Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 09:03:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 34687.60 | 748.86 | 748.86 |
Net Site Energy | 34687.60 | 748.86 | 748.86 |
Total Source Energy | 108672.02 | 2346.10 | 2346.10 |
Net Source Energy | 108672.02 | 2346.10 | 2346.10 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 4.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6198.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3703.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1941.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2684.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1414.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15621.22 |
Humidification | 1.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Heat Recovery | 119.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 564.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 34119.37 | 568.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17901.82 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 4.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 6198.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3703.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2684.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1414.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15621.22 |
Humidification | General | 1.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Heat Recovery | General | 119.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 564.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 4.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 6198.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3703.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1941.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2684.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1414.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 2170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15621.22 |
Humidification | Unassigned | 1.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Heat Recovery | Unassigned | 119.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 564.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 269.20 | 12.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Other | 372.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 736.60 | 12.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 269.20 | 12.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Other | 372.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 736.60 | 12.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 34119.373 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 34119.373 | 100.00 |
Total On-Site and Utility Electric Sources | 34119.373 | 100.00 |
Total Electricity End Uses | 34119.373 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 4944.52 | 99.41 |
Air to Air Heat Recovery for Heating | 29.42 | 0.59 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4973.94 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 17901.82 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 17901.82 | 100.00 |
Total Water End Uses | 17901.82 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 918.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.3279 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.3279 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.3279 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.3279 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 9.3279 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.3279 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 9.3279 | 18.58 | 484.4232 | |
Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.8860 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-AUG-15:00 | 04-FEB-06:10 | - | - | - | - | - | - | - | - | - | - | 17-APR-15:09 |
Heating | 0.00 | 212165.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 476372.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84885.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 207336.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 75424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 97050.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 26422.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2057502.42 | 238588.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 212165.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 476372.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5451.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 207336.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 75424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 97050.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 26422.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 4.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19629.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11728.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2126.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6150.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8503.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4479.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6875.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 379.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 611.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 108056.06 | 615.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 423.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 253.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 183.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 96.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 148.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2332.80 | 13.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 423.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 253.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 183.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 96.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 148.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2332.80 | 13.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.83 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.472866 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.49 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.456270 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.39 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.98 | 0.318131 | 0.322000 | 1.93 | 0.848350 | 0.500000 | 0.001198 | 0.000169 | 1.93 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 56.22 | 0.338312 | 0.336000 | 18.89 | 0.902164 | 0.500000 | 0.001126 | 0.003048 | 18.89 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.60 | 0.339759 | 0.344000 | 1.93 | 0.906024 | 0.500000 | 0.001121 | 0.000501 | 1.93 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.990096 | 0.241209 | 0.300000 | 0.297029 | 0.643225 | 0.500000 | 0.001580 | 0.000035 | 0.297029 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.931763 | 0.165176 | 0.300000 | 0.279529 | 0.440470 | 0.500000 | 0.002307 | 0.000033 | 0.279529 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.980504 | 0.243574 | 0.300000 | 0.294151 | 0.649532 | 0.500000 | 0.001564 | 0.000051 | 0.294151 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.21 | 0.126761 | 0.300000 | 0.364242 | 0.338028 | 0.500000 | 0.003006 | 0.000032 | 0.364242 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.35 | 0.255362 | 0.300000 | 2.81 | 0.680965 | 0.500000 | 0.001492 | 0.001059 | 3.61 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 9.53 | 0.161553 | 0.300000 | 2.86 | 0.430808 | 0.500000 | 0.002358 | 0.000746 | 2.86 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 9.15 | 0.261062 | 0.300000 | 2.74 | 0.696165 | 0.500000 | 0.001459 | 0.001057 | 3.60 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.27 | 0.149901 | 0.300000 | 3.08 | 0.399735 | 0.500000 | 0.002542 | 0.000698 | 3.08 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.06 | 0.226076 | 0.300000 | 0.316912 | 0.602870 | 0.500000 | 0.001685 | 0.000150 | 0.510142 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.980265 | 0.157004 | 0.300000 | 0.294080 | 0.418676 | 0.500000 | 0.002427 | 0.000099 | 0.336670 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.06 | 0.225416 | 0.300000 | 0.317847 | 0.601108 | 0.500000 | 0.001690 | 0.000149 | 0.509285 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.13 | 0.136575 | 0.300000 | 0.338068 | 0.364199 | 0.500000 | 0.002790 | 0.000093 | 0.338068 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19361.22 | 0.000169 | 390.31 |
CORE_MID VAV BOX REHEAT COIL | 348444.33 | 0.003048 | 7656.70 |
CORE_TOP VAV BOX REHEAT COIL | 57213.05 | 0.000501 | 1435.42 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 3993.48 | 0.000035 | 83.27 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3773.84 | 0.000033 | 78.73 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5883.36 | 0.000051 | 131.51 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3663.13 | 0.000032 | 73.85 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 121085.05 | 0.001059 | 3195.90 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 85253.86 | 0.000746 | 2142.26 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 120837.36 | 0.001057 | 3189.37 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 79826.81 | 0.000698 | 1910.60 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17096.30 | 0.000150 | 451.04 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11282.06 | 0.000099 | 297.64 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17067.68 | 0.000149 | 450.28 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10644.38 | 0.000093 | 273.31 |
VAV_BOT WITH REHEAT HEATING COIL | 15205.57 | 0.000133 | 269.99 |
VAV_MID WITH REHEAT HEATING COIL | 113326.30 | 0.000991 | 2025.52 |
VAV_TOP WITH REHEAT HEATING COIL | 9466.04 | 0.000083 | 170.19 |
CAV_BAS HEATING COIL | 269000.46 | 0.002353 | 6149.61 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.05 | 3.16 | 10.10 | 3.16 | 9.55 | 9.55 | 0.300000 | 0.330949 | 9.55 |
VAV_MID WITH REHEAT | 47.26 | 30.38 | 94.52 | 30.38 | 88.92 | 88.92 | 0.300000 | 0.341646 | 88.92 |
VAV_TOP WITH REHEAT | 4.91 | 3.19 | 9.82 | 3.27 | 9.51 | 9.51 | 0.300000 | 0.343780 | 9.51 |
CAV_BAS | 5.83 | 5.83 | 5.83 | 5.83 | 5.83 | 5.83 | 1.00 | 1.00 | 5.83 |
AIRLOOP DATACENTER BASEMENT | 21.39 | 21.39 | 21.39 | 21.39 | 21.39 | 21.39 | 1.00 | 0.999989 | 21.39 |
AIRLOOP DATACENTER BOT | 0.472866 | 0.472866 | 0.472866 | 0.472866 | 0.472866 | 0.472866 | 1.00 | 1.00 | 0.472866 |
AIRLOOP DATACENTER MID | 4.49 | 4.49 | 4.49 | 4.49 | 4.49 | 4.49 | 1.00 | 1.00 | 4.49 |
AIRLOOP DATACENTER TOP | 0.456270 | 0.456270 | 0.456270 | 0.456270 | 0.456270 | 0.456270 | 1.00 | 1.00 | 0.456270 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.55 | 2.54 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 88.92 | 25.38 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.51 | 2.54 |
CAV_BAS_OA_CONTROLLER | 5.83 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.39 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.472866 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.49 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.456270 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.63 | 6.67 | 11.05 | 0.011285 | 0.008500 | 264203.12 | 0.011240 | 9.55 |
VAV_MID WITH REHEAT COOLING COIL | 26.94 | 6.67 | 11.05 | 0.011670 | 0.008500 | 2599258.69 | 0.110578 | 88.92 |
VAV_TOP WITH REHEAT COOLING COIL | 26.44 | 6.67 | 11.05 | 0.011211 | 0.008500 | 258741.72 | 0.011007 | 9.51 |
CAV_BAS COOLING COIL | 24.92 | 6.67 | 11.42 | 0.010627 | 0.008500 | 134482.17 | 0.005721 | 5.83 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.55 |
VAV_MID WITH REHEAT FAN | 88.92 |
VAV_TOP WITH REHEAT FAN | 9.51 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.011240 | 0.000042 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000133 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.110578 | 0.000004 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.000991 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.011007 | 0.000043 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000083 | |
CAV_BAS_COOLC_CONTROLLER | 0.005721 | 0.000083 |
CAV_BAS_HEATC_CONTROLLER | 0.002353 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.83 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.39 | 435606.48 | 312997.16 | 0.010668 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.472866 | 9663.38 | 6927.59 | 0.000237 |
AIRLOOP DATACENTER MID COOLING COIL | 4.49 | 92090.34 | 65920.34 | 0.002255 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.456270 | 9341.61 | 6690.35 | 0.000229 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.39 | 21.39 | 21.39 | 21.39 | 435606.48 | 435606.48 | 12800.94 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.472866 | 0.472866 | 0.472866 | 0.472866 | 9663.38 | 9663.38 | 591.35 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.49 | 4.49 | 4.49 | 4.49 | 92090.34 | 92090.34 | 5913.50 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.456270 | 0.456270 | 0.456270 | 0.456270 | 9341.61 | 9341.61 | 591.35 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.39 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.472866 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.49 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.456270 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.39 | 435606.48 | 0.010668 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.472866 | 9663.38 | 0.000237 |
AIRLOOP DATACENTER MID HEATING COIL | 4.49 | 92090.34 | 0.002255 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.456270 | 9341.61 | 0.000229 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 12800.94 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 591.35 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 5913.50 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 591.35 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000037 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.138547 | 28549.39 | |
HEATSYS1 PUMP | 0.011482 | 3457.77 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.138547 | 16.63 |
HEATSYS1 | 0.011482 | 1.38 |
COOLSYS1_SUPPLY | 0.138547 | 16.63 |
SINGLE WATER PLANT LOOP | 0.013389 | 1.61 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.138547 | 0.138547 | 581551.02 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1312424.28 | 1312424.28 | 0.011482 |
CENTRAL BOILER | 551499.35 | 540881.28 | 0.013389 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.138547 | 19765.71 |
PLANT CIRC PUMP | 0.013389 | 3414.79 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.138547 | 0.069835 | 1645574.60 | 1653377.78 | 0.081820 |
COOLSYS1 CHILLER2 | 0.138547 | 0.069835 | 1645574.60 | 1653377.78 | 0.081820 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013389 | 139666.47 | 58901.94 | 69833.23 | 7879.72 | 21377.84 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.163639 | 19.64 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.163639 | 49284.53 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 62.98 | 1961699.31 | 12.60 | 245212.41 |
TOWERWATERSYS COOLTOWER 2 | 62.98 | 1961699.31 | 12.60 | 245212.41 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.084985 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.328 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 14.170 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 9.328 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.751 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 25926.330 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25926.330 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 7310.116 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7310.116 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.743 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.656 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 2.135 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4064 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4365 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3009 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | 0.76055735E-15 | 0.55973061E-16 | -0.11090261E-09 | -0.43371185E-17 |
51 | 8 | 0.16390423E-07 | 0.22068143E-12 | 0.31740643E-03 | -0.18636477E-09 |
52 | 7 | -0.10429999E-01 | 0.12271718E-07 | -0.20474149E-01 | 0.11859286E-03 |
53 | 6 | 0.35611320 | 0.43955117E-05 | 0.42991281 | -0.41673803E-02 |
54 | 5 | -4.7098961 | 0.16827687E-03 | -4.1162358 | 0.57223947E-01 |
55 | 4 | 30.875684 | 0.14076848E-02 | 20.167480 | -0.39388153 |
56 | 3 | -106.69740 | 0.31291265E-02 | -53.106522 | 1.4497707 |
57 | 2 | 192.63914 | 0.17911574E-02 | 75.570394 | -2.8293896 |
58 | 1 | -169.50392 | 0.19431750E-03 | -54.592911 | 2.7164834 |
59 | 0 | 57.057407 | 0.11257899E-05 | 15.674734 | |
60 | 9 | 0.11474244E-14 | 0.54197419E-16 | -0.11508650E-09 | -0.49945851E-17 |
61 | 8 | 0.16984416E-07 | 0.21156325E-12 | 0.32425024E-03 | -0.19311866E-09 |
62 | 7 | -0.10636353E-01 | 0.11664670E-07 | -0.20772028E-01 | 0.12093918E-03 |
63 | 6 | 0.36172330 | 0.41637772E-05 | 0.43474562 | -0.42335086E-02 |
64 | 5 | -4.7646824 | 0.15893927E-03 | -4.1535939 | 0.57903236E-01 |
65 | 4 | 31.118254 | 0.13261305E-02 | 20.314042 | -0.39710182 |
66 | 3 | -107.21418 | 0.29411649E-02 | -53.396504 | 1.4572354 |
67 | 2 | 193.15212 | 0.16802168E-02 | 75.835339 | -2.8375342 |
68 | 1 | -169.69371 | 0.18194848E-03 | -54.668081 | 2.7198097 |
69 | 0 | 57.057407 | 0.10520719E-05 | 15.660794 | |
70 | 9 | 0.66246833E-15 | 0.57738042E-16 | -0.92036509E-10 | -0.27018983E-17 |
71 | 8 | 0.13701644E-07 | 0.25726543E-12 | 0.28527343E-03 | -0.15579243E-09 |
72 | 7 | -0.94571194E-02 | 0.14940887E-07 | -0.19068097E-01 | 0.10753086E-03 |
73 | 6 | 0.32965778 | 0.54453531E-05 | 0.40701455 | -0.38555430E-02 |
74 | 5 | -4.4514676 | 0.21157254E-03 | -3.9387765 | 0.54019785E-01 |
75 | 4 | 29.731016 | 0.17930056E-02 | 19.470280 | -0.37868589 |
76 | 3 | -104.25747 | 0.40308508E-02 | -51.726693 | 1.4145289 |
77 | 2 | 190.21562 | 0.23301583E-02 | 74.311741 | -2.7909129 |
78 | 1 | -168.60668 | 0.25508611E-03 | -54.239505 | 2.7007581 |
79 | 0 | 57.057407 | 0.14924561E-05 | 15.743350 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5533E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5544E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6757E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6767E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1028E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1035E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2452E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5792E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6514E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6968E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7572E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1192E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1670E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2574E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2891E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9711E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8573E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6597E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9875E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.8468E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1347E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6042E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.1095E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5845E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6766E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7025E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7841E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1244E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1870E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2577E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2900E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5532E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5546E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6757E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6768E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1028E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1036E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2451E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7402E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8576E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6107E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7300E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.4743E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5383E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1302E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1521E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2292E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5651E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0579E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4196E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2637E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.3226E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6787E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.9865E-003 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7143E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7645E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5787E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6156E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.4554E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4712E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1303E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1525E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2066E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2078E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0406E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0415E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.2099E-004 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.2168E-004 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2452E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2332E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2990E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0624E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1148E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.3804E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.7518E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2577E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2900E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8693E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0505E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4666E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.0688E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4304E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.6624E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6042E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.1067E-003 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2312E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2961E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0599E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1097E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.3395E-004 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.6275E-004 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2574E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2891E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2065E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2076E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0405E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0413E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.2091E-004 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.2144E-004 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2451E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3477E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4000E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1379E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1758E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1023E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1165E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1303E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1525E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.5174E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3000E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.2122E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1066E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.5390E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0488E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6787E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.9865E-003 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3685E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4624E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1640E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2550E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1200E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1763E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1302E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1521E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.9605E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.9299E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.4799E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.1109E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.1587E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0397E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.0133E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4574E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7108E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1690E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.5252E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9976E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7138E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.8700E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.0820E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4729E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2593E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5652E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8190E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2540E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.7732E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 9.7402E-003 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0133E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4571E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9370E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8208E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.6042E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5845E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9319E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5189E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0820E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4729E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.9616E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.9360E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.4827E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.1180E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.1633E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0461E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.0168E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4602E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7101E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1711E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.5255E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9998E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7159E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.8733E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.0854E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4757E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2569E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5659E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8174E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2546E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.7742E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 9.7542E-003 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0168E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4599E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9355E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8222E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.6035E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5859E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9335E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5214E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0854E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4757E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 80805.15408 | 80805.15408 | 5.82541 | 5.82541 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 8.70000 | 6.99286E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 82944.08495 | 82944.08495 | 5.97880 | 5.97880 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 8.70000 | 6.99286E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 780165.50071 | 780165.50071 | 56.22166 | 56.22166 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 158465.33607 | 158465.33607 | 6.62828 | 10.77825 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 77683.39019 | 77683.39019 | 5.59821 | 5.59821 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 37845.68453 | 37845.68453 | 1.60346 | 1.60346 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13722.12675 | 13722.12675 | 0.99010 | 0.99010 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 1010.05152 | 1010.05152 | 4.30097E-002 | 0.13533 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12808.39637 | 12808.39637 | 0.93176 | 0.93176 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 30.08450 | 1.71613E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 965.90763 | 965.90763 | 4.09860E-002 | 8.72129E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 13478.36208 | 13478.36208 | 0.98050 | 0.98050 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.20000 | 1.71672E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 2927.81400 | 2927.81400 | 0.12323 | 0.13533 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 16690.17350 | 16690.17350 | 1.21414 | 1.21414 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
17 | PERIMETER_MID_ZN_3 | Cooling | 129623.91432 | 129623.91432 | 9.35224 | 9.35224 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 84802.04718 | 84802.04718 | 3.60962 | 3.60962 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 130944.39013 | 130944.39013 | 9.52660 | 9.52660 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 30.27433 | 1.71616E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 56525.77647 | 56525.77647 | 2.40647 | 2.40647 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 125743.23603 | 125743.23603 | 9.14825 | 9.14825 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.20000 | 1.71672E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 84628.92608 | 84628.92608 | 3.60221 | 3.60221 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 141123.21831 | 141123.21831 | 10.26713 | 10.26713 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 48869.01666 | 48869.01666 | 2.07873 | 2.07873 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14519.43625 | 14519.43625 | 1.05637 | 1.05637 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.13300 | 1.71671E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 11967.67538 | 11967.67538 | 0.51014 | 0.51014 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 13473.37868 | 13473.37868 | 0.98027 | 0.98027 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.65400 | 1.71624E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 7897.38883 | 7897.38883 | 0.33667 | 0.33667 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 14562.29567 | 14562.29567 | 1.05949 | 1.05949 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 11947.66703 | 11947.66703 | 0.50928 | 0.50928 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 15488.79370 | 15488.79370 | 1.12689 | 1.12689 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 7245.82098 | 7245.82098 | 0.30879 | 0.30879 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8242.72213 | 8242.72213 | 0.47287 | 0.47287 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 26.54467 | 1.71546E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 8.70000 | 6.99286E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 78328.89957 | 78328.89957 | 4.49355 | 4.49355 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 26.54467 | 1.71546E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 8.70000 | 6.99286E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7952.51728 | 7952.51728 | 0.45627 | 0.45627 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.92200 | 1.71629E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 8.70000 | 6.99286E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372737.63450 | 372737.63450 | 21.38510 | 21.38510 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.10300 | 1.71556E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 8.70000 | 6.99286E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 148355.40 | 9.54868 | 9.54868 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 7546.34 | 1.52292 | 1.52292 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1356964.12 | 88.91873 | 88.91873 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 111369.23 | 22.47528 | 22.47528 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 156258.89 | 9.50710 | 9.50710 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 12528.34 | 3.26835 | 3.26835 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:10:00 |
7 | CAV_BAS | Cooling | Sensible | 85348.05 | 5.82541 | 5.82541 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 45400.28 | 1.20016 | 1.20016 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 369000.92 | 21.38534 | 21.38534 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 12800.94 | 0.33839 | 0.33839 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8126.32 | 0.47287 | 0.47287 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 591.35 | 1.56323E-002 | 1.56323E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 77293.57 | 4.49355 | 4.49355 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 5913.50 | 0.15632 | 0.15632 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7904.01 | 0.45627 | 0.45627 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 591.35 | 1.56323E-002 | 1.56323E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.82541 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.97880 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31813 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32200 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.92518 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84835 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19762E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69380E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.92518 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19361.22458 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69380E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 390.30709 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 56.22166 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33831 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33600 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.89048 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90216 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12618E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.04834E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.89048 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 348444.32803 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.04834E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7656.69952 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.59821 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33976 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34400 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.92579 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90602 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12138E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.00525E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.92579 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 57213.04800 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.00525E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1435.41866 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99010 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24121 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29703 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64323 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57954E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.49367E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29703 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3993.48194 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.49367E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 83.26906 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93176 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16518 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27953 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44047 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.30663E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.30152E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27953 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3773.83524 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.30152E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 78.73398 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98050 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24357 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29415 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64953 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.56420E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.14702E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29415 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5883.36113 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.14702E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 131.50741 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.21414 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12676 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36424 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33803 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.00567E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.20467E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36424 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3663.13035 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.20467E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 73.84583 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.35224 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25536 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.80567 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68096 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49200E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05930E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.60962 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 121085.05284 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05930E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3195.89657 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.52660 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16155 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.85798 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43081 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35836E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.45838E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.85798 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 85253.86335 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.45838E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2142.26427 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.14825 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26106 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.74447 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69617 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45942E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05714E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.60221 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 120837.36250 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05714E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3189.37156 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.26713 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14990 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.08014 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39974 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54168E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.98360E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.08014 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 79826.81297 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.98360E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1910.60468 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05637 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22608 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31691 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60287 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68527E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49566E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51014 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17096.30129 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49566E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 451.03812 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98027 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15700 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29408 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41868 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42670E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.87004E-005 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33667 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11282.05835 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.87004E-005 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 297.63689 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05949 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22542 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31785 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60111 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.69021E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49315E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50928 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17067.67596 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49315E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 450.28401 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12689 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13657 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33807 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36420 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.78968E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.31217E-005 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33807 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10644.38128 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.31217E-005 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 273.30545 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47287 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.49355 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45627 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.38510 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.04765 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.16013 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.09531 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.16013 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.54868 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.54868 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33095 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 47.25794 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 30.37874 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 94.51588 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 30.37874 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 88.91873 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 88.91873 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34165 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.91062 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.19269 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.82124 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.26835 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.50710 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.50710 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34378 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.82541 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.82541 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.82541 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.82541 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.82541 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.82541 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.38510 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.38510 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.38510 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.38510 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.38534 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.38534 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47287 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47287 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47287 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47287 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47287 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.47287 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.49355 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.49355 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.49355 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.49355 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.49355 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.49355 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45627 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45627 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45627 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45627 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45627 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45627 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.54868 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 88.91873 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.50710 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.82541 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.38534 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.47287 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.49355 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45627 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.54868 |
289 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
290 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.62978 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04853 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.12847E-002 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 264203.12424 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.12398E-002 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.54868 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 15205.56816 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33025E-004 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 269.98620 |
302 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.54868 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.12398E-002 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.23664E-005 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.33025E-004 |
306 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 88.91873 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 25.38195 |
308 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.93932 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04975 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.16700E-002 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2599258.69332 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 0.11058 |
316 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 88.91873 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 113326.29502 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.91428E-004 |
319 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2025.52086 |
320 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 88.91873 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.11058 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.30636E-006 |
323 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.91428E-004 |
324 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.50710 |
325 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
326 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.44492 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04830 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.12111E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 258741.72242 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.10075E-002 |
334 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.50710 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 9466.03706 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.28130E-005 |
337 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.19050 |
338 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.50710 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.10075E-002 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.32607E-005 |
341 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.28130E-005 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.82541 |
343 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.92245 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.42401 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.06266E-002 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 134482.16802 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.72118E-003 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.82541 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 269000.46252 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.35333E-003 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6149.60514 |
355 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.82541 |
356 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.72118E-003 |
357 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.32329E-005 |
358 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.35333E-003 |
359 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.38534 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.38534 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 435606.47838 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 312997.16272 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06680E-002 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.38534 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.38534 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.38534 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.38534 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 435606.47838 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 435606.47838 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 12800.93607 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
373 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.38534 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.38534 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 435606.47838 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06680E-002 |
377 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 12800.93607 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 3.73288E-005 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
381 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
382 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47287 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47287 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9663.38475 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6927.59391 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36656E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47287 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47287 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47287 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47287 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9663.38475 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9663.38475 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 591.35022 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47287 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47287 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9663.38475 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36656E-004 |
400 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 591.35022 |
401 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.49355 |
402 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.49355 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 92090.34496 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 65920.33955 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25529E-003 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.49355 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.49355 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.49355 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.49355 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 92090.34496 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 92090.34496 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 5913.50215 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
415 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.49355 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.49355 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 92090.34496 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25529E-003 |
419 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5913.50215 |
420 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45627 |
421 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45627 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9341.61459 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6690.34987 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28776E-004 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45627 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45627 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45627 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45627 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9341.61459 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9341.61459 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 591.35022 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
434 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45627 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45627 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9341.61459 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28776E-004 |
438 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 591.35022 |
439 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.13855 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 28549.38899 |
441 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.13855 |
442 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 16.62563 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.13855 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.13855 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 581551.01929 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
447 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.14817E-002 |
448 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.37780 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.14817E-002 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3457.77182 |
451 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1312424.28056 |
453 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1312424.28000 |
454 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.14817E-002 |
455 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.13855 |
456 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 16.62563 |
457 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.13855 |
458 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 19765.70504 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13855 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.98350E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1645574.59857 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1653377.78000 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 8.18195E-002 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13855 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.98350E-002 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1645574.59857 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1653377.78000 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 8.18195E-002 |
469 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.33887E-002 |
470 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.60664 |
471 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.33887E-002 |
472 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3414.78611 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.33887E-002 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 58901.94056 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21377.83845 |
479 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 551499.34707 |
480 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 540881.28000 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.33887E-002 |
482 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
483 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
484 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
486 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.16364 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 19.63669 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.16364 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 49284.52859 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 62.97964 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1961699.31222 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 12.59593 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 245212.41403 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 62.97964 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1961699.31222 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 12.59593 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 245212.41403 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 8.49850E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 8.49850E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18358.22 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 330235.42 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 54184.80 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 3786.00 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3577.76 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5575.48 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3473.36 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 114736.76 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 80740.89 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 114502.14 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 75621.49 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16198.64 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10689.62 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16171.53 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10080.01 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 13560.81 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 102292.21 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 8636.10 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 220085.63 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 263138.57 | 177273.99 | 85864.58 | 0.67 | 27463.45 | 278.55 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2501215.19 | 1674939.00 | 826276.19 | 0.67 | 262396.45 | 2661.37 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 260538.77 | 175823.45 | 84715.32 | 0.67 | 27189.82 | 275.77 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 148112.93 | 102180.47 | 45932.46 | 0.69 | 15105.89 | 153.21 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2046937275 | 0.1933037275 | Pass | Pass | 3.5511657622 | 18.9952485399 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2859203022 | 0.2425201793 | Pass | Pass | 0.2891424177 | 0.4522952229 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1619585601 | 0.1684551649 | Pass | Pass | 0.2229901157 | 0.4152960308 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1379600063 | 0.1961870198 | Pass | Pass | 0.2037261045 | 0.4010940030 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2868700682 | 0.2503812905 | Pass | Pass | 0.2867149123 | 0.4488944037 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4317261760 | 0.3987816688 | Pass | Pass | 0.2907069688 | 0.4478930641 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3943891661 | 0.4141967813 | Pass | Pass | 0.3293602613 | 0.4931346378 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5038459616 | 0.4551505219 | Pass | Pass | 0.2916406574 | 0.4467122419 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1666470461 | 0.1907560687 | Pass | Pass | 0.2225032587 | 0.4131261180 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2965587228 | 0.3464483737 | Pass | Pass | 0.2248949659 | 0.4132944992 | Pass | Fail |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2908764495 | 0.4084302720 | Pass | Pass | 0.2584445293 | 0.4605315488 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2641008404 | 0.3213111248 | Pass | Pass | 0.2240228817 | 0.4108088528 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1695018312 | 0.2218235357 | Pass | Pass | 0.2026362124 | 0.3996181202 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2740694206 | 0.3382604436 | Pass | Pass | 0.2043075276 | 0.4016098887 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2825795509 | 0.4220145432 | Pass | Pass | 0.2270177348 | 0.4271022928 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2618099857 | 0.3519890684 | Pass | Pass | 0.2045072237 | 0.3986415529 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.8913137934E-002 | 4.2007236361E-002 | Pass | Pass | 0.3133319167 | 0.4576172728 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.2752893645E-002 | 3.9732652915E-002 | Pass | Pass | 0.2447406902 | 0.4277151137 | Fail | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.8476871969E-002 | 8.4250301961E-002 | Pass | Pass | 0.2006517199 | 0.3794172228 | Fail | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.8034393787E-004 | 3.0387512183E-004 | Pass | Pass | 2.5060265290E-003 | 1.5695928521E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.3354931442E-006 | 6.5065256401E-006 | Pass | Pass | 2.9986542663E-003 | 2.6989149913E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.8186075294E-006 | 5.6299886957E-006 | Pass | Pass | 3.9919145932E-003 | 3.2595039991E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.8173628275E-004 | 3.1558725551E-004 | Pass | Pass | 4.0451630882E-005 | 1.1306356262E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5688.14 | -100.6 | 0.00 | -11075.3 | 40290.89 | 34803.06 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 1043.06 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.869 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.3279 | 2779.43 | 25926.33 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 240.45 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.3279 | 24961.20 | 232836.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 2159.39 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.87 | 0.0000 | Y | 18.59 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.85 | 0.0000 | Y | 11.97 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.66 | 0.0000 | Y | 18.47 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.81 | 0.0000 | Y | 11.96 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.3279 | 3134.13 | 29234.97 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.91 | 0.0000 | Y | 186.07 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.86 | 0.0000 | Y | 119.74 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.3279 | 3134.20 | 29235.61 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.67 | 0.0000 | Y | 184.80 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.82 | 0.0000 | Y | 119.62 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.91 | 0.0000 | Y | 18.61 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.86 | 0.0000 | Y | 11.97 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.67 | 0.0000 | Y | 18.48 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.82 | 0.0000 | Y | 11.96 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 9.3279 | 783.68 | 7310.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 67.80 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 16.0861 | 362.03 | 5823.61 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 59.65 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
Interior Lighting Total | 9.3913 | 46320.38 | 435009.77 | 1156.99 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.01 | AstronomicalClock | - | 41.82 | 41.82 | 78.30 | |
EXTERIOR_LIGHTS_B | 44362.79 | AstronomicalClock | - | 83.82 | 71.22 | 593.12 | |
Exterior Lighting Total | 54335.80 | 671.42 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3249196.29 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1312424.28 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1653377.78 | 6.28 | 1582499.52 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1653377.78 | 6.28 | 1582499.52 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 540881.28 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1961699.31 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1961699.31 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 264203.12 | 263138.57 | 177273.99 | 85864.58 | 0.67 | - | 27463.45 | 278.55 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2599258.69 | 2501215.19 | 1674939.00 | 826276.19 | 0.67 | - | 262396.45 | 2661.37 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 258741.72 | 260538.77 | 175823.45 | 84715.32 | 0.67 | - | 27189.82 | 275.77 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 134482.17 | 148112.93 | 102180.47 | 45932.46 | 0.69 | - | 15105.89 | 153.21 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 435606.48 | 312997.16 | 122609.32 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9663.38 | 6927.59 | 2735.79 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 92090.34 | 65920.34 | 26170.01 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9341.61 | 6690.35 | 2651.26 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19361.22 | 18358.22 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 348444.33 | 330235.42 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 57213.05 | 54184.80 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 3993.48 | 3786.00 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 3773.84 | 3577.76 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5883.36 | 5575.48 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3663.13 | 3473.36 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 121085.05 | 114736.76 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 85253.86 | 80740.89 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 120837.36 | 114502.14 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 79826.81 | 75621.49 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17096.30 | 16198.64 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11282.06 | 10689.62 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17067.68 | 16171.53 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10644.38 | 10080.01 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 15205.57 | 13560.81 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 113326.30 | 102292.21 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 9466.04 | 8636.10 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 269000.46 | 220085.63 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 435606.48 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9663.38 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 92090.34 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9341.61 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 12800.94 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 591.35 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 5913.50 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 591.35 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.55 | 20634.20 | 2160.95 | 1.00 | 1.12 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 88.92 | 192148.63 | 2160.95 | 1.00 | 1.08 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.51 | 20544.33 | 2160.95 | 1.00 | 1.12 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.83 | 9877.89 | 1695.65 | 1.00 | 1.16 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.39 | 35456.32 | 1657.97 | 1.00 | 1.13 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 529.66 | 1120.11 | 1.00 | 1.63 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.49 | 5033.26 | 1120.11 | 1.00 | 1.16 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 511.07 | 1120.11 | 1.00 | 1.65 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.138547 | 28549.39 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.011482 | 3457.77 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.138547 | 19765.71 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013389 | 3414.79 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.163639 | 49284.53 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 80805.15 | 80805.15 | 29.07 | 5.825 | 5.825 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 28.24 | 0.01716 | 1.200 | 0.00 |
CORE_BOTTOM | 82944.08 | 82944.08 | 33.23 | 5.979 | 5.979 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 28.24 | 0.01716 | 1.078 | 0.00 |
CORE_MID | 780165.50 | 780165.50 | 312.55 | 56.222 | 56.222 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 28.24 | 0.01716 | 10.778 | 0.00 |
CORE_TOP | 77683.39 | 77683.39 | 31.12 | 5.598 | 5.598 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 28.24 | 0.01716 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13722.13 | 13722.13 | 43.78 | 0.990 | 0.990 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00900 | 28.24 | 0.01716 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12808.40 | 12808.40 | 63.42 | 0.932 | 0.932 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00884 | 30.08 | 0.01716 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 13478.36 | 13478.36 | 43.00 | 0.981 | 0.981 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00899 | 33.20 | 0.01717 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 16690.17 | 16690.17 | 82.63 | 1.214 | 1.214 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00876 | 32.26 | 0.01717 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 129623.91 | 129623.91 | 413.59 | 9.352 | 9.352 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00931 | 28.24 | 0.01716 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 130944.39 | 130944.39 | 648.32 | 9.527 | 9.527 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00902 | 30.27 | 0.01716 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 125743.24 | 125743.24 | 401.20 | 9.148 | 9.148 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00931 | 33.20 | 0.01717 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 141123.22 | 141123.22 | 698.72 | 10.267 | 10.267 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00898 | 32.26 | 0.01717 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14519.44 | 14519.44 | 46.33 | 1.056 | 1.056 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00930 | 33.13 | 0.01717 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13473.38 | 13473.38 | 66.71 | 0.980 | 0.980 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00908 | 30.65 | 0.01716 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14562.30 | 14562.30 | 46.46 | 1.059 | 1.059 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00930 | 33.20 | 0.01717 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15488.79 | 15488.79 | 76.69 | 1.127 | 1.127 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00901 | 32.26 | 0.01717 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8242.72 | 8242.72 | 227.68 | 0.473 | 0.473 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.54 | 0.01715 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78328.90 | 78328.90 | 2163.62 | 4.494 | 4.494 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.54 | 0.01715 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7952.52 | 7952.52 | 219.67 | 0.456 | 0.456 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 30.92 | 0.01716 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372737.63 | 372737.63 | 475.63 | 21.385 | 21.385 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 27.10 | 0.01716 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 26.09 | 0.00699 | 8.70 | 0.00699 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 23.65 | 0.00699 | 8.70 | 0.00699 | 1.078 | 0.00 | |
CORE_MID | 158465.34 | 158465.34 | 63.48 | 6.628 | 10.778 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 10.778 | 0.00 |
CORE_TOP | 37845.68 | 37845.68 | 15.16 | 1.603 | 1.603 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 1010.05 | 1010.05 | 3.22 | 0.043 | 0.135 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00733 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 965.91 | 965.91 | 4.78 | 0.041 | 0.087 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00738 | 8.70 | 0.00699 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 2927.81 | 2927.81 | 9.34 | 0.123 | 0.135 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 21.18 | 0.00699 | 8.70 | 0.00699 | 0.087 | 0.00 | |
PERIMETER_MID_ZN_3 | 84802.05 | 84802.05 | 270.58 | 3.610 | 3.610 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | 8.70 | 0.00699 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 56525.78 | 56525.78 | 279.87 | 2.406 | 2.406 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 8.70 | 0.00699 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 84628.93 | 84628.93 | 270.02 | 3.602 | 3.602 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | 8.70 | 0.00699 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 48869.02 | 48869.02 | 241.96 | 2.079 | 2.079 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | 8.70 | 0.00699 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11967.68 | 11967.68 | 38.19 | 0.510 | 0.510 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 7897.39 | 7897.39 | 39.10 | 0.337 | 0.337 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 8.70 | 0.00699 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 11947.67 | 11947.67 | 38.12 | 0.509 | 0.509 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 7245.82 | 7245.82 | 35.87 | 0.309 | 0.309 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 8.70 | 0.00699 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 8.70 | 0.00699 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.25 | 0.00848 | 8.70 | 0.00699 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.35 | 0.00722 | 8.70 | 0.00699 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 8.70 | 0.00699 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.55 | 9.55 | 1.52 | 1.52 | 9.5487 | 3.1601 | 9.5487 | 0.3309 | 0.3000 |
VAV_MID WITH REHEAT | 88.92 | 88.92 | 22.48 | 22.48 | 88.9187 | 30.3787 | 88.9187 | 0.3416 | 0.3000 |
VAV_TOP WITH REHEAT | 9.51 | 9.51 | 3.27 | 3.27 | 9.5071 | 3.2683 | 9.5071 | 0.3438 | 0.3000 |
