Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 09:03:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31272.18 | 675.13 | 675.13 |
Net Site Energy | 31272.18 | 675.13 | 675.13 |
Total Source Energy | 93238.73 | 2012.91 | 2012.91 |
Net Source Energy | 93238.73 | 2012.91 | 2012.91 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2036.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3090.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3707.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 671.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1941.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 492.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 908.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3462.52 |
Humidification | 17.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 |
Heat Recovery | 46.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 748.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28487.61 | 2784.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5749.36 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2036.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3090.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3707.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 671.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 492.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 908.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3462.52 |
Humidification | General | 17.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 |
Heat Recovery | General | 46.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 748.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2036.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3090.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3707.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 671.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1941.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 492.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 908.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3462.52 |
Humidification | Unassigned | 17.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 |
Heat Recovery | Unassigned | 46.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 748.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 149.11 | 60.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 371.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 615.01 | 60.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 149.11 | 60.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 371.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 615.01 | 60.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 28487.608 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 28487.608 | 100.00 |
Total On-Site and Utility Electric Sources | 28487.608 | 100.00 |
Total Electricity End Uses | 28487.608 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 174.70 | 5.03 |
Air to Air Heat Recovery for Heating | 3295.27 | 94.97 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3469.97 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5749.36 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5749.36 | 100.00 |
Total Water End Uses | 5749.36 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 107.17 |
Time Setpoint Not Met During Occupied Cooling | 174.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5939.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:03 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.3279 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.3279 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.3279 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.3279 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.0861 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.3279 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.3913 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.3279 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.3279 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 9.3279 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.3279 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.3279 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.3279 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.3279 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 16.0861 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 9.3279 | 18.58 | 484.4232 | |
Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 9.3913 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.8860 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-AUG-14:30 | 21-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 03-AUG-15:39 |
Heating | 0.00 | 2063243.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 543094.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 39494.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 219050.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 69441.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 88758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29972.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2070659.62 | 2093215.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2063243.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 543094.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 316816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5451.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 33930.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 112.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 219050.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 69441.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 88758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 29972.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2207.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9787.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11740.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2126.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6150.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7594.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1559.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2877.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 56.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 148.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 811.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 90220.25 | 3018.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 47.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 211.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 253.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 33.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 62.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1947.74 | 65.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 47.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 211.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 253.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 33.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 62.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1947.74 | 65.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.80 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.500510 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.78 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.486731 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.89 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.07 | 0.313463 | 0.320000 | 1.94 | 0.835902 | 0.500000 | 0.001215 | 0.000217 | 1.94 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 57.01 | 0.333623 | 0.333000 | 18.98 | 0.889660 | 0.500000 | 0.001142 | 0.004519 | 18.98 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.64 | 0.336978 | 0.344000 | 1.94 | 0.898609 | 0.500000 | 0.001131 | 0.000877 | 3.06 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.960884 | 0.248543 | 0.300000 | 0.288265 | 0.662780 | 0.500000 | 0.001533 | 0.000155 | 0.542734 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.16 | 0.133244 | 0.300000 | 0.346520 | 0.355316 | 0.500000 | 0.002859 | 0.000106 | 0.369335 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.38 | 0.172692 | 0.300000 | 0.414887 | 0.460513 | 0.500000 | 0.002206 | 0.000170 | 0.594032 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.43 | 0.107476 | 0.300000 | 0.429600 | 0.300000 | 0.500000 | 0.003545 | 0.000096 | 0.429600 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.01 | 0.265126 | 0.300000 | 2.70 | 0.707004 | 0.500000 | 0.001437 | 0.002415 | 8.45 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 12.15 | 0.126688 | 0.300000 | 3.64 | 0.337835 | 0.500000 | 0.003007 | 0.001584 | 5.54 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 13.62 | 0.175377 | 0.300000 | 4.09 | 0.467673 | 0.500000 | 0.002172 | 0.002415 | 8.45 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.80 | 0.120209 | 0.300000 | 3.84 | 0.320558 | 0.500000 | 0.003169 | 0.001544 | 5.40 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.09 | 0.218401 | 0.300000 | 0.328048 | 0.582404 | 0.500000 | 0.001744 | 0.000312 | 1.09 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.23 | 0.125446 | 0.300000 | 0.368058 | 0.334523 | 0.500000 | 0.003037 | 0.000204 | 0.714592 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.48 | 0.161832 | 0.300000 | 0.442728 | 0.431553 | 0.500000 | 0.002354 | 0.000312 | 1.09 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.36 | 0.113006 | 0.300000 | 0.408577 | 0.301348 | 0.500000 | 0.003372 | 0.000202 | 0.708136 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 24819.80 | 0.000217 | 515.70 |
CORE_MID VAV BOX REHEAT COIL | 516575.98 | 0.004519 | 12663.92 |
CORE_TOP VAV BOX REHEAT COIL | 100197.92 | 0.000877 | 2644.57 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17745.64 | 0.000155 | 468.08 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12074.57 | 0.000106 | 318.48 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 19419.68 | 0.000170 | 512.20 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10967.97 | 0.000096 | 263.28 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 275992.80 | 0.002415 | 7276.65 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 181088.97 | 0.001584 | 4774.40 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 275994.35 | 0.002415 | 7276.69 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 176473.84 | 0.001544 | 4652.78 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 35705.74 | 0.000312 | 941.24 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 23332.92 | 0.000204 | 615.08 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 35706.01 | 0.000312 | 941.25 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23122.21 | 0.000202 | 609.52 |
VAV_BOT WITH REHEAT HEATING COIL | 83192.50 | 0.000728 | 1313.72 |
VAV_MID WITH REHEAT HEATING COIL | 857187.50 | 0.007499 | 13369.89 |
VAV_TOP WITH REHEAT HEATING COIL | 84779.53 | 0.000742 | 1336.03 |
CAV_BAS HEATING COIL | 296555.55 | 0.002594 | 6449.85 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.50 | 3.42 | 11.00 | 3.42 | 9.82 | 9.82 | 0.300000 | 0.348464 | 9.82 |
VAV_MID WITH REHEAT | 52.29 | 33.26 | 104.59 | 42.16 | 91.11 | 91.11 | 0.300000 | 0.462800 | 91.11 |
VAV_TOP WITH REHEAT | 5.40 | 3.49 | 10.80 | 6.67 | 9.83 | 9.83 | 0.300000 | 0.678618 | 9.83 |
CAV_BAS | 5.80 | 5.80 | 5.80 | 5.80 | 5.80 | 5.80 | 1.00 | 1.00 | 5.80 |
AIRLOOP DATACENTER BASEMENT | 21.89 | 21.89 | 21.89 | 21.89 | 21.89 | 21.89 | 1.00 | 0.999990 | 21.89 |
AIRLOOP DATACENTER BOT | 0.500510 | 0.500510 | 0.500510 | 0.500510 | 0.500510 | 0.500510 | 1.00 | 1.00 | 0.500510 |
AIRLOOP DATACENTER MID | 4.78 | 4.78 | 4.78 | 4.78 | 4.78 | 4.78 | 1.00 | 1.00 | 4.78 |
AIRLOOP DATACENTER TOP | 0.486731 | 0.486731 | 0.486731 | 0.486731 | 0.486731 | 0.486731 | 1.00 | 1.00 | 0.486731 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.82 | 2.54 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 91.11 | 25.38 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.83 | 2.54 |
CAV_BAS_OA_CONTROLLER | 5.80 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.89 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.500510 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.78 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.486731 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.70 | 6.67 | 10.91 | 0.010098 | 0.008500 | 220872.80 | 0.009396 | 9.82 |
VAV_MID WITH REHEAT COOLING COIL | 25.87 | 6.67 | 10.90 | 0.010299 | 0.008500 | 2124780.80 | 0.090393 | 91.11 |
VAV_TOP WITH REHEAT COOLING COIL | 25.63 | 6.67 | 10.91 | 0.010102 | 0.008500 | 220434.70 | 0.009378 | 9.83 |
CAV_BAS COOLING COIL | 24.93 | 6.67 | 11.39 | 0.009959 | 0.008500 | 119357.91 | 0.005078 | 5.80 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.82 |
VAV_MID WITH REHEAT FAN | 91.11 |
VAV_TOP WITH REHEAT FAN | 9.83 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.009396 | 0.000051 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000728 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.090393 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.007499 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.009378 | 0.000051 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000742 | |
CAV_BAS_COOLC_CONTROLLER | 0.005078 | 0.000094 |
CAV_BAS_HEATC_CONTROLLER | 0.002594 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.80 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.89 | 434369.89 | 305610.94 | 0.010638 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.500510 | 9810.55 | 6939.21 | 0.000240 |
AIRLOOP DATACENTER MID COOLING COIL | 4.78 | 93907.70 | 66371.16 | 0.002300 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.486731 | 9548.79 | 6750.82 | 0.000234 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.89 | 21.89 | 21.89 | 21.89 | 434369.89 | 434369.89 | 22473.72 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.500510 | 0.500510 | 0.500510 | 0.500510 | 9810.55 | 9810.55 | 1038.19 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.78 | 4.78 | 4.78 | 4.78 | 93907.70 | 93907.70 | 10381.93 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.486731 | 0.486731 | 0.486731 | 0.486731 | 9548.79 | 9548.79 | 1038.19 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.89 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.500510 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.78 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.486731 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.89 | 434369.89 | 0.010638 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.500510 | 9810.55 | 0.000240 |
AIRLOOP DATACENTER MID HEATING COIL | 4.78 | 93907.70 | 0.002300 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.486731 | 9548.79 | 0.000234 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 22473.72 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1038.19 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 10381.93 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1038.19 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000188 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.114245 | 23541.68 | |
HEATSYS1 PUMP | 0.026691 | 8038.13 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.114245 | 13.71 |
HEATSYS1 | 0.026691 | 3.20 |
COOLSYS1_SUPPLY | 0.114245 | 13.71 |
SINGLE WATER PLANT LOOP | 0.013412 | 1.61 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.114245 | 0.114245 | 479543.97 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3050933.49 | 3050933.49 | 0.026691 |
CENTRAL BOILER | 552442.66 | 541642.60 | 0.013412 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.114245 | 16298.70 |
PLANT CIRC PUMP | 0.013412 | 3420.63 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.114245 | 0.057415 | 1352912.80 | 1359303.49 | 0.067267 |
COOLSYS1 CHILLER2 | 0.114245 | 0.057415 | 1352912.80 | 1359303.49 | 0.067267 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013412 | 139666.47 | 58813.21 | 69833.23 | 7879.72 | 21369.07 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.134534 | 16.14 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.134534 | 40518.65 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 53.33 | 1612847.60 | 10.67 | 201605.95 |
TOWERWATERSYS COOLTOWER 2 | 53.33 | 1612847.60 | 10.67 | 201605.95 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.069870 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.328 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 14.170 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.328 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.398 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 16.086 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 231.385 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 9.328 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.751 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 25926.330 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25926.330 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 23283.667 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23283.667 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2923.497 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.497 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2923.561 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2923.561 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1884.012 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1884.012 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 7310.116 | 9.328 | 173.302 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7310.116 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 582.361 | 16.086 | 298.861 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 582.361 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.226 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.149 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.571 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6483 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7026 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4692 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.15847945E-14 | 0.40415870E-16 | -0.13570955E-09 | -0.55776231E-17 |
51 | 8 | 0.19900788E-07 | 0.16227319E-12 | 0.35673126E-03 | -0.22627880E-09 |
52 | 7 | -0.11611995E-01 | 0.86155623E-08 | -0.22179000E-01 | 0.13203260E-03 |
53 | 6 | 0.38824249 | 0.30290701E-05 | 0.45749374 | -0.45461023E-02 |
54 | 5 | -5.0235921 | 0.11413317E-03 | -4.3290265 | 0.61113495E-01 |
55 | 4 | 32.264180 | 0.94131685E-03 | 21.001374 | -0.41231550 |
56 | 3 | -109.65428 | 0.20665218E-02 | -54.756066 | 1.4924847 |
57 | 2 | 195.57288 | 0.11699747E-02 | 77.079281 | -2.8759721 |
58 | 1 | -170.58880 | 0.12564906E-03 | -55.024271 | 2.7354972 |
59 | 0 | 57.057407 | 0.71994484E-06 | 15.597457 | |
60 | 9 | 0.92194319E-15 | 0.45185080E-16 | -0.13934922E-09 | -0.37336789E-17 |
61 | 8 | 0.20414049E-07 | 0.15291409E-12 | 0.36227410E-03 | -0.23211478E-09 |
62 | 7 | -0.11777906E-01 | 0.80689916E-08 | -0.22418053E-01 | 0.13391908E-03 |
63 | 6 | 0.39275134 | 0.28300412E-05 | 0.46134659 | -0.45992504E-02 |
64 | 5 | -5.0676021 | 0.10641223E-03 | -4.3586752 | 0.61659190E-01 |
65 | 4 | 32.458904 | 0.87600040E-03 | 21.117392 | -0.41490080 |
66 | 3 | -110.06874 | 0.19199492E-02 | -54.985491 | 1.4984722 |
67 | 2 | 195.98384 | 0.10853975E-02 | 77.289466 | -2.8824978 |
68 | 1 | -170.74067 | 0.11640795E-03 | -55.084954 | 2.7381589 |
69 | 0 | 57.057407 | 0.66605595E-06 | 15.587079 | |
70 | 9 | 0.99499981E-15 | 0.49201796E-16 | -0.11918706E-09 | -0.33210447E-17 |
71 | 8 | 0.17565796E-07 | 0.20231051E-12 | 0.33086922E-03 | -0.19972915E-09 |
72 | 7 | -0.10835659E-01 | 0.11065463E-07 | -0.21059630E-01 | 0.12320537E-03 |
73 | 6 | 0.36714142 | 0.39371282E-05 | 0.43940598 | -0.42973741E-02 |
74 | 5 | -4.8175888 | 0.14987275E-03 | -4.1895891 | 0.58559222E-01 |
75 | 4 | 31.352470 | 0.12474171E-02 | 20.455190 | -0.40021127 |
76 | 3 | -107.71307 | 0.27606440E-02 | -53.675749 | 1.4644420 |
77 | 2 | 193.64724 | 0.15741070E-02 | 76.090603 | -2.8453956 |
78 | 1 | -169.87685 | 0.17016149E-03 | -54.740743 | 2.7230195 |
79 | 0 | 57.057407 | 0.98204117E-06 | 15.647518 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2400E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2420E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7911E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7927E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5751E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5763E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9650E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9658E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2843E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4140E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.8283E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.9407E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6068E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7007E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9845E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0341E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1346 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.4091E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1537 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4647E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.8675E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1331E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1298E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4495E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2917E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4525E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.8363E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.9829E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6133E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7260E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9850E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0355E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2398E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2421E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7909E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7928E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5750E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5765E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9650E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9657E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6432E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9732E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4912E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8646E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1125E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2391E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3625E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3966E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4776E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7764E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2809E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5844E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5766E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3585E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2472E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5878E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5423E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.6371E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3598E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4292E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0731E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1012E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3626E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3972E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0850E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0869E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7684E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7700E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5572E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5584E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9651E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9658E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1289E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2411E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8048E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8948E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5875E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6550E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9850E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0356E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3920E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9709E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6247E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4957E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6384E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0471E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1298E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4491E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1268E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2399E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8019E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8900E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5824E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6391E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9846E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0341E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0848E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0867E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7683E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7698E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5570E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5581E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9650E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9657E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0325E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1313E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7159E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7873E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6839E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7097E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3627E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3972E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4973E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3722E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0537E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0776E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7731E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0275E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2472E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5878E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1103E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.3504E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8180E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0760E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7206E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8332E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3624E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3966E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1277 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.4294E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1416 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1066 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1037 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.6430E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.7714E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.3115E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2703E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8104E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.0566E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.5924E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.3030E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2664E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8823E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3360E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0324E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8511E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1985E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2492E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2080E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7375E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7714E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3111E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2074E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2809E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.7244E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9266E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.4406E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.8500E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8823E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3360E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1275 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.4418E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1414 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1068 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1037 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.6542E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.7768E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.3160E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.2666E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8138E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.0541E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.5960E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3046E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2720E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8875E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3404E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0271E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8522E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1948E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2502E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2096E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7402E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7768E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3156E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2035E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2834E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.7216E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9290E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.4420E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.8547E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8875E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3404E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 78469.82413 | 78469.82413 | 5.79587 | 5.79587 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 82158.47620 | 82158.47620 | 6.06783 | 6.06783 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 5760.86308 | 5760.86308 | 0.25074 | 1.07782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 772138.11595 | 772138.11595 | 57.01184 | 57.01184 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 330221.01102 | 330221.01102 | 14.31827 | 14.31827 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 76444.60357 | 76444.60357 | 5.64441 | 5.64441 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 70157.42787 | 70157.42787 | 3.06038 | 3.06038 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12892.48929 | 12892.48929 | 0.96088 | 0.96088 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 12424.66515 | 12424.66515 | 0.54273 | 0.54273 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15498.01666 | 15498.01666 | 1.15507 | 1.15507 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 8453.27885 | 8453.27885 | 0.36934 | 0.36934 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 18555.64976 | 18555.64976 | 1.38296 | 1.38296 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.99000 | 1.33664E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 13594.66188 | 13594.66188 | 0.59403 | 0.59403 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19213.85222 | 19213.85222 | 1.43200 | 1.43200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 6758.33022 | 6758.33022 | 0.29499 | 0.29499 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 120852.96510 | 120852.96510 | 9.00780 | 9.00780 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 193183.15848 | 193183.15848 | 8.44937 | 8.44937 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 162989.56458 | 162989.56458 | 12.14836 | 12.14836 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.71200 | 1.33588E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 126754.04094 | 126754.04094 | 5.54413 | 5.54413 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 182704.19647 | 182704.19647 | 13.61782 | 13.61782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 193184.24480 | 193184.24480 | 8.44942 | 8.44942 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 171774.28581 | 171774.28581 | 12.80311 | 12.80311 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 123526.92400 | 123526.92400 | 5.40268 | 5.40268 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13722.16574 | 13722.16574 | 1.02281 | 1.02281 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 24988.94186 | 24988.94186 | 1.09349 | 1.09349 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16459.88717 | 16459.88717 | 1.22686 | 1.22686 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 16329.78864 | 16329.78864 | 0.71459 | 0.71459 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 19799.18849 | 19799.18849 | 1.47576 | 1.47576 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 24989.12899 | 24989.12899 | 1.09350 | 1.09350 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18271.97980 | 18271.97980 | 1.36192 | 1.36192 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 16182.41437 | 16182.41437 | 0.70814 | 0.70814 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8514.66012 | 8514.66012 | 0.50051 | 0.50051 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 81387.57437 | 81387.57437 | 4.78416 | 4.78416 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8280.22244 | 8280.22244 | 0.48673 | 0.48673 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372464.60839 | 372464.60839 | 21.89397 | 21.89397 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 21.83700 | 1.33520E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 14:00:00 | -16.30000 | 9.24091E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 143245.79 | 9.81730 | 9.81730 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 87114.41 | 2.87892 | 2.87892 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:50:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1316621.69 | 91.10594 | 91.10594 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 863621.42 | 42.16386 | 42.16386 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 148534.65 | 9.82895 | 9.82895 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 86792.88 | 6.67010 | 6.67010 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
7 | CAV_BAS | Cooling | Sensible | 76423.52 | 5.79587 | 5.79587 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 79706.12 | 1.20016 | 1.20016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 367556.93 | 21.89418 | 21.89418 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 22473.72 | 0.33839 | 0.33839 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8375.54 | 0.50051 | 0.50051 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1038.19 | 1.56323E-002 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 80049.85 | 4.78416 | 4.78416 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 10381.93 | 0.15632 | 0.15632 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8146.18 | 0.48673 | 0.48673 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1038.19 | 1.56323E-002 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.79587 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.06783 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31346 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.94171 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83590 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21545E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.17134E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.94171 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24819.80103 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17134E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 515.69515 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 57.01184 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33362 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33300 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.98494 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88966 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14201E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.51923E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.98494 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 516575.98056 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.51923E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12663.91609 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.64441 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33698 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34400 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.94168 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89861 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13064E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.76575E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.06038 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 100197.92464 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.76575E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2644.56550 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96088 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24854 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28827 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66278 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53294E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55247E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54273 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17745.63771 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55247E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 468.08217 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15507 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13324 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34652 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35532 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.85942E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05634E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36934 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12074.57041 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05634E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 318.47671 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38296 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17269 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41489 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46051 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20624E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69892E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59403 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19419.68259 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69892E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 512.20005 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43200 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10748 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42960 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.54499E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.59526E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42960 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10967.96866 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.59526E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 263.27783 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.00780 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26513 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.70234 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70700 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43705E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.41451E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.44937 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 275992.79891 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.41451E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7276.64557 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.14836 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12669 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.64451 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33783 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.00739E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.58425E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.54413 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 181088.97489 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58425E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4774.39976 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.61782 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17538 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.08535 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46767 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.17246E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.41452E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.44942 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 275994.34873 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.41452E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7276.68653 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.80311 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12021 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.84093 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32056 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16948E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54387E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.40268 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 176473.84439 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54387E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4652.78167 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.09349 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21840 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32805 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58240 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.74449E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.12369E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.09349 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35705.73848 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.12369E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 941.24377 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.22686 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12545 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36806 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33452 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.03716E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.04127E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71459 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23332.92433 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.04127E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 615.07569 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.47576 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16183 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.44273 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43155 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35429E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.12372E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.09350 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35706.00577 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.12372E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 941.25082 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.36192 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11301 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40858 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30135 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.37152E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.02283E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.70814 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23122.20627 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.02283E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 609.52182 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.50051 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.78416 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48673 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.89397 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.49937 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.42098 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.99874 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.42098 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.81730 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.81730 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34846 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 52.29447 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 33.25807 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 104.58893 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 42.16386 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 91.10594 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 91.10594 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46280 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.40123 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.48909 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.80245 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 6.67010 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.82895 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.82895 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.67862 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.79587 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.79587 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.79587 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.79587 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.79587 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.79587 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.89397 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.89397 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.89397 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.89397 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.89418 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.89418 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.50051 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.50051 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.50051 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.50051 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.50051 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.50051 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.78416 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.78416 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.78416 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.78416 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.78416 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.78416 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48673 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48673 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48673 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48673 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48673 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.48673 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.81730 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 91.10594 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.82895 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.79587 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.89418 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.50051 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.78416 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.48673 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.81730 |
289 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
290 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.69729 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90959 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.00977E-002 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 220872.80094 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.39644E-003 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.81730 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 83192.50405 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.27804E-004 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1313.72167 |
302 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.81730 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.39644E-003 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.06778E-005 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.27804E-004 |
306 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 91.10594 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 25.38195 |
308 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.87147 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90019 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.02993E-002 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2124780.80497 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.03931E-002 |
316 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 91.10594 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 857187.49867 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.49905E-003 |
319 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 13369.89040 |
320 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 91.10594 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.03931E-002 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.26800E-006 |
323 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.49905E-003 |
324 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.82895 |
325 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53819 |
326 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.62764 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90961 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.01019E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 220434.69672 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.37780E-003 |
334 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.82895 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 84779.53066 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.41688E-004 |
337 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1336.02751 |
338 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.82895 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.37780E-003 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.07785E-005 |
341 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.41688E-004 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.79587 |
343 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.93432 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.38853 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.95925E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 119357.90924 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.07776E-003 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.79587 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 296555.54797 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.59440E-003 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6449.85176 |
355 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.79587 |
356 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.07776E-003 |
357 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.37796E-005 |
358 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.59440E-003 |
359 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.89418 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.89418 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 434369.88743 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 305610.94005 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06377E-002 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.89418 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.89418 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.89418 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.89418 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 434369.88743 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 434369.88743 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 22473.71574 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
373 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.89418 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.89418 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 434369.88743 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06377E-002 |
377 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 22473.71574 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.87550E-004 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
381 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
382 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.50051 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50051 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9810.55138 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6939.21246 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.40260E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.50051 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.50051 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.50051 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.50051 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9810.55138 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9810.55138 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1038.19256 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.50051 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50051 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9810.55138 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.40260E-004 |
400 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1038.19256 |
401 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.78416 |
402 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.78416 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 93907.70095 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 66371.15506 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29979E-003 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.78416 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.78416 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.78416 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.78416 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 93907.70095 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 93907.70095 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 10381.92564 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
415 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.78416 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.78416 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 93907.70095 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29979E-003 |
419 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 10381.92564 |
420 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48673 |
421 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48673 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9548.79200 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6750.81947 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.33849E-004 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48673 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48673 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48673 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48673 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9548.79200 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9548.79200 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1038.19256 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
434 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48673 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48673 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9548.79200 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.33849E-004 |
438 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1038.19256 |
439 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.11425 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 23541.67868 |
441 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.11425 |
442 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 13.70941 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.11425 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.11425 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 479543.96641 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
447 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.66909E-002 |
448 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.20291 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.66909E-002 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 8038.12608 |
451 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3050933.48870 |
453 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3050933.49000 |
454 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.66909E-002 |
455 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.11425 |
456 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 13.70941 |
457 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.11425 |
458 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 16298.69827 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11425 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.74150E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1352912.80270 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1359303.48500 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.72669E-002 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11425 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.74150E-002 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1352912.80270 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1359303.48500 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.72669E-002 |
469 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.34116E-002 |
470 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.60939 |
471 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.34116E-002 |
472 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3420.62695 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.34116E-002 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 58813.20583 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21369.06580 |
479 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 552442.66209 |
480 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 541642.60000 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.34116E-002 |
482 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
483 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
484 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
486 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.13453 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 16.14405 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.13453 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 40518.64751 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 53.33267 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1612847.59882 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.66653 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 201605.94985 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 53.33267 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1612847.59882 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.66653 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 201605.94985 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.98700E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.98700E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 23531.23 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 489312.24 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 94948.85 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16814.08 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11440.60 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18399.98 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10390.59 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 261482.37 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 171567.66 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 261483.84 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 167195.58 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 33827.48 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22105.48 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 33827.74 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21905.85 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 58656.68 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 587848.65 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 59503.95 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 228589.98 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 252587.08 | 171278.18 | 81308.90 | 0.68 | 26748.21 | 271.30 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2379017.48 | 1605543.14 | 773474.34 | 0.67 | 252113.46 | 2557.07 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 252614.09 | 171360.78 | 81253.32 | 0.68 | 26761.07 | 271.43 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 141584.90 | 97492.94 | 44091.96 | 0.69 | 14648.64 | 148.57 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 7.0797311243E-004 | 1.2648450649E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 1.6021567228E-003 | 1.9606153822E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.4382644115E-002 | 2.4566794332E-002 | Pass | Pass | 0.4878004230 | 0.4943850913 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.0257197952E-002 | 2.3735262655E-002 | Pass | Pass | 11.6887696001 | 35.2507646316 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.8383895743E-002 | 1.2881835898E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.8379428516E-002 | 1.2709490579E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.0131921176E-002 | 1.4120127677E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.9852328080E-002 | 1.3850985189E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2715488830 | 0.2598987486 | Pass | Pass | 13.8164500726 | 45.2909589776 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2746969411 | 0.2648002815 | Pass | Pass | 7.8101866640 | 25.3816148615 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2422499882 | 0.2406283211 | Pass | Pass | 11.5552279550 | 38.8093430797 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1655622931 | 0.1750077748 | Pass | Pass | 9.4948377912 | 34.4786635305 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4456688242 | 0.4268209075 | Pass | Pass | 18.7038220549 | 71.7117157101 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4635561100 | 0.4432788798 | Pass | Pass | 13.2357079129 | 45.8565206664 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4231638330 | 0.4100572634 | Pass | Pass | 18.9920693384 | 66.1776104276 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3595533164 | 0.3536924942 | Pass | Pass | 11.5205174741 | 54.5954783317 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.5542272008E-003 | 5.1927284563E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.6671071638E-002 | 2.8378473774E-002 | Pass | Pass | 0.4976308047 | 0.4651949699 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1347274959 | 9.0065061151E-002 | Pass | Pass | 0.4958511505 | 0.4767684139 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.6355188114E-007 | 6.3817158103E-007 | Pass | Pass | 3.0261035647E-003 | 2.2308659823E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.4135765367E-003 | 3.1470461925E-003 | Pass | Pass | 1.5064529828E-003 | 1.2621956509E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.4491554982E-003 | 5.3033037767E-003 | Pass | Pass | 2.7276525755E-003 | 2.0001481951E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.3148856518E-006 | 8.5835147985E-006 | Pass | Pass | 3.4327673091E-005 | 1.0990216975E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6972.43 | 306.47 | 0.00 | 20468.81 | 19188.70 | 46936.41 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 1043.06 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.171 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.3279 | 2779.43 | 25926.33 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 240.45 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.3279 | 24961.20 | 232836.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 2159.39 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.3279 | 2496.12 | 23283.67 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 215.94 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.04 | 0.0000 | Y | 18.68 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.98 | 0.0000 | Y | 12.02 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.85 | 0.0000 | Y | 18.58 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.95 | 0.0000 | Y | 12.01 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.3279 | 3134.13 | 29234.97 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.08 | 0.0000 | Y | 187.01 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.99 | 0.0000 | Y | 120.21 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.3279 | 3134.20 | 29235.61 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.88 | 0.0000 | Y | 185.94 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.3279 | 2019.75 | 18840.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.97 | 0.0000 | Y | 120.12 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.3279 | 313.41 | 2923.50 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 34.08 | 0.0000 | Y | 18.70 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.99 | 0.0000 | Y | 12.02 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.3279 | 313.42 | 2923.56 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.88 | 0.0000 | Y | 18.59 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.3279 | 201.98 | 1884.01 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 33.97 | 0.0000 | Y | 12.01 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 9.3279 | 783.68 | 7310.12 | LightsWired | LTG_SCH_OFFICE | 50.72 | 168.00 | 49.41 | 0.0000 | Y | 67.80 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 16.0861 | 362.03 | 5823.61 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 59.65 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 16.0861 | 36.20 | 582.36 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.97 |
Interior Lighting Total | 9.3913 | 46320.38 | 435009.77 | 1157.90 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.56 | 1127.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.56 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2923.50 | 1127.59 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2923.50 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1884.01 | 726.66 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1884.01 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.01 | AstronomicalClock | - | 42.04 | 42.04 | 78.71 | |
EXTERIOR_LIGHTS_B | 44362.79 | AstronomicalClock | - | 83.67 | 71.18 | 592.75 | |
Exterior Lighting Total | 54335.80 | 671.46 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2679270.48 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3050933.49 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1359303.49 | 6.28 | 1301036.01 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1359303.49 | 6.28 | 1301036.01 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 541642.60 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1612847.60 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1612847.60 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 220872.80 | 252587.08 | 171278.18 | 81308.90 | 0.68 | - | 26748.21 | 271.30 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2124780.80 | 2379017.48 | 1605543.14 | 773474.34 | 0.67 | - | 252113.46 | 2557.07 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 220434.70 | 252614.09 | 171360.78 | 81253.32 | 0.68 | - | 26761.07 | 271.43 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 119357.91 | 141584.90 | 97492.94 | 44091.96 | 0.69 | - | 14648.64 | 148.57 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 434369.89 | 305610.94 | 128758.95 | 0.70 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9810.55 | 6939.21 | 2871.34 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 93907.70 | 66371.16 | 27536.55 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9548.79 | 6750.82 | 2797.97 | 0.71 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 24819.80 | 23531.23 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 516575.98 | 489312.24 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 100197.92 | 94948.85 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17745.64 | 16814.08 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12074.57 | 11440.60 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19419.68 | 18399.98 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10967.97 | 10390.59 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 275992.80 | 261482.37 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 181088.97 | 171567.66 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 275994.35 | 261483.84 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 176473.84 | 167195.58 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 35705.74 | 33827.48 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 23332.92 | 22105.48 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 35706.01 | 33827.74 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 23122.21 | 21905.85 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 83192.50 | 58656.68 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 857187.50 | 587848.65 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 84779.53 | 59503.95 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 296555.55 | 228589.98 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 434369.89 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9810.55 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 93907.70 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9548.79 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 22473.72 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1038.19 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 10381.93 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1038.19 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.82 | 22300.92 | 2271.59 | 1.00 | 1.12 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 91.11 | 208061.18 | 2283.73 | 1.00 | 1.07 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.83 | 22327.38 | 2271.59 | 1.00 | 1.12 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.80 | 9827.79 | 1695.65 | 1.00 | 1.16 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 21.89 | 36108.90 | 1649.25 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 560.63 | 1120.11 | 1.00 | 1.61 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.78 | 5358.78 | 1120.11 | 1.00 | 1.16 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 545.19 | 1120.11 | 1.00 | 1.62 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.114245 | 23541.68 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.026691 | 8038.13 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.114245 | 16298.70 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013412 | 3420.63 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.134534 | 40518.65 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 78469.82 | 78469.82 | 28.23 | 5.796 | 5.796 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 23.42 | 0.01335 | 1.200 | 0.00 |
CORE_BOTTOM | 82158.48 | 82158.48 | 32.91 | 6.068 | 6.068 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 23.42 | 0.01335 | 1.078 | 0.00 |
CORE_MID | 772138.12 | 772138.12 | 309.34 | 57.012 | 57.012 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 23.42 | 0.01335 | 10.778 | 0.00 |
CORE_TOP | 76444.60 | 76444.60 | 30.63 | 5.644 | 5.644 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 23.42 | 0.01335 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12892.49 | 12892.49 | 41.14 | 0.961 | 0.961 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00894 | 30.30 | 0.01337 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15498.02 | 15498.02 | 76.73 | 1.155 | 1.155 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00875 | 25.18 | 0.01336 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 18555.65 | 18555.65 | 59.20 | 1.383 | 1.383 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00881 | 29.99 | 0.01337 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19213.85 | 19213.85 | 95.13 | 1.432 | 1.432 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00870 | 28.84 | 0.01336 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 120852.97 | 120852.97 | 385.60 | 9.008 | 9.008 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00917 | 30.30 | 0.01337 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 162989.56 | 162989.56 | 806.98 | 12.148 | 12.148 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00884 | 25.71 | 0.01336 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 182704.20 | 182704.20 | 582.94 | 13.618 | 13.618 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00895 | 30.07 | 0.01337 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 171774.29 | 171774.29 | 850.47 | 12.803 | 12.803 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00882 | 28.84 | 0.01336 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13722.17 | 13722.17 | 43.78 | 1.023 | 1.023 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00916 | 30.30 | 0.01337 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16459.89 | 16459.89 | 81.49 | 1.227 | 1.227 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00888 | 25.98 | 0.01336 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 19799.19 | 19799.19 | 63.17 | 1.476 | 1.476 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00897 | 30.22 | 0.01337 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18271.98 | 18271.98 | 90.47 | 1.362 | 1.362 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00884 | 28.84 | 0.01336 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8514.66 | 8514.66 | 235.19 | 0.501 | 0.501 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 26.50 | 0.01336 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 81387.57 | 81387.57 | 2248.11 | 4.784 | 4.784 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 26.50 | 0.01336 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8280.22 | 8280.22 | 228.72 | 0.487 | 0.487 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.00 | 27.00 | 0.00859 | 26.67 | 0.01336 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372464.61 | 372464.61 | 475.28 | 21.894 | 21.894 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 21.84 | 0.01335 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.96 | 0.00092 | -16.30 | 0.00092 | 1.200 | 0.00 |
CORE_BOTTOM | 5760.86 | 5760.86 | 2.31 | 0.251 | 1.078 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -16.30 | 0.00092 | 1.078 | 0.00 |
CORE_MID | 330221.01 | 330221.01 | 132.29 | 14.318 | 14.318 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 10.778 | 0.00 |
CORE_TOP | 70157.43 | 70157.43 | 28.11 | 3.060 | 3.060 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12424.67 | 12424.67 | 39.64 | 0.543 | 0.543 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 8453.28 | 8453.28 | 41.85 | 0.369 | 0.369 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 13594.66 | 13594.66 | 43.38 | 0.594 | 0.594 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 6758.33 | 6758.33 | 33.46 | 0.295 | 0.295 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00724 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 193183.16 | 193183.16 | 616.39 | 8.449 | 8.449 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00737 | -16.30 | 0.00092 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 126754.04 | 126754.04 | 627.57 | 5.544 | 5.544 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00736 | -16.30 | 0.00092 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 193184.24 | 193184.24 | 616.38 | 8.449 | 8.449 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00737 | -16.30 | 0.00092 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 123526.92 | 123526.92 | 611.59 | 5.403 | 5.403 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00734 | -16.30 | 0.00092 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 24988.94 | 24988.94 | 79.73 | 1.093 | 1.093 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00739 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16329.79 | 16329.79 | 80.85 | 0.715 | 0.715 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00738 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 24989.13 | 24989.13 | 79.73 | 1.094 | 1.094 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00739 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16182.41 | 16182.41 | 80.12 | 0.708 | 0.708 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00738 | -16.30 | 0.00092 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.72 | 0.00248 | -16.30 | 0.00092 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.51 | 0.00148 | -16.30 | 0.00092 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 20.39 | 0.00148 | -16.30 | 0.00092 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 14:00:00 | 18.00 | 27.00 | 0.00850 | -16.30 | 0.00092 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.82 | 9.82 | 2.88 | 2.88 | 9.8173 | 3.4210 | 9.8173 | 0.3485 | 0.3000 |
VAV_MID WITH REHEAT | 91.11 | 91.11 | 42.16 | 42.16 | 91.1059 | 42.1639 | 91.1059 | 0.4628 | 0.3000 |
VAV_TOP WITH REHEAT | 9.83 | 9.83 | 6.67 | 6.67 | 9.8290 | 6.6701 | 9.8290 | 0.6786 | 0.3000 |
