -1292.747 -3849.677


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 25-SEP-03:02 0.00 0.00 0.00 -115332.94 0.00 0.00 0.00 1166.43 13457.54 0.00 0.00 0.00 100708.97 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 11-SEP-03:02 0.00 0.00 0.00 -95351.91 0.00 0.00 0.00 1047.53 8057.15 0.00 0.00 0.00 86247.23 0.00 -0.00 0.00 0.00 0.00
CORE_MID 14-AUG-03:02 0.00 0.00 0.00 -861736.68 0.00 0.00 0.00 10475.32 80571.20 0.00 0.00 0.00 770690.16 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 21-JUN-03:02 0.00 0.00 0.00 -83024.04 0.00 0.00 0.00 1047.53 8057.12 0.00 0.00 0.00 73919.39 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 04-SEP-16:01 0.00 0.00 0.00 -15721.96 0.00 0.00 44.68 80.80 758.77 2848.56 0.00 110.70 11878.45 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 04-SEP-08:42 0.00 0.00 0.00 -21612.78 0.00 0.00 21.83 52.07 488.98 13376.05 0.00 0.00 7702.15 0.00 -0.00 0.00 -28.30 0.00
PERIMETER_BOT_ZN_1 15-OCT-12:31 0.00 0.00 0.00 -28546.53 0.00 0.00 33.06 80.80 758.78 29220.34 0.00 0.00 0.00 0.00 -0.00 0.00 -418.95 -1127.51
PERIMETER_BOT_ZN_4 04-SEP-16:01 0.00 0.00 0.00 -28775.45 0.00 0.00 18.07 52.07 488.98 17088.17 0.00 43.42 11084.73 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 16-JUL-18:31 0.00 0.00 0.00 -150584.09 0.00 0.00 0.00 807.98 7587.73 59734.95 0.00 2112.97 80340.47 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 06-AUG-09:21 0.00 0.00 0.00 -251010.34 0.00 0.00 181.20 520.69 4889.82 164071.53 0.00 0.00 81748.57 0.00 -0.00 0.00 -401.47 0.00
PERIMETER_MID_ZN_1 03-SEP-12:41 0.00 0.00 0.00 -307321.30 0.00 0.00 280.74 807.99 7587.84 241776.23 0.00 3813.82 53054.68 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 16-JUL-17:11 0.00 0.00 0.00 -276626.08 0.00 0.00 0.00 520.69 4889.79 185025.58 0.00 668.45 85521.57 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 06-AUG-16:11 0.00 0.00 0.00 -19337.43 0.00 0.00 41.70 80.80 758.77 3798.83 0.00 739.69 13917.64 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 06-AUG-08:11 0.00 0.00 0.00 -24302.50 0.00 0.00 19.70 52.07 488.98 19000.82 0.00 0.00 4892.10 0.00 -0.00 0.00 -151.18 0.00
PERIMETER_TOP_ZN_1 06-AUG-14:11 0.00 0.00 0.00 -30913.93 0.00 0.00 30.91 80.80 758.78 15032.48 0.00 439.13 14571.83 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 06-AUG-16:11 0.00 0.00 0.00 -28605.90 0.00 0.00 16.61 52.07 488.98 16858.90 0.00 335.11 10854.24 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 03-AUG-18:50 0.00 0.00 0.00 -8260.54 0.00 0.00 10.53 173.61 7794.42 0.00 0.00 0.00 281.97 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 03-AUG-18:50 0.00 0.00 0.00 -78938.17 0.00 0.00 106.08 1736.14 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -848.26
DATACENTER_TOP_ZN_6 03-AUG-18:40 0.00 0.00 0.00 -7963.81 0.00 0.00 10.62 173.61 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -14.84
DATACENTER_BASEMENT_ZN_6 22-AUG-07:20 0.00 0.00 0.00 -369522.43 0.00 0.00 2182.56 5919.59 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -18212.24
GROUNDFLOOR_PLENUM 17-JUL-05:15 0.00 -11926.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11972.87 0.00 -0.00 0.00 -46.71 0.00
MIDFLOOR_PLENUM 04-MAR-04:01 0.00 -111795.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 143402.99 0.00 -0.00 0.00 -31607.24 0.00
TOPFLOOR_PLENUM 17-JUL-15:00 0.00 -22981.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22981.13 0.00 -0.00 0.00 0.00 0.00
Total Facility 07-AUG-03:02 0.00 73527.95 0.00 -1964195.45 0.00 0.00 0.00 19603.93 623236.89 0.00 0.00 0.00 1318557.34 0.00 -52668.48 0.00 -18062.18 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 05-AUG-16:01 0.00 0.00 23292.41 0.00 0.00 0.00 520.12 1166.43 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -38436.51
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID 09-JAN-05:01 0.00 0.00 540347.65 0.00 0.00 0.00 0.00 20950.64 80571.20 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -641869.49
CORE_TOP 09-JAN-04:01 0.00 0.00 80080.83 0.00 0.00 0.00 0.00 1047.53 8057.12 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -89185.48
PERIMETER_BOT_ZN_3 09-JAN-04:01 0.00 0.00 13736.79 0.00 0.00 0.00 0.00 131.53 1011.70 0.00 0.00 0.00 0.00 0.00 -6558.91 0.00 -842.57 -7478.53
PERIMETER_BOT_ZN_2 09-JAN-04:01 0.00 0.00 15441.51 0.00 0.00 0.00 0.00 84.76 651.98 0.00 0.00 0.00 0.00 0.00 -4357.86 0.00 -565.77 -11254.61
PERIMETER_BOT_ZN_1 09-JAN-04:01 0.00 0.00 21401.51 0.00 0.00 0.00 0.00 131.53 1011.71 0.00 0.00 0.00 0.00 0.00 -6327.92 0.00 -846.47 -15370.37
PERIMETER_BOT_ZN_4 09-JAN-04:01 0.00 0.00 13947.66 0.00 0.00 0.00 0.00 84.76 651.97 0.00 0.00 0.00 0.00 0.00 -4380.95 0.00 -575.86 -9727.57
PERIMETER_MID_ZN_3 30-JAN-04:11 0.00 0.00 144418.85 0.00 0.00 0.00 0.00 1315.28 10116.97 0.00 0.00 0.00 0.00 0.00 -49409.72 0.00 -30977.36 -75464.02
PERIMETER_MID_ZN_2 30-JAN-04:11 0.00 0.00 195879.85 0.00 0.00 0.00 0.00 847.62 6519.76 0.00 0.00 0.00 0.00 0.00 -33029.84 0.00 -21026.06 -149191.32
PERIMETER_MID_ZN_1 09-JAN-03:02 0.00 0.00 235136.81 0.00 0.00 0.00 0.00 1315.31 10117.12 0.00 0.00 0.00 0.00 0.00 -61493.19 0.00 -24945.13 -160130.93
PERIMETER_MID_ZN_4 30-JAN-04:11 0.00 0.00 207502.17 0.00 0.00 0.00 0.00 847.62 6519.72 0.00 0.00 0.00 0.00 0.00 -34472.27 0.00 -21291.15 -159106.09
PERIMETER_TOP_ZN_3 30-JAN-05:21 0.00 0.00 18996.04 0.00 0.00 0.00 0.00 263.06 1011.70 0.00 0.00 0.00 0.00 0.00 -4622.18 0.00 -3791.13 -11857.47
PERIMETER_TOP_ZN_2 31-DEC-03:41 0.00 0.00 19953.44 0.00 0.00 0.00 0.00 84.76 488.98 0.00 0.00 0.00 0.00 0.00 -4039.59 0.00 -2009.11 -14478.49
PERIMETER_TOP_ZN_1 31-DEC-03:41 0.00 0.00 25934.66 0.00 0.00 0.00 0.00 131.53 758.78 0.00 0.00 0.00 0.00 0.00 -5908.71 0.00 -3017.10 -17899.16
PERIMETER_TOP_ZN_4 09-JAN-04:01 0.00 0.00 22214.51 0.00 0.00 0.00 0.00 84.76 651.97 0.00 0.00 0.00 0.00 0.00 -3948.90 0.00 -1568.11 -17434.24
DATACENTER_BOT_ZN_6 09-JAN-03:44 0.00 0.00 640.39 0.00 0.00 0.00 0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2617.93
DATACENTER_MID_ZN_6 29-JAN-17:50 0.00 0.00 6628.76 0.00 0.00 0.00 54.13 289.38 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -26458.32
DATACENTER_TOP_ZN_6 30-APR-23:05 0.00 0.00 778.84 0.00 0.00 0.00 0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2756.38
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 19-DEC-05:01 14977.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -1833.38 -13144.14
MIDFLOOR_PLENUM 09-JAN-06:12 144208.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -8452.67 -135756.26
TOPFLOOR_PLENUM 11-JAN-05:12 35014.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -1465.21 -33549.55
Total Facility 30-JAN-05:01 -5100.34 96520.32 1415958.07 -96520.32 0.00 0.00 0.00 39207.80 268362.69 0.00 0.00 0.00 0.00 0.00 -210490.82 0.00 -206307.45 -1301629.96



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 12.5879 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.9284 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 120.3972 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 101.2491 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 12.3378 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.3018 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.4741 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.4741 0.1854 1.0000 Not calculated 1.2002 0.1854    
AIRLOOP DATACENTER BASEMENT 24.4712 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 24.4714 0.0138 1.0000 Not calculated 0.3384 0.0138    
AIRLOOP DATACENTER BOT 0.5700 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5700 0.0274 1.0000 Not calculated 0.0156 0.0274    
AIRLOOP DATACENTER MID 5.4580 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 5.4580 0.0286 1.0000 Not calculated 0.1563 0.0286    
AIRLOOP DATACENTER TOP 0.5556 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5556 0.0281 1.0000 Not calculated 0.0156 0.0281    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 6.2940 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.7764 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 60.1986 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 36.5663 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 6.1689 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.8621 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.4741 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.4741 1.0000 1.0000 Not calculated 1.2002 0.1854    
AIRLOOP DATACENTER BASEMENT 24.4712 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 24.4712 1.0000 1.0000 Not calculated 0.3384 0.0138    
AIRLOOP DATACENTER BOT 0.5700 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5700 1.0000 1.0000 Not calculated 0.0156 0.0274    
AIRLOOP DATACENTER MID 5.4580 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 5.4580 1.0000 1.0000 Not calculated 0.1563 0.0286    
AIRLOOP DATACENTER TOP 0.5556 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5556 1.0000 1.0000 Not calculated 0.0156 0.0281    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.4741 6.4741 6.4741 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.7944 6.7944 2.0383 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 63.8726 63.8726 19.6089 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.1821 6.1821 2.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0823 1.0823 0.3247 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3412 1.3412 0.4024 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6974 1.6974 0.5092 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6726 1.6726 0.5018 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.1856 10.1856 3.0557 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 14.1044 14.1044 4.2313 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 17.0701 17.0701 5.1210 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 15.1645 15.1645 4.5493 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2866 1.2866 0.3860 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4139 1.4139 0.4242 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8413 1.8413 0.5524 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6139 1.6139 0.4842 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5700 0.5700 0.5700 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.4580 5.4580 5.4580 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5556 0.5556 0.5556 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 24.4712 24.4712 24.4712 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 12.5879 10.9284 12.5879 3.7764 0.0000 1.0000
VAV_MID WITH REHEAT 120.3972 101.2491 120.3972 36.5663 0.0000 1.0000
VAV_TOP WITH REHEAT 12.3378 11.3018 12.3378 3.8621 0.0000 1.0000
CAV_BAS 6.4741 6.4741 6.4741 6.4741 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 24.4712 24.4714 24.4712 24.4712 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5700 0.5700 0.5700 0.5700 0.0156 1.0000
AIRLOOP DATACENTER MID 5.4580 5.4580 5.4580 5.4580 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.5556 0.5556 0.5556 0.5556 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.4741 6.4741 6.4741 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.3972 3.3972 2.0383 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 31.9363 31.9363 19.6089 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.0910 3.0910 2.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5412 0.5412 0.3247 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6706 0.6706 0.4024 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8487 0.8487 0.5092 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8363 0.8363 0.5018 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.0928 5.0928 3.0557 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.0522 7.0522 4.2313 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 8.5351 8.5351 5.1210 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.5822 7.5822 4.5493 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6433 0.6433 0.3860 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7070 0.7070 0.4242 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9206 0.9206 0.5524 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8069 0.8069 0.4842 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5700 0.5700 0.5700 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.4580 5.4580 5.4580 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5556 0.5556 0.5556 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 24.4712 24.4712 24.4712 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 6.2940 3.7764 3.7764 3.7764 0.0000 1.0000
VAV_MID WITH REHEAT 60.1986 36.5663 36.5663 36.5663 0.0000 1.0000
VAV_TOP WITH REHEAT 6.1689 3.8621 3.8621 3.8621 0.0000 1.0000
CAV_BAS 6.4741 6.4741 6.4741 6.4741 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 24.4712 24.4712 24.4712 24.4712 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5700 0.5700 0.5700 0.5700 0.0156 1.0000
AIRLOOP DATACENTER MID 5.4580 5.4580 5.4580 5.4580 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.5556 0.5556 0.5556 0.5556 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 115.33
Number of hours cooling loads not met 480.50
Number of hours not met 595.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 3397.54 2290324.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 3205.79 426109.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 3711.21 352853.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 671.16 54335.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5871.99 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 87.33 5481.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2703.50 324151.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 416.96 56384.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 812.86 81829.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 840.82 52016.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 771.55 85520.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 15213.41 29517.66
Natural Gas 0.00 4169.09
Additional 0.00 0.00
Total 15213.41 33686.75


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 80.12
Space Heating 0.00
Space Cooling 69.21
Fans (All) 58.37
Service Water Heating 0.00
Receptacle Equipment 328.44
Miscellaneous (All) 637.25
Subtotal 637.25


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 73.35
Service Water Heating 16.66
Miscellaneous (All) 90.01
Subtotal 90.01


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 11.02
Space Heating 10.09
Space Cooling 9.52
Fans (All) 8.03
Service Water Heating 2.29
Receptacle Equipment 45.16
Miscellaneous 13.90


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2645. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4487. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 2347. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8718.67 41.33 0.00 0.00 0.00
CORE_BOTTOM 8754.50 5.50 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8758.83 1.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8746.83 13.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8747.67 12.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8699.00 61.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8759.67 0.33 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8744.17 15.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8746.50 13.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8741.00 19.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8758.67 1.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8744.83 15.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8748.50 11.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8738.83 21.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8746.50 13.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8755.50 4.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8754.17 5.83 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8205.33 554.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8742.50 17.50 0.00 0.00 0.00
Min 8205.33 0.00 0.00 0.00 0.00
Max 8760.00 554.67 0.00 0.00 0.00
Average 8723.99 36.01 0.00 0.00 0.00
Sum 200651.67 828.33 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 368438.67 177.33 0.00 0.00 0.00
CORE_BOTTOM 330793.00 20.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2265.50 2.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 95508.33 7886.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 368438.67 7886.67 0.00 0.00 0.00
Average 79983.33 351.59 0.00 0.00 0.00
Sum 1839616.50 8086.50 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8685.33 74.67 0.00 0.00 0.00
CORE_BOTTOM 8725.33 34.67 0.00 0.00 0.00
CORE_MID 8720.00 40.00 0.00 0.00 0.00
CORE_TOP 8733.17 26.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8748.17 11.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8747.83 12.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8744.33 15.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8708.83 51.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8751.17 8.83 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8743.17 16.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8742.00 18.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8734.67 25.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8751.00 9.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8742.67 17.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8743.33 16.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8735.17 24.83 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8394.50 365.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8745.17 14.83 0.00 0.00 0.00
MIDFLOOR_PLENUM 8752.17 7.83 0.00 0.00 0.00
TOPFLOOR_PLENUM 8721.33 38.67 0.00 0.00 0.00
Min 8394.50 0.00 0.00 0.00 0.00
Max 8760.00 365.50 0.00 0.00 0.00
Average 8723.88 36.12 0.00 0.00 0.00
Sum 200649.33 830.67 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 368336.17 279.83 0.00 0.00 0.00
CORE_BOTTOM 330734.00 79.00 0.00 0.00 0.00
CORE_MID 330707.00 106.00 0.00 0.00 0.00
CORE_TOP 330757.00 56.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 98025.33 5369.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 368336.17 5369.67 0.00 0.00 0.00
Average 80078.80 256.11 0.00 0.00 0.00
Sum 1841812.50 5890.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:16

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.483369E+11 109422.06 02-JAN-04:03 -0.5 -3.0 0.533861E+10 7499.16 12-JAN-10:09 6.78 3.19
February 0.432255E+11 108714.50 27-FEB-04:02 4.82 0.54 0.503687E+10 7499.22 06-FEB-10:00 4.82 0.54
March 0.534522E+11 109493.07 27-MAR-03:01 2.02 -1.7 0.611548E+10 7499.21 01-MAR-10:09 2.02 -1.7
April 0.513995E+11 111076.76 24-APR-03:02 4.82 3.52 0.544567E+10 7499.19 04-APR-09:09 4.82 3.52
May 0.543533E+11 111369.96 30-MAY-03:02 15.60 10.52 0.589965E+10 7499.77 02-MAY-13:20 15.60 10.52
June 0.589045E+11 113748.30 05-JUN-03:02 8.62 5.44 0.588123E+10 7499.12 20-JUN-13:20 27.77 18.21
July 0.612236E+11 114647.14 24-JUL-02:52 12.20 8.81 0.547408E+10 7499.22 03-JUL-13:09 12.20 8.81
August 0.682817E+11 111020.31 28-AUG-03:02 9.90 5.61 0.613858E+10 7499.06 01-AUG-13:20 9.90 5.61
September 0.589181E+11 115330.66 25-SEP-03:02 13.22 9.31 0.545243E+10 7499.35 07-SEP-09:00 13.22 9.31
October 0.602410E+11 111018.82 23-OCT-03:02 8.98 3.95 0.567031E+10 7499.08 06-OCT-09:00 8.98 3.95
November 0.557484E+11 113763.15 20-NOV-04:01 -1.7 -4.9 0.561261E+10 7499.08 03-NOV-09:20 -1.7 -4.9
December 0.532276E+11 112017.84 11-DEC-04:01 -2.6 -4.7 0.540854E+10 7499.17 07-DEC-10:09 -2.6 -4.7
                     
Annual Sum or Average 0.667312E+12         0.674740E+11        
Minimum of Months 0.432255E+11 108714.50   -2.6 -4.9 0.503687E+10 7499.06   -2.6 -4.9
Maximum of Months 0.682817E+11 115330.66   15.60 10.52 0.613858E+10 7499.77   27.77 18.21



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.316212E+11 85470.72 02-JAN-05:01 -0.2 -2.7 0.495077E+10 6734.75 02-JAN-10:09 2.48 -0.4
February 0.338215E+11 87271.24 28-FEB-05:01 -3.4 -4.0 0.457101E+10 6734.73 28-FEB-10:09 1.57 -0.3
March 0.474270E+11 87990.47 29-MAR-04:01 -0.1 -2.6 0.549132E+10 6734.78 01-MAR-10:09 -0.1 -2.6
April 0.519398E+11 91365.05 10-APR-03:02 4.40 0.24 0.488335E+10 6734.79 04-APR-09:09 4.40 0.24
May 0.489443E+11 94325.69 30-MAY-03:02 15.60 10.52 0.528951E+10 6735.16 02-MAY-13:09 15.60 10.52
June 0.598851E+11 92244.87 05-JUN-03:02 8.62 5.44 0.526940E+10 6734.79 20-JUN-13:09 27.48 18.05
July 0.662231E+11 95202.99 05-JUL-03:02 9.90 9.28 0.489747E+10 6734.96 03-JUL-13:09 9.90 9.28
August 0.743198E+11 91027.10 23-AUG-03:02 11.20 7.14 0.549787E+10 6734.79 01-AUG-13:09 11.20 7.14
September 0.520086E+11 95353.02 11-SEP-03:02 11.10 10.41 0.488210E+10 6735.13 07-SEP-09:50 11.10 10.41
October 0.497970E+11 90648.56 02-OCT-03:02 5.00 2.94 0.507958E+10 6734.74 27-OCT-09:20 8.13 3.61
November 0.451588E+11 91324.31 06-NOV-04:02 -2.8 -3.9 0.502805E+10 6734.75 03-NOV-09:20 -2.8 -3.9
December 0.413374E+11 88067.31 07-DEC-05:01 -1.6 -2.7 0.488809E+10 6734.78 07-DEC-10:09 3.35 1.22
                     
Annual Sum or Average 0.602484E+12         0.607285E+11        
Minimum of Months 0.316212E+11 85470.72   -3.4 -4.0 0.457101E+10 6734.73   -2.8 -3.9
Maximum of Months 0.743198E+11 95353.02   15.60 10.52 0.549787E+10 6735.16   27.48 18.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.227886E+11 22197.39 05-JAN-17:00 -20.0 -20.5 0.453387E+10 6734.50 04-JAN-14:00 -20.0 -20.5
February 0.227223E+11 32974.19 28-FEB-17:00 10.00 4.31 0.430103E+10 6734.74 28-FEB-10:09 10.00 4.31
March 0.309130E+11 72251.87 30-MAR-05:02 0.00 -2.1 0.532813E+10 6734.77 01-MAR-10:09 0.00 -2.1
April 0.329764E+11 79501.27 25-APR-05:02 1.10 -0.7 0.483230E+10 6734.75 04-APR-09:09 1.10 -0.7
May 0.373035E+11 82557.55 30-MAY-03:02 15.60 10.52 0.525350E+10 6735.19 02-MAY-13:09 15.60 10.52
June 0.470721E+11 82945.55 23-JUN-03:02 17.38 11.72 0.526088E+10 6734.81 20-JUN-13:09 17.38 11.72
July 0.494647E+11 84115.05 19-JUL-03:02 21.02 16.34 0.489297E+10 6734.96 03-JUL-13:09 21.02 16.34
August 0.514817E+11 86169.38 14-AUG-03:02 12.20 10.20 0.549501E+10 6734.80 01-AUG-13:09 12.20 10.20
September 0.410082E+11 84765.63 11-SEP-03:02 11.10 10.41 0.486653E+10 6735.14 07-SEP-09:00 11.10 10.41
October 0.340989E+11 77892.21 17-OCT-05:02 3.90 1.71 0.503328E+10 6734.73 27-OCT-09:20 8.13 3.61
November 0.278594E+11 73286.14 08-NOV-06:02 10.13 4.88 0.486675E+10 6734.74 03-NOV-09:20 10.13 4.88
December 0.248492E+11 28782.98 07-DEC-16:30 5.55 1.71 0.454622E+10 6734.76 07-DEC-10:09 5.55 1.71
                     
Annual Sum or Average 0.422538E+12         0.592105E+11        
Minimum of Months 0.227223E+11 22197.39   -20.0 -20.5 0.430103E+10 6734.50   -20.0 -20.5
Maximum of Months 0.514817E+11 86169.38   21.02 16.34 0.549501E+10 6735.19   21.02 16.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.139895E+11 17269.51 13-JAN-17:00 7.80 3.93 0.396855E+10 6250.00 13-JAN-14:00 7.80 3.93
February 0.162533E+11 25420.93 28-FEB-17:00 10.00 4.31 0.382337E+10 6734.33 28-FEB-14:00 10.00 4.31
March 0.224858E+11 28756.00 23-MAR-15:40 7.40 0.85 0.487108E+10 6734.59 02-MAR-14:30 7.40 0.85
April 0.259464E+11 42101.24 25-APR-16:00 17.80 7.70 0.459338E+10 6734.63 13-APR-13:00 17.80 7.70
May 0.325175E+11 77318.18 20-MAY-05:02 11.47 8.41 0.506190E+10 6735.18 02-MAY-13:09 11.47 8.41
June 0.460665E+11 83055.98 21-JUN-03:02 19.22 13.03 0.523545E+10 6734.77 20-JUN-13:00 19.22 13.03
July 0.507598E+11 82170.91 19-JUL-03:02 21.02 16.34 0.488489E+10 6734.96 03-JUL-13:09 21.02 16.34
August 0.503834E+11 81277.97 10-AUG-03:02 17.38 10.51 0.547944E+10 6734.78 01-AUG-13:09 17.38 10.51
September 0.359145E+11 82121.42 05-SEP-03:02 18.30 12.34 0.476573E+10 6735.09 07-SEP-09:00 16.70 15.61
October 0.255535E+11 48080.75 19-OCT-05:03 12.20 5.54 0.474916E+10 6734.68 20-OCT-09:30 8.35 4.25
November 0.196923E+11 27154.23 03-NOV-16:00 14.30 7.69 0.435755E+10 6734.45 17-NOV-14:00 16.50 8.23
December 0.159645E+11 19521.72 06-DEC-17:00 6.70 2.38 0.399208E+10 6688.62 07-DEC-14:00 8.30 2.55
                     
Annual Sum or Average 0.355527E+12         0.557826E+11        
Minimum of Months 0.139895E+11 17269.51   6.70 0.85 0.382337E+10 6250.00   7.40 0.85
Maximum of Months 0.507598E+11 83055.98   21.02 16.34 0.547944E+10 6735.18   21.02 16.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.142923E+10 3099.00 02-JAN-05:01 -0.2 -2.7 0.490361E+09 783.89 02-JAN-14:50 6.20 1.19
February 0.222864E+10 3977.28 27-FEB-16:00 18.90 7.06 0.477128E+09 845.60 21-FEB-14:00 18.90 7.06
March 0.372776E+10 4409.57 27-MAR-14:40 9.63 2.75 0.624067E+09 845.61 02-MAR-14:20 9.63 2.75
April 0.492516E+10 6875.62 07-APR-14:30 22.50 9.29 0.589346E+09 845.62 13-APR-13:00 13.30 7.60
May 0.553327E+10 12818.70 30-MAY-05:03 15.60 11.34 0.643051E+09 845.68 02-MAY-13:09 15.60 11.34
June 0.873312E+10 12630.23 26-JUN-05:03 9.87 8.82 0.658928E+09 845.64 20-JUN-13:09 9.87 8.82
July 0.105437E+11 12434.53 26-JUL-05:02 19.50 10.94 0.614691E+09 846.91 18-JUL-13:20 19.50 10.94
August 0.104857E+11 12913.10 06-AUG-15:41 35.40 16.19 0.688922E+09 845.64 01-AUG-13:09 35.40 16.19
September 0.597643E+10 15722.04 04-SEP-16:01 32.80 16.54 0.599638E+09 845.67 07-SEP-09:50 16.52 15.26
October 0.449033E+10 5758.45 19-OCT-14:30 21.40 10.24 0.608455E+09 845.62 18-OCT-13:20 21.40 10.24
November 0.339134E+10 4019.59 24-NOV-14:30 14.90 6.43 0.564161E+09 845.61 17-NOV-14:09 14.90 6.43
December 0.250767E+10 3191.03 06-DEC-05:01 7.20 4.06 0.511399E+09 830.36 06-DEC-14:39 11.30 5.42
                     
Annual Sum or Average 0.639724E+11         0.707015E+10        
Minimum of Months 0.142923E+10 3099.00   -0.2 -2.7 0.477128E+09 783.89   6.20 1.19
Maximum of Months 0.105437E+11 15722.04   35.40 16.54 0.688922E+09 846.91   35.40 16.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.146107E+10 3740.98 02-JAN-05:01 -0.2 -2.7 0.310655E+09 511.83 17-JAN-10:30 5.25 1.27
February 0.243029E+10 6388.57 27-FEB-10:00 11.70 4.23 0.303144E+09 544.95 28-FEB-10:09 1.57 -0.3
March 0.419219E+10 8998.90 28-MAR-09:20 5.73 0.86 0.386615E+09 544.95 01-MAR-10:09 5.73 0.86
April 0.554662E+10 11271.55 24-APR-08:30 10.30 6.86 0.363616E+09 544.95 25-APR-09:09 9.87 4.86
May 0.632613E+10 11467.98 19-MAY-08:30 16.95 11.09 0.406852E+09 544.99 02-MAY-13:09 16.95 11.09
June 0.906108E+10 21345.19 25-JUN-07:52 15.60 11.35 0.420817E+09 546.34 23-JUN-09:50 15.60 11.35
July 0.109119E+11 20922.12 02-JUL-08:32 21.67 15.15 0.394291E+09 546.39 03-JUL-09:00 23.30 14.49
August 0.105755E+11 20982.84 06-AUG-08:22 25.25 14.09 0.439550E+09 546.19 07-AUG-09:00 30.60 15.43
September 0.659308E+10 21612.54 04-SEP-08:42 26.52 14.78 0.378475E+09 544.97 07-SEP-09:00 16.70 15.61
October 0.492595E+10 8583.53 18-OCT-09:20 18.13 8.00 0.378526E+09 544.95 16-OCT-09:09 18.13 8.00
November 0.341907E+10 5880.64 06-NOV-09:35 1.20 -1.1 0.341742E+09 544.95 03-NOV-09:20 1.20 -1.1
December 0.219249E+10 3620.85 01-DEC-06:02 1.70 -2.2 0.309683E+09 513.62 20-DEC-10:30 3.85 -0.4
                     
Annual Sum or Average 0.676353E+11         0.443397E+10        
Minimum of Months 0.146107E+10 3620.85   -0.2 -2.7 0.303144E+09 511.83   1.20 -1.1
Maximum of Months 0.109119E+11 21612.54   26.52 15.15 0.439550E+09 546.39   30.60 15.61



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.321116E+10 11419.37 19-JAN-13:30 -6.2 -7.9 0.519275E+09 845.64 31-JAN-14:20 -0.8 -4.4
February 0.547852E+10 25758.13 26-FEB-14:02 15.78 5.88 0.512421E+09 847.27 27-FEB-14:39 18.70 7.17
March 0.786447E+10 18751.34 01-MAR-13:40 6.33 2.52 0.623369E+09 847.97 23-MAR-13:00 10.00 2.51
April 0.842445E+10 18544.08 16-APR-12:02 17.38 7.48 0.569363E+09 846.37 24-APR-13:00 17.80 9.82
May 0.845513E+10 14809.00 19-MAY-13:30 26.65 14.96 0.622891E+09 845.71 02-MAY-13:09 26.65 14.96
June 0.114272E+11 15479.01 25-JUN-15:12 24.80 13.02 0.649594E+09 845.68 19-JUN-13:30 24.80 13.02
July 0.144730E+11 22873.94 16-JUL-15:22 33.05 18.62 0.611858E+09 846.60 14-JUL-13:00 33.05 18.62
August 0.166138E+11 25917.72 06-AUG-13:42 34.32 15.27 0.684270E+09 848.46 22-AUG-13:50 24.13 15.51
September 0.118259E+11 28169.66 04-SEP-15:21 32.50 16.58 0.592582E+09 846.76 05-SEP-13:00 24.40 15.14
October 0.993421E+10 28542.76 15-OCT-12:31 21.83 10.70 0.607568E+09 851.72 18-OCT-13:30 24.70 11.11
November 0.703991E+10 22898.53 12-NOV-13:32 -0.6 -3.6 0.574276E+09 846.99 06-NOV-14:39 -0.6 -3.6
December 0.481657E+10 13178.46 12-DEC-12:30 -2.8 -5.7 0.531271E+09 845.64 19-DEC-14:09 10.97 6.81
                     
Annual Sum or Average 0.109564E+12         0.709874E+10        
Minimum of Months 0.321116E+10 11419.37   -6.2 -7.9 0.512421E+09 845.64   -0.8 -4.4
Maximum of Months 0.166138E+11 28542.76   34.32 18.62 0.684270E+09 851.72   33.05 18.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.248505E+10 4895.35 02-JAN-05:01 -0.2 -2.7 0.314418E+09 521.79 02-JAN-14:00 6.10 1.11
February 0.426120E+10 9917.43 28-FEB-16:40 10.37 4.49 0.314936E+09 544.93 27-FEB-14:00 10.37 4.49
March 0.676626E+10 12444.23 28-MAR-16:00 10.60 3.09 0.409165E+09 544.95 14-MAR-13:00 10.60 3.09
April 0.883160E+10 25973.33 16-APR-17:22 19.70 8.86 0.386872E+09 544.96 13-APR-13:00 19.70 8.86
May 0.823204E+10 25802.33 13-MAY-18:22 21.95 8.73 0.403154E+09 544.96 25-MAY-13:09 17.20 8.78
June 0.115362E+11 25757.82 18-JUN-17:02 25.50 14.50 0.422974E+09 544.97 19-JUN-13:30 24.70 12.18
July 0.144932E+11 27760.02 16-JUL-17:21 33.05 17.12 0.396947E+09 544.98 13-JUL-09:00 33.05 17.12
August 0.160256E+11 27667.00 06-AUG-16:21 35.30 16.02 0.445344E+09 544.97 15-AUG-13:30 25.00 13.67
September 0.843008E+10 28775.52 04-SEP-16:01 32.80 16.54 0.376059E+09 544.99 07-SEP-09:50 16.52 15.26
October 0.703203E+10 17848.21 15-OCT-15:11 22.60 10.96 0.387701E+09 544.96 20-OCT-13:00 13.30 6.77
November 0.587873E+10 9275.45 03-NOV-15:40 14.40 7.69 0.372365E+09 544.94 17-NOV-14:30 16.30 8.01
December 0.504731E+10 8501.44 06-DEC-15:30 10.25 4.94 0.349426E+09 544.94 12-DEC-14:00 -2.8 -5.6
                     
Annual Sum or Average 0.990193E+11         0.457936E+10        
Minimum of Months 0.248505E+10 4895.35   -0.2 -2.7 0.314418E+09 521.79   -2.8 -5.6
Maximum of Months 0.160256E+11 28775.52   35.30 17.12 0.445344E+09 544.99   33.05 17.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.119807E+09 1778.31 13-JAN-17:00 7.80 3.93 0.462912E+09 626.02 10-JAN-10:50 7.80 3.93
February 0.635928E+09 2893.83 27-FEB-13:30 17.75 6.76 0.428214E+09 731.95 27-FEB-14:00 18.90 7.23
March 0.172371E+10 2808.87 23-MAR-13:30 9.70 2.18 0.535506E+09 774.20 29-MAR-13:00 12.80 4.50
April 0.269710E+10 4918.91 07-APR-14:30 22.50 9.29 0.525198E+09 845.60 26-APR-13:00 11.10 4.95
May 0.391550E+10 7053.07 19-MAY-16:00 27.80 14.54 0.599524E+09 845.62 25-MAY-13:09 17.20 8.78
June 0.674903E+10 11399.41 21-JUN-05:03 15.87 11.84 0.651206E+09 845.64 27-JUN-13:00 25.00 13.11
July 0.803598E+10 15058.68 16-JUL-18:31 32.40 17.11 0.612498E+09 846.34 18-JUL-13:20 33.17 17.33
August 0.708744E+10 14214.44 06-AUG-17:21 34.15 15.38 0.680997E+09 845.64 01-AUG-13:09 34.15 15.38
September 0.444613E+10 11882.22 04-SEP-14:11 30.73 16.07 0.570044E+09 845.67 07-SEP-09:00 16.70 15.61
October 0.276229E+10 4186.86 19-OCT-14:40 21.50 10.24 0.542818E+09 845.61 19-OCT-13:09 21.50 10.24
November 0.141170E+10 2799.71 03-NOV-13:30 14.35 7.74 0.485226E+09 772.17 08-NOV-14:00 13.20 7.65
December 0.399587E+09 1999.14 06-DEC-16:20 8.50 3.80 0.449902E+09 669.95 06-DEC-14:00 8.50 3.80
                     
Annual Sum or Average 0.399842E+11         0.654404E+10        
Minimum of Months 0.119807E+09 1778.31   7.80 2.18 0.428214E+09 626.02   7.80 3.80
Maximum of Months 0.803598E+10 15058.68   34.15 17.11 0.680997E+09 846.34   34.15 17.33



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.258075E+09 2508.06 13-JAN-06:03 0.50 -2.4 0.219648E+09 385.84 10-JAN-09:30 0.50 -2.4
February 0.113448E+10 4578.83 26-FEB-11:52 13.30 4.89 0.205397E+09 514.26 28-FEB-09:00 1.10 -0.5
March 0.253030E+10 6868.85 28-MAR-10:05 7.38 1.58 0.257887E+09 521.20 22-MAR-10:20 7.38 1.58
April 0.404820E+10 10382.86 25-APR-09:00 9.40 4.65 0.250072E+09 521.20 06-APR-10:30 9.40 4.65
May 0.535520E+10 11855.12 19-MAY-08:50 17.52 11.29 0.284590E+09 521.26 02-MAY-12:09 17.52 11.29
June 0.843727E+10 20821.35 04-JUN-07:42 15.63 13.07 0.305122E+09 521.61 23-JUN-10:09 27.98 15.45
July 0.101466E+11 24537.22 16-JUL-09:11 22.57 16.22 0.288991E+09 522.87 14-JUL-10:30 22.57 16.22
August 0.924419E+10 25100.89 06-AUG-09:21 28.60 14.63 0.319998E+09 523.29 07-AUG-10:50 30.60 14.99
September 0.576648E+10 22391.49 04-SEP-08:52 26.70 14.88 0.265152E+09 521.21 06-SEP-12:09 22.07 17.08
October 0.363482E+10 7088.57 18-OCT-10:10 20.28 8.90 0.253487E+09 521.20 19-OCT-10:09 19.18 9.33
November 0.176813E+10 3813.69 03-NOV-13:00 13.70 7.60 0.226606E+09 508.28 03-NOV-10:30 13.70 7.60
December 0.527450E+09 2652.07 20-DEC-10:00 3.30 -0.6 0.212117E+09 406.47 07-DEC-11:30 3.30 -0.6
                     
Annual Sum or Average 0.528512E+11         0.308907E+10        
Minimum of Months 0.258075E+09 2508.06   0.50 -2.4 0.205397E+09 385.84   0.50 -2.4
Maximum of Months 0.101466E+11 25100.89   28.60 16.22 0.319998E+09 523.29   30.60 17.08



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.214311E+10 10904.24 19-JAN-14:00 -5.6 -7.5 0.500800E+09 845.64 19-JAN-14:30 -5.3 -7.2
February 0.440719E+10 28055.29 26-FEB-13:12 15.20 5.59 0.491963E+09 846.11 27-FEB-14:39 18.70 7.17
March 0.622283E+10 19948.17 01-MAR-13:50 6.52 2.64 0.590756E+09 846.64 23-MAR-13:00 10.00 2.51
April 0.640843E+10 17735.91 16-APR-13:52 19.40 8.41 0.539762E+09 845.82 24-APR-13:00 17.80 9.82
May 0.724695E+10 15124.33 19-MAY-13:40 26.83 14.98 0.601623E+09 845.71 02-MAY-13:09 26.83 14.98
June 0.990686E+10 14907.61 30-JUN-13:30 28.05 13.89 0.637559E+09 845.68 19-JUN-13:09 28.05 13.89
July 0.123108E+11 27487.61 16-JUL-13:52 31.70 18.44 0.606559E+09 846.26 18-JUL-13:00 31.70 17.43
August 0.137359E+11 27696.65 06-AUG-14:41 34.40 15.36 0.675312E+09 854.75 30-AUG-13:39 26.33 14.35
September 0.111401E+11 30732.60 03-SEP-12:41 33.22 15.94 0.578774E+09 865.68 01-SEP-13:50 33.22 15.94
October 0.886618E+10 27282.21 15-OCT-13:22 22.75 10.91 0.587479E+09 875.79 18-OCT-13:39 24.80 11.21
November 0.541218E+10 24315.79 12-NOV-13:32 -0.6 -3.6 0.548639E+09 846.25 06-NOV-14:50 -0.6 -3.6
December 0.292548E+10 11219.99 12-DEC-14:30 -2.2 -5.4 0.499122E+09 845.63 12-DEC-14:20 -2.2 -5.4
                     
Annual Sum or Average 0.907259E+11         0.685835E+10        
Minimum of Months 0.214311E+10 10904.24   -5.6 -7.5 0.491963E+09 845.63   -5.3 -7.2
Maximum of Months 0.137359E+11 30732.60   34.40 18.44 0.675312E+09 875.79   33.22 17.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.436258E+09 3386.28 13-JAN-15:50 9.08 4.76 0.300990E+09 453.77 13-JAN-15:00 8.90 4.67
February 0.138149E+10 6693.60 28-FEB-16:40 10.37 4.49 0.281565E+09 521.20 27-FEB-16:30 10.37 4.49
March 0.279185E+10 8340.89 28-MAR-17:00 10.60 2.97 0.344190E+09 544.85 02-MAR-14:00 10.60 2.97
April 0.435108E+10 22865.17 16-APR-17:11 19.80 8.90 0.325477E+09 540.75 07-APR-13:00 19.80 8.90
May 0.588951E+10 23168.34 28-MAY-17:52 20.00 10.33 0.369196E+09 544.94 19-MAY-13:30 20.00 10.33
June 0.826535E+10 23796.50 18-JUN-17:31 25.20 14.48 0.402821E+09 544.96 27-JUN-13:00 25.00 13.11
July 0.974864E+10 27664.98 16-JUL-17:11 33.13 17.22 0.386743E+09 544.97 03-JUL-13:09 33.13 17.22
August 0.908122E+10 24794.91 06-AUG-16:41 35.10 15.80 0.424823E+09 544.96 01-AUG-13:09 35.10 15.80
September 0.614916E+10 26400.92 04-SEP-16:51 32.80 16.77 0.347428E+09 544.94 05-SEP-13:00 24.40 15.14
October 0.402715E+10 9677.05 16-OCT-16:00 19.40 8.07 0.336098E+09 531.07 13-OCT-13:00 19.40 8.07
November 0.218316E+10 5093.91 03-NOV-15:50 14.35 7.69 0.314379E+09 522.38 09-NOV-14:00 9.00 3.82
December 0.858996E+09 3693.53 06-DEC-15:50 9.68 4.65 0.292651E+09 482.87 06-DEC-15:00 9.40 4.51
                     
Annual Sum or Average 0.551639E+11         0.412636E+10        
Minimum of Months 0.436258E+09 3386.28   9.08 2.97 0.281565E+09 453.77   8.90 2.97
Maximum of Months 0.974864E+10 27664.98   35.10 17.22 0.424823E+09 544.97   35.10 17.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 28595646.44 2087.53 14-JAN-17:03 8.90 4.06 0.458969E+09 626.05 09-JAN-14:30 8.90 4.06
February 0.231349E+09 2622.12 27-FEB-16:10 17.78 6.92 0.421849E+09 670.30 27-FEB-14:00 17.78 6.92
March 0.935659E+09 2821.68 29-MAR-16:00 12.20 4.07 0.511549E+09 703.28 29-MAR-13:00 12.20 4.07
April 0.214659E+10 4425.28 07-APR-14:30 22.50 9.29 0.484754E+09 845.60 07-APR-13:50 22.50 9.29
May 0.371830E+10 7709.16 19-MAY-16:00 27.80 14.54 0.562775E+09 845.63 19-MAY-13:09 27.80 14.54
June 0.687946E+10 9530.52 29-JUN-15:10 32.02 14.63 0.633031E+09 845.63 21-JUN-13:09 32.02 14.63
July 0.846756E+10 15130.90 16-JUL-18:41 32.30 17.18 0.605987E+09 845.65 03-JUL-13:09 32.30 17.18
August 0.729852E+10 19338.03 06-AUG-16:11 35.40 16.13 0.663961E+09 845.64 01-AUG-13:09 35.40 16.13
September 0.428284E+10 8066.96 05-SEP-14:00 24.40 15.14 0.536253E+09 845.62 05-SEP-09:09 24.40 15.14
October 0.205354E+10 4115.68 18-OCT-13:50 24.90 11.31 0.497626E+09 826.58 19-OCT-13:00 21.10 10.22
November 0.673898E+09 2665.86 17-NOV-17:00 17.20 8.89 0.463598E+09 693.63 08-NOV-14:00 17.20 8.89
December 0.121714E+09 2181.97 06-DEC-16:20 8.50 3.80 0.446542E+09 626.02 29-DEC-14:50 -19.5 -20.1
                     
Annual Sum or Average 0.368380E+11         0.628689E+10        
Minimum of Months 28595646.44 2087.53   8.50 3.80 0.421849E+09 626.02   -19.5 -20.1
Maximum of Months 0.846756E+10 19338.03   35.40 17.18 0.663961E+09 845.65   35.40 17.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 65819451.08 2513.67 19-JAN-06:04 -14.9 -15.6 0.298656E+09 403.47 10-JAN-10:50 -14.9 -15.6
February 0.668312E+09 3276.85 28-FEB-10:30 2.50 0.37 0.275084E+09 487.83 28-FEB-10:39 2.97 0.62
March 0.173132E+10 5190.53 23-MAR-10:30 8.60 1.66 0.343013E+09 544.95 28-MAR-09:39 6.47 1.20
April 0.317380E+10 9357.45 25-APR-09:40 11.27 5.45 0.333308E+09 544.95 25-APR-09:09 11.27 5.45
May 0.478880E+10 11400.37 19-MAY-09:20 18.53 11.74 0.381764E+09 544.99 02-MAY-13:09 18.53 11.74
June 0.830770E+10 22632.36 25-JUN-09:02 17.15 11.95 0.413772E+09 545.98 23-JUN-09:00 17.15 11.95
July 0.103461E+11 22351.13 16-JUL-09:22 22.75 16.30 0.391788E+09 545.73 03-JUL-09:00 22.75 16.30
August 0.921965E+10 24303.86 06-AUG-08:11 24.60 14.01 0.435031E+09 546.09 11-AUG-09:00 27.80 12.62
September 0.516773E+10 16405.27 04-SEP-09:02 26.88 14.90 0.356500E+09 544.95 15-SEP-13:09 19.08 11.71
October 0.275087E+10 5935.97 18-OCT-10:00 20.00 8.80 0.332275E+09 544.95 18-OCT-09:20 20.00 8.80
November 0.994073E+09 3210.92 03-NOV-10:00 8.70 5.33 0.299979E+09 479.07 03-NOV-09:00 8.70 5.33
December 0.213554E+09 2489.13 09-DEC-06:04 -5.1 -5.7 0.288222E+09 403.43 27-DEC-10:00 -12.2 -12.7
                     
Annual Sum or Average 0.474277E+11         0.414939E+10        
Minimum of Months 65819451.08 2489.13   -14.9 -15.6 0.275084E+09 403.43   -14.9 -15.6
Maximum of Months 0.103461E+11 24303.86   26.88 16.30 0.435031E+09 546.09   27.80 16.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.144381E+10 8957.88 31-JAN-13:40 -0.8 -4.5 0.485424E+09 845.63 31-JAN-14:00 -1.1 -4.4
February 0.333083E+10 27507.63 26-FEB-14:21 16.15 6.12 0.470774E+09 845.86 28-FEB-14:39 10.40 4.69
March 0.473577E+10 17910.34 01-MAR-14:10 6.97 2.89 0.569424E+09 846.20 23-MAR-13:50 9.90 2.40
April 0.518975E+10 16948.28 25-APR-13:40 16.30 6.98 0.517864E+09 845.93 24-APR-13:20 16.30 6.98
May 0.652726E+10 15685.85 19-MAY-13:50 27.02 15.00 0.582296E+09 845.71 02-MAY-13:09 27.02 15.00
June 0.978493E+10 17968.33 25-JUN-15:02 24.90 13.05 0.623853E+09 845.66 21-JUN-13:09 24.90 13.05
July 0.126601E+11 27884.71 16-JUL-14:02 31.97 18.55 0.599840E+09 846.65 18-JUL-13:00 31.70 17.43
August 0.137872E+11 30915.84 06-AUG-14:11 34.40 15.37 0.664933E+09 846.58 31-AUG-13:39 25.37 13.99
September 0.103255E+11 30633.58 03-SEP-13:31 33.70 16.17 0.560733E+09 848.84 01-SEP-13:50 33.70 16.17
October 0.714543E+10 30022.91 15-OCT-14:22 23.05 11.10 0.561241E+09 845.76 23-OCT-13:39 20.77 9.63
November 0.398203E+10 17302.60 03-NOV-13:30 14.35 7.74 0.521539E+09 845.82 03-NOV-13:00 15.00 7.85
December 0.194211E+10 8609.56 06-DEC-14:40 11.30 5.42 0.480003E+09 845.63 01-DEC-14:00 11.30 5.42
                     
Annual Sum or Average 0.808547E+11         0.663793E+10        
Minimum of Months 0.144381E+10 8609.56   -0.8 -4.5 0.470774E+09 845.63   -1.1 -4.4
Maximum of Months 0.137872E+11 30915.84   34.40 18.55 0.664933E+09 848.84   33.70 17.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.227232E+09 3377.10 13-JAN-15:50 9.08 4.76 0.299155E+09 434.37 13-JAN-15:00 8.90 4.67
February 0.914164E+09 6085.77 28-FEB-16:40 10.37 4.49 0.277817E+09 521.18 28-FEB-16:00 10.00 4.31
March 0.191771E+10 7911.71 28-MAR-17:00 10.60 2.97 0.338149E+09 531.11 02-MAR-14:00 10.60 2.97
April 0.356248E+10 17634.83 16-APR-17:11 19.80 8.90 0.313902E+09 536.38 25-APR-13:00 16.10 6.69
May 0.539540E+10 24383.89 28-MAY-17:52 20.00 10.33 0.357709E+09 544.95 19-MAY-13:50 20.00 10.33
June 0.818649E+10 26299.55 18-JUN-16:41 25.50 14.47 0.393168E+09 544.96 20-JUN-13:09 27.48 18.05
July 0.998672E+10 27979.85 09-JUL-17:31 27.97 13.10 0.381483E+09 544.97 03-JUL-13:09 27.97 13.10
August 0.910991E+10 28607.14 06-AUG-16:11 35.40 16.13 0.416015E+09 544.96 01-AUG-13:09 35.40 16.13
September 0.565537E+10 25445.69 04-SEP-16:22 32.80 16.63 0.336924E+09 544.94 05-SEP-13:00 24.40 15.14
October 0.309750E+10 9471.34 18-OCT-16:00 24.40 11.02 0.322964E+09 521.18 11-OCT-15:00 24.40 11.02
November 0.139780E+10 4337.77 03-NOV-16:00 14.30 7.69 0.305681E+09 520.31 03-NOV-15:00 14.30 7.69
December 0.467476E+09 3678.20 06-DEC-15:50 9.68 4.65 0.289630E+09 460.53 06-DEC-15:00 9.40 4.51
                     
Annual Sum or Average 0.499183E+11         0.403260E+10        
Minimum of Months 0.227232E+09 3377.10   9.08 2.97 0.277817E+09 434.37   8.90 2.97
Maximum of Months 0.998672E+10 28607.14   35.40 16.63 0.416015E+09 544.97   35.40 18.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.664186E+09 7642.15 06-JAN-05:01 -24.5 -24.9 0.00 0.00 01-JAN-00:10 -24.5 -24.9
February 0.994793E+09 5618.53 28-FEB-06:08 -3.9 -4.3 0.00 0.00 01-FEB-00:10 -3.9 -4.3
March 0.249003E+10 5445.36 01-MAR-06:08 -12.2 -12.7 0.00 0.00 01-MAR-00:10 -12.2 -12.7
April 0.416925E+10 5853.81 25-APR-05:08 1.10 -0.7 0.00 0.00 01-APR-00:10 1.10 -0.7
May 0.422889E+10 9655.13 30-MAY-05:15 15.60 11.34 0.00 0.00 01-MAY-00:10 15.60 11.34
June 0.763454E+10 8736.68 26-JUN-05:15 10.33 9.12 0.00 0.00 01-JUN-00:10 10.33 9.12
July 0.965296E+10 11925.90 17-JUL-05:15 16.83 12.38 0.00 0.00 01-JUL-00:10 16.83 12.38
August 0.100594E+11 10771.09 07-AUG-05:25 18.05 10.23 0.00 0.00 01-AUG-00:10 18.05 10.23
September 0.595347E+10 10073.69 06-SEP-05:13 15.00 12.76 0.00 0.00 01-SEP-00:10 15.00 12.76
October 0.430051E+10 5671.83 02-OCT-05:15 4.80 2.86 0.00 0.00 01-OCT-00:10 4.80 2.86
November 0.252724E+10 6023.33 06-NOV-06:07 -3.5 -4.3 0.00 0.00 01-NOV-00:10 -3.5 -4.3
December 0.123930E+10 4374.40 09-DEC-06:07 -5.1 -5.7 0.00 0.00 01-DEC-00:10 -5.1 -5.7
                     
Annual Sum or Average 0.539146E+11         0.00        
Minimum of Months 0.664186E+09 4374.40   -24.5 -24.9 0.00 0.00   -24.5 -24.9
Maximum of Months 0.100594E+11 11925.90   18.05 12.76 0.00 0.00   18.05 12.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.437145E+09 10304.67 06-JAN-04:11 -24.4 -24.9 0.00 0.00 01-JAN-00:10 -24.4 -24.9
February 0.343269E+09 9223.57 04-FEB-04:11 -21.7 -22.0 0.00 0.00 01-FEB-00:10 -21.7 -22.0
March 0.998663E+09 11179.56 04-MAR-04:01 -18.4 -18.9 0.00 0.00 01-MAR-00:10 -18.4 -18.9
April 0.174361E+10 6667.10 29-APR-04:01 -7.8 -8.7 0.00 0.00 01-APR-00:10 -7.8 -8.7
May 0.242779E+10 6448.79 08-MAY-04:01 -2.3 -2.7 0.00 0.00 01-MAY-00:10 -2.3 -2.7
June 0.554971E+10 6698.62 23-JUN-15:30 27.50 14.33 0.00 0.00 01-JUN-00:10 27.50 14.33
July 0.722867E+10 8154.85 17-JUL-15:20 36.47 17.10 0.00 0.00 01-JUL-00:10 36.47 17.10
August 0.710100E+10 8156.32 07-AUG-15:40 32.40 16.10 0.00 0.00 01-AUG-00:10 32.40 16.10
September 0.427619E+10 7728.48 05-SEP-14:40 24.40 14.90 0.00 0.00 01-SEP-00:10 24.40 14.90
October 0.214994E+10 6029.53 10-OCT-04:01 -5.2 -5.7 0.00 0.00 01-OCT-00:10 -5.2 -5.7
November 0.985698E+09 8747.41 27-NOV-04:01 -15.8 -16.7 0.00 0.00 01-NOV-00:10 -15.8 -16.7
December 0.583042E+09 8033.56 29-DEC-04:01 -24.5 -24.8 0.00 0.00 01-DEC-00:10 -24.5 -24.8
                     
Annual Sum or Average 0.338247E+11         0.00        
Minimum of Months 0.343269E+09 6029.53   -24.5 -24.9 0.00 0.00   -24.5 -24.9
Maximum of Months 0.722867E+10 11179.56   36.47 17.10 0.00 0.00   36.47 17.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 12354.73 82.36 14-JAN-17:10 8.90 4.06 0.00 0.00 01-JAN-00:10 8.90 4.06
February 94367182.19 2545.11 26-FEB-14:26 16.15 6.12 0.00 0.00 01-FEB-00:10 16.15 6.12
March 0.563955E+09 4410.76 23-MAR-13:40 9.80 2.29 0.00 0.00 01-MAR-00:10 9.80 2.29
April 0.217949E+10 10711.34 25-APR-15:00 17.00 7.46 0.00 0.00 01-APR-00:10 17.00 7.46
May 0.467572E+10 16442.43 19-MAY-15:00 28.30 14.88 0.00 0.00 01-MAY-00:10 28.30 14.88
June 0.968488E+10 19298.83 23-JUN-13:30 31.40 15.21 0.00 0.00 01-JUN-00:10 31.40 15.21
July 0.128960E+11 22981.96 17-JUL-15:00 36.10 17.00 0.00 0.00 01-JUL-00:10 36.10 17.00
August 0.110028E+11 20527.83 07-AUG-15:40 32.40 16.10 0.00 0.00 01-AUG-00:10 32.40 16.10
September 0.518587E+10 15022.49 01-SEP-15:40 28.30 14.15 0.00 0.00 01-SEP-00:10 28.30 14.15
October 0.137413E+10 8533.89 18-OCT-15:10 24.90 11.51 0.00 0.00 01-OCT-00:10 24.90 11.51
November 94553154.05 1924.04 03-NOV-14:20 14.87 7.79 0.00 0.00 01-NOV-00:10 14.87 7.79
December 0.00 0.00 01-DEC-00:10 -2.1 -4.2 0.00 0.00 01-DEC-00:10 -2.1 -4.2
                     
Annual Sum or Average 0.477518E+11         0.00        
Minimum of Months 0.00 0.00   -2.1 -4.2 0.00 0.00   -2.1 -4.2
Maximum of Months 0.128960E+11 22981.96   36.10 17.00 0.00 0.00   36.10 17.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.203709E+10 2000.09 19-JAN-16:50 -6.4 -8.0 95189148.19 126.82 02-JAN-10:09 -6.4 -8.0
February 0.724141E+10 4351.56 28-FEB-17:00 10.00 4.31 86396455.50 126.82 09-FEB-14:20 10.00 4.31
March 0.137836E+11 6820.26 31-MAR-24:00 2.50 0.99 0.103236E+09 126.82 29-MAR-13:09 2.50 0.99
April 0.187626E+11 8237.58 25-APR-18:10 16.73 7.64 91605248.45 126.82 21-APR-09:00 16.73 7.64
May 0.422608E+10 3506.78 31-MAY-24:00 15.50 10.27 99234985.04 126.84 30-MAY-09:30 15.50 10.27
June 0.935433E+10 5350.58 30-JUN-23:12 20.20 12.29 98962590.25 126.85 01-JUN-13:00 20.20 12.29
July 0.148553E+11 7256.02 31-JUL-23:40 19.77 11.91 91883731.97 126.84 03-JUL-13:09 19.77 11.91
August 0.199388E+11 8260.85 03-AUG-18:50 24.60 12.54 0.103466E+09 132.67 11-AUG-13:00 32.20 13.16
September 0.421326E+10 3314.41 30-SEP-24:00 11.80 6.26 91611124.86 126.86 06-SEP-13:39 11.80 6.26
October 0.917216E+10 4956.61 31-OCT-24:00 4.70 1.47 95230936.12 126.83 25-OCT-09:00 4.70 1.47
November 0.134260E+11 6112.93 13-NOV-16:20 3.27 -2.5 94300334.74 126.83 08-NOV-14:00 3.27 -2.5
December 0.184149E+11 7887.99 06-DEC-16:10 8.95 4.16 91880819.54 126.82 15-DEC-14:39 -10.6 -10.9
                     
Annual Sum or Average 0.135425E+12         0.114300E+10        
Minimum of Months 0.203709E+10 2000.09   -6.4 -8.0 86396455.50 126.82   -10.6 -10.9
Maximum of Months 0.199388E+11 8260.85   24.60 12.54 0.103466E+09 132.67   32.20 13.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.531494E+09 1638.84 19-JAN-16:50 -6.4 -8.0 93479354.29 126.82 04-JAN-10:09 -6.4 -8.0
February 0.500080E+10 3967.54 28-FEB-17:00 10.00 4.31 86396467.54 126.82 03-FEB-14:30 10.00 4.31
March 0.113652E+11 5898.77 31-MAR-23:30 2.00 0.53 0.103236E+09 126.82 29-MAR-13:09 2.00 0.53
April 0.167655E+11 7816.14 25-APR-18:10 16.73 7.64 91605285.46 126.82 24-APR-09:09 16.73 7.64
May 0.321674E+10 3305.33 31-MAY-24:00 15.50 10.27 99234851.51 126.84 30-MAY-09:30 15.50 10.27
June 0.855243E+10 5241.42 30-JUN-23:55 19.60 12.23 98962372.41 126.85 01-JUN-13:50 19.60 12.23
July 0.140068E+11 7067.46 31-JUL-23:53 19.20 11.32 91883994.61 126.84 03-JUL-13:09 19.20 11.32
August 0.187065E+11 7894.12 03-AUG-18:50 24.60 12.54 0.103320E+09 130.18 11-AUG-13:00 32.20 13.16
September 0.338162E+10 2869.57 30-SEP-23:40 12.27 6.64 91609841.68 126.84 11-SEP-13:00 12.27 6.64
October 0.748440E+10 4140.53 31-OCT-24:00 4.70 1.47 95230858.11 126.83 25-OCT-09:00 4.70 1.47
November 0.109556E+11 5570.73 03-NOV-16:00 14.30 7.69 94300354.64 126.83 08-NOV-14:00 13.20 7.65
December 0.148897E+11 7159.06 06-DEC-16:20 8.50 3.80 91880842.46 126.82 18-DEC-14:39 0.60 -2.8
                     
Annual Sum or Average 0.114857E+12         0.114114E+10        
Minimum of Months 0.531494E+09 1638.84   -6.4 -8.0 86396467.54 126.82   -6.4 -8.0
Maximum of Months 0.187065E+11 7894.12   24.60 12.54 0.103320E+09 130.18   32.20 13.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.207777E+09 1412.46 13-JAN-16:30 8.35 4.30 88646654.17 126.87 24-JAN-10:09 0.60 -0.8
February 0.340319E+10 3906.11 28-FEB-17:00 10.00 4.31 86391631.66 126.82 01-FEB-14:20 10.00 4.31
March 0.968651E+10 5836.58 28-MAR-17:50 9.18 2.32 0.103236E+09 126.82 29-MAR-13:09 12.30 4.26
April 0.155485E+11 7866.44 25-APR-18:10 16.73 7.64 91605313.83 126.82 21-APR-09:00 16.73 7.64
May 0.261452E+10 3221.75 31-MAY-24:00 15.50 10.27 98949549.85 126.84 30-MAY-09:39 15.50 10.27
June 0.830384E+10 5241.25 30-JUN-23:55 19.60 12.23 98962418.46 126.85 01-JUN-13:00 19.60 12.23
July 0.139207E+11 7020.76 31-JUL-23:53 19.20 11.32 91884005.65 126.84 03-JUL-13:09 19.20 11.32
August 0.185383E+11 7964.13 03-AUG-18:40 24.80 12.58 0.103296E+09 128.68 11-AUG-13:00 32.20 13.16
September 0.282002E+10 2744.97 04-SEP-17:32 32.07 16.48 91608048.39 126.84 05-SEP-09:00 17.20 11.96
October 0.604409E+10 4046.38 18-OCT-17:00 21.70 10.27 95230836.49 126.83 25-OCT-09:00 13.30 8.54
November 0.902619E+10 5486.74 03-NOV-16:00 14.30 7.69 94300359.98 126.83 08-NOV-14:00 13.20 7.65
December 0.128215E+11 7056.03 06-DEC-16:20 8.50 3.80 91880849.26 126.82 27-DEC-14:30 -15.6 -16.1
                     
Annual Sum or Average 0.102935E+12         0.113599E+10        
Minimum of Months 0.207777E+09 1412.46   8.35 2.32 86391631.66 126.82   -15.6 -16.1
Maximum of Months 0.185383E+11 7964.13   32.07 16.48 0.103296E+09 128.68   32.20 13.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.234172E+12 91678.72 02-JAN-17:00 2.20 -1.7 0.206142E+10 2745.29 02-JAN-14:00 2.20 -1.7
February 0.433230E+12 183625.84 28-FEB-17:00 10.00 4.31 0.187202E+10 2748.45 10-FEB-10:20 10.00 4.31
March 0.726873E+12 357551.65 31-MAR-24:00 2.50 0.99 0.223630E+10 2747.51 03-MAR-10:00 2.50 0.99
April 0.940985E+12 367104.14 26-APR-16:00 9.40 4.24 0.199568E+10 3007.30 07-APR-13:00 9.40 4.24
May 0.239915E+12 176036.66 31-MAY-24:00 15.50 10.27 0.214841E+10 2747.90 30-MAY-13:00 15.50 10.27
June 0.469940E+12 267990.03 30-JUN-24:00 19.60 12.23 0.214398E+10 2748.92 22-JUN-13:09 19.60 12.23
July 0.732530E+12 359143.61 31-JUL-23:12 20.33 12.51 0.198986E+10 2750.00 18-JUL-09:00 20.33 12.51
August 0.972124E+12 369523.53 22-AUG-07:20 12.77 9.84 0.254667E+10 3859.23 07-AUG-13:00 12.77 9.84
September 0.235574E+12 175705.64 30-SEP-24:00 11.80 6.26 0.198353E+10 2748.16 06-SEP-13:39 11.80 6.26
October 0.486854E+12 267688.27 31-OCT-24:00 4.70 1.47 0.206339E+10 2748.51 24-OCT-13:09 4.70 1.47
November 0.707049E+12 276683.89 06-NOV-16:55 6.70 2.26 0.204275E+10 2747.58 08-NOV-14:00 13.20 7.65
December 0.973541E+12 367834.76 07-DEC-17:00 4.40 1.14 0.198912E+10 2745.72 29-DEC-10:09 -23.5 -23.9
                     
Annual Sum or Average 0.715279E+13         0.250731E+11        
Minimum of Months 0.234172E+12 91678.72   2.20 -1.7 0.187202E+10 2745.29   -23.5 -23.9
Maximum of Months 0.973541E+12 369523.53   20.33 12.51 0.254667E+10 3859.23   20.33 12.51



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.301584E+09 13047.72 02-JAN-04:05 -0.5
February 78653578.47 13085.06 27-FEB-04:04 4.82
March 0.134655E+09 12977.11 15-MAR-04:04 -1.1
April 0.137253E+09 13088.66 03-APR-03:04 1.88
May 0.284582E+09 15765.98 20-MAY-16:03 29.82
June 0.265307E+09 14481.83 24-JUN-16:02 28.22
July 0.408255E+09 20391.58 15-JUL-16:01 32.80
August 0.404490E+09 23292.48 05-AUG-16:01 35.22
September 0.481548E+09 21093.72 02-SEP-16:02 33.98
October 0.389405E+09 13225.42 16-OCT-03:45 12.30
November 0.270651E+09 12983.38 20-NOV-04:44 -1.7
December 0.123748E+09 12711.28 30-DEC-06:04 -20.5
         
Annual Sum or Average 0.328013E+10      
Minimum of Months 78653578.47 12711.28   -20.5
Maximum of Months 0.481548E+09 23292.48   35.22



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.38
February 0.00 0.00 01-FEB-00:10 -12.4
March 0.00 0.00 01-MAR-00:10 -3.0
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:05 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -12.4
Maximum of Months 0.00 0.00   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.423125E+09 54034.84 09-JAN-05:01 -27.2
February 0.143289E+09 52188.75 06-FEB-05:01 -0.4
March 34530066.70 50710.21 06-MAR-05:01 -18.4
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:05 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 5391611.82 47264.98 27-NOV-06:01 -14.5
December 0.100799E+09 51362.20 26-DEC-05:11 -7.4
         