CAV_BAS | 5.83 | 5.83 | 1.20 | 1.20 | 5.8254 | 5.8254 | 5.8254 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.39 | 21.39 | 0.34 | 0.34 | 21.3853 | 21.3851 | 21.3853 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4729 | 0.4729 | 0.4729 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.49 | 4.49 | 0.16 | 0.16 | 4.4935 | 4.4935 | 4.4935 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4563 | 0.4563 | 0.4563 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19361.225 | 19361.225 | 1.925175 | 0.00016938 | 390.307 | 1/21 00:10:00 | 1/21 00:10:00 | 19361.22 | 19361.22 | 1.925175 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 19432.61 | 19432.61 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 348444.328 | 348444.328 | 18.890479 | 0.00304834 | 7656.700 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 348444.33 | 348444.33 | 18.890479 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 158465.34 | 0.00 | 349648.95 | 349648.95 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 57213.048 | 57213.048 | 1.925786 | 0.00050052 | 1435.419 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 57213.05 | 57213.05 | 1.925786 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 37845.68 | 0.00 | 57391.06 | 57391.06 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 3993.482 | 3993.482 | 0.297029 | 0.00003494 | 83.269 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3993.48 | 3993.48 | 0.297029 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00732633 | 47.3574 | 1010.05 | 0.00 | 4007.96 | 4007.96 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 3773.835 | 3773.835 | 0.279529 | 0.00003302 | 78.734 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3773.84 | 3773.84 | 0.279529 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00738445 | 47.7289 | 965.91 | 0.00 | 3787.52 | 3787.52 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 5883.361 | 5883.361 | 0.294151 | 0.00005147 | 131.507 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5883.36 | 5883.36 | 0.294151 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00752983 | 48.6578 | 2927.81 | 0.00 | 5903.53 | 5903.53 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3663.130 | 3663.130 | 0.364242 | 0.00003205 | 73.846 | 1/21 00:10:00 | 1/21 00:10:00 | 3663.13 | 3663.13 | 0.364242 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 3676.64 | 3676.64 | ||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 121085.053 | 121085.053 | 3.609624 | 0.00105930 | 3195.897 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 121085.05 | 121085.05 | 3.609624 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00776339 | 50.1490 | 84802.05 | 0.00 | 121500.76 | 121500.76 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 85253.863 | 85253.863 | 2.857981 | 0.00074584 | 2142.264 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 85253.86 | 85253.86 | 2.857981 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00777070 | 50.1957 | 56525.78 | 0.00 | 85518.89 | 85518.89 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 120837.363 | 120837.363 | 3.602210 | 0.00105714 | 3189.372 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 120837.36 | 120837.36 | 3.602210 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00776279 | 50.1452 | 84628.93 | 0.00 | 121252.31 | 121252.31 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 79826.813 | 79826.813 | 3.080138 | 0.00069836 | 1910.605 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 79826.81 | 79826.81 | 3.080138 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00771529 | 49.8424 | 48869.02 | 0.00 | 80086.05 | 80086.05 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 17096.301 | 17096.301 | 0.510142 | 0.00014957 | 451.038 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17096.30 | 17096.30 | 0.510142 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00784431 | 50.6650 | 11967.68 | 0.00 | 17153.57 | 17153.57 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11282.058 | 11282.058 | 0.336670 | 0.00009870 | 297.637 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11282.06 | 11282.06 | 0.336670 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00784607 | 50.6762 | 7897.39 | 0.00 | 11319.79 | 11319.79 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 17067.676 | 17067.676 | 0.509285 | 0.00014932 | 450.284 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17067.68 | 17067.68 | 0.509285 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00784402 | 50.6631 | 11947.67 | 0.00 | 17124.86 | 17124.86 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 10644.381 | 10644.381 | 0.338068 | 0.00009312 | 273.305 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10644.38 | 10644.38 | 0.338068 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00782321 | 50.5306 | 7245.82 | 0.00 | 10677.13 | 10677.13 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 264203.124 | -999.000 | 9.548684 | 0.01123981 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 264203.12 | 180665.89 | 9.548684 | 26.63 | 19.51 | 0.01128469 | 11.05 | 11.05 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 26.5816 | 24.00 | 0.00892879 | 47.9792 | 122015.42 | 0.00 | 264559.50 | 176596.53 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 15205.568 | 15205.568 | 2.864605 | 0.00013302 | 269.986 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 15205.57 | 15205.57 | 2.864605 | 8.41 | 8.41 | 0.00700823 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 88.6052 | 21.13 | 0.00733647 | 47.0539 | 0.00 | 0.00 | 16418.89 | 16418.89 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2599258.693 | -999.000 | 88.918726 | 0.11057847 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2599258.69 | 1714685.77 | 88.918726 | 26.94 | 19.90 | 0.01167005 | 11.05 | 11.05 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 28.5451 | 24.00 | 0.00908742 | 48.8208 | 1091560.74 | 0.00 | 2602909.08 | 1683044.45 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 113326.295 | 113326.295 | 26.675618 | 0.00099143 | 2025.521 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 113326.30 | 113326.30 | 26.675618 | 9.28 | 9.02 | 0.00703555 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 95.1504 | 21.00 | 0.00784436 | 50.6649 | 433291.10 | 0.00 | 123849.75 | 123849.75 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 258741.722 | -999.000 | 9.507096 | 0.01100747 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 258741.72 | 177742.94 | 9.507096 | 26.44 | 19.39 | 0.01121112 | 11.05 | 11.05 | 0.00850000 | 33.13 | 0.01716709 | 25.31 | 26.6978 | 24.00 | 0.00903195 | 48.5274 | 130249.97 | 0.00 | 259187.25 | 173638.07 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 9466.037 | 9466.037 | 2.852129 | 0.00008281 | 170.191 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9466.04 | 9466.04 | 2.852129 | 10.05 | 9.43 | 0.00709538 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 88.9928 | 21.00 | 0.00792429 | 51.1740 | 59261.71 | 0.00 | 10456.00 | 10456.00 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 134482.168 | -999.000 | 5.825413 | 0.00572118 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 134482.17 | 96209.80 | 5.825413 | 24.92 | 18.45 | 0.01062659 | 11.42 | 11.42 | 0.00850000 | 28.24 | 0.01715778 | 24.03 | 20.6021 | 24.00 | 0.00893188 | 47.9950 | 80805.15 | 0.00 | 134675.27 | 93653.64 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 269000.463 | 269000.463 | 5.825413 | 0.00235333 | 6149.605 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 269000.46 | 269000.46 | 5.825413 | 1.79 | 1.79 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 20.6021 | 26.09 | 0.00699286 | 33.2718 | 0.00 | 0.00 | 233017.26 | 233017.26 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 435606.478 | 312997.163 | 21.385338 | 0.01066797 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 408139.50 | 397622.24 | -999.0 | 28.50 | 18.07 | 0.00867883 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | -999.0000 | 27.00 | 0.00854217 | 38.4364 | 372219.97 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9663.385 | 6927.594 | 0.472866 | 0.00023666 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 9058.31 | 8571.98 | -999.0 | 28.08 | 18.09 | 0.00887414 | 12.80 | 12.09 | 0.00850000 | 30.92 | 0.01716288 | 24.74 | -999.0000 | 27.00 | 0.00858849 | 38.6397 | 8178.67 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92090.345 | 65920.340 | 4.493547 | 0.00225529 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 86365.59 | 81505.68 | -999.0 | 28.08 | 18.11 | 0.00889336 | 12.80 | 12.09 | 0.00850000 | 30.92 | 0.01716288 | 24.74 | -999.0000 | 27.00 | 0.00859306 | 38.6603 | 77754.61 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9341.615 | 6690.350 | 0.456270 | 0.00022878 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8759.48 | 8276.78 | -999.0 | 28.09 | 18.10 | 0.00888480 | 12.80 | 12.09 | 0.00850000 | 31.09 | 0.01716319 | 24.78 | -999.0000 | 27.00 | 0.00859100 | 38.6510 | 7949.64 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 435606.478 | 435606.478 | 21.385338 | 0.01066797 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 435606.48 | 435606.48 | 21.385338 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 1.5824 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9663.385 | 9663.385 | 0.472866 | 0.00023666 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9663.38 | 9663.38 | 0.472866 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.3059 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92090.345 | 92090.345 | 4.493547 | 0.00225529 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 92090.34 | 92090.34 | 4.493547 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.4788 | 25.25 | 0.00847983 | 42.3116 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9341.615 | 9341.615 | 0.456270 | 0.00022878 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9341.61 | 9341.61 | 0.456270 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.4261 | 24.35 | 0.00722418 | 38.1038 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 12800.936 | 12800.936 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 12800.94 | 12800.94 | 21.385338 | 0.14 | 0.14 | 0.00847615 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 1.5824 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 591.350 | 591.350 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 591.35 | 591.35 | 0.472866 | 0.29 | 0.29 | 0.00845018 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.3059 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 5913.502 | 5913.502 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 5913.50 | 5913.50 | 4.493547 | 0.30 | 0.30 | 0.00842810 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.4788 | 25.25 | 0.00847983 | 42.3116 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 591.350 | 591.350 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 591.35 | 591.35 | 0.456270 | 0.30 | 0.30 | 0.00721625 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.4261 | 24.35 | 0.00722418 | 38.1038 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19361.225 | 19361.225 | 1.925175 | 0.00016938 | 390.307 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 1.4461 | 1.475226 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 19361.22 | 19361.22 | 1.0000 | 2.31548307 | 1.925175 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.16936316 | 60.00 | 32.22 | 27.78 | 0.000 | 19361.22 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 19432.61 | 19432.61 | 2.31548307 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 348444.328 | 348444.328 | 18.890479 | 0.00304834 | 7656.700 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 26.0259 | 26.549671 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 348444.33 | 348444.33 | 1.0000 | 22.72031462 | 18.890479 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 3.04803202 | 60.00 | 32.22 | 27.78 | 0.000 | 348444.33 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.60 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 158465.34 | 0.00 | 349648.95 | 349648.95 | 22.72031462 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.89 | 17.32 | 0.00800000 | 48449.1 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 57213.048 | 57213.048 | 1.925786 | 0.00050052 | 1435.419 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 4.2733 | 4.359341 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 57213.05 | 57213.05 | 1.0000 | 2.31621725 | 1.925786 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.50047364 | 60.00 | 32.22 | 27.78 | 0.000 | 57213.05 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 37845.68 | 0.00 | 57391.06 | 57391.06 | 2.31621725 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.10 | 20.31 | 0.00800000 | 57837.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3993.482 | 3993.482 | 0.297029 | 0.00003494 | 83.269 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 0.2983 | 0.304283 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3993.48 | 3993.48 | 1.0000 | 0.35724816 | 0.297029 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.03493316 | 60.00 | 32.22 | 27.78 | 0.000 | 3993.48 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00732633 | 21.00 | 0.00732633 | 47.3574 | 1010.05 | 0.00 | 4007.96 | 4007.96 | 0.35724816 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.80 | 15.88 | 0.00800000 | 44278.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3773.835 | 3773.835 | 0.279529 | 0.00003302 | 78.734 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 0.2819 | 0.287547 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3773.84 | 3773.84 | 1.0000 | 0.33620023 | 0.279529 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.03301179 | 60.00 | 32.22 | 27.78 | 0.000 | 3773.84 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00738445 | 21.00 | 0.00738445 | 47.7289 | 965.91 | 0.00 | 3787.52 | 3787.52 | 0.33620023 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.85 | 15.90 | 0.00800000 | 44325.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5883.361 | 5883.361 | 0.294151 | 0.00005147 | 131.507 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 0.4394 | 0.448282 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5883.36 | 5883.36 | 1.0000 | 0.35378727 | 0.294151 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.05146496 | 60.00 | 32.22 | 27.78 | 0.000 | 5883.36 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.83 | 0.00752983 | 21.00 | 0.00752983 | 48.6578 | 2927.81 | 0.00 | 5903.53 | 5903.53 | 0.35378727 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.16 | 17.76 | 0.00800000 | 49746.5 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3663.130 | 3663.130 | 0.364242 | 0.00003205 | 73.846 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 0.2736 | 0.279112 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 3663.13 | 3663.13 | 1.0000 | 0.43808780 | 0.364242 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.03204339 | 60.00 | 32.22 | 27.78 | 0.000 | 3663.13 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 3676.64 | 3676.64 | 0.43808780 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 121085.053 | 121085.053 | 3.609624 | 0.00105930 | 3195.897 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 9.0440 | 9.226060 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 121085.05 | 121085.05 | 1.0000 | 4.34143555 | 3.609624 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.05919680 | 60.00 | 32.22 | 27.78 | 0.000 | 121085.05 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00776339 | 21.00 | 0.00776339 | 50.1490 | 84802.05 | 0.00 | 121500.76 | 121500.76 | 4.34143555 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.25 | 0.00800000 | 61046.1 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 85253.863 | 85253.863 | 2.857981 | 0.00074584 | 2142.264 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 6.3678 | 6.495907 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 85253.86 | 85253.86 | 1.0000 | 3.43740515 | 2.857981 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.74576190 | 60.00 | 32.22 | 27.78 | 0.000 | 85253.86 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00777070 | 21.00 | 0.00777070 | 50.1957 | 56525.78 | 0.00 | 85518.89 | 85518.89 | 3.43740515 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.20 | 20.34 | 0.00800000 | 57938.7 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 120837.363 | 120837.363 | 3.602210 | 0.00105714 | 3189.372 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 9.0255 | 9.207187 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 120837.36 | 120837.36 | 1.0000 | 4.33251777 | 3.602210 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.05703012 | 60.00 | 32.22 | 27.78 | 0.000 | 120837.36 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00776279 | 21.00 | 0.00776279 | 50.1452 | 84628.93 | 0.00 | 121252.31 | 121252.31 | 4.33251777 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.25 | 0.00800000 | 61046.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 79826.813 | 79826.813 | 3.080138 | 0.00069836 | 1910.605 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 5.9624 | 6.082394 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 79826.81 | 79826.81 | 1.0000 | 3.70460198 | 3.080138 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.69828854 | 60.00 | 32.22 | 27.78 | 0.000 | 79826.81 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00771529 | 21.00 | 0.00771529 | 49.8424 | 48869.02 | 0.00 | 80086.05 | 80086.05 | 3.70460198 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.00 | 19.34 | 0.00800000 | 54677.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17096.301 | 17096.301 | 0.510142 | 0.00014957 | 451.038 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 1.2770 | 1.302650 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17096.30 | 17096.30 | 1.0000 | 0.61356710 | 0.510142 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.14955064 | 60.00 | 32.22 | 27.78 | 0.000 | 17096.30 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00784431 | 21.00 | 0.00784431 | 50.6650 | 11967.68 | 0.00 | 17153.57 | 17153.57 | 0.61356710 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61016.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11282.058 | 11282.058 | 0.336670 | 0.00009870 | 297.637 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 0.8427 | 0.859635 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11282.06 | 11282.06 | 1.0000 | 0.40492625 | 0.336670 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.09869030 | 60.00 | 32.22 | 27.78 | 0.000 | 11282.06 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00784607 | 21.00 | 0.00784607 | 50.6762 | 7897.39 | 0.00 | 11319.79 | 11319.79 | 0.40492625 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61015.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17067.676 | 17067.676 | 0.509285 | 0.00014932 | 450.284 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 1.2748 | 1.300469 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17067.68 | 17067.68 | 1.0000 | 0.61253654 | 0.509285 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.14930024 | 60.00 | 32.22 | 27.78 | 0.000 | 17067.68 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00784402 | 21.00 | 0.00784402 | 50.6631 | 11947.67 | 0.00 | 17124.86 | 17124.86 | 0.61253654 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61017.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10644.381 | 10644.381 | 0.338068 | 0.00009312 | 273.305 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 0.7950 | 0.811047 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10644.38 | 10644.38 | 1.0000 | 0.40660732 | 0.338068 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.09311219 | 60.00 | 32.22 | 27.78 | 0.000 | 10644.38 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00782321 | 21.00 | 0.00782321 | 50.5306 | 7245.82 | 0.00 | 10677.13 | 10677.13 | 0.40660732 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.55 | 20.75 | 0.00800000 | 59318.9 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 264203.124 | -999.000 | 9.548684 | 0.01123981 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.8177 | 1004.8586 | 1.2027 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.548684 | 11.48457372 | 4197.9300 | 999.8980 | 138.53280528 | 12.27 | 6.67 | 5.60 | 3256685.71 | 8.1126 | 8.112638 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 264203.12 | 180665.89 | 1.0000 | 11.48457372 | 9.548684 | 26.63 | 19.51 | 0.01128469 | 55539.6 | 11.05 | 11.05 | 0.00850000 | 32534.6 | 11.23866509 | 6.67 | 12.27 | 5.60 | 20634.197 | 243568.93 | 33.20 | 0.01716721 | 25.32 | 2.53819000 | 26.5816 | 24.00 | 0.00892879 | 24.00 | 0.00892879 | 47.9792 | 122015.42 | 0.00 | 264559.50 | 176596.53 | 11.48457372 | 26.63 | 19.52 | 0.01128469 | 55539.6 | 11.64 | 11.36 | 0.00824842 | 32503.5 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15205.568 | 15205.568 | 2.864605 | 0.00013302 | 269.986 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.548684 | 11.48457372 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 1.1357 | 1.158586 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 15205.57 | 15205.57 | 1.0000 | 3.44537212 | 2.864605 | 8.41 | 8.41 | 0.00700823 | 26085.4 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.13301137 | 60.00 | 32.22 | 27.78 | 0.000 | 15205.57 | 8.70 | 0.00699286 | 8.70 | 2.53819000 | 88.6052 | 6.14 | 0.00712773 | 21.13 | 0.00733647 | 47.0539 | 0.00 | 0.00 | 16418.89 | 16418.89 | 3.44537212 | 2.80 | 2.80 | 0.00700823 | 20377.2 | 7.48 | 7.48 | 0.00700823 | 25142.7 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2599258.693 | -999.000 | 88.918726 | 0.11057847 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5340 | 1004.8586 | 1.2027 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 88.918726 | 106.94601384 | 4197.9300 | 999.8980 | 138.53280528 | 12.27 | 6.67 | 5.60 | 3256685.71 | 79.8130 | 79.813004 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2599258.69 | 1714685.77 | 1.0000 | 106.94601384 | 88.918726 | 26.94 | 19.90 | 0.01167005 | 56840.2 | 11.05 | 11.05 | 0.00850000 | 32535.8 | 110.56719338 | 6.67 | 12.27 | 5.60 | 192148.632 | 2407110.06 | 33.20 | 0.01716721 | 25.32 | 25.38195000 | 28.5451 | 24.00 | 0.00908742 | 24.00 | 0.00908742 | 48.8208 | 1091560.74 | 0.00 | 2602909.08 | 1683044.45 | 106.94601384 | 26.94 | 19.91 | 0.01167005 | 56840.2 | 11.61 | 11.36 | 0.00826028 | 32501.7 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 113326.295 | 113326.295 | 26.675618 | 0.00099143 | 2025.521 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 88.918726 | 106.94601384 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 8.4645 | 8.634883 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 113326.30 | 113326.30 | 1.0000 | 32.08380415 | 26.675618 | 9.28 | 9.02 | 0.00703555 | 27046.7 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.99132673 | 60.00 | 32.22 | 27.78 | 0.000 | 113326.30 | 8.70 | 0.00699286 | 8.70 | 25.38195000 | 95.1504 | 20.76 | 0.00787310 | 21.00 | 0.00784436 | 50.6649 | 433291.10 | 0.00 | 123849.75 | 123849.75 | 32.08380415 | 2.80 | 2.80 | 0.00703555 | 20445.6 | 6.59 | 6.59 | 0.00703555 | 24305.8 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 258741.722 | -999.000 | 9.507096 | 0.01100747 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6809 | 1004.8586 | 1.2027 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.507096 | 11.43455441 | 4197.9300 | 999.8980 | 138.53280528 | 12.27 | 6.67 | 5.60 | 3256685.71 | 7.9449 | 7.944940 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 258741.72 | 177742.94 | 1.0000 | 11.43455441 | 9.507096 | 26.44 | 19.39 | 0.01121112 | 55162.4 | 11.05 | 11.05 | 0.00850000 | 32534.3 | 11.00634813 | 6.67 | 12.27 | 5.60 | 20544.328 | 238197.39 | 33.13 | 0.01716709 | 25.31 | 2.53819000 | 26.6978 | 24.00 | 0.00903195 | 24.00 | 0.00903195 | 48.5274 | 130249.97 | 0.00 | 259187.25 | 173638.07 | 11.43455441 | 26.44 | 19.41 | 0.01121112 | 55162.4 | 11.64 | 11.36 | 0.00824525 | 32495.4 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 9466.037 | 9466.037 | 2.852129 | 0.00008281 | 170.191 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.507096 | 11.43455441 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 0.7070 | 0.721263 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9466.04 | 9466.04 | 1.0000 | 3.43036632 | 2.852129 | 10.05 | 9.43 | 0.00709538 | 27980.3 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.08280457 | 60.00 | 32.22 | 27.78 | 0.000 | 9466.04 | 8.70 | 0.00699286 | 8.70 | 2.53819000 | 88.9928 | 21.00 | 0.00792429 | 21.00 | 0.00792429 | 51.1740 | 59261.71 | 0.00 | 10456.00 | 10456.00 | 3.43036632 | 2.80 | 2.80 | 0.00709538 | 20595.6 | 5.79 | 5.79 | 0.00709538 | 23643.7 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 134482.168 | -999.000 | 5.825413 | 0.00572118 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5943 | 1004.8586 | 1.2027 | CAV_BAS FAN | Fan:ConstantVolume | 5.825413 | 7.00645125 | 4197.9300 | 999.8980 | 138.53280528 | 12.27 | 6.67 | 5.60 | 3256685.71 | 4.1294 | 4.129418 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 134482.17 | 96209.80 | 1.0000 | 7.00645125 | 5.825413 | 24.92 | 18.45 | 0.01062659 | 52111.9 | 11.42 | 11.42 | 0.00850000 | 32917.8 | 5.72059869 | 6.67 | 12.27 | 5.60 | 9877.887 | 124604.28 | 28.24 | 0.01715778 | 24.03 | 1.20015641 | 20.6021 | 24.06 | 0.00893188 | 24.00 | 0.00893188 | 47.9950 | 80805.15 | 0.00 | 134675.27 | 93653.64 | 7.00645125 | 24.92 | 18.46 | 0.01062659 | 52111.9 | 11.88 | 11.52 | 0.00830602 | 32890.2 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 269000.463 | 269000.463 | 5.825413 | 0.00235333 | 6149.605 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | CAV_BAS FAN | Fan:ConstantVolume | 5.825413 | 7.00645125 | 4197.9300 | 999.8980 | 11.48048889 | 54.44 | 82.22 | 27.78 | 1338837.34 | 20.0921 | 20.496456 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 269000.46 | 269000.46 | 1.0000 | 7.00645125 | 5.825413 | 1.79 | 1.79 | 0.00699286 | 19313.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 2.35309333 | 60.00 | 32.22 | 27.78 | 0.000 | 269000.46 | 8.70 | 0.00699286 | 8.70 | 1.20015641 | 20.6021 | 0.00 | 0.00699286 | 26.09 | 0.00699286 | 33.2718 | 0.00 | 0.00 | 233017.26 | 233017.26 | 7.00645125 | 12.80 | 10.55 | 0.00699286 | 30517.1 | 45.47 | 22.06 | 0.00699286 | 63774.6 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 435606.478 | 312997.163 | 21.385338 | 0.01066797 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.9735 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 408139.50 | 397622.24 | 0.9369 | -999.0 | -999.0 | 28.50 | 18.07 | 0.00867883 | 50800.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 408139.50 | 33.20 | 0.01716721 | 25.32 | 0.33839277 | -999.0000 | 27.00 | 0.00854217 | 27.00 | 0.00854217 | 38.4364 | 372219.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9663.385 | 6927.594 | 0.472866 | 0.00023666 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3366 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | Sensible | 9058.31 | 8571.98 | 0.9374 | -999.0 | -999.0 | 28.08 | 18.09 | 0.00887414 | 50869.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9058.31 | 30.92 | 0.01716288 | 24.74 | 0.01563234 | -999.0000 | 27.00 | 0.00858849 | 27.00 | 0.00858849 | 38.6397 | 8178.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 92090.345 | 65920.340 | 4.493547 | 0.00225529 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3723 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | Sensible | 86365.59 | 81505.68 | 0.9378 | -999.0 | -999.0 | 28.08 | 18.11 | 0.00889336 | 50925.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86365.59 | 30.92 | 0.01716288 | 24.74 | 0.15632344 | -999.0000 | 27.00 | 0.00859306 | 27.00 | 0.00859306 | 38.6603 | 77754.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9341.615 | 6690.350 | 0.456270 | 0.00022878 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3564 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8759.48 | 8276.78 | 0.9377 | -999.0 | -999.0 | 28.09 | 18.10 | 0.00888480 | 50906.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8759.48 | 31.09 | 0.01716319 | 24.78 | 0.01563234 | -999.0000 | 27.00 | 0.00859100 | 27.00 | 0.00859100 | 38.6510 | 7949.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 435606.478 | 435606.478 | 21.385338 | 0.01066797 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 435606.48 | 435606.48 | 1.0000 | 25.72097919 | 21.385338 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 435606.48 | 8.70 | 0.00699286 | 8.70 | 0.33839277 | 1.5824 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9663.385 | 9663.385 | 0.472866 | 0.00023666 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9663.38 | 9663.38 | 1.0000 | 0.56873411 | 0.472866 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9663.38 | 8.70 | 0.00699286 | 8.70 | 0.01563234 | 3.3059 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92090.345 | 92090.345 | 4.493547 | 0.00225529 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 92090.34 | 92090.34 | 1.0000 | 5.40456368 | 4.493547 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92090.34 | 8.70 | 0.00699286 | 8.70 | 0.15632344 | 3.4788 | 0.00 | 0.00847983 | 25.25 | 0.00847983 | 42.3116 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9341.615 | 9341.615 | 0.456270 | 0.00022878 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9341.61 | 9341.61 | 1.0000 | 0.54877391 | 0.456270 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9341.61 | 8.70 | 0.00699286 | 8.70 | 0.01563234 | 3.4261 | 0.00 | 0.00722418 | 24.35 | 0.00722418 | 38.1038 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12800.936 | 12800.936 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.385338 | 25.72097919 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 12800.94 | 12800.94 | 1.0000 | 25.72097919 | 21.385338 | 0.14 | 0.14 | 0.00847615 | 21338.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12800.94 | 8.70 | 0.00699286 | 8.70 | 0.33839277 | 1.5824 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 591.350 | 591.350 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.472866 | 0.56873411 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 591.35 | 591.35 | 1.0000 | 0.56873411 | 0.472866 | 0.29 | 0.29 | 0.00845018 | 21426.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 591.35 | 8.70 | 0.00699286 | 8.70 | 0.01563234 | 3.3059 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5913.502 | 5913.502 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.493547 | 5.40456368 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 5913.50 | 5913.50 | 1.0000 | 5.40456368 | 4.493547 | 0.30 | 0.30 | 0.00842810 | 21387.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5913.50 | 8.70 | 0.00699286 | 8.70 | 0.15632344 | 3.4788 | 0.00 | 0.00847983 | 25.25 | 0.00847983 | 42.3116 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 591.350 | 591.350 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.456270 | 0.54877391 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 591.35 | 591.35 | 1.0000 | 0.54877391 | 0.456270 | 0.30 | 0.30 | 0.00721625 | 18350.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 591.35 | 8.70 | 0.00699286 | 8.70 | 0.01563234 | 3.4261 | 0.00 | 0.00722418 | 24.35 | 0.00722418 | 38.1038 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5715.00 | 2264.83 | 2264.83 |
CORE_BOTTOM | 5682.67 | 5.50 | 0.83 |
CORE_MID | 5459.33 | 68.17 | 0.00 |
CORE_TOP | 5263.67 | 299.00 | 0.83 |
PERIMETER_BOT_ZN_3 | 5357.83 | 351.83 | 85.00 |
PERIMETER_BOT_ZN_2 | 5174.67 | 480.67 | 145.00 |
PERIMETER_BOT_ZN_1 | 5631.83 | 414.00 | 309.00 |
PERIMETER_BOT_ZN_4 | 5678.83 | 579.33 | 486.33 |
PERIMETER_MID_ZN_3 | 4910.83 | 1192.67 | 504.67 |
PERIMETER_MID_ZN_2 | 4073.83 | 1075.33 | 502.67 |
PERIMETER_MID_ZN_1 | 5492.00 | 834.83 | 631.50 |
PERIMETER_MID_ZN_4 | 5017.33 | 1075.67 | 479.17 |
PERIMETER_TOP_ZN_3 | 4688.67 | 1570.67 | 604.00 |
PERIMETER_TOP_ZN_2 | 4763.33 | 1390.33 | 603.83 |
PERIMETER_TOP_ZN_1 | 5302.67 | 1070.50 | 701.17 |
PERIMETER_TOP_ZN_4 | 4765.50 | 1374.83 | 555.33 |
DATACENTER_BOT_ZN_6 | 5943.00 | 2559.83 | 2559.83 |
DATACENTER_MID_ZN_6 | 5943.00 | 253.50 | 253.50 |
DATACENTER_TOP_ZN_6 | 5939.83 | 867.00 | 867.00 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 95.67 | 0.00 | 6.50 |
CORE_BOTTOM | 0.00 | 5.67 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.17 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 4.67 | 0.00 | 0.50 |
PERIMETER_BOT_ZN_2 | 0.00 | 14.17 | 0.00 | 14.17 |
PERIMETER_BOT_ZN_1 | 0.00 | 87.33 | 0.00 | 78.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 171.83 | 0.00 | 56.67 |
PERIMETER_MID_ZN_3 | 0.00 | 1.83 | 0.00 | 0.67 |
PERIMETER_MID_ZN_2 | 0.00 | 21.17 | 0.00 | 21.17 |
PERIMETER_MID_ZN_1 | 0.00 | 123.33 | 0.00 | 117.83 |
PERIMETER_MID_ZN_4 | 0.00 | 25.33 | 0.00 | 18.83 |
PERIMETER_TOP_ZN_3 | 0.17 | 17.33 | 0.00 | 12.67 |
PERIMETER_TOP_ZN_2 | 0.17 | 42.17 | 0.00 | 39.33 |
PERIMETER_TOP_ZN_1 | 0.00 | 66.50 | 0.00 | 58.83 |
PERIMETER_TOP_ZN_4 | 0.00 | 38.00 | 0.00 | 26.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 19.17 | 0.00 | 19.17 |
DATACENTER_MID_ZN_6 | 0.00 | 14.00 | 0.00 | 14.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 7.50 | 0.00 | 7.50 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 894.00 | 0.00 | 687.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.17 | 1303.50 | 0.00 | 918.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.526 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.739 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.700 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.693 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.900 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.116 | 0.047 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.100 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 1.624 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.876 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.185 | 0.115 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.126 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.304 | 0.109 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.900 | 0.131 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.241 | 0.136 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 1.135 | 0.131 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 1.331 | 0.136 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.584 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.584 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.584 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.658 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.572 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.572 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.572 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.644 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 24055971.17 | 0.00 | 24055971.17 | 0.00 | 24055971.17 | 37848132.68 | 3192.21 | 5567.79 | 0.00 | 791.33 |
CORE_BOTTOM | 36882474.35 | 0.00 | 36882474.35 | 0.00 | 36882474.35 | 33990283.35 | 2141.11 | 1.29 | 6617.60 | 1350.39 |
CORE_MID | 0.31E+09 | 0.00 | 0.31E+09 | 0.00 | 0.31E+09 | 0.34E+09 | 3179.90 | 2.80 | 5577.30 | 554.77 |
CORE_TOP | 30572622.07 | 0.00 | 30572622.07 | 0.00 | 30572622.07 | 33990283.35 | 3183.03 | 0.46 | 5576.51 | 551.15 |
PERIMETER_BOT_ZN_3 | 5643270.01 | 0.00 | 5643270.01 | 419809.91 | 6063079.92 | 4267819.30 | 2205.74 | 10.00 | 6544.26 | 1350.39 |
PERIMETER_BOT_ZN_2 | 4671884.89 | 0.00 | 4671884.89 | 279873.08 | 4951757.97 | 2750345.05 | 2147.50 | 1.07 | 6611.43 | 1350.39 |
PERIMETER_BOT_ZN_1 | 6633228.16 | 0.00 | 6633228.16 | 419809.91 | 7053038.08 | 4267912.63 | 2157.10 | 2.24 | 6600.66 | 1350.39 |
PERIMETER_BOT_ZN_4 | 6669430.72 | 0.00 | 6669430.72 | 279873.08 | 6949303.81 | 2750345.05 | 2138.89 | 0.00 | 6621.11 | 1350.39 |
PERIMETER_MID_ZN_3 | 48359814.41 | 0.00 | 48359814.41 | 984550.17 | 49344364.58 | 42678193.03 | 3274.66 | 19.12 | 5466.21 | 554.77 |
PERIMETER_MID_ZN_2 | 44025773.77 | 0.00 | 44025773.77 | 656366.33 | 44682140.10 | 27503450.52 | 3177.46 | 0.12 | 5582.42 | 1463.77 |
PERIMETER_MID_ZN_1 | 60799337.82 | 0.00 | 60799337.82 | 984550.17 | 61783887.99 | 42679126.28 | 3189.36 | 1.11 | 5569.52 | 554.77 |
PERIMETER_MID_ZN_4 | 47086551.86 | 0.00 | 47086551.86 | 656366.33 | 47742918.19 | 27503450.52 | 3177.46 | 0.00 | 5582.54 | 554.77 |
PERIMETER_TOP_ZN_3 | 4988124.54 | 0.00 | 4988124.54 | 1222397.02 | 6210521.57 | 4267819.30 | 3195.78 | 7.30 | 5556.92 | 551.15 |
PERIMETER_TOP_ZN_2 | 4452375.23 | 0.00 | 4452375.23 | 814930.79 | 5267306.02 | 2750345.05 | 3178.44 | 0.04 | 5581.51 | 551.15 |
PERIMETER_TOP_ZN_1 | 6167976.65 | 0.00 | 6167976.65 | 1222397.02 | 7390373.67 | 4267912.63 | 3183.40 | 0.28 | 5576.32 | 551.15 |
PERIMETER_TOP_ZN_4 | 4820272.93 | 0.00 | 4820272.93 | 814930.79 | 5635203.72 | 2750345.05 | 3178.44 | 0.00 | 5581.56 | 551.15 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.53E+10 | 0.00 | 0.53E+10 | 38292351.59 | 0.53E+10 | 0.50E+10 | 4011.66 | 8760.00 | 6942.27 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9646 | 0.0000 | 0.9646 | 0.0000 | 0.9646 | 1.2002 | 1166.55 | 4776.45 | 0.00 |
CORE_BOTTOM | 1.3727 | 0.0000 | 1.3727 | 0.0000 | 1.3727 | 1.0778 | 674.29 | 1.14 | 5267.57 |
CORE_MID | 13.0021 | 0.0000 | 13.0021 | 0.0000 | 13.0021 | 10.7782 | 917.30 | 2.60 | 5023.10 |
CORE_TOP | 1.2869 | 0.0000 | 1.2869 | 0.0000 | 1.2869 | 1.0778 | 915.98 | 0.21 | 5026.81 |
PERIMETER_BOT_ZN_3 | 0.2099 | 0.0000 | 0.2099 | 0.0105 | 0.2204 | 0.1353 | 731.23 | 9.57 | 5202.20 |
PERIMETER_BOT_ZN_2 | 0.1679 | 0.0000 | 0.1679 | 0.0070 | 0.1749 | 0.0872 | 678.60 | 0.76 | 5263.64 |
PERIMETER_BOT_ZN_1 | 0.2565 | 0.0000 | 0.2565 | 0.0105 | 0.2670 | 0.1353 | 684.40 | 1.80 | 5256.81 |
PERIMETER_BOT_ZN_4 | 0.2441 | 0.0000 | 0.2441 | 0.0070 | 0.2511 | 0.0872 | 672.28 | 0.00 | 5270.72 |
PERIMETER_MID_ZN_3 | 2.0439 | 0.0000 | 2.0439 | 0.0246 | 2.0685 | 1.3533 | 1000.76 | 18.72 | 4923.52 |
PERIMETER_MID_ZN_2 | 1.7820 | 0.0000 | 1.7820 | 0.0173 | 1.7993 | 0.8721 | 915.23 | 0.12 | 4118.65 |
PERIMETER_MID_ZN_1 | 2.6257 | 0.0000 | 2.6257 | 0.0246 | 2.6503 | 1.3533 | 919.96 | 0.92 | 5022.12 |
PERIMETER_MID_ZN_4 | 1.9617 | 0.0000 | 1.9617 | 0.0164 | 1.9781 | 0.8721 | 915.23 | 0.00 | 5027.77 |
PERIMETER_TOP_ZN_3 | 0.2099 | 0.0000 | 0.2099 | 0.0306 | 0.2405 | 0.1353 | 924.56 | 6.99 | 5011.45 |
PERIMETER_TOP_ZN_2 | 0.1867 | 0.0000 | 0.1867 | 0.0204 | 0.2071 | 0.0872 | 912.60 | 0.04 | 5030.36 |
PERIMETER_TOP_ZN_1 | 0.2646 | 0.0000 | 0.2646 | 0.0306 | 0.2952 | 0.1353 | 915.29 | 0.12 | 5027.58 |
PERIMETER_TOP_ZN_4 | 0.2003 | 0.0000 | 0.2003 | 0.0204 | 0.2207 | 0.0872 | 912.60 | 0.00 | 5030.40 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 221.4498 | 0.0000 | 221.4498 | 0.9663 | 222.4161 | 158.4706 | 1399.76 | 5943.00 | 5397.29 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 87518571.37 | 0.00 | 87518571.37 | 48026705.38 | 2138.89 | 0.00 | 6621.11 | 1350.39 |
VAV_MID WITH REHEAT | 0.74E+09 | 0.00 | 0.74E+09 | 0.48E+09 | 3177.46 | 0.00 | 5582.54 | 554.77 |
VAV_TOP WITH REHEAT | 73777611.43 | 0.00 | 73777611.43 | 48026705.38 | 3178.44 | 0.00 | 5581.56 | 551.15 |
CAV_BAS | 34798909.52 | 0.00 | 34798909.52 | 37848132.68 | 3192.21 | 0.00 | 5567.79 | 791.33 |
AIRLOOP DATACENTER BASEMENT | 15437267.12 | 0.00 | 15437267.12 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 713137.79 | 0.00 | 713137.79 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7131377.88 | 0.00 | 7131377.88 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 713137.79 | 0.00 | 713137.79 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.2563 | 0.0000 | 3.2563 | 1.5229 | 672.28 | 0.00 | 5270.72 |
VAV_MID WITH REHEAT | 31.0626 | 0.0000 | 31.0626 | 15.2292 | 915.23 | 0.00 | 5027.77 |
VAV_TOP WITH REHEAT | 3.1079 | 0.0000 | 3.1079 | 1.5229 | 912.60 | 0.00 | 5030.40 |
CAV_BAS | 1.3953 | 0.0000 | 1.3953 | 1.2002 | 1166.55 | 0.00 | 4776.45 |
AIRLOOP DATACENTER BASEMENT | 0.4895 | 0.0000 | 0.4895 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2261 | 0.0000 | 0.2261 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 6621.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 5582.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 5581.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5567.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 3.6722 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 36.7227 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 3.6720 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7363 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4895 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2261 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1386 |
Defaulted Fields | 1179 |
Fields with Defaults | 3922 |
Autosized Fields | 336 |
Autosizable Fields | 412 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 34119.37 | 399993.02 | 22-JAN-10:10 | 2057502.42 | 21-AUG-16:00 |
Electricity:Building | 18916.75 | 251811.03 | 01-JAN-09:20 | 1142199.99 | 15-DEC-17:00 |
Electricity:Zone:BASEMENT | 664.85 | 14623.97 | 01-JAN-00:10 | 34452.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18916.75 | 251811.03 | 01-JAN-09:20 | 1142199.99 | 15-DEC-17:00 |
InteriorLights:Electricity | 3703.34 | 17601.77 | 01-JAN-09:20 | 352853.36 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3703.34 | 17601.77 | 01-JAN-09:20 | 352853.36 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity | 3703.34 | 17601.77 | 01-JAN-09:20 | 352853.36 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3703.34 | 17601.77 | 01-JAN-09:20 | 352853.36 | 27-SEP-07:10 |
Electricity:Zone:CORE_BOTTOM | 537.23 | 7090.40 | 01-JAN-00:10 | 36983.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5372.24 | 70903.72 | 01-JAN-00:10 | 369831.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 537.22 | 7090.37 | 01-JAN-00:10 | 36983.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 58.93 | 839.57 | 01-JAN-09:10 | 4643.71 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.59 | 80.80 | 01-JAN-09:10 | 2367.39 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.59 | 80.80 | 01-JAN-09:10 | 2367.39 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 37.97 | 541.05 | 01-JAN-07:50 | 2992.58 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.97 | 52.07 | 01-JAN-07:50 | 1525.64 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.97 | 52.07 | 01-JAN-07:50 | 1525.64 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 58.81 | 839.58 | 01-JAN-07:40 | 4643.79 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.47 | 80.80 | 01-JAN-07:40 | 2367.44 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.47 | 80.80 | 01-JAN-07:40 | 2367.44 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 37.96 | 541.05 | 01-JAN-09:20 | 2992.57 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.96 | 52.07 | 01-JAN-09:20 | 1525.64 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.96 | 52.07 | 01-JAN-09:20 | 1525.64 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 589.49 | 8395.70 | 01-JAN-09:20 | 46437.07 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 186.07 | 807.98 | 01-JAN-09:20 | 23673.89 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 186.07 | 807.98 | 01-JAN-09:20 | 23673.89 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 379.72 | 5410.51 | 01-JAN-07:50 | 29925.82 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 119.74 | 520.69 | 01-JAN-07:50 | 15256.36 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 119.74 | 520.69 | 01-JAN-07:50 | 15256.36 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 588.23 | 8395.84 | 01-JAN-07:40 | 46437.94 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 184.80 | 807.99 | 01-JAN-07:40 | 23674.41 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 184.80 | 807.99 | 01-JAN-07:40 | 23674.41 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 379.60 | 5410.48 | 01-JAN-09:20 | 29925.72 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 119.62 | 520.69 | 01-JAN-09:20 | 15256.36 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 119.62 | 520.69 | 01-JAN-09:20 | 15256.36 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 58.95 | 839.57 | 01-JAN-09:20 | 4643.71 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.61 | 80.80 | 01-JAN-09:20 | 2367.39 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.61 | 80.80 | 01-JAN-09:20 | 2367.39 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 37.97 | 541.05 | 01-JAN-07:50 | 2992.58 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.97 | 52.07 | 01-JAN-07:50 | 1525.64 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.97 | 52.07 | 01-JAN-07:50 | 1525.64 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 58.82 | 839.58 | 01-JAN-07:40 | 4643.79 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.48 | 80.80 | 01-JAN-07:40 | 2367.44 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.48 | 80.80 | 01-JAN-07:40 | 2367.44 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 37.96 | 541.05 | 01-JAN-09:20 | 2992.57 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.96 | 52.07 | 01-JAN-09:20 | 1525.64 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.96 | 52.07 | 01-JAN-09:20 | 1525.64 | 27-SEP-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7562.65 | 95237.01 | 01-JAN-00:10 | 385552.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1598.46 | 19775.43 | 01-JAN-00:10 | 83152.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 6577.00 | 9650.01 | 25-JAN-05:30 | 528219.03 | 02-OCT-05:10 |
HeatRejection:Electricity | 2170.92 | 6181.48 | 25-JAN-07:00 | 97050.41 | 27-MAY-03:10 |
General:HeatRejection:Electricity | 2170.92 | 6181.48 | 25-JAN-07:00 | 97050.41 | 27-MAY-03:10 |
Electricity:HVAC | 6099.59 | 76598.78 | 22-JAN-05:00 | 401743.74 | 16-AUG-15:40 |
ExteriorEquipment:Electricity | 1941.93 | 28795.69 | 01-JAN-00:10 | 118959.22 | 27-SEP-07:20 |
Transformer:ExteriorEquipment:Electricity | 87.32 | 1613.62 | 01-JAN-00:10 | 5481.25 | 27-SEP-07:20 |
ElectricityPurchased:Facility | 34119.37 | 399993.02 | 22-JAN-10:10 | 2057502.42 | 21-AUG-16:00 |
ElectricityPurchased:Plant | 34119.37 | 399993.02 | 22-JAN-10:10 | 2057502.42 | 21-AUG-16:00 |
Cogeneration:ElectricityPurchased | 34119.37 | 399993.02 | 22-JAN-10:10 | 2057502.42 | 21-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 34119.37 | 399993.02 | 22-JAN-10:10 | 2057502.42 | 21-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 34119.37 | 399993.02 | 22-JAN-10:10 | 2057502.42 | 21-AUG-16:00 |
ElectricityNet:Plant | 34119.37 | 399993.02 | 22-JAN-10:10 | 2057502.42 | 21-AUG-16:00 |
Cogeneration:ElectricityNet | 34119.37 | 399993.02 | 22-JAN-10:10 | 2057502.42 | 21-AUG-16:00 |
General:Cogeneration:ElectricityNet | 34119.37 | 399993.02 | 22-JAN-10:10 | 2057502.42 | 21-AUG-16:00 |
Fans:Electricity | 2684.96 | 41530.31 | 01-JAN-00:10 | 222608.04 | 24-JUL-15:40 |
General:Fans:Electricity | 2684.96 | 41530.31 | 01-JAN-00:10 | 222608.04 | 24-JUL-15:40 |
ExteriorLights:Electricity | 671.42 | 0.00 | 01-JAN-07:20 | 54335.80 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 671.42 | 0.00 | 01-JAN-07:20 | 54335.80 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 119.80 | 0.00 | 01-JAN-00:10 | 5613.48 | 01-JAN-09:10 |
General:HeatRecovery:Electricity | 119.80 | 0.00 | 01-JAN-00:10 | 5613.48 | 01-JAN-09:10 |
Cooling:Electricity | 6198.02 | 33450.35 | 22-JAN-05:00 | 476372.27 | 21-AUG-16:00 |
General:Cooling:Electricity | 6198.02 | 33450.35 | 22-JAN-05:00 | 476372.27 | 21-AUG-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1.15 | 0.00 | 01-JAN-00:10 | 4076.76 | 04-FEB-06:00 |
General:Humidifier:Electricity | 1.15 | 0.00 | 01-JAN-00:10 | 4076.76 | 04-FEB-06:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 1414.42 | 3414.79 | 01-JAN-00:10 | 81035.57 | 02-OCT-05:10 |
General:Pumps:Electricity | 1414.42 | 3414.79 | 01-JAN-00:10 | 81035.57 | 02-OCT-05:10 |
WIRED_LTG_ELECTRICITY | 104.06 | 0.00 | 01-JAN-00:10 | 9915.18 | 27-SEP-07:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 568.23 | 5695.87 | 01-JAN-00:10 | 238588.00 | 04-FEB-06:10 |
NaturalGas:Plant | 568.23 | 5695.87 | 01-JAN-00:10 | 238588.00 | 04-FEB-06:10 |
Heating:NaturalGas | 4.23 | 0.00 | 01-JAN-00:10 | 212165.94 | 04-FEB-06:10 |
Boiler:Heating:NaturalGas | 4.23 | 0.00 | 01-JAN-00:10 | 212165.94 | 04-FEB-06:10 |
WaterSystems:NaturalGas | 564.00 | 5695.87 | 01-JAN-00:10 | 68200.91 | 18-JAN-12:30 |
Water Heater:WaterSystems:NaturalGas | 564.00 | 5695.87 | 01-JAN-00:10 | 68200.91 | 18-JAN-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 34942.60 | 165213.06 | 25-JAN-06:00 | 2599182.31 | 21-AUG-16:00 |
PlantLoopCoolingDemand:HVAC | 34942.60 | 165213.06 | 25-JAN-06:00 | 2599182.31 | 21-AUG-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 34942.60 | 165213.06 | 25-JAN-06:00 | 2599182.31 | 21-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 17901.82 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:10 |
Water:HVAC | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
Humidifier:Water | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
General:Humidifier:Water | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
MainsWater:Facility | 17901.82 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:10 |
MainsWater:HVAC | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
Humidifier:MainsWater | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
General:Humidifier:MainsWater | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
Water:Plant | 17901.39 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 17901.39 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 15621.22 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:00 |
General:HeatRejection:Water | 15621.22 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:00 |
HeatRejection:MainsWater | 15621.22 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:00 |
General:HeatRejection:MainsWater | 15621.22 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 125185.70 | 234908.61 | 22-JAN-06:00 | 11375026.51 | 02-OCT-05:10 |
EnergyTransfer:Building | 23312.05 | 100953.59 | 14-JAN-18:20 | 1612052.05 | 31-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 799.38 | 0.00 | 01-JAN-00:10 | 71905.10 | 05-SEP-05:10 |
Heating:EnergyTransfer | 12.93 | 0.00 | 01-JAN-00:10 | 71960.77 | 04-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.46 | 0.00 | 01-JAN-00:10 | 22568.32 | 29-JUL-16:10 |
General:Heating:EnergyTransfer | 12.93 | 0.00 | 01-JAN-00:10 | 71960.77 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.46 | 0.00 | 01-JAN-00:10 | 22568.32 | 29-JUL-16:10 |
Cooling:EnergyTransfer | 23299.11 | 100953.59 | 14-JAN-18:20 | 1612052.05 | 31-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 794.92 | 0.00 | 01-JAN-00:10 | 71905.10 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 23299.11 | 100953.59 | 14-JAN-18:20 | 1612052.05 | 31-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 794.92 | 0.00 | 01-JAN-00:10 | 71905.10 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 809.01 | 0.00 | 01-JAN-00:10 | 57120.39 | 21-AUG-10:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 809.01 | 0.00 | 01-JAN-00:10 | 57120.39 | 21-AUG-10:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 809.01 | 0.00 | 01-JAN-00:10 | 57120.39 | 21-AUG-10:00 |
EnergyTransfer:Zone:CORE_MID | 6152.93 | 0.00 | 01-JAN-00:10 | 477214.41 | 05-SEP-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 6152.93 | 0.00 | 01-JAN-00:10 | 477214.41 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 6152.93 | 0.00 | 01-JAN-00:10 | 477214.41 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_TOP | 634.76 | 0.00 | 01-JAN-00:10 | 53835.20 | 24-JUL-15:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 634.76 | 0.00 | 01-JAN-00:10 | 53835.20 | 24-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 634.76 | 0.00 | 01-JAN-00:10 | 53835.20 | 24-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 124.09 | 0.00 | 01-JAN-00:10 | 10907.01 | 21-AUG-12:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 124.09 | 0.00 | 01-JAN-00:10 | 10907.01 | 21-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 124.09 | 0.00 | 01-JAN-00:10 | 10907.01 | 21-AUG-12:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 98.37 | 0.00 | 01-JAN-00:10 | 10151.89 | 25-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 98.37 | 0.00 | 01-JAN-00:10 | 10151.89 | 25-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 98.37 | 0.00 | 01-JAN-00:10 | 10151.89 | 25-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 151.71 | 0.00 | 01-JAN-00:10 | 14891.68 | 04-DEC-14:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 151.71 | 0.00 | 01-JAN-00:10 | 14891.68 | 04-DEC-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 151.71 | 0.00 | 01-JAN-00:10 | 14891.68 | 04-DEC-14:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 144.72 | 0.00 | 01-JAN-00:10 | 14404.04 | 17-AUG-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 144.72 | 0.00 | 01-JAN-00:10 | 14404.04 | 17-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 144.72 | 0.00 | 01-JAN-00:10 | 14404.04 | 17-AUG-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 962.13 | 0.00 | 01-JAN-00:10 | 99850.84 | 01-JUN-14:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.02 | 0.00 | 01-JAN-00:10 | 21212.63 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.02 | 0.00 | 01-JAN-00:10 | 21212.63 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 962.12 | 0.00 | 01-JAN-00:10 | 99850.84 | 01-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 962.12 | 0.00 | 01-JAN-00:10 | 99850.84 | 01-JUN-14:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 853.48 | 0.00 | 01-JAN-00:10 | 102714.39 | 25-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 13335.51 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 13335.51 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 853.47 | 0.00 | 01-JAN-00:10 | 102714.39 | 25-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 853.47 | 0.00 | 01-JAN-00:10 | 102714.39 | 25-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1262.83 | 0.00 | 01-JAN-00:10 | 142484.96 | 04-DEC-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1262.83 | 0.00 | 01-JAN-00:10 | 142484.96 | 04-DEC-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1262.83 | 0.00 | 01-JAN-00:10 | 142484.96 | 04-DEC-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 904.67 | 0.00 | 01-JAN-00:10 | 114451.33 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 3347.97 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 3347.97 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 904.67 | 0.00 | 01-JAN-00:10 | 114451.33 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 904.67 | 0.00 | 01-JAN-00:10 | 114451.33 | 17-MAY-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 102.39 | 0.00 | 01-JAN-00:10 | 11163.37 | 01-JUN-14:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.10 | 0.00 | 01-JAN-00:10 | 6064.11 | 04-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.10 | 0.00 | 01-JAN-00:10 | 6064.11 | 04-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 102.29 | 0.00 | 01-JAN-00:10 | 11163.37 | 01-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 102.29 | 0.00 | 01-JAN-00:10 | 11163.37 | 01-JUN-14:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 90.16 | 0.00 | 01-JAN-00:10 | 10897.19 | 25-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.04 | 0.00 | 01-JAN-00:10 | 4037.78 | 04-FEB-05:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.04 | 0.00 | 01-JAN-00:10 | 4037.78 | 04-FEB-05:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 90.12 | 0.00 | 01-JAN-00:10 | 10897.19 | 25-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 90.12 | 0.00 | 01-JAN-00:10 | 10897.19 | 25-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 132.38 | 0.00 | 01-JAN-00:10 | 15831.02 | 04-DEC-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 3734.18 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 3734.18 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 132.36 | 0.00 | 01-JAN-00:10 | 15831.02 | 04-DEC-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 132.36 | 0.00 | 01-JAN-00:10 | 15831.02 | 04-DEC-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 95.35 | 0.00 | 01-JAN-00:10 | 12293.18 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 2845.02 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 2845.02 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 95.32 | 0.00 | 01-JAN-00:10 | 12293.18 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 95.32 | 0.00 | 01-JAN-00:10 | 12293.18 | 17-MAY-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 116.19 | 0.00 | 01-JAN-00:10 | 11277.42 | 21-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.99 | 0.00 | 01-JAN-00:10 | 3054.76 | 05-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.99 | 0.00 | 01-JAN-00:10 | 3054.76 | 05-FEB-11:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 115.21 | 0.00 | 01-JAN-00:10 | 11277.42 | 21-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 115.21 | 0.00 | 01-JAN-00:10 | 11277.42 | 21-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 898.34 | 0.00 | 01-JAN-00:10 | 83757.89 | 31-JUL-15:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.00 | 0.00 | 01-JAN-00:10 | 20595.95 | 15-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.00 | 0.00 | 01-JAN-00:10 | 20595.95 | 15-DEC-05:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 893.33 | 0.00 | 01-JAN-00:10 | 83757.89 | 31-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 893.33 | 0.00 | 01-JAN-00:10 | 83757.89 | 31-JUL-15:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 145.67 | 0.00 | 01-JAN-00:10 | 23258.43 | 28-JUL-15:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.27 | 0.00 | 01-JAN-00:10 | 7796.11 | 04-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.27 | 0.00 | 01-JAN-00:10 | 7796.11 | 04-FEB-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 143.40 | 0.00 | 01-JAN-00:10 | 23258.43 | 28-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 143.40 | 0.00 | 01-JAN-00:10 | 23258.43 | 28-JUL-15:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.19 | 1279.86 | 14-JAN-18:20 | 7915.98 | 06-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.19 | 1279.86 | 14-JAN-18:20 | 7915.98 | 06-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.19 | 1279.86 | 14-JAN-18:20 | 7915.98 | 06-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1353.87 | 8832.36 | 25-JAN-08:00 | 75026.20 | 06-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1353.87 | 8832.36 | 25-JAN-08:00 | 75026.20 | 06-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1353.87 | 8832.36 | 25-JAN-08:00 | 75026.20 | 06-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 134.45 | 269.65 | 25-JAN-07:00 | 7688.37 | 09-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 134.45 | 269.65 | 25-JAN-07:00 | 7688.37 | 09-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 134.45 | 269.65 | 25-JAN-07:00 | 7688.37 | 09-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7200.95 | 88979.51 | 27-MAY-19:20 | 370281.94 | 28-AUG-12:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7200.95 | 88979.51 | 27-MAY-19:20 | 370281.94 | 28-AUG-12:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7200.95 | 88979.51 | 27-MAY-19:20 | 370281.94 | 28-AUG-12:20 |
PlantLoopHeatingDemand:Facility | 299.68 | 0.00 | 01-JAN-00:10 | 146144.08 | 04-FEB-06:10 |
PlantLoopHeatingDemand:Plant | 296.73 | 0.00 | 01-JAN-00:10 | 36112.65 | 18-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 296.73 | 0.00 | 01-JAN-00:10 | 36112.65 | 18-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 296.73 | 0.00 | 01-JAN-00:10 | 36112.65 | 18-JAN-12:10 |
EnergyTransfer:HVAC | 36713.13 | 132686.43 | 25-JAN-04:50 | 3135100.37 | 21-AUG-16:00 |
HeatingCoils:EnergyTransfer | 2.95 | 0.00 | 01-JAN-00:10 | 141753.61 | 04-FEB-06:10 |
PlantLoopHeatingDemand:HVAC | 2.95 | 0.00 | 01-JAN-00:10 | 141753.61 | 04-FEB-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 2.95 | 0.00 | 01-JAN-00:10 | 141753.61 | 04-FEB-06:10 |
CoolingCoils:EnergyTransfer | 31736.24 | 131665.68 | 25-JAN-06:00 | 2455999.31 | 19-JUN-05:10 |
HeatRecoveryForHeating:EnergyTransfer | 29.42 | 0.00 | 01-JAN-00:10 | 340749.26 | 04-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 4944.52 | 0.00 | 01-JAN-00:10 | 716966.85 | 21-AUG-16:00 |
EnergyTransfer:Plant | 65160.52 | 0.00 | 01-JAN-00:10 | 7402082.55 | 31-MAY-05:10 |
LoopToLoop:EnergyTransfer | 22616.83 | 0.00 | 01-JAN-00:10 | 2329594.11 | 31-MAY-05:10 |
WaterSystems:EnergyTransfer | 296.73 | 0.00 | 01-JAN-00:10 | 36112.65 | 18-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 296.73 | 0.00 | 01-JAN-00:10 | 36112.65 | 18-JAN-12:10 |
Boilers:EnergyTransfer | 2.80 | 0.00 | 01-JAN-00:10 | 167016.64 | 04-FEB-06:10 |
Chillers:EnergyTransfer | 19626.25 | 0.00 | 01-JAN-00:10 | 2362182.33 | 31-MAY-05:10 |
HeatRejection:EnergyTransfer | 22617.90 | 0.00 | 01-JAN-00:10 | 2706603.28 | 31-MAY-05:10 |
General:HeatRejection:EnergyTransfer | 22617.90 | 0.00 | 01-JAN-00:10 | 2706603.28 | 31-MAY-05:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.458 | -794.918 | 0.000 | 0.000 | 92.646 | 240.449 | 424.397 | 0.000 | 0.000 | 0.000 | 32.968 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -809.012 | 0.000 | 0.000 | 83.418 | 215.940 | 321.286 | 0.000 | 0.000 | 0.000 | 188.369 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -6152.918 | 0.000 | 0.000 | 834.605 | 2159.397 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.021 | 0.000 | 0.000 | 0.000 | 0.000 | -53.930 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -634.757 | 0.000 | 0.000 | 83.582 | 215.940 | 321.285 | 0.000 | 0.000 | 0.000 | 13.950 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -124.093 | 0.000 | 0.000 | 10.487 | 18.590 | 40.342 | 35.964 | 0.000 | 0.653 | 33.372 | 0.000 | -14.238 | 0.000 | -1.076 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -98.368 | 0.000 | 0.000 | 6.772 | 11.970 | 25.998 | 48.926 | 0.000 | 0.481 | 13.237 | 0.000 | -8.360 | 0.000 | -0.657 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -151.711 | 0.000 | 0.000 | 10.452 | 18.472 | 40.343 | 75.305 | 0.000 | 0.612 | 21.959 | 0.000 | -14.248 | 0.000 | -1.185 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -144.723 | 0.000 | 0.000 | 6.747 | 11.957 | 25.998 | 45.679 | 0.000 | 0.395 | 66.536 | 0.000 | -11.699 | 0.000 | -0.891 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.019 | -962.096 | 0.000 | 0.000 | 105.483 | 186.067 | 403.423 | 364.392 | 0.000 | 14.125 | 46.253 | 0.000 | -133.386 | 0.000 | -24.279 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.011 | -853.455 | 0.000 | 0.000 | 49.937 | 119.736 | 259.981 | 484.967 | 0.000 | 9.538 | 30.955 | 0.000 | -84.962 | 0.000 | -16.707 | -0.003 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1262.808 | 0.000 | 0.000 | 104.474 | 184.805 | 403.429 | 749.997 | 0.000 | 13.038 | 0.031 | 0.000 | -141.266 | 0.000 | -28.935 | -22.735 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.002 | -904.654 | 0.000 | 0.000 | 68.212 | 119.620 | 259.979 | 467.020 | 0.000 | 9.060 | 97.475 | 0.000 | -98.350 | 0.000 | -18.364 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.102 | -102.287 | 0.000 | 0.000 | 10.629 | 18.607 | 40.342 | 36.091 | 0.000 | 1.672 | 10.434 | 0.000 | -12.760 | 0.000 | -2.831 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.037 | -90.121 | 0.000 | 0.000 | 6.813 | 11.974 | 25.998 | 48.120 | 0.000 | 1.115 | 6.373 | 0.000 | -8.305 | 0.000 | -2.003 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.022 | -132.359 | 0.000 | 0.000 | 10.499 | 18.480 | 40.343 | 74.499 | 0.000 | 1.557 | 4.211 | 0.000 | -13.783 | 0.000 | -3.468 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.023 | -95.322 | 0.000 | 0.000 | 6.871 | 11.962 | 25.998 | 46.424 | 0.000 | 1.099 | 14.664 | 0.000 | -9.528 | 0.000 | -2.190 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -144.194 | 0.000 | 0.000 | 0.949 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -16.601 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1353.870 | 0.000 | 0.000 | 9.489 | 59.652 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -254.076 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.000 | -134.448 | 0.000 | 0.000 | 0.949 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -26.347 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7200.956 | 0.000 | 0.000 | 20.024 | 67.796 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -381.721 |
GROUNDFLOOR_PLENUM | 0.986 | -115.209 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.086 | 115.601 | 0.000 | 0.000 | 0.000 | -2.463 | -0.000 |
MIDFLOOR_PLENUM | 5.003 | -893.325 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19.396 | 911.611 | 0.000 | 0.000 | 0.000 | -42.684 | -0.000 |
TOPFLOOR_PLENUM | 2.273 | -143.396 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.681 | 144.031 | 0.000 | 0.000 | 0.000 | -4.590 | -0.000 |
Total Facility | 8.261 | -1151.930 | 4.673 | -22147.069 | 0.000 | 0.000 | 1523.038 | 3703.342 | 15213.411 | 2477.385 | 0.000 | 75.506 | 1752.051 | 0.000 | -550.885 | 0.000 | -152.323 | -755.420 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 23-JAN-04:02 | 0.00 | 0.00 | 0.00 | -96445.79 | 0.00 | 0.00 | 0.00 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 81821.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 30-JAN-04:03 | 0.00 | 0.00 | 0.00 | -97887.72 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.15 | 0.00 | 0.00 | 0.00 | 88783.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 13-FEB-04:02 | 0.00 | 0.00 | 0.00 | -893452.97 | 0.00 | 0.00 | 0.00 | 10475.32 | 80571.20 | 0.00 | 0.00 | 0.00 | 802406.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 01-MAY-03:02 | 0.00 | 0.00 | 0.00 | -88884.34 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.12 | 0.00 | 0.00 | 0.00 | 79779.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-16:12 | 0.00 | 0.00 | 0.00 | -15380.13 | 0.00 | 0.00 | 44.30 | 80.80 | 758.77 | 3514.47 | 0.00 | 96.51 | 10885.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 16-APR-09:42 | 0.00 | 0.00 | 0.00 | -16598.48 | 0.00 | 0.00 | 24.88 | 52.07 | 488.98 | 9324.49 | 0.00 | 0.00 | 6714.44 | 0.00 | -0.00 | 0.00 | -6.38 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-DEC-12:52 | 0.00 | 0.00 | 0.00 | -18848.44 | 0.00 | 0.00 | 35.69 | 80.80 | 758.78 | 14923.90 | 0.00 | 0.00 | 3056.79 | 0.00 | -0.00 | 0.00 | -7.53 | 0.00 |
PERIMETER_BOT_ZN_4 | 10-DEC-15:32 | 0.00 | 0.00 | 0.00 | -22724.69 | 0.00 | 0.00 | 21.84 | 52.07 | 488.98 | 7337.82 | 0.00 | 13.31 | 14810.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUL-16:31 | 0.00 | 0.00 | 0.00 | -159730.31 | 0.00 | 0.00 | 434.35 | 807.98 | 7587.73 | 39940.64 | 0.00 | 2580.75 | 108378.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-09:12 | 0.00 | 0.00 | 0.00 | -175495.36 | 0.00 | 0.00 | 233.73 | 520.69 | 4889.82 | 96839.43 | 0.00 | 465.93 | 72545.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 03-DEC-13:52 | 0.00 | 0.00 | 0.00 | -180928.88 | 0.00 | 0.00 | 340.74 | 807.99 | 7587.84 | 152856.54 | 0.00 | 0.00 | 21326.15 | 0.00 | -0.00 | 0.00 | -1990.39 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUL-16:31 | 0.00 | 0.00 | 0.00 | -190789.15 | 0.00 | 0.00 | 227.51 | 520.69 | 4889.79 | 79322.77 | 0.00 | 1112.94 | 104715.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-JUL-16:31 | 0.00 | 0.00 | 0.00 | -18807.10 | 0.00 | 0.00 | 40.30 | 80.80 | 758.77 | 3812.15 | 0.00 | 258.78 | 13856.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-09:12 | 0.00 | 0.00 | 0.00 | -18104.34 | 0.00 | 0.00 | 23.13 | 52.07 | 488.98 | 9631.45 | 0.00 | 53.56 | 7855.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-DEC-13:42 | 0.00 | 0.00 | 0.00 | -20890.24 | 0.00 | 0.00 | 33.71 | 80.80 | 758.78 | 15542.43 | 0.00 | 0.00 | 4729.40 | 0.00 | -0.00 | 0.00 | -254.89 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-JUL-16:31 | 0.00 | 0.00 | 0.00 | -21612.60 | 0.00 | 0.00 | 20.88 | 52.07 | 488.98 | 9596.79 | 0.00 | 120.18 | 11333.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-DEC-17:00 | 0.00 | 0.00 | 0.00 | -7915.82 | 0.00 | 0.00 | 100.85 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -500.30 |
DATACENTER_MID_ZN_6 | 06-DEC-17:00 | 0.00 | 0.00 | 0.00 | -75024.68 | 0.00 | 0.00 | 1008.49 | 5208.47 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9136.50 |
DATACENTER_TOP_ZN_6 | 09-APR-17:42 | 0.00 | 0.00 | 0.00 | -7688.35 | 0.00 | 0.00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -135.01 |
DATACENTER_BASEMENT_ZN_6 | 28-AUG-12:20 | 0.00 | 0.00 | 0.00 | -370283.37 | 0.00 | 0.00 | 2164.07 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17432.80 |
GROUNDFLOOR_PLENUM | 30-MAY-05:15 | 0.00 | -14428.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14446.49 | 0.00 | -0.00 | 0.00 | -18.25 | 0.00 |
MIDFLOOR_PLENUM | 05-SEP-05:15 | 0.00 | -116043.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116188.65 | 0.00 | -0.00 | 0.00 | -145.19 | 0.00 |
TOPFLOOR_PLENUM | 28-JUL-15:20 | 0.00 | -23257.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.77 | 23076.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-APR-05:03 | 0.00 | -53982.95 | 0.00 | -1928463.31 | 0.00 | 0.00 | 15954.92 | 39207.80 | 623236.89 | 0.00 | 0.00 | 0.00 | 1341659.91 | 0.00 | -35852.12 | 0.00 | -1761.13 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 29-JUL-16:02 | 0.00 | 0.00 | 24123.01 | 0.00 | 0.00 | 0.00 | 520.12 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -39267.11 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-FEB-06:02 | 0.00 | 0.00 | 88632.94 | 0.00 | 0.00 | 0.00 | 1434.86 | 2630.56 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -36683.54 | 0.00 | -4298.17 | -61833.61 |
PERIMETER_MID_ZN_2 | 04-FEB-06:02 | 0.00 | 0.00 | 56636.15 | 0.00 | 0.00 | 0.00 | 924.02 | 1695.23 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23844.59 | 0.00 | -2867.95 | -39062.63 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-FEB-06:02 | 0.00 | 0.00 | 16739.96 | 0.00 | 0.00 | 0.00 | 909.09 | 1695.23 | 6519.72 | 0.00 | 0.00 | 0.00 | 2029.83 | 0.00 | -25023.80 | 0.00 | -2870.02 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-FEB-05:02 | 0.00 | 0.00 | 13305.21 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 758.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3202.02 | 0.00 | -1994.51 | -8998.98 |
PERIMETER_TOP_ZN_2 | 04-FEB-05:02 | 0.00 | 0.00 | 10274.36 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2093.49 | 0.00 | -1353.73 | -7400.88 |
PERIMETER_TOP_ZN_1 | 04-FEB-06:02 | 0.00 | 0.00 | 12454.00 | 0.00 | 0.00 | 0.00 | 146.09 | 263.06 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3424.31 | 0.00 | -527.51 | -9923.05 |
PERIMETER_TOP_ZN_4 | 04-FEB-05:02 | 0.00 | 0.00 | 9351.81 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2228.68 | 0.00 | -1396.92 | -6299.95 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 22-DEC-04:02 | 11140.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -246.88 | -10893.64 |
MIDFLOOR_PLENUM | 30-JAN-04:02 | 81490.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -264.81 | -81225.27 |
TOPFLOOR_PLENUM | 15-MAR-05:03 | 19276.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -639.44 | -18636.60 |
Total Facility | 04-FEB-06:02 | -1171179.91 | 1228961.60 | 205664.90 | -1228961.60 | 0.00 | 0.00 | 17290.52 | 39207.80 | 386654.09 | 0.00 | 0.00 | 0.00 | 695662.71 | 0.00 | -147522.14 | 0.00 | -25777.98 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.0953 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.5487 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 94.5159 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 88.9187 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.8212 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.5071 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.8254 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.8254 | 0.2060 | 1.0000 | Not calculated | 1.2002 | 0.2060 | ||
AIRLOOP DATACENTER BASEMENT | 21.3851 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.3853 | 0.0158 | 1.0000 | Not calculated | 0.3384 | 0.0158 | ||
AIRLOOP DATACENTER BOT | 0.4729 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4729 | 0.0331 | 1.0000 | Not calculated | 0.0156 | 0.0331 | ||
AIRLOOP DATACENTER MID | 4.4935 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4935 | 0.0348 | 1.0000 | Not calculated | 0.1563 | 0.0348 | ||
AIRLOOP DATACENTER TOP | 0.4563 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4563 | 0.0343 | 1.0000 | Not calculated | 0.0156 | 0.0343 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.0477 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1601 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 47.2579 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 30.3787 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.9106 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1927 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.8254 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.8254 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2060 | ||
AIRLOOP DATACENTER BASEMENT | 21.3851 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.3851 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0158 | ||
AIRLOOP DATACENTER BOT | 0.4729 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4729 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0331 | ||
AIRLOOP DATACENTER MID | 4.4935 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4935 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0348 | ||
AIRLOOP DATACENTER TOP | 0.4563 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4563 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0343 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.8254 | 5.8254 | 5.8254 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9788 | 5.9788 | 1.9252 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 56.2217 | 56.2217 | 18.8905 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5982 | 5.5982 | 1.9258 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9901 | 0.9901 | 0.2970 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9318 | 0.9318 | 0.2795 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9805 | 0.9805 | 0.2942 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2141 | 1.2141 | 0.3642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.3522 | 9.3522 | 2.8057 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.5266 | 9.5266 | 2.8580 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.1482 | 9.1482 | 2.7445 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.2671 | 10.2671 | 3.0801 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0564 | 1.0564 | 0.3169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9803 | 0.9803 | 0.2941 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0595 | 1.0595 | 0.3178 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1269 | 1.1269 | 0.3381 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4729 | 0.4729 | 0.4729 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4935 | 4.4935 | 4.4935 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4563 | 0.4563 | 0.4563 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.3851 | 21.3851 | 21.3851 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.0953 | 9.5487 | 10.0953 | 3.1601 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 94.5159 | 88.9187 | 94.5159 | 30.3787 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.8212 | 9.5071 | 9.8212 | 3.1927 | 0.0000 | 1.0000 |
CAV_BAS | 5.8254 | 5.8254 | 5.8254 | 5.8254 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.3851 | 21.3853 | 21.3851 | 21.3851 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4729 | 0.4729 | 0.4729 | 0.4729 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4935 | 4.4935 | 4.4935 | 4.4935 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4563 | 0.4563 | 0.4563 | 0.4563 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.8254 | 5.8254 | 5.8254 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9894 | 2.9894 | 1.9252 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.1108 | 28.1108 | 18.8905 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7991 | 2.7991 | 1.9258 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4950 | 0.4950 | 0.2970 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4659 | 0.4659 | 0.2795 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4903 | 0.4903 | 0.2942 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6071 | 0.6071 | 0.3642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6761 | 4.6761 | 2.8057 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7633 | 4.7633 | 2.8580 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5741 | 4.5741 | 2.7445 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1336 | 5.1336 | 3.0801 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5282 | 0.5282 | 0.3169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4901 | 0.4901 | 0.2941 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5297 | 0.5297 | 0.3178 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5634 | 0.5634 | 0.3381 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4729 | 0.4729 | 0.4729 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4935 | 4.4935 | 4.4935 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4563 | 0.4563 | 0.4563 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.3851 | 21.3851 | 21.3851 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.0477 | 3.1601 | 3.1601 | 3.1601 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 47.2579 | 30.3787 | 30.3787 | 30.3787 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.9106 | 3.1927 | 3.1927 | 3.1927 | 0.0000 | 1.0000 |
CAV_BAS | 5.8254 | 5.8254 | 5.8254 | 5.8254 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.3851 | 21.3851 | 21.3851 | 21.3851 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4729 | 0.4729 | 0.4729 | 0.4729 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4935 | 4.4935 | 4.4935 | 4.4935 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4563 | 0.4563 | 0.4563 | 0.4563 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 918.33 |
Number of hours not met | 918.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 4.23 | 212165.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6198.02 | 476372.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3703.34 | 352853.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 671.42 | 54335.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.32 | 5481.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2684.96 | 222608.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1414.42 | 81035.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 2170.92 | 97050.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1.15 | 4076.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 119.80 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 564.00 | 68200.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 34119.37 |
Natural Gas | 0.00 | 568.23 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 34687.60 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 79.95 |
Space Heating | 0.00 |
Space Cooling | 133.81 |
Fans (All) | 57.96 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 736.60 |
Subtotal | 736.60 |
Natural Gas [MJ/m2] | |
Space Heating | 0.09 |
Service Water Heating | 12.18 |
Miscellaneous (All) | 12.27 |
Subtotal | 12.27 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.68 |
Space Heating | 0.01 |
Space Cooling | 17.87 |
Fans (All) | 7.74 |
Service Water Heating | 1.63 |
Receptacle Equipment | 43.86 |
Miscellaneous | 18.22 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2645. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 6781.50 | 1978.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8665.50 | 94.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8727.00 | 33.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8687.17 | 72.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8725.83 | 34.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8688.83 | 71.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8509.50 | 250.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7626.33 | 1133.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8350.33 | 409.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8175.67 | 584.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7873.83 | 886.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7565.50 | 1194.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8296.33 | 463.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8133.83 | 626.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7891.83 | 868.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7658.17 | 1101.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1267.83 | 7492.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1271.83 | 7488.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1240.00 | 7520.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 1060.17 | 7699.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8360.83 | 399.17 | 0.00 | 0.00 | 0.00 |