CAV_BAS | 5.80 | 5.80 | 1.20 | 1.20 | 5.7959 | 5.7959 | 5.7959 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.89 | 21.89 | 0.34 | 0.34 | 21.8942 | 21.8940 | 21.8942 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.50 | 0.50 | 0.02 | 0.02 | 0.5005 | 0.5005 | 0.5005 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.78 | 4.78 | 0.16 | 0.16 | 4.7842 | 4.7842 | 4.7842 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.49 | 0.49 | 0.02 | 0.02 | 0.4867 | 0.4867 | 0.4867 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 24819.801 | 24819.801 | 1.941707 | 0.00021713 | 515.695 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24819.80 | 24819.80 | 1.941707 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00797931 | 50.2898 | 5760.86 | 0.00 | 24909.95 | 24909.95 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 516575.981 | 516575.981 | 18.984943 | 0.00451923 | 12663.916 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 516575.98 | 516575.98 | 18.984943 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 330221.01 | 0.00 | 518204.88 | 518204.88 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 100197.925 | 100197.925 | 3.060381 | 0.00087658 | 2644.565 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 100197.92 | 100197.92 | 3.060381 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 70157.43 | 0.00 | 100541.64 | 100541.64 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17745.638 | 17745.638 | 0.542734 | 0.00015525 | 468.082 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17745.64 | 17745.64 | 0.542734 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00747330 | 47.1446 | 12424.67 | 0.00 | 17804.46 | 17804.46 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12074.570 | 12074.570 | 0.369335 | 0.00010563 | 318.477 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12074.57 | 12074.57 | 0.369335 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00751367 | 47.3958 | 8453.28 | 0.00 | 12114.46 | 12114.46 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 19419.683 | 19419.683 | 0.594032 | 0.00016989 | 512.200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19419.68 | 19419.68 | 0.594032 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00755961 | 47.6817 | 13594.66 | 0.00 | 19483.77 | 19483.77 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10967.969 | 10967.969 | 0.429600 | 0.00009595 | 263.278 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10967.97 | 10967.97 | 0.429600 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00723928 | 45.6873 | 6758.33 | 0.00 | 11003.54 | 11003.54 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 275992.799 | 275992.799 | 8.449368 | 0.00241451 | 7276.646 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 275992.80 | 275992.80 | 8.449368 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00736770 | 46.4896 | 193183.16 | 0.00 | 276883.78 | 276883.78 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 181088.975 | 181088.975 | 5.544127 | 0.00158425 | 4774.400 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 181088.97 | 181088.97 | 5.544127 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00735915 | 46.4365 | 126754.04 | 0.00 | 181673.05 | 181673.05 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 275994.349 | 275994.349 | 8.449416 | 0.00241452 | 7276.687 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 275994.35 | 275994.35 | 8.449416 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00736770 | 46.4896 | 193184.24 | 0.00 | 276885.34 | 276885.34 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 176473.844 | 176473.844 | 5.402681 | 0.00154387 | 4652.782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 176473.84 | 176473.84 | 5.402681 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00734300 | 46.3359 | 123526.92 | 0.00 | 177043.46 | 177043.46 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 35705.738 | 35705.738 | 1.093494 | 0.00031237 | 941.244 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35705.74 | 35604.36 | 1.093494 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00739472 | 46.6597 | 24988.94 | 0.00 | 35819.92 | 35819.92 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 23332.924 | 23332.924 | 0.714592 | 0.00020413 | 615.076 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23332.92 | 23332.92 | 0.714592 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00738354 | 46.5903 | 16329.79 | 0.00 | 23407.49 | 23407.49 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 35706.006 | 35706.006 | 1.093502 | 0.00031237 | 941.251 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35706.01 | 35706.01 | 1.093502 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00739472 | 46.6597 | 24989.13 | 0.00 | 35820.19 | 35820.19 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 23122.206 | 23122.206 | 0.708136 | 0.00020228 | 609.522 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23122.21 | 23122.21 | 0.708136 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00737867 | 46.5600 | 16182.41 | 0.00 | 23196.11 | 23196.11 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 220872.801 | -999.000 | 9.817302 | 0.00939644 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 220872.80 | 173167.94 | 9.817302 | 25.70 | 18.02 | 0.01009771 | 10.91 | 10.91 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 25.8543 | 24.00 | 0.00889112 | 46.6348 | 126332.00 | 0.00 | 224795.23 | 167334.71 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 83192.504 | 83192.504 | 2.945191 | 0.00072780 | 1313.722 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 83192.50 | 83192.50 | 2.945191 | -11.15 | -11.15 | 0.00186018 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 86.1808 | 21.00 | 0.00752983 | 47.4951 | 36560.89 | 0.00 | 70919.38 | 70919.38 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2124780.805 | -999.000 | 91.105944 | 0.09039309 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2124780.80 | 1626199.72 | 91.105944 | 25.87 | 18.24 | 0.01029929 | 10.90 | 10.90 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 27.8598 | 24.00 | 0.00900168 | 47.2074 | 1145653.56 | 0.00 | 2160990.44 | 1575120.95 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 857187.499 | 857187.499 | 27.331783 | 0.00749905 | 13369.890 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 857187.50 | 857187.50 | 27.331783 | -13.79 | -13.79 | 0.00138078 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 92.8661 | 19.29 | 0.00700352 | 49.1347 | 471600.12 | 0.00 | 710530.21 | 710530.21 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 220434.697 | -999.000 | 9.828951 | 0.00937780 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 220434.70 | 172548.50 | 9.828951 | 25.63 | 18.00 | 0.01010188 | 10.91 | 10.91 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 25.8236 | 24.00 | 0.00896317 | 47.0085 | 131702.62 | 0.00 | 224356.62 | 166728.61 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 84779.531 | 84779.531 | 2.948685 | 0.00074169 | 1336.028 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 84779.53 | 84779.53 | 2.948685 | -11.57 | -11.57 | 0.00180418 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 86.0787 | 17.37 | 0.00695340 | 55.0542 | 53845.68 | 0.00 | 71940.92 | 71940.92 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 119357.909 | -999.000 | 5.795869 | 0.00507776 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 119357.91 | 94320.20 | 5.795869 | 24.93 | 17.66 | 0.00995925 | 11.39 | 11.29 | 0.00850000 | 28.16 | 0.01336316 | 21.21 | 20.7071 | 24.00 | 0.00897223 | 47.0538 | 77431.14 | 0.00 | 121531.74 | 91548.98 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 296555.548 | 296555.548 | 5.795869 | 0.00259440 | 6449.852 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 296555.55 | 296555.55 | 5.795869 | -3.38 | -6.86 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.7071 | 23.06 | 0.00092409 | 5.1951 | 0.00 | 0.00 | 241290.97 | 241290.97 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 434369.887 | 305610.940 | 21.894177 | 0.01063769 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 403506.61 | 396786.04 | -999.0 | 28.48 | 17.76 | 0.00861685 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | -999.0000 | 27.00 | 0.00854219 | 37.5158 | 371990.75 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9810.551 | 6939.212 | 0.500510 | 0.00024026 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 9094.09 | 8786.83 | -999.0 | 27.96 | 17.68 | 0.00873408 | 12.80 | 11.87 | 0.00850000 | 26.67 | 0.01336053 | 20.77 | -999.0000 | 27.00 | 0.00858490 | 37.6984 | 8513.18 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93907.701 | 66371.155 | 4.784164 | 0.00229979 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 87069.72 | 83998.25 | -999.0 | 27.96 | 17.69 | 0.00874477 | 12.80 | 11.87 | 0.00850000 | 26.67 | 0.01336053 | 20.77 | -999.0000 | 27.00 | 0.00858881 | 37.7155 | 81368.07 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9548.792 | 6750.819 | 0.486731 | 0.00023385 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8852.70 | 8545.48 | -999.0 | 27.96 | 17.68 | 0.00874066 | 12.80 | 11.87 | 0.00850000 | 26.67 | 0.01336053 | 20.77 | -999.0000 | 27.00 | 0.00858736 | 37.7091 | 8280.22 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 434369.887 | 434369.887 | 21.894177 | 0.01063769 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 434369.89 | 434369.89 | 21.894177 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 1.5456 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9810.551 | 9810.551 | 0.500510 | 0.00024026 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9810.55 | 9810.55 | 0.500510 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.1233 | 25.44 | 0.00247647 | 12.0381 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93907.701 | 93907.701 | 4.784164 | 0.00229979 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 93907.70 | 93907.70 | 4.784164 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.2675 | 23.72 | 0.00148430 | 8.0131 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9548.792 | 9548.792 | 0.486731 | 0.00023385 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9548.79 | 9548.79 | 0.486731 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.2117 | 22.47 | 0.00148387 | 8.6361 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 22473.716 | 22473.716 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 22473.72 | 22473.72 | 21.894177 | -0.25 | -0.25 | 0.00838291 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 1.5456 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1038.19 | 1038.19 | 0.500510 | -0.51 | -2.51 | 0.00242798 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.1233 | 25.44 | 0.00247647 | 12.0381 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 10381.926 | 10381.926 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10381.93 | 10381.93 | 4.784164 | -0.53 | -4.11 | 0.00146599 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.2675 | 23.72 | 0.00148430 | 8.0131 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1038.19 | 1038.19 | 0.486731 | -0.52 | -4.11 | 0.00146590 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.2117 | 22.47 | 0.00148387 | 8.6361 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 24819.801 | 24819.801 | 1.941707 | 0.00021713 | 515.695 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 0.7975 | 0.813515 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24819.80 | 24819.80 | 1.0000 | 2.27941863 | 1.941707 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.21711230 | 60.00 | 32.22 | 27.78 | 0.000 | 24819.80 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.86 | 0.00797931 | 21.00 | 0.00797931 | 50.2898 | 5760.86 | 0.00 | 24909.95 | 24909.95 | 2.27941863 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.52 | 15.78 | 0.00800000 | 43988.0 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 516575.981 | 516575.981 | 18.984943 | 0.00451923 | 12663.916 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 16.5977 | 16.931735 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 516575.98 | 516575.98 | 1.0000 | 22.28690524 | 18.984943 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 4.51877102 | 60.00 | 32.22 | 27.78 | 0.000 | 516575.98 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 330221.01 | 0.00 | 518204.88 | 518204.88 | 22.28690524 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.60 | 19.85 | 0.00800000 | 56311.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 100197.925 | 100197.925 | 3.060381 | 0.00087658 | 2644.565 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 3.2194 | 3.284173 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 100197.92 | 100197.92 | 1.0000 | 3.59265817 | 3.060381 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.87648574 | 60.00 | 32.22 | 27.78 | 0.000 | 100197.92 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 70157.43 | 0.00 | 100541.64 | 100541.64 | 3.59265817 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61045.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17745.638 | 17745.638 | 0.542734 | 0.00015525 | 468.082 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 0.5702 | 0.581646 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17745.64 | 17745.64 | 1.0000 | 0.63712935 | 0.542734 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.15523074 | 60.00 | 32.22 | 27.78 | 0.000 | 17745.64 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00747330 | 21.00 | 0.00747330 | 47.1446 | 12424.67 | 0.00 | 17804.46 | 17804.46 | 0.63712935 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61004.6 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12074.570 | 12074.570 | 0.369335 | 0.00010563 | 318.477 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 0.3880 | 0.395766 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12074.57 | 12074.57 | 1.0000 | 0.43357201 | 0.369335 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.10562283 | 60.00 | 32.22 | 27.78 | 0.000 | 12074.57 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751367 | 21.00 | 0.00751367 | 47.3958 | 8453.28 | 0.00 | 12114.46 | 12114.46 | 0.43357201 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19419.683 | 19419.683 | 0.594032 | 0.00016989 | 512.200 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 0.6240 | 0.636516 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19419.68 | 19419.68 | 1.0000 | 0.69734915 | 0.594032 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.16987452 | 60.00 | 32.22 | 27.78 | 0.000 | 19419.68 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00755961 | 21.00 | 0.00755961 | 47.6817 | 13594.66 | 0.00 | 19483.77 | 19483.77 | 0.69734915 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60999.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10967.969 | 10967.969 | 0.429600 | 0.00009595 | 263.278 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 0.3524 | 0.359496 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10967.97 | 10967.97 | 1.0000 | 0.50431829 | 0.429600 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.09594279 | 60.00 | 32.22 | 27.78 | 0.000 | 10967.97 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.90 | 0.00723928 | 21.00 | 0.00723928 | 45.6873 | 6758.33 | 0.00 | 11003.54 | 11003.54 | 0.50431829 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.20 | 19.40 | 0.00800000 | 54878.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 275992.799 | 275992.799 | 8.449368 | 0.00241451 | 7276.646 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 8.8677 | 9.046176 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 275992.80 | 275992.80 | 1.0000 | 9.91892735 | 8.449368 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.41425910 | 60.00 | 32.22 | 27.78 | 0.000 | 275992.80 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00736770 | 21.00 | 0.00736770 | 46.4896 | 193183.16 | 0.00 | 276883.78 | 276883.78 | 9.91892735 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60974.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 181088.975 | 181088.975 | 5.544127 | 0.00158425 | 4774.400 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 5.8184 | 5.935527 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 181088.97 | 181088.97 | 1.0000 | 6.50839105 | 5.544127 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.58408374 | 60.00 | 32.22 | 27.78 | 0.000 | 181088.97 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00735915 | 21.00 | 0.00735915 | 46.4365 | 126754.04 | 0.00 | 181673.05 | 181673.05 | 6.50839105 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.5 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 275994.349 | 275994.349 | 8.449416 | 0.00241452 | 7276.687 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 8.8678 | 9.046226 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 275994.35 | 275994.35 | 1.0000 | 9.91898276 | 8.449416 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.41427266 | 60.00 | 32.22 | 27.78 | 0.000 | 275994.35 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00736770 | 21.00 | 0.00736770 | 46.4896 | 193184.24 | 0.00 | 276885.34 | 276885.34 | 9.91898276 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60974.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 176473.844 | 176473.844 | 5.402681 | 0.00154387 | 4652.782 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 5.6701 | 5.784257 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 176473.84 | 176473.84 | 1.0000 | 6.34234424 | 5.402681 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.54371268 | 60.00 | 32.22 | 27.78 | 0.000 | 176473.84 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00734300 | 21.00 | 0.00734300 | 46.3359 | 123526.92 | 0.00 | 177043.46 | 177043.46 | 6.34234424 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60974.3 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35705.738 | 35705.738 | 1.093494 | 0.00031237 | 941.244 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 1.1472 | 1.170322 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35705.74 | 35604.36 | 1.0000 | 1.28368036 | 1.093494 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.31233751 | 60.00 | 32.22 | 27.78 | 0.000 | 35705.74 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00739472 | 21.00 | 0.00739472 | 46.6597 | 24988.94 | 0.00 | 35819.92 | 35819.92 | 1.28368036 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23332.924 | 23332.924 | 0.714592 | 0.00020413 | 615.076 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 0.7497 | 0.764780 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23332.92 | 23332.92 | 1.0000 | 0.83887712 | 0.714592 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.20410578 | 60.00 | 32.22 | 27.78 | 0.000 | 23332.92 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00738354 | 21.00 | 0.00738354 | 46.5903 | 16329.79 | 0.00 | 23407.49 | 23407.49 | 0.83887712 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35706.006 | 35706.006 | 1.093502 | 0.00031237 | 941.251 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 1.1472 | 1.170331 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35706.01 | 35706.01 | 1.0000 | 1.28368994 | 1.093502 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.31233985 | 60.00 | 32.22 | 27.78 | 0.000 | 35706.01 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00739472 | 21.00 | 0.00739472 | 46.6597 | 24989.13 | 0.00 | 35820.19 | 35820.19 | 1.28368994 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23122.206 | 23122.206 | 0.708136 | 0.00020228 | 609.522 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 0.7429 | 0.757873 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23122.21 | 23122.21 | 1.0000 | 0.83129878 | 0.708136 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.20226251 | 60.00 | 32.22 | 27.78 | 0.000 | 23122.21 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00737867 | 21.00 | 0.00737867 | 46.5600 | 16182.41 | 0.00 | 23196.11 | 23196.11 | 0.83129878 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.3 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 220872.801 | -999.000 | 9.817302 | 0.00939644 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6111 | 1004.8586 | 1.1739 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.817302 | 11.52477986 | 4197.9300 | 999.8980 | 114.23343562 | 12.27 | 6.67 | 5.60 | 2685446.21 | 8.2248 | 8.224808 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 220872.80 | 173167.94 | 1.0000 | 11.52477986 | 9.817302 | 25.70 | 18.02 | 0.01009771 | 51557.8 | 10.91 | 10.91 | 0.00850000 | 32392.8 | 9.39548101 | 6.67 | 12.27 | 5.60 | 22300.918 | 198571.88 | 30.30 | 0.01336696 | 21.83 | 2.53819000 | 25.8543 | 24.00 | 0.00889112 | 24.00 | 0.00889112 | 46.6348 | 126332.00 | 0.00 | 224795.23 | 167334.71 | 11.52477986 | 25.70 | 18.30 | 0.01009771 | 51557.8 | 11.51 | 11.17 | 0.00812105 | 32052.4 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 83192.504 | 83192.504 | 2.945191 | 0.00072780 | 1313.722 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.817302 | 11.52477986 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 2.6730 | 2.726789 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 83192.50 | 83192.50 | 1.0000 | 3.45743396 | 2.945191 | -11.15 | -11.15 | 0.00186018 | -6585.9 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.72773007 | 60.00 | 32.22 | 27.78 | 0.000 | 83192.50 | -16.30 | 0.00092409 | -16.30 | 2.53819000 | 86.1808 | 21.00 | 0.00769796 | 21.00 | 0.00752983 | 47.4951 | 36560.89 | 0.00 | 70919.38 | 70919.38 | 3.45743396 | 2.80 | -1.40 | 0.00186018 | 7475.4 | 23.14 | 9.54 | 0.00186018 | 27987.6 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2124780.805 | -999.000 | 91.105944 | 0.09039309 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9859 | 1004.8586 | 1.1739 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 91.105944 | 106.95157400 | 4197.9300 | 999.8980 | 114.23343562 | 12.27 | 6.67 | 5.60 | 2685446.21 | 79.1221 | 79.122076 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2124780.80 | 1626199.72 | 1.0000 | 106.95157400 | 91.105944 | 25.87 | 18.24 | 0.01029929 | 52249.9 | 10.90 | 10.90 | 0.00850000 | 32383.2 | 90.38386627 | 6.67 | 12.27 | 5.60 | 208061.178 | 1916719.63 | 30.30 | 0.01336696 | 21.83 | 25.38195000 | 27.8598 | 24.00 | 0.00900168 | 24.00 | 0.00900168 | 47.2074 | 1145653.56 | 0.00 | 2160990.44 | 1575120.95 | 106.95157400 | 25.87 | 18.51 | 0.01029929 | 52249.9 | 11.49 | 11.17 | 0.00812750 | 32044.6 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 857187.499 | 857187.499 | 27.331783 | 0.00749905 | 13369.890 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 91.105944 | 106.95157400 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 27.5416 | 28.095909 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 857187.50 | 857187.50 | 1.0000 | 32.08547220 | 27.331783 | -13.79 | -13.79 | 0.00138078 | -10435.4 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 7.49828520 | 60.00 | 32.22 | 27.78 | 0.000 | 857187.50 | -16.30 | 0.00092409 | -16.30 | 25.38195000 | 92.8661 | 18.93 | 0.00732577 | 19.29 | 0.00700352 | 49.1347 | 471600.12 | 0.00 | 710530.21 | 710530.21 | 32.08547220 | 2.80 | -2.17 | 0.00138078 | 6274.0 | 24.78 | 9.75 | 0.00138078 | 28418.9 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 220434.697 | -999.000 | 9.828951 | 0.00937780 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6189 | 1004.8586 | 1.1739 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.828951 | 11.53845401 | 4197.9300 | 999.8980 | 114.23343562 | 12.27 | 6.67 | 5.60 | 2685446.21 | 8.2085 | 8.208494 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 220434.70 | 172548.50 | 1.0000 | 11.53845401 | 9.828951 | 25.63 | 18.00 | 0.01010188 | 51497.1 | 10.91 | 10.91 | 0.00850000 | 32392.8 | 9.37684495 | 6.67 | 12.27 | 5.60 | 22327.378 | 198107.32 | 30.30 | 0.01336696 | 21.83 | 2.53819000 | 25.8236 | 24.00 | 0.00896317 | 24.00 | 0.00896317 | 47.0085 | 131702.62 | 0.00 | 224356.62 | 166728.61 | 11.53845401 | 25.63 | 18.28 | 0.01010188 | 51497.1 | 11.51 | 11.17 | 0.00812180 | 32052.9 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 84779.531 | 84779.531 | 2.948685 | 0.00074169 | 1336.028 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.828951 | 11.53845401 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 2.7240 | 2.778806 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 84779.53 | 84779.53 | 1.0000 | 3.46153620 | 2.948685 | -11.57 | -11.57 | 0.00180418 | -7156.2 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.74161266 | 60.00 | 32.22 | 27.78 | 0.000 | 84779.53 | -16.30 | 0.00092409 | -16.30 | 2.53819000 | 86.0787 | 17.65 | 0.00724595 | 17.37 | 0.00695340 | 55.0542 | 53845.68 | 0.00 | 71940.92 | 71940.92 | 3.46153620 | 2.80 | -1.49 | 0.00180418 | 7335.1 | 23.41 | 9.60 | 0.00180418 | 28118.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 119357.909 | -999.000 | 5.795869 | 0.00507776 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3538 | 1004.8586 | 1.1739 | CAV_BAS FAN | Fan:ConstantVolume | 5.795869 | 6.80391752 | 4197.9300 | 999.8980 | 114.23343562 | 12.27 | 6.67 | 5.60 | 2685446.21 | 4.4446 | 4.444621 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 119357.91 | 94320.20 | 1.0000 | 6.80391752 | 5.795869 | 24.93 | 17.66 | 0.00995925 | 50424.1 | 11.39 | 11.29 | 0.00850000 | 32881.6 | 5.07724339 | 6.67 | 12.27 | 5.60 | 9827.791 | 109530.12 | 28.16 | 0.01336316 | 21.21 | 1.20015641 | 20.7071 | 24.00 | 0.00897223 | 24.00 | 0.00897223 | 47.0538 | 77431.14 | 0.00 | 121531.74 | 91548.98 | 6.80391752 | 24.93 | 17.93 | 0.00995925 | 50424.1 | 11.79 | 11.38 | 0.00821254 | 32562.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 296555.548 | 296555.548 | 5.795869 | 0.00259440 | 6449.852 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | CAV_BAS FAN | Fan:ConstantVolume | 5.795869 | 6.80391752 | 4197.9300 | 999.8980 | 26.68817435 | 54.44 | 82.22 | 27.78 | 3112334.74 | 9.5284 | 9.720158 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 296555.55 | 296555.55 | 1.0000 | 6.80391752 | 5.795869 | -3.38 | -6.86 | 0.00092409 | -1086.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.59413265 | 60.00 | 32.22 | 27.78 | 0.000 | 296555.55 | -16.30 | 0.00092409 | -16.30 | 1.20015641 | 20.7071 | 0.00 | 0.00092409 | 23.06 | 0.00092409 | 5.1951 | 0.00 | 0.00 | 241290.97 | 241290.97 | 6.80391752 | 12.80 | 3.26 | 0.00092409 | 15195.0 | 48.03 | 18.24 | 0.00092409 | 50658.6 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 434369.887 | 305610.940 | 21.894177 | 0.01063769 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8583 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 403506.61 | 396786.04 | 0.9289 | -999.0 | -999.0 | 28.48 | 17.76 | 0.00861685 | 50621.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 403506.61 | 30.30 | 0.01336696 | 21.83 | 0.33839277 | -999.0000 | 27.00 | 0.00854219 | 27.00 | 0.00854219 | 37.5158 | 371990.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9810.551 | 6939.212 | 0.500510 | 0.00024026 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0762 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 9094.09 | 8786.83 | 0.9270 | -999.0 | -999.0 | 27.96 | 17.68 | 0.00873408 | 50391.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9094.09 | 26.67 | 0.01336053 | 20.77 | 0.01563234 | -999.0000 | 27.00 | 0.00858490 | 27.00 | 0.00858490 | 37.6984 | 8513.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 93907.701 | 66371.155 | 4.784164 | 0.00229979 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0961 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 87069.72 | 83998.25 | 0.9272 | -999.0 | -999.0 | 27.96 | 17.69 | 0.00874477 | 50417.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87069.72 | 26.67 | 0.01336053 | 20.77 | 0.15632344 | -999.0000 | 27.00 | 0.00858881 | 27.00 | 0.00858881 | 37.7155 | 81368.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9548.792 | 6750.819 | 0.486731 | 0.00023385 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0885 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8852.70 | 8545.48 | 0.9271 | -999.0 | -999.0 | 27.96 | 17.68 | 0.00874066 | 50407.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8852.70 | 26.67 | 0.01336053 | 20.77 | 0.01563234 | -999.0000 | 27.00 | 0.00858736 | 27.00 | 0.00858736 | 37.7091 | 8280.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 434369.887 | 434369.887 | 21.894177 | 0.01063769 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 434369.89 | 434369.89 | 1.0000 | 25.70212854 | 21.894177 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 434369.89 | -16.30 | 0.00092409 | -16.30 | 0.33839277 | 1.5456 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9810.551 | 9810.551 | 0.500510 | 0.00024026 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9810.55 | 9810.55 | 1.0000 | 0.58756154 | 0.500510 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9810.55 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.1233 | 0.00 | 0.00247647 | 25.44 | 0.00247647 | 12.0381 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 93907.701 | 93907.701 | 4.784164 | 0.00229979 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 93907.70 | 93907.70 | 1.0000 | 5.61625120 | 4.784164 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93907.70 | -16.30 | 0.00092409 | -16.30 | 0.15632344 | 3.2675 | 0.00 | 0.00148430 | 23.72 | 0.00148430 | 8.0131 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9548.792 | 9548.792 | 0.486731 | 0.00023385 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9548.79 | 9548.79 | 1.0000 | 0.57138590 | 0.486731 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9548.79 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.2117 | 0.00 | 0.00148387 | 22.47 | 0.00148387 | 8.6361 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22473.716 | 22473.716 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.894177 | 25.70212854 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 22473.72 | 22473.72 | 1.0000 | 25.70212854 | 21.894177 | -0.25 | -0.25 | 0.00838291 | 20708.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22473.72 | -16.30 | 0.00092409 | -16.30 | 0.33839277 | 1.5456 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.500510 | 0.58756154 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1038.19 | 1038.19 | 1.0000 | 0.58756154 | 0.500510 | -0.51 | -2.51 | 0.00242798 | 5558.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1038.19 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.1233 | 0.00 | 0.00247647 | 25.44 | 0.00247647 | 12.0381 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10381.926 | 10381.926 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.784164 | 5.61625120 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10381.93 | 10381.93 | 1.0000 | 5.61625120 | 4.784164 | -0.53 | -4.11 | 0.00146599 | 3129.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10381.93 | -16.30 | 0.00092409 | -16.30 | 0.15632344 | 3.2675 | 0.00 | 0.00148430 | 23.72 | 0.00148430 | 8.0131 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.486731 | 0.57138590 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1038.19 | 1038.19 | 1.0000 | 0.57138590 | 0.486731 | -0.52 | -4.11 | 0.00146590 | 3138.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1038.19 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.2117 | 0.00 | 0.00148387 | 22.47 | 0.00148387 | 8.6361 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.54 | 9.82 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 25.38 | 91.11 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.54 | 9.83 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.80 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2508.33 | 1630.50 | 403.67 |
CORE_BOTTOM | 2441.17 | 1453.50 | 16.33 |
CORE_MID | 1905.00 | 3045.33 | 179.50 |
CORE_TOP | 2544.83 | 3617.83 | 996.17 |
PERIMETER_BOT_ZN_3 | 2313.50 | 3366.67 | 633.00 |
PERIMETER_BOT_ZN_2 | 2389.33 | 3641.17 | 696.83 |
PERIMETER_BOT_ZN_1 | 2597.17 | 3228.33 | 688.83 |
PERIMETER_BOT_ZN_4 | 2647.17 | 2809.83 | 332.00 |
PERIMETER_MID_ZN_3 | 3239.00 | 4112.00 | 1939.33 |
PERIMETER_MID_ZN_2 | 2737.67 | 3540.33 | 1632.50 |
PERIMETER_MID_ZN_1 | 3000.67 | 3684.00 | 1415.83 |
PERIMETER_MID_ZN_4 | 3097.00 | 4144.17 | 1668.17 |
PERIMETER_TOP_ZN_3 | 3608.17 | 4391.33 | 2458.83 |
PERIMETER_TOP_ZN_2 | 3648.67 | 4184.83 | 2289.67 |
PERIMETER_TOP_ZN_1 | 3381.83 | 4037.83 | 1971.67 |
PERIMETER_TOP_ZN_4 | 3416.83 | 4334.83 | 2132.17 |
DATACENTER_BOT_ZN_6 | 5908.00 | 837.17 | 837.17 |
DATACENTER_MID_ZN_6 | 5145.33 | 241.67 | 143.83 |
DATACENTER_TOP_ZN_6 | 4671.50 | 690.83 | 302.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5585.00 | 5585.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5939.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 46.83 | 0.00 | 1.67 |
CORE_BOTTOM | 0.00 | 1.17 | 0.00 | 0.00 |
CORE_MID | 1.17 | 0.17 | 0.17 | 0.00 |
CORE_TOP | 14.17 | 0.00 | 2.17 | 0.00 |
PERIMETER_BOT_ZN_3 | 1.83 | 0.17 | 0.17 | 0.00 |
PERIMETER_BOT_ZN_2 | 3.00 | 7.00 | 0.00 | 7.00 |
PERIMETER_BOT_ZN_1 | 4.00 | 10.17 | 0.17 | 10.17 |
PERIMETER_BOT_ZN_4 | 0.33 | 53.50 | 0.00 | 22.50 |
PERIMETER_MID_ZN_3 | 120.00 | 0.00 | 34.17 | 0.00 |
PERIMETER_MID_ZN_2 | 62.67 | 6.17 | 3.33 | 6.17 |
PERIMETER_MID_ZN_1 | 54.50 | 9.00 | 2.67 | 9.00 |
PERIMETER_MID_ZN_4 | 45.67 | 16.17 | 0.83 | 8.33 |
PERIMETER_TOP_ZN_3 | 300.00 | 1.00 | 103.33 | 0.83 |
PERIMETER_TOP_ZN_2 | 190.33 | 6.67 | 38.00 | 6.67 |
PERIMETER_TOP_ZN_1 | 169.17 | 10.83 | 33.50 | 10.50 |
PERIMETER_TOP_ZN_4 | 137.00 | 16.50 | 26.00 | 8.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 134.33 | 0.00 | 124.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 338.17 | 264.50 | 107.17 | 174.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 1.298 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 1.040 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.846 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.824 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 1.025 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.665 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.475 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.194 | 0.061 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.899 | 0.138 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.636 | 0.151 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.427 | 0.138 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.817 | 0.143 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 1.012 | 0.171 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.754 | 0.177 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.471 | 0.171 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.899 | 0.177 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.481 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 53955831.33 | 0.00 | 53955831.33 | 0.00 | 53955831.33 | 37848132.68 | 3939.84 | 986.42 | 3833.74 | 380.16 |
CORE_BOTTOM | 44549589.65 | 0.00 | 44549589.65 | 0.00 | 44549589.65 | 33990283.35 | 3609.19 | 6.36 | 5144.44 | 522.71 |
CORE_MID | 0.35E+09 | 0.00 | 0.35E+09 | 0.00 | 0.35E+09 | 0.34E+09 | 4040.34 | 4.74 | 4714.93 | 390.97 |
CORE_TOP | 33872050.49 | 0.00 | 33872050.49 | 0.00 | 33872050.49 | 33990283.35 | 4082.71 | 7.18 | 4670.11 | 467.36 |
PERIMETER_BOT_ZN_3 | 5579377.58 | 0.00 | 5579377.58 | 584665.50 | 6164043.08 | 4267819.30 | 3730.90 | 57.02 | 4972.07 | 522.71 |
PERIMETER_BOT_ZN_2 | 5920786.54 | 0.00 | 5920786.54 | 389776.73 | 6310563.27 | 2750345.05 | 3445.63 | 1.75 | 5312.61 | 522.71 |
PERIMETER_BOT_ZN_1 | 8033271.04 | 0.00 | 8033271.04 | 584665.50 | 8617936.53 | 4267912.63 | 3486.22 | 5.10 | 5268.69 | 522.71 |
PERIMETER_BOT_ZN_4 | 7764993.89 | 0.00 | 7764993.89 | 389776.73 | 8154770.62 | 2750345.05 | 3397.69 | 2.45 | 5359.86 | 522.71 |
PERIMETER_MID_ZN_3 | 46886471.17 | 0.00 | 46886471.17 | 1371204.53 | 48257675.70 | 42678193.03 | 4016.91 | 3.27 | 4739.82 | 390.97 |
PERIMETER_MID_ZN_2 | 58886073.04 | 0.00 | 58886073.04 | 914135.73 | 59800208.77 | 27503450.52 | 3860.61 | 3.46 | 4895.93 | 1299.97 |
PERIMETER_MID_ZN_1 | 74259706.05 | 0.00 | 74259706.05 | 1371204.53 | 75630910.59 | 42679126.28 | 3933.43 | 2.16 | 4824.40 | 390.97 |
PERIMETER_MID_ZN_4 | 61401635.57 | 0.00 | 61401635.57 | 914135.73 | 62315771.30 | 27503450.52 | 3855.47 | 2.44 | 4902.09 | 390.97 |
PERIMETER_TOP_ZN_3 | 5254219.77 | 0.00 | 5254219.77 | 1702496.76 | 6956716.53 | 4267819.30 | 4033.52 | 4.45 | 4722.03 | 467.36 |
PERIMETER_TOP_ZN_2 | 5867600.69 | 0.00 | 5867600.69 | 1134997.06 | 7002597.75 | 2750345.05 | 3955.28 | 3.37 | 4801.36 | 467.36 |
PERIMETER_TOP_ZN_1 | 7612248.74 | 0.00 | 7612248.74 | 1702496.76 | 9314745.49 | 4267912.63 | 3999.57 | 2.32 | 4758.11 | 467.36 |
PERIMETER_TOP_ZN_4 | 6369087.34 | 0.00 | 6369087.34 | 1134997.06 | 7504084.40 | 2750345.05 | 3940.24 | 3.24 | 4816.52 | 467.36 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.61E+10 | 0.00 | 0.61E+10 | 53330677.35 | 0.62E+10 | 0.50E+10 | 4574.17 | 4396.74 | 5552.36 | 2012.13 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.3900 | 0.0000 | 2.3900 | 0.0000 | 2.3900 | 1.2002 | 1349.57 | 982.89 | 3610.53 |
CORE_BOTTOM | 1.9350 | 0.0000 | 1.9350 | 0.0000 | 1.9350 | 1.0778 | 1216.19 | 2.45 | 4724.37 |
CORE_MID | 15.7582 | 0.0000 | 15.7582 | 0.0000 | 15.7582 | 10.7782 | 1359.63 | 4.37 | 4578.99 |
CORE_TOP | 1.5363 | 0.0000 | 1.5363 | 0.0000 | 1.5363 | 1.0778 | 1368.14 | 7.01 | 4567.85 |
PERIMETER_BOT_ZN_3 | 0.2400 | 0.0000 | 0.2400 | 0.0139 | 0.2539 | 0.1353 | 1360.46 | 53.32 | 4529.22 |
PERIMETER_BOT_ZN_2 | 0.2518 | 0.0000 | 0.2518 | 0.0092 | 0.2611 | 0.0872 | 1123.12 | 1.08 | 4818.79 |
PERIMETER_BOT_ZN_1 | 0.3456 | 0.0000 | 0.3456 | 0.0139 | 0.3595 | 0.1353 | 1152.07 | 3.56 | 4787.37 |
PERIMETER_BOT_ZN_4 | 0.3313 | 0.0000 | 0.3313 | 0.0092 | 0.3405 | 0.0872 | 1094.35 | 1.89 | 4846.76 |
PERIMETER_MID_ZN_3 | 2.1095 | 0.0000 | 2.1095 | 0.0325 | 2.1420 | 1.3533 | 1342.71 | 2.93 | 4597.37 |
PERIMETER_MID_ZN_2 | 2.4795 | 0.0000 | 2.4795 | 0.0230 | 2.5024 | 0.8721 | 1244.35 | 2.37 | 3787.28 |
PERIMETER_MID_ZN_1 | 3.3500 | 0.0000 | 3.3500 | 0.0325 | 3.3825 | 1.3533 | 1280.79 | 1.10 | 4661.11 |
PERIMETER_MID_ZN_4 | 2.7537 | 0.0000 | 2.7537 | 0.0217 | 2.7754 | 0.8721 | 1242.16 | 0.89 | 4699.95 |
PERIMETER_TOP_ZN_3 | 0.2378 | 0.0000 | 0.2378 | 0.0404 | 0.2782 | 0.1353 | 1331.79 | 2.68 | 4608.53 |
PERIMETER_TOP_ZN_2 | 0.2657 | 0.0000 | 0.2657 | 0.0269 | 0.2927 | 0.0872 | 1282.91 | 1.90 | 4658.19 |
PERIMETER_TOP_ZN_1 | 0.3455 | 0.0000 | 0.3455 | 0.0404 | 0.3859 | 0.1353 | 1309.67 | 1.05 | 4632.28 |
PERIMETER_TOP_ZN_4 | 0.2878 | 0.0000 | 0.2878 | 0.0269 | 0.3148 | 0.0872 | 1276.41 | 1.41 | 4665.18 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 274.0870 | 0.0000 | 274.0870 | 1.2780 | 275.3650 | 158.4706 | 1757.17 | 4373.17 | 4895.30 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 99019987.39 | 0.00 | 99019987.39 | 48026705.38 | 3479.35 | 5.82 | 5274.83 | 522.71 |
VAV_MID WITH REHEAT | 0.81E+09 | 0.00 | 0.81E+09 | 0.48E+09 | 3936.59 | 2.47 | 4820.94 | 390.97 |
VAV_TOP WITH REHEAT | 81274406.14 | 0.00 | 81274406.14 | 48026705.38 | 4007.60 | 3.13 | 4749.26 | 467.17 |
CAV_BAS | 74356565.78 | 0.00 | 74356565.78 | 37848132.68 | 3857.75 | 5.58 | 4896.66 | 380.16 |
AIRLOOP DATACENTER BASEMENT | 7287763.88 | 0.00 | 7287763.88 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 336664.50 | 0.00 | 336664.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3366645.00 | 0.00 | 3366645.00 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 336664.50 | 0.00 | 336664.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.2776 | 0.0000 | 4.2776 | 1.5229 | 1144.71 | 4.23 | 4794.06 |
VAV_MID WITH REHEAT | 36.6802 | 0.0000 | 36.6802 | 15.2292 | 1281.66 | 1.42 | 4659.92 |
VAV_TOP WITH REHEAT | 3.6840 | 0.0000 | 3.6840 | 1.5229 | 1313.90 | 2.66 | 4626.44 |
CAV_BAS | 3.2936 | 0.0000 | 3.2936 | 1.2002 | 1318.55 | 2.50 | 4621.95 |
AIRLOOP DATACENTER BASEMENT | 0.3406 | 0.0000 | 0.3406 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0157 | 0.0000 | 0.0157 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1574 | 0.0000 | 0.1574 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0157 | 0.0000 | 0.0157 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 2011.38 | 3366.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 2396.81 | 2789.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 2531.22 | 2797.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 968.47 | 4070.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 3.4987 | 6.4671 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 34.9906 | 55.9436 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 3.4981 | 5.5966 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6547 | 4.8705 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4664 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2155 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1386 |
Defaulted Fields | 1179 |
Fields with Defaults | 3922 |
Autosized Fields | 336 |
Autosizable Fields | 412 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 28487.61 | 366863.27 | 29-JAN-10:30 | 2070659.62 | 15-AUG-14:30 |
Electricity:Building | 18920.42 | 251811.03 | 01-JAN-09:10 | 1146857.44 | 01-DEC-16:40 |
Electricity:Zone:BASEMENT | 664.85 | 14623.97 | 01-JAN-00:10 | 34452.17 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18920.42 | 251811.03 | 01-JAN-09:10 | 1146857.44 | 01-DEC-16:40 |
InteriorLights:Electricity | 3707.01 | 17601.77 | 01-JAN-09:10 | 352853.36 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3707.01 | 17601.77 | 01-JAN-09:10 | 352853.36 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 3707.01 | 17601.77 | 01-JAN-09:10 | 352853.36 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 240.45 | 1166.43 | 01-JAN-00:10 | 20994.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3707.01 | 17601.77 | 01-JAN-09:10 | 352853.36 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 537.23 | 7090.40 | 01-JAN-00:10 | 36983.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5372.24 | 70903.72 | 01-JAN-00:10 | 369831.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2159.40 | 10475.32 | 01-JAN-00:10 | 188546.48 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 537.22 | 7090.37 | 01-JAN-00:10 | 36983.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 215.94 | 1047.53 | 01-JAN-00:10 | 18854.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 59.03 | 839.57 | 01-JAN-09:10 | 4643.71 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.68 | 80.80 | 01-JAN-09:10 | 2367.39 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.68 | 80.80 | 01-JAN-09:10 | 2367.39 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 38.02 | 541.05 | 01-JAN-08:40 | 2992.58 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.02 | 52.07 | 01-JAN-08:40 | 1525.64 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.02 | 52.07 | 01-JAN-08:40 | 1525.64 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 58.92 | 839.58 | 01-JAN-08:40 | 4643.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.58 | 80.80 | 01-JAN-08:40 | 2367.44 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.58 | 80.80 | 01-JAN-08:40 | 2367.44 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 38.01 | 541.05 | 01-JAN-09:10 | 2992.57 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 12.01 | 52.07 | 01-JAN-09:10 | 1525.64 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 12.01 | 52.07 | 01-JAN-09:10 | 1525.64 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 590.43 | 8395.70 | 01-JAN-09:10 | 46437.07 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 187.01 | 807.98 | 01-JAN-09:10 | 23673.89 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 187.01 | 807.98 | 01-JAN-09:10 | 23673.89 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 380.19 | 5410.51 | 01-JAN-08:40 | 29925.82 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 120.21 | 520.69 | 01-JAN-08:40 | 15256.36 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 120.21 | 520.69 | 01-JAN-08:40 | 15256.36 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 589.37 | 8395.84 | 01-JAN-08:50 | 46437.94 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 185.94 | 807.99 | 01-JAN-08:50 | 23674.41 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 185.94 | 807.99 | 01-JAN-08:50 | 23674.41 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 380.10 | 5410.48 | 01-JAN-09:10 | 29925.72 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 120.12 | 520.69 | 01-JAN-09:10 | 15256.36 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 120.12 | 520.69 | 01-JAN-09:10 | 15256.36 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 59.04 | 839.57 | 01-JAN-09:10 | 4643.71 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.70 | 80.80 | 01-JAN-09:10 | 2367.39 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.70 | 80.80 | 01-JAN-09:10 | 2367.39 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 38.02 | 541.05 | 01-JAN-08:40 | 2992.58 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.02 | 52.07 | 01-JAN-08:40 | 1525.64 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.02 | 52.07 | 01-JAN-08:40 | 1525.64 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 58.94 | 839.58 | 01-JAN-08:50 | 4643.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.59 | 80.80 | 01-JAN-08:50 | 2367.44 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.59 | 80.80 | 01-JAN-08:50 | 2367.44 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 38.01 | 541.05 | 01-JAN-09:10 | 2992.57 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 12.01 | 52.07 | 01-JAN-09:10 | 1525.64 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 12.01 | 52.07 | 01-JAN-09:10 | 1525.64 | 02-JAN-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7562.65 | 95237.01 | 01-JAN-00:10 | 385552.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 67.80 | 328.88 | 01-JAN-00:10 | 5919.59 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1598.46 | 19775.43 | 01-JAN-00:10 | 83152.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 59.65 | 289.38 | 01-JAN-00:10 | 5208.47 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.85 | 1977.54 | 01-JAN-00:10 | 8315.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.97 | 28.94 | 01-JAN-00:10 | 520.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2063.60 | 5447.73 | 31-JAN-02:00 | 545345.49 | 15-AUG-14:30 |
HeatRejection:Electricity | 908.47 | 1834.50 | 04-JAN-08:00 | 88758.50 | 01-JUN-14:50 |
General:HeatRejection:Electricity | 908.47 | 1834.50 | 04-JAN-08:00 | 88758.50 | 01-JUN-14:50 |
Electricity:HVAC | 4977.51 | 74721.20 | 01-JAN-04:00 | 444446.01 | 09-AUG-15:20 |
ExteriorEquipment:Electricity | 1941.94 | 28795.69 | 01-JAN-00:10 | 118957.30 | 02-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 87.32 | 1613.62 | 01-JAN-00:10 | 5481.25 | 01-DEC-16:50 |
ElectricityPurchased:Facility | 28487.61 | 366863.27 | 29-JAN-10:30 | 2070659.62 | 15-AUG-14:30 |
ElectricityPurchased:Plant | 28487.61 | 366863.27 | 29-JAN-10:30 | 2070659.62 | 15-AUG-14:30 |
Cogeneration:ElectricityPurchased | 28487.61 | 366863.27 | 29-JAN-10:30 | 2070659.62 | 15-AUG-14:30 |
General:Cogeneration:ElectricityPurchased | 28487.61 | 366863.27 | 29-JAN-10:30 | 2070659.62 | 15-AUG-14:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 28487.61 | 366863.27 | 29-JAN-10:30 | 2070659.62 | 15-AUG-14:30 |
ElectricityNet:Plant | 28487.61 | 366863.27 | 29-JAN-10:30 | 2070659.62 | 15-AUG-14:30 |
Cogeneration:ElectricityNet | 28487.61 | 366863.27 | 29-JAN-10:30 | 2070659.62 | 15-AUG-14:30 |
General:Cogeneration:ElectricityNet | 28487.61 | 366863.27 | 29-JAN-10:30 | 2070659.62 | 15-AUG-14:30 |
Fans:Electricity | 2398.00 | 42573.50 | 09-JAN-22:10 | 262302.90 | 09-AUG-15:20 |
General:Fans:Electricity | 2398.00 | 42573.50 | 09-JAN-22:10 | 262302.90 | 09-AUG-15:20 |
ExteriorLights:Electricity | 671.46 | 0.00 | 01-JAN-08:00 | 54335.80 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 671.46 | 0.00 | 01-JAN-08:00 | 54335.80 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 46.74 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 46.74 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
Cooling:Electricity | 3090.36 | 27192.71 | 30-JAN-07:10 | 543094.23 | 15-AUG-14:30 |
General:Cooling:Electricity | 3090.36 | 27192.71 | 30-JAN-07:10 | 543094.23 | 15-AUG-14:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 17.94 | 0.00 | 01-JAN-00:10 | 6182.53 | 23-JAN-21:00 |
General:Humidifier:Electricity | 17.94 | 0.00 | 01-JAN-00:10 | 6182.53 | 23-JAN-21:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 492.28 | 3420.63 | 07-JAN-06:00 | 69521.04 | 01-AUG-16:00 |
General:Pumps:Electricity | 492.28 | 3420.63 | 07-JAN-06:00 | 69521.04 | 01-AUG-16:00 |
WIRED_LTG_ELECTRICITY | 104.17 | 0.00 | 01-JAN-00:10 | 9915.18 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2784.58 | 5695.87 | 24-JAN-04:50 | 2093215.67 | 21-FEB-07:10 |
NaturalGas:Plant | 2784.58 | 5695.87 | 24-JAN-04:50 | 2093215.67 | 21-FEB-07:10 |
Heating:NaturalGas | 2036.02 | 0.00 | 01-JAN-00:40 | 2063243.41 | 21-FEB-07:10 |
Boiler:Heating:NaturalGas | 2036.02 | 0.00 | 01-JAN-00:40 | 2063243.41 | 21-FEB-07:10 |
WaterSystems:NaturalGas | 748.56 | 5695.87 | 02-JAN-04:20 | 84377.97 | 16-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 748.56 | 5695.87 | 02-JAN-04:20 | 84377.97 | 16-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 16767.16 | 133901.27 | 30-JAN-07:10 | 3360209.00 | 15-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 16767.16 | 133901.27 | 30-JAN-07:10 | 3360209.00 | 15-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 16767.16 | 133901.27 | 30-JAN-07:10 | 3360209.00 | 15-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 5749.36 | 0.00 | 01-JAN-00:10 | 0.00 | 03-AUG-15:40 |
Water:HVAC | 6.67 | 0.00 | 01-JAN-00:10 | 0.00 | 23-JAN-21:00 |
Humidifier:Water | 6.67 | 0.00 | 01-JAN-00:10 | 0.00 | 23-JAN-21:00 |
General:Humidifier:Water | 6.67 | 0.00 | 01-JAN-00:10 | 0.00 | 23-JAN-21:00 |
MainsWater:Facility | 5749.36 | 0.00 | 01-JAN-00:10 | 0.00 | 03-AUG-15:40 |
MainsWater:HVAC | 6.67 | 0.00 | 01-JAN-00:10 | 0.00 | 23-JAN-21:00 |
Humidifier:MainsWater | 6.67 | 0.00 | 01-JAN-00:10 | 0.00 | 23-JAN-21:00 |
General:Humidifier:MainsWater | 6.67 | 0.00 | 01-JAN-00:10 | 0.00 | 23-JAN-21:00 |
Water:Plant | 5742.69 | 0.00 | 01-JAN-00:10 | 0.00 | 03-AUG-15:40 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5742.69 | 0.00 | 01-JAN-00:10 | 0.00 | 03-AUG-15:40 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3462.52 | 0.00 | 01-JAN-00:10 | 0.00 | 03-AUG-15:40 |
General:HeatRejection:Water | 3462.52 | 0.00 | 01-JAN-00:10 | 0.00 | 03-AUG-15:40 |
HeatRejection:MainsWater | 3462.52 | 0.00 | 01-JAN-00:10 | 0.00 | 03-AUG-15:40 |
General:HeatRejection:MainsWater | 3462.52 | 0.00 | 01-JAN-00:10 | 0.00 | 03-AUG-15:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 53933.27 | 213051.45 | 30-JAN-03:50 | 13092785.30 | 15-AUG-14:30 |
EnergyTransfer:Building | 18574.62 | 88355.85 | 15-JAN-15:00 | 1643751.14 | 09-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 668.58 | 0.00 | 01-JAN-00:10 | 71593.14 | 05-SEP-05:10 |
Heating:EnergyTransfer | 943.49 | 0.00 | 01-FEB-00:20 | 1291946.06 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 2.86 | 0.00 | 01-JAN-00:10 | 13443.35 | 17-JUN-16:40 |
General:Heating:EnergyTransfer | 943.49 | 0.00 | 01-FEB-00:20 | 1291946.06 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 2.86 | 0.00 | 01-JAN-00:10 | 13443.35 | 17-JUN-16:40 |
Cooling:EnergyTransfer | 17631.13 | 85235.83 | 30-JAN-03:50 | 1643751.14 | 09-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 665.72 | 0.00 | 01-JAN-00:10 | 71593.14 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 17631.13 | 85235.83 | 30-JAN-03:50 | 1643751.14 | 09-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 665.72 | 0.00 | 01-JAN-00:10 | 71593.14 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 606.51 | 0.00 | 01-JAN-00:10 | 53583.08 | 07-AUG-10:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 606.51 | 0.00 | 01-JAN-00:10 | 53583.08 | 07-AUG-10:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 606.51 | 0.00 | 01-JAN-00:10 | 53583.08 | 07-AUG-10:00 |
EnergyTransfer:Zone:CORE_MID | 4305.86 | 0.00 | 01-JAN-00:40 | 482669.16 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 11.90 | 0.00 | 01-JAN-00:10 | 482669.16 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 11.90 | 0.00 | 01-JAN-00:10 | 482669.16 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4293.96 | 0.00 | 01-JAN-00:40 | 447547.49 | 20-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4293.96 | 0.00 | 01-JAN-00:40 | 447547.49 | 20-JUL-13:10 |
EnergyTransfer:Zone:CORE_TOP | 396.96 | 0.00 | 01-JAN-00:40 | 70828.88 | 26-DEC-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 17.25 | 0.00 | 01-JAN-00:40 | 70828.88 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 17.25 | 0.00 | 01-JAN-00:40 | 70828.88 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 379.71 | 0.00 | 01-JAN-00:20 | 51966.01 | 17-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 379.71 | 0.00 | 01-JAN-00:20 | 51966.01 | 17-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 67.60 | 0.00 | 01-JAN-00:10 | 10201.72 | 21-JUL-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 1.26 | 0.00 | 01-JAN-00:10 | 8943.58 | 07-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 1.26 | 0.00 | 01-JAN-00:10 | 8943.58 | 07-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 66.34 | 0.00 | 01-JAN-00:10 | 10201.72 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 66.34 | 0.00 | 01-JAN-00:10 | 10201.72 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.93 | 0.00 | 01-JAN-00:10 | 12205.14 | 13-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.15 | 0.00 | 01-JAN-00:10 | 6918.32 | 07-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.15 | 0.00 | 01-JAN-00:10 | 6918.32 | 07-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 63.78 | 0.00 | 01-JAN-00:10 | 12205.14 | 13-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 63.78 | 0.00 | 01-JAN-00:10 | 12205.14 | 13-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 97.14 | 0.00 | 01-JAN-00:10 | 18684.00 | 11-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.11 | 0.00 | 01-JAN-00:10 | 11036.15 | 07-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.11 | 0.00 | 01-JAN-00:10 | 11036.15 | 07-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 95.03 | 0.00 | 01-JAN-00:10 | 18684.00 | 11-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 95.03 | 0.00 | 01-JAN-00:10 | 18684.00 | 11-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 96.40 | 0.00 | 01-JAN-00:10 | 16372.40 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.15 | 0.00 | 01-JAN-00:10 | 4072.44 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.15 | 0.00 | 01-JAN-00:10 | 4072.44 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 96.24 | 0.00 | 01-JAN-00:10 | 16372.40 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 96.24 | 0.00 | 01-JAN-00:10 | 16372.40 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 613.81 | 0.00 | 01-JAN-00:40 | 126843.54 | 13-FEB-04:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 194.80 | 0.00 | 01-JAN-00:40 | 126843.54 | 13-FEB-04:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 194.80 | 0.00 | 01-JAN-00:40 | 126843.54 | 13-FEB-04:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 419.01 | 0.00 | 01-JAN-00:20 | 96838.45 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 419.01 | 0.00 | 01-JAN-00:20 | 96838.45 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 599.94 | 0.00 | 01-JAN-00:40 | 148584.41 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 115.69 | 0.00 | 01-JAN-00:40 | 148584.41 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 115.69 | 0.00 | 01-JAN-00:40 | 148584.41 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 484.25 | 0.00 | 01-JAN-00:20 | 128958.45 | 13-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 484.25 | 0.00 | 01-JAN-00:20 | 128958.45 | 13-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 867.17 | 0.00 | 01-JAN-00:40 | 188479.97 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 125.98 | 0.00 | 01-JAN-00:40 | 178979.52 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 125.98 | 0.00 | 01-JAN-00:40 | 178979.52 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 741.19 | 0.00 | 01-JAN-00:20 | 188479.97 | 31-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 741.19 | 0.00 | 01-JAN-00:20 | 188479.97 | 31-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 617.58 | 0.00 | 01-JAN-00:40 | 145130.87 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 92.02 | 0.00 | 01-JAN-00:40 | 145130.87 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 92.02 | 0.00 | 01-JAN-00:40 | 145130.87 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 525.56 | 0.00 | 01-JAN-00:20 | 136723.08 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 525.56 | 0.00 | 01-JAN-00:20 | 136723.08 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 83.47 | 0.00 | 01-JAN-00:40 | 16468.30 | 26-DEC-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.87 | 0.00 | 01-JAN-00:40 | 16468.30 | 26-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.87 | 0.00 | 01-JAN-00:40 | 16468.30 | 26-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.60 | 0.00 | 01-JAN-00:10 | 10746.72 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.60 | 0.00 | 01-JAN-00:10 | 10746.72 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 70.58 | 0.00 | 01-JAN-00:40 | 16643.77 | 13-FEB-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.86 | 0.00 | 01-JAN-00:40 | 16643.77 | 13-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.86 | 0.00 | 01-JAN-00:40 | 16643.77 | 13-FEB-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.72 | 0.00 | 01-JAN-00:20 | 12794.74 | 30-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.72 | 0.00 | 01-JAN-00:20 | 12794.74 | 30-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 98.91 | 0.00 | 01-JAN-00:40 | 21250.06 | 13-FEB-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 31.38 | 0.00 | 01-JAN-00:40 | 21250.06 | 13-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 31.38 | 0.00 | 01-JAN-00:40 | 21250.06 | 13-FEB-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 67.53 | 0.00 | 01-JAN-00:20 | 19137.41 | 11-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 67.53 | 0.00 | 01-JAN-00:20 | 19137.41 | 11-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 70.03 | 0.00 | 01-JAN-00:40 | 17397.93 | 07-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 21.16 | 0.00 | 01-JAN-00:40 | 17397.93 | 07-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 21.16 | 0.00 | 01-JAN-00:40 | 17397.93 | 07-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 48.87 | 0.00 | 01-JAN-00:20 | 14280.09 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 48.87 | 0.00 | 01-JAN-00:20 | 14280.09 | 10-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 58.03 | 0.00 | 01-JAN-00:10 | 9080.62 | 17-JUL-12:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.73 | 0.00 | 01-JAN-00:10 | 5774.57 | 11-DEC-15:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.73 | 0.00 | 01-JAN-00:10 | 5774.57 | 11-DEC-15:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 53.30 | 0.00 | 01-JAN-00:10 | 9080.62 | 17-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 53.30 | 0.00 | 01-JAN-00:10 | 9080.62 | 17-JUL-12:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 527.58 | 0.00 | 01-JAN-00:40 | 167678.53 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 180.55 | 0.00 | 01-JAN-00:40 | 167678.53 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 180.55 | 0.00 | 01-JAN-00:40 | 167678.53 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 347.04 | 0.00 | 01-JAN-00:10 | 75452.41 | 21-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 347.04 | 0.00 | 01-JAN-00:10 | 75452.41 | 21-JUL-12:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 112.89 | 0.00 | 01-JAN-00:40 | 29618.88 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 63.98 | 0.00 | 01-JAN-00:40 | 29618.88 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 63.98 | 0.00 | 01-JAN-00:40 | 29618.88 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 48.90 | 0.00 | 01-JAN-00:10 | 19538.43 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 48.90 | 0.00 | 01-JAN-00:10 | 19538.43 | 21-JUL-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.44 | 100.05 | 30-JAN-05:20 | 8166.74 | 04-AUG-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.44 | 100.05 | 30-JAN-05:20 | 8166.74 | 04-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.44 | 100.05 | 30-JAN-05:20 | 8166.74 | 04-AUG-18:30 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1148.44 | 1.54 | 20-JAN-07:50 | 77950.19 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.87 | 0.00 | 02-JAN-08:30 | 5603.80 | 24-JAN-02:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.87 | 0.00 | 02-JAN-08:30 | 5603.80 | 24-JAN-02:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1142.57 | 0.00 | 01-JAN-00:10 | 77950.19 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1142.57 | 0.00 | 01-JAN-00:10 | 77950.19 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 104.93 | 0.01 | 26-JAN-21:40 | 7849.40 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.93 | 0.00 | 02-JAN-08:30 | 599.58 | 09-JAN-23:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.93 | 0.00 | 02-JAN-08:30 | 599.58 | 09-JAN-23:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 104.00 | 0.00 | 01-JAN-00:10 | 7849.40 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 104.00 | 0.00 | 01-JAN-00:10 | 7849.40 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7161.85 | 84996.53 | 30-JAN-05:00 | 369092.54 | 11-AUG-11:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7161.85 | 84996.53 | 30-JAN-05:00 | 369092.54 | 11-AUG-11:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7161.85 | 84996.53 | 30-JAN-05:00 | 369092.54 | 11-AUG-11:00 |
PlantLoopHeatingDemand:Facility | 1939.67 | 0.00 | 01-JAN-00:40 | 1731177.26 | 26-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 444.85 | 0.00 | 01-JAN-00:10 | 55177.51 | 14-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 444.85 | 0.00 | 01-JAN-00:10 | 55177.51 | 14-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 444.85 | 0.00 | 01-JAN-00:10 | 55177.51 | 14-FEB-12:20 |
EnergyTransfer:HVAC | 19304.44 | 121905.36 | 30-JAN-03:50 | 3204260.61 | 15-AUG-14:30 |
HeatingCoils:EnergyTransfer | 1494.82 | 0.00 | 01-JAN-00:40 | 1713574.86 | 26-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 1494.82 | 0.00 | 01-JAN-00:40 | 1713574.86 | 26-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 1494.82 | 0.00 | 01-JAN-00:40 | 1713574.86 | 26-DEC-07:10 |
CoolingCoils:EnergyTransfer | 14339.65 | 106708.56 | 30-JAN-07:10 | 3204260.61 | 15-AUG-14:30 |
HeatRecoveryForHeating:EnergyTransfer | 3295.27 | 0.00 | 01-JAN-00:10 | 1004113.83 | 11-DEC-20:00 |
HeatRecoveryForCooling:EnergyTransfer | 174.70 | 0.00 | 01-JAN-00:10 | 485359.96 | 20-JUL-14:00 |
EnergyTransfer:Plant | 16054.22 | 0.00 | 01-JAN-00:40 | 8338533.53 | 15-AUG-14:30 |
LoopToLoop:EnergyTransfer | 4779.86 | -1421.13 | 10-MAR-16:20 | 2704826.71 | 15-AUG-14:30 |
WaterSystems:EnergyTransfer | 444.85 | 0.00 | 01-JAN-00:10 | 55177.51 | 14-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 444.85 | 0.00 | 01-JAN-00:10 | 55177.51 | 14-FEB-12:20 |
Boilers:EnergyTransfer | 1481.37 | 0.00 | 01-JAN-00:40 | 1716822.53 | 21-FEB-07:10 |
Chillers:EnergyTransfer | 4342.65 | 0.00 | 01-JAN-00:10 | 2610835.71 | 15-AUG-14:30 |
HeatRejection:EnergyTransfer | 5005.49 | 0.00 | 01-JAN-00:10 | 2997981.56 | 15-AUG-14:30 |
General:HeatRejection:EnergyTransfer | 5005.49 | 0.00 | 01-JAN-00:10 | 2997981.56 | 15-AUG-14:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 2.857 | -665.719 | 0.000 | 0.000 | 92.967 | 240.449 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -94.950 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -606.512 | 0.000 | 0.000 | 83.531 | 215.940 | 321.286 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -14.244 |
CORE_MID | 0.000 | 0.000 | 11.904 | -4293.943 | 0.000 | 0.000 | 857.386 | 2159.397 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1947.589 |
CORE_TOP | 0.000 | 0.000 | 17.254 | -379.703 | 0.000 | 0.000 | 88.567 | 215.940 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -263.343 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 1.264 | -66.339 | 0.000 | 0.000 | 11.032 | 18.683 | 40.342 | 22.682 | 0.000 | 0.053 | 38.262 | 0.000 | -55.276 | 0.000 | -10.705 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.147 | -63.779 | 0.000 | 0.000 | 7.245 | 12.018 | 25.998 | 43.265 | 0.000 | 0.044 | 14.661 | 0.000 | -33.637 | 0.000 | -6.960 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.105 | -95.032 | 0.000 | 0.000 | 11.045 | 18.578 | 40.343 | 80.418 | 0.000 | 0.052 | 3.116 | 0.000 | -50.053 | 0.000 | -10.573 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.154 | -96.242 | 0.000 | 0.000 | 7.067 | 12.008 | 25.998 | 42.421 | 0.000 | 0.033 | 54.663 | 0.000 | -38.470 | 0.000 | -7.633 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 194.802 | -419.010 | 0.000 | 0.000 | 114.940 | 187.011 | 403.423 | 235.784 | 0.000 | 1.231 | 1.473 | 0.000 | -497.575 | 0.000 | -222.079 | -0.014 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 115.690 | -484.244 | 0.000 | 0.000 | 54.824 | 120.213 | 259.981 | 435.598 | 0.000 | 0.888 | 0.005 | 0.000 | -311.778 | 0.000 | -148.823 | -42.348 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 125.981 | -741.181 | 0.000 | 0.000 | 113.054 | 185.943 | 403.429 | 805.280 | 0.000 | 1.130 | 0.005 | 0.000 | -476.235 | 0.000 | -231.106 | -186.294 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 92.016 | -525.561 | 0.000 | 0.000 | 74.950 | 120.124 | 259.979 | 436.130 | 0.000 | 0.837 | 27.489 | 0.000 | -333.048 | 0.000 | -152.915 | -0.003 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 43.872 | -39.600 | 0.000 | 0.000 | 11.694 | 18.701 | 40.342 | 24.119 | 0.000 | 0.145 | 0.001 | 0.000 | -47.022 | 0.000 | -26.233 | -26.018 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 25.855 | -44.724 | 0.000 | 0.000 | 7.500 | 12.021 | 25.998 | 43.847 | 0.000 | 0.098 | 0.001 | 0.000 | -29.688 | 0.000 | -17.715 | -23.193 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 31.378 | -67.531 | 0.000 | 0.000 | 11.491 | 18.594 | 40.343 | 81.130 | 0.000 | 0.132 | 0.001 | 0.000 | -45.068 | 0.000 | -27.222 | -43.246 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 21.159 | -48.870 | 0.000 | 0.000 | 7.581 | 12.012 | 25.998 | 43.817 | 0.000 | 0.098 | 0.000 | 0.000 | -31.791 | 0.000 | -18.176 | -11.829 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -135.436 | 0.000 | 0.000 | 0.950 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -25.360 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 5.868 | -1142.575 | 0.000 | 0.000 | 9.518 | 59.652 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -471.269 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.928 | -104.000 | 0.000 | 0.000 | 0.956 | 5.965 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -57.730 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7161.854 | 0.000 | 0.000 | 20.483 | 67.796 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -421.283 |
GROUNDFLOOR_PLENUM | 4.730 | -53.298 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.089 | 71.258 | 0.000 | 0.000 | 0.000 | -22.779 | 0.000 |
MIDFLOOR_PLENUM | 180.550 | -347.035 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.685 | 543.962 | 0.000 | 0.000 | 0.000 | -379.163 | -0.020 |
TOPFLOOR_PLENUM | 63.985 | -48.903 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.106 | 25.123 | 0.000 | 0.000 | 0.000 | -40.312 | -0.001 |
Total Facility | 249.265 | -449.235 | 694.234 | -17181.855 | 0.000 | 0.000 | 1586.780 | 3707.010 | 15213.411 | 2294.489 | 0.000 | 6.623 | 780.023 | 0.000 | -1949.640 | 0.000 | -1322.394 | -3628.734 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 16-OCT-03:01 | 0.00 | 0.00 | 0.00 | -113660.76 | 0.00 | 0.00 | 0.00 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 99036.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 18-SEP-03:02 | 0.00 | 0.00 | 0.00 | -96087.91 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.15 | 0.00 | 0.00 | 0.00 | 86983.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 18-SEP-03:02 | 0.00 | 0.00 | 0.00 | -866478.29 | 0.00 | 0.00 | 0.00 | 10475.32 | 80571.20 | 0.00 | 0.00 | 0.00 | 775431.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-03:02 | 0.00 | 0.00 | 0.00 | -86211.83 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.12 | 0.00 | 0.00 | 0.00 | 77107.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-16:21 | 0.00 | 0.00 | 0.00 | -15859.06 | 0.00 | 0.00 | 44.22 | 80.80 | 758.77 | 3924.51 | 0.00 | 79.55 | 10971.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-08:51 | 0.00 | 0.00 | 0.00 | -21569.80 | 0.00 | 0.00 | 21.69 | 52.07 | 488.98 | 15844.12 | 0.00 | 0.00 | 5320.23 | 0.00 | -0.00 | 0.00 | -157.29 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-12:23 | 0.00 | 0.00 | 0.00 | -23812.98 | 0.00 | 0.00 | 38.16 | 80.80 | 758.78 | 18983.81 | 0.00 | 0.00 | 4204.43 | 0.00 | -0.00 | 0.00 | -253.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 16-JUL-17:01 | 0.00 | 0.00 | 0.00 | -27446.95 | 0.00 | 0.00 | 0.00 | 52.07 | 488.98 | 13145.08 | 0.00 | 0.00 | 13817.79 | 0.00 | -0.00 | 0.00 | -56.96 | 0.00 |
PERIMETER_MID_ZN_3 | 18-JUL-05:03 | 0.00 | 0.00 | 0.00 | -116142.38 | 0.00 | 0.00 | 1096.48 | 1971.07 | 10116.97 | 11876.73 | 0.00 | 0.00 | 91081.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:51 | 0.00 | 0.00 | 0.00 | -230189.36 | 0.00 | 0.00 | 207.33 | 520.69 | 4889.82 | 157416.02 | 0.00 | 0.00 | 71017.68 | 0.00 | -0.00 | 0.00 | -3862.19 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-13:32 | 0.00 | 0.00 | 0.00 | -240291.01 | 0.00 | 0.00 | 374.93 | 807.99 | 7587.84 | 173648.71 | 0.00 | 0.00 | 66324.58 | 0.00 | -0.00 | 0.00 | -8453.05 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-16:42 | 0.00 | 0.00 | 0.00 | -229395.10 | 0.00 | 0.00 | 183.21 | 520.69 | 4889.79 | 171663.62 | 0.00 | 0.00 | 54098.07 | 0.00 | -0.00 | 0.00 | -1960.28 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-15:12 | 0.00 | 0.00 | 0.00 | -18033.08 | 0.00 | 0.00 | 42.20 | 80.80 | 758.77 | 4810.93 | 0.00 | 234.46 | 12105.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 16-JUL-09:12 | 0.00 | 0.00 | 0.00 | -22531.95 | 0.00 | 0.00 | 21.75 | 52.07 | 488.98 | 13930.27 | 0.00 | 0.00 | 8117.55 | 0.00 | -0.00 | 0.00 | -78.67 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-13:32 | 0.00 | 0.00 | 0.00 | -25246.42 | 0.00 | 0.00 | 39.02 | 80.80 | 758.78 | 17370.33 | 0.00 | 0.00 | 8010.59 | 0.00 | -0.00 | 0.00 | -1013.10 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-16:42 | 0.00 | 0.00 | 0.00 | -24452.15 | 0.00 | 0.00 | 17.63 | 52.07 | 488.98 | 17091.60 | 0.00 | 0.00 | 7057.29 | 0.00 | -0.00 | 0.00 | -255.42 | 0.00 |
DATACENTER_BOT_ZN_6 | 04-AUG-18:30 | 0.00 | 0.00 | 0.00 | -8166.56 | 0.00 | 0.00 | 10.62 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 187.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -77948.70 | 0.00 | 0.00 | 106.16 | 1736.14 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1837.82 |
DATACENTER_TOP_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -7849.25 | 0.00 | 0.00 | 10.62 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -129.40 |
DATACENTER_BASEMENT_ZN_6 | 04-AUG-21:02 | 0.00 | 0.00 | 0.00 | -369883.98 | 0.00 | 0.00 | 114.12 | 657.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10520.43 |
GROUNDFLOOR_PLENUM | 17-JUL-05:15 | 0.00 | -10973.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11010.61 | 0.00 | -0.00 | 0.00 | -36.66 | 0.00 |
MIDFLOOR_PLENUM | 07-AUG-05:03 | 0.00 | -90680.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91884.67 | 0.00 | -0.00 | 0.00 | -1203.76 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-13:50 | 0.00 | -19537.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.68 | 19314.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-AUG-05:03 | 0.00 | 1561.16 | 0.00 | -1841131.80 | 0.00 | 0.00 | 15895.77 | 39207.80 | 623236.89 | 0.00 | 0.00 | 0.00 | 1202047.19 | 0.00 | -36303.25 | 0.00 | -4513.76 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 17-JUN-16:25 | 0.00 | 0.00 | 13982.96 | 0.00 | 0.00 | 0.00 | 436.63 | 1166.43 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29043.56 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:11 | 0.00 | 0.00 | 549780.66 | 0.00 | 0.00 | 0.00 | 0.00 | 10475.32 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -640827.19 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 80765.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1047.53 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -89869.92 |
PERIMETER_BOT_ZN_3 | 07-FEB-05:01 | 0.00 | 0.00 | 12374.69 | 0.00 | 0.00 | 0.00 | 0.00 | 263.06 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5500.51 | 0.00 | -2096.93 | -6052.01 |
PERIMETER_BOT_ZN_2 | 07-FEB-05:01 | 0.00 | 0.00 | 12700.87 | 0.00 | 0.00 | 0.00 | 0.00 | 169.52 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3650.23 | 0.00 | -1406.41 | -8465.73 |
PERIMETER_BOT_ZN_1 | 06-FEB-04:01 | 0.00 | 0.00 | 18908.20 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5375.21 | 0.00 | -1873.49 | -12802.74 |
PERIMETER_BOT_ZN_4 | 07-FEB-05:01 | 0.00 | 0.00 | 10619.44 | 0.00 | 0.00 | 0.00 | 0.00 | 169.52 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3900.71 | 0.00 | -1429.37 | -6110.86 |
PERIMETER_MID_ZN_3 | 13-FEB-03:42 | 0.00 | 0.00 | 139548.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.28 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -38800.02 | 0.00 | -54901.82 | -57278.75 |
PERIMETER_MID_ZN_2 | 13-FEB-03:42 | 0.00 | 0.00 | 183391.13 | 0.00 | 0.00 | 0.00 | 0.00 | 847.62 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25798.80 | 0.00 | -37694.46 | -127265.24 |
PERIMETER_MID_ZN_1 | 13-FEB-03:42 | 0.00 | 0.00 | 208041.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.31 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -40485.03 | 0.00 | -55739.41 | -123249.26 |
PERIMETER_MID_ZN_4 | 13-FEB-03:42 | 0.00 | 0.00 | 189357.06 | 0.00 | 0.00 | 0.00 | 0.00 | 847.62 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27444.90 | 0.00 | -38439.24 | -130840.25 |
PERIMETER_TOP_ZN_3 | 26-DEC-05:31 | 0.00 | 0.00 | 17702.68 | 0.00 | 0.00 | 0.00 | 0.00 | 263.06 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4445.15 | 0.00 | -5320.90 | -9211.39 |
PERIMETER_TOP_ZN_2 | 12-FEB-22:02 | 0.00 | 0.00 | 19043.26 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2406.73 | 0.00 | -3218.39 | -13991.88 |
PERIMETER_TOP_ZN_1 | 07-FEB-03:02 | 0.00 | 0.00 | 23071.89 | 0.00 | 0.00 | 0.00 | 0.00 | 131.53 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5062.83 | 0.00 | -5259.48 | -13892.82 |
PERIMETER_TOP_ZN_4 | 09-JAN-02:42 | 0.00 | 0.00 | 20847.87 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2672.71 | 0.00 | -2425.91 | -16485.98 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 24-JAN-02:00 | 0.00 | 0.00 | 5603.80 | 0.00 | 0.00 | 0.00 | 0.00 | 289.38 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25379.24 |
DATACENTER_TOP_ZN_6 | 15-JAN-18:05 | 0.00 | 0.00 | 605.18 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2582.72 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 15-FEB-06:01 | 15812.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -839.19 | -14973.24 |
MIDFLOOR_PLENUM | 02-JAN-06:02 | 174623.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5263.96 | -169359.91 |
TOPFLOOR_PLENUM | 06-FEB-05:10 | 30933.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7906.73 | -23027.02 |
Total Facility | 02-JAN-04:11 | -70483.68 | 116590.50 | 1385610.66 | -116590.50 | 0.00 | 0.00 | 0.00 | 19603.93 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -107360.58 | 0.00 | -78914.69 | -1416818.34 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.9987 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.8173 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 104.5889 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 91.1059 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.8025 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.8290 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.7959 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.7959 | 0.2071 | 1.0000 | Not calculated | 1.2002 | 0.2071 | ||
AIRLOOP DATACENTER BASEMENT | 21.8940 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.8942 | 0.0155 | 1.0000 | Not calculated | 0.3384 | 0.0155 | ||
AIRLOOP DATACENTER BOT | 0.5005 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5005 | 0.0312 | 1.0000 | Not calculated | 0.0156 | 0.0312 | ||
AIRLOOP DATACENTER MID | 4.7842 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.7842 | 0.0327 | 1.0000 | Not calculated | 0.1563 | 0.0327 | ||
AIRLOOP DATACENTER TOP | 0.4867 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4867 | 0.0321 | 1.0000 | Not calculated | 0.0156 | 0.0321 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.4994 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.4210 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 52.2945 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 33.2581 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.4012 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.4891 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.7959 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.7959 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2071 | ||
AIRLOOP DATACENTER BASEMENT | 21.8940 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.8940 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0155 | ||
AIRLOOP DATACENTER BOT | 0.5005 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5005 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0312 | ||
AIRLOOP DATACENTER MID | 4.7842 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.7842 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0327 | ||
AIRLOOP DATACENTER TOP | 0.4867 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4867 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0321 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7959 | 5.7959 | 5.7959 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0678 | 6.0678 | 1.9417 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 57.0118 | 57.0118 | 18.9849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6444 | 5.6444 | 1.9417 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9609 | 0.9609 | 0.2883 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1551 | 1.1551 | 0.3465 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3830 | 1.3830 | 0.4149 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4320 | 1.4320 | 0.4296 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.0078 | 9.0078 | 2.7023 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.1484 | 12.1484 | 3.6445 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.6178 | 13.6178 | 4.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.8031 | 12.8031 | 3.8409 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0935 | 1.0935 | 0.3280 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2269 | 1.2269 | 0.3681 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4758 | 1.4758 | 0.4427 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3619 | 1.3619 | 0.4086 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5005 | 0.5005 | 0.5005 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7842 | 4.7842 | 4.7842 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4867 | 0.4867 | 0.4867 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.8940 | 21.8940 | 21.8940 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.9987 | 9.8173 | 10.9987 | 3.4210 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 104.5889 | 91.1059 | 104.5889 | 33.2581 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.8025 | 9.8290 | 10.8025 | 3.4891 | 0.0000 | 1.0000 |
CAV_BAS | 5.7959 | 5.7959 | 5.7959 | 5.7959 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.8940 | 21.8942 | 21.8940 | 21.8940 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5005 | 0.5005 | 0.5005 | 0.5005 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7842 | 4.7842 | 4.7842 | 4.7842 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4867 | 0.4867 | 0.4867 | 0.4867 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7959 | 5.7959 | 5.7959 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0339 | 3.0339 | 1.9417 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.5059 | 28.5059 | 18.9849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8222 | 2.8222 | 1.9417 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4804 | 0.4804 | 0.2883 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5775 | 0.5775 | 0.3465 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6915 | 0.6915 | 0.4149 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7160 | 0.7160 | 0.4296 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5039 | 4.5039 | 2.7023 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0742 | 6.0742 | 3.6445 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.8089 | 6.8089 | 4.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4016 | 6.4016 | 3.8409 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5467 | 0.5467 | 0.3280 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6134 | 0.6134 | 0.3681 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7379 | 0.7379 | 0.4427 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6810 | 0.6810 | 0.4086 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5005 | 0.5005 | 0.5005 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7842 | 4.7842 | 4.7842 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4867 | 0.4867 | 0.4867 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.8940 | 21.8940 | 21.8940 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.4994 | 3.4210 | 3.4210 | 3.4210 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 52.2945 | 33.2581 | 33.2581 | 33.2581 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.4012 | 3.4891 | 3.4891 | 3.4891 | 0.0000 | 1.0000 |
CAV_BAS | 5.7959 | 5.7959 | 5.7959 | 5.7959 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.8940 | 21.8940 | 21.8940 | 21.8940 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5005 | 0.5005 | 0.5005 | 0.5005 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7842 | 4.7842 | 4.7842 | 4.7842 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4867 | 0.4867 | 0.4867 | 0.4867 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 107.17 |
Number of hours cooling loads not met | 174.67 |
Number of hours not met | 281.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 2036.02 | 2063243.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3090.36 | 543094.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3707.01 | 352853.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 671.46 | 54335.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.32 | 5481.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2398.00 | 262302.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 492.28 | 69521.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 908.47 | 88758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 17.94 | 6182.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 46.74 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 748.56 | 84377.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 28487.61 |
