Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 09:03:10
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 32924.69 | 710.80 | 710.80 |
Net Site Energy | 32924.69 | 710.80 | 710.80 |
Total Source Energy | 101413.21 | 2189.39 | 2189.39 |
Net Source Energy | 101413.21 | 2189.39 | 2189.39 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 679.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4091.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3702.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 670.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1941.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3008.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 617.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1157.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6921.82 |
Humidification | 1149.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.69 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 692.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31552.01 | 1372.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9629.69 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 679.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 4091.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3702.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 670.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 3008.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 617.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1157.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6921.82 |
Humidification | General | 1149.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.69 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 692.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 679.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 4091.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3702.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 670.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1941.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 3008.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 617.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1157.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6921.82 |
Humidification | Unassigned | 1149.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.69 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 692.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 216.40 | 29.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Other | 370.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 681.17 | 29.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 216.40 | 29.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Other | 370.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 681.17 | 29.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31552.012 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31552.012 | 100.00 |
Total On-Site and Utility Electric Sources | 31552.012 | 100.00 |
Total Electricity End Uses | 31552.012 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9629.69 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9629.69 | 100.00 |
Total Water End Uses | 9629.69 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 8.67 |
Time Setpoint Not Met During Occupied Cooling | 1543.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.3279 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.3279 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.3279 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.3279 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 9.3279 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.3279 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 9.3279 | 18.58 | 484.4232 | |
Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.8860 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-15:00 | 06-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 28-JUN-16:19 |
Heating | 0.00 | 753815.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 433145.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84885.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 294086.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 60084.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 82925.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 35907.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29467.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2101855.59 | 783282.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 753815.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 433145.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5451.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 294086.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 60084.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 82925.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 35907.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 29467.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 736.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12956.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11724.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2124.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6150.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9527.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1955.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3665.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 751.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 99925.22 | 1487.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 279.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 253.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 205.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 42.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 79.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 78.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2157.26 | 32.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 279.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 253.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 205.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 42.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 79.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 78.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2157.26 | 32.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.99 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.594499 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.68 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.580265 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 26.05 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.27 | 0.261609 | 0.300000 | 2.18 | 0.697624 | 0.500000 | 0.001456 | 0.000158 | 2.18 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 68.39 | 0.278112 | 0.300000 | 20.52 | 0.741632 | 0.500000 | 0.001370 | 0.003702 | 20.52 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.75 | 0.281982 | 0.304000 | 2.05 | 0.751953 | 0.500000 | 0.001351 | 0.000719 | 2.97 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.23 | 0.194401 | 0.300000 | 0.368548 | 0.518404 | 0.500000 | 0.001960 | 0.000093 | 0.387034 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.41 | 0.109116 | 0.300000 | 0.423140 | 0.300000 | 0.500000 | 0.003492 | 0.000077 | 0.423140 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.50 | 0.159739 | 0.300000 | 0.448530 | 0.425970 | 0.500000 | 0.002385 | 0.000113 | 0.465923 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.78 | 0.086645 | 0.300000 | 0.532883 | 0.300000 | 0.500000 | 0.004397 | 0.000071 | 0.532883 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 11.62 | 0.205606 | 0.300000 | 3.48 | 0.548281 | 0.500000 | 0.001853 | 0.001788 | 7.41 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 14.83 | 0.103752 | 0.300000 | 4.45 | 0.300000 | 0.500000 | 0.003672 | 0.001186 | 4.92 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.39 | 0.165989 | 0.300000 | 4.32 | 0.442636 | 0.500000 | 0.002295 | 0.001772 | 7.35 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 15.96 | 0.096427 | 0.300000 | 4.79 | 0.300000 | 0.500000 | 0.003951 | 0.001131 | 4.79 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.33 | 0.179059 | 0.300000 | 0.400126 | 0.477491 | 0.500000 | 0.002128 | 0.000234 | 0.972598 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.50 | 0.102320 | 0.300000 | 0.451245 | 0.300000 | 0.500000 | 0.003724 | 0.000155 | 0.641794 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.60 | 0.149555 | 0.300000 | 0.479074 | 0.398812 | 0.500000 | 0.002548 | 0.000233 | 0.964580 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.71 | 0.089843 | 0.300000 | 0.513911 | 0.300000 | 0.500000 | 0.004241 | 0.000150 | 0.620724 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18063.21 | 0.000158 | 364.14 |
CORE_MID VAV BOX REHEAT COIL | 423150.01 | 0.003702 | 10022.42 |
CORE_TOP VAV BOX REHEAT COIL | 82180.72 | 0.000719 | 2169.11 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10686.45 | 0.000093 | 282.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8800.18 | 0.000077 | 208.96 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12859.68 | 0.000113 | 339.29 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8081.04 | 0.000071 | 177.52 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 204364.43 | 0.001788 | 5389.10 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 135620.65 | 0.001186 | 3576.23 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 202605.99 | 0.001772 | 5342.77 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 129313.48 | 0.001131 | 3378.90 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 26802.04 | 0.000234 | 706.64 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 17685.41 | 0.000155 | 466.27 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 26581.38 | 0.000233 | 700.82 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 17105.40 | 0.000150 | 450.98 |
VAV_BOT WITH REHEAT HEATING COIL | 50965.82 | 0.000446 | 847.17 |
VAV_MID WITH REHEAT HEATING COIL | 444544.66 | 0.003889 | 7429.38 |
VAV_TOP WITH REHEAT HEATING COIL | 43323.50 | 0.000379 | 730.72 |
CAV_BAS HEATING COIL | 287807.63 | 0.002518 | 6382.65 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.59 | 3.95 | 13.18 | 3.95 | 11.87 | 11.87 | 0.300000 | 0.333160 | 11.87 |
VAV_MID WITH REHEAT | 62.59 | 37.56 | 125.19 | 37.56 | 110.57 | 110.57 | 0.300000 | 0.339670 | 110.57 |
VAV_TOP WITH REHEAT | 6.45 | 3.89 | 12.89 | 6.17 | 12.12 | 12.12 | 0.300000 | 0.509318 | 12.12 |
CAV_BAS | 6.99 | 6.99 | 6.99 | 6.99 | 6.99 | 6.99 | 1.00 | 1.00 | 6.99 |
AIRLOOP DATACENTER BASEMENT | 26.05 | 26.05 | 26.05 | 26.05 | 26.05 | 26.05 | 1.00 | 0.999987 | 26.05 |
AIRLOOP DATACENTER BOT | 0.594499 | 0.594499 | 0.594499 | 0.594499 | 0.594499 | 0.594499 | 1.00 | 1.00 | 0.594499 |
AIRLOOP DATACENTER MID | 5.68 | 5.68 | 5.68 | 5.68 | 5.68 | 5.68 | 1.00 | 1.00 | 5.68 |
AIRLOOP DATACENTER TOP | 0.580265 | 0.580265 | 0.580265 | 0.580265 | 0.580265 | 0.580265 | 1.00 | 1.00 | 0.580265 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 11.87 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 110.57 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 12.12 | |
CAV_BAS_OA_CONTROLLER | 6.99 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 26.05 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.594499 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.68 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.580265 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.34 | 6.67 | 10.67 | 0.006980 | 0.006980 | 187518.64 | 0.007977 | 11.87 |
VAV_MID WITH REHEAT COOLING COIL | 26.67 | 6.67 | 10.67 | 0.006945 | 0.006945 | 1783963.62 | 0.075894 | 110.57 |
VAV_TOP WITH REHEAT COOLING COIL | 26.33 | 6.67 | 10.67 | 0.006952 | 0.006952 | 191412.14 | 0.008143 | 12.12 |
CAV_BAS COOLING COIL | 25.77 | 6.67 | 11.13 | 0.007136 | 0.007136 | 103262.48 | 0.004393 | 6.99 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 11.87 |
VAV_MID WITH REHEAT FAN | 110.57 |
VAV_TOP WITH REHEAT FAN | 12.12 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007977 | 0.000060 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000446 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.075894 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.003889 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.008143 | 0.000058 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000379 | |
CAV_BAS_COOLC_CONTROLLER | 0.004393 | 0.000108 |
CAV_BAS_HEATC_CONTROLLER | 0.002518 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.99 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 26.05 | 476903.19 | 252970.44 | 0.011679 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.594499 | 10601.48 | 5675.28 | 0.000260 |
AIRLOOP DATACENTER MID COOLING COIL | 5.68 | 101351.39 | 54241.81 | 0.002482 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.580265 | 10350.51 | 5540.10 | 0.000253 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 26.05 | 26.05 | 26.05 | 26.05 | 476903.19 | 476903.19 | 16131.55 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.594499 | 0.594499 | 0.594499 | 0.594499 | 10601.48 | 10601.48 | 745.21 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.68 | 5.68 | 5.68 | 5.68 | 101351.39 | 101351.39 | 7452.11 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.580265 | 0.580265 | 0.580265 | 0.580265 | 10350.51 | 10350.51 | 745.21 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 26.05 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.594499 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.68 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.580265 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 26.05 | 476903.19 | 0.011679 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.594499 | 10601.48 | 0.000260 |
AIRLOOP DATACENTER MID HEATING COIL | 5.68 | 101351.39 | 0.002482 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.580265 | 10350.51 | 0.000253 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 16131.55 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 745.21 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 7452.11 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 745.21 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000141 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.096408 | 19866.02 | |
HEATSYS1 PUMP | 0.018814 | 5665.91 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.096408 | 11.57 |
HEATSYS1 | 0.018814 | 2.26 |
COOLSYS1_SUPPLY | 0.096408 | 11.57 |
SINGLE WATER PLANT LOOP | 0.014675 | 1.76 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.096408 | 0.096408 | 404670.87 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2150541.67 | 2150541.67 | 0.018814 |
CENTRAL BOILER | 604464.85 | 590854.07 | 0.014675 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.096408 | 13753.92 |
PLANT CIRC PUMP | 0.014675 | 3742.74 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.096408 | 0.048938 | 1153160.52 | 1158629.75 | 0.057336 |
COOLSYS1 CHILLER2 | 0.096408 | 0.048938 | 1153160.52 | 1158629.75 | 0.057336 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014675 | 139666.47 | 54810.55 | 69833.23 | 7879.72 | 20939.09 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.114673 | 13.76 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.114673 | 34536.89 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 53.88 | 1376422.51 | 10.78 | 172052.81 |
TOWERWATERSYS COOLTOWER 2 | 53.88 | 1376422.51 | 10.78 | 172052.81 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.059555 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.328 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 14.170 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 9.328 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.751 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 25926.330 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25926.330 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 7310.116 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7310.116 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.339 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.260 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.694 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5795 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6262 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4230 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.13684007E-14 | 0.43769670E-16 | -0.13032795E-09 | -0.34517937E-17 |
51 | 8 | 0.19139952E-07 | 0.17580734E-12 | 0.34842432E-03 | -0.21762784E-09 |
52 | 7 | -0.11363040E-01 | 0.94207812E-08 | -0.21820187E-01 | 0.12920189E-03 |
53 | 6 | 0.38147639 | 0.33245073E-05 | 0.45170425 | -0.44663469E-02 |
54 | 5 | -4.9575440 | 0.12566514E-03 | -4.2844407 | 0.60294545E-01 |
55 | 4 | 31.971915 | 0.10393916E-02 | 20.826829 | -0.40843520 |
56 | 3 | -109.03212 | 0.22875987E-02 | -54.410870 | 1.4834967 |
57 | 2 | 194.95586 | 0.12980373E-02 | 76.763178 | -2.8661744 |
58 | 1 | -170.36074 | 0.13969006E-03 | -54.933270 | 2.7315001 |
59 | 0 | 57.057407 | 0.80219562E-06 | 15.613236 | |
60 | 9 | 0.17296484E-14 | 0.42300129E-16 | -0.13408130E-09 | -0.44058463E-17 |
61 | 8 | 0.19671007E-07 | 0.16641005E-12 | 0.35423406E-03 | -0.22366611E-09 |
62 | 7 | -0.11537194E-01 | 0.88593938E-08 | -0.22071206E-01 | 0.13118209E-03 |
63 | 6 | 0.38620962 | 0.31182457E-05 | 0.45575528 | -0.45221398E-02 |
64 | 5 | -5.0037487 | 0.11760487E-03 | -4.3156427 | 0.60867449E-01 |
65 | 4 | 32.176377 | 0.97077592E-03 | 20.948989 | -0.41114975 |
66 | 3 | -109.46738 | 0.21328008E-02 | -54.652468 | 1.4897847 |
67 | 2 | 195.38754 | 0.12083052E-02 | 76.984396 | -2.8730290 |
68 | 1 | -170.52030 | 0.12984550E-03 | -54.996922 | 2.7342967 |
69 | 0 | 57.057407 | 0.74448799E-06 | 15.602172 | |
70 | 9 | 0.10997584E-14 | 0.53843923E-16 | -0.11326114E-09 | -0.28570046E-17 |
71 | 8 | 0.16725364E-07 | 0.21557791E-12 | 0.32127585E-03 | -0.19017314E-09 |
72 | 7 | -0.10546704E-01 | 0.11930081E-07 | -0.20642631E-01 | 0.11991984E-03 |
73 | 6 | 0.35928609 | 0.42648229E-05 | 0.43264702 | -0.42047803E-02 |
74 | 5 | -4.7408821 | 0.16300219E-03 | -4.1373754 | 0.57608138E-01 |
75 | 4 | 31.012880 | 0.13615538E-02 | 20.250423 | -0.39570291 |
76 | 3 | -106.98970 | 0.30226891E-02 | -53.270634 | 1.4539929 |
77 | 2 | 192.92930 | 0.17282771E-02 | 75.720319 | -2.8339965 |
78 | 1 | -169.61128 | 0.18730106E-03 | -54.635416 | 2.7183650 |
79 | 0 | 57.057407 | 0.10839563E-05 | 15.666826 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8699E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8719E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2903E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2919E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5637E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5650E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9650E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9658E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9147E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0483E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3281E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4448E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5962E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6927E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9845E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0341E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1329 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5380E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1506 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2948E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1004 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.0390E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1298E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4495E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9166E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0569E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3300E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4535E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5979E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6989E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9850E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0355E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8697E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8717E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2901E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2918E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5636E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5649E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9650E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9657E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2525E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5002E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0118E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2784E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8669E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9825E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3625E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3966E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8307E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4657E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4844E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2104E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0816E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1354E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2472E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5878E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1800E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2710E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9186E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9845E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8302E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8559E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3626E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3972E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0160E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0179E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7144E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7159E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5167E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5178E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9651E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9658E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0576E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1661E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7481E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8334E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5437E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6036E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9850E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0356E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2143E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8612E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4855E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4104E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4980E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.9299E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1298E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4491E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0565E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1634E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7470E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8307E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5424E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5998E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9846E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0341E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0159E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0178E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7144E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7158E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5166E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5177E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9650E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9657E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1059E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1974E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8266E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8928E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7682E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7936E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3627E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3972E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6869E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4084E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.3078E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1400E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9532E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0837E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2472E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5878E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1758E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4132E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9166E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1704E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8044E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9181E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3624E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3966E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1211 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 8.3746E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1324 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.2470E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1037 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.5367E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.7714E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.3115E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5669E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4075E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1902E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1044E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.7738E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9901E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8823E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3360E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8423E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7137E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0490E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1421E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0556E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6652E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7714E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3111E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.4109E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3324E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.9983E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0119E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6358E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9248E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8823E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3360E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1210 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 8.3866E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1323 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.2614E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1038 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.5480E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.7768E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.3160E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5637E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4104E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1883E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.1074E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.7756E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9952E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8875E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3404E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8374E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7148E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0456E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1430E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0571E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6677E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7768E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3156E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.4077E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3352E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.9964E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0147E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6376E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9298E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8875E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3404E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 79604.52996 | 79604.52996 | 6.99271 | 6.99271 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | -7.90000 | 2.34317E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 82778.31525 | 82778.31525 | 7.27056 | 7.27056 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 778826.36161 | 778826.36161 | 68.39132 | 68.39132 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 253236.48383 | 253236.48383 | 12.99806 | 12.99806 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 76812.96461 | 76812.96461 | 6.74526 | 6.74526 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 57544.02644 | 57544.02644 | 2.97493 | 2.97493 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13869.08762 | 13869.08762 | 1.22849 | 1.22849 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 7484.89292 | 7484.89292 | 0.38703 | 0.38703 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15923.64388 | 15923.64388 | 1.41047 | 1.41047 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.67500 | 5.68796E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 5299.36933 | 5299.36933 | 0.27414 | 0.27414 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 16879.02012 | 16879.02012 | 1.49510 | 1.49510 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 34.65000 | 5.69869E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 9004.20583 | 9004.20583 | 0.46592 | 0.46592 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20053.53768 | 20053.53768 | 1.77628 | 1.77628 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 3676.39126 | 3676.39126 | 0.18977 | 0.18977 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 131135.15234 | 131135.15234 | 11.61547 | 11.61547 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 143027.24814 | 143027.24814 | 7.41290 | 7.41290 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 167471.86905 | 167471.86905 | 14.83392 | 14.83392 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44000 | 5.68912E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 94913.89501 | 94913.89501 | 4.91963 | 4.91963 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 162437.35956 | 162437.35956 | 14.38808 | 14.38808 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 141797.90161 | 141797.90161 | 7.34901 | 7.34901 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 180193.03469 | 180193.03469 | 15.96072 | 15.96072 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 89695.96167 | 89695.96167 | 4.64849 | 4.64849 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 15057.78086 | 15057.78086 | 1.33375 | 1.33375 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 18754.26281 | 18754.26281 | 0.97260 | 0.97260 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16981.66170 | 16981.66170 | 1.50415 | 1.50415 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 29.20500 | 5.69029E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 12374.92766 | 12374.92766 | 0.64179 | 0.64179 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 18028.82449 | 18028.82449 | 1.59691 | 1.59691 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 18599.98441 | 18599.98441 | 0.96458 | 0.96458 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 19339.95374 | 19339.95374 | 1.71304 | 1.71304 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 11969.36882 | 11969.36882 | 0.62072 | 0.62072 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8509.18854 | 8509.18854 | 0.59450 | 0.59450 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.51000 | 5.69229E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 81307.64429 | 81307.64429 | 5.68064 | 5.68064 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.17250 | 5.69177E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8305.43092 | 8305.43092 | 0.58027 | 0.58027 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.51000 | 5.69229E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372915.59943 | 372915.59943 | 26.05358 | 26.05358 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 22.81500 | 5.68069E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:40:00 | -7.90000 | 2.34317E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 153411.22 | 11.86898 | 11.86898 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 49333.16 | 2.39469 | 2.39469 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1424789.59 | 110.56872 | 110.56872 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 510253.86 | 37.32809 | 37.32809 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 162699.58 | 12.12333 | 12.12333 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 52128.29 | 6.17463 | 6.17463 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 |
7 | CAV_BAS | Cooling | Sensible | 81568.58 | 6.99271 | 6.99271 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 57212.75 | 1.20016 | 1.20016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 370415.58 | 26.05390 | 26.05390 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 16131.55 | 0.33839 | 0.33839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8455.19 | 0.59450 | 0.59450 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 745.21 | 1.56323E-002 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 80813.10 | 5.68064 | 5.68064 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 7452.11 | 0.15632 | 0.15632 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8254.04 | 0.58027 | 0.58027 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 745.21 | 1.56323E-002 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.99271 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.27056 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26161 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.18117 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69762 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45637E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.58025E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.18117 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18063.21022 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58025E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 364.14014 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 68.39132 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27811 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 20.51739 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74163 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36995E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.70190E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 20.51739 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 423150.01379 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.70190E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10022.41776 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.74526 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28198 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30400 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.05056 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75195 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35115E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.18953E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.97493 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 82180.71875 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.18953E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2169.11215 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.22849 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19440 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36855 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51840 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95986E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.34897E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38703 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10686.44982 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.34897E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 282.00025 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.41047 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10912 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42314 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.49169E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.69878E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42314 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8800.17880 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.69878E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 208.95946 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.49510 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15974 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.44853 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42597 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38514E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12502E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46592 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12859.68370 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12502E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 339.28895 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.77628 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.66447E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.53288 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.39727E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.06964E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.53288 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8081.03788 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.06964E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 177.51521 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.61547 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20561 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.48464 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54828 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85306E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.78787E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.41290 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 204364.43267 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.78787E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5389.10003 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.83392 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10375 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.45018 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.67221E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.18647E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.91963 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 135620.64917 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18647E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3576.23398 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.38808 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16599 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.31642 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44264 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29534E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.77249E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.34901 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 202605.98994 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.77249E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5342.76670 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.96072 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.64274E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.78821 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.95116E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.13129E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.78821 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 129313.48066 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13129E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3378.90184 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.33375 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17906 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40013 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47749 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.12779E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.34476E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.97260 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26802.04320 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.34476E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 706.63553 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.50415 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10232 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.45125 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.72360E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54720E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.64179 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17685.40706 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54720E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 466.26805 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59691 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14955 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.47907 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39881 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54756E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.32546E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.96458 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26581.38231 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.32546E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 700.82123 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.71304 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.98434E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.51391 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.24071E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49645E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.62072 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17105.39638 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49645E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 450.98339 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.59450 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.68064 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.58027 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 26.05358 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.59045 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.95427 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 13.18090 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.95427 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.86898 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.86898 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33316 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 62.59475 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 37.55685 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 125.18951 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 37.55685 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 110.56872 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 110.56872 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33967 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.44656 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.89492 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.89311 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 6.17463 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 12.12333 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 12.12333 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50932 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.99271 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.99271 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.99271 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.99271 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.99271 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.99271 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 26.05358 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 26.05358 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 26.05358 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.05358 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.05390 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 26.05390 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.59450 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.59450 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.59450 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.59450 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.59450 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.59450 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.68064 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.68064 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.68064 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.68064 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.68064 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.68064 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.58027 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.58027 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.58027 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.58027 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.58027 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.58027 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.86898 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 110.56872 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 12.12333 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.99271 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 26.05390 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.59450 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.68064 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.58027 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.86898 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.34054 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66771 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.98014E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.98014E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 187518.63543 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.97748E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.86898 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 50965.81850 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.45871E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 847.16961 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.86898 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.97748E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.96919E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.45871E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 110.56872 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.67414 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66757 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.94463E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.94463E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1783963.62447 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.58939E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 110.56872 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 444544.65515 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.88907E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7429.38205 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 110.56872 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.58939E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.27442E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.88907E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 12.12333 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.33100 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66760 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.95228E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.95228E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 191412.14307 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.14311E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 12.12333 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 43323.49617 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.79013E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 730.71680 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 12.12333 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.14311E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.84777E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.79013E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.99271 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.77423 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.12922 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.13602E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.13602E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 103262.47854 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.39302E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.99271 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 287807.62569 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.51787E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6382.65343 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.99271 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.39302E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.08397E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.51787E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.05390 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 26.05390 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 476903.19483 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 252970.43816 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.16793E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 26.05390 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 26.05390 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 26.05390 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 26.05390 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 476903.19483 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 476903.19483 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 16131.54879 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 26.05390 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 26.05390 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 476903.19483 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.16793E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 16131.54879 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.40909E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.59450 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.59450 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10601.47616 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5675.27845 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.59629E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.59450 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.59450 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.59450 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.59450 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10601.47616 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10601.47616 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.21073 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.59450 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.59450 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10601.47616 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.59629E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 745.21073 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.68064 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.68064 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 101351.39488 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 54241.81139 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48209E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.68064 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.68064 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.68064 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.68064 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 101351.39488 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 101351.39488 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 7452.10725 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.68064 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.68064 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 101351.39488 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48209E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7452.10725 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.58027 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58027 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10350.50672 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5540.09983 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.53483E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.58027 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.58027 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.58027 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.58027 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10350.50672 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10350.50672 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.21073 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.58027 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58027 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10350.50672 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.53483E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 745.21073 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.64076E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 19866.02335 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.64076E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 11.56891 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.64076E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.64076E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 404670.87170 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.88139E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.25767 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.88139E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 5665.91345 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2150541.66986 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2150541.67000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.88139E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.64076E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 11.56891 |
451 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 9.64076E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 13753.91809 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.64076E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.89379E-002 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1153160.52334 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1158629.75500 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.73363E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.64076E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.89379E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1153160.52334 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1158629.75500 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.73363E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.46745E-002 |
464 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.76094 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.46745E-002 |
466 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3742.73909 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.46745E-002 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 54810.54878 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 20939.09248 |
473 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 604464.84687 |
474 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 590854.07000 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.46745E-002 |
476 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
477 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
479 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
480 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
481 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11467 |
482 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 13.76071 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11467 |
484 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 34536.88683 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 53.88238 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1376422.51375 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.77648 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 172052.81422 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 53.88238 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1376422.51375 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.77648 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 172052.81422 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.95550E-002 |
494 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.95550E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17130.26 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 401051.15 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 77903.99 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10129.90 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8340.53 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12189.55 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7661.14 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 193695.53 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 128539.93 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 192029.14 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 122521.62 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 25401.92 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16761.48 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 25192.81 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 16211.82 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 40038.63 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 353070.16 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 35041.28 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 227174.21 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 253930.66 | 161598.85 | 92331.81 | 0.64 | 26033.62 | 264.05 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2387687.08 | 1514042.39 | 873644.69 | 0.63 | 243940.03 | 2474.18 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 259294.92 | 165031.53 | 94263.39 | 0.64 | 26586.19 | 269.65 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 141633.54 | 91611.60 | 50021.94 | 0.65 | 13991.84 | 141.91 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2550093691 | 0.2327673207 | Pass | Pass | 1.1599687051 | 1.7441560878 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1062704936 | 0.1772887698 | Pass | Pass | 0.1611981463 | 0.3672081583 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.0225112786E-002 | 0.1308370328 | Pass | Pass | 0.1327938380 | 0.3392583779 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.9739321171E-002 | 6.2411839186E-002 | Pass | Pass | 0.2405987935 | 0.4246874970 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.9192462436E-002 | 0.1610405013 | Pass | Pass | 0.1613246218 | 0.3652371714 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2263552554 | 0.3364783402 | Pass | Pass | 0.1651926260 | 0.3707119403 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2872874093 | 0.5054494324 | Pass | Pass | 0.1661108155 | 0.3677262197 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2368604112 | 0.3944876180 | Pass | Pass | 0.1623103149 | 0.3607861028 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.6575787721E-002 | 7.9732776914E-002 | Pass | Pass | 0.1327523406 | 0.3357576966 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1902399114 | 0.2597811313 | Pass | Pass | 0.1379673873 | 0.3489788653 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3138127754 | 0.5228028573 | Pass | Pass | 0.1738738718 | 0.4131545291 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1689643224 | 0.2663730060 | Pass | Pass | 0.1320181342 | 0.3329624575 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1101754893 | 0.1587583180 | Pass | Pass | 5.0808668657 | 28.5469138103 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1351300751 | 0.1550375534 | Pass | Pass | 2.5422323495 | 15.4993793692 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2497015347 | 0.2836176060 | Pass | Pass | 0.2445712365 | 0.4263733330 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1374644636 | 0.1754199124 | Pass | Pass | 0.2640952661 | 0.4954886093 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.4734864089E-002 | 3.1166555233E-002 | Pass | Pass | 0.2656168875 | 0.5964283310 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.9624584155E-002 | 3.7504584769E-002 | Pass | Pass | 1.6058402091 | 12.7027459313 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.5225414094E-002 | 7.2403533197E-002 | Pass | Pass | 0.2483498900 | 0.4232657891 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.5547319494E-006 | 7.9487779388E-006 | Pass | Pass | 7.1743022826E-003 | 9.1187811316E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.1104253031E-006 | 7.9666029610E-006 | Pass | Pass | 0.1980896784 | 0.7460373427 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.5870670398E-002 | 2.8322568382E-002 | Pass | Pass | 0.1246105598 | 0.5315833251 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.5835015549E-005 | 9.3150392885E-005 | Pass | Pass | 6.0133949943E-005 | 1.0535502887E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8879.90 | 142.08 | 0.00 | 18872.68 | 25024.33 | 52918.98 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 1043.06 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.171 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.3279 | 2779.43 | 25926.33 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 240.45 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.3279 | 24961.20 | 232836.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 2159.39 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.84 | 0.0000 | Y | 18.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.82 | 0.0000 | Y | 11.96 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.64 | 0.0000 | Y | 18.46 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.66 | 0.0000 | Y | 11.91 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.3279 | 3134.13 | 29234.97 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.86 | 0.0000 | Y | 185.81 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.82 | 0.0000 | Y | 119.62 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.3279 | 3134.20 | 29235.61 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.65 | 0.0000 | Y | 184.65 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.67 | 0.0000 | Y | 119.08 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.86 | 0.0000 | Y | 18.58 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.82 | 0.0000 | Y | 11.96 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.65 | 0.0000 | Y | 18.47 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.67 | 0.0000 | Y | 11.91 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 9.3279 | 783.68 | 7310.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 67.80 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 16.0861 | 362.03 | 5823.61 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 59.65 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
Interior Lighting Total | 9.3913 | 46320.38 | 435009.77 | 1156.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.01 | AstronomicalClock | - | 41.81 | 41.81 | 78.28 | |
EXTERIOR_LIGHTS_B | 44362.79 | AstronomicalClock | - | 83.71 | 71.14 | 592.41 | |
Exterior Lighting Total | 54335.80 | 670.69 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2260945.39 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2150541.67 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1158629.75 | 6.28 | 1108960.56 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1158629.75 | 6.28 | 1108960.56 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 590854.07 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1376422.51 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1376422.51 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 187518.64 | 253930.66 | 161598.85 | 92331.81 | 0.64 | - | 26033.62 | 264.05 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1783963.62 | 2387687.08 | 1514042.39 | 873644.69 | 0.63 | - | 243940.03 | 2474.18 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 191412.14 | 259294.92 | 165031.53 | 94263.39 | 0.64 | - | 26586.19 | 269.65 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 103262.48 | 141633.54 | 91611.60 | 50021.94 | 0.65 | - | 13991.84 | 141.91 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 476903.19 | 252970.44 | 223932.76 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10601.48 | 5675.28 | 4926.20 | 0.54 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 101351.39 | 54241.81 | 47109.58 | 0.54 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10350.51 | 5540.10 | 4810.41 | 0.54 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18063.21 | 17130.26 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 423150.01 | 401051.15 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 82180.72 | 77903.99 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 10686.45 | 10129.90 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 8800.18 | 8340.53 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12859.68 | 12189.55 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 8081.04 | 7661.14 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 204364.43 | 193695.53 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 135620.65 | 128539.93 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 202605.99 | 192029.14 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 129313.48 | 122521.62 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 26802.04 | 25401.92 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 17685.41 | 16761.48 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26581.38 | 25192.81 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 17105.40 | 16211.82 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 50965.82 | 40038.63 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 444544.66 | 353070.16 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 43323.50 | 35041.28 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 287807.63 | 227174.21 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 476903.19 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10601.48 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 101351.39 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10350.51 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 16131.55 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 745.21 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 7452.11 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 745.21 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.87 | 25511.95 | 2149.46 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 110.57 | 237663.55 | 2149.46 | 1.00 | 1.08 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 12.12 | 26058.67 | 2149.46 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.99 | 11780.72 | 1684.71 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 26.05 | 42789.15 | 1642.33 | 1.00 | 1.14 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.59 | 665.90 | 1120.11 | 1.00 | 1.53 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.68 | 6362.93 | 1120.11 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.58 | 649.96 | 1120.11 | 1.00 | 1.54 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.096408 | 19866.02 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.018814 | 5665.91 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.096408 | 13753.92 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014675 | 3742.74 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.114673 | 34536.89 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 79604.53 | 79604.53 | 28.64 | 6.993 | 6.993 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 25.11 | 0.00568 | 1.200 | 0.00 |
CORE_BOTTOM | 82778.32 | 82778.32 | 33.16 | 7.271 | 7.271 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00738 | 25.11 | 0.00568 | 1.078 | 0.00 |
CORE_MID | 778826.36 | 778826.36 | 312.01 | 68.391 | 68.391 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 25.11 | 0.00568 | 10.778 | 0.00 |
CORE_TOP | 76812.96 | 76812.96 | 30.77 | 6.745 | 6.745 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 25.11 | 0.00568 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13869.09 | 13869.09 | 44.25 | 1.228 | 1.228 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00724 | 35.10 | 0.00570 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15923.64 | 15923.64 | 78.84 | 1.410 | 1.410 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00714 | 27.68 | 0.00569 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 16879.02 | 16879.02 | 53.85 | 1.495 | 1.495 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00720 | 34.65 | 0.00570 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20053.54 | 20053.54 | 99.29 | 1.776 | 1.776 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00711 | 33.39 | 0.00570 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 131135.15 | 131135.15 | 418.41 | 11.615 | 11.615 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00721 | 35.10 | 0.00570 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 167471.87 | 167471.87 | 829.17 | 14.834 | 14.834 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00711 | 28.44 | 0.00569 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 162437.36 | 162437.36 | 518.27 | 14.388 | 14.388 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00717 | 34.76 | 0.00570 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 180193.03 | 180193.03 | 892.15 | 15.961 | 15.961 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00710 | 33.21 | 0.00570 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15057.78 | 15057.78 | 48.04 | 1.334 | 1.334 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00717 | 35.10 | 0.00570 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16981.66 | 16981.66 | 84.08 | 1.504 | 1.504 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00710 | 29.21 | 0.00569 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18028.82 | 18028.82 | 57.52 | 1.597 | 1.597 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00715 | 34.99 | 0.00570 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 19339.95 | 19339.95 | 95.75 | 1.713 | 1.713 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00709 | 33.21 | 0.00570 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8509.19 | 8509.19 | 235.04 | 0.594 | 0.594 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00708 | 30.51 | 0.00569 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 81307.64 | 81307.64 | 2245.90 | 5.681 | 5.681 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 30.17 | 0.00569 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8305.43 | 8305.43 | 229.41 | 0.580 | 0.580 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00709 | 30.51 | 0.00569 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372915.60 | 372915.60 | 475.85 | 26.054 | 26.054 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 22.82 | 0.00568 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | 21.00 | 24.28 | 0.00234 | -7.90 | 0.00234 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 19.60 | 21.69 | 0.00234 | -7.90 | 0.00234 | 1.078 | 0.00 |
CORE_MID | 253236.48 | 253236.48 | 101.45 | 12.998 | 12.998 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 10.778 | 0.00 |
CORE_TOP | 57544.03 | 57544.03 | 23.05 | 2.975 | 2.975 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 7484.89 | 7484.89 | 23.88 | 0.387 | 0.387 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 5299.37 | 5299.37 | 26.24 | 0.274 | 0.274 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 9004.21 | 9004.21 | 28.73 | 0.466 | 0.466 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 3676.39 | 3676.39 | 18.20 | 0.190 | 0.190 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00709 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 143027.25 | 143027.25 | 456.35 | 7.413 | 7.413 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 94913.90 | 94913.90 | 469.93 | 4.920 | 4.920 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 141797.90 | 141797.90 | 452.42 | 7.349 | 7.349 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 89695.96 | 89695.96 | 444.09 | 4.648 | 4.648 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 18754.26 | 18754.26 | 59.84 | 0.973 | 0.973 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12374.93 | 12374.93 | 61.27 | 0.642 | 0.642 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18599.98 | 18599.98 | 59.35 | 0.965 | 0.965 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 11969.37 | 11969.37 | 59.26 | 0.621 | 0.621 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -7.90 | 0.00234 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 18.00 | 26.10 | 0.00700 | -7.90 | 0.00234 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.08 | 0.00393 | -7.90 | 0.00234 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.23 | 0.00284 | -7.90 | 0.00234 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:40:00 | 18.00 | 27.00 | 0.00700 | -7.90 | 0.00234 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 11.87 | 11.87 | 2.39 | 2.39 | 11.8690 | 3.9543 | 11.8690 | 0.3332 | 0.3000 |
VAV_MID WITH REHEAT | 110.57 | 110.57 | 37.33 | 37.33 | 110.5687 | 37.5569 | 110.5687 | 0.3397 | 0.3000 |
VAV_TOP WITH REHEAT | 12.12 | 12.12 | 6.17 | 6.17 | 12.1233 | 6.1746 | 12.1233 | 0.5093 | 0.3000 |