Min | 1060.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 7699.83 | 0.00 | 0.00 | 0.00 |
Average | 7003.38 | 1756.62 | 0.00 | 0.00 | 0.00 |
Sum | 161077.83 | 40402.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 363464.00 | 5152.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330718.00 | 95.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330795.00 | 18.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330758.00 | 55.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 214.50 | 2053.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 216.00 | 2052.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 211.00 | 2057.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 9512.67 | 93882.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 363464.00 | 93882.33 | 0.00 | 0.00 | 0.00 |
Average | 75753.83 | 4581.08 | 0.00 | 0.00 | 0.00 |
Sum | 1742338.17 | 105364.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 3583.83 | 5176.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 6356.00 | 2404.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 6182.50 | 2577.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 6038.33 | 2721.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 5876.67 | 2883.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6821.50 | 1938.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5598.33 | 3161.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5430.33 | 3329.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 5531.83 | 3228.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 5653.50 | 3106.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5323.67 | 3436.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5519.33 | 3240.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 5589.67 | 3170.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 5643.50 | 3116.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5380.17 | 3379.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5567.00 | 3193.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2416.00 | 6344.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2390.83 | 6369.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2321.83 | 6438.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 2458.17 | 6301.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 5165.33 | 3594.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 4537.17 | 4222.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3426.83 | 5333.17 | 0.00 | 0.00 | 0.00 |
Min | 2321.83 | 1938.50 | 0.00 | 0.00 | 0.00 |
Max | 6821.50 | 6438.17 | 0.00 | 0.00 | 0.00 |
Average | 4904.88 | 3855.12 | 0.00 | 0.00 | 0.00 |
Sum | 112812.33 | 88667.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 328521.33 | 40094.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 326431.00 | 4382.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 326643.00 | 4170.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 325887.00 | 4926.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38924.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38894.17 | 30.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18351.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38895.83 | 29.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24907.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38892.33 | 32.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24904.33 | 4.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38894.67 | 30.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24906.83 | 2.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 389.17 | 1878.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 386.50 | 1881.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 374.50 | 1893.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 19415.67 | 83979.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 328521.33 | 83979.33 | 0.00 | 0.00 | 0.00 |
Average | 74102.75 | 6232.16 | 0.00 | 0.00 | 0.00 |
Sum | 1704363.33 | 143339.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:32
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.664362E+11 | 96449.65 | 23-JAN-04:02 | 12.20 | 11.63 | 0.567285E+10 | 7499.12 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.591449E+11 | 95738.45 | 27-FEB-04:02 | 15.60 | 13.66 | 0.514478E+10 | 7499.10 | 23-FEB-10:09 | 15.60 | 13.66 |
March | 0.667945E+11 | 93086.82 | 21-MAR-03:02 | 11.78 | 9.38 | 0.613753E+10 | 7499.07 | 17-MAR-13:09 | 11.78 | 9.38 |
April | 0.611623E+11 | 90149.02 | 20-APR-03:02 | 21.02 | 15.02 | 0.545369E+10 | 7499.09 | 21-APR-09:20 | 25.40 | 18.57 |
May | 0.651893E+11 | 87338.49 | 08-MAY-03:02 | 23.30 | 18.59 | 0.590528E+10 | 7498.81 | 25-MAY-09:20 | 24.23 | 23.36 |
June | 0.650857E+11 | 80121.06 | 13-JUN-03:02 | 24.32 | 22.73 | 0.588460E+10 | 7498.80 | 28-JUN-09:20 | 26.30 | 24.72 |
July | 0.660860E+11 | 81173.33 | 06-JUL-03:02 | 23.40 | 22.52 | 0.547696E+10 | 7498.80 | 07-JUL-13:20 | 32.03 | 25.28 |
August | 0.738068E+11 | 82524.57 | 08-AUG-03:02 | 26.10 | 23.70 | 0.614008E+10 | 7498.77 | 25-AUG-09:20 | 26.10 | 23.98 |
September | 0.659853E+11 | 81103.64 | 12-SEP-03:02 | 24.40 | 22.75 | 0.545529E+10 | 7498.78 | 15-SEP-09:20 | 27.40 | 24.40 |
October | 0.694916E+11 | 86538.25 | 18-OCT-03:02 | 24.32 | 18.76 | 0.567480E+10 | 7498.77 | 18-OCT-09:20 | 26.70 | 18.90 |
November | 0.683989E+11 | 95190.97 | 27-NOV-05:02 | 10.00 | 8.82 | 0.561896E+10 | 7499.12 | 13-NOV-10:09 | 10.00 | 8.82 |
December | 0.673400E+11 | 93039.92 | 21-DEC-04:02 | 10.60 | 9.92 | 0.547630E+10 | 7499.15 | 21-DEC-10:09 | 19.08 | 15.38 |
Annual Sum or Average | 0.794922E+12 | 0.680411E+11 | ||||||||
Minimum of Months | 0.591449E+11 | 80121.06 | 10.00 | 8.82 | 0.514478E+10 | 7498.77 | 10.00 | 8.82 | ||
Maximum of Months | 0.738068E+11 | 96449.65 | 26.10 | 23.70 | 0.614008E+10 | 7499.15 | 32.03 | 25.28 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.565824E+11 | 97920.70 | 30-JAN-04:03 | 21.60 | 20.86 | 0.507976E+10 | 6734.94 | 27-JAN-10:00 | 21.60 | 20.86 |
February | 0.546329E+11 | 96852.18 | 13-FEB-04:02 | 20.50 | 19.41 | 0.460836E+10 | 6734.87 | 14-FEB-14:39 | 24.23 | 20.09 |
March | 0.691726E+11 | 97233.12 | 20-MAR-03:02 | 12.70 | 9.59 | 0.549845E+10 | 6734.79 | 01-MAR-10:09 | 12.70 | 9.59 |
April | 0.711291E+11 | 87551.13 | 17-APR-05:04 | 18.90 | 16.76 | 0.487800E+10 | 6734.82 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.652854E+11 | 89740.55 | 08-MAY-03:02 | 23.30 | 18.59 | 0.528626E+10 | 6734.59 | 22-MAY-13:00 | 33.90 | 23.74 |
June | 0.692211E+11 | 83298.79 | 19-JUN-04:23 | 24.40 | 22.95 | 0.526738E+10 | 6734.61 | 12-JUN-09:00 | 24.40 | 22.95 |
July | 0.735895E+11 | 80667.76 | 03-JUL-05:04 | 25.10 | 24.21 | 0.489320E+10 | 6734.55 | 26-JUL-13:00 | 31.70 | 25.48 |
August | 0.813493E+11 | 83126.69 | 21-AUG-05:05 | 27.20 | 24.67 | 0.549436E+10 | 6734.78 | 07-AUG-13:20 | 27.20 | 24.67 |
September | 0.641527E+11 | 90162.30 | 05-SEP-03:02 | 23.30 | 21.69 | 0.488032E+10 | 6734.79 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.686813E+11 | 90969.60 | 28-OCT-03:02 | 21.10 | 20.29 | 0.507605E+10 | 6734.94 | 26-OCT-13:20 | 21.10 | 20.29 |
November | 0.671296E+11 | 94973.98 | 27-NOV-04:02 | 10.00 | 8.82 | 0.502899E+10 | 6734.94 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.680868E+11 | 94831.93 | 27-DEC-04:02 | 9.40 | 8.79 | 0.489964E+10 | 6735.06 | 22-DEC-14:39 | 9.40 | 8.79 |
Annual Sum or Average | 0.809013E+12 | 0.608908E+11 | ||||||||
Minimum of Months | 0.546329E+11 | 80667.76 | 9.40 | 8.79 | 0.460836E+10 | 6734.55 | 9.40 | 8.79 | ||
Maximum of Months | 0.813493E+11 | 97920.70 | 27.20 | 24.67 | 0.549845E+10 | 6735.06 | 33.90 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.459205E+11 | 87555.63 | 02-JAN-04:02 | 18.80 | 18.44 | 0.506902E+10 | 6734.94 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.423611E+11 | 89373.23 | 13-FEB-04:02 | 20.50 | 19.41 | 0.459815E+10 | 6734.84 | 14-FEB-14:39 | 24.23 | 20.09 |
March | 0.510954E+11 | 85605.81 | 20-MAR-03:02 | 12.70 | 9.59 | 0.549550E+10 | 6734.78 | 01-MAR-10:09 | 12.70 | 9.59 |
April | 0.498919E+11 | 84249.68 | 11-APR-03:02 | 22.30 | 19.32 | 0.487840E+10 | 6734.82 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.550992E+11 | 88443.11 | 01-MAY-03:02 | 21.27 | 19.49 | 0.528447E+10 | 6734.58 | 22-MAY-13:00 | 33.90 | 23.74 |
June | 0.555933E+11 | 83650.21 | 06-JUN-03:02 | 23.30 | 22.94 | 0.526773E+10 | 6734.59 | 05-JUN-13:00 | 23.30 | 22.94 |
July | 0.552201E+11 | 83693.43 | 06-JUL-03:02 | 23.40 | 22.52 | 0.489203E+10 | 6734.59 | 25-JUL-09:20 | 30.93 | 25.34 |
August | 0.576335E+11 | 82574.71 | 24-AUG-03:02 | 25.00 | 24.24 | 0.549472E+10 | 6734.65 | 07-AUG-13:20 | 25.00 | 24.24 |
September | 0.536855E+11 | 85284.89 | 26-SEP-03:02 | 23.30 | 22.57 | 0.487786E+10 | 6734.80 | 11-SEP-13:39 | 23.30 | 22.57 |
October | 0.538767E+11 | 86287.74 | 16-OCT-03:02 | 21.70 | 20.21 | 0.507397E+10 | 6734.94 | 26-OCT-13:39 | 24.27 | 21.92 |
November | 0.492510E+11 | 87483.04 | 13-NOV-04:03 | 12.80 | 8.34 | 0.502673E+10 | 6734.93 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.456653E+11 | 85440.85 | 26-DEC-04:02 | 23.22 | 22.09 | 0.488937E+10 | 6735.00 | 18-DEC-14:39 | 23.22 | 22.09 |
Annual Sum or Average | 0.615293E+12 | 0.608480E+11 | ||||||||
Minimum of Months | 0.423611E+11 | 82574.71 | 12.70 | 8.34 | 0.459815E+10 | 6734.58 | 12.70 | 9.59 | ||
Maximum of Months | 0.576335E+11 | 89373.23 | 25.00 | 24.24 | 0.549550E+10 | 6735.00 | 33.90 | 25.34 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.401266E+11 | 85630.17 | 30-JAN-04:02 | 21.60 | 20.86 | 0.502066E+10 | 6734.88 | 27-JAN-10:00 | 21.60 | 20.86 |
February | 0.398210E+11 | 87054.25 | 13-FEB-04:02 | 20.50 | 19.41 | 0.456989E+10 | 6734.78 | 23-FEB-10:50 | 24.13 | 18.14 |
March | 0.500438E+11 | 86376.26 | 27-MAR-03:02 | 21.52 | 21.17 | 0.547732E+10 | 6734.75 | 01-MAR-10:09 | 21.52 | 21.17 |
April | 0.522364E+11 | 85934.61 | 24-APR-03:02 | 22.80 | 19.79 | 0.487841E+10 | 6734.80 | 20-APR-09:09 | 22.80 | 19.79 |
May | 0.603971E+11 | 88904.46 | 01-MAY-03:02 | 21.27 | 19.49 | 0.528777E+10 | 6734.55 | 25-MAY-09:09 | 24.32 | 23.32 |
June | 0.620477E+11 | 84246.87 | 06-JUN-03:02 | 23.30 | 22.94 | 0.527075E+10 | 6734.59 | 05-JUN-13:50 | 23.30 | 22.94 |
July | 0.626028E+11 | 84369.13 | 18-JUL-03:02 | 22.80 | 22.38 | 0.489742E+10 | 6734.56 | 14-JUL-13:00 | 22.80 | 22.38 |
August | 0.633166E+11 | 83456.31 | 24-AUG-03:02 | 25.00 | 24.24 | 0.549698E+10 | 6734.60 | 07-AUG-13:00 | 25.00 | 24.24 |
September | 0.586811E+11 | 84863.27 | 05-SEP-03:02 | 23.30 | 21.69 | 0.488213E+10 | 6734.73 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.560907E+11 | 87358.39 | 16-OCT-03:02 | 21.70 | 20.21 | 0.507654E+10 | 6734.85 | 26-OCT-13:30 | 25.55 | 22.33 |
November | 0.480644E+11 | 87790.32 | 24-NOV-04:02 | 21.60 | 21.31 | 0.501631E+10 | 6734.90 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.413316E+11 | 86421.16 | 26-DEC-04:02 | 23.22 | 22.09 | 0.485209E+10 | 6734.85 | 18-DEC-14:20 | 23.22 | 22.09 |
Annual Sum or Average | 0.634760E+12 | 0.607263E+11 | ||||||||
Minimum of Months | 0.398210E+11 | 83456.31 | 20.50 | 19.41 | 0.456989E+10 | 6734.55 | 21.52 | 16.63 | ||
Maximum of Months | 0.633166E+11 | 88904.46 | 25.00 | 24.24 | 0.549698E+10 | 6734.90 | 28.73 | 24.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.640301E+10 | 13760.18 | 30-JAN-04:02 | 21.60 | 20.86 | 0.630580E+09 | 845.63 | 11-JAN-14:30 | 21.60 | 20.86 |
February | 0.689325E+10 | 12450.45 | 10-FEB-06:03 | 22.20 | 19.69 | 0.575031E+09 | 845.65 | 14-FEB-14:39 | 24.23 | 20.09 |
March | 0.912807E+10 | 12408.44 | 04-MAR-06:03 | 22.80 | 20.89 | 0.687428E+09 | 845.63 | 01-MAR-10:09 | 22.80 | 20.89 |
April | 0.107589E+11 | 12808.50 | 17-APR-05:02 | 18.90 | 16.76 | 0.612422E+09 | 845.63 | 20-APR-09:00 | 24.40 | 18.06 |
May | 0.113407E+11 | 14246.91 | 08-MAY-03:02 | 23.30 | 18.59 | 0.664600E+09 | 845.61 | 22-MAY-13:00 | 33.90 | 23.74 |
June | 0.127353E+11 | 12806.35 | 26-JUN-04:53 | 25.60 | 24.44 | 0.662402E+09 | 845.61 | 12-JUN-09:50 | 25.60 | 24.44 |
July | 0.135773E+11 | 15383.90 | 16-JUL-16:12 | 30.20 | 23.46 | 0.615844E+09 | 845.61 | 26-JUL-13:00 | 31.70 | 25.48 |
August | 0.139936E+11 | 13505.96 | 21-AUG-05:02 | 27.20 | 24.67 | 0.690658E+09 | 845.64 | 07-AUG-13:20 | 27.20 | 24.67 |
September | 0.110535E+11 | 13658.46 | 21-SEP-03:02 | 25.28 | 23.87 | 0.613639E+09 | 845.64 | 11-SEP-13:39 | 25.28 | 23.87 |
October | 0.106241E+11 | 13353.20 | 02-OCT-04:23 | 26.70 | 25.17 | 0.637784E+09 | 845.66 | 26-OCT-13:20 | 26.83 | 22.68 |
November | 0.934878E+10 | 13014.89 | 29-NOV-06:02 | 25.00 | 19.84 | 0.630461E+09 | 845.64 | 27-NOV-10:00 | 25.00 | 19.84 |
December | 0.823787E+10 | 12710.31 | 26-DEC-06:02 | 20.32 | 18.04 | 0.611529E+09 | 845.67 | 18-DEC-14:30 | 20.32 | 18.04 |
Annual Sum or Average | 0.124094E+12 | 0.763238E+10 | ||||||||
Minimum of Months | 0.640301E+10 | 12408.44 | 18.90 | 16.76 | 0.575031E+09 | 845.61 | 20.32 | 18.04 | ||
Maximum of Months | 0.139936E+11 | 15383.90 | 30.20 | 25.17 | 0.690658E+09 | 845.67 | 33.90 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.565064E+10 | 15199.07 | 01-JAN-10:23 | 25.85 | 21.37 | 0.405767E+09 | 544.98 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.581990E+10 | 10815.50 | 20-FEB-09:23 | 19.45 | 16.01 | 0.369726E+09 | 544.97 | 14-FEB-14:39 | 19.45 | 16.01 |
March | 0.778503E+10 | 9138.13 | 27-MAR-08:40 | 23.17 | 21.01 | 0.442121E+09 | 544.96 | 01-MAR-10:09 | 23.17 | 21.01 |
April | 0.881319E+10 | 16605.91 | 16-APR-09:42 | 26.83 | 21.70 | 0.393360E+09 | 544.96 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.915100E+10 | 15139.40 | 07-MAY-09:43 | 28.03 | 21.83 | 0.427760E+09 | 545.27 | 16-MAY-09:50 | 29.32 | 22.48 |
June | 0.967236E+10 | 13528.63 | 04-JUN-09:13 | 30.20 | 25.08 | 0.426504E+09 | 545.83 | 12-JUN-09:50 | 30.40 | 24.34 |
July | 0.102851E+11 | 16469.76 | 04-JUL-10:02 | 30.78 | 24.92 | 0.396533E+09 | 545.35 | 25-JUL-09:00 | 32.80 | 25.50 |
August | 0.102020E+11 | 11842.68 | 21-AUG-05:02 | 27.20 | 24.67 | 0.444019E+09 | 544.97 | 07-AUG-13:20 | 27.20 | 24.67 |
September | 0.890399E+10 | 11832.03 | 24-SEP-11:32 | 31.10 | 25.07 | 0.395237E+09 | 544.96 | 11-SEP-13:39 | 31.10 | 25.07 |
October | 0.857651E+10 | 16169.16 | 09-OCT-08:43 | 28.12 | 24.23 | 0.410119E+09 | 544.98 | 26-OCT-13:20 | 26.83 | 22.68 |
November | 0.719115E+10 | 8338.08 | 07-NOV-09:00 | 23.90 | 21.61 | 0.404879E+09 | 544.97 | 13-NOV-10:09 | 19.68 | 13.91 |
December | 0.631776E+10 | 6774.39 | 08-DEC-09:50 | 25.92 | 22.59 | 0.388437E+09 | 544.98 | 22-DEC-14:39 | 24.27 | 20.02 |
Annual Sum or Average | 0.983686E+11 | 0.490446E+10 | ||||||||
Minimum of Months | 0.565064E+10 | 6774.39 | 19.45 | 16.01 | 0.369726E+09 | 544.96 | 19.45 | 13.91 | ||
Maximum of Months | 0.102851E+11 | 16605.91 | 31.10 | 25.08 | 0.444019E+09 | 545.83 | 32.80 | 25.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111038E+11 | 18238.27 | 15-JAN-13:52 | 25.60 | 16.48 | 0.639290E+09 | 920.18 | 02-JAN-14:39 | 25.60 | 16.48 |
February | 0.106591E+11 | 18809.97 | 20-FEB-14:02 | 26.20 | 17.78 | 0.580650E+09 | 906.71 | 21-FEB-14:20 | 25.77 | 14.45 |
March | 0.122948E+11 | 16957.63 | 26-MAR-12:43 | 27.02 | 22.21 | 0.689586E+09 | 873.08 | 01-MAR-14:30 | 27.02 | 22.21 |
April | 0.120286E+11 | 17150.17 | 16-APR-13:42 | 31.70 | 21.06 | 0.613051E+09 | 846.22 | 14-APR-13:39 | 31.70 | 21.06 |
May | 0.112791E+11 | 14156.13 | 08-MAY-03:02 | 23.30 | 18.59 | 0.664598E+09 | 845.98 | 22-MAY-13:00 | 33.90 | 23.74 |
June | 0.122152E+11 | 13377.51 | 19-JUN-04:23 | 24.40 | 22.95 | 0.662266E+09 | 845.81 | 02-JUN-13:50 | 24.40 | 22.95 |
July | 0.132735E+11 | 15374.15 | 16-JUL-15:32 | 30.77 | 23.83 | 0.615761E+09 | 845.93 | 26-JUL-13:00 | 31.70 | 25.48 |
August | 0.146623E+11 | 16898.53 | 06-AUG-13:12 | 32.93 | 25.10 | 0.690881E+09 | 848.33 | 07-AUG-13:20 | 29.07 | 24.82 |
September | 0.131313E+11 | 17342.24 | 24-SEP-11:32 | 31.10 | 25.07 | 0.614496E+09 | 850.35 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.145215E+11 | 18002.61 | 09-OCT-14:42 | 30.50 | 24.25 | 0.640981E+09 | 880.80 | 25-OCT-13:20 | 30.20 | 22.36 |
November | 0.136093E+11 | 18410.31 | 19-NOV-12:42 | 26.70 | 21.27 | 0.637435E+09 | 923.50 | 07-NOV-14:09 | 26.70 | 21.27 |
December | 0.129333E+11 | 18853.23 | 10-DEC-12:52 | 28.30 | 23.48 | 0.618424E+09 | 940.34 | 04-DEC-14:39 | 28.30 | 23.48 |
Annual Sum or Average | 0.151712E+12 | 0.766742E+10 | ||||||||
Minimum of Months | 0.106591E+11 | 13377.51 | 23.30 | 16.48 | 0.580650E+09 | 845.81 | 24.40 | 14.45 | ||
Maximum of Months | 0.146623E+11 | 18853.23 | 32.93 | 25.10 | 0.690881E+09 | 940.34 | 33.90 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.731705E+10 | 16831.66 | 30-JAN-04:02 | 21.60 | 20.86 | 0.404262E+09 | 544.96 | 11-JAN-14:30 | 21.60 | 20.86 |
February | 0.834678E+10 | 20032.45 | 20-FEB-15:22 | 26.70 | 17.88 | 0.372236E+09 | 544.98 | 14-FEB-14:39 | 26.70 | 17.88 |
March | 0.121487E+11 | 21090.59 | 12-MAR-16:42 | 24.40 | 18.60 | 0.445432E+09 | 544.96 | 24-MAR-13:00 | 26.10 | 19.80 |
April | 0.145517E+11 | 21731.07 | 02-APR-16:42 | 25.78 | 18.10 | 0.396079E+09 | 544.96 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.115690E+11 | 20263.08 | 29-MAY-16:32 | 32.23 | 24.43 | 0.428615E+09 | 544.94 | 22-MAY-13:00 | 32.23 | 24.43 |
June | 0.128614E+11 | 19719.25 | 10-JUN-17:05 | 30.60 | 24.10 | 0.427238E+09 | 544.95 | 12-JUN-09:50 | 30.40 | 24.34 |
July | 0.149626E+11 | 22472.62 | 16-JUL-16:12 | 30.20 | 23.46 | 0.397474E+09 | 544.94 | 26-JUL-13:00 | 31.70 | 25.48 |
August | 0.172469E+11 | 21992.07 | 20-AUG-16:22 | 30.60 | 24.86 | 0.445998E+09 | 544.98 | 07-AUG-13:20 | 30.60 | 24.86 |
September | 0.110329E+11 | 19355.41 | 10-SEP-15:22 | 31.10 | 25.13 | 0.395769E+09 | 544.96 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.119518E+11 | 21796.16 | 09-OCT-16:02 | 29.32 | 23.78 | 0.411801E+09 | 544.99 | 26-OCT-13:20 | 26.83 | 22.68 |
November | 0.112994E+11 | 21359.27 | 26-NOV-15:22 | 21.70 | 12.72 | 0.407634E+09 | 544.97 | 30-NOV-14:30 | 27.20 | 24.74 |
December | 0.114352E+11 | 22736.30 | 10-DEC-15:32 | 28.50 | 22.56 | 0.397250E+09 | 545.00 | 22-DEC-14:39 | 24.27 | 20.02 |
Annual Sum or Average | 0.144723E+12 | 0.492979E+10 | ||||||||
Minimum of Months | 0.731705E+10 | 16831.66 | 21.60 | 12.72 | 0.372236E+09 | 544.94 | 21.60 | 17.53 | ||
Maximum of Months | 0.172469E+11 | 22736.30 | 32.23 | 25.13 | 0.445998E+09 | 545.00 | 32.23 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.499389E+10 | 9803.75 | 07-JAN-06:03 | 22.80 | 22.00 | 0.610653E+09 | 845.63 | 11-JAN-14:39 | 23.17 | 17.75 |
February | 0.509829E+10 | 11096.62 | 11-FEB-06:02 | 23.90 | 22.27 | 0.566441E+09 | 845.63 | 14-FEB-14:39 | 24.23 | 20.09 |
March | 0.648484E+10 | 11580.98 | 30-MAR-05:03 | 22.80 | 19.52 | 0.676362E+09 | 845.63 | 22-MAR-13:00 | 22.80 | 19.52 |
April | 0.750273E+10 | 11844.58 | 24-APR-05:03 | 22.70 | 19.76 | 0.611557E+09 | 845.63 | 20-APR-09:20 | 22.70 | 19.76 |
May | 0.986392E+10 | 13869.05 | 15-MAY-03:02 | 25.60 | 22.76 | 0.664733E+09 | 845.60 | 22-MAY-13:00 | 33.90 | 23.74 |
June | 0.108236E+11 | 14080.21 | 26-JUN-03:02 | 25.60 | 24.11 | 0.662841E+09 | 845.60 | 21-JUN-13:30 | 25.60 | 24.11 |
July | 0.109571E+11 | 15975.38 | 04-JUL-16:31 | 30.57 | 25.19 | 0.616330E+09 | 845.60 | 25-JUL-09:20 | 30.93 | 25.34 |
August | 0.105794E+11 | 13954.81 | 19-AUG-03:02 | 27.30 | 24.11 | 0.691144E+09 | 845.61 | 07-AUG-13:20 | 27.30 | 24.11 |
September | 0.958544E+10 | 14130.80 | 09-SEP-03:02 | 27.80 | 23.94 | 0.613808E+09 | 845.62 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.840779E+10 | 13078.21 | 03-OCT-03:02 | 26.70 | 25.37 | 0.637731E+09 | 845.64 | 26-OCT-13:39 | 24.27 | 21.92 |
November | 0.669100E+10 | 11985.81 | 29-NOV-06:02 | 25.00 | 19.84 | 0.626836E+09 | 845.62 | 30-NOV-14:39 | 27.20 | 24.74 |
December | 0.522346E+10 | 12408.73 | 01-DEC-06:03 | 23.30 | 18.35 | 0.592672E+09 | 845.65 | 18-DEC-14:39 | 25.00 | 19.68 |
Annual Sum or Average | 0.962115E+11 | 0.757111E+10 | ||||||||
Minimum of Months | 0.499389E+10 | 9803.75 | 22.70 | 18.35 | 0.566441E+09 | 845.60 | 22.70 | 17.75 | ||
Maximum of Months | 0.109571E+11 | 15975.38 | 30.57 | 25.37 | 0.691144E+09 | 845.65 | 33.90 | 25.34 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487681E+10 | 13763.88 | 01-JAN-10:13 | 25.57 | 21.29 | 0.291586E+09 | 521.24 | 27-JAN-11:20 | 22.07 | 15.40 |
February | 0.494835E+10 | 8919.28 | 26-FEB-09:53 | 22.20 | 16.05 | 0.268409E+09 | 521.21 | 23-FEB-16:10 | 22.20 | 16.05 |
March | 0.643163E+10 | 8796.99 | 27-MAR-08:40 | 23.17 | 21.01 | 0.322773E+09 | 521.22 | 17-MAR-10:39 | 23.17 | 21.01 |
April | 0.732900E+10 | 17384.30 | 16-APR-09:42 | 26.83 | 21.70 | 0.289475E+09 | 521.22 | 20-APR-10:09 | 24.68 | 18.29 |
May | 0.849465E+10 | 16566.06 | 07-MAY-10:23 | 28.60 | 21.92 | 0.314692E+09 | 521.20 | 22-MAY-14:20 | 32.80 | 23.98 |
June | 0.883399E+10 | 16513.29 | 04-JUN-09:13 | 30.20 | 25.08 | 0.313984E+09 | 521.20 | 12-JUN-08:00 | 29.40 | 23.47 |
July | 0.914940E+10 | 17556.90 | 04-JUL-09:12 | 29.80 | 24.62 | 0.293059E+09 | 521.92 | 25-JUL-10:30 | 33.05 | 25.33 |
August | 0.881686E+10 | 12387.33 | 13-AUG-09:32 | 29.23 | 24.81 | 0.326873E+09 | 521.20 | 08-AUG-14:20 | 29.23 | 24.81 |
September | 0.827094E+10 | 16391.46 | 17-SEP-10:32 | 30.40 | 24.34 | 0.291144E+09 | 521.20 | 07-SEP-14:09 | 30.40 | 24.34 |
October | 0.753180E+10 | 15917.79 | 09-OCT-10:53 | 32.20 | 23.83 | 0.302132E+09 | 521.23 | 10-OCT-12:20 | 27.37 | 23.47 |
November | 0.589224E+10 | 9964.91 | 29-NOV-06:02 | 25.00 | 19.84 | 0.296811E+09 | 521.22 | 13-NOV-11:20 | 25.00 | 19.84 |
December | 0.477172E+10 | 6903.51 | 01-DEC-06:03 | 23.30 | 18.35 | 0.277109E+09 | 521.23 | 08-DEC-11:39 | 27.20 | 22.61 |
Annual Sum or Average | 0.853474E+11 | 0.358805E+10 | ||||||||
Minimum of Months | 0.477172E+10 | 6903.51 | 22.20 | 16.05 | 0.268409E+09 | 521.20 | 22.07 | 15.40 | ||
Maximum of Months | 0.914940E+10 | 17556.90 | 32.20 | 25.08 | 0.326873E+09 | 521.92 | 33.05 | 25.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101096E+11 | 17335.57 | 01-JAN-13:32 | 26.47 | 21.74 | 0.641105E+09 | 952.23 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.922612E+10 | 16745.69 | 20-FEB-12:13 | 24.07 | 17.34 | 0.580560E+09 | 928.34 | 21-FEB-14:39 | 25.93 | 14.05 |
March | 0.983395E+10 | 14055.12 | 05-MAR-11:53 | 28.30 | 23.49 | 0.687172E+09 | 891.23 | 01-MAR-14:39 | 28.30 | 23.49 |
April | 0.889862E+10 | 15923.05 | 16-APR-13:42 | 31.70 | 21.06 | 0.612918E+09 | 846.01 | 14-APR-13:39 | 31.70 | 21.06 |
May | 0.980061E+10 | 13545.85 | 15-MAY-03:02 | 25.60 | 22.76 | 0.664714E+09 | 845.86 | 22-MAY-13:00 | 33.90 | 23.74 |
June | 0.102768E+11 | 13673.67 | 26-JUN-03:02 | 25.60 | 24.11 | 0.662640E+09 | 845.70 | 02-JUN-13:00 | 25.60 | 24.11 |
July | 0.106492E+11 | 15447.93 | 04-JUL-15:51 | 31.70 | 25.12 | 0.616189E+09 | 845.82 | 26-JUL-13:00 | 31.70 | 25.48 |
August | 0.113519E+11 | 13744.31 | 19-AUG-03:02 | 27.30 | 24.11 | 0.691424E+09 | 845.88 | 02-AUG-13:39 | 27.30 | 24.11 |
September | 0.118436E+11 | 16784.57 | 17-SEP-13:12 | 31.10 | 24.35 | 0.614846E+09 | 869.14 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.126884E+11 | 17257.14 | 29-OCT-11:42 | 30.60 | 24.92 | 0.643755E+09 | 904.75 | 25-OCT-13:00 | 30.60 | 24.92 |
November | 0.113920E+11 | 17341.27 | 19-NOV-13:22 | 26.70 | 21.27 | 0.639883E+09 | 955.95 | 07-NOV-14:20 | 26.70 | 21.27 |
December | 0.102123E+11 | 18088.06 | 03-DEC-13:52 | 24.40 | 18.35 | 0.617118E+09 | 966.51 | 04-DEC-14:39 | 25.93 | 17.99 |
Annual Sum or Average | 0.126283E+12 | 0.767233E+10 | ||||||||
Minimum of Months | 0.889862E+10 | 13545.85 | 24.07 | 17.34 | 0.580560E+09 | 845.70 | 25.60 | 14.05 | ||
Maximum of Months | 0.126884E+11 | 18088.06 | 31.70 | 25.12 | 0.691424E+09 | 966.51 | 33.90 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.516143E+10 | 8035.02 | 14-JAN-05:02 | 23.90 | 21.32 | 0.386107E+09 | 544.96 | 11-JAN-14:00 | 23.90 | 21.32 |
February | 0.531820E+10 | 12587.39 | 19-FEB-16:12 | 27.03 | 21.82 | 0.360546E+09 | 544.96 | 14-FEB-14:39 | 27.03 | 21.82 |
March | 0.703689E+10 | 12723.84 | 12-MAR-16:23 | 24.40 | 18.50 | 0.433468E+09 | 544.96 | 22-MAR-13:00 | 23.30 | 17.73 |
April | 0.792772E+10 | 18388.13 | 09-APR-16:11 | 27.03 | 18.57 | 0.394056E+09 | 544.96 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.889604E+10 | 18001.57 | 29-MAY-16:12 | 32.77 | 24.48 | 0.427999E+09 | 544.94 | 22-MAY-13:00 | 32.77 | 24.48 |
June | 0.885555E+10 | 16294.87 | 10-JUN-17:05 | 30.60 | 24.10 | 0.427009E+09 | 544.94 | 21-JUN-13:30 | 29.40 | 23.64 |
July | 0.950358E+10 | 19083.30 | 04-JUL-16:31 | 30.57 | 25.19 | 0.397209E+09 | 544.94 | 25-JUL-09:20 | 30.93 | 25.34 |
August | 0.960521E+10 | 18414.68 | 13-AUG-16:52 | 30.00 | 25.51 | 0.445414E+09 | 544.94 | 07-AUG-13:20 | 30.00 | 25.51 |
September | 0.832693E+10 | 18878.80 | 17-SEP-15:12 | 31.10 | 24.71 | 0.395208E+09 | 544.95 | 11-SEP-13:39 | 31.10 | 24.71 |
October | 0.788224E+10 | 18199.16 | 15-OCT-15:42 | 28.98 | 20.79 | 0.410420E+09 | 544.97 | 26-OCT-13:30 | 25.55 | 22.33 |
November | 0.638603E+10 | 11898.17 | 29-NOV-06:02 | 25.00 | 19.84 | 0.401428E+09 | 544.96 | 30-NOV-14:39 | 27.20 | 24.74 |
December | 0.556701E+10 | 17977.59 | 10-DEC-15:32 | 28.50 | 22.56 | 0.376718E+09 | 544.98 | 18-DEC-14:30 | 25.00 | 19.78 |
Annual Sum or Average | 0.904668E+11 | 0.485558E+10 | ||||||||
Minimum of Months | 0.516143E+10 | 8035.02 | 23.90 | 18.50 | 0.360546E+09 | 544.94 | 23.30 | 17.53 | ||
Maximum of Months | 0.960521E+10 | 19083.30 | 32.77 | 25.51 | 0.445414E+09 | 544.98 | 32.77 | 25.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471569E+10 | 11101.55 | 14-JAN-06:03 | 23.62 | 21.60 | 0.586540E+09 | 845.62 | 20-JAN-14:09 | 18.98 | 12.27 |
February | 0.502319E+10 | 12409.21 | 11-FEB-06:02 | 23.90 | 22.27 | 0.553843E+09 | 845.62 | 14-FEB-14:30 | 24.70 | 20.13 |
March | 0.662320E+10 | 12645.68 | 14-MAR-05:03 | 23.30 | 22.15 | 0.663290E+09 | 845.63 | 22-MAR-13:00 | 23.30 | 17.73 |
April | 0.797855E+10 | 13030.74 | 29-APR-05:02 | 22.80 | 20.23 | 0.609146E+09 | 845.63 | 20-APR-09:09 | 22.80 | 20.23 |
May | 0.107870E+11 | 17993.49 | 29-MAY-16:12 | 32.77 | 24.48 | 0.664578E+09 | 845.60 | 01-MAY-13:00 | 32.77 | 24.48 |
June | 0.119749E+11 | 17912.64 | 25-JUN-17:12 | 29.40 | 24.47 | 0.662930E+09 | 845.83 | 02-JUN-13:39 | 29.40 | 24.47 |
July | 0.122955E+11 | 18809.04 | 04-JUL-16:31 | 30.57 | 25.19 | 0.616531E+09 | 845.60 | 10-JUL-09:09 | 25.37 | 23.57 |
August | 0.115909E+11 | 18031.29 | 20-AUG-15:31 | 31.13 | 25.04 | 0.690980E+09 | 845.60 | 09-AUG-13:39 | 31.13 | 25.04 |
September | 0.105285E+11 | 18435.55 | 10-SEP-15:12 | 31.10 | 25.19 | 0.613688E+09 | 845.61 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.891597E+10 | 14346.61 | 02-OCT-03:02 | 26.70 | 25.31 | 0.636689E+09 | 845.63 | 26-OCT-13:20 | 26.83 | 22.68 |
November | 0.676803E+10 | 13613.53 | 29-NOV-06:02 | 25.00 | 19.84 | 0.620409E+09 | 845.61 | 13-NOV-14:00 | 25.00 | 19.84 |
December | 0.508749E+10 | 11641.09 | 01-DEC-06:03 | 23.30 | 18.35 | 0.571899E+09 | 845.63 | 18-DEC-14:20 | 25.00 | 19.88 |
Annual Sum or Average | 0.102289E+12 | 0.749052E+10 | ||||||||
Minimum of Months | 0.471569E+10 | 11101.55 | 22.80 | 18.35 | 0.553843E+09 | 845.60 | 18.98 | 12.27 | ||
Maximum of Months | 0.122955E+11 | 18809.04 | 32.77 | 25.31 | 0.690980E+09 | 845.83 | 32.77 | 25.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.451692E+10 | 10047.27 | 01-JAN-10:02 | 25.28 | 21.21 | 0.392113E+09 | 544.98 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.484632E+10 | 7135.81 | 28-FEB-10:10 | 24.40 | 16.25 | 0.362806E+09 | 544.96 | 23-FEB-10:50 | 24.40 | 16.25 |
March | 0.649135E+10 | 8980.36 | 27-MAR-10:30 | 25.85 | 21.67 | 0.438684E+09 | 544.97 | 17-MAR-09:09 | 25.85 | 21.67 |
April | 0.773661E+10 | 17090.79 | 09-APR-09:32 | 25.37 | 18.85 | 0.393196E+09 | 544.97 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.925827E+10 | 17137.12 | 07-MAY-10:32 | 28.70 | 21.94 | 0.427766E+09 | 545.32 | 18-MAY-09:00 | 29.40 | 22.43 |
June | 0.978075E+10 | 17102.58 | 04-JUN-09:13 | 30.20 | 25.08 | 0.427176E+09 | 545.63 | 12-JUN-09:50 | 30.40 | 24.34 |
July | 0.102184E+11 | 18111.55 | 04-JUL-09:12 | 29.80 | 24.62 | 0.397458E+09 | 545.28 | 25-JUL-09:00 | 32.80 | 25.50 |
August | 0.966590E+10 | 16587.58 | 20-AUG-15:31 | 31.13 | 25.04 | 0.444858E+09 | 545.29 | 30-AUG-09:00 | 30.60 | 23.44 |
September | 0.907731E+10 | 17176.26 | 10-SEP-15:12 | 31.10 | 25.19 | 0.395374E+09 | 544.95 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.800725E+10 | 16947.62 | 09-OCT-10:53 | 32.20 | 23.83 | 0.410048E+09 | 544.96 | 26-OCT-13:20 | 26.83 | 22.68 |
November | 0.597692E+10 | 10661.71 | 29-NOV-06:02 | 25.00 | 19.84 | 0.402208E+09 | 544.96 | 13-NOV-10:20 | 25.00 | 19.84 |
December | 0.454749E+10 | 6720.62 | 08-DEC-10:30 | 26.65 | 22.70 | 0.372165E+09 | 544.96 | 22-DEC-14:30 | 24.45 | 19.96 |
Annual Sum or Average | 0.901234E+11 | 0.486385E+10 | ||||||||
Minimum of Months | 0.451692E+10 | 6720.62 | 24.40 | 16.25 | 0.362806E+09 | 544.95 | 21.70 | 15.05 | ||
Maximum of Months | 0.102184E+11 | 18111.55 | 32.20 | 25.19 | 0.444858E+09 | 545.63 | 32.80 | 25.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.958881E+10 | 19815.74 | 01-JAN-13:22 | 26.65 | 21.70 | 0.628291E+09 | 909.13 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.907871E+10 | 19639.54 | 19-FEB-14:32 | 27.20 | 21.86 | 0.572653E+09 | 888.94 | 21-FEB-14:50 | 26.02 | 13.83 |
March | 0.991445E+10 | 18199.67 | 26-MAR-12:43 | 27.02 | 22.21 | 0.679634E+09 | 854.28 | 01-MAR-14:39 | 27.02 | 22.21 |
April | 0.942830E+10 | 13705.87 | 24-APR-05:03 | 22.70 | 19.76 | 0.610998E+09 | 845.98 | 17-APR-13:20 | 22.70 | 19.76 |
May | 0.107331E+11 | 17755.05 | 29-MAY-16:12 | 32.77 | 24.48 | 0.664374E+09 | 845.90 | 22-MAY-13:39 | 32.77 | 24.48 |
June | 0.114041E+11 | 15237.21 | 17-JUN-03:02 | 26.52 | 21.99 | 0.662661E+09 | 845.62 | 21-JUN-13:20 | 29.40 | 23.58 |
July | 0.119890E+11 | 18693.83 | 04-JUL-15:51 | 31.70 | 25.12 | 0.616322E+09 | 845.77 | 31-JUL-13:20 | 31.83 | 25.29 |
August | 0.124236E+11 | 18271.78 | 20-AUG-15:31 | 31.13 | 25.04 | 0.691203E+09 | 845.92 | 22-AUG-13:20 | 32.23 | 25.94 |
September | 0.129573E+11 | 19631.64 | 10-SEP-15:12 | 31.10 | 25.19 | 0.614623E+09 | 851.05 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.134100E+11 | 20042.86 | 15-OCT-13:02 | 28.90 | 21.63 | 0.640538E+09 | 880.90 | 25-OCT-13:00 | 30.60 | 22.69 |
November | 0.115421E+11 | 19262.84 | 19-NOV-11:32 | 26.70 | 21.43 | 0.633099E+09 | 919.57 | 07-NOV-14:20 | 26.70 | 21.43 |
December | 0.989267E+10 | 20895.19 | 03-DEC-13:42 | 24.32 | 18.38 | 0.605968E+09 | 923.96 | 04-DEC-14:39 | 25.93 | 17.99 |
Annual Sum or Average | 0.132362E+12 | 0.762036E+10 | ||||||||
Minimum of Months | 0.907871E+10 | 13705.87 | 22.70 | 18.38 | 0.572653E+09 | 845.62 | 22.70 | 13.83 | ||
Maximum of Months | 0.134100E+11 | 20895.19 | 32.77 | 25.19 | 0.691203E+09 | 923.96 | 32.77 | 25.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.492477E+10 | 9733.11 | 14-JAN-06:03 | 23.62 | 21.60 | 0.373510E+09 | 544.94 | 11-JAN-14:00 | 23.62 | 21.60 |
February | 0.527105E+10 | 19922.76 | 19-FEB-17:12 | 26.13 | 21.54 | 0.352929E+09 | 544.96 | 21-FEB-14:50 | 26.02 | 13.83 |
March | 0.713403E+10 | 14886.19 | 13-MAR-05:02 | 21.78 | 19.92 | 0.426017E+09 | 544.96 | 22-MAR-13:00 | 23.30 | 17.73 |
April | 0.833810E+10 | 20554.81 | 02-APR-16:12 | 26.33 | 18.20 | 0.391844E+09 | 544.96 | 20-APR-09:00 | 24.40 | 18.06 |
May | 0.963679E+10 | 19803.49 | 29-MAY-16:12 | 32.77 | 24.48 | 0.427129E+09 | 544.93 | 23-MAY-13:09 | 32.77 | 24.48 |
June | 0.974489E+10 | 18743.00 | 10-JUN-17:05 | 30.60 | 24.10 | 0.426552E+09 | 544.94 | 12-JUN-09:00 | 30.60 | 24.52 |
July | 0.105374E+11 | 21615.73 | 09-JUL-16:31 | 30.37 | 25.12 | 0.396926E+09 | 544.93 | 10-JUL-09:09 | 25.37 | 23.57 |
August | 0.104071E+11 | 20135.81 | 20-AUG-16:11 | 30.60 | 24.86 | 0.444921E+09 | 544.94 | 08-AUG-09:00 | 30.60 | 24.86 |
September | 0.909787E+10 | 21003.61 | 10-SEP-15:12 | 31.10 | 25.19 | 0.394372E+09 | 544.95 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.832927E+10 | 20100.82 | 15-OCT-15:42 | 28.98 | 20.79 | 0.408981E+09 | 544.96 | 26-OCT-13:20 | 26.83 | 22.68 |
November | 0.647868E+10 | 12157.81 | 29-NOV-06:02 | 25.00 | 19.84 | 0.396713E+09 | 544.95 | 16-NOV-14:39 | 25.00 | 19.84 |
December | 0.542347E+10 | 11847.20 | 10-DEC-16:23 | 27.75 | 22.51 | 0.366352E+09 | 544.97 | 18-DEC-14:30 | 25.00 | 19.78 |
Annual Sum or Average | 0.953234E+11 | 0.480625E+10 | ||||||||
Minimum of Months | 0.492477E+10 | 9733.11 | 21.78 | 18.20 | 0.352929E+09 | 544.93 | 23.30 | 13.83 | ||
Maximum of Months | 0.105374E+11 | 21615.73 | 32.77 | 25.19 | 0.444921E+09 | 544.97 | 32.77 | 24.86 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.697678E+10 | 12576.55 | 02-JAN-06:15 | 19.23 | 19.01 | 0.00 | 0.00 | 01-JAN-00:10 | 19.23 | 19.01 |
February | 0.697854E+10 | 11751.11 | 21-FEB-06:15 | 15.60 | 15.30 | 0.00 | 0.00 | 01-FEB-00:10 | 15.60 | 15.30 |
March | 0.881382E+10 | 9431.51 | 06-MAR-06:15 | 22.80 | 21.91 | 0.00 | 0.00 | 01-MAR-00:10 | 22.80 | 21.91 |
April | 0.965704E+10 | 9834.71 | 10-APR-05:15 | 20.20 | 18.35 | 0.00 | 0.00 | 01-APR-00:10 | 20.20 | 18.35 |
May | 0.101563E+11 | 14430.30 | 30-MAY-05:15 | 24.03 | 22.53 | 0.00 | 0.00 | 01-MAY-00:10 | 24.03 | 22.53 |
June | 0.110070E+11 | 11518.24 | 19-JUN-05:15 | 24.40 | 23.01 | 0.00 | 0.00 | 01-JUN-00:10 | 24.40 | 23.01 |
July | 0.117499E+11 | 13799.42 | 17-JUL-05:15 | 25.77 | 23.66 | 0.00 | 0.00 | 01-JUL-00:10 | 25.77 | 23.66 |
August | 0.124309E+11 | 14017.33 | 21-AUG-05:15 | 27.20 | 24.60 | 0.00 | 0.00 | 01-AUG-00:10 | 27.20 | 24.60 |
September | 0.103484E+11 | 14059.26 | 11-SEP-05:15 | 27.03 | 24.29 | 0.00 | 0.00 | 01-SEP-00:10 | 27.03 | 24.29 |
October | 0.101680E+11 | 13569.82 | 10-OCT-05:15 | 23.90 | 22.40 | 0.00 | 0.00 | 01-OCT-00:10 | 23.90 | 22.40 |
November | 0.900833E+10 | 12694.54 | 20-NOV-06:15 | 24.40 | 20.29 | 0.00 | 0.00 | 01-NOV-00:10 | 24.40 | 20.29 |
December | 0.791418E+10 | 12548.82 | 26-DEC-06:15 | 20.03 | 17.71 | 0.00 | 0.00 | 01-DEC-00:10 | 20.03 | 17.71 |
Annual Sum or Average | 0.115209E+12 | 0.00 | ||||||||
Minimum of Months | 0.697678E+10 | 9431.51 | 15.60 | 15.30 | 0.00 | 0.00 | 15.60 | 15.30 | ||
Maximum of Months | 0.124309E+11 | 14430.30 | 27.20 | 24.60 | 0.00 | 0.00 | 27.20 | 24.60 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.506893E+10 | 8611.12 | 02-JAN-06:15 | 19.23 | 19.01 | 0.00 | 0.00 | 01-JAN-00:10 | 19.23 | 19.01 |
February | 0.488602E+10 | 7461.97 | 21-FEB-06:15 | 15.60 | 15.30 | 0.00 | 0.00 | 01-FEB-00:10 | 15.60 | 15.30 |
March | 0.637196E+10 | 8261.32 | 06-MAR-06:15 | 22.80 | 21.91 | 0.00 | 0.00 | 01-MAR-00:10 | 22.80 | 21.91 |
April | 0.711490E+10 | 7482.68 | 14-APR-05:03 | 23.30 | 22.20 | 0.00 | 0.00 | 01-APR-00:10 | 23.30 | 22.20 |
May | 0.874586E+10 | 8895.95 | 30-MAY-05:02 | 24.22 | 22.51 | 0.00 | 0.00 | 01-MAY-00:10 | 24.22 | 22.51 |
June | 0.927265E+10 | 11163.41 | 19-JUN-05:15 | 24.40 | 23.01 | 0.00 | 0.00 | 01-JUN-00:10 | 24.40 | 23.01 |
July | 0.941268E+10 | 8923.26 | 18-JUL-05:15 | 23.50 | 22.60 | 0.00 | 0.00 | 01-JUL-00:10 | 23.50 | 22.60 |
August | 0.940611E+10 | 8130.46 | 05-AUG-05:03 | 26.10 | 24.79 | 0.00 | 0.00 | 01-AUG-00:10 | 26.10 | 24.79 |
September | 0.883210E+10 | 11605.97 | 05-SEP-05:15 | 22.93 | 21.59 | 0.00 | 0.00 | 01-SEP-00:10 | 22.93 | 21.59 |
October | 0.829010E+10 | 11553.30 | 02-OCT-05:13 | 26.70 | 25.24 | 0.00 | 0.00 | 01-OCT-00:10 | 26.70 | 25.24 |
November | 0.663425E+10 | 8955.83 | 06-NOV-06:15 | 20.93 | 19.77 | 0.00 | 0.00 | 01-NOV-00:10 | 20.93 | 19.77 |
December | 0.529780E+10 | 7619.69 | 11-DEC-06:15 | 22.20 | 21.45 | 0.00 | 0.00 | 01-DEC-00:10 | 22.20 | 21.45 |
Annual Sum or Average | 0.893333E+11 | 0.00 | ||||||||
Minimum of Months | 0.488602E+10 | 7461.97 | 15.60 | 15.30 | 0.00 | 0.00 | 15.60 | 15.30 | ||
Maximum of Months | 0.941268E+10 | 11605.97 | 26.70 | 25.24 | 0.00 | 0.00 | 26.70 | 25.24 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.541489E+10 | 13112.07 | 02-JAN-15:00 | 28.90 | 23.37 | 0.00 | 0.00 | 01-JAN-00:10 | 28.90 | 23.37 |
February | 0.681417E+10 | 13661.82 | 17-FEB-14:30 | 26.70 | 21.51 | 0.00 | 0.00 | 01-FEB-00:10 | 26.70 | 21.51 |
March | 0.960790E+10 | 17139.36 | 27-MAR-15:20 | 27.60 | 22.33 | 0.00 | 0.00 | 01-MAR-00:10 | 27.60 | 22.33 |
April | 0.124222E+11 | 20235.08 | 13-APR-14:00 | 28.90 | 24.03 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 24.03 |
May | 0.158203E+11 | 21818.61 | 22-MAY-13:40 | 34.07 | 23.58 | 0.00 | 0.00 | 01-MAY-00:10 | 34.07 | 23.58 |
June | 0.166943E+11 | 22597.43 | 09-JUN-13:30 | 30.85 | 24.91 | 0.00 | 0.00 | 01-JUN-00:10 | 30.85 | 24.91 |
July | 0.179567E+11 | 23258.43 | 28-JUL-15:20 | 35.00 | 25.13 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 25.13 |
August | 0.164999E+11 | 21998.25 | 23-AUG-13:50 | 32.48 | 25.39 | 0.00 | 0.00 | 01-AUG-00:10 | 32.48 | 25.39 |
September | 0.150461E+11 | 19578.03 | 18-SEP-14:10 | 31.20 | 25.04 | 0.00 | 0.00 | 01-SEP-00:10 | 31.20 | 25.04 |
October | 0.122961E+11 | 18542.82 | 06-OCT-13:10 | 29.82 | 23.71 | 0.00 | 0.00 | 01-OCT-00:10 | 29.82 | 23.71 |
November | 0.888990E+10 | 15040.21 | 10-NOV-14:10 | 28.90 | 24.10 | 0.00 | 0.00 | 01-NOV-00:10 | 28.90 | 24.10 |
December | 0.593550E+10 | 13073.78 | 08-DEC-14:30 | 27.50 | 22.77 | 0.00 | 0.00 | 01-DEC-00:10 | 27.50 | 22.77 |
Annual Sum or Average | 0.143398E+12 | 0.00 | ||||||||
Minimum of Months | 0.541489E+10 | 13073.78 | 26.70 | 21.51 | 0.00 | 0.00 | 26.70 | 21.51 | ||
Maximum of Months | 0.179567E+11 | 23258.43 | 35.00 | 25.39 | 0.00 | 0.00 | 35.00 | 25.39 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.444596E+10 | 2126.58 | 24-JAN-17:00 | 16.70 | 8.78 | 95235795.48 | 126.85 | 12-JAN-14:00 | 16.70 | 8.78 |
February | 0.869491E+10 | 4226.12 | 20-FEB-17:50 | 25.28 | 17.48 | 86408838.13 | 126.86 | 02-FEB-10:20 | 25.28 | 17.48 |
March | 0.147023E+11 | 7233.49 | 31-MAR-23:40 | 22.67 | 18.03 | 0.103245E+09 | 126.85 | 10-MAR-10:09 | 22.67 | 18.03 |
April | 0.191510E+11 | 7896.98 | 09-APR-18:00 | 25.60 | 18.39 | 91626948.18 | 127.49 | 14-APR-13:00 | 30.60 | 24.51 |
May | 0.472479E+10 | 3524.53 | 31-MAY-24:00 | 26.70 | 24.69 | 99234693.10 | 126.86 | 22-MAY-13:00 | 26.70 | 24.69 |
June | 0.942037E+10 | 5368.62 | 30-JUN-23:55 | 26.90 | 23.74 | 98986457.17 | 126.87 | 06-JUN-09:09 | 26.90 | 23.74 |
July | 0.148057E+11 | 7273.94 | 31-JUL-23:57 | 28.60 | 26.07 | 91894373.87 | 126.85 | 12-JUL-09:09 | 28.60 | 26.07 |
August | 0.199538E+11 | 7750.18 | 06-AUG-16:05 | 28.22 | 23.94 | 0.104631E+09 | 134.44 | 23-AUG-13:50 | 32.48 | 25.39 |
September | 0.458298E+10 | 3485.49 | 30-SEP-24:00 | 28.00 | 23.53 | 91605143.12 | 126.82 | 18-SEP-09:39 | 28.00 | 23.53 |
October | 0.975001E+10 | 5393.93 | 31-OCT-23:42 | 22.60 | 21.27 | 95254414.11 | 126.88 | 04-OCT-09:09 | 22.60 | 21.27 |
November | 0.142624E+11 | 6003.30 | 07-NOV-17:00 | 27.80 | 22.39 | 94311626.18 | 126.85 | 30-NOV-10:09 | 26.70 | 24.69 |
December | 0.196994E+11 | 7915.98 | 06-DEC-17:00 | 25.60 | 21.66 | 91882891.57 | 126.83 | 29-DEC-10:09 | 19.27 | 17.74 |
Annual Sum or Average | 0.144194E+12 | 0.114432E+10 | ||||||||
Minimum of Months | 0.444596E+10 | 2126.58 | 16.70 | 8.78 | 86408838.13 | 126.82 | 16.70 | 8.78 | ||
Maximum of Months | 0.199538E+11 | 7915.98 | 28.60 | 26.07 | 0.104631E+09 | 134.44 | 32.48 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369699E+10 | 1950.28 | 24-JAN-17:00 | 16.70 | 8.78 | 95233213.02 | 126.84 | 23-JAN-14:00 | 16.70 | 8.78 |
February | 0.789895E+10 | 3850.50 | 20-FEB-17:50 | 25.28 | 17.48 | 86408186.20 | 126.86 | 02-FEB-10:00 | 25.28 | 17.48 |
March | 0.138384E+11 | 6967.91 | 31-MAR-23:57 | 22.60 | 17.97 | 0.103246E+09 | 126.85 | 06-MAR-14:00 | 22.60 | 17.97 |
April | 0.182408E+11 | 7423.57 | 09-APR-18:00 | 25.60 | 18.39 | 91623524.62 | 127.45 | 14-APR-13:00 | 30.60 | 24.51 |
May | 0.439610E+10 | 3417.84 | 31-MAY-24:00 | 26.70 | 24.69 | 99233532.51 | 126.84 | 01-MAY-13:00 | 26.70 | 24.69 |
June | 0.896239E+10 | 5232.75 | 30-JUN-23:55 | 26.90 | 23.74 | 98987018.78 | 126.87 | 23-JUN-13:00 | 26.90 | 23.74 |
July | 0.141198E+11 | 7009.19 | 31-JUL-23:57 | 28.60 | 26.07 | 91896111.61 | 126.85 | 17-JUL-13:20 | 28.60 | 26.07 |
August | 0.188977E+11 | 7303.96 | 08-AUG-16:00 | 28.30 | 24.27 | 0.104414E+09 | 134.39 | 23-AUG-13:50 | 32.48 | 25.39 |
September | 0.423795E+10 | 3357.40 | 30-SEP-24:00 | 28.00 | 23.53 | 91605143.30 | 126.82 | 25-SEP-09:09 | 28.00 | 23.53 |
October | 0.922028E+10 | 5102.03 | 31-OCT-24:00 | 22.50 | 21.29 | 95254473.09 | 126.87 | 04-OCT-13:09 | 22.50 | 21.29 |
November | 0.134334E+11 | 5699.87 | 07-NOV-17:00 | 27.80 | 22.39 | 94312630.20 | 126.85 | 29-NOV-14:30 | 26.70 | 24.27 |
December | 0.184442E+11 | 7502.62 | 06-DEC-17:00 | 25.60 | 21.66 | 91883219.46 | 126.83 | 29-DEC-10:09 | 19.27 | 17.74 |
Annual Sum or Average | 0.135387E+12 | 0.114410E+10 | ||||||||
Minimum of Months | 0.369699E+10 | 1950.28 | 16.70 | 8.78 | 86408186.20 | 126.82 | 16.70 | 8.78 | ||
Maximum of Months | 0.188977E+11 | 7502.62 | 28.60 | 26.07 | 0.104414E+09 | 134.39 | 32.48 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318607E+10 | 1953.88 | 02-JAN-17:00 | 25.00 | 20.39 | 95232808.62 | 126.84 | 23-JAN-14:00 | 25.60 | 19.68 |
February | 0.759315E+10 | 3958.87 | 20-FEB-17:50 | 25.28 | 17.48 | 86408486.27 | 126.86 | 02-FEB-14:00 | 25.28 | 17.48 |
March | 0.136779E+11 | 6919.95 | 31-MAR-23:57 | 22.60 | 17.97 | 0.103246E+09 | 126.85 | 06-MAR-10:00 | 22.60 | 17.97 |
April | 0.182620E+11 | 7688.38 | 09-APR-17:44 | 25.78 | 18.40 | 91622024.87 | 127.23 | 14-APR-13:00 | 30.60 | 24.51 |
May | 0.448419E+10 | 3430.84 | 31-MAY-24:00 | 26.70 | 24.69 | 99234213.66 | 126.86 | 22-MAY-13:39 | 26.70 | 24.69 |
June | 0.906221E+10 | 5204.12 | 30-JUN-23:20 | 27.10 | 23.92 | 98987312.15 | 126.88 | 05-JUN-13:00 | 27.10 | 23.92 |
July | 0.142581E+11 | 7020.77 | 31-JUL-23:42 | 28.62 | 25.96 | 91895486.29 | 126.85 | 10-JUL-09:09 | 28.62 | 25.96 |
August | 0.189876E+11 | 7513.87 | 06-AUG-16:22 | 28.05 | 23.89 | 0.104087E+09 | 133.88 | 23-AUG-13:00 | 32.20 | 25.37 |
September | 0.432982E+10 | 3407.12 | 30-SEP-24:00 | 28.00 | 23.53 | 91605144.66 | 126.82 | 18-SEP-09:39 | 28.00 | 23.53 |
October | 0.924181E+10 | 5025.46 | 31-OCT-24:00 | 22.50 | 21.29 | 95254790.28 | 126.87 | 10-OCT-13:09 | 22.50 | 21.29 |
November | 0.132769E+11 | 5767.69 | 07-NOV-17:00 | 27.80 | 22.39 | 94312722.14 | 126.85 | 29-NOV-14:09 | 26.70 | 24.27 |
December | 0.180886E+11 | 7565.77 | 06-DEC-17:00 | 25.60 | 21.66 | 91883539.56 | 126.83 | 29-DEC-10:09 | 19.27 | 17.74 |
Annual Sum or Average | 0.134448E+12 | 0.114377E+10 | ||||||||
Minimum of Months | 0.318607E+10 | 1953.88 | 22.50 | 17.48 | 86408486.27 | 126.82 | 19.27 | 17.48 | ||
Maximum of Months | 0.189876E+11 | 7688.38 | 28.62 | 25.96 | 0.104087E+09 | 133.88 | 32.20 | 25.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243753E+12 | 94128.64 | 02-JAN-17:00 | 25.00 | 20.39 | 0.206189E+10 | 2746.78 | 30-JAN-14:09 | 16.60 | 15.83 |
February | 0.440463E+12 | 185419.65 | 21-FEB-17:00 | 25.60 | 14.07 | 0.187056E+10 | 2746.27 | 02-FEB-10:30 | 25.60 | 14.07 |
March | 0.732509E+12 | 359888.65 | 31-MAR-23:53 | 22.60 | 17.97 | 0.223501E+10 | 2746.80 | 16-MAR-13:09 | 22.60 | 17.97 |
April | 0.943567E+12 | 369782.43 | 17-APR-21:02 | 23.22 | 17.86 | 0.208125E+10 | 3272.65 | 14-APR-13:00 | 23.22 | 17.86 |
May | 0.243661E+12 | 176867.94 | 31-MAY-24:00 | 26.70 | 24.69 | 0.214909E+10 | 2747.15 | 24-MAY-09:00 | 26.70 | 24.69 |
June | 0.472047E+12 | 268400.48 | 30-JUN-23:53 | 26.90 | 23.74 | 0.214293E+10 | 2746.67 | 05-JUN-13:00 | 26.90 | 23.74 |
July | 0.733766E+12 | 358139.63 | 31-JUL-23:12 | 28.67 | 25.64 | 0.198926E+10 | 2745.88 | 10-JUL-09:09 | 28.67 | 25.64 |
August | 0.972238E+12 | 370281.94 | 28-AUG-12:20 | 22.20 | 21.97 | 0.264235E+10 | 3594.90 | 23-AUG-13:39 | 22.20 | 21.97 |
September | 0.238070E+12 | 176869.05 | 30-SEP-23:55 | 28.00 | 23.53 | 0.198409E+10 | 2747.17 | 22-SEP-09:09 | 28.00 | 23.53 |
October | 0.489938E+12 | 269170.10 | 31-OCT-23:55 | 22.50 | 21.29 | 0.206209E+10 | 2746.72 | 04-OCT-09:09 | 22.50 | 21.29 |
November | 0.711368E+12 | 277642.05 | 07-NOV-17:00 | 27.80 | 22.39 | 0.204157E+10 | 2745.87 | 29-NOV-10:00 | 26.10 | 24.93 |
December | 0.979570E+12 | 369715.12 | 11-DEC-17:00 | 22.80 | 16.83 | 0.202304E+10 | 3083.05 | 08-DEC-14:00 | 22.80 | 16.83 |
Annual Sum or Average | 0.720095E+13 | 0.252831E+11 | ||||||||
Minimum of Months | 0.238070E+12 | 94128.64 | 22.20 | 14.07 | 0.187056E+10 | 2745.87 | 16.60 | 14.07 | ||
Maximum of Months | 0.979570E+12 | 370281.94 | 28.67 | 25.64 | 0.264235E+10 | 3594.90 | 28.67 | 25.64 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141336E+09 | 11673.80 | 01-JAN-12:54 | 27.20 |
February | 0.151860E+09 | 11961.05 | 11-FEB-17:12 | 26.83 |
March | 0.199344E+09 | 10733.54 | 04-MAR-17:12 | 25.93 |
April | 0.328830E+09 | 19396.08 | 16-APR-17:02 | 31.10 |
May | 0.481319E+09 | 17256.22 | 29-MAY-16:43 | 31.97 |
June | 0.427253E+09 | 18725.47 | 10-JUN-16:02 | 31.52 |
July | 0.594947E+09 | 24122.13 | 29-JUL-16:02 | 35.40 |
August | 0.464788E+09 | 19895.25 | 06-AUG-13:04 | 33.12 |
September | 0.611049E+09 | 17559.91 | 10-SEP-20:42 | 30.00 |
October | 0.511599E+09 | 17703.21 | 14-OCT-16:03 | 31.23 |
November | 0.323017E+09 | 13280.57 | 23-NOV-15:43 | 27.20 |
December | 0.222661E+09 | 13796.56 | 10-DEC-13:30 | 28.60 |
Annual Sum or Average | 0.445800E+10 | |||
Minimum of Months | 0.141336E+09 | 10733.54 | 25.93 | |
Maximum of Months | 0.611049E+09 | 24122.13 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 1864094.42 | 8863.25 | 04-FEB-06:02 | 5.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 1864094.42 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 1864094.42 | 8863.25 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 1050330.62 | 5663.58 | 04-FEB-06:02 | 5.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 1050330.62 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 1050330.62 | 5663.58 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 200878.20 | 1673.98 | 04-FEB-06:02 | 5.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 200878.20 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 200878.20 | 1673.98 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16048730.90 | 12406.80 | 25-JAN-06:03 | 9.40 |
February | 50056857.56 | 13305.11 | 04-FEB-05:02 | 6.02 |
March | 12815631.72 | 12472.44 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 146306.06 | 975.37 | 13-NOV-06:03 | 12.20 |
December | 22947499.69 | 12443.57 | 15-DEC-06:03 | 7.80 |
Annual Sum or Average | 0.102015E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.02 | |
Maximum of Months | 50056857.56 | 13305.11 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3540620.59 | 6541.03 | 25-JAN-06:03 | 9.40 |
February | 20511360.76 | 10274.23 | 04-FEB-05:02 | 6.02 |
March | 4009506.13 | 6655.44 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 9091154.73 | 9093.23 | 15-DEC-06:03 | 7.80 |
Annual Sum or Average | 37152642.21 | |||
Minimum of Months | 0.00 | 0.00 | 6.02 | |
Maximum of Months | 20511360.76 | 10274.23 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 20855213.38 | 12453.83 | 04-FEB-06:02 | 5.50 |
March | 758170.70 | 3239.34 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 77834.12 | 518.89 | 15-DEC-06:03 | 7.80 |
Annual Sum or Average | 21691218.20 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 20855213.38 | 12453.83 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 491283.00 | 1761.88 | 25-JAN-06:03 | 9.40 |
February | 20442584.67 | 9351.68 | 04-FEB-05:02 | 6.02 |
March | 163486.41 | 1089.91 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 1416984.72 | 4945.50 | 15-DEC-06:03 | 7.80 |
Annual Sum or Average | 22514338.81 | |||
Minimum of Months | 0.00 | 0.00 | 6.02 | |
Maximum of Months | 20442584.67 | 9351.68 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69030983.97 | 10423.18 | 30-JAN-04:02 | 21.60 |
February | 80095519.24 | 10760.31 | 06-FEB-04:02 | 17.30 |
March | 0.106633E+09 | 10662.92 | 20-MAR-03:02 | 12.70 |
April | 87183977.21 | 5452.03 | 19-APR-03:02 | 15.00 |
May | 69538673.45 | 8657.21 | 25-MAY-03:02 | 24.72 |
June | 55966511.61 | 4696.23 | 24-JUN-03:02 | 26.02 |
July | 52820205.80 | 5376.32 | 15-JUL-03:02 | 23.17 |
August | 51038123.71 | 4610.34 | 06-AUG-14:32 | 31.87 |
September | 63129884.44 | 7754.89 | 28-SEP-03:02 | 23.90 |
October | 92918542.10 | 7926.49 | 27-OCT-03:02 | 23.22 |
November | 0.116198E+09 | 8107.35 | 12-NOV-10:22 | 17.20 |
December | 0.141127E+09 | 11140.39 | 22-DEC-04:02 | 18.80 |
Annual Sum or Average | 0.985680E+09 | |||
Minimum of Months | 51038123.71 | 4610.34 | 12.70 | |
Maximum of Months | 0.141127E+09 | 11140.39 | 31.87 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49888712.97 | 8149.47 | 30-JAN-04:02 | 21.60 |
February | 47377515.77 | 8015.32 | 13-FEB-04:02 | 20.50 |
March | 43210671.12 | 8036.85 | 20-MAR-03:02 | 12.70 |
April | 37190829.70 | 6904.72 | 12-APR-03:02 | 24.90 |
May | 40276540.62 | 7114.11 | 01-MAY-03:02 | 21.27 |
June | 38552795.71 | 7754.21 | 19-JUN-03:02 | 24.40 |
July | 39894468.45 | 7573.93 | 14-JUL-03:02 | 26.70 |
August | 39330455.60 | 7834.43 | 28-AUG-03:02 | 25.68 |
September | 41386947.55 | 7905.78 | 29-SEP-03:02 | 26.42 |
October | 39329684.93 | 8092.59 | 02-OCT-03:02 | 26.70 |
November | 38183951.79 | 7640.57 | 13-NOV-04:03 | 12.80 |
December | 45656577.68 | 7476.18 | 18-DEC-05:03 | 17.20 |
Annual Sum or Average | 0.500279E+09 | |||
Minimum of Months | 37190829.70 | 6904.72 | 12.70 | |
Maximum of Months | 49888712.97 | 8149.47 | 26.70 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.535459E+09 | 17615.89 | 24-JAN-06:02 | 12.12 |
February | 0.359418E+09 | 18991.30 | 24-FEB-06:03 | 12.62 |
March | 0.369709E+09 | 19277.83 | 15-MAR-05:03 | 12.12 |
April | 92008676.24 | 16319.09 | 19-APR-05:03 | 15.10 |
May | 63498440.01 | 11669.81 | 01-MAY-03:02 | 21.27 |
June | 45604508.39 | 9972.42 | 05-JUN-03:02 | 25.60 |
July | 61878403.05 | 10806.90 | 24-JUL-03:02 | 24.40 |
August | 48720689.69 | 9849.98 | 31-AUG-03:02 | 25.68 |
September | 50867539.61 | 11827.93 | 05-SEP-03:02 | 23.30 |
October | 66477590.96 | 11948.51 | 16-OCT-03:02 | 21.70 |
November | 0.144189E+09 | 16923.42 | 27-NOV-06:03 | 10.00 |
December | 0.435160E+09 | 17356.75 | 20-DEC-06:03 | 13.03 |
Annual Sum or Average | 0.227299E+10 | |||
Minimum of Months | 45604508.39 | 9849.98 | 10.00 | |
Maximum of Months | 0.535459E+09 | 19277.83 | 25.68 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200626E+11 | 20994.62 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.181982E+11 | 20994.62 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.216246E+11 | 20994.62 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.193152E+11 | 20994.62 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.208436E+11 | 20994.62 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.207428E+11 | 20994.62 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.194159E+11 | 20994.62 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.216246E+11 | 20994.62 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.193152E+11 | 20994.62 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.200626E+11 | 20994.62 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.198274E+11 | 20994.62 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.194159E+11 | 20994.62 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.240449E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.181982E+11 | 20994.62 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.216246E+11 | 20994.62 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162163E+10 | 2083.29 | 04-JAN-16:00 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.143046E+10 | 1869.85 | 07-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166195E+10 | 1954.99 | 15-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146886E+10 | 1821.32 | 12-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.156260E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.155181E+10 | 2070.14 | 15-JUN-07:30 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.145115E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.162845E+10 | 1820.11 | 28-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.148095E+10 | 2367.39 | 27-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.156633E+10 | 2093.66 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.158202E+10 | 2037.04 | 29-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.158375E+10 | 2250.90 | 15-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.185899E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.143046E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166195E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103645E+10 | 1354.34 | 04-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.920460E+09 | 1200.97 | 13-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.106643E+10 | 1064.34 | 02-MAR-16:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.948446E+09 | 1074.68 | 12-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101072E+10 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.100484E+10 | 1313.84 | 15-JUN-07:30 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.938916E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.105097E+10 | 1083.53 | 28-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.955542E+09 | 1525.64 | 27-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100435E+10 | 1304.79 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.101630E+10 | 1336.23 | 29-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.101629E+10 | 1452.08 | 15-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.119697E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.920460E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.106643E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.157751E+10 | 2021.75 | 04-JAN-16:00 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.141124E+10 | 1634.09 | 08-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.165113E+10 | 1874.91 | 15-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.147136E+10 | 1835.83 | 12-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.157130E+10 | 1616.73 | 25-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.156633E+10 | 2106.18 | 15-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.145951E+10 | 1601.21 | 05-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.163251E+10 | 1856.67 | 28-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147991E+10 | 2367.44 | 27-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.155009E+10 | 2056.04 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.155415E+10 | 1925.02 | 29-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.154692E+10 | 2243.69 | 15-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.184720E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.141124E+10 | 1601.21 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.165113E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103023E+10 | 1282.56 | 04-JAN-16:00 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.915515E+09 | 1220.34 | 07-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107267E+10 | 1296.07 | 15-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.947102E+09 | 1240.80 | 12-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.101167E+10 | 1119.36 | 25-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.100734E+10 | 1377.99 | 15-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.939570E+09 | 1110.83 | 05-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.105370E+10 | 1245.48 | 28-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.957131E+09 | 1525.64 | 27-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.101019E+10 | 1362.07 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.100891E+10 | 1273.53 | 24-NOV-08:09 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.100308E+10 | 1443.51 | 15-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119571E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.915515E+09 | 1110.83 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107267E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162462E+10 | 2091.49 | 04-JAN-16:00 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.143225E+10 | 1879.22 | 07-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166351E+10 | 1965.66 | 15-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146933E+10 | 1837.23 | 12-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.156311E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.155239E+10 | 2078.77 | 15-JUN-07:30 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.145159E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.162924E+10 | 1836.11 | 28-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.148205E+10 | 2367.39 | 27-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.156774E+10 | 2101.60 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.158409E+10 | 2046.64 | 29-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.158677E+10 | 2254.31 | 15-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.186067E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.143225E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166351E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103682E+10 | 1355.70 | 04-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.920791E+09 | 1203.40 | 13-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.106688E+10 | 1069.73 | 02-MAR-16:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.948687E+09 | 1083.25 | 12-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101093E+10 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.100500E+10 | 1315.76 | 15-JUN-07:30 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.939128E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.105118E+10 | 1091.39 | 28-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.955865E+09 | 1525.64 | 27-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100463E+10 | 1307.72 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.101688E+10 | 1337.85 | 29-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.101678E+10 | 1452.63 | 15-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.119736E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.920791E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.106688E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.157809E+10 | 2032.82 | 04-JAN-16:00 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.141179E+10 | 1656.83 | 08-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.165195E+10 | 1885.97 | 15-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.147185E+10 | 1851.14 | 12-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.157216E+10 | 1637.64 | 25-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.156739E+10 | 2113.43 | 15-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.146040E+10 | 1622.37 | 05-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.163323E+10 | 1871.23 | 28-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148048E+10 | 2367.44 | 27-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.154935E+10 | 2065.68 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.155583E+10 | 1940.10 | 29-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.154796E+10 | 2247.46 | 15-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.184805E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.141179E+10 | 1622.37 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.165195E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103070E+10 | 1285.97 | 04-JAN-16:00 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.915980E+09 | 1223.05 | 07-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107312E+10 | 1300.32 | 15-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.947513E+09 | 1242.90 | 12-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.101201E+10 | 1122.34 | 25-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.100773E+10 | 1379.07 | 15-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.939936E+09 | 1113.90 | 05-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.105396E+10 | 1247.55 | 28-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.957446E+09 | 1525.64 | 27-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.101072E+10 | 1363.33 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.100940E+10 | 1275.45 | 24-NOV-08:09 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.100344E+10 | 1444.31 | 15-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119620E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.915980E+09 | 1113.90 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107312E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162465E+10 | 2091.25 | 04-JAN-16:00 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.143226E+10 | 1879.64 | 07-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166359E+10 | 1966.04 | 15-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146933E+10 | 1836.83 | 12-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.156311E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.155239E+10 | 2078.47 | 15-JUN-07:30 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.145158E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.162924E+10 | 1835.72 | 28-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.148204E+10 | 2367.39 | 27-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.156775E+10 | 2101.37 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.158407E+10 | 2046.43 | 29-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.158678E+10 | 2254.19 | 15-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.186068E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.143226E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166359E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103684E+10 | 1355.55 | 04-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.920801E+09 | 1203.21 | 13-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.106689E+10 | 1070.11 | 02-MAR-16:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.948694E+09 | 1083.11 | 12-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101093E+10 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.100500E+10 | 1315.59 | 15-JUN-07:30 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.939125E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.105118E+10 | 1091.25 | 28-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.955862E+09 | 1525.64 | 27-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100464E+10 | 1307.62 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.101688E+10 | 1337.71 | 29-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.101684E+10 | 1452.56 | 15-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.119737E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.920801E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.106689E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.157810E+10 | 2032.60 | 04-JAN-16:00 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.141179E+10 | 1656.43 | 08-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.165196E+10 | 1886.43 | 15-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.147185E+10 | 1850.74 | 12-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.157216E+10 | 1637.08 | 25-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.156739E+10 | 2113.22 | 15-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.146040E+10 | 1621.82 | 05-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.163323E+10 | 1870.83 | 28-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148048E+10 | 2367.44 | 27-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.154935E+10 | 2065.46 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.155583E+10 | 1939.94 | 29-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.154796E+10 | 2247.35 | 15-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.184805E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.141179E+10 | 1621.82 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.165196E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103078E+10 | 1285.88 | 04-JAN-16:00 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.915991E+09 | 1223.40 | 07-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107315E+10 | 1300.62 | 15-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.947521E+09 | 1242.65 | 12-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.101201E+10 | 1121.99 | 25-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.100768E+10 | 1378.94 | 15-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.939937E+09 | 1113.56 | 05-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.105396E+10 | 1247.30 | 28-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.957446E+09 | 1525.64 | 27-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.101073E+10 | 1363.18 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.100942E+10 | 1275.21 | 24-NOV-08:09 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.100344E+10 | 1444.25 | 15-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119621E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.915991E+09 | 1113.56 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107315E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.565679E+10 | 5919.59 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.513113E+10 | 5919.59 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.609720E+10 | 5919.59 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.544605E+10 | 5919.59 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.587700E+10 | 5919.59 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.584858E+10 | 5919.59 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.547447E+10 | 5919.59 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.609720E+10 | 5919.59 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.544605E+10 | 5919.59 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.565679E+10 | 5919.59 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.559049E+10 | 5919.59 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.547447E+10 | 5919.59 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.677962E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.513113E+10 | 5919.59 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.609720E+10 | 5919.59 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.208436E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.207428E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.198274E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.240449E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.162163E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6123138.86 | 0.180269E+09 |
February | 0.136985E+10 | 0.143046E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11717083.32 | 0.241733E+09 |
March | 0.163685E+10 | 0.166195E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14245388.12 | 0.199474E+09 |
April | 0.145243E+10 | 0.146886E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32403250.87 | 70349861.98 |
May | 0.157338E+10 | 0.156260E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79346392.09 | 30369441.89 |
June | 0.156900E+10 | 0.155181E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100017E+09 | 5702849.73 |
July | 0.145680E+10 | 0.145115E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91728969.64 | 5242012.97 |
August | 0.163685E+10 | 0.162845E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110297E+09 | 2730869.58 |
September | 0.145243E+10 | 0.148095E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99852380.99 | 8620495.68 |
October | 0.150991E+10 | 0.156633E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66632226.39 | 16823735.18 |
November | 0.149516E+10 | 0.158202E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30794425.42 | 0.139719E+09 |
December | 0.145680E+10 | 0.158375E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9697895.39 | 0.174978E+09 |
Annual Sum or Average | 0.181194E+11 | 0.185899E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652856E+09 | 0.107601E+10 |
Minimum of Months | 0.136985E+10 | 0.143046E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6123138.86 | 2730869.58 |
Maximum of Months | 0.163685E+10 | 0.166195E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110297E+09 | 0.241733E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103645E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4124948.71 | 0.119525E+09 |
February | 0.882782E+09 | 0.920460E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8324027.50 | 0.155617E+09 |
March | 0.105485E+10 | 0.106643E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10617328.23 | 0.120221E+09 |
April | 0.936002E+09 | 0.948446E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23498046.10 | 35321704.92 |
May | 0.101394E+10 | 0.101072E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57393392.04 | 17376255.92 |
June | 0.101113E+10 | 0.100484E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73985579.90 | 2280954.82 |
July | 0.938820E+09 | 0.938916E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66903065.51 | 2135996.91 |
August | 0.105485E+10 | 0.105097E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83775310.08 | 774824.43 |
September | 0.936002E+09 | 0.955542E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68959784.84 | 4876948.39 |
October | 0.973041E+09 | 0.100435E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49074975.62 | 8133693.52 |
November | 0.963541E+09 | 0.101630E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25460711.29 | 86791017.08 |
December | 0.938820E+09 | 0.101629E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8487404.65 | 0.103519E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119697E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480605E+09 | 0.656573E+09 |
Minimum of Months | 0.882782E+09 | 0.920460E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4124948.71 | 774824.43 |
Maximum of Months | 0.105485E+10 | 0.106643E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83775310.08 | 0.155617E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.157751E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4319595.54 | 0.200625E+09 |
February | 0.136988E+10 | 0.141124E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9437425.95 | 0.265551E+09 |
March | 0.163688E+10 | 0.165113E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12425546.55 | 0.214639E+09 |
April | 0.145246E+10 | 0.147136E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28075474.88 | 75548136.09 |
May | 0.157341E+10 | 0.157130E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79304710.46 | 30326249.21 |
June | 0.156904E+10 | 0.156633E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101300E+09 | 5857334.28 |
July | 0.145684E+10 | 0.145951E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92409109.58 | 5201443.87 |
August | 0.163688E+10 | 0.163251E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108293E+09 | 2932687.59 |
September | 0.145246E+10 | 0.147991E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91477521.57 | 9953045.58 |
October | 0.150994E+10 | 0.155009E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55006984.30 | 22908197.84 |
November | 0.149520E+10 | 0.155415E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23929935.02 | 0.159654E+09 |
December | 0.145684E+10 | 0.154692E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6198109.40 | 0.192280E+09 |
Annual Sum or Average | 0.181198E+11 | 0.184720E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612177E+09 | 0.118548E+10 |
Minimum of Months | 0.136988E+10 | 0.141124E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4319595.54 | 2932687.59 |
Maximum of Months | 0.163688E+10 | 0.165113E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108293E+09 | 0.265551E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103023E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4080141.15 | 0.132173E+09 |
February | 0.882782E+09 | 0.915515E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6686362.02 | 0.191782E+09 |
March | 0.105485E+10 | 0.107267E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8610346.97 | 0.167441E+09 |
April | 0.936002E+09 | 0.947102E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17373494.64 | 71601843.57 |
May | 0.101394E+10 | 0.101167E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51656063.43 | 29050243.26 |
June | 0.101113E+10 | 0.100734E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62438671.91 | 6174989.32 |
July | 0.938820E+09 | 0.939570E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56301221.76 | 5707514.35 |
August | 0.105485E+10 | 0.105370E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62729753.82 | 3928023.92 |
September | 0.936002E+09 | 0.957131E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62779410.49 | 7626064.08 |
October | 0.973041E+09 | 0.101019E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39904205.44 | 18075916.46 |
November | 0.963541E+09 | 0.100891E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17170538.80 | 0.114537E+09 |
December | 0.938820E+09 | 0.100308E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4931398.35 | 0.142716E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119571E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394662E+09 | 0.890813E+09 |
Minimum of Months | 0.882782E+09 | 0.915515E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4080141.15 | 3928023.92 |
Maximum of Months | 0.105485E+10 | 0.107267E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62779410.49 | 0.191782E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.162462E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17282432.62 | 0.372678E+09 |
February | 0.136985E+10 | 0.143225E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29890400.30 | 0.495517E+09 |
March | 0.163685E+10 | 0.166351E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31898501.43 | 0.452432E+09 |
April | 0.145243E+10 | 0.146933E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74931208.35 | 0.200900E+09 |
May | 0.157338E+10 | 0.156311E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172182E+09 | 86073897.86 |
June | 0.156900E+10 | 0.155239E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205664E+09 | 26249892.18 |
July | 0.145680E+10 | 0.145159E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198888E+09 | 23376827.77 |
August | 0.163685E+10 | 0.162924E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232714E+09 | 12391129.87 |
September | 0.145243E+10 | 0.148205E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217297E+09 | 24988817.00 |
October | 0.150991E+10 | 0.156774E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143528E+09 | 53897910.80 |
November | 0.149516E+10 | 0.158409E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64079197.23 | 0.303914E+09 |
December | 0.145680E+10 | 0.158677E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24111925.79 | 0.375525E+09 |
Annual Sum or Average | 0.181194E+11 | 0.186067E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141247E+10 | 0.242794E+10 |
Minimum of Months | 0.136985E+10 | 0.143225E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17282432.62 | 12391129.87 |
Maximum of Months | 0.163685E+10 | 0.166351E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232714E+09 | 0.495517E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.103682E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10060693.31 | 0.258600E+09 |
February | 0.649041E+09 | 0.920791E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19357036.62 | 0.342817E+09 |
March | 0.773965E+09 | 0.106688E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21405529.90 | 0.312380E+09 |
April | 0.688021E+09 | 0.948687E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45385571.60 | 0.139476E+09 |
May | 0.744847E+09 | 0.101093E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119481E+09 | 58618193.88 |
June | 0.742030E+09 | 0.100500E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140784E+09 | 17987724.47 |
July | 0.690839E+09 | 0.939128E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134610E+09 | 16380126.18 |
August | 0.773965E+09 | 0.105118E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158665E+09 | 7941312.78 |
September | 0.688021E+09 | 0.955865E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144938E+09 | 17304424.68 |
October | 0.715730E+09 | 0.100463E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96269462.34 | 37688741.02 |
November | 0.708685E+09 | 0.101688E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45150777.22 | 0.212848E+09 |
December | 0.690839E+09 | 0.101678E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17679855.48 | 0.248697E+09 |
Annual Sum or Average | 0.858171E+10 | 0.119736E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953788E+09 | 0.167074E+10 |
Minimum of Months | 0.649041E+09 | 0.920791E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10060693.31 | 7941312.78 |
Maximum of Months | 0.773965E+09 | 0.106688E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158665E+09 | 0.342817E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.157809E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8806177.41 | 0.459510E+09 |
February | 0.136988E+10 | 0.141179E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20037367.27 | 0.600139E+09 |
March | 0.163688E+10 | 0.165195E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26472139.50 | 0.517152E+09 |
April | 0.145246E+10 | 0.147185E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63130117.40 | 0.220342E+09 |
May | 0.157341E+10 | 0.157216E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172862E+09 | 85794503.85 |
June | 0.156904E+10 | 0.156739E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210230E+09 | 25231293.44 |
July | 0.145684E+10 | 0.146040E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201668E+09 | 22518943.66 |
August | 0.163688E+10 | 0.163323E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226730E+09 | 13026601.88 |
September | 0.145246E+10 | 0.148048E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197695E+09 | 29502007.17 |
October | 0.150994E+10 | 0.154935E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115470E+09 | 76495809.54 |
November | 0.149520E+10 | 0.155583E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47706894.13 | 0.385324E+09 |
December | 0.145684E+10 | 0.154796E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13002950.92 | 0.458435E+09 |
Annual Sum or Average | 0.181198E+11 | 0.184805E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130381E+10 | 0.289347E+10 |