Natural Gas | 0.00 | 2784.58 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 31272.18 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 80.03 |
Space Heating | 0.00 |
Space Cooling | 66.72 |
Fans (All) | 51.77 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 615.01 |
Subtotal | 615.01 |
Natural Gas [MJ/m2] | |
Space Heating | 43.96 |
Service Water Heating | 16.16 |
Miscellaneous (All) | 60.12 |
Subtotal | 60.12 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.85 |
Space Heating | 6.51 |
Space Cooling | 9.88 |
Fans (All) | 7.67 |
Service Water Heating | 2.39 |
Receptacle Equipment | 48.65 |
Miscellaneous | 13.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2645. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8409.00 | 351.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8725.00 | 35.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8734.83 | 25.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8472.83 | 287.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8751.17 | 8.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8726.67 | 33.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8721.83 | 38.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8609.67 | 150.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8718.50 | 41.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8705.50 | 54.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8613.67 | 146.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7664.00 | 1096.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7653.17 | 1106.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7629.33 | 1130.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7637.50 | 1122.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8695.67 | 64.33 | 0.00 | 0.00 | 0.00 |
Min | 7629.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1130.67 | 0.00 | 0.00 | 0.00 |
Average | 8510.28 | 249.72 | 0.00 | 0.00 | 0.00 |
Sum | 195736.50 | 5743.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367541.50 | 1074.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330803.00 | 10.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330795.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1685.33 | 582.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1676.17 | 591.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1662.33 | 605.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 81176.50 | 22218.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367541.50 | 22218.50 | 0.00 | 0.00 | 0.00 |
Average | 79243.56 | 1091.36 | 0.00 | 0.00 | 0.00 |
Sum | 1822601.83 | 25101.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7733.50 | 1026.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8222.67 | 537.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8248.17 | 511.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8244.83 | 515.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8305.83 | 454.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8536.00 | 224.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8371.33 | 388.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8079.33 | 680.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8282.33 | 477.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8319.33 | 440.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8262.83 | 497.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8197.00 | 563.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8305.17 | 454.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8313.33 | 446.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8277.00 | 483.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8212.00 | 548.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8267.50 | 492.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8247.83 | 512.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8236.00 | 524.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8329.83 | 430.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8172.33 | 587.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8260.50 | 499.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7979.00 | 781.00 | 0.00 | 0.00 | 0.00 |
Min | 7733.50 | 224.00 | 0.00 | 0.00 | 0.00 |
Max | 8536.00 | 1026.50 | 0.00 | 0.00 | 0.00 |
Average | 8234.94 | 525.06 | 0.00 | 0.00 | 0.00 |
Sum | 189403.67 | 12076.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 359677.50 | 8938.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 329931.50 | 881.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330034.00 | 779.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330001.00 | 812.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38922.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38923.17 | 1.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1948.83 | 319.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1939.83 | 328.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1934.33 | 333.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 93262.67 | 10132.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 359677.50 | 10132.33 | 0.00 | 0.00 | 0.00 |
Average | 79355.41 | 979.51 | 0.00 | 0.00 | 0.00 |
Sum | 1825174.33 | 22528.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:17
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.452022E+11 | 112428.37 | 02-JAN-04:01 | -1.0 | -1.9 | 0.555607E+10 | 7499.18 | 11-JAN-10:09 | 7.98 | 6.90 |
February | 0.409114E+11 | 108757.37 | 21-FEB-04:50 | -11.6 | -12.7 | 0.502166E+10 | 7499.21 | 28-FEB-10:30 | -3.0 | -4.8 |
March | 0.536604E+11 | 109045.57 | 20-MAR-03:01 | -2.3 | -3.7 | 0.611871E+10 | 7499.20 | 28-MAR-09:09 | 2.38 | -0.7 |
April | 0.527270E+11 | 112717.00 | 10-APR-03:02 | 3.80 | 3.10 | 0.544653E+10 | 7499.16 | 12-APR-13:20 | 11.70 | 9.99 |
May | 0.556198E+11 | 110714.23 | 01-MAY-03:02 | 4.48 | 3.23 | 0.589930E+10 | 7499.28 | 10-MAY-09:09 | 18.68 | 14.82 |
June | 0.598411E+11 | 105928.49 | 13-JUN-03:02 | 10.50 | 10.11 | 0.588185E+10 | 7499.51 | 22-JUN-13:20 | 20.60 | 15.30 |
July | 0.609689E+11 | 103111.33 | 06-JUL-03:02 | 13.12 | 10.73 | 0.547348E+10 | 7499.04 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.683517E+11 | 102240.11 | 04-AUG-03:02 | 13.12 | 11.25 | 0.613846E+10 | 7533.25 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.605415E+11 | 110731.94 | 05-SEP-03:02 | 7.12 | 6.58 | 0.545266E+10 | 7499.51 | 12-SEP-13:20 | 21.10 | 16.62 |
October | 0.602744E+11 | 113675.78 | 16-OCT-03:01 | 0.68 | 0.41 | 0.566886E+10 | 7499.15 | 10-OCT-09:30 | 0.68 | 0.41 |
November | 0.568215E+11 | 113430.65 | 13-NOV-04:01 | 5.50 | 4.05 | 0.561244E+10 | 7499.20 | 06-NOV-14:20 | 5.50 | 4.05 |
December | 0.508003E+11 | 113321.60 | 26-DEC-04:01 | -11.8 | -12.8 | 0.545066E+10 | 7499.16 | 08-DEC-10:20 | -11.8 | -12.8 |
Annual Sum or Average | 0.665720E+12 | 0.677207E+11 | ||||||||
Minimum of Months | 0.409114E+11 | 102240.11 | -11.8 | -12.8 | 0.502166E+10 | 7499.04 | -11.8 | -12.8 | ||
Maximum of Months | 0.683517E+11 | 113675.78 | 13.12 | 11.25 | 0.613846E+10 | 7533.25 | 23.90 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321565E+11 | 81995.85 | 18-JAN-06:01 | 2.80 | 1.63 | 0.501253E+10 | 6748.28 | 17-JAN-10:30 | 2.80 | 1.63 |
February | 0.304990E+11 | 83347.83 | 23-FEB-06:01 | 2.30 | 1.81 | 0.455687E+10 | 6784.14 | 17-FEB-10:00 | 2.30 | 1.81 |
March | 0.474887E+11 | 89250.39 | 17-MAR-03:02 | 11.02 | 10.40 | 0.549482E+10 | 6834.93 | 01-MAR-10:09 | 11.02 | 10.40 |
April | 0.522059E+11 | 92968.08 | 10-APR-03:02 | 3.80 | 3.10 | 0.488340E+10 | 6739.56 | 17-APR-09:09 | 0.87 | -1.8 |
May | 0.523104E+11 | 95795.42 | 30-MAY-03:02 | 12.20 | 11.33 | 0.528777E+10 | 6734.85 | 10-MAY-09:09 | 12.20 | 11.33 |
June | 0.618326E+11 | 91870.34 | 13-JUN-03:02 | 10.50 | 10.11 | 0.526997E+10 | 6735.14 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.682264E+11 | 91895.64 | 06-JUL-03:02 | 13.12 | 10.73 | 0.489520E+10 | 6734.83 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.746398E+11 | 91379.11 | 31-AUG-03:02 | 12.12 | 11.53 | 0.549655E+10 | 6735.26 | 02-AUG-13:09 | 12.12 | 11.53 |
September | 0.530156E+11 | 96125.51 | 18-SEP-03:02 | 11.52 | 10.07 | 0.488354E+10 | 6735.16 | 12-SEP-13:09 | 11.52 | 10.07 |
October | 0.492071E+11 | 93439.26 | 23-OCT-03:02 | 15.63 | 12.80 | 0.507952E+10 | 6734.84 | 03-OCT-09:00 | 15.63 | 12.80 |
November | 0.455426E+11 | 93441.20 | 13-NOV-04:01 | 5.50 | 4.05 | 0.503040E+10 | 6778.12 | 28-NOV-10:30 | 2.75 | 1.17 |
December | 0.393880E+11 | 87373.42 | 18-DEC-05:01 | 1.70 | 0.81 | 0.488721E+10 | 6831.35 | 04-DEC-10:39 | 1.70 | 0.81 |
Annual Sum or Average | 0.606513E+12 | 0.607778E+11 | ||||||||
Minimum of Months | 0.304990E+11 | 81995.85 | 1.70 | 0.81 | 0.455687E+10 | 6734.83 | 0.87 | -1.8 | ||
Maximum of Months | 0.746398E+11 | 96125.51 | 15.63 | 12.80 | 0.549655E+10 | 6834.93 | 20.60 | 15.40 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227139E+11 | 23597.70 | 20-JAN-15:30 | -0.6 | -3.7 | 0.438918E+10 | 6662.91 | 20-JAN-14:00 | -0.6 | -3.7 |
February | 0.215034E+11 | 25204.28 | 17-FEB-16:50 | 1.28 | 0.31 | 0.401594E+10 | 6712.64 | 17-FEB-14:00 | 1.28 | 0.31 |
March | 0.306455E+11 | 77607.78 | 17-MAR-05:03 | 10.50 | 9.94 | 0.528094E+10 | 7097.13 | 24-MAR-13:20 | -0.6 | -3.7 |
April | 0.322695E+11 | 78257.86 | 10-APR-05:03 | 3.98 | 3.28 | 0.480482E+10 | 6826.97 | 04-APR-13:00 | 3.98 | 3.28 |
May | 0.418347E+11 | 81279.47 | 24-MAY-04:02 | 17.98 | 15.63 | 0.526964E+10 | 6734.85 | 10-MAY-09:09 | 17.98 | 15.63 |
June | 0.489502E+11 | 83813.02 | 30-JUN-03:02 | 17.12 | 16.11 | 0.526346E+10 | 6735.15 | 22-JUN-13:09 | 17.12 | 16.11 |
July | 0.504647E+11 | 84608.90 | 24-JUL-03:02 | 17.02 | 15.41 | 0.489323E+10 | 6734.82 | 03-JUL-13:30 | 17.02 | 15.41 |
August | 0.528512E+11 | 84591.88 | 21-AUG-03:02 | 15.50 | 13.60 | 0.549541E+10 | 6735.23 | 02-AUG-13:09 | 15.50 | 13.60 |
September | 0.429863E+11 | 86681.81 | 18-SEP-03:02 | 11.52 | 10.07 | 0.487030E+10 | 6735.17 | 12-SEP-13:09 | 11.52 | 10.07 |
October | 0.335915E+11 | 80710.54 | 05-OCT-05:02 | 8.80 | 8.23 | 0.501869E+10 | 6787.80 | 24-OCT-09:20 | 2.97 | 0.67 |
November | 0.277482E+11 | 73285.20 | 01-NOV-05:03 | 5.68 | 3.03 | 0.489419E+10 | 6838.05 | 17-NOV-14:50 | 5.50 | 2.49 |
December | 0.238366E+11 | 28008.20 | 21-DEC-17:00 | 0.60 | -0.7 | 0.437406E+10 | 6734.62 | 01-DEC-10:50 | 0.60 | -0.7 |
Annual Sum or Average | 0.429396E+12 | 0.585699E+11 | ||||||||
Minimum of Months | 0.215034E+11 | 23597.70 | -0.6 | -3.7 | 0.401594E+10 | 6662.91 | -0.6 | -3.7 | ||
Maximum of Months | 0.528512E+11 | 86681.81 | 17.98 | 16.11 | 0.549541E+10 | 7097.13 | 17.98 | 16.11 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157227E+11 | 17378.12 | 11-JAN-17:00 | 11.10 | 9.84 | 0.398059E+10 | 6030.25 | 19-JAN-14:00 | 1.10 | -0.2 |
February | 0.155805E+11 | 17808.96 | 17-FEB-17:00 | 1.10 | 0.20 | 0.368034E+10 | 6173.09 | 17-FEB-14:00 | 1.10 | 0.20 |
March | 0.250099E+11 | 53386.00 | 15-MAR-05:03 | 15.00 | 11.89 | 0.483641E+10 | 6741.48 | 17-MAR-09:00 | 10.00 | 9.40 |
April | 0.267226E+11 | 39976.02 | 21-APR-16:00 | 13.30 | 8.77 | 0.456223E+10 | 6734.76 | 21-APR-13:00 | 13.30 | 8.77 |
May | 0.375971E+11 | 79776.22 | 24-MAY-04:02 | 17.98 | 15.63 | 0.520628E+10 | 6752.51 | 03-MAY-09:39 | 17.98 | 15.63 |
June | 0.494308E+11 | 84749.76 | 19-JUN-03:02 | 17.12 | 16.11 | 0.525194E+10 | 6735.13 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.529855E+11 | 84870.74 | 05-JUL-03:02 | 18.80 | 16.41 | 0.489371E+10 | 6734.79 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.532070E+11 | 86225.22 | 07-AUG-03:02 | 20.00 | 18.50 | 0.549053E+10 | 6735.22 | 02-AUG-13:09 | 20.00 | 18.50 |
September | 0.388766E+11 | 85143.60 | 18-SEP-03:02 | 11.52 | 10.07 | 0.482914E+10 | 6735.14 | 12-SEP-13:09 | 11.52 | 10.07 |
October | 0.265718E+11 | 72882.38 | 12-OCT-05:02 | 13.40 | 11.29 | 0.472898E+10 | 6734.67 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.209210E+11 | 26582.48 | 01-NOV-16:00 | 9.40 | 6.91 | 0.439315E+10 | 6734.77 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.170794E+11 | 18438.51 | 01-DEC-17:00 | 7.20 | 4.89 | 0.388846E+10 | 6345.72 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.379705E+12 | 0.557418E+11 | ||||||||
Minimum of Months | 0.155805E+11 | 17378.12 | 1.10 | 0.20 | 0.368034E+10 | 6030.25 | 1.10 | -0.2 | ||
Maximum of Months | 0.532070E+11 | 86225.22 | 20.00 | 18.50 | 0.549053E+10 | 6752.51 | 20.60 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161387E+10 | 2897.30 | 17-JAN-06:02 | 7.20 | 2.95 | 0.490077E+09 | 753.35 | 17-JAN-14:00 | 6.70 | 5.64 |
February | 0.169699E+10 | 3562.54 | 28-FEB-14:50 | 0.00 | -2.8 | 0.455233E+09 | 765.68 | 23-FEB-14:20 | 0.00 | -2.8 |
March | 0.390388E+10 | 8313.84 | 16-MAR-05:03 | 14.03 | 11.42 | 0.620758E+09 | 845.65 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.483776E+10 | 6356.78 | 07-APR-13:30 | 20.00 | 10.05 | 0.592891E+09 | 845.64 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.611841E+10 | 7398.54 | 23-MAY-14:40 | 23.90 | 13.32 | 0.656901E+09 | 845.63 | 17-MAY-09:00 | 23.90 | 13.32 |
June | 0.922481E+10 | 12690.75 | 12-JUN-05:03 | 22.30 | 17.71 | 0.661170E+09 | 845.68 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.110423E+11 | 15861.98 | 16-JUL-16:21 | 28.90 | 21.75 | 0.615085E+09 | 846.01 | 20-JUL-13:20 | 30.00 | 23.48 |
August | 0.110576E+11 | 12634.28 | 21-AUG-05:03 | 14.40 | 13.12 | 0.689826E+09 | 845.97 | 14-AUG-13:20 | 14.40 | 13.12 |
September | 0.636087E+10 | 11130.53 | 15-SEP-05:03 | 18.30 | 16.87 | 0.607549E+09 | 845.68 | 12-SEP-13:09 | 18.30 | 16.87 |
October | 0.450667E+10 | 6743.36 | 23-OCT-05:03 | 11.70 | 9.96 | 0.613423E+09 | 845.63 | 03-OCT-09:00 | 11.70 | 9.96 |
November | 0.355506E+10 | 4523.20 | 27-NOV-12:00 | 15.00 | 10.52 | 0.583051E+09 | 845.64 | 16-NOV-14:09 | 15.00 | 10.52 |
December | 0.242066E+10 | 3159.37 | 01-DEC-06:02 | 10.10 | 8.62 | 0.501318E+09 | 813.26 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.663389E+11 | 0.708728E+10 | ||||||||
Minimum of Months | 0.161387E+10 | 2897.30 | 0.00 | -2.8 | 0.455233E+09 | 753.35 | 0.00 | -2.8 | ||
Maximum of Months | 0.110576E+11 | 15861.98 | 28.90 | 21.75 | 0.689826E+09 | 846.01 | 30.00 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154509E+10 | 3469.25 | 20-JAN-06:02 | -0.7 | -3.0 | 0.307187E+09 | 458.58 | 12-JAN-10:30 | -0.7 | -3.0 |
February | 0.161928E+10 | 4228.76 | 28-FEB-14:50 | 0.00 | -2.8 | 0.287023E+09 | 544.95 | 28-FEB-10:09 | 0.00 | -2.8 |
March | 0.399296E+10 | 7100.57 | 21-MAR-09:10 | 1.88 | -0.4 | 0.391276E+09 | 545.58 | 21-MAR-09:09 | 1.88 | -0.4 |
April | 0.532540E+10 | 10883.26 | 24-APR-08:20 | 5.37 | 2.54 | 0.368200E+09 | 544.96 | 21-APR-13:00 | 5.37 | 2.54 |
May | 0.664265E+10 | 13720.74 | 21-MAY-09:13 | 16.50 | 11.82 | 0.415098E+09 | 544.96 | 26-MAY-09:00 | 18.90 | 12.57 |
June | 0.862884E+10 | 20068.84 | 11-JUN-09:12 | 23.67 | 16.37 | 0.423406E+09 | 545.45 | 30-JUN-09:20 | 20.20 | 14.50 |
July | 0.996198E+10 | 21578.17 | 04-JUL-08:51 | 21.10 | 17.14 | 0.394412E+09 | 545.58 | 03-JUL-09:09 | 21.10 | 17.14 |
August | 0.970528E+10 | 11991.97 | 04-AUG-08:30 | 20.80 | 15.53 | 0.440607E+09 | 545.66 | 04-AUG-09:09 | 22.67 | 16.74 |
September | 0.649236E+10 | 13142.29 | 04-SEP-08:23 | 14.75 | 12.06 | 0.384819E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.461144E+10 | 8790.26 | 11-OCT-08:45 | 14.53 | 11.11 | 0.379126E+09 | 544.96 | 03-OCT-09:00 | 14.53 | 11.11 |
November | 0.344808E+10 | 4826.77 | 03-NOV-09:10 | 4.18 | 2.03 | 0.341232E+09 | 544.94 | 03-NOV-09:50 | 5.32 | 2.80 |
December | 0.180592E+10 | 3463.39 | 04-DEC-10:20 | -1.5 | -3.6 | 0.299378E+09 | 522.65 | 04-DEC-10:30 | -1.4 | -3.6 |
Annual Sum or Average | 0.637793E+11 | 0.443176E+10 | ||||||||
Minimum of Months | 0.154509E+10 | 3463.39 | -1.5 | -3.6 | 0.287023E+09 | 458.58 | -1.4 | -3.6 | ||
Maximum of Months | 0.996198E+10 | 21578.17 | 23.67 | 17.14 | 0.440607E+09 | 545.66 | 22.67 | 17.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268796E+10 | 10708.55 | 06-JAN-13:10 | -3.2 | -5.2 | 0.510630E+09 | 845.63 | 12-JAN-14:09 | -6.0 | -8.6 |
February | 0.297429E+10 | 19848.40 | 28-FEB-15:00 | 0.00 | -2.8 | 0.476622E+09 | 850.84 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.676438E+10 | 19698.37 | 01-MAR-14:10 | 0.10 | -2.4 | 0.634876E+09 | 873.46 | 07-MAR-14:20 | -2.6 | -5.6 |
April | 0.753597E+10 | 14026.13 | 24-APR-12:40 | 10.93 | 5.90 | 0.577908E+09 | 846.07 | 24-APR-13:20 | 11.67 | 6.21 |
May | 0.847331E+10 | 18758.85 | 14-MAY-13:52 | 25.00 | 18.14 | 0.644874E+09 | 845.67 | 10-MAY-13:09 | 25.00 | 18.14 |
June | 0.111128E+11 | 17800.16 | 25-JUN-13:12 | 26.10 | 17.35 | 0.657165E+09 | 845.71 | 22-JUN-13:09 | 26.10 | 17.35 |
July | 0.135849E+11 | 23321.17 | 16-JUL-11:42 | 27.88 | 20.85 | 0.613881E+09 | 846.58 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.148028E+11 | 21666.36 | 13-AUG-15:12 | 29.80 | 23.30 | 0.688288E+09 | 846.52 | 03-AUG-13:00 | 29.80 | 23.30 |
September | 0.106127E+11 | 23809.96 | 04-SEP-12:23 | 19.15 | 12.86 | 0.603707E+09 | 846.94 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.795963E+10 | 18684.00 | 11-OCT-12:30 | 21.95 | 13.79 | 0.608591E+09 | 853.66 | 31-OCT-13:20 | 15.00 | 10.26 |
November | 0.541060E+10 | 14412.03 | 03-NOV-12:20 | 8.17 | 4.43 | 0.562163E+09 | 846.07 | 03-NOV-13:20 | 9.07 | 4.95 |
December | 0.311323E+10 | 11740.19 | 04-DEC-11:25 | -0.6 | -3.1 | 0.495792E+09 | 849.83 | 04-DEC-10:00 | -0.6 | -3.1 |
Annual Sum or Average | 0.950326E+11 | 0.707450E+10 | ||||||||
Minimum of Months | 0.268796E+10 | 10708.55 | -3.2 | -5.2 | 0.476622E+09 | 845.63 | -6.0 | -8.6 | ||
Maximum of Months | 0.148028E+11 | 23809.96 | 29.80 | 23.30 | 0.688288E+09 | 873.46 | 29.80 | 23.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272108E+10 | 4578.23 | 17-JAN-06:01 | 7.20 | 2.95 | 0.314430E+09 | 487.47 | 12-JAN-16:10 | 7.20 | 2.95 |
February | 0.337034E+10 | 7587.49 | 28-FEB-15:00 | 0.00 | -2.8 | 0.300848E+09 | 543.04 | 22-FEB-14:00 | 0.00 | -2.8 |
March | 0.663148E+10 | 14816.30 | 16-MAR-05:03 | 14.03 | 11.42 | 0.416454E+09 | 547.96 | 07-MAR-14:00 | 14.03 | 11.42 |
April | 0.850808E+10 | 23897.43 | 09-APR-17:12 | 12.20 | 9.68 | 0.389945E+09 | 544.97 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.831917E+10 | 20114.50 | 07-MAY-16:32 | 15.00 | 5.92 | 0.416072E+09 | 544.96 | 17-MAY-09:00 | 18.90 | 14.77 |
June | 0.120342E+11 | 26915.57 | 11-JUN-15:51 | 25.60 | 17.82 | 0.426178E+09 | 544.99 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.143459E+11 | 27459.32 | 16-JUL-17:01 | 27.12 | 20.22 | 0.397202E+09 | 544.99 | 03-JUL-13:30 | 27.12 | 20.22 |
August | 0.155318E+11 | 25337.10 | 06-AUG-16:32 | 27.80 | 18.98 | 0.445734E+09 | 545.02 | 02-AUG-13:09 | 27.80 | 18.98 |
September | 0.809290E+10 | 19099.21 | 04-SEP-16:22 | 18.30 | 13.01 | 0.386774E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.652190E+10 | 12618.15 | 23-OCT-03:02 | 15.63 | 12.80 | 0.391886E+09 | 544.96 | 12-OCT-13:00 | 15.63 | 12.80 |
November | 0.550541E+10 | 9351.49 | 04-NOV-05:02 | 10.18 | 9.37 | 0.380042E+09 | 544.97 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.466013E+10 | 6740.23 | 04-DEC-15:30 | -0.3 | -3.1 | 0.344121E+09 | 540.05 | 04-DEC-14:50 | -0.3 | -3.1 |
Annual Sum or Average | 0.962424E+11 | 0.460969E+10 | ||||||||
Minimum of Months | 0.272108E+10 | 4578.23 | -0.3 | -3.1 | 0.300848E+09 | 487.47 | -0.3 | -3.1 | ||
Maximum of Months | 0.155318E+11 | 27459.32 | 27.80 | 20.22 | 0.445734E+09 | 547.96 | 27.80 | 20.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100400E+09 | 1665.88 | 14-JAN-17:02 | 3.22 | 2.72 | 0.464092E+09 | 625.90 | 12-JAN-10:50 | 3.22 | 2.72 |
February | 0.130109E+09 | 1745.40 | 17-FEB-15:00 | 3.30 | 1.08 | 0.421050E+09 | 627.18 | 17-FEB-14:00 | 3.30 | 1.08 |
March | 0.169706E+10 | 5543.97 | 15-MAR-14:30 | 25.85 | 16.15 | 0.546464E+09 | 845.64 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.262212E+10 | 3645.83 | 21-APR-15:10 | 14.72 | 8.39 | 0.520585E+09 | 845.62 | 21-APR-13:00 | 14.72 | 8.39 |
May | 0.450256E+10 | 6498.29 | 23-MAY-14:40 | 23.90 | 13.32 | 0.637214E+09 | 845.63 | 17-MAY-09:00 | 23.90 | 13.32 |
June | 0.721124E+10 | 11390.59 | 21-JUN-05:03 | 18.30 | 16.18 | 0.657769E+09 | 845.67 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.839658E+10 | 11618.31 | 18-JUL-05:03 | 17.30 | 16.98 | 0.614681E+09 | 845.76 | 20-JUL-13:20 | 30.00 | 23.48 |
August | 0.781652E+10 | 9942.94 | 14-AUG-03:02 | 23.80 | 22.23 | 0.687379E+09 | 845.69 | 02-AUG-13:09 | 23.80 | 22.23 |
September | 0.485495E+10 | 6788.15 | 15-SEP-14:00 | 25.60 | 21.03 | 0.594148E+09 | 845.68 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.281524E+10 | 3881.11 | 12-OCT-15:30 | 18.30 | 15.05 | 0.547730E+09 | 845.62 | 12-OCT-13:00 | 18.30 | 15.05 |
November | 0.152316E+10 | 3569.11 | 28-NOV-13:55 | 1.70 | 1.02 | 0.485520E+09 | 770.79 | 16-NOV-14:00 | 1.70 | 1.02 |
December | 0.231403E+09 | 2358.07 | 01-DEC-13:40 | 10.17 | 8.68 | 0.448695E+09 | 673.95 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.419013E+11 | 0.662533E+10 | ||||||||
Minimum of Months | 0.100400E+09 | 1665.88 | 1.70 | 1.02 | 0.421050E+09 | 625.90 | 1.70 | 1.02 | ||
Maximum of Months | 0.839658E+10 | 11618.31 | 25.85 | 22.23 | 0.687379E+09 | 845.76 | 30.00 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104641E+09 | 2426.42 | 11-JAN-06:04 | 5.68 | 2.64 | 0.219308E+09 | 385.83 | 20-JAN-13:50 | -0.5 | -3.5 |
February | 0.324965E+09 | 2976.27 | 28-FEB-10:00 | -3.9 | -5.5 | 0.199560E+09 | 449.74 | 28-FEB-09:00 | -3.9 | -5.5 |
March | 0.232934E+10 | 4964.00 | 14-MAR-10:40 | 21.27 | 17.29 | 0.256761E+09 | 521.20 | 15-MAR-12:20 | 25.00 | 15.61 |
April | 0.376957E+10 | 10212.03 | 24-APR-07:50 | 4.63 | 2.29 | 0.249395E+09 | 534.45 | 24-APR-07:40 | 4.63 | 2.29 |
May | 0.591374E+10 | 11540.74 | 31-MAY-08:50 | 17.70 | 13.18 | 0.293705E+09 | 522.19 | 08-MAY-07:30 | 17.70 | 13.18 |
June | 0.796170E+10 | 21086.22 | 11-JUN-09:52 | 24.40 | 16.86 | 0.307278E+09 | 521.33 | 20-JUN-08:50 | 21.23 | 16.06 |
July | 0.886019E+10 | 23027.95 | 04-JUL-08:51 | 21.10 | 17.14 | 0.290124E+09 | 521.43 | 13-JUL-08:00 | 20.00 | 16.15 |
August | 0.830599E+10 | 12925.81 | 06-AUG-09:13 | 24.47 | 17.45 | 0.320787E+09 | 521.46 | 04-AUG-08:00 | 24.47 | 17.45 |
September | 0.583873E+10 | 18842.92 | 04-SEP-08:52 | 16.70 | 13.10 | 0.274473E+09 | 521.24 | 12-SEP-12:20 | 20.77 | 15.37 |
October | 0.336974E+10 | 7018.21 | 11-OCT-09:00 | 15.00 | 11.35 | 0.251627E+09 | 521.21 | 10-OCT-10:20 | 15.00 | 11.35 |
November | 0.147611E+10 | 3649.15 | 03-NOV-10:15 | 5.97 | 3.19 | 0.224572E+09 | 495.23 | 03-NOV-10:30 | 6.15 | 3.28 |
December | 0.170008E+09 | 2508.05 | 01-DEC-06:04 | 10.10 | 8.62 | 0.211721E+09 | 389.60 | 01-DEC-13:00 | 8.30 | 6.91 |
Annual Sum or Average | 0.484247E+11 | 0.309931E+10 | ||||||||
Minimum of Months | 0.104641E+09 | 2426.42 | -3.9 | -5.5 | 0.199560E+09 | 385.83 | -3.9 | -5.5 | ||
Maximum of Months | 0.886019E+10 | 23027.95 | 24.47 | 17.45 | 0.320787E+09 | 534.45 | 25.00 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131012E+10 | 8660.98 | 12-JAN-13:40 | -6.5 | -9.0 | 0.488488E+09 | 845.64 | 12-JAN-14:39 | -5.8 | -8.3 |
February | 0.161489E+10 | 12666.81 | 28-FEB-13:50 | 0.00 | -3.0 | 0.450196E+09 | 845.64 | 28-FEB-14:50 | 0.00 | -2.8 |
March | 0.499954E+10 | 15554.75 | 15-MAR-13:30 | 25.55 | 15.84 | 0.598614E+09 | 867.65 | 21-MAR-13:50 | 4.90 | 1.79 |
April | 0.542469E+10 | 13350.92 | 24-APR-13:10 | 11.38 | 6.04 | 0.543743E+09 | 845.67 | 21-APR-13:50 | 11.38 | 6.04 |
May | 0.731913E+10 | 18099.40 | 14-MAY-13:42 | 24.82 | 18.07 | 0.628657E+09 | 845.66 | 05-MAY-13:09 | 24.82 | 18.07 |
June | 0.943383E+10 | 13244.08 | 12-JUN-13:10 | 29.60 | 19.81 | 0.650263E+09 | 845.71 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.109909E+11 | 18383.42 | 04-JUL-14:52 | 26.70 | 17.63 | 0.611946E+09 | 846.32 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.117749E+11 | 23244.80 | 13-AUG-14:21 | 30.00 | 23.06 | 0.684259E+09 | 846.29 | 03-AUG-13:00 | 30.00 | 23.06 |
September | 0.983703E+10 | 24030.68 | 04-SEP-13:32 | 18.33 | 13.04 | 0.595426E+09 | 851.40 | 21-SEP-13:39 | 25.40 | 16.58 |
October | 0.670923E+10 | 18848.00 | 31-OCT-13:30 | 15.00 | 10.33 | 0.583067E+09 | 877.82 | 31-OCT-13:39 | 15.00 | 10.41 |
November | 0.358900E+10 | 14374.99 | 03-NOV-12:40 | 8.53 | 4.68 | 0.518855E+09 | 848.52 | 06-NOV-10:39 | 8.53 | 4.46 |
December | 0.111521E+10 | 7467.25 | 16-DEC-13:30 | 5.60 | 3.03 | 0.460883E+09 | 845.63 | 04-DEC-14:09 | 5.60 | 3.03 |
Annual Sum or Average | 0.741186E+11 | 0.681440E+10 | ||||||||
Minimum of Months | 0.111521E+10 | 7467.25 | -6.5 | -9.0 | 0.450196E+09 | 845.63 | -5.8 | -8.3 | ||
Maximum of Months | 0.117749E+11 | 24030.68 | 30.00 | 23.06 | 0.684259E+09 | 877.82 | 30.00 | 23.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279680E+09 | 2752.40 | 12-JAN-16:00 | -6.1 | -8.3 | 0.299896E+09 | 414.12 | 06-JAN-14:00 | -6.1 | -8.3 |
February | 0.484180E+09 | 3740.51 | 28-FEB-16:40 | -0.2 | -2.7 | 0.274005E+09 | 511.78 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.270615E+10 | 5936.29 | 21-MAR-16:00 | 4.40 | 1.34 | 0.351287E+09 | 544.94 | 15-MAR-13:00 | 4.40 | 1.34 |
April | 0.402572E+10 | 9926.12 | 24-APR-16:00 | 13.30 | 7.63 | 0.327921E+09 | 544.86 | 20-APR-13:00 | 13.30 | 7.63 |
May | 0.621116E+10 | 17557.65 | 27-MAY-17:05 | 20.32 | 11.21 | 0.387004E+09 | 544.95 | 23-MAY-13:09 | 20.32 | 11.21 |
June | 0.864206E+10 | 21813.69 | 11-JUN-16:42 | 25.60 | 17.82 | 0.414028E+09 | 544.99 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.920073E+10 | 22943.12 | 02-JUL-16:42 | 25.00 | 17.06 | 0.391944E+09 | 544.98 | 03-JUL-13:30 | 25.00 | 16.74 |
August | 0.893512E+10 | 22280.19 | 13-AUG-15:41 | 29.50 | 23.39 | 0.435622E+09 | 545.00 | 02-AUG-13:09 | 29.50 | 23.39 |
September | 0.602467E+10 | 21772.96 | 04-SEP-17:32 | 17.23 | 12.32 | 0.364873E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.369338E+10 | 9154.11 | 11-OCT-16:00 | 21.70 | 14.52 | 0.337335E+09 | 544.93 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.194546E+10 | 5521.26 | 24-NOV-16:15 | 3.87 | 1.42 | 0.308342E+09 | 519.56 | 15-NOV-14:00 | 3.87 | 1.42 |
December | 0.408152E+09 | 3039.33 | 01-DEC-13:40 | 10.17 | 8.68 | 0.289580E+09 | 429.92 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.525565E+11 | 0.418184E+10 | ||||||||
Minimum of Months | 0.279680E+09 | 2752.40 | -6.1 | -8.3 | 0.274005E+09 | 414.12 | -6.1 | -8.3 | ||
Maximum of Months | 0.920073E+10 | 22943.12 | 29.50 | 23.39 | 0.435622E+09 | 545.00 | 29.50 | 23.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21611820.93 | 1979.28 | 14-JAN-17:02 | 3.22 | 2.72 | 0.462505E+09 | 625.92 | 13-JAN-10:30 | 3.22 | 2.72 |
February | 26751189.79 | 1954.66 | 18-FEB-17:03 | 0.82 | -0.6 | 0.418778E+09 | 625.96 | 21-FEB-10:09 | -11.5 | -12.7 |
March | 0.121637E+10 | 5918.56 | 15-MAR-14:50 | 25.68 | 16.21 | 0.528162E+09 | 845.64 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.210755E+10 | 3604.49 | 20-APR-16:00 | 15.00 | 11.00 | 0.484428E+09 | 827.37 | 07-APR-13:00 | 15.00 | 11.00 |
May | 0.433413E+10 | 6542.07 | 23-MAY-14:40 | 23.90 | 13.32 | 0.603808E+09 | 845.63 | 10-MAY-13:39 | 23.90 | 13.32 |
June | 0.742121E+10 | 10997.88 | 26-JUN-05:03 | 20.60 | 16.79 | 0.648811E+09 | 845.68 | 22-JUN-13:09 | 20.60 | 16.79 |
July | 0.889318E+10 | 18038.61 | 16-JUL-15:12 | 29.80 | 22.21 | 0.612727E+09 | 845.63 | 12-JUL-09:00 | 29.80 | 22.21 |
August | 0.804021E+10 | 11676.82 | 14-AUG-03:02 | 23.80 | 22.23 | 0.680823E+09 | 845.69 | 02-AUG-13:09 | 23.80 | 22.23 |
September | 0.469163E+10 | 7044.01 | 15-SEP-14:00 | 25.60 | 21.03 | 0.569353E+09 | 845.68 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.214991E+10 | 3726.66 | 11-OCT-12:30 | 21.95 | 13.79 | 0.506055E+09 | 834.20 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.630693E+09 | 2654.49 | 16-NOV-17:00 | 18.30 | 13.48 | 0.464305E+09 | 706.24 | 16-NOV-14:00 | 18.30 | 13.48 |
December | 67325981.44 | 1962.89 | 02-DEC-17:02 | 2.62 | 1.32 | 0.445815E+09 | 625.97 | 11-DEC-10:20 | -12.9 | -13.3 |
Annual Sum or Average | 0.396006E+11 | 0.642557E+10 | ||||||||
Minimum of Months | 21611820.93 | 1954.66 | 0.82 | -0.6 | 0.418778E+09 | 625.92 | -12.9 | -13.3 | ||
Maximum of Months | 0.889318E+10 | 18038.61 | 29.80 | 22.23 | 0.680823E+09 | 845.69 | 29.80 | 22.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27002544.59 | 2186.03 | 14-JAN-17:02 | 3.22 | 2.72 | 0.298650E+09 | 403.40 | 13-JAN-14:50 | 3.22 | 2.72 |
February | 0.158759E+09 | 2614.14 | 28-FEB-10:10 | -3.6 | -5.3 | 0.271319E+09 | 429.39 | 28-FEB-10:20 | -3.3 | -5.1 |
March | 0.169287E+10 | 4722.37 | 15-MAR-14:00 | 26.10 | 16.06 | 0.343154E+09 | 544.97 | 15-MAR-13:20 | 26.10 | 16.06 |
April | 0.298592E+10 | 7730.67 | 24-APR-09:30 | 6.65 | 3.34 | 0.331153E+09 | 544.96 | 21-APR-13:00 | 6.65 | 3.34 |
May | 0.539973E+10 | 10880.57 | 31-MAY-09:10 | 17.88 | 13.30 | 0.395490E+09 | 544.96 | 10-MAY-13:39 | 17.88 | 13.30 |
June | 0.801196E+10 | 14658.41 | 18-JUN-08:32 | 24.80 | 21.57 | 0.418283E+09 | 545.68 | 12-JUN-09:00 | 24.80 | 21.57 |
July | 0.921630E+10 | 22538.71 | 16-JUL-09:12 | 27.03 | 22.10 | 0.394146E+09 | 545.46 | 13-JUL-09:30 | 27.03 | 22.10 |
August | 0.844624E+10 | 12944.37 | 06-AUG-09:13 | 24.47 | 17.45 | 0.436500E+09 | 545.48 | 10-AUG-09:50 | 27.33 | 20.25 |
September | 0.542954E+10 | 9077.35 | 18-SEP-09:30 | 16.15 | 11.54 | 0.370730E+09 | 544.99 | 12-SEP-13:09 | 16.15 | 11.54 |
October | 0.257816E+10 | 5822.04 | 11-OCT-09:50 | 16.42 | 12.11 | 0.329598E+09 | 544.94 | 11-OCT-09:00 | 16.70 | 12.25 |
November | 0.721563E+09 | 2840.48 | 03-NOV-10:15 | 5.97 | 3.19 | 0.299615E+09 | 453.40 | 03-NOV-09:00 | 5.97 | 3.19 |
December | 56361639.76 | 2446.55 | 21-DEC-06:04 | 1.02 | 0.58 | 0.288054E+09 | 403.39 | 12-DEC-14:09 | 1.02 | 0.58 |
Annual Sum or Average | 0.447244E+11 | 0.417669E+10 | ||||||||
Minimum of Months | 27002544.59 | 2186.03 | -3.6 | -5.3 | 0.271319E+09 | 403.39 | -3.3 | -5.1 | ||
Maximum of Months | 0.921630E+10 | 22538.71 | 27.03 | 22.10 | 0.436500E+09 | 545.68 | 27.33 | 22.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.786315E+09 | 5960.34 | 12-JAN-14:00 | -6.1 | -8.8 | 0.477349E+09 | 845.64 | 12-JAN-14:00 | -5.6 | -8.1 |
February | 0.110091E+10 | 11465.24 | 28-FEB-14:10 | 0.00 | -3.0 | 0.439229E+09 | 845.64 | 28-FEB-14:50 | 0.00 | -2.8 |
March | 0.390833E+10 | 15945.65 | 15-MAR-13:30 | 25.55 | 15.84 | 0.575015E+09 | 846.55 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.440475E+10 | 12475.35 | 24-APR-13:30 | 11.95 | 6.38 | 0.518540E+09 | 845.67 | 21-APR-13:50 | 11.95 | 6.38 |
May | 0.672500E+10 | 11633.29 | 26-MAY-13:40 | 21.13 | 13.64 | 0.606476E+09 | 845.68 | 10-MAY-13:39 | 21.13 | 13.64 |
June | 0.955066E+10 | 15267.08 | 25-JUN-13:52 | 26.10 | 17.70 | 0.641444E+09 | 845.71 | 22-JUN-13:09 | 26.10 | 17.70 |
July | 0.115036E+11 | 25002.51 | 16-JUL-13:12 | 27.57 | 20.80 | 0.608539E+09 | 846.66 | 21-JUL-13:50 | 31.52 | 21.79 |
August | 0.119855E+11 | 24741.59 | 13-AUG-15:12 | 29.80 | 23.30 | 0.677691E+09 | 846.45 | 03-AUG-13:00 | 29.80 | 23.30 |
September | 0.930579E+10 | 25247.70 | 04-SEP-13:32 | 18.33 | 13.04 | 0.581344E+09 | 846.82 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.543393E+10 | 19137.41 | 11-OCT-12:30 | 21.95 | 13.79 | 0.553810E+09 | 846.18 | 11-OCT-13:39 | 22.20 | 14.14 |
November | 0.224385E+10 | 12030.31 | 03-NOV-13:10 | 8.98 | 4.94 | 0.496520E+09 | 845.64 | 01-NOV-13:39 | 8.98 | 4.94 |
December | 0.582520E+09 | 5158.33 | 16-DEC-13:30 | 5.60 | 3.03 | 0.453301E+09 | 841.92 | 04-DEC-14:50 | 5.60 | 3.03 |
Annual Sum or Average | 0.675312E+11 | 0.662926E+10 | ||||||||
Minimum of Months | 0.582520E+09 | 5158.33 | -6.1 | -8.8 | 0.439229E+09 | 841.92 | -5.6 | -8.1 | ||
Maximum of Months | 0.119855E+11 | 25247.70 | 29.80 | 23.30 | 0.677691E+09 | 846.82 | 31.52 | 23.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111914E+09 | 2705.89 | 18-JAN-06:04 | 2.80 | 1.63 | 0.298826E+09 | 403.41 | 31-JAN-10:00 | -11.1 | -12.2 |
February | 0.288612E+09 | 3779.83 | 28-FEB-16:40 | -0.2 | -2.7 | 0.272574E+09 | 492.11 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.210939E+10 | 5980.56 | 15-MAR-14:20 | 25.93 | 16.12 | 0.342965E+09 | 544.95 | 15-MAR-13:00 | 25.93 | 16.12 |
April | 0.329908E+10 | 9545.20 | 19-APR-16:00 | 17.20 | 8.76 | 0.315729E+09 | 544.15 | 20-APR-13:00 | 13.30 | 10.04 |
May | 0.583017E+10 | 17820.86 | 27-MAY-17:05 | 20.32 | 11.21 | 0.372382E+09 | 544.95 | 10-MAY-13:00 | 20.32 | 11.21 |
June | 0.873659E+10 | 23645.88 | 25-JUN-15:52 | 27.80 | 18.29 | 0.407228E+09 | 544.98 | 22-JUN-13:09 | 27.80 | 18.29 |
July | 0.954885E+10 | 24456.05 | 02-JUL-16:42 | 25.00 | 17.06 | 0.388869E+09 | 544.96 | 12-JUL-13:00 | 22.20 | 14.92 |
August | 0.908072E+10 | 23412.70 | 06-AUG-16:32 | 27.80 | 18.98 | 0.429830E+09 | 545.00 | 02-AUG-13:09 | 27.80 | 18.98 |
September | 0.572834E+10 | 21466.55 | 04-SEP-17:32 | 17.23 | 12.32 | 0.352809E+09 | 544.96 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.288902E+10 | 9137.34 | 11-OCT-16:00 | 21.70 | 14.52 | 0.324356E+09 | 544.42 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.107671E+10 | 3651.61 | 15-NOV-15:40 | 11.70 | 6.73 | 0.301905E+09 | 490.83 | 15-NOV-14:00 | 11.70 | 6.73 |
December | 0.170717E+09 | 2762.99 | 04-DEC-15:50 | -0.5 | -3.2 | 0.288336E+09 | 403.41 | 27-DEC-10:50 | -9.6 | -11.2 |
Annual Sum or Average | 0.488701E+11 | 0.409581E+10 | ||||||||
Minimum of Months | 0.111914E+09 | 2705.89 | -0.5 | -3.2 | 0.272574E+09 | 403.41 | -11.1 | -12.2 | ||
Maximum of Months | 0.954885E+10 | 24456.05 | 27.80 | 18.98 | 0.429830E+09 | 545.00 | 27.80 | 18.98 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347743E+09 | 4417.74 | 30-JAN-05:01 | -9.5 | -10.5 | 0.00 | 0.00 | 01-JAN-00:10 | -9.5 | -10.5 |
February | 0.316773E+09 | 3945.19 | 25-FEB-06:01 | -8.4 | -9.2 | 0.00 | 0.00 | 01-FEB-00:10 | -8.4 | -9.2 |
March | 0.220352E+10 | 5804.18 | 16-MAR-05:15 | 13.67 | 11.27 | 0.00 | 0.00 | 01-MAR-00:10 | 13.67 | 11.27 |
April | 0.378058E+10 | 8119.48 | 10-APR-05:13 | 4.07 | 3.41 | 0.00 | 0.00 | 01-APR-00:10 | 4.07 | 3.41 |
May | 0.528231E+10 | 8986.26 | 30-MAY-05:15 | 12.20 | 11.93 | 0.00 | 0.00 | 01-MAY-00:10 | 12.20 | 11.93 |
June | 0.803369E+10 | 8860.33 | 19-JUN-05:15 | 16.70 | 15.97 | 0.00 | 0.00 | 01-JUN-00:10 | 16.70 | 15.97 |
July | 0.962546E+10 | 10975.07 | 17-JUL-05:15 | 22.80 | 21.19 | 0.00 | 0.00 | 01-JUL-00:10 | 22.80 | 21.19 |
August | 0.997620E+10 | 9925.88 | 21-AUG-05:15 | 14.40 | 13.12 | 0.00 | 0.00 | 01-AUG-00:10 | 14.40 | 13.12 |
September | 0.640712E+10 | 9654.05 | 18-SEP-05:15 | 9.60 | 8.73 | 0.00 | 0.00 | 01-SEP-00:10 | 9.60 | 8.73 |
October | 0.400027E+10 | 8060.99 | 23-OCT-05:13 | 11.70 | 10.06 | 0.00 | 0.00 | 01-OCT-00:10 | 11.70 | 10.06 |
November | 0.267641E+10 | 5860.58 | 06-NOV-06:10 | 8.90 | 6.87 | 0.00 | 0.00 | 01-NOV-00:10 | 8.90 | 6.87 |
December | 0.648210E+09 | 3363.90 | 01-DEC-06:10 | 10.10 | 8.62 | 0.00 | 0.00 | 01-DEC-00:10 | 10.10 | 8.62 |
Annual Sum or Average | 0.532983E+11 | 0.00 | ||||||||
Minimum of Months | 0.316773E+09 | 3363.90 | -9.5 | -10.5 | 0.00 | 0.00 | -9.5 | -10.5 | ||
Maximum of Months | 0.997620E+10 | 10975.07 | 22.80 | 21.19 | 0.00 | 0.00 | 22.80 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315992E+09 | 6179.44 | 23-JAN-04:01 | -2.0 | -3.6 | 0.00 | 0.00 | 01-JAN-00:10 | -2.0 | -3.6 |
February | 0.261390E+09 | 5922.25 | 05-FEB-21:51 | -12.8 | -13.7 | 0.00 | 0.00 | 01-FEB-00:10 | -12.8 | -13.7 |
March | 0.871124E+09 | 6715.08 | 04-MAR-05:01 | -10.1 | -11.1 | 0.00 | 0.00 | 01-MAR-00:10 | -10.1 | -11.1 |
April | 0.153090E+10 | 5048.88 | 17-APR-04:01 | -3.4 | -5.0 | 0.00 | 0.00 | 01-APR-00:10 | -3.4 | -5.0 |
May | 0.342369E+10 | 5595.91 | 30-MAY-05:10 | 12.20 | 11.93 | 0.00 | 0.00 | 01-MAY-00:10 | 12.20 | 11.93 |
June | 0.594288E+10 | 6365.59 | 27-JUN-16:00 | 26.10 | 22.53 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 22.53 |
July | 0.736885E+10 | 8705.83 | 18-JUL-05:13 | 17.40 | 17.08 | 0.00 | 0.00 | 01-JUL-00:10 | 17.40 | 17.08 |
August | 0.732167E+10 | 9068.21 | 07-AUG-05:03 | 20.10 | 18.54 | 0.00 | 0.00 | 01-AUG-00:10 | 20.10 | 18.54 |
September | 0.472485E+10 | 6812.15 | 18-SEP-05:15 | 9.60 | 8.73 | 0.00 | 0.00 | 01-SEP-00:10 | 9.60 | 8.73 |
October | 0.195143E+10 | 5261.77 | 05-OCT-05:10 | 8.80 | 8.23 | 0.00 | 0.00 | 01-OCT-00:10 | 8.80 | 8.23 |
November | 0.691991E+09 | 6041.33 | 24-NOV-05:11 | -3.2 | -3.9 | 0.00 | 0.00 | 01-NOV-00:10 | -3.2 | -3.9 |
December | 0.298942E+09 | 6406.33 | 10-DEC-05:32 | -13.3 | -13.7 | 0.00 | 0.00 | 01-DEC-00:10 | -13.3 | -13.7 |
Annual Sum or Average | 0.347037E+11 | 0.00 | ||||||||
Minimum of Months | 0.261390E+09 | 5048.88 | -13.3 | -13.7 | 0.00 | 0.00 | -13.3 | -13.7 | ||
Maximum of Months | 0.736885E+10 | 9068.21 | 26.10 | 22.53 | 0.00 | 0.00 | 26.10 | 22.53 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
March | 0.701614E+09 | 11062.47 | 15-MAR-14:00 | 26.10 | 16.06 | 0.00 | 0.00 | 01-MAR-00:10 | 26.10 | 16.06 |
April | 0.190710E+10 | 8593.94 | 21-APR-14:30 | 14.70 | 8.36 | 0.00 | 0.00 | 01-APR-00:10 | 14.70 | 8.36 |
May | 0.535232E+10 | 13642.47 | 31-MAY-14:30 | 21.70 | 14.07 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 14.07 |
June | 0.102887E+11 | 18836.69 | 12-JUN-13:50 | 30.40 | 20.15 | 0.00 | 0.00 | 01-JUN-00:10 | 30.40 | 20.15 |
July | 0.126347E+11 | 19538.43 | 21-JUL-13:50 | 31.52 | 21.79 | 0.00 | 0.00 | 01-JUL-00:10 | 31.52 | 21.79 |
August | 0.111116E+11 | 18242.86 | 09-AUG-15:20 | 29.40 | 18.24 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.24 |
September | 0.561194E+10 | 13791.00 | 21-SEP-15:40 | 26.10 | 17.00 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.00 |
October | 0.121175E+10 | 7532.38 | 11-OCT-15:30 | 21.95 | 14.56 | 0.00 | 0.00 | 01-OCT-00:10 | 21.95 | 14.56 |
November | 83698472.16 | 2004.90 | 04-NOV-16:20 | 17.93 | 13.33 | 0.00 | 0.00 | 01-NOV-00:10 | 17.93 | 13.33 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.489034E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 0.00 | 0.00 | -3.3 | -4.7 | ||
Maximum of Months | 0.126347E+11 | 19538.43 | 31.52 | 21.79 | 0.00 | 0.00 | 31.52 | 21.79 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218975E+10 | 1880.84 | 12-JAN-16:40 | -6.5 | -8.3 | 95230017.63 | 126.82 | 12-JAN-10:39 | -6.5 | -8.3 |
February | 0.683105E+10 | 4136.19 | 28-FEB-17:00 | -0.6 | -3.0 | 86396473.38 | 126.82 | 16-FEB-14:09 | -0.6 | -3.0 |
March | 0.138688E+11 | 6988.87 | 31-MAR-24:00 | 4.20 | 3.93 | 0.103237E+09 | 126.83 | 14-MAR-09:00 | 4.20 | 3.93 |
April | 0.187629E+11 | 8047.93 | 24-APR-18:00 | 11.70 | 8.10 | 91605141.61 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.435924E+10 | 3498.46 | 31-MAY-24:00 | 17.10 | 14.03 | 99236154.08 | 126.85 | 17-MAY-13:50 | 17.10 | 14.03 |
June | 0.943079E+10 | 5372.64 | 30-JUN-24:00 | 16.90 | 13.02 | 98966935.70 | 126.86 | 21-JUN-09:00 | 16.90 | 13.02 |
July | 0.148191E+11 | 7254.26 | 31-JUL-23:50 | 19.37 | 17.14 | 91888684.43 | 126.84 | 05-JUL-13:09 | 19.37 | 17.14 |
August | 0.198442E+11 | 8166.74 | 04-AUG-18:30 | 26.95 | 16.52 | 0.103238E+09 | 126.83 | 30-AUG-09:00 | 17.80 | 17.48 |
September | 0.432653E+10 | 3189.40 | 30-SEP-24:00 | 14.40 | 12.09 | 91611595.00 | 126.86 | 13-SEP-13:30 | 14.40 | 12.09 |
October | 0.912181E+10 | 5148.81 | 31-OCT-24:00 | 6.60 | 4.77 | 95232287.15 | 126.84 | 12-OCT-13:20 | 6.60 | 4.77 |
November | 0.135119E+11 | 5872.37 | 24-NOV-16:10 | 4.13 | 1.57 | 94300296.36 | 126.82 | 10-NOV-14:00 | 4.13 | 1.57 |
December | 0.183703E+11 | 7723.23 | 04-DEC-16:10 | -0.9 | -3.5 | 91880872.81 | 126.82 | 01-DEC-14:09 | -0.9 | -3.5 |
Annual Sum or Average | 0.135436E+12 | 0.114282E+10 | ||||||||
Minimum of Months | 0.218975E+10 | 1880.84 | -6.5 | -8.3 | 86396473.38 | 126.82 | -6.5 | -8.3 | ||
Maximum of Months | 0.198442E+11 | 8166.74 | 26.95 | 17.14 | 0.103238E+09 | 126.86 | 19.37 | 17.48 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415342E+09 | 1437.05 | 12-JAN-16:40 | -6.5 | -8.3 | 93551181.67 | 126.82 | 12-JAN-10:39 | -6.5 | -8.3 |
February | 0.411997E+10 | 3561.83 | 28-FEB-17:00 | -0.6 | -3.0 | 86396479.65 | 126.82 | 16-FEB-14:09 | -0.6 | -3.0 |
March | 0.114038E+11 | 6102.35 | 31-MAR-24:00 | 4.20 | 3.93 | 0.103237E+09 | 126.83 | 14-MAR-09:09 | 4.20 | 3.93 |
April | 0.166563E+11 | 7584.51 | 24-APR-18:00 | 11.70 | 8.10 | 91605165.81 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.354482E+10 | 3280.01 | 31-MAY-24:00 | 17.10 | 14.03 | 99235658.05 | 126.84 | 24-MAY-09:00 | 17.10 | 14.03 |
June | 0.873315E+10 | 5157.73 | 30-JUN-24:00 | 16.90 | 13.02 | 98966859.85 | 126.86 | 27-JUN-13:00 | 16.90 | 13.02 |
July | 0.140616E+11 | 7014.40 | 31-JUL-23:55 | 19.10 | 16.93 | 91889631.05 | 126.85 | 05-JUL-13:00 | 19.10 | 16.93 |
August | 0.188135E+11 | 7795.02 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103239E+09 | 126.83 | 30-AUG-13:50 | 19.72 | 18.42 |
September | 0.356882E+10 | 2606.58 | 30-SEP-24:00 | 14.40 | 12.09 | 91609570.81 | 126.85 | 08-SEP-13:00 | 14.40 | 12.09 |
October | 0.732991E+10 | 4392.32 | 31-OCT-24:00 | 6.60 | 4.77 | 95232083.80 | 126.84 | 26-OCT-09:00 | 6.60 | 4.77 |
November | 0.109949E+11 | 5353.78 | 15-NOV-16:20 | 10.93 | 6.40 | 94300316.39 | 126.82 | 10-NOV-14:00 | 10.93 | 6.40 |
December | 0.146153E+11 | 6854.36 | 04-DEC-16:20 | -1.1 | -3.7 | 91880881.59 | 126.82 | 01-DEC-14:09 | -1.1 | -3.7 |
Annual Sum or Average | 0.114257E+12 | 0.114114E+10 | ||||||||
Minimum of Months | 0.415342E+09 | 1437.05 | -6.5 | -8.3 | 86396479.65 | 126.82 | -6.5 | -8.3 | ||
Maximum of Months | 0.188135E+11 | 7795.02 | 22.07 | 16.93 | 0.103239E+09 | 126.86 | 19.72 | 18.42 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177262E+09 | 1191.43 | 12-JAN-16:30 | -6.4 | -8.3 | 89673426.55 | 126.82 | 11-JAN-14:00 | -6.4 | -8.3 |
February | 0.276288E+10 | 3496.33 | 28-FEB-17:00 | -0.6 | -3.0 | 86395594.13 | 126.82 | 16-FEB-14:09 | -0.6 | -3.0 |
March | 0.985017E+10 | 5688.03 | 31-MAR-23:20 | 4.60 | 4.18 | 0.103237E+09 | 126.83 | 14-MAR-09:20 | 4.60 | 4.18 |
April | 0.155788E+11 | 7575.61 | 24-APR-18:00 | 11.70 | 8.10 | 91605170.52 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.304503E+10 | 3178.53 | 31-MAY-24:00 | 17.10 | 14.03 | 99235621.49 | 126.84 | 24-MAY-09:00 | 17.10 | 14.03 |
June | 0.861858E+10 | 5087.99 | 30-JUN-24:00 | 16.90 | 13.02 | 98967003.32 | 126.86 | 27-JUN-13:00 | 16.90 | 13.02 |
July | 0.140785E+11 | 7009.13 | 31-JUL-23:55 | 19.10 | 16.93 | 91889550.84 | 126.85 | 05-JUL-13:00 | 19.10 | 16.93 |
August | 0.187554E+11 | 7849.40 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103239E+09 | 126.83 | 30-AUG-09:00 | 17.80 | 17.48 |
September | 0.313433E+10 | 2219.19 | 11-SEP-17:40 | 17.57 | 11.79 | 91609269.78 | 126.85 | 08-SEP-13:00 | 17.57 | 11.79 |
October | 0.596026E+10 | 3991.04 | 31-OCT-23:20 | 6.87 | 4.91 | 95232042.49 | 126.83 | 12-OCT-13:00 | 6.87 | 4.91 |
November | 0.928102E+10 | 5229.54 | 15-NOV-16:30 | 10.55 | 6.20 | 94300314.49 | 126.82 | 10-NOV-14:00 | 10.55 | 6.20 |
December | 0.127572E+11 | 6490.87 | 04-DEC-16:20 | -1.1 | -3.7 | 91880884.81 | 126.82 | 01-DEC-14:09 | -1.1 | -3.7 |
Annual Sum or Average | 0.104000E+12 | 0.113727E+10 | ||||||||
Minimum of Months | 0.177262E+09 | 1191.43 | -6.4 | -8.3 | 86395594.13 | 126.82 | -6.4 | -8.3 | ||
Maximum of Months | 0.187554E+11 | 7849.40 | 22.07 | 16.93 | 0.103239E+09 | 126.86 | 19.10 | 17.48 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234955E+12 | 91026.33 | 19-JAN-17:00 | 0.60 | -0.1 | 0.206152E+10 | 2746.77 | 20-JAN-10:00 | -1.7 | -2.7 |
February | 0.432343E+12 | 182619.45 | 23-FEB-17:00 | -0.6 | -1.8 | 0.187142E+10 | 2749.36 | 06-FEB-10:09 | -0.6 | -1.8 |
March | 0.727348E+12 | 358188.08 | 31-MAR-24:00 | 4.20 | 3.93 | 0.223586E+10 | 2748.92 | 06-MAR-10:09 | 4.20 | 3.93 |
April | 0.942098E+12 | 367506.02 | 21-APR-16:00 | 13.30 | 8.77 | 0.198329E+10 | 2747.98 | 17-APR-13:00 | 13.30 | 8.77 |
May | 0.240181E+12 | 175939.15 | 31-MAY-24:00 | 17.10 | 14.03 | 0.214825E+10 | 2746.24 | 17-MAY-13:50 | 17.10 | 14.03 |
June | 0.470631E+12 | 268034.09 | 30-JUN-24:00 | 16.90 | 13.02 | 0.214239E+10 | 2746.41 | 14-JUN-13:09 | 16.90 | 13.02 |
July | 0.732516E+12 | 360155.42 | 31-JUL-23:55 | 19.10 | 16.93 | 0.198911E+10 | 2745.80 | 05-JUL-13:00 | 19.10 | 16.93 |
August | 0.977657E+12 | 369891.16 | 04-AUG-21:02 | 21.52 | 16.10 | 0.231509E+10 | 3247.36 | 10-AUG-13:00 | 30.60 | 20.24 |
September | 0.236043E+12 | 175347.70 | 30-SEP-24:00 | 14.40 | 12.09 | 0.198325E+10 | 2746.55 | 14-SEP-13:00 | 14.40 | 12.09 |
October | 0.486903E+12 | 268301.21 | 31-OCT-24:00 | 6.60 | 4.77 | 0.206165E+10 | 2747.46 | 17-OCT-13:09 | 6.60 | 4.77 |
November | 0.707624E+12 | 276617.62 | 06-NOV-17:00 | 6.10 | 3.25 | 0.204169E+10 | 2747.10 | 22-NOV-10:09 | 1.10 | -1.2 |
December | 0.973552E+12 | 367281.17 | 15-DEC-17:00 | 2.80 | 1.83 | 0.199035E+10 | 2749.52 | 26-DEC-10:09 | -11.9 | -13.2 |
Annual Sum or Average | 0.716185E+13 | 0.248239E+11 | ||||||||
Minimum of Months | 0.234955E+12 | 91026.33 | -0.6 | -1.8 | 0.187142E+10 | 2745.80 | -11.9 | -13.2 | ||
Maximum of Months | 0.977657E+12 | 369891.16 | 21.52 | 16.93 | 0.231509E+10 | 3247.36 | 30.60 | 20.24 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52384935.41 | 11455.55 | 23-JAN-05:03 | -3.4 |
February | 58051583.38 | 11563.55 | 21-FEB-04:03 | -11.2 |
March | 0.125875E+09 | 12121.59 | 13-MAR-03:15 | 11.83 |
April | 0.124085E+09 | 11985.32 | 29-APR-04:05 | 7.20 |
May | 0.215909E+09 | 13472.19 | 29-MAY-11:02 | 18.80 |
June | 0.257473E+09 | 13982.79 | 17-JUN-16:25 | 28.60 |
July | 0.348131E+09 | 13527.57 | 31-JUL-02:62 | 18.80 |
August | 0.361953E+09 | 13748.59 | 31-AUG-03:53 | 11.70 |
September | 0.538312E+09 | 12402.96 | 11-SEP-03:25 | 10.85 |
October | 0.378596E+09 | 12219.54 | 02-OCT-03:25 | 8.60 |
November | 0.296166E+09 | 11866.26 | 28-NOV-04:04 | 4.40 |
December | 0.100014E+09 | 11522.38 | 26-DEC-04:04 | -11.8 |
Annual Sum or Average | 0.285695E+10 | |||
Minimum of Months | 52384935.41 | 11455.55 | -11.8 | |
Maximum of Months | 0.538312E+09 | 13982.79 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.750738E+09 | 54978.18 | 02-JAN-04:11 | -0.9 |
February | 0.222236E+09 | 47799.59 | 06-FEB-05:11 | -14.6 |
March | 11133536.51 | 44122.55 | 06-MAR-06:03 | -11.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.206237E+09 | 49416.48 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.119034E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.750738E+09 | 54978.18 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.535082E+10 | 80765.44 | 02-JAN-04:01 | -1.0 |
February | 0.454317E+10 | 80716.64 | 06-FEB-04:01 | -15.0 |
March | 0.170439E+10 | 77447.24 | 06-MAR-04:01 | -11.1 |
April | 0.345292E+09 | 73294.72 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.293910E+09 | 70705.89 | 30-OCT-04:01 | -0.5 |
November | 0.863377E+09 | 73194.57 | 24-NOV-05:01 | -3.0 |
December | 0.415347E+10 | 80741.63 | 26-DEC-04:11 | -11.9 |
Annual Sum or Average | 0.172544E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.535082E+10 | 80765.44 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.561637E+09 | 12201.22 | 30-JAN-05:01 | -9.5 |
February | 0.491152E+09 | 12374.98 | 07-FEB-05:01 | -15.7 |
March | 48978725.61 | 11356.71 | 06-MAR-05:01 | -11.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.162354E+09 | 11604.01 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.126412E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.561637E+09 | 12374.98 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.436450E+09 | 12607.46 | 30-JAN-05:01 | -9.5 |
February | 0.417631E+09 | 12700.89 | 07-FEB-05:01 | -15.7 |
March | 35707997.99 | 11611.80 | 06-MAR-05:01 | -11.1 |
April | 205069.61 | 2101.54 | 05-APR-05:01 | 1.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 53781.34 | 627.45 | 17-OCT-05:04 | -2.8 |
November | 639272.45 | 4924.74 | 25-NOV-06:01 | -1.7 |
December | 0.256607E+09 | 12139.27 | 28-DEC-05:01 | -11.8 |
Annual Sum or Average | 0.114729E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.7 | |
Maximum of Months | 0.436450E+09 | 12700.89 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.819823E+09 | 17898.68 | 24-JAN-05:01 | -11.8 |
February | 0.809923E+09 | 18908.01 | 06-FEB-04:01 | -15.0 |
March | 82833445.48 | 16784.38 | 06-MAR-05:01 | -11.1 |
April | 3287512.69 | 6742.11 | 17-APR-05:03 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 910867.98 | 5929.22 | 30-OCT-05:02 | -0.1 |
November | 8057444.27 | 11241.58 | 24-NOV-06:03 | -3.8 |
December | 0.380550E+09 | 17330.30 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.210538E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.819823E+09 | 18908.01 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89414163.74 | 10510.86 | 30-JAN-05:01 | -9.5 |
February | 59227144.24 | 10619.45 | 07-FEB-05:01 | -15.7 |
March | 340513.27 | 2270.09 | 06-MAR-06:03 | -11.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 4716631.60 | 7236.57 | 28-DEC-06:01 | -12.2 |
Annual Sum or Average | 0.153698E+09 | |||
Minimum of Months | 0.00 | 0.00 | -15.7 | |
Maximum of Months | 89414163.74 | 10619.45 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.624831E+10 | 13385.01 | 29-JAN-18:32 | -6.5 |
February | 0.549369E+10 | 13955.11 | 13-FEB-03:42 | -8.9 |
March | 0.178867E+10 | 13157.30 | 06-MAR-03:42 | -11.0 |
April | 0.209408E+09 | 11937.16 | 17-APR-03:01 | -2.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.115863E+09 | 11246.50 | 30-OCT-04:01 | -0.5 |
November | 0.599261E+09 | 11693.60 | 24-NOV-05:11 | -3.2 |
December | 0.502485E+10 | 13409.61 | 26-DEC-03:42 | -11.7 |
Annual Sum or Average | 0.194801E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.7 | |
Maximum of Months | 0.624831E+10 | 13955.11 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369149E+10 | 17606.64 | 09-JAN-01:51 | -8.3 |
February | 0.327427E+10 | 18339.28 | 13-FEB-03:42 | -8.9 |
March | 0.772720E+09 | 16849.74 | 06-MAR-04:01 | -11.1 |
April | 0.106984E+09 | 15522.52 | 17-APR-04:01 | -3.4 |
May | 44735.14 | 193.21 | 12-MAY-05:05 | 8.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 35915.38 | 239.44 | 30-SEP-05:03 | 7.20 |
October | 71376141.62 | 14914.94 | 30-OCT-04:01 | -0.5 |
November | 0.389371E+09 | 15547.44 | 24-NOV-05:11 | -3.2 |
December | 0.326272E+10 | 17703.38 | 11-DEC-04:11 | -17.2 |
Annual Sum or Average | 0.115690E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.369149E+10 | 18339.28 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405249E+10 | 19761.28 | 02-JAN-04:11 | -0.9 |
February | 0.378027E+10 | 20804.38 | 13-FEB-03:42 | -8.9 |
March | 0.734148E+09 | 18815.16 | 06-MAR-04:01 | -11.1 |
April | 0.154403E+09 | 17236.87 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 51470460.70 | 16392.61 | 30-OCT-04:01 | -0.5 |
November | 0.410707E+09 | 17433.62 | 24-NOV-05:11 | -3.2 |
December | 0.341458E+10 | 19930.21 | 26-DEC-03:42 | -11.7 |
Annual Sum or Average | 0.125981E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.7 | |
Maximum of Months | 0.405249E+10 | 20804.38 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319491E+10 | 18315.29 | 24-JAN-04:11 | -11.7 |
February | 0.267397E+10 | 18935.89 | 13-FEB-03:42 | -8.9 |
March | 0.580797E+09 | 17622.91 | 06-MAR-04:01 | -11.1 |
April | 64721729.27 | 15431.12 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 6622.65 | 55.19 | 29-SEP-05:04 | 10.50 |
October | 40868933.80 | 14405.47 | 17-OCT-05:01 | -2.8 |
November | 0.261233E+09 | 16013.40 | 24-NOV-05:11 | -3.2 |
December | 0.238506E+10 | 18334.65 | 11-DEC-04:11 | -17.2 |
Annual Sum or Average | 0.920157E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.319491E+10 | 18935.89 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119908E+11 | 17270.99 | 09-JAN-02:42 | -9.2 |
February | 0.108092E+11 | 17316.51 | 12-FEB-22:02 | -8.3 |
March | 0.503153E+10 | 16799.23 | 06-MAR-03:42 | -11.0 |
April | 0.127784E+10 | 15968.94 | 16-APR-07:13 | -3.5 |
May | 36467216.42 | 12609.74 | 01-MAY-05:03 | 1.70 |
June | 122603.81 | 817.36 | 14-JUN-05:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 34675926.65 | 12749.10 | 29-SEP-05:02 | 10.50 |
October | 0.972797E+09 | 15719.46 | 30-OCT-03:11 | -0.2 |
November | 0.280583E+10 | 15813.38 | 13-NOV-04:01 | 5.50 |
December | 0.109128E+11 | 17703.29 | 26-DEC-05:31 | -12.2 |
Annual Sum or Average | 0.438721E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.119908E+11 | 17703.29 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.721264E+10 | 18959.08 | 09-JAN-02:42 | -9.2 |
February | 0.648981E+10 | 19043.97 | 12-FEB-22:02 | -8.3 |
March | 0.235070E+10 | 18297.73 | 06-MAR-03:42 | -11.0 |
April | 0.603086E+09 | 17039.20 | 17-APR-03:01 | -2.9 |
May | 16968907.50 | 10502.36 | 01-MAY-05:03 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 23097074.99 | 14059.26 | 29-SEP-05:02 | 10.50 |
October | 0.521733E+09 | 17380.64 | 30-OCT-03:11 | -0.2 |
November | 0.165389E+10 | 17303.11 | 13-NOV-04:01 | 5.50 |
December | 0.698349E+10 | 19017.57 | 25-DEC-20:52 | -9.4 |
Annual Sum or Average | 0.258554E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.0 | |
Maximum of Months | 0.721264E+10 | 19043.97 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.860543E+10 | 22818.85 | 09-JAN-02:42 | -9.2 |
February | 0.817867E+10 | 23072.53 | 07-FEB-03:02 | -15.7 |
March | 0.272711E+10 | 21907.77 | 06-MAR-03:42 | -11.0 |
April | 0.945597E+09 | 20704.51 | 17-APR-03:01 | -2.9 |
May | 31595631.65 | 14015.60 | 12-MAY-05:03 | 8.90 |
June | 1130069.69 | 5952.53 | 14-JUN-05:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 24791747.72 | 16997.37 | 29-SEP-05:02 | 10.50 |
October | 0.577792E+09 | 20921.47 | 30-OCT-03:11 | -0.2 |
November | 0.197363E+10 | 20736.21 | 24-NOV-04:01 | -3.2 |
December | 0.831183E+10 | 23025.10 | 26-DEC-05:31 | -12.2 |
Annual Sum or Average | 0.313776E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.7 | |
Maximum of Months | 0.860543E+10 | 23072.53 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.652350E+10 | 20848.25 | 09-JAN-02:42 | -9.2 |
February | 0.545676E+10 | 20824.40 | 07-FEB-03:02 | -15.7 |
March | 0.185994E+10 | 19037.23 | 27-MAR-03:01 | -6.0 |
April | 0.422628E+09 | 18712.77 | 17-APR-03:01 | -2.9 |
May | 4837328.15 | 7648.27 | 12-MAY-05:03 | 8.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 12652979.79 | 12438.74 | 29-SEP-05:02 | 10.50 |
October | 0.361171E+09 | 18562.97 | 30-OCT-03:11 | -0.2 |
November | 0.116201E+10 | 18803.87 | 24-NOV-04:01 | -3.2 |
December | 0.535552E+10 | 20634.38 | 26-DEC-04:11 | -11.9 |
Annual Sum or Average | 0.211590E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.7 | |
Maximum of Months | 0.652350E+10 | 20848.25 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129597E+10 | 13454.89 | 11-JAN-06:01 | 5.68 |
February | 0.152467E+10 | 15812.52 | 15-FEB-06:01 | 5.60 |
March | 0.413435E+09 | 14661.60 | 02-MAR-06:01 | 1.10 |
April | 0.134786E+09 | 12887.28 | 20-APR-03:02 | 12.12 |
May | 90189996.02 | 10204.93 | 01-MAY-03:02 | 4.48 |
June | 91695370.21 | 10518.10 | 05-JUN-03:02 | 15.82 |
July | 0.126640E+09 | 8849.15 | 06-JUL-03:02 | 13.12 |
August | 0.115179E+09 | 10756.34 | 31-AUG-03:02 | 12.12 |
September | 70521245.88 | 10785.25 | 01-SEP-03:02 | 15.43 |
October | 92572790.95 | 11832.75 | 23-OCT-03:02 | 15.63 |
November | 72572223.82 | 13427.40 | 27-NOV-04:02 | 17.30 |
December | 0.701836E+09 | 15081.33 | 14-DEC-05:09 | 5.60 |
Annual Sum or Average | 0.473007E+10 | |||
Minimum of Months | 70521245.88 | 8849.15 | 1.10 | |
Maximum of Months | 0.152467E+10 | 15812.52 | 17.30 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.567555E+10 | 17462.42 | 02-JAN-06:02 | -1.1 |
February | 0.475599E+10 | 12058.98 | 06-FEB-06:12 | -13.9 |
March | 0.189741E+10 | 8269.32 | 15-MAR-05:03 | 15.00 |
April | 0.507382E+09 | 8159.23 | 20-APR-05:03 | 10.63 |
May | 70479080.16 | 7822.90 | 30-MAY-03:02 | 12.20 |
June | 54318667.19 | 6897.92 | 13-JUN-04:03 | 9.82 |
July | 57403026.10 | 7863.59 | 20-JUL-03:02 | 25.50 |
August | 48758351.93 | 7741.18 | 14-AUG-03:02 | 23.80 |
September | 51882826.89 | 7099.00 | 29-SEP-05:02 | 10.50 |
October | 0.279080E+09 | 8418.28 | 12-OCT-05:02 | 13.40 |
November | 0.683554E+09 | 8572.05 | 16-NOV-06:03 | 11.78 |
December | 0.397278E+10 | 9167.90 | 11-DEC-06:05 | -18.5 |
Annual Sum or Average | 0.180546E+11 | |||
Minimum of Months | 48758351.93 | 6897.92 | -18.5 | |
Maximum of Months | 0.567555E+10 | 17462.42 | 25.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162220E+11 | 28026.09 | 30-JAN-05:19 | -9.6 |
February | 0.142577E+11 | 30933.81 | 06-FEB-05:10 | -14.8 |
March | 0.706830E+10 | 28273.49 | 06-MAR-05:12 | -11.1 |
April | 0.258207E+10 | 21805.00 | 17-APR-04:12 | -3.5 |
May | 0.507201E+09 | 18297.30 | 23-MAY-05:03 | 7.38 |
June | 0.151391E+09 | 18348.15 | 06-JUN-05:03 | 6.78 |
July | 82661200.69 | 14641.40 | 07-JUL-05:02 | 12.30 |
August | 0.101736E+09 | 15327.07 | 03-AUG-05:02 | 11.10 |
September | 0.376714E+09 | 18231.40 | 06-SEP-05:02 | 6.10 |
October | 0.221964E+10 | 17511.88 | 30-OCT-05:02 | -0.1 |
November | 0.541667E+10 | 22704.48 | 24-NOV-05:11 | -3.2 |
December | 0.149985E+11 | 30378.28 | 26-DEC-05:10 | -12.2 |
Annual Sum or Average | 0.639845E+11 | |||
Minimum of Months | 82661200.69 | 14641.40 | -14.8 | |
Maximum of Months | 0.162220E+11 | 30933.81 | 12.30 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.586799E+09 | 560.38 | 24-JAN-02:00 | -11.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.586799E+09 | |||
Minimum of Months | 0.00 | 0.00 | -11.1 | |
Maximum of Months | 0.586799E+09 | 560.38 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.781037E+09 | 605.18 | 15-JAN-18:05 | 0.92 |
February | 0.146818E+09 | 557.74 | 05-FEB-20:20 | -11.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.927856E+09 | |||
Minimum of Months | 0.00 | 0.00 | -11.3 | |
Maximum of Months | 0.781037E+09 | 605.18 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200626E+11 | 20994.62 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.181982E+11 | 20994.62 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.216246E+11 | 20994.62 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.193152E+11 | 20994.62 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.208436E+11 | 20994.62 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.207428E+11 | 20994.62 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.194159E+11 | 20994.62 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.216246E+11 | 20994.62 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.193152E+11 | 20994.62 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.200626E+11 | 20994.62 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.198274E+11 | 20994.62 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.194159E+11 | 20994.62 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.240449E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.181982E+11 | 20994.62 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.216246E+11 | 20994.62 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180176E+11 | 18854.65 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.163433E+11 | 18854.65 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.194204E+11 | 18854.65 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.173464E+11 | 18854.65 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.187190E+11 | 18854.65 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.186285E+11 | 18854.65 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.174369E+11 | 18854.65 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.194204E+11 | 18854.65 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.173464E+11 | 18854.65 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.180176E+11 | 18854.65 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.178064E+11 | 18854.65 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.174369E+11 | 18854.65 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.215940E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.163433E+11 | 18854.65 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.194204E+11 | 18854.65 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.166633E+10 | 2367.39 | 02-JAN-16:49 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.145337E+10 | 2141.31 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166008E+10 | 1853.94 | 17-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.145159E+10 | 1656.79 | 12-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.153991E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.151941E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.142938E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.160340E+10 | 1454.29 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.147168E+10 | 1801.80 | 26-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.158087E+10 | 2311.32 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.165836E+10 | 2367.39 | 06-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.164881E+10 | 2367.39 | 01-DEC-16:40 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.186832E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.142938E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166633E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106446E+10 | 1525.64 | 02-JAN-16:49 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.934484E+09 | 1390.00 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.106845E+10 | 1098.84 | 17-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.936607E+09 | 937.20 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.995733E+09 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.982591E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.924071E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.103643E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.947948E+09 | 1061.27 | 26-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.101334E+10 | 1407.60 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.106164E+10 | 1525.64 | 06-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.105175E+10 | 1525.64 | 01-DEC-16:40 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120175E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.924071E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.106845E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.163269E+10 | 2367.44 | 02-JAN-16:49 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.144090E+10 | 2106.95 | 01-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.165301E+10 | 1816.25 | 17-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145361E+10 | 1646.25 | 12-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.154547E+10 | 1454.32 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.152545E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.143482E+10 | 1454.32 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.160735E+10 | 1454.32 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147039E+10 | 1773.15 | 26-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.156551E+10 | 2125.78 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.163171E+10 | 2367.44 | 06-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.161671E+10 | 2367.44 | 01-DEC-16:40 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.185776E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.143482E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.165301E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106279E+10 | 1525.64 | 02-JAN-16:49 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.932201E+09 | 1375.80 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.106778E+10 | 1241.41 | 17-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.936438E+09 | 1124.49 | 12-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.993524E+09 | 937.20 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.980384E+09 | 937.20 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.922599E+09 | 937.20 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103407E+10 | 937.20 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.949052E+09 | 1208.60 | 26-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.101744E+10 | 1490.32 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.105966E+10 | 1525.64 | 06-NOV-16:00 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.105229E+10 | 1525.64 | 01-DEC-16:40 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.120082E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.922599E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.106778E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.166936E+10 | 2367.39 | 02-JAN-16:49 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.145494E+10 | 2148.10 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166141E+10 | 1869.43 | 17-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.145228E+10 | 1677.85 | 12-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.154064E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.152022E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.142974E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.160403E+10 | 1454.29 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.147273E+10 | 1818.58 | 26-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.158289E+10 | 2313.40 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.166087E+10 | 2367.39 | 06-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.165197E+10 | 2367.39 | 01-DEC-16:40 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.187011E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.142974E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166936E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106500E+10 | 1525.64 | 02-JAN-16:49 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.934765E+09 | 1391.10 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.106873E+10 | 1105.64 | 17-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.936741E+09 | 937.20 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.995957E+09 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.982740E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.924249E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.103663E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.948137E+09 | 1068.71 | 26-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.101377E+10 | 1409.44 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.106217E+10 | 1525.64 | 06-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.105243E+10 | 1525.64 | 01-DEC-16:40 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120213E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.924249E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.106873E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.163504E+10 | 2367.44 | 02-JAN-16:49 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.144290E+10 | 2115.41 | 01-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.165391E+10 | 1833.38 | 17-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145430E+10 | 1667.68 | 12-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.154627E+10 | 1454.32 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.152604E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.143544E+10 | 1454.32 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.160818E+10 | 1454.32 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147135E+10 | 1791.07 | 26-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.156725E+10 | 2230.30 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.163479E+10 | 2367.44 | 06-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.161886E+10 | 2367.44 | 01-DEC-16:40 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.185943E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.143544E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.165391E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106358E+10 | 1525.64 | 02-JAN-16:49 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.932563E+09 | 1376.98 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.106805E+10 | 1243.63 | 17-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.936704E+09 | 1127.53 | 12-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.993693E+09 | 937.20 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.980503E+09 | 937.20 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.922761E+09 | 937.20 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103430E+10 | 937.20 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.949360E+09 | 1211.03 | 26-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.101781E+10 | 1491.11 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.106023E+10 | 1525.64 | 06-NOV-16:00 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.105279E+10 | 1525.64 | 01-DEC-16:40 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.120124E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.922761E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.106805E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.166934E+10 | 2367.39 | 02-JAN-16:49 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.145492E+10 | 2147.91 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166141E+10 | 1869.05 | 17-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.145228E+10 | 1677.26 | 12-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.154064E+10 | 1454.29 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.152022E+10 | 1454.29 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.142974E+10 | 1454.29 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.160403E+10 | 1454.29 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.147272E+10 | 1818.13 | 26-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.158280E+10 | 2313.46 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.166084E+10 | 2367.39 | 06-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.165193E+10 | 2367.39 | 01-DEC-16:40 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.187009E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.142974E+10 | 1454.29 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166934E+10 | 2367.39 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106500E+10 | 1525.64 | 02-JAN-16:49 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.934760E+09 | 1390.98 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.106874E+10 | 1105.52 | 17-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.936741E+09 | 937.20 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.995956E+09 | 937.20 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.982723E+09 | 937.20 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.924256E+09 | 937.20 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.103663E+10 | 937.20 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.948137E+09 | 1068.54 | 26-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.101377E+10 | 1409.68 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.106211E+10 | 1525.64 | 06-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.105241E+10 | 1525.64 | 01-DEC-16:40 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120212E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.924256E+09 | 937.20 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.106874E+10 | 1525.64 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.163512E+10 | 2367.44 | 02-JAN-16:49 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.144290E+10 | 2115.23 | 01-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.165391E+10 | 1833.01 | 17-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.145430E+10 | 1667.08 | 12-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.154626E+10 | 1454.32 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.152604E+10 | 1454.32 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.143544E+10 | 1454.32 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.160818E+10 | 1454.32 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147134E+10 | 1790.62 | 26-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.156725E+10 | 2230.53 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.163479E+10 | 2367.44 | 06-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.161885E+10 | 2367.44 | 01-DEC-16:40 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.185944E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.143544E+10 | 1454.32 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.165391E+10 | 2367.44 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106358E+10 | 1525.64 | 02-JAN-16:49 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.932506E+09 | 1376.84 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.106805E+10 | 1243.39 | 17-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.936708E+09 | 1127.16 | 12-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.993691E+09 | 937.20 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.980505E+09 | 937.20 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.922763E+09 | 937.20 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.103430E+10 | 937.20 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.949359E+09 | 1210.75 | 26-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.101783E+10 | 1491.16 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.106017E+10 | 1525.64 | 06-NOV-16:00 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.105278E+10 | 1525.64 | 01-DEC-16:40 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.120122E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.922763E+09 | 937.20 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.106805E+10 | 1525.64 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497722E+09 | 520.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.451470E+09 | 520.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.536472E+09 | 520.85 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.479179E+09 | 520.85 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.517097E+09 | 520.85 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.514597E+09 | 520.85 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.481680E+09 | 520.85 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.536472E+09 | 520.85 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.479179E+09 | 520.85 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.497722E+09 | 520.85 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.491888E+09 | 520.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.481680E+09 | 520.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.596516E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.451470E+09 | 520.85 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.536472E+09 | 520.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.565679E+10 | 5919.59 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.513113E+10 | 5919.59 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.609720E+10 | 5919.59 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.544605E+10 | 5919.59 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.587700E+10 | 5919.59 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.584858E+10 | 5919.59 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.547447E+10 | 5919.59 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.609720E+10 | 5919.59 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.544605E+10 | 5919.59 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.565679E+10 | 5919.59 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.559049E+10 | 5919.59 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.547447E+10 | 5919.59 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.677962E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.513113E+10 | 5919.59 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.609720E+10 | 5919.59 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.208436E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.207428E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.193152E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.200626E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.198274E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.194159E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.240449E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.181982E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.216246E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.180176E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.173464E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.187190E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.186285E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.174369E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.173464E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.180176E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.178064E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.174369E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.215940E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.163433E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.194204E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.166633E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169908E+10 |
February | 0.136985E+10 | 0.145337E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179783E+10 |
March | 0.163685E+10 | 0.166008E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 360194.97 | 0.114169E+10 |
April | 0.145243E+10 | 0.145159E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940284E+09 |
May | 0.157338E+10 | 0.153991E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 339786.26 | 0.538450E+09 |
June | 0.156900E+10 | 0.151941E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9426257.36 | 0.299639E+09 |
July | 0.145680E+10 | 0.142938E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23590057.29 | 0.164268E+09 |
August | 0.163685E+10 | 0.160340E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18426047.84 | 0.192073E+09 |
September | 0.145243E+10 | 0.147168E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1323521.95 | 0.315122E+09 |
October | 0.150991E+10 | 0.158087E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737858E+09 |
November | 0.149516E+10 | 0.165836E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101930E+10 |
December | 0.145680E+10 | 0.164881E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185940E+10 |
Annual Sum or Average | 0.181194E+11 | 0.186832E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53465865.67 | 0.107050E+11 |
Minimum of Months | 0.136985E+10 | 0.142938E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164268E+09 |
Maximum of Months | 0.163685E+10 | 0.166633E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23590057.29 | 0.185940E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.106446E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112652E+10 |
February | 0.882782E+09 | 0.934484E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118614E+10 |
March | 0.105485E+10 | 0.106845E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 246728.58 | 0.748989E+09 |
April | 0.936002E+09 | 0.936607E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605861E+09 |
May | 0.101394E+10 | 0.995733E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 484309.80 | 0.355534E+09 |
June | 0.101113E+10 | 0.982591E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7583022.97 | 0.188746E+09 |
July | 0.938820E+09 | 0.924071E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18969924.65 | 93208326.03 |
August | 0.105485E+10 | 0.103643E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15386502.84 | 0.109003E+09 |
September | 0.936002E+09 | 0.947948E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1022411.55 | 0.203355E+09 |
October | 0.973041E+09 | 0.101334E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480013E+09 |
November | 0.963541E+09 | 0.106164E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652669E+09 |
December | 0.938820E+09 | 0.105175E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121043E+10 |
Annual Sum or Average | 0.116768E+11 | 0.120175E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43692900.39 | 0.696047E+10 |
Minimum of Months | 0.882782E+09 | 0.924071E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93208326.03 |
Maximum of Months | 0.105485E+10 | 0.106845E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18969924.65 | 0.121043E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.163269E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168470E+10 |
February | 0.136988E+10 | 0.144090E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176932E+10 |
March | 0.163688E+10 | 0.165301E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 359265.74 | 0.114807E+10 |
April | 0.145246E+10 | 0.145361E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923363E+09 |
May | 0.157341E+10 | 0.154547E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 179484.23 | 0.535339E+09 |
June | 0.156904E+10 | 0.152545E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9473187.68 | 0.291454E+09 |
July | 0.145684E+10 | 0.143482E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24149513.56 | 0.158398E+09 |
August | 0.163688E+10 | 0.160735E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17059065.36 | 0.188973E+09 |
September | 0.145246E+10 | 0.147039E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1250685.63 | 0.322042E+09 |
October | 0.150994E+10 | 0.156551E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738552E+09 |
November | 0.149520E+10 | 0.163171E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990322E+09 |
December | 0.145684E+10 | 0.161671E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182248E+10 |
Annual Sum or Average | 0.181198E+11 | 0.185776E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52471202.20 | 0.105730E+11 |
Minimum of Months | 0.136988E+10 | 0.143482E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158398E+09 |