CAV_BAS | 6.99 | 6.99 | 1.20 | 1.20 | 6.9927 | 6.9927 | 6.9927 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.05 | 26.05 | 0.34 | 0.34 | 26.0539 | 26.0536 | 26.0539 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.59 | 0.59 | 0.02 | 0.02 | 0.5945 | 0.5945 | 0.5945 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.68 | 5.68 | 0.16 | 0.16 | 5.6806 | 5.6806 | 5.6806 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.58 | 0.58 | 0.02 | 0.02 | 0.5803 | 0.5803 | 0.5803 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18063.210 | 18063.210 | 2.181168 | 0.00015802 | 364.140 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 18063.21 | 18063.21 | 2.181168 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 18129.81 | 18129.81 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 423150.014 | 423150.014 | 20.517395 | 0.00370190 | 10022.418 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 423150.01 | 423150.01 | 20.517395 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 253236.48 | 0.00 | 424531.19 | 424531.19 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 82180.719 | 82180.719 | 2.974929 | 0.00071895 | 2169.112 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 82180.72 | 82180.72 | 2.974929 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 57544.03 | 0.00 | 82463.22 | 82463.22 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 10686.450 | 10686.450 | 0.387034 | 0.00009349 | 282.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10686.45 | 10686.45 | 0.387034 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00747723 | 39.7938 | 7484.89 | 0.00 | 10722.74 | 10722.74 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8800.179 | 8800.179 | 0.423140 | 0.00007699 | 208.959 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8800.18 | 8800.18 | 0.423140 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00755928 | 40.2249 | 5299.37 | 0.00 | 8828.87 | 8828.87 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 12859.684 | 12859.684 | 0.465923 | 0.00011250 | 339.289 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12859.68 | 12859.68 | 0.465923 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00764653 | 40.6830 | 9004.21 | 0.00 | 12902.92 | 12902.92 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8081.038 | 8081.038 | 0.532883 | 0.00007070 | 177.515 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8081.04 | 8081.04 | 0.532883 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00708987 | 37.7567 | 3676.39 | 0.00 | 8108.98 | 8108.98 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 204364.433 | 204364.433 | 7.412901 | 0.00178787 | 5389.100 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 204364.43 | 204364.43 | 7.412901 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00763715 | 40.6347 | 143027.25 | 0.00 | 205031.11 | 205031.11 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 135620.649 | 135620.649 | 4.919630 | 0.00118647 | 3576.234 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 135620.65 | 135620.65 | 4.919630 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00763697 | 40.6339 | 94913.90 | 0.00 | 136062.43 | 136062.43 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 202605.990 | 202605.990 | 7.349007 | 0.00177249 | 5342.767 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 202605.99 | 202605.99 | 7.349007 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00763375 | 40.6169 | 141797.90 | 0.00 | 203267.20 | 203267.20 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 129313.481 | 129313.481 | 4.788215 | 0.00113129 | 3378.902 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 129313.48 | 129313.48 | 4.788215 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00761398 | 40.5131 | 89695.96 | 0.00 | 129708.58 | 129708.58 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 26802.043 | 26802.043 | 0.972598 | 0.00023448 | 706.636 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26802.04 | 26802.04 | 0.972598 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00766122 | 40.7618 | 18754.26 | 0.00 | 26888.50 | 26888.50 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 17685.407 | 17685.407 | 0.641794 | 0.00015472 | 466.268 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17685.41 | 17685.41 | 0.641794 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00765799 | 40.7450 | 12374.93 | 0.00 | 17742.40 | 17742.40 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 26581.382 | 26581.382 | 0.964580 | 0.00023255 | 700.821 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26581.38 | 26581.38 | 0.964580 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00765855 | 40.7478 | 18599.98 | 0.00 | 26667.15 | 26667.15 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 17105.396 | 17105.396 | 0.620724 | 0.00014965 | 450.983 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17105.40 | 17105.40 | 0.620724 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00764708 | 40.6876 | 11969.37 | 0.00 | 17160.57 | 17160.57 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 187518.635 | -999.000 | 11.868980 | 0.00797748 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 187518.64 | 187518.63 | 11.868980 | 26.34 | 13.92 | 0.00698014 | 10.67 | 7.96 | 0.00698014 | 35.10 | 0.00569938 | 15.77 | 20.2332 | 24.00 | 0.00732254 | 32.4837 | 128520.01 | 0.00 | 168614.74 | 168614.74 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 50965.819 | 50965.819 | 3.560694 | 0.00044587 | 847.170 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 50965.82 | 50965.82 | 3.560694 | -1.58 | -2.70 | 0.00326611 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 67.4439 | 21.28 | 0.00556406 | 29.1996 | 25464.86 | 0.00 | 48436.00 | 48436.00 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1783963.624 | -999.000 | 110.568724 | 0.07589394 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1783963.62 | 1783963.62 | 110.568724 | 26.67 | 14.01 | 0.00694463 | 10.67 | 7.92 | 0.00694463 | 35.10 | 0.00569938 | 15.77 | 22.4905 | 24.00 | 0.00734002 | 32.5602 | 1164921.71 | 0.00 | 1601418.71 | 1601418.71 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 444544.655 | 444544.655 | 33.170617 | 0.00388907 | 7429.382 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 444544.66 | 444544.66 | 33.170617 | -0.67 | -1.61 | 0.00367830 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 74.9685 | 19.79 | 0.00759697 | 43.5603 | 380946.33 | 0.00 | 427173.37 | 427173.37 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 191412.143 | -999.000 | 12.123329 | 0.00814311 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 191412.14 | 191412.14 | 12.123329 | 26.33 | 13.90 | 0.00695228 | 10.67 | 7.93 | 0.00695228 | 35.10 | 0.00569938 | 15.77 | 20.9364 | 24.00 | 0.00728550 | 32.3211 | 136398.72 | 0.00 | 171631.92 | 171631.92 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 43323.496 | 43323.496 | 3.636999 | 0.00037901 | 730.717 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 43323.50 | 43323.50 | 3.636999 | 0.83 | -0.49 | 0.00393647 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 69.7880 | 18.55 | 0.00760000 | 47.0620 | 46505.13 | 0.00 | 42400.59 | 42400.59 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 103262.479 | -999.000 | 6.992712 | 0.00439302 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 103262.48 | 103262.48 | 6.992712 | 25.77 | 13.86 | 0.00713602 | 11.13 | 8.32 | 0.00713602 | 33.34 | 0.00569665 | 15.21 | 17.1630 | 24.00 | 0.00747361 | 33.1463 | 71315.42 | 0.00 | 93254.14 | 93254.14 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 287807.626 | 287807.626 | 6.992712 | 0.00251787 | 6382.653 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 287807.63 | 287807.63 | 6.992712 | -1.36 | -3.99 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 17.1630 | 24.35 | 0.00234317 | 10.2573 | 0.00 | 0.00 | 239857.41 | 239857.41 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 476903.195 | 252970.438 | 26.053902 | 0.01167933 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 407024.14 | 405931.94 | -999.0 | 28.79 | 14.78 | 0.00702456 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | -999.0000 | 27.00 | 0.00704202 | 26.1552 | 372441.37 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10601.476 | 5675.278 | 0.594499 | 0.00025963 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 9004.33 | 8956.03 | -999.0 | 28.24 | 14.62 | 0.00704808 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00708469 | 26.3099 | 8509.19 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 101351.395 | 54241.811 | 5.680637 | 0.00248209 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 86090.56 | 85608.63 | -999.0 | 28.25 | 14.62 | 0.00705019 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00708862 | 26.3245 | 81304.70 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10350.507 | 5540.100 | 0.580265 | 0.00025348 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8791.62 | 8743.30 | -999.0 | 28.24 | 14.62 | 0.00704928 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00708685 | 26.3179 | 8305.43 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 476903.195 | 476903.195 | 26.053902 | 0.01167933 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 476903.19 | 476903.19 | 26.053902 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.2988 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10601.476 | 10601.476 | 0.594499 | 0.00025963 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10601.48 | 10601.48 | 0.594499 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.6295 | 26.52 | 0.00699525 | 26.7217 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 101351.395 | 101351.395 | 5.680637 | 0.00248209 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 101351.39 | 101351.39 | 5.680637 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7519 | 24.27 | 0.00392913 | 17.2447 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10350.507 | 10350.507 | 0.580265 | 0.00025348 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10350.51 | 10350.51 | 0.580265 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.6940 | 23.09 | 0.00283710 | 13.3873 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 16131.549 | 16131.549 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 16131.55 | 16131.55 | 26.053902 | -0.10 | -0.10 | 0.00693952 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.2988 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.21 | 745.21 | 0.594499 | -0.21 | -0.21 | 0.00687292 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.6295 | 26.52 | 0.00699525 | 26.7217 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 7452.107 | 7452.107 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7452.11 | 7452.11 | 5.680637 | -0.22 | -1.09 | 0.00388549 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7519 | 24.27 | 0.00392913 | 17.2447 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.21 | 745.21 | 0.580265 | -0.21 | -2.63 | 0.00282380 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.6940 | 23.09 | 0.00283710 | 13.3873 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18063.210 | 18063.210 | 2.181168 | 0.00015802 | 364.140 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 0.8234 | 0.839938 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | Sensible | 18063.21 | 18063.21 | 1.0000 | 2.16024856 | 2.181168 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.15800872 | 60.00 | 32.22 | 27.78 | 0.000 | 18063.21 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 18129.81 | 18129.81 | 2.16024856 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 423150.014 | 423150.014 | 20.517395 | 0.00370190 | 10022.418 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 19.2883 | 19.676439 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 423150.01 | 423150.01 | 1.0000 | 20.32061045 | 20.517395 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 3.70152328 | 60.00 | 32.22 | 27.78 | 0.000 | 423150.01 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 253236.48 | 0.00 | 424531.19 | 424531.19 | 20.32061045 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.29 | 19.11 | 0.00800000 | 53951.5 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 82180.719 | 82180.719 | 2.974929 | 0.00071895 | 2169.112 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 3.7460 | 3.821396 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 82180.72 | 82180.72 | 1.0000 | 2.94639648 | 2.974929 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.71887944 | 60.00 | 32.22 | 27.78 | 0.000 | 82180.72 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 57544.03 | 0.00 | 82463.22 | 82463.22 | 2.94639648 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61047.6 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10686.450 | 10686.450 | 0.387034 | 0.00009349 | 282.000 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 0.4871 | 0.496919 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10686.45 | 10686.45 | 1.0000 | 0.38332240 | 0.387034 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.09348019 | 60.00 | 32.22 | 27.78 | 0.000 | 10686.45 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00747723 | 21.00 | 0.00747723 | 39.7938 | 7484.89 | 0.00 | 10722.74 | 10722.74 | 0.38332240 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61033.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8800.179 | 8800.179 | 0.423140 | 0.00007699 | 208.959 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 0.4011 | 0.409208 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8800.18 | 8800.18 | 1.0000 | 0.41908193 | 0.423140 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.07697995 | 60.00 | 32.22 | 27.78 | 0.000 | 8800.18 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00755928 | 21.00 | 0.00755928 | 40.2249 | 5299.37 | 0.00 | 8828.87 | 8828.87 | 0.41908193 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.46 | 19.17 | 0.00800000 | 54127.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12859.684 | 12859.684 | 0.465923 | 0.00011250 | 339.289 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 0.5862 | 0.597974 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12859.68 | 12859.68 | 1.0000 | 0.46145386 | 0.465923 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.11249065 | 60.00 | 32.22 | 27.78 | 0.000 | 12859.68 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00764653 | 21.00 | 0.00764653 | 40.6830 | 9004.21 | 0.00 | 12902.92 | 12902.92 | 0.46145386 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61021.3 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8081.038 | 8081.038 | 0.532883 | 0.00007070 | 177.515 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 0.3684 | 0.375768 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8081.04 | 8081.04 | 1.0000 | 0.52777226 | 0.532883 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.07068923 | 60.00 | 32.22 | 27.78 | 0.000 | 8081.04 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00708987 | 21.00 | 0.00708987 | 37.7567 | 3676.39 | 0.00 | 8108.98 | 8108.98 | 0.52777226 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.87 | 17.32 | 0.00800000 | 48424.4 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 204364.433 | 204364.433 | 7.412901 | 0.00178787 | 5389.100 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 9.3155 | 9.502928 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 204364.43 | 204364.43 | 1.0000 | 7.34180351 | 7.412901 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.78768683 | 60.00 | 32.22 | 27.78 | 0.000 | 204364.43 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00763715 | 21.00 | 0.00763715 | 40.6347 | 143027.25 | 0.00 | 205031.11 | 205031.11 | 7.34180351 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.4 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 135620.649 | 135620.649 | 4.919630 | 0.00118647 | 3576.234 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 6.1819 | 6.306348 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 135620.65 | 135620.65 | 1.0000 | 4.87244499 | 4.919630 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.18634757 | 60.00 | 32.22 | 27.78 | 0.000 | 135620.65 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00763697 | 21.00 | 0.00763697 | 40.6339 | 94913.90 | 0.00 | 136062.43 | 136062.43 | 4.87244499 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60984.7 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 202605.990 | 202605.990 | 7.349007 | 0.00177249 | 5342.767 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 9.2353 | 9.421161 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 202605.99 | 202605.99 | 1.0000 | 7.27852141 | 7.349007 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.77230477 | 60.00 | 32.22 | 27.78 | 0.000 | 202605.99 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00763375 | 21.00 | 0.00763375 | 40.6169 | 141797.90 | 0.00 | 203267.20 | 203267.20 | 7.27852141 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.8 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 129313.481 | 129313.481 | 4.788215 | 0.00113129 | 3378.902 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 5.8944 | 6.013066 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 129313.48 | 129313.48 | 1.0000 | 4.74229047 | 4.788215 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.13117534 | 60.00 | 32.22 | 27.78 | 0.000 | 129313.48 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00761398 | 21.00 | 0.00761398 | 40.5131 | 89695.96 | 0.00 | 129708.58 | 129708.58 | 4.74229047 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.62 | 21.07 | 0.00800000 | 60411.3 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26802.043 | 26802.043 | 0.972598 | 0.00023448 | 706.636 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 1.2217 | 1.246293 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26802.04 | 26802.04 | 1.0000 | 0.96326945 | 0.972598 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.23445205 | 60.00 | 32.22 | 27.78 | 0.000 | 26802.04 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00766122 | 21.00 | 0.00766122 | 40.7618 | 18754.26 | 0.00 | 26888.50 | 26888.50 | 0.96326945 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.6 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17685.407 | 17685.407 | 0.641794 | 0.00015472 | 466.268 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 0.8061 | 0.822370 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17685.41 | 17685.41 | 1.0000 | 0.63563850 | 0.641794 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.15470387 | 60.00 | 32.22 | 27.78 | 0.000 | 17685.41 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00765799 | 21.00 | 0.00765799 | 40.7450 | 12374.93 | 0.00 | 17742.40 | 17742.40 | 0.63563850 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26581.382 | 26581.382 | 0.964580 | 0.00023255 | 700.821 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 1.2116 | 1.236032 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26581.38 | 26581.38 | 1.0000 | 0.95532866 | 0.964580 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.23252181 | 60.00 | 32.22 | 27.78 | 0.000 | 26581.38 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00765855 | 21.00 | 0.00765855 | 40.7478 | 18599.98 | 0.00 | 26667.15 | 26667.15 | 0.95532866 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17105.396 | 17105.396 | 0.620724 | 0.00014965 | 450.983 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 0.7797 | 0.795399 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17105.40 | 17105.40 | 1.0000 | 0.61477101 | 0.620724 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.14963020 | 60.00 | 32.22 | 27.78 | 0.000 | 17105.40 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00764708 | 21.00 | 0.00764708 | 40.6876 | 11969.37 | 0.00 | 17160.57 | 17160.57 | 0.61477101 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.6 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 187518.635 | -999.000 | 11.868980 | 0.00797748 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8157 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.868980 | 11.75514345 | 4197.9300 | 999.8980 | 96.39771785 | 12.27 | 6.67 | 5.60 | 2266156.88 | 8.2747 | 8.274742 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 187518.64 | 187518.63 | 1.0000 | 11.75514345 | 11.868980 | 26.34 | 13.92 | 0.00698014 | 44266.7 | 10.67 | 7.96 | 0.00698014 | 28314.7 | 7.97666245 | 6.67 | 12.27 | 5.60 | 25511.952 | 162006.68 | 35.10 | 0.00569938 | 15.77 | 2.40147000 | 20.2332 | 24.00 | 0.00732254 | 24.00 | 0.00732254 | 32.4837 | 128520.01 | 0.00 | 168614.74 | 168614.74 | 11.75514345 | 26.34 | 15.90 | 0.00698014 | 44266.7 | 12.25 | 10.29 | 0.00698014 | 29922.8 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 50965.819 | 50965.819 | 3.560694 | 0.00044587 | 847.170 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.868980 | 11.75514345 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 2.3232 | 2.369906 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 50965.82 | 50965.82 | 1.0000 | 3.52654303 | 3.560694 | -1.58 | -2.70 | 0.00326611 | 6568.9 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 0.44582573 | 60.00 | 32.22 | 27.78 | 0.000 | 50965.82 | -7.90 | 0.00234317 | -7.90 | 2.40147000 | 67.4439 | 11.51 | 0.00517808 | 21.28 | 0.00556406 | 29.1996 | 25464.86 | 0.00 | 48436.00 | 48436.00 | 3.52654303 | 2.80 | 0.91 | 0.00326611 | 10998.9 | 16.39 | 8.03 | 0.00326611 | 24733.6 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1783963.624 | -999.000 | 110.568724 | 0.07589394 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7497 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 110.568724 | 109.50824754 | 4197.9300 | 999.8980 | 96.39771785 | 12.27 | 6.67 | 5.60 | 2266156.88 | 78.7220 | 78.721983 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1783963.62 | 1783963.62 | 1.0000 | 109.50824754 | 110.568724 | 26.67 | 14.01 | 0.00694463 | 44515.7 | 10.67 | 7.92 | 0.00694463 | 28225.0 | 75.88619461 | 6.67 | 12.27 | 5.60 | 237663.554 | 1546300.07 | 35.10 | 0.00569938 | 15.77 | 24.86750000 | 22.4905 | 24.00 | 0.00734002 | 24.00 | 0.00734002 | 32.5602 | 1164921.71 | 0.00 | 1601418.71 | 1601418.71 | 109.50824754 | 26.67 | 15.99 | 0.00694463 | 44515.7 | 12.31 | 10.28 | 0.00694463 | 29892.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 444544.655 | 444544.655 | 33.170617 | 0.00388907 | 7429.382 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 110.568724 | 109.50824754 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 20.2635 | 20.671288 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 444544.66 | 444544.66 | 1.0000 | 32.85247426 | 33.170617 | -0.67 | -1.61 | 0.00367830 | 8525.3 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 3.88867385 | 60.00 | 32.22 | 27.78 | 0.000 | 444544.66 | -7.90 | 0.00234317 | -7.90 | 24.86750000 | 74.9685 | 21.00 | 0.00767698 | 19.79 | 0.00759697 | 43.5603 | 380946.33 | 0.00 | 427173.37 | 427173.37 | 32.85247426 | 2.80 | 1.49 | 0.00367830 | 12031.9 | 15.65 | 8.17 | 0.00367830 | 25034.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 191412.143 | -999.000 | 12.123329 | 0.00814311 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7639 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 12.123329 | 12.00705323 | 4197.9300 | 999.8980 | 96.39771785 | 12.27 | 6.67 | 5.60 | 2266156.88 | 8.4466 | 8.446553 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 191412.14 | 191412.14 | 1.0000 | 12.00705323 | 12.123329 | 26.33 | 13.90 | 0.00695228 | 44186.0 | 10.67 | 7.93 | 0.00695228 | 28244.3 | 8.14228437 | 6.67 | 12.27 | 5.60 | 26058.667 | 165353.48 | 35.10 | 0.00569938 | 15.77 | 2.53819000 | 20.9364 | 24.00 | 0.00728550 | 24.00 | 0.00728550 | 32.3211 | 136398.72 | 0.00 | 171631.92 | 171631.92 | 12.00705323 | 26.33 | 15.88 | 0.00695228 | 44186.0 | 12.29 | 10.28 | 0.00695228 | 29891.7 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 43323.496 | 43323.496 | 3.636999 | 0.00037901 | 730.717 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 12.123329 | 12.00705323 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 1.9748 | 2.014539 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 43323.50 | 43323.50 | 1.0000 | 3.60211597 | 3.636999 | 0.83 | -0.49 | 0.00393647 | 10685.9 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 0.37897418 | 60.00 | 32.22 | 27.78 | 0.000 | 43323.50 | -7.90 | 0.00234317 | -7.90 | 2.53819000 | 69.7880 | 21.00 | 0.00761691 | 18.55 | 0.00760000 | 47.0620 | 46505.13 | 0.00 | 42400.59 | 42400.59 | 3.60211597 | 2.80 | 1.86 | 0.00393647 | 12678.9 | 14.43 | 7.89 | 0.00393647 | 24449.9 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 103262.479 | -999.000 | 6.992712 | 0.00439302 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1055 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:ConstantVolume | 6.992712 | 6.92564369 | 4197.9300 | 999.8980 | 96.39771785 | 12.27 | 6.67 | 5.60 | 2266156.88 | 4.5567 | 4.556722 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 103262.48 | 103262.48 | 1.0000 | 6.92564369 | 6.992712 | 25.77 | 13.86 | 0.00713602 | 44087.6 | 11.13 | 8.32 | 0.00713602 | 29177.5 | 4.39257642 | 6.67 | 12.27 | 5.60 | 11780.723 | 91481.76 | 33.34 | 0.00569665 | 15.21 | 1.20015641 | 17.1630 | 24.00 | 0.00747361 | 24.00 | 0.00747361 | 33.1463 | 71315.42 | 0.00 | 93254.14 | 93254.14 | 6.92564369 | 25.77 | 15.84 | 0.00713602 | 44087.6 | 12.55 | 10.59 | 0.00713602 | 30622.6 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 287807.626 | 287807.626 | 6.992712 | 0.00251787 | 6382.653 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:ConstantVolume | 6.992712 | 6.92564369 | 4197.9300 | 999.8980 | 18.81195747 | 54.44 | 82.22 | 27.78 | 2193822.18 | 13.1190 | 13.383029 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 287807.63 | 287807.63 | 1.0000 | 6.92564369 | 6.992712 | -1.36 | -3.99 | 0.00234317 | 4491.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 2.51760981 | 60.00 | 32.22 | 27.78 | 0.000 | 287807.63 | -7.90 | 0.00234317 | -7.90 | 1.20015641 | 17.1630 | 0.00 | 0.00234317 | 24.35 | 0.00234317 | 10.2573 | 0.00 | 0.00 | 239857.41 | 239857.41 | 6.92564369 | 12.80 | 5.14 | 0.00234317 | 18777.8 | 47.12 | 19.09 | 0.00234317 | 53411.1 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 476903.195 | 252970.438 | 26.053902 | 0.01167933 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.8983 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 407024.14 | 405931.94 | 0.8535 | -999.0 | -999.0 | 28.79 | 14.78 | 0.00702456 | 46873.1 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 407024.14 | 35.10 | 0.00569938 | 15.77 | 0.33839277 | -999.0000 | 27.00 | 0.00704202 | 27.00 | 0.00704202 | 26.1552 | 372441.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10601.476 | 5675.278 | 0.594499 | 0.00025963 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9420 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 9004.33 | 8956.03 | 0.8493 | -999.0 | -999.0 | 28.24 | 14.62 | 0.00704808 | 46375.0 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9004.33 | 30.51 | 0.00569229 | 14.27 | 0.01563234 | -999.0000 | 27.00 | 0.00708469 | 27.00 | 0.00708469 | 26.3099 | 8509.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 101351.395 | 54241.811 | 5.680637 | 0.00248209 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9460 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 86090.56 | 85608.63 | 0.8494 | -999.0 | -999.0 | 28.25 | 14.62 | 0.00705019 | 46384.7 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86090.56 | 30.51 | 0.00569229 | 14.27 | 0.15632344 | -999.0000 | 27.00 | 0.00708862 | 27.00 | 0.00708862 | 26.3245 | 81304.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10350.507 | 5540.100 | 0.580265 | 0.00025348 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9443 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8791.62 | 8743.30 | 0.8494 | -999.0 | -999.0 | 28.24 | 14.62 | 0.00704928 | 46380.3 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8791.62 | 30.51 | 0.00569229 | 14.27 | 0.01563234 | -999.0000 | 27.00 | 0.00708685 | 27.00 | 0.00708685 | 26.3179 | 8305.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 476903.195 | 476903.195 | 26.053902 | 0.01167933 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 476903.19 | 476903.19 | 1.0000 | 25.80401643 | 26.053902 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 476903.19 | -7.90 | 0.00234317 | -7.90 | 0.33839277 | 1.2988 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10601.476 | 10601.476 | 0.594499 | 0.00025963 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10601.48 | 10601.48 | 1.0000 | 0.58879741 | 0.594499 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10601.48 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.6295 | 0.00 | 0.00699525 | 26.52 | 0.00699525 | 26.7217 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 101351.395 | 101351.395 | 5.680637 | 0.00248209 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 101351.39 | 101351.39 | 1.0000 | 5.62615321 | 5.680637 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 101351.39 | -7.90 | 0.00234317 | -7.90 | 0.15632344 | 2.7519 | 0.00 | 0.00392913 | 24.27 | 0.00392913 | 17.2447 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10350.507 | 10350.507 | 0.580265 | 0.00025348 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10350.51 | 10350.51 | 1.0000 | 0.57469979 | 0.580265 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10350.51 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.6940 | 0.00 | 0.00283710 | 23.09 | 0.00283710 | 13.3873 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16131.549 | 16131.549 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 26.053902 | 25.80401643 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 16131.55 | 16131.55 | 1.0000 | 25.80401643 | 26.053902 | -0.10 | -0.10 | 0.00693952 | 17250.9 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16131.55 | -7.90 | 0.00234317 | -7.90 | 0.33839277 | 1.2988 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.594499 | 0.58879741 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 745.21 | 745.21 | 1.0000 | 0.58879741 | 0.594499 | -0.21 | -0.21 | 0.00687292 | 16977.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.21 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.6295 | 0.00 | 0.00699525 | 26.52 | 0.00699525 | 26.7217 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7452.107 | 7452.107 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.680637 | 5.62615321 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 7452.11 | 7452.11 | 1.0000 | 5.62615321 | 5.680637 | -0.22 | -1.09 | 0.00388549 | 9497.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7452.11 | -7.90 | 0.00234317 | -7.90 | 0.15632344 | 2.7519 | 0.00 | 0.00392913 | 24.27 | 0.00392913 | 17.2447 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.580265 | 0.57469979 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 745.21 | 745.21 | 1.0000 | 0.57469979 | 0.580265 | -0.21 | -2.63 | 0.00282380 | 6847.2 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.21 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.6940 | 0.00 | 0.00283710 | 23.09 | 0.00283710 | 13.3873 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.87 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 110.57 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 12.12 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.99 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2499.67 | 1228.50 | 223.50 |
CORE_BOTTOM | 2227.83 | 1335.00 | 218.67 |
CORE_MID | 1757.67 | 3072.67 | 265.83 |
CORE_TOP | 2108.50 | 3468.83 | 612.00 |
PERIMETER_BOT_ZN_3 | 1942.00 | 3318.83 | 214.83 |
PERIMETER_BOT_ZN_2 | 2268.17 | 3037.83 | 310.67 |
PERIMETER_BOT_ZN_1 | 2724.00 | 2135.17 | 339.67 |
PERIMETER_BOT_ZN_4 | 2863.50 | 2168.50 | 344.00 |
PERIMETER_MID_ZN_3 | 2732.33 | 3807.00 | 1261.00 |
PERIMETER_MID_ZN_2 | 2284.00 | 3019.00 | 842.00 |
PERIMETER_MID_ZN_1 | 2728.83 | 2504.33 | 537.33 |
PERIMETER_MID_ZN_4 | 2466.00 | 3567.83 | 768.17 |
PERIMETER_TOP_ZN_3 | 3410.50 | 3994.83 | 2022.00 |
PERIMETER_TOP_ZN_2 | 3201.50 | 3560.00 | 1443.83 |
PERIMETER_TOP_ZN_1 | 2900.17 | 2830.83 | 902.83 |
PERIMETER_TOP_ZN_4 | 2967.33 | 3757.17 | 1358.83 |
DATACENTER_BOT_ZN_6 | 5943.00 | 873.33 | 873.33 |
DATACENTER_MID_ZN_6 | 5851.83 | 172.50 | 172.50 |
DATACENTER_TOP_ZN_6 | 5365.17 | 416.50 | 311.00 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 94.83 | 0.00 | 3.00 |
CORE_BOTTOM | 0.00 | 7.83 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 4.83 | 0.00 | 2.67 |
PERIMETER_BOT_ZN_2 | 0.00 | 36.67 | 0.00 | 36.67 |
PERIMETER_BOT_ZN_1 | 0.00 | 90.83 | 0.00 | 89.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 103.17 | 0.00 | 41.00 |
PERIMETER_MID_ZN_3 | 6.33 | 1.67 | 0.33 | 1.00 |
PERIMETER_MID_ZN_2 | 5.33 | 40.83 | 0.00 | 40.50 |
PERIMETER_MID_ZN_1 | 1.33 | 169.00 | 0.00 | 167.67 |
PERIMETER_MID_ZN_4 | 1.83 | 32.83 | 0.00 | 20.33 |
PERIMETER_TOP_ZN_3 | 53.50 | 8.33 | 8.67 | 5.17 |
PERIMETER_TOP_ZN_2 | 37.17 | 46.17 | 1.67 | 43.67 |
PERIMETER_TOP_ZN_1 | 24.00 | 69.33 | 0.17 | 66.33 |
PERIMETER_TOP_ZN_4 | 25.17 | 35.33 | 0.00 | 21.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 94.33 | 0.00 | 80.50 |
DATACENTER_MID_ZN_6 | 0.00 | 33.67 | 0.00 | 26.50 |
DATACENTER_TOP_ZN_6 | 0.00 | 21.83 | 0.00 | 14.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1968.33 | 0.00 | 1273.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 59.00 | 2341.17 | 8.67 | 1543.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 1.593 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 1.162 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.880 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.829 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 1.161 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 2.070 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.912 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.597 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.971 | 0.100 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.934 | 0.112 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.748 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.967 | 0.104 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 1.045 | 0.124 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 2.055 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.756 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 2.057 | 0.129 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.425 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.425 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.425 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.481 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 68801558.65 | 0.00 | 68801558.65 | 0.00 | 68801558.65 | 37848132.68 | 3683.54 | 1150.86 | 3925.61 | 568.83 |
CORE_BOTTOM | 51578586.25 | 0.00 | 51578586.25 | 0.00 | 51578586.25 | 33990283.35 | 4455.74 | 24.28 | 4279.98 | 709.09 |
CORE_MID | 0.37E+09 | 0.00 | 0.37E+09 | 0.00 | 0.37E+09 | 0.34E+09 | 5539.15 | 28.36 | 3192.49 | 252.42 |
CORE_TOP | 34720816.98 | 0.00 | 34720816.98 | 0.00 | 34720816.98 | 33990283.35 | 5892.48 | 28.91 | 2838.62 | 340.76 |
PERIMETER_BOT_ZN_3 | 6655642.36 | 0.00 | 6655642.36 | 435989.32 | 7091631.68 | 4267819.30 | 3293.71 | 52.05 | 5414.25 | 709.09 |
PERIMETER_BOT_ZN_2 | 7651876.09 | 0.00 | 7651876.09 | 290659.35 | 7942535.43 | 2750345.05 | 3036.16 | 2.17 | 5721.67 | 709.09 |
PERIMETER_BOT_ZN_1 | 10616796.36 | 0.00 | 10616796.36 | 435989.32 | 11052785.67 | 4267912.63 | 3055.10 | 11.15 | 5693.75 | 709.09 |
PERIMETER_BOT_ZN_4 | 9621415.27 | 0.00 | 9621415.27 | 290659.35 | 9912074.62 | 2750345.05 | 3035.49 | 0.00 | 5724.51 | 709.09 |
PERIMETER_MID_ZN_3 | 51586468.52 | 0.00 | 51586468.52 | 1022509.09 | 52608977.60 | 42678193.03 | 3907.43 | 37.70 | 4814.87 | 252.42 |
PERIMETER_MID_ZN_2 | 70097728.98 | 0.00 | 70097728.98 | 681672.26 | 70779401.24 | 27503450.52 | 3615.23 | 0.00 | 5144.77 | 1161.42 |
PERIMETER_MID_ZN_1 | 91332892.27 | 0.00 | 91332892.27 | 1022509.09 | 92355401.35 | 42679126.28 | 3713.33 | 7.28 | 5039.40 | 252.42 |
PERIMETER_MID_ZN_4 | 67635698.25 | 0.00 | 67635698.25 | 681672.26 | 68317370.51 | 27503450.52 | 3615.23 | 0.00 | 5144.77 | 252.42 |
PERIMETER_TOP_ZN_3 | 5553204.32 | 0.00 | 5553204.32 | 1269544.06 | 6822748.38 | 4267819.30 | 3942.18 | 12.77 | 4805.04 | 340.76 |
PERIMETER_TOP_ZN_2 | 6989826.91 | 0.00 | 6989826.91 | 846362.13 | 7836189.04 | 2750345.05 | 3741.68 | 4.51 | 5013.81 | 340.76 |
PERIMETER_TOP_ZN_1 | 9179543.66 | 0.00 | 9179543.66 | 1269544.06 | 10449087.72 | 4267912.63 | 3830.13 | 8.91 | 4920.96 | 340.76 |
PERIMETER_TOP_ZN_4 | 7051425.74 | 0.00 | 7051425.74 | 846362.13 | 7897787.87 | 2750345.05 | 3709.69 | 5.62 | 5044.69 | 340.76 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.68E+10 | 0.00 | 0.68E+10 | 39768736.56 | 0.68E+10 | 0.50E+10 | 6504.24 | 4399.16 | 6044.36 | 1971.35 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.9530 | 0.0000 | 2.9530 | 0.0000 | 2.9530 | 1.2002 | 1272.08 | 1146.49 | 3524.43 |
CORE_BOTTOM | 2.1773 | 0.0000 | 2.1773 | 0.0000 | 2.1773 | 1.0778 | 2253.12 | 22.18 | 3667.70 |
CORE_MID | 16.4846 | 0.0000 | 16.4846 | 0.0000 | 16.4846 | 10.7782 | 2920.07 | 27.59 | 2995.34 |
CORE_TOP | 1.5533 | 0.0000 | 1.5533 | 0.0000 | 1.5533 | 1.0778 | 3236.57 | 28.91 | 2677.53 |
PERIMETER_BOT_ZN_3 | 0.2734 | 0.0000 | 0.2734 | 0.0101 | 0.2835 | 0.1353 | 1153.49 | 48.08 | 4741.42 |
PERIMETER_BOT_ZN_2 | 0.3144 | 0.0000 | 0.3144 | 0.0067 | 0.3212 | 0.0872 | 928.25 | 2.17 | 5012.58 |
PERIMETER_BOT_ZN_1 | 0.4504 | 0.0000 | 0.4504 | 0.0101 | 0.4605 | 0.1353 | 944.80 | 8.59 | 4989.61 |
PERIMETER_BOT_ZN_4 | 0.3942 | 0.0000 | 0.3942 | 0.0067 | 0.4009 | 0.0872 | 927.58 | 0.00 | 5015.42 |
PERIMETER_MID_ZN_3 | 2.2896 | 0.0000 | 2.2896 | 0.0237 | 2.3133 | 1.3533 | 1297.37 | 37.33 | 4608.30 |
PERIMETER_MID_ZN_2 | 2.9404 | 0.0000 | 2.9404 | 0.0170 | 2.9574 | 0.8721 | 1050.65 | 0.00 | 3983.35 |
PERIMETER_MID_ZN_1 | 4.1186 | 0.0000 | 4.1186 | 0.0237 | 4.1424 | 1.3533 | 1109.78 | 5.78 | 4827.44 |
PERIMETER_MID_ZN_4 | 2.9928 | 0.0000 | 2.9928 | 0.0158 | 3.0086 | 0.8721 | 1050.65 | 0.00 | 4892.35 |
PERIMETER_TOP_ZN_3 | 0.2468 | 0.0000 | 0.2468 | 0.0295 | 0.2763 | 0.1353 | 1293.72 | 11.96 | 4637.32 |
PERIMETER_TOP_ZN_2 | 0.3125 | 0.0000 | 0.3125 | 0.0197 | 0.3321 | 0.0872 | 1137.89 | 3.47 | 4801.64 |
PERIMETER_TOP_ZN_1 | 0.4138 | 0.0000 | 0.4138 | 0.0295 | 0.4433 | 0.1353 | 1191.50 | 6.98 | 4744.52 |
PERIMETER_TOP_ZN_4 | 0.3131 | 0.0000 | 0.3131 | 0.0197 | 0.3327 | 0.0872 | 1120.07 | 3.12 | 4819.80 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 299.0738 | 0.0000 | 299.0738 | 0.9354 | 300.0092 | 158.4706 | 3687.24 | 4378.09 | 5122.82 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 84480244.24 | 0.00 | 84480244.24 | 48026705.38 | 3131.42 | 18.11 | 5610.47 | 709.09 |
VAV_MID WITH REHEAT | 0.64E+09 | 0.00 | 0.64E+09 | 0.48E+09 | 3769.65 | 8.54 | 4981.80 | 252.42 |
VAV_TOP WITH REHEAT | 62282681.24 | 0.00 | 62282681.24 | 48026705.38 | 3871.69 | 11.96 | 4876.35 | 340.76 |
CAV_BAS | 67488121.57 | 0.00 | 67488121.57 | 37848132.68 | 4834.30 | 6.27 | 3919.43 | 568.74 |
AIRLOOP DATACENTER BASEMENT | 5187312.62 | 0.00 | 5187312.62 | 10671554.30 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 239632.35 | 0.00 | 239632.35 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 2396323.53 | 0.00 | 2396323.53 | 4929815.99 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 239632.35 | 0.00 | 239632.35 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.5407 | 0.0000 | 3.5407 | 1.5229 | 980.55 | 13.98 | 4948.47 |
VAV_MID WITH REHEAT | 28.4543 | 0.0000 | 28.4543 | 15.2292 | 1155.57 | 8.29 | 4779.14 |
VAV_TOP WITH REHEAT | 2.7853 | 0.0000 | 2.7853 | 1.5229 | 1217.22 | 11.74 | 4714.04 |
CAV_BAS | 2.8966 | 0.0000 | 2.8966 | 1.2002 | 2418.57 | 1.58 | 3522.85 |
AIRLOOP DATACENTER BASEMENT | 0.2425 | 0.0000 | 0.2425 | 0.3384 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.0112 | 0.0000 | 0.0112 | 0.0156 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.1120 | 0.0000 | 0.1120 | 0.1563 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.0112 | 0.0000 | 0.0112 | 0.0156 | 5943.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.18 | 4632.06 | 0.00 | 0.00 | 0.00 | 1092.26 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.10 | 3721.52 | 0.00 | 0.00 | 0.00 | 1423.15 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.05 | 3498.48 | 0.00 | 0.00 | 0.00 | 1734.44 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1144.83 | 4117.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 4.9184 | 0.0000 | 0.0000 | 0.0000 | 1.6030 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 41.9241 | 0.0000 | 0.0000 | 0.0000 | 16.6275 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.3243 | 0.0000 | 0.0000 | 0.0000 | 1.6730 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.1781 | 4.4708 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3320 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1534 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1380 |
Defaulted Fields | 1179 |
Fields with Defaults | 3862 |
Autosized Fields | 330 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31552.01 | 407021.91 | 15-JAN-10:10 | 2101855.59 | 07-AUG-16:00 |
Electricity:Building | 18915.49 | 251811.03 | 01-JAN-08:40 | 1146857.44 | 01-DEC-17:00 |
Electricity:Zone:BASEMENT | 664.85 | 14623.97 | 01-JAN-00:10 | 34452.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18915.49 | 251811.03 | 01-JAN-08:40 | 1146857.44 | 01-DEC-17:00 |
InteriorLights:Electricity | 3702.08 | 17601.77 | 01-JAN-08:40 | 352853.36 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3702.08 | 17601.77 | 01-JAN-08:40 | 352853.36 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity | 3702.08 | 17601.77 | 01-JAN-08:40 | 352853.36 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3702.08 | 17601.77 | 01-JAN-08:40 | 352853.36 | 13-NOV-17:00 |
Electricity:Zone:CORE_BOTTOM | 537.23 | 7090.40 | 01-JAN-00:10 | 36983.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5372.24 | 70903.72 | 01-JAN-00:10 | 369831.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 537.22 | 7090.37 | 01-JAN-00:10 | 36983.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 58.91 | 839.57 | 01-JAN-08:40 | 4643.71 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.57 | 80.80 | 01-JAN-08:40 | 2367.39 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.57 | 80.80 | 01-JAN-08:40 | 2367.39 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 37.96 | 541.05 | 01-JAN-07:50 | 2992.58 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.96 | 52.07 | 01-JAN-07:50 | 1525.64 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.96 | 52.07 | 01-JAN-07:50 | 1525.64 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 58.80 | 839.58 | 01-JAN-07:50 | 4643.79 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.46 | 80.80 | 01-JAN-07:50 | 2367.44 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.46 | 80.80 | 01-JAN-07:50 | 2367.44 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 37.90 | 541.05 | 01-JAN-08:40 | 2992.57 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.91 | 52.07 | 01-JAN-08:40 | 1525.64 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.91 | 52.07 | 01-JAN-08:40 | 1525.64 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 589.23 | 8395.70 | 01-JAN-08:40 | 46437.07 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 185.81 | 807.98 | 01-JAN-08:40 | 23673.89 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 185.81 | 807.98 | 01-JAN-08:40 | 23673.89 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 379.60 | 5410.51 | 01-JAN-07:50 | 29925.82 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 119.62 | 520.69 | 01-JAN-07:50 | 15256.36 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 119.62 | 520.69 | 01-JAN-07:50 | 15256.36 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 588.08 | 8395.84 | 01-JAN-07:50 | 46437.94 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 184.66 | 807.99 | 01-JAN-07:50 | 23674.41 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 184.66 | 807.99 | 01-JAN-07:50 | 23674.41 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 379.06 | 5410.48 | 01-JAN-08:40 | 29925.72 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 119.08 | 520.69 | 01-JAN-08:40 | 15256.36 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 119.08 | 520.69 | 01-JAN-08:40 | 15256.36 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 58.92 | 839.57 | 01-JAN-08:40 | 4643.71 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.58 | 80.80 | 01-JAN-08:40 | 2367.39 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.58 | 80.80 | 01-JAN-08:40 | 2367.39 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 37.96 | 541.05 | 01-JAN-07:50 | 2992.58 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.96 | 52.07 | 01-JAN-07:50 | 1525.64 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.96 | 52.07 | 01-JAN-07:50 | 1525.64 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 58.81 | 839.58 | 01-JAN-07:50 | 4643.79 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.47 | 80.80 | 01-JAN-07:50 | 2367.44 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.47 | 80.80 | 01-JAN-07:50 | 2367.44 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 37.91 | 541.05 | 01-JAN-08:40 | 2992.57 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.91 | 52.07 | 01-JAN-08:40 | 1525.64 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.91 | 52.07 | 01-JAN-08:40 | 1525.64 | 13-NOV-17:00 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7562.65 | 95237.01 | 01-JAN-00:10 | 385552.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1598.46 | 19775.43 | 01-JAN-00:10 | 83152.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2776.96 | 6816.59 | 20-JAN-02:00 | 408470.39 | 05-SEP-13:10 |
HeatRejection:Electricity | 1157.48 | 2837.17 | 21-JAN-07:10 | 82925.55 | 06-JUN-12:40 |
General:HeatRejection:Electricity | 1157.48 | 2837.17 | 21-JAN-07:10 | 82925.55 | 06-JUN-12:40 |
Electricity:HVAC | 7334.26 | 111822.40 | 17-JAN-04:40 | 556178.58 | 07-AUG-15:40 |
ExteriorEquipment:Electricity | 1941.93 | 28795.69 | 01-JAN-00:10 | 118950.32 | 02-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 87.32 | 1613.62 | 01-JAN-00:10 | 5481.25 | 05-DEC-17:00 |
ElectricityPurchased:Facility | 31552.01 | 407021.91 | 15-JAN-10:10 | 2101855.59 | 07-AUG-16:00 |
ElectricityPurchased:Plant | 31552.01 | 407021.91 | 15-JAN-10:10 | 2101855.59 | 07-AUG-16:00 |
Cogeneration:ElectricityPurchased | 31552.01 | 407021.91 | 15-JAN-10:10 | 2101855.59 | 07-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 31552.01 | 407021.91 | 15-JAN-10:10 | 2101855.59 | 07-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31552.01 | 407021.91 | 15-JAN-10:10 | 2101855.59 | 07-AUG-16:00 |
ElectricityNet:Plant | 31552.01 | 407021.91 | 15-JAN-10:10 | 2101855.59 | 07-AUG-16:00 |
Cogeneration:ElectricityNet | 31552.01 | 407021.91 | 15-JAN-10:10 | 2101855.59 | 07-AUG-16:00 |
General:Cogeneration:ElectricityNet | 31552.01 | 407021.91 | 15-JAN-10:10 | 2101855.59 | 07-AUG-16:00 |
Fans:Electricity | 3008.25 | 50467.94 | 01-JAN-21:40 | 306490.58 | 07-AUG-15:40 |
General:Fans:Electricity | 3008.25 | 50467.94 | 01-JAN-21:40 | 306490.58 | 07-AUG-15:40 |
ExteriorLights:Electricity | 670.69 | 0.00 | 01-JAN-07:20 | 54335.80 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 670.69 | 0.00 | 01-JAN-07:20 | 54335.80 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 4091.14 | 36027.39 | 17-JAN-07:10 | 436579.83 | 01-AUG-15:10 |
General:Cooling:Electricity | 4091.14 | 36027.39 | 17-JAN-07:10 | 436579.83 | 01-AUG-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1149.71 | 0.00 | 06-JUL-15:40 | 75188.39 | 23-DEC-07:30 |
General:Humidifier:Electricity | 1149.71 | 0.00 | 06-JUL-15:40 | 75188.39 | 23-DEC-07:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 617.32 | 3742.74 | 17-JAN-02:40 | 70368.37 | 27-JUN-15:50 |
General:Pumps:Electricity | 617.32 | 3742.74 | 17-JAN-02:40 | 70368.37 | 27-JUN-15:50 |
WIRED_LTG_ELECTRICITY | 104.03 | 0.00 | 01-JAN-00:10 | 9915.18 | 13-NOV-17:10 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1372.68 | 5695.87 | 17-JAN-06:00 | 783282.91 | 06-FEB-07:10 |
NaturalGas:Plant | 1372.68 | 5695.87 | 17-JAN-06:00 | 783282.91 | 06-FEB-07:10 |
Heating:NaturalGas | 679.70 | 0.00 | 01-JAN-00:10 | 753815.78 | 06-FEB-07:10 |
Boiler:Heating:NaturalGas | 679.70 | 0.00 | 01-JAN-00:10 | 753815.78 | 06-FEB-07:10 |
WaterSystems:NaturalGas | 692.98 | 5695.87 | 17-JAN-05:30 | 81613.24 | 02-FEB-12:50 |
Water Heater:WaterSystems:NaturalGas | 692.98 | 5695.87 | 17-JAN-05:30 | 81613.24 | 02-FEB-12:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 21492.19 | 177067.87 | 17-JAN-07:10 | 2458444.42 | 23-AUG-16:00 |
PlantLoopCoolingDemand:HVAC | 21492.19 | 177067.87 | 17-JAN-07:10 | 2458444.42 | 23-AUG-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 21492.19 | 177067.87 | 17-JAN-07:10 | 2458444.42 | 23-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9629.69 | 0.00 | 31-AUG-23:10 | 0.00 | 28-JUN-16:20 |
Water:HVAC | 427.69 | 0.00 | 06-JUL-15:40 | 0.00 | 23-DEC-07:30 |
Humidifier:Water | 427.69 | 0.00 | 06-JUL-15:40 | 0.00 | 23-DEC-07:30 |
General:Humidifier:Water | 427.69 | 0.00 | 06-JUL-15:40 | 0.00 | 23-DEC-07:30 |
MainsWater:Facility | 9629.69 | 0.00 | 31-AUG-23:10 | 0.00 | 28-JUN-16:20 |
MainsWater:HVAC | 427.69 | 0.00 | 06-JUL-15:40 | 0.00 | 23-DEC-07:30 |
Humidifier:MainsWater | 427.69 | 0.00 | 06-JUL-15:40 | 0.00 | 23-DEC-07:30 |
General:Humidifier:MainsWater | 427.69 | 0.00 | 06-JUL-15:40 | 0.00 | 23-DEC-07:30 |
Water:Plant | 9201.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 9201.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 6921.82 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
General:HeatRejection:Water | 6921.82 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
HeatRejection:MainsWater | 6921.82 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
General:HeatRejection:MainsWater | 6921.82 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 62712.80 | 246930.44 | 22-JAN-06:00 | 9451776.37 | 05-SEP-13:10 |
EnergyTransfer:Building | 20809.90 | 89104.39 | 22-JAN-04:40 | 1708766.86 | 07-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 736.17 | 0.00 | 01-JAN-00:10 | 69674.17 | 10-OCT-05:10 |
Heating:EnergyTransfer | 152.75 | 0.00 | 01-JAN-16:10 | 464048.74 | 17-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.09 | 0.00 | 01-JAN-00:10 | 22423.48 | 22-JUL-16:10 |
General:Heating:EnergyTransfer | 152.75 | 0.00 | 01-JAN-16:10 | 464048.74 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.09 | 0.00 | 01-JAN-00:10 | 22423.48 | 22-JUL-16:10 |
Cooling:EnergyTransfer | 20657.15 | 88235.72 | 22-JAN-08:00 | 1708766.86 | 07-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 732.08 | 0.00 | 01-JAN-00:10 | 69674.17 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer | 20657.15 | 88235.72 | 22-JAN-08:00 | 1708766.86 | 07-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 732.08 | 0.00 | 01-JAN-00:10 | 69674.17 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 699.56 | 0.00 | 01-JAN-00:10 | 59968.78 | 21-AUG-10:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 699.56 | 0.00 | 01-JAN-00:10 | 59968.78 | 21-AUG-10:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 699.56 | 0.00 | 01-JAN-00:10 | 59968.78 | 21-AUG-10:20 |
EnergyTransfer:Zone:CORE_MID | 5021.51 | 0.00 | 01-JAN-00:10 | 456358.07 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5021.51 | 0.00 | 01-JAN-00:10 | 456358.07 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5021.51 | 0.00 | 01-JAN-00:10 | 456358.07 | 05-SEP-13:10 |
EnergyTransfer:Zone:CORE_TOP | 465.89 | 0.00 | 01-JAN-00:10 | 55801.66 | 28-JUN-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 2.78 | 0.00 | 01-JAN-00:10 | 52401.11 | 17-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 2.78 | 0.00 | 01-JAN-00:10 | 52401.11 | 17-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 463.12 | 0.00 | 01-JAN-00:10 | 55801.66 | 28-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 463.12 | 0.00 | 01-JAN-00:10 | 55801.66 | 28-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 89.79 | 0.00 | 01-JAN-00:10 | 11471.61 | 07-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 955.09 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 955.09 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 89.79 | 0.00 | 01-JAN-00:10 | 11471.61 | 07-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 89.79 | 0.00 | 01-JAN-00:10 | 11471.61 | 07-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 94.86 | 0.00 | 01-JAN-00:10 | 14235.19 | 05-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1148.14 | 21-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1148.14 | 21-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 94.84 | 0.00 | 01-JAN-00:10 | 14235.19 | 05-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 94.84 | 0.00 | 01-JAN-00:10 | 14235.19 | 05-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 145.00 | 0.00 | 01-JAN-00:10 | 18446.67 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 3822.95 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 3822.95 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 144.96 | 0.00 | 01-JAN-00:10 | 18446.67 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 144.96 | 0.00 | 01-JAN-00:10 | 18446.67 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 132.44 | 0.00 | 01-JAN-00:10 | 19817.10 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 132.44 | 0.00 | 01-JAN-00:10 | 19817.10 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 132.44 | 0.00 | 01-JAN-00:10 | 19817.10 | 21-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 663.69 | 0.00 | 01-JAN-00:10 | 106595.06 | 29-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.73 | 0.00 | 01-JAN-00:10 | 99903.83 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.73 | 0.00 | 01-JAN-00:10 | 99903.83 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 634.96 | 0.00 | 01-JAN-00:10 | 106595.06 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 634.96 | 0.00 | 01-JAN-00:10 | 106595.06 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 839.35 | 0.00 | 01-JAN-00:10 | 149033.37 | 05-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 12.95 | 0.00 | 01-JAN-00:10 | 69241.18 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 12.95 | 0.00 | 01-JAN-00:10 | 69241.18 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 826.40 | 0.00 | 01-JAN-00:10 | 149033.37 | 05-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 826.40 | 0.00 | 01-JAN-00:10 | 149033.37 | 05-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1269.15 | 0.00 | 01-JAN-00:10 | 187340.68 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 7.20 | 0.00 | 01-JAN-00:10 | 90376.63 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 7.20 | 0.00 | 01-JAN-00:10 | 90376.63 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1261.96 | 0.00 | 01-JAN-00:10 | 187340.68 | 28-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1261.96 | 0.00 | 01-JAN-00:10 | 187340.68 | 28-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 840.27 | 0.00 | 01-JAN-00:10 | 166289.84 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.29 | 0.00 | 01-JAN-00:10 | 63114.97 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.29 | 0.00 | 01-JAN-00:10 | 63114.97 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 831.99 | 0.00 | 01-JAN-00:10 | 166289.84 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 831.99 | 0.00 | 01-JAN-00:10 | 166289.84 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 74.55 | 0.00 | 01-JAN-00:10 | 14756.78 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.21 | 0.00 | 01-JAN-00:10 | 14756.78 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.21 | 0.00 | 01-JAN-00:10 | 14756.78 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 61.35 | 0.00 | 01-JAN-00:10 | 12023.27 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 61.35 | 0.00 | 01-JAN-00:10 | 12023.27 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 84.57 | 0.00 | 01-JAN-00:10 | 15244.68 | 05-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.71 | 0.00 | 01-JAN-00:10 | 13105.03 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.71 | 0.00 | 01-JAN-00:10 | 13105.03 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 78.86 | 0.00 | 01-JAN-00:10 | 15244.68 | 05-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 78.86 | 0.00 | 01-JAN-00:10 | 15244.68 | 05-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 124.74 | 0.00 | 01-JAN-00:10 | 20215.52 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.13 | 0.00 | 01-JAN-00:10 | 16646.70 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.13 | 0.00 | 01-JAN-00:10 | 16646.70 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 119.61 | 0.00 | 01-JAN-00:10 | 20215.52 | 28-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 119.61 | 0.00 | 01-JAN-00:10 | 20215.52 | 28-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 84.23 | 0.00 | 01-JAN-00:10 | 17605.12 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.35 | 0.00 | 01-JAN-00:10 | 11751.62 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.35 | 0.00 | 01-JAN-00:10 | 11751.62 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 79.88 | 0.00 | 01-JAN-00:10 | 17605.12 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 79.88 | 0.00 | 01-JAN-00:10 | 17605.12 | 28-JUN-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 81.60 | 0.00 | 01-JAN-00:10 | 11299.19 | 21-AUG-09:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.30 | 0.00 | 01-JAN-00:10 | 3888.45 | 17-DEC-10:00 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.30 | 0.00 | 01-JAN-00:10 | 3888.45 | 17-DEC-10:00 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 80.31 | 0.00 | 01-JAN-00:10 | 11299.19 | 21-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 80.31 | 0.00 | 01-JAN-00:10 | 11299.19 | 21-AUG-09:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 569.87 | 0.00 | 01-JAN-00:10 | 86899.84 | 05-JUL-15:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 34.45 | 0.00 | 01-JAN-00:10 | 46306.80 | 06-FEB-15:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 34.45 | 0.00 | 01-JAN-00:10 | 46306.80 | 06-FEB-15:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 535.42 | 0.00 | 01-JAN-00:10 | 86899.84 | 05-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 535.42 | 0.00 | 01-JAN-00:10 | 86899.84 | 05-JUL-15:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 112.62 | 0.00 | 01-JAN-00:10 | 24424.25 | 28-JUN-13:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.66 | 0.00 | 01-JAN-00:10 | 20472.01 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.66 | 0.00 | 01-JAN-00:10 | 20472.01 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 88.96 | 0.00 | 01-JAN-00:10 | 24424.25 | 28-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 88.96 | 0.00 | 01-JAN-00:10 | 24424.25 | 28-JUN-13:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.74 | 800.00 | 21-JAN-08:00 | 8292.36 | 15-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.74 | 800.00 | 21-JAN-08:00 | 8292.36 | 15-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.74 | 800.00 | 21-JAN-08:00 | 8292.36 | 15-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1256.89 | 13.24 | 01-JAN-05:10 | 78287.71 | 24-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.20 | 0.00 | 01-JAN-00:10 | 4464.90 | 17-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.20 | 0.00 | 01-JAN-00:10 | 4464.90 | 17-JAN-05:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1256.69 | 0.00 | 01-JAN-05:10 | 78287.71 | 24-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1256.69 | 0.00 | 01-JAN-05:10 | 78287.71 | 24-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 118.50 | 3.30 | 20-JAN-09:50 | 7904.06 | 16-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.66 | 0.00 | 01-JAN-16:00 | 689.28 | 18-JAN-01:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.66 | 0.00 | 01-JAN-16:00 | 689.28 | 18-JAN-01:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 117.85 | 0.00 | 01-JAN-00:10 | 7904.06 | 16-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 117.85 | 0.00 | 01-JAN-00:10 | 7904.06 | 16-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7162.89 | 87354.72 | 22-JAN-09:20 | 367562.68 | 18-APR-07:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7162.89 | 87354.72 | 22-JAN-09:20 | 367562.68 | 18-APR-07:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7162.89 | 87354.72 | 22-JAN-09:20 | 367562.68 | 18-APR-07:20 |
PlantLoopHeatingDemand:Facility | 895.05 | 0.00 | 01-JAN-00:10 | 664296.43 | 06-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 400.27 | 0.00 | 01-JAN-00:10 | 50686.82 | 08-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 400.27 | 0.00 | 01-JAN-00:10 | 50686.82 | 08-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 400.27 | 0.00 | 01-JAN-00:10 | 50686.82 | 08-FEB-12:50 |
EnergyTransfer:HVAC | 18897.99 | 154153.81 | 17-JAN-04:40 | 2285782.45 | 23-AUG-16:00 |
HeatingCoils:EnergyTransfer | 494.77 | 0.00 | 01-JAN-00:10 | 647441.77 | 06-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 494.77 | 0.00 | 01-JAN-00:10 | 647441.77 | 06-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 494.77 | 0.00 | 01-JAN-00:10 | 647441.77 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 18403.22 | 141040.48 | 17-JAN-07:10 | 2285782.45 | 23-AUG-16:00 |
EnergyTransfer:Plant | 23004.91 | 0.00 | 01-JAN-00:10 | 6094212.69 | 05-SEP-13:00 |
LoopToLoop:EnergyTransfer | 7387.30 | 0.00 | 01-JAN-00:10 | 1927434.60 | 05-SEP-13:10 |
WaterSystems:EnergyTransfer | 400.27 | 0.00 | 01-JAN-00:10 | 50686.82 | 08-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 400.27 | 0.00 | 01-JAN-00:10 | 50686.82 | 08-FEB-12:50 |
Boilers:EnergyTransfer | 490.41 | 0.00 | 01-JAN-00:10 | 627986.91 | 06-FEB-07:10 |
Chillers:EnergyTransfer | 6862.38 | 0.00 | 01-JAN-00:10 | 1937955.59 | 05-SEP-13:10 |
HeatRejection:EnergyTransfer | 7864.54 | 0.00 | 01-JAN-00:10 | 2199920.28 | 05-SEP-13:10 |
General:HeatRejection:EnergyTransfer | 7864.54 | 0.00 | 01-JAN-00:10 | 2199920.28 | 05-SEP-13:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.092 | -732.070 | 0.000 | 0.000 | 92.678 | 240.449 | 424.397 | 0.000 | 0.000 | 0.000 | 0.007 | 0.000 | 0.000 | 0.000 | 0.000 | -29.546 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -699.553 | 0.000 | 0.000 | 83.426 | 215.940 | 321.286 | 0.000 | 0.000 | 0.000 | 78.901 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5021.473 | 0.000 | 0.000 | 838.320 | 2159.397 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1189.089 |
CORE_TOP | 0.000 | 0.000 | 2.778 | -463.110 | 0.000 | 0.000 | 85.638 | 215.940 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -162.530 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.003 | -89.790 | 0.000 | 0.000 | 10.781 | 18.569 | 40.342 | 33.022 | 0.000 | 0.198 | 36.210 | 0.000 | -44.531 | 0.000 | -4.804 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.021 | -94.840 | 0.000 | 0.000 | 6.976 | 11.959 | 25.998 | 78.294 | 0.000 | 0.143 | 1.764 | 0.000 | -27.164 | 0.000 | -3.150 | -0.001 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.040 | -144.957 | 0.000 | 0.000 | 10.588 | 18.459 | 40.343 | 139.530 | 0.000 | 0.196 | 0.002 | 0.000 | -42.250 | 0.000 | -4.973 | -16.975 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -132.434 | 0.000 | 0.000 | 6.899 | 11.905 | 25.998 | 71.164 | 0.000 | 0.122 | 51.907 | 0.000 | -32.040 | 0.000 | -3.521 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 28.728 | -634.952 | 0.000 | 0.000 | 112.182 | 185.807 | 403.423 | 341.938 | 0.000 | 4.588 | 68.041 | 0.000 | -408.058 | 0.000 | -101.696 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 12.950 | -826.396 | 0.000 | 0.000 | 52.616 | 119.621 | 259.981 | 783.727 | 0.000 | 3.103 | 0.018 | 0.000 | -259.076 | 0.000 | -70.103 | -76.423 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 7.198 | -1261.930 | 0.000 | 0.000 | 106.577 | 184.656 | 403.429 | 1391.669 | 0.000 | 4.429 | 0.000 | 0.000 | -413.052 | 0.000 | -113.225 | -309.750 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 8.286 | -831.968 | 0.000 | 0.000 | 72.544 | 119.081 | 259.979 | 724.725 | 0.000 | 2.938 | 1.102 | 0.000 | -284.192 | 0.000 | -72.497 | -0.016 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 13.209 | -61.344 | 0.000 | 0.000 | 11.417 | 18.581 | 40.342 | 34.690 | 0.000 | 0.543 | 0.001 | 0.000 | -38.315 | 0.000 | -11.756 | -7.367 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 5.708 | -78.857 | 0.000 | 0.000 | 7.218 | 11.962 | 25.998 | 78.653 | 0.000 | 0.360 | 0.001 | 0.000 | -24.658 | 0.000 | -8.228 | -18.157 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.130 | -119.605 | 0.000 | 0.000 | 10.846 | 18.466 | 40.343 | 139.645 | 0.000 | 0.526 | 0.002 | 0.000 | -39.177 | 0.000 | -13.224 | -42.950 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.347 | -79.880 | 0.000 | 0.000 | 7.342 | 11.908 | 25.998 | 72.595 | 0.000 | 0.354 | 0.001 | 0.000 | -27.097 | 0.000 | -8.528 | -7.039 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -141.744 | 0.000 | 0.000 | 0.949 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -19.051 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.197 | -1256.693 | 0.000 | 0.000 | 9.496 | 59.652 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -351.457 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.659 | -117.845 | 0.000 | 0.000 | 0.951 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -43.610 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7162.899 | 0.000 | 0.000 | 19.168 | 67.796 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -418.923 |
GROUNDFLOOR_PLENUM | 1.299 | -80.305 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.350 | 89.041 | 0.000 | 0.000 | 0.000 | -10.385 | 0.000 |
MIDFLOOR_PLENUM | 34.451 | -535.414 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.391 | 672.971 | 0.000 | 0.000 | 0.000 | -178.400 | 0.000 |
TOPFLOOR_PLENUM | 23.660 | -88.960 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.541 | 83.707 | 0.000 | 0.000 | 0.000 | -18.948 | -0.002 |
Total Facility | 59.411 | -704.679 | 93.345 | -19952.340 | 0.000 | 0.000 | 1546.610 | 3702.077 | 15213.411 | 3889.654 | 0.000 | 24.782 | 1083.675 | 0.000 | -1639.610 | 0.000 | -623.436 | -2692.884 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-NOV-04:02 | 0.00 | 0.00 | 0.00 | -116818.99 | 0.00 | 0.00 | 0.00 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 102195.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 05-JUN-03:02 | 0.00 | 0.00 | 0.00 | -94966.37 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.15 | 0.00 | 0.00 | 0.00 | 85861.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-03:02 | 0.00 | 0.00 | 0.00 | -862665.32 | 0.00 | 0.00 | 0.00 | 10475.32 | 80571.20 | 0.00 | 0.00 | 0.00 | 771618.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 10-JUL-03:02 | 0.00 | 0.00 | 0.00 | -87622.07 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.12 | 0.00 | 0.00 | 0.00 | 78517.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 18-JUN-18:11 | 0.00 | 0.00 | 0.00 | -17634.81 | 0.00 | 0.00 | 0.00 | 80.80 | 758.77 | 6577.96 | 0.00 | 132.66 | 10084.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 18-JUN-07:31 | 0.00 | 0.00 | 0.00 | -22645.11 | 0.00 | 0.00 | 19.92 | 52.07 | 488.98 | 18808.42 | 0.00 | 0.00 | 3275.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 23-NOV-12:31 | 0.00 | 0.00 | 0.00 | -23682.88 | 0.00 | 0.00 | 33.35 | 80.80 | 758.78 | 23418.23 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -193.94 | -414.35 |
PERIMETER_BOT_ZN_4 | 18-JUN-16:51 | 0.00 | 0.00 | 0.00 | -30409.47 | 0.00 | 0.00 | 14.95 | 52.07 | 488.98 | 19109.52 | 0.00 | 67.21 | 10676.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUL-17:01 | 0.00 | 0.00 | 0.00 | -169325.20 | 0.00 | 0.00 | 0.00 | 807.98 | 7587.73 | 51748.92 | 0.00 | 8920.52 | 100260.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 25-JUN-09:11 | 0.00 | 0.00 | 0.00 | -246065.96 | 0.00 | 0.00 | 186.37 | 520.69 | 4889.82 | 144272.89 | 0.00 | 0.00 | 96628.45 | 0.00 | -0.00 | 0.00 | -432.26 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-13:01 | 0.00 | 0.00 | 0.00 | -249573.50 | 0.00 | 0.00 | 275.88 | 807.99 | 7587.84 | 223192.70 | 0.00 | 0.00 | 18270.25 | 0.00 | -0.00 | 0.00 | -561.18 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUL-17:01 | 0.00 | 0.00 | 0.00 | -280744.57 | 0.00 | 0.00 | 0.00 | 520.69 | 4889.79 | 188440.63 | 0.00 | 3730.08 | 83163.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-JUL-15:01 | 0.00 | 0.00 | 0.00 | -19930.45 | 0.00 | 0.00 | 38.46 | 80.80 | 758.77 | 4588.40 | 0.00 | 1135.80 | 13328.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-07:41 | 0.00 | 0.00 | 0.00 | -24686.76 | 0.00 | 0.00 | 19.03 | 52.07 | 488.98 | 18493.09 | 0.00 | 0.00 | 5877.08 | 0.00 | -0.00 | 0.00 | -243.49 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-13:12 | 0.00 | 0.00 | 0.00 | -25075.72 | 0.00 | 0.00 | 26.89 | 80.80 | 758.78 | 21878.10 | 0.00 | 0.00 | 2356.97 | 0.00 | -0.00 | 0.00 | -25.83 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-JUL-16:21 | 0.00 | 0.00 | 0.00 | -30425.43 | 0.00 | 0.00 | 13.00 | 52.07 | 488.98 | 19210.85 | 0.00 | 415.44 | 10245.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 15-APR-18:00 | 0.00 | 0.00 | 0.00 | -8292.40 | 0.00 | 0.00 | 5.31 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 463.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 24-APR-18:00 | 0.00 | 0.00 | 0.00 | -78281.04 | 0.00 | 0.00 | 106.16 | 1736.14 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1505.47 |
DATACENTER_TOP_ZN_6 | 16-APR-17:51 | 0.00 | 0.00 | 0.00 | -7907.93 | 0.00 | 0.00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 84.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 18-APR-07:15 | 0.00 | 0.00 | 0.00 | -367581.66 | 0.00 | 0.00 | 2007.53 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19977.98 |
GROUNDFLOOR_PLENUM | 21-AUG-05:15 | 0.00 | -14955.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15061.39 | 0.00 | -0.00 | 0.00 | -106.02 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-05:15 | 0.00 | -86989.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87302.72 | 0.00 | -0.00 | 0.00 | -313.65 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-13:30 | 0.00 | -24418.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.78 | 24218.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-AUG-03:02 | 0.00 | 63726.83 | 0.00 | -2039591.18 | 0.00 | 0.00 | 0.00 | 19603.93 | 623236.89 | 0.00 | 0.00 | 0.00 | 1367685.75 | 0.00 | -34662.21 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-JUL-16:02 | 0.00 | 0.00 | 23718.85 | 0.00 | 0.00 | 0.00 | 520.13 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -38862.95 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JAN-04:01 | 0.00 | 0.00 | 76148.48 | 0.00 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -85253.13 |
PERIMETER_BOT_ZN_3 | 17-JAN-06:01 | 0.00 | 0.00 | 6859.74 | 0.00 | 0.00 | 0.00 | 141.06 | 263.06 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4110.39 | 0.00 | -304.17 | -3860.99 |
PERIMETER_BOT_ZN_2 | 22-DEC-06:01 | 0.00 | 0.00 | 6091.91 | 0.00 | 0.00 | 0.00 | 94.15 | 169.52 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3008.03 | 0.00 | -110.06 | -3889.46 |
PERIMETER_BOT_ZN_1 | 17-JAN-06:01 | 0.00 | 0.00 | 11022.04 | 0.00 | 0.00 | 0.00 | 147.97 | 263.06 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3804.23 | 0.00 | -293.62 | -8346.93 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 17-JAN-04:01 | 0.00 | 0.00 | 137329.83 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.28 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34047.94 | 0.00 | -26133.54 | -88580.60 |
PERIMETER_MID_ZN_2 | 17-JAN-04:01 | 0.00 | 0.00 | 150873.31 | 0.00 | 0.00 | 0.00 | 0.00 | 847.62 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22818.16 | 0.00 | -17769.95 | -117652.57 |
PERIMETER_MID_ZN_1 | 17-JAN-04:01 | 0.00 | 0.00 | 161516.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.31 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34652.65 | 0.00 | -27649.47 | -110646.63 |
PERIMETER_MID_ZN_4 | 17-JAN-04:01 | 0.00 | 0.00 | 143819.96 | 0.00 | 0.00 | 0.00 | 0.00 | 847.62 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22834.36 | 0.00 | -18397.56 | -109955.37 |
PERIMETER_TOP_ZN_3 | 06-FEB-03:42 | 0.00 | 0.00 | 16842.20 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3339.89 | 0.00 | -2296.18 | -12349.35 |
PERIMETER_TOP_ZN_2 | 17-JAN-04:01 | 0.00 | 0.00 | 18655.90 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1998.19 | 0.00 | -2044.38 | -15350.06 |
PERIMETER_TOP_ZN_1 | 17-JAN-04:01 | 0.00 | 0.00 | 19912.57 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2948.83 | 0.00 | -3052.59 | -15054.39 |
PERIMETER_TOP_ZN_4 | 17-JAN-04:01 | 0.00 | 0.00 | 19432.24 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1983.83 | 0.00 | -2082.64 | -16102.49 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 19-JAN-04:07 | 0.00 | 0.00 | 5116.71 | 0.00 | 0.00 | 0.00 | 0.00 | 289.38 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24892.14 |
DATACENTER_TOP_ZN_6 | 18-JAN-01:40 | 0.00 | 0.00 | 689.28 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2666.82 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 14-DEC-04:01 | 14298.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4404.76 | -9893.37 |
MIDFLOOR_PLENUM | 04-JUL-16:21 | 86153.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14773.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -100926.96 |
TOPFLOOR_PLENUM | 06-FEB-05:12 | 25210.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3787.71 | -21422.85 |
Total Facility | 17-JAN-04:01 | -413929.73 | 351828.33 | 749513.26 | -351828.33 | 0.00 | 0.00 | 0.00 | 19603.93 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -137679.28 | 0.00 | -160721.28 | -325149.60 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 13.1809 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.8690 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 125.1895 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 110.5687 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.8931 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.1233 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.9927 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.9927 | 0.1716 | 1.0000 | Not calculated | 1.2002 | 0.1716 | ||
AIRLOOP DATACENTER BASEMENT | 26.0536 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 26.0539 | 0.0130 | 1.0000 | Not calculated | 0.3384 | 0.0130 | ||
AIRLOOP DATACENTER BOT | 0.5945 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5945 | 0.0263 | 1.0000 | Not calculated | 0.0156 | 0.0263 | ||
AIRLOOP DATACENTER MID | 5.6806 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.6806 | 0.0275 | 1.0000 | Not calculated | 0.1563 | 0.0275 | ||
AIRLOOP DATACENTER TOP | 0.5803 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5803 | 0.0269 | 1.0000 | Not calculated | 0.0156 | 0.0269 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.5904 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.9543 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 62.5948 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 37.5569 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.4466 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.8949 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.9927 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.9927 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1716 | ||
AIRLOOP DATACENTER BASEMENT | 26.0536 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 26.0536 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0130 | ||
AIRLOOP DATACENTER BOT | 0.5945 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5945 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0263 | ||
AIRLOOP DATACENTER MID | 5.6806 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.6806 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0275 | ||
AIRLOOP DATACENTER TOP | 0.5803 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5803 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0269 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.9927 | 6.9927 | 6.9927 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.2706 | 7.2706 | 2.1812 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 68.3913 | 68.3913 | 20.5174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7453 | 6.7453 | 2.0506 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2285 | 1.2285 | 0.3685 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4105 | 1.4105 | 0.4231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4951 | 1.4951 | 0.4485 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7763 | 1.7763 | 0.5329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.6155 | 11.6155 | 3.4846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.8339 | 14.8339 | 4.4502 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.3881 | 14.3881 | 4.3164 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.9607 | 15.9607 | 4.7882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3338 | 1.3338 | 0.4001 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5042 | 1.5042 | 0.4512 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5969 | 1.5969 | 0.4791 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7130 | 1.7130 | 0.5139 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5945 | 0.5945 | 0.5945 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.6806 | 5.6806 | 5.6806 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5803 | 0.5803 | 0.5803 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 26.0536 | 26.0536 | 26.0536 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 13.1809 | 11.8690 | 13.1809 | 3.9543 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 125.1895 | 110.5687 | 125.1895 | 37.5569 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.8931 | 12.1233 | 12.8931 | 3.8949 | 0.0000 | 1.0000 |
CAV_BAS | 6.9927 | 6.9927 | 6.9927 | 6.9927 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.0536 | 26.0539 | 26.0536 | 26.0536 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5945 | 0.5945 | 0.5945 | 0.5945 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.6806 | 5.6806 | 5.6806 | 5.6806 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5803 | 0.5803 | 0.5803 | 0.5803 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.9927 | 6.9927 | 6.9927 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.6353 | 3.6353 | 2.1812 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 34.1957 | 34.1957 | 20.5174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3726 | 3.3726 | 2.0506 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6142 | 0.6142 | 0.3685 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7052 | 0.7052 | 0.4231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7476 | 0.7476 | 0.4485 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8881 | 0.8881 | 0.5329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8077 | 5.8077 | 3.4846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.4170 | 7.4170 | 4.4502 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.1940 | 7.1940 | 4.3164 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.9804 | 7.9804 | 4.7882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6669 | 0.6669 | 0.4001 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7521 | 0.7521 | 0.4512 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7985 | 0.7985 | 0.4791 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8565 | 0.8565 | 0.5139 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5945 | 0.5945 | 0.5945 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.6806 | 5.6806 | 5.6806 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5803 | 0.5803 | 0.5803 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 26.0536 | 26.0536 | 26.0536 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.5904 | 3.9543 | 3.9543 | 3.9543 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 62.5948 | 37.5569 | 37.5569 | 37.5569 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.4466 | 3.8949 | 3.8949 | 3.8949 | 0.0000 | 1.0000 |
CAV_BAS | 6.9927 | 6.9927 | 6.9927 | 6.9927 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.0536 | 26.0536 | 26.0536 | 26.0536 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5945 | 0.5945 | 0.5945 | 0.5945 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.6806 | 5.6806 | 5.6806 | 5.6806 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5803 | 0.5803 | 0.5803 | 0.5803 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 8.67 |
Number of hours cooling loads not met | 1543.50 |
Number of hours not met | 1549.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 679.70 | 753815.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 4091.14 | 436579.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3702.08 | 352853.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 670.69 | 54335.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.32 | 5481.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 3008.25 | 306490.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 617.32 | 70368.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1157.48 | 82925.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1149.71 | 75188.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 692.98 | 81613.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 31552.01 |
Natural Gas | 0.00 | 1372.68 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 32924.69 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 79.92 |
Space Heating | 0.00 |
Space Cooling | 88.32 |
Fans (All) | 64.94 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 681.17 |
Subtotal | 681.17 |
Natural Gas [MJ/m2] | |
Space Heating | 14.67 |
Service Water Heating | 14.96 |
Miscellaneous (All) | 29.63 |
Subtotal | 29.63 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.24 |
Space Heating | 2.06 |
Space Cooling | 12.43 |
Fans (All) | 9.14 |
Service Water Heating | 2.10 |
Receptacle Equipment | 46.21 |
Miscellaneous | 16.82 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2645. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8596.33 | 163.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8713.00 | 47.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8721.50 | 38.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8592.17 | 167.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8694.83 | 65.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8718.67 | 41.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8682.17 | 77.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8686.83 | 73.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8721.67 | 38.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8682.17 | 77.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8676.33 | 83.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8728.17 | 31.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8736.17 | 23.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6682.00 | 2003.17 | 74.83 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8655.50 | 104.50 | 0.00 | 0.00 | 0.00 |