Annual Sum or Average 0.707135E+09      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.423125E+09 54034.84   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.832726E+10 80080.93 09-JAN-04:01 -27.2
February 0.289604E+10 79068.21 06-FEB-04:11 -0.6
March 0.165733E+10 78871.35 06-MAR-04:01 -18.4
April 42111400.19 64096.14 10-APR-05:01 3.90
May 0.526948E+09 71741.53 08-MAY-04:01 -2.3
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.271047E+09 71496.44 10-OCT-04:01 -5.2
November 0.197885E+10 78725.86 27-NOV-04:01 -15.8
December 0.416207E+10 78587.15 26-DEC-04:01 -6.3
         
Annual Sum or Average 0.198617E+11      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.832726E+10 80080.93   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.207579E+10 13736.79 09-JAN-04:01 -27.2
February 0.477819E+09 12244.76 04-FEB-05:01 -20.4
March 83842469.87 12437.51 06-MAR-05:01 -18.4
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:05 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 28943984.30 11655.47 27-NOV-05:01 -15.4
December 0.296234E+09 12112.04 30-DEC-05:01 -20.6
         
Annual Sum or Average 0.296263E+10      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.207579E+10 13736.79   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.137111E+10 15441.51 09-JAN-04:01 -27.2
February 0.376444E+09 13800.66 04-FEB-05:01 -20.4
March 76167110.74 13901.58 06-MAR-05:01 -18.4
April 1304394.21 7979.91 29-APR-05:01 -7.7
May 756500.85 10573.28 22-MAY-05:01 -0.6
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 484025.34 2519.07 10-OCT-05:03 -6.1
November 43964110.85 13273.28 27-NOV-05:01 -15.4
December 0.334159E+09 13888.89 30-DEC-05:01 -20.6
         
Annual Sum or Average 0.220438E+10      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.137111E+10 15441.51   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.194849E+10 21401.51 09-JAN-04:01 -27.2
February 0.441711E+09 19618.78 04-FEB-05:01 -20.4
March 0.140663E+09 20215.03 06-MAR-04:01 -18.4
April 2962893.07 16382.12 29-APR-05:01 -7.7
May 15550128.32 16475.60 08-MAY-05:02 -2.8
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 3316984.83 11310.79 10-OCT-05:03 -6.1
November 0.102690E+09 19240.24 27-NOV-05:01 -15.4
December 0.451459E+09 19446.68 30-DEC-05:01 -20.6
         
Annual Sum or Average 0.310685E+10      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.194849E+10 21401.51   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.601901E+09 13947.66 09-JAN-04:01 -27.2
February 33162460.92 10825.85 10-FEB-06:01 -19.9
March 4806836.58 11563.78 06-MAR-05:01 -18.4
April 0.00 0.00 01-APR-00:10 2.68
May 285749.86 4286.25 22-MAY-05:01 -0.6
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 1510040.08 10814.36 27-NOV-06:01 -14.5
December 4074133.22 10723.64 29-DEC-06:01 -25.1
         
Annual Sum or Average 0.645740E+09      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.601901E+09 13947.66   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.766619E+10 14441.97 30-JAN-04:11 -17.6
February 0.351477E+10 13752.34 06-FEB-01:32 -2.4
March 0.157057E+10 13771.78 06-MAR-03:23 -18.6
April 0.153438E+09 11400.27 29-APR-04:01 -7.8
May 0.176671E+09 11843.75 08-MAY-04:01 -2.3
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 18436649.93 10498.83 20-SEP-05:03 3.30
October 0.138277E+09 11741.58 10-OCT-04:01 -5.2
November 0.148759E+10 13545.43 27-NOV-04:01 -15.8
December 0.449676E+10 13765.33 31-DEC-07:31 -28.0
         
Annual Sum or Average 0.192227E+11      
Minimum of Months 0.00 0.00   -28.0
Maximum of Months 0.766619E+10 14441.97   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.463994E+10 19588.13 30-JAN-04:11 -17.6
February 0.196633E+10 18417.42 05-FEB-04:52 -20.0
March 0.875646E+09 18532.15 06-MAR-04:01 -18.4
April 90621297.98 15433.66 29-APR-04:01 -7.8
May 0.113660E+09 16107.43 08-MAY-04:01 -2.3
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 11068969.11 8932.05 20-SEP-05:03 3.30
October 79238020.63 15861.80 10-OCT-04:01 -5.2
November 0.927575E+09 18417.11 27-NOV-04:01 -15.8
December 0.272680E+10 18710.09 31-DEC-07:31 -28.0
         
Annual Sum or Average 0.114309E+11      
Minimum of Months 0.00 0.00   -28.0
Maximum of Months 0.463994E+10 19588.13   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.490378E+10 23513.84 09-JAN-03:02 -27.2
February 0.177176E+10 22407.19 05-FEB-04:52 -20.0
March 0.908919E+09 22473.14 06-MAR-04:01 -18.4
April 0.122316E+09 18722.58 29-APR-04:01 -7.8
May 0.175680E+09 19613.89 08-MAY-04:01 -2.3
June 47981.25 319.88 17-JUN-05:03 2.35
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 10150942.15 9971.36 19-SEP-05:03 2.20
October 66345016.38 19074.92 10-OCT-04:01 -5.2
November 0.854189E+09 22225.23 27-NOV-04:01 -15.8
December 0.261679E+10 22748.66 31-DEC-07:31 -28.0
         
Annual Sum or Average 0.114300E+11      
Minimum of Months 0.00 0.00   -28.0
Maximum of Months 0.490378E+10 23513.84   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.413037E+10 20750.35 30-JAN-04:11 -17.6
February 0.152055E+10 19212.46 06-FEB-04:11 -0.6
March 0.677066E+09 19629.12 06-MAR-04:01 -18.4
April 54238530.87 15364.09 29-APR-05:01 -7.7
May 82894289.40 16979.88 08-MAY-04:01 -2.3
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 7532999.77 7495.85 19-SEP-05:03 2.20
October 52339416.61 16226.19 10-OCT-04:01 -5.2
November 0.646624E+09 19538.55 27-NOV-04:01 -15.8
December 0.203501E+10 19846.83 31-DEC-07:31 -28.0
         
Annual Sum or Average 0.920663E+10      
Minimum of Months 0.00 0.00   -28.0
Maximum of Months 0.413037E+10 20750.35   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.152191E+11 18996.18 30-JAN-05:21 -16.6
February 0.780276E+10 18144.69 06-FEB-01:32 -2.4
March 0.484183E+10 18265.78 06-MAR-05:01 -18.4
April 0.128561E+10 15819.18 29-APR-03:02 -6.9
May 0.102507E+10 16336.08 08-MAY-03:01 -2.7
June 21992497.23 14070.49 17-JUN-04:02 2.12
July 0.00 0.00 01-JUL-00:10 19.45
August 15459986.70 13198.02 18-AUG-05:02 7.30
September 0.320100E+09 15077.21 19-SEP-04:01 2.20
October 0.124167E+10 16739.36 10-OCT-03:11 -4.3
November 0.513253E+10 18111.04 26-NOV-18:42 -13.9
December 0.109770E+11 18497.93 31-DEC-03:41 -24.9
         
Annual Sum or Average 0.478831E+11      
Minimum of Months 0.00 0.00   -24.9
Maximum of Months 0.152191E+11 18996.18   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.920962E+10 19717.39 09-JAN-04:01 -27.2
February 0.432887E+10 19482.66 05-FEB-06:52 -20.0
March 0.261626E+10 19434.94 06-MAR-05:01 -18.4
April 0.627936E+09 17005.94 29-APR-03:02 -6.9
May 0.571066E+09 17550.37 08-MAY-03:01 -2.7
June 11853648.70 15189.89 17-JUN-04:02 2.12
July 0.00 0.00 01-JUL-00:10 19.45
August 8391072.61 9762.80 18-AUG-05:02 7.30
September 0.160061E+09 16212.17 19-SEP-04:01 2.20
October 0.631875E+09 18097.84 10-OCT-03:11 -4.3
November 0.290580E+10 19350.63 26-NOV-18:42 -13.9
December 0.659684E+10 19953.91 31-DEC-03:41 -24.9
         
Annual Sum or Average 0.276686E+11      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.920962E+10 19953.91   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.106632E+11 25650.26 09-JAN-04:01 -27.2
February 0.463241E+10 25407.39 05-FEB-06:52 -20.0
March 0.323022E+10 25284.05 06-MAR-05:01 -18.4
April 0.969029E+09 22169.00 29-APR-03:02 -6.9
May 0.964722E+09 23040.31 08-MAY-03:01 -2.7
June 36856164.44 19889.78 17-JUN-04:02 2.12
July 0.00 0.00 01-JUL-00:10 19.45
August 20153161.82 15066.42 18-AUG-05:02 7.30
September 0.200556E+09 20977.16 19-SEP-04:01 2.20
October 0.659536E+09 23603.57 10-OCT-03:11 -4.3
November 0.309382E+10 25104.82 27-NOV-04:01 -15.8
December 0.728679E+10 25935.30 31-DEC-03:41 -24.9
         
Annual Sum or Average 0.317572E+11      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.106632E+11 25935.30   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.852739E+10 22214.46 09-JAN-04:01 -27.2
February 0.354706E+10 21616.71 05-FEB-08:12 -20.2
March 0.214604E+10 21683.62 06-MAR-05:01 -18.4
April 0.464646E+09 18032.92 29-APR-04:01 -7.8
May 0.439470E+09 19818.23 08-MAY-03:01 -2.7
June 14742318.89 10187.12 17-JUN-04:02 2.12
July 0.00 0.00 01-JUL-00:10 19.45
August 9459312.34 9574.54 18-AUG-05:02 7.30
September 0.116778E+09 18011.85 19-SEP-04:01 2.20
October 0.445764E+09 20150.90 10-OCT-03:11 -4.3
November 0.219463E+10 21626.04 27-NOV-04:01 -15.8
December 0.521703E+10 22161.70 31-DEC-03:41 -24.9
         
Annual Sum or Average 0.231230E+11      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.852739E+10 22214.46   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.219929E+10 12869.87 24-JAN-06:03 8.22
February 0.901693E+09 14023.53 13-FEB-06:01 2.80
March 0.355999E+09 13969.24 09-MAR-06:01 2.30
April 0.139565E+09 12514.28 17-APR-03:02 9.40
May 76571375.79 11289.14 01-MAY-04:02 -0.6
June 91676016.20 9835.52 19-JUN-03:02 13.53
July 0.116219E+09 10707.47 05-JUL-03:02 9.90
August 0.117760E+09 11052.32 23-AUG-03:02 11.20
September 84716979.22 10111.73 20-SEP-04:01 3.30
October 95393863.72 10984.45 30-OCT-03:02 5.82
November 0.211252E+09 14248.76 30-NOV-06:01 1.10
December 0.416540E+09 14976.91 19-DEC-05:01 3.40
         
Annual Sum or Average 0.480667E+10      
Minimum of Months 76571375.79 9835.52   -0.6
Maximum of Months 0.219929E+10 14976.91   13.53



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.522055E+10 14420.89 09-JAN-06:12 -27.2
February 0.291042E+10 10394.59 06-FEB-06:03 0.60
March 0.149631E+10 8273.31 06-MAR-13:30 -0.3
April 0.136226E+09 8065.10 16-APR-17:11 19.80
May 0.393593E+09 8533.81 03-MAY-05:03 0.92
June 61500443.99 7065.50 19-JUN-05:02 11.78
July 71214996.40 8869.62 16-JUL-16:31 33.13
August 58538310.94 9600.87 06-AUG-16:01 35.50
September 79332405.17 8183.59 15-SEP-05:02 12.80
October 0.256128E+09 8708.93 13-OCT-05:02 14.03
November 0.131129E+10 7627.45 12-NOV-13:32 -0.6
December 0.302360E+10 8723.15 26-DEC-06:04 -7.9
         
Annual Sum or Average 0.150187E+11      
Minimum of Months 58538310.94 7065.50   -27.2
Maximum of Months 0.522055E+10 14420.89   35.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.208053E+11 35014.76 11-JAN-05:12 -30.2
February 0.110759E+11 29159.56 04-FEB-05:13 -20.2
March 0.769377E+10 33132.90 06-MAR-05:08 -18.4
April 0.285824E+10 15206.08 29-APR-05:13 -7.6
May 0.215487E+10 22498.21 08-MAY-04:12 -2.4
June 0.368333E+09 17752.95 14-JUN-05:02 7.30
July 0.137864E+09 16908.68 12-JUL-05:03 6.85
August 0.263193E+09 16951.20 03-AUG-05:03 8.12
September 0.104570E+10 17738.60 28-SEP-05:03 8.90
October 0.283722E+10 21033.93 10-OCT-04:13 -5.4
November 0.804937E+10 31305.07 27-NOV-05:09 -15.4
December 0.156245E+11 32169.85 29-DEC-05:22 -25.0
         
Annual Sum or Average 0.729143E+11      
Minimum of Months 0.137864E+09 15206.08   -30.2
Maximum of Months 0.208053E+11 35014.76   8.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 65778145.37 640.39 09-JAN-03:44 -27.2
February 0.00 0.00 01-FEB-00:10 -12.4
March 0.00 0.00 01-MAR-00:10 -3.0
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:05 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 65778145.37      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 65778145.37 640.39   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.563361E+09 662.87 29-JAN-17:50 -21.9
February 0.00 0.00 01-FEB-00:10 -12.4
March 0.00 0.00 01-MAR-00:10 -3.0
April 0.00 0.00 01-APR-00:10 2.68
May 3007558.18 173.25 08-MAY-04:12 -2.4
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 0.566368E+09      
Minimum of Months 0.00 0.00   -21.9
Maximum of Months 0.563361E+09 662.87   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.895974E+09 694.06 29-JAN-17:50 -21.9
February 69885876.91 644.48 05-FEB-18:40 -18.3
March 0.00 0.00 01-MAR-00:10 -3.0
April 2514822.08 778.84 30-APR-23:05 -1.3
May 0.127606E+09 668.29 01-MAY-00:15 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 31059390.17 530.57 17-SEP-07:25 3.60
October 388126.45 462.65 10-OCT-03:40 -4.6
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 0.112743E+10      
Minimum of Months 0.00 0.00   -21.9
Maximum of Months 0.895974E+09 778.84   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.38
February 0.00 0.00 01-FEB-00:10 -12.4
March 0.00 0.00 01-MAR-00:10 -3.0
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:05 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:05 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -12.4
Maximum of Months 0.00 0.00   19.45



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.200626E+11 20994.62 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.181982E+11 20994.62 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.216246E+11 20994.62 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.193152E+11 20994.62 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.208436E+11 20994.62 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.207428E+11 20994.62 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.194159E+11 20994.62 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.216246E+11 20994.62 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.193152E+11 20994.62 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.200626E+11 20994.62 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.198274E+11 20994.62 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.194159E+11 20994.62 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.240449E+12     0.424397E+12    
Minimum of Months 0.181982E+11 20994.62   0.325565E+11 13457.54  
Maximum of Months 0.216246E+11 20994.62   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.180176E+11 18854.65 02-JAN-08:09 0.270551E+11 18128.59 02-JAN-08:09
February 0.163433E+11 18854.65 01-FEB-08:09 0.244881E+11 18128.59 01-FEB-08:09
March 0.194204E+11 18854.65 01-MAR-08:09 0.280558E+11 18128.59 01-MAR-08:09
April 0.173464E+11 18854.65 03-APR-07:10 0.261305E+11 18128.59 03-APR-07:10
May 0.187190E+11 18854.65 01-MAY-07:10 0.275555E+11 18128.59 01-MAY-07:10
June 0.186285E+11 18854.65 01-JUN-07:10 0.270261E+11 18128.59 01-JUN-07:10
July 0.174369E+11 18854.65 03-JUL-07:10 0.266527E+11 18128.59 03-JUL-07:10
August 0.194204E+11 18854.65 01-AUG-07:10 0.280558E+11 18128.59 01-AUG-07:10
September 0.173464E+11 18854.65 01-SEP-07:10 0.261160E+11 18128.59 01-SEP-07:10
October 0.180176E+11 18854.65 02-OCT-07:10 0.270624E+11 18128.59 02-OCT-07:10
November 0.178064E+11 18854.65 01-NOV-07:10 0.264424E+11 18128.59 01-NOV-07:10
December 0.174369E+11 18854.65 01-DEC-08:09 0.266454E+11 18128.59 01-DEC-08:09
             
Annual Sum or Average 0.215940E+12     0.321286E+12    
Minimum of Months 0.163433E+11 18854.65   0.244881E+11 18128.59  
Maximum of Months 0.194204E+11 18854.65   0.280558E+11 18128.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.180176E+11 18854.65 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.163433E+11 18854.65 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.194204E+11 18854.65 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.173464E+11 18854.65 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.187190E+11 18854.65 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.186285E+11 18854.65 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.174369E+11 18854.65 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.194204E+11 18854.65 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.173464E+11 18854.65 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.180176E+11 18854.65 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.178064E+11 18854.65 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.174369E+11 18854.65 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.215940E+12     0.321285E+12    
Minimum of Months 0.163433E+11 18854.65   0.244880E+11 18128.52  
Maximum of Months 0.194204E+11 18854.65   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.180176E+11 18854.65 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.163433E+11 18854.65 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.194204E+11 18854.65 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.173464E+11 18854.65 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.187190E+11 18854.65 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.186285E+11 18854.65 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.174369E+11 18854.65 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.194204E+11 18854.65 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.173464E+11 18854.65 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.180176E+11 18854.65 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.178064E+11 18854.65 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.174369E+11 18854.65 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.215940E+12     0.321285E+12    
Minimum of Months 0.163433E+11 18854.65   0.244880E+11 18128.52  
Maximum of Months 0.194204E+11 18854.65   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.174291E+10 2367.39 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.146587E+10 2130.26 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.167143E+10 2276.96 17-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.145175E+10 1870.19 14-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.153397E+10 1667.18 03-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.150617E+10 1454.29 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.142879E+10 1454.29 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.159751E+10 1454.29 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.147368E+10 1903.66 11-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.159298E+10 2367.39 30-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.167149E+10 2367.39 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.169739E+10 2367.39 01-DEC-16:40 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.188339E+11     0.403423E+11    
Minimum of Months 0.142879E+10 1454.29   0.307485E+10 2276.32  
Maximum of Months 0.174291E+10 2367.39   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110380E+10 1525.64 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.936931E+09 1325.94 01-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.107152E+10 1467.36 17-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.934366E+09 1168.51 14-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.990416E+09 937.20 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.975320E+09 937.20 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.922519E+09 937.20 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.103231E+10 937.20 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.948439E+09 1113.40 13-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.101533E+10 1525.64 30-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.106365E+10 1525.64 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.107574E+10 1525.64 01-DEC-16:40 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.120704E+11     0.259981E+11    
Minimum of Months 0.922519E+09 937.20   0.198155E+10 1466.95  
Maximum of Months 0.110380E+10 1525.64   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.169573E+10 2367.44 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.144019E+10 1935.52 02-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.166019E+10 2277.01 17-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.145334E+10 1867.37 14-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.153879E+10 1678.53 03-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.151417E+10 1454.32 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.143419E+10 1454.32 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.160307E+10 1454.32 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.147153E+10 1866.72 11-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.156703E+10 2367.44 30-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.162683E+10 2367.44 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.164265E+10 2367.44 01-DEC-16:40 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.186477E+11     0.403429E+11    
Minimum of Months 0.143419E+10 1454.32   0.307490E+10 2276.35  
Maximum of Months 0.169573E+10 2367.44   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.111120E+10 1525.64 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.937270E+09 1379.11 02-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.107607E+10 1467.36 17-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.937539E+09 1226.09 14-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.990351E+09 1115.36 03-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.972386E+09 937.20 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.923109E+09 937.20 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.103173E+10 1074.29 17-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.950334E+09 1298.16 11-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.102285E+10 1525.64 30-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.106132E+10 1525.64 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.107549E+10 1525.64 01-DEC-16:40 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.120896E+11     0.259979E+11    
Minimum of Months 0.923109E+09 937.20   0.198154E+10 1466.94  
Maximum of Months 0.111120E+10 1525.64   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.174560E+10 2367.39 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.146807E+10 2138.92 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.167265E+10 2279.69 17-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.145247E+10 1885.11 14-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.153433E+10 1687.96 03-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.150653E+10 1454.29 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.142906E+10 1454.29 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.159787E+10 1454.29 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.147463E+10 1917.27 11-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.159484E+10 2367.39 30-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.167452E+10 2367.39 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.170163E+10 2367.39 01-DEC-16:40 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.188522E+11     0.403423E+11    
Minimum of Months 0.142906E+10 1454.29   0.307485E+10 2276.32  
Maximum of Months 0.174560E+10 2367.39   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110432E+10 1525.64 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.937324E+09 1330.59 01-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.107181E+10 1467.80 17-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.934523E+09 1172.96 14-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.990563E+09 937.20 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.975505E+09 937.20 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.922648E+09 937.20 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.103252E+10 937.20 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.948667E+09 1119.23 13-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.101588E+10 1525.64 30-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.106419E+10 1525.64 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.107649E+10 1525.64 01-DEC-16:40 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.120744E+11     0.259981E+11    
Minimum of Months 0.922648E+09 937.20   0.198155E+10 1466.95  
Maximum of Months 0.110432E+10 1525.64   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.169686E+10 2367.44 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.144112E+10 1950.52 02-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.166122E+10 2279.74 17-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.145403E+10 1882.39 14-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.153939E+10 1698.88 03-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.151482E+10 1454.32 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.143465E+10 1454.32 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.160378E+10 1593.65 17-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.147210E+10 1881.74 11-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.156814E+10 2367.44 30-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.162821E+10 2367.44 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.164406E+10 2367.44 01-DEC-16:40 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.186584E+11     0.403429E+11    
Minimum of Months 0.143465E+10 1454.32   0.307490E+10 2276.35  
Maximum of Months 0.169686E+10 2367.44   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.111163E+10 1525.64 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.937696E+09 1380.86 02-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.107625E+10 1467.80 17-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.937740E+09 1228.37 14-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.990470E+09 1118.46 03-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.972570E+09 937.20 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.923209E+09 937.20 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.103194E+10 1077.70 17-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.950707E+09 1299.84 11-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.102344E+10 1525.64 30-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.106194E+10 1525.64 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.107617E+10 1525.64 01-DEC-16:40 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.120938E+11     0.259979E+11    
Minimum of Months 0.923209E+09 937.20   0.198154E+10 1466.94  
Maximum of Months 0.111163E+10 1525.64   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.174560E+10 2367.39 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.146809E+10 2139.17 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.167265E+10 2279.59 17-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.145247E+10 1884.63 14-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.153432E+10 1687.30 03-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.150654E+10 1454.29 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.142906E+10 1454.29 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.159786E+10 1454.29 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.147463E+10 1917.03 11-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.159487E+10 2367.39 30-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.167455E+10 2367.39 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.170168E+10 2367.39 01-DEC-16:40 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.188523E+11     0.403423E+11    
Minimum of Months 0.142906E+10 1454.29   0.307485E+10 2276.32  
Maximum of Months 0.174560E+10 2367.39   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110432E+10 1525.64 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.937335E+09 1330.86 01-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.107175E+10 1467.74 17-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.934523E+09 1172.70 14-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.990567E+09 937.20 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.975509E+09 937.20 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.922651E+09 937.20 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.103252E+10 937.20 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.948670E+09 1119.02 13-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.101589E+10 1525.64 30-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.106442E+10 1525.64 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.107651E+10 1525.64 01-DEC-16:40 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.120747E+11     0.259981E+11    
Minimum of Months 0.922651E+09 937.20   0.198155E+10 1466.95  
Maximum of Months 0.110432E+10 1525.64   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.169687E+10 2367.44 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.144112E+10 1950.66 02-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.166122E+10 2279.64 17-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.145403E+10 1881.91 14-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.153939E+10 1698.22 03-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.151482E+10 1454.32 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.143466E+10 1454.32 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.160376E+10 1592.97 17-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.147210E+10 1881.50 11-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.156826E+10 2367.44 30-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.162822E+10 2367.44 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.164408E+10 2367.44 01-DEC-16:40 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.186585E+11     0.403429E+11    
Minimum of Months 0.143466E+10 1454.32   0.307490E+10 2276.35  
Maximum of Months 0.169687E+10 2367.44   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.111164E+10 1525.64 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.937705E+09 1380.84 02-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.107625E+10 1467.74 17-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.937751E+09 1228.07 14-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.990471E+09 1118.06 03-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.972574E+09 937.20 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.923211E+09 937.20 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.103194E+10 1077.28 17-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.950710E+09 1299.68 11-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.102346E+10 1525.64 30-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.106197E+10 1525.64 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.107619E+10 1525.64 01-DEC-16:40 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.120939E+11     0.259979E+11    
Minimum of Months 0.923211E+09 937.20   0.198154E+10 1466.94  
Maximum of Months 0.111164E+10 1525.64   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.497722E+09 520.85 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.451470E+09 520.85 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.536472E+09 520.85 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.479179E+09 520.85 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.517097E+09 520.85 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.514597E+09 520.85 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.481680E+09 520.85 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.536472E+09 520.85 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.479179E+09 520.85 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.497722E+09 520.85 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.491888E+09 520.85 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.481680E+09 520.85 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.596516E+10     0.153881E+12    
Minimum of Months 0.451470E+09 520.85   0.505780E+10 1948.61  
Maximum of Months 0.536472E+09 520.85   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.497722E+09 520.85 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.451470E+09 520.85 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.536472E+09 520.85 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.479179E+09 520.85 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.517097E+09 520.85 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.514597E+09 520.85 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.481680E+09 520.85 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.536472E+09 520.85 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.479179E+09 520.85 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.497722E+09 520.85 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.491888E+09 520.85 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.481680E+09 520.85 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.596516E+10     0.153881E+12    
Minimum of Months 0.451470E+09 520.85   0.505780E+10 1948.61  
Maximum of Months 0.536472E+09 520.85   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.497722E+09 520.85 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.451470E+09 520.85 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.536472E+09 520.85 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.479179E+09 520.85 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.517097E+09 520.85 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.514597E+09 520.85 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.481680E+09 520.85 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.536472E+09 520.85 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.479179E+09 520.85 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.497722E+09 520.85 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.491888E+09 520.85 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.481680E+09 520.85 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.596516E+10     0.153881E+12    
Minimum of Months 0.451470E+09 520.85   0.505780E+10 1948.61  
Maximum of Months 0.536472E+09 520.85   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.565679E+10 5919.59 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.513113E+10 5919.59 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.609720E+10 5919.59 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.544605E+10 5919.59 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.587700E+10 5919.59 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.584858E+10 5919.59 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.547447E+10 5919.59 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.609720E+10 5919.59 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.544605E+10 5919.59 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.565679E+10 5919.59 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.559049E+10 5919.59 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.547447E+10 5919.59 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.677962E+11     0.749486E+13    
Minimum of Months 0.513113E+10 5919.59   0.246344E+12 94908.13  
Maximum of Months 0.609720E+10 5919.59   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.200626E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.181982E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.216246E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.193152E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.208436E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.207428E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.194159E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.216246E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.193152E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.200626E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.198274E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.194159E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.240449E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.181982E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.216246E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.180176E+11 0.270551E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.163433E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.194204E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.173464E+11 0.261305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.187190E+11 0.275555E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.186285E+11 0.270261E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.174369E+11 0.266527E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.194204E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.173464E+11 0.261160E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.180176E+11 0.270624E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.178064E+11 0.264424E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.174369E+11 0.266454E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.215940E+12 0.321286E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.163433E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.194204E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.180176E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.173464E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.187190E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.186285E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.174369E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.173464E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.180176E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.178064E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.174369E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.215940E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.180176E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.173464E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.187190E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.186285E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.174369E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.173464E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.180176E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.178064E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.174369E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.215940E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.163433E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.194204E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.174291E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.153900E+10
February 0.136985E+10 0.146587E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.123247E+10
March 0.163685E+10 0.167143E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.112437E+10
April 0.145243E+10 0.145175E+10 0.328108E+10 0.00 0.00 0.00 0.00 0.00 0.817039E+09
May 0.157338E+10 0.153397E+10 0.346000E+10 0.00 0.00 0.00 0.00 1862219.08 0.800693E+09
June 0.156900E+10 0.150617E+10 0.339353E+10 0.00 0.00 0.00 0.00 9446304.45 0.395919E+09
July 0.145680E+10 0.142879E+10 0.334664E+10 0.00 0.00 0.00 0.00 33091435.56 0.258816E+09
August 0.163685E+10 0.159751E+10 0.352283E+10 0.00 0.00 0.00 0.00 27483426.73 0.284711E+09
September 0.145243E+10 0.147368E+10 0.327926E+10 0.00 0.00 0.00 0.00 18254302.96 0.527194E+09
October 0.150991E+10 0.159298E+10 0.339809E+10 0.00 0.00 0.00 0.00 109487.54 0.795643E+09
November 0.149516E+10 0.167149E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.112722E+10
December 0.145680E+10 0.169739E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.143156E+10
                   
Annual Sum or Average 0.181194E+11 0.188339E+11 0.403423E+11 0.00 0.00 0.00 0.00 90247176.32 0.103346E+11
Minimum of Months 0.136985E+10 0.142879E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.258816E+09
Maximum of Months 0.163685E+10 0.174291E+10 0.352283E+10 0.00 0.00 0.00 0.00 33091435.56 0.153900E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.110380E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.102340E+10
February 0.882782E+09 0.936931E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.820191E+09
March 0.105485E+10 0.107152E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.738782E+09
April 0.936002E+09 0.934366E+09 0.211446E+10 0.00 0.00 0.00 0.00 0.00 0.531741E+09
May 0.101394E+10 0.990416E+09 0.222976E+10 0.00 0.00 0.00 0.00 1393951.39 0.522185E+09
June 0.101113E+10 0.975320E+09 0.218692E+10 0.00 0.00 0.00 0.00 6718324.70 0.256089E+09
July 0.938820E+09 0.922519E+09 0.215670E+10 0.00 0.00 0.00 0.00 23443329.88 0.161622E+09
August 0.105485E+10 0.103231E+10 0.227025E+10 0.00 0.00 0.00 0.00 19180440.38 0.173177E+09
September 0.936002E+09 0.948439E+09 0.211328E+10 0.00 0.00 0.00 0.00 12692114.81 0.346369E+09
October 0.973041E+09 0.101533E+10 0.218986E+10 0.00 0.00 0.00 0.00 106231.29 0.522424E+09
November 0.963541E+09 0.106365E+10 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.732419E+09
December 0.938820E+09 0.107574E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.934372E+09
                   
Annual Sum or Average 0.116768E+11 0.120704E+11 0.259981E+11 0.00 0.00 0.00 0.00 63534392.44 0.676278E+10
Minimum of Months 0.882782E+09 0.922519E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.161622E+09
Maximum of Months 0.105485E+10 0.110380E+10 0.227025E+10 0.00 0.00 0.00 0.00 23443329.88 0.102340E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.169573E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.154822E+10
February 0.136988E+10 0.144019E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.126346E+10
March 0.163688E+10 0.166019E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.112896E+10
April 0.145246E+10 0.145334E+10 0.328113E+10 0.00 0.00 0.00 0.00 0.00 0.811174E+09
May 0.157341E+10 0.153879E+10 0.346006E+10 0.00 0.00 0.00 0.00 1894239.02 0.784367E+09
June 0.156904E+10 0.151417E+10 0.339359E+10 0.00 0.00 0.00 0.00 9585417.22 0.386917E+09
July 0.145684E+10 0.143419E+10 0.334669E+10 0.00 0.00 0.00 0.00 32277700.27 0.251090E+09
August 0.163688E+10 0.160307E+10 0.352288E+10 0.00 0.00 0.00 0.00 27015640.32 0.279335E+09
September 0.145246E+10 0.147153E+10 0.327931E+10 0.00 0.00 0.00 0.00 15747337.83 0.533820E+09
October 0.150994E+10 0.156703E+10 0.339814E+10 0.00 0.00 0.00 0.00 104084.84 0.812795E+09
November 0.149520E+10 0.162683E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.112886E+10
December 0.145684E+10 0.164265E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.143286E+10
                   
Annual Sum or Average 0.181198E+11 0.186477E+11 0.403429E+11 0.00 0.00 0.00 0.00 86624419.50 0.103619E+11
Minimum of Months 0.136988E+10 0.143419E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.251090E+09
Maximum of Months 0.163688E+10 0.169573E+10 0.352288E+10 0.00 0.00 0.00 0.00 32277700.27 0.154822E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.111120E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.105395E+10
February 0.882782E+09 0.937270E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.876418E+09
March 0.105485E+10 0.107607E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.801065E+09
April 0.936002E+09 0.937539E+09 0.211444E+10 0.00 0.00 0.00 0.00 0.00 0.603266E+09
May 0.101394E+10 0.990351E+09 0.222974E+10 0.00 0.00 0.00 0.00 1224856.78 0.563421E+09
June 0.101113E+10 0.972386E+09 0.218691E+10 0.00 0.00 0.00 0.00 6060798.71 0.284133E+09
July 0.938820E+09 0.923109E+09 0.215669E+10 0.00 0.00 0.00 0.00 20341913.37 0.192864E+09
August 0.105485E+10 0.103173E+10 0.227023E+10 0.00 0.00 0.00 0.00 17377724.52 0.210849E+09
September 0.936002E+09 0.950334E+09 0.211327E+10 0.00 0.00 0.00 0.00 12203675.18 0.368332E+09
October 0.973041E+09 0.102285E+10 0.218984E+10 0.00 0.00 0.00 0.00 78043.58 0.569464E+09
November 0.963541E+09 0.106132E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.808360E+09
December 0.938820E+09 0.107549E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.103608E+10
                   
Annual Sum or Average 0.116768E+11 0.120896E+11 0.259979E+11 0.00 0.00 0.00 0.00 57287012.14 0.736819E+10
Minimum of Months 0.882782E+09 0.923109E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.192864E+09
Maximum of Months 0.105485E+10 0.111120E+10 0.227023E+10 0.00 0.00 0.00 0.00 20341913.37 0.105395E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.174560E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.328485E+10
February 0.136985E+10 0.146807E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.252416E+10
March 0.163685E+10 0.167265E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.234215E+10
April 0.145243E+10 0.145247E+10 0.328108E+10 0.00 0.00 0.00 0.00 0.00 0.168117E+10
May 0.157338E+10 0.153433E+10 0.346000E+10 0.00 0.00 0.00 0.00 4140923.43 0.170647E+10
June 0.156900E+10 0.150653E+10 0.339353E+10 0.00 0.00 0.00 0.00 22193700.66 0.881057E+09
July 0.145680E+10 0.142906E+10 0.334664E+10 0.00 0.00 0.00 0.00 78657649.30 0.593988E+09
August 0.163685E+10 0.159787E+10 0.352283E+10 0.00 0.00 0.00 0.00 64109500.13 0.647294E+09
September 0.145243E+10 0.147463E+10 0.327926E+10 0.00 0.00 0.00 0.00 42953648.19 0.112759E+10
October 0.150991E+10 0.159484E+10 0.339809E+10 0.00 0.00 0.00 0.00 2068727.57 0.160258E+10
November 0.149516E+10 0.167452E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.227687E+10
December 0.145680E+10 0.170163E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.287598E+10
                   
Annual Sum or Average 0.181194E+11 0.188522E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.214124E+09 0.215441E+11
Minimum of Months 0.136985E+10 0.142906E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.593988E+09
Maximum of Months 0.163685E+10 0.174560E+10 0.352283E+10 0.00 0.00 0.00 0.00 78657649.30 0.328485E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.110432E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.221153E+10
February 0.649041E+09 0.937324E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.172304E+10
March 0.773965E+09 0.107181E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.159154E+10
April 0.688021E+09 0.934523E+09 0.211446E+10 0.00 0.00 0.00 0.00 0.00 0.115481E+10
May 0.744847E+09 0.990563E+09 0.222976E+10 0.00 0.00 0.00 0.00 3043120.60 0.113551E+10
June 0.742030E+09 0.975505E+09 0.218692E+10 0.00 0.00 0.00 0.00 15210191.91 0.590359E+09
July 0.690839E+09 0.922648E+09 0.215670E+10 0.00 0.00 0.00 0.00 51859719.12 0.402535E+09
August 0.773965E+09 0.103252E+10 0.227025E+10 0.00 0.00 0.00 0.00 42925100.46 0.431475E+09
September 0.688021E+09 0.948667E+09 0.211328E+10 0.00 0.00 0.00 0.00 28594114.95 0.762729E+09
October 0.715730E+09 0.101588E+10 0.218986E+10 0.00 0.00 0.00 0.00 732055.87 0.109553E+10
November 0.708685E+09 0.106419E+10 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.152934E+10
December 0.690839E+09 0.107649E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.193343E+10
                   
Annual Sum or Average 0.858171E+10 0.120744E+11 0.259981E+11 0.00 0.00 0.00 0.00 0.142364E+09 0.145618E+11
Minimum of Months 0.649041E+09 0.922648E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.402535E+09
Maximum of Months 0.773965E+09 0.110432E+10 0.227025E+10 0.00 0.00 0.00 0.00 51859719.12 0.221153E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.169686E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.344980E+10
February 0.136988E+10 0.144112E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.278248E+10
March 0.163688E+10 0.166122E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.250202E+10
April 0.145246E+10 0.145403E+10 0.328113E+10 0.00 0.00 0.00 0.00 0.00 0.179425E+10
May 0.157341E+10 0.153939E+10 0.346006E+10 0.00 0.00 0.00 0.00 4071243.12 0.174106E+10
June 0.156904E+10 0.151482E+10 0.339359E+10 0.00 0.00 0.00 0.00 21803794.15 0.879139E+09
July 0.145684E+10 0.143465E+10 0.334669E+10 0.00 0.00 0.00 0.00 73171464.57 0.601758E+09
August 0.163688E+10 0.160378E+10 0.352288E+10 0.00 0.00 0.00 0.00 61689625.27 0.669528E+09
September 0.145246E+10 0.147210E+10 0.327931E+10 0.00 0.00 0.00 0.00 34922487.81 0.120524E+10
October 0.150994E+10 0.156814E+10 0.339814E+10 0.00 0.00 0.00 0.00 154752.03 0.180145E+10
November 0.149520E+10 0.162821E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.245713E+10
December 0.145684E+10 0.164406E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.306429E+10
                   
Annual Sum or Average 0.181198E+11 0.186584E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.195813E+09 0.229481E+11
Minimum of Months 0.136988E+10 0.143465E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.601758E+09
Maximum of Months 0.163688E+10 0.169686E+10 0.352288E+10 0.00 0.00 0.00 0.00 73171464.57 0.344980E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.111163E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.223373E+10
February 0.882782E+09 0.937696E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.175715E+10
March 0.105485E+10 0.107625E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.161747E+10
April 0.936002E+09 0.937740E+09 0.211444E+10 0.00 0.00 0.00 0.00 0.00 0.119167E+10
May 0.101394E+10 0.990470E+09 0.222974E+10 0.00 0.00 0.00 0.00 2814552.95 0.119580E+10
June 0.101113E+10 0.972570E+09 0.218691E+10 0.00 0.00 0.00 0.00 14248041.73 0.610353E+09
July 0.938820E+09 0.923209E+09 0.215669E+10 0.00 0.00 0.00 0.00 51075701.59 0.428529E+09
August 0.105485E+10 0.103194E+10 0.227023E+10 0.00 0.00 0.00 0.00 42163258.29 0.449173E+09
September 0.936002E+09 0.950707E+09 0.211327E+10 0.00 0.00 0.00 0.00 29565124.08 0.775092E+09
October 0.973041E+09 0.102344E+10 0.218984E+10 0.00 0.00 0.00 0.00 686327.39 0.111569E+10
November 0.963541E+09 0.106194E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.156441E+10
December 0.938820E+09 0.107617E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.196809E+10
                   
Annual Sum or Average 0.116768E+11 0.120938E+11 0.259979E+11 0.00 0.00 0.00 0.00 0.140553E+09 0.149072E+11
Minimum of Months 0.882782E+09 0.923209E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.428529E+09
Maximum of Months 0.105485E+10 0.111163E+10 0.227023E+10 0.00 0.00 0.00 0.00 51075701.59 0.223373E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.174560E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.396069E+10
February 0.136985E+10 0.146809E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.292819E+10
March 0.163685E+10 0.167265E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.273296E+10
April 0.145243E+10 0.145247E+10 0.328108E+10 0.00 0.00 0.00 0.00 0.00 0.190044E+10
May 0.157338E+10 0.153432E+10 0.346000E+10 0.00 0.00 0.00 0.00 5134859.16 0.197595E+10
June 0.156900E+10 0.150654E+10 0.339353E+10 0.00 0.00 0.00 0.00 27006209.05 0.104818E+10
July 0.145680E+10 0.142906E+10 0.334664E+10 0.00 0.00 0.00 0.00 97911685.83 0.712220E+09
August 0.163685E+10 0.159786E+10 0.352283E+10 0.00 0.00 0.00 0.00 77775112.42 0.767145E+09
September 0.145243E+10 0.147463E+10 0.327926E+10 0.00 0.00 0.00 0.00 54576293.87 0.129095E+10
October 0.150991E+10 0.159487E+10 0.339809E+10 0.00 0.00 0.00 0.00 6810949.41 0.175291E+10
November 0.149516E+10 0.167455E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.260751E+10
December 0.145680E+10 0.170168E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.343875E+10
                   
Annual Sum or Average 0.181194E+11 0.188523E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.269215E+09 0.251159E+11
Minimum of Months 0.136985E+10 0.142906E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.712220E+09
Maximum of Months 0.163685E+10 0.174560E+10 0.352283E+10 0.00 0.00 0.00 0.00 97911685.83 0.396069E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.110432E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.265991E+10
February 0.882782E+09 0.937335E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.199311E+10
March 0.105485E+10 0.107175E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.186432E+10
April 0.936002E+09 0.934523E+09 0.211446E+10 0.00 0.00 0.00 0.00 0.00 0.133018E+10
May 0.101394E+10 0.990567E+09 0.222976E+10 0.00 0.00 0.00 0.00 3489844.61 0.133698E+10
June 0.101113E+10 0.975509E+09 0.218692E+10 0.00 0.00 0.00 0.00 17764221.02 0.720440E+09
July 0.938820E+09 0.922651E+09 0.215670E+10 0.00 0.00 0.00 0.00 60905035.59 0.497525E+09
August 0.105485E+10 0.103252E+10 0.227025E+10 0.00 0.00 0.00 0.00 50665395.88 0.528423E+09
September 0.936002E+09 0.948670E+09 0.211328E+10 0.00 0.00 0.00 0.00 32855774.14 0.900596E+09
October 0.973041E+09 0.101589E+10 0.218986E+10 0.00 0.00 0.00 0.00 1770321.13 0.122246E+10
November 0.963541E+09 0.106442E+10 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.175729E+10
December 0.938820E+09 0.107651E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.230356E+10
                   
Annual Sum or Average 0.116768E+11 0.120747E+11 0.259981E+11 0.00 0.00 0.00 0.00 0.167451E+09 0.171148E+11
Minimum of Months 0.882782E+09 0.922651E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.497525E+09
Maximum of Months 0.105485E+10 0.110432E+10 0.227025E+10 0.00 0.00 0.00 0.00 60905035.59 0.265991E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.169687E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.407933E+10
February 0.136988E+10 0.144112E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.319385E+10
March 0.163688E+10 0.166122E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.292218E+10
April 0.145246E+10 0.145403E+10 0.328113E+10 0.00 0.00 0.00 0.00 0.00 0.205864E+10
May 0.157341E+10 0.153939E+10 0.346006E+10 0.00 0.00 0.00 0.00 4843004.36 0.203909E+10
June 0.156904E+10 0.151482E+10 0.339359E+10 0.00 0.00 0.00 0.00 25963442.62 0.105968E+10
July 0.145684E+10 0.143466E+10 0.334669E+10 0.00 0.00 0.00 0.00 88678024.88 0.732740E+09
August 0.163688E+10 0.160376E+10 0.352288E+10 0.00 0.00 0.00 0.00 74270583.60 0.811253E+09
September 0.145246E+10 0.147210E+10 0.327931E+10 0.00 0.00 0.00 0.00 41787211.61 0.141595E+10
October 0.150994E+10 0.156826E+10 0.339814E+10 0.00 0.00 0.00 0.00 221301.19 0.202884E+10
November 0.149520E+10 0.162822E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.279442E+10
December 0.145684E+10 0.164408E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.357241E+10
                   
Annual Sum or Average 0.181198E+11 0.186585E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.235764E+09 0.267084E+11
Minimum of Months 0.136988E+10 0.143466E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.732740E+09
Maximum of Months 0.163688E+10 0.169687E+10 0.352288E+10 0.00 0.00 0.00 0.00 88678024.88 0.407933E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.111164E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.267763E+10
February 0.882782E+09 0.937705E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.204711E+10
March 0.105485E+10 0.107625E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.190818E+10
April 0.936002E+09 0.937751E+09 0.211444E+10 0.00 0.00 0.00 0.00 0.00 0.138140E+10
May 0.101394E+10 0.990471E+09 0.222974E+10 0.00 0.00 0.00 0.00 3371888.32 0.140866E+10
June 0.101113E+10 0.972574E+09 0.218691E+10 0.00 0.00 0.00 0.00 17211831.06 0.739467E+09
July 0.938820E+09 0.923211E+09 0.215669E+10 0.00 0.00 0.00 0.00 62509058.37 0.523924E+09
August 0.105485E+10 0.103194E+10 0.227023E+10 0.00 0.00 0.00 0.00 51152357.23 0.545221E+09
September 0.936002E+09 0.950710E+09 0.211327E+10 0.00 0.00 0.00 0.00 36116128.94 0.914169E+09
October 0.973041E+09 0.102346E+10 0.218984E+10 0.00 0.00 0.00 0.00 1640111.82 0.126641E+10
November 0.963541E+09 0.106197E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.181186E+10
December 0.938820E+09 0.107619E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.233993E+10
                   
Annual Sum or Average 0.116768E+11 0.120939E+11 0.259979E+11 0.00 0.00 0.00 0.00 0.172001E+09 0.175640E+11
Minimum of Months 0.882782E+09 0.923211E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.523924E+09
Maximum of Months 0.105485E+10 0.111164E+10 0.227023E+10 0.00 0.00 0.00 0.00 62509058.37 0.267763E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.497722E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.451470E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.536472E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.479179E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.517097E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.514597E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.481680E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.536472E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.479179E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.497722E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.491888E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.481680E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.596516E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.451470E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.536472E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.497722E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.451470E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.536472E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.479179E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.517097E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.514597E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.481680E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.536472E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.479179E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.497722E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.491888E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.481680E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.596516E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.451470E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.536472E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.497722E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.451470E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.536472E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.479179E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.517097E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.514597E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.481680E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.536472E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.479179E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.497722E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.491888E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.481680E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.596516E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.451470E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.536472E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.565679E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.513113E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.609720E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.544605E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.587700E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.584858E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.547447E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.609720E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.544605E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.565679E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.559049E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.547447E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.677962E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.513113E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.609720E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.328148E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.263885E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.238236E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.172396E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2914567.06 0.167644E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15285826.70 0.826866E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59053999.16 0.550850E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50000525.51 0.611704E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33544081.19 0.112338E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 71841.01 0.169552E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.240910E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.306560E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.160871E+09 0.219861E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.550850E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59053999.16 0.328148E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.551985E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.438270E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.403224E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.292160E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5459477.99 0.289278E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28154225.78 0.144866E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.109688E+09 0.973734E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 91106338.41 0.108137E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62055606.32 0.195694E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 199086.92 0.285896E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.401557E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.501341E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.296663E+09 0.370978E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.973734E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.109688E+09 0.551985E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.579931E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.450078E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.424787E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.306359E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3363265.96 0.313772E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23056400.20 0.165081E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96676047.94 0.111990E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85797199.33 0.121811E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54696039.93 0.209194E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.286852E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.402922E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.511201E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.263589E+09 0.388398E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.111990E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96676047.94 0.579931E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 20994.62 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 20994.62 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 20994.62 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 20994.62 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 20994.62 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 20994.62 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 20994.62 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 20994.62 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 20994.62 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 20994.62 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 20994.62 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 20994.62 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   20994.62   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   20994.62   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18854.65 02-JAN-08:09 18128.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18854.65 01-FEB-08:09 18128.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18854.65 01-MAR-08:09 18128.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18854.65 03-APR-07:10 18128.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18854.65 01-MAY-07:10 18128.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18854.65 01-JUN-07:10 18128.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18854.65 03-JUL-07:10 18128.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18854.65 01-AUG-07:10 18128.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18854.65 01-SEP-07:10 18128.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18854.65 02-OCT-07:10 18128.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18854.65 01-NOV-07:10 18128.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18854.65 01-DEC-08:09 18128.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18854.65   18128.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18854.65   18128.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18854.65 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18854.65 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18854.65 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18854.65 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18854.65 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18854.65 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18854.65 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18854.65 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18854.65 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18854.65 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18854.65 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18854.65 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18854.65 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18854.65 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18854.65 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18854.65 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18854.65 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18854.65 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18854.65 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18854.65 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18854.65 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18854.65 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18854.65 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18854.65 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18854.65   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2367.39 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2513.50 05-JAN-22:01
February 2010.79 01-FEB-10:09 2130.26 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1587.93 17-FEB-04:00
March 2010.79 01-MAR-10:09 2276.96 17-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1930.03 02-MAR-23:00
April 2010.79 03-APR-09:09 1870.19 14-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1386.85 27-APR-02:00
May 2010.79 01-MAY-09:09 1667.18 03-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 113.38 20-MAY-17:02 2620.39 22-MAY-03:53
June 2010.79 01-JUN-09:09 1454.29 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 127.69 29-JUN-15:00 1112.70 14-JUN-02:00
July 2010.79 03-JUL-09:09 1454.29 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 283.72 30-JUL-12:00 667.65 05-JUL-01:00
August 2010.79 01-AUG-09:09 1454.29 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 333.05 06-AUG-17:52 858.06 23-AUG-03:00
September 2010.79 01-SEP-09:09 1903.66 11-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 416.41 03-SEP-12:52 1479.49 12-SEP-03:00
October 2010.79 02-OCT-09:09 2367.39 30-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 11.99 18-OCT-14:00 1262.75 30-OCT-22:00
November 2010.79 01-NOV-09:09 2367.39 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1506.87 26-NOV-19:51
December 2010.79 01-DEC-10:09 2367.39 01-DEC-16:40 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2346.50 01-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1454.29   2276.32   0.00 0.00 0.00 0.00 0.00   667.65  
Maximum of Months 2010.79   2367.39   2276.32   0.00 0.00 0.00 0.00 416.41   2620.39  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1525.64 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1675.05 05-JAN-22:01
February 1295.83 01-FEB-10:09 1325.94 01-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1038.94 17-FEB-04:00
March 1295.83 01-MAR-10:09 1467.36 17-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1258.87 02-MAR-23:00
April 1295.83 03-APR-09:09 1168.51 14-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 905.25 27-APR-02:00
May 1295.83 01-MAY-09:09 937.20 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 93.27 20-MAY-17:02 1713.52 22-MAY-04:30
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 96.96 24-JUN-17:10 719.97 14-JUN-02:00
July 1295.83 03-JUL-09:09 937.20 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 213.34 30-JUL-12:00 429.41 05-JUL-01:00
August 1295.83 01-AUG-09:09 937.20 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 260.08 06-AUG-17:52 550.00 23-AUG-03:00
September 1295.83 01-SEP-09:09 1113.40 13-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 287.97 03-SEP-12:52 966.31 12-SEP-03:00
October 1295.83 02-OCT-09:09 1525.64 30-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 17.02 15-OCT-14:00 821.76 30-OCT-22:10
November 1295.83 01-NOV-09:09 1525.64 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1003.92 28-NOV-05:58
December 1295.83 01-DEC-10:09 1525.64 01-DEC-16:40 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1513.90 01-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.95   0.00 0.00 0.00 0.00 0.00   429.41  
Maximum of Months 1295.83   1525.64   1466.95   0.00 0.00 0.00 0.00 287.97   1713.52  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2367.44 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2512.57 05-JAN-22:01
February 2010.83 01-FEB-10:09 1935.52 02-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1562.86 17-FEB-04:00
March 2010.83 01-MAR-10:09 2277.01 17-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1956.59 02-MAR-23:00
April 2010.83 03-APR-09:09 1867.37 14-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1368.43 27-APR-02:00
May 2010.83 01-MAY-09:09 1678.53 03-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 121.03 20-MAY-17:02 2530.42 22-MAY-03:53
June 2010.83 01-JUN-09:09 1454.32 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 127.69 29-JUN-15:00 1088.98 14-JUN-02:00
July 2010.83 03-JUL-09:09 1454.32 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 282.36 30-JUL-14:00 652.44 05-JUL-01:00
August 2010.83 01-AUG-09:09 1454.32 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 346.97 06-AUG-17:50 853.96 23-AUG-03:00
September 2010.83 01-SEP-09:09 1866.72 11-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 351.25 03-SEP-12:55 1433.70 12-SEP-03:00
October 2010.83 02-OCT-09:09 2367.44 30-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 11.91 18-OCT-14:10 1279.77 30-OCT-22:00
November 2010.83 01-NOV-09:09 2367.44 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1505.90 28-NOV-05:55
December 2010.83 01-DEC-10:09 2367.44 01-DEC-16:40 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2262.50 01-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1454.32   2276.35   0.00 0.00 0.00 0.00 0.00   652.44  
Maximum of Months 2010.83   2367.44   2276.35   0.00 0.00 0.00 0.00 351.25   2530.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1525.64 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1677.25 05-JAN-22:01
February 1295.83 01-FEB-10:09 1379.11 02-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1127.82 17-FEB-04:00
March 1295.83 01-MAR-10:09 1467.36 17-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1371.68 02-MAR-23:00
April 1295.83 03-APR-09:09 1226.09 14-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1012.39 27-APR-02:00
May 1295.83 01-MAY-09:09 1115.36 03-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 76.05 20-MAY-17:02 1761.69 22-MAY-04:30
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 85.13 29-JUN-15:00 806.18 14-JUN-02:00
July 1295.83 03-JUL-09:09 937.20 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 218.15 30-JUL-12:00 499.42 05-JUL-01:00
August 1295.83 01-AUG-09:09 1074.29 17-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 231.57 06-AUG-17:45 668.18 23-AUG-03:00
September 1295.83 01-SEP-09:09 1298.16 11-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 308.40 03-SEP-12:52 1016.15 12-SEP-03:00
October 1295.83 02-OCT-09:09 1525.64 30-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 7.99 18-OCT-14:00 896.67 30-OCT-22:50
November 1295.83 01-NOV-09:09 1525.64 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1066.98 26-NOV-19:51
December 1295.83 01-DEC-10:09 1525.64 01-DEC-16:40 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1707.89 01-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.94   0.00 0.00 0.00 0.00 0.00   499.42  
Maximum of Months 1295.83   1525.64   1466.94   0.00 0.00 0.00 0.00 308.40   1761.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2367.39 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 5881.77 05-JAN-22:01
February 2010.79 01-FEB-10:09 2138.92 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3236.95 08-FEB-22:02
March 2010.79 01-MAR-10:09 2279.69 17-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4113.67 02-MAR-23:00
April 2010.79 03-APR-09:09 1885.11 14-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2911.46 27-APR-02:00
May 2010.79 01-MAY-09:09 1687.96 03-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 267.86 20-MAY-17:02 5691.66 22-MAY-04:53
June 2010.79 01-JUN-09:09 1454.29 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 295.49 29-JUN-15:00 2341.11 14-JUN-02:00
July 2010.79 03-JUL-09:09 1454.29 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 693.71 30-JUL-12:00 1405.09 05-JUL-01:00
August 2010.79 01-AUG-09:09 1454.29 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 771.82 06-AUG-17:50 1737.03 23-AUG-03:00
September 2010.79 01-SEP-09:09 1917.27 11-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 947.96 03-SEP-13:00 3034.09 12-SEP-03:00
October 2010.79 02-OCT-09:09 2367.39 30-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 229.47 15-OCT-14:10 2578.73 30-OCT-22:00
November 2010.79 01-NOV-09:09 2367.39 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3528.95 28-NOV-05:50
December 2010.79 01-DEC-10:09 2367.39 01-DEC-16:40 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5043.08 01-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1454.29   2276.32   0.00 0.00 0.00 0.00 0.00   1405.09  
Maximum of Months 2010.79   2367.39   2276.32   0.00 0.00 0.00 0.00 947.96   5881.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1525.64 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3920.83 05-JAN-22:01
February 1239.33 01-FEB-08:09 1330.59 01-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2157.37 08-FEB-22:02
March 1239.33 01-MAR-08:09 1467.80 17-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2731.66 02-MAR-23:00
April 1239.33 03-APR-07:10 1172.96 14-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1937.63 27-APR-02:00
May 1239.33 01-MAY-07:10 937.20 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 221.35 20-MAY-17:02 3794.48 22-MAY-05:00
June 1239.33 01-JUN-07:10 937.20 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 217.10 24-JUN-17:10 1524.41 14-JUN-02:00
July 1239.33 03-JUL-07:10 937.20 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 461.88 30-JUL-14:30 934.06 05-JUL-01:00
August 1239.33 01-AUG-07:10 937.20 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 576.01 06-AUG-17:30 1152.79 23-AUG-03:00
September 1239.33 01-SEP-07:10 1119.23 13-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 642.20 03-SEP-12:52 1976.91 12-SEP-03:00
October 1239.33 02-OCT-07:10 1525.64 30-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 107.90 15-OCT-14:10 1718.74 30-OCT-22:00
November 1239.33 01-NOV-07:10 1525.64 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2352.70 28-NOV-05:47
December 1239.33 01-DEC-08:09 1525.64 01-DEC-16:40 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3362.23 01-DEC-05:07
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   937.20   1466.95   0.00 0.00 0.00 0.00 0.00   934.06  
Maximum of Months 1239.33   1525.64   1466.95   0.00 0.00 0.00 0.00 642.20   3920.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2367.44 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 5884.54 05-JAN-22:01
February 2010.83 01-FEB-10:09 1950.52 02-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3375.39 19-FEB-13:00
March 2010.83 01-MAR-10:09 2279.74 17-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4290.66 02-MAR-23:00
April 2010.83 03-APR-09:09 1882.39 14-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2941.61 27-APR-02:00
May 2010.83 01-MAY-09:09 1698.88 03-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 282.14 20-MAY-17:02 5691.72 22-MAY-04:53
June 2010.83 01-JUN-09:09 1454.32 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 295.49 29-JUN-15:00 2315.61 14-JUN-02:00
July 2010.83 03-JUL-09:09 1454.32 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 642.39 30-JUL-12:00 1418.34 05-JUL-01:00
August 2010.83 01-AUG-09:09 1593.65 17-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 767.76 06-AUG-17:30 1782.68 23-AUG-03:00
September 2010.83 01-SEP-09:09 1881.74 11-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 810.14 03-SEP-13:00 3008.07 12-SEP-03:00
October 2010.83 02-OCT-09:09 2367.44 30-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 24.47 18-OCT-15:00 2761.72 30-OCT-22:00
November 2010.83 01-NOV-09:09 2367.44 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3529.15 28-NOV-05:45
December 2010.83 01-DEC-10:09 2367.44 01-DEC-16:40 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5043.23 01-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1454.32   2276.35   0.00 0.00 0.00 0.00 0.00   1418.34  
Maximum of Months 2010.83   2367.44   2276.35   0.00 0.00 0.00 0.00 810.14   5884.54  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1525.64 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3921.89 05-JAN-22:01
February 1295.83 01-FEB-10:09 1380.86 02-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2163.68 17-FEB-05:45
March 1295.83 01-MAR-10:09 1467.80 17-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2824.43 02-MAR-23:00
April 1295.83 03-APR-09:09 1228.37 14-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1965.08 27-APR-02:00
May 1295.83 01-MAY-09:09 1118.46 03-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 195.32 20-MAY-17:02 3794.49 22-MAY-04:57
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 196.99 29-JUN-15:00 1583.37 14-JUN-02:00
July 1295.83 03-JUL-09:09 937.20 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 592.96 30-JUL-11:50 1001.53 05-JUL-01:00
August 1295.83 01-AUG-09:09 1077.70 17-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 568.57 06-AUG-12:10 1199.80 23-AUG-03:00
September 1295.83 01-SEP-09:09 1299.84 11-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 709.21 03-SEP-12:55 1982.08 12-SEP-03:00
October 1295.83 02-OCT-09:09 1525.64 30-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 109.59 15-OCT-12:50 1760.48 30-OCT-22:00
November 1295.83 01-NOV-09:09 1525.64 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2352.65 28-NOV-05:45
December 1295.83 01-DEC-10:09 1525.64 01-DEC-16:40 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3362.21 01-DEC-05:07
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.94   0.00 0.00 0.00 0.00 0.00   1001.53  
Maximum of Months 1295.83   1525.64   1466.94   0.00 0.00 0.00 0.00 709.21   3921.89  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2367.39 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 7293.37 05-JAN-22:01
February 2010.79 01-FEB-10:09 2139.17 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 4018.66 17-FEB-05:50
March 2010.79 01-MAR-10:09 2279.59 17-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4958.09 17-MAR-04:45
April 2010.79 03-APR-09:09 1884.63 14-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3310.80 27-APR-02:00
May 2010.79 01-MAY-09:09 1687.30 03-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 329.00 20-MAY-17:02 7102.37 22-MAY-04:47
June 2010.79 01-JUN-09:09 1454.29 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 361.92 29-JUN-15:00 2686.28 14-JUN-02:00
July 2010.79 03-JUL-09:09 1454.29 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 889.60 30-JUL-12:00 1610.44 05-JUL-01:00
August 2010.79 01-AUG-09:09 1454.29 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 953.01 06-AUG-17:40 1985.93 22-AUG-21:10
September 2010.79 01-SEP-09:09 1917.03 11-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 1192.46 03-SEP-13:00 3302.78 12-SEP-03:00
October 2010.79 02-OCT-09:09 2367.39 30-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 499.02 15-OCT-14:00 3157.47 30-OCT-21:03
November 2010.79 01-NOV-09:09 2367.39 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4315.46 28-NOV-06:00
December 2010.79 01-DEC-10:09 2367.39 01-DEC-16:40 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 6180.41 01-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1454.29   2276.32   0.00 0.00 0.00 0.00 0.00   1610.44  
Maximum of Months 2010.79   2367.39   2276.32   0.00 0.00 0.00 0.00 1192.46   7293.37  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1525.64 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4861.13 05-JAN-22:01
February 1295.83 01-FEB-10:09 1330.86 01-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2679.22 17-FEB-05:47
March 1295.83 01-MAR-10:09 1467.74 17-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 3305.34 17-MAR-04:50
April 1295.83 03-APR-09:09 1172.70 14-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2230.30 27-APR-02:00
May 1295.83 01-MAY-09:09 937.20 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 250.63 20-MAY-17:02 4734.47 22-MAY-04:43
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 241.28 29-JUN-15:00 1839.07 04-JUN-14:00
July 1295.83 03-JUL-09:09 937.20 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 569.92 30-JUL-14:40 1077.62 05-JUL-01:00
August 1295.83 01-AUG-09:09 937.20 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 711.59 06-AUG-17:40 1318.12 22-AUG-24:00
September 1295.83 01-SEP-09:09 1119.02 13-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 801.42 03-SEP-13:00 2178.67 12-SEP-03:00
October 1295.83 02-OCT-09:09 1525.64 30-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 213.76 15-OCT-13:50 2108.47 30-OCT-21:03
November 1295.83 01-NOV-09:09 1525.64 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2948.75 28-NOV-05:53
December 1295.83 01-DEC-10:09 1525.64 01-DEC-16:40 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4198.70 01-DEC-05:07
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.95   0.00 0.00 0.00 0.00 0.00   1077.62  
Maximum of Months 1295.83   1525.64   1466.95   0.00 0.00 0.00 0.00 801.42   4861.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2367.44 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 7295.80 05-JAN-22:01
February 2010.83 01-FEB-10:09 1950.66 02-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 4029.27 08-FEB-22:02
March 2010.83 01-MAR-10:09 2279.64 17-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 5080.16 02-MAR-23:00
April 2010.83 03-APR-09:09 1881.91 14-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3372.02 27-APR-02:00
May 2010.83 01-MAY-09:09 1698.22 03-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 328.46 20-MAY-17:02 7102.30 22-MAY-04:47
June 2010.83 01-JUN-09:09 1454.32 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 361.92 29-JUN-15:00 2661.21 14-JUN-02:00
July 2010.83 03-JUL-09:09 1454.32 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 810.38 30-JUL-12:00 1634.59 05-JUL-01:00
August 2010.83 01-AUG-09:09 1592.97 17-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 949.43 06-AUG-17:40 2049.87 22-AUG-21:10
September 2010.83 01-SEP-09:09 1881.50 11-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 990.91 03-SEP-12:55 3300.23 12-SEP-03:00
October 2010.83 02-OCT-09:09 2367.44 30-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 27.25 18-OCT-14:10 3211.15 30-OCT-21:03
November 2010.83 01-NOV-09:09 2367.44 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4423.25 28-NOV-06:00
December 2010.83 01-DEC-10:09 2367.44 01-DEC-16:40 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 6297.98 01-DEC-05:07
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1454.32   2276.35   0.00 0.00 0.00 0.00 0.00   1634.59  
Maximum of Months 2010.83   2367.44   2276.35   0.00 0.00 0.00 0.00 990.91   7295.80  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1525.64 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4862.36 05-JAN-22:01
February 1295.83 01-FEB-10:09 1380.84 02-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2682.56 08-FEB-22:02
March 1295.83 01-MAR-10:09 1467.74 17-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 3358.91 02-MAR-23:00
April 1295.83 03-APR-09:09 1228.07 14-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2264.76 27-APR-02:00
May 1295.83 01-MAY-09:09 1118.06 03-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 229.80 20-MAY-17:02 4735.00 22-MAY-04:47
June 1295.83 01-JUN-09:09 937.20 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 241.28 29-JUN-15:00 1826.27 14-JUN-02:00
July 1295.83 03-JUL-09:09 937.20 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 739.33 30-JUL-12:00 1167.39 05-JUL-01:00
August 1295.83 01-AUG-09:09 1077.28 17-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 684.43 06-AUG-12:00 1378.72 22-AUG-24:00
September 1295.83 01-SEP-09:09 1299.68 11-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 903.32 03-SEP-13:00 2201.44 12-SEP-03:00
October 1295.83 02-OCT-09:09 1525.64 30-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 201.92 15-OCT-12:31 2122.88 30-OCT-21:03
November 1295.83 01-NOV-09:09 1525.64 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2948.87 28-NOV-05:58
December 1295.83 01-DEC-10:09 1525.64 01-DEC-16:40 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4198.67 01-DEC-05:09
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   937.20   1466.94   0.00 0.00 0.00 0.00 0.00   1167.39  
Maximum of Months 1295.83   1525.64   1466.94   0.00 0.00 0.00 0.00 903.32   4862.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 520.85 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 520.85 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 520.85 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 520.85 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 520.85 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 520.85 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 520.85 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 520.85 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 520.85 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 520.85 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 520.85 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 520.85 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   520.85   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   520.85   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 520.85 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 520.85 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 520.85 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 520.85 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 520.85 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 520.85 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 520.85 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 520.85 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 520.85 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 520.85 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 520.85 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 520.85 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   520.85   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   520.85   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 520.85 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 520.85 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 520.85 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 520.85 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 520.85 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 520.85 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 520.85 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 520.85 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 520.85 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 520.85 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 520.85 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 520.85 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   520.85   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   520.85   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 5919.59 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 5919.59 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 5919.59 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 5919.59 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 5919.59 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 5919.59 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 5919.59 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 5919.59 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 5919.59 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 5919.59 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 5919.59 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 5919.59 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   5919.59   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   5919.59   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 5185.15 05-JAN-22:01
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3460.67 17-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4103.31 02-MAR-23:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2930.34 27-APR-02:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 224.66 20-MAY-17:02 5818.28 22-MAY-03:53
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 232.19 29-JUN-15:00 2327.57 14-JUN-02:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 583.04 30-JUL-11:55 1367.03 05-JUL-01:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 669.70 06-AUG-17:58 1784.74 23-AUG-03:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 800.18 03-SEP-13:00 3183.06 12-SEP-03:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.16 18-OCT-15:00 2692.94 30-OCT-23:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3279.06 26-NOV-19:51
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5128.39 01-DEC-05:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1367.03  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 800.18   5818.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 9173.95 05-JAN-22:01
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 5846.99 17-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 7142.53 02-MAR-23:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 5092.52 27-APR-02:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 423.50 20-MAY-17:02 10050.29 22-MAY-04:01
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 415.58 29-JUN-15:00 4048.43 14-JUN-02:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1109.05 30-JUL-12:00 2373.36 05-JUL-01:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1246.28 06-AUG-17:52 3066.91 23-AUG-03:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1427.84 03-SEP-13:00 5526.77 12-SEP-03:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.95 18-OCT-14:00 4585.81 30-OCT-22:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 5428.91 26-NOV-20:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 8282.87 01-DEC-05:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   2373.36  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1427.84   10050.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 10284.09 05-JAN-22:01
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 5780.34 08-FEB-22:02
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 7747.03 02-MAR-23:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 5315.40 27-APR-02:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 385.09 20-MAY-17:02 10122.59 22-MAY-04:10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 430.27 29-JUN-15:00 4182.55 14-JUN-02:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1039.02 30-JUL-11:55 2520.59 05-JUL-01:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1146.84 06-AUG-18:00 3167.29 22-AUG-21:03
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1341.96 03-SEP-13:00 5422.04 12-SEP-03:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 4845.83 30-OCT-21:03
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 5761.72 28-NOV-06:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 8341.77 01-DEC-05:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   2520.59  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1341.96   10284.09  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 109422.06 02-JAN-04:03 0.00 4665.70 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
February 108714.50 27-FEB-04:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
March 109493.07 27-MAR-03:01 0.00 9331.40 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
April 111076.76 24-APR-03:02 0.00 6998.55 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
May 111369.96 30-MAY-03:02 0.00 6998.55 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
June 113748.30 05-JUN-03:02 0.00 6998.55 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
July 114647.14 24-JUL-02:52 0.00 6998.55 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
August 111020.31 28-AUG-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
September 115330.66 25-SEP-03:02 0.00 6998.55 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
October 111018.82 23-OCT-03:02 0.00 5832.13 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
November 113763.15 20-NOV-04:01 0.00 10497.83 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
December 112017.84 11-DEC-04:01 0.00 8164.98 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 108714.50   0.00 4665.70 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 115330.66   0.00 10497.83 121117.90 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 85470.72 02-JAN-05:01 0.00 16760.51 64457.21 0.00 0.00 0.00 0.00 0.00 0.00
February 87271.24 28-FEB-05:01 0.00 16760.51 64457.21 0.00 0.00 0.00 0.00 0.00 0.00
March 87990.47 29-MAR-04:01 0.00 16760.51 64457.21 0.00 0.00 0.00 0.00 0.00 0.00
April 91365.05 10-APR-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
May 94325.69 30-MAY-03:02 0.00 6285.19 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
June 92244.87 05-JUN-03:02 0.00 6285.19 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
July 95202.99 05-JUL-03:02 0.00 6285.19 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
August 91027.10 23-AUG-03:02 0.00 6285.19 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
September 95353.02 11-SEP-03:02 0.00 6285.19 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
October 90648.56 02-OCT-03:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
November 91324.31 06-NOV-04:02 0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
December 88067.31 07-DEC-05:01 0.00 18855.58 72514.36 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 85470.72   0.00 5237.66 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 95353.02   0.00 18855.58 72514.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 22197.39 05-JAN-17:00 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 32974.19 28-FEB-17:00 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
March 72251.87 30-MAR-05:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
April 79501.27 25-APR-05:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
May 82557.55 30-MAY-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
June 82945.55 23-JUN-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
July 84115.05 19-JUL-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
August 86169.38 14-AUG-03:02 0.00 5237.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 84765.63 11-SEP-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
October 77892.21 17-OCT-05:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
November 73286.14 08-NOV-06:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
December 28782.98 07-DEC-16:30 30632.53 37709.30 36257.04 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 22197.39   0.00 5237.66 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 86169.38   30632.53 37709.30 48342.72 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17269.51 13-JAN-17:00 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 25420.93 28-FEB-17:00 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
March 28756.00 23-MAR-15:40 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
April 42101.24 25-APR-16:00 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
May 77318.18 20-MAY-05:02 8061.19 10475.32 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
June 83055.98 21-JUN-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
July 82170.91 19-JUL-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
August 81277.97 10-AUG-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
September 82121.42 05-SEP-03:02 0.00 6285.19 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
October 48080.75 19-OCT-05:03 6448.95 8380.26 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
November 27154.23 03-NOV-16:00 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
December 19521.72 06-DEC-17:00 15316.26 18854.65 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17269.51   0.00 6285.19 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 83055.98   15316.26 18854.65 48342.72 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3099.00 02-JAN-05:01 0.00 2104.45 8093.57 0.00 0.00 0.00 0.00 0.00 54.20
February 3977.28 27-FEB-16:00 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 46.22
March 4409.57 27-MAR-14:40 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 96.41
April 6875.62 07-APR-14:30 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 23.97
May 12818.70 30-MAY-05:03 809.73 1004.05 4046.79 0.00 0.00 0.00 0.00 0.00 78.02
June 12630.23 26-JUN-05:03 809.73 646.38 4046.79 0.00 0.00 0.00 0.00 0.00 72.28
July 12434.53 26-JUL-05:02 1012.16 1069.19 5058.48 0.00 0.00 0.00 0.00 0.00 40.32
August 12913.10 06-AUG-15:41 708.51 565.58 5311.41 0.00 0.00 0.00 0.00 262.48 0.00
September 15722.04 04-SEP-16:01 910.95 727.18 6828.95 0.00 0.00 0.00 0.00 110.70 0.00
October 5758.45 19-OCT-14:30 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 29.32
November 4019.59 24-NOV-14:30 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 166.86
December 3191.03 06-DEC-05:01 0.00 2104.45 8093.57 0.00 0.00 0.00 0.00 0.00 830.41
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3099.00   0.00 565.58 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15722.04   2010.79 2104.45 8093.57 0.00 0.00 0.00 0.00 262.48 830.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3740.98 02-JAN-05:01 0.00 1356.19 5215.81 0.00 0.00 0.00 0.00 0.00 35.76
February 6388.57 27-FEB-10:00 2478.65 1874.40 2933.89 0.00 0.00 0.00 0.00 0.00 103.07
March 8998.90 28-MAR-09:20 2591.66 1874.40 2933.89 0.00 0.00 0.00 0.00 0.00 133.10
April 11271.55 24-APR-08:30 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 35.17
May 11467.98 19-MAY-08:30 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 32.73
June 21345.19 25-JUN-07:52 391.37 312.41 2933.89 0.00 0.00 0.00 0.00 0.00 135.51
July 20922.12 02-JUL-08:32 391.37 312.41 2933.89 0.00 0.00 0.00 0.00 0.00 110.74
August 20982.84 06-AUG-08:22 391.37 312.41 2933.89 0.00 0.00 0.00 0.00 0.00 28.16
September 21612.54 04-SEP-08:42 391.37 312.41 2933.89 0.00 0.00 0.00 0.00 0.00 28.30
October 8583.53 18-OCT-09:20 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 60.01
November 5880.64 06-NOV-09:35 2478.65 1874.40 2933.89 0.00 0.00 0.00 0.00 0.00 54.71
December 3620.85 01-DEC-06:02 1174.10 1525.71 5867.78 0.00 0.00 0.00 0.00 0.00 258.97
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3620.85   0.00 312.41 1466.95 0.00 0.00 0.00 0.00 0.00 28.16
Maximum of Months 21612.54   2591.66 1874.40 5867.78 0.00 0.00 0.00 0.00 0.00 258.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11419.37 19-JAN-13:30 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 231.04
February 25758.13 26-FEB-14:02 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 0.00 440.67
March 18751.34 01-MAR-13:40 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 125.43
April 18544.08 16-APR-12:02 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 0.00 431.36
May 14809.00 19-MAY-13:30 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 33.90 0.00
June 15479.01 25-JUN-15:12 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 0.00 49.18
July 22873.94 16-JUL-15:22 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 118.39 0.00
August 25917.72 06-AUG-13:42 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 225.16 0.00
September 28169.66 04-SEP-15:21 809.75 646.40 6070.27 0.00 0.00 0.00 0.00 83.67 0.00
October 28542.76 15-OCT-12:31 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 0.00 418.95
November 22898.53 12-NOV-13:32 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 0.00 475.85
December 13178.46 12-DEC-12:30 1058.33 1454.32 2023.42 0.00 0.00 0.00 0.00 0.00 177.02
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11419.37   404.87 323.20 2023.42 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 28542.76   2010.83 1454.32 6070.27 0.00 0.00 0.00 0.00 225.16 475.85