Minimum of Months | 0.136988E+10 | 0.141179E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8806177.41 | 13026601.88 |
Maximum of Months | 0.163688E+10 | 0.165195E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226730E+09 | 0.600139E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103070E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12137950.60 | 0.260363E+09 |
February | 0.882782E+09 | 0.915980E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17033869.86 | 0.364383E+09 |
March | 0.105485E+10 | 0.107312E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20645492.63 | 0.348335E+09 |
April | 0.936002E+09 | 0.947513E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44011685.74 | 0.172007E+09 |
May | 0.101394E+10 | 0.101201E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114067E+09 | 74459473.68 |
June | 0.101113E+10 | 0.100773E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134350E+09 | 21596137.56 |
July | 0.938820E+09 | 0.939936E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130555E+09 | 20092058.62 |
August | 0.105485E+10 | 0.105396E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146707E+09 | 11080370.18 |
September | 0.936002E+09 | 0.957446E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138278E+09 | 20040988.30 |
October | 0.973041E+09 | 0.101072E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91017399.03 | 48018162.91 |
November | 0.963541E+09 | 0.100940E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42006232.50 | 0.221917E+09 |
December | 0.938820E+09 | 0.100344E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15151137.57 | 0.274105E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119620E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905960E+09 | 0.183640E+10 |
Minimum of Months | 0.882782E+09 | 0.915980E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12137950.60 | 11080370.18 |
Maximum of Months | 0.105485E+10 | 0.107312E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146707E+09 | 0.364383E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.162465E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23052586.14 | 0.416000E+09 |
February | 0.136985E+10 | 0.143226E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35564968.78 | 0.562607E+09 |
March | 0.163685E+10 | 0.166359E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36083211.47 | 0.533892E+09 |
April | 0.145243E+10 | 0.146933E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85057491.31 | 0.249192E+09 |
May | 0.157338E+10 | 0.156311E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203350E+09 | 0.113738E+09 |
June | 0.156900E+10 | 0.155239E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246162E+09 | 35445207.67 |
July | 0.145680E+10 | 0.145158E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233865E+09 | 31223558.17 |
August | 0.163685E+10 | 0.162924E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277978E+09 | 16513336.40 |
September | 0.145243E+10 | 0.148204E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257551E+09 | 32909745.39 |
October | 0.150991E+10 | 0.156775E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168616E+09 | 67946740.92 |
November | 0.149516E+10 | 0.158407E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75301708.69 | 0.345113E+09 |
December | 0.145680E+10 | 0.158678E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29167489.99 | 0.426129E+09 |
Annual Sum or Average | 0.181194E+11 | 0.186068E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167175E+10 | 0.283071E+10 |
Minimum of Months | 0.136985E+10 | 0.143226E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23052586.14 | 16513336.40 |
Maximum of Months | 0.163685E+10 | 0.166359E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277978E+09 | 0.562607E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103684E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11736706.02 | 0.299278E+09 |
February | 0.882782E+09 | 0.920801E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21448222.63 | 0.399987E+09 |
March | 0.105485E+10 | 0.106689E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23543438.18 | 0.380165E+09 |
April | 0.936002E+09 | 0.948694E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50143077.76 | 0.177534E+09 |
May | 0.101394E+10 | 0.101093E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139080E+09 | 78124211.24 |
June | 0.101113E+10 | 0.100500E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168574E+09 | 23911921.64 |
July | 0.938820E+09 | 0.939125E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157270E+09 | 21589541.51 |
August | 0.105485E+10 | 0.105118E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188522E+09 | 10771938.99 |
September | 0.936002E+09 | 0.955862E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171396E+09 | 23135084.81 |
October | 0.973041E+09 | 0.100464E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111607E+09 | 48743822.62 |
November | 0.963541E+09 | 0.101688E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51510468.26 | 0.248807E+09 |
December | 0.938820E+09 | 0.101684E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20107514.50 | 0.290675E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119737E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111494E+10 | 0.200272E+10 |
Minimum of Months | 0.882782E+09 | 0.920801E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11736706.02 | 10771938.99 |
Maximum of Months | 0.105485E+10 | 0.106689E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188522E+09 | 0.399987E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.157810E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10811587.51 | 0.536379E+09 |
February | 0.136988E+10 | 0.141179E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23979798.00 | 0.704764E+09 |
March | 0.163688E+10 | 0.165196E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30686276.44 | 0.623474E+09 |
April | 0.145246E+10 | 0.147185E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73080028.45 | 0.275714E+09 |
May | 0.157341E+10 | 0.157216E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205175E+09 | 0.112451E+09 |
June | 0.156904E+10 | 0.156739E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252231E+09 | 33948599.78 |
July | 0.145684E+10 | 0.146040E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238149E+09 | 29769075.85 |
August | 0.163688E+10 | 0.163323E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272569E+09 | 17228562.10 |
September | 0.145246E+10 | 0.148048E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237968E+09 | 38616266.37 |
October | 0.150994E+10 | 0.154935E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139055E+09 | 98265844.27 |
November | 0.149520E+10 | 0.155583E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57572123.06 | 0.455758E+09 |
December | 0.145684E+10 | 0.154796E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15660063.51 | 0.541797E+09 |
Annual Sum or Average | 0.181198E+11 | 0.184805E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155694E+10 | 0.346817E+10 |
Minimum of Months | 0.136988E+10 | 0.141179E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10811587.51 | 17228562.10 |
Maximum of Months | 0.163688E+10 | 0.165196E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272569E+09 | 0.704764E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103078E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15668807.32 | 0.300078E+09 |
February | 0.882782E+09 | 0.915991E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20887386.28 | 0.427081E+09 |
March | 0.105485E+10 | 0.107315E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24346832.83 | 0.421125E+09 |
April | 0.936002E+09 | 0.947521E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52175140.18 | 0.214337E+09 |
May | 0.101394E+10 | 0.101201E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137753E+09 | 95505796.78 |
June | 0.101113E+10 | 0.100768E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165004E+09 | 27331993.65 |
July | 0.938820E+09 | 0.939937E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157149E+09 | 24892834.50 |
August | 0.105485E+10 | 0.105396E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178362E+09 | 14157606.82 |
September | 0.936002E+09 | 0.957446E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168397E+09 | 25746745.87 |
October | 0.973041E+09 | 0.101073E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109901E+09 | 60148421.40 |
November | 0.963541E+09 | 0.100942E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50648821.38 | 0.259230E+09 |
December | 0.938820E+09 | 0.100344E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18537629.37 | 0.320305E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119621E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109883E+10 | 0.218994E+10 |
Minimum of Months | 0.882782E+09 | 0.915991E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15668807.32 | 14157606.82 |
Maximum of Months | 0.105485E+10 | 0.107315E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178362E+09 | 0.427081E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.565679E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.513113E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.609720E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.544605E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.587700E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.584858E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.547447E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.609720E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.544605E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.565679E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.559049E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.547447E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.677962E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.513113E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.609720E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6339370.55 | 0.400070E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12791135.85 | 0.536049E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18261161.79 | 0.460405E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47664027.03 | 0.184076E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133224E+09 | 62535628.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176706E+09 | 12802682.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164815E+09 | 13846475.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191180E+09 | 8984688.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176919E+09 | 20351278.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104877E+09 | 44015743.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40137367.80 | 0.320095E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12649434.37 | 0.399716E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108556E+10 | 0.246295E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6339370.55 | 8984688.09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191180E+09 | 0.536049E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13637520.29 | 0.686472E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25405245.90 | 0.908081E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32679001.57 | 0.801415E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87764622.30 | 0.335812E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236597E+09 | 0.113772E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307562E+09 | 27484341.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296482E+09 | 27506578.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340471E+09 | 17877252.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314531E+09 | 37215972.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187194E+09 | 82322326.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72149926.35 | 0.550697E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25104994.74 | 0.679768E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193958E+10 | 0.426842E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13637520.29 | 17877252.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340471E+09 | 0.908081E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7602159.99 | 0.698094E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10922989.08 | 0.939330E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13011232.03 | 0.880048E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50916818.99 | 0.403927E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198293E+09 | 0.145524E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291495E+09 | 44142020.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261455E+09 | 39815473.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331439E+09 | 25223017.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287057E+09 | 43583729.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160580E+09 | 87837829.21 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55742390.05 | 0.567728E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12805502.25 | 0.714452E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168132E+10 | 0.458971E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7602159.99 | 25223017.38 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331439E+09 | 0.939330E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 20994.62 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 20994.62 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 20994.62 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 20994.62 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 20994.62 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 20994.62 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 20994.62 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 20994.62 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 20994.62 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 20994.62 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 20994.62 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 20994.62 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2083.29 | 04-JAN-16:00 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.07 | 15-JAN-14:02 | 504.87 | 24-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1869.85 | 07-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.34 | 20-FEB-15:30 | 853.53 | 04-FEB-05:00 |
March | 2010.79 | 01-MAR-10:09 | 1954.99 | 15-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 124.12 | 05-MAR-14:15 | 831.12 | 16-MAR-02:00 |
April | 2010.79 | 03-APR-09:09 | 1821.32 | 12-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.58 | 15-APR-17:01 | 261.36 | 18-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.03 | 29-MAY-16:00 | 162.05 | 08-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 2070.14 | 15-JUN-07:30 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.16 | 17-JUN-17:50 | 140.71 | 18-JUN-20:10 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.27 | 30-JUL-16:00 | 123.38 | 02-JUL-16:00 |
August | 2010.79 | 01-AUG-09:09 | 1820.11 | 28-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.89 | 13-AUG-13:00 | 171.76 | 14-AUG-03:10 |
September | 2010.79 | 01-SEP-09:09 | 2367.39 | 27-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 301.59 | 17-SEP-13:50 | 88.33 | 19-SEP-23:20 |
October | 2010.79 | 02-OCT-09:09 | 2093.66 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.71 | 29-OCT-14:00 | 144.91 | 16-OCT-05:00 |
November | 2010.79 | 01-NOV-09:09 | 2037.04 | 29-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.64 | 22-NOV-22:02 | 828.87 | 11-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 2250.90 | 15-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 200.63 | 10-DEC-14:20 | 787.62 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 87.34 | 88.33 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 404.03 | 853.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1354.34 | 04-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 64.37 | 15-JAN-14:02 | 334.24 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1200.97 | 13-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.50 | 19-FEB-16:10 | 559.86 | 04-FEB-05:00 |
March | 1295.83 | 01-MAR-10:09 | 1064.34 | 02-MAR-16:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.51 | 05-MAR-14:15 | 551.41 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 1074.68 | 12-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.86 | 15-APR-17:01 | 167.97 | 18-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.56 | 29-MAY-16:00 | 109.55 | 08-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 1313.84 | 15-JUN-07:30 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.05 | 17-JUN-17:50 | 75.65 | 18-JUN-20:10 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.59 | 30-JUL-16:00 | 80.00 | 02-JUL-16:00 |
August | 1295.83 | 01-AUG-09:09 | 1083.53 | 28-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.38 | 13-AUG-13:00 | 88.52 | 14-AUG-03:10 |
September | 1295.83 | 01-SEP-09:09 | 1525.64 | 27-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.62 | 17-SEP-16:50 | 56.57 | 19-SEP-23:20 |
October | 1295.83 | 02-OCT-09:09 | 1304.79 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.19 | 29-OCT-14:00 | 86.04 | 16-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1336.23 | 29-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.51 | 23-NOV-12:10 | 613.87 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 1452.08 | 15-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 173.07 | 10-DEC-15:00 | 511.88 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 64.37 | 56.57 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 292.56 | 613.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2021.75 | 04-JAN-16:00 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.47 | 07-JAN-13:00 | 527.44 | 24-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1634.09 | 08-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.56 | 02-FEB-14:00 | 855.80 | 04-FEB-05:00 |
March | 2010.83 | 01-MAR-10:09 | 1874.91 | 15-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.90 | 05-MAR-14:20 | 850.86 | 16-MAR-02:00 |
April | 2010.83 | 03-APR-09:09 | 1835.83 | 12-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.87 | 15-APR-17:01 | 266.57 | 18-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1616.73 | 25-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.26 | 29-MAY-16:00 | 163.69 | 08-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 2106.18 | 15-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.61 | 17-JUN-17:50 | 148.57 | 18-JUN-20:10 |
July | 2010.83 | 03-JUL-09:09 | 1601.21 | 05-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.85 | 30-JUL-16:00 | 123.86 | 02-JUL-16:00 |
August | 2010.83 | 01-AUG-09:09 | 1856.67 | 28-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.99 | 13-AUG-12:53 | 175.43 | 14-AUG-03:10 |
September | 2010.83 | 01-SEP-09:09 | 2367.44 | 27-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.33 | 17-SEP-16:08 | 102.07 | 19-SEP-23:20 |
October | 2010.83 | 02-OCT-09:09 | 2056.04 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.86 | 29-OCT-13:55 | 165.77 | 16-OCT-05:00 |
November | 2010.83 | 01-NOV-09:09 | 1925.02 | 29-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.92 | 22-NOV-22:02 | 915.29 | 11-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 2243.69 | 15-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 129.18 | 10-DEC-14:15 | 809.26 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1601.21 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 58.47 | 102.07 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 405.26 | 915.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1282.56 | 04-JAN-16:00 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.41 | 29-JAN-12:00 | 371.13 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1220.34 | 07-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.04 | 02-FEB-14:00 | 618.63 | 04-FEB-05:00 |
March | 1295.83 | 01-MAR-10:09 | 1296.07 | 15-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.11 | 05-MAR-14:15 | 634.63 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 1240.80 | 12-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.85 | 16-APR-13:06 | 216.45 | 19-APR-00:10 |
May | 1295.83 | 01-MAY-09:09 | 1119.36 | 25-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.04 | 29-MAY-15:56 | 125.38 | 08-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 1377.99 | 15-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.33 | 25-JUN-14:00 | 123.49 | 18-JUN-20:10 |
July | 1295.83 | 03-JUL-09:09 | 1110.83 | 05-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.93 | 30-JUL-16:00 | 99.93 | 02-JUL-16:00 |
August | 1295.83 | 01-AUG-09:09 | 1245.48 | 28-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.23 | 20-AUG-11:48 | 167.31 | 14-AUG-03:10 |
September | 1295.83 | 01-SEP-09:09 | 1525.64 | 27-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.63 | 17-SEP-12:50 | 90.95 | 19-SEP-23:20 |
October | 1295.83 | 02-OCT-09:09 | 1362.07 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.17 | 29-OCT-12:00 | 116.74 | 16-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1273.53 | 24-NOV-08:09 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.77 | 23-NOV-12:10 | 638.97 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 1443.51 | 15-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.60 | 10-DEC-14:15 | 600.65 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1110.83 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 47.04 | 90.95 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 269.04 | 638.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2091.49 | 04-JAN-16:00 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.96 | 15-JAN-14:20 | 1050.16 | 24-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1879.22 | 07-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 296.83 | 20-FEB-15:00 | 1760.20 | 04-FEB-05:00 |
March | 2010.79 | 01-MAR-10:09 | 1965.66 | 15-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 301.03 | 26-MAR-15:00 | 1727.47 | 16-MAR-02:00 |
April | 2010.79 | 03-APR-09:09 | 1837.23 | 12-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 670.92 | 15-APR-17:01 | 588.41 | 18-APR-23:55 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 886.80 | 29-MAY-16:16 | 369.09 | 07-MAY-18:55 |
June | 2010.79 | 01-JUN-09:09 | 2078.77 | 15-JUN-07:30 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 559.81 | 17-JUN-17:40 | 403.73 | 18-JUN-19:53 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 692.53 | 30-JUL-16:00 | 288.41 | 04-JUL-02:53 |
August | 2010.79 | 01-AUG-09:09 | 1836.11 | 28-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 673.58 | 13-AUG-12:40 | 463.86 | 14-AUG-02:55 |
September | 2010.79 | 01-SEP-09:09 | 2367.39 | 27-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 680.06 | 17-SEP-14:00 | 214.38 | 19-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2101.60 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 533.30 | 29-OCT-13:50 | 334.51 | 16-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2046.64 | 29-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.57 | 22-NOV-22:02 | 1695.47 | 11-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 2254.31 | 15-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 508.32 | 10-DEC-14:20 | 1628.06 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 259.57 | 214.38 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 886.80 | 1760.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1355.70 | 04-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 186.06 | 15-JAN-15:00 | 708.66 | 24-JAN-03:00 |
February | 1239.33 | 01-FEB-08:09 | 1203.40 | 13-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.73 | 20-FEB-15:00 | 1173.95 | 04-FEB-05:00 |
March | 1239.33 | 01-MAR-08:09 | 1069.73 | 02-MAR-16:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 232.15 | 05-MAR-14:00 | 1186.23 | 16-MAR-02:00 |
April | 1239.33 | 03-APR-07:10 | 1083.25 | 12-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 454.66 | 15-APR-17:01 | 405.92 | 18-APR-23:55 |
May | 1239.33 | 01-MAY-07:10 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 633.84 | 29-MAY-16:20 | 299.15 | 07-MAY-18:55 |
June | 1239.33 | 01-JUN-07:10 | 1315.76 | 15-JUN-07:30 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 430.36 | 17-JUN-17:40 | 261.20 | 18-JUN-19:53 |
July | 1239.33 | 03-JUL-07:10 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 517.01 | 30-JUL-16:00 | 208.76 | 02-JUL-16:10 |
August | 1239.33 | 01-AUG-07:10 | 1091.39 | 28-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.95 | 13-AUG-13:00 | 303.67 | 14-AUG-02:55 |
September | 1239.33 | 01-SEP-07:10 | 1525.64 | 27-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 503.70 | 17-SEP-14:00 | 155.06 | 19-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 1307.72 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.93 | 29-OCT-13:50 | 227.93 | 16-OCT-03:00 |
November | 1239.33 | 01-NOV-07:10 | 1337.85 | 29-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.80 | 22-NOV-22:02 | 1311.74 | 11-NOV-09:00 |
December | 1239.33 | 01-DEC-08:09 | 1452.63 | 15-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 385.64 | 10-DEC-15:00 | 1088.48 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 180.73 | 155.06 | |||||
Maximum of Months | 1239.33 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 633.84 | 1311.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2032.82 | 04-JAN-16:00 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.66 | 07-JAN-13:00 | 1158.62 | 24-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1656.83 | 08-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.30 | 02-FEB-14:00 | 1854.48 | 04-FEB-05:00 |
March | 2010.83 | 01-MAR-10:09 | 1885.97 | 15-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 262.71 | 05-MAR-14:00 | 1851.06 | 16-MAR-02:00 |
April | 2010.83 | 03-APR-09:09 | 1851.14 | 12-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 632.52 | 15-APR-17:01 | 615.07 | 18-APR-23:55 |
May | 2010.83 | 01-MAY-09:09 | 1637.64 | 25-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 886.87 | 29-MAY-16:16 | 373.19 | 07-MAY-18:55 |
June | 2010.83 | 01-JUN-09:09 | 2113.43 | 15-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 581.90 | 17-JUN-17:03 | 408.17 | 18-JUN-19:53 |
July | 2010.83 | 03-JUL-09:09 | 1622.37 | 05-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 690.85 | 30-JUL-16:00 | 281.68 | 04-JUL-02:53 |
August | 2010.83 | 01-AUG-09:09 | 1871.23 | 28-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 641.57 | 13-AUG-13:00 | 475.30 | 14-AUG-02:55 |
September | 2010.83 | 01-SEP-09:09 | 2367.44 | 27-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 614.70 | 17-SEP-13:56 | 249.04 | 19-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2065.68 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.11 | 29-OCT-13:58 | 402.93 | 16-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1940.10 | 29-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.75 | 22-NOV-22:02 | 1942.03 | 11-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 2247.46 | 15-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 290.55 | 10-DEC-14:15 | 1754.30 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1622.37 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 133.66 | 249.04 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 886.87 | 1942.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1285.97 | 04-JAN-16:00 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 227.83 | 15-JAN-12:20 | 737.79 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1223.05 | 07-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 121.42 | 19-FEB-13:40 | 1204.05 | 04-FEB-05:00 |
March | 1295.83 | 01-MAR-10:09 | 1300.32 | 15-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 233.41 | 05-MAR-14:00 | 1238.06 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 1242.90 | 12-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.51 | 16-APR-13:10 | 443.26 | 18-APR-23:55 |
May | 1295.83 | 01-MAY-09:09 | 1122.34 | 25-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 578.70 | 29-MAY-15:34 | 301.00 | 07-MAY-18:55 |
June | 1295.83 | 01-JUN-09:09 | 1379.07 | 15-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 425.25 | 11-JUN-11:53 | 300.00 | 18-JUN-19:53 |
July | 1295.83 | 03-JUL-09:09 | 1113.90 | 05-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 512.39 | 30-JUL-16:00 | 220.50 | 04-JUL-02:53 |
August | 1295.83 | 01-AUG-09:09 | 1247.55 | 28-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 512.80 | 13-AUG-12:40 | 360.64 | 14-AUG-02:55 |
September | 1295.83 | 01-SEP-09:09 | 1525.64 | 27-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.65 | 17-SEP-13:58 | 189.93 | 19-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1363.33 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.99 | 29-OCT-12:30 | 258.25 | 16-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1275.45 | 24-NOV-08:09 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.22 | 23-NOV-11:53 | 1165.98 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 1444.31 | 15-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 318.60 | 10-DEC-13:40 | 1119.23 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1113.90 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 121.42 | 189.93 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 578.70 | 1238.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2091.25 | 04-JAN-16:00 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 392.35 | 15-JAN-14:10 | 1204.00 | 24-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1879.64 | 07-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 362.31 | 20-FEB-15:00 | 2101.41 | 04-FEB-05:10 |
March | 2010.79 | 01-MAR-10:09 | 1966.04 | 15-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 330.65 | 05-MAR-14:00 | 1939.32 | 16-MAR-02:00 |
April | 2010.79 | 03-APR-09:09 | 1836.83 | 12-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 781.37 | 15-APR-17:01 | 694.98 | 18-APR-23:55 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1097.12 | 29-MAY-16:16 | 495.82 | 07-MAY-18:55 |
June | 2010.79 | 01-JUN-09:09 | 2078.47 | 15-JUN-07:30 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 690.75 | 25-JUN-14:00 | 542.95 | 18-JUN-19:53 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 857.42 | 30-JUL-16:00 | 374.09 | 04-JUL-02:53 |
August | 2010.79 | 01-AUG-09:09 | 1835.72 | 28-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 785.78 | 13-AUG-12:50 | 609.37 | 14-AUG-02:55 |
September | 2010.79 | 01-SEP-09:09 | 2367.39 | 27-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 848.84 | 17-SEP-13:58 | 289.80 | 19-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2101.37 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 599.85 | 29-OCT-13:50 | 416.97 | 16-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2046.43 | 29-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.26 | 19-NOV-11:00 | 1922.07 | 11-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 2254.19 | 15-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 609.54 | 10-DEC-14:30 | 1808.59 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 325.26 | 289.80 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1097.12 | 2101.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1355.55 | 04-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 197.16 | 15-JAN-14:10 | 824.28 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1203.21 | 13-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 210.73 | 19-FEB-16:00 | 1401.00 | 04-FEB-05:08 |
March | 1295.83 | 01-MAR-10:09 | 1070.11 | 02-MAR-16:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 258.64 | 05-MAR-14:00 | 1351.58 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 1083.11 | 12-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 517.00 | 15-APR-17:01 | 484.69 | 18-APR-23:55 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 769.81 | 29-MAY-16:18 | 402.80 | 07-MAY-18:55 |
June | 1295.83 | 01-JUN-09:09 | 1315.59 | 15-JUN-07:30 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 503.33 | 25-JUN-14:00 | 347.83 | 18-JUN-19:53 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 639.48 | 30-JUL-16:00 | 277.97 | 02-JUL-15:30 |
August | 1295.83 | 01-AUG-09:09 | 1091.25 | 28-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 565.41 | 13-AUG-12:30 | 400.44 | 14-AUG-02:55 |
September | 1295.83 | 01-SEP-09:09 | 1525.64 | 27-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 608.47 | 17-SEP-13:58 | 209.48 | 19-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1307.62 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 438.12 | 29-OCT-13:50 | 285.17 | 16-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1337.71 | 29-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.81 | 22-NOV-22:02 | 1504.21 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 1452.56 | 15-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 453.55 | 10-DEC-14:30 | 1226.05 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 197.16 | 209.48 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 769.81 | 1504.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2032.60 | 04-JAN-16:00 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.64 | 07-JAN-13:00 | 1359.60 | 24-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1656.43 | 08-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 195.06 | 02-FEB-14:00 | 2115.69 | 04-FEB-05:04 |
March | 2010.83 | 01-MAR-10:09 | 1886.43 | 15-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 330.03 | 05-MAR-14:00 | 2115.58 | 16-MAR-02:00 |
April | 2010.83 | 03-APR-09:09 | 1850.74 | 12-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 735.72 | 15-APR-17:01 | 732.60 | 18-APR-23:55 |
May | 2010.83 | 01-MAY-09:09 | 1637.08 | 25-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1105.23 | 29-MAY-16:16 | 501.10 | 07-MAY-18:55 |
June | 2010.83 | 01-JUN-09:09 | 2113.22 | 15-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 689.58 | 25-JUN-14:00 | 549.42 | 18-JUN-19:53 |
July | 2010.83 | 03-JUL-09:09 | 1621.82 | 05-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 856.65 | 30-JUL-16:00 | 363.62 | 04-JUL-02:53 |
August | 2010.83 | 01-AUG-09:09 | 1870.83 | 28-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 773.75 | 13-AUG-12:30 | 620.50 | 14-AUG-02:55 |
September | 2010.83 | 01-SEP-09:09 | 2367.44 | 27-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 762.48 | 17-SEP-13:56 | 336.86 | 19-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2065.46 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.43 | 29-OCT-11:46 | 499.02 | 16-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1939.94 | 29-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.57 | 22-NOV-22:02 | 2227.57 | 11-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 2247.35 | 15-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 328.42 | 10-DEC-14:50 | 1996.95 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1621.82 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 161.64 | 336.86 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1105.23 | 2227.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1285.88 | 04-JAN-16:00 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 305.19 | 15-JAN-12:50 | 862.93 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1223.40 | 07-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 150.61 | 20-FEB-13:40 | 1412.25 | 04-FEB-05:04 |
March | 1295.83 | 01-MAR-10:09 | 1300.62 | 15-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 278.54 | 05-MAR-14:00 | 1419.28 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 1242.65 | 12-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.52 | 16-APR-12:52 | 531.90 | 18-APR-23:55 |
May | 1295.83 | 01-MAY-09:09 | 1121.99 | 25-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 708.89 | 29-MAY-15:36 | 380.20 | 07-MAY-18:55 |
June | 1295.83 | 01-JUN-09:09 | 1378.94 | 15-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 506.84 | 11-JUN-11:53 | 388.51 | 18-JUN-19:53 |
July | 1295.83 | 03-JUL-09:09 | 1113.56 | 05-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 645.06 | 30-JUL-16:00 | 284.43 | 04-JUL-02:53 |
August | 1295.83 | 01-AUG-09:09 | 1247.30 | 28-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 600.74 | 13-AUG-12:50 | 462.21 | 14-AUG-02:55 |
September | 1295.83 | 01-SEP-09:09 | 1525.64 | 27-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 591.86 | 17-SEP-13:56 | 254.83 | 19-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1363.18 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 469.27 | 29-OCT-11:50 | 315.97 | 01-OCT-06:53 |
November | 1295.83 | 01-NOV-09:09 | 1275.21 | 24-NOV-08:09 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.85 | 19-NOV-12:20 | 1332.95 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 1444.25 | 15-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 403.77 | 10-DEC-13:50 | 1271.18 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1113.56 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 150.61 | 254.83 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 708.89 | 1419.28 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5919.59 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5919.59 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5919.59 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5919.59 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5919.59 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5919.59 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5919.59 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5919.59 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5919.59 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5919.59 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5919.59 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5919.59 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.77 | 29-JAN-12:20 | 1069.67 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.77 | 02-FEB-14:00 | 1889.31 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.14 | 05-MAR-13:53 | 1815.01 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.18 | 15-APR-17:01 | 562.67 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 784.09 | 29-MAY-16:00 | 299.46 | 25-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.69 | 25-JUN-13:53 | 230.77 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.02 | 30-JUL-15:42 | 206.70 | 02-JUL-16:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 607.28 | 13-AUG-13:00 | 321.38 | 14-AUG-03:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.44 | 17-SEP-13:52 | 143.16 | 19-SEP-23:26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.18 | 29-OCT-14:00 | 316.69 | 16-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.08 | 23-NOV-11:53 | 1701.67 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.06 | 10-DEC-14:42 | 1702.93 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.77 | 143.16 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 784.09 | 1889.31 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.12 | 29-JAN-12:20 | 1832.65 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.80 | 19-FEB-16:00 | 3294.83 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.81 | 05-MAR-14:00 | 3169.05 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 991.52 | 15-APR-17:01 | 1009.30 | 18-APR-23:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1443.31 | 29-MAY-16:00 | 542.36 | 25-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 940.31 | 25-JUN-13:53 | 472.17 | 18-JUN-19:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1157.79 | 30-JUL-15:42 | 389.15 | 04-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1079.05 | 20-AUG-12:00 | 607.70 | 14-AUG-02:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1049.03 | 17-SEP-14:00 | 259.91 | 19-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 804.59 | 29-OCT-14:00 | 560.89 | 16-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.83 | 04-NOV-17:03 | 2960.98 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.09 | 10-DEC-14:42 | 3010.21 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.80 | 259.91 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1443.31 | 3294.83 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.60 | 29-JAN-11:53 | 1908.88 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.37 | 02-FEB-14:00 | 3101.85 | 04-FEB-05:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.31 | 13-MAR-17:00 | 3075.21 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 876.28 | 15-APR-17:01 | 1012.01 | 18-APR-23:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.79 | 29-MAY-16:00 | 727.05 | 07-MAY-18:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 806.26 | 16-JUN-21:02 | 740.16 | 18-JUN-19:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 940.63 | 29-JUL-18:00 | 597.92 | 02-JUL-15:33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841.14 | 20-AUG-11:55 | 810.47 | 14-AUG-02:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.48 | 16-SEP-17:02 | 393.13 | 03-SEP-13:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.80 | 29-OCT-11:30 | 590.42 | 01-OCT-06:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.55 | 22-NOV-22:02 | 3059.99 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.65 | 10-DEC-14:50 | 2836.76 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.37 | 393.13 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.79 | 3101.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 96449.65 | 23-JAN-04:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95738.45 | 27-FEB-04:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93086.82 | 21-MAR-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 90149.02 | 20-APR-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87338.49 | 08-MAY-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80121.06 | 13-JUN-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81173.33 | 06-JUL-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82524.57 | 08-AUG-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81103.64 | 12-SEP-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86538.25 | 18-OCT-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95190.97 | 27-NOV-05:02 | 0.00 | 11664.26 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 93039.92 | 21-DEC-04:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 80121.06 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96449.65 | 0.00 | 11664.26 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 97920.70 | 30-JAN-04:03 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96852.18 | 13-FEB-04:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 97233.12 | 20-MAR-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 87551.13 | 17-APR-05:04 | 8061.19 | 10475.32 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89740.55 | 08-MAY-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83298.79 | 19-JUN-04:23 | 0.00 | 8380.26 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80667.76 | 03-JUL-05:04 | 8061.19 | 10475.32 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 83126.69 | 21-AUG-05:05 | 9673.43 | 12570.39 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 90162.30 | 05-SEP-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90969.60 | 28-OCT-03:02 | 0.00 | 5237.66 | 30214.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94973.98 | 27-NOV-04:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 94831.93 | 27-DEC-04:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 80667.76 | 0.00 | 5237.66 | 30214.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97920.70 | 9673.43 | 12570.39 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 87555.63 | 02-JAN-04:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 89373.23 | 13-FEB-04:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85605.81 | 20-MAR-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84249.68 | 11-APR-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88443.11 | 01-MAY-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83650.21 | 06-JUN-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83693.43 | 06-JUL-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82574.71 | 24-AUG-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85284.89 | 26-SEP-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86287.74 | 16-OCT-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87483.04 | 13-NOV-04:03 | 0.00 | 4190.13 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85440.85 | 26-DEC-04:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 82574.71 | 0.00 | 4190.13 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89373.23 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 85630.17 | 30-JAN-04:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87054.25 | 13-FEB-04:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86376.26 | 27-MAR-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85934.61 | 24-APR-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88904.46 | 01-MAY-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84246.87 | 06-JUN-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84369.13 | 18-JUL-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 83456.31 | 24-AUG-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84863.27 | 05-SEP-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87358.39 | 16-OCT-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87790.32 | 24-NOV-04:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 86421.16 | 26-DEC-04:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 83456.31 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88904.46 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13760.18 | 30-JAN-04:02 | 0.00 | 789.17 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.73 |
February | 12450.45 | 10-FEB-06:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.01 |
March | 12408.44 | 04-MAR-06:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 |
April | 12808.50 | 17-APR-05:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.80 |
May | 14246.91 | 08-MAY-03:02 | 0.00 | 657.64 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.53 |
June | 12806.35 | 26-JUN-04:53 | 0.00 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 0.00 |
July | 15383.90 | 16-JUL-16:12 | 607.30 | 484.79 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 96.51 | 0.00 |
August | 13505.96 | 21-AUG-05:02 | 1214.60 | 1578.34 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 | 0.00 |
September | 13658.46 | 21-SEP-03:02 | 0.00 | 789.17 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 |
October | 13353.20 | 02-OCT-04:23 | 0.00 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 51.06 | 0.00 |
November | 13014.89 | 29-NOV-06:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 | 0.00 |
December | 12710.31 | 26-DEC-06:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12408.44 | 0.00 | 484.79 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15383.90 | 1214.60 | 1578.34 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 96.51 | 118.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15199.07 | 01-JAN-10:23 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.23 |
February | 10815.50 | 20-FEB-09:23 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.02 |
March | 9138.13 | 27-MAR-08:40 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 |
April | 16605.91 | 16-APR-09:42 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 |
May | 15139.40 | 07-MAY-09:43 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 26.09 | 0.00 |
June | 13528.63 | 04-JUN-09:13 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 51.98 | 0.00 |
July | 16469.76 | 04-JUL-10:02 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 59.53 | 0.00 |
August | 11842.68 | 21-AUG-05:02 | 782.73 | 1017.14 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 | 0.00 |
September | 11832.03 | 24-SEP-11:32 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 115.05 | 0.00 |
October | 16169.16 | 09-OCT-08:43 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 0.00 |
November | 8338.08 | 07-NOV-09:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6774.39 | 08-DEC-09:50 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 9.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6774.39 | 260.91 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16605.91 | 1239.33 | 1017.14 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 115.05 | 210.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18238.27 | 15-JAN-13:52 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.76 |
February | 18809.97 | 20-FEB-14:02 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.55 |
March | 16957.63 | 26-MAR-12:43 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 | 0.00 |
April | 17150.17 | 16-APR-13:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 121.86 | 0.00 |
May | 14156.13 | 08-MAY-03:02 | 0.00 | 657.65 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.41 |
June | 13377.51 | 19-JUN-04:23 | 0.00 | 1052.25 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 |
July | 15374.15 | 16-JUL-15:32 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 130.89 | 0.00 |
August | 16898.53 | 06-AUG-13:12 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 136.01 | 0.00 |
September | 17342.24 | 24-SEP-11:32 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 155.03 | 0.00 |
October | 18002.61 | 09-OCT-14:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 49.04 | 0.00 |
November | 18410.31 | 19-NOV-12:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.45 |
December | 18853.23 | 10-DEC-12:52 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13377.51 | 0.00 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18853.23 | 607.31 | 1052.25 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 155.03 | 153.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16831.66 | 30-JAN-04:02 | 0.00 | 508.57 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.13 |
February | 20032.45 | 20-FEB-15:22 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 |
March | 21090.59 | 12-MAR-16:42 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.04 |
April | 21731.07 | 02-APR-16:42 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 |
May | 20263.08 | 29-MAY-16:32 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 218.47 | 0.00 |
June | 19719.25 | 10-JUN-17:05 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 | 0.00 |
July | 22472.62 | 16-JUL-16:12 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 39.98 | 0.00 |
August | 21992.07 | 20-AUG-16:22 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 68.79 | 0.00 |
September | 19355.41 | 10-SEP-15:22 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 111.76 | 0.00 |
October | 21796.16 | 09-OCT-16:02 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 25.31 | 0.00 |
November | 21359.27 | 26-NOV-15:22 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.72 |
December | 22736.30 | 10-DEC-15:32 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 13.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16831.66 | 0.00 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22736.30 | 391.37 | 508.57 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 218.47 | 145.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9803.75 | 07-JAN-06:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.90 |
February | 11096.62 | 11-FEB-06:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 |
March | 11580.98 | 30-MAR-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.44 |
April | 11844.58 | 24-APR-05:03 | 607.30 | 789.17 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 |
May | 13869.05 | 15-MAY-03:02 | 0.00 | 657.64 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.87 |
June | 14080.21 | 26-JUN-03:02 | 0.00 | 657.64 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 |
July | 15975.38 | 04-JUL-16:31 | 708.51 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 258.07 | 0.00 |
August | 13954.81 | 19-AUG-03:02 | 0.00 | 657.64 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 111.79 | 0.00 |
September | 14130.80 | 09-SEP-03:02 | 0.00 | 657.64 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 67.64 | 0.00 |
October | 13078.21 | 03-OCT-03:02 | 0.00 | 657.64 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 66.75 | 0.00 |
November | 11985.81 | 29-NOV-06:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 | 0.00 |
December | 12408.73 | 01-DEC-06:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9803.75 | 0.00 | 565.58 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15975.38 | 1012.16 | 1315.28 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 258.07 | 32.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13763.88 | 01-JAN-10:13 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.07 |
February | 8919.28 | 26-FEB-09:53 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.09 |
March | 8796.99 | 27-MAR-08:40 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 |
April | 17384.30 | 16-APR-09:42 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.40 |
May | 16566.06 | 07-MAY-10:23 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 83.73 | 0.00 |
June | 16513.29 | 04-JUN-09:13 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 115.04 | 0.00 |
July | 17556.90 | 04-JUL-09:12 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 46.59 | 0.00 |
August | 12387.33 | 13-AUG-09:32 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 122.27 | 0.00 |
September | 16391.46 | 17-SEP-10:32 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 156.44 | 0.00 |
October | 15917.79 | 09-OCT-10:53 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 178.22 | 0.00 |
November | 9964.91 | 29-NOV-06:02 | 652.28 | 847.62 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 12.71 | 0.00 |
December | 6903.51 | 01-DEC-06:03 | 521.82 | 678.09 | 2607.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6903.51 | 260.91 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17556.90 | 1239.33 | 937.20 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 178.22 | 188.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17335.57 | 01-JAN-13:32 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.29 |
February | 16745.69 | 20-FEB-12:13 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.22 |
March | 14055.12 | 05-MAR-11:53 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 126.14 | 0.00 |
April | 15923.05 | 16-APR-13:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 286.31 | 0.00 |
May | 13545.85 | 15-MAY-03:02 | 0.00 | 657.65 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.49 |
June | 13673.67 | 26-JUN-03:02 | 0.00 | 657.65 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 |
July | 15447.93 | 04-JUL-15:51 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 410.13 | 0.00 |
August | 13744.31 | 19-AUG-03:02 | 0.00 | 657.65 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 105.33 | 0.00 |
September | 16784.57 | 17-SEP-13:12 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 401.92 | 0.00 |
October | 17257.14 | 29-OCT-11:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 237.54 | 0.00 |
November | 17341.27 | 19-NOV-13:22 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.41 |
December | 18088.06 | 03-DEC-13:52 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13545.85 | 0.00 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18088.06 | 708.53 | 657.65 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 410.13 | 480.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8035.02 | 14-JAN-05:02 | 0.00 | 423.81 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.48 |
February | 12587.39 | 19-FEB-16:12 | 260.91 | 208.28 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 0.00 |
March | 12723.84 | 12-MAR-16:23 | 260.91 | 208.28 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.74 |
April | 18388.13 | 09-APR-16:11 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 |
May | 18001.57 | 29-MAY-16:12 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 513.68 | 0.00 |
June | 16294.87 | 10-JUN-17:05 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 134.92 | 0.00 |
July | 19083.30 | 04-JUL-16:31 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 111.29 | 0.00 |
August | 18414.68 | 13-AUG-16:52 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 184.08 | 0.00 |
September | 18878.80 | 17-SEP-15:12 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 240.33 | 0.00 |
October | 18199.16 | 15-OCT-15:42 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 0.00 |
November | 11898.17 | 29-NOV-06:02 | 652.28 | 847.62 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 | 0.00 |
December | 17977.59 | 10-DEC-15:32 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 95.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8035.02 | 0.00 | 208.28 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19083.30 | 652.28 | 847.62 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 513.68 | 162.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11101.55 | 14-JAN-06:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.86 |
February | 12409.21 | 11-FEB-06:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 |
March | 12645.68 | 14-MAR-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 |
April | 13030.74 | 29-APR-05:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.91 |
May | 17993.49 | 29-MAY-16:12 | 506.08 | 403.99 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 991.30 | 0.00 |
June | 17912.64 | 25-JUN-17:12 | 0.00 | 323.19 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 160.04 | 0.00 |
July | 18809.04 | 04-JUL-16:31 | 708.51 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 258.78 | 0.00 |
August | 18031.29 | 20-AUG-15:31 | 809.73 | 646.38 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 392.87 | 0.00 |
September | 18435.55 | 10-SEP-15:12 | 607.30 | 484.79 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 413.99 | 0.00 |
October | 14346.61 | 02-OCT-03:02 | 0.00 | 657.64 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 45.20 | 0.00 |
November | 13613.53 | 29-NOV-06:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 14.20 | 0.00 |
December | 11641.09 | 01-DEC-06:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11101.55 | 0.00 | 323.19 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18809.04 | 1012.16 | 1315.28 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 991.30 | 36.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10047.27 | 01-JAN-10:02 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.07 |
February | 7135.81 | 28-FEB-10:10 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 0.00 |
March | 8980.36 | 27-MAR-10:30 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 | 0.00 |
April | 17090.79 | 09-APR-09:32 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.50 |
May | 17137.12 | 07-MAY-10:32 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 100.80 | 0.00 |
June | 17102.58 | 04-JUN-09:13 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 134.16 | 0.00 |
July | 18111.55 | 04-JUL-09:12 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 53.56 | 0.00 |
August | 16587.58 | 20-AUG-15:31 | 521.82 | 416.55 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 269.05 | 0.00 |
September | 17176.26 | 10-SEP-15:12 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 270.92 | 0.00 |
October | 16947.62 | 09-OCT-10:53 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 212.90 | 0.00 |
November | 10661.71 | 29-NOV-06:02 | 652.28 | 847.62 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 0.00 |
December | 6720.62 | 08-DEC-10:30 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 36.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6720.62 | 260.91 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18111.55 | 1295.83 | 937.20 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 270.92 | 78.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19815.74 | 01-JAN-13:22 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.07 |
February | 19639.54 | 19-FEB-14:32 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.70 |
March | 18199.67 | 26-MAR-12:43 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 | 0.00 |
April | 13705.87 | 24-APR-05:03 | 607.31 | 789.19 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 |
May | 17755.05 | 29-MAY-16:12 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 996.25 | 0.00 |
June | 15237.21 | 17-JUN-03:02 | 0.00 | 657.65 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 56.91 | 0.00 |
July | 18693.83 | 04-JUL-15:51 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 434.82 | 0.00 |
August | 18271.78 | 20-AUG-15:31 | 809.75 | 646.40 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 378.17 | 0.00 |
September | 19631.64 | 10-SEP-15:12 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 314.20 | 0.00 |
October | 20042.86 | 15-OCT-13:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 66.78 | 0.00 |
November | 19262.84 | 19-NOV-11:32 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.84 |
December | 20895.19 | 03-DEC-13:42 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13705.87 | 0.00 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20895.19 | 809.75 | 789.19 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 996.25 | 254.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9733.11 | 14-JAN-06:03 | 521.82 | 678.09 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 |
February | 19922.76 | 19-FEB-17:12 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.19 |
March | 14886.19 | 13-MAR-05:02 | 652.28 | 847.62 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.98 |
April | 20554.81 | 02-APR-16:12 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.27 |
May | 19803.49 | 29-MAY-16:12 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 608.83 | 0.00 |
June | 18743.00 | 10-JUN-17:05 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 160.73 | 0.00 |
July | 21615.73 | 09-JUL-16:31 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 120.18 | 0.00 |
August | 20135.81 | 20-AUG-16:11 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 190.15 | 0.00 |
September | 21003.61 | 10-SEP-15:12 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 202.62 | 0.00 |
October | 20100.82 | 15-OCT-15:42 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 106.49 | 0.00 |
November | 12157.81 | 29-NOV-06:02 | 652.28 | 847.62 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 13.58 | 0.00 |
December | 11847.20 | 10-DEC-16:23 | 260.91 | 208.28 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 63.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9733.11 | 260.91 | 208.28 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21615.73 | 652.28 | 847.62 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 608.83 | 118.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12576.55 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.35 |
February | 11751.11 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.42 |
March | 9431.51 | 06-MAR-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 |
April | 9834.71 | 10-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14430.30 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.25 |
June | 11518.24 | 19-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 |
July | 13799.42 | 17-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 0.00 |
August | 14017.33 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 0.00 |
September | 14059.26 | 11-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 0.00 |
October | 13569.82 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 |
November | 12694.54 | 20-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 |
December | 12548.82 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9431.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14430.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 166.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8611.12 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.85 |
February | 7461.97 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.16 |
March | 8261.32 | 06-MAR-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.80 |
April | 7482.68 | 14-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 |
May | 8895.95 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.25 |
June | 11163.41 | 19-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 |
July | 8923.26 | 18-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 |
August | 8130.46 | 05-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 | 0.00 |
September | 11605.97 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.52 |
October | 11553.30 | 02-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.76 | 0.00 |
November | 8955.83 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.49 |
December | 7619.69 | 11-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7461.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11605.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.76 | 237.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13112.07 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.81 | 0.00 |
February | 13661.82 | 17-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 | 0.00 |
March | 17139.36 | 27-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.63 | 0.00 |
April | 20235.08 | 13-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.98 | 0.00 |
May | 21818.61 | 22-MAY-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.84 | 0.00 |
June | 22597.43 | 09-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.70 | 0.00 |
July | 23258.43 | 28-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.77 | 0.00 |
August | 21998.25 | 23-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.24 | 0.00 |
September | 19578.03 | 18-SEP-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.86 | 0.00 |
October | 18542.82 | 06-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.86 | 0.00 |
November | 15040.21 | 10-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.53 | 0.00 |
December | 13073.78 | 08-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13073.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.95 | 0.00 | |
Maximum of Months | 23258.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.84 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2126.58 | 24-JAN-17:00 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4226.12 | 20-FEB-17:50 | 23.38 | 57.88 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7233.49 | 31-MAR-23:40 | 0.00 | 57.88 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7896.98 | 09-APR-18:00 | 0.00 | 57.88 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3524.53 | 31-MAY-24:00 | 0.00 | 57.88 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5368.62 | 30-JUN-23:55 | 0.00 | 115.75 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7273.94 | 31-JUL-23:57 | 0.00 | 86.81 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7750.18 | 06-AUG-16:05 | 46.77 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3485.49 | 30-SEP-24:00 | 0.00 | 57.88 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5393.93 | 31-OCT-23:42 | 0.00 | 115.75 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6003.30 | 07-NOV-17:00 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7915.98 | 06-DEC-17:00 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2126.58 | 0.00 | 57.88 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7915.98 | 222.14 | 520.85 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1950.28 | 24-JAN-17:00 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3850.50 | 20-FEB-17:50 | 23.38 | 57.88 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6967.91 | 31-MAR-23:57 | 0.00 | 86.81 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7423.57 | 09-APR-18:00 | 0.00 | 57.88 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3417.84 | 31-MAY-24:00 | 0.00 | 57.88 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5232.75 | 30-JUN-23:55 | 0.00 | 115.75 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7009.19 | 31-JUL-23:57 | 0.00 | 86.81 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7303.96 | 08-AUG-16:00 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3357.40 | 30-SEP-24:00 | 0.00 | 57.88 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5102.03 | 31-OCT-24:00 | 0.00 | 57.88 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5699.87 | 07-NOV-17:00 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7502.62 | 06-DEC-17:00 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1950.28 | 0.00 | 57.88 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7502.62 | 222.14 | 520.85 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1953.88 | 02-JAN-17:00 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3958.87 | 20-FEB-17:50 | 23.38 | 57.88 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6919.95 | 31-MAR-23:57 | 0.00 | 86.81 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7688.38 | 09-APR-17:44 | 0.00 | 144.69 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3430.84 | 31-MAY-24:00 | 0.00 | 57.88 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5204.12 | 30-JUN-23:20 | 0.00 | 86.81 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7020.77 | 31-JUL-23:42 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7513.87 | 06-AUG-16:22 | 58.46 | 144.69 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3407.12 | 30-SEP-24:00 | 0.00 | 57.88 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5025.46 | 31-OCT-24:00 | 0.00 | 57.88 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5767.69 | 07-NOV-17:00 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7565.77 | 06-DEC-17:00 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1953.88 | 0.00 | 57.88 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7688.38 | 222.14 | 520.85 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 94128.64 | 02-JAN-17:00 | 4808.68 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 185419.65 | 21-FEB-17:00 | 4808.68 | 5919.59 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359888.65 | 31-MAR-23:53 | 0.00 | 986.65 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369782.43 | 17-APR-21:02 | 1518.53 | 3946.59 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176867.94 | 31-MAY-24:00 | 0.00 | 657.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268400.48 | 30-JUN-23:53 | 0.00 | 1315.53 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 358139.63 | 31-JUL-23:12 | 0.00 | 1315.53 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370281.94 | 28-AUG-12:20 | 4808.68 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176869.05 | 30-SEP-23:55 | 0.00 | 657.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269170.10 | 31-OCT-23:55 | 0.00 | 657.76 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277642.05 | 07-NOV-17:00 | 4808.68 | 5919.59 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369715.12 | 11-DEC-17:00 | 4808.68 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 94128.64 | 0.00 | 657.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370281.94 | 4808.68 | 5919.59 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.203735E+13 | 1480522.23 | 02-JAN-16:00 | 0.510628E+11 | 112176.67 | 25-JAN-06:19 |
February | 0.223776E+13 | 1620504.87 | 17-FEB-08:00 | 0.469536E+11 | 238588.00 | 04-FEB-06:10 |
March | 0.300023E+13 | 1821384.45 | 13-MAR-15:00 | 0.519922E+11 | 116233.47 | 16-MAR-07:10 |
April | 0.333573E+13 | 2007290.51 | 14-APR-15:50 | 0.460883E+11 | 63471.71 | 20-APR-11:00 |
May | 0.237166E+13 | 1558013.25 | 31-MAY-15:09 | 0.470587E+11 | 62467.50 | 01-MAY-11:00 |
June | 0.279145E+13 | 1738373.37 | 08-JUN-15:00 | 0.450439E+11 | 59517.55 | 06-JUN-11:39 |
July | 0.325866E+13 | 1918193.64 | 27-JUL-15:00 | 0.436518E+11 | 58034.74 | 06-JUL-11:39 |
August | 0.374877E+13 | 2057502.42 | 21-AUG-15:00 | 0.465909E+11 | 59455.65 | 31-AUG-11:00 |
September | 0.232101E+13 | 1540622.44 | 05-SEP-07:00 | 0.443030E+11 | 61619.29 | 27-SEP-11:39 |
October | 0.275833E+13 | 1689207.71 | 06-OCT-07:00 | 0.472411E+11 | 63654.42 | 20-OCT-11:00 |
November | 0.297476E+13 | 1834250.80 | 10-NOV-08:00 | 0.479092E+11 | 115644.54 | 27-NOV-06:19 |
December | 0.328366E+13 | 1958950.24 | 08-DEC-08:50 | 0.503351E+11 | 137608.31 | 15-DEC-06:19 |
Annual Sum or Average | 0.341194E+14 | 0.568231E+12 | ||||
Minimum of Months | 0.203735E+13 | 1480522.23 | 0.436518E+11 | 58034.74 | ||
Maximum of Months | 0.374877E+13 | 2057502.42 | 0.519922E+11 | 238588.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.311142E+12 | 0.659794E+11 | 0.811612E+12 | 0.164870E+12 | 0.195068E+12 | 0.925395E+11 | 0.00 | 0.256706E+12 | 0.130337E+12 | 0.334413E+09 | 0.875996E+10 | 0.00 | 0.00 |
February | 0.281033E+12 | 0.563057E+11 | 0.102011E+13 | 0.148925E+12 | 0.183111E+12 | 0.850167E+11 | 0.00 | 0.323518E+12 | 0.131279E+12 | 0.357043E+09 | 0.810857E+10 | 0.00 | 0.00 |
March | 0.332667E+12 | 0.578942E+11 | 0.146267E+13 | 0.165150E+12 | 0.219312E+12 | 0.108722E+12 | 0.00 | 0.483520E+12 | 0.160127E+12 | 0.297666E+09 | 0.987079E+10 | 0.00 | 0.00 |
April | 0.296715E+12 | 0.516812E+11 | 0.170311E+13 | 0.159525E+12 | 0.223722E+12 | 0.118117E+12 | 0.00 | 0.605111E+12 | 0.167577E+12 | 0.00 | 0.101787E+11 | 0.00 | 0.00 |
May | 0.319450E+12 | 0.494830E+11 | 0.820521E+12 | 0.165009E+12 | 0.247844E+12 | 0.122798E+12 | 0.00 | 0.437488E+12 | 0.198768E+12 | 0.00 | 0.103033E+11 | 0.00 | 0.00 |
June | 0.317896E+12 | 0.461063E+11 | 0.110677E+13 | 0.159787E+12 | 0.249058E+12 | 0.130436E+12 | 0.00 | 0.562625E+12 | 0.208085E+12 | 0.00 | 0.106789E+11 | 0.00 | 0.00 |
July | 0.297404E+12 | 0.482116E+11 | 0.143888E+13 | 0.164745E+12 | 0.253549E+12 | 0.139566E+12 | 0.00 | 0.686606E+12 | 0.218476E+12 | 0.00 | 0.112250E+11 | 0.00 | 0.00 |
August | 0.331613E+12 | 0.516673E+11 | 0.177780E+13 | 0.165150E+12 | 0.257234E+12 | 0.144419E+12 | 0.00 | 0.787038E+12 | 0.222427E+12 | 0.00 | 0.114238E+11 | 0.00 | 0.00 |
September | 0.297176E+12 | 0.541915E+11 | 0.784732E+12 | 0.159523E+12 | 0.230029E+12 | 0.125526E+12 | 0.00 | 0.455941E+12 | 0.203608E+12 | 0.00 | 0.102856E+11 | 0.00 | 0.00 |
October | 0.309491E+12 | 0.605023E+11 | 0.112899E+13 | 0.164870E+12 | 0.223714E+12 | 0.126527E+12 | 0.00 | 0.533717E+12 | 0.200314E+12 | 0.00 | 0.102016E+11 | 0.00 | 0.00 |
November | 0.306987E+12 | 0.625701E+11 | 0.140306E+13 | 0.159632E+12 | 0.205010E+12 | 0.114074E+12 | 0.00 | 0.538691E+12 | 0.175310E+12 | 90239720.47 | 0.933585E+10 | 0.00 | 0.00 |
December | 0.301768E+12 | 0.668270E+11 | 0.175516E+13 | 0.164746E+12 | 0.197305E+12 | 0.106679E+12 | 0.00 | 0.527056E+12 | 0.154612E+12 | 70980311.98 | 0.943212E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.370334E+13 | 0.671420E+12 | 0.152134E+14 | 0.194193E+13 | 0.268496E+13 | 0.141442E+13 | 0.00 | 0.619802E+13 | 0.217092E+13 | 0.115034E+10 | 0.119804E+12 | 0.00 | 0.00 |
Minimum of Months | 0.281033E+12 | 0.461063E+11 | 0.784732E+12 | 0.148925E+12 | 0.183111E+12 | 0.850167E+11 | 0.00 | 0.256706E+12 | 0.130337E+12 | 0.00 | 0.810857E+10 | 0.00 | 0.00 |
Maximum of Months | 0.332667E+12 | 0.668270E+11 | 0.177780E+13 | 0.165150E+12 | 0.257234E+12 | 0.144419E+12 | 0.00 | 0.787038E+12 | 0.222427E+12 | 0.357043E+09 | 0.114238E+11 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.629755E+09 | 0.00 | 0.504331E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.149559E+10 | 0.00 | 0.454581E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.671344E+09 | 0.00 | 0.513208E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 418.40 | 0.00 | 0.460883E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.470587E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.450439E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.436518E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.465909E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.443030E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.472411E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.259416E+09 | 0.00 | 0.476498E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.117093E+10 | 0.00 | 0.491641E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.422703E+10 | 0.00 | 0.564003E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.436518E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.149559E+10 | 0.00 | 0.513208E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 340587.21 | 04-JAN-16:00 | 54335.80 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 118936.46 | 26-JAN-08:20 | 152732.34 | 04-JAN-13:50 | 77952.75 | 02-JAN-13:39 | 0.00 | 01-JAN-00:10 |
February | 326470.35 | 08-FEB-16:00 | 54335.80 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 118936.24 | 07-FEB-08:20 | 164207.58 | 13-FEB-13:39 | 77004.34 | 17-FEB-13:00 | 0.00 | 01-FEB-00:10 |
March | 332465.06 | 15-MAR-07:10 | 54335.80 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 118942.19 | 15-MAR-07:19 | 178855.05 | 09-MAR-16:19 | 77516.70 | 27-MAR-13:39 | 0.00 | 01-MAR-00:10 |
April | 331551.42 | 12-APR-07:10 | 54335.80 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 118941.42 | 12-APR-07:19 | 204876.93 | 14-APR-15:50 | 75329.44 | 12-APR-13:20 | 0.00 | 01-APR-00:10 |
May | 321212.92 | 25-MAY-07:10 | 54335.80 | 01-MAY-05:10 | 439129.89 | 01-MAY-07:10 | 118932.81 | 25-MAY-07:19 | 211033.03 | 22-MAY-15:00 | 80595.45 | 31-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 341530.44 | 15-JUN-07:10 | 54335.80 | 01-JUN-05:10 | 557421.28 | 01-JUN-07:10 | 118949.75 | 15-JUN-07:19 | 211732.69 | 29-JUN-15:50 | 80131.77 | 19-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 320928.16 | 05-JUL-07:10 | 54335.80 | 01-JUL-05:10 | 675712.68 | 03-JUL-07:10 | 118932.57 | 05-JUL-07:19 | 222608.04 | 24-JUL-15:39 | 75933.40 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
August | 331933.76 | 28-AUG-07:10 | 54335.80 | 01-AUG-05:10 | 794004.08 | 01-AUG-07:10 | 118941.74 | 28-AUG-07:19 | 212698.55 | 02-AUG-15:39 | 76636.76 | 31-AUG-12:30 | 0.00 | 01-AUG-00:10 |
September | 352853.36 | 27-SEP-07:10 | 54335.80 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 118959.22 | 27-SEP-07:19 | 193551.04 | 05-SEP-14:00 | 80968.45 | 05-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 341457.76 | 31-OCT-07:10 | 54335.80 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 118949.69 | 31-OCT-07:19 | 187684.96 | 02-OCT-12:09 | 81035.57 | 02-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 337794.75 | 29-NOV-16:00 | 54335.80 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 118944.42 | 24-NOV-08:20 | 169349.79 | 09-NOV-16:40 | 78254.72 | 02-NOV-15:30 | 0.00 | 01-NOV-00:10 |