Min | 6682.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2003.17 | 74.83 | 0.00 | 0.00 |
Average | 8623.19 | 133.56 | 3.25 | 0.00 | 0.00 |
Sum | 198333.33 | 3071.83 | 74.83 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368018.67 | 597.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330802.00 | 11.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2233.50 | 34.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2256.17 | 11.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2261.50 | 6.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 79176.33 | 23099.17 | 1119.50 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368018.67 | 23099.17 | 1119.50 | 0.00 | 0.00 |
Average | 79253.18 | 1033.06 | 48.67 | 0.00 | 0.00 |
Sum | 1822823.17 | 23760.33 | 1119.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8492.17 | 267.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8661.67 | 98.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8652.50 | 107.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8655.67 | 104.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8677.17 | 82.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8674.17 | 85.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8661.50 | 98.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8548.00 | 212.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8685.33 | 74.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8606.17 | 153.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8637.83 | 122.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8603.33 | 156.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8679.00 | 81.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8603.33 | 156.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8641.00 | 119.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8608.50 | 151.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7538.83 | 1221.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8628.50 | 131.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8692.17 | 67.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8547.67 | 212.33 | 0.00 | 0.00 | 0.00 |
Min | 7538.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1221.17 | 0.00 | 0.00 | 0.00 |
Average | 8598.78 | 161.22 | 0.00 | 0.00 | 0.00 |
Sum | 197771.83 | 3708.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367722.67 | 893.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330652.00 | 161.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330687.00 | 126.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330693.00 | 120.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 88740.83 | 14654.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367722.67 | 14654.17 | 0.00 | 0.00 | 0.00 |
Average | 79641.24 | 693.67 | 0.00 | 0.00 | 0.00 |
Sum | 1831748.50 | 15954.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:10
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.535301E+11 | 115516.25 | 17-JAN-04:01 | -3.3 | -5.0 | 0.566517E+10 | 7499.06 | 13-JAN-10:20 | -3.3 | -5.0 |
February | 0.489877E+11 | 111319.28 | 13-FEB-04:02 | 1.10 | -1.6 | 0.513885E+10 | 7499.07 | 01-FEB-10:00 | 1.10 | -1.6 |
March | 0.598615E+11 | 113788.04 | 27-MAR-03:02 | 5.50 | 0.89 | 0.613365E+10 | 7498.99 | 02-MAR-14:09 | 5.50 | 0.89 |
April | 0.582489E+11 | 114307.10 | 03-APR-03:02 | 9.22 | 2.19 | 0.545165E+10 | 7499.01 | 26-APR-13:20 | 24.80 | 9.90 |
May | 0.605353E+11 | 109460.82 | 01-MAY-03:02 | 11.85 | 8.24 | 0.590266E+10 | 7536.19 | 22-MAY-09:50 | 24.13 | 14.54 |
June | 0.624765E+11 | 106368.80 | 20-JUN-03:02 | 10.78 | 4.69 | 0.588376E+10 | 7499.13 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.638662E+11 | 93731.80 | 04-JUL-17:05 | 35.73 | 14.63 | 0.547615E+10 | 7499.01 | 28-JUL-09:09 | 24.68 | 16.51 |
August | 0.735816E+11 | 96157.38 | 29-AUG-03:02 | 16.10 | 12.92 | 0.614106E+10 | 7522.11 | 28-AUG-13:09 | 16.10 | 12.92 |
September | 0.639652E+11 | 109359.61 | 11-SEP-03:02 | 13.90 | 9.80 | 0.545505E+10 | 7558.19 | 11-SEP-09:00 | 23.30 | 14.32 |
October | 0.659684E+11 | 112941.26 | 23-OCT-03:02 | 8.22 | 7.00 | 0.567350E+10 | 7499.10 | 24-OCT-13:50 | 8.87 | 4.55 |
November | 0.618374E+11 | 116836.16 | 06-NOV-04:02 | 2.62 | -1.0 | 0.561588E+10 | 7498.92 | 08-NOV-10:39 | 13.70 | 6.24 |
December | 0.592170E+11 | 115757.71 | 11-DEC-04:01 | 2.12 | -2.0 | 0.547195E+10 | 7498.99 | 15-DEC-10:09 | -2.3 | -7.0 |
Annual Sum or Average | 0.732076E+12 | 0.680093E+11 | ||||||||
Minimum of Months | 0.489877E+11 | 93731.80 | -3.3 | -5.0 | 0.513885E+10 | 7498.92 | -3.3 | -7.0 | ||
Maximum of Months | 0.735816E+11 | 116836.16 | 35.73 | 14.63 | 0.614106E+10 | 7558.19 | 26.70 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419723E+11 | 87590.30 | 03-JAN-05:01 | -0.8 | -2.3 | 0.506517E+10 | 6734.73 | 24-JAN-10:09 | 8.07 | 2.63 |
February | 0.416656E+11 | 90101.37 | 21-FEB-04:02 | 2.70 | 0.07 | 0.460224E+10 | 6734.75 | 15-FEB-10:09 | 2.70 | 0.07 |
March | 0.566350E+11 | 91514.76 | 27-MAR-03:02 | 5.50 | 0.89 | 0.549902E+10 | 6734.70 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.641762E+11 | 94903.49 | 24-APR-03:02 | 5.18 | 2.43 | 0.488165E+10 | 6734.79 | 17-APR-13:00 | 5.18 | 2.43 |
May | 0.576358E+11 | 93136.89 | 30-MAY-03:01 | 14.82 | 11.26 | 0.528561E+10 | 6735.01 | 11-MAY-09:09 | 14.82 | 11.26 |
June | 0.653778E+11 | 94955.14 | 05-JUN-03:02 | 15.00 | 13.28 | 0.526833E+10 | 6734.83 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.701977E+11 | 88285.75 | 18-JUL-03:02 | 20.60 | 15.47 | 0.489421E+10 | 6734.78 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.831661E+11 | 89038.88 | 19-AUG-05:03 | 19.22 | 11.93 | 0.549585E+10 | 6766.16 | 21-AUG-09:00 | 26.70 | 17.15 |
September | 0.576398E+11 | 94546.74 | 18-SEP-03:02 | 14.90 | 11.31 | 0.488401E+10 | 6734.82 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.575461E+11 | 94577.61 | 23-OCT-03:02 | 8.22 | 7.00 | 0.507808E+10 | 6734.83 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.530226E+11 | 92106.12 | 13-NOV-04:02 | 0.00 | -1.8 | 0.502725E+10 | 6734.69 | 27-NOV-10:09 | 1.28 | -3.1 |
December | 0.505223E+11 | 93165.18 | 26-DEC-04:01 | 0.32 | -0.9 | 0.490103E+10 | 6734.74 | 26-DEC-10:09 | 2.38 | 0.81 |
Annual Sum or Average | 0.699557E+12 | 0.608824E+11 | ||||||||
Minimum of Months | 0.416656E+11 | 87590.30 | -0.8 | -2.3 | 0.460224E+10 | 6734.69 | 1.28 | -3.1 | ||
Maximum of Months | 0.831661E+11 | 94955.14 | 20.60 | 15.47 | 0.549902E+10 | 6766.16 | 26.70 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294695E+11 | 71838.03 | 27-JAN-06:02 | -6.0 | -8.3 | 0.495483E+10 | 6734.73 | 24-JAN-10:09 | -6.0 | -8.3 |
February | 0.285865E+11 | 77184.35 | 15-FEB-06:03 | 6.93 | 2.40 | 0.453423E+10 | 6734.71 | 01-FEB-10:00 | 6.93 | 2.40 |
March | 0.385605E+11 | 79463.26 | 09-MAR-06:02 | 4.40 | 1.00 | 0.546607E+10 | 6734.67 | 01-MAR-10:09 | 4.40 | 1.00 |
April | 0.413583E+11 | 81540.08 | 14-APR-04:02 | 9.72 | 2.54 | 0.487003E+10 | 6734.73 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.477699E+11 | 84706.24 | 22-MAY-03:01 | 18.22 | 12.62 | 0.527848E+10 | 6734.98 | 11-MAY-09:09 | 18.22 | 12.62 |
June | 0.523539E+11 | 84585.57 | 30-JUN-03:02 | 18.03 | 12.61 | 0.526517E+10 | 6734.84 | 08-JUN-13:09 | 18.03 | 12.61 |
July | 0.531745E+11 | 85748.41 | 10-JUL-03:02 | 20.00 | 15.66 | 0.489294E+10 | 6734.77 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.561933E+11 | 84934.90 | 09-AUG-03:02 | 17.88 | 15.13 | 0.549528E+10 | 6735.87 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.477725E+11 | 86267.45 | 05-SEP-03:02 | 17.80 | 15.22 | 0.487818E+10 | 6734.80 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.430408E+11 | 83063.93 | 06-OCT-03:01 | 13.98 | 7.66 | 0.505909E+10 | 6734.76 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.343198E+11 | 76720.84 | 09-NOV-06:03 | 12.20 | 7.74 | 0.498468E+10 | 6734.70 | 27-NOV-10:09 | 1.28 | -3.1 |
December | 0.295519E+11 | 73895.80 | 01-DEC-06:03 | 3.90 | -0.5 | 0.479751E+10 | 6734.71 | 15-DEC-10:09 | -2.3 | -7.0 |
Annual Sum or Average | 0.502151E+12 | 0.604765E+11 | ||||||||
Minimum of Months | 0.285865E+11 | 71838.03 | -6.0 | -8.3 | 0.453423E+10 | 6734.67 | -6.0 | -8.3 | ||
Maximum of Months | 0.561933E+11 | 86267.45 | 20.00 | 15.66 | 0.549528E+10 | 6735.87 | 25.37 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212063E+11 | 27544.38 | 05-JAN-17:00 | 13.30 | 5.53 | 0.447681E+10 | 6734.36 | 11-JAN-14:00 | 7.80 | 1.41 |
February | 0.213903E+11 | 37700.64 | 15-FEB-16:40 | 16.87 | 6.07 | 0.422364E+10 | 6734.61 | 15-FEB-10:09 | 16.87 | 6.07 |
March | 0.310710E+11 | 39716.38 | 08-MAR-16:50 | 22.30 | 8.39 | 0.530390E+10 | 6734.62 | 02-MAR-14:09 | 22.30 | 8.39 |
April | 0.376215E+11 | 76848.19 | 28-APR-05:03 | 11.93 | 4.35 | 0.482434E+10 | 6734.76 | 17-APR-13:00 | 11.93 | 4.35 |
May | 0.466716E+11 | 84782.86 | 22-MAY-03:01 | 18.22 | 12.62 | 0.526145E+10 | 6734.92 | 11-MAY-09:09 | 18.22 | 12.62 |
June | 0.555260E+11 | 83946.53 | 30-JUN-03:02 | 18.03 | 12.61 | 0.526312E+10 | 6811.25 | 28-JUN-13:00 | 18.03 | 12.61 |
July | 0.586616E+11 | 87633.43 | 10-JUL-03:02 | 20.00 | 15.66 | 0.489680E+10 | 6734.75 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.604335E+11 | 85753.31 | 14-AUG-03:02 | 19.32 | 16.70 | 0.549742E+10 | 6735.92 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.475239E+11 | 87167.42 | 05-SEP-03:02 | 17.80 | 15.22 | 0.487321E+10 | 6734.76 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.367824E+11 | 78361.50 | 04-OCT-05:02 | 12.80 | 7.65 | 0.497440E+10 | 6734.71 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.255851E+11 | 50944.78 | 01-NOV-05:03 | 7.70 | 5.59 | 0.473660E+10 | 6734.61 | 08-NOV-10:39 | 13.70 | 6.24 |
December | 0.206426E+11 | 27709.41 | 01-DEC-17:00 | 12.20 | 4.22 | 0.433918E+10 | 6734.36 | 01-DEC-14:00 | 12.20 | 4.22 |
Annual Sum or Average | 0.463116E+12 | 0.586709E+11 | ||||||||
Minimum of Months | 0.206426E+11 | 27544.38 | 7.70 | 4.22 | 0.422364E+10 | 6734.36 | 7.80 | 1.41 | ||
Maximum of Months | 0.604335E+11 | 87633.43 | 22.30 | 16.70 | 0.549742E+10 | 6811.25 | 25.73 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.360224E+10 | 3870.59 | 02-JAN-15:00 | 14.40 | 5.68 | 0.548875E+09 | 822.17 | 24-JAN-14:00 | 16.10 | 4.97 |
February | 0.364298E+10 | 4529.72 | 15-FEB-13:20 | 15.77 | 6.33 | 0.521383E+09 | 845.60 | 27-FEB-14:09 | 11.28 | 4.26 |
March | 0.548556E+10 | 6584.23 | 27-MAR-14:30 | 18.05 | 6.97 | 0.666657E+09 | 845.63 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.780803E+10 | 8633.67 | 14-APR-14:00 | 23.30 | 10.26 | 0.606703E+09 | 845.64 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.805641E+10 | 13225.29 | 22-MAY-05:03 | 16.78 | 12.20 | 0.660400E+09 | 845.65 | 11-MAY-09:09 | 16.78 | 12.20 |
June | 0.115045E+11 | 17635.56 | 18-JUN-18:11 | 29.43 | 10.52 | 0.661548E+09 | 845.65 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.128092E+11 | 17305.84 | 04-JUL-18:31 | 32.77 | 13.53 | 0.615311E+09 | 846.26 | 31-JUL-13:20 | 29.80 | 18.31 |
August | 0.138182E+11 | 15635.47 | 20-AUG-15:41 | 35.00 | 15.92 | 0.690207E+09 | 850.10 | 21-AUG-09:00 | 26.70 | 17.15 |
September | 0.810500E+10 | 8694.75 | 01-SEP-15:30 | 28.60 | 16.32 | 0.611182E+09 | 845.63 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.629760E+10 | 13312.75 | 02-OCT-05:03 | 17.12 | 12.75 | 0.619531E+09 | 845.64 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.466500E+10 | 4912.55 | 03-NOV-13:30 | 11.95 | 2.20 | 0.594668E+09 | 845.61 | 21-NOV-14:09 | 15.18 | 5.79 |
December | 0.399658E+10 | 3887.76 | 11-DEC-13:30 | 8.30 | 1.56 | 0.541717E+09 | 845.60 | 01-DEC-14:09 | 8.30 | 1.56 |
Annual Sum or Average | 0.897913E+11 | 0.733818E+10 | ||||||||
Minimum of Months | 0.360224E+10 | 3870.59 | 8.30 | 1.56 | 0.521383E+09 | 822.17 | 8.30 | 1.56 | ||
Maximum of Months | 0.138182E+11 | 17635.56 | 35.00 | 16.32 | 0.690207E+09 | 850.10 | 29.80 | 18.31 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400044E+10 | 6526.47 | 02-JAN-09:25 | 2.75 | -0.6 | 0.353919E+09 | 544.95 | 24-JAN-10:09 | 8.07 | 2.63 |
February | 0.420271E+10 | 8847.36 | 14-FEB-09:05 | 7.25 | 1.90 | 0.335237E+09 | 544.96 | 15-FEB-10:09 | 11.38 | 5.33 |
March | 0.636653E+10 | 18768.53 | 12-MAR-08:52 | 7.20 | 0.83 | 0.424868E+09 | 544.95 | 21-MAR-09:09 | 14.40 | 6.68 |
April | 0.897484E+10 | 21725.41 | 30-APR-08:51 | 15.60 | 4.83 | 0.391040E+09 | 546.29 | 28-APR-09:50 | 15.60 | 4.83 |
May | 0.921453E+10 | 21930.82 | 14-MAY-08:11 | 19.63 | 9.03 | 0.425154E+09 | 545.95 | 15-MAY-09:50 | 20.92 | 9.24 |
June | 0.116371E+11 | 22647.30 | 18-JUN-07:31 | 22.23 | 11.31 | 0.425550E+09 | 546.09 | 27-JUN-09:00 | 30.00 | 15.78 |
July | 0.122944E+11 | 21061.04 | 04-JUL-08:32 | 25.93 | 18.46 | 0.396056E+09 | 546.18 | 14-JUL-09:50 | 26.93 | 17.09 |
August | 0.126792E+11 | 20889.70 | 20-AUG-08:22 | 25.25 | 15.06 | 0.443493E+09 | 549.71 | 21-AUG-09:00 | 26.70 | 17.15 |
September | 0.887267E+10 | 21316.42 | 17-SEP-09:12 | 18.33 | 13.15 | 0.392353E+09 | 546.10 | 11-SEP-09:09 | 18.33 | 13.15 |
October | 0.717353E+10 | 21183.40 | 01-OCT-08:52 | 17.80 | 11.25 | 0.395631E+09 | 544.97 | 18-OCT-09:09 | 12.35 | 5.73 |
November | 0.526002E+10 | 9136.07 | 01-NOV-08:50 | 9.63 | 6.30 | 0.373824E+09 | 544.95 | 27-NOV-10:09 | 1.28 | -3.1 |
December | 0.416404E+10 | 6067.22 | 29-DEC-09:15 | 1.67 | -0.9 | 0.343959E+09 | 544.95 | 26-DEC-10:09 | 1.67 | -0.9 |
Annual Sum or Average | 0.948400E+11 | 0.470108E+10 | ||||||||
Minimum of Months | 0.400044E+10 | 6067.22 | 1.67 | -0.9 | 0.335237E+09 | 544.95 | 1.28 | -3.1 | ||
Maximum of Months | 0.126792E+11 | 22647.30 | 25.93 | 18.46 | 0.443493E+09 | 549.71 | 30.00 | 17.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.922974E+10 | 22866.33 | 01-JAN-12:12 | 11.50 | 3.97 | 0.602630E+09 | 880.09 | 23-JAN-14:09 | 14.60 | 4.35 |
February | 0.934456E+10 | 23104.53 | 19-FEB-12:42 | 14.63 | 6.08 | 0.558576E+09 | 904.51 | 14-FEB-14:09 | 14.63 | 6.08 |
March | 0.105235E+11 | 22531.69 | 12-MAR-13:32 | 17.43 | 5.83 | 0.672755E+09 | 847.18 | 20-MAR-13:00 | 18.30 | 8.36 |
April | 0.116259E+11 | 21623.52 | 30-APR-13:32 | 21.33 | 7.45 | 0.605586E+09 | 847.57 | 17-APR-13:00 | 21.33 | 7.45 |
May | 0.960430E+10 | 13440.28 | 22-MAY-05:03 | 16.78 | 12.20 | 0.656801E+09 | 845.67 | 09-MAY-13:20 | 16.78 | 12.20 |
June | 0.118791E+11 | 14560.43 | 18-JUN-14:11 | 31.70 | 11.43 | 0.659550E+09 | 845.67 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.141686E+11 | 20887.75 | 30-JUL-14:22 | 32.75 | 17.84 | 0.615084E+09 | 846.35 | 25-JUL-13:39 | 32.75 | 17.84 |
August | 0.175267E+11 | 21607.69 | 20-AUG-15:01 | 35.00 | 15.71 | 0.690526E+09 | 851.75 | 31-AUG-13:09 | 29.50 | 15.73 |
September | 0.140376E+11 | 23039.12 | 17-SEP-13:12 | 23.90 | 14.61 | 0.614172E+09 | 926.21 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.141527E+11 | 23414.81 | 01-OCT-12:11 | 26.13 | 14.41 | 0.636123E+09 | 933.10 | 31-OCT-13:30 | 21.40 | 8.63 |
November | 0.118342E+11 | 23680.33 | 23-NOV-12:31 | 13.33 | 4.25 | 0.624474E+09 | 931.82 | 01-NOV-13:09 | 13.33 | 4.25 |
December | 0.110326E+11 | 22499.60 | 31-DEC-13:22 | 9.15 | 1.31 | 0.595860E+09 | 892.90 | 29-DEC-14:09 | 9.15 | 1.31 |
Annual Sum or Average | 0.144960E+12 | 0.753214E+10 | ||||||||
Minimum of Months | 0.922974E+10 | 13440.28 | 9.15 | 1.31 | 0.558576E+09 | 845.67 | 9.15 | 1.31 | ||
Maximum of Months | 0.175267E+11 | 23680.33 | 35.00 | 17.84 | 0.690526E+09 | 933.10 | 32.75 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.571086E+10 | 9109.10 | 26-JAN-16:30 | 10.30 | 1.40 | 0.355642E+09 | 544.93 | 10-JAN-14:00 | 10.30 | 1.40 |
February | 0.645747E+10 | 15553.99 | 12-FEB-15:02 | 18.30 | 6.40 | 0.342367E+09 | 544.94 | 27-FEB-14:09 | 11.28 | 4.26 |
March | 0.933496E+10 | 25191.71 | 12-MAR-16:12 | 19.80 | 6.19 | 0.434283E+09 | 544.96 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.135931E+11 | 27176.74 | 16-APR-16:31 | 20.20 | 8.02 | 0.395124E+09 | 544.97 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.105267E+11 | 27954.15 | 14-MAY-15:31 | 28.30 | 11.12 | 0.421938E+09 | 544.97 | 09-MAY-13:20 | 28.30 | 11.12 |
June | 0.141182E+11 | 30411.24 | 18-JUN-16:51 | 31.70 | 11.85 | 0.426140E+09 | 544.97 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.161335E+11 | 28329.83 | 04-JUL-16:31 | 35.93 | 14.49 | 0.397029E+09 | 544.97 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.205171E+11 | 28940.98 | 20-AUG-15:41 | 35.00 | 15.92 | 0.446008E+09 | 549.31 | 21-AUG-09:00 | 26.70 | 17.15 |
September | 0.106387E+11 | 25182.86 | 17-SEP-14:32 | 23.90 | 14.61 | 0.392593E+09 | 544.96 | 19-SEP-13:09 | 25.18 | 14.10 |
October | 0.984001E+10 | 25555.98 | 01-OCT-14:51 | 28.30 | 12.89 | 0.398811E+09 | 544.97 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.803175E+10 | 24712.85 | 12-NOV-15:02 | 9.40 | 2.60 | 0.391427E+09 | 544.95 | 21-NOV-14:09 | 15.18 | 5.79 |
December | 0.753370E+10 | 14039.14 | 31-DEC-15:22 | 10.55 | 1.85 | 0.376295E+09 | 544.94 | 11-DEC-14:30 | 10.55 | 1.85 |
Annual Sum or Average | 0.132436E+12 | 0.477766E+10 | ||||||||
Minimum of Months | 0.571086E+10 | 9109.10 | 9.40 | 1.40 | 0.342367E+09 | 544.93 | 10.30 | 1.40 | ||
Maximum of Months | 0.205171E+11 | 30411.24 | 35.93 | 15.92 | 0.446008E+09 | 549.31 | 28.30 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166496E+10 | 3232.15 | 05-JAN-15:30 | 16.10 | 6.84 | 0.482138E+09 | 719.52 | 04-JAN-14:00 | 16.10 | 6.84 |
February | 0.198973E+10 | 3648.20 | 15-FEB-15:50 | 17.20 | 6.53 | 0.453158E+09 | 785.71 | 15-FEB-14:00 | 17.20 | 6.53 |
March | 0.344677E+10 | 4029.12 | 27-MAR-14:50 | 18.22 | 7.02 | 0.601640E+09 | 845.62 | 28-MAR-13:20 | 16.13 | 7.51 |
April | 0.472216E+10 | 7231.55 | 14-APR-14:30 | 23.60 | 10.45 | 0.583468E+09 | 845.63 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.653831E+10 | 8105.17 | 31-MAY-16:00 | 28.30 | 11.06 | 0.652525E+09 | 845.64 | 09-MAY-13:20 | 28.30 | 11.06 |
June | 0.962521E+10 | 16580.62 | 25-JUN-17:51 | 32.80 | 15.93 | 0.660273E+09 | 845.65 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.103413E+11 | 16936.43 | 04-JUL-17:01 | 35.73 | 14.63 | 0.615378E+09 | 845.95 | 31-JUL-13:30 | 30.00 | 18.38 |
August | 0.971055E+10 | 12556.85 | 06-AUG-14:42 | 29.87 | 16.39 | 0.689537E+09 | 845.79 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.663322E+10 | 9844.08 | 05-SEP-05:03 | 15.92 | 14.88 | 0.606744E+09 | 845.62 | 22-SEP-13:09 | 27.98 | 16.22 |
October | 0.456104E+10 | 7230.92 | 02-OCT-13:40 | 26.33 | 15.37 | 0.581615E+09 | 845.62 | 04-OCT-13:50 | 25.32 | 13.57 |
November | 0.282659E+10 | 3651.35 | 02-NOV-15:30 | 16.95 | 9.55 | 0.515927E+09 | 830.02 | 03-NOV-13:00 | 12.20 | 2.42 |
December | 0.143634E+10 | 3068.10 | 29-DEC-15:50 | 11.60 | 3.89 | 0.458762E+09 | 760.16 | 01-DEC-14:00 | 11.60 | 3.89 |
Annual Sum or Average | 0.634961E+11 | 0.690116E+10 | ||||||||
Minimum of Months | 0.143634E+10 | 3068.10 | 11.60 | 3.89 | 0.453158E+09 | 719.52 | 11.60 | 2.42 | ||
Maximum of Months | 0.103413E+11 | 16936.43 | 35.73 | 16.39 | 0.689537E+09 | 845.95 | 30.00 | 18.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256110E+10 | 4465.31 | 27-JAN-11:10 | 6.28 | -0.7 | 0.235299E+09 | 521.18 | 27-JAN-09:00 | 6.28 | -0.7 |
February | 0.303378E+10 | 7278.24 | 14-FEB-09:40 | 8.90 | 2.72 | 0.223598E+09 | 521.19 | 14-FEB-09:09 | 8.90 | 2.72 |
March | 0.519260E+10 | 16279.80 | 26-MAR-09:12 | 11.87 | 4.49 | 0.293040E+09 | 521.20 | 10-MAR-11:09 | 11.87 | 4.49 |
April | 0.753377E+10 | 23035.87 | 30-APR-08:51 | 15.60 | 4.83 | 0.284809E+09 | 521.67 | 27-APR-08:00 | 15.60 | 4.83 |
May | 0.888440E+10 | 23283.71 | 29-MAY-08:61 | 16.47 | 12.41 | 0.309659E+09 | 521.41 | 19-MAY-08:50 | 16.47 | 12.41 |
June | 0.112451E+11 | 24604.96 | 25-JUN-09:11 | 27.23 | 16.34 | 0.311624E+09 | 522.97 | 29-JUN-10:30 | 32.50 | 16.89 |
July | 0.116014E+11 | 24482.98 | 04-JUL-07:41 | 24.13 | 17.77 | 0.292289E+09 | 529.35 | 05-JUL-07:19 | 24.80 | 15.16 |
August | 0.113614E+11 | 24005.77 | 06-AUG-10:01 | 26.28 | 15.10 | 0.325858E+09 | 523.06 | 02-AUG-10:30 | 26.28 | 15.10 |
September | 0.848081E+10 | 21876.66 | 03-SEP-09:02 | 25.97 | 15.10 | 0.286419E+09 | 521.52 | 13-SEP-08:39 | 21.27 | 13.03 |
October | 0.632778E+10 | 22072.23 | 01-OCT-09:02 | 18.35 | 11.47 | 0.279894E+09 | 521.22 | 02-OCT-12:09 | 25.10 | 14.89 |
November | 0.392451E+10 | 8058.10 | 01-NOV-09:00 | 10.00 | 6.46 | 0.252538E+09 | 521.19 | 01-NOV-10:20 | 12.97 | 7.67 |
December | 0.249356E+10 | 4332.74 | 29-DEC-11:20 | 6.33 | 1.82 | 0.225131E+09 | 521.15 | 29-DEC-09:00 | 6.33 | 1.82 |
Annual Sum or Average | 0.826402E+11 | 0.332016E+10 | ||||||||
Minimum of Months | 0.249356E+10 | 4332.74 | 6.28 | -0.7 | 0.223598E+09 | 521.15 | 6.28 | -0.7 | ||
Maximum of Months | 0.116014E+11 | 24604.96 | 27.23 | 17.77 | 0.325858E+09 | 529.35 | 32.50 | 16.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.871685E+10 | 22684.47 | 22-JAN-13:02 | 10.68 | 2.29 | 0.593854E+09 | 939.15 | 23-JAN-14:20 | 14.80 | 4.45 |
February | 0.863335E+10 | 21444.69 | 19-FEB-11:32 | 12.07 | 5.10 | 0.549335E+09 | 957.60 | 14-FEB-14:20 | 12.07 | 5.10 |
March | 0.903628E+10 | 21383.94 | 26-MAR-12:32 | 17.80 | 6.78 | 0.655310E+09 | 861.22 | 13-MAR-13:50 | 17.80 | 6.78 |
April | 0.884998E+10 | 20733.46 | 30-APR-13:32 | 21.33 | 7.45 | 0.595021E+09 | 846.85 | 17-APR-13:00 | 21.33 | 7.45 |
May | 0.842519E+10 | 11496.67 | 14-MAY-14:22 | 27.50 | 11.00 | 0.650097E+09 | 845.67 | 09-MAY-13:20 | 27.50 | 11.00 |
June | 0.100400E+11 | 19084.45 | 25-JUN-16:31 | 34.07 | 14.58 | 0.657007E+09 | 845.67 | 30-JUN-13:50 | 28.08 | 17.83 |
July | 0.116361E+11 | 21024.89 | 04-JUL-15:01 | 35.60 | 14.14 | 0.614926E+09 | 845.95 | 25-JUL-13:39 | 34.03 | 17.66 |
August | 0.136287E+11 | 21130.02 | 06-AUG-14:02 | 31.73 | 16.63 | 0.690089E+09 | 862.11 | 31-AUG-13:09 | 29.50 | 15.73 |
September | 0.133607E+11 | 22522.32 | 10-SEP-12:22 | 25.25 | 15.43 | 0.615343E+09 | 982.91 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.133993E+11 | 24957.17 | 01-OCT-13:01 | 27.38 | 14.05 | 0.636276E+09 | 987.38 | 31-OCT-13:00 | 22.80 | 8.86 |
November | 0.107831E+11 | 21426.62 | 23-NOV-12:02 | 12.48 | 4.07 | 0.620181E+09 | 981.08 | 01-NOV-13:30 | 12.48 | 4.07 |
December | 0.968615E+10 | 22205.12 | 31-DEC-14:02 | 10.18 | 1.71 | 0.584637E+09 | 931.23 | 29-DEC-14:09 | 10.18 | 1.71 |
Annual Sum or Average | 0.126196E+12 | 0.746208E+10 | ||||||||
Minimum of Months | 0.842519E+10 | 11496.67 | 10.18 | 1.71 | 0.549335E+09 | 845.67 | 10.18 | 1.71 | ||
Maximum of Months | 0.136287E+11 | 24957.17 | 35.60 | 16.63 | 0.690089E+09 | 987.38 | 34.03 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294229E+10 | 7145.13 | 26-JAN-16:30 | 10.30 | 1.40 | 0.324163E+09 | 521.19 | 24-JAN-16:49 | 10.30 | 1.40 |
February | 0.356370E+10 | 10906.17 | 15-FEB-16:30 | 16.95 | 6.18 | 0.302864E+09 | 544.91 | 15-FEB-14:00 | 16.95 | 6.18 |
March | 0.544018E+10 | 11300.28 | 24-MAR-16:00 | 18.30 | 5.82 | 0.377378E+09 | 544.93 | 09-MAR-14:00 | 18.30 | 5.82 |
April | 0.723297E+10 | 23230.99 | 16-APR-16:31 | 20.20 | 8.02 | 0.365208E+09 | 544.96 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.843694E+10 | 25173.01 | 14-MAY-15:41 | 28.30 | 11.08 | 0.404716E+09 | 544.97 | 16-MAY-13:00 | 25.00 | 9.24 |
June | 0.106376E+11 | 27396.46 | 25-JUN-17:11 | 33.13 | 14.92 | 0.418271E+09 | 544.97 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.110792E+11 | 28081.29 | 04-JUL-17:01 | 35.73 | 14.63 | 0.394183E+09 | 544.96 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.111544E+11 | 26622.63 | 13-AUG-16:21 | 30.55 | 17.22 | 0.440893E+09 | 545.07 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.854810E+10 | 24280.31 | 04-SEP-17:01 | 26.52 | 16.05 | 0.379730E+09 | 544.97 | 18-SEP-13:00 | 25.00 | 14.88 |
October | 0.684032E+10 | 23924.29 | 01-OCT-15:41 | 28.80 | 13.20 | 0.363689E+09 | 544.96 | 04-OCT-13:00 | 25.60 | 13.67 |
November | 0.441417E+10 | 9423.81 | 02-NOV-16:00 | 16.70 | 9.78 | 0.337625E+09 | 544.86 | 20-NOV-14:00 | 15.00 | 4.99 |
December | 0.290904E+10 | 5941.02 | 29-DEC-16:00 | 11.70 | 3.88 | 0.313654E+09 | 521.19 | 26-DEC-16:40 | 11.70 | 3.88 |
Annual Sum or Average | 0.831988E+11 | 0.442237E+10 | ||||||||
Minimum of Months | 0.290904E+10 | 5941.02 | 10.30 | 1.40 | 0.302864E+09 | 521.19 | 10.30 | 1.40 | ||
Maximum of Months | 0.111544E+11 | 28081.29 | 35.73 | 17.22 | 0.440893E+09 | 545.07 | 26.70 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.787636E+09 | 3293.49 | 05-JAN-14:30 | 16.10 | 6.84 | 0.467818E+09 | 673.36 | 24-JAN-14:00 | 16.10 | 4.97 |
February | 0.121087E+10 | 3985.74 | 15-FEB-15:30 | 17.20 | 6.59 | 0.432343E+09 | 747.83 | 15-FEB-16:00 | 16.70 | 5.85 |
March | 0.289807E+10 | 3823.66 | 08-MAR-14:00 | 22.80 | 9.68 | 0.561362E+09 | 826.41 | 09-MAR-14:00 | 16.70 | 5.68 |
April | 0.449842E+10 | 7540.87 | 28-APR-15:30 | 25.00 | 10.42 | 0.558506E+09 | 845.63 | 17-APR-13:00 | 25.00 | 10.42 |
May | 0.659113E+10 | 8786.43 | 31-MAY-15:30 | 27.75 | 11.03 | 0.638399E+09 | 845.64 | 31-MAY-13:20 | 27.75 | 11.03 |
June | 0.102396E+11 | 18757.76 | 25-JUN-17:21 | 33.05 | 15.18 | 0.657203E+09 | 861.76 | 28-JUN-13:00 | 37.80 | 14.11 |
July | 0.113224E+11 | 19934.68 | 04-JUL-15:01 | 35.60 | 14.14 | 0.615056E+09 | 845.64 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.104423E+11 | 18298.88 | 13-AUG-16:21 | 30.55 | 17.22 | 0.687855E+09 | 845.79 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.680480E+10 | 8864.51 | 01-SEP-15:20 | 28.70 | 16.42 | 0.598432E+09 | 845.65 | 13-SEP-13:30 | 26.40 | 14.44 |
October | 0.412485E+10 | 7591.96 | 02-OCT-13:40 | 26.33 | 15.37 | 0.552177E+09 | 845.63 | 02-OCT-13:20 | 26.33 | 15.37 |
November | 0.190462E+10 | 3970.12 | 01-NOV-15:10 | 12.43 | 7.32 | 0.483845E+09 | 772.87 | 09-NOV-14:00 | 18.30 | 9.49 |
December | 0.520624E+09 | 2918.85 | 29-DEC-15:10 | 11.20 | 3.93 | 0.449412E+09 | 694.40 | 01-DEC-14:00 | 11.20 | 3.93 |
Annual Sum or Average | 0.613454E+11 | 0.670241E+10 | ||||||||
Minimum of Months | 0.520624E+09 | 2918.85 | 11.20 | 3.93 | 0.432343E+09 | 673.36 | 11.20 | 3.93 | ||
Maximum of Months | 0.113224E+11 | 19934.68 | 35.60 | 17.22 | 0.687855E+09 | 861.76 | 37.80 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165378E+10 | 3747.62 | 03-JAN-13:20 | 14.27 | 5.50 | 0.308504E+09 | 491.89 | 27-JAN-10:20 | 3.90 | -1.9 |
February | 0.222602E+10 | 5424.83 | 14-FEB-10:10 | 10.83 | 3.59 | 0.293788E+09 | 544.94 | 14-FEB-10:09 | 10.83 | 3.59 |
March | 0.431119E+10 | 7483.78 | 08-MAR-09:50 | 13.43 | 6.40 | 0.393104E+09 | 544.95 | 17-MAR-13:00 | 16.10 | 5.42 |
April | 0.703792E+10 | 18041.91 | 30-APR-09:02 | 15.78 | 4.89 | 0.386539E+09 | 545.85 | 28-APR-09:00 | 15.78 | 4.89 |
May | 0.879741E+10 | 23705.85 | 29-MAY-08:51 | 18.30 | 12.78 | 0.420762E+09 | 545.81 | 19-MAY-09:00 | 18.30 | 12.78 |
June | 0.117283E+11 | 22419.56 | 25-JUN-09:22 | 27.50 | 16.43 | 0.424337E+09 | 548.63 | 28-JUN-13:00 | 37.80 | 14.11 |
July | 0.124212E+11 | 24704.92 | 04-JUL-07:41 | 24.13 | 17.77 | 0.396702E+09 | 546.10 | 12-JUL-09:00 | 28.30 | 16.24 |
August | 0.120122E+11 | 23190.92 | 20-AUG-09:21 | 27.20 | 16.00 | 0.443820E+09 | 545.89 | 16-AUG-09:00 | 27.20 | 16.00 |
September | 0.856526E+10 | 22226.55 | 17-SEP-09:42 | 19.13 | 13.27 | 0.389203E+09 | 545.05 | 13-SEP-09:20 | 19.13 | 13.27 |
October | 0.562989E+10 | 15904.70 | 01-OCT-09:12 | 18.90 | 11.69 | 0.378226E+09 | 544.97 | 02-OCT-13:20 | 25.97 | 15.23 |
November | 0.294691E+10 | 7025.41 | 01-NOV-09:10 | 10.47 | 6.68 | 0.329741E+09 | 544.95 | 01-NOV-09:09 | 10.47 | 6.68 |
December | 0.152786E+10 | 3740.67 | 29-DEC-13:20 | 9.47 | 2.91 | 0.294173E+09 | 486.66 | 29-DEC-10:09 | 9.47 | 2.91 |
Annual Sum or Average | 0.788579E+11 | 0.445890E+10 | ||||||||
Minimum of Months | 0.152786E+10 | 3740.67 | 9.47 | 2.91 | 0.293788E+09 | 486.66 | 3.90 | -1.9 | ||
Maximum of Months | 0.124212E+11 | 24704.92 | 27.50 | 17.77 | 0.443820E+09 | 548.63 | 37.80 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.692553E+10 | 22799.78 | 01-JAN-14:52 | 16.10 | 5.83 | 0.568628E+09 | 864.48 | 26-JAN-14:20 | 10.20 | 1.54 |
February | 0.719277E+10 | 23781.99 | 19-FEB-14:02 | 16.28 | 6.80 | 0.526181E+09 | 902.76 | 14-FEB-14:30 | 16.28 | 6.80 |
March | 0.779918E+10 | 23647.77 | 12-MAR-14:12 | 18.53 | 6.14 | 0.628961E+09 | 846.21 | 16-MAR-13:00 | 20.60 | 8.86 |
April | 0.834538E+10 | 15123.28 | 28-APR-13:20 | 24.40 | 9.99 | 0.580145E+09 | 847.00 | 27-APR-13:00 | 24.40 | 9.99 |
May | 0.845374E+10 | 18894.43 | 21-MAY-13:32 | 27.43 | 12.30 | 0.637154E+09 | 845.67 | 08-MAY-13:30 | 27.43 | 12.30 |
June | 0.106890E+11 | 16934.28 | 25-JUN-16:41 | 33.68 | 14.48 | 0.652329E+09 | 856.97 | 28-JUN-13:00 | 37.80 | 14.11 |
July | 0.127088E+11 | 24209.10 | 04-JUL-15:01 | 35.60 | 14.14 | 0.613860E+09 | 845.66 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.145144E+11 | 23770.23 | 06-AUG-12:12 | 29.63 | 16.08 | 0.688017E+09 | 846.77 | 25-AUG-13:00 | 28.90 | 17.11 |
September | 0.136008E+11 | 24928.83 | 10-SEP-12:32 | 25.53 | 15.18 | 0.608547E+09 | 953.11 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.126020E+11 | 25075.66 | 01-OCT-13:12 | 27.57 | 13.97 | 0.615569E+09 | 945.57 | 05-OCT-13:39 | 26.33 | 12.76 |
November | 0.904986E+10 | 23228.01 | 19-NOV-13:51 | 13.30 | 3.30 | 0.595011E+09 | 927.95 | 01-NOV-13:30 | 13.30 | 3.30 |
December | 0.772657E+10 | 23443.93 | 31-DEC-14:02 | 10.18 | 1.71 | 0.558868E+09 | 861.83 | 29-DEC-14:09 | 10.18 | 1.71 |
Annual Sum or Average | 0.119608E+12 | 0.727327E+10 | ||||||||
Minimum of Months | 0.692553E+10 | 15123.28 | 10.18 | 1.71 | 0.526181E+09 | 845.66 | 10.18 | 1.54 | ||
Maximum of Months | 0.145144E+11 | 25075.66 | 35.60 | 16.08 | 0.688017E+09 | 953.11 | 37.80 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202415E+10 | 6330.55 | 26-JAN-16:30 | 10.30 | 1.40 | 0.317366E+09 | 521.18 | 09-JAN-16:00 | 10.30 | 1.40 |
February | 0.275182E+10 | 10681.51 | 15-FEB-16:30 | 16.95 | 6.18 | 0.296460E+09 | 544.76 | 15-FEB-14:00 | 16.95 | 6.18 |
March | 0.466773E+10 | 11272.35 | 07-MAR-16:30 | 21.15 | 8.79 | 0.364139E+09 | 544.92 | 07-MAR-14:00 | 21.15 | 8.79 |
April | 0.687695E+10 | 24434.66 | 09-APR-17:12 | 18.70 | 5.91 | 0.354223E+09 | 544.97 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.845635E+10 | 25161.17 | 29-MAY-16:11 | 26.83 | 13.10 | 0.395143E+09 | 544.97 | 08-MAY-13:30 | 26.83 | 13.10 |
June | 0.111276E+11 | 27186.31 | 25-JUN-16:41 | 33.68 | 14.48 | 0.414277E+09 | 560.87 | 27-JUN-15:00 | 37.80 | 15.32 |
July | 0.118594E+11 | 30434.53 | 04-JUL-16:21 | 35.85 | 14.32 | 0.392508E+09 | 544.96 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.117764E+11 | 28751.68 | 13-AUG-16:21 | 30.55 | 17.22 | 0.437845E+09 | 545.08 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.867078E+10 | 26096.21 | 04-SEP-17:01 | 26.52 | 16.05 | 0.374176E+09 | 544.99 | 13-SEP-13:30 | 26.40 | 14.44 |
October | 0.626813E+10 | 20013.14 | 01-OCT-15:12 | 28.50 | 13.01 | 0.353948E+09 | 544.95 | 02-OCT-13:39 | 26.33 | 15.37 |
November | 0.345466E+10 | 8970.01 | 02-NOV-16:00 | 16.70 | 9.78 | 0.327718E+09 | 539.30 | 22-NOV-14:00 | 15.60 | 6.11 |
December | 0.194820E+10 | 5253.97 | 29-DEC-16:00 | 11.70 | 3.88 | 0.307179E+09 | 521.18 | 29-DEC-16:49 | 10.28 | 3.14 |
Annual Sum or Average | 0.798822E+11 | 0.433498E+10 | ||||||||
Minimum of Months | 0.194820E+10 | 5253.97 | 10.30 | 1.40 | 0.296460E+09 | 521.18 | 10.28 | 1.40 | ||
Maximum of Months | 0.118594E+11 | 30434.53 | 35.85 | 17.22 | 0.437845E+09 | 560.87 | 37.80 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229995E+10 | 5967.48 | 02-JAN-06:08 | -4.2 | -5.0 | 0.00 | 0.00 | 01-JAN-00:10 | -4.2 | -5.0 |
February | 0.256661E+10 | 5592.21 | 21-FEB-06:10 | 3.40 | 0.81 | 0.00 | 0.00 | 01-FEB-00:10 | 3.40 | 0.81 |
March | 0.468558E+10 | 5768.25 | 27-MAR-05:10 | 5.50 | 0.60 | 0.00 | 0.00 | 01-MAR-00:10 | 5.50 | 0.60 |
April | 0.692006E+10 | 8170.75 | 28-APR-05:13 | 11.67 | 4.22 | 0.00 | 0.00 | 01-APR-00:10 | 11.67 | 4.22 |
May | 0.736129E+10 | 9786.82 | 30-MAY-05:15 | 14.43 | 10.90 | 0.00 | 0.00 | 01-MAY-00:10 | 14.43 | 10.90 |
June | 0.990104E+10 | 9758.05 | 05-JUN-05:15 | 15.00 | 12.60 | 0.00 | 0.00 | 01-JUN-00:10 | 15.00 | 12.60 |
July | 0.113313E+11 | 10949.12 | 05-JUL-05:15 | 22.20 | 13.64 | 0.00 | 0.00 | 01-JUL-00:10 | 22.20 | 13.64 |
August | 0.127564E+11 | 14955.87 | 21-AUG-05:15 | 21.50 | 15.46 | 0.00 | 0.00 | 01-AUG-00:10 | 21.50 | 15.46 |
September | 0.847088E+10 | 10638.36 | 05-SEP-05:15 | 15.73 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 15.73 | 14.76 |
October | 0.667579E+10 | 12363.45 | 02-OCT-05:13 | 17.03 | 12.72 | 0.00 | 0.00 | 01-OCT-00:10 | 17.03 | 12.72 |
November | 0.438392E+10 | 5940.80 | 13-NOV-06:09 | 0.10 | -1.5 | 0.00 | 0.00 | 01-NOV-00:10 | 0.10 | -1.5 |
December | 0.295258E+10 | 4709.74 | 18-DEC-06:06 | -2.2 | -4.5 | 0.00 | 0.00 | 01-DEC-00:10 | -2.2 | -4.5 |
Annual Sum or Average | 0.803054E+11 | 0.00 | ||||||||
Minimum of Months | 0.229995E+10 | 4709.74 | -4.2 | -5.0 | 0.00 | 0.00 | -4.2 | -5.0 | ||
Maximum of Months | 0.127564E+11 | 14955.87 | 22.20 | 15.46 | 0.00 | 0.00 | 22.20 | 15.46 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.796615E+09 | 7199.33 | 17-JAN-04:01 | -3.3 | -5.0 | 0.00 | 0.00 | 01-JAN-00:10 | -3.3 | -5.0 |
February | 0.103844E+10 | 5695.12 | 04-FEB-05:01 | -6.2 | -7.7 | 0.00 | 0.00 | 01-FEB-00:10 | -6.2 | -7.7 |
March | 0.216590E+10 | 5076.11 | 09-MAR-06:08 | 4.40 | 1.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4.40 | 1.00 |
April | 0.394406E+10 | 6589.68 | 14-APR-05:13 | 8.87 | 2.20 | 0.00 | 0.00 | 01-APR-00:10 | 8.87 | 2.20 |
May | 0.554485E+10 | 6406.69 | 23-MAY-05:13 | 14.40 | 9.72 | 0.00 | 0.00 | 01-MAY-00:10 | 14.40 | 9.72 |
June | 0.793082E+10 | 8182.02 | 29-JUN-15:00 | 37.80 | 15.70 | 0.00 | 0.00 | 01-JUN-00:10 | 37.80 | 15.70 |
July | 0.908394E+10 | 8698.59 | 24-JUL-05:15 | 22.20 | 14.92 | 0.00 | 0.00 | 01-JUL-00:10 | 22.20 | 14.92 |
August | 0.916156E+10 | 8567.03 | 07-AUG-15:40 | 33.13 | 16.01 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 16.01 |
September | 0.665255E+10 | 8154.45 | 05-SEP-05:15 | 15.73 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 15.73 | 14.76 |
October | 0.441263E+10 | 6875.37 | 04-OCT-05:13 | 12.80 | 7.65 | 0.00 | 0.00 | 01-OCT-00:10 | 12.80 | 7.65 |
November | 0.197501E+10 | 5658.75 | 25-NOV-06:01 | 1.10 | -1.4 | 0.00 | 0.00 | 01-NOV-00:10 | 1.10 | -1.4 |
December | 0.835434E+09 | 5709.18 | 22-DEC-05:01 | -4.7 | -6.6 | 0.00 | 0.00 | 01-DEC-00:10 | -4.7 | -6.6 |
Annual Sum or Average | 0.535418E+11 | 0.00 | ||||||||
Minimum of Months | 0.796615E+09 | 5076.11 | -6.2 | -7.7 | 0.00 | 0.00 | -6.2 | -7.7 | ||
Maximum of Months | 0.916156E+10 | 8698.59 | 37.80 | 16.01 | 0.00 | 0.00 | 37.80 | 16.01 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.439461E+09 | 3493.32 | 05-JAN-14:10 | 16.10 | 6.84 | 0.00 | 0.00 | 01-JAN-00:10 | 16.10 | 6.84 |
February | 0.115830E+10 | 7512.30 | 15-FEB-15:40 | 17.20 | 6.56 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 6.56 |
March | 0.326098E+10 | 10060.47 | 08-MAR-15:00 | 22.20 | 9.10 | 0.00 | 0.00 | 01-MAR-00:10 | 22.20 | 9.10 |
April | 0.712394E+10 | 16573.99 | 28-APR-14:40 | 24.80 | 10.38 | 0.00 | 0.00 | 01-APR-00:10 | 24.80 | 10.38 |
May | 0.999001E+10 | 19149.32 | 30-MAY-14:30 | 27.20 | 12.25 | 0.00 | 0.00 | 01-MAY-00:10 | 27.20 | 12.25 |
June | 0.152451E+11 | 24424.25 | 28-JUN-13:30 | 37.50 | 13.98 | 0.00 | 0.00 | 01-JUN-00:10 | 37.50 | 13.98 |
July | 0.173611E+11 | 23534.00 | 21-JUL-14:00 | 37.80 | 15.31 | 0.00 | 0.00 | 01-JUL-00:10 | 37.80 | 15.31 |
August | 0.165599E+11 | 22266.33 | 07-AUG-14:20 | 33.13 | 15.81 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 15.81 |
September | 0.107228E+11 | 17465.70 | 01-SEP-15:00 | 28.90 | 16.64 | 0.00 | 0.00 | 01-SEP-00:10 | 28.90 | 16.64 |
October | 0.549028E+10 | 13531.93 | 05-OCT-14:30 | 26.70 | 12.37 | 0.00 | 0.00 | 01-OCT-00:10 | 26.70 | 12.37 |
November | 0.140943E+10 | 6535.64 | 02-NOV-14:50 | 16.93 | 9.25 | 0.00 | 0.00 | 01-NOV-00:10 | 16.93 | 9.25 |
December | 0.201668E+09 | 2975.58 | 31-DEC-14:05 | 10.18 | 1.71 | 0.00 | 0.00 | 01-DEC-00:10 | 10.18 | 1.71 |
Annual Sum or Average | 0.889630E+11 | 0.00 | ||||||||
Minimum of Months | 0.201668E+09 | 2975.58 | 10.18 | 1.71 | 0.00 | 0.00 | 10.18 | 1.71 | ||
Maximum of Months | 0.173611E+11 | 24424.25 | 37.80 | 16.64 | 0.00 | 0.00 | 37.80 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339325E+10 | 2488.03 | 26-JAN-17:00 | 10.00 | 1.21 | 95230023.82 | 126.82 | 19-JAN-14:09 | 10.00 | 1.21 |
February | 0.804245E+10 | 4542.01 | 15-FEB-17:00 | 16.70 | 5.85 | 86396720.87 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.144222E+11 | 7130.24 | 31-MAR-24:00 | 6.90 | 3.36 | 0.103236E+09 | 126.83 | 21-MAR-13:20 | 6.90 | 3.36 |
April | 0.192389E+11 | 8292.36 | 15-APR-17:55 | 7.20 | 4.16 | 91686105.76 | 127.17 | 13-APR-13:00 | 7.20 | 4.16 |
May | 0.459731E+10 | 3533.62 | 31-MAY-24:00 | 18.60 | 7.93 | 99235680.40 | 126.85 | 24-MAY-13:00 | 18.60 | 7.93 |
June | 0.951119E+10 | 5364.83 | 30-JUN-23:23 | 22.60 | 14.29 | 98962008.20 | 126.86 | 08-JUN-13:00 | 22.60 | 14.29 |
July | 0.148803E+11 | 7269.66 | 31-JUL-23:57 | 21.00 | 17.53 | 91885748.33 | 126.84 | 17-JUL-09:09 | 21.00 | 17.53 |
August | 0.203375E+11 | 8129.85 | 23-AUG-18:00 | 23.90 | 15.31 | 0.104740E+09 | 135.72 | 17-AUG-13:00 | 23.90 | 15.31 |
September | 0.459291E+10 | 3524.63 | 30-SEP-24:00 | 17.40 | 10.77 | 91613689.88 | 126.86 | 07-SEP-13:00 | 17.40 | 10.77 |
October | 0.958434E+10 | 5321.98 | 31-OCT-24:00 | 13.00 | 4.55 | 95233160.44 | 126.85 | 11-OCT-09:30 | 13.00 | 4.55 |
November | 0.138804E+11 | 6393.65 | 06-NOV-16:40 | 14.40 | 4.29 | 94300813.48 | 126.83 | 02-NOV-09:00 | 14.40 | 4.29 |
December | 0.192632E+11 | 8195.52 | 26-DEC-16:30 | 8.05 | 3.32 | 91880713.80 | 126.82 | 08-DEC-14:09 | 8.05 | 3.32 |
Annual Sum or Average | 0.141744E+12 | 0.114440E+10 | ||||||||
Minimum of Months | 0.339325E+10 | 2488.03 | 6.90 | 1.21 | 86396720.87 | 126.82 | 6.90 | 1.21 | ||
Maximum of Months | 0.203375E+11 | 8292.36 | 23.90 | 17.53 | 0.104740E+09 | 135.72 | 23.90 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169973E+10 | 2264.18 | 26-JAN-17:00 | 10.00 | 1.21 | 95229888.33 | 126.82 | 20-JAN-14:00 | 10.00 | 1.21 |
February | 0.641868E+10 | 4251.44 | 15-FEB-17:00 | 16.70 | 5.85 | 86396718.80 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.127667E+11 | 6546.27 | 31-MAR-24:00 | 6.90 | 3.36 | 0.103236E+09 | 126.83 | 29-MAR-09:30 | 6.90 | 3.36 |
April | 0.177593E+11 | 7828.77 | 24-APR-18:00 | 20.60 | 8.33 | 91630735.13 | 126.82 | 20-APR-09:39 | 20.60 | 8.33 |
May | 0.398868E+10 | 3341.93 | 31-MAY-24:00 | 18.60 | 7.93 | 99235166.30 | 126.84 | 24-MAY-09:00 | 18.60 | 7.93 |
June | 0.892366E+10 | 5194.84 | 30-JUN-23:55 | 22.10 | 13.89 | 98961856.50 | 126.85 | 08-JUN-13:00 | 22.10 | 13.89 |
July | 0.141725E+11 | 7007.21 | 31-JUL-23:57 | 21.00 | 17.53 | 91886463.93 | 126.84 | 17-JUL-09:09 | 21.00 | 17.53 |
August | 0.189534E+11 | 7612.57 | 30-AUG-17:30 | 28.60 | 14.79 | 0.103826E+09 | 131.64 | 17-AUG-13:00 | 28.60 | 14.79 |
September | 0.404114E+10 | 3323.45 | 30-SEP-24:00 | 17.40 | 10.77 | 91612397.75 | 126.85 | 07-SEP-13:00 | 17.40 | 10.77 |
October | 0.842782E+10 | 4834.05 | 31-OCT-24:00 | 13.00 | 4.55 | 95233000.73 | 126.84 | 11-OCT-09:00 | 13.00 | 4.55 |
November | 0.119932E+11 | 5914.62 | 02-NOV-16:40 | 16.30 | 9.65 | 94300797.70 | 126.83 | 02-NOV-09:00 | 16.30 | 9.65 |
December | 0.165246E+11 | 7554.44 | 29-DEC-16:50 | 10.28 | 3.14 | 91880778.18 | 126.82 | 08-DEC-14:09 | 10.28 | 3.14 |
Annual Sum or Average | 0.125669E+12 | 0.114343E+10 | ||||||||
Minimum of Months | 0.169973E+10 | 2264.18 | 6.90 | 1.21 | 86396718.80 | 126.82 | 6.90 | 1.21 | ||
Maximum of Months | 0.189534E+11 | 7828.77 | 28.60 | 17.53 | 0.103826E+09 | 131.64 | 28.60 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.773352E+09 | 2178.73 | 26-JAN-17:00 | 10.00 | 1.21 | 94441846.85 | 126.82 | 13-JAN-10:09 | 10.00 | 1.21 |
February | 0.503241E+10 | 4266.76 | 15-FEB-17:00 | 16.70 | 5.85 | 86396719.59 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.117736E+11 | 6173.30 | 31-MAR-23:20 | 6.50 | 3.19 | 0.103236E+09 | 126.83 | 29-MAR-09:30 | 6.50 | 3.19 |
April | 0.173101E+11 | 7907.93 | 16-APR-17:51 | 19.40 | 7.60 | 91619911.34 | 126.82 | 20-APR-09:39 | 11.47 | 5.64 |
May | 0.376884E+10 | 3288.43 | 31-MAY-24:00 | 18.60 | 7.93 | 99235004.38 | 126.84 | 23-MAY-13:00 | 18.60 | 7.93 |
June | 0.892552E+10 | 5196.12 | 30-JUN-23:55 | 22.10 | 13.89 | 98961893.77 | 126.85 | 08-JUN-13:00 | 22.10 | 13.89 |
July | 0.142794E+11 | 6990.45 | 31-JUL-23:57 | 21.00 | 17.53 | 91886373.77 | 126.84 | 10-JUL-09:00 | 21.00 | 17.53 |
August | 0.190201E+11 | 7749.62 | 30-AUG-17:30 | 28.60 | 14.79 | 0.103667E+09 | 130.25 | 17-AUG-13:00 | 28.60 | 14.79 |
September | 0.393813E+10 | 3305.16 | 30-SEP-24:00 | 17.40 | 10.77 | 91612293.09 | 126.86 | 07-SEP-13:00 | 17.40 | 10.77 |
October | 0.777763E+10 | 4603.25 | 31-OCT-24:00 | 13.00 | 4.55 | 95232998.55 | 126.84 | 11-OCT-09:00 | 13.00 | 4.55 |
November | 0.106193E+11 | 5897.04 | 02-NOV-16:40 | 16.30 | 9.65 | 94300815.55 | 126.83 | 02-NOV-09:00 | 16.30 | 9.65 |
December | 0.146270E+11 | 7466.96 | 29-DEC-16:50 | 10.28 | 3.14 | 91880800.93 | 126.82 | 08-DEC-14:09 | 10.28 | 3.14 |
Annual Sum or Average | 0.117845E+12 | 0.114247E+10 | ||||||||
Minimum of Months | 0.773352E+09 | 2178.73 | 6.50 | 1.21 | 86396719.59 | 126.82 | 6.50 | 1.21 | ||
Maximum of Months | 0.190201E+11 | 7907.93 | 28.60 | 17.53 | 0.103667E+09 | 130.25 | 28.60 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239117E+12 | 92747.52 | 02-JAN-17:00 | 11.10 | 4.18 | 0.206145E+10 | 2745.74 | 05-JAN-14:00 | 16.10 | 6.84 |
February | 0.436678E+12 | 184425.13 | 15-FEB-17:00 | 16.70 | 5.85 | 0.187265E+10 | 2749.46 | 10-FEB-14:00 | 16.70 | 5.85 |
March | 0.730310E+12 | 359215.42 | 31-MAR-24:00 | 6.90 | 3.36 | 0.223666E+10 | 2748.25 | 01-MAR-14:09 | 6.90 | 3.36 |
April | 0.937179E+12 | 367579.35 | 18-APR-07:15 | 7.23 | 1.32 | 0.228489E+10 | 3610.11 | 28-APR-13:00 | 24.40 | 10.28 |
May | 0.242395E+12 | 176459.54 | 31-MAY-24:00 | 18.60 | 7.93 | 0.214867E+10 | 2747.85 | 08-MAY-13:00 | 18.60 | 7.93 |
June | 0.471809E+12 | 268280.72 | 30-JUN-23:55 | 22.10 | 13.89 | 0.214394E+10 | 2749.56 | 09-JUN-09:50 | 22.10 | 13.89 |
July | 0.733828E+12 | 354759.61 | 31-JUL-23:30 | 21.10 | 17.28 | 0.198993E+10 | 2749.78 | 25-JUL-13:30 | 21.10 | 17.28 |
August | 0.959809E+12 | 365342.00 | 31-AUG-06:05 | 13.63 | 11.20 | 0.321922E+10 | 4403.44 | 17-AUG-13:00 | 13.63 | 11.20 |
September | 0.238105E+12 | 176750.26 | 30-SEP-24:00 | 17.40 | 10.77 | 0.198380E+10 | 2748.04 | 15-SEP-13:30 | 17.40 | 10.77 |
October | 0.489309E+12 | 269083.64 | 31-OCT-24:00 | 13.00 | 4.55 | 0.206389E+10 | 2749.59 | 16-OCT-09:30 | 13.00 | 4.55 |
November | 0.709720E+12 | 277309.20 | 24-NOV-17:00 | 13.90 | 4.33 | 0.204309E+10 | 2748.27 | 01-NOV-13:50 | 13.90 | 4.33 |
December | 0.974628E+12 | 367475.74 | 13-DEC-16:55 | 7.20 | 0.17 | 0.209076E+10 | 3003.50 | 26-DEC-14:00 | 10.00 | 3.84 |
Annual Sum or Average | 0.716289E+13 | 0.261390E+11 | ||||||||
Minimum of Months | 0.238105E+12 | 92747.52 | 6.90 | 0.17 | 0.187265E+10 | 2745.74 | 6.90 | 3.36 | ||
Maximum of Months | 0.974628E+12 | 367579.35 | 22.10 | 17.28 | 0.321922E+10 | 4403.44 | 24.40 | 17.28 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211105E+09 | 13779.73 | 03-JAN-04:15 | -0.2 |
February | 0.171610E+09 | 13985.42 | 27-FEB-04:04 | 1.20 |
March | 0.215260E+09 | 14218.71 | 13-MAR-04:25 | 2.25 |
April | 0.273599E+09 | 14523.64 | 24-APR-04:35 | 6.10 |
May | 0.415970E+09 | 15628.73 | 29-MAY-14:42 | 27.02 |
June | 0.405944E+09 | 20749.24 | 24-JUN-16:01 | 33.12 |
July | 0.510387E+09 | 23718.94 | 22-JUL-16:02 | 36.05 |
August | 0.417195E+09 | 18953.66 | 05-AUG-16:01 | 31.52 |
September | 0.419432E+09 | 18301.25 | 02-SEP-16:01 | 31.10 |
October | 0.384835E+09 | 15210.78 | 15-OCT-20:03 | 16.93 |
November | 0.330433E+09 | 14839.42 | 12-NOV-07:23 | 0.55 |
December | 0.336078E+09 | 13865.74 | 27-DEC-04:04 | -2.2 |
Annual Sum or Average | 0.409185E+10 | |||
Minimum of Months | 0.171610E+09 | 13779.73 | -2.2 | |
Maximum of Months | 0.510387E+09 | 23718.94 | 36.05 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119150E+10 | 76148.67 | 17-JAN-04:01 | -3.3 |
February | 0.454151E+09 | 74907.12 | 06-FEB-04:01 | -4.4 |
March | 16081609.91 | 65282.11 | 06-MAR-06:01 | -2.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.217512E+09 | 70301.28 | 27-NOV-05:11 | -4.1 |
December | 0.898970E+09 | 75747.70 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.277822E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.119150E+10 | 76148.67 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1054006.18 | 6859.69 | 17-JAN-06:01 | -3.4 |
February | 1409207.06 | 6138.93 | 06-FEB-06:01 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 263061.71 | 1736.22 | 22-DEC-06:01 | -6.1 |
Annual Sum or Average | 2726274.95 | |||
Minimum of Months | 0.00 | 0.00 | -6.1 | |
Maximum of Months | 1409207.06 | 6859.69 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6497192.30 | 5734.29 | 17-JAN-06:01 | -3.4 |
February | 3690797.16 | 5614.73 | 07-FEB-06:01 | -3.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 155185.90 | 780.95 | 25-OCT-05:03 | -1.1 |
November | 628933.86 | 3753.01 | 28-NOV-06:01 | -2.1 |
December | 9632099.54 | 6091.95 | 22-DEC-06:01 | -6.1 |
Annual Sum or Average | 20604208.76 | |||
Minimum of Months | 0.00 | 0.00 | -6.1 | |
Maximum of Months | 9632099.54 | 6091.95 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26462401.88 | 11021.93 | 17-JAN-06:01 | -3.4 |
February | 8795955.74 | 10848.56 | 06-FEB-06:01 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 4811888.36 | 10801.87 | 22-DEC-06:01 | -6.1 |
Annual Sum or Average | 40070245.99 | |||
Minimum of Months | 0.00 | 0.00 | -6.1 | |
Maximum of Months | 26462401.88 | 11021.93 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.996594E+09 | 13732.92 | 17-JAN-04:01 | -3.3 |
February | 0.585404E+09 | 13517.45 | 06-FEB-04:01 | -4.4 |
March | 79263669.25 | 11863.62 | 06-MAR-05:01 | -0.5 |
April | 2544668.40 | 8498.64 | 08-APR-05:03 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 22732091.56 | 11280.64 | 26-OCT-05:02 | -2.5 |
November | 0.200705E+09 | 12463.35 | 27-NOV-05:01 | -4.0 |
December | 0.985509E+09 | 12573.48 | 23-DEC-05:01 | -5.1 |
Annual Sum or Average | 0.287275E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.996594E+09 | 13732.92 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.497246E+09 | 15087.20 | 17-JAN-04:01 | -3.3 |
February | 0.243260E+09 | 14579.90 | 06-FEB-04:01 | -4.4 |
March | 24024596.07 | 12594.65 | 04-MAR-05:01 | -1.2 |
April | 1128698.11 | 4302.68 | 08-APR-05:03 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 13063558.40 | 10993.59 | 26-OCT-05:02 | -2.5 |
November | 67817622.53 | 13044.18 | 27-NOV-05:01 | -4.0 |
December | 0.448486E+09 | 13460.76 | 23-DEC-05:01 | -5.1 |
Annual Sum or Average | 0.129503E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.497246E+09 | 15087.20 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292074E+09 | 16151.54 | 17-JAN-04:01 | -3.3 |
February | 0.149856E+09 | 15579.21 | 06-FEB-05:01 | -4.4 |
March | 16891549.53 | 13912.27 | 04-MAR-06:01 | -1.7 |
April | 381286.75 | 2541.91 | 08-APR-05:03 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 8357765.84 | 13709.64 | 26-OCT-05:02 | -2.5 |
November | 12531468.31 | 13857.76 | 28-NOV-06:01 | -2.1 |
December | 0.239677E+09 | 14961.87 | 26-DEC-05:01 | -1.0 |
Annual Sum or Average | 0.719769E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.292074E+09 | 16151.54 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325214E+09 | 14381.86 | 17-JAN-04:01 | -3.3 |
February | 0.176801E+09 | 13674.00 | 06-FEB-05:01 | -4.4 |
March | 16023564.92 | 11636.87 | 04-MAR-06:01 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 7112288.52 | 9370.64 | 26-OCT-05:02 | -2.5 |
November | 30681988.91 | 11644.99 | 28-NOV-06:01 | -2.1 |
December | 0.272741E+09 | 12695.01 | 22-DEC-05:01 | -4.7 |
Annual Sum or Average | 0.828574E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.7 | |
Maximum of Months | 0.325214E+09 | 14381.86 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.397055E+10 | 16838.17 | 17-JAN-02:62 | -3.3 |
February | 0.252900E+10 | 16842.31 | 06-FEB-03:42 | -4.5 |
March | 0.858418E+09 | 15042.70 | 06-MAR-04:02 | 0.50 |
April | 0.113047E+09 | 13830.54 | 08-APR-04:02 | 2.80 |
May | 11554192.70 | 12807.68 | 06-MAY-05:02 | 6.02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.321261E+09 | 14656.66 | 26-OCT-04:01 | -2.8 |
November | 0.142356E+10 | 15841.15 | 27-NOV-04:01 | -3.9 |
December | 0.398149E+10 | 16348.60 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.132089E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.5 | |
Maximum of Months | 0.398149E+10 | 16842.31 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183787E+10 | 18655.82 | 17-JAN-04:01 | -3.3 |
February | 0.108967E+10 | 17630.11 | 06-FEB-05:01 | -4.4 |
March | 0.322816E+09 | 15728.24 | 04-MAR-05:01 | -1.2 |
April | 29133669.68 | 12385.43 | 08-APR-04:02 | 2.80 |
May | 4089857.24 | 6804.92 | 06-MAY-05:02 | 6.02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.143919E+09 | 16021.60 | 26-OCT-04:01 | -2.8 |
November | 0.536088E+09 | 17165.90 | 27-NOV-04:01 | -3.9 |
December | 0.174425E+10 | 17984.71 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.570784E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.183787E+10 | 18655.82 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167501E+10 | 19912.50 | 17-JAN-04:01 | -3.3 |
February | 0.102737E+10 | 19576.27 | 06-FEB-03:42 | -4.5 |
March | 0.368440E+09 | 17118.89 | 04-MAR-05:01 | -1.2 |
April | 54023482.44 | 14750.76 | 08-APR-04:02 | 2.80 |
May | 12637297.18 | 11893.48 | 05-MAY-05:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.138695E+09 | 17268.32 | 26-OCT-04:01 | -2.8 |
November | 0.350191E+09 | 17979.70 | 27-NOV-04:01 | -3.9 |
December | 0.150351E+10 | 19372.60 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.512987E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.5 | |
Maximum of Months | 0.167501E+10 | 19912.50 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144139E+10 | 19432.16 | 17-JAN-04:01 | -3.3 |
February | 0.863047E+09 | 18405.70 | 06-FEB-04:01 | -4.4 |
March | 0.252581E+09 | 16224.03 | 04-MAR-05:01 | -1.2 |
April | 15094814.56 | 7237.03 | 08-APR-05:03 | 2.62 |
May | 4170021.37 | 7501.44 | 05-MAY-05:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 96654241.21 | 16097.02 | 26-OCT-04:01 | -2.8 |
November | 0.387352E+09 | 17340.52 | 27-NOV-04:01 | -3.9 |
December | 0.128707E+10 | 18341.73 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.434735E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.144139E+10 | 19432.16 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138801E+09 | 12480.19 | 17-JAN-05:01 | -3.3 |
February | 0.101562E+09 | 11763.42 | 08-FEB-05:01 | 0.60 |
March | 0.114633E+09 | 12132.99 | 20-MAR-03:02 | 11.32 |
April | 0.145984E+09 | 11847.88 | 24-APR-03:02 | 5.18 |
May | 77301016.89 | 8991.69 | 22-MAY-03:01 | 18.22 |
June | 84835428.01 | 9667.21 | 05-JUN-03:02 | 15.00 |
July | 99397280.41 | 8284.66 | 30-JUL-15:41 | 33.80 |
August | 76733489.39 | 10588.55 | 20-AUG-15:41 | 35.00 |
September | 69955354.64 | 8590.86 | 18-SEP-03:02 | 14.90 |
October | 96456004.41 | 10825.82 | 16-OCT-03:02 | 13.80 |
November | 0.142405E+09 | 11965.91 | 06-NOV-04:02 | 2.62 |
December | 0.151106E+09 | 14297.47 | 14-DEC-04:01 | -1.4 |
Annual Sum or Average | 0.129917E+10 | |||
Minimum of Months | 69955354.64 | 8284.66 | -3.3 | |
Maximum of Months | 0.151106E+09 | 14297.47 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112096E+10 | 8104.44 | 22-JAN-15:02 | 13.80 |
February | 0.674849E+09 | 7109.98 | 15-FEB-06:03 | 6.93 |
March | 0.104291E+09 | 8101.92 | 14-MAR-05:03 | 6.02 |
April | 56745075.51 | 6945.33 | 25-APR-04:02 | 6.20 |
May | 62784897.20 | 6780.62 | 18-MAY-04:03 | 12.20 |
June | 59173470.92 | 7776.21 | 25-JUN-16:31 | 34.07 |
July | 68500232.07 | 8614.81 | 04-JUL-16:21 | 35.85 |
August | 54684147.55 | 7504.32 | 20-AUG-15:21 | 35.00 |
September | 58317551.03 | 6827.86 | 10-SEP-15:42 | 26.88 |
October | 75969885.98 | 8206.76 | 15-OCT-16:32 | 20.60 |
November | 0.209543E+09 | 7618.42 | 08-NOV-06:03 | 11.52 |
December | 0.899284E+09 | 7268.52 | 17-DEC-14:12 | 11.30 |
Annual Sum or Average | 0.344510E+10 | |||
Minimum of Months | 54684147.55 | 6780.62 | 6.02 | |
Maximum of Months | 0.112096E+10 | 8614.81 | 35.85 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.614965E+10 | 24262.19 | 17-JAN-06:12 | -3.5 |
February | 0.398704E+10 | 25210.57 | 06-FEB-05:12 | -4.4 |
March | 0.212589E+10 | 11185.04 | 06-MAR-06:04 | -2.9 |
April | 0.686224E+09 | 18050.89 | 03-APR-05:02 | 7.85 |
May | 0.289362E+09 | 16786.94 | 12-MAY-05:02 | 9.60 |
June | 0.127912E+09 | 14887.03 | 10-JUN-05:03 | 12.30 |
July | 82840068.51 | 10956.00 | 08-JUL-04:02 | 16.20 |
August | 78845768.28 | 11887.74 | 29-AUG-04:02 | 16.02 |
September | 0.126354E+09 | 14495.03 | 27-SEP-05:03 | 11.60 |
October | 0.118128E+10 | 18625.71 | 12-OCT-05:03 | 6.70 |
November | 0.270538E+10 | 18923.60 | 27-NOV-06:03 | -4.4 |
December | 0.611909E+10 | 21732.21 | 26-DEC-06:13 | -1.0 |
Annual Sum or Average | 0.236599E+11 | |||
Minimum of Months | 78845768.28 | 10956.00 | -4.4 | |
Maximum of Months | 0.614965E+10 | 25210.57 | 16.20 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19684201.33 | 511.67 | 19-JAN-04:07 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 19684201.33 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 19684201.33 | 511.67 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.654073E+09 | 689.28 | 18-JAN-01:40 | -2.2 |
February | 4859259.29 | 443.19 | 05-FEB-22:45 | -3.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.658932E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.8 | |
Maximum of Months | 0.654073E+09 | 689.28 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200626E+11 | 20994.62 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.181982E+11 | 20994.62 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.216246E+11 | 20994.62 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.193152E+11 | 20994.62 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.208436E+11 | 20994.62 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.207428E+11 | 20994.62 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.194159E+11 | 20994.62 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.216246E+11 | 20994.62 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.193152E+11 | 20994.62 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.200626E+11 | 20994.62 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.198274E+11 | 20994.62 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.194159E+11 | 20994.62 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.240449E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.181982E+11 | 20994.62 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.216246E+11 | 20994.62 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162420E+10 | 2171.33 | 09-JAN-16:00 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.143857E+10 | 1959.63 | 16-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.165636E+10 | 1753.13 | 20-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.144954E+10 | 1454.29 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.155194E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.152932E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.144271E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.161203E+10 | 1454.29 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.146879E+10 | 1928.61 | 08-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.156813E+10 | 1929.54 | 25-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.160651E+10 | 2367.39 | 13-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.162056E+10 | 2367.39 | 01-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.185687E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.143857E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.165636E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104017E+10 | 1399.97 | 09-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.924360E+09 | 1246.20 | 16-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.106642E+10 | 1063.32 | 14-MAR-15:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.936714E+09 | 937.20 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.100511E+10 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.989807E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.932797E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.104119E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.946609E+09 | 1229.70 | 08-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100426E+10 | 1186.76 | 25-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.103376E+10 | 1525.64 | 13-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.103776E+10 | 1525.64 | 01-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.119590E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.924360E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.106642E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.159102E+10 | 2055.72 | 04-JAN-16:00 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.142254E+10 | 1943.63 | 16-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.165132E+10 | 1721.50 | 20-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145276E+10 | 1454.32 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.155890E+10 | 1454.32 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.153775E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.144870E+10 | 1454.32 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.161551E+10 | 1454.32 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.146788E+10 | 1925.32 | 08-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.154952E+10 | 1892.68 | 25-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.158028E+10 | 2367.44 | 13-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.158308E+10 | 2367.44 | 01-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.184593E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.142254E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.165132E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103184E+10 | 1299.00 | 04-JAN-16:00 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.919847E+09 | 1266.26 | 16-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.106536E+10 | 1202.08 | 22-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.933498E+09 | 937.20 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.100027E+10 | 937.20 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.987545E+09 | 1065.42 | 08-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.931216E+09 | 937.20 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103935E+10 | 937.20 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.945539E+09 | 1249.03 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.100495E+10 | 1262.57 | 25-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.101970E+10 | 1525.64 | 13-NOV-16:00 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.102605E+10 | 1525.64 | 01-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119051E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.919847E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.106536E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162645E+10 | 2179.03 | 09-JAN-16:00 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.143992E+10 | 1971.84 | 16-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.165744E+10 | 1771.54 | 20-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.144979E+10 | 1454.29 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.155213E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.152965E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.144301E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.161201E+10 | 1454.29 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.146961E+10 | 1941.80 | 08-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.156962E+10 | 1942.55 | 25-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.160831E+10 | 2367.39 | 13-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.162270E+10 | 2367.39 | 01-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.185807E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.143992E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.165744E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104057E+10 | 1403.33 | 09-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.924669E+09 | 1248.75 | 16-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.106669E+10 | 1066.60 | 14-MAR-15:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.936837E+09 | 937.20 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.100527E+10 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.990013E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.932937E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.104134E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.946793E+09 | 1232.49 | 08-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100459E+10 | 1190.97 | 25-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.103426E+10 | 1525.64 | 13-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.103808E+10 | 1525.64 | 01-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.119621E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.924669E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.106669E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.159180E+10 | 2066.72 | 04-JAN-16:00 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.142314E+10 | 1956.53 | 16-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.165186E+10 | 1741.22 | 20-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145317E+10 | 1454.32 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.155946E+10 | 1454.32 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.153845E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.144928E+10 | 1454.32 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.161599E+10 | 1454.32 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.146856E+10 | 1938.63 | 08-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.154804E+10 | 1907.25 | 25-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.158110E+10 | 2367.44 | 13-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.158472E+10 | 2367.44 | 01-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.184656E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.142314E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.165186E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103225E+10 | 1302.95 | 04-JAN-16:00 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.920135E+09 | 1268.25 | 16-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.106565E+10 | 1204.43 | 22-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.933653E+09 | 937.20 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.100037E+10 | 937.20 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.987665E+09 | 1068.55 | 08-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.931339E+09 | 937.20 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103953E+10 | 937.20 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.945734E+09 | 1251.14 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.100529E+10 | 1264.61 | 25-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.102018E+10 | 1525.64 | 13-NOV-16:00 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.102635E+10 | 1525.64 | 01-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119081E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.920135E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.106565E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162657E+10 | 2179.25 | 09-JAN-16:00 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.143994E+10 | 1971.40 | 16-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.165752E+10 | 1771.00 | 20-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.144980E+10 | 1454.29 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.155213E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.152965E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.144297E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.161201E+10 | 1454.29 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.146962E+10 | 1941.33 | 08-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.156968E+10 | 1942.15 | 25-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.160834E+10 | 2367.39 | 13-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.162274E+10 | 2367.39 | 01-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.185810E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.143994E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.165752E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104054E+10 | 1403.50 | 09-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.924678E+09 | 1248.50 | 16-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.106669E+10 | 1066.24 | 14-MAR-15:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.936841E+09 | 937.20 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.100528E+10 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.990020E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.932938E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.104135E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.946798E+09 | 1232.22 | 08-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100467E+10 | 1190.78 | 25-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.103428E+10 | 1525.64 | 13-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.103810E+10 | 1525.64 | 01-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.119622E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.924678E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.106669E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.159182E+10 | 2066.62 | 04-JAN-16:00 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.142314E+10 | 1956.10 | 16-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.165186E+10 | 1740.70 | 20-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145314E+10 | 1454.32 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.155949E+10 | 1454.32 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.153846E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.144928E+10 | 1454.32 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.161599E+10 | 1454.32 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.146857E+10 | 1938.17 | 08-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.154805E+10 | 1906.86 | 25-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.158111E+10 | 2367.44 | 13-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.158473E+10 | 2367.44 | 01-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.184656E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.142314E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.165186E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103227E+10 | 1302.94 | 04-JAN-16:00 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.920142E+09 | 1267.98 | 16-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.106572E+10 | 1204.27 | 22-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.933662E+09 | 937.20 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.100037E+10 | 937.20 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.987668E+09 | 1068.19 | 08-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.931339E+09 | 937.20 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103953E+10 | 937.20 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.945744E+09 | 1250.85 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.100531E+10 | 1264.36 | 25-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.102019E+10 | 1525.64 | 13-NOV-16:00 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.102637E+10 | 1525.64 | 01-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119083E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.920142E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.106572E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.565679E+10 | 5919.59 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.513113E+10 | 5919.59 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.609720E+10 | 5919.59 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.544605E+10 | 5919.59 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.587700E+10 | 5919.59 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.584858E+10 | 5919.59 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.547447E+10 | 5919.59 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.609720E+10 | 5919.59 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.544605E+10 | 5919.59 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.565679E+10 | 5919.59 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.559049E+10 | 5919.59 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.547447E+10 | 5919.59 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.677962E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.513113E+10 | 5919.59 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.609720E+10 | 5919.59 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.208436E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.207428E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.198274E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.240449E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.162420E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695030E+09 |
February | 0.136985E+10 | 0.143857E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645115E+09 |
March | 0.163685E+10 | 0.165636E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634182E+09 |
April | 0.145243E+10 | 0.144954E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1150363.21 | 0.446280E+09 |
May | 0.157338E+10 | 0.155194E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11691605.36 | 0.305758E+09 |
June | 0.156900E+10 | 0.152932E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53164491.57 | 0.157802E+09 |
July | 0.145680E+10 | 0.144271E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76926663.65 | 78818888.75 |
August | 0.163685E+10 | 0.161203E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38336800.48 | 0.103815E+09 |
September | 0.145243E+10 | 0.146879E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13314422.48 | 0.182690E+09 |
October | 0.150991E+10 | 0.156813E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3198289.41 | 0.342482E+09 |
November | 0.149516E+10 | 0.160651E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561333E+09 |
December | 0.145680E+10 | 0.162056E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650712E+09 |
Annual Sum or Average | 0.181194E+11 | 0.185687E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197783E+09 | 0.480402E+10 |
Minimum of Months | 0.136985E+10 | 0.143857E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78818888.75 |
Maximum of Months | 0.163685E+10 | 0.165636E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76926663.65 | 0.695030E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.104017E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466690E+09 |
February | 0.882782E+09 | 0.924360E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429055E+09 |
March | 0.105485E+10 | 0.106642E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417429E+09 |
April | 0.936002E+09 | 0.936714E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 928184.60 | 0.290250E+09 |
May | 0.101394E+10 | 0.100511E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8090746.98 | 0.205300E+09 |
June | 0.101113E+10 | 0.989807E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38063095.07 | 98700939.96 |
July | 0.938820E+09 | 0.932797E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55190321.63 | 44781657.81 |
August | 0.105485E+10 | 0.104119E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28836018.41 | 54288212.40 |
September | 0.936002E+09 | 0.946609E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9350833.83 | 0.119742E+09 |
October | 0.973041E+09 | 0.100426E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2282341.44 | 0.226684E+09 |
November | 0.963541E+09 | 0.103376E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370305E+09 |
December | 0.938820E+09 | 0.103776E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426967E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119590E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142742E+09 | 0.315019E+10 |
Minimum of Months | 0.882782E+09 | 0.924360E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44781657.81 |
Maximum of Months | 0.105485E+10 | 0.106642E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55190321.63 | 0.466690E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.159102E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727062E+09 |
February | 0.136988E+10 | 0.142254E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674271E+09 |
March | 0.163688E+10 | 0.165132E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649207E+09 |
April | 0.145246E+10 | 0.145276E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1077527.54 | 0.452824E+09 |
May | 0.157341E+10 | 0.155890E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10915496.20 | 0.304296E+09 |
June | 0.156904E+10 | 0.153775E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55412902.21 | 0.151655E+09 |
July | 0.145684E+10 | 0.144870E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77222062.47 | 75730845.14 |
August | 0.163688E+10 | 0.161551E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37240971.14 | 0.103481E+09 |
September | 0.145246E+10 | 0.146788E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11537571.51 | 0.195336E+09 |
October | 0.150994E+10 | 0.154952E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2529450.16 | 0.365699E+09 |
November | 0.149520E+10 | 0.158028E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594323E+09 |
December | 0.145684E+10 | 0.158308E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679274E+09 |
Annual Sum or Average | 0.181198E+11 | 0.184593E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195936E+09 | 0.497316E+10 |
Minimum of Months | 0.136988E+10 | 0.142254E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75730845.14 |
Maximum of Months | 0.163688E+10 | 0.165132E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77222062.47 | 0.727062E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103184E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486933E+09 |
February | 0.882782E+09 | 0.919847E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462276E+09 |
March | 0.105485E+10 | 0.106536E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464033E+09 |
April | 0.936002E+09 | 0.933498E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 702957.27 | 0.339941E+09 |
May | 0.101394E+10 | 0.100027E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6725789.15 | 0.221899E+09 |
June | 0.101113E+10 | 0.987545E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33060659.34 | 0.116731E+09 |
July | 0.938820E+09 | 0.931216E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48001073.85 | 60759121.20 |
August | 0.105485E+10 | 0.103935E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22983865.29 | 86920029.12 |
September | 0.936002E+09 | 0.945539E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8456513.64 | 0.135690E+09 |
October | 0.973041E+09 | 0.100495E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1888683.16 | 0.251700E+09 |
November | 0.963541E+09 | 0.101970E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411099E+09 |
December | 0.938820E+09 | 0.102605E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483196E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119051E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121820E+09 | 0.352118E+10 |
Minimum of Months | 0.882782E+09 | 0.919847E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60759121.20 |
Maximum of Months | 0.105485E+10 | 0.106536E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48001073.85 | 0.486933E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.162645E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143434E+10 |
February | 0.136985E+10 | 0.143992E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134188E+10 |
March | 0.163685E+10 | 0.165744E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132418E+10 |
April | 0.145243E+10 | 0.144979E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2975606.11 | 0.959573E+09 |
May | 0.157338E+10 | 0.155213E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28519946.31 | 0.674751E+09 |
June | 0.156900E+10 | 0.152965E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121925E+09 | 0.367532E+09 |
July | 0.145680E+10 | 0.144301E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174847E+09 | 0.211390E+09 |
August | 0.163685E+10 | 0.161201E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91003638.76 | 0.274923E+09 |
September | 0.145243E+10 | 0.146961E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31997789.12 | 0.400349E+09 |
October | 0.150991E+10 | 0.156962E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7572862.13 | 0.720781E+09 |
November | 0.149516E+10 | 0.160831E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114509E+10 |
December | 0.145680E+10 | 0.162270E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131484E+10 |
Annual Sum or Average | 0.181194E+11 | 0.185807E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458841E+09 | 0.101696E+11 |
Minimum of Months | 0.136985E+10 | 0.143992E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211390E+09 |
Maximum of Months | 0.163685E+10 | 0.165744E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174847E+09 | 0.143434E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.104057E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985242E+09 |
February | 0.649041E+09 | 0.924669E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919591E+09 |
March | 0.773965E+09 | 0.106669E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910568E+09 |
April | 0.688021E+09 | 0.936837E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2076287.33 | 0.683799E+09 |
May | 0.744847E+09 | 0.100527E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17968160.29 | 0.469269E+09 |
June | 0.742030E+09 | 0.990013E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84144692.69 | 0.243968E+09 |
July | 0.690839E+09 | 0.932937E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117925E+09 | 0.146310E+09 |
August | 0.773965E+09 | 0.104134E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61236414.07 | 0.189377E+09 |
September | 0.688021E+09 | 0.946793E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21609516.51 | 0.273084E+09 |
October | 0.715730E+09 | 0.100459E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5353951.25 | 0.500281E+09 |
November | 0.708685E+09 | 0.103426E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789813E+09 |
December | 0.690839E+09 | 0.103808E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898979E+09 |
Annual Sum or Average | 0.858171E+10 | 0.119621E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310314E+09 | 0.701028E+10 |
Minimum of Months | 0.649041E+09 | 0.924669E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146310E+09 |
Maximum of Months | 0.773965E+09 | 0.106669E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117925E+09 | 0.985242E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.159180E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163577E+10 |
February | 0.136988E+10 | 0.142314E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151965E+10 |