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4895.35 02-JAN-05:01 0.00 1356.19 5215.77 0.00 0.00 0.00 0.00 0.00 36.45
February 9917.43 28-FEB-16:40 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 66.32
March 12444.23 28-MAR-16:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 136.13
April 25973.33 16-APR-17:22 0.00 312.41 2933.87 0.00 0.00 0.00 0.00 0.00 151.92
May 25802.33 13-MAY-18:22 0.00 312.41 2933.87 0.00 0.00 0.00 0.00 0.00 124.37
June 25757.82 18-JUN-17:02 0.00 312.41 2933.87 0.00 0.00 0.00 0.00 0.00 15.88
July 27760.02 16-JUL-17:21 0.00 364.48 3422.85 0.00 0.00 0.00 0.00 45.99 0.00
August 27667.00 06-AUG-16:21 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 149.60 0.00
September 28775.52 04-SEP-16:01 587.05 468.62 4400.81 0.00 0.00 0.00 0.00 43.42 0.00
October 17848.21 15-OCT-15:11 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 0.00 170.31
November 9275.45 03-NOV-15:40 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 61.93
December 8501.44 06-DEC-15:30 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 214.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4895.35   0.00 312.41 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 28775.52   1239.33 1356.19 5215.77 0.00 0.00 0.00 0.00 149.60 214.22



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1778.31 13-JAN-17:00 1923.11 2367.39 2276.32 0.00 0.00 0.00 0.00 0.00 364.96
February 2893.83 27-FEB-13:30 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 125.05
March 2808.87 23-MAR-13:30 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 542.74
April 4918.91 07-APR-14:30 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 60.30
May 7053.07 19-MAY-16:00 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 178.84 0.00
June 11399.41 21-JUN-05:03 809.73 646.38 4046.79 0.00 0.00 0.00 0.00 0.00 167.11
July 15058.68 16-JUL-18:31 0.00 807.98 7587.73 0.00 0.00 0.00 0.00 211.30 0.00
August 14214.44 06-AUG-17:21 0.00 565.58 5311.41 0.00 0.00 0.00 0.00 697.79 0.00
September 11882.22 04-SEP-14:11 708.51 565.58 5311.41 0.00 0.00 0.00 0.00 308.33 0.00
October 4186.86 19-OCT-14:40 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 68.97
November 2799.71 03-NOV-13:30 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 186.39
December 1999.14 06-DEC-16:20 1923.11 2192.00 2276.32 0.00 0.00 0.00 0.00 0.00 534.83
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1778.31   0.00 565.58 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15058.68   2010.79 2367.39 7587.73 0.00 0.00 0.00 0.00 697.79 542.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2508.06 13-JAN-06:03 913.19 1186.66 4563.83 0.00 0.00 0.00 0.00 0.00 176.29
February 4578.83 26-FEB-11:52 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 723.93
March 6868.85 28-MAR-10:05 2478.65 1874.40 2933.89 0.00 0.00 0.00 0.00 0.00 214.50
April 10382.86 25-APR-09:00 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 98.65
May 11855.12 19-MAY-08:50 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 74.37
June 20821.35 04-JUN-07:42 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 314.06
July 24537.22 16-JUL-09:11 521.82 416.55 3911.86 0.00 0.00 0.00 0.00 0.00 286.38
August 25100.89 06-AUG-09:21 587.05 468.62 4400.84 0.00 0.00 0.00 0.00 0.00 40.15
September 22391.49 04-SEP-08:52 391.37 312.41 2933.89 0.00 0.00 0.00 0.00 0.00 49.64
October 7088.57 18-OCT-10:10 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 95.83
November 3813.69 03-NOV-13:00 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 134.95
December 2652.07 20-DEC-10:00 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 217.56
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2508.06   326.14 260.35 1466.95 0.00 0.00 0.00 0.00 0.00 40.15
Maximum of Months 25100.89   2478.65 1874.40 4563.83 0.00 0.00 0.00 0.00 0.00 723.93



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10904.24 19-JAN-14:00 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 501.93
February 28055.29 26-FEB-13:12 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 0.00 1241.22
March 19948.17 01-MAR-13:50 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 287.03
April 17735.91 16-APR-13:52 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 0.00 802.38
May 15124.33 19-MAY-13:40 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 85.14 0.00
June 14907.61 30-JUN-13:30 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 40.55 0.00
July 27487.61 16-JUL-13:52 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 137.42 0.00
August 27696.65 06-AUG-14:41 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 351.82 0.00
September 30732.60 03-SEP-12:41 910.97 727.20 6829.06 0.00 0.00 0.00 0.00 381.38 0.00
October 27282.21 15-OCT-13:22 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 0.00 727.56
November 24315.79 12-NOV-13:32 404.87 323.20 3035.14 0.00 0.00 0.00 0.00 0.00 1121.00
December 11219.99 12-DEC-14:30 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 465.20
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10904.24   404.87 323.20 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30732.60   2010.83 1454.32 6829.06 0.00 0.00 0.00 0.00 381.38 1241.22



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3386.28 13-JAN-15:50 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 357.87
February 6693.60 28-FEB-16:40 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 156.78
March 8340.89 28-MAR-17:00 391.37 520.67 814.96 0.00 0.00 0.00 0.00 0.00 356.46
April 22865.17 16-APR-17:11 0.00 468.62 4400.81 0.00 0.00 0.00 0.00 0.00 363.84
May 23168.34 28-MAY-17:52 0.00 312.41 2933.87 0.00 0.00 0.00 0.00 0.00 670.28
June 23796.50 18-JUN-17:31 0.00 416.55 3911.83 0.00 0.00 0.00 0.00 0.00 63.49
July 27664.98 16-JUL-17:11 0.00 520.69 4889.79 0.00 0.00 0.00 0.00 66.84 0.00
August 24794.91 06-AUG-16:41 652.28 520.69 4889.79 0.00 0.00 0.00 0.00 353.44 0.00
September 26400.92 04-SEP-16:51 587.05 468.62 4400.81 0.00 0.00 0.00 0.00 82.76 0.00
October 9677.05 16-OCT-16:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 72.46
November 5093.91 03-NOV-15:50 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 147.24
December 3693.53 06-DEC-15:50 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 451.87
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3386.28   0.00 312.41 814.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 27664.98   1239.33 937.20 4889.79 0.00 0.00 0.00 0.00 353.44 670.28



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2087.53 14-JAN-17:03 404.87 526.11 3035.09 0.00 0.00 0.00 0.00 0.00 450.86
February 2622.12 27-FEB-16:10 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 121.98
March 2821.68 29-MAR-16:00 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 635.94
April 4425.28 07-APR-14:30 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 0.00 79.94
May 7709.16 19-MAY-16:00 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 215.48 0.00
June 9530.52 29-JUN-15:10 1923.11 1454.29 2276.32 0.00 0.00 0.00 0.00 350.96 0.00
July 15130.90 16-JUL-18:41 0.00 565.58 5311.41 0.00 0.00 0.00 0.00 279.53 0.00
August 19338.03 06-AUG-16:11 1012.16 807.98 7587.73 0.00 0.00 0.00 0.00 739.69 0.00
September 8066.96 05-SEP-14:00 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 2.16 0.00
October 4115.68 18-OCT-13:50 2010.79 1454.29 2276.32 0.00 0.00 0.00 0.00 60.48 0.00
November 2665.86 17-NOV-17:00 1923.11 2367.39 2276.32 0.00 0.00 0.00 0.00 0.00 265.30
December 2181.97 06-DEC-16:20 1923.11 2192.21 2276.32 0.00 0.00 0.00 0.00 0.00 633.71
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2087.53   0.00 526.11 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19338.03   2010.79 2367.39 7587.73 0.00 0.00 0.00 0.00 739.69 635.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2513.67 19-JAN-06:04 1174.10 1525.71 5867.78 0.00 0.00 0.00 0.00 0.00 44.81
February 3276.85 28-FEB-10:30 2591.66 1874.40 2933.89 0.00 0.00 0.00 0.00 0.00 193.23
March 5190.53 23-MAR-10:30 1239.33 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 675.21
April 9357.45 25-APR-09:40 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 134.71
May 11400.37 19-MAY-09:20 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 99.00
June 22632.36 25-JUN-09:02 391.37 312.41 2933.89 0.00 0.00 0.00 0.00 0.00 295.17
July 22351.13 16-JUL-09:22 391.37 312.41 2933.89 0.00 0.00 0.00 0.00 0.00 265.28
August 24303.86 06-AUG-08:11 521.82 416.55 3911.86 0.00 0.00 0.00 0.00 0.00 151.18
September 16405.27 04-SEP-09:02 326.14 260.35 2444.91 0.00 0.00 0.00 0.00 0.00 13.76
October 5935.97 18-OCT-10:00 1295.83 937.20 1466.95 0.00 0.00 0.00 0.00 0.00 133.46
November 3210.92 03-NOV-10:00 2591.66 1874.40 2933.89 0.00 0.00 0.00 0.00 0.00 262.56
December 2489.13 09-DEC-06:04 913.19 1186.66 4563.83 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2489.13   326.14 260.35 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24303.86   2591.66 1874.40 5867.78 0.00 0.00 0.00 0.00 0.00 675.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8957.88 31-JAN-13:40 1923.15 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 853.90
February 27507.63 26-FEB-14:21 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 0.00 1174.29
March 17910.34 01-MAR-14:10 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 348.85
April 16948.28 25-APR-13:40 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 147.43
May 15685.85 19-MAY-13:50 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 112.92 0.00
June 17968.33 25-JUN-15:02 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 0.00 143.40
July 27884.71 16-JUL-14:02 506.09 404.00 3793.92 0.00 0.00 0.00 0.00 245.37 0.00
August 30915.84 06-AUG-14:11 809.75 646.40 6070.27 0.00 0.00 0.00 0.00 439.13 0.00
September 30633.58 03-SEP-13:31 708.53 565.60 5311.49 0.00 0.00 0.00 0.00 575.92 0.00
October 30022.91 15-OCT-14:22 607.31 484.80 4552.71 0.00 0.00 0.00 0.00 0.00 903.93
November 17302.60 03-NOV-13:30 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 291.02
December 8609.56 06-DEC-14:40 2010.83 1454.32 2276.35 0.00 0.00 0.00 0.00 0.00 1018.71
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8609.56   506.09 404.00 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30915.84   2010.83 1454.32 6070.27 0.00 0.00 0.00 0.00 575.92 1174.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3377.10 13-JAN-15:50 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 433.75
February 6085.77 28-FEB-16:40 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 196.20
March 7911.71 28-MAR-17:00 391.37 520.67 814.96 0.00 0.00 0.00 0.00 0.00 446.15
April 17634.83 16-APR-17:11 0.00 468.62 4400.81 0.00 0.00 0.00 0.00 0.00 442.82
May 24383.89 28-MAY-17:52 0.00 312.41 2933.87 0.00 0.00 0.00 0.00 0.00 825.93
June 26299.55 18-JUN-16:41 456.59 364.48 3422.85 0.00 0.00 0.00 0.00 0.00 75.60
July 27979.85 09-JUL-17:31 0.00 468.62 4400.81 0.00 0.00 0.00 0.00 0.00 68.87
August 28607.14 06-AUG-16:11 652.28 520.69 4889.79 0.00 0.00 0.00 0.00 335.11 0.00
September 25445.69 04-SEP-16:22 391.37 312.41 2933.87 0.00 0.00 0.00 0.00 164.68 0.00
October 9471.34 18-OCT-16:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 4.27 0.00
November 4337.77 03-NOV-16:00 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 184.91
December 3678.20 06-DEC-15:50 1239.33 937.20 1466.94 0.00 0.00 0.00 0.00 0.00 545.60
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3377.10   0.00 312.41 814.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 28607.14   1239.33 937.20 4889.79 0.00 0.00 0.00 0.00 335.11 825.93



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7642.15 06-JAN-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2594.12
February 5618.53 28-FEB-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 169.78
March 5445.36 01-MAR-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 5853.81 25-APR-05:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 237.23
May 9655.13 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 172.90
June 8736.68 26-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 147.40
July 11925.90 17-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 46.71
August 10771.09 07-AUG-05:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 87.87
September 10073.69 06-SEP-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 72.98
October 5671.83 02-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 360.15
November 6023.33 06-NOV-06:07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 228.64
December 4374.40 09-DEC-06:07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4374.40   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11925.90   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2594.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10304.67 06-JAN-04:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5986.82
February 9223.57 04-FEB-04:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2912.12
March 11179.56 04-MAR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3160.72
April 6667.10 29-APR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3267.67
May 6448.79 08-MAY-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4185.32
June 6698.62 23-JUN-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.70 0.00
July 8154.85 17-JUL-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96.35 0.00
August 8156.32 07-AUG-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.32 0.00
September 7728.48 05-SEP-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.62
October 6029.53 10-OCT-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2703.96
November 8747.41 27-NOV-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5017.44
December 8033.56 29-DEC-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 6029.53   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11179.56   0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.32 5986.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 82.36 14-JAN-17:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 672.37
February 2545.11 26-FEB-14:26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 915.50
March 4410.76 23-MAR-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1172.99
April 10711.34 25-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 184.88
May 16442.43 19-MAY-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 181.42 0.00
June 19298.83 23-JUN-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 93.93 0.00
July 22981.96 17-JUL-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 20527.83 07-AUG-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 140.57 0.00
September 15022.49 01-SEP-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 141.91 0.00
October 8533.89 18-OCT-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.16
November 1924.04 03-NOV-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 405.36
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5142.72
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22981.96   0.00 0.00 0.00 0.00 0.00 0.00 0.00 181.42 5142.72



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2000.09 19-JAN-16:50 222.14 520.85 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4351.56 28-FEB-17:00 222.14 520.85 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6820.26 31-MAR-24:00 0.00 28.94 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8237.58 25-APR-18:10 23.38 173.61 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3506.78 31-MAY-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5350.58 30-JUN-23:12 0.00 115.75 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
July 7256.02 31-JUL-23:40 0.00 57.88 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 8260.85 03-AUG-18:50 23.38 173.61 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3314.41 30-SEP-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4956.61 31-OCT-24:00 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 6112.93 13-NOV-16:20 222.14 520.85 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7887.99 06-DEC-16:10 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2000.09   0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8260.85   222.14 520.85 23383.27 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1638.84 19-JAN-16:50 222.14 520.85 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3967.54 28-FEB-17:00 222.14 520.85 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5898.77 31-MAR-23:30 0.00 28.94 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7816.14 25-APR-18:10 23.38 173.61 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3305.33 31-MAY-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5241.42 30-JUN-23:55 0.00 57.88 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 7067.46 31-JUL-23:53 0.00 115.75 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7894.12 03-AUG-18:50 23.38 173.61 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2869.57 30-SEP-23:40 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4140.53 31-OCT-24:00 0.00 28.94 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5570.73 03-NOV-16:00 222.14 520.85 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7159.06 06-DEC-16:20 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1638.84   0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7894.12   222.14 520.85 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1412.46 13-JAN-16:30 222.14 520.85 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3906.11 28-FEB-17:00 222.14 520.85 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5836.58 28-MAR-17:50 23.38 173.61 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
April 7866.44 25-APR-18:10 23.38 173.61 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3221.75 31-MAY-24:00 0.00 28.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5241.25 30-JUN-23:55 0.00 57.88 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 7020.76 31-JUL-23:53 0.00 115.75 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7964.13 03-AUG-18:40 23.38 173.61 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2744.97 04-SEP-17:32 0.00 260.44 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
October 4046.38 18-OCT-17:00 70.15 289.36 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 5486.74 03-NOV-16:00 222.14 520.85 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7056.03 06-DEC-16:20 222.14 520.85 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1412.46   0.00 28.94 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7964.13   222.14 520.85 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 91678.72 02-JAN-17:00 4808.68 5919.59 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 183625.84 28-FEB-17:00 4808.68 5919.59 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 357551.65 31-MAR-24:00 0.00 328.88 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 367104.14 26-APR-16:00 4808.68 5919.59 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 176036.66 31-MAY-24:00 0.00 328.88 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 267990.03 30-JUN-24:00 0.00 657.76 569448.78 0.00 0.00 0.00 0.00 0.00 0.00
July 359143.61 31-JUL-23:12 0.00 1315.53 1518530.09 0.00 0.00 0.00 0.00 0.00 0.00
August 369523.53 22-AUG-07:20 9617.36 11839.17 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
September 175705.64 30-SEP-24:00 0.00 328.88 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 267688.27 31-OCT-24:00 0.00 328.88 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 276683.89 06-NOV-16:55 9617.36 11839.17 569448.78 0.00 0.00 0.00 0.00 0.00 0.00
December 367834.76 07-DEC-17:00 4808.68 5919.59 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 91678.72   0.00 328.88 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 369523.53   9617.36 11839.17 1518530.09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.172878E+13 1118183.89 13-JAN-16:00 0.120550E+13 2312600.18 09-JAN-07:19
February 0.195189E+13 1318307.10 27-FEB-16:10 0.667591E+12 1587928.39 01-FEB-07:10
March 0.262755E+13 1419859.85 16-MAR-15:30 0.431289E+12 1662964.84 06-MAR-07:10
April 0.295818E+13 1743546.65 06-APR-15:09 0.156661E+12 663030.05 29-APR-06:10
May 0.183464E+13 1441912.00 19-MAY-15:30 0.128849E+12 761928.97 08-MAY-04:10
June 0.238369E+13 1656963.57 29-JUN-15:09 0.652655E+11 206282.66 16-JUN-06:00
July 0.296599E+13 1961886.96 17-JUL-15:20 0.588336E+11 78804.62 05-JUL-11:30
August 0.342631E+13 2076655.13 07-AUG-15:39 0.626446E+11 142038.55 18-AUG-05:10
September 0.185895E+13 1532670.76 07-SEP-14:00 0.757554E+11 395687.78 19-SEP-05:10
October 0.223932E+13 1523275.77 18-OCT-15:00 0.135665E+12 758595.46 10-OCT-06:19
November 0.254807E+13 1537631.62 17-NOV-16:00 0.371771E+12 1419432.90 27-NOV-07:19
December 0.299430E+13 1626727.63 06-DEC-16:30 0.809265E+12 1687417.24 29-DEC-07:00
             
Annual Sum or Average 0.295177E+14     0.416909E+13    
Minimum of Months 0.172878E+13 1118183.89   0.588336E+11 78804.62  
Maximum of Months 0.342631E+13 2076655.13   0.120550E+13 2312600.18  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.315800E+12 0.768683E+11 0.811612E+12 0.164873E+12 0.199097E+12 0.153119E+11 0.00 0.956387E+11 0.853760E+10 0.410426E+11 0.00 0.00 0.00
February 0.282273E+12 0.623044E+11 0.102011E+13 0.148926E+12 0.179752E+12 0.163878E+11 0.00 0.159183E+12 0.215578E+11 0.614006E+11 0.00 0.00 0.00
March 0.332984E+12 0.590027E+11 0.146267E+13 0.165150E+12 0.208440E+12 0.193541E+11 0.00 0.248424E+12 0.389759E+11 0.925469E+11 0.00 0.00 0.00
April 0.296011E+12 0.470192E+11 0.170311E+13 0.159524E+12 0.207578E+12 0.254750E+11 0.00 0.324970E+12 0.831990E+11 0.111297E+12 0.00 0.00 0.00
May 0.318209E+12 0.400984E+11 0.820521E+12 0.165009E+12 0.222905E+12 0.340451E+11 0.00 0.143615E+12 0.532230E+11 0.370105E+11 0.00 0.00 0.00
June 0.315940E+12 0.349424E+11 0.110677E+13 0.159786E+12 0.262211E+12 0.542555E+11 0.00 0.293831E+12 0.106620E+12 0.493325E+11 0.00 0.00 0.00
July 0.296427E+12 0.375927E+11 0.143888E+13 0.164745E+12 0.290979E+12 0.736343E+11 0.00 0.474610E+12 0.134358E+12 0.547636E+11 0.00 0.00 0.00
August 0.330396E+12 0.445602E+11 0.177780E+13 0.165149E+12 0.290795E+12 0.709632E+11 0.00 0.528540E+12 0.132076E+12 0.860316E+11 0.00 0.00 0.00
September 0.296819E+12 0.526918E+11 0.784732E+12 0.159522E+12 0.231612E+12 0.449880E+11 0.00 0.179587E+12 0.774669E+11 0.315279E+11 0.00 0.00 0.00
October 0.310327E+12 0.648057E+11 0.112899E+13 0.164871E+12 0.213945E+12 0.277201E+11 0.00 0.202911E+12 0.613945E+11 0.643582E+11 0.00 0.00 0.00
November 0.310139E+12 0.718289E+11 0.140306E+13 0.159634E+12 0.196971E+12 0.182486E+11 0.00 0.243575E+12 0.528489E+11 0.917602E+11 0.00 0.00 0.00
December 0.305886E+12 0.794438E+11 0.175516E+13 0.164749E+12 0.199220E+12 0.165813E+11 0.00 0.310904E+12 0.426063E+11 0.119747E+12 0.00 0.00 0.00
                           
Annual Sum or Average 0.371121E+13 0.671158E+12 0.152134E+14 0.194194E+13 0.270350E+13 0.416965E+12 0.00 0.320579E+13 0.812864E+12 0.840818E+12 0.00 0.00 0.00
Minimum of Months 0.282273E+12 0.349424E+11 0.784732E+12 0.148926E+12 0.179752E+12 0.153119E+11 0.00 0.956387E+11 0.853760E+10 0.315279E+11 0.00 0.00 0.00
Maximum of Months 0.332984E+12 0.794438E+11 0.177780E+13 0.165150E+12 0.290979E+12 0.736343E+11 0.00 0.528540E+12 0.134358E+12 0.119747E+12 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.113587E+13 0.00 0.696306E+11 0.00 0.00
February 0.00 0.00 0.603572E+12 0.00 0.640187E+11 0.00 0.00
March 0.00 0.00 0.357620E+12 0.00 0.736690E+11 0.00 0.00
April 0.00 0.00 0.907589E+11 0.00 0.659025E+11 0.00 0.00
May 0.00 0.00 0.619418E+11 0.00 0.669075E+11 0.00 0.00
June 0.00 0.00 0.242476E+10 0.00 0.628408E+11 0.00 0.00
July 0.00 0.00 32213096.08 0.00 0.588014E+11 0.00 0.00
August 0.00 0.00 0.865777E+09 0.00 0.617788E+11 0.00 0.00
September 0.00 0.00 0.181576E+11 0.00 0.575977E+11 0.00 0.00
October 0.00 0.00 0.742052E+11 0.00 0.614602E+11 0.00 0.00
November 0.00 0.00 0.308900E+12 0.00 0.628711E+11 0.00 0.00
December 0.00 0.00 0.743192E+12 0.00 0.660724E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.339754E+13 0.00 0.771551E+12 0.00 0.00
Minimum of Months 0.00 0.00 32213096.08 0.00 0.575977E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.113587E+13 0.00 0.736690E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 352853.36 02-JAN-08:09 54335.80 01-JAN-06:10 439129.89 02-JAN-08:09 118959.22 02-JAN-08:20 113119.89 09-JAN-06:10 36605.46 25-JAN-06:10 0.00 01-JAN-00:10
February 338792.62 02-FEB-08:09 54335.80 01-FEB-06:10 557421.28 01-FEB-08:09 118947.47 02-FEB-08:20 150673.86 28-FEB-15:00 36954.08 01-FEB-06:10 0.00 01-FEB-00:10
March 349353.81 17-MAR-07:10 54335.80 01-MAR-06:10 675712.68 01-MAR-08:09 118956.29 17-MAR-07:19 159301.19 28-MAR-15:39 36880.72 04-MAR-06:10 0.00 01-MAR-00:10
April 333407.84 14-APR-07:10 54335.80 01-APR-05:10 794004.08 03-APR-07:10 118942.97 14-APR-07:19 211188.89 25-APR-15:39 50608.93 06-APR-14:00 0.00 01-APR-00:10
May 324684.10 03-MAY-07:10 54335.80 01-MAY-05:10 439129.89 01-MAY-07:10 118935.70 03-MAY-07:19 245353.78 19-MAY-15:30 53174.75 19-MAY-12:09 0.00 01-MAY-00:10
June 316816.17 01-JUN-07:10 54335.80 01-JUN-20:10 557421.28 01-JUN-07:10 118929.14 01-JUN-07:19 276989.67 29-JUN-14:30 54017.37 30-JUN-15:00 0.00 01-JUN-00:10
July 316816.17 03-JUL-07:10 54335.80 01-JUL-20:30 675712.68 03-JUL-07:10 118929.14 03-JUL-07:19 324151.01 17-JUL-15:20 55364.25 31-JUL-15:20 0.00 01-JUL-00:10
August 320030.31 17-AUG-07:10 54335.80 01-AUG-19:00 794004.08 01-AUG-07:10 118931.82 17-AUG-07:19 315966.19 11-AUG-15:30 55496.83 07-AUG-12:00 0.00 01-AUG-00:10
September 333129.14 11-SEP-07:10 54335.80 01-SEP-05:10 439129.89 01-SEP-07:10 118942.74 11-SEP-07:19 258653.69 05-SEP-14:39 56384.85 05-SEP-12:30 0.00 01-SEP-00:10
October 352853.36 30-OCT-07:10 54335.80 01-OCT-05:10 557421.28 02-OCT-07:10 118959.22 30-OCT-07:19 191997.27 18-OCT-15:00 51049.12 18-OCT-14:30 0.00 01-OCT-00:10
November 352853.36 01-NOV-07:10 54335.80 01-NOV-05:10 675712.68 01-NOV-07:10 118959.22 01-NOV-07:19 155545.77 03-NOV-15:20 36454.99 13-NOV-06:10 0.00 01-NOV-00:10
December 352853.36 01-DEC-16:40 54335.80 01-DEC-06:10 794004.08 01-DEC-08:09 118959.22 13-DEC-08:20 120437.62 07-DEC-14:09 36783.45 27-DEC-16:00 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 316816.17   54335.80   439129.89   118929.14   113119.89   36454.99   0.00  
Maximum of Months 352853.36   54335.80   794004.08   118959.22   324151.01   56384.85   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 43209.98 13-JAN-16:40 7436.44 14-JAN-14:00 20103.49 26-JAN-18:00 0.00 0.00 0.00
February 137839.13 27-FEB-15:30 49248.27 20-FEB-15:39 31480.82 04-FEB-07:40 0.00 0.00 0.00
March 116445.58 31-MAR-23:00 49248.27 14-MAR-11:20 43072.45 31-MAR-23:00 0.00 0.00 0.00
April 242316.19 07-APR-14:39 50128.65 06-APR-15:39 50208.67 29-APR-06:10 0.00 0.00 0.00
May 246537.85 19-MAY-15:30 53190.21 19-MAY-11:00 21872.30 31-MAY-23:00 0.00 0.00 0.00
June 322093.69 29-JUN-14:00 81829.93 06-JUN-14:39 27061.62 08-JUN-20:00 0.00 0.00 0.00
July 425587.55 17-JUL-15:30 81829.93 13-JUL-13:09 36644.71 12-JUL-06:19 0.00 0.00 0.00
August 426109.78 07-AUG-15:39 81829.93 05-AUG-12:00 49233.96 01-AUG-20:00 0.00 0.00 0.00
September 372469.93 07-SEP-14:00 81829.93 02-SEP-10:50 22843.25 30-SEP-23:00 0.00 0.00 0.00
October 264571.91 18-OCT-14:30 51033.48 18-OCT-15:09 33042.50 31-OCT-23:00 0.00 0.00 0.00
November 148130.83 17-NOV-16:00 49316.91 17-NOV-16:00 41304.61 20-NOV-21:00 0.00 0.00 0.00
December 125107.23 10-DEC-01:00 49248.27 05-DEC-11:00 52016.10 28-DEC-18:00 0.00 0.00 0.00
                   
Annual Sum or Average             0.00 0.00 0.00
Minimum of Months 43209.98   7436.44   20103.49   0.00 0.00 0.00
Maximum of Months 426109.78   81829.93   52016.10   0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1118183.89 13-JAN-16:00 352853.36 439129.89 54335.80 84914.28 90626.64 33715.72 0.00 43026.01 6403.97
February 1318307.10 27-FEB-16:10 316816.17 557421.28 0.00 84885.75 128154.56 33758.52 0.00 126684.05 49248.27
March 1419859.85 16-MAR-15:30 316816.17 675712.68 0.00 84885.75 154803.78 33663.86 0.00 97491.98 19674.87
April 1743546.65 06-APR-15:09 316816.17 794004.08 0.00 84885.75 182803.22 50574.82 0.00 238176.49 49855.51
May 1441912.00 19-MAY-15:30 316816.17 439129.89 0.00 84885.75 245353.78 52513.26 0.00 246537.85 52887.37
June 1656963.57 29-JUN-15:09 316816.17 557421.28 0.00 84885.75 273781.58 51098.08 0.00 320955.25 51272.64
July 1961886.96 17-JUL-15:20 316816.17 675712.68 0.00 84885.75 324151.01 54475.53 0.00 424015.89 81829.93
August 2076655.13 07-AUG-15:39 316816.17 794004.08 0.00 84885.75 301770.59 55015.81 0.00 426109.78 81829.93
September 1532670.76 07-SEP-14:00 316816.17 439129.89 0.00 39494.57 228836.31 54093.96 0.00 372469.93 81829.93
October 1523275.77 18-OCT-15:00 320848.56 557421.28 0.00 84888.31 191997.27 50830.49 0.00 255259.77 49999.01
November 1537631.62 17-NOV-16:00 352853.36 675712.68 54335.80 84915.83 112792.50 33717.52 0.00 148130.83 49316.91
December 1626727.63 06-DEC-16:30 352853.36 794004.08 54335.80 84905.03 105171.46 33668.37 0.00 121890.35 36495.38
                       
Annual Sum or Average                      
Minimum of Months 1118183.89   316816.17 439129.89 0.00 39494.57 90626.64 33663.86 0.00 43026.01 6403.97
Maximum of Months 2076655.13   352853.36 794004.08 54335.80 84915.83 324151.01 55015.81 0.00 426109.78 81829.93



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 2290324.49 09-JAN-07:10 0.00 85363.68 30-JAN-12:50 0.00
February 0.00 0.00 1558403.84 01-FEB-07:10 0.00 85520.85 22-FEB-12:20 0.00
March 0.00 0.00 1632342.91 06-MAR-07:10 0.00 85470.31 02-MAR-12:39 0.00
April 0.00 0.00 635188.25 29-APR-06:10 0.00 84643.89 03-APR-11:50 0.00
May 0.00 0.00 756233.10 08-MAY-04:10 0.00 83179.15 01-MAY-11:30 0.00
June 0.00 0.00 176680.99 16-JUN-06:00 0.00 81111.10 01-JUN-11:00 0.00
July 0.00 0.00 3489.77 08-JUL-05:10 0.00 78804.62 05-JUL-11:30 0.00
August 0.00 0.00 136342.68 18-AUG-05:10 0.00 77551.31 01-AUG-11:20 0.00
September 0.00 0.00 389991.91 19-SEP-05:10 0.00 78382.67 28-SEP-11:39 0.00
October 0.00 0.00 729958.18 10-OCT-06:30 0.00 80550.48 31-OCT-11:39 0.00
November 0.00 0.00 1389429.21 27-NOV-07:19 0.00 82614.83 30-NOV-12:39 0.00
December 0.00 0.00 1657082.82 29-DEC-07:00 0.00 84265.96 29-DEC-12:50 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 3489.77   0.00 77551.31   0.00
Maximum of Months 0.00 0.00 2290324.49   0.00 85520.85   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 6.00 27.19 1.50 27.22
February 0.00 0.00 0.00 0.00 1.17 25.95 0.00 25.95
March 0.00 0.00 0.00 0.00 1.83 25.95 0.00 25.95
April 0.00 0.00 0.00 0.00 2.17 25.85 0.00 25.85
May 0.00 0.00 0.00 0.00 2.00 26.06 0.00 26.06
June 0.00 0.00 0.00 0.00 2.50 25.88 0.00 25.88
July 0.00 0.00 0.00 0.00 6.83 26.15 0.00 26.15
August 0.00 0.00 0.00 0.00 7.17 25.86 0.00 25.86
September 0.00 0.00 0.00 0.00 9.17 26.41 0.33 26.45
October 0.00 0.00 0.00 0.00 11.17 26.44 0.83 26.51
November 0.00 0.00 0.00 0.00 7.33 26.43 0.17 26.45
December 0.00 0.00 0.00 0.00 2.33 25.99 0.00 25.99
                 
Annual Sum or Average 0.00   0.00   59.67 26.31 2.83 26.36
Minimum of Months 0.00 0.00 0.00 0.00 1.17 25.85 0.00 25.85
Maximum of Months 0.00 0.00 0.00 0.00 11.17 27.19 1.50 27.22



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
April 0.00 0.00 0.00 0.00 0.33 25.93 0.00 25.93
May 0.00 0.00 0.00 0.00 1.00 25.71 0.00 25.71
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.67 25.60 0.00 25.60
August 0.00 0.00 0.00 0.00 1.17 25.63 0.00 25.63
September 0.00 0.00 0.00 0.00 0.83 25.62 0.00 25.62
October 0.00 0.00 0.00 0.00 0.33 25.66 0.00 25.66
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.50 25.66 0.00 25.66
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.17 25.93 0.00 25.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.35 0.00 19.35 0.00 19.35 0.00 19.35
                 
Annual Sum or Average 0.17 19.35 0.00 19.35 0.17 22.46 0.00 22.46
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.35 0.00 19.35 0.17 25.56 0.00 25.56



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 8.17 18.81 2.00 19.03 0.00 19.03 0.00 19.03
February 1.50 18.60 0.17 18.78 0.00 18.78 0.00 18.78
March 1.33 18.59 0.33 18.94 0.00 18.94 0.00 18.94
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.33 18.78 0.00 18.78 0.00 18.78 0.00 18.78
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.17 19.39 0.00 19.39 0.00 19.39 0.00 19.39
November 1.67 18.92 0.33 19.08 0.00 19.08 0.00 19.08
December 2.67 18.65 0.33 18.82 0.00 18.82 0.00 18.82
                 
Annual Sum or Average 15.83 18.76 3.17 18.97 0.00 18.97 0.00 18.97
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8.17 19.39 2.00 19.39 0.00 19.39 0.00 19.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.00 18.57 0.83 18.80 0.00 18.80 0.00 18.80
February 0.50 19.29 0.00 19.29 0.00 19.29 0.00 19.29
March 0.33 19.04 0.00 19.04 0.00 19.04 0.00 19.04
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.50 26.72 0.33 26.95
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.31 0.00 19.31 0.00 19.31 0.00 19.31
                 
Annual Sum or Average 6.00 18.67 0.83 18.86 0.50 19.40 0.33 19.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.00 19.31 0.83 19.31 0.50 26.72 0.33 26.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.83 18.07 0.00 18.07 0.00 18.07 0.00 18.07
February 0.83 19.26 0.00 19.26 0.00 19.26 0.00 19.26
March 0.50 19.03 0.00 19.03 0.00 19.03 0.00 19.03
April 0.00 0.00 0.00 0.00 0.50 27.57 0.50 27.57
May 0.00 0.00 0.00 0.00 0.17 27.27 0.17 27.27
June 0.00 0.00 0.00 0.00 4.00 27.90 4.00 27.90
July 0.00 0.00 0.00 0.00 5.50 28.17 5.50 28.17
August 0.00 0.00 0.00 0.00 1.67 28.30 1.67 28.30
September 0.00 0.00 0.00 0.00 2.50 27.80 2.50 27.80
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.44 0.00 19.44 0.00 19.44 0.00 19.44
December 0.50 19.14 0.00 19.14 0.00 19.14 0.00 19.14
                 
Annual Sum or Average 5.83 18.45 0.00 18.45 14.33 25.25 14.33 26.39
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.83 19.44 0.00 19.44 5.50 28.30 5.50 28.30



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.50 18.16 0.17 18.24 0.17 18.56 0.17 18.85
February 0.67 19.15 0.00 19.15 1.50 25.35 1.50 26.48
March 0.50 18.84 0.00 18.84 0.33 22.27 0.33 23.73
April 0.00 0.00 0.00 0.00 1.00 27.60 1.00 27.60
May 0.00 0.00 0.00 0.00 0.17 27.27 0.17 27.27
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 4.50 27.71 4.50 27.71
August 0.00 0.00 0.00 0.00 3.67 27.93 3.33 27.95
September 0.00 0.00 0.00 0.00 5.83 28.06 5.33 28.08
October 0.00 0.00 0.00 0.00 2.50 28.15 2.50 28.15
November 0.17 19.06 0.00 19.06 1.17 26.46 1.17 26.95
December 0.50 19.06 0.00 19.06 0.17 21.11 0.17 22.34
                 
Annual Sum or Average 6.33 18.42 0.17 18.47 21.00 25.67 20.17 26.62
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.50 19.15 0.17 19.15 5.83 28.15 5.33 28.15



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.67 18.74 0.00 18.74 0.00 18.74 0.00 18.74
February 0.00 0.00 0.00 0.00 0.33 27.57 0.33 27.57
March 0.00 0.00 0.00 0.00 0.17 27.32 0.17 27.32
April 0.00 0.00 0.00 0.00 2.33 28.42 1.50 28.40
May 0.00 0.00 0.00 0.00 2.67 28.29 1.17 28.25
June 0.00 0.00 0.00 0.00 7.17 27.97 3.00 27.98
July 0.00 0.00 0.00 0.00 16.83 28.02 5.83 28.15
August 0.00 0.00 0.00 0.00 16.33 27.54 4.83 27.73
September 0.00 0.00 0.00 0.00 3.17 28.31 2.00 28.34
October 0.00 0.00 0.00 0.00 0.67 28.28 0.50 28.30
November 0.00 0.00 0.00 0.00 0.17 27.28 0.17 27.28
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.67 18.74 0.00 18.74 49.83 27.44 19.50 27.67
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.67 18.74 0.00 18.74 16.83 28.42 5.83 28.40



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 57.33 17.13 23.50 17.46 0.00 17.46 0.00 17.46
February 19.50 17.16 5.50 17.17 0.00 17.17 0.00 17.17
March 8.67 17.57 2.17 17.99 0.00 17.99 0.00 17.99
April 0.33 19.25 0.00 19.25 0.00 19.25 0.00 19.25
May 0.67 19.12 0.00 19.12 0.00 19.12 0.00 19.12
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.33 19.23 0.00 19.23 0.00 19.23 0.00 19.23
November 8.33 17.35 1.83 17.70 0.00 17.70 0.00 17.70
December 21.67 17.04 5.67 17.04 0.00 17.04 0.00 17.04
                 
Annual Sum or Average 116.83 17.19 38.67 17.41 0.00 17.41 0.00 17.41
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 57.33 19.25 23.50 19.25 0.00 19.25 0.00 19.25



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 26.83 15.59 4.17 15.45 0.00 15.45 0.00 15.45
February 12.17 16.57 1.17 16.48 0.00 16.48 0.00 16.48
March 6.17 16.56 0.33 16.61 0.00 16.61 0.00 16.61
April 0.33 19.15 0.00 19.15 0.00 19.15 0.00 19.15
May 0.67 19.08 0.00 19.08 0.00 19.08 0.00 19.08
June 0.00 0.00 0.00 0.00 3.67 27.97 3.67 27.97
July 0.00 0.00 0.00 0.00 6.50 28.24 6.50 28.24
August 0.00 0.00 0.00 0.00 2.50 28.32 2.50 28.32
September 0.00 0.00 0.00 0.00 2.67 27.82 2.67 27.82
October 0.33 19.25 0.00 19.25 0.00 19.25 0.00 19.25
November 5.33 16.67 0.17 16.77 0.00 16.77 0.00 16.77
December 14.33 16.21 3.17 15.95 0.00 15.95 0.00 15.95
                 
Annual Sum or Average 66.17 16.15 9.00 16.01 15.33 18.06 15.33 19.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.45 0.00 15.45
Maximum of Months 26.83 19.25 4.17 19.25 6.50 28.32 6.50 28.32



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 21.50 16.06 2.83 15.97 0.00 15.97 0.00 15.97
February 7.33 17.27 0.83 17.13 1.33 18.70 1.33 19.89
March 3.83 17.22 0.17 17.33 0.33 18.09 0.33 18.75
April 0.33 19.29 0.00 19.29 0.67 24.78 0.67 25.88
May 0.50 19.08 0.00 19.08 0.00 19.08 0.00 19.08
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 4.17 27.71 4.00 27.72
August 0.00 0.00 0.00 0.00 3.17 27.98 2.83 27.99
September 0.00 0.00 0.00 0.00 6.50 28.17 5.83 28.20
October 0.17 19.21 0.00 19.21 2.83 27.68 2.83 27.92
November 2.67 17.37 0.17 17.53 1.17 20.45 1.17 22.05
December 11.00 16.64 2.00 16.38 0.00 16.38 0.00 16.38
                 
Annual Sum or Average 47.33 16.62 6.00 16.49 20.17 19.65 19.00 21.36
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21.50 19.29 2.83 19.29 6.50 28.17 5.83 28.20



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 24.00 15.73 3.83 15.58 0.00 15.58 0.00 15.58
February 8.50 16.96 1.00 16.74 0.00 16.74 0.00 16.74
March 3.83 17.21 0.17 17.34 0.00 17.34 0.00 17.34
April 0.17 19.38 0.00 19.38 0.83 26.54 0.33 26.89
May 0.33 19.02 0.00 19.02 2.17 26.86 0.83 27.09
June 0.00 0.00 0.00 0.00 3.00 28.23 1.17 28.20
July 0.00 0.00 0.00 0.00 7.00 28.50 3.17 28.46
August 0.00 0.00 0.00 0.00 2.33 28.49 1.00 28.53
September 0.00 0.00 0.00 0.00 2.33 28.52 1.50 28.55
October 0.17 19.26 0.00 19.26 0.00 19.26 0.00 19.26
November 3.67 17.31 0.17 17.44 0.00 17.44 0.00 17.44
December 11.67 16.46 2.67 16.11 0.00 16.11 0.00 16.11
                 
Annual Sum or Average 52.33 16.36 7.83 16.17 17.67 18.94 8.00 19.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.58 0.00 15.58
Maximum of Months 24.00 19.38 3.83 19.38 7.00 28.52 3.17 28.55



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 113.33 16.29 46.33 16.68 0.00 16.68 0.00 16.68
February 46.83 16.77 14.33 17.01 0.00 17.01 0.00 17.01
March 26.83 16.67 7.50 16.81 0.00 16.81 0.00 16.81
April 3.83 18.55 0.17 18.62 0.00 18.62 0.00 18.62
May 6.50 17.52 0.83 17.71 0.00 17.71 0.00 17.71
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.17 27.46 0.00 27.46
August 0.00 0.00 0.00 0.00 0.83 27.36 0.50 27.36
September 0.83 19.16 0.00 19.16 0.00 19.16 0.00 19.16
October 3.83 18.11 0.17 18.20 0.00 18.20 0.00 18.20
November 31.50 16.14 10.00 16.23 0.00 16.23 0.00 16.23
December 73.83 16.00 27.00 16.15 0.00 16.15 0.00 16.15
                 
Annual Sum or Average 307.33 16.39 106.33 16.62 1.00 16.65 0.50 16.66
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 113.33 19.16 46.33 19.16 0.83 27.46 0.50 27.46



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 61.33 15.15 13.67 15.17 0.00 15.17 0.00 15.17
February 26.33 15.59 4.00 15.47 0.00 15.47 0.00 15.47
March 18.67 15.99 3.17 15.78 0.00 15.78 0.00 15.78
April 3.33 18.61 0.00 18.61 0.00 18.61 0.00 18.61
May 4.50 16.96 0.00 16.96 0.00 16.96 0.00 16.96
June 0.00 0.00 0.00 0.00 2.67 27.78 2.67 27.78
July 0.00 0.00 0.00 0.00 7.67 28.10 7.33 28.12
August 0.00 0.00 0.00 0.00 3.00 28.43 2.67 28.47
September 0.67 19.15 0.00 19.15 4.00 26.52 4.00 27.09
October 2.83 17.42 0.00 17.42 0.00 17.42 0.00 17.42
November 21.33 15.68 4.00 15.55 0.00 15.55 0.00 15.55
December 52.67 15.06 13.17 14.92 0.00 14.92 0.00 14.92
                 
Annual Sum or Average 191.67 15.48 38.00 15.36 17.33 16.25 16.67 17.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.92 0.00 14.92
Maximum of Months 61.33 19.15 13.67 19.15 7.67 28.43 7.33 28.47



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 54.17 15.69 12.50 15.86 0.00 15.86 0.00 15.86
February 20.17 16.17 1.50 16.08 0.83 16.52 0.83 16.92
March 16.00 16.39 1.83 16.35 0.00 16.35 0.00 16.35
April 2.67 18.52 0.00 18.52 0.00 18.52 0.00 18.52
May 4.33 16.94 0.00 16.94 0.00 16.94 0.00 16.94
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 4.50 27.84 4.00 27.85
August 0.00 0.00 0.00 0.00 2.67 28.32 2.17 28.35
September 0.67 19.22 0.00 19.22 5.17 27.33 4.33 27.82
October 1.50 18.12 0.00 18.12 1.17 22.56 1.17 24.29
November 15.00 16.33 2.17 16.25 0.00 16.25 0.00 16.25
December 40.50 15.44 8.17 15.31 0.00 15.31 0.00 15.31
                 
Annual Sum or Average 155.00 15.95 26.17 15.92 14.33 16.82 12.50 17.50
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 54.17 19.22 12.50 19.22 5.17 28.32 4.33 28.35



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 50.17 15.00 11.00 14.94 0.00 14.94 0.00 14.94
February 20.50 15.95 3.00 15.80 0.00 15.80 0.00 15.80
March 14.50 16.20 1.83 16.02 0.00 16.02 0.00 16.02
April 2.00 18.82 0.00 18.82 0.67 21.02 0.33 21.74
May 2.67 17.47 0.00 17.47 2.00 21.99 0.67 22.69
June 0.00 0.00 0.00 0.00 3.00 28.29 1.17 28.27
July 0.00 0.00 0.00 0.00 7.17 28.62 2.83 28.60
August 0.00 0.00 0.00 0.00 2.67 28.56 1.17 28.62
September 0.50 19.24 0.00 19.24 2.83 27.09 1.83 27.63
October 1.50 18.25 0.00 18.25 0.00 18.25 0.00 18.25
November 15.50 15.99 3.33 15.80 0.00 15.80 0.00 15.80
December 39.83 15.29 10.00 15.12 0.00 15.12 0.00 15.12
                 
Annual Sum or Average 147.17 15.58 29.17 15.42 18.33 16.65 8.00 17.11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.94 0.00 14.94
Maximum of Months 50.17 19.24 11.00 19.24 7.17 28.62 2.83 28.62



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 27.57 0.00 27.57
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 16.17 27.91 11.83 27.87
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   16.50 27.91 11.83 27.87
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 16.17 27.91 11.83 27.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 6.50 27.82 3.83 27.81
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   6.50 27.82 3.83 27.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.50 27.82 3.83 27.81



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 6.83 27.92 3.00 27.91
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   6.83 27.92 3.00 27.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.83 27.92 3.00 27.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 24.33 27.88 22.50 27.88
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 497.00 29.07 380.67 29.11
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   521.33 29.01 403.17 29.05
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 497.00 29.07 380.67 29.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 394.33 23.29 33.67 23.53 0.50 23.52
February 311.83 23.73 35.17 23.99 0.00 23.99
March 279.67 23.96 35.33 24.20 0.00 24.20
April 100.33 24.01 76.50 24.93 0.00 24.93
May 97.00 24.00 102.17 25.01 0.00 25.01
June 11.00 24.33 220.67 24.93 8.50 24.92
July 11.17 25.14 334.00 24.91 11.17 24.91
August 0.00 0.00 215.00 25.13 0.00 25.13
September 25.17 24.00 209.17 25.09 16.50 25.02
October 15.67 24.00 109.17 26.17 0.00 26.17
November 114.17 24.00 89.33 25.09 0.00 25.09
December 257.50 23.80 50.83 24.21 0.00 24.21
             
Annual Sum or Average 1617.83 23.75 1511.00 24.58 36.67 24.58
Minimum of Months 0.00 0.00 33.67 23.53 0.00 23.52
Maximum of Months 394.33 25.14 334.00 26.17 16.50 26.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 435.17 23.51 10.33 23.57 0.00 23.57
February 318.83 23.79 6.17 23.83 0.00 23.83
March 242.17 23.95 22.00 24.11 0.00 24.11
April 74.83 23.98 57.50 24.85 0.00 24.85
May 98.83 23.97 87.50 24.68 0.00 24.68
June 7.67 24.35 224.17 24.50 5.50 24.50
July 3.17 24.99 359.00 24.41 3.17 24.42
August 0.00 0.00 262.17 24.47 0.00 24.47
September 37.50 24.05 199.17 24.58 15.17 24.56
October 50.83 23.98 82.50 25.21 0.00 25.21
November 158.83 23.98 54.50 24.49 0.00 24.49
December 263.67 23.92 22.17 24.07 0.00 24.07
             
Annual Sum or Average 1691.50 23.81 1387.17 24.27 23.83 24.27
Minimum of Months 0.00 0.00 6.17 23.57 0.00 23.57
Maximum of Months 435.17 24.99 359.00 25.21 15.17 25.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 22.31 99.00 22.05 99.00 21.87
February 450.50 22.84 29.17 22.69 29.17 22.56
March 502.00 23.39 16.83 23.31 16.83 23.24
April 337.83 23.67 0.00 23.67 0.00 23.67
May 233.33 23.72 56.00 24.04 0.00 24.04
June 70.67 23.80 155.33 24.21 6.83 24.21
July 28.83 24.19 273.00 24.38 7.33 24.40
August 19.50 23.78 160.50 24.55 0.00 24.55
September 129.33 23.79 140.33 24.20 15.83 24.19
October 294.50 23.71 5.00 23.74 0.00 23.74
November 437.50 23.43 4.33 23.41 4.33 23.39
December 497.00 22.67 57.17 22.44 57.17 22.26
             
Annual Sum or Average 3503.00 23.17 996.67 23.30 236.50 23.19
Minimum of Months 19.50 22.31 0.00 22.05 0.00 21.87
Maximum of Months 502.00 24.19 273.00 24.55 99.00 24.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.72 316.50 20.47 316.50 20.35
February 454.00 21.40 190.67 21.06 190.67 20.87
March 514.00 22.13 115.67 21.78 115.67 21.54
April 443.17 22.77 43.83 22.58 43.83 22.42
May 321.67 23.07 62.00 23.12 22.33 22.97
June 119.83 23.48 156.00 23.94 5.50 23.95
July 50.33 23.78 282.83 24.26 9.33 24.27
August 68.67 23.59 161.67 24.21 0.00 24.21
September 238.83 23.21 118.33 23.62 17.50 23.64
October 453.00 22.73 25.50 22.60 25.50 22.48
November 486.83 21.89 128.17 21.55 128.17 21.33
December 497.00 21.04 259.83 20.68 259.83 20.50
             
Annual Sum or Average 4149.33 22.07 1861.00 22.02 1134.83 21.74
Minimum of Months 50.33 20.72 25.50 20.47 0.00 20.35
Maximum of Months 514.00 23.78 316.50 24.26 316.50 24.27



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.94 291.50 20.74 291.50 20.64
February 454.00 21.65 139.33 21.40 139.33 21.24
March 514.00 22.50 47.17 22.33 47.17 22.19
April 416.00 23.24 0.00 23.24 0.00 23.24
May 303.17 23.24 56.33 23.51 0.00 23.51
June 72.33 23.63 214.00 24.13 4.17 24.14
July 9.33 24.12 349.67 24.39 2.17 24.39
August 38.17 23.62 212.00 24.26 0.33 24.26
September 239.33 23.25 123.83 23.71 10.00 23.72
October 431.83 23.15 4.50 23.17 0.00 23.17
November 480.33 22.45 33.67 22.34 33.67 22.24
December 497.00 21.60 156.33 21.35 156.33 21.20
             
Annual Sum or Average 3957.50 22.37 1628.33 22.50 684.67 22.29
Minimum of Months 9.33 20.94 0.00 20.74 0.00 20.64
Maximum of Months 514.00 24.12 349.67 24.39 291.50 24.39



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 500.17 20.88 295.50 20.71 295.50 20.63
February 434.50 21.46 149.83 21.27 147.50 21.14
March 473.00 21.90 59.67 21.80 54.00 21.69
April 354.17 22.39 44.17 22.63 1.17 22.63
May 263.67 22.56 94.00 23.09 0.00 23.09
June 130.17 23.43 268.17 24.05 18.67 24.15
July 64.33 24.38 369.17 24.38 23.17 24.50
August 125.83 23.17 278.67 23.89 6.00 23.94
September 240.50 22.79 174.17 23.52 17.00 23.58
October 402.33 22.51 13.67 22.60 0.00 22.60
November 475.67 21.87 55.67 21.76 55.67 21.66
December 497.00 21.16 196.00 20.99 196.00 20.89
             
Annual Sum or Average 3961.33 21.96 1998.67 22.29 814.67 22.14
Minimum of Months 64.33 20.88 13.67 20.71 0.00 20.63
Maximum of Months 500.17 24.38 369.17 24.38 295.50 24.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 461.00 21.20 260.17 21.00 250.67 20.85
February 358.00 21.79 151.00 21.79 117.67 21.61
March 395.83 22.07 95.50 22.13 50.83 21.98
April 318.67 22.53 56.83 22.82 4.33 22.81
May 274.33 22.50 103.50 23.00 9.50 22.94
June 139.67 23.10 217.50 23.86 5.00 23.87
July 59.50 24.08 355.33 24.35 15.67 24.44
August 86.33 23.56 308.33 24.16 9.33 24.22
September 191.17 23.13 226.83 23.94 24.00 24.06
October 282.83 22.77 108.67 23.25 7.33 23.30
November 358.67 22.16 101.00 22.35 45.50 22.20
December 426.67 21.51 167.67 21.34 151.33 21.15
             
Annual Sum or Average 3352.67 22.17 2152.33 22.63 691.17 22.46
Minimum of Months 59.50 21.20 56.83 21.00 4.33 20.85
Maximum of Months 461.00 24.08 355.33 24.35 250.67 24.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 500.50 21.17 216.00 20.98 216.00 20.89
February 409.50 21.96 86.00 21.89 72.67 21.75
March 391.00 22.69 48.67 22.78 14.83 22.72
April 146.67 23.23 140.00 24.12 5.33 24.18
May 224.50 22.80 166.17 23.66 4.67 23.70
June 60.00 23.75 357.17 24.34 14.33 24.40
July 32.33 26.83 464.50 24.67 32.17 24.80
August 22.00 26.09 471.17 24.51 17.33 24.59
September 200.67 22.94 200.50 23.79 17.67 23.87
October 276.00 22.89 85.00 23.37 2.00 23.39
November 360.33 22.63 39.67 22.89 2.00 22.88
December 439.50 22.32 51.17 22.22 44.33 22.11
             
Annual Sum or Average 3063.00 22.44 2326.00 23.12 443.33 23.03
Minimum of Months 22.00 21.17 39.67 20.98 2.00 20.89
Maximum of Months 500.50 26.83 471.17 24.67 216.00 24.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.98 491.67 19.97 491.67 19.96
February 454.00 20.41 376.67 20.33 376.67 20.30
March 514.00 20.90 267.17 20.68 267.17 20.58
April 482.67 21.89 86.17 21.67 86.17 21.50
May 402.00 22.46 60.50 22.41 35.67 22.24
June 166.33 23.24 143.83 23.69 4.67 23.70
July 53.50 23.54 260.83 24.22 2.67 24.22
August 138.83 23.27 129.83 23.83 0.00 23.83
September 327.17 22.54 95.00 22.92 21.33 22.90
October 500.67 21.86 68.17 21.68 68.17 21.54
November 489.00 20.77 274.67 20.54 274.67 20.44
December 497.00 20.07 443.17 20.01 443.17 19.99
             