Maximum of Months | 0.163688E+10 | 0.165301E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24149513.56 | 0.182248E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.106279E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116458E+10 |
February | 0.882782E+09 | 0.932201E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125170E+10 |
March | 0.105485E+10 | 0.106778E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 240126.06 | 0.825777E+09 |
April | 0.936002E+09 | 0.936438E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690919E+09 |
May | 0.101394E+10 | 0.993524E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113404.58 | 0.385153E+09 |
June | 0.101113E+10 | 0.980384E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6061156.92 | 0.222021E+09 |
July | 0.938820E+09 | 0.922599E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15157840.18 | 0.127979E+09 |
August | 0.105485E+10 | 0.103407E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11058066.92 | 0.149395E+09 |
September | 0.936002E+09 | 0.949052E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 761862.95 | 0.225036E+09 |
October | 0.973041E+09 | 0.101744E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527082E+09 |
November | 0.963541E+09 | 0.105966E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730302E+09 |
December | 0.938820E+09 | 0.105229E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133276E+10 |
Annual Sum or Average | 0.116768E+11 | 0.120082E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33392457.61 | 0.763271E+10 |
Minimum of Months | 0.882782E+09 | 0.922599E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127979E+09 |
Maximum of Months | 0.105485E+10 | 0.106778E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15157840.18 | 0.133276E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.166936E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355189E+10 |
February | 0.136985E+10 | 0.145494E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376391E+10 |
March | 0.163685E+10 | 0.166141E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 764765.18 | 0.235776E+10 |
April | 0.145243E+10 | 0.145228E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191350E+10 |
May | 0.157338E+10 | 0.154064E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1261816.09 | 0.115676E+10 |
June | 0.156900E+10 | 0.152022E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23692558.42 | 0.672563E+09 |
July | 0.145680E+10 | 0.142974E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51292934.88 | 0.395605E+09 |
August | 0.163685E+10 | 0.160403E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42991675.06 | 0.458531E+09 |
September | 0.145243E+10 | 0.147273E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3074145.17 | 0.676756E+09 |
October | 0.150991E+10 | 0.158289E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148128E+10 |
November | 0.149516E+10 | 0.166087E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200571E+10 |
December | 0.145680E+10 | 0.165197E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377362E+10 |
Annual Sum or Average | 0.181194E+11 | 0.187011E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123078E+09 | 0.222079E+11 |
Minimum of Months | 0.136985E+10 | 0.142974E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395605E+09 |
Maximum of Months | 0.163685E+10 | 0.166936E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51292934.88 | 0.377362E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.106500E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237788E+10 |
February | 0.649041E+09 | 0.934765E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252217E+10 |
March | 0.773965E+09 | 0.106873E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 604063.35 | 0.158757E+10 |
April | 0.688021E+09 | 0.936741E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129364E+10 |
May | 0.744847E+09 | 0.995957E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1320218.34 | 0.787794E+09 |
June | 0.742030E+09 | 0.982740E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16872389.52 | 0.443518E+09 |
July | 0.690839E+09 | 0.924249E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36607826.84 | 0.257392E+09 |
August | 0.773965E+09 | 0.103663E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30985831.11 | 0.301107E+09 |
September | 0.688021E+09 | 0.948137E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2414375.41 | 0.448826E+09 |
October | 0.715730E+09 | 0.101377E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100061E+10 |
November | 0.708685E+09 | 0.106217E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134074E+10 |
December | 0.690839E+09 | 0.105243E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252104E+10 |
Annual Sum or Average | 0.858171E+10 | 0.120213E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88804704.57 | 0.148823E+11 |
Minimum of Months | 0.649041E+09 | 0.924249E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257392E+09 |
Maximum of Months | 0.773965E+09 | 0.106873E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36607826.84 | 0.252217E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.163504E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365997E+10 |
February | 0.136988E+10 | 0.144290E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384831E+10 |
March | 0.163688E+10 | 0.165391E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 749241.54 | 0.251442E+10 |
April | 0.145246E+10 | 0.145430E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199974E+10 |
May | 0.157341E+10 | 0.154627E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 355540.92 | 0.119711E+10 |
June | 0.156904E+10 | 0.152604E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21811660.30 | 0.667618E+09 |
July | 0.145684E+10 | 0.143544E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50225441.31 | 0.400650E+09 |
August | 0.163688E+10 | 0.160818E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37103107.24 | 0.481297E+09 |
September | 0.145246E+10 | 0.147135E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2748450.83 | 0.729674E+09 |
October | 0.150994E+10 | 0.156725E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161666E+10 |
November | 0.149520E+10 | 0.163479E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211064E+10 |
December | 0.145684E+10 | 0.161886E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388455E+10 |
Annual Sum or Average | 0.181198E+11 | 0.185943E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112993E+09 | 0.231106E+11 |
Minimum of Months | 0.136988E+10 | 0.143544E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400650E+09 |
Maximum of Months | 0.163688E+10 | 0.165391E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50225441.31 | 0.388455E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.106358E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240595E+10 |
February | 0.882782E+09 | 0.932563E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255782E+10 |
March | 0.105485E+10 | 0.106805E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 765143.18 | 0.164503E+10 |
April | 0.936002E+09 | 0.936704E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134089E+10 |
May | 0.101394E+10 | 0.993693E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 256495.10 | 0.819370E+09 |
June | 0.101113E+10 | 0.980503E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16553452.79 | 0.480616E+09 |
July | 0.938820E+09 | 0.922761E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36010984.35 | 0.291162E+09 |
August | 0.105485E+10 | 0.103430E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28138395.80 | 0.336761E+09 |
September | 0.936002E+09 | 0.949360E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2011604.01 | 0.466025E+09 |
October | 0.973041E+09 | 0.101781E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101554E+10 |
November | 0.963541E+09 | 0.106023E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136552E+10 |
December | 0.938820E+09 | 0.105279E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256683E+10 |
Annual Sum or Average | 0.116768E+11 | 0.120124E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83736075.23 | 0.152915E+11 |
Minimum of Months | 0.882782E+09 | 0.922761E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291162E+09 |
Maximum of Months | 0.105485E+10 | 0.106805E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36010984.35 | 0.256683E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.166934E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429887E+10 |
February | 0.136985E+10 | 0.145492E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457013E+10 |
March | 0.163685E+10 | 0.166141E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 965060.64 | 0.276470E+10 |
April | 0.145243E+10 | 0.145228E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219837E+10 |
May | 0.157338E+10 | 0.154064E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1436706.45 | 0.134662E+10 |
June | 0.156900E+10 | 0.152022E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27900856.12 | 0.814526E+09 |
July | 0.145680E+10 | 0.142974E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60108003.59 | 0.488666E+09 |
August | 0.163685E+10 | 0.160403E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50998227.00 | 0.561180E+09 |
September | 0.145243E+10 | 0.147272E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3620107.98 | 0.781512E+09 |
October | 0.150991E+10 | 0.158280E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162850E+10 |
November | 0.149516E+10 | 0.166084E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225271E+10 |
December | 0.145680E+10 | 0.165193E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452687E+10 |
Annual Sum or Average | 0.181194E+11 | 0.187009E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145029E+09 | 0.262327E+11 |
Minimum of Months | 0.136985E+10 | 0.142974E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488666E+09 |
Maximum of Months | 0.163685E+10 | 0.166934E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60108003.59 | 0.457013E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.106500E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288051E+10 |
February | 0.882782E+09 | 0.934760E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306815E+10 |
March | 0.105485E+10 | 0.106874E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 598021.03 | 0.185570E+10 |
April | 0.936002E+09 | 0.936741E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150703E+10 |
May | 0.101394E+10 | 0.995956E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1207278.12 | 0.943688E+09 |
June | 0.101113E+10 | 0.982723E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17636294.92 | 0.552058E+09 |
July | 0.938820E+09 | 0.924256E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41165093.89 | 0.327276E+09 |
August | 0.105485E+10 | 0.103663E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35048465.87 | 0.378817E+09 |
September | 0.936002E+09 | 0.948137E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2644414.01 | 0.536940E+09 |
October | 0.973041E+09 | 0.101377E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112172E+10 |
November | 0.963541E+09 | 0.106211E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151604E+10 |
December | 0.938820E+09 | 0.105241E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302710E+10 |
Annual Sum or Average | 0.116768E+11 | 0.120212E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98299567.84 | 0.177150E+11 |
Minimum of Months | 0.882782E+09 | 0.924256E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327276E+09 |
Maximum of Months | 0.105485E+10 | 0.106874E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41165093.89 | 0.306815E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.163512E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437750E+10 |
February | 0.136988E+10 | 0.144290E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463514E+10 |
March | 0.163688E+10 | 0.165391E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 819055.01 | 0.291010E+10 |
April | 0.145246E+10 | 0.145430E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231787E+10 |
May | 0.157341E+10 | 0.154626E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 398624.65 | 0.141724E+10 |
June | 0.156904E+10 | 0.152604E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25168901.17 | 0.816889E+09 |
July | 0.145684E+10 | 0.143544E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58662887.67 | 0.499179E+09 |
August | 0.163688E+10 | 0.160818E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43589551.50 | 0.596376E+09 |
September | 0.145246E+10 | 0.147134E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3152376.30 | 0.866425E+09 |
October | 0.150994E+10 | 0.156725E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181457E+10 |
November | 0.149520E+10 | 0.163479E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237411E+10 |
December | 0.145684E+10 | 0.161885E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459681E+10 |
Annual Sum or Average | 0.181198E+11 | 0.185944E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131791E+09 | 0.272222E+11 |
Minimum of Months | 0.136988E+10 | 0.143544E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499179E+09 |
Maximum of Months | 0.163688E+10 | 0.165391E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58662887.67 | 0.463514E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.106358E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290125E+10 |
February | 0.882782E+09 | 0.932506E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309594E+10 |
March | 0.105485E+10 | 0.106805E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 947302.97 | 0.192637E+10 |
April | 0.936002E+09 | 0.936708E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156907E+10 |
May | 0.101394E+10 | 0.993691E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 290889.90 | 0.978519E+09 |
June | 0.101113E+10 | 0.980505E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19176417.57 | 0.589925E+09 |
July | 0.938820E+09 | 0.922763E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42106121.67 | 0.361127E+09 |
August | 0.105485E+10 | 0.103430E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33341764.23 | 0.416784E+09 |
September | 0.936002E+09 | 0.949359E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2502064.90 | 0.554399E+09 |
October | 0.973041E+09 | 0.101783E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115642E+10 |
November | 0.963541E+09 | 0.106017E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156409E+10 |
December | 0.938820E+09 | 0.105278E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306164E+10 |
Annual Sum or Average | 0.116768E+11 | 0.120122E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98364561.24 | 0.181755E+11 |
Minimum of Months | 0.882782E+09 | 0.922763E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361127E+09 |
Maximum of Months | 0.105485E+10 | 0.106805E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42106121.67 | 0.309594E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.497722E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.451470E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.536472E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.479179E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.517097E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.514597E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.481680E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.536472E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.479179E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.497722E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.491888E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.481680E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.596516E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.451470E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.536472E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.565679E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.513113E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.609720E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.544605E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.587700E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.584858E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.547447E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.609720E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.544605E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.565679E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.559049E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.547447E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.677962E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.513113E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.609720E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364683E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383770E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399663.06 | 0.243596E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197905E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599023.96 | 0.111996E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15303081.13 | 0.628344E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38645978.95 | 0.352934E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32599270.23 | 0.422697E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1712922.24 | 0.667837E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155720E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215467E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397589E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89259939.58 | 0.227791E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352934E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38645978.95 | 0.397589E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599030E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632583E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1207186.86 | 0.408166E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332474E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1980609.09 | 0.193295E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32780290.99 | 0.109675E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68994129.65 | 0.627268E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60250442.77 | 0.754260E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3277252.24 | 0.115849E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260896E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354228E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647280E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168490E+09 | 0.379163E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627268E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68994129.65 | 0.647280E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633289E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672654E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92941.34 | 0.428398E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354162E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82372.96 | 0.220319E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16889307.30 | 0.130684E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48317717.43 | 0.785917E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39298044.05 | 0.901649E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1694762.19 | 0.128812E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265509E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355371E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673247E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106375E+09 | 0.403120E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785917E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48317717.43 | 0.673247E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 20994.62 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 20994.62 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 20994.62 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 20994.62 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 20994.62 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 20994.62 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 20994.62 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 20994.62 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 20994.62 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 20994.62 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 20994.62 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 20994.62 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 20994.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18854.65 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18854.65 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18854.65 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18854.65 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18854.65 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18854.65 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18854.65 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18854.65 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18854.65 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18854.65 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18854.65 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18854.65 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2367.39 | 02-JAN-16:49 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3036.42 | 12-JAN-05:53 |
February | 2010.79 | 01-FEB-10:09 | 2141.31 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3141.81 | 13-FEB-05:51 |
March | 2010.79 | 01-MAR-10:09 | 1853.94 | 17-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 15-MAR-14:00 | 1922.98 | 02-MAR-01:00 |
April | 2010.79 | 03-APR-09:09 | 1656.79 | 12-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1856.11 | 16-APR-01:55 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.72 | 14-MAY-15:00 | 1052.15 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.39 | 17-JUN-17:02 | 920.41 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.21 | 21-JUL-02:40 | 677.72 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 1454.29 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.40 | 13-AUG-13:00 | 423.33 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1801.80 | 26-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.41 | 16-SEP-17:02 | 790.75 | 29-SEP-03:55 |
October | 2010.79 | 02-OCT-09:09 | 2311.32 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1034.51 | 08-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 06-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1827.41 | 17-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-16:40 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2965.01 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.33 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 310.40 | 3141.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-16:49 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2024.30 | 12-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 1390.00 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2092.36 | 13-FEB-05:51 |
March | 1295.83 | 01-MAR-10:09 | 1098.84 | 17-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 | 15-MAR-14:00 | 1276.23 | 02-MAR-01:00 |
April | 1295.83 | 03-APR-09:09 | 937.20 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1197.93 | 16-APR-01:55 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.17 | 14-MAY-15:00 | 737.12 | 29-MAY-14:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.43 | 17-JUN-17:02 | 610.40 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.32 | 21-JUL-02:20 | 428.77 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.04 | 13-AUG-13:20 | 259.22 | 30-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 1061.27 | 26-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.05 | 16-SEP-17:02 | 510.01 | 29-SEP-03:55 |
October | 1295.83 | 02-OCT-09:09 | 1407.60 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 699.94 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1171.01 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:40 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1921.86 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.22 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 269.04 | 2092.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2367.44 | 02-JAN-16:49 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3036.45 | 12-JAN-05:53 |
February | 2010.83 | 01-FEB-10:09 | 2106.95 | 01-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3132.60 | 13-FEB-05:51 |
March | 2010.83 | 01-MAR-10:09 | 1816.25 | 17-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.06 | 15-MAR-14:00 | 1993.07 | 02-MAR-01:00 |
April | 2010.83 | 03-APR-09:09 | 1646.25 | 12-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1756.91 | 16-APR-01:55 |
May | 2010.83 | 01-MAY-09:09 | 1454.32 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.28 | 14-MAY-15:00 | 1092.77 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.76 | 17-JUN-17:02 | 921.64 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1454.32 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.83 | 21-JUL-02:20 | 668.67 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 1454.32 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.92 | 13-AUG-13:18 | 411.12 | 30-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1773.15 | 26-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.79 | 16-SEP-17:20 | 761.67 | 29-SEP-03:55 |
October | 2010.83 | 02-OCT-09:09 | 2125.78 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1013.98 | 08-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 06-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1785.16 | 17-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-16:40 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2910.18 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.12 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 279.92 | 3132.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-16:49 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2039.42 | 12-JAN-02:00 |
February | 1295.83 | 01-FEB-10:09 | 1375.80 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2099.93 | 13-FEB-05:51 |
March | 1295.83 | 01-MAR-10:09 | 1241.41 | 17-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 | 15-MAR-14:00 | 1425.88 | 02-MAR-01:00 |
April | 1295.83 | 03-APR-09:09 | 1124.49 | 12-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1356.51 | 16-APR-01:55 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.69 | 14-MAY-15:20 | 763.41 | 29-MAY-14:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.17 | 17-JUN-17:50 | 676.53 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.57 | 21-JUL-03:10 | 526.68 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.31 | 13-AUG-13:20 | 335.23 | 27-AUG-16:40 |
September | 1295.83 | 01-SEP-09:09 | 1208.60 | 26-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.40 | 16-SEP-13:00 | 553.25 | 29-SEP-03:55 |
October | 1295.83 | 02-OCT-09:09 | 1490.32 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 746.30 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:00 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1329.78 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:40 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2073.06 | 09-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.23 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 202.31 | 2099.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2367.39 | 02-JAN-16:49 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6841.28 | 12-JAN-05:40 |
February | 2010.79 | 01-FEB-10:09 | 2148.10 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6764.61 | 13-FEB-06:00 |
March | 2010.79 | 01-MAR-10:09 | 1869.43 | 17-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.11 | 15-MAR-14:00 | 4090.53 | 02-MAR-05:09 |
April | 2010.79 | 03-APR-09:09 | 1677.85 | 12-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3533.35 | 16-APR-01:55 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.66 | 14-MAY-15:10 | 2092.32 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.79 | 17-JUN-17:02 | 1968.52 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.83 | 21-JUL-03:10 | 1431.20 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 1454.29 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 720.97 | 13-AUG-13:10 | 921.95 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1818.58 | 26-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.03 | 16-SEP-17:02 | 1601.50 | 29-SEP-03:55 |
October | 2010.79 | 02-OCT-09:09 | 2313.40 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1993.72 | 08-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 06-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3517.78 | 17-NOV-05:55 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-16:40 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6335.60 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 921.95 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 720.97 | 6841.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1525.64 | 02-JAN-16:49 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4766.65 | 12-JAN-06:00 |
February | 1239.33 | 01-FEB-08:09 | 1391.10 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4952.89 | 13-FEB-06:00 |
March | 1239.33 | 01-MAR-08:09 | 1105.64 | 17-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 | 15-MAR-14:00 | 2727.05 | 02-MAR-05:09 |
April | 1239.33 | 03-APR-07:10 | 937.20 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2348.84 | 16-APR-07:00 |
May | 1239.33 | 01-MAY-07:10 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.30 | 14-MAY-15:10 | 1576.01 | 29-MAY-14:00 |
June | 1239.33 | 01-JUN-07:10 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.83 | 17-JUN-17:02 | 1329.80 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 435.15 | 21-JUL-03:10 | 942.88 | 06-JUL-02:00 |
August | 1239.33 | 01-AUG-07:10 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 591.03 | 13-AUG-13:10 | 572.42 | 30-AUG-21:10 |
September | 1239.33 | 01-SEP-07:10 | 1068.71 | 26-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.78 | 16-SEP-17:20 | 1035.53 | 29-SEP-03:55 |
October | 1239.33 | 02-OCT-07:10 | 1409.44 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1384.36 | 08-OCT-09:00 |
November | 1239.33 | 01-NOV-07:10 | 1525.64 | 06-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2345.21 | 17-NOV-05:55 |
December | 1239.33 | 01-DEC-08:09 | 1525.64 | 01-DEC-16:40 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4181.47 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.42 | |||||
Maximum of Months | 1239.33 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 591.03 | 4952.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2367.44 | 02-JAN-16:49 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7149.82 | 12-JAN-06:00 |
February | 2010.83 | 01-FEB-10:09 | 2115.41 | 01-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7225.98 | 13-FEB-06:00 |
March | 2010.83 | 01-MAR-10:09 | 1833.38 | 17-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.74 | 15-MAR-14:00 | 4155.92 | 26-MAR-13:00 |
April | 2010.83 | 03-APR-09:09 | 1667.68 | 12-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3534.60 | 16-APR-01:55 |
May | 2010.83 | 01-MAY-09:09 | 1454.32 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.51 | 10-MAY-14:00 | 2314.74 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.97 | 17-JUN-17:02 | 1992.87 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1454.32 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 577.95 | 21-JUL-03:10 | 1434.00 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 1454.32 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 641.24 | 13-AUG-13:05 | 898.86 | 30-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1791.07 | 26-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.11 | 16-SEP-13:00 | 1600.38 | 29-SEP-03:55 |
October | 2010.83 | 02-OCT-09:09 | 2230.30 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2120.96 | 08-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 06-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3600.83 | 17-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-16:40 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6388.01 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 898.86 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 641.24 | 7225.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-16:49 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4766.45 | 12-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1376.98 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4952.76 | 13-FEB-05:54 |
March | 1295.83 | 01-MAR-10:09 | 1243.63 | 17-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.07 | 15-MAR-14:00 | 2758.50 | 25-MAR-17:10 |
April | 1295.83 | 03-APR-09:09 | 1127.53 | 12-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2395.68 | 16-APR-01:55 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.68 | 10-MAY-14:00 | 1633.41 | 29-MAY-15:20 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.56 | 17-JUN-17:30 | 1362.08 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.58 | 21-JUL-03:10 | 1002.85 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 607.93 | 13-AUG-13:10 | 685.71 | 27-AUG-17:00 |
September | 1295.83 | 01-SEP-09:09 | 1211.03 | 26-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.96 | 16-SEP-12:40 | 1049.16 | 29-SEP-03:55 |
October | 1295.83 | 02-OCT-09:09 | 1491.11 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1372.16 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:00 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2349.12 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:40 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4262.27 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.71 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 607.93 | 4952.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2367.39 | 02-JAN-16:49 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 8347.40 | 12-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 2147.91 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7935.63 | 13-FEB-05:50 |
March | 2010.79 | 01-MAR-10:09 | 1869.05 | 17-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.50 | 15-MAR-14:00 | 4930.19 | 02-MAR-05:30 |
April | 2010.79 | 03-APR-09:09 | 1677.26 | 12-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4149.90 | 04-APR-21:03 |
May | 2010.79 | 01-MAY-09:09 | 1454.29 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.23 | 14-MAY-15:00 | 2452.54 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 1454.29 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.35 | 17-JUN-17:02 | 2382.89 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1454.29 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 593.19 | 21-JUL-03:08 | 1692.44 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 1454.29 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 958.07 | 13-AUG-12:53 | 1096.51 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1818.13 | 26-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.89 | 16-SEP-17:02 | 1743.27 | 29-SEP-04:10 |
October | 2010.79 | 02-OCT-09:09 | 2313.46 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2356.30 | 30-OCT-05:00 |
November | 2010.79 | 01-NOV-09:09 | 2367.39 | 06-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4399.07 | 17-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 2367.39 | 01-DEC-16:40 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7537.45 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.51 | |||||
Maximum of Months | 2010.79 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 958.07 | 8347.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-16:49 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5942.06 | 12-JAN-05:55 |
February | 1295.83 | 01-FEB-10:09 | 1390.98 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5880.52 | 13-FEB-05:50 |
March | 1295.83 | 01-MAR-10:09 | 1105.52 | 17-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 15-MAR-14:00 | 3405.38 | 02-MAR-05:10 |
April | 1295.83 | 03-APR-09:09 | 937.20 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2765.64 | 04-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.58 | 14-MAY-15:00 | 1871.96 | 29-MAY-14:00 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 355.77 | 17-JUN-17:02 | 1616.81 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.65 | 21-JUL-03:00 | 1119.34 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 681.75 | 13-AUG-13:20 | 713.17 | 20-AUG-15:00 |
September | 1295.83 | 01-SEP-09:09 | 1068.54 | 26-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.17 | 16-SEP-17:20 | 1160.57 | 29-SEP-04:10 |
October | 1295.83 | 02-OCT-09:09 | 1409.68 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1571.01 | 30-OCT-04:57 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2932.38 | 17-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:40 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4999.49 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 713.17 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 681.75 | 5942.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2367.44 | 02-JAN-16:49 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 8816.43 | 12-JAN-06:00 |
February | 2010.83 | 01-FEB-10:09 | 2115.23 | 01-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8424.28 | 13-FEB-05:50 |
March | 2010.83 | 01-MAR-10:09 | 1833.01 | 17-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.35 | 15-MAR-14:00 | 5107.99 | 02-MAR-05:09 |
April | 2010.83 | 03-APR-09:09 | 1667.08 | 12-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4150.32 | 04-APR-21:03 |
May | 2010.83 | 01-MAY-09:09 | 1454.32 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.71 | 10-MAY-14:00 | 2729.08 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 1454.32 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.27 | 17-JUN-17:02 | 2414.72 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1454.32 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 644.15 | 21-JUL-03:00 | 1696.36 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 1454.32 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 762.18 | 13-AUG-13:18 | 1148.70 | 20-AUG-15:00 |
September | 2010.83 | 01-SEP-09:09 | 1790.62 | 26-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.89 | 16-SEP-13:00 | 1743.26 | 29-SEP-04:10 |
October | 2010.83 | 02-OCT-09:09 | 2230.53 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2356.42 | 30-OCT-04:57 |
November | 2010.83 | 01-NOV-09:09 | 2367.44 | 06-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4398.64 | 17-NOV-05:55 |
December | 2010.83 | 01-DEC-10:09 | 2367.44 | 01-DEC-16:40 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7606.28 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.70 | |||||
Maximum of Months | 2010.83 | 2367.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 762.18 | 8816.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1525.64 | 02-JAN-16:49 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5941.95 | 12-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1376.84 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6078.81 | 13-FEB-05:50 |
March | 1295.83 | 01-MAR-10:09 | 1243.39 | 17-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 15-MAR-14:00 | 3405.39 | 02-MAR-05:10 |
April | 1295.83 | 03-APR-09:09 | 1127.16 | 12-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2770.17 | 04-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 937.20 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.41 | 14-MAY-15:30 | 2001.64 | 06-MAY-17:10 |
June | 1295.83 | 01-JUN-09:09 | 937.20 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.61 | 17-JUN-17:30 | 1650.11 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 937.20 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 504.75 | 21-JUL-03:00 | 1191.26 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 937.20 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 708.41 | 13-AUG-12:40 | 889.74 | 27-AUG-16:40 |
September | 1295.83 | 01-SEP-09:09 | 1210.75 | 26-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.41 | 16-SEP-12:40 | 1161.90 | 29-SEP-04:10 |
October | 1295.83 | 02-OCT-09:09 | 1491.16 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1570.87 | 30-OCT-04:53 |
November | 1295.83 | 01-NOV-09:09 | 1525.64 | 06-NOV-16:00 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2932.50 | 17-NOV-05:55 |
December | 1295.83 | 01-DEC-10:09 | 1525.64 | 01-DEC-16:40 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5107.59 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 889.74 | |||||
Maximum of Months | 1295.83 | 1525.64 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 708.41 | 6078.81 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 520.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 520.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 520.85 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 520.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 520.85 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 520.85 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 520.85 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 520.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 520.85 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 520.85 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 520.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 520.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5919.59 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5919.59 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5919.59 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5919.59 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5919.59 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5919.59 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5919.59 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5919.59 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5919.59 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5919.59 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5919.59 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5919.59 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6456.53 | 12-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6503.22 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 15-MAR-14:00 | 4238.86 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3989.60 | 16-APR-01:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.10 | 14-MAY-15:00 | 1951.01 | 29-MAY-14:08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.06 | 17-JUN-17:02 | 1900.87 | 13-JUN-03:04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.65 | 21-JUL-02:40 | 1376.20 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.81 | 13-AUG-13:00 | 867.08 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 16-SEP-17:02 | 1692.49 | 29-SEP-04:05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2173.17 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3893.85 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6397.58 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 867.08 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.81 | 6503.22 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10747.81 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10627.25 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.62 | 15-MAR-14:00 | 6924.68 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6601.58 | 16-APR-01:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.78 | 14-MAY-14:53 | 3178.54 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612.98 | 17-JUN-17:02 | 3277.98 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 695.48 | 21-JUL-02:40 | 2399.26 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.39 | 13-AUG-12:53 | 1529.90 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.35 | 16-SEP-17:02 | 2911.56 | 29-SEP-03:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3633.71 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6475.20 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 10764.23 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1529.90 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.39 | 10764.23 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 11691.50 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 11381.26 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.92 | 15-MAR-14:00 | 6908.11 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6388.13 | 16-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 | 10-MAY-15:00 | 4261.14 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.59 | 17-JUN-17:02 | 3720.62 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 669.71 | 21-JUL-01:53 | 2622.37 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.46 | 13-AUG-13:00 | 1683.32 | 30-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.29 | 16-SEP-13:00 | 2843.29 | 29-SEP-04:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3324.36 | 19-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6532.73 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 11999.51 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1683.32 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.46 | 11999.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 112428.37 | 02-JAN-04:01 | 0.00 | 11664.26 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 108757.37 | 21-FEB-04:50 | 0.00 | 11664.26 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 109045.57 | 20-MAR-03:01 | 0.00 | 8164.98 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 112717.00 | 10-APR-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 110714.23 | 01-MAY-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 105928.49 | 13-JUN-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 103111.33 | 06-JUL-03:02 | 0.00 | 6998.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 102240.11 | 04-AUG-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 110731.94 | 05-SEP-03:02 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 113675.78 | 16-OCT-03:01 | 0.00 | 8164.98 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 113430.65 | 13-NOV-04:01 | 0.00 | 10497.83 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 113321.60 | 26-DEC-04:01 | 0.00 | 9331.40 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 102240.11 | 0.00 | 5832.13 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 113675.78 | 0.00 | 11664.26 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 81995.85 | 18-JAN-06:01 | 11285.67 | 14665.45 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83347.83 | 23-FEB-06:01 | 11285.67 | 14665.45 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 89250.39 | 17-MAR-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 92968.08 | 10-APR-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95795.42 | 30-MAY-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 91870.34 | 13-JUN-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 91895.64 | 06-JUL-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 91379.11 | 31-AUG-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 96125.51 | 18-SEP-03:02 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 93439.26 | 23-OCT-03:02 | 0.00 | 6285.19 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 93441.20 | 13-NOV-04:01 | 0.00 | 9427.79 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 87373.42 | 18-DEC-05:01 | 0.00 | 14665.45 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 81995.85 | 0.00 | 5237.66 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96125.51 | 11285.67 | 14665.45 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 23597.70 | 20-JAN-15:30 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25204.28 | 17-FEB-16:50 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77607.78 | 17-MAR-05:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78257.86 | 10-APR-05:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81279.47 | 24-MAY-04:02 | 0.00 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83813.02 | 30-JUN-03:02 | 0.00 | 6285.19 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84608.90 | 24-JUL-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84591.88 | 21-AUG-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86681.81 | 18-SEP-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80710.54 | 05-OCT-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 73285.20 | 01-NOV-05:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28008.20 | 21-DEC-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 23597.70 | 0.00 | 5237.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86681.81 | 15316.26 | 18854.65 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17378.12 | 11-JAN-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17808.96 | 17-FEB-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53386.00 | 15-MAR-05:03 | 6448.95 | 8380.26 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39976.02 | 21-APR-16:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79776.22 | 24-MAY-04:02 | 0.00 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84749.76 | 19-JUN-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84870.74 | 05-JUL-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86225.22 | 07-AUG-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85143.60 | 18-SEP-03:02 | 0.00 | 5237.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72882.38 | 12-OCT-05:02 | 8061.19 | 10475.32 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26582.48 | 01-NOV-16:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18438.51 | 01-DEC-17:00 | 15316.26 | 18854.65 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17378.12 | 0.00 | 5237.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86225.22 | 15316.26 | 18854.65 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2897.30 | 17-JAN-06:02 | 1619.46 | 2104.45 | 8093.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.93 |
February | 3562.54 | 28-FEB-14:50 | 6032.37 | 4362.86 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.83 |
March | 8313.84 | 16-MAR-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.45 |
April | 6356.78 | 07-APR-13:30 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.69 |
May | 7398.54 | 23-MAY-14:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 |
June | 12690.75 | 12-JUN-05:03 | 809.73 | 808.54 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 |
July | 15861.98 | 16-JUL-16:21 | 809.73 | 646.38 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 79.55 | 0.00 |
August | 12634.28 | 21-AUG-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.24 |
September | 11130.53 | 15-SEP-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 |
October | 6743.36 | 23-OCT-05:03 | 809.73 | 1052.22 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.39 |
November | 4523.20 | 27-NOV-12:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.12 |
December | 3159.37 | 01-DEC-06:02 | 1012.16 | 1315.28 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2897.30 | 809.73 | 646.38 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15861.98 | 6032.37 | 4362.86 | 8093.57 | 0.00 | 0.00 | 0.00 | 0.00 | 79.55 | 264.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3469.25 | 20-JAN-06:02 | 1043.64 | 1356.19 | 5215.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.28 |
February | 4228.76 | 28-FEB-14:50 | 3887.49 | 2811.59 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.56 |
March | 7100.57 | 21-MAR-09:10 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.47 |
April | 10883.26 | 24-APR-08:20 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.20 |
May | 13720.74 | 21-MAY-09:13 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.96 |
June | 20068.84 | 11-JUN-09:12 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.94 |
July | 21578.17 | 04-JUL-08:51 | 456.59 | 364.48 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.29 |
August | 11991.97 | 04-AUG-08:30 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 |
September | 13142.29 | 04-SEP-08:23 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.04 |
October | 8790.26 | 11-OCT-08:45 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 |
November | 4826.77 | 03-NOV-09:10 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.99 |
December | 3463.39 | 04-DEC-10:20 | 2591.66 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3463.39 | 260.91 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 | |
Maximum of Months | 21578.17 | 3887.49 | 2811.59 | 5215.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10708.55 | 06-JAN-13:10 | 5769.46 | 4362.96 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.35 |
February | 19848.40 | 28-FEB-15:00 | 6032.50 | 4362.96 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.39 |
March | 19698.37 | 01-MAR-14:10 | 6032.50 | 4362.96 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.10 |
April | 14026.13 | 24-APR-12:40 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.70 |
May | 18758.85 | 14-MAY-13:52 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.18 |
June | 17800.16 | 25-JUN-13:12 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 |
July | 23321.17 | 16-JUL-11:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 54.91 | 0.00 |
August | 21666.36 | 13-AUG-15:12 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 209.03 | 0.00 |
September | 23809.96 | 04-SEP-12:23 | 404.87 | 323.20 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.00 |
October | 18684.00 | 11-OCT-12:30 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 |
November | 14412.03 | 03-NOV-12:20 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.75 |
December | 11740.19 | 04-DEC-11:25 | 3846.30 | 2908.64 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10708.55 | 404.87 | 323.20 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23809.96 | 6032.50 | 4362.96 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 209.03 | 540.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4578.23 | 17-JAN-06:01 | 1043.64 | 1356.19 | 5215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.04 |
February | 7587.49 | 28-FEB-15:00 | 3887.49 | 2811.59 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.73 |
March | 14816.30 | 16-MAR-05:03 | 521.82 | 678.09 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.53 |
April | 23897.43 | 09-APR-17:12 | 0.00 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.77 |
May | 20114.50 | 07-MAY-16:32 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.54 |
June | 26915.57 | 11-JUN-15:51 | 456.59 | 364.48 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.66 |
July | 27459.32 | 16-JUL-17:01 | 0.00 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.96 |
August | 25337.10 | 06-AUG-16:32 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 0.00 |
September | 19099.21 | 04-SEP-16:22 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.82 |
October | 12618.15 | 23-OCT-03:02 | 0.00 | 508.57 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.32 |
November | 9351.49 | 04-NOV-05:02 | 652.28 | 847.62 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.08 |
December | 6740.23 | 04-DEC-15:30 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4578.23 | 0.00 | 260.35 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27459.32 | 3887.49 | 2811.59 | 5215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 316.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1665.88 | 14-JAN-17:02 | 506.08 | 657.64 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.83 |
February | 1745.40 | 17-FEB-15:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.81 |
March | 5543.97 | 15-MAR-14:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 39.92 | 0.00 |
April | 3645.83 | 21-APR-15:10 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.04 |
May | 6498.29 | 23-MAY-14:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
June | 11390.59 | 21-JUN-05:03 | 809.73 | 646.38 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.00 |
July | 11618.31 | 18-JUL-05:03 | 809.73 | 788.43 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9942.94 | 14-AUG-03:02 | 0.00 | 789.17 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.79 |
September | 6788.15 | 15-SEP-14:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 0.00 |
October | 3881.11 | 12-OCT-15:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.57 |
November | 3569.11 | 28-NOV-13:55 | 3846.22 | 2908.57 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.28 |
December | 2358.07 | 01-DEC-13:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1665.88 | 0.00 | 646.38 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11618.31 | 3846.22 | 2908.57 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 39.92 | 666.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2426.42 | 11-JAN-06:04 | 1043.64 | 1356.19 | 5215.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.30 |
February | 2976.27 | 28-FEB-10:00 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.93 |
March | 4964.00 | 14-MAR-10:40 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 |
April | 10212.03 | 24-APR-07:50 | 3717.98 | 2811.59 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.03 |
May | 11540.74 | 31-MAY-08:50 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.27 |
June | 21086.22 | 11-JUN-09:52 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.73 |
July | 23027.95 | 04-JUL-08:51 | 456.59 | 364.48 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.22 |
August | 12925.81 | 06-AUG-09:13 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.09 |
September | 18842.92 | 04-SEP-08:52 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.12 |
October | 7018.21 | 11-OCT-09:00 | 1239.33 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.56 |
November | 3649.15 | 03-NOV-10:15 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.73 |
December | 2508.05 | 01-DEC-06:04 | 652.28 | 847.62 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2426.42 | 260.91 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | |
Maximum of Months | 23027.95 | 3717.98 | 2811.59 | 5215.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8660.98 | 12-JAN-13:40 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1659.29 |
February | 12666.81 | 28-FEB-13:50 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.06 |
March | 15554.75 | 15-MAR-13:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 42.17 | 0.00 |
April | 13350.92 | 24-APR-13:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.92 |
May | 18099.40 | 14-MAY-13:42 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.50 |
June | 13244.08 | 12-JUN-13:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 245.89 | 0.00 |
July | 18383.42 | 04-JUL-14:52 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 |
August | 23244.80 | 13-AUG-14:21 | 708.53 | 565.60 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 439.13 | 0.00 |
September | 24030.68 | 04-SEP-13:32 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 845.31 |
October | 18848.00 | 31-OCT-13:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.72 |
November | 14374.99 | 03-NOV-12:40 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.06 |
December | 7467.25 | 16-DEC-13:30 | 202.44 | 242.38 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7467.25 | 202.44 | 242.38 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24030.68 | 2010.83 | 1454.32 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 439.13 | 1659.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2752.40 | 12-JAN-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 919.59 |
February | 3740.51 | 28-FEB-16:40 | 2478.65 | 1874.40 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.35 |
March | 5936.29 | 21-MAR-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.06 |
April | 9926.12 | 24-APR-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.96 |
May | 17557.65 | 27-MAY-17:05 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.88 |
June | 21813.69 | 11-JUN-16:42 | 326.14 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.29 |
July | 22943.12 | 02-JUL-16:42 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.03 |
August | 22280.19 | 13-AUG-15:41 | 521.82 | 416.55 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 207.75 | 0.00 |
September | 21772.96 | 04-SEP-17:32 | 0.00 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.03 |
October | 9154.11 | 11-OCT-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.84 |
November | 5521.26 | 24-NOV-16:15 | 2478.65 | 1874.40 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.21 |
December | 3039.33 | 01-DEC-13:40 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2752.40 | 0.00 | 260.35 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22943.12 | 2478.65 | 1874.40 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 207.75 | 919.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1979.28 | 14-JAN-17:02 | 506.08 | 657.64 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.12 |
February | 1954.66 | 18-FEB-17:03 | 404.87 | 420.38 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 713.52 |
March | 5918.56 | 15-MAR-14:50 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 36.56 | 0.00 |
April | 3604.49 | 20-APR-16:00 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.35 |
May | 6542.07 | 23-MAY-14:40 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 |
June | 10997.88 | 26-JUN-05:03 | 809.73 | 955.71 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.91 |
July | 18038.61 | 16-JUL-15:12 | 607.30 | 484.79 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 234.46 | 0.00 |
August | 11676.82 | 14-AUG-03:02 | 0.00 | 789.17 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.99 |
September | 7044.01 | 15-SEP-14:00 | 2010.79 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 | 0.00 |
October | 3726.66 | 11-OCT-12:30 | 1923.11 | 1454.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 |
November | 2654.49 | 16-NOV-17:00 | 1923.11 | 2367.39 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.75 |
December | 1962.89 | 02-DEC-17:02 | 506.08 | 657.64 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1188.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1954.66 | 0.00 | 420.38 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18038.61 | 2010.79 | 2367.39 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 234.46 | 1188.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2186.03 | 14-JAN-17:02 | 326.14 | 423.81 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.57 |
February | 2614.14 | 28-FEB-10:10 | 2591.66 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.38 |
March | 4722.37 | 15-MAR-14:00 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 0.00 |
April | 7730.67 | 24-APR-09:30 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.62 |
May | 10880.57 | 31-MAY-09:10 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.27 |
June | 14658.41 | 18-JUN-08:32 | 326.14 | 260.35 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.81 |
July | 22538.71 | 16-JUL-09:12 | 391.37 | 312.41 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.67 |
August | 12944.37 | 06-AUG-09:13 | 260.91 | 208.28 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.89 |
September | 9077.35 | 18-SEP-09:30 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.53 |
October | 5822.04 | 11-OCT-09:50 | 1295.83 | 937.20 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.18 |
November | 2840.48 | 03-NOV-10:15 | 2478.65 | 1874.40 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.14 |
December | 2446.55 | 21-DEC-06:04 | 913.19 | 1186.66 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2186.03 | 260.91 | 208.28 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22538.71 | 2591.66 | 1874.40 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 364.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5960.34 | 12-JAN-14:00 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1948.77 |
February | 11465.24 | 28-FEB-14:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.92 |
March | 15945.65 | 15-MAR-13:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 48.38 | 0.00 |
April | 12475.35 | 24-APR-13:30 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.15 |
May | 11633.29 | 26-MAY-13:40 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.85 |
June | 15267.08 | 25-JUN-13:52 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.69 |
July | 25002.51 | 16-JUL-13:12 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 15.15 | 0.00 |
August | 24741.59 | 13-AUG-15:12 | 607.31 | 484.80 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 545.78 | 0.00 |
September | 25247.70 | 04-SEP-13:32 | 506.09 | 404.00 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.10 |
October | 19137.41 | 11-OCT-12:30 | 1923.15 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.64 |
November | 12030.31 | 03-NOV-13:10 | 2010.83 | 1454.32 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.61 |
December | 5158.33 | 16-DEC-13:30 | 202.44 | 242.38 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5158.33 | 202.44 | 242.38 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25247.70 | 2010.83 | 1454.32 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 545.78 | 1948.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2705.89 | 18-JAN-06:04 | 913.19 | 1186.66 | 4563.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.73 |
February | 3779.83 | 28-FEB-16:40 | 2478.65 | 1874.40 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.89 |
March | 5980.56 | 15-MAR-14:20 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 34.56 | 0.00 |
April | 9545.20 | 19-APR-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.07 |
May | 17820.86 | 27-MAY-17:05 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.38 |
June | 23645.88 | 25-JUN-15:52 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 | 0.00 |
July | 24456.05 | 02-JUL-16:42 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.42 |
August | 23412.70 | 06-AUG-16:32 | 391.37 | 312.41 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 30.77 | 0.00 |
September | 21466.55 | 04-SEP-17:32 | 0.00 | 260.35 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.02 |
October | 9137.34 | 11-OCT-16:00 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 |
November | 3651.61 | 15-NOV-15:40 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.05 |
December | 2762.99 | 04-DEC-15:50 | 1239.33 | 937.20 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2705.89 | 0.00 | 260.35 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24456.05 | 2478.65 | 1874.40 | 4563.80 | 0.00 | 0.00 | 0.00 | 0.00 | 34.56 | 588.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4417.74 | 30-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2397.82 |
February | 3945.19 | 25-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 790.17 |
March | 5804.18 | 16-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.54 |
April | 8119.48 | 10-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.03 |
May | 8986.26 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.12 |
June | 8860.33 | 19-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.84 |
July | 10975.07 | 17-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.66 |
August | 9925.88 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.58 |
September | 9654.05 | 18-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.47 |
October | 8060.99 | 23-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.19 |
November | 5860.58 | 06-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.91 |
December | 3363.90 | 01-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3363.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.66 | |
Maximum of Months | 10975.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2397.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6179.44 | 23-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4462.84 |
February | 5922.25 | 05-FEB-21:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7806.44 |
March | 6715.08 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2679.08 |
April | 5048.88 | 17-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5595.91 | 30-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.28 |
June | 6365.59 | 27-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 | 0.00 |
July | 8705.83 | 18-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9068.21 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.38 |
September | 6812.15 | 18-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.60 |
October | 5261.77 | 05-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.99 |
November | 6041.33 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1634.74 |
December | 6406.33 | 10-DEC-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3965.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5048.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9068.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 | 7806.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2158.07 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3127.52 |
March | 11062.47 | 15-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.92 | 0.00 |
April | 8593.94 | 21-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.82 |
May | 13642.47 | 31-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.10 |
June | 18836.69 | 12-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.41 | 0.00 |
July | 19538.43 | 21-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.68 | 0.00 |
August | 18242.86 | 09-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.83 | 0.00 |
September | 13791.00 | 21-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 | 0.00 |
October | 7532.38 | 11-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.40 |
November | 2004.90 | 04-NOV-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.99 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2695.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19538.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.41 | 3127.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1880.84 | 12-JAN-16:40 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4136.19 | 28-FEB-17:00 | 444.28 | 1041.69 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6988.87 | 31-MAR-24:00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8047.93 | 24-APR-18:00 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3498.46 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5372.64 | 30-JUN-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7254.26 | 31-JUL-23:50 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8166.74 | 04-AUG-18:30 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3189.40 | 30-SEP-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5148.81 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5872.37 | 24-NOV-16:10 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7723.23 | 04-DEC-16:10 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1880.84 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8166.74 | 444.28 | 1041.69 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1437.05 | 12-JAN-16:40 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3561.83 | 28-FEB-17:00 | 444.28 | 1041.69 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6102.35 | 31-MAR-24:00 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7584.51 | 24-APR-18:00 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3280.01 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5157.73 | 30-JUN-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7014.40 | 31-JUL-23:55 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7795.02 | 02-AUG-18:40 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2606.58 | 30-SEP-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4392.32 | 31-OCT-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5353.78 | 15-NOV-16:20 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6854.36 | 04-DEC-16:20 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1437.05 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7795.02 | 444.28 | 1041.69 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1191.43 | 12-JAN-16:30 | 222.14 | 520.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3496.33 | 28-FEB-17:00 | 444.28 | 1041.69 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5688.03 | 31-MAR-23:20 | 0.00 | 28.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7575.61 | 24-APR-18:00 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3178.53 | 31-MAY-24:00 | 0.00 | 28.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5087.99 | 30-JUN-24:00 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7009.13 | 31-JUL-23:55 | 0.00 | 115.75 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7849.40 | 02-AUG-18:40 | 23.38 | 173.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2219.19 | 11-SEP-17:40 | 23.38 | 173.61 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3991.04 | 31-OCT-23:20 | 0.00 | 28.94 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5229.54 | 15-NOV-16:30 | 222.14 | 520.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6490.87 | 04-DEC-16:20 | 222.14 | 520.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1191.43 | 0.00 | 28.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7849.40 | 444.28 | 1041.69 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91026.33 | 19-JAN-17:00 | 4808.68 | 5919.59 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182619.45 | 23-FEB-17:00 | 4808.68 | 5919.59 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358188.08 | 31-MAR-24:00 | 0.00 | 328.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367506.02 | 21-APR-16:00 | 4808.68 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175939.15 | 31-MAY-24:00 | 0.00 | 328.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268034.09 | 30-JUN-24:00 | 0.00 | 328.88 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360155.42 | 31-JUL-23:55 | 0.00 | 1315.53 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369891.16 | 04-AUG-21:02 | 1518.53 | 3946.59 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175347.70 | 30-SEP-24:00 | 0.00 | 328.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268301.21 | 31-OCT-24:00 | 0.00 | 328.88 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276617.62 | 06-NOV-17:00 | 4808.68 | 5919.59 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367281.17 | 15-DEC-17:00 | 4808.68 | 5919.59 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91026.33 | 0.00 | 328.88 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369891.16 | 4808.68 | 5919.59 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.165782E+13 | 1096423.58 | 09-JAN-16:00 | 0.629527E+12 | 1894219.92 | 02-JAN-07:10 |
February | 0.184553E+13 | 1185519.56 | 21-FEB-08:50 | 0.544967E+12 | 2093215.67 | 21-FEB-07:10 |
March | 0.250633E+13 | 1545146.55 | 15-MAR-15:09 | 0.274406E+12 | 1754181.10 | 06-MAR-07:10 |
April | 0.277345E+13 | 1589851.10 | 07-APR-15:09 | 0.130127E+12 | 1151047.11 | 17-APR-06:10 |
May | 0.179304E+13 | 1271569.16 | 31-MAY-15:09 | 0.696353E+11 | 429889.85 | 04-MAY-06:10 |
June | 0.237840E+13 | 1690235.27 | 27-JUN-07:40 | 0.611647E+11 | 218576.10 | 10-JUN-06:10 |
July | 0.296965E+13 | 1941856.39 | 05-JUL-15:00 | 0.569030E+11 | 77158.91 | 03-JUL-11:20 |
August | 0.337603E+13 | 2070659.62 | 15-AUG-14:30 | 0.599449E+11 | 75897.18 | 01-AUG-11:00 |
September | 0.184468E+13 | 1478353.19 | 21-SEP-15:00 | 0.592728E+11 | 397868.10 | 30-SEP-06:10 |
October | 0.211781E+13 | 1405946.17 | 11-OCT-15:00 | 0.111492E+12 | 997764.26 | 17-OCT-06:10 |
November | 0.240860E+13 | 1508684.82 | 16-NOV-16:00 | 0.231086E+12 | 1113924.92 | 24-NOV-07:10 |
December | 0.281626E+13 | 1545770.14 | 20-DEC-16:49 | 0.556052E+12 | 2092782.34 | 26-DEC-07:10 |
Annual Sum or Average | 0.284876E+14 | 0.278458E+13 | ||||
Minimum of Months | 0.165782E+13 | 1096423.58 | 0.569030E+11 | 75897.18 | ||
Maximum of Months | 0.337603E+13 | 2070659.62 | 0.629527E+12 | 2093215.67 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.313092E+12 | 0.740319E+11 | 0.811612E+12 | 0.164871E+12 | 0.177364E+12 | 0.146378E+11 | 0.00 | 0.827576E+11 | 0.802138E+10 | 0.425448E+10 | 0.717402E+10 | 0.00 | 0.00 |
February | 0.282044E+12 | 0.607069E+11 | 0.102011E+13 | 0.148925E+12 | 0.160388E+12 | 0.137455E+11 | 0.00 | 0.137025E+12 | 0.122183E+11 | 0.380894E+10 | 0.656402E+10 | 0.00 | 0.00 |
March | 0.332627E+12 | 0.587092E+11 | 0.146267E+13 | 0.165150E+12 | 0.183439E+12 | 0.196176E+11 | 0.00 | 0.232346E+12 | 0.426999E+11 | 0.286605E+10 | 0.621150E+10 | 0.00 | 0.00 |
April | 0.296026E+12 | 0.482254E+11 | 0.170311E+13 | 0.159524E+12 | 0.180948E+12 | 0.200252E+11 | 0.00 | 0.283006E+12 | 0.777343E+11 | 0.113469E+10 | 0.371865E+10 | 0.00 | 0.00 |
May | 0.318471E+12 | 0.426553E+11 | 0.820521E+12 | 0.165009E+12 | 0.205488E+12 | 0.383798E+11 | 0.00 | 0.133651E+12 | 0.671910E+11 | 0.630110E+09 | 0.104177E+10 | 0.00 | 0.00 |
June | 0.316421E+12 | 0.381095E+11 | 0.110677E+13 | 0.159786E+12 | 0.235375E+12 | 0.744283E+11 | 0.00 | 0.313718E+12 | 0.132503E+12 | 76899366.79 | 0.120746E+10 | 0.00 | 0.00 |
July | 0.296458E+12 | 0.403825E+11 | 0.143888E+13 | 0.164745E+12 | 0.255541E+12 | 0.976684E+11 | 0.00 | 0.503955E+12 | 0.169147E+12 | 0.00 | 0.287298E+10 | 0.00 | 0.00 |
August | 0.330600E+12 | 0.464511E+11 | 0.177780E+13 | 0.165149E+12 | 0.257158E+12 | 0.939517E+11 | 0.00 | 0.544718E+12 | 0.158026E+12 | 0.00 | 0.218476E+10 | 0.00 | 0.00 |
September | 0.296764E+12 | 0.531157E+11 | 0.784732E+12 | 0.159522E+12 | 0.209778E+12 | 0.561983E+11 | 0.00 | 0.184489E+12 | 0.994035E+11 | 0.00 | 0.673243E+09 | 0.00 | 0.00 |
October | 0.310079E+12 | 0.636973E+11 | 0.112899E+13 | 0.164871E+12 | 0.185589E+12 | 0.260648E+11 | 0.00 | 0.176176E+12 | 0.587303E+11 | 0.500402E+09 | 0.311436E+10 | 0.00 | 0.00 |
November | 0.310008E+12 | 0.692860E+11 | 0.140306E+13 | 0.159634E+12 | 0.170962E+12 | 0.201489E+11 | 0.00 | 0.219729E+12 | 0.493753E+11 | 0.133613E+10 | 0.506176E+10 | 0.00 | 0.00 |
December | 0.304419E+12 | 0.760858E+11 | 0.175516E+13 | 0.164748E+12 | 0.175968E+12 | 0.174185E+11 | 0.00 | 0.278787E+12 | 0.334233E+11 | 0.332926E+10 | 0.692001E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.370701E+13 | 0.671457E+12 | 0.152134E+14 | 0.194194E+13 | 0.239800E+13 | 0.492285E+12 | 0.00 | 0.309036E+13 | 0.908474E+12 | 0.179370E+11 | 0.467445E+11 | 0.00 | 0.00 |
Minimum of Months | 0.282044E+12 | 0.381095E+11 | 0.784732E+12 | 0.148925E+12 | 0.160388E+12 | 0.137455E+11 | 0.00 | 0.827576E+11 | 0.802138E+10 | 0.00 | 0.673243E+09 | 0.00 | 0.00 |
Maximum of Months | 0.332627E+12 | 0.760858E+11 | 0.177780E+13 | 0.165150E+12 | 0.257158E+12 | 0.976684E+11 | 0.00 | 0.544718E+12 | 0.169147E+12 | 0.425448E+10 | 0.717402E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.561816E+12 | 0.00 | 0.677106E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.482846E+12 | 0.00 | 0.621206E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.203130E+12 | 0.00 | 0.712750E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.664662E+11 | 0.00 | 0.636613E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.507551E+10 | 0.00 | 0.645598E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.516222E+09 | 0.00 | 0.606485E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 5771.39 | 0.00 | 0.569030E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 24604309.44 | 0.00 | 0.599203E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.320552E+10 | 0.00 | 0.560673E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.515576E+11 | 0.00 | 0.599345E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.169752E+12 | 0.00 | 0.613342E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.491632E+12 | 0.00 | 0.644201E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.203602E+13 | 0.00 | 0.748555E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 5771.39 | 0.00 | 0.560673E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.561816E+12 | 0.00 | 0.712750E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 352853.36 | 02-JAN-16:49 | 54335.80 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 118952.11 | 11-JAN-08:20 | 104847.06 | 02-JAN-05:10 | 44834.71 | 02-JAN-07:19 | 0.00 | 01-JAN-00:10 |
February | 343386.17 | 01-FEB-16:00 | 54335.80 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 118950.91 | 01-FEB-08:20 | 97661.32 | 06-FEB-06:10 | 43646.11 | 14-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 332002.41 | 17-MAR-07:10 | 54335.80 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 118941.80 | 17-MAR-07:19 | 160097.51 | 15-MAR-14:09 | 61229.31 | 15-MAR-10:50 | 0.00 | 01-MAR-00:10 |
April | 324296.24 | 12-APR-07:10 | 54335.80 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 118935.37 | 12-APR-07:19 | 153837.00 | 21-APR-15:20 | 41381.03 | 13-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 316816.17 | 01-MAY-07:10 | 54335.80 | 01-MAY-05:10 | 439129.89 | 01-MAY-07:10 | 118929.14 | 01-MAY-07:19 | 182726.45 | 31-MAY-15:00 | 62655.62 | 31-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 316816.17 | 01-JUN-07:10 | 54335.80 | 01-JUN-19:49 | 557421.28 | 01-JUN-07:10 | 118929.14 | 01-JUN-07:19 | 229558.17 | 12-JUN-15:20 | 64696.64 | 27-JUN-07:40 | 0.00 | 01-JUN-00:10 |