March | 0.163688E+10 | 0.165186E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145377E+10 |
April | 0.145246E+10 | 0.145317E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2252140.33 | 0.103195E+10 |
May | 0.157341E+10 | 0.155946E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24481515.38 | 0.687095E+09 |
June | 0.156904E+10 | 0.153845E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127484E+09 | 0.357304E+09 |
July | 0.145684E+10 | 0.144928E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173793E+09 | 0.210711E+09 |
August | 0.163688E+10 | 0.161599E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84765650.31 | 0.291321E+09 |
September | 0.145246E+10 | 0.146856E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25076746.21 | 0.451383E+09 |
October | 0.150994E+10 | 0.154804E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5046081.65 | 0.838592E+09 |
November | 0.149520E+10 | 0.158110E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133628E+10 |
December | 0.145684E+10 | 0.158472E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150867E+10 |
Annual Sum or Average | 0.181198E+11 | 0.184656E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442899E+09 | 0.113225E+11 |
Minimum of Months | 0.136988E+10 | 0.142314E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210711E+09 |
Maximum of Months | 0.163688E+10 | 0.165186E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173793E+09 | 0.163577E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103225E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101010E+10 |
February | 0.882782E+09 | 0.920135E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.949373E+09 |
March | 0.105485E+10 | 0.106565E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937520E+09 |
April | 0.936002E+09 | 0.933653E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1489070.68 | 0.704097E+09 |
May | 0.101394E+10 | 0.100037E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16149936.95 | 0.478543E+09 |
June | 0.101113E+10 | 0.987665E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77814618.79 | 0.261529E+09 |
July | 0.938820E+09 | 0.931339E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115100E+09 | 0.153463E+09 |
August | 0.105485E+10 | 0.103953E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57850085.08 | 0.203818E+09 |
September | 0.936002E+09 | 0.945734E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20601561.17 | 0.290468E+09 |
October | 0.973041E+09 | 0.100529E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4812152.21 | 0.517952E+09 |
November | 0.963541E+09 | 0.102018E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812268E+09 |
December | 0.938820E+09 | 0.102635E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930553E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119081E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293817E+09 | 0.724968E+10 |
Minimum of Months | 0.882782E+09 | 0.920135E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153463E+09 |
Maximum of Months | 0.105485E+10 | 0.106565E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115100E+09 | 0.101010E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.162657E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163310E+10 |
February | 0.136985E+10 | 0.143994E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154635E+10 |
March | 0.163685E+10 | 0.165752E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151565E+10 |
April | 0.145243E+10 | 0.144980E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3477842.06 | 0.111970E+10 |
May | 0.157338E+10 | 0.155213E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33399590.76 | 0.804227E+09 |
June | 0.156900E+10 | 0.152965E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145402E+09 | 0.448747E+09 |
July | 0.145680E+10 | 0.144297E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207051E+09 | 0.266099E+09 |
August | 0.163685E+10 | 0.161201E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106777E+09 | 0.340671E+09 |
September | 0.145243E+10 | 0.146962E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37185575.78 | 0.485195E+09 |
October | 0.150991E+10 | 0.156968E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9414542.99 | 0.828837E+09 |
November | 0.149516E+10 | 0.160834E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128372E+10 |
December | 0.145680E+10 | 0.162274E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148329E+10 |
Annual Sum or Average | 0.181194E+11 | 0.185810E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542707E+09 | 0.117556E+11 |
Minimum of Months | 0.136985E+10 | 0.143994E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266099E+09 |
Maximum of Months | 0.163685E+10 | 0.165752E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207051E+09 | 0.163310E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.104054E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112269E+10 |
February | 0.882782E+09 | 0.924678E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106469E+10 |
March | 0.105485E+10 | 0.106669E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106450E+10 |
April | 0.936002E+09 | 0.936841E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2087583.39 | 0.823843E+09 |
May | 0.101394E+10 | 0.100528E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20018624.53 | 0.573814E+09 |
June | 0.101113E+10 | 0.990020E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98616769.78 | 0.304209E+09 |
July | 0.938820E+09 | 0.932938E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137815E+09 | 0.187170E+09 |
August | 0.105485E+10 | 0.104135E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71198690.85 | 0.238746E+09 |
September | 0.936002E+09 | 0.946798E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24207783.94 | 0.338862E+09 |
October | 0.973041E+09 | 0.100467E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6097456.95 | 0.593812E+09 |
November | 0.963541E+09 | 0.103428E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898323E+09 |
December | 0.938820E+09 | 0.103810E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101685E+10 |
Annual Sum or Average | 0.116768E+11 | 0.119622E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360042E+09 | 0.822751E+10 |
Minimum of Months | 0.882782E+09 | 0.924678E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187170E+09 |
Maximum of Months | 0.105485E+10 | 0.106669E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137815E+09 | 0.112269E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.159182E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186378E+10 |
February | 0.136988E+10 | 0.142314E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175769E+10 |
March | 0.163688E+10 | 0.165186E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169415E+10 |
April | 0.145246E+10 | 0.145314E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2434356.96 | 0.122348E+10 |
May | 0.157341E+10 | 0.155949E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28451152.05 | 0.823780E+09 |
June | 0.156904E+10 | 0.153846E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151289E+09 | 0.436511E+09 |
July | 0.145684E+10 | 0.144928E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206542E+09 | 0.265342E+09 |
August | 0.163688E+10 | 0.161599E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100988E+09 | 0.363019E+09 |
September | 0.145246E+10 | 0.146857E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30111957.99 | 0.554753E+09 |
October | 0.150994E+10 | 0.154805E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6447387.70 | 0.993426E+09 |
November | 0.149520E+10 | 0.158111E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153183E+10 |
December | 0.145684E+10 | 0.158473E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171595E+10 |
Annual Sum or Average | 0.181198E+11 | 0.184656E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526263E+09 | 0.132237E+11 |
Minimum of Months | 0.136988E+10 | 0.142314E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265342E+09 |
Maximum of Months | 0.163688E+10 | 0.165186E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206542E+09 | 0.186378E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.103227E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116014E+10 |
February | 0.882782E+09 | 0.920142E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110801E+10 |
March | 0.105485E+10 | 0.106572E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110025E+10 |
April | 0.936002E+09 | 0.933662E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1623959.38 | 0.842207E+09 |
May | 0.101394E+10 | 0.100037E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19545113.07 | 0.578626E+09 |
June | 0.101113E+10 | 0.987668E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94451429.93 | 0.322070E+09 |
July | 0.938820E+09 | 0.931339E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138501E+09 | 0.191493E+09 |
August | 0.105485E+10 | 0.103953E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69406884.08 | 0.252440E+09 |
September | 0.936002E+09 | 0.945744E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24185481.74 | 0.357112E+09 |
October | 0.973041E+09 | 0.100531E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5927893.33 | 0.614828E+09 |
November | 0.963541E+09 | 0.102019E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935397E+09 |
December | 0.938820E+09 | 0.102637E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106535E+10 |
Annual Sum or Average | 0.116768E+11 | 0.119083E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353642E+09 | 0.852791E+10 |
Minimum of Months | 0.882782E+09 | 0.920142E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191493E+09 |
Maximum of Months | 0.105485E+10 | 0.106572E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138501E+09 | 0.116014E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.565679E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.513113E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.609720E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.544605E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.587700E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.584858E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.547447E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.609720E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.544605E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.565679E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.559049E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.547447E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.677962E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.513113E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.609720E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151085E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139347E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135671E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 811496.91 | 0.960487E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18575417.16 | 0.646008E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97154410.41 | 0.336732E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142322E+09 | 0.178240E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66651215.56 | 0.245722E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20622405.84 | 0.389562E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3852449.16 | 0.742289E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121727E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140760E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349990E+09 | 0.103849E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178240E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142322E+09 | 0.151085E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255979E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238238E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232806E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1663966.74 | 0.165916E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35484805.25 | 0.113406E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176275E+09 | 0.597599E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256977E+09 | 0.329158E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123286E+09 | 0.450335E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38181507.08 | 0.680893E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7209269.94 | 0.128323E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207372E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236159E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639077E+09 | 0.178400E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329158E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256977E+09 | 0.255979E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258225E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247660E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248319E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67541.31 | 0.185444E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19325006.01 | 0.128443E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159461E+09 | 0.682936E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226808E+09 | 0.398520E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105616E+09 | 0.533236E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26162914.14 | 0.782792E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3752000.65 | 0.137492E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212478E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236951E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541193E+09 | 0.189476E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398520E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226808E+09 | 0.258225E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 20994.62 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 20994.62 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 20994.62 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 20994.62 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 20994.62 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 20994.62 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 20994.62 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 20994.62 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 20994.62 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 20994.62 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 20994.62 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 20994.62 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2171.33 | 09-JAN-16:00 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2008.04 | 16-JAN-17:52 |
February | 2010.79 | 01-FEB-10:09 | 1959.63 | 16-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1509.05 | 05-FEB-00:55 |
March | 2010.79 | 01-MAR-10:09 | 1753.13 | 20-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1358.50 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 1454.29 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 29-APR-16:00 | 1476.81 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.73 | 14-MAY-17:00 | 916.30 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.84 | 18-JUN-16:20 | 710.08 | 10-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 512.39 | 04-JUL-14:51 | 358.40 | 15-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 1454.29 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.25 | 05-AUG-17:10 | 368.39 | 22-AUG-21:50 |
September | 2010.79 | 01-SEP-09:09 | 1928.61 | 08-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.19 | 03-SEP-15:00 | 528.77 | 18-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 1929.54 | 25-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.38 | 01-OCT-16:20 | 845.26 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 13-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1522.04 | 26-NOV-05:55 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2132.46 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.40 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 512.39 | 2132.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1399.97 | 09-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1345.28 | 16-JAN-17:52 |
February | 1295.83 | 01-FEB-10:09 | 1246.20 | 16-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1011.44 | 05-FEB-00:55 |
March | 1295.83 | 01-MAR-10:09 | 1063.32 | 14-MAR-15:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 899.70 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 937.20 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 | 29-APR-17:50 | 966.13 | 07-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.07 | 14-MAY-17:00 | 597.64 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.38 | 18-JUN-16:20 | 463.10 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.56 | 04-JUL-15:00 | 235.01 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.08 | 05-AUG-17:10 | 293.33 | 27-AUG-07:50 |
September | 1295.83 | 01-SEP-09:09 | 1229.70 | 08-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.48 | 03-SEP-15:00 | 361.27 | 18-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 1186.76 | 25-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.51 | 01-OCT-16:20 | 555.55 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 13-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 997.90 | 26-NOV-05:55 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1394.40 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.01 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 357.56 | 1394.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2055.72 | 04-JAN-16:00 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1999.53 | 16-JAN-17:52 |
February | 2010.83 | 01-FEB-10:09 | 1943.63 | 16-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1576.16 | 05-FEB-00:55 |
March | 2010.83 | 01-MAR-10:09 | 1721.50 | 20-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1383.67 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 1454.32 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 29-APR-16:00 | 1490.40 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1454.32 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.86 | 14-MAY-17:00 | 897.54 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 427.45 | 18-JUN-16:20 | 692.22 | 10-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 1454.32 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 506.04 | 04-JUL-14:51 | 365.45 | 15-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 1454.32 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.67 | 05-AUG-17:10 | 378.63 | 22-AUG-21:50 |
September | 2010.83 | 01-SEP-09:09 | 1925.32 | 08-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.33 | 03-SEP-14:55 | 569.21 | 18-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 1892.68 | 25-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.45 | 11-OCT-14:00 | 873.86 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 13-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1535.60 | 03-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2179.97 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.45 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 506.04 | 2179.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1299.00 | 04-JAN-16:00 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1408.69 | 16-JAN-17:52 |
February | 1295.83 | 01-FEB-10:09 | 1266.26 | 16-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1104.97 | 05-FEB-00:55 |
March | 1295.83 | 01-MAR-10:09 | 1202.08 | 22-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1013.30 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 937.20 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 29-APR-16:00 | 1122.86 | 07-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.37 | 14-MAY-17:40 | 673.33 | 18-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1065.42 | 08-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.39 | 18-JUN-16:00 | 559.51 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.94 | 04-JUL-15:00 | 291.16 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.50 | 20-AUG-17:04 | 340.97 | 22-AUG-21:50 |
September | 1295.83 | 01-SEP-09:09 | 1249.03 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.00 | 03-SEP-15:00 | 402.71 | 18-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 1262.57 | 25-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 | 11-OCT-13:00 | 622.28 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 13-NOV-16:00 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1116.15 | 03-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1584.51 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.16 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 329.94 | 1584.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2179.03 | 09-JAN-16:00 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3837.17 | 16-JAN-17:52 |
February | 2010.79 | 01-FEB-10:09 | 1971.84 | 16-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3027.70 | 05-FEB-00:55 |
March | 2010.79 | 01-MAR-10:09 | 1771.54 | 20-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2678.46 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 1454.29 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.65 | 01-APR-17:10 | 3087.00 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 419.61 | 14-MAY-17:10 | 1970.51 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 931.63 | 18-JUN-16:00 | 1494.33 | 10-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.29 | 04-JUL-14:51 | 833.99 | 15-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 1454.29 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 660.64 | 05-AUG-17:01 | 812.79 | 08-AUG-00:52 |
September | 2010.79 | 01-SEP-09:09 | 1941.80 | 08-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 448.75 | 03-SEP-14:50 | 1090.94 | 07-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 1942.55 | 25-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.18 | 01-OCT-16:30 | 1835.41 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 13-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3080.44 | 03-NOV-21:03 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4184.03 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 812.79 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.29 | 4184.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1403.33 | 09-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2620.14 | 16-JAN-17:52 |
February | 1239.33 | 01-FEB-08:09 | 1248.75 | 16-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2074.15 | 05-FEB-00:55 |
March | 1239.33 | 01-MAR-08:09 | 1066.60 | 14-MAR-15:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1843.76 | 14-MAR-03:00 |
April | 1239.33 | 03-APR-07:10 | 937.20 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.94 | 01-APR-17:50 | 2168.56 | 23-APR-09:00 |
May | 1239.33 | 01-MAY-07:10 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.67 | 14-MAY-17:10 | 1282.97 | 03-MAY-22:00 |
June | 1239.33 | 01-JUN-07:10 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 691.54 | 18-JUN-16:30 | 993.76 | 10-JUN-01:00 |
July | 1239.33 | 03-JUL-07:10 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 795.20 | 04-JUL-15:10 | 595.74 | 15-JUL-19:00 |
August | 1239.33 | 01-AUG-07:10 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.55 | 05-AUG-17:10 | 675.49 | 27-AUG-07:40 |
September | 1239.33 | 01-SEP-07:10 | 1232.49 | 08-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.11 | 03-SEP-15:10 | 765.95 | 18-SEP-01:00 |
October | 1239.33 | 02-OCT-07:10 | 1190.97 | 25-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.51 | 01-OCT-16:30 | 1220.20 | 11-OCT-23:00 |
November | 1239.33 | 01-NOV-07:10 | 1525.64 | 13-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2037.37 | 03-NOV-21:03 |
December | 1239.33 | 01-DEC-08:09 | 1525.64 | 01-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2821.87 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595.74 | |||||
Maximum of Months | 1239.33 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 795.20 | 2821.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2066.72 | 04-JAN-16:00 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4305.24 | 16-JAN-17:52 |
February | 2010.83 | 01-FEB-10:09 | 1956.53 | 16-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3422.89 | 05-FEB-00:55 |
March | 2010.83 | 01-MAR-10:09 | 1741.22 | 20-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2908.78 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 1454.32 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.68 | 29-APR-16:00 | 3204.43 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1454.32 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.90 | 14-MAY-17:10 | 1943.18 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 966.38 | 18-JUN-15:50 | 1471.90 | 10-JUN-01:30 |
July | 2010.83 | 03-JUL-09:09 | 1454.32 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.55 | 04-JUL-15:04 | 857.77 | 15-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 1454.32 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 622.70 | 05-AUG-17:01 | 855.05 | 08-AUG-00:52 |
September | 2010.83 | 01-SEP-09:09 | 1938.63 | 08-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.25 | 03-SEP-15:06 | 1277.68 | 17-SEP-20:00 |
October | 2010.83 | 02-OCT-09:09 | 1907.25 | 25-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.10 | 11-OCT-15:00 | 1936.60 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 13-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3328.30 | 03-NOV-21:10 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4564.17 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 855.05 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.55 | 4564.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1302.95 | 04-JAN-16:00 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2735.01 | 16-JAN-17:52 |
February | 1295.83 | 01-FEB-10:09 | 1268.25 | 16-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2190.26 | 05-FEB-00:55 |
March | 1295.83 | 01-MAR-10:09 | 1204.43 | 22-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1870.82 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 937.20 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 | 29-APR-16:00 | 2331.40 | 15-APR-17:09 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.75 | 21-MAY-16:40 | 1382.32 | 18-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1068.55 | 08-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 540.70 | 18-JUN-16:00 | 1102.05 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 723.85 | 04-JUL-15:10 | 622.99 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.03 | 20-AUG-17:00 | 639.33 | 08-AUG-00:52 |
September | 1295.83 | 01-SEP-09:09 | 1251.14 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.33 | 03-SEP-15:10 | 861.75 | 17-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 1264.61 | 25-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.38 | 11-OCT-13:00 | 1278.83 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 13-NOV-16:00 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2137.56 | 03-NOV-21:13 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2914.48 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.99 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 723.85 | 2914.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2179.25 | 09-JAN-16:00 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4344.74 | 16-JAN-17:52 |
February | 2010.79 | 01-FEB-10:09 | 1971.40 | 16-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3488.27 | 05-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 1771.00 | 20-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3216.43 | 14-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 1454.29 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.06 | 01-APR-17:01 | 3589.26 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 471.52 | 14-MAY-16:40 | 2292.68 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.15 | 18-JUN-15:50 | 1809.98 | 04-JUN-16:55 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1381.21 | 04-JUL-15:04 | 1081.52 | 15-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 1454.29 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 765.55 | 05-AUG-17:01 | 991.06 | 08-AUG-00:52 |
September | 2010.79 | 01-SEP-09:09 | 1941.33 | 08-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 500.12 | 03-SEP-14:50 | 1286.48 | 07-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 1942.15 | 25-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.27 | 01-OCT-16:00 | 2197.33 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 13-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3754.46 | 03-NOV-21:03 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4974.66 | 14-DEC-04:08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 991.06 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1381.21 | 4974.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1403.50 | 09-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2903.55 | 16-JAN-17:52 |
February | 1295.83 | 01-FEB-10:09 | 1248.50 | 16-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2325.48 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1066.24 | 14-MAR-15:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2144.25 | 14-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 937.20 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.56 | 01-APR-17:50 | 2640.42 | 23-APR-09:00 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.28 | 14-MAY-16:40 | 1506.01 | 18-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 831.58 | 18-JUN-15:50 | 1269.72 | 04-JUN-16:55 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 971.71 | 04-JUL-15:04 | 778.36 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 537.03 | 05-AUG-17:10 | 822.78 | 27-AUG-07:40 |
September | 1295.83 | 01-SEP-09:09 | 1232.22 | 08-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.25 | 03-SEP-15:10 | 952.44 | 17-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 1190.78 | 25-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.92 | 01-OCT-16:00 | 1470.29 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 13-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2512.83 | 03-NOV-21:03 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3324.47 | 14-DEC-04:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 778.36 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 971.71 | 3324.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2066.62 | 04-JAN-16:00 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4418.33 | 16-JAN-17:52 |
February | 2010.83 | 01-FEB-10:09 | 1956.10 | 16-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3783.35 | 05-FEB-00:55 |
March | 2010.83 | 01-MAR-10:09 | 1740.70 | 20-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3329.28 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 1454.32 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.38 | 29-APR-16:00 | 3773.23 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1454.32 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.62 | 14-MAY-16:40 | 2255.32 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1136.02 | 18-JUN-15:50 | 1808.49 | 04-JUN-16:55 |
July | 2010.83 | 03-JUL-09:09 | 1454.32 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1405.58 | 04-JUL-15:04 | 1113.64 | 15-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 1454.32 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 730.17 | 20-AUG-16:51 | 1044.88 | 22-AUG-22:00 |
September | 2010.83 | 01-SEP-09:09 | 1938.17 | 08-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.42 | 03-SEP-15:06 | 1611.92 | 17-SEP-20:00 |
October | 2010.83 | 02-OCT-09:09 | 1906.86 | 25-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.05 | 11-OCT-14:00 | 2333.88 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 13-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3966.65 | 03-NOV-21:03 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5079.61 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.88 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1405.58 | 5079.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1302.94 | 04-JAN-16:00 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2930.02 | 16-JAN-17:52 |
February | 1295.83 | 01-FEB-10:09 | 1267.98 | 16-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2431.24 | 05-FEB-00:55 |
March | 1295.83 | 01-MAR-10:09 | 1204.27 | 22-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2144.17 | 14-MAR-05:00 |
April | 1295.83 | 03-APR-09:09 | 937.20 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.25 | 29-APR-16:00 | 2807.39 | 15-APR-17:10 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.19 | 21-MAY-17:30 | 1648.13 | 18-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1068.19 | 08-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 657.55 | 18-JUN-16:00 | 1304.16 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 887.56 | 04-JUL-15:10 | 801.89 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.41 | 20-AUG-17:00 | 776.84 | 08-AUG-00:52 |
September | 1295.83 | 01-SEP-09:09 | 1250.85 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 375.64 | 03-SEP-15:10 | 1084.93 | 17-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 1264.36 | 25-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.65 | 01-OCT-15:56 | 1541.28 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 13-NOV-16:00 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2545.56 | 03-NOV-21:03 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3344.72 | 14-DEC-04:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 776.84 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 887.56 | 3344.72 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5919.59 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5919.59 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5919.59 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5919.59 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5919.59 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5919.59 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5919.59 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5919.59 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5919.59 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5919.59 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5919.59 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5919.59 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4324.41 | 16-JAN-17:52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3352.07 | 05-FEB-00:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2913.35 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.85 | 26-APR-15:00 | 3126.87 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.52 | 14-MAY-17:00 | 1911.46 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 797.73 | 18-JUN-16:00 | 1482.95 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1042.81 | 04-JUL-15:00 | 692.47 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.81 | 05-AUG-17:01 | 732.43 | 22-AUG-21:57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.21 | 03-SEP-15:00 | 1092.48 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.28 | 01-OCT-16:00 | 1759.39 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3348.48 | 26-NOV-05:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4672.85 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 692.47 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1042.81 | 4672.85 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7159.12 | 16-JAN-17:52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5715.06 | 05-FEB-00:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4905.88 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.76 | 17-APR-15:00 | 5424.19 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 591.28 | 14-MAY-16:51 | 3351.57 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1466.92 | 18-JUN-16:00 | 2571.84 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1879.31 | 04-JUL-14:51 | 1256.26 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1009.75 | 05-AUG-17:01 | 1283.32 | 22-AUG-22:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.64 | 03-SEP-14:50 | 1861.08 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.09 | 01-OCT-16:00 | 3076.04 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5626.44 | 26-NOV-05:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7897.67 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.26 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1879.31 | 7897.67 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6804.75 | 16-JAN-17:52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5627.47 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5033.57 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 | 13-APR-17:00 | 5813.24 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.21 | 14-MAY-17:00 | 3539.37 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1149.51 | 18-JUN-16:10 | 2817.51 | 04-JUN-16:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1599.35 | 04-JUL-14:51 | 1696.57 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 843.66 | 20-AUG-17:00 | 1469.68 | 08-AUG-00:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.54 | 03-SEP-14:50 | 2104.76 | 17-SEP-20:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.36 | 01-OCT-16:00 | 3412.79 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6044.34 | 03-NOV-21:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7781.37 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.68 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1599.35 | 7781.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 115516.25 | 17-JAN-04:01 | 0.00 | 11664.26 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 111319.28 | 13-FEB-04:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 113788.04 | 27-MAR-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 114307.10 | 03-APR-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 109460.82 | 01-MAY-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 106368.80 | 20-JUN-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 93731.80 | 04-JUL-17:05 | 0.00 | 11664.26 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 96157.38 | 29-AUG-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 109359.61 | 11-SEP-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 112941.26 | 23-OCT-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 116836.16 | 06-NOV-04:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 115757.71 | 11-DEC-04:01 | 0.00 | 10497.83 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93731.80 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 116836.16 | 0.00 | 11664.26 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 87590.30 | 03-JAN-05:01 | 0.00 | 16760.51 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90101.37 | 21-FEB-04:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 91514.76 | 27-MAR-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 94903.49 | 24-APR-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 93136.89 | 30-MAY-03:01 | 0.00 | 7332.73 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 94955.14 | 05-JUN-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88285.75 | 18-JUL-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89038.88 | 19-AUG-05:03 | 9673.43 | 12570.39 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94546.74 | 18-SEP-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 94577.61 | 23-OCT-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 92106.12 | 13-NOV-04:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 93165.18 | 26-DEC-04:01 | 0.00 | 9427.79 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 87590.30 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94955.14 | 9673.43 | 16760.51 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 71838.03 | 27-JAN-06:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77184.35 | 15-FEB-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 79463.26 | 09-MAR-06:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81540.08 | 14-APR-04:02 | 0.00 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84706.24 | 22-MAY-03:01 | 0.00 | 7332.73 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84585.57 | 30-JUN-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85748.41 | 10-JUL-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84934.90 | 09-AUG-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86267.45 | 05-SEP-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83063.93 | 06-OCT-03:01 | 0.00 | 7332.73 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 76720.84 | 09-NOV-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 73895.80 | 01-DEC-06:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 71838.03 | 0.00 | 6285.19 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86267.45 | 8061.19 | 10475.32 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 27544.38 | 05-JAN-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 37700.64 | 15-FEB-16:40 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39716.38 | 08-MAR-16:50 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76848.19 | 28-APR-05:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84782.86 | 22-MAY-03:01 | 0.00 | 7332.73 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83946.53 | 30-JUN-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87633.43 | 10-JUL-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85753.31 | 14-AUG-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87167.42 | 05-SEP-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78361.50 | 04-OCT-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 50944.78 | 01-NOV-05:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27709.41 | 01-DEC-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 27544.38 | 0.00 | 6285.19 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87633.43 | 15316.26 | 18854.65 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3870.59 | 02-JAN-15:00 | 2010.79 | 1670.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.46 |
February | 4529.72 | 15-FEB-13:20 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.51 |
March | 6584.23 | 27-MAR-14:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.65 |
April | 8633.67 | 14-APR-14:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 |
May | 13225.29 | 22-MAY-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.44 |
June | 17635.56 | 18-JUN-18:11 | 0.00 | 807.98 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 132.66 | 0.00 |
July | 17305.84 | 04-JUL-18:31 | 0.00 | 565.58 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 204.81 | 0.00 |
August | 15635.47 | 20-AUG-15:41 | 809.73 | 646.38 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 138.11 | 0.00 |
September | 8694.75 | 01-SEP-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 18.99 | 0.00 |
October | 13312.75 | 02-OCT-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 |
November | 4912.55 | 03-NOV-13:30 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.50 |
December | 3887.76 | 11-DEC-13:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3870.59 | 0.00 | 565.58 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17635.56 | 2010.79 | 1670.39 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 204.81 | 95.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6526.47 | 02-JAN-09:25 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.22 |
February | 8847.36 | 14-FEB-09:05 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.09 |
March | 18768.53 | 12-MAR-08:52 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.25 |
April | 21725.41 | 30-APR-08:51 | 456.59 | 364.48 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.43 |
May | 21930.82 | 14-MAY-08:11 | 456.59 | 364.48 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.42 |
June | 22647.30 | 18-JUN-07:31 | 521.82 | 416.55 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21061.04 | 04-JUL-08:32 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 |
August | 20889.70 | 20-AUG-08:22 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 |
September | 21316.42 | 17-SEP-09:12 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.61 |
October | 21183.40 | 01-OCT-08:52 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.59 |
November | 9136.07 | 01-NOV-08:50 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.34 |
December | 6067.22 | 29-DEC-09:15 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6067.22 | 326.14 | 260.35 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22647.30 | 2478.65 | 1874.40 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22866.33 | 01-JAN-12:12 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.49 |
February | 23104.53 | 19-FEB-12:42 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.44 |
March | 22531.69 | 12-MAR-13:32 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.70 |
April | 21623.52 | 30-APR-13:32 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.45 |
May | 13440.28 | 22-MAY-05:03 | 809.75 | 1052.25 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 |
June | 14560.43 | 18-JUN-14:11 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 278.93 | 0.00 |
July | 20887.75 | 30-JUL-14:22 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 122.34 | 0.00 |
August | 21607.69 | 20-AUG-15:01 | 809.75 | 646.40 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 99.58 | 0.00 |
September | 23039.12 | 17-SEP-13:12 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.63 |
October | 23414.81 | 01-OCT-12:11 | 910.97 | 727.20 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 |
November | 23680.33 | 23-NOV-12:31 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.94 |
December | 22499.60 | 31-DEC-13:22 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13440.28 | 607.31 | 484.80 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23680.33 | 910.97 | 1052.25 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 278.93 | 517.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9109.10 | 26-JAN-16:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.38 |
February | 15553.99 | 12-FEB-15:02 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.40 |
March | 25191.71 | 12-MAR-16:12 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.79 |
April | 27176.74 | 16-APR-16:31 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.23 |
May | 27954.15 | 14-MAY-15:31 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 |
June | 30411.24 | 18-JUN-16:51 | 652.28 | 520.69 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 67.21 | 0.00 |
July | 28329.83 | 04-JUL-16:31 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 221.34 | 0.00 |
August | 28940.98 | 20-AUG-15:41 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 65.35 | 0.00 |
September | 25182.86 | 17-SEP-14:32 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.39 |
October | 25555.98 | 01-OCT-14:51 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 0.00 |
November | 24712.85 | 12-NOV-15:02 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.02 |
December | 14039.14 | 31-DEC-15:22 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9109.10 | 326.14 | 260.35 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30411.24 | 1239.33 | 937.20 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 221.34 | 117.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3232.15 | 05-JAN-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.38 |
February | 3648.20 | 15-FEB-15:50 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.65 |
March | 4029.12 | 27-MAR-14:50 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.30 |
April | 7231.55 | 14-APR-14:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 |
May | 8105.17 | 31-MAY-16:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 140.29 | 0.00 |
June | 16580.62 | 25-JUN-17:51 | 0.00 | 807.98 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 381.68 | 0.00 |
July | 16936.43 | 04-JUL-17:01 | 0.00 | 807.98 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 892.05 | 0.00 |
August | 12556.85 | 06-AUG-14:42 | 607.30 | 484.79 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 351.97 | 0.00 |
September | 9844.08 | 05-SEP-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.98 |
October | 7230.92 | 02-OCT-13:40 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 0.00 |
November | 3651.35 | 02-NOV-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.07 |
December | 3068.10 | 29-DEC-15:50 | 1923.11 | 1746.72 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3068.10 | 0.00 | 484.79 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16936.43 | 2010.79 | 1746.72 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 892.05 | 112.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4465.31 | 27-JAN-11:10 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.39 |
February | 7278.24 | 14-FEB-09:40 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.24 |
March | 16279.80 | 26-MAR-09:12 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.71 |
April | 23035.87 | 30-APR-08:51 | 456.59 | 364.48 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 875.94 |
May | 23283.71 | 29-MAY-08:61 | 456.59 | 364.48 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.48 |
June | 24604.96 | 25-JUN-09:11 | 587.05 | 468.62 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.23 |
July | 24482.98 | 04-JUL-07:41 | 521.82 | 416.55 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.25 |
August | 24005.77 | 06-AUG-10:01 | 521.82 | 416.55 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.04 |
September | 21876.66 | 03-SEP-09:02 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 |
October | 22072.23 | 01-OCT-09:02 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.77 |
November | 8058.10 | 01-NOV-09:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.07 |
December | 4332.74 | 29-DEC-11:20 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4332.74 | 326.14 | 260.35 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | |
Maximum of Months | 24604.96 | 1239.33 | 937.20 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 875.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22684.47 | 22-JAN-13:02 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.35 |
February | 21444.69 | 19-FEB-11:32 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 777.50 |
March | 21383.94 | 26-MAR-12:32 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.95 |
April | 20733.46 | 30-APR-13:32 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.44 |
May | 11496.67 | 14-MAY-14:22 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 62.87 | 0.00 |
June | 19084.45 | 25-JUN-16:31 | 1012.19 | 807.99 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 583.68 | 0.00 |
July | 21024.89 | 04-JUL-15:01 | 1012.19 | 807.99 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 961.13 | 0.00 |
August | 21130.02 | 06-AUG-14:02 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 284.03 | 0.00 |
September | 22522.32 | 10-SEP-12:22 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.60 |
October | 24957.17 | 01-OCT-13:01 | 910.97 | 727.20 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.12 |
November | 21426.62 | 23-NOV-12:02 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.97 |
December | 22205.12 | 31-DEC-14:02 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11496.67 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24957.17 | 1012.19 | 807.99 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 961.13 | 777.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7145.13 | 26-JAN-16:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.55 |
February | 10906.17 | 15-FEB-16:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 |
March | 11300.28 | 24-MAR-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.46 |
April | 23230.99 | 16-APR-16:31 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.05 |
May | 25173.01 | 14-MAY-15:41 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 |
June | 27396.46 | 25-JUN-17:11 | 0.00 | 520.69 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 172.87 | 0.00 |
July | 28081.29 | 04-JUL-17:01 | 0.00 | 520.69 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 373.01 | 0.00 |
August | 26622.63 | 13-AUG-16:21 | 652.28 | 520.69 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 18.08 | 0.00 |
September | 24280.31 | 04-SEP-17:01 | 0.00 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.27 |
October | 23924.29 | 01-OCT-15:41 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 | 0.00 |
November | 9423.81 | 02-NOV-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 |
December | 5941.02 | 29-DEC-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5941.02 | 0.00 | 364.48 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28081.29 | 1239.33 | 937.20 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 373.01 | 102.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3293.49 | 05-JAN-14:30 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.44 |
February | 3985.74 | 15-FEB-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.64 |
March | 3823.66 | 08-MAR-14:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 |
April | 7540.87 | 28-APR-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 0.00 |
May | 8786.43 | 31-MAY-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 131.32 | 0.00 |
June | 18757.76 | 25-JUN-17:21 | 0.00 | 646.38 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 630.28 | 0.00 |
July | 19934.68 | 04-JUL-15:01 | 1012.16 | 807.98 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1135.80 | 0.00 |
August | 18298.88 | 13-AUG-16:21 | 1012.16 | 807.98 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 125.33 | 0.00 |
September | 8864.51 | 01-SEP-15:20 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 58.58 | 0.00 |
October | 7591.96 | 02-OCT-13:40 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 21.91 | 0.00 |
November | 3970.12 | 01-NOV-15:10 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.83 |
December | 2918.85 | 29-DEC-15:10 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2918.85 | 0.00 | 646.38 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19934.68 | 2010.79 | 1454.29 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1135.80 | 573.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3747.62 | 03-JAN-13:20 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 |
February | 5424.83 | 14-FEB-10:10 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.95 |
March | 7483.78 | 08-MAR-09:50 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.80 |
April | 18041.91 | 30-APR-09:02 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 917.02 |
May | 23705.85 | 29-MAY-08:51 | 456.59 | 364.48 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.43 |
June | 22419.56 | 25-JUN-09:22 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 |
July | 24704.92 | 04-JUL-07:41 | 521.82 | 416.55 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.49 |
August | 23190.92 | 20-AUG-09:21 | 456.59 | 364.48 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 |
September | 22226.55 | 17-SEP-09:42 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.32 |
October | 15904.70 | 01-OCT-09:12 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.66 |
November | 7025.41 | 01-NOV-09:10 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.43 |
December | 3740.67 | 29-DEC-13:20 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3740.67 | 326.14 | 260.35 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | |
Maximum of Months | 24704.92 | 1295.83 | 937.20 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 917.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22799.78 | 01-JAN-14:52 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1036.78 |
February | 23781.99 | 19-FEB-14:02 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.09 |
March | 23647.77 | 12-MAR-14:12 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.23 |
April | 15123.28 | 28-APR-13:20 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 0.00 |
May | 18894.43 | 21-MAY-13:32 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 30.23 | 0.00 |
June | 16934.28 | 25-JUN-16:41 | 809.75 | 646.40 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 767.91 | 0.00 |
July | 24209.10 | 04-JUL-15:01 | 1012.19 | 807.99 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1103.92 | 0.00 |
August | 23770.23 | 06-AUG-12:12 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 79.69 | 0.00 |
September | 24928.83 | 10-SEP-12:32 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.24 |
October | 25075.66 | 01-OCT-13:12 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 |
November | 23228.01 | 19-NOV-13:51 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 797.82 |
December | 23443.93 | 31-DEC-14:02 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15123.28 | 607.31 | 484.80 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25075.66 | 2010.83 | 1454.32 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1103.92 | 1180.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6330.55 | 26-JAN-16:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.34 |
February | 10681.51 | 15-FEB-16:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.37 |
March | 11272.35 | 07-MAR-16:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.47 |
April | 24434.66 | 09-APR-17:12 | 0.00 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.79 |
May | 25161.17 | 29-MAY-16:11 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.81 |
June | 27186.31 | 25-JUN-16:41 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 356.76 | 0.00 |
July | 30434.53 | 04-JUL-16:21 | 652.28 | 520.69 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 415.44 | 0.00 |
August | 28751.68 | 13-AUG-16:21 | 652.28 | 520.69 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 0.00 |
September | 26096.21 | 04-SEP-17:01 | 0.00 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.38 |
October | 20013.14 | 01-OCT-15:12 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 36.84 | 0.00 |
November | 8970.01 | 02-NOV-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.49 |
December | 5253.97 | 29-DEC-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5253.97 | 0.00 | 312.41 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30434.53 | 1239.33 | 937.20 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 415.44 | 431.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5967.48 | 02-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.07 |
February | 5592.21 | 21-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.78 |
March | 5768.25 | 27-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.34 |
April | 8170.75 | 28-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.63 |
May | 9786.82 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 |
June | 9758.05 | 05-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.82 |
July | 10949.12 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.52 |
August | 14955.87 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.02 |
September | 10638.36 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.41 |
October | 12363.45 | 02-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.55 |
November | 5940.80 | 13-NOV-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 |
December | 4709.74 | 18-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4709.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 | |
Maximum of Months | 14955.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7199.33 | 17-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4870.78 |
February | 5695.12 | 04-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2884.15 |
March | 5076.11 | 09-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.46 |
April | 6589.68 | 14-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.59 |
May | 6406.69 | 23-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.43 |
June | 8182.02 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.90 | 0.00 |
July | 8698.59 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.37 |
August | 8567.03 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.58 | 0.00 |
September | 8154.45 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.57 |
October | 6875.37 | 04-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.21 |
November | 5658.75 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.31 |
December | 5709.18 | 22-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2284.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5076.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8698.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.90 | 4870.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3493.32 | 05-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.90 |
February | 7512.30 | 15-FEB-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.47 |
March | 10060.47 | 08-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.45 |
April | 16573.99 | 28-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 |
May | 19149.32 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 | 0.00 |
June | 24424.25 | 28-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.78 | 0.00 |
July | 23534.00 | 21-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.00 | 0.00 |
August | 22266.33 | 07-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.37 | 0.00 |
September | 17465.70 | 01-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.97 | 0.00 |
October | 13531.93 | 05-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 | 0.00 |
November | 6535.64 | 02-NOV-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.51 |
December | 2975.58 | 31-DEC-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2975.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24424.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.00 | 201.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2488.03 | 26-JAN-17:00 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4542.01 | 15-FEB-17:00 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7130.24 | 31-MAR-24:00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8292.36 | 15-APR-17:55 | 23.38 | 57.88 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3533.62 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5364.83 | 30-JUN-23:23 | 0.00 | 115.75 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7269.66 | 31-JUL-23:57 | 0.00 | 86.81 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8129.85 | 23-AUG-18:00 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3524.63 | 30-SEP-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5321.98 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6393.65 | 06-NOV-16:40 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8195.52 | 26-DEC-16:30 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2488.03 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8292.36 | 222.14 | 520.85 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2264.18 | 26-JAN-17:00 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4251.44 | 15-FEB-17:00 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6546.27 | 31-MAR-24:00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7828.77 | 24-APR-18:00 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3341.93 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5194.84 | 30-JUN-23:55 | 0.00 | 115.75 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7007.21 | 31-JUL-23:57 | 0.00 | 86.81 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7612.57 | 30-AUG-17:30 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3323.45 | 30-SEP-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4834.05 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5914.62 | 02-NOV-16:40 | 70.15 | 289.36 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7554.44 | 29-DEC-16:50 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2264.18 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7828.77 | 222.14 | 520.85 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2178.73 | 26-JAN-17:00 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4266.76 | 15-FEB-17:00 | 222.14 | 520.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6173.30 | 31-MAR-23:20 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7907.93 | 16-APR-17:51 | 0.00 | 202.56 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3288.43 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5196.12 | 30-JUN-23:55 | 0.00 | 115.75 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6990.45 | 31-JUL-23:57 | 0.00 | 86.81 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7749.62 | 30-AUG-17:30 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3305.16 | 30-SEP-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4603.25 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5897.04 | 02-NOV-16:40 | 70.15 | 289.36 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7466.96 | 29-DEC-16:50 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2178.73 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7907.93 | 222.14 | 520.85 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92747.52 | 02-JAN-17:00 | 4808.68 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184425.13 | 15-FEB-17:00 | 4808.68 | 5919.59 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359215.42 | 31-MAR-24:00 | 0.00 | 328.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367579.35 | 18-APR-07:15 | 9617.36 | 11839.17 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176459.54 | 31-MAY-24:00 | 0.00 | 328.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268280.72 | 30-JUN-23:55 | 0.00 | 1315.53 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 354759.61 | 31-JUL-23:30 | 0.00 | 657.76 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 365342.00 | 31-AUG-06:05 | 2024.71 | 3946.44 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176750.26 | 30-SEP-24:00 | 0.00 | 328.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269083.64 | 31-OCT-24:00 | 0.00 | 328.88 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277309.20 | 24-NOV-17:00 | 4808.68 | 5919.59 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367475.74 | 13-DEC-16:55 | 9617.36 | 11839.17 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92747.52 | 0.00 | 328.88 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 367579.35 | 9617.36 | 11839.17 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.177617E+13 | 1158140.62 | 05-JAN-16:10 | 0.286212E+12 | 774700.42 | 17-JAN-07:10 |
February | 0.202237E+13 | 1416293.61 | 14-FEB-16:00 | 0.185710E+12 | 783282.91 | 06-FEB-07:10 |
March | 0.277815E+13 | 1575657.09 | 08-MAR-16:19 | 0.104532E+12 | 404071.15 | 06-MAR-06:10 |
April | 0.319006E+13 | 1944812.77 | 13-APR-15:20 | 0.631821E+11 | 227440.58 | 08-APR-05:10 |
May | 0.205510E+13 | 1472244.39 | 19-MAY-15:20 | 0.596422E+11 | 90066.25 | 05-MAY-05:10 |
June | 0.262058E+13 | 1725559.85 | 26-JUN-15:20 | 0.549933E+11 | 74045.43 | 05-JUN-11:00 |
July | 0.317930E+13 | 1932405.58 | 31-JUL-15:09 | 0.516982E+11 | 71450.54 | 05-JUL-11:39 |
August | 0.371191E+13 | 2101855.59 | 07-AUG-15:00 | 0.546209E+11 | 70735.60 | 30-AUG-11:50 |
September | 0.206873E+13 | 1489733.15 | 06-SEP-15:50 | 0.517354E+11 | 72286.69 | 22-SEP-11:50 |
October | 0.241460E+13 | 1593821.17 | 02-OCT-15:00 | 0.740593E+11 | 435113.66 | 26-OCT-06:19 |
November | 0.263427E+13 | 1529488.60 | 02-NOV-15:00 | 0.115319E+12 | 572966.12 | 27-NOV-07:10 |
December | 0.310077E+13 | 1675926.83 | 19-DEC-16:00 | 0.270976E+12 | 695205.48 | 15-DEC-07:10 |
Annual Sum or Average | 0.315520E+14 | 0.137268E+13 | ||||
Minimum of Months | 0.177617E+13 | 1158140.62 | 0.516982E+11 | 70735.60 | ||
Maximum of Months | 0.371191E+13 | 2101855.59 | 0.286212E+12 | 783282.91 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.311392E+12 | 0.695003E+11 | 0.811612E+12 | 0.164870E+12 | 0.209589E+12 | 0.206191E+11 | 0.00 | 0.114010E+12 | 0.180283E+11 | 0.565455E+11 | 0.00 | 0.00 | 0.00 |
February | 0.281359E+12 | 0.583922E+11 | 0.102011E+13 | 0.148925E+12 | 0.193711E+12 | 0.221940E+11 | 0.00 | 0.178368E+12 | 0.358058E+11 | 0.835088E+11 | 0.00 | 0.00 | 0.00 |
March | 0.332502E+12 | 0.583180E+11 | 0.146267E+13 | 0.165150E+12 | 0.230445E+12 | 0.276743E+11 | 0.00 | 0.290886E+12 | 0.858115E+11 | 0.124692E+12 | 0.00 | 0.00 | 0.00 |
April | 0.295948E+12 | 0.499533E+11 | 0.170311E+13 | 0.159524E+12 | 0.247486E+12 | 0.450132E+11 | 0.00 | 0.417367E+12 | 0.117215E+12 | 0.154448E+12 | 0.00 | 0.00 | 0.00 |
May | 0.318960E+12 | 0.461484E+11 | 0.820521E+12 | 0.165009E+12 | 0.267536E+12 | 0.564359E+11 | 0.00 | 0.228999E+12 | 0.103449E+12 | 0.480409E+11 | 0.00 | 0.00 | 0.00 |
June | 0.316856E+12 | 0.420916E+11 | 0.110677E+13 | 0.159787E+12 | 0.296557E+12 | 0.830096E+11 | 0.00 | 0.428571E+12 | 0.130519E+12 | 0.564159E+11 | 0.00 | 0.00 | 0.00 |
July | 0.296991E+12 | 0.445928E+11 | 0.143888E+13 | 0.164745E+12 | 0.313835E+12 | 0.970089E+11 | 0.00 | 0.606861E+12 | 0.156025E+12 | 0.603678E+11 | 0.00 | 0.00 | 0.00 |
August | 0.330910E+12 | 0.491244E+11 | 0.177780E+13 | 0.165149E+12 | 0.320643E+12 | 0.102522E+12 | 0.00 | 0.678387E+12 | 0.150197E+12 | 0.137177E+12 | 0.00 | 0.00 | 0.00 |
September | 0.296634E+12 | 0.537025E+11 | 0.784732E+12 | 0.159522E+12 | 0.260287E+12 | 0.711363E+11 | 0.00 | 0.276921E+12 | 0.124551E+12 | 0.412427E+11 | 0.00 | 0.00 | 0.00 |
October | 0.309433E+12 | 0.620672E+11 | 0.112899E+13 | 0.164870E+12 | 0.241551E+12 | 0.483585E+11 | 0.00 | 0.278527E+12 | 0.972448E+11 | 0.835580E+11 | 0.00 | 0.00 | 0.00 |
November | 0.307920E+12 | 0.657324E+11 | 0.140306E+13 | 0.159633E+12 | 0.214724E+12 | 0.202312E+11 | 0.00 | 0.263311E+12 | 0.732235E+11 | 0.126434E+12 | 0.00 | 0.00 | 0.00 |
December | 0.303171E+12 | 0.710652E+11 | 0.175516E+13 | 0.164747E+12 | 0.211890E+12 | 0.231185E+11 | 0.00 | 0.328930E+12 | 0.654077E+11 | 0.177284E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370208E+13 | 0.670688E+12 | 0.152134E+14 | 0.194193E+13 | 0.300825E+13 | 0.617322E+12 | 0.00 | 0.409114E+13 | 0.115748E+13 | 0.114971E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.281359E+12 | 0.420916E+11 | 0.784732E+12 | 0.148925E+12 | 0.193711E+12 | 0.202312E+11 | 0.00 | 0.114010E+12 | 0.180283E+11 | 0.412427E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.332502E+12 | 0.710652E+11 | 0.177780E+13 | 0.165150E+12 | 0.320643E+12 | 0.102522E+12 | 0.00 | 0.678387E+12 | 0.156025E+12 | 0.177284E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.222435E+12 | 0.00 | 0.637776E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.127506E+12 | 0.00 | 0.582040E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.383663E+11 | 0.00 | 0.661660E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.456532E+10 | 0.00 | 0.586168E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.762506E+09 | 0.00 | 0.588797E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 45100080.70 | 0.00 | 0.549482E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.516982E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.546209E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 4947179.93 | 0.00 | 0.517305E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.181562E+11 | 0.00 | 0.559030E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.576631E+11 | 0.00 | 0.576564E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.210197E+12 | 0.00 | 0.607793E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.679701E+12 | 0.00 | 0.692980E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.516982E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.222435E+12 | 0.00 | 0.661660E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 342201.69 | 04-JAN-16:00 | 54335.80 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 118936.89 | 03-JAN-08:20 | 145303.17 | 26-JAN-16:00 | 37287.52 | 17-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 336733.49 | 16-FEB-08:09 | 54335.80 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 118945.75 | 16-FEB-08:20 | 182952.57 | 15-FEB-16:00 | 52961.65 | 13-FEB-15:09 | 0.00 | 01-FEB-00:10 |
March | 328221.04 | 20-MAR-07:10 | 54335.80 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 118938.65 | 20-MAR-07:19 | 182966.83 | 30-MAR-15:50 | 52774.27 | 16-MAR-13:20 | 0.00 | 01-MAR-00:10 |
April | 316816.17 | 03-APR-07:10 | 54335.80 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 118929.14 | 03-APR-07:19 | 247165.43 | 28-APR-14:00 | 53798.83 | 27-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 316816.17 | 01-MAY-07:10 | 54335.80 | 01-MAY-05:10 | 439129.89 | 01-MAY-07:10 | 118929.14 | 01-MAY-07:19 | 253702.14 | 19-MAY-15:20 | 60720.46 | 23-MAY-10:30 | 0.00 | 01-MAY-00:10 |
June | 318388.93 | 08-JUN-07:10 | 54335.80 | 01-JUN-19:10 | 557421.28 | 01-JUN-07:10 | 118930.45 | 08-JUN-07:19 | 292435.11 | 28-JUN-14:50 | 70368.37 | 27-JUN-15:50 | 0.00 | 01-JUN-00:10 |
July | 316816.17 | 03-JUL-07:10 | 54335.80 | 01-JUL-19:19 | 675712.68 | 03-JUL-07:10 | 118929.14 | 03-JUL-07:19 | 297657.58 | 31-JUL-15:09 | 69751.23 | 21-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 316816.17 | 01-AUG-07:10 | 54335.80 | 01-AUG-05:10 | 794004.08 | 01-AUG-07:10 | 118929.14 | 01-AUG-07:19 | 306490.58 | 07-AUG-15:39 | 62595.98 | 02-AUG-07:49 | 0.00 | 01-AUG-00:10 |
September | 335755.96 | 08-SEP-07:10 | 54335.80 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 118944.93 | 08-SEP-07:19 | 250183.90 | 06-SEP-15:50 | 69237.35 | 21-SEP-14:39 | 0.00 | 01-SEP-00:10 |
October | 335049.62 | 25-OCT-07:10 | 54335.80 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 118944.34 | 25-OCT-07:19 | 210872.37 | 02-OCT-08:00 | 65953.67 | 04-OCT-14:20 | 0.00 | 01-OCT-00:10 |
November | 352853.36 | 13-NOV-16:00 | 54335.80 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 118950.32 | 02-NOV-07:19 | 181737.17 | 03-NOV-15:00 | 35853.83 | 28-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 352853.36 | 01-DEC-16:00 | 54335.80 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 118941.35 | 08-DEC-08:20 | 147799.17 | 29-DEC-16:40 | 36205.11 | 14-DEC-05:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 316816.17 | 54335.80 | 439129.89 | 118929.14 | 145303.17 | 35853.83 | 0.00 | |||||||
Maximum of Months | 352853.36 | 54335.80 | 794004.08 | 118950.32 | 306490.58 | 70368.37 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 92553.96 | 05-JAN-14:00 | 49248.27 | 05-JAN-13:00 | 24565.33 | 27-JAN-18:10 | 0.00 | 0.00 | 0.00 |
February | 172677.50 | 14-FEB-16:00 | 49812.38 | 14-FEB-15:00 | 38997.29 | 24-FEB-19:00 | 0.00 | 0.00 | 0.00 |
March | 211561.09 | 07-MAR-15:39 | 49986.01 | 08-MAR-15:39 | 60025.43 | 31-MAR-23:30 | 0.00 | 0.00 | 0.00 |
April | 356196.74 | 13-APR-15:20 | 50475.70 | 28-APR-13:39 | 73649.13 | 05-APR-19:10 | 0.00 | 0.00 | 0.00 |
May | 263204.29 | 19-MAY-15:20 | 53238.28 | 22-MAY-13:09 | 27449.64 | 31-MAY-23:00 | 0.00 | 0.00 | 0.00 |
June | 370664.96 | 28-JUN-14:50 | 82925.55 | 06-JUN-12:39 | 36404.76 | 19-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 424636.61 | 21-JUL-14:50 | 82925.55 | 03-JUL-08:00 | 48386.94 | 31-JUL-23:49 | 0.00 | 0.00 | 0.00 |
August | 436579.83 | 01-AUG-15:09 | 82925.55 | 01-AUG-09:30 | 71263.69 | 25-AUG-20:19 | 0.00 | 0.00 | 0.00 |
September | 322168.49 | 05-SEP-13:09 | 82925.55 | 01-SEP-10:20 | 29526.87 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 |
October | 298656.88 | 02-OCT-11:20 | 82925.55 | 02-OCT-13:00 | 46266.90 | 31-OCT-23:00 | 0.00 | 0.00 | 0.00 |
November | 178969.54 | 09-NOV-13:00 | 49498.49 | 02-NOV-15:09 | 53706.35 | 18-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 131223.94 | 24-DEC-15:30 | 49248.27 | 01-DEC-12:30 | 75188.39 | 23-DEC-07:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 92553.96 | 49248.27 | 24565.33 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 436579.83 | 82925.55 | 75188.39 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1158140.62 | 05-JAN-16:10 | 320768.91 | 439129.89 | 0.00 | 84885.75 | 134911.38 | 34695.92 | 0.00 | 77099.34 | 46088.83 |
February | 1416293.61 | 14-FEB-16:00 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 156647.51 | 52472.97 | 0.00 | 172677.50 | 49387.52 |
March | 1575657.09 | 08-MAR-16:19 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 179107.39 | 35417.05 | 0.00 | 205586.48 | 49517.69 |
April | 1944812.77 | 13-APR-15:20 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 245294.41 | 53261.07 | 0.00 | 356196.74 | 50012.72 |
May | 1472244.39 | 19-MAY-15:20 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 253702.14 | 53392.89 | 0.00 | 263204.29 | 51651.08 |
June | 1725559.85 | 26-JUN-15:20 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 289772.97 | 61650.70 | 0.00 | 359281.54 | 52077.21 |
July | 1932405.58 | 31-JUL-15:09 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 297657.58 | 55890.69 | 0.00 | 413420.79 | 82925.55 |
August | 2101855.59 | 07-AUG-15:00 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 294086.68 | 60084.54 | 0.00 | 433145.53 | 82925.55 |
September | 1489733.15 | 06-SEP-15:50 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 250183.90 | 54445.58 | 0.00 | 252796.16 | 82925.55 |
October | 1593821.17 | 02-OCT-15:00 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 209295.58 | 60205.59 | 0.00 | 296921.02 | 50400.57 |
November | 1529488.60 | 02-NOV-15:00 | 319665.99 | 675712.68 | 0.00 | 84885.75 | 157815.13 | 34906.40 | 0.00 | 167474.66 | 49447.91 |
December | 1675926.83 | 19-DEC-16:00 | 352853.36 | 794004.08 | 54335.80 | 84914.22 | 125737.91 | 34640.00 | 0.00 | 127728.79 | 34784.77 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1158140.62 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 125737.91 | 34640.00 | 0.00 | 77099.34 | 34784.77 | |
Maximum of Months | 2101855.59 | 352853.36 | 794004.08 | 54335.80 | 84914.22 | 297657.58 | 61650.70 | 0.00 | 433145.53 | 82925.55 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 745289.93 | 17-JAN-07:10 | 0.00 | 81591.23 | 30-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 753815.78 | 06-FEB-07:10 | 0.00 | 81613.24 | 02-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 380191.92 | 04-MAR-07:10 | 0.00 | 81288.45 | 02-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 221744.71 | 08-APR-05:10 | 0.00 | 79636.44 | 04-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 84370.38 | 05-MAY-05:10 | 0.00 | 77457.64 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 9357.06 | 09-JUN-05:10 | 0.00 | 74045.43 | 05-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 71450.54 | 05-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 70735.60 | 30-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 1426.02 | 09-SEP-05:49 | 0.00 | 72286.69 | 22-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 414032.41 | 26-OCT-05:10 | 0.00 | 75972.16 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 543944.10 | 27-NOV-07:10 | 0.00 | 78665.56 | 29-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 666010.57 | 15-DEC-07:10 | 0.00 | 80651.10 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 70735.60 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 753815.78 | 0.00 | 81613.24 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.70 | 0.33 | 26.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.27 | 0.17 | 26.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 26.01 | 0.00 | 26.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 25.99 | 0.00 | 25.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.35 | 0.00 | 26.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 25.97 | 0.00 | 25.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 25.82 | 0.00 | 25.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.90 | 0.00 | 25.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.09 | 0.33 | 26.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 26.35 | 0.50 | 26.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.46 | 0.33 | 26.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.57 | 1.33 | 26.66 |