Annual Sum or Average 4527.17 21.30 2697.67 21.24 2072.00 20.99
Minimum of Months 53.50 19.98 60.50 19.97 0.00 19.96
Maximum of Months 514.00 23.54 491.67 24.22 491.67 24.22



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 19.99 398.83 19.96 398.83 19.95
February 384.17 20.56 274.17 20.41 274.17 20.35
March 424.83 20.95 193.00 20.74 193.00 20.62
April 351.33 21.66 73.00 21.62 56.33 21.48
May 302.17 22.02 80.00 22.23 28.83 22.06
June 155.67 23.06 196.50 23.88 19.17 24.00
July 88.00 24.10 289.83 24.48 28.17 24.64
August 137.00 22.94 211.50 23.88 7.67 23.96
September 264.67 22.28 116.83 23.00 19.67 23.06
October 408.17 21.67 47.50 21.57 44.33 21.47
November 416.83 20.76 222.50 20.58 222.50 20.50
December 422.00 20.00 365.33 19.92 365.33 19.90
             
Annual Sum or Average 3781.83 21.23 2469.00 21.41 1658.00 21.19
Minimum of Months 88.00 19.99 47.50 19.92 7.67 19.90
Maximum of Months 427.00 24.10 398.83 24.48 398.83 24.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 475.67 20.73 337.17 20.54 331.00 20.43
February 378.33 21.26 229.17 21.18 198.33 21.00
March 414.83 21.35 191.00 21.32 149.50 21.13
April 366.17 21.88 100.00 22.02 55.83 21.87
May 323.50 22.11 104.33 22.35 36.67 22.18
June 197.83 22.74 187.67 23.53 4.67 23.54
July 97.00 23.44 309.33 24.20 13.50 24.28
August 135.67 23.08 278.50 24.00 8.17 24.06
September 226.67 22.73 214.00 23.66 29.17 23.79
October 334.67 22.25 121.67 22.67 30.67 22.65
November 396.83 21.55 174.67 21.52 132.83 21.31
December 458.33 20.75 285.00 20.48 284.00 20.35
             
Annual Sum or Average 3805.50 21.68 2532.50 22.00 1274.33 21.76
Minimum of Months 97.00 20.73 100.00 20.48 4.67 20.35
Maximum of Months 475.67 23.44 337.17 24.20 331.00 24.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.21 452.50 20.16 452.50 20.14
February 445.33 20.70 290.17 20.53 290.00 20.46
March 492.83 21.01 194.17 20.83 192.33 20.72
April 420.83 21.70 76.67 21.76 49.83 21.67
May 342.83 22.04 112.00 22.42 30.83 22.32
June 202.83 22.68 202.17 23.53 10.17 23.59
July 112.83 23.37 316.00 24.17 16.67 24.26
August 169.50 22.78 241.17 23.77 4.83 23.80
September 318.33 22.17 133.33 22.86 19.83 22.93
October 456.67 21.66 52.67 21.64 39.33 21.56
November 483.67 20.97 204.00 20.76 204.00 20.64
December 497.00 20.27 381.00 20.15 381.00 20.10
             
Annual Sum or Average 4444.67 21.30 2655.83 21.50 1691.33 21.28
Minimum of Months 112.83 20.21 52.67 20.15 4.83 20.10
Maximum of Months 502.00 23.37 452.50 24.17 452.50 24.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.65 496.50 19.65 496.50 19.64
February 454.00 19.99 436.17 19.97 436.17 19.96
March 514.00 20.36 385.33 20.23 385.33 20.18
April 484.17 21.05 209.50 20.75 209.50 20.58
May 437.00 21.85 126.00 21.66 103.00 21.43
June 231.00 22.69 131.00 23.21 6.00 23.22
July 112.50 23.09 238.00 23.91 3.50 23.92
August 210.83 22.83 128.50 23.39 1.67 23.38
September 373.17 21.93 117.67 22.16 58.33 22.04
October 502.00 20.92 217.67 20.66 217.67 20.51
November 489.00 20.13 388.17 20.01 388.17 19.96
December 497.00 19.81 480.83 19.79 480.83 19.79
             
Annual Sum or Average 4806.67 20.84 3355.33 20.77 2786.67 20.56
Minimum of Months 112.50 19.65 117.67 19.65 1.67 19.64
Maximum of Months 514.00 23.09 496.50 23.91 496.50 23.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.82 488.33 19.80 488.33 19.80
February 454.00 20.22 376.00 20.11 376.00 20.07
March 509.33 20.64 309.33 20.42 309.33 20.32
April 416.67 21.24 146.50 20.99 137.33 20.79
May 354.50 21.75 129.50 21.80 70.67 21.55
June 163.67 22.62 250.50 23.69 14.33 23.74
July 102.83 23.92 357.33 24.34 29.00 24.48
August 149.50 22.78 287.00 23.81 11.50 23.87
September 313.67 22.10 149.17 22.70 45.00 22.71
October 493.00 21.20 139.17 20.93 139.17 20.76
November 489.00 20.26 350.00 20.12 350.00 20.06
December 497.00 19.87 466.83 19.84 466.83 19.83
             
Annual Sum or Average 4445.17 20.91 3449.67 21.09 2437.50 20.86
Minimum of Months 102.83 19.82 129.50 19.80 11.50 19.80
Maximum of Months 509.33 23.92 488.33 24.34 488.33 24.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 493.17 20.24 400.17 20.06 400.17 19.99
February 409.17 20.78 275.00 20.59 260.33 20.44
March 440.83 20.85 270.67 20.69 247.17 20.53
April 392.67 21.30 171.83 21.19 138.33 20.97
May 357.83 21.73 147.00 21.82 83.67 21.57
June 226.33 22.38 182.33 23.23 8.33 23.22
July 135.67 23.11 294.00 24.00 14.33 24.08
August 165.50 22.73 273.50 23.76 9.83 23.80
September 255.17 22.26 217.83 23.12 50.83 23.12
October 367.83 21.51 171.17 21.63 104.67 21.41
November 433.00 20.89 249.67 20.69 233.83 20.53
December 477.17 20.26 364.67 20.05 364.67 19.97
             
Annual Sum or Average 4154.33 21.20 3017.83 21.41 1916.17 21.14
Minimum of Months 135.67 20.24 147.00 20.05 8.33 19.97
Maximum of Months 493.17 23.11 400.17 24.00 400.17 24.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.87 473.50 19.83 473.50 19.82
February 449.83 20.34 354.17 20.21 354.17 20.15
March 498.50 20.65 297.33 20.46 297.33 20.37
April 433.00 21.21 156.33 21.09 134.50 20.92
May 378.00 21.77 144.33 21.97 69.67 21.78
June 237.67 22.41 197.33 23.29 11.50 23.34
July 146.50 23.03 296.50 23.96 17.67 24.06
August 204.00 22.53 229.00 23.52 7.00 23.56
September 338.83 21.85 145.00 22.41 47.83 22.39
October 474.67 21.15 146.67 20.97 136.50 20.82
November 488.00 20.48 314.83 20.29 314.83 20.21
December 497.00 19.98 437.67 19.91 437.67 19.88
             
Annual Sum or Average 4648.00 20.98 3192.67 21.11 2302.17 20.88
Minimum of Months 146.50 19.87 144.33 19.83 7.00 19.82
Maximum of Months 502.00 23.03 473.50 23.96 473.50 24.06



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 26.27 389.17 27.00 0.00 27.00
February 1.50 27.00 436.83 27.00 1.50 27.00
March 5.33 27.00 512.50 27.00 5.33 27.00
April 22.67 27.00 485.00 27.00 22.67 27.00
May 1.50 27.00 508.00 27.00 1.50 27.00
June 16.83 27.00 496.00 27.00 16.83 27.00
July 116.17 27.00 497.00 27.00 116.17 27.00
August 227.83 27.08 514.00 27.05 227.83 27.06
September 8.17 27.00 485.00 27.00 8.17 27.00
October 8.50 27.00 502.00 27.00 8.50 27.00
November 6.17 27.00 489.00 27.00 6.17 27.00
December 3.00 27.00 497.00 27.00 3.00 27.00
             
Annual Sum or Average 418.33 27.04 5811.50 27.01 417.67 27.01
Minimum of Months 0.67 26.27 389.17 27.00 0.00 27.00
Maximum of Months 227.83 27.08 514.00 27.05 227.83 27.06



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 99.83 25.62 214.00 26.56 0.00 26.56
February 13.17 27.00 312.33 27.00 0.00 27.00
March 6.50 27.00 463.17 27.00 0.00 27.00
April 3.33 27.00 480.33 27.00 3.33 27.00
May 0.83 27.00 498.33 27.00 0.83 27.00
June 7.17 27.00 496.00 27.00 7.17 27.00
July 16.50 27.00 497.00 27.00 16.50 27.00
August 34.50 27.19 514.00 27.03 34.50 27.03
September 4.00 27.00 485.00 27.00 4.00 27.00
October 0.00 0.00 502.00 27.00 0.00 27.00
November 0.00 0.00 455.33 27.00 0.00 27.00
December 12.00 27.00 346.17 27.00 0.00 27.00
             
Annual Sum or Average 197.83 26.34 5263.67 26.98 66.33 26.98
Minimum of Months 0.00 0.00 214.00 26.56 0.00 26.56
Maximum of Months 99.83 27.19 514.00 27.03 34.50 27.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 267.33 24.62 124.50 24.96 32.33 24.72
February 46.33 26.94 183.67 26.99 0.00 26.99
March 21.83 27.00 355.17 27.00 0.00 27.00
April 4.17 27.00 421.67 27.00 4.17 27.00
May 22.67 25.75 472.83 26.94 1.50 26.94
June 9.67 27.00 496.00 27.00 9.67 27.00
July 42.17 27.00 497.00 27.00 42.17 27.00
August 58.00 27.10 514.00 27.02 58.00 27.03
September 6.00 27.00 476.17 27.00 6.00 27.00
October 0.00 0.00 455.67 27.00 0.00 27.00
November 22.50 27.00 320.67 27.00 0.00 27.00
December 65.83 27.00 206.17 27.00 0.00 27.00
             
Annual Sum or Average 566.50 25.83 4523.50 26.84 153.83 26.81
Minimum of Months 0.00 0.00 124.50 24.96 0.00 24.72
Maximum of Months 267.33 27.10 514.00 27.02 58.00 27.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 236.00 27.00 502.00 27.00 236.00 27.00
February 454.00 27.01 454.00 27.01 454.00 27.01
March 514.00 27.01 514.00 27.01 514.00 27.01
April 485.00 27.07 485.00 27.07 485.00 27.07
May 490.00 27.00 508.00 27.00 490.00 27.00
June 496.00 27.01 496.00 27.01 496.00 27.01
July 497.00 27.01 497.00 27.01 497.00 27.01
August 514.00 28.64 514.00 28.64 514.00 28.64
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.01 502.00 27.01 502.00 27.01
November 489.00 27.01 489.00 27.01 489.00 27.01
December 497.00 27.00 497.00 27.00 497.00 27.00
             
Annual Sum or Average 5659.00 27.16 5943.00 27.16 5659.00 27.16
Minimum of Months 236.00 27.00 454.00 27.00 236.00 27.00
Maximum of Months 514.00 28.64 514.00 28.64 514.00 28.64



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.99490 13.62839 0.61185 13.07136
February 454.00000 27.00000 14.88765 0.70540 15.64095
March 514.00000 27.00000 16.83473 0.78876 18.24563
April 485.00000 27.00001 20.01035 0.88618 21.66965
May 508.00000 27.00015 22.20497 0.14169 5.59476
June 496.00000 27.00044 25.70015 0.25807 6.49326
July 497.00000 27.00025 26.88201 0.33213 7.38715
August 514.00000 27.03490 26.43124 0.38575 8.27403
September 485.00000 27.00051 25.35453 0.17738 5.82274
October 502.00000 27.00006 22.37184 0.83699 19.85120
November 489.00000 27.00000 18.49119 0.80724 18.85041
December 497.00000 27.00000 14.80780 0.76736 17.56590
           
Annual Sum or Average 5943.00000 27.00271 20.67327 0.55667 13.17101
Minimum of Months 454.00000 26.99490 13.62839 0.14169 5.59476
Maximum of Months 514.00000 27.03490 26.88201 0.88618 21.66965



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.69802 13.63789 0.44205 9.94706
February 454.00000 27.00000 14.87950 0.57003 12.03889
March 514.00000 27.00000 16.81832 0.64243 13.88428
April 485.00000 27.00002 19.97972 0.73735 16.61523
May 508.00000 27.00014 22.22341 0.04219 5.34040
June 496.00000 27.00042 25.71351 0.15852 5.71168
July 497.00000 27.00027 26.88319 0.22156 6.17603
August 514.00000 27.01421 26.44788 0.23247 6.33618
September 485.00000 27.00042 25.45500 0.08602 5.40635
October 502.00000 27.00006 22.35327 0.72628 16.21667
November 489.00000 27.00000 18.46547 0.65253 14.12632
December 497.00000 27.00000 14.78128 0.57110 12.08892
           
Annual Sum or Average 5943.00000 26.97583 20.67605 0.42191 10.29867
Minimum of Months 454.00000 26.69802 13.63789 0.04219 5.34040
Maximum of Months 514.00000 27.01421 26.88319 0.73735 16.61523



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 25.69245 13.96200 0.17581 8.81200
February 454.00000 26.99433 14.88094 0.49591 10.49331
March 514.00000 27.00000 16.82506 0.57320 12.24657
April 485.00000 27.00002 19.99553 0.67789 15.00140
May 508.00000 26.94141 22.28278 -0.0233 6.04910
June 496.00000 27.00043 25.72724 0.14533 5.79274
July 497.00000 27.00027 26.89229 0.22152 6.30109
August 514.00000 27.01218 26.45819 0.22232 6.38359
September 485.00000 27.00025 25.53745 0.04511 5.52958
October 502.00000 27.00006 22.37649 0.66004 14.39732
November 489.00000 27.00001 18.47708 0.56792 12.06912
December 497.00000 27.00000 14.79243 0.48961 10.38469
           
Annual Sum or Average 5943.00000 26.88525 20.72386 0.35263 9.43787
Minimum of Months 454.00000 25.69245 13.96200 -0.0233 5.52958
Maximum of Months 514.00000 27.01218 26.89229 0.67789 15.00140



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.99981 30.00049 0.99374 25.89664
February 454.00000 27.01078 29.99966 1.18262 34.42412
March 514.00000 27.00795 29.99988 1.34234 42.47348
April 485.00000 27.06675 29.99907 1.49883 50.83931
May 508.00000 27.00179 30.00194 0.46759 9.61113
June 496.00000 27.00948 29.99933 0.71320 15.72080
July 497.00000 27.00531 30.02780 0.93155 23.34487
August 514.00000 28.64486 29.87838 1.59673 55.38967
September 485.00000 27.00302 30.00174 0.52492 10.82973
October 502.00000 27.01100 29.99906 1.24779 37.62196
November 489.00000 27.00798 29.99859 1.37396 44.13327
December 497.00000 27.00097 30.00028 1.48221 49.93784
           
Annual Sum or Average 5943.00000 27.15251 29.99182 1.11343 33.38527
Minimum of Months 454.00000 26.99981 29.87838 0.46759 9.61113
Maximum of Months 514.00000 28.64486 30.02780 1.59673 55.38967



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.70856 12.38623 0.09392 6.75309
February 454.00000 24.13296 14.08573 0.20466 6.53852
March 514.00000 24.27482 15.10745 0.25555 6.66082
April 485.00000 24.44224 18.68000 0.32108 7.48544
May 508.00000 24.46415 22.37733 -0.5046 11.30397
June 496.00000 24.43836 31.09925 -0.4325 9.70754
July 497.00000 24.60675 35.53865 -0.3413 8.73746
August 514.00000 24.47978 30.66511 -0.4032 9.34697
September 485.00000 24.54025 30.25048 -0.4028 9.54345
October 502.00000 24.57326 20.84148 0.38143 8.61691
November 489.00000 24.54907 16.29411 0.33627 7.87166
December 497.00000 24.29826 13.41643 0.25174 6.91087
           
Annual Sum or Average 5943.00000 24.37653 21.77772 -0.0227 8.30474
Minimum of Months 454.00000 23.70856 12.38623 -0.5046 6.53852
Maximum of Months 514.00000 24.60675 35.53865 0.38143 11.30397



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.67350 14.38255 0.06957 5.99637
February 454.00000 24.00541 15.76540 0.17759 6.05796
March 514.00000 24.20043 16.44079 0.25195 6.54396
April 485.00000 24.32866 19.69834 0.32329 7.44150
May 508.00000 24.33576 23.61159 -0.5251 11.45788
June 496.00000 24.24353 32.39644 -0.4515 9.63282
July 497.00000 24.30374 36.45446 -0.3885 8.61598
August 514.00000 24.24943 31.76956 -0.4264 9.10833
September 485.00000 24.30446 31.46318 -0.4586 9.98963
October 502.00000 24.38017 22.45818 0.34791 7.83842
November 489.00000 24.36954 17.89279 0.30144 7.17527
December 497.00000 24.22258 15.14635 0.23450 6.46131
           
Annual Sum or Average 5943.00000 24.21897 23.17070 -0.0479 8.04229
Minimum of Months 454.00000 23.67350 14.38255 -0.5251 5.99637
Maximum of Months 514.00000 24.38017 36.45446 0.34791 11.45788



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.30568 16.86609 -0.2744 8.19720
February 454.00000 22.84615 17.59246 -0.1280 6.72346
March 514.00000 23.40222 18.27499 0.02740 5.96262
April 485.00000 23.84274 21.33002 0.17238 5.97375
May 508.00000 24.08543 24.53332 -0.6463 14.66046
June 496.00000 24.12970 32.94674 -0.5258 11.15946
July 497.00000 24.23274 36.90761 -0.4545 9.76981
August 514.00000 24.21580 32.08386 -0.4940 10.43834
September 485.00000 24.13765 32.16960 -0.5487 11.91860
October 502.00000 23.93933 24.05068 0.21380 6.17869
November 489.00000 23.50918 19.85775 0.05957 5.81210
December 497.00000 22.66998 17.04837 -0.1738 7.36702
           
Annual Sum or Average 5943.00000 23.61495 24.51456 -0.2327 8.70247
Minimum of Months 454.00000 22.30568 16.86609 -0.6463 5.81210
Maximum of Months 514.00000 24.23274 36.90761 0.21380 14.66046



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.72390 15.84935 -0.6978 18.18191
February 454.00000 21.39875 18.35209 -0.5011 12.86868
March 514.00000 22.12515 19.77100 -0.2999 9.61325
April 485.00000 22.88517 22.98520 -0.0719 6.96531
May 508.00000 23.53415 25.47651 -0.8488 22.88321
June 496.00000 23.98613 33.09636 -0.5739 12.75974
July 497.00000 24.17048 36.88961 -0.4657 10.04620
August 514.00000 24.13629 32.18786 -0.5212 11.22352
September 485.00000 23.74401 33.20886 -0.6972 17.24152
October 502.00000 22.85629 26.26057 -0.0637 6.65617
November 489.00000 21.90431 21.59987 -0.3479 10.31112
December 497.00000 21.03866 17.93101 -0.5953 16.02068
           
Annual Sum or Average 5943.00000 22.71890 25.34041 -0.4742 12.90803
Minimum of Months 454.00000 20.72390 15.84935 -0.8488 6.65617
Maximum of Months 514.00000 24.17048 36.88961 -0.0637 22.88321



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.93659 14.08719 -0.6258 15.31817
February 454.00000 21.64948 16.28270 -0.4088 10.27672
March 514.00000 22.49879 17.04854 -0.1818 7.11893
April 485.00000 23.35826 20.22475 0.06158 5.78746
May 508.00000 23.68274 23.90017 -0.7632 19.28761
June 496.00000 24.10500 31.97485 -0.4949 10.75618
July 497.00000 24.29325 35.67876 -0.3758 8.52616
August 514.00000 24.15952 31.32959 -0.4673 10.09933
September 485.00000 23.79277 31.81349 -0.6601 16.13472
October 502.00000 23.28437 23.13973 0.05448 5.72240
November 489.00000 22.48587 18.65002 -0.1772 6.96485
December 497.00000 21.60372 15.67503 -0.4174 10.27917
           
Annual Sum or Average 5943.00000 22.99709 23.36003 -0.3719 10.53267
Minimum of Months 454.00000 20.93659 14.08719 -0.7632 5.72240
Maximum of Months 514.00000 24.29325 35.67876 0.06158 19.28761



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.89423 13.41916 -0.6249 15.27781
February 454.00000 21.58728 15.61802 -0.3992 10.51605
March 514.00000 22.08464 16.65656 -0.2353 8.13270
April 485.00000 22.88199 20.21822 0.01002 6.88559
May 508.00000 23.35970 23.73402 -0.7781 21.05061
June 496.00000 23.95010 31.94301 -0.4416 11.60703
July 497.00000 24.18219 35.70118 -0.2983 8.87849
August 514.00000 23.85389 31.56527 -0.4620 11.45880
September 485.00000 23.53051 31.86682 -0.6529 17.60474
October 502.00000 22.85222 23.05945 0.00409 6.39245
November 489.00000 21.93796 18.48665 -0.2739 7.90251
December 497.00000 21.16299 15.35236 -0.5092 11.74430
           
Annual Sum or Average 5943.00000 22.69796 23.18094 -0.3891 11.46984
Minimum of Months 454.00000 20.89423 13.41916 -0.7781 6.39245
Maximum of Months 514.00000 24.18219 35.70118 0.01002 21.05061



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.47797 13.16279 -0.4734 13.85572
February 454.00000 22.34819 15.01570 -0.1972 10.10257
March 514.00000 22.55611 16.21317 -0.1126 8.31767
April 485.00000 23.11852 19.98044 0.05758 7.14243
May 508.00000 23.33474 23.84171 -0.8159 22.95013
June 496.00000 23.88195 32.17702 -0.5165 12.62624
July 497.00000 24.19401 35.72988 -0.3401 8.97959
August 514.00000 24.06837 31.16991 -0.3902 9.97256
September 485.00000 23.84195 31.23842 -0.5221 15.19343
October 502.00000 23.41671 22.24350 0.16308 7.75957
November 489.00000 22.76721 17.67216 -0.0600 8.22552
December 497.00000 21.91742 14.77186 -0.3152 10.90437
           
Annual Sum or Average 5943.00000 23.08162 22.81669 -0.2953 11.35746
Minimum of Months 454.00000 21.47797 13.16279 -0.8159 7.14243
Maximum of Months 514.00000 24.19401 35.72988 0.16308 22.95013



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.17574 13.08421 -0.5198 12.32272
February 454.00000 22.20986 14.87227 -0.2047 8.18463
March 514.00000 23.08482 15.55306 0.04233 6.62851
April 485.00000 24.07273 18.69494 0.34105 8.53225
May 508.00000 23.70611 23.16999 -0.6165 16.68288
June 496.00000 24.18685 31.47661 -0.3069 8.80630
July 497.00000 24.47445 35.03296 -0.1280 7.11538
August 514.00000 24.38686 30.46038 -0.1708 7.08115
September 485.00000 23.73050 31.31603 -0.5403 14.75420
October 502.00000 23.56875 21.91553 0.20695 7.09435
November 489.00000 23.14146 17.07746 0.05180 6.65717
December 497.00000 22.55762 14.01692 -0.1248 7.09664
           
Annual Sum or Average 5943.00000 23.36539 22.26813 -0.1646 9.24877
Minimum of Months 454.00000 21.17574 13.08421 -0.6165 6.62851
Maximum of Months 514.00000 24.47445 35.03296 0.34105 16.68288



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.97723 14.25844 -0.9404 25.85463
February 454.00000 20.41274 17.12537 -0.7696 19.17661
March 514.00000 20.89903 18.58482 -0.5932 14.19847
April 485.00000 21.90056 22.39242 -0.2978 8.56149
May 508.00000 22.83862 25.33342 -1.0643 31.83290
June 496.00000 23.81947 32.69581 -0.6196 14.36619
July 497.00000 24.14908 35.89608 -0.4616 10.17951
August 514.00000 23.94231 31.79365 -0.5880 13.36146
September 485.00000 23.13061 33.11813 -0.9009 25.73983
October 502.00000 21.86266 25.35158 -0.2915 8.17780
November 489.00000 20.76955 20.22525 -0.6199 15.22038
December 497.00000 20.07062 16.80845 -0.8637 23.20101
           
Annual Sum or Average 5943.00000 21.99387 24.50734 -0.6674 17.48646
Minimum of Months 454.00000 19.97723 14.25844 -1.0643 8.17780
Maximum of Months 514.00000 24.14908 35.89608 -0.2915 31.83290



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 19.99326 13.14845 -0.9211 25.04471
February 385.00000 20.56596 15.89631 -0.7072 17.64837
March 433.00000 21.01078 17.23484 -0.5370 13.32505
April 410.00000 22.03612 21.13663 -0.2164 8.68810
May 430.00000 22.69746 24.57197 -1.0262 31.44550
June 418.00000 23.78089 32.02084 -0.5201 14.68318
July 422.00000 24.22304 35.21646 -0.3128 10.09880
August 433.00000 23.84467 31.06142 -0.5017 13.54526
September 410.00000 23.04139 32.58756 -0.8410 25.45281
October 427.00000 21.78483 24.29756 -0.2697 8.03661
November 417.00000 20.76221 18.99034 -0.6039 14.35457
December 422.00000 19.99828 15.64177 -0.8690 23.33436
           
Annual Sum or Average 5034.00000 21.98667 23.51620 -0.6105 17.14476
Minimum of Months 385.00000 19.99326 13.14845 -1.0262 8.03661
Maximum of Months 433.00000 24.22304 35.21646 -0.2164 31.44550



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.93421 13.01990 -0.6417 18.10011
February 454.00000 21.78548 15.25048 -0.3552 13.11540
March 514.00000 21.89766 16.91697 -0.2852 10.97328
April 485.00000 22.48019 21.00612 -0.1050 8.47920
May 508.00000 22.89410 24.60854 -0.9729 29.56350
June 496.00000 23.62020 32.70652 -0.6187 16.05601
July 497.00000 24.08093 35.84287 -0.4001 10.54804
August 514.00000 23.94766 31.25513 -0.4577 12.25817
September 485.00000 23.58043 31.74137 -0.6111 19.11299
October 502.00000 22.91108 23.09689 0.04346 8.44111
November 489.00000 22.08519 18.23643 -0.2410 10.67283
December 497.00000 21.00581 15.36623 -0.5734 16.57430
           
Annual Sum or Average 5943.00000 22.60784 23.30295 -0.4364 14.51828
Minimum of Months 454.00000 20.93421 13.01990 -0.9729 8.44111
Maximum of Months 514.00000 24.08093 35.84287 0.04346 29.56350



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.20839 13.33832 -0.8571 22.55879
February 454.00000 20.75928 15.98346 -0.6414 16.06516
March 514.00000 21.13454 17.53401 -0.4903 12.35397
April 485.00000 22.04032 21.41564 -0.2001 8.21609
May 508.00000 22.78528 24.66355 -0.9717 29.99625
June 496.00000 23.54563 32.79936 -0.5894 16.01497
July 497.00000 23.99796 36.03479 -0.3827 10.76644
August 514.00000 23.74704 31.65541 -0.5198 13.78187
September 485.00000 22.89615 32.90768 -0.8667 26.44313
October 502.00000 21.87513 24.43023 -0.2323 7.89073
November 489.00000 21.00588 19.18231 -0.5241 12.84249
December 497.00000 20.27404 15.83872 -0.7809 20.27073
           
Annual Sum or Average 5943.00000 22.03308 23.86090 -0.5881 16.44115
Minimum of Months 454.00000 20.20839 13.33832 -0.9717 7.89073
Maximum of Months 514.00000 23.99796 36.03479 -0.2001 29.99625



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.65330 14.10673 -1.0932 32.48294
February 454.00000 19.99323 17.19038 -0.9318 25.65421
March 514.00000 20.35663 18.84577 -0.7765 20.06017
April 485.00000 21.05409 23.18807 -0.5238 13.47240
May 508.00000 22.17772 26.02146 -1.2983 41.56313
June 496.00000 23.43471 33.24437 -0.7395 19.31221
July 497.00000 23.92614 36.26760 -0.5217 12.23048
August 514.00000 23.61876 32.29005 -0.6863 17.21255
September 485.00000 22.48843 34.17203 -1.1208 35.51506
October 502.00000 20.92335 26.53482 -0.5423 13.36506
November 489.00000 20.12574 20.83278 -0.8338 22.39329
December 497.00000 19.81335 16.64572 -1.0062 28.86730
           
Annual Sum or Average 5943.00000 21.47700 24.98792 -0.8391 23.49801
Minimum of Months 454.00000 19.65330 14.10673 -1.2983 12.23048
Maximum of Months 514.00000 23.92614 36.26760 -0.5217 41.56313



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.81879 13.67424 -1.0321 29.81375
February 454.00000 20.21505 16.51655 -0.8405 22.39449
March 514.00000 20.66950 18.07375 -0.6590 17.10474
April 485.00000 21.64018 21.93211 -0.3355 11.48941
May 508.00000 22.47489 25.11854 -1.1144 34.50547
June 496.00000 23.68307 32.30263 -0.5360 15.48661
July 497.00000 24.13509 35.51840 -0.3071 10.04445
August 514.00000 23.78095 31.47246 -0.4958 13.87385
September 485.00000 22.86594 33.19595 -0.9099 28.52277
October 502.00000 21.24608 25.57532 -0.4232 11.15271
November 489.00000 20.26345 20.22556 -0.7734 20.10052
December 497.00000 19.87451 16.17855 -0.9722 27.52421
           
Annual Sum or Average 5943.00000 21.73496 24.19176 -0.6993 20.15347
Minimum of Months 454.00000 19.81879 13.67424 -1.1144 10.04445
Maximum of Months 514.00000 24.13509 35.51840 -0.3071 34.50547



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.31257 13.35778 -0.8514 24.42411
February 454.00000 21.13325 15.74807 -0.5597 17.42011
March 514.00000 21.30802 17.47882 -0.4728 15.12952
April 485.00000 21.87005 21.76430 -0.2814 11.57841
May 508.00000 22.47370 25.19744 -1.1385 36.08289
June 496.00000 23.37038 33.05305 -0.7003 19.64634
July 497.00000 23.91398 36.10240 -0.4427 12.28631
August 514.00000 23.76268 31.56512 -0.5139 14.69950
September 485.00000 23.23099 32.46089 -0.7468 24.70777
October 502.00000 22.22500 24.19713 -0.1521 10.50772
November 489.00000 21.25780 19.19103 -0.4849 14.93322
December 497.00000 20.40717 15.76055 -0.7789 22.46275
           
Annual Sum or Average 5943.00000 22.11337 23.87092 -0.5946 18.68126
Minimum of Months 454.00000 20.31257 13.35778 -1.1385 10.50772
Maximum of Months 514.00000 23.91398 36.10240 -0.1521 36.08289



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.86742 13.55840 -1.0062 28.84375
February 454.00000 20.37585 16.27959 -0.7843 20.95125
March 514.00000 20.75190 17.88774 -0.6301 16.46453
April 485.00000 21.53053 22.03797 -0.3508 11.10647
May 508.00000 22.40550 25.17928 -1.1207 35.94052
June 496.00000 23.30874 33.11788 -0.6657 19.32560
July 497.00000 23.82567 36.29768 -0.4264 12.50441
August 514.00000 23.54091 31.99225 -0.5822 16.39295
September 485.00000 22.57138 33.58443 -0.9926 32.13746
October 502.00000 21.31159 25.35438 -0.3985 10.92184
November 489.00000 20.48866 19.87984 -0.6984 18.07029
December 497.00000 19.98005 15.99102 -0.9165 25.45648
           
Annual Sum or Average 5943.00000 21.67457 24.30870 -0.7142 20.67684
Minimum of Months 454.00000 19.86742 13.55840 -1.1207 10.92184
Maximum of Months 514.00000 23.82567 36.29768 -0.3508 35.94052



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.146005E+09 2653.17 25-JAN-06:13 15.31 0.664844E+09 0.00 0.810849E+09 0.09 4.56 18-JAN-05:00 0.00 0.00
February 0.139478E+10 57932.15 27-FEB-15:30 51.20 0.766623E+10 0.00 0.906101E+10 0.36 6.69 27-FEB-13:40 0.00 0.00
March 0.780301E+09 10218.29 14-MAR-13:30 78.03 0.355391E+10 0.00 0.433422E+10 0.48 4.56 16-MAR-12:20 0.00 0.00
April 0.105760E+11 82261.61 07-APR-14:40 144.38 0.609212E+11 0.00 0.714972E+11 0.99 7.42 06-APR-15:10 0.00 0.00
May 0.281768E+11 91967.84 19-MAY-15:30 215.98 0.175064E+12 0.00 0.203241E+12 1.59 7.40 30-MAY-14:50 0.00 0.00
June 0.695462E+11 103253.02 29-JUN-15:00 368.56 0.456624E+12 0.00 0.526170E+12 3.07 7.48 29-JUN-15:00 0.00 0.00
July 0.106459E+12 121498.27 17-JUL-15:30 500.23 0.724024E+12 0.00 0.830483E+12 4.21 7.54 25-JUL-15:20 0.00 0.00
August 0.931619E+11 113497.38 07-AUG-15:40 489.66 0.628117E+12 0.00 0.721279E+12 3.98 7.53 10-AUG-15:40 0.00 0.00
September 0.517400E+11 157579.02 07-SEP-15:00 300.64 0.337901E+12 0.00 0.389641E+12 2.45 7.51 07-SEP-14:00 0.00 0.00
October 0.158366E+11 84343.56 18-OCT-14:30 158.33 0.966509E+11 0.00 0.112487E+12 1.11 7.44 16-OCT-13:30 0.00 0.00
November 0.180340E+10 39794.97 17-NOV-17:00 72.04 0.816699E+10 0.00 0.997039E+10 0.46 4.56 13-NOV-06:50 0.00 0.00
December 0.382181E+09 2657.27 27-DEC-17:00 40.07 0.174066E+10 0.00 0.212284E+10 0.25 4.56 24-DEC-00:20 0.00 0.00
                         
Annual Sum or Average 0.380003E+12     2434.43 0.250109E+13 0.00 0.288110E+13 1.59     0.00 0.00
Minimum of Months 0.146005E+09 2653.17   15.31 0.664844E+09 0.00 0.810849E+09 0.09 4.56   0.00 0.00
Maximum of Months 0.106459E+12 157579.02   500.23 0.724024E+12 0.00 0.830483E+12 4.21 7.54   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.202547E+10 91967.84 19-MAY-15:30 6.67 0.146942E+11 0.00 0.167197E+11 0.06 7.36 19-MAY-12:10 0.00 0.00
June 0.206999E+11 103253.02 29-JUN-15:00 65.69 0.150532E+12 0.00 0.171232E+12 0.66 7.48 29-JUN-15:00 0.00 0.00
July 0.427509E+11 121498.27 17-JUL-15:30 130.56 0.312821E+12 0.00 0.355572E+12 1.28 7.54 25-JUL-15:20 0.00 0.00
August 0.359727E+11 113497.38 07-AUG-15:40 110.76 0.263948E+12 0.00 0.299921E+12 1.09 7.53 10-AUG-15:40 0.00 0.00
September 0.104827E+11 157579.02 07-SEP-15:00 33.30 0.760114E+11 0.00 0.864941E+11 0.34 7.51 07-SEP-14:00 0.00 0.00
October 0.106160E+10 84343.56 18-OCT-14:30 3.67 0.764948E+10 0.00 0.871108E+10 0.04 7.25 18-OCT-12:40 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.112993E+12     350.64 0.825656E+12 0.00 0.938649E+12 0.29     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.427509E+11 157579.02   130.56 0.312821E+12 0.00 0.355572E+12 1.28 7.54   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.853760E+10 744.00 7436.44 14-JAN-15:00 203429.85 13-JAN-16:30 21.70 18.33 15.31
February 0.215578E+11 672.00 49248.27 20-FEB-15:40 387904.83 26-FEB-17:03 24.70 18.36 15.31
March 0.389759E+11 744.00 49248.27 14-MAR-11:20 646331.74 31-MAR-24:00 27.62 18.34 15.31
April 0.831700E+11 720.00 49248.27 01-APR-11:00 704607.28 16-APR-18:02 31.45 19.20 15.31
May 0.529996E+11 744.00 49248.27 02-MAY-10:20 365958.40 31-MAY-24:00 23.16 19.26 15.31
June 0.103375E+12 720.00 49248.27 01-JUN-00:10 529048.27 30-JUN-23:33 29.08 22.15 15.31
July 0.127835E+12 744.00 49248.27 01-JUL-00:10 686446.65 31-JUL-23:42 36.34 26.41 15.31
August 0.129415E+12 744.00 49248.27 01-AUG-00:05 759557.43 05-AUG-19:32 39.16 26.48 15.31
September 0.754933E+11 720.00 49248.27 01-SEP-00:02 353867.39 30-SEP-24:00 24.70 20.68 15.31
October 0.613285E+11 744.00 49248.27 02-OCT-13:10 498622.67 31-OCT-24:00 25.59 18.90 15.31
November 0.528484E+11 720.00 49248.27 01-NOV-10:50 529487.65 03-NOV-16:00 27.81 18.45 15.31
December 0.426063E+11 744.00 49248.27 05-DEC-12:00 665192.42 06-DEC-16:10 30.28 18.35 15.31
                   
Annual Sum or Average 0.798142E+12 8760.00         28.50 20.43 15.31
Minimum of Months 0.853760E+10 672.00 7436.44   203429.85   21.70 18.33 15.31
Maximum of Months 0.129415E+12 744.00 49248.27   759557.43   39.16 26.48 15.31



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 219537.27 17-JAN-07:00 21.02 21.02 0.12
February 0.00 0.00 0.00 01-FEB-00:10 458702.71 27-FEB-15:30 21.00 20.98 0.98
March 0.00 0.00 0.00 01-MAR-00:10 219587.20 16-MAR-13:00 20.95 20.94 0.84
April 29053086.52 41.51 880.38 06-APR-15:40 883898.27 06-APR-16:00 21.13 21.00 5.82
May 0.195868E+09 128.43 2092.39 19-MAY-17:50 1135948.74 19-MAY-15:30 21.54 21.16 12.13
June 0.213470E+10 297.13 16290.83 06-JUN-14:40 1152126.20 30-JUN-14:40 22.21 21.17 26.05
July 0.417225E+10 419.81 16290.83 13-JUL-13:10 1152052.90 24-JUL-14:30 22.75 21.16 35.04
August 0.175826E+10 365.68 16290.83 05-AUG-11:40 1149917.89 24-AUG-15:00 22.51 21.08 31.99
September 0.140373E+10 221.91 16290.83 02-SEP-10:50 1273486.46 07-SEP-15:00 21.89 21.15 20.07
October 64002721.12 67.48 944.18 18-OCT-16:20 997413.79 18-OCT-12:10 21.22 21.02 7.43
November 452312.65 5.17 68.64 17-NOV-17:00 231704.75 17-NOV-17:00 20.99 20.96 1.64
December 0.00 0.00 0.00 01-DEC-00:10 219518.39 20-DEC-07:00 21.00 20.99 0.32
                   
Annual Sum or Average 0.975831E+10 1547.12         21.52 21.05 11.94
Minimum of Months 0.00 0.00 0.00   219518.39   20.95 20.94 0.12
Maximum of Months 0.417225E+10 419.81 16290.83   1273486.46   22.75 21.17 35.04



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 21.02 21.02 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 21.00 21.00 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 20.95 20.95 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 21.13 21.13 0.00
May 27517676.95 4.83 1970.97 19-MAY-12:00 1135948.74 19-MAY-15:30 21.54 21.51 0.36
June 0.111044E+10 51.83 16290.83 06-JUN-14:40 1152126.20 30-JUN-14:40 22.21 21.92 3.98
July 0.235124E+10 106.58 16290.83 13-JUL-13:10 1152052.90 24-JUL-14:30 22.75 22.15 7.91
August 0.903030E+09 91.83 16290.83 05-AUG-13:00 1149917.89 24-AUG-15:00 22.51 21.99 6.82
September 0.569917E+09 25.33 16290.83 02-SEP-10:50 1273486.46 07-SEP-15:00 21.89 21.74 1.94
October 2001419.40 0.67 892.61 18-OCT-15:10 969131.76 18-OCT-14:50 21.22 21.22 0.05
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 20.99 20.99 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 21.00 21.00 0.00
                   
Annual Sum or Average 0.496414E+10 281.08         21.52 21.39 1.77
Minimum of Months 0.00 0.00 0.00   0.00   20.95 20.95 0.00
Maximum of Months 0.235124E+10 106.58 16290.83   1273486.46   22.75 22.15 7.91



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.908041E+12 0.00 613.56 1926652.15 09-JAN-07:10 0.00 32.45 72.17 1.83 0.00 0.10 0.57 09-JAN-07:10
February 0.471065E+12 0.00 456.86 1989661.92 07-FEB-06:01 0.00 28.30 63.48 0.97 0.00 0.06 0.59 07-FEB-06:01
March 0.264416E+12 0.00 448.88 1928193.29 06-MAR-05:01 0.00 25.32 58.19 0.47 0.00 0.03 0.57 06-MAR-05:01
April 0.617474E+11 0.00 249.57 1360847.79 29-APR-05:01 0.00 22.52 42.28 0.10 0.00 0.01 0.40 29-APR-05:01
May 0.434825E+11 0.00 170.12 1555198.13 22-MAY-04:01 0.00 22.67 35.57 0.07 0.00 0.00 0.46 22-MAY-04:01
June 0.157475E+10 0.00 35.42 183589.52 17-JUN-05:03 0.00 21.18 24.05 0.00 0.00 0.00 0.05 17-JUN-05:03
July 20912399.13 0.00 4.54 3713.59 08-JUL-05:05 0.00 20.87 21.23 0.00 0.00 0.00 0.00 08-JUL-05:05
August 0.562214E+09 0.00 15.13 173688.76 18-AUG-05:02 0.00 20.84 22.03 0.00 0.00 0.00 0.05 18-AUG-05:02
September 0.119485E+11 0.00 118.81 867742.81 19-SEP-05:03 0.00 20.91 30.49 0.02 0.00 0.00 0.26 19-SEP-05:03
October 0.508915E+11 0.00 266.33 1598765.11 10-OCT-04:01 0.00 21.93 42.42 0.08 0.00 0.01 0.47 10-OCT-04:01
November 0.229836E+12 0.00 437.44 1698994.42 27-NOV-06:01 0.00 25.08 58.26 0.42 0.00 0.03 0.50 27-NOV-06:01
December 0.578719E+12 0.00 566.08 2009651.10 26-DEC-05:11 0.00 29.60 68.59 1.08 0.00 0.06 0.59 26-DEC-05:11
                           
Annual Sum or Average 0.262230E+13 0.00 3382.72     0.00 24.29 44.81 0.42 0.00 0.02    
Minimum of Months 20912399.13 0.00 4.54 3713.59   0.00 20.84 21.23 0.00 0.00 0.00 0.00  
Maximum of Months 0.908041E+12 0.00 613.56 2009651.10   0.00 32.45 72.17 1.83 0.00 0.10 0.59  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 21.70 21.70 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 24.70 24.70 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 27.62 27.62 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 31.45 31.45 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 23.16 23.16 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 29.08 29.08 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 36.34 36.34 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:05 0.00 39.16 39.16 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:02 0.00 24.70 24.70 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 25.59 25.59 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 27.81 27.81 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 30.28 30.28 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 28.50 28.50 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 21.70 21.70 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 39.16 39.16 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.631469E+09 0.00 11.70 0.631469E+09 0.00 0.00 0.00 0.00 42298.79 27-FEB-15:30 42298.79 27-FEB-15:30 0.00 0.00 0.00
March 34245100.02 0.00 4.24 34245100.02 0.00 0.00 0.00 0.00 6873.66 14-MAR-13:30 6873.66 14-MAR-13:30 0.00 0.00 0.00
April 0.661475E+10 0.00 77.94 0.661475E+10 0.00 0.00 0.00 0.00 84147.20 07-APR-14:00 84147.20 07-APR-14:00 0.00 0.00 0.00
May 0.181362E+11 0.00 167.52 0.181362E+11 0.00 0.00 0.00 0.00 110739.54 19-MAY-15:20 110739.54 19-MAY-15:20 0.00 0.00 0.00
June 0.599180E+11 0.00 348.79 0.598665E+11 0.00 0.00 0.00 0.00 127546.54 29-JUN-14:50 127546.54 29-JUN-14:50 0.00 0.00 0.00
July 0.102793E+12 0.00 479.42 0.102626E+12 0.00 0.00 0.00 0.00 153583.55 17-JUL-15:20 153583.55 17-JUL-15:20 0.00 0.00 0.00
August 0.950781E+11 0.00 470.22 0.950781E+11 0.00 0.00 0.00 0.00 153907.64 07-AUG-15:20 153907.64 07-AUG-15:20 0.00 0.00 0.00
September 0.388729E+11 0.00 261.29 0.376260E+11 0.00 0.00 0.00 0.00 195729.35 07-SEP-15:00 125610.52 01-SEP-16:00 0.00 0.00 0.00
October 0.105474E+11 0.00 109.72 0.105474E+11 0.00 0.00 0.00 0.00 102919.20 18-OCT-15:50 102919.20 18-OCT-15:50 0.00 0.00 0.00
November 0.560038E+09 0.00 22.93 0.560038E+09 0.00 0.00 0.00 0.00 18833.65 17-NOV-17:00 18833.65 17-NOV-17:00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.333186E+12 0.00 1953.76 0.331721E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.102793E+12 0.00 479.42 0.102626E+12 0.00 0.00 0.00 0.00 195729.35   153907.64   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 22025.30 0.00 12.40 22025.30 0.00 0.00 0.00 0.00 3.82 02-JAN-05:43 3.82 02-JAN-05:43 0.00 0.00 0.00
February 0.449454E+10 0.00 47.53 0.449454E+10 0.00 0.00 0.00 0.00 298207.97 27-FEB-13:50 298207.97 27-FEB-13:50 0.00 0.00 0.00
March 95868854.75 0.00 77.28 95868854.75 0.00 0.00 0.00 0.00 21490.08 14-MAR-13:40 21490.08 14-MAR-13:40 0.00 0.00 0.00
April 0.465868E+11 0.00 134.08 0.465868E+11 0.00 0.00 0.00 0.00 634436.50 06-APR-16:00 634436.50 06-APR-16:00 0.00 0.00 0.00
May 0.153363E+12 0.00 199.87 0.153363E+12 0.00 0.00 0.00 0.00 1047502.37 19-MAY-15:30 1047502.37 19-MAY-15:30 0.00 0.00 0.00
June 0.507393E+12 0.00 329.45 0.506952E+12 0.00 0.00 0.00 0.00 1202902.78 29-JUN-14:50 1202902.78 29-JUN-14:50 0.00 0.00 0.00
July 0.851486E+12 0.00 417.66 0.850458E+12 0.00 0.00 0.00 0.00 1392153.47 17-JUL-15:30 1392153.47 17-JUL-15:30 0.00 0.00 0.00
August 0.737744E+12 0.00 389.04 0.737744E+12 0.00 0.00 0.00 0.00 1322502.29 10-AUG-15:40 1322502.29 10-AUG-15:40 0.00 0.00 0.00
September 0.339029E+12 0.00 272.26 0.327943E+12 0.00 0.00 0.00 0.00 1792594.27 07-SEP-15:00 1142540.98 01-SEP-16:00 0.00 0.00 0.00
October 0.830409E+11 0.00 144.29 0.830409E+11 0.00 0.00 0.00 0.00 851650.27 18-OCT-15:00 851650.27 18-OCT-15:00 0.00 0.00 0.00
November 0.402796E+10 0.00 69.04 0.402796E+10 0.00 0.00 0.00 0.00 131398.09 17-NOV-17:00 131398.09 17-NOV-17:00 0.00 0.00 0.00
December 85216.38 0.00 38.21 85216.38 0.00 0.00 0.00 0.00 1.39 21-DEC-15:00 1.39 21-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.272726E+13 0.00 2131.12 0.271471E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 22025.30 0.00 12.40 22025.30 0.00 0.00 0.00 0.00 1.39   1.39   0.00 0.00 0.00
Maximum of Months 0.851486E+12 0.00 417.66 0.850458E+12 0.00 0.00 0.00 0.00 1792594.27   1392153.47   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 59233.01 0.00 2.43 59233.01 0.00 0.00 0.00 0.00 471.39 17-JAN-04:52 471.39 17-JAN-04:52 0.00 0.00 0.00
February 0.319283E+09 0.00 12.65 0.319283E+09 0.00 0.00 0.00 0.00 21923.36 26-FEB-14:21 21923.36 26-FEB-14:21 0.00 0.00 0.00
March 2115474.09 0.00 1.58 2115474.09 0.00 0.00 0.00 0.00 1667.83 04-MAR-05:41 1667.83 04-MAR-05:41 0.00 0.00 0.00
April 0.433904E+10 0.00 65.15 0.433904E+10 0.00 0.00 0.00 0.00 64046.14 06-APR-16:00 64046.14 06-APR-16:00 0.00 0.00 0.00
May 0.159500E+11 0.00 153.57 0.159500E+11 0.00 0.00 0.00 0.00 125734.12 19-MAY-15:30 125734.12 19-MAY-15:30 0.00 0.00 0.00
June 0.557763E+11 0.00 318.70 0.557211E+11 0.00 0.00 0.00 0.00 143214.45 29-JUN-15:00 143214.45 29-JUN-15:00 0.00 0.00 0.00
July 0.941281E+11 0.00 416.96 0.940337E+11 0.00 0.00 0.00 0.00 169657.20 17-JUL-15:30 169657.20 17-JUL-15:30 0.00 0.00 0.00
August 0.794769E+11 0.00 379.64 0.794769E+11 0.00 0.00 0.00 0.00 157975.35 07-AUG-15:40 157975.35 07-AUG-15:40 0.00 0.00 0.00
September 0.347387E+11 0.00 241.90 0.336262E+11 0.00 0.00 0.00 0.00 183238.71 07-SEP-15:20 131239.44 01-SEP-16:00 0.00 0.00 0.00
October 0.713518E+10 0.00 93.46 0.713518E+10 0.00 0.00 0.00 0.00 88699.86 18-OCT-15:00 88699.86 18-OCT-15:00 0.00 0.00 0.00
November 0.301718E+09 0.00 16.05 0.301718E+09 0.00 0.00 0.00 0.00 10754.42 17-NOV-17:00 10754.42 17-NOV-17:00 0.00 0.00 0.00
December 1767.86 0.00 1.52 1767.86 0.00 0.00 0.00 0.00 0.37 01-DEC-06:25 0.37 01-DEC-06:25 0.00 0.00 0.00
                               
Annual Sum or Average 0.292167E+12 0.00 1703.61 0.290905E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1767.86 0.00 1.52 1767.86 0.00 0.00 0.00 0.00 0.37   0.37   0.00 0.00 0.00
Maximum of Months 0.941281E+11 0.00 416.96 0.940337E+11 0.00 0.00 0.00 0.00 183238.71   169657.20   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 483334.78 0.00 0.52 483334.78 0.00 0.00 0.00 0.00 5566.60 24-JAN-05:01 5566.60 24-JAN-05:01 0.00 0.00 0.00
February 0.261761E+09 0.00 5.00 0.261761E+09 0.00 0.00 0.00 0.00 23743.59 27-FEB-15:00 23743.59 27-FEB-15:00 0.00 0.00 0.00
March 10369.74 0.00 0.17 10369.74 0.00 0.00 0.00 0.00 17.28 06-MAR-20:00 17.28 06-MAR-20:00 0.00 0.00 0.00
April 0.231208E+10 0.00 37.08 0.231208E+10 0.00 0.00 0.00 0.00 49353.32 07-APR-14:00 49353.32 07-APR-14:00 0.00 0.00 0.00
May 0.883342E+10 0.00 104.91 0.883342E+10 0.00 0.00 0.00 0.00 70670.19 29-MAY-14:30 70670.19 29-MAY-14:30 0.00 0.00 0.00
June 0.311339E+11 0.00 231.49 0.311222E+11 0.00 0.00 0.00 0.00 67672.65 26-JUN-11:00 67672.65 26-JUN-11:00 0.00 0.00 0.00
July 0.530670E+11 0.00 322.92 0.530396E+11 0.00 0.00 0.00 0.00 109277.90 19-JUL-03:02 84644.13 25-JUL-03:02 0.00 0.00 0.00
August 0.493011E+11 0.00 317.32 0.493011E+11 0.00 0.00 0.00 0.00 107536.15 06-AUG-17:27 107536.15 06-AUG-17:27 0.00 0.00 0.00
September 0.203694E+11 0.00 180.99 0.200026E+11 0.00 0.00 0.00 0.00 123411.10 04-SEP-17:21 123411.10 04-SEP-17:21 0.00 0.00 0.00
October 0.573405E+10 0.00 60.39 0.573405E+10 0.00 0.00 0.00 0.00 59639.08 18-OCT-14:00 59639.08 18-OCT-14:00 0.00 0.00 0.00
November 68497280.37 0.00 4.31 68497280.37 0.00 0.00 0.00 0.00 25354.47 17-NOV-06:03 25354.47 17-NOV-06:03 0.00 0.00 0.00
December 60297.63 0.00 0.33 60297.63 0.00 0.00 0.00 0.00 59.02 27-DEC-17:00 59.02 27-DEC-17:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.171082E+12 0.00 1265.44 0.170676E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 10369.74 0.00 0.17 10369.74 0.00 0.00 0.00 0.00 17.28   17.28   0.00 0.00 0.00
Maximum of Months 0.530670E+11 0.00 322.92 0.530396E+11 0.00 0.00 0.00 0.00 123411.10   123411.10   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.361894E+12 0.918927E+11 744.00 0.328237E+12 0.336571E+11 0.00 0.36 03-JAN-22:02 0.30 09-JAN-07:02 142941.73 18-JAN-22:01 129770.01 02-JAN-22:03 13973.15 18-JAN-22:01 35976.17 03-JAN-22:02 0.00
February 0.575724E+12 0.138529E+12 672.00 0.521962E+12 0.537618E+11 0.00 0.59 27-FEB-16:00 0.54 01-FEB-07:07 245398.86 27-FEB-22:03 222161.37 28-FEB-22:03 23908.55 05-FEB-00:52 66529.05 27-FEB-16:00 0.00
March 0.910631E+12 0.209937E+12 744.00 0.827777E+12 0.828536E+11 0.00 0.98 31-MAR-24:00 0.76 06-MAR-07:07 440819.95 31-MAR-24:00 400344.89 31-MAR-24:00 40475.07 31-MAR-24:00 97766.24 31-MAR-24:00 0.00
April 0.114518E+13 0.261672E+12 720.00 0.104327E+13 0.101913E+12 0.00 1.00 06-APR-09:50 0.39 30-APR-24:00 449692.72 24-APR-21:02 407738.89 06-APR-22:55 44489.66 21-APR-16:00 132528.56 07-APR-14:00 0.00
May 0.375766E+12 0.982215E+11 744.00 0.342794E+12 0.329723E+11 0.00 0.58 31-MAY-23:40 0.33 08-MAY-06:10 238067.17 31-MAY-24:00 217604.10 31-MAY-24:00 20463.07 31-MAY-24:00 59624.41 31-MAY-23:20 0.00
June 0.620352E+12 0.169569E+12 720.00 0.573444E+12 0.469081E+11 0.00 0.80 30-JUN-23:12 0.57 01-JUN-06:10 330249.59 30-JUN-23:02 309564.52 30-JUN-24:00 23537.90 01-JUN-19:00 95949.24 30-JUN-23:12 0.00
July 0.894884E+12 0.267843E+12 744.00 0.842211E+12 0.526731E+11 0.00 1.00 31-JUL-23:03 0.78 08-JUL-06:10 427103.05 31-JUL-24:00 400837.94 31-JUL-23:57 34344.47 05-JUL-09:00 150134.95 17-JUL-16:00 0.00
August 0.116120E+13 0.327110E+12 744.00 0.108112E+13 0.800772E+11 0.00 1.00 01-AUG-00:05 0.41 31-AUG-24:00 456734.48 04-AUG-00:25 412410.78 12-AUG-05:00 47140.61 01-AUG-21:00 167883.90 06-AUG-16:00 0.00
September 0.366935E+12 0.100677E+12 720.00 0.336783E+12 0.301515E+11 0.00 0.57 30-SEP-24:00 0.34 18-SEP-07:00 238748.02 30-SEP-24:00 217328.36 30-SEP-24:00 21419.66 30-SEP-24:00 59175.14 02-SEP-17:00 0.00
October 0.649195E+12 0.158766E+12 744.00 0.590735E+12 0.584605E+11 0.00 0.78 31-OCT-24:00 0.56 10-OCT-06:10 340945.21 31-OCT-24:00 309906.43 31-OCT-24:00 31038.78 31-OCT-24:00 79111.49 18-OCT-15:00 0.00
November 0.889805E+12 0.205448E+12 720.00 0.806754E+12 0.830507E+11 0.00 0.81 17-NOV-17:00 0.77 27-NOV-07:10 349085.01 06-NOV-22:03 315596.37 06-NOV-22:03 34462.23 03-NOV-08:00 89865.99 17-NOV-17:00 0.00
December 0.118267E+13 0.263000E+12 744.00 0.107452E+13 0.108149E+12 0.00 0.99 07-DEC-24:00 0.96 30-DEC-07:10 448631.08 07-DEC-24:00 407061.91 07-DEC-22:03 43514.42 16-DEC-17:00 105040.09 10-DEC-02:00 0.00
                                       
Annual Sum or Average 0.913423E+13 0.229267E+13 8760.00 0.836961E+13 0.764628E+12 0.00                         0.00
Minimum of Months 0.361894E+12 0.918927E+11 672.00 0.328237E+12 0.301515E+11 0.00 0.36   0.30   142941.73   129770.01   13973.15   35976.17   0.00
Maximum of Months 0.118267E+13 0.327110E+12 744.00 0.108112E+13 0.108149E+12 0.00 1.00   0.96   456734.48   412410.78   47140.61   167883.90   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.292943E+10 0.842232E+09 731.18 0.292912E+10 319508.34 0.00 0.27 13-JAN-16:20 0.00 07-JAN-23:22 2213.04 13-JAN-16:20 2213.04 13-JAN-16:20 12.48 02-JAN-07:10 579.60 13-JAN-16:20 0.00
February 0.821852E+10 0.216357E+10 672.00 0.821852E+10 -0.0 0.00 0.58 26-FEB-17:03 0.27 01-FEB-07:03 4835.78 26-FEB-17:14 4835.78 26-FEB-17:14 0.00 17-FEB-06:50 1273.03 27-FEB-16:00 0.00
March 0.149235E+11 0.369842E+10 744.00 0.149235E+11 0.00 0.00 0.81 31-MAR-24:00 0.52 06-MAR-07:03 7458.73 31-MAR-24:00 7458.73 31-MAR-24:00 0.00 14-MAR-16:20 1758.08 31-MAR-24:00 0.00
April 0.200314E+11 0.483299E+10 720.00 0.200239E+11 7423479.97 0.00 1.00 16-APR-17:11 0.30 30-APR-24:00 8875.20 22-APR-18:10 8875.20 22-APR-18:10 128.44 17-APR-16:10 2708.89 07-APR-14:00 0.00
May 0.562191E+10 0.153555E+10 744.00 0.560040E+10 21504642.77 0.00 0.48 31-MAY-24:00 0.14 08-MAY-06:10 4145.25 31-MAY-24:00 4145.25 31-MAY-24:00 137.92 30-MAY-09:10 1075.41 31-MAY-23:30 0.00
June 0.109113E+11 0.304603E+10 720.00 0.108315E+11 79834224.45 0.00 0.68 30-JUN-23:12 0.39 17-JUN-06:40 5989.05 30-JUN-23:12 5989.05 30-JUN-23:12 305.90 06-JUN-16:50 1890.32 29-JUN-15:00 0.00
July 0.165864E+11 0.504171E+10 744.00 0.164977E+11 88748177.02 0.00 0.88 16-JUL-18:55 0.62 08-JUL-06:20 7894.49 31-JUL-23:40 7894.49 31-JUL-23:40 313.64 03-JUL-17:00 3075.87 17-JUL-16:00 0.00
August 0.215881E+11 0.635677E+10 744.00 0.215254E+11 62711067.08 0.00 1.00 03-AUG-18:20 0.31 31-AUG-24:00 8876.31 05-AUG-19:57 8876.31 05-AUG-19:57 369.31 22-AUG-16:00 3631.15 06-AUG-16:00 0.00
September 0.571231E+10 0.161785E+10 720.00 0.563016E+10 82144932.12 0.00 0.45 30-SEP-24:00 0.16 19-SEP-07:00 3952.88 30-SEP-24:00 3952.88 30-SEP-24:00 343.94 07-SEP-15:30 1354.93 04-SEP-17:31 0.00
October 0.105331E+11 0.267977E+10 744.00 0.105225E+11 10577683.61 0.00 0.64 31-OCT-24:00 0.36 10-OCT-06:10 5595.08 31-OCT-24:00 5595.08 31-OCT-24:00 111.27 25-OCT-11:00 1568.18 15-OCT-16:43 0.00
November 0.146199E+11 0.359111E+10 720.00 0.146182E+11 1644586.47 0.00 0.72 13-NOV-16:20 0.53 27-NOV-07:10 6539.94 03-NOV-16:00 6485.12 03-NOV-16:00 84.08 08-NOV-15:20 1662.11 17-NOV-16:50 0.00
December 0.194867E+11 0.472659E+10 744.00 0.194865E+11 197339.12 0.00 0.90 10-DEC-16:05 0.73 29-DEC-07:03 8258.67 10-DEC-16:10 8258.67 10-DEC-16:10 47.84 19-DEC-17:05 1981.65 10-DEC-02:00 0.00
                                       
Annual Sum or Average 0.151163E+12 0.401326E+11 8747.18 0.150808E+12 0.355106E+09 0.00                         0.00
Minimum of Months 0.292943E+10 0.842232E+09 672.00 0.292912E+10 -0.0 0.00 0.27   0.00   2213.04   2213.04   0.00   579.60   0.00
Maximum of Months 0.215881E+11 0.635677E+10 744.00 0.215254E+11 88748177.02 0.00 1.00   0.73   8876.31   8876.31   369.31   3631.15   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.857650E+10 0.267915E+10 485.78 0.857355E+10 2950457.18 0.00 0.23 13-JAN-16:30 0.00 01-JAN-06:13 18216.38 13-JAN-16:30 18216.38 13-JAN-16:30 113.24 01-JAN-15:45 4827.52 13-JAN-16:30 0.00
February 0.591237E+11 0.159221E+11 672.00 0.591237E+11 -0.0 0.00 0.51 24-FEB-17:00 0.12 06-FEB-04:11 42953.71 28-FEB-17:00 42953.71 28-FEB-17:00 0.00 20-FEB-11:17 11558.16 27-FEB-16:00 0.00
March 0.124326E+12 0.312603E+11 744.00 0.124326E+12 0.00 0.00 0.75 31-MAR-23:30 0.37 06-MAR-07:03 65101.25 31-MAR-23:30 65101.25 31-MAR-23:30 0.00 10-MAR-23:20 15535.33 31-MAR-23:30 0.00
April 0.179642E+12 0.437564E+11 720.00 0.179566E+12 75967418.34 0.00 0.99 16-APR-17:51 0.14 30-APR-24:00 82573.71 25-APR-18:00 82573.71 25-APR-18:00 1279.10 17-APR-16:10 25589.72 07-APR-14:00 0.00
May 0.453654E+11 0.125784E+11 744.00 0.451545E+11 0.210900E+09 0.00 0.47 31-MAY-24:00 0.02 08-MAY-06:10 39166.80 31-MAY-24:00 39166.80 31-MAY-24:00 1321.41 30-MAY-09:10 10187.82 31-MAY-23:30 0.00
June 0.100389E+12 0.281921E+11 720.00 0.995931E+11 0.795620E+09 0.00 0.69 30-JUN-23:12 0.34 17-JUN-06:10 58527.79 30-JUN-23:55 58527.79 30-JUN-23:55 2997.84 06-JUN-16:50 17994.60 29-JUN-15:00 0.00
July 0.156653E+12 0.477361E+11 744.00 0.155766E+12 0.887617E+09 0.00 0.89 31-JUL-23:12 0.58 08-JUL-06:30 76788.16 31-JUL-23:53 76788.16 31-JUL-23:53 3079.89 03-JUL-17:00 29290.49 17-JUL-16:00 0.00
August 0.202839E+12 0.599522E+11 744.00 0.202210E+12 0.628492E+09 0.00 1.00 03-AUG-18:30 0.27 31-AUG-24:00 84672.67 03-AUG-18:50 84672.67 03-AUG-18:50 3625.50 22-AUG-16:00 34760.66 06-AUG-16:00 0.00
September 0.480861E+11 0.138244E+11 720.00 0.472823E+11 0.803724E+09 0.00 0.42 04-SEP-17:42 0.10 19-SEP-06:10 34809.25 30-SEP-23:40 34809.25 30-SEP-23:40 3442.26 07-SEP-15:30 12669.00 04-SEP-17:31 0.00
October 0.877275E+11 0.226340E+11 744.00 0.876218E+11 0.105715E+09 0.00 0.58 31-OCT-24:00 0.25 10-OCT-06:10 47518.81 31-OCT-24:00 47518.81 31-OCT-24:00 1088.71 25-OCT-11:00 14603.24 18-OCT-16:00 0.00
November 0.120793E+12 0.301485E+11 720.00 0.120776E+12 17115694.31 0.00 0.68 03-NOV-16:00 0.37 27-NOV-07:10 60246.14 03-NOV-16:00 59699.37 03-NOV-16:00 836.52 08-NOV-15:20 15304.01 17-NOV-17:00 0.00
December 0.158891E+12 0.393130E+11 744.00 0.158888E+12 2820246.17 0.00 0.83 12-DEC-16:00 0.56 31-DEC-23:55 74945.28 06-DEC-16:10 74671.23 06-DEC-16:10 515.32 19-DEC-17:05 17094.54 06-DEC-16:10 0.00
                                       