July | 316816.17 | 03-JUL-07:10 | 54335.80 | 01-JUL-19:00 | 675712.68 | 03-JUL-07:10 | 118929.14 | 03-JUL-07:19 | 243500.05 | 21-JUL-12:09 | 69082.34 | 20-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 316816.17 | 01-AUG-07:10 | 54335.80 | 01-AUG-19:40 | 794004.08 | 01-AUG-07:10 | 118929.14 | 01-AUG-07:19 | 262302.90 | 09-AUG-15:20 | 69521.04 | 01-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 330046.96 | 26-SEP-07:10 | 54335.80 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 118940.17 | 26-SEP-07:19 | 219604.56 | 21-SEP-15:00 | 69270.47 | 20-SEP-14:39 | 0.00 | 01-SEP-00:10 |
October | 348630.50 | 31-OCT-07:10 | 54335.80 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 118955.69 | 31-OCT-07:19 | 160407.85 | 11-OCT-15:00 | 64919.78 | 11-OCT-14:20 | 0.00 | 01-OCT-00:10 |
November | 352853.36 | 06-NOV-16:00 | 54335.80 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 118957.30 | 02-NOV-07:19 | 168285.01 | 28-NOV-13:09 | 41600.22 | 25-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 352853.36 | 01-DEC-16:40 | 54335.80 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 118953.22 | 18-DEC-08:20 | 97240.07 | 11-DEC-06:10 | 44611.08 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 316816.17 | 54335.80 | 439129.89 | 118929.14 | 97240.07 | 41381.03 | 0.00 | |||||||
Maximum of Months | 352853.36 | 54335.80 | 794004.08 | 118957.30 | 262302.90 | 69521.04 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 39676.68 | 17-JAN-15:30 | 7648.87 | 11-JAN-15:00 | 6182.53 | 23-JAN-20:00 | 5613.48 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 65894.83 | 28-FEB-15:30 | 29716.28 | 22-FEB-17:00 | 5981.98 | 06-FEB-20:00 | 5613.48 | 01-FEB-07:10 | 0.00 | 0.00 |
March | 221675.99 | 14-MAR-13:39 | 69003.39 | 14-MAR-10:00 | 5865.32 | 06-MAR-19:00 | 5613.48 | 01-MAR-07:10 | 0.00 | 0.00 |
April | 207753.83 | 07-APR-13:00 | 50515.71 | 08-APR-13:50 | 4996.71 | 17-APR-19:00 | 5613.48 | 01-APR-06:10 | 0.00 | 0.00 |
May | 148328.51 | 10-MAY-14:50 | 69003.39 | 10-MAY-12:39 | 4634.34 | 08-MAY-18:00 | 5613.48 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 399240.30 | 27-JUN-07:40 | 88758.50 | 01-JUN-14:50 | 2555.95 | 03-JUN-16:00 | 5613.48 | 01-JUN-16:49 | 0.00 | 0.00 |
July | 500131.54 | 05-JUL-15:00 | 88758.50 | 03-JUL-12:39 | 0.00 | 01-JUL-00:10 | 5613.48 | 03-JUL-14:09 | 0.00 | 0.00 |
August | 543094.23 | 15-AUG-14:30 | 88758.50 | 01-AUG-12:00 | 0.00 | 01-AUG-00:10 | 5613.48 | 03-AUG-11:00 | 0.00 | 0.00 |
September | 319360.26 | 15-SEP-10:00 | 88758.50 | 08-SEP-13:09 | 0.00 | 01-SEP-00:10 | 5613.48 | 02-SEP-06:10 | 0.00 | 0.00 |
October | 174233.91 | 11-OCT-13:50 | 52539.68 | 11-OCT-13:00 | 3880.37 | 17-OCT-17:10 | 5613.48 | 02-OCT-06:10 | 0.00 | 0.00 |
November | 159638.44 | 16-NOV-12:00 | 50049.30 | 16-NOV-13:09 | 4193.92 | 29-NOV-20:00 | 5613.48 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 117975.50 | 01-DEC-10:50 | 49248.27 | 01-DEC-08:00 | 5935.88 | 27-DEC-21:00 | 5613.48 | 01-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 39676.68 | 7648.87 | 0.00 | 5613.48 | 0.00 | 0.00 | ||||
Maximum of Months | 543094.23 | 88758.50 | 6182.53 | 5613.48 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1096423.58 | 09-JAN-16:00 | 352853.36 | 439129.89 | 54335.80 | 84911.10 | 80511.44 | 40770.04 | 0.00 | 33073.09 | 2521.53 |
February | 1185519.56 | 21-FEB-08:50 | 316816.17 | 557421.28 | 0.00 | 118929.14 | 81739.28 | 41871.32 | 0.00 | 56408.10 | 3352.95 |
March | 1545146.55 | 15-MAR-15:09 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 145438.99 | 41101.17 | 0.00 | 206574.93 | 69003.39 |
April | 1589851.10 | 07-APR-15:09 | 316816.17 | 794004.08 | 0.00 | 84885.75 | 120674.36 | 39952.83 | 0.00 | 183979.58 | 49538.34 |
May | 1271569.16 | 31-MAY-15:09 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 177477.87 | 60614.44 | 0.00 | 139808.88 | 52836.17 |
June | 1690235.27 | 27-JUN-07:40 | 316816.17 | 557421.28 | 0.00 | 118929.14 | 144373.24 | 64696.64 | 0.00 | 399240.30 | 88758.50 |
July | 1941856.39 | 05-JUL-15:00 | 316816.17 | 675712.68 | 0.00 | 84885.75 | 206954.01 | 68597.74 | 0.00 | 500131.54 | 88758.50 |
August | 2070659.62 | 15-AUG-14:30 | 316816.17 | 794004.08 | 0.00 | 39494.57 | 219050.93 | 69441.14 | 0.00 | 543094.23 | 88758.50 |
September | 1478353.19 | 21-SEP-15:00 | 316816.17 | 439129.89 | 0.00 | 84885.75 | 219604.56 | 62311.81 | 0.00 | 261233.04 | 88758.50 |
October | 1405946.17 | 11-OCT-15:00 | 316816.17 | 557421.28 | 0.00 | 84885.75 | 160407.85 | 62166.92 | 0.00 | 172726.75 | 51521.45 |
November | 1508684.82 | 16-NOV-16:00 | 352853.36 | 675712.68 | 54335.80 | 84915.83 | 100399.50 | 40047.76 | 0.00 | 150439.33 | 49980.56 |
December | 1545770.14 | 20-DEC-16:49 | 352853.36 | 794004.08 | 54335.80 | 84915.83 | 82599.26 | 40944.91 | 0.00 | 108698.69 | 21118.98 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1096423.58 | 316816.17 | 439129.89 | 0.00 | 39494.57 | 80511.44 | 39952.83 | 0.00 | 33073.09 | 2521.53 | |
Maximum of Months | 2070659.62 | 352853.36 | 794004.08 | 54335.80 | 118929.14 | 219604.56 | 69441.14 | 0.00 | 543094.23 | 88758.50 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1864429.51 | 02-JAN-07:10 | 0.00 | 84226.60 | 30-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 2063243.41 | 21-FEB-07:10 | 0.00 | 84377.97 | 16-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 1724267.83 | 06-MAR-07:10 | 0.00 | 84199.83 | 06-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 1121452.81 | 17-APR-06:10 | 0.00 | 83238.02 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 400438.46 | 04-MAY-06:10 | 0.00 | 81609.69 | 02-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 212880.23 | 10-JUN-06:10 | 0.00 | 79421.97 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 9.62 | 11-JUL-08:30 | 0.00 | 77158.91 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 11312.02 | 31-AUG-06:19 | 0.00 | 75897.18 | 01-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 370702.09 | 30-SEP-06:10 | 0.00 | 77081.77 | 28-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 968765.32 | 17-OCT-06:10 | 0.00 | 79363.35 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 1104741.50 | 24-NOV-07:10 | 0.00 | 81535.39 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 2063098.96 | 26-DEC-07:10 | 0.00 | 83204.08 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 9.62 | 0.00 | 75897.18 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 2063243.41 | 0.00 | 84377.97 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.21 | 0.00 | 26.21 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.78 | 0.00 | 25.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.38 | 0.33 | 26.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.93 | 0.00 | 25.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.09 | 0.00 | 26.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.21 | 0.17 | 26.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 26.84 | 0.17 | 26.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.46 | 0.50 | 26.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.41 | 0.50 | 26.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.76 | 0.00 | 25.76 |
Annual Sum or Average | 0.00 | 0.00 | 46.83 | 26.37 | 1.67 | 26.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 26.84 | 0.50 | 26.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.64 | 0.00 | 25.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 25.60 | 0.00 | 25.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.91 | 0.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
February | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 18.97 | 0.17 | 19.14 | 0.17 | 19.85 | 0.00 | 19.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.35 | 0.17 | 19.35 | 0.17 | 25.57 | 0.00 | 25.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 18.86 | 1.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
February | 3.50 | 18.75 | 0.67 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
March | 1.17 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
April | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
December | 3.83 | 18.62 | 0.50 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
Annual Sum or Average | 14.17 | 18.75 | 2.17 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.17 | 19.36 | 1.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
February | 1.33 | 19.11 | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.83 | 19.13 | 0.17 | 19.24 | 0.17 | 19.73 | 0.00 | 19.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.20 | 0.17 | 19.25 | 0.17 | 25.61 | 0.00 | 25.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
February | 1.50 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.33 | 0.83 | 27.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.68 | 1.33 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.90 | 2.67 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.71 | 0.50 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.65 | 1.67 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Annual Sum or Average | 3.00 | 19.11 | 0.00 | 19.11 | 7.00 | 25.14 | 7.00 | 26.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.38 | 0.00 | 19.38 | 2.67 | 27.90 | 2.67 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
February | 2.00 | 18.77 | 0.17 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.35 | 0.50 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.51 | 2.67 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.73 | 3.17 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.86 | 3.17 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
Annual Sum or Average | 4.00 | 18.95 | 0.17 | 19.01 | 10.17 | 25.15 | 10.17 | 26.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.18 | 0.17 | 19.18 | 3.17 | 27.86 | 3.17 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.96 | 2.50 | 27.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.89 | 1.67 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.05 | 3.83 | 28.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.64 | 6.50 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.34 | 5.67 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.84 | 2.33 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.29 | 0.00 | 19.29 | 53.50 | 27.60 | 22.50 | 27.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.29 | 0.00 | 19.29 | 18.83 | 28.05 | 6.50 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.00 | 17.60 | 10.67 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
February | 39.33 | 17.56 | 11.67 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
March | 8.00 | 18.89 | 1.67 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
April | 0.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
November | 1.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
December | 32.00 | 17.50 | 10.17 | 17.69 | 0.00 | 17.69 | 0.00 | 17.69 |
Annual Sum or Average | 120.00 | 17.67 | 34.17 | 17.95 | 0.00 | 17.95 | 0.00 | 17.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.33 | 19.32 | 11.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.00 | 16.39 | 1.50 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 |
February | 19.17 | 16.22 | 0.67 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
March | 3.83 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
April | 0.33 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.74 | 1.33 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.02 | 3.50 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.95 | 0.83 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.59 | 0.50 | 27.59 |
October | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
November | 1.17 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
December | 17.00 | 16.46 | 1.17 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
Annual Sum or Average | 62.67 | 16.56 | 3.33 | 16.50 | 6.17 | 17.48 | 6.17 | 18.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.00 | 19.29 | 1.50 | 19.29 | 3.50 | 28.02 | 3.50 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.33 | 16.96 | 0.67 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
February | 19.17 | 16.88 | 1.33 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
March | 3.33 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
April | 0.33 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.52 | 2.67 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.73 | 3.17 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.88 | 3.17 | 27.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
December | 13.50 | 17.27 | 0.67 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
Annual Sum or Average | 54.50 | 17.16 | 2.67 | 17.23 | 9.00 | 18.65 | 9.00 | 19.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.17 | 19.40 | 1.33 | 19.40 | 3.17 | 27.88 | 3.17 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.33 | 16.96 | 0.50 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
February | 15.33 | 16.58 | 0.17 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
March | 3.17 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.89 | 0.67 | 27.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.17 | 2.33 | 28.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.35 | 2.50 | 28.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.98 | 2.17 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.74 | 0.67 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
December | 11.17 | 17.04 | 0.17 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
Annual Sum or Average | 45.67 | 17.00 | 0.83 | 17.01 | 16.17 | 19.88 | 8.33 | 20.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.33 | 18.99 | 0.50 | 18.99 | 5.17 | 28.35 | 2.50 | 28.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 87.00 | 16.52 | 30.50 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
February | 85.83 | 16.34 | 31.33 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
March | 34.33 | 16.97 | 10.50 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
April | 6.17 | 16.90 | 1.83 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.35 | 0.83 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.17 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
November | 9.33 | 18.07 | 1.83 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
December | 75.17 | 16.42 | 27.33 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
Annual Sum or Average | 300.00 | 16.56 | 103.33 | 16.78 | 1.00 | 16.80 | 0.83 | 16.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.00 | 18.14 | 31.33 | 18.14 | 1.00 | 27.35 | 0.83 | 27.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.17 | 15.40 | 13.00 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
February | 52.33 | 15.36 | 11.83 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
March | 17.67 | 16.26 | 0.50 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
April | 4.00 | 17.28 | 0.33 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.73 | 1.00 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.98 | 4.33 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.75 | 1.33 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.17 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
November | 7.83 | 17.55 | 0.33 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
December | 51.17 | 15.38 | 12.00 | 15.28 | 0.00 | 15.28 | 0.00 | 15.28 |
Annual Sum or Average | 190.33 | 15.62 | 38.00 | 15.51 | 6.67 | 15.86 | 6.67 | 16.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.17 | 17.89 | 13.00 | 17.89 | 4.33 | 27.98 | 4.33 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.17 | 15.90 | 11.17 | 15.89 | 0.00 | 15.89 | 0.00 | 15.89 |
February | 51.00 | 15.83 | 12.67 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
March | 13.67 | 16.72 | 0.50 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
April | 3.83 | 17.14 | 1.00 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.52 | 0.83 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.69 | 3.50 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.76 | 3.67 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.78 | 2.50 | 27.78 |
October | 1.33 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
November | 6.00 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
December | 43.17 | 15.98 | 8.17 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 |
Annual Sum or Average | 169.17 | 16.09 | 33.50 | 16.10 | 10.83 | 16.69 | 10.50 | 17.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.00 | 18.20 | 12.67 | 18.20 | 3.83 | 27.78 | 3.67 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 45.00 | 15.38 | 11.50 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
February | 38.17 | 15.48 | 7.67 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
March | 11.67 | 16.75 | 1.00 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
April | 1.83 | 18.24 | 0.17 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.89 | 0.50 | 27.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.19 | 2.67 | 28.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.45 | 2.67 | 28.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.12 | 2.00 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.58 | 0.50 | 27.60 |
October | 1.33 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
November | 5.17 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
December | 33.83 | 15.57 | 5.67 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
Annual Sum or Average | 137.00 | 15.75 | 26.00 | 15.62 | 16.50 | 16.78 | 8.33 | 17.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 0.00 | 15.27 |
Maximum of Months | 45.00 | 18.45 | 11.50 | 18.45 | 5.50 | 28.45 | 2.67 | 28.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 134.33 | 28.35 | 124.17 | 28.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 134.33 | 28.35 | 124.17 | 28.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 134.33 | 28.35 | 124.17 | 28.36 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 360.67 | 23.84 | 33.50 | 24.02 | 12.00 | 24.10 |
February | 338.33 | 23.70 | 18.33 | 23.82 | 0.00 | 23.82 |
March | 224.83 | 23.93 | 91.50 | 24.24 | 0.00 | 24.24 |
April | 34.17 | 24.00 | 94.67 | 25.58 | 0.00 | 25.58 |
May | 24.17 | 24.00 | 184.33 | 25.06 | 0.00 | 25.06 |
June | 91.83 | 24.66 | 347.17 | 24.64 | 91.67 | 24.64 |
July | 178.83 | 25.04 | 484.17 | 24.73 | 178.83 | 24.80 |
August | 75.50 | 24.89 | 475.17 | 24.57 | 75.50 | 24.61 |
September | 45.67 | 25.10 | 368.33 | 24.76 | 45.67 | 24.79 |
October | 1.67 | 24.00 | 214.50 | 25.27 | 0.00 | 25.27 |
November | 45.33 | 24.01 | 125.33 | 25.48 | 0.00 | 25.48 |
December | 209.50 | 23.89 | 71.33 | 24.45 | 0.00 | 24.45 |
Annual Sum or Average | 1630.50 | 24.10 | 2508.33 | 24.60 | 403.67 | 24.63 |
Minimum of Months | 1.67 | 23.70 | 18.33 | 23.82 | 0.00 | 23.82 |
Maximum of Months | 360.67 | 25.10 | 484.17 | 25.58 | 178.83 | 25.58 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 434.50 | 23.75 | 12.67 | 23.77 | 12.67 | 23.79 |
February | 385.00 | 23.78 | 0.00 | 23.78 | 0.00 | 23.78 |
March | 205.00 | 23.95 | 93.17 | 24.18 | 0.00 | 24.18 |
April | 32.83 | 23.97 | 95.50 | 25.08 | 0.00 | 25.08 |
May | 35.33 | 23.95 | 180.00 | 24.66 | 0.00 | 24.66 |
June | 0.17 | 23.96 | 365.00 | 24.33 | 0.00 | 24.33 |
July | 0.00 | 0.00 | 487.33 | 24.27 | 0.00 | 24.27 |
August | 0.00 | 0.00 | 492.67 | 24.24 | 0.00 | 24.24 |
September | 5.33 | 25.65 | 366.17 | 24.45 | 3.67 | 24.47 |
October | 26.67 | 23.90 | 213.83 | 24.77 | 0.00 | 24.77 |
November | 67.00 | 23.95 | 95.50 | 24.96 | 0.00 | 24.96 |
December | 261.67 | 23.90 | 39.33 | 24.10 | 0.00 | 24.10 |
Annual Sum or Average | 1453.50 | 23.84 | 2441.17 | 24.27 | 16.33 | 24.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.77 | 0.00 | 23.78 |
Maximum of Months | 434.50 | 25.65 | 492.67 | 25.08 | 12.67 | 25.08 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.95 | 80.83 | 21.68 | 80.83 | 21.49 |
February | 454.00 | 22.15 | 57.67 | 22.00 | 57.67 | 21.89 |
March | 424.00 | 23.16 | 31.83 | 23.21 | 2.17 | 23.20 |
April | 302.33 | 23.51 | 9.50 | 23.55 | 0.00 | 23.55 |
May | 134.83 | 23.72 | 134.33 | 24.16 | 0.00 | 24.16 |
June | 24.00 | 23.74 | 303.83 | 24.22 | 0.00 | 24.22 |
July | 0.00 | 0.00 | 478.17 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 446.33 | 24.26 | 0.00 | 24.26 |
September | 39.17 | 23.69 | 275.00 | 24.29 | 3.33 | 24.31 |
October | 260.67 | 23.61 | 50.33 | 23.73 | 0.00 | 23.73 |
November | 414.67 | 23.41 | 1.67 | 23.41 | 0.00 | 23.41 |
December | 489.67 | 22.32 | 35.50 | 22.20 | 35.50 | 22.10 |
Annual Sum or Average | 3045.33 | 22.82 | 1905.00 | 23.25 | 179.50 | 23.16 |
Minimum of Months | 0.00 | 0.00 | 1.67 | 21.68 | 0.00 | 21.49 |
Maximum of Months | 502.00 | 23.74 | 478.17 | 24.29 | 80.83 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.77 | 284.50 | 20.50 | 284.50 | 20.37 |
February | 454.00 | 20.97 | 227.17 | 20.65 | 227.17 | 20.50 |
March | 459.33 | 21.87 | 140.83 | 21.65 | 117.50 | 21.42 |
April | 410.00 | 22.71 | 22.00 | 22.57 | 20.67 | 22.45 |
May | 228.00 | 23.43 | 87.83 | 23.68 | 0.00 | 23.68 |
June | 55.83 | 23.65 | 299.00 | 24.13 | 0.00 | 24.13 |
July | 0.00 | 0.00 | 471.17 | 24.29 | 0.00 | 24.29 |
August | 5.17 | 23.47 | 437.00 | 24.25 | 0.00 | 24.25 |
September | 130.67 | 23.29 | 216.00 | 23.90 | 2.83 | 23.90 |
October | 392.00 | 22.48 | 47.50 | 22.39 | 31.67 | 22.26 |
November | 483.83 | 22.01 | 74.33 | 21.77 | 74.33 | 21.59 |
December | 497.00 | 20.91 | 237.50 | 20.61 | 237.50 | 20.45 |
Annual Sum or Average | 3617.83 | 21.83 | 2544.83 | 22.16 | 996.17 | 21.87 |
Minimum of Months | 0.00 | 0.00 | 22.00 | 20.50 | 0.00 | 20.37 |
Maximum of Months | 502.00 | 23.65 | 471.17 | 24.29 | 284.50 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.06 | 261.17 | 20.92 | 261.17 | 20.86 |
February | 454.00 | 21.22 | 194.17 | 21.06 | 194.17 | 20.98 |
March | 442.17 | 22.25 | 86.33 | 22.21 | 56.33 | 22.08 |
April | 344.33 | 23.18 | 17.17 | 23.26 | 0.00 | 23.26 |
May | 196.17 | 23.49 | 100.17 | 23.84 | 0.00 | 23.84 |
June | 23.33 | 24.13 | 333.17 | 24.31 | 4.17 | 24.32 |
July | 3.17 | 26.37 | 482.67 | 24.36 | 3.17 | 24.37 |
August | 5.83 | 24.46 | 460.83 | 24.25 | 1.67 | 24.26 |
September | 95.00 | 23.49 | 229.33 | 24.07 | 8.33 | 24.12 |
October | 350.83 | 23.09 | 36.17 | 23.22 | 0.00 | 23.22 |
November | 452.83 | 22.75 | 8.33 | 22.80 | 0.00 | 22.80 |
December | 497.00 | 21.57 | 104.00 | 21.42 | 104.00 | 21.31 |
Annual Sum or Average | 3366.67 | 22.21 | 2313.50 | 22.68 | 633.00 | 22.49 |
Minimum of Months | 3.17 | 21.06 | 8.33 | 20.92 | 0.00 | 20.86 |
Maximum of Months | 502.00 | 26.37 | 482.67 | 24.36 | 261.17 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.93 | 248.33 | 20.83 | 248.33 | 20.78 |
February | 454.00 | 21.07 | 204.17 | 20.94 | 204.17 | 20.87 |
March | 464.00 | 21.97 | 63.83 | 21.98 | 38.50 | 21.90 |
April | 350.50 | 22.45 | 37.17 | 22.65 | 0.50 | 22.64 |
May | 217.00 | 22.90 | 161.83 | 23.58 | 3.00 | 23.61 |
June | 74.33 | 23.48 | 339.83 | 24.13 | 9.33 | 24.18 |
July | 22.83 | 25.54 | 454.67 | 24.27 | 15.67 | 24.34 |
August | 59.00 | 23.02 | 389.17 | 23.96 | 2.83 | 23.98 |
September | 158.00 | 22.88 | 258.33 | 23.79 | 9.17 | 23.84 |
October | 380.00 | 22.46 | 58.83 | 22.74 | 0.00 | 22.74 |
November | 462.50 | 21.91 | 9.17 | 21.96 | 1.33 | 21.96 |
December | 497.00 | 21.06 | 164.00 | 20.96 | 164.00 | 20.90 |
Annual Sum or Average | 3641.17 | 21.84 | 2389.33 | 22.41 | 696.83 | 22.26 |
Minimum of Months | 22.83 | 20.93 | 9.17 | 20.83 | 0.00 | 20.78 |
Maximum of Months | 502.00 | 25.54 | 454.67 | 24.27 | 248.33 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.17 | 21.13 | 237.50 | 20.95 | 233.33 | 20.84 |
February | 431.83 | 21.26 | 181.17 | 21.03 | 181.17 | 20.91 |
March | 378.83 | 22.17 | 82.33 | 22.28 | 36.67 | 22.17 |
April | 317.33 | 22.66 | 57.00 | 22.88 | 6.50 | 22.84 |
May | 217.67 | 23.04 | 145.17 | 23.62 | 2.00 | 23.64 |
June | 65.83 | 23.57 | 340.50 | 24.16 | 7.83 | 24.19 |
July | 28.83 | 25.73 | 467.83 | 24.41 | 21.50 | 24.50 |
August | 36.33 | 24.85 | 449.33 | 24.31 | 17.00 | 24.39 |
September | 110.67 | 23.52 | 317.33 | 24.20 | 18.33 | 24.30 |
October | 283.33 | 22.64 | 114.50 | 23.17 | 0.50 | 23.18 |
November | 396.00 | 22.15 | 43.00 | 22.36 | 5.83 | 22.34 |
December | 477.50 | 21.33 | 161.50 | 21.18 | 158.17 | 21.07 |
Annual Sum or Average | 3228.33 | 22.05 | 2597.17 | 22.67 | 688.83 | 22.51 |
Minimum of Months | 28.83 | 21.13 | 43.00 | 20.95 | 0.50 | 20.84 |
Maximum of Months | 484.17 | 25.73 | 467.83 | 24.41 | 233.33 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.50 | 21.22 | 135.17 | 21.13 | 134.00 | 21.07 |
February | 443.33 | 21.64 | 49.50 | 21.56 | 49.50 | 21.50 |
March | 316.67 | 22.70 | 83.17 | 23.08 | 0.17 | 23.08 |
April | 126.67 | 23.47 | 194.67 | 24.31 | 9.17 | 24.38 |
May | 160.00 | 23.13 | 216.00 | 24.03 | 7.83 | 24.08 |
June | 33.00 | 25.93 | 444.50 | 24.55 | 24.50 | 24.66 |
July | 51.00 | 26.81 | 495.83 | 24.72 | 51.00 | 24.89 |
August | 36.17 | 26.80 | 514.00 | 24.58 | 36.17 | 24.72 |
September | 98.83 | 23.49 | 327.00 | 24.22 | 17.00 | 24.32 |
October | 237.67 | 22.90 | 136.33 | 23.53 | 0.00 | 23.53 |
November | 333.50 | 22.89 | 44.83 | 23.18 | 0.00 | 23.18 |
December | 473.50 | 22.41 | 6.17 | 22.43 | 2.67 | 22.42 |
Annual Sum or Average | 2809.83 | 22.51 | 2647.17 | 23.37 | 332.00 | 23.37 |
Minimum of Months | 33.00 | 21.22 | 6.17 | 21.13 | 0.00 | 21.07 |
Maximum of Months | 499.50 | 26.81 | 514.00 | 24.72 | 134.00 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.99 | 471.67 | 19.96 | 471.67 | 19.95 |
February | 454.00 | 20.04 | 426.67 | 20.01 | 426.67 | 20.00 |
March | 487.50 | 20.93 | 271.50 | 20.76 | 257.00 | 20.63 |
April | 479.33 | 21.86 | 58.83 | 21.66 | 58.83 | 21.50 |
May | 345.00 | 23.05 | 51.33 | 23.20 | 0.00 | 23.20 |
June | 84.67 | 23.72 | 273.67 | 24.10 | 10.17 | 24.14 |
July | 26.67 | 25.39 | 462.67 | 24.39 | 24.33 | 24.45 |
August | 39.33 | 23.47 | 393.50 | 24.17 | 3.50 | 24.18 |
September | 235.17 | 23.07 | 149.00 | 23.52 | 12.00 | 23.59 |
October | 472.33 | 21.82 | 72.33 | 21.67 | 67.33 | 21.53 |
November | 489.00 | 20.96 | 178.33 | 20.76 | 178.33 | 20.64 |
December | 497.00 | 20.05 | 429.50 | 19.98 | 429.50 | 19.95 |
Annual Sum or Average | 4112.00 | 21.24 | 3239.00 | 21.48 | 1939.33 | 21.21 |
Minimum of Months | 26.67 | 19.99 | 51.33 | 19.96 | 0.00 | 19.95 |
Maximum of Months | 502.00 | 25.39 | 471.67 | 24.39 | 471.67 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.88 | 406.33 | 19.86 | 406.33 | 19.85 |
February | 385.00 | 19.98 | 349.67 | 19.92 | 349.67 | 19.90 |
March | 417.83 | 20.93 | 189.67 | 20.76 | 180.50 | 20.64 |
April | 351.67 | 21.55 | 63.00 | 21.55 | 42.67 | 21.40 |
May | 260.67 | 22.42 | 87.50 | 22.99 | 1.50 | 23.01 |
June | 112.00 | 23.20 | 243.67 | 23.99 | 13.00 | 24.08 |
July | 55.67 | 25.31 | 368.33 | 24.52 | 39.00 | 24.68 |
August | 85.67 | 23.00 | 292.17 | 24.02 | 7.50 | 24.08 |
September | 210.50 | 22.58 | 151.00 | 23.35 | 13.33 | 23.45 |
October | 395.33 | 21.58 | 49.83 | 21.52 | 42.50 | 21.42 |
November | 417.00 | 20.86 | 157.00 | 20.69 | 157.00 | 20.59 |
December | 422.00 | 19.93 | 379.50 | 19.87 | 379.50 | 19.85 |
Annual Sum or Average | 3540.33 | 21.10 | 2737.67 | 21.44 | 1632.50 | 21.19 |
Minimum of Months | 55.67 | 19.88 | 49.83 | 19.86 | 1.50 | 19.85 |
Maximum of Months | 427.00 | 25.31 | 406.33 | 24.52 | 406.33 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.83 | 20.41 | 372.00 | 20.24 | 369.67 | 20.16 |
February | 441.50 | 20.47 | 310.00 | 20.25 | 310.00 | 20.15 |
March | 425.00 | 21.50 | 149.50 | 21.38 | 122.33 | 21.20 |
April | 370.17 | 21.83 | 72.17 | 21.91 | 38.33 | 21.77 |
May | 273.33 | 22.66 | 103.83 | 23.15 | 1.83 | 23.17 |
June | 116.00 | 23.21 | 281.83 | 23.94 | 10.50 | 23.99 |
July | 60.50 | 24.94 | 447.67 | 24.43 | 38.17 | 24.55 |
August | 73.67 | 23.86 | 408.00 | 24.26 | 17.33 | 24.35 |
September | 163.33 | 23.23 | 272.83 | 23.97 | 22.50 | 24.10 |
October | 349.00 | 22.04 | 107.50 | 22.41 | 22.33 | 22.31 |
November | 432.83 | 21.34 | 124.33 | 21.21 | 111.83 | 21.07 |
December | 487.83 | 20.40 | 351.00 | 20.25 | 351.00 | 20.18 |
Annual Sum or Average | 3684.00 | 21.47 | 3000.67 | 21.91 | 1415.83 | 21.66 |
Minimum of Months | 60.50 | 20.40 | 72.17 | 20.24 | 1.83 | 20.15 |
Maximum of Months | 490.83 | 24.94 | 447.67 | 24.43 | 369.67 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.13 | 446.67 | 20.08 | 446.67 | 20.06 |
February | 454.00 | 20.26 | 370.17 | 20.16 | 370.17 | 20.13 |
March | 484.00 | 21.15 | 179.33 | 21.00 | 168.67 | 20.88 |
April | 416.33 | 21.67 | 67.67 | 21.77 | 32.33 | 21.66 |
May | 318.67 | 22.49 | 120.33 | 23.05 | 3.67 | 23.09 |
June | 122.83 | 23.26 | 321.00 | 24.03 | 17.50 | 24.12 |
July | 56.67 | 24.93 | 441.67 | 24.43 | 34.33 | 24.55 |
August | 83.17 | 23.38 | 390.17 | 24.17 | 13.50 | 24.24 |
September | 261.00 | 22.64 | 172.67 | 23.33 | 14.17 | 23.43 |
October | 459.50 | 21.61 | 56.50 | 21.63 | 36.33 | 21.56 |
November | 489.00 | 21.01 | 140.50 | 20.86 | 140.50 | 20.77 |
December | 497.00 | 20.22 | 390.33 | 20.12 | 390.33 | 20.08 |
Annual Sum or Average | 4144.17 | 21.26 | 3097.00 | 21.65 | 1668.17 | 21.42 |
Minimum of Months | 56.67 | 20.13 | 56.50 | 20.08 | 3.67 | 20.06 |
Maximum of Months | 502.00 | 24.93 | 446.67 | 24.43 | 446.67 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.75 | 493.67 | 19.74 | 493.67 | 19.74 |
February | 454.00 | 19.81 | 449.50 | 19.80 | 449.50 | 19.80 |
March | 495.17 | 20.48 | 350.00 | 20.33 | 340.00 | 20.24 |
April | 483.00 | 21.15 | 156.33 | 20.87 | 156.33 | 20.70 |
May | 396.33 | 22.43 | 47.50 | 22.52 | 11.33 | 22.47 |
June | 142.83 | 23.23 | 257.17 | 23.85 | 11.83 | 23.90 |
July | 47.00 | 24.70 | 443.00 | 24.34 | 29.33 | 24.42 |
August | 83.00 | 23.10 | 352.33 | 24.00 | 5.83 | 24.02 |
September | 306.00 | 22.49 | 110.33 | 22.92 | 14.50 | 22.99 |
October | 496.00 | 21.01 | 151.83 | 20.69 | 150.00 | 20.49 |
November | 489.00 | 20.29 | 322.33 | 20.13 | 322.33 | 20.06 |
December | 497.00 | 19.76 | 474.17 | 19.74 | 474.17 | 19.73 |
Annual Sum or Average | 4391.33 | 20.86 | 3608.17 | 21.06 | 2458.83 | 20.80 |
Minimum of Months | 47.00 | 19.75 | 47.50 | 19.74 | 5.83 | 19.73 |
Maximum of Months | 502.00 | 24.70 | 493.67 | 24.34 | 493.67 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 494.33 | 19.81 | 494.33 | 19.81 |
February | 454.00 | 19.89 | 429.67 | 19.86 | 429.67 | 19.85 |
March | 493.33 | 20.54 | 292.50 | 20.36 | 278.67 | 20.23 |
April | 423.67 | 21.25 | 109.50 | 21.02 | 100.00 | 20.80 |
May | 305.83 | 22.23 | 112.17 | 22.78 | 5.00 | 22.78 |
June | 128.17 | 23.11 | 311.00 | 23.95 | 15.83 | 24.03 |
July | 65.50 | 25.20 | 443.83 | 24.46 | 45.33 | 24.61 |
August | 104.67 | 23.03 | 367.50 | 23.99 | 12.33 | 24.05 |
September | 239.83 | 22.23 | 189.50 | 23.12 | 12.67 | 23.18 |
October | 481.83 | 21.11 | 118.50 | 20.84 | 115.67 | 20.65 |
November | 489.00 | 20.37 | 305.33 | 20.20 | 305.33 | 20.13 |
December | 497.00 | 19.81 | 474.83 | 19.79 | 474.83 | 19.78 |
Annual Sum or Average | 4184.83 | 20.85 | 3648.67 | 21.19 | 2289.67 | 20.94 |
Minimum of Months | 65.50 | 19.81 | 109.50 | 19.79 | 5.00 | 19.78 |
Maximum of Months | 502.00 | 25.20 | 494.33 | 24.46 | 494.33 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.17 | 20.07 | 431.17 | 19.94 | 431.17 | 19.89 |
February | 447.33 | 20.09 | 360.33 | 19.90 | 360.33 | 19.83 |
March | 452.50 | 20.95 | 235.50 | 20.73 | 215.00 | 20.55 |
April | 401.83 | 21.33 | 135.50 | 21.24 | 107.00 | 21.03 |
May | 330.17 | 22.32 | 96.00 | 22.72 | 11.33 | 22.70 |
June | 153.33 | 22.93 | 268.83 | 23.77 | 13.67 | 23.84 |
July | 83.00 | 24.58 | 425.00 | 24.40 | 45.83 | 24.54 |
August | 102.67 | 23.47 | 380.17 | 24.14 | 19.83 | 24.24 |
September | 205.83 | 22.67 | 239.33 | 23.58 | 21.00 | 23.70 |
October | 399.83 | 21.41 | 145.17 | 21.45 | 86.00 | 21.20 |
November | 465.33 | 20.78 | 230.33 | 20.53 | 226.00 | 20.38 |
December | 495.83 | 20.01 | 434.50 | 19.91 | 434.50 | 19.87 |
Annual Sum or Average | 4037.83 | 21.11 | 3381.83 | 21.44 | 1971.67 | 21.17 |
Minimum of Months | 83.00 | 20.01 | 96.00 | 19.90 | 11.33 | 19.83 |
Maximum of Months | 500.17 | 24.58 | 434.50 | 24.40 | 434.50 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.88 | 480.00 | 19.85 | 480.00 | 19.84 |
February | 454.00 | 19.99 | 407.67 | 19.92 | 407.67 | 19.90 |
March | 492.33 | 20.76 | 256.67 | 20.56 | 249.33 | 20.43 |
April | 427.83 | 21.23 | 126.00 | 21.19 | 97.00 | 21.01 |
May | 356.00 | 22.14 | 100.83 | 22.66 | 5.67 | 22.69 |
June | 148.67 | 22.96 | 298.00 | 23.86 | 20.17 | 23.97 |
July | 80.33 | 24.36 | 418.17 | 24.37 | 38.83 | 24.51 |
August | 114.67 | 23.09 | 362.50 | 24.03 | 16.50 | 24.12 |
September | 300.50 | 22.28 | 148.00 | 22.95 | 13.50 | 23.05 |
October | 472.50 | 21.09 | 119.50 | 20.93 | 104.00 | 20.75 |
November | 489.00 | 20.53 | 249.50 | 20.33 | 249.50 | 20.23 |
December | 497.00 | 19.89 | 450.00 | 19.84 | 450.00 | 19.82 |
Annual Sum or Average | 4334.83 | 20.96 | 3416.83 | 21.27 | 2132.17 | 21.03 |
Minimum of Months | 80.33 | 19.88 | 100.83 | 19.84 | 5.67 | 19.82 |
Maximum of Months | 502.00 | 24.36 | 480.00 | 24.37 | 480.00 | 24.51 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 469.50 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 451.50 | 27.00 | 0.00 | 27.00 |
March | 12.67 | 27.00 | 514.00 | 27.00 | 12.67 | 27.00 |
April | 47.00 | 27.00 | 485.00 | 27.00 | 47.00 | 27.00 |
May | 6.50 | 27.00 | 508.00 | 27.00 | 6.50 | 27.00 |
June | 106.50 | 27.00 | 496.00 | 27.00 | 106.50 | 27.00 |
July | 261.83 | 27.00 | 497.00 | 27.00 | 261.83 | 27.00 |
August | 375.33 | 27.00 | 514.00 | 27.00 | 375.33 | 27.00 |
September | 15.50 | 27.00 | 485.00 | 27.00 | 15.50 | 27.00 |
October | 9.50 | 27.00 | 502.00 | 27.00 | 9.50 | 27.00 |
November | 2.33 | 27.00 | 489.00 | 27.00 | 2.33 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 837.17 | 27.00 | 5908.00 | 27.00 | 837.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 451.50 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 375.33 | 27.00 | 514.00 | 27.00 | 375.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 87.50 | 25.35 | 167.67 | 26.43 | 0.00 | 26.43 |
February | 10.33 | 27.00 | 219.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 446.67 | 27.00 | 0.00 | 27.00 |
April | 1.50 | 27.00 | 485.00 | 27.00 | 1.50 | 27.00 |
May | 2.00 | 27.00 | 508.00 | 27.00 | 2.00 | 27.00 |
June | 10.83 | 27.00 | 496.00 | 27.00 | 10.83 | 27.00 |
July | 51.50 | 27.00 | 497.00 | 27.00 | 51.50 | 27.00 |
August | 74.17 | 27.00 | 514.00 | 27.00 | 74.17 | 27.00 |
September | 2.67 | 27.00 | 485.00 | 27.00 | 2.67 | 27.00 |
October | 1.17 | 27.00 | 502.00 | 27.00 | 1.17 | 27.00 |
November | 0.00 | 0.00 | 487.83 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 337.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 241.67 | 26.40 | 5145.33 | 26.97 | 143.83 | 26.97 |
Minimum of Months | 0.00 | 0.00 | 167.67 | 26.43 | 0.00 | 26.43 |
Maximum of Months | 87.50 | 27.00 | 514.00 | 27.00 | 74.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 255.50 | 24.85 | 119.33 | 25.13 | 33.83 | 24.92 |
February | 77.83 | 27.00 | 139.00 | 27.00 | 0.00 | 27.00 |
March | 23.67 | 27.00 | 356.17 | 27.00 | 0.00 | 27.00 |
April | 0.50 | 27.00 | 462.83 | 27.00 | 0.50 | 27.00 |
May | 3.50 | 27.00 | 508.00 | 27.00 | 3.50 | 27.00 |
June | 42.67 | 27.00 | 496.00 | 27.00 | 42.67 | 27.00 |
July | 107.50 | 27.00 | 497.00 | 27.00 | 107.50 | 27.00 |
August | 108.67 | 27.00 | 514.00 | 27.00 | 108.67 | 27.00 |
September | 4.17 | 27.00 | 485.00 | 27.00 | 4.17 | 27.00 |
October | 1.50 | 27.00 | 461.67 | 27.00 | 1.50 | 27.00 |
November | 1.67 | 27.00 | 405.17 | 27.00 | 0.00 | 27.00 |
December | 63.67 | 27.00 | 227.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 690.83 | 26.21 | 4671.50 | 26.87 | 302.33 | 26.85 |
Minimum of Months | 0.50 | 24.85 | 119.33 | 25.13 | 0.00 | 24.92 |
Maximum of Months | 255.50 | 27.00 | 514.00 | 27.00 | 108.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 151.67 | 27.00 | 502.00 | 27.00 | 151.67 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 500.33 | 27.00 | 508.00 | 27.00 | 500.33 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.37 | 514.00 | 27.37 | 514.00 | 27.37 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
Annual Sum or Average | 5585.00 | 27.04 | 5943.00 | 27.04 | 5585.00 | 27.04 |
Minimum of Months | 151.67 | 27.00 | 454.00 | 27.00 | 151.67 | 27.00 |
Maximum of Months | 514.00 | 27.37 | 514.00 | 27.37 | 514.00 | 27.37 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 16.91498 | 0.64810 | 13.94435 |
February | 454.00000 | 27.00000 | 16.13067 | 0.68741 | 15.03694 |
March | 514.00000 | 27.00007 | 21.75485 | 0.83591 | 19.96361 |
April | 485.00000 | 27.00000 | 26.65016 | 0.94207 | 23.82401 |
May | 508.00000 | 27.00023 | 30.43617 | 0.22090 | 6.15725 |
June | 496.00000 | 27.00083 | 35.01204 | 0.34552 | 7.58438 |
July | 497.00000 | 27.00078 | 37.34455 | 0.41641 | 8.68272 |
August | 514.00000 | 27.00020 | 36.65190 | 0.45111 | 9.31849 |
September | 485.00000 | 27.00058 | 36.07576 | 0.27801 | 6.71898 |
October | 502.00000 | 27.00016 | 30.28909 | 0.89864 | 22.14059 |
November | 489.00000 | 27.00000 | 26.09449 | 0.87244 | 21.16398 |
December | 497.00000 | 27.00000 | 19.08307 | 0.79499 | 18.43739 |
Annual Sum or Average | 5943.00000 | 27.00024 | 27.77977 | 0.61486 | 14.39061 |
Minimum of Months | 454.00000 | 27.00000 | 16.13067 | 0.22090 | 6.15725 |
Maximum of Months | 514.00000 | 27.00083 | 37.34455 | 0.94207 | 23.82401 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.64744 | 17.09161 | 0.44721 | 10.02356 |
February | 454.00000 | 27.00000 | 16.11442 | 0.53403 | 11.13759 |
March | 514.00000 | 27.00007 | 21.74185 | 0.68475 | 15.19205 |
April | 485.00000 | 27.00001 | 26.62315 | 0.78674 | 18.20458 |
May | 508.00000 | 27.00020 | 30.45166 | 0.13324 | 5.56595 |
June | 496.00000 | 27.00082 | 35.02097 | 0.25453 | 6.50438 |
July | 497.00000 | 27.00083 | 37.35507 | 0.31604 | 7.17630 |
August | 514.00000 | 27.00023 | 36.63655 | 0.32365 | 7.29821 |
September | 485.00000 | 27.00044 | 36.19409 | 0.19267 | 5.93984 |
October | 502.00000 | 27.00015 | 30.27129 | 0.78235 | 18.04468 |
November | 489.00000 | 27.00000 | 26.05579 | 0.71149 | 15.78485 |
December | 497.00000 | 27.00000 | 19.05477 | 0.58892 | 12.46498 |
Annual Sum or Average | 5943.00000 | 26.97045 | 27.79435 | 0.47865 | 11.09725 |
Minimum of Months | 454.00000 | 26.64744 | 16.11442 | 0.13324 | 5.56595 |
Maximum of Months | 514.00000 | 27.00083 | 37.35507 | 0.78674 | 18.20458 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.82901 | 17.47042 | 0.23435 | 8.59240 |
February | 454.00000 | 26.99990 | 16.11588 | 0.47492 | 9.99648 |
March | 514.00000 | 27.00007 | 21.75287 | 0.62246 | 13.66074 |
April | 485.00000 | 27.00001 | 26.63458 | 0.73540 | 16.67700 |
May | 508.00000 | 27.00020 | 30.48670 | 0.10108 | 5.55806 |
June | 496.00000 | 27.00083 | 35.03804 | 0.25276 | 6.59924 |
July | 497.00000 | 27.00083 | 37.37054 | 0.32560 | 7.37385 |
August | 514.00000 | 27.00025 | 36.65810 | 0.32312 | 7.37482 |
September | 485.00000 | 27.00041 | 36.26979 | 0.16242 | 5.85396 |
October | 502.00000 | 27.00015 | 30.30021 | 0.72135 | 16.24379 |
November | 489.00000 | 27.00000 | 26.07321 | 0.63484 | 13.69400 |
December | 497.00000 | 27.00000 | 19.06578 | 0.51781 | 10.89434 |
Annual Sum or Average | 5943.00000 | 26.90131 | 27.84689 | 0.42456 | 10.19996 |
Minimum of Months | 454.00000 | 25.82901 | 16.11588 | 0.10108 | 5.55806 |
Maximum of Months | 514.00000 | 27.00083 | 37.37054 | 0.73540 | 16.67700 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00029 | 30.36911 | 1.00790 | 26.46890 |
February | 454.00000 | 27.00446 | 30.11567 | 1.17130 | 33.86893 |
March | 514.00000 | 27.00552 | 31.13965 | 1.35509 | 43.14610 |
April | 485.00000 | 27.00303 | 30.82112 | 1.49993 | 50.89835 |
May | 508.00000 | 27.00071 | 32.62432 | 0.49449 | 10.16626 |
June | 496.00000 | 27.00119 | 35.27416 | 0.76349 | 17.31453 |
July | 497.00000 | 27.00077 | 37.16691 | 0.98904 | 25.68404 |
August | 514.00000 | 27.36734 | 36.33600 | 1.28723 | 39.84684 |
September | 485.00000 | 27.00124 | 35.73142 | 0.58144 | 12.13917 |
October | 502.00000 | 27.00139 | 32.26570 | 1.26483 | 38.49143 |
November | 489.00000 | 27.00352 | 30.97065 | 1.38603 | 44.77295 |
December | 497.00000 | 27.00884 | 30.28561 | 1.48530 | 50.10373 |
Annual Sum or Average | 5943.00000 | 27.03433 | 32.78030 | 1.10680 | 32.73281 |
Minimum of Months | 454.00000 | 27.00029 | 30.11567 | 0.49449 | 10.16626 |
Maximum of Months | 514.00000 | 27.36734 | 37.16691 | 1.49993 | 50.89835 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.11946 | 17.89727 | 0.22406 | 6.84881 |
February | 454.00000 | 24.05337 | 16.59236 | 0.19823 | 6.27610 |
March | 514.00000 | 24.29184 | 22.99199 | 0.31550 | 7.47311 |
April | 485.00000 | 24.45570 | 26.44940 | 0.38298 | 8.49845 |
May | 508.00000 | 24.45831 | 32.25799 | -0.4322 | 9.81082 |
June | 496.00000 | 24.44653 | 46.21462 | -0.3192 | 8.09745 |
July | 497.00000 | 24.59876 | 57.23969 | -0.1878 | 7.12461 |
August | 514.00000 | 24.47847 | 51.13560 | -0.2569 | 7.45948 |
September | 485.00000 | 24.54257 | 45.38086 | -0.2885 | 7.95246 |
October | 502.00000 | 24.55604 | 32.01562 | 0.45729 | 9.96186 |
November | 489.00000 | 24.54966 | 25.22869 | 0.40253 | 8.95531 |
December | 497.00000 | 24.40557 | 19.03635 | 0.31089 | 7.47737 |
Annual Sum or Average | 5943.00000 | 24.41489 | 32.82584 | 0.06530 | 8.00587 |
Minimum of Months | 454.00000 | 24.05337 | 16.59236 | -0.4322 | 6.27610 |
Maximum of Months | 514.00000 | 24.59876 | 57.23969 | 0.45729 | 9.96186 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.82058 | 22.34360 | 0.16317 | 6.12716 |
February | 454.00000 | 23.89396 | 19.71613 | 0.16552 | 5.85732 |
March | 514.00000 | 24.21479 | 24.55085 | 0.31210 | 7.38797 |
April | 485.00000 | 24.32767 | 27.66764 | 0.38071 | 8.31447 |
May | 508.00000 | 24.30668 | 33.56064 | -0.4505 | 9.85437 |
June | 496.00000 | 24.25423 | 45.10767 | -0.3551 | 8.05607 |
July | 497.00000 | 24.26935 | 53.52494 | -0.2784 | 6.91003 |
August | 514.00000 | 24.22986 | 50.18907 | -0.3048 | 7.20505 |
September | 485.00000 | 24.33145 | 45.42566 | -0.3454 | 8.14168 |
October | 502.00000 | 24.38466 | 33.85809 | 0.42746 | 9.17371 |
November | 489.00000 | 24.40736 | 27.38324 | 0.37825 | 8.38940 |
December | 497.00000 | 24.22835 | 21.50199 | 0.27458 | 6.84564 |
Annual Sum or Average | 5943.00000 | 24.22405 | 33.84350 | 0.02871 | 7.70034 |
Minimum of Months | 454.00000 | 23.82058 | 19.71613 | -0.4505 | 5.85732 |
Maximum of Months | 514.00000 | 24.40736 | 53.52494 | 0.42746 | 9.85437 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.94729 | 22.57052 | -0.3232 | 9.03384 |
February | 454.00000 | 22.14549 | 22.04148 | -0.2765 | 7.66492 |
March | 514.00000 | 23.31405 | 27.22197 | 0.06596 | 6.22138 |
April | 485.00000 | 23.76079 | 29.91071 | 0.20899 | 6.34669 |
May | 508.00000 | 24.13615 | 34.26693 | -0.5397 | 11.62940 |
June | 496.00000 | 24.15744 | 45.68389 | -0.4214 | 9.09696 |
July | 497.00000 | 24.24146 | 54.10954 | -0.3275 | 7.59569 |
August | 514.00000 | 24.22124 | 50.86615 | -0.3556 | 7.95776 |
September | 485.00000 | 24.16787 | 46.20443 | -0.4303 | 9.48412 |
October | 502.00000 | 23.85928 | 35.85676 | 0.27403 | 6.91641 |
November | 489.00000 | 23.50707 | 30.32961 | 0.13044 | 5.87831 |
December | 497.00000 | 22.34735 | 24.97162 | -0.2046 | 7.17584 |
Annual Sum or Average | 5943.00000 | 23.49324 | 35.43527 | -0.1835 | 7.92339 |
Minimum of Months | 454.00000 | 21.94729 | 22.04148 | -0.5397 | 5.87831 |
Maximum of Months | 514.00000 | 24.24146 | 54.10954 | 0.27403 | 11.62940 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.77409 | 23.19210 | -0.6344 | 16.30440 |
February | 454.00000 | 20.96893 | 22.87870 | -0.5839 | 15.01664 |
March | 514.00000 | 22.10251 | 28.86399 | -0.2388 | 9.58951 |
April | 485.00000 | 22.91269 | 31.68081 | -0.0059 | 6.87181 |
May | 508.00000 | 23.86019 | 35.07045 | -0.6425 | 14.72680 |
June | 496.00000 | 24.10784 | 45.87545 | -0.4309 | 9.45254 |
July | 497.00000 | 24.27003 | 53.85423 | -0.3064 | 7.37885 |
August | 514.00000 | 24.20477 | 50.82100 | -0.3569 | 8.02100 |
September | 485.00000 | 23.91387 | 47.18787 | -0.5251 | 11.98842 |
October | 502.00000 | 22.81261 | 38.73602 | 0.01121 | 6.98491 |
November | 489.00000 | 22.02882 | 33.24446 | -0.2394 | 8.10052 |
December | 497.00000 | 20.91069 | 26.32323 | -0.5745 | 14.63503 |
Annual Sum or Average | 5943.00000 | 22.75259 | 36.57395 | -0.3763 | 10.73187 |
Minimum of Months | 454.00000 | 20.77409 | 22.87870 | -0.6425 | 6.87181 |
Maximum of Months | 514.00000 | 24.27003 | 53.85423 | 0.01121 | 16.30440 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.05603 | 20.63184 | -0.5324 | 11.74198 |
February | 454.00000 | 21.22005 | 20.46301 | -0.4879 | 10.77983 |
March | 514.00000 | 22.50686 | 25.61407 | -0.1184 | 7.52581 |
April | 485.00000 | 23.45717 | 28.26545 | 0.13978 | 6.19434 |
May | 508.00000 | 23.92418 | 33.95828 | -0.6003 | 13.57639 |
June | 496.00000 | 24.21995 | 44.66367 | -0.3593 | 8.35224 |
July | 497.00000 | 24.33423 | 52.92653 | -0.2330 | 6.72394 |
August | 514.00000 | 24.21644 | 49.68732 | -0.3079 | 7.47728 |
September | 485.00000 | 24.00591 | 45.69421 | -0.4817 | 10.89476 |
October | 502.00000 | 23.39875 | 34.66288 | 0.16007 | 6.40604 |
November | 489.00000 | 22.86956 | 28.38229 | -0.0214 | 5.94650 |
December | 497.00000 | 21.57432 | 22.66913 | -0.3765 | 8.95482 |
Annual Sum or Average | 5943.00000 | 23.07789 | 34.06991 | -0.2675 | 8.70669 |
Minimum of Months | 454.00000 | 21.05603 | 20.46301 | -0.6003 | 5.94650 |
Maximum of Months | 514.00000 | 24.33423 | 52.92653 | 0.16007 | 13.57639 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.92830 | 20.08301 | -0.5540 | 11.99190 |
February | 454.00000 | 21.06605 | 19.95415 | -0.5133 | 11.26531 |
March | 514.00000 | 22.16072 | 25.66302 | -0.1638 | 7.48305 |
April | 485.00000 | 22.91739 | 28.61870 | 0.07013 | 6.61149 |
May | 508.00000 | 23.66058 | 34.01235 | -0.5988 | 15.06259 |
June | 496.00000 | 24.01787 | 44.91465 | -0.3480 | 9.09445 |
July | 497.00000 | 24.12369 | 53.33118 | -0.2293 | 7.38537 |
August | 514.00000 | 23.89052 | 50.48228 | -0.3484 | 8.76435 |
September | 485.00000 | 23.72911 | 46.06255 | -0.4914 | 12.52803 |
October | 502.00000 | 22.88497 | 35.08943 | 0.08274 | 6.69380 |
November | 489.00000 | 22.05243 | 28.92887 | -0.1815 | 6.84726 |
December | 497.00000 | 21.05665 | 22.68694 | -0.4943 | 10.64902 |
Annual Sum or Average | 5943.00000 | 22.71964 | 34.25846 | -0.3134 | 9.52424 |
Minimum of Months | 454.00000 | 20.92830 | 19.95415 | -0.5988 | 6.61149 |
Maximum of Months | 514.00000 | 24.12369 | 53.33118 | 0.08274 | 15.06259 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.25294 | 20.05709 | -0.4790 | 11.93103 |
February | 454.00000 | 21.39335 | 19.80378 | -0.4361 | 11.14804 |
March | 514.00000 | 22.68633 | 25.05809 | -0.0399 | 7.64205 |
April | 485.00000 | 23.18160 | 28.22312 | 0.11634 | 6.99139 |
May | 508.00000 | 23.72043 | 34.02301 | -0.6171 | 15.20547 |
June | 496.00000 | 24.08066 | 44.85483 | -0.3706 | 9.17165 |
July | 497.00000 | 24.28203 | 52.90011 | -0.2094 | 7.01220 |
August | 514.00000 | 24.17681 | 49.58838 | -0.2577 | 7.53863 |
September | 485.00000 | 24.04408 | 45.21018 | -0.3793 | 10.39644 |
October | 502.00000 | 23.33821 | 34.18663 | 0.19510 | 7.78191 |
November | 489.00000 | 22.57423 | 28.27526 | -0.0641 | 7.05694 |
December | 497.00000 | 21.45825 | 22.50621 | -0.4010 | 10.05226 |
Annual Sum or Average | 5943.00000 | 23.02796 | 33.82802 | -0.2445 | 9.32163 |
Minimum of Months | 454.00000 | 21.25294 | 19.80378 | -0.6171 | 6.99139 |
Maximum of Months | 514.00000 | 24.28203 | 52.90011 | 0.19510 | 15.20547 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.23588 | 19.56136 | -0.4490 | 9.88684 |
February | 454.00000 | 21.69715 | 19.06193 | -0.3190 | 8.07347 |
March | 514.00000 | 23.30534 | 23.76512 | 0.14794 | 7.33624 |
April | 485.00000 | 24.14611 | 26.33790 | 0.40900 | 9.61907 |
May | 508.00000 | 23.95280 | 33.32025 | -0.4603 | 11.94748 |
June | 496.00000 | 24.36459 | 43.86651 | -0.1499 | 7.14433 |
July | 497.00000 | 24.49975 | 51.96439 | -0.0063 | 6.55798 |
August | 514.00000 | 24.42256 | 48.65596 | -0.0409 | 6.42442 |
September | 485.00000 | 24.01726 | 45.14326 | -0.3544 | 9.91936 |
October | 502.00000 | 23.63843 | 33.35945 | 0.29044 | 7.96633 |
November | 489.00000 | 23.40791 | 26.59849 | 0.16793 | 6.76233 |
December | 497.00000 | 22.50996 | 20.70913 | -0.0984 | 6.31896 |
Annual Sum or Average | 5943.00000 | 23.44472 | 32.79876 | -0.0708 | 8.16024 |
Minimum of Months | 454.00000 | 21.23588 | 19.06193 | -0.4603 | 6.31896 |
Maximum of Months | 514.00000 | 24.49975 | 51.96439 | 0.40900 | 11.94748 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.98862 | 21.58331 | -0.8847 | 23.79671 |
February | 454.00000 | 20.04290 | 21.64466 | -0.8564 | 22.70671 |
March | 514.00000 | 21.08437 | 28.13918 | -0.4967 | 13.65882 |
April | 485.00000 | 21.88808 | 31.18918 | -0.2462 | 8.19768 |
May | 508.00000 | 23.37656 | 35.52846 | -0.8012 | 20.20171 |
June | 496.00000 | 24.04223 | 45.66570 | -0.4454 | 10.06759 |
July | 497.00000 | 24.30494 | 54.08651 | -0.2730 | 7.20320 |
August | 514.00000 | 24.11848 | 50.67385 | -0.3811 | 8.70771 |
September | 485.00000 | 23.54791 | 47.38565 | -0.6545 | 15.98320 |
October | 502.00000 | 21.95071 | 37.70558 | -0.1920 | 7.66967 |
November | 489.00000 | 20.95507 | 31.71236 | -0.4962 | 11.35820 |
December | 497.00000 | 20.05191 | 24.81783 | -0.8278 | 21.83615 |
Annual Sum or Average | 5943.00000 | 22.12963 | 35.94646 | -0.5444 | 14.23049 |
Minimum of Months | 454.00000 | 19.98862 | 21.58331 | -0.8847 | 7.20320 |
Maximum of Months | 514.00000 | 24.30494 | 54.08651 | -0.1920 | 23.79671 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.88351 | 20.58472 | -0.8975 | 24.32524 |
February | 385.00000 | 19.97555 | 20.70884 | -0.8542 | 22.70493 |
March | 433.00000 | 21.02454 | 27.30477 | -0.4759 | 12.26229 |
April | 410.00000 | 21.94066 | 30.17064 | -0.1872 | 8.44714 |
May | 430.00000 | 23.16437 | 35.03019 | -0.7814 | 21.68401 |
June | 418.00000 | 23.86476 | 45.61583 | -0.4148 | 11.15184 |
July | 422.00000 | 24.24817 | 53.89403 | -0.2083 | 8.00802 |
August | 433.00000 | 23.90792 | 50.75633 | -0.3694 | 10.02751 |
September | 410.00000 | 23.30744 | 47.45601 | -0.6501 | 17.59981 |
October | 427.00000 | 21.76027 | 37.01968 | -0.2039 | 7.69611 |
November | 417.00000 | 20.85999 | 30.56543 | -0.5115 | 11.54018 |
December | 422.00000 | 19.92709 | 23.83715 | -0.8541 | 22.71549 |
Annual Sum or Average | 5034.00000 | 22.00172 | 35.33494 | -0.5323 | 14.80104 |
Minimum of Months | 385.00000 | 19.88351 | 20.58472 | -0.8975 | 7.69611 |
Maximum of Months | 433.00000 | 24.24817 | 53.89403 | -0.1872 | 24.32524 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.49829 | 20.59877 | -0.7079 | 18.96825 |
February | 454.00000 | 20.56950 | 20.64718 | -0.6720 | 18.12202 |
March | 514.00000 | 21.93576 | 26.68572 | -0.2323 | 9.77839 |
April | 485.00000 | 22.40744 | 29.74035 | -0.0799 | 8.10418 |
May | 508.00000 | 23.36247 | 34.99127 | -0.7438 | 19.67608 |
June | 496.00000 | 23.88483 | 45.76002 | -0.4513 | 11.14098 |
July | 497.00000 | 24.25966 | 53.89864 | -0.2388 | 7.66616 |
August | 514.00000 | 24.11884 | 50.27662 | -0.3045 | 8.61258 |
September | 485.00000 | 23.82603 | 46.06567 | -0.4560 | 12.70618 |
October | 502.00000 | 22.71075 | 35.50179 | 0.04357 | 8.07624 |
November | 489.00000 | 21.66140 | 30.02746 | -0.2949 | 9.40754 |
December | 497.00000 | 20.47252 | 23.91545 | -0.6879 | 17.57805 |
Annual Sum or Average | 5943.00000 | 22.49102 | 34.94707 | -0.4006 | 12.45461 |
Minimum of Months | 454.00000 | 20.47252 | 20.59877 | -0.7438 | 7.66616 |
Maximum of Months | 514.00000 | 24.25966 | 53.89864 | 0.04357 | 19.67608 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13178 | 20.66197 | -0.8246 | 21.48571 |
February | 454.00000 | 20.25813 | 20.70226 | -0.7703 | 19.63210 |
March | 514.00000 | 21.31413 | 27.22666 | -0.3906 | 10.89031 |
April | 485.00000 | 22.04455 | 30.11028 | -0.1497 | 8.12063 |
May | 508.00000 | 23.13853 | 35.24782 | -0.7712 | 21.34934 |
June | 496.00000 | 23.89237 | 45.52997 | -0.3761 | 10.72769 |
July | 497.00000 | 24.21818 | 53.89232 | -0.1963 | 7.79080 |
August | 514.00000 | 24.01148 | 50.56725 | -0.3044 | 9.12394 |
September | 485.00000 | 23.27119 | 47.53188 | -0.6462 | 17.34648 |
October | 502.00000 | 21.81142 | 37.13366 | -0.1772 | 7.47178 |
November | 489.00000 | 21.01487 | 30.80583 | -0.4545 | 10.30549 |
December | 497.00000 | 20.21745 | 23.91899 | -0.7612 | 19.13169 |
Annual Sum or Average | 5943.00000 | 22.12585 | 35.38277 | -0.4833 | 13.57475 |
Minimum of Months | 454.00000 | 20.13178 | 20.66197 | -0.8246 | 7.47178 |
Maximum of Months | 514.00000 | 24.21818 | 53.89232 | -0.1497 | 21.48571 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.75169 | 21.75458 | -1.0012 | 28.74404 |
February | 454.00000 | 19.80577 | 21.77358 | -0.9734 | 27.67088 |
March | 514.00000 | 20.60920 | 28.89811 | -0.6551 | 18.31307 |
April | 485.00000 | 21.16347 | 32.49587 | -0.4385 | 11.46967 |
May | 508.00000 | 22.77462 | 36.68455 | -0.9984 | 28.58820 |
June | 496.00000 | 23.82739 | 46.21707 | -0.5060 | 12.27123 |
July | 497.00000 | 24.22628 | 54.25546 | -0.2857 | 7.63228 |
August | 514.00000 | 23.96188 | 51.05775 | -0.4248 | 10.02092 |
September | 485.00000 | 23.01508 | 48.84348 | -0.8297 | 22.85184 |
October | 502.00000 | 21.04736 | 39.63839 | -0.4278 | 12.00252 |
November | 489.00000 | 20.29185 | 33.39372 | -0.7029 | 17.75197 |
December | 497.00000 | 19.76413 | 25.38733 | -0.9620 | 27.38913 |
Annual Sum or Average | 5943.00000 | 21.70334 | 36.80343 | -0.6817 | 18.66442 |
Minimum of Months | 454.00000 | 19.75169 | 21.75458 | -1.0012 | 7.63228 |
Maximum of Months | 514.00000 | 24.22628 | 54.25546 | -0.2857 | 28.74404 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82015 | 21.27224 | -0.9683 | 27.40141 |
February | 454.00000 | 19.89140 | 21.32989 | -0.9271 | 25.92691 |
March | 514.00000 | 20.67160 | 28.39986 | -0.5919 | 16.45267 |
April | 485.00000 | 21.61197 | 31.32346 | -0.2843 | 10.39474 |
May | 508.00000 | 22.99539 | 35.67734 | -0.8373 | 23.95812 |
June | 496.00000 | 23.83335 | 45.76284 | -0.4039 | 11.25658 |
July | 497.00000 | 24.21825 | 53.76426 | -0.1869 | 7.73851 |
August | 514.00000 | 23.87654 | 50.85448 | -0.3554 | 10.02752 |
September | 485.00000 | 23.13744 | 48.04719 | -0.7044 | 19.80619 |
October | 502.00000 | 21.21703 | 38.72303 | -0.3536 | 10.55046 |
November | 489.00000 | 20.36932 | 32.75991 | -0.6709 | 16.68639 |
December | 497.00000 | 19.81289 | 25.01043 | -0.9434 | 26.58285 |
Annual Sum or Average | 5943.00000 | 21.80374 | 36.18139 | -0.6001 | 17.17184 |
Minimum of Months | 454.00000 | 19.81289 | 21.27224 | -0.9683 | 7.73851 |
Maximum of Months | 514.00000 | 24.21825 | 53.76426 | -0.1869 | 27.40141 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.08465 | 21.13991 | -0.8577 | 24.10571 |
February | 454.00000 | 20.14659 | 21.18893 | -0.8226 | 23.64116 |
March | 514.00000 | 21.31181 | 27.70920 | -0.4159 | 13.78626 |
April | 485.00000 | 21.82931 | 31.03322 | -0.2410 | 10.33544 |
May | 508.00000 | 22.96160 | 35.92099 | -0.8839 | 25.55941 |
June | 496.00000 | 23.71584 | 46.25326 | -0.4982 | 13.14982 |
July | 497.00000 | 24.18267 | 54.09304 | -0.2500 | 8.29677 |
August | 514.00000 | 23.99604 | 50.57481 | -0.3368 | 9.74952 |
September | 485.00000 | 23.49747 | 47.07803 | -0.5712 | 16.69143 |
October | 502.00000 | 21.96617 | 37.23509 | -0.1573 | 10.12458 |
November | 489.00000 | 20.93363 | 31.94177 | -0.5102 | 13.98463 |
December | 497.00000 | 20.01491 | 24.87407 | -0.8535 | 23.60538 |
Annual Sum or Average | 5943.00000 | 22.06934 | 35.85758 | -0.5314 | 16.03945 |
Minimum of Months | 454.00000 | 20.01491 | 21.13991 | -0.8839 | 8.29677 |
Maximum of Months | 514.00000 | 24.18267 | 54.09304 | -0.1573 | 25.55941 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.87660 | 21.13408 | -0.9401 | 26.27928 |
February | 454.00000 | 19.98544 | 21.14093 | -0.8824 | 24.26508 |
March | 514.00000 | 20.88575 | 28.03910 | -0.5285 | 14.59851 |
April | 485.00000 | 21.59391 | 31.18023 | -0.2807 | 10.10424 |
May | 508.00000 | 22.76869 | 36.09498 | -0.8992 | 26.85316 |
June | 496.00000 | 23.72281 | 46.03101 | -0.4221 | 12.58397 |
July | 497.00000 | 24.13389 | 54.11299 | -0.2100 | 8.43964 |
August | 514.00000 | 23.87188 | 50.90848 | -0.3413 | 10.34356 |
September | 485.00000 | 22.92008 | 48.58417 | -0.7662 | 21.98390 |
October | 502.00000 | 21.25721 | 38.53791 | -0.3349 | 10.21548 |
November | 489.00000 | 20.52899 | 32.38916 | -0.6127 | 14.89933 |
December | 497.00000 | 19.89089 | 24.82748 | -0.8901 | 24.52623 |
Annual Sum or Average | 5943.00000 | 21.80200 | 36.18668 | -0.5903 | 17.04064 |
Minimum of Months | 454.00000 | 19.87660 | 21.13408 | -0.9401 | 8.43964 |
Maximum of Months | 514.00000 | 24.13389 | 54.11299 | -0.2100 | 26.85316 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.318136E+09 | 3261.47 | 20-JAN-07:20 | 27.48 | 0.144877E+10 | 0.00 | 0.176690E+10 | 0.17 | 4.56 | 08-JAN-01:40 | 0.00 | 0.00 |
February | 0.339860E+09 | 3281.44 | 04-FEB-07:20 | 29.33 | 0.154744E+10 | 0.00 | 0.188730E+10 | 0.20 | 4.56 | 05-FEB-05:40 | 0.00 | 0.00 |
March | 0.788075E+10 | 101674.02 | 14-MAR-13:40 | 73.46 | 0.487188E+11 | 0.00 | 0.565995E+11 | 0.51 | 7.24 | 14-MAR-16:00 | 0.00 | 0.00 |
April | 0.501194E+10 | 70660.31 | 07-APR-14:00 | 83.44 | 0.248436E+11 | 0.00 | 0.298556E+11 | 0.54 | 6.63 | 07-APR-14:00 | 0.00 | 0.00 |
May | 0.341189E+11 | 100615.59 | 10-MAY-12:30 | 219.78 | 0.194696E+12 | 0.00 | 0.228815E+12 | 1.54 | 7.36 | 16-MAY-14:40 | 0.00 | 0.00 |
June | 0.103349E+12 | 170043.64 | 27-JUN-05:03 | 448.17 | 0.665442E+12 | 0.00 | 0.768791E+12 | 3.70 | 7.61 | 19-JUN-05:03 | 0.00 | 0.00 |
July | 0.151195E+12 | 191141.28 | 20-JUL-05:02 | 570.33 | 0.100387E+13 | 0.00 | 0.115506E+13 | 4.72 | 7.75 | 18-JUL-05:03 | 0.00 | 0.00 |
August | 0.134458E+12 | 193572.92 | 15-AUG-14:30 | 562.59 | 0.892263E+12 | 0.00 | 0.102672E+13 | 4.57 | 7.69 | 07-AUG-05:03 | 0.00 | 0.00 |
September | 0.698865E+11 | 152660.98 | 14-SEP-05:03 | 332.57 | 0.443509E+12 | 0.00 | 0.513396E+12 | 2.67 | 7.65 | 14-SEP-05:03 | 0.00 | 0.00 |
October | 0.130953E+11 | 96791.32 | 11-OCT-13:50 | 126.27 | 0.691808E+11 | 0.00 | 0.822761E+11 | 0.82 | 7.32 | 11-OCT-13:50 | 0.00 | 0.00 |
November | 0.314173E+10 | 60542.18 | 16-NOV-13:00 | 81.95 | 0.142927E+11 | 0.00 | 0.174345E+11 | 0.52 | 6.11 | 16-NOV-13:00 | 0.00 | 0.00 |
December | 0.596641E+09 | 15694.72 | 01-DEC-06:02 | 50.45 | 0.271665E+10 | 0.00 | 0.331329E+10 | 0.31 | 4.56 | 12-DEC-02:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.523393E+12 | 2605.82 | 0.336252E+13 | 0.00 | 0.388592E+13 | 1.70 | 0.00 | 0.00 | ||||
Minimum of Months | 0.318136E+09 | 3261.47 | 27.48 | 0.144877E+10 | 0.00 | 0.176690E+10 | 0.17 | 4.56 | 0.00 | 0.00 | ||
Maximum of Months | 0.151195E+12 | 193572.92 | 570.33 | 0.100387E+13 | 0.00 | 0.115506E+13 | 4.72 | 7.75 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.255402E+11 | 170043.64 | 27-JUN-05:03 | 66.63 | 0.180042E+12 | 0.00 | 0.205582E+12 | 0.65 | 7.61 | 19-JUN-05:03 | 0.00 | 0.00 |
July | 0.572237E+11 | 191141.28 | 20-JUL-05:02 | 138.80 | 0.399452E+12 | 0.00 | 0.456676E+12 | 1.30 | 7.75 | 18-JUL-05:03 | 0.00 | 0.00 |
August | 0.438063E+11 | 193572.92 | 15-AUG-14:30 | 108.92 | 0.308729E+12 | 0.00 | 0.352535E+12 | 1.03 | 7.69 | 07-AUG-05:03 | 0.00 | 0.00 |
September | 0.128827E+11 | 152660.98 | 14-SEP-05:03 | 34.51 | 0.919008E+11 | 0.00 | 0.104784E+12 | 0.34 | 7.65 | 14-SEP-05:03 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.139453E+12 | 348.86 | 0.980123E+12 | 0.00 | 0.111958E+13 | 0.28 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.572237E+11 | 193572.92 | 138.80 | 0.399452E+12 | 0.00 | 0.456676E+12 | 1.30 | 7.75 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.802138E+10 | 744.00 | 7648.87 | 11-JAN-16:00 | 215318.95 | 11-JAN-12:00 | 21.49 | 18.33 | 14.25 |
February | 0.122183E+11 | 672.00 | 29716.28 | 22-FEB-18:00 | 377271.87 | 28-FEB-15:35 | 24.27 | 18.33 | 14.26 |
March | 0.420045E+11 | 744.00 | 49248.27 | 12-MAR-12:25 | 588415.55 | 31-MAR-24:00 | 27.79 | 18.70 | 14.19 |
April | 0.777106E+11 | 720.00 | 49248.27 | 06-APR-13:50 | 639740.19 | 07-APR-14:10 | 30.62 | 18.71 | 14.26 |
May | 0.663879E+11 | 744.00 | 49248.27 | 02-MAY-11:00 | 330048.22 | 31-MAY-24:00 | 22.80 | 19.03 | 14.26 |
June | 0.114961E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 476090.32 | 30-JUN-23:40 | 29.39 | 22.52 | 14.28 |
July | 0.131217E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 637045.98 | 31-JUL-23:22 | 36.53 | 26.57 | 14.29 |
August | 0.131436E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 688137.77 | 18-AUG-16:00 | 39.19 | 26.48 | 14.29 |
September | 0.895968E+11 | 720.00 | 49248.27 | 01-SEP-10:00 | 313644.07 | 30-SEP-24:00 | 24.08 | 20.19 | 14.28 |
October | 0.585641E+11 | 744.00 | 49248.27 | 01-OCT-09:30 | 453493.40 | 31-OCT-24:00 | 25.18 | 18.67 | 14.17 |
November | 0.493525E+11 | 720.00 | 49248.27 | 04-NOV-10:30 | 514373.96 | 02-NOV-12:03 | 27.70 | 18.55 | 14.16 |
December | 0.334233E+11 | 744.00 | 49248.27 | 01-DEC-09:00 | 604506.99 | 01-DEC-13:10 | 29.89 | 18.34 | 14.27 |
Annual Sum or Average | 0.814893E+12 | 8760.00 | 28.28 | 20.39 | 14.24 | ||||
Minimum of Months | 0.802138E+10 | 672.00 | 7648.87 | 215318.95 | 21.49 | 18.33 | 14.16 | ||
Maximum of Months | 0.131436E+12 | 744.00 | 49248.27 | 688137.77 | 39.19 | 26.57 | 14.29 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 238288.23 | 13-JAN-16:50 | 20.95 | 20.94 | 0.36 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 238443.22 | 23-FEB-15:00 | 20.89 | 20.88 | 0.47 |
March | 0.695430E+09 | 29.37 | 19755.11 | 14-MAR-11:00 | 1040450.71 | 15-MAR-13:40 | 21.12 | 21.03 | 3.63 |
April | 23743840.60 | 20.00 | 1267.44 | 08-APR-13:50 | 556660.09 | 07-APR-14:00 | 21.07 | 21.02 | 3.75 |
May | 0.803137E+09 | 157.39 | 19755.11 | 10-MAY-12:40 | 1139730.10 | 31-MAY-15:30 | 21.50 | 21.16 | 18.17 |
June | 0.127305E+11 | 406.27 | 19755.11 | 01-JUN-13:00 | 1239888.11 | 27-JUN-07:40 | 22.80 | 21.67 | 40.71 |
July | 0.268024E+11 | 538.03 | 19755.11 | 01-JUL-14:10 | 1491285.69 | 05-JUL-16:00 | 24.11 | 22.47 | 50.35 |
August | 0.198712E+11 | 490.79 | 19755.11 | 01-AUG-11:50 | 1499568.35 | 15-AUG-14:40 | 23.30 | 21.81 | 48.92 |
September | 0.736028E+10 | 288.44 | 19755.11 | 08-SEP-11:00 | 1229942.43 | 22-SEP-13:20 | 22.30 | 21.53 | 30.07 |
October | 0.166209E+09 | 68.06 | 3291.41 | 11-OCT-14:00 | 1007330.52 | 11-OCT-12:50 | 21.16 | 21.04 | 8.48 |
November | 22800981.40 | 15.08 | 801.02 | 16-NOV-13:10 | 424852.97 | 16-NOV-13:00 | 21.05 | 21.02 | 2.50 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 238469.38 | 26-DEC-07:00 | 20.98 | 20.97 | 0.66 |
Annual Sum or Average | 0.684756E+11 | 2013.42 | 21.78 | 21.30 | 17.46 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 238288.23 | 20.89 | 20.88 | 0.36 | ||
Maximum of Months | 0.268024E+11 | 538.03 | 19755.11 | 1499568.35 | 24.11 | 22.47 | 50.35 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 20.95 | 20.95 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 20.89 | 20.89 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.12 | 21.12 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.07 | 21.07 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 21.50 | 21.50 | 0.00 |
June | 0.481184E+10 | 67.81 | 19755.11 | 01-JUN-14:50 | 1239888.11 | 27-JUN-07:40 | 22.80 | 22.51 | 6.27 |
July | 0.111285E+11 | 156.48 | 19755.11 | 03-JUL-12:40 | 1491285.69 | 05-JUL-16:00 | 24.11 | 23.42 | 13.76 |
August | 0.671811E+10 | 94.59 | 19755.11 | 01-AUG-13:00 | 1499568.35 | 15-AUG-14:40 | 23.30 | 22.88 | 8.50 |
September | 0.244647E+10 | 34.40 | 19755.11 | 08-SEP-13:10 | 1229942.43 | 22-SEP-13:20 | 22.30 | 22.14 | 3.20 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.16 | 21.16 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.05 | 21.05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.98 | 20.98 | 0.00 |
Annual Sum or Average | 0.251049E+11 | 353.28 | 21.78 | 21.64 | 2.67 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 20.89 | 0.00 | ||
Maximum of Months | 0.111285E+11 | 156.48 | 19755.11 | 1499568.35 | 24.11 | 23.42 | 13.76 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.417001E+12 | 0.00 | 588.43 | 2078711.27 | 02-JAN-04:11 | 0.00 | 30.33 | 70.49 | 0.81 | 0.00 | 0.05 | 0.68 | 02-JAN-04:11 |
February | 0.358759E+12 | 0.00 | 539.58 | 1844852.23 | 27-FEB-05:01 | 0.00 | 29.91 | 70.98 | 0.78 | 0.00 | 0.05 | 0.60 | 27-FEB-05:01 |
March | 0.143235E+12 | 0.00 | 449.62 | 1621243.40 | 06-MAR-06:03 | 0.00 | 25.73 | 58.01 | 0.27 | 0.00 | 0.02 | 0.53 | 06-MAR-06:03 |
April | 0.455836E+11 | 0.00 | 296.99 | 1400562.56 | 17-APR-04:01 | 0.00 | 25.51 | 47.61 | 0.08 | 0.00 | 0.01 | 0.46 | 17-APR-04:01 |
May | 0.335378E+10 | 0.00 | 88.68 | 302925.88 | 04-MAY-06:10 | 0.00 | 25.26 | 31.66 | 0.01 | 0.00 | 0.00 | 0.10 | 04-MAY-06:10 |
June | 0.335128E+09 | 0.00 | 11.29 | 138199.58 | 10-JUN-06:10 | 0.00 | 25.00 | 25.86 | 0.00 | 0.00 | 0.00 | 0.05 | 10-JUN-06:10 |
July | 4689.26 | 0.00 | 0.17 | 7.82 | 11-JUL-08:30 | 0.00 | 25.28 | 25.30 | 0.00 | 0.00 | 0.00 | 0.00 | 11-JUL-08:30 |
August | 15973956.35 | 0.00 | 2.92 | 8699.14 | 31-AUG-06:10 | 0.00 | 25.27 | 25.48 | 0.00 | 0.00 | 0.00 | 0.00 | 31-AUG-06:10 |
September | 0.211296E+10 | 0.00 | 50.90 | 275899.52 | 30-SEP-06:10 | 0.00 | 25.32 | 29.25 | 0.00 | 0.00 | 0.00 | 0.09 | 30-SEP-06:10 |
October | 0.348554E+11 | 0.00 | 265.95 | 1443075.43 | 30-OCT-04:01 | 0.00 | 23.39 | 43.09 | 0.06 | 0.00 | 0.00 | 0.47 | 30-OCT-04:01 |
November | 0.115995E+12 | 0.00 | 401.10 | 1434615.82 | 25-NOV-05:01 | 0.00 | 24.64 | 54.49 | 0.21 | 0.00 | 0.01 | 0.47 | 25-NOV-05:01 |
December | 0.360122E+12 | 0.00 | 569.31 | 1800162.23 | 11-DEC-05:01 | 0.00 | 29.78 | 68.67 | 0.70 | 0.00 | 0.04 | 0.59 | 11-DEC-05:01 |
Annual Sum or Average | 0.148137E+13 | 0.00 | 3264.93 | 0.00 | 26.27 | 45.77 | 0.24 | 0.00 | 0.02 | ||||
Minimum of Months | 4689.26 | 0.00 | 0.17 | 7.82 | 0.00 | 23.39 | 25.30 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.417001E+12 | 0.00 | 588.43 | 2078711.27 | 0.00 | 30.33 | 70.98 | 0.81 | 0.00 | 0.05 | 0.68 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 21.49 | 21.49 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 24.27 | 24.27 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.79 | 27.79 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 30.62 | 30.62 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 22.80 | 22.80 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 29.39 | 29.39 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 36.53 | 36.53 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 39.19 | 39.19 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 24.08 | 24.08 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 25.18 | 25.18 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.70 | 27.70 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 29.89 | 29.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 28.28 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 | 21.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.19 | 39.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8114121.25 | 0.00 | 12.33 | 8114121.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4315.41 | 20-JAN-13:10 | 4315.41 | 20-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 6770624.54 | 0.00 | 9.67 | 6770624.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2096.89 | 23-FEB-14:30 | 2096.89 | 23-FEB-14:30 | 0.00 | 0.00 | 0.00 |
March | 0.600346E+10 | 0.00 | 46.02 | 0.586104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103952.58 | 14-MAR-13:10 | 101446.40 | 15-MAR-14:10 | 0.00 | 0.00 | 0.00 |
April | 0.240630E+10 | 0.00 | 52.98 | 0.240630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51313.59 | 07-APR-14:00 | 51313.59 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.186031E+11 | 0.00 | 212.31 | 0.183628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96479.75 | 10-MAY-14:30 | 88814.27 | 23-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.840778E+11 | 0.00 | 430.90 | 0.663051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206746.94 | 27-JUN-07:40 | 119685.55 | 12-JUN-14:00 | 0.00 | 0.00 | 0.00 |
July | 0.151040E+12 | 0.00 | 549.01 | 0.108254E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 283341.76 | 20-JUL-05:02 | 153392.51 | 21-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.130916E+12 | 0.00 | 546.41 | 0.101744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 262843.66 | 14-AUG-05:03 | 127666.77 | 09-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.507913E+11 | 0.00 | 321.62 | 0.401864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206976.94 | 16-SEP-05:03 | 106122.41 | 21-SEP-15:30 | 0.00 | 0.00 | 0.00 |
October | 0.668867E+10 | 0.00 | 96.72 | 0.668395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77148.82 | 11-OCT-15:00 | 77148.82 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.116199E+10 | 0.00 | 35.33 | 0.116199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57388.05 | 27-NOV-06:02 | 57388.05 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 25712958.61 | 0.00 | 15.58 | 25712958.61 | 0.00 | 0.00 | 0.00 | 0.00 | 10673.12 | 13-DEC-08:10 | 10673.12 | 13-DEC-08:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451729E+12 | 0.00 | 2328.88 | 0.351006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6770624.54 | 0.00 | 9.67 | 6770624.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2096.89 | 2096.89 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.151040E+12 | 0.00 | 549.01 | 0.108254E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 283341.76 | 153392.51 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 574441.83 | 0.00 | 24.04 | 574441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 171.20 | 13-JAN-14:40 | 171.20 | 13-JAN-14:40 | 0.00 | 0.00 | 0.00 |
February | 4002224.65 | 0.00 | 25.99 | 4002224.65 | 0.00 | 0.00 | 0.00 | 0.00 | 4540.44 | 18-FEB-13:40 | 4540.44 | 18-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 0.413995E+11 | 0.00 | 57.46 | 0.405424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 761583.62 | 15-MAR-14:10 | 761583.62 | 15-MAR-14:10 | 0.00 | 0.00 | 0.00 |
April | 0.158866E+11 | 0.00 | 55.44 | 0.158866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 343285.97 | 07-APR-14:00 | 343285.97 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.157391E+12 | 0.00 | 204.83 | 0.155342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 849844.41 | 10-MAY-14:40 | 794007.32 | 23-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.686468E+12 | 0.00 | 392.24 | 0.547287E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1852483.89 | 27-JUN-05:03 | 1047049.91 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.117121E+13 | 0.00 | 450.12 | 0.856843E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2945249.34 | 20-JUL-03:02 | 1394241.13 | 21-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.967985E+12 | 0.00 | 435.53 | 0.772383E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2820344.06 | 14-AUG-03:02 | 1132460.51 | 09-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.430682E+12 | 0.00 | 310.41 | 0.344296E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1804221.17 | 16-SEP-05:03 | 989408.56 | 21-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.510302E+11 | 0.00 | 101.55 | 0.509958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 613665.29 | 11-OCT-15:00 | 613665.29 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.749077E+10 | 0.00 | 46.04 | 0.749077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 192901.12 | 16-NOV-13:10 | 192901.12 | 16-NOV-13:10 | 0.00 | 0.00 | 0.00 |
December | 3380673.32 | 0.00 | 42.73 | 3380673.32 | 0.00 | 0.00 | 0.00 | 0.00 | 8228.29 | 01-DEC-13:30 | 8228.29 | 01-DEC-13:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352955E+13 | 0.00 | 2146.38 | 0.279107E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 574441.83 | 0.00 | 24.04 | 574441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 171.20 | 171.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.117121E+13 | 0.00 | 450.12 | 0.856843E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2945249.34 | 1394241.13 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1420301.39 | 0.00 | 11.25 | 1420301.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1422.59 | 31-JAN-05:21 | 1422.59 | 31-JAN-05:21 | 0.00 | 0.00 | 0.00 |
February | 1186414.48 | 0.00 | 8.98 | 1186414.48 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.39 | 08-FEB-04:42 | 1109.39 | 08-FEB-04:42 | 0.00 | 0.00 | 0.00 |
March | 0.431531E+10 | 0.00 | 53.51 | 0.430281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93557.51 | 15-MAR-14:00 | 93557.51 | 15-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.149805E+10 | 0.00 | 66.78 | 0.149805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32502.08 | 07-APR-14:00 | 32502.08 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.157472E+11 | 0.00 | 198.16 | 0.155861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99082.34 | 10-MAY-14:50 | 91191.75 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 |
June | 0.749270E+11 | 0.00 | 385.79 | 0.594912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 301382.14 | 27-JUN-15:00 | 131988.56 | 12-JUN-14:00 | 0.00 | 0.00 | 0.00 |
July | 0.129844E+12 | 0.00 | 449.17 | 0.949940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 312411.20 | 20-JUL-03:02 | 138729.04 | 21-JUL-13:50 | 0.00 | 0.00 | 0.00 |
August | 0.104682E+12 | 0.00 | 430.44 | 0.833492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 299129.32 | 14-AUG-03:02 | 136854.90 | 09-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.426268E+11 | 0.00 | 302.06 | 0.339424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 177585.11 | 15-SEP-12:40 | 114483.89 | 21-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.425789E+10 | 0.00 | 107.01 | 0.425789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59945.95 | 11-OCT-15:00 | 59945.95 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.699632E+09 | 0.00 | 69.44 | 0.699632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16121.93 | 16-NOV-18:00 | 16121.93 | 16-NOV-18:00 | 0.00 | 0.00 | 0.00 |
December | 2767290.88 | 0.00 | 22.22 | 2767290.88 | 0.00 | 0.00 | 0.00 | 0.00 | 562.71 | 26-DEC-06:05 | 562.71 | 26-DEC-06:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378603E+12 | 0.00 | 2104.80 | 0.298127E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1186414.48 | 0.00 | 8.98 | 1186414.48 | 0.00 | 0.00 | 0.00 | 0.00 | 562.71 | 562.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.129844E+12 | 0.00 | 449.17 | 0.949940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 312411.20 | 138729.04 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 95009.62 | 0.00 | 1.19 | 95009.62 | 0.00 | 0.00 | 0.00 | 0.00 | 99.04 | 23-JAN-15:00 | 99.04 | 23-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 361799.24 | 0.00 | 1.99 | 361799.24 | 0.00 | 0.00 | 0.00 | 0.00 | 245.84 | 28-FEB-09:50 | 245.84 | 28-FEB-09:50 | 0.00 | 0.00 | 0.00 |
March | 0.335824E+10 | 0.00 | 29.14 | 0.334588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58075.26 | 16-MAR-04:02 | 58075.26 | 16-MAR-04:02 | 0.00 | 0.00 | 0.00 |
April | 0.574047E+09 | 0.00 | 14.95 | 0.574047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25222.68 | 07-APR-14:00 | 25222.68 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.798655E+10 | 0.00 | 116.96 | 0.795815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78103.06 | 24-MAY-05:03 | 54582.46 | 10-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.401057E+11 | 0.00 | 293.82 | 0.338481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126881.96 | 27-JUN-05:03 | 73341.09 | 12-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.770569E+11 | 0.00 | 368.96 | 0.582156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 174696.92 | 20-JUL-03:02 | 89892.46 | 04-JUL-17:00 | 0.00 | 0.00 | 0.00 |
August | 0.672626E+11 | 0.00 | 376.96 | 0.551561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167870.79 | 14-AUG-03:03 | 103207.37 | 06-AUG-15:41 | 0.00 | 0.00 | 0.00 |
September | 0.289325E+11 | 0.00 | 238.08 | 0.242489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121004.21 | 16-SEP-05:03 | 66187.66 | 25-SEP-13:10 | 0.00 | 0.00 | 0.00 |
October | 0.279682E+10 | 0.00 | 57.53 | 0.277795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59032.12 | 26-OCT-05:03 | 46869.09 | 11-OCT-13:20 | 0.00 | 0.00 | 0.00 |
November | 0.538739E+09 | 0.00 | 12.77 | 0.538739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49149.55 | 27-NOV-04:02 | 49149.55 | 27-NOV-04:02 | 0.00 | 0.00 | 0.00 |
December | 1384225.75 | 0.00 | 0.83 | 1384225.75 | 0.00 | 0.00 | 0.00 | 0.00 | 9041.30 | 01-DEC-06:02 | 9041.30 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228614E+12 | 0.00 | 1513.16 | 0.186665E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 95009.62 | 0.00 | 0.83 | 95009.62 | 0.00 | 0.00 | 0.00 | 0.00 | 99.04 | 99.04 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.770569E+11 | 0.00 | 376.96 | 0.582156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 174696.92 | 103207.37 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.316085E+12 | 0.798547E+11 | 744.00 | 0.316077E+12 | 8397326.88 | 0.00 | 0.34 | 17-JAN-10:10 | 0.29 | 30-JAN-07:05 | 124177.62 | 19-JAN-22:10 | 124177.62 | 19-JAN-22:10 | 796.95 | 02-JAN-07:10 | 37133.81 | 17-JAN-10:10 | 0.00 |
February | 0.505287E+12 | 0.121189E+12 | 672.00 | 0.505287E+12 | -0.0 | 0.00 | 0.56 | 17-FEB-13:10 | 0.51 | 06-FEB-07:05 | 215859.26 | 17-FEB-22:03 | 215859.26 | 17-FEB-22:03 | 0.00 | 25-FEB-08:40 | 57134.18 | 17-FEB-11:40 | 0.00 |
March | 0.811787E+12 | 0.188290E+12 | 744.00 | 0.811278E+12 | 0.509358E+09 | 0.00 | 0.92 | 31-MAR-24:00 | 0.71 | 06-MAR-07:10 | 394296.99 | 31-MAR-24:00 | 394296.99 | 31-MAR-24:00 | 7539.58 | 16-MAR-16:10 | 100977.50 | 15-MAR-14:00 | 0.00 |
April | 0.102639E+13 | 0.229634E+12 | 720.00 | 0.102637E+13 | 24187859.12 | 0.00 | 1.00 | 07-APR-14:00 | 0.36 | 30-APR-24:00 | 400590.23 | 21-APR-21:03 | 400590.23 | 21-APR-21:03 | 1969.37 | 12-APR-16:10 | 113845.99 | 08-APR-13:00 | 0.00 |
May | 0.331400E+12 | 0.847698E+11 | 744.00 | 0.330439E+12 | 0.960499E+09 | 0.00 | 0.54 | 31-MAY-24:00 | 0.31 | 13-MAY-06:10 | 212798.28 | 31-MAY-24:00 | 212048.08 | 31-MAY-24:00 | 6225.30 | 10-MAY-17:50 | 52912.14 | 31-MAY-23:30 | 0.00 |
June | 0.565166E+12 | 0.152241E+12 | 720.00 | 0.560407E+12 | 0.475931E+10 | 0.00 | 0.76 | 30-JUN-23:20 | 0.53 | 10-JUN-06:30 | 304142.99 | 30-JUN-24:00 | 304142.99 | 30-JUN-24:00 | 11605.41 | 27-JUN-14:00 | 83921.40 | 27-JUN-13:00 | 0.00 |
July | 0.834982E+12 | 0.241561E+12 | 744.00 | 0.827609E+12 | 0.737350E+10 | 0.00 | 0.96 | 31-JUL-23:15 | 0.73 | 07-JUL-06:30 | 396896.39 | 31-JUL-23:53 | 396265.88 | 31-JUL-23:55 | 11362.74 | 20-JUL-21:00 | 119761.04 | 21-JUL-14:00 | 0.00 |
August | 0.107628E+13 | 0.298956E+12 | 744.00 | 0.107150E+13 | 0.478382E+10 | 0.00 | 1.00 | 01-AUG-15:20 | 0.36 | 31-AUG-24:00 | 416226.20 | 15-AUG-15:00 | 407140.76 | 04-AUG-21:02 | 12901.82 | 26-AUG-16:00 | 140546.64 | 10-AUG-14:00 | 0.00 |
September | 0.328970E+12 | 0.862348E+11 | 720.00 | 0.325098E+12 | 0.387219E+10 | 0.00 | 0.54 | 30-SEP-24:00 | 0.31 | 06-SEP-06:10 | 211456.61 | 30-SEP-24:00 | 211456.61 | 30-SEP-24:00 | 8767.97 | 15-SEP-15:10 | 50362.72 | 30-SEP-24:00 | 0.00 |
October | 0.576107E+12 | 0.138430E+12 | 744.00 | 0.575278E+12 | 0.828607E+09 | 0.00 | 0.74 | 31-OCT-24:00 | 0.53 | 03-OCT-06:10 | 304410.11 | 31-OCT-24:00 | 304410.11 | 31-OCT-24:00 | 4972.74 | 12-OCT-16:10 | 69019.70 | 31-OCT-24:00 | 0.00 |
November | 0.790879E+12 | 0.182426E+12 | 720.00 | 0.790857E+12 | 22213387.71 | 0.00 | 0.78 | 26-NOV-14:00 | 0.73 | 01-NOV-06:10 | 309819.05 | 16-NOV-17:00 | 309430.21 | 06-NOV-22:03 | 5017.45 | 16-NOV-18:40 | 82682.70 | 05-NOV-14:00 | 0.00 |
December | 0.105560E+13 | 0.233929E+12 | 744.00 | 0.105558E+13 | 11505920.67 | 0.00 | 0.95 | 05-DEC-22:02 | 0.90 | 11-DEC-07:05 | 400851.02 | 26-DEC-22:01 | 400851.02 | 26-DEC-22:01 | 2893.94 | 01-DEC-13:20 | 92662.29 | 01-DEC-11:00 | 0.00 |
Annual Sum or Average | 0.821893E+13 | 0.203752E+13 | 8760.00 | 0.819578E+13 | 0.231536E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.316085E+12 | 0.798547E+11 | 672.00 | 0.316077E+12 | -0.0 | 0.00 | 0.34 | 0.29 | 124177.62 | 124177.62 | 0.00 | 37133.81 | 0.00 | ||||||
Maximum of Months | 0.107628E+13 | 0.298956E+12 | 744.00 | 0.107150E+13 | 0.737350E+10 | 0.00 | 1.00 | 0.90 | 416226.20 | 407140.76 | 12901.82 | 140546.64 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.296203E+10 | 0.827634E+09 | 744.00 | 0.296203E+10 | 0.00 | 0.00 | 0.27 | 15-JAN-16:30 | 0.03 | 30-JAN-07:05 | 2133.01 | 15-JAN-16:30 | 2133.01 | 15-JAN-16:30 | 0.00 | 14-JAN-14:50 | 551.75 | 15-JAN-16:30 | 0.00 |
February | 0.751377E+10 | 0.194143E+10 | 672.00 | 0.751377E+10 | -0.0 | 0.00 | 0.52 | 28-FEB-16:55 | 0.28 | 06-FEB-07:05 | 4185.36 | 28-FEB-16:55 | 4185.36 | 28-FEB-16:55 | 0.00 | 28-FEB-16:10 | 1041.13 | 28-FEB-16:55 | 0.00 |
March | 0.147959E+11 | 0.355725E+10 | 744.00 | 0.147742E+11 | 21671016.54 | 0.00 | 0.81 | 31-MAR-24:00 | 0.57 | 06-MAR-07:10 | 7549.50 | 31-MAR-24:00 | 7549.50 | 31-MAR-24:00 | 256.46 | 16-MAR-16:10 | 1990.56 | 15-MAR-14:10 | 0.00 |
April | 0.197859E+11 | 0.445908E+10 | 720.00 | 0.197831E+11 | 2780034.28 | 0.00 | 0.93 | 22-APR-17:53 | 0.30 | 30-APR-24:00 | 8571.65 | 02-APR-17:44 | 8571.65 | 02-APR-17:44 | 98.56 | 12-APR-16:10 | 2228.33 | 07-APR-14:00 | 0.00 |
May | 0.559877E+10 | 0.143393E+10 | 744.00 | 0.556130E+10 | 37471964.25 | 0.00 | 0.47 | 31-MAY-24:00 | 0.18 | 11-MAY-21:00 | 4066.31 | 31-MAY-24:00 | 4059.08 | 31-MAY-24:00 | 233.12 | 17-MAY-15:30 | 992.29 | 31-MAY-24:00 | 0.00 |
June | 0.108957E+11 | 0.289263E+10 | 720.00 | 0.107074E+11 | 0.188266E+09 | 0.00 | 0.68 | 30-JUN-24:00 | 0.41 | 10-JUN-06:35 | 5933.27 | 30-JUN-24:00 | 5933.27 | 30-JUN-24:00 | 482.37 | 27-JUN-15:00 | 1697.23 | 27-JUN-13:00 | 0.00 |