Annual Sum or Average | 0.00 | 0.00 | 94.83 | 26.21 | 3.00 | 26.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.82 | 0.00 | 25.82 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.70 | 1.33 | 26.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.60 | 0.00 | 25.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.62 | 0.00 | 25.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.60 | 0.00 | 25.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.66 | 0.00 | 25.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.63 | 0.00 | 25.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.76 | 0.00 | 25.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.77 | 0.00 | 25.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.62 | 0.00 | 25.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.19 | 0.00 | 26.19 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.21 | 0.00 | 26.21 |
Annual Sum or Average | 0.00 | 0.00 | 7.83 | 25.73 | 0.00 | 25.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.21 | 0.00 | 26.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
February | 0.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
December | 0.50 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
Annual Sum or Average | 1.17 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.00 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.25 | 1.00 | 27.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.97 | 1.67 | 27.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.83 | 27.09 | 2.67 | 27.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.36 | 1.67 | 27.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.70 | 1.50 | 27.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.86 | 3.33 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.24 | 5.83 | 28.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.37 | 4.50 | 28.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.26 | 10.17 | 28.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.23 | 5.50 | 28.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.17 | 2.83 | 28.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.83 | 2.83 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 36.67 | 28.16 | 36.67 | 28.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.37 | 10.17 | 28.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.06 | 6.00 | 28.06 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 26.40 | 7.00 | 26.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.91 | 3.17 | 27.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.61 | 1.50 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.62 | 4.83 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.74 | 6.50 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.71 | 12.67 | 26.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 25.92 | 25.83 | 25.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 26.32 | 15.17 | 26.32 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.59 | 6.67 | 27.59 |
Annual Sum or Average | 0.00 | 0.00 | 90.83 | 26.74 | 89.33 | 26.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 28.06 | 25.83 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.44 | 0.67 | 27.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.30 | 2.67 | 28.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.93 | 4.00 | 28.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.42 | 2.67 | 28.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.25 | 4.33 | 28.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 27.54 | 6.17 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 27.63 | 10.33 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.14 | 3.67 | 28.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.56 | 3.00 | 28.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.77 | 1.67 | 27.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.62 | 1.83 | 27.62 |
Annual Sum or Average | 0.00 | 0.00 | 103.17 | 27.82 | 41.00 | 28.01 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 28.56 | 10.33 | 28.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 19.04 | 0.17 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
February | 1.50 | 18.87 | 0.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.00 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.54 | 1.00 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
December | 1.83 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Annual Sum or Average | 6.33 | 19.07 | 0.33 | 19.14 | 1.67 | 20.81 | 1.00 | 21.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.28 | 0.17 | 19.28 | 1.50 | 27.54 | 1.00 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
February | 1.17 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
March | 0.17 | 19.36 | 0.00 | 19.36 | 0.33 | 24.81 | 0.33 | 25.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.41 | 1.33 | 28.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.29 | 5.83 | 28.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.37 | 5.83 | 28.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 28.35 | 14.00 | 28.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.30 | 8.50 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.13 | 3.33 | 28.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.94 | 1.33 | 27.94 |
November | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
December | 1.67 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Annual Sum or Average | 5.33 | 19.00 | 0.00 | 19.00 | 40.83 | 27.22 | 40.50 | 27.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.66 | 0.00 | 18.66 |
Maximum of Months | 2.17 | 19.36 | 0.00 | 19.36 | 14.33 | 28.41 | 14.00 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.75 | 0.00 | 18.75 | 24.00 | 25.59 | 24.00 | 25.66 |
February | 0.33 | 18.71 | 0.00 | 18.71 | 16.83 | 25.40 | 16.83 | 25.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.01 | 2.83 | 28.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.61 | 0.83 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.69 | 4.17 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.82 | 5.50 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 26.59 | 15.67 | 26.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 | 25.68 | 48.00 | 25.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 25.57 | 35.67 | 25.57 |
December | 0.50 | 19.39 | 0.00 | 19.39 | 14.17 | 25.79 | 14.17 | 25.90 |
Annual Sum or Average | 1.33 | 18.98 | 0.00 | 18.98 | 169.00 | 25.89 | 167.67 | 25.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.39 | 0.00 | 19.39 | 48.50 | 28.01 | 48.00 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
February | 0.67 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.77 | 0.50 | 27.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.12 | 2.33 | 28.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.31 | 2.17 | 28.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.93 | 2.67 | 28.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.60 | 4.67 | 28.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.54 | 3.00 | 28.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.15 | 2.83 | 28.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.99 | 2.17 | 28.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Annual Sum or Average | 1.83 | 18.83 | 0.00 | 18.83 | 32.83 | 27.94 | 20.33 | 28.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.33 | 0.00 | 19.33 | 7.83 | 28.93 | 4.67 | 28.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.83 | 17.16 | 3.33 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
February | 13.17 | 17.13 | 2.50 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
March | 2.33 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
April | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.57 | 0.67 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.66 | 3.00 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.48 | 1.50 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
November | 5.17 | 18.44 | 0.33 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
December | 15.33 | 17.43 | 2.50 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 |
Annual Sum or Average | 53.50 | 17.45 | 8.67 | 17.49 | 8.33 | 18.68 | 5.17 | 19.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.83 | 19.22 | 3.33 | 19.22 | 4.50 | 27.66 | 3.00 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.50 | 17.02 | 0.67 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
February | 9.00 | 17.13 | 0.67 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
March | 1.17 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
April | 0.17 | 19.28 | 0.00 | 19.28 | 1.00 | 27.10 | 1.00 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.19 | 5.33 | 28.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.30 | 7.00 | 28.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 28.43 | 16.00 | 28.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.34 | 9.83 | 28.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.12 | 3.50 | 28.12 |
October | 0.33 | 19.06 | 0.00 | 19.06 | 1.00 | 25.77 | 1.00 | 26.73 |
November | 3.33 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
December | 11.67 | 17.37 | 0.33 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
Annual Sum or Average | 37.17 | 17.38 | 1.67 | 17.30 | 46.17 | 23.29 | 43.67 | 25.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.97 | 0.00 | 16.97 |
Maximum of Months | 11.67 | 19.28 | 0.67 | 19.28 | 17.17 | 28.43 | 16.00 | 28.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 17.68 | 0.17 | 17.72 | 3.00 | 20.19 | 3.00 | 21.68 |
February | 5.33 | 17.99 | 0.00 | 17.99 | 3.67 | 21.38 | 3.67 | 22.81 |
March | 0.67 | 18.80 | 0.00 | 18.80 | 2.00 | 25.57 | 2.00 | 26.54 |
April | 0.17 | 19.41 | 0.00 | 19.41 | 0.67 | 25.88 | 0.67 | 26.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.41 | 1.00 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.87 | 5.83 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.99 | 6.17 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.72 | 13.50 | 26.72 |
October | 0.33 | 19.20 | 0.00 | 19.20 | 23.33 | 25.85 | 23.00 | 25.88 |
November | 1.50 | 18.55 | 0.00 | 18.55 | 6.00 | 24.98 | 6.00 | 25.69 |
December | 7.17 | 18.52 | 0.00 | 18.52 | 1.50 | 20.17 | 1.50 | 21.33 |
Annual Sum or Average | 24.00 | 18.12 | 0.17 | 18.13 | 69.33 | 24.56 | 66.33 | 25.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.83 | 19.41 | 0.17 | 19.41 | 23.33 | 27.99 | 23.00 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.00 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
February | 5.83 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
March | 0.67 | 18.91 | 0.00 | 18.91 | 0.50 | 22.59 | 0.33 | 23.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.20 | 2.00 | 28.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.39 | 2.00 | 28.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.74 | 3.50 | 28.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.67 | 5.00 | 28.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.64 | 3.33 | 28.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.22 | 3.33 | 28.24 |
October | 0.33 | 19.27 | 0.00 | 19.27 | 2.17 | 26.78 | 2.00 | 27.30 |
November | 1.67 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
December | 7.67 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
Annual Sum or Average | 25.17 | 18.03 | 0.00 | 18.03 | 35.33 | 24.15 | 21.50 | 25.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.46 | 0.00 | 17.46 |
Maximum of Months | 9.00 | 19.27 | 0.00 | 19.27 | 9.33 | 28.74 | 5.00 | 28.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.94 | 9.00 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 80.17 | 27.96 | 71.50 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 94.33 | 27.95 | 80.50 | 27.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 80.17 | 27.96 | 71.50 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.86 | 5.17 | 27.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 27.84 | 21.33 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 33.67 | 27.85 | 26.50 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 27.86 | 21.33 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.93 | 1.50 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 28.01 | 12.50 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.83 | 28.00 | 14.00 | 27.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 28.01 | 12.50 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 692.67 | 28.82 | 463.50 | 28.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.38 | 0.00 | 28.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 31.76 | 514.00 | 31.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 531.50 | 27.84 | 296.00 | 27.83 |
Annual Sum or Average | 0.00 | 0.00 | 1968.33 | 29.67 | 1273.50 | 29.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 31.76 | 514.00 | 31.84 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 197.83 | 24.00 | 75.17 | 24.65 | 0.00 | 24.65 |
February | 152.83 | 24.00 | 71.67 | 24.75 | 0.00 | 24.75 |
March | 142.83 | 24.00 | 70.17 | 24.76 | 0.00 | 24.76 |
April | 142.17 | 24.00 | 83.33 | 24.93 | 0.00 | 24.93 |
May | 92.83 | 24.00 | 152.67 | 24.92 | 0.67 | 24.91 |
June | 4.67 | 24.00 | 294.67 | 24.77 | 0.00 | 24.77 |
July | 123.33 | 24.44 | 475.00 | 24.61 | 123.33 | 24.58 |
August | 83.50 | 24.31 | 498.67 | 24.48 | 83.50 | 24.46 |
September | 16.00 | 24.82 | 381.33 | 24.73 | 16.00 | 24.73 |
October | 47.17 | 24.00 | 198.17 | 25.21 | 0.00 | 25.21 |
November | 58.50 | 24.00 | 107.00 | 25.65 | 0.00 | 25.65 |
December | 166.83 | 24.00 | 91.83 | 24.92 | 0.00 | 24.92 |
Annual Sum or Average | 1228.50 | 24.08 | 2499.67 | 24.78 | 223.50 | 24.76 |
Minimum of Months | 4.67 | 24.00 | 70.17 | 24.48 | 0.00 | 24.46 |
Maximum of Months | 197.83 | 24.82 | 498.67 | 25.65 | 123.33 | 25.65 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 269.83 | 23.93 | 11.00 | 24.00 | 0.00 | 24.00 |
February | 170.50 | 23.97 | 24.67 | 24.22 | 0.00 | 24.22 |
March | 131.83 | 24.00 | 45.50 | 24.52 | 0.00 | 24.52 |
April | 94.33 | 24.01 | 32.83 | 24.52 | 0.00 | 24.52 |
May | 88.83 | 24.00 | 134.00 | 24.45 | 1.17 | 24.45 |
June | 2.50 | 24.02 | 311.00 | 24.32 | 0.00 | 24.32 |
July | 143.33 | 24.37 | 479.00 | 24.28 | 143.33 | 24.30 |
August | 55.67 | 24.29 | 513.50 | 24.22 | 55.67 | 24.22 |
September | 18.50 | 24.35 | 388.17 | 24.41 | 18.50 | 24.41 |
October | 65.17 | 23.98 | 177.17 | 24.59 | 0.00 | 24.59 |
November | 102.00 | 24.00 | 62.17 | 24.69 | 0.00 | 24.69 |
December | 192.50 | 24.00 | 48.83 | 24.44 | 0.00 | 24.44 |
Annual Sum or Average | 1335.00 | 24.04 | 2227.83 | 24.35 | 218.67 | 24.35 |
Minimum of Months | 2.50 | 23.93 | 11.00 | 24.00 | 0.00 | 24.00 |
Maximum of Months | 269.83 | 24.37 | 513.50 | 24.69 | 143.33 | 24.69 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.00 | 23.48 | 0.00 | 23.48 | 0.00 | 23.48 |
February | 409.67 | 23.65 | 0.00 | 23.65 | 0.00 | 23.65 |
March | 367.83 | 23.83 | 1.17 | 23.83 | 0.00 | 23.83 |
April | 284.17 | 23.94 | 4.83 | 23.97 | 0.00 | 23.97 |
May | 152.33 | 23.95 | 90.17 | 24.16 | 1.17 | 24.16 |
June | 24.67 | 23.88 | 262.33 | 24.27 | 0.00 | 24.27 |
July | 151.33 | 24.18 | 467.17 | 24.23 | 151.33 | 24.22 |
August | 94.17 | 24.17 | 484.67 | 24.22 | 94.17 | 24.21 |
September | 21.33 | 24.29 | 339.33 | 24.33 | 19.17 | 24.33 |
October | 194.67 | 23.83 | 106.00 | 24.06 | 0.00 | 24.06 |
November | 383.17 | 23.77 | 2.00 | 23.77 | 0.00 | 23.77 |
December | 492.33 | 23.54 | 0.00 | 23.54 | 0.00 | 23.54 |
Annual Sum or Average | 3072.67 | 23.74 | 1757.67 | 23.95 | 265.83 | 23.96 |
Minimum of Months | 21.33 | 23.48 | 0.00 | 23.48 | 0.00 | 23.48 |
Maximum of Months | 497.00 | 24.29 | 484.67 | 24.33 | 151.33 | 24.33 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.99 | 129.17 | 21.62 | 129.17 | 21.38 |
February | 450.00 | 22.53 | 49.83 | 22.32 | 49.83 | 22.15 |
March | 473.33 | 23.26 | 9.33 | 23.21 | 9.33 | 23.17 |
April | 338.17 | 23.72 | 1.33 | 23.73 | 0.00 | 23.73 |
May | 166.67 | 23.74 | 86.33 | 23.97 | 1.33 | 23.97 |
June | 25.50 | 23.76 | 278.50 | 24.25 | 0.00 | 24.25 |
July | 137.83 | 24.25 | 476.50 | 24.29 | 137.83 | 24.29 |
August | 90.33 | 24.24 | 494.33 | 24.26 | 90.33 | 24.25 |
September | 40.33 | 23.97 | 325.67 | 24.28 | 22.50 | 24.28 |
October | 287.33 | 23.39 | 87.67 | 23.60 | 1.83 | 23.60 |
November | 460.33 | 22.82 | 37.17 | 22.66 | 37.17 | 22.53 |
December | 497.00 | 22.04 | 132.67 | 21.69 | 132.67 | 21.46 |
Annual Sum or Average | 3468.83 | 22.90 | 2108.50 | 23.18 | 612.00 | 23.06 |
Minimum of Months | 25.50 | 21.99 | 1.33 | 21.62 | 0.00 | 21.38 |
Maximum of Months | 502.00 | 24.25 | 494.33 | 24.29 | 137.83 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.04 | 22.83 | 21.99 | 22.83 | 21.95 |
February | 451.67 | 22.53 | 12.50 | 22.48 | 12.50 | 22.44 |
March | 464.83 | 23.25 | 0.00 | 23.25 | 0.00 | 23.25 |
April | 285.50 | 23.71 | 3.00 | 23.72 | 0.00 | 23.72 |
May | 149.33 | 23.66 | 110.17 | 24.03 | 0.83 | 24.03 |
June | 6.33 | 23.56 | 355.00 | 24.33 | 0.17 | 24.34 |
July | 103.83 | 24.87 | 489.67 | 24.46 | 103.83 | 24.52 |
August | 50.83 | 24.54 | 509.83 | 24.27 | 50.83 | 24.29 |
September | 48.83 | 23.63 | 334.67 | 24.25 | 12.50 | 24.24 |
October | 295.00 | 23.28 | 93.00 | 23.51 | 0.00 | 23.51 |
November | 463.67 | 22.96 | 0.00 | 22.96 | 0.00 | 22.96 |
December | 497.00 | 22.35 | 11.33 | 22.32 | 11.33 | 22.29 |
Annual Sum or Average | 3318.83 | 22.93 | 1942.00 | 23.42 | 214.83 | 23.44 |
Minimum of Months | 6.33 | 22.04 | 0.00 | 21.99 | 0.00 | 21.95 |
Maximum of Months | 502.00 | 24.87 | 509.83 | 24.46 | 103.83 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 465.17 | 21.92 | 31.67 | 21.93 | 24.17 | 21.88 |
February | 402.50 | 22.25 | 18.83 | 22.31 | 7.67 | 22.28 |
March | 358.83 | 22.72 | 40.67 | 22.94 | 1.00 | 22.95 |
April | 205.50 | 23.25 | 100.17 | 23.72 | 4.83 | 23.78 |
May | 143.17 | 23.67 | 208.33 | 24.24 | 19.67 | 24.38 |
June | 43.17 | 24.61 | 374.50 | 24.38 | 16.67 | 24.49 |
July | 116.67 | 25.25 | 473.00 | 24.55 | 113.50 | 24.67 |
August | 76.50 | 24.68 | 461.50 | 24.25 | 63.00 | 24.34 |
September | 86.17 | 23.67 | 360.50 | 24.23 | 24.83 | 24.30 |
October | 257.00 | 22.87 | 149.50 | 23.50 | 5.67 | 23.55 |
November | 413.50 | 22.46 | 18.33 | 22.58 | 1.00 | 22.57 |
December | 469.67 | 21.97 | 31.17 | 21.93 | 28.67 | 21.88 |
Annual Sum or Average | 3037.83 | 22.68 | 2268.17 | 23.38 | 310.67 | 23.45 |
Minimum of Months | 43.17 | 21.92 | 18.33 | 21.93 | 1.00 | 21.88 |
Maximum of Months | 469.67 | 25.25 | 473.00 | 24.55 | 113.50 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 321.00 | 22.55 | 124.50 | 23.04 | 32.50 | 23.02 |
February | 250.67 | 22.80 | 102.17 | 23.30 | 14.67 | 23.31 |
March | 266.67 | 23.13 | 74.67 | 23.49 | 3.33 | 23.53 |
April | 183.50 | 23.46 | 64.50 | 23.82 | 0.83 | 23.83 |
May | 158.17 | 23.38 | 131.00 | 23.92 | 0.83 | 23.92 |
June | 40.83 | 23.41 | 311.00 | 24.20 | 0.67 | 24.21 |
July | 114.17 | 24.99 | 485.00 | 24.47 | 114.17 | 24.55 |
August | 65.83 | 25.23 | 509.17 | 24.38 | 65.83 | 24.47 |
September | 66.33 | 25.15 | 396.33 | 24.64 | 43.67 | 24.77 |
October | 141.67 | 23.79 | 258.83 | 24.45 | 24.83 | 24.61 |
November | 237.00 | 23.35 | 142.83 | 23.96 | 15.17 | 24.07 |
December | 289.33 | 22.84 | 124.00 | 23.32 | 23.17 | 23.34 |
Annual Sum or Average | 2135.17 | 23.31 | 2724.00 | 23.97 | 339.67 | 24.04 |
Minimum of Months | 40.83 | 22.55 | 64.50 | 23.04 | 0.67 | 23.02 |
Maximum of Months | 321.00 | 25.23 | 509.17 | 24.64 | 114.17 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 430.67 | 22.10 | 11.17 | 22.18 | 0.00 | 22.18 |
February | 320.83 | 22.68 | 53.33 | 22.96 | 0.17 | 22.97 |
March | 200.17 | 23.23 | 109.67 | 23.85 | 8.00 | 23.94 |
April | 48.17 | 24.88 | 228.33 | 24.95 | 19.00 | 25.08 |
May | 106.83 | 23.51 | 252.17 | 24.29 | 12.33 | 24.38 |
June | 26.00 | 26.06 | 435.33 | 24.52 | 19.50 | 24.62 |
July | 127.17 | 25.19 | 497.00 | 24.60 | 127.17 | 24.70 |
August | 112.67 | 25.34 | 514.00 | 24.60 | 112.67 | 24.72 |
September | 54.17 | 24.50 | 396.00 | 24.49 | 30.00 | 24.56 |
October | 160.67 | 23.28 | 231.00 | 24.09 | 13.17 | 24.19 |
November | 263.50 | 23.11 | 77.00 | 23.51 | 1.33 | 23.52 |
December | 317.67 | 23.08 | 58.50 | 23.40 | 0.67 | 23.41 |
Annual Sum or Average | 2168.50 | 23.23 | 2863.50 | 24.00 | 344.00 | 24.10 |
Minimum of Months | 26.00 | 22.10 | 11.17 | 22.18 | 0.00 | 22.18 |
Maximum of Months | 430.67 | 26.06 | 514.00 | 24.95 | 127.17 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.72 | 311.17 | 20.57 | 311.17 | 20.51 |
February | 454.00 | 21.11 | 186.67 | 20.92 | 186.67 | 20.82 |
March | 514.00 | 22.09 | 64.50 | 21.93 | 64.50 | 21.81 |
April | 422.83 | 23.06 | 5.00 | 23.04 | 5.00 | 23.02 |
May | 238.83 | 23.39 | 65.50 | 23.60 | 1.00 | 23.60 |
June | 33.83 | 23.43 | 302.33 | 24.27 | 0.00 | 24.27 |
July | 98.33 | 24.50 | 488.33 | 24.40 | 98.33 | 24.42 |
August | 68.00 | 24.12 | 484.33 | 24.24 | 64.33 | 24.23 |
September | 99.33 | 23.37 | 255.00 | 23.97 | 13.50 | 23.97 |
October | 389.83 | 22.39 | 76.33 | 22.51 | 23.33 | 22.44 |
November | 489.00 | 21.44 | 138.17 | 21.23 | 138.17 | 21.09 |
December | 497.00 | 20.66 | 355.00 | 20.56 | 355.00 | 20.52 |
Annual Sum or Average | 3807.00 | 21.89 | 2732.33 | 22.26 | 1261.00 | 22.05 |
Minimum of Months | 33.83 | 20.66 | 5.00 | 20.56 | 0.00 | 20.51 |
Maximum of Months | 514.00 | 24.50 | 488.33 | 24.40 | 355.00 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 21.07 | 197.17 | 20.90 | 197.17 | 20.81 |
February | 369.83 | 21.33 | 97.83 | 21.17 | 96.00 | 21.04 |
March | 372.00 | 22.06 | 37.17 | 22.15 | 18.83 | 22.09 |
April | 213.50 | 22.89 | 81.17 | 23.48 | 5.17 | 23.52 |
May | 176.17 | 23.38 | 154.00 | 24.06 | 20.67 | 24.23 |
June | 62.17 | 24.21 | 294.83 | 24.49 | 19.67 | 24.62 |
July | 108.67 | 25.61 | 399.00 | 24.82 | 107.33 | 24.96 |
August | 83.33 | 24.97 | 385.33 | 24.53 | 68.83 | 24.64 |
September | 117.17 | 23.33 | 253.83 | 24.08 | 24.33 | 24.17 |
October | 279.67 | 22.33 | 108.50 | 22.86 | 16.00 | 22.84 |
November | 388.33 | 21.57 | 56.67 | 21.51 | 49.50 | 21.42 |
December | 421.17 | 20.95 | 218.50 | 20.77 | 218.50 | 20.69 |
Annual Sum or Average | 3019.00 | 22.07 | 2284.00 | 22.70 | 842.00 | 22.61 |
Minimum of Months | 62.17 | 20.95 | 37.17 | 20.77 | 5.17 | 20.69 |
Maximum of Months | 427.00 | 25.61 | 399.00 | 24.82 | 218.50 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 337.50 | 22.20 | 185.00 | 22.58 | 96.00 | 22.46 |
February | 269.83 | 22.32 | 126.67 | 22.81 | 40.50 | 22.73 |
March | 319.33 | 22.65 | 74.17 | 22.98 | 9.83 | 22.99 |
April | 250.83 | 23.07 | 48.33 | 23.40 | 0.33 | 23.40 |
May | 215.17 | 23.20 | 99.50 | 23.63 | 1.00 | 23.63 |
June | 75.33 | 23.20 | 274.33 | 24.09 | 0.50 | 24.10 |
July | 107.83 | 24.78 | 475.33 | 24.46 | 107.83 | 24.51 |
August | 74.67 | 24.93 | 489.67 | 24.42 | 71.33 | 24.49 |
September | 88.67 | 24.76 | 371.50 | 24.59 | 49.83 | 24.73 |
October | 183.00 | 23.55 | 248.50 | 24.31 | 36.83 | 24.48 |
November | 270.50 | 22.88 | 147.67 | 23.55 | 30.67 | 23.63 |
December | 311.67 | 22.20 | 188.17 | 22.53 | 92.67 | 22.37 |
Annual Sum or Average | 2504.33 | 22.93 | 2728.83 | 23.64 | 537.33 | 23.64 |
Minimum of Months | 74.67 | 22.20 | 48.33 | 22.53 | 0.33 | 22.37 |
Maximum of Months | 337.50 | 24.93 | 489.67 | 24.59 | 107.83 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.50 | 21.16 | 177.17 | 20.98 | 177.17 | 20.87 |
February | 407.17 | 21.42 | 90.33 | 21.31 | 86.00 | 21.21 |
March | 435.67 | 21.93 | 47.00 | 22.08 | 15.50 | 22.04 |
April | 309.33 | 22.75 | 78.17 | 23.16 | 7.00 | 23.23 |
May | 242.17 | 22.88 | 148.17 | 23.53 | 8.50 | 23.60 |
June | 100.50 | 23.40 | 333.33 | 24.19 | 15.17 | 24.29 |
July | 112.17 | 24.45 | 477.67 | 24.32 | 112.17 | 24.34 |
August | 74.17 | 24.23 | 475.33 | 24.25 | 66.17 | 24.27 |
September | 136.67 | 23.19 | 283.50 | 23.99 | 26.83 | 24.06 |
October | 338.50 | 22.29 | 105.67 | 22.77 | 10.67 | 22.81 |
November | 441.83 | 21.59 | 56.33 | 21.51 | 49.67 | 21.42 |
December | 483.17 | 21.19 | 193.33 | 21.01 | 193.33 | 20.92 |
Annual Sum or Average | 3567.83 | 22.01 | 2466.00 | 22.64 | 768.17 | 22.56 |
Minimum of Months | 74.17 | 21.16 | 47.00 | 20.98 | 7.00 | 20.87 |
Maximum of Months | 486.50 | 24.45 | 477.67 | 24.32 | 193.33 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 428.83 | 20.06 | 428.83 | 20.03 |
February | 454.00 | 20.51 | 309.50 | 20.35 | 309.50 | 20.29 |
March | 514.00 | 21.39 | 180.83 | 21.14 | 180.83 | 21.00 |
April | 425.67 | 22.51 | 50.50 | 22.31 | 50.50 | 22.15 |
May | 276.00 | 22.96 | 65.67 | 23.14 | 10.50 | 23.08 |
June | 64.50 | 23.15 | 305.50 | 24.14 | 1.67 | 24.15 |
July | 107.67 | 24.68 | 484.00 | 24.44 | 107.67 | 24.47 |
August | 76.83 | 24.07 | 467.83 | 24.22 | 64.67 | 24.22 |
September | 163.50 | 23.09 | 224.00 | 23.72 | 16.00 | 23.72 |
October | 424.67 | 21.87 | 132.00 | 21.84 | 90.00 | 21.67 |
November | 489.00 | 20.68 | 290.17 | 20.47 | 290.17 | 20.37 |
December | 497.00 | 20.10 | 471.67 | 20.07 | 471.67 | 20.06 |
Annual Sum or Average | 3994.83 | 21.40 | 3410.50 | 21.71 | 2022.00 | 21.46 |
Minimum of Months | 64.50 | 20.10 | 50.50 | 20.06 | 1.67 | 20.03 |
Maximum of Months | 514.00 | 24.68 | 484.00 | 24.44 | 471.67 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.52 | 326.83 | 20.36 | 326.83 | 20.28 |
February | 450.50 | 20.96 | 190.00 | 20.71 | 190.00 | 20.57 |
March | 446.67 | 21.85 | 88.00 | 21.72 | 79.50 | 21.57 |
April | 230.83 | 22.68 | 96.83 | 23.16 | 16.17 | 23.10 |
May | 188.00 | 23.20 | 194.17 | 23.92 | 23.17 | 24.06 |
June | 67.00 | 24.23 | 379.33 | 24.41 | 24.17 | 24.55 |
July | 129.50 | 25.47 | 476.33 | 24.73 | 126.83 | 24.87 |
August | 99.50 | 24.89 | 471.17 | 24.46 | 81.83 | 24.57 |
September | 131.83 | 23.23 | 326.00 | 24.00 | 30.00 | 24.08 |
October | 332.67 | 22.19 | 147.67 | 22.58 | 42.67 | 22.47 |
November | 484.50 | 21.22 | 168.17 | 20.99 | 165.67 | 20.84 |
December | 497.00 | 20.38 | 337.00 | 20.23 | 337.00 | 20.16 |
Annual Sum or Average | 3560.00 | 21.73 | 3201.50 | 22.29 | 1443.83 | 22.11 |
Minimum of Months | 67.00 | 20.38 | 88.00 | 20.23 | 16.17 | 20.16 |
Maximum of Months | 502.00 | 25.47 | 476.33 | 24.73 | 337.00 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 361.83 | 21.32 | 229.67 | 21.42 | 162.33 | 21.16 |
February | 300.00 | 21.58 | 172.00 | 21.71 | 110.33 | 21.46 |
March | 357.00 | 22.07 | 125.00 | 22.15 | 74.33 | 21.97 |
April | 272.83 | 22.57 | 75.50 | 22.74 | 28.17 | 22.60 |
May | 250.83 | 22.82 | 103.67 | 23.24 | 9.83 | 23.18 |
June | 98.33 | 22.97 | 276.17 | 23.98 | 3.33 | 24.00 |
July | 120.17 | 24.78 | 469.00 | 24.46 | 118.00 | 24.52 |
August | 89.00 | 24.64 | 473.83 | 24.38 | 75.33 | 24.45 |
September | 120.50 | 24.12 | 349.50 | 24.40 | 49.50 | 24.55 |
October | 215.83 | 22.89 | 249.50 | 23.67 | 54.17 | 23.68 |
November | 303.50 | 22.01 | 165.33 | 22.39 | 67.83 | 22.17 |
December | 341.00 | 21.29 | 211.00 | 21.32 | 149.67 | 21.04 |
Annual Sum or Average | 2830.83 | 22.31 | 2900.17 | 22.96 | 902.83 | 22.81 |
Minimum of Months | 89.00 | 21.29 | 75.50 | 21.32 | 3.33 | 21.04 |
Maximum of Months | 361.83 | 24.78 | 473.83 | 24.46 | 162.33 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.83 | 20.69 | 305.17 | 20.47 | 305.17 | 20.37 |
February | 418.33 | 21.03 | 182.50 | 20.81 | 179.50 | 20.68 |
March | 445.50 | 21.52 | 124.17 | 21.54 | 95.50 | 21.41 |
April | 323.50 | 22.35 | 98.50 | 22.72 | 25.67 | 22.70 |
May | 272.17 | 22.58 | 145.83 | 23.23 | 13.33 | 23.28 |
June | 117.00 | 23.13 | 324.67 | 24.09 | 16.67 | 24.20 |
July | 117.00 | 24.37 | 463.17 | 24.31 | 114.33 | 24.32 |
August | 91.00 | 23.94 | 457.00 | 24.19 | 67.50 | 24.21 |
September | 171.50 | 22.93 | 266.50 | 23.78 | 28.83 | 23.85 |
October | 357.33 | 21.95 | 130.67 | 22.30 | 48.00 | 22.23 |
November | 456.33 | 21.15 | 151.33 | 20.95 | 146.50 | 20.80 |
December | 493.67 | 20.73 | 317.83 | 20.51 | 317.83 | 20.42 |
Annual Sum or Average | 3757.17 | 21.66 | 2967.33 | 22.17 | 1358.83 | 21.99 |
Minimum of Months | 91.00 | 20.69 | 98.50 | 20.47 | 13.33 | 20.37 |
Maximum of Months | 493.83 | 24.37 | 463.17 | 24.31 | 317.83 | 24.32 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 9.67 | 27.00 | 454.00 | 27.00 | 9.67 | 27.00 |
March | 19.50 | 27.00 | 514.00 | 27.00 | 19.50 | 27.00 |
April | 69.33 | 27.18 | 485.00 | 27.05 | 69.33 | 27.06 |
May | 2.83 | 27.00 | 508.00 | 27.00 | 2.83 | 27.00 |
June | 48.50 | 27.00 | 496.00 | 27.00 | 48.50 | 27.00 |
July | 188.50 | 27.00 | 497.00 | 27.00 | 188.50 | 27.00 |
August | 425.50 | 27.20 | 514.00 | 27.18 | 425.50 | 27.18 |
September | 22.83 | 27.00 | 485.00 | 27.00 | 22.83 | 27.00 |
October | 37.67 | 27.00 | 502.00 | 27.00 | 37.67 | 27.00 |
November | 23.67 | 27.00 | 489.00 | 27.00 | 23.67 | 27.00 |
December | 25.33 | 27.00 | 497.00 | 27.00 | 25.33 | 27.00 |
Annual Sum or Average | 873.33 | 27.11 | 5943.00 | 27.03 | 873.33 | 27.04 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 425.50 | 27.20 | 514.00 | 27.18 | 425.50 | 27.18 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 461.00 | 27.00 | 0.00 | 27.00 |
February | 0.67 | 27.00 | 439.83 | 27.00 | 0.67 | 27.00 |
March | 2.33 | 27.00 | 514.00 | 27.00 | 2.33 | 27.00 |
April | 11.67 | 27.46 | 485.00 | 27.02 | 11.67 | 27.03 |
May | 0.67 | 27.00 | 508.00 | 27.00 | 0.67 | 27.00 |
June | 9.67 | 27.00 | 496.00 | 27.00 | 9.67 | 27.00 |
July | 38.33 | 27.00 | 497.00 | 27.00 | 38.33 | 27.00 |
August | 87.33 | 27.38 | 514.00 | 27.11 | 87.33 | 27.15 |
September | 9.17 | 27.00 | 485.00 | 27.00 | 9.17 | 27.00 |
October | 11.33 | 27.00 | 502.00 | 27.00 | 11.33 | 27.00 |
November | 1.33 | 27.00 | 489.00 | 27.00 | 1.33 | 27.00 |
December | 0.00 | 0.00 | 461.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 172.50 | 27.22 | 5851.83 | 27.01 | 172.50 | 27.02 |
Minimum of Months | 0.00 | 0.00 | 439.83 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 87.33 | 27.46 | 514.00 | 27.11 | 87.33 | 27.15 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 74.50 | 25.47 | 295.67 | 26.69 | 0.00 | 26.69 |
February | 11.50 | 27.00 | 345.83 | 27.00 | 0.67 | 27.00 |
March | 3.67 | 27.00 | 479.67 | 27.00 | 3.67 | 27.00 |
April | 12.67 | 27.29 | 484.33 | 27.02 | 12.67 | 27.02 |
May | 1.83 | 27.00 | 503.50 | 27.00 | 1.83 | 27.00 |
June | 33.67 | 27.00 | 496.00 | 27.00 | 33.67 | 27.00 |
July | 100.17 | 27.00 | 497.00 | 27.00 | 100.17 | 27.00 |
August | 124.83 | 27.22 | 514.00 | 27.09 | 124.83 | 27.11 |
September | 17.67 | 27.00 | 485.00 | 27.00 | 17.67 | 27.00 |
October | 14.50 | 27.00 | 490.33 | 27.00 | 14.50 | 27.00 |
November | 1.33 | 27.00 | 432.83 | 27.00 | 1.33 | 27.00 |
December | 20.17 | 27.00 | 341.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 416.50 | 26.80 | 5365.17 | 26.99 | 311.00 | 27.00 |
Minimum of Months | 1.33 | 25.47 | 295.67 | 26.69 | 0.00 | 26.69 |
Maximum of Months | 124.83 | 27.29 | 514.00 | 27.09 | 124.83 | 27.11 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.02 | 454.00 | 27.02 | 454.00 | 27.02 |
March | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
April | 485.00 | 28.86 | 485.00 | 28.86 | 485.00 | 28.86 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.01 | 496.00 | 27.01 | 496.00 | 27.01 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 31.95 | 514.00 | 31.95 | 514.00 | 31.95 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.01 | 502.00 | 27.01 | 502.00 | 27.01 |
November | 489.00 | 27.01 | 489.00 | 27.01 | 489.00 | 27.01 |
December | 497.00 | 27.65 | 497.00 | 27.65 | 497.00 | 27.65 |
Annual Sum or Average | 5943.00 | 27.64 | 5943.00 | 27.64 | 5943.00 | 27.64 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 31.95 | 514.00 | 31.95 | 514.00 | 31.95 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 16.99369 | 0.72165 | 16.06833 |
February | 454.00000 | 27.00002 | 17.43655 | 0.78278 | 18.02871 |
March | 514.00000 | 27.00001 | 18.11325 | 0.84671 | 20.21927 |
April | 485.00000 | 27.02682 | 16.87190 | 0.91126 | 22.63380 |
May | 508.00000 | 27.00021 | 20.19849 | 0.16503 | 5.70855 |
June | 496.00000 | 27.00040 | 24.56062 | 0.27073 | 6.63434 |
July | 497.00000 | 27.00048 | 27.19786 | 0.34260 | 7.52983 |
August | 514.00000 | 27.16278 | 27.05805 | 0.47120 | 10.00178 |
September | 485.00000 | 27.00080 | 25.64198 | 0.22784 | 6.19752 |
October | 502.00000 | 27.00025 | 21.06872 | 0.86048 | 20.75476 |
November | 489.00000 | 27.00004 | 18.28990 | 0.84212 | 20.06079 |
December | 497.00000 | 26.99999 | 14.80717 | 0.82900 | 19.60035 |
Annual Sum or Average | 5943.00000 | 27.01645 | 20.71748 | 0.60435 | 14.41545 |
Minimum of Months | 454.00000 | 26.99999 | 14.80717 | 0.16503 | 5.70855 |
Maximum of Months | 514.00000 | 27.16278 | 27.19786 | 0.91126 | 22.63380 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99997 | 16.97435 | 0.62543 | 13.35904 |
February | 454.00000 | 27.00002 | 17.41715 | 0.67122 | 14.65105 |
March | 514.00000 | 27.00001 | 18.08745 | 0.72859 | 16.31725 |
April | 485.00000 | 27.01387 | 16.85385 | 0.78426 | 18.11433 |
May | 508.00000 | 27.00017 | 20.21290 | 0.09352 | 5.37795 |
June | 496.00000 | 27.00038 | 24.56992 | 0.19038 | 5.91267 |
July | 497.00000 | 27.00052 | 27.21787 | 0.24822 | 6.39842 |
August | 514.00000 | 27.06650 | 27.15747 | 0.28720 | 6.95718 |
September | 485.00000 | 27.00069 | 25.75255 | 0.15773 | 5.67184 |
October | 502.00000 | 27.00024 | 21.06902 | 0.77373 | 17.80314 |
November | 489.00000 | 27.00004 | 18.27282 | 0.71129 | 15.79401 |
December | 497.00000 | 26.99999 | 14.78402 | 0.65323 | 14.13809 |
Annual Sum or Average | 5943.00000 | 27.00705 | 20.72864 | 0.49198 | 11.67574 |
Minimum of Months | 454.00000 | 26.99997 | 14.78402 | 0.09352 | 5.37795 |
Maximum of Months | 514.00000 | 27.06650 | 27.21787 | 0.78426 | 18.11433 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.75094 | 17.21030 | 0.50143 | 11.13697 |
February | 454.00000 | 27.00002 | 17.43142 | 0.60621 | 13.05291 |
March | 514.00000 | 27.00001 | 18.10255 | 0.68290 | 15.07808 |
April | 485.00000 | 27.00900 | 16.87051 | 0.76301 | 17.52081 |
May | 508.00000 | 27.00015 | 20.23497 | 0.08481 | 5.48571 |
June | 496.00000 | 27.00039 | 24.58073 | 0.20197 | 6.11222 |
July | 497.00000 | 27.00052 | 27.22096 | 0.26883 | 6.69395 |
August | 514.00000 | 27.05333 | 27.16946 | 0.29821 | 7.16510 |
September | 485.00000 | 27.00068 | 25.77056 | 0.15675 | 5.77136 |
October | 502.00000 | 27.00024 | 21.08854 | 0.74328 | 16.95182 |
November | 489.00000 | 27.00004 | 18.28551 | 0.64754 | 14.09162 |
December | 497.00000 | 26.99999 | 14.79492 | 0.57073 | 12.15518 |
Annual Sum or Average | 5943.00000 | 26.98448 | 20.76149 | 0.45896 | 10.90922 |
Minimum of Months | 454.00000 | 26.75094 | 14.79492 | 0.08481 | 5.48571 |
Maximum of Months | 514.00000 | 27.05333 | 27.22096 | 0.76301 | 17.52081 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00003 | 29.99809 | 1.06005 | 28.72667 |
February | 454.00000 | 27.01511 | 29.99847 | 1.22166 | 36.32079 |
March | 514.00000 | 27.00981 | 29.99791 | 1.37208 | 44.03321 |
April | 485.00000 | 28.86240 | 29.90173 | 1.90424 | 71.54411 |
May | 508.00000 | 27.00297 | 29.99968 | 0.51058 | 10.52025 |
June | 496.00000 | 27.00944 | 29.99734 | 0.73786 | 16.47821 |
July | 497.00000 | 27.00513 | 29.99771 | 0.94595 | 23.91728 |
August | 514.00000 | 31.95259 | 29.87205 | 2.61971 | 93.96054 |
September | 485.00000 | 27.00417 | 29.99790 | 0.56500 | 11.76569 |
October | 502.00000 | 27.01344 | 29.99707 | 1.27067 | 38.77589 |
November | 489.00000 | 27.00964 | 29.99983 | 1.39830 | 45.42399 |
December | 497.00000 | 27.64584 | 30.01510 | 1.65725 | 59.43648 |
Annual Sum or Average | 5943.00000 | 27.64008 | 29.98084 | 1.27493 | 40.19293 |
Minimum of Months | 454.00000 | 27.00003 | 29.87205 | 0.51058 | 10.52025 |
Maximum of Months | 514.00000 | 31.95259 | 30.01510 | 2.61971 | 93.96054 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.50272 | 14.25415 | 0.30451 | 7.38172 |
February | 454.00000 | 24.49027 | 15.36855 | 0.31117 | 7.44944 |
March | 514.00000 | 24.41538 | 15.31062 | 0.30267 | 7.22095 |
April | 485.00000 | 24.52564 | 13.69266 | 0.31993 | 7.62300 |
May | 508.00000 | 24.50186 | 21.22344 | -0.4822 | 10.93375 |
June | 496.00000 | 24.47333 | 31.90349 | -0.4052 | 9.32460 |
July | 497.00000 | 24.62972 | 45.76301 | -0.2545 | 7.58619 |
August | 514.00000 | 24.49823 | 45.33607 | -0.2786 | 7.61120 |
September | 485.00000 | 24.57121 | 37.48907 | -0.3249 | 8.53547 |
October | 502.00000 | 24.61666 | 22.63350 | 0.41460 | 9.37401 |
November | 489.00000 | 24.59443 | 15.85355 | 0.35663 | 8.27030 |
December | 497.00000 | 24.57153 | 12.19680 | 0.31799 | 7.67412 |
Annual Sum or Average | 5943.00000 | 24.53231 | 24.34032 | 0.04581 | 8.25541 |
Minimum of Months | 454.00000 | 24.41538 | 12.19680 | -0.4822 | 7.22095 |
Maximum of Months | 514.00000 | 24.62972 | 45.76301 | 0.41460 | 10.93375 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.18813 | 15.95873 | 0.23853 | 6.35931 |
February | 454.00000 | 24.27539 | 16.74171 | 0.27433 | 6.75514 |
March | 514.00000 | 24.27674 | 16.23629 | 0.29266 | 6.97529 |
April | 485.00000 | 24.28835 | 14.16674 | 0.30109 | 7.07019 |
May | 508.00000 | 24.26358 | 22.52037 | -0.5217 | 11.18557 |
June | 496.00000 | 24.22282 | 33.49797 | -0.4365 | 9.28737 |
July | 497.00000 | 24.24909 | 47.80584 | -0.3159 | 7.36375 |
August | 514.00000 | 24.20892 | 46.01482 | -0.3162 | 7.28257 |
September | 485.00000 | 24.33542 | 38.65502 | -0.3753 | 8.53383 |
October | 502.00000 | 24.35191 | 23.55509 | 0.36984 | 8.24961 |
November | 489.00000 | 24.34141 | 16.72083 | 0.30990 | 7.24256 |
December | 497.00000 | 24.37029 | 13.47919 | 0.28346 | 6.96010 |
Annual Sum or Average | 5943.00000 | 24.28058 | 25.53303 | 0.00601 | 7.78166 |
Minimum of Months | 454.00000 | 24.18813 | 13.47919 | -0.5217 | 6.35931 |
Maximum of Months | 514.00000 | 24.37029 | 47.80584 | 0.36984 | 11.18557 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.48527 | 17.53528 | 0.04399 | 5.54558 |
February | 454.00000 | 23.70358 | 18.23359 | 0.10886 | 5.61265 |
March | 514.00000 | 23.96323 | 17.29626 | 0.18408 | 5.91954 |
April | 485.00000 | 24.13925 | 14.85122 | 0.22401 | 6.19975 |
May | 508.00000 | 24.16282 | 22.88732 | -0.5850 | 12.57481 |
June | 496.00000 | 24.17314 | 33.56858 | -0.4883 | 10.28393 |
July | 497.00000 | 24.23063 | 47.54709 | -0.3658 | 8.06001 |
August | 514.00000 | 24.21213 | 46.56916 | -0.3764 | 8.20854 |
September | 485.00000 | 24.23660 | 39.07872 | -0.4378 | 9.40543 |
October | 502.00000 | 24.11805 | 24.31739 | 0.28597 | 7.09113 |
November | 489.00000 | 23.89940 | 18.25166 | 0.16857 | 5.87186 |
December | 497.00000 | 23.55112 | 15.62531 | 0.04913 | 5.49121 |
Annual Sum or Average | 5943.00000 | 23.99153 | 26.39567 | -0.1013 | 7.54118 |
Minimum of Months | 454.00000 | 23.48527 | 14.85122 | -0.5850 | 5.49121 |
Maximum of Months | 514.00000 | 24.23660 | 47.54709 | 0.28597 | 12.57481 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.99213 | 19.27371 | -0.3343 | 9.82132 |
February | 454.00000 | 22.54077 | 20.00219 | -0.1877 | 7.67671 |
March | 514.00000 | 23.31642 | 18.46145 | 0.01241 | 6.06336 |
April | 485.00000 | 23.87650 | 15.08958 | 0.15411 | 5.95068 |
May | 508.00000 | 24.07171 | 22.70737 | -0.6159 | 13.66202 |
June | 496.00000 | 24.17768 | 33.55157 | -0.4696 | 9.95934 |
July | 497.00000 | 24.29609 | 47.44303 | -0.3203 | 7.53478 |
August | 514.00000 | 24.24907 | 46.45464 | -0.3461 | 7.82639 |
September | 485.00000 | 24.21185 | 38.77767 | -0.4451 | 9.56023 |
October | 502.00000 | 23.72105 | 24.99753 | 0.17732 | 6.65165 |
November | 489.00000 | 22.88780 | 20.07830 | -0.0939 | 6.81935 |
December | 497.00000 | 22.03914 | 17.49976 | -0.3341 | 9.51670 |
Annual Sum or Average | 5943.00000 | 23.45521 | 27.10238 | -0.2345 | 8.43112 |
Minimum of Months | 454.00000 | 21.99213 | 15.08958 | -0.6159 | 5.95068 |
Maximum of Months | 514.00000 | 24.29609 | 47.44303 | 0.17732 | 13.66202 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.04193 | 17.00226 | -0.2911 | 7.44628 |
February | 454.00000 | 22.53414 | 17.77052 | -0.1645 | 6.47303 |
March | 514.00000 | 23.32830 | 16.78654 | 0.03395 | 5.68606 |
April | 485.00000 | 23.88919 | 14.07199 | 0.18310 | 6.03809 |
May | 508.00000 | 24.07283 | 22.24198 | -0.5897 | 13.14889 |
June | 496.00000 | 24.25405 | 32.68645 | -0.3881 | 8.66414 |
July | 497.00000 | 24.36142 | 46.73064 | -0.2330 | 6.80706 |
August | 514.00000 | 24.23722 | 45.27040 | -0.2819 | 7.13896 |
September | 485.00000 | 24.20419 | 38.22506 | -0.4283 | 9.54353 |
October | 502.00000 | 23.63634 | 23.85758 | 0.17051 | 6.63079 |
November | 489.00000 | 23.01556 | 17.51388 | -0.0440 | 5.68489 |
December | 497.00000 | 22.34775 | 14.48340 | -0.2310 | 6.73692 |
Annual Sum or Average | 5943.00000 | 23.50043 | 25.63349 | -0.1894 | 7.51185 |
Minimum of Months | 454.00000 | 22.04193 | 14.07199 | -0.5897 | 5.68489 |
Maximum of Months | 514.00000 | 24.36142 | 46.73064 | 0.18310 | 13.14889 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.10857 | 16.30970 | -0.2364 | 7.59352 |
February | 454.00000 | 22.48491 | 17.17809 | -0.1264 | 6.88003 |
March | 514.00000 | 23.17318 | 16.39740 | 0.06465 | 6.60041 |
April | 485.00000 | 23.80349 | 13.73825 | 0.25225 | 7.61336 |
May | 508.00000 | 24.08211 | 21.80271 | -0.4640 | 12.35443 |
June | 496.00000 | 24.19795 | 32.63161 | -0.2902 | 8.48116 |
July | 497.00000 | 24.32764 | 46.68623 | -0.1384 | 7.71432 |
August | 514.00000 | 24.08575 | 45.52118 | -0.2350 | 7.99402 |
September | 485.00000 | 24.09968 | 38.13927 | -0.3475 | 9.49618 |
October | 502.00000 | 23.54937 | 23.48478 | 0.22176 | 8.12111 |
November | 489.00000 | 22.75008 | 17.12733 | -0.0494 | 6.42787 |
December | 497.00000 | 22.09940 | 14.04347 | -0.2494 | 7.55361 |
Annual Sum or Average | 5943.00000 | 23.40358 | 25.33761 | -0.1338 | 8.08111 |
Minimum of Months | 454.00000 | 22.09940 | 13.73825 | -0.4640 | 6.42787 |
Maximum of Months | 514.00000 | 24.32764 | 46.68623 | 0.25225 | 12.35443 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.24451 | 15.29136 | 0.06456 | 8.57860 |
February | 454.00000 | 23.48741 | 16.10998 | 0.14422 | 8.05845 |
March | 514.00000 | 23.66351 | 15.91148 | 0.18259 | 7.21184 |
April | 485.00000 | 23.95986 | 13.70244 | 0.25522 | 7.22694 |
May | 508.00000 | 24.00580 | 22.19781 | -0.5805 | 13.62926 |
June | 496.00000 | 24.14449 | 32.87164 | -0.4214 | 9.51934 |
July | 497.00000 | 24.33942 | 46.75697 | -0.2193 | 7.01648 |
August | 514.00000 | 24.26812 | 45.04473 | -0.2082 | 6.96090 |
September | 485.00000 | 24.40240 | 37.41670 | -0.2426 | 8.24894 |
October | 502.00000 | 24.22953 | 22.52277 | 0.41698 | 10.87726 |
November | 489.00000 | 23.89716 | 15.91429 | 0.26353 | 8.67033 |
December | 497.00000 | 23.46428 | 12.92103 | 0.12615 | 8.29931 |
Annual Sum or Average | 5943.00000 | 23.92774 | 24.80965 | -0.0204 | 8.70149 |
Minimum of Months | 454.00000 | 23.24451 | 12.92103 | -0.5805 | 6.96090 |
Maximum of Months | 514.00000 | 24.40240 | 46.75697 | 0.41698 | 13.62926 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.40801 | 15.84183 | -0.1316 | 6.79008 |
February | 454.00000 | 23.17886 | 16.31869 | 0.08074 | 6.64862 |
March | 514.00000 | 23.91226 | 15.52726 | 0.28410 | 7.78615 |
April | 485.00000 | 24.42138 | 13.14384 | 0.46729 | 10.52333 |
May | 508.00000 | 24.10866 | 21.87938 | -0.4270 | 11.03947 |
June | 496.00000 | 24.33300 | 32.34333 | -0.1962 | 7.55256 |
July | 497.00000 | 24.45123 | 46.30238 | -0.0174 | 6.60375 |
August | 514.00000 | 24.44108 | 44.44029 | 0.04529 | 6.53885 |
September | 485.00000 | 24.29633 | 37.67776 | -0.2408 | 8.23582 |
October | 502.00000 | 23.99255 | 22.80579 | 0.36985 | 9.55637 |
November | 489.00000 | 23.72627 | 15.96493 | 0.22556 | 7.06555 |
December | 497.00000 | 23.62955 | 12.67628 | 0.16258 | 6.67438 |
Annual Sum or Average | 5943.00000 | 23.91261 | 24.66058 | 0.05109 | 7.92429 |
Minimum of Months | 454.00000 | 22.40801 | 12.67628 | -0.4270 | 6.53885 |
Maximum of Months | 514.00000 | 24.45123 | 46.30238 | 0.46729 | 11.03947 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.72384 | 18.28223 | -0.6407 | 14.68099 |
February | 454.00000 | 21.10595 | 19.38702 | -0.5266 | 11.88514 |
March | 514.00000 | 22.08768 | 18.32861 | -0.2726 | 7.78060 |
April | 485.00000 | 23.19693 | 15.05822 | -0.0056 | 6.09577 |
May | 508.00000 | 23.78866 | 22.79408 | -0.7074 | 16.89078 |
June | 496.00000 | 24.18860 | 32.63434 | -0.4405 | 9.71865 |
July | 497.00000 | 24.37907 | 46.33483 | -0.2652 | 7.09155 |
August | 514.00000 | 24.22453 | 45.60103 | -0.3421 | 7.87842 |
September | 485.00000 | 23.97579 | 38.82587 | -0.5292 | 11.67724 |
October | 502.00000 | 22.76394 | 25.14425 | -0.0492 | 7.09298 |
November | 489.00000 | 21.43749 | 19.19955 | -0.4307 | 10.11214 |
December | 497.00000 | 20.66144 | 16.36099 | -0.6698 | 15.30805 |
Annual Sum or Average | 5943.00000 | 22.72362 | 26.57073 | -0.4062 | 10.51210 |
Minimum of Months | 454.00000 | 20.66144 | 15.05822 | -0.7074 | 6.09577 |
Maximum of Months | 514.00000 | 24.37907 | 46.33483 | -0.0056 | 16.89078 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.07320 | 16.88753 | -0.5261 | 11.97932 |
February | 385.00000 | 21.45061 | 17.93200 | -0.4028 | 10.14106 |
March | 433.00000 | 22.39159 | 16.96834 | -0.1398 | 7.44343 |
April | 410.00000 | 23.62276 | 13.77511 | 0.18536 | 7.74517 |
May | 430.00000 | 23.92454 | 22.03438 | -0.5332 | 15.18458 |
June | 418.00000 | 24.24662 | 31.86801 | -0.2980 | 9.44493 |
July | 422.00000 | 24.53804 | 45.19675 | -0.0978 | 8.41004 |
August | 433.00000 | 24.29671 | 44.65378 | -0.1996 | 8.37300 |
September | 410.00000 | 23.95050 | 38.03242 | -0.4232 | 11.53700 |
October | 427.00000 | 23.02564 | 23.72061 | 0.07775 | 8.08284 |
November | 417.00000 | 21.76114 | 17.96835 | -0.3071 | 8.59600 |
December | 422.00000 | 20.95110 | 15.12519 | -0.5643 | 12.82855 |
Annual Sum or Average | 5034.00000 | 22.94462 | 25.40946 | -0.2686 | 9.98205 |
Minimum of Months | 385.00000 | 20.95110 | 13.77511 | -0.5643 | 7.44343 |
Maximum of Months | 433.00000 | 24.53804 | 45.19675 | 0.18536 | 15.18458 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.95258 | 15.64962 | -0.0096 | 9.98833 |
February | 454.00000 | 23.15145 | 16.67194 | 0.06198 | 9.03299 |
March | 514.00000 | 23.25072 | 16.55565 | 0.07835 | 7.51655 |
April | 485.00000 | 23.66052 | 14.10894 | 0.16538 | 7.05588 |
May | 508.00000 | 23.80312 | 22.56330 | -0.6627 | 16.23941 |
June | 496.00000 | 24.06374 | 32.82872 | -0.4750 | 10.82611 |
July | 497.00000 | 24.36529 | 46.33242 | -0.2458 | 7.29538 |
August | 514.00000 | 24.30747 | 45.18737 | -0.2407 | 7.40813 |
September | 485.00000 | 24.34389 | 37.48626 | -0.2700 | 9.01549 |
October | 502.00000 | 24.10224 | 22.74997 | 0.38362 | 11.23126 |
November | 489.00000 | 23.58192 | 16.41791 | 0.18607 | 9.33102 |
December | 497.00000 | 23.00691 | 13.80598 | 0.00873 | 9.64864 |
Annual Sum or Average | 5943.00000 | 23.71908 | 25.11654 | -0.0871 | 9.56125 |
Minimum of Months | 454.00000 | 22.95258 | 13.80598 | -0.6627 | 7.05588 |
Maximum of Months | 514.00000 | 24.36529 | 46.33242 | 0.38362 | 16.23941 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.25011 | 17.05944 | -0.4640 | 11.22715 |
February | 454.00000 | 21.69243 | 18.08831 | -0.3238 | 9.39649 |
March | 514.00000 | 22.29282 | 17.39570 | -0.1495 | 7.53828 |
April | 485.00000 | 23.32473 | 14.30081 | 0.12022 | 7.44311 |
May | 508.00000 | 23.58650 | 22.72987 | -0.6452 | 17.19473 |
June | 496.00000 | 24.03336 | 32.82414 | -0.3707 | 10.66666 |
July | 497.00000 | 24.25324 | 46.63179 | -0.1875 | 7.61796 |
August | 514.00000 | 24.16779 | 45.57127 | -0.2273 | 7.75975 |
September | 485.00000 | 23.83399 | 38.72740 | -0.4412 | 11.79217 |
October | 502.00000 | 22.88159 | 24.37697 | 0.06618 | 7.94502 |
November | 489.00000 | 21.82820 | 18.09048 | -0.2721 | 8.37034 |
December | 497.00000 | 21.26351 | 15.12755 | -0.4708 | 11.25931 |
Annual Sum or Average | 5943.00000 | 22.87624 | 25.99109 | -0.2807 | 9.85755 |
Minimum of Months | 454.00000 | 21.25011 | 14.30081 | -0.6452 | 7.44311 |
Maximum of Months | 514.00000 | 24.25324 | 46.63179 | 0.12022 | 17.19473 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.14236 | 18.91397 | -0.8356 | 22.07181 |
February | 454.00000 | 20.50737 | 20.05961 | -0.7121 | 17.54888 |
March | 514.00000 | 21.38826 | 18.93342 | -0.4576 | 11.14226 |
April | 485.00000 | 22.69736 | 15.27225 | -0.1253 | 7.26226 |
May | 508.00000 | 23.49761 | 22.88816 | -0.7983 | 20.80437 |
June | 496.00000 | 24.10281 | 32.90260 | -0.4508 | 10.44925 |
July | 497.00000 | 24.36702 | 46.54950 | -0.2455 | 7.14957 |
August | 514.00000 | 24.17608 | 45.80727 | -0.3401 | 8.18422 |
September | 485.00000 | 23.77112 | 38.94097 | -0.5901 | 13.81566 |
October | 502.00000 | 22.19367 | 25.68992 | -0.1946 | 8.70747 |
November | 489.00000 | 20.68362 | 20.04683 | -0.6432 | 15.83504 |
December | 497.00000 | 20.10016 | 17.00392 | -0.8642 | 22.99789 |
Annual Sum or Average | 5943.00000 | 22.31644 | 26.99044 | -0.5204 | 13.80667 |
Minimum of Months | 454.00000 | 20.10016 | 15.27225 | -0.8642 | 7.14957 |
Maximum of Months | 514.00000 | 24.36702 | 46.54950 | -0.1253 | 22.99789 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.52105 | 17.99117 | -0.6971 | 17.10637 |
February | 454.00000 | 20.98592 | 19.02932 | -0.5413 | 13.51087 |
March | 514.00000 | 22.15267 | 17.65199 | -0.2143 | 8.48570 |
April | 485.00000 | 23.51754 | 13.92711 | 0.16480 | 7.80160 |
May | 508.00000 | 23.85032 | 21.85038 | -0.5402 | 15.37296 |
June | 496.00000 | 24.20537 | 32.47826 | -0.2685 | 9.08855 |
July | 497.00000 | 24.48392 | 46.03936 | -0.0620 | 8.06750 |
August | 514.00000 | 24.25685 | 45.30394 | -0.1645 | 8.00800 |
September | 485.00000 | 23.89747 | 38.17699 | -0.4124 | 11.42441 |
October | 502.00000 | 22.86586 | 24.29417 | 0.03305 | 8.40310 |
November | 489.00000 | 21.24573 | 18.93570 | -0.4562 | 11.27912 |
December | 497.00000 | 20.38346 | 16.22941 | -0.7403 | 18.60662 |
Annual Sum or Average | 5943.00000 | 22.71053 | 26.06642 | -0.3236 | 11.41376 |
Minimum of Months | 454.00000 | 20.38346 | 13.92711 | -0.7403 | 7.80160 |
Maximum of Months | 514.00000 | 24.48392 | 46.03936 | 0.16480 | 18.60662 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.20894 | 16.50463 | -0.2307 | 12.52743 |
February | 454.00000 | 22.49739 | 17.52682 | -0.1280 | 10.91989 |
March | 514.00000 | 22.73721 | 17.19069 | -0.0660 | 8.69291 |
April | 485.00000 | 23.31002 | 14.31569 | 0.07769 | 7.56490 |
May | 508.00000 | 23.54480 | 22.63819 | -0.7430 | 19.72698 |
June | 496.00000 | 23.95759 | 33.14119 | -0.4907 | 11.88507 |
July | 497.00000 | 24.33051 | 46.62303 | -0.2316 | 7.55951 |
August | 514.00000 | 24.25049 | 45.43658 | -0.2388 | 7.81012 |
September | 485.00000 | 24.19699 | 37.51344 | -0.3111 | 10.24621 |
October | 502.00000 | 23.72169 | 23.17052 | 0.28057 | 10.88529 |
November | 489.00000 | 22.93060 | 17.30691 | 0.00062 | 9.81427 |
December | 497.00000 | 22.23932 | 14.71991 | -0.2170 | 12.78357 |
Annual Sum or Average | 5943.00000 | 23.33259 | 25.59152 | -0.1929 | 10.87965 |
Minimum of Months | 454.00000 | 22.20894 | 14.31569 | -0.7430 | 7.55951 |
Maximum of Months | 514.00000 | 24.33051 | 46.62303 | 0.28057 | 19.72698 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.74301 | 17.72454 | -0.6322 | 16.43661 |
February | 454.00000 | 21.26430 | 18.68511 | -0.4645 | 12.72446 |
March | 514.00000 | 21.89110 | 17.87146 | -0.2691 | 9.26114 |
April | 485.00000 | 23.00367 | 14.45518 | 0.04002 | 7.96834 |
May | 508.00000 | 23.34323 | 22.79245 | -0.7194 | 20.41503 |
June | 496.00000 | 23.92410 | 33.15335 | -0.3859 | 11.80469 |
July | 497.00000 | 24.20629 | 46.96575 | -0.1776 | 8.06394 |
August | 514.00000 | 24.09473 | 45.85024 | -0.2309 | 8.32607 |
September | 485.00000 | 23.67197 | 38.78549 | -0.4862 | 13.50096 |
October | 502.00000 | 22.56797 | 24.73930 | -0.0227 | 8.61967 |
November | 489.00000 | 21.34242 | 18.79654 | -0.4216 | 11.39028 |
December | 497.00000 | 20.75499 | 15.80391 | -0.6404 | 16.46740 |
Annual Sum or Average | 5943.00000 | 22.57739 | 26.38149 | -0.3672 | 12.08068 |
Minimum of Months | 454.00000 | 20.74301 | 14.45518 | -0.7194 | 7.96834 |
Maximum of Months | 514.00000 | 24.20629 | 46.96575 | 0.04002 | 20.41503 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.337968E+10 | 48127.53 | 05-JAN-14:30 | 88.88 | 0.159590E+11 | 0.00 | 0.193387E+11 | 0.55 | 5.97 | 05-JAN-14:30 | 0.00 | 0.00 |
February | 0.626337E+10 | 80084.68 | 13-FEB-15:10 | 113.84 | 0.369921E+11 | 0.00 | 0.432554E+11 | 0.82 | 7.36 | 14-FEB-13:40 | 0.00 | 0.00 |
March | 0.186271E+11 | 82262.93 | 07-MAR-15:40 | 156.52 | 0.105617E+12 | 0.00 | 0.124244E+12 | 1.08 | 7.37 | 07-MAR-15:30 | 0.00 | 0.00 |
April | 0.479889E+11 | 90486.03 | 26-APR-13:10 | 295.83 | 0.310135E+12 | 0.00 | 0.358124E+12 | 2.37 | 7.42 | 24-APR-15:40 | 0.00 | 0.00 |
May | 0.776164E+11 | 96648.45 | 19-MAY-15:20 | 373.11 | 0.512651E+12 | 0.00 | 0.590268E+12 | 3.09 | 7.42 | 23-MAY-12:20 | 0.00 | 0.00 |
June | 0.122990E+12 | 114896.15 | 28-JUN-14:50 | 538.21 | 0.840008E+12 | 0.00 | 0.962998E+12 | 4.73 | 7.54 | 27-JUN-07:05 | 0.00 | 0.00 |
July | 0.147370E+12 | 121588.72 | 31-JUL-15:00 | 634.37 | 0.100929E+13 | 0.00 | 0.115666E+13 | 5.38 | 7.53 | 21-JUL-14:50 | 0.00 | 0.00 |
August | 0.143681E+12 | 116320.77 | 23-AUG-16:00 | 682.28 | 0.981390E+12 | 0.00 | 0.112507E+13 | 5.63 | 7.62 | 15-AUG-05:03 | 0.00 | 0.00 |
September | 0.100023E+12 | 130982.34 | 05-SEP-13:10 | 456.13 | 0.673476E+12 | 0.00 | 0.773499E+12 | 3.97 | 7.57 | 05-SEP-12:10 | 0.00 | 0.00 |
October | 0.535574E+11 | 99649.39 | 02-OCT-11:20 | 309.14 | 0.348040E+12 | 0.00 | 0.401597E+12 | 2.43 | 7.52 | 02-OCT-10:20 | 0.00 | 0.00 |
November | 0.599919E+10 | 63365.30 | 02-NOV-15:00 | 92.93 | 0.299019E+11 | 0.00 | 0.359011E+11 | 0.61 | 6.96 | 02-NOV-15:00 | 0.00 | 0.00 |
December | 0.109550E+10 | 4650.96 | 24-DEC-14:12 | 111.88 | 0.499005E+10 | 0.00 | 0.608555E+10 | 0.68 | 4.56 | 14-DEC-10:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.728592E+12 | 3853.12 | 0.486845E+13 | 0.00 | 0.559705E+13 | 2.62 | 0.00 | 0.00 | ||||
Minimum of Months | 0.109550E+10 | 4650.96 | 88.88 | 0.499005E+10 | 0.00 | 0.608555E+10 | 0.55 | 4.56 | 0.00 | 0.00 | ||
Maximum of Months | 0.147370E+12 | 130982.34 | 682.28 | 0.100929E+13 | 0.00 | 0.115666E+13 | 5.63 | 7.62 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.789203E+10 | 90486.03 | 26-APR-13:10 | 26.00 | 0.572139E+11 | 0.00 | 0.651059E+11 | 0.26 | 7.34 | 28-APR-13:30 | 0.00 | 0.00 |
May | 0.167508E+11 | 96648.45 | 19-MAY-15:20 | 54.08 | 0.121067E+12 | 0.00 | 0.137818E+12 | 0.53 | 7.42 | 23-MAY-12:20 | 0.00 | 0.00 |
June | 0.544778E+11 | 114896.15 | 28-JUN-14:50 | 163.05 | 0.397718E+12 | 0.00 | 0.452195E+12 | 1.65 | 7.54 | 27-JUN-07:05 | 0.00 | 0.00 |
July | 0.716707E+11 | 121588.72 | 31-JUL-15:00 | 209.09 | 0.522775E+12 | 0.00 | 0.594446E+12 | 2.05 | 7.53 | 21-JUL-14:50 | 0.00 | 0.00 |
August | 0.706717E+11 | 116320.77 | 23-AUG-16:00 | 209.05 | 0.516248E+12 | 0.00 | 0.586919E+12 | 2.05 | 7.62 | 15-AUG-05:03 | 0.00 | 0.00 |
September | 0.386965E+11 | 130982.34 | 05-SEP-13:10 | 120.40 | 0.281525E+12 | 0.00 | 0.320222E+12 | 1.22 | 7.57 | 05-SEP-12:10 | 0.00 | 0.00 |
October | 0.134078E+11 | 99649.39 | 02-OCT-11:20 | 43.27 | 0.973805E+11 | 0.00 | 0.110788E+12 | 0.42 | 7.52 | 02-OCT-10:20 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.273567E+12 | 824.93 | 0.199393E+13 | 0.00 | 0.226749E+13 | 0.69 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.716707E+11 | 130982.34 | 209.09 | 0.522775E+12 | 0.00 | 0.594446E+12 | 2.05 | 7.62 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.180283E+11 | 744.00 | 49248.27 | 05-JAN-14:00 | 231017.18 | 26-JAN-17:00 | 22.14 | 18.33 | 15.63 |
February | 0.357938E+11 | 672.00 | 49248.27 | 10-FEB-15:30 | 415338.66 | 13-FEB-17:05 | 25.24 | 18.49 | 15.63 |
March | 0.857692E+11 | 744.00 | 49248.27 | 01-MAR-12:00 | 682793.62 | 31-MAR-24:00 | 29.01 | 19.29 | 15.63 |
April | 0.117015E+12 | 720.00 | 49248.27 | 01-APR-07:50 | 739843.10 | 29-APR-18:11 | 35.32 | 22.59 | 15.63 |
May | 0.102813E+12 | 744.00 | 49248.27 | 02-MAY-10:40 | 388196.33 | 31-MAY-24:00 | 26.03 | 21.81 | 15.63 |
June | 0.125093E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 554428.67 | 30-JUN-23:42 | 34.92 | 27.64 | 15.63 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:05 | 702579.02 | 31-JUL-24:00 | 41.95 | 31.69 | 15.63 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 779026.35 | 20-AUG-18:11 | 45.07 | 31.90 | 15.63 |
September | 0.120252E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 385717.50 | 30-SEP-24:00 | 27.64 | 23.31 | 15.63 |
October | 0.964459E+11 | 744.00 | 49248.27 | 01-OCT-00:10 | 536873.13 | 31-OCT-23:50 | 27.87 | 20.83 | 15.63 |
November | 0.732165E+11 | 720.00 | 49248.27 | 01-NOV-00:10 | 561096.56 | 02-NOV-16:00 | 28.28 | 18.57 | 15.63 |
December | 0.654077E+11 | 744.00 | 49248.27 | 01-DEC-12:30 | 707404.85 | 24-DEC-16:22 | 30.78 | 18.35 | 15.63 |
Annual Sum or Average | 0.110365E+13 | 8760.00 | 31.23 | 22.76 | 15.63 | ||||
Minimum of Months | 0.180283E+11 | 672.00 | 49248.27 | 231017.18 | 22.14 | 18.33 | 15.63 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 779026.35 | 45.07 | 31.90 | 15.63 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 350773.67 | 05-JAN-14:40 | 20.99 | 20.96 | 2.42 |
February | 12015639.34 | 17.00 | 564.11 | 14-FEB-16:00 | 955889.25 | 14-FEB-16:00 | 21.07 | 20.98 | 3.67 |
March | 42291384.36 | 85.68 | 737.74 | 08-MAR-15:40 | 955203.33 | 08-MAR-14:10 | 21.18 | 20.97 | 9.09 |
April | 0.178504E+09 | 191.45 | 1009.69 | 14-APR-16:20 | 1090952.93 | 13-APR-15:20 | 21.69 | 21.01 | 18.96 |
May | 0.542808E+09 | 320.72 | 2198.72 | 22-MAY-09:20 | 1187446.93 | 19-MAY-15:10 | 22.37 | 21.27 | 27.28 |
June | 0.344040E+10 | 460.72 | 16838.64 | 06-JUN-12:40 | 1191510.95 | 12-JUN-15:00 | 23.09 | 21.18 | 40.54 |
July | 0.148811E+11 | 560.50 | 16838.64 | 01-JUL-05:03 | 1161142.43 | 21-JUL-16:30 | 23.37 | 21.31 | 48.00 |
August | 0.110057E+11 | 536.75 | 16838.64 | 01-AUG-09:30 | 1144259.05 | 31-AUG-14:40 | 23.25 | 21.17 | 49.69 |
September | 0.282903E+10 | 399.38 | 16838.64 | 01-SEP-10:20 | 1191510.32 | 13-SEP-15:40 | 22.92 | 21.37 | 35.04 |
October | 0.567973E+09 | 220.92 | 16838.64 | 02-OCT-14:00 | 1149683.43 | 04-OCT-14:20 | 21.92 | 21.15 | 20.51 |
November | 6930301.15 | 23.25 | 250.22 | 02-NOV-15:10 | 516653.97 | 02-NOV-15:10 | 21.02 | 20.95 | 3.91 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 226959.30 | 20-DEC-16:30 | 21.01 | 20.99 | 1.31 |
Annual Sum or Average | 0.335068E+11 | 2816.36 | 22.00 | 21.11 | 21.82 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 226959.30 | 20.99 | 20.95 | 1.31 | ||
Maximum of Months | 0.148811E+11 | 560.50 | 16838.64 | 1191510.95 | 23.37 | 21.37 | 49.69 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 20.99 | 20.99 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.07 | 21.07 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.18 | 21.18 | 0.00 |
April | 21664159.83 | 13.00 | 613.72 | 28-APR-13:40 | 1090952.93 | 13-APR-15:20 | 21.69 | 21.61 | 1.03 |
May | 93730148.06 | 31.33 | 1995.00 | 22-MAY-13:10 | 1187446.93 | 19-MAY-15:10 | 22.37 | 22.18 | 2.40 |
June | 0.198619E+10 | 138.75 | 16838.64 | 06-JUN-12:40 | 1191510.95 | 12-JUN-15:00 | 23.09 | 22.27 | 11.00 |
July | 0.923742E+10 | 177.33 | 16838.64 | 03-JUL-09:00 | 1161142.43 | 21-JUL-16:30 | 23.37 | 22.46 | 13.61 |
August | 0.728455E+10 | 171.17 | 16838.64 | 01-AUG-09:30 | 1144259.05 | 31-AUG-14:40 | 23.25 | 22.34 | 13.14 |
September | 0.147018E+10 | 94.33 | 16838.64 | 01-SEP-10:20 | 1191510.32 | 13-SEP-15:40 | 22.92 | 22.34 | 7.48 |
October | 0.230934E+09 | 35.17 | 16838.64 | 02-OCT-14:00 | 1149683.43 | 04-OCT-14:20 | 21.92 | 21.71 | 2.70 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.02 | 21.02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.01 | 21.01 | 0.00 |
Annual Sum or Average | 0.203247E+11 | 661.08 | 22.00 | 21.69 | 4.31 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 | 20.99 | 0.00 | ||
Maximum of Months | 0.923742E+10 | 177.33 | 16838.64 | 1191510.95 | 23.37 | 22.46 | 13.61 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.164543E+12 | 0.00 | 424.58 | 1176253.26 | 18-JAN-05:01 | 0.00 | 25.67 | 56.54 | 0.29 | 0.00 | 0.03 | 0.55 | 18-JAN-05:01 |
February | 0.920036E+11 | 0.00 | 327.69 | 1164202.40 | 01-FEB-06:01 | 0.00 | 24.47 | 51.07 | 0.18 | 0.00 | 0.02 | 0.54 | 01-FEB-06:01 |
March | 0.258682E+11 | 0.00 | 208.55 | 1216420.68 | 06-MAR-06:01 | 0.00 | 23.35 | 39.13 | 0.04 | 0.00 | 0.00 | 0.57 | 06-MAR-06:01 |
April | 0.296086E+10 | 0.00 | 53.64 | 454321.44 | 08-APR-05:03 | 0.00 | 22.56 | 26.82 | 0.00 | 0.00 | 0.00 | 0.21 | 08-APR-05:03 |
May | 0.488540E+09 | 0.00 | 19.74 | 93873.82 | 05-MAY-05:03 | 0.00 | 21.80 | 23.34 | 0.00 | 0.00 | 0.00 | 0.04 | 05-MAY-05:03 |
June | 28895726.15 | 0.00 | 3.98 | 10275.60 | 09-JUN-05:10 | 0.00 | 21.48 | 21.80 | 0.00 | 0.00 | 0.00 | 0.00 | 09-JUN-05:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 21.40 | 21.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 21.40 | 21.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3169669.64 | 0.00 | 2.21 | 1025.61 | 09-SEP-05:10 | 0.00 | 21.37 | 21.55 | 0.00 | 0.00 | 0.00 | 0.00 | 09-SEP-05:10 |
October | 0.123628E+11 | 0.00 | 110.86 | 1116459.14 | 26-OCT-05:02 | 0.00 | 21.75 | 30.20 | 0.02 | 0.00 | 0.00 | 0.52 | 26-OCT-05:02 |
November | 0.394447E+11 | 0.00 | 282.22 | 1156276.82 | 28-NOV-06:01 | 0.00 | 22.70 | 44.68 | 0.07 | 0.00 | 0.01 | 0.54 | 28-NOV-06:01 |
December | 0.152706E+12 | 0.00 | 435.31 | 1246055.06 | 04-DEC-05:01 | 0.00 | 24.92 | 57.10 | 0.27 | 0.00 | 0.03 | 0.58 | 04-DEC-05:01 |
Annual Sum or Average | 0.490410E+12 | 0.00 | 1868.78 | 0.00 | 22.73 | 34.51 | 0.07 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.37 | 21.40 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.164543E+12 | 0.00 | 435.31 | 1246055.06 | 0.00 | 25.67 | 57.10 | 0.29 | 0.00 | 0.03 | 0.58 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 22.14 | 22.14 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 25.24 | 25.24 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 29.01 | 29.01 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 35.32 | 35.32 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 26.03 | 26.03 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 34.92 | 34.92 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 41.95 | 41.95 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 45.07 | 45.07 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 27.64 | 27.64 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 27.87 | 27.87 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 28.28 | 28.28 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 30.78 | 30.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 31.23 | 31.23 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.14 | 22.14 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.07 | 45.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.115025E+10 | 0.00 | 26.95 | 0.115025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26812.55 | 05-JAN-14:30 | 26812.55 | 05-JAN-14:30 | 0.00 | 0.00 | 0.00 |
February | 0.349401E+10 | 0.00 | 37.78 | 0.349401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76342.57 | 14-FEB-15:50 | 76342.57 | 14-FEB-15:50 | 0.00 | 0.00 | 0.00 |
March | 0.108938E+11 | 0.00 | 130.44 | 0.108938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83025.15 | 08-MAR-16:00 | 83025.15 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.405220E+11 | 0.00 | 280.34 | 0.405220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119899.85 | 28-APR-14:50 | 119899.85 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.604086E+11 | 0.00 | 351.44 | 0.604086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119718.13 | 30-MAY-14:30 | 119718.13 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.116807E+12 | 0.00 | 511.93 | 0.116804E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 155845.26 | 29-JUN-05:03 | 142994.39 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.149613E+12 | 0.00 | 597.69 | 0.145685E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 152113.48 | 31-JUL-15:00 | 144113.20 | 05-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.159466E+12 | 0.00 | 652.37 | 0.154781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 172954.22 | 23-AUG-16:00 | 154509.78 | 07-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.864646E+11 | 0.00 | 436.19 | 0.853273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168932.63 | 05-SEP-13:10 | 122800.25 | 01-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.415551E+11 | 0.00 | 268.31 | 0.415320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118501.84 | 10-OCT-16:00 | 118501.84 | 10-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.271523E+10 | 0.00 | 60.49 | 0.271523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41737.98 | 02-NOV-15:00 | 41737.98 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 43718.29 | 0.00 | 0.65 | 43718.29 | 0.00 | 0.00 | 0.00 | 0.00 | 358.70 | 24-DEC-13:52 | 358.70 | 24-DEC-13:52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.673089E+12 | 0.00 | 3354.60 | 0.663313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 43718.29 | 0.00 | 0.65 | 43718.29 | 0.00 | 0.00 | 0.00 | 0.00 | 358.70 | 358.70 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.159466E+12 | 0.00 | 652.37 | 0.154781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 172954.22 | 154509.78 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.100859E+11 | 0.00 | 87.81 | 0.100859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 227716.84 | 05-JAN-15:30 | 227716.84 | 05-JAN-15:30 | 0.00 | 0.00 | 0.00 |
February | 0.293658E+11 | 0.00 | 111.40 | 0.293658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 646229.57 | 14-FEB-16:00 | 646229.57 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.840737E+11 | 0.00 | 145.58 | 0.840737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 646639.43 | 08-MAR-16:00 | 646639.43 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.293867E+12 | 0.00 | 244.82 | 0.293867E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 997882.21 | 13-APR-15:20 | 997882.21 | 13-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.526489E+12 | 0.00 | 345.69 | 0.526489E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1103399.87 | 19-MAY-15:20 | 1103399.87 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.100454E+13 | 0.00 | 458.52 | 0.100451E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1339774.11 | 28-JUN-14:50 | 1339774.11 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.121524E+13 | 0.00 | 493.06 | 0.118889E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1358682.81 | 31-JUL-15:00 | 1329448.13 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.115813E+13 | 0.00 | 500.61 | 0.113352E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1423974.14 | 14-AUG-03:02 | 1301637.81 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.758173E+12 | 0.00 | 417.90 | 0.747991E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1486259.89 | 05-SEP-13:30 | 1118336.65 | 21-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.351671E+12 | 0.00 | 281.70 | 0.351481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1044000.65 | 06-OCT-15:30 | 1044000.65 | 06-OCT-15:30 | 0.00 | 0.00 | 0.00 |
November | 0.207018E+11 | 0.00 | 89.84 | 0.207018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 341173.28 | 02-NOV-15:00 | 341173.28 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 2908108.81 | 0.00 | 111.21 | 2908108.81 | 0.00 | 0.00 | 0.00 | 0.00 | 21811.83 | 24-DEC-14:12 | 21811.83 | 24-DEC-14:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.545234E+13 | 0.00 | 3288.14 | 0.539097E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2908108.81 | 0.00 | 87.81 | 2908108.81 | 0.00 | 0.00 | 0.00 | 0.00 | 21811.83 | 21811.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.121524E+13 | 0.00 | 500.61 | 0.118889E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1486259.89 | 1339774.11 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.613080E+09 | 0.00 | 21.65 | 0.613080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19709.60 | 01-JAN-14:52 | 19709.60 | 01-JAN-14:52 | 0.00 | 0.00 | 0.00 |
February | 0.251712E+10 | 0.00 | 33.62 | 0.251712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64592.43 | 14-FEB-16:00 | 64592.43 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.727450E+10 | 0.00 | 117.06 | 0.727450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67815.17 | 08-MAR-16:00 | 67815.17 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.309021E+11 | 0.00 | 230.96 | 0.309021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119809.04 | 26-APR-15:00 | 119809.04 | 26-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.577152E+11 | 0.00 | 339.22 | 0.577152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134469.29 | 19-MAY-15:20 | 134469.29 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.114307E+12 | 0.00 | 454.22 | 0.114307E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 167547.81 | 28-JUN-14:20 | 167547.81 | 28-JUN-14:20 | 0.00 | 0.00 | 0.00 |
July | 0.139664E+12 | 0.00 | 497.57 | 0.136763E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 174629.60 | 16-JUL-15:21 | 164603.75 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.130993E+12 | 0.00 | 501.54 | 0.128478E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 168954.70 | 13-AUG-16:21 | 158214.85 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.824280E+11 | 0.00 | 407.95 | 0.816287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159621.05 | 05-SEP-13:30 | 133450.19 | 21-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.352528E+11 | 0.00 | 245.41 | 0.352520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119130.34 | 06-OCT-15:20 | 119130.34 | 06-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.150822E+10 | 0.00 | 50.17 | 0.150822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31695.62 | 02-NOV-15:00 | 31695.62 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 592.28 | 0.00 | 0.54 | 592.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 25-DEC-22:30 | 0.36 | 25-DEC-22:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.603175E+12 | 0.00 | 2899.90 | 0.596958E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 592.28 | 0.00 | 0.54 | 592.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 0.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.139664E+12 | 0.00 | 501.54 | 0.136763E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 174629.60 | 167547.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 139559.43 | 0.00 | 0.17 | 139559.43 | 0.00 | 0.00 | 0.00 | 0.00 | 232.60 | 02-JAN-15:00 | 232.60 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.139424E+10 | 0.00 | 16.00 | 0.139424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45143.11 | 13-FEB-16:00 | 45143.11 | 13-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.380723E+10 | 0.00 | 68.74 | 0.380723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47922.30 | 08-MAR-16:00 | 47922.30 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.205081E+11 | 0.00 | 177.94 | 0.205081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66525.61 | 17-APR-15:00 | 66525.61 | 17-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.357141E+11 | 0.00 | 259.61 | 0.357125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105756.05 | 29-MAY-16:00 | 105756.05 | 29-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.654134E+11 | 0.00 | 365.56 | 0.654022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89996.36 | 29-JUN-05:03 | 85604.44 | 29-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.789673E+11 | 0.00 | 404.09 | 0.780423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142034.72 | 02-JUL-18:07 | 108324.79 | 04-JUL-17:05 | 0.00 | 0.00 | 0.00 |
August | 0.817150E+11 | 0.00 | 436.30 | 0.805558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112806.65 | 13-AUG-15:01 | 98537.20 | 13-AUG-18:20 | 0.00 | 0.00 | 0.00 |
September | 0.531638E+11 | 0.00 | 342.90 | 0.525189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106112.70 | 05-SEP-13:00 | 88323.41 | 03-SEP-16:58 | 0.00 | 0.00 | 0.00 |
October | 0.243442E+11 | 0.00 | 193.67 | 0.243414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107219.62 | 01-OCT-15:46 | 107219.62 | 01-OCT-15:46 | 0.00 | 0.00 | 0.00 |
November | 0.558754E+09 | 0.00 | 24.50 | 0.558754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26225.60 | 09-NOV-14:00 | 26225.60 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365586E+12 | 0.00 | 2289.49 | 0.362842E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.817150E+11 | 0.00 | 436.30 | 0.805558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142034.72 | 108324.79 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.396513E+12 | 0.100492E+12 | 744.00 | 0.347135E+12 | 0.493775E+11 | 0.00 | 0.38 | 03-JAN-22:03 | 0.35 | 21-JAN-07:10 | 152567.68 | 03-JAN-22:03 | 133463.98 | 02-JAN-22:07 | 19335.71 | 11-JAN-22:03 | 38543.27 | 05-JAN-16:00 | 0.00 |
February | 0.611935E+12 | 0.147987E+12 | 672.00 | 0.536610E+12 | 0.753247E+11 | 0.00 | 0.62 | 14-FEB-16:00 | 0.57 | 01-FEB-08:00 | 258044.48 | 24-FEB-22:03 | 226593.79 | 14-FEB-16:00 | 32837.35 | 25-FEB-01:00 | 77462.20 | 14-FEB-16:00 | 0.00 |
March | 0.958077E+12 | 0.228372E+12 | 744.00 | 0.844419E+12 | 0.113657E+12 | 0.00 | 1.00 | 31-MAR-23:30 | 0.79 | 01-MAR-07:05 | 461653.66 | 31-MAR-24:00 | 405287.80 | 31-MAR-24:00 | 56415.71 | 31-MAR-23:40 | 110437.40 | 08-MAR-16:00 | 0.00 |
April | 0.119135E+13 | 0.297130E+12 | 720.00 | 0.105084E+13 | 0.140517E+12 | 0.00 | 1.00 | 01-APR-00:10 | 0.42 | 30-APR-24:00 | 478905.48 | 29-APR-02:50 | 412510.27 | 29-APR-02:50 | 66949.35 | 29-APR-03:02 | 146308.18 | 13-APR-17:00 | 0.00 |
May | 0.399365E+12 | 0.114020E+12 | 744.00 | 0.356302E+12 | 0.430625E+11 | 0.00 | 0.60 | 31-MAY-23:30 | 0.36 | 04-MAY-06:05 | 246534.28 | 31-MAY-24:00 | 220754.29 | 31-MAY-24:00 | 25779.98 | 31-MAY-24:00 | 69820.34 | 31-MAY-23:20 | 0.00 |
June | 0.638768E+12 | 0.207809E+12 | 720.00 | 0.585530E+12 | 0.532377E+11 | 0.00 | 0.83 | 30-JUN-23:12 | 0.59 | 01-JUN-06:10 | 341132.21 | 30-JUN-24:00 | 312747.48 | 30-JUN-24:00 | 33014.30 | 10-JUN-06:05 | 116269.96 | 28-JUN-16:00 | 0.00 |
July | 0.912781E+12 | 0.319031E+12 | 744.00 | 0.852379E+12 | 0.604013E+11 | 0.00 | 1.00 | 31-JUL-23:02 | 0.82 | 01-JUL-06:10 | 439158.72 | 31-JUL-24:00 | 397251.44 | 31-JUL-24:00 | 42335.22 | 31-JUL-23:57 | 157793.21 | 21-JUL-15:00 | 0.00 |
August | 0.120900E+13 | 0.377777E+12 | 744.00 | 0.107855E+13 | 0.130452E+12 | 0.00 | 1.00 | 01-AUG-00:03 | 0.45 | 31-AUG-24:00 | 477553.37 | 25-AUG-21:00 | 411672.62 | 31-AUG-06:00 | 73336.28 | 25-AUG-20:30 | 172667.74 | 20-AUG-16:00 | 0.00 |
September | 0.390063E+12 | 0.116722E+12 | 720.00 | 0.349510E+12 | 0.405521E+11 | 0.00 | 0.60 | 30-SEP-24:00 | 0.36 | 09-SEP-06:10 | 248686.15 | 30-SEP-24:00 | 221152.25 | 30-SEP-24:00 | 27765.16 | 30-SEP-23:10 | 66847.82 | 30-SEP-23:30 | 0.00 |
October | 0.680556E+12 | 0.178199E+12 | 744.00 | 0.603569E+12 | 0.769869E+11 | 0.00 | 0.81 | 31-OCT-23:30 | 0.58 | 26-OCT-07:00 | 358028.69 | 31-OCT-24:00 | 314469.71 | 31-OCT-24:00 | 43558.98 | 31-OCT-24:00 | 90640.59 | 01-OCT-16:00 | 0.00 |
November | 0.935728E+12 | 0.217204E+12 | 720.00 | 0.820010E+12 | 0.115718E+12 | 0.00 | 0.83 | 09-NOV-14:00 | 0.80 | 27-NOV-07:10 | 365483.22 | 20-NOV-22:03 | 319443.60 | 02-NOV-21:03 | 46916.53 | 12-NOV-10:53 | 101338.30 | 09-NOV-14:00 | 0.00 |
December | 0.125086E+13 | 0.275182E+12 | 744.00 | 0.108869E+13 | 0.162167E+12 | 0.00 | 1.00 | 01-DEC-00:10 | 1.00 | 01-DEC-07:10 | 473654.45 | 24-DEC-16:47 | 409639.48 | 18-DEC-24:00 | 67890.44 | 26-DEC-07:30 | 109251.67 | 24-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.957500E+13 | 0.257993E+13 | 8760.00 | 0.851354E+13 | 0.106145E+13 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.390063E+12 | 0.100492E+12 | 672.00 | 0.347135E+12 | 0.405521E+11 | 0.00 | 0.38 | 0.35 | 152567.68 | 133463.98 | 19335.71 | 38543.27 | 0.00 | ||||||
Maximum of Months | 0.125086E+13 | 0.377777E+12 | 744.00 | 0.108869E+13 | 0.162167E+12 | 0.00 | 1.00 | 1.00 | 478905.48 | 412510.27 | 73336.28 | 172667.74 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.472837E+10 | 0.130847E+10 | 744.00 | 0.472783E+10 | 542501.97 | 0.00 | 0.36 | 26-JAN-17:00 | 0.13 | 21-JAN-07:40 | 2888.42 | 26-JAN-17:00 | 2888.42 | 26-JAN-17:00 | 27.55 | 20-JAN-17:00 | 775.95 | 26-JAN-17:00 | 0.00 |
February | 0.927689E+10 | 0.241607E+10 | 672.00 | 0.927401E+10 | 2870994.79 | 0.00 | 0.60 | 14-FEB-17:00 | 0.37 | 04-FEB-07:55 | 5046.25 | 15-FEB-17:00 | 5046.25 | 15-FEB-17:00 | 80.40 | 17-FEB-11:10 | 1574.40 | 14-FEB-17:00 | 0.00 |
March | 0.158670E+11 | 0.404976E+10 | 744.00 | 0.158630E+11 | 4057850.26 | 0.00 | 0.86 | 12-MAR-17:21 | 0.59 | 04-MAR-07:15 | 7796.15 | 31-MAR-24:00 | 7796.15 | 31-MAR-24:00 | 100.46 | 20-MAR-16:05 | 2271.31 | 12-MAR-17:03 | 0.00 |
April | 0.207493E+11 | 0.573198E+10 | 720.00 | 0.207491E+11 | 160752.03 | 0.00 | 1.00 | 01-APR-15:30 | 0.33 | 30-APR-23:56 | 8958.26 | 15-APR-17:55 | 8958.26 | 15-APR-17:55 | 41.26 | 20-APR-09:30 | 3097.26 | 13-APR-17:00 | 0.00 |
May | 0.626172E+10 | 0.189748E+10 | 744.00 | 0.622596E+10 | 35764259.51 | 0.00 | 0.50 | 31-MAY-23:50 | 0.20 | 05-MAY-06:05 | 4199.52 | 31-MAY-24:00 | 4199.52 | 31-MAY-24:00 | 276.11 | 24-MAY-15:50 | 1250.41 | 31-MAY-23:20 | 0.00 |
June | 0.112999E+11 | 0.379917E+10 | 720.00 | 0.112233E+11 | 76524627.57 | 0.00 | 0.71 | 18-JUN-18:21 | 0.43 | 09-JUN-06:10 | 6034.41 | 30-JUN-23:40 | 6030.74 | 30-JUN-23:23 | 315.38 | 30-JUN-14:00 | 2451.75 | 28-JUN-16:00 | 0.00 |
July | 0.168882E+11 | 0.598208E+10 | 744.00 | 0.166927E+11 | 0.195528E+09 | 0.00 | 0.92 | 04-JUL-18:11 | 0.67 | 08-JUL-06:05 | 7935.56 | 31-JUL-23:57 | 7935.56 | 31-JUL-23:57 | 432.51 | 07-JUL-17:00 | 3234.19 | 21-JUL-18:10 | 0.00 |
August | 0.223138E+11 | 0.760902E+10 | 744.00 | 0.221015E+11 | 0.212267E+09 | 0.00 | 1.00 | 01-AUG-12:20 | 0.34 | 31-AUG-24:00 | 8985.53 | 23-AUG-16:00 | 8747.61 | 23-AUG-18:00 | 418.61 | 23-AUG-14:00 | 3658.01 | 20-AUG-16:00 | 0.00 |
September | 0.636990E+10 | 0.195658E+10 | 720.00 | 0.623621E+10 | 0.133687E+09 | 0.00 | 0.49 | 30-SEP-24:00 | 0.22 | 09-SEP-06:15 | 4190.54 | 30-SEP-24:00 | 4190.54 | 30-SEP-24:00 | 302.08 | 05-SEP-14:40 | 1252.14 | 02-SEP-17:31 | 0.00 |
October | 0.111858E+11 | 0.307977E+10 | 744.00 | 0.111380E+11 | 47801874.55 | 0.00 | 0.68 | 31-OCT-23:40 | 0.38 | 26-OCT-06:55 | 5987.88 | 31-OCT-24:00 | 5987.88 | 31-OCT-24:00 | 257.83 | 02-OCT-17:00 | 1832.59 | 05-OCT-17:00 | 0.00 |
November | 0.152633E+11 | 0.377934E+10 | 720.00 | 0.152535E+11 | 9805107.47 | 0.00 | 0.79 | 19-NOV-16:23 | 0.60 | 10-NOV-07:50 | 6866.99 | 02-NOV-16:30 | 6861.81 | 06-NOV-16:40 | 132.21 | 02-NOV-11:10 | 1839.20 | 02-NOV-16:00 | 0.00 |
December | 0.205757E+11 | 0.499324E+10 | 744.00 | 0.205757E+11 | 88853.68 | 0.00 | 0.97 | 17-DEC-16:15 | 0.77 | 09-DEC-07:40 | 8718.64 | 31-DEC-16:30 | 8718.64 | 31-DEC-16:30 | 24.07 | 27-DEC-17:03 | 2152.61 | 24-DEC-16:03 | 0.00 |
Annual Sum or Average | 0.160780E+12 | 0.466029E+11 | 8760.00 | 0.160061E+12 | 0.719099E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.472837E+10 | 0.130847E+10 | 672.00 | 0.472783E+10 | 88853.68 | 0.00 | 0.36 | 0.13 | 2888.42 | 2888.42 | 24.07 | 775.95 | 0.00 | ||||||
Maximum of Months | 0.223138E+11 | 0.760902E+10 | 744.00 | 0.221015E+11 | 0.212267E+09 | 0.00 | 1.00 | 0.77 | 8985.53 | 8958.26 | 432.51 | 3658.01 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.293595E+11 | 0.841123E+10 | 743.39 | 0.293537E+11 | 5765646.37 | 0.00 | 0.34 | 26-JAN-17:00 | 0.00 | 17-JAN-07:10 | 26349.74 | 26-JAN-17:00 | 26349.74 | 26-JAN-17:00 | 273.43 | 20-JAN-17:00 | 7108.08 | 26-JAN-17:00 | 0.00 |