Annual Sum or Average 0.129241E+13 0.347997E+12 8501.78 0.128888E+13 0.353092E+10 0.00                         0.00
Minimum of Months 0.857650E+10 0.267915E+10 485.78 0.857355E+10 -0.0 0.00 0.23   0.00   18216.38   18216.38   0.00   4827.52   0.00
Maximum of Months 0.202839E+12 0.599522E+11 744.00 0.202210E+12 0.887617E+09 0.00 1.00   0.58   84672.67   84672.67   3625.50   34760.66   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.243203E+09 78608724.00 174.35 0.243203E+09 0.00 0.00 0.22 13-JAN-16:30 0.00 01-JAN-00:05 1723.69 13-JAN-16:30 1723.69 13-JAN-16:30 0.00 24-JAN-15:20 459.70 13-JAN-16:30 0.00
February 0.427161E+10 0.117389E+10 650.05 0.427161E+10 -0.0 0.00 0.49 28-FEB-17:00 0.00 04-FEB-02:42 4244.96 28-FEB-17:00 4244.96 28-FEB-17:00 0.00 21-FEB-03:00 1132.77 27-FEB-16:00 0.00
March 0.107834E+11 0.274816E+10 744.00 0.107834E+11 0.00 0.00 0.71 28-MAR-17:50 0.19 06-MAR-04:03 6162.30 28-MAR-17:50 6162.30 28-MAR-17:50 0.00 02-MAR-06:20 1494.64 28-MAR-17:50 0.00
April 0.167733E+11 0.413232E+10 719.00 0.167658E+11 7470022.72 0.00 0.96 16-APR-17:51 0.00 30-APR-23:05 8322.34 25-APR-18:00 8322.34 25-APR-18:00 126.71 17-APR-16:10 2567.55 07-APR-14:00 0.00
May 0.383926E+10 0.107777E+10 691.18 0.381852E+10 20739497.80 0.00 0.46 31-MAY-23:40 0.00 01-MAY-00:05 3844.10 31-MAY-24:00 3844.10 31-MAY-24:00 127.61 30-MAY-09:20 1005.28 31-MAY-23:20 0.00
June 0.981859E+10 0.277704E+10 720.00 0.973923E+10 79363723.30 0.00 0.68 30-JUN-23:12 0.25 17-JUN-06:10 5863.59 30-JUN-23:55 5863.59 30-JUN-23:55 302.13 06-JUN-16:50 1840.37 29-JUN-15:00 0.00
July 0.156086E+11 0.477948E+10 744.00 0.155200E+11 88595047.62 0.00 0.90 16-JUL-18:55 0.53 08-JUL-06:40 7643.11 31-JUL-23:53 7643.11 31-JUL-23:53 308.76 03-JUL-17:00 2996.88 17-JUL-16:00 0.00
August 0.201452E+11 0.598609E+10 744.00 0.200825E+11 62694564.17 0.00 1.00 04-AUG-17:30 0.26 31-AUG-24:00 8604.14 05-AUG-19:53 8604.14 05-AUG-19:53 363.81 22-AUG-16:00 3538.92 06-AUG-16:00 0.00
September 0.424334E+10 0.124454E+10 718.36 0.416419E+10 79154891.55 0.00 0.44 04-SEP-17:21 0.00 12-SEP-03:25 3367.31 04-SEP-17:32 3367.31 04-SEP-17:32 346.95 07-SEP-15:30 1365.28 04-SEP-17:21 0.00
October 0.736129E+10 0.193234E+10 743.78 0.735096E+10 10334594.73 0.00 0.56 18-OCT-16:50 0.00 10-OCT-02:55 4584.13 18-OCT-16:50 4584.13 18-OCT-16:50 107.76 25-OCT-11:00 1471.31 18-OCT-16:00 0.00
November 0.101784E+11 0.258401E+10 720.00 0.101767E+11 1666974.25 0.00 0.67 03-NOV-16:00 0.19 27-NOV-04:12 5951.50 03-NOV-16:00 5896.96 03-NOV-16:00 82.80 08-NOV-15:20 1506.88 17-NOV-16:50 0.00
December 0.138504E+11 0.348254E+10 744.00 0.138502E+11 242074.50 0.00 0.80 06-DEC-16:10 0.40 31-DEC-23:55 7397.97 06-DEC-16:10 7372.79 06-DEC-16:10 48.49 19-DEC-17:05 1694.22 06-DEC-16:10 0.00
                                       
Annual Sum or Average 0.117117E+12 0.319968E+11 8112.72 0.116766E+12 0.350261E+09 0.00                         0.00
Minimum of Months 0.243203E+09 78608724.00 174.35 0.243203E+09 -0.0 0.00 0.22   0.00   1723.69   1723.69   0.00   459.70   0.00
Maximum of Months 0.201452E+11 0.598609E+10 744.00 0.200825E+11 88595047.62 0.00 1.00   0.53   8604.14   8604.14   363.81   3538.92   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 90.40 0.00 90.40 1.50 793.07 0.00 0.00 0.00
February 127.65 0.00 127.65 15.59 597.73 0.00 0.00 0.00
March 207.35 0.00 207.35 62.53 487.21 0.00 0.00 0.00
April 236.43 1.38 235.05 115.41 350.04 0.00 0.00 0.00
May 310.49 18.40 292.09 225.36 252.82 0.00 0.00 0.00
June 361.54 41.56 319.99 366.57 158.44 0.00 0.00 0.00
July 330.29 30.94 299.35 398.37 130.42 0.00 0.00 0.00
August 264.66 7.09 257.57 288.14 150.85 0.00 0.00 0.00
September 198.21 0.07 198.14 167.43 234.60 0.00 0.00 0.00
October 144.59 0.00 144.59 58.40 360.06 0.00 0.00 0.00
November 98.29 0.00 98.29 11.55 521.78 0.00 0.00 0.00
December 75.81 0.00 75.81 0.49 707.77 0.00 0.00 0.00
                 
Annual Sum or Average 204.22 8.33 195.89 143.41 394.60 0.00 0.00 0.00
Minimum of Months 75.81 0.00 75.81 0.49 130.42 0.00 0.00 0.00
Maximum of Months 361.54 41.56 319.99 398.37 793.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 90.40 0.00 90.40 1.50 793.07 0.00 0.00 0.00
February 127.64 0.00 127.64 15.59 597.73 0.00 0.00 0.00
March 207.35 0.00 207.35 62.53 487.21 0.00 0.00 0.00
April 236.42 1.38 235.04 115.41 350.04 0.00 0.00 0.00
May 310.48 18.40 292.08 225.36 252.82 0.00 0.00 0.00
June 361.54 41.56 319.98 366.56 158.44 0.00 0.00 0.00
July 330.29 30.93 299.35 398.37 130.42 0.00 0.00 0.00
August 264.66 7.09 257.57 288.14 150.85 0.00 0.00 0.00
September 198.21 0.07 198.14 167.43 234.60 0.00 0.00 0.00
October 144.58 0.00 144.58 58.40 360.06 0.00 0.00 0.00
November 98.29 0.00 98.29 11.55 521.78 0.00 0.00 0.00
December 75.81 0.00 75.81 0.49 707.77 0.00 0.00 0.00
                 
Annual Sum or Average 204.22 8.33 195.89 143.41 394.60 0.00 0.00 0.00
Minimum of Months 75.81 0.00 75.81 0.49 130.42 0.00 0.00 0.00
Maximum of Months 361.54 41.56 319.98 398.37 793.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 90.40 0.00 90.40 1.50 793.07 0.00 0.00 0.00
February 127.64 0.00 127.64 15.59 597.73 0.00 0.00 0.00
March 207.35 0.00 207.35 62.53 487.21 0.00 0.00 0.00
April 236.43 1.38 235.05 115.41 350.04 0.00 0.00 0.00
May 310.48 18.40 292.08 225.36 252.82 0.00 0.00 0.00
June 361.54 41.56 319.98 366.57 158.44 0.00 0.00 0.00
July 330.29 30.93 299.35 398.37 130.42 0.00 0.00 0.00
August 264.66 7.09 257.57 288.14 150.85 0.00 0.00 0.00
September 198.21 0.07 198.14 167.43 234.60 0.00 0.00 0.00
October 144.58 0.00 144.58 58.40 360.06 0.00 0.00 0.00
November 98.29 0.00 98.29 11.55 521.78 0.00 0.00 0.00
December 75.81 0.00 75.81 0.49 707.77 0.00 0.00 0.00
                 
Annual Sum or Average 204.22 8.33 195.89 143.41 394.60 0.00 0.00 0.00
Minimum of Months 75.81 0.00 75.81 0.49 130.42 0.00 0.00 0.00
Maximum of Months 361.54 41.56 319.98 398.37 793.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 90.40 0.00 90.40 1.50 793.07 0.00 0.00 0.00
February 127.64 0.00 127.64 15.59 597.73 0.00 0.00 0.00
March 207.35 0.00 207.35 62.53 487.21 0.00 0.00 0.00
April 236.42 1.38 235.04 115.41 350.04 0.00 0.00 0.00
May 310.48 18.40 292.08 225.36 252.82 0.00 0.00 0.00
June 361.54 41.56 319.98 366.56 158.44 0.00 0.00 0.00
July 330.29 30.93 299.35 398.37 130.42 0.00 0.00 0.00
August 264.66 7.09 257.57 288.14 150.85 0.00 0.00 0.00
September 198.21 0.07 198.14 167.43 234.60 0.00 0.00 0.00
October 144.58 0.00 144.58 58.40 360.06 0.00 0.00 0.00
November 98.29 0.00 98.29 11.55 521.78 0.00 0.00 0.00
December 75.81 0.00 75.81 0.49 707.77 0.00 0.00 0.00
                 
Annual Sum or Average 204.22 8.33 195.89 143.41 394.60 0.00 0.00 0.00
Minimum of Months 75.81 0.00 75.81 0.49 130.42 0.00 0.00 0.00
Maximum of Months 361.54 41.56 319.98 398.37 793.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 90.40 0.00 90.40 1.50 793.04 0.00 0.00 0.00
February 127.64 0.00 127.64 15.59 597.71 0.00 0.00 0.00
March 207.34 0.00 207.34 62.52 487.19 0.00 0.00 0.00
April 236.41 1.38 235.04 115.40 350.02 0.00 0.00 0.00
May 310.47 18.40 292.07 225.35 252.81 0.00 0.00 0.00
June 361.52 41.55 319.97 366.55 158.43 0.00 0.00 0.00
July 330.27 30.93 299.34 398.35 130.41 0.00 0.00 0.00
August 264.65 7.09 257.56 288.13 150.85 0.00 0.00 0.00
September 198.20 0.07 198.13 167.42 234.59 0.00 0.00 0.00
October 144.58 0.00 144.58 58.39 360.05 0.00 0.00 0.00
November 98.29 0.00 98.29 11.55 521.76 0.00 0.00 0.00
December 75.80 0.00 75.80 0.49 707.74 0.00 0.00 0.00
                 
Annual Sum or Average 204.21 8.33 195.88 143.40 394.59 0.00 0.00 0.00
Minimum of Months 75.80 0.00 75.80 0.49 130.41 0.00 0.00 0.00
Maximum of Months 361.52 41.55 319.97 398.35 793.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 230.66 105.75 124.91 118.69 803.80 0.00 0.00 0.00
February 360.77 179.11 181.66 264.04 600.52 0.00 0.00 0.00
March 485.09 200.72 284.37 389.87 496.05 0.00 0.00 0.00
April 618.92 306.73 312.19 595.09 356.61 0.00 0.00 0.00
May 683.68 304.20 379.49 708.16 277.59 0.00 0.00 0.00
June 884.94 455.39 429.55 1057.90 175.42 0.00 0.00 0.00
July 928.77 525.06 403.71 1198.16 138.42 0.00 0.00 0.00
August 807.14 449.71 357.43 1017.44 154.66 0.00 0.00 0.00
September 570.97 294.73 276.24 651.46 239.63 0.00 0.00 0.00
October 409.64 208.01 201.63 383.68 363.81 0.00 0.00 0.00
November 259.62 121.21 138.41 174.00 512.16 0.00 0.00 0.00
December 191.49 82.24 109.24 91.05 703.86 0.00 0.00 0.00
                 
Annual Sum or Average 536.89 269.87 267.02 555.79 401.13 0.00 0.00 0.00
Minimum of Months 191.49 82.24 109.24 91.05 138.42 0.00 0.00 0.00
Maximum of Months 928.77 525.06 429.55 1198.16 803.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 230.66 105.75 124.91 118.69 803.80 0.00 0.00 0.00
February 360.77 179.11 181.66 264.04 600.52 0.00 0.00 0.00
March 485.09 200.72 284.37 389.87 496.05 0.00 0.00 0.00
April 618.92 306.73 312.19 595.09 356.61 0.00 0.00 0.00
May 683.68 304.20 379.49 708.16 277.59 0.00 0.00 0.00
June 884.94 455.39 429.55 1057.90 175.42 0.00 0.00 0.00
July 928.77 525.06 403.71 1198.16 138.42 0.00 0.00 0.00
August 807.14 449.71 357.43 1017.44 154.66 0.00 0.00 0.00
September 570.97 294.73 276.24 651.46 239.63 0.00 0.00 0.00
October 409.64 208.01 201.63 383.68 363.81 0.00 0.00 0.00
November 259.62 121.21 138.41 174.00 512.16 0.00 0.00 0.00
December 191.49 82.24 109.24 91.05 703.86 0.00 0.00 0.00
                 
Annual Sum or Average 536.89 269.87 267.02 555.79 401.13 0.00 0.00 0.00
Minimum of Months 191.49 82.24 109.24 91.05 138.42 0.00 0.00 0.00
Maximum of Months 928.77 525.06 429.55 1198.16 803.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 230.65 105.75 124.91 118.69 803.79 0.00 0.00 0.00
February 360.76 179.11 181.65 264.03 600.51 0.00 0.00 0.00
March 485.08 200.71 284.37 389.86 496.04 0.00 0.00 0.00
April 618.91 306.73 312.18 595.08 356.61 0.00 0.00 0.00
May 683.67 304.19 379.48 708.14 277.59 0.00 0.00 0.00
June 884.92 455.38 429.54 1057.88 175.42 0.00 0.00 0.00
July 928.75 525.05 403.70 1198.14 138.42 0.00 0.00 0.00
August 807.13 449.71 357.42 1017.42 154.66 0.00 0.00 0.00
September 570.96 294.73 276.23 651.45 239.63 0.00 0.00 0.00
October 409.64 208.01 201.63 383.67 363.80 0.00 0.00 0.00
November 259.62 121.21 138.41 173.99 512.16 0.00 0.00 0.00
December 191.48 82.24 109.24 91.05 703.85 0.00 0.00 0.00
                 
Annual Sum or Average 536.88 269.87 267.02 555.78 401.13 0.00 0.00 0.00
Minimum of Months 191.48 82.24 109.24 91.05 138.42 0.00 0.00 0.00
Maximum of Months 928.75 525.05 429.54 1198.14 803.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 637.24 455.13 182.11 591.53 665.66 0.00 0.00 0.00
February 811.51 583.67 227.84 828.78 508.27 0.00 0.00 0.00
March 725.39 407.34 318.04 738.23 456.65 0.00 0.00 0.00
April 583.09 278.89 304.20 615.76 343.50 0.00 0.00 0.00
May 518.06 172.06 346.00 559.33 266.06 0.00 0.00 0.00
June 514.75 150.12 364.62 635.26 179.63 0.00 0.00 0.00
July 554.95 204.99 349.95 763.69 141.06 0.00 0.00 0.00
August 659.52 332.52 327.00 879.82 159.63 0.00 0.00 0.00
September 731.48 448.20 283.28 905.82 232.31 0.00 0.00 0.00
October 764.73 528.80 235.93 866.18 333.74 0.00 0.00 0.00
November 697.20 505.03 192.18 717.12 434.32 0.00 0.00 0.00
December 605.98 437.58 168.40 572.04 581.86 0.00 0.00 0.00
                 
Annual Sum or Average 649.20 373.97 275.23 721.97 358.00 0.00 0.00 0.00
Minimum of Months 514.75 150.12 168.40 559.33 141.06 0.00 0.00 0.00
Maximum of Months 811.51 583.67 364.62 905.82 665.66 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 637.23 455.12 182.11 591.53 665.66 0.00 0.00 0.00
February 811.51 583.66 227.84 828.78 508.27 0.00 0.00 0.00
March 725.38 407.34 318.04 738.22 456.65 0.00 0.00 0.00
April 583.09 278.89 304.19 615.76 343.50 0.00 0.00 0.00
May 518.06 172.06 346.00 559.33 266.06 0.00 0.00 0.00
June 514.74 150.12 364.62 635.25 179.63 0.00 0.00 0.00
July 554.95 204.99 349.95 763.69 141.06 0.00 0.00 0.00
August 659.51 332.51 327.00 879.81 159.63 0.00 0.00 0.00
September 731.48 448.20 283.28 905.81 232.31 0.00 0.00 0.00
October 764.72 528.79 235.93 866.17 333.74 0.00 0.00 0.00
November 697.20 505.02 192.18 717.11 434.32 0.00 0.00 0.00
December 605.97 437.57 168.40 572.03 581.86 0.00 0.00 0.00
                 
Annual Sum or Average 649.20 373.97 275.23 721.97 358.00 0.00 0.00 0.00
Minimum of Months 514.74 150.12 168.40 559.33 141.06 0.00 0.00 0.00
Maximum of Months 811.51 583.66 364.62 905.81 665.66 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 637.24 455.13 182.11 591.53 665.66 0.00 0.00 0.00
February 811.51 583.67 227.84 828.78 508.27 0.00 0.00 0.00
March 725.39 407.34 318.04 738.23 456.65 0.00 0.00 0.00
April 583.09 278.89 304.20 615.76 343.50 0.00 0.00 0.00
May 518.06 172.06 346.00 559.33 266.06 0.00 0.00 0.00
June 514.75 150.12 364.62 635.26 179.63 0.00 0.00 0.00
July 554.95 204.99 349.95 763.69 141.06 0.00 0.00 0.00
August 659.52 332.52 327.00 879.82 159.63 0.00 0.00 0.00
September 731.48 448.20 283.28 905.82 232.31 0.00 0.00 0.00
October 764.73 528.80 235.93 866.18 333.74 0.00 0.00 0.00
November 697.20 505.03 192.18 717.12 434.32 0.00 0.00 0.00
December 605.98 437.58 168.40 572.04 581.86 0.00 0.00 0.00
                 
Annual Sum or Average 649.20 373.97 275.23 721.97 358.00 0.00 0.00 0.00
Minimum of Months 514.75 150.12 168.40 559.33 141.06 0.00 0.00 0.00
Maximum of Months 811.51 583.67 364.62 905.82 665.66 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 637.23 455.12 182.11 591.53 665.66 0.00 0.00 0.00
February 811.51 583.66 227.84 828.78 508.27 0.00 0.00 0.00
March 725.38 407.34 318.04 738.22 456.65 0.00 0.00 0.00
April 583.09 278.89 304.19 615.76 343.50 0.00 0.00 0.00
May 518.06 172.06 346.00 559.33 266.06 0.00 0.00 0.00
June 514.74 150.12 364.62 635.25 179.63 0.00 0.00 0.00
July 554.95 204.99 349.95 763.69 141.06 0.00 0.00 0.00
August 659.51 332.51 327.00 879.81 159.63 0.00 0.00 0.00
September 731.48 448.20 283.28 905.81 232.31 0.00 0.00 0.00
October 764.72 528.79 235.93 866.17 333.74 0.00 0.00 0.00
November 697.20 505.02 192.18 717.11 434.32 0.00 0.00 0.00
December 605.97 437.57 168.40 572.03 581.86 0.00 0.00 0.00
                 
Annual Sum or Average 649.20 373.97 275.23 721.97 358.00 0.00 0.00 0.00
Minimum of Months 514.74 150.12 168.40 559.33 141.06 0.00 0.00 0.00
Maximum of Months 811.51 583.66 364.62 905.81 665.66 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 637.21 455.11 182.10 591.51 665.63 0.00 0.00 0.00
February 811.48 583.64 227.83 828.75 508.25 0.00 0.00 0.00
March 725.35 407.32 318.03 738.20 456.63 0.00 0.00 0.00
April 583.06 278.88 304.18 615.74 343.49 0.00 0.00 0.00
May 518.04 172.05 345.99 559.31 266.05 0.00 0.00 0.00
June 514.72 150.12 364.61 635.23 179.63 0.00 0.00 0.00
July 554.92 204.99 349.94 763.66 141.06 0.00 0.00 0.00
August 659.49 332.50 326.99 879.78 159.62 0.00 0.00 0.00
September 731.45 448.18 283.27 905.78 232.30 0.00 0.00 0.00
October 764.69 528.77 235.92 866.14 333.73 0.00 0.00 0.00
November 697.17 505.00 192.17 717.09 434.30 0.00 0.00 0.00
December 605.95 437.56 168.39 572.01 581.84 0.00 0.00 0.00
                 
Annual Sum or Average 649.18 373.96 275.22 721.94 357.98 0.00 0.00 0.00
Minimum of Months 514.72 150.12 168.39 559.31 141.06 0.00 0.00 0.00
Maximum of Months 811.48 583.64 364.61 905.78 665.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 208.93 84.20 124.73 102.51 863.49 0.00 0.00 0.00
February 356.61 175.29 181.32 259.88 655.07 0.00 0.00 0.00
March 456.37 167.22 289.15 345.33 564.47 0.00 0.00 0.00
April 595.79 263.96 331.83 557.81 428.71 0.00 0.00 0.00
May 736.96 336.09 400.86 778.40 312.85 0.00 0.00 0.00
June 801.78 368.29 433.49 947.17 214.94 0.00 0.00 0.00
July 821.33 415.03 406.30 1052.76 180.14 0.00 0.00 0.00
August 697.42 342.28 355.14 863.05 202.99 0.00 0.00 0.00
September 561.03 283.64 277.40 643.34 274.75 0.00 0.00 0.00
October 400.98 199.23 201.76 374.99 417.42 0.00 0.00 0.00
November 283.86 140.82 143.04 207.70 584.85 0.00 0.00 0.00
December 190.81 80.53 110.27 91.45 795.52 0.00 0.00 0.00
                 
Annual Sum or Average 510.02 238.28 271.74 520.06 457.21 0.00 0.00 0.00
Minimum of Months 190.81 80.53 110.27 91.45 180.14 0.00 0.00 0.00
Maximum of Months 821.33 415.03 433.49 1052.76 863.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 208.93 84.20 124.73 102.51 863.49 0.00 0.00 0.00
February 356.61 175.29 181.32 259.88 655.07 0.00 0.00 0.00
March 456.37 167.22 289.15 345.33 564.47 0.00 0.00 0.00
April 595.79 263.96 331.83 557.81 428.71 0.00 0.00 0.00
May 736.96 336.09 400.86 778.40 312.85 0.00 0.00 0.00
June 801.78 368.29 433.49 947.17 214.94 0.00 0.00 0.00
July 821.33 415.03 406.30 1052.76 180.14 0.00 0.00 0.00
August 697.42 342.28 355.14 863.05 202.99 0.00 0.00 0.00
September 561.03 283.64 277.40 643.34 274.75 0.00 0.00 0.00
October 400.98 199.23 201.76 374.99 417.42 0.00 0.00 0.00
November 283.86 140.82 143.04 207.70 584.85 0.00 0.00 0.00
December 190.81 80.53 110.27 91.45 795.52 0.00 0.00 0.00
                 
Annual Sum or Average 510.02 238.28 271.74 520.06 457.21 0.00 0.00 0.00
Minimum of Months 190.81 80.53 110.27 91.45 180.14 0.00 0.00 0.00
Maximum of Months 821.33 415.03 433.49 1052.76 863.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 208.92 84.20 124.73 102.50 863.47 0.00 0.00 0.00
February 356.60 175.29 181.31 259.87 655.06 0.00 0.00 0.00
March 456.36 167.22 289.14 345.32 564.46 0.00 0.00 0.00
April 595.78 263.96 331.82 557.80 428.71 0.00 0.00 0.00
May 736.94 336.09 400.86 778.39 312.85 0.00 0.00 0.00
June 801.76 368.28 433.48 947.15 214.93 0.00 0.00 0.00
July 821.32 415.02 406.29 1052.74 180.14 0.00 0.00 0.00
August 697.41 342.27 355.14 863.03 202.99 0.00 0.00 0.00
September 561.02 283.63 277.39 643.33 274.75 0.00 0.00 0.00
October 400.98 199.22 201.75 374.99 417.41 0.00 0.00 0.00
November 283.85 140.82 143.04 207.69 584.84 0.00 0.00 0.00
December 190.80 80.53 110.27 91.45 795.50 0.00 0.00 0.00
                 
Annual Sum or Average 510.01 238.27 271.73 520.05 457.21 0.00 0.00 0.00
Minimum of Months 190.80 80.53 110.27 91.45 180.14 0.00 0.00 0.00
Maximum of Months 821.32 415.02 433.48 1052.74 863.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 452.02 0.00 452.02 15.63 3731.01 0.00 0.00 0.00
February 638.23 0.00 638.23 118.93 2750.25 0.00 0.00 0.00
March 1036.77 0.00 1036.77 380.09 2214.13 0.00 0.00 0.00
April 1182.14 6.90 1175.24 645.80 1570.63 0.00 0.00 0.00
May 1552.43 91.99 1460.44 1171.77 1171.82 0.00 0.00 0.00
June 1807.72 207.78 1599.93 1857.11 759.29 0.00 0.00 0.00
July 1651.45 154.68 1496.77 2013.80 633.73 0.00 0.00 0.00
August 1323.31 35.47 1287.84 1466.98 723.54 0.00 0.00 0.00
September 991.07 0.36 990.71 867.83 1091.94 0.00 0.00 0.00
October 722.93 0.00 722.93 345.89 1612.59 0.00 0.00 0.00
November 491.45 0.00 491.45 85.80 2309.03 0.00 0.00 0.00
December 379.05 0.00 379.05 8.28 3179.77 0.00 0.00 0.00
                 
Annual Sum or Average 1021.09 41.64 979.45 752.06 1808.76 0.00 0.00 0.00
Minimum of Months 379.05 0.00 379.05 8.28 633.73 0.00 0.00 0.00
Maximum of Months 1807.72 207.78 1599.93 2013.80 3731.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 691.97 317.24 374.73 372.00 2293.42 0.00 0.00 0.00
February 1082.30 537.34 544.96 820.42 1690.96 0.00 0.00 0.00
March 1455.25 602.14 853.11 1198.32 1394.39 0.00 0.00 0.00
April 1856.76 920.19 936.56 1802.15 1004.63 0.00 0.00 0.00
May 2051.03 912.58 1138.45 2132.25 783.58 0.00 0.00 0.00
June 2654.79 1366.15 1288.64 3163.32 516.02 0.00 0.00 0.00
July 2786.28 1575.16 1211.12 3578.93 422.59 0.00 0.00 0.00
August 2421.40 1349.13 1072.27 3038.28 475.49 0.00 0.00 0.00
September 1712.90 884.19 828.71 1958.30 684.67 0.00 0.00 0.00
October 1228.92 624.03 604.89 1176.39 1009.63 0.00 0.00 0.00
November 778.86 363.63 415.24 548.89 1409.87 0.00 0.00 0.00
December 574.46 246.73 327.73 293.16 1951.03 0.00 0.00 0.00
                 
Annual Sum or Average 1610.66 809.61 801.05 1678.41 1134.35 0.00 0.00 0.00
Minimum of Months 574.46 246.73 327.73 293.16 422.59 0.00 0.00 0.00
Maximum of Months 2786.28 1575.16 1288.64 3578.93 2293.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3186.24 2275.68 910.56 2955.62 3254.46 0.00 0.00 0.00
February 4057.63 2918.40 1139.23 4135.80 2460.93 0.00 0.00 0.00
March 3627.00 2036.75 1590.24 3686.92 2200.42 0.00 0.00 0.00
April 2915.50 1394.50 1521.00 3082.21 1639.69 0.00 0.00 0.00
May 2590.34 860.32 1730.02 2794.20 1281.27 0.00 0.00 0.00
June 2573.77 750.63 1823.13 3174.12 875.44 0.00 0.00 0.00
July 2774.78 1025.00 1749.79 3814.63 700.60 0.00 0.00 0.00
August 3297.64 1662.61 1635.03 4389.02 794.49 0.00 0.00 0.00
September 3657.48 2241.06 1416.43 4502.97 1136.37 0.00 0.00 0.00
October 3823.70 2644.04 1179.66 4316.23 1612.24 0.00 0.00 0.00
November 3486.08 2525.18 960.91 3591.19 2080.04 0.00 0.00 0.00
December 3029.94 2187.92 842.02 2884.94 2766.09 0.00 0.00 0.00
                 
Annual Sum or Average 3246.08 1869.91 1376.16 3606.59 1730.82 0.00 0.00 0.00
Minimum of Months 2573.77 750.63 842.02 2794.20 700.60 0.00 0.00 0.00
Maximum of Months 4057.63 2918.40 1823.13 4502.97 3254.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 626.78 252.60 374.18 322.02 2420.90 0.00 0.00 0.00
February 1069.81 525.87 543.95 823.15 1769.49 0.00 0.00 0.00
March 1369.10 501.66 867.44 1099.23 1487.11 0.00 0.00 0.00
April 1787.37 791.89 995.48 1746.76 1096.24 0.00 0.00 0.00
May 2210.84 1008.26 1202.58 2364.57 861.61 0.00 0.00 0.00
June 2405.31 1104.85 1300.46 2874.72 593.67 0.00 0.00 0.00
July 2463.98 1245.08 1218.89 3193.82 498.88 0.00 0.00 0.00
August 2092.25 1026.83 1065.42 2639.25 538.33 0.00 0.00 0.00
September 1683.08 850.90 832.18 1956.64 754.32 0.00 0.00 0.00
October 1202.94 597.68 605.26 1177.93 1091.93 0.00 0.00 0.00
November 851.57 422.45 429.12 672.06 1501.35 0.00 0.00 0.00
December 572.41 241.60 330.81 309.12 2048.62 0.00 0.00 0.00
                 
Annual Sum or Average 1530.03 714.83 815.21 1602.30 1219.95 0.00 0.00 0.00
Minimum of Months 572.41 241.60 330.81 309.12 498.88 0.00 0.00 0.00
Maximum of Months 2463.98 1245.08 1300.46 3193.82 2420.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 452.02 0.00 452.02 22.12 3598.48 0.00 0.00 0.00
February 638.23 0.00 638.23 141.17 2618.94 0.00 0.00 0.00
March 1036.77 0.00 1036.77 416.00 2082.47 0.00 0.00 0.00
April 1182.14 6.90 1175.24 697.53 1445.79 0.00 0.00 0.00
May 1552.43 91.99 1460.44 1211.51 1093.97 0.00 0.00 0.00
June 1807.72 207.78 1599.93 1876.32 732.54 0.00 0.00 0.00
July 1651.45 154.68 1496.77 2018.11 621.30 0.00 0.00 0.00
August 1323.31 35.47 1287.84 1477.13 698.19 0.00 0.00 0.00
September 991.07 0.36 990.71 896.32 1018.79 0.00 0.00 0.00
October 722.93 0.00 722.93 394.75 1462.36 0.00 0.00 0.00
November 491.45 0.00 491.45 105.76 2131.69 0.00 0.00 0.00
December 379.05 0.00 379.05 10.75 3037.83 0.00 0.00 0.00
                 
Annual Sum or Average 1021.09 41.64 979.45 776.14 1708.57 0.00 0.00 0.00
Minimum of Months 379.05 0.00 379.05 10.75 621.30 0.00 0.00 0.00
Maximum of Months 1807.72 207.78 1599.93 2018.11 3598.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 691.97 317.24 374.73 384.08 2212.40 0.00 0.00 0.00
February 1082.30 537.34 544.96 844.91 1612.39 0.00 0.00 0.00
March 1455.25 602.14 853.11 1226.41 1317.90 0.00 0.00 0.00
April 1856.76 920.19 936.56 1828.68 939.32 0.00 0.00 0.00
May 2051.03 912.58 1138.45 2144.57 743.14 0.00 0.00 0.00
June 2654.79 1366.15 1288.64 3161.46 507.17 0.00 0.00 0.00
July 2786.28 1575.16 1211.12 3570.43 421.20 0.00 0.00 0.00
August 2421.40 1349.13 1072.27 3033.03 469.25 0.00 0.00 0.00
September 1712.90 884.19 828.71 1966.01 655.69 0.00 0.00 0.00
October 1228.92 624.03 604.89 1209.20 931.08 0.00 0.00 0.00
November 778.86 363.63 415.24 574.42 1308.33 0.00 0.00 0.00
December 574.46 246.73 327.73 304.00 1864.53 0.00 0.00 0.00
                 
Annual Sum or Average 1610.66 809.61 801.05 1692.05 1080.02 0.00 0.00 0.00
Minimum of Months 574.46 246.73 327.73 304.00 421.20 0.00 0.00 0.00
Maximum of Months 2786.28 1575.16 1288.64 3570.43 2212.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3186.24 2275.68 910.56 2994.04 3113.04 0.00 0.00 0.00
February 4057.63 2918.40 1139.23 4180.14 2328.42 0.00 0.00 0.00
March 3627.00 2036.75 1590.24 3724.64 2072.31 0.00 0.00 0.00
April 2915.50 1394.50 1521.00 3118.71 1527.97 0.00 0.00 0.00
May 2590.34 860.32 1730.02 2812.84 1209.30 0.00 0.00 0.00
June 2573.77 750.63 1823.13 3176.65 851.08 0.00 0.00 0.00
July 2774.78 1025.00 1749.79 3808.16 691.10 0.00 0.00 0.00
August 3297.64 1662.61 1635.03 4383.62 777.19 0.00 0.00 0.00
September 3657.48 2241.06 1416.43 4511.98 1083.13 0.00 0.00 0.00
October 3823.70 2644.04 1179.66 4356.22 1488.10 0.00 0.00 0.00
November 3486.08 2525.18 960.91 3649.54 1921.70 0.00 0.00 0.00
December 3029.94 2187.92 842.02 2926.35 2624.44 0.00 0.00 0.00
                 
Annual Sum or Average 3246.08 1869.91 1376.16 3632.69 1638.22 0.00 0.00 0.00
Minimum of Months 2573.77 750.63 842.02 2812.84 691.10 0.00 0.00 0.00
Maximum of Months 4057.63 2918.40 1823.13 4511.98 3113.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 626.78 252.60 374.18 330.37 2336.46 0.00 0.00 0.00
February 1069.81 525.87 543.95 837.47 1692.28 0.00 0.00 0.00
March 1369.10 501.66 867.44 1114.95 1413.68 0.00 0.00 0.00
April 1787.37 791.89 995.48 1766.80 1031.07 0.00 0.00 0.00
May 2210.84 1008.26 1202.58 2374.14 817.99 0.00 0.00 0.00
June 2405.31 1104.85 1300.46 2874.94 579.68 0.00 0.00 0.00
July 2463.98 1245.08 1218.89 3189.73 493.20 0.00 0.00 0.00
August 2092.25 1026.83 1065.42 2638.29 527.48 0.00 0.00 0.00
September 1683.08 850.90 832.18 1963.24 721.00 0.00 0.00 0.00
October 1202.94 597.68 605.26 1198.84 1015.93 0.00 0.00 0.00
November 851.57 422.45 429.12 688.64 1405.12 0.00 0.00 0.00
December 572.41 241.60 330.81 316.23 1965.12 0.00 0.00 0.00
                 
Annual Sum or Average 1530.03 714.83 815.21 1611.77 1164.81 0.00 0.00 0.00
Minimum of Months 572.41 241.60 330.81 316.23 493.20 0.00 0.00 0.00
Maximum of Months 2463.98 1245.08 1300.46 3189.73 2336.46 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.242139E+09 0.00 0.242139E+09 4019776.27 0.212416E+10
February 0.308799E+09 0.00 0.308799E+09 37717438.67 0.144603E+10
March 0.555376E+09 0.00 0.555376E+09 0.167477E+09 0.130495E+10
April 0.612820E+09 3576254.47 0.609243E+09 0.299147E+09 0.907298E+09
May 0.831604E+09 49277394.08 0.782327E+09 0.603605E+09 0.677141E+09
June 0.937120E+09 0.107713E+09 0.829407E+09 0.950152E+09 0.410666E+09
July 0.884648E+09 82857303.69 0.801791E+09 0.106700E+10 0.349312E+09
August 0.708873E+09 19000970.75 0.689872E+09 0.771757E+09 0.404050E+09
September 0.513771E+09 184367.60 0.513587E+09 0.433988E+09 0.608081E+09
October 0.387258E+09 0.00 0.387258E+09 0.156413E+09 0.964389E+09
November 0.254769E+09 0.00 0.254769E+09 29944615.62 0.135246E+10
December 0.203047E+09 0.00 0.203047E+09 1321142.19 0.189569E+10
           
Annual Sum or Average 0.644022E+10 0.262610E+09 0.617761E+10 0.452254E+10 0.124442E+11
Minimum of Months 0.203047E+09 0.00 0.203047E+09 1321142.19 0.349312E+09
Maximum of Months 0.937120E+09 0.107713E+09 0.829407E+09 0.106700E+10 0.212416E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.242135E+09 0.00 0.242135E+09 4019392.08 0.212416E+10
February 0.308795E+09 0.00 0.308795E+09 37715617.64 0.144603E+10
March 0.555368E+09 0.00 0.555368E+09 0.167470E+09 0.130495E+10
April 0.612811E+09 3576175.85 0.609235E+09 0.299140E+09 0.907299E+09
May 0.831592E+09 49276310.77 0.782316E+09 0.603591E+09 0.677142E+09
June 0.937106E+09 0.107711E+09 0.829396E+09 0.950135E+09 0.410665E+09
July 0.884636E+09 82855482.17 0.801781E+09 0.106699E+10 0.349311E+09
August 0.708864E+09 19000553.03 0.689863E+09 0.771747E+09 0.404049E+09
September 0.513764E+09 184363.55 0.513580E+09 0.433981E+09 0.608080E+09
October 0.387253E+09 0.00 0.387253E+09 0.156408E+09 0.964388E+09
November 0.254766E+09 0.00 0.254766E+09 29943097.09 0.135246E+10
December 0.203044E+09 0.00 0.203044E+09 1320974.89 0.189569E+10
           
Annual Sum or Average 0.644013E+10 0.262604E+09 0.617753E+10 0.452246E+10 0.124442E+11
Minimum of Months 0.203044E+09 0.00 0.203044E+09 1320974.89 0.349311E+09
Maximum of Months 0.937106E+09 0.107711E+09 0.829396E+09 0.106699E+10 0.212416E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.242136E+09 0.00 0.242136E+09 4019520.15 0.212416E+10
February 0.308796E+09 0.00 0.308796E+09 37716224.65 0.144603E+10
March 0.555371E+09 0.00 0.555371E+09 0.167473E+09 0.130495E+10
April 0.612814E+09 3576202.05 0.609237E+09 0.299142E+09 0.907299E+09
May 0.831596E+09 49276671.88 0.782319E+09 0.603596E+09 0.677142E+09
June 0.937111E+09 0.107712E+09 0.829399E+09 0.950141E+09 0.410665E+09
July 0.884640E+09 82856089.35 0.801784E+09 0.106699E+10 0.349311E+09
August 0.708867E+09 19000692.27 0.689866E+09 0.771750E+09 0.404049E+09
September 0.513767E+09 184364.90 0.513582E+09 0.433983E+09 0.608080E+09
October 0.387254E+09 0.00 0.387254E+09 0.156410E+09 0.964388E+09
November 0.254767E+09 0.00 0.254767E+09 29943603.27 0.135246E+10
December 0.203045E+09 0.00 0.203045E+09 1321030.66 0.189569E+10
           
Annual Sum or Average 0.644016E+10 0.262606E+09 0.617756E+10 0.452249E+10 0.124442E+11
Minimum of Months 0.203045E+09 0.00 0.203045E+09 1321030.66 0.349311E+09
Maximum of Months 0.937111E+09 0.107712E+09 0.829399E+09 0.106699E+10 0.212416E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.242135E+09 0.00 0.242135E+09 4019392.08 0.212416E+10
February 0.308795E+09 0.00 0.308795E+09 37715617.64 0.144603E+10
March 0.555368E+09 0.00 0.555368E+09 0.167470E+09 0.130495E+10
April 0.612811E+09 3576175.85 0.609235E+09 0.299140E+09 0.907299E+09
May 0.831592E+09 49276310.77 0.782316E+09 0.603591E+09 0.677142E+09
June 0.937106E+09 0.107711E+09 0.829396E+09 0.950135E+09 0.410665E+09
July 0.884636E+09 82855482.17 0.801781E+09 0.106699E+10 0.349311E+09
August 0.708864E+09 19000553.03 0.689863E+09 0.771747E+09 0.404049E+09
September 0.513764E+09 184363.55 0.513580E+09 0.433981E+09 0.608080E+09
October 0.387253E+09 0.00 0.387253E+09 0.156408E+09 0.964388E+09
November 0.254766E+09 0.00 0.254766E+09 29943097.09 0.135246E+10
December 0.203044E+09 0.00 0.203044E+09 1320974.89 0.189569E+10
           
Annual Sum or Average 0.644013E+10 0.262604E+09 0.617753E+10 0.452246E+10 0.124442E+11
Minimum of Months 0.203044E+09 0.00 0.203044E+09 1320974.89 0.349311E+09
Maximum of Months 0.937106E+09 0.107711E+09 0.829396E+09 0.106699E+10 0.212416E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.242126E+09 0.00 0.242126E+09 4019294.11 0.212408E+10
February 0.308783E+09 0.00 0.308783E+09 37714401.03 0.144598E+10
March 0.555347E+09 0.00 0.555347E+09 0.167465E+09 0.130490E+10
April 0.612788E+09 3576044.81 0.609211E+09 0.299129E+09 0.907262E+09
May 0.831561E+09 49274505.26 0.782286E+09 0.603569E+09 0.677114E+09
June 0.937071E+09 0.107707E+09 0.829364E+09 0.950100E+09 0.410649E+09
July 0.884602E+09 82852446.31 0.801750E+09 0.106694E+10 0.349297E+09
August 0.708837E+09 18999856.84 0.689837E+09 0.771718E+09 0.404032E+09
September 0.513745E+09 184356.80 0.513560E+09 0.433964E+09 0.608056E+09
October 0.387238E+09 0.00 0.387238E+09 0.156403E+09 0.964349E+09
November 0.254756E+09 0.00 0.254756E+09 29942143.33 0.135240E+10
December 0.203036E+09 0.00 0.203036E+09 1320949.53 0.189561E+10
           
Annual Sum or Average 0.643989E+10 0.262594E+09 0.617729E+10 0.452229E+10 0.124437E+11
Minimum of Months 0.203036E+09 0.00 0.203036E+09 1320949.53 0.349297E+09
Maximum of Months 0.937071E+09 0.107707E+09 0.829364E+09 0.106694E+10 0.212408E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.617795E+09 0.283234E+09 0.334561E+09 0.317893E+09 0.215290E+10
February 0.872775E+09 0.433312E+09 0.439463E+09 0.638756E+09 0.145279E+10
March 0.129926E+10 0.537598E+09 0.761663E+09 0.104422E+10 0.132861E+10
April 0.160425E+10 0.795056E+09 0.809197E+09 0.154248E+10 0.924344E+09
May 0.183118E+10 0.814759E+09 0.101642E+10 0.189673E+10 0.743502E+09
June 0.229376E+10 0.118037E+10 0.111339E+10 0.274207E+10 0.454688E+09
July 0.248761E+10 0.140631E+10 0.108130E+10 0.320916E+10 0.370746E+09
August 0.216185E+10 0.120451E+10 0.957333E+09 0.272511E+10 0.414240E+09
September 0.147996E+10 0.763951E+09 0.716011E+09 0.168859E+10 0.621124E+09
October 0.109719E+10 0.557135E+09 0.540053E+09 0.102765E+10 0.974431E+09
November 0.672946E+09 0.314177E+09 0.358768E+09 0.451000E+09 0.132753E+10
December 0.512881E+09 0.220284E+09 0.292597E+09 0.243861E+09 0.188523E+10
           
Annual Sum or Average 0.169315E+11 0.851070E+10 0.842076E+10 0.175275E+11 0.126501E+11
Minimum of Months 0.512881E+09 0.220284E+09 0.292597E+09 0.243861E+09 0.370746E+09
Maximum of Months 0.248761E+10 0.140631E+10 0.111339E+10 0.320916E+10 0.215290E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.617795E+09 0.283234E+09 0.334561E+09 0.317893E+09 0.215290E+10
February 0.872775E+09 0.433312E+09 0.439463E+09 0.638756E+09 0.145279E+10
March 0.129926E+10 0.537598E+09 0.761663E+09 0.104422E+10 0.132861E+10
April 0.160425E+10 0.795056E+09 0.809197E+09 0.154248E+10 0.924344E+09
May 0.183118E+10 0.814759E+09 0.101642E+10 0.189673E+10 0.743502E+09
June 0.229376E+10 0.118037E+10 0.111339E+10 0.274207E+10 0.454688E+09
July 0.248761E+10 0.140631E+10 0.108130E+10 0.320916E+10 0.370746E+09
August 0.216185E+10 0.120451E+10 0.957333E+09 0.272511E+10 0.414240E+09
September 0.147996E+10 0.763951E+09 0.716011E+09 0.168859E+10 0.621124E+09
October 0.109719E+10 0.557135E+09 0.540053E+09 0.102765E+10 0.974431E+09
November 0.672946E+09 0.314177E+09 0.358768E+09 0.451000E+09 0.132753E+10
December 0.512881E+09 0.220284E+09 0.292597E+09 0.243861E+09 0.188523E+10
           
Annual Sum or Average 0.169315E+11 0.851070E+10 0.842076E+10 0.175275E+11 0.126501E+11
Minimum of Months 0.512881E+09 0.220284E+09 0.292597E+09 0.243861E+09 0.370746E+09
Maximum of Months 0.248761E+10 0.140631E+10 0.111339E+10 0.320916E+10 0.215290E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.617784E+09 0.283229E+09 0.334555E+09 0.317887E+09 0.215286E+10
February 0.872759E+09 0.433304E+09 0.439455E+09 0.638744E+09 0.145276E+10
March 0.129924E+10 0.537588E+09 0.761649E+09 0.104420E+10 0.132859E+10
April 0.160422E+10 0.795042E+09 0.809182E+09 0.154245E+10 0.924327E+09
May 0.183114E+10 0.814744E+09 0.101640E+10 0.189669E+10 0.743488E+09
June 0.229372E+10 0.118035E+10 0.111337E+10 0.274202E+10 0.454680E+09
July 0.248757E+10 0.140629E+10 0.108128E+10 0.320911E+10 0.370740E+09
August 0.216181E+10 0.120449E+10 0.957315E+09 0.272506E+10 0.414233E+09
September 0.147994E+10 0.763937E+09 0.715998E+09 0.168856E+10 0.621112E+09
October 0.109717E+10 0.557125E+09 0.540043E+09 0.102763E+10 0.974413E+09
November 0.672933E+09 0.314171E+09 0.358762E+09 0.450992E+09 0.132751E+10
December 0.512872E+09 0.220279E+09 0.292592E+09 0.243857E+09 0.188519E+10
           
Annual Sum or Average 0.169312E+11 0.851055E+10 0.842060E+10 0.175272E+11 0.126499E+11
Minimum of Months 0.512872E+09 0.220279E+09 0.292592E+09 0.243857E+09 0.370740E+09
Maximum of Months 0.248757E+10 0.140629E+10 0.111337E+10 0.320911E+10 0.215286E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170677E+10 0.121901E+10 0.487764E+09 0.158436E+10 0.178290E+10
February 0.196321E+10 0.141201E+10 0.551198E+09 0.200499E+10 0.122961E+10
March 0.194287E+10 0.109103E+10 0.851849E+09 0.197727E+10 0.122308E+10
April 0.151137E+10 0.722894E+09 0.788475E+09 0.159606E+10 0.890361E+09
May 0.138758E+10 0.460849E+09 0.926727E+09 0.149811E+10 0.712616E+09
June 0.133422E+10 0.389120E+09 0.945104E+09 0.164659E+10 0.465613E+09
July 0.148637E+10 0.549058E+09 0.937317E+09 0.204548E+10 0.377824E+09
August 0.176645E+10 0.890610E+09 0.875845E+09 0.235651E+10 0.427540E+09
September 0.189601E+10 0.116174E+10 0.734266E+09 0.234788E+10 0.602140E+09
October 0.204824E+10 0.141633E+10 0.631912E+09 0.231997E+10 0.893899E+09
November 0.180715E+10 0.130903E+10 0.498126E+09 0.185877E+10 0.112575E+10
December 0.162305E+10 0.117200E+10 0.451044E+09 0.153214E+10 0.155845E+10
           
Annual Sum or Average 0.204733E+11 0.117937E+11 0.867963E+10 0.227681E+11 0.112898E+11
Minimum of Months 0.133422E+10 0.389120E+09 0.451044E+09 0.149811E+10 0.377824E+09
Maximum of Months 0.204824E+10 0.141633E+10 0.945104E+09 0.235651E+10 0.178290E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170676E+10 0.121900E+10 0.487761E+09 0.158435E+10 0.178290E+10
February 0.196319E+10 0.141200E+10 0.551195E+09 0.200498E+10 0.122961E+10
March 0.194286E+10 0.109102E+10 0.851844E+09 0.197726E+10 0.122308E+10
April 0.151136E+10 0.722889E+09 0.788471E+09 0.159605E+10 0.890361E+09
May 0.138757E+10 0.460846E+09 0.926722E+09 0.149810E+10 0.712616E+09
June 0.133422E+10 0.389117E+09 0.945099E+09 0.164658E+10 0.465613E+09
July 0.148637E+10 0.549054E+09 0.937312E+09 0.204546E+10 0.377823E+09
August 0.176644E+10 0.890603E+09 0.875840E+09 0.235650E+10 0.427540E+09
September 0.189599E+10 0.116173E+10 0.734262E+09 0.234786E+10 0.602140E+09
October 0.204823E+10 0.141632E+10 0.631909E+09 0.231995E+10 0.893899E+09
November 0.180714E+10 0.130902E+10 0.498123E+09 0.185875E+10 0.112575E+10
December 0.162303E+10 0.117199E+10 0.451041E+09 0.153213E+10 0.155845E+10
           
Annual Sum or Average 0.204732E+11 0.117936E+11 0.867958E+10 0.227680E+11 0.112898E+11
Minimum of Months 0.133422E+10 0.389117E+09 0.451041E+09 0.149810E+10 0.377823E+09
Maximum of Months 0.204823E+10 0.141632E+10 0.945099E+09 0.235650E+10 0.178290E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170677E+10 0.121901E+10 0.487764E+09 0.158436E+10 0.178290E+10
February 0.196321E+10 0.141201E+10 0.551198E+09 0.200499E+10 0.122961E+10
March 0.194287E+10 0.109103E+10 0.851849E+09 0.197727E+10 0.122308E+10
April 0.151137E+10 0.722894E+09 0.788475E+09 0.159606E+10 0.890361E+09
May 0.138758E+10 0.460849E+09 0.926727E+09 0.149811E+10 0.712616E+09
June 0.133422E+10 0.389120E+09 0.945104E+09 0.164659E+10 0.465613E+09
July 0.148637E+10 0.549058E+09 0.937317E+09 0.204548E+10 0.377824E+09
August 0.176645E+10 0.890610E+09 0.875845E+09 0.235651E+10 0.427540E+09
September 0.189601E+10 0.116174E+10 0.734266E+09 0.234788E+10 0.602140E+09
October 0.204824E+10 0.141633E+10 0.631912E+09 0.231997E+10 0.893899E+09
November 0.180715E+10 0.130903E+10 0.498126E+09 0.185877E+10 0.112575E+10
December 0.162305E+10 0.117200E+10 0.451044E+09 0.153214E+10 0.155845E+10
           
Annual Sum or Average 0.204733E+11 0.117937E+11 0.867963E+10 0.227681E+11 0.112898E+11
Minimum of Months 0.133422E+10 0.389120E+09 0.451044E+09 0.149811E+10 0.377824E+09
Maximum of Months 0.204824E+10 0.141633E+10 0.945104E+09 0.235651E+10 0.178290E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170676E+10 0.121900E+10 0.487761E+09 0.158435E+10 0.178290E+10
February 0.196319E+10 0.141200E+10 0.551195E+09 0.200498E+10 0.122961E+10
March 0.194286E+10 0.109102E+10 0.851844E+09 0.197726E+10 0.122308E+10
April 0.151136E+10 0.722889E+09 0.788471E+09 0.159605E+10 0.890361E+09
May 0.138757E+10 0.460846E+09 0.926722E+09 0.149810E+10 0.712616E+09
June 0.133422E+10 0.389117E+09 0.945099E+09 0.164658E+10 0.465613E+09
July 0.148637E+10 0.549054E+09 0.937312E+09 0.204546E+10 0.377823E+09
August 0.176644E+10 0.890603E+09 0.875840E+09 0.235650E+10 0.427540E+09
September 0.189599E+10 0.116173E+10 0.734262E+09 0.234786E+10 0.602140E+09
October 0.204823E+10 0.141632E+10 0.631909E+09 0.231995E+10 0.893899E+09
November 0.180714E+10 0.130902E+10 0.498123E+09 0.185875E+10 0.112575E+10
December 0.162303E+10 0.117199E+10 0.451041E+09 0.153213E+10 0.155845E+10
           
Annual Sum or Average 0.204732E+11 0.117936E+11 0.867958E+10 0.227680E+11 0.112898E+11
Minimum of Months 0.133422E+10 0.389117E+09 0.451041E+09 0.149810E+10 0.377823E+09
Maximum of Months 0.204823E+10 0.141632E+10 0.945099E+09 0.235650E+10 0.178290E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170670E+10 0.121896E+10 0.487742E+09 0.158429E+10 0.178283E+10
February 0.196312E+10 0.141195E+10 0.551174E+09 0.200490E+10 0.122956E+10
March 0.194279E+10 0.109098E+10 0.851812E+09 0.197718E+10 0.122303E+10
April 0.151130E+10 0.722862E+09 0.788441E+09 0.159599E+10 0.890325E+09
May 0.138752E+10 0.460829E+09 0.926687E+09 0.149804E+10 0.712587E+09
June 0.133417E+10 0.389103E+09 0.945063E+09 0.164652E+10 0.465594E+09
July 0.148631E+10 0.549034E+09 0.937277E+09 0.204539E+10 0.377808E+09
August 0.176638E+10 0.890571E+09 0.875807E+09 0.235641E+10 0.427523E+09
September 0.189592E+10 0.116169E+10 0.734234E+09 0.234778E+10 0.602116E+09
October 0.204815E+10 0.141627E+10 0.631885E+09 0.231986E+10 0.893863E+09
November 0.180707E+10 0.130897E+10 0.498104E+09 0.185869E+10 0.112571E+10
December 0.162297E+10 0.117195E+10 0.451025E+09 0.153207E+10 0.155839E+10
           
Annual Sum or Average 0.204724E+11 0.117932E+11 0.867925E+10 0.227671E+11 0.112893E+11
Minimum of Months 0.133417E+10 0.389103E+09 0.451025E+09 0.149804E+10 0.377808E+09
Maximum of Months 0.204815E+10 0.141627E+10 0.945063E+09 0.235641E+10 0.178283E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.559591E+09 0.225519E+09 0.334072E+09 0.274550E+09 0.231277E+10
February 0.862705E+09 0.424063E+09 0.438642E+09 0.628694E+09 0.158474E+10
March 0.122234E+10 0.447885E+09 0.774459E+09 0.924927E+09 0.151189E+10
April 0.154430E+10 0.684197E+09 0.860104E+09 0.144584E+10 0.111123E+10
May 0.197386E+10 0.900187E+09 0.107368E+10 0.208488E+10 0.837942E+09
June 0.207821E+10 0.954601E+09 0.112361E+10 0.245505E+10 0.557122E+09
July 0.219986E+10 0.111162E+10 0.108824E+10 0.281971E+10 0.482499E+09
August 0.186798E+10 0.916764E+09 0.951214E+09 0.231159E+10 0.543694E+09
September 0.145420E+10 0.735184E+09 0.719015E+09 0.166755E+10 0.712156E+09
October 0.107400E+10 0.533611E+09 0.540386E+09 0.100438E+10 0.111802E+10
November 0.735763E+09 0.365001E+09 0.370762E+09 0.538352E+09 0.151594E+10
December 0.511052E+09 0.215701E+09 0.295352E+09 0.244940E+09 0.213071E+10
           
Annual Sum or Average 0.160839E+11 0.751434E+10 0.856953E+10 0.164005E+11 0.144187E+11
Minimum of Months 0.511052E+09 0.215701E+09 0.295352E+09 0.244940E+09 0.482499E+09
Maximum of Months 0.219986E+10 0.111162E+10 0.112361E+10 0.281971E+10 0.231277E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.559591E+09 0.225519E+09 0.334072E+09 0.274550E+09 0.231277E+10
February 0.862705E+09 0.424063E+09 0.438642E+09 0.628694E+09 0.158474E+10
March 0.122234E+10 0.447885E+09 0.774459E+09 0.924927E+09 0.151189E+10
April 0.154430E+10 0.684197E+09 0.860104E+09 0.144584E+10 0.111123E+10
May 0.197386E+10 0.900187E+09 0.107368E+10 0.208488E+10 0.837942E+09
June 0.207821E+10 0.954601E+09 0.112361E+10 0.245505E+10 0.557122E+09
July 0.219986E+10 0.111162E+10 0.108824E+10 0.281971E+10 0.482499E+09
August 0.186798E+10 0.916764E+09 0.951214E+09 0.231159E+10 0.543694E+09
September 0.145420E+10 0.735184E+09 0.719015E+09 0.166755E+10 0.712156E+09
October 0.107400E+10 0.533611E+09 0.540386E+09 0.100438E+10 0.111802E+10
November 0.735763E+09 0.365001E+09 0.370762E+09 0.538352E+09 0.151594E+10
December 0.511052E+09 0.215701E+09 0.295352E+09 0.244940E+09 0.213071E+10
           
Annual Sum or Average 0.160839E+11 0.751434E+10 0.856953E+10 0.164005E+11 0.144187E+11
Minimum of Months 0.511052E+09 0.215701E+09 0.295352E+09 0.244940E+09 0.482499E+09
Maximum of Months 0.219986E+10 0.111162E+10 0.112361E+10 0.281971E+10 0.231277E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.559581E+09 0.225515E+09 0.334066E+09 0.274545E+09 0.231272E+10
February 0.862689E+09 0.424056E+09 0.438634E+09 0.628683E+09 0.158471E+10
March 0.122232E+10 0.447877E+09 0.774445E+09 0.924910E+09 0.151186E+10
April 0.154427E+10 0.684184E+09 0.860088E+09 0.144581E+10 0.111121E+10
May 0.197383E+10 0.900170E+09 0.107366E+10 0.208484E+10 0.837926E+09
June 0.207817E+10 0.954583E+09 0.112359E+10 0.245501E+10 0.557111E+09
July 0.219982E+10 0.111160E+10 0.108822E+10 0.281966E+10 0.482490E+09
August 0.186794E+10 0.916748E+09 0.951197E+09 0.231155E+10 0.543684E+09
September 0.145417E+10 0.735170E+09 0.719002E+09 0.166752E+10 0.712143E+09
October 0.107398E+10 0.533602E+09 0.540376E+09 0.100436E+10 0.111800E+10
November 0.735749E+09 0.364994E+09 0.370755E+09 0.538342E+09 0.151591E+10
December 0.511043E+09 0.215697E+09 0.295346E+09 0.244936E+09 0.213067E+10
           
Annual Sum or Average 0.160836E+11 0.751420E+10 0.856937E+10 0.164002E+11 0.144184E+11
Minimum of Months 0.511043E+09 0.215697E+09 0.295346E+09 0.244936E+09 0.482490E+09
Maximum of Months 0.219982E+10 0.111160E+10 0.112359E+10 0.281966E+10 0.231272E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121069E+10 0.00 0.121069E+10 41869899.32 0.999314E+10
February 0.154399E+10 0.00 0.154399E+10 0.287706E+09 0.665340E+10
March 0.277688E+10 0.00 0.277688E+10 0.101803E+10 0.593033E+10
April 0.306410E+10 17881386.28 0.304622E+10 0.167392E+10 0.407108E+10
May 0.415802E+10 0.246389E+09 0.391163E+10 0.313847E+10 0.313861E+10
June 0.468560E+10 0.538570E+09 0.414703E+10 0.481362E+10 0.196808E+10
July 0.442324E+10 0.414289E+09 0.400895E+10 0.539375E+10 0.169738E+10
August 0.354436E+10 95005459.17 0.344936E+10 0.392917E+10 0.193794E+10
September 0.256885E+10 921843.89 0.256793E+10 0.224942E+10 0.283030E+10
October 0.193629E+10 0.00 0.193629E+10 0.926435E+09 0.431917E+10
November 0.127385E+10 0.00 0.127385E+10 0.222386E+09 0.598501E+10
December 0.101523E+10 0.00 0.101523E+10 22179672.85 0.851669E+10
           
Annual Sum or Average 0.322011E+11 0.131306E+10 0.308881E+11 0.237170E+11 0.570411E+11
Minimum of Months 0.101523E+10 0.00 0.101523E+10 22179672.85 0.169738E+10
Maximum of Months 0.468560E+10 0.538570E+09 0.414703E+10 0.539375E+10 0.999314E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.185337E+10 0.849694E+09 0.100367E+10 0.996365E+09 0.614268E+10
February 0.261830E+10 0.129992E+10 0.131838E+10 0.198477E+10 0.409077E+10
March 0.389774E+10 0.161278E+10 0.228496E+10 0.320958E+10 0.373474E+10
April 0.481271E+10 0.238514E+10 0.242757E+10 0.467118E+10 0.260400E+10
May 0.549347E+10 0.244425E+10 0.304922E+10 0.571102E+10 0.209874E+10
June 0.688122E+10 0.354107E+10 0.334015E+10 0.819933E+10 0.133751E+10
July 0.746276E+10 0.421890E+10 0.324386E+10 0.958580E+10 0.113187E+10
August 0.648547E+10 0.361351E+10 0.287197E+10 0.813773E+10 0.127356E+10
September 0.443984E+10 0.229183E+10 0.214801E+10 0.507591E+10 0.177466E+10
October 0.329153E+10 0.167139E+10 0.162014E+10 0.315085E+10 0.270419E+10
November 0.201882E+10 0.942522E+09 0.107629E+10 0.142272E+10 0.365437E+10
December 0.153863E+10 0.660844E+09 0.877783E+09 0.785192E+09 0.522563E+10
           
Annual Sum or Average 0.507939E+11 0.255318E+11 0.252620E+11 0.529304E+11 0.357727E+11
Minimum of Months 0.153863E+10 0.660844E+09 0.877783E+09 0.785192E+09 0.113187E+10
Maximum of Months 0.746276E+10 0.421890E+10 0.334015E+10 0.958580E+10 0.614268E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.853404E+10 0.609518E+10 0.243886E+10 0.791633E+10 0.871674E+10
February 0.981623E+10 0.706020E+10 0.275603E+10 0.100053E+11 0.595349E+10
March 0.971455E+10 0.545524E+10 0.425930E+10 0.987506E+10 0.589361E+10
April 0.755697E+10 0.361455E+10 0.394242E+10 0.798910E+10 0.425008E+10
May 0.693798E+10 0.230429E+10 0.463369E+10 0.748399E+10 0.343176E+10
June 0.667121E+10 0.194564E+10 0.472556E+10 0.822733E+10 0.226915E+10
July 0.743197E+10 0.274535E+10 0.468662E+10 0.102171E+11 0.187648E+10
August 0.883241E+10 0.445314E+10 0.437927E+10 0.117556E+11 0.212796E+10
September 0.948020E+10 0.580882E+10 0.367137E+10 0.116717E+11 0.294546E+10
October 0.102414E+11 0.708180E+10 0.315960E+10 0.115606E+11 0.431821E+10
November 0.903593E+10 0.654527E+10 0.249067E+10 0.930836E+10 0.539146E+10
December 0.811539E+10 0.586013E+10 0.225526E+10 0.772703E+10 0.740869E+10
           
Annual Sum or Average 0.102368E+12 0.589696E+11 0.433987E+11 0.113737E+12 0.545831E+11
Minimum of Months 0.667121E+10 0.194564E+10 0.225526E+10 0.748399E+10 0.187648E+10
Maximum of Months 0.102414E+11 0.708180E+10 0.472556E+10 0.117556E+11 0.871674E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.167876E+10 0.676552E+09 0.100221E+10 0.862497E+09 0.648415E+10
February 0.258809E+10 0.127218E+10 0.131591E+10 0.199136E+10 0.428075E+10
March 0.366700E+10 0.134364E+10 0.232335E+10 0.294418E+10 0.398307E+10
April 0.463285E+10 0.205257E+10 0.258029E+10 0.452760E+10 0.284145E+10
May 0.592153E+10 0.270053E+10 0.322099E+10 0.633327E+10 0.230774E+10
June 0.623457E+10 0.286377E+10 0.337080E+10 0.745126E+10 0.153879E+10
July 0.659951E+10 0.333483E+10 0.326468E+10 0.855434E+10 0.133619E+10
August 0.560388E+10 0.275026E+10 0.285361E+10 0.706896E+10 0.144186E+10
September 0.436255E+10 0.220553E+10 0.215702E+10 0.507161E+10 0.195519E+10
October 0.322196E+10 0.160082E+10 0.162114E+10 0.315497E+10 0.292463E+10
November 0.220727E+10 0.109499E+10 0.111227E+10 0.174199E+10 0.389151E+10
December 0.153314E+10 0.647096E+09 0.886046E+09 0.827943E+09 0.548703E+10
           
Annual Sum or Average 0.482511E+11 0.225428E+11 0.257083E+11 0.505300E+11 0.384724E+11
Minimum of Months 0.153314E+10 0.647096E+09 0.886046E+09 0.827943E+09 0.133619E+10
Maximum of Months 0.659951E+10 0.333483E+10 0.337080E+10 0.855434E+10 0.648415E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121069E+10 0.00 0.121069E+10 59255395.68 0.963816E+10
February 0.154399E+10 0.00 0.154399E+10 0.341519E+09 0.633575E+10
March 0.277688E+10 0.00 0.277688E+10 0.111422E+10 0.557768E+10
April 0.306410E+10 17881386.28 0.304622E+10 0.180800E+10 0.374749E+10
May 0.415802E+10 0.246389E+09 0.391163E+10 0.324491E+10 0.293009E+10
June 0.468560E+10 0.538570E+09 0.414703E+10 0.486343E+10 0.189875E+10
July 0.442324E+10 0.414289E+09 0.400895E+10 0.540530E+10 0.166410E+10
August 0.354436E+10 95005459.17 0.344936E+10 0.395636E+10 0.187003E+10
September 0.256885E+10 921843.89 0.256793E+10 0.232325E+10 0.264072E+10
October 0.193629E+10 0.00 0.193629E+10 0.105730E+10 0.391679E+10
November 0.127385E+10 0.00 0.127385E+10 0.274128E+09 0.552533E+10
December 0.101523E+10 0.00 0.101523E+10 28789739.25 0.813653E+10
           