July | 0.165578E+11 | 0.470646E+10 | 744.00 | 0.162458E+11 | 0.311929E+09 | 0.00 | 0.86 | 31-JUL-23:22 | 0.62 | 07-JUL-06:10 | 7833.53 | 31-JUL-23:45 | 7814.91 | 31-JUL-23:47 | 477.41 | 20-JUL-15:00 | 2430.21 | 21-JUL-14:00 | 0.00 |
August | 0.214481E+11 | 0.589258E+10 | 744.00 | 0.212257E+11 | 0.222309E+09 | 0.00 | 0.99 | 18-AUG-15:50 | 0.29 | 31-AUG-24:00 | 8740.26 | 14-AUG-15:30 | 8726.07 | 04-AUG-18:30 | 472.15 | 14-AUG-10:00 | 3000.38 | 10-AUG-14:10 | 0.00 |
September | 0.571184E+10 | 0.148128E+10 | 720.00 | 0.557001E+10 | 0.141825E+09 | 0.00 | 0.44 | 30-SEP-24:00 | 0.17 | 30-SEP-07:00 | 3750.03 | 30-SEP-24:00 | 3750.03 | 30-SEP-24:00 | 340.48 | 15-SEP-15:10 | 885.04 | 21-SEP-17:00 | 0.00 |
October | 0.102706E+11 | 0.246042E+10 | 744.00 | 0.102373E+11 | 33278551.94 | 0.00 | 0.63 | 31-OCT-24:00 | 0.37 | 30-OCT-06:10 | 5709.43 | 31-OCT-24:00 | 5709.43 | 31-OCT-24:00 | 193.00 | 12-OCT-15:40 | 1327.67 | 11-OCT-16:50 | 0.00 |
November | 0.144854E+11 | 0.338639E+10 | 720.00 | 0.144839E+11 | 1500941.70 | 0.00 | 0.73 | 26-NOV-14:00 | 0.58 | 20-NOV-22:00 | 6121.56 | 15-NOV-16:10 | 6121.56 | 15-NOV-16:10 | 117.39 | 16-NOV-18:40 | 1671.28 | 26-NOV-14:00 | 0.00 |
December | 0.191878E+11 | 0.446018E+10 | 744.00 | 0.191873E+11 | 456187.80 | 0.00 | 0.88 | 04-DEC-16:10 | 0.74 | 11-DEC-07:05 | 7766.99 | 04-DEC-16:10 | 7766.99 | 04-DEC-16:10 | 92.93 | 01-DEC-13:30 | 1779.47 | 04-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.149213E+12 | 0.374992E+11 | 8760.00 | 0.148252E+12 | 0.961488E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.296203E+10 | 0.827634E+09 | 672.00 | 0.296203E+10 | -0.0 | 0.00 | 0.27 | 0.03 | 2133.01 | 2133.01 | 0.00 | 551.75 | 0.00 | ||||||
Maximum of Months | 0.214481E+11 | 0.589258E+10 | 744.00 | 0.212257E+11 | 0.311929E+09 | 0.00 | 0.99 | 0.74 | 8740.26 | 8726.07 | 482.37 | 3000.38 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.538486E+10 | 0.171021E+10 | 413.41 | 0.538486E+10 | 6798.68 | 0.00 | 0.19 | 12-JAN-16:40 | 0.00 | 01-JAN-00:03 | 13535.17 | 12-JAN-16:40 | 13535.17 | 12-JAN-16:40 | 6.62 | 11-JAN-18:10 | 3726.07 | 12-JAN-16:40 | 0.00 |
February | 0.474289E+11 | 0.126658E+11 | 672.00 | 0.474289E+11 | -0.0 | 0.00 | 0.47 | 28-FEB-16:55 | 0.10 | 06-FEB-07:05 | 35862.96 | 28-FEB-16:55 | 35862.96 | 28-FEB-16:55 | 0.00 | 01-FEB-17:40 | 9022.33 | 28-FEB-16:55 | 0.00 |
March | 0.122646E+12 | 0.299595E+11 | 744.00 | 0.122430E+12 | 0.215426E+09 | 0.00 | 0.75 | 31-MAR-24:00 | 0.41 | 06-MAR-07:10 | 66382.30 | 31-MAR-24:00 | 66382.30 | 31-MAR-24:00 | 2521.40 | 16-MAR-16:10 | 18746.36 | 15-MAR-14:10 | 0.00 |
April | 0.176153E+12 | 0.400952E+11 | 720.00 | 0.176124E+12 | 29465704.24 | 0.00 | 0.91 | 22-APR-17:53 | 0.21 | 30-APR-24:00 | 78352.94 | 24-APR-18:00 | 78352.94 | 24-APR-18:00 | 984.83 | 12-APR-16:10 | 20911.13 | 07-APR-14:00 | 0.00 |
May | 0.471718E+11 | 0.122181E+11 | 744.00 | 0.468060E+11 | 0.365871E+09 | 0.00 | 0.46 | 31-MAY-24:00 | 0.12 | 01-MAY-06:05 | 38224.84 | 31-MAY-24:00 | 38158.88 | 31-MAY-24:00 | 2266.80 | 17-MAY-15:30 | 9347.04 | 31-MAY-23:50 | 0.00 |
June | 0.101323E+12 | 0.270061E+11 | 720.00 | 0.994565E+11 | 0.186657E+10 | 0.00 | 0.68 | 30-JUN-23:40 | 0.37 | 14-JUN-06:05 | 56936.09 | 30-JUN-24:00 | 56936.09 | 30-JUN-24:00 | 4791.02 | 27-JUN-15:00 | 16212.55 | 27-JUN-13:00 | 0.00 |
July | 0.157328E+12 | 0.447685E+11 | 744.00 | 0.154221E+12 | 0.310708E+10 | 0.00 | 0.87 | 31-JUL-23:15 | 0.60 | 06-JUL-06:50 | 75684.66 | 31-JUL-23:53 | 75503.28 | 31-JUL-23:55 | 4762.51 | 20-JUL-15:00 | 23208.45 | 21-JUL-14:00 | 0.00 |
August | 0.203511E+12 | 0.559951E+11 | 744.00 | 0.201288E+12 | 0.222277E+10 | 0.00 | 0.99 | 18-AUG-16:00 | 0.23 | 31-AUG-24:00 | 83032.01 | 04-AUG-18:30 | 83032.01 | 04-AUG-18:30 | 4710.35 | 14-AUG-10:00 | 28520.08 | 10-AUG-14:10 | 0.00 |
September | 0.488572E+11 | 0.128160E+11 | 720.00 | 0.474813E+11 | 0.137590E+10 | 0.00 | 0.39 | 30-SEP-24:00 | 0.11 | 30-SEP-07:00 | 31424.60 | 30-SEP-24:00 | 31424.60 | 30-SEP-24:00 | 3369.07 | 15-SEP-15:10 | 8427.39 | 21-SEP-17:00 | 0.00 |
October | 0.841202E+11 | 0.204463E+11 | 744.00 | 0.837918E+11 | 0.328382E+09 | 0.00 | 0.57 | 31-OCT-24:00 | 0.27 | 30-OCT-06:10 | 49281.94 | 31-OCT-24:00 | 49281.94 | 31-OCT-24:00 | 1913.66 | 12-OCT-15:30 | 12376.33 | 11-OCT-16:50 | 0.00 |
November | 0.119045E+12 | 0.283064E+11 | 720.00 | 0.119028E+12 | 17006943.14 | 0.00 | 0.66 | 03-NOV-16:00 | 0.46 | 24-NOV-07:10 | 55903.94 | 15-NOV-16:20 | 55903.94 | 15-NOV-16:20 | 1089.07 | 16-NOV-18:40 | 14078.18 | 16-NOV-13:00 | 0.00 |
December | 0.153667E+12 | 0.365335E+11 | 744.00 | 0.153661E+12 | 5421157.14 | 0.00 | 0.82 | 04-DEC-16:20 | 0.56 | 11-DEC-07:05 | 68685.31 | 04-DEC-16:20 | 68685.31 | 04-DEC-16:20 | 1002.01 | 01-DEC-13:30 | 15918.00 | 04-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.126664E+13 | 0.322521E+12 | 8429.41 | 0.125710E+13 | 0.953390E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.538486E+10 | 0.171021E+10 | 413.41 | 0.538486E+10 | -0.0 | 0.00 | 0.19 | 0.00 | 13535.17 | 13535.17 | 0.00 | 3726.07 | 0.00 | ||||||
Maximum of Months | 0.203511E+12 | 0.559951E+11 | 744.00 | 0.201288E+12 | 0.310708E+10 | 0.00 | 0.99 | 0.60 | 83032.01 | 83032.01 | 4791.02 | 28520.08 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.145070E+09 | 46974201.41 | 126.46 | 0.145070E+09 | 0.00 | 0.00 | 0.16 | 12-JAN-16:30 | 0.00 | 01-JAN-00:03 | 1119.15 | 12-JAN-16:30 | 1119.15 | 12-JAN-16:30 | 0.00 | 06-JAN-18:20 | 313.87 | 12-JAN-16:30 | 0.00 |
February | 0.326160E+10 | 0.888980E+09 | 634.96 | 0.326160E+10 | -0.0 | 0.00 | 0.45 | 28-FEB-16:55 | 0.00 | 01-FEB-00:03 | 3530.13 | 28-FEB-16:55 | 3530.13 | 28-FEB-16:55 | 0.00 | 20-FEB-09:10 | 890.84 | 28-FEB-16:55 | 0.00 |
March | 0.107358E+11 | 0.265789E+10 | 744.00 | 0.107144E+11 | 21388165.26 | 0.00 | 0.72 | 15-MAR-15:00 | 0.25 | 06-MAR-04:04 | 6233.22 | 31-MAR-23:20 | 6233.22 | 31-MAR-23:20 | 252.16 | 16-MAR-16:10 | 1898.91 | 15-MAR-14:10 | 0.00 |
April | 0.165620E+11 | 0.380654E+10 | 720.00 | 0.165591E+11 | 2866629.37 | 0.00 | 0.89 | 07-APR-14:00 | 0.15 | 30-APR-24:00 | 7835.71 | 24-APR-18:00 | 7835.71 | 24-APR-18:00 | 97.47 | 12-APR-16:10 | 2098.01 | 07-APR-14:00 | 0.00 |
May | 0.424174E+10 | 0.111067E+10 | 744.00 | 0.420576E+10 | 35981625.17 | 0.00 | 0.44 | 31-MAY-24:00 | 0.04 | 01-MAY-06:05 | 3730.22 | 31-MAY-24:00 | 3723.72 | 31-MAY-24:00 | 225.08 | 17-MAY-15:30 | 916.99 | 31-MAY-23:30 | 0.00 |
June | 0.100416E+11 | 0.268831E+10 | 720.00 | 0.985522E+10 | 0.186403E+09 | 0.00 | 0.66 | 30-JUN-23:30 | 0.32 | 14-JUN-06:05 | 5633.18 | 30-JUN-24:00 | 5633.18 | 30-JUN-24:00 | 481.43 | 27-JUN-15:00 | 1649.66 | 27-JUN-13:00 | 0.00 |
July | 0.157743E+11 | 0.449994E+10 | 744.00 | 0.154639E+11 | 0.310405E+09 | 0.00 | 0.85 | 31-JUL-23:15 | 0.57 | 06-JUL-06:50 | 7572.61 | 31-JUL-23:53 | 7554.38 | 31-JUL-23:55 | 476.24 | 20-JUL-15:00 | 2361.45 | 21-JUL-14:00 | 0.00 |
August | 0.203175E+11 | 0.560921E+10 | 744.00 | 0.200957E+11 | 0.221858E+09 | 0.00 | 0.99 | 18-AUG-15:50 | 0.19 | 31-AUG-24:00 | 8391.24 | 10-AUG-18:00 | 8390.26 | 04-AUG-18:30 | 470.93 | 14-AUG-10:00 | 2889.06 | 10-AUG-14:10 | 0.00 |
September | 0.447376E+10 | 0.118786E+10 | 720.00 | 0.433781E+10 | 0.135949E+09 | 0.00 | 0.35 | 21-SEP-17:20 | 0.04 | 30-SEP-06:40 | 2775.02 | 21-SEP-17:20 | 2729.61 | 04-SEP-17:45 | 338.84 | 15-SEP-15:00 | 863.51 | 21-SEP-17:00 | 0.00 |
October | 0.706680E+10 | 0.174333E+10 | 744.00 | 0.703451E+10 | 32296270.43 | 0.00 | 0.54 | 11-OCT-16:50 | 0.11 | 30-OCT-03:25 | 4536.23 | 31-OCT-23:20 | 4536.23 | 31-OCT-23:20 | 191.81 | 12-OCT-15:30 | 1249.10 | 11-OCT-16:50 | 0.00 |
November | 0.102147E+11 | 0.246793E+10 | 720.00 | 0.102131E+11 | 1573329.42 | 0.00 | 0.64 | 03-NOV-16:00 | 0.30 | 24-NOV-04:03 | 5473.84 | 15-NOV-16:20 | 5473.84 | 15-NOV-16:20 | 106.82 | 16-NOV-18:40 | 1374.57 | 16-NOV-17:00 | 0.00 |
December | 0.135336E+11 | 0.326799E+10 | 744.00 | 0.135331E+11 | 504071.69 | 0.00 | 0.78 | 04-DEC-16:20 | 0.42 | 26-DEC-04:23 | 6534.02 | 01-DEC-13:30 | 6514.42 | 04-DEC-16:20 | 93.14 | 01-DEC-13:30 | 1523.33 | 04-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.116369E+12 | 0.299756E+11 | 8105.41 | 0.115419E+12 | 0.949225E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.145070E+09 | 46974201.41 | 126.46 | 0.145070E+09 | -0.0 | 0.00 | 0.16 | 0.00 | 1119.15 | 1119.15 | 0.00 | 313.87 | 0.00 | ||||||
Maximum of Months | 0.203175E+11 | 0.560921E+10 | 744.00 | 0.200957E+11 | 0.310405E+09 | 0.00 | 0.99 | 0.57 | 8391.24 | 8390.26 | 481.43 | 2889.06 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.51 | 0.00 | 103.51 | 0.06 | 662.17 | 0.00 | 0.00 | 0.00 |
February | 157.71 | 0.00 | 157.71 | 5.62 | 618.01 | 0.00 | 0.00 | 0.00 |
March | 191.25 | 0.00 | 191.25 | 52.13 | 458.66 | 0.00 | 0.00 | 0.00 |
April | 243.70 | 0.97 | 242.73 | 116.43 | 330.81 | 0.00 | 0.00 | 0.00 |
May | 283.17 | 12.01 | 271.16 | 214.69 | 200.50 | 0.00 | 0.00 | 0.00 |
June | 340.59 | 28.99 | 311.60 | 360.86 | 126.98 | 0.00 | 0.00 | 0.00 |
July | 315.94 | 20.39 | 295.55 | 387.55 | 86.76 | 0.00 | 0.00 | 0.00 |
August | 273.38 | 4.16 | 269.22 | 315.22 | 116.69 | 0.00 | 0.00 | 0.00 |
September | 208.05 | 0.04 | 208.00 | 182.99 | 197.31 | 0.00 | 0.00 | 0.00 |
October | 155.52 | 0.00 | 155.52 | 65.23 | 330.43 | 0.00 | 0.00 | 0.00 |
November | 104.51 | 0.00 | 104.51 | 14.65 | 443.21 | 0.00 | 0.00 | 0.00 |
December | 96.88 | 0.00 | 96.88 | 0.61 | 651.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 206.38 | 5.57 | 200.81 | 143.85 | 350.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.88 | 0.00 | 96.88 | 0.06 | 86.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.59 | 28.99 | 311.60 | 387.55 | 662.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.51 | 0.00 | 103.51 | 0.06 | 662.18 | 0.00 | 0.00 | 0.00 |
February | 157.71 | 0.00 | 157.71 | 5.62 | 618.01 | 0.00 | 0.00 | 0.00 |
March | 191.25 | 0.00 | 191.25 | 52.13 | 458.66 | 0.00 | 0.00 | 0.00 |
April | 243.69 | 0.97 | 242.72 | 116.42 | 330.81 | 0.00 | 0.00 | 0.00 |
May | 283.16 | 12.01 | 271.15 | 214.69 | 200.50 | 0.00 | 0.00 | 0.00 |
June | 340.58 | 28.99 | 311.59 | 360.85 | 126.98 | 0.00 | 0.00 | 0.00 |
July | 315.94 | 20.39 | 295.54 | 387.54 | 86.76 | 0.00 | 0.00 | 0.00 |
August | 273.37 | 4.16 | 269.21 | 315.22 | 116.69 | 0.00 | 0.00 | 0.00 |
September | 208.04 | 0.04 | 208.00 | 182.99 | 197.31 | 0.00 | 0.00 | 0.00 |
October | 155.52 | 0.00 | 155.52 | 65.23 | 330.43 | 0.00 | 0.00 | 0.00 |
November | 104.51 | 0.00 | 104.51 | 14.65 | 443.22 | 0.00 | 0.00 | 0.00 |
December | 96.88 | 0.00 | 96.88 | 0.61 | 651.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 206.38 | 5.57 | 200.81 | 143.85 | 350.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.88 | 0.00 | 96.88 | 0.06 | 86.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.58 | 28.99 | 311.59 | 387.54 | 662.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.51 | 0.00 | 103.51 | 0.06 | 662.17 | 0.00 | 0.00 | 0.00 |
February | 157.71 | 0.00 | 157.71 | 5.62 | 618.01 | 0.00 | 0.00 | 0.00 |
March | 191.25 | 0.00 | 191.25 | 52.13 | 458.66 | 0.00 | 0.00 | 0.00 |
April | 243.70 | 0.97 | 242.72 | 116.43 | 330.81 | 0.00 | 0.00 | 0.00 |
May | 283.16 | 12.01 | 271.15 | 214.69 | 200.50 | 0.00 | 0.00 | 0.00 |
June | 340.58 | 28.99 | 311.59 | 360.85 | 126.98 | 0.00 | 0.00 | 0.00 |
July | 315.94 | 20.39 | 295.54 | 387.54 | 86.76 | 0.00 | 0.00 | 0.00 |
August | 273.37 | 4.16 | 269.22 | 315.22 | 116.69 | 0.00 | 0.00 | 0.00 |
September | 208.04 | 0.04 | 208.00 | 182.99 | 197.31 | 0.00 | 0.00 | 0.00 |
October | 155.52 | 0.00 | 155.52 | 65.23 | 330.43 | 0.00 | 0.00 | 0.00 |
November | 104.51 | 0.00 | 104.51 | 14.65 | 443.21 | 0.00 | 0.00 | 0.00 |
December | 96.88 | 0.00 | 96.88 | 0.61 | 651.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 206.38 | 5.57 | 200.81 | 143.85 | 350.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.88 | 0.00 | 96.88 | 0.06 | 86.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.58 | 28.99 | 311.59 | 387.54 | 662.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.51 | 0.00 | 103.51 | 0.06 | 662.18 | 0.00 | 0.00 | 0.00 |
February | 157.71 | 0.00 | 157.71 | 5.62 | 618.01 | 0.00 | 0.00 | 0.00 |
March | 191.25 | 0.00 | 191.25 | 52.13 | 458.66 | 0.00 | 0.00 | 0.00 |
April | 243.69 | 0.97 | 242.72 | 116.42 | 330.81 | 0.00 | 0.00 | 0.00 |
May | 283.16 | 12.01 | 271.15 | 214.69 | 200.50 | 0.00 | 0.00 | 0.00 |
June | 340.58 | 28.99 | 311.59 | 360.85 | 126.98 | 0.00 | 0.00 | 0.00 |
July | 315.94 | 20.39 | 295.54 | 387.54 | 86.76 | 0.00 | 0.00 | 0.00 |
August | 273.37 | 4.16 | 269.21 | 315.22 | 116.69 | 0.00 | 0.00 | 0.00 |
September | 208.04 | 0.04 | 208.00 | 182.99 | 197.31 | 0.00 | 0.00 | 0.00 |
October | 155.52 | 0.00 | 155.52 | 65.23 | 330.43 | 0.00 | 0.00 | 0.00 |
November | 104.51 | 0.00 | 104.51 | 14.65 | 443.22 | 0.00 | 0.00 | 0.00 |
December | 96.88 | 0.00 | 96.88 | 0.61 | 651.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 206.38 | 5.57 | 200.81 | 143.85 | 350.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.88 | 0.00 | 96.88 | 0.06 | 86.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.58 | 28.99 | 311.59 | 387.54 | 662.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.50 | 0.00 | 103.50 | 0.06 | 662.15 | 0.00 | 0.00 | 0.00 |
February | 157.70 | 0.00 | 157.70 | 5.62 | 617.99 | 0.00 | 0.00 | 0.00 |
March | 191.24 | 0.00 | 191.24 | 52.12 | 458.64 | 0.00 | 0.00 | 0.00 |
April | 243.69 | 0.97 | 242.71 | 116.42 | 330.80 | 0.00 | 0.00 | 0.00 |
May | 283.15 | 12.01 | 271.14 | 214.68 | 200.49 | 0.00 | 0.00 | 0.00 |
June | 340.57 | 28.99 | 311.58 | 360.84 | 126.97 | 0.00 | 0.00 | 0.00 |
July | 315.92 | 20.39 | 295.53 | 387.53 | 86.76 | 0.00 | 0.00 | 0.00 |
August | 273.36 | 4.16 | 269.20 | 315.21 | 116.69 | 0.00 | 0.00 | 0.00 |
September | 208.03 | 0.04 | 207.99 | 182.98 | 197.30 | 0.00 | 0.00 | 0.00 |
October | 155.51 | 0.00 | 155.51 | 65.23 | 330.42 | 0.00 | 0.00 | 0.00 |
November | 104.50 | 0.00 | 104.50 | 14.65 | 443.20 | 0.00 | 0.00 | 0.00 |
December | 96.88 | 0.00 | 96.88 | 0.61 | 651.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 206.37 | 5.57 | 200.80 | 143.84 | 350.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.88 | 0.00 | 96.88 | 0.06 | 86.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.57 | 28.99 | 311.58 | 387.53 | 662.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 210.47 | 67.87 | 142.60 | 77.19 | 664.41 | 0.00 | 0.00 | 0.00 |
February | 308.82 | 92.67 | 216.15 | 138.55 | 622.43 | 0.00 | 0.00 | 0.00 |
March | 443.15 | 185.59 | 257.56 | 335.03 | 455.98 | 0.00 | 0.00 | 0.00 |
April | 586.53 | 259.16 | 327.37 | 538.25 | 331.54 | 0.00 | 0.00 | 0.00 |
May | 657.13 | 290.68 | 366.45 | 704.34 | 219.76 | 0.00 | 0.00 | 0.00 |
June | 733.90 | 324.35 | 409.55 | 883.32 | 137.47 | 0.00 | 0.00 | 0.00 |
July | 704.74 | 310.29 | 394.45 | 913.24 | 89.24 | 0.00 | 0.00 | 0.00 |
August | 636.46 | 267.15 | 369.31 | 806.52 | 117.38 | 0.00 | 0.00 | 0.00 |
September | 529.64 | 234.93 | 294.71 | 603.85 | 203.16 | 0.00 | 0.00 | 0.00 |
October | 359.41 | 148.66 | 210.75 | 311.20 | 333.16 | 0.00 | 0.00 | 0.00 |
November | 203.86 | 65.40 | 138.47 | 116.79 | 447.71 | 0.00 | 0.00 | 0.00 |
December | 164.12 | 33.91 | 130.21 | 38.70 | 660.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 462.20 | 190.52 | 271.69 | 457.31 | 355.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.12 | 33.91 | 130.21 | 38.70 | 89.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 733.90 | 324.35 | 409.55 | 913.24 | 664.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 210.47 | 67.87 | 142.60 | 77.19 | 664.41 | 0.00 | 0.00 | 0.00 |
February | 308.82 | 92.67 | 216.15 | 138.55 | 622.43 | 0.00 | 0.00 | 0.00 |
March | 443.15 | 185.59 | 257.56 | 335.03 | 455.98 | 0.00 | 0.00 | 0.00 |
April | 586.53 | 259.16 | 327.37 | 538.25 | 331.54 | 0.00 | 0.00 | 0.00 |
May | 657.13 | 290.68 | 366.45 | 704.34 | 219.76 | 0.00 | 0.00 | 0.00 |
June | 733.90 | 324.35 | 409.55 | 883.32 | 137.47 | 0.00 | 0.00 | 0.00 |
July | 704.74 | 310.29 | 394.45 | 913.24 | 89.24 | 0.00 | 0.00 | 0.00 |
August | 636.46 | 267.15 | 369.31 | 806.52 | 117.38 | 0.00 | 0.00 | 0.00 |
September | 529.64 | 234.93 | 294.71 | 603.85 | 203.16 | 0.00 | 0.00 | 0.00 |
October | 359.41 | 148.66 | 210.75 | 311.20 | 333.16 | 0.00 | 0.00 | 0.00 |
November | 203.86 | 65.40 | 138.47 | 116.79 | 447.71 | 0.00 | 0.00 | 0.00 |
December | 164.12 | 33.91 | 130.21 | 38.70 | 660.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 462.20 | 190.52 | 271.69 | 457.31 | 355.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.12 | 33.91 | 130.21 | 38.70 | 89.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 733.90 | 324.35 | 409.55 | 913.24 | 664.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 210.46 | 67.87 | 142.60 | 77.18 | 664.39 | 0.00 | 0.00 | 0.00 |
February | 308.81 | 92.67 | 216.15 | 138.54 | 622.41 | 0.00 | 0.00 | 0.00 |
March | 443.14 | 185.58 | 257.56 | 335.02 | 455.97 | 0.00 | 0.00 | 0.00 |
April | 586.52 | 259.16 | 327.37 | 538.24 | 331.54 | 0.00 | 0.00 | 0.00 |
May | 657.12 | 290.68 | 366.44 | 704.32 | 219.76 | 0.00 | 0.00 | 0.00 |
June | 733.89 | 324.34 | 409.55 | 883.31 | 137.47 | 0.00 | 0.00 | 0.00 |
July | 704.73 | 310.28 | 394.44 | 913.22 | 89.24 | 0.00 | 0.00 | 0.00 |
August | 636.44 | 267.14 | 369.30 | 806.50 | 117.37 | 0.00 | 0.00 | 0.00 |
September | 529.63 | 234.92 | 294.71 | 603.84 | 203.16 | 0.00 | 0.00 | 0.00 |
October | 359.40 | 148.66 | 210.74 | 311.19 | 333.16 | 0.00 | 0.00 | 0.00 |
November | 203.86 | 65.40 | 138.46 | 116.79 | 447.70 | 0.00 | 0.00 | 0.00 |
December | 164.12 | 33.91 | 130.21 | 38.69 | 660.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 462.20 | 190.51 | 271.68 | 457.30 | 355.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.12 | 33.91 | 130.21 | 38.69 | 89.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 733.89 | 324.34 | 409.55 | 913.22 | 664.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 445.08 | 259.80 | 185.27 | 352.57 | 548.60 | 0.00 | 0.00 | 0.00 |
February | 508.17 | 245.03 | 263.13 | 396.68 | 535.98 | 0.00 | 0.00 | 0.00 |
March | 620.25 | 348.52 | 271.74 | 596.13 | 407.46 | 0.00 | 0.00 | 0.00 |
April | 513.67 | 205.26 | 308.41 | 514.18 | 324.72 | 0.00 | 0.00 | 0.00 |
May | 449.51 | 130.55 | 318.95 | 493.50 | 214.73 | 0.00 | 0.00 | 0.00 |
June | 436.78 | 92.55 | 344.22 | 536.48 | 137.34 | 0.00 | 0.00 | 0.00 |
July | 445.88 | 108.18 | 337.69 | 605.40 | 92.41 | 0.00 | 0.00 | 0.00 |
August | 500.57 | 162.30 | 338.27 | 667.21 | 121.06 | 0.00 | 0.00 | 0.00 |
September | 582.01 | 283.48 | 298.53 | 716.46 | 197.11 | 0.00 | 0.00 | 0.00 |
October | 556.90 | 318.11 | 238.79 | 590.39 | 302.91 | 0.00 | 0.00 | 0.00 |
November | 398.84 | 225.16 | 173.68 | 366.79 | 391.69 | 0.00 | 0.00 | 0.00 |
December | 372.17 | 192.62 | 179.56 | 276.41 | 549.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 485.67 | 214.18 | 271.48 | 510.01 | 317.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 372.17 | 92.55 | 173.68 | 276.41 | 92.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.25 | 348.52 | 344.22 | 716.46 | 549.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 445.08 | 259.80 | 185.27 | 352.57 | 548.60 | 0.00 | 0.00 | 0.00 |
February | 508.16 | 245.03 | 263.13 | 396.68 | 535.98 | 0.00 | 0.00 | 0.00 |
March | 620.25 | 348.51 | 271.74 | 596.13 | 407.46 | 0.00 | 0.00 | 0.00 |
April | 513.67 | 205.26 | 308.40 | 514.17 | 324.72 | 0.00 | 0.00 | 0.00 |
May | 449.50 | 130.55 | 318.95 | 493.50 | 214.73 | 0.00 | 0.00 | 0.00 |
June | 436.77 | 92.55 | 344.22 | 536.48 | 137.34 | 0.00 | 0.00 | 0.00 |
July | 445.87 | 108.18 | 337.69 | 605.39 | 92.41 | 0.00 | 0.00 | 0.00 |
August | 500.57 | 162.30 | 338.27 | 667.20 | 121.06 | 0.00 | 0.00 | 0.00 |
September | 582.01 | 283.48 | 298.53 | 716.45 | 197.11 | 0.00 | 0.00 | 0.00 |
October | 556.90 | 318.11 | 238.79 | 590.39 | 302.91 | 0.00 | 0.00 | 0.00 |
November | 398.84 | 225.16 | 173.68 | 366.79 | 391.69 | 0.00 | 0.00 | 0.00 |
December | 372.17 | 192.62 | 179.56 | 276.41 | 549.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 485.66 | 214.18 | 271.48 | 510.01 | 317.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 372.17 | 92.55 | 173.68 | 276.41 | 92.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.25 | 348.51 | 344.22 | 716.45 | 549.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 445.08 | 259.80 | 185.27 | 352.57 | 548.60 | 0.00 | 0.00 | 0.00 |
February | 508.17 | 245.03 | 263.13 | 396.68 | 535.98 | 0.00 | 0.00 | 0.00 |
March | 620.25 | 348.52 | 271.74 | 596.13 | 407.46 | 0.00 | 0.00 | 0.00 |
April | 513.67 | 205.26 | 308.41 | 514.18 | 324.72 | 0.00 | 0.00 | 0.00 |
May | 449.51 | 130.55 | 318.95 | 493.50 | 214.73 | 0.00 | 0.00 | 0.00 |
June | 436.78 | 92.55 | 344.22 | 536.48 | 137.34 | 0.00 | 0.00 | 0.00 |
July | 445.88 | 108.18 | 337.69 | 605.40 | 92.41 | 0.00 | 0.00 | 0.00 |
August | 500.57 | 162.30 | 338.27 | 667.21 | 121.06 | 0.00 | 0.00 | 0.00 |
September | 582.01 | 283.48 | 298.53 | 716.46 | 197.11 | 0.00 | 0.00 | 0.00 |
October | 556.90 | 318.11 | 238.79 | 590.39 | 302.91 | 0.00 | 0.00 | 0.00 |
November | 398.84 | 225.16 | 173.68 | 366.79 | 391.69 | 0.00 | 0.00 | 0.00 |
December | 372.17 | 192.62 | 179.56 | 276.41 | 549.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 485.67 | 214.18 | 271.48 | 510.01 | 317.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 372.17 | 92.55 | 173.68 | 276.41 | 92.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.25 | 348.52 | 344.22 | 716.46 | 549.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 445.08 | 259.80 | 185.27 | 352.57 | 548.60 | 0.00 | 0.00 | 0.00 |
February | 508.16 | 245.03 | 263.13 | 396.68 | 535.98 | 0.00 | 0.00 | 0.00 |
March | 620.25 | 348.51 | 271.74 | 596.13 | 407.46 | 0.00 | 0.00 | 0.00 |
April | 513.67 | 205.26 | 308.40 | 514.17 | 324.72 | 0.00 | 0.00 | 0.00 |
May | 449.50 | 130.55 | 318.95 | 493.50 | 214.73 | 0.00 | 0.00 | 0.00 |
June | 436.77 | 92.55 | 344.22 | 536.48 | 137.34 | 0.00 | 0.00 | 0.00 |
July | 445.87 | 108.18 | 337.69 | 605.39 | 92.41 | 0.00 | 0.00 | 0.00 |
August | 500.57 | 162.30 | 338.27 | 667.20 | 121.06 | 0.00 | 0.00 | 0.00 |
September | 582.01 | 283.48 | 298.53 | 716.45 | 197.11 | 0.00 | 0.00 | 0.00 |
October | 556.90 | 318.11 | 238.79 | 590.39 | 302.91 | 0.00 | 0.00 | 0.00 |
November | 398.84 | 225.16 | 173.68 | 366.79 | 391.69 | 0.00 | 0.00 | 0.00 |
December | 372.17 | 192.62 | 179.56 | 276.41 | 549.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 485.66 | 214.18 | 271.48 | 510.01 | 317.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 372.17 | 92.55 | 173.68 | 276.41 | 92.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.25 | 348.51 | 344.22 | 716.45 | 549.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 445.06 | 259.79 | 185.27 | 352.56 | 548.57 | 0.00 | 0.00 | 0.00 |
February | 508.15 | 245.02 | 263.12 | 396.66 | 535.95 | 0.00 | 0.00 | 0.00 |
March | 620.23 | 348.50 | 271.73 | 596.10 | 407.44 | 0.00 | 0.00 | 0.00 |
April | 513.65 | 205.25 | 308.39 | 514.15 | 324.71 | 0.00 | 0.00 | 0.00 |
May | 449.49 | 130.55 | 318.94 | 493.48 | 214.72 | 0.00 | 0.00 | 0.00 |
June | 436.76 | 92.55 | 344.21 | 536.46 | 137.33 | 0.00 | 0.00 | 0.00 |
July | 445.86 | 108.18 | 337.68 | 605.37 | 92.41 | 0.00 | 0.00 | 0.00 |
August | 500.55 | 162.29 | 338.26 | 667.18 | 121.05 | 0.00 | 0.00 | 0.00 |
September | 581.99 | 283.47 | 298.52 | 716.43 | 197.11 | 0.00 | 0.00 | 0.00 |
October | 556.87 | 318.10 | 238.78 | 590.37 | 302.89 | 0.00 | 0.00 | 0.00 |
November | 398.82 | 225.15 | 173.67 | 366.77 | 391.67 | 0.00 | 0.00 | 0.00 |
December | 372.16 | 192.61 | 179.55 | 276.40 | 549.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 485.65 | 214.17 | 271.47 | 509.99 | 317.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 372.16 | 92.55 | 173.67 | 276.40 | 92.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.23 | 348.50 | 344.21 | 716.43 | 549.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.58 | 42.39 | 138.18 | 45.78 | 715.59 | 0.00 | 0.00 | 0.00 |
February | 292.67 | 75.22 | 217.45 | 113.62 | 682.53 | 0.00 | 0.00 | 0.00 |
March | 458.70 | 196.41 | 262.30 | 341.45 | 517.40 | 0.00 | 0.00 | 0.00 |
April | 561.62 | 230.29 | 331.33 | 493.21 | 400.09 | 0.00 | 0.00 | 0.00 |
May | 662.52 | 299.42 | 363.10 | 707.41 | 251.57 | 0.00 | 0.00 | 0.00 |
June | 799.35 | 375.98 | 423.37 | 960.09 | 171.17 | 0.00 | 0.00 | 0.00 |
July | 714.65 | 313.33 | 401.32 | 911.57 | 122.02 | 0.00 | 0.00 | 0.00 |
August | 646.36 | 274.84 | 371.52 | 806.83 | 158.46 | 0.00 | 0.00 | 0.00 |
September | 507.59 | 219.21 | 288.38 | 572.44 | 233.41 | 0.00 | 0.00 | 0.00 |
October | 329.04 | 115.91 | 213.14 | 267.44 | 381.77 | 0.00 | 0.00 | 0.00 |
November | 194.99 | 56.19 | 138.80 | 99.20 | 515.71 | 0.00 | 0.00 | 0.00 |
December | 169.04 | 36.83 | 132.21 | 39.90 | 746.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 460.52 | 186.87 | 273.64 | 448.39 | 406.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 169.04 | 36.83 | 132.21 | 39.90 | 122.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 799.35 | 375.98 | 423.37 | 960.09 | 746.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.58 | 42.39 | 138.18 | 45.78 | 715.59 | 0.00 | 0.00 | 0.00 |
February | 292.67 | 75.22 | 217.45 | 113.62 | 682.53 | 0.00 | 0.00 | 0.00 |
March | 458.70 | 196.41 | 262.30 | 341.45 | 517.40 | 0.00 | 0.00 | 0.00 |
April | 561.62 | 230.29 | 331.33 | 493.21 | 400.09 | 0.00 | 0.00 | 0.00 |
May | 662.52 | 299.42 | 363.10 | 707.41 | 251.57 | 0.00 | 0.00 | 0.00 |
June | 799.35 | 375.98 | 423.37 | 960.09 | 171.17 | 0.00 | 0.00 | 0.00 |
July | 714.65 | 313.33 | 401.32 | 911.57 | 122.02 | 0.00 | 0.00 | 0.00 |
August | 646.36 | 274.84 | 371.52 | 806.83 | 158.46 | 0.00 | 0.00 | 0.00 |
September | 507.59 | 219.21 | 288.38 | 572.44 | 233.41 | 0.00 | 0.00 | 0.00 |
October | 329.04 | 115.91 | 213.14 | 267.44 | 381.77 | 0.00 | 0.00 | 0.00 |
November | 194.99 | 56.19 | 138.80 | 99.20 | 515.71 | 0.00 | 0.00 | 0.00 |
December | 169.04 | 36.83 | 132.21 | 39.90 | 746.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 460.52 | 186.87 | 273.64 | 448.39 | 406.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 169.04 | 36.83 | 132.21 | 39.90 | 122.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 799.35 | 375.98 | 423.37 | 960.09 | 746.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.57 | 42.39 | 138.18 | 45.77 | 715.58 | 0.00 | 0.00 | 0.00 |
February | 292.66 | 75.22 | 217.44 | 113.62 | 682.52 | 0.00 | 0.00 | 0.00 |
March | 458.69 | 196.40 | 262.29 | 341.45 | 517.39 | 0.00 | 0.00 | 0.00 |
April | 561.61 | 230.28 | 331.33 | 493.20 | 400.09 | 0.00 | 0.00 | 0.00 |
May | 662.51 | 299.41 | 363.10 | 707.40 | 251.56 | 0.00 | 0.00 | 0.00 |
June | 799.33 | 375.97 | 423.36 | 960.08 | 171.17 | 0.00 | 0.00 | 0.00 |
July | 714.64 | 313.32 | 401.31 | 911.55 | 122.01 | 0.00 | 0.00 | 0.00 |
August | 646.35 | 274.83 | 371.51 | 806.81 | 158.46 | 0.00 | 0.00 | 0.00 |
September | 507.58 | 219.20 | 288.38 | 572.43 | 233.40 | 0.00 | 0.00 | 0.00 |
October | 329.04 | 115.91 | 213.13 | 267.44 | 381.77 | 0.00 | 0.00 | 0.00 |
November | 194.99 | 56.19 | 138.80 | 99.20 | 515.70 | 0.00 | 0.00 | 0.00 |
December | 169.04 | 36.83 | 132.21 | 39.90 | 746.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 460.51 | 186.87 | 273.64 | 448.38 | 406.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 169.04 | 36.83 | 132.21 | 39.90 | 122.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 799.33 | 375.97 | 423.36 | 960.08 | 746.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 517.54 | 0.00 | 517.54 | 6.76 | 3006.85 | 0.00 | 0.00 | 0.00 |
February | 788.54 | 0.00 | 788.54 | 53.33 | 2806.40 | 0.00 | 0.00 | 0.00 |
March | 956.27 | 0.00 | 956.27 | 307.35 | 2046.93 | 0.00 | 0.00 | 0.00 |
April | 1218.49 | 4.86 | 1213.63 | 660.22 | 1455.94 | 0.00 | 0.00 | 0.00 |
May | 1415.83 | 60.04 | 1355.79 | 1106.55 | 938.03 | 0.00 | 0.00 | 0.00 |
June | 1702.94 | 144.96 | 1557.98 | 1816.35 | 610.34 | 0.00 | 0.00 | 0.00 |
July | 1579.70 | 101.97 | 1477.73 | 1945.19 | 428.28 | 0.00 | 0.00 | 0.00 |
August | 1366.88 | 20.79 | 1346.09 | 1589.93 | 567.92 | 0.00 | 0.00 | 0.00 |
September | 1040.23 | 0.22 | 1040.01 | 936.08 | 918.61 | 0.00 | 0.00 | 0.00 |
October | 777.61 | 0.00 | 777.61 | 381.18 | 1455.13 | 0.00 | 0.00 | 0.00 |
November | 522.54 | 0.00 | 522.54 | 110.87 | 1900.58 | 0.00 | 0.00 | 0.00 |
December | 484.40 | 0.00 | 484.40 | 8.18 | 2871.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1031.92 | 27.86 | 1004.06 | 747.67 | 1577.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 484.40 | 0.00 | 484.40 | 6.76 | 428.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1702.94 | 144.96 | 1557.98 | 1945.19 | 3006.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 631.40 | 203.60 | 427.80 | 245.40 | 1824.85 | 0.00 | 0.00 | 0.00 |
February | 926.45 | 278.00 | 648.45 | 441.26 | 1726.42 | 0.00 | 0.00 | 0.00 |
March | 1329.43 | 556.76 | 772.67 | 1032.96 | 1258.80 | 0.00 | 0.00 | 0.00 |
April | 1759.59 | 777.48 | 982.11 | 1638.46 | 920.07 | 0.00 | 0.00 | 0.00 |
May | 1971.37 | 872.04 | 1099.33 | 2114.38 | 625.75 | 0.00 | 0.00 | 0.00 |
June | 2201.68 | 973.04 | 1228.65 | 2638.24 | 405.86 | 0.00 | 0.00 | 0.00 |
July | 2114.19 | 930.85 | 1183.34 | 2720.35 | 282.92 | 0.00 | 0.00 | 0.00 |
August | 1909.35 | 801.44 | 1107.91 | 2403.39 | 369.00 | 0.00 | 0.00 | 0.00 |
September | 1588.91 | 704.78 | 884.13 | 1812.89 | 578.02 | 0.00 | 0.00 | 0.00 |
October | 1078.21 | 445.98 | 632.23 | 962.32 | 909.33 | 0.00 | 0.00 | 0.00 |
November | 611.58 | 196.19 | 415.39 | 376.62 | 1206.88 | 0.00 | 0.00 | 0.00 |
December | 492.35 | 101.73 | 390.62 | 128.36 | 1799.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1386.60 | 571.54 | 815.06 | 1381.27 | 988.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 492.35 | 101.73 | 390.62 | 128.36 | 282.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2201.68 | 973.04 | 1228.65 | 2720.35 | 1824.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2225.43 | 1299.05 | 926.38 | 1778.03 | 2602.00 | 0.00 | 0.00 | 0.00 |
February | 2540.89 | 1225.19 | 1315.69 | 1999.07 | 2552.89 | 0.00 | 0.00 | 0.00 |
March | 3101.32 | 1742.61 | 1358.71 | 2985.83 | 1935.88 | 0.00 | 0.00 | 0.00 |
April | 2568.38 | 1026.33 | 1542.05 | 2585.00 | 1528.25 | 0.00 | 0.00 | 0.00 |
May | 2247.56 | 652.79 | 1594.78 | 2461.25 | 1035.33 | 0.00 | 0.00 | 0.00 |
June | 2183.91 | 462.78 | 1721.13 | 2676.46 | 666.22 | 0.00 | 0.00 | 0.00 |
July | 2229.41 | 540.93 | 1688.49 | 3016.76 | 465.26 | 0.00 | 0.00 | 0.00 |
August | 2502.89 | 811.50 | 1691.39 | 3325.20 | 606.80 | 0.00 | 0.00 | 0.00 |
September | 2910.11 | 1417.44 | 1492.67 | 3565.67 | 959.26 | 0.00 | 0.00 | 0.00 |
October | 2784.54 | 1590.59 | 1193.96 | 2951.98 | 1440.19 | 0.00 | 0.00 | 0.00 |
November | 1994.23 | 1125.81 | 868.42 | 1851.55 | 1832.32 | 0.00 | 0.00 | 0.00 |
December | 1860.90 | 963.10 | 897.80 | 1406.84 | 2564.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2428.38 | 1070.94 | 1357.44 | 2553.53 | 1510.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1860.90 | 462.78 | 868.42 | 1406.84 | 465.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3101.32 | 1742.61 | 1721.13 | 3565.67 | 2602.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 541.73 | 127.18 | 414.55 | 149.10 | 1928.82 | 0.00 | 0.00 | 0.00 |
February | 877.99 | 225.65 | 652.34 | 374.83 | 1818.36 | 0.00 | 0.00 | 0.00 |
March | 1376.09 | 589.21 | 786.88 | 1086.17 | 1327.66 | 0.00 | 0.00 | 0.00 |
April | 1684.84 | 690.85 | 993.99 | 1562.58 | 997.24 | 0.00 | 0.00 | 0.00 |
May | 1987.54 | 898.24 | 1089.30 | 2149.15 | 690.03 | 0.00 | 0.00 | 0.00 |
June | 2398.02 | 1127.93 | 1270.09 | 2900.49 | 469.31 | 0.00 | 0.00 | 0.00 |
July | 2143.92 | 939.97 | 1203.95 | 2761.85 | 335.60 | 0.00 | 0.00 | 0.00 |
August | 1939.05 | 824.50 | 1114.55 | 2456.67 | 420.99 | 0.00 | 0.00 | 0.00 |
September | 1522.76 | 657.61 | 865.14 | 1742.97 | 630.38 | 0.00 | 0.00 | 0.00 |
October | 987.12 | 347.72 | 639.40 | 860.49 | 967.80 | 0.00 | 0.00 | 0.00 |
November | 584.97 | 168.57 | 416.40 | 343.81 | 1261.39 | 0.00 | 0.00 | 0.00 |
December | 507.12 | 110.50 | 396.62 | 142.66 | 1871.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1381.54 | 560.61 | 820.92 | 1382.96 | 1056.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 507.12 | 110.50 | 396.62 | 142.66 | 335.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2398.02 | 1127.93 | 1270.09 | 2900.49 | 1928.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 517.54 | 0.00 | 517.54 | 11.47 | 2899.20 | 0.00 | 0.00 | 0.00 |
February | 788.54 | 0.00 | 788.54 | 63.33 | 2702.54 | 0.00 | 0.00 | 0.00 |
March | 956.27 | 0.00 | 956.27 | 332.38 | 1923.25 | 0.00 | 0.00 | 0.00 |
April | 1218.49 | 4.86 | 1213.63 | 705.21 | 1345.60 | 0.00 | 0.00 | 0.00 |
May | 1415.83 | 60.04 | 1355.79 | 1141.39 | 880.87 | 0.00 | 0.00 | 0.00 |
June | 1702.94 | 144.96 | 1557.98 | 1818.41 | 596.07 | 0.00 | 0.00 | 0.00 |
July | 1579.70 | 101.97 | 1477.73 | 1934.08 | 427.00 | 0.00 | 0.00 | 0.00 |
August | 1366.88 | 20.79 | 1346.09 | 1586.21 | 557.23 | 0.00 | 0.00 | 0.00 |
September | 1040.23 | 0.22 | 1040.01 | 958.09 | 859.55 | 0.00 | 0.00 | 0.00 |
October | 777.61 | 0.00 | 777.61 | 428.11 | 1306.98 | 0.00 | 0.00 | 0.00 |
November | 522.54 | 0.00 | 522.54 | 137.13 | 1726.07 | 0.00 | 0.00 | 0.00 |
December | 484.40 | 0.00 | 484.40 | 12.08 | 2739.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1031.92 | 27.86 | 1004.06 | 764.81 | 1491.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 484.40 | 0.00 | 484.40 | 11.47 | 427.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1702.94 | 144.96 | 1557.98 | 1934.08 | 2899.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 631.40 | 203.60 | 427.80 | 253.59 | 1758.97 | 0.00 | 0.00 | 0.00 |
February | 926.45 | 278.00 | 648.45 | 454.23 | 1665.30 | 0.00 | 0.00 | 0.00 |
March | 1329.43 | 556.76 | 772.67 | 1055.58 | 1184.92 | 0.00 | 0.00 | 0.00 |
April | 1759.59 | 777.48 | 982.11 | 1663.03 | 863.85 | 0.00 | 0.00 | 0.00 |
May | 1971.37 | 872.04 | 1099.33 | 2121.60 | 600.45 | 0.00 | 0.00 | 0.00 |
June | 2201.68 | 973.04 | 1228.65 | 2629.45 | 402.89 | 0.00 | 0.00 | 0.00 |
July | 2114.19 | 930.85 | 1183.34 | 2706.50 | 286.56 | 0.00 | 0.00 | 0.00 |
August | 1909.35 | 801.44 | 1107.91 | 2394.30 | 368.41 | 0.00 | 0.00 | 0.00 |
September | 1588.91 | 704.78 | 884.13 | 1818.22 | 554.95 | 0.00 | 0.00 | 0.00 |
October | 1078.21 | 445.98 | 632.23 | 993.37 | 830.82 | 0.00 | 0.00 | 0.00 |
November | 611.58 | 196.19 | 415.39 | 399.11 | 1103.23 | 0.00 | 0.00 | 0.00 |
December | 492.35 | 101.73 | 390.62 | 135.54 | 1719.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1386.60 | 571.54 | 815.06 | 1390.38 | 941.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 492.35 | 101.73 | 390.62 | 135.54 | 286.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2201.68 | 973.04 | 1228.65 | 2706.50 | 1758.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2225.43 | 1299.05 | 926.38 | 1803.06 | 2491.08 | 0.00 | 0.00 | 0.00 |
February | 2540.89 | 1225.19 | 1315.69 | 2025.88 | 2448.72 | 0.00 | 0.00 | 0.00 |
March | 3101.32 | 1742.61 | 1358.71 | 3025.63 | 1810.59 | 0.00 | 0.00 | 0.00 |
April | 2568.38 | 1026.33 | 1542.05 | 2619.74 | 1427.21 | 0.00 | 0.00 | 0.00 |
May | 2247.56 | 652.79 | 1594.78 | 2475.94 | 983.57 | 0.00 | 0.00 | 0.00 |
June | 2183.91 | 462.78 | 1721.13 | 2669.01 | 652.71 | 0.00 | 0.00 | 0.00 |
July | 2229.41 | 540.93 | 1688.49 | 3000.58 | 465.35 | 0.00 | 0.00 | 0.00 |
August | 2502.89 | 811.50 | 1691.39 | 3314.40 | 600.21 | 0.00 | 0.00 | 0.00 |
September | 2910.11 | 1417.44 | 1492.67 | 3573.20 | 915.93 | 0.00 | 0.00 | 0.00 |
October | 2784.54 | 1590.59 | 1193.96 | 2997.49 | 1313.34 | 0.00 | 0.00 | 0.00 |
November | 1994.23 | 1125.81 | 868.42 | 1894.47 | 1669.89 | 0.00 | 0.00 | 0.00 |
December | 1860.90 | 963.10 | 897.80 | 1433.92 | 2435.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2428.38 | 1070.94 | 1357.44 | 2572.60 | 1429.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1860.90 | 462.78 | 868.42 | 1433.92 | 465.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3101.32 | 1742.61 | 1721.13 | 3573.20 | 2491.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 541.73 | 127.18 | 414.55 | 155.03 | 1858.86 | 0.00 | 0.00 | 0.00 |
February | 877.99 | 225.65 | 652.34 | 382.54 | 1757.23 | 0.00 | 0.00 | 0.00 |
March | 1376.09 | 589.21 | 786.88 | 1101.33 | 1254.43 | 0.00 | 0.00 | 0.00 |
April | 1684.84 | 690.85 | 993.99 | 1579.71 | 938.44 | 0.00 | 0.00 | 0.00 |
May | 1987.54 | 898.24 | 1089.30 | 2156.93 | 660.22 | 0.00 | 0.00 | 0.00 |
June | 2398.02 | 1127.93 | 1270.09 | 2893.44 | 461.50 | 0.00 | 0.00 | 0.00 |
July | 2143.92 | 939.97 | 1203.95 | 2750.68 | 335.15 | 0.00 | 0.00 | 0.00 |
August | 1939.05 | 824.50 | 1114.55 | 2450.57 | 416.88 | 0.00 | 0.00 | 0.00 |
September | 1522.76 | 657.61 | 865.14 | 1749.76 | 603.34 | 0.00 | 0.00 | 0.00 |
October | 987.12 | 347.72 | 639.40 | 881.29 | 894.08 | 0.00 | 0.00 | 0.00 |
November | 584.97 | 168.57 | 416.40 | 359.18 | 1169.00 | 0.00 | 0.00 | 0.00 |
December | 507.12 | 110.50 | 396.62 | 148.32 | 1792.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1381.54 | 560.61 | 820.92 | 1389.43 | 1008.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 507.12 | 110.50 | 396.62 | 148.32 | 335.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2398.02 | 1127.93 | 1270.09 | 2893.44 | 1858.86 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277236E+09 | 0.00 | 0.277236E+09 | 163825.17 | 0.177357E+10 |
February | 0.381526E+09 | 0.00 | 0.381526E+09 | 13601656.35 | 0.149509E+10 |
March | 0.512257E+09 | 0.00 | 0.512257E+09 | 0.139618E+09 | 0.122848E+10 |
April | 0.631665E+09 | 2520578.33 | 0.629145E+09 | 0.301782E+09 | 0.857459E+09 |
May | 0.758430E+09 | 32161509.05 | 0.726268E+09 | 0.575028E+09 | 0.537022E+09 |
June | 0.882804E+09 | 75148287.61 | 0.807656E+09 | 0.935342E+09 | 0.329131E+09 |
July | 0.846215E+09 | 54624744.50 | 0.791591E+09 | 0.103801E+10 | 0.232387E+09 |
August | 0.732211E+09 | 11138934.65 | 0.721072E+09 | 0.844293E+09 | 0.312553E+09 |
September | 0.539254E+09 | 112032.80 | 0.539141E+09 | 0.474315E+09 | 0.511418E+09 |
October | 0.416552E+09 | 0.00 | 0.416552E+09 | 0.174714E+09 | 0.885027E+09 |
November | 0.270883E+09 | 0.00 | 0.270883E+09 | 37964817.64 | 0.114881E+10 |
December | 0.259485E+09 | 0.00 | 0.259485E+09 | 1620747.53 | 0.174427E+10 |
Annual Sum or Average | 0.650852E+10 | 0.175706E+09 | 0.633281E+10 | 0.453645E+10 | 0.110552E+11 |
Minimum of Months | 0.259485E+09 | 0.00 | 0.259485E+09 | 163825.17 | 0.232387E+09 |
Maximum of Months | 0.882804E+09 | 75148287.61 | 0.807656E+09 | 0.103801E+10 | 0.177357E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277232E+09 | 0.00 | 0.277232E+09 | 163732.78 | 0.177357E+10 |
February | 0.381520E+09 | 0.00 | 0.381520E+09 | 13599847.91 | 0.149510E+10 |
March | 0.512250E+09 | 0.00 | 0.512250E+09 | 0.139613E+09 | 0.122848E+10 |
April | 0.631656E+09 | 2520522.91 | 0.629136E+09 | 0.301773E+09 | 0.857460E+09 |
May | 0.758419E+09 | 32160802.02 | 0.726258E+09 | 0.575016E+09 | 0.537022E+09 |
June | 0.882792E+09 | 75146635.57 | 0.807645E+09 | 0.935327E+09 | 0.329130E+09 |
July | 0.846203E+09 | 54623543.64 | 0.791580E+09 | 0.103799E+10 | 0.232386E+09 |
August | 0.732201E+09 | 11138689.77 | 0.721062E+09 | 0.844281E+09 | 0.312552E+09 |
September | 0.539246E+09 | 112030.34 | 0.539134E+09 | 0.474307E+09 | 0.511417E+09 |
October | 0.416545E+09 | 0.00 | 0.416545E+09 | 0.174708E+09 | 0.885027E+09 |
November | 0.270879E+09 | 0.00 | 0.270879E+09 | 37962949.58 | 0.114881E+10 |
December | 0.259480E+09 | 0.00 | 0.259480E+09 | 1620529.48 | 0.174427E+10 |
Annual Sum or Average | 0.650842E+10 | 0.175702E+09 | 0.633272E+10 | 0.453636E+10 | 0.110552E+11 |
Minimum of Months | 0.259480E+09 | 0.00 | 0.259480E+09 | 163732.78 | 0.232386E+09 |
Maximum of Months | 0.882792E+09 | 75146635.57 | 0.807645E+09 | 0.103799E+10 | 0.177357E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277233E+09 | 0.00 | 0.277233E+09 | 163763.58 | 0.177357E+10 |
February | 0.381522E+09 | 0.00 | 0.381522E+09 | 13600450.72 | 0.149509E+10 |
March | 0.512252E+09 | 0.00 | 0.512252E+09 | 0.139615E+09 | 0.122848E+10 |
April | 0.631659E+09 | 2520541.39 | 0.629139E+09 | 0.301776E+09 | 0.857460E+09 |
May | 0.758423E+09 | 32161037.69 | 0.726262E+09 | 0.575020E+09 | 0.537022E+09 |
June | 0.882796E+09 | 75147186.25 | 0.807649E+09 | 0.935332E+09 | 0.329130E+09 |
July | 0.846207E+09 | 54623943.93 | 0.791583E+09 | 0.103800E+10 | 0.232386E+09 |
August | 0.732204E+09 | 11138771.40 | 0.721066E+09 | 0.844285E+09 | 0.312552E+09 |
September | 0.539248E+09 | 112031.16 | 0.539136E+09 | 0.474310E+09 | 0.511417E+09 |
October | 0.416548E+09 | 0.00 | 0.416548E+09 | 0.174710E+09 | 0.885027E+09 |
November | 0.270880E+09 | 0.00 | 0.270880E+09 | 37963572.27 | 0.114881E+10 |
December | 0.259482E+09 | 0.00 | 0.259482E+09 | 1620602.16 | 0.174427E+10 |
Annual Sum or Average | 0.650845E+10 | 0.175704E+09 | 0.633275E+10 | 0.453639E+10 | 0.110552E+11 |
Minimum of Months | 0.259482E+09 | 0.00 | 0.259482E+09 | 163763.58 | 0.232386E+09 |
Maximum of Months | 0.882796E+09 | 75147186.25 | 0.807649E+09 | 0.103800E+10 | 0.177357E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277232E+09 | 0.00 | 0.277232E+09 | 163732.78 | 0.177357E+10 |
February | 0.381520E+09 | 0.00 | 0.381520E+09 | 13599847.91 | 0.149510E+10 |
March | 0.512250E+09 | 0.00 | 0.512250E+09 | 0.139613E+09 | 0.122848E+10 |
April | 0.631656E+09 | 2520522.91 | 0.629136E+09 | 0.301773E+09 | 0.857460E+09 |
May | 0.758419E+09 | 32160802.02 | 0.726258E+09 | 0.575016E+09 | 0.537022E+09 |
June | 0.882792E+09 | 75146635.57 | 0.807645E+09 | 0.935327E+09 | 0.329130E+09 |
July | 0.846203E+09 | 54623543.64 | 0.791580E+09 | 0.103799E+10 | 0.232386E+09 |
August | 0.732201E+09 | 11138689.77 | 0.721062E+09 | 0.844281E+09 | 0.312552E+09 |
September | 0.539246E+09 | 112030.34 | 0.539134E+09 | 0.474307E+09 | 0.511417E+09 |
October | 0.416545E+09 | 0.00 | 0.416545E+09 | 0.174708E+09 | 0.885027E+09 |
November | 0.270879E+09 | 0.00 | 0.270879E+09 | 37962949.58 | 0.114881E+10 |
December | 0.259480E+09 | 0.00 | 0.259480E+09 | 1620529.48 | 0.174427E+10 |
Annual Sum or Average | 0.650842E+10 | 0.175702E+09 | 0.633272E+10 | 0.453636E+10 | 0.110552E+11 |
Minimum of Months | 0.259480E+09 | 0.00 | 0.259480E+09 | 163732.78 | 0.232386E+09 |
Maximum of Months | 0.882792E+09 | 75146635.57 | 0.807645E+09 | 0.103799E+10 | 0.177357E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277221E+09 | 0.00 | 0.277221E+09 | 163741.58 | 0.177350E+10 |
February | 0.381506E+09 | 0.00 | 0.381506E+09 | 13599601.17 | 0.149503E+10 |
March | 0.512230E+09 | 0.00 | 0.512230E+09 | 0.139608E+09 | 0.122843E+10 |
April | 0.631632E+09 | 2520430.56 | 0.629112E+09 | 0.301763E+09 | 0.857425E+09 |
May | 0.758390E+09 | 32159623.63 | 0.726231E+09 | 0.574995E+09 | 0.537000E+09 |
June | 0.882758E+09 | 75143882.16 | 0.807614E+09 | 0.935291E+09 | 0.329116E+09 |
July | 0.846171E+09 | 54621542.21 | 0.791550E+09 | 0.103795E+10 | 0.232377E+09 |
August | 0.732173E+09 | 11138281.65 | 0.721035E+09 | 0.844249E+09 | 0.312539E+09 |
September | 0.539225E+09 | 112026.24 | 0.539113E+09 | 0.474289E+09 | 0.511396E+09 |
October | 0.416530E+09 | 0.00 | 0.416530E+09 | 0.174702E+09 | 0.884991E+09 |
November | 0.270868E+09 | 0.00 | 0.270868E+09 | 37961730.84 | 0.114877E+10 |
December | 0.259471E+09 | 0.00 | 0.259471E+09 | 1620500.50 | 0.174420E+10 |
Annual Sum or Average | 0.650818E+10 | 0.175696E+09 | 0.633248E+10 | 0.453619E+10 | 0.110548E+11 |
Minimum of Months | 0.259471E+09 | 0.00 | 0.259471E+09 | 163741.58 | 0.232377E+09 |
Maximum of Months | 0.882758E+09 | 75143882.16 | 0.807614E+09 | 0.103795E+10 | 0.177350E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.563716E+09 | 0.181774E+09 | 0.381943E+09 | 0.206735E+09 | 0.177955E+10 |
February | 0.747097E+09 | 0.224185E+09 | 0.522912E+09 | 0.335171E+09 | 0.150577E+10 |
March | 0.118693E+10 | 0.497078E+09 | 0.689850E+09 | 0.897339E+09 | 0.122130E+10 |
April | 0.152030E+10 | 0.671749E+09 | 0.848548E+09 | 0.139514E+10 | 0.859356E+09 |
May | 0.176005E+10 | 0.778566E+09 | 0.981487E+09 | 0.188649E+10 | 0.588603E+09 |
June | 0.190227E+10 | 0.840712E+09 | 0.106156E+10 | 0.228957E+10 | 0.356331E+09 |
July | 0.188757E+10 | 0.831072E+09 | 0.105650E+10 | 0.244602E+10 | 0.239027E+09 |
August | 0.170468E+10 | 0.715534E+09 | 0.989151E+09 | 0.216018E+10 | 0.314380E+09 |
September | 0.137283E+10 | 0.608936E+09 | 0.763897E+09 | 0.156518E+10 | 0.526597E+09 |
October | 0.962633E+09 | 0.398171E+09 | 0.564462E+09 | 0.833512E+09 | 0.892340E+09 |
November | 0.528409E+09 | 0.169508E+09 | 0.358902E+09 | 0.302726E+09 | 0.116047E+10 |
December | 0.439576E+09 | 90825905.20 | 0.348750E+09 | 0.103641E+09 | 0.176881E+10 |
Annual Sum or Average | 0.145761E+11 | 0.600811E+10 | 0.856796E+10 | 0.144217E+11 | 0.112125E+11 |
Minimum of Months | 0.439576E+09 | 90825905.20 | 0.348750E+09 | 0.103641E+09 | 0.239027E+09 |
Maximum of Months | 0.190227E+10 | 0.840712E+09 | 0.106156E+10 | 0.244602E+10 | 0.177955E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.563716E+09 | 0.181774E+09 | 0.381943E+09 | 0.206735E+09 | 0.177955E+10 |
February | 0.747097E+09 | 0.224185E+09 | 0.522912E+09 | 0.335171E+09 | 0.150577E+10 |
March | 0.118693E+10 | 0.497078E+09 | 0.689850E+09 | 0.897339E+09 | 0.122130E+10 |
April | 0.152030E+10 | 0.671749E+09 | 0.848548E+09 | 0.139514E+10 | 0.859356E+09 |
May | 0.176005E+10 | 0.778566E+09 | 0.981487E+09 | 0.188649E+10 | 0.588603E+09 |
June | 0.190227E+10 | 0.840712E+09 | 0.106156E+10 | 0.228957E+10 | 0.356331E+09 |
July | 0.188757E+10 | 0.831072E+09 | 0.105650E+10 | 0.244602E+10 | 0.239027E+09 |
August | 0.170468E+10 | 0.715534E+09 | 0.989151E+09 | 0.216018E+10 | 0.314380E+09 |
September | 0.137283E+10 | 0.608936E+09 | 0.763897E+09 | 0.156518E+10 | 0.526597E+09 |
October | 0.962633E+09 | 0.398171E+09 | 0.564462E+09 | 0.833512E+09 | 0.892340E+09 |
November | 0.528409E+09 | 0.169508E+09 | 0.358902E+09 | 0.302726E+09 | 0.116047E+10 |
December | 0.439576E+09 | 90825905.20 | 0.348750E+09 | 0.103641E+09 | 0.176881E+10 |
Annual Sum or Average | 0.145761E+11 | 0.600811E+10 | 0.856796E+10 | 0.144217E+11 | 0.112125E+11 |
Minimum of Months | 0.439576E+09 | 90825905.20 | 0.348750E+09 | 0.103641E+09 | 0.239027E+09 |
Maximum of Months | 0.190227E+10 | 0.840712E+09 | 0.106156E+10 | 0.244602E+10 | 0.177955E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.563706E+09 | 0.181770E+09 | 0.381936E+09 | 0.206731E+09 | 0.177951E+10 |
February | 0.747083E+09 | 0.224181E+09 | 0.522902E+09 | 0.335165E+09 | 0.150574E+10 |
March | 0.118691E+10 | 0.497069E+09 | 0.689837E+09 | 0.897323E+09 | 0.122128E+10 |
April | 0.152027E+10 | 0.671737E+09 | 0.848532E+09 | 0.139512E+10 | 0.859340E+09 |
May | 0.176002E+10 | 0.778552E+09 | 0.981469E+09 | 0.188646E+10 | 0.588592E+09 |
June | 0.190224E+10 | 0.840696E+09 | 0.106154E+10 | 0.228953E+10 | 0.356324E+09 |
July | 0.188754E+10 | 0.831057E+09 | 0.105648E+10 | 0.244597E+10 | 0.239023E+09 |
August | 0.170465E+10 | 0.715521E+09 | 0.989133E+09 | 0.216014E+10 | 0.314374E+09 |
September | 0.137281E+10 | 0.608925E+09 | 0.763883E+09 | 0.156515E+10 | 0.526587E+09 |
October | 0.962616E+09 | 0.398164E+09 | 0.564452E+09 | 0.833497E+09 | 0.892323E+09 |
November | 0.528400E+09 | 0.169504E+09 | 0.358895E+09 | 0.302720E+09 | 0.116045E+10 |
December | 0.439568E+09 | 90824245.61 | 0.348744E+09 | 0.103639E+09 | 0.176878E+10 |
Annual Sum or Average | 0.145758E+11 | 0.600800E+10 | 0.856781E+10 | 0.144214E+11 | 0.112123E+11 |
Minimum of Months | 0.439568E+09 | 90824245.61 | 0.348744E+09 | 0.103639E+09 | 0.239023E+09 |
Maximum of Months | 0.190224E+10 | 0.840696E+09 | 0.106154E+10 | 0.244597E+10 | 0.177951E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119210E+10 | 0.695862E+09 | 0.496237E+09 | 0.944335E+09 | 0.146936E+10 |
February | 0.122936E+10 | 0.592785E+09 | 0.636575E+09 | 0.959656E+09 | 0.129663E+10 |
March | 0.166129E+10 | 0.933464E+09 | 0.727824E+09 | 0.159668E+10 | 0.109133E+10 |
April | 0.133143E+10 | 0.532040E+09 | 0.799389E+09 | 0.133274E+10 | 0.841684E+09 |
May | 0.120396E+10 | 0.349678E+09 | 0.854281E+09 | 0.132179E+10 | 0.575128E+09 |
June | 0.113212E+10 | 0.239901E+09 | 0.892224E+09 | 0.139055E+10 | 0.355980E+09 |
July | 0.119424E+10 | 0.289759E+09 | 0.904479E+09 | 0.162150E+10 | 0.247509E+09 |
August | 0.134073E+10 | 0.434694E+09 | 0.906032E+09 | 0.178705E+10 | 0.324236E+09 |
September | 0.150858E+10 | 0.734786E+09 | 0.773790E+09 | 0.185706E+10 | 0.510922E+09 |
October | 0.149160E+10 | 0.852027E+09 | 0.639571E+09 | 0.158131E+10 | 0.811302E+09 |
November | 0.103379E+10 | 0.583609E+09 | 0.450183E+09 | 0.950721E+09 | 0.101526E+10 |
December | 0.996831E+09 | 0.515904E+09 | 0.480927E+09 | 0.740347E+09 | 0.147124E+10 |
Annual Sum or Average | 0.153160E+11 | 0.675451E+10 | 0.856151E+10 | 0.160837E+11 | 0.100106E+11 |
Minimum of Months | 0.996831E+09 | 0.239901E+09 | 0.450183E+09 | 0.740347E+09 | 0.247509E+09 |
Maximum of Months | 0.166129E+10 | 0.933464E+09 | 0.906032E+09 | 0.185706E+10 | 0.147124E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119209E+10 | 0.695856E+09 | 0.496234E+09 | 0.944325E+09 | 0.146936E+10 |
February | 0.122935E+10 | 0.592781E+09 | 0.636571E+09 | 0.959645E+09 | 0.129663E+10 |
March | 0.166128E+10 | 0.933457E+09 | 0.727819E+09 | 0.159666E+10 | 0.109133E+10 |
April | 0.133142E+10 | 0.532036E+09 | 0.799385E+09 | 0.133273E+10 | 0.841684E+09 |
May | 0.120395E+10 | 0.349675E+09 | 0.854277E+09 | 0.132178E+10 | 0.575128E+09 |
June | 0.113212E+10 | 0.239899E+09 | 0.892219E+09 | 0.139054E+10 | 0.355979E+09 |
July | 0.119423E+10 | 0.289757E+09 | 0.904475E+09 | 0.162149E+10 | 0.247509E+09 |
August | 0.134072E+10 | 0.434691E+09 | 0.906027E+09 | 0.178704E+10 | 0.324235E+09 |
September | 0.150857E+10 | 0.734780E+09 | 0.773786E+09 | 0.185704E+10 | 0.510921E+09 |
October | 0.149159E+10 | 0.852021E+09 | 0.639567E+09 | 0.158129E+10 | 0.811301E+09 |
November | 0.103378E+10 | 0.583604E+09 | 0.450180E+09 | 0.950712E+09 | 0.101526E+10 |
December | 0.996824E+09 | 0.515900E+09 | 0.480924E+09 | 0.740339E+09 | 0.147125E+10 |
Annual Sum or Average | 0.153159E+11 | 0.675446E+10 | 0.856146E+10 | 0.160836E+11 | 0.100106E+11 |
Minimum of Months | 0.996824E+09 | 0.239899E+09 | 0.450180E+09 | 0.740339E+09 | 0.247509E+09 |
Maximum of Months | 0.166128E+10 | 0.933457E+09 | 0.906027E+09 | 0.185704E+10 | 0.147125E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119210E+10 | 0.695862E+09 | 0.496237E+09 | 0.944335E+09 | 0.146936E+10 |
February | 0.122936E+10 | 0.592785E+09 | 0.636575E+09 | 0.959656E+09 | 0.129663E+10 |
March | 0.166129E+10 | 0.933464E+09 | 0.727824E+09 | 0.159668E+10 | 0.109133E+10 |
April | 0.133143E+10 | 0.532040E+09 | 0.799389E+09 | 0.133274E+10 | 0.841684E+09 |
May | 0.120396E+10 | 0.349678E+09 | 0.854281E+09 | 0.132179E+10 | 0.575128E+09 |
June | 0.113212E+10 | 0.239901E+09 | 0.892224E+09 | 0.139055E+10 | 0.355980E+09 |
July | 0.119424E+10 | 0.289759E+09 | 0.904479E+09 | 0.162150E+10 | 0.247509E+09 |
August | 0.134073E+10 | 0.434694E+09 | 0.906032E+09 | 0.178705E+10 | 0.324236E+09 |
September | 0.150858E+10 | 0.734786E+09 | 0.773790E+09 | 0.185706E+10 | 0.510922E+09 |
October | 0.149160E+10 | 0.852027E+09 | 0.639571E+09 | 0.158131E+10 | 0.811302E+09 |
November | 0.103379E+10 | 0.583609E+09 | 0.450183E+09 | 0.950721E+09 | 0.101526E+10 |
December | 0.996831E+09 | 0.515904E+09 | 0.480927E+09 | 0.740347E+09 | 0.147124E+10 |
Annual Sum or Average | 0.153160E+11 | 0.675451E+10 | 0.856151E+10 | 0.160837E+11 | 0.100106E+11 |
Minimum of Months | 0.996831E+09 | 0.239901E+09 | 0.450183E+09 | 0.740347E+09 | 0.247509E+09 |
Maximum of Months | 0.166129E+10 | 0.933464E+09 | 0.906032E+09 | 0.185706E+10 | 0.147124E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119209E+10 | 0.695856E+09 | 0.496234E+09 | 0.944325E+09 | 0.146936E+10 |
February | 0.122935E+10 | 0.592781E+09 | 0.636571E+09 | 0.959645E+09 | 0.129663E+10 |
March | 0.166128E+10 | 0.933457E+09 | 0.727819E+09 | 0.159666E+10 | 0.109133E+10 |
April | 0.133142E+10 | 0.532036E+09 | 0.799385E+09 | 0.133273E+10 | 0.841684E+09 |
May | 0.120395E+10 | 0.349675E+09 | 0.854277E+09 | 0.132178E+10 | 0.575128E+09 |
June | 0.113212E+10 | 0.239899E+09 | 0.892219E+09 | 0.139054E+10 | 0.355979E+09 |
July | 0.119423E+10 | 0.289757E+09 | 0.904475E+09 | 0.162149E+10 | 0.247509E+09 |
August | 0.134072E+10 | 0.434691E+09 | 0.906027E+09 | 0.178704E+10 | 0.324235E+09 |
September | 0.150857E+10 | 0.734780E+09 | 0.773786E+09 | 0.185704E+10 | 0.510921E+09 |
October | 0.149159E+10 | 0.852021E+09 | 0.639567E+09 | 0.158129E+10 | 0.811301E+09 |
November | 0.103378E+10 | 0.583604E+09 | 0.450180E+09 | 0.950712E+09 | 0.101526E+10 |
December | 0.996824E+09 | 0.515900E+09 | 0.480924E+09 | 0.740339E+09 | 0.147125E+10 |
Annual Sum or Average | 0.153159E+11 | 0.675446E+10 | 0.856146E+10 | 0.160836E+11 | 0.100106E+11 |
Minimum of Months | 0.996824E+09 | 0.239899E+09 | 0.450180E+09 | 0.740339E+09 | 0.247509E+09 |
Maximum of Months | 0.166128E+10 | 0.933457E+09 | 0.906027E+09 | 0.185704E+10 | 0.147125E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119205E+10 | 0.695831E+09 | 0.496215E+09 | 0.944292E+09 | 0.146930E+10 |
February | 0.122931E+10 | 0.592759E+09 | 0.636548E+09 | 0.959612E+09 | 0.129658E+10 |
March | 0.166121E+10 | 0.933423E+09 | 0.727792E+09 | 0.159661E+10 | 0.109129E+10 |
April | 0.133137E+10 | 0.532017E+09 | 0.799354E+09 | 0.133268E+10 | 0.841650E+09 |
May | 0.120391E+10 | 0.349662E+09 | 0.854244E+09 | 0.132173E+10 | 0.575105E+09 |
June | 0.113208E+10 | 0.239890E+09 | 0.892185E+09 | 0.139049E+10 | 0.355965E+09 |
July | 0.119419E+10 | 0.289746E+09 | 0.904440E+09 | 0.162143E+10 | 0.247499E+09 |
August | 0.134067E+10 | 0.434675E+09 | 0.905993E+09 | 0.178697E+10 | 0.324223E+09 |
September | 0.150851E+10 | 0.734753E+09 | 0.773757E+09 | 0.185697E+10 | 0.510901E+09 |
October | 0.149153E+10 | 0.851990E+09 | 0.639543E+09 | 0.158123E+10 | 0.811269E+09 |
November | 0.103375E+10 | 0.583583E+09 | 0.450163E+09 | 0.950678E+09 | 0.101522E+10 |
December | 0.996787E+09 | 0.515881E+09 | 0.480906E+09 | 0.740313E+09 | 0.147119E+10 |
Annual Sum or Average | 0.153154E+11 | 0.675421E+10 | 0.856114E+10 | 0.160830E+11 | 0.100102E+11 |
Minimum of Months | 0.996787E+09 | 0.239890E+09 | 0.450163E+09 | 0.740313E+09 | 0.247499E+09 |
Maximum of Months | 0.166121E+10 | 0.933423E+09 | 0.905993E+09 | 0.185697E+10 | 0.147119E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.483658E+09 | 0.113544E+09 | 0.370114E+09 | 0.122604E+09 | 0.191663E+10 |
February | 0.708018E+09 | 0.181966E+09 | 0.526052E+09 | 0.274881E+09 | 0.165118E+10 |
March | 0.122859E+10 | 0.526053E+09 | 0.702535E+09 | 0.914548E+09 | 0.138579E+10 |
April | 0.145572E+10 | 0.596902E+09 | 0.858813E+09 | 0.127841E+10 | 0.103704E+10 |
May | 0.177449E+10 | 0.801955E+09 | 0.972535E+09 | 0.189473E+10 | 0.673799E+09 |
June | 0.207191E+10 | 0.974542E+09 | 0.109737E+10 | 0.248857E+10 | 0.443677E+09 |
July | 0.191411E+10 | 0.839213E+09 | 0.107490E+10 | 0.244154E+10 | 0.326810E+09 |
August | 0.173120E+10 | 0.736124E+09 | 0.995079E+09 | 0.216100E+10 | 0.424418E+09 |
September | 0.131568E+10 | 0.568183E+09 | 0.747492E+09 | 0.148378E+10 | 0.604990E+09 |
October | 0.881313E+09 | 0.310449E+09 | 0.570864E+09 | 0.716315E+09 | 0.102254E+10 |
November | 0.505422E+09 | 0.145645E+09 | 0.359777E+09 | 0.257125E+09 | 0.133673E+10 |
December | 0.452761E+09 | 98651580.88 | 0.354109E+09 | 0.106862E+09 | 0.199971E+10 |
Annual Sum or Average | 0.145229E+11 | 0.589323E+10 | 0.862964E+10 | 0.141404E+11 | 0.128233E+11 |
Minimum of Months | 0.452761E+09 | 98651580.88 | 0.354109E+09 | 0.106862E+09 | 0.326810E+09 |
Maximum of Months | 0.207191E+10 | 0.974542E+09 | 0.109737E+10 | 0.248857E+10 | 0.199971E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.483658E+09 | 0.113544E+09 | 0.370114E+09 | 0.122604E+09 | 0.191663E+10 |
February | 0.708018E+09 | 0.181966E+09 | 0.526052E+09 | 0.274881E+09 | 0.165118E+10 |
March | 0.122859E+10 | 0.526053E+09 | 0.702535E+09 | 0.914548E+09 | 0.138579E+10 |
April | 0.145572E+10 | 0.596902E+09 | 0.858813E+09 | 0.127841E+10 | 0.103704E+10 |
May | 0.177449E+10 | 0.801955E+09 | 0.972535E+09 | 0.189473E+10 | 0.673799E+09 |
June | 0.207191E+10 | 0.974542E+09 | 0.109737E+10 | 0.248857E+10 | 0.443677E+09 |
July | 0.191411E+10 | 0.839213E+09 | 0.107490E+10 | 0.244154E+10 | 0.326810E+09 |
August | 0.173120E+10 | 0.736124E+09 | 0.995079E+09 | 0.216100E+10 | 0.424418E+09 |
September | 0.131568E+10 | 0.568183E+09 | 0.747492E+09 | 0.148378E+10 | 0.604990E+09 |
October | 0.881313E+09 | 0.310449E+09 | 0.570864E+09 | 0.716315E+09 | 0.102254E+10 |
November | 0.505422E+09 | 0.145645E+09 | 0.359777E+09 | 0.257125E+09 | 0.133673E+10 |
December | 0.452761E+09 | 98651580.88 | 0.354109E+09 | 0.106862E+09 | 0.199971E+10 |
Annual Sum or Average | 0.145229E+11 | 0.589323E+10 | 0.862964E+10 | 0.141404E+11 | 0.128233E+11 |
Minimum of Months | 0.452761E+09 | 98651580.88 | 0.354109E+09 | 0.106862E+09 | 0.326810E+09 |
Maximum of Months | 0.207191E+10 | 0.974542E+09 | 0.109737E+10 | 0.248857E+10 | 0.199971E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.483650E+09 | 0.113542E+09 | 0.370108E+09 | 0.122602E+09 | 0.191660E+10 |
February | 0.708005E+09 | 0.181963E+09 | 0.526043E+09 | 0.274876E+09 | 0.165115E+10 |
March | 0.122857E+10 | 0.526043E+09 | 0.702522E+09 | 0.914531E+09 | 0.138577E+10 |
April | 0.145569E+10 | 0.596891E+09 | 0.858798E+09 | 0.127838E+10 | 0.103702E+10 |
May | 0.177446E+10 | 0.801940E+09 | 0.972517E+09 | 0.189469E+10 | 0.673787E+09 |
June | 0.207187E+10 | 0.974524E+09 | 0.109735E+10 | 0.248852E+10 | 0.443669E+09 |
July | 0.191408E+10 | 0.839198E+09 | 0.107488E+10 | 0.244149E+10 | 0.326804E+09 |
August | 0.173117E+10 | 0.736111E+09 | 0.995060E+09 | 0.216096E+10 | 0.424411E+09 |
September | 0.131565E+10 | 0.568172E+09 | 0.747479E+09 | 0.148375E+10 | 0.604979E+09 |
October | 0.881297E+09 | 0.310443E+09 | 0.570854E+09 | 0.716302E+09 | 0.102253E+10 |
November | 0.505413E+09 | 0.145642E+09 | 0.359771E+09 | 0.257121E+09 | 0.133671E+10 |
December | 0.452753E+09 | 98649778.30 | 0.354103E+09 | 0.106860E+09 | 0.199967E+10 |
Annual Sum or Average | 0.145226E+11 | 0.589312E+10 | 0.862949E+10 | 0.141401E+11 | 0.128231E+11 |
Minimum of Months | 0.452753E+09 | 98649778.30 | 0.354103E+09 | 0.106860E+09 | 0.326804E+09 |
Maximum of Months | 0.207187E+10 | 0.974524E+09 | 0.109735E+10 | 0.248852E+10 | 0.199967E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138618E+10 | 0.00 | 0.138618E+10 | 18115884.54 | 0.805353E+10 |
February | 0.190763E+10 | 0.00 | 0.190763E+10 | 0.129015E+09 | 0.678925E+10 |
March | 0.256129E+10 | 0.00 | 0.256129E+10 | 0.823205E+09 | 0.548249E+10 |
April | 0.315833E+10 | 12602971.95 | 0.314572E+10 | 0.171129E+10 | 0.377379E+10 |
May | 0.379215E+10 | 0.160809E+09 | 0.363134E+10 | 0.296378E+10 | 0.251242E+10 |
June | 0.441402E+10 | 0.375744E+09 | 0.403828E+10 | 0.470798E+10 | 0.158201E+10 |
July | 0.423108E+10 | 0.273125E+09 | 0.395795E+10 | 0.521001E+10 | 0.114709E+10 |
August | 0.366106E+10 | 55695028.17 | 0.360536E+10 | 0.425847E+10 | 0.152113E+10 |
September | 0.269627E+10 | 560167.59 | 0.269571E+10 | 0.242632E+10 | 0.238104E+10 |
October | 0.208276E+10 | 0.00 | 0.208276E+10 | 0.102095E+10 | 0.389741E+10 |
November | 0.135442E+10 | 0.00 | 0.135442E+10 | 0.287368E+09 | 0.492631E+10 |
December | 0.129743E+10 | 0.00 | 0.129743E+10 | 21919636.77 | 0.769099E+10 |
Annual Sum or Average | 0.325426E+11 | 0.878536E+09 | 0.316641E+11 | 0.235784E+11 | 0.497575E+11 |
Minimum of Months | 0.129743E+10 | 0.00 | 0.129743E+10 | 18115884.54 | 0.114709E+10 |
Maximum of Months | 0.441402E+10 | 0.375744E+09 | 0.403828E+10 | 0.521001E+10 | 0.805353E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169113E+10 | 0.545315E+09 | 0.114582E+10 | 0.657274E+09 | 0.488768E+10 |
February | 0.224127E+10 | 0.672549E+09 | 0.156872E+10 | 0.106748E+10 | 0.417656E+10 |
March | 0.356075E+10 | 0.149122E+10 | 0.206953E+10 | 0.276669E+10 | 0.337157E+10 |
April | 0.456084E+10 | 0.201523E+10 | 0.254562E+10 | 0.424689E+10 | 0.238482E+10 |
May | 0.528011E+10 | 0.233567E+10 | 0.294443E+10 | 0.566316E+10 | 0.167601E+10 |
June | 0.570676E+10 | 0.252211E+10 | 0.318465E+10 | 0.683833E+10 | 0.105200E+10 |
July | 0.566266E+10 | 0.249319E+10 | 0.316947E+10 | 0.728617E+10 | 0.757769E+09 |
August | 0.511400E+10 | 0.214658E+10 | 0.296742E+10 | 0.643725E+10 | 0.988321E+09 |
September | 0.411846E+10 | 0.182679E+10 | 0.229167E+10 | 0.469900E+10 | 0.149822E+10 |
October | 0.288787E+10 | 0.119450E+10 | 0.169337E+10 | 0.257749E+10 | 0.243556E+10 |
November | 0.158521E+10 | 0.508518E+09 | 0.107669E+10 | 0.976208E+09 | 0.312822E+10 |
December | 0.131871E+10 | 0.272475E+09 | 0.104624E+10 | 0.343806E+09 | 0.482108E+10 |
Annual Sum or Average | 0.437278E+11 | 0.180241E+11 | 0.257036E+11 | 0.435598E+11 | 0.311778E+11 |
Minimum of Months | 0.131871E+10 | 0.272475E+09 | 0.104624E+10 | 0.343806E+09 | 0.757769E+09 |
Maximum of Months | 0.570676E+10 | 0.252211E+10 | 0.318465E+10 | 0.728617E+10 | 0.488768E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.596060E+10 | 0.347938E+10 | 0.248122E+10 | 0.476228E+10 | 0.696919E+10 |
February | 0.614692E+10 | 0.296399E+10 | 0.318293E+10 | 0.483614E+10 | 0.617594E+10 |
March | 0.830658E+10 | 0.466742E+10 | 0.363917E+10 | 0.799725E+10 | 0.518507E+10 |
April | 0.665725E+10 | 0.266026E+10 | 0.399699E+10 | 0.670033E+10 | 0.396123E+10 |
May | 0.601987E+10 | 0.174842E+10 | 0.427145E+10 | 0.659222E+10 | 0.277304E+10 |
June | 0.566069E+10 | 0.119953E+10 | 0.446116E+10 | 0.693738E+10 | 0.172684E+10 |
July | 0.597126E+10 | 0.144882E+10 | 0.452244E+10 | 0.808008E+10 | 0.124615E+10 |
August | 0.670373E+10 | 0.217352E+10 | 0.453021E+10 | 0.890620E+10 | 0.162526E+10 |
September | 0.754301E+10 | 0.367400E+10 | 0.386900E+10 | 0.924221E+10 | 0.248641E+10 |
October | 0.745813E+10 | 0.426023E+10 | 0.319790E+10 | 0.790659E+10 | 0.385740E+10 |
November | 0.516905E+10 | 0.291810E+10 | 0.225095E+10 | 0.479922E+10 | 0.474937E+10 |
December | 0.498425E+10 | 0.257957E+10 | 0.240467E+10 | 0.376808E+10 | 0.686760E+10 |
Annual Sum or Average | 0.765813E+11 | 0.337732E+11 | 0.428081E+11 | 0.805280E+11 | 0.476235E+11 |
Minimum of Months | 0.498425E+10 | 0.119953E+10 | 0.225095E+10 | 0.376808E+10 | 0.124615E+10 |
Maximum of Months | 0.830658E+10 | 0.466742E+10 | 0.453021E+10 | 0.924221E+10 | 0.696919E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.145096E+10 | 0.340629E+09 | 0.111033E+10 | 0.399340E+09 | 0.516616E+10 |
February | 0.212403E+10 | 0.545892E+09 | 0.157814E+10 | 0.906780E+09 | 0.439898E+10 |
March | 0.368573E+10 | 0.157814E+10 | 0.210758E+10 | 0.290919E+10 | 0.355601E+10 |
April | 0.436710E+10 | 0.179069E+10 | 0.257641E+10 | 0.405022E+10 | 0.258484E+10 |
May | 0.532342E+10 | 0.240584E+10 | 0.291758E+10 | 0.575629E+10 | 0.184818E+10 |
June | 0.621567E+10 | 0.292360E+10 | 0.329208E+10 | 0.751808E+10 | 0.121646E+10 |
July | 0.574228E+10 | 0.251761E+10 | 0.322467E+10 | 0.739735E+10 | 0.898874E+09 |
August | 0.519356E+10 | 0.220835E+10 | 0.298521E+10 | 0.657996E+10 | 0.112757E+10 |
September | 0.394699E+10 | 0.170453E+10 | 0.224245E+10 | 0.451778E+10 | 0.163393E+10 |
October | 0.264391E+10 | 0.931337E+09 | 0.171258E+10 | 0.230473E+10 | 0.259215E+10 |
November | 0.151625E+10 | 0.436929E+09 | 0.107932E+10 | 0.891145E+09 | 0.326953E+10 |
December | 0.135827E+10 | 0.295952E+09 | 0.106232E+10 | 0.382110E+09 | 0.501210E+10 |
Annual Sum or Average | 0.435682E+11 | 0.176795E+11 | 0.258887E+11 | 0.436130E+11 | 0.333048E+11 |
Minimum of Months | 0.135827E+10 | 0.295952E+09 | 0.106232E+10 | 0.382110E+09 | 0.898874E+09 |
Maximum of Months | 0.621567E+10 | 0.292360E+10 | 0.329208E+10 | 0.751808E+10 | 0.516616E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138618E+10 | 0.00 | 0.138618E+10 | 30711998.00 | 0.776520E+10 |
February | 0.190763E+10 | 0.00 | 0.190763E+10 | 0.153215E+09 | 0.653800E+10 |
March | 0.256129E+10 | 0.00 | 0.256129E+10 | 0.890247E+09 | 0.515123E+10 |
April | 0.315833E+10 | 12602971.95 | 0.314572E+10 | 0.182791E+10 | 0.348779E+10 |
May | 0.379215E+10 | 0.160809E+09 | 0.363134E+10 | 0.305711E+10 | 0.235932E+10 |
June | 0.441402E+10 | 0.375744E+09 | 0.403828E+10 | 0.471331E+10 | 0.154501E+10 |
July | 0.423108E+10 | 0.273125E+09 | 0.395795E+10 | 0.518025E+10 | 0.114366E+10 |
August | 0.366106E+10 | 55695028.17 | 0.360536E+10 | 0.424850E+10 | 0.149249E+10 |
September | 0.269627E+10 | 560167.59 | 0.269571E+10 | 0.248336E+10 | 0.222796E+10 |
October | 0.208276E+10 | 0.00 | 0.208276E+10 | 0.114665E+10 | 0.350062E+10 |
November | 0.135442E+10 | 0.00 | 0.135442E+10 | 0.355447E+09 | 0.447398E+10 |
December | 0.129743E+10 | 0.00 | 0.129743E+10 | 32351778.45 | 0.733714E+10 |
Annual Sum or Average | 0.325426E+11 | 0.878536E+09 | 0.316641E+11 | 0.241191E+11 | 0.470224E+11 |
Minimum of Months | 0.129743E+10 | 0.00 | 0.129743E+10 | 30711998.00 | 0.114366E+10 |
Maximum of Months | 0.441402E+10 | 0.375744E+09 | 0.403828E+10 | 0.518025E+10 | 0.776520E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169113E+10 | 0.545315E+09 | 0.114582E+10 | 0.679208E+09 | 0.471122E+10 |
February | 0.224127E+10 | 0.672549E+09 | 0.156872E+10 | 0.109887E+10 | 0.402869E+10 |
March | 0.356075E+10 | 0.149122E+10 | 0.206953E+10 | 0.282727E+10 | 0.317370E+10 |
April | 0.456084E+10 | 0.201523E+10 | 0.254562E+10 | 0.431059E+10 | 0.223909E+10 |
May | 0.528011E+10 | 0.233567E+10 | 0.294443E+10 | 0.568250E+10 | 0.160826E+10 |
June | 0.570676E+10 | 0.252211E+10 | 0.318465E+10 | 0.681554E+10 | 0.104428E+10 |
July | 0.566266E+10 | 0.249319E+10 | 0.316947E+10 | 0.724908E+10 | 0.767535E+09 |
August | 0.511400E+10 | 0.214658E+10 | 0.296742E+10 | 0.641290E+10 | 0.986742E+09 |
September | 0.411846E+10 | 0.182679E+10 | 0.229167E+10 | 0.471283E+10 | 0.143843E+10 |
October | 0.288787E+10 | 0.119450E+10 | 0.169337E+10 | 0.266064E+10 | 0.222527E+10 |
November | 0.158521E+10 | 0.508518E+09 | 0.107669E+10 | 0.103449E+10 | 0.285957E+10 |
December | 0.131871E+10 | 0.272475E+09 | 0.104624E+10 | 0.363022E+09 | 0.460496E+10 |
Annual Sum or Average | 0.437278E+11 | 0.180241E+11 | 0.257036E+11 | 0.438469E+11 | 0.296877E+11 |
Minimum of Months | 0.131871E+10 | 0.272475E+09 | 0.104624E+10 | 0.363022E+09 | 0.767535E+09 |
Maximum of Months | 0.570676E+10 | 0.252211E+10 | 0.318465E+10 | 0.724908E+10 | 0.471122E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.596060E+10 | 0.347938E+10 | 0.248122E+10 | 0.482931E+10 | 0.667211E+10 |
February | 0.614692E+10 | 0.296399E+10 | 0.318293E+10 | 0.490101E+10 | 0.592394E+10 |
March | 0.830658E+10 | 0.466742E+10 | 0.363917E+10 | 0.810384E+10 | 0.484948E+10 |
April | 0.665725E+10 | 0.266026E+10 | 0.399699E+10 | 0.679037E+10 | 0.369934E+10 |
May | 0.601987E+10 | 0.174842E+10 | 0.427145E+10 | 0.663156E+10 | 0.263441E+10 |
June | 0.566069E+10 | 0.119953E+10 | 0.446116E+10 | 0.691808E+10 | 0.169181E+10 |
July | 0.597126E+10 | 0.144882E+10 | 0.452244E+10 | 0.803675E+10 | 0.124640E+10 |
August | 0.670373E+10 | 0.217352E+10 | 0.453021E+10 | 0.887728E+10 | 0.160760E+10 |
September | 0.754301E+10 | 0.367400E+10 | 0.386900E+10 | 0.926174E+10 | 0.237408E+10 |
October | 0.745813E+10 | 0.426023E+10 | 0.319790E+10 | 0.802847E+10 | 0.351766E+10 |
November | 0.516905E+10 | 0.291810E+10 | 0.225095E+10 | 0.491047E+10 | 0.432835E+10 |
December | 0.498425E+10 | 0.257957E+10 | 0.240467E+10 | 0.384062E+10 | 0.652303E+10 |
Annual Sum or Average | 0.765813E+11 | 0.337732E+11 | 0.428081E+11 | 0.811295E+11 | 0.450682E+11 |
Minimum of Months | 0.498425E+10 | 0.119953E+10 | 0.225095E+10 | 0.384062E+10 | 0.124640E+10 |
Maximum of Months | 0.830658E+10 | 0.466742E+10 | 0.453021E+10 | 0.926174E+10 | 0.667211E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.145096E+10 | 0.340629E+09 | 0.111033E+10 | 0.415222E+09 | 0.497877E+10 |
February | 0.212403E+10 | 0.545892E+09 | 0.157814E+10 | 0.925441E+09 | 0.425108E+10 |
March | 0.368573E+10 | 0.157814E+10 | 0.210758E+10 | 0.294980E+10 | 0.335986E+10 |
April | 0.436710E+10 | 0.179069E+10 | 0.257641E+10 | 0.409460E+10 | 0.243243E+10 |
May | 0.532342E+10 | 0.240584E+10 | 0.291758E+10 | 0.577713E+10 | 0.176835E+10 |
June | 0.621567E+10 | 0.292360E+10 | 0.329208E+10 | 0.749979E+10 | 0.119621E+10 |
July | 0.574228E+10 | 0.251761E+10 | 0.322467E+10 | 0.736743E+10 | 0.897653E+09 |
August | 0.519356E+10 | 0.220835E+10 | 0.298521E+10 | 0.656361E+10 | 0.111658E+10 |
September | 0.394699E+10 | 0.170453E+10 | 0.224245E+10 | 0.453538E+10 | 0.156386E+10 |
October | 0.264391E+10 | 0.931337E+09 | 0.171258E+10 | 0.236045E+10 | 0.239471E+10 |
November | 0.151625E+10 | 0.436929E+09 | 0.107932E+10 | 0.930991E+09 | 0.303004E+10 |
December | 0.135827E+10 | 0.295952E+09 | 0.106232E+10 | 0.397262E+09 | 0.480143E+10 |
Annual Sum or Average | 0.435682E+11 | 0.176795E+11 | 0.258887E+11 | 0.438171E+11 | 0.317910E+11 |
Minimum of Months | 0.135827E+10 | 0.295952E+09 | 0.106232E+10 | 0.397262E+09 | 0.897653E+09 |
Maximum of Months | 0.621567E+10 | 0.292360E+10 | 0.329208E+10 | 0.749979E+10 | 0.497877E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.31 | 3310.85 | 517.53 | 0.00 | 517.53 | 0.00 | 0.00 |
February | 28.11 | 3090.03 | 788.52 | 0.00 | 788.52 | 0.00 | 0.00 |
March | 260.63 | 2293.30 | 956.26 | 0.00 | 956.26 | 0.00 | 0.00 |
April | 582.13 | 1654.04 | 1218.47 | 4.86 | 1213.61 | 0.00 | 0.00 |
May | 1073.43 | 1002.50 | 1415.80 | 60.04 | 1355.76 | 0.00 | 0.00 |
June | 1804.25 | 634.89 | 1702.91 | 144.96 | 1557.95 | 0.00 | 0.00 |
July | 1937.70 | 433.81 | 1579.67 | 101.97 | 1477.70 | 0.00 | 0.00 |
August | 1576.09 | 583.46 | 1366.86 | 20.79 | 1346.06 | 0.00 | 0.00 |
September | 914.94 | 986.52 | 1040.21 | 0.22 | 1039.99 | 0.00 | 0.00 |
October | 326.14 | 1652.14 | 777.60 | 0.00 | 777.60 | 0.00 | 0.00 |
November | 73.23 | 2216.06 | 522.53 | 0.00 | 522.53 | 0.00 | 0.00 |
December | 3.03 | 3256.16 | 484.39 | 0.00 | 484.39 | 0.00 | 0.00 |
Annual Sum or Average | 719.23 | 1752.78 | 1031.90 | 27.86 | 1004.04 | 0.00 | 0.00 |
Minimum of Months | 0.31 | 433.81 | 484.39 | 0.00 | 484.39 | 0.00 | 0.00 |
Maximum of Months | 1937.70 | 3310.85 | 1702.91 | 144.96 | 1557.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 231.56 | 1993.21 | 631.40 | 203.60 | 427.80 | 0.00 | 0.00 |
February | 415.64 | 1867.26 | 926.45 | 278.01 | 648.45 | 0.00 | 0.00 |
March | 1005.08 | 1367.94 | 1329.44 | 556.76 | 772.68 | 0.00 | 0.00 |
April | 1614.74 | 994.62 | 1759.59 | 777.48 | 982.11 | 0.00 | 0.00 |
May | 2112.99 | 659.27 | 1971.37 | 872.04 | 1099.33 | 0.00 | 0.00 |
June | 2649.95 | 412.42 | 2201.69 | 973.04 | 1228.65 | 0.00 | 0.00 |
July | 2739.70 | 267.73 | 2114.20 | 930.85 | 1183.35 | 0.00 | 0.00 |
August | 2419.54 | 352.13 | 1909.36 | 801.44 | 1107.91 | 0.00 | 0.00 |
September | 1811.54 | 609.48 | 1588.92 | 704.78 | 884.13 | 0.00 | 0.00 |
October | 933.59 | 999.48 | 1078.21 | 445.98 | 632.23 | 0.00 | 0.00 |
November | 350.37 | 1343.13 | 611.58 | 196.19 | 415.39 | 0.00 | 0.00 |
December | 116.08 | 1981.18 | 492.35 | 101.73 | 390.62 | 0.00 | 0.00 |
Annual Sum or Average | 1371.92 | 1066.63 | 1386.60 | 571.54 | 815.06 | 0.00 | 0.00 |
Minimum of Months | 116.08 | 267.73 | 492.35 | 101.73 | 390.62 | 0.00 | 0.00 |
Maximum of Months | 2739.70 | 1993.21 | 2201.69 | 973.04 | 1228.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1762.85 | 2742.95 | 2225.37 | 1299.01 | 926.36 | 0.00 | 0.00 |
February | 1983.39 | 2679.86 | 2540.81 | 1225.15 | 1315.66 | 0.00 | 0.00 |
March | 2980.62 | 2037.26 | 3101.23 | 1742.56 | 1358.68 | 0.00 | 0.00 |
April | 2570.85 | 1623.61 | 2568.31 | 1026.30 | 1542.01 | 0.00 | 0.00 |
May | 2467.46 | 1073.63 | 2247.51 | 652.77 | 1594.74 | 0.00 | 0.00 |
June | 2682.36 | 686.68 | 2183.86 | 462.77 | 1721.09 | 0.00 | 0.00 |
July | 3026.96 | 462.04 | 2229.36 | 540.91 | 1688.45 | 0.00 | 0.00 |
August | 3336.00 | 605.27 | 2502.82 | 811.47 | 1691.35 | 0.00 | 0.00 |
September | 3582.24 | 985.57 | 2910.03 | 1417.39 | 1492.64 | 0.00 | 0.00 |
October | 2951.92 | 1514.51 | 2784.46 | 1590.53 | 1193.93 | 0.00 | 0.00 |
November | 1833.93 | 1958.43 | 1994.17 | 1125.77 | 868.40 | 0.00 | 0.00 |
December | 1382.05 | 2746.48 | 1860.85 | 963.07 | 897.78 | 0.00 | 0.00 |
Annual Sum or Average | 2550.03 | 1587.15 | 2428.31 | 1070.91 | 1357.40 | 0.00 | 0.00 |
Minimum of Months | 1382.05 | 462.04 | 1860.85 | 462.77 | 868.40 | 0.00 | 0.00 |
Maximum of Months | 3582.24 | 2746.48 | 3101.23 | 1742.56 | 1721.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 137.32 | 2146.75 | 541.73 | 127.18 | 414.55 | 0.00 | 0.00 |
February | 340.87 | 2047.58 | 877.99 | 225.65 | 652.34 | 0.00 | 0.00 |
March | 1024.35 | 1552.18 | 1376.10 | 589.21 | 786.88 | 0.00 | 0.00 |
April | 1479.63 | 1200.27 | 1684.85 | 690.85 | 993.99 | 0.00 | 0.00 |
May | 2122.22 | 754.70 | 1987.54 | 898.24 | 1089.30 | 0.00 | 0.00 |
June | 2880.27 | 513.51 | 2398.03 | 1127.94 | 1270.10 | 0.00 | 0.00 |
July | 2734.68 | 366.05 | 2143.93 | 939.97 | 1203.96 | 0.00 | 0.00 |
August | 2420.46 | 475.38 | 1939.06 | 824.51 | 1114.55 | 0.00 | 0.00 |
September | 1717.32 | 700.22 | 1522.76 | 657.61 | 865.15 | 0.00 | 0.00 |
October | 802.32 | 1145.32 | 987.13 | 347.72 | 639.40 | 0.00 | 0.00 |
November | 297.60 | 1547.13 | 584.98 | 168.57 | 416.41 | 0.00 | 0.00 |
December | 119.69 | 2239.80 | 507.12 | 110.50 | 396.63 | 0.00 | 0.00 |
Annual Sum or Average | 1345.15 | 1219.87 | 1381.54 | 560.62 | 820.93 | 0.00 | 0.00 |
Minimum of Months | 119.69 | 366.05 | 507.12 | 110.50 | 396.63 | 0.00 | 0.00 |
Maximum of Months | 2880.27 | 2239.80 | 2398.03 | 1127.94 | 1270.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.76 | 3006.85 | 517.54 | 0.00 | 517.54 | 0.00 | 0.00 |
February | 53.33 | 2806.40 | 788.54 | 0.00 | 788.54 | 0.00 | 0.00 |
March | 307.35 | 2046.93 | 956.27 | 0.00 | 956.27 | 0.00 | 0.00 |
April | 660.22 | 1455.94 | 1218.49 | 4.86 | 1213.63 | 0.00 | 0.00 |
May | 1106.55 | 938.03 | 1415.83 | 60.04 | 1355.79 | 0.00 | 0.00 |
June | 1816.35 | 610.34 | 1702.94 | 144.96 | 1557.98 | 0.00 | 0.00 |
July | 1945.19 | 428.28 | 1579.70 | 101.97 | 1477.73 | 0.00 | 0.00 |
August | 1589.93 | 567.92 | 1366.88 | 20.79 | 1346.09 | 0.00 | 0.00 |
September | 936.08 | 918.61 | 1040.23 | 0.22 | 1040.01 | 0.00 | 0.00 |
October | 381.18 | 1455.13 | 777.61 | 0.00 | 777.61 | 0.00 | 0.00 |
November | 110.87 | 1900.58 | 522.54 | 0.00 | 522.54 | 0.00 | 0.00 |
December | 8.18 | 2871.49 | 484.40 | 0.00 | 484.40 | 0.00 | 0.00 |
Annual Sum or Average | 747.67 | 1577.80 | 1031.92 | 27.86 | 1004.06 | 0.00 | 0.00 |
Minimum of Months | 6.76 | 428.28 | 484.40 | 0.00 | 484.40 | 0.00 | 0.00 |
Maximum of Months | 1945.19 | 3006.85 | 1702.94 | 144.96 | 1557.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 245.40 | 1824.85 | 631.40 | 203.60 | 427.80 | 0.00 | 0.00 |
February | 441.26 | 1726.42 | 926.45 | 278.00 | 648.45 | 0.00 | 0.00 |
March | 1032.96 | 1258.80 | 1329.43 | 556.76 | 772.67 | 0.00 | 0.00 |
April | 1638.46 | 920.07 | 1759.59 | 777.48 | 982.11 | 0.00 | 0.00 |
May | 2114.38 | 625.75 | 1971.37 | 872.04 | 1099.33 | 0.00 | 0.00 |
June | 2638.24 | 405.86 | 2201.68 | 973.04 | 1228.65 | 0.00 | 0.00 |
July | 2720.35 | 282.92 | 2114.19 | 930.85 | 1183.34 | 0.00 | 0.00 |
August | 2403.39 | 369.00 | 1909.35 | 801.44 | 1107.91 | 0.00 | 0.00 |
September | 1812.89 | 578.02 | 1588.91 | 704.78 | 884.13 | 0.00 | 0.00 |
October | 962.32 | 909.33 | 1078.21 | 445.98 | 632.23 | 0.00 | 0.00 |
November | 376.62 | 1206.88 | 611.58 | 196.19 | 415.39 | 0.00 | 0.00 |
December | 128.36 | 1799.98 | 492.35 | 101.73 | 390.62 | 0.00 | 0.00 |
Annual Sum or Average | 1381.27 | 988.64 | 1386.60 | 571.54 | 815.06 | 0.00 | 0.00 |
Minimum of Months | 128.36 | 282.92 | 492.35 | 101.73 | 390.62 | 0.00 | 0.00 |
Maximum of Months | 2720.35 | 1824.85 | 2201.68 | 973.04 | 1228.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1778.03 | 2602.00 | 2225.43 | 1299.05 | 926.38 | 0.00 | 0.00 |
February | 1999.07 | 2552.89 | 2540.89 | 1225.19 | 1315.69 | 0.00 | 0.00 |
March | 2985.83 | 1935.88 | 3101.32 | 1742.61 | 1358.71 | 0.00 | 0.00 |
April | 2585.00 | 1528.25 | 2568.38 | 1026.33 | 1542.05 | 0.00 | 0.00 |
May | 2461.25 | 1035.33 | 2247.56 | 652.79 | 1594.78 | 0.00 | 0.00 |
June | 2676.46 | 666.22 | 2183.91 | 462.78 | 1721.13 | 0.00 | 0.00 |
July | 3016.76 | 465.26 | 2229.41 | 540.93 | 1688.49 | 0.00 | 0.00 |
August | 3325.20 | 606.80 | 2502.89 | 811.50 | 1691.39 | 0.00 | 0.00 |
September | 3565.67 | 959.26 | 2910.11 | 1417.44 | 1492.67 | 0.00 | 0.00 |
October | 2951.98 | 1440.19 | 2784.54 | 1590.59 | 1193.96 | 0.00 | 0.00 |
November | 1851.55 | 1832.32 | 1994.23 | 1125.81 | 868.42 | 0.00 | 0.00 |
December | 1406.84 | 2564.07 | 1860.90 | 963.10 | 897.80 | 0.00 | 0.00 |
Annual Sum or Average | 2553.53 | 1510.13 | 2428.38 | 1070.94 | 1357.44 | 0.00 | 0.00 |
Minimum of Months | 1406.84 | 465.26 | 1860.90 | 462.78 | 868.42 | 0.00 | 0.00 |
Maximum of Months | 3565.67 | 2602.00 | 3101.32 | 1742.61 | 1721.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 149.10 | 1928.82 | 541.73 | 127.18 | 414.55 | 0.00 | 0.00 |
February | 374.83 | 1818.36 | 877.99 | 225.65 | 652.34 | 0.00 | 0.00 |
March | 1086.17 | 1327.66 | 1376.09 | 589.21 | 786.88 | 0.00 | 0.00 |
April | 1562.58 | 997.24 | 1684.84 | 690.85 | 993.99 | 0.00 | 0.00 |
May | 2149.15 | 690.03 | 1987.54 | 898.24 | 1089.30 | 0.00 | 0.00 |
June | 2900.49 | 469.31 | 2398.02 | 1127.93 | 1270.09 | 0.00 | 0.00 |
July | 2761.85 | 335.60 | 2143.92 | 939.97 | 1203.95 | 0.00 | 0.00 |
August | 2456.67 | 420.99 | 1939.05 | 824.50 | 1114.55 | 0.00 | 0.00 |
September | 1742.97 | 630.38 | 1522.76 | 657.61 | 865.14 | 0.00 | 0.00 |
October | 860.49 | 967.80 | 987.12 | 347.72 | 639.40 | 0.00 | 0.00 |
November | 343.81 | 1261.39 | 584.97 | 168.57 | 416.40 | 0.00 | 0.00 |
December | 142.66 | 1871.30 | 507.12 | 110.50 | 396.62 | 0.00 | 0.00 |
Annual Sum or Average | 1382.96 | 1056.09 | 1381.54 | 560.61 | 820.92 | 0.00 | 0.00 |
Minimum of Months | 142.66 | 335.60 | 507.12 | 110.50 | 396.62 | 0.00 | 0.00 |
Maximum of Months | 2900.49 | 1928.82 | 2398.02 | 1127.93 | 1270.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.47 | 2899.20 | 517.54 | 0.00 | 517.54 | 0.00 | 0.00 |
February | 63.33 | 2702.54 | 788.54 | 0.00 | 788.54 | 0.00 | 0.00 |
March | 332.38 | 1923.25 | 956.27 | 0.00 | 956.27 | 0.00 | 0.00 |
April | 705.21 | 1345.60 | 1218.49 | 4.86 | 1213.63 | 0.00 | 0.00 |
May | 1141.39 | 880.87 | 1415.83 | 60.04 | 1355.79 | 0.00 | 0.00 |
June | 1818.41 | 596.07 | 1702.94 | 144.96 | 1557.98 | 0.00 | 0.00 |
July | 1934.08 | 427.00 | 1579.70 | 101.97 | 1477.73 | 0.00 | 0.00 |
August | 1586.21 | 557.23 | 1366.88 | 20.79 | 1346.09 | 0.00 | 0.00 |
September | 958.09 | 859.55 | 1040.23 | 0.22 | 1040.01 | 0.00 | 0.00 |
October | 428.11 | 1306.98 | 777.61 | 0.00 | 777.61 | 0.00 | 0.00 |
November | 137.13 | 1726.07 | 522.54 | 0.00 | 522.54 | 0.00 | 0.00 |
December | 12.08 | 2739.37 | 484.40 | 0.00 | 484.40 | 0.00 | 0.00 |
Annual Sum or Average | 764.81 | 1491.07 | 1031.92 | 27.86 | 1004.06 | 0.00 | 0.00 |
Minimum of Months | 11.47 | 427.00 | 484.40 | 0.00 | 484.40 | 0.00 | 0.00 |
Maximum of Months | 1934.08 | 2899.20 | 1702.94 | 144.96 | 1557.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 253.59 | 1758.97 | 631.40 | 203.60 | 427.80 | 0.00 | 0.00 |
February | 454.23 | 1665.30 | 926.45 | 278.00 | 648.45 | 0.00 | 0.00 |
March | 1055.58 | 1184.92 | 1329.43 | 556.76 | 772.67 | 0.00 | 0.00 |
April | 1663.03 | 863.85 | 1759.59 | 777.48 | 982.11 | 0.00 | 0.00 |
May | 2121.60 | 600.45 | 1971.37 | 872.04 | 1099.33 | 0.00 | 0.00 |
June | 2629.45 | 402.89 | 2201.68 | 973.04 | 1228.65 | 0.00 | 0.00 |
July | 2706.50 | 286.56 | 2114.19 | 930.85 | 1183.34 | 0.00 | 0.00 |
August | 2394.30 | 368.41 | 1909.35 | 801.44 | 1107.91 | 0.00 | 0.00 |
September | 1818.22 | 554.95 | 1588.91 | 704.78 | 884.13 | 0.00 | 0.00 |
October | 993.37 | 830.82 | 1078.21 | 445.98 | 632.23 | 0.00 | 0.00 |
November | 399.11 | 1103.23 | 611.58 | 196.19 | 415.39 | 0.00 | 0.00 |
December | 135.54 | 1719.30 | 492.35 | 101.73 | 390.62 | 0.00 | 0.00 |
Annual Sum or Average | 1390.38 | 941.39 | 1386.60 | 571.54 | 815.06 | 0.00 | 0.00 |
Minimum of Months | 135.54 | 286.56 | 492.35 | 101.73 | 390.62 | 0.00 | 0.00 |
Maximum of Months | 2706.50 | 1758.97 | 2201.68 | 973.04 | 1228.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1803.06 | 2491.08 | 2225.43 | 1299.05 | 926.38 | 0.00 | 0.00 |
February | 2025.88 | 2448.72 | 2540.89 | 1225.19 | 1315.69 | 0.00 | 0.00 |
March | 3025.63 | 1810.59 | 3101.32 | 1742.61 | 1358.71 | 0.00 | 0.00 |
April | 2619.74 | 1427.21 | 2568.38 | 1026.33 | 1542.05 | 0.00 | 0.00 |
May | 2475.94 | 983.57 | 2247.56 | 652.79 | 1594.78 | 0.00 | 0.00 |
June | 2669.01 | 652.71 | 2183.91 | 462.78 | 1721.13 | 0.00 | 0.00 |
July | 3000.58 | 465.35 | 2229.41 | 540.93 | 1688.49 | 0.00 | 0.00 |
August | 3314.40 | 600.21 | 2502.89 | 811.50 | 1691.39 | 0.00 | 0.00 |
September | 3573.20 | 915.93 | 2910.11 | 1417.44 | 1492.67 | 0.00 | 0.00 |
October | 2997.49 | 1313.34 | 2784.54 | 1590.59 | 1193.96 | 0.00 | 0.00 |
November | 1894.47 | 1669.89 | 1994.23 | 1125.81 | 868.42 | 0.00 | 0.00 |
December | 1433.92 | 2435.42 | 1860.90 | 963.10 | 897.80 | 0.00 | 0.00 |
Annual Sum or Average | 2572.60 | 1429.10 | 2428.38 | 1070.94 | 1357.44 | 0.00 | 0.00 |
Minimum of Months | 1433.92 | 465.35 | 1860.90 | 462.78 | 868.42 | 0.00 | 0.00 |
Maximum of Months | 3573.20 | 2491.08 | 3101.32 | 1742.61 | 1721.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 155.03 | 1858.86 | 541.73 | 127.18 | 414.55 | 0.00 | 0.00 |
February | 382.54 | 1757.23 | 877.99 | 225.65 | 652.34 | 0.00 | 0.00 |
March | 1101.33 | 1254.43 | 1376.09 | 589.21 | 786.88 | 0.00 | 0.00 |
April | 1579.71 | 938.44 | 1684.84 | 690.85 | 993.99 | 0.00 | 0.00 |
May | 2156.93 | 660.22 | 1987.54 | 898.24 | 1089.30 | 0.00 | 0.00 |
June | 2893.44 | 461.50 | 2398.02 | 1127.93 | 1270.09 | 0.00 | 0.00 |
July | 2750.68 | 335.15 | 2143.92 | 939.97 | 1203.95 | 0.00 | 0.00 |
August | 2450.57 | 416.88 | 1939.05 | 824.50 | 1114.55 | 0.00 | 0.00 |
September | 1749.76 | 603.34 | 1522.76 | 657.61 | 865.14 | 0.00 | 0.00 |
October | 881.29 | 894.08 | 987.12 | 347.72 | 639.40 | 0.00 | 0.00 |
November | 359.18 | 1169.00 | 584.97 | 168.57 | 416.40 | 0.00 | 0.00 |
December | 148.32 | 1792.65 | 507.12 | 110.50 | 396.62 | 0.00 | 0.00 |