February | 0.758155E+11 | 0.200309E+11 | 672.00 | 0.757864E+11 | 29097515.33 | 0.00 | 0.59 | 14-FEB-17:00 | 0.25 | 06-FEB-07:10 | 47260.79 | 15-FEB-17:00 | 47260.79 | 15-FEB-17:00 | 775.98 | 17-FEB-11:10 | 14701.38 | 14-FEB-17:00 | 0.00 |
March | 0.141324E+12 | 0.364048E+11 | 744.00 | 0.141282E+12 | 41627325.52 | 0.00 | 0.83 | 12-MAR-17:21 | 0.52 | 04-MAR-07:05 | 71825.67 | 31-MAR-24:00 | 71825.67 | 31-MAR-24:00 | 993.87 | 20-MAR-16:05 | 20677.48 | 12-MAR-17:03 | 0.00 |
April | 0.191932E+12 | 0.533602E+11 | 720.00 | 0.191929E+12 | 2127759.59 | 0.00 | 1.00 | 01-APR-16:40 | 0.29 | 30-APR-23:52 | 84370.30 | 16-APR-18:22 | 84370.30 | 16-APR-18:22 | 445.32 | 20-APR-09:30 | 29602.65 | 13-APR-17:00 | 0.00 |
May | 0.557337E+11 | 0.170491E+11 | 744.00 | 0.553804E+11 | 0.353329E+09 | 0.00 | 0.50 | 31-MAY-23:40 | 0.15 | 05-MAY-06:05 | 39782.22 | 31-MAY-24:00 | 39782.22 | 31-MAY-24:00 | 2685.50 | 24-MAY-15:50 | 11865.40 | 31-MAY-23:20 | 0.00 |
June | 0.106354E+12 | 0.358771E+11 | 720.00 | 0.105591E+12 | 0.763749E+09 | 0.00 | 0.71 | 30-JUN-23:42 | 0.39 | 09-JUN-06:10 | 58426.37 | 30-JUN-23:53 | 58311.92 | 30-JUN-23:55 | 3093.74 | 30-JUN-14:00 | 23412.18 | 28-JUN-16:00 | 0.00 |
July | 0.161010E+12 | 0.570373E+11 | 744.00 | 0.159056E+12 | 0.195317E+10 | 0.00 | 0.92 | 04-JUL-18:31 | 0.65 | 08-JUL-06:05 | 76435.02 | 31-JUL-23:57 | 76435.02 | 31-JUL-23:57 | 4248.08 | 07-JUL-17:00 | 31066.75 | 21-JUL-18:10 | 0.00 |
August | 0.208533E+12 | 0.714448E+11 | 744.00 | 0.206405E+12 | 0.212798E+10 | 0.00 | 1.00 | 01-AUG-12:50 | 0.30 | 31-AUG-24:00 | 83825.31 | 23-AUG-16:00 | 82796.67 | 30-AUG-18:10 | 4143.04 | 23-AUG-14:00 | 34945.30 | 20-AUG-16:00 | 0.00 |
September | 0.573966E+11 | 0.177548E+11 | 720.00 | 0.560768E+11 | 0.131972E+10 | 0.00 | 0.48 | 30-SEP-24:00 | 0.19 | 09-SEP-06:25 | 39597.45 | 30-SEP-24:00 | 39597.45 | 30-SEP-24:00 | 3001.33 | 05-SEP-14:40 | 11822.45 | 02-SEP-17:31 | 0.00 |
October | 0.994975E+11 | 0.276570E+11 | 744.00 | 0.990218E+11 | 0.475749E+09 | 0.00 | 0.65 | 31-OCT-23:30 | 0.32 | 26-OCT-06:10 | 54703.44 | 31-OCT-24:00 | 54703.44 | 31-OCT-24:00 | 2549.45 | 02-OCT-17:00 | 17438.25 | 05-OCT-17:00 | 0.00 |
November | 0.132993E+12 | 0.332939E+11 | 720.00 | 0.132895E+12 | 98240877.21 | 0.00 | 0.74 | 02-NOV-16:40 | 0.50 | 27-NOV-07:10 | 64477.42 | 02-NOV-16:40 | 63827.10 | 02-NOV-16:40 | 1316.69 | 02-NOV-11:10 | 17244.76 | 02-NOV-16:30 | 0.00 |
December | 0.177579E+12 | 0.436887E+11 | 744.00 | 0.177578E+12 | 1129679.62 | 0.00 | 0.90 | 15-DEC-16:40 | 0.69 | 27-DEC-07:10 | 79283.98 | 29-DEC-16:40 | 79283.98 | 29-DEC-16:40 | 243.01 | 27-DEC-17:03 | 18789.29 | 01-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.143753E+13 | 0.422010E+12 | 8759.39 | 0.143036E+13 | 0.717168E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.293595E+11 | 0.841123E+10 | 672.00 | 0.293537E+11 | 1129679.62 | 0.00 | 0.34 | 0.00 | 26349.74 | 26349.74 | 243.01 | 7108.08 | 0.00 | ||||||
Maximum of Months | 0.208533E+12 | 0.714448E+11 | 744.00 | 0.206405E+12 | 0.212798E+10 | 0.00 | 1.00 | 0.69 | 84370.30 | 84370.30 | 4248.08 | 34945.30 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.141617E+10 | 0.418264E+09 | 517.78 | 0.141567E+10 | 497538.89 | 0.00 | 0.33 | 26-JAN-17:00 | 0.00 | 01-JAN-00:05 | 2563.21 | 26-JAN-17:00 | 2563.21 | 26-JAN-17:00 | 31.54 | 01-JAN-16:42 | 694.36 | 26-JAN-17:00 | 0.00 |
February | 0.622344E+10 | 0.167070E+10 | 671.92 | 0.622063E+10 | 2812106.89 | 0.00 | 0.58 | 14-FEB-17:00 | 0.00 | 05-FEB-22:45 | 4755.08 | 15-FEB-17:00 | 4755.08 | 15-FEB-17:00 | 75.90 | 17-FEB-11:30 | 1481.46 | 14-FEB-17:00 | 0.00 |
March | 0.131758E+11 | 0.343188E+10 | 744.00 | 0.131717E+11 | 4061606.76 | 0.00 | 0.80 | 12-MAR-17:21 | 0.42 | 04-MAR-07:05 | 6823.26 | 31-MAR-23:20 | 6823.26 | 31-MAR-23:20 | 98.17 | 20-MAR-16:05 | 2076.19 | 08-MAR-17:00 | 0.00 |
April | 0.187795E+11 | 0.526400E+10 | 720.00 | 0.187793E+11 | 183763.05 | 0.00 | 1.00 | 01-APR-16:50 | 0.27 | 30-APR-23:54 | 8560.28 | 16-APR-17:51 | 8560.28 | 16-APR-17:51 | 41.47 | 20-APR-09:30 | 3022.73 | 13-APR-17:00 | 0.00 |
May | 0.538992E+10 | 0.166570E+10 | 744.00 | 0.535481E+10 | 35113314.45 | 0.00 | 0.49 | 31-MAY-23:30 | 0.08 | 05-MAY-06:05 | 3938.39 | 31-MAY-24:00 | 3938.39 | 31-MAY-24:00 | 266.08 | 24-MAY-15:50 | 1202.56 | 20-MAY-18:10 | 0.00 |
June | 0.106726E+11 | 0.361772E+10 | 720.00 | 0.105964E+11 | 76218882.71 | 0.00 | 0.72 | 18-JUN-18:35 | 0.33 | 09-JUN-06:10 | 5857.71 | 30-JUN-23:53 | 5846.14 | 30-JUN-23:55 | 311.84 | 30-JUN-14:00 | 2416.01 | 28-JUN-16:00 | 0.00 |
July | 0.162443E+11 | 0.576989E+10 | 744.00 | 0.160491E+11 | 0.195180E+09 | 0.00 | 0.94 | 04-JUL-18:11 | 0.62 | 08-JUL-06:05 | 7640.41 | 31-JUL-23:57 | 7640.41 | 31-JUL-23:57 | 426.63 | 07-JUL-17:00 | 3200.24 | 04-JUL-17:51 | 0.00 |
August | 0.209570E+11 | 0.720388E+10 | 744.00 | 0.207443E+11 | 0.212763E+09 | 0.00 | 1.00 | 01-AUG-13:10 | 0.29 | 31-AUG-24:00 | 8485.45 | 11-AUG-18:20 | 8423.44 | 30-AUG-18:00 | 414.87 | 23-AUG-14:00 | 3569.88 | 20-AUG-16:00 | 0.00 |
September | 0.567190E+10 | 0.176722E+10 | 720.00 | 0.554010E+10 | 0.131802E+09 | 0.00 | 0.47 | 30-SEP-23:40 | 0.15 | 09-SEP-06:55 | 3955.12 | 30-SEP-24:00 | 3955.12 | 30-SEP-24:00 | 302.23 | 05-SEP-14:30 | 1236.85 | 02-SEP-17:31 | 0.00 |
October | 0.933602E+10 | 0.262514E+10 | 744.00 | 0.928862E+10 | 47400074.29 | 0.00 | 0.62 | 31-OCT-23:30 | 0.21 | 26-OCT-06:10 | 5253.21 | 31-OCT-24:00 | 5253.21 | 31-OCT-24:00 | 255.07 | 02-OCT-17:00 | 1774.68 | 06-OCT-16:50 | 0.00 |
November | 0.119608E+11 | 0.303409E+10 | 720.00 | 0.119511E+11 | 9743958.16 | 0.00 | 0.73 | 02-NOV-16:40 | 0.36 | 27-NOV-04:20 | 6444.17 | 02-NOV-16:40 | 6378.81 | 02-NOV-16:40 | 131.73 | 02-NOV-11:10 | 1728.13 | 02-NOV-16:30 | 0.00 |
December | 0.158970E+11 | 0.397059E+10 | 744.00 | 0.158969E+11 | 100157.67 | 0.00 | 0.87 | 13-DEC-16:30 | 0.51 | 26-DEC-04:01 | 7854.47 | 29-DEC-16:50 | 7854.47 | 29-DEC-16:50 | 23.90 | 27-DEC-17:03 | 1863.49 | 01-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.135724E+12 | 0.404391E+11 | 8533.69 | 0.135009E+12 | 0.715875E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.141617E+10 | 0.418264E+09 | 517.78 | 0.141567E+10 | 100157.67 | 0.00 | 0.33 | 0.00 | 2563.21 | 2563.21 | 23.90 | 694.36 | 0.00 | ||||||
Maximum of Months | 0.209570E+11 | 0.720388E+10 | 744.00 | 0.207443E+11 | 0.212763E+09 | 0.00 | 1.00 | 0.62 | 8560.28 | 8560.28 | 426.63 | 3569.88 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.28 | 0.00 | 138.28 | 27.49 | 507.65 | 0.00 | 0.00 | 0.00 |
February | 172.83 | 0.00 | 172.83 | 59.76 | 459.43 | 0.00 | 0.00 | 0.00 |
March | 218.00 | 0.00 | 218.00 | 131.58 | 361.53 | 0.00 | 0.00 | 0.00 |
April | 276.58 | 2.37 | 274.21 | 218.13 | 238.40 | 0.00 | 0.00 | 0.00 |
May | 300.65 | 19.38 | 281.26 | 306.64 | 170.15 | 0.00 | 0.00 | 0.00 |
June | 341.61 | 55.90 | 285.71 | 467.61 | 110.70 | 0.00 | 0.00 | 0.00 |
July | 313.55 | 26.10 | 287.45 | 462.85 | 73.25 | 0.00 | 0.00 | 0.00 |
August | 290.87 | 6.51 | 284.36 | 391.24 | 84.58 | 0.00 | 0.00 | 0.00 |
September | 232.60 | 0.06 | 232.54 | 268.60 | 154.08 | 0.00 | 0.00 | 0.00 |
October | 173.57 | 0.00 | 173.57 | 122.12 | 281.03 | 0.00 | 0.00 | 0.00 |
November | 147.40 | 0.00 | 147.40 | 40.56 | 411.87 | 0.00 | 0.00 | 0.00 |
December | 117.70 | 0.00 | 117.70 | 7.17 | 546.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.17 | 9.21 | 217.96 | 209.43 | 282.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 117.70 | 0.00 | 117.70 | 7.17 | 73.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 341.61 | 55.90 | 287.45 | 467.61 | 546.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.28 | 0.00 | 138.28 | 27.48 | 507.65 | 0.00 | 0.00 | 0.00 |
February | 172.83 | 0.00 | 172.83 | 59.76 | 459.43 | 0.00 | 0.00 | 0.00 |
March | 218.00 | 0.00 | 218.00 | 131.58 | 361.53 | 0.00 | 0.00 | 0.00 |
April | 276.58 | 2.37 | 274.21 | 218.13 | 238.40 | 0.00 | 0.00 | 0.00 |
May | 300.64 | 19.38 | 281.26 | 306.64 | 170.15 | 0.00 | 0.00 | 0.00 |
June | 341.61 | 55.90 | 285.71 | 467.60 | 110.70 | 0.00 | 0.00 | 0.00 |
July | 313.54 | 26.10 | 287.45 | 462.84 | 73.25 | 0.00 | 0.00 | 0.00 |
August | 290.86 | 6.51 | 284.35 | 391.24 | 84.58 | 0.00 | 0.00 | 0.00 |
September | 232.60 | 0.06 | 232.54 | 268.59 | 154.08 | 0.00 | 0.00 | 0.00 |
October | 173.57 | 0.00 | 173.57 | 122.12 | 281.03 | 0.00 | 0.00 | 0.00 |
November | 147.40 | 0.00 | 147.40 | 40.56 | 411.87 | 0.00 | 0.00 | 0.00 |
December | 117.70 | 0.00 | 117.70 | 7.17 | 546.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.17 | 9.21 | 217.96 | 209.43 | 282.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 117.70 | 0.00 | 117.70 | 7.17 | 73.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 341.61 | 55.90 | 287.45 | 467.60 | 546.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.28 | 0.00 | 138.28 | 27.48 | 507.65 | 0.00 | 0.00 | 0.00 |
February | 172.83 | 0.00 | 172.83 | 59.76 | 459.43 | 0.00 | 0.00 | 0.00 |
March | 218.00 | 0.00 | 218.00 | 131.58 | 361.53 | 0.00 | 0.00 | 0.00 |
April | 276.58 | 2.37 | 274.21 | 218.13 | 238.40 | 0.00 | 0.00 | 0.00 |
May | 300.64 | 19.38 | 281.26 | 306.64 | 170.15 | 0.00 | 0.00 | 0.00 |
June | 341.61 | 55.90 | 285.71 | 467.60 | 110.70 | 0.00 | 0.00 | 0.00 |
July | 313.55 | 26.10 | 287.45 | 462.85 | 73.25 | 0.00 | 0.00 | 0.00 |
August | 290.87 | 6.51 | 284.35 | 391.24 | 84.58 | 0.00 | 0.00 | 0.00 |
September | 232.60 | 0.06 | 232.54 | 268.59 | 154.08 | 0.00 | 0.00 | 0.00 |
October | 173.57 | 0.00 | 173.57 | 122.12 | 281.03 | 0.00 | 0.00 | 0.00 |
November | 147.40 | 0.00 | 147.40 | 40.56 | 411.87 | 0.00 | 0.00 | 0.00 |
December | 117.70 | 0.00 | 117.70 | 7.17 | 546.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.17 | 9.21 | 217.96 | 209.43 | 282.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 117.70 | 0.00 | 117.70 | 7.17 | 73.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 341.61 | 55.90 | 287.45 | 467.60 | 546.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.28 | 0.00 | 138.28 | 27.48 | 507.65 | 0.00 | 0.00 | 0.00 |
February | 172.83 | 0.00 | 172.83 | 59.76 | 459.43 | 0.00 | 0.00 | 0.00 |
March | 218.00 | 0.00 | 218.00 | 131.58 | 361.53 | 0.00 | 0.00 | 0.00 |
April | 276.58 | 2.37 | 274.21 | 218.13 | 238.40 | 0.00 | 0.00 | 0.00 |
May | 300.64 | 19.38 | 281.26 | 306.64 | 170.15 | 0.00 | 0.00 | 0.00 |
June | 341.61 | 55.90 | 285.71 | 467.60 | 110.70 | 0.00 | 0.00 | 0.00 |
July | 313.54 | 26.10 | 287.45 | 462.84 | 73.25 | 0.00 | 0.00 | 0.00 |
August | 290.86 | 6.51 | 284.35 | 391.24 | 84.58 | 0.00 | 0.00 | 0.00 |
September | 232.60 | 0.06 | 232.54 | 268.59 | 154.08 | 0.00 | 0.00 | 0.00 |
October | 173.57 | 0.00 | 173.57 | 122.12 | 281.03 | 0.00 | 0.00 | 0.00 |
November | 147.40 | 0.00 | 147.40 | 40.56 | 411.87 | 0.00 | 0.00 | 0.00 |
December | 117.70 | 0.00 | 117.70 | 7.17 | 546.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.17 | 9.21 | 217.96 | 209.43 | 282.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 117.70 | 0.00 | 117.70 | 7.17 | 73.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 341.61 | 55.90 | 287.45 | 467.60 | 546.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.28 | 0.00 | 138.28 | 27.48 | 507.63 | 0.00 | 0.00 | 0.00 |
February | 172.82 | 0.00 | 172.82 | 59.75 | 459.41 | 0.00 | 0.00 | 0.00 |
March | 217.99 | 0.00 | 217.99 | 131.57 | 361.52 | 0.00 | 0.00 | 0.00 |
April | 276.57 | 2.37 | 274.20 | 218.12 | 238.39 | 0.00 | 0.00 | 0.00 |
May | 300.63 | 19.38 | 281.25 | 306.62 | 170.14 | 0.00 | 0.00 | 0.00 |
June | 341.60 | 55.90 | 285.70 | 467.59 | 110.70 | 0.00 | 0.00 | 0.00 |
July | 313.53 | 26.09 | 287.44 | 462.83 | 73.25 | 0.00 | 0.00 | 0.00 |
August | 290.85 | 6.51 | 284.34 | 391.22 | 84.58 | 0.00 | 0.00 | 0.00 |
September | 232.59 | 0.06 | 232.53 | 268.58 | 154.08 | 0.00 | 0.00 | 0.00 |
October | 173.56 | 0.00 | 173.56 | 122.11 | 281.02 | 0.00 | 0.00 | 0.00 |
November | 147.39 | 0.00 | 147.39 | 40.56 | 411.85 | 0.00 | 0.00 | 0.00 |
December | 117.69 | 0.00 | 117.69 | 7.17 | 546.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.16 | 9.21 | 217.95 | 209.42 | 282.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 117.69 | 0.00 | 117.69 | 7.17 | 73.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 341.60 | 55.90 | 287.44 | 467.59 | 546.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 425.52 | 237.90 | 187.61 | 357.67 | 511.74 | 0.00 | 0.00 | 0.00 |
February | 516.99 | 278.72 | 238.28 | 478.05 | 465.24 | 0.00 | 0.00 | 0.00 |
March | 681.99 | 387.70 | 294.29 | 715.84 | 365.53 | 0.00 | 0.00 | 0.00 |
April | 931.74 | 530.81 | 400.93 | 1078.52 | 246.37 | 0.00 | 0.00 | 0.00 |
May | 889.08 | 506.68 | 382.40 | 1087.30 | 189.52 | 0.00 | 0.00 | 0.00 |
June | 958.50 | 590.48 | 368.02 | 1287.36 | 117.37 | 0.00 | 0.00 | 0.00 |
July | 886.91 | 507.17 | 379.74 | 1241.95 | 74.61 | 0.00 | 0.00 | 0.00 |
August | 877.66 | 483.87 | 393.79 | 1193.94 | 82.43 | 0.00 | 0.00 | 0.00 |
September | 730.51 | 408.72 | 321.78 | 939.02 | 161.38 | 0.00 | 0.00 | 0.00 |
October | 635.31 | 403.08 | 232.23 | 719.38 | 284.37 | 0.00 | 0.00 | 0.00 |
November | 496.53 | 291.91 | 204.62 | 472.97 | 414.86 | 0.00 | 0.00 | 0.00 |
December | 402.33 | 244.85 | 157.48 | 340.11 | 542.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.44 | 406.50 | 296.95 | 827.57 | 287.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 402.33 | 237.90 | 157.48 | 340.11 | 74.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 958.50 | 590.48 | 400.93 | 1287.36 | 542.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 425.52 | 237.90 | 187.61 | 357.67 | 511.74 | 0.00 | 0.00 | 0.00 |
February | 516.99 | 278.72 | 238.28 | 478.05 | 465.24 | 0.00 | 0.00 | 0.00 |
March | 681.99 | 387.70 | 294.29 | 715.84 | 365.53 | 0.00 | 0.00 | 0.00 |
April | 931.74 | 530.81 | 400.93 | 1078.52 | 246.37 | 0.00 | 0.00 | 0.00 |
May | 889.08 | 506.68 | 382.40 | 1087.30 | 189.52 | 0.00 | 0.00 | 0.00 |
June | 958.50 | 590.48 | 368.02 | 1287.36 | 117.37 | 0.00 | 0.00 | 0.00 |
July | 886.91 | 507.17 | 379.74 | 1241.95 | 74.61 | 0.00 | 0.00 | 0.00 |
August | 877.66 | 483.87 | 393.79 | 1193.94 | 82.43 | 0.00 | 0.00 | 0.00 |
September | 730.51 | 408.72 | 321.78 | 939.02 | 161.38 | 0.00 | 0.00 | 0.00 |
October | 635.31 | 403.08 | 232.23 | 719.38 | 284.37 | 0.00 | 0.00 | 0.00 |
November | 496.53 | 291.91 | 204.62 | 472.97 | 414.86 | 0.00 | 0.00 | 0.00 |
December | 402.33 | 244.85 | 157.48 | 340.11 | 542.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.44 | 406.50 | 296.95 | 827.57 | 287.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 402.33 | 237.90 | 157.48 | 340.11 | 74.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 958.50 | 590.48 | 400.93 | 1287.36 | 542.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 425.51 | 237.90 | 187.61 | 357.67 | 511.73 | 0.00 | 0.00 | 0.00 |
February | 516.98 | 278.71 | 238.27 | 478.04 | 465.24 | 0.00 | 0.00 | 0.00 |
March | 681.98 | 387.69 | 294.29 | 715.82 | 365.52 | 0.00 | 0.00 | 0.00 |
April | 931.73 | 530.80 | 400.93 | 1078.50 | 246.36 | 0.00 | 0.00 | 0.00 |
May | 889.06 | 506.67 | 382.39 | 1087.28 | 189.51 | 0.00 | 0.00 | 0.00 |
June | 958.48 | 590.47 | 368.01 | 1287.33 | 117.37 | 0.00 | 0.00 | 0.00 |
July | 886.90 | 507.16 | 379.73 | 1241.92 | 74.61 | 0.00 | 0.00 | 0.00 |
August | 877.64 | 483.86 | 393.78 | 1193.91 | 82.43 | 0.00 | 0.00 | 0.00 |
September | 730.49 | 408.72 | 321.78 | 939.01 | 161.37 | 0.00 | 0.00 | 0.00 |
October | 635.30 | 403.08 | 232.23 | 719.37 | 284.36 | 0.00 | 0.00 | 0.00 |
November | 496.52 | 291.90 | 204.62 | 472.96 | 414.85 | 0.00 | 0.00 | 0.00 |
December | 402.32 | 244.85 | 157.47 | 340.10 | 542.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.43 | 406.49 | 296.94 | 827.55 | 287.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 402.32 | 237.90 | 157.47 | 340.10 | 74.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 958.48 | 590.47 | 400.93 | 1287.33 | 542.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1022.31 | 795.50 | 226.81 | 1145.59 | 458.28 | 0.00 | 0.00 | 0.00 |
February | 1000.47 | 730.81 | 269.66 | 1145.15 | 425.49 | 0.00 | 0.00 | 0.00 |
March | 737.25 | 445.71 | 291.54 | 862.36 | 347.60 | 0.00 | 0.00 | 0.00 |
April | 574.96 | 236.01 | 338.95 | 698.69 | 247.36 | 0.00 | 0.00 | 0.00 |
May | 383.45 | 84.35 | 299.10 | 471.08 | 179.75 | 0.00 | 0.00 | 0.00 |
June | 324.37 | 39.97 | 284.40 | 466.18 | 116.31 | 0.00 | 0.00 | 0.00 |
July | 358.93 | 57.32 | 301.61 | 556.89 | 75.90 | 0.00 | 0.00 | 0.00 |
August | 493.55 | 160.43 | 333.13 | 732.42 | 89.63 | 0.00 | 0.00 | 0.00 |
September | 682.48 | 380.57 | 301.91 | 943.08 | 159.94 | 0.00 | 0.00 | 0.00 |
October | 933.71 | 687.67 | 246.04 | 1164.42 | 269.35 | 0.00 | 0.00 | 0.00 |
November | 1039.97 | 798.18 | 241.80 | 1200.53 | 377.15 | 0.00 | 0.00 | 0.00 |
December | 1109.18 | 914.96 | 194.22 | 1250.17 | 478.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 720.16 | 442.82 | 277.34 | 884.90 | 267.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 324.37 | 39.97 | 194.22 | 466.18 | 75.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1109.18 | 914.96 | 338.95 | 1250.17 | 478.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1022.31 | 795.49 | 226.81 | 1145.58 | 458.28 | 0.00 | 0.00 | 0.00 |
February | 1000.47 | 730.80 | 269.66 | 1145.14 | 425.49 | 0.00 | 0.00 | 0.00 |
March | 737.24 | 445.71 | 291.54 | 862.35 | 347.60 | 0.00 | 0.00 | 0.00 |
April | 574.96 | 236.01 | 338.95 | 698.68 | 247.36 | 0.00 | 0.00 | 0.00 |
May | 383.45 | 84.35 | 299.10 | 471.07 | 179.75 | 0.00 | 0.00 | 0.00 |
June | 324.37 | 39.97 | 284.39 | 466.18 | 116.31 | 0.00 | 0.00 | 0.00 |
July | 358.93 | 57.32 | 301.61 | 556.89 | 75.90 | 0.00 | 0.00 | 0.00 |
August | 493.55 | 160.43 | 333.12 | 732.42 | 89.63 | 0.00 | 0.00 | 0.00 |
September | 682.47 | 380.56 | 301.91 | 943.07 | 159.94 | 0.00 | 0.00 | 0.00 |
October | 933.70 | 687.67 | 246.04 | 1164.41 | 269.35 | 0.00 | 0.00 | 0.00 |
November | 1039.97 | 798.17 | 241.80 | 1200.52 | 377.15 | 0.00 | 0.00 | 0.00 |
December | 1109.17 | 914.95 | 194.22 | 1250.16 | 478.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 720.15 | 442.81 | 277.34 | 884.90 | 267.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 324.37 | 39.97 | 194.22 | 466.18 | 75.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1109.17 | 914.95 | 338.95 | 1250.16 | 478.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1022.31 | 795.50 | 226.81 | 1145.59 | 458.28 | 0.00 | 0.00 | 0.00 |
February | 1000.47 | 730.81 | 269.66 | 1145.15 | 425.49 | 0.00 | 0.00 | 0.00 |
March | 737.25 | 445.71 | 291.54 | 862.36 | 347.60 | 0.00 | 0.00 | 0.00 |
April | 574.96 | 236.01 | 338.95 | 698.69 | 247.36 | 0.00 | 0.00 | 0.00 |
May | 383.45 | 84.35 | 299.10 | 471.08 | 179.75 | 0.00 | 0.00 | 0.00 |
June | 324.37 | 39.97 | 284.40 | 466.18 | 116.31 | 0.00 | 0.00 | 0.00 |
July | 358.93 | 57.32 | 301.61 | 556.89 | 75.90 | 0.00 | 0.00 | 0.00 |
August | 493.55 | 160.43 | 333.13 | 732.42 | 89.63 | 0.00 | 0.00 | 0.00 |
September | 682.48 | 380.57 | 301.91 | 943.08 | 159.94 | 0.00 | 0.00 | 0.00 |
October | 933.71 | 687.67 | 246.04 | 1164.42 | 269.35 | 0.00 | 0.00 | 0.00 |
November | 1039.97 | 798.18 | 241.80 | 1200.53 | 377.15 | 0.00 | 0.00 | 0.00 |
December | 1109.18 | 914.96 | 194.22 | 1250.17 | 478.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 720.16 | 442.82 | 277.34 | 884.90 | 267.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 324.37 | 39.97 | 194.22 | 466.18 | 75.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1109.18 | 914.96 | 338.95 | 1250.17 | 478.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1022.31 | 795.49 | 226.81 | 1145.58 | 458.28 | 0.00 | 0.00 | 0.00 |
February | 1000.47 | 730.80 | 269.66 | 1145.14 | 425.49 | 0.00 | 0.00 | 0.00 |
March | 737.24 | 445.71 | 291.54 | 862.35 | 347.60 | 0.00 | 0.00 | 0.00 |
April | 574.96 | 236.01 | 338.95 | 698.68 | 247.36 | 0.00 | 0.00 | 0.00 |
May | 383.45 | 84.35 | 299.10 | 471.07 | 179.75 | 0.00 | 0.00 | 0.00 |
June | 324.37 | 39.97 | 284.39 | 466.18 | 116.31 | 0.00 | 0.00 | 0.00 |
July | 358.93 | 57.32 | 301.61 | 556.89 | 75.90 | 0.00 | 0.00 | 0.00 |
August | 493.55 | 160.43 | 333.12 | 732.42 | 89.63 | 0.00 | 0.00 | 0.00 |
September | 682.47 | 380.56 | 301.91 | 943.07 | 159.94 | 0.00 | 0.00 | 0.00 |
October | 933.70 | 687.67 | 246.04 | 1164.41 | 269.35 | 0.00 | 0.00 | 0.00 |
November | 1039.97 | 798.17 | 241.80 | 1200.52 | 377.15 | 0.00 | 0.00 | 0.00 |
December | 1109.17 | 914.95 | 194.22 | 1250.16 | 478.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 720.15 | 442.81 | 277.34 | 884.90 | 267.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 324.37 | 39.97 | 194.22 | 466.18 | 75.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1109.17 | 914.95 | 338.95 | 1250.16 | 478.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1022.27 | 795.46 | 226.80 | 1145.54 | 458.26 | 0.00 | 0.00 | 0.00 |
February | 1000.43 | 730.78 | 269.65 | 1145.10 | 425.47 | 0.00 | 0.00 | 0.00 |
March | 737.22 | 445.69 | 291.53 | 862.32 | 347.58 | 0.00 | 0.00 | 0.00 |
April | 574.94 | 236.00 | 338.94 | 698.66 | 247.35 | 0.00 | 0.00 | 0.00 |
May | 383.44 | 84.35 | 299.09 | 471.05 | 179.74 | 0.00 | 0.00 | 0.00 |
June | 324.36 | 39.97 | 284.38 | 466.16 | 116.30 | 0.00 | 0.00 | 0.00 |
July | 358.92 | 57.31 | 301.60 | 556.87 | 75.90 | 0.00 | 0.00 | 0.00 |
August | 493.53 | 160.42 | 333.11 | 732.39 | 89.62 | 0.00 | 0.00 | 0.00 |
September | 682.45 | 380.55 | 301.90 | 943.04 | 159.93 | 0.00 | 0.00 | 0.00 |
October | 933.67 | 687.64 | 246.03 | 1164.37 | 269.34 | 0.00 | 0.00 | 0.00 |
November | 1039.93 | 798.14 | 241.79 | 1200.48 | 377.13 | 0.00 | 0.00 | 0.00 |
December | 1109.13 | 914.92 | 194.22 | 1250.12 | 478.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 720.12 | 442.80 | 277.33 | 884.86 | 267.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 324.36 | 39.97 | 194.22 | 466.16 | 75.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1109.13 | 914.92 | 338.94 | 1250.12 | 478.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 438.90 | 250.29 | 188.61 | 403.05 | 567.12 | 0.00 | 0.00 | 0.00 |
February | 565.02 | 326.39 | 238.62 | 554.79 | 529.91 | 0.00 | 0.00 | 0.00 |
March | 631.06 | 335.93 | 295.13 | 654.40 | 432.09 | 0.00 | 0.00 | 0.00 |
April | 805.42 | 428.65 | 376.77 | 901.03 | 307.53 | 0.00 | 0.00 | 0.00 |
May | 763.66 | 393.49 | 370.17 | 920.19 | 215.56 | 0.00 | 0.00 | 0.00 |
June | 818.64 | 456.79 | 361.85 | 1100.06 | 150.21 | 0.00 | 0.00 | 0.00 |
July | 738.39 | 361.36 | 377.03 | 1033.20 | 102.57 | 0.00 | 0.00 | 0.00 |
August | 754.50 | 348.99 | 405.51 | 1013.88 | 128.31 | 0.00 | 0.00 | 0.00 |
September | 681.49 | 358.91 | 322.58 | 878.85 | 190.12 | 0.00 | 0.00 | 0.00 |
October | 623.47 | 387.51 | 235.96 | 715.09 | 337.03 | 0.00 | 0.00 | 0.00 |
November | 489.42 | 287.94 | 201.48 | 470.43 | 480.79 | 0.00 | 0.00 | 0.00 |
December | 423.25 | 265.42 | 157.83 | 373.41 | 633.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 644.49 | 349.97 | 294.52 | 752.21 | 338.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 423.25 | 250.29 | 157.83 | 373.41 | 102.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 818.64 | 456.79 | 405.51 | 1100.06 | 633.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 438.90 | 250.29 | 188.61 | 403.05 | 567.12 | 0.00 | 0.00 | 0.00 |
February | 565.02 | 326.39 | 238.62 | 554.79 | 529.91 | 0.00 | 0.00 | 0.00 |
March | 631.06 | 335.93 | 295.13 | 654.40 | 432.09 | 0.00 | 0.00 | 0.00 |
April | 805.42 | 428.65 | 376.77 | 901.03 | 307.53 | 0.00 | 0.00 | 0.00 |
May | 763.66 | 393.49 | 370.17 | 920.19 | 215.56 | 0.00 | 0.00 | 0.00 |
June | 818.64 | 456.79 | 361.85 | 1100.06 | 150.21 | 0.00 | 0.00 | 0.00 |
July | 738.39 | 361.36 | 377.03 | 1033.20 | 102.57 | 0.00 | 0.00 | 0.00 |
August | 754.50 | 348.99 | 405.51 | 1013.88 | 128.31 | 0.00 | 0.00 | 0.00 |
September | 681.49 | 358.91 | 322.58 | 878.85 | 190.12 | 0.00 | 0.00 | 0.00 |
October | 623.47 | 387.51 | 235.96 | 715.09 | 337.03 | 0.00 | 0.00 | 0.00 |
November | 489.42 | 287.94 | 201.48 | 470.43 | 480.79 | 0.00 | 0.00 | 0.00 |
December | 423.25 | 265.42 | 157.83 | 373.41 | 633.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 644.49 | 349.97 | 294.52 | 752.21 | 338.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 423.25 | 250.29 | 157.83 | 373.41 | 102.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 818.64 | 456.79 | 405.51 | 1100.06 | 633.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 438.90 | 250.29 | 188.61 | 403.05 | 567.11 | 0.00 | 0.00 | 0.00 |
February | 565.01 | 326.39 | 238.62 | 554.78 | 529.90 | 0.00 | 0.00 | 0.00 |
March | 631.05 | 335.92 | 295.13 | 654.39 | 432.09 | 0.00 | 0.00 | 0.00 |
April | 805.41 | 428.64 | 376.77 | 901.01 | 307.52 | 0.00 | 0.00 | 0.00 |
May | 763.64 | 393.48 | 370.16 | 920.17 | 215.56 | 0.00 | 0.00 | 0.00 |
June | 818.62 | 456.78 | 361.84 | 1100.04 | 150.21 | 0.00 | 0.00 | 0.00 |
July | 738.37 | 361.35 | 377.02 | 1033.18 | 102.57 | 0.00 | 0.00 | 0.00 |
August | 754.49 | 348.98 | 405.51 | 1013.86 | 128.31 | 0.00 | 0.00 | 0.00 |
September | 681.48 | 358.91 | 322.57 | 878.84 | 190.11 | 0.00 | 0.00 | 0.00 |
October | 623.46 | 387.50 | 235.96 | 715.08 | 337.02 | 0.00 | 0.00 | 0.00 |
November | 489.41 | 287.93 | 201.48 | 470.43 | 480.78 | 0.00 | 0.00 | 0.00 |
December | 423.24 | 265.42 | 157.82 | 373.40 | 633.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 644.48 | 349.97 | 294.51 | 752.19 | 338.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 423.24 | 250.29 | 157.82 | 373.40 | 102.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 818.62 | 456.78 | 405.51 | 1100.04 | 633.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 691.42 | 0.00 | 691.42 | 187.42 | 2314.77 | 0.00 | 0.00 | 0.00 |
February | 864.15 | 0.00 | 864.15 | 362.04 | 2092.78 | 0.00 | 0.00 | 0.00 |
March | 1090.02 | 0.00 | 1090.02 | 721.60 | 1650.93 | 0.00 | 0.00 | 0.00 |
April | 1382.90 | 11.84 | 1371.06 | 1140.20 | 1103.10 | 0.00 | 0.00 | 0.00 |
May | 1503.22 | 96.92 | 1406.31 | 1554.44 | 812.34 | 0.00 | 0.00 | 0.00 |
June | 1708.07 | 279.52 | 1428.54 | 2351.35 | 543.00 | 0.00 | 0.00 | 0.00 |
July | 1567.74 | 130.48 | 1437.25 | 2326.95 | 369.15 | 0.00 | 0.00 | 0.00 |
August | 1454.34 | 32.56 | 1421.78 | 1980.17 | 416.26 | 0.00 | 0.00 | 0.00 |
September | 1163.02 | 0.30 | 1162.72 | 1361.04 | 732.40 | 0.00 | 0.00 | 0.00 |
October | 867.85 | 0.00 | 867.85 | 653.55 | 1286.89 | 0.00 | 0.00 | 0.00 |
November | 737.01 | 0.00 | 737.01 | 259.08 | 1833.06 | 0.00 | 0.00 | 0.00 |
December | 588.50 | 0.00 | 588.50 | 68.59 | 2418.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1135.84 | 46.05 | 1089.79 | 1084.28 | 1293.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 588.50 | 0.00 | 588.50 | 68.59 | 369.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1708.07 | 279.52 | 1437.25 | 2351.35 | 2418.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1276.54 | 713.70 | 562.83 | 1104.99 | 1431.91 | 0.00 | 0.00 | 0.00 |
February | 1550.97 | 836.14 | 714.83 | 1461.65 | 1306.71 | 0.00 | 0.00 | 0.00 |
March | 2045.96 | 1163.09 | 882.87 | 2158.63 | 1039.02 | 0.00 | 0.00 | 0.00 |
April | 2795.20 | 1592.41 | 1202.79 | 3223.50 | 728.69 | 0.00 | 0.00 | 0.00 |
May | 2667.21 | 1520.02 | 1147.19 | 3248.27 | 553.68 | 0.00 | 0.00 | 0.00 |
June | 2875.46 | 1771.42 | 1104.04 | 3845.27 | 357.61 | 0.00 | 0.00 | 0.00 |
July | 2660.71 | 1521.50 | 1139.21 | 3705.99 | 247.85 | 0.00 | 0.00 | 0.00 |
August | 2632.96 | 1451.60 | 1181.36 | 3560.69 | 278.66 | 0.00 | 0.00 | 0.00 |
September | 2191.49 | 1226.16 | 965.33 | 2809.54 | 470.99 | 0.00 | 0.00 | 0.00 |
October | 1905.93 | 1209.24 | 696.69 | 2163.84 | 810.66 | 0.00 | 0.00 | 0.00 |
November | 1489.58 | 875.71 | 613.87 | 1439.54 | 1156.43 | 0.00 | 0.00 | 0.00 |
December | 1206.98 | 734.56 | 472.42 | 1045.66 | 1504.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2110.31 | 1219.47 | 890.84 | 2485.18 | 821.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1206.98 | 713.70 | 472.42 | 1045.66 | 247.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2875.46 | 1771.42 | 1202.79 | 3845.27 | 1504.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5111.66 | 3977.58 | 1134.08 | 5701.53 | 2251.44 | 0.00 | 0.00 | 0.00 |
February | 5002.46 | 3654.13 | 1348.33 | 5700.43 | 2080.75 | 0.00 | 0.00 | 0.00 |
March | 3686.30 | 2228.59 | 1457.71 | 4298.27 | 1686.63 | 0.00 | 0.00 | 0.00 |
April | 2874.84 | 1180.07 | 1694.77 | 3489.64 | 1198.02 | 0.00 | 0.00 | 0.00 |
May | 1917.28 | 421.77 | 1495.52 | 2355.11 | 872.53 | 0.00 | 0.00 | 0.00 |
June | 1621.86 | 199.88 | 1421.98 | 2343.87 | 571.36 | 0.00 | 0.00 | 0.00 |
July | 1794.67 | 286.59 | 1508.08 | 2790.90 | 387.11 | 0.00 | 0.00 | 0.00 |
August | 2467.80 | 802.16 | 1665.64 | 3663.74 | 454.37 | 0.00 | 0.00 | 0.00 |
September | 3412.44 | 1902.88 | 1509.56 | 4691.83 | 788.83 | 0.00 | 0.00 | 0.00 |
October | 4668.63 | 3438.42 | 1230.21 | 5793.19 | 1325.48 | 0.00 | 0.00 | 0.00 |
November | 5199.97 | 3990.96 | 1209.01 | 5979.65 | 1837.42 | 0.00 | 0.00 | 0.00 |
December | 5546.01 | 4574.88 | 971.13 | 6234.89 | 2310.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3600.84 | 2214.13 | 1386.70 | 4412.95 | 1309.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1621.86 | 199.88 | 971.13 | 2343.87 | 387.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5546.01 | 4574.88 | 1694.77 | 6234.89 | 2310.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1316.70 | 750.87 | 565.83 | 1243.93 | 1556.78 | 0.00 | 0.00 | 0.00 |
February | 1695.03 | 979.17 | 715.86 | 1711.31 | 1427.24 | 0.00 | 0.00 | 0.00 |
March | 1893.16 | 1007.77 | 885.39 | 2022.83 | 1141.28 | 0.00 | 0.00 | 0.00 |
April | 2416.24 | 1285.93 | 1130.31 | 2763.57 | 809.98 | 0.00 | 0.00 | 0.00 |
May | 2290.95 | 1180.46 | 1110.49 | 2779.95 | 602.89 | 0.00 | 0.00 | 0.00 |
June | 2455.89 | 1370.36 | 1085.53 | 3324.50 | 420.62 | 0.00 | 0.00 | 0.00 |
July | 2215.14 | 1084.06 | 1131.08 | 3130.47 | 282.78 | 0.00 | 0.00 | 0.00 |
August | 2263.48 | 1046.95 | 1216.53 | 3094.68 | 325.46 | 0.00 | 0.00 | 0.00 |
September | 2044.45 | 1076.73 | 967.72 | 2655.67 | 527.70 | 0.00 | 0.00 | 0.00 |
October | 1870.40 | 1162.52 | 707.88 | 2184.59 | 903.91 | 0.00 | 0.00 | 0.00 |
November | 1468.25 | 863.81 | 604.45 | 1468.77 | 1241.37 | 0.00 | 0.00 | 0.00 |
December | 1269.74 | 796.26 | 473.48 | 1172.92 | 1605.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1933.46 | 1049.91 | 883.55 | 2298.09 | 901.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1269.74 | 750.87 | 473.48 | 1172.92 | 282.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2455.89 | 1370.36 | 1216.53 | 3324.50 | 1605.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 691.42 | 0.00 | 691.42 | 221.52 | 2145.22 | 0.00 | 0.00 | 0.00 |
February | 864.15 | 0.00 | 864.15 | 399.50 | 1950.00 | 0.00 | 0.00 | 0.00 |
March | 1090.02 | 0.00 | 1090.02 | 762.34 | 1539.10 | 0.00 | 0.00 | 0.00 |
April | 1382.90 | 11.84 | 1371.06 | 1166.06 | 1043.00 | 0.00 | 0.00 | 0.00 |
May | 1503.22 | 96.92 | 1406.31 | 1564.19 | 786.32 | 0.00 | 0.00 | 0.00 |
June | 1708.07 | 279.52 | 1428.54 | 2341.47 | 539.47 | 0.00 | 0.00 | 0.00 |
July | 1567.74 | 130.48 | 1437.25 | 2307.65 | 374.60 | 0.00 | 0.00 | 0.00 |
August | 1454.34 | 32.56 | 1421.78 | 1966.00 | 417.29 | 0.00 | 0.00 | 0.00 |
September | 1163.02 | 0.30 | 1162.72 | 1361.03 | 714.74 | 0.00 | 0.00 | 0.00 |
October | 867.85 | 0.00 | 867.85 | 679.10 | 1202.71 | 0.00 | 0.00 | 0.00 |
November | 737.01 | 0.00 | 737.01 | 298.78 | 1677.74 | 0.00 | 0.00 | 0.00 |
December | 588.50 | 0.00 | 588.50 | 89.57 | 2231.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1135.84 | 46.05 | 1089.79 | 1100.02 | 1214.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 588.50 | 0.00 | 588.50 | 89.57 | 374.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1708.07 | 279.52 | 1437.25 | 2341.47 | 2231.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1276.54 | 713.70 | 562.83 | 1143.61 | 1335.48 | 0.00 | 0.00 | 0.00 |
February | 1550.97 | 836.14 | 714.83 | 1494.33 | 1226.65 | 0.00 | 0.00 | 0.00 |
March | 2045.96 | 1163.09 | 882.87 | 2178.72 | 985.35 | 0.00 | 0.00 | 0.00 |
April | 2795.20 | 1592.41 | 1202.79 | 3226.63 | 704.57 | 0.00 | 0.00 | 0.00 |
May | 2667.21 | 1520.02 | 1147.19 | 3242.35 | 544.36 | 0.00 | 0.00 | 0.00 |
June | 2875.46 | 1771.42 | 1104.04 | 3831.24 | 359.32 | 0.00 | 0.00 | 0.00 |
July | 2660.71 | 1521.50 | 1139.21 | 3688.64 | 254.25 | 0.00 | 0.00 | 0.00 |
August | 2632.96 | 1451.60 | 1181.36 | 3545.79 | 282.96 | 0.00 | 0.00 | 0.00 |
September | 2191.49 | 1226.16 | 965.33 | 2802.49 | 468.68 | 0.00 | 0.00 | 0.00 |
October | 1905.93 | 1209.24 | 696.69 | 2172.99 | 776.19 | 0.00 | 0.00 | 0.00 |
November | 1489.58 | 875.71 | 613.87 | 1473.02 | 1075.64 | 0.00 | 0.00 | 0.00 |
December | 1206.98 | 734.56 | 472.42 | 1076.11 | 1395.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2110.31 | 1219.47 | 890.84 | 2494.07 | 781.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1206.98 | 713.70 | 472.42 | 1076.11 | 254.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2875.46 | 1771.42 | 1202.79 | 3831.24 | 1395.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5111.66 | 3977.58 | 1134.08 | 5756.20 | 2098.80 | 0.00 | 0.00 | 0.00 |
February | 5002.46 | 3654.13 | 1348.33 | 5741.80 | 1949.35 | 0.00 | 0.00 | 0.00 |
March | 3686.30 | 2228.59 | 1457.71 | 4326.31 | 1593.34 | 0.00 | 0.00 | 0.00 |
April | 2874.84 | 1180.07 | 1694.77 | 3499.40 | 1145.75 | 0.00 | 0.00 | 0.00 |
May | 1917.28 | 421.77 | 1495.52 | 2356.84 | 846.40 | 0.00 | 0.00 | 0.00 |
June | 1621.86 | 199.88 | 1421.98 | 2333.04 | 566.03 | 0.00 | 0.00 | 0.00 |
July | 1794.67 | 286.59 | 1508.08 | 2771.23 | 392.54 | 0.00 | 0.00 | 0.00 |
August | 2467.80 | 802.16 | 1665.64 | 3645.81 | 456.58 | 0.00 | 0.00 | 0.00 |
September | 3412.44 | 1902.88 | 1509.56 | 4682.87 | 778.96 | 0.00 | 0.00 | 0.00 |
October | 4668.63 | 3438.42 | 1230.21 | 5809.14 | 1267.12 | 0.00 | 0.00 | 0.00 |
November | 5199.97 | 3990.96 | 1209.01 | 6024.44 | 1712.75 | 0.00 | 0.00 | 0.00 |
December | 5546.01 | 4574.88 | 971.13 | 6279.64 | 2143.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3600.84 | 2214.13 | 1386.70 | 4428.12 | 1242.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1621.86 | 199.88 | 971.13 | 2333.04 | 392.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5546.01 | 4574.88 | 1694.77 | 6279.64 | 2143.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1316.70 | 750.87 | 565.83 | 1262.98 | 1461.14 | 0.00 | 0.00 | 0.00 |
February | 1695.03 | 979.17 | 715.86 | 1726.39 | 1348.44 | 0.00 | 0.00 | 0.00 |
March | 1893.16 | 1007.77 | 885.39 | 2035.24 | 1084.21 | 0.00 | 0.00 | 0.00 |
April | 2416.24 | 1285.93 | 1130.31 | 2767.90 | 779.63 | 0.00 | 0.00 | 0.00 |
May | 2290.95 | 1180.46 | 1110.49 | 2778.90 | 588.51 | 0.00 | 0.00 | 0.00 |
June | 2455.89 | 1370.36 | 1085.53 | 3315.50 | 418.56 | 0.00 | 0.00 | 0.00 |
July | 2215.14 | 1084.06 | 1131.08 | 3117.15 | 285.21 | 0.00 | 0.00 | 0.00 |
August | 2263.48 | 1046.95 | 1216.53 | 3083.96 | 326.31 | 0.00 | 0.00 | 0.00 |
September | 2044.45 | 1076.73 | 967.72 | 2651.27 | 521.44 | 0.00 | 0.00 | 0.00 |
October | 1870.40 | 1162.52 | 707.88 | 2189.98 | 864.27 | 0.00 | 0.00 | 0.00 |
November | 1468.25 | 863.81 | 604.45 | 1485.27 | 1161.23 | 0.00 | 0.00 | 0.00 |
December | 1269.74 | 796.26 | 473.48 | 1186.10 | 1501.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1933.46 | 1049.91 | 883.55 | 2301.97 | 859.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1269.74 | 750.87 | 473.48 | 1186.10 | 285.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2455.89 | 1370.36 | 1216.53 | 3315.50 | 1501.46 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370379E+09 | 0.00 | 0.370379E+09 | 73617836.77 | 0.135968E+10 |
February | 0.418114E+09 | 0.00 | 0.418114E+09 | 0.144567E+09 | 0.111144E+10 |
March | 0.583904E+09 | 0.00 | 0.583904E+09 | 0.352423E+09 | 0.968328E+09 |
April | 0.716896E+09 | 6137711.37 | 0.710759E+09 | 0.565396E+09 | 0.617926E+09 |
May | 0.805248E+09 | 51916540.85 | 0.753331E+09 | 0.821306E+09 | 0.455726E+09 |
June | 0.885463E+09 | 0.144903E+09 | 0.740560E+09 | 0.121204E+10 | 0.286936E+09 |
July | 0.839807E+09 | 69896590.08 | 0.769910E+09 | 0.123969E+10 | 0.196194E+09 |
August | 0.779061E+09 | 17441368.69 | 0.761620E+09 | 0.104791E+10 | 0.226547E+09 |
September | 0.602911E+09 | 154736.52 | 0.602756E+09 | 0.696202E+09 | 0.399387E+09 |
October | 0.464889E+09 | 0.00 | 0.464889E+09 | 0.327079E+09 | 0.752710E+09 |
November | 0.382065E+09 | 0.00 | 0.382065E+09 | 0.105129E+09 | 0.106757E+10 |
December | 0.315248E+09 | 0.00 | 0.315248E+09 | 19200277.58 | 0.146383E+10 |
Annual Sum or Average | 0.716399E+10 | 0.290450E+09 | 0.687354E+10 | 0.660456E+10 | 0.890628E+10 |
Minimum of Months | 0.315248E+09 | 0.00 | 0.315248E+09 | 19200277.58 | 0.196194E+09 |
Maximum of Months | 0.885463E+09 | 0.144903E+09 | 0.769910E+09 | 0.123969E+10 | 0.146383E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370374E+09 | 0.00 | 0.370374E+09 | 73614722.86 | 0.135968E+10 |
February | 0.418108E+09 | 0.00 | 0.418108E+09 | 0.144563E+09 | 0.111144E+10 |
March | 0.583897E+09 | 0.00 | 0.583897E+09 | 0.352416E+09 | 0.968326E+09 |
April | 0.716888E+09 | 6137576.44 | 0.710750E+09 | 0.565387E+09 | 0.617924E+09 |
May | 0.805238E+09 | 51915399.52 | 0.753323E+09 | 0.821295E+09 | 0.455724E+09 |
June | 0.885451E+09 | 0.144900E+09 | 0.740551E+09 | 0.121203E+10 | 0.286935E+09 |
July | 0.839797E+09 | 69895053.49 | 0.769902E+09 | 0.123968E+10 | 0.196193E+09 |
August | 0.779052E+09 | 17440985.27 | 0.761611E+09 | 0.104789E+10 | 0.226546E+09 |
September | 0.602904E+09 | 154733.12 | 0.602749E+09 | 0.696194E+09 | 0.399385E+09 |
October | 0.464884E+09 | 0.00 | 0.464884E+09 | 0.327075E+09 | 0.752708E+09 |
November | 0.382060E+09 | 0.00 | 0.382060E+09 | 0.105126E+09 | 0.106757E+10 |
December | 0.315245E+09 | 0.00 | 0.315245E+09 | 19198965.63 | 0.146383E+10 |
Annual Sum or Average | 0.716390E+10 | 0.290444E+09 | 0.687345E+10 | 0.660447E+10 | 0.890626E+10 |
Minimum of Months | 0.315245E+09 | 0.00 | 0.315245E+09 | 19198965.63 | 0.196193E+09 |
Maximum of Months | 0.885451E+09 | 0.144900E+09 | 0.769902E+09 | 0.123968E+10 | 0.146383E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370376E+09 | 0.00 | 0.370376E+09 | 73615760.83 | 0.135968E+10 |
February | 0.418110E+09 | 0.00 | 0.418110E+09 | 0.144564E+09 | 0.111144E+10 |
March | 0.583899E+09 | 0.00 | 0.583899E+09 | 0.352419E+09 | 0.968327E+09 |
April | 0.716891E+09 | 6137621.42 | 0.710753E+09 | 0.565390E+09 | 0.617925E+09 |
May | 0.805241E+09 | 51915779.97 | 0.753326E+09 | 0.821298E+09 | 0.455724E+09 |
June | 0.885455E+09 | 0.144901E+09 | 0.740554E+09 | 0.121203E+10 | 0.286935E+09 |
July | 0.839800E+09 | 69895565.69 | 0.769905E+09 | 0.123968E+10 | 0.196193E+09 |
August | 0.779055E+09 | 17441113.07 | 0.761614E+09 | 0.104790E+10 | 0.226546E+09 |
September | 0.602906E+09 | 154734.26 | 0.602751E+09 | 0.696196E+09 | 0.399386E+09 |
October | 0.464885E+09 | 0.00 | 0.464885E+09 | 0.327076E+09 | 0.752709E+09 |
November | 0.382062E+09 | 0.00 | 0.382062E+09 | 0.105127E+09 | 0.106757E+10 |
December | 0.315246E+09 | 0.00 | 0.315246E+09 | 19199402.95 | 0.146383E+10 |
Annual Sum or Average | 0.716393E+10 | 0.290446E+09 | 0.687348E+10 | 0.660450E+10 | 0.890626E+10 |
Minimum of Months | 0.315246E+09 | 0.00 | 0.315246E+09 | 19199402.95 | 0.196193E+09 |
Maximum of Months | 0.885455E+09 | 0.144901E+09 | 0.769905E+09 | 0.123968E+10 | 0.146383E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370374E+09 | 0.00 | 0.370374E+09 | 73614722.86 | 0.135968E+10 |
February | 0.418108E+09 | 0.00 | 0.418108E+09 | 0.144563E+09 | 0.111144E+10 |
March | 0.583897E+09 | 0.00 | 0.583897E+09 | 0.352416E+09 | 0.968326E+09 |
April | 0.716888E+09 | 6137576.44 | 0.710750E+09 | 0.565387E+09 | 0.617924E+09 |
May | 0.805238E+09 | 51915399.52 | 0.753323E+09 | 0.821295E+09 | 0.455724E+09 |
June | 0.885451E+09 | 0.144900E+09 | 0.740551E+09 | 0.121203E+10 | 0.286935E+09 |
July | 0.839797E+09 | 69895053.49 | 0.769902E+09 | 0.123968E+10 | 0.196193E+09 |
August | 0.779052E+09 | 17440985.27 | 0.761611E+09 | 0.104789E+10 | 0.226546E+09 |
September | 0.602904E+09 | 154733.12 | 0.602749E+09 | 0.696194E+09 | 0.399385E+09 |
October | 0.464884E+09 | 0.00 | 0.464884E+09 | 0.327075E+09 | 0.752708E+09 |
November | 0.382060E+09 | 0.00 | 0.382060E+09 | 0.105126E+09 | 0.106757E+10 |
December | 0.315245E+09 | 0.00 | 0.315245E+09 | 19198965.63 | 0.146383E+10 |
Annual Sum or Average | 0.716390E+10 | 0.290444E+09 | 0.687345E+10 | 0.660447E+10 | 0.890626E+10 |
Minimum of Months | 0.315245E+09 | 0.00 | 0.315245E+09 | 19198965.63 | 0.196193E+09 |
Maximum of Months | 0.885451E+09 | 0.144900E+09 | 0.769902E+09 | 0.123968E+10 | 0.146383E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370360E+09 | 0.00 | 0.370360E+09 | 73612274.83 | 0.135963E+10 |
February | 0.418092E+09 | 0.00 | 0.418092E+09 | 0.144558E+09 | 0.111140E+10 |
March | 0.583875E+09 | 0.00 | 0.583875E+09 | 0.352403E+09 | 0.968288E+09 |
April | 0.716860E+09 | 6137351.56 | 0.710723E+09 | 0.565366E+09 | 0.617899E+09 |
May | 0.805207E+09 | 51913497.32 | 0.753294E+09 | 0.821263E+09 | 0.455706E+09 |
June | 0.885418E+09 | 0.144895E+09 | 0.740523E+09 | 0.121198E+10 | 0.286923E+09 |
July | 0.839765E+09 | 69892492.50 | 0.769872E+09 | 0.123963E+10 | 0.196185E+09 |
August | 0.779022E+09 | 17440346.22 | 0.761581E+09 | 0.104785E+10 | 0.226537E+09 |
September | 0.602881E+09 | 154727.45 | 0.602726E+09 | 0.696167E+09 | 0.399369E+09 |
October | 0.464866E+09 | 0.00 | 0.464866E+09 | 0.327062E+09 | 0.752678E+09 |
November | 0.382046E+09 | 0.00 | 0.382046E+09 | 0.105122E+09 | 0.106752E+10 |
December | 0.315233E+09 | 0.00 | 0.315233E+09 | 19198410.48 | 0.146377E+10 |
Annual Sum or Average | 0.716362E+10 | 0.290433E+09 | 0.687319E+10 | 0.660422E+10 | 0.890590E+10 |
Minimum of Months | 0.315233E+09 | 0.00 | 0.315233E+09 | 19198410.48 | 0.196185E+09 |
Maximum of Months | 0.885418E+09 | 0.144895E+09 | 0.769872E+09 | 0.123963E+10 | 0.146377E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113970E+10 | 0.637202E+09 | 0.502502E+09 | 0.957994E+09 | 0.137064E+10 |
February | 0.125071E+10 | 0.674268E+09 | 0.576444E+09 | 0.115650E+10 | 0.112552E+10 |
March | 0.182665E+10 | 0.103842E+10 | 0.788234E+09 | 0.191729E+10 | 0.979030E+09 |
April | 0.241508E+10 | 0.137586E+10 | 0.103922E+10 | 0.279551E+10 | 0.638584E+09 |
May | 0.238131E+10 | 0.135709E+10 | 0.102422E+10 | 0.291222E+10 | 0.507604E+09 |
June | 0.248442E+10 | 0.153052E+10 | 0.953899E+09 | 0.333683E+10 | 0.304228E+09 |
July | 0.237551E+10 | 0.135841E+10 | 0.101710E+10 | 0.332643E+10 | 0.199834E+09 |
August | 0.235073E+10 | 0.129600E+10 | 0.105473E+10 | 0.319784E+10 | 0.220784E+09 |
September | 0.189347E+10 | 0.105941E+10 | 0.834057E+09 | 0.243395E+10 | 0.418290E+09 |
October | 0.170163E+10 | 0.107962E+10 | 0.622011E+09 | 0.192679E+10 | 0.761649E+09 |
November | 0.128701E+10 | 0.756622E+09 | 0.530385E+09 | 0.122595E+10 | 0.107531E+10 |
December | 0.107760E+10 | 0.655819E+09 | 0.421783E+09 | 0.910953E+09 | 0.145333E+10 |
Annual Sum or Average | 0.221838E+11 | 0.128192E+11 | 0.936458E+10 | 0.260982E+11 | 0.905479E+10 |
Minimum of Months | 0.107760E+10 | 0.637202E+09 | 0.421783E+09 | 0.910953E+09 | 0.199834E+09 |
Maximum of Months | 0.248442E+10 | 0.153052E+10 | 0.105473E+10 | 0.333683E+10 | 0.145333E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113970E+10 | 0.637202E+09 | 0.502502E+09 | 0.957994E+09 | 0.137064E+10 |
February | 0.125071E+10 | 0.674268E+09 | 0.576444E+09 | 0.115650E+10 | 0.112552E+10 |
March | 0.182665E+10 | 0.103842E+10 | 0.788234E+09 | 0.191729E+10 | 0.979030E+09 |
April | 0.241508E+10 | 0.137586E+10 | 0.103922E+10 | 0.279551E+10 | 0.638584E+09 |
May | 0.238131E+10 | 0.135709E+10 | 0.102422E+10 | 0.291222E+10 | 0.507604E+09 |
June | 0.248442E+10 | 0.153052E+10 | 0.953899E+09 | 0.333683E+10 | 0.304228E+09 |
July | 0.237551E+10 | 0.135841E+10 | 0.101710E+10 | 0.332643E+10 | 0.199834E+09 |
August | 0.235073E+10 | 0.129600E+10 | 0.105473E+10 | 0.319784E+10 | 0.220784E+09 |
September | 0.189347E+10 | 0.105941E+10 | 0.834057E+09 | 0.243395E+10 | 0.418290E+09 |
October | 0.170163E+10 | 0.107962E+10 | 0.622011E+09 | 0.192679E+10 | 0.761649E+09 |
November | 0.128701E+10 | 0.756622E+09 | 0.530385E+09 | 0.122595E+10 | 0.107531E+10 |
December | 0.107760E+10 | 0.655819E+09 | 0.421783E+09 | 0.910953E+09 | 0.145333E+10 |
Annual Sum or Average | 0.221838E+11 | 0.128192E+11 | 0.936458E+10 | 0.260982E+11 | 0.905479E+10 |
Minimum of Months | 0.107760E+10 | 0.637202E+09 | 0.421783E+09 | 0.910953E+09 | 0.199834E+09 |
Maximum of Months | 0.248442E+10 | 0.153052E+10 | 0.105473E+10 | 0.333683E+10 | 0.145333E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113968E+10 | 0.637190E+09 | 0.502492E+09 | 0.957977E+09 | 0.137061E+10 |
February | 0.125069E+10 | 0.674256E+09 | 0.576434E+09 | 0.115648E+10 | 0.112550E+10 |
March | 0.182662E+10 | 0.103840E+10 | 0.788219E+09 | 0.191726E+10 | 0.979012E+09 |
April | 0.241503E+10 | 0.137583E+10 | 0.103920E+10 | 0.279546E+10 | 0.638572E+09 |
May | 0.238127E+10 | 0.135707E+10 | 0.102420E+10 | 0.291216E+10 | 0.507594E+09 |
June | 0.248438E+10 | 0.153050E+10 | 0.953882E+09 | 0.333677E+10 | 0.304222E+09 |
July | 0.237547E+10 | 0.135839E+10 | 0.101708E+10 | 0.332636E+10 | 0.199830E+09 |
August | 0.235068E+10 | 0.129598E+10 | 0.105471E+10 | 0.319778E+10 | 0.220780E+09 |
September | 0.189343E+10 | 0.105939E+10 | 0.834041E+09 | 0.243391E+10 | 0.418282E+09 |
October | 0.170160E+10 | 0.107960E+10 | 0.622000E+09 | 0.192675E+10 | 0.761635E+09 |
November | 0.128698E+10 | 0.756608E+09 | 0.530375E+09 | 0.122592E+10 | 0.107529E+10 |
December | 0.107758E+10 | 0.655807E+09 | 0.421775E+09 | 0.910937E+09 | 0.145330E+10 |
Annual Sum or Average | 0.221834E+11 | 0.128190E+11 | 0.936441E+10 | 0.260978E+11 | 0.905463E+10 |
Minimum of Months | 0.107758E+10 | 0.637190E+09 | 0.421775E+09 | 0.910937E+09 | 0.199830E+09 |
Maximum of Months | 0.248438E+10 | 0.153050E+10 | 0.105471E+10 | 0.333677E+10 | 0.145330E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273816E+10 | 0.213067E+10 | 0.607499E+09 | 0.306834E+10 | 0.122745E+10 |
February | 0.242035E+10 | 0.176798E+10 | 0.652370E+09 | 0.277035E+10 | 0.102934E+10 |
March | 0.197464E+10 | 0.119379E+10 | 0.780855E+09 | 0.230975E+10 | 0.931007E+09 |
April | 0.149030E+10 | 0.611736E+09 | 0.878562E+09 | 0.181100E+10 | 0.641145E+09 |
May | 0.102704E+10 | 0.225927E+09 | 0.801113E+09 | 0.126173E+10 | 0.481435E+09 |
June | 0.840767E+09 | 0.103614E+09 | 0.737153E+09 | 0.120834E+10 | 0.301470E+09 |
July | 0.961360E+09 | 0.153518E+09 | 0.807842E+09 | 0.149159E+10 | 0.203288E+09 |
August | 0.132194E+10 | 0.429693E+09 | 0.892244E+09 | 0.196172E+10 | 0.240052E+09 |
September | 0.176898E+10 | 0.986432E+09 | 0.782551E+09 | 0.244447E+10 | 0.414554E+09 |
October | 0.250085E+10 | 0.184186E+10 | 0.658992E+09 | 0.311878E+10 | 0.721432E+09 |
November | 0.269561E+10 | 0.206887E+10 | 0.626742E+09 | 0.311178E+10 | 0.977565E+09 |
December | 0.297083E+10 | 0.245062E+10 | 0.520209E+09 | 0.334846E+10 | 0.128142E+10 |
Annual Sum or Average | 0.227108E+11 | 0.139647E+11 | 0.874613E+10 | 0.279063E+11 | 0.845015E+10 |
Minimum of Months | 0.840767E+09 | 0.103614E+09 | 0.520209E+09 | 0.120834E+10 | 0.203288E+09 |
Maximum of Months | 0.297083E+10 | 0.245062E+10 | 0.892244E+09 | 0.334846E+10 | 0.128142E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273815E+10 | 0.213065E+10 | 0.607495E+09 | 0.306831E+10 | 0.122745E+10 |
February | 0.242033E+10 | 0.176796E+10 | 0.652366E+09 | 0.277033E+10 | 0.102934E+10 |
March | 0.197463E+10 | 0.119378E+10 | 0.780852E+09 | 0.230973E+10 | 0.931006E+09 |
April | 0.149029E+10 | 0.611731E+09 | 0.878558E+09 | 0.181098E+10 | 0.641145E+09 |
May | 0.102704E+10 | 0.225926E+09 | 0.801110E+09 | 0.126172E+10 | 0.481434E+09 |
June | 0.840763E+09 | 0.103613E+09 | 0.737150E+09 | 0.120834E+10 | 0.301469E+09 |
July | 0.961356E+09 | 0.153517E+09 | 0.807839E+09 | 0.149158E+10 | 0.203287E+09 |
August | 0.132193E+10 | 0.429690E+09 | 0.892240E+09 | 0.196171E+10 | 0.240052E+09 |
September | 0.176897E+10 | 0.986424E+09 | 0.782547E+09 | 0.244445E+10 | 0.414554E+09 |
October | 0.250083E+10 | 0.184184E+10 | 0.658989E+09 | 0.311875E+10 | 0.721432E+09 |
November | 0.269559E+10 | 0.206886E+10 | 0.626739E+09 | 0.311175E+10 | 0.977564E+09 |
December | 0.297081E+10 | 0.245060E+10 | 0.520206E+09 | 0.334844E+10 | 0.128142E+10 |
Annual Sum or Average | 0.227107E+11 | 0.139646E+11 | 0.874609E+10 | 0.279061E+11 | 0.845015E+10 |
Minimum of Months | 0.840763E+09 | 0.103613E+09 | 0.520206E+09 | 0.120834E+10 | 0.203287E+09 |
Maximum of Months | 0.297081E+10 | 0.245060E+10 | 0.892240E+09 | 0.334844E+10 | 0.128142E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273816E+10 | 0.213067E+10 | 0.607499E+09 | 0.306834E+10 | 0.122745E+10 |
February | 0.242035E+10 | 0.176798E+10 | 0.652370E+09 | 0.277035E+10 | 0.102934E+10 |
March | 0.197464E+10 | 0.119379E+10 | 0.780855E+09 | 0.230975E+10 | 0.931007E+09 |
April | 0.149030E+10 | 0.611736E+09 | 0.878562E+09 | 0.181100E+10 | 0.641145E+09 |
May | 0.102704E+10 | 0.225927E+09 | 0.801113E+09 | 0.126173E+10 | 0.481435E+09 |
June | 0.840767E+09 | 0.103614E+09 | 0.737153E+09 | 0.120834E+10 | 0.301470E+09 |
July | 0.961360E+09 | 0.153518E+09 | 0.807842E+09 | 0.149159E+10 | 0.203288E+09 |
August | 0.132194E+10 | 0.429693E+09 | 0.892244E+09 | 0.196172E+10 | 0.240052E+09 |
September | 0.176898E+10 | 0.986432E+09 | 0.782551E+09 | 0.244447E+10 | 0.414554E+09 |
October | 0.250085E+10 | 0.184186E+10 | 0.658992E+09 | 0.311878E+10 | 0.721432E+09 |
November | 0.269561E+10 | 0.206887E+10 | 0.626742E+09 | 0.311178E+10 | 0.977565E+09 |
December | 0.297083E+10 | 0.245062E+10 | 0.520209E+09 | 0.334846E+10 | 0.128142E+10 |
Annual Sum or Average | 0.227108E+11 | 0.139647E+11 | 0.874613E+10 | 0.279063E+11 | 0.845015E+10 |
Minimum of Months | 0.840767E+09 | 0.103614E+09 | 0.520209E+09 | 0.120834E+10 | 0.203288E+09 |
Maximum of Months | 0.297083E+10 | 0.245062E+10 | 0.892244E+09 | 0.334846E+10 | 0.128142E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273815E+10 | 0.213065E+10 | 0.607495E+09 | 0.306831E+10 | 0.122745E+10 |
February | 0.242033E+10 | 0.176796E+10 | 0.652366E+09 | 0.277033E+10 | 0.102934E+10 |
March | 0.197463E+10 | 0.119378E+10 | 0.780852E+09 | 0.230973E+10 | 0.931006E+09 |
April | 0.149029E+10 | 0.611731E+09 | 0.878558E+09 | 0.181098E+10 | 0.641145E+09 |
May | 0.102704E+10 | 0.225926E+09 | 0.801110E+09 | 0.126172E+10 | 0.481434E+09 |
June | 0.840763E+09 | 0.103613E+09 | 0.737150E+09 | 0.120834E+10 | 0.301469E+09 |
July | 0.961356E+09 | 0.153517E+09 | 0.807839E+09 | 0.149158E+10 | 0.203287E+09 |
August | 0.132193E+10 | 0.429690E+09 | 0.892240E+09 | 0.196171E+10 | 0.240052E+09 |
September | 0.176897E+10 | 0.986424E+09 | 0.782547E+09 | 0.244445E+10 | 0.414554E+09 |
October | 0.250083E+10 | 0.184184E+10 | 0.658989E+09 | 0.311875E+10 | 0.721432E+09 |
November | 0.269559E+10 | 0.206886E+10 | 0.626739E+09 | 0.311175E+10 | 0.977564E+09 |
December | 0.297081E+10 | 0.245060E+10 | 0.520206E+09 | 0.334844E+10 | 0.128142E+10 |
Annual Sum or Average | 0.227107E+11 | 0.139646E+11 | 0.874609E+10 | 0.279061E+11 | 0.845015E+10 |
Minimum of Months | 0.840763E+09 | 0.103613E+09 | 0.520206E+09 | 0.120834E+10 | 0.203287E+09 |
Maximum of Months | 0.297081E+10 | 0.245060E+10 | 0.892240E+09 | 0.334844E+10 | 0.128142E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273804E+10 | 0.213057E+10 | 0.607473E+09 | 0.306820E+10 | 0.122740E+10 |
February | 0.242024E+10 | 0.176790E+10 | 0.652342E+09 | 0.277023E+10 | 0.102930E+10 |
March | 0.197456E+10 | 0.119374E+10 | 0.780822E+09 | 0.230965E+10 | 0.930969E+09 |
April | 0.149023E+10 | 0.611709E+09 | 0.878525E+09 | 0.181092E+10 | 0.641119E+09 |
May | 0.102700E+10 | 0.225918E+09 | 0.801079E+09 | 0.126167E+10 | 0.481415E+09 |
June | 0.840731E+09 | 0.103609E+09 | 0.737122E+09 | 0.120829E+10 | 0.301458E+09 |
July | 0.961319E+09 | 0.153512E+09 | 0.807808E+09 | 0.149152E+10 | 0.203279E+09 |
August | 0.132188E+10 | 0.429674E+09 | 0.892206E+09 | 0.196163E+10 | 0.240043E+09 |
September | 0.176891E+10 | 0.986388E+09 | 0.782517E+09 | 0.244436E+10 | 0.414537E+09 |
October | 0.250074E+10 | 0.184177E+10 | 0.658964E+09 | 0.311864E+10 | 0.721403E+09 |
November | 0.269549E+10 | 0.206878E+10 | 0.626715E+09 | 0.311164E+10 | 0.977525E+09 |
December | 0.297070E+10 | 0.245051E+10 | 0.520187E+09 | 0.334831E+10 | 0.128137E+10 |
Annual Sum or Average | 0.227098E+11 | 0.139641E+11 | 0.874576E+10 | 0.279051E+11 | 0.844981E+10 |
Minimum of Months | 0.840731E+09 | 0.103609E+09 | 0.520187E+09 | 0.120829E+10 | 0.203279E+09 |
Maximum of Months | 0.297070E+10 | 0.245051E+10 | 0.892206E+09 | 0.334831E+10 | 0.128137E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117556E+10 | 0.670386E+09 | 0.505176E+09 | 0.107954E+10 | 0.151897E+10 |
February | 0.136689E+10 | 0.789611E+09 | 0.577278E+09 | 0.134214E+10 | 0.128195E+10 |
March | 0.169023E+10 | 0.899743E+09 | 0.790487E+09 | 0.175275E+10 | 0.115732E+10 |
April | 0.208765E+10 | 0.111106E+10 | 0.976594E+09 | 0.233547E+10 | 0.797119E+09 |
May | 0.204538E+10 | 0.105392E+10 | 0.991456E+09 | 0.246463E+10 | 0.577362E+09 |
June | 0.212191E+10 | 0.118400E+10 | 0.937906E+09 | 0.285136E+10 | 0.389353E+09 |
July | 0.197769E+10 | 0.967857E+09 | 0.100984E+10 | 0.276733E+10 | 0.274726E+09 |
August | 0.202085E+10 | 0.934727E+09 | 0.108613E+10 | 0.271557E+10 | 0.343674E+09 |
September | 0.176642E+10 | 0.930304E+09 | 0.836119E+09 | 0.227799E+10 | 0.492786E+09 |
October | 0.166991E+10 | 0.103791E+10 | 0.631998E+09 | 0.191531E+10 | 0.902692E+09 |
November | 0.126858E+10 | 0.746336E+09 | 0.522247E+09 | 0.121937E+10 | 0.124620E+10 |
December | 0.113364E+10 | 0.710910E+09 | 0.422725E+09 | 0.100014E+10 | 0.169801E+10 |
Annual Sum or Average | 0.203247E+11 | 0.110368E+11 | 0.928795E+10 | 0.237216E+11 | 0.106802E+11 |
Minimum of Months | 0.113364E+10 | 0.670386E+09 | 0.422725E+09 | 0.100014E+10 | 0.274726E+09 |
Maximum of Months | 0.212191E+10 | 0.118400E+10 | 0.108613E+10 | 0.285136E+10 | 0.169801E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117556E+10 | 0.670386E+09 | 0.505176E+09 | 0.107954E+10 | 0.151897E+10 |
February | 0.136689E+10 | 0.789611E+09 | 0.577278E+09 | 0.134214E+10 | 0.128195E+10 |
March | 0.169023E+10 | 0.899743E+09 | 0.790487E+09 | 0.175275E+10 | 0.115732E+10 |
April | 0.208765E+10 | 0.111106E+10 | 0.976594E+09 | 0.233547E+10 | 0.797119E+09 |
May | 0.204538E+10 | 0.105392E+10 | 0.991456E+09 | 0.246463E+10 | 0.577362E+09 |
June | 0.212191E+10 | 0.118400E+10 | 0.937906E+09 | 0.285136E+10 | 0.389353E+09 |
July | 0.197769E+10 | 0.967857E+09 | 0.100984E+10 | 0.276733E+10 | 0.274726E+09 |
August | 0.202085E+10 | 0.934727E+09 | 0.108613E+10 | 0.271557E+10 | 0.343674E+09 |
September | 0.176642E+10 | 0.930304E+09 | 0.836119E+09 | 0.227799E+10 | 0.492786E+09 |
October | 0.166991E+10 | 0.103791E+10 | 0.631998E+09 | 0.191531E+10 | 0.902692E+09 |
November | 0.126858E+10 | 0.746336E+09 | 0.522247E+09 | 0.121937E+10 | 0.124620E+10 |
December | 0.113364E+10 | 0.710910E+09 | 0.422725E+09 | 0.100014E+10 | 0.169801E+10 |
Annual Sum or Average | 0.203247E+11 | 0.110368E+11 | 0.928795E+10 | 0.237216E+11 | 0.106802E+11 |
Minimum of Months | 0.113364E+10 | 0.670386E+09 | 0.422725E+09 | 0.100014E+10 | 0.274726E+09 |
Maximum of Months | 0.212191E+10 | 0.118400E+10 | 0.108613E+10 | 0.285136E+10 | 0.169801E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117554E+10 | 0.670373E+09 | 0.505167E+09 | 0.107952E+10 | 0.151894E+10 |
February | 0.136686E+10 | 0.789597E+09 | 0.577268E+09 | 0.134211E+10 | 0.128193E+10 |
March | 0.169020E+10 | 0.899727E+09 | 0.790473E+09 | 0.175272E+10 | 0.115730E+10 |
April | 0.208761E+10 | 0.111104E+10 | 0.976576E+09 | 0.233543E+10 | 0.797104E+09 |
May | 0.204534E+10 | 0.105390E+10 | 0.991438E+09 | 0.246459E+10 | 0.577352E+09 |
June | 0.212187E+10 | 0.118398E+10 | 0.937889E+09 | 0.285130E+10 | 0.389346E+09 |
July | 0.197766E+10 | 0.967840E+09 | 0.100982E+10 | 0.276728E+10 | 0.274721E+09 |
August | 0.202082E+10 | 0.934710E+09 | 0.108611E+10 | 0.271552E+10 | 0.343668E+09 |
September | 0.176639E+10 | 0.930287E+09 | 0.836104E+09 | 0.227795E+10 | 0.492777E+09 |
October | 0.166988E+10 | 0.103789E+10 | 0.631987E+09 | 0.191527E+10 | 0.902675E+09 |
November | 0.126856E+10 | 0.746323E+09 | 0.522238E+09 | 0.121934E+10 | 0.124618E+10 |
December | 0.113361E+10 | 0.710897E+09 | 0.422717E+09 | 0.100012E+10 | 0.169798E+10 |
Annual Sum or Average | 0.203243E+11 | 0.110366E+11 | 0.928778E+10 | 0.237212E+11 | 0.106800E+11 |
Minimum of Months | 0.113361E+10 | 0.670373E+09 | 0.422717E+09 | 0.100012E+10 | 0.274721E+09 |
Maximum of Months | 0.212187E+10 | 0.118398E+10 | 0.108611E+10 | 0.285130E+10 | 0.169798E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185189E+10 | 0.00 | 0.185189E+10 | 0.501986E+09 | 0.619989E+10 |
February | 0.209056E+10 | 0.00 | 0.209056E+10 | 0.875856E+09 | 0.506285E+10 |
March | 0.291952E+10 | 0.00 | 0.291952E+10 | 0.193274E+10 | 0.442186E+10 |
April | 0.358447E+10 | 30688752.42 | 0.355379E+10 | 0.295540E+10 | 0.285924E+10 |
May | 0.402623E+10 | 0.259584E+09 | 0.376665E+10 | 0.416342E+10 | 0.217577E+10 |
June | 0.442731E+10 | 0.724521E+09 | 0.370279E+10 | 0.609469E+10 | 0.140747E+10 |
July | 0.419903E+10 | 0.349485E+09 | 0.384954E+10 | 0.623250E+10 | 0.988743E+09 |
August | 0.389530E+10 | 87207399.21 | 0.380809E+10 | 0.530367E+10 | 0.111492E+10 |
September | 0.301455E+10 | 773687.54 | 0.301377E+10 | 0.352782E+10 | 0.189837E+10 |
October | 0.232444E+10 | 0.00 | 0.232444E+10 | 0.175047E+10 | 0.344680E+10 |
November | 0.191032E+10 | 0.00 | 0.191032E+10 | 0.671524E+09 | 0.475130E+10 |
December | 0.157624E+10 | 0.00 | 0.157624E+10 | 0.183714E+09 | 0.647858E+10 |
Annual Sum or Average | 0.358199E+11 | 0.145226E+10 | 0.343676E+11 | 0.341938E+11 | 0.408058E+11 |
Minimum of Months | 0.157624E+10 | 0.00 | 0.157624E+10 | 0.183714E+09 | 0.988743E+09 |
Maximum of Months | 0.442731E+10 | 0.724521E+09 | 0.384954E+10 | 0.623250E+10 | 0.647858E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.341908E+10 | 0.191159E+10 | 0.150749E+10 | 0.295959E+10 | 0.383524E+10 |
February | 0.375210E+10 | 0.202278E+10 | 0.172931E+10 | 0.353602E+10 | 0.316120E+10 |
March | 0.547990E+10 | 0.311522E+10 | 0.236468E+10 | 0.578169E+10 | 0.278291E+10 |
April | 0.724516E+10 | 0.412753E+10 | 0.311763E+10 | 0.835531E+10 | 0.188876E+10 |
May | 0.714386E+10 | 0.407123E+10 | 0.307263E+10 | 0.870017E+10 | 0.148298E+10 |
June | 0.745319E+10 | 0.459152E+10 | 0.286167E+10 | 0.996695E+10 | 0.926914E+09 |
July | 0.712646E+10 | 0.407520E+10 | 0.305126E+10 | 0.992613E+10 | 0.663845E+09 |
August | 0.705211E+10 | 0.388796E+10 | 0.316415E+10 | 0.953696E+10 | 0.746360E+09 |
September | 0.568035E+10 | 0.317821E+10 | 0.250214E+10 | 0.728232E+10 | 0.122080E+10 |
October | 0.510483E+10 | 0.323882E+10 | 0.186601E+10 | 0.579562E+10 | 0.217127E+10 |
November | 0.386098E+10 | 0.226984E+10 | 0.159114E+10 | 0.373130E+10 | 0.299745E+10 |
December | 0.323277E+10 | 0.196744E+10 | 0.126533E+10 | 0.280068E+10 | 0.402987E+10 |
Annual Sum or Average | 0.665508E+11 | 0.384573E+11 | 0.280934E+11 | 0.783727E+11 | 0.259076E+11 |
Minimum of Months | 0.323277E+10 | 0.191159E+10 | 0.126533E+10 | 0.280068E+10 | 0.663845E+09 |
Maximum of Months | 0.745319E+10 | 0.459152E+10 | 0.316415E+10 | 0.996695E+10 | 0.402987E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136911E+11 | 0.106536E+11 | 0.303753E+10 | 0.152710E+11 | 0.603026E+10 |
February | 0.121019E+11 | 0.884006E+10 | 0.326189E+10 | 0.137905E+11 | 0.503376E+10 |
March | 0.987338E+10 | 0.596907E+10 | 0.390432E+10 | 0.115125E+11 | 0.451746E+10 |
April | 0.745159E+10 | 0.305874E+10 | 0.439285E+10 | 0.904516E+10 | 0.310527E+10 |
May | 0.513525E+10 | 0.112966E+10 | 0.400559E+10 | 0.630792E+10 | 0.233699E+10 |
June | 0.420386E+10 | 0.518080E+09 | 0.368578E+10 | 0.607531E+10 | 0.148096E+10 |
July | 0.480684E+10 | 0.767608E+09 | 0.403923E+10 | 0.747515E+10 | 0.103683E+10 |
August | 0.660977E+10 | 0.214851E+10 | 0.446126E+10 | 0.981295E+10 | 0.121697E+10 |
September | 0.884505E+10 | 0.493226E+10 | 0.391279E+10 | 0.121612E+11 | 0.204465E+10 |
October | 0.125045E+11 | 0.920947E+10 | 0.329499E+10 | 0.155165E+11 | 0.355016E+10 |
November | 0.134783E+11 | 0.103446E+11 | 0.313375E+10 | 0.154992E+11 | 0.476259E+10 |
December | 0.148544E+11 | 0.122533E+11 | 0.260108E+10 | 0.166995E+11 | 0.618929E+10 |
Annual Sum or Average | 0.113556E+12 | 0.698249E+11 | 0.437311E+11 | 0.139167E+12 | 0.413052E+11 |
Minimum of Months | 0.420386E+10 | 0.518080E+09 | 0.260108E+10 | 0.607531E+10 | 0.103683E+10 |
Maximum of Months | 0.148544E+11 | 0.122533E+11 | 0.446126E+10 | 0.166995E+11 | 0.618929E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.352665E+10 | 0.201114E+10 | 0.151551E+10 | 0.333174E+10 | 0.416967E+10 |
February | 0.410063E+10 | 0.236881E+10 | 0.173182E+10 | 0.414001E+10 | 0.345278E+10 |
March | 0.507064E+10 | 0.269920E+10 | 0.237144E+10 | 0.541794E+10 | 0.305680E+10 |
April | 0.626289E+10 | 0.333314E+10 | 0.292975E+10 | 0.716317E+10 | 0.209947E+10 |
May | 0.613607E+10 | 0.316173E+10 | 0.297434E+10 | 0.744583E+10 | 0.161477E+10 |
June | 0.636567E+10 | 0.355198E+10 | 0.281369E+10 | 0.861712E+10 | 0.109025E+10 |
July | 0.593302E+10 | 0.290354E+10 | 0.302948E+10 | 0.838464E+10 | 0.757386E+09 |
August | 0.606249E+10 | 0.280415E+10 | 0.325834E+10 | 0.828879E+10 | 0.871703E+09 |
September | 0.529921E+10 | 0.279088E+10 | 0.250833E+10 | 0.688348E+10 | 0.136779E+10 |
October | 0.500967E+10 | 0.311369E+10 | 0.189598E+10 | 0.585121E+10 | 0.242104E+10 |
November | 0.380571E+10 | 0.223899E+10 | 0.156673E+10 | 0.380704E+10 | 0.321763E+10 |
December | 0.340087E+10 | 0.213271E+10 | 0.126816E+10 | 0.314156E+10 | 0.429987E+10 |
Annual Sum or Average | 0.609735E+11 | 0.331100E+11 | 0.278636E+11 | 0.724725E+11 | 0.284192E+11 |
Minimum of Months | 0.340087E+10 | 0.201114E+10 | 0.126816E+10 | 0.314156E+10 | 0.757386E+09 |
Maximum of Months | 0.636567E+10 | 0.355198E+10 | 0.325834E+10 | 0.861712E+10 | 0.429987E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185189E+10 | 0.00 | 0.185189E+10 | 0.593322E+09 | 0.574576E+10 |
February | 0.209056E+10 | 0.00 | 0.209056E+10 | 0.966477E+09 | 0.471743E+10 |
March | 0.291952E+10 | 0.00 | 0.291952E+10 | 0.204186E+10 | 0.412233E+10 |
April | 0.358447E+10 | 30688752.42 | 0.355379E+10 | 0.302243E+10 | 0.270346E+10 |
May | 0.402623E+10 | 0.259584E+09 | 0.376665E+10 | 0.418953E+10 | 0.210609E+10 |
June | 0.442731E+10 | 0.724521E+09 | 0.370279E+10 | 0.606910E+10 | 0.139831E+10 |
July | 0.419903E+10 | 0.349485E+09 | 0.384954E+10 | 0.618082E+10 | 0.100332E+10 |
August | 0.389530E+10 | 87207399.21 | 0.380809E+10 | 0.526573E+10 | 0.111768E+10 |
September | 0.301455E+10 | 773687.54 | 0.301377E+10 | 0.352779E+10 | 0.185261E+10 |
October | 0.232444E+10 | 0.00 | 0.232444E+10 | 0.181890E+10 | 0.322134E+10 |
November | 0.191032E+10 | 0.00 | 0.191032E+10 | 0.774439E+09 | 0.434869E+10 |
December | 0.157624E+10 | 0.00 | 0.157624E+10 | 0.239900E+09 | 0.597784E+10 |
Annual Sum or Average | 0.358199E+11 | 0.145226E+10 | 0.343676E+11 | 0.346903E+11 | 0.383149E+11 |
Minimum of Months | 0.157624E+10 | 0.00 | 0.157624E+10 | 0.239900E+09 | 0.100332E+10 |
Maximum of Months | 0.442731E+10 | 0.724521E+09 | 0.384954E+10 | 0.618082E+10 | 0.597784E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.341908E+10 | 0.191159E+10 | 0.150749E+10 | 0.306303E+10 | 0.357694E+10 |
February | 0.375210E+10 | 0.202278E+10 | 0.172931E+10 | 0.361508E+10 | 0.296750E+10 |
March | 0.547990E+10 | 0.311522E+10 | 0.236468E+10 | 0.583548E+10 | 0.263916E+10 |
April | 0.724516E+10 | 0.412753E+10 | 0.311763E+10 | 0.836342E+10 | 0.182625E+10 |
May | 0.714386E+10 | 0.407123E+10 | 0.307263E+10 | 0.868430E+10 | 0.145801E+10 |
June | 0.745319E+10 | 0.459152E+10 | 0.286167E+10 | 0.993058E+10 | 0.931349E+09 |
July | 0.712646E+10 | 0.407520E+10 | 0.305126E+10 | 0.987966E+10 | 0.680974E+09 |
August | 0.705211E+10 | 0.388796E+10 | 0.316415E+10 | 0.949704E+10 | 0.757889E+09 |
September | 0.568035E+10 | 0.317821E+10 | 0.250214E+10 | 0.726405E+10 | 0.121483E+10 |
October | 0.510483E+10 | 0.323882E+10 | 0.186601E+10 | 0.582012E+10 | 0.207895E+10 |
November | 0.386098E+10 | 0.226984E+10 | 0.159114E+10 | 0.381808E+10 | 0.278806E+10 |
December | 0.323277E+10 | 0.196744E+10 | 0.126533E+10 | 0.288225E+10 | 0.373794E+10 |
Annual Sum or Average | 0.665508E+11 | 0.384573E+11 | 0.280934E+11 | 0.786531E+11 | 0.246578E+11 |
Minimum of Months | 0.323277E+10 | 0.191159E+10 | 0.126533E+10 | 0.288225E+10 | 0.680974E+09 |
Maximum of Months | 0.745319E+10 | 0.459152E+10 | 0.316415E+10 | 0.993058E+10 | 0.373794E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136911E+11 | 0.106536E+11 | 0.303753E+10 | 0.154174E+11 | 0.562142E+10 |
February | 0.121019E+11 | 0.884006E+10 | 0.326189E+10 | 0.138906E+11 | 0.471587E+10 |
March | 0.987338E+10 | 0.596907E+10 | 0.390432E+10 | 0.115876E+11 | 0.426759E+10 |
April | 0.745159E+10 | 0.305874E+10 | 0.439285E+10 | 0.907045E+10 | 0.296977E+10 |
May | 0.513525E+10 | 0.112966E+10 | 0.400559E+10 | 0.631257E+10 | 0.226701E+10 |
June | 0.420386E+10 | 0.518080E+09 | 0.368578E+10 | 0.604724E+10 | 0.146716E+10 |
July | 0.480684E+10 | 0.767608E+09 | 0.403923E+10 | 0.742246E+10 | 0.105139E+10 |
August | 0.660977E+10 | 0.214851E+10 | 0.446126E+10 | 0.976493E+10 | 0.122291E+10 |
September | 0.884505E+10 | 0.493226E+10 | 0.391279E+10 | 0.121380E+11 | 0.201906E+10 |
October | 0.125045E+11 | 0.920947E+10 | 0.329499E+10 | 0.155592E+11 | 0.339387E+10 |
November | 0.134783E+11 | 0.103446E+11 | 0.313375E+10 | 0.156154E+11 | 0.443945E+10 |
December | 0.148544E+11 | 0.122533E+11 | 0.260108E+10 | 0.168194E+11 | 0.574127E+10 |
Annual Sum or Average | 0.113556E+12 | 0.698249E+11 | 0.437311E+11 | 0.139645E+12 | 0.391768E+11 |
Minimum of Months | 0.420386E+10 | 0.518080E+09 | 0.260108E+10 | 0.604724E+10 | 0.105139E+10 |
Maximum of Months | 0.148544E+11 | 0.122533E+11 | 0.446126E+10 | 0.168194E+11 | 0.574127E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.352665E+10 | 0.201114E+10 | 0.151551E+10 | 0.338276E+10 | 0.391352E+10 |
February | 0.410063E+10 | 0.236881E+10 | 0.173182E+10 | 0.417648E+10 | 0.326215E+10 |
March | 0.507064E+10 | 0.269920E+10 | 0.237144E+10 | 0.545120E+10 | 0.290395E+10 |
April | 0.626289E+10 | 0.333314E+10 | 0.292975E+10 | 0.717440E+10 | 0.202080E+10 |
May | 0.613607E+10 | 0.316173E+10 | 0.297434E+10 | 0.744300E+10 | 0.157626E+10 |
June | 0.636567E+10 | 0.355198E+10 | 0.281369E+10 | 0.859377E+10 | 0.108491E+10 |
July | 0.593302E+10 | 0.290354E+10 | 0.302948E+10 | 0.834897E+10 | 0.763917E+09 |
August | 0.606249E+10 | 0.280415E+10 | 0.325834E+10 | 0.826008E+10 | 0.873987E+09 |
September | 0.529921E+10 | 0.279088E+10 | 0.250833E+10 | 0.687210E+10 | 0.135156E+10 |
October | 0.500967E+10 | 0.311369E+10 | 0.189598E+10 | 0.586563E+10 | 0.231486E+10 |
November | 0.380571E+10 | 0.223899E+10 | 0.156673E+10 | 0.384981E+10 | 0.300992E+10 |
December | 0.340087E+10 | 0.213271E+10 | 0.126816E+10 | 0.317685E+10 | 0.402150E+10 |
Annual Sum or Average | 0.609735E+11 | 0.331100E+11 | 0.278636E+11 | 0.725950E+11 | 0.270973E+11 |
Minimum of Months | 0.340087E+10 | 0.201114E+10 | 0.126816E+10 | 0.317685E+10 | 0.763917E+09 |
Maximum of Months | 0.636567E+10 | 0.355198E+10 | 0.325834E+10 | 0.859377E+10 | 0.402150E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 137.42 | 2538.22 | 691.41 | 0.00 | 691.41 | 0.00 | 0.00 |
February | 298.78 | 2297.11 | 864.14 | 0.00 | 864.14 | 0.00 | 0.00 |
March | 657.88 | 1807.64 | 1090.01 | 0.00 | 1090.01 | 0.00 | 0.00 |
April | 1090.64 | 1191.97 | 1382.88 | 11.84 | 1371.04 | 0.00 | 0.00 |
May | 1533.18 | 850.73 | 1503.20 | 96.91 | 1406.29 | 0.00 | 0.00 |
June | 2338.00 | 553.50 | 1708.04 | 279.51 | 1428.53 | 0.00 | 0.00 |
July | 2314.21 | 366.25 | 1567.71 | 130.48 | 1437.24 | 0.00 | 0.00 |
August | 1956.18 | 422.91 | 1454.32 | 32.56 | 1421.76 | 0.00 | 0.00 |
September | 1342.96 | 770.41 | 1163.00 | 0.30 | 1162.71 | 0.00 | 0.00 |
October | 610.58 | 1405.14 | 867.83 | 0.00 | 867.83 | 0.00 | 0.00 |
November | 202.79 | 2059.33 | 737.00 | 0.00 | 737.00 | 0.00 | 0.00 |
December | 35.84 | 2732.63 | 588.49 | 0.00 | 588.49 | 0.00 | 0.00 |
Annual Sum or Average | 1047.13 | 1412.07 | 1135.82 | 46.05 | 1089.77 | 0.00 | 0.00 |
Minimum of Months | 35.84 | 366.25 | 588.49 | 0.00 | 588.49 | 0.00 | 0.00 |
Maximum of Months | 2338.00 | 2732.63 | 1708.04 | 279.51 | 1437.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1073.02 | 1535.20 | 1276.54 | 713.71 | 562.83 | 0.00 | 0.00 |
February | 1434.15 | 1395.73 | 1550.97 | 836.14 | 714.83 | 0.00 | 0.00 |
March | 2147.49 | 1096.58 | 2045.97 | 1163.10 | 882.87 | 0.00 | 0.00 |
April | 3235.53 | 739.10 | 2795.21 | 1592.42 | 1202.79 | 0.00 | 0.00 |
May | 3261.87 | 568.55 | 2667.22 | 1520.03 | 1147.19 | 0.00 | 0.00 |
June | 3862.05 | 352.11 | 2875.47 | 1771.43 | 1104.04 | 0.00 | 0.00 |
July | 3725.81 | 223.83 | 2660.72 | 1521.51 | 1139.21 | 0.00 | 0.00 |
August | 3581.79 | 247.29 | 2632.97 | 1451.60 | 1181.36 | 0.00 | 0.00 |
September | 2817.06 | 484.13 | 2191.50 | 1226.16 | 965.34 | 0.00 | 0.00 |
October | 2158.13 | 853.10 | 1905.93 | 1209.24 | 696.69 | 0.00 | 0.00 |
November | 1418.91 | 1244.56 | 1489.58 | 875.71 | 613.87 | 0.00 | 0.00 |
December | 1020.33 | 1627.82 | 1206.98 | 734.56 | 472.42 | 0.00 | 0.00 |
Annual Sum or Average | 2482.70 | 861.37 | 2110.32 | 1219.48 | 890.84 | 0.00 | 0.00 |
Minimum of Months | 1020.33 | 223.83 | 1206.98 | 713.71 | 472.42 | 0.00 | 0.00 |
Maximum of Months | 3862.05 | 1627.82 | 2875.47 | 1771.43 | 1202.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5727.86 | 2291.36 | 5111.51 | 3977.45 | 1134.06 | 0.00 | 0.00 |
February | 5725.69 | 2127.42 | 5002.31 | 3654.01 | 1348.30 | 0.00 | 0.00 |
March | 4311.76 | 1737.98 | 3686.20 | 2228.52 | 1457.67 | 0.00 | 0.00 |
April | 3493.40 | 1236.77 | 2874.77 | 1180.03 | 1694.74 | 0.00 | 0.00 |
May | 2355.35 | 898.73 | 1917.24 | 421.75 | 1495.49 | 0.00 | 0.00 |
June | 2330.88 | 581.53 | 1621.83 | 199.87 | 1421.96 | 0.00 | 0.00 |
July | 2784.44 | 379.49 | 1794.64 | 286.58 | 1508.05 | 0.00 | 0.00 |
August | 3662.07 | 448.12 | 2467.75 | 802.14 | 1665.61 | 0.00 | 0.00 |
September | 4715.35 | 799.67 | 3412.35 | 1902.82 | 1509.53 | 0.00 | 0.00 |
October | 5822.02 | 1346.75 | 4668.49 | 3438.31 | 1230.18 | 0.00 | 0.00 |
November | 6002.59 | 1885.72 | 5199.81 | 3990.83 | 1208.98 | 0.00 | 0.00 |
December | 6250.79 | 2392.12 | 5545.83 | 4574.73 | 971.11 | 0.00 | 0.00 |
Annual Sum or Average | 4424.46 | 1339.75 | 3600.74 | 2214.06 | 1386.68 | 0.00 | 0.00 |
Minimum of Months | 2330.88 | 379.49 | 1621.83 | 199.87 | 971.11 | 0.00 | 0.00 |
Maximum of Months | 6250.79 | 2392.12 | 5545.83 | 4574.73 | 1694.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1209.15 | 1701.34 | 1316.70 | 750.88 | 565.83 | 0.00 | 0.00 |
February | 1664.35 | 1589.72 | 1695.04 | 979.17 | 715.87 | 0.00 | 0.00 |
March | 1963.20 | 1296.28 | 1893.17 | 1007.77 | 885.40 | 0.00 | 0.00 |
April | 2703.07 | 922.59 | 2416.25 | 1285.94 | 1130.31 | 0.00 | 0.00 |
May | 2760.55 | 646.68 | 2290.96 | 1180.46 | 1110.49 | 0.00 | 0.00 |
June | 3300.16 | 450.64 | 2455.90 | 1370.37 | 1085.53 | 0.00 | 0.00 |
July | 3099.59 | 307.71 | 2215.14 | 1084.06 | 1131.08 | 0.00 | 0.00 |
August | 3041.62 | 384.94 | 2263.49 | 1046.95 | 1216.53 | 0.00 | 0.00 |
September | 2636.55 | 570.35 | 2044.46 | 1076.73 | 967.72 | 0.00 | 0.00 |
October | 2145.27 | 1011.07 | 1870.40 | 1162.52 | 707.88 | 0.00 | 0.00 |
November | 1411.29 | 1442.35 | 1468.26 | 863.81 | 604.45 | 0.00 | 0.00 |
December | 1120.22 | 1901.88 | 1269.75 | 796.27 | 473.48 | 0.00 | 0.00 |
Annual Sum or Average | 2256.61 | 1015.99 | 1933.47 | 1049.91 | 883.55 | 0.00 | 0.00 |
Minimum of Months | 1120.22 | 307.71 | 1269.75 | 750.88 | 473.48 | 0.00 | 0.00 |
Maximum of Months | 3300.16 | 1901.88 | 2455.90 | 1370.37 | 1216.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 187.42 | 2314.77 | 691.42 | 0.00 | 691.42 | 0.00 | 0.00 |
February | 362.04 | 2092.78 | 864.15 | 0.00 | 864.15 | 0.00 | 0.00 |
March | 721.60 | 1650.93 | 1090.02 | 0.00 | 1090.02 | 0.00 | 0.00 |
April | 1140.20 | 1103.10 | 1382.90 | 11.84 | 1371.06 | 0.00 | 0.00 |
May | 1554.44 | 812.34 | 1503.22 | 96.92 | 1406.31 | 0.00 | 0.00 |
June | 2351.35 | 543.00 | 1708.07 | 279.52 | 1428.54 | 0.00 | 0.00 |
July | 2326.95 | 369.15 | 1567.74 | 130.48 | 1437.25 | 0.00 | 0.00 |
August | 1980.17 | 416.26 | 1454.34 | 32.56 | 1421.78 | 0.00 | 0.00 |
September | 1361.04 | 732.40 | 1163.02 | 0.30 | 1162.72 | 0.00 | 0.00 |
October | 653.55 | 1286.89 | 867.85 | 0.00 | 867.85 | 0.00 | 0.00 |
November | 259.08 | 1833.06 | 737.01 | 0.00 | 737.01 | 0.00 | 0.00 |
December | 68.59 | 2418.82 | 588.50 | 0.00 | 588.50 | 0.00 | 0.00 |
Annual Sum or Average | 1084.28 | 1293.94 | 1135.84 | 46.05 | 1089.79 | 0.00 | 0.00 |
Minimum of Months | 68.59 | 369.15 | 588.50 | 0.00 | 588.50 | 0.00 | 0.00 |
Maximum of Months | 2351.35 | 2418.82 | 1708.07 | 279.52 | 1437.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1104.99 | 1431.91 | 1276.54 | 713.70 | 562.83 | 0.00 | 0.00 |
February | 1461.65 | 1306.71 | 1550.97 | 836.14 | 714.83 | 0.00 | 0.00 |
March | 2158.63 | 1039.02 | 2045.96 | 1163.09 | 882.87 | 0.00 | 0.00 |
April | 3223.50 | 728.69 | 2795.20 | 1592.41 | 1202.79 | 0.00 | 0.00 |
May | 3248.27 | 553.68 | 2667.21 | 1520.02 | 1147.19 | 0.00 | 0.00 |
June | 3845.27 | 357.61 | 2875.46 | 1771.42 | 1104.04 | 0.00 | 0.00 |
July | 3705.99 | 247.85 | 2660.71 | 1521.50 | 1139.21 | 0.00 | 0.00 |
August | 3560.69 | 278.66 | 2632.96 | 1451.60 | 1181.36 | 0.00 | 0.00 |
September | 2809.54 | 470.99 | 2191.49 | 1226.16 | 965.33 | 0.00 | 0.00 |
October | 2163.84 | 810.66 | 1905.93 | 1209.24 | 696.69 | 0.00 | 0.00 |
November | 1439.54 | 1156.43 | 1489.58 | 875.71 | 613.87 | 0.00 | 0.00 |
December | 1045.66 | 1504.58 | 1206.98 | 734.56 | 472.42 | 0.00 | 0.00 |
Annual Sum or Average | 2485.18 | 821.52 | 2110.31 | 1219.47 | 890.84 | 0.00 | 0.00 |
Minimum of Months | 1045.66 | 247.85 | 1206.98 | 713.70 | 472.42 | 0.00 | 0.00 |
Maximum of Months | 3845.27 | 1504.58 | 2875.46 | 1771.42 | 1202.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5701.53 | 2251.44 | 5111.66 | 3977.58 | 1134.08 | 0.00 | 0.00 |
February | 5700.43 | 2080.75 | 5002.46 | 3654.13 | 1348.33 | 0.00 | 0.00 |
March | 4298.27 | 1686.63 | 3686.30 | 2228.59 | 1457.71 | 0.00 | 0.00 |
April | 3489.64 | 1198.02 | 2874.84 | 1180.07 | 1694.77 | 0.00 | 0.00 |
May | 2355.11 | 872.53 | 1917.28 | 421.77 | 1495.52 | 0.00 | 0.00 |
June | 2343.87 | 571.36 | 1621.86 | 199.88 | 1421.98 | 0.00 | 0.00 |
July | 2790.90 | 387.11 | 1794.67 | 286.59 | 1508.08 | 0.00 | 0.00 |
August | 3663.74 | 454.37 | 2467.80 | 802.16 | 1665.64 | 0.00 | 0.00 |
September | 4691.83 | 788.83 | 3412.44 | 1902.88 | 1509.56 | 0.00 | 0.00 |
October | 5793.19 | 1325.48 | 4668.63 | 3438.42 | 1230.21 | 0.00 | 0.00 |
November | 5979.65 | 1837.42 | 5199.97 | 3990.96 | 1209.01 | 0.00 | 0.00 |
December | 6234.89 | 2310.82 | 5546.01 | 4574.88 | 971.13 | 0.00 | 0.00 |
Annual Sum or Average | 4412.95 | 1309.78 | 3600.84 | 2214.13 | 1386.70 | 0.00 | 0.00 |
Minimum of Months | 2343.87 | 387.11 | 1621.86 | 199.88 | 971.13 | 0.00 | 0.00 |
Maximum of Months | 6234.89 | 2310.82 | 5546.01 | 4574.88 | 1694.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1243.93 | 1556.78 | 1316.70 | 750.87 | 565.83 | 0.00 | 0.00 |
February | 1711.31 | 1427.24 | 1695.03 | 979.17 | 715.86 | 0.00 | 0.00 |
March | 2022.83 | 1141.28 | 1893.16 | 1007.77 | 885.39 | 0.00 | 0.00 |
April | 2763.57 | 809.98 | 2416.24 | 1285.93 | 1130.31 | 0.00 | 0.00 |
May | 2779.95 | 602.89 | 2290.95 | 1180.46 | 1110.49 | 0.00 | 0.00 |
June | 3324.50 | 420.62 | 2455.89 | 1370.36 | 1085.53 | 0.00 | 0.00 |
July | 3130.47 | 282.78 | 2215.14 | 1084.06 | 1131.08 | 0.00 | 0.00 |
August | 3094.68 | 325.46 | 2263.48 | 1046.95 | 1216.53 | 0.00 | 0.00 |
September | 2655.67 | 527.70 | 2044.45 | 1076.73 | 967.72 | 0.00 | 0.00 |
October | 2184.59 | 903.91 | 1870.40 | 1162.52 | 707.88 | 0.00 | 0.00 |
November | 1468.77 | 1241.37 | 1468.25 | 863.81 | 604.45 | 0.00 | 0.00 |
December | 1172.92 | 1605.39 | 1269.74 | 796.26 | 473.48 | 0.00 | 0.00 |
Annual Sum or Average | 2298.09 | 901.17 | 1933.46 | 1049.91 | 883.55 | 0.00 | 0.00 |
Minimum of Months | 1172.92 | 282.78 | 1269.74 | 750.87 | 473.48 | 0.00 | 0.00 |
Maximum of Months | 3324.50 | 1605.39 | 2455.89 | 1370.36 | 1216.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 221.52 | 2145.22 | 691.42 | 0.00 | 691.42 | 0.00 | 0.00 |
February | 399.50 | 1950.00 | 864.15 | 0.00 | 864.15 | 0.00 | 0.00 |
March | 762.34 | 1539.10 | 1090.02 | 0.00 | 1090.02 | 0.00 | 0.00 |
April | 1166.06 | 1043.00 | 1382.90 | 11.84 | 1371.06 | 0.00 | 0.00 |
May | 1564.19 | 786.32 | 1503.22 | 96.92 | 1406.31 | 0.00 | 0.00 |
June | 2341.47 | 539.47 | 1708.07 | 279.52 | 1428.54 | 0.00 | 0.00 |
July | 2307.65 | 374.60 | 1567.74 | 130.48 | 1437.25 | 0.00 | 0.00 |
August | 1966.00 | 417.29 | 1454.34 | 32.56 | 1421.78 | 0.00 | 0.00 |
September | 1361.03 | 714.74 | 1163.02 | 0.30 | 1162.72 | 0.00 | 0.00 |
October | 679.10 | 1202.71 | 867.85 | 0.00 | 867.85 | 0.00 | 0.00 |
November | 298.78 | 1677.74 | 737.01 | 0.00 | 737.01 | 0.00 | 0.00 |
December | 89.57 | 2231.87 | 588.50 | 0.00 | 588.50 | 0.00 | 0.00 |
Annual Sum or Average | 1100.02 | 1214.96 | 1135.84 | 46.05 | 1089.79 | 0.00 | 0.00 |
Minimum of Months | 89.57 | 374.60 | 588.50 | 0.00 | 588.50 | 0.00 | 0.00 |
Maximum of Months | 2341.47 | 2231.87 | 1708.07 | 279.52 | 1437.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1143.61 | 1335.48 | 1276.54 | 713.70 | 562.83 | 0.00 | 0.00 |
February | 1494.33 | 1226.65 | 1550.97 | 836.14 | 714.83 | 0.00 | 0.00 |
March | 2178.72 | 985.35 | 2045.96 | 1163.09 | 882.87 | 0.00 | 0.00 |
April | 3226.63 | 704.57 | 2795.20 | 1592.41 | 1202.79 | 0.00 | 0.00 |
May | 3242.35 | 544.36 | 2667.21 | 1520.02 | 1147.19 | 0.00 | 0.00 |
June | 3831.24 | 359.32 | 2875.46 | 1771.42 | 1104.04 | 0.00 | 0.00 |
July | 3688.64 | 254.25 | 2660.71 | 1521.50 | 1139.21 | 0.00 | 0.00 |
August | 3545.79 | 282.96 | 2632.96 | 1451.60 | 1181.36 | 0.00 | 0.00 |
September | 2802.49 | 468.68 | 2191.49 | 1226.16 | 965.33 | 0.00 | 0.00 |
October | 2172.99 | 776.19 | 1905.93 | 1209.24 | 696.69 | 0.00 | 0.00 |
November | 1473.02 | 1075.64 | 1489.58 | 875.71 | 613.87 | 0.00 | 0.00 |
December | 1076.11 | 1395.59 | 1206.98 | 734.56 | 472.42 | 0.00 | 0.00 |
Annual Sum or Average | 2494.07 | 781.90 | 2110.31 | 1219.47 | 890.84 | 0.00 | 0.00 |
Minimum of Months | 1076.11 | 254.25 | 1206.98 | 713.70 | 472.42 | 0.00 | 0.00 |
Maximum of Months | 3831.24 | 1395.59 | 2875.46 | 1771.42 | 1202.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5756.20 | 2098.80 | 5111.66 | 3977.58 | 1134.08 | 0.00 | 0.00 |
February | 5741.80 | 1949.35 | 5002.46 | 3654.13 | 1348.33 | 0.00 | 0.00 |
March | 4326.31 | 1593.34 | 3686.30 | 2228.59 | 1457.71 | 0.00 | 0.00 |
April | 3499.40 | 1145.75 | 2874.84 | 1180.07 | 1694.77 | 0.00 | 0.00 |
May | 2356.84 | 846.40 | 1917.28 | 421.77 | 1495.52 | 0.00 | 0.00 |
June | 2333.04 | 566.03 | 1621.86 | 199.88 | 1421.98 | 0.00 | 0.00 |
July | 2771.23 | 392.54 | 1794.67 | 286.59 | 1508.08 | 0.00 | 0.00 |
August | 3645.81 | 456.58 | 2467.80 | 802.16 | 1665.64 | 0.00 | 0.00 |
September | 4682.87 | 778.96 | 3412.44 | 1902.88 | 1509.56 | 0.00 | 0.00 |
October | 5809.14 | 1267.12 | 4668.63 | 3438.42 | 1230.21 | 0.00 | 0.00 |
November | 6024.44 | 1712.75 | 5199.97 | 3990.96 | 1209.01 | 0.00 | 0.00 |
December | 6279.64 | 2143.54 | 5546.01 | 4574.88 | 971.13 | 0.00 | 0.00 |
Annual Sum or Average | 4428.12 | 1242.29 | 3600.84 | 2214.13 | 1386.70 | 0.00 | 0.00 |
Minimum of Months | 2333.04 | 392.54 | 1621.86 | 199.88 | 971.13 | 0.00 | 0.00 |
Maximum of Months | 6279.64 | 2143.54 | 5546.01 | 4574.88 | 1694.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1262.98 | 1461.14 | 1316.70 | 750.87 | 565.83 | 0.00 | 0.00 |
February | 1726.39 | 1348.44 | 1695.03 | 979.17 | 715.86 | 0.00 | 0.00 |
March | 2035.24 | 1084.21 | 1893.16 | 1007.77 | 885.39 | 0.00 | 0.00 |
April | 2767.90 | 779.63 | 2416.24 | 1285.93 | 1130.31 | 0.00 | 0.00 |
May | 2778.90 | 588.51 | 2290.95 | 1180.46 | 1110.49 | 0.00 | 0.00 |