December | 348195.92 | 15-DEC-16:00 | 54335.80 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 118946.86 | 29-DEC-08:39 | 169423.77 | 01-DEC-16:00 | 78726.81 | 11-DEC-10:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 320928.16 | 54335.80 | 439129.89 | 118932.57 | 152732.34 | 75329.44 | 0.00 | |||||||
Maximum of Months | 352853.36 | 54335.80 | 794004.08 | 118959.22 | 222608.04 | 81035.57 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 336982.79 | 02-JAN-13:39 | 97050.41 | 02-JAN-09:09 | 3672.98 | 25-JAN-01:00 | 5613.48 | 01-JAN-09:09 | 0.00 | 0.00 |
February | 357528.53 | 10-FEB-15:20 | 97050.41 | 02-FEB-08:39 | 4076.76 | 04-FEB-05:00 | 5613.48 | 01-FEB-06:10 | 0.00 | 0.00 |
March | 407241.14 | 13-MAR-14:39 | 97050.41 | 03-MAR-13:09 | 2982.06 | 16-MAR-17:00 | 5613.48 | 01-MAR-06:10 | 0.00 | 0.00 |
April | 442270.78 | 14-APR-14:30 | 97050.41 | 01-APR-14:39 | 0.00 | 01-APR-00:10 | 5613.48 | 01-APR-04:19 | 0.00 | 0.00 |
May | 395434.97 | 31-MAY-05:10 | 97050.41 | 27-MAY-03:09 | 0.00 | 01-MAY-00:10 | 5613.48 | 01-MAY-03:30 | 0.00 | 0.00 |
June | 396207.21 | 19-JUN-05:10 | 97050.41 | 07-JUN-03:09 | 0.00 | 01-JUN-00:10 | 5613.48 | 01-JUN-03:20 | 0.00 | 0.00 |
July | 447555.31 | 31-JUL-13:00 | 97050.41 | 03-JUL-03:09 | 0.00 | 01-JUL-00:10 | 5613.48 | 01-JUL-03:20 | 0.00 | 0.00 |
August | 476372.27 | 21-AUG-15:00 | 97050.41 | 06-AUG-11:09 | 0.00 | 01-AUG-00:10 | 5613.48 | 01-AUG-00:49 | 0.00 | 0.00 |
September | 353868.46 | 20-SEP-13:09 | 97050.41 | 10-SEP-14:39 | 0.00 | 01-SEP-00:10 | 5613.48 | 01-SEP-03:20 | 0.00 | 0.00 |
October | 441190.69 | 02-OCT-05:10 | 97050.41 | 01-OCT-11:30 | 0.00 | 01-OCT-00:10 | 5613.48 | 01-OCT-09:50 | 0.00 | 0.00 |
November | 416740.05 | 03-NOV-11:20 | 97050.41 | 04-NOV-03:09 | 2343.63 | 13-NOV-05:00 | 5613.48 | 01-NOV-04:10 | 0.00 | 0.00 |
December | 444410.24 | 08-DEC-14:30 | 97050.41 | 01-DEC-13:39 | 2436.44 | 20-DEC-19:30 | 5613.48 | 01-DEC-04:19 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 336982.79 | 97050.41 | 0.00 | 5613.48 | 0.00 | 0.00 | ||||
Maximum of Months | 476372.27 | 97050.41 | 4076.76 | 5613.48 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1480522.23 | 02-JAN-16:00 | 326779.69 | 439129.89 | 0.00 | 84892.88 | 127966.19 | 77704.29 | 0.00 | 321385.42 | 97050.41 |
February | 1620504.87 | 17-FEB-08:00 | 316816.17 | 557421.28 | 0.00 | 118929.14 | 128998.67 | 74142.86 | 0.00 | 321532.85 | 97050.41 |
March | 1821384.45 | 13-MAR-15:00 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 163522.08 | 75286.12 | 0.00 | 402497.77 | 97050.41 |
April | 2007290.51 | 14-APR-15:50 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 204876.93 | 74563.92 | 0.00 | 429479.77 | 97050.41 |
May | 1558013.25 | 31-MAY-15:09 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 206926.72 | 74773.61 | 0.00 | 332817.22 | 97050.41 |
June | 1738373.37 | 08-JUN-15:00 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 209844.84 | 75104.56 | 0.00 | 391636.89 | 97050.41 |
July | 1918193.64 | 27-JUL-15:00 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 216414.05 | 75279.46 | 0.00 | 446421.64 | 97050.41 |
August | 2057502.42 | 21-AUG-15:00 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 207336.16 | 75424.10 | 0.00 | 476372.27 | 97050.41 |
September | 1540622.44 | 05-SEP-07:00 | 316816.17 | 439129.89 | 0.00 | 118929.14 | 154380.74 | 75532.40 | 0.00 | 333170.21 | 97050.41 |
October | 1689207.71 | 06-OCT-07:00 | 316816.17 | 557421.28 | 0.00 | 118930.21 | 157328.49 | 74686.46 | 0.00 | 361361.22 | 97050.41 |
November | 1834250.80 | 10-NOV-08:00 | 316816.17 | 675712.68 | 0.00 | 118929.14 | 152000.77 | 74766.17 | 0.00 | 393361.98 | 97050.41 |
December | 1958950.24 | 08-DEC-08:50 | 316816.17 | 794004.08 | 0.00 | 118929.14 | 140959.79 | 74492.61 | 0.00 | 411084.56 | 97050.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1480522.23 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 127966.19 | 74142.86 | 0.00 | 321385.42 | 97050.41 | |
Maximum of Months | 2057502.42 | 326779.69 | 794004.08 | 0.00 | 118930.21 | 216414.05 | 77704.29 | 0.00 | 476372.27 | 97050.41 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 106480.80 | 25-JAN-06:19 | 0.00 | 68200.91 | 18-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 212165.94 | 04-FEB-06:10 | 0.00 | 67896.37 | 03-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 98595.62 | 16-MAR-05:10 | 0.00 | 66351.46 | 14-MAR-11:20 | 0.00 |
April | 0.00 | 0.00 | 0.70 | 03-APR-00:49 | 0.00 | 63471.71 | 20-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 62467.50 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 59517.55 | 06-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 58034.74 | 06-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 59455.65 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 61619.29 | 27-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 63654.42 | 20-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 89383.99 | 27-NOV-06:19 | 0.00 | 66676.60 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 126921.17 | 27-DEC-06:19 | 0.00 | 67932.55 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 58034.74 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 212165.94 | 0.00 | 68200.91 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.70 | 1.17 | 26.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 26.72 | 0.83 | 26.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 25.93 | 0.17 | 25.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.24 | 0.00 | 26.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.47 | 0.33 | 26.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 26.07 | 0.00 | 26.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 25.92 | 0.17 | 25.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.09 | 0.00 | 26.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 26.32 | 1.17 | 26.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 25.99 | 0.50 | 25.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.33 | 1.33 | 26.44 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.15 | 0.83 | 26.21 |
Annual Sum or Average | 0.00 | 0.00 | 95.67 | 26.29 | 6.50 | 26.33 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 25.92 | 0.00 | 25.89 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.72 | 1.33 | 26.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.60 | 0.00 | 25.60 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.60 | 0.00 | 25.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.61 | 0.00 | 25.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.62 | 0.00 | 25.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.62 | 0.00 | 25.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.65 | 0.00 | 25.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.61 | 0.00 | 25.61 |
Annual Sum or Average | 0.00 | 0.00 | 5.67 | 25.61 | 0.00 | 25.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.65 | 0.00 | 25.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.49 | 0.33 | 26.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.68 | 0.00 | 25.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.71 | 0.00 | 25.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.84 | 0.17 | 25.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.66 | 0.00 | 25.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.67 | 25.87 | 0.50 | 26.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.49 | 0.33 | 26.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.54 | 0.67 | 27.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.66 | 1.33 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.49 | 1.00 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.58 | 2.00 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.72 | 5.00 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.46 | 0.83 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.58 | 2.33 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.59 | 0.83 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.43 | 0.17 | 27.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.17 | 27.62 | 14.17 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.72 | 5.00 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.27 | 11.17 | 26.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.37 | 9.50 | 26.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.54 | 1.50 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.50 | 0.83 | 27.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 26.90 | 1.00 | 27.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.63 | 0.00 | 25.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.62 | 1.17 | 26.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 26.60 | 2.17 | 26.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.23 | 6.17 | 27.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.42 | 8.67 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 25.66 | 21.00 | 25.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 26.08 | 14.83 | 26.09 |
Annual Sum or Average | 0.00 | 0.00 | 87.33 | 26.39 | 78.00 | 26.42 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.63 | 0.00 | 25.63 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 27.54 | 21.00 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.83 | 3.17 | 27.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.02 | 3.33 | 27.16 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.14 | 6.00 | 27.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.39 | 4.00 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 26.76 | 3.83 | 26.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.07 | 6.67 | 27.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 27.25 | 8.67 | 27.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.20 | 4.00 | 27.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.08 | 6.17 | 27.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.00 | 5.17 | 27.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.08 | 5.50 | 27.30 |
Annual Sum or Average | 0.00 | 0.00 | 171.83 | 27.12 | 56.67 | 27.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.76 | 0.17 | 26.94 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 27.83 | 8.67 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.06 | 0.67 | 27.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 25.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.83 | 26.39 | 0.67 | 26.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.06 | 0.67 | 27.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.37 | 0.33 | 27.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.66 | 2.83 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.60 | 1.00 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.73 | 2.67 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.80 | 8.00 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.51 | 2.00 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.69 | 3.17 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.61 | 1.17 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.17 | 27.70 | 21.17 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.80 | 8.00 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 25.49 | 22.00 | 25.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 25.62 | 17.00 | 25.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.74 | 2.00 | 26.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.38 | 0.83 | 27.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.34 | 1.00 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.59 | 0.00 | 25.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.16 | 1.00 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.98 | 1.17 | 27.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.14 | 5.83 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 26.63 | 14.17 | 26.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 25.39 | 32.67 | 25.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 25.81 | 20.17 | 25.81 |
Annual Sum or Average | 0.00 | 0.00 | 123.33 | 25.88 | 117.83 | 25.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.39 | 0.00 | 25.39 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 27.38 | 32.67 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.87 | 1.17 | 27.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.91 | 0.50 | 27.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.86 | 3.00 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.90 | 1.33 | 27.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.64 | 1.67 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.81 | 3.33 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.57 | 2.17 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.72 | 2.50 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.66 | 2.67 | 27.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.45 | 0.33 | 27.45 |
Annual Sum or Average | 0.00 | 0.00 | 25.33 | 27.75 | 18.83 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.91 | 3.33 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.45 | 1.33 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.14 | 2.00 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.35 | 5.17 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.21 | 1.83 | 27.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.09 | 2.33 | 27.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.32 | 0.00 | 19.32 | 17.33 | 27.19 | 12.67 | 27.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.32 | 0.00 | 19.32 | 7.17 | 27.45 | 5.17 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.71 | 3.67 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.60 | 3.67 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.71 | 6.17 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.87 | 12.33 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.66 | 4.50 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.69 | 7.50 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.62 | 1.50 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.32 | 0.00 | 19.32 | 42.17 | 27.70 | 39.33 | 27.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.32 | 0.00 | 19.32 | 13.50 | 27.87 | 12.33 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.01 | 5.67 | 27.01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.88 | 4.33 | 27.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.53 | 1.67 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.47 | 1.50 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.62 | 1.33 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.17 | 1.17 | 27.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.43 | 4.67 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.33 | 3.17 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.50 | 6.33 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.81 | 9.00 | 27.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.35 | 11.17 | 26.35 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.90 | 8.83 | 26.90 |
Annual Sum or Average | 0.00 | 0.00 | 66.50 | 27.24 | 58.83 | 27.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.35 | 1.17 | 26.35 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.88 | 11.17 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.83 | 1.50 | 27.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.77 | 0.83 | 27.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.95 | 3.00 | 28.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.92 | 2.50 | 27.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.75 | 2.17 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.92 | 5.00 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.72 | 3.17 | 27.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.90 | 3.50 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.80 | 3.67 | 27.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.33 | 27.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.47 | 0.50 | 27.47 |
Annual Sum or Average | 0.00 | 0.00 | 38.00 | 27.85 | 26.17 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.95 | 5.00 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.64 | 19.17 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.17 | 27.64 | 19.17 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.64 | 19.17 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.62 | 14.00 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.00 | 27.62 | 14.00 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.62 | 14.00 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.62 | 7.50 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.50 | 27.62 | 7.50 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.62 | 7.50 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 150.83 | 28.20 | 140.17 | 28.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.86 | 0.00 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 674.67 | 28.81 | 481.67 | 28.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 | 27.92 | 66.00 | 27.93 |
Annual Sum or Average | 0.00 | 0.00 | 894.00 | 28.64 | 687.83 | 28.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 674.67 | 28.81 | 481.67 | 28.90 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 120.67 | 25.52 | 433.83 | 24.88 | 120.67 | 25.00 |
February | 101.33 | 25.16 | 388.50 | 24.78 | 101.33 | 24.84 |
March | 131.17 | 25.21 | 449.33 | 24.69 | 131.17 | 24.78 |
April | 193.83 | 25.22 | 479.50 | 24.76 | 193.83 | 24.86 |
May | 260.50 | 25.05 | 508.00 | 24.71 | 260.50 | 24.80 |
June | 256.50 | 24.95 | 496.00 | 24.65 | 256.50 | 24.72 |
July | 250.00 | 25.28 | 497.00 | 24.85 | 250.00 | 24.96 |
August | 197.83 | 25.24 | 514.00 | 24.71 | 197.83 | 24.82 |
September | 235.50 | 25.19 | 485.00 | 24.78 | 235.50 | 24.88 |
October | 212.17 | 25.45 | 502.00 | 24.88 | 212.17 | 25.01 |
November | 169.50 | 25.45 | 487.33 | 24.85 | 169.50 | 24.98 |
December | 135.83 | 25.63 | 474.50 | 24.88 | 135.83 | 25.02 |
Annual Sum or Average | 2264.83 | 25.25 | 5715.00 | 24.78 | 2264.83 | 24.89 |
Minimum of Months | 101.33 | 24.95 | 388.50 | 24.65 | 101.33 | 24.72 |
Maximum of Months | 260.50 | 25.63 | 514.00 | 24.88 | 260.50 | 25.02 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 24.45 | 420.83 | 24.45 | 0.33 | 24.46 |
February | 3.17 | 24.49 | 387.33 | 24.44 | 0.50 | 24.44 |
March | 0.00 | 0.00 | 445.67 | 24.30 | 0.00 | 24.30 |
April | 0.00 | 0.00 | 479.67 | 24.23 | 0.00 | 24.23 |
May | 0.00 | 0.00 | 508.00 | 24.27 | 0.00 | 24.27 |
June | 0.00 | 0.00 | 496.00 | 24.21 | 0.00 | 24.21 |
July | 0.00 | 0.00 | 497.00 | 24.23 | 0.00 | 24.23 |
August | 0.00 | 0.00 | 514.00 | 24.19 | 0.00 | 24.19 |
September | 0.00 | 0.00 | 485.00 | 24.27 | 0.00 | 24.27 |
October | 0.00 | 0.00 | 502.00 | 24.32 | 0.00 | 24.32 |
November | 0.00 | 0.00 | 484.67 | 24.37 | 0.00 | 24.37 |
December | 0.00 | 0.00 | 462.50 | 24.37 | 0.00 | 24.37 |
Annual Sum or Average | 5.50 | 24.47 | 5682.67 | 24.30 | 0.83 | 24.30 |
Minimum of Months | 0.00 | 0.00 | 387.33 | 24.19 | 0.00 | 24.19 |
Maximum of Months | 3.17 | 24.49 | 514.00 | 24.45 | 0.50 | 24.46 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.17 | 23.77 | 378.50 | 24.29 | 0.00 | 24.29 |
February | 25.00 | 23.57 | 344.50 | 24.27 | 0.00 | 24.27 |
March | 10.17 | 23.88 | 409.67 | 24.29 | 0.00 | 24.29 |
April | 0.00 | 0.00 | 470.83 | 24.26 | 0.00 | 24.26 |
May | 0.00 | 0.00 | 507.33 | 24.25 | 0.00 | 24.25 |
June | 0.00 | 0.00 | 496.00 | 24.22 | 0.00 | 24.22 |
July | 0.00 | 0.00 | 497.00 | 24.22 | 0.00 | 24.22 |
August | 0.00 | 0.00 | 513.50 | 24.21 | 0.00 | 24.21 |
September | 0.00 | 0.00 | 480.00 | 24.24 | 0.00 | 24.24 |
October | 0.00 | 0.00 | 493.67 | 24.30 | 0.00 | 24.30 |
November | 0.00 | 0.00 | 474.00 | 24.34 | 0.00 | 24.34 |
December | 12.83 | 23.59 | 394.33 | 24.30 | 0.00 | 24.30 |
Annual Sum or Average | 68.17 | 23.68 | 5459.33 | 24.26 | 0.00 | 24.26 |
Minimum of Months | 0.00 | 0.00 | 344.50 | 24.21 | 0.00 | 24.21 |
Maximum of Months | 25.00 | 23.88 | 513.50 | 24.34 | 0.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 96.50 | 23.32 | 294.33 | 23.97 | 0.00 | 23.97 |
February | 66.83 | 22.98 | 319.83 | 24.05 | 0.00 | 24.05 |
March | 51.67 | 23.48 | 390.50 | 24.20 | 0.00 | 24.20 |
April | 1.50 | 23.50 | 468.17 | 24.28 | 0.00 | 24.28 |
May | 0.83 | 27.12 | 508.00 | 24.31 | 0.83 | 24.31 |
June | 0.00 | 0.00 | 496.00 | 24.27 | 0.00 | 24.27 |
July | 0.00 | 0.00 | 497.00 | 24.31 | 0.00 | 24.31 |
August | 0.00 | 0.00 | 510.00 | 24.26 | 0.00 | 24.26 |
September | 0.00 | 0.00 | 485.00 | 24.31 | 0.00 | 24.31 |
October | 0.00 | 0.00 | 501.67 | 24.34 | 0.00 | 24.34 |
November | 6.17 | 23.26 | 458.00 | 24.28 | 0.00 | 24.28 |
December | 75.50 | 23.19 | 335.17 | 24.05 | 0.00 | 24.05 |
Annual Sum or Average | 299.00 | 23.25 | 5263.67 | 24.23 | 0.83 | 24.23 |
Minimum of Months | 0.00 | 0.00 | 294.33 | 23.97 | 0.00 | 23.97 |
Maximum of Months | 96.50 | 27.12 | 510.00 | 24.34 | 0.83 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 109.50 | 23.38 | 314.17 | 24.03 | 3.67 | 24.04 |
February | 60.00 | 23.43 | 338.50 | 24.14 | 5.33 | 24.16 |
March | 57.00 | 23.64 | 397.17 | 24.18 | 5.33 | 24.19 |
April | 2.33 | 24.00 | 471.33 | 24.24 | 0.33 | 24.24 |
May | 22.67 | 26.19 | 508.00 | 24.46 | 22.67 | 24.53 |
June | 11.67 | 26.09 | 496.00 | 24.38 | 11.67 | 24.42 |
July | 16.17 | 26.62 | 497.00 | 24.50 | 16.17 | 24.56 |
August | 11.17 | 26.60 | 514.00 | 24.34 | 11.17 | 24.39 |
September | 3.17 | 26.61 | 485.00 | 24.40 | 3.17 | 24.42 |
October | 5.00 | 26.07 | 502.00 | 24.39 | 5.00 | 24.41 |
November | 5.17 | 23.57 | 467.50 | 24.28 | 0.50 | 24.28 |
December | 48.00 | 23.31 | 367.17 | 24.16 | 0.00 | 24.16 |
Annual Sum or Average | 351.83 | 24.01 | 5357.83 | 24.30 | 85.00 | 24.33 |
Minimum of Months | 2.33 | 23.31 | 314.17 | 24.03 | 0.00 | 24.04 |
Maximum of Months | 109.50 | 26.62 | 514.00 | 24.50 | 22.67 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 113.83 | 23.20 | 304.50 | 24.01 | 8.00 | 24.06 |
February | 59.17 | 23.34 | 322.17 | 24.12 | 7.67 | 24.16 |
March | 53.00 | 23.27 | 391.50 | 24.04 | 6.17 | 24.06 |
April | 18.50 | 25.48 | 436.50 | 24.24 | 12.33 | 24.30 |
May | 24.00 | 26.25 | 506.33 | 24.42 | 24.00 | 24.50 |
June | 14.67 | 26.66 | 495.83 | 24.35 | 14.67 | 24.42 |
July | 33.67 | 26.69 | 496.83 | 24.52 | 33.67 | 24.65 |
August | 9.00 | 26.60 | 505.83 | 24.21 | 9.00 | 24.25 |
September | 20.83 | 26.65 | 485.00 | 24.47 | 20.83 | 24.56 |
October | 7.33 | 26.59 | 492.67 | 24.33 | 7.33 | 24.36 |
November | 13.00 | 23.43 | 442.33 | 24.15 | 1.33 | 24.16 |
December | 113.67 | 22.86 | 295.17 | 23.76 | 0.00 | 23.76 |
Annual Sum or Average | 480.67 | 24.01 | 5174.67 | 24.24 | 145.00 | 24.29 |
Minimum of Months | 7.33 | 22.86 | 295.17 | 23.76 | 0.00 | 23.76 |
Maximum of Months | 113.83 | 26.69 | 506.33 | 24.52 | 33.67 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 69.00 | 25.03 | 405.00 | 24.61 | 33.83 | 24.75 |
February | 47.67 | 25.16 | 394.67 | 24.58 | 26.33 | 24.70 |
March | 42.67 | 24.60 | 437.17 | 24.37 | 18.00 | 24.44 |
April | 16.00 | 26.28 | 474.17 | 24.38 | 14.00 | 24.44 |
May | 23.67 | 26.18 | 508.00 | 24.46 | 23.67 | 24.54 |
June | 11.50 | 26.08 | 496.00 | 24.36 | 11.50 | 24.40 |
July | 17.50 | 26.65 | 497.00 | 24.49 | 17.50 | 24.56 |
August | 17.67 | 26.68 | 514.00 | 24.39 | 17.67 | 24.46 |
September | 32.83 | 26.79 | 485.00 | 24.63 | 32.83 | 24.76 |
October | 46.33 | 26.82 | 502.00 | 24.74 | 46.33 | 24.91 |
November | 36.83 | 26.58 | 481.17 | 24.69 | 33.83 | 24.82 |
December | 52.33 | 25.58 | 437.67 | 24.62 | 33.50 | 24.76 |
Annual Sum or Average | 414.00 | 25.83 | 5631.83 | 24.53 | 309.00 | 24.63 |
Minimum of Months | 11.50 | 24.60 | 394.67 | 24.36 | 11.50 | 24.40 |
Maximum of Months | 69.00 | 26.82 | 514.00 | 24.74 | 46.33 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 69.17 | 23.26 | 370.67 | 24.19 | 4.67 | 24.21 |
February | 45.33 | 25.30 | 398.67 | 24.60 | 26.33 | 24.73 |
March | 39.17 | 26.31 | 468.00 | 24.62 | 33.50 | 24.76 |
April | 48.17 | 26.80 | 485.00 | 24.71 | 48.17 | 24.88 |
May | 41.50 | 26.76 | 508.00 | 24.63 | 41.50 | 24.78 |
June | 37.00 | 26.78 | 496.00 | 24.58 | 37.00 | 24.72 |
July | 63.33 | 26.68 | 497.00 | 24.78 | 63.33 | 24.98 |
August | 67.17 | 26.64 | 514.00 | 24.71 | 67.17 | 24.91 |
September | 34.50 | 26.77 | 485.00 | 24.61 | 34.50 | 24.75 |
October | 49.17 | 26.84 | 502.00 | 24.73 | 49.17 | 24.90 |
November | 39.17 | 26.70 | 483.00 | 24.69 | 37.33 | 24.84 |
December | 45.67 | 26.65 | 471.50 | 24.75 | 43.67 | 24.91 |
Annual Sum or Average | 579.33 | 26.18 | 5678.83 | 24.64 | 486.33 | 24.79 |
Minimum of Months | 34.50 | 23.26 | 370.67 | 24.19 | 4.67 | 24.21 |
Maximum of Months | 69.17 | 26.84 | 514.00 | 24.78 | 67.17 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 239.00 | 22.99 | 194.17 | 23.50 | 15.67 | 23.53 |
February | 144.17 | 23.05 | 259.83 | 23.75 | 17.17 | 23.81 |
March | 151.83 | 23.46 | 344.00 | 23.99 | 33.17 | 24.07 |
April | 30.83 | 25.10 | 447.67 | 24.32 | 24.00 | 24.38 |
May | 71.67 | 25.98 | 508.00 | 24.60 | 71.67 | 24.75 |
June | 47.67 | 26.23 | 496.00 | 24.56 | 47.67 | 24.70 |
July | 43.00 | 26.20 | 497.00 | 24.62 | 43.00 | 24.74 |
August | 55.00 | 25.96 | 514.00 | 24.52 | 55.00 | 24.65 |
September | 53.17 | 26.04 | 485.00 | 24.57 | 53.17 | 24.71 |
October | 55.17 | 25.81 | 501.17 | 24.53 | 55.17 | 24.65 |
November | 78.50 | 24.35 | 409.00 | 24.26 | 41.67 | 24.35 |
December | 222.67 | 23.22 | 255.00 | 23.74 | 47.33 | 23.84 |
Annual Sum or Average | 1192.67 | 24.07 | 4910.83 | 24.28 | 504.67 | 24.39 |
Minimum of Months | 30.83 | 22.99 | 194.17 | 23.50 | 15.67 | 23.53 |
Maximum of Months | 239.00 | 26.23 | 514.00 | 24.62 | 71.67 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 188.33 | 22.94 | 176.00 | 23.62 | 16.33 | 23.71 |
February | 118.00 | 23.10 | 215.17 | 23.85 | 16.00 | 23.93 |
March | 103.67 | 23.63 | 292.33 | 24.12 | 31.67 | 24.23 |
April | 51.00 | 25.54 | 359.33 | 24.57 | 38.83 | 24.72 |
May | 64.33 | 26.16 | 425.67 | 24.68 | 64.33 | 24.85 |
June | 53.67 | 26.48 | 418.00 | 24.72 | 53.67 | 24.90 |
July | 62.67 | 26.59 | 422.00 | 24.87 | 62.67 | 25.07 |
August | 51.67 | 26.25 | 423.00 | 24.64 | 51.67 | 24.80 |
September | 51.17 | 26.52 | 409.50 | 24.74 | 51.17 | 24.91 |
October | 52.50 | 26.21 | 413.17 | 24.67 | 51.83 | 24.83 |
November | 69.00 | 24.25 | 339.17 | 24.28 | 31.83 | 24.39 |
December | 209.33 | 22.95 | 180.50 | 23.59 | 32.67 | 23.72 |
Annual Sum or Average | 1075.33 | 24.30 | 4073.83 | 24.41 | 502.67 | 24.56 |
Minimum of Months | 51.00 | 22.94 | 176.00 | 23.59 | 16.00 | 23.71 |
Maximum of Months | 209.33 | 26.59 | 425.67 | 24.87 | 64.33 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 104.00 | 24.57 | 383.67 | 24.55 | 42.33 | 24.71 |
February | 68.83 | 24.66 | 368.33 | 24.51 | 35.00 | 24.65 |
March | 87.83 | 24.49 | 411.67 | 24.39 | 41.67 | 24.50 |
April | 35.33 | 25.78 | 464.17 | 24.47 | 32.00 | 24.56 |
May | 72.33 | 25.95 | 508.00 | 24.59 | 72.33 | 24.74 |
June | 46.33 | 26.05 | 496.00 | 24.52 | 46.33 | 24.64 |
July | 42.17 | 26.09 | 497.00 | 24.59 | 42.17 | 24.70 |
August | 56.83 | 26.12 | 514.00 | 24.56 | 56.83 | 24.71 |
September | 64.50 | 26.56 | 485.00 | 24.76 | 64.50 | 24.95 |
October | 78.33 | 26.68 | 502.00 | 24.90 | 78.33 | 25.11 |
November | 63.50 | 26.17 | 468.83 | 24.77 | 56.17 | 24.94 |
December | 114.83 | 24.93 | 393.33 | 24.63 | 63.83 | 24.83 |
Annual Sum or Average | 834.83 | 25.53 | 5492.00 | 24.61 | 631.50 | 24.76 |
Minimum of Months | 35.33 | 24.49 | 368.33 | 24.39 | 32.00 | 24.50 |
Maximum of Months | 114.83 | 26.68 | 514.00 | 24.90 | 78.33 | 25.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 222.33 | 22.76 | 213.50 | 23.45 | 12.83 | 23.49 |
February | 125.50 | 23.11 | 279.00 | 23.91 | 20.50 | 24.00 |
March | 115.17 | 23.63 | 383.83 | 24.17 | 32.83 | 24.28 |
April | 42.33 | 26.14 | 461.00 | 24.54 | 38.33 | 24.68 |
May | 62.83 | 26.28 | 508.00 | 24.63 | 62.83 | 24.79 |
June | 42.50 | 26.58 | 496.00 | 24.58 | 42.50 | 24.72 |
July | 48.33 | 26.59 | 497.00 | 24.69 | 48.33 | 24.84 |
August | 54.83 | 26.34 | 514.00 | 24.60 | 54.83 | 24.75 |
September | 45.50 | 26.51 | 483.83 | 24.61 | 45.50 | 24.76 |
October | 54.17 | 26.33 | 492.83 | 24.63 | 53.00 | 24.79 |
November | 67.50 | 24.27 | 414.00 | 24.28 | 32.67 | 24.38 |
December | 194.67 | 23.11 | 274.33 | 23.82 | 35.00 | 23.94 |
Annual Sum or Average | 1075.67 | 24.24 | 5017.33 | 24.36 | 479.17 | 24.49 |
Minimum of Months | 42.33 | 22.76 | 213.50 | 23.45 | 12.83 | 23.49 |
Maximum of Months | 222.33 | 26.59 | 514.00 | 24.69 | 62.83 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 323.83 | 22.50 | 150.50 | 22.96 | 23.83 | 22.99 |
February | 198.50 | 22.65 | 232.83 | 23.34 | 30.67 | 23.33 |
March | 187.50 | 23.02 | 312.67 | 23.75 | 37.33 | 23.82 |
April | 53.67 | 24.35 | 416.50 | 24.28 | 26.33 | 24.34 |
May | 76.00 | 25.97 | 507.33 | 24.61 | 76.00 | 24.77 |
June | 58.83 | 26.28 | 496.00 | 24.61 | 58.83 | 24.77 |
July | 61.67 | 26.38 | 497.00 | 24.72 | 61.67 | 24.89 |
August | 62.50 | 26.03 | 511.67 | 24.55 | 62.50 | 24.70 |
September | 64.50 | 26.11 | 485.00 | 24.63 | 64.50 | 24.78 |
October | 65.00 | 25.69 | 487.17 | 24.55 | 62.33 | 24.67 |
November | 129.17 | 23.72 | 372.67 | 24.09 | 45.83 | 24.20 |
December | 289.50 | 22.72 | 219.33 | 23.32 | 54.17 | 23.42 |
Annual Sum or Average | 1570.67 | 23.67 | 4688.67 | 24.16 | 604.00 | 24.28 |
Minimum of Months | 53.67 | 22.50 | 150.50 | 22.96 | 23.83 | 22.99 |
Maximum of Months | 323.83 | 26.38 | 511.67 | 24.72 | 76.00 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 243.33 | 22.58 | 197.17 | 23.31 | 17.17 | 23.36 |
February | 153.50 | 22.75 | 257.83 | 23.61 | 22.50 | 23.64 |
March | 132.00 | 23.37 | 345.00 | 24.00 | 34.17 | 24.08 |
April | 71.67 | 25.10 | 420.00 | 24.49 | 46.33 | 24.64 |
May | 75.00 | 26.17 | 500.00 | 24.63 | 74.83 | 24.81 |
June | 63.17 | 26.49 | 496.00 | 24.66 | 63.17 | 24.85 |
July | 71.67 | 26.71 | 497.00 | 24.83 | 71.67 | 25.04 |
August | 68.00 | 25.94 | 498.67 | 24.58 | 61.17 | 24.75 |
September | 66.83 | 26.49 | 480.67 | 24.71 | 66.83 | 24.90 |
October | 72.50 | 26.03 | 474.67 | 24.65 | 68.17 | 24.82 |
November | 98.17 | 23.89 | 383.33 | 24.16 | 38.17 | 24.27 |
December | 274.50 | 22.66 | 213.00 | 23.34 | 39.67 | 23.45 |
Annual Sum or Average | 1390.33 | 24.03 | 4763.33 | 24.29 | 603.83 | 24.45 |
Minimum of Months | 63.17 | 22.58 | 197.17 | 23.31 | 17.17 | 23.36 |
Maximum of Months | 274.50 | 26.71 | 500.00 | 24.83 | 74.83 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 142.83 | 23.66 | 346.00 | 24.21 | 39.50 | 24.36 |
February | 102.33 | 23.84 | 343.83 | 24.24 | 40.67 | 24.34 |
March | 112.67 | 23.92 | 389.00 | 24.23 | 43.83 | 24.36 |
April | 51.67 | 25.42 | 435.83 | 24.47 | 40.83 | 24.59 |
May | 75.67 | 25.92 | 504.50 | 24.60 | 75.67 | 24.75 |
June | 56.83 | 26.13 | 496.00 | 24.57 | 56.83 | 24.71 |
July | 59.83 | 26.28 | 497.00 | 24.68 | 59.83 | 24.84 |
August | 62.67 | 26.14 | 512.00 | 24.58 | 62.67 | 24.74 |
September | 70.33 | 26.52 | 485.00 | 24.77 | 70.33 | 24.97 |
October | 84.83 | 26.58 | 498.00 | 24.88 | 84.00 | 25.10 |
November | 83.17 | 25.37 | 446.67 | 24.65 | 59.83 | 24.82 |
December | 167.67 | 24.09 | 348.83 | 24.37 | 67.17 | 24.57 |
Annual Sum or Average | 1070.50 | 24.99 | 5302.67 | 24.53 | 701.17 | 24.70 |
Minimum of Months | 51.67 | 23.66 | 343.83 | 24.21 | 39.50 | 24.34 |
Maximum of Months | 167.67 | 26.58 | 512.00 | 24.88 | 84.00 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 286.67 | 22.37 | 170.50 | 23.00 | 15.83 | 23.02 |
February | 171.50 | 22.74 | 250.17 | 23.56 | 30.83 | 23.61 |
March | 141.67 | 23.14 | 353.50 | 23.97 | 34.50 | 24.09 |
April | 55.67 | 25.49 | 433.83 | 24.52 | 41.33 | 24.66 |
May | 68.50 | 26.24 | 498.33 | 24.63 | 68.50 | 24.80 |
June | 49.17 | 26.53 | 494.83 | 24.58 | 49.17 | 24.74 |
July | 57.83 | 26.66 | 497.00 | 24.73 | 57.83 | 24.91 |
August | 61.67 | 26.34 | 503.33 | 24.63 | 61.50 | 24.80 |
September | 56.17 | 26.45 | 476.50 | 24.64 | 56.17 | 24.81 |
October | 69.83 | 25.93 | 473.83 | 24.63 | 62.00 | 24.81 |
November | 105.67 | 23.68 | 374.67 | 24.13 | 37.50 | 24.24 |
December | 250.50 | 22.71 | 239.00 | 23.48 | 40.17 | 23.61 |
Annual Sum or Average | 1374.83 | 23.83 | 4765.50 | 24.25 | 555.33 | 24.40 |
Minimum of Months | 49.17 | 22.37 | 170.50 | 23.00 | 15.83 | 23.02 |
Maximum of Months | 286.67 | 26.66 | 503.33 | 24.73 | 68.50 | 24.91 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.33 | 27.00 | 502.00 | 27.00 | 9.33 | 27.00 |
February | 54.83 | 27.00 | 454.00 | 27.00 | 54.83 | 27.00 |
March | 193.17 | 27.00 | 514.00 | 27.00 | 193.17 | 27.00 |
April | 367.00 | 27.00 | 485.00 | 27.00 | 367.00 | 27.00 |
May | 71.67 | 27.00 | 508.00 | 27.00 | 71.67 | 27.00 |
June | 201.83 | 27.00 | 496.00 | 27.00 | 201.83 | 27.00 |
July | 327.33 | 27.00 | 497.00 | 27.00 | 327.33 | 27.00 |
August | 499.33 | 27.10 | 514.00 | 27.10 | 499.33 | 27.10 |
September | 126.17 | 27.00 | 485.00 | 27.00 | 126.17 | 27.00 |
October | 191.33 | 27.00 | 502.00 | 27.00 | 191.33 | 27.00 |
November | 230.50 | 27.00 | 489.00 | 27.00 | 230.50 | 27.00 |
December | 287.33 | 27.00 | 497.00 | 27.00 | 287.33 | 27.00 |
Annual Sum or Average | 2559.83 | 27.02 | 5943.00 | 27.01 | 2559.83 | 27.01 |
Minimum of Months | 9.33 | 27.00 | 454.00 | 27.00 | 9.33 | 27.00 |
Maximum of Months | 499.33 | 27.10 | 514.00 | 27.10 | 499.33 | 27.10 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 3.00 | 27.00 | 454.00 | 27.00 | 3.00 | 27.00 |
March | 3.83 | 27.00 | 514.00 | 27.00 | 3.83 | 27.00 |
April | 42.83 | 27.01 | 485.00 | 27.00 | 42.83 | 27.00 |
May | 1.67 | 27.00 | 508.00 | 27.00 | 1.67 | 27.00 |
June | 3.17 | 27.00 | 496.00 | 27.00 | 3.17 | 27.00 |
July | 28.00 | 27.00 | 497.00 | 27.00 | 28.00 | 27.00 |
August | 138.33 | 27.27 | 514.00 | 27.12 | 138.33 | 27.14 |
September | 5.50 | 27.00 | 485.00 | 27.00 | 5.50 | 27.00 |
October | 5.50 | 27.00 | 502.00 | 27.00 | 5.50 | 27.00 |
November | 8.17 | 27.00 | 489.00 | 27.00 | 8.17 | 27.00 |
December | 13.50 | 27.00 | 497.00 | 27.00 | 13.50 | 27.00 |
Annual Sum or Average | 253.50 | 27.15 | 5943.00 | 27.01 | 253.50 | 27.02 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 138.33 | 27.27 | 514.00 | 27.12 | 138.33 | 27.14 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 27.00 | 502.00 | 27.00 | 0.33 | 27.00 |
February | 6.50 | 27.00 | 450.83 | 27.00 | 6.50 | 27.00 |
March | 34.00 | 27.00 | 514.00 | 27.00 | 34.00 | 27.00 |
April | 112.33 | 27.00 | 485.00 | 27.00 | 112.33 | 27.00 |
May | 69.67 | 27.00 | 508.00 | 27.00 | 69.67 | 27.00 |
June | 86.67 | 27.00 | 496.00 | 27.00 | 86.67 | 27.00 |
July | 159.00 | 27.00 | 497.00 | 27.00 | 159.00 | 27.00 |
August | 186.33 | 27.16 | 514.00 | 27.09 | 186.33 | 27.10 |
September | 77.00 | 27.00 | 485.00 | 27.00 | 77.00 | 27.00 |
October | 63.83 | 27.00 | 502.00 | 27.00 | 63.83 | 27.00 |
November | 41.50 | 27.00 | 489.00 | 27.00 | 41.50 | 27.00 |
December | 29.83 | 27.00 | 497.00 | 27.00 | 29.83 | 27.00 |
Annual Sum or Average | 867.00 | 27.04 | 5939.83 | 27.01 | 867.00 | 27.01 |
Minimum of Months | 0.33 | 27.00 | 450.83 | 27.00 | 0.33 | 27.00 |
Maximum of Months | 186.33 | 27.16 | 514.00 | 27.09 | 186.33 | 27.10 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.43 | 485.00 | 27.43 | 485.00 | 27.43 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 28.91 | 514.00 | 28.91 | 514.00 | 28.91 |
September | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.17 | 497.00 | 27.17 | 497.00 | 27.17 |
Annual Sum or Average | 5943.00 | 27.22 | 5943.00 | 27.22 | 5943.00 | 27.22 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 28.91 | 514.00 | 28.91 | 514.00 | 28.91 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00060 | 37.41441 | 0.95554 | 24.36187 |
February | 454.00000 | 27.00141 | 36.28881 | 0.99046 | 25.80330 |
March | 514.00000 | 27.00092 | 36.45238 | 1.02695 | 27.32005 |
April | 485.00000 | 27.00160 | 38.08905 | 1.07791 | 29.53372 |
May | 508.00000 | 27.00021 | 43.35431 | 0.37117 | 7.90829 |
June | 496.00000 | 27.00308 | 41.64928 | 0.40218 | 8.40593 |
July | 497.00000 | 27.00159 | 40.55119 | 0.44385 | 9.14764 |
August | 514.00000 | 27.09753 | 39.73256 | 0.51808 | 10.74281 |
September | 485.00000 | 27.00000 | 44.74847 | 0.38349 | 8.10050 |
October | 502.00000 | 27.00263 | 40.87974 | 1.04277 | 27.97488 |
November | 489.00000 | 27.00133 | 38.33173 | 1.04748 | 28.18830 |
December | 497.00000 | 27.00028 | 36.60452 | 1.05353 | 28.46397 |
Annual Sum or Average | 5943.00000 | 27.00957 | 39.52325 | 0.77405 | 19.59759 |
Minimum of Months | 454.00000 | 27.00000 | 36.28881 | 0.37117 | 7.90829 |
Maximum of Months | 514.00000 | 27.09753 | 44.74847 | 1.07791 | 29.53372 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00033 | 37.67457 | 0.90066 | 22.23009 |
February | 454.00000 | 27.00135 | 36.34606 | 0.91818 | 22.92631 |
March | 514.00000 | 27.00095 | 36.44555 | 0.94944 | 24.12230 |
April | 485.00000 | 27.00134 | 38.05566 | 0.99481 | 25.93210 |
May | 508.00000 | 27.00007 | 43.63579 | 0.32474 | 7.23754 |
June | 496.00000 | 27.00309 | 41.76280 | 0.33366 | 7.35444 |
July | 497.00000 | 27.00168 | 40.59172 | 0.35159 | 7.61310 |
August | 514.00000 | 27.07562 | 39.76792 | 0.38456 | 8.19832 |
September | 485.00000 | 27.00000 | 45.11797 | 0.33411 | 7.36216 |
October | 502.00000 | 27.00261 | 40.98602 | 0.99078 | 25.75769 |
November | 489.00000 | 27.00136 | 38.35367 | 0.96923 | 24.89338 |
December | 497.00000 | 27.00031 | 36.57189 | 0.94561 | 23.95517 |
Annual Sum or Average | 5943.00000 | 27.00763 | 39.62448 | 0.69757 | 17.23804 |
Minimum of Months | 454.00000 | 27.00000 | 36.34606 | 0.32474 | 7.23754 |
Maximum of Months | 514.00000 | 27.07562 | 45.11797 | 0.99481 | 25.93210 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00030 | 37.86851 | 0.87673 | 21.40065 |
February | 454.00000 | 27.00137 | 36.39267 | 0.90454 | 22.49681 |
March | 514.00000 | 27.00097 | 36.47687 | 0.94468 | 23.99575 |
April | 485.00000 | 27.00127 | 38.08726 | 1.00183 | 26.25667 |
May | 508.00000 | 27.00017 | 43.56723 | 0.34332 | 7.54150 |
June | 496.00000 | 27.00314 | 41.74989 | 0.35522 | 7.70145 |
July | 497.00000 | 27.00165 | 40.59887 | 0.37818 | 8.06457 |
August | 514.00000 | 27.05996 | 39.80491 | 0.39938 | 8.49497 |
September | 485.00000 | 27.00000 | 45.03844 | 0.35223 | 7.66351 |
October | 502.00000 | 27.00264 | 41.00938 | 0.99786 | 26.07466 |
November | 489.00000 | 27.00138 | 38.39393 | 0.96424 | 24.73968 |
December | 497.00000 | 27.00035 | 36.61868 | 0.92648 | 23.26662 |
Annual Sum or Average | 5943.00000 | 27.00628 | 39.64927 | 0.70163 | 17.25021 |
Minimum of Months | 454.00000 | 27.00000 | 36.39267 | 0.34332 | 7.54150 |
Maximum of Months | 514.00000 | 27.05996 | 45.03844 | 1.00183 | 26.25667 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00240 | 36.94925 | 1.17208 | 33.91280 |
February | 454.00000 | 27.00217 | 36.65383 | 1.31268 | 40.93790 |
March | 514.00000 | 27.00140 | 36.93080 | 1.44612 | 47.98844 |
April | 485.00000 | 27.43226 | 38.03896 | 1.67065 | 60.06211 |
May | 508.00000 | 27.00487 | 40.73272 | 0.62207 | 13.15534 |
June | 496.00000 | 27.00387 | 40.17281 | 0.82348 | 19.32010 |
July | 497.00000 | 27.00161 | 39.88354 | 1.02539 | 27.21717 |
August | 514.00000 | 28.90713 | 38.28855 | 1.77150 | 65.12741 |
September | 485.00000 | 27.00581 | 41.50389 | 0.66118 | 14.23435 |
October | 502.00000 | 27.00323 | 39.71575 | 1.35510 | 43.13929 |
November | 489.00000 | 27.00137 | 38.18509 | 1.47895 | 49.76101 |
December | 497.00000 | 27.16758 | 36.96970 | 1.62595 | 57.72710 |
Annual Sum or Average | 5943.00000 | 27.21646 | 38.67646 | 1.24765 | 39.41736 |
Minimum of Months | 454.00000 | 27.00137 | 36.65383 | 0.62207 | 13.15534 |
Maximum of Months | 514.00000 | 28.90713 | 41.50389 | 1.77150 | 65.12741 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.60853 | 52.72998 | 0.63148 | 14.37916 |
February | 454.00000 | 24.58116 | 53.10770 | 0.62495 | 14.07020 |
March | 514.00000 | 24.46953 | 54.82838 | 0.61142 | 13.62100 |
April | 485.00000 | 24.55942 | 60.54963 | 0.66957 | 15.20333 |
May | 508.00000 | 24.53800 | 63.38352 | -0.1546 | 6.92603 |
June | 496.00000 | 24.49105 | 63.27465 | -0.1674 | 6.82306 |
July | 497.00000 | 24.64199 | 62.14059 | -0.1250 | 6.99593 |
August | 514.00000 | 24.50117 | 61.71375 | -0.1576 | 6.89393 |
September | 485.00000 | 24.57930 | 62.41578 | -0.1372 | 7.01828 |
October | 502.00000 | 24.63522 | 61.18743 | 0.70416 | 16.39243 |
November | 489.00000 | 24.63940 | 59.00222 | 0.68969 | 15.84538 |
December | 497.00000 | 24.63394 | 54.91469 | 0.65640 | 15.09550 |
Annual Sum or Average | 5943.00000 | 24.57262 | 59.13679 | 0.31726 | 11.57460 |
Minimum of Months | 454.00000 | 24.46953 | 52.72998 | -0.1674 | 6.82306 |
Maximum of Months | 514.00000 | 24.64199 | 63.38352 | 0.70416 | 16.39243 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.38365 | 49.26636 | 0.55774 | 11.96026 |
February | 454.00000 | 24.37570 | 49.57030 | 0.56473 | 12.11463 |
March | 514.00000 | 24.26496 | 50.55846 | 0.55421 | 11.71158 |
April | 485.00000 | 24.22540 | 54.82163 | 0.58184 | 12.20923 |
May | 508.00000 | 24.27337 | 56.36782 | -0.2647 | 6.79496 |
June | 496.00000 | 24.20706 | 56.36066 | -0.2749 | 6.77085 |
July | 497.00000 | 24.23470 | 55.92641 | -0.2615 | 6.61672 |
August | 514.00000 | 24.19190 | 55.53235 | -0.2635 | 6.60874 |
September | 485.00000 | 24.27048 | 55.64304 | -0.2659 | 6.81260 |
October | 502.00000 | 24.31561 | 54.62100 | 0.59700 | 12.68593 |
November | 489.00000 | 24.36381 | 53.28638 | 0.60022 | 12.81675 |
December | 497.00000 | 24.34328 | 50.85588 | 0.57593 | 12.25791 |
Annual Sum or Average | 5943.00000 | 24.28667 | 53.58909 | 0.22172 | 9.92309 |
Minimum of Months | 454.00000 | 24.19190 | 49.26636 | -0.2749 | 6.60874 |
Maximum of Months | 514.00000 | 24.38365 | 56.36782 | 0.60022 | 12.81675 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.23265 | 50.03123 | 0.50134 | 10.57942 |
February | 454.00000 | 24.23271 | 50.53360 | 0.50697 | 10.79829 |
March | 514.00000 | 24.23357 | 51.25573 | 0.51897 | 10.96481 |
April | 485.00000 | 24.24710 | 55.85378 | 0.55801 | 11.73557 |
May | 508.00000 | 24.25076 | 56.79199 | -0.2958 | 7.15390 |
June | 496.00000 | 24.21663 | 56.83617 | -0.3022 | 7.20243 |
July | 497.00000 | 24.21597 | 56.75524 | -0.3056 | 7.21559 |
August | 514.00000 | 24.20932 | 56.73130 | -0.3065 | 7.22946 |
September | 485.00000 | 24.23736 | 55.99233 | -0.3035 | 7.26983 |
October | 502.00000 | 24.29364 | 55.08553 | 0.56964 | 12.03834 |
November | 489.00000 | 24.33161 | 54.44329 | 0.56755 | 12.04934 |
December | 497.00000 | 24.22278 | 51.77420 | 0.51194 | 10.77088 |
Annual Sum or Average | 5943.00000 | 24.24357 | 54.36051 | 0.18179 | 9.56823 |
Minimum of Months | 454.00000 | 24.20932 | 50.03123 | -0.3065 | 7.15390 |
Maximum of Months | 514.00000 | 24.33161 | 56.83617 | 0.56964 | 12.04934 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.94274 | 51.44638 | 0.42460 | 9.28078 |
February | 454.00000 | 24.03691 | 51.38901 | 0.45902 | 10.32662 |
March | 514.00000 | 24.16134 | 51.71700 | 0.50375 | 10.81578 |
April | 485.00000 | 24.26622 | 55.67548 | 0.57067 | 12.04899 |
May | 508.00000 | 24.30360 | 56.30117 | -0.2598 | 6.83080 |
June | 496.00000 | 24.26731 | 56.31161 | -0.2645 | 6.82413 |
July | 497.00000 | 24.30723 | 56.02084 | -0.2523 | 6.71332 |
August | 514.00000 | 24.25017 | 56.39514 | -0.2741 | 6.89874 |
September | 485.00000 | 24.30883 | 55.77165 | -0.2617 | 6.87784 |
October | 502.00000 | 24.34037 | 55.34100 | 0.58954 | 12.55381 |
November | 489.00000 | 24.25297 | 55.24596 | 0.55247 | 11.66476 |
December | 497.00000 | 24.01698 | 52.97547 | 0.45852 | 9.94558 |
Annual Sum or Average | 5943.00000 | 24.20544 | 54.56459 | 0.18423 | 9.21628 |
Minimum of Months | 454.00000 | 23.94274 | 51.38901 | -0.2741 | 6.71332 |
Maximum of Months | 514.00000 | 24.34037 | 56.39514 | 0.58954 | 12.55381 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.99639 | 49.84762 | 0.43736 | 9.66228 |
February | 454.00000 | 24.10280 | 49.86831 | 0.48309 | 10.56960 |
March | 514.00000 | 24.13582 | 50.79566 | 0.50926 | 10.98427 |
April | 485.00000 | 24.23170 | 54.51357 | 0.58530 | 12.39639 |
May | 508.00000 | 24.38621 | 56.26807 | -0.1890 | 6.52351 |
June | 496.00000 | 24.34441 | 55.84612 | -0.1779 | 6.27994 |
July | 497.00000 | 24.42802 | 55.13384 | -0.1452 | 6.27877 |
August | 514.00000 | 24.29249 | 55.14031 | -0.1933 | 6.36027 |
September | 485.00000 | 24.38941 | 55.26028 | -0.1931 | 6.51245 |
October | 502.00000 | 24.37595 | 54.57426 | 0.61892 | 13.41624 |
November | 489.00000 | 24.27182 | 53.27690 | 0.57002 | 12.06950 |
December | 497.00000 | 24.11266 | 51.50621 | 0.49524 | 10.64237 |
Annual Sum or Average | 5943.00000 | 24.25637 | 53.52310 | 0.23064 | 9.29000 |
Minimum of Months | 454.00000 | 23.99639 | 49.84762 | -0.1933 | 6.27877 |
Maximum of Months | 514.00000 | 24.42802 | 56.26807 | 0.61892 | 13.41624 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.91474 | 49.60514 | 0.45276 | 10.29588 |
February | 454.00000 | 24.00949 | 49.88264 | 0.49428 | 10.90541 |
March | 514.00000 | 23.97998 | 50.88198 | 0.51127 | 11.09136 |
April | 485.00000 | 24.10627 | 54.67682 | 0.59082 | 12.83211 |
May | 508.00000 | 24.32574 | 56.10822 | -0.1643 | 6.43331 |
June | 496.00000 | 24.28642 | 55.81124 | -0.1649 | 6.27750 |
July | 497.00000 | 24.37301 | 55.12114 | -0.1311 | 6.52345 |
August | 514.00000 | 24.15305 | 55.46275 | -0.2161 | 6.61415 |
September | 485.00000 | 24.37759 | 54.97219 | -0.1526 | 6.49427 |
October | 502.00000 | 24.27896 | 54.49733 | 0.62596 | 13.66093 |
November | 489.00000 | 24.10206 | 53.51419 | 0.55249 | 11.70555 |
December | 497.00000 | 23.72358 | 52.39422 | 0.42622 | 9.52133 |
Annual Sum or Average | 5943.00000 | 24.13630 | 53.59853 | 0.23250 | 9.34399 |
Minimum of Months | 454.00000 | 23.72358 | 49.60514 | -0.2161 | 6.27750 |
Maximum of Months | 514.00000 | 24.37759 | 56.10822 | 0.62596 | 13.66093 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.39023 | 48.10959 | 0.59440 | 13.50726 |
February | 454.00000 | 24.40756 | 48.62506 | 0.61135 | 13.83590 |
March | 514.00000 | 24.26984 | 50.05064 | 0.58400 | 12.83694 |
April | 485.00000 | 24.30778 | 54.14832 | 0.62064 | 13.47040 |
May | 508.00000 | 24.38351 | 56.29365 | -0.1914 | 6.56554 |
June | 496.00000 | 24.32456 | 55.96622 | -0.1948 | 6.37151 |
July | 497.00000 | 24.41324 | 55.20844 | -0.1559 | 6.34002 |
August | 514.00000 | 24.31198 | 55.01213 | -0.1748 | 6.33231 |
September | 485.00000 | 24.48652 | 54.73076 | -0.1205 | 6.56689 |
October | 502.00000 | 24.55291 | 53.57563 | 0.71176 | 16.43233 |
November | 489.00000 | 24.53040 | 52.03385 | 0.68895 | 15.67531 |
December | 497.00000 | 24.40763 | 50.01402 | 0.62878 | 14.34066 |
Annual Sum or Average | 5943.00000 | 24.39810 | 52.83980 | 0.29686 | 10.99131 |
Minimum of Months | 454.00000 | 24.26984 | 48.10959 | -0.1948 | 6.33231 |
Maximum of Months | 514.00000 | 24.55291 | 56.29365 | 0.71176 | 16.43233 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.09831 | 48.84983 | 0.52628 | 11.65364 |
February | 454.00000 | 24.40971 | 48.40946 | 0.63783 | 14.55686 |
March | 514.00000 | 24.42374 | 49.23980 | 0.68750 | 15.76088 |
April | 485.00000 | 24.49808 | 53.10135 | 0.77953 | 18.49148 |
May | 508.00000 | 24.45399 | 55.42509 | -0.0634 | 6.21843 |
June | 496.00000 | 24.41482 | 55.10800 | -0.0461 | 6.03475 |
July | 497.00000 | 24.54145 | 54.27411 | 0.03246 | 6.41855 |
August | 514.00000 | 24.46105 | 53.96190 | 0.04650 | 6.33471 |
September | 485.00000 | 24.45895 | 54.50933 | -0.0736 | 6.27404 |
October | 502.00000 | 24.52486 | 53.39383 | 0.73997 | 17.19872 |
November | 489.00000 | 24.52016 | 51.79583 | 0.72203 | 16.57494 |
December | 497.00000 | 24.52500 | 49.42835 | 0.69953 | 16.18666 |
Annual Sum or Average | 5943.00000 | 24.44397 | 52.31345 | 0.38814 | 11.77070 |
Minimum of Months | 454.00000 | 24.09831 | 48.40946 | -0.0736 | 6.03475 |
Maximum of Months | 514.00000 | 24.54145 | 55.42509 | 0.77953 | 18.49148 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.49145 | 51.73536 | 0.30636 | 8.05987 |
February | 454.00000 | 23.70471 | 51.98684 | 0.37448 | 9.24180 |
March | 514.00000 | 23.88846 | 53.02166 | 0.43636 | 10.17558 |
April | 485.00000 | 24.22188 | 56.32820 | 0.56123 | 11.94314 |
May | 508.00000 | 24.40647 | 58.10656 | -0.1926 | 6.76293 |
June | 496.00000 | 24.40311 | 57.54854 | -0.1741 | 6.58653 |
July | 497.00000 | 24.48845 | 56.85230 | -0.1493 | 6.53346 |
August | 514.00000 | 24.36559 | 57.69878 | -0.2016 | 6.69629 |
September | 485.00000 | 24.41463 | 56.87099 | -0.1983 | 6.76860 |
October | 502.00000 | 24.39299 | 56.70457 | 0.61464 | 13.48162 |
November | 489.00000 | 24.12184 | 55.79508 | 0.52098 | 11.33731 |
December | 497.00000 | 23.63273 | 54.64805 | 0.36603 | 9.01051 |
Annual Sum or Average | 5943.00000 | 24.13014 | 55.63057 | 0.18632 | 8.87241 |
Minimum of Months | 454.00000 | 23.49145 | 51.73536 | -0.2016 | 6.53346 |
Maximum of Months | 514.00000 | 24.48845 | 58.10656 | 0.61464 | 13.48162 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.54040 | 50.81147 | 0.34989 | 9.08845 |
February | 385.00000 | 23.74507 | 51.36248 | 0.41820 | 9.95472 |
March | 433.00000 | 23.94176 | 52.45603 | 0.48952 | 11.27344 |
April | 410.00000 | 24.29412 | 55.64128 | 0.61859 | 13.95286 |
May | 430.00000 | 24.44051 | 57.70939 | -0.1414 | 6.82961 |
June | 418.00000 | 24.49260 | 57.08613 | -0.1139 | 6.69500 |
July | 422.00000 | 24.61972 | 56.10447 | -0.0703 | 7.03340 |
August | 433.00000 | 24.41549 | 57.29077 | -0.1511 | 6.83211 |
September | 410.00000 | 24.51102 | 56.31010 | -0.1254 | 6.95973 |
October | 427.00000 | 24.43266 | 56.44282 | 0.65580 | 14.92073 |
November | 417.00000 | 24.09510 | 55.54606 | 0.54287 | 12.01845 |
December | 422.00000 | 23.44278 | 54.72857 | 0.35062 | 9.23956 |
Annual Sum or Average | 5034.00000 | 24.16617 | 55.14578 | 0.23350 | 9.55750 |
Minimum of Months | 385.00000 | 23.44278 | 50.81147 | -0.1511 | 6.69500 |
Maximum of Months | 433.00000 | 24.61972 | 57.70939 | 0.65580 | 14.92073 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32730 | 48.54435 | 0.57198 | 13.19640 |
February | 454.00000 | 24.31282 | 49.62678 | 0.57936 | 13.29478 |
March | 514.00000 | 24.21570 | 51.53418 | 0.55884 | 12.56044 |
April | 485.00000 | 24.34197 | 55.71196 | 0.60910 | 13.28758 |
May | 508.00000 | 24.40171 | 58.15923 | -0.1955 | 6.78138 |
June | 496.00000 | 24.37496 | 57.75573 | -0.1942 | 6.63914 |
July | 497.00000 | 24.46744 | 56.98922 | -0.1621 | 6.55740 |
August | 514.00000 | 24.39153 | 57.49019 | -0.1783 | 6.64357 |
September | 485.00000 | 24.51797 | 56.09491 | -0.1199 | 6.82493 |
October | 502.00000 | 24.62242 | 55.14051 | 0.72448 | 17.07354 |
November | 489.00000 | 24.54261 | 53.62805 | 0.68392 | 15.81826 |
December | 497.00000 | 24.33194 | 51.51397 | 0.59762 | 14.01090 |
Annual Sum or Average | 5943.00000 | 24.40395 | 54.38115 | 0.28637 | 11.03017 |
Minimum of Months | 454.00000 | 24.21570 | 48.54435 | -0.1955 | 6.55740 |
Maximum of Months | 514.00000 | 24.62242 | 58.15923 | 0.72448 | 17.07354 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.42366 | 51.20316 | 0.33432 | 8.56058 |
February | 454.00000 | 23.76022 | 51.18591 | 0.43633 | 10.56311 |
March | 514.00000 | 23.99929 | 51.92950 | 0.52107 | 12.16184 |
April | 485.00000 | 24.34777 | 55.32842 | 0.65330 | 14.75831 |
May | 508.00000 | 24.42088 | 57.33475 | -0.1233 | 6.69609 |
June | 496.00000 | 24.40518 | 57.03104 | -0.1280 | 6.51729 |
July | 497.00000 | 24.50517 | 56.19220 | -0.0843 | 6.51219 |
August | 514.00000 | 24.41095 | 56.79523 | -0.1172 | 6.52614 |
September | 485.00000 | 24.42796 | 56.12385 | -0.1388 | 6.78591 |
October | 502.00000 | 24.42261 | 55.77382 | 0.66705 | 15.17184 |
November | 489.00000 | 24.11643 | 55.03262 | 0.56248 | 12.49116 |
December | 497.00000 | 23.65890 | 53.57482 | 0.41977 | 10.31047 |
Annual Sum or Average | 5943.00000 | 24.16058 | 54.81378 | 0.24795 | 9.73702 |
Minimum of Months | 454.00000 | 23.42366 | 51.18591 | -0.1388 | 6.51219 |
Maximum of Months | 514.00000 | 24.50517 | 57.33475 | 0.66705 | 15.17184 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.99234 | 53.43198 | 0.18905 | 7.62996 |
February | 454.00000 | 23.38410 | 53.09559 | 0.30167 | 9.16035 |
March | 514.00000 | 23.65535 | 53.81739 | 0.38804 | 10.07022 |
April | 485.00000 | 24.15122 | 56.53404 | 0.55463 | 11.95634 |
May | 508.00000 | 24.40514 | 58.01034 | -0.1733 | 6.76720 |
June | 496.00000 | 24.41694 | 57.34496 | -0.1481 | 6.57274 |
July | 497.00000 | 24.51701 | 56.50680 | -0.1155 | 6.65116 |
August | 514.00000 | 24.36770 | 57.72878 | -0.1811 | 6.73504 |
September | 485.00000 | 24.42728 | 57.03578 | -0.1740 | 6.81962 |
October | 502.00000 | 24.36282 | 57.37701 | 0.61957 | 13.71868 |
November | 489.00000 | 23.93988 | 56.93650 | 0.48618 | 11.06820 |
December | 497.00000 | 23.22423 | 56.37000 | 0.27352 | 8.62443 |
Annual Sum or Average | 5943.00000 | 23.99053 | 56.20085 | 0.16636 | 8.80400 |
Minimum of Months | 454.00000 | 22.99234 | 53.09559 | -0.1811 | 6.57274 |
Maximum of Months | 514.00000 | 24.51701 | 58.01034 | 0.61957 | 13.71868 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.29758 | 51.97524 | 0.29508 | 8.75891 |
February | 454.00000 | 23.58038 | 52.03565 | 0.38783 | 9.99451 |
March | 514.00000 | 23.85633 | 52.70311 | 0.48246 | 11.34215 |
April | 485.00000 | 24.22770 | 55.68832 | 0.62658 | 14.19377 |
May | 508.00000 | 24.38234 | 57.44657 | -0.1213 | 6.73163 |
June | 496.00000 | 24.42902 | 56.80193 | -0.0931 | 6.57226 |
July | 497.00000 | 24.55735 | 55.81155 | -0.0456 | 7.04386 |
August | 514.00000 | 24.35490 | 57.17472 | -0.1316 | 6.79324 |
September | 485.00000 | 24.45048 | 56.22115 | -0.1056 | 6.89338 |
October | 502.00000 | 24.36899 | 56.53923 | 0.66307 | 15.13322 |
November | 489.00000 | 23.97766 | 56.14358 | 0.52915 | 11.90975 |
December | 497.00000 | 23.23024 | 55.72028 | 0.30456 | 9.09180 |
Annual Sum or Average | 5943.00000 | 24.06228 | 55.37504 | 0.23048 | 9.52432 |
Minimum of Months | 454.00000 | 23.23024 | 51.97524 | -0.1316 | 6.57226 |
Maximum of Months | 514.00000 | 24.55735 | 57.44657 | 0.66307 | 15.13322 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.01721 | 49.78076 | 0.49586 | 12.12350 |
February | 454.00000 | 24.08991 | 50.50039 | 0.52854 | 12.75363 |
March | 514.00000 | 24.06078 | 52.19620 | 0.52825 | 12.38700 |
April | 485.00000 | 24.27802 | 55.90934 | 0.60487 | 13.34645 |
May | 508.00000 | 24.39217 | 58.08069 | -0.1790 | 6.79905 |
June | 496.00000 | 24.38600 | 57.55603 | -0.1698 | 6.60902 |
July | 497.00000 | 24.49025 | 56.64866 | -0.1306 | 6.65155 |
August | 514.00000 | 24.38741 | 57.53033 | -0.1594 | 6.69597 |
September | 485.00000 | 24.51838 | 56.29721 | -0.0976 | 6.91507 |
October | 502.00000 | 24.58572 | 55.82799 | 0.72991 | 17.31678 |
November | 489.00000 | 24.40376 | 54.62779 | 0.66004 | 15.41892 |
December | 497.00000 | 24.07054 | 52.88909 | 0.53809 | 13.31405 |
Annual Sum or Average | 5943.00000 | 24.30741 | 54.84914 | 0.27613 | 10.83618 |
Minimum of Months | 454.00000 | 24.01721 | 49.78076 | -0.1790 | 6.60902 |
Maximum of Months | 514.00000 | 24.58572 | 58.08069 | 0.72991 | 17.31678 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.02930 | 52.67926 | 0.24196 | 8.06209 |
February | 454.00000 | 23.49121 | 52.18104 | 0.37685 | 10.29485 |
March | 514.00000 | 23.80494 | 52.66370 | 0.48284 | 11.99836 |
April | 485.00000 | 24.26290 | 55.58158 | 0.64546 | 14.74080 |
May | 508.00000 | 24.38279 | 57.37502 | -0.1139 | 6.88241 |
June | 496.00000 | 24.38518 | 56.94610 | -0.1120 | 6.59629 |
July | 497.00000 | 24.50211 | 55.98986 | -0.0604 | 6.73687 |
August | 514.00000 | 24.39220 | 56.92335 | -0.1025 | 6.69573 |
September | 485.00000 | 24.40466 | 56.41463 | -0.1246 | 7.00241 |
October | 502.00000 | 24.36487 | 56.52079 | 0.66714 | 15.31792 |
November | 489.00000 | 23.93914 | 56.15478 | 0.53052 | 12.18099 |
December | 497.00000 | 23.33166 | 55.12486 | 0.34691 | 9.86554 |
Annual Sum or Average | 5943.00000 | 24.02745 | 55.39795 | 0.22951 | 9.68211 |
Minimum of Months | 454.00000 | 23.02930 | 52.18104 | -0.1246 | 6.59629 |
Maximum of Months | 514.00000 | 24.50211 | 57.37502 | 0.66714 | 15.31792 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.134483E+12 | 215850.02 | 07-JAN-06:03 | 490.38 | 0.871406E+12 | 0.00 | 0.100589E+13 | 3.95 | 7.77 | 30-JAN-06:03 | 0.00 | 0.00 |
February | 0.133289E+12 | 225196.00 | 11-FEB-06:04 | 452.78 | 0.873784E+12 | 0.00 | 0.100707E+13 | 4.13 | 7.78 | 21-FEB-06:04 | 0.00 | 0.00 |
March | 0.164874E+12 | 216669.33 | 06-MAR-06:03 | 571.77 | 0.108281E+13 | 0.00 | 0.124769E+13 | 4.66 | 7.71 | 28-MAR-05:02 | 0.00 | 0.00 |
April | 0.184342E+12 | 184623.43 | 22-APR-05:03 | 626.37 | 0.121610E+13 | 0.00 | 0.140044E+13 | 5.29 | 7.71 | 26-APR-05:02 | 0.00 | 0.00 |
May | 0.215638E+12 | 239946.63 | 31-MAY-05:03 | 584.16 | 0.142920E+13 | 0.00 | 0.164484E+13 | 4.98 | 7.64 | 08-MAY-05:03 | 0.00 | 0.00 |
June | 0.226217E+12 | 236873.53 | 01-JUN-05:05 | 618.10 | 0.145554E+13 | 0.00 | 0.168176E+13 | 5.24 | 7.40 | 13-JUN-04:03 | 0.00 | 0.00 |
July | 0.241128E+12 | 239164.09 | 17-JUL-05:02 | 676.85 | 0.153222E+13 | 0.00 | 0.177335E+13 | 5.44 | 7.51 | 18-JUL-04:03 | 0.00 | 0.00 |
August | 0.243816E+12 | 246426.31 | 15-AUG-05:03 | 694.76 | 0.155273E+13 | 0.00 | 0.179654E+13 | 5.56 | 7.40 | 29-AUG-05:03 | 0.00 | 0.00 |
September | 0.222963E+12 | 246271.21 | 22-SEP-05:03 | 589.49 | 0.144408E+13 | 0.00 | 0.166704E+13 | 5.08 | 7.50 | 05-SEP-03:02 | 0.00 | 0.00 |
October | 0.214022E+12 | 243489.94 | 02-OCT-05:03 | 605.28 | 0.140237E+13 | 0.00 | 0.161640E+13 | 5.03 | 7.69 | 20-OCT-05:03 | 0.00 | 0.00 |
November | 0.181073E+12 | 220265.94 | 29-NOV-06:04 | 562.09 | 0.119321E+13 | 0.00 | 0.137429E+13 | 4.79 | 7.74 | 09-NOV-06:03 | 0.00 | 0.00 |
December | 0.149184E+12 | 219474.50 | 09-DEC-06:03 | 574.44 | 0.959351E+12 | 0.00 | 0.110853E+13 | 4.51 | 7.69 | 26-DEC-06:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.231103E+13 | 7046.47 | 0.150128E+14 | 0.00 | 0.173238E+14 | 4.89 | 0.00 | 0.00 | ||||
Minimum of Months | 0.133289E+12 | 184623.43 | 452.78 | 0.871406E+12 | 0.00 | 0.100589E+13 | 3.95 | 7.40 | 0.00 | 0.00 | ||
Maximum of Months | 0.243816E+12 | 246426.31 | 694.76 | 0.155273E+13 | 0.00 | 0.179654E+13 | 5.56 | 7.78 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.118845E+11 | 215850.02 | 07-JAN-06:03 | 26.49 | 0.839010E+11 | 0.00 | 0.957855E+11 | 0.25 | 7.77 | 30-JAN-06:03 | 0.00 | 0.00 |
February | 0.929438E+10 | 225196.00 | 11-FEB-06:04 | 20.98 | 0.656698E+11 | 0.00 | 0.749642E+11 | 0.22 | 7.78 | 21-FEB-06:04 | 0.00 | 0.00 |
March | 0.279347E+11 | 216669.33 | 06-MAR-06:03 | 61.96 | 0.195750E+12 | 0.00 | 0.223685E+12 | 0.58 | 7.71 | 28-MAR-05:02 | 0.00 | 0.00 |
April | 0.318849E+11 | 184623.43 | 22-APR-05:03 | 71.00 | 0.220639E+12 | 0.00 | 0.252524E+12 | 0.68 | 7.71 | 26-APR-05:02 | 0.00 | 0.00 |
May | 0.789254E+11 | 239946.63 | 31-MAY-05:03 | 171.51 | 0.540474E+12 | 0.00 | 0.619399E+12 | 1.58 | 7.64 | 08-MAY-05:03 | 0.00 | 0.00 |
June | 0.934785E+11 | 236873.53 | 01-JUN-05:05 | 198.39 | 0.627135E+12 | 0.00 | 0.720613E+12 | 1.85 | 7.40 | 13-JUN-04:03 | 0.00 | 0.00 |
July | 0.889506E+11 | 239164.09 | 17-JUL-05:02 | 184.83 | 0.590028E+12 | 0.00 | 0.678978E+12 | 1.65 | 7.51 | 18-JUL-04:03 | 0.00 | 0.00 |
August | 0.986350E+11 | 246426.31 | 15-AUG-05:03 | 206.83 | 0.657020E+12 | 0.00 | 0.755655E+12 | 1.85 | 7.40 | 29-AUG-05:03 | 0.00 | 0.00 |
September | 0.875356E+11 | 246271.21 | 22-SEP-05:03 | 184.10 | 0.587462E+12 | 0.00 | 0.674998E+12 | 1.72 | 7.50 | 05-SEP-03:02 | 0.00 | 0.00 |
October | 0.792231E+11 | 243489.94 | 02-OCT-05:03 | 169.09 | 0.540097E+12 | 0.00 | 0.619320E+12 | 1.55 | 7.69 | 20-OCT-05:03 | 0.00 | 0.00 |
November | 0.571200E+11 | 220265.94 | 29-NOV-06:04 | 123.27 | 0.394733E+12 | 0.00 | 0.451853E+12 | 1.18 | 7.74 | 09-NOV-06:03 | 0.00 | 0.00 |
December | 0.157577E+11 | 219474.50 | 09-DEC-06:03 | 34.43 | 0.110529E+12 | 0.00 | 0.126287E+12 | 0.32 | 7.69 | 26-DEC-06:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.680624E+12 | 1452.87 | 0.461344E+13 | 0.00 | 0.529406E+13 | 1.12 | 0.00 | 0.00 | ||||
Minimum of Months | 0.929438E+10 | 184623.43 | 20.98 | 0.656698E+11 | 0.00 | 0.749642E+11 | 0.22 | 7.40 | 0.00 | 0.00 | ||
Maximum of Months | 0.986350E+11 | 246426.31 | 206.83 | 0.657020E+12 | 0.00 | 0.755655E+12 | 1.85 | 7.78 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.113223E+12 | 744.00 | 49248.27 | 01-JAN-00:05 | 243317.67 | 02-JAN-15:10 | 25.80 | 21.88 | 14.26 |
February | 0.113344E+12 | 672.00 | 49248.27 | 01-FEB-00:10 | 389683.08 | 02-FEB-15:10 | 31.28 | 24.35 | 14.26 |
March | 0.129332E+12 | 744.00 | 49248.27 | 01-MAR-00:10 | 639987.66 | 31-MAR-23:43 | 36.12 | 26.21 | 14.26 |
April | 0.127652E+12 | 720.00 | 49248.27 | 01-APR-00:05 | 696589.59 | 16-APR-18:12 | 43.01 | 30.01 | 14.26 |
May | 0.131907E+12 | 744.00 | 49248.27 | 01-MAY-00:03 | 379350.27 | 31-MAY-23:30 | 32.83 | 28.39 | 14.26 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:03 | 524990.94 | 30-JUN-23:23 | 38.69 | 31.10 | 14.26 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 678786.81 | 31-JUL-24:00 | 43.58 | 32.95 | 14.26 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 713330.39 | 23-AUG-16:20 | 47.55 | 34.11 | 14.26 |
September | 0.127652E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 373439.24 | 30-SEP-23:15 | 34.11 | 29.54 | 14.26 |
October | 0.131907E+12 | 744.00 | 49248.27 | 01-OCT-00:03 | 505268.36 | 31-OCT-23:32 | 37.17 | 29.70 | 14.26 |
November | 0.126826E+12 | 720.00 | 49248.27 | 01-NOV-00:03 | 555391.21 | 03-NOV-14:10 | 38.39 | 28.22 | 14.26 |
December | 0.129815E+12 | 744.00 | 49248.27 | 01-DEC-00:10 | 690077.28 | 08-DEC-16:40 | 38.88 | 26.20 | 14.26 |
Annual Sum or Average | 0.152312E+13 | 8760.00 | 37.32 | 28.58 | 14.26 | ||||
Minimum of Months | 0.113223E+12 | 672.00 | 49248.27 | 243317.67 | 25.80 | 21.88 | 14.26 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 713330.39 | 47.55 | 34.11 | 14.26 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.146432E+11 | 418.96 | 23901.07 | 01-JAN-08:35 | 1336130.30 | 19-JAN-15:10 | 22.96 | 21.78 | 50.72 |
February | 0.159764E+11 | 407.18 | 23901.07 | 01-FEB-10:50 | 1444682.25 | 11-FEB-06:04 | 23.17 | 21.81 | 52.57 |
March | 0.252617E+11 | 520.56 | 23901.07 | 03-MAR-08:40 | 1406078.92 | 14-MAR-15:50 | 23.34 | 21.85 | 60.49 |
April | 0.332211E+11 | 600.69 | 23901.07 | 01-APR-00:55 | 1364934.96 | 18-APR-15:10 | 23.75 | 22.03 | 70.04 |
May | 0.484575E+11 | 583.30 | 23901.07 | 01-MAY-03:02 | 1723436.48 | 31-MAY-05:05 | 25.74 | 23.88 | 63.27 |
June | 0.531839E+11 | 618.10 | 23901.07 | 01-JUN-00:52 | 1698910.07 | 01-JUN-05:05 | 27.18 | 25.20 | 65.15 |
July | 0.577593E+11 | 676.85 | 23901.07 | 01-JUL-00:10 | 1542836.68 | 03-JUL-05:04 | 27.26 | 25.27 | 68.06 |
August | 0.597799E+11 | 694.76 | 23901.07 | 01-AUG-00:05 | 1406344.28 | 28-AUG-05:03 | 27.39 | 25.36 | 70.00 |
September | 0.507221E+11 | 589.49 | 23901.07 | 01-SEP-00:03 | 1619826.29 | 21-SEP-05:05 | 27.15 | 25.22 | 62.81 |
October | 0.487505E+11 | 605.28 | 23901.07 | 01-OCT-00:03 | 1671479.68 | 02-OCT-05:05 | 25.84 | 24.00 | 64.49 |
November | 0.355848E+11 | 529.66 | 23901.07 | 01-NOV-04:05 | 1450801.16 | 29-NOV-06:04 | 24.54 | 22.89 | 61.05 |
December | 0.214139E+11 | 506.74 | 23901.07 | 01-DEC-00:12 | 1456815.67 | 04-DEC-10:30 | 23.11 | 21.80 | 60.22 |
Annual Sum or Average | 0.464755E+12 | 6751.56 | 25.13 | 23.43 | 62.46 | ||||
Minimum of Months | 0.146432E+11 | 407.18 | 23901.07 | 1336130.30 | 22.96 | 21.78 | 50.72 | ||
Maximum of Months | 0.597799E+11 | 694.76 | 23901.07 | 1723436.48 | 27.39 | 25.36 | 70.04 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.247137E+10 | 28.72 | 23901.07 | 01-JAN-12:54 | 1304981.17 | 07-JAN-06:05 | 22.96 | 22.84 | 3.15 |
February | 0.195893E+10 | 22.77 | 23901.07 | 02-FEB-06:03 | 1444682.25 | 11-FEB-06:04 | 23.17 | 23.07 | 2.76 |
March | 0.553358E+10 | 64.31 | 23901.07 | 03-MAR-13:10 | 1385682.08 | 06-MAR-06:05 | 23.34 | 23.08 | 7.04 |
April | 0.670485E+10 | 77.99 | 23901.07 | 01-APR-05:05 | 1335868.38 | 21-APR-05:04 | 23.75 | 23.43 | 8.76 |
May | 0.184040E+11 | 213.89 | 23901.07 | 01-MAY-05:03 | 1723436.48 | 31-MAY-05:05 | 25.74 | 24.91 | 22.69 |
June | 0.272496E+11 | 316.69 | 23901.07 | 01-JUN-03:02 | 1698910.07 | 01-JUN-05:05 | 27.18 | 25.94 | 31.04 |
July | 0.288096E+11 | 334.83 | 23901.07 | 01-JUL-03:02 | 1542836.68 | 03-JUL-05:04 | 27.26 | 26.00 | 30.59 |
August | 0.307406E+11 | 357.27 | 23901.07 | 01-AUG-00:33 | 1406344.28 | 28-AUG-05:03 | 27.39 | 26.04 | 33.03 |
September | 0.252344E+11 | 293.27 | 23901.07 | 01-SEP-05:03 | 1619826.29 | 21-SEP-05:05 | 27.15 | 26.00 | 29.28 |
October | 0.196570E+11 | 228.45 | 23901.07 | 01-OCT-00:45 | 1671479.68 | 02-OCT-05:05 | 25.84 | 24.95 | 23.18 |
November | 0.128989E+11 | 149.91 | 23901.07 | 01-NOV-09:30 | 1450801.16 | 29-NOV-06:04 | 24.54 | 23.93 | 16.32 |
December | 0.338372E+10 | 39.35 | 23901.07 | 01-DEC-06:05 | 1452882.03 | 11-DEC-15:40 | 23.11 | 22.95 | 4.30 |
Annual Sum or Average | 0.183047E+12 | 2127.45 | 25.13 | 24.44 | 17.76 | ||||
Minimum of Months | 0.195893E+10 | 22.77 | 23901.07 | 1304981.17 | 22.96 | 22.84 | 2.76 | ||
Maximum of Months | 0.307406E+11 | 357.27 | 23901.07 | 1723436.48 | 27.39 | 26.04 | 33.03 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.414896E+09 | 0.00 | 32.35 | 151867.44 | 25-JAN-06:20 | 0.00 | 56.57 | 58.01 | 0.00 | 0.00 | 0.00 | 0.12 | 25-JAN-06:20 |
February | 0.980899E+09 | 0.00 | 27.04 | 457199.35 | 04-FEB-06:02 | 0.00 | 25.01 | 27.13 | 0.00 | 0.00 | 0.00 | 0.35 | 04-FEB-06:02 |
March | 0.442970E+09 | 0.00 | 18.44 | 221001.68 | 16-MAR-04:05 | 0.00 | 29.51 | 30.73 | 0.00 | 0.00 | 0.00 | 0.17 | 16-MAR-04:05 |
April | 264.55 | 0.00 | 0.04 | 1.76 | 03-APR-00:48 | 0.00 | 28.99 | 29.00 | 0.00 | 0.00 | 0.00 | 0.00 | 03-APR-00:48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 28.99 | 28.99 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 28.99 | 28.99 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 28.99 | 28.99 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 28.99 | 28.99 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 28.99 | 28.99 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 28.99 | 28.99 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.175718E+09 | 0.00 | 6.86 | 151317.01 | 27-NOV-06:08 | 0.00 | 28.83 | 29.30 | 0.00 | 0.00 | 0.00 | 0.12 | 27-NOV-06:08 |
December | 0.784362E+09 | 0.00 | 33.47 | 200517.88 | 27-DEC-06:06 | 0.00 | 31.40 | 33.58 | 0.00 | 0.00 | 0.00 | 0.15 | 27-DEC-06:06 |
Annual Sum or Average | 0.279885E+10 | 0.00 | 118.20 | 0.00 | 31.26 | 31.88 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 27.13 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.980899E+09 | 0.00 | 33.47 | 457199.35 | 0.00 | 56.57 | 58.01 | 0.00 | 0.00 | 0.00 | 0.35 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 25.80 | 25.80 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 31.28 | 31.28 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 36.12 | 36.12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 43.01 | 43.01 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 32.83 | 32.83 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 38.69 | 38.69 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 43.58 | 43.58 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 47.55 | 47.55 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 34.11 | 34.11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 37.17 | 37.17 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 38.39 | 38.39 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 38.88 | 38.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 37.32 | 37.32 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 25.80 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.55 | 47.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.958198E+11 | 0.00 | 451.29 | 0.775596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 256797.53 | 30-JAN-04:02 | 148210.23 | 30-JAN-04:02 | 0.00 | 0.00 | 0.00 |
February | 0.107495E+12 | 0.00 | 424.80 | 0.867029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 250342.57 | 11-FEB-06:02 | 144694.10 | 10-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.144697E+12 | 0.00 | 550.40 | 0.112100E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 242966.03 | 10-MAR-06:02 | 146265.32 | 29-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.168492E+12 | 0.00 | 599.20 | 0.131043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 228963.26 | 11-APR-05:02 | 146732.92 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.184192E+12 | 0.00 | 543.89 | 0.132186E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 279321.64 | 27-MAY-03:02 | 156713.06 | 20-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.209250E+12 | 0.00 | 577.86 | 0.145276E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 265289.15 | 12-JUN-04:33 | 160156.46 | 09-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.225873E+12 | 0.00 | 624.39 | 0.157099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 263174.63 | 03-JUL-05:02 | 161801.84 | 10-JUL-05:03 | 0.00 | 0.00 | 0.00 |
August | 0.246060E+12 | 0.00 | 652.96 | 0.171106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 255080.24 | 24-AUG-04:03 | 165361.57 | 21-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.197144E+12 | 0.00 | 538.83 | 0.133199E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 281829.25 | 21-SEP-03:02 | 164441.48 | 11-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.194390E+12 | 0.00 | 561.45 | 0.136151E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 263348.65 | 31-OCT-03:02 | 158356.96 | 18-OCT-05:03 | 0.00 | 0.00 | 0.00 |
November | 0.165306E+12 | 0.00 | 528.72 | 0.119506E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 260897.25 | 04-NOV-05:03 | 155722.89 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.132007E+12 | 0.00 | 541.94 | 0.989925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 248352.77 | 09-DEC-06:03 | 144625.17 | 09-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207073E+13 | 0.00 | 6595.72 | 0.150092E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.958198E+11 | 0.00 | 424.80 | 0.775596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 228963.26 | 144625.17 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.246060E+12 | 0.00 | 652.96 | 0.171106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 281829.25 | 165361.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.778612E+12 | 0.00 | 417.00 | 0.613634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2463413.72 | 14-JAN-05:02 | 1239443.59 | 14-JAN-05:02 | 0.00 | 0.00 | 0.00 |
February | 0.841014E+12 | 0.00 | 382.77 | 0.662897E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2590794.21 | 11-FEB-06:02 | 1333372.45 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.105107E+13 | 0.00 | 451.53 | 0.810697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2565338.29 | 06-MAR-04:02 | 1379375.97 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.120045E+13 | 0.00 | 457.96 | 0.929218E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2659078.56 | 13-APR-03:02 | 1391850.43 | 13-APR-03:02 | 0.00 | 0.00 | 0.00 |
May | 0.159385E+13 | 0.00 | 489.09 | 0.113127E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2769367.52 | 27-MAY-05:02 | 1484731.62 | 16-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.173728E+13 | 0.00 | 495.73 | 0.118586E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3001811.29 | 19-JUN-03:02 | 1523932.61 | 08-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.177501E+13 | 0.00 | 512.51 | 0.120998E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2895456.36 | 03-JUL-03:02 | 1506923.79 | 14-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.182867E+13 | 0.00 | 516.17 | 0.123097E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2857357.77 | 28-AUG-03:02 | 1517459.77 | 22-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.172073E+13 | 0.00 | 488.25 | 0.113371E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2859545.72 | 21-SEP-03:02 | 1524109.69 | 11-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.157220E+13 | 0.00 | 475.08 | 0.108549E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3045230.76 | 02-OCT-03:02 | 1485107.64 | 03-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.124683E+13 | 0.00 | 430.57 | 0.883893E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2755354.34 | 04-NOV-03:02 | 1443090.52 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.852869E+12 | 0.00 | 415.47 | 0.644747E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2528781.93 | 26-DEC-04:02 | 1402688.34 | 01-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161986E+14 | 0.00 | 5532.12 | 0.115224E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.778612E+12 | 0.00 | 382.77 | 0.613634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2463413.72 | 1239443.59 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.182867E+13 | 0.00 | 516.17 | 0.123097E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3045230.76 | 1524109.69 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.728920E+11 | 0.00 | 399.21 | 0.570088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 253662.09 | 14-JAN-06:03 | 130824.59 | 14-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.846920E+11 | 0.00 | 371.07 | 0.669116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 265627.59 | 11-FEB-06:02 | 133316.61 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.110267E+12 | 0.00 | 440.49 | 0.850037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 268510.13 | 06-MAR-04:02 | 136001.91 | 14-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.131479E+12 | 0.00 | 453.89 | 0.103025E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 272436.06 | 13-APR-03:02 | 139719.22 | 13-APR-03:02 | 0.00 | 0.00 | 0.00 |
May | 0.178238E+12 | 0.00 | 496.57 | 0.129608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 288792.33 | 27-MAY-05:02 | 155276.92 | 23-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.196247E+12 | 0.00 | 511.73 | 0.137405E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 295029.13 | 20-JUN-03:02 | 161188.58 | 17-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.202715E+12 | 0.00 | 529.47 | 0.142629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 300276.90 | 03-JUL-03:02 | 159056.41 | 31-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.202837E+12 | 0.00 | 526.76 | 0.140600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 286262.39 | 04-AUG-03:02 | 160115.40 | 16-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.189559E+12 | 0.00 | 499.85 | 0.129110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 297510.11 | 20-SEP-03:02 | 164686.97 | 29-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.165847E+12 | 0.00 | 477.92 | 0.117573E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 316429.91 | 02-OCT-03:02 | 155137.43 | 04-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.127216E+12 | 0.00 | 420.53 | 0.912341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 293993.87 | 04-NOV-03:02 | 151556.30 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.828684E+11 | 0.00 | 405.40 | 0.622761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 260281.27 | 26-DEC-04:02 | 136781.93 | 09-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174486E+13 | 0.00 | 5532.89 | 0.126238E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.728920E+11 | 0.00 | 371.07 | 0.570088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 253662.09 | 130824.59 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.202837E+12 | 0.00 | 529.47 | 0.142629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 316429.91 | 164686.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.791063E+11 | 0.00 | 439.70 | 0.720882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 174138.48 | 29-JAN-17:22 | 96142.27 | 01-JAN-12:52 | 0.00 | 0.00 | 0.00 |
February | 0.759060E+11 | 0.00 | 398.13 | 0.684024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159604.93 | 11-FEB-05:02 | 93641.93 | 27-FEB-04:02 | 0.00 | 0.00 | 0.00 |
March | 0.877924E+11 | 0.00 | 450.96 | 0.776327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173301.76 | 06-MAR-04:02 | 92459.76 | 13-MAR-03:02 | 0.00 | 0.00 | 0.00 |
April | 0.893993E+11 | 0.00 | 421.45 | 0.773070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170128.51 | 16-APR-17:00 | 99295.73 | 16-APR-17:00 | 0.00 | 0.00 | 0.00 |
May | 0.113328E+12 | 0.00 | 455.51 | 0.883840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 202148.63 | 29-MAY-01:22 | 96082.44 | 08-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.126883E+12 | 0.00 | 448.51 | 0.903345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191141.57 | 11-JUN-23:38 | 94521.94 | 27-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.131710E+12 | 0.00 | 448.83 | 0.930455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 195793.13 | 31-JUL-03:02 | 99968.81 | 04-JUL-12:40 | 0.00 | 0.00 | 0.00 |
August | 0.144438E+12 | 0.00 | 482.15 | 0.101996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 196296.44 | 28-AUG-03:02 | 96873.28 | 22-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.127147E+12 | 0.00 | 454.76 | 0.910038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192677.90 | 10-SEP-20:00 | 94946.75 | 30-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.122079E+12 | 0.00 | 469.14 | 0.925222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 203619.56 | 02-OCT-03:02 | 97819.14 | 15-OCT-15:42 | 0.00 | 0.00 | 0.00 |
November | 0.105570E+12 | 0.00 | 443.98 | 0.841022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 181995.63 | 24-NOV-01:08 | 96825.83 | 21-NOV-04:02 | 0.00 | 0.00 | 0.00 |
December | 0.838129E+11 | 0.00 | 447.81 | 0.745635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192687.77 | 25-DEC-23:53 | 95898.06 | 03-DEC-15:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128717E+13 | 0.00 | 5360.94 | 0.101138E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.759060E+11 | 0.00 | 398.13 | 0.684024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159604.93 | 92459.76 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.144438E+12 | 0.00 | 482.15 | 0.101996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 203619.56 | 99968.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.339910E+12 | 0.936421E+11 | 744.00 | 0.330372E+12 | 0.953787E+10 | 0.00 | 0.39 | 02-JAN-15:00 | 0.31 | 23-JAN-04:33 | 140024.08 | 02-JAN-15:00 | 130297.15 | 02-JAN-15:00 | 10228.39 | 06-JAN-17:00 | 48866.10 | 02-JAN-15:00 | 0.00 |
February | 0.530005E+12 | 0.149752E+12 | 672.00 | 0.520161E+12 | 0.984387E+10 | 0.00 | 0.61 | 02-FEB-14:00 | 0.52 | 01-FEB-00:10 | 230648.68 | 02-FEB-15:10 | 220904.71 | 22-FEB-16:00 | 11338.62 | 02-FEB-15:30 | 79240.19 | 11-FEB-14:00 | 0.00 |
March | 0.834208E+12 | 0.238250E+12 | 744.00 | 0.821533E+12 | 0.126746E+11 | 0.00 | 0.97 | 31-MAR-23:30 | 0.72 | 01-MAR-04:10 | 396355.71 | 31-MAR-24:00 | 393536.94 | 31-MAR-23:53 | 12524.69 | 13-MAR-10:00 | 115907.47 | 31-MAR-23:20 | 0.00 |
April | 0.104508E+13 | 0.316795E+12 | 720.00 | 0.103206E+13 | 0.130127E+11 | 0.00 | 1.00 | 01-APR-13:00 | 0.37 | 30-APR-23:53 | 425095.91 | 25-APR-16:00 | 406834.42 | 25-APR-16:00 | 18261.48 | 25-APR-16:00 | 145195.50 | 17-APR-15:00 | 0.00 |
May | 0.359710E+12 | 0.117737E+12 | 744.00 | 0.338146E+12 | 0.215638E+11 | 0.00 | 0.60 | 31-MAY-23:10 | 0.34 | 07-MAY-05:00 | 228604.94 | 31-MAY-23:10 | 212370.79 | 31-MAY-23:32 | 16865.82 | 31-MAY-23:10 | 73983.65 | 31-MAY-23:20 | 0.00 |