Annual Sum or Average | 1389.43 | 1008.09 | 1381.54 | 560.61 | 820.92 | 0.00 | 0.00 |
Minimum of Months | 148.32 | 335.15 | 507.12 | 110.50 | 396.62 | 0.00 | 0.00 |
Maximum of Months | 2893.44 | 1858.86 | 2398.02 | 1127.93 | 1270.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 818795.90 | 0.886778E+10 | 0.138615E+10 | 0.00 | 0.138615E+10 | 0.00 | 0.00 |
February | 68001404.04 | 0.747541E+10 | 0.190759E+10 | 0.00 | 0.190759E+10 | 0.00 | 0.00 |
March | 0.698067E+09 | 0.614236E+10 | 0.256124E+10 | 0.00 | 0.256124E+10 | 0.00 | 0.00 |
April | 0.150887E+10 | 0.428726E+10 | 0.315827E+10 | 12602596.10 | 0.314567E+10 | 0.00 | 0.00 |
May | 0.287508E+10 | 0.268509E+10 | 0.379208E+10 | 0.160804E+09 | 0.363128E+10 | 0.00 | 0.00 |
June | 0.467662E+10 | 0.164564E+10 | 0.441394E+10 | 0.375733E+09 | 0.403821E+10 | 0.00 | 0.00 |
July | 0.518993E+10 | 0.116192E+10 | 0.423100E+10 | 0.273117E+09 | 0.395788E+10 | 0.00 | 0.00 |
August | 0.422139E+10 | 0.156275E+10 | 0.366099E+10 | 55693367.24 | 0.360530E+10 | 0.00 | 0.00 |
September | 0.237153E+10 | 0.255706E+10 | 0.269622E+10 | 560150.88 | 0.269566E+10 | 0.00 | 0.00 |
October | 0.873544E+09 | 0.442510E+10 | 0.208272E+10 | 0.00 | 0.208272E+10 | 0.00 | 0.00 |
November | 0.189816E+09 | 0.574402E+10 | 0.135439E+10 | 0.00 | 0.135439E+10 | 0.00 | 0.00 |
December | 8102909.15 | 0.872129E+10 | 0.129740E+10 | 0.00 | 0.129740E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.226818E+11 | 0.552757E+11 | 0.325420E+11 | 0.878510E+09 | 0.316635E+11 | 0.00 | 0.00 |
Minimum of Months | 818795.90 | 0.116192E+10 | 0.129740E+10 | 0.00 | 0.129740E+10 | 0.00 | 0.00 |
Maximum of Months | 0.518993E+10 | 0.886778E+10 | 0.441394E+10 | 0.375733E+09 | 0.403821E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.620200E+09 | 0.533861E+10 | 0.169114E+10 | 0.545317E+09 | 0.114582E+10 | 0.00 | 0.00 |
February | 0.100551E+10 | 0.451728E+10 | 0.224128E+10 | 0.672552E+09 | 0.156873E+10 | 0.00 | 0.00 |
March | 0.269200E+10 | 0.366388E+10 | 0.356076E+10 | 0.149122E+10 | 0.206954E+10 | 0.00 | 0.00 |
April | 0.418540E+10 | 0.257805E+10 | 0.456086E+10 | 0.201523E+10 | 0.254563E+10 | 0.00 | 0.00 |
May | 0.565945E+10 | 0.176580E+10 | 0.528013E+10 | 0.233568E+10 | 0.294444E+10 | 0.00 | 0.00 |
June | 0.686867E+10 | 0.106899E+10 | 0.570679E+10 | 0.252212E+10 | 0.318467E+10 | 0.00 | 0.00 |
July | 0.733801E+10 | 0.717078E+09 | 0.566268E+10 | 0.249320E+10 | 0.316948E+10 | 0.00 | 0.00 |
August | 0.648049E+10 | 0.943133E+09 | 0.511402E+10 | 0.214659E+10 | 0.296744E+10 | 0.00 | 0.00 |
September | 0.469551E+10 | 0.157978E+10 | 0.411847E+10 | 0.182680E+10 | 0.229168E+10 | 0.00 | 0.00 |
October | 0.250052E+10 | 0.267700E+10 | 0.288788E+10 | 0.119451E+10 | 0.169338E+10 | 0.00 | 0.00 |
November | 0.908171E+09 | 0.348139E+10 | 0.158522E+10 | 0.508520E+09 | 0.107670E+10 | 0.00 | 0.00 |
December | 0.310921E+09 | 0.530640E+10 | 0.131872E+10 | 0.272476E+09 | 0.104624E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.432648E+11 | 0.336374E+11 | 0.437280E+11 | 0.180242E+11 | 0.257037E+11 | 0.00 | 0.00 |
Minimum of Months | 0.310921E+09 | 0.717078E+09 | 0.131872E+10 | 0.272476E+09 | 0.104624E+10 | 0.00 | 0.00 |
Maximum of Months | 0.733801E+10 | 0.533861E+10 | 0.570679E+10 | 0.252212E+10 | 0.318467E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.472161E+10 | 0.734673E+10 | 0.596042E+10 | 0.347927E+10 | 0.248116E+10 | 0.00 | 0.00 |
February | 0.479821E+10 | 0.648311E+10 | 0.614673E+10 | 0.296389E+10 | 0.318284E+10 | 0.00 | 0.00 |
March | 0.798329E+10 | 0.545661E+10 | 0.830634E+10 | 0.466726E+10 | 0.363908E+10 | 0.00 | 0.00 |
April | 0.666364E+10 | 0.420838E+10 | 0.665707E+10 | 0.266017E+10 | 0.399690E+10 | 0.00 | 0.00 |
May | 0.660886E+10 | 0.287562E+10 | 0.601973E+10 | 0.174837E+10 | 0.427136E+10 | 0.00 | 0.00 |
June | 0.695268E+10 | 0.177988E+10 | 0.566056E+10 | 0.119949E+10 | 0.446107E+10 | 0.00 | 0.00 |
July | 0.810741E+10 | 0.123753E+10 | 0.597112E+10 | 0.144878E+10 | 0.452235E+10 | 0.00 | 0.00 |
August | 0.893515E+10 | 0.162117E+10 | 0.670356E+10 | 0.217345E+10 | 0.453011E+10 | 0.00 | 0.00 |
September | 0.928517E+10 | 0.255459E+10 | 0.754280E+10 | 0.367388E+10 | 0.386891E+10 | 0.00 | 0.00 |
October | 0.790643E+10 | 0.405647E+10 | 0.745790E+10 | 0.426009E+10 | 0.319782E+10 | 0.00 | 0.00 |
November | 0.475354E+10 | 0.507625E+10 | 0.516890E+10 | 0.291801E+10 | 0.225089E+10 | 0.00 | 0.00 |
December | 0.370169E+10 | 0.735617E+10 | 0.498410E+10 | 0.257949E+10 | 0.240461E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.804177E+11 | 0.500525E+11 | 0.765792E+11 | 0.337721E+11 | 0.428071E+11 | 0.00 | 0.00 |
Minimum of Months | 0.370169E+10 | 0.123753E+10 | 0.498410E+10 | 0.119949E+10 | 0.225089E+10 | 0.00 | 0.00 |
Maximum of Months | 0.928517E+10 | 0.735617E+10 | 0.830634E+10 | 0.466726E+10 | 0.453011E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.367811E+09 | 0.574986E+10 | 0.145097E+10 | 0.340630E+09 | 0.111034E+10 | 0.00 | 0.00 |
February | 0.824638E+09 | 0.495351E+10 | 0.212404E+10 | 0.545894E+09 | 0.157815E+10 | 0.00 | 0.00 |
March | 0.274363E+10 | 0.415735E+10 | 0.368574E+10 | 0.157815E+10 | 0.210759E+10 | 0.00 | 0.00 |
April | 0.383520E+10 | 0.311111E+10 | 0.436712E+10 | 0.179070E+10 | 0.257642E+10 | 0.00 | 0.00 |
May | 0.568415E+10 | 0.202139E+10 | 0.532344E+10 | 0.240585E+10 | 0.291759E+10 | 0.00 | 0.00 |
June | 0.746565E+10 | 0.133102E+10 | 0.621570E+10 | 0.292361E+10 | 0.329209E+10 | 0.00 | 0.00 |
July | 0.732457E+10 | 0.980423E+09 | 0.574231E+10 | 0.251762E+10 | 0.322468E+10 | 0.00 | 0.00 |
August | 0.648296E+10 | 0.127325E+10 | 0.519358E+10 | 0.220836E+10 | 0.298522E+10 | 0.00 | 0.00 |
September | 0.445130E+10 | 0.181496E+10 | 0.394700E+10 | 0.170454E+10 | 0.224246E+10 | 0.00 | 0.00 |
October | 0.214893E+10 | 0.306761E+10 | 0.264392E+10 | 0.931341E+09 | 0.171258E+10 | 0.00 | 0.00 |
November | 0.771372E+09 | 0.401017E+10 | 0.151626E+10 | 0.436931E+09 | 0.107933E+10 | 0.00 | 0.00 |
December | 0.320585E+09 | 0.599908E+10 | 0.135827E+10 | 0.295953E+09 | 0.106232E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.424208E+11 | 0.384697E+11 | 0.435683E+11 | 0.176796E+11 | 0.258888E+11 | 0.00 | 0.00 |
Minimum of Months | 0.320585E+09 | 0.980423E+09 | 0.135827E+10 | 0.295953E+09 | 0.106232E+10 | 0.00 | 0.00 |
Maximum of Months | 0.746565E+10 | 0.599908E+10 | 0.621570E+10 | 0.292361E+10 | 0.329209E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 18115884.54 | 0.805353E+10 | 0.138618E+10 | 0.00 | 0.138618E+10 | 0.00 | 0.00 |
February | 0.129015E+09 | 0.678925E+10 | 0.190763E+10 | 0.00 | 0.190763E+10 | 0.00 | 0.00 |
March | 0.823205E+09 | 0.548249E+10 | 0.256129E+10 | 0.00 | 0.256129E+10 | 0.00 | 0.00 |
April | 0.171129E+10 | 0.377379E+10 | 0.315833E+10 | 12602971.95 | 0.314572E+10 | 0.00 | 0.00 |
May | 0.296378E+10 | 0.251242E+10 | 0.379215E+10 | 0.160809E+09 | 0.363134E+10 | 0.00 | 0.00 |
June | 0.470798E+10 | 0.158201E+10 | 0.441402E+10 | 0.375744E+09 | 0.403828E+10 | 0.00 | 0.00 |
July | 0.521001E+10 | 0.114709E+10 | 0.423108E+10 | 0.273125E+09 | 0.395795E+10 | 0.00 | 0.00 |
August | 0.425847E+10 | 0.152113E+10 | 0.366106E+10 | 55695028.17 | 0.360536E+10 | 0.00 | 0.00 |
September | 0.242632E+10 | 0.238104E+10 | 0.269627E+10 | 560167.59 | 0.269571E+10 | 0.00 | 0.00 |
October | 0.102095E+10 | 0.389741E+10 | 0.208276E+10 | 0.00 | 0.208276E+10 | 0.00 | 0.00 |
November | 0.287368E+09 | 0.492631E+10 | 0.135442E+10 | 0.00 | 0.135442E+10 | 0.00 | 0.00 |
December | 21919636.77 | 0.769099E+10 | 0.129743E+10 | 0.00 | 0.129743E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.235784E+11 | 0.497575E+11 | 0.325426E+11 | 0.878536E+09 | 0.316641E+11 | 0.00 | 0.00 |
Minimum of Months | 18115884.54 | 0.114709E+10 | 0.129743E+10 | 0.00 | 0.129743E+10 | 0.00 | 0.00 |
Maximum of Months | 0.521001E+10 | 0.805353E+10 | 0.441402E+10 | 0.375744E+09 | 0.403828E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.657274E+09 | 0.488768E+10 | 0.169113E+10 | 0.545315E+09 | 0.114582E+10 | 0.00 | 0.00 |
February | 0.106748E+10 | 0.417656E+10 | 0.224127E+10 | 0.672549E+09 | 0.156872E+10 | 0.00 | 0.00 |
March | 0.276669E+10 | 0.337157E+10 | 0.356075E+10 | 0.149122E+10 | 0.206953E+10 | 0.00 | 0.00 |
April | 0.424689E+10 | 0.238482E+10 | 0.456084E+10 | 0.201523E+10 | 0.254562E+10 | 0.00 | 0.00 |
May | 0.566316E+10 | 0.167601E+10 | 0.528011E+10 | 0.233567E+10 | 0.294443E+10 | 0.00 | 0.00 |
June | 0.683833E+10 | 0.105200E+10 | 0.570676E+10 | 0.252211E+10 | 0.318465E+10 | 0.00 | 0.00 |
July | 0.728617E+10 | 0.757769E+09 | 0.566266E+10 | 0.249319E+10 | 0.316947E+10 | 0.00 | 0.00 |
August | 0.643725E+10 | 0.988321E+09 | 0.511400E+10 | 0.214658E+10 | 0.296742E+10 | 0.00 | 0.00 |
September | 0.469900E+10 | 0.149822E+10 | 0.411846E+10 | 0.182679E+10 | 0.229167E+10 | 0.00 | 0.00 |
October | 0.257749E+10 | 0.243556E+10 | 0.288787E+10 | 0.119450E+10 | 0.169337E+10 | 0.00 | 0.00 |
November | 0.976208E+09 | 0.312822E+10 | 0.158521E+10 | 0.508518E+09 | 0.107669E+10 | 0.00 | 0.00 |
December | 0.343806E+09 | 0.482108E+10 | 0.131871E+10 | 0.272475E+09 | 0.104624E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.435598E+11 | 0.311778E+11 | 0.437278E+11 | 0.180241E+11 | 0.257036E+11 | 0.00 | 0.00 |
Minimum of Months | 0.343806E+09 | 0.757769E+09 | 0.131871E+10 | 0.272475E+09 | 0.104624E+10 | 0.00 | 0.00 |
Maximum of Months | 0.728617E+10 | 0.488768E+10 | 0.570676E+10 | 0.252211E+10 | 0.318465E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.476228E+10 | 0.696919E+10 | 0.596060E+10 | 0.347938E+10 | 0.248122E+10 | 0.00 | 0.00 |
February | 0.483614E+10 | 0.617594E+10 | 0.614692E+10 | 0.296399E+10 | 0.318293E+10 | 0.00 | 0.00 |
March | 0.799725E+10 | 0.518507E+10 | 0.830658E+10 | 0.466742E+10 | 0.363917E+10 | 0.00 | 0.00 |
April | 0.670033E+10 | 0.396123E+10 | 0.665725E+10 | 0.266026E+10 | 0.399699E+10 | 0.00 | 0.00 |
May | 0.659222E+10 | 0.277304E+10 | 0.601987E+10 | 0.174842E+10 | 0.427145E+10 | 0.00 | 0.00 |
June | 0.693738E+10 | 0.172684E+10 | 0.566069E+10 | 0.119953E+10 | 0.446116E+10 | 0.00 | 0.00 |
July | 0.808008E+10 | 0.124615E+10 | 0.597126E+10 | 0.144882E+10 | 0.452244E+10 | 0.00 | 0.00 |
August | 0.890620E+10 | 0.162526E+10 | 0.670373E+10 | 0.217352E+10 | 0.453021E+10 | 0.00 | 0.00 |
September | 0.924221E+10 | 0.248641E+10 | 0.754301E+10 | 0.367400E+10 | 0.386900E+10 | 0.00 | 0.00 |
October | 0.790659E+10 | 0.385740E+10 | 0.745813E+10 | 0.426023E+10 | 0.319790E+10 | 0.00 | 0.00 |
November | 0.479922E+10 | 0.474937E+10 | 0.516905E+10 | 0.291810E+10 | 0.225095E+10 | 0.00 | 0.00 |
December | 0.376808E+10 | 0.686760E+10 | 0.498425E+10 | 0.257957E+10 | 0.240467E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.805280E+11 | 0.476235E+11 | 0.765813E+11 | 0.337732E+11 | 0.428081E+11 | 0.00 | 0.00 |
Minimum of Months | 0.376808E+10 | 0.124615E+10 | 0.498425E+10 | 0.119953E+10 | 0.225095E+10 | 0.00 | 0.00 |
Maximum of Months | 0.924221E+10 | 0.696919E+10 | 0.830658E+10 | 0.466742E+10 | 0.453021E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.399340E+09 | 0.516616E+10 | 0.145096E+10 | 0.340629E+09 | 0.111033E+10 | 0.00 | 0.00 |
February | 0.906780E+09 | 0.439898E+10 | 0.212403E+10 | 0.545892E+09 | 0.157814E+10 | 0.00 | 0.00 |
March | 0.290919E+10 | 0.355601E+10 | 0.368573E+10 | 0.157814E+10 | 0.210758E+10 | 0.00 | 0.00 |
April | 0.405022E+10 | 0.258484E+10 | 0.436710E+10 | 0.179069E+10 | 0.257641E+10 | 0.00 | 0.00 |
May | 0.575629E+10 | 0.184818E+10 | 0.532342E+10 | 0.240584E+10 | 0.291758E+10 | 0.00 | 0.00 |
June | 0.751808E+10 | 0.121646E+10 | 0.621567E+10 | 0.292360E+10 | 0.329208E+10 | 0.00 | 0.00 |
July | 0.739735E+10 | 0.898874E+09 | 0.574228E+10 | 0.251761E+10 | 0.322467E+10 | 0.00 | 0.00 |
August | 0.657996E+10 | 0.112757E+10 | 0.519356E+10 | 0.220835E+10 | 0.298521E+10 | 0.00 | 0.00 |
September | 0.451778E+10 | 0.163393E+10 | 0.394699E+10 | 0.170453E+10 | 0.224245E+10 | 0.00 | 0.00 |
October | 0.230473E+10 | 0.259215E+10 | 0.264391E+10 | 0.931337E+09 | 0.171258E+10 | 0.00 | 0.00 |
November | 0.891145E+09 | 0.326953E+10 | 0.151625E+10 | 0.436929E+09 | 0.107932E+10 | 0.00 | 0.00 |
December | 0.382110E+09 | 0.501210E+10 | 0.135827E+10 | 0.295952E+09 | 0.106232E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.436130E+11 | 0.333048E+11 | 0.435682E+11 | 0.176795E+11 | 0.258887E+11 | 0.00 | 0.00 |
Minimum of Months | 0.382110E+09 | 0.898874E+09 | 0.135827E+10 | 0.295952E+09 | 0.106232E+10 | 0.00 | 0.00 |
Maximum of Months | 0.751808E+10 | 0.516616E+10 | 0.621567E+10 | 0.292360E+10 | 0.329208E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 30711998.00 | 0.776520E+10 | 0.138618E+10 | 0.00 | 0.138618E+10 | 0.00 | 0.00 |
February | 0.153215E+09 | 0.653800E+10 | 0.190763E+10 | 0.00 | 0.190763E+10 | 0.00 | 0.00 |
March | 0.890247E+09 | 0.515123E+10 | 0.256129E+10 | 0.00 | 0.256129E+10 | 0.00 | 0.00 |
April | 0.182791E+10 | 0.348779E+10 | 0.315833E+10 | 12602971.95 | 0.314572E+10 | 0.00 | 0.00 |
May | 0.305711E+10 | 0.235932E+10 | 0.379215E+10 | 0.160809E+09 | 0.363134E+10 | 0.00 | 0.00 |
June | 0.471331E+10 | 0.154501E+10 | 0.441402E+10 | 0.375744E+09 | 0.403828E+10 | 0.00 | 0.00 |
July | 0.518025E+10 | 0.114366E+10 | 0.423108E+10 | 0.273125E+09 | 0.395795E+10 | 0.00 | 0.00 |
August | 0.424850E+10 | 0.149249E+10 | 0.366106E+10 | 55695028.17 | 0.360536E+10 | 0.00 | 0.00 |
September | 0.248336E+10 | 0.222796E+10 | 0.269627E+10 | 560167.59 | 0.269571E+10 | 0.00 | 0.00 |
October | 0.114665E+10 | 0.350062E+10 | 0.208276E+10 | 0.00 | 0.208276E+10 | 0.00 | 0.00 |
November | 0.355447E+09 | 0.447398E+10 | 0.135442E+10 | 0.00 | 0.135442E+10 | 0.00 | 0.00 |
December | 32351778.45 | 0.733714E+10 | 0.129743E+10 | 0.00 | 0.129743E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241191E+11 | 0.470224E+11 | 0.325426E+11 | 0.878536E+09 | 0.316641E+11 | 0.00 | 0.00 |
Minimum of Months | 30711998.00 | 0.114366E+10 | 0.129743E+10 | 0.00 | 0.129743E+10 | 0.00 | 0.00 |
Maximum of Months | 0.518025E+10 | 0.776520E+10 | 0.441402E+10 | 0.375744E+09 | 0.403828E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.679208E+09 | 0.471122E+10 | 0.169113E+10 | 0.545315E+09 | 0.114582E+10 | 0.00 | 0.00 |
February | 0.109887E+10 | 0.402869E+10 | 0.224127E+10 | 0.672549E+09 | 0.156872E+10 | 0.00 | 0.00 |
March | 0.282727E+10 | 0.317370E+10 | 0.356075E+10 | 0.149122E+10 | 0.206953E+10 | 0.00 | 0.00 |
April | 0.431059E+10 | 0.223909E+10 | 0.456084E+10 | 0.201523E+10 | 0.254562E+10 | 0.00 | 0.00 |
May | 0.568250E+10 | 0.160826E+10 | 0.528011E+10 | 0.233567E+10 | 0.294443E+10 | 0.00 | 0.00 |
June | 0.681554E+10 | 0.104428E+10 | 0.570676E+10 | 0.252211E+10 | 0.318465E+10 | 0.00 | 0.00 |
July | 0.724908E+10 | 0.767535E+09 | 0.566266E+10 | 0.249319E+10 | 0.316947E+10 | 0.00 | 0.00 |
August | 0.641290E+10 | 0.986742E+09 | 0.511400E+10 | 0.214658E+10 | 0.296742E+10 | 0.00 | 0.00 |
September | 0.471283E+10 | 0.143843E+10 | 0.411846E+10 | 0.182679E+10 | 0.229167E+10 | 0.00 | 0.00 |
October | 0.266064E+10 | 0.222527E+10 | 0.288787E+10 | 0.119450E+10 | 0.169337E+10 | 0.00 | 0.00 |
November | 0.103449E+10 | 0.285957E+10 | 0.158521E+10 | 0.508518E+09 | 0.107669E+10 | 0.00 | 0.00 |
December | 0.363022E+09 | 0.460496E+10 | 0.131871E+10 | 0.272475E+09 | 0.104624E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.438469E+11 | 0.296877E+11 | 0.437278E+11 | 0.180241E+11 | 0.257036E+11 | 0.00 | 0.00 |
Minimum of Months | 0.363022E+09 | 0.767535E+09 | 0.131871E+10 | 0.272475E+09 | 0.104624E+10 | 0.00 | 0.00 |
Maximum of Months | 0.724908E+10 | 0.471122E+10 | 0.570676E+10 | 0.252211E+10 | 0.318465E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.482931E+10 | 0.667211E+10 | 0.596060E+10 | 0.347938E+10 | 0.248122E+10 | 0.00 | 0.00 |
February | 0.490101E+10 | 0.592394E+10 | 0.614692E+10 | 0.296399E+10 | 0.318293E+10 | 0.00 | 0.00 |
March | 0.810384E+10 | 0.484948E+10 | 0.830658E+10 | 0.466742E+10 | 0.363917E+10 | 0.00 | 0.00 |
April | 0.679037E+10 | 0.369934E+10 | 0.665725E+10 | 0.266026E+10 | 0.399699E+10 | 0.00 | 0.00 |
May | 0.663156E+10 | 0.263441E+10 | 0.601987E+10 | 0.174842E+10 | 0.427145E+10 | 0.00 | 0.00 |
June | 0.691808E+10 | 0.169181E+10 | 0.566069E+10 | 0.119953E+10 | 0.446116E+10 | 0.00 | 0.00 |
July | 0.803675E+10 | 0.124640E+10 | 0.597126E+10 | 0.144882E+10 | 0.452244E+10 | 0.00 | 0.00 |
August | 0.887728E+10 | 0.160760E+10 | 0.670373E+10 | 0.217352E+10 | 0.453021E+10 | 0.00 | 0.00 |
September | 0.926174E+10 | 0.237408E+10 | 0.754301E+10 | 0.367400E+10 | 0.386900E+10 | 0.00 | 0.00 |
October | 0.802847E+10 | 0.351766E+10 | 0.745813E+10 | 0.426023E+10 | 0.319790E+10 | 0.00 | 0.00 |
November | 0.491047E+10 | 0.432835E+10 | 0.516905E+10 | 0.291810E+10 | 0.225095E+10 | 0.00 | 0.00 |
December | 0.384062E+10 | 0.652303E+10 | 0.498425E+10 | 0.257957E+10 | 0.240467E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.811295E+11 | 0.450682E+11 | 0.765813E+11 | 0.337732E+11 | 0.428081E+11 | 0.00 | 0.00 |
Minimum of Months | 0.384062E+10 | 0.124640E+10 | 0.498425E+10 | 0.119953E+10 | 0.225095E+10 | 0.00 | 0.00 |
Maximum of Months | 0.926174E+10 | 0.667211E+10 | 0.830658E+10 | 0.466742E+10 | 0.453021E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.415222E+09 | 0.497877E+10 | 0.145096E+10 | 0.340629E+09 | 0.111033E+10 | 0.00 | 0.00 |
February | 0.925441E+09 | 0.425108E+10 | 0.212403E+10 | 0.545892E+09 | 0.157814E+10 | 0.00 | 0.00 |
March | 0.294980E+10 | 0.335986E+10 | 0.368573E+10 | 0.157814E+10 | 0.210758E+10 | 0.00 | 0.00 |
April | 0.409460E+10 | 0.243243E+10 | 0.436710E+10 | 0.179069E+10 | 0.257641E+10 | 0.00 | 0.00 |
May | 0.577713E+10 | 0.176835E+10 | 0.532342E+10 | 0.240584E+10 | 0.291758E+10 | 0.00 | 0.00 |
June | 0.749979E+10 | 0.119621E+10 | 0.621567E+10 | 0.292360E+10 | 0.329208E+10 | 0.00 | 0.00 |
July | 0.736743E+10 | 0.897653E+09 | 0.574228E+10 | 0.251761E+10 | 0.322467E+10 | 0.00 | 0.00 |
August | 0.656361E+10 | 0.111658E+10 | 0.519356E+10 | 0.220835E+10 | 0.298521E+10 | 0.00 | 0.00 |
September | 0.453538E+10 | 0.156386E+10 | 0.394699E+10 | 0.170453E+10 | 0.224245E+10 | 0.00 | 0.00 |
October | 0.236045E+10 | 0.239471E+10 | 0.264391E+10 | 0.931337E+09 | 0.171258E+10 | 0.00 | 0.00 |
November | 0.930991E+09 | 0.303004E+10 | 0.151625E+10 | 0.436929E+09 | 0.107932E+10 | 0.00 | 0.00 |
December | 0.397262E+09 | 0.480143E+10 | 0.135827E+10 | 0.295952E+09 | 0.106232E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.438171E+11 | 0.317910E+11 | 0.435682E+11 | 0.176795E+11 | 0.258887E+11 | 0.00 | 0.00 |
Minimum of Months | 0.397262E+09 | 0.897653E+09 | 0.135827E+10 | 0.295952E+09 | 0.106232E+10 | 0.00 | 0.00 |
Maximum of Months | 0.749979E+10 | 0.497877E+10 | 0.621567E+10 | 0.292360E+10 | 0.329208E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.421764E+11 | -0.411391E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103733E+10 | 58.97 | 0.00 | 0.00 |
February | 0.388630E+11 | -0.379234E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -939589570.9 | 58.99 | 0.00 | 0.00 |
March | 0.450323E+11 | -0.440004E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103189E+10 | 58.98 | 0.00 | 0.00 |
April | 0.393153E+11 | -0.383232E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992096956.6 | 58.97 | 0.00 | 0.00 |
May | 0.396309E+11 | -0.386054E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102549E+10 | 58.98 | 0.00 | 0.00 |
June | 0.368885E+11 | -0.358967E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991799715.3 | 58.98 | 0.00 | 0.00 |
July | 0.334878E+11 | -0.324687E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101912E+10 | 58.97 | 0.00 | 0.00 |
August | 0.359021E+11 | -0.348786E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102351E+10 | 58.98 | 0.00 | 0.00 |
September | 0.332036E+11 | -0.322155E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988106818.7 | 58.97 | 0.00 | 0.00 |
October | 0.359179E+11 | -0.348968E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102108E+10 | 58.97 | 0.00 | 0.00 |
November | 0.374451E+11 | -0.364562E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988871291.3 | 58.97 | 0.00 | 0.00 |
December | 0.395181E+11 | -0.384909E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102717E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.457381E+12 | -0.445295E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120860E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.332036E+11 | -0.440004E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.103733E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.450323E+11 | -0.322155E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -939589570.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.62 | 0.61 | 01-JAN-08:39 | 3871.50 | 30.90 | 217.17 | 242.00 | 3200.16 | 33.61 | 242.17 | 215.50 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:09 | 4962.43 | 32.33 | 244.33 | 251.33 | 1508.70 | 25.37 | 215.50 | 226.50 |
March | 339.33 | 0.62 | 0.61 | 01-MAR-07:30 | 7267.08 | 29.07 | 247.33 | 320.67 | 1197.34 | 21.33 | 170.83 | 282.17 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:40 | 1728.78 | 17.53 | 0.00 | 337.33 | 943.51 | 20.47 | 167.67 | 294.67 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-06:19 | 1558.81 | 17.47 | 0.00 | 372.50 | 900.48 | 20.49 | 145.83 | 318.00 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:49 | 1412.93 | 17.24 | 0.00 | 382.33 | 799.59 | 20.23 | 168.83 | 335.67 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-05:00 | 1483.93 | 17.31 | 0.00 | 389.00 | 826.10 | 20.29 | 182.00 | 336.50 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:00 | 1760.43 | 17.87 | 0.00 | 367.33 | 954.38 | 20.83 | 216.33 | 322.33 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2526.56 | 19.46 | 17.00 | 316.83 | 1240.06 | 21.52 | 193.17 | 279.33 |
October | 314.33 | 0.63 | 0.61 | 01-OCT-06:00 | 5803.39 | 31.41 | 269.33 | 293.17 | 1292.57 | 22.10 | 177.33 | 269.33 |
November | 258.33 | 0.63 | 0.61 | 01-NOV-07:40 | 3674.60 | 30.93 | 226.50 | 234.33 | 1436.16 | 27.73 | 215.00 | 208.50 |
December | 230.67 | 0.62 | 0.61 | 01-DEC-08:09 | 3241.77 | 29.62 | 194.17 | 230.50 | 2601.75 | 32.54 | 218.00 | 197.00 |
Annual Sum or Average | 3928.50 | 0.63 | 3090.86 | 23.20 | 1415.83 | 3737.33 | 1297.88 | 23.11 | 2312.67 | 3285.50 | ||
Minimum of Months | 230.67 | 0.62 | 0.61 | 1412.93 | 17.24 | 0.00 | 230.50 | 799.59 | 20.23 | 145.83 | 197.00 | |
Maximum of Months | 439.00 | 0.63 | 0.61 | 7267.08 | 32.33 | 269.33 | 389.00 | 3200.16 | 33.61 | 242.17 | 336.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-08:39 | 1207.37 | 17.12 | 46.67 | 224.83 | 632.01 | 18.01 | 40.83 | 167.50 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:09 | 1772.97 | 18.64 | 65.33 | 239.83 | 881.56 | 18.12 | 39.50 | 202.00 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:30 | 2469.31 | 17.60 | 67.50 | 309.67 | 1001.46 | 15.23 | 1.83 | 264.50 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:19 | 2520.93 | 15.42 | 41.83 | 339.67 | 1476.93 | 14.59 | 0.00 | 297.83 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-05:30 | 3542.41 | 13.33 | 0.00 | 378.50 | 1460.72 | 14.81 | 0.00 | 328.67 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:40 | 3201.49 | 13.35 | 0.00 | 391.50 | 1384.42 | 14.69 | 0.00 | 357.50 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-04:00 | 3033.10 | 13.39 | 0.00 | 395.83 | 1298.93 | 14.68 | 0.00 | 355.17 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:49 | 2820.68 | 13.83 | 3.50 | 368.67 | 1174.41 | 15.06 | 0.00 | 329.17 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2752.53 | 16.89 | 45.67 | 312.50 | 1549.22 | 15.70 | 1.83 | 271.00 |
October | 314.33 | 0.63 | 0.61 | 01-OCT-06:00 | 1787.24 | 18.15 | 73.00 | 278.50 | 930.63 | 17.84 | 48.33 | 232.67 |
November | 258.33 | 0.64 | 0.61 | 01-NOV-07:40 | 1268.44 | 17.83 | 68.50 | 219.33 | 714.35 | 18.42 | 55.50 | 155.67 |
December | 230.67 | 0.63 | 0.61 | 01-DEC-07:00 | 1107.90 | 18.06 | 55.00 | 214.83 | 545.90 | 17.65 | 35.67 | 151.83 |
Annual Sum or Average | 3928.50 | 0.63 | 2423.37 | 15.78 | 467.00 | 3673.67 | 1135.33 | 15.96 | 223.50 | 3113.50 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 1107.90 | 13.33 | 0.00 | 214.83 | 545.90 | 14.59 | 0.00 | 151.83 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 3542.41 | 18.64 | 73.00 | 395.83 | 1549.22 | 18.42 | 55.50 | 357.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.61 | 01-JAN-09:09 | 547.98 | 0.00 | 0.00 | 205.00 | 305.46 | 0.00 | 0.00 | 79.67 |
February | 262.50 | 0.64 | 0.61 | 01-FEB-09:30 | 722.28 | 0.00 | 0.00 | 232.17 | 399.51 | 0.00 | 0.00 | 165.33 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:00 | 759.02 | 0.00 | 0.00 | 301.17 | 444.24 | 0.00 | 0.00 | 236.67 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:40 | 881.35 | 0.00 | 0.00 | 344.00 | 515.30 | 0.00 | 0.00 | 293.50 |
May | 332.17 | 0.62 | 0.61 | 01-MAY-05:40 | 1038.22 | 0.00 | 0.00 | 391.67 | 632.41 | 0.00 | 0.00 | 345.67 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:49 | 1180.33 | 0.00 | 0.00 | 407.17 | 660.95 | 0.00 | 0.00 | 375.33 |
July | 439.00 | 0.62 | 0.61 | 01-JUL-05:10 | 1122.87 | 0.00 | 0.00 | 412.50 | 653.78 | 0.00 | 0.00 | 378.17 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:49 | 990.07 | 0.00 | 0.00 | 379.67 | 588.48 | 0.00 | 0.00 | 337.67 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 818.67 | 0.00 | 0.00 | 310.33 | 510.67 | 0.00 | 0.00 | 248.00 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-07:10 | 667.02 | 0.00 | 0.00 | 266.83 | 383.17 | 0.00 | 0.00 | 181.33 |
November | 258.33 | 0.65 | 0.61 | 01-NOV-07:00 | 532.35 | 0.00 | 0.00 | 201.17 | 294.91 | 0.00 | 0.00 | 78.33 |
December | 230.67 | 0.64 | 0.61 | 01-DEC-11:20 | 553.87 | 0.00 | 0.00 | 190.00 | 301.01 | 0.00 | 0.00 | 75.67 |
Annual Sum or Average | 3928.50 | 0.63 | 858.82 | 0.00 | 0.00 | 3641.67 | 498.71 | 0.00 | 0.00 | 2795.33 | ||
Minimum of Months | 230.67 | 0.62 | 0.61 | 532.35 | 0.00 | 0.00 | 190.00 | 294.91 | 0.00 | 0.00 | 75.67 | |
Maximum of Months | 439.00 | 0.65 | 0.61 | 1180.33 | 0.00 | 0.00 | 412.50 | 660.95 | 0.00 | 0.00 | 378.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-09:09 | 1185.81 | 18.24 | 67.00 | 222.33 | 659.07 | 18.99 | 59.83 | 164.00 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:30 | 1643.85 | 18.36 | 65.00 | 240.50 | 839.39 | 18.00 | 40.50 | 199.50 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:00 | 2271.99 | 17.50 | 66.67 | 311.00 | 1339.64 | 17.30 | 41.33 | 270.00 |
April | 371.17 | 0.63 | 0.61 | 01-APR-07:10 | 2840.92 | 15.46 | 42.67 | 335.67 | 1169.20 | 14.60 | 0.00 | 296.33 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-06:30 | 2909.78 | 13.28 | 0.00 | 379.67 | 1641.39 | 14.89 | 1.50 | 331.50 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:00 | 3213.16 | 13.35 | 0.00 | 389.83 | 1326.52 | 16.44 | 34.00 | 352.83 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-06:10 | 2846.20 | 13.42 | 0.00 | 395.00 | 1221.47 | 14.73 | 0.00 | 354.67 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-06:10 | 2589.34 | 13.90 | 4.33 | 371.17 | 1431.39 | 15.06 | 0.00 | 325.83 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2755.30 | 18.19 | 64.83 | 311.67 | 1204.65 | 15.72 | 3.67 | 274.67 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-07:19 | 1674.28 | 17.83 | 69.83 | 276.67 | 867.22 | 17.69 | 48.00 | 232.50 |
November | 258.33 | 0.64 | 0.61 | 01-NOV-07:00 | 1228.21 | 17.76 | 71.17 | 217.17 | 661.19 | 18.10 | 54.33 | 159.33 |
December | 230.67 | 0.63 | 0.61 | 01-DEC-10:00 | 1152.70 | 18.07 | 54.67 | 209.17 | 592.94 | 17.55 | 33.67 | 150.00 |
Annual Sum or Average | 3928.50 | 0.63 | 2320.68 | 15.90 | 506.17 | 3659.83 | 1130.06 | 16.37 | 316.83 | 3111.17 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 1152.70 | 13.28 | 0.00 | 209.17 | 592.94 | 14.60 | 0.00 | 150.00 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 3213.16 | 18.36 | 71.17 | 395.00 | 1641.39 | 18.99 | 59.83 | 354.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-08:50 | 3720.69 | 27.71 | 191.17 | 239.83 | 3228.10 | 32.91 | 231.50 | 216.17 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:09 | 4845.79 | 29.54 | 219.17 | 248.67 | 1591.51 | 23.68 | 105.33 | 232.17 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:40 | 7219.07 | 27.36 | 218.00 | 319.33 | 1251.18 | 16.88 | 5.67 | 284.83 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:40 | 1695.95 | 11.53 | 0.00 | 336.17 | 975.32 | 16.27 | 0.00 | 297.00 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-06:19 | 1535.64 | 11.80 | 0.00 | 370.00 | 931.33 | 16.67 | 0.00 | 320.50 |
June | 430.67 | 0.64 | 0.61 | 01-JUN-05:49 | 1387.67 | 11.67 | 0.00 | 379.67 | 824.90 | 16.45 | 0.00 | 338.50 |
July | 439.00 | 0.64 | 0.61 | 01-JUL-05:00 | 1456.18 | 11.62 | 0.00 | 385.83 | 852.08 | 16.39 | 0.00 | 339.00 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:00 | 1724.27 | 12.05 | 0.00 | 365.00 | 984.29 | 16.81 | 0.00 | 324.50 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2484.21 | 13.87 | 17.00 | 315.00 | 1282.49 | 17.42 | 0.00 | 280.67 |
October | 314.33 | 0.63 | 0.61 | 01-OCT-06:00 | 5735.51 | 30.29 | 258.50 | 292.17 | 1416.89 | 17.68 | 24.67 | 270.50 |
November | 258.33 | 0.64 | 0.61 | 01-NOV-07:40 | 3569.67 | 28.20 | 206.17 | 231.17 | 1735.00 | 26.92 | 159.00 | 209.83 |
December | 230.67 | 0.62 | 0.61 | 01-DEC-08:09 | 3023.44 | 24.59 | 153.50 | 229.00 | 2611.12 | 31.05 | 201.50 | 197.17 |
Annual Sum or Average | 3928.50 | 0.63 | 3026.19 | 18.79 | 1263.50 | 3711.83 | 1357.54 | 19.79 | 727.67 | 3310.83 | ||
Minimum of Months | 230.67 | 0.62 | 0.61 | 1387.67 | 11.53 | 0.00 | 229.00 | 824.90 | 16.27 | 0.00 | 197.17 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 7219.07 | 30.29 | 258.50 | 385.83 | 3228.10 | 32.91 | 231.50 | 339.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-08:39 | 1198.45 | 14.52 | 46.83 | 223.83 | 648.03 | 15.75 | 41.17 | 170.67 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:09 | 1762.67 | 16.41 | 65.33 | 239.50 | 902.54 | 15.90 | 39.83 | 204.17 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:30 | 2293.21 | 15.16 | 67.33 | 308.67 | 1028.90 | 12.56 | 1.83 | 267.67 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:19 | 2522.12 | 12.52 | 41.83 | 339.33 | 1509.10 | 12.03 | 0.00 | 300.17 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-05:30 | 3532.77 | 9.83 | 0.00 | 378.17 | 1500.35 | 12.33 | 0.00 | 331.67 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:40 | 3187.22 | 9.94 | 0.00 | 390.33 | 1421.48 | 12.32 | 0.00 | 359.50 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-04:00 | 2998.23 | 9.95 | 0.00 | 395.50 | 1334.53 | 12.28 | 0.00 | 357.17 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:49 | 2648.89 | 10.43 | 3.50 | 368.00 | 1207.72 | 12.53 | 0.00 | 332.17 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2738.00 | 14.07 | 44.83 | 311.00 | 1582.42 | 13.05 | 1.83 | 274.33 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-06:00 | 1626.74 | 14.01 | 52.17 | 277.50 | 953.82 | 15.73 | 48.83 | 236.83 |
November | 258.33 | 0.64 | 0.61 | 01-NOV-07:40 | 1257.72 | 15.43 | 67.00 | 218.50 | 729.35 | 16.49 | 56.00 | 158.33 |
December | 230.67 | 0.63 | 0.61 | 01-DEC-07:00 | 1050.55 | 14.04 | 39.50 | 213.67 | 559.55 | 15.40 | 36.00 | 155.33 |
Annual Sum or Average | 3928.50 | 0.63 | 2364.99 | 12.64 | 428.33 | 3664.00 | 1164.10 | 13.57 | 225.50 | 3148.00 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 1050.55 | 9.83 | 0.00 | 213.67 | 559.55 | 12.03 | 0.00 | 155.33 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 3532.77 | 16.41 | 67.33 | 395.50 | 1582.42 | 16.49 | 56.00 | 359.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.61 | 01-JAN-09:09 | 534.82 | 0.00 | 0.00 | 201.67 | 313.25 | 0.00 | 0.00 | 89.33 |
February | 262.50 | 0.64 | 0.61 | 01-FEB-09:39 | 706.54 | 0.00 | 0.00 | 231.50 | 410.31 | 0.00 | 0.00 | 168.67 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:00 | 744.02 | 0.00 | 0.00 | 300.00 | 456.89 | 0.00 | 0.00 | 241.83 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:40 | 865.21 | 0.00 | 0.00 | 342.67 | 530.40 | 0.00 | 0.00 | 296.17 |
May | 332.17 | 0.62 | 0.61 | 01-MAY-05:40 | 1021.14 | 0.00 | 0.00 | 390.17 | 654.41 | 0.00 | 0.00 | 348.83 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:49 | 1134.79 | 0.00 | 0.00 | 404.17 | 708.60 | 0.00 | 0.00 | 381.00 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-05:10 | 1104.65 | 0.00 | 0.00 | 412.00 | 672.71 | 0.00 | 0.00 | 379.83 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:49 | 972.25 | 0.00 | 0.00 | 377.50 | 605.24 | 0.00 | 0.00 | 340.33 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 804.01 | 0.00 | 0.00 | 307.50 | 525.11 | 0.00 | 0.00 | 251.83 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-07:10 | 652.76 | 0.00 | 0.00 | 264.67 | 393.62 | 0.00 | 0.00 | 188.17 |
November | 258.33 | 0.65 | 0.61 | 01-NOV-07:00 | 519.68 | 0.00 | 0.00 | 198.33 | 302.56 | 0.00 | 0.00 | 87.83 |
December | 230.67 | 0.64 | 0.61 | 01-DEC-11:20 | 540.55 | 0.00 | 0.00 | 186.50 | 308.72 | 0.00 | 0.00 | 81.83 |
Annual Sum or Average | 3928.50 | 0.63 | 839.95 | 0.00 | 0.00 | 3616.67 | 516.25 | 0.00 | 0.00 | 2855.67 | ||
Minimum of Months | 230.67 | 0.62 | 0.61 | 519.68 | 0.00 | 0.00 | 186.50 | 302.56 | 0.00 | 0.00 | 81.83 | |
Maximum of Months | 439.00 | 0.65 | 0.61 | 1134.79 | 0.00 | 0.00 | 412.00 | 708.60 | 0.00 | 0.00 | 381.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-09:09 | 1176.95 | 16.10 | 66.83 | 221.33 | 672.95 | 17.07 | 60.00 | 166.17 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:39 | 1632.61 | 16.11 | 65.00 | 239.83 | 859.34 | 15.78 | 40.50 | 202.17 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:00 | 2270.13 | 15.04 | 66.50 | 310.17 | 1368.13 | 15.12 | 41.17 | 271.33 |
April | 371.17 | 0.63 | 0.61 | 01-APR-07:10 | 2840.19 | 12.58 | 42.50 | 334.83 | 1141.72 | 12.06 | 0.00 | 298.33 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-06:30 | 2902.02 | 9.76 | 0.00 | 378.67 | 1677.45 | 12.28 | 0.00 | 335.17 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:00 | 3196.69 | 9.86 | 0.00 | 389.00 | 1323.28 | 12.27 | 0.00 | 353.83 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-06:10 | 2832.35 | 9.95 | 0.00 | 394.17 | 1256.70 | 12.30 | 0.00 | 357.33 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-06:10 | 2579.42 | 10.52 | 4.17 | 370.67 | 1464.23 | 12.55 | 0.00 | 329.17 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2758.41 | 15.76 | 64.83 | 310.83 | 1239.14 | 13.08 | 3.67 | 277.00 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-07:19 | 1666.26 | 15.52 | 69.83 | 275.67 | 888.71 | 15.56 | 48.33 | 235.83 |
November | 258.33 | 0.64 | 0.61 | 01-NOV-07:00 | 1220.05 | 15.64 | 71.33 | 217.00 | 675.43 | 16.18 | 54.83 | 162.33 |
December | 230.67 | 0.63 | 0.61 | 01-DEC-10:00 | 1142.91 | 15.91 | 54.50 | 208.00 | 606.65 | 15.35 | 33.50 | 152.67 |
Annual Sum or Average | 3928.50 | 0.63 | 2312.56 | 13.08 | 505.50 | 3650.17 | 1148.19 | 13.84 | 282.00 | 3141.33 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 1142.91 | 9.76 | 0.00 | 208.00 | 606.65 | 12.06 | 0.00 | 152.67 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 3196.69 | 16.11 | 71.33 | 394.17 | 1677.45 | 17.07 | 60.00 | 357.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-08:50 | 3719.70 | 27.69 | 191.17 | 239.83 | 3229.37 | 32.90 | 231.50 | 216.17 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:09 | 4845.47 | 29.53 | 219.17 | 248.67 | 1593.33 | 23.67 | 105.17 | 232.17 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:40 | 7219.76 | 27.34 | 217.67 | 319.33 | 1252.63 | 16.86 | 5.67 | 284.83 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:40 | 1696.90 | 11.49 | 0.00 | 336.33 | 976.53 | 16.26 | 0.00 | 297.00 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-06:19 | 1536.27 | 11.76 | 0.00 | 369.83 | 932.28 | 16.65 | 0.00 | 320.50 |
June | 430.67 | 0.64 | 0.61 | 01-JUN-05:49 | 1388.26 | 11.63 | 0.00 | 379.50 | 825.78 | 16.43 | 0.00 | 338.50 |
July | 439.00 | 0.64 | 0.61 | 01-JUL-05:00 | 1456.89 | 11.58 | 0.00 | 385.50 | 853.04 | 16.37 | 0.00 | 339.17 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:00 | 1725.23 | 12.01 | 0.00 | 365.00 | 985.50 | 16.79 | 0.00 | 324.50 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2485.07 | 13.83 | 17.00 | 315.00 | 1283.98 | 17.40 | 0.00 | 280.67 |
October | 314.33 | 0.63 | 0.61 | 01-OCT-06:00 | 5735.56 | 30.27 | 258.33 | 292.17 | 1508.05 | 17.95 | 28.67 | 270.50 |
November | 258.33 | 0.64 | 0.61 | 01-NOV-07:40 | 3569.08 | 28.18 | 206.17 | 231.17 | 1992.67 | 28.73 | 185.00 | 210.17 |
December | 230.67 | 0.62 | 0.61 | 01-DEC-08:09 | 3022.41 | 24.57 | 153.50 | 229.00 | 2612.38 | 31.05 | 201.50 | 197.17 |
Annual Sum or Average | 3928.50 | 0.63 | 3026.52 | 18.76 | 1263.00 | 3711.33 | 1382.81 | 19.91 | 757.50 | 3311.33 | ||
Minimum of Months | 230.67 | 0.62 | 0.61 | 1388.26 | 11.49 | 0.00 | 229.00 | 825.78 | 16.26 | 0.00 | 197.17 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 7219.76 | 30.27 | 258.33 | 385.50 | 3229.37 | 32.90 | 231.50 | 339.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-08:39 | 1198.33 | 14.51 | 46.83 | 223.83 | 648.70 | 15.74 | 41.17 | 170.83 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:09 | 1762.66 | 16.40 | 65.33 | 239.50 | 903.47 | 15.89 | 39.83 | 204.33 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:30 | 2293.03 | 15.15 | 67.33 | 308.67 | 1029.75 | 12.56 | 1.83 | 267.67 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:19 | 2522.12 | 12.51 | 41.83 | 339.33 | 1510.06 | 12.02 | 0.00 | 300.17 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-05:30 | 3532.63 | 9.81 | 0.00 | 378.17 | 1501.30 | 12.32 | 0.00 | 331.67 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:40 | 3187.16 | 9.93 | 0.00 | 390.33 | 1422.47 | 12.31 | 0.00 | 359.50 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-04:00 | 2998.24 | 9.94 | 0.00 | 395.50 | 1335.50 | 12.27 | 0.00 | 357.33 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:49 | 2648.87 | 10.42 | 3.50 | 368.00 | 1208.75 | 12.52 | 0.00 | 332.50 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2737.49 | 14.05 | 44.83 | 311.00 | 1583.37 | 13.04 | 1.83 | 274.33 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-06:00 | 1626.60 | 14.00 | 52.17 | 277.67 | 954.59 | 15.72 | 48.83 | 237.00 |
November | 258.33 | 0.64 | 0.61 | 01-NOV-07:40 | 1257.68 | 15.42 | 67.00 | 218.50 | 729.99 | 16.49 | 56.00 | 158.33 |
December | 230.67 | 0.63 | 0.61 | 01-DEC-07:00 | 1050.55 | 14.03 | 39.50 | 213.67 | 560.22 | 15.39 | 36.00 | 155.67 |
Annual Sum or Average | 3928.50 | 0.63 | 2364.90 | 12.63 | 428.33 | 3664.17 | 1164.99 | 13.57 | 225.50 | 3149.33 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 1050.55 | 9.81 | 0.00 | 213.67 | 560.22 | 12.02 | 0.00 | 155.67 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 3532.63 | 16.40 | 67.33 | 395.50 | 1583.37 | 16.49 | 56.00 | 359.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.61 | 01-JAN-09:09 | 534.92 | 0.00 | 0.00 | 201.67 | 313.62 | 0.00 | 0.00 | 89.83 |
February | 262.50 | 0.64 | 0.61 | 01-FEB-09:39 | 706.71 | 0.00 | 0.00 | 231.50 | 410.81 | 0.00 | 0.00 | 169.00 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:00 | 744.08 | 0.00 | 0.00 | 300.00 | 457.36 | 0.00 | 0.00 | 242.17 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:40 | 865.32 | 0.00 | 0.00 | 342.67 | 530.94 | 0.00 | 0.00 | 296.33 |
May | 332.17 | 0.62 | 0.61 | 01-MAY-05:40 | 1020.99 | 0.00 | 0.00 | 390.17 | 654.92 | 0.00 | 0.00 | 348.83 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:49 | 1134.79 | 0.00 | 0.00 | 404.17 | 709.22 | 0.00 | 0.00 | 381.00 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-05:10 | 1104.68 | 0.00 | 0.00 | 412.00 | 673.33 | 0.00 | 0.00 | 380.00 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:49 | 972.28 | 0.00 | 0.00 | 377.50 | 605.82 | 0.00 | 0.00 | 340.33 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 803.82 | 0.00 | 0.00 | 307.50 | 525.52 | 0.00 | 0.00 | 251.83 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-07:10 | 652.84 | 0.00 | 0.00 | 264.67 | 394.04 | 0.00 | 0.00 | 188.33 |
November | 258.33 | 0.65 | 0.61 | 01-NOV-07:00 | 519.80 | 0.00 | 0.00 | 198.50 | 302.93 | 0.00 | 0.00 | 88.00 |
December | 230.67 | 0.64 | 0.61 | 01-DEC-11:20 | 540.70 | 0.00 | 0.00 | 186.50 | 309.11 | 0.00 | 0.00 | 82.00 |
Annual Sum or Average | 3928.50 | 0.63 | 839.99 | 0.00 | 0.00 | 3616.83 | 516.75 | 0.00 | 0.00 | 2857.67 | ||
Minimum of Months | 230.67 | 0.62 | 0.61 | 519.80 | 0.00 | 0.00 | 186.50 | 302.93 | 0.00 | 0.00 | 82.00 | |
Maximum of Months | 439.00 | 0.65 | 0.61 | 1134.79 | 0.00 | 0.00 | 412.00 | 709.22 | 0.00 | 0.00 | 381.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-09:09 | 1176.91 | 16.09 | 66.83 | 221.33 | 673.60 | 17.06 | 60.00 | 166.33 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:39 | 1632.59 | 16.10 | 65.00 | 239.83 | 860.26 | 15.77 | 40.50 | 202.33 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:00 | 2269.94 | 15.03 | 66.50 | 310.17 | 1368.99 | 15.11 | 41.17 | 271.33 |
April | 371.17 | 0.63 | 0.61 | 01-APR-07:10 | 2840.19 | 12.57 | 42.50 | 334.50 | 1142.68 | 12.05 | 0.00 | 298.33 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-06:30 | 2901.83 | 9.75 | 0.00 | 378.67 | 1678.38 | 12.27 | 0.00 | 335.33 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:00 | 3196.52 | 9.85 | 0.00 | 389.00 | 1324.31 | 12.26 | 0.00 | 353.83 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-06:10 | 2832.36 | 9.94 | 0.00 | 394.17 | 1257.72 | 12.29 | 0.00 | 357.33 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-06:10 | 2579.45 | 10.51 | 4.17 | 370.67 | 1465.28 | 12.54 | 0.00 | 329.50 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2744.50 | 15.57 | 62.83 | 310.67 | 1240.04 | 13.07 | 3.67 | 277.17 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-07:19 | 1550.01 | 13.86 | 50.50 | 275.50 | 889.52 | 15.55 | 48.33 | 235.83 |
November | 258.33 | 0.64 | 0.61 | 01-NOV-07:00 | 1220.03 | 15.63 | 71.33 | 217.00 | 676.06 | 16.17 | 54.83 | 162.33 |
December | 230.67 | 0.63 | 0.61 | 01-DEC-10:00 | 1142.89 | 15.90 | 54.50 | 208.00 | 607.32 | 15.34 | 33.50 | 152.83 |
Annual Sum or Average | 3928.50 | 0.63 | 2302.19 | 12.92 | 484.17 | 3649.50 | 1149.08 | 13.83 | 282.00 | 3142.50 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 1142.89 | 9.75 | 0.00 | 208.00 | 607.32 | 12.05 | 0.00 | 152.83 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 3196.52 | 16.10 | 71.33 | 394.17 | 1678.38 | 17.06 | 60.00 | 357.33 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101878E+10 | 52505.05 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150973E+10 | 78631.64 | 21-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274787E+10 | 69788.52 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.484447E+09 | 46124.76 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103542E+09 | 18629.40 | 04-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3011393.53 | 3038.39 | 10-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 426.03 | 0.37 | 30-AUG-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27180552.05 | 14225.22 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.366944E+09 | 42896.02 | 17-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.918483E+09 | 43586.62 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282213E+10 | 73820.35 | 28-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.282213E+10 | 78631.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168207E+10 | 15008.05 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135428E+10 | 15099.86 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215541E+09 | 15173.08 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1468058.69 | 349.70 | 25-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.638000E+09 | 15031.96 | 09-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168207E+10 | 15173.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.207293E+10 | 14751.77 | 03-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178682E+10 | 15009.00 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.377153E+09 | 15027.80 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20612974.77 | 5203.61 | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20737616.75 | 3123.06 | 17-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194583E+09 | 8111.04 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161083E+10 | 14965.36 | 26-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.608366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.207293E+10 | 15027.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241073E+10 | 20587.47 | 20-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204613E+10 | 20922.14 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.361972E+09 | 20946.79 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38087973.71 | 10634.30 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30651192.78 | 9852.47 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165205E+09 | 15883.18 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153814E+10 | 20861.07 | 26-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.659093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241073E+10 | 20946.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139780E+10 | 13406.59 | 12-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.656326E+09 | 13417.54 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17420329.49 | 4988.79 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 75555454.09 | 9948.99 | 28-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139780E+10 | 13417.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.335548E+11 | 544936.21 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307005E+11 | 806301.72 | 21-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188027E+11 | 716183.24 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127928E+11 | 521257.81 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165175E+10 | 229736.52 | 04-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267755E+09 | 119001.33 | 10-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5648.39 | 9.41 | 11-JUL-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9368251.74 | 9454.17 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.639732E+09 | 177834.46 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.832551E+10 | 466667.31 | 17-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.230594E+11 | 489932.31 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.317677E+11 | 759170.48 | 28-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161572E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5648.39 | 9.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.335548E+11 | 806301.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198430E+11 | 607223.17 | 09-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.947587E+10 | 607428.73 | 13-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.650747E+09 | 605094.83 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.673313E+10 | 607534.25 | 12-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198430E+11 | 607534.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.878245E+11 | 131746.80 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.777306E+11 | 131464.00 | 27-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315248E+11 | 131569.89 | 13-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.557504E+10 | 141813.41 | 14-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45939033.04 | 9582.07 | 30-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.362795E+10 | 141375.41 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161462E+11 | 131397.16 | 02-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.737752E+11 | 131414.09 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296250E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.878245E+11 | 141813.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.701035E+11 | 177232.03 | 03-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.609549E+11 | 176769.15 | 13-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239512E+11 | 175886.08 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.647567E+10 | 176031.15 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283325E+09 | 28450.77 | 12-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.388868E+09 | 35613.42 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.621826E+10 | 175630.89 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223811E+11 | 175927.35 | 13-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.648282E+11 | 176790.04 | 11-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255585E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.701035E+11 | 177232.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.690486E+11 | 198976.10 | 02-JAN-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.615016E+11 | 198369.72 | 08-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178373E+11 | 197489.13 | 20-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.590447E+10 | 197049.66 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78064712.40 | 17236.54 | 12-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127474E+09 | 22300.39 | 30-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.302620E+10 | 196605.33 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152154E+11 | 197332.14 | 24-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.633835E+11 | 198295.83 | 26-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.690486E+11 | 198976.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.651992E+11 | 186349.19 | 04-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.552256E+11 | 185763.44 | 13-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.212133E+11 | 184805.26 | 07-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.557957E+10 | 183763.52 | 17-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.207833E+09 | 23093.62 | 12-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.303817E+09 | 26850.36 | 29-SEP-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.539453E+10 | 183818.47 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185305E+11 | 184294.16 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.555357E+11 | 185754.02 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227190E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.651992E+11 | 186349.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.643082E+10 | 55742.49 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.590766E+10 | 81679.46 | 21-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189788E+10 | 74217.05 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.485297E+09 | 53856.55 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138693E+09 | 24111.96 | 04-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21981426.22 | 12401.96 | 10-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1471042.71 | 1491.01 | 03-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54821908.90 | 18803.20 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.356436E+09 | 49358.35 | 17-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.442916E+09 | 50581.51 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.541729E+10 | 77644.96 | 28-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.643082E+10 | 81679.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118023E+11 | 82108.80 | 02-JAN-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.998168E+10 | 81992.95 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.400704E+10 | 81978.58 | 13-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.694509E+09 | 81895.90 | 17-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.714698E+09 | 82210.33 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232705E+10 | 82144.55 | 20-NOV-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.980532E+10 | 82017.51 | 04-DEC-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118023E+11 | 82210.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152203E+11 | 15953.21 | 14-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137463E+11 | 15976.75 | 01-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.742365E+10 | 15998.16 | 13-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.246761E+10 | 15972.71 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189680E+09 | 15940.98 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 770808.28 | 2923.14 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136366E+09 | 15870.89 | 29-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.215146E+10 | 15989.30 | 16-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.519037E+10 | 15985.50 | 13-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140271E+11 | 16004.87 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.605537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152203E+11 | 16004.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106676E+11 | 17886.07 | 18-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.953244E+10 | 17927.67 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.460247E+10 | 17882.26 | 13-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167674E+10 | 17840.60 | 05-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.191640E+09 | 13411.21 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 550216.09 | 1776.05 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1450676.11 | 1274.93 | 31-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159736E+09 | 17835.01 | 29-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168810E+10 | 17906.80 | 16-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428039E+10 | 17944.00 | 20-NOV-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103721E+11 | 17908.92 | 13-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.431732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106676E+11 | 17944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122274E+11 | 21519.33 | 11-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112583E+11 | 21557.53 | 23-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.474281E+10 | 21516.63 | 28-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215586E+10 | 21544.53 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.289074E+09 | 17927.67 | 12-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20436693.68 | 8788.91 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112913E+09 | 21476.83 | 29-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156131E+10 | 21578.41 | 16-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.432778E+10 | 21585.14 | 14-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120505E+11 | 21568.99 | 13-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.487464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122274E+11 | 21585.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102525E+11 | 19844.86 | 14-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.872333E+10 | 19851.69 | 15-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.419882E+10 | 19806.61 | 21-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164570E+10 | 19725.03 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.229932E+09 | 10247.01 | 12-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10730538.06 | 2113.24 | 14-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2129417.94 | 545.22 | 31-AUG-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158778E+09 | 15870.08 | 29-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167150E+10 | 19722.00 | 16-OCT-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383236E+10 | 19848.80 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.899377E+10 | 19876.27 | 02-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.397195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102525E+11 | 19876.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8114121.25 | 8114121.25 | 4315.41 | 20-JAN-13:10 | 4315.41 | 0.00 |
February | 0.00 | 0.00 | 6770624.54 | 6770624.54 | 2096.89 | 23-FEB-14:30 | 2096.89 | 0.00 |
March | 0.00 | 0.00 | 0.600346E+10 | 0.586104E+10 | 103952.58 | 14-MAR-13:10 | 90576.65 | 0.04 |
April | 0.00 | 0.00 | 0.240630E+10 | 0.240630E+10 | 51313.59 | 07-APR-14:00 | 51313.59 | 0.01 |
May | 0.00 | 0.00 | 0.186031E+11 | 0.183628E+11 | 96479.75 | 10-MAY-14:30 | 88073.04 | 0.11 |
June | 0.00 | 0.00 | 0.840778E+11 | 0.663051E+11 | 206746.94 | 27-JUN-07:40 | 89427.70 | 0.45 |
July | 0.00 | 0.00 | 0.151040E+12 | 0.108254E+12 | 283341.76 | 20-JUL-05:02 | 113647.01 | 0.72 |
August | 0.00 | 0.00 | 0.130916E+12 | 0.101744E+12 | 262843.66 | 14-AUG-05:03 | 99841.47 | 0.71 |
September | 0.00 | 0.00 | 0.507913E+11 | 0.401864E+11 | 206976.94 | 16-SEP-05:03 | 93703.48 | 0.32 |
October | 0.00 | 0.00 | 0.668867E+10 | 0.668395E+10 | 77148.82 | 11-OCT-15:00 | 77148.82 | 0.07 |
November | 0.00 | 0.00 | 0.116199E+10 | 0.116199E+10 | 57388.05 | 27-NOV-06:02 | 57388.05 | 0.02 |
December | 0.00 | 0.00 | 25712958.61 | 25712958.61 | 10673.12 | 13-DEC-08:10 | 10673.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.451729E+12 | 0.351006E+12 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 6770624.54 | 6770624.54 | 2096.89 | 2096.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.151040E+12 | 0.108254E+12 | 283341.76 | 113647.01 | 0.72 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 574441.83 | 574441.83 | 171.20 | 13-JAN-14:40 | 171.20 | 0.00 |
February | 0.00 | 0.00 | 4002224.65 | 4002224.65 | 4540.44 | 18-FEB-13:40 | 4540.44 | 0.00 |
March | 0.00 | 0.00 | 0.413995E+11 | 0.405424E+11 | 761583.62 | 15-MAR-14:10 | 761583.62 | 0.04 |
April | 0.00 | 0.00 | 0.158866E+11 | 0.158866E+11 | 343285.97 | 07-APR-14:00 | 343285.97 | 0.01 |
May | 0.00 | 0.00 | 0.157391E+12 | 0.155342E+12 | 849844.41 | 10-MAY-14:40 | 767274.79 | 0.10 |
June | 0.00 | 0.00 | 0.686468E+12 | 0.547287E+12 | 1852483.89 | 27-JUN-05:03 | 781744.03 | 0.41 |
July | 0.00 | 0.00 | 0.117121E+13 | 0.856843E+12 | 2945249.34 | 20-JUL-03:02 | 1267500.17 | 0.59 |
August | 0.00 | 0.00 | 0.967985E+12 | 0.772383E+12 | 2820344.06 | 14-AUG-03:02 | 1084109.44 | 0.56 |
September | 0.00 | 0.00 | 0.430682E+12 | 0.344296E+12 | 1804221.17 | 16-SEP-05:03 | 811952.80 | 0.31 |
October | 0.00 | 0.00 | 0.510302E+11 | 0.509958E+11 | 613665.29 | 11-OCT-15:00 | 613665.29 | 0.07 |
November | 0.00 | 0.00 | 0.749077E+10 | 0.749077E+10 | 192901.12 | 16-NOV-13:10 | 192901.12 | 0.02 |
December | 0.00 | 0.00 | 3380673.32 | 3380673.32 | 8228.29 | 01-DEC-13:30 | 8228.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.352955E+13 | 0.279107E+13 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 574441.83 | 574441.83 | 171.20 | 171.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.117121E+13 | 0.856843E+12 | 2945249.34 | 1267500.17 | 0.59 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1420301.39 | 1420301.39 | 1422.59 | 31-JAN-05:21 | 1422.59 | 0.00 |
February | 0.00 | 0.00 | 1186414.48 | 1186414.48 | 1109.39 | 08-FEB-04:42 | 1109.39 | 0.00 |
March | 0.00 | 0.00 | 0.431531E+10 | 0.430281E+10 | 93557.51 | 15-MAR-14:00 | 93557.51 | 0.04 |
April | 0.00 | 0.00 | 0.149805E+10 | 0.149805E+10 | 32502.08 | 07-APR-14:00 | 32502.08 | 0.01 |
May | 0.00 | 0.00 | 0.157472E+11 | 0.155861E+11 | 99082.34 | 10-MAY-14:50 | 91013.03 | 0.10 |
June | 0.00 | 0.00 | 0.749270E+11 | 0.594912E+11 | 301382.14 | 27-JUN-15:00 | 126060.10 | 0.40 |
July | 0.00 | 0.00 | 0.129844E+12 | 0.949940E+11 | 312411.20 | 20-JUL-03:02 | 134643.81 | 0.59 |
August | 0.00 | 0.00 | 0.104682E+12 | 0.833492E+11 | 299129.32 | 14-AUG-03:02 | 114971.08 | 0.55 |
September | 0.00 | 0.00 | 0.426268E+11 | 0.339424E+11 | 177585.11 | 15-SEP-12:40 | 96634.51 | 0.30 |
October | 0.00 | 0.00 | 0.425789E+10 | 0.425789E+10 | 59945.95 | 11-OCT-15:00 | 59945.95 | 0.07 |
November | 0.00 | 0.00 | 0.699632E+09 | 0.699632E+09 | 16121.93 | 16-NOV-18:00 | 16121.93 | 0.02 |
December | 0.00 | 0.00 | 2767290.88 | 2767290.88 | 562.71 | 26-DEC-06:05 | 562.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.378603E+12 | 0.298127E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 1186414.48 | 1186414.48 | 562.71 | 562.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.129844E+12 | 0.949940E+11 | 312411.20 | 134643.81 | 0.59 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 95009.62 | 95009.62 | 99.04 | 23-JAN-15:00 | 99.04 | 0.00 |
February | 0.00 | 0.00 | 361799.24 | 361799.24 | 245.84 | 28-FEB-09:50 | 245.84 | 0.00 |
March | 0.00 | 0.00 | 0.335824E+10 | 0.334588E+10 | 58075.26 | 16-MAR-04:02 | 58075.26 | 0.04 |
April | 0.00 | 0.00 | 0.574047E+09 | 0.574047E+09 | 25222.68 | 07-APR-14:00 | 25222.68 | 0.00 |
May | 0.00 | 0.00 | 0.798655E+10 | 0.795815E+10 | 78103.06 | 24-MAY-05:03 | 49847.18 | 0.07 |
June | 0.00 | 0.00 | 0.401057E+11 | 0.338481E+11 | 126881.96 | 27-JUN-05:03 | 53880.34 | 0.31 |
July | 0.00 | 0.00 | 0.770569E+11 | 0.582156E+11 | 174696.92 | 20-JUL-03:02 | 75636.00 | 0.48 |
August | 0.00 | 0.00 | 0.672626E+11 | 0.551561E+11 | 167870.79 | 14-AUG-03:03 | 64528.96 | 0.48 |
September | 0.00 | 0.00 | 0.289325E+11 | 0.242489E+11 | 121004.21 | 16-SEP-05:03 | 55270.31 | 0.25 |
October | 0.00 | 0.00 | 0.279682E+10 | 0.277795E+10 | 59032.12 | 26-OCT-05:03 | 31274.09 | 0.04 |
November | 0.00 | 0.00 | 0.538739E+09 | 0.538739E+09 | 49149.55 | 27-NOV-04:02 | 49149.55 | 0.01 |
December | 0.00 | 0.00 | 1384225.75 | 1384225.75 | 9041.30 | 01-DEC-06:02 | 9041.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.228614E+12 | 0.186665E+12 | 0.14 | |||
Minimum of Months | 0.00 | 0.00 | 95009.62 | 95009.62 | 99.04 | 99.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.770569E+11 | 0.582156E+11 | 174696.92 | 75636.00 | 0.48 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.316085E+12 | 0.316077E+12 | 124177.62 | 19-JAN-22:10 | 124177.62 | 0.00 |
February | 0.00 | 0.00 | 0.505287E+12 | 0.505287E+12 | 215859.26 | 17-FEB-22:03 | 215859.26 | 0.00 |
March | 0.00 | 0.00 | 0.811787E+12 | 0.811278E+12 | 394296.99 | 31-MAR-24:00 | 394296.99 | 0.00 |
April | 0.00 | 0.00 | 0.102639E+13 | 0.102637E+13 | 400590.23 | 21-APR-21:03 | 400590.23 | 0.00 |
May | 0.00 | 0.00 | 0.331400E+12 | 0.330439E+12 | 212798.28 | 31-MAY-24:00 | 212048.08 | 0.00 |
June | 0.00 | 0.00 | 0.565166E+12 | 0.560407E+12 | 304142.99 | 30-JUN-24:00 | 304142.99 | 0.00 |
July | 0.00 | 0.00 | 0.834982E+12 | 0.827609E+12 | 396896.39 | 31-JUL-23:53 | 396261.67 | 0.00 |
August | 0.00 | 0.00 | 0.107628E+13 | 0.107150E+13 | 416226.20 | 15-AUG-15:00 | 403357.50 | 0.00 |
September | 0.00 | 0.00 | 0.328970E+12 | 0.325098E+12 | 211456.61 | 30-SEP-24:00 | 211456.61 | 0.00 |
October | 0.00 | 0.00 | 0.576107E+12 | 0.575278E+12 | 304410.11 | 31-OCT-24:00 | 304410.11 | 0.00 |
November | 0.00 | 0.00 | 0.790879E+12 | 0.790857E+12 | 309819.05 | 16-NOV-17:00 | 309028.96 | 0.00 |
December | 0.00 | 0.00 | 0.105560E+13 | 0.105558E+13 | 400851.02 | 26-DEC-22:01 | 400851.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.821893E+13 | 0.819578E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.316085E+12 | 0.316077E+12 | 124177.62 | 124177.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107628E+13 | 0.107150E+13 | 416226.20 | 403357.50 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.296203E+10 | 0.296203E+10 | 2133.01 | 15-JAN-16:30 | 2133.01 | 0.00 |
February | 0.00 | 0.00 | 0.751377E+10 | 0.751377E+10 | 4185.36 | 28-FEB-16:55 | 4185.36 | 0.00 |
March | 0.00 | 0.00 | 0.147959E+11 | 0.147742E+11 | 7549.50 | 31-MAR-24:00 | 7549.50 | 0.00 |
April | 0.00 | 0.00 | 0.197859E+11 | 0.197831E+11 | 8571.65 | 02-APR-17:44 | 8571.65 | 0.00 |
May | 0.00 | 0.00 | 0.559877E+10 | 0.556130E+10 | 4066.31 | 31-MAY-24:00 | 4059.08 | 0.00 |
June | 0.00 | 0.00 | 0.108957E+11 | 0.107074E+11 | 5933.27 | 30-JUN-24:00 | 5933.27 | 0.00 |
July | 0.00 | 0.00 | 0.165578E+11 | 0.162458E+11 | 7833.53 | 31-JUL-23:45 | 7814.91 | 0.00 |
August | 0.00 | 0.00 | 0.214481E+11 | 0.212257E+11 | 8740.26 | 14-AUG-15:30 | 8373.21 | 0.00 |
September | 0.00 | 0.00 | 0.571184E+10 | 0.557001E+10 | 3750.03 | 30-SEP-24:00 | 3750.03 | 0.00 |
October | 0.00 | 0.00 | 0.102706E+11 | 0.102373E+11 | 5709.43 | 31-OCT-24:00 | 5709.43 | 0.00 |
November | 0.00 | 0.00 | 0.144854E+11 | 0.144839E+11 | 6121.56 | 15-NOV-16:10 | 6121.56 | 0.00 |
December | 0.00 | 0.00 | 0.191878E+11 | 0.191873E+11 | 7766.99 | 04-DEC-16:10 | 7766.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.149213E+12 | 0.148252E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.296203E+10 | 0.296203E+10 | 2133.01 | 2133.01 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.214481E+11 | 0.212257E+11 | 8740.26 | 8571.65 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.538486E+10 | 0.538486E+10 | 13535.17 | 12-JAN-16:40 | 13535.17 | 0.00 |
February | 0.00 | 0.00 | 0.474289E+11 | 0.474289E+11 | 35862.96 | 28-FEB-16:55 | 35862.96 | 0.00 |
March | 0.00 | 0.00 | 0.122646E+12 | 0.122430E+12 | 66382.30 | 31-MAR-24:00 | 66382.30 | 0.00 |
April | 0.00 | 0.00 | 0.176153E+12 | 0.176124E+12 | 78352.94 | 24-APR-18:00 | 78352.94 | 0.00 |
May | 0.00 | 0.00 | 0.471718E+11 | 0.468060E+11 | 38224.84 | 31-MAY-24:00 | 38158.88 | 0.00 |
June | 0.00 | 0.00 | 0.101323E+12 | 0.994565E+11 | 56936.09 | 30-JUN-24:00 | 56936.09 | 0.00 |
July | 0.00 | 0.00 | 0.157328E+12 | 0.154221E+12 | 75684.66 | 31-JUL-23:53 | 75501.85 | 0.00 |
August | 0.00 | 0.00 | 0.203511E+12 | 0.201288E+12 | 83032.01 | 04-AUG-18:30 | 83032.01 | 0.00 |
September | 0.00 | 0.00 | 0.488572E+11 | 0.474813E+11 | 31424.60 | 30-SEP-24:00 | 31424.60 | 0.00 |
October | 0.00 | 0.00 | 0.841202E+11 | 0.837918E+11 | 49281.94 | 31-OCT-24:00 | 49281.94 | 0.00 |
November | 0.00 | 0.00 | 0.119045E+12 | 0.119028E+12 | 55903.94 | 15-NOV-16:20 | 55903.94 | 0.00 |
December | 0.00 | 0.00 | 0.153667E+12 | 0.153661E+12 | 68685.31 | 04-DEC-16:20 | 68685.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126664E+13 | 0.125710E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.538486E+10 | 0.538486E+10 | 13535.17 | 13535.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203511E+12 | 0.201288E+12 | 83032.01 | 83032.01 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.145070E+09 | 0.145070E+09 | 1119.15 | 12-JAN-16:30 | 1119.15 | 0.00 |
February | 0.00 | 0.00 | 0.326160E+10 | 0.326160E+10 | 3530.13 | 28-FEB-16:55 | 3530.13 | 0.00 |
March | 0.00 | 0.00 | 0.107358E+11 | 0.107144E+11 | 6233.22 | 31-MAR-23:20 | 6233.22 | 0.00 |
April | 0.00 | 0.00 | 0.165620E+11 | 0.165591E+11 | 7835.71 | 24-APR-18:00 | 7835.71 | 0.00 |
May | 0.00 | 0.00 | 0.424174E+10 | 0.420576E+10 | 3730.22 | 31-MAY-24:00 | 3723.72 | 0.00 |
June | 0.00 | 0.00 | 0.100416E+11 | 0.985522E+10 | 5633.18 | 30-JUN-24:00 | 5633.18 | 0.00 |
July | 0.00 | 0.00 | 0.157743E+11 | 0.154639E+11 | 7572.61 | 31-JUL-23:53 | 7554.23 | 0.00 |
August | 0.00 | 0.00 | 0.203175E+11 | 0.200957E+11 | 8391.24 | 10-AUG-18:00 | 8203.85 | 0.00 |
September | 0.00 | 0.00 | 0.447376E+10 | 0.433781E+10 | 2775.02 | 21-SEP-17:20 | 2672.30 | 0.00 |
October | 0.00 | 0.00 | 0.706680E+10 | 0.703451E+10 | 4536.23 | 31-OCT-23:20 | 4536.23 | 0.00 |
November | 0.00 | 0.00 | 0.102147E+11 | 0.102131E+11 | 5473.84 | 15-NOV-16:20 | 5473.84 | 0.00 |
December | 0.00 | 0.00 | 0.135336E+11 | 0.135331E+11 | 6534.02 | 01-DEC-13:30 | 6440.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.116369E+12 | 0.115419E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.145070E+09 | 0.145070E+09 | 1119.15 | 1119.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203175E+11 | 0.200957E+11 | 8391.24 | 8203.85 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 155690.49 | 2078711.27 | 02-JAN-04:11 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 148296.69 | 1844852.23 | 27-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 53477.67 | 1621243.40 | 06-MAR-06:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 17586.27 | 1400562.56 | 17-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1252.16 | 302925.88 | 04-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 129.29 | 138199.58 | 10-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 7.82 | 11-JUL-08:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 5.96 | 8699.14 | 31-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 815.19 | 275899.52 | 30-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13013.50 | 1443075.43 | 30-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 44751.34 | 1434615.82 | 25-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 134454.19 | 1800162.23 | 11-DEC-05:01 |
Annual Sum or Average | 0.00 | 46973.93 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 7.82 | ||
Maximum of Months | 0.00 | 0.00 | 155690.49 | 2078711.27 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1076.31 | 29610.65 | 20-JAN-07:20 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1272.78 | 29703.68 | 04-FEB-07:20 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 36192.05 | 1465211.15 | 14-MAR-13:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19053.74 | 932588.23 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 144663.35 | 1465913.93 | 10-MAY-12:30 | 64.25 | 181112.11 | 14-MAY-16:53 |
June | 511676.46 | 2541277.83 | 27-JUN-05:03 | 13.85 | 90364.44 | 20-JUN-01:02 |
July | 747596.23 | 3545739.36 | 20-JUL-05:04 | 30.69 | 100685.77 | 09-JUL-02:42 |
August | 664224.61 | 2928508.75 | 15-AUG-05:03 | 14.09 | 64720.34 | 20-AUG-02:32 |
September | 340899.54 | 2336830.05 | 14-SEP-05:03 | 8.63 | 70510.25 | 17-SEP-20:03 |
October | 51391.22 | 1417005.49 | 11-OCT-13:50 | 35.96 | 138048.90 | 23-OCT-01:13 |
November | 10908.48 | 736193.12 | 16-NOV-13:00 | 16.60 | 148441.33 | 06-NOV-04:02 |
December | 2007.74 | 142097.69 | 01-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 212530.09 | 15.53 | ||||
Minimum of Months | 1076.31 | 29610.65 | 0.00 | 0.00 | ||
Maximum of Months | 747596.23 | 3545739.36 | 64.25 | 181112.11 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.08 | 113.99 | 20-JAN-13:10 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 0.34 | 329.47 | 18-FEB-13:40 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 25232.79 | 1206738.21 | 15-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 9808.20 | 642483.43 | 08-APR-13:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 94448.29 | 2145747.30 | 24-MAY-04:02 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 405366.55 | 3441075.96 | 27-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 642555.43 | 4389555.67 | 20-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 553855.55 | 4102010.30 | 14-AUG-03:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 263397.25 | 3625778.32 | 16-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 32913.64 | 1405849.12 | 11-OCT-14:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5151.73 | 586214.57 | 27-NOV-06:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 25.96 | 141369.39 | 01-DEC-05:01 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 170771.80 | 0.00 | ||||
Minimum of Months | 0.08 | 113.99 | 0.00 | 0.00 | ||
Maximum of Months | 642555.43 | 4389555.67 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 155490.25 | 215318.95 | 11-JAN-12:00 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 294159.28 | 377271.87 | 28-FEB-15:35 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 468075.71 | 1141134.69 | 15-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 614094.68 | 1049569.46 | 08-APR-13:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 221328.34 | 706143.01 | 10-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 553232.22 | 1197401.36 | 27-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 917217.31 | 1487677.50 | 21-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1053741.67 | 1619770.38 | 10-AUG-14:10 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 285896.19 | 752430.16 | 16-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 335930.31 | 709182.99 | 11-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 462031.06 | 744882.43 | 05-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 577420.32 | 699349.06 | 01-DEC-11:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 496710.70 | 0.00 | ||||
Minimum of Months | 155490.25 | 215318.95 | 0.00 | 0.00 | ||
Maximum of Months | 1053741.67 | 1619770.38 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 16761.00 | 56740.66 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17077.18 | 56970.11 | 16-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17827.08 | 56793.38 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 16191.37 | 55044.47 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15821.41 | 52532.11 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15254.35 | 49343.32 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13531.39 | 46496.99 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 14430.45 | 45035.37 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 13844.48 | 46449.09 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14445.86 | 49309.36 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15477.65 | 52358.96 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15779.95 | 54977.25 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 15527.97 | ||||
Minimum of Months | 0.00 | 0.00 | 13531.39 | 45035.37 | ||
Maximum of Months | 0.00 | 0.00 | 17827.08 | 56970.11 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 36.95 | 28920.69 | 19-JAN-14:20 | 1287.60 | 146080.59 | 19-JAN-14:50 |
February | 52.96 | 29448.83 | 23-FEB-15:00 | 1496.39 | 155711.86 | 05-FEB-07:53 |
March | 24699.82 | 1388443.91 | 14-MAR-14:00 | 1863.27 | 137957.44 | 20-MAR-15:10 |
April | 9406.30 | 556660.09 | 07-APR-14:00 | 2334.54 | 147026.69 | 24-APR-05:30 |
May | 91850.88 | 1224272.06 | 10-MAY-15:00 | 573.59 | 110788.58 | 20-MAY-05:50 |
June | 597958.48 | 5635460.37 | 27-JUN-07:40 | 243.16 | 81114.21 | 15-JUN-08:20 |
July | 1175382.18 | 6334293.94 | 05-JUL-16:00 | 100.20 | 45088.67 | 06-JUL-03:30 |
August | 849935.77 | 6596719.57 | 14-AUG-10:10 | 287.85 | 48087.86 | 12-AUG-22:10 |
September | 344695.25 | 4385419.14 | 15-SEP-11:00 | 187.04 | 55716.75 | 11-SEP-10:30 |
October | 31119.39 | 1007330.52 | 11-OCT-12:50 | 1608.56 | 118418.69 | 17-OCT-12:20 |
November | 5201.41 | 424852.97 | 16-NOV-13:00 | 3654.38 | 145588.61 | 22-NOV-16:40 |
December | 83.84 | 30001.27 | 26-DEC-07:00 | 2386.84 | 147546.64 | 26-DEC-07:20 |
Annual Sum or Average | 263248.49 | 1331.01 | ||||
Minimum of Months | 36.95 | 28920.69 | 100.20 | 45088.67 | ||
Maximum of Months | 1175382.18 | 6596719.57 | 3654.38 | 155711.86 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139206E+11 | 0.76 | 9827.79 | 02-JAN-04:01 | 1.42 |
February | 0.127605E+11 | 0.77 | 9827.79 | 01-FEB-06:01 | 1.42 |
March | 0.156108E+11 | 0.85 | 9827.79 | 01-MAR-05:01 | 1.43 |
April | 0.145432E+11 | 0.81 | 9827.79 | 01-APR-04:02 | 1.43 |
May | 0.155048E+11 | 0.84 | 9827.79 | 01-MAY-03:02 | 1.42 |
June | 0.154591E+11 | 0.86 | 9827.79 | 01-JUN-03:02 | 1.42 |
July | 0.152447E+11 | 0.82 | 9827.79 | 01-JUL-03:02 | 1.42 |
August | 0.168265E+11 | 0.90 | 9827.79 | 01-AUG-03:02 | 1.42 |
September | 0.157965E+11 | 0.88 | 9827.79 | 01-SEP-03:02 | 1.42 |
October | 0.154621E+11 | 0.84 | 9827.79 | 02-OCT-01:00 | 1.42 |
November | 0.148881E+11 | 0.83 | 9827.79 | 01-NOV-03:02 | 1.43 |
December | 0.143013E+11 | 0.78 | 9827.79 | 01-DEC-05:01 | 1.42 |
Annual Sum or Average | 0.180318E+12 | 0.83 | |||
Minimum of Months | 0.127605E+11 | 0.76 | 9827.79 | 1.42 | |
Maximum of Months | 0.168265E+11 | 0.90 | 9827.79 | 1.43 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.397898E+10 | 0.32 | 15121.84 | 05-JAN-13:07 | 1.50 |
February | 0.388377E+10 | 0.33 | 20460.50 | 28-FEB-14:47 | 1.81 |
March | 0.693053E+10 | 0.43 | 20460.50 | 06-MAR-15:00 | 1.81 |
April | 0.795446E+10 | 0.47 | 14377.90 | 22-APR-07:17 | 1.45 |
May | 0.815655E+10 | 0.47 | 14377.90 | 01-MAY-06:50 | 1.44 |
June | 0.116051E+11 | 0.61 | 22292.00 | 19-JUN-05:03 | 1.89 |
July | 0.137845E+11 | 0.68 | 22292.00 | 17-JUL-05:02 | 1.89 |
August | 0.149289E+11 | 0.73 | 22292.00 | 09-AUG-05:02 | 1.90 |
September | 0.882727E+10 | 0.50 | 17840.18 | 16-SEP-05:03 | 1.64 |
October | 0.704380E+10 | 0.42 | 13825.46 | 17-OCT-08:17 | 1.41 |
November | 0.603971E+10 | 0.39 | 12095.81 | 04-NOV-05:02 | 1.29 |
December | 0.509108E+10 | 0.35 | 15769.52 | 04-DEC-16:10 | 1.54 |
Annual Sum or Average | 0.982246E+11 | 0.48 | |||
Minimum of Months | 0.388377E+10 | 0.32 | 12095.81 | 1.29 | |
Maximum of Months | 0.149289E+11 | 0.73 | 22292.00 | 1.90 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.404259E+11 | 0.38 | 51133.42 | 02-JAN-06:01 | 0.82 |
February | 0.361505E+11 | 0.37 | 51133.42 | 06-FEB-05:11 | 0.83 |
March | 0.422895E+11 | 0.36 | 149851.95 | 23-MAR-12:07 | 1.56 |
April | 0.441332E+11 | 0.35 | 149851.95 | 05-APR-11:17 | 1.56 |
May | 0.623710E+11 | 0.42 | 144780.16 | 08-MAY-07:17 | 1.53 |
June | 0.890737E+11 | 0.53 | 199880.05 | 19-JUN-05:03 | 1.86 |
July | 0.101840E+12 | 0.55 | 207977.95 | 17-JUL-05:02 | 1.90 |
August | 0.101319E+12 | 0.56 | 207977.95 | 14-AUG-03:02 | 1.90 |
September | 0.687924E+11 | 0.44 | 139165.20 | 21-SEP-16:00 | 1.47 |
October | 0.451759E+11 | 0.34 | 165654.08 | 17-OCT-10:20 | 1.66 |
November | 0.360928E+11 | 0.32 | 149851.95 | 03-NOV-10:20 | 1.56 |
December | 0.376334E+11 | 0.35 | 51133.42 | 11-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.705297E+12 | 0.41 | |||
Minimum of Months | 0.360928E+11 | 0.32 | 51133.42 | 0.82 | |
Maximum of Months | 0.101840E+12 | 0.56 | 207977.95 | 1.90 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.500951E+10 | 0.44 | 4995.60 | 02-JAN-04:01 | 0.78 |
February | 0.459935E+10 | 0.45 | 4995.60 | 01-FEB-05:01 | 0.78 |
March | 0.457883E+10 | 0.39 | 9803.47 | 15-MAR-14:00 | 1.13 |
April | 0.396649E+10 | 0.34 | 13761.62 | 13-APR-12:47 | 1.41 |
May | 0.542711E+10 | 0.37 | 11682.94 | 31-MAY-16:00 | 1.26 |
June | 0.888668E+10 | 0.50 | 18218.33 | 12-JUN-15:20 | 1.66 |
July | 0.106430E+11 | 0.54 | 22318.45 | 17-JUL-05:02 | 1.89 |
August | 0.100546E+11 | 0.52 | 22318.45 | 14-AUG-03:02 | 1.89 |
September | 0.601147E+10 | 0.39 | 14931.48 | 21-SEP-15:50 | 1.47 |
October | 0.387811E+10 | 0.32 | 9731.23 | 12-OCT-05:02 | 1.13 |
November | 0.359134E+10 | 0.33 | 4995.60 | 13-NOV-05:01 | 0.78 |
December | 0.491366E+10 | 0.43 | 4995.60 | 02-DEC-06:01 | 0.78 |
Annual Sum or Average | 0.715602E+11 | 0.42 | |||
Minimum of Months | 0.359134E+10 | 0.32 | 4995.60 | 0.78 | |
Maximum of Months | 0.106430E+11 | 0.54 | 22318.45 | 1.89 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.967141E+11 | 1.38 | 36108.90 | 01-JAN-00:03 | 1.38 |
February | 0.873547E+11 | 1.38 | 36108.90 | 01-FEB-00:03 | 1.38 |
March | 0.967141E+11 | 1.38 | 36108.90 | 01-MAR-00:10 | 1.38 |
April | 0.935943E+11 | 1.38 | 36108.90 | 01-APR-00:10 | 1.38 |
May | 0.967141E+11 | 1.38 | 36108.90 | 01-MAY-00:10 | 1.38 |
June | 0.935943E+11 | 1.38 | 36108.90 | 01-JUN-00:10 | 1.38 |
July | 0.967141E+11 | 1.38 | 36108.90 | 01-JUL-00:10 | 1.38 |
August | 0.967141E+11 | 1.38 | 36108.90 | 01-AUG-00:03 | 1.38 |
September | 0.935943E+11 | 1.38 | 36108.90 | 01-SEP-00:10 | 1.38 |
October | 0.967141E+11 | 1.38 | 36108.90 | 01-OCT-00:10 | 1.38 |
November | 0.935943E+11 | 1.38 | 36108.90 | 01-NOV-00:10 | 1.38 |
December | 0.967141E+11 | 1.38 | 36108.90 | 01-DEC-00:10 | 1.38 |
Annual Sum or Average | 0.113873E+13 | 1.38 | |||
Minimum of Months | 0.873547E+11 | 1.38 | 36108.90 | 1.38 | |
Maximum of Months | 0.967141E+11 | 1.38 | 36108.90 | 1.38 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150158E+10 | 0.94 | 560.63 | 01-JAN-00:03 | 0.94 |
February | 0.135626E+10 | 0.94 | 560.63 | 01-FEB-00:03 | 0.95 |
March | 0.150158E+10 | 0.94 | 560.63 | 01-MAR-00:10 | 0.94 |
April | 0.145314E+10 | 0.94 | 560.63 | 01-APR-00:10 | 0.94 |
May | 0.150158E+10 | 0.94 | 560.63 | 01-MAY-00:10 | 0.94 |
June | 0.145314E+10 | 0.94 | 560.63 | 01-JUN-00:10 | 0.94 |
July | 0.150158E+10 | 0.94 | 560.63 | 01-JUL-00:10 | 0.94 |
August | 0.150158E+10 | 0.94 | 560.63 | 01-AUG-00:03 | 0.94 |
September | 0.145314E+10 | 0.94 | 560.63 | 01-SEP-00:10 | 0.94 |
October | 0.150158E+10 | 0.94 | 560.63 | 01-OCT-00:10 | 0.94 |
November | 0.145314E+10 | 0.94 | 560.63 | 01-NOV-00:10 | 0.94 |
December | 0.150158E+10 | 0.94 | 560.63 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.176799E+11 | 0.94 | |||
Minimum of Months | 0.135626E+10 | 0.94 | 560.63 | 0.94 | |
Maximum of Months | 0.150158E+10 | 0.94 | 560.63 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143530E+11 | 0.94 | 5358.78 | 01-JAN-00:03 | 0.94 |
February | 0.129640E+11 | 0.94 | 5358.78 | 01-FEB-00:03 | 0.95 |
March | 0.143530E+11 | 0.94 | 5358.78 | 01-MAR-00:10 | 0.94 |
April | 0.138900E+11 | 0.94 | 5358.78 | 01-APR-00:10 | 0.94 |
May | 0.143530E+11 | 0.94 | 5358.78 | 01-MAY-00:10 | 0.94 |
June | 0.138900E+11 | 0.94 | 5358.78 | 01-JUN-00:10 | 0.94 |
July | 0.143530E+11 | 0.94 | 5358.78 | 01-JUL-00:10 | 0.94 |
August | 0.143530E+11 | 0.94 | 5358.78 | 01-AUG-00:03 | 0.94 |
September | 0.138900E+11 | 0.94 | 5358.78 | 01-SEP-00:10 | 0.94 |
October | 0.143530E+11 | 0.94 | 5358.78 | 01-OCT-00:10 | 0.94 |
November | 0.138900E+11 | 0.94 | 5358.78 | 01-NOV-00:10 | 0.94 |
December | 0.143530E+11 | 0.94 | 5358.78 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.168994E+12 | 0.94 | |||
Minimum of Months | 0.129640E+11 | 0.94 | 5358.78 | 0.94 | |
Maximum of Months | 0.143530E+11 | 0.94 | 5358.78 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146024E+10 | 0.94 | 545.19 | 01-JAN-00:03 | 0.94 |
February | 0.131893E+10 | 0.94 | 545.19 | 01-FEB-00:03 | 0.95 |
March | 0.146024E+10 | 0.94 | 545.19 | 01-MAR-00:10 | 0.94 |
April | 0.141314E+10 | 0.94 | 545.19 | 01-APR-00:10 | 0.94 |
May | 0.146024E+10 | 0.94 | 545.19 | 01-MAY-00:10 | 0.94 |
June | 0.141314E+10 | 0.94 | 545.19 | 01-JUN-00:10 | 0.94 |
July | 0.146024E+10 | 0.94 | 545.19 | 01-JUL-00:10 | 0.94 |
August | 0.146024E+10 | 0.94 | 545.19 | 01-AUG-00:03 | 0.94 |
September | 0.141314E+10 | 0.94 | 545.19 | 01-SEP-00:10 | 0.94 |
October | 0.146024E+10 | 0.94 | 545.19 | 01-OCT-00:10 | 0.94 |
November | 0.141314E+10 | 0.94 | 545.19 | 01-NOV-00:10 | 0.94 |