June | 3315.50 | 418.56 | 2455.89 | 1370.36 | 1085.53 | 0.00 | 0.00 |
July | 3117.15 | 285.21 | 2215.14 | 1084.06 | 1131.08 | 0.00 | 0.00 |
August | 3083.96 | 326.31 | 2263.48 | 1046.95 | 1216.53 | 0.00 | 0.00 |
September | 2651.27 | 521.44 | 2044.45 | 1076.73 | 967.72 | 0.00 | 0.00 |
October | 2189.98 | 864.27 | 1870.40 | 1162.52 | 707.88 | 0.00 | 0.00 |
November | 1485.27 | 1161.23 | 1468.25 | 863.81 | 604.45 | 0.00 | 0.00 |
December | 1186.10 | 1501.46 | 1269.74 | 796.26 | 473.48 | 0.00 | 0.00 |
Annual Sum or Average | 2301.97 | 859.25 | 1933.46 | 1049.91 | 883.55 | 0.00 | 0.00 |
Minimum of Months | 1186.10 | 285.21 | 1269.74 | 750.87 | 473.48 | 0.00 | 0.00 |
Maximum of Months | 3315.50 | 1501.46 | 2455.89 | 1370.36 | 1216.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.368075E+09 | 0.679837E+10 | 0.185186E+10 | 0.00 | 0.185186E+10 | 0.00 | 0.00 |
February | 0.722815E+09 | 0.555717E+10 | 0.209053E+10 | 0.00 | 0.209053E+10 | 0.00 | 0.00 |
March | 0.176208E+10 | 0.484160E+10 | 0.291947E+10 | 0.00 | 0.291947E+10 | 0.00 | 0.00 |
April | 0.282693E+10 | 0.308960E+10 | 0.358442E+10 | 30687837.23 | 0.355374E+10 | 0.00 | 0.00 |
May | 0.410646E+10 | 0.227860E+10 | 0.402617E+10 | 0.259577E+09 | 0.376660E+10 | 0.00 | 0.00 |
June | 0.606011E+10 | 0.143466E+10 | 0.442724E+10 | 0.724499E+09 | 0.370274E+10 | 0.00 | 0.00 |
July | 0.619837E+10 | 0.980958E+09 | 0.419897E+10 | 0.349475E+09 | 0.384949E+10 | 0.00 | 0.00 |
August | 0.523945E+10 | 0.113272E+10 | 0.389524E+10 | 87204798.52 | 0.380804E+10 | 0.00 | 0.00 |
September | 0.348095E+10 | 0.199691E+10 | 0.301451E+10 | 773664.47 | 0.301373E+10 | 0.00 | 0.00 |
October | 0.163537E+10 | 0.376351E+10 | 0.232441E+10 | 0.00 | 0.232441E+10 | 0.00 | 0.00 |
November | 0.525630E+09 | 0.533779E+10 | 0.191029E+10 | 0.00 | 0.191029E+10 | 0.00 | 0.00 |
December | 95996022.26 | 0.731907E+10 | 0.157622E+10 | 0.00 | 0.157622E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.330222E+11 | 0.445310E+11 | 0.358193E+11 | 0.145222E+10 | 0.343671E+11 | 0.00 | 0.00 |
Minimum of Months | 95996022.26 | 0.980958E+09 | 0.157622E+10 | 0.00 | 0.157622E+10 | 0.00 | 0.00 |
Maximum of Months | 0.619837E+10 | 0.731907E+10 | 0.442724E+10 | 0.724499E+09 | 0.384949E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.287397E+10 | 0.411188E+10 | 0.341909E+10 | 0.191159E+10 | 0.150750E+10 | 0.00 | 0.00 |
February | 0.346949E+10 | 0.337654E+10 | 0.375211E+10 | 0.202279E+10 | 0.172932E+10 | 0.00 | 0.00 |
March | 0.575184E+10 | 0.293707E+10 | 0.547992E+10 | 0.311524E+10 | 0.236469E+10 | 0.00 | 0.00 |
April | 0.838649E+10 | 0.191574E+10 | 0.724519E+10 | 0.412755E+10 | 0.311764E+10 | 0.00 | 0.00 |
May | 0.873660E+10 | 0.152280E+10 | 0.714389E+10 | 0.407124E+10 | 0.307265E+10 | 0.00 | 0.00 |
June | 0.100104E+11 | 0.912678E+09 | 0.745322E+10 | 0.459154E+10 | 0.286168E+10 | 0.00 | 0.00 |
July | 0.997922E+10 | 0.599497E+09 | 0.712649E+10 | 0.407521E+10 | 0.305127E+10 | 0.00 | 0.00 |
August | 0.959345E+10 | 0.662349E+09 | 0.705214E+10 | 0.388798E+10 | 0.316416E+10 | 0.00 | 0.00 |
September | 0.730181E+10 | 0.125486E+10 | 0.568037E+10 | 0.317822E+10 | 0.250215E+10 | 0.00 | 0.00 |
October | 0.578033E+10 | 0.228493E+10 | 0.510485E+10 | 0.323883E+10 | 0.186602E+10 | 0.00 | 0.00 |
November | 0.367781E+10 | 0.322590E+10 | 0.386100E+10 | 0.226985E+10 | 0.159115E+10 | 0.00 | 0.00 |
December | 0.273284E+10 | 0.435995E+10 | 0.323279E+10 | 0.196745E+10 | 0.126534E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.782943E+11 | 0.271642E+11 | 0.665511E+11 | 0.384575E+11 | 0.280936E+11 | 0.00 | 0.00 |
Minimum of Months | 0.273284E+10 | 0.599497E+09 | 0.323279E+10 | 0.191159E+10 | 0.126534E+10 | 0.00 | 0.00 |
Maximum of Months | 0.100104E+11 | 0.435995E+10 | 0.745322E+10 | 0.459154E+10 | 0.316416E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.153415E+11 | 0.613718E+10 | 0.136907E+11 | 0.106532E+11 | 0.303746E+10 | 0.00 | 0.00 |
February | 0.138516E+11 | 0.514666E+10 | 0.121016E+11 | 0.883977E+10 | 0.326181E+10 | 0.00 | 0.00 |
March | 0.115486E+11 | 0.465500E+10 | 0.987311E+10 | 0.596887E+10 | 0.390424E+10 | 0.00 | 0.00 |
April | 0.905488E+10 | 0.320570E+10 | 0.745141E+10 | 0.305864E+10 | 0.439277E+10 | 0.00 | 0.00 |
May | 0.630857E+10 | 0.240715E+10 | 0.513515E+10 | 0.112962E+10 | 0.400552E+10 | 0.00 | 0.00 |
June | 0.604164E+10 | 0.150734E+10 | 0.420379E+10 | 0.518063E+09 | 0.368573E+10 | 0.00 | 0.00 |
July | 0.745785E+10 | 0.101643E+10 | 0.480675E+10 | 0.767583E+09 | 0.403917E+10 | 0.00 | 0.00 |
August | 0.980849E+10 | 0.120025E+10 | 0.660961E+10 | 0.214844E+10 | 0.446117E+10 | 0.00 | 0.00 |
September | 0.122222E+11 | 0.207275E+10 | 0.884481E+10 | 0.493210E+10 | 0.391271E+10 | 0.00 | 0.00 |
October | 0.155937E+11 | 0.360713E+10 | 0.125041E+11 | 0.920917E+10 | 0.329493E+10 | 0.00 | 0.00 |
November | 0.155587E+11 | 0.488778E+10 | 0.134779E+11 | 0.103442E+11 | 0.313368E+10 | 0.00 | 0.00 |
December | 0.167421E+11 | 0.640704E+10 | 0.148540E+11 | 0.122529E+11 | 0.260102E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.139530E+12 | 0.422504E+11 | 0.113553E+12 | 0.698227E+11 | 0.437302E+11 | 0.00 | 0.00 |
Minimum of Months | 0.604164E+10 | 0.101643E+10 | 0.420379E+10 | 0.518063E+09 | 0.260102E+10 | 0.00 | 0.00 |
Maximum of Months | 0.167421E+11 | 0.640704E+10 | 0.148540E+11 | 0.122529E+11 | 0.446117E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.323860E+10 | 0.455687E+10 | 0.352666E+10 | 0.201114E+10 | 0.151552E+10 | 0.00 | 0.00 |
February | 0.402639E+10 | 0.384584E+10 | 0.410064E+10 | 0.236882E+10 | 0.173182E+10 | 0.00 | 0.00 |
March | 0.525823E+10 | 0.347194E+10 | 0.507066E+10 | 0.269921E+10 | 0.237145E+10 | 0.00 | 0.00 |
April | 0.700637E+10 | 0.239134E+10 | 0.626292E+10 | 0.333316E+10 | 0.292976E+10 | 0.00 | 0.00 |
May | 0.739385E+10 | 0.173208E+10 | 0.613610E+10 | 0.316175E+10 | 0.297435E+10 | 0.00 | 0.00 |
June | 0.855402E+10 | 0.116805E+10 | 0.636569E+10 | 0.355199E+10 | 0.281370E+10 | 0.00 | 0.00 |
July | 0.830193E+10 | 0.824172E+09 | 0.593304E+10 | 0.290355E+10 | 0.302949E+10 | 0.00 | 0.00 |
August | 0.814667E+10 | 0.103102E+10 | 0.606252E+10 | 0.280416E+10 | 0.325836E+10 | 0.00 | 0.00 |
September | 0.683393E+10 | 0.147835E+10 | 0.529924E+10 | 0.279089E+10 | 0.250834E+10 | 0.00 | 0.00 |
October | 0.574588E+10 | 0.270806E+10 | 0.500969E+10 | 0.311370E+10 | 0.189598E+10 | 0.00 | 0.00 |
November | 0.365807E+10 | 0.373858E+10 | 0.380573E+10 | 0.223900E+10 | 0.156673E+10 | 0.00 | 0.00 |
December | 0.300039E+10 | 0.509400E+10 | 0.340089E+10 | 0.213272E+10 | 0.126817E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.711643E+11 | 0.320403E+11 | 0.609738E+11 | 0.331101E+11 | 0.278637E+11 | 0.00 | 0.00 |
Minimum of Months | 0.300039E+10 | 0.824172E+09 | 0.340089E+10 | 0.201114E+10 | 0.126817E+10 | 0.00 | 0.00 |
Maximum of Months | 0.855402E+10 | 0.509400E+10 | 0.636569E+10 | 0.355199E+10 | 0.325836E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.501986E+09 | 0.619989E+10 | 0.185189E+10 | 0.00 | 0.185189E+10 | 0.00 | 0.00 |
February | 0.875856E+09 | 0.506285E+10 | 0.209056E+10 | 0.00 | 0.209056E+10 | 0.00 | 0.00 |
March | 0.193274E+10 | 0.442186E+10 | 0.291952E+10 | 0.00 | 0.291952E+10 | 0.00 | 0.00 |
April | 0.295540E+10 | 0.285924E+10 | 0.358447E+10 | 30688752.42 | 0.355379E+10 | 0.00 | 0.00 |
May | 0.416342E+10 | 0.217577E+10 | 0.402623E+10 | 0.259584E+09 | 0.376665E+10 | 0.00 | 0.00 |
June | 0.609469E+10 | 0.140747E+10 | 0.442731E+10 | 0.724521E+09 | 0.370279E+10 | 0.00 | 0.00 |
July | 0.623250E+10 | 0.988743E+09 | 0.419903E+10 | 0.349485E+09 | 0.384954E+10 | 0.00 | 0.00 |
August | 0.530367E+10 | 0.111492E+10 | 0.389530E+10 | 87207399.21 | 0.380809E+10 | 0.00 | 0.00 |
September | 0.352782E+10 | 0.189837E+10 | 0.301455E+10 | 773687.54 | 0.301377E+10 | 0.00 | 0.00 |
October | 0.175047E+10 | 0.344680E+10 | 0.232444E+10 | 0.00 | 0.232444E+10 | 0.00 | 0.00 |
November | 0.671524E+09 | 0.475130E+10 | 0.191032E+10 | 0.00 | 0.191032E+10 | 0.00 | 0.00 |
December | 0.183714E+09 | 0.647858E+10 | 0.157624E+10 | 0.00 | 0.157624E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.341938E+11 | 0.408058E+11 | 0.358199E+11 | 0.145226E+10 | 0.343676E+11 | 0.00 | 0.00 |
Minimum of Months | 0.183714E+09 | 0.988743E+09 | 0.157624E+10 | 0.00 | 0.157624E+10 | 0.00 | 0.00 |
Maximum of Months | 0.623250E+10 | 0.647858E+10 | 0.442731E+10 | 0.724521E+09 | 0.384954E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.295959E+10 | 0.383524E+10 | 0.341908E+10 | 0.191159E+10 | 0.150749E+10 | 0.00 | 0.00 |
February | 0.353602E+10 | 0.316120E+10 | 0.375210E+10 | 0.202278E+10 | 0.172931E+10 | 0.00 | 0.00 |
March | 0.578169E+10 | 0.278291E+10 | 0.547990E+10 | 0.311522E+10 | 0.236468E+10 | 0.00 | 0.00 |
April | 0.835531E+10 | 0.188876E+10 | 0.724516E+10 | 0.412753E+10 | 0.311763E+10 | 0.00 | 0.00 |
May | 0.870017E+10 | 0.148298E+10 | 0.714386E+10 | 0.407123E+10 | 0.307263E+10 | 0.00 | 0.00 |
June | 0.996695E+10 | 0.926914E+09 | 0.745319E+10 | 0.459152E+10 | 0.286167E+10 | 0.00 | 0.00 |
July | 0.992613E+10 | 0.663845E+09 | 0.712646E+10 | 0.407520E+10 | 0.305126E+10 | 0.00 | 0.00 |
August | 0.953696E+10 | 0.746360E+09 | 0.705211E+10 | 0.388796E+10 | 0.316415E+10 | 0.00 | 0.00 |
September | 0.728232E+10 | 0.122080E+10 | 0.568035E+10 | 0.317821E+10 | 0.250214E+10 | 0.00 | 0.00 |
October | 0.579562E+10 | 0.217127E+10 | 0.510483E+10 | 0.323882E+10 | 0.186601E+10 | 0.00 | 0.00 |
November | 0.373130E+10 | 0.299745E+10 | 0.386098E+10 | 0.226984E+10 | 0.159114E+10 | 0.00 | 0.00 |
December | 0.280068E+10 | 0.402987E+10 | 0.323277E+10 | 0.196744E+10 | 0.126533E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.783727E+11 | 0.259076E+11 | 0.665508E+11 | 0.384573E+11 | 0.280934E+11 | 0.00 | 0.00 |
Minimum of Months | 0.280068E+10 | 0.663845E+09 | 0.323277E+10 | 0.191159E+10 | 0.126533E+10 | 0.00 | 0.00 |
Maximum of Months | 0.996695E+10 | 0.402987E+10 | 0.745319E+10 | 0.459152E+10 | 0.316415E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.152710E+11 | 0.603026E+10 | 0.136911E+11 | 0.106536E+11 | 0.303753E+10 | 0.00 | 0.00 |
February | 0.137905E+11 | 0.503376E+10 | 0.121019E+11 | 0.884006E+10 | 0.326189E+10 | 0.00 | 0.00 |
March | 0.115125E+11 | 0.451746E+10 | 0.987338E+10 | 0.596907E+10 | 0.390432E+10 | 0.00 | 0.00 |
April | 0.904516E+10 | 0.310527E+10 | 0.745159E+10 | 0.305874E+10 | 0.439285E+10 | 0.00 | 0.00 |
May | 0.630792E+10 | 0.233699E+10 | 0.513525E+10 | 0.112966E+10 | 0.400559E+10 | 0.00 | 0.00 |
June | 0.607531E+10 | 0.148096E+10 | 0.420386E+10 | 0.518080E+09 | 0.368578E+10 | 0.00 | 0.00 |
July | 0.747515E+10 | 0.103683E+10 | 0.480684E+10 | 0.767608E+09 | 0.403923E+10 | 0.00 | 0.00 |
August | 0.981295E+10 | 0.121697E+10 | 0.660977E+10 | 0.214851E+10 | 0.446126E+10 | 0.00 | 0.00 |
September | 0.121612E+11 | 0.204465E+10 | 0.884505E+10 | 0.493226E+10 | 0.391279E+10 | 0.00 | 0.00 |
October | 0.155165E+11 | 0.355016E+10 | 0.125045E+11 | 0.920947E+10 | 0.329499E+10 | 0.00 | 0.00 |
November | 0.154992E+11 | 0.476259E+10 | 0.134783E+11 | 0.103446E+11 | 0.313375E+10 | 0.00 | 0.00 |
December | 0.166995E+11 | 0.618929E+10 | 0.148544E+11 | 0.122533E+11 | 0.260108E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.139167E+12 | 0.413052E+11 | 0.113556E+12 | 0.698249E+11 | 0.437311E+11 | 0.00 | 0.00 |
Minimum of Months | 0.607531E+10 | 0.103683E+10 | 0.420386E+10 | 0.518080E+09 | 0.260108E+10 | 0.00 | 0.00 |
Maximum of Months | 0.166995E+11 | 0.618929E+10 | 0.148544E+11 | 0.122533E+11 | 0.446126E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.333174E+10 | 0.416967E+10 | 0.352665E+10 | 0.201114E+10 | 0.151551E+10 | 0.00 | 0.00 |
February | 0.414001E+10 | 0.345278E+10 | 0.410063E+10 | 0.236881E+10 | 0.173182E+10 | 0.00 | 0.00 |
March | 0.541794E+10 | 0.305680E+10 | 0.507064E+10 | 0.269920E+10 | 0.237144E+10 | 0.00 | 0.00 |
April | 0.716317E+10 | 0.209947E+10 | 0.626289E+10 | 0.333314E+10 | 0.292975E+10 | 0.00 | 0.00 |
May | 0.744583E+10 | 0.161477E+10 | 0.613607E+10 | 0.316173E+10 | 0.297434E+10 | 0.00 | 0.00 |
June | 0.861712E+10 | 0.109025E+10 | 0.636567E+10 | 0.355198E+10 | 0.281369E+10 | 0.00 | 0.00 |
July | 0.838464E+10 | 0.757386E+09 | 0.593302E+10 | 0.290354E+10 | 0.302948E+10 | 0.00 | 0.00 |
August | 0.828879E+10 | 0.871703E+09 | 0.606249E+10 | 0.280415E+10 | 0.325834E+10 | 0.00 | 0.00 |
September | 0.688348E+10 | 0.136779E+10 | 0.529921E+10 | 0.279088E+10 | 0.250833E+10 | 0.00 | 0.00 |
October | 0.585121E+10 | 0.242104E+10 | 0.500967E+10 | 0.311369E+10 | 0.189598E+10 | 0.00 | 0.00 |
November | 0.380704E+10 | 0.321763E+10 | 0.380571E+10 | 0.223899E+10 | 0.156673E+10 | 0.00 | 0.00 |
December | 0.314156E+10 | 0.429987E+10 | 0.340087E+10 | 0.213271E+10 | 0.126816E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.724725E+11 | 0.284192E+11 | 0.609735E+11 | 0.331100E+11 | 0.278636E+11 | 0.00 | 0.00 |
Minimum of Months | 0.314156E+10 | 0.757386E+09 | 0.340087E+10 | 0.201114E+10 | 0.126816E+10 | 0.00 | 0.00 |
Maximum of Months | 0.861712E+10 | 0.429987E+10 | 0.636567E+10 | 0.355198E+10 | 0.325834E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.593322E+09 | 0.574576E+10 | 0.185189E+10 | 0.00 | 0.185189E+10 | 0.00 | 0.00 |
February | 0.966477E+09 | 0.471743E+10 | 0.209056E+10 | 0.00 | 0.209056E+10 | 0.00 | 0.00 |
March | 0.204186E+10 | 0.412233E+10 | 0.291952E+10 | 0.00 | 0.291952E+10 | 0.00 | 0.00 |
April | 0.302243E+10 | 0.270346E+10 | 0.358447E+10 | 30688752.42 | 0.355379E+10 | 0.00 | 0.00 |
May | 0.418953E+10 | 0.210609E+10 | 0.402623E+10 | 0.259584E+09 | 0.376665E+10 | 0.00 | 0.00 |
June | 0.606910E+10 | 0.139831E+10 | 0.442731E+10 | 0.724521E+09 | 0.370279E+10 | 0.00 | 0.00 |
July | 0.618082E+10 | 0.100332E+10 | 0.419903E+10 | 0.349485E+09 | 0.384954E+10 | 0.00 | 0.00 |
August | 0.526573E+10 | 0.111768E+10 | 0.389530E+10 | 87207399.21 | 0.380809E+10 | 0.00 | 0.00 |
September | 0.352779E+10 | 0.185261E+10 | 0.301455E+10 | 773687.54 | 0.301377E+10 | 0.00 | 0.00 |
October | 0.181890E+10 | 0.322134E+10 | 0.232444E+10 | 0.00 | 0.232444E+10 | 0.00 | 0.00 |
November | 0.774439E+09 | 0.434869E+10 | 0.191032E+10 | 0.00 | 0.191032E+10 | 0.00 | 0.00 |
December | 0.239900E+09 | 0.597784E+10 | 0.157624E+10 | 0.00 | 0.157624E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.346903E+11 | 0.383149E+11 | 0.358199E+11 | 0.145226E+10 | 0.343676E+11 | 0.00 | 0.00 |
Minimum of Months | 0.239900E+09 | 0.100332E+10 | 0.157624E+10 | 0.00 | 0.157624E+10 | 0.00 | 0.00 |
Maximum of Months | 0.618082E+10 | 0.597784E+10 | 0.442731E+10 | 0.724521E+09 | 0.384954E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.306303E+10 | 0.357694E+10 | 0.341908E+10 | 0.191159E+10 | 0.150749E+10 | 0.00 | 0.00 |
February | 0.361508E+10 | 0.296750E+10 | 0.375210E+10 | 0.202278E+10 | 0.172931E+10 | 0.00 | 0.00 |
March | 0.583548E+10 | 0.263916E+10 | 0.547990E+10 | 0.311522E+10 | 0.236468E+10 | 0.00 | 0.00 |
April | 0.836342E+10 | 0.182625E+10 | 0.724516E+10 | 0.412753E+10 | 0.311763E+10 | 0.00 | 0.00 |
May | 0.868430E+10 | 0.145801E+10 | 0.714386E+10 | 0.407123E+10 | 0.307263E+10 | 0.00 | 0.00 |
June | 0.993058E+10 | 0.931349E+09 | 0.745319E+10 | 0.459152E+10 | 0.286167E+10 | 0.00 | 0.00 |
July | 0.987966E+10 | 0.680974E+09 | 0.712646E+10 | 0.407520E+10 | 0.305126E+10 | 0.00 | 0.00 |
August | 0.949704E+10 | 0.757889E+09 | 0.705211E+10 | 0.388796E+10 | 0.316415E+10 | 0.00 | 0.00 |
September | 0.726405E+10 | 0.121483E+10 | 0.568035E+10 | 0.317821E+10 | 0.250214E+10 | 0.00 | 0.00 |
October | 0.582012E+10 | 0.207895E+10 | 0.510483E+10 | 0.323882E+10 | 0.186601E+10 | 0.00 | 0.00 |
November | 0.381808E+10 | 0.278806E+10 | 0.386098E+10 | 0.226984E+10 | 0.159114E+10 | 0.00 | 0.00 |
December | 0.288225E+10 | 0.373794E+10 | 0.323277E+10 | 0.196744E+10 | 0.126533E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.786531E+11 | 0.246578E+11 | 0.665508E+11 | 0.384573E+11 | 0.280934E+11 | 0.00 | 0.00 |
Minimum of Months | 0.288225E+10 | 0.680974E+09 | 0.323277E+10 | 0.191159E+10 | 0.126533E+10 | 0.00 | 0.00 |
Maximum of Months | 0.993058E+10 | 0.373794E+10 | 0.745319E+10 | 0.459152E+10 | 0.316415E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.154174E+11 | 0.562142E+10 | 0.136911E+11 | 0.106536E+11 | 0.303753E+10 | 0.00 | 0.00 |
February | 0.138906E+11 | 0.471587E+10 | 0.121019E+11 | 0.884006E+10 | 0.326189E+10 | 0.00 | 0.00 |
March | 0.115876E+11 | 0.426759E+10 | 0.987338E+10 | 0.596907E+10 | 0.390432E+10 | 0.00 | 0.00 |
April | 0.907045E+10 | 0.296977E+10 | 0.745159E+10 | 0.305874E+10 | 0.439285E+10 | 0.00 | 0.00 |
May | 0.631257E+10 | 0.226701E+10 | 0.513525E+10 | 0.112966E+10 | 0.400559E+10 | 0.00 | 0.00 |
June | 0.604724E+10 | 0.146716E+10 | 0.420386E+10 | 0.518080E+09 | 0.368578E+10 | 0.00 | 0.00 |
July | 0.742246E+10 | 0.105139E+10 | 0.480684E+10 | 0.767608E+09 | 0.403923E+10 | 0.00 | 0.00 |
August | 0.976493E+10 | 0.122291E+10 | 0.660977E+10 | 0.214851E+10 | 0.446126E+10 | 0.00 | 0.00 |
September | 0.121380E+11 | 0.201906E+10 | 0.884505E+10 | 0.493226E+10 | 0.391279E+10 | 0.00 | 0.00 |
October | 0.155592E+11 | 0.339387E+10 | 0.125045E+11 | 0.920947E+10 | 0.329499E+10 | 0.00 | 0.00 |
November | 0.156154E+11 | 0.443945E+10 | 0.134783E+11 | 0.103446E+11 | 0.313375E+10 | 0.00 | 0.00 |
December | 0.168194E+11 | 0.574127E+10 | 0.148544E+11 | 0.122533E+11 | 0.260108E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.139645E+12 | 0.391768E+11 | 0.113556E+12 | 0.698249E+11 | 0.437311E+11 | 0.00 | 0.00 |
Minimum of Months | 0.604724E+10 | 0.105139E+10 | 0.420386E+10 | 0.518080E+09 | 0.260108E+10 | 0.00 | 0.00 |
Maximum of Months | 0.168194E+11 | 0.574127E+10 | 0.148544E+11 | 0.122533E+11 | 0.446126E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.338276E+10 | 0.391352E+10 | 0.352665E+10 | 0.201114E+10 | 0.151551E+10 | 0.00 | 0.00 |
February | 0.417648E+10 | 0.326215E+10 | 0.410063E+10 | 0.236881E+10 | 0.173182E+10 | 0.00 | 0.00 |
March | 0.545120E+10 | 0.290395E+10 | 0.507064E+10 | 0.269920E+10 | 0.237144E+10 | 0.00 | 0.00 |
April | 0.717440E+10 | 0.202080E+10 | 0.626289E+10 | 0.333314E+10 | 0.292975E+10 | 0.00 | 0.00 |
May | 0.744300E+10 | 0.157626E+10 | 0.613607E+10 | 0.316173E+10 | 0.297434E+10 | 0.00 | 0.00 |
June | 0.859377E+10 | 0.108491E+10 | 0.636567E+10 | 0.355198E+10 | 0.281369E+10 | 0.00 | 0.00 |
July | 0.834897E+10 | 0.763917E+09 | 0.593302E+10 | 0.290354E+10 | 0.302948E+10 | 0.00 | 0.00 |
August | 0.826008E+10 | 0.873987E+09 | 0.606249E+10 | 0.280415E+10 | 0.325834E+10 | 0.00 | 0.00 |
September | 0.687210E+10 | 0.135156E+10 | 0.529921E+10 | 0.279088E+10 | 0.250833E+10 | 0.00 | 0.00 |
October | 0.586563E+10 | 0.231486E+10 | 0.500967E+10 | 0.311369E+10 | 0.189598E+10 | 0.00 | 0.00 |
November | 0.384981E+10 | 0.300992E+10 | 0.380571E+10 | 0.223899E+10 | 0.156673E+10 | 0.00 | 0.00 |
December | 0.317685E+10 | 0.402150E+10 | 0.340087E+10 | 0.213271E+10 | 0.126816E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.725950E+11 | 0.270973E+11 | 0.609735E+11 | 0.331100E+11 | 0.278636E+11 | 0.00 | 0.00 |
Minimum of Months | 0.317685E+10 | 0.763917E+09 | 0.340087E+10 | 0.201114E+10 | 0.126816E+10 | 0.00 | 0.00 |
Maximum of Months | 0.859377E+10 | 0.402150E+10 | 0.636567E+10 | 0.355198E+10 | 0.325834E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.390126E+11 | -0.379884E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102418E+10 | 58.98 | 0.00 | 0.00 |
February | 0.357123E+11 | -0.347870E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -925372710.8 | 58.98 | 0.00 | 0.00 |
March | 0.409304E+11 | -0.399036E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102678E+10 | 58.99 | 0.00 | 0.00 |
April | 0.352565E+11 | -0.342678E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988678012.0 | 58.97 | 0.00 | 0.00 |
May | 0.350665E+11 | -0.340432E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102328E+10 | 58.98 | 0.00 | 0.00 |
June | 0.323105E+11 | -0.313197E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990866419.6 | 58.98 | 0.00 | 0.00 |
July | 0.292912E+11 | -0.282729E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101833E+10 | 58.97 | 0.00 | 0.00 |
August | 0.316443E+11 | -0.306223E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102208E+10 | 58.97 | 0.00 | 0.00 |
September | 0.297255E+11 | -0.287383E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987202804.4 | 58.98 | 0.00 | 0.00 |
October | 0.326758E+11 | -0.316567E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101906E+10 | 58.98 | 0.00 | 0.00 |
November | 0.344802E+11 | -0.334934E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986821456.2 | 58.97 | 0.00 | 0.00 |
December | 0.365992E+11 | -0.355788E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102046E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.412705E+12 | -0.400672E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120331E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.292912E+11 | -0.399036E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102678E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.409304E+11 | -0.282729E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -925372710.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.63 | 0.61 | 01-JAN-07:49 | 9983.58 | 35.71 | 269.67 | 280.33 | 2412.11 | 27.61 | 200.33 | 273.67 |
February | 282.00 | 0.62 | 0.61 | 01-FEB-07:30 | 12478.43 | 37.33 | 272.00 | 272.17 | 1629.83 | 22.64 | 147.50 | 255.33 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-06:00 | 2038.04 | 17.59 | 10.67 | 325.33 | 1168.03 | 20.29 | 129.83 | 291.33 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:19 | 1629.07 | 17.61 | 0.00 | 345.83 | 980.68 | 20.59 | 143.17 | 317.00 |
May | 378.00 | 0.64 | 0.61 | 01-MAY-05:00 | 1250.34 | 16.87 | 0.00 | 364.17 | 772.16 | 19.91 | 80.33 | 325.83 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:40 | 996.80 | 15.88 | 0.00 | 357.50 | 622.85 | 19.01 | 68.00 | 305.67 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:30 | 1210.29 | 16.69 | 0.00 | 366.17 | 739.00 | 19.78 | 96.50 | 323.50 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:00 | 1516.00 | 17.35 | 0.00 | 366.67 | 902.46 | 20.37 | 162.33 | 332.00 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:10 | 2012.70 | 18.01 | 16.50 | 322.17 | 1089.78 | 20.27 | 119.83 | 294.83 |
October | 329.00 | 0.63 | 0.61 | 01-OCT-06:40 | 5887.10 | 27.46 | 181.17 | 312.83 | 1465.51 | 20.51 | 94.33 | 299.33 |
November | 284.17 | 0.62 | 0.61 | 01-NOV-06:49 | 11348.75 | 37.07 | 266.33 | 278.67 | 2357.19 | 27.21 | 176.33 | 269.67 |
December | 265.67 | 0.63 | 0.61 | 01-DEC-07:49 | 11187.07 | 35.94 | 227.83 | 259.67 | 3607.08 | 31.07 | 176.83 | 258.00 |
Annual Sum or Average | 4149.83 | 0.63 | 4507.77 | 23.23 | 1244.17 | 3851.50 | 1369.61 | 21.99 | 1595.33 | 3546.17 | ||
Minimum of Months | 265.67 | 0.62 | 0.61 | 996.80 | 15.88 | 0.00 | 259.67 | 622.85 | 19.01 | 68.00 | 255.33 | |
Maximum of Months | 412.83 | 0.64 | 0.61 | 12478.43 | 37.33 | 272.00 | 366.67 | 3607.08 | 31.07 | 200.33 | 332.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.61 | 01-JAN-07:49 | 2346.43 | 19.02 | 85.50 | 250.00 | 1367.16 | 19.95 | 74.50 | 219.50 |
February | 282.00 | 0.63 | 0.61 | 01-FEB-07:19 | 2959.37 | 18.78 | 73.50 | 255.17 | 1742.26 | 19.70 | 68.00 | 223.67 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-06:49 | 3058.68 | 15.95 | 55.67 | 315.50 | 1544.61 | 14.31 | 2.83 | 281.33 |
April | 381.83 | 0.63 | 0.61 | 01-APR-05:00 | 4516.97 | 15.90 | 55.00 | 350.33 | 1659.18 | 14.61 | 0.00 | 327.67 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-05:49 | 3458.49 | 12.52 | 0.00 | 367.67 | 1962.24 | 14.08 | 0.00 | 336.83 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:19 | 3272.28 | 11.59 | 0.00 | 377.50 | 1929.88 | 13.16 | 0.00 | 341.00 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:10 | 3331.71 | 12.39 | 0.00 | 375.67 | 1777.49 | 13.94 | 0.00 | 343.00 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:40 | 4153.31 | 13.17 | 5.50 | 374.00 | 1574.40 | 14.46 | 0.00 | 347.83 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-05:00 | 3350.10 | 15.90 | 54.50 | 322.00 | 1967.52 | 14.61 | 5.50 | 296.50 |
October | 329.00 | 0.64 | 0.61 | 01-OCT-06:40 | 3105.55 | 17.95 | 82.67 | 290.00 | 1761.21 | 17.23 | 53.83 | 263.67 |
November | 284.17 | 0.64 | 0.61 | 01-NOV-06:49 | 2547.34 | 19.29 | 76.67 | 253.50 | 1338.83 | 18.84 | 52.83 | 224.67 |
December | 265.67 | 0.65 | 0.61 | 01-DEC-07:49 | 2724.86 | 19.52 | 80.33 | 231.50 | 1678.75 | 20.21 | 67.50 | 193.17 |
Annual Sum or Average | 4149.83 | 0.63 | 3298.45 | 15.61 | 569.33 | 3762.83 | 1705.47 | 15.90 | 325.00 | 3398.83 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 2346.43 | 11.59 | 0.00 | 231.50 | 1338.83 | 13.16 | 0.00 | 193.17 | |
Maximum of Months | 412.83 | 0.65 | 0.61 | 4516.97 | 19.52 | 85.50 | 377.50 | 1967.52 | 20.21 | 74.50 | 347.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.65 | 0.61 | 01-JAN-08:39 | 554.35 | 0.00 | 0.00 | 221.67 | 358.96 | 0.00 | 0.00 | 154.50 |
February | 282.00 | 0.64 | 0.61 | 01-FEB-07:49 | 649.00 | 0.00 | 0.00 | 239.67 | 433.56 | 0.00 | 0.00 | 181.33 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-06:00 | 781.73 | 0.00 | 0.00 | 306.00 | 491.58 | 0.00 | 0.00 | 248.67 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:10 | 979.02 | 0.00 | 0.00 | 357.17 | 627.51 | 0.00 | 0.00 | 332.50 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-05:00 | 1154.77 | 0.00 | 0.00 | 386.17 | 664.98 | 0.00 | 0.00 | 346.00 |
June | 412.83 | 0.62 | 0.61 | 01-JUN-05:30 | 1198.66 | 0.00 | 0.00 | 395.17 | 629.22 | 0.00 | 0.00 | 367.17 |
July | 395.33 | 0.62 | 0.61 | 01-JUL-06:19 | 1173.46 | 0.00 | 0.00 | 391.33 | 673.44 | 0.00 | 0.00 | 363.33 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:49 | 1038.04 | 0.00 | 0.00 | 378.00 | 664.37 | 0.00 | 0.00 | 359.67 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:10 | 822.67 | 0.00 | 0.00 | 318.83 | 530.80 | 0.00 | 0.00 | 273.00 |
October | 329.00 | 0.65 | 0.61 | 01-OCT-06:00 | 590.23 | 0.00 | 0.00 | 268.33 | 409.55 | 0.00 | 0.00 | 207.50 |
November | 284.17 | 0.64 | 0.61 | 01-NOV-07:10 | 581.40 | 0.00 | 0.00 | 238.00 | 393.27 | 0.00 | 0.00 | 176.83 |
December | 265.67 | 0.66 | 0.61 | 01-DEC-08:09 | 479.62 | 0.00 | 0.00 | 208.17 | 338.35 | 0.00 | 0.00 | 132.50 |
Annual Sum or Average | 4149.83 | 0.64 | 867.67 | 0.00 | 0.00 | 3708.50 | 534.70 | 0.00 | 0.00 | 3143.00 | ||
Minimum of Months | 265.67 | 0.62 | 0.61 | 479.62 | 0.00 | 0.00 | 208.17 | 338.35 | 0.00 | 0.00 | 132.50 | |
Maximum of Months | 412.83 | 0.66 | 0.61 | 1198.66 | 0.00 | 0.00 | 395.17 | 673.44 | 0.00 | 0.00 | 367.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.61 | 01-JAN-08:39 | 1793.29 | 17.03 | 57.00 | 254.33 | 1030.66 | 18.29 | 54.17 | 219.17 |
February | 282.00 | 0.63 | 0.61 | 01-FEB-07:00 | 2975.88 | 19.06 | 74.50 | 252.83 | 1690.82 | 19.87 | 65.00 | 222.33 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-07:10 | 3065.47 | 17.49 | 78.33 | 316.50 | 1192.29 | 14.38 | 2.67 | 281.50 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:30 | 4039.96 | 15.67 | 54.00 | 351.17 | 1520.28 | 14.65 | 0.00 | 328.00 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-06:10 | 2840.90 | 12.65 | 0.00 | 377.67 | 1630.22 | 14.26 | 0.00 | 354.17 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:49 | 2956.30 | 11.61 | 0.00 | 372.50 | 1791.21 | 13.18 | 0.00 | 341.00 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:30 | 2891.29 | 12.52 | 0.00 | 375.83 | 1624.10 | 14.03 | 0.00 | 345.00 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-06:10 | 2885.14 | 13.34 | 5.50 | 365.83 | 1525.38 | 14.61 | 0.00 | 341.17 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:30 | 3219.97 | 15.87 | 56.67 | 323.50 | 1250.62 | 14.56 | 5.00 | 298.33 |
October | 329.00 | 0.64 | 0.61 | 01-OCT-07:10 | 2963.95 | 17.85 | 81.83 | 290.50 | 1561.92 | 17.40 | 56.00 | 260.50 |
November | 284.17 | 0.63 | 0.61 | 01-NOV-07:10 | 2797.56 | 19.52 | 78.50 | 263.50 | 1781.00 | 21.05 | 76.67 | 231.33 |
December | 265.67 | 0.65 | 0.61 | 01-DEC-08:09 | 2581.54 | 19.54 | 80.00 | 238.67 | 1658.54 | 21.43 | 78.67 | 205.50 |
Annual Sum or Average | 4149.83 | 0.63 | 2946.95 | 15.65 | 566.33 | 3782.83 | 1522.54 | 16.08 | 338.17 | 3428.00 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 1793.29 | 11.61 | 0.00 | 238.67 | 1030.66 | 13.18 | 0.00 | 205.50 | |
Maximum of Months | 412.83 | 0.65 | 0.61 | 4039.96 | 19.54 | 81.83 | 377.67 | 1791.21 | 21.43 | 78.67 | 354.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.63 | 0.61 | 01-JAN-07:49 | 9974.80 | 34.80 | 269.50 | 279.67 | 2483.77 | 23.88 | 127.17 | 274.50 |
February | 282.00 | 0.62 | 0.61 | 01-FEB-07:30 | 12475.25 | 36.96 | 271.17 | 271.67 | 1853.36 | 20.73 | 79.50 | 261.17 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-06:00 | 2023.97 | 11.36 | 10.67 | 324.17 | 1221.05 | 15.98 | 3.50 | 292.67 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:19 | 1613.11 | 12.12 | 0.00 | 344.00 | 1018.08 | 17.00 | 0.00 | 319.17 |
May | 378.00 | 0.64 | 0.61 | 01-MAY-06:10 | 1237.55 | 11.53 | 0.00 | 363.17 | 799.97 | 16.41 | 0.00 | 327.33 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:49 | 987.45 | 10.35 | 0.00 | 356.17 | 645.70 | 15.37 | 0.00 | 310.33 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:30 | 1196.02 | 11.20 | 0.00 | 365.00 | 764.88 | 16.15 | 0.00 | 325.50 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:00 | 1498.13 | 11.86 | 0.00 | 365.00 | 934.64 | 16.71 | 0.00 | 334.17 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:10 | 2004.98 | 12.22 | 16.50 | 321.83 | 1136.01 | 16.18 | 0.00 | 296.50 |
October | 329.00 | 0.63 | 0.61 | 01-OCT-06:40 | 5932.55 | 24.06 | 181.17 | 316.33 | 1532.86 | 15.90 | 14.67 | 300.17 |
November | 284.17 | 0.63 | 0.61 | 01-NOV-06:49 | 11342.34 | 36.45 | 265.83 | 278.17 | 2431.85 | 23.23 | 105.67 | 270.83 |
December | 265.67 | 0.64 | 0.61 | 01-DEC-07:49 | 11142.95 | 34.20 | 222.83 | 258.83 | 3693.20 | 27.77 | 146.67 | 259.33 |
Annual Sum or Average | 4149.83 | 0.63 | 4498.71 | 19.08 | 1237.67 | 3844.00 | 1428.35 | 18.30 | 477.17 | 3571.67 | ||
Minimum of Months | 265.67 | 0.62 | 0.61 | 987.45 | 10.35 | 0.00 | 258.83 | 645.70 | 15.37 | 0.00 | 259.33 | |
Maximum of Months | 412.83 | 0.64 | 0.61 | 12475.25 | 36.96 | 271.17 | 365.00 | 3693.20 | 27.77 | 146.67 | 334.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.61 | 01-JAN-07:49 | 2351.55 | 16.91 | 85.50 | 249.50 | 1250.47 | 16.24 | 55.33 | 219.83 |
February | 282.00 | 0.63 | 0.61 | 01-FEB-07:19 | 2965.43 | 16.60 | 73.67 | 254.67 | 1776.09 | 17.94 | 68.17 | 226.83 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-06:49 | 3075.45 | 13.12 | 55.67 | 315.00 | 1587.03 | 11.63 | 2.83 | 284.33 |
April | 381.83 | 0.63 | 0.61 | 01-APR-05:00 | 4119.79 | 13.02 | 55.00 | 350.00 | 1709.30 | 12.04 | 0.00 | 329.33 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-05:49 | 3449.35 | 8.95 | 0.00 | 367.17 | 2015.68 | 11.61 | 0.00 | 339.33 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:19 | 3283.19 | 7.87 | 0.00 | 376.50 | 1979.88 | 10.66 | 0.00 | 344.67 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:10 | 3333.84 | 8.74 | 0.00 | 375.17 | 1829.07 | 11.43 | 0.00 | 345.33 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:40 | 4149.18 | 9.69 | 5.50 | 373.33 | 1621.64 | 11.95 | 0.00 | 349.33 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-05:00 | 3364.46 | 13.07 | 54.50 | 321.50 | 2009.55 | 12.07 | 5.50 | 298.83 |
October | 329.00 | 0.64 | 0.61 | 01-OCT-06:40 | 3033.49 | 15.27 | 78.67 | 289.17 | 1803.13 | 15.19 | 53.83 | 267.00 |
November | 284.17 | 0.64 | 0.61 | 01-NOV-06:49 | 2189.51 | 14.85 | 54.50 | 252.83 | 1374.03 | 16.80 | 53.00 | 229.50 |
December | 265.67 | 0.65 | 0.61 | 01-DEC-07:49 | 2735.87 | 17.66 | 80.33 | 231.83 | 1665.07 | 18.02 | 63.67 | 196.00 |
Annual Sum or Average | 4149.83 | 0.63 | 3235.89 | 12.54 | 543.33 | 3756.67 | 1735.40 | 13.43 | 302.33 | 3430.33 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 2189.51 | 7.87 | 0.00 | 231.83 | 1250.47 | 10.66 | 0.00 | 196.00 | |
Maximum of Months | 412.83 | 0.65 | 0.61 | 4149.18 | 17.66 | 85.50 | 376.50 | 2015.68 | 18.02 | 68.17 | 349.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.65 | 0.61 | 01-JAN-08:39 | 545.18 | 0.00 | 0.00 | 219.67 | 369.66 | 0.00 | 0.00 | 162.50 |
February | 282.00 | 0.64 | 0.61 | 01-FEB-07:49 | 639.85 | 0.00 | 0.00 | 237.67 | 446.98 | 0.00 | 0.00 | 186.50 |
March | 351.33 | 0.64 | 0.61 | 01-MAR-06:00 | 771.46 | 0.00 | 0.00 | 304.17 | 507.72 | 0.00 | 0.00 | 253.33 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:10 | 966.92 | 0.00 | 0.00 | 356.33 | 647.28 | 0.00 | 0.00 | 334.17 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-05:00 | 1143.68 | 0.00 | 0.00 | 385.67 | 687.75 | 0.00 | 0.00 | 348.83 |
June | 412.83 | 0.62 | 0.61 | 01-JUN-05:30 | 1191.84 | 0.00 | 0.00 | 394.50 | 653.00 | 0.00 | 0.00 | 370.00 |
July | 395.33 | 0.62 | 0.61 | 01-JUL-06:19 | 1165.48 | 0.00 | 0.00 | 390.50 | 696.89 | 0.00 | 0.00 | 364.33 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:49 | 1045.96 | 0.00 | 0.00 | 380.33 | 684.85 | 0.00 | 0.00 | 360.67 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:10 | 812.63 | 0.00 | 0.00 | 317.17 | 548.21 | 0.00 | 0.00 | 276.67 |
October | 329.00 | 0.65 | 0.61 | 01-OCT-06:00 | 584.40 | 0.00 | 0.00 | 266.67 | 423.30 | 0.00 | 0.00 | 215.33 |
November | 284.17 | 0.65 | 0.61 | 01-NOV-07:10 | 571.66 | 0.00 | 0.00 | 235.50 | 404.64 | 0.00 | 0.00 | 182.83 |
December | 265.67 | 0.66 | 0.61 | 01-DEC-08:09 | 471.95 | 0.00 | 0.00 | 204.50 | 348.22 | 0.00 | 0.00 | 140.17 |
Annual Sum or Average | 4149.83 | 0.64 | 860.24 | 0.00 | 0.00 | 3692.67 | 552.27 | 0.00 | 0.00 | 3195.33 | ||
Minimum of Months | 265.67 | 0.62 | 0.61 | 471.95 | 0.00 | 0.00 | 204.50 | 348.22 | 0.00 | 0.00 | 140.17 | |
Maximum of Months | 412.83 | 0.66 | 0.61 | 1191.84 | 0.00 | 0.00 | 394.50 | 696.89 | 0.00 | 0.00 | 370.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.61 | 01-JAN-08:39 | 1797.63 | 14.53 | 57.17 | 253.67 | 1057.13 | 16.18 | 53.83 | 223.17 |
February | 282.00 | 0.63 | 0.61 | 01-FEB-07:00 | 2984.58 | 16.80 | 74.50 | 252.83 | 1559.73 | 16.19 | 48.17 | 224.17 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-07:10 | 3077.87 | 15.06 | 78.33 | 315.67 | 1227.43 | 11.72 | 1.83 | 285.00 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:30 | 4046.36 | 12.82 | 54.00 | 350.17 | 1564.43 | 12.10 | 0.00 | 328.83 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-06:19 | 2836.03 | 9.19 | 0.00 | 377.33 | 1675.14 | 11.82 | 0.00 | 356.17 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:49 | 2964.60 | 7.96 | 0.00 | 371.33 | 1837.22 | 10.72 | 0.00 | 345.17 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:30 | 2886.34 | 9.01 | 0.00 | 375.17 | 1668.24 | 11.62 | 0.00 | 347.67 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-06:10 | 2871.14 | 9.95 | 5.50 | 365.50 | 1565.54 | 12.17 | 0.00 | 343.83 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:30 | 3233.80 | 13.04 | 56.67 | 322.67 | 1292.35 | 12.02 | 5.00 | 299.67 |
October | 329.00 | 0.64 | 0.61 | 01-OCT-07:10 | 2981.42 | 15.62 | 81.83 | 290.83 | 1603.00 | 15.42 | 56.00 | 263.50 |
November | 284.17 | 0.63 | 0.61 | 01-NOV-07:19 | 2802.90 | 17.36 | 78.50 | 262.83 | 1813.84 | 19.31 | 76.67 | 234.50 |
December | 265.67 | 0.65 | 0.61 | 01-DEC-08:09 | 2592.79 | 17.65 | 80.00 | 238.50 | 1689.41 | 19.80 | 79.00 | 210.17 |
Annual Sum or Average | 4149.83 | 0.63 | 2951.69 | 12.81 | 566.50 | 3776.50 | 1550.52 | 13.68 | 320.50 | 3461.83 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 1797.63 | 7.96 | 0.00 | 238.50 | 1057.13 | 10.72 | 0.00 | 210.17 | |
Maximum of Months | 412.83 | 0.65 | 0.61 | 4046.36 | 17.65 | 81.83 | 377.33 | 1837.22 | 19.80 | 79.00 | 356.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.63 | 0.61 | 01-JAN-07:49 | 9973.83 | 34.78 | 269.50 | 279.67 | 2485.02 | 23.86 | 127.17 | 274.50 |
February | 282.00 | 0.62 | 0.61 | 01-FEB-07:30 | 12474.97 | 36.94 | 271.17 | 271.67 | 1854.72 | 20.71 | 79.33 | 261.17 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-06:00 | 2024.69 | 11.32 | 10.67 | 324.17 | 1222.24 | 15.96 | 3.50 | 292.67 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:19 | 1613.60 | 12.08 | 0.00 | 344.00 | 1019.00 | 16.98 | 0.00 | 319.17 |
May | 378.00 | 0.64 | 0.61 | 01-MAY-06:10 | 1237.77 | 11.49 | 0.00 | 363.17 | 800.63 | 16.39 | 0.00 | 327.33 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:49 | 987.64 | 10.30 | 0.00 | 356.00 | 646.21 | 15.35 | 0.00 | 310.50 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:30 | 1196.29 | 11.16 | 0.00 | 364.83 | 765.53 | 16.13 | 0.00 | 325.50 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:00 | 1498.57 | 11.82 | 0.00 | 365.00 | 935.51 | 16.69 | 0.00 | 334.17 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:10 | 2005.55 | 12.18 | 16.50 | 321.83 | 1137.04 | 16.16 | 0.00 | 296.50 |
October | 329.00 | 0.63 | 0.61 | 01-OCT-06:40 | 5932.69 | 24.03 | 181.17 | 316.33 | 1533.85 | 15.89 | 14.67 | 300.17 |
November | 284.17 | 0.63 | 0.61 | 01-NOV-06:49 | 11341.37 | 36.43 | 265.83 | 278.17 | 2433.13 | 23.22 | 105.67 | 270.83 |
December | 265.67 | 0.64 | 0.61 | 01-DEC-07:49 | 11141.52 | 34.18 | 222.83 | 258.83 | 3694.26 | 27.76 | 146.67 | 259.33 |
Annual Sum or Average | 4149.83 | 0.63 | 4498.74 | 19.05 | 1237.67 | 3843.67 | 1429.30 | 18.28 | 477.00 | 3571.83 | ||
Minimum of Months | 265.67 | 0.62 | 0.61 | 987.64 | 10.30 | 0.00 | 258.83 | 646.21 | 15.35 | 0.00 | 259.33 | |
Maximum of Months | 412.83 | 0.64 | 0.61 | 12474.97 | 36.94 | 271.17 | 365.00 | 3694.26 | 27.76 | 146.67 | 334.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.61 | 01-JAN-07:49 | 2351.21 | 16.90 | 85.50 | 249.33 | 1250.99 | 16.23 | 55.33 | 219.83 |
February | 282.00 | 0.63 | 0.61 | 01-FEB-07:19 | 2964.94 | 16.59 | 73.67 | 254.67 | 1776.73 | 17.93 | 68.17 | 227.00 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-06:49 | 3075.15 | 13.10 | 55.67 | 315.00 | 1587.80 | 11.62 | 2.83 | 284.33 |
April | 381.83 | 0.63 | 0.61 | 01-APR-05:00 | 4119.21 | 13.00 | 55.00 | 350.00 | 1710.20 | 12.03 | 0.00 | 329.33 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-05:49 | 3448.82 | 8.93 | 0.00 | 367.33 | 2016.49 | 11.60 | 0.00 | 339.33 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:19 | 3282.82 | 7.85 | 0.00 | 376.50 | 1980.54 | 10.65 | 0.00 | 344.83 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:10 | 3302.97 | 8.73 | 0.00 | 375.17 | 1829.83 | 11.42 | 0.00 | 345.33 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:40 | 3805.25 | 9.67 | 5.50 | 373.33 | 1622.48 | 11.94 | 0.00 | 349.50 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-05:00 | 3364.04 | 13.05 | 54.50 | 321.50 | 2010.31 | 12.06 | 5.50 | 298.83 |
October | 329.00 | 0.64 | 0.61 | 01-OCT-06:40 | 3032.94 | 15.25 | 78.67 | 289.17 | 1803.62 | 15.18 | 53.83 | 267.00 |
November | 284.17 | 0.64 | 0.61 | 01-NOV-06:49 | 2188.88 | 14.83 | 54.50 | 252.83 | 1374.54 | 16.79 | 53.00 | 229.50 |
December | 265.67 | 0.65 | 0.61 | 01-DEC-07:49 | 2735.34 | 17.65 | 80.33 | 231.83 | 1665.46 | 18.01 | 63.67 | 196.00 |
Annual Sum or Average | 4149.83 | 0.63 | 3198.68 | 12.52 | 543.33 | 3756.67 | 1736.09 | 13.42 | 302.33 | 3430.83 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 2188.88 | 7.85 | 0.00 | 231.83 | 1250.99 | 10.65 | 0.00 | 196.00 | |
Maximum of Months | 412.83 | 0.65 | 0.61 | 4119.21 | 17.65 | 85.50 | 376.50 | 2016.49 | 18.01 | 68.17 | 349.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.65 | 0.61 | 01-JAN-08:39 | 545.02 | 0.00 | 0.00 | 219.67 | 369.92 | 0.00 | 0.00 | 162.67 |
February | 282.00 | 0.64 | 0.61 | 01-FEB-07:49 | 639.60 | 0.00 | 0.00 | 237.50 | 447.25 | 0.00 | 0.00 | 186.50 |
March | 351.33 | 0.64 | 0.61 | 01-MAR-06:00 | 771.41 | 0.00 | 0.00 | 304.17 | 508.13 | 0.00 | 0.00 | 253.50 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:10 | 966.70 | 0.00 | 0.00 | 356.33 | 647.72 | 0.00 | 0.00 | 334.17 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-05:00 | 1143.53 | 0.00 | 0.00 | 385.67 | 688.25 | 0.00 | 0.00 | 349.00 |
June | 412.83 | 0.62 | 0.61 | 01-JUN-05:30 | 1191.76 | 0.00 | 0.00 | 394.50 | 653.47 | 0.00 | 0.00 | 370.00 |
July | 395.33 | 0.62 | 0.61 | 01-JUL-06:19 | 1165.39 | 0.00 | 0.00 | 390.33 | 697.41 | 0.00 | 0.00 | 364.33 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:49 | 1045.79 | 0.00 | 0.00 | 380.33 | 685.36 | 0.00 | 0.00 | 360.67 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:10 | 812.47 | 0.00 | 0.00 | 317.17 | 548.60 | 0.00 | 0.00 | 276.83 |
October | 329.00 | 0.65 | 0.61 | 01-OCT-06:00 | 584.14 | 0.00 | 0.00 | 266.50 | 423.51 | 0.00 | 0.00 | 215.50 |
November | 284.17 | 0.65 | 0.61 | 01-NOV-07:10 | 571.36 | 0.00 | 0.00 | 235.67 | 404.86 | 0.00 | 0.00 | 183.00 |
December | 265.67 | 0.66 | 0.61 | 01-DEC-08:09 | 471.63 | 0.00 | 0.00 | 204.33 | 348.37 | 0.00 | 0.00 | 140.33 |
Annual Sum or Average | 4149.83 | 0.64 | 860.07 | 0.00 | 0.00 | 3692.17 | 552.65 | 0.00 | 0.00 | 3196.50 | ||
Minimum of Months | 265.67 | 0.62 | 0.61 | 471.63 | 0.00 | 0.00 | 204.33 | 348.37 | 0.00 | 0.00 | 140.33 | |
Maximum of Months | 412.83 | 0.66 | 0.61 | 1191.76 | 0.00 | 0.00 | 394.50 | 697.41 | 0.00 | 0.00 | 370.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.61 | 01-JAN-08:39 | 1797.24 | 14.52 | 57.17 | 253.50 | 1057.65 | 16.17 | 53.83 | 223.33 |
February | 282.00 | 0.63 | 0.61 | 01-FEB-07:00 | 2984.04 | 16.79 | 74.50 | 252.83 | 1560.35 | 16.18 | 48.17 | 224.17 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-07:10 | 3077.67 | 15.04 | 78.33 | 315.67 | 1228.21 | 11.71 | 1.83 | 284.83 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:30 | 4046.07 | 12.81 | 54.00 | 350.17 | 1565.24 | 12.09 | 0.00 | 328.83 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-06:19 | 2835.73 | 9.17 | 0.00 | 377.33 | 1675.91 | 11.81 | 0.00 | 356.33 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:49 | 2964.37 | 7.95 | 0.00 | 371.17 | 1837.91 | 10.71 | 0.00 | 345.17 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:30 | 2886.14 | 8.99 | 0.00 | 375.17 | 1669.09 | 11.61 | 0.00 | 347.67 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-06:10 | 2870.93 | 9.93 | 5.50 | 365.50 | 1566.53 | 12.16 | 0.00 | 343.83 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:30 | 3233.48 | 13.03 | 56.67 | 322.67 | 1293.16 | 12.01 | 5.00 | 299.67 |
October | 329.00 | 0.64 | 0.61 | 01-OCT-07:10 | 2980.84 | 15.61 | 81.83 | 290.83 | 1603.51 | 15.41 | 56.00 | 263.50 |
November | 284.17 | 0.63 | 0.61 | 01-NOV-07:19 | 2802.35 | 17.35 | 78.50 | 262.67 | 1814.35 | 19.31 | 76.67 | 234.50 |
December | 265.67 | 0.65 | 0.61 | 01-DEC-08:09 | 2592.30 | 17.64 | 80.00 | 238.17 | 1689.78 | 19.79 | 79.00 | 210.17 |
Annual Sum or Average | 4149.83 | 0.63 | 2951.35 | 12.79 | 566.50 | 3775.67 | 1551.23 | 13.68 | 320.50 | 3462.00 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 1797.24 | 7.95 | 0.00 | 238.17 | 1057.65 | 10.71 | 0.00 | 210.17 | |
Maximum of Months | 412.83 | 0.65 | 0.61 | 4046.07 | 17.64 | 81.83 | 377.33 | 1837.91 | 19.79 | 79.00 | 356.33 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.242771E+10 | 21707.52 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.977723E+09 | 18911.15 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20152886.39 | 7559.95 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41954101.47 | 8585.87 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13342226.82 | 2372.06 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.502538E+09 | 14416.74 | 23-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.242771E+10 | 21707.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139300E+09 | 9634.91 | 17-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52947066.54 | 8964.36 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29664752.98 | 4434.77 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139300E+09 | 9634.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.358517E+09 | 10953.16 | 17-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155891E+09 | 9299.93 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12868505.78 | 2863.79 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 240520.54 | 1039.84 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21890445.59 | 2860.36 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29809306.37 | 6960.77 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.312021E+09 | 11030.71 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.891239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.358517E+09 | 11030.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.207264E+09 | 16175.06 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 75639319.11 | 16095.09 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4278883.64 | 3393.33 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8417103.03 | 2068.23 | 26-OCT-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3165094.70 | 1779.09 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 84828112.02 | 16080.61 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.207264E+09 | 16175.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 94848899.63 | 3049.26 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8657335.11 | 1079.09 | 06-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94848899.63 | 3049.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.610099E+11 | 259436.75 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313108E+11 | 230721.23 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.640530E+10 | 131910.10 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.734264E+09 | 65728.40 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.340553E+10 | 154631.86 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.984799E+10 | 196007.79 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.527854E+11 | 256362.88 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165499E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.610099E+11 | 259436.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241326E+11 | 153083.01 | 27-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147614E+11 | 154045.85 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.380640E+10 | 154005.92 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.235026E+09 | 118690.27 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132919E+10 | 152729.57 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.692698E+10 | 153677.08 | 30-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.257705E+11 | 142390.38 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.769621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.257705E+11 | 154045.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.202265E+11 | 161412.59 | 06-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111845E+11 | 160879.41 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342178E+10 | 158599.99 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.274207E+09 | 76604.11 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44173945.72 | 20523.62 | 06-MAY-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180833E+10 | 162164.19 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.606563E+10 | 158790.55 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197514E+11 | 160735.39 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.627765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.202265E+11 | 162164.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.856652E+10 | 175841.29 | 18-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.468509E+10 | 175486.02 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132406E+10 | 175230.32 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145408E+09 | 58093.88 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7095763.61 | 5156.89 | 05-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.557488E+09 | 188979.88 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.992814E+09 | 175023.03 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.725672E+10 | 175517.07 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.856652E+10 | 188979.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189955E+11 | 159801.89 | 30-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111134E+11 | 160102.64 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.392054E+10 | 157823.17 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316530E+09 | 26194.34 | 24-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142500E+09 | 29044.31 | 05-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7653852.17 | 7189.56 | 09-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176002E+10 | 131148.08 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.544657E+10 | 158012.59 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184073E+11 | 159966.88 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.601100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189955E+11 | 160102.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.990318E+10 | 32925.10 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.595916E+10 | 30767.81 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171494E+10 | 20512.77 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.320758E+09 | 12803.49 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23747896.74 | 3976.21 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111878E+10 | 22884.74 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262036E+10 | 26835.31 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100149E+11 | 33890.34 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100149E+11 | 33890.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.255471E+10 | 82660.24 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112959E+10 | 82395.84 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96962229.41 | 81668.39 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3930149.29 | 1809.00 | 26-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.597448E+09 | 82173.54 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227113E+10 | 82717.74 | 26-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.665378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255471E+10 | 82717.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.652661E+10 | 16445.06 | 30-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442287E+10 | 16459.73 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185123E+10 | 16404.77 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.340558E+09 | 16285.88 | 24-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 63493548.54 | 16294.72 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.835901E+09 | 16305.12 | 26-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.292862E+10 | 16434.34 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.673032E+10 | 16461.86 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.673032E+10 | 16461.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.401083E+10 | 18527.04 | 20-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253307E+10 | 18454.17 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108599E+10 | 18305.14 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139162E+09 | 15028.53 | 08-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29714250.49 | 9217.74 | 06-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1434278.07 | 712.70 | 02-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1002214.23 | 1091.57 | 09-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.544200E+09 | 18159.69 | 25-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165734E+10 | 18374.72 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.391378E+10 | 18521.62 | 09-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.401083E+10 | 18527.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.288009E+10 | 19690.57 | 20-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185289E+10 | 19636.06 | 06-FEB-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104048E+10 | 19551.66 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.246443E+09 | 17927.22 | 08-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89081410.15 | 15232.61 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7571203.42 | 2028.48 | 09-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.397478E+09 | 19528.04 | 26-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.921886E+09 | 19624.46 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245347E+10 | 19698.25 | 26-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.988939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.288009E+10 | 19698.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.396445E+10 | 19409.62 | 30-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262936E+10 | 19506.85 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138009E+10 | 19206.42 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.240092E+09 | 9972.94 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 96183354.04 | 10243.47 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14049643.16 | 2465.55 | 09-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2448772.29 | 501.77 | 09-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.633538E+09 | 18966.52 | 26-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173569E+10 | 19332.56 | 27-NOV-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.377622E+10 | 19503.77 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.396445E+10 | 19506.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.115025E+10 | 0.115025E+10 | 26812.55 | 05-JAN-14:30 | 26812.55 | 0.00 |
February | 0.00 | 0.00 | 0.349401E+10 | 0.349401E+10 | 76342.57 | 14-FEB-15:50 | 76342.57 | 0.00 |
March | 0.00 | 0.00 | 0.108938E+11 | 0.108938E+11 | 83025.15 | 08-MAR-16:00 | 83025.15 | 0.00 |
April | 0.00 | 0.00 | 0.405220E+11 | 0.405220E+11 | 119899.85 | 28-APR-14:50 | 119899.85 | 0.00 |
May | 0.00 | 0.00 | 0.604086E+11 | 0.604086E+11 | 119718.13 | 30-MAY-14:30 | 119718.13 | 0.05 |
June | 0.00 | 0.00 | 0.116807E+12 | 0.116804E+12 | 155845.26 | 29-JUN-05:03 | 141980.83 | 0.27 |
July | 0.00 | 0.00 | 0.149613E+12 | 0.145685E+12 | 152113.48 | 31-JUL-15:00 | 143370.64 | 0.74 |
August | 0.00 | 0.00 | 0.159466E+12 | 0.154781E+12 | 172954.22 | 23-AUG-16:00 | 104223.49 | 0.82 |
September | 0.00 | 0.00 | 0.864646E+11 | 0.853273E+11 | 168932.63 | 05-SEP-13:10 | 102624.25 | 0.39 |
October | 0.00 | 0.00 | 0.415551E+11 | 0.415320E+11 | 118501.84 | 10-OCT-16:00 | 118501.84 | 0.09 |
November | 0.00 | 0.00 | 0.271523E+10 | 0.271523E+10 | 41737.98 | 02-NOV-15:00 | 41737.98 | 0.00 |
December | 0.00 | 0.00 | 43718.29 | 43718.29 | 358.70 | 24-DEC-13:52 | 358.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.673089E+12 | 0.663313E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 43718.29 | 43718.29 | 358.70 | 358.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.159466E+12 | 0.154781E+12 | 172954.22 | 143370.64 | 0.82 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.100859E+11 | 0.100859E+11 | 227716.84 | 05-JAN-15:30 | 227716.84 | 0.00 |
February | 0.00 | 0.00 | 0.293658E+11 | 0.293658E+11 | 646229.57 | 14-FEB-16:00 | 646229.57 | 0.00 |
March | 0.00 | 0.00 | 0.840737E+11 | 0.840737E+11 | 646639.43 | 08-MAR-16:00 | 646639.43 | 0.00 |
April | 0.00 | 0.00 | 0.293867E+12 | 0.293867E+12 | 997882.21 | 13-APR-15:20 | 997882.21 | 0.00 |
May | 0.00 | 0.00 | 0.526489E+12 | 0.526489E+12 | 1103399.87 | 19-MAY-15:20 | 1103399.87 | 0.05 |
June | 0.00 | 0.00 | 0.100454E+13 | 0.100451E+13 | 1339774.11 | 28-JUN-14:50 | 1339774.11 | 0.25 |
July | 0.00 | 0.00 | 0.121524E+13 | 0.118889E+13 | 1358682.81 | 31-JUL-15:00 | 1266373.99 | 0.61 |
August | 0.00 | 0.00 | 0.115813E+13 | 0.113352E+13 | 1423974.14 | 14-AUG-03:02 | 728496.70 | 0.63 |
September | 0.00 | 0.00 | 0.758173E+12 | 0.747991E+12 | 1486259.89 | 05-SEP-13:30 | 919945.44 | 0.37 |
October | 0.00 | 0.00 | 0.351671E+12 | 0.351481E+12 | 1044000.65 | 06-OCT-15:30 | 1044000.65 | 0.08 |
November | 0.00 | 0.00 | 0.207018E+11 | 0.207018E+11 | 341173.28 | 02-NOV-15:00 | 341173.28 | 0.00 |
December | 0.00 | 0.00 | 2908108.81 | 2908108.81 | 21811.83 | 24-DEC-14:12 | 21811.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.545234E+13 | 0.539097E+13 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 2908108.81 | 2908108.81 | 21811.83 | 21811.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.121524E+13 | 0.118889E+13 | 1486259.89 | 1339774.11 | 0.63 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.613080E+09 | 0.613080E+09 | 19709.60 | 01-JAN-14:52 | 19709.60 | 0.00 |
February | 0.00 | 0.00 | 0.251712E+10 | 0.251712E+10 | 64592.43 | 14-FEB-16:00 | 64592.43 | 0.00 |
March | 0.00 | 0.00 | 0.727450E+10 | 0.727450E+10 | 67815.17 | 08-MAR-16:00 | 67815.17 | 0.00 |
April | 0.00 | 0.00 | 0.309021E+11 | 0.309021E+11 | 119809.04 | 26-APR-15:00 | 119809.04 | 0.00 |
May | 0.00 | 0.00 | 0.577152E+11 | 0.577152E+11 | 134469.29 | 19-MAY-15:20 | 134469.29 | 0.05 |
June | 0.00 | 0.00 | 0.114307E+12 | 0.114307E+12 | 167547.81 | 28-JUN-14:20 | 167547.81 | 0.25 |
July | 0.00 | 0.00 | 0.139664E+12 | 0.136763E+12 | 174629.60 | 16-JUL-15:21 | 137241.18 | 0.62 |
August | 0.00 | 0.00 | 0.130993E+12 | 0.128478E+12 | 168954.70 | 13-AUG-16:21 | 135318.45 | 0.64 |
September | 0.00 | 0.00 | 0.824280E+11 | 0.816287E+11 | 159621.05 | 05-SEP-13:30 | 101882.30 | 0.35 |
October | 0.00 | 0.00 | 0.352528E+11 | 0.352520E+11 | 119130.34 | 06-OCT-15:20 | 119130.34 | 0.08 |
November | 0.00 | 0.00 | 0.150822E+10 | 0.150822E+10 | 31695.62 | 02-NOV-15:00 | 31695.62 | 0.00 |
December | 0.00 | 0.00 | 592.28 | 592.28 | 0.36 | 25-DEC-22:30 | 0.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.603175E+12 | 0.596958E+12 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 592.28 | 592.28 | 0.36 | 0.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.139664E+12 | 0.136763E+12 | 174629.60 | 167547.81 | 0.64 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 139559.43 | 139559.43 | 232.60 | 02-JAN-15:00 | 232.60 | 0.00 |
February | 0.00 | 0.00 | 0.139424E+10 | 0.139424E+10 | 45143.11 | 13-FEB-16:00 | 45143.11 | 0.00 |
March | 0.00 | 0.00 | 0.380723E+10 | 0.380723E+10 | 47922.30 | 08-MAR-16:00 | 47922.30 | 0.00 |
April | 0.00 | 0.00 | 0.205081E+11 | 0.205081E+11 | 66525.61 | 17-APR-15:00 | 66525.61 | 0.00 |
May | 0.00 | 0.00 | 0.357141E+11 | 0.357125E+11 | 105756.05 | 29-MAY-16:00 | 105756.05 | 0.03 |
June | 0.00 | 0.00 | 0.654134E+11 | 0.654022E+11 | 89996.36 | 29-JUN-05:03 | 85604.44 | 0.20 |
July | 0.00 | 0.00 | 0.789673E+11 | 0.780423E+11 | 142034.72 | 02-JUL-18:07 | 89976.64 | 0.50 |
August | 0.00 | 0.00 | 0.817150E+11 | 0.805558E+11 | 112806.65 | 13-AUG-15:01 | 97609.12 | 0.55 |
September | 0.00 | 0.00 | 0.531638E+11 | 0.525189E+11 | 106112.70 | 05-SEP-13:00 | 71369.56 | 0.30 |
October | 0.00 | 0.00 | 0.243442E+11 | 0.243414E+11 | 107219.62 | 01-OCT-15:46 | 107219.62 | 0.08 |
November | 0.00 | 0.00 | 0.558754E+09 | 0.558754E+09 | 26225.60 | 09-NOV-14:00 | 26225.60 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.365586E+12 | 0.362842E+12 | 0.14 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.817150E+11 | 0.805558E+11 | 142034.72 | 107219.62 | 0.55 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.396513E+12 | 0.347135E+12 | 152567.68 | 03-JAN-22:03 | 133432.65 | 0.00 |
February | 0.00 | 0.00 | 0.611935E+12 | 0.536610E+12 | 258044.48 | 24-FEB-22:03 | 225379.60 | 0.00 |
March | 0.00 | 0.00 | 0.958077E+12 | 0.844419E+12 | 461653.66 | 31-MAR-24:00 | 405287.80 | 0.00 |
April | 0.00 | 0.00 | 0.119135E+13 | 0.105084E+13 | 478905.48 | 29-APR-02:50 | 412510.27 | 0.00 |
May | 0.00 | 0.00 | 0.399365E+12 | 0.356302E+12 | 246534.28 | 31-MAY-24:00 | 220754.29 | 0.00 |
June | 0.00 | 0.00 | 0.638768E+12 | 0.585530E+12 | 341132.21 | 30-JUN-24:00 | 312747.48 | 0.00 |
July | 0.00 | 0.00 | 0.912781E+12 | 0.852379E+12 | 439158.72 | 31-JUL-24:00 | 397251.44 | 0.00 |
August | 0.00 | 0.00 | 0.120900E+13 | 0.107855E+13 | 477553.37 | 25-AUG-21:00 | 404392.79 | 0.00 |
September | 0.00 | 0.00 | 0.390063E+12 | 0.349510E+12 | 248686.15 | 30-SEP-24:00 | 221152.25 | 0.00 |
October | 0.00 | 0.00 | 0.680556E+12 | 0.603569E+12 | 358028.69 | 31-OCT-24:00 | 314469.71 | 0.00 |
November | 0.00 | 0.00 | 0.935728E+12 | 0.820010E+12 | 365483.22 | 20-NOV-22:03 | 319387.79 | 0.00 |
December | 0.00 | 0.00 | 0.125086E+13 | 0.108869E+13 | 473654.45 | 24-DEC-16:47 | 408735.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.957500E+13 | 0.851354E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.390063E+12 | 0.347135E+12 | 152567.68 | 133432.65 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125086E+13 | 0.108869E+13 | 478905.48 | 412510.27 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.472837E+10 | 0.472783E+10 | 2888.42 | 26-JAN-17:00 | 2888.42 | 0.00 |
February | 0.00 | 0.00 | 0.927689E+10 | 0.927401E+10 | 5046.25 | 15-FEB-17:00 | 5046.25 | 0.00 |
March | 0.00 | 0.00 | 0.158670E+11 | 0.158630E+11 | 7796.15 | 31-MAR-24:00 | 7796.15 | 0.00 |
April | 0.00 | 0.00 | 0.207493E+11 | 0.207491E+11 | 8958.26 | 15-APR-17:55 | 8958.26 | 0.00 |
May | 0.00 | 0.00 | 0.626172E+10 | 0.622596E+10 | 4199.52 | 31-MAY-24:00 | 4199.52 | 0.00 |
June | 0.00 | 0.00 | 0.112999E+11 | 0.112233E+11 | 6034.41 | 30-JUN-23:40 | 6029.50 | 0.00 |
July | 0.00 | 0.00 | 0.168882E+11 | 0.166927E+11 | 7935.56 | 31-JUL-23:57 | 7935.56 | 0.00 |
August | 0.00 | 0.00 | 0.223138E+11 | 0.221015E+11 | 8985.53 | 23-AUG-16:00 | 8590.63 | 0.00 |
September | 0.00 | 0.00 | 0.636990E+10 | 0.623621E+10 | 4190.54 | 30-SEP-24:00 | 4190.54 | 0.00 |
October | 0.00 | 0.00 | 0.111858E+11 | 0.111380E+11 | 5987.88 | 31-OCT-24:00 | 5987.88 | 0.00 |
November | 0.00 | 0.00 | 0.152633E+11 | 0.152535E+11 | 6866.99 | 02-NOV-16:30 | 6791.32 | 0.00 |
December | 0.00 | 0.00 | 0.205757E+11 | 0.205757E+11 | 8718.64 | 31-DEC-16:30 | 8718.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160780E+12 | 0.160061E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.472837E+10 | 0.472783E+10 | 2888.42 | 2888.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.223138E+11 | 0.221015E+11 | 8985.53 | 8958.26 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.293595E+11 | 0.293537E+11 | 26349.74 | 26-JAN-17:00 | 26349.74 | 0.00 |
February | 0.00 | 0.00 | 0.758155E+11 | 0.757864E+11 | 47260.79 | 15-FEB-17:00 | 47260.79 | 0.00 |
March | 0.00 | 0.00 | 0.141324E+12 | 0.141282E+12 | 71825.67 | 31-MAR-24:00 | 71825.67 | 0.00 |
April | 0.00 | 0.00 | 0.191932E+12 | 0.191929E+12 | 84370.30 | 16-APR-18:22 | 84370.30 | 0.00 |
May | 0.00 | 0.00 | 0.557337E+11 | 0.553804E+11 | 39782.22 | 31-MAY-24:00 | 39782.22 | 0.00 |
June | 0.00 | 0.00 | 0.106354E+12 | 0.105591E+12 | 58426.37 | 30-JUN-23:53 | 58310.98 | 0.00 |
July | 0.00 | 0.00 | 0.161010E+12 | 0.159056E+12 | 76435.02 | 31-JUL-23:57 | 76435.02 | 0.00 |
August | 0.00 | 0.00 | 0.208533E+12 | 0.206405E+12 | 83825.31 | 23-AUG-16:00 | 79908.49 | 0.00 |
September | 0.00 | 0.00 | 0.573966E+11 | 0.560768E+11 | 39597.45 | 30-SEP-24:00 | 39597.45 | 0.00 |
October | 0.00 | 0.00 | 0.994975E+11 | 0.990218E+11 | 54703.44 | 31-OCT-24:00 | 54703.44 | 0.00 |
November | 0.00 | 0.00 | 0.132993E+12 | 0.132895E+12 | 64477.42 | 02-NOV-16:40 | 63827.10 | 0.00 |
December | 0.00 | 0.00 | 0.177579E+12 | 0.177578E+12 | 79283.98 | 29-DEC-16:40 | 79283.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143753E+13 | 0.143036E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.293595E+11 | 0.293537E+11 | 26349.74 | 26349.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208533E+12 | 0.206405E+12 | 84370.30 | 84370.30 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.141617E+10 | 0.141567E+10 | 2563.21 | 26-JAN-17:00 | 2563.21 | 0.00 |
February | 0.00 | 0.00 | 0.622344E+10 | 0.622063E+10 | 4755.08 | 15-FEB-17:00 | 4755.08 | 0.00 |
March | 0.00 | 0.00 | 0.131758E+11 | 0.131717E+11 | 6823.26 | 31-MAR-23:20 | 6823.26 | 0.00 |
April | 0.00 | 0.00 | 0.187795E+11 | 0.187793E+11 | 8560.28 | 16-APR-17:51 | 8560.28 | 0.00 |
May | 0.00 | 0.00 | 0.538992E+10 | 0.535481E+10 | 3938.39 | 31-MAY-24:00 | 3938.39 | 0.00 |
June | 0.00 | 0.00 | 0.106726E+11 | 0.105964E+11 | 5857.71 | 30-JUN-23:53 | 5846.05 | 0.00 |
July | 0.00 | 0.00 | 0.162443E+11 | 0.160491E+11 | 7640.41 | 31-JUL-23:57 | 7640.41 | 0.00 |
August | 0.00 | 0.00 | 0.209570E+11 | 0.207443E+11 | 8485.45 | 11-AUG-18:20 | 8327.90 | 0.00 |
September | 0.00 | 0.00 | 0.567190E+10 | 0.554010E+10 | 3955.12 | 30-SEP-24:00 | 3955.12 | 0.00 |
October | 0.00 | 0.00 | 0.933602E+10 | 0.928862E+10 | 5253.21 | 31-OCT-24:00 | 5253.21 | 0.00 |
November | 0.00 | 0.00 | 0.119608E+11 | 0.119511E+11 | 6444.17 | 02-NOV-16:40 | 6378.81 | 0.00 |
December | 0.00 | 0.00 | 0.158970E+11 | 0.158969E+11 | 7854.47 | 29-DEC-16:50 | 7854.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135724E+12 | 0.135009E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.141617E+10 | 0.141567E+10 | 2563.21 | 2563.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.209570E+11 | 0.207443E+11 | 8560.28 | 8560.28 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 61433.41 | 1176253.26 | 18-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 38030.58 | 1164202.40 | 01-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 9658.09 | 1216420.68 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1142.31 | 454321.44 | 08-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 182.40 | 93873.82 | 05-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.15 | 10275.60 | 09-JUN-05:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 1.22 | 1025.61 | 09-SEP-05:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 4615.73 | 1116459.14 | 26-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15217.88 | 1156276.82 | 28-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57013.89 | 1246055.06 | 04-DEC-05:01 |
Annual Sum or Average | 0.00 | 15550.80 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 61433.41 | 1246055.06 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 11738.06 | 566178.93 | 05-JAN-14:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 30136.34 | 1173803.66 | 13-FEB-15:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 77698.74 | 1210507.24 | 07-MAR-15:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 236548.82 | 1305838.47 | 13-APR-13:40 | 18.88 | 55000.23 | 13-APR-22:42 |
May | 378742.86 | 1425573.62 | 19-MAY-15:20 | 391.41 | 467185.65 | 14-MAY-06:22 |
June | 643297.89 | 1730095.34 | 28-JUN-14:50 | 128.58 | 176039.72 | 04-JUN-17:52 |
July | 748457.10 | 1762257.84 | 31-JUL-15:00 | 13.34 | 108290.64 | 15-JUL-17:52 |
August | 727778.65 | 1737423.11 | 23-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 515329.83 | 1937955.59 | 05-SEP-13:10 | 79.56 | 299142.97 | 17-SEP-07:22 |
October | 257137.97 | 1491009.69 | 02-OCT-11:20 | 160.97 | 439571.89 | 01-OCT-06:52 |
November | 22726.35 | 868279.78 | 02-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 3670.25 | 41681.97 | 24-DEC-14:12 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 306144.76 | 66.71 | ||||
Minimum of Months | 3670.25 | 41681.97 | 0.00 | 0.00 | ||
Maximum of Months | 748457.10 | 1937955.59 | 391.41 | 467185.65 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6404.37 | 414036.35 | 05-JAN-14:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 21102.80 | 1095339.08 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 51291.85 | 1074833.14 | 08-MAR-14:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 175972.44 | 1351981.40 | 13-APR-13:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 293085.01 | 1980992.14 | 22-MAY-03:01 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 549102.99 | 2080799.19 | 29-JUN-03:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 643997.31 | 2578702.50 | 17-JUL-03:02 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 637748.83 | 2616482.24 | 14-AUG-03:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 437284.05 | 2414811.15 | 05-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 209373.34 | 1647658.08 | 02-OCT-10:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 14020.10 | 689267.51 | 02-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1.73 | 35048.35 | 24-DEC-14:12 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 254743.13 | 0.00 | ||||
Minimum of Months | 1.73 | 35048.35 | 0.00 | 0.00 | ||
Maximum of Months | 643997.31 | 2616482.24 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 206759.80 | 240366.72 | 05-JAN-16:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 376594.68 | 845239.53 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 584305.58 | 1134828.58 | 08-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 935915.07 | 1587957.76 | 13-APR-17:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 420851.57 | 1047338.33 | 19-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 914739.66 | 1854227.04 | 28-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1309235.52 | 2073052.69 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1485919.26 | 2142054.76 | 20-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 509443.39 | 1186138.84 | 03-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 521982.83 | 1233350.52 | 01-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 543696.97 | 928369.89 | 09-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 681828.67 | 815693.15 | 24-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 710125.71 | 0.00 | ||||
Minimum of Months | 206759.80 | 240366.72 | 0.00 | 0.00 | ||
Maximum of Months | 1485919.26 | 2142054.76 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15592.55 | 52458.79 | 31-JAN-12:35 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 15790.54 | 52479.83 | 09-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16305.53 | 51962.65 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14628.02 | 49723.45 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14121.19 | 46845.19 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13495.08 | 43470.87 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 11970.99 | 40727.77 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 12845.68 | 40007.34 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 12505.88 | 41932.82 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13235.52 | 45180.15 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14336.08 | 48453.22 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14698.32 | 51018.43 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 14117.67 | ||||
Minimum of Months | 0.00 | 0.00 | 11970.99 | 40007.34 | ||
Maximum of Months | 0.00 | 0.00 | 16305.53 | 52479.83 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4661.35 | 350773.67 | 05-JAN-14:40 | 2495.80 | 142390.71 | 10-JAN-12:10 |
February | 16943.98 | 955889.25 | 14-FEB-16:00 | 3399.94 | 137593.21 | 03-FEB-15:20 |
March | 47492.56 | 955203.33 | 08-MAR-14:10 | 1976.91 | 121935.31 | 03-MAR-15:30 |
April | 188385.90 | 2181905.86 | 13-APR-15:20 | 2270.52 | 122678.47 | 15-APR-13:40 |
May | 331149.19 | 2374893.85 | 19-MAY-15:10 | 633.67 | 121274.37 | 05-MAY-07:50 |
June | 681221.62 | 2383021.90 | 12-JUN-15:00 | 630.27 | 76500.71 | 10-JUN-06:30 |
July | 809667.30 | 3221770.01 | 31-JUL-15:00 | 94.26 | 37237.81 | 19-JUL-05:00 |
August | 782406.83 | 2829352.42 | 23-AUG-16:00 | 475.87 | 42693.14 | 25-AUG-05:50 |
September | 542139.45 | 3256007.10 | 05-SEP-13:10 | 285.53 | 53962.92 | 09-SEP-07:40 |
October | 237348.98 | 2299366.87 | 04-OCT-14:20 | 1647.53 | 136000.84 | 25-OCT-13:40 |
November | 10820.04 | 516653.97 | 02-NOV-15:10 | 2225.77 | 124141.66 | 16-NOV-09:20 |
December | 208.81 | 26686.15 | 20-DEC-16:30 | 4107.85 | 143474.88 | 14-DEC-12:20 |
Annual Sum or Average | 306171.04 | 1676.57 | ||||
Minimum of Months | 208.81 | 26686.15 | 94.26 | 37237.81 | ||
Maximum of Months | 809667.30 | 3256007.10 | 4107.85 | 143474.88 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183071E+11 | 0.98 | 11780.72 | 01-JAN-00:20 | 1.68 |
February | 0.164023E+11 | 0.97 | 11780.72 | 01-FEB-05:01 | 1.69 |
March | 0.192356E+11 | 1.03 | 11780.72 | 01-MAR-04:10 | 1.68 |
April | 0.178411E+11 | 0.98 | 11780.72 | 01-APR-03:02 | 1.69 |
May | 0.192395E+11 | 1.02 | 11780.72 | 01-MAY-00:33 | 1.68 |
June | 0.189785E+11 | 1.04 | 11780.72 | 01-JUN-03:02 | 1.67 |
July | 0.192527E+11 | 1.01 | 11780.72 | 01-JUL-03:02 | 1.66 |
August | 0.210397E+11 | 1.11 | 11780.72 | 01-AUG-03:02 | 1.67 |
September | 0.195599E+11 | 1.07 | 11780.72 | 01-SEP-03:02 | 1.66 |
October | 0.200382E+11 | 1.06 | 11780.72 | 01-OCT-12:20 | 1.67 |
November | 0.184875E+11 | 1.02 | 11780.72 | 01-NOV-03:02 | 1.67 |
December | 0.184086E+11 | 0.98 | 11780.72 | 01-DEC-04:02 | 1.68 |
Annual Sum or Average | 0.226791E+12 | 1.02 | |||
Minimum of Months | 0.164023E+11 | 0.97 | 11780.72 | 1.66 | |
Maximum of Months | 0.210397E+11 | 1.11 | 11780.72 | 1.69 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.629459E+10 | 0.42 | 14476.80 | 17-JAN-06:01 | 1.50 |
February | 0.664617E+10 | 0.46 | 13790.76 | 15-FEB-16:40 | 1.46 |
March | 0.980842E+10 | 0.56 | 14874.61 | 13-MAR-15:10 | 1.53 |
April | 0.134656E+11 | 0.71 | 20242.58 | 28-APR-14:50 | 1.85 |
May | 0.114938E+11 | 0.61 | 23177.57 | 22-MAY-05:03 | 2.00 |
June | 0.147791E+11 | 0.75 | 25501.75 | 14-JUN-05:02 | 2.14 |
July | 0.167111E+11 | 0.80 | 25501.75 | 22-JUL-05:02 | 2.13 |
August | 0.202444E+11 | 0.93 | 25501.75 | 07-AUG-05:02 | 2.12 |
September | 0.112601E+11 | 0.61 | 18716.82 | 18-SEP-15:40 | 1.74 |
October | 0.993933E+10 | 0.55 | 25365.75 | 02-OCT-05:03 | 2.12 |
November | 0.858782E+10 | 0.52 | 14180.02 | 20-NOV-16:10 | 1.49 |
December | 0.808688E+10 | 0.48 | 14476.80 | 22-DEC-06:01 | 1.50 |
Annual Sum or Average | 0.137317E+12 | 0.62 | |||
Minimum of Months | 0.629459E+10 | 0.42 | 13790.76 | 1.46 | |
Maximum of Months | 0.202444E+11 | 0.93 | 25501.75 | 2.14 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.453868E+11 | 0.39 | 157974.39 | 12-JAN-06:02 | 1.66 |
February | 0.445556E+11 | 0.39 | 139077.84 | 18-FEB-06:02 | 1.53 |
March | 0.611126E+11 | 0.44 | 127506.19 | 11-MAR-06:02 | 1.45 |
April | 0.783416E+11 | 0.50 | 151435.93 | 13-APR-15:20 | 1.61 |
May | 0.927030E+11 | 0.55 | 156566.74 | 19-MAY-15:20 | 1.64 |
June | 0.119193E+12 | 0.66 | 230706.44 | 29-JUN-03:02 | 2.08 |
July | 0.128466E+12 | 0.66 | 237568.49 | 05-JUL-05:02 | 2.13 |
August | 0.130103E+12 | 0.67 | 231873.71 | 07-AUG-03:02 | 2.09 |
September | 0.896763E+11 | 0.55 | 188874.17 | 05-SEP-05:03 | 1.83 |
October | 0.702826E+11 | 0.47 | 152753.89 | 26-OCT-05:02 | 1.62 |
November | 0.524364E+11 | 0.41 | 127506.19 | 13-NOV-06:01 | 1.45 |
December | 0.458632E+11 | 0.38 | 127506.19 | 30-DEC-06:03 | 1.45 |
Annual Sum or Average | 0.958120E+12 | 0.51 | |||
Minimum of Months | 0.445556E+11 | 0.38 | 127506.19 | 1.45 | |
Maximum of Months | 0.130103E+12 | 0.67 | 237568.49 | 2.13 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.442705E+10 | 0.40 | 5442.90 | 09-JAN-05:01 | 0.84 |
February | 0.401515E+10 | 0.38 | 9261.95 | 15-FEB-16:40 | 1.13 |
March | 0.511469E+10 | 0.40 | 9659.86 | 24-MAR-15:50 | 1.16 |
April | 0.702516E+10 | 0.45 | 17019.29 | 13-APR-15:20 | 1.64 |
May | 0.892663E+10 | 0.51 | 18731.77 | 19-MAY-15:20 | 1.73 |
June | 0.127942E+11 | 0.64 | 26048.24 | 27-JUN-15:50 | 2.13 |
July | 0.142315E+11 | 0.67 | 26048.24 | 24-JUL-03:01 | 2.12 |
August | 0.140829E+11 | 0.67 | 26048.24 | 07-AUG-05:02 | 2.12 |
September | 0.897807E+10 | 0.52 | 18300.56 | 11-SEP-16:00 | 1.70 |
October | 0.611754E+10 | 0.42 | 14485.94 | 02-OCT-16:00 | 1.47 |
November | 0.439902E+10 | 0.38 | 9570.49 | 01-NOV-05:03 | 1.15 |
December | 0.435801E+10 | 0.39 | 5442.90 | 04-DEC-05:01 | 0.84 |
Annual Sum or Average | 0.944699E+11 | 0.49 | |||
Minimum of Months | 0.401515E+10 | 0.38 | 5442.90 | 0.84 | |
Maximum of Months | 0.142315E+11 | 0.67 | 26048.24 | 2.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114606E+12 | 1.63 | 42789.15 | 01-JAN-00:05 | 1.63 |
February | 0.103516E+12 | 1.63 | 42789.15 | 01-FEB-00:10 | 1.63 |
March | 0.114606E+12 | 1.63 | 42789.15 | 01-MAR-00:10 | 1.63 |
April | 0.110909E+12 | 1.62 | 42789.15 | 01-APR-00:10 | 1.63 |
May | 0.114606E+12 | 1.63 | 42789.15 | 01-MAY-00:03 | 1.63 |
June | 0.110909E+12 | 1.63 | 42789.15 | 01-JUN-00:10 | 1.63 |
July | 0.114606E+12 | 1.63 | 42789.15 | 01-JUL-00:05 | 1.63 |
August | 0.114606E+12 | 1.62 | 42789.15 | 01-AUG-00:03 | 1.62 |
September | 0.110909E+12 | 1.63 | 42789.15 | 01-SEP-00:07 | 1.63 |
October | 0.114606E+12 | 1.63 | 42789.15 | 01-OCT-00:10 | 1.63 |
November | 0.110909E+12 | 1.63 | 42789.15 | 01-NOV-00:20 | 1.63 |
December | 0.114606E+12 | 1.63 | 42789.15 | 01-DEC-00:10 | 1.63 |
Annual Sum or Average | 0.134940E+13 | 1.63 | |||
Minimum of Months | 0.103516E+12 | 1.62 | 42789.15 | 1.62 | |
Maximum of Months | 0.114606E+12 | 1.63 | 42789.15 | 1.63 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.178356E+10 | 1.12 | 665.90 | 01-JAN-00:05 | 1.11 |
February | 0.161095E+10 | 1.12 | 665.90 | 01-FEB-00:10 | 1.12 |
March | 0.178356E+10 | 1.12 | 665.90 | 01-MAR-00:10 | 1.12 |
April | 0.172602E+10 | 1.12 | 665.90 | 01-APR-00:10 | 1.12 |
May | 0.178356E+10 | 1.11 | 665.90 | 01-MAY-00:03 | 1.12 |
June | 0.172602E+10 | 1.11 | 665.90 | 01-JUN-00:10 | 1.12 |
July | 0.178356E+10 | 1.11 | 665.90 | 01-JUL-00:05 | 1.11 |
August | 0.178356E+10 | 1.11 | 665.90 | 01-AUG-00:03 | 1.11 |
September | 0.172602E+10 | 1.11 | 665.90 | 01-SEP-00:03 | 1.11 |
October | 0.178356E+10 | 1.11 | 665.90 | 01-OCT-00:10 | 1.11 |
November | 0.172602E+10 | 1.12 | 665.90 | 01-NOV-00:10 | 1.12 |
December | 0.178356E+10 | 1.12 | 665.90 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.209999E+11 | 1.11 | |||
Minimum of Months | 0.161095E+10 | 1.11 | 665.90 | 1.11 | |
Maximum of Months | 0.178356E+10 | 1.12 | 665.90 | 1.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170425E+11 | 1.12 | 6362.93 | 01-JAN-00:05 | 1.11 |
February | 0.153932E+11 | 1.12 | 6362.93 | 01-FEB-00:10 | 1.12 |
March | 0.170425E+11 | 1.12 | 6362.93 | 01-MAR-00:10 | 1.12 |
April | 0.164927E+11 | 1.12 | 6362.93 | 01-APR-00:10 | 1.12 |
May | 0.170425E+11 | 1.11 | 6362.93 | 01-MAY-00:03 | 1.12 |
June | 0.164927E+11 | 1.11 | 6362.93 | 01-JUN-00:20 | 1.12 |
July | 0.170425E+11 | 1.11 | 6362.93 | 01-JUL-00:05 | 1.11 |
August | 0.170425E+11 | 1.11 | 6362.93 | 01-AUG-00:03 | 1.11 |
September | 0.164927E+11 | 1.11 | 6362.93 | 01-SEP-00:03 | 1.11 |
October | 0.170425E+11 | 1.11 | 6362.93 | 01-OCT-00:10 | 1.11 |
November | 0.164927E+11 | 1.12 | 6362.93 | 01-NOV-00:10 | 1.12 |
December | 0.170425E+11 | 1.12 | 6362.93 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.200661E+12 | 1.11 | |||
Minimum of Months | 0.153932E+11 | 1.11 | 6362.93 | 1.11 | |
Maximum of Months | 0.170425E+11 | 1.12 | 6362.93 | 1.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.174085E+10 | 1.12 | 649.96 | 01-JAN-00:05 | 1.11 |
February | 0.157238E+10 | 1.12 | 649.96 | 01-FEB-00:10 | 1.12 |
March | 0.174085E+10 | 1.12 | 649.96 | 01-MAR-00:10 | 1.12 |
April | 0.168470E+10 | 1.12 | 649.96 | 01-APR-00:10 | 1.12 |
May | 0.174085E+10 | 1.11 | 649.96 | 01-MAY-00:03 | 1.12 |
June | 0.168470E+10 | 1.11 | 649.96 | 01-JUN-00:10 | 1.12 |
July | 0.174085E+10 | 1.11 | 649.96 | 01-JUL-00:05 | 1.11 |
August | 0.174085E+10 | 1.11 | 649.96 | 01-AUG-00:03 | 1.11 |
September | 0.168470E+10 | 1.11 | 649.96 | 01-SEP-00:03 | 1.11 |
October | 0.174085E+10 | 1.11 | 649.96 | 01-OCT-00:10 | 1.11 |
November | 0.168470E+10 | 1.12 | 649.96 | 01-NOV-00:10 | 1.12 |
December | 0.174085E+10 | 1.12 | 649.96 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.204971E+11 | 1.11 | |||
Minimum of Months | 0.157238E+10 | 1.11 | 649.96 | 1.11 | |
Maximum of Months | 0.174085E+10 | 1.12 | 649.96 | 1.12 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.689827E+09 | 0.620844E+09 | 3702.85 | 17-JAN-06:01 | 3332.56 | 3332.56 | 44.52 | 6.30 |
February | 0.385709E+09 | 0.347138E+09 | 3687.03 | 06-FEB-06:01 | 3318.32 | 3318.32 | 44.90 | 6.24 |
March | 0.105560E+09 | 95004387.42 | 3638.13 | 06-MAR-06:01 | 3274.32 | 3274.32 | 33.79 | 6.09 |
April | 12010057.95 | 10809052.16 | 1704.61 | 08-APR-05:03 | 1534.15 | 1534.15 | 27.41 | 2.04 |
May | 1962515.25 | 1766263.72 | 366.71 | 05-MAY-05:03 | 330.03 | 330.03 | 21.86 | 0.39 |