June | 0.591583E+12 | 0.198217E+12 | 720.00 | 0.564924E+12 | 0.266595E+11 | 0.00 | 0.81 | 30-JUN-23:13 | 0.58 | 01-JUN-06:00 | 316478.67 | 30-JUN-23:03 | 303901.71 | 30-JUN-23:53 | 16196.91 | 23-JUN-14:00 | 103257.31 | 30-JUN-23:13 | 0.00 |
July | 0.857394E+12 | 0.290210E+12 | 744.00 | 0.830238E+12 | 0.271561E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.78 | 04-JUL-04:30 | 401837.92 | 31-JUL-24:00 | 391650.37 | 31-JUL-24:00 | 16547.02 | 25-JUL-15:00 | 135758.37 | 31-JUL-23:30 | 0.00 |
August | 0.109212E+13 | 0.359537E+12 | 744.00 | 0.106652E+13 | 0.256031E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.42 | 31-AUG-23:20 | 425352.01 | 23-AUG-17:00 | 406864.38 | 23-AUG-17:00 | 18487.62 | 23-AUG-17:00 | 150053.83 | 23-AUG-13:00 | 0.00 |
September | 0.355933E+12 | 0.119657E+12 | 720.00 | 0.330726E+12 | 0.252076E+11 | 0.00 | 0.59 | 30-SEP-23:12 | 0.35 | 05-SEP-06:00 | 224635.63 | 30-SEP-23:02 | 212818.81 | 30-SEP-23:55 | 13633.95 | 07-SEP-14:00 | 75517.37 | 30-SEP-23:12 | 0.00 |
October | 0.608095E+12 | 0.196742E+12 | 744.00 | 0.584370E+12 | 0.237250E+11 | 0.00 | 0.78 | 31-OCT-23:10 | 0.57 | 28-OCT-04:00 | 312967.34 | 31-OCT-23:10 | 302838.16 | 31-OCT-23:32 | 15440.23 | 04-OCT-08:30 | 91260.02 | 31-OCT-23:20 | 0.00 |
November | 0.817669E+12 | 0.245915E+12 | 720.00 | 0.799734E+12 | 0.179348E+11 | 0.00 | 0.84 | 03-NOV-14:00 | 0.73 | 11-NOV-07:30 | 326456.61 | 30-NOV-17:00 | 314033.83 | 17-NOV-15:00 | 14014.96 | 29-NOV-11:00 | 114247.62 | 17-NOV-15:00 | 0.00 |
December | 0.107898E+13 | 0.296514E+12 | 744.00 | 0.106702E+13 | 0.119548E+11 | 0.00 | 1.00 | 01-DEC-09:20 | 0.91 | 16-DEC-04:10 | 413385.74 | 08-DEC-17:10 | 404527.91 | 11-DEC-16:30 | 12009.27 | 08-DEC-17:10 | 136512.82 | 10-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.851068E+13 | 0.262297E+13 | 8760.00 | 0.828581E+13 | 0.224874E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.339910E+12 | 0.936421E+11 | 672.00 | 0.330372E+12 | 0.953787E+10 | 0.00 | 0.39 | 0.31 | 140024.08 | 130297.15 | 10228.39 | 48866.10 | 0.00 | ||||||
Maximum of Months | 0.109212E+13 | 0.359537E+12 | 744.00 | 0.106702E+13 | 0.271561E+11 | 0.00 | 1.00 | 0.91 | 425352.01 | 406864.38 | 18487.62 | 150053.83 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.585536E+10 | 0.159593E+10 | 744.00 | 0.547846E+10 | 0.376896E+09 | 0.00 | 0.36 | 02-JAN-15:00 | 0.20 | 26-JAN-07:00 | 2942.85 | 02-JAN-15:00 | 2556.50 | 02-JAN-17:00 | 408.30 | 06-JAN-17:00 | 983.50 | 02-JAN-15:00 | 0.00 |
February | 0.101041E+11 | 0.281115E+10 | 672.00 | 0.969481E+10 | 0.409331E+09 | 0.00 | 0.58 | 19-FEB-17:12 | 0.41 | 04-FEB-08:00 | 4850.59 | 19-FEB-17:37 | 4726.14 | 20-FEB-17:35 | 442.83 | 02-FEB-15:20 | 1548.36 | 02-FEB-14:00 | 0.00 |
March | 0.163997E+11 | 0.460537E+10 | 744.00 | 0.158460E+11 | 0.553722E+09 | 0.00 | 0.88 | 31-MAR-23:23 | 0.62 | 11-MAR-08:00 | 7825.80 | 31-MAR-23:23 | 7681.03 | 31-MAR-23:40 | 527.94 | 13-MAR-10:00 | 2284.22 | 13-MAR-16:00 | 0.00 |
April | 0.210033E+11 | 0.627339E+10 | 720.00 | 0.203848E+11 | 0.618517E+09 | 0.00 | 1.00 | 12-APR-15:50 | 0.31 | 30-APR-23:53 | 8777.99 | 13-APR-16:00 | 8400.62 | 09-APR-18:00 | 551.40 | 25-APR-15:30 | 3089.62 | 17-APR-15:00 | 0.00 |
May | 0.699590E+10 | 0.221405E+10 | 744.00 | 0.612108E+10 | 0.874816E+09 | 0.00 | 0.55 | 31-MAY-23:10 | 0.27 | 06-MAY-06:00 | 4753.61 | 31-MAY-23:10 | 4052.82 | 31-MAY-24:00 | 751.85 | 31-MAY-23:10 | 1469.36 | 31-MAY-23:20 | 0.00 |
June | 0.119804E+11 | 0.388366E+10 | 720.00 | 0.108378E+11 | 0.114258E+10 | 0.00 | 0.74 | 30-JUN-23:03 | 0.51 | 17-JUN-06:40 | 6465.34 | 30-JUN-23:03 | 5900.35 | 30-JUN-23:55 | 634.83 | 23-JUN-14:00 | 2038.66 | 30-JUN-23:13 | 0.00 |
July | 0.175007E+11 | 0.575544E+10 | 744.00 | 0.162940E+11 | 0.120667E+10 | 0.00 | 0.96 | 31-JUL-24:00 | 0.71 | 14-JUL-20:00 | 8434.50 | 31-JUL-23:03 | 7840.23 | 31-JUL-23:57 | 687.92 | 25-JUL-15:00 | 2780.46 | 31-JUL-24:00 | 0.00 |
August | 0.226740E+11 | 0.741926E+10 | 744.00 | 0.214309E+11 | 0.124305E+10 | 0.00 | 1.00 | 01-AUG-10:10 | 0.36 | 31-AUG-23:15 | 8935.38 | 21-AUG-13:00 | 8329.26 | 20-AUG-18:10 | 663.46 | 22-AUG-15:00 | 3191.73 | 23-AUG-13:00 | 0.00 |
September | 0.702049E+10 | 0.227187E+10 | 720.00 | 0.599015E+10 | 0.103034E+10 | 0.00 | 0.54 | 30-SEP-23:04 | 0.29 | 16-SEP-07:00 | 4551.12 | 30-SEP-23:02 | 4038.15 | 30-SEP-24:00 | 554.45 | 22-SEP-08:70 | 1472.73 | 30-SEP-23:12 | 0.00 |
October | 0.121546E+11 | 0.381754E+10 | 744.00 | 0.111437E+11 | 0.101088E+10 | 0.00 | 0.71 | 31-OCT-23:10 | 0.49 | 28-OCT-07:00 | 6286.39 | 31-OCT-23:10 | 5841.60 | 31-OCT-23:42 | 655.71 | 04-OCT-08:20 | 1790.16 | 03-OCT-15:00 | 0.00 |
November | 0.162614E+11 | 0.478603E+10 | 720.00 | 0.154717E+11 | 0.789684E+09 | 0.00 | 0.81 | 07-NOV-17:00 | 0.63 | 27-NOV-07:00 | 6965.77 | 07-NOV-17:00 | 6551.51 | 07-NOV-17:00 | 618.62 | 29-NOV-11:00 | 2302.09 | 17-NOV-15:00 | 0.00 |
December | 0.213384E+11 | 0.578477E+10 | 744.00 | 0.207775E+11 | 0.560933E+09 | 0.00 | 1.00 | 08-DEC-16:40 | 0.79 | 16-DEC-08:00 | 8894.76 | 08-DEC-16:50 | 8421.35 | 06-DEC-17:00 | 504.66 | 08-DEC-16:50 | 2840.33 | 10-DEC-15:02 | 0.00 |
Annual Sum or Average | 0.169288E+12 | 0.512185E+11 | 8760.00 | 0.159471E+12 | 0.981742E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.585536E+10 | 0.159593E+10 | 672.00 | 0.547846E+10 | 0.376896E+09 | 0.00 | 0.36 | 0.20 | 2942.85 | 2556.50 | 408.30 | 983.50 | 0.00 | ||||||
Maximum of Months | 0.226740E+11 | 0.741926E+10 | 744.00 | 0.214309E+11 | 0.124305E+10 | 0.00 | 1.00 | 0.79 | 8935.38 | 8421.35 | 751.85 | 3191.73 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.502432E+11 | 0.138364E+11 | 744.00 | 0.465867E+11 | 0.365649E+10 | 0.00 | 0.36 | 02-JAN-15:00 | 0.15 | 26-JAN-08:00 | 27832.54 | 02-JAN-15:00 | 23963.01 | 02-JAN-17:00 | 4040.97 | 06-JAN-17:00 | 9294.60 | 02-JAN-15:00 | 0.00 |
February | 0.924078E+11 | 0.258496E+11 | 672.00 | 0.883515E+11 | 0.405636E+10 | 0.00 | 0.57 | 19-FEB-17:12 | 0.36 | 05-FEB-06:00 | 45799.64 | 10-FEB-17:00 | 43213.86 | 20-FEB-17:50 | 4395.02 | 02-FEB-15:20 | 14728.37 | 02-FEB-14:00 | 0.00 |
March | 0.154644E+12 | 0.435257E+11 | 744.00 | 0.149116E+12 | 0.552794E+10 | 0.00 | 0.89 | 31-MAR-23:53 | 0.59 | 21-MAR-07:00 | 75264.91 | 31-MAR-23:53 | 73878.48 | 31-MAR-23:57 | 5268.00 | 14-MAR-09:00 | 21736.56 | 13-MAR-16:00 | 0.00 |
April | 0.200259E+12 | 0.598096E+11 | 720.00 | 0.194064E+12 | 0.619510E+10 | 0.00 | 1.00 | 12-APR-16:00 | 0.30 | 30-APR-23:12 | 83624.26 | 13-APR-16:00 | 79008.91 | 09-APR-18:00 | 5482.94 | 25-APR-15:30 | 29387.99 | 17-APR-15:00 | 0.00 |
May | 0.658665E+11 | 0.208498E+11 | 744.00 | 0.572162E+11 | 0.865031E+10 | 0.00 | 0.56 | 31-MAY-23:10 | 0.26 | 27-MAY-13:00 | 46351.31 | 31-MAY-23:10 | 39198.26 | 31-MAY-24:00 | 7742.06 | 31-MAY-23:10 | 14264.29 | 31-MAY-23:20 | 0.00 |
June | 0.114496E+12 | 0.370782E+11 | 720.00 | 0.103115E+12 | 0.113811E+11 | 0.00 | 0.76 | 30-JUN-23:03 | 0.50 | 21-JUN-21:12 | 62995.70 | 30-JUN-23:03 | 57381.50 | 30-JUN-23:55 | 6303.33 | 23-JUN-14:00 | 19789.19 | 30-JUN-23:13 | 0.00 |
July | 0.167424E+12 | 0.550040E+11 | 744.00 | 0.155376E+12 | 0.120477E+11 | 0.00 | 0.97 | 31-JUL-23:05 | 0.70 | 14-JUL-21:20 | 81749.17 | 31-JUL-23:03 | 75491.43 | 31-JUL-23:57 | 6847.71 | 25-JUL-15:00 | 26818.80 | 31-JUL-23:12 | 0.00 |
August | 0.215484E+12 | 0.705291E+11 | 744.00 | 0.203052E+12 | 0.124315E+11 | 0.00 | 1.00 | 01-AUG-09:50 | 0.32 | 31-AUG-23:15 | 84680.38 | 23-AUG-16:30 | 78523.19 | 20-AUG-18:10 | 6683.06 | 22-AUG-15:00 | 30417.26 | 23-AUG-13:00 | 0.00 |
September | 0.659516E+11 | 0.213409E+11 | 720.00 | 0.557672E+11 | 0.101844E+11 | 0.00 | 0.55 | 30-SEP-23:04 | 0.27 | 16-SEP-07:00 | 44205.65 | 30-SEP-23:02 | 38837.45 | 30-SEP-24:00 | 5595.26 | 30-SEP-23:02 | 14254.37 | 30-SEP-23:12 | 0.00 |
October | 0.115495E+12 | 0.362661E+11 | 744.00 | 0.105434E+12 | 0.100611E+11 | 0.00 | 0.71 | 31-OCT-23:10 | 0.47 | 28-OCT-07:00 | 59618.33 | 31-OCT-23:10 | 55213.53 | 31-OCT-24:00 | 6545.79 | 04-OCT-08:20 | 17086.94 | 03-OCT-15:00 | 0.00 |
November | 0.153625E+12 | 0.452899E+11 | 720.00 | 0.145745E+12 | 0.788006E+10 | 0.00 | 0.81 | 07-NOV-17:00 | 0.60 | 27-NOV-07:00 | 66348.88 | 07-NOV-17:00 | 62217.51 | 07-NOV-17:00 | 6175.53 | 29-NOV-11:00 | 21956.82 | 03-NOV-14:00 | 0.00 |
December | 0.200134E+12 | 0.544332E+11 | 744.00 | 0.194518E+12 | 0.561565E+10 | 0.00 | 0.99 | 08-DEC-16:40 | 0.75 | 16-DEC-08:00 | 84499.89 | 08-DEC-16:50 | 79816.68 | 06-DEC-17:00 | 5037.89 | 08-DEC-16:50 | 26631.49 | 10-DEC-15:02 | 0.00 |
Annual Sum or Average | 0.159603E+13 | 0.483813E+12 | 8760.00 | 0.149834E+13 | 0.976877E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.502432E+11 | 0.138364E+11 | 672.00 | 0.465867E+11 | 0.365649E+10 | 0.00 | 0.36 | 0.15 | 27832.54 | 23963.01 | 4040.97 | 9294.60 | 0.00 | ||||||
Maximum of Months | 0.215484E+12 | 0.705291E+11 | 744.00 | 0.203052E+12 | 0.124315E+11 | 0.00 | 1.00 | 0.75 | 84680.38 | 79816.68 | 7742.06 | 30417.26 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.452626E+10 | 0.126428E+10 | 744.00 | 0.416850E+10 | 0.357761E+09 | 0.00 | 0.36 | 02-JAN-15:00 | 0.07 | 25-JAN-07:00 | 2825.70 | 02-JAN-15:00 | 2429.24 | 02-JAN-17:00 | 405.59 | 02-JAN-15:20 | 943.73 | 02-JAN-15:00 | 0.00 |
February | 0.895183E+10 | 0.252120E+10 | 672.00 | 0.854807E+10 | 0.403758E+09 | 0.00 | 0.58 | 19-FEB-17:23 | 0.24 | 05-FEB-07:50 | 4712.48 | 19-FEB-17:25 | 4437.50 | 20-FEB-17:50 | 441.38 | 02-FEB-11:00 | 1493.14 | 02-FEB-14:00 | 0.00 |
March | 0.153235E+11 | 0.433048E+10 | 744.00 | 0.147718E+11 | 0.551656E+09 | 0.00 | 0.87 | 31-MAR-23:53 | 0.52 | 16-MAR-07:00 | 7487.88 | 31-MAR-23:10 | 7347.64 | 31-MAR-23:57 | 526.87 | 14-MAR-09:00 | 2203.43 | 13-MAR-16:00 | 0.00 |
April | 0.200663E+11 | 0.600555E+10 | 720.00 | 0.194477E+11 | 0.618588E+09 | 0.00 | 1.00 | 12-APR-16:00 | 0.30 | 30-APR-23:53 | 8485.76 | 13-APR-16:00 | 8176.94 | 09-APR-17:50 | 548.05 | 25-APR-15:30 | 2977.43 | 17-APR-15:00 | 0.00 |
May | 0.669809E+10 | 0.212239E+10 | 744.00 | 0.583057E+10 | 0.867517E+09 | 0.00 | 0.56 | 31-MAY-23:10 | 0.25 | 01-MAY-06:00 | 4652.10 | 31-MAY-23:10 | 3940.56 | 31-MAY-24:00 | 770.26 | 31-MAY-23:10 | 1433.85 | 31-MAY-23:20 | 0.00 |
June | 0.115703E+11 | 0.375013E+10 | 720.00 | 0.104314E+11 | 0.113884E+10 | 0.00 | 0.75 | 30-JUN-23:03 | 0.49 | 13-JUN-07:00 | 6319.84 | 30-JUN-23:03 | 5721.32 | 30-JUN-23:20 | 631.56 | 23-JUN-14:00 | 1985.50 | 30-JUN-23:13 | 0.00 |
July | 0.169014E+11 | 0.555831E+10 | 744.00 | 0.156966E+11 | 0.120475E+10 | 0.00 | 0.96 | 31-JUL-23:12 | 0.69 | 14-JUL-21:25 | 8171.62 | 31-JUL-23:03 | 7568.71 | 31-JUL-23:42 | 685.57 | 25-JUL-15:00 | 2690.46 | 31-JUL-23:12 | 0.00 |
August | 0.216588E+11 | 0.710099E+10 | 744.00 | 0.204164E+11 | 0.124246E+10 | 0.00 | 1.00 | 01-AUG-11:50 | 0.32 | 31-AUG-23:15 | 8609.11 | 23-AUG-16:30 | 8056.75 | 06-AUG-16:22 | 664.62 | 22-AUG-15:00 | 3085.14 | 23-AUG-13:00 | 0.00 |
September | 0.671007E+10 | 0.217395E+10 | 720.00 | 0.568869E+10 | 0.102137E+10 | 0.00 | 0.55 | 30-SEP-23:04 | 0.26 | 26-SEP-07:00 | 4465.72 | 30-SEP-23:02 | 3941.21 | 30-SEP-24:00 | 551.70 | 30-SEP-23:02 | 1438.03 | 30-SEP-23:12 | 0.00 |
October | 0.115912E+11 | 0.364548E+10 | 744.00 | 0.105857E+11 | 0.100551E+10 | 0.00 | 0.69 | 31-OCT-23:10 | 0.44 | 28-OCT-07:00 | 5895.51 | 31-OCT-23:10 | 5452.52 | 31-OCT-24:00 | 655.16 | 04-OCT-08:20 | 1741.40 | 03-OCT-15:00 | 0.00 |
November | 0.152247E+11 | 0.450661E+10 | 720.00 | 0.144381E+11 | 0.786563E+09 | 0.00 | 0.81 | 07-NOV-17:00 | 0.54 | 27-NOV-08:00 | 6710.21 | 07-NOV-17:00 | 6297.31 | 07-NOV-17:00 | 617.97 | 29-NOV-11:00 | 2225.04 | 03-NOV-14:00 | 0.00 |
December | 0.196770E+11 | 0.538229E+10 | 744.00 | 0.191170E+11 | 0.559979E+09 | 0.00 | 0.99 | 08-DEC-16:40 | 0.68 | 16-DEC-08:00 | 8531.57 | 08-DEC-16:50 | 8053.01 | 06-DEC-16:50 | 503.55 | 08-DEC-16:50 | 2699.03 | 10-DEC-15:02 | 0.00 |
Annual Sum or Average | 0.158899E+12 | 0.483617E+11 | 8760.00 | 0.149141E+12 | 0.975875E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.452626E+10 | 0.126428E+10 | 672.00 | 0.416850E+10 | 0.357761E+09 | 0.00 | 0.36 | 0.07 | 2825.70 | 2429.24 | 405.59 | 943.73 | 0.00 | ||||||
Maximum of Months | 0.216588E+11 | 0.710099E+10 | 744.00 | 0.204164E+11 | 0.124246E+10 | 0.00 | 1.00 | 0.69 | 8609.11 | 8176.94 | 770.26 | 3085.14 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.18 | 0.00 | 88.18 | 87.39 | 209.09 | 0.00 | 0.00 | 0.00 |
February | 104.38 | 0.00 | 104.38 | 132.75 | 173.91 | 0.00 | 0.00 | 0.00 |
March | 124.48 | 0.00 | 124.48 | 161.33 | 141.05 | 0.00 | 0.00 | 0.00 |
April | 139.48 | 0.63 | 138.85 | 225.28 | 86.14 | 0.00 | 0.00 | 0.00 |
May | 159.28 | 7.12 | 152.16 | 311.68 | 44.58 | 0.00 | 0.00 | 0.00 |
June | 170.15 | 12.25 | 157.89 | 358.40 | 18.71 | 0.00 | 0.00 | 0.00 |
July | 172.18 | 8.44 | 163.74 | 377.62 | 26.75 | 0.00 | 0.00 | 0.00 |
August | 152.38 | 1.40 | 150.98 | 316.67 | 18.06 | 0.00 | 0.00 | 0.00 |
September | 135.18 | 0.01 | 135.17 | 293.88 | 32.35 | 0.00 | 0.00 | 0.00 |
October | 113.25 | 0.00 | 113.25 | 217.02 | 51.83 | 0.00 | 0.00 | 0.00 |
November | 98.47 | 0.00 | 98.47 | 151.80 | 105.91 | 0.00 | 0.00 | 0.00 |
December | 87.22 | 0.00 | 87.22 | 97.75 | 179.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.84 | 2.50 | 126.34 | 228.08 | 90.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.22 | 0.00 | 87.22 | 87.39 | 18.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.18 | 12.25 | 163.74 | 377.62 | 209.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.18 | 0.00 | 88.18 | 87.39 | 209.09 | 0.00 | 0.00 | 0.00 |
February | 104.37 | 0.00 | 104.37 | 132.75 | 173.91 | 0.00 | 0.00 | 0.00 |
March | 124.47 | 0.00 | 124.47 | 161.33 | 141.05 | 0.00 | 0.00 | 0.00 |
April | 139.48 | 0.63 | 138.85 | 225.27 | 86.14 | 0.00 | 0.00 | 0.00 |
May | 159.28 | 7.12 | 152.15 | 311.68 | 44.58 | 0.00 | 0.00 | 0.00 |
June | 170.14 | 12.25 | 157.89 | 358.40 | 18.71 | 0.00 | 0.00 | 0.00 |
July | 172.18 | 8.44 | 163.74 | 377.61 | 26.75 | 0.00 | 0.00 | 0.00 |
August | 152.38 | 1.40 | 150.98 | 316.67 | 18.06 | 0.00 | 0.00 | 0.00 |
September | 135.18 | 0.01 | 135.17 | 293.88 | 32.35 | 0.00 | 0.00 | 0.00 |
October | 113.25 | 0.00 | 113.25 | 217.02 | 51.83 | 0.00 | 0.00 | 0.00 |
November | 98.47 | 0.00 | 98.47 | 151.79 | 105.91 | 0.00 | 0.00 | 0.00 |
December | 87.22 | 0.00 | 87.22 | 97.75 | 179.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.84 | 2.50 | 126.34 | 228.08 | 90.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.22 | 0.00 | 87.22 | 87.39 | 18.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.18 | 12.25 | 163.74 | 377.61 | 209.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.18 | 0.00 | 88.18 | 87.39 | 209.09 | 0.00 | 0.00 | 0.00 |
February | 104.38 | 0.00 | 104.38 | 132.75 | 173.91 | 0.00 | 0.00 | 0.00 |
March | 124.47 | 0.00 | 124.47 | 161.33 | 141.05 | 0.00 | 0.00 | 0.00 |
April | 139.48 | 0.63 | 138.85 | 225.27 | 86.14 | 0.00 | 0.00 | 0.00 |
May | 159.28 | 7.12 | 152.15 | 311.68 | 44.58 | 0.00 | 0.00 | 0.00 |
June | 170.14 | 12.25 | 157.89 | 358.40 | 18.71 | 0.00 | 0.00 | 0.00 |
July | 172.18 | 8.44 | 163.74 | 377.61 | 26.75 | 0.00 | 0.00 | 0.00 |
August | 152.38 | 1.40 | 150.98 | 316.67 | 18.06 | 0.00 | 0.00 | 0.00 |
September | 135.18 | 0.01 | 135.17 | 293.88 | 32.35 | 0.00 | 0.00 | 0.00 |
October | 113.25 | 0.00 | 113.25 | 217.02 | 51.83 | 0.00 | 0.00 | 0.00 |
November | 98.47 | 0.00 | 98.47 | 151.80 | 105.91 | 0.00 | 0.00 | 0.00 |
December | 87.22 | 0.00 | 87.22 | 97.75 | 179.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.84 | 2.50 | 126.34 | 228.08 | 90.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.22 | 0.00 | 87.22 | 87.39 | 18.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.18 | 12.25 | 163.74 | 377.61 | 209.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.18 | 0.00 | 88.18 | 87.39 | 209.09 | 0.00 | 0.00 | 0.00 |
February | 104.37 | 0.00 | 104.37 | 132.75 | 173.91 | 0.00 | 0.00 | 0.00 |
March | 124.47 | 0.00 | 124.47 | 161.33 | 141.05 | 0.00 | 0.00 | 0.00 |
April | 139.48 | 0.63 | 138.85 | 225.27 | 86.14 | 0.00 | 0.00 | 0.00 |
May | 159.28 | 7.12 | 152.15 | 311.68 | 44.58 | 0.00 | 0.00 | 0.00 |
June | 170.14 | 12.25 | 157.89 | 358.40 | 18.71 | 0.00 | 0.00 | 0.00 |
July | 172.18 | 8.44 | 163.74 | 377.61 | 26.75 | 0.00 | 0.00 | 0.00 |
August | 152.38 | 1.40 | 150.98 | 316.67 | 18.06 | 0.00 | 0.00 | 0.00 |
September | 135.18 | 0.01 | 135.17 | 293.88 | 32.35 | 0.00 | 0.00 | 0.00 |
October | 113.25 | 0.00 | 113.25 | 217.02 | 51.83 | 0.00 | 0.00 | 0.00 |
November | 98.47 | 0.00 | 98.47 | 151.79 | 105.91 | 0.00 | 0.00 | 0.00 |
December | 87.22 | 0.00 | 87.22 | 97.75 | 179.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.84 | 2.50 | 126.34 | 228.08 | 90.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.22 | 0.00 | 87.22 | 87.39 | 18.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.18 | 12.25 | 163.74 | 377.61 | 209.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.18 | 0.00 | 88.18 | 87.39 | 209.08 | 0.00 | 0.00 | 0.00 |
February | 104.37 | 0.00 | 104.37 | 132.74 | 173.90 | 0.00 | 0.00 | 0.00 |
March | 124.47 | 0.00 | 124.47 | 161.32 | 141.04 | 0.00 | 0.00 | 0.00 |
April | 139.47 | 0.63 | 138.85 | 225.26 | 86.14 | 0.00 | 0.00 | 0.00 |
May | 159.27 | 7.12 | 152.15 | 311.66 | 44.57 | 0.00 | 0.00 | 0.00 |
June | 170.14 | 12.25 | 157.89 | 358.39 | 18.71 | 0.00 | 0.00 | 0.00 |
July | 172.17 | 8.44 | 163.74 | 377.60 | 26.75 | 0.00 | 0.00 | 0.00 |
August | 152.37 | 1.40 | 150.97 | 316.66 | 18.06 | 0.00 | 0.00 | 0.00 |
September | 135.18 | 0.01 | 135.16 | 293.87 | 32.34 | 0.00 | 0.00 | 0.00 |
October | 113.24 | 0.00 | 113.24 | 217.01 | 51.83 | 0.00 | 0.00 | 0.00 |
November | 98.47 | 0.00 | 98.47 | 151.79 | 105.90 | 0.00 | 0.00 | 0.00 |
December | 87.22 | 0.00 | 87.22 | 97.74 | 179.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.83 | 2.50 | 126.33 | 228.07 | 90.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.22 | 0.00 | 87.22 | 87.39 | 18.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.17 | 12.25 | 163.74 | 377.60 | 209.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.92 | 113.02 | 122.90 | 325.97 | 211.79 | 0.00 | 0.00 | 0.00 |
February | 272.41 | 126.10 | 146.31 | 408.62 | 174.53 | 0.00 | 0.00 | 0.00 |
March | 332.59 | 157.23 | 175.35 | 504.30 | 136.07 | 0.00 | 0.00 | 0.00 |
April | 360.94 | 161.05 | 199.89 | 610.68 | 85.61 | 0.00 | 0.00 | 0.00 |
May | 341.47 | 135.98 | 205.49 | 628.88 | 44.59 | 0.00 | 0.00 | 0.00 |
June | 337.03 | 129.45 | 207.58 | 654.43 | 16.58 | 0.00 | 0.00 | 0.00 |
July | 346.30 | 124.88 | 221.42 | 692.55 | 23.64 | 0.00 | 0.00 | 0.00 |
August | 316.66 | 105.89 | 210.78 | 619.40 | 11.90 | 0.00 | 0.00 | 0.00 |
September | 305.28 | 110.36 | 194.92 | 602.01 | 33.63 | 0.00 | 0.00 | 0.00 |
October | 281.00 | 121.02 | 159.99 | 515.67 | 50.43 | 0.00 | 0.00 | 0.00 |
November | 228.07 | 90.94 | 137.13 | 375.98 | 101.29 | 0.00 | 0.00 | 0.00 |
December | 184.23 | 65.04 | 119.19 | 262.45 | 174.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 295.21 | 120.00 | 175.21 | 517.15 | 88.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 184.23 | 65.04 | 119.19 | 262.45 | 11.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.94 | 161.05 | 221.42 | 692.55 | 211.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.92 | 113.02 | 122.90 | 325.97 | 211.79 | 0.00 | 0.00 | 0.00 |
February | 272.41 | 126.10 | 146.31 | 408.62 | 174.53 | 0.00 | 0.00 | 0.00 |
March | 332.59 | 157.23 | 175.35 | 504.30 | 136.07 | 0.00 | 0.00 | 0.00 |
April | 360.94 | 161.05 | 199.89 | 610.68 | 85.61 | 0.00 | 0.00 | 0.00 |
May | 341.47 | 135.98 | 205.49 | 628.88 | 44.59 | 0.00 | 0.00 | 0.00 |
June | 337.03 | 129.45 | 207.58 | 654.43 | 16.58 | 0.00 | 0.00 | 0.00 |
July | 346.30 | 124.88 | 221.42 | 692.55 | 23.64 | 0.00 | 0.00 | 0.00 |
August | 316.66 | 105.89 | 210.78 | 619.40 | 11.90 | 0.00 | 0.00 | 0.00 |
September | 305.28 | 110.36 | 194.92 | 602.01 | 33.63 | 0.00 | 0.00 | 0.00 |
October | 281.00 | 121.02 | 159.99 | 515.67 | 50.43 | 0.00 | 0.00 | 0.00 |
November | 228.07 | 90.94 | 137.13 | 375.98 | 101.29 | 0.00 | 0.00 | 0.00 |
December | 184.23 | 65.04 | 119.19 | 262.45 | 174.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 295.21 | 120.00 | 175.21 | 517.15 | 88.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 184.23 | 65.04 | 119.19 | 262.45 | 11.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.94 | 161.05 | 221.42 | 692.55 | 211.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.91 | 113.02 | 122.90 | 325.96 | 211.79 | 0.00 | 0.00 | 0.00 |
February | 272.40 | 126.10 | 146.31 | 408.61 | 174.53 | 0.00 | 0.00 | 0.00 |
March | 332.58 | 157.23 | 175.35 | 504.29 | 136.07 | 0.00 | 0.00 | 0.00 |
April | 360.94 | 161.05 | 199.89 | 610.67 | 85.61 | 0.00 | 0.00 | 0.00 |
May | 341.46 | 135.98 | 205.48 | 628.87 | 44.58 | 0.00 | 0.00 | 0.00 |
June | 337.03 | 129.45 | 207.58 | 654.41 | 16.58 | 0.00 | 0.00 | 0.00 |
July | 346.30 | 124.88 | 221.42 | 692.54 | 23.64 | 0.00 | 0.00 | 0.00 |
August | 316.66 | 105.88 | 210.77 | 619.38 | 11.90 | 0.00 | 0.00 | 0.00 |
September | 305.28 | 110.36 | 194.92 | 602.00 | 33.63 | 0.00 | 0.00 | 0.00 |
October | 281.00 | 121.01 | 159.98 | 515.66 | 50.43 | 0.00 | 0.00 | 0.00 |
November | 228.07 | 90.94 | 137.13 | 375.97 | 101.29 | 0.00 | 0.00 | 0.00 |
December | 184.23 | 65.04 | 119.19 | 262.45 | 174.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 295.20 | 120.00 | 175.20 | 517.14 | 88.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 184.23 | 65.04 | 119.19 | 262.45 | 11.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.94 | 161.05 | 221.42 | 692.54 | 211.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.44 | 269.25 | 145.19 | 634.17 | 200.71 | 0.00 | 0.00 | 0.00 |
February | 374.92 | 216.94 | 157.98 | 605.06 | 170.40 | 0.00 | 0.00 | 0.00 |
March | 287.85 | 121.70 | 166.15 | 471.56 | 139.10 | 0.00 | 0.00 | 0.00 |
April | 195.74 | 34.32 | 161.41 | 351.46 | 90.55 | 0.00 | 0.00 | 0.00 |
May | 156.85 | 3.39 | 153.46 | 307.93 | 44.17 | 0.00 | 0.00 | 0.00 |
June | 149.54 | 0.28 | 149.26 | 315.73 | 19.08 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 1.48 | 158.64 | 352.51 | 26.95 | 0.00 | 0.00 | 0.00 |
August | 181.73 | 15.34 | 166.40 | 380.93 | 18.85 | 0.00 | 0.00 | 0.00 |
September | 232.64 | 57.01 | 175.63 | 487.17 | 35.10 | 0.00 | 0.00 | 0.00 |
October | 319.93 | 150.10 | 169.83 | 596.97 | 59.08 | 0.00 | 0.00 | 0.00 |
November | 364.00 | 203.15 | 160.85 | 611.00 | 107.57 | 0.00 | 0.00 | 0.00 |
December | 399.40 | 251.92 | 147.48 | 624.23 | 176.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 269.28 | 109.93 | 159.34 | 477.59 | 90.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 149.54 | 0.28 | 145.19 | 307.93 | 18.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 414.44 | 269.25 | 175.63 | 634.17 | 200.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.43 | 269.25 | 145.19 | 634.17 | 200.71 | 0.00 | 0.00 | 0.00 |
February | 374.92 | 216.93 | 157.98 | 605.06 | 170.40 | 0.00 | 0.00 | 0.00 |
March | 287.85 | 121.70 | 166.15 | 471.56 | 139.10 | 0.00 | 0.00 | 0.00 |
April | 195.73 | 34.32 | 161.41 | 351.45 | 90.54 | 0.00 | 0.00 | 0.00 |
May | 156.85 | 3.39 | 153.46 | 307.93 | 44.17 | 0.00 | 0.00 | 0.00 |
June | 149.54 | 0.28 | 149.26 | 315.73 | 19.08 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 1.48 | 158.64 | 352.51 | 26.95 | 0.00 | 0.00 | 0.00 |
August | 181.73 | 15.34 | 166.40 | 380.92 | 18.85 | 0.00 | 0.00 | 0.00 |
September | 232.64 | 57.01 | 175.63 | 487.16 | 35.10 | 0.00 | 0.00 | 0.00 |
October | 319.92 | 150.10 | 169.83 | 596.97 | 59.08 | 0.00 | 0.00 | 0.00 |
November | 364.00 | 203.15 | 160.85 | 611.00 | 107.57 | 0.00 | 0.00 | 0.00 |
December | 399.40 | 251.92 | 147.48 | 624.22 | 176.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 269.27 | 109.93 | 159.34 | 477.59 | 90.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 149.54 | 0.28 | 145.19 | 307.93 | 18.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 414.43 | 269.25 | 175.63 | 634.17 | 200.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.44 | 269.25 | 145.19 | 634.17 | 200.71 | 0.00 | 0.00 | 0.00 |
February | 374.92 | 216.94 | 157.98 | 605.06 | 170.40 | 0.00 | 0.00 | 0.00 |
March | 287.85 | 121.70 | 166.15 | 471.56 | 139.10 | 0.00 | 0.00 | 0.00 |
April | 195.74 | 34.32 | 161.41 | 351.46 | 90.55 | 0.00 | 0.00 | 0.00 |
May | 156.85 | 3.39 | 153.46 | 307.93 | 44.17 | 0.00 | 0.00 | 0.00 |
June | 149.54 | 0.28 | 149.26 | 315.73 | 19.08 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 1.48 | 158.64 | 352.51 | 26.95 | 0.00 | 0.00 | 0.00 |
August | 181.73 | 15.34 | 166.40 | 380.93 | 18.85 | 0.00 | 0.00 | 0.00 |
September | 232.64 | 57.01 | 175.63 | 487.17 | 35.10 | 0.00 | 0.00 | 0.00 |
October | 319.93 | 150.10 | 169.83 | 596.97 | 59.08 | 0.00 | 0.00 | 0.00 |
November | 364.00 | 203.15 | 160.85 | 611.00 | 107.57 | 0.00 | 0.00 | 0.00 |
December | 399.40 | 251.92 | 147.48 | 624.23 | 176.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 269.28 | 109.93 | 159.34 | 477.59 | 90.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 149.54 | 0.28 | 145.19 | 307.93 | 18.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 414.44 | 269.25 | 175.63 | 634.17 | 200.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.43 | 269.25 | 145.19 | 634.17 | 200.71 | 0.00 | 0.00 | 0.00 |
February | 374.92 | 216.93 | 157.98 | 605.06 | 170.40 | 0.00 | 0.00 | 0.00 |
March | 287.85 | 121.70 | 166.15 | 471.56 | 139.10 | 0.00 | 0.00 | 0.00 |
April | 195.73 | 34.32 | 161.41 | 351.45 | 90.54 | 0.00 | 0.00 | 0.00 |
May | 156.85 | 3.39 | 153.46 | 307.93 | 44.17 | 0.00 | 0.00 | 0.00 |
June | 149.54 | 0.28 | 149.26 | 315.73 | 19.08 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 1.48 | 158.64 | 352.51 | 26.95 | 0.00 | 0.00 | 0.00 |
August | 181.73 | 15.34 | 166.40 | 380.92 | 18.85 | 0.00 | 0.00 | 0.00 |
September | 232.64 | 57.01 | 175.63 | 487.16 | 35.10 | 0.00 | 0.00 | 0.00 |
October | 319.92 | 150.10 | 169.83 | 596.97 | 59.08 | 0.00 | 0.00 | 0.00 |
November | 364.00 | 203.15 | 160.85 | 611.00 | 107.57 | 0.00 | 0.00 | 0.00 |
December | 399.40 | 251.92 | 147.48 | 624.22 | 176.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 269.27 | 109.93 | 159.34 | 477.59 | 90.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 149.54 | 0.28 | 145.19 | 307.93 | 18.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 414.43 | 269.25 | 175.63 | 634.17 | 200.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.42 | 269.24 | 145.18 | 634.14 | 200.70 | 0.00 | 0.00 | 0.00 |
February | 374.90 | 216.93 | 157.98 | 605.04 | 170.39 | 0.00 | 0.00 | 0.00 |
March | 287.84 | 121.70 | 166.14 | 471.54 | 139.09 | 0.00 | 0.00 | 0.00 |
April | 195.73 | 34.32 | 161.40 | 351.44 | 90.54 | 0.00 | 0.00 | 0.00 |
May | 156.84 | 3.39 | 153.45 | 307.92 | 44.17 | 0.00 | 0.00 | 0.00 |
June | 149.54 | 0.28 | 149.26 | 315.71 | 19.08 | 0.00 | 0.00 | 0.00 |
July | 160.11 | 1.48 | 158.63 | 352.50 | 26.95 | 0.00 | 0.00 | 0.00 |
August | 181.72 | 15.33 | 166.39 | 380.91 | 18.85 | 0.00 | 0.00 | 0.00 |
September | 232.63 | 57.01 | 175.62 | 487.15 | 35.10 | 0.00 | 0.00 | 0.00 |
October | 319.91 | 150.09 | 169.82 | 596.95 | 59.07 | 0.00 | 0.00 | 0.00 |
November | 363.99 | 203.15 | 160.84 | 610.97 | 107.57 | 0.00 | 0.00 | 0.00 |
December | 399.38 | 251.91 | 147.48 | 624.20 | 176.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 269.26 | 109.93 | 159.33 | 477.57 | 90.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 149.54 | 0.28 | 145.18 | 307.92 | 18.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 414.42 | 269.24 | 175.62 | 634.14 | 200.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 211.93 | 91.37 | 120.57 | 289.56 | 247.91 | 0.00 | 0.00 | 0.00 |
February | 265.02 | 119.93 | 145.08 | 398.65 | 221.33 | 0.00 | 0.00 | 0.00 |
March | 330.03 | 150.71 | 179.32 | 499.11 | 188.41 | 0.00 | 0.00 | 0.00 |
April | 363.26 | 168.20 | 195.06 | 597.52 | 130.48 | 0.00 | 0.00 | 0.00 |
May | 331.16 | 127.48 | 203.68 | 606.18 | 65.08 | 0.00 | 0.00 | 0.00 |
June | 280.60 | 78.71 | 201.89 | 538.46 | 33.22 | 0.00 | 0.00 | 0.00 |
July | 313.59 | 97.02 | 216.58 | 614.96 | 47.16 | 0.00 | 0.00 | 0.00 |
August | 312.88 | 101.97 | 210.91 | 580.76 | 45.55 | 0.00 | 0.00 | 0.00 |
September | 266.90 | 78.70 | 188.20 | 523.01 | 45.90 | 0.00 | 0.00 | 0.00 |
October | 265.52 | 103.51 | 162.01 | 478.27 | 79.43 | 0.00 | 0.00 | 0.00 |
November | 219.02 | 80.34 | 138.68 | 352.57 | 147.26 | 0.00 | 0.00 | 0.00 |
December | 219.42 | 98.10 | 121.32 | 309.34 | 237.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 281.74 | 107.98 | 173.76 | 482.83 | 123.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.93 | 78.70 | 120.57 | 289.56 | 33.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.26 | 168.20 | 216.58 | 614.96 | 247.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 211.93 | 91.37 | 120.57 | 289.56 | 247.91 | 0.00 | 0.00 | 0.00 |
February | 265.02 | 119.93 | 145.08 | 398.65 | 221.33 | 0.00 | 0.00 | 0.00 |
March | 330.03 | 150.71 | 179.32 | 499.11 | 188.41 | 0.00 | 0.00 | 0.00 |
April | 363.26 | 168.20 | 195.06 | 597.52 | 130.48 | 0.00 | 0.00 | 0.00 |
May | 331.16 | 127.48 | 203.68 | 606.18 | 65.08 | 0.00 | 0.00 | 0.00 |
June | 280.60 | 78.71 | 201.89 | 538.46 | 33.22 | 0.00 | 0.00 | 0.00 |
July | 313.59 | 97.02 | 216.58 | 614.96 | 47.16 | 0.00 | 0.00 | 0.00 |
August | 312.88 | 101.97 | 210.91 | 580.76 | 45.55 | 0.00 | 0.00 | 0.00 |
September | 266.90 | 78.70 | 188.20 | 523.01 | 45.90 | 0.00 | 0.00 | 0.00 |
October | 265.52 | 103.51 | 162.01 | 478.27 | 79.43 | 0.00 | 0.00 | 0.00 |
November | 219.02 | 80.34 | 138.68 | 352.57 | 147.26 | 0.00 | 0.00 | 0.00 |
December | 219.42 | 98.10 | 121.32 | 309.34 | 237.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 281.74 | 107.98 | 173.76 | 482.83 | 123.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.93 | 78.70 | 120.57 | 289.56 | 33.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.26 | 168.20 | 216.58 | 614.96 | 247.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 211.93 | 91.37 | 120.56 | 289.56 | 247.90 | 0.00 | 0.00 | 0.00 |
February | 265.01 | 119.93 | 145.08 | 398.64 | 221.33 | 0.00 | 0.00 | 0.00 |
March | 330.02 | 150.70 | 179.32 | 499.10 | 188.41 | 0.00 | 0.00 | 0.00 |
April | 363.26 | 168.20 | 195.06 | 597.51 | 130.47 | 0.00 | 0.00 | 0.00 |
May | 331.16 | 127.48 | 203.68 | 606.17 | 65.08 | 0.00 | 0.00 | 0.00 |
June | 280.59 | 78.71 | 201.88 | 538.45 | 33.22 | 0.00 | 0.00 | 0.00 |
July | 313.58 | 97.01 | 216.57 | 614.95 | 47.16 | 0.00 | 0.00 | 0.00 |
August | 312.87 | 101.96 | 210.91 | 580.75 | 45.55 | 0.00 | 0.00 | 0.00 |
September | 266.90 | 78.70 | 188.20 | 523.00 | 45.90 | 0.00 | 0.00 | 0.00 |
October | 265.51 | 103.50 | 162.01 | 478.26 | 79.43 | 0.00 | 0.00 | 0.00 |
November | 219.02 | 80.34 | 138.68 | 352.57 | 147.26 | 0.00 | 0.00 | 0.00 |
December | 219.41 | 98.10 | 121.31 | 309.34 | 237.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 281.73 | 107.97 | 173.76 | 482.82 | 123.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.93 | 78.70 | 120.56 | 289.56 | 33.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.26 | 168.20 | 216.57 | 614.95 | 247.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 440.90 | 0.00 | 440.90 | 463.63 | 954.46 | 0.00 | 0.00 | 0.00 |
February | 521.88 | 0.00 | 521.88 | 691.74 | 785.99 | 0.00 | 0.00 | 0.00 |
March | 622.38 | 0.00 | 622.38 | 822.81 | 655.88 | 0.00 | 0.00 | 0.00 |
April | 697.41 | 3.13 | 694.27 | 1139.45 | 421.48 | 0.00 | 0.00 | 0.00 |
May | 796.40 | 35.62 | 760.78 | 1558.46 | 222.25 | 0.00 | 0.00 | 0.00 |
June | 850.73 | 61.25 | 789.47 | 1792.18 | 102.44 | 0.00 | 0.00 | 0.00 |
July | 860.91 | 42.19 | 818.72 | 1898.59 | 142.52 | 0.00 | 0.00 | 0.00 |
August | 761.91 | 7.01 | 754.91 | 1605.10 | 95.20 | 0.00 | 0.00 | 0.00 |
September | 675.91 | 0.05 | 675.86 | 1476.14 | 161.27 | 0.00 | 0.00 | 0.00 |
October | 566.25 | 0.00 | 566.25 | 1096.24 | 252.55 | 0.00 | 0.00 | 0.00 |
November | 492.36 | 0.00 | 492.36 | 777.19 | 488.01 | 0.00 | 0.00 | 0.00 |
December | 436.11 | 0.00 | 436.11 | 517.53 | 811.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 644.21 | 12.50 | 631.71 | 1155.48 | 422.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 436.11 | 0.00 | 436.11 | 463.63 | 95.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 860.91 | 61.25 | 818.72 | 1898.59 | 954.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 707.75 | 339.05 | 368.69 | 982.58 | 598.34 | 0.00 | 0.00 | 0.00 |
February | 817.21 | 378.29 | 438.92 | 1224.26 | 495.32 | 0.00 | 0.00 | 0.00 |
March | 997.75 | 471.69 | 526.06 | 1494.39 | 409.16 | 0.00 | 0.00 | 0.00 |
April | 1082.81 | 483.15 | 599.67 | 1806.55 | 283.61 | 0.00 | 0.00 | 0.00 |
May | 1024.39 | 407.93 | 616.45 | 1868.29 | 142.88 | 0.00 | 0.00 | 0.00 |
June | 1011.08 | 388.35 | 622.73 | 1937.58 | 66.73 | 0.00 | 0.00 | 0.00 |
July | 1038.90 | 374.65 | 664.25 | 2057.35 | 95.58 | 0.00 | 0.00 | 0.00 |
August | 949.98 | 317.65 | 632.33 | 1836.14 | 61.08 | 0.00 | 0.00 | 0.00 |
September | 915.85 | 331.08 | 584.76 | 1789.69 | 109.14 | 0.00 | 0.00 | 0.00 |
October | 843.00 | 363.05 | 479.95 | 1533.29 | 167.55 | 0.00 | 0.00 | 0.00 |
November | 684.20 | 272.82 | 411.39 | 1119.90 | 305.78 | 0.00 | 0.00 | 0.00 |
December | 552.69 | 195.13 | 357.56 | 789.70 | 509.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 885.61 | 359.99 | 525.62 | 1537.82 | 269.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 552.69 | 195.13 | 357.56 | 789.70 | 61.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.81 | 483.15 | 664.25 | 2057.35 | 598.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2072.22 | 1346.28 | 725.95 | 3141.12 | 988.51 | 0.00 | 0.00 | 0.00 |
February | 1874.63 | 1084.70 | 789.93 | 3000.19 | 827.61 | 0.00 | 0.00 | 0.00 |
March | 1439.29 | 608.52 | 830.77 | 2338.32 | 680.50 | 0.00 | 0.00 | 0.00 |
April | 978.69 | 171.62 | 807.07 | 1754.34 | 452.13 | 0.00 | 0.00 | 0.00 |
May | 784.26 | 16.97 | 767.30 | 1540.67 | 217.79 | 0.00 | 0.00 | 0.00 |
June | 747.73 | 1.41 | 746.32 | 1585.88 | 101.79 | 0.00 | 0.00 | 0.00 |
July | 800.61 | 7.42 | 793.19 | 1776.34 | 141.28 | 0.00 | 0.00 | 0.00 |
August | 908.67 | 76.68 | 831.99 | 1920.15 | 100.29 | 0.00 | 0.00 | 0.00 |
September | 1163.22 | 285.05 | 878.17 | 2425.71 | 179.39 | 0.00 | 0.00 | 0.00 |
October | 1599.66 | 750.51 | 849.15 | 2963.74 | 304.17 | 0.00 | 0.00 | 0.00 |
November | 1820.06 | 1015.79 | 804.26 | 3031.38 | 532.28 | 0.00 | 0.00 | 0.00 |
December | 1997.04 | 1259.62 | 737.42 | 3097.97 | 869.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1346.40 | 549.68 | 796.71 | 2378.22 | 447.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 747.73 | 1.41 | 725.95 | 1540.67 | 100.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2072.22 | 1346.28 | 878.17 | 3141.12 | 988.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 635.79 | 274.10 | 361.69 | 896.55 | 652.60 | 0.00 | 0.00 | 0.00 |
February | 795.04 | 359.80 | 435.24 | 1231.32 | 561.91 | 0.00 | 0.00 | 0.00 |
March | 990.07 | 452.12 | 537.95 | 1527.83 | 482.63 | 0.00 | 0.00 | 0.00 |
April | 1089.78 | 504.60 | 585.17 | 1830.03 | 337.15 | 0.00 | 0.00 | 0.00 |
May | 993.47 | 382.44 | 611.03 | 1826.36 | 178.69 | 0.00 | 0.00 | 0.00 |
June | 841.78 | 236.13 | 605.65 | 1643.04 | 84.02 | 0.00 | 0.00 | 0.00 |
July | 940.76 | 291.04 | 649.72 | 1883.69 | 116.91 | 0.00 | 0.00 | 0.00 |
August | 938.62 | 305.90 | 632.73 | 1801.07 | 87.91 | 0.00 | 0.00 | 0.00 |
September | 800.69 | 236.10 | 564.60 | 1584.78 | 122.79 | 0.00 | 0.00 | 0.00 |
October | 796.54 | 310.52 | 486.03 | 1457.48 | 202.93 | 0.00 | 0.00 | 0.00 |
November | 657.06 | 241.02 | 416.05 | 1095.14 | 356.44 | 0.00 | 0.00 | 0.00 |
December | 658.24 | 294.29 | 363.95 | 976.88 | 571.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 845.20 | 323.92 | 521.28 | 1480.91 | 311.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 635.79 | 236.10 | 361.69 | 896.55 | 84.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1089.78 | 504.60 | 649.72 | 1883.69 | 652.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 440.90 | 0.00 | 440.90 | 485.53 | 874.00 | 0.00 | 0.00 | 0.00 |
February | 521.88 | 0.00 | 521.88 | 702.38 | 733.49 | 0.00 | 0.00 | 0.00 |
March | 622.38 | 0.00 | 622.38 | 821.42 | 625.33 | 0.00 | 0.00 | 0.00 |
April | 697.41 | 3.13 | 694.27 | 1122.72 | 418.57 | 0.00 | 0.00 | 0.00 |
May | 796.40 | 35.62 | 760.78 | 1533.74 | 230.14 | 0.00 | 0.00 | 0.00 |
June | 850.73 | 61.25 | 789.47 | 1760.59 | 108.14 | 0.00 | 0.00 | 0.00 |
July | 860.91 | 42.19 | 818.72 | 1865.03 | 151.60 | 0.00 | 0.00 | 0.00 |
August | 761.91 | 7.01 | 754.91 | 1579.87 | 100.37 | 0.00 | 0.00 | 0.00 |
September | 675.91 | 0.05 | 675.86 | 1447.17 | 165.02 | 0.00 | 0.00 | 0.00 |
October | 566.25 | 0.00 | 566.25 | 1080.35 | 252.95 | 0.00 | 0.00 | 0.00 |
November | 492.36 | 0.00 | 492.36 | 777.00 | 460.42 | 0.00 | 0.00 | 0.00 |
December | 436.11 | 0.00 | 436.11 | 531.86 | 752.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 644.21 | 12.50 | 631.71 | 1144.45 | 404.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 436.11 | 0.00 | 436.11 | 485.53 | 100.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 860.91 | 61.25 | 818.72 | 1865.03 | 874.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 707.75 | 339.05 | 368.69 | 993.03 | 564.20 | 0.00 | 0.00 | 0.00 |
February | 817.21 | 378.29 | 438.92 | 1226.74 | 473.05 | 0.00 | 0.00 | 0.00 |
March | 997.75 | 471.69 | 526.06 | 1486.37 | 400.15 | 0.00 | 0.00 | 0.00 |
April | 1082.81 | 483.15 | 599.67 | 1789.31 | 286.32 | 0.00 | 0.00 | 0.00 |
May | 1024.39 | 407.93 | 616.45 | 1846.87 | 148.95 | 0.00 | 0.00 | 0.00 |
June | 1011.08 | 388.35 | 622.73 | 1913.26 | 70.57 | 0.00 | 0.00 | 0.00 |
July | 1038.90 | 374.65 | 664.25 | 2031.41 | 101.53 | 0.00 | 0.00 | 0.00 |
August | 949.98 | 317.65 | 632.33 | 1814.91 | 64.58 | 0.00 | 0.00 | 0.00 |
September | 915.85 | 331.08 | 584.76 | 1766.63 | 112.38 | 0.00 | 0.00 | 0.00 |
October | 843.00 | 363.05 | 479.95 | 1518.30 | 170.51 | 0.00 | 0.00 | 0.00 |
November | 684.20 | 272.82 | 411.39 | 1115.76 | 295.32 | 0.00 | 0.00 | 0.00 |
December | 552.69 | 195.13 | 357.56 | 794.32 | 483.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 885.61 | 359.99 | 525.62 | 1525.86 | 263.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 552.69 | 195.13 | 357.56 | 794.32 | 64.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.81 | 483.15 | 664.25 | 2031.41 | 564.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2072.22 | 1346.28 | 725.95 | 3152.41 | 935.52 | 0.00 | 0.00 | 0.00 |
February | 1874.63 | 1084.70 | 789.93 | 3001.14 | 791.93 | 0.00 | 0.00 | 0.00 |
March | 1439.29 | 608.52 | 830.77 | 2327.51 | 660.90 | 0.00 | 0.00 | 0.00 |
April | 978.69 | 171.62 | 807.07 | 1734.39 | 451.04 | 0.00 | 0.00 | 0.00 |
May | 784.26 | 16.97 | 767.30 | 1515.60 | 224.40 | 0.00 | 0.00 | 0.00 |
June | 747.73 | 1.41 | 746.32 | 1555.58 | 106.89 | 0.00 | 0.00 | 0.00 |
July | 800.61 | 7.42 | 793.19 | 1743.44 | 149.45 | 0.00 | 0.00 | 0.00 |
August | 908.67 | 76.68 | 831.99 | 1893.47 | 104.96 | 0.00 | 0.00 | 0.00 |
September | 1163.22 | 285.05 | 878.17 | 2395.10 | 184.09 | 0.00 | 0.00 | 0.00 |
October | 1599.66 | 750.51 | 849.15 | 2943.34 | 308.03 | 0.00 | 0.00 | 0.00 |
November | 1820.06 | 1015.79 | 804.26 | 3024.65 | 516.09 | 0.00 | 0.00 | 0.00 |
December | 1997.04 | 1259.62 | 737.42 | 3099.47 | 830.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1346.40 | 549.68 | 796.71 | 2362.34 | 437.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 747.73 | 1.41 | 725.95 | 1515.60 | 104.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2072.22 | 1346.28 | 878.17 | 3152.41 | 935.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 635.79 | 274.10 | 361.69 | 905.21 | 611.04 | 0.00 | 0.00 | 0.00 |
February | 795.04 | 359.80 | 435.24 | 1233.11 | 535.03 | 0.00 | 0.00 | 0.00 |
March | 990.07 | 452.12 | 537.95 | 1522.01 | 468.14 | 0.00 | 0.00 | 0.00 |
April | 1089.78 | 504.60 | 585.17 | 1816.97 | 336.33 | 0.00 | 0.00 | 0.00 |
May | 993.47 | 382.44 | 611.03 | 1810.15 | 182.26 | 0.00 | 0.00 | 0.00 |
June | 841.78 | 236.13 | 605.65 | 1624.76 | 85.97 | 0.00 | 0.00 | 0.00 |
July | 940.76 | 291.04 | 649.72 | 1863.31 | 119.67 | 0.00 | 0.00 | 0.00 |
August | 938.62 | 305.90 | 632.73 | 1784.85 | 90.35 | 0.00 | 0.00 | 0.00 |
September | 800.69 | 236.10 | 564.60 | 1567.85 | 123.67 | 0.00 | 0.00 | 0.00 |
October | 796.54 | 310.52 | 486.03 | 1446.53 | 202.46 | 0.00 | 0.00 | 0.00 |
November | 657.06 | 241.02 | 416.05 | 1092.99 | 342.26 | 0.00 | 0.00 | 0.00 |
December | 658.24 | 294.29 | 363.95 | 981.04 | 540.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 845.20 | 323.92 | 521.28 | 1472.08 | 302.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 635.79 | 236.10 | 361.69 | 905.21 | 85.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1089.78 | 504.60 | 649.72 | 1863.31 | 611.04 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.236184E+09 | 0.00 | 0.236184E+09 | 0.234066E+09 | 0.560024E+09 |
February | 0.252507E+09 | 0.00 | 0.252507E+09 | 0.321147E+09 | 0.420721E+09 |
March | 0.333397E+09 | 0.00 | 0.333397E+09 | 0.432103E+09 | 0.377788E+09 |
April | 0.361535E+09 | 1624044.80 | 0.359911E+09 | 0.583915E+09 | 0.223284E+09 |
May | 0.426616E+09 | 19083416.75 | 0.407533E+09 | 0.834800E+09 | 0.119394E+09 |
June | 0.441017E+09 | 31754364.89 | 0.409263E+09 | 0.928983E+09 | 48491886.97 |
July | 0.461171E+09 | 22598115.53 | 0.438572E+09 | 0.101141E+10 | 71656464.28 |
August | 0.408143E+09 | 3753765.63 | 0.404389E+09 | 0.848171E+09 | 48365230.11 |
September | 0.350392E+09 | 27719.12 | 0.350365E+09 | 0.761736E+09 | 83841318.99 |
October | 0.303328E+09 | 0.00 | 0.303328E+09 | 0.581273E+09 | 0.138831E+09 |
November | 0.255237E+09 | 0.00 | 0.255237E+09 | 0.393457E+09 | 0.274515E+09 |
December | 0.233615E+09 | 0.00 | 0.233615E+09 | 0.261814E+09 | 0.480806E+09 |
Annual Sum or Average | 0.406314E+10 | 78841426.72 | 0.398430E+10 | 0.719287E+10 | 0.284772E+10 |
Minimum of Months | 0.233615E+09 | 0.00 | 0.233615E+09 | 0.234066E+09 | 48365230.11 |
Maximum of Months | 0.461171E+09 | 31754364.89 | 0.438572E+09 | 0.101141E+10 | 0.560024E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.236180E+09 | 0.00 | 0.236180E+09 | 0.234062E+09 | 0.560021E+09 |
February | 0.252503E+09 | 0.00 | 0.252503E+09 | 0.321142E+09 | 0.420719E+09 |
March | 0.333392E+09 | 0.00 | 0.333392E+09 | 0.432097E+09 | 0.377786E+09 |
April | 0.361531E+09 | 1624009.10 | 0.359907E+09 | 0.583908E+09 | 0.223282E+09 |
May | 0.426610E+09 | 19082997.22 | 0.407527E+09 | 0.834791E+09 | 0.119392E+09 |
June | 0.441010E+09 | 31753666.81 | 0.409257E+09 | 0.928973E+09 | 48490831.13 |
July | 0.461164E+09 | 22597618.74 | 0.438566E+09 | 0.101139E+10 | 71654964.61 |
August | 0.408137E+09 | 3753683.11 | 0.404383E+09 | 0.848163E+09 | 48363950.49 |
September | 0.350387E+09 | 27718.51 | 0.350360E+09 | 0.761729E+09 | 83840035.48 |
October | 0.303324E+09 | 0.00 | 0.303324E+09 | 0.581267E+09 | 0.138828E+09 |
November | 0.255234E+09 | 0.00 | 0.255234E+09 | 0.393452E+09 | 0.274513E+09 |
December | 0.233612E+09 | 0.00 | 0.233612E+09 | 0.261810E+09 | 0.480804E+09 |
Annual Sum or Average | 0.406308E+10 | 78839693.48 | 0.398424E+10 | 0.719279E+10 | 0.284770E+10 |
Minimum of Months | 0.233612E+09 | 0.00 | 0.233612E+09 | 0.234062E+09 | 48363950.49 |
Maximum of Months | 0.461164E+09 | 31753666.81 | 0.438566E+09 | 0.101139E+10 | 0.560021E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.236182E+09 | 0.00 | 0.236182E+09 | 0.234064E+09 | 0.560022E+09 |
February | 0.252505E+09 | 0.00 | 0.252505E+09 | 0.321144E+09 | 0.420719E+09 |
March | 0.333394E+09 | 0.00 | 0.333394E+09 | 0.432099E+09 | 0.377786E+09 |
April | 0.361532E+09 | 1624021.00 | 0.359908E+09 | 0.583911E+09 | 0.223283E+09 |
May | 0.426612E+09 | 19083137.06 | 0.407529E+09 | 0.834794E+09 | 0.119393E+09 |
June | 0.441013E+09 | 31753899.50 | 0.409259E+09 | 0.928976E+09 | 48491183.08 |
July | 0.461166E+09 | 22597784.34 | 0.438568E+09 | 0.101140E+10 | 71655464.49 |
August | 0.408139E+09 | 3753710.61 | 0.404385E+09 | 0.848166E+09 | 48364377.03 |
September | 0.350389E+09 | 27718.71 | 0.350361E+09 | 0.761731E+09 | 83840463.32 |
October | 0.303325E+09 | 0.00 | 0.303325E+09 | 0.581269E+09 | 0.138829E+09 |
November | 0.255235E+09 | 0.00 | 0.255235E+09 | 0.393454E+09 | 0.274514E+09 |
December | 0.233613E+09 | 0.00 | 0.233613E+09 | 0.261811E+09 | 0.480805E+09 |
Annual Sum or Average | 0.406310E+10 | 78840271.22 | 0.398426E+10 | 0.719282E+10 | 0.284770E+10 |
Minimum of Months | 0.233613E+09 | 0.00 | 0.233613E+09 | 0.234064E+09 | 48364377.03 |
Maximum of Months | 0.461166E+09 | 31753899.50 | 0.438568E+09 | 0.101140E+10 | 0.560022E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.236180E+09 | 0.00 | 0.236180E+09 | 0.234062E+09 | 0.560021E+09 |
February | 0.252503E+09 | 0.00 | 0.252503E+09 | 0.321142E+09 | 0.420719E+09 |
March | 0.333392E+09 | 0.00 | 0.333392E+09 | 0.432097E+09 | 0.377786E+09 |
April | 0.361531E+09 | 1624009.10 | 0.359907E+09 | 0.583908E+09 | 0.223282E+09 |
May | 0.426610E+09 | 19082997.22 | 0.407527E+09 | 0.834791E+09 | 0.119392E+09 |
June | 0.441010E+09 | 31753666.81 | 0.409257E+09 | 0.928973E+09 | 48490831.13 |
July | 0.461164E+09 | 22597618.74 | 0.438566E+09 | 0.101139E+10 | 71654964.61 |
August | 0.408137E+09 | 3753683.11 | 0.404383E+09 | 0.848163E+09 | 48363950.49 |
September | 0.350387E+09 | 27718.51 | 0.350360E+09 | 0.761729E+09 | 83840035.48 |
October | 0.303324E+09 | 0.00 | 0.303324E+09 | 0.581267E+09 | 0.138828E+09 |
November | 0.255234E+09 | 0.00 | 0.255234E+09 | 0.393452E+09 | 0.274513E+09 |
December | 0.233612E+09 | 0.00 | 0.233612E+09 | 0.261810E+09 | 0.480804E+09 |
Annual Sum or Average | 0.406308E+10 | 78839693.48 | 0.398424E+10 | 0.719279E+10 | 0.284770E+10 |
Minimum of Months | 0.233612E+09 | 0.00 | 0.233612E+09 | 0.234062E+09 | 48363950.49 |
Maximum of Months | 0.461164E+09 | 31753666.81 | 0.438566E+09 | 0.101139E+10 | 0.560021E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.236171E+09 | 0.00 | 0.236171E+09 | 0.234054E+09 | 0.559999E+09 |
February | 0.252494E+09 | 0.00 | 0.252494E+09 | 0.321130E+09 | 0.420702E+09 |
March | 0.333380E+09 | 0.00 | 0.333380E+09 | 0.432081E+09 | 0.377771E+09 |
April | 0.361517E+09 | 1623949.59 | 0.359893E+09 | 0.583886E+09 | 0.223274E+09 |
May | 0.426594E+09 | 19082298.01 | 0.407512E+09 | 0.834759E+09 | 0.119388E+09 |
June | 0.440994E+09 | 31752503.34 | 0.409241E+09 | 0.928937E+09 | 48489052.71 |
July | 0.461146E+09 | 22596790.75 | 0.438550E+09 | 0.101136E+10 | 71652326.53 |
August | 0.408121E+09 | 3753545.57 | 0.404368E+09 | 0.848130E+09 | 48362214.47 |
September | 0.350374E+09 | 27717.49 | 0.350346E+09 | 0.761700E+09 | 83836870.27 |
October | 0.303312E+09 | 0.00 | 0.303312E+09 | 0.581245E+09 | 0.138823E+09 |
November | 0.255224E+09 | 0.00 | 0.255224E+09 | 0.393437E+09 | 0.274502E+09 |
December | 0.233603E+09 | 0.00 | 0.233603E+09 | 0.261800E+09 | 0.480785E+09 |
Annual Sum or Average | 0.406293E+10 | 78836804.75 | 0.398409E+10 | 0.719251E+10 | 0.284759E+10 |
Minimum of Months | 0.233603E+09 | 0.00 | 0.233603E+09 | 0.234054E+09 | 48362214.47 |
Maximum of Months | 0.461146E+09 | 31752503.34 | 0.438550E+09 | 0.101136E+10 | 0.559999E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.631881E+09 | 0.302710E+09 | 0.329171E+09 | 0.873074E+09 | 0.567271E+09 |
February | 0.659006E+09 | 0.305055E+09 | 0.353951E+09 | 0.988539E+09 | 0.422227E+09 |
March | 0.890803E+09 | 0.421133E+09 | 0.469669E+09 | 0.135072E+10 | 0.364452E+09 |
April | 0.935561E+09 | 0.417443E+09 | 0.518118E+09 | 0.158288E+10 | 0.221893E+09 |
May | 0.914581E+09 | 0.364207E+09 | 0.550373E+09 | 0.168438E+10 | 0.119417E+09 |
June | 0.873586E+09 | 0.335539E+09 | 0.538048E+09 | 0.169627E+10 | 42985929.16 |
July | 0.927539E+09 | 0.334490E+09 | 0.593049E+09 | 0.185494E+10 | 63326781.88 |
August | 0.848154E+09 | 0.283605E+09 | 0.564549E+09 | 0.165899E+10 | 31884337.36 |
September | 0.791299E+09 | 0.286058E+09 | 0.505241E+09 | 0.156041E+10 | 87179999.99 |
October | 0.752637E+09 | 0.324131E+09 | 0.428505E+09 | 0.138116E+10 | 0.135084E+09 |
November | 0.591158E+09 | 0.235718E+09 | 0.355441E+09 | 0.974541E+09 | 0.262543E+09 |
December | 0.493445E+09 | 0.174210E+09 | 0.319235E+09 | 0.702959E+09 | 0.468383E+09 |
Annual Sum or Average | 0.930965E+10 | 0.378430E+10 | 0.552535E+10 | 0.163089E+11 | 0.278665E+10 |
Minimum of Months | 0.493445E+09 | 0.174210E+09 | 0.319235E+09 | 0.702959E+09 | 31884337.36 |
Maximum of Months | 0.935561E+09 | 0.421133E+09 | 0.593049E+09 | 0.185494E+10 | 0.567271E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.631881E+09 | 0.302710E+09 | 0.329171E+09 | 0.873074E+09 | 0.567271E+09 |
February | 0.659006E+09 | 0.305055E+09 | 0.353951E+09 | 0.988539E+09 | 0.422227E+09 |
March | 0.890803E+09 | 0.421133E+09 | 0.469669E+09 | 0.135072E+10 | 0.364452E+09 |
April | 0.935561E+09 | 0.417443E+09 | 0.518118E+09 | 0.158288E+10 | 0.221893E+09 |
May | 0.914581E+09 | 0.364207E+09 | 0.550373E+09 | 0.168438E+10 | 0.119417E+09 |
June | 0.873586E+09 | 0.335539E+09 | 0.538048E+09 | 0.169627E+10 | 42985929.16 |
July | 0.927539E+09 | 0.334490E+09 | 0.593049E+09 | 0.185494E+10 | 63326781.88 |
August | 0.848154E+09 | 0.283605E+09 | 0.564549E+09 | 0.165899E+10 | 31884337.36 |
September | 0.791299E+09 | 0.286058E+09 | 0.505241E+09 | 0.156041E+10 | 87179999.99 |
October | 0.752637E+09 | 0.324131E+09 | 0.428505E+09 | 0.138116E+10 | 0.135084E+09 |
November | 0.591158E+09 | 0.235718E+09 | 0.355441E+09 | 0.974541E+09 | 0.262543E+09 |
December | 0.493445E+09 | 0.174210E+09 | 0.319235E+09 | 0.702959E+09 | 0.468383E+09 |
Annual Sum or Average | 0.930965E+10 | 0.378430E+10 | 0.552535E+10 | 0.163089E+11 | 0.278665E+10 |
Minimum of Months | 0.493445E+09 | 0.174210E+09 | 0.319235E+09 | 0.702959E+09 | 31884337.36 |
Maximum of Months | 0.935561E+09 | 0.421133E+09 | 0.593049E+09 | 0.185494E+10 | 0.567271E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.631870E+09 | 0.302705E+09 | 0.329165E+09 | 0.873058E+09 | 0.567261E+09 |
February | 0.658994E+09 | 0.305050E+09 | 0.353944E+09 | 0.988521E+09 | 0.422220E+09 |
March | 0.890786E+09 | 0.421126E+09 | 0.469661E+09 | 0.135069E+10 | 0.364445E+09 |
April | 0.935544E+09 | 0.417436E+09 | 0.518108E+09 | 0.158285E+10 | 0.221889E+09 |
May | 0.914564E+09 | 0.364201E+09 | 0.550363E+09 | 0.168435E+10 | 0.119415E+09 |
June | 0.873570E+09 | 0.335532E+09 | 0.538038E+09 | 0.169624E+10 | 42985143.71 |
July | 0.927522E+09 | 0.334484E+09 | 0.593038E+09 | 0.185490E+10 | 63325624.76 |
August | 0.848138E+09 | 0.283600E+09 | 0.564539E+09 | 0.165896E+10 | 31883754.76 |
September | 0.791284E+09 | 0.286052E+09 | 0.505232E+09 | 0.156038E+10 | 87178407.02 |
October | 0.752623E+09 | 0.324125E+09 | 0.428497E+09 | 0.138114E+10 | 0.135081E+09 |
November | 0.591148E+09 | 0.235714E+09 | 0.355434E+09 | 0.974523E+09 | 0.262538E+09 |
December | 0.493436E+09 | 0.174207E+09 | 0.319229E+09 | 0.702946E+09 | 0.468375E+09 |
Annual Sum or Average | 0.930948E+10 | 0.378423E+10 | 0.552525E+10 | 0.163086E+11 | 0.278660E+10 |
Minimum of Months | 0.493436E+09 | 0.174207E+09 | 0.319229E+09 | 0.702946E+09 | 31883754.76 |
Maximum of Months | 0.935544E+09 | 0.421126E+09 | 0.593038E+09 | 0.185490E+10 | 0.567261E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111003E+10 | 0.721158E+09 | 0.388870E+09 | 0.169856E+10 | 0.537572E+09 |
February | 0.907005E+09 | 0.524812E+09 | 0.382193E+09 | 0.146377E+10 | 0.412235E+09 |
March | 0.770987E+09 | 0.325965E+09 | 0.445022E+09 | 0.126303E+10 | 0.372561E+09 |
April | 0.507348E+09 | 88968323.50 | 0.418379E+09 | 0.910975E+09 | 0.234693E+09 |
May | 0.420110E+09 | 9088870.06 | 0.411021E+09 | 0.824764E+09 | 0.118316E+09 |
June | 0.387618E+09 | 731491.00 | 0.386886E+09 | 0.818366E+09 | 49453188.72 |
July | 0.428868E+09 | 3975183.30 | 0.424893E+09 | 0.944175E+09 | 72195657.09 |
August | 0.486750E+09 | 41074249.11 | 0.445676E+09 | 0.102027E+10 | 50500130.53 |
September | 0.603003E+09 | 0.147766E+09 | 0.455237E+09 | 0.126274E+10 | 90990289.42 |
October | 0.856889E+09 | 0.402025E+09 | 0.454865E+09 | 0.159893E+10 | 0.158228E+09 |
November | 0.943500E+09 | 0.526576E+09 | 0.416924E+09 | 0.158371E+10 | 0.278824E+09 |
December | 0.106976E+10 | 0.674740E+09 | 0.395016E+09 | 0.167193E+10 | 0.473967E+09 |
Annual Sum or Average | 0.849186E+10 | 0.346688E+10 | 0.502498E+10 | 0.150612E+11 | 0.284954E+10 |
Minimum of Months | 0.387618E+09 | 731491.00 | 0.382193E+09 | 0.818366E+09 | 49453188.72 |
Maximum of Months | 0.111003E+10 | 0.721158E+09 | 0.455237E+09 | 0.169856E+10 | 0.537572E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111002E+10 | 0.721153E+09 | 0.388867E+09 | 0.169855E+10 | 0.537571E+09 |
February | 0.906999E+09 | 0.524808E+09 | 0.382191E+09 | 0.146376E+10 | 0.412235E+09 |
March | 0.770982E+09 | 0.325963E+09 | 0.445019E+09 | 0.126302E+10 | 0.372561E+09 |
April | 0.507345E+09 | 88967671.54 | 0.418377E+09 | 0.910970E+09 | 0.234692E+09 |
May | 0.420108E+09 | 9088803.46 | 0.411019E+09 | 0.824761E+09 | 0.118315E+09 |
June | 0.387616E+09 | 731485.64 | 0.386884E+09 | 0.818364E+09 | 49452837.15 |
July | 0.428866E+09 | 3975154.17 | 0.424891E+09 | 0.944172E+09 | 72195156.84 |
August | 0.486748E+09 | 41073948.11 | 0.445674E+09 | 0.102027E+10 | 50499717.02 |
September | 0.603000E+09 | 0.147765E+09 | 0.455234E+09 | 0.126273E+10 | 90989828.63 |
October | 0.856884E+09 | 0.402022E+09 | 0.454862E+09 | 0.159893E+10 | 0.158227E+09 |
November | 0.943494E+09 | 0.526572E+09 | 0.416922E+09 | 0.158370E+10 | 0.278823E+09 |
December | 0.106975E+10 | 0.674735E+09 | 0.395014E+09 | 0.167192E+10 | 0.473966E+09 |
Annual Sum or Average | 0.849181E+10 | 0.346686E+10 | 0.502496E+10 | 0.150612E+11 | 0.284953E+10 |
Minimum of Months | 0.387616E+09 | 731485.64 | 0.382191E+09 | 0.818364E+09 | 49452837.15 |
Maximum of Months | 0.111002E+10 | 0.721153E+09 | 0.455234E+09 | 0.169855E+10 | 0.537571E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111003E+10 | 0.721158E+09 | 0.388870E+09 | 0.169856E+10 | 0.537572E+09 |
February | 0.907005E+09 | 0.524812E+09 | 0.382193E+09 | 0.146377E+10 | 0.412235E+09 |
March | 0.770987E+09 | 0.325965E+09 | 0.445022E+09 | 0.126303E+10 | 0.372561E+09 |
April | 0.507348E+09 | 88968323.50 | 0.418379E+09 | 0.910975E+09 | 0.234693E+09 |
May | 0.420110E+09 | 9088870.06 | 0.411021E+09 | 0.824764E+09 | 0.118316E+09 |
June | 0.387618E+09 | 731491.00 | 0.386886E+09 | 0.818366E+09 | 49453188.72 |
July | 0.428868E+09 | 3975183.30 | 0.424893E+09 | 0.944175E+09 | 72195657.09 |
August | 0.486750E+09 | 41074249.11 | 0.445676E+09 | 0.102027E+10 | 50500130.53 |
September | 0.603003E+09 | 0.147766E+09 | 0.455237E+09 | 0.126274E+10 | 90990289.42 |
October | 0.856889E+09 | 0.402025E+09 | 0.454865E+09 | 0.159893E+10 | 0.158228E+09 |
November | 0.943500E+09 | 0.526576E+09 | 0.416924E+09 | 0.158371E+10 | 0.278824E+09 |
December | 0.106976E+10 | 0.674740E+09 | 0.395016E+09 | 0.167193E+10 | 0.473967E+09 |
Annual Sum or Average | 0.849186E+10 | 0.346688E+10 | 0.502498E+10 | 0.150612E+11 | 0.284954E+10 |
Minimum of Months | 0.387618E+09 | 731491.00 | 0.382193E+09 | 0.818366E+09 | 49453188.72 |
Maximum of Months | 0.111003E+10 | 0.721158E+09 | 0.455237E+09 | 0.169856E+10 | 0.537572E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111002E+10 | 0.721153E+09 | 0.388867E+09 | 0.169855E+10 | 0.537571E+09 |
February | 0.906999E+09 | 0.524808E+09 | 0.382191E+09 | 0.146376E+10 | 0.412235E+09 |
March | 0.770982E+09 | 0.325963E+09 | 0.445019E+09 | 0.126302E+10 | 0.372561E+09 |
April | 0.507345E+09 | 88967671.54 | 0.418377E+09 | 0.910970E+09 | 0.234692E+09 |
May | 0.420108E+09 | 9088803.46 | 0.411019E+09 | 0.824761E+09 | 0.118315E+09 |
June | 0.387616E+09 | 731485.64 | 0.386884E+09 | 0.818364E+09 | 49452837.15 |
July | 0.428866E+09 | 3975154.17 | 0.424891E+09 | 0.944172E+09 | 72195156.84 |
August | 0.486748E+09 | 41073948.11 | 0.445674E+09 | 0.102027E+10 | 50499717.02 |
September | 0.603000E+09 | 0.147765E+09 | 0.455234E+09 | 0.126273E+10 | 90989828.63 |
October | 0.856884E+09 | 0.402022E+09 | 0.454862E+09 | 0.159893E+10 | 0.158227E+09 |
November | 0.943494E+09 | 0.526572E+09 | 0.416922E+09 | 0.158370E+10 | 0.278823E+09 |
December | 0.106975E+10 | 0.674735E+09 | 0.395014E+09 | 0.167192E+10 | 0.473966E+09 |
Annual Sum or Average | 0.849181E+10 | 0.346686E+10 | 0.502496E+10 | 0.150612E+11 | 0.284953E+10 |
Minimum of Months | 0.387616E+09 | 731485.64 | 0.382191E+09 | 0.818364E+09 | 49452837.15 |
Maximum of Months | 0.111002E+10 | 0.721153E+09 | 0.455234E+09 | 0.169855E+10 | 0.537571E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110998E+10 | 0.721127E+09 | 0.388853E+09 | 0.169849E+10 | 0.537550E+09 |
February | 0.906966E+09 | 0.524789E+09 | 0.382177E+09 | 0.146371E+10 | 0.412219E+09 |
March | 0.770953E+09 | 0.325951E+09 | 0.445003E+09 | 0.126298E+10 | 0.372546E+09 |
April | 0.507326E+09 | 88964411.72 | 0.418361E+09 | 0.910936E+09 | 0.234683E+09 |
May | 0.420092E+09 | 9088470.44 | 0.411004E+09 | 0.824730E+09 | 0.118311E+09 |
June | 0.387601E+09 | 731458.84 | 0.386870E+09 | 0.818332E+09 | 49451019.76 |
July | 0.428850E+09 | 3975008.51 | 0.424875E+09 | 0.944136E+09 | 72192497.16 |
August | 0.486729E+09 | 41072443.14 | 0.445657E+09 | 0.102023E+10 | 50497888.41 |
September | 0.602977E+09 | 0.147760E+09 | 0.455217E+09 | 0.126268E+10 | 90986391.73 |
October | 0.856852E+09 | 0.402007E+09 | 0.454845E+09 | 0.159887E+10 | 0.158221E+09 |
November | 0.943459E+09 | 0.526553E+09 | 0.416906E+09 | 0.158365E+10 | 0.278812E+09 |
December | 0.106971E+10 | 0.674710E+09 | 0.394999E+09 | 0.167186E+10 | 0.473947E+09 |
Annual Sum or Average | 0.849149E+10 | 0.346673E+10 | 0.502477E+10 | 0.150606E+11 | 0.284942E+10 |
Minimum of Months | 0.387601E+09 | 731458.84 | 0.382177E+09 | 0.818332E+09 | 49451019.76 |
Maximum of Months | 0.110998E+10 | 0.721127E+09 | 0.455217E+09 | 0.169849E+10 | 0.537550E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.567640E+09 | 0.244718E+09 | 0.322922E+09 | 0.775564E+09 | 0.664001E+09 |
February | 0.641127E+09 | 0.290147E+09 | 0.350980E+09 | 0.964410E+09 | 0.535448E+09 |
March | 0.883942E+09 | 0.403654E+09 | 0.480288E+09 | 0.133682E+10 | 0.504642E+09 |
April | 0.941577E+09 | 0.435981E+09 | 0.505596E+09 | 0.154877E+10 | 0.338193E+09 |
May | 0.886982E+09 | 0.341447E+09 | 0.545535E+09 | 0.162360E+10 | 0.174323E+09 |
June | 0.727302E+09 | 0.204015E+09 | 0.523287E+09 | 0.139569E+10 | 86111306.76 |
July | 0.839920E+09 | 0.259845E+09 | 0.580075E+09 | 0.164711E+10 | 0.126322E+09 |
August | 0.838010E+09 | 0.273106E+09 | 0.564904E+09 | 0.155550E+10 | 0.122001E+09 |
September | 0.691807E+09 | 0.203992E+09 | 0.487815E+09 | 0.135565E+10 | 0.118968E+09 |
October | 0.711161E+09 | 0.277233E+09 | 0.433929E+09 | 0.128099E+10 | 0.212747E+09 |
November | 0.567710E+09 | 0.208239E+09 | 0.359471E+09 | 0.913868E+09 | 0.381708E+09 |
December | 0.587683E+09 | 0.262749E+09 | 0.324934E+09 | 0.828542E+09 | 0.635110E+09 |
Annual Sum or Average | 0.888486E+10 | 0.340513E+10 | 0.547974E+10 | 0.152265E+11 | 0.389958E+10 |
Minimum of Months | 0.567640E+09 | 0.203992E+09 | 0.322922E+09 | 0.775564E+09 | 86111306.76 |
Maximum of Months | 0.941577E+09 | 0.435981E+09 | 0.580075E+09 | 0.164711E+10 | 0.664001E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.567640E+09 | 0.244718E+09 | 0.322922E+09 | 0.775564E+09 | 0.664001E+09 |
February | 0.641127E+09 | 0.290147E+09 | 0.350980E+09 | 0.964410E+09 | 0.535448E+09 |
March | 0.883942E+09 | 0.403654E+09 | 0.480288E+09 | 0.133682E+10 | 0.504642E+09 |
April | 0.941577E+09 | 0.435981E+09 | 0.505596E+09 | 0.154877E+10 | 0.338193E+09 |
May | 0.886982E+09 | 0.341447E+09 | 0.545535E+09 | 0.162360E+10 | 0.174323E+09 |
June | 0.727302E+09 | 0.204015E+09 | 0.523287E+09 | 0.139569E+10 | 86111306.76 |
July | 0.839920E+09 | 0.259845E+09 | 0.580075E+09 | 0.164711E+10 | 0.126322E+09 |
August | 0.838010E+09 | 0.273106E+09 | 0.564904E+09 | 0.155550E+10 | 0.122001E+09 |
September | 0.691807E+09 | 0.203992E+09 | 0.487815E+09 | 0.135565E+10 | 0.118968E+09 |
October | 0.711161E+09 | 0.277233E+09 | 0.433929E+09 | 0.128099E+10 | 0.212747E+09 |
November | 0.567710E+09 | 0.208239E+09 | 0.359471E+09 | 0.913868E+09 | 0.381708E+09 |
December | 0.587683E+09 | 0.262749E+09 | 0.324934E+09 | 0.828542E+09 | 0.635110E+09 |
Annual Sum or Average | 0.888486E+10 | 0.340513E+10 | 0.547974E+10 | 0.152265E+11 | 0.389958E+10 |
Minimum of Months | 0.567640E+09 | 0.203992E+09 | 0.322922E+09 | 0.775564E+09 | 86111306.76 |
Maximum of Months | 0.941577E+09 | 0.435981E+09 | 0.580075E+09 | 0.164711E+10 | 0.664001E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.567630E+09 | 0.244713E+09 | 0.322917E+09 | 0.775550E+09 | 0.663989E+09 |
February | 0.641115E+09 | 0.290141E+09 | 0.350974E+09 | 0.964393E+09 | 0.535438E+09 |
March | 0.883926E+09 | 0.403647E+09 | 0.480279E+09 | 0.133680E+10 | 0.504633E+09 |
April | 0.941560E+09 | 0.435973E+09 | 0.505587E+09 | 0.154875E+10 | 0.338187E+09 |
May | 0.886966E+09 | 0.341441E+09 | 0.545525E+09 | 0.162357E+10 | 0.174320E+09 |
June | 0.727289E+09 | 0.204011E+09 | 0.523278E+09 | 0.139566E+10 | 86109733.31 |
July | 0.839905E+09 | 0.259840E+09 | 0.580065E+09 | 0.164708E+10 | 0.126319E+09 |
August | 0.837995E+09 | 0.273101E+09 | 0.564894E+09 | 0.155547E+10 | 0.121999E+09 |
September | 0.691795E+09 | 0.203988E+09 | 0.487806E+09 | 0.135562E+10 | 0.118966E+09 |
October | 0.711148E+09 | 0.277228E+09 | 0.433921E+09 | 0.128097E+10 | 0.212744E+09 |
November | 0.567700E+09 | 0.208236E+09 | 0.359464E+09 | 0.913851E+09 | 0.381701E+09 |
December | 0.587673E+09 | 0.262744E+09 | 0.324929E+09 | 0.828526E+09 | 0.635098E+09 |
Annual Sum or Average | 0.888470E+10 | 0.340506E+10 | 0.547964E+10 | 0.152262E+11 | 0.389950E+10 |
Minimum of Months | 0.567630E+09 | 0.203988E+09 | 0.322917E+09 | 0.775550E+09 | 86109733.31 |
Maximum of Months | 0.941560E+09 | 0.435973E+09 | 0.580065E+09 | 0.164708E+10 | 0.663989E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118092E+10 | 0.00 | 0.118092E+10 | 0.124178E+10 | 0.255642E+10 |
February | 0.126253E+10 | 0.00 | 0.126253E+10 | 0.167345E+10 | 0.190147E+10 |
March | 0.166698E+10 | 0.00 | 0.166698E+10 | 0.220380E+10 | 0.175670E+10 |
April | 0.180767E+10 | 8120275.76 | 0.179955E+10 | 0.295345E+10 | 0.109247E+10 |
May | 0.213308E+10 | 95417691.79 | 0.203766E+10 | 0.417419E+10 | 0.595281E+09 |
June | 0.220509E+10 | 0.158773E+09 | 0.204631E+10 | 0.464534E+10 | 0.265512E+09 |
July | 0.230585E+10 | 0.112991E+09 | 0.219286E+10 | 0.508518E+10 | 0.381731E+09 |
August | 0.204071E+10 | 18768947.75 | 0.202194E+10 | 0.429910E+10 | 0.254990E+09 |
September | 0.175196E+10 | 138596.46 | 0.175182E+10 | 0.382616E+10 | 0.418011E+09 |
October | 0.151664E+10 | 0.00 | 0.151664E+10 | 0.293617E+10 | 0.676425E+09 |
November | 0.127619E+10 | 0.00 | 0.127619E+10 | 0.201447E+10 | 0.126493E+10 |
December | 0.116808E+10 | 0.00 | 0.116808E+10 | 0.138615E+10 | 0.217463E+10 |
Annual Sum or Average | 0.203157E+11 | 0.394210E+09 | 0.199215E+11 | 0.364392E+11 | 0.133386E+11 |
Minimum of Months | 0.116808E+10 | 0.00 | 0.116808E+10 | 0.124178E+10 | 0.254990E+09 |
Maximum of Months | 0.230585E+10 | 0.158773E+09 | 0.219286E+10 | 0.508518E+10 | 0.255642E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189562E+10 | 0.908121E+09 | 0.987503E+09 | 0.263175E+10 | 0.160261E+10 |
February | 0.197700E+10 | 0.915156E+09 | 0.106184E+10 | 0.296173E+10 | 0.119829E+10 |
March | 0.267238E+10 | 0.126339E+10 | 0.140899E+10 | 0.400258E+10 | 0.109590E+10 |
April | 0.280665E+10 | 0.125232E+10 | 0.155434E+10 | 0.468258E+10 | 0.735114E+09 |
May | 0.274371E+10 | 0.109261E+10 | 0.165110E+10 | 0.500404E+10 | 0.382682E+09 |
June | 0.262073E+10 | 0.100661E+10 | 0.161413E+10 | 0.502220E+10 | 0.172975E+09 |
July | 0.278259E+10 | 0.100346E+10 | 0.177913E+10 | 0.551041E+10 | 0.256013E+09 |
August | 0.254444E+10 | 0.850805E+09 | 0.169363E+10 | 0.491791E+10 | 0.163594E+09 |
September | 0.237387E+10 | 0.858164E+09 | 0.151571E+10 | 0.463887E+10 | 0.282896E+09 |
October | 0.225789E+10 | 0.972384E+09 | 0.128550E+10 | 0.410676E+10 | 0.448761E+09 |
November | 0.177346E+10 | 0.707146E+09 | 0.106631E+10 | 0.290278E+10 | 0.792572E+09 |
December | 0.148032E+10 | 0.522625E+09 | 0.957695E+09 | 0.211512E+10 | 0.136476E+10 |
Annual Sum or Average | 0.279287E+11 | 0.113528E+11 | 0.165759E+11 | 0.484967E+11 | 0.849616E+10 |
Minimum of Months | 0.148032E+10 | 0.522625E+09 | 0.957695E+09 | 0.211512E+10 | 0.163594E+09 |
Maximum of Months | 0.280665E+10 | 0.126339E+10 | 0.177913E+10 | 0.551041E+10 | 0.160261E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555024E+10 | 0.360587E+10 | 0.194437E+10 | 0.841318E+10 | 0.264761E+10 |
February | 0.453510E+10 | 0.262412E+10 | 0.191099E+10 | 0.725805E+10 | 0.200216E+10 |
March | 0.385499E+10 | 0.162986E+10 | 0.222513E+10 | 0.626297E+10 | 0.182265E+10 |
April | 0.253677E+10 | 0.444851E+09 | 0.209192E+10 | 0.454724E+10 | 0.117193E+10 |
May | 0.210057E+10 | 45445305.95 | 0.205512E+10 | 0.412653E+10 | 0.583324E+09 |
June | 0.193811E+10 | 3657531.91 | 0.193445E+10 | 0.411059E+10 | 0.263851E+09 |
July | 0.214436E+10 | 19876334.45 | 0.212448E+10 | 0.475774E+10 | 0.378391E+09 |
August | 0.243378E+10 | 0.205376E+09 | 0.222840E+10 | 0.514292E+10 | 0.268628E+09 |
September | 0.301506E+10 | 0.738847E+09 | 0.227621E+10 | 0.628745E+10 | 0.464984E+09 |
October | 0.428452E+10 | 0.201016E+10 | 0.227435E+10 | 0.793808E+10 | 0.814693E+09 |
November | 0.471759E+10 | 0.263293E+10 | 0.208465E+10 | 0.785733E+10 | 0.137968E+10 |
December | 0.534888E+10 | 0.337377E+10 | 0.197511E+10 | 0.829760E+10 | 0.232868E+10 |
Annual Sum or Average | 0.424600E+11 | 0.173348E+11 | 0.251252E+11 | 0.749997E+11 | 0.141266E+11 |
Minimum of Months | 0.193811E+10 | 3657531.91 | 0.191099E+10 | 0.411059E+10 | 0.263851E+09 |
Maximum of Months | 0.555024E+10 | 0.360587E+10 | 0.227621E+10 | 0.841318E+10 | 0.264761E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170290E+10 | 0.734146E+09 | 0.968757E+09 | 0.240131E+10 | 0.174792E+10 |
February | 0.192336E+10 | 0.870431E+09 | 0.105293E+10 | 0.297880E+10 | 0.135938E+10 |
March | 0.265180E+10 | 0.121095E+10 | 0.144085E+10 | 0.409213E+10 | 0.129269E+10 |
April | 0.282470E+10 | 0.130793E+10 | 0.151677E+10 | 0.474344E+10 | 0.873904E+09 |
May | 0.266092E+10 | 0.102433E+10 | 0.163659E+10 | 0.489173E+10 | 0.478611E+09 |
June | 0.218188E+10 | 0.612039E+09 | 0.156985E+10 | 0.425876E+10 | 0.217785E+09 |
July | 0.251974E+10 | 0.779528E+09 | 0.174021E+10 | 0.504527E+10 | 0.313140E+09 |
August | 0.251400E+10 | 0.819310E+09 | 0.169469E+10 | 0.482399E+10 | 0.235459E+09 |
September | 0.207540E+10 | 0.611970E+09 | 0.146343E+10 | 0.410776E+10 | 0.318272E+09 |
October | 0.213346E+10 | 0.831689E+09 | 0.130177E+10 | 0.390373E+10 | 0.543527E+09 |
November | 0.170311E+10 | 0.624712E+09 | 0.107840E+10 | 0.283860E+10 | 0.923901E+09 |
December | 0.176303E+10 | 0.788238E+09 | 0.974793E+09 | 0.261648E+10 | 0.153041E+10 |
Annual Sum or Average | 0.266543E+11 | 0.102153E+11 | 0.164390E+11 | 0.467020E+11 | 0.983498E+10 |
Minimum of Months | 0.170290E+10 | 0.611970E+09 | 0.968757E+09 | 0.240131E+10 | 0.217785E+09 |
Maximum of Months | 0.282470E+10 | 0.130793E+10 | 0.174021E+10 | 0.504527E+10 | 0.174792E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118092E+10 | 0.00 | 0.118092E+10 | 0.130044E+10 | 0.234091E+10 |
February | 0.126253E+10 | 0.00 | 0.126253E+10 | 0.169920E+10 | 0.177446E+10 |
March | 0.166698E+10 | 0.00 | 0.166698E+10 | 0.220008E+10 | 0.167489E+10 |
April | 0.180767E+10 | 8120275.76 | 0.179955E+10 | 0.291009E+10 | 0.108492E+10 |
May | 0.213308E+10 | 95417691.79 | 0.203766E+10 | 0.410796E+10 | 0.616418E+09 |
June | 0.220509E+10 | 0.158773E+09 | 0.204631E+10 | 0.456345E+10 | 0.280294E+09 |
July | 0.230585E+10 | 0.112991E+09 | 0.219286E+10 | 0.499528E+10 | 0.406042E+09 |
August | 0.204071E+10 | 18768947.75 | 0.202194E+10 | 0.423153E+10 | 0.268824E+09 |
September | 0.175196E+10 | 138596.46 | 0.175182E+10 | 0.375107E+10 | 0.427736E+09 |
October | 0.151664E+10 | 0.00 | 0.151664E+10 | 0.289362E+10 | 0.677500E+09 |
November | 0.127619E+10 | 0.00 | 0.127619E+10 | 0.201398E+10 | 0.119340E+10 |
December | 0.116808E+10 | 0.00 | 0.116808E+10 | 0.142452E+10 | 0.201467E+10 |
Annual Sum or Average | 0.203157E+11 | 0.394210E+09 | 0.199215E+11 | 0.360912E+11 | 0.127601E+11 |
Minimum of Months | 0.116808E+10 | 0.00 | 0.116808E+10 | 0.130044E+10 | 0.268824E+09 |
Maximum of Months | 0.230585E+10 | 0.158773E+09 | 0.219286E+10 | 0.499528E+10 | 0.234091E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189562E+10 | 0.908121E+09 | 0.987503E+09 | 0.265974E+10 | 0.151115E+10 |
February | 0.197700E+10 | 0.915156E+09 | 0.106184E+10 | 0.296773E+10 | 0.114440E+10 |
March | 0.267238E+10 | 0.126339E+10 | 0.140899E+10 | 0.398109E+10 | 0.107176E+10 |
April | 0.280665E+10 | 0.125232E+10 | 0.155434E+10 | 0.463788E+10 | 0.742146E+09 |
May | 0.274371E+10 | 0.109261E+10 | 0.165110E+10 | 0.494666E+10 | 0.398937E+09 |
June | 0.262073E+10 | 0.100661E+10 | 0.161413E+10 | 0.495918E+10 | 0.182917E+09 |
July | 0.278259E+10 | 0.100346E+10 | 0.177913E+10 | 0.544093E+10 | 0.271929E+09 |
August | 0.254444E+10 | 0.850805E+09 | 0.169363E+10 | 0.486105E+10 | 0.172984E+09 |
September | 0.237387E+10 | 0.858164E+09 | 0.151571E+10 | 0.457910E+10 | 0.291280E+09 |
October | 0.225789E+10 | 0.972384E+09 | 0.128550E+10 | 0.406661E+10 | 0.456688E+09 |
November | 0.177346E+10 | 0.707146E+09 | 0.106631E+10 | 0.289205E+10 | 0.765473E+09 |
December | 0.148032E+10 | 0.522625E+09 | 0.957695E+09 | 0.212749E+10 | 0.129583E+10 |
Annual Sum or Average | 0.279287E+11 | 0.113528E+11 | 0.165759E+11 | 0.481195E+11 | 0.830549E+10 |
Minimum of Months | 0.148032E+10 | 0.522625E+09 | 0.957695E+09 | 0.212749E+10 | 0.172984E+09 |
Maximum of Months | 0.280665E+10 | 0.126339E+10 | 0.177913E+10 | 0.544093E+10 | 0.151115E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555024E+10 | 0.360587E+10 | 0.194437E+10 | 0.844340E+10 | 0.250571E+10 |
February | 0.453510E+10 | 0.262412E+10 | 0.191099E+10 | 0.726036E+10 | 0.191584E+10 |
March | 0.385499E+10 | 0.162986E+10 | 0.222513E+10 | 0.623401E+10 | 0.177016E+10 |
April | 0.253677E+10 | 0.444851E+09 | 0.209192E+10 | 0.449553E+10 | 0.116910E+10 |
May | 0.210057E+10 | 45445305.95 | 0.205512E+10 | 0.405939E+10 | 0.601044E+09 |
June | 0.193811E+10 | 3657531.91 | 0.193445E+10 | 0.403206E+10 | 0.277064E+09 |
July | 0.214436E+10 | 19876334.45 | 0.212448E+10 | 0.466963E+10 | 0.400291E+09 |
August | 0.243378E+10 | 0.205376E+09 | 0.222840E+10 | 0.507146E+10 | 0.281132E+09 |
September | 0.301506E+10 | 0.738847E+09 | 0.227621E+10 | 0.620810E+10 | 0.477160E+09 |
October | 0.428452E+10 | 0.201016E+10 | 0.227435E+10 | 0.788345E+10 | 0.825038E+09 |
November | 0.471759E+10 | 0.263293E+10 | 0.208465E+10 | 0.783988E+10 | 0.133770E+10 |
December | 0.534888E+10 | 0.337377E+10 | 0.197511E+10 | 0.830162E+10 | 0.222312E+10 |
Annual Sum or Average | 0.424600E+11 | 0.173348E+11 | 0.251252E+11 | 0.744989E+11 | 0.137834E+11 |
Minimum of Months | 0.193811E+10 | 3657531.91 | 0.191099E+10 | 0.403206E+10 | 0.277064E+09 |
Maximum of Months | 0.555024E+10 | 0.360587E+10 | 0.227621E+10 | 0.844340E+10 | 0.250571E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170290E+10 | 0.734146E+09 | 0.968757E+09 | 0.242451E+10 | 0.163660E+10 |
February | 0.192336E+10 | 0.870431E+09 | 0.105293E+10 | 0.298313E+10 | 0.129434E+10 |
March | 0.265180E+10 | 0.121095E+10 | 0.144085E+10 | 0.407656E+10 | 0.125386E+10 |
April | 0.282470E+10 | 0.130793E+10 | 0.151677E+10 | 0.470959E+10 | 0.871755E+09 |
May | 0.266092E+10 | 0.102433E+10 | 0.163659E+10 | 0.484830E+10 | 0.488175E+09 |
June | 0.218188E+10 | 0.612039E+09 | 0.156985E+10 | 0.421138E+10 | 0.222831E+09 |
July | 0.251974E+10 | 0.779528E+09 | 0.174021E+10 | 0.499070E+10 | 0.320536E+09 |
August | 0.251400E+10 | 0.819310E+09 | 0.169469E+10 | 0.478054E+10 | 0.241985E+09 |
September | 0.207540E+10 | 0.611970E+09 | 0.146343E+10 | 0.406387E+10 | 0.320545E+09 |
October | 0.213346E+10 | 0.831689E+09 | 0.130177E+10 | 0.387437E+10 | 0.542266E+09 |
November | 0.170311E+10 | 0.624712E+09 | 0.107840E+10 | 0.283304E+10 | 0.887142E+09 |
December | 0.176303E+10 | 0.788238E+09 | 0.974793E+09 | 0.262761E+10 | 0.144836E+10 |
Annual Sum or Average | 0.266543E+11 | 0.102153E+11 | 0.164390E+11 | 0.464236E+11 | 0.952840E+10 |
Minimum of Months | 0.170290E+10 | 0.611970E+09 | 0.968757E+09 | 0.242451E+10 | 0.222831E+09 |
Maximum of Months | 0.282470E+10 | 0.130793E+10 | 0.174021E+10 | 0.499070E+10 | 0.163660E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 436.94 | 1045.43 | 440.90 | 0.00 | 440.90 | 0.00 | 0.00 |
February | 663.73 | 869.54 | 521.87 | 0.00 | 521.87 | 0.00 | 0.00 |
March | 806.63 | 705.24 | 622.37 | 0.00 | 622.37 | 0.00 | 0.00 |
April | 1126.36 | 430.71 | 697.39 | 3.13 | 694.26 | 0.00 | 0.00 |
May | 1558.37 | 222.88 | 796.39 | 35.62 | 760.76 | 0.00 | 0.00 |
June | 1791.99 | 93.54 | 850.71 | 61.25 | 789.46 | 0.00 | 0.00 |
July | 1888.05 | 133.76 | 860.89 | 42.18 | 818.71 | 0.00 | 0.00 |
August | 1583.33 | 90.29 | 761.90 | 7.01 | 754.89 | 0.00 | 0.00 |
September | 1469.38 | 161.73 | 675.90 | 0.05 | 675.85 | 0.00 | 0.00 |
October | 1085.10 | 259.16 | 566.24 | 0.00 | 566.24 | 0.00 | 0.00 |
November | 758.97 | 529.54 | 492.35 | 0.00 | 492.35 | 0.00 | 0.00 |
December | 488.74 | 897.55 | 436.10 | 0.00 | 436.10 | 0.00 | 0.00 |
Annual Sum or Average | 1140.40 | 451.50 | 644.20 | 12.50 | 631.70 | 0.00 | 0.00 |
Minimum of Months | 436.94 | 90.29 | 436.10 | 0.00 | 436.10 | 0.00 | 0.00 |
Maximum of Months | 1888.05 | 1045.43 | 860.89 | 61.25 | 818.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 977.90 | 635.38 | 707.75 | 339.06 | 368.69 | 0.00 | 0.00 |
February | 1225.86 | 523.59 | 817.21 | 378.29 | 438.92 | 0.00 | 0.00 |
March | 1512.89 | 408.21 | 997.76 | 471.70 | 526.06 | 0.00 | 0.00 |
April | 1832.03 | 256.82 | 1082.82 | 483.15 | 599.67 | 0.00 | 0.00 |
May | 1886.62 | 133.76 | 1024.39 | 407.94 | 616.45 | 0.00 | 0.00 |
June | 1963.27 | 49.75 | 1011.09 | 388.35 | 622.74 | 0.00 | 0.00 |
July | 2077.65 | 70.93 | 1038.90 | 374.65 | 664.25 | 0.00 | 0.00 |
August | 1858.18 | 35.71 | 949.99 | 317.66 | 632.33 | 0.00 | 0.00 |
September | 1806.02 | 100.90 | 915.85 | 331.08 | 584.77 | 0.00 | 0.00 |
October | 1546.99 | 151.30 | 843.00 | 363.05 | 479.95 | 0.00 | 0.00 |
November | 1127.93 | 303.87 | 684.21 | 272.82 | 411.39 | 0.00 | 0.00 |
December | 787.36 | 524.62 | 552.69 | 195.13 | 357.56 | 0.00 | 0.00 |
Annual Sum or Average | 1551.44 | 265.09 | 885.62 | 360.00 | 525.62 | 0.00 | 0.00 |
Minimum of Months | 787.36 | 35.71 | 552.69 | 195.13 | 357.56 | 0.00 | 0.00 |
Maximum of Months | 2077.65 | 635.38 | 1082.82 | 483.15 | 664.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3170.82 | 1003.52 | 2072.16 | 1346.23 | 725.93 | 0.00 | 0.00 |
February | 3025.29 | 852.00 | 1874.58 | 1084.67 | 789.91 | 0.00 | 0.00 |
March | 2357.78 | 695.49 | 1439.25 | 608.50 | 830.75 | 0.00 | 0.00 |
April | 1757.26 | 452.72 | 978.67 | 171.62 | 807.05 | 0.00 | 0.00 |
May | 1539.64 | 220.87 | 784.25 | 16.97 | 767.28 | 0.00 | 0.00 |
June | 1578.62 | 95.39 | 747.71 | 1.41 | 746.30 | 0.00 | 0.00 |
July | 1762.56 | 134.77 | 800.60 | 7.42 | 793.18 | 0.00 | 0.00 |
August | 1904.61 | 94.27 | 908.65 | 76.68 | 831.97 | 0.00 | 0.00 |
September | 2435.81 | 175.52 | 1163.19 | 285.04 | 878.15 | 0.00 | 0.00 |
October | 2984.84 | 295.38 | 1599.61 | 750.49 | 849.13 | 0.00 | 0.00 |
November | 3054.97 | 537.85 | 1820.00 | 1015.76 | 804.24 | 0.00 | 0.00 |
December | 3121.10 | 884.79 | 1996.98 | 1259.58 | 737.40 | 0.00 | 0.00 |
Annual Sum or Average | 2387.92 | 451.79 | 1346.36 | 549.66 | 796.70 | 0.00 | 0.00 |
Minimum of Months | 1539.64 | 94.27 | 747.71 | 1.41 | 725.93 | 0.00 | 0.00 |
Maximum of Months | 3170.82 | 1003.52 | 2072.16 | 1346.23 | 878.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 868.68 | 743.72 | 635.79 | 274.10 | 361.69 | 0.00 | 0.00 |
February | 1195.94 | 663.99 | 795.04 | 359.80 | 435.24 | 0.00 | 0.00 |
March | 1497.33 | 565.23 | 990.07 | 452.12 | 537.95 | 0.00 | 0.00 |
April | 1792.55 | 391.42 | 1089.78 | 504.60 | 585.18 | 0.00 | 0.00 |
May | 1818.54 | 195.25 | 993.48 | 382.44 | 611.04 | 0.00 | 0.00 |
June | 1615.37 | 99.67 | 841.78 | 236.13 | 605.65 | 0.00 | 0.00 |
July | 1844.87 | 141.49 | 940.77 | 291.04 | 649.72 | 0.00 | 0.00 |
August | 1742.26 | 136.65 | 938.63 | 305.90 | 632.73 | 0.00 | 0.00 |
September | 1569.03 | 137.69 | 800.70 | 236.10 | 564.60 | 0.00 | 0.00 |
October | 1434.79 | 238.29 | 796.55 | 310.52 | 486.03 | 0.00 | 0.00 |
November | 1057.71 | 441.79 | 657.07 | 241.02 | 416.05 | 0.00 | 0.00 |
December | 928.02 | 711.36 | 658.24 | 294.30 | 363.95 | 0.00 | 0.00 |
Annual Sum or Average | 1448.48 | 370.96 | 845.21 | 323.93 | 521.28 | 0.00 | 0.00 |
Minimum of Months | 868.68 | 99.67 | 635.79 | 236.10 | 361.69 | 0.00 | 0.00 |
Maximum of Months | 1844.87 | 743.72 | 1089.78 | 504.60 | 649.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 463.63 | 954.46 | 440.90 | 0.00 | 440.90 | 0.00 | 0.00 |
February | 691.74 | 785.99 | 521.88 | 0.00 | 521.88 | 0.00 | 0.00 |
March | 822.81 | 655.88 | 622.38 | 0.00 | 622.38 | 0.00 | 0.00 |
April | 1139.45 | 421.48 | 697.41 | 3.13 | 694.27 | 0.00 | 0.00 |
May | 1558.46 | 222.25 | 796.40 | 35.62 | 760.78 | 0.00 | 0.00 |
June | 1792.18 | 102.44 | 850.73 | 61.25 | 789.47 | 0.00 | 0.00 |
July | 1898.59 | 142.52 | 860.91 | 42.19 | 818.72 | 0.00 | 0.00 |
August | 1605.10 | 95.20 | 761.91 | 7.01 | 754.91 | 0.00 | 0.00 |
September | 1476.14 | 161.27 | 675.91 | 0.05 | 675.86 | 0.00 | 0.00 |
October | 1096.24 | 252.55 | 566.25 | 0.00 | 566.25 | 0.00 | 0.00 |
November | 777.19 | 488.01 | 492.36 | 0.00 | 492.36 | 0.00 | 0.00 |
December | 517.53 | 811.91 | 436.11 | 0.00 | 436.11 | 0.00 | 0.00 |
Annual Sum or Average | 1155.48 | 422.96 | 644.21 | 12.50 | 631.71 | 0.00 | 0.00 |
Minimum of Months | 463.63 | 95.20 | 436.11 | 0.00 | 436.11 | 0.00 | 0.00 |
Maximum of Months | 1898.59 | 954.46 | 860.91 | 61.25 | 818.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 982.58 | 598.34 | 707.75 | 339.05 | 368.69 | 0.00 | 0.00 |
February | 1224.26 | 495.32 | 817.21 | 378.29 | 438.92 | 0.00 | 0.00 |
March | 1494.39 | 409.16 | 997.75 | 471.69 | 526.06 | 0.00 | 0.00 |
April | 1806.55 | 283.61 | 1082.81 | 483.15 | 599.67 | 0.00 | 0.00 |
May | 1868.29 | 142.88 | 1024.39 | 407.93 | 616.45 | 0.00 | 0.00 |
June | 1937.58 | 66.73 | 1011.08 | 388.35 | 622.73 | 0.00 | 0.00 |
July | 2057.35 | 95.58 | 1038.90 | 374.65 | 664.25 | 0.00 | 0.00 |
August | 1836.14 | 61.08 | 949.98 | 317.65 | 632.33 | 0.00 | 0.00 |
September | 1789.69 | 109.14 | 915.85 | 331.08 | 584.76 | 0.00 | 0.00 |
October | 1533.29 | 167.55 | 843.00 | 363.05 | 479.95 | 0.00 | 0.00 |
November | 1119.90 | 305.78 | 684.20 | 272.82 | 411.39 | 0.00 | 0.00 |
December | 789.70 | 509.54 | 552.69 | 195.13 | 357.56 | 0.00 | 0.00 |
Annual Sum or Average | 1537.82 | 269.41 | 885.61 | 359.99 | 525.62 | 0.00 | 0.00 |
Minimum of Months | 789.70 | 61.08 | 552.69 | 195.13 | 357.56 | 0.00 | 0.00 |
Maximum of Months | 2057.35 | 598.34 | 1082.81 | 483.15 | 664.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3141.12 | 988.51 | 2072.22 | 1346.28 | 725.95 | 0.00 | 0.00 |
February | 3000.19 | 827.61 | 1874.63 | 1084.70 | 789.93 | 0.00 | 0.00 |
March | 2338.32 | 680.50 | 1439.29 | 608.52 | 830.77 | 0.00 | 0.00 |
April | 1754.34 | 452.13 | 978.69 | 171.62 | 807.07 | 0.00 | 0.00 |
May | 1540.67 | 217.79 | 784.26 | 16.97 | 767.30 | 0.00 | 0.00 |
June | 1585.88 | 101.79 | 747.73 | 1.41 | 746.32 | 0.00 | 0.00 |
July | 1776.34 | 141.28 | 800.61 | 7.42 | 793.19 | 0.00 | 0.00 |
August | 1920.15 | 100.29 | 908.67 | 76.68 | 831.99 | 0.00 | 0.00 |
September | 2425.71 | 179.39 | 1163.22 | 285.05 | 878.17 | 0.00 | 0.00 |
October | 2963.74 | 304.17 | 1599.66 | 750.51 | 849.15 | 0.00 | 0.00 |