December | 0.146024E+10 | 0.94 | 545.19 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.171932E+11 | 0.94 | |||
Minimum of Months | 0.131893E+10 | 0.94 | 545.19 | 0.94 | |
Maximum of Months | 0.146024E+10 | 0.94 | 545.19 | 0.95 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.186301E+10 | 0.167671E+10 | 5845.62 | 02-JAN-06:01 | 5261.06 | 5261.06 | 49.03 | 11.65 |
February | 0.161514E+10 | 0.145363E+10 | 5870.57 | 21-FEB-07:10 | 5283.51 | 5283.51 | 47.44 | 11.82 |
March | 0.637398E+09 | 0.573658E+09 | 5759.03 | 06-MAR-06:03 | 5183.13 | 5183.13 | 47.44 | 11.16 |
April | 0.198813E+09 | 0.178932E+09 | 4452.23 | 17-APR-04:01 | 4007.01 | 4007.01 | 31.01 | 6.62 |
May | 14291249.97 | 12862124.98 | 1233.25 | 04-MAY-06:10 | 1109.92 | 1109.92 | 26.75 | 1.35 |
June | 1413184.20 | 1271865.78 | 574.58 | 10-JUN-06:10 | 517.12 | 517.12 | 25.07 | 0.61 |
July | 20.35 | 18.31 | 0.03 | 11-JUL-08:30 | 0.03 | 0.03 | 25.28 | 0.00 |
August | 69217.29 | 62295.56 | 37.61 | 31-AUG-06:10 | 33.85 | 33.85 | 25.20 | 0.04 |
September | 8670460.18 | 7803414.16 | 1061.21 | 30-SEP-06:10 | 955.09 | 955.09 | 22.63 | 1.15 |
October | 0.147367E+09 | 0.132630E+09 | 4513.86 | 16-OCT-05:01 | 4062.47 | 4062.47 | 32.25 | 6.77 |
November | 0.515060E+09 | 0.463554E+09 | 4612.29 | 14-NOV-06:01 | 4151.06 | 4151.06 | 34.17 | 7.01 |
December | 0.163230E+10 | 0.146907E+10 | 5819.62 | 26-DEC-07:10 | 5237.66 | 5237.66 | 46.52 | 11.51 |
Annual Sum or Average | 0.663353E+10 | 0.597018E+10 | ||||||
Minimum of Months | 20.35 | 18.31 | 0.03 | 0.03 | 0.03 | 22.63 | 0.00 | |
Maximum of Months | 0.186301E+10 | 0.167671E+10 | 5870.57 | 5283.51 | 5283.51 | 49.03 | 11.82 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1377.18 | 1239.47 | 0.50 | 20-JAN-13:10 | 0.45 | 0.45 | 6.76 | 0.12 |
February | 1533.34 | 1380.00 | 0.59 | 18-FEB-13:40 | 0.53 | 0.53 | 6.83 | 0.14 |
March | 54097878.41 | 48688090.57 | 1832.31 | 15-MAR-13:30 | 1649.08 | 1649.08 | 7.31 | 39.03 |
April | 7155754.86 | 6440179.37 | 362.17 | 08-APR-13:40 | 325.96 | 325.96 | 8.36 | 17.83 |
May | 0.146571E+09 | 0.131914E+09 | 4300.23 | 31-MAY-15:40 | 3870.21 | 3870.21 | 8.75 | 56.84 |
June | 0.973586E+09 | 0.876228E+09 | 19697.87 | 27-JUN-05:03 | 17728.08 | 17728.08 | 8.13 | 106.23 |
July | 0.189266E+10 | 0.170339E+10 | 23680.57 | 17-JUL-05:02 | 21312.52 | 21312.52 | 7.91 | 114.23 |
August | 0.179420E+10 | 0.161478E+10 | 23680.57 | 15-AUG-05:03 | 21312.52 | 21312.52 | 8.08 | 114.23 |
September | 0.670862E+09 | 0.603775E+09 | 23245.66 | 16-SEP-05:03 | 20921.09 | 20921.09 | 8.19 | 113.39 |
October | 71598852.75 | 64438967.47 | 6085.89 | 11-OCT-14:30 | 5477.31 | 5477.31 | 8.70 | 65.86 |
November | 4997790.98 | 4498011.89 | 438.10 | 27-NOV-06:02 | 394.29 | 394.29 | 8.23 | 19.66 |
December | 15359.60 | 13823.64 | 41.72 | 01-DEC-06:02 | 37.55 | 37.55 | 8.44 | 5.08 |
Annual Sum or Average | 0.561574E+10 | 0.505417E+10 | ||||||
Minimum of Months | 1377.18 | 1239.47 | 0.50 | 0.45 | 0.45 | 6.76 | 0.12 | |
Maximum of Months | 0.189266E+10 | 0.170339E+10 | 23680.57 | 21312.52 | 21312.52 | 8.75 | 114.23 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.161212E+10 | 0.145090E+10 | 16298.70 | 02-JAN-05:09 | 14668.83 | 14668.83 | 8.43 | 114.23 |
February | 0.172103E+10 | 0.154893E+10 | 16298.70 | 01-FEB-12:30 | 14668.83 | 14668.83 | 8.43 | 114.23 |
March | 0.431031E+10 | 0.387928E+10 | 16298.70 | 01-MAR-17:05 | 14668.83 | 14668.83 | 8.43 | 114.23 |
April | 0.489941E+10 | 0.440947E+10 | 16298.70 | 01-APR-06:30 | 14668.83 | 14668.83 | 8.43 | 114.23 |
May | 0.129402E+11 | 0.116462E+11 | 16298.70 | 01-MAY-07:10 | 14668.83 | 14668.83 | 8.52 | 114.23 |
June | 0.263107E+11 | 0.236796E+11 | 16298.70 | 01-JUN-03:02 | 14668.83 | 14668.83 | 8.70 | 114.23 |
July | 0.335113E+11 | 0.301602E+11 | 16298.70 | 01-JUL-03:02 | 14668.83 | 14668.83 | 8.57 | 114.23 |
August | 0.330357E+11 | 0.297321E+11 | 16298.70 | 01-AUG-00:03 | 14668.83 | 14668.83 | 8.00 | 114.23 |
September | 0.195242E+11 | 0.175718E+11 | 16298.70 | 01-SEP-03:02 | 14668.83 | 14668.83 | 8.63 | 114.23 |
October | 0.743011E+10 | 0.668710E+10 | 16298.70 | 02-OCT-03:02 | 14668.83 | 14668.83 | 8.58 | 114.23 |
November | 0.481785E+10 | 0.433606E+10 | 16298.70 | 01-NOV-06:20 | 14668.83 | 14668.83 | 8.45 | 114.23 |
December | 0.296026E+10 | 0.266423E+10 | 16298.70 | 01-DEC-05:01 | 14668.83 | 14668.83 | 8.53 | 114.23 |
Annual Sum or Average | 0.153073E+12 | 0.137766E+12 | ||||||
Minimum of Months | 0.161212E+10 | 0.145090E+10 | 16298.70 | 14668.83 | 14668.83 | 8.00 | 114.23 | |
Maximum of Months | 0.335113E+11 | 0.301602E+11 | 16298.70 | 14668.83 | 14668.83 | 8.70 | 114.23 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.916181E+10 | 0.824563E+10 | 3420.63 | 01-JAN-00:03 | 3078.56 | 3078.56 | 21.51 | 14.29 |
February | 0.827518E+10 | 0.744766E+10 | 3420.63 | 01-FEB-00:03 | 3078.56 | 3078.56 | 23.41 | 14.29 |
March | 0.916181E+10 | 0.824563E+10 | 3420.63 | 01-MAR-00:10 | 3078.56 | 3078.56 | 26.91 | 14.29 |
April | 0.886627E+10 | 0.797964E+10 | 3420.63 | 01-APR-00:10 | 3078.56 | 3078.56 | 30.09 | 14.29 |
May | 0.916181E+10 | 0.824563E+10 | 3420.63 | 01-MAY-00:10 | 3078.56 | 3078.56 | 22.35 | 14.29 |
June | 0.886627E+10 | 0.797964E+10 | 3420.63 | 01-JUN-00:10 | 3078.56 | 3078.56 | 26.61 | 14.29 |
July | 0.916181E+10 | 0.824563E+10 | 3420.63 | 01-JUL-00:10 | 3078.56 | 3078.56 | 30.57 | 14.29 |
August | 0.916181E+10 | 0.824563E+10 | 3420.63 | 01-AUG-00:03 | 3078.56 | 3078.56 | 37.10 | 14.29 |
September | 0.886627E+10 | 0.797964E+10 | 3420.63 | 01-SEP-00:10 | 3078.56 | 3078.56 | 22.43 | 14.29 |
October | 0.916181E+10 | 0.824563E+10 | 3420.63 | 01-OCT-00:10 | 3078.56 | 3078.56 | 24.63 | 14.29 |
November | 0.886627E+10 | 0.797964E+10 | 3420.63 | 01-NOV-00:10 | 3078.56 | 3078.56 | 27.42 | 14.29 |
December | 0.916181E+10 | 0.824563E+10 | 3420.63 | 01-DEC-00:10 | 3078.56 | 3078.56 | 29.75 | 14.29 |
Annual Sum or Average | 0.107873E+12 | 0.970856E+11 | ||||||
Minimum of Months | 0.827518E+10 | 0.744766E+10 | 3420.63 | 3078.56 | 3078.56 | 21.51 | 14.29 | |
Maximum of Months | 0.916181E+10 | 0.824563E+10 | 3420.63 | 3078.56 | 3078.56 | 37.10 | 14.29 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:03 | 1.79 | 1.79 | 55.79 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:01 | 1.79 | 1.79 | 55.91 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:01 | 1.79 | 1.79 | 55.88 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:02 | 1.79 | 1.79 | 56.11 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 55.93 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 55.62 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 56.42 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 55.96 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 57.01 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.34 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 55.63 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:02 | 1.79 | 1.79 | 55.66 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.62 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 57.01 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.198891E+10 | 0.179002E+10 | 20111.37 | 19-JAN-14:20 | 18100.23 | 18100.23 | 21.20 | 66.99 |
February | 0.212329E+10 | 0.191096E+10 | 20111.40 | 23-FEB-15:00 | 18100.26 | 18100.26 | 21.21 | 66.99 |
March | 0.544203E+10 | 0.489783E+10 | 40291.77 | 14-MAR-14:00 | 36262.59 | 36262.59 | 23.58 | 133.99 |
April | 0.604198E+10 | 0.543778E+10 | 20138.64 | 07-APR-14:00 | 18124.78 | 18124.78 | 23.09 | 66.99 |
May | 0.161050E+11 | 0.144945E+11 | 40274.27 | 10-MAY-12:30 | 36246.84 | 36246.84 | 22.97 | 133.99 |
June | 0.382647E+11 | 0.344383E+11 | 40461.92 | 27-JUN-07:05 | 36415.73 | 36415.73 | 28.87 | 133.99 |
July | 0.530906E+11 | 0.477816E+11 | 40461.92 | 05-JUL-09:40 | 36415.73 | 36415.73 | 29.02 | 133.99 |
August | 0.499479E+11 | 0.449531E+11 | 40461.92 | 07-AUG-11:00 | 36415.73 | 36415.73 | 28.95 | 133.99 |
September | 0.271167E+11 | 0.244051E+11 | 40461.92 | 15-SEP-11:00 | 36415.73 | 36415.73 | 28.93 | 133.99 |
October | 0.924199E+10 | 0.831779E+10 | 40268.45 | 11-OCT-14:40 | 36241.61 | 36241.61 | 22.77 | 133.99 |
November | 0.593317E+10 | 0.533985E+10 | 20131.83 | 16-NOV-13:00 | 18118.64 | 18118.64 | 22.62 | 66.99 |
December | 0.365215E+10 | 0.328693E+10 | 20111.43 | 26-DEC-07:00 | 18100.28 | 18100.28 | 21.21 | 66.99 |
Annual Sum or Average | 0.218949E+12 | 0.197054E+12 | ||||||
Minimum of Months | 0.198891E+10 | 0.179002E+10 | 20111.37 | 18100.23 | 18100.23 | 21.20 | 66.99 | |
Maximum of Months | 0.530906E+11 | 0.477816E+11 | 40461.92 | 36415.73 | 36415.73 | 29.02 | 133.99 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 29.17 | 29.17 | 155690.49 | 2078711.27 | 02-JAN-04:11 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 33.49 | 33.49 | 148296.69 | 1844852.23 | 27-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 26.02 | 26.02 | 53477.67 | 1621243.40 | 06-MAR-06:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 21.44 | 21.44 | 17586.27 | 1400562.56 | 17-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.29 | 20.29 | 1252.16 | 302925.88 | 04-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.39 | 23.39 | 129.29 | 138199.58 | 10-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.28 | 25.28 | 0.00 | 7.82 | 11-JUL-08:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.28 | 25.28 | 5.96 | 8699.14 | 31-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25.54 | 25.54 | 815.19 | 275899.52 | 30-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21.72 | 21.72 | 13013.50 | 1443075.43 | 30-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.41 | 22.41 | 44751.34 | 1434615.82 | 25-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.67 | 23.67 | 134454.19 | 1800162.23 | 11-DEC-05:01 |
Annual Sum or Average | 0.00 | 46973.93 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.29 | 20.29 | 0.00 | 7.82 | ||
Maximum of Months | 0.00 | 0.00 | 33.49 | 33.49 | 155690.49 | 2078711.27 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1076.31 | 29610.65 | 20-JAN-07:20 | 8.43 | 8.40 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1272.78 | 29703.68 | 04-FEB-07:20 | 8.43 | 8.40 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 36192.05 | 1465211.15 | 14-MAR-13:40 | 10.02 | 8.37 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19053.74 | 932588.23 | 07-APR-14:00 | 9.66 | 8.68 | 0.00 | 0.00 | 01-APR-00:10 |
May | 144663.35 | 1465913.93 | 10-MAY-12:30 | 10.18 | 8.54 | 64.25 | 181112.11 | 14-MAY-16:53 |
June | 511676.46 | 2541277.83 | 27-JUN-05:03 | 12.84 | 7.53 | 13.85 | 90364.44 | 20-JUN-01:02 |
July | 747596.23 | 3545739.36 | 20-JUL-05:04 | 14.54 | 8.85 | 30.69 | 100685.77 | 09-JUL-02:42 |
August | 664224.61 | 2928508.75 | 15-AUG-05:03 | 13.42 | 7.74 | 14.09 | 64720.34 | 20-AUG-02:32 |
September | 340899.54 | 2336830.05 | 14-SEP-05:03 | 12.50 | 7.62 | 8.63 | 70510.25 | 17-SEP-20:03 |
October | 51391.22 | 1417005.49 | 11-OCT-13:50 | 10.34 | 8.79 | 35.96 | 138048.90 | 23-OCT-01:13 |
November | 10908.48 | 736193.12 | 16-NOV-13:00 | 9.41 | 8.64 | 16.60 | 148441.33 | 06-NOV-04:02 |
December | 2007.74 | 142097.69 | 01-DEC-06:02 | 8.67 | 8.52 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 212530.09 | 15.53 | ||||||
Minimum of Months | 1076.31 | 29610.65 | 8.43 | 7.53 | 0.00 | 0.00 | ||
Maximum of Months | 747596.23 | 3545739.36 | 14.54 | 8.85 | 64.25 | 181112.11 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.08 | 113.99 | 20-JAN-13:10 | 6.93 | 8.40 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 0.34 | 329.47 | 18-FEB-13:40 | 7.27 | 8.40 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 25232.79 | 1206738.21 | 15-MAR-13:30 | 14.09 | 8.04 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 9808.20 | 642483.43 | 08-APR-13:40 | 15.31 | 8.34 | 0.00 | 0.00 | 01-APR-00:10 |
May | 94448.29 | 2145747.30 | 24-MAY-04:02 | 15.74 | 8.80 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 405366.55 | 3441075.96 | 27-JUN-05:03 | 14.44 | 7.88 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 642555.43 | 4389555.67 | 20-JUL-05:02 | 15.88 | 7.91 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 553855.55 | 4102010.30 | 14-AUG-03:02 | 16.05 | 7.26 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 263397.25 | 3625778.32 | 16-SEP-05:03 | 14.34 | 7.80 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 32913.64 | 1405849.12 | 11-OCT-14:10 | 12.22 | 8.76 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5151.73 | 586214.57 | 27-NOV-06:02 | 13.82 | 8.21 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 25.96 | 141369.39 | 01-DEC-05:01 | 13.35 | 8.42 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 170771.80 | 0.00 | ||||||
Minimum of Months | 0.08 | 113.99 | 6.93 | 7.26 | 0.00 | 0.00 | ||
Maximum of Months | 642555.43 | 4389555.67 | 16.05 | 8.80 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 155490.25 | 215318.95 | 11-JAN-12:00 | 22.66 | 18.33 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 294159.28 | 377271.87 | 28-FEB-15:35 | 25.90 | 18.33 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 468075.71 | 1141134.69 | 15-MAR-14:00 | 40.91 | 30.73 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 614094.68 | 1049569.46 | 08-APR-13:10 | 39.13 | 26.66 | 0.00 | 0.00 | 01-APR-00:10 |
May | 221328.34 | 706143.01 | 10-MAY-15:00 | 32.41 | 28.05 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 553232.22 | 1197401.36 | 27-JUN-13:00 | 42.00 | 34.16 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 917217.31 | 1487677.50 | 21-JUL-14:00 | 47.58 | 36.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1053741.67 | 1619770.38 | 10-AUG-14:10 | 50.10 | 36.68 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 285896.19 | 752430.16 | 16-SEP-14:00 | 33.32 | 29.10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 335930.31 | 709182.99 | 11-OCT-15:00 | 32.47 | 25.38 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 462031.06 | 744882.43 | 05-NOV-14:00 | 33.18 | 23.67 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 577420.32 | 699349.06 | 01-DEC-11:00 | 32.28 | 20.35 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 496710.70 | 0.00 | ||||||
Minimum of Months | 155490.25 | 215318.95 | 22.66 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1053741.67 | 1619770.38 | 50.10 | 36.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.52 | 57.52 | 16761.00 | 56740.66 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 56.41 | 56.41 | 17077.18 | 56970.11 | 16-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.37 | 56.37 | 17827.08 | 56793.38 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.41 | 56.41 | 16191.37 | 55044.47 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.87 | 56.87 | 15821.41 | 52532.11 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.37 | 56.37 | 15254.35 | 49343.32 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.37 | 57.37 | 13531.39 | 46496.99 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 56.45 | 56.45 | 14430.45 | 45035.37 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.47 | 57.47 | 13844.48 | 46449.09 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.65 | 56.65 | 14445.86 | 49309.36 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.39 | 56.39 | 15477.65 | 52358.96 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.26 | 56.26 | 15779.95 | 54977.25 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 15527.97 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.26 | 56.26 | 13531.39 | 45035.37 | ||
Maximum of Months | 0.00 | 0.00 | 57.52 | 57.52 | 17827.08 | 56970.11 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 36.95 | 28920.69 | 19-JAN-14:20 | 21.20 | 20.37 | 1287.60 | 146080.59 | 19-JAN-14:50 |
February | 52.96 | 29448.83 | 23-FEB-15:00 | 21.21 | 20.35 | 1496.39 | 155711.86 | 05-FEB-07:53 |
March | 24699.82 | 1388443.91 | 14-MAR-14:00 | 23.58 | 22.35 | 1863.27 | 137957.44 | 20-MAR-15:10 |
April | 9406.30 | 556660.09 | 07-APR-14:00 | 23.09 | 21.10 | 2334.54 | 147026.69 | 24-APR-05:30 |
May | 91850.88 | 1224272.06 | 10-MAY-15:00 | 25.47 | 22.45 | 573.59 | 110788.58 | 20-MAY-05:50 |
June | 597958.48 | 5635460.37 | 27-JUN-07:40 | 31.16 | 26.73 | 243.16 | 81114.21 | 15-JUN-08:20 |
July | 1175382.18 | 6334293.94 | 05-JUL-16:00 | 32.41 | 27.08 | 100.20 | 45088.67 | 06-JUL-03:30 |
August | 849935.77 | 6596719.57 | 14-AUG-10:10 | 32.88 | 27.59 | 287.85 | 48087.86 | 12-AUG-22:10 |
September | 344695.25 | 4385419.14 | 15-SEP-11:00 | 28.93 | 24.97 | 187.04 | 55716.75 | 11-SEP-10:30 |
October | 31119.39 | 1007330.52 | 11-OCT-12:50 | 24.70 | 21.10 | 1608.56 | 118418.69 | 17-OCT-12:20 |
November | 5201.41 | 424852.97 | 16-NOV-13:00 | 22.62 | 21.10 | 3654.38 | 145588.61 | 22-NOV-16:40 |
December | 83.84 | 30001.27 | 26-DEC-07:00 | 21.21 | 20.36 | 2386.84 | 147546.64 | 26-DEC-07:20 |
Annual Sum or Average | 263248.49 | 1331.01 | ||||||
Minimum of Months | 36.95 | 28920.69 | 21.20 | 20.35 | 100.20 | 45088.67 | ||
Maximum of Months | 1175382.18 | 6596719.57 | 32.88 | 27.59 | 3654.38 | 155711.86 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.858230E+10 | 0.00 | 8114121.25 | 0.397898E+10 | 0.00 | 0.00 |
February | 0.735328E+10 | 0.00 | 6770624.54 | 0.388377E+10 | 0.00 | 0.00 |
March | 0.371996E+10 | 0.00 | 0.600346E+10 | 0.693053E+10 | 0.00 | 0.00 |
April | 0.543148E+09 | 0.00 | 0.240630E+10 | 0.795446E+10 | 0.00 | 0.00 |
May | 0.103542E+09 | 0.00 | 0.186031E+11 | 0.815655E+10 | 0.00 | 0.00 |
June | 3011393.53 | 0.00 | 0.840778E+11 | 0.116051E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.151040E+12 | 0.137845E+11 | 0.00 | 0.00 |
August | 426.03 | 0.00 | 0.130916E+12 | 0.149289E+11 | 0.00 | 0.00 |
September | 27180552.05 | 0.00 | 0.507913E+11 | 0.882727E+10 | 0.00 | 0.00 |
October | 0.418333E+09 | 0.00 | 0.668867E+10 | 0.704380E+10 | 0.00 | 0.00 |
November | 0.127974E+10 | 0.00 | 0.116199E+10 | 0.603971E+10 | 0.00 | 0.00 |
December | 0.668465E+10 | 0.00 | 25712958.61 | 0.509108E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.287151E+11 | 0.00 | 0.451729E+12 | 0.982246E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 6770624.54 | 0.388377E+10 | 0.00 | 0.00 |
Maximum of Months | 0.858230E+10 | 0.00 | 0.151040E+12 | 0.149289E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.345574E+12 | 0.00 | 574441.83 | 0.404259E+11 | 0.00 | 0.00 |
February | 0.295589E+12 | 0.00 | 4002224.65 | 0.361505E+11 | 0.00 | 0.00 |
March | 0.113980E+12 | 0.00 | 0.413995E+11 | 0.422895E+11 | 0.00 | 0.00 |
April | 0.363276E+11 | 0.00 | 0.158866E+11 | 0.441332E+11 | 0.00 | 0.00 |
May | 0.222098E+10 | 0.00 | 0.157391E+12 | 0.623710E+11 | 0.00 | 0.00 |
June | 0.267755E+09 | 0.00 | 0.686468E+12 | 0.890737E+11 | 0.00 | 0.00 |
July | 5648.39 | 0.00 | 0.117121E+13 | 0.101840E+12 | 0.00 | 0.00 |
August | 9368251.74 | 0.00 | 0.967985E+12 | 0.101319E+12 | 0.00 | 0.00 |
September | 0.150583E+10 | 0.00 | 0.430682E+12 | 0.687924E+11 | 0.00 | 0.00 |
October | 0.265924E+11 | 0.00 | 0.510302E+11 | 0.451759E+11 | 0.00 | 0.00 |
November | 0.953326E+11 | 0.00 | 0.749077E+10 | 0.360928E+11 | 0.00 | 0.00 |
December | 0.296023E+12 | 0.00 | 3380673.32 | 0.376334E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.121342E+13 | 0.00 | 0.352955E+13 | 0.705297E+12 | 0.00 | 0.00 |
Minimum of Months | 5648.39 | 0.00 | 574441.83 | 0.360928E+11 | 0.00 | 0.00 |
Maximum of Months | 0.345574E+12 | 0.00 | 0.117121E+13 | 0.101840E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.666009E+11 | 0.00 | 1420301.39 | 0.500951E+10 | 0.00 | 0.00 |
February | 0.591498E+11 | 0.00 | 1186414.48 | 0.459935E+10 | 0.00 | 0.00 |
March | 0.268727E+11 | 0.00 | 0.431531E+10 | 0.457883E+10 | 0.00 | 0.00 |
April | 0.912571E+10 | 0.00 | 0.149805E+10 | 0.396649E+10 | 0.00 | 0.00 |
May | 0.103902E+10 | 0.00 | 0.157472E+11 | 0.542711E+10 | 0.00 | 0.00 |
June | 54469682.32 | 0.00 | 0.749270E+11 | 0.888668E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.129844E+12 | 0.106430E+11 | 0.00 | 0.00 |
August | 5051136.76 | 0.00 | 0.104682E+12 | 0.100546E+11 | 0.00 | 0.00 |
September | 0.622615E+09 | 0.00 | 0.426268E+11 | 0.601147E+10 | 0.00 | 0.00 |
October | 0.814350E+10 | 0.00 | 0.425789E+10 | 0.387811E+10 | 0.00 | 0.00 |
November | 0.204009E+11 | 0.00 | 0.699632E+09 | 0.359134E+10 | 0.00 | 0.00 |
December | 0.606661E+11 | 0.00 | 2767290.88 | 0.491366E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.252681E+12 | 0.00 | 0.378603E+12 | 0.715602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 1186414.48 | 0.359134E+10 | 0.00 | 0.00 |
Maximum of Months | 0.666009E+11 | 0.00 | 0.129844E+12 | 0.106430E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 95009.62 | 0.139206E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 361799.24 | 0.127605E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.335824E+10 | 0.156108E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.574047E+09 | 0.145432E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.798655E+10 | 0.155048E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.401057E+11 | 0.154591E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.770569E+11 | 0.152447E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.672626E+11 | 0.168265E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.289325E+11 | 0.157965E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.279682E+10 | 0.154621E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.538739E+09 | 0.148881E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1384225.75 | 0.143013E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.228614E+12 | 0.180318E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 95009.62 | 0.127605E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.770569E+11 | 0.168265E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.395940E+12 | 0.180823E+12 | 0.00 | 1.58 |
February | 0.00 | 0.00 | 0.626475E+12 | 0.212352E+12 | 0.00 | 1.42 |
March | 0.00 | 0.00 | 0.100008E+13 | 0.287870E+12 | 0.00 | 1.07 |
April | 0.00 | 0.00 | 0.125602E+13 | 0.324363E+12 | 0.00 | 0.42 |
May | 0.00 | 0.00 | 0.416170E+12 | 0.182114E+12 | 0.00 | 0.23 |
June | 0.00 | 0.00 | 0.717407E+12 | 0.245912E+12 | 0.00 | 0.03 |
July | 0.00 | 0.00 | 0.107654E+13 | 0.338275E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.137524E+13 | 0.395671E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.415205E+12 | 0.179829E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.714537E+12 | 0.235645E+12 | 0.00 | 0.19 |
November | 0.00 | 0.00 | 0.973305E+12 | 0.277357E+12 | 0.00 | 0.50 |
December | 0.00 | 0.00 | 0.128953E+13 | 0.333972E+12 | 0.00 | 1.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.102564E+14 | 0.319418E+13 | 0.00 | 6.67 |
Minimum of Months | 0.00 | 0.00 | 0.395940E+12 | 0.179829E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.137524E+13 | 0.395671E+12 | 0.00 | 1.58 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.378966E+10 | 0.232921E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.945520E+10 | 0.329770E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.183531E+11 | 0.505883E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.242449E+11 | 0.591222E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.703270E+10 | 0.293551E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.137883E+11 | 0.434577E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.212642E+11 | 0.620804E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.273406E+11 | 0.739416E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.719312E+10 | 0.293442E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.127310E+11 | 0.396199E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.178718E+11 | 0.483953E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.236480E+11 | 0.596176E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186713E+12 | 0.551791E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.378966E+10 | 0.232921E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.273406E+11 | 0.739416E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.709507E+10 | 0.160632E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.600947E+11 | 0.256298E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.152605E+12 | 0.443125E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.216248E+12 | 0.539852E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.593899E+11 | 0.265710E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.128329E+12 | 0.408961E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202096E+12 | 0.591215E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.259506E+12 | 0.703480E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.616732E+11 | 0.267059E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104566E+12 | 0.347992E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.147352E+12 | 0.421964E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.190200E+12 | 0.508864E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158916E+13 | 0.491515E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.709507E+10 | 0.160632E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.259506E+12 | 0.703480E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.192044E+09 | 0.150721E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.415058E+10 | 0.220791E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.133937E+11 | 0.411813E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.203685E+11 | 0.521968E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.535241E+10 | 0.257091E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127299E+11 | 0.410145E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202743E+11 | 0.596019E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.259267E+11 | 0.706945E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.566162E+10 | 0.260100E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.881014E+10 | 0.320357E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.126826E+11 | 0.388106E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.168016E+11 | 0.472823E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.146344E+12 | 0.471688E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.192044E+09 | 0.150721E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.259267E+11 | 0.706945E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.397898E+10 | 8114121.25 | 0.858230E+10 | 0.620435E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.388377E+10 | 6770624.54 | 0.735328E+10 | 0.552552E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.693053E+10 | 0.600346E+10 | 0.371996E+10 | 0.231704E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.795446E+10 | 0.240630E+10 | 0.543148E+09 | 0.534938E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.815655E+10 | 0.186031E+11 | 0.103542E+09 | 0.541258E+09 | 1734545.38 | 0.00 | 0.00 | 0.00 |
June | 0.116051E+11 | 0.840778E+11 | 3011393.53 | 0.194851E+09 | 0.286101E+10 | 0.00 | 0.00 | 0.00 |
July | 0.137845E+11 | 0.151040E+12 | 0.00 | 0.181765E+09 | 0.844294E+10 | 0.00 | 0.00 | 0.00 |
August | 0.149289E+11 | 0.130916E+12 | 426.03 | 0.743569E+09 | 0.337828E+10 | 0.00 | 0.00 | 0.00 |
September | 0.882727E+10 | 0.507913E+11 | 27180552.05 | 0.172815E+09 | 0.416412E+09 | 0.00 | 0.00 | 0.00 |
October | 0.704380E+10 | 0.668867E+10 | 0.418333E+09 | 0.386392E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.603971E+10 | 0.116199E+10 | 0.127974E+10 | 0.101758E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.509108E+10 | 25712958.61 | 0.668465E+10 | 0.430554E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.982246E+11 | 0.451729E+12 | 0.287151E+11 | 0.204748E+12 | 0.151004E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.388377E+10 | 6770624.54 | 0.00 | 0.172815E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149289E+11 | 0.151040E+12 | 0.858230E+10 | 0.620435E+11 | 0.844294E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.404259E+11 | 574441.83 | 0.345574E+12 | 0.693145E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361505E+11 | 4002224.65 | 0.295589E+12 | 0.637075E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.422895E+11 | 0.414009E+11 | 0.113980E+12 | 0.396257E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.441332E+11 | 0.158866E+11 | 0.363276E+11 | 0.130297E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.623710E+11 | 0.157391E+12 | 0.222098E+10 | 0.120468E+11 | 9923503.73 | 0.00 | 0.00 | 0.00 |
June | 0.890737E+11 | 0.686468E+12 | 0.267755E+09 | 0.343022E+10 | 0.282817E+11 | 0.00 | 0.00 | 0.00 |
July | 0.101840E+12 | 0.117121E+13 | 5648.39 | 0.219912E+10 | 0.824771E+11 | 0.00 | 0.00 | 0.00 |
August | 0.101319E+12 | 0.967985E+12 | 9368251.74 | 0.773154E+10 | 0.323967E+11 | 0.00 | 0.00 | 0.00 |
September | 0.687924E+11 | 0.430682E+12 | 0.150583E+10 | 0.392222E+10 | 0.429498E+10 | 0.00 | 0.00 | 0.00 |
October | 0.451759E+11 | 0.510302E+11 | 0.265924E+11 | 0.818224E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.360928E+11 | 0.749077E+10 | 0.953326E+11 | 0.223289E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376334E+11 | 7793248.11 | 0.296023E+12 | 0.606002E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.705297E+12 | 0.352956E+13 | 0.121342E+13 | 0.279722E+13 | 0.147460E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.360928E+11 | 574441.83 | 5648.39 | 0.219912E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101840E+12 | 0.117121E+13 | 0.345574E+12 | 0.693145E+12 | 0.824771E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.500951E+10 | 1420301.39 | 0.666009E+11 | 0.679334E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.459935E+10 | 1186414.48 | 0.591498E+11 | 0.621615E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.457883E+10 | 0.431531E+10 | 0.268727E+11 | 0.418251E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396649E+10 | 0.149805E+10 | 0.912571E+10 | 0.170678E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.542711E+10 | 0.157472E+11 | 0.103902E+10 | 0.180574E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.888668E+10 | 0.749270E+11 | 54469682.32 | 0.397195E+09 | 0.235935E+10 | 0.00 | 0.00 | 0.00 |
July | 0.106430E+11 | 0.129844E+12 | 0.00 | 0.159145E+09 | 0.699394E+10 | 0.00 | 0.00 | 0.00 |
August | 0.100546E+11 | 0.104682E+12 | 5051136.76 | 0.738873E+09 | 0.251946E+10 | 0.00 | 0.00 | 0.00 |
September | 0.601147E+10 | 0.426268E+11 | 0.622615E+09 | 0.629673E+09 | 0.267427E+09 | 0.00 | 0.00 | 0.00 |
October | 0.387811E+10 | 0.425789E+10 | 0.814350E+10 | 0.114062E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.359134E+10 | 0.699632E+09 | 0.204009E+11 | 0.286418E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.491366E+10 | 2767290.88 | 0.606661E+11 | 0.605362E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.715602E+11 | 0.378603E+12 | 0.252681E+12 | 0.293303E+12 | 0.121402E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.359134E+10 | 1186414.48 | 0.00 | 0.159145E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106430E+11 | 0.129844E+12 | 0.666009E+11 | 0.679334E+11 | 0.699394E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139206E+11 | 95009.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127605E+11 | 361799.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156108E+11 | 0.335824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145432E+11 | 0.574047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155048E+11 | 0.798655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154591E+11 | 0.401057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152447E+11 | 0.770569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168265E+11 | 0.672626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157965E+11 | 0.289325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154621E+11 | 0.279682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148881E+11 | 0.538739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143013E+11 | 1384225.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180318E+12 | 0.228614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127605E+11 | 95009.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168265E+11 | 0.770569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.967141E+11 | 0.316085E+12 | 0.00 | 0.00 | 0.00 | 0.423542E+10 | 0.00 | 0.00 |
February | 0.873547E+11 | 0.505287E+12 | 0.00 | 0.00 | 0.00 | 0.379187E+10 | 0.00 | 0.00 |
March | 0.967141E+11 | 0.811787E+12 | 0.00 | 0.00 | 0.00 | 0.285321E+10 | 0.00 | 0.00 |
April | 0.935943E+11 | 0.102639E+13 | 0.00 | 0.00 | 0.00 | 0.112960E+10 | 0.00 | 0.00 |
May | 0.967141E+11 | 0.331400E+12 | 0.00 | 0.00 | 0.00 | 0.627287E+09 | 0.00 | 0.00 |
June | 0.935943E+11 | 0.565166E+12 | 0.00 | 0.00 | 0.00 | 76554762.77 | 0.00 | 0.00 |
July | 0.967141E+11 | 0.834982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.967141E+11 | 0.107628E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.935943E+11 | 0.328970E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.967141E+11 | 0.576107E+12 | 0.00 | 0.00 | 0.00 | 0.498160E+09 | 0.00 | 0.00 |
November | 0.935943E+11 | 0.790879E+12 | 0.00 | 0.00 | 0.00 | 0.133014E+10 | 0.00 | 0.00 |
December | 0.967141E+11 | 0.105560E+13 | 0.00 | 0.00 | 0.00 | 0.331434E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113873E+13 | 0.821893E+13 | 0.00 | 0.00 | 0.00 | 0.178566E+11 | 0.00 | 0.00 |
Minimum of Months | 0.873547E+11 | 0.316085E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.967141E+11 | 0.107628E+13 | 0.00 | 0.00 | 0.00 | 0.423542E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150158E+10 | 0.296203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135626E+10 | 0.751377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150158E+10 | 0.147959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145314E+10 | 0.197859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150158E+10 | 0.559877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145314E+10 | 0.108957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150158E+10 | 0.165578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150158E+10 | 0.214481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145314E+10 | 0.571184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150158E+10 | 0.102706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145314E+10 | 0.144854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150158E+10 | 0.191878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176799E+11 | 0.149213E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135626E+10 | 0.296203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150158E+10 | 0.214481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143530E+11 | 0.538486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129640E+11 | 0.474289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143530E+11 | 0.122646E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138900E+11 | 0.176153E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143530E+11 | 0.471718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138900E+11 | 0.101323E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143530E+11 | 0.157328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143530E+11 | 0.203511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138900E+11 | 0.488572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143530E+11 | 0.841202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138900E+11 | 0.119045E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143530E+11 | 0.153667E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168994E+12 | 0.126664E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129640E+11 | 0.538486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143530E+11 | 0.203511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146024E+10 | 0.145070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131893E+10 | 0.326160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146024E+10 | 0.107358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141314E+10 | 0.165620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146024E+10 | 0.424174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141314E+10 | 0.100416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146024E+10 | 0.157743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146024E+10 | 0.203175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141314E+10 | 0.447376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146024E+10 | 0.706680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141314E+10 | 0.102147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146024E+10 | 0.135336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171932E+11 | 0.116369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131893E+10 | 0.145070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146024E+10 | 0.203175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.397898E+10 | 0.858230E+10 | 8114121.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.388377E+10 | 0.735328E+10 | 6770624.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.693053E+10 | 0.371996E+10 | 0.600346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.795446E+10 | 0.543148E+09 | 0.240630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.815655E+10 | 0.103542E+09 | 0.186031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.116051E+11 | 3011393.53 | 0.840778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137845E+11 | 0.00 | 0.151040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149289E+11 | 426.03 | 0.130916E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.882727E+10 | 27180552.05 | 0.507913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.704380E+10 | 0.418333E+09 | 0.668867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.603971E+10 | 0.127974E+10 | 0.116199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.509108E+10 | 0.668465E+10 | 25712958.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.982246E+11 | 0.287151E+11 | 0.451729E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.388377E+10 | 0.00 | 6770624.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149289E+11 | 0.858230E+10 | 0.151040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.404259E+11 | 0.345574E+12 | 574441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361505E+11 | 0.295589E+12 | 4002224.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.422895E+11 | 0.113980E+12 | 0.413995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.441332E+11 | 0.363276E+11 | 0.158866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.623710E+11 | 0.222098E+10 | 0.157391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.890737E+11 | 0.267755E+09 | 0.686468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101840E+12 | 5648.39 | 0.117121E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101319E+12 | 9368251.74 | 0.967985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.687924E+11 | 0.150583E+10 | 0.430682E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.451759E+11 | 0.265924E+11 | 0.510302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.360928E+11 | 0.953326E+11 | 0.749077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376334E+11 | 0.296023E+12 | 3380673.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.705297E+12 | 0.121342E+13 | 0.352955E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.360928E+11 | 5648.39 | 574441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101840E+12 | 0.345574E+12 | 0.117121E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.500951E+10 | 0.666009E+11 | 1420301.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.459935E+10 | 0.591498E+11 | 1186414.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.457883E+10 | 0.268727E+11 | 0.431531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396649E+10 | 0.912571E+10 | 0.149805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.542711E+10 | 0.103902E+10 | 0.157472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.888668E+10 | 54469682.32 | 0.749270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106430E+11 | 0.00 | 0.129844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100546E+11 | 5051136.76 | 0.104682E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.601147E+10 | 0.622615E+09 | 0.426268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.387811E+10 | 0.814350E+10 | 0.425789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.359134E+10 | 0.204009E+11 | 0.699632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.491366E+10 | 0.606661E+11 | 2767290.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.715602E+11 | 0.252681E+12 | 0.378603E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.359134E+10 | 0.00 | 1186414.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106430E+11 | 0.666009E+11 | 0.129844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.139206E+11 | 0.00 | 95009.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127605E+11 | 0.00 | 361799.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156108E+11 | 0.00 | 0.335824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145432E+11 | 0.00 | 0.574047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155048E+11 | 0.00 | 0.798655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154591E+11 | 0.00 | 0.401057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152447E+11 | 0.00 | 0.770569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168265E+11 | 0.00 | 0.672626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157965E+11 | 0.00 | 0.289325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154621E+11 | 0.00 | 0.279682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148881E+11 | 0.00 | 0.538739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143013E+11 | 0.00 | 1384225.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180318E+12 | 0.00 | 0.228614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127605E+11 | 0.00 | 95009.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168265E+11 | 0.00 | 0.770569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.967141E+11 | 0.00 | 0.395940E+12 | 0.00 | 0.798547E+11 | 0.00 | 0.00 | 0.00 | 0.425448E+10 | 0.00 | 0.00 | 0.00 |
February | 0.873547E+11 | 0.00 | 0.626475E+12 | 0.00 | 0.121189E+12 | 0.00 | 0.00 | 0.00 | 0.380894E+10 | 0.00 | 0.00 | 0.00 |
March | 0.967141E+11 | 0.00 | 0.100008E+13 | 0.00 | 0.188290E+12 | 0.00 | 0.00 | 0.00 | 0.286605E+10 | 0.00 | 0.00 | 0.00 |
April | 0.935943E+11 | 0.00 | 0.125602E+13 | 0.00 | 0.229634E+12 | 0.00 | 0.00 | 0.00 | 0.113469E+10 | 0.00 | 0.00 | 0.00 |
May | 0.967141E+11 | 0.00 | 0.416170E+12 | 0.00 | 0.847698E+11 | 0.00 | 0.00 | 0.00 | 0.630110E+09 | 0.00 | 0.00 | 0.00 |
June | 0.935943E+11 | 0.00 | 0.717407E+12 | 0.00 | 0.152241E+12 | 0.00 | 0.00 | 0.00 | 76899366.79 | 0.00 | 0.00 | 0.00 |
July | 0.967141E+11 | 0.00 | 0.107654E+13 | 0.00 | 0.241561E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.967141E+11 | 0.00 | 0.137524E+13 | 0.00 | 0.298956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.935943E+11 | 0.00 | 0.415205E+12 | 0.00 | 0.862348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.967141E+11 | 0.00 | 0.714537E+12 | 0.00 | 0.138430E+12 | 0.00 | 0.00 | 0.00 | 0.500402E+09 | 0.00 | 0.00 | 0.00 |
November | 0.935943E+11 | 0.00 | 0.973305E+12 | 0.00 | 0.182426E+12 | 0.00 | 0.00 | 0.00 | 0.133613E+10 | 0.00 | 0.00 | 0.00 |
December | 0.967141E+11 | 0.00 | 0.128953E+13 | 0.00 | 0.233929E+12 | 0.00 | 0.00 | 0.00 | 0.332926E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113873E+13 | 0.00 | 0.102564E+14 | 0.00 | 0.203752E+13 | 0.00 | 0.00 | 0.00 | 0.179370E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.873547E+11 | 0.00 | 0.395940E+12 | 0.00 | 0.798547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.967141E+11 | 0.00 | 0.137524E+13 | 0.00 | 0.298956E+12 | 0.00 | 0.00 | 0.00 | 0.425448E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150158E+10 | 0.00 | 0.378966E+10 | 0.00 | 0.827634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135626E+10 | 0.00 | 0.945520E+10 | 0.00 | 0.194143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150158E+10 | 0.00 | 0.183531E+11 | 0.00 | 0.355725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145314E+10 | 0.00 | 0.242449E+11 | 0.00 | 0.445908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150158E+10 | 0.00 | 0.703270E+10 | 0.00 | 0.143393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145314E+10 | 0.00 | 0.137883E+11 | 0.00 | 0.289263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150158E+10 | 0.00 | 0.212642E+11 | 0.00 | 0.470646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150158E+10 | 0.00 | 0.273406E+11 | 0.00 | 0.589258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145314E+10 | 0.00 | 0.719312E+10 | 0.00 | 0.148128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150158E+10 | 0.00 | 0.127310E+11 | 0.00 | 0.246042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145314E+10 | 0.00 | 0.178718E+11 | 0.00 | 0.338639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150158E+10 | 0.00 | 0.236480E+11 | 0.00 | 0.446018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176799E+11 | 0.00 | 0.186713E+12 | 0.00 | 0.374992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135626E+10 | 0.00 | 0.378966E+10 | 0.00 | 0.827634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150158E+10 | 0.00 | 0.273406E+11 | 0.00 | 0.589258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143530E+11 | 0.00 | 0.709507E+10 | 0.00 | 0.171021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129640E+11 | 0.00 | 0.600947E+11 | 0.00 | 0.126658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143530E+11 | 0.00 | 0.152605E+12 | 0.00 | 0.299595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138900E+11 | 0.00 | 0.216248E+12 | 0.00 | 0.400952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143530E+11 | 0.00 | 0.593899E+11 | 0.00 | 0.122181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138900E+11 | 0.00 | 0.128329E+12 | 0.00 | 0.270061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143530E+11 | 0.00 | 0.202096E+12 | 0.00 | 0.447685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143530E+11 | 0.00 | 0.259506E+12 | 0.00 | 0.559951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138900E+11 | 0.00 | 0.616732E+11 | 0.00 | 0.128160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143530E+11 | 0.00 | 0.104566E+12 | 0.00 | 0.204463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138900E+11 | 0.00 | 0.147352E+12 | 0.00 | 0.283064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143530E+11 | 0.00 | 0.190200E+12 | 0.00 | 0.365335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168994E+12 | 0.00 | 0.158916E+13 | 0.00 | 0.322521E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129640E+11 | 0.00 | 0.709507E+10 | 0.00 | 0.171021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143530E+11 | 0.00 | 0.259506E+12 | 0.00 | 0.559951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146024E+10 | 0.00 | 0.192044E+09 | 0.00 | 46974201.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131893E+10 | 0.00 | 0.415058E+10 | 0.00 | 0.888980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146024E+10 | 0.00 | 0.133937E+11 | 0.00 | 0.265789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141314E+10 | 0.00 | 0.203685E+11 | 0.00 | 0.380654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146024E+10 | 0.00 | 0.535241E+10 | 0.00 | 0.111067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141314E+10 | 0.00 | 0.127299E+11 | 0.00 | 0.268831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146024E+10 | 0.00 | 0.202743E+11 | 0.00 | 0.449994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146024E+10 | 0.00 | 0.259267E+11 | 0.00 | 0.560921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141314E+10 | 0.00 | 0.566162E+10 | 0.00 | 0.118786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146024E+10 | 0.00 | 0.881014E+10 | 0.00 | 0.174333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141314E+10 | 0.00 | 0.126826E+11 | 0.00 | 0.246793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146024E+10 | 0.00 | 0.168016E+11 | 0.00 | 0.326799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171932E+11 | 0.00 | 0.146344E+12 | 0.00 | 0.299756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131893E+10 | 0.00 | 0.192044E+09 | 0.00 | 46974201.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146024E+10 | 0.00 | 0.259267E+11 | 0.00 | 0.560921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.879960E+10 | 0.00 | 0.00 | 71031928.53 | 0.00 | 0.00 | 0.563529E+11 | 0.00 | 0.38 |
February | 0.106406E+11 | 0.00 | 0.00 | 61976853.51 | 0.00 | 0.00 | 0.480278E+11 | 0.00 | 0.38 |
March | 0.952525E+09 | 0.00 | 0.00 | 0.117915E+09 | 0.00 | 0.00 | 0.708377E+11 | 0.00 | 0.64 |
April | 0.412511E+09 | 0.00 | 0.00 | 0.113993E+09 | 0.00 | 0.00 | 0.715673E+11 | 0.00 | 0.83 |
May | 0.234158E+09 | 0.00 | 0.00 | 0.112751E+09 | 0.00 | 0.00 | 0.685875E+11 | 0.00 | 1.26 |
June | 0.124512E+09 | 0.292276E+10 | 0.00 | 0.101822E+09 | 34103856.27 | 0.00 | 0.435630E+11 | 0.00 | 1.41 |
July | 97571236.45 | 0.128882E+11 | 0.00 | 69733049.10 | 55286113.41 | 0.00 | 0.166382E+11 | 0.00 | 1.14 |
August | 85967233.86 | 0.756682E+10 | 0.00 | 0.103956E+09 | 30953262.53 | 0.00 | 0.310856E+11 | 0.00 | 1.37 |
September | 0.384963E+09 | 0.190612E+10 | 0.00 | 0.119169E+09 | 4185593.97 | 0.00 | 0.538888E+11 | 0.00 | 1.47 |
October | 0.420767E+09 | 0.00 | 0.00 | 0.130202E+09 | 0.00 | 0.00 | 0.779454E+11 | 0.00 | 1.03 |
November | 0.365985E+09 | 0.00 | 0.00 | 0.125846E+09 | 0.00 | 0.00 | 0.762112E+11 | 0.00 | 0.76 |
December | 0.104764E+10 | 0.00 | 0.00 | 0.112004E+09 | 0.00 | 0.00 | 0.694219E+11 | 0.00 | 0.45 |
Annual Sum or Average | 0.235668E+11 | 0.252839E+11 | 0.00 | 0.124040E+10 | 0.124529E+09 | 0.00 | 0.684127E+12 | 0.00 | 0.93 |
Minimum of Months | 85967233.86 | 0.00 | 0.00 | 61976853.51 | 0.00 | 0.00 | 0.166382E+11 | 0.00 | 0.38 |
Maximum of Months | 0.106406E+11 | 0.128882E+11 | 0.00 | 0.130202E+09 | 55286113.41 | 0.00 | 0.779454E+11 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106038E+11 | 0.00 | 0.00 | 37575834.05 | 0.00 | 0.00 | 0.254755E+11 | 0.00 | 0.41 |
February | 0.787033E+10 | 0.00 | 0.00 | 40223105.71 | 0.00 | 0.00 | 0.264767E+11 | 0.00 | 0.42 |
March | 0.225801E+10 | 0.00 | 0.00 | 95127024.51 | 0.00 | 0.00 | 0.525430E+11 | 0.00 | 0.58 |
April | 0.463767E+10 | 0.00 | 0.00 | 98429004.05 | 0.00 | 0.00 | 0.580281E+11 | 0.00 | 0.73 |
May | 0.359693E+10 | 1393277.53 | 0.00 | 91732637.56 | 20580886.60 | 0.00 | 0.512395E+11 | 0.00 | 0.91 |
June | 0.363641E+10 | 0.326554E+10 | 0.00 | 77545698.93 | 0.573266E+09 | 0.00 | 0.303443E+11 | 0.00 | 1.09 |
July | 0.448150E+10 | 0.121539E+11 | 0.00 | 42456364.24 | 0.257545E+10 | 0.00 | 0.102853E+11 | 0.00 | 1.01 |
August | 0.691068E+10 | 0.750763E+10 | 0.00 | 75538048.74 | 0.147691E+10 | 0.00 | 0.211905E+11 | 0.00 | 1.19 |
September | 0.399753E+10 | 0.270418E+10 | 0.00 | 80048166.73 | 69256150.20 | 0.00 | 0.354975E+11 | 0.00 | 1.00 |
October | 0.243339E+10 | 0.00 | 0.00 | 94105487.54 | 0.00 | 0.00 | 0.545477E+11 | 0.00 | 0.73 |
November | 0.144208E+10 | 0.00 | 0.00 | 90726418.37 | 1391769.45 | 0.00 | 0.531323E+11 | 0.00 | 0.57 |
December | 0.245241E+10 | 0.00 | 0.00 | 71689324.66 | 0.00 | 0.00 | 0.436478E+11 | 0.00 | 0.45 |
Annual Sum or Average | 0.543207E+11 | 0.256327E+11 | 0.00 | 0.895197E+09 | 0.471686E+10 | 0.00 | 0.462408E+12 | 0.00 | 0.76 |
Minimum of Months | 0.144208E+10 | 0.00 | 0.00 | 37575834.05 | 0.00 | 0.00 | 0.102853E+11 | 0.00 | 0.41 |
Maximum of Months | 0.106038E+11 | 0.121539E+11 | 0.00 | 98429004.05 | 0.257545E+10 | 0.00 | 0.580281E+11 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.234800E+12 | 0.00 | 0.00 | 13359760.39 | 0.00 | 0.527931E+10 | 0.236122E+11 | 0.00 | 0.40 |
February | 0.219806E+12 | 0.00 | 0.00 | 15118813.37 | 0.00 | 0.379092E+10 | 0.203759E+11 | 0.00 | 0.40 |
March | 0.155965E+12 | 0.00 | 0.00 | 0.269376E+09 | 0.00 | 89733502.65 | 0.176852E+12 | 0.00 | 0.46 |
April | 0.943916E+11 | 0.00 | 0.00 | 0.395819E+09 | 0.00 | 0.00 | 0.284027E+12 | 0.00 | 0.51 |
May | 0.323194E+11 | 32798596.27 | 0.00 | 0.655647E+09 | 0.266124E+09 | 0.00 | 0.396452E+12 | 0.00 | 0.74 |
June | 0.185990E+11 | 0.261251E+11 | 0.00 | 0.622356E+09 | 0.199149E+10 | 0.00 | 0.246010E+12 | 0.00 | 0.87 |
July | 0.172032E+11 | 0.972152E+11 | 0.00 | 0.360631E+09 | 0.845051E+10 | 0.00 | 0.826893E+11 | 0.00 | 0.74 |
August | 0.186594E+11 | 0.538834E+11 | 0.00 | 0.628341E+09 | 0.345954E+10 | 0.00 | 0.170755E+12 | 0.00 | 0.84 |
September | 0.370664E+11 | 0.221964E+11 | 0.00 | 0.602189E+09 | 0.117839E+09 | 0.00 | 0.272645E+12 | 0.00 | 0.82 |
October | 0.775955E+11 | 0.00 | 0.00 | 0.446488E+09 | 2908654.44 | 0.00 | 0.300007E+12 | 0.00 | 0.53 |
November | 0.121989E+12 | 0.00 | 0.00 | 0.267152E+09 | 28775266.89 | 0.00 | 0.202133E+12 | 0.00 | 0.43 |
December | 0.222590E+12 | 0.00 | 0.00 | 40220167.23 | 0.00 | 0.254159E+10 | 0.460583E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.125098E+13 | 0.199453E+12 | 0.00 | 0.431670E+10 | 0.143172E+11 | 0.117016E+11 | 0.222162E+13 | 0.00 | 0.60 |
Minimum of Months | 0.172032E+11 | 0.00 | 0.00 | 13359760.39 | 0.00 | 0.00 | 0.203759E+11 | 0.00 | 0.39 |
Maximum of Months | 0.234800E+12 | 0.972152E+11 | 0.00 | 0.655647E+09 | 0.845051E+10 | 0.527931E+10 | 0.396452E+12 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.182542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274459E+10 | 0.00 | 0.00 | 0.37 |
February | 0.173142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256710E+10 | 0.00 | 0.00 | 0.37 |
March | 0.188850E+11 | 0.00 | 0.00 | 10349643.40 | 0.00 | 0.951017E+09 | 0.720370E+10 | 0.00 | 0.44 |
April | 0.145401E+11 | 0.00 | 0.00 | 18578633.70 | 0.00 | 0.162272E+09 | 0.157742E+11 | 0.00 | 0.46 |
May | 0.757096E+10 | 4071500.32 | 0.00 | 47486339.61 | 17506842.52 | 0.00 | 0.309071E+11 | 0.00 | 0.69 |
June | 0.242917E+10 | 0.286679E+10 | 0.00 | 57332315.07 | 0.341168E+09 | 0.00 | 0.235266E+11 | 0.00 | 0.90 |
July | 0.153298E+10 | 0.106417E+11 | 0.00 | 34702301.70 | 0.105648E+10 | 0.00 | 0.823536E+10 | 0.00 | 0.80 |
August | 0.159557E+10 | 0.601100E+10 | 0.00 | 60055151.34 | 0.395156E+09 | 0.00 | 0.158723E+11 | 0.00 | 0.86 |
September | 0.644509E+10 | 0.212860E+10 | 0.00 | 43886067.46 | 32316416.57 | 0.00 | 0.201798E+11 | 0.00 | 0.76 |
October | 0.142180E+11 | 0.00 | 0.00 | 18773291.97 | 1562544.19 | 0.237746E+09 | 0.146299E+11 | 0.00 | 0.47 |
November | 0.188294E+11 | 0.00 | 0.00 | 3420458.25 | 21436907.17 | 0.411530E+09 | 0.393977E+10 | 0.00 | 0.40 |
December | 0.185390E+11 | 0.00 | 0.00 | 13304.42 | 0.00 | 0.244584E+10 | 0.128471E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.140154E+12 | 0.216521E+11 | 0.00 | 0.294598E+09 | 0.186562E+10 | 0.952009E+10 | 0.140397E+12 | 0.00 | 0.58 |
Minimum of Months | 0.153298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.188850E+11 | 0.106417E+11 | 0.00 | 60055151.34 | 0.105648E+10 | 0.274459E+10 | 0.309071E+11 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.329922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109660E+10 | 0.00 | 0.00 | 0.41 |
February | 0.321413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837192E+09 | 0.00 | 0.00 | 0.41 |
March | 0.400661E+10 | 0.00 | 0.00 | 1965586.75 | 0.00 | 0.146378E+09 | 0.125426E+10 | 0.00 | 0.48 |
April | 0.284965E+10 | 0.00 | 0.00 | 4129478.46 | 0.00 | 0.00 | 0.333271E+10 | 0.00 | 0.60 |
May | 0.169516E+10 | 0.00 | 0.00 | 7424022.18 | 3126044.27 | 0.00 | 0.467961E+10 | 0.00 | 0.88 |
June | 0.657054E+09 | 0.581049E+09 | 0.00 | 9404426.77 | 85584096.88 | 0.00 | 0.385050E+10 | 0.00 | 1.28 |
July | 0.735921E+09 | 0.206988E+10 | 0.00 | 5722111.74 | 0.382222E+09 | 0.00 | 0.136631E+10 | 0.00 | 1.26 |
August | 0.114562E+10 | 0.119893E+10 | 0.00 | 9538730.40 | 0.225389E+09 | 0.00 | 0.255148E+10 | 0.00 | 1.37 |
September | 0.144784E+10 | 0.381108E+09 | 0.00 | 6185021.51 | 10721404.62 | 0.00 | 0.305144E+10 | 0.00 | 0.98 |
October | 0.274738E+10 | 0.00 | 0.00 | 3527262.02 | 0.00 | 0.00 | 0.281224E+10 | 0.00 | 0.58 |
November | 0.373355E+10 | 0.00 | 0.00 | 1059419.50 | 206621.65 | 0.00 | 0.116903E+10 | 0.00 | 0.42 |
December | 0.416991E+10 | 0.00 | 0.00 | 10600.59 | 0.00 | 0.392735E+09 | 49543365.97 | 0.00 | 0.38 |
Annual Sum or Average | 0.297020E+11 | 0.423097E+10 | 0.00 | 48966659.92 | 0.707249E+09 | 0.247290E+10 | 0.241171E+11 | 0.00 | 0.76 |
Minimum of Months | 0.657054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.416991E+10 | 0.206988E+10 | 0.00 | 9538730.40 | 0.382222E+09 | 0.109660E+10 | 0.467961E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.386038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142085E+10 | 0.00 | 0.00 | 0.76 |
February | 0.367065E+10 | 0.00 | 0.00 | 82910.20 | 0.00 | 0.115131E+10 | 46606238.10 | 0.00 | 0.76 |
March | 0.496643E+10 | 0.00 | 0.00 | 1729586.64 | 0.00 | 0.155961E+09 | 0.119693E+10 | 0.00 | 0.84 |
April | 0.423113E+10 | 0.00 | 0.00 | 4158231.37 | 0.00 | 1099376.50 | 0.315109E+10 | 0.00 | 1.06 |
May | 0.266849E+10 | 0.00 | 0.00 | 7264551.17 | 3757774.78 | 0.00 | 0.472170E+10 | 0.00 | 1.52 |
June | 0.129258E+10 | 0.468041E+09 | 0.00 | 7597939.68 | 96786227.41 | 0.00 | 0.368628E+10 | 0.00 | 1.92 |
July | 0.937103E+09 | 0.152892E+10 | 0.00 | 5788463.60 | 0.536041E+09 | 0.00 | 0.155382E+10 | 0.00 | 1.92 |
August | 0.181926E+10 | 0.774571E+09 | 0.00 | 7262155.09 | 0.322211E+09 | 0.00 | 0.210406E+10 | 0.00 | 2.00 |
September | 0.233739E+10 | 0.278782E+09 | 0.00 | 5824155.96 | 52448272.29 | 0.00 | 0.289789E+10 | 0.00 | 1.60 |
October | 0.391626E+10 | 0.00 | 0.00 | 2568458.17 | 0.00 | 377742.75 | 0.235691E+10 | 0.00 | 1.00 |
November | 0.539013E+10 | 0.00 | 0.00 | 337354.06 | 248377.04 | 3369278.49 | 0.424037E+09 | 0.00 | 0.77 |
December | 0.444366E+10 | 0.00 | 0.00 | 1261.92 | 0.00 | 0.109896E+10 | 2288734.97 | 0.00 | 0.70 |
Annual Sum or Average | 0.395335E+11 | 0.305032E+10 | 0.00 | 42615067.87 | 0.101149E+10 | 0.383193E+10 | 0.221416E+11 | 0.00 | 1.24 |
Minimum of Months | 0.937103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
Maximum of Months | 0.539013E+10 | 0.152892E+10 | 0.00 | 7597939.68 | 0.536041E+09 | 0.142085E+10 | 0.472170E+10 | 0.00 | 2.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.414438E+10 | 0.00 | 0.00 | 1048822.71 | 0.00 | 0.158269E+10 | 0.821737E+09 | 0.00 | 0.60 |
February | 0.376588E+10 | 0.00 | 0.00 | 1824965.22 | 0.00 | 0.129959E+10 | 0.116540E+10 | 0.00 | 0.62 |
March | 0.449836E+10 | 0.00 | 0.00 | 7239216.43 | 0.00 | 0.302305E+09 | 0.426220E+10 | 0.00 | 0.77 |
April | 0.441054E+10 | 0.00 | 0.00 | 7129847.30 | 0.00 | 22412836.46 | 0.551221E+10 | 0.00 | 0.97 |
May | 0.318083E+10 | 1774321.30 | 0.00 | 9099967.18 | 3017341.43 | 0.00 | 0.578786E+10 | 0.00 | 1.25 |
June | 0.157278E+10 | 0.632721E+09 | 0.00 | 9470672.49 | 0.119673E+09 | 0.00 | 0.399750E+10 | 0.00 | 1.56 |
July | 0.119506E+10 | 0.229431E+10 | 0.00 | 6133214.55 | 0.551684E+09 | 0.00 | 0.138253E+10 | 0.00 | 1.53 |
August | 0.193996E+10 | 0.136483E+10 | 0.00 | 11907602.76 | 0.332361E+09 | 0.00 | 0.289402E+10 | 0.00 | 1.80 |
September | 0.222298E+10 | 0.520388E+09 | 0.00 | 12171529.24 | 16931226.11 | 0.00 | 0.514951E+10 | 0.00 | 1.62 |
October | 0.352298E+10 | 0.00 | 0.00 | 8821073.51 | 0.00 | 6701208.12 | 0.605018E+10 | 0.00 | 1.06 |
November | 0.524329E+10 | 61694.96 | 0.00 | 3591779.22 | 235685.91 | 36769224.89 | 0.268540E+10 | 0.00 | 0.69 |
December | 0.520031E+10 | 0.00 | 0.00 | 1031182.56 | 0.00 | 0.924914E+09 | 0.755431E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.408973E+11 | 0.481409E+10 | 0.00 | 79469873.17 | 0.102390E+10 | 0.417538E+10 | 0.404640E+11 | 0.00 | 1.09 |
Minimum of Months | 0.119506E+10 | 0.00 | 0.00 | 1031182.56 | 0.00 | 0.00 | 0.755431E+09 | 0.00 | 0.56 |
Maximum of Months | 0.524329E+10 | 0.229431E+10 | 0.00 | 12171529.24 | 0.551684E+09 | 0.158269E+10 | 0.605018E+10 | 0.00 | 1.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.598705E+10 | 0.00 | 0.00 | 8818.67 | 0.00 | 0.520498E+09 | 35883515.84 | 0.00 | 0.94 |
February | 0.554597E+10 | 0.00 | 0.00 | 456650.01 | 0.00 | 0.183328E+09 | 0.340234E+09 | 0.00 | 0.95 |
March | 0.389145E+10 | 0.00 | 0.00 | 5984865.14 | 0.00 | 601218.99 | 0.451584E+10 | 0.00 | 1.12 |
April | 0.169051E+10 | 0.00 | 0.00 | 11942962.07 | 0.00 | 0.00 | 0.862578E+10 | 0.00 | 1.56 |
May | 0.235360E+10 | 622401.84 | 0.00 | 9595542.36 | 4202330.81 | 0.00 | 0.643854E+10 | 0.00 | 1.88 |
June | 0.863490E+09 | 0.673789E+09 | 0.00 | 14046397.14 | 0.107507E+09 | 0.00 | 0.511157E+10 | 0.00 | 2.57 |
July | 0.931631E+09 | 0.252309E+10 | 0.00 | 9183549.36 | 0.420194E+09 | 0.00 | 0.176717E+10 | 0.00 | 2.50 |
August | 0.134551E+10 | 0.151347E+10 | 0.00 | 16063711.50 | 0.237198E+09 | 0.00 | 0.374665E+10 | 0.00 | 2.89 |
September | 0.204901E+10 | 0.400072E+09 | 0.00 | 7923025.83 | 16674348.71 | 0.00 | 0.397724E+10 | 0.00 | 1.94 |
October | 0.322123E+10 | 0.00 | 0.00 | 5522210.80 | 0.00 | 0.00 | 0.481536E+10 | 0.00 | 1.32 |
November | 0.381081E+10 | 66185.20 | 0.00 | 3025670.57 | 244044.22 | 0.00 | 0.359069E+10 | 0.00 | 0.99 |
December | 0.553549E+10 | 0.00 | 0.00 | 644615.13 | 0.00 | 3671638.68 | 0.135267E+10 | 0.00 | 0.87 |
Annual Sum or Average | 0.372257E+11 | 0.511111E+10 | 0.00 | 84398018.59 | 0.786019E+09 | 0.708099E+09 | 0.443176E+11 | 0.00 | 1.63 |
Minimum of Months | 0.863490E+09 | 0.00 | 0.00 | 8818.67 | 0.00 | 0.00 | 35883515.84 | 0.00 | 0.87 |
Maximum of Months | 0.598705E+10 | 0.252309E+10 | 0.00 | 16063711.50 | 0.420194E+09 | 0.520498E+09 | 0.862578E+10 | 0.00 | 2.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.437053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348820E+11 | 0.00 | 0.00 | 0.46 |
February | 0.598680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307504E+11 | 0.00 | 0.00 | 0.47 |
March | 0.250473E+11 | 0.00 | 0.00 | 5278455.23 | 0.00 | 0.163151E+11 | 0.225114E+10 | 0.00 | 0.48 |
April | 0.357978E+11 | 0.00 | 0.00 | 3837085.84 | 0.00 | 0.344597E+10 | 0.380307E+10 | 0.00 | 0.47 |
May | 0.225827E+11 | 0.00 | 0.00 | 39190038.68 | 40702197.86 | 0.00 | 0.249029E+11 | 0.00 | 0.68 |
June | 0.717256E+10 | 0.485973E+10 | 0.00 | 66762855.04 | 0.281156E+09 | 0.00 | 0.260286E+11 | 0.00 | 1.00 |
July | 0.311117E+10 | 0.172107E+11 | 0.00 | 45054553.31 | 0.118609E+10 | 0.00 | 0.103975E+11 | 0.00 | 0.94 |
August | 0.667725E+10 | 0.895820E+10 | 0.00 | 68385512.77 | 0.511429E+09 | 0.00 | 0.169250E+11 | 0.00 | 0.96 |
September | 0.184187E+11 | 0.303097E+10 | 0.00 | 35003500.59 | 92387885.75 | 0.00 | 0.158878E+11 | 0.00 | 0.77 |
October | 0.351721E+11 | 0.00 | 0.00 | 6037631.80 | 414021.41 | 0.204645E+10 | 0.497528E+10 | 0.00 | 0.48 |
November | 0.306089E+11 | 0.00 | 0.00 | 0.00 | 4095906.49 | 0.103668E+11 | 0.00 | 0.00 | 0.44 |
December | 0.732460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325891E+11 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.202270E+12 | 0.340596E+11 | 0.00 | 0.269550E+09 | 0.211628E+10 | 0.130396E+12 | 0.105171E+12 | 0.00 | 0.63 |
Minimum of Months | 0.311117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.357978E+11 | 0.172107E+11 | 0.00 | 68385512.77 | 0.118609E+10 | 0.348820E+11 | 0.260286E+11 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.738123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434454E+11 | 0.00 | 0.00 | 0.94 |
February | 0.120808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350294E+11 | 0.00 | 0.00 | 0.94 |
March | 0.408111E+11 | 0.00 | 0.00 | 4778059.12 | 0.00 | 0.146348E+11 | 0.238227E+10 | 0.00 | 0.98 |
April | 0.393999E+11 | 0.00 | 0.00 | 23552451.42 | 0.00 | 0.310302E+10 | 0.187902E+11 | 0.00 | 1.02 |
May | 0.314084E+11 | 0.00 | 0.00 | 54649269.93 | 54892961.35 | 11738736.44 | 0.356592E+11 | 0.00 | 1.43 |
June | 0.125274E+11 | 0.436563E+10 | 0.00 | 66988610.99 | 0.470263E+09 | 0.00 | 0.329847E+11 | 0.00 | 1.78 |
July | 0.482090E+10 | 0.147458E+11 | 0.00 | 60623111.88 | 0.248106E+10 | 0.00 | 0.151879E+11 | 0.00 | 1.66 |
August | 0.107815E+11 | 0.668850E+10 | 0.00 | 70014426.52 | 0.148499E+10 | 0.00 | 0.197048E+11 | 0.00 | 1.68 |
September | 0.253221E+11 | 0.223260E+10 | 0.00 | 44912408.69 | 0.777609E+09 | 7547401.22 | 0.223543E+11 | 0.00 | 1.51 |
October | 0.477677E+11 | 0.00 | 0.00 | 7187654.19 | 558369.39 | 0.232672E+10 | 0.658199E+10 | 0.00 | 1.00 |
November | 0.426669E+11 | 0.00 | 0.00 | 14519.76 | 5523938.47 | 0.123884E+11 | 0.107156E+09 | 0.00 | 0.91 |
December | 0.954329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424658E+11 | 0.00 | 0.00 | 0.93 |
Annual Sum or Average | 0.284511E+12 | 0.280325E+11 | 0.00 | 0.332721E+09 | 0.527490E+10 | 0.153413E+12 | 0.153753E+12 | 0.00 | 1.23 |
Minimum of Months | 0.482090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 |
Maximum of Months | 0.477677E+11 | 0.147458E+11 | 0.00 | 70014426.52 | 0.248106E+10 | 0.434454E+11 | 0.356592E+11 | 0.00 | 1.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.195631E+11 | 0.00 | 0.00 | 5340931.15 | 0.00 | 0.350182E+11 | 0.351388E+10 | 0.00 | 0.69 |
February | 0.206436E+11 | 0.00 | 0.00 | 11227493.03 | 0.00 | 0.285370E+11 | 0.576641E+10 | 0.00 | 0.71 |
March | 0.385956E+11 | 0.00 | 0.00 | 49807822.35 | 0.00 | 0.971365E+10 | 0.255876E+11 | 0.00 | 0.82 |
April | 0.402868E+11 | 0.00 | 0.00 | 46515425.70 | 0.00 | 0.390591E+10 | 0.336755E+11 | 0.00 | 0.86 |
May | 0.343690E+11 | 17208467.96 | 0.00 | 71725906.78 | 46652142.86 | 0.00 | 0.430192E+11 | 0.00 | 1.12 |
June | 0.160179E+11 | 0.545684E+10 | 0.00 | 75456306.04 | 0.554225E+09 | 0.00 | 0.305078E+11 | 0.00 | 1.33 |
July | 0.731064E+10 | 0.199179E+11 | 0.00 | 52812817.17 | 0.211346E+10 | 0.00 | 0.107472E+11 | 0.00 | 1.21 |
August | 0.121207E+11 | 0.111778E+11 | 0.00 | 0.103187E+09 | 0.856521E+09 | 0.00 | 0.223261E+11 | 0.00 | 1.40 |
September | 0.220990E+11 | 0.461670E+10 | 0.00 | 0.112773E+09 | 0.219819E+09 | 0.00 | 0.438360E+11 | 0.00 | 1.51 |
October | 0.376009E+11 | 323370.47 | 0.00 | 67979219.95 | 302539.32 | 0.158751E+10 | 0.424457E+11 | 0.00 | 0.99 |
November | 0.414860E+11 | 0.00 | 0.00 | 22670790.05 | 6192114.54 | 0.102034E+11 | 0.164380E+11 | 0.00 | 0.72 |
December | 0.224108E+11 | 0.00 | 0.00 | 4152603.48 | 0.00 | 0.344093E+11 | 0.231584E+10 | 0.00 | 0.68 |
Annual Sum or Average | 0.312504E+12 | 0.411867E+11 | 0.00 | 0.623649E+09 | 0.379717E+10 | 0.123375E+12 | 0.280179E+12 | 0.00 | 1.00 |
Minimum of Months | 0.731064E+10 | 0.00 | 0.00 | 4152603.48 | 0.00 | 0.00 | 0.231584E+10 | 0.00 | 0.68 |
Maximum of Months | 0.414860E+11 | 0.199179E+11 | 0.00 | 0.112773E+09 | 0.211346E+10 | 0.350182E+11 | 0.438360E+11 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416667E+11 | 0.00 | 0.00 | 0.99 |
February | 0.163288E+11 | 0.00 | 0.00 | 209284.50 | 0.00 | 0.330241E+11 | 0.184294E+09 | 0.00 | 0.99 |
March | 0.447150E+11 | 0.00 | 0.00 | 7111483.67 | 0.00 | 0.121762E+11 | 0.425101E+10 | 0.00 | 1.03 |
April | 0.458428E+11 | 0.00 | 0.00 | 19999805.48 | 0.00 | 0.275233E+10 | 0.163207E+11 | 0.00 | 1.10 |
May | 0.368978E+11 | 0.00 | 0.00 | 50158758.45 | 57851521.41 | 0.00 | 0.325941E+11 | 0.00 | 1.53 |
June | 0.149218E+11 | 0.480936E+10 | 0.00 | 77001029.58 | 0.586437E+09 | 0.00 | 0.285605E+11 | 0.00 | 1.89 |
July | 0.627787E+10 | 0.163021E+11 | 0.00 | 49439752.61 | 0.194608E+10 | 0.00 | 0.930896E+10 | 0.00 | 1.61 |
August | 0.122239E+11 | 0.825021E+10 | 0.00 | 71077043.66 | 0.978032E+09 | 0.00 | 0.155908E+11 | 0.00 | 1.70 |
September | 0.293936E+11 | 0.227453E+10 | 0.00 | 38736547.63 | 0.819186E+09 | 5384429.67 | 0.181263E+11 | 0.00 | 1.56 |
October | 0.518616E+11 | 0.00 | 0.00 | 9490556.00 | 588463.76 | 0.189282E+10 | 0.651065E+10 | 0.00 | 1.07 |
November | 0.471619E+11 | 0.00 | 0.00 | 492271.61 | 5821661.59 | 0.997019E+10 | 0.977847E+09 | 0.00 | 0.96 |
December | 0.172480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374653E+11 | 0.00 | 0.00 | 0.98 |
Annual Sum or Average | 0.334696E+12 | 0.316362E+11 | 0.00 | 0.323717E+09 | 0.439400E+10 | 0.138953E+12 | 0.132425E+12 | 0.00 | 1.29 |
Minimum of Months | 0.627787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
Maximum of Months | 0.518616E+11 | 0.163021E+11 | 0.00 | 77001029.58 | 0.194608E+10 | 0.416667E+11 | 0.325941E+11 | 0.00 | 1.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68751291.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370948E+10 | 0.00 | 0.00 | 0.52 |
February | 0.139507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348702E+10 | 0.00 | 0.00 | 0.54 |
March | 0.180050E+10 | 0.00 | 0.00 | 391725.18 | 0.00 | 0.252812E+10 | 0.160241E+09 | 0.00 | 0.58 |
April | 0.344746E+10 | 0.00 | 0.00 | 147977.29 | 0.00 | 0.102117E+10 | 0.190230E+09 | 0.00 | 0.56 |
May | 0.317012E+10 | 67479.35 | 0.00 | 2544855.00 | 3232802.47 | 87188882.68 | 0.179979E+10 | 0.00 | 0.72 |
June | 0.108811E+10 | 0.519545E+09 | 0.00 | 5950455.51 | 65145007.15 | 344899.87 | 0.240074E+10 | 0.00 | 1.07 |
July | 0.439335E+09 | 0.183861E+10 | 0.00 | 4063175.27 | 0.202737E+09 | 0.00 | 0.989101E+09 | 0.00 | 1.03 |
August | 0.894345E+09 | 0.974668E+09 | 0.00 | 6460655.33 | 84769721.89 | 0.00 | 0.152363E+10 | 0.00 | 1.03 |
September | 0.243406E+10 | 0.270335E+09 | 0.00 | 2374568.80 | 42787678.35 | 55340775.17 | 0.107844E+10 | 0.00 | 0.81 |
October | 0.338998E+10 | 0.00 | 0.00 | 129506.63 | 263993.32 | 0.920048E+09 | 0.152695E+09 | 0.00 | 0.57 |
November | 0.169311E+10 | 0.00 | 3361649.62 | 0.00 | 281364.23 | 0.223706E+10 | 0.00 | 55636.16 | 0.54 |
December | 0.246098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353919E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.188114E+11 | 0.360322E+10 | 3361649.62 | 22062919.01 | 0.399217E+09 | 0.175850E+11 | 0.829488E+10 | 55636.16 | 0.71 |
Minimum of Months | 68751291.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.344746E+10 | 0.183861E+10 | 3361649.62 | 6460655.33 | 0.202737E+09 | 0.370948E+10 | 0.240074E+10 | 55636.16 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 87599557.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390837E+10 | 0.00 | 0.00 | 0.87 |
February | 0.648612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314332E+10 | 0.00 | 0.00 | 0.88 |
March | 0.288669E+10 | 0.00 | 0.00 | 384057.58 | 0.00 | 0.186839E+10 | 0.159479E+09 | 0.00 | 0.98 |
April | 0.324842E+10 | 0.00 | 0.00 | 1548299.03 | 0.00 | 0.768136E+09 | 0.136302E+10 | 0.00 | 1.00 |
May | 0.289485E+10 | 75709.44 | 0.00 | 4832995.43 | 3627089.89 | 51707221.15 | 0.330884E+10 | 0.00 | 1.38 |
June | 0.111236E+10 | 0.475258E+09 | 0.00 | 6933223.43 | 65018280.71 | 0.00 | 0.335064E+10 | 0.00 | 1.84 |
July | 0.407750E+09 | 0.161145E+10 | 0.00 | 5989633.57 | 0.301774E+09 | 0.00 | 0.159021E+10 | 0.00 | 1.77 |
August | 0.949834E+09 | 0.744361E+09 | 0.00 | 7448690.12 | 0.158970E+09 | 0.00 | 0.197699E+10 | 0.00 | 1.74 |
September | 0.220700E+10 | 0.212104E+09 | 0.00 | 4124137.38 | 87445612.46 | 48902955.04 | 0.208056E+10 | 0.00 | 1.47 |
October | 0.392691E+10 | 0.00 | 0.00 | 292673.46 | 296191.16 | 0.762676E+09 | 0.315306E+09 | 0.00 | 0.99 |
November | 0.213064E+10 | 0.00 | 3356449.96 | 0.00 | 730913.14 | 0.224597E+10 | 0.00 | 28930.14 | 0.93 |
December | 0.292366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373046E+10 | 0.00 | 0.00 | 0.88 |
Annual Sum or Average | 0.207930E+11 | 0.304325E+10 | 3356449.96 | 31553710.00 | 0.617863E+09 | 0.165279E+11 | 0.141451E+11 | 28930.14 | 1.23 |
Minimum of Months | 87599557.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Maximum of Months | 0.392691E+10 | 0.161145E+10 | 3356449.96 | 7448690.12 | 0.301774E+09 | 0.390837E+10 | 0.335064E+10 | 28930.14 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109972E+10 | 0.00 | 0.00 | 189019.14 | 0.00 | 0.364119E+10 | 0.125519E+09 | 0.00 | 0.68 |
February | 0.138292E+10 | 0.00 | 0.00 | 648428.74 | 0.00 | 0.299146E+10 | 0.351397E+09 | 0.00 | 0.70 |
March | 0.313596E+10 | 0.00 | 0.00 | 3397363.59 | 0.00 | 0.155997E+10 | 0.171908E+10 | 0.00 | 0.83 |
April | 0.348981E+10 | 0.00 | 0.00 | 3518538.67 | 0.00 | 0.938568E+09 | 0.283622E+10 | 0.00 | 0.87 |
May | 0.355241E+10 | 900866.89 | 0.00 | 6022768.05 | 3691731.14 | 0.119567E+09 | 0.399104E+10 | 0.00 | 1.11 |
June | 0.178322E+10 | 0.576814E+09 | 0.00 | 7399724.61 | 0.110637E+09 | 2957446.60 | 0.304352E+10 | 0.00 | 1.41 |
July | 0.757773E+09 | 0.217025E+10 | 0.00 | 5226361.72 | 0.325435E+09 | 0.00 | 0.116139E+10 | 0.00 | 1.33 |
August | 0.127583E+10 | 0.122233E+10 | 0.00 | 10702731.26 | 0.125789E+09 | 0.00 | 0.224518E+10 | 0.00 | 1.49 |
September | 0.225361E+10 | 0.428107E+09 | 0.00 | 9959926.97 | 45132640.65 | 59159157.89 | 0.408273E+10 | 0.00 | 1.50 |
October | 0.349539E+10 | 75040.39 | 0.00 | 4945270.72 | 294172.24 | 0.655478E+09 | 0.318340E+10 | 0.00 | 0.97 |
November | 0.276766E+10 | 0.00 | 2052490.38 | 1165094.54 | 2826739.14 | 0.189062E+10 | 0.889835E+09 | 16356.73 | 0.75 |
December | 0.951075E+09 | 0.00 | 0.00 | 105581.88 | 0.00 | 0.384628E+10 | 89503820.23 | 0.00 | 0.69 |
Annual Sum or Average | 0.259454E+11 | 0.439848E+10 | 2052490.38 | 53280809.89 | 0.613805E+09 | 0.157052E+11 | 0.237188E+11 | 16356.73 | 1.03 |
Minimum of Months | 0.757773E+09 | 0.00 | 0.00 | 105581.88 | 0.00 | 0.00 | 89503820.23 | 0.00 | 0.68 |
Maximum of Months | 0.355241E+10 | 0.217025E+10 | 2052490.38 | 10702731.26 | 0.325435E+09 | 0.384628E+10 | 0.408273E+10 | 16356.73 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.536768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388479E+10 | 0.00 | 0.00 | 0.96 |
February | 0.916322E+09 | 0.00 | 0.00 | 3593.46 | 0.00 | 0.326214E+10 | 10569919.99 | 0.00 | 0.97 |
March | 0.340770E+10 | 0.00 | 0.00 | 524954.86 | 0.00 | 0.170604E+10 | 0.339790E+09 | 0.00 | 1.09 |
April | 0.406367E+10 | 0.00 | 0.00 | 1629531.45 | 0.00 | 0.644756E+09 | 0.141988E+10 | 0.00 | 1.14 |
May | 0.405263E+10 | 84044.18 | 0.00 | 4407253.92 | 4026390.56 | 30801140.81 | 0.287138E+10 | 0.00 | 1.54 |
June | 0.161298E+10 | 0.503998E+09 | 0.00 | 8220316.96 | 0.114159E+09 | 0.00 | 0.289604E+10 | 0.00 | 2.01 |
July | 0.658886E+09 | 0.173077E+10 | 0.00 | 4854710.44 | 0.318329E+09 | 0.00 | 0.962142E+09 | 0.00 | 1.75 |
August | 0.126762E+10 | 0.901245E+09 | 0.00 | 7447462.34 | 0.135328E+09 | 0.00 | 0.151571E+10 | 0.00 | 1.80 |
September | 0.304111E+10 | 0.200122E+09 | 0.00 | 3354813.34 | 0.111329E+09 | 51962614.22 | 0.153005E+10 | 0.00 | 1.59 |
October | 0.443183E+10 | 0.00 | 0.00 | 728150.35 | 328798.38 | 0.604451E+09 | 0.560267E+09 | 0.00 | 1.11 |
November | 0.296306E+10 | 0.00 | 1584858.44 | 2260.01 | 2919530.61 | 0.186403E+10 | 27049663.29 | 6472.40 | 1.03 |
December | 0.762439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368361E+10 | 0.00 | 0.00 | 0.97 |
Annual Sum or Average | 0.277150E+11 | 0.333622E+10 | 1584858.44 | 31173047.13 | 0.686420E+09 | 0.157326E+11 | 0.121329E+11 | 6472.40 | 1.33 |
Minimum of Months | 0.536768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
Maximum of Months | 0.443183E+10 | 0.173077E+10 | 1584858.44 | 8220316.96 | 0.318329E+09 | 0.388479E+10 | 0.289604E+10 | 6472.40 | 2.01 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2326252.35 | 0.00 | 0.00 | 0.828933E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6715577.96 | 0.00 | 0.00 | 0.752850E+09 | 0.00 | 0.28 |
March | 0.00 | 294149.81 | 0.00 | 14330506.47 | 0.00 | 0.00 | 0.662451E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 17455581.46 | 0.00 | 0.00 | 0.504184E+09 | 0.00 | 0.29 |
May | 0.00 | 183021.71 | 0.00 | 3969575.85 | 0.00 | 0.00 | 0.362464E+09 | 0.00 | 0.29 |
June | 0.00 | 56713153.89 | 0.00 | 5595743.97 | 0.00 | 0.00 | 0.161484E+09 | 0.00 | 0.30 |
July | 0.00 | 0.160572E+09 | 0.00 | 3077090.80 | 0.00 | 0.00 | 29007477.61 | 0.00 | 0.28 |
August | 0.00 | 82100673.65 | 0.00 | 10202154.38 | 0.00 | 0.00 | 76399010.67 | 0.00 | 0.31 |
September | 0.00 | 22572419.21 | 0.00 | 3079672.56 | 0.00 | 0.00 | 0.198709E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8209827.87 | 0.00 | 0.00 | 0.445566E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12116060.33 | 0.00 | 0.00 | 0.565136E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16610854.77 | 0.00 | 0.00 | 0.761911E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.322436E+09 | 0.00 | 0.103689E+09 | 0.00 | 0.00 | 0.534910E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2326252.35 | 0.00 | 0.00 | 29007477.61 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.160572E+09 | 0.00 | 17455581.46 | 0.00 | 0.00 | 0.828933E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.273412E+10 | 0.00 | 0.00 | 6567044.23 | 0.00 | 0.00 | 0.549734E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 48346013.74 | 0.00 | 0.00 | 0.754708E+10 | 0.00 | 0.28 |
March | 0.00 | 2786288.68 | 0.00 | 0.122913E+09 | 0.00 | 0.00 | 0.664482E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.157870E+09 | 0.00 | 0.00 | 0.505651E+10 | 0.00 | 0.29 |
May | 0.00 | 1616262.15 | 0.00 | 33292627.09 | 0.00 | 0.00 | 0.363627E+10 | 0.00 | 0.29 |
June | 0.00 | 0.562261E+09 | 0.00 | 52014424.93 | 0.00 | 0.00 | 0.161766E+10 | 0.00 | 0.30 |
July | 0.00 | 0.160151E+10 | 0.00 | 29117905.54 | 0.00 | 0.00 | 0.291215E+09 | 0.00 | 0.28 |
August | 0.00 | 0.819998E+09 | 0.00 | 96676478.07 | 0.00 | 0.00 | 0.767039E+09 | 0.00 | 0.31 |
September | 0.00 | 0.216233E+09 | 0.00 | 26085385.44 | 0.00 | 0.00 | 0.200305E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 69273794.87 | 0.00 | 0.00 | 0.446809E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.103171E+09 | 0.00 | 0.00 | 0.566612E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.140193E+09 | 0.00 | 0.00 | 0.764298E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.273412E+10 | 0.320440E+10 | 0.00 | 0.885520E+09 | 0.00 | 0.00 | 0.508382E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6567044.23 | 0.00 | 0.00 | 0.291215E+09 | 0.00 | 0.28 |
Maximum of Months | 0.273412E+10 | 0.160151E+10 | 0.00 | 0.157870E+09 | 0.00 | 0.00 | 0.764298E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.557804E+09 | 0.00 | 0.00 | 226861.60 | 0.00 | 0.00 | 0.248835E+09 | 0.00 | 0.28 |
February | 506890.94 | 0.00 | 0.00 | 4099148.98 | 0.00 | 0.00 | 0.754869E+09 | 0.00 | 0.28 |
March | 0.00 | 271777.75 | 0.00 | 11346353.23 | 0.00 | 0.00 | 0.665529E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15130366.27 | 0.00 | 0.00 | 0.506403E+09 | 0.00 | 0.29 |
May | 0.00 | 167352.96 | 0.00 | 3017776.26 | 0.00 | 0.00 | 0.364458E+09 | 0.00 | 0.29 |
June | 0.00 | 56219147.26 | 0.00 | 5139382.52 | 0.00 | 0.00 | 0.162023E+09 | 0.00 | 0.30 |
July | 0.00 | 0.160014E+09 | 0.00 | 2903850.77 | 0.00 | 0.00 | 29201228.25 | 0.00 | 0.28 |
August | 0.00 | 81854055.19 | 0.00 | 9639344.17 | 0.00 | 0.00 | 76929968.50 | 0.00 | 0.31 |
September | 0.00 | 21499687.37 | 0.00 | 2358240.06 | 0.00 | 0.00 | 0.201545E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6153314.05 | 0.00 | 0.00 | 0.447989E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9324875.70 | 0.00 | 0.00 | 0.567769E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13044965.85 | 0.00 | 0.00 | 0.765355E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.558310E+09 | 0.320026E+09 | 0.00 | 82384479.45 | 0.00 | 0.00 | 0.479091E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 226861.60 | 0.00 | 0.00 | 29201228.25 | 0.00 | 0.28 |
Maximum of Months | 0.557804E+09 | 0.160014E+09 | 0.00 | 15130366.27 | 0.00 | 0.00 | 0.765355E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.208845E+09 | 0.00 | 0.00 | 0.217272E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.402383E+09 | 0.00 | 0.00 | 0.196733E+11 | 0.00 | 0.32 |
March | 0.00 | 7335960.57 | 0.00 | 0.739449E+09 | 0.00 | 0.00 | 0.167363E+11 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.00 | 0.873110E+09 | 0.00 | 0.00 | 0.115246E+11 | 0.00 | 0.33 |
May | 0.00 | 6830631.43 | 0.00 | 0.214351E+09 | 0.00 | 0.00 | 0.829206E+10 | 0.00 | 0.33 |
June | 0.00 | 0.133471E+10 | 0.00 | 0.272230E+09 | 0.00 | 0.00 | 0.345098E+10 | 0.00 | 0.34 |
July | 0.00 | 0.358755E+10 | 0.00 | 0.144503E+09 | 0.00 | 0.00 | 0.560656E+09 | 0.00 | 0.32 |
August | 0.00 | 0.153590E+10 | 0.00 | 0.518132E+09 | 0.00 | 0.00 | 0.152440E+10 | 0.00 | 0.34 |
September | 0.00 | 0.612066E+09 | 0.00 | 0.164446E+09 | 0.00 | 0.00 | 0.415645E+10 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.00 | 0.432508E+09 | 0.00 | 0.00 | 0.990307E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.629421E+09 | 0.00 | 0.00 | 0.131006E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.871292E+09 | 0.00 | 0.00 | 0.190931E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.708440E+10 | 0.00 | 0.547067E+10 | 0.00 | 0.00 | 0.129743E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.144503E+09 | 0.00 | 0.00 | 0.560656E+09 | 0.00 | 0.32 |
Maximum of Months | 0.00 | 0.358755E+10 | 0.00 | 0.873110E+09 | 0.00 | 0.00 | 0.217272E+11 | 0.00 | 0.34 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:03:17
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.271207E+12 | 0.513660E+11 | 0.00 | 0.204364E+13 | 0.572634E+12 |
February | 0.409667E+12 | 0.541319E+11 | 0.00 | 0.189065E+13 | 0.851860E+12 |
March | 0.608411E+12 | 0.341250E+11 | 0.00 | 0.214561E+13 | 0.137172E+13 |
April | 0.729836E+12 | 0.276554E+11 | 0.00 | 0.217515E+13 | 0.167488E+13 |
May | 0.896512E+12 | 0.159771E+11 | 0.00 | 0.207522E+13 | 0.819340E+12 |
June | 0.961512E+12 | 0.672415E+10 | 0.00 | 0.115670E+13 | 0.205260E+13 |
July | 0.892171E+12 | -659167166.8 | 0.00 | 0.174691E+12 | 0.323108E+13 |
August | 0.764386E+12 | 0.297299E+10 | 0.00 | 0.827901E+12 | 0.331797E+13 |
September | 0.582981E+12 | 0.910808E+10 | 0.00 | 0.166179E+13 | 0.126798E+13 |
October | 0.394472E+12 | 0.212389E+11 | 0.00 | 0.218815E+13 | 0.101945E+13 |
November | 0.216668E+12 | 0.292104E+11 | 0.00 | 0.205368E+13 | 0.129272E+13 |
December | 0.244613E+12 | 0.546202E+11 | 0.00 | 0.207562E+13 | 0.171644E+13 |
Annual Sum or Average | 0.697243E+13 | 0.306471E+12 | 0.00 | 0.204688E+14 | 0.191887E+14 |
Minimum of Months | 0.216668E+12 | -659167166.8 | 0.00 | 0.174691E+12 | 0.572634E+12 |