Annual Sum or Average 0.322011E+11 0.131306E+10 0.308881E+11 0.244765E+11 0.538814E+11
Minimum of Months 0.101523E+10 0.00 0.101523E+10 28789739.25 0.166410E+10
Maximum of Months 0.468560E+10 0.538570E+09 0.414703E+10 0.540530E+10 0.963816E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.185337E+10 0.849694E+09 0.100367E+10 0.102873E+10 0.592569E+10
February 0.261830E+10 0.129992E+10 0.131838E+10 0.204401E+10 0.390070E+10
March 0.389774E+10 0.161278E+10 0.228496E+10 0.328483E+10 0.352986E+10
April 0.481271E+10 0.238514E+10 0.242757E+10 0.473994E+10 0.243472E+10
May 0.549347E+10 0.244425E+10 0.304922E+10 0.574402E+10 0.199043E+10
June 0.688122E+10 0.354107E+10 0.334015E+10 0.819451E+10 0.131459E+10
July 0.746276E+10 0.421890E+10 0.324386E+10 0.956304E+10 0.112814E+10
August 0.648547E+10 0.361351E+10 0.287197E+10 0.812366E+10 0.125685E+10
September 0.443984E+10 0.229183E+10 0.214801E+10 0.509591E+10 0.169954E+10
October 0.329153E+10 0.167139E+10 0.162014E+10 0.323873E+10 0.249382E+10
November 0.201882E+10 0.942522E+09 0.107629E+10 0.148891E+10 0.339118E+10
December 0.153863E+10 0.660844E+09 0.877783E+09 0.814236E+09 0.499397E+10
           
Annual Sum or Average 0.507939E+11 0.255318E+11 0.252620E+11 0.533605E+11 0.340595E+11
Minimum of Months 0.153863E+10 0.660844E+09 0.877783E+09 0.814236E+09 0.112814E+10
Maximum of Months 0.746276E+10 0.421890E+10 0.334015E+10 0.956304E+10 0.592569E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.853404E+10 0.609518E+10 0.243886E+10 0.801925E+10 0.833798E+10
February 0.981623E+10 0.706020E+10 0.275603E+10 0.101126E+11 0.563292E+10
March 0.971455E+10 0.545524E+10 0.425930E+10 0.997606E+10 0.555047E+10
April 0.755697E+10 0.361455E+10 0.394242E+10 0.808368E+10 0.396049E+10
May 0.693798E+10 0.230429E+10 0.463369E+10 0.753390E+10 0.323899E+10
June 0.667121E+10 0.194564E+10 0.472556E+10 0.823388E+10 0.220600E+10
July 0.743197E+10 0.274535E+10 0.468662E+10 0.101998E+11 0.185105E+10
August 0.883241E+10 0.445314E+10 0.437927E+10 0.117411E+11 0.208161E+10
September 0.948020E+10 0.580882E+10 0.367137E+10 0.116951E+11 0.280748E+10
October 0.102414E+11 0.708180E+10 0.315960E+10 0.116677E+11 0.398572E+10
November 0.903593E+10 0.654527E+10 0.249067E+10 0.945961E+10 0.498105E+10
December 0.811539E+10 0.586013E+10 0.225526E+10 0.783793E+10 0.702929E+10
           
Annual Sum or Average 0.102368E+12 0.589696E+11 0.433987E+11 0.114561E+12 0.516630E+11
Minimum of Months 0.667121E+10 0.194564E+10 0.225526E+10 0.753390E+10 0.185105E+10
Maximum of Months 0.102414E+11 0.708180E+10 0.472556E+10 0.117411E+11 0.833798E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.167876E+10 0.676552E+09 0.100221E+10 0.884871E+09 0.625798E+10
February 0.258809E+10 0.127218E+10 0.131591E+10 0.202600E+10 0.409397E+10
March 0.366700E+10 0.134364E+10 0.232335E+10 0.298628E+10 0.378639E+10
April 0.463285E+10 0.205257E+10 0.258029E+10 0.457955E+10 0.267254E+10
May 0.592153E+10 0.270053E+10 0.322099E+10 0.635889E+10 0.219090E+10
June 0.623457E+10 0.286377E+10 0.337080E+10 0.745184E+10 0.150252E+10
July 0.659951E+10 0.333483E+10 0.326468E+10 0.854337E+10 0.132098E+10
August 0.560388E+10 0.275026E+10 0.285361E+10 0.706640E+10 0.141279E+10
September 0.436255E+10 0.220553E+10 0.215702E+10 0.508871E+10 0.186883E+10
October 0.322196E+10 0.160082E+10 0.162114E+10 0.321099E+10 0.272107E+10
November 0.220727E+10 0.109499E+10 0.111227E+10 0.178495E+10 0.364207E+10
December 0.153314E+10 0.647096E+09 0.886046E+09 0.847004E+09 0.526337E+10
           
Annual Sum or Average 0.482511E+11 0.225428E+11 0.257083E+11 0.508289E+11 0.367334E+11
Minimum of Months 0.153314E+10 0.647096E+09 0.886046E+09 0.847004E+09 0.132098E+10
Maximum of Months 0.659951E+10 0.333483E+10 0.337080E+10 0.854337E+10 0.625798E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 7.50 3965.33 452.01 0.00 452.01 0.00 0.00
February 77.95 2988.64 638.21 0.00 638.21 0.00 0.00
March 312.63 2436.05 1036.75 0.00 1036.75 0.00 0.00
April 577.04 1750.18 1182.12 6.90 1175.22 0.00 0.00
May 1126.77 1264.07 1552.40 91.99 1460.41 0.00 0.00
June 1832.82 792.17 1807.68 207.78 1599.91 0.00 0.00
July 1991.83 652.08 1651.42 154.67 1496.75 0.00 0.00
August 1440.68 754.27 1323.29 35.47 1287.82 0.00 0.00
September 837.15 1172.99 991.05 0.36 990.70 0.00 0.00
October 291.98 1800.29 722.92 0.00 722.92 0.00 0.00
November 57.76 2608.89 491.44 0.00 491.44 0.00 0.00
December 2.47 3538.81 379.04 0.00 379.04 0.00 0.00
               
Annual Sum or Average 717.03 1973.00 1021.07 41.64 979.44 0.00 0.00
Minimum of Months 2.47 652.08 379.04 0.00 379.04 0.00 0.00
Maximum of Months 1991.83 3965.33 1807.68 207.78 1599.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 356.06 2411.39 691.97 317.24 374.73 0.00 0.00
February 792.10 1801.56 1082.30 537.34 544.97 0.00 0.00
March 1169.59 1488.13 1455.26 602.14 853.11 0.00 0.00
April 1785.26 1069.84 1856.76 920.20 936.56 0.00 0.00
May 2124.46 832.77 2051.04 912.58 1138.45 0.00 0.00
June 3173.67 526.26 2654.80 1366.16 1288.64 0.00 0.00
July 3594.47 415.26 2786.29 1575.16 1211.13 0.00 0.00
August 3052.30 463.98 2421.41 1349.13 1072.27 0.00 0.00
September 1954.37 718.89 1712.91 884.20 828.71 0.00 0.00
October 1151.03 1091.43 1228.92 624.03 604.89 0.00 0.00
November 521.99 1536.49 778.87 363.63 415.24 0.00 0.00
December 273.14 2111.57 574.46 246.73 327.73 0.00 0.00
               
Annual Sum or Average 1667.37 1203.39 1610.67 809.61 801.06 0.00 0.00
Minimum of Months 273.14 415.26 574.46 246.73 327.73 0.00 0.00
Maximum of Months 3594.47 2411.39 2786.29 1575.16 1288.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2957.62 3328.27 3186.14 2275.60 910.54 0.00 0.00
February 4143.87 2541.33 4057.51 2918.31 1139.20 0.00 0.00
March 3691.10 2283.22 3626.89 2036.69 1590.20 0.00 0.00
April 3078.79 1717.50 2915.42 1394.46 1520.96 0.00 0.00
May 2796.62 1330.29 2590.28 860.30 1729.98 0.00 0.00
June 3176.25 898.17 2573.71 750.61 1823.10 0.00 0.00
July 3818.42 705.31 2774.71 1024.96 1749.75 0.00 0.00
August 4399.05 798.12 3297.56 1662.56 1635.00 0.00 0.00
September 4529.04 1161.53 3657.38 2240.99 1416.39 0.00 0.00
October 4330.83 1668.70 3823.59 2643.96 1179.63 0.00 0.00
November 3585.55 2171.57 3485.98 2525.10 960.88 0.00 0.00
December 2860.15 2909.27 3029.84 2187.85 841.99 0.00 0.00
               
Annual Sum or Average 3609.82 1789.97 3245.98 1869.85 1376.13 0.00 0.00
Minimum of Months 2796.62 705.31 2573.71 750.61 841.99 0.00 0.00
Maximum of Months 4529.04 3328.27 4057.51 2918.31 1823.10 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 307.51 2590.45 626.78 252.60 374.18 0.00 0.00
February 779.63 1965.20 1069.82 525.87 543.95 0.00 0.00
March 1035.98 1693.41 1369.10 501.66 867.44 0.00 0.00
April 1673.42 1286.14 1787.37 791.89 995.48 0.00 0.00
May 2335.20 938.55 2210.85 1008.27 1202.59 0.00 0.00
June 2841.48 644.81 2405.32 1104.86 1300.47 0.00 0.00
July 3158.26 540.43 2463.99 1245.09 1218.90 0.00 0.00
August 2589.13 608.97 2092.26 1026.84 1065.42 0.00 0.00
September 1930.02 824.25 1683.09 850.90 832.19 0.00 0.00
October 1124.97 1252.26 1202.95 597.68 605.27 0.00 0.00
November 623.09 1754.55 851.57 422.45 429.12 0.00 0.00
December 274.35 2386.53 572.41 241.60 330.81 0.00 0.00
               
Annual Sum or Average 1560.16 1371.63 1530.04 714.83 815.21 0.00 0.00
Minimum of Months 274.35 540.43 572.41 241.60 330.81 0.00 0.00
Maximum of Months 3158.26 2590.45 2463.99 1245.09 1300.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 15.63 3731.01 452.02 0.00 452.02 0.00 0.00
February 118.93 2750.25 638.23 0.00 638.23 0.00 0.00
March 380.09 2214.13 1036.77 0.00 1036.77 0.00 0.00
April 645.80 1570.63 1182.14 6.90 1175.24 0.00 0.00
May 1171.77 1171.82 1552.43 91.99 1460.44 0.00 0.00
June 1857.11 759.29 1807.72 207.78 1599.93 0.00 0.00
July 2013.80 633.73 1651.45 154.68 1496.77 0.00 0.00
August 1466.98 723.54 1323.31 35.47 1287.84 0.00 0.00
September 867.83 1091.94 991.07 0.36 990.71 0.00 0.00
October 345.89 1612.59 722.93 0.00 722.93 0.00 0.00
November 85.80 2309.03 491.45 0.00 491.45 0.00 0.00
December 8.28 3179.77 379.05 0.00 379.05 0.00 0.00
               
Annual Sum or Average 752.06 1808.76 1021.09 41.64 979.45 0.00 0.00
Minimum of Months 8.28 633.73 379.05 0.00 379.05 0.00 0.00
Maximum of Months 2013.80 3731.01 1807.72 207.78 1599.93 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 372.00 2293.42 691.97 317.24 374.73 0.00 0.00
February 820.42 1690.96 1082.30 537.34 544.96 0.00 0.00
March 1198.32 1394.39 1455.25 602.14 853.11 0.00 0.00
April 1802.15 1004.63 1856.76 920.19 936.56 0.00 0.00
May 2132.25 783.58 2051.03 912.58 1138.45 0.00 0.00
June 3163.32 516.02 2654.79 1366.15 1288.64 0.00 0.00
July 3578.93 422.59 2786.28 1575.16 1211.12 0.00 0.00
August 3038.28 475.49 2421.40 1349.13 1072.27 0.00 0.00
September 1958.30 684.67 1712.90 884.19 828.71 0.00 0.00
October 1176.39 1009.63 1228.92 624.03 604.89 0.00 0.00
November 548.89 1409.87 778.86 363.63 415.24 0.00 0.00
December 293.16 1951.03 574.46 246.73 327.73 0.00 0.00
               
Annual Sum or Average 1678.41 1134.35 1610.66 809.61 801.05 0.00 0.00
Minimum of Months 293.16 422.59 574.46 246.73 327.73 0.00 0.00
Maximum of Months 3578.93 2293.42 2786.28 1575.16 1288.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2955.62 3254.46 3186.24 2275.68 910.56 0.00 0.00
February 4135.80 2460.93 4057.63 2918.40 1139.23 0.00 0.00
March 3686.92 2200.42 3627.00 2036.75 1590.24 0.00 0.00
April 3082.21 1639.69 2915.50 1394.50 1521.00 0.00 0.00
May 2794.20 1281.27 2590.34 860.32 1730.02 0.00 0.00
June 3174.12 875.44 2573.77 750.63 1823.13 0.00 0.00
July 3814.63 700.60 2774.78 1025.00 1749.79 0.00 0.00
August 4389.02 794.49 3297.64 1662.61 1635.03 0.00 0.00
September 4502.97 1136.37 3657.48 2241.06 1416.43 0.00 0.00
October 4316.23 1612.24 3823.70 2644.04 1179.66 0.00 0.00
November 3591.19 2080.04 3486.08 2525.18 960.91 0.00 0.00
December 2884.94 2766.09 3029.94 2187.92 842.02 0.00 0.00
               
Annual Sum or Average 3606.59 1730.82 3246.08 1869.91 1376.16 0.00 0.00
Minimum of Months 2794.20 700.60 2573.77 750.63 842.02 0.00 0.00
Maximum of Months 4502.97 3254.46 4057.63 2918.40 1823.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 322.02 2420.90 626.78 252.60 374.18 0.00 0.00
February 823.15 1769.49 1069.81 525.87 543.95 0.00 0.00
March 1099.23 1487.11 1369.10 501.66 867.44 0.00 0.00
April 1746.76 1096.24 1787.37 791.89 995.48 0.00 0.00
May 2364.57 861.61 2210.84 1008.26 1202.58 0.00 0.00
June 2874.72 593.67 2405.31 1104.85 1300.46 0.00 0.00
July 3193.82 498.88 2463.98 1245.08 1218.89 0.00 0.00
August 2639.25 538.33 2092.25 1026.83 1065.42 0.00 0.00
September 1956.64 754.32 1683.08 850.90 832.18 0.00 0.00
October 1177.93 1091.93 1202.94 597.68 605.26 0.00 0.00
November 672.06 1501.35 851.57 422.45 429.12 0.00 0.00
December 309.12 2048.62 572.41 241.60 330.81 0.00 0.00
               
Annual Sum or Average 1602.30 1219.95 1530.03 714.83 815.21 0.00 0.00
Minimum of Months 309.12 498.88 572.41 241.60 330.81 0.00 0.00
Maximum of Months 3193.82 2420.90 2463.98 1245.08 1300.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 22.12 3598.48 452.02 0.00 452.02 0.00 0.00
February 141.17 2618.94 638.23 0.00 638.23 0.00 0.00
March 416.00 2082.47 1036.77 0.00 1036.77 0.00 0.00
April 697.53 1445.79 1182.14 6.90 1175.24 0.00 0.00
May 1211.51 1093.97 1552.43 91.99 1460.44 0.00 0.00
June 1876.32 732.54 1807.72 207.78 1599.93 0.00 0.00
July 2018.11 621.30 1651.45 154.68 1496.77 0.00 0.00
August 1477.13 698.19 1323.31 35.47 1287.84 0.00 0.00
September 896.32 1018.79 991.07 0.36 990.71 0.00 0.00
October 394.75 1462.36 722.93 0.00 722.93 0.00 0.00
November 105.76 2131.69 491.45 0.00 491.45 0.00 0.00
December 10.75 3037.83 379.05 0.00 379.05 0.00 0.00
               
Annual Sum or Average 776.14 1708.57 1021.09 41.64 979.45 0.00 0.00
Minimum of Months 10.75 621.30 379.05 0.00 379.05 0.00 0.00
Maximum of Months 2018.11 3598.48 1807.72 207.78 1599.93 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 384.08 2212.40 691.97 317.24 374.73 0.00 0.00
February 844.91 1612.39 1082.30 537.34 544.96 0.00 0.00
March 1226.41 1317.90 1455.25 602.14 853.11 0.00 0.00
April 1828.68 939.32 1856.76 920.19 936.56 0.00 0.00
May 2144.57 743.14 2051.03 912.58 1138.45 0.00 0.00
June 3161.46 507.17 2654.79 1366.15 1288.64 0.00 0.00
July 3570.43 421.20 2786.28 1575.16 1211.12 0.00 0.00
August 3033.03 469.25 2421.40 1349.13 1072.27 0.00 0.00
September 1966.01 655.69 1712.90 884.19 828.71 0.00 0.00
October 1209.20 931.08 1228.92 624.03 604.89 0.00 0.00
November 574.42 1308.33 778.86 363.63 415.24 0.00 0.00
December 304.00 1864.53 574.46 246.73 327.73 0.00 0.00
               
Annual Sum or Average 1692.05 1080.02 1610.66 809.61 801.05 0.00 0.00
Minimum of Months 304.00 421.20 574.46 246.73 327.73 0.00 0.00
Maximum of Months 3570.43 2212.40 2786.28 1575.16 1288.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2994.04 3113.04 3186.24 2275.68 910.56 0.00 0.00
February 4180.14 2328.42 4057.63 2918.40 1139.23 0.00 0.00
March 3724.64 2072.31 3627.00 2036.75 1590.24 0.00 0.00
April 3118.71 1527.97 2915.50 1394.50 1521.00 0.00 0.00
May 2812.84 1209.30 2590.34 860.32 1730.02 0.00 0.00
June 3176.65 851.08 2573.77 750.63 1823.13 0.00 0.00
July 3808.16 691.10 2774.78 1025.00 1749.79 0.00 0.00
August 4383.62 777.19 3297.64 1662.61 1635.03 0.00 0.00
September 4511.98 1083.13 3657.48 2241.06 1416.43 0.00 0.00
October 4356.22 1488.10 3823.70 2644.04 1179.66 0.00 0.00
November 3649.54 1921.70 3486.08 2525.18 960.91 0.00 0.00
December 2926.35 2624.44 3029.94 2187.92 842.02 0.00 0.00
               
Annual Sum or Average 3632.69 1638.22 3246.08 1869.91 1376.16 0.00 0.00
Minimum of Months 2812.84 691.10 2573.77 750.63 842.02 0.00 0.00
Maximum of Months 4511.98 3113.04 4057.63 2918.40 1823.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 330.37 2336.46 626.78 252.60 374.18 0.00 0.00
February 837.47 1692.28 1069.81 525.87 543.95 0.00 0.00
March 1114.95 1413.68 1369.10 501.66 867.44 0.00 0.00
April 1766.80 1031.07 1787.37 791.89 995.48 0.00 0.00
May 2374.14 817.99 2210.84 1008.26 1202.58 0.00 0.00
June 2874.94 579.68 2405.31 1104.85 1300.46 0.00 0.00
July 3189.73 493.20 2463.98 1245.08 1218.89 0.00 0.00
August 2638.29 527.48 2092.25 1026.83 1065.42 0.00 0.00
September 1963.24 721.00 1683.08 850.90 832.18 0.00 0.00
October 1198.84 1015.93 1202.94 597.68 605.26 0.00 0.00
November 688.64 1405.12 851.57 422.45 429.12 0.00 0.00
December 316.23 1965.12 572.41 241.60 330.81 0.00 0.00
               
Annual Sum or Average 1611.77 1164.81 1530.03 714.83 815.21 0.00 0.00
Minimum of Months 316.23 493.20 572.41 241.60 330.81 0.00 0.00
Maximum of Months 3189.73 2336.46 2463.98 1245.08 1300.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 20097374.69 0.106207E+11 0.121067E+10 0.00 0.121067E+10 0.00 0.00
February 0.188579E+09 0.723011E+10 0.154397E+10 0.00 0.154397E+10 0.00 0.00
March 0.837355E+09 0.652472E+10 0.277683E+10 0.00 0.277683E+10 0.00 0.00
April 0.149570E+10 0.453646E+10 0.306404E+10 17880853.02 0.304616E+10 0.00 0.00
May 0.301795E+10 0.338568E+10 0.415795E+10 0.246381E+09 0.391156E+10 0.00 0.00
June 0.475066E+10 0.205331E+10 0.468551E+10 0.538554E+09 0.414696E+10 0.00 0.00
July 0.533491E+10 0.174654E+10 0.442316E+10 0.414277E+09 0.400889E+10 0.00 0.00
August 0.385872E+10 0.202023E+10 0.354431E+10 95002625.92 0.344930E+10 0.00 0.00
September 0.216990E+10 0.304038E+10 0.256881E+10 921816.40 0.256789E+10 0.00 0.00
October 0.782041E+09 0.482190E+10 0.193626E+10 0.00 0.193626E+10 0.00 0.00
November 0.149717E+09 0.676223E+10 0.127382E+10 0.00 0.127382E+10 0.00 0.00
December 6605072.17 0.947836E+10 0.101522E+10 0.00 0.101522E+10 0.00 0.00
               
Annual Sum or Average 0.226122E+11 0.622206E+11 0.322005E+11 0.131302E+10 0.308875E+11 0.00 0.00
Minimum of Months 6605072.17 0.174654E+10 0.101522E+10 0.00 0.101522E+10 0.00 0.00
Maximum of Months 0.533491E+10 0.106207E+11 0.468551E+10 0.538554E+09 0.414696E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.953672E+09 0.645866E+10 0.185337E+10 0.849697E+09 0.100368E+10 0.00 0.00
February 0.191626E+10 0.435834E+10 0.261831E+10 0.129993E+10 0.131838E+10 0.00 0.00
March 0.313264E+10 0.398581E+10 0.389776E+10 0.161278E+10 0.228497E+10 0.00 0.00
April 0.462740E+10 0.277301E+10 0.481273E+10 0.238515E+10 0.242758E+10 0.00 0.00
May 0.569015E+10 0.223049E+10 0.549350E+10 0.244426E+10 0.304924E+10 0.00 0.00
June 0.822615E+10 0.136406E+10 0.688124E+10 0.354108E+10 0.334016E+10 0.00 0.00
July 0.962744E+10 0.111223E+10 0.746279E+10 0.421892E+10 0.324388E+10 0.00 0.00
August 0.817528E+10 0.124271E+10 0.648550E+10 0.361352E+10 0.287198E+10 0.00 0.00
September 0.506573E+10 0.186336E+10 0.443986E+10 0.229184E+10 0.214802E+10 0.00 0.00
October 0.308292E+10 0.292327E+10 0.329155E+10 0.167140E+10 0.162015E+10 0.00 0.00
November 0.135299E+10 0.398257E+10 0.201882E+10 0.942526E+09 0.107630E+10 0.00 0.00
December 0.731579E+09 0.565564E+10 0.153863E+10 0.660846E+09 0.877787E+09 0.00 0.00
               
Annual Sum or Average 0.525822E+11 0.379502E+11 0.507941E+11 0.255320E+11 0.252621E+11 0.00 0.00
Minimum of Months 0.731579E+09 0.111223E+10 0.153863E+10 0.660846E+09 0.877787E+09 0.00 0.00
Maximum of Months 0.962744E+10 0.645866E+10 0.746279E+10 0.421892E+10 0.334016E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.792170E+10 0.891444E+10 0.853377E+10 0.609498E+10 0.243879E+10 0.00 0.00
February 0.100248E+11 0.614798E+10 0.981593E+10 0.705997E+10 0.275596E+10 0.00 0.00
March 0.988624E+10 0.611537E+10 0.971426E+10 0.545506E+10 0.425920E+10 0.00 0.00
April 0.798021E+10 0.445177E+10 0.755676E+10 0.361443E+10 0.394233E+10 0.00 0.00
May 0.749046E+10 0.356305E+10 0.693780E+10 0.230422E+10 0.463359E+10 0.00 0.00
June 0.823285E+10 0.232805E+10 0.667105E+10 0.194558E+10 0.472547E+10 0.00 0.00
July 0.102273E+11 0.188910E+10 0.743179E+10 0.274526E+10 0.468653E+10 0.00 0.00
August 0.117824E+11 0.213768E+10 0.883217E+10 0.445300E+10 0.437918E+10 0.00 0.00
September 0.117393E+11 0.301067E+10 0.947992E+10 0.580863E+10 0.367129E+10 0.00 0.00
October 0.115997E+11 0.446946E+10 0.102411E+11 0.708157E+10 0.315953E+10 0.00 0.00
November 0.929374E+10 0.562872E+10 0.903565E+10 0.654505E+10 0.249060E+10 0.00 0.00
December 0.766061E+10 0.779220E+10 0.811513E+10 0.585994E+10 0.225520E+10 0.00 0.00
               
Annual Sum or Average 0.113839E+12 0.564485E+11 0.102365E+12 0.589677E+11 0.433977E+11 0.00 0.00
Minimum of Months 0.749046E+10 0.188910E+10 0.667105E+10 0.194558E+10 0.225520E+10 0.00 0.00
Maximum of Months 0.117824E+11 0.891444E+10 0.102411E+11 0.708157E+10 0.472547E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.823644E+09 0.693826E+10 0.167876E+10 0.676554E+09 0.100221E+10 0.00 0.00
February 0.188607E+10 0.475420E+10 0.258810E+10 0.127218E+10 0.131592E+10 0.00 0.00
March 0.277476E+10 0.453563E+10 0.366701E+10 0.134365E+10 0.232336E+10 0.00 0.00
April 0.433750E+10 0.333367E+10 0.463287E+10 0.205258E+10 0.258030E+10 0.00 0.00
May 0.625459E+10 0.251381E+10 0.592155E+10 0.270054E+10 0.322101E+10 0.00 0.00
June 0.736512E+10 0.167135E+10 0.623460E+10 0.286378E+10 0.337081E+10 0.00 0.00
July 0.845909E+10 0.144749E+10 0.659954E+10 0.333485E+10 0.326470E+10 0.00 0.00
August 0.693473E+10 0.163107E+10 0.560390E+10 0.275028E+10 0.285362E+10 0.00 0.00
September 0.500261E+10 0.213645E+10 0.436257E+10 0.220554E+10 0.215703E+10 0.00 0.00
October 0.301313E+10 0.335404E+10 0.322197E+10 0.160082E+10 0.162115E+10 0.00 0.00
November 0.161505E+10 0.454779E+10 0.220727E+10 0.109500E+10 0.111228E+10 0.00 0.00
December 0.734816E+09 0.639209E+10 0.153315E+10 0.647098E+09 0.886049E+09 0.00 0.00
               
Annual Sum or Average 0.492011E+11 0.432559E+11 0.482513E+11 0.225429E+11 0.257084E+11 0.00 0.00
Minimum of Months 0.734816E+09 0.144749E+10 0.153315E+10 0.647098E+09 0.886049E+09 0.00 0.00
Maximum of Months 0.845909E+10 0.693826E+10 0.659954E+10 0.333485E+10 0.337081E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 41869899.32 0.999314E+10 0.121069E+10 0.00 0.121069E+10 0.00 0.00
February 0.287706E+09 0.665340E+10 0.154399E+10 0.00 0.154399E+10 0.00 0.00
March 0.101803E+10 0.593033E+10 0.277688E+10 0.00 0.277688E+10 0.00 0.00
April 0.167392E+10 0.407108E+10 0.306410E+10 17881386.28 0.304622E+10 0.00 0.00
May 0.313847E+10 0.313861E+10 0.415802E+10 0.246389E+09 0.391163E+10 0.00 0.00
June 0.481362E+10 0.196808E+10 0.468560E+10 0.538570E+09 0.414703E+10 0.00 0.00
July 0.539375E+10 0.169738E+10 0.442324E+10 0.414289E+09 0.400895E+10 0.00 0.00
August 0.392917E+10 0.193794E+10 0.354436E+10 95005459.17 0.344936E+10 0.00 0.00
September 0.224942E+10 0.283030E+10 0.256885E+10 921843.89 0.256793E+10 0.00 0.00
October 0.926435E+09 0.431917E+10 0.193629E+10 0.00 0.193629E+10 0.00 0.00
November 0.222386E+09 0.598501E+10 0.127385E+10 0.00 0.127385E+10 0.00 0.00
December 22179672.85 0.851669E+10 0.101523E+10 0.00 0.101523E+10 0.00 0.00
               
Annual Sum or Average 0.237170E+11 0.570411E+11 0.322011E+11 0.131306E+10 0.308881E+11 0.00 0.00
Minimum of Months 22179672.85 0.169738E+10 0.101523E+10 0.00 0.101523E+10 0.00 0.00
Maximum of Months 0.539375E+10 0.999314E+10 0.468560E+10 0.538570E+09 0.414703E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.996365E+09 0.614268E+10 0.185337E+10 0.849694E+09 0.100367E+10 0.00 0.00
February 0.198477E+10 0.409077E+10 0.261830E+10 0.129992E+10 0.131838E+10 0.00 0.00
March 0.320958E+10 0.373474E+10 0.389774E+10 0.161278E+10 0.228496E+10 0.00 0.00
April 0.467118E+10 0.260400E+10 0.481271E+10 0.238514E+10 0.242757E+10 0.00 0.00
May 0.571102E+10 0.209874E+10 0.549347E+10 0.244425E+10 0.304922E+10 0.00 0.00
June 0.819933E+10 0.133751E+10 0.688122E+10 0.354107E+10 0.334015E+10 0.00 0.00
July 0.958580E+10 0.113187E+10 0.746276E+10 0.421890E+10 0.324386E+10 0.00 0.00
August 0.813773E+10 0.127356E+10 0.648547E+10 0.361351E+10 0.287197E+10 0.00 0.00
September 0.507591E+10 0.177466E+10 0.443984E+10 0.229183E+10 0.214801E+10 0.00 0.00
October 0.315085E+10 0.270419E+10 0.329153E+10 0.167139E+10 0.162014E+10 0.00 0.00
November 0.142272E+10 0.365437E+10 0.201882E+10 0.942522E+09 0.107629E+10 0.00 0.00
December 0.785192E+09 0.522563E+10 0.153863E+10 0.660844E+09 0.877783E+09 0.00 0.00
               
Annual Sum or Average 0.529304E+11 0.357727E+11 0.507939E+11 0.255318E+11 0.252620E+11 0.00 0.00
Minimum of Months 0.785192E+09 0.113187E+10 0.153863E+10 0.660844E+09 0.877783E+09 0.00 0.00
Maximum of Months 0.958580E+10 0.614268E+10 0.746276E+10 0.421890E+10 0.334015E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.791633E+10 0.871674E+10 0.853404E+10 0.609518E+10 0.243886E+10 0.00 0.00
February 0.100053E+11 0.595349E+10 0.981623E+10 0.706020E+10 0.275603E+10 0.00 0.00
March 0.987506E+10 0.589361E+10 0.971455E+10 0.545524E+10 0.425930E+10 0.00 0.00
April 0.798910E+10 0.425008E+10 0.755697E+10 0.361455E+10 0.394242E+10 0.00 0.00
May 0.748399E+10 0.343176E+10 0.693798E+10 0.230429E+10 0.463369E+10 0.00 0.00
June 0.822733E+10 0.226915E+10 0.667121E+10 0.194564E+10 0.472556E+10 0.00 0.00
July 0.102171E+11 0.187648E+10 0.743197E+10 0.274535E+10 0.468662E+10 0.00 0.00
August 0.117556E+11 0.212796E+10 0.883241E+10 0.445314E+10 0.437927E+10 0.00 0.00
September 0.116717E+11 0.294546E+10 0.948020E+10 0.580882E+10 0.367137E+10 0.00 0.00
October 0.115606E+11 0.431821E+10 0.102414E+11 0.708180E+10 0.315960E+10 0.00 0.00
November 0.930836E+10 0.539146E+10 0.903593E+10 0.654527E+10 0.249067E+10 0.00 0.00
December 0.772703E+10 0.740869E+10 0.811539E+10 0.586013E+10 0.225526E+10 0.00 0.00
               
Annual Sum or Average 0.113737E+12 0.545831E+11 0.102368E+12 0.589696E+11 0.433987E+11 0.00 0.00
Minimum of Months 0.748399E+10 0.187648E+10 0.667121E+10 0.194564E+10 0.225526E+10 0.00 0.00
Maximum of Months 0.117556E+11 0.871674E+10 0.102414E+11 0.708180E+10 0.472556E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.862497E+09 0.648415E+10 0.167876E+10 0.676552E+09 0.100221E+10 0.00 0.00
February 0.199136E+10 0.428075E+10 0.258809E+10 0.127218E+10 0.131591E+10 0.00 0.00
March 0.294418E+10 0.398307E+10 0.366700E+10 0.134364E+10 0.232335E+10 0.00 0.00
April 0.452760E+10 0.284145E+10 0.463285E+10 0.205257E+10 0.258029E+10 0.00 0.00
May 0.633327E+10 0.230774E+10 0.592153E+10 0.270053E+10 0.322099E+10 0.00 0.00
June 0.745126E+10 0.153879E+10 0.623457E+10 0.286377E+10 0.337080E+10 0.00 0.00
July 0.855434E+10 0.133619E+10 0.659951E+10 0.333483E+10 0.326468E+10 0.00 0.00
August 0.706896E+10 0.144186E+10 0.560388E+10 0.275026E+10 0.285361E+10 0.00 0.00
September 0.507161E+10 0.195519E+10 0.436255E+10 0.220553E+10 0.215702E+10 0.00 0.00
October 0.315497E+10 0.292463E+10 0.322196E+10 0.160082E+10 0.162114E+10 0.00 0.00
November 0.174199E+10 0.389151E+10 0.220727E+10 0.109499E+10 0.111227E+10 0.00 0.00
December 0.827943E+09 0.548703E+10 0.153314E+10 0.647096E+09 0.886046E+09 0.00 0.00
               
Annual Sum or Average 0.505300E+11 0.384724E+11 0.482511E+11 0.225428E+11 0.257083E+11 0.00 0.00
Minimum of Months 0.827943E+09 0.133619E+10 0.153314E+10 0.647096E+09 0.886046E+09 0.00 0.00
Maximum of Months 0.855434E+10 0.648415E+10 0.659951E+10 0.333483E+10 0.337080E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 59255395.68 0.963816E+10 0.121069E+10 0.00 0.121069E+10 0.00 0.00
February 0.341519E+09 0.633575E+10 0.154399E+10 0.00 0.154399E+10 0.00 0.00
March 0.111422E+10 0.557768E+10 0.277688E+10 0.00 0.277688E+10 0.00 0.00
April 0.180800E+10 0.374749E+10 0.306410E+10 17881386.28 0.304622E+10 0.00 0.00
May 0.324491E+10 0.293009E+10 0.415802E+10 0.246389E+09 0.391163E+10 0.00 0.00
June 0.486343E+10 0.189875E+10 0.468560E+10 0.538570E+09 0.414703E+10 0.00 0.00
July 0.540530E+10 0.166410E+10 0.442324E+10 0.414289E+09 0.400895E+10 0.00 0.00
August 0.395636E+10 0.187003E+10 0.354436E+10 95005459.17 0.344936E+10 0.00 0.00
September 0.232325E+10 0.264072E+10 0.256885E+10 921843.89 0.256793E+10 0.00 0.00
October 0.105730E+10 0.391679E+10 0.193629E+10 0.00 0.193629E+10 0.00 0.00
November 0.274128E+09 0.552533E+10 0.127385E+10 0.00 0.127385E+10 0.00 0.00
December 28789739.25 0.813653E+10 0.101523E+10 0.00 0.101523E+10 0.00 0.00
               
Annual Sum or Average 0.244765E+11 0.538814E+11 0.322011E+11 0.131306E+10 0.308881E+11 0.00 0.00
Minimum of Months 28789739.25 0.166410E+10 0.101523E+10 0.00 0.101523E+10 0.00 0.00
Maximum of Months 0.540530E+10 0.963816E+10 0.468560E+10 0.538570E+09 0.414703E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.102873E+10 0.592569E+10 0.185337E+10 0.849694E+09 0.100367E+10 0.00 0.00
February 0.204401E+10 0.390070E+10 0.261830E+10 0.129992E+10 0.131838E+10 0.00 0.00
March 0.328483E+10 0.352986E+10 0.389774E+10 0.161278E+10 0.228496E+10 0.00 0.00
April 0.473994E+10 0.243472E+10 0.481271E+10 0.238514E+10 0.242757E+10 0.00 0.00
May 0.574402E+10 0.199043E+10 0.549347E+10 0.244425E+10 0.304922E+10 0.00 0.00
June 0.819451E+10 0.131459E+10 0.688122E+10 0.354107E+10 0.334015E+10 0.00 0.00
July 0.956304E+10 0.112814E+10 0.746276E+10 0.421890E+10 0.324386E+10 0.00 0.00
August 0.812366E+10 0.125685E+10 0.648547E+10 0.361351E+10 0.287197E+10 0.00 0.00
September 0.509591E+10 0.169954E+10 0.443984E+10 0.229183E+10 0.214801E+10 0.00 0.00
October 0.323873E+10 0.249382E+10 0.329153E+10 0.167139E+10 0.162014E+10 0.00 0.00
November 0.148891E+10 0.339118E+10 0.201882E+10 0.942522E+09 0.107629E+10 0.00 0.00
December 0.814236E+09 0.499397E+10 0.153863E+10 0.660844E+09 0.877783E+09 0.00 0.00
               
Annual Sum or Average 0.533605E+11 0.340595E+11 0.507939E+11 0.255318E+11 0.252620E+11 0.00 0.00
Minimum of Months 0.814236E+09 0.112814E+10 0.153863E+10 0.660844E+09 0.877783E+09 0.00 0.00
Maximum of Months 0.956304E+10 0.592569E+10 0.746276E+10 0.421890E+10 0.334015E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.801925E+10 0.833798E+10 0.853404E+10 0.609518E+10 0.243886E+10 0.00 0.00
February 0.101126E+11 0.563292E+10 0.981623E+10 0.706020E+10 0.275603E+10 0.00 0.00
March 0.997606E+10 0.555047E+10 0.971455E+10 0.545524E+10 0.425930E+10 0.00 0.00
April 0.808368E+10 0.396049E+10 0.755697E+10 0.361455E+10 0.394242E+10 0.00 0.00
May 0.753390E+10 0.323899E+10 0.693798E+10 0.230429E+10 0.463369E+10 0.00 0.00
June 0.823388E+10 0.220600E+10 0.667121E+10 0.194564E+10 0.472556E+10 0.00 0.00
July 0.101998E+11 0.185105E+10 0.743197E+10 0.274535E+10 0.468662E+10 0.00 0.00
August 0.117411E+11 0.208161E+10 0.883241E+10 0.445314E+10 0.437927E+10 0.00 0.00
September 0.116951E+11 0.280748E+10 0.948020E+10 0.580882E+10 0.367137E+10 0.00 0.00
October 0.116677E+11 0.398572E+10 0.102414E+11 0.708180E+10 0.315960E+10 0.00 0.00
November 0.945961E+10 0.498105E+10 0.903593E+10 0.654527E+10 0.249067E+10 0.00 0.00
December 0.783793E+10 0.702929E+10 0.811539E+10 0.586013E+10 0.225526E+10 0.00 0.00
               
Annual Sum or Average 0.114561E+12 0.516630E+11 0.102368E+12 0.589696E+11 0.433987E+11 0.00 0.00
Minimum of Months 0.753390E+10 0.185105E+10 0.667121E+10 0.194564E+10 0.225526E+10 0.00 0.00
Maximum of Months 0.117411E+11 0.833798E+10 0.102414E+11 0.708180E+10 0.472556E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.884871E+09 0.625798E+10 0.167876E+10 0.676552E+09 0.100221E+10 0.00 0.00
February 0.202600E+10 0.409397E+10 0.258809E+10 0.127218E+10 0.131591E+10 0.00 0.00
March 0.298628E+10 0.378639E+10 0.366700E+10 0.134364E+10 0.232335E+10 0.00 0.00
April 0.457955E+10 0.267254E+10 0.463285E+10 0.205257E+10 0.258029E+10 0.00 0.00
May 0.635889E+10 0.219090E+10 0.592153E+10 0.270053E+10 0.322099E+10 0.00 0.00
June 0.745184E+10 0.150252E+10 0.623457E+10 0.286377E+10 0.337080E+10 0.00 0.00
July 0.854337E+10 0.132098E+10 0.659951E+10 0.333483E+10 0.326468E+10 0.00 0.00
August 0.706640E+10 0.141279E+10 0.560388E+10 0.275026E+10 0.285361E+10 0.00 0.00
September 0.508871E+10 0.186883E+10 0.436255E+10 0.220553E+10 0.215702E+10 0.00 0.00
October 0.321099E+10 0.272107E+10 0.322196E+10 0.160082E+10 0.162114E+10 0.00 0.00
November 0.178495E+10 0.364207E+10 0.220727E+10 0.109499E+10 0.111227E+10 0.00 0.00
December 0.847004E+09 0.526337E+10 0.153314E+10 0.647096E+09 0.886046E+09 0.00 0.00
               
Annual Sum or Average 0.508289E+11 0.367334E+11 0.482511E+11 0.225428E+11 0.257083E+11 0.00 0.00
Minimum of Months 0.847004E+09 0.132098E+10 0.153314E+10 0.647096E+09 0.886046E+09 0.00 0.00
Maximum of Months 0.854337E+10 0.625798E+10 0.659951E+10 0.333483E+10 0.337080E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -8.8 -10.9 -16.1 5.70 -23.3 32.48 106.19 0.00
February -2.2 -5.0 -9.9 6.21 -16.1 41.31 158.25 0.00
March 0.30 -2.9 -8.4 5.38 -12.8 78.62 145.02 0.00
April 6.67 2.34 -2.9 4.89 -6.2 82.10 182.32 0.01
May 10.10 5.18 0.22 5.28 -1.1 102.67 205.47 0.01
June 16.46 10.06 4.91 4.56 5.05 103.05 264.47 0.02
July 20.57 12.46 6.56 4.24 8.00 89.47 301.47 0.00
August 19.17 11.04 4.61 4.29 7.19 78.96 261.05 0.00
September 14.69 9.08 4.37 5.43 3.42 63.03 204.21 0.00
October 8.64 4.13 -1.0 5.38 -4.2 47.64 162.42 0.00
November 2.84 -0.9 -6.9 5.91 -11.0 33.00 125.52 0.00
December -4.1 -6.5 -11.1 5.64 -18.2 26.54 97.81 0.00
                 
Annual Sum or Average 7.07 2.37 -2.9 5.23 -5.7 65.04 184.63 0.00
Minimum of Months -8.8 -10.9 -16.1 4.24 -23.3 26.54 97.81 0.00
Maximum of Months 20.57 12.46 6.56 6.21 8.00 103.05 301.47 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.60 14-JAN-12:00 5.16 -1.1 8.20 -2.3 105.00 464.50
February 18.90 27-FEB-14:00 7.23 -7.8 5.20 1.37 76.00 634.50
March 15.00 14-MAR-13:20 6.67 -2.4 9.30 1.23 201.67 711.67
April 23.30 07-APR-13:00 9.68 -4.4 9.30 4.92 314.50 110.00
May 30.00 20-MAY-15:00 15.22 5.60 6.70 20.57 215.50 18.50
June 32.20 29-JUN-12:00 14.40 0.60 9.30 17.03 187.00 729.00
July 37.20 17-JUL-15:00 17.28 4.40 4.60 20.22 119.50 797.00
August 35.60 05-AUG-15:00 17.65 6.70 5.20 22.47 136.50 625.50
September 34.40 02-SEP-14:00 16.28 4.40 7.70 20.75 95.50 789.50
October 25.00 18-OCT-13:00 11.40 -1.1 7.70 7.35 48.00 913.00
November 17.20 04-NOV-13:00 8.18 -1.1 11.30 2.22 81.00 689.50
December 13.90 10-DEC-01:00 5.50 -5.0 13.90 5.74 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 10.60   5.16 -7.8 4.60 -2.3 0.00 0.00
Maximum of Months 37.20   17.65 6.70 13.90 22.47 314.50 913.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -33.9 10-JAN-21:00 -34.1 -37.8 3.10 -54.3 0.00 0.00
February -25.0 01-FEB-03:00 -25.2 -27.8 2.10 -45.6 0.00 0.00
March -23.3 04-MAR-23:00 -23.8 -28.9 3.60 -44.5 0.00 0.00
April -7.8 29-APR-03:00 -8.7 -10.6 4.10 -25.6 0.00 0.00
May -2.8 08-MAY-00:10 -3.3 -3.9 6.18 -10.2 0.00 0.00
June 0.60 15-JUN-03:00 -0.5 -1.7 2.60 -15.7 0.00 0.00
July 5.60 08-JUL-03:00 2.99 0.00 4.10 -9.2 0.00 0.00
August 6.70 17-AUG-00:00 4.32 1.70 2.60 -7.1 0.00 0.00
September 0.00 17-SEP-02:00 -1.6 -3.9 4.10 -16.8 0.00 0.00
October -6.1 10-OCT-05:19 -6.6 -7.8 3.77 -20.6 0.00 0.00
November -16.7 26-NOV-07:00 -17.3 -20.6 4.60 -33.8 19.50 94.00
December -28.3 29-DEC-08:00 -28.6 -32.2 2.10 -48.7 69.50 0.00
                 
Annual Sum or Average                
Minimum of Months -33.9   -34.1 -37.8 2.10 -54.3 0.00 0.00
Maximum of Months 6.70   4.32 1.70 6.18 -7.1 69.50 94.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 5.18 13-JAN-14:00 10.00 0.00 8.80 -3.0 40.00 694.00
February 7.23 27-FEB-14:00 18.90 -7.8 5.20 1.37 76.00 634.50
March 6.94 14-MAR-13:00 15.00 -1.7 10.30 1.80 241.00 538.00
April 11.02 06-APR-15:00 22.20 1.10 3.60 5.33 110.00 779.00
May 15.22 20-MAY-15:00 30.00 5.60 6.70 20.57 215.50 18.50
June 19.20 20-JUN-14:00 29.40 14.40 2.60 18.28 204.00 614.00
July 19.21 19-JUL-11:00 29.40 14.40 8.80 19.52 306.50 563.50
August 17.65 05-AUG-15:00 35.60 6.70 5.20 22.47 136.50 625.50
September 20.12 07-SEP-15:20 25.17 17.93 4.10 15.88 127.67 652.00
October 11.61 18-OCT-14:00 25.00 -0.6 7.70 7.55 40.50 852.00
November 8.89 17-NOV-16:00 17.20 1.10 11.30 4.10 0.00 0.00
December 7.62 19-DEC-14:00 12.80 2.80 8.20 1.37 74.00 138.50
                 
Annual Sum or Average                
Minimum of Months 5.18   10.00 -7.8 2.60 -3.0 0.00 0.00
Maximum of Months 20.12   35.60 17.93 11.30 22.47 306.50 852.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.70 12-JAN-14:00 7.20 4.48 5.20 -1.0 107.00 61.00
February -0.6 11-FEB-08:00 4.40 2.16 10.80 -5.7 69.50 50.50
March -0.6 10-MAR-12:00 8.90 4.51 10.30 -2.3 253.00 140.50
April 6.10 17-APR-16:19 7.97 6.96 4.50 0.87 201.50 117.50
May 12.20 02-MAY-12:00 18.90 14.61 12.90 14.84 108.50 934.50
June 15.60 20-JUN-19:00 25.60 18.76 3.60 20.22 17.50 17.00
July 16.70 18-JUL-21:00 19.40 17.51 4.10 16.49 0.00 0.00
August 11.10 08-AUG-11:00 26.70 16.75 2.60 12.03 134.50 869.00
September 18.30 07-SEP-14:00 24.40 20.10 4.10 15.57 111.00 720.00
October 6.70 01-OCT-14:09 9.08 7.78 2.10 4.07 260.33 0.33
November 3.30 16-NOV-19:00 10.60 6.88 9.80 -1.7 0.00 0.00
December 2.80 19-DEC-14:09 10.97 6.81 10.78 -1.0 95.00 292.00
                 
Annual Sum or Average                
Minimum of Months -0.6   4.40 2.16 2.10 -5.7 0.00 0.00
Maximum of Months 18.30   26.70 20.10 12.90 20.22 260.33 934.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 5.41 12.59 0.00
February 18.00 13.00 16.00 4.46 20.37 0.00
March 18.00 13.00 16.00 5.03 30.19 0.00
April 18.00 13.00 16.00 7.01 37.07 0.00
May 18.00 13.00 16.00 9.90 46.35 0.00
June 18.00 13.00 16.00 12.91 55.45 0.00
July 18.00 13.00 16.00 15.24 57.38 0.00
August 18.00 13.00 16.00 16.26 48.01 0.00
September 18.00 13.00 16.00 15.67 34.51 0.00
October 18.00 13.00 16.00 13.64 22.84 0.00
November 18.00 13.00 16.00 10.74 14.52 0.00
December 18.00 13.00 16.00 7.74 10.24 0.00
             
Annual Sum or Average 18.00 13.00 16.00 10.37 32.53 0.00
Minimum of Months 18.00 13.00 16.00 4.46 10.24 0.00
Maximum of Months 18.00 13.00 16.00 16.26 57.38 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.437175E+11 -0.426679E+11 0.00 0.00 744.00 0.00 -0.104954E+10 58.98 0.00 0.00
February 0.403890E+11 -0.394524E+11 0.00 0.00 672.00 0.00 -936616652.6 58.98 0.00 0.00
March 0.469608E+11 -0.459284E+11 0.00 0.00 744.00 0.00 -0.103244E+10 58.97 0.00 0.00
April 0.411161E+11 -0.401232E+11 0.00 0.00 720.00 0.00 -992933268.5 58.97 0.00 0.00
May 0.415208E+11 -0.404953E+11 0.00 0.00 744.00 0.00 -0.102546E+10 58.98 0.00 0.00
June 0.386510E+11 -0.376584E+11 0.00 0.00 720.00 0.00 -992537841.9 58.98 0.00 0.00
July 0.350100E+11 -0.339907E+11 0.00 0.00 744.00 0.00 -0.101922E+10 58.98 0.00 0.00
August 0.373965E+11 -0.363731E+11 0.00 0.00 744.00 0.00 -0.102341E+10 58.98 0.00 0.00
September 0.344383E+11 -0.334497E+11 0.00 0.00 720.00 0.00 -988546487.4 58.98 0.00 0.00
October 0.371413E+11 -0.361207E+11 0.00 0.00 744.00 0.00 -0.102060E+10 58.98 0.00 0.00
November 0.386802E+11 -0.376911E+11 0.00 0.00 720.00 0.00 -989053281.2 58.98 0.00 0.00
December 0.408551E+11 -0.398248E+11 0.00 0.00 744.00 0.00 -0.103031E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.475876E+12 -0.463776E+12 0.00 0.00 8760.00 0.00 -0.121007E+11 58.98 0.00 0.00
Minimum of Months 0.344383E+11 -0.459284E+11 0.00 0.00 672.00 0.00 -0.104954E+10 58.97 0.00 0.00
Maximum of Months 0.469608E+11 -0.334497E+11 0.00 0.00 744.00 0.00 -936616652.6 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.64 0.61 01-JAN-08:50 5097.18 32.67 186.00 222.00 4508.42 37.63 218.67 207.17
February 275.00 0.63 0.61 01-FEB-08:20 7187.51 34.27 240.83 249.83 3012.65 31.09 228.67 239.83
March 304.00 0.63 0.61 01-MAR-07:49 8536.88 32.08 253.50 316.17 1586.52 22.09 194.67 285.17
April 325.17 0.63 0.61 01-APR-08:39 1939.33 18.00 0.00 339.83 1094.23 21.03 159.17 297.33
May 385.83 0.63 0.61 01-MAY-06:10 1718.33 17.69 0.00 385.83 953.00 20.69 170.50 336.33
June 434.17 0.64 0.61 01-JUN-13:39 1461.07 17.04 0.00 394.17 842.21 20.09 183.17 341.67
July 417.33 0.63 0.61 01-JUL-06:40 1565.82 17.48 0.00 393.33 928.13 20.55 142.50 350.17
August 421.33 0.64 0.61 01-AUG-06:19 1676.86 17.06 0.00 370.83 991.36 20.07 147.00 328.17
September 352.17 0.64 0.61 01-SEP-06:49 2439.00 18.71 29.50 318.67 1163.65 20.35 140.67 285.50
October 317.67 0.63 0.61 01-OCT-07:40 7376.52 33.51 276.67 294.67 1885.38 23.09 168.33 272.50
November 269.50 0.63 0.61 01-NOV-07:49 5291.25 33.17 223.50 240.67 4880.05 38.16 261.50 236.17
December 236.83 0.64 0.61 01-DEC-08:50 3827.25 30.55 166.50 221.83 3680.55 37.33 224.50 210.67
                         
Annual Sum or Average 3965.83 0.63     3668.97 23.84 1376.50 3747.83 1871.79 24.71 2239.33 3390.67
Minimum of Months 226.83 0.63 0.61   1461.07 17.04 0.00 221.83 842.21 20.07 140.67 207.17
Maximum of Months 434.17 0.64 0.61   8536.88 34.27 276.67 394.17 4880.05 38.16 261.50 350.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.65 0.61 01-JAN-08:50 1515.70 19.87 73.83 201.50 909.48 20.73 61.50 159.33
February 275.00 0.64 0.61 01-FEB-08:09 1512.39 16.70 48.83 232.00 897.48 18.14 46.17 192.50
March 304.00 0.63 0.61 01-MAR-07:40 2643.32 18.73 70.33 309.50 1543.82 18.41 44.83 270.67
April 325.17 0.63 0.61 01-APR-08:39 2661.32 16.14 42.50 346.83 1551.95 15.15 0.00 297.33
May 385.83 0.63 0.61 01-MAY-05:40 3060.56 13.63 0.00 394.67 1315.48 15.00 0.00 347.00
June 434.17 0.63 0.61 01-JUN-13:39 3714.72 13.03 0.00 406.33 1589.50 14.54 0.00 369.50
July 417.33 0.62 0.61 01-JUL-06:40 4046.93 13.47 3.67 409.33 1706.80 14.95 0.00 377.67
August 421.33 0.63 0.61 01-AUG-05:40 3022.20 15.49 55.83 378.50 1838.33 14.30 0.00 338.50
September 352.17 0.64 0.61 01-SEP-06:30 2350.16 15.89 52.50 313.00 1343.76 14.94 8.50 274.00
October 317.67 0.64 0.61 01-OCT-07:40 2076.98 18.31 80.17 273.17 1248.14 19.32 73.33 229.83
November 269.50 0.65 0.61 01-NOV-07:49 1373.22 18.88 81.33 215.00 727.59 18.22 53.83 170.83
December 236.83 0.65 0.61 01-DEC-08:50 1174.43 19.62 80.33 190.00 738.18 20.91 72.50 142.17
                         
Annual Sum or Average 3965.83 0.64     2602.30 16.20 589.33 3669.83 1349.58 16.60 360.67 3169.33
Minimum of Months 226.83 0.62 0.61   1174.43 13.03 0.00 190.00 727.59 14.30 0.00 142.17
Maximum of Months 434.17 0.65 0.61   4046.93 19.87 81.33 409.33 1838.33 20.91 73.33 377.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.67 0.61 01-JAN-09:39 494.54 0.00 0.00 170.83 293.92 0.00 0.00 68.67
February 275.00 0.65 0.61 01-FEB-10:20 538.64 0.00 0.00 209.83 334.67 0.00 0.00 129.00
March 304.00 0.63 0.61 01-MAR-07:00 858.79 0.00 0.00 299.67 505.19 0.00 0.00 245.67
April 325.17 0.63 0.61 01-APR-08:39 892.96 0.00 0.00 342.50 533.87 0.00 0.00 281.00
May 385.83 0.62 0.61 01-MAY-05:49 1114.37 0.00 0.00 404.17 651.57 0.00 0.00 363.00
June 434.17 0.63 0.61 01-JUN-13:39 1155.10 0.00 0.00 432.33 637.69 0.00 0.00 395.83
July 417.33 0.62 0.61 01-JUL-06:40 1129.94 0.00 0.00 419.17 646.37 0.00 0.00 386.00
August 421.33 0.63 0.61 01-AUG-05:40 869.82 0.00 0.00 391.67 558.50 0.00 0.00 357.67
September 352.17 0.64 0.61 01-SEP-06:49 707.70 0.00 0.00 310.67 442.60 0.00 0.00 241.50
October 317.67 0.65 0.61 01-OCT-07:49 584.73 0.00 0.00 249.83 358.91 0.00 0.00 166.50
November 269.50 0.66 0.61 01-NOV-08:09 462.77 0.00 0.00 181.17 280.42 0.00 0.00 61.17
December 236.83 0.67 0.61 01-DEC-09:09 401.05 0.00 0.00 148.67 242.56 0.00 0.00 15.83
                         
Annual Sum or Average 3965.83 0.64     815.95 0.00 0.00 3560.50 484.67 0.00 0.00 2711.83
Minimum of Months 226.83 0.62 0.61   401.05 0.00 0.00 148.67 242.56 0.00 0.00 15.83
Maximum of Months 434.17 0.67 0.61   1155.10 0.00 0.00 432.33 651.57 0.00 0.00 395.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.66 0.61 01-JAN-09:39 1396.40 18.96 69.17 194.83 866.64 19.81 58.83 148.83
February 275.00 0.64 0.61 01-FEB-10:20 1854.80 19.00 76.33 229.83 955.29 18.25 48.83 192.67
March 304.00 0.63 0.61 01-MAR-07:00 2492.22 18.53 69.00 305.00 1412.19 19.45 62.00 268.33
April 325.17 0.63 0.61 01-APR-08:39 2604.19 16.34 48.50 335.17 1512.15 15.24 0.00 295.50
May 385.83 0.63 0.61 01-MAY-06:19 3076.06 13.72 0.00 389.50 1774.73 15.20 1.33 348.00
June 434.17 0.63 0.61 01-JUN-13:39 3145.79 13.15 0.00 409.50 1403.52 16.71 47.50 369.67
July 417.33 0.63 0.61 01-JUL-06:40 3662.35 13.44 3.67 397.50 1634.67 16.31 31.50 360.67
August 421.33 0.63 0.61 01-AUG-06:30 2705.64 15.41 56.83 374.00 1540.18 14.36 0.00 337.00
September 352.17 0.64 0.61 01-SEP-06:00 2876.75 17.35 75.33 314.50 1113.30 14.77 5.50 274.50
October 317.67 0.64 0.61 01-OCT-07:00 1853.40 18.27 77.67 270.83 991.50 18.09 53.33 228.50
November 269.50 0.65 0.61 01-NOV-08:20 1582.40 19.14 82.33 212.17 941.30 20.18 71.83 169.83
December 236.83 0.65 0.61 01-DEC-09:09 1122.44 19.52 79.17 194.00 608.57 18.53 49.83 139.83
                         
Annual Sum or Average 3965.83 0.64     2508.03 16.46 638.00 3626.83 1288.60 16.93 430.50 3133.33
Minimum of Months 226.83 0.63 0.61   1122.44 13.15 0.00 194.00 608.57 14.36 0.00 139.83
Maximum of Months 434.17 0.66 0.61   3662.35 19.52 82.33 409.50 1774.73 20.18 71.83 369.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.64 0.61 01-JAN-08:50 4462.85 25.63 138.83 220.83 4554.30 37.18 214.33 207.67
February 275.00 0.63 0.61 01-FEB-08:20 7152.76 33.30 239.33 249.17 3067.03 28.60 169.67 240.17
March 304.00 0.63 0.61 01-MAR-07:49 8490.01 31.08 250.17 314.33 1637.51 17.40 6.67 286.83
April 325.17 0.63 0.61 01-APR-08:39 1908.40 12.00 0.00 338.17 1134.03 16.87 0.00 299.17
May 385.83 0.63 0.61 01-MAY-06:10 1687.13 11.93 0.00 384.83 984.97 16.71 0.00 339.83
June 434.17 0.64 0.61 01-JUN-13:39 1437.92 11.48 0.00 392.17 870.55 16.33 0.00 345.00
July 417.33 0.63 0.61 01-JUL-06:40 1545.48 11.87 0.00 391.17 961.96 16.80 0.00 352.33
August 421.33 0.64 0.61 01-AUG-06:19 1659.43 11.18 0.00 368.33 1030.17 16.05 0.00 330.83
September 352.17 0.64 0.61 01-SEP-06:49 2418.58 12.96 29.50 317.50 1225.17 16.21 5.50 287.17
October 317.67 0.63 0.61 01-OCT-07:40 7290.95 32.29 270.17 293.83 2020.28 20.65 76.17 278.50
November 269.50 0.64 0.61 01-NOV-07:49 5031.46 28.74 191.00 240.17 4886.22 36.56 248.83 233.00
December 236.83 0.64 0.61 01-DEC-08:50 3085.67 21.26 108.67 220.67 3717.67 36.67 218.00 211.50
                         
Annual Sum or Average 3965.83 0.63     3543.98 18.96 1227.67 3731.17 1918.16 21.48 939.17 3412.00
Minimum of Months 226.83 0.63 0.61   1437.92 11.18 0.00 220.67 870.55 16.05 0.00 207.67
Maximum of Months 434.17 0.64 0.61   8490.01 33.30 270.17 392.17 4886.22 37.18 248.83 352.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.65 0.61 01-JAN-08:50 1511.97 18.02 74.00 200.67 843.63 16.72 46.17 160.00
February 275.00 0.64 0.61 01-FEB-08:09 1512.87 14.14 48.83 231.00 922.21 15.98 46.50 194.67
March 304.00 0.63 0.61 01-MAR-07:40 2640.82 16.41 70.33 308.50 1578.00 16.18 44.50 272.67
April 325.17 0.63 0.61 01-APR-08:39 2666.43 13.26 42.50 345.67 1588.35 12.52 0.00 300.83
May 385.83 0.63 0.61 01-MAY-05:40 3058.86 10.22 0.00 394.33 1352.32 12.53 0.00 350.50
June 434.17 0.63 0.61 01-JUN-13:39 3705.48 9.52 0.00 405.83 1632.30 12.07 0.00 372.33
July 417.33 0.62 0.61 01-JUL-06:40 4046.95 9.92 3.67 408.33 1754.47 12.39 0.00 380.17
August 421.33 0.63 0.61 01-AUG-05:40 3030.38 12.59 55.83 378.50 1879.80 11.71 0.00 341.83
September 352.17 0.64 0.61 01-SEP-06:30 2353.22 13.22 52.50 312.33 1375.63 12.40 8.50 277.50
October 317.67 0.64 0.61 01-OCT-07:40 2022.78 15.71 76.50 272.67 1272.19 17.45 73.67 233.67
November 269.50 0.65 0.61 01-NOV-07:49 1167.73 14.33 56.67 214.67 745.98 16.16 53.67 174.33
December 236.83 0.66 0.61 01-DEC-08:50 1169.49 17.76 80.33 188.67 752.12 19.15 72.67 144.50
                         
Annual Sum or Average 3965.83 0.64     2583.71 13.24 561.17 3661.17 1377.67 14.16 345.67 3203.00
Minimum of Months 226.83 0.62 0.61   1167.73 9.52 0.00 188.67 745.98 11.71 0.00 144.50
Maximum of Months 434.17 0.66 0.61   4046.95 18.02 80.33 408.33 1879.80 19.15 73.67 380.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.67 0.61 01-JAN-09:50 482.82 0.00 0.00 168.17 301.22 0.00 0.00 75.83
February 275.00 0.65 0.61 01-FEB-10:20 527.36 0.00 0.00 207.67 343.55 0.00 0.00 137.67
March 304.00 0.63 0.61 01-MAR-07:00 841.75 0.00 0.00 297.50 519.31 0.00 0.00 249.50
April 325.17 0.63 0.61 01-APR-08:39 877.01 0.00 0.00 340.50 549.67 0.00 0.00 286.00
May 385.83 0.62 0.61 01-MAY-05:49 1096.75 0.00 0.00 403.00 670.62 0.00 0.00 366.50
June 434.17 0.63 0.61 01-JUN-13:39 1139.92 0.00 0.00 431.00 657.69 0.00 0.00 397.00
July 417.33 0.62 0.61 01-JUL-06:40 1116.82 0.00 0.00 418.50 667.34 0.00 0.00 387.83
August 421.33 0.63 0.61 01-AUG-05:40 857.49 0.00 0.00 390.17 575.05 0.00 0.00 361.17
September 352.17 0.64 0.61 01-SEP-06:49 695.45 0.00 0.00 307.67 455.59 0.00 0.00 248.00
October 317.67 0.65 0.61 01-OCT-07:49 572.75 0.00 0.00 247.50 368.69 0.00 0.00 174.67
November 269.50 0.67 0.61 01-NOV-08:09 452.19 0.00 0.00 178.67 287.50 0.00 0.00 72.33
December 236.83 0.68 0.61 01-DEC-09:09 390.42 0.00 0.00 144.83 247.99 0.00 0.00 20.67
                         
Annual Sum or Average 3965.83 0.64     802.42 0.00 0.00 3535.17 498.83 0.00 0.00 2777.17
Minimum of Months 226.83 0.62 0.61   390.42 0.00 0.00 144.83 247.99 0.00 0.00 20.67
Maximum of Months 434.17 0.68 0.61   1139.92 0.00 0.00 431.00 670.62 0.00 0.00 397.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.66 0.61 01-JAN-09:50 1391.45 17.13 69.17 194.50 883.82 17.99 58.17 151.83
February 275.00 0.64 0.61 01-FEB-10:20 1853.11 16.87 76.50 229.00 979.31 16.09 48.67 196.00
March 304.00 0.63 0.61 01-MAR-07:00 2486.70 16.15 68.83 304.50 1442.85 17.44 62.17 270.50
April 325.17 0.63 0.61 01-APR-08:39 2604.96 13.56 48.50 334.00 1547.88 12.66 0.00 297.83
May 385.83 0.63 0.61 01-MAY-06:19 2823.08 10.24 0.00 388.33 1813.43 12.69 1.33 350.00
June 434.17 0.63 0.61 01-JUN-13:39 3133.75 9.71 0.00 408.17 1440.99 14.66 47.83 372.50
July 417.33 0.63 0.61 01-JUL-06:40 3655.10 10.00 3.67 396.67 1678.84 14.09 31.50 364.17
August 421.33 0.64 0.61 01-AUG-06:30 2672.63 12.61 56.83 373.00 1577.08 11.85 0.00 339.83
September 352.17 0.64 0.61 01-SEP-06:00 2626.87 14.72 72.33 314.00 1145.72 12.21 5.50 277.17
October 317.67 0.64 0.61 01-OCT-07:00 1611.16 13.92 53.67 270.33 1000.05 15.62 49.33 231.17
November 269.50 0.65 0.61 01-NOV-08:20 1570.29 16.79 78.83 211.67 866.97 16.21 52.50 170.33
December 236.83 0.66 0.61 01-DEC-09:09 953.39 14.75 54.00 192.83 622.98 16.45 49.83 145.00
                         