November | 3031.38 | 532.28 | 1820.06 | 1015.79 | 804.26 | 0.00 | 0.00 |
December | 3097.97 | 869.43 | 1997.04 | 1259.62 | 737.42 | 0.00 | 0.00 |
Annual Sum or Average | 2378.22 | 447.95 | 1346.40 | 549.68 | 796.71 | 0.00 | 0.00 |
Minimum of Months | 1540.67 | 100.29 | 747.73 | 1.41 | 725.95 | 0.00 | 0.00 |
Maximum of Months | 3141.12 | 988.51 | 2072.22 | 1346.28 | 878.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 896.55 | 652.60 | 635.79 | 274.10 | 361.69 | 0.00 | 0.00 |
February | 1231.32 | 561.91 | 795.04 | 359.80 | 435.24 | 0.00 | 0.00 |
March | 1527.83 | 482.63 | 990.07 | 452.12 | 537.95 | 0.00 | 0.00 |
April | 1830.03 | 337.15 | 1089.78 | 504.60 | 585.17 | 0.00 | 0.00 |
May | 1826.36 | 178.69 | 993.47 | 382.44 | 611.03 | 0.00 | 0.00 |
June | 1643.04 | 84.02 | 841.78 | 236.13 | 605.65 | 0.00 | 0.00 |
July | 1883.69 | 116.91 | 940.76 | 291.04 | 649.72 | 0.00 | 0.00 |
August | 1801.07 | 87.91 | 938.62 | 305.90 | 632.73 | 0.00 | 0.00 |
September | 1584.78 | 122.79 | 800.69 | 236.10 | 564.60 | 0.00 | 0.00 |
October | 1457.48 | 202.93 | 796.54 | 310.52 | 486.03 | 0.00 | 0.00 |
November | 1095.14 | 356.44 | 657.06 | 241.02 | 416.05 | 0.00 | 0.00 |
December | 976.88 | 571.39 | 658.24 | 294.29 | 363.95 | 0.00 | 0.00 |
Annual Sum or Average | 1480.91 | 311.87 | 845.20 | 323.92 | 521.28 | 0.00 | 0.00 |
Minimum of Months | 896.55 | 84.02 | 635.79 | 236.10 | 361.69 | 0.00 | 0.00 |
Maximum of Months | 1883.69 | 652.60 | 1089.78 | 504.60 | 649.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 485.53 | 874.00 | 440.90 | 0.00 | 440.90 | 0.00 | 0.00 |
February | 702.38 | 733.49 | 521.88 | 0.00 | 521.88 | 0.00 | 0.00 |
March | 821.42 | 625.33 | 622.38 | 0.00 | 622.38 | 0.00 | 0.00 |
April | 1122.72 | 418.57 | 697.41 | 3.13 | 694.27 | 0.00 | 0.00 |
May | 1533.74 | 230.14 | 796.40 | 35.62 | 760.78 | 0.00 | 0.00 |
June | 1760.59 | 108.14 | 850.73 | 61.25 | 789.47 | 0.00 | 0.00 |
July | 1865.03 | 151.60 | 860.91 | 42.19 | 818.72 | 0.00 | 0.00 |
August | 1579.87 | 100.37 | 761.91 | 7.01 | 754.91 | 0.00 | 0.00 |
September | 1447.17 | 165.02 | 675.91 | 0.05 | 675.86 | 0.00 | 0.00 |
October | 1080.35 | 252.95 | 566.25 | 0.00 | 566.25 | 0.00 | 0.00 |
November | 777.00 | 460.42 | 492.36 | 0.00 | 492.36 | 0.00 | 0.00 |
December | 531.86 | 752.19 | 436.11 | 0.00 | 436.11 | 0.00 | 0.00 |
Annual Sum or Average | 1144.45 | 404.62 | 644.21 | 12.50 | 631.71 | 0.00 | 0.00 |
Minimum of Months | 485.53 | 100.37 | 436.11 | 0.00 | 436.11 | 0.00 | 0.00 |
Maximum of Months | 1865.03 | 874.00 | 860.91 | 61.25 | 818.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 993.03 | 564.20 | 707.75 | 339.05 | 368.69 | 0.00 | 0.00 |
February | 1226.74 | 473.05 | 817.21 | 378.29 | 438.92 | 0.00 | 0.00 |
March | 1486.37 | 400.15 | 997.75 | 471.69 | 526.06 | 0.00 | 0.00 |
April | 1789.31 | 286.32 | 1082.81 | 483.15 | 599.67 | 0.00 | 0.00 |
May | 1846.87 | 148.95 | 1024.39 | 407.93 | 616.45 | 0.00 | 0.00 |
June | 1913.26 | 70.57 | 1011.08 | 388.35 | 622.73 | 0.00 | 0.00 |
July | 2031.41 | 101.53 | 1038.90 | 374.65 | 664.25 | 0.00 | 0.00 |
August | 1814.91 | 64.58 | 949.98 | 317.65 | 632.33 | 0.00 | 0.00 |
September | 1766.63 | 112.38 | 915.85 | 331.08 | 584.76 | 0.00 | 0.00 |
October | 1518.30 | 170.51 | 843.00 | 363.05 | 479.95 | 0.00 | 0.00 |
November | 1115.76 | 295.32 | 684.20 | 272.82 | 411.39 | 0.00 | 0.00 |
December | 794.32 | 483.81 | 552.69 | 195.13 | 357.56 | 0.00 | 0.00 |
Annual Sum or Average | 1525.86 | 263.37 | 885.61 | 359.99 | 525.62 | 0.00 | 0.00 |
Minimum of Months | 794.32 | 64.58 | 552.69 | 195.13 | 357.56 | 0.00 | 0.00 |
Maximum of Months | 2031.41 | 564.20 | 1082.81 | 483.15 | 664.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3152.41 | 935.52 | 2072.22 | 1346.28 | 725.95 | 0.00 | 0.00 |
February | 3001.14 | 791.93 | 1874.63 | 1084.70 | 789.93 | 0.00 | 0.00 |
March | 2327.51 | 660.90 | 1439.29 | 608.52 | 830.77 | 0.00 | 0.00 |
April | 1734.39 | 451.04 | 978.69 | 171.62 | 807.07 | 0.00 | 0.00 |
May | 1515.60 | 224.40 | 784.26 | 16.97 | 767.30 | 0.00 | 0.00 |
June | 1555.58 | 106.89 | 747.73 | 1.41 | 746.32 | 0.00 | 0.00 |
July | 1743.44 | 149.45 | 800.61 | 7.42 | 793.19 | 0.00 | 0.00 |
August | 1893.47 | 104.96 | 908.67 | 76.68 | 831.99 | 0.00 | 0.00 |
September | 2395.10 | 184.09 | 1163.22 | 285.05 | 878.17 | 0.00 | 0.00 |
October | 2943.34 | 308.03 | 1599.66 | 750.51 | 849.15 | 0.00 | 0.00 |
November | 3024.65 | 516.09 | 1820.06 | 1015.79 | 804.26 | 0.00 | 0.00 |
December | 3099.47 | 830.02 | 1997.04 | 1259.62 | 737.42 | 0.00 | 0.00 |
Annual Sum or Average | 2362.34 | 437.07 | 1346.40 | 549.68 | 796.71 | 0.00 | 0.00 |
Minimum of Months | 1515.60 | 104.96 | 747.73 | 1.41 | 725.95 | 0.00 | 0.00 |
Maximum of Months | 3152.41 | 935.52 | 2072.22 | 1346.28 | 878.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 905.21 | 611.04 | 635.79 | 274.10 | 361.69 | 0.00 | 0.00 |
February | 1233.11 | 535.03 | 795.04 | 359.80 | 435.24 | 0.00 | 0.00 |
March | 1522.01 | 468.14 | 990.07 | 452.12 | 537.95 | 0.00 | 0.00 |
April | 1816.97 | 336.33 | 1089.78 | 504.60 | 585.17 | 0.00 | 0.00 |
May | 1810.15 | 182.26 | 993.47 | 382.44 | 611.03 | 0.00 | 0.00 |
June | 1624.76 | 85.97 | 841.78 | 236.13 | 605.65 | 0.00 | 0.00 |
July | 1863.31 | 119.67 | 940.76 | 291.04 | 649.72 | 0.00 | 0.00 |
August | 1784.85 | 90.35 | 938.62 | 305.90 | 632.73 | 0.00 | 0.00 |
September | 1567.85 | 123.67 | 800.69 | 236.10 | 564.60 | 0.00 | 0.00 |
October | 1446.53 | 202.46 | 796.54 | 310.52 | 486.03 | 0.00 | 0.00 |
November | 1092.99 | 342.26 | 657.06 | 241.02 | 416.05 | 0.00 | 0.00 |
December | 981.04 | 540.76 | 658.24 | 294.29 | 363.95 | 0.00 | 0.00 |
Annual Sum or Average | 1472.08 | 302.14 | 845.20 | 323.92 | 521.28 | 0.00 | 0.00 |
Minimum of Months | 905.21 | 85.97 | 635.79 | 236.10 | 361.69 | 0.00 | 0.00 |
Maximum of Months | 1863.31 | 611.04 | 1089.78 | 504.60 | 649.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117031E+10 | 0.280009E+10 | 0.118090E+10 | 0.00 | 0.118090E+10 | 0.00 | 0.00 |
February | 0.160571E+10 | 0.210358E+10 | 0.126251E+10 | 0.00 | 0.126251E+10 | 0.00 | 0.00 |
March | 0.216048E+10 | 0.188892E+10 | 0.166695E+10 | 0.00 | 0.166695E+10 | 0.00 | 0.00 |
April | 0.291953E+10 | 0.111641E+10 | 0.180765E+10 | 8120033.60 | 0.179953E+10 | 0.00 | 0.00 |
May | 0.417393E+10 | 0.596959E+09 | 0.213304E+10 | 95414846.25 | 0.203763E+10 | 0.00 | 0.00 |
June | 0.464484E+10 | 0.242454E+09 | 0.220504E+10 | 0.158768E+09 | 0.204628E+10 | 0.00 | 0.00 |
July | 0.505695E+10 | 0.358274E+09 | 0.230581E+10 | 0.112988E+09 | 0.219282E+10 | 0.00 | 0.00 |
August | 0.424079E+10 | 0.241820E+09 | 0.204068E+10 | 18768388.03 | 0.202191E+10 | 0.00 | 0.00 |
September | 0.380863E+10 | 0.419199E+09 | 0.175193E+10 | 138592.33 | 0.175179E+10 | 0.00 | 0.00 |
October | 0.290632E+10 | 0.694139E+09 | 0.151661E+10 | 0.00 | 0.151661E+10 | 0.00 | 0.00 |
November | 0.196725E+10 | 0.137256E+10 | 0.127616E+10 | 0.00 | 0.127616E+10 | 0.00 | 0.00 |
December | 0.130905E+10 | 0.240400E+10 | 0.116805E+10 | 0.00 | 0.116805E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.359638E+11 | 0.142384E+11 | 0.203153E+11 | 0.394198E+09 | 0.199211E+11 | 0.00 | 0.00 |
Minimum of Months | 0.117031E+10 | 0.241820E+09 | 0.116805E+10 | 0.00 | 0.116805E+10 | 0.00 | 0.00 |
Maximum of Months | 0.505695E+10 | 0.280009E+10 | 0.230581E+10 | 0.158768E+09 | 0.219282E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.261920E+10 | 0.170180E+10 | 0.189563E+10 | 0.908125E+09 | 0.987507E+09 | 0.00 | 0.00 |
February | 0.296560E+10 | 0.126667E+10 | 0.197701E+10 | 0.915160E+09 | 0.106185E+10 | 0.00 | 0.00 |
March | 0.405212E+10 | 0.109335E+10 | 0.267239E+10 | 0.126339E+10 | 0.140900E+10 | 0.00 | 0.00 |
April | 0.474862E+10 | 0.665676E+09 | 0.280667E+10 | 0.125232E+10 | 0.155434E+10 | 0.00 | 0.00 |
May | 0.505312E+10 | 0.358250E+09 | 0.274373E+10 | 0.109262E+10 | 0.165111E+10 | 0.00 | 0.00 |
June | 0.508879E+10 | 0.128957E+09 | 0.262074E+10 | 0.100661E+10 | 0.161413E+10 | 0.00 | 0.00 |
July | 0.556477E+10 | 0.189979E+09 | 0.278260E+10 | 0.100346E+10 | 0.177914E+10 | 0.00 | 0.00 |
August | 0.497694E+10 | 95652429.48 | 0.254445E+10 | 0.850809E+09 | 0.169364E+10 | 0.00 | 0.00 |
September | 0.468119E+10 | 0.261538E+09 | 0.237388E+10 | 0.858168E+09 | 0.151571E+10 | 0.00 | 0.00 |
October | 0.414346E+10 | 0.405248E+09 | 0.225790E+10 | 0.972388E+09 | 0.128551E+10 | 0.00 | 0.00 |
November | 0.292360E+10 | 0.787623E+09 | 0.177346E+10 | 0.707149E+09 | 0.106632E+10 | 0.00 | 0.00 |
December | 0.210886E+10 | 0.140514E+10 | 0.148033E+10 | 0.522627E+09 | 0.957699E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.489263E+11 | 0.835989E+10 | 0.279288E+11 | 0.113528E+11 | 0.165760E+11 | 0.00 | 0.00 |
Minimum of Months | 0.210886E+10 | 95652429.48 | 0.148033E+10 | 0.522627E+09 | 0.957699E+09 | 0.00 | 0.00 |
Maximum of Months | 0.556477E+10 | 0.170180E+10 | 0.280667E+10 | 0.126339E+10 | 0.177914E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.849272E+10 | 0.268784E+10 | 0.555008E+10 | 0.360575E+10 | 0.194433E+10 | 0.00 | 0.00 |
February | 0.731878E+10 | 0.206116E+10 | 0.453497E+10 | 0.262403E+10 | 0.191094E+10 | 0.00 | 0.00 |
March | 0.631508E+10 | 0.186279E+10 | 0.385489E+10 | 0.162981E+10 | 0.222508E+10 | 0.00 | 0.00 |
April | 0.455483E+10 | 0.117345E+10 | 0.253671E+10 | 0.444836E+09 | 0.209187E+10 | 0.00 | 0.00 |
May | 0.412378E+10 | 0.591573E+09 | 0.210053E+10 | 45443817.48 | 0.205508E+10 | 0.00 | 0.00 |
June | 0.409179E+10 | 0.247263E+09 | 0.193807E+10 | 3657412.11 | 0.193441E+10 | 0.00 | 0.00 |
July | 0.472083E+10 | 0.360974E+09 | 0.214432E+10 | 19875683.44 | 0.212444E+10 | 0.00 | 0.00 |
August | 0.510130E+10 | 0.252498E+09 | 0.243373E+10 | 0.205369E+09 | 0.222836E+10 | 0.00 | 0.00 |
September | 0.631362E+10 | 0.454947E+09 | 0.301498E+10 | 0.738822E+09 | 0.227616E+10 | 0.00 | 0.00 |
October | 0.799458E+10 | 0.791133E+09 | 0.428440E+10 | 0.201010E+10 | 0.227430E+10 | 0.00 | 0.00 |
November | 0.791848E+10 | 0.139411E+10 | 0.471745E+10 | 0.263285E+10 | 0.208460E+10 | 0.00 | 0.00 |
December | 0.835956E+10 | 0.236981E+10 | 0.534872E+10 | 0.337366E+10 | 0.197506E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.753054E+11 | 0.142475E+11 | 0.424588E+11 | 0.173342E+11 | 0.251246E+11 | 0.00 | 0.00 |
Minimum of Months | 0.409179E+10 | 0.247263E+09 | 0.193807E+10 | 3657412.11 | 0.191094E+10 | 0.00 | 0.00 |
Maximum of Months | 0.849272E+10 | 0.268784E+10 | 0.555008E+10 | 0.360575E+10 | 0.227616E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.232668E+10 | 0.199199E+10 | 0.170291E+10 | 0.734149E+09 | 0.968761E+09 | 0.00 | 0.00 |
February | 0.289321E+10 | 0.160633E+10 | 0.192337E+10 | 0.870434E+09 | 0.105293E+10 | 0.00 | 0.00 |
March | 0.401044E+10 | 0.151392E+10 | 0.265181E+10 | 0.121096E+10 | 0.144085E+10 | 0.00 | 0.00 |
April | 0.464630E+10 | 0.101457E+10 | 0.282471E+10 | 0.130794E+10 | 0.151678E+10 | 0.00 | 0.00 |
May | 0.487078E+10 | 0.522967E+09 | 0.266093E+10 | 0.102433E+10 | 0.163660E+10 | 0.00 | 0.00 |
June | 0.418704E+10 | 0.258332E+09 | 0.218189E+10 | 0.612041E+09 | 0.156985E+10 | 0.00 | 0.00 |
July | 0.494131E+10 | 0.378962E+09 | 0.251975E+10 | 0.779531E+09 | 0.174021E+10 | 0.00 | 0.00 |
August | 0.466647E+10 | 0.366002E+09 | 0.251402E+10 | 0.819314E+09 | 0.169470E+10 | 0.00 | 0.00 |
September | 0.406692E+10 | 0.356903E+09 | 0.207541E+10 | 0.611973E+09 | 0.146344E+10 | 0.00 | 0.00 |
October | 0.384295E+10 | 0.638239E+09 | 0.213347E+10 | 0.831693E+09 | 0.130178E+10 | 0.00 | 0.00 |
November | 0.274159E+10 | 0.114512E+10 | 0.170312E+10 | 0.624714E+09 | 0.107841E+10 | 0.00 | 0.00 |
December | 0.248561E+10 | 0.190532E+10 | 0.176304E+10 | 0.788242E+09 | 0.974797E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.456793E+11 | 0.116987E+11 | 0.266544E+11 | 0.102153E+11 | 0.164391E+11 | 0.00 | 0.00 |
Minimum of Months | 0.232668E+10 | 0.258332E+09 | 0.170291E+10 | 0.611973E+09 | 0.968761E+09 | 0.00 | 0.00 |
Maximum of Months | 0.494131E+10 | 0.199199E+10 | 0.282471E+10 | 0.130794E+10 | 0.174021E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124178E+10 | 0.255642E+10 | 0.118092E+10 | 0.00 | 0.118092E+10 | 0.00 | 0.00 |
February | 0.167345E+10 | 0.190147E+10 | 0.126253E+10 | 0.00 | 0.126253E+10 | 0.00 | 0.00 |
March | 0.220380E+10 | 0.175670E+10 | 0.166698E+10 | 0.00 | 0.166698E+10 | 0.00 | 0.00 |
April | 0.295345E+10 | 0.109247E+10 | 0.180767E+10 | 8120275.76 | 0.179955E+10 | 0.00 | 0.00 |
May | 0.417419E+10 | 0.595281E+09 | 0.213308E+10 | 95417691.79 | 0.203766E+10 | 0.00 | 0.00 |
June | 0.464534E+10 | 0.265512E+09 | 0.220509E+10 | 0.158773E+09 | 0.204631E+10 | 0.00 | 0.00 |
July | 0.508518E+10 | 0.381731E+09 | 0.230585E+10 | 0.112991E+09 | 0.219286E+10 | 0.00 | 0.00 |
August | 0.429910E+10 | 0.254990E+09 | 0.204071E+10 | 18768947.75 | 0.202194E+10 | 0.00 | 0.00 |
September | 0.382616E+10 | 0.418011E+09 | 0.175196E+10 | 138596.46 | 0.175182E+10 | 0.00 | 0.00 |
October | 0.293617E+10 | 0.676425E+09 | 0.151664E+10 | 0.00 | 0.151664E+10 | 0.00 | 0.00 |
November | 0.201447E+10 | 0.126493E+10 | 0.127619E+10 | 0.00 | 0.127619E+10 | 0.00 | 0.00 |
December | 0.138615E+10 | 0.217463E+10 | 0.116808E+10 | 0.00 | 0.116808E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.364392E+11 | 0.133386E+11 | 0.203157E+11 | 0.394210E+09 | 0.199215E+11 | 0.00 | 0.00 |
Minimum of Months | 0.124178E+10 | 0.254990E+09 | 0.116808E+10 | 0.00 | 0.116808E+10 | 0.00 | 0.00 |
Maximum of Months | 0.508518E+10 | 0.255642E+10 | 0.230585E+10 | 0.158773E+09 | 0.219286E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.263175E+10 | 0.160261E+10 | 0.189562E+10 | 0.908121E+09 | 0.987503E+09 | 0.00 | 0.00 |
February | 0.296173E+10 | 0.119829E+10 | 0.197700E+10 | 0.915156E+09 | 0.106184E+10 | 0.00 | 0.00 |
March | 0.400258E+10 | 0.109590E+10 | 0.267238E+10 | 0.126339E+10 | 0.140899E+10 | 0.00 | 0.00 |
April | 0.468258E+10 | 0.735114E+09 | 0.280665E+10 | 0.125232E+10 | 0.155434E+10 | 0.00 | 0.00 |
May | 0.500404E+10 | 0.382682E+09 | 0.274371E+10 | 0.109261E+10 | 0.165110E+10 | 0.00 | 0.00 |
June | 0.502220E+10 | 0.172975E+09 | 0.262073E+10 | 0.100661E+10 | 0.161413E+10 | 0.00 | 0.00 |
July | 0.551041E+10 | 0.256013E+09 | 0.278259E+10 | 0.100346E+10 | 0.177913E+10 | 0.00 | 0.00 |
August | 0.491791E+10 | 0.163594E+09 | 0.254444E+10 | 0.850805E+09 | 0.169363E+10 | 0.00 | 0.00 |
September | 0.463887E+10 | 0.282896E+09 | 0.237387E+10 | 0.858164E+09 | 0.151571E+10 | 0.00 | 0.00 |
October | 0.410676E+10 | 0.448761E+09 | 0.225789E+10 | 0.972384E+09 | 0.128550E+10 | 0.00 | 0.00 |
November | 0.290278E+10 | 0.792572E+09 | 0.177346E+10 | 0.707146E+09 | 0.106631E+10 | 0.00 | 0.00 |
December | 0.211512E+10 | 0.136476E+10 | 0.148032E+10 | 0.522625E+09 | 0.957695E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.484967E+11 | 0.849616E+10 | 0.279287E+11 | 0.113528E+11 | 0.165759E+11 | 0.00 | 0.00 |
Minimum of Months | 0.211512E+10 | 0.163594E+09 | 0.148032E+10 | 0.522625E+09 | 0.957695E+09 | 0.00 | 0.00 |
Maximum of Months | 0.551041E+10 | 0.160261E+10 | 0.280665E+10 | 0.126339E+10 | 0.177913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.841318E+10 | 0.264761E+10 | 0.555024E+10 | 0.360587E+10 | 0.194437E+10 | 0.00 | 0.00 |
February | 0.725805E+10 | 0.200216E+10 | 0.453510E+10 | 0.262412E+10 | 0.191099E+10 | 0.00 | 0.00 |
March | 0.626297E+10 | 0.182265E+10 | 0.385499E+10 | 0.162986E+10 | 0.222513E+10 | 0.00 | 0.00 |
April | 0.454724E+10 | 0.117193E+10 | 0.253677E+10 | 0.444851E+09 | 0.209192E+10 | 0.00 | 0.00 |
May | 0.412653E+10 | 0.583324E+09 | 0.210057E+10 | 45445305.95 | 0.205512E+10 | 0.00 | 0.00 |
June | 0.411059E+10 | 0.263851E+09 | 0.193811E+10 | 3657531.91 | 0.193445E+10 | 0.00 | 0.00 |
July | 0.475774E+10 | 0.378391E+09 | 0.214436E+10 | 19876334.45 | 0.212448E+10 | 0.00 | 0.00 |
August | 0.514292E+10 | 0.268628E+09 | 0.243378E+10 | 0.205376E+09 | 0.222840E+10 | 0.00 | 0.00 |
September | 0.628745E+10 | 0.464984E+09 | 0.301506E+10 | 0.738847E+09 | 0.227621E+10 | 0.00 | 0.00 |
October | 0.793808E+10 | 0.814693E+09 | 0.428452E+10 | 0.201016E+10 | 0.227435E+10 | 0.00 | 0.00 |
November | 0.785733E+10 | 0.137968E+10 | 0.471759E+10 | 0.263293E+10 | 0.208465E+10 | 0.00 | 0.00 |
December | 0.829760E+10 | 0.232868E+10 | 0.534888E+10 | 0.337377E+10 | 0.197511E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.749997E+11 | 0.141266E+11 | 0.424600E+11 | 0.173348E+11 | 0.251252E+11 | 0.00 | 0.00 |
Minimum of Months | 0.411059E+10 | 0.263851E+09 | 0.193811E+10 | 3657531.91 | 0.191099E+10 | 0.00 | 0.00 |
Maximum of Months | 0.841318E+10 | 0.264761E+10 | 0.555024E+10 | 0.360587E+10 | 0.227621E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.240131E+10 | 0.174792E+10 | 0.170290E+10 | 0.734146E+09 | 0.968757E+09 | 0.00 | 0.00 |
February | 0.297880E+10 | 0.135938E+10 | 0.192336E+10 | 0.870431E+09 | 0.105293E+10 | 0.00 | 0.00 |
March | 0.409213E+10 | 0.129269E+10 | 0.265180E+10 | 0.121095E+10 | 0.144085E+10 | 0.00 | 0.00 |
April | 0.474344E+10 | 0.873904E+09 | 0.282470E+10 | 0.130793E+10 | 0.151677E+10 | 0.00 | 0.00 |
May | 0.489173E+10 | 0.478611E+09 | 0.266092E+10 | 0.102433E+10 | 0.163659E+10 | 0.00 | 0.00 |
June | 0.425876E+10 | 0.217785E+09 | 0.218188E+10 | 0.612039E+09 | 0.156985E+10 | 0.00 | 0.00 |
July | 0.504527E+10 | 0.313140E+09 | 0.251974E+10 | 0.779528E+09 | 0.174021E+10 | 0.00 | 0.00 |
August | 0.482399E+10 | 0.235459E+09 | 0.251400E+10 | 0.819310E+09 | 0.169469E+10 | 0.00 | 0.00 |
September | 0.410776E+10 | 0.318272E+09 | 0.207540E+10 | 0.611970E+09 | 0.146343E+10 | 0.00 | 0.00 |
October | 0.390373E+10 | 0.543527E+09 | 0.213346E+10 | 0.831689E+09 | 0.130177E+10 | 0.00 | 0.00 |
November | 0.283860E+10 | 0.923901E+09 | 0.170311E+10 | 0.624712E+09 | 0.107840E+10 | 0.00 | 0.00 |
December | 0.261648E+10 | 0.153041E+10 | 0.176303E+10 | 0.788238E+09 | 0.974793E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.467020E+11 | 0.983498E+10 | 0.266543E+11 | 0.102153E+11 | 0.164390E+11 | 0.00 | 0.00 |
Minimum of Months | 0.240131E+10 | 0.217785E+09 | 0.170290E+10 | 0.611970E+09 | 0.968757E+09 | 0.00 | 0.00 |
Maximum of Months | 0.504527E+10 | 0.174792E+10 | 0.282470E+10 | 0.130793E+10 | 0.174021E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.130044E+10 | 0.234091E+10 | 0.118092E+10 | 0.00 | 0.118092E+10 | 0.00 | 0.00 |
February | 0.169920E+10 | 0.177446E+10 | 0.126253E+10 | 0.00 | 0.126253E+10 | 0.00 | 0.00 |
March | 0.220008E+10 | 0.167489E+10 | 0.166698E+10 | 0.00 | 0.166698E+10 | 0.00 | 0.00 |
April | 0.291009E+10 | 0.108492E+10 | 0.180767E+10 | 8120275.76 | 0.179955E+10 | 0.00 | 0.00 |
May | 0.410796E+10 | 0.616418E+09 | 0.213308E+10 | 95417691.79 | 0.203766E+10 | 0.00 | 0.00 |
June | 0.456345E+10 | 0.280294E+09 | 0.220509E+10 | 0.158773E+09 | 0.204631E+10 | 0.00 | 0.00 |
July | 0.499528E+10 | 0.406042E+09 | 0.230585E+10 | 0.112991E+09 | 0.219286E+10 | 0.00 | 0.00 |
August | 0.423153E+10 | 0.268824E+09 | 0.204071E+10 | 18768947.75 | 0.202194E+10 | 0.00 | 0.00 |
September | 0.375107E+10 | 0.427736E+09 | 0.175196E+10 | 138596.46 | 0.175182E+10 | 0.00 | 0.00 |
October | 0.289362E+10 | 0.677500E+09 | 0.151664E+10 | 0.00 | 0.151664E+10 | 0.00 | 0.00 |
November | 0.201398E+10 | 0.119340E+10 | 0.127619E+10 | 0.00 | 0.127619E+10 | 0.00 | 0.00 |
December | 0.142452E+10 | 0.201467E+10 | 0.116808E+10 | 0.00 | 0.116808E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.360912E+11 | 0.127601E+11 | 0.203157E+11 | 0.394210E+09 | 0.199215E+11 | 0.00 | 0.00 |
Minimum of Months | 0.130044E+10 | 0.268824E+09 | 0.116808E+10 | 0.00 | 0.116808E+10 | 0.00 | 0.00 |
Maximum of Months | 0.499528E+10 | 0.234091E+10 | 0.230585E+10 | 0.158773E+09 | 0.219286E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.265974E+10 | 0.151115E+10 | 0.189562E+10 | 0.908121E+09 | 0.987503E+09 | 0.00 | 0.00 |
February | 0.296773E+10 | 0.114440E+10 | 0.197700E+10 | 0.915156E+09 | 0.106184E+10 | 0.00 | 0.00 |
March | 0.398109E+10 | 0.107176E+10 | 0.267238E+10 | 0.126339E+10 | 0.140899E+10 | 0.00 | 0.00 |
April | 0.463788E+10 | 0.742146E+09 | 0.280665E+10 | 0.125232E+10 | 0.155434E+10 | 0.00 | 0.00 |
May | 0.494666E+10 | 0.398937E+09 | 0.274371E+10 | 0.109261E+10 | 0.165110E+10 | 0.00 | 0.00 |
June | 0.495918E+10 | 0.182917E+09 | 0.262073E+10 | 0.100661E+10 | 0.161413E+10 | 0.00 | 0.00 |
July | 0.544093E+10 | 0.271929E+09 | 0.278259E+10 | 0.100346E+10 | 0.177913E+10 | 0.00 | 0.00 |
August | 0.486105E+10 | 0.172984E+09 | 0.254444E+10 | 0.850805E+09 | 0.169363E+10 | 0.00 | 0.00 |
September | 0.457910E+10 | 0.291280E+09 | 0.237387E+10 | 0.858164E+09 | 0.151571E+10 | 0.00 | 0.00 |
October | 0.406661E+10 | 0.456688E+09 | 0.225789E+10 | 0.972384E+09 | 0.128550E+10 | 0.00 | 0.00 |
November | 0.289205E+10 | 0.765473E+09 | 0.177346E+10 | 0.707146E+09 | 0.106631E+10 | 0.00 | 0.00 |
December | 0.212749E+10 | 0.129583E+10 | 0.148032E+10 | 0.522625E+09 | 0.957695E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.481195E+11 | 0.830549E+10 | 0.279287E+11 | 0.113528E+11 | 0.165759E+11 | 0.00 | 0.00 |
Minimum of Months | 0.212749E+10 | 0.172984E+09 | 0.148032E+10 | 0.522625E+09 | 0.957695E+09 | 0.00 | 0.00 |
Maximum of Months | 0.544093E+10 | 0.151115E+10 | 0.280665E+10 | 0.126339E+10 | 0.177913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.844340E+10 | 0.250571E+10 | 0.555024E+10 | 0.360587E+10 | 0.194437E+10 | 0.00 | 0.00 |
February | 0.726036E+10 | 0.191584E+10 | 0.453510E+10 | 0.262412E+10 | 0.191099E+10 | 0.00 | 0.00 |
March | 0.623401E+10 | 0.177016E+10 | 0.385499E+10 | 0.162986E+10 | 0.222513E+10 | 0.00 | 0.00 |
April | 0.449553E+10 | 0.116910E+10 | 0.253677E+10 | 0.444851E+09 | 0.209192E+10 | 0.00 | 0.00 |
May | 0.405939E+10 | 0.601044E+09 | 0.210057E+10 | 45445305.95 | 0.205512E+10 | 0.00 | 0.00 |
June | 0.403206E+10 | 0.277064E+09 | 0.193811E+10 | 3657531.91 | 0.193445E+10 | 0.00 | 0.00 |
July | 0.466963E+10 | 0.400291E+09 | 0.214436E+10 | 19876334.45 | 0.212448E+10 | 0.00 | 0.00 |
August | 0.507146E+10 | 0.281132E+09 | 0.243378E+10 | 0.205376E+09 | 0.222840E+10 | 0.00 | 0.00 |
September | 0.620810E+10 | 0.477160E+09 | 0.301506E+10 | 0.738847E+09 | 0.227621E+10 | 0.00 | 0.00 |
October | 0.788345E+10 | 0.825038E+09 | 0.428452E+10 | 0.201016E+10 | 0.227435E+10 | 0.00 | 0.00 |
November | 0.783988E+10 | 0.133770E+10 | 0.471759E+10 | 0.263293E+10 | 0.208465E+10 | 0.00 | 0.00 |
December | 0.830162E+10 | 0.222312E+10 | 0.534888E+10 | 0.337377E+10 | 0.197511E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.744989E+11 | 0.137834E+11 | 0.424600E+11 | 0.173348E+11 | 0.251252E+11 | 0.00 | 0.00 |
Minimum of Months | 0.403206E+10 | 0.277064E+09 | 0.193811E+10 | 3657531.91 | 0.191099E+10 | 0.00 | 0.00 |
Maximum of Months | 0.844340E+10 | 0.250571E+10 | 0.555024E+10 | 0.360587E+10 | 0.227621E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.242451E+10 | 0.163660E+10 | 0.170290E+10 | 0.734146E+09 | 0.968757E+09 | 0.00 | 0.00 |
February | 0.298313E+10 | 0.129434E+10 | 0.192336E+10 | 0.870431E+09 | 0.105293E+10 | 0.00 | 0.00 |
March | 0.407656E+10 | 0.125386E+10 | 0.265180E+10 | 0.121095E+10 | 0.144085E+10 | 0.00 | 0.00 |
April | 0.470959E+10 | 0.871755E+09 | 0.282470E+10 | 0.130793E+10 | 0.151677E+10 | 0.00 | 0.00 |
May | 0.484830E+10 | 0.488175E+09 | 0.266092E+10 | 0.102433E+10 | 0.163659E+10 | 0.00 | 0.00 |
June | 0.421138E+10 | 0.222831E+09 | 0.218188E+10 | 0.612039E+09 | 0.156985E+10 | 0.00 | 0.00 |
July | 0.499070E+10 | 0.320536E+09 | 0.251974E+10 | 0.779528E+09 | 0.174021E+10 | 0.00 | 0.00 |
August | 0.478054E+10 | 0.241985E+09 | 0.251400E+10 | 0.819310E+09 | 0.169469E+10 | 0.00 | 0.00 |
September | 0.406387E+10 | 0.320545E+09 | 0.207540E+10 | 0.611970E+09 | 0.146343E+10 | 0.00 | 0.00 |
October | 0.387437E+10 | 0.542266E+09 | 0.213346E+10 | 0.831689E+09 | 0.130177E+10 | 0.00 | 0.00 |
November | 0.283304E+10 | 0.887142E+09 | 0.170311E+10 | 0.624712E+09 | 0.107840E+10 | 0.00 | 0.00 |
December | 0.262761E+10 | 0.144836E+10 | 0.176303E+10 | 0.788238E+09 | 0.974793E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.464236E+11 | 0.952840E+10 | 0.266543E+11 | 0.102153E+11 | 0.164390E+11 | 0.00 | 0.00 |
Minimum of Months | 0.242451E+10 | 0.222831E+09 | 0.170290E+10 | 0.611970E+09 | 0.968757E+09 | 0.00 | 0.00 |
Maximum of Months | 0.499070E+10 | 0.163660E+10 | 0.282470E+10 | 0.130793E+10 | 0.174021E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.282873E+11 | -0.272686E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101864E+10 | 58.96 | 0.00 | 0.00 |
February | 0.254633E+11 | -0.245421E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -921237051.8 | 58.97 | 0.00 | 0.00 |
March | 0.289968E+11 | -0.279733E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102347E+10 | 58.97 | 0.00 | 0.00 |
April | 0.251810E+11 | -0.241934E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987623205.4 | 58.98 | 0.00 | 0.00 |
May | 0.255681E+11 | -0.245468E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102133E+10 | 58.97 | 0.00 | 0.00 |
June | 0.243393E+11 | -0.233495E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989806994.4 | 58.97 | 0.00 | 0.00 |
July | 0.228287E+11 | -0.218111E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101756E+10 | 58.97 | 0.00 | 0.00 |
August | 0.251886E+11 | -0.241670E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102162E+10 | 58.96 | 0.00 | 0.00 |
September | 0.237500E+11 | -0.227636E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986486603.8 | 58.97 | 0.00 | 0.00 |
October | 0.257142E+11 | -0.246967E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101749E+10 | 58.96 | 0.00 | 0.00 |
November | 0.264342E+11 | -0.254493E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -984952684.5 | 58.97 | 0.00 | 0.00 |
December | 0.272646E+11 | -0.262469E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101777E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.309016E+12 | -0.297008E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120080E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.228287E+11 | -0.279733E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102347E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.289968E+11 | -0.218111E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -921237051.8 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.63 | 0.61 | 01-JAN-07:40 | 6206.83 | 35.38 | 274.83 | 288.17 | 1080.06 | 24.81 | 181.33 | 266.17 |
February | 304.33 | 0.63 | 0.61 | 01-FEB-07:49 | 2161.07 | 24.35 | 135.00 | 273.67 | 828.87 | 19.93 | 98.17 | 239.83 |
March | 362.67 | 0.64 | 0.61 | 01-MAR-07:30 | 1279.63 | 17.27 | 5.67 | 314.67 | 688.95 | 19.87 | 92.67 | 276.33 |
April | 357.50 | 0.64 | 0.61 | 01-APR-07:10 | 991.11 | 16.52 | 0.00 | 315.33 | 556.18 | 19.36 | 20.83 | 265.17 |
May | 389.00 | 0.64 | 0.61 | 01-MAY-06:49 | 852.19 | 15.98 | 0.00 | 332.67 | 472.62 | 18.85 | 2.83 | 262.33 |
June | 388.17 | 0.65 | 0.61 | 01-JUN-06:00 | 806.45 | 15.29 | 0.00 | 310.17 | 442.41 | 18.17 | 2.33 | 243.50 |
July | 403.83 | 0.64 | 0.61 | 01-JUL-06:40 | 902.05 | 16.22 | 0.00 | 340.83 | 496.56 | 19.12 | 4.83 | 278.00 |
August | 348.33 | 0.64 | 0.61 | 01-AUG-06:49 | 1074.91 | 16.79 | 0.00 | 333.00 | 578.53 | 19.65 | 47.17 | 282.00 |
September | 349.67 | 0.64 | 0.61 | 01-SEP-06:00 | 1296.76 | 17.11 | 0.00 | 307.67 | 676.55 | 20.00 | 114.33 | 261.67 |
October | 323.50 | 0.64 | 0.61 | 02-OCT-07:10 | 1724.29 | 19.01 | 30.50 | 307.50 | 828.10 | 20.62 | 154.50 | 271.50 |
November | 314.83 | 0.63 | 0.61 | 01-NOV-07:10 | 3426.49 | 29.87 | 237.50 | 286.00 | 925.07 | 22.51 | 190.17 | 257.67 |
December | 282.67 | 0.63 | 0.61 | 01-DEC-08:39 | 5834.93 | 34.38 | 264.50 | 270.50 | 1282.07 | 26.18 | 202.33 | 255.17 |
Annual Sum or Average | 4111.50 | 0.64 | 2038.20 | 20.80 | 948.00 | 3680.17 | 711.82 | 20.53 | 1111.50 | 3159.33 | ||
Minimum of Months | 282.67 | 0.63 | 0.61 | 806.45 | 15.29 | 0.00 | 270.50 | 442.41 | 18.17 | 2.33 | 239.83 | |
Maximum of Months | 403.83 | 0.65 | 0.61 | 6206.83 | 35.38 | 274.83 | 340.83 | 1282.07 | 26.18 | 202.33 | 282.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.65 | 0.61 | 01-JAN-07:49 | 1796.58 | 17.95 | 81.50 | 248.00 | 972.09 | 18.98 | 72.33 | 195.50 |
February | 304.33 | 0.65 | 0.61 | 01-FEB-07:49 | 1855.12 | 16.90 | 74.50 | 243.33 | 697.66 | 16.37 | 40.50 | 195.50 |
March | 362.67 | 0.64 | 0.61 | 01-MAR-07:30 | 1778.96 | 14.86 | 52.50 | 305.50 | 899.50 | 13.60 | 1.83 | 254.67 |
April | 357.50 | 0.64 | 0.61 | 01-APR-06:00 | 2070.53 | 12.04 | 0.00 | 306.83 | 1126.01 | 13.37 | 0.00 | 258.83 |
May | 389.00 | 0.64 | 0.61 | 01-MAY-06:10 | 1974.02 | 12.21 | 0.00 | 338.83 | 786.10 | 13.31 | 0.00 | 277.67 |
June | 388.17 | 0.64 | 0.61 | 01-JUN-05:00 | 1920.52 | 11.90 | 0.00 | 325.00 | 767.26 | 12.88 | 0.00 | 264.00 |
July | 403.83 | 0.64 | 0.61 | 01-JUL-06:10 | 1881.57 | 12.67 | 0.00 | 347.67 | 792.68 | 13.67 | 0.00 | 290.33 |
August | 348.33 | 0.64 | 0.61 | 01-AUG-06:30 | 1797.56 | 12.79 | 0.00 | 332.00 | 963.27 | 13.90 | 0.00 | 278.83 |
September | 349.67 | 0.64 | 0.61 | 01-SEP-06:40 | 1779.78 | 13.27 | 8.50 | 297.17 | 923.21 | 14.21 | 5.50 | 247.83 |
October | 323.50 | 0.64 | 0.61 | 02-OCT-06:00 | 1758.23 | 17.44 | 80.83 | 287.83 | 932.00 | 16.90 | 52.50 | 245.00 |
November | 314.83 | 0.64 | 0.61 | 01-NOV-06:00 | 1412.75 | 17.56 | 77.83 | 255.67 | 696.16 | 17.04 | 48.33 | 203.83 |
December | 282.67 | 0.65 | 0.61 | 01-DEC-08:39 | 1510.52 | 17.76 | 75.00 | 236.50 | 611.78 | 16.62 | 34.00 | 176.50 |
Annual Sum or Average | 4111.50 | 0.64 | 1806.60 | 14.54 | 450.67 | 3524.33 | 850.24 | 14.88 | 255.00 | 2888.50 | ||
Minimum of Months | 282.67 | 0.64 | 0.61 | 1412.75 | 11.90 | 0.00 | 236.50 | 611.78 | 12.88 | 0.00 | 176.50 | |
Maximum of Months | 403.83 | 0.65 | 0.61 | 2070.53 | 17.95 | 81.50 | 347.67 | 1126.01 | 18.98 | 72.33 | 290.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.67 | 0.61 | 01-JAN-09:09 | 436.64 | 0.00 | 0.00 | 214.67 | 280.48 | 0.00 | 0.00 | 71.33 |
February | 304.33 | 0.65 | 0.61 | 01-FEB-08:09 | 501.24 | 0.00 | 0.00 | 229.33 | 311.57 | 0.00 | 0.00 | 114.00 |
March | 362.67 | 0.64 | 0.61 | 01-MAR-08:00 | 602.13 | 0.00 | 0.00 | 291.67 | 365.54 | 0.00 | 0.00 | 200.83 |
April | 357.50 | 0.64 | 0.61 | 01-APR-07:10 | 720.83 | 0.00 | 0.00 | 321.33 | 430.16 | 0.00 | 0.00 | 254.67 |
May | 389.00 | 0.63 | 0.61 | 01-MAY-06:30 | 862.16 | 0.00 | 0.00 | 356.17 | 481.55 | 0.00 | 0.00 | 302.50 |
June | 388.17 | 0.64 | 0.61 | 01-JUN-06:19 | 918.77 | 0.00 | 0.00 | 339.33 | 491.99 | 0.00 | 0.00 | 279.83 |
July | 403.83 | 0.63 | 0.61 | 01-JUL-06:19 | 967.46 | 0.00 | 0.00 | 363.50 | 528.47 | 0.00 | 0.00 | 314.83 |
August | 348.33 | 0.63 | 0.61 | 01-AUG-06:40 | 869.22 | 0.00 | 0.00 | 342.67 | 490.26 | 0.00 | 0.00 | 287.17 |
September | 349.67 | 0.64 | 0.61 | 01-SEP-06:00 | 729.81 | 0.00 | 0.00 | 304.67 | 417.05 | 0.00 | 0.00 | 226.17 |
October | 323.50 | 0.65 | 0.61 | 02-OCT-07:19 | 573.22 | 0.00 | 0.00 | 275.33 | 352.74 | 0.00 | 0.00 | 175.33 |
November | 314.83 | 0.65 | 0.61 | 01-NOV-07:40 | 507.20 | 0.00 | 0.00 | 232.33 | 305.34 | 0.00 | 0.00 | 107.33 |
December | 282.67 | 0.65 | 0.61 | 01-DEC-08:39 | 478.74 | 0.00 | 0.00 | 216.50 | 297.14 | 0.00 | 0.00 | 78.67 |
Annual Sum or Average | 4111.50 | 0.64 | 699.27 | 0.00 | 0.00 | 3487.50 | 404.77 | 0.00 | 0.00 | 2412.67 | ||
Minimum of Months | 282.67 | 0.63 | 0.61 | 436.64 | 0.00 | 0.00 | 214.67 | 280.48 | 0.00 | 0.00 | 71.33 | |
Maximum of Months | 403.83 | 0.67 | 0.61 | 967.46 | 0.00 | 0.00 | 363.50 | 528.47 | 0.00 | 0.00 | 314.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.65 | 0.61 | 01-JAN-09:20 | 1529.62 | 16.96 | 71.50 | 247.67 | 860.55 | 18.25 | 63.83 | 183.17 |
February | 304.33 | 0.64 | 0.61 | 01-FEB-08:39 | 1310.79 | 15.04 | 46.00 | 247.50 | 716.35 | 16.24 | 42.67 | 195.33 |
March | 362.67 | 0.64 | 0.61 | 01-MAR-09:09 | 1744.46 | 14.94 | 54.00 | 300.33 | 868.31 | 13.63 | 1.83 | 250.00 |
April | 357.50 | 0.64 | 0.61 | 01-APR-07:30 | 1893.93 | 12.09 | 0.00 | 320.00 | 1024.04 | 13.50 | 0.00 | 273.83 |
May | 389.00 | 0.64 | 0.61 | 01-MAY-07:10 | 1712.62 | 12.20 | 0.00 | 334.83 | 890.53 | 13.37 | 1.33 | 282.17 |
June | 388.17 | 0.65 | 0.61 | 01-JUN-07:10 | 1428.37 | 11.85 | 0.00 | 317.83 | 632.18 | 14.62 | 34.50 | 260.50 |
July | 403.83 | 0.64 | 0.61 | 01-JUL-06:00 | 1618.11 | 12.66 | 0.00 | 342.33 | 713.42 | 13.66 | 0.00 | 291.50 |
August | 348.33 | 0.64 | 0.61 | 01-AUG-07:19 | 1753.63 | 12.84 | 0.00 | 328.17 | 901.11 | 13.96 | 0.00 | 280.00 |
September | 349.67 | 0.64 | 0.61 | 01-SEP-07:10 | 1456.11 | 13.18 | 7.00 | 301.33 | 734.47 | 14.13 | 4.00 | 248.83 |
October | 323.50 | 0.65 | 0.61 | 02-OCT-07:40 | 1732.65 | 17.30 | 83.17 | 281.17 | 927.07 | 16.84 | 54.17 | 239.67 |
November | 314.83 | 0.64 | 0.61 | 01-NOV-07:49 | 1380.92 | 17.52 | 80.50 | 257.17 | 692.39 | 16.99 | 52.33 | 202.17 |
December | 282.67 | 0.64 | 0.61 | 01-DEC-08:39 | 1589.57 | 18.96 | 81.50 | 250.33 | 803.66 | 18.15 | 51.67 | 194.33 |
Annual Sum or Average | 4111.50 | 0.64 | 1601.93 | 14.40 | 423.67 | 3528.67 | 812.76 | 15.10 | 306.33 | 2901.50 | ||
Minimum of Months | 282.67 | 0.64 | 0.61 | 1310.79 | 11.85 | 0.00 | 247.50 | 632.18 | 13.37 | 0.00 | 183.17 | |
Maximum of Months | 403.83 | 0.65 | 0.61 | 1893.93 | 18.96 | 83.17 | 342.33 | 1024.04 | 18.25 | 63.83 | 291.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.64 | 0.61 | 01-JAN-07:40 | 6188.62 | 34.95 | 274.17 | 287.17 | 1116.85 | 20.74 | 81.17 | 267.50 |
February | 304.33 | 0.63 | 0.61 | 01-FEB-07:49 | 2141.99 | 20.56 | 132.83 | 272.67 | 860.12 | 15.24 | 0.00 | 241.17 |
March | 362.67 | 0.64 | 0.61 | 01-MAR-07:30 | 1261.41 | 11.47 | 5.67 | 313.17 | 712.96 | 15.94 | 0.00 | 278.33 |
April | 357.50 | 0.64 | 0.61 | 01-APR-07:10 | 973.87 | 11.14 | 0.00 | 314.33 | 573.42 | 15.86 | 0.00 | 268.83 |
May | 389.00 | 0.64 | 0.61 | 01-MAY-06:49 | 835.45 | 10.46 | 0.00 | 330.50 | 486.26 | 15.17 | 0.00 | 266.00 |
June | 388.17 | 0.65 | 0.61 | 01-JUN-06:00 | 790.27 | 9.69 | 0.00 | 308.00 | 455.12 | 14.37 | 0.00 | 247.33 |
July | 403.83 | 0.64 | 0.61 | 01-JUL-06:40 | 883.53 | 10.62 | 0.00 | 339.83 | 510.33 | 15.34 | 0.00 | 280.67 |
August | 348.33 | 0.64 | 0.61 | 01-AUG-06:49 | 1052.35 | 11.27 | 0.00 | 331.83 | 594.57 | 15.93 | 0.00 | 284.17 |
September | 349.67 | 0.64 | 0.61 | 01-SEP-06:00 | 1269.21 | 11.21 | 0.00 | 307.00 | 695.76 | 15.88 | 0.00 | 264.50 |
October | 323.50 | 0.64 | 0.61 | 02-OCT-07:10 | 1708.44 | 13.23 | 28.50 | 309.67 | 856.19 | 16.79 | 9.17 | 275.00 |
November | 314.83 | 0.63 | 0.61 | 01-NOV-07:10 | 3377.78 | 27.00 | 224.83 | 282.17 | 966.60 | 19.99 | 71.33 | 264.00 |
December | 282.67 | 0.63 | 0.61 | 01-DEC-08:39 | 5795.56 | 33.59 | 262.67 | 269.67 | 1316.97 | 22.26 | 92.50 | 255.83 |
Annual Sum or Average | 4111.50 | 0.64 | 2015.54 | 16.22 | 928.67 | 3666.00 | 734.94 | 16.74 | 254.17 | 3193.33 | ||
Minimum of Months | 282.67 | 0.63 | 0.61 | 790.27 | 9.69 | 0.00 | 269.67 | 455.12 | 14.37 | 0.00 | 241.17 | |
Maximum of Months | 403.83 | 0.65 | 0.61 | 6188.62 | 34.95 | 274.17 | 339.83 | 1316.97 | 22.26 | 92.50 | 284.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.65 | 0.61 | 01-JAN-07:49 | 1795.57 | 15.93 | 81.50 | 247.67 | 992.20 | 17.27 | 72.50 | 199.83 |
February | 304.33 | 0.65 | 0.61 | 01-FEB-07:49 | 1854.61 | 14.65 | 74.50 | 242.83 | 718.55 | 14.32 | 40.67 | 199.67 |
March | 362.67 | 0.64 | 0.61 | 01-MAR-07:30 | 1788.39 | 12.12 | 52.50 | 304.67 | 924.42 | 11.11 | 1.83 | 260.50 |
April | 357.50 | 0.64 | 0.61 | 01-APR-06:00 | 2054.22 | 8.67 | 0.00 | 306.17 | 1150.27 | 11.02 | 0.00 | 265.00 |
May | 389.00 | 0.64 | 0.61 | 01-MAY-06:10 | 1858.84 | 8.81 | 0.00 | 337.50 | 809.61 | 11.07 | 0.00 | 283.50 |
June | 388.17 | 0.64 | 0.61 | 01-JUN-05:00 | 1911.29 | 8.52 | 0.00 | 324.50 | 789.69 | 10.66 | 0.00 | 268.50 |
July | 403.83 | 0.64 | 0.61 | 01-JUL-06:10 | 1801.64 | 9.29 | 0.00 | 346.67 | 815.46 | 11.47 | 0.00 | 293.83 |
August | 348.33 | 0.64 | 0.61 | 01-AUG-06:30 | 1775.61 | 9.47 | 0.00 | 331.00 | 986.05 | 11.64 | 0.00 | 282.33 |
September | 349.67 | 0.64 | 0.61 | 01-SEP-06:40 | 1773.52 | 10.00 | 8.50 | 296.67 | 940.69 | 11.83 | 5.50 | 252.50 |
October | 323.50 | 0.65 | 0.61 | 02-OCT-06:00 | 1761.83 | 15.26 | 80.83 | 286.17 | 912.50 | 14.94 | 52.67 | 246.17 |
November | 314.83 | 0.64 | 0.61 | 01-NOV-06:00 | 1406.20 | 15.32 | 78.33 | 255.00 | 714.66 | 14.95 | 48.83 | 207.17 |
December | 282.67 | 0.65 | 0.61 | 01-DEC-08:39 | 1504.37 | 15.66 | 75.17 | 236.00 | 628.64 | 14.44 | 34.33 | 181.00 |
Annual Sum or Average | 4111.50 | 0.64 | 1783.25 | 11.67 | 451.33 | 3514.83 | 868.54 | 12.69 | 256.33 | 2940.00 | ||
Minimum of Months | 282.67 | 0.64 | 0.61 | 1406.20 | 8.52 | 0.00 | 236.00 | 628.64 | 10.66 | 0.00 | 181.00 | |
Maximum of Months | 403.83 | 0.65 | 0.61 | 2054.22 | 15.93 | 81.50 | 346.67 | 1150.27 | 17.27 | 72.50 | 293.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.67 | 0.61 | 01-JAN-09:20 | 428.98 | 0.00 | 0.00 | 210.50 | 288.44 | 0.00 | 0.00 | 85.17 |
February | 304.33 | 0.66 | 0.61 | 01-FEB-08:20 | 492.80 | 0.00 | 0.00 | 227.00 | 320.74 | 0.00 | 0.00 | 125.83 |
March | 362.67 | 0.64 | 0.61 | 01-MAR-08:00 | 592.23 | 0.00 | 0.00 | 290.00 | 376.47 | 0.00 | 0.00 | 211.17 |
April | 357.50 | 0.64 | 0.61 | 01-APR-07:10 | 709.22 | 0.00 | 0.00 | 320.50 | 443.12 | 0.00 | 0.00 | 261.17 |
May | 389.00 | 0.63 | 0.61 | 01-MAY-06:30 | 846.90 | 0.00 | 0.00 | 354.83 | 495.97 | 0.00 | 0.00 | 307.33 |
June | 388.17 | 0.64 | 0.61 | 01-JUN-06:30 | 903.04 | 0.00 | 0.00 | 338.17 | 516.64 | 0.00 | 0.00 | 293.67 |
July | 403.83 | 0.63 | 0.61 | 01-JUL-06:19 | 978.35 | 0.00 | 0.00 | 363.83 | 543.07 | 0.00 | 0.00 | 317.50 |
August | 348.33 | 0.64 | 0.61 | 01-AUG-06:49 | 852.72 | 0.00 | 0.00 | 341.50 | 503.85 | 0.00 | 0.00 | 291.00 |
September | 349.67 | 0.64 | 0.61 | 01-SEP-06:00 | 715.96 | 0.00 | 0.00 | 303.17 | 428.72 | 0.00 | 0.00 | 229.67 |
October | 323.50 | 0.65 | 0.61 | 02-OCT-07:19 | 562.70 | 0.00 | 0.00 | 273.67 | 362.52 | 0.00 | 0.00 | 180.67 |
November | 314.83 | 0.65 | 0.61 | 01-NOV-07:40 | 497.35 | 0.00 | 0.00 | 229.17 | 313.73 | 0.00 | 0.00 | 117.17 |
December | 282.67 | 0.65 | 0.61 | 01-DEC-08:39 | 469.32 | 0.00 | 0.00 | 213.33 | 305.19 | 0.00 | 0.00 | 92.67 |
Annual Sum or Average | 4111.50 | 0.64 | 689.56 | 0.00 | 0.00 | 3465.67 | 417.33 | 0.00 | 0.00 | 2513.00 | ||
Minimum of Months | 282.67 | 0.63 | 0.61 | 428.98 | 0.00 | 0.00 | 210.50 | 288.44 | 0.00 | 0.00 | 85.17 | |
Maximum of Months | 403.83 | 0.67 | 0.61 | 978.35 | 0.00 | 0.00 | 363.83 | 543.07 | 0.00 | 0.00 | 317.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.65 | 0.61 | 01-JAN-09:20 | 1527.60 | 14.85 | 71.50 | 247.00 | 878.88 | 16.49 | 64.17 | 190.33 |
February | 304.33 | 0.65 | 0.61 | 01-FEB-08:39 | 1309.57 | 12.43 | 46.00 | 246.50 | 736.30 | 14.26 | 42.67 | 201.83 |
March | 362.67 | 0.64 | 0.61 | 01-MAR-08:00 | 1754.21 | 12.17 | 54.00 | 299.50 | 892.83 | 11.14 | 1.83 | 257.17 |
April | 357.50 | 0.64 | 0.61 | 01-APR-07:30 | 1880.07 | 8.69 | 0.00 | 319.33 | 992.54 | 11.10 | 0.00 | 275.00 |
May | 389.00 | 0.64 | 0.61 | 01-MAY-07:10 | 1698.80 | 8.80 | 0.00 | 333.83 | 913.87 | 11.13 | 1.33 | 286.67 |
June | 388.17 | 0.65 | 0.61 | 01-JUN-07:10 | 1420.43 | 8.61 | 0.00 | 317.17 | 651.44 | 12.84 | 35.17 | 264.83 |
July | 403.83 | 0.64 | 0.61 | 01-JUL-06:00 | 1604.62 | 9.33 | 0.00 | 341.33 | 734.59 | 11.48 | 0.00 | 296.67 |
August | 348.33 | 0.64 | 0.61 | 01-AUG-07:19 | 1732.09 | 9.51 | 0.00 | 327.00 | 923.78 | 11.68 | 0.00 | 283.00 |
September | 349.67 | 0.64 | 0.61 | 01-SEP-07:10 | 1449.60 | 9.96 | 7.00 | 300.33 | 754.09 | 11.78 | 4.00 | 253.67 |
October | 323.50 | 0.65 | 0.61 | 02-OCT-07:40 | 1733.91 | 15.13 | 83.17 | 280.67 | 946.92 | 14.89 | 54.33 | 243.17 |
November | 314.83 | 0.64 | 0.61 | 01-NOV-07:49 | 1373.38 | 15.29 | 80.67 | 257.00 | 709.86 | 14.93 | 52.33 | 205.67 |
December | 282.67 | 0.64 | 0.61 | 01-DEC-08:39 | 1584.85 | 16.87 | 81.50 | 249.67 | 822.86 | 16.04 | 51.67 | 199.83 |
Annual Sum or Average | 4111.50 | 0.64 | 1594.79 | 11.52 | 423.83 | 3519.33 | 828.86 | 12.96 | 307.50 | 2957.83 | ||
Minimum of Months | 282.67 | 0.64 | 0.61 | 1309.57 | 8.61 | 0.00 | 246.50 | 651.44 | 11.10 | 0.00 | 190.33 | |
Maximum of Months | 403.83 | 0.65 | 0.61 | 1880.07 | 16.87 | 83.17 | 341.33 | 992.54 | 16.49 | 64.17 | 296.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.64 | 0.61 | 01-JAN-07:40 | 6188.52 | 34.94 | 274.17 | 287.17 | 1117.91 | 20.73 | 81.17 | 267.67 |
February | 304.33 | 0.63 | 0.61 | 01-FEB-07:49 | 2142.54 | 20.53 | 132.83 | 272.67 | 861.08 | 15.22 | 0.00 | 241.17 |
March | 362.67 | 0.64 | 0.61 | 01-MAR-07:30 | 1262.01 | 11.43 | 5.67 | 313.17 | 713.77 | 15.93 | 0.00 | 278.50 |
April | 357.50 | 0.64 | 0.61 | 01-APR-07:10 | 974.29 | 11.10 | 0.00 | 314.33 | 574.05 | 15.85 | 0.00 | 269.00 |
May | 389.00 | 0.64 | 0.61 | 01-MAY-06:49 | 835.83 | 10.42 | 0.00 | 330.50 | 486.80 | 15.15 | 0.00 | 266.50 |
June | 388.17 | 0.65 | 0.61 | 01-JUN-06:00 | 790.68 | 9.65 | 0.00 | 308.00 | 455.64 | 14.35 | 0.00 | 247.67 |
July | 403.83 | 0.64 | 0.61 | 01-JUL-06:40 | 883.93 | 10.58 | 0.00 | 339.83 | 510.91 | 15.33 | 0.00 | 281.17 |
August | 348.33 | 0.64 | 0.61 | 01-AUG-06:49 | 1052.91 | 11.23 | 0.00 | 331.83 | 595.29 | 15.91 | 0.00 | 284.67 |
September | 349.67 | 0.64 | 0.61 | 01-SEP-06:00 | 1270.02 | 11.17 | 0.00 | 307.00 | 696.69 | 15.87 | 0.00 | 264.50 |
October | 323.50 | 0.64 | 0.61 | 02-OCT-07:10 | 1709.14 | 13.19 | 28.50 | 309.67 | 857.24 | 16.77 | 9.17 | 275.17 |
November | 314.83 | 0.63 | 0.61 | 01-NOV-07:10 | 3378.18 | 26.98 | 224.83 | 282.17 | 967.79 | 19.98 | 71.33 | 264.00 |
December | 282.67 | 0.63 | 0.61 | 01-DEC-08:39 | 5795.39 | 33.58 | 262.67 | 269.67 | 1318.21 | 22.25 | 92.50 | 255.83 |
Annual Sum or Average | 4111.50 | 0.64 | 2015.97 | 16.18 | 928.67 | 3666.00 | 735.77 | 16.73 | 254.17 | 3195.83 | ||
Minimum of Months | 282.67 | 0.63 | 0.61 | 790.68 | 9.65 | 0.00 | 269.67 | 455.64 | 14.35 | 0.00 | 241.17 | |
Maximum of Months | 403.83 | 0.65 | 0.61 | 6188.52 | 34.94 | 274.17 | 339.83 | 1318.21 | 22.25 | 92.50 | 284.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.65 | 0.61 | 01-JAN-07:49 | 1795.30 | 15.92 | 81.50 | 247.50 | 992.68 | 17.26 | 72.50 | 199.83 |
February | 304.33 | 0.65 | 0.61 | 01-FEB-07:49 | 1854.42 | 14.64 | 74.50 | 242.67 | 719.12 | 14.32 | 40.67 | 199.83 |
March | 362.67 | 0.64 | 0.61 | 01-MAR-07:30 | 1788.14 | 12.10 | 52.50 | 304.50 | 925.04 | 11.10 | 1.83 | 260.67 |
April | 357.50 | 0.64 | 0.61 | 01-APR-06:00 | 2054.22 | 8.66 | 0.00 | 306.00 | 1150.99 | 11.01 | 0.00 | 265.00 |
May | 389.00 | 0.64 | 0.61 | 01-MAY-06:10 | 1858.96 | 8.79 | 0.00 | 337.50 | 810.34 | 11.06 | 0.00 | 283.67 |
June | 388.17 | 0.64 | 0.61 | 01-JUN-05:00 | 1911.56 | 8.51 | 0.00 | 324.50 | 790.44 | 10.65 | 0.00 | 269.00 |
July | 403.83 | 0.64 | 0.61 | 01-JUL-06:10 | 1801.86 | 9.28 | 0.00 | 346.67 | 816.29 | 11.47 | 0.00 | 294.00 |
August | 348.33 | 0.64 | 0.61 | 01-AUG-06:30 | 1775.83 | 9.45 | 0.00 | 331.00 | 986.89 | 11.64 | 0.00 | 282.67 |
September | 349.67 | 0.64 | 0.61 | 01-SEP-06:40 | 1773.72 | 9.99 | 8.50 | 296.83 | 941.56 | 11.82 | 5.50 | 252.83 |
October | 323.50 | 0.65 | 0.61 | 02-OCT-06:00 | 1761.49 | 15.25 | 80.83 | 286.17 | 913.15 | 14.93 | 52.67 | 246.33 |
November | 314.83 | 0.64 | 0.61 | 01-NOV-06:00 | 1406.07 | 15.31 | 78.33 | 254.67 | 715.27 | 14.95 | 48.83 | 207.17 |
December | 282.67 | 0.65 | 0.61 | 01-DEC-08:39 | 1504.21 | 15.65 | 75.17 | 236.00 | 629.19 | 14.43 | 34.33 | 181.17 |
Annual Sum or Average | 4111.50 | 0.64 | 1783.24 | 11.66 | 451.33 | 3514.00 | 869.23 | 12.68 | 256.33 | 2942.17 | ||
Minimum of Months | 282.67 | 0.64 | 0.61 | 1406.07 | 8.51 | 0.00 | 236.00 | 629.19 | 10.65 | 0.00 | 181.17 | |
Maximum of Months | 403.83 | 0.65 | 0.61 | 2054.22 | 15.92 | 81.50 | 346.67 | 1150.99 | 17.26 | 72.50 | 294.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.67 | 0.61 | 01-JAN-09:20 | 428.84 | 0.00 | 0.00 | 210.50 | 288.64 | 0.00 | 0.00 | 85.17 |
February | 304.33 | 0.66 | 0.61 | 01-FEB-08:20 | 492.74 | 0.00 | 0.00 | 227.17 | 321.00 | 0.00 | 0.00 | 126.00 |
March | 362.67 | 0.64 | 0.61 | 01-MAR-08:00 | 592.22 | 0.00 | 0.00 | 290.00 | 376.80 | 0.00 | 0.00 | 211.17 |
April | 357.50 | 0.64 | 0.61 | 01-APR-07:10 | 709.27 | 0.00 | 0.00 | 320.50 | 443.52 | 0.00 | 0.00 | 261.50 |
May | 389.00 | 0.63 | 0.61 | 01-MAY-06:30 | 847.15 | 0.00 | 0.00 | 354.83 | 496.50 | 0.00 | 0.00 | 307.33 |
June | 388.17 | 0.64 | 0.61 | 01-JUN-06:30 | 903.44 | 0.00 | 0.00 | 338.17 | 517.24 | 0.00 | 0.00 | 293.67 |
July | 403.83 | 0.63 | 0.61 | 01-JUL-06:19 | 978.67 | 0.00 | 0.00 | 363.83 | 543.69 | 0.00 | 0.00 | 317.67 |
August | 348.33 | 0.64 | 0.61 | 01-AUG-06:49 | 852.93 | 0.00 | 0.00 | 341.50 | 504.40 | 0.00 | 0.00 | 291.33 |
September | 349.67 | 0.64 | 0.61 | 01-SEP-06:00 | 716.10 | 0.00 | 0.00 | 303.17 | 429.17 | 0.00 | 0.00 | 230.17 |
October | 323.50 | 0.65 | 0.61 | 02-OCT-07:19 | 562.61 | 0.00 | 0.00 | 273.50 | 362.82 | 0.00 | 0.00 | 180.83 |
November | 314.83 | 0.65 | 0.61 | 01-NOV-07:40 | 497.32 | 0.00 | 0.00 | 229.33 | 314.02 | 0.00 | 0.00 | 117.83 |
December | 282.67 | 0.65 | 0.61 | 01-DEC-08:39 | 469.22 | 0.00 | 0.00 | 213.50 | 305.43 | 0.00 | 0.00 | 93.17 |
Annual Sum or Average | 4111.50 | 0.64 | 689.66 | 0.00 | 0.00 | 3466.00 | 417.74 | 0.00 | 0.00 | 2515.83 | ||
Minimum of Months | 282.67 | 0.63 | 0.61 | 428.84 | 0.00 | 0.00 | 210.50 | 288.64 | 0.00 | 0.00 | 85.17 | |
Maximum of Months | 403.83 | 0.67 | 0.61 | 978.67 | 0.00 | 0.00 | 363.83 | 543.69 | 0.00 | 0.00 | 317.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.65 | 0.61 | 01-JAN-09:20 | 1527.36 | 14.84 | 71.50 | 247.00 | 879.35 | 16.49 | 64.17 | 190.33 |
February | 304.33 | 0.65 | 0.61 | 01-FEB-08:39 | 1309.37 | 12.42 | 46.00 | 246.50 | 736.86 | 14.25 | 42.67 | 202.00 |
March | 362.67 | 0.64 | 0.61 | 01-MAR-08:00 | 1753.98 | 12.16 | 54.00 | 299.50 | 893.48 | 11.13 | 1.83 | 257.17 |
April | 357.50 | 0.64 | 0.61 | 01-APR-07:30 | 1880.05 | 8.68 | 0.00 | 319.33 | 993.19 | 11.09 | 0.00 | 275.17 |
May | 389.00 | 0.64 | 0.61 | 01-MAY-07:10 | 1698.97 | 8.79 | 0.00 | 333.83 | 914.61 | 11.12 | 1.33 | 287.00 |
June | 388.17 | 0.65 | 0.61 | 01-JUN-07:10 | 1420.81 | 8.60 | 0.00 | 317.17 | 652.18 | 12.84 | 35.17 | 264.83 |
July | 403.83 | 0.64 | 0.61 | 01-JUL-06:00 | 1604.91 | 9.32 | 0.00 | 341.17 | 735.40 | 11.48 | 0.00 | 296.83 |
August | 348.33 | 0.64 | 0.61 | 01-AUG-07:19 | 1732.37 | 9.50 | 0.00 | 327.17 | 924.65 | 11.67 | 0.00 | 283.33 |
September | 349.67 | 0.64 | 0.61 | 01-SEP-07:10 | 1449.90 | 9.94 | 7.00 | 300.33 | 754.89 | 11.77 | 4.00 | 253.67 |
October | 323.50 | 0.65 | 0.61 | 02-OCT-07:40 | 1733.81 | 15.12 | 83.17 | 280.67 | 947.61 | 14.88 | 54.33 | 243.50 |
November | 314.83 | 0.64 | 0.61 | 01-NOV-07:49 | 1373.27 | 15.28 | 80.67 | 257.00 | 710.48 | 14.92 | 52.33 | 206.33 |
December | 282.67 | 0.64 | 0.61 | 01-DEC-08:39 | 1584.62 | 16.86 | 81.50 | 249.67 | 823.41 | 16.04 | 51.67 | 199.83 |
Annual Sum or Average | 4111.50 | 0.64 | 1594.84 | 11.51 | 423.83 | 3519.33 | 829.55 | 12.95 | 307.50 | 2960.00 | ||
Minimum of Months | 282.67 | 0.64 | 0.61 | 1309.37 | 8.60 | 0.00 | 246.50 | 652.18 | 11.09 | 0.00 | 190.33 | |
Maximum of Months | 403.83 | 0.65 | 0.61 | 1880.05 | 16.86 | 83.17 | 341.17 | 993.19 | 16.49 | 64.17 | 296.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 18633502.86 | 8256.15 | 25-JAN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19564592.00 | 15391.68 | 04-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17584212.59 | 15169.77 | 16-MAR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 339.46 | 2.26 | 03-APR-00:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9696354.11 | 7458.25 | 27-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33371783.06 | 13733.86 | 15-DEC-04:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98850784.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33371783.06 | 15391.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.287600E+09 | 113073.43 | 25-JAN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.222664E+09 | 118556.97 | 04-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.259007E+09 | 116565.00 | 16-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110107E+09 | 96247.66 | 27-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386937E+09 | 114987.91 | 15-DEC-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.386937E+09 | 118556.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 7129360.86 | 3389.89 | 25-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174612E+09 | 132971.63 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27825155.36 | 10593.28 | 16-MAR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 909747.54 | 1377.24 | 15-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174612E+09 | 132971.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 16634956.74 | 10071.28 | 25-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100034E+09 | 87742.49 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24963805.53 | 13557.17 | 16-MAR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 57121969.96 | 10188.77 | 15-DEC-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100034E+09 | 87742.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10595164.94 | 8383.17 | 04-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10595164.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10595164.94 | 8383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5114126.00 | 1956.92 | 25-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157776E+09 | 46036.65 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54958.47 | 183.19 | 16-MAR-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8935258.34 | 2313.04 | 15-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171880E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157776E+09 | 46036.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3514040.43 | 4585.21 | 09-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5111403.15 | 9257.01 | 25-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6359098.55 | 4566.52 | 21-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2091562.77 | 9424.97 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3162840.62 | 5038.01 | 27-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20238945.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6359098.55 | 9424.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 97484647.52 | 15696.04 | 25-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122568E+09 | 15647.26 | 04-FEB-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 49735844.87 | 15689.65 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20400564.48 | 2970.36 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112035E+09 | 15686.86 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122568E+09 | 15696.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 53372007.96 | 8459.48 | 25-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50918913.52 | 12660.99 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23638194.87 | 8576.64 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8076879.92 | 1516.80 | 13-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 86514706.54 | 11925.73 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86514706.54 | 12660.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8048327.64 | 1174.92 | 25-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46143968.63 | 15694.65 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15209852.85 | 5323.56 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1593385.32 | 882.99 | 13-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22408190.15 | 2604.33 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93403724.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46143968.63 | 15694.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 62637836.31 | 3975.11 | 25-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80828668.33 | 12628.73 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25669482.97 | 3306.18 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12809784.12 | 2097.92 | 13-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 75420823.44 | 7157.92 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80828668.33 | 12628.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.958198E+11 | 0.775596E+11 | 256797.53 | 30-JAN-04:02 | 148210.23 | 0.51 |
February | 0.00 | 0.00 | 0.107495E+12 | 0.867029E+11 | 250342.57 | 11-FEB-06:02 | 142468.02 | 0.55 |
March | 0.00 | 0.00 | 0.144697E+12 | 0.112100E+12 | 242966.03 | 10-MAR-06:02 | 140271.04 | 0.65 |
April | 0.00 | 0.00 | 0.168492E+12 | 0.131043E+12 | 228963.26 | 11-APR-05:02 | 146732.92 | 0.83 |
May | 0.00 | 0.00 | 0.184192E+12 | 0.132186E+12 | 279321.64 | 27-MAY-03:02 | 139981.96 | 0.73 |
June | 0.00 | 0.00 | 0.209250E+12 | 0.145276E+12 | 265289.15 | 12-JUN-04:33 | 152856.93 | 0.80 |
July | 0.00 | 0.00 | 0.225873E+12 | 0.157099E+12 | 263174.63 | 03-JUL-05:02 | 150509.90 | 0.84 |
August | 0.00 | 0.00 | 0.246060E+12 | 0.171106E+12 | 255080.24 | 24-AUG-04:03 | 139152.14 | 0.88 |
September | 0.00 | 0.00 | 0.197144E+12 | 0.133199E+12 | 281829.25 | 21-SEP-03:02 | 155897.82 | 0.75 |
October | 0.00 | 0.00 | 0.194390E+12 | 0.136151E+12 | 263348.65 | 31-OCT-03:02 | 146643.25 | 0.75 |
November | 0.00 | 0.00 | 0.165306E+12 | 0.119506E+12 | 260897.25 | 04-NOV-05:03 | 142557.18 | 0.71 |
December | 0.00 | 0.00 | 0.132007E+12 | 0.989925E+11 | 248352.77 | 09-DEC-06:03 | 144625.17 | 0.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.207073E+13 | 0.150092E+13 | 0.72 | |||
Minimum of Months | 0.00 | 0.00 | 0.958198E+11 | 0.775596E+11 | 228963.26 | 139152.14 | 0.51 | |
Maximum of Months | 0.00 | 0.00 | 0.246060E+12 | 0.171106E+12 | 281829.25 | 155897.82 | 0.88 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.778612E+12 | 0.613634E+12 | 2463413.72 | 14-JAN-05:02 | 1239443.59 | 0.47 |
February | 0.00 | 0.00 | 0.841014E+12 | 0.662897E+12 | 2590794.21 | 11-FEB-06:02 | 1333372.45 | 0.50 |
March | 0.00 | 0.00 | 0.105107E+13 | 0.810697E+12 | 2565338.29 | 06-MAR-04:02 | 1220102.03 | 0.52 |
April | 0.00 | 0.00 | 0.120045E+13 | 0.929218E+12 | 2659078.56 | 13-APR-03:02 | 1391850.43 | 0.63 |
May | 0.00 | 0.00 | 0.159385E+13 | 0.113127E+13 | 2769367.52 | 27-MAY-05:02 | 1331537.78 | 0.66 |
June | 0.00 | 0.00 | 0.173728E+13 | 0.118586E+13 | 3001811.29 | 19-JUN-03:02 | 1386788.66 | 0.69 |
July | 0.00 | 0.00 | 0.177501E+13 | 0.120998E+13 | 2895456.36 | 03-JUL-03:02 | 1433801.77 | 0.69 |
August | 0.00 | 0.00 | 0.182867E+13 | 0.123097E+13 | 2857357.77 | 28-AUG-03:02 | 1464028.07 | 0.69 |
September | 0.00 | 0.00 | 0.172073E+13 | 0.113371E+13 | 2859545.72 | 21-SEP-03:02 | 1434398.54 | 0.68 |
October | 0.00 | 0.00 | 0.157220E+13 | 0.108549E+13 | 3045230.76 | 02-OCT-03:02 | 1459365.17 | 0.64 |
November | 0.00 | 0.00 | 0.124683E+13 | 0.883893E+12 | 2755354.34 | 04-NOV-03:02 | 1324939.04 | 0.58 |
December | 0.00 | 0.00 | 0.852869E+12 | 0.644747E+12 | 2528781.93 | 26-DEC-04:02 | 1210734.89 | 0.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.161986E+14 | 0.115224E+14 | 0.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.778612E+12 | 0.613634E+12 | 2463413.72 | 1210734.89 | 0.47 | |
Maximum of Months | 0.00 | 0.00 | 0.182867E+13 | 0.123097E+13 | 3045230.76 | 1464028.07 | 0.69 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.728920E+11 | 0.570088E+11 | 253662.09 | 14-JAN-06:03 | 130824.59 | 0.45 |
February | 0.00 | 0.00 | 0.846920E+11 | 0.669116E+11 | 265627.59 | 11-FEB-06:02 | 133316.61 | 0.48 |
March | 0.00 | 0.00 | 0.110267E+12 | 0.850037E+11 | 268510.13 | 06-MAR-04:02 | 126437.22 | 0.51 |
April | 0.00 | 0.00 | 0.131479E+12 | 0.103025E+12 | 272436.06 | 13-APR-03:02 | 139719.22 | 0.63 |
May | 0.00 | 0.00 | 0.178238E+12 | 0.129608E+12 | 288792.33 | 27-MAY-05:02 | 138762.43 | 0.67 |
June | 0.00 | 0.00 | 0.196247E+12 | 0.137405E+12 | 295029.13 | 20-JUN-03:02 | 150682.18 | 0.71 |
July | 0.00 | 0.00 | 0.202715E+12 | 0.142629E+12 | 300276.90 | 03-JUL-03:02 | 152090.27 | 0.71 |
August | 0.00 | 0.00 | 0.202837E+12 | 0.140600E+12 | 286262.39 | 04-AUG-03:02 | 156426.90 | 0.71 |
September | 0.00 | 0.00 | 0.189559E+12 | 0.129110E+12 | 297510.11 | 20-SEP-03:02 | 151128.65 | 0.69 |
October | 0.00 | 0.00 | 0.165847E+12 | 0.117573E+12 | 316429.91 | 02-OCT-03:02 | 151843.37 | 0.64 |
November | 0.00 | 0.00 | 0.127216E+12 | 0.912341E+11 | 293993.87 | 04-NOV-03:02 | 142452.30 | 0.57 |
December | 0.00 | 0.00 | 0.828684E+11 | 0.622761E+11 | 260281.27 | 26-DEC-04:02 | 122789.86 | 0.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.174486E+13 | 0.126238E+13 | 0.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.728920E+11 | 0.570088E+11 | 253662.09 | 122789.86 | 0.45 | |
Maximum of Months | 0.00 | 0.00 | 0.202837E+12 | 0.142629E+12 | 316429.91 | 156426.90 | 0.71 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.791063E+11 | 0.720882E+11 | 174138.48 | 29-JAN-17:22 | 91937.79 | 0.52 |
February | 0.00 | 0.00 | 0.759060E+11 | 0.684024E+11 | 159604.93 | 11-FEB-05:02 | 84206.64 | 0.51 |
March | 0.00 | 0.00 | 0.877924E+11 | 0.776327E+11 | 173301.76 | 06-MAR-04:02 | 85882.06 | 0.53 |
April | 0.00 | 0.00 | 0.893993E+11 | 0.773070E+11 | 170128.51 | 16-APR-17:00 | 99295.73 | 0.59 |
May | 0.00 | 0.00 | 0.113328E+12 | 0.883840E+11 | 202148.63 | 29-MAY-01:22 | 85164.28 | 0.61 |
June | 0.00 | 0.00 | 0.126883E+12 | 0.903345E+11 | 191141.57 | 11-JUN-23:38 | 91010.12 | 0.62 |
July | 0.00 | 0.00 | 0.131710E+12 | 0.930455E+11 | 195793.13 | 31-JUL-03:02 | 86305.73 | 0.60 |
August | 0.00 | 0.00 | 0.144438E+12 | 0.101996E+12 | 196296.44 | 28-AUG-03:02 | 83816.97 | 0.65 |
September | 0.00 | 0.00 | 0.127147E+12 | 0.910038E+11 | 192677.90 | 10-SEP-20:00 | 90438.30 | 0.63 |
October | 0.00 | 0.00 | 0.122079E+12 | 0.925222E+11 | 203619.56 | 02-OCT-03:02 | 86475.31 | 0.63 |
November | 0.00 | 0.00 | 0.105570E+12 | 0.841022E+11 | 181995.63 | 24-NOV-01:08 | 84378.40 | 0.59 |
December | 0.00 | 0.00 | 0.838129E+11 | 0.745635E+11 | 192687.77 | 25-DEC-23:53 | 84537.16 | 0.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.128717E+13 | 0.101138E+13 | 0.59 | |||
Minimum of Months | 0.00 | 0.00 | 0.759060E+11 | 0.684024E+11 | 159604.93 | 83816.97 | 0.51 | |
Maximum of Months | 0.00 | 0.00 | 0.144438E+12 | 0.101996E+12 | 203619.56 | 99295.73 | 0.65 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.339910E+12 | 0.330372E+12 | 140024.08 | 02-JAN-15:00 | 130297.15 | 0.00 |
February | 0.00 | 0.00 | 0.530005E+12 | 0.520161E+12 | 230648.68 | 02-FEB-15:10 | 219654.07 | 0.00 |
March | 0.00 | 0.00 | 0.834208E+12 | 0.821533E+12 | 396355.71 | 31-MAR-24:00 | 393536.91 | 0.00 |
April | 0.00 | 0.00 | 0.104508E+13 | 0.103206E+13 | 425095.91 | 25-APR-16:00 | 406834.42 | 0.00 |
May | 0.00 | 0.00 | 0.359710E+12 | 0.338146E+12 | 228604.94 | 31-MAY-23:10 | 211739.11 | 0.00 |
June | 0.00 | 0.00 | 0.591583E+12 | 0.564924E+12 | 316478.67 | 30-JUN-23:03 | 303361.71 | 0.00 |
July | 0.00 | 0.00 | 0.857394E+12 | 0.830238E+12 | 401837.92 | 31-JUL-24:00 | 391650.37 | 0.00 |
August | 0.00 | 0.00 | 0.109212E+13 | 0.106652E+13 | 425352.01 | 23-AUG-17:00 | 406864.38 | 0.00 |
September | 0.00 | 0.00 | 0.355933E+12 | 0.330726E+12 | 224635.63 | 30-SEP-23:02 | 212299.21 | 0.00 |
October | 0.00 | 0.00 | 0.608095E+12 | 0.584370E+12 | 312967.34 | 31-OCT-23:10 | 302306.15 | 0.00 |
November | 0.00 | 0.00 | 0.817669E+12 | 0.799734E+12 | 326456.61 | 30-NOV-17:00 | 313270.37 | 0.00 |
December | 0.00 | 0.00 | 0.107898E+13 | 0.106702E+13 | 413385.74 | 08-DEC-17:10 | 401376.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.851068E+13 | 0.828581E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.339910E+12 | 0.330372E+12 | 140024.08 | 130297.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109212E+13 | 0.106702E+13 | 425352.01 | 406864.38 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.585536E+10 | 0.547846E+10 | 2942.85 | 02-JAN-15:00 | 2540.95 | 0.00 |
February | 0.00 | 0.00 | 0.101041E+11 | 0.969481E+10 | 4850.59 | 19-FEB-17:37 | 4554.31 | 0.00 |
March | 0.00 | 0.00 | 0.163997E+11 | 0.158460E+11 | 7825.80 | 31-MAR-23:23 | 7679.53 | 0.00 |
April | 0.00 | 0.00 | 0.210033E+11 | 0.203848E+11 | 8777.99 | 13-APR-16:00 | 8298.06 | 0.00 |
May | 0.00 | 0.00 | 0.699590E+10 | 0.612108E+10 | 4753.61 | 31-MAY-23:10 | 4001.76 | 0.00 |
June | 0.00 | 0.00 | 0.119804E+11 | 0.108378E+11 | 6465.34 | 30-JUN-23:03 | 5870.13 | 0.00 |
July | 0.00 | 0.00 | 0.175007E+11 | 0.162940E+11 | 8434.50 | 31-JUL-23:03 | 7806.79 | 0.00 |
August | 0.00 | 0.00 | 0.226740E+11 | 0.214309E+11 | 8935.38 | 21-AUG-13:00 | 8275.15 | 0.00 |
September | 0.00 | 0.00 | 0.702049E+10 | 0.599015E+10 | 4551.12 | 30-SEP-23:02 | 4005.61 | 0.00 |
October | 0.00 | 0.00 | 0.121546E+11 | 0.111437E+11 | 6286.39 | 31-OCT-23:10 | 5805.75 | 0.00 |
November | 0.00 | 0.00 | 0.162614E+11 | 0.154717E+11 | 6965.77 | 07-NOV-17:00 | 6551.51 | 0.00 |
December | 0.00 | 0.00 | 0.213384E+11 | 0.207775E+11 | 8894.76 | 08-DEC-16:50 | 8390.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169288E+12 | 0.159471E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.585536E+10 | 0.547846E+10 | 2942.85 | 2540.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.226740E+11 | 0.214309E+11 | 8935.38 | 8390.10 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.502432E+11 | 0.465867E+11 | 27832.54 | 02-JAN-15:00 | 23837.83 | 0.00 |
February | 0.00 | 0.00 | 0.924078E+11 | 0.883515E+11 | 45799.64 | 10-FEB-17:00 | 41422.72 | 0.00 |
March | 0.00 | 0.00 | 0.154644E+12 | 0.149116E+12 | 75264.91 | 31-MAR-23:53 | 73878.07 | 0.00 |
April | 0.00 | 0.00 | 0.200259E+12 | 0.194064E+12 | 83624.26 | 13-APR-16:00 | 78809.69 | 0.00 |
May | 0.00 | 0.00 | 0.658665E+11 | 0.572162E+11 | 46351.31 | 31-MAY-23:10 | 38609.26 | 0.00 |
June | 0.00 | 0.00 | 0.114496E+12 | 0.103115E+12 | 62995.70 | 30-JUN-23:03 | 56941.92 | 0.00 |
July | 0.00 | 0.00 | 0.167424E+12 | 0.155376E+12 | 81749.17 | 31-JUL-23:03 | 75407.03 | 0.00 |
August | 0.00 | 0.00 | 0.215484E+12 | 0.203052E+12 | 84680.38 | 23-AUG-16:30 | 78408.48 | 0.00 |
September | 0.00 | 0.00 | 0.659516E+11 | 0.557672E+11 | 44205.65 | 30-SEP-23:02 | 38610.40 | 0.00 |
October | 0.00 | 0.00 | 0.115495E+12 | 0.105434E+12 | 59618.33 | 31-OCT-23:10 | 54710.93 | 0.00 |
November | 0.00 | 0.00 | 0.153625E+12 | 0.145745E+12 | 66348.88 | 07-NOV-17:00 | 62217.51 | 0.00 |
December | 0.00 | 0.00 | 0.200134E+12 | 0.194518E+12 | 84499.89 | 08-DEC-16:50 | 79462.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159603E+13 | 0.149834E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.502432E+11 | 0.465867E+11 | 27832.54 | 23837.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.215484E+12 | 0.203052E+12 | 84680.38 | 79462.01 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.452626E+10 | 0.416850E+10 | 2825.70 | 02-JAN-15:00 | 2423.20 | 0.00 |
February | 0.00 | 0.00 | 0.895183E+10 | 0.854807E+10 | 4712.48 | 19-FEB-17:25 | 4416.86 | 0.00 |
March | 0.00 | 0.00 | 0.153235E+11 | 0.147718E+11 | 7487.88 | 31-MAR-23:10 | 7307.32 | 0.00 |
April | 0.00 | 0.00 | 0.200663E+11 | 0.194477E+11 | 8485.76 | 13-APR-16:00 | 8004.75 | 0.00 |
May | 0.00 | 0.00 | 0.669809E+10 | 0.583057E+10 | 4652.10 | 31-MAY-23:10 | 3881.84 | 0.00 |
June | 0.00 | 0.00 | 0.115703E+11 | 0.104314E+11 | 6319.84 | 30-JUN-23:03 | 5716.04 | 0.00 |
July | 0.00 | 0.00 | 0.169014E+11 | 0.156966E+11 | 8171.62 | 31-JUL-23:03 | 7539.17 | 0.00 |
August | 0.00 | 0.00 | 0.216588E+11 | 0.204164E+11 | 8609.11 | 23-AUG-16:30 | 7982.65 | 0.00 |
September | 0.00 | 0.00 | 0.671007E+10 | 0.568869E+10 | 4465.72 | 30-SEP-23:02 | 3914.02 | 0.00 |
October | 0.00 | 0.00 | 0.115912E+11 | 0.105857E+11 | 5895.51 | 31-OCT-23:10 | 5403.20 | 0.00 |
November | 0.00 | 0.00 | 0.152247E+11 | 0.144381E+11 | 6710.21 | 07-NOV-17:00 | 6297.31 | 0.00 |
December | 0.00 | 0.00 | 0.196770E+11 | 0.191170E+11 | 8531.57 | 08-DEC-16:50 | 8028.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158899E+12 | 0.149141E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.452626E+10 | 0.416850E+10 | 2825.70 | 2423.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216588E+11 | 0.204164E+11 | 8609.11 | 8028.02 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 154.90 | 151867.44 | 25-JAN-06:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 405.46 | 457199.35 | 04-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 165.39 | 221001.68 | 16-MAR-04:05 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 1.76 | 03-APR-00:48 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 67.79 | 151317.01 | 27-NOV-06:08 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 292.85 | 200517.88 | 27-DEC-06:06 |
Annual Sum or Average | 0.00 | 88.75 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 405.46 | 457199.35 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 646292.66 | 3198104.73 | 07-JAN-06:03 | 42.56 | 178722.63 | 22-JAN-21:05 |
February | 717328.59 | 3656393.75 | 11-FEB-06:04 | 8.92 | 48180.43 | 27-FEB-00:25 |
March | 803507.28 | 3167358.38 | 06-MAR-06:03 | 12.44 | 106585.34 | 12-MAR-06:52 |
April | 932497.45 | 2800131.12 | 22-APR-05:03 | 1.98 | 33321.86 | 02-APR-04:22 |
May | 1062567.73 | 3839063.09 | 31-MAY-05:05 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1118693.87 | 3944704.95 | 22-JUN-05:04 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1139243.35 | 3360377.10 | 15-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1154794.63 | 3301681.22 | 15-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1109760.97 | 3551908.35 | 16-SEP-05:04 | 5.98 | 113275.00 | 02-SEP-21:52 |
October | 1042683.59 | 3962748.77 | 02-OCT-05:05 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 916220.50 | 3269114.81 | 29-NOV-06:04 | 5.09 | 73474.56 | 11-NOV-09:42 |
December | 711550.97 | 3148512.22 | 09-DEC-06:03 | 4.90 | 49496.38 | 12-DEC-00:42 |
Annual Sum or Average | 947343.10 | 6.84 | ||||
Minimum of Months | 646292.66 | 2800131.12 | 0.00 | 0.00 | ||
Maximum of Months | 1154794.63 | 3962748.77 | 42.56 | 178722.63 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 480358.98 | 4601358.74 | 30-JAN-04:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 556809.73 | 4768588.27 | 11-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 623498.03 | 4635477.55 | 10-MAR-06:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 715088.16 | 4320085.41 | 13-APR-03:02 | 0.00 | 0.00 | 01-APR-00:05 |
May | 873024.01 | 4846886.01 | 27-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 956543.52 | 4767689.81 | 22-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 942648.30 | 4720124.47 | 03-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 977947.48 | 4768741.01 | 28-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 945457.28 | 4895403.14 | 21-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 860333.57 | 4948473.09 | 02-OCT-03:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 741544.34 | 4623443.37 | 24-NOV-06:02 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 535641.81 | 4620449.29 | 23-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 768347.09 | 0.00 | ||||
Minimum of Months | 480358.98 | 4320085.41 | 0.00 | 0.00 | ||
Maximum of Months | 977947.48 | 4948473.09 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 372322.09 | 876990.87 | 02-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 648038.75 | 1106227.39 | 11-FEB-14:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 894688.37 | 1355663.94 | 13-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1248541.94 | 1707993.26 | 17-APR-15:00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 726474.60 | 1164679.13 | 22-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1025320.15 | 1262740.80 | 11-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1277790.51 | 1697688.49 | 29-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1484319.40 | 1814505.01 | 23-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 791260.09 | 1063581.83 | 20-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 947676.53 | 1268938.83 | 02-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 1010381.37 | 1386687.58 | 17-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 1036235.18 | 1525450.29 | 10-DEC-14:58 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 957081.91 | 0.00 | ||||
Minimum of Months | 372322.09 | 876990.87 | 0.00 | 0.00 | ||
Maximum of Months | 1484319.40 | 1814505.01 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 11606.11 | 37905.80 | 17-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11570.65 | 37798.55 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11862.85 | 37083.45 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:05 | 10759.90 | 35527.46 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10592.08 | 33962.65 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 10434.03 | 32419.51 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 9572.34 | 31470.04 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 10449.42 | 32176.17 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 10209.41 | 33524.91 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 10642.36 | 35296.53 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 11240.28 | 36806.94 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 11221.98 | 37692.67 | 28-DEC-13:00 |
Annual Sum or Average | 0.00 | 10842.87 | ||||
Minimum of Months | 0.00 | 0.00 | 9572.34 | 31470.04 | ||
Maximum of Months | 0.00 | 0.00 | 11862.85 | 37905.80 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 573577.09 | 5478669.66 | 02-JAN-14:10 | 1241.11 | 153210.89 | 25-JAN-06:30 |
February | 660119.28 | 5520370.29 | 11-FEB-06:04 | 1219.05 | 170522.49 | 04-FEB-06:30 |
March | 878218.13 | 5201897.16 | 13-MAR-13:10 | 871.46 | 159797.41 | 16-MAR-06:10 |
April | 1088634.16 | 5528320.32 | 14-APR-14:40 | 160.77 | 85520.53 | 02-APR-02:00 |
May | 1977799.07 | 7511266.10 | 31-MAY-05:05 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 2706617.46 | 6824154.58 | 08-JUN-05:04 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 2826657.83 | 6935694.38 | 03-JUL-05:04 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2950607.64 | 6931984.02 | 21-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 2602138.78 | 7935637.97 | 22-SEP-05:05 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 2065497.71 | 7951880.58 | 02-OCT-05:05 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 1491385.19 | 6026048.11 | 29-NOV-11:40 | 541.13 | 106790.30 | 13-NOV-04:30 |
December | 751022.88 | 5318612.33 | 09-DEC-06:05 | 1076.89 | 146616.80 | 20-DEC-20:30 |
Annual Sum or Average | 1720195.61 | 422.09 | ||||
Minimum of Months | 573577.09 | 5201897.16 | 0.00 | 0.00 | ||
Maximum of Months | 2950607.64 | 7951880.58 | 1241.11 | 170522.49 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169660E+11 | 0.88 | 9877.89 | 01-JAN-00:15 | 1.37 |
February | 0.150893E+11 | 0.87 | 9877.89 | 01-FEB-04:03 | 1.38 |
March | 0.166620E+11 | 0.87 | 9877.89 | 01-MAR-04:02 | 1.38 |
April | 0.154333E+11 | 0.83 | 9877.89 | 01-APR-03:02 | 1.38 |
May | 0.166613E+11 | 0.86 | 9877.89 | 01-MAY-00:03 | 1.37 |
June | 0.162313E+11 | 0.87 | 9877.89 | 01-JUN-03:02 | 1.38 |
July | 0.163239E+11 | 0.85 | 9877.89 | 01-JUL-03:02 | 1.38 |
August | 0.174711E+11 | 0.91 | 9877.89 | 01-AUG-03:02 | 1.38 |
September | 0.165833E+11 | 0.89 | 9877.89 | 01-SEP-03:02 | 1.38 |
October | 0.170962E+11 | 0.89 | 9877.89 | 01-OCT-12:58 | 1.36 |
November | 0.167099E+11 | 0.90 | 9877.89 | 01-NOV-03:02 | 1.38 |
December | 0.167650E+11 | 0.87 | 9877.89 | 01-DEC-04:02 | 1.38 |
Annual Sum or Average | 0.197993E+12 | 0.87 | |||
Minimum of Months | 0.150893E+11 | 0.83 | 9877.89 | 1.36 | |
Maximum of Months | 0.174711E+11 | 0.91 | 9877.89 | 1.38 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.725849E+10 | 0.43 | 20625.94 | 30-JAN-04:02 | 1.76 |
February | 0.776162E+10 | 0.47 | 20625.94 | 13-FEB-06:03 | 1.76 |
March | 0.107206E+11 | 0.57 | 20625.94 | 27-MAR-05:03 | 1.76 |
April | 0.120042E+11 | 0.65 | 20576.74 | 17-APR-05:02 | 1.76 |
May | 0.113636E+11 | 0.58 | 20625.94 | 06-MAY-05:03 | 1.76 |
June | 0.125004E+11 | 0.65 | 20625.94 | 02-JUN-05:03 | 1.76 |
July | 0.136679E+11 | 0.68 | 20625.94 | 03-JUL-04:23 | 1.76 |
August | 0.152225E+11 | 0.74 | 20625.94 | 28-AUG-05:02 | 1.76 |
September | 0.104354E+11 | 0.57 | 20625.94 | 06-SEP-05:03 | 1.76 |
October | 0.101783E+11 | 0.56 | 20625.94 | 04-OCT-05:02 | 1.76 |
November | 0.958390E+10 | 0.55 | 20625.94 | 20-NOV-06:02 | 1.76 |
December | 0.912824E+10 | 0.52 | 20251.11 | 26-DEC-06:02 | 1.74 |
Annual Sum or Average | 0.129825E+12 | 0.58 | |||
Minimum of Months | 0.725849E+10 | 0.43 | 20251.11 | 1.74 | |
Maximum of Months | 0.152225E+11 | 0.74 | 20625.94 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.547384E+11 | 0.38 | 158235.27 | 07-JAN-06:03 | 1.55 |
February | 0.544947E+11 | 0.39 | 192071.77 | 11-FEB-06:02 | 1.76 |
March | 0.732746E+11 | 0.45 | 192071.77 | 14-MAR-05:03 | 1.76 |
April | 0.799479E+11 | 0.48 | 192071.77 | 24-APR-05:03 | 1.76 |
May | 0.975241E+11 | 0.53 | 192071.77 | 03-MAY-05:03 | 1.76 |
June | 0.101106E+12 | 0.56 | 192071.77 | 01-JUN-03:02 | 1.76 |
July | 0.100461E+12 | 0.55 | 192071.77 | 01-JUL-03:02 | 1.76 |
August | 0.101615E+12 | 0.56 | 192071.77 | 01-AUG-05:03 | 1.76 |
September | 0.855307E+11 | 0.51 | 192071.77 | 05-SEP-05:03 | 1.76 |
October | 0.768573E+11 | 0.46 | 192071.77 | 02-OCT-03:02 | 1.76 |
November | 0.644979E+11 | 0.42 | 192071.77 | 29-NOV-06:02 | 1.76 |
December | 0.549945E+11 | 0.38 | 185711.04 | 01-DEC-06:03 | 1.72 |
Annual Sum or Average | 0.945043E+12 | 0.47 | |||
Minimum of Months | 0.544947E+11 | 0.38 | 158235.27 | 1.55 | |
Maximum of Months | 0.101615E+12 | 0.56 | 192071.77 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.487034E+10 | 0.34 | 17888.47 | 14-JAN-06:03 | 1.61 |
February | 0.529533E+10 | 0.37 | 18922.09 | 11-FEB-06:02 | 1.67 |
March | 0.742038E+10 | 0.43 | 19324.65 | 14-MAR-05:03 | 1.69 |
April | 0.868989E+10 | 0.48 | 19938.22 | 29-APR-05:02 | 1.73 |
May | 0.110601E+11 | 0.55 | 20536.11 | 08-MAY-05:03 | 1.76 |
June | 0.115738E+11 | 0.59 | 20536.11 | 01-JUN-03:02 | 1.76 |
July | 0.118614E+11 | 0.58 | 20536.11 | 01-JUL-03:02 | 1.76 |
August | 0.116903E+11 | 0.58 | 20536.11 | 16-AUG-03:02 | 1.76 |
September | 0.983302E+10 | 0.54 | 20536.11 | 09-SEP-05:03 | 1.76 |
October | 0.834747E+10 | 0.47 | 20536.11 | 02-OCT-03:02 | 1.76 |
November | 0.657152E+10 | 0.40 | 20536.11 | 29-NOV-06:02 | 1.76 |
December | 0.518223E+10 | 0.35 | 17218.84 | 09-DEC-06:03 | 1.57 |
Annual Sum or Average | 0.102396E+12 | 0.47 | |||
Minimum of Months | 0.487034E+10 | 0.34 | 17218.84 | 1.57 | |
Maximum of Months | 0.118614E+11 | 0.59 | 20536.11 | 1.76 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.949662E+11 | 1.35 | 35456.32 | 01-JAN-00:05 | 1.35 |
February | 0.857759E+11 | 1.35 | 35456.32 | 01-FEB-00:10 | 1.35 |
March | 0.949662E+11 | 1.35 | 35456.32 | 01-MAR-00:10 | 1.35 |
April | 0.919028E+11 | 1.35 | 35456.32 | 01-APR-00:05 | 1.35 |
May | 0.949662E+11 | 1.35 | 35456.32 | 01-MAY-00:03 | 1.35 |
June | 0.919028E+11 | 1.35 | 35456.32 | 01-JUN-00:03 | 1.35 |
July | 0.949662E+11 | 1.35 | 35456.32 | 01-JUL-00:10 | 1.35 |
August | 0.949662E+11 | 1.35 | 35456.32 | 01-AUG-00:05 | 1.35 |
September | 0.919028E+11 | 1.35 | 35456.32 | 01-SEP-00:03 | 1.35 |
October | 0.949662E+11 | 1.35 | 35456.32 | 01-OCT-00:03 | 1.35 |
November | 0.919028E+11 | 1.35 | 35456.32 | 01-NOV-00:03 | 1.35 |
December | 0.949662E+11 | 1.35 | 35456.32 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.111815E+13 | 1.35 | |||
Minimum of Months | 0.857759E+11 | 1.35 | 35456.32 | 1.35 | |
Maximum of Months | 0.949662E+11 | 1.35 | 35456.32 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141864E+10 | 0.91 | 529.66 | 01-JAN-00:05 | 0.91 |
February | 0.128136E+10 | 0.91 | 529.66 | 01-FEB-00:10 | 0.91 |
March | 0.141864E+10 | 0.91 | 529.66 | 01-MAR-00:10 | 0.91 |
April | 0.137288E+10 | 0.91 | 529.66 | 01-APR-00:05 | 0.91 |
May | 0.141864E+10 | 0.91 | 529.66 | 01-MAY-00:03 | 0.91 |
June | 0.137288E+10 | 0.91 | 529.66 | 01-JUN-00:03 | 0.91 |
July | 0.141864E+10 | 0.91 | 529.66 | 01-JUL-00:10 | 0.91 |
August | 0.141864E+10 | 0.91 | 529.66 | 01-AUG-00:05 | 0.91 |
September | 0.137288E+10 | 0.91 | 529.66 | 01-SEP-00:03 | 0.91 |
October | 0.141864E+10 | 0.91 | 529.66 | 01-OCT-00:03 | 0.91 |
November | 0.137288E+10 | 0.91 | 529.66 | 01-NOV-00:03 | 0.91 |
December | 0.141864E+10 | 0.91 | 529.66 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.167034E+11 | 0.91 | |||
Minimum of Months | 0.128136E+10 | 0.91 | 529.66 | 0.91 | |
Maximum of Months | 0.141864E+10 | 0.91 | 529.66 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134811E+11 | 0.91 | 5033.26 | 01-JAN-00:05 | 0.91 |
February | 0.121765E+11 | 0.91 | 5033.26 | 01-FEB-00:10 | 0.91 |
March | 0.134811E+11 | 0.91 | 5033.26 | 01-MAR-00:10 | 0.91 |
April | 0.130462E+11 | 0.91 | 5033.26 | 01-APR-00:05 | 0.91 |
May | 0.134811E+11 | 0.91 | 5033.26 | 01-MAY-00:03 | 0.91 |
June | 0.130462E+11 | 0.91 | 5033.26 | 01-JUN-00:03 | 0.91 |
July | 0.134811E+11 | 0.91 | 5033.26 | 01-JUL-00:10 | 0.91 |
August | 0.134811E+11 | 0.91 | 5033.26 | 01-AUG-00:05 | 0.91 |
September | 0.130462E+11 | 0.91 | 5033.26 | 01-SEP-00:07 | 0.91 |
October | 0.134811E+11 | 0.91 | 5033.26 | 01-OCT-00:03 | 0.91 |
November | 0.130462E+11 | 0.91 | 5033.26 | 01-NOV-00:03 | 0.91 |
December | 0.134811E+11 | 0.91 | 5033.26 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.158729E+12 | 0.91 | |||
Minimum of Months | 0.121765E+11 | 0.91 | 5033.26 | 0.91 | |
Maximum of Months | 0.134811E+11 | 0.91 | 5033.26 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136885E+10 | 0.91 | 511.07 | 01-JAN-00:05 | 0.91 |
February | 0.123639E+10 | 0.91 | 511.07 | 01-FEB-00:10 | 0.91 |
March | 0.136885E+10 | 0.91 | 511.07 | 01-MAR-00:10 | 0.91 |
April | 0.132470E+10 | 0.91 | 511.07 | 01-APR-00:05 | 0.91 |
May | 0.136885E+10 | 0.91 | 511.07 | 01-MAY-00:03 | 0.91 |
June | 0.132470E+10 | 0.91 | 511.07 | 01-JUN-00:03 | 0.91 |
July | 0.136885E+10 | 0.91 | 511.07 | 01-JUL-00:10 | 0.91 |
August | 0.136885E+10 | 0.91 | 511.07 | 01-AUG-00:05 | 0.91 |
September | 0.132470E+10 | 0.91 | 511.07 | 01-SEP-00:03 | 0.91 |
October | 0.136885E+10 | 0.91 | 511.07 | 01-OCT-00:03 | 0.91 |
November | 0.132470E+10 | 0.91 | 511.07 | 01-NOV-00:03 | 0.91 |
December | 0.136885E+10 | 0.91 | 511.07 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.161172E+11 | 0.91 | |||
Minimum of Months | 0.123639E+10 | 0.91 | 511.07 | 0.91 | |
Maximum of Months | 0.136885E+10 | 0.91 | 511.07 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 2679834.36 | 2411850.92 | 927.35 | 25-JAN-06:20 | 834.61 | 834.61 | 45.88 | 1.08 |
February | 4407441.80 | 3966697.62 | 1778.17 | 04-FEB-06:02 | 1600.35 | 1600.35 | 36.86 | 2.53 |
March | 2114565.25 | 1903108.72 | 971.49 | 16-MAR-05:05 | 874.34 | 874.34 | 36.47 | 1.15 |
April | 1.23 | 1.11 | 0.01 | 03-APR-00:48 | 0.01 | 0.01 | 28.99 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 28.99 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 28.99 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 28.99 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 28.99 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 28.99 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 28.99 | 0.00 |
November | 835580.16 | 752022.15 | 676.59 | 27-NOV-06:08 | 608.93 | 608.93 | 31.72 | 0.76 |
December | 3860427.32 | 3474384.59 | 957.03 | 15-DEC-06:20 | 861.33 | 861.33 | 41.09 | 1.12 |
Annual Sum or Average | 13897850.12 | 12508065.11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.99 | 0.00 | |