June | 116622.06 | 104959.85 | 41.34 | 09-JUN-05:10 | 37.21 | 37.21 | 21.64 | 0.04 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 21.40 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 21.40 | 0.00 |
September | 12809.94 | 11528.95 | 4.15 | 09-SEP-05:10 | 3.73 | 3.73 | 21.40 | 0.00 |
October | 50166332.83 | 45149699.55 | 3524.78 | 26-OCT-05:02 | 3172.30 | 3172.30 | 34.81 | 5.72 |
November | 0.163348E+09 | 0.147013E+09 | 3640.17 | 28-NOV-06:01 | 3276.16 | 3276.16 | 36.05 | 6.09 |
December | 0.638860E+09 | 0.574974E+09 | 3676.83 | 04-DEC-06:01 | 3309.14 | 3309.14 | 38.73 | 6.22 |
Annual Sum or Average | 0.204757E+10 | 0.184281E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.40 | 0.00 | |
Maximum of Months | 0.689827E+09 | 0.620844E+09 | 3702.85 | 3332.56 | 3332.56 | 44.90 | 6.30 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 7583682.41 | 6825314.17 | 288.33 | 05-JAN-14:30 | 259.50 | 259.50 | 9.00 | 14.60 |
February | 48801495.53 | 43921345.98 | 1765.95 | 14-FEB-16:00 | 1589.35 | 1589.35 | 7.79 | 34.97 |
March | 76390315.29 | 68751283.76 | 1568.79 | 08-MAR-14:00 | 1411.91 | 1411.91 | 7.72 | 33.15 |
April | 0.285410E+09 | 0.256869E+09 | 1934.51 | 27-APR-13:30 | 1741.06 | 1741.06 | 7.50 | 36.43 |
May | 0.600291E+09 | 0.540262E+09 | 8848.75 | 23-MAY-10:30 | 7963.87 | 7963.87 | 6.91 | 69.61 |
June | 0.255198E+10 | 0.229678E+10 | 18481.75 | 27-JUN-15:50 | 16633.58 | 16633.58 | 6.74 | 93.48 |
July | 0.275794E+10 | 0.248214E+10 | 19983.23 | 05-JUL-05:02 | 17984.91 | 17984.91 | 8.21 | 96.40 |
August | 0.315545E+10 | 0.283990E+10 | 19557.08 | 16-AUG-05:02 | 17601.37 | 17601.37 | 8.58 | 95.57 |
September | 0.264816E+10 | 0.238334E+10 | 18854.55 | 01-SEP-05:03 | 16969.09 | 16969.09 | 8.54 | 94.21 |
October | 0.992424E+09 | 0.893182E+09 | 14046.08 | 04-OCT-14:20 | 12641.47 | 12641.47 | 6.90 | 83.86 |
November | 17721527.76 | 15949374.99 | 839.88 | 02-NOV-15:00 | 755.89 | 755.89 | 9.20 | 24.81 |
December | 925.73 | 833.15 | 7.15 | 24-DEC-14:12 | 6.44 | 6.44 | 8.57 | 1.32 |
Annual Sum or Average | 0.131421E+11 | 0.118279E+11 | ||||||
Minimum of Months | 925.73 | 833.15 | 7.15 | 6.44 | 6.44 | 6.74 | 1.32 | |
Maximum of Months | 0.315545E+10 | 0.283990E+10 | 19983.23 | 17984.91 | 17984.91 | 9.20 | 96.40 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.440060E+10 | 0.396054E+10 | 13753.92 | 01-JAN-12:12 | 12378.53 | 12378.53 | 8.47 | 96.40 |
February | 0.563679E+10 | 0.507311E+10 | 13753.92 | 01-FEB-10:45 | 12378.53 | 12378.53 | 8.43 | 96.40 |
March | 0.774992E+10 | 0.697493E+10 | 13753.92 | 01-MAR-16:30 | 12378.53 | 12378.53 | 8.47 | 96.40 |
April | 0.146863E+11 | 0.132177E+11 | 13753.92 | 01-APR-05:03 | 12378.53 | 12378.53 | 8.43 | 96.40 |
May | 0.185676E+11 | 0.167108E+11 | 13753.92 | 01-MAY-03:02 | 12378.53 | 12378.53 | 8.67 | 96.40 |
June | 0.267376E+11 | 0.240639E+11 | 13753.92 | 01-JUN-03:02 | 12378.53 | 12378.53 | 9.62 | 96.40 |
July | 0.314199E+11 | 0.282779E+11 | 13753.92 | 01-JUL-00:42 | 12378.53 | 12378.53 | 7.58 | 96.40 |
August | 0.337827E+11 | 0.304044E+11 | 13753.92 | 01-AUG-00:18 | 12378.53 | 12378.53 | 7.77 | 96.40 |
September | 0.226089E+11 | 0.203480E+11 | 13753.92 | 01-SEP-00:03 | 12378.53 | 12378.53 | 7.62 | 96.40 |
October | 0.153458E+11 | 0.138112E+11 | 13753.92 | 01-OCT-06:52 | 12378.53 | 12378.53 | 7.28 | 96.40 |
November | 0.460149E+10 | 0.414134E+10 | 13753.92 | 01-NOV-03:02 | 12378.53 | 12378.53 | 8.76 | 96.40 |
December | 0.553971E+10 | 0.498574E+10 | 13753.92 | 01-DEC-06:05 | 12378.53 | 12378.53 | 8.45 | 96.40 |
Annual Sum or Average | 0.191077E+12 | 0.171970E+12 | ||||||
Minimum of Months | 0.440060E+10 | 0.396054E+10 | 13753.92 | 12378.53 | 12378.53 | 7.28 | 96.40 | |
Maximum of Months | 0.337827E+11 | 0.304044E+11 | 13753.92 | 12378.53 | 12378.53 | 9.62 | 96.40 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.100246E+11 | 0.902210E+10 | 3742.74 | 01-JAN-00:05 | 3368.47 | 3368.47 | 22.16 | 15.63 |
February | 0.905443E+10 | 0.814899E+10 | 3742.74 | 01-FEB-00:10 | 3368.47 | 3368.47 | 24.65 | 15.63 |
March | 0.100246E+11 | 0.902210E+10 | 3742.74 | 01-MAR-00:10 | 3368.47 | 3368.47 | 27.59 | 15.63 |
April | 0.970118E+10 | 0.873106E+10 | 3742.74 | 01-APR-00:10 | 3368.47 | 3368.47 | 30.80 | 15.63 |
May | 0.100246E+11 | 0.902210E+10 | 3742.74 | 01-MAY-00:03 | 3368.47 | 3368.47 | 23.03 | 15.63 |
June | 0.970118E+10 | 0.873106E+10 | 3742.74 | 01-JUN-00:10 | 3368.47 | 3368.47 | 29.64 | 15.63 |
July | 0.100246E+11 | 0.902210E+10 | 3742.74 | 01-JUL-00:05 | 3368.47 | 3368.47 | 37.86 | 15.63 |
August | 0.100246E+11 | 0.902210E+10 | 3742.74 | 01-AUG-00:03 | 3368.47 | 3368.47 | 41.19 | 15.63 |
September | 0.970118E+10 | 0.873106E+10 | 3742.74 | 01-SEP-00:03 | 3368.47 | 3368.47 | 29.84 | 15.63 |
October | 0.100246E+11 | 0.902210E+10 | 3742.74 | 01-OCT-00:10 | 3368.47 | 3368.47 | 28.49 | 15.63 |
November | 0.970118E+10 | 0.873106E+10 | 3742.74 | 01-NOV-00:10 | 3368.47 | 3368.47 | 28.34 | 15.63 |
December | 0.100246E+11 | 0.902210E+10 | 3742.74 | 01-DEC-00:10 | 3368.47 | 3368.47 | 30.44 | 15.63 |
Annual Sum or Average | 0.118031E+12 | 0.106228E+12 | ||||||
Minimum of Months | 0.905443E+10 | 0.814899E+10 | 3742.74 | 3368.47 | 3368.47 | 22.16 | 15.63 | |
Maximum of Months | 0.100246E+11 | 0.902210E+10 | 3742.74 | 3368.47 | 3368.47 | 41.19 | 15.63 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 55.69 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:01 | 1.79 | 1.79 | 56.39 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 56.53 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 56.47 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 56.33 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 56.97 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 56.31 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 57.08 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.17 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.12 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 56.60 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:03 | 1.79 | 1.79 | 56.54 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.69 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 57.08 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.548462E+10 | 0.493616E+10 | 17159.18 | 05-JAN-14:40 | 15443.26 | 15443.26 | 22.57 | 57.10 |
February | 0.705749E+10 | 0.635174E+10 | 34322.87 | 13-FEB-15:10 | 30890.59 | 30890.59 | 22.74 | 114.21 |
March | 0.970591E+10 | 0.873532E+10 | 34322.06 | 07-MAR-15:40 | 30889.86 | 30889.86 | 22.71 | 114.21 |
April | 0.203167E+11 | 0.182850E+11 | 34397.88 | 13-APR-15:20 | 30958.09 | 30958.09 | 25.67 | 114.21 |
May | 0.272296E+11 | 0.245066E+11 | 34409.54 | 19-MAY-15:10 | 30968.59 | 30968.59 | 26.08 | 114.21 |
June | 0.440072E+11 | 0.396064E+11 | 34410.03 | 12-JUN-15:00 | 30969.03 | 30969.03 | 26.09 | 114.21 |
July | 0.527945E+11 | 0.475150E+11 | 34460.79 | 31-JUL-15:00 | 31014.71 | 31014.71 | 27.85 | 114.21 |
August | 0.555474E+11 | 0.499927E+11 | 34437.03 | 23-AUG-16:00 | 30993.32 | 30993.32 | 27.03 | 114.21 |
September | 0.361664E+11 | 0.325498E+11 | 34462.87 | 05-SEP-13:10 | 31016.58 | 31016.58 | 27.92 | 114.21 |
October | 0.219335E+11 | 0.197402E+11 | 34404.98 | 04-OCT-14:20 | 30964.48 | 30964.48 | 25.92 | 114.21 |
November | 0.573584E+10 | 0.516226E+10 | 17167.76 | 02-NOV-15:10 | 15450.99 | 15450.99 | 23.26 | 57.10 |
December | 0.690342E+10 | 0.621308E+10 | 17142.44 | 20-DEC-16:30 | 15428.19 | 15428.19 | 21.21 | 57.10 |
Annual Sum or Average | 0.292883E+12 | 0.263594E+12 | ||||||
Minimum of Months | 0.548462E+10 | 0.493616E+10 | 17142.44 | 15428.19 | 15428.19 | 21.21 | 57.10 | |
Maximum of Months | 0.555474E+11 | 0.499927E+11 | 34462.87 | 31016.58 | 31016.58 | 27.92 | 114.21 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 30.59 | 30.59 | 61433.41 | 1176253.26 | 18-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 28.95 | 28.95 | 38030.58 | 1164202.40 | 01-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 21.75 | 21.75 | 9658.09 | 1216420.68 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.15 | 23.15 | 1142.31 | 454321.44 | 08-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.31 | 22.31 | 182.40 | 93873.82 | 05-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 21.69 | 21.69 | 11.15 | 10275.60 | 09-JUN-05:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 21.40 | 21.40 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 21.40 | 21.40 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.40 | 21.40 | 1.22 | 1025.61 | 09-SEP-05:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21.36 | 21.36 | 4615.73 | 1116459.14 | 26-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.53 | 21.53 | 15217.88 | 1156276.82 | 28-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.74 | 21.74 | 57013.89 | 1246055.06 | 04-DEC-05:01 |
Annual Sum or Average | 0.00 | 15550.80 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.36 | 21.36 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 30.59 | 30.59 | 61433.41 | 1246055.06 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 11738.06 | 566178.93 | 05-JAN-14:30 | 9.70 | 8.98 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 30136.34 | 1173803.66 | 13-FEB-15:10 | 10.43 | 8.96 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 77698.74 | 1210507.24 | 07-MAR-15:40 | 10.50 | 8.89 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 236548.82 | 1305838.47 | 13-APR-13:40 | 10.30 | 7.07 | 18.88 | 55000.23 | 13-APR-22:42 |
May | 378742.86 | 1425573.62 | 19-MAY-15:20 | 10.23 | 6.70 | 391.41 | 467185.65 | 14-MAY-06:22 |
June | 643297.89 | 1730095.34 | 28-JUN-14:50 | 10.98 | 6.70 | 128.58 | 176039.72 | 04-JUN-17:52 |
July | 748457.10 | 1762257.84 | 31-JUL-15:00 | 11.06 | 6.70 | 13.34 | 108290.64 | 15-JUL-17:52 |
August | 727778.65 | 1737423.11 | 23-AUG-16:00 | 11.51 | 7.21 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 515329.83 | 1937955.59 | 05-SEP-13:10 | 11.91 | 7.11 | 79.56 | 299142.97 | 17-SEP-07:22 |
October | 257137.97 | 1491009.69 | 02-OCT-11:20 | 10.76 | 7.07 | 160.97 | 439571.89 | 01-OCT-06:52 |
November | 22726.35 | 868279.78 | 02-NOV-15:00 | 10.28 | 9.19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 3670.25 | 41681.97 | 24-DEC-14:12 | 8.47 | 8.42 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 306144.76 | 66.71 | ||||||
Minimum of Months | 3670.25 | 41681.97 | 8.47 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 748457.10 | 1937955.59 | 11.91 | 9.19 | 391.41 | 467185.65 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6404.37 | 414036.35 | 05-JAN-14:30 | 13.47 | 9.00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 21102.80 | 1095339.08 | 14-FEB-16:00 | 14.18 | 8.53 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 51291.85 | 1074833.14 | 08-MAR-14:20 | 14.46 | 8.47 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 175972.44 | 1351981.40 | 13-APR-13:40 | 15.70 | 7.07 | 0.00 | 0.00 | 01-APR-00:10 |
May | 293085.01 | 1980992.14 | 22-MAY-03:01 | 17.00 | 8.05 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 549102.99 | 2080799.19 | 29-JUN-03:02 | 13.28 | 7.97 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 643997.31 | 2578702.50 | 17-JUL-03:02 | 14.98 | 7.76 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 637748.83 | 2616482.24 | 14-AUG-03:02 | 14.76 | 7.85 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 437284.05 | 2414811.15 | 05-SEP-05:03 | 13.14 | 8.33 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 209373.34 | 1647658.08 | 02-OCT-10:30 | 11.65 | 8.50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 14020.10 | 689267.51 | 02-NOV-15:00 | 13.33 | 9.21 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1.73 | 35048.35 | 24-DEC-14:12 | 13.03 | 8.41 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 254743.13 | 0.00 | ||||||
Minimum of Months | 1.73 | 35048.35 | 11.65 | 7.07 | 0.00 | 0.00 | ||
Maximum of Months | 643997.31 | 2616482.24 | 17.00 | 9.21 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 206759.80 | 240366.72 | 05-JAN-16:00 | 22.75 | 18.53 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 376594.68 | 845239.53 | 14-FEB-16:00 | 33.72 | 26.45 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 584305.58 | 1134828.58 | 08-MAR-16:00 | 38.89 | 28.76 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 935915.07 | 1587957.76 | 13-APR-17:00 | 46.88 | 33.86 | 0.00 | 0.00 | 01-APR-00:10 |
May | 420851.57 | 1047338.33 | 19-MAY-16:00 | 37.33 | 32.71 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 914739.66 | 1854227.04 | 28-JUN-16:00 | 51.52 | 43.63 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1309235.52 | 2073052.69 | 22-JUL-15:00 | 55.31 | 44.70 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1485919.26 | 2142054.76 | 20-AUG-16:00 | 56.50 | 43.10 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 509443.39 | 1186138.84 | 03-SEP-14:00 | 39.80 | 35.40 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 521982.83 | 1233350.52 | 01-OCT-16:00 | 40.64 | 33.26 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 543696.97 | 928369.89 | 09-NOV-14:00 | 35.21 | 25.24 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 681828.67 | 815693.15 | 24-DEC-15:00 | 33.19 | 20.63 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 710125.71 | 0.00 | ||||||
Minimum of Months | 206759.80 | 240366.72 | 22.75 | 18.53 | 0.00 | 0.00 | ||
Maximum of Months | 1485919.26 | 2142054.76 | 56.50 | 44.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.69 | 57.69 | 15592.55 | 52458.79 | 31-JAN-12:35 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.85 | 56.85 | 15790.54 | 52479.83 | 09-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.11 | 57.11 | 16305.53 | 51962.65 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.05 | 57.05 | 14628.02 | 49723.45 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.10 | 57.10 | 14121.19 | 46845.19 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.26 | 57.26 | 13495.08 | 43470.87 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 56.87 | 56.87 | 11970.99 | 40727.77 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.17 | 57.17 | 12845.68 | 40007.34 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 56.64 | 56.64 | 12505.88 | 41932.82 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.03 | 57.03 | 13235.52 | 45180.15 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.17 | 57.17 | 14336.08 | 48453.22 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.11 | 57.11 | 14698.32 | 51018.43 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 14117.67 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.64 | 56.64 | 11970.99 | 40007.34 | ||
Maximum of Months | 0.00 | 0.00 | 57.69 | 57.69 | 16305.53 | 52479.83 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4661.35 | 350773.67 | 05-JAN-14:40 | 22.57 | 21.10 | 2495.80 | 142390.71 | 10-JAN-12:10 |
February | 16943.98 | 955889.25 | 14-FEB-16:00 | 25.11 | 21.10 | 3399.94 | 137593.21 | 03-FEB-15:20 |
March | 47492.56 | 955203.33 | 08-MAR-14:10 | 25.10 | 21.10 | 1976.91 | 121935.31 | 03-MAR-15:30 |
April | 188385.90 | 2181905.86 | 13-APR-15:20 | 25.67 | 21.10 | 2270.52 | 122678.47 | 15-APR-13:40 |
May | 331149.19 | 2374893.85 | 19-MAY-15:10 | 26.08 | 21.10 | 633.67 | 121274.37 | 05-MAY-07:50 |
June | 681221.62 | 2383021.90 | 12-JUN-15:00 | 26.09 | 21.10 | 630.27 | 76500.71 | 10-JUN-06:30 |
July | 809667.30 | 3221770.01 | 31-JUL-15:00 | 27.85 | 23.60 | 94.26 | 37237.81 | 19-JUL-05:00 |
August | 782406.83 | 2829352.42 | 23-AUG-16:00 | 27.03 | 22.84 | 475.87 | 42693.14 | 25-AUG-05:50 |
September | 542139.45 | 3256007.10 | 05-SEP-13:10 | 27.92 | 23.22 | 285.53 | 53962.92 | 09-SEP-07:40 |
October | 237348.98 | 2299366.87 | 04-OCT-14:20 | 25.92 | 21.10 | 1647.53 | 136000.84 | 25-OCT-13:40 |
November | 10820.04 | 516653.97 | 02-NOV-15:10 | 23.26 | 21.10 | 2225.77 | 124141.66 | 16-NOV-09:20 |
December | 208.81 | 26686.15 | 20-DEC-16:30 | 21.21 | 20.26 | 4107.85 | 143474.88 | 14-DEC-12:20 |
Annual Sum or Average | 306171.04 | 1676.57 | ||||||
Minimum of Months | 208.81 | 26686.15 | 21.21 | 20.26 | 94.26 | 37237.81 | ||
Maximum of Months | 809667.30 | 3256007.10 | 27.92 | 23.60 | 4107.85 | 143474.88 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.322764E+10 | 0.00 | 0.115025E+10 | 0.629459E+10 | 0.00 | 0.00 |
February | 0.127086E+10 | 0.00 | 0.349401E+10 | 0.664617E+10 | 0.00 | 0.00 |
March | 37300275.81 | 0.00 | 0.108938E+11 | 0.980842E+10 | 0.00 | 0.00 |
April | 240520.54 | 0.00 | 0.405220E+11 | 0.134656E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.604086E+11 | 0.114938E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.116807E+12 | 0.147791E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.149613E+12 | 0.167111E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.159466E+12 | 0.202444E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.864646E+11 | 0.112601E+11 | 0.00 | 0.00 |
October | 72261650.08 | 0.00 | 0.415551E+11 | 0.993933E+10 | 0.00 | 0.00 |
November | 46316627.88 | 0.00 | 0.271523E+10 | 0.858782E+10 | 0.00 | 0.00 |
December | 0.929052E+09 | 0.00 | 43718.29 | 0.808688E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.558367E+10 | 0.00 | 0.673089E+12 | 0.137317E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 43718.29 | 0.629459E+10 | 0.00 | 0.00 |
Maximum of Months | 0.322764E+10 | 0.00 | 0.159466E+12 | 0.202444E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.132931E+12 | 0.00 | 0.100859E+11 | 0.453868E+11 | 0.00 | 0.00 |
February | 0.730552E+11 | 0.00 | 0.293658E+11 | 0.445556E+11 | 0.00 | 0.00 |
March | 0.188781E+11 | 0.00 | 0.840737E+11 | 0.611126E+11 | 0.00 | 0.00 |
April | 0.170544E+10 | 0.00 | 0.293867E+12 | 0.783416E+11 | 0.00 | 0.00 |
May | 0.193769E+09 | 0.00 | 0.526489E+12 | 0.927030E+11 | 0.00 | 0.00 |
June | 7653852.17 | 0.00 | 0.100454E+13 | 0.119193E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.121524E+13 | 0.128466E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.115813E+13 | 0.130103E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.758173E+12 | 0.896763E+11 | 0.00 | 0.00 |
October | 0.886055E+10 | 0.00 | 0.351671E+12 | 0.702826E+11 | 0.00 | 0.00 |
November | 0.292800E+11 | 0.00 | 0.207018E+11 | 0.524364E+11 | 0.00 | 0.00 |
December | 0.123971E+12 | 0.00 | 2908108.81 | 0.458632E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.388883E+12 | 0.00 | 0.545234E+13 | 0.958120E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 2908108.81 | 0.445556E+11 | 0.00 | 0.00 |
Maximum of Months | 0.132931E+12 | 0.00 | 0.121524E+13 | 0.130103E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.298399E+11 | 0.00 | 0.613080E+09 | 0.442705E+10 | 0.00 | 0.00 |
February | 0.185269E+11 | 0.00 | 0.251712E+10 | 0.401515E+10 | 0.00 | 0.00 |
March | 0.716970E+10 | 0.00 | 0.727450E+10 | 0.511469E+10 | 0.00 | 0.00 |
April | 0.128701E+10 | 0.00 | 0.309021E+11 | 0.702516E+10 | 0.00 | 0.00 |
May | 0.302220E+09 | 0.00 | 0.577152E+11 | 0.892663E+10 | 0.00 | 0.00 |
June | 23055124.65 | 0.00 | 0.114307E+12 | 0.127942E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.139664E+12 | 0.142315E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.130993E+12 | 0.140829E+11 | 0.00 | 0.00 |
September | 3450986.52 | 0.00 | 0.824280E+11 | 0.897807E+10 | 0.00 | 0.00 |
October | 0.353383E+10 | 0.00 | 0.352528E+11 | 0.611754E+10 | 0.00 | 0.00 |
November | 0.104613E+11 | 0.00 | 0.150822E+10 | 0.439902E+10 | 0.00 | 0.00 |
December | 0.291598E+11 | 0.00 | 592.28 | 0.435801E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100307E+12 | 0.00 | 0.603175E+12 | 0.944699E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 592.28 | 0.401515E+10 | 0.00 | 0.00 |
Maximum of Months | 0.298399E+11 | 0.00 | 0.139664E+12 | 0.142315E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 139559.43 | 0.183071E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.139424E+10 | 0.164023E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.380723E+10 | 0.192356E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.205081E+11 | 0.178411E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.357141E+11 | 0.192395E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.654134E+11 | 0.189785E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.789673E+11 | 0.192527E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.817150E+11 | 0.210397E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.531638E+11 | 0.195599E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.243442E+11 | 0.200382E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.558754E+09 | 0.184875E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.184086E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.365586E+12 | 0.226791E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.164023E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.817150E+11 | 0.210397E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.497005E+12 | 0.271644E+12 | 0.00 | 21.03 |
February | 0.00 | 0.00 | 0.759922E+12 | 0.335011E+12 | 0.00 | 31.07 |
March | 0.00 | 0.00 | 0.118645E+13 | 0.467671E+12 | 0.00 | 46.39 |
April | 0.00 | 0.00 | 0.148848E+13 | 0.562487E+12 | 0.00 | 57.45 |
May | 0.00 | 0.00 | 0.513385E+12 | 0.276667E+12 | 0.00 | 17.87 |
June | 0.00 | 0.00 | 0.846577E+12 | 0.375134E+12 | 0.00 | 20.99 |
July | 0.00 | 0.00 | 0.123181E+13 | 0.494005E+12 | 0.00 | 22.46 |
August | 0.00 | 0.00 | 0.158678E+13 | 0.629560E+12 | 0.00 | 51.03 |
September | 0.00 | 0.00 | 0.506785E+12 | 0.268874E+12 | 0.00 | 15.34 |
October | 0.00 | 0.00 | 0.858755E+12 | 0.376364E+12 | 0.00 | 31.08 |
November | 0.00 | 0.00 | 0.115293E+13 | 0.454547E+12 | 0.00 | 47.03 |
December | 0.00 | 0.00 | 0.152604E+13 | 0.567072E+12 | 0.00 | 65.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.121549E+14 | 0.507904E+13 | 0.00 | 427.69 |
Minimum of Months | 0.00 | 0.00 | 0.497005E+12 | 0.268874E+12 | 0.00 | 15.34 |
Maximum of Months | 0.00 | 0.00 | 0.158678E+13 | 0.629560E+12 | 0.00 | 65.95 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.603684E+10 | 0.309202E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.116930E+11 | 0.402703E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.199168E+11 | 0.583332E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.264812E+11 | 0.745800E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.815920E+10 | 0.368104E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.150990E+11 | 0.552519E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.228703E+11 | 0.776563E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.299228E+11 | 0.939257E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.832648E+10 | 0.368260E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.142656E+11 | 0.486333E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.190426E+11 | 0.550536E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.255690E+11 | 0.677680E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207383E+12 | 0.676029E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.603684E+10 | 0.309202E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.299228E+11 | 0.939257E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.377707E+11 | 0.254537E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.958465E+11 | 0.354241E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.177729E+12 | 0.534472E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245292E+12 | 0.698529E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.727828E+11 | 0.340916E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.142232E+12 | 0.523698E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.218047E+12 | 0.740797E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.279978E+12 | 0.884873E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.751514E+11 | 0.342475E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.127155E+12 | 0.446995E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.166287E+12 | 0.497866E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.221268E+12 | 0.607311E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.185954E+13 | 0.622671E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.377707E+11 | 0.254537E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.279978E+12 | 0.884873E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.183443E+10 | 0.215912E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.789414E+10 | 0.324308E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.166077E+11 | 0.517273E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.240435E+11 | 0.694870E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.705562E+10 | 0.340656E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.142903E+11 | 0.530242E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.220142E+11 | 0.751074E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.281609E+11 | 0.894474E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.743912E+10 | 0.345192E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.119612E+11 | 0.436600E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.149949E+11 | 0.471879E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.198676E+11 | 0.571144E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.176163E+12 | 0.609362E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.183443E+10 | 0.215912E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.281609E+11 | 0.894474E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.629459E+10 | 0.115025E+10 | 0.322764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.664617E+10 | 0.349401E+10 | 0.127086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.980842E+10 | 0.108938E+11 | 37300275.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134656E+11 | 0.405220E+11 | 240520.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114938E+11 | 0.604086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147791E+11 | 0.116807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167111E+11 | 0.149613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202444E+11 | 0.159466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112601E+11 | 0.864646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.993933E+10 | 0.415551E+11 | 72261650.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.858782E+10 | 0.271523E+10 | 46316627.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.808688E+10 | 43718.29 | 0.929052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137317E+12 | 0.673089E+12 | 0.558367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.629459E+10 | 43718.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.202444E+11 | 0.159466E+12 | 0.322764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.453868E+11 | 0.100859E+11 | 0.132931E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.445556E+11 | 0.293658E+11 | 0.730552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.611126E+11 | 0.840737E+11 | 0.188781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.783416E+11 | 0.293867E+12 | 0.170544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.927030E+11 | 0.526489E+12 | 0.193769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119193E+12 | 0.100454E+13 | 7653852.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128466E+12 | 0.121524E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130103E+12 | 0.115813E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.896763E+11 | 0.758173E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.702826E+11 | 0.351671E+12 | 0.886055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.524364E+11 | 0.207018E+11 | 0.292800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.458632E+11 | 2908108.81 | 0.123971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.958120E+12 | 0.545234E+13 | 0.388883E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.445556E+11 | 2908108.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130103E+12 | 0.121524E+13 | 0.132931E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.442705E+10 | 0.613080E+09 | 0.298399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.401515E+10 | 0.251712E+10 | 0.185269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511469E+10 | 0.727450E+10 | 0.716970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.702516E+10 | 0.309021E+11 | 0.128701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.892663E+10 | 0.577152E+11 | 0.302220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127942E+11 | 0.114307E+12 | 23055124.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142315E+11 | 0.139664E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140829E+11 | 0.130993E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.897807E+10 | 0.824280E+11 | 3450986.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.611754E+10 | 0.352528E+11 | 0.353383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.439902E+10 | 0.150822E+10 | 0.104613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.435801E+10 | 592.28 | 0.291598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.944699E+11 | 0.603175E+12 | 0.100307E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.401515E+10 | 592.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142315E+11 | 0.139664E+12 | 0.298399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.183071E+11 | 139559.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164023E+11 | 0.139424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192356E+11 | 0.380723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178411E+11 | 0.205081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192395E+11 | 0.357141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.189785E+11 | 0.654134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.192527E+11 | 0.789673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.210397E+11 | 0.817150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195599E+11 | 0.531638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200382E+11 | 0.243442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184875E+11 | 0.558754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226791E+12 | 0.365586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.210397E+11 | 0.817150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.114606E+12 | 0.396513E+12 | 0.00 | 0.00 | 0.00 | 0.562921E+11 | 0.00 | 0.00 |
February | 0.103516E+12 | 0.611935E+12 | 0.00 | 0.00 | 0.00 | 0.831345E+11 | 0.00 | 0.00 |
March | 0.114606E+12 | 0.958077E+12 | 0.00 | 0.00 | 0.00 | 0.124133E+12 | 0.00 | 0.00 |
April | 0.110909E+12 | 0.119135E+13 | 0.00 | 0.00 | 0.00 | 0.153756E+12 | 0.00 | 0.00 |
May | 0.114606E+12 | 0.399365E+12 | 0.00 | 0.00 | 0.00 | 0.478256E+11 | 0.00 | 0.00 |
June | 0.110909E+12 | 0.638768E+12 | 0.00 | 0.00 | 0.00 | 0.561631E+11 | 0.00 | 0.00 |
July | 0.114606E+12 | 0.912781E+12 | 0.00 | 0.00 | 0.00 | 0.600973E+11 | 0.00 | 0.00 |
August | 0.114606E+12 | 0.120900E+13 | 0.00 | 0.00 | 0.00 | 0.136562E+12 | 0.00 | 0.00 |
September | 0.110909E+12 | 0.390063E+12 | 0.00 | 0.00 | 0.00 | 0.410578E+11 | 0.00 | 0.00 |
October | 0.114606E+12 | 0.680556E+12 | 0.00 | 0.00 | 0.00 | 0.831835E+11 | 0.00 | 0.00 |
November | 0.110909E+12 | 0.935728E+12 | 0.00 | 0.00 | 0.00 | 0.125867E+12 | 0.00 | 0.00 |
December | 0.114606E+12 | 0.125086E+13 | 0.00 | 0.00 | 0.00 | 0.176489E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.134940E+13 | 0.957500E+13 | 0.00 | 0.00 | 0.00 | 0.114456E+13 | 0.00 | 0.00 |
Minimum of Months | 0.103516E+12 | 0.390063E+12 | 0.00 | 0.00 | 0.00 | 0.410578E+11 | 0.00 | 0.00 |
Maximum of Months | 0.114606E+12 | 0.125086E+13 | 0.00 | 0.00 | 0.00 | 0.176489E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.178356E+10 | 0.472837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161095E+10 | 0.927689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178356E+10 | 0.158670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172602E+10 | 0.207493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178356E+10 | 0.626172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172602E+10 | 0.112999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178356E+10 | 0.168882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178356E+10 | 0.223138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172602E+10 | 0.636990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178356E+10 | 0.111858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172602E+10 | 0.152633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178356E+10 | 0.205757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209999E+11 | 0.160780E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161095E+10 | 0.472837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178356E+10 | 0.223138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.170425E+11 | 0.293595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153932E+11 | 0.758155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170425E+11 | 0.141324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164927E+11 | 0.191932E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170425E+11 | 0.557337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164927E+11 | 0.106354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170425E+11 | 0.161010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170425E+11 | 0.208533E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164927E+11 | 0.573966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170425E+11 | 0.994975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164927E+11 | 0.132993E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170425E+11 | 0.177579E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200661E+12 | 0.143753E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153932E+11 | 0.293595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170425E+11 | 0.208533E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.174085E+10 | 0.141617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157238E+10 | 0.622344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174085E+10 | 0.131758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168470E+10 | 0.187795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174085E+10 | 0.538992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168470E+10 | 0.106726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174085E+10 | 0.162443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174085E+10 | 0.209570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168470E+10 | 0.567190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174085E+10 | 0.933602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168470E+10 | 0.119608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174085E+10 | 0.158970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204971E+11 | 0.135724E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157238E+10 | 0.141617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174085E+10 | 0.209570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.629459E+10 | 0.322764E+10 | 0.115025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.664617E+10 | 0.127086E+10 | 0.349401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.980842E+10 | 37300275.81 | 0.108938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134656E+11 | 240520.54 | 0.405220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114938E+11 | 0.00 | 0.604086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147791E+11 | 0.00 | 0.116807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167111E+11 | 0.00 | 0.149613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202444E+11 | 0.00 | 0.159466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112601E+11 | 0.00 | 0.864646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.993933E+10 | 72261650.08 | 0.415551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.858782E+10 | 46316627.88 | 0.271523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.808688E+10 | 0.929052E+09 | 43718.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137317E+12 | 0.558367E+10 | 0.673089E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.629459E+10 | 0.00 | 43718.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.202444E+11 | 0.322764E+10 | 0.159466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.453868E+11 | 0.132931E+12 | 0.100859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.445556E+11 | 0.730552E+11 | 0.293658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.611126E+11 | 0.188781E+11 | 0.840737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.783416E+11 | 0.170544E+10 | 0.293867E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.927030E+11 | 0.193769E+09 | 0.526489E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119193E+12 | 7653852.17 | 0.100454E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128466E+12 | 0.00 | 0.121524E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130103E+12 | 0.00 | 0.115813E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.896763E+11 | 0.00 | 0.758173E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.702826E+11 | 0.886055E+10 | 0.351671E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.524364E+11 | 0.292800E+11 | 0.207018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.458632E+11 | 0.123971E+12 | 2908108.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.958120E+12 | 0.388883E+12 | 0.545234E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.445556E+11 | 0.00 | 2908108.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130103E+12 | 0.132931E+12 | 0.121524E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.442705E+10 | 0.298399E+11 | 0.613080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.401515E+10 | 0.185269E+11 | 0.251712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511469E+10 | 0.716970E+10 | 0.727450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.702516E+10 | 0.128701E+10 | 0.309021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.892663E+10 | 0.302220E+09 | 0.577152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127942E+11 | 23055124.65 | 0.114307E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142315E+11 | 0.00 | 0.139664E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140829E+11 | 0.00 | 0.130993E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.897807E+10 | 3450986.52 | 0.824280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.611754E+10 | 0.353383E+10 | 0.352528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.439902E+10 | 0.104613E+11 | 0.150822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.435801E+10 | 0.291598E+11 | 592.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.944699E+11 | 0.100307E+12 | 0.603175E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.401515E+10 | 0.00 | 592.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142315E+11 | 0.298399E+11 | 0.139664E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.183071E+11 | 0.00 | 139559.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164023E+11 | 0.00 | 0.139424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192356E+11 | 0.00 | 0.380723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178411E+11 | 0.00 | 0.205081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192395E+11 | 0.00 | 0.357141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.189785E+11 | 0.00 | 0.654134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.192527E+11 | 0.00 | 0.789673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.210397E+11 | 0.00 | 0.817150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195599E+11 | 0.00 | 0.531638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200382E+11 | 0.00 | 0.243442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184875E+11 | 0.00 | 0.558754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226791E+12 | 0.00 | 0.365586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.210397E+11 | 0.00 | 0.817150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.114606E+12 | 0.00 | 0.497005E+12 | 0.00 | 0.100492E+12 | 0.00 | 0.00 | 0.00 | 0.565455E+11 | 0.00 | 0.00 | 0.00 |
February | 0.103516E+12 | 0.00 | 0.759922E+12 | 0.00 | 0.147987E+12 | 0.00 | 0.00 | 0.00 | 0.835088E+11 | 0.00 | 0.00 | 0.00 |
March | 0.114606E+12 | 0.00 | 0.118645E+13 | 0.00 | 0.228372E+12 | 0.00 | 0.00 | 0.00 | 0.124692E+12 | 0.00 | 0.00 | 0.00 |
April | 0.110909E+12 | 0.00 | 0.148848E+13 | 0.00 | 0.297130E+12 | 0.00 | 0.00 | 0.00 | 0.154448E+12 | 0.00 | 0.00 | 0.00 |
May | 0.114606E+12 | 0.00 | 0.513385E+12 | 0.00 | 0.114020E+12 | 0.00 | 0.00 | 0.00 | 0.480409E+11 | 0.00 | 0.00 | 0.00 |
June | 0.110909E+12 | 0.00 | 0.846577E+12 | 0.00 | 0.207809E+12 | 0.00 | 0.00 | 0.00 | 0.564159E+11 | 0.00 | 0.00 | 0.00 |
July | 0.114606E+12 | 0.00 | 0.123181E+13 | 0.00 | 0.319031E+12 | 0.00 | 0.00 | 0.00 | 0.603678E+11 | 0.00 | 0.00 | 0.00 |
August | 0.114606E+12 | 0.00 | 0.158678E+13 | 0.00 | 0.377777E+12 | 0.00 | 0.00 | 0.00 | 0.137177E+12 | 0.00 | 0.00 | 0.00 |
September | 0.110909E+12 | 0.00 | 0.506785E+12 | 0.00 | 0.116722E+12 | 0.00 | 0.00 | 0.00 | 0.412427E+11 | 0.00 | 0.00 | 0.00 |
October | 0.114606E+12 | 0.00 | 0.858755E+12 | 0.00 | 0.178199E+12 | 0.00 | 0.00 | 0.00 | 0.835580E+11 | 0.00 | 0.00 | 0.00 |
November | 0.110909E+12 | 0.00 | 0.115293E+13 | 0.00 | 0.217204E+12 | 0.00 | 0.00 | 0.00 | 0.126434E+12 | 0.00 | 0.00 | 0.00 |
December | 0.114606E+12 | 0.00 | 0.152604E+13 | 0.00 | 0.275182E+12 | 0.00 | 0.00 | 0.00 | 0.177284E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134940E+13 | 0.00 | 0.121549E+14 | 0.00 | 0.257993E+13 | 0.00 | 0.00 | 0.00 | 0.114971E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103516E+12 | 0.00 | 0.497005E+12 | 0.00 | 0.100492E+12 | 0.00 | 0.00 | 0.00 | 0.412427E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114606E+12 | 0.00 | 0.158678E+13 | 0.00 | 0.377777E+12 | 0.00 | 0.00 | 0.00 | 0.177284E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.178356E+10 | 0.00 | 0.603684E+10 | 0.00 | 0.130847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161095E+10 | 0.00 | 0.116930E+11 | 0.00 | 0.241607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178356E+10 | 0.00 | 0.199168E+11 | 0.00 | 0.404976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172602E+10 | 0.00 | 0.264812E+11 | 0.00 | 0.573198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178356E+10 | 0.00 | 0.815920E+10 | 0.00 | 0.189748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172602E+10 | 0.00 | 0.150990E+11 | 0.00 | 0.379917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178356E+10 | 0.00 | 0.228703E+11 | 0.00 | 0.598208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178356E+10 | 0.00 | 0.299228E+11 | 0.00 | 0.760902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172602E+10 | 0.00 | 0.832648E+10 | 0.00 | 0.195658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178356E+10 | 0.00 | 0.142656E+11 | 0.00 | 0.307977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172602E+10 | 0.00 | 0.190426E+11 | 0.00 | 0.377934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178356E+10 | 0.00 | 0.255690E+11 | 0.00 | 0.499324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209999E+11 | 0.00 | 0.207383E+12 | 0.00 | 0.466029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161095E+10 | 0.00 | 0.603684E+10 | 0.00 | 0.130847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178356E+10 | 0.00 | 0.299228E+11 | 0.00 | 0.760902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.170425E+11 | 0.00 | 0.377707E+11 | 0.00 | 0.841123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153932E+11 | 0.00 | 0.958465E+11 | 0.00 | 0.200309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170425E+11 | 0.00 | 0.177729E+12 | 0.00 | 0.364048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164927E+11 | 0.00 | 0.245292E+12 | 0.00 | 0.533602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170425E+11 | 0.00 | 0.727828E+11 | 0.00 | 0.170491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164927E+11 | 0.00 | 0.142232E+12 | 0.00 | 0.358771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170425E+11 | 0.00 | 0.218047E+12 | 0.00 | 0.570373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170425E+11 | 0.00 | 0.279978E+12 | 0.00 | 0.714448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164927E+11 | 0.00 | 0.751514E+11 | 0.00 | 0.177548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170425E+11 | 0.00 | 0.127155E+12 | 0.00 | 0.276570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164927E+11 | 0.00 | 0.166287E+12 | 0.00 | 0.332939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170425E+11 | 0.00 | 0.221268E+12 | 0.00 | 0.436887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200661E+12 | 0.00 | 0.185954E+13 | 0.00 | 0.422010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153932E+11 | 0.00 | 0.377707E+11 | 0.00 | 0.841123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170425E+11 | 0.00 | 0.279978E+12 | 0.00 | 0.714448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.174085E+10 | 0.00 | 0.183443E+10 | 0.00 | 0.418264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157238E+10 | 0.00 | 0.789414E+10 | 0.00 | 0.167070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174085E+10 | 0.00 | 0.166077E+11 | 0.00 | 0.343188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168470E+10 | 0.00 | 0.240435E+11 | 0.00 | 0.526400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174085E+10 | 0.00 | 0.705562E+10 | 0.00 | 0.166570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168470E+10 | 0.00 | 0.142903E+11 | 0.00 | 0.361772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174085E+10 | 0.00 | 0.220142E+11 | 0.00 | 0.576989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174085E+10 | 0.00 | 0.281609E+11 | 0.00 | 0.720388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168470E+10 | 0.00 | 0.743912E+10 | 0.00 | 0.176722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174085E+10 | 0.00 | 0.119612E+11 | 0.00 | 0.262514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168470E+10 | 0.00 | 0.149949E+11 | 0.00 | 0.303409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174085E+10 | 0.00 | 0.198676E+11 | 0.00 | 0.397059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204971E+11 | 0.00 | 0.176163E+12 | 0.00 | 0.404391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157238E+10 | 0.00 | 0.183443E+10 | 0.00 | 0.418264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174085E+10 | 0.00 | 0.281609E+11 | 0.00 | 0.720388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.463575E+09 | 0.00 | 0.00 | 0.124351E+09 | 0.00 | 0.00 | 0.768694E+11 | 0.00 | 0.80 |
February | 0.342758E+09 | 0.00 | 0.00 | 0.111022E+09 | 0.00 | 0.00 | 0.686342E+11 | 0.00 | 0.89 |
March | 0.230962E+09 | 0.00 | 0.00 | 0.127627E+09 | 0.00 | 0.00 | 0.809829E+11 | 0.00 | 1.31 |
April | 0.197738E+09 | 12225718.55 | 0.00 | 0.122512E+09 | 113528.65 | 0.00 | 0.605880E+11 | 0.00 | 1.47 |
May | 0.140571E+09 | 0.118319E+09 | 0.00 | 0.125384E+09 | 10032279.78 | 0.00 | 0.495124E+11 | 0.00 | 1.45 |
June | 42783080.82 | 0.246018E+10 | 0.00 | 83178750.71 | 26497670.53 | 0.00 | 0.237453E+11 | 0.00 | 1.11 |
July | 76506033.24 | 0.286296E+10 | 0.00 | 79038595.21 | 67239762.20 | 0.00 | 0.116489E+11 | 0.00 | 0.97 |
August | 85802990.24 | 0.172028E+10 | 0.00 | 0.116517E+09 | 41370116.85 | 0.00 | 0.203360E+11 | 0.00 | 1.23 |
September | 0.168081E+09 | 0.317870E+09 | 0.00 | 0.131163E+09 | 11716608.50 | 0.00 | 0.355949E+11 | 0.00 | 1.46 |
October | 0.291260E+09 | 19216123.98 | 0.00 | 0.148634E+09 | 599665.10 | 0.00 | 0.668156E+11 | 0.00 | 1.50 |
November | 0.417168E+09 | 0.00 | 0.00 | 0.141180E+09 | 0.00 | 0.00 | 0.846449E+11 | 0.00 | 1.15 |
December | 0.482779E+09 | 0.00 | 0.00 | 0.145255E+09 | 0.00 | 0.00 | 0.823743E+11 | 0.00 | 0.76 |
Annual Sum or Average | 0.293998E+10 | 0.751105E+10 | 0.00 | 0.145586E+10 | 0.157570E+09 | 0.00 | 0.661747E+12 | 0.00 | 1.18 |
Minimum of Months | 42783080.82 | 0.00 | 0.00 | 79038595.21 | 0.00 | 0.00 | 0.116489E+11 | 0.00 | 0.76 |
Maximum of Months | 0.482779E+09 | 0.286296E+10 | 0.00 | 0.148634E+09 | 67239762.20 | 0.00 | 0.846449E+11 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.324367E+10 | 0.00 | 0.00 | 78448094.46 | 0.00 | 0.00 | 0.473246E+11 | 0.00 | 0.53 |
February | 0.260220E+10 | 0.00 | 0.00 | 81617591.88 | 0.00 | 0.00 | 0.463556E+11 | 0.00 | 0.62 |
March | 0.388773E+10 | 0.00 | 0.00 | 0.105941E+09 | 0.00 | 0.00 | 0.603019E+11 | 0.00 | 0.98 |
April | 0.945944E+10 | 2963605.66 | 0.00 | 0.104483E+09 | 0.00 | 0.00 | 0.484399E+11 | 0.00 | 1.28 |
May | 0.337982E+10 | 50310940.98 | 0.00 | 98261124.87 | 16596697.19 | 0.00 | 0.358231E+11 | 0.00 | 1.05 |
June | 0.447415E+10 | 0.975113E+09 | 0.00 | 69134588.84 | 0.125608E+09 | 0.00 | 0.159100E+11 | 0.00 | 0.86 |
July | 0.392110E+10 | 0.141891E+10 | 0.00 | 51976144.19 | 0.391151E+09 | 0.00 | 0.530941E+10 | 0.00 | 0.74 |
August | 0.651172E+10 | 0.108673E+10 | 0.00 | 89119031.03 | 0.127986E+09 | 0.00 | 0.134368E+11 | 0.00 | 1.08 |
September | 0.299669E+10 | 0.301365E+09 | 0.00 | 92182358.56 | 15853334.03 | 0.00 | 0.227044E+11 | 0.00 | 0.95 |
October | 0.465589E+10 | 2265501.83 | 0.00 | 0.104087E+09 | 796631.50 | 0.00 | 0.440190E+11 | 0.00 | 0.98 |
November | 0.488141E+10 | 0.00 | 0.00 | 0.101166E+09 | 0.00 | 0.00 | 0.585103E+11 | 0.00 | 0.83 |
December | 0.370578E+10 | 0.00 | 0.00 | 0.106671E+09 | 0.00 | 0.00 | 0.572028E+11 | 0.00 | 0.56 |
Annual Sum or Average | 0.537196E+11 | 0.383766E+10 | 0.00 | 0.108309E+10 | 0.677991E+09 | 0.00 | 0.455338E+12 | 0.00 | 0.87 |
Minimum of Months | 0.260220E+10 | 0.00 | 0.00 | 51976144.19 | 0.00 | 0.00 | 0.530941E+10 | 0.00 | 0.53 |
Maximum of Months | 0.945944E+10 | 0.141891E+10 | 0.00 | 0.106671E+09 | 0.391151E+09 | 0.00 | 0.603019E+11 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143560E+12 | 0.00 | 0.00 | 0.311246E+09 | 0.00 | 0.00 | 0.222978E+12 | 0.00 | 0.39 |
February | 0.100707E+12 | 0.00 | 0.00 | 0.357570E+09 | 0.00 | 0.00 | 0.235028E+12 | 0.00 | 0.44 |
March | 0.442157E+11 | 0.00 | 0.00 | 0.594243E+09 | 0.00 | 0.00 | 0.381956E+12 | 0.00 | 0.68 |
April | 0.314204E+11 | 22409244.50 | 0.00 | 0.692907E+09 | 12238313.50 | 0.00 | 0.328299E+12 | 0.00 | 0.83 |
May | 0.241035E+11 | 0.527756E+09 | 0.00 | 0.794113E+09 | 0.145186E+09 | 0.00 | 0.290521E+12 | 0.00 | 0.87 |
June | 0.185715E+11 | 0.108315E+11 | 0.00 | 0.580077E+09 | 0.520341E+09 | 0.00 | 0.127446E+12 | 0.00 | 0.67 |
July | 0.131879E+11 | 0.139085E+11 | 0.00 | 0.453270E+09 | 0.236255E+10 | 0.00 | 0.419545E+11 | 0.00 | 0.53 |
August | 0.156717E+11 | 0.816862E+10 | 0.00 | 0.714587E+09 | 0.829387E+09 | 0.00 | 0.101692E+12 | 0.00 | 0.69 |
September | 0.211998E+11 | 0.282876E+10 | 0.00 | 0.750909E+09 | 0.202428E+09 | 0.00 | 0.179042E+12 | 0.00 | 0.77 |
October | 0.420564E+11 | 17251821.05 | 0.00 | 0.713461E+09 | 71889297.48 | 0.00 | 0.304299E+12 | 0.00 | 0.73 |
November | 0.619229E+11 | 0.00 | 0.00 | 0.504680E+09 | 0.00 | 0.00 | 0.340634E+12 | 0.00 | 0.55 |
December | 0.138645E+12 | 0.00 | 0.00 | 0.331738E+09 | 0.00 | 0.00 | 0.229332E+12 | 0.00 | 0.35 |
Annual Sum or Average | 0.655262E+12 | 0.363048E+11 | 0.00 | 0.679880E+10 | 0.414402E+10 | 0.00 | 0.278318E+13 | 0.00 | 0.63 |
Minimum of Months | 0.131879E+11 | 0.00 | 0.00 | 0.311246E+09 | 0.00 | 0.00 | 0.419545E+11 | 0.00 | 0.35 |
Maximum of Months | 0.143560E+12 | 0.139085E+11 | 0.00 | 0.794113E+09 | 0.236255E+10 | 0.00 | 0.381956E+12 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213842E+11 | 0.00 | 0.00 | 6590636.72 | 0.00 | 0.871808E+09 | 0.668401E+10 | 0.00 | 0.32 |
February | 0.158210E+11 | 0.00 | 0.00 | 12289793.30 | 0.00 | 0.284950E+09 | 0.104436E+11 | 0.00 | 0.36 |
March | 0.107498E+11 | 0.00 | 0.00 | 32264086.63 | 0.00 | 23225726.66 | 0.238908E+11 | 0.00 | 0.57 |
April | 0.480644E+10 | 35722.88 | 0.00 | 53284126.88 | 0.00 | 0.00 | 0.272354E+11 | 0.00 | 0.82 |
May | 0.339367E+10 | 22467752.59 | 0.00 | 69899270.42 | 14253702.59 | 0.00 | 0.258605E+11 | 0.00 | 0.88 |
June | 0.192078E+10 | 0.716479E+09 | 0.00 | 65090506.18 | 51066227.90 | 0.00 | 0.117211E+11 | 0.00 | 0.67 |
July | 0.125969E+10 | 0.928798E+09 | 0.00 | 58025040.82 | 0.222795E+09 | 0.00 | 0.407865E+10 | 0.00 | 0.55 |
August | 0.146468E+10 | 0.537649E+09 | 0.00 | 82662589.74 | 81643795.42 | 0.00 | 0.100023E+11 | 0.00 | 0.72 |
September | 0.169437E+10 | 0.152826E+09 | 0.00 | 72260709.70 | 8600886.60 | 0.00 | 0.161808E+11 | 0.00 | 0.78 |
October | 0.727733E+10 | 2085308.52 | 0.00 | 48663725.09 | 450762.86 | 0.00 | 0.205001E+11 | 0.00 | 0.66 |
November | 0.133365E+11 | 0.00 | 0.00 | 21312557.81 | 0.00 | 0.190850E+09 | 0.168958E+11 | 0.00 | 0.43 |
December | 0.219001E+11 | 0.00 | 0.00 | 6031014.10 | 0.00 | 0.554286E+09 | 0.609274E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.105009E+12 | 0.236034E+10 | 0.00 | 0.528374E+09 | 0.378811E+09 | 0.192512E+10 | 0.179586E+12 | 0.00 | 0.59 |
Minimum of Months | 0.125969E+10 | 0.00 | 0.00 | 6031014.10 | 0.00 | 0.00 | 0.407865E+10 | 0.00 | 0.28 |
Maximum of Months | 0.219001E+11 | 0.928798E+09 | 0.00 | 82662589.74 | 0.222795E+09 | 0.871808E+09 | 0.272354E+11 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.550237E+10 | 0.00 | 0.00 | 79246.37 | 0.00 | 21003229.99 | 0.261595E+09 | 0.00 | 0.47 |
February | 0.421009E+10 | 0.00 | 0.00 | 898971.45 | 0.00 | 11273238.90 | 0.985052E+09 | 0.00 | 0.52 |
March | 0.317468E+10 | 0.00 | 0.00 | 4624340.12 | 0.00 | 0.00 | 0.352957E+10 | 0.00 | 0.83 |
April | 0.265077E+10 | 549534.93 | 0.00 | 8786348.58 | 0.00 | 0.00 | 0.428208E+10 | 0.00 | 1.29 |
May | 0.122758E+10 | 11129512.63 | 0.00 | 10444671.13 | 2804310.40 | 0.00 | 0.375680E+10 | 0.00 | 1.15 |
June | 0.899832E+09 | 0.209440E+09 | 0.00 | 10101810.84 | 21777913.24 | 0.00 | 0.209550E+10 | 0.00 | 1.11 |
July | 0.706226E+09 | 0.304821E+09 | 0.00 | 8091638.23 | 66264868.59 | 0.00 | 0.763683E+09 | 0.00 | 1.02 |
August | 0.122397E+10 | 0.204159E+09 | 0.00 | 12587632.61 | 21625606.19 | 0.00 | 0.172741E+10 | 0.00 | 1.35 |
September | 0.915562E+09 | 49592025.36 | 0.00 | 9844834.84 | 2678705.83 | 0.00 | 0.235282E+10 | 0.00 | 1.02 |
October | 0.260392E+10 | 382453.20 | 0.00 | 6226694.14 | 134605.22 | 0.00 | 0.268261E+10 | 0.00 | 0.90 |
November | 0.385042E+10 | 0.00 | 0.00 | 2342193.68 | 0.00 | 0.00 | 0.245358E+10 | 0.00 | 0.65 |
December | 0.549925E+10 | 0.00 | 0.00 | 270264.08 | 0.00 | 1076375.33 | 0.507324E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.324647E+11 | 0.780074E+09 | 0.00 | 74298646.07 | 0.115286E+09 | 33352844.21 | 0.253980E+11 | 0.00 | 0.90 |
Minimum of Months | 0.706226E+09 | 0.00 | 0.00 | 79246.37 | 0.00 | 0.00 | 0.261595E+09 | 0.00 | 0.44 |
Maximum of Months | 0.550237E+10 | 0.304821E+09 | 0.00 | 12587632.61 | 66264868.59 | 21003229.99 | 0.428208E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.558118E+10 | 0.00 | 0.00 | 1463999.86 | 0.00 | 66498936.87 | 0.112051E+10 | 0.00 | 0.85 |
February | 0.432463E+10 | 0.00 | 0.00 | 2353471.12 | 0.00 | 33066052.40 | 0.186558E+10 | 0.00 | 0.96 |
March | 0.341635E+10 | 0.00 | 0.00 | 6559662.43 | 0.00 | 0.00 | 0.471616E+10 | 0.00 | 1.47 |
April | 0.292614E+10 | 436767.81 | 0.00 | 11432707.48 | 0.00 | 0.00 | 0.603062E+10 | 0.00 | 2.35 |
May | 0.137322E+10 | 9880809.31 | 0.00 | 14583919.66 | 3219710.89 | 0.00 | 0.525512E+10 | 0.00 | 2.16 |
June | 0.116406E+10 | 0.161298E+09 | 0.00 | 11659809.09 | 24139502.76 | 0.00 | 0.229891E+10 | 0.00 | 1.92 |
July | 0.874866E+09 | 0.256683E+09 | 0.00 | 8652847.37 | 72991922.74 | 0.00 | 0.729854E+09 | 0.00 | 1.66 |
August | 0.156950E+10 | 0.161278E+09 | 0.00 | 11739966.11 | 24426698.25 | 0.00 | 0.165706E+10 | 0.00 | 2.19 |
September | 0.122448E+10 | 36666431.74 | 0.00 | 11302611.11 | 3012454.37 | 0.00 | 0.294372E+10 | 0.00 | 1.95 |
October | 0.279270E+10 | 299634.15 | 0.00 | 8097200.95 | 147152.19 | 1196198.01 | 0.391076E+10 | 0.00 | 1.67 |
November | 0.430355E+10 | 0.00 | 0.00 | 3319202.75 | 0.00 | 2927834.73 | 0.317738E+10 | 0.00 | 1.17 |
December | 0.581752E+10 | 0.00 | 0.00 | 1448644.18 | 0.00 | 68346604.50 | 0.108582E+10 | 0.00 | 0.78 |
Annual Sum or Average | 0.353682E+11 | 0.626542E+09 | 0.00 | 92614042.13 | 0.127937E+09 | 0.172036E+09 | 0.347915E+11 | 0.00 | 1.60 |
Minimum of Months | 0.874866E+09 | 0.00 | 0.00 | 1448644.18 | 0.00 | 0.00 | 0.729854E+09 | 0.00 | 0.78 |
Maximum of Months | 0.581752E+10 | 0.256683E+09 | 0.00 | 14583919.66 | 72991922.74 | 68346604.50 | 0.603062E+10 | 0.00 | 2.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.316547E+10 | 0.00 | 0.00 | 15812959.48 | 0.00 | 0.124428E+09 | 0.863791E+10 | 0.00 | 1.08 |
February | 0.247739E+10 | 0.00 | 0.00 | 15384438.60 | 0.00 | 30344212.09 | 0.890723E+10 | 0.00 | 1.24 |
March | 0.268247E+10 | 0.00 | 0.00 | 15223289.00 | 0.00 | 0.00 | 0.938590E+10 | 0.00 | 1.59 |
April | 0.305616E+10 | 805543.30 | 0.00 | 14691810.20 | 0.00 | 0.00 | 0.696929E+10 | 0.00 | 1.94 |
May | 0.175815E+10 | 16139852.97 | 0.00 | 11596064.77 | 3412906.83 | 0.00 | 0.413231E+10 | 0.00 | 1.37 |
June | 0.131331E+10 | 0.212922E+09 | 0.00 | 8928312.22 | 26840069.02 | 0.00 | 0.180476E+10 | 0.00 | 1.14 |
July | 0.878302E+09 | 0.346903E+09 | 0.00 | 7913872.63 | 80645788.02 | 0.00 | 0.708313E+09 | 0.00 | 1.09 |
August | 0.149777E+10 | 0.272057E+09 | 0.00 | 15166911.50 | 26318833.64 | 0.00 | 0.190726E+10 | 0.00 | 1.61 |
September | 0.993586E+09 | 95795401.86 | 0.00 | 19902935.54 | 2916826.65 | 0.00 | 0.361533E+10 | 0.00 | 1.59 |
October | 0.187425E+10 | 1033709.26 | 0.00 | 26176019.35 | 0.00 | 0.00 | 0.882938E+10 | 0.00 | 1.90 |
November | 0.224293E+10 | 0.00 | 0.00 | 21778143.37 | 0.00 | 0.00 | 0.122417E+11 | 0.00 | 1.53 |
December | 0.278215E+10 | 0.00 | 0.00 | 19184011.21 | 0.00 | 23742803.71 | 0.112365E+11 | 0.00 | 1.06 |
Annual Sum or Average | 0.247219E+11 | 0.945656E+09 | 0.00 | 0.191759E+09 | 0.140134E+09 | 0.178515E+09 | 0.783758E+11 | 0.00 | 1.43 |
Minimum of Months | 0.878302E+09 | 0.00 | 0.00 | 7913872.63 | 0.00 | 0.00 | 0.708313E+09 | 0.00 | 1.06 |
Maximum of Months | 0.316547E+10 | 0.346903E+09 | 0.00 | 26176019.35 | 80645788.02 | 0.124428E+09 | 0.122417E+11 | 0.00 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.655836E+10 | 0.00 | 0.00 | 2401441.93 | 0.00 | 0.00 | 0.215570E+10 | 0.00 | 1.12 |
February | 0.411310E+10 | 0.00 | 0.00 | 5113181.47 | 0.00 | 0.00 | 0.437065E+10 | 0.00 | 1.38 |
March | 0.234168E+10 | 0.00 | 0.00 | 12305840.16 | 0.00 | 0.00 | 0.834439E+10 | 0.00 | 2.14 |
April | 0.212954E+10 | 856852.53 | 0.00 | 23732675.31 | 0.00 | 0.00 | 0.901325E+10 | 0.00 | 3.35 |
May | 0.164139E+10 | 22541489.77 | 0.00 | 13310828.58 | 1716735.18 | 0.00 | 0.470859E+10 | 0.00 | 2.28 |
June | 0.116162E+10 | 0.279966E+09 | 0.00 | 11980598.02 | 22888534.25 | 0.00 | 0.234629E+10 | 0.00 | 2.04 |
July | 0.883695E+09 | 0.394184E+09 | 0.00 | 10516379.14 | 80437075.85 | 0.00 | 0.978175E+09 | 0.00 | 1.93 |
August | 0.102967E+10 | 0.321519E+09 | 0.00 | 22738225.71 | 10566508.63 | 0.00 | 0.321236E+10 | 0.00 | 2.98 |
September | 0.116266E+10 | 61166047.79 | 0.00 | 13736027.91 | 1930261.28 | 0.00 | 0.295628E+10 | 0.00 | 1.95 |
October | 0.243616E+10 | 522204.72 | 0.00 | 13032176.85 | 194625.76 | 0.00 | 0.553649E+10 | 0.00 | 2.12 |
November | 0.278805E+10 | 0.00 | 0.00 | 8155424.85 | 0.00 | 0.00 | 0.741051E+10 | 0.00 | 1.67 |
December | 0.324729E+10 | 0.00 | 0.00 | 6830878.38 | 0.00 | 0.00 | 0.660191E+10 | 0.00 | 1.14 |
Annual Sum or Average | 0.294932E+11 | 0.108076E+10 | 0.00 | 0.143854E+09 | 0.117734E+09 | 0.00 | 0.576346E+11 | 0.00 | 2.01 |
Minimum of Months | 0.883695E+09 | 0.00 | 0.00 | 2401441.93 | 0.00 | 0.00 | 0.978175E+09 | 0.00 | 1.12 |
Maximum of Months | 0.655836E+10 | 0.394184E+09 | 0.00 | 23732675.31 | 80437075.85 | 0.00 | 0.901325E+10 | 0.00 | 3.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.374030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173913E+11 | 0.00 | 0.00 | 0.45 |
February | 0.357336E+11 | 0.00 | 0.00 | 31019.33 | 0.00 | 0.108545E+11 | 0.271459E+09 | 0.00 | 0.47 |
March | 0.423839E+11 | 0.00 | 0.00 | 6009640.18 | 0.00 | 0.222768E+10 | 0.640102E+10 | 0.00 | 0.64 |
April | 0.235422E+11 | 4613985.64 | 0.00 | 40583582.52 | 2078535.80 | 72730581.17 | 0.183798E+11 | 0.00 | 0.82 |
May | 0.139465E+11 | 0.118772E+09 | 0.00 | 76201045.86 | 24658123.95 | 0.00 | 0.249707E+11 | 0.00 | 0.93 |
June | 0.566590E+10 | 0.258798E+10 | 0.00 | 80058000.62 | 87937134.64 | 0.00 | 0.152421E+11 | 0.00 | 0.89 |
July | 0.236105E+10 | 0.334454E+10 | 0.00 | 70300812.04 | 0.401883E+09 | 0.00 | 0.629540E+10 | 0.00 | 0.76 |
August | 0.387405E+10 | 0.176157E+10 | 0.00 | 98921036.53 | 0.140896E+09 | 0.00 | 0.126144E+11 | 0.00 | 0.87 |
September | 0.991287E+10 | 0.477920E+09 | 0.00 | 71842721.15 | 34379971.08 | 0.00 | 0.156040E+11 | 0.00 | 0.82 |
October | 0.307261E+11 | 2974735.06 | 0.00 | 28619294.56 | 12209564.55 | 0.990274E+09 | 0.962929E+10 | 0.00 | 0.71 |
November | 0.455217E+11 | 0.00 | 0.00 | 695674.72 | 0.00 | 0.489904E+10 | 0.130193E+10 | 0.00 | 0.55 |
December | 0.334876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210464E+11 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.284559E+12 | 0.829837E+10 | 0.00 | 0.473263E+09 | 0.704042E+09 | 0.574819E+11 | 0.110710E+12 | 0.00 | 0.69 |
Minimum of Months | 0.236105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.455217E+11 | 0.334454E+10 | 0.00 | 98921036.53 | 0.401883E+09 | 0.210464E+11 | 0.249707E+11 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.529027E+11 | 0.00 | 0.00 | 1614377.31 | 0.00 | 0.145002E+11 | 0.241574E+10 | 0.00 | 0.90 |
February | 0.468628E+11 | 0.00 | 0.00 | 8801482.17 | 0.00 | 0.697589E+10 | 0.658494E+10 | 0.00 | 0.95 |
March | 0.400555E+11 | 0.00 | 0.00 | 37129263.45 | 0.00 | 0.119021E+10 | 0.301509E+11 | 0.00 | 1.36 |
April | 0.185487E+11 | 7620086.09 | 0.00 | 0.101613E+09 | 408570.02 | 80227086.06 | 0.525505E+11 | 0.00 | 1.97 |
May | 0.141277E+11 | 0.127458E+09 | 0.00 | 0.140386E+09 | 31490464.83 | 0.00 | 0.477232E+11 | 0.00 | 2.10 |
June | 0.754618E+10 | 0.219707E+10 | 0.00 | 0.111698E+09 | 0.105155E+09 | 0.00 | 0.211696E+11 | 0.00 | 1.77 |
July | 0.342532E+10 | 0.356178E+10 | 0.00 | 90358207.80 | 0.321981E+09 | 0.00 | 0.753906E+10 | 0.00 | 1.42 |
August | 0.561010E+10 | 0.174567E+10 | 0.00 | 0.130663E+09 | 0.179682E+09 | 0.00 | 0.173256E+11 | 0.00 | 1.76 |
September | 0.132628E+11 | 0.388097E+09 | 0.00 | 0.102227E+09 | 43696393.15 | 0.00 | 0.245904E+11 | 0.00 | 1.85 |
October | 0.316825E+11 | 3833775.94 | 0.00 | 60349361.34 | 15349334.50 | 0.790000E+09 | 0.271119E+11 | 0.00 | 1.56 |
November | 0.529501E+11 | 0.00 | 0.00 | 12245176.18 | 0.00 | 0.278824E+10 | 0.112088E+11 | 0.00 | 1.09 |
December | 0.541097E+11 | 0.00 | 0.00 | 686731.10 | 0.00 | 0.143676E+11 | 0.104156E+10 | 0.00 | 0.79 |
Annual Sum or Average | 0.341084E+12 | 0.803152E+10 | 0.00 | 0.797773E+09 | 0.697763E+09 | 0.406924E+11 | 0.249412E+12 | 0.00 | 1.46 |
Minimum of Months | 0.342532E+10 | 0.00 | 0.00 | 686731.10 | 0.00 | 0.00 | 0.104156E+10 | 0.00 | 0.79 |
Maximum of Months | 0.541097E+11 | 0.356178E+10 | 0.00 | 0.140386E+09 | 0.321981E+09 | 0.145002E+11 | 0.525505E+11 | 0.00 | 2.10 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.289091E+11 | 0.00 | 0.00 | 0.165524E+09 | 0.00 | 0.694701E+10 | 0.776215E+11 | 0.00 | 1.07 |
February | 0.223049E+11 | 0.00 | 0.00 | 0.148734E+09 | 0.00 | 0.367357E+10 | 0.786250E+11 | 0.00 | 1.17 |
March | 0.263473E+11 | 0.00 | 0.00 | 0.131360E+09 | 0.00 | 0.387592E+09 | 0.743795E+11 | 0.00 | 1.40 |
April | 0.203625E+11 | 12473176.49 | 0.00 | 0.114726E+09 | 396290.31 | 7323434.93 | 0.518061E+11 | 0.00 | 1.48 |
May | 0.180488E+11 | 0.192667E+09 | 0.00 | 96148601.42 | 30544008.88 | 0.00 | 0.316674E+11 | 0.00 | 1.20 |
June | 0.100444E+11 | 0.262267E+10 | 0.00 | 70923739.22 | 0.110801E+09 | 0.00 | 0.125679E+11 | 0.00 | 0.92 |
July | 0.317566E+10 | 0.387061E+10 | 0.00 | 69360784.19 | 0.496934E+09 | 0.00 | 0.613009E+10 | 0.00 | 0.82 |
August | 0.484161E+10 | 0.258840E+10 | 0.00 | 0.135808E+09 | 0.174485E+09 | 0.00 | 0.157443E+11 | 0.00 | 1.13 |
September | 0.897003E+10 | 0.106376E+10 | 0.00 | 0.186283E+09 | 32369068.42 | 0.00 | 0.305034E+11 | 0.00 | 1.45 |
October | 0.162587E+11 | 34136537.40 | 0.00 | 0.262972E+09 | 758390.76 | 0.320789E+09 | 0.777034E+11 | 0.00 | 1.76 |
November | 0.207928E+11 | 0.00 | 0.00 | 0.209598E+09 | 0.00 | 0.340789E+09 | 0.105800E+12 | 0.00 | 1.38 |
December | 0.250072E+11 | 0.00 | 0.00 | 0.173985E+09 | 0.00 | 0.599454E+10 | 0.936584E+11 | 0.00 | 0.97 |
Annual Sum or Average | 0.205063E+12 | 0.103847E+11 | 0.00 | 0.176542E+10 | 0.846289E+09 | 0.176716E+11 | 0.656207E+12 | 0.00 | 1.23 |
Minimum of Months | 0.317566E+10 | 0.00 | 0.00 | 69360784.19 | 0.00 | 0.00 | 0.613009E+10 | 0.00 | 0.82 |
Maximum of Months | 0.289091E+11 | 0.387061E+10 | 0.00 | 0.262972E+09 | 0.496934E+09 | 0.694701E+10 | 0.105800E+12 | 0.00 | 1.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.534675E+11 | 0.00 | 0.00 | 8264866.04 | 0.00 | 0.136011E+11 | 0.842723E+10 | 0.00 | 0.97 |
February | 0.459431E+11 | 0.00 | 0.00 | 19284902.97 | 0.00 | 0.729028E+10 | 0.139011E+11 | 0.00 | 1.08 |
March | 0.528288E+11 | 0.00 | 0.00 | 33446674.90 | 0.00 | 0.732516E+09 | 0.226028E+11 | 0.00 | 1.53 |
April | 0.302552E+11 | 10626771.06 | 0.00 | 82639315.24 | 305808.41 | 0.00 | 0.321072E+11 | 0.00 | 1.91 |
May | 0.232837E+11 | 0.241448E+09 | 0.00 | 83550137.21 | 9399513.12 | 0.00 | 0.272958E+11 | 0.00 | 1.88 |
June | 0.114390E+11 | 0.319673E+10 | 0.00 | 65855047.50 | 79310732.86 | 0.00 | 0.116412E+11 | 0.00 | 1.50 |
July | 0.405360E+10 | 0.375706E+10 | 0.00 | 55326959.94 | 0.494097E+09 | 0.00 | 0.545091E+10 | 0.00 | 1.23 |
August | 0.655063E+10 | 0.207145E+10 | 0.00 | 97595473.93 | 0.147345E+09 | 0.00 | 0.123260E+11 | 0.00 | 1.50 |
September | 0.161241E+11 | 0.594402E+09 | 0.00 | 84579962.54 | 26676168.43 | 0.00 | 0.161645E+11 | 0.00 | 1.58 |
October | 0.393636E+11 | 16276533.93 | 0.00 | 56057002.03 | 5796699.06 | 0.514054E+09 | 0.204053E+11 | 0.00 | 1.63 |
November | 0.562045E+11 | 0.00 | 0.00 | 18293058.60 | 0.00 | 0.132504E+10 | 0.159274E+11 | 0.00 | 1.22 |
December | 0.541177E+11 | 0.00 | 0.00 | 7976117.80 | 0.00 | 0.120536E+11 | 0.883330E+10 | 0.00 | 0.86 |
Annual Sum or Average | 0.393631E+12 | 0.988798E+10 | 0.00 | 0.612870E+09 | 0.762930E+09 | 0.355166E+11 | 0.195083E+12 | 0.00 | 1.41 |
Minimum of Months | 0.405360E+10 | 0.00 | 0.00 | 7976117.80 | 0.00 | 0.00 | 0.545091E+10 | 0.00 | 0.86 |
Maximum of Months | 0.562045E+11 | 0.375706E+10 | 0.00 | 97595473.93 | 0.494097E+09 | 0.136011E+11 | 0.321072E+11 | 0.00 | 1.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343840E+10 | 0.00 | 0.00 | 0.49 |
February | 0.272460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222707E+10 | 0.00 | 0.00 | 0.52 |
March | 0.441882E+10 | 0.00 | 0.00 | 155098.40 | 0.00 | 0.906992E+09 | 0.190297E+09 | 0.00 | 0.70 |
April | 0.274374E+10 | 7150.27 | 0.00 | 3259650.32 | 0.00 | 0.196301E+09 | 0.145206E+10 | 0.00 | 0.90 |
May | 0.181440E+10 | 4733036.67 | 0.00 | 6873137.17 | 2781327.20 | 24145878.25 | 0.218755E+10 | 0.00 | 1.01 |
June | 0.728665E+09 | 0.162625E+09 | 0.00 | 9497677.92 | 9743035.94 | 0.00 | 0.136857E+10 | 0.00 | 0.91 |
July | 0.297759E+09 | 0.207114E+09 | 0.00 | 8961643.37 | 43377245.89 | 0.00 | 0.602169E+09 | 0.00 | 0.79 |
August | 0.527308E+09 | 0.106408E+09 | 0.00 | 11300632.00 | 15992769.39 | 0.00 | 0.123422E+10 | 0.00 | 0.93 |
September | 0.122463E+10 | 24409582.46 | 0.00 | 7017060.25 | 1678292.34 | 0.00 | 0.136153E+10 | 0.00 | 0.91 |
October | 0.321921E+10 | 320962.38 | 0.00 | 2070767.34 | 87957.43 | 0.424095E+09 | 0.594981E+09 | 0.00 | 0.77 |
November | 0.381568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147402E+10 | 0.00 | 0.00 | 0.58 |
December | 0.185213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369389E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.255332E+11 | 0.505618E+09 | 0.00 | 49135666.77 | 73660628.18 | 0.123849E+11 | 0.899139E+10 | 0.00 | 0.75 |
Minimum of Months | 0.297759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.441882E+10 | 0.207114E+09 | 0.00 | 11300632.00 | 43377245.89 | 0.369389E+10 | 0.218755E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.373938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251093E+10 | 0.00 | 0.00 | 0.85 |
February | 0.386128E+10 | 0.00 | 0.00 | 285124.64 | 0.00 | 0.136810E+10 | 0.329208E+09 | 0.00 | 0.91 |
March | 0.367029E+10 | 0.00 | 0.00 | 2660065.24 | 0.00 | 0.540707E+09 | 0.231023E+10 | 0.00 | 1.28 |
April | 0.153189E+10 | 9029.00 | 0.00 | 9306976.70 | 0.00 | 63189480.46 | 0.497180E+10 | 0.00 | 1.96 |
May | 0.122986E+10 | 5127049.55 | 0.00 | 13437653.09 | 2995993.45 | 11254779.37 | 0.470557E+10 | 0.00 | 2.16 |
June | 0.654616E+09 | 0.139342E+09 | 0.00 | 13095280.29 | 8779211.76 | 0.00 | 0.211084E+10 | 0.00 | 1.79 |
July | 0.336893E+09 | 0.238682E+09 | 0.00 | 11585121.92 | 31101645.97 | 0.00 | 0.753780E+09 | 0.00 | 1.47 |
August | 0.527984E+09 | 0.108868E+09 | 0.00 | 15702013.38 | 17743870.41 | 0.00 | 0.179854E+10 | 0.00 | 1.85 |
September | 0.113167E+10 | 20071996.21 | 0.00 | 10777420.01 | 1841582.56 | 0.00 | 0.243801E+10 | 0.00 | 1.93 |
October | 0.267510E+10 | 151838.22 | 0.00 | 5235851.36 | 274130.21 | 0.295703E+09 | 0.232278E+10 | 0.00 | 1.50 |
November | 0.467059E+10 | 0.00 | 0.00 | 330005.56 | 0.00 | 0.763601E+09 | 0.535323E+09 | 0.00 | 1.02 |
December | 0.385224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233756E+10 | 0.00 | 0.00 | 0.75 |
Annual Sum or Average | 0.278818E+11 | 0.512252E+09 | 0.00 | 82415512.20 | 62736434.36 | 0.789105E+10 | 0.222761E+11 | 0.00 | 1.46 |
Minimum of Months | 0.336893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 |
Maximum of Months | 0.467059E+10 | 0.238682E+09 | 0.00 | 15702013.38 | 31101645.97 | 0.251093E+10 | 0.497180E+10 | 0.00 | 2.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.264999E+10 | 0.00 | 0.00 | 9575839.79 | 0.00 | 0.140081E+10 | 0.595178E+10 | 0.00 | 0.97 |
February | 0.223442E+10 | 0.00 | 0.00 | 10786649.65 | 0.00 | 0.806440E+09 | 0.647110E+10 | 0.00 | 1.09 |
March | 0.265071E+10 | 0.00 | 0.00 | 10265663.99 | 0.00 | 0.593804E+09 | 0.658714E+10 | 0.00 | 1.35 |
April | 0.207657E+10 | 13312.06 | 0.00 | 10527972.32 | 0.00 | 0.118098E+09 | 0.502804E+10 | 0.00 | 1.55 |
May | 0.204472E+10 | 7337230.25 | 0.00 | 9128526.47 | 3180757.70 | 50924633.64 | 0.305926E+10 | 0.00 | 1.31 |
June | 0.108061E+10 | 0.160541E+09 | 0.00 | 8857673.16 | 11930647.20 | 0.00 | 0.125237E+10 | 0.00 | 0.96 |
July | 0.399230E+09 | 0.232834E+09 | 0.00 | 9149929.92 | 51977647.91 | 0.00 | 0.600569E+09 | 0.00 | 0.87 |
August | 0.617010E+09 | 0.150835E+09 | 0.00 | 16175740.06 | 18544608.66 | 0.00 | 0.163169E+10 | 0.00 | 1.21 |
September | 0.102282E+10 | 52366826.36 | 0.00 | 20457591.33 | 1201021.48 | 0.00 | 0.306988E+10 | 0.00 | 1.60 |
October | 0.157225E+10 | 767148.99 | 0.00 | 23633747.09 | 898.82 | 0.248248E+09 | 0.735376E+10 | 0.00 | 1.80 |
November | 0.212098E+10 | 0.00 | 0.00 | 14192394.51 | 0.00 | 0.512122E+09 | 0.876465E+10 | 0.00 | 1.28 |
December | 0.260823E+10 | 0.00 | 0.00 | 10753151.34 | 0.00 | 0.110492E+10 | 0.690940E+10 | 0.00 | 0.85 |
Annual Sum or Average | 0.210776E+11 | 0.604694E+09 | 0.00 | 0.153505E+09 | 86835581.77 | 0.483537E+10 | 0.566796E+11 | 0.00 | 1.24 |
Minimum of Months | 0.399230E+09 | 0.00 | 0.00 | 8857673.16 | 0.00 | 0.00 | 0.600569E+09 | 0.00 | 0.85 |
Maximum of Months | 0.265071E+10 | 0.232834E+09 | 0.00 | 23633747.09 | 51977647.91 | 0.140081E+10 | 0.876465E+10 | 0.00 | 1.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.405339E+10 | 0.00 | 0.00 | 499230.04 | 0.00 | 0.243635E+10 | 0.644111E+09 | 0.00 | 0.97 |
February | 0.384323E+10 | 0.00 | 0.00 | 1537763.26 | 0.00 | 0.146904E+10 | 0.122628E+10 | 0.00 | 1.09 |
March | 0.486820E+10 | 0.00 | 0.00 | 2876296.47 | 0.00 | 0.709963E+09 | 0.208482E+10 | 0.00 | 1.55 |
April | 0.315703E+10 | 8166.59 | 0.00 | 7817838.27 | 0.00 | 64695971.79 | 0.304573E+10 | 0.00 | 2.05 |
May | 0.263016E+10 | 9468348.46 | 0.00 | 8664006.31 | 2501831.55 | 24957274.40 | 0.256440E+10 | 0.00 | 2.03 |
June | 0.124057E+10 | 0.189237E+09 | 0.00 | 8624695.69 | 9699572.02 | 0.00 | 0.113334E+10 | 0.00 | 1.56 |
July | 0.486116E+09 | 0.219818E+09 | 0.00 | 7705132.94 | 51367806.24 | 0.00 | 0.512370E+09 | 0.00 | 1.29 |
August | 0.755919E+09 | 0.121252E+09 | 0.00 | 11710846.13 | 15941728.84 | 0.00 | 0.125657E+10 | 0.00 | 1.61 |
September | 0.162132E+10 | 29442272.91 | 0.00 | 9475816.78 | 1142439.58 | 0.00 | 0.156603E+10 | 0.00 | 1.73 |
October | 0.365221E+10 | 551905.71 | 0.00 | 5068757.82 | 15102.71 | 0.323410E+09 | 0.183658E+10 | 0.00 | 1.68 |
November | 0.479455E+10 | 0.00 | 0.00 | 1397716.83 | 0.00 | 0.862503E+09 | 0.129106E+10 | 0.00 | 1.20 |
December | 0.397361E+10 | 0.00 | 0.00 | 402463.47 | 0.00 | 0.241051E+10 | 0.664349E+09 | 0.00 | 0.85 |
Annual Sum or Average | 0.350763E+11 | 0.569778E+09 | 0.00 | 65780564.01 | 80668480.94 | 0.830143E+10 | 0.178256E+11 | 0.00 | 1.47 |
Minimum of Months | 0.486116E+09 | 0.00 | 0.00 | 402463.47 | 0.00 | 0.00 | 0.512370E+09 | 0.00 | 0.85 |
Maximum of Months | 0.486820E+10 | 0.219818E+09 | 0.00 | 11710846.13 | 51367806.24 | 0.243635E+10 | 0.304573E+10 | 0.00 | 2.05 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3492080.74 | 0.00 | 0.00 | 0.544389E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7935145.61 | 0.00 | 0.00 | 0.454692E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 14330612.82 | 0.00 | 0.00 | 0.428407E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 17692329.11 | 0.00 | 0.00 | 0.290806E+09 | 0.00 | 0.29 |
May | 0.00 | 467556.14 | 0.00 | 4157433.43 | 0.00 | 0.00 | 0.215430E+09 | 0.00 | 0.29 |
June | 0.00 | 23827148.16 | 0.00 | 5378861.71 | 0.00 | 0.00 | 51685175.12 | 0.00 | 0.30 |
July | 0.00 | 0.136260E+09 | 0.00 | 375349.54 | 0.00 | 0.00 | 381134.27 | 0.00 | 0.28 |
August | 0.00 | 96868988.01 | 0.00 | 2199505.43 | 0.00 | 0.00 | 2399761.06 | 0.00 | 0.30 |
September | 0.00 | 18096275.13 | 0.00 | 2780451.25 | 0.00 | 0.00 | 56726498.39 | 0.00 | 0.29 |
October | 0.00 | 3684313.82 | 0.00 | 7968438.84 | 0.00 | 0.00 | 0.275988E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12994043.81 | 0.00 | 0.00 | 0.425106E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18648556.61 | 0.00 | 0.00 | 0.547326E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.279204E+09 | 0.00 | 97952808.89 | 0.00 | 0.00 | 0.329334E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 375349.54 | 0.00 | 0.00 | 381134.27 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.136260E+09 | 0.00 | 18648556.61 | 0.00 | 0.00 | 0.547326E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28475462.55 | 0.00 | 0.00 | 23070306.13 | 0.00 | 0.00 | 0.542607E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 67104282.83 | 0.00 | 0.00 | 0.455894E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.129183E+09 | 0.00 | 0.00 | 0.429697E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.163898E+09 | 0.00 | 0.00 | 0.291697E+10 | 0.00 | 0.29 |
May | 0.00 | 4201239.63 | 0.00 | 36839714.69 | 0.00 | 0.00 | 0.216350E+10 | 0.00 | 0.29 |
June | 0.00 | 0.236520E+09 | 0.00 | 50471657.15 | 0.00 | 0.00 | 0.521489E+09 | 0.00 | 0.30 |
July | 0.00 | 0.135805E+10 | 0.00 | 3571385.41 | 0.00 | 0.00 | 3725853.80 | 0.00 | 0.28 |
August | 0.00 | 0.996877E+09 | 0.00 | 18240913.02 | 0.00 | 0.00 | 21448691.70 | 0.00 | 0.30 |
September | 0.00 | 0.171181E+09 | 0.00 | 25188359.74 | 0.00 | 0.00 | 0.578931E+09 | 0.00 | 0.29 |
October | 0.00 | 35552453.23 | 0.00 | 71095876.82 | 0.00 | 0.00 | 0.276915E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.115665E+09 | 0.00 | 0.00 | 0.426468E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.165254E+09 | 0.00 | 0.00 | 0.549364E+10 | 0.00 | 0.28 |
Annual Sum or Average | 28475462.55 | 0.280238E+10 | 0.00 | 0.869583E+09 | 0.00 | 0.00 | 0.330155E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3571385.41 | 0.00 | 0.00 | 3725853.80 | 0.00 | 0.28 |
Maximum of Months | 28475462.55 | 0.135805E+10 | 0.00 | 0.165254E+09 | 0.00 | 0.00 | 0.549364E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133069E+09 | 0.00 | 0.00 | 1371639.38 | 0.00 | 0.00 | 0.411071E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5869801.45 | 0.00 | 0.00 | 0.456828E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 12258315.97 | 0.00 | 0.00 | 0.430469E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 16127572.74 | 0.00 | 0.00 | 0.291911E+09 | 0.00 | 0.29 |
May | 0.00 | 422684.78 | 0.00 | 3566163.71 | 0.00 | 0.00 | 0.216705E+09 | 0.00 | 0.29 |
June | 0.00 | 23674858.19 | 0.00 | 5045531.24 | 0.00 | 0.00 | 52275804.46 | 0.00 | 0.30 |
July | 0.00 | 0.135802E+09 | 0.00 | 362925.57 | 0.00 | 0.00 | 380155.31 | 0.00 | 0.28 |
August | 0.00 | 0.100313E+09 | 0.00 | 1774428.40 | 0.00 | 0.00 | 2075635.74 | 0.00 | 0.30 |
September | 0.00 | 17084245.66 | 0.00 | 2461254.56 | 0.00 | 0.00 | 58130585.35 | 0.00 | 0.29 |
October | 0.00 | 3534085.12 | 0.00 | 6696307.88 | 0.00 | 0.00 | 0.277540E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10765891.98 | 0.00 | 0.00 | 0.427373E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 15372112.68 | 0.00 | 0.00 | 0.550559E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.133069E+09 | 0.280830E+09 | 0.00 | 81671945.56 | 0.00 | 0.00 | 0.317532E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 362925.57 | 0.00 | 0.00 | 380155.31 | 0.00 | 0.28 |
Maximum of Months | 0.133069E+09 | 0.135802E+09 | 0.00 | 16127572.74 | 0.00 | 0.00 | 0.550559E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.226892E+09 | 0.00 | 0.00 | 0.153237E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.420373E+09 | 0.00 | 0.00 | 0.128191E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.721052E+09 | 0.00 | 0.00 | 0.124468E+11 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.00 | 0.901634E+09 | 0.00 | 0.00 | 0.112976E+11 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.00 | 0.219825E+09 | 0.00 | 0.00 | 0.737723E+10 | 0.00 | 0.33 |
June | 0.00 | 0.306279E+09 | 0.00 | 0.326343E+09 | 0.00 | 0.00 | 0.220584E+10 | 0.00 | 0.34 |
July | 0.00 | 0.242507E+10 | 0.00 | 51391557.91 | 0.00 | 0.00 | 47659378.44 | 0.00 | 0.31 |
August | 0.00 | 14007744.11 | 0.00 | 0.954058E+09 | 0.00 | 0.00 | 0.331290E+10 | 0.00 | 0.35 |
September | 0.00 | 0.234131E+09 | 0.00 | 0.168612E+09 | 0.00 | 0.00 | 0.204635E+10 | 0.00 | 0.32 |
October | 0.00 | 24350972.36 | 0.00 | 0.425644E+09 | 0.00 | 0.00 | 0.817558E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.658294E+09 | 0.00 | 0.00 | 0.121059E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.954999E+09 | 0.00 | 0.00 | 0.160581E+11 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.300384E+10 | 0.00 | 0.602912E+10 | 0.00 | 0.00 | 0.103217E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 51391557.91 | 0.00 | 0.00 | 47659378.44 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.242507E+10 | 0.00 | 0.954999E+09 | 0.00 | 0.00 | 0.160581E+11 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:03:10
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.485230E+12 | 0.208116E+11 | 0.00 | 0.195992E+13 | 0.653991E+12 |
February | 0.588566E+12 | 0.193650E+11 | 0.00 | 0.183511E+13 | 0.101414E+13 |
March | 0.756976E+12 | 0.187308E+11 | 0.00 | 0.211097E+13 | 0.166240E+13 |
April | 0.925308E+12 | 0.135339E+11 | 0.00 | 0.196700E+13 | 0.240002E+13 |
May | 0.982052E+12 | 0.886275E+10 | 0.00 | 0.160978E+13 | 0.154110E+13 |
June | 0.917612E+12 | 0.412983E+10 | 0.00 | 0.880385E+12 | 0.285834E+13 |
July | 0.941988E+12 | 0.148043E+10 | 0.00 | 0.335876E+12 | 0.358376E+13 |
August | 0.925887E+12 | 0.323412E+10 | 0.00 | 0.702473E+12 | 0.402125E+13 |
September | 0.758320E+12 | 0.560923E+10 | 0.00 | 0.132696E+13 | 0.205908E+13 |
October | 0.629340E+12 | 0.104782E+11 | 0.00 | 0.196919E+13 | 0.176279E+13 |
November | 0.513102E+12 | 0.168307E+11 | 0.00 | 0.214382E+13 | 0.150735E+13 |
December | 0.455522E+12 | 0.190085E+11 | 0.00 | 0.203097E+13 | 0.196004E+13 |
Annual Sum or Average | 0.887990E+13 | 0.142075E+12 | 0.00 | 0.188724E+14 | 0.250243E+14 |
Minimum of Months | 0.455522E+12 | 0.148043E+10 | 0.00 | 0.335876E+12 | 0.653991E+12 |