Annual Sum or Average 3965.83 0.64     2424.56 13.39 582.33 3617.00 1312.34 14.52 406.83 3166.33
Minimum of Months 226.83 0.63 0.61   953.39 9.71 0.00 192.83 622.98 11.85 0.00 145.00
Maximum of Months 434.17 0.66 0.61   3655.10 17.13 78.83 408.17 1813.43 17.99 62.17 372.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.64 0.61 01-JAN-08:50 4461.26 25.61 138.83 220.83 4555.28 37.17 214.33 207.83
February 275.00 0.63 0.61 01-FEB-08:20 7151.54 33.28 239.33 249.17 3068.36 28.59 169.67 240.17
March 304.00 0.63 0.61 01-MAR-07:49 8490.16 31.07 250.17 314.33 1639.37 17.38 6.67 287.00
April 325.17 0.63 0.61 01-APR-08:39 1909.27 11.96 0.00 338.17 1135.34 16.85 0.00 299.17
May 385.83 0.63 0.61 01-MAY-06:10 1688.03 11.89 0.00 384.67 986.12 16.70 0.00 340.00
June 434.17 0.64 0.61 01-JUN-13:39 1438.50 11.44 0.00 392.17 871.44 16.31 0.00 345.00
July 417.33 0.63 0.61 01-JUL-06:40 1546.04 11.83 0.00 391.17 962.87 16.78 0.00 352.50
August 421.33 0.64 0.61 01-AUG-06:19 1660.07 11.14 0.00 368.33 1031.19 16.03 0.00 330.83
September 352.17 0.64 0.61 01-SEP-06:49 2419.04 12.92 29.50 317.50 1226.41 16.19 5.50 287.17
October 317.67 0.63 0.61 01-OCT-07:40 7290.12 32.27 270.17 293.83 2021.62 20.63 76.17 278.50
November 269.50 0.64 0.61 01-NOV-07:49 5029.92 28.72 191.00 240.17 4887.26 36.55 248.83 233.00
December 236.83 0.64 0.61 01-DEC-08:50 3083.93 21.23 108.67 220.67 3718.34 36.67 218.00 211.50
                         
Annual Sum or Average 3965.83 0.63     3543.93 18.92 1227.67 3731.00 1919.30 21.47 939.17 3412.67
Minimum of Months 226.83 0.63 0.61   1438.50 11.14 0.00 220.67 871.44 16.03 0.00 207.83
Maximum of Months 434.17 0.64 0.61   8490.16 33.28 270.17 392.17 4887.26 37.17 248.83 352.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.65 0.61 01-JAN-08:50 1511.69 18.01 74.00 200.67 844.16 16.71 46.17 160.00
February 275.00 0.64 0.61 01-FEB-08:09 1512.44 14.12 48.83 231.00 922.76 15.97 46.50 194.67
March 304.00 0.63 0.61 01-MAR-07:40 2640.59 16.40 70.33 308.50 1579.01 16.17 44.50 272.83
April 325.17 0.63 0.61 01-APR-08:39 2666.21 13.25 42.50 345.67 1589.22 12.51 0.00 300.67
May 385.83 0.63 0.61 01-MAY-05:40 3058.92 10.20 0.00 394.33 1353.32 12.52 0.00 350.67
June 434.17 0.63 0.61 01-JUN-13:39 3705.14 9.51 0.00 405.67 1633.17 12.06 0.00 372.50
July 417.33 0.62 0.61 01-JUL-06:40 4046.53 9.91 3.67 408.17 1755.30 12.38 0.00 380.00
August 421.33 0.63 0.61 01-AUG-05:40 3030.04 12.58 55.83 378.33 1880.61 11.70 0.00 341.83
September 352.17 0.64 0.61 01-SEP-06:30 2352.79 13.21 52.50 312.33 1376.37 12.40 8.50 277.67
October 317.67 0.64 0.61 01-OCT-07:40 2022.38 15.69 76.50 272.67 1272.81 17.45 73.67 233.67
November 269.50 0.65 0.61 01-NOV-07:49 1167.42 14.32 56.67 214.50 746.46 16.15 53.67 174.33
December 236.83 0.66 0.61 01-DEC-08:50 1169.18 17.75 80.33 188.67 752.52 19.15 72.67 144.67
                         
Annual Sum or Average 3965.83 0.64     2583.41 13.23 561.17 3660.50 1378.42 14.15 345.67 3203.50
Minimum of Months 226.83 0.62 0.61   1167.42 9.51 0.00 188.67 746.46 11.70 0.00 144.67
Maximum of Months 434.17 0.66 0.61   4046.53 18.01 80.33 408.17 1880.61 19.15 73.67 380.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.67 0.61 01-JAN-09:50 482.76 0.00 0.00 168.17 301.50 0.00 0.00 76.00
February 275.00 0.65 0.61 01-FEB-10:20 527.23 0.00 0.00 207.67 343.83 0.00 0.00 137.83
March 304.00 0.63 0.61 01-MAR-07:00 841.78 0.00 0.00 297.50 519.84 0.00 0.00 249.50
April 325.17 0.63 0.61 01-APR-08:39 877.01 0.00 0.00 340.67 550.19 0.00 0.00 286.00
May 385.83 0.62 0.61 01-MAY-05:49 1096.79 0.00 0.00 403.00 671.24 0.00 0.00 366.50
June 434.17 0.63 0.61 01-JUN-13:39 1139.75 0.00 0.00 431.00 658.23 0.00 0.00 397.00
July 417.33 0.62 0.61 01-JUL-06:40 1116.59 0.00 0.00 418.50 667.83 0.00 0.00 387.83
August 421.33 0.63 0.61 01-AUG-05:40 857.34 0.00 0.00 390.17 575.47 0.00 0.00 361.17
September 352.17 0.64 0.61 01-SEP-06:49 695.32 0.00 0.00 307.67 455.96 0.00 0.00 248.33
October 317.67 0.65 0.61 01-OCT-07:49 572.65 0.00 0.00 247.17 369.00 0.00 0.00 175.17
November 269.50 0.67 0.61 01-NOV-08:09 452.11 0.00 0.00 178.67 287.75 0.00 0.00 72.67
December 236.83 0.68 0.61 01-DEC-09:09 390.32 0.00 0.00 144.33 248.21 0.00 0.00 20.67
                         
Annual Sum or Average 3965.83 0.64     802.32 0.00 0.00 3534.50 499.25 0.00 0.00 2778.67
Minimum of Months 226.83 0.62 0.61   390.32 0.00 0.00 144.33 248.21 0.00 0.00 20.67
Maximum of Months 434.17 0.68 0.61   1139.75 0.00 0.00 431.00 671.24 0.00 0.00 397.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 226.83 0.66 0.61 01-JAN-09:50 1391.20 17.12 69.17 194.67 884.35 17.98 58.17 152.17
February 275.00 0.64 0.61 01-FEB-10:20 1852.71 16.86 76.50 229.00 979.87 16.08 48.67 196.00
March 304.00 0.63 0.61 01-MAR-07:00 2486.49 16.14 68.83 304.50 1443.87 17.43 62.17 270.67
April 325.17 0.63 0.61 01-APR-08:39 2604.61 13.55 48.50 333.83 1548.87 12.65 0.00 297.83
May 385.83 0.63 0.61 01-MAY-06:19 2822.92 10.23 0.00 388.33 1814.51 12.68 1.33 350.33
June 434.17 0.63 0.61 01-JUN-13:39 3133.54 9.69 0.00 408.17 1441.93 14.65 47.83 372.50
July 417.33 0.63 0.61 01-JUL-06:40 3654.71 9.99 3.67 396.67 1679.75 14.08 31.50 364.17
August 421.33 0.64 0.61 01-AUG-06:30 2672.36 12.59 56.83 372.83 1577.92 11.84 0.00 339.83
September 352.17 0.64 0.61 01-SEP-06:00 2626.42 14.71 72.33 314.00 1146.45 12.21 5.50 277.17
October 317.67 0.64 0.61 01-OCT-07:00 1610.76 13.91 53.67 270.33 1000.67 15.61 49.33 231.33
November 269.50 0.65 0.61 01-NOV-08:20 1569.91 16.78 78.83 211.67 867.46 16.20 52.50 170.67
December 236.83 0.66 0.61 01-DEC-09:09 953.07 14.74 54.00 192.67 623.38 16.44 49.83 145.50
                         
Annual Sum or Average 3965.83 0.64     2424.25 13.38 582.33 3616.67 1313.13 14.51 406.83 3168.17
Minimum of Months 226.83 0.63 0.61   953.07 9.69 0.00 192.67 623.38 11.84 0.00 145.50
Maximum of Months 434.17 0.66 0.61   3654.71 17.12 78.83 408.17 1814.51 17.98 62.17 372.50



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.307740E+11 78379.64 10-JAN-22:00 0.00 0.00 0.00 0.00 0.00
February 0.144052E+11 60096.07 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.551863E+10 49910.69 06-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.341869E+09 21350.25 29-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.347120E+09 15750.31 08-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 23429063.58 3229.47 20-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.261805E+09 11494.23 05-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.292663E+10 37294.45 27-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.140900E+11 64499.47 29-DEC-08:65 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.686887E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.307740E+11 78379.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.350505E+10 15101.01 21-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.111393E+10 15330.00 24-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.252386E+09 14039.86 06-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 258923.08 750.01 29-APR-05:04 0.00 0.00 0.00 0.00 0.00
May 3232001.54 1041.21 08-MAY-05:04 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.136052E+09 14052.35 27-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.837442E+09 15138.26 23-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.584835E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.350505E+10 15330.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.334058E+10 16329.77 18-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.143250E+10 16360.49 24-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.524933E+09 15936.79 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 67796317.61 11212.01 29-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 39677463.37 15593.71 22-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 5460753.98 1073.48 13-SEP-05:10 0.00 0.00 0.00 0.00 0.00
October 47787231.71 5320.48 10-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.492060E+09 15913.36 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.160253E+10 16383.04 14-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.755332E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.334058E+10 16383.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.390686E+10 23248.46 18-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.135058E+10 23391.35 23-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.552121E+09 22004.34 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 81272889.73 23019.90 29-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.125868E+09 23125.32 08-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 60391.77 402.61 17-JUN-05:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 12985109.20 2127.23 19-SEP-05:08 0.00 0.00 0.00 0.00 0.00
October 55922434.18 15178.61 10-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.486619E+09 23233.98 13-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.146394E+10 23332.40 27-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.803622E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.390686E+10 23391.35   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.247536E+10 15236.59 30-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.553614E+09 15221.11 09-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 75727768.96 15221.91 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 9565486.91 8328.73 22-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 40909678.65 15221.46 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.195088E+09 15217.33 29-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.335027E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.247536E+10 15236.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.403999E+12 833963.52 10-JAN-22:00 0.00 0.00 0.00 0.00 0.00
February 0.220774E+12 655764.29 01-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.115505E+12 557085.36 06-MAR-07:07 0.00 0.00 0.00 0.00 0.00
April 0.219481E+11 263998.85 29-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.144372E+11 202179.07 08-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.229272E+09 68273.86 16-JUN-07:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.216361E+10 87116.10 19-SEP-06:30 0.00 0.00 0.00 0.00 0.00
October 0.174230E+11 265625.57 10-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.900261E+11 441046.85 27-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.254949E+12 709780.43 29-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.114145E+13     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.403999E+12 833963.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.117826E+11 642875.84 10-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.333629E+10 635078.82 07-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.137260E+10 642124.48 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.712175E+09 640199.09 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.386562E+10 642282.23 26-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.210693E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117826E+11 642875.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.102670E+12 133107.39 31-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.533363E+11 133412.94 06-FEB-05:04 0.00 0.00 0.00 0.00 0.00
March 0.277940E+11 142909.14 30-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.520309E+10 143001.23 11-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.365258E+10 143247.66 04-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 1419473.38 5854.62 17-JUN-05:08 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 186887.26 1557.39 18-AUG-05:10 0.00 0.00 0.00 0.00 0.00
September 0.899916E+09 138161.90 20-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.452204E+10 143704.09 04-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.266756E+11 143632.44 09-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.668704E+11 133447.29 18-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.291625E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.102670E+12 143704.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.793490E+11 184149.74 30-JAN-05:05 0.00 0.00 0.00 0.00 0.00
February 0.421824E+11 184608.36 07-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.254396E+11 184124.82 06-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.715376E+10 182610.23 15-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 0.465947E+10 193036.84 23-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.190430E+09 24793.72 17-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 68960200.81 34470.55 18-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.191898E+10 119092.67 20-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.671163E+10 183062.07 11-OCT-04:01 0.00 0.00 0.00 0.00 0.00
November 0.266599E+11 190651.09 06-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.568988E+11 184206.92 26-DEC-05:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.251233E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.793490E+11 193036.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.777151E+11 223159.04 31-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.347284E+11 223555.38 06-FEB-05:04 0.00 0.00 0.00 0.00 0.00
March 0.225111E+11 222416.67 06-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.691952E+10 221063.58 15-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 0.593935E+10 237501.07 22-MAY-04:01 0.00 0.00 0.00 0.00 0.00
June 0.232104E+09 44469.25 17-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.100252E+09 26342.15 18-AUG-05:04 0.00 0.00 0.00 0.00 0.00
September 0.125527E+10 133719.14 19-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.341821E+10 221059.37 11-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.207624E+11 222439.38 27-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.485561E+11 223053.34 26-DEC-05:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.222138E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.777151E+11 237501.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.752637E+11 197527.64 30-JAN-05:32 0.00 0.00 0.00 0.00 0.00
February 0.383262E+11 196213.65 09-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.240793E+11 197873.96 06-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.625283E+10 195847.52 29-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.439794E+10 198322.92 22-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.230554E+09 29807.32 17-JUN-05:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.122898E+09 26769.74 18-AUG-05:04 0.00 0.00 0.00 0.00 0.00
September 0.198519E+10 105074.18 19-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.631465E+10 192079.96 10-OCT-04:01 0.00 0.00 0.00 0.00 0.00
November 0.232151E+11 197894.85 27-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.496445E+11 196250.95 16-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.229833E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.752637E+11 198322.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.475527E+11 89110.48 10-JAN-22:00 0.00 0.00 0.00 0.00 0.00
February 0.260495E+11 71469.67 01-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.165262E+11 62893.92 04-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.501516E+10 33551.74 29-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.293757E+10 25563.45 08-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.112422E+09 10150.22 16-JUN-07:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 434926.66 749.25 18-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.793977E+09 14422.64 19-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.373162E+10 32380.73 10-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.126137E+11 47193.63 27-NOV-08:00 0.00 0.00 0.00 0.00 0.00
December 0.320975E+11 78742.78 29-DEC-09:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.147431E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.475527E+11 89110.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.150748E+11 80751.44 02-JAN-05:33 0.00 0.00 0.00 0.00 0.00
February 0.642978E+10 80671.88 21-FEB-05:04 0.00 0.00 0.00 0.00 0.00
March 0.355996E+10 80468.65 27-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.407157E+09 79617.08 10-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.921421E+09 80639.09 08-MAY-05:04 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 1116086.75 730.39 19-SEP-06:00 0.00 0.00 0.00 0.00 0.00
October 0.543820E+09 80601.59 10-OCT-04:04 0.00 0.00 0.00 0.00 0.00
November 0.393014E+10 80599.99 20-NOV-05:04 0.00 0.00 0.00 0.00 0.00
December 0.927172E+10 80480.68 11-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.401399E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.150748E+11 80751.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.187292E+11 16871.31 13-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.107020E+11 16848.64 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.750368E+10 16852.57 13-MAR-05:04 0.00 0.00 0.00 0.00 0.00
April 0.266452E+10 16860.79 10-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.181082E+10 16847.64 01-MAY-04:53 0.00 0.00 0.00 0.00 0.00
June 89248435.13 16730.20 17-JUN-04:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 51136479.22 16775.31 18-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.823461E+09 16828.90 14-SEP-05:02 0.00 0.00 0.00 0.00 0.00
October 0.267787E+10 16889.96 10-OCT-04:17 0.00 0.00 0.00 0.00 0.00
November 0.765841E+10 16863.45 06-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.142313E+11 16840.24 09-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.669417E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.187292E+11 16889.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.127779E+11 18510.74 12-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.701136E+10 18519.88 08-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.494976E+10 18484.67 09-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.186969E+10 18422.18 29-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.126142E+10 18500.99 08-MAY-04:43 0.00 0.00 0.00 0.00 0.00
June 92708234.54 18391.86 17-JUN-04:02 0.00 0.00 0.00 0.00 0.00
July 6315839.09 1929.68 05-JUL-05:08 0.00 0.00 0.00 0.00 0.00
August 54906063.51 12495.54 18-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.648484E+09 18398.53 13-SEP-04:02 0.00 0.00 0.00 0.00 0.00
October 0.184745E+10 18483.33 10-OCT-04:33 0.00 0.00 0.00 0.00 0.00
November 0.539429E+10 18482.03 29-NOV-05:12 0.00 0.00 0.00 0.00 0.00
December 0.992310E+10 18473.88 02-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.458373E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 6315839.09 1929.68   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.127779E+11 18519.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.144157E+11 24081.77 23-JAN-05:54 0.00 0.00 0.00 0.00 0.00
February 0.705826E+10 24123.42 11-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.563984E+10 24102.45 10-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.249950E+10 24057.79 01-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.199787E+10 24115.19 08-MAY-04:14 0.00 0.00 0.00 0.00 0.00
June 0.241683E+09 23969.97 17-JUN-04:02 0.00 0.00 0.00 0.00 0.00
July 13369674.08 2521.05 08-JUL-05:05 0.00 0.00 0.00 0.00 0.00
August 88997247.17 19281.09 18-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.753252E+09 24017.62 12-SEP-04:02 0.00 0.00 0.00 0.00 0.00
October 0.176070E+10 24133.50 10-OCT-04:33 0.00 0.00 0.00 0.00 0.00
November 0.523980E+10 24098.75 22-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.105058E+11 24105.11 19-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.502148E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 13369674.08 2521.05   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144157E+11 24133.50   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.124166E+11 21052.79 18-JAN-05:13 0.00 0.00 0.00 0.00 0.00
February 0.650844E+10 21048.25 17-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.493395E+10 21001.75 04-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.189034E+10 21046.00 29-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.132890E+10 21056.53 22-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.174499E+09 12411.80 17-JUN-04:02 0.00 0.00 0.00 0.00 0.00
July 2735678.76 464.77 08-JUL-05:10 0.00 0.00 0.00 0.00 0.00
August 80894238.45 12330.69 18-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.771192E+09 20911.02 19-SEP-04:01 0.00 0.00 0.00 0.00 0.00
October 0.196356E+10 21040.87 10-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.486095E+10 21091.19 29-NOV-05:12 0.00 0.00 0.00 0.00 0.00
December 0.878715E+10 21033.08 04-DEC-04:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.437192E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2735678.76 464.77   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.124166E+11 21091.19   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.388718E+09 24991.53 10-JAN-22:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.388718E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.388718E+09 24991.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.631469E+09 0.631469E+09 42298.79 27-FEB-15:30 42298.79 0.00
March 0.00 0.00 34245100.02 34245100.02 6873.66 14-MAR-13:30 6873.66 0.00
April 0.00 0.00 0.661475E+10 0.661475E+10 84147.20 07-APR-14:00 84147.20 0.00
May 0.00 0.00 0.181362E+11 0.181362E+11 110739.54 19-MAY-15:20 110739.54 0.02
June 0.00 0.00 0.599180E+11 0.598665E+11 127546.54 29-JUN-14:50 127546.54 0.17
July 0.00 0.00 0.102793E+12 0.102626E+12 153583.55 17-JUL-15:20 153583.55 0.30
August 0.00 0.00 0.950781E+11 0.950781E+11 153907.64 07-AUG-15:20 153907.64 0.14
September 0.00 0.00 0.388729E+11 0.376260E+11 195729.35 07-SEP-15:00 103894.21 0.10
October 0.00 0.00 0.105474E+11 0.105474E+11 102919.20 18-OCT-15:50 102919.20 0.00
November 0.00 0.00 0.560038E+09 0.560038E+09 18833.65 17-NOV-17:00 18833.65 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.333186E+12 0.331721E+12       0.06
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.102793E+12 0.102626E+12 195729.35   153907.64 0.30



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 22025.30 22025.30 3.82 02-JAN-05:43 3.82 0.00
February 0.00 0.00 0.449454E+10 0.449454E+10 298207.97 27-FEB-13:50 298207.97 0.00
March 0.00 0.00 95868854.75 95868854.75 21490.08 14-MAR-13:40 21490.08 0.00
April 0.00 0.00 0.465868E+11 0.465868E+11 634436.50 06-APR-16:00 634436.50 0.00
May 0.00 0.00 0.153363E+12 0.153363E+12 1047502.37 19-MAY-15:30 1047502.37 0.02
June 0.00 0.00 0.507393E+12 0.506952E+12 1202902.78 29-JUN-14:50 1202902.78 0.15
July 0.00 0.00 0.851486E+12 0.850458E+12 1392153.47 17-JUL-15:30 1392153.47 0.27
August 0.00 0.00 0.737744E+12 0.737744E+12 1322502.29 10-AUG-15:40 1322502.29 0.12
September 0.00 0.00 0.339029E+12 0.327943E+12 1792594.27 07-SEP-15:00 952755.13 0.09
October 0.00 0.00 0.830409E+11 0.830409E+11 851650.27 18-OCT-15:00 851650.27 0.00
November 0.00 0.00 0.402796E+10 0.402796E+10 131398.09 17-NOV-17:00 131398.09 0.00
December 0.00 0.00 85216.38 85216.38 1.39 21-DEC-15:00 1.39 0.00
                 
Annual Sum or Average 0.00 0.00 0.272726E+13 0.271471E+13       0.05
Minimum of Months 0.00 0.00 22025.30 22025.30 1.39   1.39 0.00
Maximum of Months 0.00 0.00 0.851486E+12 0.850458E+12 1792594.27   1392153.47 0.27



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 59233.01 59233.01 471.39 17-JAN-04:52 471.39 0.00
February 0.00 0.00 0.319283E+09 0.319283E+09 21923.36 26-FEB-14:21 21923.36 0.00
March 0.00 0.00 2115474.09 2115474.09 1667.83 04-MAR-05:41 1667.83 0.00
April 0.00 0.00 0.433904E+10 0.433904E+10 64046.14 06-APR-16:00 64046.14 0.00
May 0.00 0.00 0.159500E+11 0.159500E+11 125734.12 19-MAY-15:30 125734.12 0.02
June 0.00 0.00 0.557763E+11 0.557211E+11 143214.45 29-JUN-15:00 143214.45 0.15
July 0.00 0.00 0.941281E+11 0.940337E+11 169657.20 17-JUL-15:30 169657.20 0.27
August 0.00 0.00 0.794769E+11 0.794769E+11 157975.35 07-AUG-15:40 157975.35 0.12
September 0.00 0.00 0.347387E+11 0.336262E+11 183238.71 07-SEP-15:20 105335.70 0.09
October 0.00 0.00 0.713518E+10 0.713518E+10 88699.86 18-OCT-15:00 88699.86 0.00
November 0.00 0.00 0.301718E+09 0.301718E+09 10754.42 17-NOV-17:00 10754.42 0.00
December 0.00 0.00 1767.86 1767.86 0.37 01-DEC-06:25 0.37 0.00
                 
Annual Sum or Average 0.00 0.00 0.292167E+12 0.290905E+12       0.05
Minimum of Months 0.00 0.00 1767.86 1767.86 0.37   0.37 0.00
Maximum of Months 0.00 0.00 0.941281E+11 0.940337E+11 183238.71   169657.20 0.27



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 483334.78 483334.78 5566.60 24-JAN-05:01 5566.60 0.00
February 0.00 0.00 0.261761E+09 0.261761E+09 23743.59 27-FEB-15:00 23743.59 0.00
March 0.00 0.00 10369.74 10369.74 17.28 06-MAR-20:00 17.28 0.00
April 0.00 0.00 0.231208E+10 0.231208E+10 49353.32 07-APR-14:00 49353.32 0.00
May 0.00 0.00 0.883342E+10 0.883342E+10 70670.19 29-MAY-14:30 70670.19 0.02
June 0.00 0.00 0.311339E+11 0.311222E+11 67672.65 26-JUN-11:00 67672.65 0.12
July 0.00 0.00 0.530670E+11 0.530396E+11 109277.90 19-JUL-03:02 71895.67 0.22
August 0.00 0.00 0.493011E+11 0.493011E+11 107536.15 06-AUG-17:27 107536.15 0.12
September 0.00 0.00 0.203694E+11 0.200026E+11 123411.10 04-SEP-17:21 123411.10 0.08
October 0.00 0.00 0.573405E+10 0.573405E+10 59639.08 18-OCT-14:00 59639.08 0.00
November 0.00 0.00 68497280.37 68497280.37 25354.47 17-NOV-06:03 25354.47 0.00
December 0.00 0.00 60297.63 60297.63 59.02 27-DEC-17:00 59.02 0.00
                 
Annual Sum or Average 0.00 0.00 0.171082E+12 0.170676E+12       0.05
Minimum of Months 0.00 0.00 10369.74 10369.74 17.28   17.28 0.00
Maximum of Months 0.00 0.00 0.530670E+11 0.530396E+11 123411.10   123411.10 0.22



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.361894E+12 0.328237E+12 142941.73 18-JAN-22:01 128968.58 0.00
February 0.00 0.00 0.575724E+12 0.521962E+12 245398.86 27-FEB-22:03 222099.23 0.00
March 0.00 0.00 0.910631E+12 0.827777E+12 440819.95 31-MAR-24:00 400344.89 0.00
April 0.00 0.00 0.114518E+13 0.104327E+13 449692.72 24-APR-21:02 407430.76 0.00
May 0.00 0.00 0.375766E+12 0.342794E+12 238067.17 31-MAY-24:00 217604.10 0.00
June 0.00 0.00 0.620352E+12 0.573444E+12 330249.59 30-JUN-23:02 309039.51 0.00
July 0.00 0.00 0.894884E+12 0.842211E+12 427103.05 31-JUL-24:00 400827.11 0.00
August 0.00 0.00 0.116120E+13 0.108112E+13 456734.48 04-AUG-00:25 411628.79 0.00
September 0.00 0.00 0.366935E+12 0.336783E+12 238748.02 30-SEP-24:00 217328.36 0.00
October 0.00 0.00 0.649195E+12 0.590735E+12 340945.21 31-OCT-24:00 309906.43 0.00
November 0.00 0.00 0.889805E+12 0.806754E+12 349085.01 06-NOV-22:03 315596.37 0.00
December 0.00 0.00 0.118267E+13 0.107452E+13 448631.08 07-DEC-24:00 406789.80 0.00
                 
Annual Sum or Average 0.00 0.00 0.913423E+13 0.836961E+13       0.00
Minimum of Months 0.00 0.00 0.361894E+12 0.328237E+12 142941.73   128968.58 0.00
Maximum of Months 0.00 0.00 0.118267E+13 0.108112E+13 456734.48   411628.79 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.292943E+10 0.292912E+10 2213.04 13-JAN-16:20 2213.04 0.00
February 0.00 0.00 0.821852E+10 0.821852E+10 4835.78 26-FEB-17:14 4835.78 0.00
March 0.00 0.00 0.149235E+11 0.149235E+11 7458.73 31-MAR-24:00 7458.73 0.00
April 0.00 0.00 0.200314E+11 0.200239E+11 8875.20 22-APR-18:10 8875.20 0.00
May 0.00 0.00 0.562191E+10 0.560040E+10 4145.25 31-MAY-24:00 4145.25 0.00
June 0.00 0.00 0.109113E+11 0.108315E+11 5989.05 30-JUN-23:12 5989.05 0.00
July 0.00 0.00 0.165864E+11 0.164977E+11 7894.49 31-JUL-23:40 7894.49 0.00
August 0.00 0.00 0.215881E+11 0.215254E+11 8876.31 05-AUG-19:57 8876.31 0.00
September 0.00 0.00 0.571231E+10 0.563016E+10 3952.88 30-SEP-24:00 3952.88 0.00
October 0.00 0.00 0.105331E+11 0.105225E+11 5595.08 31-OCT-24:00 5595.08 0.00
November 0.00 0.00 0.146199E+11 0.146182E+11 6539.94 03-NOV-16:00 6485.12 0.00
December 0.00 0.00 0.194867E+11 0.194865E+11 8258.67 10-DEC-16:10 8258.67 0.00
                 
Annual Sum or Average 0.00 0.00 0.151163E+12 0.150808E+12       0.00
Minimum of Months 0.00 0.00 0.292943E+10 0.292912E+10 2213.04   2213.04 0.00
Maximum of Months 0.00 0.00 0.215881E+11 0.215254E+11 8876.31   8876.31 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.857650E+10 0.857355E+10 18216.38 13-JAN-16:30 18216.38 0.00
February 0.00 0.00 0.591237E+11 0.591237E+11 42953.71 28-FEB-17:00 42953.71 0.00
March 0.00 0.00 0.124326E+12 0.124326E+12 65101.25 31-MAR-23:30 65101.25 0.00
April 0.00 0.00 0.179642E+12 0.179566E+12 82573.71 25-APR-18:00 82573.71 0.00
May 0.00 0.00 0.453654E+11 0.451545E+11 39166.80 31-MAY-24:00 39166.80 0.00
June 0.00 0.00 0.100389E+12 0.995931E+11 58527.79 30-JUN-23:55 58527.79 0.00
July 0.00 0.00 0.156653E+12 0.155766E+12 76788.16 31-JUL-23:53 76788.16 0.00
August 0.00 0.00 0.202839E+12 0.202210E+12 84672.67 03-AUG-18:50 84672.67 0.00
September 0.00 0.00 0.480861E+11 0.472823E+11 34809.25 30-SEP-23:40 34809.25 0.00
October 0.00 0.00 0.877275E+11 0.876218E+11 47518.81 31-OCT-24:00 47518.81 0.00
November 0.00 0.00 0.120793E+12 0.120776E+12 60246.14 03-NOV-16:00 59699.37 0.00
December 0.00 0.00 0.158891E+12 0.158888E+12 74945.28 06-DEC-16:10 74671.23 0.00
                 
Annual Sum or Average 0.00 0.00 0.129241E+13 0.128888E+13       0.00
Minimum of Months 0.00 0.00 0.857650E+10 0.857355E+10 18216.38   18216.38 0.00
Maximum of Months 0.00 0.00 0.202839E+12 0.202210E+12 84672.67   84672.67 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.243203E+09 0.243203E+09 1723.69 13-JAN-16:30 1723.69 0.00
February 0.00 0.00 0.427161E+10 0.427161E+10 4244.96 28-FEB-17:00 4244.96 0.00
March 0.00 0.00 0.107834E+11 0.107834E+11 6162.30 28-MAR-17:50 6162.30 0.00
April 0.00 0.00 0.167733E+11 0.167658E+11 8322.34 25-APR-18:00 8322.34 0.00
May 0.00 0.00 0.383926E+10 0.381852E+10 3844.10 31-MAY-24:00 3844.10 0.00
June 0.00 0.00 0.981859E+10 0.973923E+10 5863.59 30-JUN-23:55 5863.59 0.00
July 0.00 0.00 0.156086E+11 0.155200E+11 7643.11 31-JUL-23:53 7643.11 0.00
August 0.00 0.00 0.201452E+11 0.200825E+11 8604.14 05-AUG-19:53 8604.14 0.00
September 0.00 0.00 0.424334E+10 0.416419E+10 3367.31 04-SEP-17:32 3367.31 0.00
October 0.00 0.00 0.736129E+10 0.735096E+10 4584.13 18-OCT-16:50 4584.13 0.00
November 0.00 0.00 0.101784E+11 0.101767E+11 5951.50 03-NOV-16:00 5896.96 0.00
December 0.00 0.00 0.138504E+11 0.138502E+11 7397.97 06-DEC-16:10 7372.79 0.00
                 
Annual Sum or Average 0.00 0.00 0.117117E+12 0.116766E+12       0.00
Minimum of Months 0.00 0.00 0.243203E+09 0.243203E+09 1723.69   1723.69 0.00
Maximum of Months 0.00 0.00 0.201452E+11 0.200825E+11 8604.14   8604.14 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 339023.58 1926652.15 09-JAN-07:10
February 0.00 0.00 01-FEB-00:10 194719.19 1989661.92 07-FEB-06:01
March 0.00 0.00 01-MAR-00:10 98721.51 1928193.29 06-MAR-05:01
April 0.00 0.00 01-APR-00:10 23822.29 1360847.79 29-APR-05:01
May 0.00 0.00 01-MAY-00:05 16234.50 1555198.13 22-MAY-04:01
June 0.00 0.00 01-JUN-00:10 607.54 183589.52 17-JUN-05:03
July 0.00 0.00 01-JUL-00:10 7.81 3713.59 08-JUL-05:05
August 0.00 0.00 01-AUG-00:05 209.91 173688.76 18-AUG-05:02
September 0.00 0.00 01-SEP-00:02 4609.77 867742.81 19-SEP-05:03
October 0.00 0.00 01-OCT-00:10 19000.69 1598765.11 10-OCT-04:01
November 0.00 0.00 01-NOV-00:10 88671.10 1698994.42 27-NOV-06:01
December 0.00 0.00 01-DEC-00:10 216068.91 2009651.10 26-DEC-05:11
             
Annual Sum or Average 0.00     83152.69    
Minimum of Months 0.00 0.00   7.81 3713.59  
Maximum of Months 0.00 0.00   339023.58 2009651.10  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 492.76 23956.38 18-JAN-04:30 0.00 0.00 01-JAN-00:05
February 6290.69 767570.65 27-FEB-15:30 0.00 0.00 01-FEB-00:10
March 2634.02 92255.96 14-MAR-13:30 0.00 0.00 01-MAR-00:10
April 46677.36 1218246.89 06-APR-15:10 0.00 0.00 01-APR-00:10
May 129871.09 1352656.72 19-MAY-15:30 6.53 61494.16 14-MAY-10:22
June 350670.30 1544209.36 29-JUN-15:00 16.05 69554.18 12-JUN-03:02
July 538512.08 1804877.51 17-JUL-15:30 63.19 163386.19 15-JUL-02:52
August 467117.07 1708601.32 07-AUG-15:40 54.45 126076.41 20-AUG-20:23
September 259380.66 2396542.22 07-SEP-15:00 36.76 132020.91 24-SEP-08:53
October 71738.30 1216199.05 16-OCT-13:30 0.24 5264.00 22-OCT-17:02
November 6254.82 353838.65 17-NOV-17:00 0.00 0.00 01-NOV-00:10
December 1290.11 24000.82 27-DEC-17:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 157882.06     14.91    
Minimum of Months 492.76 23956.38   0.00 0.00  
Maximum of Months 538512.08 2396542.22   63.19 163386.19  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 34.41 24-JAN-05:01 0.00 0.00 01-JAN-00:05
February 2825.94 481998.94 27-FEB-13:40 0.00 0.00 01-FEB-00:10
March 75.00 42390.25 14-MAR-13:30 0.00 0.00 01-MAR-00:10
April 27727.77 944406.12 06-APR-16:00 0.00 0.00 01-APR-00:10
May 84618.46 1342256.31 19-MAY-15:30 0.00 0.00 01-MAY-00:05
June 281411.46 1534118.04 29-JUN-14:50 0.00 0.00 01-JUN-00:10
July 447169.61 1795623.09 17-JUL-15:30 0.00 0.00 01-JUL-00:10
August 390756.16 1700251.12 07-AUG-15:40 0.00 0.00 01-AUG-00:05
September 188723.01 2397394.92 07-SEP-15:00 0.00 0.00 01-SEP-00:02
October 47084.92 1218975.67 18-OCT-14:30 0.00 0.00 01-OCT-00:10
November 2414.33 203637.87 17-NOV-17:00 0.00 0.00 01-NOV-00:10
December 0.06 58.19 27-DEC-17:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 123693.85     0.00    
Minimum of Months 0.00 34.41   0.00 0.00  
Maximum of Months 447169.61 2397394.92   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 179034.94 203429.85 13-JAN-16:30 0.00 0.00 01-JAN-00:05
February 339907.49 611324.26 27-FEB-16:00 0.00 0.00 01-FEB-00:10
March 496610.59 646331.74 31-MAR-24:00 0.00 0.00 01-MAR-00:10
April 704405.74 1331712.83 07-APR-14:00 0.00 0.00 01-APR-00:10
May 257424.13 977536.06 20-MAY-16:00 0.00 0.00 01-MAY-00:05
June 577175.23 1382428.54 29-JUN-15:00 0.00 0.00 01-JUN-00:10
July 973324.80 1963229.89 17-JUL-16:00 0.00 0.00 01-JUL-00:10
August 1128273.56 2079262.87 06-AUG-16:00 0.00 0.00 01-AUG-00:05
September 340455.72 1248242.38 02-SEP-17:00 0.00 0.00 01-SEP-00:02
October 387534.22 964208.46 18-OCT-15:00 0.00 0.00 01-OCT-00:10
November 506922.86 752941.62 17-NOV-17:00 0.00 0.00 01-NOV-00:10
December 640762.49 770295.67 10-DEC-02:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 546131.79     0.00    
Minimum of Months 179034.94 203429.85   0.00 0.00  
Maximum of Months 1128273.56 2079262.87   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 17330.34 58856.19 31-JAN-12:40
February 0.00 0.00 01-FEB-00:10 17710.01 59175.84 23-FEB-12:10
March 0.00 0.00 01-MAR-00:10 18546.15 59076.98 01-MAR-12:10
April 0.00 0.00 01-APR-00:10 16883.10 57464.84 03-APR-11:50
May 0.00 0.00 01-MAY-00:05 16524.78 54983.52 01-MAY-11:50
June 0.00 0.00 01-JUN-00:10 15933.46 51687.31 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 14098.76 48649.95 03-JUL-11:50
August 0.00 0.00 01-AUG-00:05 14985.47 46963.74 01-AUG-11:40
September 0.00 0.00 01-SEP-00:02 14315.64 48068.79 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 14900.62 50877.81 31-OCT-12:00
November 0.00 0.00 01-NOV-00:10 15950.63 54068.05 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 16274.20 56868.56 29-DEC-12:40
             
Annual Sum or Average 0.00     16111.88    
Minimum of Months 0.00 0.00   14098.76 46963.74  
Maximum of Months 0.00 0.00   18546.15 59175.84  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 18.01 25051.42 17-JAN-07:00 528.57 116000.37 19-JAN-06:30
February 2575.33 458702.71 27-FEB-15:30 1778.14 138377.22 16-FEB-14:40
March 150.96 52307.38 14-MAR-13:20 2823.17 137969.83 30-MAR-12:30
April 27118.59 883898.27 06-APR-16:00 3109.58 138706.99 28-APR-15:20
May 90919.87 2271897.48 19-MAY-15:30 2253.60 137986.30 03-MAY-13:40
June 329930.68 2560561.27 20-JUN-15:40 889.27 87488.84 14-JUN-17:20
July 543119.95 2607154.70 19-JUL-12:20 550.89 61079.90 05-JUL-12:10
August 469393.00 2300545.91 05-AUG-14:20 1415.82 75695.57 12-AUG-02:55
September 221813.06 4512479.33 07-SEP-15:00 1787.05 111934.85 18-SEP-11:40
October 47414.29 1938263.51 18-OCT-14:50 2553.75 121425.93 03-OCT-09:00
November 2070.83 231704.75 17-NOV-17:00 2314.02 141333.30 26-NOV-22:02
December 77.57 24700.86 08-DEC-14:10 1431.62 137204.81 14-DEC-13:50
             
Annual Sum or Average 145709.61     1783.74    
Minimum of Months 18.01 24700.86   528.57 61079.90  
Maximum of Months 543119.95 4512479.33   3109.58 141333.30  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.162493E+11 0.88 10977.79 01-JAN-00:10 1.59
February 0.144709E+11 0.87 10977.79 01-FEB-06:03 1.60
March 0.174156E+11 0.94 10977.79 01-MAR-04:30 1.59
April 0.161896E+11 0.91 10977.79 01-APR-04:01 1.60
May 0.172389E+11 0.93 10977.79 01-MAY-03:01 1.59
June 0.172626E+11 0.96 10977.79 01-JUN-03:02 1.58
July 0.172372E+11 0.93 10977.79 01-JUL-03:02 1.57
August 0.188642E+11 1.02 10977.79 01-AUG-03:02 1.58
September 0.176503E+11 0.98 10977.79 01-SEP-03:02 1.58
October 0.173438E+11 0.94 10977.79 01-OCT-24:00 1.58
November 0.165060E+11 0.92 10977.79 01-NOV-03:10 1.60
December 0.160803E+11 0.87 10977.79 01-DEC-05:01 1.60
           
Annual Sum or Average 0.202509E+12 0.93      
Minimum of Months 0.144709E+11 0.87 10977.79   1.57
Maximum of Months 0.188642E+11 1.02 10977.79   1.60



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.467664E+10 0.38 16259.86 18-JAN-06:01 1.64
February 0.518639E+10 0.40 16259.86 07-FEB-06:01 1.63
March 0.768867E+10 0.48 13925.18 07-MAR-06:01 1.48
April 0.933259E+10 0.54 18698.99 24-APR-14:50 1.78
May 0.852548E+10 0.50 18636.64 30-MAY-05:03 1.76
June 0.129105E+11 0.68 24814.88 22-JUN-05:02 2.11
July 0.158946E+11 0.76 24814.88 17-JUL-05:02 2.11
August 0.174352E+11 0.83 24814.88 07-AUG-05:02 2.12
September 0.955195E+10 0.56 20542.00 01-SEP-16:00 1.87
October 0.853678E+10 0.49 16714.64 16-OCT-15:50 1.66
November 0.722493E+10 0.46 14605.94 13-NOV-06:01 1.53
December 0.623312E+10 0.41 16259.86 16-DEC-06:02 1.64
           
Annual Sum or Average 0.113197E+12 0.54      
Minimum of Months 0.467664E+10 0.38 13925.18   1.48
Maximum of Months 0.174352E+11 0.83 24814.88   2.12



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.445872E+11 0.42 61109.06 09-JAN-05:01 0.96
February 0.401120E+11 0.40 75899.62 28-FEB-16:00 1.08
March 0.506749E+11 0.42 140377.59 30-MAR-05:02 1.56
April 0.537990E+11 0.41 146523.60 10-APR-05:01 1.61
May 0.636069E+11 0.44 177469.14 22-MAY-04:01 1.80
June 0.989918E+11 0.59 214937.32 21-JUN-05:03 2.02
July 0.118348E+12 0.63 229904.72 18-JUL-05:02 2.12
August 0.115825E+12 0.63 217455.37 07-AUG-03:02 2.05
September 0.743134E+11 0.49 212890.07 05-SEP-03:02 2.01
October 0.557654E+11 0.40 136861.24 05-OCT-05:03 1.54
November 0.450663E+11 0.38 155568.53 06-NOV-06:01 1.67
December 0.437815E+11 0.40 61109.06 26-DEC-05:11 0.96
           
Annual Sum or Average 0.804871E+12 0.47      
Minimum of Months 0.401120E+11 0.38 61109.06   0.96
Maximum of Months 0.118348E+12 0.63 229904.72   2.12



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.573410E+10 0.50 5663.00 02-JAN-04:11 0.86
February 0.450550E+10 0.44 5663.00 01-FEB-05:01 0.87
March 0.481016E+10 0.42 5694.99 28-MAR-16:00 0.87
April 0.453039E+10 0.38 11621.02 25-APR-16:00 1.30
May 0.568372E+10 0.41 17143.44 19-MAY-15:40 1.64
June 0.932005E+10 0.53 20232.69 29-JUN-14:50 1.82
July 0.116491E+11 0.58 25662.76 17-JUL-15:00 2.11
August 0.108198E+11 0.57 24038.74 10-AUG-15:50 2.03
September 0.637016E+10 0.44 17965.07 01-SEP-16:00 1.69
October 0.444869E+10 0.36 10377.51 18-OCT-16:00 1.21
November 0.444823E+10 0.40 5663.00 06-NOV-06:01 0.86
December 0.527489E+10 0.47 5663.00 01-DEC-06:01 0.86
           
Annual Sum or Average 0.775948E+11 0.46      
Minimum of Months 0.444823E+10 0.36 5663.00   0.86
Maximum of Months 0.116491E+11 0.58 25662.76   2.11



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.108099E+12 1.54 40359.42 01-JAN-00:10 1.54
February 0.976375E+11 1.54 40359.42 01-FEB-00:10 1.54
March 0.108099E+12 1.54 40359.42 01-MAR-00:10 1.54
April 0.104612E+12 1.54 40359.42 01-APR-00:10 1.54
May 0.108099E+12 1.54 40359.42 01-MAY-00:05 1.54
June 0.104612E+12 1.54 40359.42 01-JUN-00:10 1.54
July 0.108099E+12 1.54 40359.42 01-JUL-00:10 1.54
August 0.108099E+12 1.54 40359.42 01-AUG-00:05 1.54
September 0.104612E+12 1.54 40359.42 01-SEP-00:02 1.54
October 0.108099E+12 1.54 40359.42 01-OCT-00:10 1.54
November 0.104612E+12 1.54 40359.42 01-NOV-00:10 1.54
December 0.108099E+12 1.54 40359.42 01-DEC-00:10 1.54
           
Annual Sum or Average 0.127277E+13 1.54      
Minimum of Months 0.976375E+11 1.54 40359.42   1.54
Maximum of Months 0.108099E+12 1.54 40359.42   1.54



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.171008E+10 1.05 638.47 01-JAN-00:05 1.05
February 0.154459E+10 1.05 638.47 01-FEB-00:10 1.05
March 0.171008E+10 1.05 638.47 01-MAR-00:10 1.05
April 0.165491E+10 1.05 638.47 01-APR-00:10 1.05
May 0.171008E+10 1.05 638.47 01-MAY-00:05 1.05
June 0.165491E+10 1.05 638.47 01-JUN-00:10 1.05
July 0.171008E+10 1.05 638.47 01-JUL-00:10 1.05
August 0.171008E+10 1.05 638.47 01-AUG-00:05 1.05
September 0.165491E+10 1.05 638.47 01-SEP-00:02 1.05
October 0.171008E+10 1.05 638.47 01-OCT-00:20 1.05
November 0.165491E+10 1.05 638.47 01-NOV-00:10 1.05
December 0.171008E+10 1.05 638.47 01-DEC-00:10 1.05
           
Annual Sum or Average 0.201348E+11 1.05      
Minimum of Months 0.154459E+10 1.05 638.47   1.05
Maximum of Months 0.171008E+10 1.05 638.47   1.05



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.163745E+11 1.05 6113.55 01-JAN-00:05 1.05
February 0.147899E+11 1.05 6113.55 01-FEB-00:15 1.05
March 0.163745E+11 1.05 6113.55 01-MAR-00:10 1.05
April 0.158463E+11 1.05 6113.55 01-APR-00:10 1.05
May 0.163745E+11 1.05 6113.55 01-MAY-00:05 1.05
June 0.158463E+11 1.05 6113.55 01-JUN-00:10 1.05
July 0.163745E+11 1.05 6113.55 01-JUL-00:10 1.05
August 0.163745E+11 1.05 6113.55 01-AUG-00:10 1.05
September 0.158463E+11 1.05 6113.55 01-SEP-00:02 1.05
October 0.163745E+11 1.05 6113.55 01-OCT-00:10 1.05
November 0.158463E+11 1.05 6113.55 01-NOV-00:10 1.05
December 0.163745E+11 1.05 6113.55 01-DEC-00:10 1.05
           
Annual Sum or Average 0.192797E+12 1.05      
Minimum of Months 0.147899E+11 1.05 6113.55   1.05
Maximum of Months 0.163745E+11 1.05 6113.55   1.05



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.166690E+10 1.05 622.35 01-JAN-00:05 1.05
February 0.150558E+10 1.05 622.35 01-FEB-00:10 1.05
March 0.166690E+10 1.05 622.35 01-MAR-00:10 1.05
April 0.161313E+10 1.05 622.35 01-APR-00:10 1.05
May 0.166690E+10 1.05 622.35 01-MAY-00:05 1.05
June 0.161313E+10 1.05 622.35 01-JUN-00:10 1.05
July 0.166690E+10 1.05 622.35 01-JUL-00:10 1.05
August 0.166690E+10 1.05 622.35 01-AUG-00:05 1.05
September 0.161313E+10 1.05 622.35 01-SEP-00:02 1.05
October 0.166690E+10 1.05 622.35 01-OCT-00:10 1.05
November 0.161313E+10 1.05 622.35 01-NOV-00:10 1.05
December 0.166690E+10 1.05 622.35 01-DEC-00:10 1.05
           
Annual Sum or Average 0.196264E+11 1.05      
Minimum of Months 0.150558E+10 1.05 622.35   1.05
Maximum of Months 0.166690E+10 1.05 622.35   1.05



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.382936E+10 0.344643E+10 6404.75 09-JAN-07:02 5764.27 5764.27 46.63 12.50
February 0.197898E+10 0.178108E+10 6309.81 06-FEB-05:03 5678.83 5678.83 46.20 11.99
March 0.110024E+10 0.990215E+09 6283.28 06-MAR-05:01 5654.95 5654.95 43.34 11.87
April 0.251030E+09 0.225927E+09 4820.70 29-APR-05:01 4338.63 4338.63 36.03 7.05
May 0.181308E+09 0.163178E+09 4907.11 22-MAY-05:01 4416.40 4416.40 38.66 7.25
June 6245492.40 5620943.16 715.12 17-JUN-05:03 643.61 643.61 22.68 0.76
July 83592.67 75233.40 14.72 08-JUL-05:05 13.25 13.25 20.93 0.02
August 2231147.71 2008032.94 670.92 18-AUG-05:02 603.82 603.82 21.25 0.71
September 47950752.15 43155676.94 3203.67 19-SEP-05:03 2883.30 2883.30 28.76 4.00
October 0.206870E+09 0.186183E+09 4863.47 10-OCT-04:01 4377.13 4377.13 28.60 7.17
November 0.956863E+09 0.861177E+09 6278.26 27-NOV-06:01 5650.43 5650.43 47.82 11.82
December 0.242609E+10 0.218348E+10 6262.11 18-DEC-06:02 5635.90 5635.90 46.00 11.75
                 
Annual Sum or Average 0.109872E+11 0.988852E+10            
Minimum of Months 83592.67 75233.40 14.72   13.25 13.25 20.93 0.02
Maximum of Months 0.382936E+10 0.344643E+10 6404.75   5764.27 5764.27 47.82 12.50



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 209.41 188.47 2.58 24-JAN-05:01 2.33 2.33 6.71 0.55
February 2017178.01 1815460.21 195.34 27-FEB-13:40 175.81 175.81 8.98 11.74
March 25313.42 22782.08 5.53 14-MAR-13:30 4.98 4.98 8.64 1.06
April 19798686.55 17818817.89 384.19 06-APR-16:00 345.77 345.77 7.99 16.70
May 98274110.25 88446699.23 2848.37 19-MAY-12:10 2563.53 2563.53 7.13 42.59
June 0.489459E+09 0.440513E+09 3679.79 30-JUN-16:00 3311.81 3311.81 6.72 47.56
July 0.106374E+10 0.957366E+09 5019.76 31-JUL-15:20 4517.78 4517.78 6.72 54.25
August 0.939353E+09 0.845418E+09 5156.33 07-AUG-13:00 4640.70 4640.70 6.72 54.86
September 0.342613E+09 0.308352E+09 6052.29 05-SEP-12:30 5447.06 5447.06 7.52 58.66
October 43627842.93 39265058.64 725.29 18-OCT-14:30 652.76 652.76 7.44 22.83
November 1168879.76 1051991.78 54.75 03-NOV-14:00 49.27 49.27 8.71 5.63
December 20.86 18.78 0.01 27-DEC-17:00 0.01 0.01 8.48 0.00
                 
Annual Sum or Average 0.300008E+10 0.270007E+10            
Minimum of Months 20.86 18.78 0.01   0.01 0.01 6.71 0.00
Maximum of Months 0.106374E+10 0.957366E+09 6052.29   5447.06 5447.06 8.98 58.66



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.739139E+09 0.665225E+09 13408.88 01-JAN-13:32 12068.00 12068.00 8.43 93.98
February 0.247169E+10 0.222452E+10 13408.88 01-FEB-03:55 12068.00 12068.00 8.43 93.98
March 0.376656E+10 0.338990E+10 13408.88 01-MAR-05:01 12068.00 12068.00 8.43 93.98
April 0.696954E+10 0.627259E+10 13408.88 01-APR-12:15 12068.00 12068.00 8.43 93.98
May 0.104325E+11 0.938926E+10 13408.88 01-MAY-12:10 12068.00 12068.00 8.43 93.98
June 0.178197E+11 0.160377E+11 13408.88 01-JUN-03:02 12068.00 12068.00 8.74 93.98
July 0.242069E+11 0.217862E+11 13408.88 01-JUL-00:22 12068.00 12068.00 7.91 93.98
August 0.236964E+11 0.213267E+11 13408.88 01-AUG-00:12 12068.00 12068.00 7.98 93.98
September 0.145354E+11 0.130818E+11 13408.88 01-SEP-00:02 12068.00 12068.00 8.06 93.98
October 0.764440E+10 0.687996E+10 13408.88 02-OCT-05:05 12068.00 12068.00 8.72 93.98
November 0.347750E+10 0.312975E+10 13408.88 01-NOV-04:01 12068.00 12068.00 8.64 93.98
December 0.193407E+10 0.174066E+10 13408.88 01-DEC-05:43 12068.00 12068.00 8.43 93.98
                 
Annual Sum or Average 0.117694E+12 0.105924E+12            
Minimum of Months 0.739139E+09 0.665225E+09 13408.88   12068.00 12068.00 7.91 93.98
Maximum of Months 0.242069E+11 0.217862E+11 13408.88   12068.00 12068.00 8.74 93.98



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.981732E+10 0.883559E+10 3665.37 01-JAN-00:05 3298.83 3298.83 21.85 15.31
February 0.886726E+10 0.798053E+10 3665.37 01-FEB-00:10 3298.83 3298.83 24.23 15.31
March 0.981732E+10 0.883559E+10 3665.37 01-MAR-00:10 3298.83 3298.83 27.41 15.31
April 0.950063E+10 0.855057E+10 3665.37 01-APR-00:10 3298.83 3298.83 30.39 15.31
May 0.981732E+10 0.883559E+10 3665.37 01-MAY-00:05 3298.83 3298.83 22.35 15.31
June 0.950063E+10 0.855057E+10 3665.37 01-JUN-00:10 3298.83 3298.83 26.00 15.31
July 0.981732E+10 0.883559E+10 3665.37 01-JUL-00:10 3298.83 3298.83 34.65 15.31
August 0.981732E+10 0.883559E+10 3665.37 01-AUG-00:05 3298.83 3298.83 38.59 15.31
September 0.950063E+10 0.855057E+10 3665.37 01-SEP-00:02 3298.83 3298.83 25.52 15.31
October 0.981732E+10 0.883559E+10 3665.37 01-OCT-00:10 3298.83 3298.83 24.97 15.31
November 0.950063E+10 0.855057E+10 3665.37 01-NOV-00:10 3298.83 3298.83 27.65 15.31
December 0.981732E+10 0.883559E+10 3665.37 01-DEC-00:10 3298.83 3298.83 30.04 15.31
                 
Annual Sum or Average 0.115591E+12 0.104032E+12            
Minimum of Months 0.886726E+10 0.798053E+10 3665.37   3298.83 3298.83 21.85 15.31
Maximum of Months 0.981732E+10 0.883559E+10 3665.37   3298.83 3298.83 38.59 15.31



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 11967951.72 3590385.52 5.96 01-JAN-06:03 1.79 1.79 55.15 0.44
February 10809762.85 3242928.85 5.96 01-FEB-06:03 1.79 1.79 56.00 0.44
March 11967951.72 3590385.52 5.96 01-MAR-06:02 1.79 1.79 56.09 0.44
April 11581888.76 3474566.63 5.96 01-APR-05:01 1.79 1.79 56.22 0.44
May 11967951.72 3590385.52 5.96 01-MAY-05:02 1.79 1.79 55.87 0.44
June 11581888.76 3474566.63 5.96 01-JUN-05:03 1.79 1.79 56.57 0.44
July 11967951.72 3590385.52 5.96 01-JUL-05:03 1.79 1.79 56.58 0.44
August 11967951.72 3590385.52 5.96 01-AUG-05:03 1.79 1.79 56.27 0.44
September 11581888.76 3474566.63 5.96 01-SEP-05:03 1.79 1.79 56.24 0.44
October 11967951.72 3590385.52 5.96 01-OCT-05:10 1.79 1.79 56.19 0.44
November 11581888.76 3474566.63 5.96 01-NOV-05:03 1.79 1.79 55.37 0.44
December 11967951.72 3590385.52 5.96 01-DEC-06:01 1.79 1.79 56.05 0.44
                 
Annual Sum or Average 0.140913E+09 42273893.99            
Minimum of Months 10809762.85 3242928.85 5.96   1.79 1.79 55.15 0.44
Maximum of Months 11967951.72 3590385.52 5.96   1.79 1.79 56.58 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.914075E+09 0.822667E+09 16585.00 17-JAN-07:00 14926.50 14926.50 21.21 55.25
February 0.305701E+10 0.275131E+10 16607.41 27-FEB-15:30 14946.67 14946.67 23.09 55.25
March 0.465799E+10 0.419220E+10 16586.41 14-MAR-13:20 14927.77 14927.77 21.33 55.25
April 0.872245E+10 0.785020E+10 33208.99 07-APR-14:40 29888.09 29888.09 22.83 110.49
May 0.135037E+11 0.121533E+11 33289.14 19-MAY-15:30 29960.23 29960.23 26.02 110.49
June 0.264279E+11 0.237851E+11 33306.59 20-JUN-15:40 29975.93 29975.93 26.64 110.49
July 0.385343E+11 0.346808E+11 33309.41 19-JUL-12:20 29978.47 29978.47 26.75 110.49
August 0.364960E+11 0.328464E+11 33290.87 05-AUG-14:20 29961.79 29961.79 26.08 110.49
September 0.205499E+11 0.184949E+11 33367.13 07-SEP-14:40 30030.41 30030.41 29.39 110.49
October 0.999592E+10 0.899632E+10 33268.99 18-OCT-14:50 29942.09 29942.09 25.30 110.49
November 0.430083E+10 0.387075E+10 16595.68 17-NOV-17:00 14936.11 14936.11 22.10 55.25
December 0.239182E+10 0.215263E+10 16584.99 08-DEC-14:10 14926.49 14926.49 21.21 55.25
                 
Annual Sum or Average 0.169552E+12 0.152597E+12            
Minimum of Months 0.914075E+09 0.822667E+09 16584.99   14926.49 14926.49 21.21 55.25
Maximum of Months 0.385343E+11 0.346808E+11 33367.13   30030.41 30030.41 29.39 110.49



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 35.01 35.01 339023.58 1926652.15 09-JAN-07:10
February 0.00 0.00 01-FEB-00:10 30.91 30.91 194719.19 1989661.92 07-FEB-06:01
March 0.00 0.00 01-MAR-00:10 24.06 24.06 98721.51 1928193.29 06-MAR-05:01
April 0.00 0.00 01-APR-00:10 25.44 25.44 23822.29 1360847.79 29-APR-05:01
May 0.00 0.00 01-MAY-00:05 22.12 22.12 16234.50 1555198.13 22-MAY-04:01
June 0.00 0.00 01-JUN-00:10 21.57 21.57 607.54 183589.52 17-JUN-05:03
July 0.00 0.00 01-JUL-00:10 21.00 21.00 7.81 3713.59 08-JUL-05:05
August 0.00 0.00 01-AUG-00:05 20.84 20.84 209.91 173688.76 18-AUG-05:02
September 0.00 0.00 01-SEP-00:02 20.82 20.82 4609.77 867742.81 19-SEP-05:03
October 0.00 0.00 01-OCT-00:10 20.00 20.00 19000.69 1598765.11 10-OCT-04:01
November 0.00 0.00 01-NOV-00:10 25.28 25.28 88671.10 1698994.42 27-NOV-06:01
December 0.00 0.00 01-DEC-00:10 28.78 28.78 216068.91 2009651.10 26-DEC-05:11
                 
Annual Sum or Average 0.00         83152.69    
Minimum of Months 0.00 0.00   20.00 20.00 7.81 3713.59  
Maximum of Months 0.00 0.00   35.01 35.01 339023.58 2009651.10  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 492.76 23956.38 18-JAN-04:30 8.43 8.40 0.00 0.00 01-JAN-00:05
February 6290.69 767570.65 27-FEB-15:30 9.82 8.84 0.00 0.00 01-FEB-00:10
March 2634.02 92255.96 14-MAR-13:30 8.60 8.49 0.00 0.00 01-MAR-00:10
April 46677.36 1218246.89 06-APR-15:10 10.61 8.94 0.00 0.00 01-APR-00:10
May 129871.09 1352656.72 19-MAY-15:30 10.13 6.70 6.53 61494.16 14-MAY-10:22
June 350670.30 1544209.36 29-JUN-15:00 10.62 6.70 16.05 69554.18 12-JUN-03:02
July 538512.08 1804877.51 17-JUL-15:30 11.28 6.70 63.19 163386.19 15-JUL-02:52
August 467117.07 1708601.32 07-AUG-15:40 11.04 6.70 54.45 126076.41 20-AUG-20:23
September 259380.66 2396542.22 07-SEP-15:00 13.14 7.44 36.76 132020.91 24-SEP-08:53
October 71738.30 1216199.05 16-OCT-13:30 10.63 8.96 0.24 5264.00 22-OCT-17:02
November 6254.82 353838.65 17-NOV-17:00 9.03 8.57 0.00 0.00 01-NOV-00:10
December 1290.11 24000.82 27-DEC-17:00 8.43 8.40 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 157882.06         14.91    
Minimum of Months 492.76 23956.38   8.43 6.70 0.00 0.00  
Maximum of Months 538512.08 2396542.22   13.14 8.96 63.19 163386.19  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 34.41 24-JAN-05:01 6.71 8.40 0.00 0.00 01-JAN-00:05
February 2825.94 481998.94 27-FEB-13:40 16.51 8.99 0.00 0.00 01-FEB-00:10
March 75.00 42390.25 14-MAR-13:30 16.23 8.49 0.00 0.00 01-MAR-00:10
April 27727.77 944406.12 06-APR-16:00 20.22 8.52 0.00 0.00 01-APR-00:10
May 84618.46 1342256.31 19-MAY-15:30 15.23 6.70 0.00 0.00 01-MAY-00:05
June 281411.46 1534118.04 29-JUN-14:50 22.35 6.70 0.00 0.00 01-JUN-00:10
July 447169.61 1795623.09 17-JUL-15:30 15.29 6.70 0.00 0.00 01-JUL-00:10
August 390756.16 1700251.12 07-AUG-15:40 14.42 6.70 0.00 0.00 01-AUG-00:05
September 188723.01 2397394.92 07-SEP-15:00 18.80 7.57 0.00 0.00 01-SEP-00:02
October 47084.92 1218975.67 18-OCT-14:30 19.47 6.96 0.00 0.00 01-OCT-00:10
November 2414.33 203637.87 17-NOV-17:00 16.97 8.58 0.00 0.00 01-NOV-00:10
December 0.06 58.19 27-DEC-17:00 14.51 8.40 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 123693.85         0.00    
Minimum of Months 0.00 34.41   6.71 6.70 0.00 0.00  
Maximum of Months 447169.61 2397394.92   22.35 8.99 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 179034.94 203429.85 13-JAN-16:30 22.15 18.33 0.00 0.00 01-JAN-00:05
February 339907.49 611324.26 27-FEB-16:00 29.74 22.74 0.00 0.00 01-FEB-00:10
March 496610.59 646331.74 31-MAR-24:00 30.38 18.33 0.00 0.00 01-MAR-00:10
April 704405.74 1331712.83 07-APR-14:00 42.87 30.32 0.00 0.00 01-APR-00:10
May 257424.13 977536.06 20-MAY-16:00 36.46 32.30 0.00 0.00 01-MAY-00:05
June 577175.23 1382428.54 29-JUN-15:00 43.78 36.36 0.00 0.00 01-JUN-00:10
July 973324.80 1963229.89 17-JUL-16:00 54.13 43.34 0.00 0.00 01-JUL-00:10
August 1128273.56 2079262.87 06-AUG-16:00 56.18 43.08 0.00 0.00 01-AUG-00:05
September 340455.72 1248242.38 02-SEP-17:00 41.37 36.90 0.00 0.00 01-SEP-00:02
October 387534.22 964208.46 18-OCT-15:00 36.21 29.00 0.00 0.00 01-OCT-00:10
November 506922.86 752941.62 17-NOV-17:00 32.35 22.58 0.00 0.00 01-NOV-00:10
December 640762.49 770295.67 10-DEC-02:00 32.66 20.56 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 546131.79         0.00    
Minimum of Months 179034.94 203429.85   22.15 18.33 0.00 0.00  
Maximum of Months 1128273.56 2079262.87   56.18 43.34 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 56.14 56.14 17330.34 58856.19 31-JAN-12:40
February 0.00 0.00 01-FEB-00:10 56.72 56.72 17710.01 59175.84 23-FEB-12:10
March 0.00 0.00 01-MAR-00:10 56.70 56.70 18546.15 59076.98 01-MAR-12:10
April 0.00 0.00 01-APR-00:10 56.62 56.62 16883.10 57464.84 03-APR-11:50
May 0.00 0.00 01-MAY-00:05 56.72 56.72 16524.78 54983.52 01-MAY-11:50
June 0.00 0.00 01-JUN-00:10 57.12 57.12 15933.46 51687.31 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 57.22 57.22 14098.76 48649.95 03-JUL-11:50
August 0.00 0.00 01-AUG-00:05 56.79 56.79 14985.47 46963.74 01-AUG-11:40
September 0.00 0.00 01-SEP-00:02 57.13 57.13 14315.64 48068.79 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 57.20 57.20 14900.62 50877.81 31-OCT-12:00
November 0.00 0.00 01-NOV-00:10 56.01 56.01 15950.63 54068.05 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 56.48 56.48 16274.20 56868.56 29-DEC-12:40
                 