Maximum of Months | 4407441.80 | 3966697.62 | 1778.17 | 1600.35 | 1600.35 | 45.88 | 2.53 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128482E+10 | 0.115634E+10 | 27589.26 | 02-JAN-06:03 | 24830.33 | 24830.33 | 8.18 | 136.35 |
February | 0.138499E+10 | 0.124649E+10 | 28717.83 | 11-FEB-06:02 | 25846.05 | 25846.05 | 7.78 | 138.53 |
March | 0.159295E+10 | 0.143365E+10 | 28717.83 | 06-MAR-06:03 | 25846.05 | 25846.05 | 8.03 | 138.53 |
April | 0.160515E+10 | 0.144463E+10 | 28600.32 | 24-APR-05:03 | 25740.29 | 25740.29 | 7.67 | 138.30 |
May | 0.222150E+10 | 0.199935E+10 | 28717.83 | 03-MAY-05:03 | 25846.05 | 25846.05 | 7.92 | 138.53 |
June | 0.237727E+10 | 0.213954E+10 | 28717.83 | 01-JUN-05:03 | 25846.05 | 25846.05 | 7.74 | 138.53 |
July | 0.236909E+10 | 0.213218E+10 | 28717.83 | 03-JUL-05:02 | 25846.05 | 25846.05 | 7.84 | 138.53 |
August | 0.256793E+10 | 0.231114E+10 | 28717.83 | 01-AUG-05:03 | 25846.05 | 25846.05 | 7.24 | 138.53 |
September | 0.267176E+10 | 0.240459E+10 | 28717.83 | 05-SEP-05:03 | 25846.05 | 25846.05 | 7.75 | 138.53 |
October | 0.288284E+10 | 0.259456E+10 | 28717.83 | 02-OCT-04:23 | 25846.05 | 25846.05 | 7.67 | 138.53 |
November | 0.240230E+10 | 0.216207E+10 | 28717.83 | 04-NOV-05:03 | 25846.05 | 25846.05 | 7.47 | 138.53 |
December | 0.155183E+10 | 0.139664E+10 | 28717.83 | 23-DEC-06:02 | 25846.05 | 25846.05 | 7.79 | 138.53 |
Annual Sum or Average | 0.249124E+11 | 0.224212E+11 | ||||||
Minimum of Months | 0.128482E+10 | 0.115634E+10 | 27589.26 | 24830.33 | 24830.33 | 7.24 | 136.35 | |
Maximum of Months | 0.288284E+10 | 0.259456E+10 | 28717.83 | 25846.05 | 25846.05 | 8.18 | 138.53 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.349177E+11 | 0.314259E+11 | 19765.71 | 01-JAN-00:15 | 17789.13 | 17789.13 | 7.79 | 138.53 |
February | 0.322288E+11 | 0.290059E+11 | 19765.71 | 01-FEB-04:03 | 17789.13 | 17789.13 | 8.73 | 138.53 |
March | 0.406996E+11 | 0.366296E+11 | 19765.71 | 01-MAR-04:02 | 17789.13 | 17789.13 | 9.45 | 138.53 |
April | 0.445750E+11 | 0.401175E+11 | 19765.71 | 01-APR-00:32 | 17789.13 | 17789.13 | 7.53 | 138.53 |
May | 0.415667E+11 | 0.374100E+11 | 19765.71 | 01-MAY-00:03 | 17789.13 | 17789.13 | 7.65 | 138.53 |
June | 0.439821E+11 | 0.395838E+11 | 19765.71 | 01-JUN-00:52 | 17789.13 | 17789.13 | 7.01 | 138.53 |
July | 0.481623E+11 | 0.433461E+11 | 19765.71 | 01-JUL-00:10 | 17789.13 | 17789.13 | 6.99 | 138.53 |
August | 0.494368E+11 | 0.444931E+11 | 19765.71 | 01-AUG-00:05 | 17789.13 | 17789.13 | 7.04 | 138.53 |
September | 0.419509E+11 | 0.377558E+11 | 19765.71 | 01-SEP-00:03 | 17789.13 | 17789.13 | 7.12 | 138.53 |
October | 0.430695E+11 | 0.387625E+11 | 19765.71 | 01-OCT-00:03 | 17789.13 | 17789.13 | 7.54 | 138.53 |
November | 0.400034E+11 | 0.360031E+11 | 19765.71 | 01-NOV-02:42 | 17789.13 | 17789.13 | 7.67 | 138.53 |
December | 0.408844E+11 | 0.367959E+11 | 19765.71 | 01-DEC-00:12 | 17789.13 | 17789.13 | 7.36 | 138.53 |
Annual Sum or Average | 0.501477E+12 | 0.451329E+12 | ||||||
Minimum of Months | 0.322288E+11 | 0.290059E+11 | 19765.71 | 17789.13 | 17789.13 | 6.99 | 138.53 | |
Maximum of Months | 0.494368E+11 | 0.444931E+11 | 19765.71 | 17789.13 | 17789.13 | 9.45 | 138.53 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.914616E+10 | 0.823155E+10 | 3414.79 | 01-JAN-00:05 | 3073.31 | 3073.31 | 26.41 | 14.26 |
February | 0.826105E+10 | 0.743495E+10 | 3414.79 | 01-FEB-00:10 | 3073.31 | 3073.31 | 25.04 | 14.26 |
March | 0.914616E+10 | 0.823155E+10 | 3414.79 | 01-MAR-00:10 | 3073.31 | 3073.31 | 30.12 | 14.26 |
April | 0.885113E+10 | 0.796601E+10 | 3414.79 | 01-APR-00:05 | 3073.31 | 3073.31 | 40.97 | 14.26 |
May | 0.914616E+10 | 0.823155E+10 | 3414.79 | 01-MAY-00:03 | 3073.31 | 3073.31 | 28.51 | 14.26 |
June | 0.885113E+10 | 0.796601E+10 | 3414.79 | 01-JUN-00:03 | 3073.31 | 3073.31 | 37.45 | 14.26 |
July | 0.914616E+10 | 0.823155E+10 | 3414.79 | 01-JUL-00:10 | 3073.31 | 3073.31 | 41.87 | 14.26 |
August | 0.914616E+10 | 0.823155E+10 | 3414.79 | 01-AUG-00:05 | 3073.31 | 3073.31 | 48.07 | 14.26 |
September | 0.885113E+10 | 0.796601E+10 | 3414.79 | 01-SEP-00:03 | 3073.31 | 3073.31 | 34.29 | 14.26 |
October | 0.914616E+10 | 0.823155E+10 | 3414.79 | 01-OCT-00:03 | 3073.31 | 3073.31 | 38.67 | 14.26 |
November | 0.885113E+10 | 0.796601E+10 | 3414.79 | 01-NOV-00:03 | 3073.31 | 3073.31 | 36.87 | 14.26 |
December | 0.914616E+10 | 0.823155E+10 | 3414.79 | 01-DEC-00:10 | 3073.31 | 3073.31 | 42.27 | 14.26 |
Annual Sum or Average | 0.107689E+12 | 0.969198E+11 | ||||||
Minimum of Months | 0.826105E+10 | 0.743495E+10 | 3414.79 | 3073.31 | 3073.31 | 25.04 | 14.26 | |
Maximum of Months | 0.914616E+10 | 0.823155E+10 | 3414.79 | 3073.31 | 3073.31 | 48.07 | 14.26 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:02 | 1.79 | 1.79 | 56.64 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:03 | 1.79 | 1.79 | 56.50 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 57.30 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 57.02 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 57.46 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 57.25 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 57.50 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 57.92 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.42 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:05 | 1.79 | 1.79 | 57.61 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 57.55 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:03 | 1.79 | 1.79 | 56.34 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 56.34 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 57.92 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.471762E+11 | 0.424586E+11 | 49215.53 | 02-JAN-14:00 | 44293.98 | 44293.98 | 29.06 | 162.97 |
February | 0.431267E+11 | 0.388140E+11 | 49215.53 | 11-FEB-06:04 | 44293.98 | 44293.98 | 29.20 | 162.97 |
March | 0.572697E+11 | 0.515428E+11 | 49212.60 | 13-MAR-13:10 | 44291.34 | 44291.34 | 28.74 | 162.97 |
April | 0.630741E+11 | 0.567667E+11 | 49215.53 | 14-APR-14:00 | 44293.98 | 44293.98 | 28.95 | 162.97 |
May | 0.698515E+11 | 0.628664E+11 | 49215.53 | 10-MAY-05:05 | 44293.98 | 44293.98 | 30.08 | 162.97 |
June | 0.752138E+11 | 0.676924E+11 | 49215.53 | 01-JUN-05:03 | 44293.98 | 44293.98 | 29.21 | 162.97 |
July | 0.798763E+11 | 0.718887E+11 | 49215.53 | 01-JUL-05:05 | 44293.98 | 44293.98 | 28.99 | 162.97 |
August | 0.832559E+11 | 0.749303E+11 | 49215.53 | 01-AUG-05:03 | 44293.98 | 44293.98 | 28.81 | 162.97 |
September | 0.720409E+11 | 0.648368E+11 | 49215.53 | 01-SEP-08:00 | 44293.98 | 44293.98 | 28.97 | 162.97 |
October | 0.714166E+11 | 0.642749E+11 | 49215.53 | 01-OCT-11:24 | 44293.98 | 44293.98 | 29.00 | 162.97 |
November | 0.628052E+11 | 0.565247E+11 | 49215.53 | 03-NOV-08:70 | 44293.98 | 44293.98 | 28.82 | 162.97 |
December | 0.550806E+11 | 0.495726E+11 | 49215.53 | 09-DEC-06:05 | 44293.98 | 44293.98 | 28.91 | 162.97 |
Annual Sum or Average | 0.780188E+12 | 0.702169E+12 | ||||||
Minimum of Months | 0.431267E+11 | 0.388140E+11 | 49212.60 | 44291.34 | 44291.34 | 28.74 | 162.97 | |
Maximum of Months | 0.832559E+11 | 0.749303E+11 | 49215.53 | 44293.98 | 44293.98 | 30.08 | 162.97 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 79.40 | 79.40 | 154.90 | 151867.44 | 25-JAN-06:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 30.66 | 30.66 | 405.46 | 457199.35 | 04-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 30.16 | 30.16 | 165.39 | 221001.68 | 16-MAR-04:05 |
April | 0.00 | 0.00 | 01-APR-00:05 | 28.99 | 28.99 | 0.00 | 1.76 | 03-APR-00:48 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.99 | 28.99 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.99 | 28.99 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 28.99 | 28.99 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.99 | 28.99 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.99 | 28.99 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.99 | 28.99 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 28.99 | 28.99 | 67.79 | 151317.01 | 27-NOV-06:08 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 33.47 | 33.47 | 292.85 | 200517.88 | 27-DEC-06:06 |
Annual Sum or Average | 0.00 | 88.75 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.99 | 28.99 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 79.40 | 79.40 | 405.46 | 457199.35 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 646292.66 | 3198104.73 | 07-JAN-06:03 | 12.80 | 7.29 | 42.56 | 178722.63 | 22-JAN-21:05 |
February | 717328.59 | 3656393.75 | 11-FEB-06:04 | 13.43 | 7.72 | 8.92 | 48180.43 | 27-FEB-00:25 |
March | 803507.28 | 3167358.38 | 06-MAR-06:03 | 12.75 | 7.29 | 12.44 | 106585.34 | 12-MAR-06:52 |
April | 932497.45 | 2800131.12 | 22-APR-05:03 | 12.04 | 7.21 | 1.98 | 33321.86 | 02-APR-04:22 |
May | 1062567.73 | 3839063.09 | 31-MAY-05:05 | 13.57 | 7.87 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1118693.87 | 3944704.95 | 22-JUN-05:04 | 13.77 | 8.07 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1139243.35 | 3360377.10 | 15-JUL-05:03 | 12.58 | 6.88 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1154794.63 | 3301681.22 | 15-AUG-05:03 | 12.39 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1109760.97 | 3551908.35 | 16-SEP-05:04 | 13.24 | 7.54 | 5.98 | 113275.00 | 02-SEP-21:52 |
October | 1042683.59 | 3962748.77 | 02-OCT-05:05 | 13.53 | 7.83 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 916220.50 | 3269114.81 | 29-NOV-06:04 | 12.59 | 6.96 | 5.09 | 73474.56 | 11-NOV-09:42 |
December | 711550.97 | 3148512.22 | 09-DEC-06:03 | 12.40 | 6.97 | 4.90 | 49496.38 | 12-DEC-00:42 |
Annual Sum or Average | 947343.10 | 6.84 | ||||||
Minimum of Months | 646292.66 | 2800131.12 | 12.04 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1154794.63 | 3962748.77 | 13.77 | 8.07 | 42.56 | 178722.63 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 480358.98 | 4601358.74 | 30-JAN-04:02 | 15.69 | 7.48 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 556809.73 | 4768588.27 | 11-FEB-06:02 | 14.92 | 7.59 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 623498.03 | 4635477.55 | 10-MAR-06:02 | 14.71 | 7.74 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 715088.16 | 4320085.41 | 13-APR-03:02 | 14.87 | 7.04 | 0.00 | 0.00 | 01-APR-00:05 |
May | 873024.01 | 4846886.01 | 27-MAY-05:02 | 15.06 | 7.15 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 956543.52 | 4767689.81 | 22-JUN-05:02 | 14.92 | 7.76 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 942648.30 | 4720124.47 | 03-JUL-05:02 | 14.84 | 7.48 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 977947.48 | 4768741.01 | 28-AUG-05:02 | 14.93 | 7.48 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 945457.28 | 4895403.14 | 21-SEP-03:02 | 15.14 | 6.89 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 860333.57 | 4948473.09 | 02-OCT-03:02 | 15.31 | 6.74 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 741544.34 | 4623443.37 | 24-NOV-06:02 | 14.67 | 8.10 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 535641.81 | 4620449.29 | 23-DEC-06:02 | 14.67 | 7.38 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 768347.09 | 0.00 | ||||||
Minimum of Months | 480358.98 | 4320085.41 | 14.67 | 6.74 | 0.00 | 0.00 | ||
Maximum of Months | 977947.48 | 4948473.09 | 15.69 | 8.10 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 372322.09 | 876990.87 | 02-JAN-15:00 | 35.80 | 31.03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 648038.75 | 1106227.39 | 11-FEB-14:00 | 40.27 | 32.78 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 894688.37 | 1355663.94 | 13-MAR-16:00 | 45.09 | 34.31 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1248541.94 | 1707993.26 | 17-APR-15:00 | 51.83 | 38.38 | 0.00 | 0.00 | 01-APR-00:05 |
May | 726474.60 | 1164679.13 | 22-MAY-13:00 | 41.40 | 36.58 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1025320.15 | 1262740.80 | 11-JUN-13:00 | 43.30 | 35.66 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1277790.51 | 1697688.49 | 29-JUL-16:00 | 51.63 | 40.65 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1484319.40 | 1814505.01 | 23-AUG-13:00 | 53.86 | 40.20 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 791260.09 | 1063581.83 | 20-SEP-14:00 | 39.44 | 34.45 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 947676.53 | 1268938.83 | 02-OCT-14:00 | 43.42 | 35.36 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 1010381.37 | 1386687.58 | 17-NOV-15:00 | 45.69 | 34.91 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 1036235.18 | 1525450.29 | 10-DEC-14:58 | 48.35 | 35.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 957081.91 | 0.00 | ||||||
Minimum of Months | 372322.09 | 876990.87 | 35.80 | 31.03 | 0.00 | 0.00 | ||
Maximum of Months | 1484319.40 | 1814505.01 | 53.86 | 40.65 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.36 | 57.36 | 11606.11 | 37905.80 | 17-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.94 | 56.94 | 11570.65 | 37798.55 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.71 | 57.71 | 11862.85 | 37083.45 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:05 | 57.43 | 57.43 | 10759.90 | 35527.46 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.99 | 57.99 | 10592.08 | 33962.65 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 57.59 | 57.59 | 10434.03 | 32419.51 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.32 | 58.32 | 9572.34 | 31470.04 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 58.23 | 58.23 | 10449.42 | 32176.17 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 56.78 | 56.78 | 10209.41 | 33524.91 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 58.06 | 58.06 | 10642.36 | 35296.53 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 57.90 | 57.90 | 11240.28 | 36806.94 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.92 | 56.92 | 11221.98 | 37692.67 | 28-DEC-13:00 |
Annual Sum or Average | 0.00 | 10842.87 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.78 | 56.78 | 9572.34 | 31470.04 | ||
Maximum of Months | 0.00 | 0.00 | 58.32 | 58.32 | 11862.85 | 37905.80 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 573577.09 | 5478669.66 | 02-JAN-14:10 | 29.14 | 26.16 | 1241.11 | 153210.89 | 25-JAN-06:30 |
February | 660119.28 | 5520370.29 | 11-FEB-06:04 | 29.20 | 24.96 | 1219.05 | 170522.49 | 04-FEB-06:30 |
March | 878218.13 | 5201897.16 | 13-MAR-13:10 | 28.74 | 25.54 | 871.46 | 159797.41 | 16-MAR-06:10 |
April | 1088634.16 | 5528320.32 | 14-APR-14:40 | 29.22 | 26.15 | 160.77 | 85520.53 | 02-APR-02:00 |
May | 1977799.07 | 7511266.10 | 31-MAY-05:05 | 32.13 | 27.07 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 2706617.46 | 6824154.58 | 08-JUN-05:04 | 31.12 | 27.39 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 2826657.83 | 6935694.38 | 03-JUL-05:04 | 31.28 | 26.75 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2950607.64 | 6931984.02 | 21-AUG-16:00 | 31.28 | 28.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 2602138.78 | 7935637.97 | 22-SEP-05:05 | 32.75 | 28.06 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 2065497.71 | 7951880.58 | 02-OCT-05:05 | 32.77 | 27.87 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 1491385.19 | 6026048.11 | 29-NOV-11:40 | 29.95 | 26.72 | 541.13 | 106790.30 | 13-NOV-04:30 |
December | 751022.88 | 5318612.33 | 09-DEC-06:05 | 28.91 | 25.03 | 1076.89 | 146616.80 | 20-DEC-20:30 |
Annual Sum or Average | 1720195.61 | 422.09 | ||||||
Minimum of Months | 573577.09 | 5201897.16 | 28.74 | 24.96 | 0.00 | 0.00 | ||
Maximum of Months | 2950607.64 | 7951880.58 | 32.77 | 28.06 | 1241.11 | 170522.49 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 18633502.86 | 0.00 | 0.958198E+11 | 0.725849E+10 | 0.00 | 0.00 |
February | 19564592.00 | 0.00 | 0.107495E+12 | 0.776162E+10 | 0.00 | 0.00 |
March | 17584212.59 | 0.00 | 0.144697E+12 | 0.107206E+11 | 0.00 | 0.00 |
April | 339.46 | 0.00 | 0.168492E+12 | 0.120042E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.184192E+12 | 0.113636E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.209250E+12 | 0.125004E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.225873E+12 | 0.136679E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.246060E+12 | 0.152225E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.197144E+12 | 0.104354E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.194390E+12 | 0.101783E+11 | 0.00 | 0.00 |
November | 9696354.11 | 0.00 | 0.165306E+12 | 0.958390E+10 | 0.00 | 0.00 |
December | 33371783.06 | 0.00 | 0.132007E+12 | 0.912824E+10 | 0.00 | 0.00 |
Annual Sum or Average | 98850784.08 | 0.00 | 0.207073E+13 | 0.129825E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.958198E+11 | 0.725849E+10 | 0.00 | 0.00 |
Maximum of Months | 33371783.06 | 0.00 | 0.246060E+12 | 0.152225E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.316478E+09 | 0.00 | 0.778612E+12 | 0.547384E+11 | 0.00 | 0.00 |
February | 0.665681E+09 | 0.00 | 0.841014E+12 | 0.544947E+11 | 0.00 | 0.00 |
March | 0.311851E+09 | 0.00 | 0.105107E+13 | 0.732746E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.120045E+13 | 0.799479E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.159385E+13 | 0.975241E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.173728E+13 | 0.101106E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.177501E+13 | 0.100461E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.182867E+13 | 0.101615E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.172073E+13 | 0.855307E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.157220E+13 | 0.768573E+11 | 0.00 | 0.00 |
November | 0.110107E+09 | 0.00 | 0.124683E+13 | 0.644979E+11 | 0.00 | 0.00 |
December | 0.453904E+09 | 0.00 | 0.852869E+12 | 0.549945E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.185802E+10 | 0.00 | 0.161986E+14 | 0.945043E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.778612E+12 | 0.544947E+11 | 0.00 | 0.00 |
Maximum of Months | 0.665681E+09 | 0.00 | 0.182867E+13 | 0.101615E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.225057E+09 | 0.00 | 0.728920E+11 | 0.487034E+10 | 0.00 | 0.00 |
February | 0.305571E+09 | 0.00 | 0.846920E+11 | 0.529533E+10 | 0.00 | 0.00 |
March | 0.120612E+09 | 0.00 | 0.110267E+12 | 0.742038E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.131479E+12 | 0.868989E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.178238E+12 | 0.110601E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.196247E+12 | 0.115738E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202715E+12 | 0.118614E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.202837E+12 | 0.116903E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.189559E+12 | 0.983302E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.165847E+12 | 0.834747E+10 | 0.00 | 0.00 |
November | 44972176.61 | 0.00 | 0.127216E+12 | 0.657152E+10 | 0.00 | 0.00 |
December | 0.299542E+09 | 0.00 | 0.828684E+11 | 0.518223E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.995754E+09 | 0.00 | 0.174486E+13 | 0.102396E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.728920E+11 | 0.487034E+10 | 0.00 | 0.00 |
Maximum of Months | 0.305571E+09 | 0.00 | 0.202837E+12 | 0.118614E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.791063E+11 | 0.169660E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.759060E+11 | 0.150893E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.877924E+11 | 0.166620E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.893993E+11 | 0.154333E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.113328E+12 | 0.166613E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126883E+12 | 0.162313E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.131710E+12 | 0.163239E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.144438E+12 | 0.174711E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.127147E+12 | 0.165833E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.122079E+12 | 0.170962E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.105570E+12 | 0.167099E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.838129E+11 | 0.167650E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.128717E+13 | 0.197993E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.759060E+11 | 0.150893E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.144438E+12 | 0.174711E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.433552E+12 | 0.188943E+12 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.679758E+12 | 0.235885E+12 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.107246E+13 | 0.333514E+12 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.136187E+13 | 0.408698E+12 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.477447E+12 | 0.212704E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.789800E+12 | 0.290120E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.114760E+13 | 0.385176E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.145166E+13 | 0.454504E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.475590E+12 | 0.211559E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.804838E+12 | 0.291709E+12 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.106358E+13 | 0.337908E+12 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.137549E+13 | 0.391552E+12 | 0.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.111336E+14 | 0.374227E+13 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.433552E+12 | 0.188943E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.145166E+13 | 0.454504E+12 | 0.00 | 0.13 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.745129E+10 | 0.301458E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.129153E+11 | 0.409250E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.210051E+11 | 0.602402E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.272767E+11 | 0.764627E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.920995E+10 | 0.363269E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.158641E+11 | 0.525655E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.232561E+11 | 0.717408E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.300932E+11 | 0.883791E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.929236E+10 | 0.364475E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.159721E+11 | 0.523618E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.210475E+11 | 0.615891E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.271232E+11 | 0.720342E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.220507E+12 | 0.679219E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.745129E+10 | 0.301458E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.300932E+11 | 0.883791E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.640796E+11 | 0.273174E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.118257E+12 | 0.380260E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.198170E+12 | 0.570068E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.260069E+12 | 0.728558E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.867163E+11 | 0.343309E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.151575E+12 | 0.501244E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.222428E+12 | 0.684851E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.286013E+12 | 0.840102E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.872926E+11 | 0.343871E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.151761E+12 | 0.497472E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.198915E+12 | 0.583361E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.254567E+12 | 0.679143E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207984E+13 | 0.642541E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.640796E+11 | 0.273174E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.286013E+12 | 0.840102E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.579054E+10 | 0.263313E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.114730E+11 | 0.375758E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.196539E+11 | 0.569933E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.260718E+11 | 0.733025E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.882048E+10 | 0.349124E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.153204E+11 | 0.507483E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.224597E+11 | 0.692717E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.287598E+11 | 0.846985E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.888402E+10 | 0.349865E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.152366E+11 | 0.501433E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.197313E+11 | 0.583131E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.250593E+11 | 0.675115E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207261E+12 | 0.644788E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.579054E+10 | 0.263313E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.287598E+11 | 0.846985E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.725849E+10 | 0.958198E+11 | 18633502.86 | 0.182810E+09 | 0.416961E+10 | 0.00 | 0.00 | 0.00 |
February | 0.776162E+10 | 0.107495E+12 | 19564592.00 | 0.838838E+09 | 0.527148E+10 | 0.00 | 0.00 | 0.00 |
March | 0.107206E+11 | 0.144697E+12 | 17584212.59 | 0.260281E+09 | 0.809192E+10 | 0.00 | 0.00 | 0.00 |
April | 0.120042E+11 | 0.168492E+12 | 339.46 | 34924185.67 | 0.161785E+11 | 0.00 | 0.00 | 0.00 |
May | 0.113636E+11 | 0.184192E+12 | 0.00 | 0.00 | 0.407148E+11 | 0.00 | 0.00 | 0.00 |
June | 0.125004E+11 | 0.209250E+12 | 0.00 | 0.00 | 0.702545E+11 | 0.00 | 0.00 | 0.00 |
July | 0.136679E+11 | 0.225873E+12 | 0.00 | 0.00 | 0.812345E+11 | 0.00 | 0.00 | 0.00 |
August | 0.152225E+11 | 0.246060E+12 | 0.00 | 0.00 | 0.863176E+11 | 0.00 | 0.00 | 0.00 |
September | 0.104354E+11 | 0.197144E+12 | 0.00 | 0.00 | 0.616514E+11 | 0.00 | 0.00 | 0.00 |
October | 0.101783E+11 | 0.194390E+12 | 0.00 | 0.00 | 0.478789E+11 | 0.00 | 0.00 | 0.00 |
November | 0.958390E+10 | 0.165306E+12 | 9696354.11 | 60312186.00 | 0.291221E+11 | 0.00 | 0.00 | 0.00 |
December | 0.912824E+10 | 0.132007E+12 | 33371783.06 | 0.248135E+09 | 0.811118E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129825E+12 | 0.207073E+13 | 98850784.08 | 0.162530E+10 | 0.458996E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.725849E+10 | 0.958198E+11 | 0.00 | 0.00 | 0.416961E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152225E+11 | 0.246060E+12 | 33371783.06 | 0.838838E+09 | 0.863176E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.547384E+11 | 0.778612E+12 | 0.316478E+09 | 0.364420E+10 | 0.439030E+11 | 0.00 | 0.00 | 0.00 |
February | 0.544947E+11 | 0.841014E+12 | 0.665681E+09 | 0.106190E+11 | 0.525673E+11 | 0.00 | 0.00 | 0.00 |
March | 0.732746E+11 | 0.105107E+13 | 0.311851E+09 | 0.440122E+10 | 0.783753E+11 | 0.00 | 0.00 | 0.00 |
April | 0.799479E+11 | 0.120045E+13 | 0.00 | 0.511019E+09 | 0.148630E+12 | 0.00 | 0.00 | 0.00 |
May | 0.975241E+11 | 0.159385E+13 | 0.00 | 0.00 | 0.383994E+12 | 0.00 | 0.00 | 0.00 |
June | 0.101106E+12 | 0.173728E+13 | 0.00 | 0.00 | 0.619448E+12 | 0.00 | 0.00 | 0.00 |
July | 0.100461E+12 | 0.177501E+13 | 0.00 | 0.00 | 0.708940E+12 | 0.00 | 0.00 | 0.00 |
August | 0.101615E+12 | 0.182867E+13 | 0.00 | 0.00 | 0.701532E+12 | 0.00 | 0.00 | 0.00 |
September | 0.855307E+11 | 0.172073E+13 | 0.00 | 0.00 | 0.573419E+12 | 0.00 | 0.00 | 0.00 |
October | 0.768573E+11 | 0.157220E+13 | 0.00 | 1094030.06 | 0.435192E+12 | 0.00 | 0.00 | 0.00 |
November | 0.644979E+11 | 0.124683E+13 | 0.110107E+09 | 0.114530E+10 | 0.263558E+12 | 0.00 | 0.00 | 0.00 |
December | 0.549945E+11 | 0.852869E+12 | 0.453904E+09 | 0.457963E+10 | 0.796755E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.945043E+12 | 0.161986E+14 | 0.185802E+10 | 0.249014E+11 | 0.408923E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.544947E+11 | 0.778612E+12 | 0.00 | 0.00 | 0.439030E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101615E+12 | 0.182867E+13 | 0.665681E+09 | 0.106190E+11 | 0.708940E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.487034E+10 | 0.728920E+11 | 0.225057E+09 | 0.398034E+09 | 0.354117E+10 | 0.00 | 0.00 | 0.00 |
February | 0.529533E+10 | 0.846920E+11 | 0.305571E+09 | 0.111025E+10 | 0.404096E+10 | 0.00 | 0.00 | 0.00 |
March | 0.742038E+10 | 0.110267E+12 | 0.120612E+09 | 0.578871E+09 | 0.582820E+10 | 0.00 | 0.00 | 0.00 |
April | 0.868989E+10 | 0.131479E+12 | 0.00 | 25536678.53 | 0.127975E+11 | 0.00 | 0.00 | 0.00 |
May | 0.110601E+11 | 0.178238E+12 | 0.00 | 0.00 | 0.371764E+11 | 0.00 | 0.00 | 0.00 |
June | 0.115738E+11 | 0.196247E+12 | 0.00 | 0.00 | 0.615304E+11 | 0.00 | 0.00 | 0.00 |
July | 0.118614E+11 | 0.202715E+12 | 0.00 | 0.00 | 0.701461E+11 | 0.00 | 0.00 | 0.00 |
August | 0.116903E+11 | 0.202837E+12 | 0.00 | 0.00 | 0.698175E+11 | 0.00 | 0.00 | 0.00 |
September | 0.983302E+10 | 0.189559E+12 | 0.00 | 0.00 | 0.569616E+11 | 0.00 | 0.00 | 0.00 |
October | 0.834747E+10 | 0.165847E+12 | 0.00 | 165005.56 | 0.430353E+11 | 0.00 | 0.00 | 0.00 |
November | 0.657152E+10 | 0.127216E+12 | 44972176.61 | 0.157666E+09 | 0.248962E+11 | 0.00 | 0.00 | 0.00 |
December | 0.518223E+10 | 0.828684E+11 | 0.299542E+09 | 0.617811E+09 | 0.651983E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102396E+12 | 0.174486E+13 | 0.995754E+09 | 0.288833E+10 | 0.396291E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.487034E+10 | 0.728920E+11 | 0.00 | 0.00 | 0.354117E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118614E+11 | 0.202837E+12 | 0.305571E+09 | 0.111025E+10 | 0.701461E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169660E+11 | 0.791063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150893E+11 | 0.759060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166620E+11 | 0.877924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154333E+11 | 0.893993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166613E+11 | 0.113328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162313E+11 | 0.126883E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163239E+11 | 0.131710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174711E+11 | 0.144438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165833E+11 | 0.127147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170962E+11 | 0.122079E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167099E+11 | 0.105570E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167650E+11 | 0.838129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197993E+12 | 0.128717E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150893E+11 | 0.759060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174711E+11 | 0.144438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.949662E+11 | 0.339910E+12 | 0.00 | 0.00 | 0.00 | 0.332914E+09 | 0.00 | 0.00 |
February | 0.857759E+11 | 0.530005E+12 | 0.00 | 0.00 | 0.00 | 0.355443E+09 | 0.00 | 0.00 |
March | 0.949662E+11 | 0.834208E+12 | 0.00 | 0.00 | 0.00 | 0.296332E+09 | 0.00 | 0.00 |
April | 0.919028E+11 | 0.104508E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.949662E+11 | 0.359710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.919028E+11 | 0.591583E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.949662E+11 | 0.857394E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.949662E+11 | 0.109212E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.919028E+11 | 0.355933E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.949662E+11 | 0.608095E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.919028E+11 | 0.817669E+12 | 0.00 | 0.00 | 0.00 | 89835335.22 | 0.00 | 0.00 |
December | 0.949662E+11 | 0.107898E+13 | 0.00 | 0.00 | 0.00 | 70662232.63 | 0.00 | 0.00 |
Annual Sum or Average | 0.111815E+13 | 0.851068E+13 | 0.00 | 0.00 | 0.00 | 0.114519E+10 | 0.00 | 0.00 |
Minimum of Months | 0.857759E+11 | 0.339910E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.949662E+11 | 0.109212E+13 | 0.00 | 0.00 | 0.00 | 0.355443E+09 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141864E+10 | 0.585536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128136E+10 | 0.101041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141864E+10 | 0.163997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137288E+10 | 0.210033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141864E+10 | 0.699590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137288E+10 | 0.119804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141864E+10 | 0.175007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141864E+10 | 0.226740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137288E+10 | 0.702049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141864E+10 | 0.121546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137288E+10 | 0.162614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141864E+10 | 0.213384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167034E+11 | 0.169288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128136E+10 | 0.585536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141864E+10 | 0.226740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134811E+11 | 0.502432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121765E+11 | 0.924078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134811E+11 | 0.154644E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130462E+11 | 0.200259E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134811E+11 | 0.658665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130462E+11 | 0.114496E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134811E+11 | 0.167424E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134811E+11 | 0.215484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130462E+11 | 0.659516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134811E+11 | 0.115495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130462E+11 | 0.153625E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134811E+11 | 0.200134E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158729E+12 | 0.159603E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121765E+11 | 0.502432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134811E+11 | 0.215484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136885E+10 | 0.452626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123639E+10 | 0.895183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136885E+10 | 0.153235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132470E+10 | 0.200663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136885E+10 | 0.669809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132470E+10 | 0.115703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136885E+10 | 0.169014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136885E+10 | 0.216588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132470E+10 | 0.671007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136885E+10 | 0.115912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132470E+10 | 0.152247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136885E+10 | 0.196770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161172E+11 | 0.158899E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123639E+10 | 0.452626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136885E+10 | 0.216588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.725849E+10 | 18633502.86 | 0.958198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.776162E+10 | 19564592.00 | 0.107495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107206E+11 | 17584212.59 | 0.144697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120042E+11 | 339.46 | 0.168492E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113636E+11 | 0.00 | 0.184192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125004E+11 | 0.00 | 0.209250E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136679E+11 | 0.00 | 0.225873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152225E+11 | 0.00 | 0.246060E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104354E+11 | 0.00 | 0.197144E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101783E+11 | 0.00 | 0.194390E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.958390E+10 | 9696354.11 | 0.165306E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.912824E+10 | 33371783.06 | 0.132007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129825E+12 | 98850784.08 | 0.207073E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.725849E+10 | 0.00 | 0.958198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152225E+11 | 33371783.06 | 0.246060E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.547384E+11 | 0.316478E+09 | 0.778612E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.544947E+11 | 0.665681E+09 | 0.841014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.732746E+11 | 0.311851E+09 | 0.105107E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.799479E+11 | 0.00 | 0.120045E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.975241E+11 | 0.00 | 0.159385E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101106E+12 | 0.00 | 0.173728E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100461E+12 | 0.00 | 0.177501E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101615E+12 | 0.00 | 0.182867E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.855307E+11 | 0.00 | 0.172073E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.768573E+11 | 0.00 | 0.157220E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.644979E+11 | 0.110107E+09 | 0.124683E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.549945E+11 | 0.453904E+09 | 0.852869E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.945043E+12 | 0.185802E+10 | 0.161986E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.544947E+11 | 0.00 | 0.778612E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101615E+12 | 0.665681E+09 | 0.182867E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.487034E+10 | 0.225057E+09 | 0.728920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.529533E+10 | 0.305571E+09 | 0.846920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.742038E+10 | 0.120612E+09 | 0.110267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.868989E+10 | 0.00 | 0.131479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110601E+11 | 0.00 | 0.178238E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115738E+11 | 0.00 | 0.196247E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118614E+11 | 0.00 | 0.202715E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116903E+11 | 0.00 | 0.202837E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.983302E+10 | 0.00 | 0.189559E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.834747E+10 | 0.00 | 0.165847E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.657152E+10 | 44972176.61 | 0.127216E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.518223E+10 | 0.299542E+09 | 0.828684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102396E+12 | 0.995754E+09 | 0.174486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.487034E+10 | 0.00 | 0.728920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118614E+11 | 0.305571E+09 | 0.202837E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169660E+11 | 0.00 | 0.791063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150893E+11 | 0.00 | 0.759060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166620E+11 | 0.00 | 0.877924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154333E+11 | 0.00 | 0.893993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166613E+11 | 0.00 | 0.113328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162313E+11 | 0.00 | 0.126883E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163239E+11 | 0.00 | 0.131710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174711E+11 | 0.00 | 0.144438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165833E+11 | 0.00 | 0.127147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170962E+11 | 0.00 | 0.122079E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167099E+11 | 0.00 | 0.105570E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167650E+11 | 0.00 | 0.838129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197993E+12 | 0.00 | 0.128717E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150893E+11 | 0.00 | 0.759060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174711E+11 | 0.00 | 0.144438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.949662E+11 | 0.00 | 0.433552E+12 | 0.00 | 0.936421E+11 | 0.00 | 0.00 | 0.00 | 0.334413E+09 | 0.00 | 0.00 | 0.00 |
February | 0.857759E+11 | 0.00 | 0.679758E+12 | 0.00 | 0.149752E+12 | 0.00 | 0.00 | 0.00 | 0.357043E+09 | 0.00 | 0.00 | 0.00 |
March | 0.949662E+11 | 0.00 | 0.107246E+13 | 0.00 | 0.238250E+12 | 0.00 | 0.00 | 0.00 | 0.297666E+09 | 0.00 | 0.00 | 0.00 |
April | 0.919028E+11 | 0.00 | 0.136187E+13 | 0.00 | 0.316795E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.949662E+11 | 0.00 | 0.477447E+12 | 0.00 | 0.117737E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.919028E+11 | 0.00 | 0.789800E+12 | 0.00 | 0.198217E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.949662E+11 | 0.00 | 0.114760E+13 | 0.00 | 0.290210E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.949662E+11 | 0.00 | 0.145166E+13 | 0.00 | 0.359537E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.919028E+11 | 0.00 | 0.475590E+12 | 0.00 | 0.119657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.949662E+11 | 0.00 | 0.804838E+12 | 0.00 | 0.196742E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.919028E+11 | 0.00 | 0.106358E+13 | 0.00 | 0.245915E+12 | 0.00 | 0.00 | 0.00 | 90239720.47 | 0.00 | 0.00 | 0.00 |
December | 0.949662E+11 | 0.00 | 0.137549E+13 | 0.00 | 0.296514E+12 | 0.00 | 0.00 | 0.00 | 70980311.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111815E+13 | 0.00 | 0.111336E+14 | 0.00 | 0.262297E+13 | 0.00 | 0.00 | 0.00 | 0.115034E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.857759E+11 | 0.00 | 0.433552E+12 | 0.00 | 0.936421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.949662E+11 | 0.00 | 0.145166E+13 | 0.00 | 0.359537E+12 | 0.00 | 0.00 | 0.00 | 0.357043E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141864E+10 | 0.00 | 0.745129E+10 | 0.00 | 0.159593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128136E+10 | 0.00 | 0.129153E+11 | 0.00 | 0.281115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141864E+10 | 0.00 | 0.210051E+11 | 0.00 | 0.460537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137288E+10 | 0.00 | 0.272767E+11 | 0.00 | 0.627339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141864E+10 | 0.00 | 0.920995E+10 | 0.00 | 0.221405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137288E+10 | 0.00 | 0.158641E+11 | 0.00 | 0.388366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141864E+10 | 0.00 | 0.232561E+11 | 0.00 | 0.575544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141864E+10 | 0.00 | 0.300932E+11 | 0.00 | 0.741926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137288E+10 | 0.00 | 0.929236E+10 | 0.00 | 0.227187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141864E+10 | 0.00 | 0.159721E+11 | 0.00 | 0.381754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137288E+10 | 0.00 | 0.210475E+11 | 0.00 | 0.478603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141864E+10 | 0.00 | 0.271232E+11 | 0.00 | 0.578477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167034E+11 | 0.00 | 0.220507E+12 | 0.00 | 0.512185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128136E+10 | 0.00 | 0.745129E+10 | 0.00 | 0.159593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141864E+10 | 0.00 | 0.300932E+11 | 0.00 | 0.741926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.134811E+11 | 0.00 | 0.640796E+11 | 0.00 | 0.138364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121765E+11 | 0.00 | 0.118257E+12 | 0.00 | 0.258496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134811E+11 | 0.00 | 0.198170E+12 | 0.00 | 0.435257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130462E+11 | 0.00 | 0.260069E+12 | 0.00 | 0.598096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134811E+11 | 0.00 | 0.867163E+11 | 0.00 | 0.208498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130462E+11 | 0.00 | 0.151575E+12 | 0.00 | 0.370782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134811E+11 | 0.00 | 0.222428E+12 | 0.00 | 0.550040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134811E+11 | 0.00 | 0.286013E+12 | 0.00 | 0.705291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130462E+11 | 0.00 | 0.872926E+11 | 0.00 | 0.213409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134811E+11 | 0.00 | 0.151761E+12 | 0.00 | 0.362661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130462E+11 | 0.00 | 0.198915E+12 | 0.00 | 0.452899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134811E+11 | 0.00 | 0.254567E+12 | 0.00 | 0.544332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158729E+12 | 0.00 | 0.207984E+13 | 0.00 | 0.483813E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121765E+11 | 0.00 | 0.640796E+11 | 0.00 | 0.138364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134811E+11 | 0.00 | 0.286013E+12 | 0.00 | 0.705291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136885E+10 | 0.00 | 0.579054E+10 | 0.00 | 0.126428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123639E+10 | 0.00 | 0.114730E+11 | 0.00 | 0.252120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136885E+10 | 0.00 | 0.196539E+11 | 0.00 | 0.433048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132470E+10 | 0.00 | 0.260718E+11 | 0.00 | 0.600555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136885E+10 | 0.00 | 0.882048E+10 | 0.00 | 0.212239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132470E+10 | 0.00 | 0.153204E+11 | 0.00 | 0.375013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136885E+10 | 0.00 | 0.224597E+11 | 0.00 | 0.555831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136885E+10 | 0.00 | 0.287598E+11 | 0.00 | 0.710099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132470E+10 | 0.00 | 0.888402E+10 | 0.00 | 0.217395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136885E+10 | 0.00 | 0.152366E+11 | 0.00 | 0.364548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132470E+10 | 0.00 | 0.197313E+11 | 0.00 | 0.450661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136885E+10 | 0.00 | 0.250593E+11 | 0.00 | 0.538229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161172E+11 | 0.00 | 0.207261E+12 | 0.00 | 0.483617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123639E+10 | 0.00 | 0.579054E+10 | 0.00 | 0.126428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136885E+10 | 0.00 | 0.287598E+11 | 0.00 | 0.710099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127401E+10 | 0.430869E+10 | 0.00 | 0.100335E+09 | 30545461.21 | 0.00 | 0.133594E+11 | 0.00 | 0.42 |
February | 0.757249E+09 | 0.466049E+10 | 0.00 | 79123418.48 | 80047641.36 | 0.00 | 0.728800E+10 | 0.00 | 0.41 |
March | 0.445768E+09 | 0.724169E+10 | 0.00 | 70838944.19 | 72516180.95 | 0.00 | 0.825957E+10 | 0.00 | 0.41 |
April | 0.163415E+09 | 0.102966E+11 | 0.00 | 40988422.11 | 0.171543E+09 | 0.00 | 0.231757E+10 | 0.00 | 0.39 |
May | 64448516.65 | 0.262547E+11 | 0.00 | 4710588.16 | 0.419958E+09 | 0.00 | 0.184613E+09 | 0.00 | 0.41 |
June | 0.00 | 0.403019E+11 | 0.00 | 0.00 | 0.645022E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
July | 107961.58 | 0.443365E+11 | 0.00 | 689205.79 | 0.820099E+09 | 0.00 | 910049.98 | 0.00 | 0.40 |
August | 0.00 | 0.479289E+11 | 0.00 | 233193.91 | 0.799467E+09 | 0.00 | 87764.93 | 0.00 | 0.43 |
September | 2311942.01 | 0.399176E+11 | 0.00 | 2143095.57 | 0.757864E+09 | 0.00 | 36487356.30 | 0.00 | 0.43 |
October | 13946403.35 | 0.304484E+11 | 0.00 | 8065441.99 | 0.485321E+09 | 0.00 | 0.123685E+09 | 0.00 | 0.42 |
November | 0.706022E+09 | 0.191973E+11 | 0.00 | 49871683.29 | 0.287567E+09 | 0.00 | 0.362307E+10 | 0.00 | 0.43 |
December | 0.507693E+09 | 0.624120E+10 | 0.00 | 95089154.62 | 0.159793E+09 | 0.00 | 0.112708E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.393497E+10 | 0.281134E+12 | 0.00 | 0.452089E+09 | 0.472974E+10 | 0.00 | 0.464643E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.430869E+10 | 0.00 | 0.00 | 30545461.21 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.127401E+10 | 0.479289E+11 | 0.00 | 0.100335E+09 | 0.820099E+09 | 0.00 | 0.133594E+11 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239117E+10 | 0.519695E+10 | 0.00 | 59906217.56 | 0.836816E+09 | 0.00 | 0.141871E+11 | 0.00 | 0.54 |
February | 0.136353E+10 | 0.568866E+10 | 0.00 | 45837847.08 | 0.882869E+09 | 0.00 | 0.751313E+10 | 0.00 | 0.55 |
March | 0.134317E+10 | 0.836989E+10 | 0.00 | 47103018.51 | 0.399397E+10 | 0.00 | 0.993837E+10 | 0.00 | 0.63 |
April | 0.134718E+10 | 0.904004E+10 | 0.00 | 17779387.78 | 0.546812E+10 | 0.00 | 0.190538E+10 | 0.00 | 0.69 |
May | 15523869.28 | 0.174730E+11 | 0.00 | 450423.51 | 0.717096E+10 | 0.00 | 5198091.95 | 0.00 | 0.60 |
June | 0.00 | 0.228069E+11 | 0.00 | 0.00 | 0.106023E+11 | 0.00 | 0.00 | 0.00 | 0.65 |
July | 0.00 | 0.224997E+11 | 0.00 | 0.00 | 0.145677E+11 | 0.00 | 0.00 | 0.00 | 0.68 |
August | 0.00 | 0.256658E+11 | 0.00 | 0.00 | 0.146569E+11 | 0.00 | 0.00 | 0.00 | 0.71 |
September | 0.00 | 0.240125E+11 | 0.00 | 0.00 | 0.951102E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 13240378.49 | 0.189965E+11 | 0.00 | 1328960.39 | 0.966008E+10 | 0.00 | 10597644.48 | 0.00 | 0.62 |
November | 0.159849E+10 | 0.137977E+11 | 0.00 | 18519620.81 | 0.608432E+10 | 0.00 | 0.220333E+10 | 0.00 | 0.62 |
December | 0.172524E+10 | 0.634365E+10 | 0.00 | 59713002.89 | 0.598646E+10 | 0.00 | 0.133528E+11 | 0.00 | 0.63 |
Annual Sum or Average | 0.979755E+10 | 0.179891E+12 | 0.00 | 0.250638E+09 | 0.894216E+11 | 0.00 | 0.491159E+11 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.519695E+10 | 0.00 | 0.00 | 0.836816E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.239117E+10 | 0.256658E+11 | 0.00 | 59906217.56 | 0.146569E+11 | 0.00 | 0.141871E+11 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153953E+11 | 0.476087E+11 | 0.00 | 0.464019E+09 | 0.611671E+10 | 0.00 | 0.128341E+12 | 0.00 | 0.50 |
February | 0.982317E+10 | 0.519261E+11 | 0.00 | 0.335177E+09 | 0.354299E+10 | 0.00 | 0.633101E+11 | 0.00 | 0.50 |
March | 0.690386E+10 | 0.754842E+11 | 0.00 | 0.379035E+09 | 0.900588E+10 | 0.00 | 0.888691E+11 | 0.00 | 0.53 |
April | 0.375205E+10 | 0.829054E+11 | 0.00 | 0.161869E+09 | 0.162402E+11 | 0.00 | 0.190929E+11 | 0.00 | 0.53 |
May | 76737019.68 | 0.166094E+12 | 0.00 | 5126306.64 | 0.374600E+11 | 0.00 | 73022745.29 | 0.00 | 0.54 |
June | 0.00 | 0.216485E+12 | 0.00 | 0.00 | 0.507316E+11 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.212904E+12 | 0.00 | 0.00 | 0.716211E+11 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.239645E+12 | 0.00 | 0.00 | 0.561388E+11 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.230069E+12 | 0.00 | 0.00 | 0.590837E+11 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.186820E+09 | 0.180957E+12 | 0.00 | 16944369.23 | 0.421725E+11 | 0.00 | 0.220645E+09 | 0.00 | 0.53 |
November | 0.741029E+10 | 0.130313E+12 | 0.00 | 0.139077E+09 | 0.163863E+11 | 0.00 | 0.187652E+11 | 0.00 | 0.51 |
December | 0.827850E+10 | 0.553885E+11 | 0.00 | 0.413355E+09 | 0.162213E+11 | 0.00 | 0.116069E+12 | 0.00 | 0.50 |
Annual Sum or Average | 0.518268E+11 | 0.168978E+13 | 0.00 | 0.191460E+10 | 0.384721E+12 | 0.00 | 0.434741E+12 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.476087E+11 | 0.00 | 0.00 | 0.354299E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.153953E+11 | 0.239645E+12 | 0.00 | 0.464019E+09 | 0.716211E+11 | 0.00 | 0.128341E+12 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.355689E+10 | 0.435997E+10 | 0.00 | 28808375.19 | 0.734237E+09 | 0.00 | 0.835058E+10 | 0.00 | 0.46 |
February | 0.173910E+10 | 0.500374E+10 | 0.00 | 23301576.90 | 0.395462E+09 | 0.00 | 0.426812E+10 | 0.00 | 0.47 |
March | 0.151721E+10 | 0.771284E+10 | 0.00 | 27334466.17 | 0.104015E+10 | 0.00 | 0.665389E+10 | 0.00 | 0.51 |
April | 0.353824E+09 | 0.833539E+10 | 0.00 | 14319956.90 | 0.171465E+10 | 0.00 | 0.177505E+10 | 0.00 | 0.52 |
May | 4713127.82 | 0.162579E+11 | 0.00 | 636317.34 | 0.409680E+10 | 0.00 | 6868391.49 | 0.00 | 0.55 |
June | 0.00 | 0.216417E+11 | 0.00 | 0.00 | 0.573103E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.213705E+11 | 0.00 | 0.00 | 0.765658E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.235125E+11 | 0.00 | 0.00 | 0.605733E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.223659E+11 | 0.00 | 0.00 | 0.611230E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 12570579.45 | 0.167871E+11 | 0.00 | 1656155.18 | 0.419027E+10 | 0.00 | 17297154.56 | 0.00 | 0.52 |
November | 0.851544E+09 | 0.124686E+11 | 0.00 | 8892071.94 | 0.172174E+10 | 0.00 | 0.120104E+10 | 0.00 | 0.49 |
December | 0.231203E+10 | 0.518294E+10 | 0.00 | 26274428.90 | 0.167906E+10 | 0.00 | 0.806742E+10 | 0.00 | 0.47 |
Annual Sum or Average | 0.103479E+11 | 0.164999E+12 | 0.00 | 0.131223E+09 | 0.411296E+11 | 0.00 | 0.303403E+11 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 0.435997E+10 | 0.00 | 0.00 | 0.395462E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.355689E+10 | 0.235125E+11 | 0.00 | 28808375.19 | 0.765658E+10 | 0.00 | 0.835058E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106236E+10 | 0.665438E+09 | 0.00 | 3222683.24 | 0.136228E+09 | 0.00 | 0.777467E+09 | 0.00 | 0.51 |
February | 0.551391E+09 | 0.787429E+09 | 0.00 | 3224625.86 | 0.143510E+09 | 0.00 | 0.476125E+09 | 0.00 | 0.57 |
March | 0.554496E+09 | 0.118979E+10 | 0.00 | 3443434.63 | 0.638908E+09 | 0.00 | 0.657769E+09 | 0.00 | 0.68 |
April | 0.226345E+09 | 0.137980E+10 | 0.00 | 1994672.44 | 0.857640E+09 | 0.00 | 0.219285E+09 | 0.00 | 0.83 |
May | 2670965.93 | 0.308530E+10 | 0.00 | 33685.21 | 0.106760E+10 | 0.00 | 457544.25 | 0.00 | 0.82 |
June | 0.00 | 0.436598E+10 | 0.00 | 0.00 | 0.156208E+10 | 0.00 | 0.00 | 0.00 | 0.93 |
July | 0.00 | 0.441568E+10 | 0.00 | 0.00 | 0.215006E+10 | 0.00 | 0.00 | 0.00 | 0.96 |
August | 0.00 | 0.450565E+10 | 0.00 | 0.00 | 0.222086E+10 | 0.00 | 0.00 | 0.00 | 0.95 |
September | 0.00 | 0.410765E+10 | 0.00 | 0.00 | 0.146386E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
October | 2385428.77 | 0.285618E+10 | 0.00 | 150051.07 | 0.153235E+10 | 0.00 | 1098966.74 | 0.00 | 0.76 |
November | 0.335239E+09 | 0.197386E+10 | 0.00 | 1399988.55 | 0.964101E+09 | 0.00 | 0.137579E+09 | 0.00 | 0.70 |
December | 0.697070E+09 | 0.849304E+09 | 0.00 | 3889087.99 | 0.939284E+09 | 0.00 | 0.911527E+09 | 0.00 | 0.64 |
Annual Sum or Average | 0.343196E+10 | 0.301821E+11 | 0.00 | 17358228.98 | 0.136765E+11 | 0.00 | 0.318131E+10 | 0.00 | 0.77 |
Minimum of Months | 0.00 | 0.665438E+09 | 0.00 | 0.00 | 0.136228E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.106236E+10 | 0.450565E+10 | 0.00 | 3889087.99 | 0.222086E+10 | 0.00 | 0.911527E+09 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103288E+10 | 0.522820E+09 | 0.00 | 3052280.06 | 0.154365E+09 | 0.00 | 0.748820E+09 | 0.00 | 0.72 |
February | 0.522237E+09 | 0.587026E+09 | 0.00 | 2970418.84 | 0.157873E+09 | 0.00 | 0.469870E+09 | 0.00 | 0.77 |
March | 0.528469E+09 | 0.900693E+09 | 0.00 | 3350573.94 | 0.617608E+09 | 0.00 | 0.741818E+09 | 0.00 | 0.93 |
April | 0.234271E+09 | 0.105908E+10 | 0.00 | 1355264.86 | 0.838798E+09 | 0.00 | 0.172654E+09 | 0.00 | 1.10 |
May | 2442261.81 | 0.230164E+10 | 0.00 | 19807.05 | 0.108445E+10 | 0.00 | 470167.64 | 0.00 | 1.05 |
June | 0.00 | 0.310495E+10 | 0.00 | 0.00 | 0.156073E+10 | 0.00 | 0.00 | 0.00 | 1.14 |
July | 0.00 | 0.312131E+10 | 0.00 | 0.00 | 0.208822E+10 | 0.00 | 0.00 | 0.00 | 1.18 |
August | 0.00 | 0.299250E+10 | 0.00 | 0.00 | 0.223224E+10 | 0.00 | 0.00 | 0.00 | 1.15 |
September | 0.00 | 0.320799E+10 | 0.00 | 0.00 | 0.136815E+10 | 0.00 | 0.00 | 0.00 | 1.05 |
October | 2262329.94 | 0.218071E+10 | 0.00 | 95880.60 | 0.148762E+10 | 0.00 | 878149.89 | 0.00 | 0.99 |
November | 0.320904E+09 | 0.140759E+10 | 0.00 | 1006716.24 | 0.941278E+09 | 0.00 | 0.119682E+09 | 0.00 | 0.88 |
December | 0.908672E+09 | 0.538241E+09 | 0.00 | 2033665.16 | 0.970226E+09 | 0.00 | 0.511594E+09 | 0.00 | 0.84 |
Annual Sum or Average | 0.355214E+10 | 0.219245E+11 | 0.00 | 13884606.75 | 0.135015E+11 | 0.00 | 0.276579E+10 | 0.00 | 0.98 |
Minimum of Months | 0.00 | 0.522820E+09 | 0.00 | 0.00 | 0.154365E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
Maximum of Months | 0.103288E+10 | 0.320799E+10 | 0.00 | 3350573.94 | 0.223224E+10 | 0.00 | 0.748820E+09 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.609958E+09 | 0.110903E+10 | 0.00 | 10708371.83 | 83257369.29 | 0.00 | 0.220970E+10 | 0.00 | 0.80 |
February | 0.387969E+09 | 0.112990E+10 | 0.00 | 8945747.68 | 0.121994E+09 | 0.00 | 0.101409E+10 | 0.00 | 0.82 |
March | 0.460921E+09 | 0.153270E+10 | 0.00 | 6492646.47 | 0.597645E+09 | 0.00 | 0.115785E+10 | 0.00 | 0.87 |
April | 0.220706E+09 | 0.158602E+10 | 0.00 | 2341941.08 | 0.826272E+09 | 0.00 | 0.251127E+09 | 0.00 | 0.90 |
May | 2645090.59 | 0.305586E+10 | 0.00 | 35100.99 | 0.104801E+10 | 0.00 | 455717.59 | 0.00 | 0.81 |
June | 0.00 | 0.414454E+10 | 0.00 | 0.00 | 0.155454E+10 | 0.00 | 0.00 | 0.00 | 0.90 |
July | 0.00 | 0.429279E+10 | 0.00 | 0.00 | 0.213221E+10 | 0.00 | 0.00 | 0.00 | 0.94 |
August | 0.00 | 0.478953E+10 | 0.00 | 0.00 | 0.213804E+10 | 0.00 | 0.00 | 0.00 | 0.99 |
September | 0.00 | 0.520065E+10 | 0.00 | 0.00 | 0.118610E+10 | 0.00 | 0.00 | 0.00 | 0.95 |
October | 1643534.48 | 0.427643E+10 | 0.00 | 220180.03 | 0.122269E+10 | 0.00 | 2144369.59 | 0.00 | 0.99 |
November | 0.234273E+09 | 0.301520E+10 | 0.00 | 3513854.22 | 0.830453E+09 | 0.00 | 0.353376E+09 | 0.00 | 0.94 |
December | 0.511092E+09 | 0.151854E+10 | 0.00 | 9634538.32 | 0.806807E+09 | 0.00 | 0.186879E+10 | 0.00 | 0.91 |
Annual Sum or Average | 0.242921E+10 | 0.356512E+11 | 0.00 | 41892380.62 | 0.125480E+11 | 0.00 | 0.685753E+10 | 0.00 | 0.90 |
Minimum of Months | 0.00 | 0.110903E+10 | 0.00 | 0.00 | 83257369.29 | 0.00 | 0.00 | 0.00 | 0.80 |
Maximum of Months | 0.609958E+09 | 0.520065E+10 | 0.00 | 10708371.83 | 0.213804E+10 | 0.00 | 0.220970E+10 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101548E+10 | 0.719799E+09 | 0.00 | 4084906.71 | 0.163359E+09 | 0.00 | 0.125483E+10 | 0.00 | 0.93 |
February | 0.453163E+09 | 0.934558E+09 | 0.00 | 5544297.34 | 0.144537E+09 | 0.00 | 0.839100E+09 | 0.00 | 1.07 |
March | 0.360764E+09 | 0.164649E+10 | 0.00 | 6974915.94 | 0.604668E+09 | 0.00 | 0.133353E+10 | 0.00 | 1.40 |
April | 0.197700E+09 | 0.227972E+10 | 0.00 | 5073188.65 | 0.688510E+09 | 0.00 | 0.404079E+09 | 0.00 | 1.72 |
May | 3150066.67 | 0.316850E+10 | 0.00 | 48006.65 | 0.118287E+10 | 0.00 | 656309.99 | 0.00 | 1.34 |
June | 0.00 | 0.461649E+10 | 0.00 | 0.00 | 0.159633E+10 | 0.00 | 0.00 | 0.00 | 1.52 |
July | 0.00 | 0.545657E+10 | 0.00 | 0.00 | 0.195135E+10 | 0.00 | 0.00 | 0.00 | 1.68 |
August | 0.00 | 0.662479E+10 | 0.00 | 0.00 | 0.170797E+10 | 0.00 | 0.00 | 0.00 | 1.84 |
September | 0.00 | 0.421238E+10 | 0.00 | 0.00 | 0.154570E+10 | 0.00 | 0.00 | 0.00 | 1.32 |
October | 2101885.16 | 0.345439E+10 | 0.00 | 197145.81 | 0.155717E+10 | 0.00 | 2233269.53 | 0.00 | 1.36 |
November | 0.327312E+09 | 0.259201E+10 | 0.00 | 2308794.66 | 0.929825E+09 | 0.00 | 0.262300E+09 | 0.00 | 1.32 |
December | 0.390245E+09 | 0.148364E+10 | 0.00 | 8351384.59 | 0.881532E+09 | 0.00 | 0.180430E+10 | 0.00 | 1.34 |
Annual Sum or Average | 0.274992E+10 | 0.371893E+11 | 0.00 | 32582640.34 | 0.129538E+11 | 0.00 | 0.590103E+10 | 0.00 | 1.41 |
Minimum of Months | 0.00 | 0.719799E+09 | 0.00 | 0.00 | 0.144537E+09 | 0.00 | 0.00 | 0.00 | 0.93 |
Maximum of Months | 0.101548E+10 | 0.662479E+10 | 0.00 | 8351384.59 | 0.195135E+10 | 0.00 | 0.180430E+10 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136448E+11 | 0.556322E+10 | 0.00 | 11366175.92 | 0.145288E+10 | 0.00 | 0.301085E+10 | 0.00 | 0.48 |
February | 0.615174E+10 | 0.667457E+10 | 0.00 | 16205900.00 | 0.959829E+09 | 0.138899E+09 | 0.239104E+10 | 0.00 | 0.51 |
March | 0.744369E+10 | 0.106949E+11 | 0.00 | 16641624.89 | 0.145690E+10 | 0.00 | 0.303292E+10 | 0.00 | 0.55 |
April | 0.913106E+09 | 0.127687E+11 | 0.00 | 13986273.84 | 0.249081E+10 | 0.00 | 0.197826E+10 | 0.00 | 0.63 |
May | 18380162.01 | 0.304348E+11 | 0.00 | 252007.55 | 0.496404E+10 | 0.00 | 3044461.84 | 0.00 | 0.76 |
June | 0.00 | 0.443249E+11 | 0.00 | 0.00 | 0.638678E+10 | 0.00 | 0.00 | 0.00 | 0.85 |
July | 0.00 | 0.451508E+11 | 0.00 | 0.00 | 0.943914E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
August | 0.00 | 0.451056E+11 | 0.00 | 0.00 | 0.764012E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
September | 0.00 | 0.412742E+11 | 0.00 | 0.00 | 0.827993E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
October | 30149918.72 | 0.279125E+11 | 0.00 | 1865661.57 | 0.636461E+10 | 0.00 | 24484702.85 | 0.00 | 0.64 |
November | 0.241175E+10 | 0.186570E+11 | 0.00 | 6800297.59 | 0.260298E+10 | 0.00 | 0.779149E+09 | 0.00 | 0.56 |
December | 0.104907E+11 | 0.671872E+10 | 0.00 | 11944298.59 | 0.319908E+10 | 0.00 | 0.355594E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.411044E+11 | 0.295280E+12 | 0.00 | 79062239.95 | 0.552371E+11 | 0.138899E+09 | 0.147757E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.556322E+10 | 0.00 | 0.00 | 0.959829E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.136448E+11 | 0.451508E+11 | 0.00 | 16641624.89 | 0.943914E+10 | 0.138899E+09 | 0.355594E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112049E+11 | 0.438456E+10 | 0.00 | 17716322.58 | 0.223177E+10 | 0.00 | 0.603078E+10 | 0.00 | 0.74 |
February | 0.575012E+10 | 0.513759E+10 | 0.00 | 21736723.67 | 0.185813E+10 | 59079754.21 | 0.357972E+10 | 0.00 | 0.78 |
March | 0.508804E+10 | 0.953193E+10 | 0.00 | 27463682.29 | 0.171061E+10 | 0.00 | 0.706685E+10 | 0.00 | 0.86 |
April | 0.105453E+10 | 0.121496E+11 | 0.00 | 14630254.70 | 0.275151E+10 | 0.00 | 0.205116E+10 | 0.00 | 0.97 |
May | 19538221.59 | 0.248794E+11 | 0.00 | 196202.36 | 0.563407E+10 | 0.00 | 2093970.94 | 0.00 | 1.03 |
June | 0.00 | 0.352809E+11 | 0.00 | 0.00 | 0.668633E+10 | 0.00 | 0.00 | 0.00 | 1.09 |
July | 0.00 | 0.368955E+11 | 0.00 | 0.00 | 0.921237E+10 | 0.00 | 0.00 | 0.00 | 1.11 |
August | 0.00 | 0.357986E+11 | 0.00 | 0.00 | 0.892434E+10 | 0.00 | 0.00 | 0.00 | 1.06 |
September | 0.00 | 0.351797E+11 | 0.00 | 0.00 | 0.815834E+10 | 0.00 | 0.00 | 0.00 | 1.04 |
October | 32184212.61 | 0.241635E+11 | 0.00 | 1490386.17 | 0.700551E+10 | 0.00 | 22685315.49 | 0.00 | 0.92 |
November | 0.235058E+10 | 0.155212E+11 | 0.00 | 7305201.12 | 0.329314E+10 | 0.00 | 0.917751E+09 | 0.00 | 0.79 |
December | 0.104543E+11 | 0.518886E+10 | 0.00 | 8771693.38 | 0.427553E+10 | 0.00 | 0.366863E+10 | 0.00 | 0.74 |
Annual Sum or Average | 0.359541E+11 | 0.244111E+12 | 0.00 | 99310466.27 | 0.617417E+11 | 59079754.21 | 0.233397E+11 | 0.00 | 0.93 |
Minimum of Months | 0.00 | 0.438456E+10 | 0.00 | 0.00 | 0.171061E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
Maximum of Months | 0.112049E+11 | 0.368955E+11 | 0.00 | 27463682.29 | 0.921237E+10 | 59079754.21 | 0.706685E+10 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.577123E+10 | 0.110097E+11 | 0.00 | 99292800.44 | 0.483835E+09 | 0.00 | 0.213980E+11 | 0.00 | 0.82 |
February | 0.343701E+10 | 0.110426E+11 | 0.00 | 80979461.77 | 0.384735E+09 | 0.00 | 0.931300E+10 | 0.00 | 0.81 |
March | 0.400895E+10 | 0.148492E+11 | 0.00 | 54211592.65 | 0.100684E+10 | 0.00 | 0.107598E+11 | 0.00 | 0.78 |
April | 0.744654E+09 | 0.152060E+11 | 0.00 | 19683430.61 | 0.229283E+10 | 0.00 | 0.251214E+10 | 0.00 | 0.73 |
May | 14483525.88 | 0.300263E+11 | 0.00 | 298967.23 | 0.488839E+10 | 0.00 | 6726339.88 | 0.00 | 0.75 |
June | 0.00 | 0.414987E+11 | 0.00 | 0.00 | 0.657119E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
July | 0.00 | 0.435692E+11 | 0.00 | 0.00 | 0.941362E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
August | 0.00 | 0.489127E+11 | 0.00 | 0.00 | 0.686991E+10 | 0.00 | 0.00 | 0.00 | 0.85 |
September | 0.00 | 0.535976E+11 | 0.00 | 0.00 | 0.586481E+10 | 0.00 | 0.00 | 0.00 | 0.92 |
October | 23229681.06 | 0.445375E+11 | 0.00 | 3030705.61 | 0.364764E+10 | 0.00 | 41279541.02 | 0.00 | 0.93 |
November | 0.119059E+10 | 0.312291E+11 | 0.00 | 31915329.23 | 0.160889E+10 | 0.00 | 0.333117E+10 | 0.00 | 0.88 |
December | 0.405329E+10 | 0.149452E+11 | 0.00 | 82059882.83 | 0.135878E+10 | 0.00 | 0.185091E+11 | 0.00 | 0.83 |
Annual Sum or Average | 0.192434E+11 | 0.360424E+12 | 0.00 | 0.371472E+09 | 0.443915E+11 | 0.00 | 0.658712E+11 | 0.00 | 0.83 |
Minimum of Months | 0.00 | 0.110097E+11 | 0.00 | 0.00 | 0.384735E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
Maximum of Months | 0.577123E+10 | 0.535976E+11 | 0.00 | 99292800.44 | 0.941362E+10 | 0.00 | 0.213980E+11 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142678E+11 | 0.507996E+10 | 0.00 | 14383269.69 | 0.204517E+10 | 0.00 | 0.431652E+10 | 0.00 | 0.80 |
February | 0.655387E+10 | 0.657747E+10 | 0.00 | 20739681.51 | 0.105705E+10 | 3421586.85 | 0.327233E+10 | 0.00 | 0.84 |
March | 0.705897E+10 | 0.108193E+11 | 0.00 | 26429483.92 | 0.140440E+10 | 0.00 | 0.549575E+10 | 0.00 | 0.95 |
April | 0.922673E+09 | 0.140374E+11 | 0.00 | 22711245.36 | 0.223020E+10 | 0.00 | 0.228615E+10 | 0.00 | 1.06 |
May | 21056969.18 | 0.270927E+11 | 0.00 | 234253.28 | 0.529009E+10 | 0.00 | 2286017.89 | 0.00 | 1.09 |
June | 0.00 | 0.353623E+11 | 0.00 | 0.00 | 0.727440E+10 | 0.00 | 0.00 | 0.00 | 1.11 |
July | 0.00 | 0.386955E+11 | 0.00 | 0.00 | 0.974536E+10 | 0.00 | 0.00 | 0.00 | 1.17 |
August | 0.00 | 0.414355E+11 | 0.00 | 0.00 | 0.758641E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
September | 0.00 | 0.360288E+11 | 0.00 | 0.00 | 0.838428E+10 | 0.00 | 0.00 | 0.00 | 1.06 |
October | 30875987.09 | 0.258680E+11 | 0.00 | 1573495.26 | 0.697177E+10 | 0.00 | 26562596.72 | 0.00 | 0.97 |
November | 0.261636E+10 | 0.172276E+11 | 0.00 | 6284227.41 | 0.300930E+10 | 0.00 | 0.857026E+09 | 0.00 | 0.86 |
December | 0.110442E+11 | 0.727943E+10 | 0.00 | 13554242.24 | 0.338991E+10 | 0.00 | 0.446195E+10 | 0.00 | 0.83 |
Annual Sum or Average | 0.425158E+11 | 0.265504E+12 | 0.00 | 0.105910E+09 | 0.583884E+11 | 3421586.85 | 0.207186E+11 | 0.00 | 0.99 |
Minimum of Months | 0.00 | 0.507996E+10 | 0.00 | 0.00 | 0.105705E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
Maximum of Months | 0.142678E+11 | 0.414355E+11 | 0.00 | 26429483.92 | 0.974536E+10 | 3421586.85 | 0.549575E+10 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142421E+10 | 0.423081E+09 | 0.00 | 727159.81 | 0.298024E+09 | 28478771.55 | 0.184349E+09 | 0.00 | 0.51 |
February | 0.608663E+09 | 0.602737E+09 | 0.00 | 1188240.00 | 0.181396E+09 | 37651176.63 | 0.179306E+09 | 0.00 | 0.52 |
March | 0.775654E+09 | 0.104421E+10 | 0.00 | 1389809.78 | 0.257294E+09 | 15045066.21 | 0.260950E+09 | 0.00 | 0.57 |
April | 0.115936E+09 | 0.123842E+10 | 0.00 | 1279700.77 | 0.358072E+09 | 0.00 | 0.175147E+09 | 0.00 | 0.64 |
May | 1441518.93 | 0.296539E+10 | 0.00 | 22025.63 | 0.606164E+09 | 0.00 | 286541.40 | 0.00 | 0.77 |
June | 0.00 | 0.437967E+10 | 0.00 | 0.00 | 0.796397E+09 | 0.00 | 0.00 | 0.00 | 0.87 |
July | 0.00 | 0.448676E+10 | 0.00 | 0.00 | 0.106643E+10 | 0.00 | 0.00 | 0.00 | 0.87 |
August | 0.00 | 0.441722E+10 | 0.00 | 0.00 | 0.890207E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
September | 0.00 | 0.405916E+10 | 0.00 | 0.00 | 0.913522E+09 | 0.00 | 0.00 | 0.00 | 0.79 |
October | 2130961.11 | 0.256600E+10 | 0.00 | 175230.80 | 0.785764E+09 | 0.00 | 2263713.67 | 0.00 | 0.66 |
November | 0.219779E+09 | 0.173237E+10 | 0.00 | 462439.79 | 0.412876E+09 | 293275.46 | 70043769.78 | 0.00 | 0.57 |
December | 0.111369E+10 | 0.597107E+09 | 0.00 | 728394.77 | 0.438426E+09 | 60515113.44 | 0.211287E+09 | 0.00 | 0.52 |
Annual Sum or Average | 0.426151E+10 | 0.285121E+11 | 0.00 | 5973001.36 | 0.700457E+10 | 0.141983E+09 | 0.108363E+10 | 0.00 | 0.68 |
Minimum of Months | 0.00 | 0.423081E+09 | 0.00 | 0.00 | 0.181396E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.142421E+10 | 0.448676E+10 | 0.00 | 1389809.78 | 0.106643E+10 | 60515113.44 | 0.260950E+09 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.959890E+09 | 0.396027E+09 | 0.00 | 1457650.70 | 0.261899E+09 | 13286287.89 | 0.557403E+09 | 0.00 | 0.73 |
February | 0.491497E+09 | 0.481586E+09 | 0.00 | 2003863.16 | 0.227705E+09 | 19395832.09 | 0.306210E+09 | 0.00 | 0.77 |
March | 0.395654E+09 | 0.935527E+09 | 0.00 | 2555128.87 | 0.251828E+09 | 9711198.27 | 0.692769E+09 | 0.00 | 0.86 |
April | 92308717.17 | 0.118750E+10 | 0.00 | 1563859.60 | 0.338212E+09 | 0.00 | 0.209072E+09 | 0.00 | 0.97 |
May | 1398320.67 | 0.243041E+10 | 0.00 | 20554.54 | 0.619679E+09 | 0.00 | 207969.62 | 0.00 | 1.04 |
June | 0.00 | 0.354144E+10 | 0.00 | 0.00 | 0.733583E+09 | 0.00 | 0.00 | 0.00 | 1.12 |
July | 0.00 | 0.373393E+10 | 0.00 | 0.00 | 0.927023E+09 | 0.00 | 0.00 | 0.00 | 1.14 |
August | 0.00 | 0.351302E+10 | 0.00 | 0.00 | 0.967523E+09 | 0.00 | 0.00 | 0.00 | 1.08 |
September | 0.00 | 0.349071E+10 | 0.00 | 0.00 | 0.836471E+09 | 0.00 | 0.00 | 0.00 | 1.06 |
October | 2117815.08 | 0.227028E+10 | 0.00 | 166182.10 | 0.747391E+09 | 0.00 | 2225507.69 | 0.00 | 0.94 |
November | 0.180473E+09 | 0.145317E+10 | 0.00 | 616029.82 | 0.433749E+09 | 0.00 | 93245299.60 | 0.00 | 0.79 |
December | 0.946080E+09 | 0.452392E+09 | 0.00 | 724206.78 | 0.489224E+09 | 44894761.42 | 0.287886E+09 | 0.00 | 0.74 |
Annual Sum or Average | 0.306942E+10 | 0.238860E+11 | 0.00 | 9107475.59 | 0.683429E+10 | 87288079.67 | 0.214902E+10 | 0.00 | 0.94 |
Minimum of Months | 0.00 | 0.396027E+09 | 0.00 | 0.00 | 0.227705E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
Maximum of Months | 0.959890E+09 | 0.373393E+10 | 0.00 | 2555128.87 | 0.967523E+09 | 44894761.42 | 0.692769E+09 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.615521E+09 | 0.106039E+10 | 0.00 | 8413912.40 | 85565095.26 | 0.00 | 0.201917E+10 | 0.00 | 0.83 |
February | 0.332420E+09 | 0.104781E+10 | 0.00 | 7023398.51 | 70261615.86 | 21929375.99 | 0.869284E+09 | 0.00 | 0.81 |
March | 0.456078E+09 | 0.152588E+10 | 0.00 | 5101799.01 | 0.134585E+09 | 4850905.69 | 0.100734E+10 | 0.00 | 0.78 |
April | 99005852.05 | 0.151681E+10 | 0.00 | 1863594.30 | 0.290503E+09 | 0.00 | 0.234307E+09 | 0.00 | 0.74 |
May | 1445774.70 | 0.291273E+10 | 0.00 | 28378.13 | 0.623732E+09 | 0.00 | 288704.70 | 0.00 | 0.76 |
June | 0.00 | 0.408458E+10 | 0.00 | 0.00 | 0.849400E+09 | 0.00 | 0.00 | 0.00 | 0.83 |
July | 0.00 | 0.430480E+10 | 0.00 | 0.00 | 0.111045E+10 | 0.00 | 0.00 | 0.00 | 0.85 |
August | 0.00 | 0.476371E+10 | 0.00 | 0.00 | 0.837552E+09 | 0.00 | 0.00 | 0.00 | 0.87 |
September | 0.00 | 0.518693E+10 | 0.00 | 0.00 | 0.731404E+09 | 0.00 | 0.00 | 0.00 | 0.94 |
October | 2074751.17 | 0.416083E+10 | 0.00 | 307494.69 | 0.466003E+09 | 0.00 | 3088413.68 | 0.00 | 0.95 |
November | 95263453.84 | 0.301503E+10 | 0.00 | 2611691.34 | 0.217931E+09 | 0.00 | 0.329913E+09 | 0.00 | 0.88 |
December | 0.476317E+09 | 0.140841E+10 | 0.00 | 7413458.97 | 0.194163E+09 | 291877.81 | 0.169252E+10 | 0.00 | 0.84 |
Annual Sum or Average | 0.207813E+10 | 0.349879E+11 | 0.00 | 32763727.36 | 0.561155E+10 | 27072159.49 | 0.615590E+10 | 0.00 | 0.84 |
Minimum of Months | 0.00 | 0.104781E+10 | 0.00 | 0.00 | 70261615.86 | 0.00 | 0.00 | 0.00 | 0.74 |
Maximum of Months | 0.615521E+09 | 0.518693E+10 | 0.00 | 8413912.40 | 0.111045E+10 | 21929375.99 | 0.201917E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139828E+10 | 0.407454E+09 | 0.00 | 1202307.35 | 0.334502E+09 | 6809912.42 | 0.372089E+09 | 0.00 | 0.84 |
February | 0.590770E+09 | 0.588379E+09 | 0.00 | 1858275.06 | 0.204963E+09 | 33178566.16 | 0.291189E+09 | 0.00 | 0.86 |
March | 0.701237E+09 | 0.107428E+10 | 0.00 | 2713231.75 | 0.228238E+09 | 290498.95 | 0.527384E+09 | 0.00 | 0.96 |
April | 0.100780E+09 | 0.138190E+10 | 0.00 | 2347591.81 | 0.302361E+09 | 0.00 | 0.222384E+09 | 0.00 | 1.06 |
May | 1612299.06 | 0.261231E+10 | 0.00 | 19960.55 | 0.657498E+09 | 0.00 | 222441.13 | 0.00 | 1.11 |
June | 0.00 | 0.346428E+10 | 0.00 | 0.00 | 0.899796E+09 | 0.00 | 0.00 | 0.00 | 1.14 |
July | 0.00 | 0.377719E+10 | 0.00 | 0.00 | 0.111867E+10 | 0.00 | 0.00 | 0.00 | 1.20 |
August | 0.00 | 0.393535E+10 | 0.00 | 0.00 | 0.959198E+09 | 0.00 | 0.00 | 0.00 | 1.18 |
September | 0.00 | 0.345645E+10 | 0.00 | 0.00 | 0.102852E+10 | 0.00 | 0.00 | 0.00 | 1.10 |
October | 2404619.78 | 0.239467E+10 | 0.00 | 147306.44 | 0.818127E+09 | 0.00 | 2059653.22 | 0.00 | 1.00 |
November | 0.227082E+09 | 0.159152E+10 | 0.00 | 505630.83 | 0.469494E+09 | 0.00 | 87084400.19 | 0.00 | 0.87 |
December | 0.114796E+10 | 0.657323E+09 | 0.00 | 1070401.05 | 0.444857E+09 | 8159285.51 | 0.336858E+09 | 0.00 | 0.87 |
Annual Sum or Average | 0.417013E+10 | 0.253411E+11 | 0.00 | 9864704.84 | 0.746623E+10 | 48438263.04 | 0.183927E+10 | 0.00 | 1.02 |
Minimum of Months | 0.00 | 0.407454E+09 | 0.00 | 0.00 | 0.204963E+09 | 0.00 | 0.00 | 0.00 | 0.84 |
Maximum of Months | 0.139828E+10 | 0.393535E+10 | 0.00 | 2713231.75 | 0.111867E+10 | 33178566.16 | 0.527384E+09 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.145122E+09 | 0.00 | 6078022.07 | 0.00 | 0.00 | 0.269753E+09 | 0.00 | 0.58 |
February | 0.00 | 0.191723E+09 | 0.00 | 9676403.93 | 0.00 | 0.00 | 0.170687E+09 | 0.00 | 0.58 |
March | 0.00 | 0.324495E+09 | 0.00 | 12782570.65 | 0.00 | 0.00 | 0.161845E+09 | 0.00 | 0.58 |
April | 0.00 | 0.423075E+09 | 0.00 | 7002465.94 | 0.00 | 0.00 | 29594997.57 | 0.00 | 0.58 |
May | 0.00 | 0.723540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.105350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.116236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.119882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.944246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.853120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.575851E+09 | 0.00 | 7952612.68 | 0.00 | 0.00 | 60518560.97 | 0.00 | 0.58 |
December | 0.00 | 0.315160E+09 | 0.00 | 18778439.10 | 0.00 | 0.00 | 0.174316E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.791102E+10 | 0.00 | 62270514.37 | 0.00 | 0.00 | 0.866715E+09 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.145122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.119882E+10 | 0.00 | 18778439.10 | 0.00 | 0.00 | 0.269753E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.139398E+10 | 0.00 | 49249841.01 | 0.00 | 0.00 | 0.273338E+10 | 0.00 | 0.58 |
February | 0.00 | 0.190076E+10 | 0.00 | 86434346.37 | 0.00 | 0.00 | 0.171493E+10 | 0.00 | 0.58 |
March | 0.00 | 0.324451E+10 | 0.00 | 0.118660E+09 | 0.00 | 0.00 | 0.162265E+10 | 0.00 | 0.58 |
April | 0.00 | 0.423967E+10 | 0.00 | 66603189.69 | 0.00 | 0.00 | 0.296946E+09 | 0.00 | 0.58 |
May | 0.00 | 0.715738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.105073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.116151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.120008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.934260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.850344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.575280E+10 | 0.00 | 73378931.81 | 0.00 | 0.00 | 0.609316E+09 | 0.00 | 0.58 |
December | 0.00 | 0.315423E+10 | 0.00 | 0.174244E+09 | 0.00 | 0.00 | 0.174897E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.788126E+11 | 0.00 | 0.568571E+09 | 0.00 | 0.00 | 0.872619E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.139398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.120008E+11 | 0.00 | 0.174244E+09 | 0.00 | 0.00 | 0.273338E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.136304E+09 | 0.00 | 3929257.53 | 0.00 | 0.00 | 0.277709E+09 | 0.00 | 0.58 |
February | 0.00 | 0.189189E+09 | 0.00 | 8031194.73 | 0.00 | 0.00 | 0.172588E+09 | 0.00 | 0.58 |
March | 0.00 | 0.323769E+09 | 0.00 | 11503010.48 | 0.00 | 0.00 | 0.162947E+09 | 0.00 | 0.58 |
April | 0.00 | 0.423141E+09 | 0.00 | 6612978.46 | 0.00 | 0.00 | 29845806.11 | 0.00 | 0.58 |
May | 0.00 | 0.717521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.105097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.116122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.120015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.936404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.849585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.574183E+09 | 0.00 | 7030185.12 | 0.00 | 0.00 | 61395832.08 | 0.00 | 0.58 |
December | 0.00 | 0.314488E+09 | 0.00 | 16800937.15 | 0.00 | 0.00 | 0.176046E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.787692E+10 | 0.00 | 53907563.45 | 0.00 | 0.00 | 0.880532E+09 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.136304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.120015E+10 | 0.00 | 16800937.15 | 0.00 | 0.00 | 0.277709E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.368286E+10 | 0.00 | 0.327815E+09 | 0.00 | 0.00 | 0.594559E+10 | 0.00 | 0.66 |
February | 0.00 | 0.434095E+10 | 0.00 | 0.480943E+09 | 0.00 | 0.00 | 0.385321E+10 | 0.00 | 0.66 |
March | 0.00 | 0.708069E+10 | 0.00 | 0.615183E+09 | 0.00 | 0.00 | 0.356080E+10 | 0.00 | 0.66 |
April | 0.00 | 0.838580E+10 | 0.00 | 0.318417E+09 | 0.00 | 0.00 | 0.532231E+09 | 0.00 | 0.66 |
May | 0.00 | 0.172470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
June | 0.00 | 0.236666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
July | 0.00 | 0.255362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
August | 0.00 | 0.225803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.223413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
October | 0.00 | 0.191713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
November | 0.00 | 0.126337E+11 | 0.00 | 0.371494E+09 | 0.00 | 0.00 | 0.124171E+10 | 0.00 | 0.66 |
December | 0.00 | 0.649631E+10 | 0.00 | 0.885541E+09 | 0.00 | 0.00 | 0.354641E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.173163E+12 | 0.00 | 0.299939E+10 | 0.00 | 0.00 | 0.186800E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.368286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.255362E+11 | 0.00 | 0.885541E+09 | 0.00 | 0.00 | 0.594559E+10 | 0.00 | 0.66 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:03:32
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.372547E+12 | 0.335503E+10 | 0.00 | 0.349476E+12 | 0.182704E+13 |
February | 0.394461E+12 | 0.353168E+10 | 0.00 | 0.138271E+12 | 0.217610E+13 |
March | 0.543118E+12 | 0.299234E+09 | 0.00 | -0.364967E+11 | 0.308780E+13 |
April | 0.588124E+12 | -0.380024E+10 | 0.00 | -0.402070E+12 | 0.366179E+13 |
May | 0.559068E+12 | -0.156703E+11 | 0.00 | -0.124123E+13 | 0.321131E+13 |
June | 0.500651E+12 | -0.177243E+11 | 0.00 | -0.184960E+13 | 0.375990E+13 |
July | 0.546329E+12 | -0.161154E+11 | 0.00 | -0.201996E+13 | 0.426322E+13 |
August | 0.598749E+12 | -0.187438E+11 | 0.00 | -0.206333E+13 | 0.476585E+13 |
September | 0.447769E+12 | -0.169920E+11 | 0.00 | -0.182436E+13 | 0.329283E+13 |
October | 0.450194E+12 | -0.140415E+11 | 0.00 | -0.143667E+13 | 0.358056E+13 |
November | 0.330222E+12 | -0.461759E+10 | 0.00 | -0.705406E+12 | 0.346115E+13 |
December | 0.356906E+12 | -96695000.2 | 0.00 | 0.160488E+11 | 0.320324E+13 |
Annual Sum or Average | 0.568814E+13 | -0.100616E+12 | 0.00 | -0.110753E+14 | 0.402908E+14 |
Minimum of Months | 0.330222E+12 | -0.187438E+11 | 0.00 | -0.206333E+13 | 0.182704E+13 |
Maximum of Months | 0.598749E+12 | 0.353168E+10 | 0.00 | 0.349476E+12 | 0.476585E+13 |