Annual Sum or Average 0.00         16111.88    
Minimum of Months 0.00 0.00   56.01 56.01 14098.76 46963.74  
Maximum of Months 0.00 0.00   57.22 57.22 18546.15 59175.84  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 18.01 25051.42 17-JAN-07:00 21.21 20.26 528.57 116000.37 19-JAN-06:30
February 2575.33 458702.71 27-FEB-15:30 23.09 21.10 1778.14 138377.22 16-FEB-14:40
March 150.96 52307.38 14-MAR-13:20 21.33 20.64 2823.17 137969.83 30-MAR-12:30
April 27118.59 883898.27 06-APR-16:00 24.93 21.10 3109.58 138706.99 28-APR-15:20
May 90919.87 2271897.48 19-MAY-15:30 26.02 21.10 2253.60 137986.30 03-MAY-13:40
June 329930.68 2560561.27 20-JUN-15:40 26.64 22.96 889.27 87488.84 14-JUN-17:20
July 543119.95 2607154.70 19-JUL-12:20 26.75 22.93 550.89 61079.90 05-JUL-12:10
August 469393.00 2300545.91 05-AUG-14:20 26.08 21.92 1415.82 75695.57 12-AUG-02:55
September 221813.06 4512479.33 07-SEP-15:00 30.87 25.36 1787.05 111934.85 18-SEP-11:40
October 47414.29 1938263.51 18-OCT-14:50 25.30 21.10 2553.75 121425.93 03-OCT-09:00
November 2070.83 231704.75 17-NOV-17:00 22.10 21.10 2314.02 141333.30 26-NOV-22:02
December 77.57 24700.86 08-DEC-14:10 21.21 20.27 1431.62 137204.81 14-DEC-13:50
                 
Annual Sum or Average 145709.61         1783.74    
Minimum of Months 18.01 24700.86   21.21 20.26 528.57 61079.90  
Maximum of Months 543119.95 4512479.33   30.87 25.36 3109.58 141333.30  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.440019E+11 0.00 0.00 0.467664E+10 0.00 0.00
February 0.188558E+11 0.00 0.631469E+09 0.518639E+10 0.00 0.00
March 0.692379E+10 0.00 34245100.02 0.768867E+10 0.00 0.00
April 0.491197E+09 0.00 0.661475E+10 0.933259E+10 0.00 0.00
May 0.525464E+09 0.00 0.181362E+11 0.852548E+10 0.00 0.00
June 60391.77 0.00 0.599180E+11 0.129105E+11 0.00 0.00
July 0.00 0.00 0.102793E+12 0.158946E+11 0.00 0.00
August 0.00 0.00 0.950781E+11 0.174352E+11 0.00 0.00
September 41874926.76 0.00 0.388729E+11 0.955195E+10 0.00 0.00
October 0.365514E+09 0.00 0.105474E+11 0.853678E+10 0.00 0.00
November 0.408227E+10 0.00 0.560038E+09 0.722493E+10 0.00 0.00
December 0.181890E+11 0.00 0.00 0.623312E+10 0.00 0.00
             
Annual Sum or Average 0.934769E+11 0.00 0.333186E+12 0.113197E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.467664E+10 0.00 0.00
Maximum of Months 0.440019E+11 0.00 0.102793E+12 0.174352E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.750779E+12 0.00 22025.30 0.445872E+11 0.00 0.00
February 0.392684E+12 0.00 0.449454E+10 0.401120E+11 0.00 0.00
March 0.216701E+12 0.00 95868854.75 0.506749E+11 0.00 0.00
April 0.474773E+11 0.00 0.465868E+11 0.537990E+11 0.00 0.00
May 0.330866E+11 0.00 0.153363E+12 0.636069E+11 0.00 0.00
June 0.883779E+09 0.00 0.507393E+12 0.989918E+11 0.00 0.00
July 0.00 0.00 0.851486E+12 0.118348E+12 0.00 0.00
August 0.292297E+09 0.00 0.737744E+12 0.115825E+12 0.00 0.00
September 0.822296E+10 0.00 0.339029E+12 0.743134E+11 0.00 0.00
October 0.383895E+11 0.00 0.830409E+11 0.557654E+11 0.00 0.00
November 0.188051E+12 0.00 0.402796E+10 0.450663E+11 0.00 0.00
December 0.480785E+12 0.00 85216.38 0.437815E+11 0.00 0.00
             
Annual Sum or Average 0.215735E+13 0.00 0.272726E+13 0.804871E+12 0.00 0.00
Minimum of Months 0.00 0.00 22025.30 0.401120E+11 0.00 0.00
Maximum of Months 0.750779E+12 0.00 0.851486E+12 0.118348E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.120967E+12 0.00 59233.01 0.573410E+10 0.00 0.00
February 0.637594E+11 0.00 0.319283E+09 0.450550E+10 0.00 0.00
March 0.431134E+11 0.00 2115474.09 0.481016E+10 0.00 0.00
April 0.143464E+11 0.00 0.433904E+10 0.453039E+10 0.00 0.00
May 0.102580E+11 0.00 0.159500E+11 0.568372E+10 0.00 0.00
June 0.710561E+09 0.00 0.557763E+11 0.932005E+10 0.00 0.00
July 22421191.93 0.00 0.941281E+11 0.116491E+11 0.00 0.00
August 0.276369E+09 0.00 0.794769E+11 0.108198E+11 0.00 0.00
September 0.379148E+10 0.00 0.347387E+11 0.637016E+10 0.00 0.00
October 0.125250E+11 0.00 0.713518E+10 0.444869E+10 0.00 0.00
November 0.396973E+11 0.00 0.301718E+09 0.444823E+10 0.00 0.00
December 0.848166E+11 0.00 1767.86 0.527489E+10 0.00 0.00
             
Annual Sum or Average 0.394284E+12 0.00 0.292167E+12 0.775948E+11 0.00 0.00
Minimum of Months 22421191.93 0.00 1767.86 0.444823E+10 0.00 0.00
Maximum of Months 0.120967E+12 0.00 0.941281E+11 0.116491E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.388718E+09 0.00 483334.78 0.162493E+11 0.00 0.00
February 0.00 0.00 0.261761E+09 0.144709E+11 0.00 0.00
March 0.00 0.00 10369.74 0.174156E+11 0.00 0.00
April 0.00 0.00 0.231208E+10 0.161896E+11 0.00 0.00
May 0.00 0.00 0.883342E+10 0.172389E+11 0.00 0.00
June 0.00 0.00 0.311339E+11 0.172626E+11 0.00 0.00
July 0.00 0.00 0.530670E+11 0.172372E+11 0.00 0.00
August 0.00 0.00 0.493011E+11 0.188642E+11 0.00 0.00
September 0.00 0.00 0.203694E+11 0.176503E+11 0.00 0.00
October 0.00 0.00 0.573405E+10 0.173438E+11 0.00 0.00
November 0.00 0.00 68497280.37 0.165060E+11 0.00 0.00
December 0.00 0.00 60297.63 0.160803E+11 0.00 0.00
             
Annual Sum or Average 0.388718E+09 0.00 0.171082E+12 0.202509E+12 0.00 0.00
Minimum of Months 0.00 0.00 10369.74 0.144709E+11 0.00 0.00
Maximum of Months 0.388718E+09 0.00 0.530670E+11 0.188642E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.453786E+12 0.241034E+12 0.00 15.27
February 0.00 0.00 0.714253E+12 0.297567E+12 0.00 22.84
March 0.00 0.00 0.112057E+13 0.410583E+12 0.00 34.43
April 0.00 0.00 0.140686E+13 0.477581E+12 0.00 41.40
May 0.00 0.00 0.473988E+12 0.243331E+12 0.00 13.77
June 0.00 0.00 0.789921E+12 0.323513E+12 0.00 18.35
July 0.00 0.00 0.116273E+13 0.430705E+12 0.00 20.37
August 0.00 0.00 0.148831E+13 0.521240E+12 0.00 32.00
September 0.00 0.00 0.467612E+12 0.236817E+12 0.00 11.73
October 0.00 0.00 0.807962E+12 0.331223E+12 0.00 23.94
November 0.00 0.00 0.109525E+13 0.401819E+12 0.00 34.13
December 0.00 0.00 0.144567E+13 0.490845E+12 0.00 44.55
             
Annual Sum or Average 0.00 0.00 0.114269E+14 0.440626E+13 0.00 312.78
Minimum of Months 0.00 0.00 0.453786E+12 0.236817E+12 0.00 11.73
Maximum of Months 0.00 0.00 0.148831E+13 0.521240E+12 0.00 44.55



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.377167E+10 0.255231E+10 0.00 0.00
February 0.00 0.00 0.103821E+11 0.370816E+10 0.00 0.00
March 0.00 0.00 0.186220E+11 0.540850E+10 0.00 0.00
April 0.00 0.00 0.248643E+11 0.648790E+10 0.00 0.00
May 0.00 0.00 0.715745E+10 0.324562E+10 0.00 0.00
June 0.00 0.00 0.139573E+11 0.470094E+10 0.00 0.00
July 0.00 0.00 0.216282E+11 0.675179E+10 0.00 0.00
August 0.00 0.00 0.279449E+11 0.806685E+10 0.00 0.00
September 0.00 0.00 0.733016E+10 0.327277E+10 0.00 0.00
October 0.00 0.00 0.132129E+11 0.438985E+10 0.00 0.00
November 0.00 0.00 0.182110E+11 0.524603E+10 0.00 0.00
December 0.00 0.00 0.242133E+11 0.643666E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.191295E+12 0.602674E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.377167E+10 0.255231E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.279449E+11 0.806685E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.112556E+11 0.190537E+11 0.00 0.00
February 0.00 0.00 0.750458E+11 0.307120E+11 0.00 0.00
March 0.00 0.00 0.155586E+12 0.476348E+11 0.00 0.00
April 0.00 0.00 0.223398E+12 0.596027E+11 0.00 0.00
May 0.00 0.00 0.579438E+11 0.289529E+11 0.00 0.00
June 0.00 0.00 0.128581E+12 0.440384E+11 0.00 0.00
July 0.00 0.00 0.204389E+12 0.641106E+11 0.00 0.00
August 0.00 0.00 0.262791E+12 0.763267E+11 0.00 0.00
September 0.00 0.00 0.619105E+11 0.296707E+11 0.00 0.00
October 0.00 0.00 0.110362E+12 0.390086E+11 0.00 0.00
November 0.00 0.00 0.150941E+12 0.459949E+11 0.00 0.00
December 0.00 0.00 0.198204E+12 0.556875E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.164041E+13 0.540793E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.112556E+11 0.190537E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.262791E+12 0.763267E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.321811E+09 0.174551E+10 0.00 0.00
February 0.00 0.00 0.544551E+10 0.267948E+10 0.00 0.00
March 0.00 0.00 0.135316E+11 0.441505E+10 0.00 0.00
April 0.00 0.00 0.209056E+11 0.574544E+10 0.00 0.00
May 0.00 0.00 0.491702E+10 0.274466E+10 0.00 0.00
June 0.00 0.00 0.125956E+11 0.439017E+10 0.00 0.00
July 0.00 0.00 0.203881E+11 0.644638E+10 0.00 0.00
August 0.00 0.00 0.261312E+11 0.765298E+10 0.00 0.00
September 0.00 0.00 0.548788E+10 0.285766E+10 0.00 0.00
October 0.00 0.00 0.929364E+10 0.359924E+10 0.00 0.00
November 0.00 0.00 0.127624E+11 0.419714E+10 0.00 0.00
December 0.00 0.00 0.173330E+11 0.514944E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.149113E+12 0.516232E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.321811E+09 0.174551E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.261312E+11 0.765298E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.467664E+10 0.00 0.440019E+11 0.00 0.00 0.00 0.00 0.00
February 0.518639E+10 0.631469E+09 0.188558E+11 0.00 0.00 0.00 0.00 0.00
March 0.768867E+10 34245100.02 0.692379E+10 0.00 0.00 0.00 0.00 0.00
April 0.933259E+10 0.661475E+10 0.491197E+09 0.00 0.00 0.00 0.00 0.00
May 0.852548E+10 0.181362E+11 0.525464E+09 0.00 0.00 0.00 0.00 0.00
June 0.129105E+11 0.599180E+11 60391.77 0.00 0.00 0.00 0.00 0.00
July 0.158946E+11 0.102793E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.174352E+11 0.950781E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.955195E+10 0.388729E+11 41874926.76 0.00 0.00 0.00 0.00 0.00
October 0.853678E+10 0.105474E+11 0.365514E+09 0.00 0.00 0.00 0.00 0.00
November 0.722493E+10 0.560038E+09 0.408227E+10 0.00 0.00 0.00 0.00 0.00
December 0.623312E+10 0.00 0.181890E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.113197E+12 0.333186E+12 0.934769E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.467664E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.174352E+11 0.102793E+12 0.440019E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.445872E+11 22025.30 0.750779E+12 0.00 0.00 0.00 0.00 0.00
February 0.401120E+11 0.449454E+10 0.392684E+12 0.00 0.00 0.00 0.00 0.00
March 0.506749E+11 95868854.75 0.216701E+12 0.00 0.00 0.00 0.00 0.00
April 0.537990E+11 0.465868E+11 0.474773E+11 0.00 0.00 0.00 0.00 0.00
May 0.636069E+11 0.153363E+12 0.330866E+11 0.00 0.00 0.00 0.00 0.00
June 0.989918E+11 0.507393E+12 0.883779E+09 0.00 0.00 0.00 0.00 0.00
July 0.118348E+12 0.851486E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.115825E+12 0.737744E+12 0.292297E+09 0.00 0.00 0.00 0.00 0.00
September 0.743134E+11 0.339029E+12 0.822296E+10 0.00 0.00 0.00 0.00 0.00
October 0.557654E+11 0.830409E+11 0.383895E+11 0.00 0.00 0.00 0.00 0.00
November 0.450663E+11 0.402796E+10 0.188051E+12 0.00 0.00 0.00 0.00 0.00
December 0.437815E+11 85216.38 0.480785E+12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.804871E+12 0.272726E+13 0.215735E+13 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.401120E+11 22025.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.118348E+12 0.851486E+12 0.750779E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.573410E+10 59233.01 0.120967E+12 0.00 0.00 0.00 0.00 0.00
February 0.450550E+10 0.319283E+09 0.637594E+11 0.00 0.00 0.00 0.00 0.00
March 0.481016E+10 2115474.09 0.431134E+11 0.00 0.00 0.00 0.00 0.00
April 0.453039E+10 0.433904E+10 0.143464E+11 0.00 0.00 0.00 0.00 0.00
May 0.568372E+10 0.159500E+11 0.102580E+11 0.00 0.00 0.00 0.00 0.00
June 0.932005E+10 0.557763E+11 0.710561E+09 0.00 0.00 0.00 0.00 0.00
July 0.116491E+11 0.941281E+11 22421191.93 0.00 0.00 0.00 0.00 0.00
August 0.108198E+11 0.794769E+11 0.276369E+09 0.00 0.00 0.00 0.00 0.00
September 0.637016E+10 0.347387E+11 0.379148E+10 0.00 0.00 0.00 0.00 0.00
October 0.444869E+10 0.713518E+10 0.125250E+11 0.00 0.00 0.00 0.00 0.00
November 0.444823E+10 0.301718E+09 0.396973E+11 0.00 0.00 0.00 0.00 0.00
December 0.527489E+10 1767.86 0.848166E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.775948E+11 0.292167E+12 0.394284E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.444823E+10 1767.86 22421191.93 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.116491E+11 0.941281E+11 0.120967E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.162493E+11 483334.78 0.388718E+09 0.00 0.00 0.00 0.00 0.00
February 0.144709E+11 0.261761E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.174156E+11 10369.74 0.00 0.00 0.00 0.00 0.00 0.00
April 0.161896E+11 0.231208E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.172389E+11 0.883342E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.172626E+11 0.311339E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.172372E+11 0.530670E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.188642E+11 0.493011E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.176503E+11 0.203694E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.173438E+11 0.573405E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.165060E+11 68497280.37 0.00 0.00 0.00 0.00 0.00 0.00
December 0.160803E+11 60297.63 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.202509E+12 0.171082E+12 0.388718E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.144709E+11 10369.74 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.188642E+11 0.530670E+11 0.388718E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.108099E+12 0.361894E+12 0.00 0.00 0.00 0.408587E+11 0.00 0.00
February 0.976375E+11 0.575724E+12 0.00 0.00 0.00 0.611255E+11 0.00 0.00
March 0.108099E+12 0.910631E+12 0.00 0.00 0.00 0.921321E+11 0.00 0.00
April 0.104612E+12 0.114518E+13 0.00 0.00 0.00 0.110798E+12 0.00 0.00
May 0.108099E+12 0.375766E+12 0.00 0.00 0.00 0.368446E+11 0.00 0.00
June 0.104612E+12 0.620352E+12 0.00 0.00 0.00 0.491114E+11 0.00 0.00
July 0.108099E+12 0.894884E+12 0.00 0.00 0.00 0.545182E+11 0.00 0.00
August 0.108099E+12 0.116120E+13 0.00 0.00 0.00 0.856461E+11 0.00 0.00
September 0.104612E+12 0.366935E+12 0.00 0.00 0.00 0.313866E+11 0.00 0.00
October 0.108099E+12 0.649195E+12 0.00 0.00 0.00 0.640698E+11 0.00 0.00
November 0.104612E+12 0.889805E+12 0.00 0.00 0.00 0.913490E+11 0.00 0.00
December 0.108099E+12 0.118267E+13 0.00 0.00 0.00 0.119210E+12 0.00 0.00
                 
Annual Sum or Average 0.127277E+13 0.913423E+13 0.00 0.00 0.00 0.837050E+12 0.00 0.00
Minimum of Months 0.976375E+11 0.361894E+12 0.00 0.00 0.00 0.313866E+11 0.00 0.00
Maximum of Months 0.108099E+12 0.118267E+13 0.00 0.00 0.00 0.119210E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.171008E+10 0.292943E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.154459E+10 0.821852E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.171008E+10 0.149235E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.165491E+10 0.200314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.171008E+10 0.562191E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.165491E+10 0.109113E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.171008E+10 0.165864E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.171008E+10 0.215881E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.165491E+10 0.571231E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.171008E+10 0.105331E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.165491E+10 0.146199E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.171008E+10 0.194867E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.201348E+11 0.151163E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.154459E+10 0.292943E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171008E+10 0.215881E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.163745E+11 0.857650E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.147899E+11 0.591237E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.163745E+11 0.124326E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.158463E+11 0.179642E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.163745E+11 0.453654E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.158463E+11 0.100389E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.163745E+11 0.156653E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.163745E+11 0.202839E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.158463E+11 0.480861E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.163745E+11 0.877275E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.158463E+11 0.120793E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.163745E+11 0.158891E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.192797E+12 0.129241E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.147899E+11 0.857650E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.163745E+11 0.202839E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.166690E+10 0.243203E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.150558E+10 0.427161E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.166690E+10 0.107834E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.161313E+10 0.167733E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.166690E+10 0.383926E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.161313E+10 0.981859E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.166690E+10 0.156086E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.166690E+10 0.201452E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.161313E+10 0.424334E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.166690E+10 0.736129E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.161313E+10 0.101784E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.166690E+10 0.138504E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.196264E+11 0.117117E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.150558E+10 0.243203E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.166690E+10 0.201452E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.467664E+10 0.440019E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.518639E+10 0.188558E+11 0.631469E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.768867E+10 0.692379E+10 34245100.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.933259E+10 0.491197E+09 0.661475E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.852548E+10 0.525464E+09 0.181362E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.129105E+11 60391.77 0.599180E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.158946E+11 0.00 0.102793E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.174352E+11 0.00 0.950781E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.955195E+10 41874926.76 0.388729E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.853678E+10 0.365514E+09 0.105474E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.722493E+10 0.408227E+10 0.560038E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.623312E+10 0.181890E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.113197E+12 0.934769E+11 0.333186E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.467664E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.174352E+11 0.440019E+11 0.102793E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.445872E+11 0.750779E+12 22025.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.401120E+11 0.392684E+12 0.449454E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.506749E+11 0.216701E+12 95868854.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.537990E+11 0.474773E+11 0.465868E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.636069E+11 0.330866E+11 0.153363E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.989918E+11 0.883779E+09 0.507393E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.118348E+12 0.00 0.851486E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.115825E+12 0.292297E+09 0.737744E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.743134E+11 0.822296E+10 0.339029E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.557654E+11 0.383895E+11 0.830409E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.450663E+11 0.188051E+12 0.402796E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.437815E+11 0.480785E+12 85216.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.804871E+12 0.215735E+13 0.272726E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.401120E+11 0.00 22025.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.118348E+12 0.750779E+12 0.851486E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.573410E+10 0.120967E+12 59233.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.450550E+10 0.637594E+11 0.319283E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.481016E+10 0.431134E+11 2115474.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453039E+10 0.143464E+11 0.433904E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.568372E+10 0.102580E+11 0.159500E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.932005E+10 0.710561E+09 0.557763E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116491E+11 22421191.93 0.941281E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.108198E+11 0.276369E+09 0.794769E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.637016E+10 0.379148E+10 0.347387E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.444869E+10 0.125250E+11 0.713518E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.444823E+10 0.396973E+11 0.301718E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.527489E+10 0.848166E+11 1767.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.775948E+11 0.394284E+12 0.292167E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.444823E+10 22421191.93 1767.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.116491E+11 0.120967E+12 0.941281E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.162493E+11 0.388718E+09 483334.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.144709E+11 0.00 0.261761E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.174156E+11 0.00 10369.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.161896E+11 0.00 0.231208E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.172389E+11 0.00 0.883342E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.172626E+11 0.00 0.311339E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.172372E+11 0.00 0.530670E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.188642E+11 0.00 0.493011E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.176503E+11 0.00 0.203694E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.173438E+11 0.00 0.573405E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.165060E+11 0.00 68497280.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.160803E+11 0.00 60297.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.202509E+12 0.388718E+09 0.171082E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.144709E+11 0.00 10369.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.188642E+11 0.388718E+09 0.530670E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.108099E+12 0.00 0.453786E+12 0.00 0.918927E+11 0.00 0.00 0.00 0.410426E+11 0.00 0.00 0.00
February 0.976375E+11 0.00 0.714253E+12 0.00 0.138529E+12 0.00 0.00 0.00 0.614006E+11 0.00 0.00 0.00
March 0.108099E+12 0.00 0.112057E+13 0.00 0.209937E+12 0.00 0.00 0.00 0.925469E+11 0.00 0.00 0.00
April 0.104612E+12 0.00 0.140686E+13 0.00 0.261672E+12 0.00 0.00 0.00 0.111297E+12 0.00 0.00 0.00
May 0.108099E+12 0.00 0.473988E+12 0.00 0.982215E+11 0.00 0.00 0.00 0.370105E+11 0.00 0.00 0.00
June 0.104612E+12 0.00 0.789921E+12 0.00 0.169569E+12 0.00 0.00 0.00 0.493325E+11 0.00 0.00 0.00
July 0.108099E+12 0.00 0.116273E+13 0.00 0.267843E+12 0.00 0.00 0.00 0.547636E+11 0.00 0.00 0.00
August 0.108099E+12 0.00 0.148831E+13 0.00 0.327110E+12 0.00 0.00 0.00 0.860316E+11 0.00 0.00 0.00
September 0.104612E+12 0.00 0.467612E+12 0.00 0.100677E+12 0.00 0.00 0.00 0.315279E+11 0.00 0.00 0.00
October 0.108099E+12 0.00 0.807962E+12 0.00 0.158766E+12 0.00 0.00 0.00 0.643582E+11 0.00 0.00 0.00
November 0.104612E+12 0.00 0.109525E+13 0.00 0.205448E+12 0.00 0.00 0.00 0.917602E+11 0.00 0.00 0.00
December 0.108099E+12 0.00 0.144567E+13 0.00 0.263000E+12 0.00 0.00 0.00 0.119747E+12 0.00 0.00 0.00
                         
Annual Sum or Average 0.127277E+13 0.00 0.114269E+14 0.00 0.229267E+13 0.00 0.00 0.00 0.840818E+12 0.00 0.00 0.00
Minimum of Months 0.976375E+11 0.00 0.453786E+12 0.00 0.918927E+11 0.00 0.00 0.00 0.315279E+11 0.00 0.00 0.00
Maximum of Months 0.108099E+12 0.00 0.148831E+13 0.00 0.327110E+12 0.00 0.00 0.00 0.119747E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.171008E+10 0.00 0.377167E+10 0.00 0.842232E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.154459E+10 0.00 0.103821E+11 0.00 0.216357E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.171008E+10 0.00 0.186220E+11 0.00 0.369842E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.165491E+10 0.00 0.248643E+11 0.00 0.483299E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.171008E+10 0.00 0.715745E+10 0.00 0.153555E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.165491E+10 0.00 0.139573E+11 0.00 0.304603E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.171008E+10 0.00 0.216282E+11 0.00 0.504171E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.171008E+10 0.00 0.279449E+11 0.00 0.635677E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.165491E+10 0.00 0.733016E+10 0.00 0.161785E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.171008E+10 0.00 0.132129E+11 0.00 0.267977E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.165491E+10 0.00 0.182110E+11 0.00 0.359111E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.171008E+10 0.00 0.242133E+11 0.00 0.472659E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.201348E+11 0.00 0.191295E+12 0.00 0.401326E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.154459E+10 0.00 0.377167E+10 0.00 0.842232E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171008E+10 0.00 0.279449E+11 0.00 0.635677E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.163745E+11 0.00 0.112556E+11 0.00 0.267915E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.147899E+11 0.00 0.750458E+11 0.00 0.159221E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.163745E+11 0.00 0.155586E+12 0.00 0.312603E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.158463E+11 0.00 0.223398E+12 0.00 0.437564E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.163745E+11 0.00 0.579438E+11 0.00 0.125784E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.158463E+11 0.00 0.128581E+12 0.00 0.281921E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.163745E+11 0.00 0.204389E+12 0.00 0.477361E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.163745E+11 0.00 0.262791E+12 0.00 0.599522E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.158463E+11 0.00 0.619105E+11 0.00 0.138244E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.163745E+11 0.00 0.110362E+12 0.00 0.226340E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.158463E+11 0.00 0.150941E+12 0.00 0.301485E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.163745E+11 0.00 0.198204E+12 0.00 0.393130E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.192797E+12 0.00 0.164041E+13 0.00 0.347997E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.147899E+11 0.00 0.112556E+11 0.00 0.267915E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.163745E+11 0.00 0.262791E+12 0.00 0.599522E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.166690E+10 0.00 0.321811E+09 0.00 78608724.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.150558E+10 0.00 0.544551E+10 0.00 0.117389E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.166690E+10 0.00 0.135316E+11 0.00 0.274816E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.161313E+10 0.00 0.209056E+11 0.00 0.413232E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.166690E+10 0.00 0.491702E+10 0.00 0.107777E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.161313E+10 0.00 0.125956E+11 0.00 0.277704E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.166690E+10 0.00 0.203881E+11 0.00 0.477948E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.166690E+10 0.00 0.261312E+11 0.00 0.598609E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.161313E+10 0.00 0.548788E+10 0.00 0.124454E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.166690E+10 0.00 0.929364E+10 0.00 0.193234E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.161313E+10 0.00 0.127624E+11 0.00 0.258401E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.166690E+10 0.00 0.173330E+11 0.00 0.348254E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.196264E+11 0.00 0.149113E+12 0.00 0.319968E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.150558E+10 0.00 0.321811E+09 0.00 78608724.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.166690E+10 0.00 0.261312E+11 0.00 0.598609E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.255807E+11 0.00 0.00 60904153.32 0.00 0.00 0.445738E+11 0.00 0.42
February 0.920522E+10 0.00 0.00 74905898.41 0.00 0.00 0.531874E+11 0.00 0.54
March 0.271066E+10 0.00 0.00 0.111422E+09 0.00 0.00 0.741796E+11 0.00 0.67
April 0.322909E+09 0.00 0.00 0.108324E+09 0.00 0.00 0.703401E+11 0.00 0.94
May 0.135583E+09 42041095.72 0.00 0.113916E+09 6524016.38 0.00 0.683122E+11 0.00 1.14
June 0.107123E+09 0.377210E+09 0.00 0.107366E+09 357699.19 0.00 0.508381E+11 0.00 1.34
July 0.134483E+09 0.132364E+10 0.00 0.104457E+09 30691129.14 0.00 0.317188E+11 0.00 1.13
August 89896047.93 0.931127E+09 0.00 0.123060E+09 49730553.65 0.00 0.444720E+11 0.00 1.36
September 0.249436E+09 0.358599E+09 0.00 0.120326E+09 37632052.85 0.00 0.614325E+11 0.00 1.33
October 0.398575E+09 0.00 0.00 0.129042E+09 0.00 0.00 0.769013E+11 0.00 1.11
November 0.373693E+09 0.00 0.00 0.125741E+09 0.00 0.00 0.772043E+11 0.00 0.82
December 0.594994E+10 0.00 0.00 0.105172E+09 0.00 0.00 0.687076E+11 0.00 0.54
                   
Annual Sum or Average 0.452582E+11 0.303262E+10 0.00 0.128464E+10 0.124935E+09 0.00 0.721868E+12 0.00 0.95
Minimum of Months 89896047.93 0.00 0.00 60904153.32 0.00 0.00 0.317188E+11 0.00 0.42
Maximum of Months 0.255807E+11 0.132364E+10 0.00 0.129042E+09 49730553.65 0.00 0.772043E+11 0.00 1.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.194306E+11 0.00 0.00 36547066.71 0.00 0.00 0.324939E+11 0.00 0.30
February 0.781778E+10 0.00 0.00 57007154.39 0.00 0.00 0.389759E+11 0.00 0.40
March 0.311246E+10 0.00 0.00 91282716.69 0.00 0.00 0.568748E+11 0.00 0.52
April 0.405471E+10 0.00 0.00 95898615.13 0.00 0.00 0.567000E+11 0.00 0.78
May 0.247470E+10 17208373.75 0.00 88549606.12 7828632.48 0.00 0.487550E+11 0.00 0.79
June 0.477442E+10 0.215250E+09 0.00 91963222.15 12701503.76 0.00 0.388690E+11 0.00 1.05
July 0.721042E+10 0.576019E+09 0.00 81648166.22 65129007.37 0.00 0.221614E+11 0.00 0.95
August 0.933712E+10 0.422835E+09 0.00 99487470.73 47477099.10 0.00 0.337341E+11 0.00 1.18
September 0.306931E+10 0.379260E+09 0.00 86402271.75 35952527.31 0.00 0.413278E+11 0.00 0.89
October 0.280369E+10 0.00 0.00 93563831.27 0.00 0.00 0.531238E+11 0.00 0.78
November 0.213379E+10 0.00 0.00 86814238.41 0.00 0.00 0.534573E+11 0.00 0.58
December 0.363746E+10 0.00 0.00 77422307.24 0.00 0.00 0.524489E+11 0.00 0.40
                   
Annual Sum or Average 0.698564E+11 0.161057E+10 0.00 0.986587E+09 0.169089E+09 0.00 0.528922E+12 0.00 0.72
Minimum of Months 0.213379E+10 0.00 0.00 36547066.71 0.00 0.00 0.221614E+11 0.00 0.30
Maximum of Months 0.194306E+11 0.576019E+09 0.00 99487470.73 65129007.37 0.00 0.568748E+11 0.00 1.18



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.364605E+12 0.00 0.00 51607363.83 0.00 0.595075E+10 0.860742E+11 0.00 0.27
February 0.241452E+12 0.00 0.00 0.132644E+09 0.00 0.103681E+10 0.122097E+12 0.00 0.31
March 0.171607E+12 0.00 0.00 0.318166E+09 0.00 0.146827E+10 0.240612E+12 0.00 0.36
April 0.708865E+11 0.00 0.00 0.461839E+09 0.00 0.00 0.310493E+12 0.00 0.51
May 0.475470E+11 0.204988E+09 0.00 0.561112E+09 89262658.02 0.00 0.334046E+12 0.00 0.61
June 0.262539E+11 0.229578E+10 0.00 0.714361E+09 0.141253E+09 0.00 0.302424E+12 0.00 0.82
July 0.268519E+11 0.630499E+10 0.00 0.655019E+09 0.361157E+09 0.00 0.167896E+12 0.00 0.69
August 0.248757E+11 0.445655E+10 0.00 0.750860E+09 0.478210E+09 0.00 0.249923E+12 0.00 0.80
September 0.268756E+11 0.367285E+10 0.00 0.616482E+09 0.378650E+09 0.00 0.307702E+12 0.00 0.70
October 0.558117E+11 0.00 0.00 0.497032E+09 0.00 0.00 0.319312E+12 0.00 0.55
November 0.151267E+12 0.00 0.00 0.290669E+09 0.00 38256804.68 0.212771E+12 0.00 0.38
December 0.278660E+12 0.00 0.00 0.133193E+09 0.00 0.185611E+10 0.125004E+12 0.00 0.28
                   
Annual Sum or Average 0.148669E+13 0.169351E+11 0.00 0.518299E+10 0.144853E+10 0.103502E+11 0.277835E+13 0.00 0.52
Minimum of Months 0.248757E+11 0.00 0.00 51607363.83 0.00 0.00 0.860742E+11 0.00 0.27
Maximum of Months 0.364605E+12 0.630499E+10 0.00 0.750860E+09 0.478210E+09 0.595075E+10 0.334046E+12 0.00 0.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.291021E+11 0.00 0.00 28784.68 0.00 0.950703E+10 91755677.12 0.00 0.25
February 0.266413E+11 0.00 0.00 1222401.60 0.00 0.310742E+10 0.154928E+10 0.00 0.28
March 0.241784E+11 0.00 0.00 6930824.09 0.00 0.210434E+10 0.734762E+10 0.00 0.30
April 0.143295E+11 0.00 0.00 20770154.35 0.00 54617758.37 0.165004E+11 0.00 0.43
May 0.101680E+11 10396694.80 0.00 35946240.26 5963137.65 0.267759E+09 0.230464E+11 0.00 0.57
June 0.427299E+10 0.134029E+09 0.00 63416072.49 15136605.60 0.00 0.259393E+11 0.00 0.82
July 0.298755E+10 0.413024E+09 0.00 63933813.86 28212412.56 0.00 0.150184E+11 0.00 0.71
August 0.304325E+10 0.281089E+09 0.00 69547997.66 38638778.59 0.00 0.210024E+11 0.00 0.78
September 0.712368E+10 0.325542E+09 0.00 40709133.81 29653261.88 0.00 0.198903E+11 0.00 0.63
October 0.145597E+11 0.00 0.00 19058580.38 680691.99 0.179488E+09 0.133241E+11 0.00 0.44
November 0.211928E+11 0.00 0.00 5075546.90 0.00 0.163206E+10 0.512314E+10 0.00 0.31
December 0.272854E+11 0.00 0.00 1032481.53 0.00 0.507671E+10 0.131866E+10 0.00 0.25
                   
Annual Sum or Average 0.184885E+12 0.116408E+10 0.00 0.327672E+09 0.118285E+09 0.219294E+11 0.150152E+12 0.00 0.48
Minimum of Months 0.298755E+10 0.00 0.00 28784.68 0.00 0.00 91755677.12 0.00 0.25
Maximum of Months 0.291021E+11 0.413024E+09 0.00 69547997.66 38638778.59 0.950703E+10 0.259393E+11 0.00 0.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.312830E+10 0.00 0.00 0.00 0.00 0.382816E+10 0.00 0.00 0.31
February 0.387837E+10 0.00 0.00 245600.01 0.00 0.132494E+10 0.227942E+09 0.00 0.36
March 0.429784E+10 0.00 0.00 1274028.46 0.00 0.251920E+09 0.141439E+10 0.00 0.40
April 0.288072E+10 0.00 0.00 4218808.98 0.00 0.00 0.326047E+10 0.00 0.65
May 0.206493E+10 4636406.26 0.00 5908695.90 1247090.22 0.00 0.364618E+10 0.00 0.76
June 0.114044E+10 38514099.37 0.00 10975693.68 2023331.82 0.00 0.460524E+10 0.00 1.19
July 0.131894E+10 0.119890E+09 0.00 11013694.01 10374959.94 0.00 0.279409E+10 0.00 1.14
August 0.182350E+10 85347292.17 0.00 11089388.07 7563035.60 0.00 0.362068E+10 0.00 1.28
September 0.188722E+10 64318401.77 0.00 5593661.02 5727187.40 0.00 0.292922E+10 0.00 0.83
October 0.308544E+10 0.00 0.00 3216929.08 0.00 0.00 0.237133E+10 0.00 0.62
November 0.409027E+10 0.00 0.00 944199.16 0.00 0.106757E+09 0.102914E+10 0.00 0.42
December 0.460165E+10 0.00 0.00 86300.06 0.00 0.968686E+09 0.183399E+09 0.00 0.31
                   
Annual Sum or Average 0.341976E+11 0.312706E+09 0.00 54566998.43 26935604.98 0.648046E+10 0.260821E+11 0.00 0.69
Minimum of Months 0.114044E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.460165E+10 0.119890E+09 0.00 11089388.07 10374959.94 0.382816E+10 0.460524E+10 0.00 1.28



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.417003E+10 0.00 0.00 6218.41 0.00 0.436956E+10 23019414.14 0.00 0.60
February 0.450733E+10 0.00 0.00 745774.54 0.00 0.162026E+10 0.653515E+09 0.00 0.69
March 0.530264E+10 0.00 0.00 2128466.15 0.00 0.475653E+09 0.181078E+10 0.00 0.79
April 0.420830E+10 0.00 0.00 4623051.54 0.00 8251446.30 0.340305E+10 0.00 1.20
May 0.287537E+10 3207808.54 0.00 6702454.15 1545333.38 1620523.63 0.428156E+10 0.00 1.39
June 0.190472E+10 32248609.71 0.00 11375537.36 2507214.10 0.00 0.466317E+10 0.00 2.04
July 0.186065E+10 90952262.85 0.00 12100078.29 12856144.35 0.00 0.320525E+10 0.00 2.06
August 0.292990E+10 69704458.75 0.00 9816527.89 9130593.08 0.00 0.356703E+10 0.00 2.21
September 0.281155E+10 52793787.29 0.00 5626285.41 7021611.47 0.00 0.309173E+10 0.00 1.50
October 0.399891E+10 0.00 0.00 3174993.39 0.00 2639028.27 0.258990E+10 0.00 1.13
November 0.557521E+10 0.00 0.00 552098.38 0.00 0.274360E+09 0.583436E+09 0.00 0.80
December 0.527781E+10 0.00 0.00 8314.68 0.00 0.181320E+10 38480124.25 0.00 0.60
                   
Annual Sum or Average 0.454224E+11 0.248907E+09 0.00 56859800.18 33060896.39 0.856555E+10 0.279109E+11 0.00 1.25
Minimum of Months 0.186065E+10 0.00 0.00 6218.41 0.00 0.00 23019414.14 0.00 0.60
Maximum of Months 0.557521E+10 90952262.85 0.00 12100078.29 12856144.35 0.436956E+10 0.466317E+10 0.00 2.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.486264E+10 0.00 0.00 2137888.49 0.00 0.454325E+10 0.197827E+10 0.00 0.52
February 0.456452E+10 0.00 0.00 6717689.49 0.00 0.150808E+10 0.422847E+10 0.00 0.75
March 0.551994E+10 0.00 0.00 8162527.28 0.00 0.450152E+09 0.619297E+10 0.00 0.87
April 0.479370E+10 0.00 0.00 8477643.77 0.00 17125860.89 0.598573E+10 0.00 1.19
May 0.394204E+10 6467470.60 0.00 8489629.07 1955773.91 68890740.50 0.513367E+10 0.00 1.22
June 0.281051E+10 55364636.90 0.00 11800835.33 3173130.13 0.00 0.475228E+10 0.00 1.57
July 0.253727E+10 0.171406E+09 0.00 12868923.59 16270736.10 0.00 0.300668E+10 0.00 1.54
August 0.341235E+10 0.156666E+09 0.00 16062462.18 11860880.14 0.00 0.467730E+10 0.00 1.97
September 0.296739E+10 0.163685E+09 0.00 12711447.43 3950001.96 0.00 0.585558E+10 0.00 1.63
October 0.367867E+10 0.00 0.00 13914373.63 0.00 24362432.81 0.768161E+10 0.00 1.38
November 0.463103E+10 0.00 0.00 7361263.53 0.00 0.402908E+09 0.554240E+10 0.00 0.88
December 0.545518E+10 0.00 0.00 3761698.99 0.00 0.173329E+10 0.295629E+10 0.00 0.57
                   
Annual Sum or Average 0.491752E+11 0.553588E+09 0.00 0.112466E+09 37210522.24 0.874805E+10 0.579912E+11 0.00 1.18
Minimum of Months 0.253727E+10 0.00 0.00 2137888.49 0.00 0.00 0.197827E+10 0.00 0.52
Maximum of Months 0.551994E+10 0.171406E+09 0.00 16062462.18 16270736.10 0.454325E+10 0.768161E+10 0.00 1.97



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.668222E+10 0.00 0.00 113059.69 0.00 0.379628E+10 0.194955E+09 0.00 0.75
February 0.673375E+10 0.00 0.00 1591035.31 0.00 0.283330E+09 0.158401E+10 0.00 0.89
March 0.474091E+10 0.00 0.00 5029124.03 0.00 47180032.04 0.513823E+10 0.00 1.07
April 0.200645E+10 0.00 0.00 12207522.14 0.00 0.00 0.832426E+10 0.00 1.76
May 0.283392E+10 5214380.93 0.00 9681170.92 1927230.98 519899.16 0.581518E+10 0.00 1.75
June 0.158638E+10 52788546.85 0.00 14876621.19 1031923.05 0.00 0.589240E+10 0.00 2.40
July 0.170196E+10 0.185750E+09 0.00 17056349.92 10020957.35 0.00 0.383000E+10 0.00 2.37
August 0.211345E+10 0.138018E+09 0.00 20435395.29 2747770.54 0.00 0.590296E+10 0.00 2.92
September 0.293421E+10 0.106247E+09 0.00 6997629.71 1431833.38 0.00 0.401536E+10 0.00 1.83
October 0.354438E+10 0.00 0.00 6110186.67 0.00 0.00 0.494758E+10 0.00 1.50
November 0.457008E+10 0.00 0.00 3579822.13 0.00 1900091.15 0.387295E+10 0.00 1.07
December 0.670109E+10 0.00 0.00 1837747.47 0.00 18718832.62 0.231819E+10 0.00 0.77
                   
Annual Sum or Average 0.461488E+11 0.488018E+09 0.00 99515664.46 17159715.31 0.414793E+10 0.518361E+11 0.00 1.59
Minimum of Months 0.158638E+10 0.00 0.00 113059.69 0.00 0.00 0.194955E+09 0.00 0.75
Maximum of Months 0.673375E+10 0.185750E+09 0.00 20435395.29 10020957.35 0.379628E+10 0.832426E+10 0.00 2.92



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.669828E+10 0.00 0.00 0.00 0.00 0.715821E+11 0.00 0.00 0.35
February 0.155743E+11 0.00 0.00 0.00 0.00 0.404298E+11 0.00 0.00 0.36
March 0.357662E+11 0.00 0.00 0.00 0.00 0.200378E+11 0.00 0.00 0.37
April 0.348378E+11 0.00 0.00 6058347.12 0.00 0.401295E+10 0.513094E+10 0.00 0.46
May 0.271667E+11 50125622.77 0.00 27390747.28 15865301.27 0.218023E+10 0.154655E+11 0.00 0.60
June 0.117510E+11 0.428359E+09 0.00 77772621.50 22011652.29 0.00 0.296109E+11 0.00 0.91
July 0.672541E+10 0.144372E+10 0.00 81936275.65 57336382.63 0.00 0.191159E+11 0.00 0.82
August 0.119867E+11 0.100756E+10 0.00 68084110.75 74520250.42 0.00 0.203465E+11 0.00 0.83
September 0.242844E+11 0.608719E+09 0.00 29059113.19 59005535.64 0.547113E+09 0.124984E+11 0.00 0.65
October 0.359407E+11 0.00 0.00 4318065.10 0.00 0.329460E+10 0.381713E+10 0.00 0.49
November 0.284020E+11 0.00 0.00 0.00 0.00 0.202560E+11 0.00 0.00 0.39
December 0.128411E+11 0.00 0.00 0.00 0.00 0.496138E+11 0.00 0.00 0.34
                   
Annual Sum or Average 0.251975E+12 0.353849E+10 0.00 0.294619E+09 0.228739E+09 0.211954E+12 0.105985E+12 0.00 0.55
Minimum of Months 0.669828E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.34
Maximum of Months 0.359407E+11 0.144372E+10 0.00 81936275.65 74520250.42 0.715821E+11 0.296109E+11 0.00 0.91



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.158343E+11 0.00 0.00 0.00 0.00 0.825772E+11 0.00 0.00 0.71
February 0.276569E+11 0.00 0.00 954763.85 0.00 0.470283E+11 0.976058E+09 0.00 0.77
March 0.489606E+11 0.00 0.00 7187092.49 0.00 0.224258E+11 0.596486E+10 0.00 0.81
April 0.396768E+11 0.00 0.00 28574476.04 0.00 0.413511E+10 0.221108E+11 0.00 1.06
May 0.316626E+11 43167519.19 0.00 48111549.96 19261667.88 0.300591E+10 0.311237E+11 0.00 1.31
June 0.173470E+11 0.415507E+09 0.00 0.104636E+09 30096141.98 0.00 0.405012E+11 0.00 1.89
July 0.106266E+11 0.126936E+10 0.00 0.124864E+09 79396090.01 0.00 0.297143E+11 0.00 1.83
August 0.178378E+11 0.103039E+10 0.00 92118744.70 0.102257E+09 0.00 0.317831E+11 0.00 1.84
September 0.318063E+11 0.600992E+09 0.00 41059516.51 89297201.34 0.542034E+09 0.208777E+11 0.00 1.38
October 0.487139E+11 0.00 0.00 10623839.88 0.00 0.293261E+10 0.841447E+10 0.00 1.05
November 0.420970E+11 0.00 0.00 306044.65 0.00 0.240927E+11 0.531918E+09 0.00 0.83
December 0.231654E+11 0.00 0.00 0.00 0.00 0.608965E+11 0.00 0.00 0.71
                   
Annual Sum or Average 0.355385E+12 0.335941E+10 0.00 0.458437E+09 0.320308E+09 0.247636E+12 0.191998E+12 0.00 1.19
Minimum of Months 0.106266E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.71
Maximum of Months 0.489606E+11 0.126936E+10 0.00 0.124864E+09 0.102257E+09 0.825772E+11 0.405012E+11 0.00 1.89



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.360632E+11 0.00 0.00 13610708.53 0.00 0.718813E+11 0.152285E+11 0.00 0.57
February 0.395991E+11 0.00 0.00 57833586.85 0.00 0.334648E+11 0.335616E+11 0.00 0.78
March 0.497103E+11 0.00 0.00 66381914.04 0.00 0.198294E+11 0.477056E+11 0.00 0.84
April 0.430330E+11 0.00 0.00 63219791.18 0.00 0.423884E+10 0.427322E+11 0.00 1.01
May 0.395495E+11 85283330.15 0.00 69025728.78 23311765.00 0.381672E+10 0.389143E+11 0.00 1.12
June 0.273294E+11 0.667767E+09 0.00 95391014.37 35411343.53 11091195.49 0.354848E+11 0.00 1.35
July 0.163479E+11 0.224713E+10 0.00 0.108096E+09 96090484.16 0.00 0.233117E+11 0.00 1.25
August 0.219963E+11 0.218718E+10 0.00 0.135343E+09 0.124889E+09 0.00 0.358523E+11 0.00 1.57
September 0.304537E+11 0.192851E+10 0.00 0.117379E+09 44144981.85 0.704563E+09 0.482675E+11 0.00 1.52
October 0.376644E+11 0.00 0.00 0.124835E+09 0.00 0.238707E+10 0.615212E+11 0.00 1.28
November 0.413038E+11 0.00 0.00 55579053.83 0.00 0.177669E+11 0.406947E+11 0.00 0.83
December 0.438514E+11 0.00 0.00 19957479.13 0.00 0.462122E+11 0.168343E+11 0.00 0.60
                   
Annual Sum or Average 0.426902E+12 0.711587E+10 0.00 0.926653E+09 0.323848E+09 0.200313E+12 0.440109E+12 0.00 1.06
Minimum of Months 0.163479E+11 0.00 0.00 13610708.53 0.00 0.00 0.152285E+11 0.00 0.57
Maximum of Months 0.497103E+11 0.224713E+10 0.00 0.135343E+09 0.124889E+09 0.718813E+11 0.615212E+11 0.00 1.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.219773E+11 0.00 0.00 0.00 0.00 0.836079E+11 0.00 0.00 0.76
February 0.350441E+11 0.00 0.00 3003082.34 0.00 0.438375E+11 0.265884E+10 0.00 0.83
March 0.550138E+11 0.00 0.00 8993738.49 0.00 0.210409E+11 0.777244E+10 0.00 0.88
April 0.503824E+11 0.00 0.00 25186933.09 0.00 0.304422E+10 0.162696E+11 0.00 1.17
May 0.402035E+11 48352200.10 0.00 54224615.79 23620475.45 0.273027E+10 0.265342E+11 0.00 1.43
June 0.245262E+11 0.543188E+09 0.00 77460401.09 16031045.81 0.00 0.290722E+11 0.00 1.77
July 0.141798E+11 0.205626E+10 0.00 82852341.01 33012684.35 0.00 0.187658E+11 0.00 1.57
August 0.211050E+11 0.131346E+10 0.00 73996372.31 58709799.71 0.00 0.224170E+11 0.00 1.68
September 0.386472E+11 0.995166E+09 0.00 33947125.42 29228661.36 0.584287E+09 0.158879E+11 0.00 1.46
October 0.524040E+11 0.00 0.00 14159115.30 0.00 0.286202E+10 0.997401E+10 0.00 1.15
November 0.470629E+11 0.00 0.00 2564054.82 0.00 0.208922E+11 0.378560E+10 0.00 0.90
December 0.328760E+11 0.00 0.00 41797.85 0.00 0.572443E+11 0.202106E+09 0.00 0.77
                   
Annual Sum or Average 0.433422E+12 0.495643E+10 0.00 0.376430E+09 0.160603E+09 0.235844E+12 0.153340E+12 0.00 1.20
Minimum of Months 0.141798E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.76
Maximum of Months 0.550138E+11 0.205626E+10 0.00 82852341.01 58709799.71 0.836079E+11 0.290722E+11 0.00 1.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.182796E+09 0.00 0.00 0.00 0.00 0.855653E+10 0.00 0.00 0.43
February 0.924702E+09 0.00 0.00 0.00 0.00 0.536849E+10 0.00 0.00 0.44
March 0.260330E+10 0.00 0.00 0.00 0.00 0.381671E+10 0.00 0.00 0.46
April 0.361652E+10 0.00 0.00 203153.46 0.00 0.145078E+10 0.188361E+09 0.00 0.55
May 0.341286E+10 2783034.46 0.00 1765509.35 1142099.00 0.884125E+09 0.988490E+09 0.00 0.70
June 0.181840E+10 23470991.91 0.00 6890902.57 2899061.38 48412349.02 0.248242E+10 0.00 0.99
July 0.107932E+10 88224040.01 0.00 7863284.94 5551005.43 0.00 0.161898E+10 0.00 0.89
August 0.175103E+10 60792310.19 0.00 6410976.80 7400350.76 24838927.50 0.162557E+10 0.00 0.89
September 0.287092E+10 50875932.00 0.00 1972111.13 7774584.85 0.439386E+09 0.801053E+09 0.00 0.74
October 0.338770E+10 0.00 0.00 65474.86 130370.57 0.148525E+10 50213572.43 0.00 0.59
November 0.173475E+10 0.00 0.00 0.00 0.00 0.363841E+10 0.00 0.00 0.47
December 0.533284E+09 0.00 0.00 0.00 0.00 0.635810E+10 0.00 0.00 0.41
                   
Annual Sum or Average 0.239156E+11 0.226146E+09 0.00 25171413.12 24897471.99 0.320710E+11 0.775509E+10 0.00 0.63
Minimum of Months 0.182796E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.41
Maximum of Months 0.361652E+10 88224040.01 0.00 7863284.94 7774584.85 0.855653E+10 0.248242E+10 0.00 0.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.459244E+09 0.00 0.00 0.00 0.00 0.777040E+10 0.00 0.00 0.65
February 0.191894E+10 0.00 0.00 0.00 0.00 0.466876E+10 0.00 0.00 0.73
March 0.365643E+10 0.00 0.00 277927.33 0.00 0.301137E+10 0.276261E+09 0.00 0.77
April 0.323373E+10 0.00 0.00 2130905.37 0.00 0.110921E+10 0.175973E+10 0.00 1.01
May 0.282996E+10 2125495.11 0.00 4175563.28 1255079.63 0.703508E+09 0.270114E+10 0.00 1.28
June 0.160010E+10 22760373.11 0.00 10423133.16 3185847.20 37167740.32 0.383379E+10 0.00 1.91
July 0.893551E+09 77222697.05 0.00 12931553.56 6100131.32 0.00 0.297053E+10 0.00 1.88
August 0.150029E+10 65083063.06 0.00 9943622.03 7910376.87 13660458.15 0.307031E+10 0.00 1.83
September 0.258915E+10 52960400.15 0.00 3596627.88 6346964.95 0.325042E+09 0.183815E+10 0.00 1.33
October 0.390391E+10 0.00 0.00 486430.66 143267.30 0.109797E+10 0.403140E+09 0.00 1.01
November 0.258224E+10 0.00 0.00 0.00 0.00 0.321863E+10 0.00 0.00 0.80
December 0.101128E+10 0.00 0.00 0.00 0.00 0.609773E+10 0.00 0.00 0.66
                   
Annual Sum or Average 0.261788E+11 0.220152E+09 0.00 43965763.26 24941667.28 0.280534E+11 0.168530E+11 0.00 1.16
Minimum of Months 0.459244E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.65
Maximum of Months 0.390391E+10 77222697.05 0.00 12931553.56 7910376.87 0.777040E+10 0.383379E+10 0.00 1.91



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.243566E+10 0.00 0.00 510749.99 0.00 0.783844E+10 0.627022E+09 0.00 0.55
February 0.303680E+10 0.00 0.00 3333344.38 0.00 0.423534E+10 0.221200E+10 0.00 0.72
March 0.382168E+10 0.00 0.00 4902524.13 0.00 0.323182E+10 0.371713E+10 0.00 0.80
April 0.377116E+10 0.00 0.00 4733105.43 0.00 0.149052E+10 0.355974E+10 0.00 0.99
May 0.366970E+10 4166375.48 0.00 5951483.05 1634426.32 0.110815E+10 0.354919E+10 0.00 1.15
June 0.286160E+10 35494444.54 0.00 9627543.80 4148766.64 82190275.84 0.340153E+10 0.00 1.43
July 0.174098E+10 0.130958E+09 0.00 11637277.22 7943890.50 0.00 0.232056E+10 0.00 1.33
August 0.221738E+10 0.132447E+09 0.00 14617636.08 7979473.04 34895410.28 0.353249E+10 0.00 1.62
September 0.280020E+10 0.158601E+09 0.00 10350438.60 3343258.21 0.413874E+09 0.441398E+10 0.00 1.51
October 0.362336E+10 200798.30 0.00 8986429.19 7364.03 0.915183E+09 0.453226E+10 0.00 1.21
November 0.336503E+10 0.00 0.00 3312821.13 0.00 0.276826E+10 0.245615E+10 0.00 0.77
December 0.288802E+10 0.00 0.00 1029615.89 0.00 0.566106E+10 0.894700E+09 0.00 0.57
                   
Annual Sum or Average 0.362316E+11 0.461868E+09 0.00 78992968.89 25057178.75 0.277797E+11 0.352167E+11 0.00 1.06
Minimum of Months 0.174098E+10 0.00 0.00 510749.99 0.00 0.00 0.627022E+09 0.00 0.55
Maximum of Months 0.382168E+10 0.158601E+09 0.00 14617636.08 7979473.04 0.783844E+10 0.453226E+10 0.00 1.62



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.852480E+09 0.00 0.00 0.00 0.00 0.846077E+10 0.00 0.00 0.73
February 0.223845E+10 0.00 0.00 173638.79 0.00 0.508893E+10 0.184445E+09 0.00 0.83
March 0.407331E+10 0.00 0.00 653385.48 0.00 0.331442E+10 0.618612E+09 0.00 0.89
April 0.449985E+10 0.00 0.00 2054503.84 0.00 0.104432E+10 0.144985E+10 0.00 1.19
May 0.382493E+10 2634391.09 0.00 4900999.32 1432542.71 0.741549E+09 0.253770E+10 0.00 1.49
June 0.261554E+10 30150507.94 0.00 8664209.68 1052714.46 33984668.75 0.274844E+10 0.00 1.89
July 0.159477E+10 0.120455E+09 0.00 9110321.78 2459475.92 0.00 0.172027E+10 0.00 1.66
August 0.224719E+10 76918834.34 0.00 7948448.61 4730646.38 30825472.54 0.198850E+10 0.00 1.74
September 0.359250E+10 83150791.53 0.00 3085685.00 3610663.52 0.351227E+09 0.138603E+10 0.00 1.50
October 0.438864E+10 0.00 0.00 1012905.70 163524.71 0.106168E+10 0.796774E+09 0.00 1.18
November 0.328544E+10 0.00 0.00 74189.78 0.00 0.315027E+10 0.174611E+09 0.00 0.91
December 0.171706E+10 0.00 0.00 0.00 0.00 0.636996E+10 0.00 0.00 0.75
                   
Annual Sum or Average 0.349302E+11 0.313309E+09 0.00 37678287.96 13449567.70 0.296479E+11 0.136052E+11 0.00 1.23
Minimum of Months 0.852480E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.73
Maximum of Months 0.449985E+10 0.120455E+09 0.00 9110321.78 4730646.38 0.846077E+10 0.274844E+10 0.00 1.89



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 15410289.54 0.00 0.00 2256734.46 0.00 0.00 0.834250E+09 0.00 0.28
February 0.00 0.00 0.00 7052333.67 0.00 0.00 0.645448E+09 0.00 0.28
March 0.00 0.00 0.00 13681121.56 0.00 0.00 0.660984E+09 0.00 0.31
April 0.00 0.00 0.00 17279878.96 0.00 0.00 0.462926E+09 0.00 0.29
May 0.00 143487.60 0.00 3936002.93 0.00 0.00 0.407839E+09 0.00 0.29
June 0.00 13410891.66 0.00 7425200.44 0.00 0.00 0.201173E+09 0.00 0.30
July 0.00 21308024.34 0.00 9006717.74 0.00 0.00 81849224.59 0.00 0.28
August 0.00 5701230.98 0.00 16477813.00 0.00 0.00 0.152119E+09 0.00 0.31
September 0.00 11412500.15 0.00 3473154.57 0.00 0.00 0.257517E+09 0.00 0.29
October 0.00 0.00 0.00 8241061.12 0.00 0.00 0.439875E+09 0.00 0.28
November 0.00 0.00 0.00 12010426.08 0.00 0.00 0.544004E+09 0.00 0.28
December 0.00 0.00 0.00 16542730.20 0.00 0.00 0.716620E+09 0.00 0.28
                   
Annual Sum or Average 15410289.54 51976134.73 0.00 0.117383E+09 0.00 0.00 0.540460E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 2256734.46 0.00 0.00 81849224.59 0.00 0.28
Maximum of Months 15410289.54 21308024.34 0.00 17279878.96 0.00 0.00 0.834250E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.276700E+10 0.00 0.00 8516546.13 0.00 0.00 0.567473E+10 0.00 0.28
February 0.00 0.00 0.00 54718792.81 0.00 0.00 0.647056E+10 0.00 0.28
March 0.00 0.00 0.00 0.118059E+09 0.00 0.00 0.662823E+10 0.00 0.31
April 0.00 0.00 0.00 0.157199E+09 0.00 0.00 0.464235E+10 0.00 0.29
May 3116017.78 1351117.57 0.00 31426571.58 0.00 0.00 0.408828E+10 0.00 0.29
June 0.00 0.132799E+09 0.00 68455882.12 0.00 0.00 0.201966E+10 0.00 0.30
July 0.00 0.212127E+09 0.00 85042773.36 0.00 0.00 0.823797E+09 0.00 0.28
August 0.00 59141413.42 0.00 0.154032E+09 0.00 0.00 0.152735E+10 0.00 0.31
September 0.00 0.111260E+09 0.00 28290952.03 0.00 0.00 0.259664E+10 0.00 0.29
October 0.00 0.00 0.00 70418724.84 0.00 0.00 0.441007E+10 0.00 0.28
November 0.00 0.00 0.00 0.102983E+09 0.00 0.00 0.545621E+10 0.00 0.28
December 0.00 0.00 0.00 0.142073E+09 0.00 0.00 0.718733E+10 0.00 0.28
                   
Annual Sum or Average 0.277012E+10 0.516678E+09 0.00 0.102122E+10 0.00 0.00 0.515252E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 8516546.13 0.00 0.00 0.823797E+09 0.00 0.28
Maximum of Months 0.276700E+10 0.212127E+09 0.00 0.157199E+09 0.00 0.00 0.718733E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.594096E+09 0.00 0.00 262203.49 0.00 0.00 0.231786E+09 0.00 0.28
February 0.00 0.00 0.00 4496603.71 0.00 0.00 0.647970E+09 0.00 0.28
March 0.00 0.00 0.00 10786132.05 0.00 0.00 0.663858E+09 0.00 0.31
April 0.00 0.00 0.00 14987829.63 0.00 0.00 0.465127E+09 0.00 0.29
May 28471239.60 137052.79 0.00 2674850.00 0.00 0.00 0.380488E+09 0.00 0.29
June 0.00 13316223.30 0.00 6695939.49 0.00 0.00 0.202332E+09 0.00 0.30
July 0.00 21216637.23 0.00 8470642.74 0.00 0.00 82528963.91 0.00 0.28
August 0.00 5944231.94 0.00 15262939.52 0.00 0.00 0.152904E+09 0.00 0.31
September 6915588.09 11101535.41 0.00 2412387.06 0.00 0.00 0.254420E+09 0.00 0.29
October 0.00 0.00 0.00 6208490.48 0.00 0.00 0.442107E+09 0.00 0.28
November 0.00 0.00 0.00 9236528.92 0.00 0.00 0.546739E+09 0.00 0.28
December 0.00 0.00 0.00 13071763.66 0.00 0.00 0.719964E+09 0.00 0.28
                   
Annual Sum or Average 0.629483E+09 51715680.67 0.00 94566310.75 0.00 0.00 0.479022E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 262203.49 0.00 0.00 82528963.91 0.00 0.28
Maximum of Months 0.594096E+09 21216637.23 0.00 15262939.52 0.00 0.00 0.719964E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.215937E+09 0.00 0.00 0.230711E+11 0.00 0.32
February 0.00 0.00 0.00 0.405446E+09 0.00 0.00 0.176946E+11 0.00 0.32
March 0.00 0.00 0.00 0.709385E+09 0.00 0.00 0.179629E+11 0.00 0.35
April 0.00 0.00 0.00 0.864518E+09 0.00 0.00 0.123135E+11 0.00 0.32
May 0.00 0.00 0.00 0.219845E+09 0.00 0.00 0.110015E+11 0.00 0.33
June 0.00 0.269527E+09 0.00 0.375971E+09 0.00 0.00 0.532229E+10 0.00 0.34
July 0.00 0.421728E+09 0.00 0.457379E+09 0.00 0.00 0.221282E+10 0.00 0.31
August 0.00 0.00 0.00 0.932258E+09 0.00 0.00 0.548417E+10 0.00 0.35
September 0.00 0.251472E+09 0.00 0.194660E+09 0.00 0.00 0.667136E+10 0.00 0.32
October 0.00 0.00 0.00 0.432038E+09 0.00 0.00 0.114227E+11 0.00 0.32
November 0.00 0.00 0.00 0.624857E+09 0.00 0.00 0.145889E+11 0.00 0.32
December 0.00 0.00 0.00 0.862760E+09 0.00 0.00 0.192799E+11 0.00 0.32
                   
Annual Sum or Average 0.00 0.942727E+09 0.00 0.629505E+10 0.00 0.00 0.147026E+12 0.00 0.33
Minimum of Months 0.00 0.00 0.00 0.194660E+09 0.00 0.00 0.221282E+10 0.00 0.31
Maximum of Months 0.00 0.421728E+09 0.00 0.932258E+09 0.00 0.00 0.230711E+11 0.00 0.35



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:03:16

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.279651E+12 0.462992E+11 0.00 0.171713E+13 0.717032E+12
February 0.371703E+12 0.360246E+11 0.00 0.159986E+13 0.983357E+12
March 0.634466E+12 0.336870E+11 0.00 0.191077E+13 0.146951E+13
April 0.679243E+12 0.239997E+11 0.00 0.202963E+13 0.189895E+13
May 0.893305E+12 0.237161E+11 0.00 0.198381E+13 0.876175E+12
June 0.976493E+12 0.122704E+11 0.00 0.169700E+13 0.187525E+13
July 0.967083E+12 0.800698E+10 0.00 0.136687E+13 0.292642E+13
August 0.805174E+12 0.868640E+10 0.00 0.153158E+13 0.318198E+13
September 0.607431E+12 0.157350E+11 0.00 0.175665E+13 0.116861E+13
October 0.400755E+12 0.230487E+11 0.00 0.212382E+13 0.116854E+13
November 0.221759E+12 0.324985E+11 0.00 0.188930E+13 0.144328E+13
December 0.183967E+12 0.413115E+11 0.00 0.170839E+13 0.192431E+13
           
Annual Sum or Average 0.702103E+13 0.305284E+12 0.00 0.213148E+14 0.196334E+14
Minimum of Months 0.183967E+12 0.800698E+10 0.00 0.136687E+13 0.717032E+12